Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280
Simulation Timestamp: 2024-07-03 12:21:40
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:40
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 10918.22 | 962.36 | 962.36 |
Net Site Energy | 10918.22 | 962.36 | 962.36 |
Total Source Energy | 22050.80 | 1943.61 | 1943.61 |
Net Source Energy | 22050.80 | 1943.61 | 1943.61 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1422.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 546.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 781.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 193.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1658.18 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 813.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 511.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 71.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 170.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 94.78 | 2802.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | 61.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 4904.20 | 6014.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 1422.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 546.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 781.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 193.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 872.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 14.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 8.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 21.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 789.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 2.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 511.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 71.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 170.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 94.78 | 2802.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5742.51 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.69 | |
Refrigeration | General | 7.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 20.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 34.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1422.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 546.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 781.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 193.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 1658.18 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 813.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 511.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 71.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 170.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 94.78 | 2802.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | Unassigned | 61.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 85.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 107.94 | 372.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 238.34 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 432.27 | 530.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 85.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 107.94 | 372.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 238.34 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 432.27 | 530.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 4904.200 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 4904.200 | 100.00 |
Total On-Site and Utility Electric Sources | 4904.200 | 100.00 |
Total Electricity End Uses | 4904.200 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 150.88 | 3.68 |
Air to Air Heat Recovery for Heating | 3943.90 | 96.32 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 4094.78 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9857.19 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9857.19 | 100.00 |
Total Water End Uses | 9857.19 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 17.67 |
Time Setpoint Not Met During Occupied Cooling | 37.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 7821.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER1 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| FLR_3_DOAS COOLING COIL | VAV WITH REHEAT COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH LAUNDRY G WATER HEATER | SWH BOOSTER E WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |CoilReportMonthly
| FLR_3_DOAS HEATING COIL | VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | FLR_3_DOAS COOLING COIL | VAV WITH REHEAT COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |FanReportMonthly
| FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL_FANCOILFAN | ROOM_2_FLR_3 FAN COIL_FANCOILFAN | ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | ROOM_5_FLR_3 FAN COIL_FANCOILFAN | ROOM_6_FLR_3 FAN COIL_FANCOILFAN | ROOM_1_FLR_6 FAN COIL_FANCOILFAN | ROOM_2_FLR_6 FAN COIL_FANCOILFAN | ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| FLR_3_DOAS | VAV WITH REHEAT |AirLoopSystemComponentLoadsMonthly
| FLR_3_DOAS | VAV WITH REHEAT |AirLoopSystemComponentEnergyUseMonthly
| FLR_3_DOAS | VAV WITH REHEAT |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:40
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21 |
RunPeriod | RUNPERIOD 1 |
Weather File | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
Latitude [deg] | 42.93 |
Longitude [deg] | -78.7 |
Elevation [m] | 215.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 8.8143 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.26 | 23.26 | 11.3140 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 11.3140 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 4.6285 | 61.93 | 5.3800 |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 5.7199 | 46.45 | 2.6900 |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 4.6285 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.50 | 65.50 | 10.0104 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.08 | 85.08 | 10.7639 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 8.2882 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 8.2882 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 7.1042 | 18.58 | 0.0000 |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.74 | 6.74 | 8.2882 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 10.0104 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 10.0104 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.37 | 26.37 | 11.4097 | 4.65 | 2934.4875 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.20 | 28.20 | 7.1042 | 18.58 | 0.0000 |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 8.5566 | 7.07 | 41.0709 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 8.5566 | 7.07 | 41.0709 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 1978.83 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 8.8143 | 18.58 | 5.3800 | |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 1.00 | RETAIL_1_FLR_1 | GENERAL | RETAIL_1_FLR_1 | 11.3140 | 6.19 | 10.7600 | |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 1.00 | RETAIL_2_FLR_1 | GENERAL | RETAIL_2_FLR_1 | 11.3140 | 6.19 | 10.7600 | |
MECH_FLR_1 | 164.24 | Yes | Yes | 1.00 | MECH_FLR_1 | GENERAL | MECH_FLR_1 | 4.6285 | 61.93 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 1.00 | STORAGE_FLR_1 | GENERAL | STORAGE_FLR_1 | 5.7199 | 46.45 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 1.00 | LAUNDRY_FLR_1 | GENERAL | LAUNDRY_FLR_1 | 4.6285 | 9.29 | 597.5300 | |
CAFE_FLR_1 | 188.86 | Yes | Yes | 1.00 | CAFE_FLR_1 | GENERAL | CAFE_FLR_1 | 10.0104 | 1.33 | 5.3800 | |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 1.00 | LOBBY_FLR_1 | GENERAL | LOBBY_FLR_1 | 10.7639 | 3.10 | 8.0700 | |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_1_FLR_3 | GENERAL | ROOM_1_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_2_FLR_3 | GENERAL | ROOM_2_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 76.00 | ROOM_3_MULT19_FLR_3 | GENERAL | ROOM_3_MULT19_FLR_3 | 8.2882 | 16.35 | 10.5200 | |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 76.00 | ROOM_4_MULT19_FLR_3 | GENERAL | ROOM_4_MULT19_FLR_3 | 8.2882 | 16.35 | 10.5200 | |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_5_FLR_3 | GENERAL | ROOM_5_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_6_FLR_3 | GENERAL | ROOM_6_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 4.00 | CORRIDOR_FLR_3 | GENERAL | CORRIDOR_FLR_3 | 7.1042 | 18.58 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_1_FLR_6 | GENERAL | ROOM_1_FLR_6 | 8.2882 | 26.01 | 6.7500 | |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_2_FLR_6 | GENERAL | ROOM_2_FLR_6 | 8.2882 | 26.01 | 6.7500 | |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 9.00 | ROOM_3_MULT9_FLR_6 | GENERAL | ROOM_3_MULT9_FLR_6 | 8.2882 | 16.35 | 10.5200 | |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1.00 | BANQUET_FLR_6 | GENERAL | BANQUET_FLR_6 | 10.0104 | 1.33 | 67.8200 | |
DINING_FLR_6 | 331.66 | Yes | Yes | 1.00 | DINING_FLR_6 | GENERAL | DINING_FLR_6 | 10.0104 | 1.33 | 67.8200 | |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 1.00 | KITCHEN_FLR_6 | GENERAL | KITCHEN_FLR_6 | 11.4097 | 4.65 | 2934.4875 | |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1.00 | CORRIDOR_FLR_6 | GENERAL | CORRIDOR_FLR_6 | 7.1042 | 18.58 | 0.0000 | |
Total | 11345.29 | 8.5566 | 3.54 | 41.0709 | |||||||
Conditioned Total | 11345.29 | 8.5566 | 3.54 | 41.0709 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 11345.29 | 11345.29 | 0.00 | 0.00 | 4.6520 | 8.82 | 37.1989 |
Total | 11345.29 | 11345.29 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:40
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 21-JUL-19:00 | 06-FEB-19:19 | - | - | - | - | - | - | - | - | - | - | 05-JUN-20:10 |
Heating | 0.00 | 260378.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 158511.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 64632.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 12338.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 86439.81 | 87619.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 10999.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 28498.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 4349.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 3963.48 | 253065.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1875.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 381548.78 | 601063.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 260378.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 158511.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 64632.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 12338.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 56456.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 49984.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 37635.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1249.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 9600.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 150.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 28498.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 4349.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 3963.48 | 253065.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 536.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1098.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:40
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1542.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1731.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2475.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 613.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5251.45 | 1939.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2577.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1620.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 226.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 539.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 300.18 | 3038.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 195.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 15531.60 | 6519.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 135.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 152.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 218.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 54.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 462.88 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 227.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 142.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 19.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 47.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 26.46 | 267.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1368.99 | 574.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 135.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 152.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 218.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 54.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 462.88 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 227.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 142.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 19.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 47.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 26.46 | 267.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1368.99 | 574.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:40
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
BASEMENT VAV BOX COMPONENT | 2.49 | 0.606060 | 0.521000 | 1.30 | 1.00 | 0.500000 | 0.000629 | 0.000072 | 1.30 | 16.70 | 0.008000 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.377851 | 0.135261 | 0.521000 | 0.196860 | 0.521000 | 0.500000 | 0.002817 | 0.000035 | 0.196860 | 16.70 | 0.008000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.230093 | 0.257217 | 0.521000 | 0.119878 | 0.685912 | 0.500000 | 0.001481 | 0.000014 | 0.119878 | 16.70 | 0.008000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.180993 | 0.691482 | 0.521000 | 0.094297 | 1.00 | 0.500000 | 0.000551 | 0.000019 | 0.094297 | 16.70 | 0.008000 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.107812 | 0.669748 | 0.521000 | 0.056170 | 1.00 | 0.500000 | 0.000569 | 0.000013 | 0.056170 | 16.70 | 0.008000 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 3.33 | 0.017875 | 0.521000 | 1.73 | 0.521000 | 0.500000 | 0.021315 | 0.000098 | 1.73 | 16.70 | 0.008000 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.58 | 0.091018 | 0.521000 | 0.823773 | 0.521000 | 0.500000 | 0.004186 | 0.000104 | 0.823773 | 16.70 | 0.008000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 4.96 | 0.200985 | 0.521000 | 2.58 | 0.535960 | 0.500000 | 0.001896 | 0.000270 | 2.58 | 16.70 | 0.008000 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.56 | 0.759782 | 0.521000 | 0.813888 | 1.00 | 0.500000 | 0.000501 | 0.000130 | 0.813888 | 16.70 | 0.008000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.18 | 0.115880 | 0.521000 | 1.14 | 0.521000 | 0.500000 | 0.003288 | 0.000111 | 1.14 | 16.70 | 0.008000 |
DINING_FLR_6 VAV BOX COMPONENT | 2.29 | 0.110547 | 0.521000 | 1.19 | 0.521000 | 0.500000 | 0.003446 | 0.000114 | 1.19 | 16.70 | 0.008000 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.31 | 0.061359 | 0.521000 | 1.20 | 0.521000 | 0.500000 | 0.011168 | 0.000075 | 1.20 | 16.70 | 0.008000 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 0.776261 | 0.404553 | 0.521000 | 0.404432 | 1.00 | 0.500000 | 0.000942 | 0.000081 | 0.404432 | 16.70 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
BASEMENT VAV BOX REHEAT COIL | 8202.15 | 0.000072 | 173.10 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 4024.00 | 0.000035 | 99.52 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1596.34 | 0.000014 | 36.30 |
MECH_FLR_1 VAV BOX REHEAT COIL | 2220.65 | 0.000019 | 57.14 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 1522.88 | 0.000013 | 41.11 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 11195.84 | 0.000098 | 236.60 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 11939.67 | 0.000104 | 275.14 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 30876.16 | 0.000270 | 691.55 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | 6689.32 | 0.000059 | 191.14 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | 6688.95 | 0.000059 | 191.13 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 38389.09 | 0.000336 | 1096.89 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 38400.26 | 0.000336 | 1097.21 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | 6664.69 | 0.000058 | 190.43 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | 6664.32 | 0.000058 | 190.42 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 14814.82 | 0.000130 | 356.51 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | 2050.30 | 0.000018 | 58.58 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | 2050.17 | 0.000018 | 58.58 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 9844.16 | 0.000086 | 281.27 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 12643.30 | 0.000111 | 280.64 |
DINING_FLR_6 VAV BOX REHEAT COIL | 13072.10 | 0.000114 | 289.68 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 8607.09 | 0.000075 | 183.21 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 9229.31 | 0.000081 | 235.26 |
FLR_3_DOAS HEATING COIL | 23955.95 | 0.000210 | 376.64 |
VAV WITH REHEAT HEATING COIL | 259723.04 | 0.002272 | 4083.44 |
Design Size Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 0.061735 |
ROOM_2_FLR_3 DIRECT AIR | 0.061728 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 0.837072 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 0.837300 |
ROOM_5_FLR_3 DIRECT AIR | 0.061735 |
ROOM_6_FLR_3 DIRECT AIR | 0.061728 |
ROOM_1_FLR_6 DIRECT AIR | 0.015434 |
ROOM_2_FLR_6 DIRECT AIR | 0.015432 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 0.099154 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Hot Water Flow [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 1.15 | 0.000059 | 0.000361 |
ROOM_2_FLR_3 FAN COIL | 1.11 | 0.000059 | 0.000350 |
ROOM_3_MULT19_FLR_3 FAN COIL | 7.10 | 0.000336 | 0.002185 |
ROOM_4_MULT19_FLR_3 FAN COIL | 6.09 | 0.000336 | 0.002000 |
ROOM_5_FLR_3 FAN COIL | 1.05 | 0.000058 | 0.000331 |
ROOM_6_FLR_3 FAN COIL | 1.02 | 0.000058 | 0.000321 |
ROOM_1_FLR_6 FAN COIL | 0.299973 | 0.000018 | 0.000094 |
ROOM_2_FLR_6 FAN COIL | 0.289821 | 0.000018 | 0.000091 |
ROOM_3_MULT9_FLR_6 FAN COIL | 1.41 | 0.000086 | 0.000449 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COIL_FANCOILFAN | 1.15 |
ROOM_2_FLR_3 FAN COIL_FANCOILFAN | 1.11 |
ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | 7.10 |
ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | 6.09 |
ROOM_5_FLR_3 FAN COIL_FANCOILFAN | 1.05 |
ROOM_6_FLR_3 FAN COIL_FANCOILFAN | 1.02 |
ROOM_1_FLR_6 FAN COIL_FANCOILFAN | 0.299973 |
ROOM_2_FLR_6 FAN COIL_FANCOILFAN | 0.289821 |
ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN | 1.41 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Coil Load [W] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008606 | 12.80 | 0.008500 | 0.000361 | 1.15 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008609 | 12.80 | 0.008500 | 0.000350 | 1.11 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008535 | 12.80 | 0.008500 | 0.002185 | 7.10 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008776 | 12.80 | 0.008500 | 0.002000 | 6.09 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008616 | 12.80 | 0.008500 | 0.000331 | 1.05 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008620 | 12.80 | 0.008500 | 0.000321 | 1.02 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008602 | 12.80 | 0.008500 | 0.000094 | 0.299973 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008605 | 12.80 | 0.008500 | 0.000091 | 0.289821 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008658 | 12.80 | 0.008500 | 0.000449 | 1.41 | |
FLR_3_DOAS COOLING COIL | 30.30 | 6.70 | 0.013367 | 11.91 | 0.008500 | 0.002150 | 2.05 | 75158.60 |
VAV WITH REHEAT COOLING COIL | 27.30 | 6.70 | 0.011607 | 10.94 | 0.008500 | 0.018387 | 22.24 | 642888.98 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
VAV WITH REHEAT | 11.65 | 11.65 | 22.37 | 11.65 | 22.24 | 22.24 | 0.300000 | 0.523943 | 22.24 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
VAV WITH REHEAT_OA_CONTROLLER | 22.24 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
FLR_3_DOAS OA HEAT RECOVERY | 2.05 |
VAV WITH REHEAT OA HEAT RECOVERY | 11.66 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS FAN | 2.05 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.002150 | 0.000222 |
FLR_3_DOAS_HEATC_CONTROLLER | 0.000210 | |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.018387 | 0.000026 |
VAV WITH REHEAT_HEATC_CONTROLLER | 0.002272 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT FAN | 22.24 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.026720 | 4362.48 | |
HEATSYS1 PUMP | 0.004646 | 1399.17 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.004646 | 0.557518 |
COOLSYS1 | 0.026720 | 3.21 |
SWHSYS1 | 0.000375 | 0.045004 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 531064.59 | 531064.59 | 0.004646 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.026720 | 3020.29 |
SWHSYS1 PUMP | 0.000375 | 47.91 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.026720 | 934252.62 | 934867.06 | 106.57 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000375 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:40
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:40
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:40
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 9.70 | 6.00 | -2.20 | -3.40 | -4.20 | 2.70 | 7.50 | 13.70 | 18.60 | 22.00 | 20.70 | 16.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 | 42.93 | -78.73 | -5.00 | 215.00 | 98769 | 1.1739 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 8.97 | 26.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.58 | 23.26 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.72 | 65.50 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.80 | 85.08 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.70 | 6.74 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.96 | 26.37 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.27 | 28.20 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 8.814 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 14.194 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 11.314 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 22.074 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 11.314 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 22.074 | No |
4 | MECH_FLR_1 | 164.24 | 2.7 | 61.932 | 1.615E-002 | 4.628 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 10.008 | No |
5 | STORAGE_FLR_1 | 94.76 | 2.0 | 46.451 | 2.153E-002 | 5.720 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 8.410 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 4.628 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 602.158 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 10.010 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 15.390 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 10.764 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.834 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 8.288 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 18.808 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 8.288 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 18.808 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 21.0 | 18.581 | 5.382E-002 | 7.104 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.104 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 8.288 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 18.808 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 10.010 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 77.830 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 10.010 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 77.830 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 11.410 | 515.227 | 2419.260 | 0.000 | 0.000 | 0.000 | 2945.897 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 22.2 | 18.581 | 5.382E-002 | 7.104 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.104 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | STORAGE_FLR_1 PEOPLE | BLDG_OCC_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.0 | 2.153E-002 | 46.451 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | CORRIDOR_FLR_3 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 21.0 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 21 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
21 | CORRIDOR_FLR_6 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 22.2 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
22 | MECH_FLR_1 PEOPLE | BLDG_OCC_SCH | MECH_FLR_1 | 164.24 | 2.7 | 2.7 | 1.615E-002 | 61.932 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 3 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_BASEMENT | BASEMENT | 1978.83 | 106.5 | 17441.963 | 8.814 | 163.776 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 17441.963 |
2 | RETAIL_1_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_1_FLR_1 | 67.07 | 10.8 | 758.849 | 11.314 | 70.076 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 758.849 |
3 | RETAIL_2_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_2_FLR_1 | 77.67 | 12.5 | 878.750 | 11.314 | 70.076 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 878.750 |
4 | MECH_FLR_1_LIGHTS | LTG_SCH_MECHANIC | MECH_FLR_1 | 164.24 | 2.7 | 760.196 | 4.628 | 286.650 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 760.196 |
5 | STORAGE_FLR_1_LIGHTS | LTG_SCH_STORAGE | STORAGE_FLR_1 | 94.76 | 2.0 | 542.017 | 5.720 | 265.695 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 542.017 |
6 | LAUNDRY_FLR_1_LIGHTS | LTG_SCH_LAUNDRY | LAUNDRY_FLR_1 | 78.04 | 8.4 | 361.204 | 4.628 | 43.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 361.204 |
7 | CAFE_FLR_1_LIGHTS | LTG_SCH_DINING | CAFE_FLR_1 | 188.86 | 142.3 | 1890.589 | 10.010 | 13.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1890.589 |
8 | LOBBY_FLR_1_LIGHTS | LTG_SCH_LOBBY | LOBBY_FLR_1 | 1308.19 | 422.4 | 14081.185 | 10.764 | 33.333 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14081.185 |
9 | ROOM_1_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_3 | 39.02 | 1.5 | 323.422 | 8.288 | 215.615 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.422 |
10 | ROOM_2_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_3 | 39.02 | 1.5 | 323.384 | 8.288 | 215.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.384 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 203.259 | 8.288 | 135.506 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 203.259 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 203.314 | 8.288 | 135.543 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 203.314 |
13 | ROOM_5_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_5_FLR_3 | 39.02 | 1.5 | 323.422 | 8.288 | 215.615 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.422 |
14 | ROOM_6_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_6_FLR_3 | 39.02 | 1.5 | 323.384 | 8.288 | 215.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.384 |
15 | CORRIDOR_FLR_3_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2766.397 | 7.104 | 132.003 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2766.397 |
16 | ROOM_1_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_6 | 39.02 | 1.5 | 323.422 | 8.288 | 215.615 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.422 |
17 | ROOM_2_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_6 | 39.02 | 1.5 | 323.384 | 8.288 | 215.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.384 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 203.314 | 8.288 | 135.543 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 203.314 |
19 | BANQUET_FLR_6_LIGHTS | LTG_SCH_DINING | BANQUET_FLR_6 | 331.66 | 249.9 | 3320.034 | 10.010 | 13.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3320.034 |
20 | DINING_FLR_6_LIGHTS | LTG_SCH_DINING | DINING_FLR_6 | 331.66 | 249.9 | 3320.034 | 10.010 | 13.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3320.034 |
21 | KITCHEN_FLR_6_LIGHTS | LTG_SCH_KITCHEN | KITCHEN_FLR_6 | 103.30 | 22.2 | 1178.676 | 11.410 | 53.003 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1178.676 |
22 | CORRIDOR_FLR_6_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_6 | 412.12 | 22.2 | 2927.804 | 7.104 | 132.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2927.804 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 2.7 | 883.628 | 5.380 | 333.193 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 254.902 | 2.690 | 124.952 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 457.500 | 4.429 | 20.573 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 457.500 | 457.500 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 285.000 | 2.759 | 12.816 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 285.000 | 285.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 2.390 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
6 | RES_ROOF | 19 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
7 | NONRES_EXT_WALL_GRD | 21 | 3 | 9 | 0.167 | 0.7214 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | NONRES_EXT_WALL_MID | 22 | 3 | 9 | 0.167 | 0.9169 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | NONRES_EXT_WALL_TOP | 23 | 3 | 9 | 0.167 | 0.9299 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | RES_EXT_WALL_MID | 25 | 3 | 9 | 0.167 | 0.8441 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | RES_EXT_WALL_TOP | 26 | 3 | 9 | 0.167 | 0.8569 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | NONRES_FLOOR | 30 | 3 | 7 | 0.167 | 0.2277 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
13 | NONRES_FLOOR_CEILING | 33 | 3 | 7 | 0.167 | 0.2277 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
14 | BASEMENT_FLOOR | 36 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
15 | BASEMENT_WALL_NORTH_CFACTOR | 39 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | BASEMENT_WALL_EAST_CFACTOR | 40 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | BASEMENT_WALL_SOUTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
18 | BASEMENT_WALL_WEST_CFACTOR | 42 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4184 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
10 | RES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
11 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
12 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.219 |
14 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9233 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9080 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | RES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.017 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
25 | RES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9996 |
26 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
27 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.131 |
28 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
29 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
30 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
31 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
32 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.131 |
33 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
34 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
35 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
39 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
40 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
41 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
42 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 2.3900722 | 2.3900722 | 2.3900722 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
21 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
22 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
23 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
24 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
25 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
26 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
27 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
28 | 9 | -0.17110984E-14 | 0.24103936E-16 | -0.15943139E-09 | 0.44685538E-16 |
29 | 8 | 0.23237837E-07 | 0.98082464E-13 | 0.39196772E-03 | -0.26422217E-09 |
30 | 7 | -0.12664044E-01 | 0.50206963E-08 | -0.23693971E-01 | 0.14399480E-03 |
31 | 6 | 0.41682950 | 0.17394333E-05 | 0.48185553 | -0.48830741E-02 |
32 | 5 | -5.3025782 | 0.64717486E-04 | -4.5162048 | 0.64572787E-01 |
33 | 4 | 33.498276 | 0.52771084E-03 | 21.733161 | -0.42870077 |
34 | 3 | -112.28016 | 0.11468200E-02 | -56.202879 | 1.5304215 |
35 | 2 | 198.17562 | 0.64344368E-03 | 78.405936 | -2.9173034 |
36 | 1 | -171.55028 | 0.68528185E-04 | -55.409506 | 2.7523484 |
37 | 0 | 57.057407 | 0.38903588E-06 | 15.533392 | |
38 | 9 | -0.29206544E-14 | 0.31488305E-16 | -0.15031727E-09 | 0.48064473E-16 |
39 | 8 | 0.21958778E-07 | 0.12356532E-12 | 0.37867817E-03 | -0.24967887E-09 |
40 | 7 | -0.12267989E-01 | 0.64094198E-08 | -0.23123879E-01 | 0.13949151E-03 |
41 | 6 | 0.40606866 | 0.22324768E-05 | 0.47270315 | -0.47562292E-02 |
42 | 5 | -5.1975737 | 0.83445227E-04 | -4.4459647 | 0.63270770E-01 |
43 | 4 | 33.033866 | 0.68326082E-03 | 21.458733 | -0.42253461 |
44 | 3 | -111.29222 | 0.14903991E-02 | -55.660391 | 1.5161481 |
45 | 2 | 197.19665 | 0.83899866E-03 | 77.908180 | -2.9017570 |
46 | 1 | -171.18874 | 0.89630080E-04 | -55.264364 | 2.7460119 |
47 | 0 | 57.057407 | 0.51068186E-06 | 15.557036 | |
48 | 9 | -0.29497736E-14 | 0.32939851E-16 | -0.14970570E-09 | 0.45584202E-16 |
49 | 8 | 0.21872815E-07 | 0.12523736E-12 | 0.37777579E-03 | -0.24870145E-09 |
50 | 7 | -0.12241065E-01 | 0.65023057E-08 | -0.23085114E-01 | 0.13918537E-03 |
51 | 6 | 0.40533708 | 0.22656711E-05 | 0.47208016 | -0.47476058E-02 |
52 | 5 | -5.1904345 | 0.84713026E-04 | -4.4411801 | 0.63182247E-01 |
53 | 4 | 33.002288 | 0.69384191E-03 | 21.440032 | -0.42211534 |
54 | 3 | -111.22504 | 0.15138688E-02 | -55.623419 | 1.5151774 |
55 | 2 | 197.13007 | 0.85240592E-03 | 77.874271 | -2.9006996 |
56 | 1 | -171.16415 | 0.91081681E-04 | -55.254501 | 2.7455809 |
57 | 0 | 57.057407 | 0.51907125E-06 | 15.558664 | |
58 | 9 | -0.24257523E-14 | 0.33690592E-16 | -0.15372093E-09 | 0.39666009E-16 |
59 | 8 | 0.22436951E-07 | 0.11417013E-12 | 0.38367618E-03 | -0.25511586E-09 |
60 | 7 | -0.12417040E-01 | 0.58916776E-08 | -0.23338459E-01 | 0.14118628E-03 |
61 | 6 | 0.41011853 | 0.20479623E-05 | 0.47615013 | -0.48039676E-02 |
62 | 5 | -5.2370942 | 0.76414309E-04 | -4.4724296 | 0.63760808E-01 |
63 | 4 | 33.208666 | 0.62469949E-03 | 21.562156 | -0.42485549 |
64 | 3 | -111.66410 | 0.13607335E-02 | -55.864850 | 1.5215209 |
65 | 2 | 197.56520 | 0.76503996E-03 | 78.095736 | -2.9076095 |
66 | 1 | -171.32486 | 0.81633884E-04 | -55.318971 | 2.7483976 |
67 | 0 | 57.057407 | 0.46449959E-06 | 15.548073 | |
68 | 9 | -0.24053431E-14 | 0.30582108E-16 | -0.15312349E-09 | 0.40258954E-16 |
69 | 8 | 0.22353057E-07 | 0.11582316E-12 | 0.38280191E-03 | -0.25416195E-09 |
70 | 7 | -0.12390977E-01 | 0.59826426E-08 | -0.23300939E-01 | 0.14088992E-03 |
71 | 6 | 0.40941037 | 0.20803184E-05 | 0.47554760 | -0.47956200E-02 |
72 | 5 | -5.2301838 | 0.77645268E-04 | -4.4678046 | 0.63675121E-01 |
73 | 4 | 33.178102 | 0.63493787E-03 | 21.544084 | -0.42444968 |
74 | 3 | -111.59908 | 0.13833754E-02 | -55.829123 | 1.5205815 |
75 | 2 | 197.50076 | 0.77794062E-03 | 78.062960 | -2.9065863 |
76 | 1 | -171.30107 | 0.83027327E-04 | -55.309421 | 2.7479805 |
77 | 0 | 57.057407 | 0.47253235E-06 | 15.549635 | |
78 | 7 | -0.14139450E-14 | -0.18802902E-16 | -0.22311785E-13 | 0.54375338E-15 |
79 | 6 | 0.16999971E-10 | 0.27590984E-11 | 0.52267399E-09 | -0.18616555E-10 |
80 | 5 | -0.63950587E-07 | 0.13451749E-07 | -0.21905428E-05 | 0.17144787E-06 |
81 | 4 | 0.72477507E-04 | 0.50724086E-05 | 0.17668371E-02 | -0.28223350E-03 |
82 | 3 | -0.10573811E-01 | 0.17927531E-03 | -0.21549182 | 0.43318087E-01 |
83 | 2 | 0.15010112 | 0.77388015E-03 | 2.8998331 | -0.61891034 |
84 | 1 | -0.37982851 | 0.49528818E-03 | -7.1368477 | 1.5694772 |
85 | 0 | 0.24168561 | 0.34021171E-05 | 4.4521969 | |
86 | 7 | -0.22311785E-13 | -0.18802902E-16 | -0.14139450E-14 | 0.54375338E-15 |
87 | 6 | 0.52267399E-09 | 0.27590984E-11 | 0.16999971E-10 | -0.18616555E-10 |
88 | 5 | -0.21905428E-05 | 0.13451749E-07 | -0.63950587E-07 | 0.17144787E-06 |
89 | 4 | 0.17668371E-02 | 0.50724086E-05 | 0.72477507E-04 | -0.28223350E-03 |
90 | 3 | -0.21549182 | 0.17927531E-03 | -0.10573811E-01 | 0.43318087E-01 |
91 | 2 | 2.8998331 | 0.77388015E-03 | 0.15010112 | -0.61891034 |
92 | 1 | -7.1368477 | 0.49528818E-03 | -0.37982851 | 1.5694772 |
93 | 0 | 4.4521969 | 0.34021171E-05 | 0.24168561 | |
94 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
95 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
96 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
97 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
98 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
99 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
100 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
101 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
102 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
103 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
104 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
105 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
106 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
107 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
108 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
109 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
110 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
111 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
112 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
113 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
114 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
115 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
116 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
117 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
118 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
119 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
120 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
121 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
122 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
123 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
124 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
125 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
126 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
127 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
128 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
129 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
130 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
131 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
132 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
133 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.38_SHGC_0.38 | 37 | 1 | VerySmooth | 2.159 | 2.159 | 1.000 | 0.381 | ||
2 | RESWINDOW_U_0.38_SHGC_0.38 | 38 | 1 | VerySmooth | 2.159 | 2.159 | 1.000 | 0.381 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 3.45900E-002 | 0.29373 | 0.49855 | 0.49855 | 0.41800 | 0.13582 | 0.17513 | 0.00000 | 0.84000 | 0.84000 | 0.11893 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 3.45900E-002 | 0.29373 | 0.49855 | 0.49855 | 0.41800 | 0.13582 | 0.17513 | 0.00000 | 0.84000 | 0.84000 | 0.11893 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | CAFE_FLR_1 | 1 | 0 |
2 | LOBBY_FLR_1 | 1 | 0 |
3 | BANQUET_FLR_6 | 1 | 0 |
4 | DINING_FLR_6 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | CAFE_FLR_1 | 0 | |
2 | LOBBY_FLR_1 | 0 | |
3 | BANQUET_FLR_6 | 0 | |
4 | DINING_FLR_6 | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH LAUNDRY G WATER HEATER | 1.1356 | 163316.0 | 11.511 | 0.4388 |
2 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.219 | 1.1187 |
3 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 2.2712 | 175842.6 | 5.775 | 0.3748 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 1.764E-002 | 2.631E-004 | 1.298E-004 | 0.239 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.811E-003 | 8.769E-005 | 2.388E-004 | 7.967E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 2.7 | 1.610E-002 | 9.800E-005 | 2.563E-004 | 8.904E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 9.287E-003 | 9.800E-005 | 2.127E-004 | 8.904E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 2.198E-002 | 2.816E-004 | 2.506E-004 | 0.256 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 3.900E-002 | 2.065E-004 | 1.137E-004 | 0.188 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 0.111 | 8.519E-005 | 1.629E-004 | 7.740E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 2.563E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 2.563E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 2.857E-003 | 1.165E-004 | 2.563E-004 | 0.138 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 2.858E-003 | 1.165E-004 | 2.563E-004 | 0.138 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 2.563E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 2.563E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 1.238E-002 | 3.180E-005 | 2.563E-004 | 3.755E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 1.297E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 1.297E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 5.239E-003 | 2.136E-004 | 1.165E-004 | 0.252 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 2.500E-002 | 7.539E-005 | 5.825E-005 | 8.904E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 2.500E-002 | 7.539E-005 | 5.825E-005 | 8.904E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 2.238E-002 | 2.167E-004 | 1.174E-004 | 0.256 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 2.191E-002 | 5.316E-005 | 4.403E-005 | 6.278E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1570 |
2 | Clear Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 8.0230E-002 |
3 | Clear Turbid Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1776 |
4 | Clear Turbid Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 9.1042E-002 |
5 | Intermediate Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1093 |
6 | Intermediate Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 4.2876E-002 |
7 | Overcast Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 4.3971E-002 |
8 | Overcast Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 1.4607E-002 |
9 | Clear Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1777 |
10 | Clear Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 9.6382E-002 |
11 | Clear Turbid Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.2017 |
12 | Clear Turbid Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 0.1090 |
13 | Intermediate Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1209 |
14 | Intermediate Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 5.3577E-002 |
15 | Overcast Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 4.9373E-002 |
16 | Overcast Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 1.9973E-002 |
17 | Clear Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 3.7797E-002 |
18 | Clear Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 2.1798E-002 |
19 | Clear Turbid Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.9074E-002 |
20 | Clear Turbid Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.6461E-002 |
21 | Intermediate Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.7924E-002 |
22 | Intermediate Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.1171E-002 |
23 | Overcast Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 4.3283E-002 |
24 | Overcast Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.5348E-002 |
25 | Clear Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 3.7797E-002 |
26 | Clear Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 2.1798E-002 |
27 | Clear Turbid Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.9074E-002 |
28 | Clear Turbid Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.6461E-002 |
29 | Intermediate Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.7924E-002 |
30 | Intermediate Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.1171E-002 |
31 | Overcast Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 4.3283E-002 |
32 | Overcast Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.5348E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 33382.72040 | 33382.72040 | 2.48799 | 2.48799 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:40:00 | 25.99100 | 1.33593E-002 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
2 | BASEMENT | Heating | 1530.22371 | 1530.22371 | 6.72796E-002 | 0.85446 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -16.30000 | 9.24091E-004 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
3 | RETAIL_1_FLR_1 | Cooling | 5069.26174 | 5069.26174 | 0.37785 | 0.37785 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 30.06750 | 1.33665E-002 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 3011.25814 | 3011.25814 | 0.13239 | 0.13239 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -16.30000 | 9.24091E-004 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 3086.90642 | 3086.90642 | 0.23009 | 0.23009 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 29.83500 | 1.33661E-002 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 979.64787 | 979.64787 | 4.30719E-002 | 9.17347E-002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -16.30000 | 9.24091E-004 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 2428.71348 | 2428.71348 | 0.18099 | 0.18099 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | 29.74200 | 1.33660E-002 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 1735.63974 | 1735.63974 | 7.63103E-002 | 7.63103E-002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -16.30000 | 9.24091E-004 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 1446.69462 | 1446.69462 | 0.10781 | 0.10781 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 30.30000 | 1.33670E-002 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 1233.94116 | 1233.94116 | 5.42523E-002 | 5.77652E-002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -16.30000 | 9.24091E-004 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 44637.09724 | 44637.09724 | 3.32679 | 3.32679 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 30.30000 | 1.33670E-002 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 2281.72255 | 2281.72255 | 0.10032 | 0.10032 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -16.30000 | 9.24091E-004 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 21195.22210 | 21195.22210 | 1.58114 | 1.58114 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 30.06750 | 1.33665E-002 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 7701.44486 | 7701.44486 | 0.33860 | 0.67639 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -16.30000 | 9.24091E-004 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 66521.56466 | 66521.56466 | 4.95976 | 4.95976 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 30.14500 | 1.33667E-002 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 17582.34353 | 17582.34353 | 0.77304 | 1.89399 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -16.30000 | 9.24091E-004 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 11452.82098 | 11452.82098 | 1.15021 | 1.15021 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 28.99800 | 1.33646E-002 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 6689.38371 | 6689.38371 | 0.29583 | 0.29583 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -16.30000 | 9.24091E-004 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 11094.12531 | 11094.12531 | 1.11419 | 1.11419 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 28.84300 | 1.33644E-002 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 6689.01044 | 6689.01044 | 0.29582 | 0.29582 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -16.30000 | 9.24091E-004 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 70675.17373 | 70675.17373 | 7.09751 | 7.09751 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 30.14500 | 1.33667E-002 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 38389.26122 | 38389.26122 | 1.69776 | 1.69776 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -16.30000 | 9.24091E-004 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 60637.97434 | 60637.97434 | 6.09000 | 6.09000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 30.30000 | 1.33670E-002 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 38400.42431 | 38400.42431 | 1.69825 | 1.69825 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -16.30000 | 9.24091E-004 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 10471.98519 | 10471.98519 | 1.05171 | 1.05171 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 26.50250 | 1.33602E-002 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 6664.75209 | 6664.75209 | 0.29474 | 0.29474 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -16.30000 | 9.24091E-004 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 10153.30999 | 10153.30999 | 1.01970 | 1.01970 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 25.97550 | 1.33593E-002 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 6664.37938 | 6664.37938 | 0.29473 | 0.29473 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -16.30000 | 9.24091E-004 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 20960.89926 | 20960.89926 | 1.56217 | 1.56217 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 30.30000 | 1.33670E-002 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 10627.07887 | 10627.07887 | 0.46724 | 0.47476 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -16.30000 | 9.24091E-004 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 2986.88377 | 2986.88377 | 0.29997 | 0.29997 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 28.99800 | 1.33646E-002 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 2050.32268 | 2050.32268 | 9.06736E-002 | 9.06736E-002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -16.30000 | 9.24091E-004 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 2885.79706 | 2885.79706 | 0.28982 | 0.28982 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 28.84300 | 1.33644E-002 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 2050.19090 | 2050.19090 | 9.06678E-002 | 9.06678E-002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -16.30000 | 9.24091E-004 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 14055.84892 | 14055.84892 | 1.41166 | 1.41166 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 30.14500 | 1.33667E-002 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 9844.22740 | 9844.22740 | 0.43535 | 0.43535 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -16.30000 | 9.24091E-004 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 29226.43296 | 29226.43296 | 2.18090 | 2.18090 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 30.30000 | 1.33670E-002 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 6796.54214 | 6796.54214 | 0.29882 | 1.18780 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -16.30000 | 9.24091E-004 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 30636.80081 | 30636.80081 | 2.28611 | 2.28611 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 30.30000 | 1.33670E-002 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
40 | DINING_FLR_6 | Heating | 6943.35040 | 6943.35040 | 0.30527 | 1.18780 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | -16.30000 | 9.24091E-004 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 30880.07435 | 30880.07435 | 2.30749 | 2.30749 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 29.46300 | 1.33655E-002 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 2433.66486 | 2433.66486 | 0.10699 | 0.36735 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | -16.30000 | 9.24091E-004 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
43 | CORRIDOR_FLR_6 | Cooling | 10415.81344 | 10415.81344 | 0.77626 | 0.77626 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 30.30000 | 1.33670E-002 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 7148.14038 | 7148.14038 | 0.31428 | 0.31428 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | -16.30000 | 9.24091E-004 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | FLR_3_DOAS | Cooling | Sensible | 42344.89 | 18.28764 | 2.05125 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | FLR_3_DOAS | Heating | Sensible | 79850.37 | 5.19382 | 2.05125 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 |
3 | VAV WITH REHEAT | Cooling | Sensible | 380314.57 | 22.23975 | 22.23975 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | VAV WITH REHEAT | Heating | Sensible | 288662.18 | 7.41533 | 7.41533 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.48799 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.60606 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52100 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.29624 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.28651E-004 |
8 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.17560E-005 |
9 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.29624 |
10 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8202.14866 |
13 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.17560E-005 |
14 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 173.10088 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.37785 |
16 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13526 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52100 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.19686 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52100 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.81678E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.52037E-005 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.19686 |
24 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 4024.00394 |
27 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.52037E-005 |
28 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 99.52396 |
29 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.23009 |
30 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25722 |
31 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52100 |
32 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.11988 |
33 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.68591 |
34 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.48124E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.39655E-005 |
37 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.11988 |
38 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1596.34349 |
41 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.39655E-005 |
42 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 36.30073 |
43 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.18099 |
44 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.69148 |
45 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52100 |
46 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 9.42973E-002 |
47 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.50990E-004 |
50 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.94272E-005 |
51 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 9.42973E-002 |
52 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2220.65097 |
55 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.94272E-005 |
56 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 57.13926 |
57 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.10781 |
58 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.66975 |
59 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52100 |
60 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 5.61698E-002 |
61 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.68871E-004 |
64 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.33229E-005 |
65 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.61698E-002 |
66 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1522.88479 |
69 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.33229E-005 |
70 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 41.11258 |
71 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.32679 |
72 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 1.78749E-002 |
73 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52100 |
74 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.73326 |
75 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52100 |
76 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.13148E-002 |
78 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.79461E-005 |
79 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.73326 |
80 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11195.84292 |
83 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.79461E-005 |
84 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 236.59936 |
85 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.58114 |
86 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.10185E-002 |
87 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52100 |
88 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.82377 |
89 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52100 |
90 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.18596E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.04453E-004 |
93 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.82377 |
94 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11939.67058 |
97 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.04453E-004 |
98 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 275.14361 |
99 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 4.95976 |
100 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20098 |
101 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52100 |
102 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.58404 |
103 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.53596 |
104 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
105 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.89566E-003 |
106 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.70118E-004 |
107 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.58404 |
108 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
110 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 30876.16191 |
111 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.70118E-004 |
112 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 691.54557 |
113 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
114 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.15021 |
115 | Fan:OnOff | ROOM_1_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 1.15021 |
116 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.85211E-005 |
117 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.61102E-004 |
118 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69756 |
119 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
120 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.60615E-003 |
121 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
122 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
123 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.61102E-004 |
124 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.15021 |
125 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 6689.32157 |
126 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.85211E-005 |
127 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 191.13624 |
128 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
129 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.11419 |
130 | Fan:OnOff | ROOM_2_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 1.11419 |
131 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.85178E-005 |
132 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.50106E-004 |
133 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69755 |
134 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
135 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.60945E-003 |
136 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
137 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
138 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.50106E-004 |
139 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.11419 |
140 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 6688.94831 |
141 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.85178E-005 |
142 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 191.12558 |
143 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83707 |
144 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 7.09751 |
145 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 7.09751 |
146 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 3.35845E-004 |
147 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.18526E-003 |
148 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69812 |
149 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
150 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.53497E-003 |
151 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
152 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
153 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.18526E-003 |
154 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 7.09751 |
155 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 38389.09274 |
156 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.35845E-004 |
157 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1096.89479 |
158 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83730 |
159 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 6.09000 |
160 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 6.09000 |
161 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 3.35942E-004 |
162 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.00007E-003 |
163 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69721 |
164 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
165 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.77593E-003 |
166 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
167 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
168 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.00007E-003 |
169 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 6.09000 |
170 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 38400.25578 |
171 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.35942E-004 |
172 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1097.21375 |
173 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
174 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.05171 |
175 | Fan:OnOff | ROOM_5_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 1.05171 |
176 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.83056E-005 |
177 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.31089E-004 |
178 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69754 |
179 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
180 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.61632E-003 |
181 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
182 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
183 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.31089E-004 |
184 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.05171 |
185 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 6664.69016 |
186 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.83056E-005 |
187 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 190.43255 |
188 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
189 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.01970 |
190 | Fan:OnOff | ROOM_6_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 1.01970 |
191 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.83024E-005 |
192 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.21344E-004 |
193 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69753 |
194 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
195 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.62012E-003 |
196 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
197 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
198 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.21344E-004 |
199 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.01970 |
200 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 6664.31745 |
201 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.83024E-005 |
202 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 190.42190 |
203 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.56217 |
204 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.75978 |
205 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52100 |
206 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.81389 |
207 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.01459E-004 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.29607E-004 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.81389 |
212 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
213 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
214 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14814.82152 |
215 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.29607E-004 |
216 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 356.51320 |
217 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54338E-002 |
218 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.29997 |
219 | Fan:OnOff | ROOM_1_FLR_6 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 0.29997 |
220 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.79370E-005 |
221 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 9.40654E-005 |
222 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69757 |
223 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
224 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.60186E-003 |
225 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
226 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
227 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 9.40654E-005 |
228 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.29997 |
229 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 2050.30426 |
230 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.79370E-005 |
231 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 58.58239 |
232 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54319E-002 |
233 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.28982 |
234 | Fan:OnOff | ROOM_2_FLR_6 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 0.28982 |
235 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.79358E-005 |
236 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 9.09664E-005 |
237 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69756 |
238 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
239 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.60528E-003 |
240 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
241 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
242 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 9.09664E-005 |
243 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.28982 |
244 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 2050.17248 |
245 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.79358E-005 |
246 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 58.57862 |
247 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 9.91540E-002 |
248 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.41166 |
249 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 1.41166 |
250 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 8.61210E-005 |
251 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.49436E-004 |
252 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69733 |
253 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
254 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.65816E-003 |
255 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
256 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
257 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.49436E-004 |
258 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.41166 |
259 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 9844.15725 |
260 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.61210E-005 |
261 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 281.27133 |
262 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.18090 |
263 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11588 |
264 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52100 |
265 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.13625 |
266 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52100 |
267 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
268 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.28789E-003 |
269 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.10609E-004 |
270 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.13625 |
271 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
272 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
273 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12643.29557 |
274 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.10609E-004 |
275 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 280.64496 |
276 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.28611 |
277 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11055 |
278 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52100 |
279 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.19106 |
280 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52100 |
281 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
282 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.44649E-003 |
283 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.14360E-004 |
284 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.19106 |
285 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
286 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
287 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13072.10384 |
288 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.14360E-004 |
289 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 289.68457 |
290 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.30749 |
291 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 6.13585E-002 |
292 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52100 |
293 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.20220 |
294 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52100 |
295 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
296 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.11684E-002 |
297 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.52986E-005 |
298 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.20220 |
299 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
300 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
301 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8607.09320 |
302 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.52986E-005 |
303 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 183.20538 |
304 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.77626 |
305 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.40455 |
306 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52100 |
307 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.40443 |
308 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
309 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
310 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 9.41780E-004 |
311 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.07421E-005 |
312 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.40443 |
313 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
314 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
315 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9229.31242 |
316 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.07421E-005 |
317 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 235.26070 |
318 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05132 |
319 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05132 |
320 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05132 |
321 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05132 |
322 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05132 |
323 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05132 |
324 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
325 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
326 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 11.65235 |
327 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 11.65235 |
328 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 22.36536 |
329 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 11.65235 |
330 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 22.23975 |
331 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 22.23975 |
332 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
333 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.52394 |
334 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05132 |
335 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 22.23975 |
336 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05132 |
337 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05125 |
338 | HeatExchanger:AirToAir:SensibleAndLatent | FLR_3_DOAS OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.05125 |
339 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 30.30000 |
340 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
341 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.91477 |
342 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.33670E-002 |
343 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
344 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Coil Load [W] | 75158.60084 |
345 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.14953E-003 |
346 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 2.05132 |
347 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Rated Capacity [W] | 23955.95238 |
348 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.09577E-004 |
349 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 376.64253 |
350 | Fan:ConstantVolume | FLR_3_DOAS FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05125 |
351 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.14953E-003 |
352 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 2.21533E-004 |
353 | Controller:WaterCoil | FLR_3_DOAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.09577E-004 |
354 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 22.23975 |
355 | HeatExchanger:AirToAir:SensibleAndLatent | VAV WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 11.66146 |
356 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 27.29857 |
357 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
358 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.94045 |
359 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.16072E-002 |
360 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
361 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 642888.97719 |
362 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.83865E-002 |
363 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 22.23975 |
364 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 259723.03964 |
365 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.27217E-003 |
366 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 4083.44201 |
367 | Fan:VariableVolume | VAV WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 22.23975 |
368 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.83865E-002 |
369 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 2.58989E-005 |
370 | Controller:WaterCoil | VAV WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.27217E-003 |
371 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 2.67195E-002 |
372 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 4362.47897 |
373 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 4.64598E-003 |
374 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.55752 |
375 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 4.64598E-003 |
376 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 1399.16655 |
377 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
378 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 531064.58584 |
379 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 531064.59000 |
380 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 4.64598E-003 |
381 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 2.67195E-002 |
382 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 3.20634 |
383 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 2.67195E-002 |
384 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 3020.29133 |
385 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 2.67195E-002 |
386 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 934252.61907 |
387 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 934867.06000 |
388 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 106.57484 |
389 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
390 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
391 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
392 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
393 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | 8244.13 |
2 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 4041.21 |
3 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1603.86 |
4 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | 2229.66 |
5 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | 1528.76 |
6 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 11253.08 |
7 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | 11995.16 |
8 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | 31023.68 |
9 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | 7204.76 |
10 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | 7204.36 |
11 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 41347.04 |
12 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 41359.06 |
13 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | 7178.24 |
14 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | 7177.84 |
15 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 14879.98 |
16 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | 2208.25 |
17 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | 2208.11 |
18 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 10602.50 |
19 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | 12704.25 |
20 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | 13135.23 |
21 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | 8650.81 |
22 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 9267.67 |
23 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | 16024.01 |
24 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | 173727.34 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | 18894.52 | 16154.85 | 2739.67 | 0.86 | 3941.03 | 39.97 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | 18313.91 | 15652.63 | 2661.28 | 0.85 | 3816.02 | 38.70 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 115034.37 | 99162.13 | 15872.24 | 0.86 | 24528.36 | 248.78 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 103154.14 | 86605.02 | 16549.12 | 0.84 | 20544.18 | 208.37 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | 17308.82 | 14782.22 | 2526.60 | 0.85 | 3598.98 | 36.50 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | 16796.21 | 14338.04 | 2458.17 | 0.85 | 3491.70 | 35.41 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | 4923.76 | 4211.86 | 711.90 | 0.86 | 1028.37 | 10.43 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | 4760.14 | 4070.32 | 689.81 | 0.86 | 993.14 | 10.07 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 23414.07 | 19903.82 | 3510.25 | 0.85 | 4812.30 | 48.81 |
10 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | 61457.95 | 40035.10 | 21422.84 | 0.65 | 8414.34 | 85.34 |
11 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | 630433.64 | 419106.74 | 211326.91 | 0.66 | 95773.28 | 971.39 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 4.09 | 13.95 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.419 | 0.394 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.419 | 0.394 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.721 | 0.651 | 22.63 | 45.89 | 22.63 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 23.26 | 23.26 | 23.26 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.721 | 0.651 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.721 | 0.651 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.721 | 0.651 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.721 | 0.651 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 2.390 | 2.390 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.721 | 0.651 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.721 | 0.651 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.721 | 0.651 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.721 | 0.651 | 63.73 | 129.23 | 63.73 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 65.50 | 65.50 | 65.50 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.721 | 0.651 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.721 | 0.651 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.721 | 0.651 | 82.79 | 167.88 | 82.79 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 85.08 | 85.08 | 85.08 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.721 | 0.651 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.844 | 0.749 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.844 | 0.749 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.844 | 0.749 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.844 | 0.749 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.844 | 0.749 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.844 | 0.749 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.844 | 0.749 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.844 | 0.749 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.844 | 0.749 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.844 | 0.749 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.917 | 0.806 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.917 | 0.806 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.917 | 0.806 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.917 | 0.806 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.857 | 0.759 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.857 | 0.759 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.857 | 0.759 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.857 | 0.759 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.857 | 0.759 | 13.70 | 20.44 | 13.70 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 6.74 | 6.74 | 6.74 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.930 | 0.816 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.930 | 0.816 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.930 | 0.816 | 16.77 | 21.37 | 16.77 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.930 | 0.816 | 34.86 | 52.03 | 34.86 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 17.17 | 17.17 | 17.17 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.930 | 0.816 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.930 | 0.816 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.930 | 0.816 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.930 | 0.816 | 34.86 | 52.03 | 34.86 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 17.17 | 17.17 | 17.17 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 1.8188911541E-002 | 2.3385399312E-002 | Pass | Pass | 4.4054316724E-003 | 1.2462976560E-002 | Pass | Pass |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.7162259815E-003 | 1.3198970138E-003 | Pass | Pass | 0.1939095129 | 0.5969686248 | Pass | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.6767760035E-002 | 2.4051343064E-002 | Pass | Pass | 1.4304839812E-002 | 4.2920713608E-002 | Pass | Pass |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 3.8602862028E-004 | 2.9359992983E-004 | Pass | Pass | 0.1877053997 | 1.1464738248 | Pass | Pass |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.4140992082E-004 | 3.4878328503E-004 | Pass | Pass | 0.2244348898 | 0.6679536174 | Pass | Pass |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 7.0190068456E-002 | 0.2061199444 | Pass | Pass | 1.9281400382E-002 | 5.2175968972E-002 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.0377827325E-002 | 3.6578772140E-002 | Pass | Pass | 3.3632183989E-002 | 0.1000101163 | Pass | Pass |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.5148760941E-002 | 4.4674490731E-002 | Pass | Pass | 1.2780904423E-002 | 3.4952337875E-002 | Pass | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 8.9842280169E-002 | 0.2903519109 | Pass | Pass | 9.1922664118E-002 | 0.2878553176 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.0135213116E-002 | 0.2928880870 | Pass | Pass | 8.8902725793E-002 | 0.2736907355 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 2.7906033668E-002 | 3.7776388054E-002 | Pass | Pass | 5.8934015329E-002 | 0.2688660778 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 2.6440557089E-002 | 8.3586209486E-002 | Pass | Pass | 0.2782427095 | 1.0022216820 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 8.8828845044E-002 | 0.2858345539 | Pass | Pass | 8.5609639089E-002 | 0.2672540548 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 8.9281871072E-002 | 0.2882937016 | Pass | Pass | 9.6244295772E-002 | 0.2920479989 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.6111496687E-004 | 3.4698489948E-004 | Pass | Pass | 0.1760348307 | 0.8618153736 | Pass | Pass |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.2598825878E-002 | 0.3203488993 | Pass | Pass | 0.1313291915 | 0.6131425037 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.2652342315E-002 | 0.3210054685 | Pass | Pass | 0.2074611699 | 1.0082286046 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 7.6307254813E-002 | 0.2524243665 | Pass | Pass | 0.1328903358 | 0.5855194090 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 4.0639435022E-002 | 7.6007879991E-002 | Pass | Pass | 1.0612712667E-002 | 3.0812728632E-002 | Pass | Pass |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 3.0302560278E-002 | 6.5770646452E-002 | Pass | Pass | 1.2014339803E-002 | 3.6945558176E-002 | Pass | Pass |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 2.7001514984E-002 | 8.0091712389E-002 | Pass | Pass | 2.1344546853E-002 | 4.1761351025E-002 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 8.2012971885E-004 | 6.2864091760E-004 | Pass | Pass | 0.6984033597 | 4.1733160883 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:40
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 4371.72 | 68.17 | 1981.08 | 8066.17 | 3489.12 | 17976.27 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:40
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -16.30 | 0.00 | -16.30 | Wetbulb [C] | 5.10 | 270.00 |
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 30.30 | 9.30 | 21.80 | Wetbulb [C] | 5.70 | 240.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 44.00 | 33 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 67.00 | 33 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:40
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 211.13 | 211.13 | 0.00 | 90.00 | N |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.399 | 0.419 | 55.76 | 55.76 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 211.13 | 211.13 | 180.00 | 90.00 | S |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.399 | 0.419 | 55.76 | 55.76 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.651 | 0.721 | 45.89 | 22.63 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.651 | 0.721 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.651 | 0.721 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.651 | 0.721 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.651 | 0.721 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.651 | 0.721 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.651 | 0.721 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.651 | 0.721 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.651 | 0.721 | 129.23 | 63.73 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.651 | 0.721 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.651 | 0.721 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.651 | 0.721 | 167.88 | 82.79 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.651 | 0.721 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.749 | 0.844 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.749 | 0.844 | 104.06 | 69.72 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.749 | 0.844 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.749 | 0.844 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.749 | 0.844 | 847.14 | 567.58 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.749 | 0.844 | 847.37 | 567.71 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.749 | 0.844 | 104.06 | 69.72 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.749 | 0.844 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.749 | 0.844 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.749 | 0.844 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.917 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.917 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.917 | 26.02 | 17.43 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.917 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.759 | 0.857 | 13.94 | 9.34 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.759 | 0.857 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | RES_ROOF | 0.23 | 0.182 | 0.186 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | RES_EXT_WALL_TOP | 0.30 | 0.759 | 0.857 | 13.94 | 9.34 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.759 | 0.857 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | RES_ROOF | 0.23 | 0.182 | 0.186 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.759 | 0.857 | 183.96 | 123.26 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | RES_ROOF | 0.23 | 0.182 | 0.186 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.816 | 0.930 | 97.55 | 65.36 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.816 | 0.930 | 97.55 | 65.36 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.816 | 0.930 | 21.37 | 16.77 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.816 | 0.930 | 52.03 | 34.86 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.816 | 0.930 | 13.94 | 9.34 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.816 | 0.930 | 17.65 | 11.83 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.816 | 0.930 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.816 | 0.930 | 52.03 | 34.86 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 167.42 | 167.42 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_FLOOR | BASEMENT_FLOOR | 0.30 | 1.441 | 2.705 | 1978.83 | 1978.83 | 0.00 | 180.00 | |
BASEMENT_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 67.07 | 67.07 | 180.00 | 0.00 | |
BASEMENT_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 77.67 | 77.67 | 180.00 | 0.00 | |
BASEMENT_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 164.24 | 164.24 | 180.00 | 0.00 | |
BASEMENT_CEILING_4 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 94.76 | 94.76 | 180.00 | 0.00 | |
BASEMENT_CEILING_5 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 78.04 | 78.04 | 180.00 | 0.00 | |
BASEMENT_CEILING_6 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 188.86 | 188.86 | 180.00 | 0.00 | |
BASEMENT_CEILING_7 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 1088.56 | 1088.56 | 180.00 | 0.00 | |
BASEMENT_CEILING_8 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 219.63 | 219.63 | 90.00 | 0.00 | |
RETAIL_1_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_1_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
RETAIL_1_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 67.07 | 67.07 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
RETAIL_2_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_2_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 90.00 | 90.00 | E |
RETAIL_2_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 77.67 | 77.67 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 77.67 | 77.67 | 180.00 | 0.00 | |
MECH_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
MECH_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 180.00 | 90.00 | S |
MECH_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
MECH_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 164.24 | 164.24 | 0.00 | 180.00 | |
MECH_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 164.24 | 164.24 | 180.00 | 0.00 | |
STORAGE_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
STORAGE_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 180.00 | 90.00 | S |
STORAGE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
STORAGE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 94.76 | 94.76 | 0.00 | 180.00 | |
STORAGE_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 94.76 | 94.76 | 180.00 | 0.00 | |
LAUNDRY_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 180.00 | 90.00 | S |
LAUNDRY_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 270.00 | 90.00 | W |
LAUNDRY_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 78.04 | 78.04 | 0.00 | 180.00 | |
LAUNDRY_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 78.04 | 78.04 | 180.00 | 0.00 | |
CAFE_FLR_1_WALL_1_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_2_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
CAFE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 188.86 | 188.86 | 0.00 | 180.00 | |
LOBBY_FLR_1_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 90.00 | 90.00 | E |
LOBBY_FLR_1_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 1088.56 | 1088.56 | 180.00 | 180.00 | |
LOBBY_FLR_1_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 219.63 | 219.63 | 90.00 | 180.00 | |
LOBBY_FLR_1_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 1062.83 | 1062.83 | 270.00 | 0.00 | |
ROOM_1_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_1_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
ROOM_1_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_1_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_2_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
ROOM_2_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_2_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_2_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 156.07 | 156.07 | 180.00 | 0.00 | |
ROOM_3_MULT19_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.14 | 847.14 | 0.00 | 90.00 | N |
ROOM_3_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_3_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 1863.81 | 1863.81 | 0.00 | 180.00 | |
ROOM_3_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 1863.81 | 1863.81 | 180.00 | 0.00 | |
ROOM_4_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_4_MULT19_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.37 | 847.37 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_4_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 1864.32 | 1864.32 | 0.00 | 180.00 | |
ROOM_4_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 1864.32 | 1864.32 | 180.00 | 0.00 | |
ROOM_5_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
ROOM_5_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_5_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_6_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
ROOM_6_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_6_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 156.07 | 156.07 | 180.00 | 0.00 | |
CORRIDOR_FLR_3_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.28 | 847.28 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_4_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.27 | 847.27 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 297.29 | 297.29 | 180.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 963.06 | 963.06 | 270.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_3 | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 297.26 | 297.26 | 90.00 | 180.00 | |
CORRIDOR_FLR_3_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 297.29 | 297.29 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 963.06 | 963.06 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 297.26 | 297.26 | 90.00 | 0.00 | |
ROOM_1_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 0.00 | 90.00 | N |
ROOM_1_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_1_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_2_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_2_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 180.00 | 90.00 | S |
ROOM_2_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_3_MULT9_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.96 | 183.96 | 0.00 | 90.00 | N |
ROOM_3_MULT9_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 90.00 | 90.00 | E |
ROOM_3_MULT9_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 270.00 | 90.00 | W |
ROOM_3_MULT9_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 220.77 | 220.77 | 0.00 | 180.00 | |
BANQUET_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
BANQUET_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
BANQUET_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
BANQUET_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 331.66 | 331.66 | 0.00 | 180.00 | |
DINING_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
DINING_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
DINING_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
DINING_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 331.66 | 331.66 | 0.00 | 180.00 | |
KITCHEN_FLR_6_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 7.43 | 7.43 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 103.30 | 103.30 | 180.00 | 180.00 | |
CORRIDOR_FLR_6_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 104.98 | 104.98 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_1_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.95 | 183.95 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 11.15 | 11.15 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 40.88 | 40.88 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 412.12 | 412.12 | 180.00 | 180.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3957.66 | 0.00 | 90.00 | N | ||
RETAIL_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 134.14 | 0.00 | 90.00 | N | ||
RETAIL_2_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 155.34 | 0.00 | 90.00 | N | ||
MECH_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 328.49 | 0.00 | 90.00 | N | ||
STORAGE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 189.52 | 0.00 | 90.00 | N | ||
LAUNDRY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 156.08 | 0.00 | 90.00 | N | ||
CAFE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 377.72 | 0.00 | 90.00 | N | ||
LOBBY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 2616.37 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3727.63 | 0.00 | 90.00 | N | ||
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3728.64 | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3115.24 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.04 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.03 | 0.00 | 90.00 | N | ||
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 441.55 | 0.00 | 90.00 | N | ||
BANQUET_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
DINING_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 206.61 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 824.25 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.38 | 23.26 | 0.00 | 0.00 | 23.26 | 23.26 | 2.159 | 0.381 | 0.420 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.38 | 65.50 | 0.00 | 0.00 | 65.50 | 65.50 | 2.159 | 0.381 | 0.420 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.38 | 85.08 | 0.00 | 0.00 | 85.08 | 85.08 | 2.159 | 0.381 | 0.420 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.38_SHGC_0.38 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.159 | 0.381 | 0.420 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.38_SHGC_0.38 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.159 | 0.381 | 0.420 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.38_SHGC_0.38 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.159 | 0.381 | 0.420 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.38_SHGC_0.38 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.159 | 0.381 | 0.420 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.38_SHGC_0.38 | 3.68 | 0.00 | 0.00 | 3.68 | 279.56 | 2.159 | 0.381 | 0.420 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.38_SHGC_0.38 | 3.68 | 0.00 | 0.00 | 3.68 | 279.65 | 2.159 | 0.381 | 0.420 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.38_SHGC_0.38 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.159 | 0.381 | 0.420 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.38_SHGC_0.38 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.159 | 0.381 | 0.420 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.38_SHGC_0.38 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.159 | 0.381 | 0.420 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.38_SHGC_0.38 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.159 | 0.381 | 0.420 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.38 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.159 | 0.381 | 0.420 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.38 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 2.159 | 0.381 | 0.420 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.38 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 2.159 | 0.381 | 0.420 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.38 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.159 | 0.381 | 0.420 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.38_SHGC_0.38 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.159 | 0.381 | 0.420 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.38_SHGC_0.38 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.159 | 0.381 | 0.420 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.38_SHGC_0.38 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.159 | 0.381 | 0.420 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.38_SHGC_0.38 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.159 | 0.381 | 0.420 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.38_SHGC_0.38 | 6.74 | 0.00 | 0.00 | 6.74 | 60.70 | 2.159 | 0.381 | 0.420 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.38 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.159 | 0.381 | 0.420 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.38 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.159 | 0.381 | 0.420 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.38 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.159 | 0.381 | 0.420 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.38 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.159 | 0.381 | 0.420 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | |||||||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.38 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.159 | 0.381 | 0.420 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.38 | 5.82 | 0.00 | 0.00 | 5.82 | 5.82 | 2.159 | 0.381 | 0.420 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.38 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 2.159 | 0.381 | 0.420 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.38 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.159 | 0.381 | 0.420 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 1213.79 | 2.159 | 0.381 | 0.420 | |||||||||||||||||
North Total or Average | 432.95 | 2.159 | 0.381 | 0.420 | |||||||||||||||||
Non-North Total or Average | 780.84 | 2.159 | 0.381 | 0.420 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 1.760 | 2.390 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:40
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:40
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 8.8143 | 1978.83 | 17441.96 | LightsWired | LTG_SCH_BASEMENT | 49.32 | 168.00 | 49.26 | 0.0000 | Y | 161.29 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | RETAIL_1_FLR_1 | GENERAL | 11.3140 | 67.07 | 758.85 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 7.31 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | RETAIL_2_FLR_1 | GENERAL | 11.3140 | 77.67 | 878.75 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 8.46 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | MECH_FLR_1 | GENERAL | 4.6285 | 164.24 | 760.20 | LightsWired | LTG_SCH_MECHANIC | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 8.37 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | STORAGE_FLR_1 | GENERAL | 5.7199 | 94.76 | 542.02 | LightsWired | LTG_SCH_STORAGE | 30.30 | 168.00 | 30.27 | 0.0000 | Y | 3.08 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | LAUNDRY_FLR_1 | GENERAL | 4.6285 | 78.04 | 361.20 | LightsWired | LTG_SCH_LAUNDRY | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 3.98 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | CAFE_FLR_1 | GENERAL | 10.0104 | 188.86 | 1890.59 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 39.53 | 0.0000 | Y | 14.03 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | LOBBY_FLR_1 | GENERAL | 10.7639 | 1308.19 | 14081.18 | LightsWired | LTG_SCH_LOBBY | 44.02 | 168.00 | 41.57 | 0.0000 | Y | 109.89 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | ROOM_1_FLR_3 | GENERAL | 8.2882 | 156.09 | 1293.69 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | ROOM_2_FLR_3 | GENERAL | 8.2882 | 156.07 | 1293.54 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | GENERAL | 8.2882 | 1863.81 | 15447.65 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 110.38 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | GENERAL | 8.2882 | 1864.32 | 15451.87 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 110.41 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | ROOM_5_FLR_3 | GENERAL | 8.2882 | 156.09 | 1293.69 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | ROOM_6_FLR_3 | GENERAL | 8.2882 | 156.07 | 1293.54 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | CORRIDOR_FLR_3 | GENERAL | 7.1042 | 1557.62 | 11065.59 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 91.33 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | ROOM_1_FLR_6 | GENERAL | 8.2882 | 39.02 | 323.42 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 2.31 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | ROOM_2_FLR_6 | GENERAL | 8.2882 | 39.02 | 323.38 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 2.31 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | GENERAL | 8.2882 | 220.77 | 1829.83 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 13.08 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | BANQUET_FLR_6 | GENERAL | 10.0104 | 331.66 | 3320.03 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 49.24 | 0.0000 | Y | 30.69 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | DINING_FLR_6 | GENERAL | 10.0104 | 331.66 | 3320.03 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 49.24 | 0.0000 | Y | 30.69 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | KITCHEN_FLR_6 | GENERAL | 11.4097 | 103.30 | 1178.68 | LightsWired | LTG_SCH_KITCHEN | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 12.97 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | CORRIDOR_FLR_6 | GENERAL | 7.1042 | 412.12 | 2927.80 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 24.17 |
Interior Lighting Total | 8.5566 | 11345.29 | 97077.49 | 455.97 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
LOBBY_FLR_1_DAYLREFPT1 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.07 | 14081.18 | 985.68 |
LOBBY_FLR_1_DAYLREFPT2 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.07 | 14081.18 | 985.68 |
CAFE_FLR_1_DAYLREFPT1 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1890.59 | 737.33 |
CAFE_FLR_1_DAYLREFPT2 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1890.59 | 737.33 |
DINING_FLR_6_DAYLREFPT1 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
DINING_FLR_6_DAYLREFPT2 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
BANQUET_FLR_6_DAYLREFPT1 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
BANQUET_FLR_6_DAYLREFPT2 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 12338.45 | AstronomicalClock | - | 83.67 | 83.67 | 193.78 | |
Exterior Lighting Total | 12338.45 | 193.78 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:40
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 531064.59 | 0.80 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 934867.06 | 2.96 | 934867.06 | 2.96 | 4.09 | 13.95 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 12626.24 | 18894.52 | 16154.85 | 2739.67 | 0.86 | - | 3941.03 | 39.97 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 12241.75 | 18313.91 | 15652.63 | 2661.28 | 0.85 | - | 3816.02 | 38.70 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 76409.31 | 115034.37 | 99162.13 | 15872.24 | 0.86 | - | 24528.36 | 248.78 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 69934.18 | 103154.14 | 86605.02 | 16549.12 | 0.84 | - | 20544.18 | 208.37 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 11576.81 | 17308.82 | 14782.22 | 2526.60 | 0.85 | - | 3598.98 | 36.50 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 11236.07 | 16796.21 | 14338.04 | 2458.17 | 0.85 | - | 3491.70 | 35.41 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3289.08 | 4923.76 | 4211.86 | 711.90 | 0.86 | - | 1028.37 | 10.43 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3180.72 | 4760.14 | 4070.32 | 689.81 | 0.86 | - | 993.14 | 10.07 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 15714.92 | 23414.07 | 19903.82 | 3510.25 | 0.85 | - | 4812.30 | 48.81 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | 75158.60 | 61457.95 | 40035.10 | 21422.84 | 0.65 | - | 8414.34 | 85.34 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | 642888.98 | 630433.64 | 419106.74 | 211326.91 | 0.66 | - | 95773.28 | 971.39 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 8202.15 | 8244.13 | - |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 4024.00 | 4041.21 | - |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1596.34 | 1603.86 | - |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2220.65 | 2229.66 | - |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1522.88 | 1528.76 | - |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 11195.84 | 11253.08 | - |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 11939.67 | 11995.16 | - |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 30876.16 | 31023.68 | - |
ROOM_1_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 6689.32 | 7204.76 | - |
ROOM_2_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 6688.95 | 7204.36 | - |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 38389.09 | 41347.04 | - |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 38400.26 | 41359.06 | - |
ROOM_5_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 6664.69 | 7178.24 | - |
ROOM_6_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 6664.32 | 7177.84 | - |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 14814.82 | 14879.98 | - |
ROOM_1_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 2050.30 | 2208.25 | - |
ROOM_2_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 2050.17 | 2208.11 | - |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 9844.16 | 10602.50 | - |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 12643.30 | 12704.25 | - |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 13072.10 | 13135.23 | - |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 8607.09 | 8650.81 | - |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 9229.31 | 9267.67 | - |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | 23955.95 | 16024.01 | - |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | 259723.04 | 173727.34 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 0.24 | 76.61 | 324.68 | 1.00 | 2.78 | General | ||
LOBBY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.24 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
ROOM_1_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 1.15 | 809.33 | 703.64 | 1.00 | 1.16 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
ROOM_2_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 1.11 | 783.98 | 703.64 | 1.00 | 1.17 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 |
ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 7.10 | 4994.06 | 703.64 | 1.00 | 0.95 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 6.09 | 4285.15 | 703.64 | 1.00 | 0.96 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 |
ROOM_5_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 1.05 | 740.02 | 703.64 | 1.00 | 1.18 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 |
ROOM_6_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 1.02 | 717.50 | 703.64 | 1.00 | 1.19 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 |
ROOM_1_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 0.30 | 211.07 | 703.64 | 1.00 | 1.71 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
ROOM_2_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 0.29 | 203.93 | 703.64 | 1.00 | 1.74 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 |
ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 1.41 | 993.30 | 703.64 | 1.00 | 1.12 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
BANQUET_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
DINING_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 1.89 | 612.92 | 324.68 | 1.00 | 1.48 | General | ||
FLR_3_DOAS FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.93 | 1070.05 | 1.00 | 1.30 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 |
VAV WITH REHEAT FAN | Fan:VariableVolume | 0.62 | 1389.42 | 22.24 | 49831.24 | 2240.64 | 1.00 | 1.11 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.026720 | 4362.48 | 163269.44 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.004646 | 1399.17 | 301156.09 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.026720 | 3020.29 | 113036.94 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH LAUNDRY G WATER HEATER | WaterHeater:Mixed | 1.14 | 163316.00 | 0.80 | 11.51 | 0.44 |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.22 | 1.12 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.60 | 0.80 | 5.78 | 0.37 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:40
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 33382.72 | 33382.72 | 16.87 | 2.488 | 2.488 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:40:00 | 24.00 | 24.00 | 0.00922 | 25.99 | 0.01336 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 5069.26 | 5069.26 | 75.58 | 0.378 | 0.378 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 24.00 | 0.00903 | 30.07 | 0.01337 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 3086.91 | 3086.91 | 39.74 | 0.230 | 0.230 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 24.00 | 24.00 | 0.00945 | 29.84 | 0.01337 | 0.092 | 0.00 |
MECH_FLR_1 | 2428.71 | 2428.71 | 14.79 | 0.181 | 0.181 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | 24.00 | 24.00 | 0.00884 | 29.74 | 0.01337 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1446.69 | 1446.69 | 15.27 | 0.108 | 0.108 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00891 | 30.30 | 0.01337 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 44637.10 | 44637.10 | 571.98 | 3.327 | 3.327 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00855 | 30.30 | 0.01337 | 0.000 | 0.00 |
CAFE_FLR_1 | 21195.22 | 21195.22 | 112.23 | 1.581 | 1.581 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 23.99 | 0.01004 | 30.07 | 0.01337 | 0.676 | 0.00 |
LOBBY_FLR_1 | 66521.56 | 66521.56 | 50.85 | 4.960 | 4.960 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 23.99 | 0.00996 | 30.14 | 0.01337 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 11452.82 | 11452.82 | 293.50 | 1.150 | 1.150 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 21.11 | 21.11 | 0.00861 | 29.00 | 0.01336 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 11094.13 | 11094.13 | 284.34 | 1.114 | 1.114 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 21.11 | 21.11 | 0.00861 | 28.84 | 0.01336 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 70675.17 | 70675.17 | 2881.90 | 7.098 | 7.098 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 21.11 | 21.11 | 0.00853 | 30.14 | 0.01337 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 60637.97 | 60637.97 | 2471.94 | 6.090 | 6.090 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 21.11 | 21.11 | 0.00878 | 30.30 | 0.01337 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 10471.99 | 10471.99 | 268.36 | 1.052 | 1.052 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 21.11 | 21.11 | 0.00862 | 26.50 | 0.01336 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 10153.31 | 10153.31 | 260.22 | 1.020 | 1.020 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 21.11 | 21.11 | 0.00862 | 25.98 | 0.01336 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 20960.90 | 20960.90 | 53.83 | 1.562 | 1.562 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00944 | 30.30 | 0.01337 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 2986.88 | 2986.88 | 76.54 | 0.300 | 0.300 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 21.11 | 21.11 | 0.00860 | 29.00 | 0.01336 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2885.80 | 2885.80 | 73.96 | 0.290 | 0.290 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 21.11 | 21.11 | 0.00861 | 28.84 | 0.01336 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 14055.85 | 14055.85 | 572.99 | 1.412 | 1.412 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 21.11 | 21.11 | 0.00866 | 30.14 | 0.01337 | 0.099 | 0.00 |
BANQUET_FLR_6 | 29226.43 | 29226.43 | 88.12 | 2.181 | 2.181 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 23.98 | 0.01044 | 30.30 | 0.01337 | 1.188 | 0.00 |
DINING_FLR_6 | 30636.80 | 30636.80 | 92.37 | 2.286 | 2.286 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 23.98 | 0.01035 | 30.30 | 0.01337 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 30880.07 | 30880.07 | 298.92 | 2.307 | 2.307 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 24.00 | 23.97 | 0.01009 | 29.46 | 0.01337 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 10415.81 | 10415.81 | 25.27 | 0.776 | 0.776 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 24.00 | 0.00901 | 30.30 | 0.01337 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 1530.22 | 1530.22 | 0.77 | 0.067 | 0.854 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00797 | -16.30 | 0.00092 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 3011.26 | 3011.26 | 44.90 | 0.132 | 0.132 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.00 | 21.00 | 0.00774 | -16.30 | 0.00092 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 979.65 | 979.65 | 12.61 | 0.043 | 0.092 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.00 | 21.00 | 0.00769 | -16.30 | 0.00092 | 0.092 | 0.00 |
MECH_FLR_1 | 1735.64 | 1735.64 | 10.57 | 0.076 | 0.076 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.00 | 21.00 | 0.00760 | -16.30 | 0.00092 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1233.94 | 1233.94 | 13.02 | 0.054 | 0.058 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.00 | 21.00 | 0.00767 | -16.30 | 0.00092 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 2281.72 | 2281.72 | 29.24 | 0.100 | 0.100 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.00 | 21.00 | 0.00758 | -16.30 | 0.00092 | 0.000 | 0.00 |
CAFE_FLR_1 | 7701.44 | 7701.44 | 40.78 | 0.339 | 0.676 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.00 | 21.00 | 0.00778 | -16.30 | 0.00092 | 0.676 | 0.00 |
LOBBY_FLR_1 | 17582.34 | 17582.34 | 13.44 | 0.773 | 1.894 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.00 | 21.00 | 0.00772 | -16.30 | 0.00092 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 6689.38 | 6689.38 | 171.43 | 0.296 | 0.296 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.11 | 21.11 | 0.00773 | -16.30 | 0.00092 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 6689.01 | 6689.01 | 171.44 | 0.296 | 0.296 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.11 | 21.11 | 0.00773 | -16.30 | 0.00092 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 38389.26 | 38389.26 | 1565.39 | 1.698 | 1.698 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.11 | 21.11 | 0.00775 | -16.30 | 0.00092 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 38400.42 | 38400.42 | 1565.41 | 1.698 | 1.698 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.11 | 21.11 | 0.00775 | -16.30 | 0.00092 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 6664.75 | 6664.75 | 170.79 | 0.295 | 0.295 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.11 | 21.11 | 0.00773 | -16.30 | 0.00092 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 6664.38 | 6664.38 | 170.81 | 0.295 | 0.295 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.11 | 21.11 | 0.00773 | -16.30 | 0.00092 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 10627.08 | 10627.08 | 27.29 | 0.467 | 0.475 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.00 | 21.00 | 0.00779 | -16.30 | 0.00092 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 2050.32 | 2050.32 | 52.54 | 0.091 | 0.091 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.11 | 21.11 | 0.00778 | -16.30 | 0.00092 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2050.19 | 2050.19 | 52.55 | 0.091 | 0.091 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.11 | 21.11 | 0.00778 | -16.30 | 0.00092 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 9844.23 | 9844.23 | 401.30 | 0.435 | 0.435 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.11 | 21.11 | 0.00779 | -16.30 | 0.00092 | 0.099 | 0.00 |
BANQUET_FLR_6 | 6796.54 | 6796.54 | 20.49 | 0.299 | 1.188 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.00 | 21.00 | 0.00784 | -16.30 | 0.00092 | 1.188 | 0.00 |
DINING_FLR_6 | 6943.35 | 6943.35 | 20.94 | 0.305 | 1.188 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 21.00 | 21.00 | 0.00784 | -16.30 | 0.00092 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 2433.66 | 2433.66 | 23.56 | 0.107 | 0.367 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 21.00 | 21.00 | 0.00700 | -16.30 | 0.00092 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 7148.14 | 7148.14 | 17.34 | 0.314 | 0.314 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 21.00 | 21.00 | 0.00786 | -16.30 | 0.00092 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
FLR_3_DOAS | 18.29 | 2.05 | 5.19 | 2.05 | 2.0513 | 2.0513 | 2.0513 | 1.0000 | 0.3000 |
VAV WITH REHEAT | 22.24 | 22.24 | 7.42 | 7.42 | 22.2397 | 11.6524 | 22.2397 | 0.5239 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 8202.149 | 8202.149 | 1.296242 | 0.00007176 | 173.101 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 8202.15 | 8202.15 | 1.296242 | 16.70 | 12.95 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00797356 | 50.2540 | 1530.22 | 0.00 | 8248.05 | 8248.05 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 4024.004 | 4024.004 | 0.196860 | 0.00003520 | 99.524 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 4024.00 | 4024.00 | 0.196860 | 16.70 | 12.95 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00774115 | 48.8084 | 3011.26 | 0.00 | 4044.82 | 4044.82 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 1596.343 | 1596.343 | 0.119878 | 0.00001397 | 36.301 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 1596.34 | 1596.34 | 0.119878 | 16.70 | 12.95 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00769494 | 48.5199 | 979.65 | 0.00 | 1604.94 | 1604.94 |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 2220.651 | 2220.651 | 0.094297 | 0.00001943 | 57.139 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 2220.65 | 2220.65 | 0.094297 | 16.70 | 12.95 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00759882 | 47.9212 | 1735.64 | 0.00 | 2231.87 | 2231.87 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 1522.885 | 1522.885 | 0.056170 | 0.00001332 | 41.113 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 1522.88 | 1522.88 | 0.056170 | 16.70 | 12.95 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00767093 | 48.3703 | 1233.94 | 0.00 | 1530.46 | 1530.46 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 11195.843 | 11195.843 | 1.733259 | 0.00009795 | 236.599 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 11195.84 | 11195.84 | 1.733259 | 16.70 | 12.95 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00758423 | 47.8310 | 2281.72 | 0.00 | 11258.47 | 11258.47 |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 11939.671 | 11939.671 | 0.823773 | 0.00010445 | 275.144 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 11939.67 | 11939.67 | 0.823773 | 16.70 | 12.95 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00777515 | 49.0199 | 7701.44 | 0.00 | 12003.67 | 12003.67 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 30876.162 | 30876.162 | 2.584037 | 0.00027012 | 691.546 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 30876.16 | 30876.16 | 2.584037 | 16.70 | 12.95 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00772082 | 48.6810 | 17582.34 | 0.00 | 31043.36 | 31043.36 |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 12626.242 | -999.000 | 1.150210 | 0.00036110 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | 7/21 17:00:00 | 12626.24 | 12315.73 | 1.150210 | 21.70 | 15.40 | 0.00860615 | 12.80 | 11.87 | 0.00850000 | 29.00 | 0.01336465 | 21.45 | 0.0000 | 21.11 | 0.00860615 | 53.8202 | 11452.82 | 0.00 | 12949.88 | 12949.88 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 6689.322 | 6689.322 | 0.295832 | 0.00005852 | 191.136 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 6689.32 | 6689.32 | 0.295832 | 21.11 | 14.40 | 0.00773142 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.11 | 0.00773142 | 48.4167 | 6689.38 | 0.00 | 7211.27 | 7211.27 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 12241.754 | -999.000 | 1.114187 | 0.00035011 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | 7/21 17:10:00 | 12241.75 | 11931.59 | 1.114187 | 21.70 | 15.40 | 0.00860945 | 12.80 | 11.87 | 0.00850000 | 28.84 | 0.01336437 | 21.41 | 0.0000 | 21.11 | 0.00860945 | 53.8406 | 11094.13 | 0.00 | 12555.32 | 12555.32 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 6688.948 | 6688.948 | 0.295815 | 0.00005852 | 191.126 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 6688.95 | 6688.95 | 0.295815 | 21.11 | 14.40 | 0.00773143 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.11 | 0.00773143 | 48.4168 | 6689.01 | 0.00 | 7210.87 | 7210.87 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 76409.313 | -999.000 | 7.097506 | 0.00218526 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | unknown | 7/21 13:40:00 | 76409.31 | 75779.98 | 7.097506 | 21.70 | 15.34 | 0.00853497 | 12.80 | 11.87 | 0.00850000 | 30.14 | 0.01336669 | 21.78 | 0.0000 | 21.11 | 0.00853497 | 53.3795 | 70675.17 | 0.00 | 78385.76 | 78385.76 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 38389.093 | 38389.093 | 1.697759 | 0.00033584 | 1096.895 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 38389.09 | 38389.09 | 1.697759 | 21.11 | 14.42 | 0.00775118 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.11 | 0.00775118 | 48.5382 | 38389.26 | 0.00 | 41384.68 | 41384.68 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 69934.178 | -999.000 | 6.090005 | 0.00200007 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | unknown | 7/21 15:00:00 | 69934.18 | 65632.56 | 6.090005 | 21.70 | 15.55 | 0.00877593 | 12.80 | 11.87 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 0.0000 | 21.11 | 0.00877593 | 54.8678 | 60637.97 | 0.00 | 71688.56 | 69710.36 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 38400.256 | 38400.256 | 1.698253 | 0.00033594 | 1097.214 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 38400.26 | 38400.26 | 1.698253 | 21.11 | 14.42 | 0.00775118 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.11 | 0.00775118 | 48.5382 | 38400.42 | 0.00 | 41396.71 | 41396.71 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 11576.809 | -999.000 | 1.051706 | 0.00033109 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | unknown | 7/21 09:50:00 | 11576.81 | 11265.57 | 1.051706 | 21.70 | 15.41 | 0.00861632 | 12.80 | 11.87 | 0.00850000 | 26.50 | 0.01336023 | 20.72 | 0.0000 | 21.11 | 0.00861632 | 53.8830 | 10471.99 | 0.00 | 11872.92 | 11872.92 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 6664.690 | 6664.690 | 0.294742 | 0.00005831 | 190.433 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 6664.69 | 6664.69 | 0.294742 | 21.11 | 14.40 | 0.00773047 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.11 | 0.00773047 | 48.4108 | 6664.75 | 0.00 | 7184.72 | 7184.72 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 11236.068 | -999.000 | 1.019701 | 0.00032134 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | unknown | 7/21 09:30:00 | 11236.07 | 10924.39 | 1.019701 | 21.70 | 15.41 | 0.00862012 | 12.80 | 11.87 | 0.00850000 | 25.98 | 0.01335930 | 20.56 | 0.0000 | 21.11 | 0.00862012 | 53.9064 | 10153.31 | 0.00 | 11525.05 | 11525.05 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 6664.317 | 6664.317 | 0.294726 | 0.00005830 | 190.422 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 6664.32 | 6664.32 | 0.294726 | 21.11 | 14.40 | 0.00773047 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.11 | 0.00773047 | 48.4109 | 6664.38 | 0.00 | 7184.32 | 7184.32 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 14814.822 | 14814.822 | 0.813888 | 0.00012961 | 356.513 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 14814.82 | 14814.82 | 0.813888 | 16.70 | 12.95 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00779252 | 49.1273 | 10627.08 | 0.00 | 14892.20 | 14892.20 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 3289.076 | -999.000 | 0.299973 | 0.00009407 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | 7/21 17:00:00 | 3289.08 | 3211.38 | 0.299973 | 21.70 | 15.40 | 0.00860186 | 12.80 | 11.87 | 0.00850000 | 29.00 | 0.01336465 | 21.45 | 0.0000 | 21.11 | 0.00860186 | 53.7938 | 2986.88 | 0.00 | 3373.46 | 3373.46 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 2050.304 | 2050.304 | 0.090674 | 0.00001794 | 58.582 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 2050.30 | 2050.30 | 0.090674 | 21.11 | 14.44 | 0.00777934 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.11 | 0.00777934 | 48.7131 | 2050.32 | 0.00 | 2210.29 | 2210.29 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 3180.718 | -999.000 | 0.289821 | 0.00009097 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | 7/21 17:10:00 | 3180.72 | 3103.12 | 0.289821 | 21.70 | 15.40 | 0.00860528 | 12.80 | 11.87 | 0.00850000 | 28.84 | 0.01336437 | 21.41 | 0.0000 | 21.11 | 0.00860528 | 53.8149 | 2885.80 | 0.00 | 3262.26 | 3262.26 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 2050.172 | 2050.172 | 0.090668 | 0.00001794 | 58.579 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 2050.17 | 2050.17 | 0.090668 | 21.11 | 14.44 | 0.00777935 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.11 | 0.00777935 | 48.7131 | 2050.19 | 0.00 | 2210.14 | 2210.14 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 15714.921 | -999.000 | 1.411662 | 0.00044944 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | unknown | 7/21 13:40:00 | 15714.92 | 15145.96 | 1.411662 | 21.70 | 15.44 | 0.00865816 | 12.80 | 11.87 | 0.00850000 | 30.14 | 0.01336669 | 21.78 | 0.0000 | 21.11 | 0.00865816 | 54.1415 | 14055.85 | 0.00 | 16115.90 | 16115.90 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 9844.157 | 9844.157 | 0.435355 | 0.00008612 | 281.271 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 9844.16 | 9844.16 | 0.435355 | 21.11 | 14.45 | 0.00778811 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.11 | 0.00778811 | 48.7670 | 9844.23 | 0.00 | 10612.29 | 10612.29 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 12643.296 | 12643.296 | 1.136251 | 0.00011061 | 280.645 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 12643.30 | 12643.30 | 1.136251 | 16.70 | 12.95 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00783518 | 49.3931 | 6796.54 | 0.00 | 12712.00 | 12712.00 |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 13072.104 | 13072.104 | 1.191064 | 0.00011436 | 289.685 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 13072.10 | 13072.10 | 1.191064 | 16.70 | 12.95 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00783858 | 49.4145 | 6943.35 | 0.00 | 13143.19 | 13143.19 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 8607.093 | 8607.093 | 1.202203 | 0.00007530 | 183.205 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 8607.09 | 8607.09 | 1.202203 | 16.70 | 12.95 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00700452 | 44.2212 | 2433.66 | 0.00 | 8655.13 | 8655.13 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 9229.312 | 9229.312 | 0.404432 | 0.00008074 | 235.261 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 9229.31 | 9229.31 | 0.404432 | 16.70 | 12.95 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00786215 | 49.5611 | 7148.14 | 0.00 | 9276.63 | 9276.63 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 75158.601 | -999.000 | 2.051317 | 0.00214953 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 75158.60 | 45858.12 | 2.051317 | 30.30 | 21.83 | 0.01336696 | 11.91 | 11.51 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 99.9965 | 21.11 | 0.00864816 | 54.0788 | 182095.42 | 0.00 | 76167.93 | 46274.27 |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | FLR_3_DOAS | 23955.952 | 23955.952 | 0.615395 | 0.00020958 | 376.643 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 23955.95 | 23955.95 | 0.615395 | -16.30 | -16.30 | 0.00092409 | 16.70 | 12.95 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 333.3216 | 21.11 | 0.00775139 | 48.5395 | 117441.95 | 0.00 | 19372.81 | 19372.81 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 642888.977 | -999.000 | 22.239748 | 0.01838654 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 642888.98 | 433511.10 | 22.239748 | 27.30 | 19.69 | 0.01160721 | 10.94 | 10.94 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 52.4352 | 23.99 | 0.00962778 | 50.4581 | 298167.60 | 0.00 | 652984.36 | 430647.01 |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV WITH REHEAT | 259723.040 | 259723.040 | 6.671924 | 0.00227217 | 4083.442 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | 259723.04 | 259723.04 | 6.671924 | -16.30 | -16.30 | 0.00092409 | 16.70 | 12.95 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 174.7841 | 21.02 | 0.00776472 | 48.8912 | 69170.78 | 0.00 | 210033.98 | 210033.98 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:40
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | Yes | Yes | No | 8202.149 | 8202.149 | 1.296242 | 0.00007176 | 173.101 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.64551073 | 54.44 | 82.22 | 27.78 | 541752.47 | 1.5140 | 1.544473 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 8202.15 | 8202.15 | 1.0000 | 1.52169082 | 1.296242 | 16.70 | 12.95 | 0.00800000 | 37036.7 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.07174865 | 60.00 | 32.22 | 27.78 | 0.000 | 8202.15 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 21.00 | 0.00797356 | 21.00 | 0.00797356 | 50.2540 | 1530.22 | 0.00 | 8248.05 | 8248.05 | 1.52169082 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.92 | 15.19 | 0.00800000 | 42355.1 | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4024.004 | 4024.004 | 0.196860 | 0.00003520 | 99.524 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.64551073 | 54.44 | 82.22 | 27.78 | 541752.47 | 0.7428 | 0.757724 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 4024.00 | 4024.00 | 1.0000 | 0.23109941 | 0.196860 | 16.70 | 12.95 | 0.00800000 | 37036.7 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.03520015 | 60.00 | 32.22 | 27.78 | 0.000 | 4024.00 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 21.00 | 0.00774115 | 21.00 | 0.00774115 | 48.8084 | 3011.26 | 0.00 | 4044.82 | 4044.82 | 0.23109941 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 33.76 | 19.27 | 0.00800000 | 54437.2 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1596.343 | 1596.343 | 0.119878 | 0.00001397 | 36.301 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.64551073 | 54.44 | 82.22 | 27.78 | 541752.47 | 0.2947 | 0.300593 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 1596.34 | 1596.34 | 1.0000 | 0.14072807 | 0.119878 | 16.70 | 12.95 | 0.00800000 | 37036.7 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.01396408 | 60.00 | 32.22 | 27.78 | 0.000 | 1596.34 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 21.00 | 0.00769494 | 21.00 | 0.00769494 | 48.5199 | 979.65 | 0.00 | 1604.94 | 1604.94 | 0.14072807 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 27.78 | 17.29 | 0.00800000 | 48339.3 | |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2220.651 | 2220.651 | 0.094297 | 0.00001943 | 57.139 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.64551073 | 54.44 | 82.22 | 27.78 | 541752.47 | 0.4099 | 0.418151 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 2220.65 | 2220.65 | 1.0000 | 0.11069797 | 0.094297 | 16.70 | 12.95 | 0.00800000 | 37036.7 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.01942524 | 60.00 | 32.22 | 27.78 | 0.000 | 2220.65 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 21.00 | 0.00759882 | 21.00 | 0.00759882 | 47.9212 | 1735.64 | 0.00 | 2231.87 | 2231.87 | 0.11069797 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 36.37 | 20.08 | 0.00800000 | 57096.5 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1522.885 | 1522.885 | 0.056170 | 0.00001332 | 41.113 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.64551073 | 54.44 | 82.22 | 27.78 | 541752.47 | 0.2811 | 0.286761 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 1522.88 | 1522.88 | 1.0000 | 0.06593921 | 0.056170 | 16.70 | 12.95 | 0.00800000 | 37036.7 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.01332150 | 60.00 | 32.22 | 27.78 | 0.000 | 1522.88 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 21.00 | 0.00767093 | 21.00 | 0.00767093 | 48.3703 | 1233.94 | 0.00 | 1530.46 | 1530.46 | 0.06593921 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 39.36 | 20.99 | 0.00800000 | 60144.9 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11195.843 | 11195.843 | 1.733259 | 0.00009795 | 236.599 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.64551073 | 54.44 | 82.22 | 27.78 | 541752.47 | 2.0666 | 2.108189 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 11195.84 | 11195.84 | 1.0000 | 2.03471702 | 1.733259 | 16.70 | 12.95 | 0.00800000 | 37036.7 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.09793613 | 60.00 | 32.22 | 27.78 | 0.000 | 11195.84 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 21.00 | 0.00758423 | 21.00 | 0.00758423 | 47.8310 | 2281.72 | 0.00 | 11258.47 | 11258.47 | 2.03471702 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 22.03 | 15.23 | 0.00800000 | 42467.9 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11939.671 | 11939.671 | 0.823773 | 0.00010445 | 275.144 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.64551073 | 54.44 | 82.22 | 27.78 | 541752.47 | 2.2039 | 2.248252 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 11939.67 | 11939.67 | 1.0000 | 0.96704766 | 0.823773 | 16.70 | 12.95 | 0.00800000 | 37036.7 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.10444279 | 60.00 | 32.22 | 27.78 | 0.000 | 11939.67 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 21.00 | 0.00777515 | 21.00 | 0.00777515 | 49.0199 | 7701.44 | 0.00 | 12003.67 | 12003.67 | 0.96704766 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 28.77 | 17.62 | 0.00800000 | 49347.4 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 30876.162 | 30876.162 | 2.584037 | 0.00027012 | 691.546 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.64551073 | 54.44 | 82.22 | 27.78 | 541752.47 | 5.6993 | 5.814013 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 30876.16 | 30876.16 | 1.0000 | 3.03346611 | 2.584037 | 16.70 | 12.95 | 0.00800000 | 37036.7 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.27009058 | 60.00 | 32.22 | 27.78 | 0.000 | 30876.16 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 21.00 | 0.00772082 | 21.00 | 0.00772082 | 48.6810 | 17582.34 | 0.00 | 31043.36 | 31043.36 | 3.03346611 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 26.64 | 16.89 | 0.00800000 | 47168.4 | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12626.242 | -999.000 | 1.150210 | 0.00036110 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8384 | 1004.8586 | 1.1739 | ROOM_1_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.150210 | 1.35026037 | 4197.9300 | 999.8980 | 26.71678098 | 15.03 | 6.70 | 8.33 | 934252.62 | 1.3515 | 1.351455 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | unknown | unknown | 7/21 17:00:00 | Sensible | 12626.24 | 12315.73 | 1.0000 | 1.35026037 | 1.150210 | 21.70 | 15.40 | 0.00860615 | 43673.2 | 12.80 | 11.87 | 0.00850000 | 34322.2 | 0.36106535 | 6.70 | 15.03 | 8.33 | 0.000 | 12626.24 | 29.00 | 0.01336465 | 21.45 | 0.00000000 | 0.0000 | 21.11 | 0.00860615 | 21.11 | 0.00860615 | 53.8202 | 11452.82 | 0.00 | 12949.88 | 12949.88 | 1.35026037 | 21.70 | 15.65 | 0.00860615 | 43673.2 | 12.30 | 12.00 | 0.00860615 | 34082.5 | |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6689.322 | 6689.322 | 0.295832 | 0.00005852 | 191.136 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | ROOM_1_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.150210 | 1.35026037 | 4197.9300 | 999.8980 | 4.64551073 | 54.44 | 82.22 | 27.78 | 541752.47 | 1.2348 | 1.259606 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 6689.32 | 6689.32 | 1.0000 | 0.34728415 | 0.295832 | 21.11 | 14.40 | 0.00773142 | 40851.9 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.05851513 | 60.00 | 32.22 | 27.78 | 0.000 | 6689.32 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 21.11 | 0.00773142 | 21.11 | 0.00773142 | 48.4167 | 6689.38 | 0.00 | 7211.27 | 7211.27 | 0.34728415 | 16.60 | 12.89 | 0.00773142 | 36254.8 | 36.97 | 20.07 | 0.00773142 | 57019.5 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12241.754 | -999.000 | 1.114187 | 0.00035011 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8445 | 1004.8586 | 1.1739 | ROOM_2_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.114187 | 1.30797182 | 4197.9300 | 999.8980 | 26.71678098 | 15.03 | 6.70 | 8.33 | 934252.62 | 1.3103 | 1.310301 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | unknown | unknown | 7/21 17:10:00 | Sensible | 12241.75 | 11931.59 | 1.0000 | 1.30797182 | 1.114187 | 21.70 | 15.40 | 0.00860945 | 43681.5 | 12.80 | 11.87 | 0.00850000 | 34322.2 | 0.35007037 | 6.70 | 15.03 | 8.33 | 0.000 | 12241.75 | 28.84 | 0.01336437 | 21.41 | 0.00000000 | 0.0000 | 21.11 | 0.00860945 | 21.11 | 0.00860945 | 53.8406 | 11094.13 | 0.00 | 12555.32 | 12555.32 | 1.30797182 | 21.70 | 15.66 | 0.00860945 | 43681.5 | 12.29 | 12.00 | 0.00860945 | 34082.5 | |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6688.948 | 6688.948 | 0.295815 | 0.00005852 | 191.126 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | ROOM_2_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.114187 | 1.30797182 | 4197.9300 | 999.8980 | 4.64551073 | 54.44 | 82.22 | 27.78 | 541752.47 | 1.2347 | 1.259536 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 6688.95 | 6688.95 | 1.0000 | 0.34726477 | 0.295815 | 21.11 | 14.40 | 0.00773143 | 40852.0 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.05851187 | 60.00 | 32.22 | 27.78 | 0.000 | 6688.95 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 21.11 | 0.00773143 | 21.11 | 0.00773143 | 48.4168 | 6689.01 | 0.00 | 7210.87 | 7210.87 | 0.34726477 | 16.60 | 12.89 | 0.00773143 | 36254.8 | 36.97 | 20.07 | 0.00773143 | 57019.5 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 76409.313 | -999.000 | 7.097506 | 0.00218526 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7061 | 1004.8586 | 1.1739 | ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 7.097506 | 8.33194244 | 4197.9300 | 999.8980 | 26.71678098 | 15.03 | 6.70 | 8.33 | 934252.62 | 8.1787 | 8.178504 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | unknown | unknown | unknown | 7/21 13:40:00 | Sensible | 76409.31 | 75779.98 | 1.0000 | 8.33194244 | 7.097506 | 21.70 | 15.34 | 0.00853497 | 43492.8 | 12.80 | 11.87 | 0.00850000 | 34322.2 | 2.18503295 | 6.70 | 15.03 | 8.33 | 0.000 | 76409.31 | 30.14 | 0.01336669 | 21.78 | 0.00000000 | 0.0000 | 21.11 | 0.00853497 | 21.11 | 0.00853497 | 53.3795 | 70675.17 | 0.00 | 78385.76 | 78385.76 | 8.33194244 | 21.70 | 15.59 | 0.00853497 | 43492.8 | 12.48 | 12.00 | 0.00853497 | 34085.0 | |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 38389.093 | 38389.093 | 1.697759 | 0.00033584 | 1096.895 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 7.097506 | 8.33194244 | 4197.9300 | 999.8980 | 4.64551073 | 54.44 | 82.22 | 27.78 | 541752.47 | 7.0861 | 7.228705 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 38389.09 | 38389.09 | 1.0000 | 1.99304226 | 1.697759 | 21.11 | 14.42 | 0.00775118 | 40902.4 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.33581027 | 60.00 | 32.22 | 27.78 | 0.000 | 38389.09 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 21.11 | 0.00775118 | 21.11 | 0.00775118 | 48.5382 | 38389.26 | 0.00 | 41384.68 | 41384.68 | 1.99304226 | 16.60 | 12.91 | 0.00775118 | 36304.8 | 36.97 | 20.08 | 0.00775118 | 57069.3 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 69934.178 | -999.000 | 6.090005 | 0.00200007 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1540 | 1004.8586 | 1.1739 | ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 6.090005 | 7.14921062 | 4197.9300 | 999.8980 | 26.71678098 | 15.03 | 6.70 | 8.33 | 934252.62 | 7.4856 | 7.485435 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | unknown | unknown | unknown | 7/21 15:00:00 | Sensible | 69934.18 | 65632.56 | 1.0000 | 7.14921062 | 6.090005 | 21.70 | 15.55 | 0.00877593 | 44104.3 | 12.80 | 11.87 | 0.00850000 | 34322.2 | 1.99986727 | 6.70 | 15.03 | 8.33 | 0.000 | 69934.18 | 30.30 | 0.01336696 | 21.83 | 0.00000000 | 0.0000 | 21.11 | 0.00877593 | 21.11 | 0.00877593 | 54.8678 | 60637.97 | 0.00 | 71688.56 | 69710.36 | 7.14921062 | 21.70 | 15.80 | 0.00877593 | 44104.3 | 12.15 | 12.00 | 0.00866628 | 34076.8 | |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 38400.256 | 38400.256 | 1.698253 | 0.00033594 | 1097.214 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 6.090005 | 7.14921062 | 4197.9300 | 999.8980 | 4.64551073 | 54.44 | 82.22 | 27.78 | 541752.47 | 7.0882 | 7.230807 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 38400.26 | 38400.26 | 1.0000 | 1.99362181 | 1.698253 | 21.11 | 14.42 | 0.00775118 | 40902.4 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.33590792 | 60.00 | 32.22 | 27.78 | 0.000 | 38400.26 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 21.11 | 0.00775118 | 21.11 | 0.00775118 | 48.5382 | 38400.42 | 0.00 | 41396.71 | 41396.71 | 1.99362181 | 16.60 | 12.91 | 0.00775118 | 36304.8 | 36.97 | 20.08 | 0.00775118 | 57069.4 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11576.809 | -999.000 | 1.051706 | 0.00033109 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8573 | 1004.8586 | 1.1739 | ROOM_5_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.051706 | 1.23462383 | 4197.9300 | 999.8980 | 26.71678098 | 15.03 | 6.70 | 8.33 | 934252.62 | 1.2392 | 1.239129 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | unknown | unknown | unknown | 7/21 09:50:00 | Sensible | 11576.81 | 11265.57 | 1.0000 | 1.23462383 | 1.051706 | 21.70 | 15.41 | 0.00861632 | 43699.0 | 12.80 | 11.87 | 0.00850000 | 34322.2 | 0.33105531 | 6.70 | 15.03 | 8.33 | 0.000 | 11576.81 | 26.50 | 0.01336023 | 20.72 | 0.00000000 | 0.0000 | 21.11 | 0.00861632 | 21.11 | 0.00861632 | 53.8830 | 10471.99 | 0.00 | 11872.92 | 11872.92 | 1.23462383 | 21.70 | 15.66 | 0.00861632 | 43699.0 | 12.28 | 12.00 | 0.00861632 | 34082.4 | |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6664.690 | 6664.690 | 0.294742 | 0.00005831 | 190.433 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | ROOM_5_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.051706 | 1.23462383 | 4197.9300 | 999.8980 | 4.64551073 | 54.44 | 82.22 | 27.78 | 541752.47 | 1.2302 | 1.254968 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 6664.69 | 6664.69 | 1.0000 | 0.34600538 | 0.294742 | 21.11 | 14.40 | 0.00773047 | 40849.5 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.05829967 | 60.00 | 32.22 | 27.78 | 0.000 | 6664.69 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 21.11 | 0.00773047 | 21.11 | 0.00773047 | 48.4108 | 6664.75 | 0.00 | 7184.72 | 7184.72 | 0.34600538 | 16.60 | 12.89 | 0.00773047 | 36252.3 | 36.97 | 20.07 | 0.00773047 | 57017.1 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11236.068 | -999.000 | 1.019701 | 0.00032134 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8644 | 1004.8586 | 1.1739 | ROOM_6_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.019701 | 1.19705303 | 4197.9300 | 999.8980 | 26.71678098 | 15.03 | 6.70 | 8.33 | 934252.62 | 1.2027 | 1.202657 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | unknown | unknown | unknown | 7/21 09:30:00 | Sensible | 11236.07 | 10924.39 | 1.0000 | 1.19705303 | 1.019701 | 21.70 | 15.41 | 0.00862012 | 43708.6 | 12.80 | 11.87 | 0.00850000 | 34322.2 | 0.32131134 | 6.70 | 15.03 | 8.33 | 0.000 | 11236.07 | 25.98 | 0.01335930 | 20.56 | 0.00000000 | 0.0000 | 21.11 | 0.00862012 | 21.11 | 0.00862012 | 53.9064 | 10153.31 | 0.00 | 11525.05 | 11525.05 | 1.19705303 | 21.70 | 15.67 | 0.00862012 | 43708.6 | 12.27 | 12.00 | 0.00862012 | 34080.8 | |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6664.317 | 6664.317 | 0.294726 | 0.00005830 | 190.422 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | ROOM_6_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.019701 | 1.19705303 | 4197.9300 | 999.8980 | 4.64551073 | 54.44 | 82.22 | 27.78 | 541752.47 | 1.2301 | 1.254898 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 6664.32 | 6664.32 | 1.0000 | 0.34598603 | 0.294726 | 21.11 | 14.40 | 0.00773047 | 40849.5 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.05829641 | 60.00 | 32.22 | 27.78 | 0.000 | 6664.32 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 21.11 | 0.00773047 | 21.11 | 0.00773047 | 48.4109 | 6664.38 | 0.00 | 7184.32 | 7184.32 | 0.34598603 | 16.60 | 12.89 | 0.00773047 | 36252.3 | 36.97 | 20.07 | 0.00773047 | 57017.1 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14814.822 | 14814.822 | 0.813888 | 0.00012961 | 356.513 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.64551073 | 54.44 | 82.22 | 27.78 | 541752.47 | 2.7346 | 2.789646 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 14814.82 | 14814.82 | 1.0000 | 0.95544379 | 0.813888 | 16.70 | 12.95 | 0.00800000 | 37036.7 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.12959330 | 60.00 | 32.22 | 27.78 | 0.000 | 14814.82 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 21.00 | 0.00779252 | 21.00 | 0.00779252 | 49.1273 | 10627.08 | 0.00 | 14892.20 | 14892.20 | 0.95544379 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 31.89 | 18.66 | 0.00800000 | 52521.4 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3289.076 | -999.000 | 0.299973 | 0.00009407 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8304 | 1004.8586 | 1.1739 | ROOM_1_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.299973 | 0.35214630 | 4197.9300 | 999.8980 | 26.71678098 | 15.03 | 6.70 | 8.33 | 934252.62 | 0.3521 | 0.352048 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | unknown | unknown | 7/21 17:00:00 | Sensible | 3289.08 | 3211.38 | 1.0000 | 0.35214630 | 0.299973 | 21.70 | 15.40 | 0.00860186 | 43662.3 | 12.80 | 11.87 | 0.00850000 | 34322.2 | 0.09405580 | 6.70 | 15.03 | 8.33 | 0.000 | 3289.08 | 29.00 | 0.01336465 | 21.45 | 0.00000000 | 0.0000 | 21.11 | 0.00860186 | 21.11 | 0.00860186 | 53.7938 | 2986.88 | 0.00 | 3373.46 | 3373.46 | 0.35214630 | 21.70 | 15.65 | 0.00860186 | 43662.3 | 12.31 | 12.00 | 0.00860186 | 34082.6 | |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2050.304 | 2050.304 | 0.090674 | 0.00001794 | 58.582 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | ROOM_1_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.299973 | 0.35214630 | 4197.9300 | 999.8980 | 4.64551073 | 54.44 | 82.22 | 27.78 | 541752.47 | 0.3785 | 0.386074 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 2050.30 | 2050.30 | 1.0000 | 0.10644405 | 0.090674 | 21.11 | 14.44 | 0.00777934 | 40973.7 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.01793513 | 60.00 | 32.22 | 27.78 | 0.000 | 2050.30 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 21.11 | 0.00777934 | 21.11 | 0.00777934 | 48.7131 | 2050.32 | 0.00 | 2210.29 | 2210.29 | 0.10644405 | 16.60 | 12.94 | 0.00777934 | 36376.1 | 36.97 | 20.10 | 0.00777934 | 57140.8 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3180.718 | -999.000 | 0.289821 | 0.00009097 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8368 | 1004.8586 | 1.1739 | ROOM_2_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.289821 | 0.34022865 | 4197.9300 | 999.8980 | 26.71678098 | 15.03 | 6.70 | 8.33 | 934252.62 | 0.3405 | 0.340450 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | unknown | unknown | 7/21 17:10:00 | Sensible | 3180.72 | 3103.12 | 1.0000 | 0.34022865 | 0.289821 | 21.70 | 15.40 | 0.00860528 | 43671.0 | 12.80 | 11.87 | 0.00850000 | 34322.2 | 0.09095715 | 6.70 | 15.03 | 8.33 | 0.000 | 3180.72 | 28.84 | 0.01336437 | 21.41 | 0.00000000 | 0.0000 | 21.11 | 0.00860528 | 21.11 | 0.00860528 | 53.8149 | 2885.80 | 0.00 | 3262.26 | 3262.26 | 0.34022865 | 21.70 | 15.65 | 0.00860528 | 43671.0 | 12.30 | 12.00 | 0.00860528 | 34082.5 | |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2050.172 | 2050.172 | 0.090668 | 0.00001794 | 58.579 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | ROOM_2_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.289821 | 0.34022865 | 4197.9300 | 999.8980 | 4.64551073 | 54.44 | 82.22 | 27.78 | 541752.47 | 0.3784 | 0.386050 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 2050.17 | 2050.17 | 1.0000 | 0.10643720 | 0.090668 | 21.11 | 14.44 | 0.00777935 | 40973.7 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.01793397 | 60.00 | 32.22 | 27.78 | 0.000 | 2050.17 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 21.11 | 0.00777935 | 21.11 | 0.00777935 | 48.7131 | 2050.19 | 0.00 | 2210.14 | 2210.14 | 0.10643720 | 16.60 | 12.94 | 0.00777935 | 36376.1 | 36.97 | 20.10 | 0.00777935 | 57140.8 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15714.921 | -999.000 | 1.411662 | 0.00044944 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9351 | 1004.8586 | 1.1739 | ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 1.411662 | 1.65718547 | 4197.9300 | 999.8980 | 26.71678098 | 15.03 | 6.70 | 8.33 | 934252.62 | 1.6821 | 1.682053 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | unknown | unknown | unknown | 7/21 13:40:00 | Sensible | 15714.92 | 15145.96 | 1.0000 | 1.65718547 | 1.411662 | 21.70 | 15.44 | 0.00865816 | 43805.1 | 12.80 | 11.87 | 0.00850000 | 34322.2 | 0.44939050 | 6.70 | 15.03 | 8.33 | 0.000 | 15714.92 | 30.14 | 0.01336669 | 21.78 | 0.00000000 | 0.0000 | 21.11 | 0.00865816 | 21.11 | 0.00865816 | 54.1415 | 14055.85 | 0.00 | 16115.90 | 16115.90 | 1.65718547 | 21.70 | 15.70 | 0.00865816 | 43805.1 | 12.17 | 12.00 | 0.00865816 | 34080.2 | |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9844.157 | 9844.157 | 0.435355 | 0.00008612 | 281.271 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 1.411662 | 1.65718547 | 4197.9300 | 999.8980 | 4.64551073 | 54.44 | 82.22 | 27.78 | 541752.47 | 1.8171 | 1.853665 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 9844.16 | 9844.16 | 1.0000 | 0.51107377 | 0.435355 | 21.11 | 14.45 | 0.00778811 | 40996.0 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.08611220 | 60.00 | 32.22 | 27.78 | 0.000 | 9844.16 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 21.11 | 0.00778811 | 21.11 | 0.00778811 | 48.7670 | 9844.23 | 0.00 | 10612.29 | 10612.29 | 0.51107377 | 16.60 | 12.94 | 0.00778811 | 36398.3 | 36.97 | 20.11 | 0.00778811 | 57163.0 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12643.296 | 12643.296 | 1.136251 | 0.00011061 | 280.645 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.64551073 | 54.44 | 82.22 | 27.78 | 541752.47 | 2.3338 | 2.380745 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 12643.30 | 12643.30 | 1.0000 | 1.33387383 | 1.136251 | 16.70 | 12.95 | 0.00800000 | 37036.7 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.11059778 | 60.00 | 32.22 | 27.78 | 0.000 | 12643.30 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 21.00 | 0.00783518 | 21.00 | 0.00783518 | 49.3931 | 6796.54 | 0.00 | 12712.00 | 12712.00 | 1.33387383 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 25.95 | 16.65 | 0.00800000 | 46464.9 | |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13072.104 | 13072.104 | 1.191064 | 0.00011436 | 289.685 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.64551073 | 54.44 | 82.22 | 27.78 | 541752.47 | 2.4129 | 2.461490 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | Sensible | 13072.10 | 13072.10 | 1.0000 | 1.39822024 | 1.191064 | 16.70 | 12.95 | 0.00800000 | 37036.7 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.11434880 | 60.00 | 32.22 | 27.78 | 0.000 | 13072.10 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 21.00 | 0.00783858 | 21.00 | 0.00783858 | 49.4145 | 6943.35 | 0.00 | 13143.19 | 13143.19 | 1.39822024 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 25.82 | 16.60 | 0.00800000 | 46334.7 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8607.093 | 8607.093 | 1.202203 | 0.00007530 | 183.205 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.64551073 | 54.44 | 82.22 | 27.78 | 541752.47 | 1.5888 | 1.620724 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | Sensible | 8607.09 | 8607.09 | 1.0000 | 1.41129634 | 1.202203 | 16.70 | 12.95 | 0.00800000 | 37036.7 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.07529092 | 60.00 | 32.22 | 27.78 | 0.000 | 8607.09 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.58 | 0.00700452 | 21.00 | 0.00700452 | 44.2212 | 2433.66 | 0.00 | 8655.13 | 8655.13 | 1.41129634 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 22.61 | 15.45 | 0.00800000 | 43067.5 | |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9229.312 | 9229.312 | 0.404432 | 0.00008074 | 235.261 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.64551073 | 54.44 | 82.22 | 27.78 | 541752.47 | 1.7036 | 1.737889 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | Sensible | 9229.31 | 9229.31 | 1.0000 | 0.47477312 | 0.404432 | 16.70 | 12.95 | 0.00800000 | 37036.7 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.08073381 | 60.00 | 32.22 | 27.78 | 0.000 | 9229.31 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 21.00 | 0.00786215 | 21.00 | 0.00786215 | 49.5611 | 7148.14 | 0.00 | 9276.63 | 9276.63 | 0.47477312 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 35.76 | 19.90 | 0.00800000 | 56473.8 | |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 75158.601 | -999.000 | 2.051317 | 0.00214953 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1029.6885 | 1004.8586 | 1.1739 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.40800857 | 4197.9300 | 999.8980 | 26.71678098 | 15.03 | 6.70 | 8.33 | 934252.62 | 8.0448 | 8.044784 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | Sensible | 75158.60 | 45858.12 | 1.0000 | 2.40809323 | 2.051317 | 30.30 | 21.83 | 0.01336696 | 64629.5 | 11.91 | 11.51 | 0.00850000 | 33418.7 | 2.14930720 | 6.70 | 15.03 | 8.33 | 2195.006 | 72963.59 | 30.30 | 0.01336696 | 21.83 | 2.05124512 | 99.9965 | 21.11 | 0.00864744 | 21.11 | 0.00864816 | 54.0788 | 182095.42 | 0.00 | 76167.93 | 46274.27 | 2.40809323 | 30.30 | 22.13 | 0.01336696 | 64629.5 | 11.64 | 11.56 | 0.00844586 | 32999.6 | |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 23955.952 | 23955.952 | 0.615395 | 0.00020958 | 376.643 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.40800857 | 4197.9300 | 999.8980 | 4.64551073 | 54.44 | 82.22 | 27.78 | 541752.47 | 4.4219 | 4.510930 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 23955.95 | 23955.95 | 1.0000 | 0.72242797 | 0.615395 | -16.30 | -16.30 | 0.00092409 | -14095.8 | 16.70 | 12.95 | 0.00800000 | 37036.7 | 0.20955574 | 60.00 | 32.22 | 27.78 | 0.000 | 23955.95 | -16.30 | 0.00092409 | -16.30 | 2.05124512 | 333.3216 | 21.11 | 0.00775066 | 21.11 | 0.00775139 | 48.5395 | 117441.95 | 0.00 | 19372.81 | 19372.81 | 0.72242797 | 2.80 | -2.91 | 0.00092409 | 5129.5 | 29.44 | 11.28 | 0.00092409 | 31945.7 | |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 642888.977 | -999.000 | 22.239748 | 0.01838654 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.4172 | 1004.8586 | 1.1739 | VAV WITH REHEAT FAN | Fan:VariableVolume | 22.239748 | 26.10780337 | 4197.9300 | 999.8980 | 26.71678098 | 15.03 | 6.70 | 8.33 | 934252.62 | 68.8132 | 68.813184 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | Sensible | 642888.98 | 433511.10 | 1.0000 | 26.10780337 | 22.239748 | 27.30 | 19.69 | 0.01160721 | 57048.7 | 10.94 | 10.94 | 0.00850000 | 32424.3 | 18.38466775 | 6.70 | 15.03 | 8.33 | 49831.238 | 593057.74 | 30.30 | 0.01336696 | 21.83 | 11.66146000 | 52.4352 | 23.99 | 0.00966673 | 23.99 | 0.00962778 | 50.4581 | 298167.60 | 0.00 | 652984.36 | 430647.01 | 26.10780337 | 27.30 | 19.98 | 0.01160721 | 57048.7 | 11.23 | 11.17 | 0.00823022 | 32037.6 | |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 259723.040 | 259723.040 | 6.671924 | 0.00227217 | 4083.442 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | VAV WITH REHEAT FAN | Fan:VariableVolume | 22.239748 | 26.10780337 | 4197.9300 | 999.8980 | 4.64551073 | 54.44 | 82.22 | 27.78 | 541752.47 | 47.9413 | 48.906112 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | Sensible | 259723.04 | 259723.04 | 1.0000 | 7.83234101 | 6.671924 | -16.30 | -16.30 | 0.00092409 | -14095.8 | 16.70 | 12.95 | 0.00800000 | 37036.7 | 2.27193867 | 60.00 | 32.22 | 27.78 | 0.000 | 259723.04 | -16.30 | 0.00092409 | -16.30 | 11.66146000 | 174.7841 | 20.98 | 0.00775225 | 21.02 | 0.00776472 | 48.8912 | 69170.78 | 0.00 | 210033.98 | 210033.98 | 7.83234101 | 2.80 | -2.91 | 0.00092409 | 5129.5 | 29.44 | 11.28 | 0.00092409 | 31945.7 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:40
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - | |||
VAV WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 22.24 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | VAV WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000610 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LAUNDRY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CAFE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001448 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_3 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
KITCHEN_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003556 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 339.50 | 7148.50 | 1.83 |
RETAIL_1_FLR_1 | 2763.50 | 7535.00 | 2017.50 |
RETAIL_2_FLR_1 | 1272.83 | 7172.17 | 503.00 |
MECH_FLR_1 | 1552.33 | 7838.83 | 1336.50 |
STORAGE_FLR_1 | 1650.00 | 8321.83 | 1609.50 |
LAUNDRY_FLR_1 | 6743.50 | 3299.50 | 2490.17 |
CAFE_FLR_1 | 2767.50 | 6438.17 | 1174.17 |
LOBBY_FLR_1 | 1816.83 | 6510.00 | 621.83 |
ROOM_1_FLR_3 | 2497.83 | 8341.33 | 2466.83 |
ROOM_2_FLR_3 | 3375.33 | 8077.00 | 3079.67 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 1761.33 | 8700.83 | 1746.83 |
ROOM_5_FLR_3 | 2419.17 | 8306.33 | 2411.50 |
ROOM_6_FLR_3 | 3182.17 | 8124.00 | 3002.83 |
CORRIDOR_FLR_3 | 1408.50 | 8525.67 | 1401.67 |
ROOM_1_FLR_6 | 3102.33 | 8244.83 | 3010.83 |
ROOM_2_FLR_6 | 3956.00 | 8015.17 | 3639.67 |
ROOM_3_MULT9_FLR_6 | 1984.50 | 8261.00 | 1960.50 |
BANQUET_FLR_6 | 3754.67 | 3719.00 | 628.33 |
DINING_FLR_6 | 4550.33 | 2553.33 | 572.17 |
KITCHEN_FLR_6 | 8108.50 | 6311.33 | 6046.50 |
CORRIDOR_FLR_6 | 1890.33 | 7593.00 | 1358.67 |
Facility | 8749.17 | 8760.00 | 7821.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4.17 | 2.00 | 4.17 | 2.00 |
ROOM_2_FLR_3 | 12.00 | 7.17 | 12.00 | 7.17 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 7.17 | 16.50 | 7.17 | 16.50 |
ROOM_5_FLR_3 | 5.83 | 0.00 | 5.83 | 0.00 |
ROOM_6_FLR_3 | 11.67 | 13.50 | 11.67 | 13.50 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 5.33 | 5.67 | 5.33 | 5.67 |
ROOM_2_FLR_6 | 12.67 | 12.67 | 12.67 | 12.67 |
ROOM_3_MULT9_FLR_6 | 1.17 | 3.67 | 1.17 | 3.67 |
BANQUET_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 17.67 | 37.17 | 17.67 | 37.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:40
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.74 | 106.50 | 4826.41 | 1.003 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 2.723 | 0.063 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 1.439 | 0.021 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.530 | 0.023 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.546 | 0.023 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 23.782 | 0.067 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.49 | 142.30 | 748.35 | 4.072 | 0.049 | 0.000 | 0.000 |
LOBBY_FLR_1 | 244.88 | 422.44 | 5183.56 | 1.859 | 0.020 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.355 | 0.081 | 0.000 | 0.063 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.355 | 0.081 | 0.000 | 0.055 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.403 | 0.036 | 0.000 | 0.101 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.355 | 0.081 | 0.000 | 0.063 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.355 | 0.081 | 0.000 | 0.064 |
CORRIDOR_FLR_3 | 12.15 | 20.96 | 1186.91 | 0.626 | 0.010 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.355 | 0.081 | 0.000 | 0.076 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.355 | 0.081 | 0.000 | 0.061 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.403 | 0.066 | 0.000 | 0.121 |
BANQUET_FLR_6 | 144.86 | 249.90 | 1010.89 | 4.813 | 0.024 | 0.000 | 0.000 |
DINING_FLR_6 | 144.86 | 249.90 | 1010.89 | 5.210 | 0.024 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.89 | 22.24 | 314.87 | 22.290 | 0.068 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.86 | 22.18 | 1256.16 | 1.176 | 0.016 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.74 | 106.50 | 4826.41 | 0.814 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 2.245 | 0.001 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 1.363 | 0.000 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.507 | 0.000 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.512 | 0.000 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 19.666 | 0.001 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.49 | 142.30 | 748.35 | 3.853 | 0.001 | 0.000 | 0.000 |
LOBBY_FLR_1 | 244.88 | 422.44 | 5183.56 | 1.748 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
CORRIDOR_FLR_3 | 12.15 | 20.96 | 1186.91 | 0.520 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.000 | 0.001 | 0.000 | 0.000 |
BANQUET_FLR_6 | 144.86 | 249.90 | 1010.89 | 3.946 | 0.000 | 0.000 | 0.000 |
DINING_FLR_6 | 144.86 | 249.90 | 1010.89 | 4.143 | 0.000 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.89 | 22.24 | 314.87 | 13.456 | 0.001 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.86 | 22.18 | 1256.16 | 1.123 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:40
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | VAV WITH REHEAT | 61.74 | 106.50 | 4826.41 | 1978.83 | 0.0000 | 0.854 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 6.28 | 10.83 | 265.76 | 67.07 | 0.0000 | 0.079 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 7.27 | 12.54 | 307.76 | 77.67 | 0.0000 | 0.092 |
MECH_FLR_1 | VAV WITH REHEAT | 1.54 | 2.65 | 650.80 | 164.24 | 0.0000 | 0.000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 1.18 | 2.04 | 375.47 | 94.76 | 0.0000 | 0.058 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 4.87 | 8.40 | 309.22 | 78.04 | 0.0000 | 0.000 |
CAFE_FLR_1 | VAV WITH REHEAT | 82.49 | 142.30 | 748.35 | 188.86 | 0.0000 | 0.676 |
LOBBY_FLR_1 | VAV WITH REHEAT | 244.88 | 422.44 | 5183.56 | 1308.19 | 0.0000 | 1.894 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 1.50 | 74.75 | 24.52 | 0.0000 | 0.837 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.837 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 12.15 | 20.96 | 1186.91 | 389.40 | 0.0000 | 0.475 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.015 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.015 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.099 |
BANQUET_FLR_6 | VAV WITH REHEAT | 144.86 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
DINING_FLR_6 | VAV WITH REHEAT | 144.86 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 12.89 | 22.24 | 314.87 | 103.30 | 0.0000 | 0.367 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 12.86 | 22.18 | 1256.16 | 412.12 | 0.0000 | 0.126 |
Total Facility | 872.55 | 1604.23 | 35184.81 | 11345.29 | 0.0000 | 137.584 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 41668730.54 | 0.00 | 41668730.54 | 0.00 | 41668730.54 | 26946214.98 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_1_FLR_1 | 6258824.71 | 0.00 | 6258824.71 | 143773.36 | 6402598.07 | 2498216.28 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_2_FLR_1 | 3817828.74 | 0.00 | 3817828.74 | 55496.70 | 3873325.44 | 2892943.94 | 0.00 | 0.00 | 8760.00 | 0.00 |
MECH_FLR_1 | 2979369.02 | 0.00 | 2979369.02 | 131161.23 | 3110530.25 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
STORAGE_FLR_1 | 1771405.42 | 0.00 | 1771405.42 | 75672.80 | 1847078.22 | 1821682.01 | 8757.67 | 0.22 | 2.11 | 0.00 |
LAUNDRY_FLR_1 | 63340262.29 | 0.00 | 63340262.29 | 179093.96 | 63519356.25 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
CAFE_FLR_1 | 26250935.30 | 0.00 | 26250935.30 | 317819.16 | 26568754.46 | 21330615.53 | 0.00 | 0.00 | 8760.00 | 0.00 |
LOBBY_FLR_1 | 82882373.51 | 0.00 | 82882373.51 | 908081.92 | 83790455.43 | 59728886.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
ROOM_1_FLR_3 | 1460156.71 | 64203.78 | 1524360.49 | 83450.57 | 1607811.06 | 1946875.62 | 2190.00 | 5930.00 | 640.00 | 0.00 |
ROOM_2_FLR_3 | 1459985.63 | 55558.58 | 1515544.22 | 83444.20 | 1598988.42 | 1946647.51 | 2190.00 | 6027.31 | 542.69 | 0.00 |
ROOM_3_MULT19_FLR_3 | 1099911.97 | 79.13 | 1099991.10 | 23283.64 | 1123274.74 | 26397887.27 | 8395.00 | 365.00 | 0.00 | 365.83 |
ROOM_4_MULT19_FLR_3 | 19803829.30 | 64828.99 | 19868658.29 | 23290.01 | 19891948.30 | 26405105.73 | 2190.00 | 5932.15 | 637.85 | 0.00 |
ROOM_5_FLR_3 | 1460156.71 | 64264.64 | 1524421.36 | 83450.57 | 1607871.92 | 1946875.62 | 2190.00 | 5930.00 | 640.00 | 0.00 |
ROOM_6_FLR_3 | 1459985.63 | 64880.06 | 1524865.70 | 83444.20 | 1608309.90 | 1946647.51 | 2190.00 | 5932.78 | 637.22 | 0.00 |
CORRIDOR_FLR_3 | 25665672.15 | 0.00 | 25665672.15 | 100908.52 | 25766580.67 | 14972100.18 | 0.00 | 0.00 | 8760.00 | 0.00 |
ROOM_1_FLR_6 | 365039.18 | 77904.18 | 442943.35 | 83468.20 | 526411.56 | 486718.90 | 2022.56 | 5930.27 | 807.17 | 0.00 |
ROOM_2_FLR_6 | 364996.41 | 62094.75 | 427091.16 | 83461.83 | 510552.99 | 486661.88 | 2064.28 | 6062.51 | 633.21 | 0.00 |
ROOM_3_MULT9_FLR_6 | 2345190.31 | 77856.34 | 2423046.65 | 42705.25 | 2465751.91 | 3126920.42 | 2190.00 | 5929.00 | 641.00 | 0.00 |
BANQUET_FLR_6 | 41698214.33 | 0.00 | 41698214.33 | 203808.37 | 41902022.70 | 37458366.31 | 4087.74 | 232.76 | 4439.50 | 0.00 |
DINING_FLR_6 | 45127497.04 | 0.00 | 45127497.04 | 203808.37 | 45331305.41 | 37458366.31 | 0.00 | 2913.25 | 5846.75 | 0.00 |
KITCHEN_FLR_6 | 60173085.52 | 0.00 | 60173085.52 | 182455.74 | 60355541.26 | 11584760.86 | 0.00 | 0.00 | 8760.00 | 0.00 |
CORRIDOR_FLR_6 | 12773256.22 | 0.00 | 12773256.22 | 178577.50 | 12951833.72 | 3961413.96 | 0.00 | 0.00 | 8760.00 | 0.00 |
Total Facility | 0.21E+10 | 6769351.17 | 0.21E+10 | 8409416.39 | 0.21E+10 | 0.43E+10 | 8760.00 | 7671.77 | 8760.00 | 365.83 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 1.3213 | 0.0000 | 1.3213 | 0.0000 | 1.3213 | 0.8545 | 0.00 | 0.00 | 8760.00 |
RETAIL_1_FLR_1 | 0.1985 | 0.0000 | 0.1985 | 0.0046 | 0.2030 | 0.0792 | 0.00 | 0.00 | 8760.00 |
RETAIL_2_FLR_1 | 0.1211 | 0.0000 | 0.1211 | 0.0018 | 0.1228 | 0.0917 | 0.00 | 0.00 | 8760.00 |
MECH_FLR_1 | 0.0945 | 0.0000 | 0.0945 | 0.0042 | 0.0986 | 0.0000 | 0.00 | 0.00 | 8760.00 |
STORAGE_FLR_1 | 0.0562 | 0.0000 | 0.0562 | 0.0024 | 0.0586 | 0.0578 | 8757.67 | 0.22 | 2.11 |
LAUNDRY_FLR_1 | 2.0085 | 0.0000 | 2.0085 | 0.0057 | 2.0142 | 0.0000 | 0.00 | 0.00 | 8760.00 |
CAFE_FLR_1 | 0.8324 | 0.0000 | 0.8324 | 0.0101 | 0.8425 | 0.6764 | 0.00 | 0.00 | 8760.00 |
LOBBY_FLR_1 | 2.6282 | 0.0000 | 2.6282 | 0.0288 | 2.6570 | 1.8940 | 0.00 | 0.00 | 8760.00 |
ROOM_1_FLR_3 | 0.0463 | 0.0020 | 0.0483 | 0.0026 | 0.0510 | 0.0617 | 2190.00 | 5930.00 | 640.00 |
ROOM_2_FLR_3 | 0.0463 | 0.0018 | 0.0481 | 0.0026 | 0.0507 | 0.0617 | 2190.00 | 6027.31 | 542.69 |
ROOM_4_MULT19_FLR_3 | 0.6280 | 0.0021 | 0.6300 | 0.0007 | 0.6308 | 0.8373 | 2190.00 | 5932.15 | 637.85 |
ROOM_5_FLR_3 | 0.0463 | 0.0020 | 0.0483 | 0.0026 | 0.0510 | 0.0617 | 2190.00 | 5930.00 | 640.00 |
ROOM_6_FLR_3 | 0.0463 | 0.0021 | 0.0484 | 0.0026 | 0.0510 | 0.0617 | 2190.00 | 5932.78 | 637.22 |
CORRIDOR_FLR_3 | 0.8139 | 0.0000 | 0.8139 | 0.0032 | 0.8171 | 0.4748 | 0.00 | 0.00 | 8760.00 |
ROOM_1_FLR_6 | 0.0116 | 0.0025 | 0.0140 | 0.0026 | 0.0167 | 0.0154 | 2022.56 | 5930.27 | 807.17 |
ROOM_2_FLR_6 | 0.0116 | 0.0020 | 0.0135 | 0.0026 | 0.0162 | 0.0154 | 2064.28 | 6062.51 | 633.21 |
ROOM_3_MULT9_FLR_6 | 0.0744 | 0.0025 | 0.0768 | 0.0014 | 0.0782 | 0.0992 | 2190.00 | 5929.00 | 641.00 |
BANQUET_FLR_6 | 1.3222 | 0.0000 | 1.3222 | 0.0065 | 1.3287 | 1.1878 | 4087.74 | 232.76 | 4439.50 |
DINING_FLR_6 | 1.4310 | 0.0000 | 1.4310 | 0.0065 | 1.4374 | 1.1878 | 0.00 | 2913.25 | 5846.75 |
KITCHEN_FLR_6 | 1.9081 | 0.0000 | 1.9081 | 0.0058 | 1.9139 | 0.3674 | 0.00 | 0.00 | 8760.00 |
CORRIDOR_FLR_6 | 0.4050 | 0.0000 | 0.4050 | 0.0057 | 0.4107 | 0.1256 | 0.00 | 0.00 | 8760.00 |
Total Facility | 64.7417 | 0.2145 | 64.9561 | 0.2105 | 65.1667 | 73.9670 | 8760.00 | 7671.77 | 8760.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
FLR_3_DOAS | 41093930.13 | 531670.45 | 41625600.58 | 64690340.46 | 8747.33 | 6.43 | 6.24 | 0.00 |
VAV WITH REHEAT | 0.57E+09 | 0.00 | 0.57E+09 | 0.22E+09 | 0.00 | 0.00 | 8760.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
FLR_3_DOAS | 1.3031 | 0.0169 | 1.3199 | 2.0513 | 8747.33 | 6.43 | 6.24 |
VAV WITH REHEAT | 18.1093 | 0.0000 | 18.1093 | 6.9969 | 0.00 | 0.00 | 8760.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
FLR_3_DOAS | 0.00 | 0.00 | 0.00 | 0.00 | 6935.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
VAV WITH REHEAT | 0.00 | 0.00 | 3880.24 | 0.00 | 0.00 | 0.00 | 4879.76 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
FLR_3_DOAS | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.6460 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
VAV WITH REHEAT | 0.0000 | 0.0000 | 18.5255 | 0.0000 | 0.0000 | 0.0000 | 17.7821 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:40
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1333 |
Defaulted Fields | 1182 |
Fields with Defaults | 4000 |
Autosized Fields | 349 |
Autosizable Fields | 402 |
Autocalculated Fields | 280 |
Autocalculatable Fields | 539 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:21:40
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 4904.20 | 65086.02 | 13-MAY-05:00 | 381548.78 | 21-JUL-20:00 |
Electricity:Building | 2447.00 | 31181.31 | 10-JUN-05:00 | 151313.73 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 304.40 | 3493.55 | 02-JAN-02:10 | 22822.84 | 02-JAN-20:10 |
Electricity:SpaceType:GENERAL | 2439.91 | 31040.16 | 10-JUN-05:00 | 151072.40 | 02-JAN-20:10 |
InteriorLights:Electricity | 781.73 | 6838.19 | 10-JUN-05:00 | 64632.59 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 161.29 | 1465.65 | 02-JAN-02:10 | 13190.31 | 02-JAN-20:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 781.73 | 6838.19 | 10-JUN-05:00 | 64632.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 781.73 | 6838.19 | 10-JUN-05:00 | 64632.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 161.29 | 1465.65 | 02-JAN-02:10 | 13190.31 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 781.73 | 6838.19 | 10-JUN-05:00 | 64632.59 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 17.49 | 210.74 | 02-JAN-02:10 | 1283.20 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 7.31 | 66.40 | 02-JAN-02:10 | 597.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 7.31 | 66.40 | 02-JAN-02:10 | 597.59 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 20.26 | 244.03 | 02-JAN-02:10 | 1485.95 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 8.46 | 76.89 | 02-JAN-02:10 | 692.02 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 8.46 | 76.89 | 02-JAN-02:10 | 692.02 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 20.84 | 252.75 | 02-JAN-02:10 | 1523.62 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.37 | 76.02 | 02-JAN-02:10 | 684.18 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.37 | 76.02 | 02-JAN-02:10 | 684.18 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 6.68 | 78.96 | 02-JAN-02:10 | 493.99 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 3.08 | 27.98 | 02-JAN-02:10 | 251.84 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 3.08 | 27.98 | 02-JAN-02:10 | 251.84 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 71.91 | 998.82 | 02-JAN-02:10 | 4897.88 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 3.98 | 36.12 | 02-JAN-02:10 | 325.08 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 3.98 | 36.12 | 02-JAN-02:10 | 325.08 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 28.37 | 318.54 | 03-JUN-05:00 | 2666.80 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 14.03 | 83.19 | 01-JAN-13:10 | 1701.53 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 | 14.03 | 83.19 | 01-JAN-13:10 | 1701.53 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 258.89 | 3142.86 | 20-MAY-05:00 | 19534.01 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 109.89 | 1031.45 | 20-MAY-05:00 | 9504.80 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 109.89 | 1031.45 | 20-MAY-05:00 | 9504.80 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 19.72 | 257.38 | 01-JAN-02:10 | 1438.51 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 19.72 | 257.35 | 01-JAN-02:10 | 1438.34 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 305.38 | 4267.82 | 01-JAN-02:10 | 22404.45 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 110.39 | 934.58 | 01-JAN-02:10 | 8496.21 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 110.39 | 934.58 | 01-JAN-02:10 | 8496.21 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 305.47 | 4268.99 | 01-JAN-02:10 | 22410.58 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 110.42 | 934.84 | 01-JAN-02:10 | 8498.53 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 110.42 | 934.84 | 01-JAN-02:10 | 8498.53 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 19.72 | 257.38 | 01-JAN-02:10 | 1438.51 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 19.72 | 257.35 | 01-JAN-02:10 | 1438.34 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 4.93 | 64.34 | 01-JAN-02:10 | 359.63 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 2.31 | 19.57 | 01-JAN-02:10 | 177.88 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 2.31 | 19.57 | 01-JAN-02:10 | 177.88 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 4.93 | 64.34 | 01-JAN-02:10 | 359.59 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 2.31 | 19.56 | 01-JAN-02:10 | 177.86 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 2.31 | 19.56 | 01-JAN-02:10 | 177.86 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 36.17 | 505.54 | 01-JAN-02:10 | 2653.88 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 13.08 | 110.70 | 01-JAN-02:10 | 1006.40 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 13.08 | 110.70 | 01-JAN-02:10 | 1006.40 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 206.55 | 2470.64 | 10-JUN-05:00 | 9735.93 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 30.69 | 221.34 | 10-JUN-05:00 | 2988.03 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 30.69 | 221.34 | 10-JUN-05:00 | 2988.03 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 206.55 | 2470.64 | 10-JUN-05:00 | 9735.93 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 30.69 | 221.34 | 10-JUN-05:00 | 2988.03 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 | 30.69 | 221.34 | 10-JUN-05:00 | 2988.03 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 453.81 | 6249.79 | 02-JAN-02:10 | 18934.39 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 12.97 | 117.87 | 02-JAN-02:10 | 1060.81 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 12.97 | 117.87 | 02-JAN-02:10 | 1060.81 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1658.18 | 24201.97 | 02-JAN-02:10 | 89171.45 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 1658.18 | 24201.97 | 02-JAN-02:10 | 89171.45 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 433.74 | 5990.78 | 01-JAN-00:10 | 16487.34 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 410.33 | 5248.28 | 01-JAN-00:10 | 15744.84 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
Refrigeration:Electricity | 61.74 | 1114.64 | 11-DEC-23:30 | 3262.96 | 15-SEP-06:20 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
Electricity:Plant | 767.69 | 2753.70 | 07-APR-01:00 | 168459.13 | 21-JUL-20:00 |
LowTempRefrigeration:Refrigeration:Electricity | 20.42 | 0.00 | 01-JAN-11:10 | 1893.43 | 16-JUL-10:50 |
MedTempRefrigeration:Refrigeration:Electricity | 34.23 | 944.49 | 07-FEB-04:10 | 1203.03 | 17-MAY-13:10 |
Fans:Electricity | 511.58 | 11766.27 | 11-FEB-08:10 | 34071.56 | 10-AUG-21:10 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 703.72 | 12623.25 | 19-NOV-15:00 | 44852.31 | 10-AUG-21:10 |
ExteriorEquipment:Electricity | 813.77 | 9999.82 | 02-JAN-02:20 | 49607.07 | 02-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 21.77 | 380.99 | 10-JUN-05:00 | 1291.59 | 02-JAN-21:10 |
ElectricityPurchased:Facility | 4904.20 | 65086.02 | 13-MAY-05:00 | 381548.78 | 21-JUL-20:00 |
ElectricityPurchased:Plant | 4904.20 | 65086.02 | 13-MAY-05:00 | 381548.78 | 21-JUL-20:00 |
Cogeneration:ElectricityPurchased | 4904.20 | 65086.02 | 13-MAY-05:00 | 381548.78 | 21-JUL-20:00 |
General:Cogeneration:ElectricityPurchased | 4904.20 | 65086.02 | 13-MAY-05:00 | 381548.78 | 21-JUL-20:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 4904.20 | 65086.02 | 13-MAY-05:00 | 381548.78 | 21-JUL-20:00 |
ElectricityNet:Plant | 4904.20 | 65086.02 | 13-MAY-05:00 | 381548.78 | 21-JUL-20:00 |
Cogeneration:ElectricityNet | 4904.20 | 65086.02 | 13-MAY-05:00 | 381548.78 | 21-JUL-20:00 |
General:Cogeneration:ElectricityNet | 4904.20 | 65086.02 | 13-MAY-05:00 | 381548.78 | 21-JUL-20:00 |
General:Fans:Electricity | 511.58 | 11766.27 | 11-FEB-08:10 | 34071.56 | 10-AUG-21:10 |
ExteriorLights:Electricity | 193.78 | 0.00 | 01-JAN-08:00 | 12338.45 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 193.78 | 0.00 | 01-JAN-08:00 | 12338.45 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 789.09 | 9600.00 | 01-JAN-00:10 | 48128.80 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 2.91 | 18.80 | 01-JAN-00:10 | 188.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 170.38 | 0.00 | 11-JAN-11:10 | 9938.94 | 02-JUN-09:00 |
General:HeatRecovery:Electricity | 170.38 | 0.00 | 11-JAN-11:10 | 9938.94 | 02-JUN-09:00 |
WaterSystems:Electricity | 94.78 | 1222.48 | 07-AUG-00:50 | 4751.13 | 19-APR-18:50 |
Water Heater:WaterSystems:Electricity | 94.78 | 1222.48 | 07-AUG-00:50 | 4751.13 | 19-APR-18:50 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 546.87 | 0.00 | 01-JAN-00:10 | 158511.57 | 21-JUL-20:00 |
General:Cooling:Electricity | 546.87 | 0.00 | 01-JAN-00:10 | 158511.57 | 21-JUL-20:00 |
Pumps:Electricity | 71.38 | 47.91 | 24-OCT-11:00 | 4349.59 | 21-JUL-20:00 |
General:Pumps:Electricity | 71.38 | 47.91 | 24-OCT-11:00 | 4349.59 | 21-JUL-20:00 |
WIRED_LTG_ELECTRICITY | 27.52 | 0.00 | 01-JAN-00:10 | 2275.07 | 02-JAN-20:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 6014.02 | 25736.49 | 16-AUG-01:20 | 601063.55 | 06-FEB-19:20 |
NaturalGas:Building | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Laundry:InteriorEquipment:NaturalGas | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
NaturalGas:Plant | 4225.18 | 12374.60 | 16-AUG-01:20 | 513443.77 | 06-FEB-19:20 |
WaterSystems:NaturalGas | 2802.62 | 12374.60 | 16-AUG-01:20 | 265171.40 | 14-FEB-21:20 |
Water Heater:WaterSystems:NaturalGas | 2802.62 | 12374.60 | 16-AUG-01:20 | 265171.40 | 14-FEB-21:20 |
Heating:NaturalGas | 1422.56 | 0.00 | 14-MAR-10:10 | 285359.31 | 06-FEB-09:10 |
Boiler:Heating:NaturalGas | 1422.56 | 0.00 | 14-MAR-10:10 | 285359.31 | 06-FEB-09:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 2255.96 | 0.00 | 01-JAN-00:10 | 621682.38 | 21-JUL-20:00 |
PlantLoopCoolingDemand:HVAC | 2255.96 | 0.00 | 01-JAN-00:10 | 621682.38 | 21-JUL-20:00 |
CoolingCoils:PlantLoopCoolingDemand | 2255.96 | 0.00 | 01-JAN-00:10 | 621682.38 | 21-JUL-20:00 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 05-JUN-20:10 |
Water:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 05-JUN-20:10 |
WaterSystems:Water | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 05-JUN-20:10 |
Water Heater:WaterSystems:Water | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:20 |
MainsWater:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 05-JUN-20:10 |
MainsWater:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 05-JUN-20:10 |
WaterSystems:MainsWater | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 05-JUN-20:10 |
Water Heater:WaterSystems:MainsWater | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:20 |
WaterUse:WaterSystems:Water | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 31-MAY-07:00 |
WaterUse:WaterSystems:MainsWater | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 31-MAY-07:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 19183.81 | 133966.87 | 10-NOV-11:10 | 2481915.64 | 20-JUL-21:00 |
EnergyTransfer:Building | 4784.85 | 79237.12 | 25-JAN-11:10 | 325124.98 | 18-JUL-18:20 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 712.20 | 10257.62 | 07-FEB-04:00 | 36421.20 | 16-JUL-10:40 |
Refrigeration:EnergyTransfer | 182.32 | 4017.12 | 11-DEC-23:10 | 10367.52 | 15-SEP-06:20 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 91.16 | 2008.56 | 11-DEC-23:10 | 5183.76 | 15-SEP-06:20 |
General:Refrigeration:EnergyTransfer | 91.16 | 2008.56 | 11-DEC-23:10 | 5183.76 | 15-SEP-06:20 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 91.16 | 2008.56 | 11-DEC-23:10 | 5183.76 | 15-SEP-06:20 |
EnergyTransfer:Plant | 7059.80 | 17994.37 | 07-APR-01:00 | 1436608.01 | 21-JUL-20:00 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 21.58 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 69.58 | 1783.46 | 07-FEB-04:10 | 2559.10 | 17-MAY-13:10 |
EnergyTransfer:Zone:BASEMENT | 388.56 | 9375.36 | 08-MAY-13:10 | 21095.96 | 13-OCT-21:00 |
Heating:EnergyTransfer | 195.49 | 0.00 | 11-JAN-08:20 | 80587.97 | 07-FEB-05:00 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 195.49 | 0.00 | 11-JAN-08:20 | 80587.97 | 07-FEB-05:00 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 4498.20 | 65852.05 | 06-FEB-11:10 | 322418.41 | 18-JUL-18:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 388.56 | 9375.36 | 08-MAY-13:10 | 21095.96 | 13-OCT-21:00 |
General:Cooling:EnergyTransfer | 4498.20 | 65852.05 | 06-FEB-11:10 | 322418.41 | 18-JUL-18:20 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 388.56 | 9375.36 | 08-MAY-13:10 | 21095.96 | 13-OCT-21:00 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 35.91 | 0.03 | 19-DEC-07:00 | 4188.87 | 21-SEP-13:00 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 2.01 | 0.00 | 01-JAN-20:20 | 1418.12 | 07-FEB-07:20 |
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 2.01 | 0.00 | 01-JAN-20:20 | 1418.12 | 07-FEB-07:20 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 33.90 | 0.00 | 01-JAN-00:10 | 4188.87 | 21-SEP-13:00 |
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 33.90 | 0.00 | 01-JAN-00:10 | 4188.87 | 21-SEP-13:00 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 32.27 | 143.09 | 06-FEB-12:40 | 1984.33 | 10-AUG-21:00 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 32.27 | 143.09 | 06-FEB-12:40 | 1984.33 | 10-AUG-21:00 |
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 32.27 | 143.09 | 06-FEB-12:40 | 1984.33 | 10-AUG-21:00 |
EnergyTransfer:Zone:MECH_FLR_1 | 20.56 | 0.02 | 08-MAR-11:00 | 1639.97 | 21-JUL-20:00 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.37 | 0.00 | 01-JAN-00:10 | 548.41 | 07-FEB-11:00 |
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.37 | 0.00 | 01-JAN-00:10 | 548.41 | 07-FEB-11:00 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 20.19 | 0.00 | 01-JAN-13:20 | 1639.97 | 21-JUL-20:00 |
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 20.19 | 0.00 | 01-JAN-13:20 | 1639.97 | 21-JUL-20:00 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 11.33 | 0.01 | 15-DEC-12:50 | 729.01 | 21-JUL-10:40 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.98 | 0.00 | 01-JAN-19:40 | 539.19 | 07-FEB-10:50 |
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.98 | 0.00 | 01-JAN-19:40 | 539.19 | 07-FEB-10:50 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 10.36 | 0.00 | 01-JAN-00:10 | 729.01 | 21-JUL-10:40 |
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 10.36 | 0.00 | 01-JAN-00:10 | 729.01 | 21-JUL-10:40 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 590.99 | 8952.32 | 07-FEB-05:00 | 38699.06 | 21-JUL-20:00 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 590.99 | 8952.32 | 07-FEB-05:00 | 38699.06 | 21-JUL-20:00 |
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 590.99 | 8952.32 | 07-FEB-05:00 | 38699.06 | 21-JUL-20:00 |
EnergyTransfer:Zone:CAFE_FLR_1 | 215.04 | 40.31 | 06-FEB-13:40 | 14466.48 | 11-OCT-12:30 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.01 | 0.00 | 01-JAN-00:10 | 1291.96 | 06-FEB-09:20 |
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.01 | 0.00 | 01-JAN-00:10 | 1291.96 | 06-FEB-09:20 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 215.02 | 0.00 | 06-FEB-09:10 | 14466.48 | 11-OCT-12:30 |
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 215.02 | 0.00 | 06-FEB-09:10 | 14466.48 | 11-OCT-12:30 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 741.44 | 6491.57 | 06-FEB-13:30 | 39829.44 | 20-JUL-21:10 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 741.44 | 6491.57 | 06-FEB-13:30 | 39829.44 | 20-JUL-21:10 |
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 741.44 | 6491.57 | 06-FEB-13:30 | 39829.44 | 20-JUL-21:10 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 61.38 | 0.00 | 01-JAN-08:10 | 11267.40 | 21-SEP-15:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 21.50 | 0.00 | 01-JAN-08:10 | 6169.79 | 06-FEB-09:20 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 21.50 | 0.00 | 01-JAN-08:10 | 6169.79 | 06-FEB-09:20 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 39.88 | 0.00 | 01-JAN-00:10 | 11267.40 | 21-SEP-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 39.88 | 0.00 | 01-JAN-00:10 | 11267.40 | 21-SEP-15:10 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 54.30 | 0.00 | 01-JAN-08:10 | 11347.41 | 08-JUL-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 25.40 | 0.00 | 01-JAN-08:10 | 6282.84 | 06-FEB-09:20 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 25.40 | 0.00 | 01-JAN-08:10 | 6282.84 | 06-FEB-09:20 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 28.89 | 0.00 | 01-JAN-00:10 | 11347.41 | 08-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 28.89 | 0.00 | 01-JAN-00:10 | 11347.41 | 08-JUL-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 223.05 | 0.00 | 01-JAN-00:10 | 53088.51 | 11-OCT-12:30 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 3.63 | 0.00 | 01-JAN-00:10 | 18919.44 | 07-FEB-05:00 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 3.63 | 0.00 | 01-JAN-00:10 | 18919.44 | 07-FEB-05:00 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 219.43 | 0.00 | 01-JAN-00:10 | 53088.51 | 11-OCT-12:30 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 219.43 | 0.00 | 01-JAN-00:10 | 53088.51 | 11-OCT-12:30 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 342.76 | 0.00 | 01-JAN-08:10 | 70604.22 | 19-JUN-22:10 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 51.77 | 0.00 | 01-JAN-08:10 | 34886.25 | 11-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 51.77 | 0.00 | 01-JAN-08:10 | 34886.25 | 11-DEC-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 290.99 | 0.00 | 01-JAN-00:10 | 70604.22 | 19-JUN-22:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 290.99 | 0.00 | 01-JAN-00:10 | 70604.22 | 19-JUN-22:10 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 60.79 | 0.00 | 01-JAN-08:10 | 10398.30 | 04-JUL-08:10 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 21.15 | 0.00 | 01-JAN-08:10 | 6184.27 | 06-FEB-19:20 |
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 21.15 | 0.00 | 01-JAN-08:10 | 6184.27 | 06-FEB-19:20 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 39.63 | 0.00 | 01-JAN-00:10 | 10398.30 | 04-JUL-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 39.63 | 0.00 | 01-JAN-00:10 | 10398.30 | 04-JUL-08:10 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 54.18 | 0.00 | 01-JAN-08:10 | 11944.19 | 05-AUG-09:00 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 24.92 | 0.00 | 01-JAN-08:10 | 6310.74 | 06-FEB-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 24.92 | 0.00 | 01-JAN-08:10 | 6310.74 | 06-FEB-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 29.26 | 0.00 | 01-JAN-00:10 | 11944.19 | 05-AUG-09:00 |
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 29.26 | 0.00 | 01-JAN-00:10 | 11944.19 | 05-AUG-09:00 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 163.92 | 0.13 | 05-FEB-02:30 | 10330.95 | 21-JUL-10:40 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 1.50 | 0.00 | 01-JAN-00:10 | 3710.88 | 06-FEB-09:20 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 1.50 | 0.00 | 01-JAN-00:10 | 3710.88 | 06-FEB-09:20 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 162.42 | 0.00 | 01-JAN-13:10 | 10330.95 | 21-JUL-10:40 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 162.42 | 0.00 | 01-JAN-13:10 | 10330.95 | 21-JUL-10:40 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 17.94 | 0.00 | 01-JAN-08:10 | 2972.45 | 21-SEP-15:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 8.15 | 0.00 | 01-JAN-08:10 | 1942.32 | 06-FEB-09:20 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 8.15 | 0.00 | 01-JAN-08:10 | 1942.32 | 06-FEB-09:20 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 9.79 | 0.00 | 01-JAN-00:10 | 2972.45 | 21-SEP-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 9.79 | 0.00 | 01-JAN-00:10 | 2972.45 | 21-SEP-15:10 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 16.61 | 0.00 | 01-JAN-08:10 | 3065.76 | 08-JUL-18:20 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 9.38 | 0.00 | 01-JAN-08:10 | 1930.80 | 06-FEB-09:20 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 9.38 | 0.00 | 01-JAN-08:10 | 1930.80 | 06-FEB-09:20 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 7.22 | 0.00 | 01-JAN-00:10 | 3065.76 | 08-JUL-18:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 7.22 | 0.00 | 01-JAN-00:10 | 3065.76 | 08-JUL-18:20 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 82.60 | 0.00 | 01-JAN-08:10 | 16202.20 | 21-SEP-15:10 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 22.43 | 0.00 | 01-JAN-08:10 | 8709.73 | 06-FEB-09:20 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 22.43 | 0.00 | 01-JAN-08:10 | 8709.73 | 06-FEB-09:20 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 60.17 | 0.00 | 01-JAN-00:10 | 16202.20 | 21-SEP-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 60.17 | 0.00 | 01-JAN-00:10 | 16202.20 | 21-SEP-15:10 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 418.95 | 7632.20 | 06-FEB-15:00 | 22921.78 | 20-JUL-21:20 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 418.95 | 7632.20 | 06-FEB-15:00 | 22921.78 | 20-JUL-21:20 |
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 418.95 | 7632.20 | 06-FEB-15:00 | 22921.78 | 20-JUL-21:20 |
EnergyTransfer:Zone:DINING_FLR_6 | 459.75 | 8641.62 | 06-FEB-15:00 | 24126.81 | 20-JUL-21:20 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 459.75 | 8641.62 | 06-FEB-15:00 | 24126.81 | 20-JUL-21:20 |
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 459.75 | 8641.62 | 06-FEB-15:00 | 24126.81 | 20-JUL-21:20 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 621.04 | 8232.15 | 07-FEB-04:00 | 31348.70 | 16-JUL-10:50 |
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 621.04 | 8232.15 | 07-FEB-04:00 | 31348.70 | 16-JUL-10:50 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 80.31 | 0.06 | 05-MAR-24:00 | 6206.74 | 21-JUL-13:30 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 2.28 | 0.00 | 01-JAN-00:10 | 2867.35 | 07-FEB-07:20 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 2.28 | 0.00 | 01-JAN-00:10 | 2867.35 | 07-FEB-07:20 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 78.02 | 0.00 | 01-JAN-04:20 | 6206.74 | 21-JUL-13:30 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 78.02 | 0.00 | 01-JAN-04:20 | 6206.74 | 21-JUL-13:30 |
PlantLoopHeatingDemand:Facility | 1808.81 | 9856.88 | 16-AUG-00:50 | 274503.95 | 07-FEB-07:20 |
PlantLoopHeatingDemand:Plant | 820.39 | 9856.88 | 16-AUG-00:50 | 60820.48 | 15-FEB-07:10 |
WaterSystems:PlantLoopHeatingDemand | 820.39 | 9856.88 | 16-AUG-00:50 | 60820.48 | 15-FEB-07:10 |
General:WaterSystems:PlantLoopHeatingDemand | 820.39 | 9856.88 | 16-AUG-00:50 | 60820.48 | 15-FEB-07:10 |
EnergyTransfer:HVAC | 7339.16 | 997.71 | 28-MAY-14:50 | 811670.78 | 20-JUL-20:20 |
HeatingCoils:EnergyTransfer | 988.42 | 0.00 | 14-MAR-10:10 | 232822.87 | 06-FEB-09:10 |
PlantLoopHeatingDemand:HVAC | 988.42 | 0.00 | 14-MAR-10:10 | 232822.87 | 06-FEB-09:10 |
HeatingCoils:PlantLoopHeatingDemand | 988.42 | 0.00 | 14-MAR-10:10 | 232822.87 | 06-FEB-09:10 |
CoolingCoils:EnergyTransfer | 2255.96 | 0.00 | 01-JAN-00:10 | 621682.38 | 21-JUL-20:00 |
HeatRecoveryForHeating:EnergyTransfer | 3943.90 | 0.00 | 11-JAN-11:10 | 519626.84 | 11-DEC-06:00 |
HeatRecoveryForCooling:EnergyTransfer | 150.88 | 0.00 | 01-JAN-00:10 | 250511.94 | 21-JUL-02:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 820.39 | 9856.88 | 16-AUG-00:50 | 60820.48 | 15-FEB-07:10 |
WaterUse:WaterSystems:EnergyTransfer | 820.39 | 9856.88 | 16-AUG-00:50 | 60820.48 | 15-FEB-07:10 |
Boilers:EnergyTransfer | 980.51 | 0.00 | 14-MAR-10:10 | 231174.00 | 06-FEB-09:10 |
Chillers:EnergyTransfer | 2310.44 | 0.00 | 01-JAN-00:10 | 623115.76 | 21-JUL-20:00 |
HeatRejection:EnergyTransfer | 2857.31 | 0.00 | 01-JAN-00:10 | 781627.33 | 21-JUL-20:00 |
General:HeatRejection:EnergyTransfer | 2857.31 | 0.00 | 01-JAN-00:10 | 781627.33 | 21-JUL-20:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:40
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -388.558 | 0.000 | 0.000 | 140.859 | 161.294 | 143.105 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -56.700 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 2.014 | -33.901 | 0.000 | 0.000 | 15.680 | 7.307 | 10.186 | 20.731 | 0.000 | 0.031 | 0.000 | 0.000 | -12.091 | 0.000 | -2.262 | -7.695 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.000 | -32.268 | 0.000 | 0.000 | 17.138 | 8.462 | 11.795 | 0.000 | 0.000 | 0.012 | 0.000 | 0.000 | 0.000 | 0.000 | -0.925 | -4.214 |
MECH_FLR_1 | 0.000 | 0.000 | 0.372 | -20.188 | 0.000 | 0.000 | 3.737 | 8.366 | 12.471 | 0.000 | 0.000 | 0.029 | 0.000 | 0.000 | 0.000 | 0.000 | -2.118 | -2.669 |
STORAGE_FLR_1 | 0.000 | 0.000 | 0.975 | -10.360 | 0.000 | 0.000 | 2.909 | 3.079 | 3.598 | 0.000 | 0.000 | 0.018 | 0.986 | 0.000 | 0.000 | 0.000 | -1.205 | -0.000 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.000 | -590.996 | 0.000 | 0.000 | 11.279 | 3.975 | 658.131 | 0.000 | 0.000 | 0.048 | 0.000 | 0.000 | 0.000 | 0.000 | -3.105 | -79.332 |
CAFE_FLR_1 | 0.000 | 0.000 | 0.013 | -215.026 | 0.000 | 0.000 | 194.909 | 14.029 | 14.341 | 57.480 | 0.000 | 0.064 | 0.000 | 0.000 | -35.904 | 0.000 | -5.280 | -24.625 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.000 | -741.447 | 0.000 | 0.000 | 564.035 | 109.893 | 148.998 | 75.917 | 0.000 | 0.196 | 0.000 | 0.000 | -49.000 | 0.000 | -15.495 | -93.097 |
ROOM_1_FLR_3 | 26.020 | -33.583 | 0.000 | -10.814 | 0.000 | 0.000 | 9.742 | 9.244 | 10.478 | 40.712 | 0.000 | 0.232 | 0.000 | 0.000 | -27.897 | 0.000 | -5.850 | -18.284 |
ROOM_2_FLR_3 | 30.184 | -22.318 | 0.000 | -11.356 | 0.000 | 0.000 | 9.602 | 9.243 | 10.477 | 29.551 | 0.000 | 0.121 | 0.000 | 0.000 | -29.207 | 0.000 | -6.256 | -20.041 |
ROOM_3_MULT19_FLR_3 | 3.625 | -206.808 | 0.004 | -12.615 | 0.000 | 0.000 | 0.000 | 110.385 | 194.997 | 230.414 | 0.000 | 0.067 | 0.003 | 0.000 | -175.826 | 0.000 | -32.677 | -111.565 |
ROOM_4_MULT19_FLR_3 | 93.078 | -180.931 | 0.000 | -151.357 | 0.000 | 0.000 | 183.195 | 110.415 | 195.050 | 78.166 | 0.000 | 1.049 | 0.000 | 0.000 | -164.782 | 0.000 | -45.937 | -117.947 |
ROOM_5_FLR_3 | 25.623 | -33.281 | 0.000 | -10.821 | 0.000 | 0.000 | 9.736 | 9.244 | 10.478 | 40.578 | 0.000 | 0.233 | 0.000 | 0.000 | -27.417 | 0.000 | -5.866 | -18.507 |
ROOM_6_FLR_3 | 29.666 | -22.729 | 0.000 | -11.276 | 0.000 | 0.000 | 9.632 | 9.243 | 10.477 | 29.226 | 0.000 | 0.122 | 0.000 | 0.000 | -28.419 | 0.000 | -6.339 | -19.604 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 1.504 | -162.421 | 0.000 | 0.000 | 119.603 | 91.336 | 0.000 | 36.023 | 0.000 | 0.093 | 0.000 | 0.000 | -36.164 | 0.000 | -6.444 | -43.529 |
ROOM_1_FLR_6 | 9.392 | -8.336 | 0.000 | -2.700 | 0.000 | 0.000 | 2.439 | 2.311 | 2.620 | 10.107 | 0.000 | 0.063 | 0.000 | 0.000 | -6.948 | 0.000 | -1.497 | -7.450 |
ROOM_2_FLR_6 | 10.674 | -5.670 | 0.000 | -2.846 | 0.000 | 0.000 | 2.400 | 2.311 | 2.619 | 7.327 | 0.000 | 0.031 | 0.000 | 0.000 | -7.291 | 0.000 | -1.588 | -7.965 |
ROOM_3_MULT9_FLR_6 | 28.725 | -49.003 | 0.000 | -17.463 | 0.000 | 0.000 | 21.861 | 13.076 | 23.098 | 53.388 | 0.000 | 0.439 | 0.000 | 0.000 | -32.462 | 0.000 | -7.866 | -33.792 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.000 | -418.953 | 0.000 | 0.000 | 317.682 | 30.690 | 175.857 | 7.886 | 0.000 | 0.033 | 0.000 | 0.000 | -22.239 | 0.000 | -3.701 | -87.255 |
DINING_FLR_6 | 0.000 | 0.000 | 0.000 | -459.756 | 0.000 | 0.000 | 316.063 | 30.690 | 175.857 | 7.684 | 0.000 | 0.032 | 0.000 | 0.000 | -22.867 | 0.000 | -3.733 | -43.969 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.000 | -621.026 | 0.000 | 0.000 | 28.417 | 12.972 | 550.372 | 19.293 | 0.000 | 0.029 | 28.311 | 0.000 | -15.019 | 0.000 | -3.349 | -0.000 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 2.281 | -78.025 | 0.000 | 0.000 | 31.628 | 24.166 | 0.000 | 17.407 | 0.000 | 0.033 | 21.662 | 0.000 | -16.287 | 0.000 | -2.865 | -0.000 |
Total Facility | 256.986 | -562.660 | 7.163 | -4004.175 | 0.000 | 0.000 | 2012.546 | 781.733 | 2365.005 | 761.891 | 0.000 | 2.974 | 50.962 | 0.000 | -709.822 | 0.000 | -164.359 | -798.241 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 13-OCT-21:00 | 0.00 | 0.00 | 0.00 | -21094.87 | 0.00 | 0.00 | 5924.49 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5679.83 |
RETAIL_1_FLR_1 | 21-SEP-13:00 | 0.00 | 0.00 | 0.00 | -4188.63 | 0.00 | 0.00 | 150.60 | 166.00 | 252.59 | 5933.83 | 0.00 | 5.16 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2319.55 |
RETAIL_2_FLR_1 | 10-AUG-21:00 | 0.00 | 0.00 | 0.00 | -1984.41 | 0.00 | 0.00 | 697.61 | 615.12 | 752.15 | 0.00 | 0.00 | 4.14 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -84.61 |
MECH_FLR_1 | 21-JUL-20:00 | 0.00 | 0.00 | 0.00 | -1639.99 | 0.00 | 0.00 | 129.08 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -3.32 | -9.40 |
STORAGE_FLR_1 | 21-JUL-10:33 | 0.00 | 0.00 | 0.00 | -731.08 | 0.00 | 0.00 | 29.05 | 69.95 | 89.22 | 0.00 | 0.00 | 14.45 | 528.42 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 21-JUL-20:00 | 0.00 | 0.00 | 0.00 | -38699.41 | 0.00 | 0.00 | 408.79 | 325.08 | 44299.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -4.54 | -6329.29 |
CAFE_FLR_1 | 11-OCT-12:30 | 0.00 | 0.00 | 0.00 | -14468.33 | 0.00 | 0.00 | 1979.02 | 103.98 | 355.63 | 19027.11 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -23.58 | -6973.83 |
LOBBY_FLR_1 | 20-JUL-21:10 | 0.00 | 0.00 | 0.00 | -39836.82 | 0.00 | 0.00 | 26439.91 | 6336.53 | 7389.94 | 107.03 | 0.00 | 48.67 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -485.26 |
ROOM_1_FLR_3 | 03-MAY-18:01 | 0.00 | -14834.50 | 0.00 | -523.72 | 0.00 | 0.00 | 335.50 | 633.26 | 484.65 | 4950.87 | 0.00 | 0.00 | 9058.65 | 0.00 | -0.00 | 0.00 | -104.71 | 0.00 |
ROOM_2_FLR_3 | 03-MAY-18:01 | 0.00 | -16133.61 | 0.00 | -666.22 | 0.00 | 0.00 | 287.39 | 633.19 | 484.60 | 5172.62 | 0.00 | 0.00 | 10350.75 | 0.00 | -0.00 | 0.00 | -128.71 | 0.00 |
ROOM_3_MULT19_FLR_3 | 11-OCT-12:30 | 0.00 | -53089.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2378.94 | 2352.88 | 79823.88 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -304.71 | -31161.91 |
ROOM_4_MULT19_FLR_3 | 03-JUN-20:41 | 0.00 | -86024.12 | 0.00 | -8199.95 | 0.00 | 0.00 | 6057.04 | 8498.53 | 13532.74 | 0.00 | 0.00 | 0.00 | 72500.39 | 0.00 | -5764.92 | 0.00 | -599.71 | 0.00 |
ROOM_5_FLR_3 | 27-MAY-18:01 | 0.00 | -13243.12 | 0.00 | -623.59 | 0.00 | 0.00 | 283.21 | 711.53 | 484.65 | 233.98 | 0.00 | 0.00 | 12562.14 | 0.00 | -0.00 | 0.00 | -408.81 | 0.00 |
ROOM_6_FLR_3 | 05-AUG-08:32 | 0.00 | -14196.50 | 0.00 | -1021.80 | 0.00 | 0.00 | 90.14 | 398.41 | 653.15 | 9559.69 | 0.00 | 0.00 | 4556.80 | 0.00 | -0.00 | 0.00 | -39.89 | 0.00 |
CORRIDOR_FLR_3 | 21-JUL-10:33 | 0.00 | 0.00 | 0.00 | -10353.34 | 0.00 | 0.00 | 1212.46 | 2074.80 | 0.00 | 6078.52 | 0.00 | 79.99 | 907.57 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 03-MAY-18:01 | 0.00 | -3864.46 | 0.00 | -130.76 | 0.00 | 0.00 | 83.87 | 158.32 | 121.16 | 1222.93 | 0.00 | 0.00 | 2435.28 | 0.00 | -0.00 | 0.00 | -26.34 | 0.00 |
ROOM_2_FLR_6 | 03-MAY-18:01 | 0.00 | -4248.58 | 0.00 | -170.78 | 0.00 | 0.00 | 70.21 | 158.30 | 121.15 | 1274.05 | 0.00 | 0.00 | 2828.74 | 0.00 | -0.00 | 0.00 | -33.08 | 0.00 |
ROOM_3_MULT9_FLR_6 | 03-MAY-18:01 | 0.00 | -18264.78 | 0.00 | -839.76 | 0.00 | 0.00 | 754.87 | 895.70 | 1068.37 | 0.00 | 0.00 | 0.00 | 16941.22 | 0.00 | -434.38 | 0.00 | -121.25 | 0.00 |
BANQUET_FLR_6 | 20-JUL-21:20 | 0.00 | 0.00 | 0.00 | -22927.47 | 0.00 | 0.00 | 15637.83 | 1992.02 | 6747.90 | 54.70 | 0.00 | 9.47 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1514.46 |
DINING_FLR_6 | 20-JUL-21:20 | 0.00 | 0.00 | 0.00 | -24132.90 | 0.00 | 0.00 | 15628.00 | 1992.02 | 6747.90 | 42.20 | 0.00 | 9.45 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -286.66 |
KITCHEN_FLR_6 | 16-JUL-10:40 | 0.00 | 0.00 | 0.00 | -31360.64 | 0.00 | 0.00 | 464.23 | 353.60 | 24259.91 | 3878.43 | 0.00 | 27.61 | 2376.87 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 21-JUL-13:30 | 0.00 | 0.00 | 0.00 | -6207.47 | 0.00 | 0.00 | 308.45 | 548.96 | 0.00 | 3191.54 | 0.00 | 44.10 | 2114.42 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 20-JUL-18:02 | 0.00 | -165686.82 | 0.00 | -197496.63 | 0.00 | 0.00 | 75051.52 | 53932.35 | 120482.43 | 29002.39 | 0.00 | 1598.37 | 83116.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 07-FEB-07:20 | 0.00 | 0.00 | 1419.51 | 0.00 | 0.00 | 0.00 | 360.60 | 332.00 | 433.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1582.37 | 0.00 | -223.84 | -738.90 |
RETAIL_2_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 07-FEB-11:35 | 0.00 | 0.00 | 549.58 | 0.00 | 0.00 | 0.00 | 43.84 | 190.05 | 309.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -179.21 | -913.53 |
STORAGE_FLR_1 | 07-FEB-11:03 | 0.00 | 0.00 | 539.21 | 0.00 | 0.00 | 0.00 | 33.72 | 69.95 | 89.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -106.26 | -625.84 |
LAUNDRY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 06-FEB-09:04 | 0.00 | 0.00 | 1304.72 | 0.00 | 0.00 | 0.00 | 2352.08 | 166.37 | 508.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3195.41 | 0.00 | -474.83 | -660.97 |
LOBBY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 06-FEB-09:13 | 6714.85 | 365.65 | 0.00 | -365.65 | 0.00 | 0.00 | 98.74 | 313.07 | 453.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2747.15 | 0.00 | -492.01 | -4340.54 |
ROOM_2_FLR_3 | 06-FEB-09:13 | 6676.87 | 362.14 | 0.00 | -362.14 | 0.00 | 0.00 | 98.82 | 313.04 | 452.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2779.36 | 0.00 | -491.32 | -4271.04 |
ROOM_3_MULT19_FLR_3 | 07-FEB-05:00 | 18919.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 934.58 | 3333.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -17192.11 | 0.00 | -2310.18 | -3684.89 |
ROOM_4_MULT19_FLR_3 | 11-DEC-16:01 | 36830.47 | 3597.91 | 0.00 | -3597.91 | 0.00 | 0.00 | 5585.68 | 2379.59 | 3726.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -13294.15 | 0.00 | -2061.36 | -33166.63 |
ROOM_5_FLR_3 | 03-MAY-18:03 | 6616.24 | 413.11 | 0.00 | -413.11 | 0.00 | 0.00 | 341.02 | 633.26 | 484.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -345.60 | 0.00 | -86.07 | -7643.51 |
ROOM_6_FLR_3 | 11-DEC-16:01 | 6559.26 | 272.74 | 0.00 | -272.74 | 0.00 | 0.00 | 293.99 | 199.20 | 200.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2448.17 | 0.00 | -390.05 | -4414.39 |
CORRIDOR_FLR_3 | 06-FEB-09:04 | 0.00 | 0.00 | 3724.42 | 0.00 | 0.00 | 0.00 | 1385.71 | 3319.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3546.47 | 0.00 | -603.74 | -4279.61 |
ROOM_1_FLR_6 | 06-FEB-09:13 | 2006.31 | 89.28 | 0.00 | -89.28 | 0.00 | 0.00 | 24.79 | 78.27 | 113.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -692.42 | 0.00 | -122.83 | -1407.37 |
ROOM_2_FLR_6 | 06-FEB-09:13 | 1991.00 | 88.20 | 0.00 | -88.20 | 0.00 | 0.00 | 24.89 | 78.26 | 113.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -698.14 | 0.00 | -122.62 | -1386.64 |
ROOM_3_MULT9_FLR_6 | 06-FEB-09:13 | 9380.17 | 593.37 | 0.00 | -593.37 | 0.00 | 0.00 | 221.99 | 442.82 | 998.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3112.70 | 0.00 | -568.29 | -7362.68 |
BANQUET_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 07-FEB-07:15 | 0.00 | 0.00 | 2879.28 | 0.00 | 0.00 | 0.00 | 733.32 | 1097.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2122.21 | 0.00 | -280.26 | -2308.07 |
Total Facility | 06-FEB-09:13 | 10391.75 | 79027.83 | 9648.65 | -79027.83 | 0.00 | 0.00 | 23988.09 | 26564.80 | 88178.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -59974.67 | 0.00 | -12187.07 | -86610.48 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:40
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV WITH REHEAT | 22.3654 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 22.2397 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV WITH REHEAT | 11.6524 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 11.6524 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.6520 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.0400 | 0.000610 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.000000 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.000000 | 142.3000 | 0.003581 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.000000 | 422.4350 | 0.001448 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 83.8280 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003556 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.1800 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 | |
VAV WITH REHEAT | 0.00 | 0.001045 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.4880 | 2.4880 | 1.2962 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3779 | 0.3779 | 0.1969 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2301 | 0.2301 | 0.1199 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1810 | 0.1810 | 0.0943 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1078 | 0.1078 | 0.0562 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.3268 | 3.3268 | 1.7333 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5811 | 1.5811 | 0.8238 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.9598 | 4.9598 | 2.5840 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5622 | 1.5622 | 0.8139 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1809 | 2.1809 | 1.1363 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2861 | 2.2861 | 1.1911 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3075 | 2.3075 | 1.2022 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7763 | 0.7763 | 0.4044 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
VAV WITH REHEAT | 22.3654 | 22.2397 | 22.3654 | 11.6524 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2962 | 1.2962 | 1.2962 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1969 | 0.1969 | 0.1969 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1199 | 0.1199 | 0.1199 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0943 | 0.0943 | 0.0943 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0562 | 0.0562 | 0.0562 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7333 | 1.7333 | 1.7333 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8238 | 0.8238 | 0.8238 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.5840 | 2.5840 | 2.5840 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8139 | 0.8139 | 0.8139 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1363 | 1.1363 | 1.1363 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1911 | 1.1911 | 1.1911 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2022 | 1.2022 | 1.2022 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4044 | 0.4044 | 0.4044 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
VAV WITH REHEAT | 11.6524 | 11.6524 | 11.6524 | 11.6524 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:40
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 168.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 168.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 17.67 |
Number of hours cooling loads not met | 37.17 |
Number of hours not met | 54.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 1422.56 | 285359.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 546.87 | 158511.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 781.73 | 64632.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 193.78 | 12338.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 872.72 | 59188.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 14.43 | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 8.99 | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.20 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 21.77 | 1291.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 789.09 | 48128.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 2.91 | 188.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 511.58 | 34071.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 71.38 | 4349.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 170.38 | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 94.78 | 4751.13 | 2802.62 | 265171.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.09 | 2093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 20.42 | 1893.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 34.23 | 1203.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1719.92 | 4904.20 |
Natural Gas | 1788.84 | 6014.02 |
Additional | 0.00 | 0.00 |
Total | 3508.76 | 10918.22 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 68.90 |
Space Heating | 0.00 |
Space Cooling | 48.20 |
Fans (All) | 45.09 |
Service Water Heating | 8.35 |
Receptacle Equipment | 146.16 |
Miscellaneous (All) | 432.27 |
Subtotal | 432.27 |
Natural Gas [MJ/m2] | |
Space Heating | 125.39 |
Service Water Heating | 247.03 |
Miscellaneous (All) | 530.09 |
Subtotal | 530.09 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 7.16 |
Space Heating | 13.03 |
Space Cooling | 5.01 |
Fans (All) | 4.69 |
Service Water Heating | 26.54 |
Receptacle Equipment | 31.57 |
Miscellaneous | 12.01 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 486. | 5110. |
ELEVATOR_STANDBY_SCH | 7671. | 8760. |
LTG_SCH_KITCHEN | 3061. | 8760. |
LTG_SCH_DINING | 3061. | 8760. |
LTG_SCH_BASEMENT | 2572. | 8760. |
LTG_SCH_LOBBY | 2295. | 8760. |
LTG_SCH_STORAGE | 1580. | 8760. |
LTG_SCH_MECHANIC | 3061. | 8760. |
LTG_SCH_LAUNDRY | 3061. | 8760. |
LTG_SCH_GUESTROOM | 1980. | 8760. |
LTG_SCH_CORRIDOR | 2295. | 8760. |
LTG_SCH_RETAIL | 2678. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 1591. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3737. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 5740. | 6205. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 8760. | 8760. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 26.67 | 365 | 26.67 | 365 |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
HTGSETP_SCH | BASEMENT DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:40
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8702.67 | 57.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8510.17 | 249.83 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8735.67 | 24.33 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8663.83 | 96.17 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8510.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 249.83 | 0.00 | 0.00 | 0.00 |
Average | 8740.56 | 19.44 | 0.00 | 0.00 | 0.00 |
Sum | 192292.33 | 427.67 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4137.17 | 16.83 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4116.83 | 37.17 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108269.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 37.17 | 0.00 | 0.00 | 0.00 |
Average | 288884.59 | 2.45 | 0.00 | 0.00 | 0.00 |
Sum | 6355461.00 | 54.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8671.17 | 88.83 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8231.50 | 528.50 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8248.83 | 511.17 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8557.50 | 202.50 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8183.83 | 576.17 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8673.67 | 86.33 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8586.33 | 173.67 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8758.50 | 1.50 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8493.50 | 266.50 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8756.33 | 3.67 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8183.17 | 576.83 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8247.17 | 512.83 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8706.67 | 53.33 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8183.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 576.83 | 0.00 | 0.00 | 0.00 |
Average | 8597.19 | 162.81 | 0.00 | 0.00 | 0.00 |
Sum | 189138.17 | 3581.83 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 58196.83 | 959.17 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 646074.17 | 64342.83 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 1934800.00 | 180629.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4059.67 | 94.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4110.33 | 43.67 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4093.83 | 60.17 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4019.17 | 134.83 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1127929.33 | 117785.67 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1139361.17 | 106353.83 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 107840.33 | 428.67 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 1934800.00 | 180629.00 | 0.00 | 0.00 | 0.00 |
Average | 267485.58 | 21401.46 | 0.00 | 0.00 | 0.00 |
Sum | 5884682.83 | 470832.17 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:40
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:40
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 1592.73 | 0.00 | 0.00 |
Sum | 0.00 | 35040.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 710417.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 2115429.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 2115429.00 | 0.00 | 0.00 |
Average | 0.00 | 241694.36 | 0.00 | 0.00 |
Sum | 0.00 | 5317276.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A
For: Environment
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Environment
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO
For: Environment
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.315784E+11 | 13869.10 | 11-JAN-21:00 | 2.20 | -0.8 | 0.770363E+10 | 4814.23 | 13-JAN-22:10 | 2.80 | -2.1 |
February | 0.275894E+11 | 13581.82 | 01-FEB-21:00 | 0.60 | 0.37 | 0.679601E+10 | 4743.81 | 01-FEB-22:10 | 0.60 | 0.17 |
March | 0.287028E+11 | 13327.84 | 15-MAR-18:10 | 23.43 | 15.50 | 0.715159E+10 | 4598.06 | 01-MAR-22:10 | 23.43 | 15.50 |
April | 0.274963E+11 | 13444.45 | 22-APR-10:33 | 11.33 | 5.08 | 0.677840E+10 | 4359.52 | 28-APR-21:10 | 8.30 | 7.68 |
May | 0.286781E+11 | 13675.77 | 27-MAY-10:33 | 19.43 | 12.21 | 0.695585E+10 | 4331.93 | 12-MAY-21:10 | 19.43 | 12.21 |
June | 0.304280E+11 | 14785.65 | 25-JUN-10:33 | 23.53 | 14.84 | 0.708464E+10 | 4562.79 | 23-JUN-22:10 | 23.53 | 14.84 |
July | 0.334835E+11 | 15510.89 | 16-JUL-10:33 | 28.50 | 22.06 | 0.757360E+10 | 4750.41 | 28-JUL-22:10 | 21.10 | 19.56 |
August | 0.356802E+11 | 17063.17 | 31-AUG-21:00 | 13.90 | 11.74 | 0.797265E+10 | 4837.14 | 08-AUG-21:00 | 13.90 | 11.74 |
September | 0.362393E+11 | 19777.69 | 22-SEP-21:00 | 16.10 | 11.97 | 0.786983E+10 | 4837.19 | 07-SEP-21:30 | 16.10 | 11.97 |
October | 0.382841E+11 | 21095.96 | 13-OCT-21:00 | 8.90 | 6.98 | 0.818399E+10 | 4837.35 | 25-OCT-21:10 | 13.12 | 11.98 |
November | 0.359510E+11 | 20786.55 | 01-NOV-21:00 | 4.40 | 3.43 | 0.789707E+10 | 4837.13 | 13-NOV-00:49 | 5.87 | 3.63 |
December | 0.344458E+11 | 18946.67 | 01-DEC-22:00 | 6.10 | 3.26 | 0.803521E+10 | 4837.11 | 01-DEC-01:10 | 6.10 | 3.26 |
Annual Sum or Average | 0.388557E+12 | 0.900025E+11 | ||||||||
Minimum of Months | 0.274963E+11 | 13327.84 | 0.60 | -0.8 | 0.677840E+10 | 4331.93 | 0.60 | -2.1 | ||
Maximum of Months | 0.382841E+11 | 21095.96 | 28.50 | 22.06 | 0.818399E+10 | 4837.35 | 23.53 | 19.56 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.547954E+09 | 1953.67 | 15-JAN-11:50 | 4.13 | 2.34 | 0.621331E+09 | 364.16 | 04-JAN-05:10 | 4.13 | 2.34 |
February | 0.561654E+09 | 1983.27 | 28-FEB-11:50 | -1.3 | -3.8 | 0.562053E+09 | 364.17 | 06-FEB-05:10 | -1.3 | -3.8 |
March | 0.212359E+10 | 2935.71 | 15-MAR-13:30 | 25.55 | 15.84 | 0.635183E+09 | 438.12 | 15-MAR-21:30 | 17.80 | 13.45 |
April | 0.267470E+10 | 2404.44 | 22-APR-13:10 | 14.60 | 6.58 | 0.617038E+09 | 408.77 | 07-APR-21:30 | 14.60 | 6.58 |
May | 0.374171E+10 | 2190.58 | 27-MAY-10:33 | 19.43 | 12.21 | 0.654853E+09 | 434.04 | 23-MAY-21:40 | 19.43 | 12.21 |
June | 0.439354E+10 | 2519.10 | 27-JUN-13:10 | 30.03 | 23.62 | 0.681760E+09 | 468.00 | 27-JUN-21:30 | 21.95 | 20.56 |
July | 0.501815E+10 | 3088.80 | 21-JUL-13:30 | 31.15 | 21.91 | 0.739420E+09 | 484.57 | 19-JUL-21:30 | 31.15 | 21.91 |
August | 0.503186E+10 | 3426.55 | 18-AUG-13:30 | 29.70 | 20.75 | 0.737100E+09 | 488.35 | 10-AUG-21:30 | 29.70 | 20.75 |
September | 0.439693E+10 | 4188.87 | 21-SEP-13:00 | 25.00 | 16.50 | 0.671809E+09 | 474.73 | 21-SEP-21:30 | 17.75 | 15.84 |
October | 0.315368E+10 | 4097.46 | 11-OCT-12:30 | 21.95 | 13.79 | 0.646665E+09 | 454.38 | 11-OCT-21:40 | 15.60 | 10.74 |
November | 0.177614E+10 | 2445.04 | 03-NOV-12:30 | 8.35 | 4.56 | 0.605629E+09 | 385.11 | 01-NOV-00:10 | 8.35 | 4.56 |
December | 0.480715E+09 | 2116.31 | 17-DEC-11:50 | 1.60 | -0.2 | 0.621587E+09 | 364.16 | 28-DEC-05:10 | -11.8 | -12.1 |
Annual Sum or Average | 0.339006E+11 | 0.779443E+10 | ||||||||
Minimum of Months | 0.480715E+09 | 1953.67 | -1.3 | -3.8 | 0.562053E+09 | 364.16 | -11.8 | -12.1 | ||
Maximum of Months | 0.503186E+10 | 4188.87 | 31.15 | 23.62 | 0.739420E+09 | 488.35 | 31.15 | 21.91 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.204514E+10 | 1080.72 | 17-JAN-21:00 | 4.40 | 3.64 | 0.756419E+09 | 499.88 | 17-JAN-23:10 | 4.32 | 3.30 |
February | 0.184256E+10 | 1091.94 | 22-FEB-21:00 | 9.40 | 5.14 | 0.683301E+09 | 503.55 | 22-FEB-23:10 | 6.83 | 5.85 |
March | 0.250192E+10 | 1366.62 | 15-MAR-18:10 | 23.43 | 15.50 | 0.815769E+09 | 569.55 | 15-MAR-22:10 | 16.78 | 13.11 |
April | 0.259483E+10 | 1296.65 | 21-APR-20:00 | 7.80 | 3.65 | 0.815924E+09 | 559.79 | 21-APR-21:40 | 6.30 | 3.16 |
May | 0.292081E+10 | 1413.01 | 23-MAY-21:00 | 20.60 | 13.34 | 0.884082E+09 | 569.56 | 26-MAY-21:10 | 14.72 | 11.23 |
June | 0.314105E+10 | 1826.54 | 27-JUN-21:00 | 22.20 | 20.99 | 0.898652E+09 | 569.55 | 30-JUN-22:10 | 17.73 | 11.83 |
July | 0.345545E+10 | 1954.20 | 19-JUL-21:00 | 26.70 | 22.02 | 0.943639E+09 | 569.55 | 07-JUL-22:10 | 26.70 | 22.02 |
August | 0.342641E+10 | 1984.33 | 10-AUG-21:00 | 26.10 | 18.56 | 0.946314E+09 | 569.56 | 08-AUG-21:49 | 26.10 | 18.56 |
September | 0.304913E+10 | 1836.10 | 21-SEP-21:00 | 18.30 | 16.18 | 0.888259E+09 | 569.56 | 07-SEP-22:10 | 18.30 | 16.18 |
October | 0.276495E+10 | 1532.95 | 11-OCT-21:00 | 15.60 | 10.58 | 0.860552E+09 | 569.55 | 11-OCT-21:00 | 15.60 | 10.82 |
November | 0.244370E+10 | 1245.92 | 01-NOV-20:00 | 7.20 | 5.15 | 0.791350E+09 | 546.59 | 01-NOV-22:10 | 4.32 | 3.43 |
December | 0.208211E+10 | 1104.50 | 01-DEC-21:00 | 6.10 | 3.90 | 0.761285E+09 | 505.79 | 01-DEC-23:10 | 5.50 | 3.14 |
Annual Sum or Average | 0.322681E+11 | 0.100455E+11 | ||||||||
Minimum of Months | 0.184256E+10 | 1080.72 | 4.40 | 3.64 | 0.683301E+09 | 499.88 | 4.32 | 3.14 | ||
Maximum of Months | 0.345545E+10 | 1984.33 | 26.70 | 22.02 | 0.946314E+09 | 569.56 | 26.70 | 22.02 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.515931E+09 | 739.44 | 17-JAN-21:00 | 4.40 | 3.64 | 0.151917E+09 | 93.73 | 17-JAN-22:10 | 4.40 | 3.43 |
February | 0.419762E+09 | 727.39 | 22-FEB-21:00 | 9.40 | 5.14 | 0.137318E+09 | 92.67 | 22-FEB-22:10 | 7.70 | 4.64 |
March | 0.127174E+10 | 979.66 | 15-MAR-18:10 | 23.43 | 15.50 | 0.157255E+09 | 109.41 | 15-MAR-21:19 | 18.17 | 13.56 |
April | 0.174060E+10 | 954.71 | 09-APR-10:33 | 14.80 | 10.96 | 0.156364E+09 | 103.23 | 21-APR-21:19 | 6.50 | 3.28 |
May | 0.212640E+10 | 1053.51 | 27-MAY-10:33 | 19.43 | 12.21 | 0.174938E+09 | 111.53 | 31-MAY-22:10 | 17.55 | 13.48 |
June | 0.235095E+10 | 1199.23 | 27-JUN-21:00 | 22.20 | 20.99 | 0.183960E+09 | 120.45 | 30-JUN-21:00 | 17.80 | 11.66 |
July | 0.263315E+10 | 1639.97 | 21-JUL-20:00 | 23.30 | 21.68 | 0.197547E+09 | 120.45 | 24-JUL-21:19 | 20.93 | 17.61 |
August | 0.258233E+10 | 1395.89 | 10-AUG-21:00 | 26.10 | 18.56 | 0.197427E+09 | 120.46 | 08-AUG-21:00 | 26.10 | 18.56 |
September | 0.226997E+10 | 1160.89 | 16-SEP-10:33 | 25.37 | 19.22 | 0.180718E+09 | 119.54 | 15-SEP-21:19 | 25.37 | 19.22 |
October | 0.198020E+10 | 976.60 | 11-OCT-10:33 | 18.50 | 13.21 | 0.168941E+09 | 111.00 | 12-OCT-21:10 | 15.40 | 14.18 |
November | 0.160945E+10 | 904.94 | 05-NOV-10:33 | 18.30 | 12.89 | 0.153278E+09 | 102.73 | 01-NOV-21:10 | 18.30 | 12.89 |
December | 0.687683E+09 | 765.93 | 01-DEC-21:00 | 6.10 | 3.90 | 0.152173E+09 | 95.58 | 01-DEC-22:10 | 6.02 | 3.25 |
Annual Sum or Average | 0.201882E+11 | 0.201184E+10 | ||||||||
Minimum of Months | 0.419762E+09 | 727.39 | 4.40 | 3.64 | 0.137318E+09 | 92.67 | 4.40 | 3.25 | ||
Maximum of Months | 0.263315E+10 | 1639.97 | 26.10 | 21.68 | 0.197547E+09 | 120.46 | 26.10 | 19.22 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 70256942.73 | 388.06 | 17-JAN-22:00 | 4.40 | 3.43 | 0.116690E+09 | 68.62 | 17-JAN-23:10 | 4.32 | 3.30 |
February | 51989249.01 | 362.72 | 22-FEB-22:00 | 7.80 | 4.32 | 0.105501E+09 | 68.57 | 08-FEB-04:00 | 7.80 | 4.32 |
March | 0.506242E+09 | 565.07 | 15-MAR-18:10 | 23.43 | 15.50 | 0.119212E+09 | 81.05 | 15-MAR-22:10 | 16.78 | 13.11 |
April | 0.899354E+09 | 555.09 | 09-APR-10:33 | 14.80 | 10.96 | 0.116687E+09 | 76.02 | 09-APR-23:10 | 8.30 | 7.74 |
May | 0.121265E+10 | 613.76 | 27-MAY-10:33 | 19.43 | 12.21 | 0.130191E+09 | 82.54 | 23-MAY-22:10 | 19.43 | 12.21 |
June | 0.135232E+10 | 690.38 | 29-JUN-10:33 | 24.63 | 19.77 | 0.137558E+09 | 90.16 | 27-JUN-22:10 | 24.63 | 19.77 |
July | 0.150588E+10 | 731.11 | 21-JUL-10:33 | 29.03 | 21.82 | 0.148451E+09 | 92.66 | 21-JUL-21:19 | 22.60 | 21.00 |
August | 0.147851E+10 | 705.66 | 10-AUG-10:33 | 28.53 | 20.68 | 0.147878E+09 | 92.04 | 10-AUG-22:10 | 25.03 | 19.46 |
September | 0.129870E+10 | 679.56 | 16-SEP-10:33 | 25.37 | 19.22 | 0.134592E+09 | 88.30 | 15-SEP-22:10 | 25.37 | 19.22 |
October | 0.109882E+10 | 568.95 | 22-OCT-10:33 | 20.60 | 13.20 | 0.125074E+09 | 81.70 | 12-OCT-22:10 | 20.60 | 13.20 |
November | 0.745911E+09 | 523.93 | 05-NOV-10:33 | 18.30 | 12.89 | 0.114737E+09 | 74.53 | 05-NOV-23:10 | 9.50 | 7.69 |
December | 0.139019E+09 | 421.42 | 01-DEC-21:00 | 6.10 | 3.90 | 0.116699E+09 | 69.75 | 01-DEC-23:10 | 5.50 | 3.14 |
Annual Sum or Average | 0.103597E+11 | 0.151327E+10 | ||||||||
Minimum of Months | 51989249.01 | 362.72 | 4.40 | 3.43 | 0.105501E+09 | 68.57 | 4.32 | 3.14 | ||
Maximum of Months | 0.150588E+10 | 731.11 | 29.03 | 21.82 | 0.148451E+09 | 92.66 | 25.37 | 21.00 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.473167E+11 | 36435.72 | 17-JAN-21:00 | 4.40 | 3.64 | 0.580965E+09 | 381.60 | 20-JAN-22:10 | -2.9 | -3.9 |
February | 0.426973E+11 | 36470.25 | 22-FEB-21:00 | 9.40 | 5.14 | 0.524616E+09 | 381.63 | 22-FEB-23:10 | 6.83 | 5.85 |
March | 0.490563E+11 | 38005.68 | 15-MAR-20:00 | 21.10 | 14.48 | 0.586787E+09 | 381.65 | 15-MAR-21:10 | 18.53 | 13.66 |
April | 0.483451E+11 | 37594.26 | 07-APR-20:00 | 17.20 | 9.45 | 0.569195E+09 | 381.70 | 07-APR-21:10 | 15.92 | 10.46 |
May | 0.512748E+11 | 38022.85 | 23-MAY-20:00 | 21.10 | 12.98 | 0.591191E+09 | 381.72 | 09-MAY-21:40 | 21.10 | 12.98 |
June | 0.508273E+11 | 38464.13 | 27-JUN-20:00 | 23.90 | 21.99 | 0.575014E+09 | 381.72 | 19-JUN-21:10 | 23.90 | 21.99 |
July | 0.529963E+11 | 38699.06 | 21-JUL-20:00 | 23.30 | 21.68 | 0.594237E+09 | 381.75 | 06-JUL-21:10 | 23.30 | 21.68 |
August | 0.529916E+11 | 38625.31 | 10-AUG-20:00 | 25.60 | 18.99 | 0.595475E+09 | 381.71 | 22-AUG-21:10 | 18.03 | 13.14 |
September | 0.501715E+11 | 38250.78 | 15-SEP-20:00 | 22.20 | 20.62 | 0.573563E+09 | 381.79 | 07-SEP-21:10 | 22.20 | 20.62 |
October | 0.502731E+11 | 37889.13 | 11-OCT-20:00 | 16.10 | 11.00 | 0.589895E+09 | 381.72 | 03-OCT-21:10 | 16.10 | 11.00 |
November | 0.476666E+11 | 37188.50 | 16-NOV-21:00 | 8.30 | 6.92 | 0.568301E+09 | 381.61 | 13-NOV-22:10 | 8.30 | 6.92 |
December | 0.473767E+11 | 36635.56 | 01-DEC-21:00 | 6.10 | 3.90 | 0.581216E+09 | 381.61 | 12-DEC-22:10 | 0.00 | -0.5 |
Annual Sum or Average | 0.590993E+12 | 0.693045E+10 | ||||||||
Minimum of Months | 0.426973E+11 | 36435.72 | 4.40 | 3.64 | 0.524616E+09 | 381.60 | -2.9 | -3.9 | ||
Maximum of Months | 0.529963E+11 | 38699.06 | 25.60 | 21.99 | 0.595475E+09 | 381.79 | 23.90 | 21.99 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.126977E+11 | 8907.55 | 15-JAN-13:00 | 4.40 | 1.94 | 0.855157E+10 | 5703.39 | 06-JAN-22:40 | 4.40 | 1.94 |
February | 0.117004E+11 | 8561.04 | 28-FEB-13:30 | 0.00 | -2.9 | 0.773473E+10 | 5931.95 | 22-FEB-22:40 | 0.00 | -2.9 |
March | 0.170611E+11 | 11019.46 | 15-MAR-13:30 | 25.55 | 15.84 | 0.931877E+10 | 6462.53 | 14-MAR-22:10 | 25.55 | 15.84 |
April | 0.175736E+11 | 10439.72 | 22-APR-13:00 | 14.40 | 6.45 | 0.923651E+10 | 6462.39 | 07-APR-22:10 | 14.40 | 6.45 |
May | 0.198717E+11 | 9621.28 | 27-MAY-10:33 | 19.43 | 12.21 | 0.998137E+10 | 6462.80 | 26-MAY-21:49 | 19.43 | 12.21 |
June | 0.210048E+11 | 10534.10 | 27-JUN-21:10 | 22.12 | 20.85 | 0.101015E+11 | 6462.80 | 30-JUN-22:10 | 17.73 | 11.83 |
July | 0.231404E+11 | 11373.94 | 20-JUL-21:10 | 25.50 | 24.00 | 0.106245E+11 | 6462.79 | 07-JUL-22:10 | 25.50 | 24.00 |
August | 0.232161E+11 | 12142.27 | 17-AUG-15:03 | 28.90 | 16.32 | 0.106830E+11 | 6462.79 | 22-AUG-22:10 | 16.42 | 12.93 |
September | 0.213537E+11 | 14362.65 | 21-SEP-15:03 | 26.10 | 16.73 | 0.100706E+11 | 6462.73 | 07-SEP-22:10 | 26.10 | 16.73 |
October | 0.191508E+11 | 14466.48 | 11-OCT-12:30 | 21.95 | 13.79 | 0.974637E+10 | 6462.53 | 11-OCT-21:00 | 15.60 | 10.82 |
November | 0.157514E+11 | 9927.13 | 03-NOV-12:30 | 8.35 | 4.56 | 0.892930E+10 | 6319.79 | 01-NOV-00:10 | 8.35 | 4.56 |
December | 0.125016E+11 | 9406.99 | 17-DEC-11:33 | 1.50 | -0.3 | 0.858170E+10 | 5688.34 | 04-DEC-22:40 | 1.50 | -0.3 |
Annual Sum or Average | 0.215024E+12 | 0.113560E+12 | ||||||||
Minimum of Months | 0.117004E+11 | 8561.04 | 0.00 | -2.9 | 0.773473E+10 | 5688.34 | 0.00 | -2.9 | ||
Maximum of Months | 0.232161E+11 | 14466.48 | 28.90 | 24.00 | 0.106830E+11 | 6462.80 | 26.10 | 24.00 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.506005E+11 | 24734.29 | 15-JAN-11:33 | 3.87 | 2.17 | 0.271021E+11 | 17993.04 | 17-JAN-23:10 | 4.32 | 3.30 |
February | 0.457165E+11 | 24972.56 | 22-FEB-21:00 | 9.40 | 5.14 | 0.244682E+11 | 18193.37 | 22-FEB-23:10 | 6.83 | 5.85 |
March | 0.581424E+11 | 32972.00 | 15-MAR-21:10 | 18.53 | 13.66 | 0.290480E+11 | 19185.91 | 14-MAR-22:10 | 18.53 | 13.66 |
April | 0.592322E+11 | 29199.69 | 23-APR-10:33 | 14.80 | 7.30 | 0.287941E+11 | 19185.76 | 07-APR-22:10 | 14.80 | 7.30 |
May | 0.658921E+11 | 32868.41 | 23-MAY-21:52 | 20.60 | 13.34 | 0.308750E+11 | 19186.33 | 26-MAY-21:49 | 13.58 | 11.12 |
June | 0.697150E+11 | 37470.31 | 27-JUN-21:10 | 22.12 | 20.85 | 0.307521E+11 | 19186.31 | 30-JUN-22:10 | 17.73 | 11.83 |
July | 0.762009E+11 | 39829.44 | 20-JUL-21:10 | 25.50 | 24.00 | 0.319742E+11 | 19186.28 | 07-JUL-22:10 | 25.50 | 24.00 |
August | 0.759504E+11 | 39758.96 | 10-AUG-21:10 | 26.02 | 18.64 | 0.321539E+11 | 19186.31 | 08-AUG-22:10 | 26.02 | 18.64 |
September | 0.689275E+11 | 38232.30 | 21-SEP-21:10 | 18.12 | 16.07 | 0.306895E+11 | 19186.27 | 07-SEP-22:10 | 18.12 | 16.07 |
October | 0.635098E+11 | 35018.66 | 11-OCT-21:10 | 15.60 | 10.62 | 0.304023E+11 | 19185.91 | 11-OCT-21:00 | 15.60 | 10.82 |
November | 0.565479E+11 | 28045.69 | 01-NOV-21:20 | 4.40 | 3.43 | 0.281998E+11 | 19183.07 | 01-NOV-21:49 | 4.40 | 3.43 |
December | 0.510065E+11 | 25716.47 | 17-DEC-11:33 | 1.50 | -0.3 | 0.272320E+11 | 18169.67 | 01-DEC-23:10 | 1.50 | -0.3 |
Annual Sum or Average | 0.741442E+12 | 0.351691E+12 | ||||||||
Minimum of Months | 0.457165E+11 | 24734.29 | 1.50 | -0.3 | 0.244682E+11 | 17993.04 | 1.50 | -0.3 | ||
Maximum of Months | 0.762009E+11 | 39829.44 | 26.02 | 24.00 | 0.321539E+11 | 19186.33 | 26.02 | 24.00 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 7051337.28 | 2766.40 | 15-JAN-16:01 | 4.82 | 1.15 | 93009424.81 | 56.69 | 27-JAN-04:19 | -4.6 | -5.9 |
February | 15365820.30 | 3710.27 | 28-FEB-16:01 | 0.40 | -2.4 | 84191809.35 | 56.69 | 21-FEB-04:19 | 0.40 | -2.4 |
March | 0.211879E+09 | 3738.08 | 08-MAR-16:01 | 7.12 | 1.52 | 95906881.08 | 56.69 | 14-MAR-21:30 | 16.65 | 12.98 |
April | 0.450154E+09 | 3748.32 | 19-APR-18:01 | 14.03 | 8.86 | 93962888.30 | 56.69 | 07-APR-21:10 | 14.03 | 8.86 |
May | 0.109616E+10 | 3839.61 | 03-MAY-18:01 | 14.22 | 6.76 | 98431934.72 | 56.69 | 31-MAY-21:40 | 17.67 | 13.17 |
June | 0.192123E+10 | 3786.09 | 15-JUN-18:01 | 17.20 | 9.88 | 95795227.36 | 56.70 | 21-JUN-21:49 | 17.57 | 16.66 |
July | 0.233255E+10 | 3414.74 | 21-JUL-08:61 | 26.78 | 22.99 | 99009588.96 | 56.70 | 20-JUL-22:40 | 26.78 | 22.99 |
August | 0.212876E+10 | 3381.85 | 18-AUG-08:61 | 22.57 | 16.57 | 99020492.97 | 56.70 | 10-AUG-23:49 | 22.57 | 16.57 |
September | 0.134686E+10 | 3391.25 | 08-SEP-18:01 | 21.10 | 16.42 | 95426529.17 | 56.70 | 21-SEP-21:00 | 17.20 | 15.48 |
October | 0.393807E+09 | 3279.15 | 04-OCT-15:01 | 15.92 | 12.43 | 96821292.26 | 56.69 | 12-OCT-22:10 | 14.40 | 13.67 |
November | 61025690.24 | 3052.10 | 14-NOV-16:01 | 9.82 | 7.93 | 92039406.09 | 56.69 | 27-NOV-04:19 | 17.40 | 11.98 |
December | 5501663.82 | 3073.56 | 04-DEC-16:02 | -0.9 | -3.5 | 92997423.53 | 56.69 | 29-DEC-04:19 | -8.0 | -8.6 |
Annual Sum or Average | 0.997034E+10 | 0.113661E+10 | ||||||||
Minimum of Months | 5501663.82 | 2766.40 | -0.9 | -3.5 | 84191809.35 | 56.69 | -8.0 | -8.6 | ||
Maximum of Months | 0.233255E+10 | 3839.61 | 26.78 | 22.99 | 99020492.97 | 56.70 | 26.78 | 22.99 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1322866.66 | 899.49 | 15-JAN-16:01 | 4.82 | 1.15 | 92557745.63 | 56.69 | 27-JAN-04:19 | -4.6 | -5.9 |
February | 4144432.69 | 2308.11 | 28-FEB-16:01 | 0.40 | -2.4 | 83716478.58 | 56.69 | 14-FEB-04:19 | 0.40 | -2.4 |
March | 0.111811E+09 | 3527.70 | 28-MAR-18:01 | 5.40 | -0.5 | 95109770.73 | 68.55 | 15-MAR-21:10 | 5.40 | -0.5 |
April | 0.291263E+09 | 4117.41 | 19-APR-18:11 | 13.67 | 8.82 | 93742969.06 | 65.72 | 19-APR-18:10 | 13.67 | 8.82 |
May | 0.776354E+09 | 4200.03 | 03-MAY-18:01 | 14.22 | 6.76 | 0.102708E+09 | 88.96 | 31-MAY-18:10 | 20.82 | 13.97 |
June | 0.147080E+10 | 3621.09 | 24-JUN-21:51 | 15.60 | 12.99 | 0.106737E+09 | 93.97 | 19-JUN-18:10 | 15.60 | 12.99 |
July | 0.190976E+10 | 3705.21 | 06-JUL-21:51 | 16.70 | 12.85 | 0.107756E+09 | 90.17 | 06-JUL-18:10 | 16.70 | 12.85 |
August | 0.163065E+10 | 3758.06 | 02-AUG-21:51 | 17.20 | 12.20 | 0.107339E+09 | 91.86 | 02-AUG-18:10 | 17.20 | 12.20 |
September | 0.818815E+09 | 3428.25 | 11-SEP-19:31 | 14.60 | 10.96 | 0.101601E+09 | 78.71 | 11-SEP-18:10 | 14.60 | 10.96 |
October | 0.180879E+09 | 3270.56 | 22-OCT-15:01 | 21.60 | 14.51 | 96796858.70 | 68.57 | 11-OCT-21:30 | 21.60 | 14.51 |
November | 25323969.38 | 2793.45 | 14-NOV-16:01 | 9.82 | 7.93 | 91141307.52 | 56.69 | 27-NOV-04:19 | 17.40 | 11.98 |
December | 2211513.35 | 585.43 | 01-DEC-19:05 | 6.60 | 4.58 | 92584154.26 | 56.69 | 12-DEC-04:19 | -10.7 | -11.0 |
Annual Sum or Average | 0.722334E+10 | 0.117179E+10 | ||||||||
Minimum of Months | 1322866.66 | 585.43 | 0.40 | -2.4 | 83716478.58 | 56.69 | -10.7 | -11.0 | ||
Maximum of Months | 0.190976E+10 | 4200.03 | 21.60 | 14.51 | 0.107756E+09 | 93.97 | 21.60 | 14.51 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3855455.79 | 95.70 | 15-JAN-15:20 | 5.40 | 1.48 | 0.00 | 0.00 | 01-JAN-00:10 | 5.40 | 1.48 |
February | 3404730.56 | 79.59 | 28-FEB-15:20 | 0.20 | -2.6 | 0.00 | 0.00 | 01-FEB-00:10 | 0.20 | -2.6 |
March | 56406993.65 | 489.92 | 15-MAR-13:30 | 25.55 | 15.84 | 0.00 | 0.00 | 01-MAR-00:10 | 25.55 | 15.84 |
April | 0.140439E+09 | 401.98 | 22-APR-13:00 | 14.40 | 6.45 | 0.00 | 0.00 | 01-APR-00:10 | 14.40 | 6.45 |
May | 0.291726E+09 | 364.12 | 14-MAY-13:40 | 24.63 | 17.99 | 0.00 | 0.00 | 01-MAY-00:10 | 24.63 | 17.99 |
June | 0.437753E+09 | 412.07 | 12-JUN-13:10 | 29.60 | 19.81 | 0.00 | 0.00 | 01-JUN-00:10 | 29.60 | 19.81 |
July | 0.583789E+09 | 469.31 | 21-JUL-13:30 | 31.15 | 21.91 | 0.00 | 0.00 | 01-JUL-00:10 | 31.15 | 21.91 |
August | 0.588459E+09 | 539.06 | 18-AUG-13:30 | 29.70 | 20.75 | 0.00 | 0.00 | 01-AUG-00:10 | 29.70 | 20.75 |
September | 0.483901E+09 | 680.50 | 21-SEP-13:00 | 25.00 | 16.50 | 0.00 | 0.00 | 01-SEP-00:10 | 25.00 | 16.50 |
October | 0.237488E+09 | 698.53 | 11-OCT-12:30 | 21.95 | 13.79 | 0.00 | 0.00 | 01-OCT-00:10 | 21.95 | 13.79 |
November | 55633783.00 | 403.52 | 03-NOV-12:30 | 8.35 | 4.56 | 0.00 | 0.00 | 01-NOV-00:10 | 8.35 | 4.56 |
December | 4324983.43 | 111.30 | 04-DEC-15:20 | -0.2 | -3.0 | 0.00 | 0.00 | 01-DEC-00:10 | -0.2 | -3.0 |
Annual Sum or Average | 0.288718E+10 | 0.00 | ||||||||
Minimum of Months | 3404730.56 | 79.59 | -0.2 | -3.0 | 0.00 | 0.00 | -0.2 | -3.0 | ||
Maximum of Months | 0.588459E+09 | 698.53 | 31.15 | 21.91 | 0.00 | 0.00 | 31.15 | 21.91 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 16606910.31 | 783.65 | 15-JAN-09:02 | 0.87 | 0.15 | 94236407.87 | 56.69 | 31-JAN-04:19 | -11.7 | -12.6 |
February | 14082174.30 | 805.62 | 19-FEB-09:02 | 2.07 | -1.4 | 85226948.54 | 56.69 | 22-FEB-23:10 | 6.83 | 5.85 |
March | 0.132943E+09 | 1070.20 | 15-MAR-15:01 | 25.50 | 16.19 | 96022219.25 | 71.25 | 15-MAR-21:00 | 16.70 | 13.08 |
April | 0.253940E+09 | 1129.78 | 22-APR-18:01 | 13.53 | 6.08 | 93833388.16 | 66.25 | 07-APR-21:49 | 13.53 | 6.08 |
May | 0.452155E+09 | 1188.04 | 27-MAY-21:41 | 15.60 | 9.97 | 99812838.99 | 74.00 | 26-MAY-21:19 | 15.60 | 9.97 |
June | 0.623797E+09 | 1239.79 | 03-JUN-20:41 | 14.60 | 9.27 | 0.100905E+09 | 77.84 | 19-JUN-21:40 | 18.90 | 15.17 |
July | 0.771986E+09 | 1103.50 | 01-JUL-21:51 | 20.00 | 16.54 | 0.104708E+09 | 79.97 | 17-JUL-21:10 | 22.20 | 19.60 |
August | 0.682841E+09 | 1120.82 | 01-AUG-21:51 | 17.80 | 13.33 | 0.104238E+09 | 76.40 | 01-AUG-21:49 | 17.80 | 13.33 |
September | 0.466361E+09 | 1078.41 | 12-SEP-15:01 | 21.52 | 16.96 | 98606989.78 | 76.45 | 15-SEP-21:10 | 21.60 | 20.41 |
October | 0.264198E+09 | 1052.96 | 25-OCT-15:01 | 18.22 | 9.29 | 97184163.62 | 67.89 | 12-OCT-21:30 | 18.22 | 9.29 |
November | 0.126401E+09 | 998.19 | 05-NOV-15:01 | 17.38 | 13.77 | 92674893.68 | 56.69 | 27-NOV-04:10 | 17.30 | 11.94 |
December | 23571506.32 | 964.56 | 03-DEC-09:02 | 1.10 | -1.3 | 94322349.06 | 56.69 | 29-DEC-04:19 | -8.0 | -8.6 |
Annual Sum or Average | 0.382888E+10 | 0.116177E+10 | ||||||||
Minimum of Months | 14082174.30 | 783.65 | 0.87 | -1.4 | 85226948.54 | 56.69 | -11.7 | -12.6 | ||
Maximum of Months | 0.771986E+09 | 1239.79 | 25.50 | 16.96 | 0.104708E+09 | 79.97 | 22.20 | 20.41 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 7147630.46 | 1320.55 | 15-JAN-16:01 | 4.82 | 1.15 | 93059926.91 | 56.69 | 31-JAN-04:19 | -11.7 | -12.6 |
February | 17056676.91 | 3176.34 | 28-FEB-09:02 | -7.2 | -8.1 | 84290048.94 | 56.69 | 14-FEB-04:19 | -7.2 | -8.1 |
March | 0.200129E+09 | 3317.91 | 01-MAR-09:02 | -4.8 | -6.2 | 96044496.69 | 56.69 | 15-MAR-23:00 | 17.20 | 13.28 |
April | 0.475685E+09 | 3417.42 | 22-APR-18:01 | 13.53 | 6.08 | 94266851.92 | 56.69 | 07-APR-21:19 | 13.53 | 6.08 |
May | 0.108282E+10 | 3466.73 | 27-MAY-18:01 | 18.80 | 10.20 | 98635057.09 | 56.69 | 23-MAY-21:10 | 18.80 | 10.20 |
June | 0.181303E+10 | 3443.15 | 03-JUN-18:01 | 17.80 | 10.05 | 95907443.06 | 56.69 | 28-JUN-21:19 | 19.23 | 18.23 |
July | 0.232530E+10 | 3246.48 | 31-JUL-08:61 | 20.97 | 18.44 | 99109927.16 | 56.70 | 21-JUL-01:49 | 20.97 | 18.44 |
August | 0.210495E+10 | 3157.46 | 16-AUG-08:62 | 19.08 | 15.75 | 99150468.69 | 56.70 | 14-AUG-22:10 | 19.08 | 15.75 |
September | 0.137327E+10 | 3139.79 | 16-SEP-08:61 | 22.98 | 18.69 | 95565477.41 | 56.70 | 21-SEP-21:30 | 17.75 | 15.84 |
October | 0.419773E+09 | 3105.79 | 12-OCT-15:01 | 18.30 | 15.17 | 97062329.43 | 56.69 | 12-OCT-21:49 | 14.60 | 13.81 |
November | 80256247.52 | 2846.77 | 06-NOV-09:01 | 7.30 | 3.68 | 92072797.32 | 56.69 | 27-NOV-04:19 | 17.40 | 11.98 |
December | 8926922.35 | 565.61 | 16-DEC-09:03 | 0.68 | -0.3 | 92979435.40 | 56.69 | 08-DEC-04:19 | 0.68 | -0.3 |
Annual Sum or Average | 0.990835E+10 | 0.113814E+10 | ||||||||
Minimum of Months | 7147630.46 | 565.61 | -7.2 | -8.1 | 84290048.94 | 56.69 | -11.7 | -12.6 | ||
Maximum of Months | 0.232530E+10 | 3466.73 | 22.98 | 18.69 | 99150468.69 | 56.70 | 20.97 | 18.44 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1416136.41 | 534.57 | 17-JAN-19:05 | 7.43 | 6.38 | 92602156.48 | 56.69 | 10-JAN-04:19 | 7.43 | 6.38 |
February | 4074208.01 | 1501.52 | 28-FEB-09:02 | -7.2 | -8.1 | 83766812.65 | 56.69 | 07-FEB-04:19 | -7.2 | -8.1 |
March | 0.105059E+09 | 3084.90 | 22-MAR-15:01 | 14.82 | 6.87 | 95173766.84 | 68.42 | 15-MAR-21:10 | 14.82 | 6.87 |
April | 0.307240E+09 | 3319.92 | 22-APR-18:01 | 13.53 | 6.08 | 94079226.55 | 64.00 | 07-APR-21:40 | 13.53 | 6.08 |
May | 0.817875E+09 | 3383.35 | 21-MAY-19:41 | 14.60 | 9.07 | 0.101173E+09 | 74.80 | 23-MAY-21:10 | 20.60 | 13.34 |
June | 0.144094E+10 | 3709.37 | 30-JUN-08:32 | 19.63 | 14.65 | 0.103150E+09 | 78.68 | 12-JUN-21:40 | 19.63 | 14.65 |
July | 0.189010E+10 | 3641.10 | 10-JUL-08:51 | 21.70 | 17.13 | 0.107218E+09 | 83.23 | 17-JUL-21:10 | 22.20 | 19.60 |
August | 0.161165E+10 | 3804.72 | 05-AUG-08:32 | 23.30 | 17.42 | 0.106399E+09 | 78.17 | 02-AUG-21:40 | 23.30 | 17.42 |
September | 0.895227E+09 | 3410.55 | 09-SEP-08:51 | 18.90 | 14.02 | 0.100045E+09 | 75.69 | 15-SEP-21:10 | 21.60 | 20.41 |
October | 0.205452E+09 | 2989.68 | 11-OCT-08:62 | 12.67 | 10.12 | 96816799.27 | 65.94 | 11-OCT-21:30 | 15.60 | 10.70 |
November | 33776129.79 | 2683.96 | 06-NOV-09:01 | 7.30 | 3.68 | 91159588.93 | 56.69 | 27-NOV-04:19 | 17.40 | 11.98 |
December | 1961449.01 | 511.79 | 01-DEC-19:05 | 6.60 | 4.58 | 92595995.48 | 56.69 | 29-DEC-04:19 | -8.0 | -8.6 |
Annual Sum or Average | 0.731477E+10 | 0.116418E+10 | ||||||||
Minimum of Months | 1416136.41 | 511.79 | -7.2 | -8.1 | 83766812.65 | 56.69 | -8.0 | -8.6 | ||
Maximum of Months | 0.189010E+10 | 3804.72 | 23.30 | 17.42 | 0.107218E+09 | 83.23 | 23.30 | 20.41 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.945344E+09 | 1367.64 | 17-JAN-22:00 | 4.40 | 3.43 | 0.119882E+10 | 707.20 | 17-JAN-22:49 | 4.40 | 3.43 |
February | 0.928960E+09 | 1506.80 | 22-FEB-21:00 | 9.40 | 5.14 | 0.108394E+10 | 714.81 | 22-FEB-22:49 | 7.30 | 5.83 |
March | 0.283163E+10 | 1995.27 | 15-MAR-18:10 | 23.43 | 15.50 | 0.122282E+10 | 805.37 | 15-MAR-21:49 | 17.07 | 13.21 |
April | 0.359429E+10 | 2046.58 | 23-APR-10:33 | 14.80 | 7.30 | 0.121256E+10 | 790.07 | 24-APR-21:40 | 6.47 | 5.18 |
May | 0.445251E+10 | 2253.71 | 27-MAY-10:33 | 19.43 | 12.21 | 0.134903E+10 | 857.05 | 31-MAY-21:40 | 17.67 | 13.17 |
June | 0.493540E+10 | 2496.91 | 29-JUN-10:33 | 24.63 | 19.77 | 0.142004E+10 | 923.00 | 30-JUN-21:40 | 17.97 | 11.44 |
July | 0.543466E+10 | 2588.45 | 21-JUL-10:33 | 29.03 | 21.82 | 0.151985E+10 | 942.95 | 21-JUL-22:10 | 22.30 | 20.72 |
August | 0.533973E+10 | 2560.81 | 19-AUG-10:33 | 22.93 | 15.19 | 0.151392E+10 | 933.85 | 11-AUG-21:40 | 22.93 | 15.19 |
September | 0.469228E+10 | 2403.32 | 16-SEP-10:33 | 25.37 | 19.22 | 0.137833E+10 | 900.47 | 21-SEP-21:40 | 17.57 | 15.72 |
October | 0.382879E+10 | 2055.67 | 11-OCT-10:33 | 18.50 | 13.21 | 0.126109E+10 | 815.00 | 11-OCT-22:10 | 15.68 | 10.85 |
November | 0.261840E+10 | 1785.44 | 05-NOV-10:33 | 18.30 | 12.89 | 0.116915E+10 | 754.51 | 01-NOV-00:10 | 18.30 | 12.89 |
December | 0.100314E+10 | 1437.42 | 01-DEC-22:00 | 6.10 | 3.26 | 0.119883E+10 | 709.38 | 01-DEC-22:49 | 5.68 | 3.22 |
Annual Sum or Average | 0.406051E+11 | 0.155284E+11 | ||||||||
Minimum of Months | 0.928960E+09 | 1367.64 | 4.40 | 3.26 | 0.108394E+10 | 707.20 | 4.40 | 3.22 | ||
Maximum of Months | 0.543466E+10 | 2588.45 | 29.03 | 21.82 | 0.151985E+10 | 942.95 | 22.93 | 20.72 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3945311.69 | 2906.00 | 15-JAN-16:01 | 4.82 | 1.15 | 92626307.42 | 56.69 | 31-JAN-04:19 | -11.7 | -12.6 |
February | 11539596.31 | 3840.65 | 28-FEB-16:01 | 0.40 | -2.4 | 83821911.29 | 56.69 | 01-FEB-02:00 | 0.40 | -2.4 |
March | 0.191651E+09 | 3881.93 | 08-MAR-16:01 | 7.12 | 1.52 | 95360020.29 | 56.69 | 15-MAR-22:40 | 17.03 | 13.22 |
April | 0.435209E+09 | 3904.67 | 19-APR-18:01 | 14.03 | 8.86 | 93660172.51 | 56.69 | 20-APR-01:00 | 11.70 | 7.82 |
May | 0.106708E+10 | 3995.27 | 03-MAY-18:01 | 14.22 | 6.76 | 98297151.19 | 56.70 | 22-MAY-02:09 | 9.90 | 7.14 |
June | 0.193193E+10 | 3931.30 | 15-JUN-18:01 | 17.20 | 9.88 | 95732112.83 | 56.70 | 12-JUN-21:40 | 17.20 | 9.88 |
July | 0.237052E+10 | 3481.73 | 26-JUL-18:02 | 23.12 | 19.90 | 98963650.35 | 56.70 | 19-JUL-22:49 | 23.12 | 19.90 |
August | 0.212201E+10 | 3459.61 | 27-AUG-18:02 | 22.02 | 18.78 | 98952784.58 | 56.70 | 10-AUG-22:00 | 22.02 | 18.78 |
September | 0.127235E+10 | 3547.74 | 08-SEP-18:01 | 21.10 | 16.42 | 95275669.80 | 56.70 | 21-SEP-21:10 | 18.12 | 16.07 |
October | 0.339961E+09 | 3366.33 | 02-OCT-15:01 | 15.92 | 11.18 | 96410525.56 | 56.69 | 12-OCT-21:10 | 15.40 | 14.18 |
November | 41571675.31 | 3185.11 | 14-NOV-16:01 | 9.82 | 7.93 | 91483061.20 | 56.69 | 27-NOV-04:19 | 17.40 | 11.98 |
December | 3407175.53 | 2447.23 | 16-DEC-16:01 | 4.22 | 2.19 | 92635225.37 | 56.69 | 12-DEC-04:19 | 4.22 | 2.19 |
Annual Sum or Average | 0.979117E+10 | 0.113322E+10 | ||||||||
Minimum of Months | 3407175.53 | 2447.23 | 0.40 | -2.4 | 83821911.29 | 56.69 | -11.7 | -12.6 | ||
Maximum of Months | 0.237052E+10 | 3995.27 | 23.12 | 19.90 | 98963650.35 | 56.70 | 23.12 | 19.90 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 267299.97 | 559.04 | 15-JAN-16:03 | 4.82 | 1.15 | 92373903.50 | 56.69 | 06-JAN-04:19 | 4.82 | 1.15 |
February | 1132567.20 | 623.43 | 22-FEB-16:03 | 10.78 | 5.11 | 83502948.09 | 56.69 | 01-FEB-03:39 | 10.78 | 5.11 |
March | 89017717.32 | 3678.24 | 28-MAR-18:01 | 5.40 | -0.5 | 94638656.98 | 69.27 | 15-MAR-21:30 | 5.40 | -0.5 |
April | 0.274586E+09 | 4408.04 | 19-APR-18:11 | 13.67 | 8.82 | 93440743.59 | 68.79 | 19-APR-18:10 | 13.67 | 8.82 |
May | 0.750219E+09 | 4419.43 | 03-MAY-18:01 | 14.22 | 6.76 | 0.103275E+09 | 94.58 | 31-MAY-18:10 | 20.82 | 13.97 |
June | 0.153293E+10 | 3902.39 | 24-JUN-21:51 | 15.60 | 12.99 | 0.107994E+09 | 100.58 | 19-JUN-18:10 | 15.60 | 12.99 |
July | 0.199870E+10 | 3971.13 | 06-JUL-21:51 | 16.70 | 12.85 | 0.108278E+09 | 95.35 | 06-JUL-18:10 | 16.70 | 12.85 |
August | 0.166563E+10 | 3981.67 | 02-AUG-21:51 | 17.20 | 12.20 | 0.107825E+09 | 98.53 | 02-AUG-18:10 | 17.20 | 12.20 |
September | 0.758560E+09 | 3691.53 | 04-SEP-19:11 | 14.03 | 10.64 | 0.102069E+09 | 84.61 | 11-SEP-18:10 | 16.83 | 11.65 |
October | 0.136045E+09 | 3401.13 | 22-OCT-15:01 | 21.60 | 14.51 | 96314562.71 | 69.37 | 11-OCT-21:30 | 21.60 | 14.51 |
November | 16129638.52 | 2558.21 | 15-NOV-16:01 | 11.32 | 6.61 | 90519508.99 | 56.69 | 27-NOV-04:19 | 17.40 | 11.98 |
December | 767880.13 | 537.33 | 16-DEC-16:04 | 4.22 | 2.19 | 92339094.50 | 56.69 | 05-DEC-04:19 | 4.22 | 2.19 |
Annual Sum or Average | 0.722399E+10 | 0.117257E+10 | ||||||||
Minimum of Months | 267299.97 | 537.33 | 4.22 | -0.5 | 83502948.09 | 56.69 | 4.22 | -0.5 | ||
Maximum of Months | 0.199870E+10 | 4419.43 | 21.60 | 14.51 | 0.108278E+09 | 100.58 | 21.60 | 14.51 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 43593786.10 | 2084.62 | 12-JAN-16:01 | -6.2 | -8.3 | 94428359.02 | 56.69 | 27-JAN-04:19 | -4.6 | -5.9 |
February | 45248874.94 | 2096.10 | 28-FEB-16:01 | 0.40 | -2.4 | 85332525.65 | 56.69 | 01-FEB-04:19 | 0.40 | -2.4 |
March | 0.286995E+09 | 2109.23 | 08-MAR-16:01 | 7.12 | 1.52 | 96960107.14 | 56.69 | 15-MAR-21:30 | 17.80 | 13.45 |
April | 0.375261E+09 | 2075.99 | 22-APR-18:01 | 13.53 | 6.08 | 94320535.08 | 56.69 | 07-APR-21:00 | 13.53 | 6.08 |
May | 0.647413E+09 | 2122.76 | 03-MAY-18:01 | 14.22 | 6.76 | 98366884.32 | 56.69 | 10-MAY-23:10 | 15.60 | 13.84 |
June | 0.970333E+09 | 2077.57 | 03-JUN-18:01 | 17.80 | 10.05 | 95647813.01 | 56.69 | 29-JUN-21:00 | 20.00 | 18.86 |
July | 0.130111E+10 | 1912.99 | 05-JUL-15:02 | 22.98 | 20.66 | 98946092.49 | 56.69 | 03-JUL-21:49 | 22.98 | 20.66 |
August | 0.127096E+10 | 1899.58 | 18-AUG-08:61 | 22.57 | 16.57 | 98962113.50 | 56.69 | 09-AUG-22:40 | 22.57 | 16.57 |
September | 0.993639E+09 | 2080.63 | 02-SEP-18:01 | 16.83 | 10.26 | 95500161.44 | 56.69 | 19-SEP-21:49 | 15.28 | 12.34 |
October | 0.512189E+09 | 1837.47 | 04-OCT-15:01 | 15.92 | 12.43 | 97586783.28 | 56.69 | 11-OCT-22:19 | 15.77 | 10.88 |
November | 0.194029E+09 | 1817.15 | 16-NOV-16:01 | 17.38 | 13.61 | 93150245.54 | 56.69 | 27-NOV-03:00 | 17.20 | 11.90 |
December | 44906357.71 | 2061.16 | 11-DEC-16:01 | -9.3 | -9.8 | 94051790.69 | 56.69 | 12-DEC-04:19 | -10.7 | -11.0 |
Annual Sum or Average | 0.668568E+10 | 0.114325E+10 | ||||||||
Minimum of Months | 43593786.10 | 1817.15 | -9.3 | -9.8 | 85332525.65 | 56.69 | -10.7 | -11.0 | ||
Maximum of Months | 0.130111E+10 | 2122.76 | 22.98 | 20.66 | 98962113.50 | 56.69 | 22.98 | 20.66 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.290373E+11 | 16886.77 | 17-JAN-23:00 | 4.40 | 3.43 | 0.185343E+11 | 11347.93 | 13-JAN-00:20 | 4.40 | 3.43 |
February | 0.262221E+11 | 16905.09 | 22-FEB-23:00 | 7.20 | 6.11 | 0.167617E+11 | 11347.92 | 03-FEB-00:20 | 7.20 | 6.11 |
March | 0.322025E+11 | 20595.20 | 15-MAR-21:10 | 18.53 | 13.66 | 0.189548E+11 | 11348.64 | 14-MAR-22:10 | 18.53 | 13.66 |
April | 0.335795E+11 | 19657.03 | 07-APR-21:54 | 15.00 | 10.09 | 0.185066E+11 | 11348.35 | 07-APR-22:10 | 14.90 | 10.09 |
May | 0.381261E+11 | 21093.59 | 23-MAY-21:52 | 20.60 | 13.34 | 0.192615E+11 | 11349.23 | 31-MAY-22:10 | 17.55 | 13.48 |
June | 0.402583E+11 | 22256.92 | 27-JUN-21:20 | 22.03 | 20.71 | 0.187268E+11 | 11356.50 | 30-JUN-21:19 | 18.13 | 11.21 |
July | 0.433784E+11 | 22921.78 | 20-JUL-21:20 | 25.40 | 23.97 | 0.192942E+11 | 11359.94 | 21-JUL-21:19 | 22.60 | 21.00 |
August | 0.423998E+11 | 22634.71 | 10-AUG-22:00 | 25.60 | 18.99 | 0.193642E+11 | 11354.27 | 08-AUG-21:19 | 25.60 | 18.99 |
September | 0.378557E+11 | 21513.74 | 15-SEP-21:53 | 21.10 | 19.92 | 0.186406E+11 | 11349.08 | 08-SEP-22:10 | 21.10 | 19.92 |
October | 0.348843E+11 | 19921.57 | 12-OCT-21:44 | 14.60 | 13.81 | 0.190888E+11 | 11348.63 | 11-OCT-21:00 | 14.60 | 13.81 |
November | 0.315977E+11 | 18230.68 | 16-NOV-23:00 | 7.80 | 5.20 | 0.183145E+11 | 11348.13 | 13-NOV-00:20 | 7.80 | 5.20 |
December | 0.294085E+11 | 17208.10 | 01-DEC-23:00 | 5.60 | 3.21 | 0.185774E+11 | 11347.92 | 26-DEC-00:20 | -11.1 | -12.1 |
Annual Sum or Average | 0.418950E+12 | 0.224025E+12 | ||||||||
Minimum of Months | 0.262221E+11 | 16886.77 | 4.40 | 3.21 | 0.167617E+11 | 11347.92 | -11.1 | -12.1 | ||
Maximum of Months | 0.433784E+11 | 22921.78 | 25.60 | 23.97 | 0.193642E+11 | 11359.94 | 25.60 | 21.00 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.324339E+11 | 18937.74 | 17-JAN-23:00 | 4.40 | 3.43 | 0.188359E+11 | 11348.01 | 30-JAN-00:20 | -9.6 | -10.6 |
February | 0.293096E+11 | 18952.97 | 22-FEB-23:00 | 7.20 | 6.11 | 0.170322E+11 | 11348.07 | 01-FEB-00:20 | 7.20 | 6.11 |
March | 0.358632E+11 | 22273.99 | 15-MAR-21:10 | 18.53 | 13.66 | 0.191551E+11 | 11348.65 | 14-MAR-22:10 | 18.53 | 13.66 |
April | 0.372905E+11 | 21457.99 | 07-APR-21:10 | 15.92 | 10.46 | 0.186245E+11 | 11348.36 | 07-APR-22:10 | 14.90 | 10.09 |
May | 0.417788E+11 | 22627.86 | 23-MAY-21:52 | 20.60 | 13.34 | 0.193146E+11 | 11349.23 | 31-MAY-22:10 | 17.55 | 13.48 |
June | 0.434208E+11 | 23582.06 | 27-JUN-21:20 | 22.03 | 20.71 | 0.187485E+11 | 11384.03 | 30-JUN-21:19 | 18.13 | 11.21 |
July | 0.463660E+11 | 24126.81 | 20-JUL-21:20 | 25.40 | 23.97 | 0.193050E+11 | 11375.29 | 11-JUL-21:19 | 25.40 | 23.97 |
August | 0.454312E+11 | 23896.36 | 10-AUG-21:20 | 25.93 | 18.71 | 0.193815E+11 | 11376.37 | 07-AUG-21:19 | 25.93 | 18.71 |
September | 0.411107E+11 | 22965.13 | 15-SEP-21:20 | 21.50 | 20.31 | 0.186803E+11 | 11364.59 | 15-SEP-21:19 | 21.50 | 20.31 |
October | 0.386489E+11 | 21562.98 | 12-OCT-21:05 | 15.40 | 14.18 | 0.192108E+11 | 11348.64 | 11-OCT-21:00 | 15.40 | 14.18 |
November | 0.352386E+11 | 20198.45 | 16-NOV-22:10 | 8.22 | 6.21 | 0.184936E+11 | 11348.16 | 13-NOV-00:20 | 8.22 | 6.21 |
December | 0.328602E+11 | 19256.03 | 01-DEC-23:00 | 5.60 | 3.21 | 0.188631E+11 | 11347.99 | 26-DEC-00:20 | -11.1 | -12.1 |
Annual Sum or Average | 0.459753E+12 | 0.225645E+12 | ||||||||
Minimum of Months | 0.293096E+11 | 18937.74 | 4.40 | 3.21 | 0.170322E+11 | 11347.99 | -11.1 | -12.1 | ||
Maximum of Months | 0.463660E+11 | 24126.81 | 25.93 | 23.97 | 0.193815E+11 | 11384.03 | 25.93 | 23.97 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.472121E+11 | 26871.36 | 15-JAN-11:50 | 4.13 | 2.34 | 0.187939E+11 | 11319.65 | 28-JAN-18:19 | -6.7 | -8.3 |
February | 0.428062E+11 | 26520.32 | 28-FEB-11:33 | -1.5 | -3.8 | 0.169741E+11 | 11319.61 | 11-FEB-18:19 | -1.5 | -3.8 |
March | 0.505011E+11 | 29480.03 | 14-MAR-10:33 | 21.27 | 17.29 | 0.188201E+11 | 11319.61 | 04-MAR-18:19 | 21.27 | 17.29 |
April | 0.509547E+11 | 29819.44 | 22-APR-10:33 | 11.33 | 5.08 | 0.182219E+11 | 11319.61 | 22-APR-17:19 | 14.63 | 6.44 |
May | 0.550732E+11 | 30504.31 | 27-MAY-10:33 | 19.43 | 12.21 | 0.188455E+11 | 11319.68 | 27-MAY-17:19 | 20.03 | 11.03 |
June | 0.555411E+11 | 30946.96 | 12-JUN-10:33 | 28.53 | 19.62 | 0.182525E+11 | 11319.68 | 17-JUN-17:19 | 28.70 | 22.70 |
July | 0.585620E+11 | 31370.87 | 16-JUL-10:40 | 28.50 | 22.06 | 0.188606E+11 | 11319.68 | 08-JUL-17:19 | 28.50 | 22.06 |
August | 0.578636E+11 | 31309.35 | 10-AUG-10:40 | 28.53 | 20.68 | 0.188656E+11 | 11319.68 | 12-AUG-17:19 | 24.43 | 16.84 |
September | 0.540138E+11 | 30577.61 | 04-SEP-10:37 | 18.53 | 13.52 | 0.182431E+11 | 11319.65 | 16-SEP-17:19 | 25.73 | 19.64 |
October | 0.524999E+11 | 29580.17 | 11-OCT-10:33 | 18.50 | 13.21 | 0.188329E+11 | 11319.62 | 07-OCT-17:19 | 18.50 | 13.21 |
November | 0.486542E+11 | 27990.44 | 05-NOV-10:45 | 18.30 | 12.85 | 0.182118E+11 | 11319.66 | 04-NOV-17:19 | 18.30 | 12.85 |
December | 0.473615E+11 | 26770.98 | 16-DEC-11:50 | 4.13 | 1.57 | 0.187968E+11 | 11319.63 | 02-DEC-18:19 | 4.13 | 1.57 |
Annual Sum or Average | 0.621043E+12 | 0.221719E+12 | ||||||||
Minimum of Months | 0.428062E+11 | 26520.32 | -1.5 | -3.8 | 0.169741E+11 | 11319.61 | -6.7 | -8.3 | ||
Maximum of Months | 0.585620E+11 | 31370.87 | 28.53 | 22.06 | 0.188656E+11 | 11319.68 | 28.70 | 22.70 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.118605E+10 | 3268.51 | 15-JAN-11:33 | 3.87 | 2.17 | 0.126885E+10 | 745.63 | 23-JAN-04:49 | -3.0 | -5.0 |
February | 0.117146E+10 | 2782.73 | 22-FEB-21:10 | 9.13 | 5.01 | 0.114721E+10 | 748.15 | 22-FEB-22:40 | 7.40 | 5.54 |
March | 0.482130E+10 | 4249.51 | 15-MAR-18:10 | 23.43 | 15.50 | 0.129593E+10 | 889.73 | 15-MAR-21:40 | 17.43 | 13.33 |
April | 0.688404E+10 | 4208.72 | 23-APR-10:33 | 14.80 | 7.30 | 0.127917E+10 | 842.79 | 07-APR-21:40 | 14.80 | 7.30 |
May | 0.894528E+10 | 4676.07 | 27-MAY-10:33 | 19.43 | 12.21 | 0.142861E+10 | 912.44 | 23-MAY-21:40 | 19.43 | 12.21 |
June | 0.995550E+10 | 5174.96 | 29-JUN-10:33 | 24.63 | 19.77 | 0.150997E+10 | 994.13 | 27-JUN-21:40 | 24.63 | 19.77 |
July | 0.111842E+11 | 6206.74 | 21-JUL-13:30 | 31.15 | 21.91 | 0.163068E+10 | 1007.40 | 18-JUL-22:10 | 31.15 | 21.91 |
August | 0.108611E+11 | 5810.61 | 09-AUG-15:03 | 29.40 | 18.17 | 0.161146E+10 | 1007.39 | 10-AUG-21:19 | 25.93 | 18.71 |
September | 0.928297E+10 | 4933.97 | 16-SEP-10:33 | 25.37 | 19.22 | 0.144471E+10 | 952.94 | 21-SEP-21:30 | 17.75 | 15.84 |
October | 0.733544E+10 | 4284.98 | 11-OCT-10:33 | 18.50 | 13.21 | 0.133027E+10 | 877.33 | 11-OCT-21:40 | 15.60 | 10.74 |
November | 0.493213E+10 | 3738.55 | 27-NOV-11:33 | 14.63 | 10.55 | 0.123644E+10 | 792.21 | 01-NOV-00:10 | 14.63 | 10.55 |
December | 0.146516E+10 | 3255.49 | 16-DEC-11:33 | 3.87 | 1.42 | 0.126893E+10 | 745.62 | 26-DEC-05:10 | -12.2 | -13.2 |
Annual Sum or Average | 0.780246E+11 | 0.164522E+11 | ||||||||
Minimum of Months | 0.117146E+10 | 2782.73 | 3.87 | 1.42 | 0.114721E+10 | 745.62 | -12.2 | -13.2 | ||
Maximum of Months | 0.111842E+11 | 6206.74 | 31.15 | 21.91 | 0.163068E+10 | 1007.40 | 31.15 | 21.91 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -3.3 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -4.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 6.53 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -4.9 | |
Maximum of Months | 0.00 | 0.00 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.667694E+09 | 1200.40 | 04-JAN-07:50 | -13.2 |
February | 0.598307E+09 | 1419.84 | 07-FEB-07:20 | -16.3 |
March | 91523980.02 | 796.34 | 05-MAR-06:00 | -11.1 |
April | 7889808.11 | 318.97 | 17-APR-06:05 | -4.2 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 14.65 |
October | 732918.19 | 139.26 | 30-OCT-06:20 | -0.2 |
November | 25784066.92 | 477.36 | 24-NOV-07:05 | -3.2 |
December | 0.621769E+09 | 1230.92 | 11-DEC-07:10 | -16.4 |
Annual Sum or Average | 0.201370E+10 | |||
Minimum of Months | 0.00 | 0.00 | -16.4 | |
Maximum of Months | 0.667694E+09 | 1419.84 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -3.3 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -4.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 6.53 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -4.9 | |
Maximum of Months | 0.00 | 0.00 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.114491E+09 | 350.55 | 31-JAN-13:40 | -10.9 |
February | 0.134730E+09 | 549.58 | 07-FEB-11:35 | -12.2 |
March | 9103457.78 | 190.22 | 07-MAR-05:00 | -13.3 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 6.53 |
December | 0.113687E+09 | 406.84 | 11-DEC-10:30 | -12.8 |
Annual Sum or Average | 0.372012E+09 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.134730E+09 | 549.58 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.319295E+09 | 424.81 | 31-JAN-18:00 | -12.2 |
February | 0.323524E+09 | 539.21 | 07-FEB-11:03 | -13.0 |
March | 59174042.06 | 285.54 | 07-MAR-05:00 | -13.3 |
April | 74505.30 | 15.09 | 17-APR-04:00 | -3.3 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
November | 841148.09 | 65.80 | 23-NOV-18:00 | 0.60 |
December | 0.272224E+09 | 451.91 | 11-DEC-10:07 | -13.1 |
Annual Sum or Average | 0.975133E+09 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.323524E+09 | 539.21 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -3.3 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -4.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 6.53 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -4.9 | |
Maximum of Months | 0.00 | 0.00 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 |
February | 12580363.65 | 1304.85 | 06-FEB-09:04 | -15.0 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -4.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 6.53 |
December | 832737.99 | 296.11 | 11-DEC-09:25 | -13.6 |
Annual Sum or Average | 13413101.64 | |||
Minimum of Months | 0.00 | 0.00 | -15.0 | |
Maximum of Months | 12580363.65 | 1304.85 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -3.3 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -4.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 6.53 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -4.9 | |
Maximum of Months | 0.00 | 0.00 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.143311E+10 | 1655.04 | 31-JAN-19:02 | -11.8 |
February | 0.124378E+10 | 1678.73 | 06-FEB-09:13 | -15.0 |
March | 0.498682E+09 | 1607.42 | 20-MAR-08:62 | -2.7 |
April | 0.157749E+09 | 1576.42 | 05-APR-08:61 | 3.58 |
May | 7009800.32 | 1569.30 | 02-MAY-15:04 | 16.10 |
June | 1928348.14 | 1024.45 | 14-JUN-08:03 | 11.20 |
July | 1643591.76 | 974.50 | 02-JUL-08:04 | 19.90 |
August | 2203212.46 | 1076.51 | 30-AUG-18:04 | 13.90 |
September | 5660163.23 | 1224.03 | 24-SEP-15:04 | 18.80 |
October | 0.151045E+09 | 1553.97 | 17-OCT-08:62 | -0.0 |
November | 0.486038E+09 | 1617.34 | 30-NOV-16:02 | 3.90 |
December | 0.138694E+10 | 1660.36 | 12-DEC-16:12 | -2.1 |
Annual Sum or Average | 0.537579E+10 | |||
Minimum of Months | 1643591.76 | 974.50 | -15.0 | |
Maximum of Months | 0.143311E+10 | 1678.73 | 19.90 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.165624E+10 | 1655.26 | 31-JAN-19:13 | -11.9 |
February | 0.142873E+10 | 1669.24 | 06-FEB-09:13 | -15.0 |
March | 0.674921E+09 | 1633.79 | 07-MAR-09:02 | -9.0 |
April | 0.198244E+09 | 1581.20 | 05-APR-08:61 | 3.58 |
May | 8365569.37 | 1253.68 | 03-MAY-15:04 | 15.92 |
June | 1425896.61 | 1065.52 | 04-JUN-08:04 | 13.07 |
July | 551790.79 | 1067.22 | 06-JUL-08:04 | 15.97 |
August | 1314703.14 | 1084.40 | 31-AUG-18:14 | 14.80 |
September | 6368856.04 | 1321.22 | 23-SEP-15:04 | 17.02 |
October | 0.210061E+09 | 1587.12 | 17-OCT-08:62 | -0.0 |
November | 0.603223E+09 | 1610.21 | 29-NOV-16:02 | 2.80 |
December | 0.156104E+10 | 1660.32 | 11-DEC-09:13 | -13.7 |
Annual Sum or Average | 0.635048E+10 | |||
Minimum of Months | 551790.79 | 1065.52 | -15.0 | |
Maximum of Months | 0.165624E+10 | 1669.24 | 17.02 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 19159052.64 | 191.86 | 04-JAN-05:00 | -12.2 |
February | 25394219.85 | 248.94 | 07-FEB-05:00 | -15.6 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -4.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 6.53 |
December | 3182760.02 | 69.11 | 10-DEC-06:00 | -13.3 |
Annual Sum or Average | 47736032.50 | |||
Minimum of Months | 0.00 | 0.00 | -15.6 | |
Maximum of Months | 25394219.85 | 248.94 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.212003E+09 | 480.10 | 31-JAN-16:02 | -12.1 |
February | 0.186842E+09 | 481.82 | 06-FEB-16:02 | -13.4 |
March | 75196057.63 | 474.96 | 06-MAR-16:01 | -6.8 |
April | 2355948.94 | 460.13 | 22-APR-15:04 | 15.68 |
May | 841395.76 | 461.52 | 02-MAY-15:04 | 16.10 |
June | 206036.94 | 358.96 | 05-JUN-15:06 | 17.30 |
July | 43719.17 | 137.79 | 31-JUL-21:56 | 22.30 |
August | 135744.54 | 339.19 | 31-AUG-15:06 | 16.70 |
September | 486207.09 | 406.46 | 18-SEP-15:06 | 17.88 |
October | 2342011.54 | 443.36 | 10-OCT-15:04 | 17.70 |
November | 15123730.62 | 451.34 | 05-NOV-15:04 | 17.38 |
December | 0.185602E+09 | 484.61 | 11-DEC-16:01 | -9.3 |
Annual Sum or Average | 0.681177E+09 | |||
Minimum of Months | 43719.17 | 137.79 | -13.4 | |
Maximum of Months | 0.212003E+09 | 484.61 | 22.30 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.138211E+10 | 1618.83 | 31-JAN-19:02 | -11.8 |
February | 0.120739E+10 | 1638.92 | 06-FEB-19:13 | -14.6 |
March | 0.505261E+09 | 1572.67 | 04-MAR-19:02 | -5.1 |
April | 0.157050E+09 | 1517.62 | 16-APR-08:62 | -2.9 |
May | 11003520.35 | 1654.06 | 03-MAY-18:03 | 14.22 |
June | 1123422.13 | 1036.15 | 13-JUN-18:04 | 13.22 |
July | 184633.99 | 584.18 | 02-JUL-08:04 | 19.90 |
August | 978454.61 | 1114.30 | 30-AUG-18:04 | 13.90 |
September | 5763655.13 | 1251.93 | 23-SEP-15:04 | 17.02 |
October | 0.147314E+09 | 1497.93 | 24-OCT-08:62 | 2.30 |
November | 0.487220E+09 | 1584.05 | 30-NOV-16:02 | 3.90 |
December | 0.138272E+10 | 1622.84 | 12-DEC-16:12 | -2.1 |
Annual Sum or Average | 0.528811E+10 | |||
Minimum of Months | 184633.99 | 584.18 | -14.6 | |
Maximum of Months | 0.138272E+10 | 1654.06 | 19.90 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.159700E+10 | 1622.32 | 31-JAN-16:02 | -12.1 |
February | 0.138482E+10 | 1635.89 | 06-FEB-16:02 | -13.4 |
March | 0.684125E+09 | 1606.38 | 06-MAR-16:01 | -6.8 |
April | 0.193648E+09 | 1510.54 | 16-APR-08:62 | -2.9 |
May | 13354064.90 | 1638.11 | 03-MAY-18:03 | 14.22 |
June | 983084.84 | 885.64 | 03-JUN-08:04 | 12.38 |
July | 167291.51 | 413.70 | 11-JUL-21:54 | 20.00 |
August | 723648.70 | 1053.13 | 24-AUG-08:04 | 15.10 |
September | 6811615.58 | 1342.68 | 23-SEP-15:04 | 17.02 |
October | 0.197587E+09 | 1502.19 | 24-OCT-15:01 | 7.30 |
November | 0.595147E+09 | 1577.64 | 23-NOV-16:02 | 2.70 |
December | 0.155521E+10 | 1639.83 | 11-DEC-16:01 | -9.3 |
Annual Sum or Average | 0.622957E+10 | |||
Minimum of Months | 167291.51 | 413.70 | -13.4 | |
Maximum of Months | 0.159700E+10 | 1639.83 | 20.00 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.127231E+09 | 570.47 | 29-JAN-16:00 | -5.6 |
February | 0.105572E+09 | 931.14 | 06-FEB-09:04 | -15.0 |
March | 99853.95 | 74.56 | 07-MAR-07:10 | -12.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
November | 220104.02 | 68.91 | 30-NOV-15:00 | 3.90 |
December | 0.142934E+09 | 738.20 | 11-DEC-09:04 | -13.8 |
Annual Sum or Average | 0.376057E+09 | |||
Minimum of Months | 0.00 | 0.00 | -15.0 | |
Maximum of Months | 0.142934E+09 | 931.14 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.205803E+10 | 1984.88 | 31-JAN-19:13 | -11.9 |
February | 0.179071E+10 | 2006.34 | 06-FEB-09:13 | -15.0 |
March | 0.817688E+09 | 1914.90 | 04-MAR-19:02 | -5.1 |
April | 0.316991E+09 | 1884.59 | 16-APR-08:62 | -2.9 |
May | 31912652.65 | 1292.23 | 17-MAY-15:04 | 16.70 |
June | 2775550.62 | 1046.33 | 13-JUN-08:03 | 8.90 |
July | 1668105.73 | 956.30 | 28-JUL-08:04 | 21.60 |
August | 2172432.97 | 979.71 | 31-AUG-08:03 | 13.90 |
September | 14875967.51 | 1216.52 | 23-SEP-15:04 | 17.02 |
October | 0.313064E+09 | 1868.24 | 17-OCT-08:62 | -0.0 |
November | 0.805838E+09 | 1918.13 | 30-NOV-16:02 | 3.90 |
December | 0.199121E+10 | 1987.42 | 11-DEC-09:13 | -13.7 |
Annual Sum or Average | 0.814693E+10 | |||
Minimum of Months | 1668105.73 | 956.30 | -15.0 | |
Maximum of Months | 0.205803E+10 | 2006.34 | 21.60 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.232373E+10 | 1979.85 | 31-JAN-19:13 | -11.9 |
February | 0.201163E+10 | 1991.03 | 06-FEB-09:13 | -15.0 |
March | 0.104099E+10 | 1933.50 | 07-MAR-09:02 | -9.0 |
April | 0.379112E+09 | 1886.35 | 05-APR-08:61 | 3.58 |
May | 34718053.78 | 1277.36 | 03-MAY-15:04 | 15.92 |
June | 1757948.95 | 930.20 | 04-JUN-08:04 | 13.07 |
July | 619633.43 | 907.33 | 06-JUL-08:04 | 15.97 |
August | 1243784.76 | 1014.22 | 31-AUG-08:03 | 13.90 |
September | 16483438.26 | 1268.62 | 23-SEP-15:04 | 17.02 |
October | 0.408509E+09 | 1889.59 | 17-OCT-08:62 | -0.0 |
November | 0.966457E+09 | 1906.93 | 29-NOV-16:02 | 2.80 |
December | 0.219592E+10 | 1982.43 | 11-DEC-09:13 | -13.7 |
Annual Sum or Average | 0.938117E+10 | |||
Minimum of Months | 619633.43 | 907.33 | -15.0 | |
Maximum of Months | 0.232373E+10 | 1991.03 | 17.02 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.671981E+09 | 1028.02 | 03-JAN-16:13 | -6.3 |
February | 0.607449E+09 | 1042.23 | 06-FEB-09:13 | -15.0 |
March | 0.197441E+09 | 991.74 | 20-MAR-08:62 | -2.7 |
April | 70776539.61 | 964.78 | 17-APR-08:62 | -0.8 |
May | 4183556.45 | 884.54 | 17-MAY-15:04 | 16.70 |
June | 1000176.89 | 608.05 | 07-JUN-15:04 | 18.30 |
July | 490413.89 | 497.88 | 05-JUL-08:04 | 20.47 |
August | 901218.56 | 576.08 | 09-AUG-08:04 | 21.97 |
September | 2057202.54 | 755.65 | 23-SEP-15:04 | 17.02 |
October | 48536928.99 | 951.67 | 24-OCT-08:62 | 2.30 |
November | 0.196015E+09 | 1008.93 | 30-NOV-16:02 | 3.90 |
December | 0.691128E+09 | 1030.66 | 12-DEC-16:12 | -2.1 |
Annual Sum or Average | 0.249196E+10 | |||
Minimum of Months | 490413.89 | 497.88 | -15.0 | |
Maximum of Months | 0.691128E+09 | 1042.23 | 21.97 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -3.3 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -4.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 6.53 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -4.9 | |
Maximum of Months | 0.00 | 0.00 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -3.3 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -4.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 6.53 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -4.9 | |
Maximum of Months | 0.00 | 0.00 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -3.3 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -4.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 6.53 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -4.9 | |
Maximum of Months | 0.00 | 0.00 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.733276E+09 | 1964.55 | 10-JAN-07:05 | -11.4 |
February | 0.703331E+09 | 2879.23 | 07-FEB-07:15 | -16.3 |
March | 0.110944E+09 | 1516.65 | 07-MAR-07:05 | -12.9 |
April | 222076.83 | 163.57 | 17-APR-06:05 | -4.2 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
November | 974093.84 | 315.78 | 24-NOV-07:10 | -3.2 |
December | 0.732455E+09 | 2587.06 | 11-DEC-07:05 | -16.4 |
Annual Sum or Average | 0.228120E+10 | |||
Minimum of Months | 0.00 | 0.00 | -16.4 | |
Maximum of Months | 0.733276E+09 | 2879.23 | 18.85 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.136942E+11 | 13190.31 | 02-JAN-20:10 | 0.121516E+11 | 9632.53 | 02-JAN-20:10 |
February | 0.123646E+11 | 13190.31 | 01-FEB-20:10 | 0.109726E+11 | 9632.53 | 01-FEB-20:10 |
March | 0.137364E+11 | 13190.31 | 01-MAR-20:10 | 0.121771E+11 | 9632.53 | 01-MAR-20:10 |
April | 0.132299E+11 | 13190.31 | 03-APR-19:10 | 0.117446E+11 | 9632.53 | 03-APR-19:10 |
May | 0.137180E+11 | 13190.31 | 01-MAY-19:10 | 0.121662E+11 | 9632.53 | 01-MAY-19:10 |
June | 0.132906E+11 | 13190.31 | 01-JUN-19:10 | 0.117829E+11 | 9632.53 | 01-JUN-19:10 |
July | 0.136573E+11 | 13190.31 | 03-JUL-19:10 | 0.121279E+11 | 9632.53 | 03-JUL-19:10 |
August | 0.137417E+11 | 13190.31 | 01-AUG-19:10 | 0.121808E+11 | 9632.53 | 01-AUG-19:10 |
September | 0.132352E+11 | 13190.31 | 01-SEP-19:10 | 0.117482E+11 | 9632.53 | 01-SEP-19:10 |
October | 0.136889E+11 | 13190.31 | 02-OCT-19:10 | 0.121479E+11 | 9632.53 | 02-OCT-19:10 |
November | 0.132800E+11 | 13190.31 | 01-NOV-19:10 | 0.117774E+11 | 9632.53 | 01-NOV-19:10 |
December | 0.136573E+11 | 13190.31 | 01-DEC-20:10 | 0.121279E+11 | 9632.53 | 01-DEC-20:10 |
Annual Sum or Average | 0.161294E+12 | 0.143105E+12 | ||||
Minimum of Months | 0.123646E+11 | 13190.31 | 0.109726E+11 | 9632.53 | ||
Maximum of Months | 0.137417E+11 | 13190.31 | 0.121808E+11 | 9632.53 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.620421E+09 | 597.59 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.560184E+09 | 597.59 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.622334E+09 | 597.59 | 01-MAR-20:10 | 0.866718E+09 | 685.60 | 01-MAR-20:10 |
April | 0.599386E+09 | 597.59 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.621497E+09 | 597.59 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.602135E+09 | 597.59 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.618748E+09 | 597.59 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.622573E+09 | 597.59 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.599625E+09 | 597.59 | 01-SEP-19:10 | 0.836191E+09 | 685.60 | 01-SEP-19:10 |
October | 0.620182E+09 | 597.59 | 02-OCT-19:10 | 0.864640E+09 | 685.60 | 02-OCT-19:10 |
November | 0.601657E+09 | 597.59 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.618748E+09 | 597.59 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.730749E+10 | 0.101856E+11 | ||||
Minimum of Months | 0.560184E+09 | 597.59 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.622573E+09 | 597.59 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.718450E+09 | 692.02 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.648695E+09 | 692.02 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.720665E+09 | 692.02 | 01-MAR-20:10 | 0.100366E+10 | 793.93 | 01-MAR-20:10 |
April | 0.694091E+09 | 692.02 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.719696E+09 | 692.02 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.697275E+09 | 692.02 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.716513E+09 | 692.02 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.720942E+09 | 692.02 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.694368E+09 | 692.02 | 01-SEP-19:10 | 0.968312E+09 | 793.93 | 01-SEP-19:10 |
October | 0.718174E+09 | 692.02 | 02-OCT-19:10 | 0.100126E+10 | 793.93 | 02-OCT-19:10 |
November | 0.696721E+09 | 692.02 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.716513E+09 | 692.02 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.846210E+10 | 0.117950E+11 | ||||
Minimum of Months | 0.648695E+09 | 692.02 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.720942E+09 | 692.02 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.710312E+09 | 684.18 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.641347E+09 | 684.18 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.712502E+09 | 684.18 | 01-MAR-20:10 | 0.106120E+10 | 839.45 | 01-MAR-20:10 |
April | 0.686229E+09 | 684.18 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.711544E+09 | 684.18 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.689376E+09 | 684.18 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.708397E+09 | 684.18 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.712775E+09 | 684.18 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.686503E+09 | 684.18 | 01-SEP-19:10 | 0.102382E+10 | 839.45 | 01-SEP-19:10 |
October | 0.710039E+09 | 684.18 | 02-OCT-19:10 | 0.105866E+10 | 839.45 | 02-OCT-19:10 |
November | 0.688829E+09 | 684.18 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.708397E+09 | 684.18 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.836625E+10 | 0.124712E+11 | ||||
Minimum of Months | 0.641347E+09 | 684.18 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.712775E+09 | 684.18 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.261454E+09 | 251.84 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.236069E+09 | 251.84 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.262260E+09 | 251.84 | 01-MAR-20:10 | 0.306128E+09 | 242.16 | 01-MAR-20:10 |
April | 0.252589E+09 | 251.84 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.261907E+09 | 251.84 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.253748E+09 | 251.84 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.260749E+09 | 251.84 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.262360E+09 | 251.84 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.252690E+09 | 251.84 | 01-SEP-19:10 | 0.295345E+09 | 242.16 | 01-SEP-19:10 |
October | 0.261353E+09 | 251.84 | 02-OCT-19:10 | 0.305393E+09 | 242.16 | 02-OCT-19:10 |
November | 0.253546E+09 | 251.84 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.260749E+09 | 251.84 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.307947E+10 | 0.359760E+10 | ||||
Minimum of Months | 0.236069E+09 | 251.84 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.262360E+09 | 251.84 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.337502E+09 | 325.08 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.304733E+09 | 325.08 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.338542E+09 | 325.08 | 01-MAR-20:10 | 0.578079E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.326059E+09 | 325.08 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.338087E+09 | 325.08 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.327554E+09 | 325.08 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.336592E+09 | 325.08 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.338672E+09 | 325.08 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.326189E+09 | 325.08 | 01-SEP-19:10 | 0.557718E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.337372E+09 | 325.08 | 02-OCT-19:10 | 0.576693E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.327294E+09 | 325.08 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.336592E+09 | 325.08 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.397519E+10 | 0.679355E+11 | ||||
Minimum of Months | 0.304733E+09 | 325.08 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.338672E+09 | 325.08 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.136920E+10 | 1701.53 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.118801E+10 | 1701.53 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.122513E+10 | 1701.53 | 01-MAR-20:10 | 0.122027E+10 | 965.27 | 01-MAR-20:10 |
April | 0.108248E+10 | 1701.53 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.103308E+10 | 1701.53 | 01-MAY-19:10 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.940428E+09 | 1701.53 | 01-JUN-19:30 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.981787E+09 | 1701.53 | 03-JUL-19:40 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.106036E+10 | 1701.53 | 01-AUG-19:30 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.115346E+10 | 1701.53 | 01-SEP-19:10 | 0.117729E+10 | 965.27 | 01-SEP-19:10 |
October | 0.129438E+10 | 1701.53 | 02-OCT-19:10 | 0.121734E+10 | 965.27 | 02-OCT-19:10 |
November | 0.132139E+10 | 1701.53 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.137893E+10 | 1701.53 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.140286E+11 | 0.143405E+11 | ||||
Minimum of Months | 0.940428E+09 | 1701.53 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.137893E+10 | 1701.53 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.949005E+10 | 9504.80 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.851817E+10 | 9504.80 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.938328E+10 | 9504.80 | 01-MAR-20:10 | 0.126786E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.895462E+10 | 9504.80 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.921335E+10 | 9504.80 | 01-MAY-19:10 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.886014E+10 | 9504.80 | 01-JUN-19:30 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.912206E+10 | 9504.80 | 03-JUL-19:30 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.924239E+10 | 9504.80 | 01-AUG-19:19 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.901875E+10 | 9504.80 | 01-SEP-19:10 | 0.122320E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.941270E+10 | 9504.80 | 02-OCT-19:10 | 0.126482E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.919707E+10 | 9504.80 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.948001E+10 | 9504.80 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.109893E+12 | 0.148998E+12 | ||||
Minimum of Months | 0.851817E+10 | 9504.80 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.949005E+10 | 9504.80 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196602E+09 | 177.88 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.177551E+09 | 177.88 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.195039E+09 | 177.88 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.190486E+09 | 177.88 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.195821E+09 | 177.88 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.188975E+09 | 177.88 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.197358E+09 | 177.88 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.195039E+09 | 177.88 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.190538E+09 | 177.88 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.196576E+09 | 177.88 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.189731E+09 | 177.88 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.197383E+09 | 177.88 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.231110E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.177551E+09 | 177.88 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.197383E+09 | 177.88 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196579E+09 | 177.86 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.177530E+09 | 177.86 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.195017E+09 | 177.86 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.190464E+09 | 177.86 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.195798E+09 | 177.86 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.188953E+09 | 177.86 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.197334E+09 | 177.86 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.195017E+09 | 177.86 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.190515E+09 | 177.86 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.196553E+09 | 177.86 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.189708E+09 | 177.86 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.197360E+09 | 177.86 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.231083E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.177530E+09 | 177.86 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.197360E+09 | 177.86 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123557E+09 | 111.79 | 01-JAN-19:10 | 0.217935E+09 | 232.19 | 01-JAN-08:09 |
February | 0.111584E+09 | 111.79 | 01-FEB-20:10 | 0.196843E+09 | 232.19 | 01-FEB-07:10 |
March | 0.122575E+09 | 111.79 | 01-MAR-20:10 | 0.217824E+09 | 232.19 | 01-MAR-07:10 |
April | 0.119713E+09 | 111.79 | 01-APR-18:10 | 0.210923E+09 | 232.19 | 01-APR-07:10 |
May | 0.123066E+09 | 111.79 | 01-MAY-19:10 | 0.217879E+09 | 232.19 | 01-MAY-06:10 |
June | 0.118764E+09 | 111.79 | 01-JUN-19:10 | 0.210812E+09 | 232.19 | 01-JUN-06:10 |
July | 0.124032E+09 | 111.79 | 01-JUL-18:10 | 0.217991E+09 | 232.19 | 01-JUL-07:10 |
August | 0.122575E+09 | 111.79 | 01-AUG-19:10 | 0.217824E+09 | 232.19 | 01-AUG-06:10 |
September | 0.119746E+09 | 111.79 | 01-SEP-19:10 | 0.210923E+09 | 232.19 | 01-SEP-06:10 |
October | 0.123541E+09 | 111.79 | 01-OCT-18:10 | 0.217935E+09 | 232.19 | 01-OCT-07:10 |
November | 0.119238E+09 | 111.79 | 01-NOV-19:10 | 0.210867E+09 | 232.19 | 01-NOV-06:10 |
December | 0.124048E+09 | 111.79 | 01-DEC-20:10 | 0.217991E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.145244E+10 | 0.256575E+10 | ||||
Minimum of Months | 0.111584E+09 | 111.79 | 0.196843E+09 | 232.19 | ||
Maximum of Months | 0.124048E+09 | 111.79 | 0.217991E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123591E+09 | 111.82 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 0.111614E+09 | 111.82 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 0.122608E+09 | 111.82 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 0.119746E+09 | 111.82 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 0.123099E+09 | 111.82 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 0.118796E+09 | 111.82 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 0.124066E+09 | 111.82 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 0.122608E+09 | 111.82 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 0.119778E+09 | 111.82 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 0.123574E+09 | 111.82 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 0.119271E+09 | 111.82 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 0.124082E+09 | 111.82 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.145283E+10 | 0.256645E+10 | ||||
Minimum of Months | 0.111614E+09 | 111.82 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 0.124082E+09 | 111.82 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196602E+09 | 177.88 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.177551E+09 | 177.88 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.195039E+09 | 177.88 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.190486E+09 | 177.88 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.195821E+09 | 177.88 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.188975E+09 | 177.88 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.197358E+09 | 177.88 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.195039E+09 | 177.88 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.190538E+09 | 177.88 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.196576E+09 | 177.88 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.189731E+09 | 177.88 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.197383E+09 | 177.88 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.231110E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.177551E+09 | 177.88 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.197383E+09 | 177.88 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196579E+09 | 177.86 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.177530E+09 | 177.86 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.195017E+09 | 177.86 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.190464E+09 | 177.86 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.195798E+09 | 177.86 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.188953E+09 | 177.86 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.197334E+09 | 177.86 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.195017E+09 | 177.86 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.190515E+09 | 177.86 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.196553E+09 | 177.86 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.189708E+09 | 177.86 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.197360E+09 | 177.86 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.231083E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.177530E+09 | 177.86 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.197360E+09 | 177.86 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.193865E+10 | 1867.32 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.175042E+10 | 1867.32 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.194462E+10 | 1867.32 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.187292E+10 | 1867.32 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.194201E+10 | 1867.32 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.188151E+10 | 1867.32 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.193342E+10 | 1867.32 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.194537E+10 | 1867.32 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.187367E+10 | 1867.32 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.193790E+10 | 1867.32 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.188002E+10 | 1867.32 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.193342E+10 | 1867.32 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.228339E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.175042E+10 | 1867.32 | 0.00 | 0.00 | |
Maximum of Months | 0.194537E+10 | 1867.32 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196602E+09 | 177.88 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.177551E+09 | 177.88 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.195039E+09 | 177.88 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.190486E+09 | 177.88 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.195821E+09 | 177.88 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.188975E+09 | 177.88 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.197358E+09 | 177.88 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.195039E+09 | 177.88 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.190538E+09 | 177.88 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.196576E+09 | 177.88 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.189731E+09 | 177.88 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.197383E+09 | 177.88 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.231110E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.177551E+09 | 177.88 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.197383E+09 | 177.88 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196579E+09 | 177.86 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.177530E+09 | 177.86 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.195017E+09 | 177.86 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.190464E+09 | 177.86 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.195798E+09 | 177.86 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.188953E+09 | 177.86 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.197334E+09 | 177.86 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.195017E+09 | 177.86 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.190515E+09 | 177.86 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.196553E+09 | 177.86 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.189708E+09 | 177.86 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.197360E+09 | 177.86 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.231083E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.177530E+09 | 177.86 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.197360E+09 | 177.86 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123591E+09 | 111.82 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 0.111614E+09 | 111.82 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 0.122608E+09 | 111.82 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 0.119746E+09 | 111.82 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 0.123099E+09 | 111.82 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 0.118796E+09 | 111.82 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 0.124066E+09 | 111.82 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 0.122608E+09 | 111.82 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 0.119778E+09 | 111.82 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 0.123574E+09 | 111.82 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 0.119271E+09 | 111.82 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 0.124082E+09 | 111.82 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.145283E+10 | 0.256645E+10 | ||||
Minimum of Months | 0.111614E+09 | 111.82 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 0.124082E+09 | 111.82 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.280137E+10 | 2988.03 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.246864E+10 | 2988.03 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.265239E+10 | 2988.03 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.244620E+10 | 2988.03 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.243398E+10 | 2988.03 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.228595E+10 | 2988.03 | 01-JUN-19:40 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.236914E+10 | 2988.03 | 03-JUL-19:40 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.246697E+10 | 2988.03 | 01-AUG-19:30 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.252318E+10 | 2988.03 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.272048E+10 | 2988.03 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.271307E+10 | 2988.03 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.280838E+10 | 2988.03 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.306898E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.228595E+10 | 2988.03 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.280838E+10 | 2988.03 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.280137E+10 | 2988.03 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.246864E+10 | 2988.03 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.265239E+10 | 2988.03 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.244620E+10 | 2988.03 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.243398E+10 | 2988.03 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.228595E+10 | 2988.03 | 01-JUN-19:40 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.236914E+10 | 2988.03 | 03-JUL-19:40 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.246697E+10 | 2988.03 | 01-AUG-19:30 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.252318E+10 | 2988.03 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.272048E+10 | 2988.03 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.271307E+10 | 2988.03 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.280838E+10 | 2988.03 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.306898E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.228595E+10 | 2988.03 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.280838E+10 | 2988.03 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.110133E+10 | 1060.81 | 02-JAN-20:10 | 0.368383E+11 | 16487.34 | 01-JAN-07:10 |
February | 0.994402E+09 | 1060.81 | 01-FEB-20:10 | 0.332733E+11 | 16487.34 | 01-FEB-07:10 |
March | 0.110473E+10 | 1060.81 | 01-MAR-20:10 | 0.368383E+11 | 16487.34 | 01-MAR-07:10 |
April | 0.106399E+10 | 1060.81 | 03-APR-19:10 | 0.356500E+11 | 16487.34 | 01-APR-06:10 |
May | 0.110324E+10 | 1060.81 | 01-MAY-19:10 | 0.368383E+11 | 16487.34 | 01-MAY-06:10 |
June | 0.106887E+10 | 1060.81 | 01-JUN-19:10 | 0.356500E+11 | 16487.34 | 01-JUN-06:10 |
July | 0.109836E+10 | 1060.81 | 03-JUL-19:10 | 0.368383E+11 | 16487.34 | 01-JUL-06:10 |
August | 0.110515E+10 | 1060.81 | 01-AUG-19:10 | 0.368383E+11 | 16487.34 | 01-AUG-06:10 |
September | 0.106442E+10 | 1060.81 | 01-SEP-19:10 | 0.356500E+11 | 16487.34 | 01-SEP-06:10 |
October | 0.110091E+10 | 1060.81 | 02-OCT-19:10 | 0.368383E+11 | 16487.34 | 01-OCT-06:10 |
November | 0.106802E+10 | 1060.81 | 01-NOV-19:10 | 0.356500E+11 | 16487.34 | 01-NOV-06:10 |
December | 0.109836E+10 | 1060.81 | 01-DEC-20:10 | 0.368383E+11 | 16487.34 | 01-DEC-07:10 |
Annual Sum or Average | 0.129718E+11 | 0.433742E+12 | ||||
Minimum of Months | 0.994402E+09 | 1060.81 | 0.332733E+11 | 16487.34 | ||
Maximum of Months | 0.110515E+10 | 1060.81 | 0.368383E+11 | 16487.34 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.205176E+10 | 1976.27 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.185255E+10 | 1976.27 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.205809E+10 | 1976.27 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.198220E+10 | 1976.27 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.205532E+10 | 1976.27 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.199129E+10 | 1976.27 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.204623E+10 | 1976.27 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.205888E+10 | 1976.27 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.198299E+10 | 1976.27 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.205097E+10 | 1976.27 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.198971E+10 | 1976.27 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.204623E+10 | 1976.27 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.241662E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.185255E+10 | 1976.27 | 0.00 | 0.00 | |
Maximum of Months | 0.205888E+10 | 1976.27 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.136942E+11 | 0.121516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.123646E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196682E+11 | 0.137364E+11 | 0.121771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.132299E+11 | 0.117446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.137180E+11 | 0.121662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.132906E+11 | 0.117829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.136573E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.137417E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189689E+11 | 0.132352E+11 | 0.117482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195854E+11 | 0.136889E+11 | 0.121479E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.132800E+11 | 0.117774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.136573E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230861E+12 | 0.161294E+12 | 0.143105E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.176991E+11 | 0.123646E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196682E+11 | 0.137417E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.620421E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.373955E+09 |
February | 0.179968E+10 | 0.560184E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.350522E+09 |
March | 0.199990E+10 | 0.622334E+09 | 0.866718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 343011.17 | 0.283152E+09 |
April | 0.192973E+10 | 0.599386E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197071E+09 |
May | 0.199475E+10 | 0.621497E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 361115.15 | 0.113994E+09 |
June | 0.193394E+10 | 0.602135E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6120905.82 | 56947374.06 |
July | 0.199054E+10 | 0.618748E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13511546.84 | 24884346.57 |
August | 0.199896E+10 | 0.622573E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9815389.55 | 39253652.18 |
September | 0.192879E+10 | 0.599625E+09 | 0.836191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1124113.65 | 80051321.14 |
October | 0.199148E+10 | 0.620182E+09 | 0.864640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172760E+09 |
November | 0.192552E+10 | 0.601657E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216425E+09 |
December | 0.199054E+10 | 0.618748E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.353090E+09 |
Annual Sum or Average | 0.234744E+11 | 0.730749E+10 | 0.101856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 31276082.19 | 0.226211E+10 |
Minimum of Months | 0.179968E+10 | 0.560184E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24884346.57 |
Maximum of Months | 0.199990E+10 | 0.622573E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13511546.84 | 0.373955E+09 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.718450E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146125E+09 |
February | 0.208403E+10 | 0.648695E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136824E+09 |
March | 0.231589E+10 | 0.720665E+09 | 0.100366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 212878.01 | 0.113283E+09 |
April | 0.223463E+10 | 0.694091E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81410388.07 |
May | 0.230993E+10 | 0.719696E+09 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 187491.36 | 50723609.32 |
June | 0.223950E+10 | 0.697275E+09 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2175488.94 | 27345850.46 |
July | 0.230505E+10 | 0.716513E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5132336.85 | 13677516.41 |
August | 0.231480E+10 | 0.720942E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3944958.62 | 19791031.95 |
September | 0.223354E+10 | 0.694368E+09 | 0.968312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 439167.07 | 36395855.64 |
October | 0.230614E+10 | 0.718174E+09 | 0.100126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72657398.65 |
November | 0.222975E+10 | 0.696721E+09 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88423728.70 |
December | 0.230505E+10 | 0.716513E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138372E+09 |
Annual Sum or Average | 0.271834E+11 | 0.846210E+10 | 0.117950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 12092320.84 | 0.925030E+09 |
Minimum of Months | 0.208403E+10 | 0.648695E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13677516.41 |
Maximum of Months | 0.231589E+10 | 0.720942E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5132336.85 | 0.146125E+09 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.487480E+09 | 0.710312E+09 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340380E+09 |
February | 0.440737E+09 | 0.641347E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318957E+09 |
March | 0.489771E+09 | 0.712502E+09 | 0.106120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 654831.93 | 0.257722E+09 |
April | 0.472586E+09 | 0.686229E+09 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181615E+09 |
May | 0.488511E+09 | 0.711544E+09 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 596117.83 | 0.112815E+09 |
June | 0.473617E+09 | 0.689376E+09 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5334931.63 | 61876311.51 |
July | 0.487480E+09 | 0.708397E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11803120.07 | 31664383.31 |
August | 0.489542E+09 | 0.712775E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9243281.20 | 45893394.13 |
September | 0.472357E+09 | 0.686503E+09 | 0.102382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1154637.80 | 82249181.20 |
October | 0.487709E+09 | 0.710039E+09 | 0.105866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1117.64 | 0.163364E+09 |
November | 0.471555E+09 | 0.688829E+09 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199633E+09 |
December | 0.487480E+09 | 0.708397E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.321502E+09 |
Annual Sum or Average | 0.574883E+10 | 0.836625E+10 | 0.124712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 28788038.11 | 0.211767E+10 |
Minimum of Months | 0.440737E+09 | 0.641347E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31664383.31 |
Maximum of Months | 0.489771E+09 | 0.712775E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11803120.07 | 0.340380E+09 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.374985E+09 | 0.261454E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196306E+09 |
February | 0.339028E+09 | 0.236069E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183964E+09 |
March | 0.376747E+09 | 0.262260E+09 | 0.306128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 390340.84 | 0.147831E+09 |
April | 0.363528E+09 | 0.252589E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102907E+09 |
May | 0.375778E+09 | 0.261907E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 369667.96 | 62841317.24 |
June | 0.364321E+09 | 0.253748E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3304035.73 | 33998546.40 |
July | 0.374985E+09 | 0.260749E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7212243.66 | 16997768.16 |
August | 0.376571E+09 | 0.262360E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5689576.97 | 24921542.40 |
September | 0.363352E+09 | 0.252690E+09 | 0.295345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 761907.34 | 45319414.77 |
October | 0.375161E+09 | 0.261353E+09 | 0.305393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3710.46 | 91573611.27 |
November | 0.362735E+09 | 0.253546E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113505E+09 |
December | 0.374985E+09 | 0.260749E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185328E+09 |
Annual Sum or Average | 0.442217E+10 | 0.307947E+10 | 0.359760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17731482.96 | 0.120549E+10 |
Minimum of Months | 0.339028E+09 | 0.236069E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16997768.16 |
Maximum of Months | 0.376747E+09 | 0.262360E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7212243.66 | 0.196306E+09 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.337502E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.499895E+09 |
February | 0.139600E+10 | 0.304733E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.467162E+09 |
March | 0.155131E+10 | 0.338542E+09 | 0.578079E+10 | 0.502211E+11 | 0.00 | 0.00 | 0.00 | 618127.49 | 0.383212E+09 |
April | 0.149688E+10 | 0.326059E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273799E+09 |
May | 0.154732E+10 | 0.338087E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 683296.03 | 0.167114E+09 |
June | 0.150015E+10 | 0.327554E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 8172175.11 | 84453999.80 |
July | 0.154405E+10 | 0.336592E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 20288396.94 | 38883090.61 |
August | 0.155059E+10 | 0.338672E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 15843508.98 | 58202701.24 |
September | 0.149615E+10 | 0.326189E+09 | 0.557718E+10 | 0.484522E+11 | 0.00 | 0.00 | 0.00 | 2075829.09 | 0.114602E+09 |
October | 0.154478E+10 | 0.337372E+09 | 0.576693E+10 | 0.501006E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242608E+09 |
November | 0.149361E+10 | 0.327294E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.301497E+09 |
December | 0.154405E+10 | 0.336592E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.473700E+09 |
Annual Sum or Average | 0.182090E+11 | 0.397519E+10 | 0.679355E+11 | 0.590196E+12 | 0.00 | 0.00 | 0.00 | 47681333.65 | 0.310513E+10 |
Minimum of Months | 0.139600E+10 | 0.304733E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 38883090.61 |
Maximum of Months | 0.155131E+10 | 0.338672E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 20288396.94 | 0.499895E+09 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.136920E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.837169E+09 |
February | 0.236489E+11 | 0.118801E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.784287E+09 |
March | 0.262800E+11 | 0.122513E+10 | 0.122027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 624712.74 | 0.652035E+09 |
April | 0.253579E+11 | 0.108248E+10 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.465438E+09 |
May | 0.262123E+11 | 0.103308E+10 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 617703.92 | 0.287640E+09 |
June | 0.254132E+11 | 0.940428E+09 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12095863.18 | 0.152104E+09 |
July | 0.261570E+11 | 0.981787E+09 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28394223.67 | 74296017.96 |
August | 0.262677E+11 | 0.106036E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20857806.72 | 0.109214E+09 |
September | 0.253456E+11 | 0.115346E+10 | 0.117729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1851260.01 | 0.207722E+09 |
October | 0.261693E+11 | 0.129438E+10 | 0.121734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.414620E+09 |
November | 0.253025E+11 | 0.132139E+10 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.504130E+09 |
December | 0.261570E+11 | 0.137893E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.791437E+09 |
Annual Sum or Average | 0.308468E+12 | 0.140286E+11 | 0.143405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 64441570.25 | 0.528009E+10 |
Minimum of Months | 0.236489E+11 | 0.940428E+09 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74296017.96 |
Maximum of Months | 0.262800E+11 | 0.137893E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28394223.67 | 0.837169E+09 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.949005E+10 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243619E+10 |
February | 0.702046E+11 | 0.851817E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227968E+10 |
March | 0.780153E+11 | 0.938328E+10 | 0.126786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2849639.51 | 0.189906E+10 |
April | 0.752779E+11 | 0.895462E+10 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136786E+10 |
May | 0.778146E+11 | 0.921335E+10 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2646631.75 | 0.857427E+09 |
June | 0.754422E+11 | 0.886014E+10 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 35667980.37 | 0.457975E+09 |
July | 0.776503E+11 | 0.912206E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 84932870.24 | 0.227661E+09 |
August | 0.779788E+11 | 0.924239E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 64206639.76 | 0.329280E+09 |
September | 0.752414E+11 | 0.901875E+10 | 0.122320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 6102933.77 | 0.615173E+09 |
October | 0.776868E+11 | 0.941270E+10 | 0.126482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122812E+10 |
November | 0.751137E+11 | 0.919707E+10 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148894E+10 |
December | 0.776503E+11 | 0.948001E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230718E+10 |
Annual Sum or Average | 0.915726E+12 | 0.109893E+12 | 0.148998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196407E+09 | 0.154945E+11 |
Minimum of Months | 0.702046E+11 | 0.851817E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227661E+09 |
Maximum of Months | 0.780153E+11 | 0.949005E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 84932870.24 | 0.243619E+10 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196602E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213555E+09 |
February | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200555E+09 |
March | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 295713.18 | 0.163448E+09 |
April | 0.293479E+09 | 0.190486E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114846E+09 |
May | 0.303504E+09 | 0.195821E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 430179.76 | 66742238.12 |
June | 0.293842E+09 | 0.188975E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5264510.22 | 30663565.62 |
July | 0.303141E+09 | 0.197358E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12530154.49 | 10880697.81 |
August | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9310411.01 | 18540131.81 |
September | 0.293479E+09 | 0.190538E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1492093.28 | 43223877.60 |
October | 0.303322E+09 | 0.196576E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15233.45 | 99325009.28 |
November | 0.293661E+09 | 0.189731E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124669E+09 |
December | 0.303141E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201489E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231110E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29338295.41 | 0.128794E+10 |
Minimum of Months | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10880697.81 |
Maximum of Months | 0.303685E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12530154.49 | 0.213555E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196579E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212606E+09 |
February | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199555E+09 |
March | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 301466.74 | 0.161502E+09 |
April | 0.293479E+09 | 0.190464E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114050E+09 |
May | 0.303504E+09 | 0.195798E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 297950.21 | 69398788.67 |
June | 0.293842E+09 | 0.188953E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4422089.86 | 36955785.30 |
July | 0.303141E+09 | 0.197334E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11284871.52 | 15642755.97 |
August | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8406541.59 | 23359270.21 |
September | 0.293479E+09 | 0.190515E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1024559.11 | 46905148.17 |
October | 0.303322E+09 | 0.196553E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2031.02 | 98410103.67 |
November | 0.293661E+09 | 0.189708E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123104E+09 |
December | 0.303141E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200681E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231083E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25739510.05 | 0.130217E+10 |
Minimum of Months | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15642755.97 |
Maximum of Months | 0.303685E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11284871.52 | 0.212606E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.123557E+09 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52754617.91 |
February | 0.00 | 0.111584E+09 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49250605.45 |
March | 0.00 | 0.122575E+09 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54507167.74 |
April | 0.00 | 0.119713E+09 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42717989.60 |
May | 0.00 | 0.123066E+09 | 0.217879E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29994270.95 |
June | 0.00 | 0.118764E+09 | 0.210812E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 108122.16 | 18115942.82 |
July | 0.00 | 0.124032E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 427860.87 | 11091283.65 |
August | 0.00 | 0.122575E+09 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 345988.81 | 14168930.31 |
September | 0.00 | 0.119746E+09 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2870.42 | 22746639.52 |
October | 0.00 | 0.123541E+09 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39488335.80 |
November | 0.00 | 0.119238E+09 | 0.210867E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43744636.16 |
December | 0.00 | 0.124048E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50577615.08 |
Annual Sum or Average | 0.00 | 0.145244E+10 | 0.256575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 884842.27 | 0.429158E+09 |
Minimum of Months | 0.00 | 0.111584E+09 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11091283.65 |
Maximum of Months | 0.00 | 0.124048E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 427860.87 | 54507167.74 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.123591E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60086448.14 |
February | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56383292.53 |
March | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 92196.35 | 45518457.92 |
April | 0.293479E+09 | 0.119746E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31936853.09 |
May | 0.303504E+09 | 0.123099E+09 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 92536.13 | 18750473.58 |
June | 0.293842E+09 | 0.118796E+09 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1268701.45 | 9256079.15 |
July | 0.303141E+09 | 0.124066E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3209161.01 | 3841037.70 |
August | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2418766.54 | 5968062.99 |
September | 0.293479E+09 | 0.119778E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 321278.03 | 12455165.26 |
October | 0.303322E+09 | 0.123574E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2158.85 | 27687558.37 |
November | 0.293661E+09 | 0.119271E+09 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35009653.76 |
December | 0.303141E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56777015.32 |
Annual Sum or Average | 0.357224E+10 | 0.145283E+10 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7404798.36 | 0.363670E+09 |
Minimum of Months | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3841037.70 |
Maximum of Months | 0.303685E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3209161.01 | 60086448.14 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196602E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213667E+09 |
February | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200792E+09 |
March | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 294326.56 | 0.163976E+09 |
April | 0.293479E+09 | 0.190486E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115505E+09 |
May | 0.303504E+09 | 0.195821E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 431888.64 | 67087614.02 |
June | 0.293842E+09 | 0.188975E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5261214.82 | 30828721.33 |
July | 0.303141E+09 | 0.197358E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12526345.69 | 11011498.27 |
August | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9315271.47 | 18711851.51 |
September | 0.293479E+09 | 0.190538E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1494160.18 | 43422906.84 |
October | 0.303322E+09 | 0.196576E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15589.17 | 99805671.53 |
November | 0.293661E+09 | 0.189731E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124704E+09 |
December | 0.303141E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201443E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231110E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29338796.53 | 0.129096E+10 |
Minimum of Months | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11011498.27 |
Maximum of Months | 0.303685E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12526345.69 | 0.213667E+09 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196579E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212690E+09 |
February | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199692E+09 |
March | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 273127.91 | 0.161955E+09 |
April | 0.293479E+09 | 0.190464E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114952E+09 |
May | 0.303504E+09 | 0.195798E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 297753.16 | 68808059.70 |
June | 0.293842E+09 | 0.188953E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4414045.67 | 35176738.61 |
July | 0.303141E+09 | 0.197334E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11251992.74 | 15912046.88 |
August | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8375029.55 | 23340989.82 |
September | 0.293479E+09 | 0.190515E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1023634.68 | 46101747.64 |
October | 0.303322E+09 | 0.196553E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2186.36 | 98875884.81 |
November | 0.293661E+09 | 0.189708E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123127E+09 |
December | 0.303141E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200688E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231083E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25637770.08 | 0.130132E+10 |
Minimum of Months | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15912046.88 |
Maximum of Months | 0.303685E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11251992.74 | 0.212690E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.385223E+10 | 0.193865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262232E+09 |
February | 0.348285E+10 | 0.175042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245733E+09 |
March | 0.387034E+10 | 0.194462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 532840.50 | 0.197432E+09 |
April | 0.373454E+10 | 0.187292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138657E+09 |
May | 0.386038E+10 | 0.194201E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 428393.15 | 85015231.16 |
June | 0.374269E+10 | 0.188151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4274187.02 | 46100154.38 |
July | 0.385223E+10 | 0.193342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9540797.46 | 22693746.40 |
August | 0.386853E+10 | 0.194537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7368592.76 | 33106302.74 |
September | 0.373273E+10 | 0.187367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1006960.87 | 60586631.42 |
October | 0.385404E+10 | 0.193790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1569.38 | 0.120805E+09 |
November | 0.372639E+10 | 0.188002E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151114E+09 |
December | 0.385223E+10 | 0.193342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247585E+09 |
Annual Sum or Average | 0.454292E+11 | 0.228339E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23153341.14 | 0.161106E+10 |
Minimum of Months | 0.348285E+10 | 0.175042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22693746.40 |
Maximum of Months | 0.387034E+10 | 0.194537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9540797.46 | 0.262232E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196602E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213410E+09 |
February | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200401E+09 |
March | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 285969.64 | 0.163024E+09 |
April | 0.293479E+09 | 0.190486E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114875E+09 |
May | 0.303504E+09 | 0.195821E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 412942.84 | 67060249.83 |
June | 0.293842E+09 | 0.188975E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5134847.30 | 30943076.71 |
July | 0.303141E+09 | 0.197358E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12277148.57 | 11070972.03 |
August | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9113699.69 | 18755773.24 |
September | 0.293479E+09 | 0.190538E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1439774.61 | 43465490.66 |
October | 0.303322E+09 | 0.196576E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13378.16 | 99199775.87 |
November | 0.293661E+09 | 0.189731E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124262E+09 |
December | 0.303141E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201437E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231110E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28677760.81 | 0.128790E+10 |
Minimum of Months | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11070972.03 |
Maximum of Months | 0.303685E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12277148.57 | 0.213410E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196579E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212871E+09 |
February | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199719E+09 |
March | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 285671.09 | 0.161179E+09 |
April | 0.293479E+09 | 0.190464E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114067E+09 |
May | 0.303504E+09 | 0.195798E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 284739.08 | 70174823.18 |
June | 0.293842E+09 | 0.188953E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4322858.16 | 37960327.51 |
July | 0.303141E+09 | 0.197334E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11082094.30 | 16136572.04 |
August | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8246591.14 | 23845283.65 |
September | 0.293479E+09 | 0.190515E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 987055.94 | 47534078.33 |
October | 0.303322E+09 | 0.196553E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1855.95 | 98160629.34 |
November | 0.293661E+09 | 0.189708E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122606E+09 |
December | 0.303141E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200852E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231083E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25210865.67 | 0.130511E+10 |
Minimum of Months | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16136572.04 |
Maximum of Months | 0.303685E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11082094.30 | 0.212871E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.123591E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110911E+09 |
February | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103993E+09 |
March | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 144725.53 | 84899230.75 |
April | 0.293479E+09 | 0.119746E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59385859.43 |
May | 0.303504E+09 | 0.123099E+09 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 211746.58 | 34396173.63 |
June | 0.293842E+09 | 0.118796E+09 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2638341.82 | 15792115.56 |
July | 0.303141E+09 | 0.124066E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6293488.36 | 5652937.21 |
August | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4671180.08 | 9608223.08 |
September | 0.293479E+09 | 0.119778E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 734507.00 | 22401121.26 |
October | 0.303322E+09 | 0.123574E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6315.01 | 51708506.11 |
November | 0.293661E+09 | 0.119271E+09 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64937551.75 |
December | 0.303141E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104356E+09 |
Annual Sum or Average | 0.357224E+10 | 0.145283E+10 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14700304.39 | 0.668042E+09 |
Minimum of Months | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5652937.21 |
Maximum of Months | 0.303685E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6293488.36 | 0.110911E+09 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.280137E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.578843E+09 |
February | 0.415303E+11 | 0.246864E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.541083E+09 |
March | 0.461508E+11 | 0.265239E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 310231.02 | 0.450012E+09 |
April | 0.445315E+11 | 0.244620E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.328499E+09 |
May | 0.460320E+11 | 0.243398E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 220643.61 | 0.209036E+09 |
June | 0.446286E+11 | 0.228595E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5202585.64 | 0.111574E+09 |
July | 0.459349E+11 | 0.236914E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 14693653.83 | 56094849.79 |
August | 0.461292E+11 | 0.246697E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 11218101.68 | 79502790.13 |
September | 0.445099E+11 | 0.252318E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 897578.27 | 0.147481E+09 |
October | 0.459565E+11 | 0.272048E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292372E+09 |
November | 0.444343E+11 | 0.271307E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.356764E+09 |
December | 0.459349E+11 | 0.280838E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.549635E+09 |
Annual Sum or Average | 0.541708E+12 | 0.306898E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 32542794.05 | 0.370090E+10 |
Minimum of Months | 0.415303E+11 | 0.228595E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56094849.79 |
Maximum of Months | 0.461508E+11 | 0.280838E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 14693653.83 | 0.578843E+09 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.280137E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.584220E+09 |
February | 0.415303E+11 | 0.246864E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.545955E+09 |
March | 0.461508E+11 | 0.265239E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 257086.47 | 0.454011E+09 |
April | 0.445315E+11 | 0.244620E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.331224E+09 |
May | 0.460320E+11 | 0.243398E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 212216.32 | 0.210500E+09 |
June | 0.446286E+11 | 0.228595E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5121422.09 | 0.112149E+09 |
July | 0.459349E+11 | 0.236914E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 14568147.86 | 56289530.40 |
August | 0.461292E+11 | 0.246697E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 11095461.62 | 79905396.94 |
September | 0.445099E+11 | 0.252318E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 850400.43 | 0.148540E+09 |
October | 0.459565E+11 | 0.272048E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295148E+09 |
November | 0.444343E+11 | 0.271307E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.360443E+09 |
December | 0.459349E+11 | 0.280838E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.554783E+09 |
Annual Sum or Average | 0.541708E+12 | 0.306898E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 32104734.80 | 0.373317E+10 |
Minimum of Months | 0.415303E+11 | 0.228595E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56289530.40 |
Maximum of Months | 0.461508E+11 | 0.280838E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 14568147.86 | 0.584220E+09 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.110133E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.526815E+09 |
February | 0.369574E+10 | 0.994402E+09 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.491756E+09 |
March | 0.410691E+10 | 0.110473E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 209843.75 | 0.407366E+09 |
April | 0.396281E+10 | 0.106399E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295697E+09 |
May | 0.409635E+10 | 0.110324E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 191329.00 | 0.187355E+09 |
June | 0.397146E+10 | 0.106887E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 4576358.42 | 99639591.20 |
July | 0.408770E+10 | 0.109836E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 13027642.66 | 49888104.20 |
August | 0.410499E+10 | 0.110515E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 9887282.93 | 70970722.04 |
September | 0.396089E+10 | 0.106442E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 751310.09 | 0.132305E+09 |
October | 0.408962E+10 | 0.110091E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.264023E+09 |
November | 0.395417E+10 | 0.106802E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323274E+09 |
December | 0.408770E+10 | 0.109836E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.500131E+09 |
Annual Sum or Average | 0.482060E+11 | 0.129718E+11 | 0.392709E+12 | 0.359593E+12 | 0.00 | 0.00 | 0.00 | 28643766.84 | 0.334922E+10 |
Minimum of Months | 0.369574E+10 | 0.994402E+09 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 49888104.20 |
Maximum of Months | 0.410691E+10 | 0.110515E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 13027642.66 | 0.526815E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.407704E+10 | 0.205176E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.465223E+09 |
February | 0.368610E+10 | 0.185255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.435914E+09 |
March | 0.409620E+10 | 0.205809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 662589.24 | 0.350809E+09 |
April | 0.395248E+10 | 0.198220E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246884E+09 |
May | 0.408566E+10 | 0.205532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 461916.21 | 0.152561E+09 |
June | 0.396110E+10 | 0.199129E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5908034.94 | 82889002.51 |
July | 0.407704E+10 | 0.204623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13732375.82 | 41602968.22 |
August | 0.409429E+10 | 0.205888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10667389.44 | 59316142.88 |
September | 0.395056E+10 | 0.198299E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1229527.78 | 0.107118E+09 |
October | 0.407896E+10 | 0.205097E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215087E+09 |
November | 0.394385E+10 | 0.198971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268740E+09 |
December | 0.407704E+10 | 0.204623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.439306E+09 |
Annual Sum or Average | 0.480803E+11 | 0.241662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32661833.42 | 0.286545E+10 |
Minimum of Months | 0.368610E+10 | 0.185255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41602968.22 |
Maximum of Months | 0.409620E+10 | 0.205888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13732375.82 | 0.465223E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 13190.31 | 02-JAN-20:10 | 9632.53 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 13190.31 | 01-FEB-20:10 | 9632.53 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 13190.31 | 01-MAR-20:10 | 9632.53 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 13190.31 | 03-APR-19:10 | 9632.53 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 13190.31 | 01-MAY-19:10 | 9632.53 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 13190.31 | 01-JUN-19:10 | 9632.53 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 13190.31 | 03-JUL-19:10 | 9632.53 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 13190.31 | 01-AUG-19:10 | 9632.53 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 13190.31 | 01-SEP-19:10 | 9632.53 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 01-OCT-23:10 | 13190.31 | 02-OCT-19:10 | 9632.53 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 13190.31 | 01-NOV-19:10 | 9632.53 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 13190.31 | 01-DEC-20:10 | 9632.53 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 11501.89 | 13190.31 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 13190.31 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 597.59 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 207.35 | 31-JAN-02:00 |
February | 1169.53 | 01-FEB-00:10 | 597.59 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 227.33 | 07-FEB-07:00 |
March | 1169.53 | 01-MAR-00:10 | 597.59 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.96 | 15-MAR-17:00 | 207.82 | 07-MAR-05:50 |
April | 1169.53 | 01-APR-00:10 | 597.59 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 146.19 | 17-APR-06:00 |
May | 1169.53 | 01-MAY-00:10 | 597.59 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.07 | 10-MAY-15:00 | 107.61 | 01-MAY-05:50 |
June | 1169.53 | 01-JUN-00:10 | 597.59 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.23 | 27-JUN-13:00 | 78.73 | 10-JUN-05:00 |
July | 1169.53 | 01-JUL-00:10 | 597.59 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.72 | 21-JUL-14:00 | 52.75 | 03-JUL-04:10 |
August | 1169.53 | 01-AUG-00:10 | 597.59 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.26 | 10-AUG-14:00 | 58.12 | 01-AUG-06:00 |
September | 1169.53 | 01-SEP-00:10 | 597.59 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.34 | 16-SEP-13:00 | 82.53 | 05-SEP-06:00 |
October | 1169.53 | 01-OCT-23:10 | 597.59 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 136.77 | 17-OCT-06:00 |
November | 1169.53 | 01-NOV-00:10 | 597.59 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 142.23 | 24-NOV-06:00 |
December | 1169.53 | 01-DEC-00:10 | 597.59 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 243.62 | 11-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1169.53 | 597.59 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.75 | |||||
Maximum of Months | 1169.53 | 597.59 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 38.72 | 243.62 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 692.02 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 80.66 | 31-JAN-02:00 |
February | 1354.32 | 01-FEB-00:10 | 692.02 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 87.84 | 07-FEB-07:00 |
March | 1354.32 | 01-MAR-00:10 | 692.02 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.72 | 15-MAR-14:00 | 81.40 | 07-MAR-05:40 |
April | 1354.32 | 01-APR-00:10 | 692.02 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 58.20 | 17-APR-06:00 |
May | 1354.32 | 01-MAY-00:10 | 692.02 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.01 | 10-MAY-14:00 | 44.84 | 01-MAY-06:00 |
June | 1354.32 | 01-JUN-00:10 | 692.02 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.62 | 27-JUN-13:00 | 35.03 | 06-JUN-05:00 |
July | 1354.32 | 01-JUL-00:10 | 692.02 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.77 | 21-JUL-14:00 | 24.84 | 03-JUL-05:00 |
August | 1354.32 | 01-AUG-00:10 | 692.02 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.87 | 10-AUG-14:00 | 26.58 | 01-AUG-06:00 |
September | 1354.32 | 01-SEP-00:10 | 692.02 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.84 | 16-SEP-13:00 | 36.77 | 05-SEP-06:00 |
October | 1354.32 | 01-OCT-23:10 | 692.02 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 55.45 | 17-OCT-06:00 |
November | 1354.32 | 01-NOV-00:10 | 692.02 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 56.22 | 24-NOV-06:00 |
December | 1354.32 | 01-DEC-00:10 | 692.02 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 94.04 | 11-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1354.32 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.84 | |||||
Maximum of Months | 1354.32 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 15.77 | 94.04 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 286.42 | 02-JAN-00:10 | 684.18 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 189.15 | 31-JAN-02:00 |
February | 286.42 | 01-FEB-00:10 | 684.18 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 207.58 | 07-FEB-07:00 |
March | 286.42 | 01-MAR-00:10 | 684.18 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.69 | 15-MAR-14:00 | 189.57 | 07-MAR-06:00 |
April | 286.42 | 01-APR-00:10 | 684.18 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 133.37 | 17-APR-06:00 |
May | 286.42 | 01-MAY-00:10 | 684.18 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.69 | 10-MAY-14:00 | 101.98 | 01-MAY-06:00 |
June | 286.42 | 01-JUN-00:10 | 684.18 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.31 | 12-JUN-14:00 | 80.38 | 04-JUN-05:00 |
July | 286.42 | 01-JUL-00:10 | 684.18 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.04 | 21-JUL-14:00 | 56.98 | 13-JUL-04:40 |
August | 286.42 | 01-AUG-00:10 | 684.18 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.49 | 10-AUG-14:00 | 61.77 | 01-AUG-06:00 |
September | 286.42 | 01-SEP-00:10 | 684.18 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.40 | 16-SEP-13:00 | 83.73 | 05-SEP-06:00 |
October | 286.42 | 01-OCT-23:10 | 684.18 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.44 | 11-OCT-13:00 | 126.55 | 17-OCT-06:50 |
November | 286.42 | 01-NOV-00:10 | 684.18 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 129.73 | 24-NOV-06:00 |
December | 286.42 | 01-DEC-00:10 | 684.18 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 222.25 | 11-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 286.42 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.98 | |||||
Maximum of Months | 286.42 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 36.04 | 222.25 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 220.32 | 02-JAN-00:10 | 251.84 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 109.13 | 31-JAN-02:00 |
February | 220.32 | 01-FEB-00:10 | 251.84 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 119.77 | 07-FEB-07:00 |
March | 220.32 | 01-MAR-00:10 | 251.84 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.90 | 15-MAR-14:00 | 109.37 | 07-MAR-07:00 |
April | 220.32 | 01-APR-00:10 | 251.84 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 76.95 | 17-APR-06:00 |
May | 220.32 | 01-MAY-00:10 | 251.84 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.98 | 10-MAY-14:00 | 57.72 | 01-MAY-06:00 |
June | 220.32 | 01-JUN-00:10 | 251.84 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.96 | 12-JUN-14:00 | 45.35 | 14-JUN-05:00 |
July | 220.32 | 01-JUL-00:10 | 251.84 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.89 | 21-JUL-14:00 | 32.01 | 03-JUL-05:00 |
August | 220.32 | 01-AUG-00:10 | 251.84 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.95 | 10-AUG-14:00 | 34.60 | 01-AUG-06:00 |
September | 220.32 | 01-SEP-00:10 | 251.84 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.90 | 16-SEP-13:00 | 47.06 | 05-SEP-06:00 |
October | 220.32 | 01-OCT-23:10 | 251.84 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.61 | 11-OCT-13:00 | 71.98 | 17-OCT-06:50 |
November | 220.32 | 01-NOV-00:10 | 251.84 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 74.85 | 24-NOV-06:00 |
December | 220.32 | 01-DEC-00:10 | 251.84 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 128.23 | 11-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 220.32 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.01 | |||||
Maximum of Months | 220.32 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 20.89 | 128.23 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 325.08 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 276.22 | 04-JAN-08:00 |
February | 907.20 | 01-FEB-00:10 | 325.08 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 304.52 | 07-FEB-07:00 |
March | 907.20 | 01-MAR-00:10 | 325.08 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 19.58 | 15-MAR-14:00 | 281.20 | 07-MAR-07:00 |
April | 907.20 | 01-APR-00:10 | 325.08 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 203.45 | 17-APR-06:00 |
May | 907.20 | 01-MAY-00:10 | 325.08 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 25.03 | 14-MAY-15:20 | 154.79 | 01-MAY-06:00 |
June | 907.20 | 01-JUN-00:10 | 325.08 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 50.23 | 27-JUN-13:00 | 117.68 | 14-JUN-05:10 |
July | 907.20 | 01-JUL-00:10 | 325.08 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 57.34 | 16-JUL-16:00 | 81.37 | 03-JUL-05:10 |
August | 907.20 | 01-AUG-00:10 | 325.08 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 51.11 | 13-AUG-15:20 | 87.35 | 03-AUG-06:00 |
September | 907.20 | 01-SEP-00:10 | 325.08 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 29.51 | 16-SEP-13:00 | 123.46 | 05-SEP-06:00 |
October | 907.20 | 01-OCT-23:10 | 325.08 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 191.80 | 17-OCT-07:00 |
November | 907.20 | 01-NOV-00:10 | 325.08 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 195.06 | 24-NOV-06:20 |
December | 907.20 | 01-DEC-00:10 | 325.08 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 317.57 | 11-DEC-06:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 907.20 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 81.37 | ||||||
Maximum of Months | 907.20 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 57.34 | 317.57 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 1701.53 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 462.99 | 31-JAN-02:00 |
February | 15368.40 | 01-FEB-00:10 | 1701.53 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 503.08 | 07-FEB-07:00 |
March | 15368.40 | 01-MAR-00:10 | 1701.53 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.73 | 15-MAR-14:00 | 466.71 | 07-MAR-05:20 |
April | 15368.40 | 01-APR-00:10 | 1701.53 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 326.19 | 17-APR-05:00 |
May | 15368.40 | 01-MAY-00:10 | 1701.53 | 01-MAY-19:10 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.35 | 14-MAY-15:00 | 257.09 | 01-MAY-05:00 |
June | 15368.40 | 01-JUN-00:10 | 1701.53 | 01-JUN-19:30 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.61 | 27-JUN-13:00 | 200.05 | 10-JUN-05:00 |
July | 15368.40 | 01-JUL-00:10 | 1701.53 | 03-JUL-19:40 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.60 | 21-JUL-14:00 | 141.89 | 13-JUL-05:00 |
August | 15368.40 | 01-AUG-00:10 | 1701.53 | 01-AUG-19:30 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.53 | 10-AUG-14:00 | 151.76 | 01-AUG-05:00 |
September | 15368.40 | 01-SEP-00:10 | 1701.53 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.12 | 16-SEP-13:00 | 209.98 | 06-SEP-05:00 |
October | 15368.40 | 01-OCT-23:10 | 1701.53 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 317.17 | 17-OCT-04:30 |
November | 15368.40 | 01-NOV-00:10 | 1701.53 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 322.94 | 24-NOV-06:00 |
December | 15368.40 | 01-DEC-00:10 | 1701.53 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 538.57 | 11-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 15368.40 | 1701.53 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.89 | |||||
Maximum of Months | 15368.40 | 1701.53 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 85.60 | 538.57 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 9504.80 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1352.19 | 31-JAN-02:00 |
February | 45622.98 | 01-FEB-00:10 | 9504.80 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 1452.91 | 07-FEB-07:00 |
March | 45622.98 | 01-MAR-00:10 | 9504.80 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.17 | 15-MAR-14:00 | 1364.19 | 07-MAR-05:40 |
April | 45622.98 | 01-APR-00:10 | 9504.80 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 972.42 | 17-APR-06:00 |
May | 45622.98 | 01-MAY-00:10 | 9504.80 | 01-MAY-19:10 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 106.37 | 14-MAY-15:00 | 758.24 | 01-MAY-05:00 |
June | 45622.98 | 01-JUN-00:10 | 9504.80 | 01-JUN-19:30 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 237.15 | 27-JUN-13:00 | 591.86 | 06-JUN-05:00 |
July | 45622.98 | 01-JUL-00:10 | 9504.80 | 03-JUL-19:30 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 259.83 | 21-JUL-14:00 | 418.71 | 03-JUL-04:10 |
August | 45622.98 | 01-AUG-00:10 | 9504.80 | 01-AUG-19:19 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 224.50 | 10-AUG-14:00 | 443.04 | 03-AUG-04:10 |
September | 45622.98 | 01-SEP-00:10 | 9504.80 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.55 | 16-SEP-13:00 | 616.97 | 06-SEP-05:00 |
October | 45622.98 | 01-OCT-23:10 | 9504.80 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 935.30 | 17-OCT-04:40 |
November | 45622.98 | 01-NOV-00:10 | 9504.80 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 952.05 | 24-NOV-06:00 |
December | 45622.98 | 01-DEC-00:10 | 9504.80 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 1573.07 | 11-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 45622.98 | 9504.80 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 418.71 | |||||
Maximum of Months | 45622.98 | 9504.80 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 259.83 | 1573.07 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.88 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 120.88 | 31-JAN-02:00 |
February | 180.00 | 01-FEB-00:10 | 177.88 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 132.61 | 07-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 177.88 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.92 | 15-MAR-15:07 | 121.15 | 07-MAR-06:06 |
April | 180.00 | 01-APR-00:10 | 177.88 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 85.37 | 17-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 177.88 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 14-MAY-15:08 | 62.94 | 01-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 177.88 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.02 | 12-JUN-15:10 | 46.18 | 10-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 177.88 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.61 | 19-JUL-15:10 | 29.58 | 03-JUL-04:07 |
August | 180.00 | 01-AUG-00:10 | 177.88 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.69 | 13-AUG-15:10 | 31.74 | 03-AUG-05:10 |
September | 180.00 | 01-SEP-00:10 | 177.88 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.45 | 16-SEP-15:10 | 48.40 | 05-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 177.88 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.89 | 11-OCT-15:10 | 79.88 | 17-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 177.88 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 83.05 | 24-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 177.88 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 141.95 | 11-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.58 | |||||
Maximum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 28.61 | 141.95 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.86 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 120.87 | 31-JAN-02:00 |
February | 180.00 | 01-FEB-00:10 | 177.86 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 132.60 | 07-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 177.86 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.92 | 15-MAR-15:06 | 121.14 | 07-MAR-05:10 |
April | 180.00 | 01-APR-00:10 | 177.86 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 85.36 | 17-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 177.86 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 14-MAY-15:10 | 62.94 | 01-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 177.86 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.02 | 12-JUN-15:10 | 46.18 | 10-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 177.86 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.61 | 19-JUL-15:10 | 29.58 | 03-JUL-04:40 |
August | 180.00 | 01-AUG-00:10 | 177.86 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.69 | 13-AUG-15:10 | 31.73 | 03-AUG-04:07 |
September | 180.00 | 01-SEP-00:10 | 177.86 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.45 | 16-SEP-15:10 | 48.39 | 05-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 177.86 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.89 | 11-OCT-15:09 | 79.88 | 17-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 177.86 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 83.04 | 24-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 177.86 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 141.94 | 11-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.58 | |||||
Maximum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 28.61 | 141.94 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 111.79 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 28.88 | 30-JAN-19:00 |
February | 0.00 | 01-FEB-00:10 | 111.79 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 31.57 | 07-FEB-07:00 |
March | 0.00 | 01-MAR-00:10 | 111.79 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 35.05 | 07-MAR-07:00 |
April | 0.00 | 01-APR-00:10 | 111.79 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 26.42 | 03-APR-07:00 |
May | 0.00 | 01-MAY-00:10 | 111.79 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 22.11 | 01-MAY-06:00 |
June | 0.00 | 01-JUN-00:10 | 111.79 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27-JUN-13:00 | 17.58 | 06-JUN-05:20 |
July | 0.00 | 01-JUL-00:10 | 111.79 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.06 | 21-JUL-14:00 | 13.10 | 03-JUL-04:15 |
August | 0.00 | 01-AUG-00:10 | 111.79 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 10-AUG-14:00 | 13.75 | 03-AUG-05:30 |
September | 0.00 | 01-SEP-00:10 | 111.79 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.40 | 16-SEP-13:00 | 18.49 | 05-SEP-06:00 |
October | 0.00 | 01-OCT-00:10 | 111.79 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 26.61 | 17-OCT-07:00 |
November | 0.00 | 01-NOV-00:10 | 111.79 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 25.21 | 18-NOV-22:00 |
December | 0.00 | 01-DEC-00:10 | 111.79 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 34.15 | 11-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 0.00 | 111.79 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.10 | |||||
Maximum of Months | 0.00 | 111.79 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 4.06 | 35.05 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 111.82 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 33.74 | 31-JAN-02:00 |
February | 180.00 | 01-FEB-00:10 | 111.82 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 37.01 | 07-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 111.82 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.61 | 15-MAR-15:10 | 33.81 | 07-MAR-06:10 |
April | 180.00 | 01-APR-00:10 | 111.82 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 23.83 | 17-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 111.82 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.91 | 14-MAY-15:08 | 17.57 | 01-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 111.82 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.98 | 12-JUN-15:10 | 12.89 | 10-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 111.82 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.99 | 19-JUL-15:10 | 8.26 | 03-JUL-04:40 |
August | 180.00 | 01-AUG-00:10 | 111.82 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 13-AUG-15:10 | 8.86 | 03-AUG-05:10 |
September | 180.00 | 01-SEP-00:10 | 111.82 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.59 | 16-SEP-15:10 | 13.51 | 05-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 111.82 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.81 | 11-OCT-15:09 | 22.29 | 17-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 111.82 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 23.18 | 24-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 111.82 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 39.62 | 11-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.26 | |||||
Maximum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 7.99 | 39.62 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.88 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 120.88 | 31-JAN-02:00 |
February | 180.00 | 01-FEB-00:10 | 177.88 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 132.61 | 07-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 177.88 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.92 | 15-MAR-15:07 | 121.15 | 07-MAR-06:06 |
April | 180.00 | 01-APR-00:10 | 177.88 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 85.37 | 17-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 177.88 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 14-MAY-15:08 | 62.95 | 01-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 177.88 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.02 | 12-JUN-15:08 | 46.18 | 10-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 177.88 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.61 | 19-JUL-15:10 | 29.58 | 03-JUL-04:10 |
August | 180.00 | 01-AUG-00:10 | 177.88 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.69 | 13-AUG-15:10 | 33.11 | 31-AUG-07:20 |
September | 180.00 | 01-SEP-00:10 | 177.88 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.45 | 16-SEP-15:10 | 48.39 | 05-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 177.88 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.89 | 11-OCT-15:09 | 79.88 | 17-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 177.88 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 83.05 | 24-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 177.88 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 141.95 | 11-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.58 | |||||
Maximum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 28.61 | 141.95 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.86 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 120.87 | 31-JAN-02:00 |
February | 180.00 | 01-FEB-00:10 | 177.86 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 132.60 | 07-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 177.86 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.92 | 15-MAR-15:09 | 121.14 | 07-MAR-06:06 |
April | 180.00 | 01-APR-00:10 | 177.86 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 85.36 | 17-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 177.86 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 14-MAY-15:08 | 62.94 | 01-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 177.86 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.02 | 12-JUN-15:10 | 46.18 | 10-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 177.86 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.61 | 19-JUL-15:10 | 29.58 | 03-JUL-04:50 |
August | 180.00 | 01-AUG-00:10 | 177.86 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.69 | 13-AUG-15:08 | 33.11 | 31-AUG-07:20 |
September | 180.00 | 01-SEP-00:10 | 177.86 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.45 | 16-SEP-15:10 | 48.39 | 05-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 177.86 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.89 | 11-OCT-15:07 | 79.88 | 17-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 177.86 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 83.04 | 24-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 177.86 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 141.94 | 11-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.58 | |||||
Maximum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 28.61 | 141.94 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2263.36 | 02-JAN-00:10 | 1867.32 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 145.71 | 31-JAN-02:00 |
February | 2263.36 | 01-FEB-00:10 | 1867.32 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 159.89 | 07-FEB-07:00 |
March | 2263.36 | 01-MAR-00:10 | 1867.32 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.74 | 15-MAR-14:00 | 146.03 | 07-MAR-05:30 |
April | 2263.36 | 01-APR-00:10 | 1867.32 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 102.78 | 17-APR-06:00 |
May | 2263.36 | 01-MAY-00:10 | 1867.32 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.97 | 10-MAY-14:00 | 76.95 | 01-MAY-05:00 |
June | 2263.36 | 01-JUN-00:10 | 1867.32 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.33 | 12-JUN-14:00 | 61.24 | 14-JUN-05:00 |
July | 2263.36 | 01-JUL-00:10 | 1867.32 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.18 | 21-JUL-14:00 | 43.18 | 03-JUL-05:00 |
August | 2263.36 | 01-AUG-00:10 | 1867.32 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.84 | 10-AUG-14:00 | 46.17 | 02-AUG-06:00 |
September | 2263.36 | 01-SEP-00:10 | 1867.32 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.72 | 16-SEP-13:00 | 63.27 | 05-SEP-06:00 |
October | 2263.36 | 01-OCT-23:10 | 1867.32 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 | 11-OCT-13:00 | 96.15 | 17-OCT-06:50 |
November | 2263.36 | 01-NOV-00:10 | 1867.32 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 99.99 | 24-NOV-06:00 |
December | 2263.36 | 01-DEC-00:10 | 1867.32 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 171.18 | 11-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.18 | ||||
Maximum of Months | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.18 | 171.18 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.88 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 121.11 | 31-JAN-02:00 |
February | 180.00 | 01-FEB-00:10 | 177.88 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 132.85 | 07-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 177.88 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.74 | 15-MAR-15:10 | 121.39 | 07-MAR-05:10 |
April | 180.00 | 01-APR-00:10 | 177.88 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 85.58 | 17-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 177.88 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.83 | 14-MAY-15:10 | 63.15 | 01-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 177.88 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.85 | 12-JUN-15:10 | 46.38 | 10-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 177.88 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.44 | 19-JUL-15:10 | 29.77 | 03-JUL-04:07 |
August | 180.00 | 01-AUG-00:10 | 177.88 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.51 | 13-AUG-15:10 | 31.93 | 03-AUG-05:10 |
September | 180.00 | 01-SEP-00:10 | 177.88 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.28 | 16-SEP-15:10 | 48.60 | 05-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 177.88 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.71 | 11-OCT-15:10 | 80.10 | 17-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 177.88 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 83.27 | 24-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 177.88 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 142.19 | 11-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.77 | |||||
Maximum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 28.44 | 142.19 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.86 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 121.10 | 31-JAN-02:00 |
February | 180.00 | 01-FEB-00:10 | 177.86 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 132.84 | 07-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 177.86 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.74 | 15-MAR-15:07 | 121.38 | 07-MAR-06:06 |
April | 180.00 | 01-APR-00:10 | 177.86 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 85.58 | 17-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 177.86 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.82 | 14-MAY-15:08 | 63.15 | 01-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 177.86 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.84 | 12-JUN-15:10 | 46.38 | 10-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 177.86 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.44 | 19-JUL-15:10 | 29.77 | 03-JUL-04:30 |
August | 180.00 | 01-AUG-00:10 | 177.86 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.52 | 13-AUG-15:10 | 31.93 | 03-AUG-05:00 |
September | 180.00 | 01-SEP-00:10 | 177.86 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.27 | 16-SEP-15:10 | 48.59 | 05-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 177.86 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.71 | 11-OCT-15:09 | 80.09 | 17-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 177.86 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 83.26 | 24-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 177.86 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 142.18 | 11-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.77 | |||||
Maximum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 28.44 | 142.18 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 111.82 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 61.96 | 31-JAN-02:00 |
February | 180.00 | 01-FEB-00:10 | 111.82 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 67.97 | 07-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 111.82 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.52 | 15-MAR-15:09 | 62.11 | 07-MAR-06:10 |
April | 180.00 | 01-APR-00:10 | 111.82 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 43.79 | 17-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 111.82 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.07 | 14-MAY-15:10 | 32.31 | 01-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 111.82 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.71 | 12-JUN-15:10 | 23.73 | 10-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 111.82 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.55 | 19-JUL-15:10 | 15.23 | 03-JUL-04:10 |
August | 180.00 | 01-AUG-00:10 | 111.82 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.06 | 13-AUG-15:10 | 16.34 | 03-AUG-04:10 |
September | 180.00 | 01-SEP-00:10 | 111.82 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 16-SEP-15:10 | 24.86 | 05-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 111.82 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.20 | 11-OCT-15:10 | 40.98 | 17-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 111.82 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 42.60 | 24-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 111.82 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 72.75 | 11-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.23 | |||||
Maximum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 14.55 | 72.75 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2988.03 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 317.56 | 31-JAN-02:00 |
February | 26988.77 | 01-FEB-00:10 | 2988.03 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 343.30 | 07-FEB-07:00 |
March | 26988.77 | 01-MAR-00:10 | 2988.03 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.78 | 15-MAR-14:00 | 318.54 | 07-MAR-05:30 |
April | 26988.77 | 01-APR-00:10 | 2988.03 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 232.51 | 17-APR-06:00 |
May | 26988.77 | 01-MAY-00:10 | 2988.03 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.75 | 14-MAY-15:00 | 177.01 | 01-MAY-05:10 |
June | 26988.77 | 01-JUN-00:10 | 2988.03 | 01-JUN-19:40 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.39 | 27-JUN-13:00 | 135.76 | 10-JUN-05:00 |
July | 26988.77 | 01-JUL-00:10 | 2988.03 | 03-JUL-19:40 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.16 | 21-JUL-14:00 | 94.74 | 03-JUL-04:10 |
August | 26988.77 | 01-AUG-00:10 | 2988.03 | 01-AUG-19:30 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.42 | 10-AUG-14:00 | 100.21 | 03-AUG-05:10 |
September | 26988.77 | 01-SEP-00:10 | 2988.03 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.43 | 16-SEP-13:00 | 141.31 | 05-SEP-06:00 |
October | 26988.77 | 01-OCT-23:10 | 2988.03 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 219.06 | 17-OCT-06:00 |
November | 26988.77 | 01-NOV-00:10 | 2988.03 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 226.65 | 24-NOV-06:00 |
December | 26988.77 | 01-DEC-00:10 | 2988.03 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 367.38 | 11-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.74 | |||||
Maximum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 54.16 | 367.38 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2988.03 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 319.70 | 31-JAN-02:00 |
February | 26988.77 | 01-FEB-00:10 | 2988.03 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 345.73 | 07-FEB-07:00 |
March | 26988.77 | 01-MAR-00:10 | 2988.03 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.48 | 15-MAR-14:00 | 320.49 | 07-MAR-06:00 |
April | 26988.77 | 01-APR-00:10 | 2988.03 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 232.52 | 17-APR-06:00 |
May | 26988.77 | 01-MAY-00:10 | 2988.03 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.33 | 14-MAY-15:00 | 177.01 | 01-MAY-05:10 |
June | 26988.77 | 01-JUN-00:10 | 2988.03 | 01-JUN-19:40 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.39 | 27-JUN-13:00 | 135.76 | 10-JUN-05:00 |
July | 26988.77 | 01-JUL-00:10 | 2988.03 | 03-JUL-19:40 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.16 | 21-JUL-14:00 | 94.74 | 03-JUL-04:10 |
August | 26988.77 | 01-AUG-00:10 | 2988.03 | 01-AUG-19:30 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.42 | 10-AUG-14:00 | 100.21 | 03-AUG-05:10 |
September | 26988.77 | 01-SEP-00:10 | 2988.03 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.43 | 16-SEP-13:00 | 141.31 | 05-SEP-06:00 |
October | 26988.77 | 01-OCT-23:10 | 2988.03 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 219.07 | 17-OCT-06:00 |
November | 26988.77 | 01-NOV-00:10 | 2988.03 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 226.66 | 24-NOV-06:00 |
December | 26988.77 | 01-DEC-00:10 | 2988.03 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 369.35 | 11-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.74 | |||||
Maximum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 54.16 | 369.35 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 1060.81 | 02-JAN-20:10 | 14912.86 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 282.10 | 04-JAN-08:00 |
February | 2401.70 | 01-FEB-00:10 | 1060.81 | 01-FEB-20:10 | 14912.86 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 312.45 | 07-FEB-07:00 |
March | 2401.70 | 01-MAR-00:10 | 1060.81 | 01-MAR-20:10 | 14912.86 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 13.02 | 15-MAR-14:00 | 287.53 | 07-MAR-06:10 |
April | 2401.70 | 01-APR-00:10 | 1060.81 | 03-APR-19:10 | 14912.86 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 208.12 | 17-APR-06:00 |
May | 2401.70 | 01-MAY-00:10 | 1060.81 | 01-MAY-19:10 | 14912.86 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 12.89 | 14-MAY-15:00 | 158.45 | 01-MAY-05:10 |
June | 2401.70 | 01-JUN-00:10 | 1060.81 | 01-JUN-19:10 | 14912.86 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 41.59 | 27-JUN-13:00 | 121.07 | 06-JUN-04:10 |
July | 2401.70 | 01-JUL-00:10 | 1060.81 | 03-JUL-19:10 | 14912.86 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 48.54 | 21-JUL-14:00 | 84.79 | 03-JUL-05:00 |
August | 2401.70 | 01-AUG-00:10 | 1060.81 | 01-AUG-19:10 | 14912.86 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 41.61 | 10-AUG-14:00 | 89.70 | 03-AUG-05:07 |
September | 2401.70 | 01-SEP-00:10 | 1060.81 | 01-SEP-19:10 | 14912.86 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 20.14 | 16-SEP-13:00 | 126.47 | 05-SEP-06:00 |
October | 2401.70 | 01-OCT-23:10 | 1060.81 | 02-OCT-19:10 | 14912.86 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 196.09 | 17-OCT-06:10 |
November | 2401.70 | 01-NOV-00:10 | 1060.81 | 01-NOV-19:10 | 14912.86 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 202.90 | 24-NOV-06:00 |
December | 2401.70 | 01-DEC-00:10 | 1060.81 | 01-DEC-20:10 | 14912.86 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 326.25 | 11-DEC-06:20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2401.70 | 1060.81 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 0.00 | 84.79 | ||||||
Maximum of Months | 2401.70 | 1060.81 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 48.54 | 326.25 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2395.44 | 02-JAN-00:10 | 1976.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 258.30 | 31-JAN-02:00 |
February | 2395.44 | 01-FEB-00:10 | 1976.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 283.42 | 07-FEB-07:00 |
March | 2395.44 | 01-MAR-00:10 | 1976.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.71 | 15-MAR-14:00 | 258.89 | 07-MAR-05:40 |
April | 2395.44 | 01-APR-00:10 | 1976.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 182.32 | 17-APR-06:00 |
May | 2395.44 | 01-MAY-00:10 | 1976.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.95 | 10-MAY-15:00 | 134.35 | 01-MAY-06:00 |
June | 2395.44 | 01-JUN-00:10 | 1976.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.43 | 12-JUN-14:00 | 105.00 | 06-JUN-04:03 |
July | 2395.44 | 01-JUL-00:10 | 1976.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.45 | 21-JUL-14:00 | 74.33 | 06-JUL-05:00 |
August | 2395.44 | 01-AUG-00:10 | 1976.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.67 | 10-AUG-14:00 | 80.35 | 01-AUG-05:00 |
September | 2395.44 | 01-SEP-00:10 | 1976.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.90 | 16-SEP-13:00 | 108.52 | 05-SEP-06:00 |
October | 2395.44 | 01-OCT-23:10 | 1976.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 170.59 | 17-OCT-06:20 |
November | 2395.44 | 01-NOV-00:10 | 1976.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 177.37 | 24-NOV-06:00 |
December | 2395.44 | 01-DEC-00:10 | 1976.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 303.38 | 11-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.33 | ||||
Maximum of Months | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.45 | 303.38 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 13869.10 | 11-JAN-21:00 | 8945.92 | 13190.31 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 13581.82 | 01-FEB-21:00 | 8945.92 | 13190.31 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 13327.84 | 15-MAR-18:10 | 62621.41 | 82072.63 | 63878.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 13444.45 | 22-APR-10:33 | 11501.89 | 10992.10 | 10646.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 13675.77 | 27-MAY-10:33 | 11501.89 | 10992.10 | 10646.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 14785.65 | 25-JUN-10:33 | 11501.89 | 13190.31 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 15510.89 | 16-JUL-10:33 | 11501.89 | 13190.31 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17063.17 | 31-AUG-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 19777.69 | 22-SEP-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 21095.96 | 13-OCT-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 20786.55 | 01-NOV-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 18946.67 | 01-DEC-22:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 13327.84 | 8945.92 | 10992.10 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21095.96 | 62621.41 | 82072.63 | 63878.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1953.67 | 15-JAN-11:50 | 389.84 | 199.20 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.01 |
February | 1983.27 | 28-FEB-11:50 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.24 |
March | 2935.71 | 15-MAR-13:30 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 7.93 | 0.00 |
April | 2404.44 | 22-APR-13:10 | 779.69 | 332.00 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.84 |
May | 2190.58 | 27-MAY-10:33 | 1169.53 | 497.99 | 757.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.91 |
June | 2519.10 | 27-JUN-13:10 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 30.43 | 0.00 |
July | 3088.80 | 21-JUL-13:30 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 36.02 | 0.00 |
August | 3426.55 | 18-AUG-13:30 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 28.84 | 0.00 |
September | 4188.87 | 21-SEP-13:00 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 5.16 | 0.00 |
October | 4097.46 | 11-OCT-12:30 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 |
November | 2445.04 | 03-NOV-12:30 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.97 |
December | 2116.31 | 17-DEC-11:50 | 779.69 | 398.40 | 577.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.69 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1953.67 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4188.87 | 1169.53 | 497.99 | 757.77 | 0.00 | 0.00 | 0.00 | 0.00 | 36.02 | 136.24 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1080.72 | 17-JAN-21:00 | 1053.36 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.27 |
February | 1091.94 | 22-FEB-21:00 | 1053.36 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.80 |
March | 1366.62 | 15-MAR-18:10 | 7373.52 | 4305.87 | 5265.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 | 0.00 |
April | 1296.65 | 21-APR-20:00 | 1053.36 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.23 |
May | 1413.01 | 23-MAY-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.85 |
June | 1826.54 | 27-JUN-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.60 |
July | 1954.20 | 19-JUL-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 0.00 |
August | 1984.33 | 10-AUG-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 4.14 | 0.00 |
September | 1836.10 | 21-SEP-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.63 |
October | 1532.95 | 11-OCT-21:00 | 2407.68 | 1230.25 | 1504.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.13 |
November | 1245.92 | 01-NOV-20:00 | 1053.36 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.77 |
December | 1104.50 | 01-DEC-21:00 | 1053.36 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.23 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1080.72 | 1053.36 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1984.33 | 7373.52 | 4305.87 | 5265.02 | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 38.27 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 739.44 | 17-JAN-21:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.55 |
February | 727.39 | 22-FEB-21:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.70 |
March | 979.66 | 15-MAR-18:10 | 1559.38 | 4257.10 | 5566.86 | 0.00 | 0.00 | 0.00 | 0.00 | 4.75 | 0.00 |
April | 954.71 | 09-APR-10:33 | 286.42 | 684.18 | 1060.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.80 |
May | 1053.51 | 27-MAY-10:33 | 286.42 | 570.15 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.79 |
June | 1199.23 | 27-JUN-21:00 | 254.59 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.52 |
July | 1639.97 | 21-JUL-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.32 |
August | 1395.89 | 10-AUG-21:00 | 254.59 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 9.79 | 0.00 |
September | 1160.89 | 16-SEP-10:33 | 286.42 | 570.15 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 10.05 | 0.00 |
October | 976.60 | 11-OCT-10:33 | 190.94 | 570.15 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.63 |
November | 904.94 | 05-NOV-10:33 | 286.42 | 684.18 | 1060.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.88 |
December | 765.93 | 01-DEC-21:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.41 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 727.39 | 190.94 | 570.15 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1639.97 | 1559.38 | 4257.10 | 5566.86 | 0.00 | 0.00 | 0.00 | 0.00 | 10.05 | 85.55 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 388.06 | 17-JAN-22:00 | 195.84 | 223.85 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.29 |
February | 362.72 | 22-FEB-22:00 | 195.84 | 223.85 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.28 |
March | 565.07 | 15-MAR-18:10 | 1199.52 | 1566.97 | 1605.89 | 0.00 | 0.00 | 0.00 | 0.00 | 3.49 | 0.00 |
April | 555.09 | 09-APR-10:33 | 220.32 | 251.83 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.51 |
May | 613.76 | 27-MAY-10:33 | 220.32 | 209.86 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.38 |
June | 690.38 | 29-JUN-10:33 | 146.88 | 209.86 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 4.15 | 0.00 |
July | 731.11 | 21-JUL-10:33 | 146.88 | 209.86 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 14.45 | 0.00 |
August | 705.66 | 10-AUG-10:33 | 146.88 | 209.86 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 14.12 | 0.00 |
September | 679.56 | 16-SEP-10:33 | 220.32 | 209.86 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 6.28 | 0.00 |
October | 568.95 | 22-OCT-10:33 | 220.32 | 251.83 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.68 |
November | 523.93 | 05-NOV-10:33 | 220.32 | 251.83 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.13 |
December | 421.42 | 01-DEC-21:00 | 171.36 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.60 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 362.72 | 146.88 | 209.86 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 731.11 | 1199.52 | 1566.97 | 1605.89 | 0.00 | 0.00 | 0.00 | 0.00 | 14.45 | 48.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 36435.72 | 17-JAN-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 134.80 |
February | 36470.25 | 22-FEB-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 96.94 |
March | 38005.68 | 15-MAR-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 18.80 |
April | 37594.26 | 07-APR-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 44.76 |
May | 38022.85 | 23-MAY-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 18.83 |
June | 38464.13 | 27-JUN-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 |
July | 38699.06 | 21-JUL-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 4.54 |
August | 38625.31 | 10-AUG-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 10.20 | 0.00 |
September | 38250.78 | 15-SEP-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 11.70 |
October | 37889.13 | 11-OCT-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 51.90 |
November | 37188.50 | 16-NOV-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 105.54 |
December | 36635.56 | 01-DEC-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 120.74 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 36435.72 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 38699.06 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 10.20 | 134.80 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8907.55 | 15-JAN-13:00 | 5122.80 | 124.78 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 241.78 |
February | 8561.04 | 28-FEB-13:30 | 3415.20 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 297.88 |
March | 11019.46 | 15-MAR-13:30 | 3415.20 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 17.54 | 0.00 |
April | 10439.72 | 22-APR-13:00 | 5122.80 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.59 |
May | 9621.28 | 27-MAY-10:33 | 15368.40 | 311.95 | 1066.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.26 |
June | 10534.10 | 27-JUN-21:10 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.57 |
July | 11373.94 | 20-JUL-21:10 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 17.06 | 0.00 |
August | 12142.27 | 17-AUG-15:03 | 51228.00 | 623.89 | 2133.76 | 0.00 | 0.00 | 0.00 | 0.00 | 55.11 | 0.00 |
September | 14362.65 | 21-SEP-15:03 | 59766.00 | 727.88 | 2489.39 | 0.00 | 0.00 | 0.00 | 0.00 | 23.85 | 0.00 |
October | 14466.48 | 11-OCT-12:30 | 3415.20 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.58 |
November | 9927.13 | 03-NOV-12:30 | 3415.20 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.82 |
December | 9406.99 | 17-DEC-11:33 | 15368.40 | 374.34 | 1219.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 277.11 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8561.04 | 3415.20 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14466.48 | 59766.00 | 1134.35 | 2489.39 | 0.00 | 0.00 | 0.00 | 0.00 | 55.11 | 297.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 24734.29 | 15-JAN-11:33 | 45622.98 | 8174.13 | 12668.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 650.25 |
February | 24972.56 | 22-FEB-21:00 | 35484.54 | 9504.80 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 453.94 |
March | 32972.00 | 15-MAR-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.18 |
April | 29199.69 | 23-APR-10:33 | 45622.98 | 8174.13 | 12668.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 263.19 |
May | 32868.41 | 23-MAY-21:52 | 410606.82 | 57028.80 | 66509.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.93 |
June | 37470.31 | 27-JUN-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.69 |
July | 39829.44 | 20-JUL-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 48.67 | 0.00 |
August | 39758.96 | 10-AUG-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 65.15 | 0.00 |
September | 38232.30 | 21-SEP-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.60 |
October | 35018.66 | 11-OCT-21:10 | 91245.96 | 12673.07 | 14779.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 280.22 |
November | 28045.69 | 01-NOV-21:20 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 677.64 |
December | 25716.47 | 17-DEC-11:33 | 45622.98 | 8174.13 | 12668.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 748.28 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 24734.29 | 35484.54 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 39829.44 | 410606.82 | 57028.80 | 66509.49 | 0.00 | 0.00 | 0.00 | 0.00 | 65.15 | 748.28 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2766.40 | 15-JAN-16:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.18 |
February | 3710.27 | 28-FEB-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.09 |
March | 3738.08 | 08-MAR-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.10 |
April | 3748.32 | 19-APR-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.00 |
May | 3839.61 | 03-MAY-18:01 | 1386.00 | 1583.15 | 1211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.18 |
June | 3786.09 | 15-JUN-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.28 |
July | 3414.74 | 21-JUL-08:61 | 252.00 | 547.88 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 12.94 | 0.00 |
August | 3381.85 | 18-AUG-08:61 | 252.00 | 547.88 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.61 | 0.00 |
September | 3391.25 | 08-SEP-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.38 |
October | 3279.15 | 04-OCT-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.92 |
November | 3052.10 | 14-NOV-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.41 |
December | 3073.56 | 04-DEC-16:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.26 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2766.40 | 252.00 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3839.61 | 1386.00 | 1583.15 | 1211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 12.94 | 72.26 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 899.49 | 15-JAN-16:01 | 378.00 | 410.86 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.85 |
February | 2308.11 | 28-FEB-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.51 |
March | 3527.70 | 28-MAR-18:01 | 970.20 | 1108.08 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.73 |
April | 4117.41 | 19-APR-18:11 | 1386.00 | 1582.97 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.93 |
May | 4200.03 | 03-MAY-18:01 | 1386.00 | 1582.97 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.18 |
June | 3621.09 | 24-JUN-21:51 | 1386.00 | 1511.82 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.30 |
July | 3705.21 | 06-JUL-21:51 | 1800.00 | 1191.67 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.84 |
August | 3758.06 | 02-AUG-21:51 | 1800.00 | 1191.67 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.39 |
September | 3428.25 | 11-SEP-19:31 | 1386.00 | 1778.61 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.28 |
October | 3270.56 | 22-OCT-15:01 | 378.00 | 410.86 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.46 |
November | 2793.45 | 14-NOV-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.20 |
December | 585.43 | 01-DEC-19:05 | 831.60 | 949.78 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.58 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 585.43 | 378.00 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.46 | |
Maximum of Months | 4200.03 | 1800.00 | 1778.61 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.51 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 95.70 | 15-JAN-15:20 | 0.00 | 36.89 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.70 |
February | 79.59 | 28-FEB-15:20 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.43 |
March | 489.92 | 15-MAR-13:30 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.97 |
April | 401.98 | 22-APR-13:00 | 0.00 | 36.89 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.58 |
May | 364.12 | 14-MAY-13:40 | 0.00 | 36.89 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.72 |
June | 412.07 | 12-JUN-13:10 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 2.36 | 0.00 |
July | 469.31 | 21-JUL-13:30 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 3.62 | 0.00 |
August | 539.06 | 18-AUG-13:30 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 2.45 | 0.00 |
September | 680.50 | 21-SEP-13:00 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.43 |
October | 698.53 | 11-OCT-12:30 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.01 |
November | 403.52 | 03-NOV-12:30 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.14 |
December | 111.30 | 04-DEC-15:20 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 79.59 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 698.53 | 0.00 | 36.89 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 3.62 | 22.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 783.65 | 15-JAN-09:02 | 324.00 | 375.72 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.64 |
February | 805.62 | 19-FEB-09:02 | 324.00 | 375.72 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.17 |
March | 1070.20 | 15-MAR-15:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 2.18 | 0.00 |
April | 1129.78 | 22-APR-18:01 | 819.00 | 782.76 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.69 |
May | 1188.04 | 27-MAY-21:41 | 1386.00 | 950.49 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.51 |
June | 1239.79 | 03-JUN-20:41 | 1386.00 | 1118.23 | 1780.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.89 |
July | 1103.50 | 01-JUL-21:51 | 1386.00 | 950.49 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.25 |
August | 1120.82 | 01-AUG-21:51 | 1800.00 | 749.21 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.12 |
September | 1078.41 | 12-SEP-15:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.12 |
October | 1052.96 | 25-OCT-15:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.63 |
November | 998.19 | 05-NOV-15:01 | 378.00 | 258.31 | 379.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.80 |
December | 964.56 | 03-DEC-09:02 | 324.00 | 375.72 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.99 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 783.65 | 324.00 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1239.79 | 1800.00 | 1118.23 | 1780.62 | 0.00 | 0.00 | 0.00 | 0.00 | 2.18 | 18.64 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1320.55 | 15-JAN-16:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.88 |
February | 3176.34 | 28-FEB-09:02 | 216.00 | 469.61 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.74 |
March | 3317.91 | 01-MAR-09:02 | 216.00 | 469.61 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.67 |
April | 3417.42 | 22-APR-18:01 | 819.00 | 1245.18 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.12 |
May | 3466.73 | 27-MAY-18:01 | 819.00 | 1245.18 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.03 |
June | 3443.15 | 03-JUN-18:01 | 819.00 | 1245.18 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.90 |
July | 3246.48 | 31-JUL-08:61 | 252.00 | 547.88 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.39 |
August | 3157.46 | 16-AUG-08:62 | 216.00 | 469.61 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.90 |
September | 3139.79 | 16-SEP-08:61 | 378.00 | 697.30 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.81 | 0.00 |
October | 3105.79 | 12-OCT-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.59 |
November | 2846.77 | 06-NOV-09:01 | 252.00 | 547.88 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.19 |
December | 565.61 | 16-DEC-09:03 | 324.00 | 597.68 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.67 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 565.61 | 216.00 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3466.73 | 819.00 | 1245.18 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.81 | 95.74 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 534.57 | 17-JAN-19:05 | 831.60 | 949.78 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.43 |
February | 1501.52 | 28-FEB-09:02 | 216.00 | 469.55 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.13 |
March | 3084.90 | 22-MAR-15:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.96 |
April | 3319.92 | 22-APR-18:01 | 819.00 | 1245.03 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.13 |
May | 3383.35 | 21-MAY-19:41 | 936.00 | 1422.89 | 1306.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.51 |
June | 3709.37 | 30-JUN-08:32 | 216.00 | 469.55 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.39 |
July | 3641.10 | 10-JUL-08:51 | 360.00 | 782.59 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.03 |
August | 3804.72 | 05-AUG-08:32 | 324.00 | 597.61 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.97 |
September | 3410.55 | 09-SEP-08:51 | 540.00 | 996.02 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.66 |
October | 2989.68 | 11-OCT-08:62 | 216.00 | 469.55 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.48 |
November | 2683.96 | 06-NOV-09:01 | 252.00 | 547.81 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.49 |
December | 511.79 | 01-DEC-19:05 | 831.60 | 949.78 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.58 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 511.79 | 216.00 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.97 | |
Maximum of Months | 3804.72 | 936.00 | 1422.89 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.13 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1367.64 | 17-JAN-22:00 | 2011.87 | 1659.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.56 |
February | 1506.80 | 22-FEB-21:00 | 1760.39 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.55 |
March | 1995.27 | 15-MAR-18:10 | 12322.72 | 11618.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.29 | 0.00 |
April | 2046.58 | 23-APR-10:33 | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.57 |
May | 2253.71 | 27-MAY-10:33 | 2263.36 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.44 |
June | 2496.91 | 29-JUN-10:33 | 1508.90 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.45 | 0.00 |
July | 2588.45 | 21-JUL-10:33 | 1508.90 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.00 | 0.00 |
August | 2560.81 | 19-AUG-10:33 | 2263.36 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.39 |
September | 2403.32 | 16-SEP-10:33 | 2263.36 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.10 | 0.00 |
October | 2055.67 | 11-OCT-10:33 | 1508.90 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.15 |
November | 1785.44 | 05-NOV-10:33 | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.65 |
December | 1437.42 | 01-DEC-22:00 | 2011.87 | 1659.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.79 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 1367.64 | 1508.90 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2588.45 | 12322.72 | 11618.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.00 | 64.56 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2906.00 | 15-JAN-16:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.22 |
February | 3840.65 | 28-FEB-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.10 |
March | 3881.93 | 08-MAR-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.20 |
April | 3904.67 | 19-APR-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.20 |
May | 3995.27 | 03-MAY-18:01 | 1386.00 | 1583.15 | 1211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.34 |
June | 3931.30 | 15-JUN-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.38 |
July | 3481.73 | 26-JUL-18:02 | 831.60 | 949.89 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 1.97 | 0.00 |
August | 3459.61 | 27-AUG-18:02 | 702.00 | 1067.29 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.85 |
September | 3547.74 | 08-SEP-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.51 |
October | 3366.33 | 02-OCT-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.19 |
November | 3185.11 | 14-NOV-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.32 |
December | 2447.23 | 16-DEC-16:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.82 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2447.23 | 378.00 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3995.27 | 1386.00 | 1583.15 | 1211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1.97 | 71.10 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 559.04 | 15-JAN-16:03 | 378.00 | 410.86 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.03 |
February | 623.43 | 22-FEB-16:03 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.01 |
March | 3678.24 | 28-MAR-18:01 | 970.20 | 1108.08 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.13 |
April | 4408.04 | 19-APR-18:11 | 1386.00 | 1582.97 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.73 |
May | 4419.43 | 03-MAY-18:01 | 1386.00 | 1582.97 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.08 |
June | 3902.39 | 24-JUN-21:51 | 1386.00 | 1511.82 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.48 |
July | 3971.13 | 06-JUL-21:51 | 1800.00 | 1191.67 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.86 |
August | 3981.67 | 02-AUG-21:51 | 1800.00 | 1191.67 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.65 |
September | 3691.53 | 04-SEP-19:11 | 1170.00 | 1778.61 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.20 |
October | 3401.13 | 22-OCT-15:01 | 378.00 | 410.86 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.56 |
November | 2558.21 | 15-NOV-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.74 |
December | 537.33 | 16-DEC-16:04 | 378.00 | 410.86 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.61 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 537.33 | 378.00 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.56 | |
Maximum of Months | 4419.43 | 1800.00 | 1778.61 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.61 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2084.62 | 12-JAN-16:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.43 |
February | 2096.10 | 28-FEB-16:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.82 |
March | 2109.23 | 08-MAR-16:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.55 |
April | 2075.99 | 22-APR-18:01 | 819.00 | 782.76 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.10 |
May | 2122.76 | 03-MAY-18:01 | 1386.00 | 995.22 | 1187.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.47 |
June | 2077.57 | 03-JUN-18:01 | 819.00 | 782.76 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.18 |
July | 1912.99 | 05-JUL-15:02 | 583.20 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 | 0.00 |
August | 1899.58 | 18-AUG-08:61 | 252.00 | 344.41 | 776.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.22 | 0.00 |
September | 2080.63 | 02-SEP-18:01 | 819.00 | 782.76 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.91 |
October | 1837.47 | 04-OCT-15:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.45 |
November | 1817.15 | 16-NOV-16:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.71 |
December | 2061.16 | 11-DEC-16:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.39 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1817.15 | 252.00 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2122.76 | 1386.00 | 995.22 | 1187.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 | 55.39 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 16886.77 | 17-JAN-23:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.15 |
February | 16905.09 | 22-FEB-23:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.85 |
March | 20595.20 | 15-MAR-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.40 |
April | 19657.03 | 07-APR-21:54 | 134943.84 | 9960.10 | 33739.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.78 |
May | 21093.59 | 23-MAY-21:52 | 242898.91 | 17928.18 | 60731.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.87 |
June | 22256.92 | 27-JUN-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.20 |
July | 22921.78 | 20-JUL-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 9.47 | 0.00 |
August | 22634.71 | 10-AUG-22:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 10.90 | 0.00 |
September | 21513.74 | 15-SEP-21:53 | 188921.38 | 13944.14 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.22 |
October | 19921.57 | 12-OCT-21:44 | 134943.84 | 9960.10 | 33739.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.54 |
November | 18230.68 | 16-NOV-23:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.11 |
December | 17208.10 | 01-DEC-23:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.23 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 16886.77 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22921.78 | 242898.91 | 17928.18 | 60731.12 | 0.00 | 0.00 | 0.00 | 0.00 | 10.90 | 154.15 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18937.74 | 17-JAN-23:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.16 |
February | 18952.97 | 22-FEB-23:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.85 |
March | 22273.99 | 15-MAR-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.40 |
April | 21457.99 | 07-APR-21:10 | 53977.54 | 3984.04 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.64 |
May | 22627.86 | 23-MAY-21:52 | 242898.91 | 17928.18 | 60731.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.87 |
June | 23582.06 | 27-JUN-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.25 |
July | 24126.81 | 20-JUL-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 9.45 | 0.00 |
August | 23896.36 | 10-AUG-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 13.26 | 0.00 |
September | 22965.13 | 15-SEP-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.25 |
October | 21562.98 | 12-OCT-21:05 | 53977.54 | 3984.04 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.37 |
November | 20198.45 | 16-NOV-22:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.76 |
December | 19256.03 | 01-DEC-23:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.23 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 18937.74 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24126.81 | 242898.91 | 17928.18 | 60731.12 | 0.00 | 0.00 | 0.00 | 0.00 | 13.26 | 154.16 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 26871.36 | 15-JAN-11:50 | 800.57 | 353.60 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 141.66 |
February | 26520.32 | 28-FEB-11:33 | 1601.14 | 884.01 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 183.44 |
March | 29480.03 | 14-MAR-10:33 | 1601.14 | 884.01 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 18.69 |
April | 29819.44 | 22-APR-10:33 | 2401.70 | 884.01 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 87.03 |
May | 30504.31 | 27-MAY-10:33 | 2401.70 | 884.01 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 31.30 |
June | 30946.96 | 12-JUN-10:33 | 1601.14 | 884.01 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 28.58 | 0.00 |
July | 31370.87 | 16-JUL-10:40 | 2401.70 | 1060.81 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 27.61 | 0.00 |
August | 31309.35 | 10-AUG-10:40 | 1601.14 | 884.01 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 28.04 | 0.00 |
September | 30577.61 | 04-SEP-10:37 | 2401.70 | 1060.81 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 37.59 |
October | 29580.17 | 11-OCT-10:33 | 1601.14 | 884.01 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 37.42 |
November | 27990.44 | 05-NOV-10:45 | 1601.14 | 707.21 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 37.72 |
December | 26770.98 | 16-DEC-11:50 | 800.57 | 294.67 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 140.34 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 26520.32 | 800.57 | 294.67 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31370.87 | 2401.70 | 1060.81 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 28.58 | 183.44 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3268.51 | 15-JAN-11:33 | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.95 |
February | 2782.73 | 22-FEB-21:10 | 2129.28 | 1756.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.33 |
March | 4249.51 | 15-MAR-18:10 | 13041.84 | 12296.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.22 | 0.00 |
April | 4208.72 | 23-APR-10:33 | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.60 |
May | 4676.07 | 27-MAY-10:33 | 2395.44 | 1646.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.57 |
June | 5174.96 | 29-JUN-10:33 | 1596.96 | 1646.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.42 | 0.00 |
July | 6206.74 | 21-JUL-13:30 | 532.32 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.10 | 0.00 |
August | 5810.61 | 09-AUG-15:03 | 7984.80 | 3293.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.40 | 0.00 |
September | 4933.97 | 16-SEP-10:33 | 2395.44 | 1646.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.61 | 0.00 |
October | 4284.98 | 11-OCT-10:33 | 1596.96 | 1646.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.59 |
November | 3738.55 | 27-NOV-11:33 | 1596.96 | 1646.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.92 |
December | 3255.49 | 16-DEC-11:33 | 2395.44 | 1646.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.96 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 2782.73 | 532.32 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6206.74 | 13041.84 | 12296.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.10 | 119.95 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.379404E+12 | 225211.72 | 17-JAN-07:40 | 0.677955E+12 | 563287.45 | 31-JAN-19:10 |
February | 0.341143E+12 | 224330.46 | 07-FEB-07:19 | 0.626270E+12 | 601063.55 | 06-FEB-19:19 |
March | 0.380304E+12 | 262427.10 | 15-MAR-18:10 | 0.560317E+12 | 550184.26 | 10-MAR-18:40 |
April | 0.364838E+12 | 224161.30 | 07-APR-19:00 | 0.484987E+12 | 528036.99 | 12-APR-17:00 |
May | 0.391774E+12 | 251328.22 | 23-MAY-19:40 | 0.480715E+12 | 475002.21 | 11-MAY-17:10 |
June | 0.450860E+12 | 364446.34 | 27-JUN-20:10 | 0.392881E+12 | 431568.21 | 13-JUN-21:10 |
July | 0.543734E+12 | 381548.78 | 21-JUL-19:00 | 0.374545E+12 | 331077.39 | 03-JUL-17:49 |
August | 0.502154E+12 | 347060.56 | 14-AUG-20:00 | 0.376216E+12 | 324939.97 | 01-AUG-17:40 |
September | 0.420648E+12 | 328516.02 | 15-SEP-19:00 | 0.408554E+12 | 414436.61 | 28-SEP-17:10 |
October | 0.382878E+12 | 242061.41 | 11-OCT-18:10 | 0.502929E+12 | 513200.94 | 17-OCT-17:00 |
November | 0.366445E+12 | 226219.16 | 01-NOV-06:49 | 0.487933E+12 | 532814.52 | 14-NOV-18:00 |
December | 0.380018E+12 | 224799.82 | 15-DEC-07:40 | 0.640718E+12 | 561659.33 | 11-DEC-19:00 |
Annual Sum or Average | 0.490420E+13 | 0.601402E+13 | ||||
Minimum of Months | 0.341143E+12 | 224161.30 | 0.374545E+12 | 324939.97 | ||
Maximum of Months | 0.543734E+12 | 381548.78 | 0.677955E+12 | 601063.55 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.671462E+11 | 0.203510E+11 | 0.140828E+12 | 0.691146E+11 | 0.409993E+11 | 0.215099E+10 | 0.00 | 0.204597E+09 | 0.00 | 0.00 | 0.254043E+11 | 0.804796E+10 | 0.00 |
February | 0.604111E+11 | 0.169826E+11 | 0.127191E+12 | 0.624261E+11 | 0.370375E+11 | 0.195584E+10 | 0.00 | 0.201548E+09 | 0.00 | 0.00 | 0.230096E+11 | 0.727243E+10 | 0.00 |
March | 0.664951E+11 | 0.168716E+11 | 0.140882E+12 | 0.691168E+11 | 0.405393E+11 | 0.463345E+10 | 0.00 | 0.739286E+10 | 0.00 | 0.00 | 0.211274E+11 | 0.804633E+10 | 0.00 |
April | 0.639608E+11 | 0.143768E+11 | 0.136245E+12 | 0.668843E+11 | 0.396170E+11 | 0.623836E+10 | 0.00 | 0.926536E+10 | 0.00 | 0.00 | 0.154091E+11 | 0.779749E+10 | 0.00 |
May | 0.657527E+11 | 0.131404E+11 | 0.140860E+12 | 0.691150E+11 | 0.432372E+11 | 0.860305E+10 | 0.00 | 0.331824E+11 | 0.00 | 0.00 | 0.457941E+10 | 0.804737E+10 | 0.00 |
June | 0.633444E+11 | 0.118893E+11 | 0.136336E+12 | 0.668863E+11 | 0.453387E+11 | 0.841683E+10 | 0.00 | 0.100008E+12 | 0.00 | 0.00 | 0.570217E+10 | 0.778873E+10 | 0.00 |
July | 0.655429E+11 | 0.126148E+11 | 0.140770E+12 | 0.691124E+11 | 0.492707E+11 | 0.891741E+10 | 0.00 | 0.174630E+12 | 0.00 | 0.00 | 0.948473E+10 | 0.805560E+10 | 0.00 |
August | 0.658291E+11 | 0.140880E+11 | 0.140892E+12 | 0.691164E+11 | 0.486590E+11 | 0.876137E+10 | 0.00 | 0.133651E+12 | 0.00 | 0.00 | 0.776473E+10 | 0.804717E+10 | 0.00 |
September | 0.642665E+11 | 0.154872E+11 | 0.136256E+12 | 0.668845E+11 | 0.440750E+11 | 0.833725E+10 | 0.00 | 0.691535E+11 | 0.00 | 0.00 | 0.324313E+10 | 0.779864E+10 | 0.00 |
October | 0.668187E+11 | 0.180043E+11 | 0.140818E+12 | 0.691144E+11 | 0.421704E+11 | 0.712520E+10 | 0.00 | 0.147592E+11 | 0.00 | 0.00 | 0.107748E+11 | 0.804609E+10 | 0.00 |
November | 0.649856E+11 | 0.191591E+11 | 0.136330E+12 | 0.668858E+11 | 0.394995E+11 | 0.415636E+10 | 0.00 | 0.418076E+10 | 0.00 | 0.00 | 0.184315E+11 | 0.778069E+10 | 0.00 |
December | 0.671795E+11 | 0.208174E+11 | 0.140770E+12 | 0.691135E+11 | 0.411334E+11 | 0.208641E+10 | 0.00 | 0.243863E+09 | 0.00 | 0.00 | 0.254444E+11 | 0.805636E+10 | 0.00 |
Annual Sum or Average | 0.781733E+12 | 0.193783E+12 | 0.165818E+13 | 0.813770E+12 | 0.511577E+12 | 0.713825E+11 | 0.00 | 0.546873E+12 | 0.00 | 0.00 | 0.170375E+12 | 0.947849E+11 | 0.00 |
Minimum of Months | 0.604111E+11 | 0.118893E+11 | 0.127191E+12 | 0.624261E+11 | 0.370375E+11 | 0.195584E+10 | 0.00 | 0.201548E+09 | 0.00 | 0.00 | 0.324313E+10 | 0.727243E+10 | 0.00 |
Maximum of Months | 0.671795E+11 | 0.208174E+11 | 0.140892E+12 | 0.691168E+11 | 0.492707E+11 | 0.891741E+10 | 0.00 | 0.174630E+12 | 0.00 | 0.00 | 0.254444E+11 | 0.805636E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.151918E+12 | 0.00 | 0.268569E+12 | 0.00 | 0.257468E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.254627E+12 | 0.00 | 0.234440E+12 | 0.00 | 0.00 |
March | 0.152024E+12 | 0.00 | 0.150549E+12 | 0.00 | 0.257744E+12 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.962204E+11 | 0.00 | 0.241810E+12 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.900420E+11 | 0.00 | 0.238695E+12 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 0.257309E+11 | 0.00 | 0.220036E+12 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 0.383783E+10 | 0.00 | 0.218887E+12 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 0.845602E+10 | 0.00 | 0.215721E+12 | 0.00 | 0.00 |
September | 0.146971E+12 | 0.00 | 0.500529E+11 | 0.00 | 0.211530E+12 | 0.00 | 0.00 |
October | 0.151903E+12 | 0.00 | 0.124285E+12 | 0.00 | 0.226741E+12 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.110542E+12 | 0.00 | 0.230300E+12 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.239647E+12 | 0.00 | 0.249251E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178884E+13 | 0.00 | 0.142256E+13 | 0.00 | 0.280262E+13 | 0.00 | 0.00 |
Minimum of Months | 0.137204E+12 | 0.00 | 0.383783E+10 | 0.00 | 0.211530E+12 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.268569E+12 | 0.00 | 0.257744E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 64632.59 | 02-JAN-20:10 | 12338.45 | 01-JAN-00:10 | 89171.45 | 02-JAN-07:10 | 49607.07 | 02-JAN-07:19 | 23275.63 | 31-JAN-19:19 | 3889.02 | 30-JAN-10:50 | 0.00 | 01-JAN-00:10 |
February | 64632.59 | 01-FEB-20:10 | 12338.45 | 01-FEB-00:10 | 89171.45 | 01-FEB-07:10 | 49607.07 | 01-FEB-07:19 | 25263.03 | 06-FEB-19:19 | 3860.77 | 08-FEB-09:09 | 0.00 | 01-FEB-00:10 |
March | 64632.59 | 01-MAR-20:10 | 12338.45 | 01-MAR-00:10 | 89171.45 | 01-MAR-07:10 | 49607.07 | 13-MAR-06:19 | 28445.36 | 15-MAR-21:00 | 3827.09 | 22-MAR-06:10 | 0.00 | 01-MAR-00:10 |
April | 64632.59 | 03-APR-19:10 | 12338.45 | 01-APR-00:10 | 89171.45 | 03-APR-06:10 | 49606.78 | 10-APR-06:19 | 25383.08 | 07-APR-21:00 | 3819.20 | 29-APR-06:19 | 0.00 | 01-APR-00:10 |
May | 64632.59 | 01-MAY-19:10 | 12338.45 | 01-MAY-00:10 | 89171.45 | 01-MAY-06:10 | 49606.28 | 12-MAY-06:19 | 29424.66 | 23-MAY-21:00 | 3766.08 | 06-MAY-06:10 | 0.00 | 01-MAY-00:10 |
June | 64632.59 | 01-JUN-19:40 | 12338.45 | 01-JUN-00:10 | 89171.45 | 01-JUN-06:10 | 49605.70 | 26-JUN-06:19 | 32325.68 | 29-JUN-21:00 | 4130.81 | 17-JUN-18:00 | 0.00 | 01-JUN-00:10 |
July | 64632.59 | 03-JUL-19:40 | 12338.45 | 01-JUL-00:10 | 89171.45 | 03-JUL-06:10 | 49606.38 | 21-JUL-06:19 | 33767.58 | 17-JUL-21:00 | 4349.59 | 21-JUL-19:00 | 0.00 | 01-JUL-00:10 |
August | 64632.59 | 01-AUG-19:30 | 12338.45 | 01-AUG-00:10 | 89171.45 | 01-AUG-06:10 | 49606.78 | 28-AUG-06:19 | 34071.56 | 10-AUG-21:10 | 3960.60 | 14-AUG-21:00 | 0.00 | 01-AUG-00:10 |
September | 64632.59 | 01-SEP-19:10 | 12338.45 | 01-SEP-00:10 | 89171.45 | 01-SEP-06:10 | 49607.07 | 18-SEP-06:19 | 33462.55 | 15-SEP-21:00 | 3809.66 | 30-SEP-06:10 | 0.00 | 01-SEP-00:10 |
October | 64632.59 | 02-OCT-19:10 | 12338.45 | 01-OCT-00:10 | 89171.45 | 02-OCT-06:10 | 49607.07 | 02-OCT-06:19 | 30931.54 | 11-OCT-21:49 | 3837.51 | 19-OCT-08:09 | 0.00 | 01-OCT-00:10 |
November | 64632.59 | 01-NOV-19:10 | 12338.45 | 01-NOV-00:10 | 89171.45 | 01-NOV-06:10 | 49607.07 | 01-NOV-06:19 | 23310.58 | 16-NOV-22:10 | 3847.36 | 12-NOV-11:39 | 0.00 | 01-NOV-00:10 |
December | 64632.59 | 01-DEC-20:10 | 12338.45 | 01-DEC-00:10 | 89171.45 | 01-DEC-07:10 | 49607.07 | 01-DEC-07:19 | 23424.23 | 28-DEC-19:19 | 3970.11 | 11-DEC-10:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 64632.59 | 12338.45 | 89171.45 | 49605.70 | 23275.63 | 3766.08 | 0.00 | |||||||
Maximum of Months | 64632.59 | 12338.45 | 89171.45 | 49607.07 | 34071.56 | 4349.59 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 3457.31 | 15-JAN-16:10 | 0.00 | 0.00 | 9938.94 | 01-JAN-00:10 | 4751.10 | 20-JAN-19:00 | 0.00 |
February | 3845.64 | 28-FEB-16:10 | 0.00 | 0.00 | 9938.94 | 01-FEB-00:20 | 4751.13 | 13-FEB-07:00 | 0.00 |
March | 72612.45 | 15-MAR-15:09 | 0.00 | 0.00 | 9938.94 | 01-MAR-00:20 | 4751.13 | 08-MAR-07:49 | 0.00 |
April | 41556.39 | 08-APR-15:09 | 0.00 | 0.00 | 9938.94 | 01-APR-00:10 | 4751.13 | 19-APR-18:49 | 0.00 |
May | 79707.44 | 10-MAY-15:09 | 0.00 | 0.00 | 9938.94 | 01-MAY-00:10 | 4751.13 | 15-MAY-06:00 | 0.00 |
June | 148552.14 | 27-JUN-20:10 | 0.00 | 0.00 | 9938.94 | 02-JUN-08:00 | 4751.13 | 13-JUN-18:40 | 0.00 |
July | 158511.57 | 21-JUL-19:00 | 0.00 | 0.00 | 9938.94 | 15-JUL-08:39 | 4751.12 | 27-JUL-18:00 | 0.00 |
August | 144802.24 | 13-AUG-15:20 | 0.00 | 0.00 | 9938.94 | 06-AUG-08:00 | 4751.13 | 29-AUG-18:49 | 0.00 |
September | 123272.62 | 15-SEP-21:00 | 0.00 | 0.00 | 9938.94 | 16-SEP-08:00 | 4751.13 | 07-SEP-06:00 | 0.00 |
October | 65155.28 | 11-OCT-15:09 | 0.00 | 0.00 | 9938.94 | 02-OCT-04:19 | 4751.13 | 17-OCT-18:49 | 0.00 |
November | 26419.86 | 05-NOV-08:00 | 0.00 | 0.00 | 9938.94 | 01-NOV-00:10 | 4751.13 | 03-NOV-06:00 | 0.00 |
December | 3420.28 | 01-DEC-19:10 | 0.00 | 0.00 | 9938.94 | 01-DEC-00:20 | 4751.13 | 04-DEC-07:49 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 3420.28 | 0.00 | 0.00 | 9938.94 | 4751.10 | 0.00 | |||
Maximum of Months | 158511.57 | 0.00 | 0.00 | 9938.94 | 4751.13 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 225211.72 | 17-JAN-07:40 | 36001.17 | 89171.45 | 12338.45 | 49607.07 | 15789.74 | 3284.25 | 0.00 | 1127.41 | 0.00 |
February | 224330.46 | 07-FEB-07:19 | 36001.17 | 89171.45 | 12338.45 | 49607.07 | 18250.09 | 1083.93 | 0.00 | 0.00 | 0.00 |
March | 262427.10 | 15-MAR-18:10 | 56530.17 | 77573.37 | 0.00 | 28158.31 | 20099.63 | 3285.51 | 0.00 | 59676.79 | 0.00 |
April | 224161.30 | 07-APR-19:00 | 64632.59 | 86439.81 | 12338.45 | 10999.77 | 20635.69 | 3099.40 | 0.00 | 20220.62 | 0.00 |
May | 251328.22 | 23-MAY-19:40 | 64632.59 | 86439.81 | 12338.45 | 10999.77 | 22001.29 | 3164.53 | 0.00 | 45940.69 | 0.00 |
June | 364446.34 | 27-JUN-20:10 | 57474.69 | 88218.55 | 12338.45 | 11004.39 | 26813.86 | 3986.04 | 0.00 | 148552.14 | 0.00 |
July | 381548.78 | 21-JUL-19:00 | 64632.59 | 86439.81 | 12338.45 | 10999.77 | 28498.75 | 4349.59 | 0.00 | 158511.57 | 0.00 |
August | 347060.56 | 14-AUG-20:00 | 57474.69 | 88218.55 | 12338.45 | 10998.34 | 30537.84 | 3860.06 | 0.00 | 127191.84 | 0.00 |
September | 328516.02 | 15-SEP-19:00 | 64632.59 | 86439.81 | 12338.45 | 10999.77 | 24427.64 | 3743.73 | 0.00 | 120097.80 | 0.00 |
October | 242061.41 | 11-OCT-18:10 | 57474.69 | 77573.37 | 12338.45 | 28159.60 | 20451.68 | 3226.32 | 0.00 | 35685.82 | 0.00 |
November | 226219.16 | 01-NOV-06:49 | 36001.17 | 89171.45 | 12338.45 | 49607.07 | 15906.13 | 3145.77 | 0.00 | 3523.17 | 0.00 |
December | 224799.82 | 15-DEC-07:40 | 36001.17 | 89171.45 | 12338.45 | 49607.07 | 15761.69 | 3358.53 | 0.00 | 655.90 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 224161.30 | 36001.17 | 77573.37 | 0.00 | 10998.34 | 15761.69 | 1083.93 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 381548.78 | 64632.59 | 89171.45 | 12338.45 | 49607.07 | 30537.84 | 4349.59 | 0.00 | 158511.57 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 241754.88 | 31-JAN-16:10 | 0.00 | 265084.95 | 31-JAN-21:19 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 285359.31 | 06-FEB-09:09 | 0.00 | 265171.40 | 14-FEB-21:19 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 201729.81 | 07-MAR-07:10 | 0.00 | 265096.36 | 01-MAR-21:19 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 194657.11 | 13-APR-10:50 | 0.00 | 261343.03 | 03-APR-20:00 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 170738.52 | 06-MAY-06:30 | 0.00 | 251666.62 | 01-MAY-20:19 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 165809.10 | 04-JUN-03:39 | 0.00 | 239077.32 | 01-JUN-20:40 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 59391.26 | 13-JUL-03:00 | 0.00 | 228264.83 | 03-JUL-20:19 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 89714.82 | 31-AUG-04:00 | 0.00 | 224395.68 | 31-AUG-20:49 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 179677.41 | 30-SEP-06:30 | 0.00 | 228219.58 | 29-SEP-20:19 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 193237.87 | 14-OCT-06:30 | 0.00 | 239018.38 | 31-OCT-20:40 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 204492.64 | 12-NOV-11:50 | 0.00 | 250553.54 | 30-NOV-21:00 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 261860.74 | 11-DEC-09:09 | 0.00 | 261383.37 | 28-DEC-21:49 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 104248.32 | 0.00 | 59391.26 | 0.00 | 224395.68 | 0.00 | |||
Maximum of Months | 104248.32 | 0.00 | 285359.31 | 0.00 | 265171.40 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.17 | 20.54 | 1.17 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 |
February | 0.83 | 20.46 | 0.83 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.69 | 0.17 | 21.69 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.74 | 1.50 | 21.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.84 | 0.33 | 21.84 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.17 | 20.52 | 2.17 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
Annual Sum or Average | 4.17 | 20.52 | 4.17 | 20.52 | 2.00 | 20.75 | 2.00 | 20.92 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.17 | 20.54 | 2.17 | 20.54 | 1.50 | 21.84 | 1.50 | 21.84 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.17 | 20.51 | 5.17 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
February | 2.50 | 20.49 | 2.50 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 |
March | 0.17 | 20.55 | 0.17 | 20.55 | 0.00 | 20.55 | 0.00 | 20.55 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.96 | 0.83 | 21.96 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 21.81 | 2.33 | 21.81 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 21.73 | 2.67 | 21.73 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.72 | 1.17 | 21.72 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.75 | 0.17 | 21.75 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 4.17 | 20.49 | 4.17 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 |
Annual Sum or Average | 12.00 | 20.50 | 12.00 | 20.50 | 7.17 | 20.79 | 7.17 | 20.98 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5.17 | 20.55 | 5.17 | 20.55 | 2.67 | 21.96 | 2.67 | 21.96 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.83 | 20.35 | 2.83 | 20.35 | 0.00 | 20.35 | 0.00 | 20.35 |
February | 1.33 | 20.31 | 1.33 | 20.31 | 0.00 | 20.31 | 0.00 | 20.31 |
March | 0.33 | 20.45 | 0.33 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.74 | 0.67 | 21.74 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 21.83 | 5.17 | 21.83 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 21.87 | 6.00 | 21.87 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 21.86 | 3.00 | 21.86 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.79 | 1.67 | 21.79 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.67 | 20.27 | 2.67 | 20.27 | 0.00 | 20.27 | 0.00 | 20.27 |
Annual Sum or Average | 7.17 | 20.32 | 7.17 | 20.32 | 16.50 | 21.13 | 16.50 | 21.38 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.83 | 20.45 | 2.83 | 20.45 | 6.00 | 21.87 | 6.00 | 21.87 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.83 | 20.53 | 1.83 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 |
February | 1.17 | 20.48 | 1.17 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.83 | 20.52 | 2.83 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
Annual Sum or Average | 5.83 | 20.51 | 5.83 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.83 | 20.53 | 2.83 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.83 | 20.50 | 4.83 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
February | 2.33 | 20.45 | 2.33 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 22.30 | 0.17 | 22.30 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 22.18 | 2.67 | 22.18 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 22.17 | 6.17 | 22.17 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 22.25 | 4.00 | 22.25 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 22.04 | 0.50 | 22.04 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 4.50 | 20.45 | 4.50 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 |
Annual Sum or Average | 11.67 | 20.47 | 11.67 | 20.47 | 13.50 | 21.10 | 13.50 | 21.39 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.83 | 20.50 | 4.83 | 20.50 | 6.17 | 22.30 | 6.17 | 22.30 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.17 | 20.53 | 2.17 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 |
February | 0.83 | 20.42 | 0.83 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.71 | 0.67 | 21.71 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.72 | 1.67 | 21.72 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 21.79 | 2.83 | 21.79 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.86 | 0.50 | 21.86 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.33 | 20.50 | 2.33 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
Annual Sum or Average | 5.33 | 20.50 | 5.33 | 20.50 | 5.67 | 20.94 | 5.67 | 21.15 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.33 | 20.53 | 2.33 | 20.53 | 2.83 | 21.86 | 2.83 | 21.86 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.67 | 20.49 | 5.67 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 |
February | 2.67 | 20.46 | 2.67 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.73 | 0.33 | 21.73 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 22.00 | 1.33 | 22.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 21.87 | 3.67 | 21.87 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 21.77 | 3.83 | 21.77 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 21.76 | 2.67 | 21.76 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.84 | 0.83 | 21.84 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 4.33 | 20.46 | 4.33 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 |
Annual Sum or Average | 12.67 | 20.47 | 12.67 | 20.47 | 12.67 | 20.92 | 12.67 | 21.15 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5.67 | 20.49 | 5.67 | 20.49 | 3.83 | 22.00 | 3.83 | 22.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 20.54 | 0.33 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 |
February | 0.33 | 20.46 | 0.33 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.75 | 1.83 | 21.75 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.80 | 1.17 | 21.80 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.86 | 0.67 | 21.86 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.50 | 20.53 | 0.50 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 |
Annual Sum or Average | 1.17 | 20.51 | 1.17 | 20.51 | 3.67 | 21.29 | 3.67 | 21.48 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 20.54 | 0.50 | 20.54 | 1.83 | 21.86 | 1.83 | 21.86 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 23.20 | 0.00 | 23.20 | 0.00 | 23.20 |
February | 672.00 | 22.94 | 0.00 | 22.94 | 0.00 | 22.94 |
March | 744.00 | 22.39 | 0.00 | 22.39 | 0.00 | 22.39 |
April | 720.00 | 22.21 | 0.00 | 22.21 | 0.00 | 22.21 |
May | 744.00 | 22.13 | 0.00 | 22.13 | 0.00 | 22.13 |
June | 720.00 | 22.62 | 0.00 | 22.62 | 0.00 | 22.62 |
July | 696.17 | 22.97 | 0.00 | 22.97 | 0.00 | 22.97 |
August | 340.00 | 23.23 | 129.33 | 23.40 | 0.00 | 23.40 |
September | 185.17 | 23.55 | 184.50 | 23.75 | 1.83 | 23.75 |
October | 328.17 | 23.77 | 25.67 | 23.79 | 0.00 | 23.79 |
November | 528.83 | 23.81 | 0.00 | 23.81 | 0.00 | 23.81 |
December | 726.17 | 23.65 | 0.00 | 23.65 | 0.00 | 23.65 |
Annual Sum or Average | 7148.50 | 22.93 | 339.50 | 22.97 | 1.83 | 22.97 |
Minimum of Months | 185.17 | 22.13 | 0.00 | 22.13 | 0.00 | 22.13 |
Maximum of Months | 744.00 | 23.81 | 184.50 | 23.81 | 1.83 | 23.81 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 741.33 | 21.06 | 598.50 | 21.03 | 598.50 | 21.02 |
February | 668.83 | 21.06 | 500.67 | 21.04 | 500.67 | 21.02 |
March | 716.50 | 21.22 | 203.83 | 21.20 | 196.17 | 21.16 |
April | 688.67 | 21.27 | 25.83 | 21.26 | 24.67 | 21.25 |
May | 693.83 | 21.49 | 10.00 | 21.52 | 0.00 | 21.52 |
June | 552.00 | 21.96 | 92.17 | 22.19 | 0.00 | 22.19 |
July | 379.67 | 22.24 | 248.67 | 22.77 | 0.00 | 22.77 |
August | 422.67 | 22.14 | 226.50 | 22.68 | 0.00 | 22.68 |
September | 544.50 | 21.78 | 120.33 | 22.15 | 0.00 | 22.15 |
October | 683.00 | 21.31 | 48.83 | 21.45 | 9.33 | 21.45 |
November | 704.67 | 21.13 | 141.67 | 21.11 | 141.67 | 21.09 |
December | 739.33 | 21.05 | 546.50 | 21.03 | 546.50 | 21.02 |
Annual Sum or Average | 7535.00 | 21.40 | 2763.50 | 21.49 | 2017.50 | 21.41 |
Minimum of Months | 379.67 | 21.05 | 10.00 | 21.03 | 0.00 | 21.02 |
Maximum of Months | 741.33 | 22.24 | 598.50 | 22.77 | 598.50 | 22.77 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.37 | 90.00 | 21.33 | 90.00 | 21.30 |
February | 672.00 | 21.36 | 49.33 | 21.34 | 49.33 | 21.32 |
March | 733.83 | 21.97 | 0.00 | 21.97 | 0.00 | 21.97 |
April | 720.00 | 22.35 | 0.00 | 22.35 | 0.00 | 22.35 |
May | 700.17 | 22.76 | 2.17 | 22.77 | 0.00 | 22.77 |
June | 436.33 | 23.08 | 194.17 | 23.31 | 59.83 | 23.34 |
July | 256.33 | 23.39 | 413.17 | 23.67 | 119.00 | 23.70 |
August | 251.00 | 23.25 | 330.50 | 23.60 | 77.00 | 23.63 |
September | 482.33 | 23.01 | 125.50 | 23.17 | 44.33 | 23.20 |
October | 712.17 | 22.52 | 4.50 | 22.53 | 0.00 | 22.53 |
November | 720.00 | 22.08 | 0.00 | 22.08 | 0.00 | 22.08 |
December | 744.00 | 21.43 | 63.50 | 21.39 | 63.50 | 21.36 |
Annual Sum or Average | 7172.17 | 22.21 | 1272.83 | 22.39 | 503.00 | 22.40 |
Minimum of Months | 251.00 | 21.36 | 0.00 | 21.33 | 0.00 | 21.30 |
Maximum of Months | 744.00 | 23.39 | 413.17 | 23.67 | 119.00 | 23.70 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.01 | 441.83 | 21.01 | 441.83 | 21.00 |
February | 672.00 | 21.01 | 402.33 | 21.01 | 402.33 | 21.00 |
March | 744.00 | 21.25 | 195.50 | 21.20 | 195.50 | 21.16 |
April | 720.00 | 21.51 | 5.83 | 21.51 | 5.83 | 21.50 |
May | 744.00 | 22.27 | 0.00 | 22.27 | 0.00 | 22.27 |
June | 617.00 | 22.99 | 11.50 | 23.01 | 0.00 | 23.01 |
July | 292.33 | 23.27 | 146.67 | 23.48 | 0.00 | 23.48 |
August | 425.17 | 23.31 | 56.50 | 23.38 | 0.00 | 23.38 |
September | 672.33 | 22.89 | 1.17 | 22.89 | 0.00 | 22.89 |
October | 744.00 | 21.95 | 0.00 | 21.95 | 0.00 | 21.95 |
November | 720.00 | 21.36 | 0.00 | 21.36 | 0.00 | 21.36 |
December | 744.00 | 21.02 | 291.00 | 21.02 | 291.00 | 21.01 |
Annual Sum or Average | 7838.83 | 21.85 | 1552.33 | 21.77 | 1336.50 | 21.68 |
Minimum of Months | 292.33 | 21.01 | 0.00 | 21.01 | 0.00 | 21.00 |
Maximum of Months | 744.00 | 23.31 | 441.83 | 23.48 | 441.83 | 23.48 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.00 | 499.33 | 21.00 | 499.33 | 21.00 |
February | 672.00 | 21.00 | 479.50 | 21.00 | 479.50 | 21.00 |
March | 744.00 | 21.14 | 253.33 | 21.10 | 253.33 | 21.08 |
April | 720.00 | 21.26 | 23.33 | 21.25 | 23.33 | 21.24 |
May | 744.00 | 21.97 | 0.00 | 21.97 | 0.00 | 21.97 |
June | 698.83 | 22.80 | 0.00 | 22.80 | 0.00 | 22.80 |
July | 475.00 | 23.15 | 39.50 | 23.20 | 0.00 | 23.20 |
August | 607.67 | 23.15 | 1.00 | 23.15 | 0.00 | 23.15 |
September | 708.33 | 22.62 | 0.00 | 22.62 | 0.00 | 22.62 |
October | 744.00 | 21.60 | 0.00 | 21.60 | 0.00 | 21.60 |
November | 720.00 | 21.13 | 11.67 | 21.13 | 11.67 | 21.13 |
December | 744.00 | 21.00 | 342.33 | 21.00 | 342.33 | 21.00 |
Annual Sum or Average | 8321.83 | 21.75 | 1650.00 | 21.64 | 1609.50 | 21.55 |
Minimum of Months | 475.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
Maximum of Months | 744.00 | 23.15 | 499.33 | 23.20 | 499.33 | 23.20 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 262.50 | 22.59 | 383.50 | 23.26 | 125.17 | 23.38 |
February | 247.33 | 22.55 | 332.33 | 23.24 | 111.67 | 23.37 |
March | 260.83 | 22.94 | 490.83 | 23.29 | 161.50 | 23.42 |
April | 251.83 | 23.14 | 567.83 | 23.29 | 176.67 | 23.42 |
May | 294.83 | 23.47 | 629.50 | 23.35 | 240.33 | 23.48 |
June | 290.17 | 23.86 | 676.33 | 23.36 | 278.00 | 23.50 |
July | 318.17 | 23.96 | 729.67 | 23.35 | 317.67 | 23.49 |
August | 309.67 | 23.97 | 717.00 | 23.37 | 309.00 | 23.51 |
September | 294.67 | 23.81 | 660.33 | 23.39 | 276.00 | 23.52 |
October | 265.17 | 23.36 | 618.00 | 23.34 | 206.83 | 23.47 |
November | 240.50 | 23.01 | 531.83 | 23.30 | 156.50 | 23.42 |
December | 263.83 | 22.64 | 406.33 | 23.26 | 130.83 | 23.38 |
Annual Sum or Average | 3299.50 | 23.31 | 6743.50 | 23.32 | 2490.17 | 23.46 |
Minimum of Months | 240.50 | 22.55 | 332.33 | 23.24 | 111.67 | 23.37 |
Maximum of Months | 318.17 | 23.97 | 729.67 | 23.39 | 317.67 | 23.52 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 736.83 | 21.36 | 190.17 | 21.30 | 187.67 | 21.25 |
February | 662.00 | 21.35 | 143.17 | 21.30 | 140.83 | 21.26 |
March | 657.00 | 21.91 | 46.50 | 22.01 | 5.83 | 22.00 |
April | 641.00 | 22.18 | 26.00 | 22.24 | 0.00 | 22.24 |
May | 557.50 | 22.52 | 84.00 | 22.66 | 16.67 | 22.67 |
June | 354.17 | 23.04 | 373.67 | 23.32 | 139.00 | 23.41 |
July | 297.50 | 23.60 | 637.50 | 23.61 | 258.33 | 23.66 |
August | 231.67 | 23.33 | 575.67 | 23.62 | 153.83 | 23.66 |
September | 323.00 | 22.83 | 389.83 | 23.31 | 106.67 | 23.36 |
October | 563.00 | 22.17 | 122.00 | 22.47 | 8.17 | 22.48 |
November | 681.33 | 21.92 | 16.83 | 21.96 | 0.17 | 21.96 |
December | 733.17 | 21.36 | 162.17 | 21.32 | 157.00 | 21.27 |
Annual Sum or Average | 6438.17 | 22.07 | 2767.50 | 22.41 | 1174.17 | 22.43 |
Minimum of Months | 231.67 | 21.35 | 16.83 | 21.30 | 0.00 | 21.25 |
Maximum of Months | 736.83 | 23.60 | 637.50 | 23.62 | 258.33 | 23.66 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.84 | 3.50 | 21.83 | 3.50 | 21.83 |
February | 672.00 | 21.83 | 10.00 | 21.82 | 10.00 | 21.81 |
March | 702.67 | 22.40 | 20.50 | 22.45 | 0.00 | 22.45 |
April | 686.00 | 22.69 | 0.33 | 22.70 | 0.00 | 22.70 |
May | 540.67 | 22.89 | 49.33 | 22.97 | 15.17 | 22.99 |
June | 346.50 | 23.26 | 302.67 | 23.54 | 122.33 | 23.60 |
July | 280.67 | 23.77 | 551.67 | 23.79 | 235.33 | 23.83 |
August | 208.33 | 23.57 | 514.33 | 23.76 | 134.67 | 23.79 |
September | 297.67 | 23.23 | 299.50 | 23.55 | 96.50 | 23.60 |
October | 578.17 | 22.79 | 64.50 | 22.90 | 3.83 | 22.91 |
November | 709.33 | 22.53 | 0.00 | 22.53 | 0.00 | 22.53 |
December | 744.00 | 21.88 | 0.50 | 21.88 | 0.50 | 21.88 |
Annual Sum or Average | 6510.00 | 22.52 | 1816.83 | 22.80 | 621.83 | 22.88 |
Minimum of Months | 208.33 | 21.83 | 0.00 | 21.82 | 0.00 | 21.81 |
Maximum of Months | 744.00 | 23.77 | 551.67 | 23.79 | 235.33 | 23.83 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.62 | 695.17 | 20.60 | 695.17 | 20.60 |
February | 672.00 | 20.67 | 599.83 | 20.64 | 599.83 | 20.63 |
March | 740.67 | 21.15 | 246.00 | 21.07 | 246.00 | 21.02 |
April | 715.33 | 21.37 | 27.17 | 21.35 | 27.17 | 21.33 |
May | 712.83 | 21.54 | 0.00 | 21.54 | 0.00 | 21.54 |
June | 635.50 | 21.50 | 6.17 | 21.51 | 1.17 | 21.52 |
July | 622.17 | 21.42 | 11.83 | 21.45 | 0.67 | 21.46 |
August | 635.33 | 21.44 | 14.50 | 21.49 | 1.17 | 21.49 |
September | 664.17 | 21.52 | 2.33 | 21.53 | 0.83 | 21.53 |
October | 735.33 | 21.33 | 19.50 | 21.32 | 19.50 | 21.30 |
November | 720.00 | 21.03 | 232.67 | 20.92 | 232.67 | 20.85 |
December | 744.00 | 20.63 | 642.67 | 20.59 | 642.67 | 20.58 |
Annual Sum or Average | 8341.33 | 21.17 | 2497.83 | 21.05 | 2466.83 | 20.97 |
Minimum of Months | 622.17 | 20.62 | 0.00 | 20.59 | 0.00 | 20.58 |
Maximum of Months | 744.00 | 21.54 | 695.17 | 21.54 | 695.17 | 21.54 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.52 | 726.00 | 20.51 | 726.00 | 20.51 |
February | 672.00 | 20.54 | 646.33 | 20.53 | 646.33 | 20.53 |
March | 744.00 | 20.94 | 369.33 | 20.83 | 369.33 | 20.77 |
April | 716.17 | 21.27 | 49.33 | 21.23 | 49.17 | 21.19 |
May | 680.33 | 21.71 | 39.00 | 21.93 | 5.83 | 21.98 |
June | 553.00 | 22.10 | 133.33 | 22.75 | 51.67 | 22.97 |
July | 559.67 | 21.99 | 138.83 | 22.54 | 65.50 | 22.72 |
August | 583.50 | 22.00 | 101.83 | 22.42 | 53.00 | 22.59 |
September | 620.83 | 21.82 | 82.00 | 22.16 | 25.67 | 22.21 |
October | 739.50 | 21.23 | 57.17 | 21.20 | 55.00 | 21.15 |
November | 720.00 | 20.84 | 327.17 | 20.74 | 327.17 | 20.69 |
December | 744.00 | 20.54 | 705.00 | 20.52 | 705.00 | 20.52 |
Annual Sum or Average | 8077.00 | 21.24 | 3375.33 | 21.23 | 3079.67 | 21.14 |
Minimum of Months | 553.00 | 20.52 | 39.00 | 20.51 | 5.83 | 20.51 |
Maximum of Months | 744.00 | 22.10 | 726.00 | 22.75 | 726.00 | 22.97 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.82 | 501.17 | 20.77 | 501.17 | 20.75 |
February | 672.00 | 20.85 | 462.00 | 20.81 | 462.00 | 20.79 |
March | 744.00 | 21.11 | 222.50 | 21.04 | 222.50 | 20.99 |
April | 720.00 | 21.33 | 1.17 | 21.33 | 1.17 | 21.33 |
May | 744.00 | 21.68 | 0.00 | 21.68 | 0.00 | 21.68 |
June | 700.00 | 22.07 | 33.50 | 22.13 | 27.33 | 22.18 |
July | 716.50 | 22.15 | 68.50 | 22.29 | 60.67 | 22.39 |
August | 736.00 | 22.12 | 44.33 | 22.21 | 44.00 | 22.28 |
September | 716.33 | 21.87 | 24.00 | 21.93 | 23.83 | 21.98 |
October | 744.00 | 21.34 | 1.33 | 21.34 | 1.33 | 21.34 |
November | 720.00 | 21.12 | 27.33 | 21.09 | 27.33 | 21.07 |
December | 744.00 | 20.85 | 375.50 | 20.77 | 375.50 | 20.73 |
Annual Sum or Average | 8700.83 | 21.44 | 1761.33 | 21.37 | 1746.83 | 21.31 |
Minimum of Months | 672.00 | 20.82 | 0.00 | 20.77 | 0.00 | 20.73 |
Maximum of Months | 744.00 | 22.15 | 501.17 | 22.29 | 501.17 | 22.39 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.64 | 677.00 | 20.61 | 677.00 | 20.61 |
February | 672.00 | 20.70 | 585.50 | 20.66 | 585.50 | 20.65 |
March | 742.83 | 21.21 | 237.67 | 21.14 | 237.67 | 21.10 |
April | 719.67 | 21.46 | 21.33 | 21.45 | 21.33 | 21.44 |
May | 733.83 | 21.64 | 0.00 | 21.64 | 0.00 | 21.64 |
June | 630.50 | 21.50 | 2.50 | 21.51 | 0.67 | 21.51 |
July | 593.50 | 21.35 | 4.33 | 21.36 | 0.67 | 21.36 |
August | 619.83 | 21.42 | 2.67 | 21.43 | 0.83 | 21.43 |
September | 646.67 | 21.50 | 1.00 | 21.50 | 0.67 | 21.51 |
October | 739.50 | 21.40 | 15.67 | 21.39 | 15.67 | 21.38 |
November | 720.00 | 21.03 | 229.83 | 20.92 | 229.83 | 20.85 |
December | 744.00 | 20.62 | 641.67 | 20.59 | 641.67 | 20.57 |
Annual Sum or Average | 8306.33 | 21.20 | 2419.17 | 21.07 | 2411.50 | 20.99 |
Minimum of Months | 593.50 | 20.62 | 0.00 | 20.59 | 0.00 | 20.57 |
Maximum of Months | 744.00 | 21.64 | 677.00 | 21.64 | 677.00 | 21.64 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.53 | 720.67 | 20.52 | 720.67 | 20.52 |
February | 672.00 | 20.56 | 643.83 | 20.55 | 643.83 | 20.54 |
March | 744.00 | 20.99 | 367.67 | 20.90 | 367.67 | 20.85 |
April | 720.00 | 21.40 | 34.00 | 21.37 | 34.00 | 21.35 |
May | 729.17 | 21.84 | 2.67 | 21.85 | 0.33 | 21.85 |
June | 566.00 | 21.98 | 79.33 | 22.29 | 32.00 | 22.39 |
July | 509.00 | 21.94 | 138.00 | 22.53 | 69.17 | 22.76 |
August | 543.00 | 21.89 | 102.67 | 22.31 | 49.50 | 22.45 |
September | 688.83 | 22.01 | 32.33 | 22.10 | 24.67 | 22.15 |
October | 744.00 | 21.31 | 37.17 | 21.28 | 37.17 | 21.26 |
November | 720.00 | 20.84 | 327.67 | 20.74 | 327.67 | 20.69 |
December | 744.00 | 20.54 | 696.17 | 20.52 | 696.17 | 20.52 |
Annual Sum or Average | 8124.00 | 21.27 | 3182.17 | 21.20 | 3002.83 | 21.11 |
Minimum of Months | 509.00 | 20.53 | 2.67 | 20.52 | 0.33 | 20.52 |
Maximum of Months | 744.00 | 22.01 | 720.67 | 22.53 | 720.67 | 22.76 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.00 | 430.67 | 21.00 | 430.67 | 21.00 |
February | 672.00 | 21.00 | 355.83 | 21.00 | 355.83 | 21.00 |
March | 744.00 | 21.12 | 128.17 | 21.10 | 128.17 | 21.09 |
April | 720.00 | 21.36 | 0.00 | 21.36 | 0.00 | 21.36 |
May | 744.00 | 22.05 | 0.00 | 22.05 | 0.00 | 22.05 |
June | 705.17 | 22.86 | 33.00 | 22.86 | 33.00 | 22.87 |
July | 605.50 | 23.21 | 81.00 | 23.24 | 74.17 | 23.25 |
August | 663.00 | 23.15 | 56.00 | 23.15 | 56.00 | 23.16 |
September | 720.00 | 22.61 | 23.50 | 22.61 | 23.50 | 22.61 |
October | 744.00 | 21.43 | 0.00 | 21.43 | 0.00 | 21.43 |
November | 720.00 | 21.06 | 8.00 | 21.06 | 8.00 | 21.06 |
December | 744.00 | 21.00 | 292.33 | 21.00 | 292.33 | 21.00 |
Annual Sum or Average | 8525.67 | 21.79 | 1408.50 | 21.72 | 1401.67 | 21.67 |
Minimum of Months | 605.50 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
Maximum of Months | 744.00 | 23.21 | 430.67 | 23.24 | 430.67 | 23.25 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.54 | 728.33 | 20.54 | 728.33 | 20.53 |
February | 672.00 | 20.58 | 641.67 | 20.57 | 641.67 | 20.56 |
March | 738.83 | 21.03 | 346.17 | 20.94 | 346.17 | 20.89 |
April | 709.00 | 21.29 | 95.00 | 21.23 | 95.00 | 21.18 |
May | 700.33 | 21.49 | 2.00 | 21.49 | 0.83 | 21.49 |
June | 617.33 | 21.43 | 23.17 | 21.50 | 4.83 | 21.50 |
July | 603.67 | 21.36 | 37.67 | 21.47 | 6.17 | 21.49 |
August | 617.50 | 21.38 | 36.83 | 21.49 | 4.33 | 21.50 |
September | 646.33 | 21.45 | 18.67 | 21.48 | 11.17 | 21.48 |
October | 731.83 | 21.25 | 95.50 | 21.20 | 95.00 | 21.16 |
November | 720.00 | 20.92 | 369.17 | 20.80 | 369.17 | 20.75 |
December | 744.00 | 20.56 | 708.17 | 20.54 | 708.17 | 20.54 |
Annual Sum or Average | 8244.83 | 21.09 | 3102.33 | 20.98 | 3010.83 | 20.90 |
Minimum of Months | 603.67 | 20.54 | 2.00 | 20.54 | 0.83 | 20.53 |
Maximum of Months | 744.00 | 21.49 | 728.33 | 21.50 | 728.33 | 21.50 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.48 | 740.50 | 20.48 | 740.50 | 20.48 |
February | 672.00 | 20.50 | 664.67 | 20.50 | 664.67 | 20.49 |
March | 742.33 | 20.83 | 449.83 | 20.73 | 449.83 | 20.68 |
April | 714.00 | 21.20 | 129.17 | 21.12 | 127.83 | 21.06 |
May | 672.00 | 21.72 | 49.67 | 22.02 | 13.00 | 22.12 |
June | 546.50 | 22.23 | 150.00 | 22.96 | 72.50 | 23.27 |
July | 548.50 | 22.02 | 157.17 | 22.63 | 83.00 | 22.85 |
August | 565.67 | 22.00 | 127.17 | 22.51 | 66.50 | 22.72 |
September | 608.17 | 21.80 | 106.00 | 22.22 | 42.83 | 22.31 |
October | 738.00 | 21.13 | 165.50 | 21.06 | 162.67 | 21.00 |
November | 720.00 | 20.71 | 484.67 | 20.65 | 484.67 | 20.62 |
December | 744.00 | 20.49 | 731.67 | 20.49 | 731.67 | 20.49 |
Annual Sum or Average | 8015.17 | 21.20 | 3956.00 | 21.20 | 3639.67 | 21.12 |
Minimum of Months | 546.50 | 20.48 | 49.67 | 20.48 | 13.00 | 20.48 |
Maximum of Months | 744.00 | 22.23 | 740.50 | 22.96 | 740.50 | 23.27 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 741.33 | 20.92 | 571.33 | 20.83 | 571.33 | 20.79 |
February | 672.00 | 20.94 | 489.17 | 20.86 | 489.17 | 20.83 |
March | 736.50 | 21.36 | 167.17 | 21.29 | 167.17 | 21.24 |
April | 695.67 | 21.41 | 18.50 | 21.39 | 18.50 | 21.38 |
May | 703.67 | 21.52 | 0.00 | 21.52 | 0.00 | 21.52 |
June | 648.50 | 21.51 | 3.50 | 21.52 | 3.50 | 21.52 |
July | 634.33 | 21.44 | 9.67 | 21.46 | 9.67 | 21.48 |
August | 639.83 | 21.44 | 9.00 | 21.47 | 4.83 | 21.48 |
September | 633.17 | 21.45 | 14.17 | 21.49 | 2.33 | 21.50 |
October | 702.67 | 21.39 | 11.50 | 21.41 | 3.50 | 21.41 |
November | 712.50 | 21.22 | 151.50 | 21.12 | 151.50 | 21.06 |
December | 740.83 | 20.83 | 539.00 | 20.75 | 539.00 | 20.71 |
Annual Sum or Average | 8261.00 | 21.28 | 1984.50 | 21.18 | 1960.50 | 21.11 |
Minimum of Months | 633.17 | 20.83 | 0.00 | 20.75 | 0.00 | 20.71 |
Maximum of Months | 741.33 | 21.52 | 571.33 | 21.52 | 571.33 | 21.52 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 653.50 | 23.12 | 0.00 | 23.12 | 0.00 | 23.12 |
February | 603.67 | 23.15 | 0.00 | 23.15 | 0.00 | 23.15 |
March | 448.83 | 23.25 | 120.33 | 23.39 | 1.67 | 23.40 |
April | 208.00 | 23.18 | 132.67 | 23.49 | 0.00 | 23.49 |
May | 64.00 | 23.44 | 433.00 | 23.89 | 17.00 | 23.89 |
June | 125.50 | 23.97 | 647.83 | 23.97 | 120.83 | 23.97 |
July | 236.17 | 24.00 | 743.00 | 23.98 | 236.17 | 23.98 |
August | 139.50 | 24.00 | 739.00 | 23.96 | 139.50 | 23.97 |
September | 109.67 | 23.93 | 632.50 | 23.94 | 102.17 | 23.95 |
October | 194.50 | 23.18 | 258.67 | 23.63 | 11.00 | 23.64 |
November | 337.33 | 23.13 | 47.67 | 23.23 | 0.00 | 23.23 |
December | 598.33 | 23.09 | 0.00 | 23.09 | 0.00 | 23.09 |
Annual Sum or Average | 3719.00 | 23.29 | 3754.67 | 23.63 | 628.33 | 23.65 |
Minimum of Months | 64.00 | 23.09 | 0.00 | 23.09 | 0.00 | 23.09 |
Maximum of Months | 653.50 | 24.00 | 743.00 | 23.98 | 236.17 | 23.98 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 505.00 | 23.24 | 9.17 | 23.25 | 0.00 | 23.25 |
February | 451.00 | 23.25 | 6.83 | 23.26 | 0.00 | 23.26 |
March | 274.50 | 23.30 | 195.33 | 23.57 | 0.00 | 23.57 |
April | 71.00 | 23.23 | 316.33 | 23.85 | 0.00 | 23.85 |
May | 16.00 | 23.87 | 557.17 | 23.97 | 12.50 | 23.97 |
June | 111.33 | 23.99 | 698.17 | 23.98 | 111.00 | 23.99 |
July | 223.17 | 24.00 | 744.00 | 23.99 | 223.17 | 23.99 |
August | 127.00 | 24.00 | 744.00 | 23.98 | 127.00 | 23.98 |
September | 92.83 | 24.00 | 692.67 | 23.97 | 92.83 | 23.97 |
October | 73.33 | 23.29 | 388.67 | 23.86 | 5.67 | 23.86 |
November | 187.17 | 23.18 | 166.00 | 23.55 | 0.00 | 23.55 |
December | 421.00 | 23.15 | 32.00 | 23.21 | 0.00 | 23.21 |
Annual Sum or Average | 2553.33 | 23.40 | 4550.33 | 23.77 | 572.17 | 23.78 |
Minimum of Months | 16.00 | 23.15 | 6.83 | 23.21 | 0.00 | 23.21 |
Maximum of Months | 505.00 | 24.00 | 744.00 | 23.99 | 223.17 | 23.99 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 507.00 | 23.72 | 592.17 | 23.85 | 427.50 | 23.89 |
February | 470.33 | 23.70 | 532.83 | 23.83 | 392.33 | 23.88 |
March | 527.17 | 23.86 | 648.67 | 23.89 | 487.00 | 23.92 |
April | 503.33 | 23.98 | 686.50 | 23.91 | 500.83 | 23.94 |
May | 536.83 | 23.99 | 740.00 | 23.93 | 536.83 | 23.95 |
June | 552.33 | 23.99 | 720.00 | 23.96 | 552.33 | 23.97 |
July | 593.67 | 23.99 | 744.00 | 23.97 | 593.67 | 23.98 |
August | 580.33 | 23.99 | 744.00 | 23.97 | 580.33 | 23.98 |
September | 535.33 | 23.99 | 720.00 | 23.95 | 535.33 | 23.96 |
October | 520.50 | 23.99 | 717.67 | 23.92 | 520.50 | 23.94 |
November | 488.33 | 23.97 | 653.67 | 23.93 | 484.00 | 23.94 |
December | 496.17 | 23.77 | 609.00 | 23.86 | 435.83 | 23.90 |
Annual Sum or Average | 6311.33 | 23.92 | 8108.50 | 23.92 | 6046.50 | 23.94 |
Minimum of Months | 470.33 | 23.70 | 532.83 | 23.83 | 392.33 | 23.88 |
Maximum of Months | 593.67 | 23.99 | 744.00 | 23.97 | 593.67 | 23.98 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.00 | 457.33 | 21.00 | 457.33 | 21.00 |
February | 672.00 | 21.00 | 421.17 | 21.00 | 421.17 | 21.00 |
March | 744.00 | 21.15 | 153.50 | 21.13 | 153.50 | 21.11 |
April | 720.00 | 21.39 | 0.33 | 21.39 | 0.33 | 21.39 |
May | 744.00 | 22.13 | 0.00 | 22.13 | 0.00 | 22.13 |
June | 531.83 | 22.79 | 56.67 | 22.89 | 0.00 | 22.89 |
July | 191.83 | 23.04 | 314.67 | 23.52 | 0.00 | 23.52 |
August | 362.67 | 22.96 | 154.17 | 23.22 | 0.00 | 23.22 |
September | 674.67 | 22.52 | 6.17 | 22.53 | 0.00 | 22.53 |
October | 744.00 | 21.44 | 0.00 | 21.44 | 0.00 | 21.44 |
November | 720.00 | 21.08 | 2.33 | 21.08 | 2.33 | 21.08 |
December | 744.00 | 21.00 | 324.00 | 21.00 | 324.00 | 21.00 |
Annual Sum or Average | 7593.00 | 21.62 | 1890.33 | 21.65 | 1358.67 | 21.57 |
Minimum of Months | 191.83 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
Maximum of Months | 744.00 | 23.04 | 457.33 | 23.52 | 457.33 | 23.52 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.19676 | 22.80559 | 0.01575 | 5.15301 |
February | 672.00000 | 22.94249 | 23.24752 | -0.0456 | 5.20187 |
March | 744.00000 | 22.38641 | 31.14953 | -0.1347 | 5.58338 |
April | 720.00000 | 22.20937 | 34.86885 | -0.1561 | 5.68636 |
May | 744.00000 | 22.13140 | 40.80328 | -1.2367 | 37.23155 |
June | 720.00000 | 22.62119 | 51.96903 | -0.9869 | 25.87985 |
July | 744.00000 | 23.00931 | 59.25034 | -0.7955 | 18.58659 |
August | 744.00000 | 23.50906 | 54.46191 | -0.6426 | 13.92991 |
September | 720.00000 | 23.78151 | 48.39816 | -0.5793 | 12.26426 |
October | 744.00000 | 23.87985 | 36.50913 | 0.29549 | 6.91393 |
November | 720.00000 | 23.85363 | 30.60105 | 0.24501 | 6.32250 |
December | 744.00000 | 23.66074 | 25.34108 | 0.15407 | 5.62505 |
Annual Sum or Average | 8760.00000 | 23.09956 | 38.37258 | -0.3240 | 12.42183 |
Minimum of Months | 672.00000 | 22.13140 | 22.80559 | -1.2367 | 5.15301 |
Maximum of Months | 744.00000 | 23.87985 | 59.25034 | 0.29549 | 37.23155 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.06482 | 23.53467 | -0.5946 | 12.84924 |
February | 672.00000 | 21.07355 | 23.76653 | -0.5838 | 12.64635 |
March | 744.00000 | 21.31395 | 31.32237 | -0.3757 | 9.28346 |
April | 720.00000 | 21.37049 | 35.05650 | -0.3053 | 7.99433 |
May | 744.00000 | 21.61969 | 40.59264 | -1.2669 | 39.91409 |
June | 720.00000 | 22.27742 | 51.48646 | -0.9207 | 24.98856 |
July | 744.00000 | 22.79820 | 58.81726 | -0.6648 | 15.98612 |
August | 744.00000 | 22.72881 | 55.60096 | -0.7110 | 17.92812 |
September | 720.00000 | 22.22107 | 51.48875 | -0.9439 | 26.96295 |
October | 744.00000 | 21.51695 | 40.12647 | -0.2204 | 7.68341 |
November | 720.00000 | 21.18369 | 33.79868 | -0.4088 | 9.27280 |
December | 744.00000 | 21.06542 | 27.20967 | -0.5764 | 12.42838 |
Annual Sum or Average | 8760.00000 | 21.69036 | 39.48959 | -0.6313 | 16.51757 |
Minimum of Months | 672.00000 | 21.06482 | 23.53467 | -1.2669 | 7.68341 |
Maximum of Months | 744.00000 | 22.79820 | 58.81726 | -0.2204 | 39.91409 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.36916 | 25.51956 | -0.4084 | 8.76100 |
February | 672.00000 | 21.36172 | 25.75807 | -0.4087 | 8.76839 |
March | 744.00000 | 21.99395 | 32.45188 | -0.1935 | 6.52001 |
April | 720.00000 | 22.34742 | 35.58090 | -0.0820 | 5.61180 |
May | 744.00000 | 22.82184 | 40.39643 | -0.9377 | 24.20830 |
June | 720.00000 | 23.32218 | 50.97633 | -0.6744 | 15.33492 |
July | 744.00000 | 23.56380 | 58.47670 | -0.5271 | 11.19985 |
August | 744.00000 | 23.54635 | 55.30682 | -0.5567 | 11.92194 |
September | 720.00000 | 23.24677 | 50.93848 | -0.7056 | 16.18650 |
October | 744.00000 | 22.57663 | 40.21974 | 0.00905 | 5.56547 |
November | 720.00000 | 22.07694 | 34.57225 | -0.1613 | 5.96860 |
December | 744.00000 | 21.42562 | 29.01703 | -0.3726 | 8.23709 |
Annual Sum or Average | 8760.00000 | 22.47711 | 40.01725 | -0.4185 | 10.70519 |
Minimum of Months | 672.00000 | 21.36172 | 25.51956 | -0.9377 | 5.56547 |
Maximum of Months | 744.00000 | 23.56380 | 58.47670 | 0.00905 | 24.20830 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.86159 | 19.32914 | 0.49483 | 12.90227 |
February | 672.00000 | 22.85332 | 19.56323 | 0.49375 | 12.91607 |
March | 744.00000 | 22.93643 | 26.48943 | 0.59967 | 15.43580 |
April | 720.00000 | 22.97725 | 29.82576 | 0.65344 | 16.61075 |
May | 744.00000 | 23.01183 | 35.24305 | -0.0000 | 10.26063 |
June | 720.00000 | 23.03142 | 47.08583 | 0.12357 | 10.46171 |
July | 744.00000 | 23.04618 | 55.45716 | 0.20214 | 10.71498 |
August | 744.00000 | 23.04424 | 52.15484 | 0.17602 | 10.64310 |
September | 720.00000 | 23.04203 | 46.74689 | 0.10696 | 10.37127 |
October | 744.00000 | 23.02204 | 34.67759 | 0.70360 | 18.00321 |
November | 720.00000 | 22.98718 | 28.42022 | 0.62874 | 15.91500 |
December | 744.00000 | 22.86755 | 22.61433 | 0.51981 | 13.45032 |
Annual Sum or Average | 8760.00000 | 22.97401 | 34.89058 | 0.39119 | 13.14009 |
Minimum of Months | 672.00000 | 22.85332 | 19.32914 | -0.0000 | 10.26063 |
Maximum of Months | 744.00000 | 23.04618 | 55.45716 | 0.70360 | 18.00321 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.37940 | 28.60637 | -0.4111 | 9.19912 |
February | 672.00000 | 21.38703 | 28.81940 | -0.4012 | 9.09596 |
March | 744.00000 | 22.11092 | 35.61725 | -0.1012 | 6.73816 |
April | 720.00000 | 22.32539 | 38.90074 | -0.0063 | 6.09145 |
May | 744.00000 | 22.74871 | 43.85361 | -0.8220 | 20.62237 |
June | 720.00000 | 23.18730 | 54.58530 | -0.5487 | 12.59642 |
July | 744.00000 | 23.46679 | 61.98721 | -0.3652 | 8.51692 |
August | 744.00000 | 23.47200 | 58.78667 | -0.3863 | 9.21634 |
September | 720.00000 | 23.24762 | 54.17441 | -0.5266 | 12.70376 |
October | 744.00000 | 22.53559 | 43.51656 | 0.09336 | 6.83822 |
November | 720.00000 | 22.00660 | 37.88862 | -0.1293 | 6.51387 |
December | 744.00000 | 21.39532 | 32.13007 | -0.3903 | 8.93451 |
Annual Sum or Average | 8760.00000 | 22.44442 | 43.32286 | -0.3327 | 9.76407 |
Minimum of Months | 672.00000 | 21.37940 | 28.60637 | -0.8220 | 6.09145 |
Maximum of Months | 744.00000 | 23.47200 | 61.98721 | 0.09336 | 20.62237 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.83857 | 27.81445 | -0.2710 | 7.05005 |
February | 672.00000 | 21.83123 | 28.03591 | -0.2709 | 7.03750 |
March | 744.00000 | 22.47883 | 34.65339 | -0.0446 | 5.83631 |
April | 720.00000 | 22.74761 | 37.78411 | 0.05066 | 5.60051 |
May | 744.00000 | 23.12939 | 42.64469 | -0.7797 | 18.59100 |
June | 720.00000 | 23.44192 | 53.35073 | -0.5707 | 12.57816 |
July | 744.00000 | 23.59586 | 60.86784 | -0.4471 | 9.56215 |
August | 744.00000 | 23.61079 | 57.63307 | -0.4655 | 9.93388 |
September | 720.00000 | 23.48447 | 52.99814 | -0.5608 | 12.23091 |
October | 744.00000 | 23.00316 | 42.25445 | 0.15281 | 6.12657 |
November | 720.00000 | 22.54563 | 36.69159 | -0.0157 | 5.64219 |
December | 744.00000 | 21.87692 | 31.21636 | -0.2396 | 6.81888 |
Annual Sum or Average | 8760.00000 | 22.80384 | 42.24481 | -0.2888 | 8.93175 |
Minimum of Months | 672.00000 | 21.83123 | 27.81445 | -0.7797 | 5.60051 |
Maximum of Months | 744.00000 | 23.61079 | 60.86784 | 0.15281 | 18.59100 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.62480 | 37.57640 | -0.6886 | 15.43582 |
February | 672.00000 | 20.66838 | 37.65934 | -0.6692 | 14.90540 |
March | 744.00000 | 21.15723 | 42.94399 | -0.4327 | 9.72283 |
April | 720.00000 | 21.38339 | 46.06103 | -0.3095 | 7.83988 |
May | 744.00000 | 21.61828 | 48.18884 | -1.2932 | 41.10214 |
June | 720.00000 | 21.71099 | 51.28505 | -1.1417 | 34.01666 |
July | 744.00000 | 21.73032 | 53.41409 | -1.0878 | 31.58499 |
August | 744.00000 | 21.71635 | 53.15452 | -1.1153 | 32.86181 |
September | 720.00000 | 21.66394 | 54.24715 | -1.2052 | 36.96949 |
October | 744.00000 | 21.35657 | 50.74833 | -0.2941 | 7.55672 |
November | 720.00000 | 21.02766 | 46.09905 | -0.4690 | 10.17650 |
December | 744.00000 | 20.62825 | 41.11988 | -0.6662 | 14.85025 |
Annual Sum or Average | 8760.00000 | 21.27693 | 46.92262 | -0.7819 | 21.46295 |
Minimum of Months | 672.00000 | 20.62480 | 37.57640 | -1.2932 | 7.55672 |
Maximum of Months | 744.00000 | 21.73032 | 54.24715 | -0.2941 | 41.10214 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.51897 | 37.84434 | -0.7320 | 16.78801 |
February | 672.00000 | 20.54370 | 37.96022 | -0.7163 | 16.27026 |
March | 744.00000 | 20.93681 | 43.59379 | -0.5083 | 11.33261 |
April | 720.00000 | 21.28761 | 46.38560 | -0.3506 | 8.29228 |
May | 744.00000 | 21.96067 | 47.67798 | -1.2156 | 38.97669 |
June | 720.00000 | 22.61762 | 50.33541 | -0.8871 | 27.16280 |
July | 744.00000 | 22.47377 | 53.73524 | -0.8757 | 24.92159 |
August | 744.00000 | 22.42021 | 53.39635 | -0.9259 | 26.79995 |
September | 720.00000 | 22.18920 | 54.74561 | -1.0830 | 32.89249 |
October | 744.00000 | 21.25183 | 51.54220 | -0.3423 | 8.14527 |
November | 720.00000 | 20.83709 | 46.63976 | -0.5302 | 11.23235 |
December | 744.00000 | 20.53760 | 41.36831 | -0.7019 | 15.88712 |
Annual Sum or Average | 8760.00000 | 21.46922 | 47.15064 | -0.7396 | 19.92152 |
Minimum of Months | 672.00000 | 20.51897 | 37.84434 | -1.2156 | 8.14527 |
Maximum of Months | 744.00000 | 22.61762 | 54.74561 | -0.3423 | 38.97669 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.82355 | 34.50268 | -0.5923 | 12.65137 |
February | 672.00000 | 20.85251 | 34.67166 | -0.5833 | 12.35521 |
March | 744.00000 | 21.11469 | 40.23137 | -0.4514 | 9.80861 |
April | 720.00000 | 21.33105 | 43.44539 | -0.3485 | 7.76661 |
May | 744.00000 | 21.68479 | 45.24001 | -1.3600 | 43.87950 |
June | 720.00000 | 22.12055 | 50.94767 | -1.1365 | 33.60781 |
July | 744.00000 | 22.21426 | 55.68378 | -1.0567 | 30.32125 |
August | 744.00000 | 22.14464 | 54.18453 | -1.1052 | 32.18909 |
September | 720.00000 | 21.88519 | 52.94231 | -1.2381 | 38.10302 |
October | 744.00000 | 21.34174 | 47.90296 | -0.3177 | 7.33512 |
November | 720.00000 | 21.11976 | 43.07317 | -0.4283 | 8.94730 |
December | 744.00000 | 20.85274 | 37.97422 | -0.5615 | 11.92349 |
Annual Sum or Average | 8760.00000 | 21.46037 | 45.12430 | -0.7662 | 20.79466 |
Minimum of Months | 672.00000 | 20.82355 | 34.50268 | -1.3600 | 7.33512 |
Maximum of Months | 744.00000 | 22.21426 | 55.68378 | -0.3177 | 43.87950 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.63725 | 37.51381 | -0.6810 | 15.19882 |
February | 672.00000 | 20.69725 | 37.57964 | -0.6588 | 14.59137 |
March | 744.00000 | 21.21752 | 42.71424 | -0.4207 | 9.50694 |
April | 720.00000 | 21.46343 | 45.80435 | -0.2878 | 7.67053 |
May | 744.00000 | 21.65942 | 47.64436 | -1.2810 | 40.56977 |
June | 720.00000 | 21.73192 | 50.88754 | -1.1450 | 34.21601 |
July | 744.00000 | 21.74677 | 52.76760 | -1.0842 | 31.48941 |
August | 744.00000 | 21.73658 | 52.60713 | -1.1115 | 32.74069 |
September | 720.00000 | 21.68830 | 53.54919 | -1.1961 | 36.59189 |
October | 744.00000 | 21.41328 | 50.30486 | -0.2791 | 7.42664 |
November | 720.00000 | 21.03210 | 46.04223 | -0.4661 | 10.13421 |
December | 744.00000 | 20.62311 | 41.11532 | -0.6665 | 14.85958 |
Annual Sum or Average | 8760.00000 | 21.30698 | 46.59018 | -0.7741 | 21.29448 |
Minimum of Months | 672.00000 | 20.62311 | 37.51381 | -1.2810 | 7.42664 |
Maximum of Months | 744.00000 | 21.74677 | 53.54919 | -0.2791 | 40.56977 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.52829 | 37.79503 | -0.7252 | 16.57634 |
February | 672.00000 | 20.56016 | 37.90267 | -0.7084 | 16.00684 |
March | 744.00000 | 20.99227 | 43.32720 | -0.4976 | 11.04832 |
April | 720.00000 | 21.39777 | 46.03562 | -0.3232 | 7.94129 |
May | 744.00000 | 21.88737 | 47.31159 | -1.2369 | 38.55209 |
June | 720.00000 | 22.39278 | 50.63270 | -0.9610 | 27.59981 |
July | 744.00000 | 22.51020 | 53.37952 | -0.8648 | 24.78633 |
August | 744.00000 | 22.42125 | 52.95746 | -0.9275 | 26.51675 |
September | 720.00000 | 22.08778 | 54.20369 | -1.1107 | 32.97076 |
October | 744.00000 | 21.30635 | 51.05563 | -0.3279 | 7.82577 |
November | 720.00000 | 20.84008 | 46.59216 | -0.5271 | 11.20881 |
December | 744.00000 | 20.53826 | 41.34053 | -0.7015 | 15.90099 |
Annual Sum or Average | 8760.00000 | 21.46011 | 46.92432 | -0.7431 | 19.77320 |
Minimum of Months | 672.00000 | 20.52829 | 37.79503 | -1.2369 | 7.82577 |
Maximum of Months | 744.00000 | 22.51020 | 54.20369 | -0.3232 | 38.55209 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.54323 | 38.42412 | -0.7518 | 17.41977 |
February | 672.00000 | 20.58298 | 38.49358 | -0.7322 | 16.82551 |
March | 744.00000 | 21.04656 | 44.13376 | -0.4839 | 10.91122 |
April | 720.00000 | 21.32476 | 47.16565 | -0.3379 | 8.44176 |
May | 744.00000 | 21.59773 | 49.12321 | -1.3070 | 42.00501 |
June | 720.00000 | 21.70276 | 52.18101 | -1.1407 | 34.19221 |
July | 744.00000 | 21.72594 | 54.42352 | -1.0807 | 31.48241 |
August | 744.00000 | 21.70753 | 54.40795 | -1.1141 | 33.02989 |
September | 720.00000 | 21.64040 | 55.94555 | -1.2189 | 37.83078 |
October | 744.00000 | 21.28033 | 52.26947 | -0.3281 | 8.15684 |
November | 720.00000 | 20.91562 | 47.36840 | -0.5215 | 11.40332 |
December | 744.00000 | 20.55745 | 42.09661 | -0.7248 | 16.63081 |
Annual Sum or Average | 8760.00000 | 21.22206 | 48.05172 | -0.8125 | 22.39965 |
Minimum of Months | 672.00000 | 20.54323 | 38.42412 | -1.3070 | 8.15684 |
Maximum of Months | 744.00000 | 21.72594 | 55.94555 | -0.3281 | 42.00501 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.48377 | 38.63664 | -0.7867 | 18.58854 |
February | 672.00000 | 20.49841 | 38.73961 | -0.7723 | 18.07588 |
March | 744.00000 | 20.83795 | 44.79543 | -0.5590 | 12.69525 |
April | 720.00000 | 21.22764 | 47.52090 | -0.3807 | 8.96221 |
May | 744.00000 | 21.99545 | 48.47503 | -1.2102 | 39.71867 |
June | 720.00000 | 22.69722 | 50.60393 | -0.8523 | 27.50237 |
July | 744.00000 | 22.50067 | 54.18791 | -0.8542 | 24.91705 |
August | 744.00000 | 22.43997 | 54.13433 | -0.9119 | 27.12378 |
September | 720.00000 | 22.21238 | 56.15735 | -1.0796 | 33.61686 |
October | 744.00000 | 21.16057 | 53.14077 | -0.3813 | 8.92869 |
November | 720.00000 | 20.71334 | 47.97721 | -0.5866 | 12.66606 |
December | 744.00000 | 20.49191 | 42.31431 | -0.7562 | 17.62031 |
Annual Sum or Average | 8760.00000 | 21.44299 | 48.10605 | -0.7612 | 20.89291 |
Minimum of Months | 672.00000 | 20.48377 | 38.63664 | -1.2102 | 8.92869 |
Maximum of Months | 744.00000 | 22.69722 | 56.15735 | -0.3807 | 39.71867 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.92467 | 38.26701 | -0.5872 | 13.15063 |
February | 672.00000 | 20.94224 | 38.34936 | -0.5792 | 12.82682 |
March | 744.00000 | 21.37974 | 43.13721 | -0.3571 | 8.81572 |
April | 720.00000 | 21.47039 | 46.31449 | -0.2881 | 7.79211 |
May | 744.00000 | 21.61762 | 48.29408 | -1.3257 | 42.83730 |
June | 720.00000 | 21.69011 | 52.52699 | -1.2098 | 37.21651 |
July | 744.00000 | 21.72024 | 54.86893 | -1.1400 | 33.98855 |
August | 744.00000 | 21.70836 | 53.90393 | -1.1552 | 34.79393 |
September | 720.00000 | 21.68061 | 53.47226 | -1.2084 | 37.40888 |
October | 744.00000 | 21.50102 | 49.71616 | -0.2402 | 7.25993 |
November | 720.00000 | 21.23967 | 45.95164 | -0.3917 | 9.21984 |
December | 744.00000 | 20.84494 | 41.66572 | -0.5914 | 13.21828 |
Annual Sum or Average | 8760.00000 | 21.39562 | 47.25257 | -0.7574 | 21.60073 |
Minimum of Months | 672.00000 | 20.84494 | 38.26701 | -1.3257 | 7.25993 |
Maximum of Months | 744.00000 | 21.72024 | 54.86893 | -0.2402 | 42.83730 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.22275 | 28.89068 | 0.06855 | 5.95988 |
February | 672.00000 | 23.23567 | 29.13384 | 0.07346 | 5.90737 |
March | 744.00000 | 23.51071 | 35.08002 | 0.22275 | 6.85973 |
April | 720.00000 | 23.72099 | 37.57087 | 0.32368 | 7.50424 |
May | 744.00000 | 23.86718 | 41.93969 | -0.4452 | 9.44291 |
June | 720.00000 | 23.94183 | 52.44349 | -0.2906 | 7.02914 |
July | 744.00000 | 23.97144 | 60.04182 | -0.1988 | 5.89050 |
August | 744.00000 | 23.95329 | 57.13370 | -0.2421 | 6.33075 |
September | 720.00000 | 23.89065 | 52.69869 | -0.3459 | 7.78982 |
October | 744.00000 | 23.71049 | 42.24761 | 0.35599 | 8.02266 |
November | 720.00000 | 23.56423 | 36.78500 | 0.25338 | 6.78781 |
December | 744.00000 | 23.26199 | 31.93099 | 0.10320 | 6.12864 |
Annual Sum or Average | 8760.00000 | 23.65634 | 42.23531 | -0.0108 | 6.97650 |
Minimum of Months | 672.00000 | 23.22275 | 28.89068 | -0.4452 | 5.89050 |
Maximum of Months | 744.00000 | 23.97144 | 60.04182 | 0.35599 | 9.44291 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.47176 | 27.85912 | 0.16923 | 6.23474 |
February | 672.00000 | 23.48498 | 28.08950 | 0.17430 | 6.20487 |
March | 744.00000 | 23.70081 | 34.01278 | 0.30805 | 7.58639 |
April | 720.00000 | 23.85761 | 36.53269 | 0.39533 | 8.45997 |
May | 744.00000 | 23.94024 | 41.08791 | -0.3687 | 8.03772 |
June | 720.00000 | 23.97575 | 51.79487 | -0.2349 | 6.36717 |
July | 744.00000 | 23.98773 | 59.51035 | -0.1536 | 5.54525 |
August | 744.00000 | 23.97978 | 56.54936 | -0.1925 | 5.85444 |
September | 720.00000 | 23.94775 | 51.91553 | -0.2796 | 6.84553 |
October | 744.00000 | 23.84538 | 41.20408 | 0.42646 | 9.04324 |
November | 720.00000 | 23.74729 | 35.67166 | 0.33755 | 7.66411 |
December | 744.00000 | 23.50200 | 30.85845 | 0.20182 | 6.52254 |
Annual Sum or Average | 8760.00000 | 23.78819 | 41.33559 | 0.06451 | 7.03396 |
Minimum of Months | 672.00000 | 23.47176 | 27.85912 | -0.3687 | 5.54525 |
Maximum of Months | 744.00000 | 23.98773 | 59.51035 | 0.42646 | 9.04324 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.66919 | 26.23498 | 0.82668 | 22.16805 |
February | 672.00000 | 23.65747 | 26.41741 | 0.82885 | 22.36365 |
March | 744.00000 | 23.75189 | 32.46899 | 0.95837 | 27.07927 |
April | 720.00000 | 23.81333 | 35.30763 | 1.03701 | 29.90003 |
May | 744.00000 | 23.88164 | 40.19419 | 0.56443 | 16.27066 |
June | 720.00000 | 23.93331 | 50.98855 | 0.71946 | 20.03259 |
July | 744.00000 | 23.96047 | 58.63224 | 0.81432 | 22.65648 |
August | 744.00000 | 23.95134 | 55.64760 | 0.76925 | 21.29886 |
September | 720.00000 | 23.91111 | 50.81938 | 0.66427 | 18.53767 |
October | 744.00000 | 23.83616 | 39.86493 | 1.06995 | 31.14567 |
November | 720.00000 | 23.78200 | 34.24863 | 0.97373 | 27.21069 |
December | 744.00000 | 23.68238 | 29.21132 | 0.85207 | 22.97751 |
Annual Sum or Average | 8760.00000 | 23.82007 | 40.08355 | 0.83986 | 23.47426 |
Minimum of Months | 672.00000 | 23.65747 | 26.23498 | 0.56443 | 16.27066 |
Maximum of Months | 744.00000 | 23.96047 | 58.63224 | 1.06995 | 31.14567 |
Report: OccupantComfortDataSummaryMonthly
For: STORAGE_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.00014 | 22.67949 | -0.5685 | 11.83616 |
February | 672.00000 | 21.00014 | 22.88403 | -0.5698 | 11.85786 |
March | 744.00000 | 21.13665 | 30.46143 | -0.4554 | 9.81625 |
April | 720.00000 | 21.25636 | 34.21897 | -0.3856 | 8.30472 |
May | 744.00000 | 21.96857 | 38.79210 | -1.2820 | 39.58490 |
June | 720.00000 | 22.81906 | 49.17149 | -0.9160 | 23.26823 |
July | 744.00000 | 23.31081 | 56.35680 | -0.6936 | 15.34852 |
August | 744.00000 | 23.22649 | 53.20068 | -0.7453 | 16.91859 |
September | 720.00000 | 22.63174 | 49.35888 | -0.9812 | 25.83231 |
October | 744.00000 | 21.59730 | 38.95065 | -0.2656 | 6.87934 |
November | 720.00000 | 21.13030 | 32.91370 | -0.4287 | 8.97706 |
December | 744.00000 | 21.00060 | 26.37095 | -0.5408 | 11.20729 |
Annual Sum or Average | 8760.00000 | 21.84544 | 38.03238 | -0.6531 | 15.84332 |
Minimum of Months | 672.00000 | 21.00014 | 22.67949 | -1.2820 | 6.87934 |
Maximum of Months | 744.00000 | 23.31081 | 56.35680 | -0.2656 | 39.58490 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.00051 | 25.91234 | -0.5440 | 11.24485 |
February | 672.00000 | 21.00087 | 26.12520 | -0.5404 | 11.15382 |
March | 744.00000 | 21.11998 | 33.76412 | -0.4395 | 9.35119 |
April | 720.00000 | 21.35906 | 37.21402 | -0.3533 | 7.79765 |
May | 744.00000 | 22.05387 | 41.79708 | -1.2540 | 38.16778 |
June | 720.00000 | 22.86955 | 52.22993 | -0.8983 | 22.43547 |
July | 744.00000 | 23.27869 | 59.48726 | -0.7037 | 15.54237 |
August | 744.00000 | 23.19366 | 56.48788 | -0.7549 | 17.20015 |
September | 720.00000 | 22.60537 | 52.62866 | -0.9897 | 26.08963 |
October | 744.00000 | 21.42615 | 42.49773 | -0.3026 | 7.22143 |
November | 720.00000 | 21.06152 | 36.20935 | -0.4430 | 9.16872 |
December | 744.00000 | 21.00063 | 29.57916 | -0.5228 | 10.77909 |
Annual Sum or Average | 8760.00000 | 21.83608 | 41.24728 | -0.6461 | 15.53908 |
Minimum of Months | 672.00000 | 21.00051 | 25.91234 | -1.2540 | 7.22143 |
Maximum of Months | 744.00000 | 23.27869 | 59.48726 | -0.3026 | 38.16778 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.00177 | 23.71401 | -0.5584 | 11.60303 |
February | 672.00000 | 21.00200 | 23.94730 | -0.5554 | 11.52125 |
March | 744.00000 | 21.15407 | 31.48056 | -0.4280 | 9.35288 |
April | 720.00000 | 21.38790 | 34.99921 | -0.3286 | 7.57383 |
May | 744.00000 | 22.13365 | 39.37319 | -1.1814 | 34.86137 |
June | 720.00000 | 22.98968 | 49.49836 | -0.8042 | 19.51577 |
July | 744.00000 | 23.48857 | 56.47244 | -0.5734 | 12.28280 |
August | 744.00000 | 23.31618 | 53.74481 | -0.6567 | 14.62528 |
September | 720.00000 | 22.57601 | 50.38230 | -0.9507 | 24.91795 |
October | 744.00000 | 21.44115 | 40.24138 | -0.2804 | 7.10765 |
November | 720.00000 | 21.07768 | 34.00454 | -0.4299 | 8.97835 |
December | 744.00000 | 21.00265 | 27.39687 | -0.5344 | 11.06943 |
Annual Sum or Average | 8760.00000 | 21.88678 | 38.85528 | -0.6070 | 14.46616 |
Minimum of Months | 672.00000 | 21.00177 | 23.71401 | -1.1814 | 7.10765 |
Maximum of Months | 744.00000 | 23.48857 | 56.47244 | -0.2804 | 34.86137 |
Report: OccupantComfortDataSummaryMonthly
For: MECH_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.00961 | 22.29520 | -0.5498 | 11.39759 |
February | 672.00000 | 21.00814 | 22.50244 | -0.5517 | 11.42732 |
March | 744.00000 | 21.24967 | 29.85042 | -0.4227 | 9.32244 |
April | 720.00000 | 21.50931 | 33.35493 | -0.3285 | 7.52990 |
May | 744.00000 | 22.26987 | 37.77348 | -1.1899 | 35.07317 |
June | 720.00000 | 23.08664 | 48.07051 | -0.8336 | 20.23147 |
July | 744.00000 | 23.53879 | 55.23954 | -0.6227 | 13.37081 |
August | 744.00000 | 23.48487 | 52.03685 | -0.6647 | 14.51949 |
September | 720.00000 | 22.93897 | 48.13520 | -0.8861 | 22.10656 |
October | 744.00000 | 21.94680 | 37.82617 | -0.1891 | 6.15382 |
November | 720.00000 | 21.35508 | 32.12871 | -0.3747 | 8.13912 |
December | 744.00000 | 21.02133 | 25.96934 | -0.5207 | 10.76371 |
Annual Sum or Average | 8760.00000 | 22.04131 | 37.18211 | -0.5948 | 14.18852 |
Minimum of Months | 672.00000 | 21.00814 | 22.29520 | -1.1899 | 6.15382 |
Maximum of Months | 744.00000 | 23.53879 | 55.23954 | -0.1891 | 35.07317 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.204597E+09 | 8260.82 | 01-JAN-09:02 | 54.69 | 0.964964E+09 | 0.00 | 0.116956E+10 | 0.35 | 4.72 | 30-JAN-16:05 | 0.00 | 0.00 |
February | 0.201548E+09 | 7209.24 | 19-FEB-09:02 | 48.25 | 0.950585E+09 | 0.00 | 0.115213E+10 | 0.34 | 4.72 | 08-FEB-14:10 | 0.00 | 0.00 |
March | 0.739286E+10 | 85573.24 | 15-MAR-15:03 | 336.60 | 0.322459E+11 | 0.00 | 0.396388E+11 | 2.11 | 4.72 | 05-MAR-13:03 | 0.00 | 0.00 |
April | 0.926536E+10 | 54160.17 | 08-APR-15:03 | 514.08 | 0.429251E+11 | 0.00 | 0.521905E+11 | 3.35 | 4.72 | 05-APR-22:00 | 0.00 | 0.00 |
May | 0.331824E+11 | 92051.18 | 10-MAY-15:03 | 734.47 | 0.147706E+12 | 0.00 | 0.180889E+12 | 4.54 | 4.72 | 16-MAY-06:20 | 0.00 | 0.00 |
June | 0.100008E+12 | 156907.83 | 17-JUN-18:03 | 720.00 | 0.422490E+12 | 0.00 | 0.522498E+12 | 4.39 | 4.72 | 04-JUN-06:30 | 0.00 | 0.00 |
July | 0.174630E+12 | 172859.67 | 20-JUL-18:03 | 744.00 | 0.719860E+12 | 0.00 | 0.894489E+12 | 4.22 | 4.72 | 03-JUL-03:10 | 0.00 | 0.00 |
August | 0.133651E+12 | 152131.16 | 13-AUG-15:03 | 744.00 | 0.556178E+12 | 0.00 | 0.689829E+12 | 4.29 | 4.72 | 01-AUG-04:10 | 0.00 | 0.00 |
September | 0.691535E+11 | 132445.94 | 15-SEP-21:53 | 714.08 | 0.299730E+12 | 0.00 | 0.368883E+12 | 4.46 | 4.72 | 04-SEP-04:30 | 0.00 | 0.00 |
October | 0.147592E+11 | 76935.15 | 11-OCT-15:03 | 585.02 | 0.670160E+11 | 0.00 | 0.817753E+11 | 3.67 | 4.72 | 11-OCT-03:10 | 0.00 | 0.00 |
November | 0.418076E+10 | 42984.75 | 04-NOV-15:01 | 310.14 | 0.192220E+11 | 0.00 | 0.234027E+11 | 2.01 | 4.72 | 01-NOV-09:50 | 0.00 | 0.00 |
December | 0.243863E+09 | 8161.77 | 01-DEC-19:02 | 60.22 | 0.114983E+10 | 0.00 | 0.139369E+10 | 0.38 | 4.72 | 01-DEC-06:15 | 0.00 | 0.00 |
Annual Sum or Average | 0.546873E+12 | 5565.55 | 0.231044E+13 | 0.00 | 0.285731E+13 | 2.85 | 0.00 | 0.00 | ||||
Minimum of Months | 0.201548E+09 | 7209.24 | 48.25 | 0.950585E+09 | 0.00 | 0.115213E+10 | 0.34 | 4.72 | 0.00 | 0.00 | ||
Maximum of Months | 0.174630E+12 | 172859.67 | 744.00 | 0.719860E+12 | 0.00 | 0.894489E+12 | 4.54 | 4.72 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.190595E+12 | 0.00 | 744.00 | 201281.64 | 31-JAN-09:05 | 0.00 | 37.03 | 60.00 | 0.72 | 0.00 | 0.13 | 0.38 | 31-JAN-09:05 |
February | 0.180771E+12 | 0.00 | 672.00 | 238326.29 | 06-FEB-09:06 | 0.00 | 36.39 | 60.00 | 0.75 | 0.00 | 0.14 | 0.45 | 06-FEB-09:06 |
March | 0.997002E+11 | 0.00 | 706.11 | 156741.90 | 06-MAR-19:03 | 0.00 | 37.83 | 58.54 | 0.38 | 0.00 | 0.07 | 0.30 | 06-MAR-19:03 |
April | 0.624439E+11 | 0.00 | 639.73 | 140584.62 | 02-APR-15:04 | 0.00 | 37.27 | 56.41 | 0.23 | 0.00 | 0.05 | 0.26 | 02-APR-15:04 |
May | 0.622958E+11 | 0.00 | 429.48 | 122933.10 | 11-MAY-15:05 | 0.00 | 29.30 | 46.48 | 0.18 | 0.00 | 0.04 | 0.23 | 11-MAY-15:05 |
June | 0.195463E+11 | 0.00 | 148.34 | 107075.77 | 13-JUN-08:05 | 0.00 | 27.98 | 34.55 | 0.06 | 0.00 | 0.01 | 0.20 | 13-JUN-08:05 |
July | 0.304413E+10 | 0.00 | 37.16 | 47513.01 | 13-JUL-04:00 | 0.00 | 31.84 | 33.54 | 0.01 | 0.00 | 0.00 | 0.09 | 13-JUL-04:00 |
August | 0.651075E+10 | 0.00 | 77.08 | 59651.60 | 01-AUG-06:00 | 0.00 | 30.04 | 33.54 | 0.02 | 0.00 | 0.00 | 0.11 | 01-AUG-06:00 |
September | 0.356428E+11 | 0.00 | 253.84 | 111858.23 | 30-SEP-06:30 | 0.00 | 29.56 | 40.77 | 0.11 | 0.00 | 0.03 | 0.21 | 30-SEP-06:30 |
October | 0.805227E+11 | 0.00 | 622.64 | 138937.15 | 19-OCT-08:62 | 0.00 | 35.38 | 55.35 | 0.27 | 0.00 | 0.06 | 0.26 | 19-OCT-08:62 |
November | 0.705453E+11 | 0.00 | 703.70 | 167513.21 | 12-NOV-19:03 | 0.00 | 40.36 | 59.56 | 0.30 | 0.00 | 0.05 | 0.32 | 12-NOV-19:03 |
December | 0.168889E+12 | 0.00 | 744.00 | 218600.88 | 11-DEC-09:06 | 0.00 | 37.94 | 60.00 | 0.65 | 0.00 | 0.12 | 0.41 | 11-DEC-09:06 |
Annual Sum or Average | 0.980507E+12 | 0.00 | 5778.08 | 0.00 | 34.23 | 49.84 | 0.30 | 0.00 | 0.06 | ||||
Minimum of Months | 0.304413E+10 | 0.00 | 37.16 | 47513.01 | 0.00 | 27.98 | 33.54 | 0.01 | 0.00 | 0.00 | 0.09 | ||
Maximum of Months | 0.190595E+12 | 0.00 | 744.00 | 238326.29 | 0.00 | 40.36 | 60.00 | 0.75 | 0.00 | 0.14 | 0.45 |
Report: DXReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 |
March | 0.105566E+10 | 0.00 | 37.50 | 0.101810E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20597.44 | 14-MAR-12:15 | 17411.51 | 15-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.441673E+09 | 0.00 | 42.50 | 0.441673E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13334.54 | 08-APR-13:00 | 13334.54 | 08-APR-13:00 | 0.00 | 0.00 | 0.00 |
May | 0.484402E+10 | 0.00 | 220.67 | 0.463670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20799.01 | 10-MAY-15:02 | 17599.36 | 14-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.221055E+11 | 0.00 | 435.67 | 0.153086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 42305.96 | 18-JUN-08:62 | 19444.68 | 27-JUN-13:00 | 0.00 | 0.00 | 0.00 |
July | 0.401031E+11 | 0.00 | 556.00 | 0.246561E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 41895.96 | 17-JUL-18:03 | 19559.21 | 19-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.294595E+11 | 0.00 | 514.83 | 0.202800E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 40550.07 | 14-AUG-08:61 | 19208.19 | 13-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.146686E+11 | 0.00 | 355.50 | 0.100012E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 37049.81 | 15-SEP-20:00 | 18017.87 | 16-SEP-13:00 | 0.00 | 0.00 | 0.00 |
October | 0.151414E+10 | 0.00 | 101.17 | 0.151414E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14829.38 | 11-OCT-15:01 | 14829.38 | 11-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.566791E+09 | 0.00 | 41.67 | 0.566791E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8665.56 | 05-NOV-13:00 | 8665.56 | 05-NOV-13:00 | 0.00 | 0.00 | 0.00 |
December | 849913.39 | 0.00 | 0.67 | 849913.39 | 0.00 | 0.00 | 0.00 | 0.00 | 572.03 | 01-DEC-11:00 | 572.03 | 01-DEC-11:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.114760E+12 | 0.00 | 2306.17 | 0.784241E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.401031E+11 | 0.00 | 556.00 | 0.246561E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 42305.96 | 19559.21 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 338043.09 | 0.00 | 2.50 | 338043.09 | 0.00 | 0.00 | 0.00 | 0.00 | 103.29 | 23-JAN-02:70 | 103.29 | 23-JAN-02:70 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 |
March | 0.145278E+11 | 0.00 | 51.83 | 0.142819E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 205907.65 | 14-MAR-10:45 | 183484.87 | 15-MAR-18:10 | 0.00 | 0.00 | 0.00 |
April | 0.839677E+10 | 0.00 | 77.50 | 0.839677E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 104138.67 | 08-APR-13:00 | 104138.67 | 08-APR-13:00 | 0.00 | 0.00 | 0.00 |
May | 0.684660E+11 | 0.00 | 336.08 | 0.673118E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 182921.32 | 10-MAY-15:30 | 167688.62 | 23-MAY-18:03 | 0.00 | 0.00 | 0.00 |
June | 0.278497E+12 | 0.00 | 574.85 | 0.205124E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 514969.43 | 27-JUN-20:04 | 211278.42 | 17-JUN-17:15 | 0.00 | 0.00 | 0.00 |
July | 0.517479E+12 | 0.00 | 709.83 | 0.328081E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 513583.00 | 21-JUL-20:04 | 243556.83 | 20-JUL-19:10 | 0.00 | 0.00 | 0.00 |
August | 0.379345E+12 | 0.00 | 671.00 | 0.276101E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 451679.04 | 14-AUG-22:00 | 233936.38 | 10-AUG-21:00 | 0.00 | 0.00 | 0.00 |
September | 0.183876E+12 | 0.00 | 482.04 | 0.136664E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 424208.73 | 15-SEP-20:20 | 196690.07 | 16-SEP-21:00 | 0.00 | 0.00 | 0.00 |
October | 0.227346E+11 | 0.00 | 143.25 | 0.227346E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 132621.08 | 11-OCT-15:15 | 132621.08 | 11-OCT-15:15 | 0.00 | 0.00 | 0.00 |
November | 0.720306E+10 | 0.00 | 60.17 | 0.720306E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79919.23 | 05-NOV-10:45 | 79919.23 | 05-NOV-10:45 | 0.00 | 0.00 | 0.00 |
December | 9040451.82 | 0.00 | 0.78 | 9040451.82 | 0.00 | 0.00 | 0.00 | 0.00 | 6525.92 | 01-DEC-11:35 | 6525.92 | 01-DEC-11:35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.148053E+13 | 0.00 | 3109.83 | 0.106591E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.517479E+12 | 0.00 | 709.83 | 0.328081E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 514969.43 | 243556.83 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 9168842.12 | 0.00 | 2.06 | 5660350.46 | 0.00 | 0.00 | 0.00 | 0.00 | 12549.94 | 15-JAN-16:01 | 12549.94 | 15-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 34949429.23 | 0.00 | 7.15 | 29843659.68 | 0.00 | 0.00 | 0.00 | 0.00 | 16624.63 | 28-FEB-16:01 | 16624.63 | 28-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.704715E+09 | 0.00 | 121.69 | 0.454767E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16629.73 | 25-MAR-15:01 | 16629.73 | 25-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.152344E+10 | 0.00 | 241.88 | 0.950491E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16627.66 | 17-APR-15:01 | 16627.66 | 17-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.397971E+10 | 0.00 | 548.57 | 0.234668E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16985.17 | 17-MAY-15:01 | 16632.90 | 20-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.797928E+10 | 0.00 | 663.50 | 0.445103E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18314.98 | 08-JUN-08:62 | 16630.71 | 15-JUN-18:01 | 0.00 | 0.00 | 0.00 |
July | 0.101385E+11 | 0.00 | 703.55 | 0.553522E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18344.25 | 29-JUL-08:61 | 15066.47 | 21-JUL-08:61 | 0.00 | 0.00 | 0.00 |
August | 0.902738E+10 | 0.00 | 692.54 | 0.493855E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18043.91 | 14-AUG-08:61 | 15030.51 | 18-AUG-08:61 | 0.00 | 0.00 | 0.00 |
September | 0.539363E+10 | 0.00 | 617.34 | 0.257557E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18100.59 | 13-SEP-18:01 | 14956.78 | 15-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.128945E+10 | 0.00 | 260.97 | 0.569638E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17233.64 | 01-OCT-08:62 | 14748.99 | 04-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.115419E+09 | 0.00 | 40.36 | 46987661.77 | 0.00 | 0.00 | 0.00 | 0.00 | 15687.14 | 04-NOV-15:01 | 13833.70 | 14-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 4835728.48 | 0.00 | 0.96 | 3830820.49 | 0.00 | 0.00 | 0.00 | 0.00 | 14008.77 | 04-DEC-16:02 | 14008.77 | 04-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.402004E+11 | 0.00 | 3900.57 | 0.219083E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4835728.48 | 0.00 | 0.96 | 3830820.49 | 0.00 | 0.00 | 0.00 | 0.00 | 12549.94 | 12549.94 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.101385E+11 | 0.00 | 703.55 | 0.553522E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18344.25 | 16632.90 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 985643.07 | 0.00 | 0.29 | 374769.12 | 0.00 | 0.00 | 0.00 | 0.00 | 3463.28 | 15-JAN-16:01 | 2018.54 | 15-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 5647898.61 | 0.00 | 1.95 | 4637152.37 | 0.00 | 0.00 | 0.00 | 0.00 | 9821.21 | 28-FEB-16:01 | 9821.21 | 28-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.304729E+09 | 0.00 | 69.19 | 0.170075E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16439.15 | 14-MAR-15:01 | 15882.00 | 28-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.905528E+09 | 0.00 | 164.81 | 0.530122E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17809.96 | 19-APR-18:11 | 17809.96 | 19-APR-18:11 | 0.00 | 0.00 | 0.00 |
May | 0.255619E+10 | 0.00 | 411.18 | 0.134465E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18165.10 | 03-MAY-18:01 | 18165.10 | 03-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.575391E+10 | 0.00 | 479.92 | 0.310413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20446.82 | 18-JUN-08:21 | 15635.70 | 24-JUN-21:51 | 0.00 | 0.00 | 0.00 |
July | 0.793029E+10 | 0.00 | 524.61 | 0.447873E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20487.50 | 16-JUL-08:21 | 15953.06 | 06-JUL-21:51 | 0.00 | 0.00 | 0.00 |
August | 0.653946E+10 | 0.00 | 507.25 | 0.353526E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20179.61 | 14-AUG-08:21 | 16135.25 | 02-AUG-21:51 | 0.00 | 0.00 | 0.00 |
September | 0.284487E+10 | 0.00 | 425.13 | 0.110729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17917.65 | 15-SEP-21:51 | 14847.60 | 11-SEP-19:31 | 0.00 | 0.00 | 0.00 |
October | 0.417823E+09 | 0.00 | 127.10 | 0.153363E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16661.66 | 01-OCT-08:62 | 14443.92 | 22-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 21880168.20 | 0.00 | 9.01 | 10235781.90 | 0.00 | 0.00 | 0.00 | 0.00 | 13800.95 | 05-NOV-15:01 | 12693.17 | 14-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 633692.73 | 0.00 | 0.28 | 264518.19 | 0.00 | 0.00 | 0.00 | 0.00 | 2437.12 | 01-DEC-19:05 | 1396.20 | 04-DEC-16:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.272819E+11 | 0.00 | 2720.72 | 0.144391E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 633692.73 | 0.00 | 0.28 | 264518.19 | 0.00 | 0.00 | 0.00 | 0.00 | 2437.12 | 1396.20 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.793029E+10 | 0.00 | 524.61 | 0.447873E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20487.50 | 18165.10 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 |
March | 0.339702E+10 | 0.00 | 112.77 | 0.167305E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41451.63 | 15-MAR-13:30 | 29412.52 | 15-MAR-13:30 | 0.00 | 0.00 | 0.00 |
April | 0.993089E+10 | 0.00 | 284.95 | 0.728227E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31583.18 | 22-APR-13:00 | 31583.18 | 22-APR-13:00 | 0.00 | 0.00 | 0.00 |
May | 0.219075E+11 | 0.00 | 561.68 | 0.103185E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 30209.42 | 14-MAY-13:15 | 27052.71 | 05-MAY-13:30 | 0.00 | 0.00 | 0.00 |
June | 0.344396E+11 | 0.00 | 681.38 | 0.128544E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 34761.39 | 27-JUN-13:00 | 21087.09 | 12-JUN-13:10 | 0.00 | 0.00 | 0.00 |
July | 0.471008E+11 | 0.00 | 743.50 | 0.193918E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 39114.03 | 30-JUL-12:30 | 26987.62 | 21-JUL-13:30 | 0.00 | 0.00 | 0.00 |
August | 0.467554E+11 | 0.00 | 738.39 | 0.207455E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 44000.29 | 18-AUG-13:30 | 35122.10 | 18-AUG-13:30 | 0.00 | 0.00 | 0.00 |
September | 0.379538E+11 | 0.00 | 652.94 | 0.177556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 54111.00 | 21-SEP-13:00 | 51255.06 | 21-SEP-12:00 | 0.00 | 0.00 | 0.00 |
October | 0.175918E+11 | 0.00 | 407.47 | 0.977417E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55542.68 | 11-OCT-12:30 | 51370.51 | 31-OCT-12:30 | 0.00 | 0.00 | 0.00 |
November | 0.335997E+10 | 0.00 | 117.11 | 0.224833E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31703.93 | 03-NOV-12:30 | 31703.93 | 03-NOV-12:30 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.222437E+12 | 0.00 | 4300.20 | 0.102044E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.471008E+11 | 0.00 | 743.50 | 0.207455E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 55542.68 | 51370.51 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.117800E+09 | 0.00 | 12.17 | 64018015.27 | 0.00 | 0.00 | 0.00 | 0.00 | 61557.12 | 15-JAN-09:02 | 61557.12 | 15-JAN-09:02 | 0.00 | 0.00 | 0.00 |
February | 94390571.65 | 0.00 | 9.21 | 77345743.16 | 0.00 | 0.00 | 0.00 | 0.00 | 61682.92 | 20-FEB-09:02 | 61682.92 | 20-FEB-09:02 | 0.00 | 0.00 | 0.00 |
March | 0.554412E+10 | 0.00 | 159.90 | 0.272399E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 86524.36 | 14-MAR-15:01 | 83180.82 | 22-MAR-18:02 | 0.00 | 0.00 | 0.00 |
April | 0.106562E+11 | 0.00 | 343.38 | 0.588415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 87203.27 | 22-APR-18:01 | 87203.27 | 22-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.252850E+11 | 0.00 | 447.54 | 0.154963E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 92240.40 | 17-MAY-18:01 | 89794.87 | 27-MAY-21:41 | 0.00 | 0.00 | 0.00 |
June | 0.410297E+11 | 0.00 | 421.22 | 0.255538E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 112708.63 | 18-JUN-08:21 | 93231.58 | 03-JUN-20:41 | 0.00 | 0.00 | 0.00 |
July | 0.544687E+11 | 0.00 | 472.03 | 0.338215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 112782.61 | 16-JUL-08:21 | 81449.35 | 12-JUL-21:51 | 0.00 | 0.00 | 0.00 |
August | 0.462865E+11 | 0.00 | 452.25 | 0.278703E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 111733.78 | 14-AUG-08:21 | 82687.00 | 01-AUG-21:51 | 0.00 | 0.00 | 0.00 |
September | 0.282288E+11 | 0.00 | 393.75 | 0.147953E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 101365.58 | 15-SEP-21:51 | 80595.53 | 01-SEP-15:01 | 0.00 | 0.00 | 0.00 |
October | 0.113166E+11 | 0.00 | 359.03 | 0.457539E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 88345.45 | 12-OCT-21:42 | 81462.42 | 25-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.330059E+10 | 0.00 | 175.95 | 0.139331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78139.40 | 04-NOV-15:01 | 77150.88 | 05-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 0.213465E+09 | 0.00 | 20.39 | 85776735.38 | 0.00 | 0.00 | 0.00 | 0.00 | 75687.49 | 03-DEC-09:02 | 75687.49 | 03-DEC-09:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.226542E+12 | 0.00 | 3266.82 | 0.132341E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 94390571.65 | 0.00 | 9.21 | 64018015.27 | 0.00 | 0.00 | 0.00 | 0.00 | 61557.12 | 61557.12 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.544687E+11 | 0.00 | 472.03 | 0.338215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 112782.61 | 93231.58 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 3138068.26 | 0.00 | 1.81 | 1412475.11 | 0.00 | 0.00 | 0.00 | 0.00 | 5621.77 | 15-JAN-16:01 | 4833.99 | 15-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 34704453.42 | 0.00 | 8.71 | 33246110.05 | 0.00 | 0.00 | 0.00 | 0.00 | 14384.69 | 28-FEB-09:02 | 14384.69 | 28-FEB-09:02 | 0.00 | 0.00 | 0.00 |
March | 0.650601E+09 | 0.00 | 113.30 | 0.392371E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15334.67 | 14-MAR-08:62 | 14964.65 | 01-MAR-09:02 | 0.00 | 0.00 | 0.00 |
April | 0.162047E+10 | 0.00 | 271.49 | 0.959351E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15207.54 | 22-APR-18:01 | 15207.54 | 22-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.396120E+10 | 0.00 | 572.08 | 0.222334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15510.59 | 17-MAY-15:01 | 15219.11 | 09-MAY-15:01 | 0.00 | 0.00 | 0.00 |
June | 0.754870E+10 | 0.00 | 676.16 | 0.407002E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16788.81 | 08-JUN-08:62 | 15210.79 | 03-JUN-18:01 | 0.00 | 0.00 | 0.00 |
July | 0.101643E+11 | 0.00 | 721.23 | 0.563124E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16648.36 | 29-JUL-08:61 | 13791.39 | 31-JUL-08:61 | 0.00 | 0.00 | 0.00 |
August | 0.896560E+10 | 0.00 | 710.06 | 0.489120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16433.90 | 28-AUG-18:02 | 13778.12 | 29-AUG-15:01 | 0.00 | 0.00 | 0.00 |
September | 0.555045E+10 | 0.00 | 630.53 | 0.268390E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16573.81 | 17-SEP-08:61 | 13817.75 | 12-SEP-08:62 | 0.00 | 0.00 | 0.00 |
October | 0.140034E+10 | 0.00 | 282.05 | 0.611582E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15850.18 | 01-OCT-08:62 | 13740.88 | 06-OCT-08:61 | 0.00 | 0.00 | 0.00 |
November | 0.186802E+09 | 0.00 | 50.46 | 75219812.24 | 0.00 | 0.00 | 0.00 | 0.00 | 14190.56 | 04-NOV-15:01 | 12728.45 | 06-NOV-09:01 | 0.00 | 0.00 | 0.00 |
December | 13451606.10 | 0.00 | 5.30 | 6057372.30 | 0.00 | 0.00 | 0.00 | 0.00 | 1940.47 | 16-DEC-09:03 | 1568.64 | 04-DEC-16:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.400997E+11 | 0.00 | 4043.19 | 0.215789E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3138068.26 | 0.00 | 1.81 | 1412475.11 | 0.00 | 0.00 | 0.00 | 0.00 | 1940.47 | 1568.64 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.101643E+11 | 0.00 | 721.23 | 0.563124E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16788.81 | 15219.11 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 1018592.21 | 0.00 | 0.33 | 310478.38 | 0.00 | 0.00 | 0.00 | 0.00 | 1872.86 | 17-JAN-19:05 | 677.09 | 17-JAN-19:05 | 0.00 | 0.00 | 0.00 |
February | 3894996.18 | 0.00 | 1.62 | 3707182.22 | 0.00 | 0.00 | 0.00 | 0.00 | 6176.12 | 28-FEB-09:02 | 6176.12 | 28-FEB-09:02 | 0.00 | 0.00 | 0.00 |
March | 0.283618E+09 | 0.00 | 71.79 | 0.134796E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14781.67 | 14-MAR-08:62 | 13816.45 | 22-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.958967E+09 | 0.00 | 186.07 | 0.552500E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14750.52 | 22-APR-18:01 | 14750.52 | 22-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.277674E+10 | 0.00 | 452.76 | 0.150504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15815.89 | 17-MAY-18:01 | 14829.94 | 21-MAY-19:41 | 0.00 | 0.00 | 0.00 |
June | 0.565362E+10 | 0.00 | 500.88 | 0.308095E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19124.41 | 18-JUN-08:21 | 16099.27 | 30-JUN-08:32 | 0.00 | 0.00 | 0.00 |
July | 0.789796E+10 | 0.00 | 535.87 | 0.444223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19443.58 | 17-JUL-08:32 | 15673.12 | 04-JUL-08:32 | 0.00 | 0.00 | 0.00 |
August | 0.650177E+10 | 0.00 | 523.60 | 0.351002E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18577.83 | 14-AUG-08:21 | 16452.25 | 05-AUG-08:32 | 0.00 | 0.00 | 0.00 |
September | 0.322544E+10 | 0.00 | 461.79 | 0.142499E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17248.95 | 16-SEP-08:51 | 14366.44 | 09-SEP-08:51 | 0.00 | 0.00 | 0.00 |
October | 0.513760E+09 | 0.00 | 143.25 | 0.201771E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15407.63 | 01-OCT-08:62 | 13338.14 | 11-OCT-08:62 | 0.00 | 0.00 | 0.00 |
November | 40887136.32 | 0.00 | 19.80 | 13835252.63 | 0.00 | 0.00 | 0.00 | 0.00 | 13231.57 | 05-NOV-15:01 | 12033.65 | 06-NOV-09:01 | 0.00 | 0.00 | 0.00 |
December | 1008168.36 | 0.00 | 0.37 | 283395.69 | 0.00 | 0.00 | 0.00 | 0.00 | 2040.69 | 01-DEC-19:05 | 632.91 | 01-DEC-19:05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.278587E+11 | 0.00 | 2898.14 | 0.148704E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1008168.36 | 0.00 | 0.33 | 283395.69 | 0.00 | 0.00 | 0.00 | 0.00 | 1872.86 | 632.91 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.789796E+10 | 0.00 | 535.87 | 0.444223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19443.58 | 16452.25 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 1706070.63 | 0.00 | 1.08 | 1017062.93 | 0.00 | 0.00 | 0.00 | 0.00 | 3310.27 | 15-JAN-16:01 | 3310.27 | 15-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 7717265.78 | 0.00 | 5.05 | 6527670.64 | 0.00 | 0.00 | 0.00 | 0.00 | 4334.55 | 28-FEB-16:01 | 4334.55 | 28-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.165028E+09 | 0.00 | 99.81 | 0.107123E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4335.89 | 25-MAR-15:01 | 4335.89 | 25-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.388268E+09 | 0.00 | 198.19 | 0.252771E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4335.43 | 17-APR-15:01 | 4335.43 | 17-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.992208E+09 | 0.00 | 472.89 | 0.620248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4443.29 | 17-MAY-15:01 | 4336.31 | 20-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.201475E+10 | 0.00 | 645.00 | 0.116137E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4920.41 | 08-JUN-08:62 | 4335.59 | 15-JUN-18:01 | 0.00 | 0.00 | 0.00 |
July | 0.258187E+10 | 0.00 | 701.76 | 0.143792E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5041.33 | 29-JUL-08:61 | 3867.18 | 26-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.224924E+10 | 0.00 | 685.79 | 0.126341E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4977.95 | 14-AUG-08:61 | 3834.00 | 29-AUG-15:01 | 0.00 | 0.00 | 0.00 |
September | 0.127438E+10 | 0.00 | 559.12 | 0.641182E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4912.65 | 17-SEP-08:61 | 3904.14 | 12-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.289638E+09 | 0.00 | 192.72 | 0.139662E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4676.52 | 01-OCT-08:62 | 3802.67 | 02-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 21224363.71 | 0.00 | 26.40 | 10052993.42 | 0.00 | 0.00 | 0.00 | 0.00 | 4120.96 | 04-NOV-15:01 | 3626.04 | 14-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 866999.55 | 0.00 | 0.55 | 682677.29 | 0.00 | 0.00 | 0.00 | 0.00 | 2664.86 | 16-DEC-16:01 | 2652.50 | 16-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.998690E+10 | 0.00 | 3588.35 | 0.564197E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 866999.55 | 0.00 | 0.55 | 682677.29 | 0.00 | 0.00 | 0.00 | 0.00 | 2664.86 | 2652.50 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.258187E+10 | 0.00 | 701.76 | 0.143792E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5041.33 | 4336.31 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 76983.04 | 0.00 | 0.10 | 35454.31 | 0.00 | 0.00 | 0.00 | 0.00 | 479.28 | 15-JAN-16:03 | 173.12 | 15-JAN-16:03 | 0.00 | 0.00 | 0.00 |
February | 295406.10 | 0.00 | 0.80 | 269210.47 | 0.00 | 0.00 | 0.00 | 0.00 | 546.69 | 22-FEB-16:03 | 546.69 | 22-FEB-16:03 | 0.00 | 0.00 | 0.00 |
March | 63776133.90 | 0.00 | 54.62 | 33748393.26 | 0.00 | 0.00 | 0.00 | 0.00 | 4218.96 | 14-MAR-15:01 | 4152.66 | 28-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.229023E+09 | 0.00 | 130.25 | 0.139533E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4772.58 | 19-APR-18:11 | 4772.58 | 19-APR-18:11 | 0.00 | 0.00 | 0.00 |
May | 0.637104E+09 | 0.00 | 353.86 | 0.351868E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4790.16 | 03-MAY-18:01 | 4790.16 | 03-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.151001E+10 | 0.00 | 478.40 | 0.843407E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5486.21 | 18-JUN-08:21 | 4217.75 | 24-JUN-21:51 | 0.00 | 0.00 | 0.00 |
July | 0.208287E+10 | 0.00 | 526.40 | 0.120092E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5512.28 | 16-JUL-08:21 | 4281.90 | 06-JUL-21:51 | 0.00 | 0.00 | 0.00 |
August | 0.167187E+10 | 0.00 | 505.68 | 0.925621E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5454.00 | 14-AUG-08:21 | 4275.99 | 02-AUG-21:51 | 0.00 | 0.00 | 0.00 |
September | 0.651275E+09 | 0.00 | 386.69 | 0.265032E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4812.32 | 15-SEP-21:51 | 3996.31 | 04-SEP-19:11 | 0.00 | 0.00 | 0.00 |
October | 78929016.08 | 0.00 | 84.81 | 31260531.58 | 0.00 | 0.00 | 0.00 | 0.00 | 4303.21 | 01-OCT-15:01 | 3781.36 | 03-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 3151222.75 | 0.00 | 3.99 | 1301739.47 | 0.00 | 0.00 | 0.00 | 0.00 | 3320.59 | 05-NOV-15:01 | 2927.48 | 15-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 144335.10 | 0.00 | 0.15 | 62691.98 | 0.00 | 0.00 | 0.00 | 0.00 | 455.71 | 16-DEC-16:04 | 367.36 | 04-DEC-16:05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.692853E+10 | 0.00 | 2525.73 | 0.379306E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 76983.04 | 0.00 | 0.10 | 35454.31 | 0.00 | 0.00 | 0.00 | 0.00 | 455.71 | 173.12 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.208287E+10 | 0.00 | 526.40 | 0.120092E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5512.28 | 4790.16 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.291301E+09 | 0.00 | 39.64 | 0.238634E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20485.55 | 06-JAN-16:01 | 20485.55 | 06-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.297270E+09 | 0.00 | 40.41 | 0.257896E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20491.07 | 28-FEB-16:01 | 20491.07 | 28-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.224609E+10 | 0.00 | 229.86 | 0.163849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20491.56 | 22-MAR-15:01 | 20491.56 | 22-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.283559E+10 | 0.00 | 318.69 | 0.166331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20479.36 | 19-APR-18:01 | 20479.36 | 19-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.509110E+10 | 0.00 | 544.52 | 0.282556E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21130.40 | 17-MAY-15:01 | 20488.27 | 16-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.890831E+10 | 0.00 | 637.76 | 0.447554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23100.11 | 08-JUN-08:62 | 20418.26 | 03-JUN-18:01 | 0.00 | 0.00 | 0.00 |
July | 0.127137E+11 | 0.00 | 697.15 | 0.670166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23796.05 | 28-JUL-18:02 | 18462.08 | 05-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.120829E+11 | 0.00 | 689.81 | 0.668538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24003.33 | 14-AUG-08:61 | 18490.56 | 18-AUG-08:61 | 0.00 | 0.00 | 0.00 |
September | 0.905733E+10 | 0.00 | 629.67 | 0.498767E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23206.06 | 17-SEP-08:61 | 20490.25 | 02-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.412370E+10 | 0.00 | 395.42 | 0.230223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20732.85 | 01-OCT-08:62 | 18152.35 | 04-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.136303E+10 | 0.00 | 181.88 | 0.677272E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20012.28 | 04-NOV-15:01 | 18223.04 | 16-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.319652E+09 | 0.00 | 39.47 | 0.217237E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20449.43 | 11-DEC-16:01 | 20449.43 | 11-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.593299E+11 | 0.00 | 4444.29 | 0.326709E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.291301E+09 | 0.00 | 39.47 | 0.217237E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20012.28 | 18152.35 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.127137E+11 | 0.00 | 697.15 | 0.670166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24003.33 | 20491.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 557.21 | 325.42 | 231.79 | 442.93 | 722.31 | 0.00 | 0.00 | 0.00 |
February | 631.03 | 301.80 | 329.23 | 494.36 | 703.16 | 0.00 | 0.00 | 0.00 |
March | 775.39 | 435.63 | 339.76 | 760.64 | 500.75 | 0.00 | 0.00 | 0.00 |
April | 641.30 | 255.68 | 385.62 | 666.78 | 377.72 | 0.00 | 0.00 | 0.00 |
May | 565.52 | 166.71 | 398.81 | 654.96 | 231.34 | 0.00 | 0.00 | 0.00 |
June | 544.34 | 113.98 | 430.36 | 702.32 | 141.65 | 0.00 | 0.00 | 0.00 |
July | 553.29 | 131.07 | 422.21 | 786.13 | 91.00 | 0.00 | 0.00 | 0.00 |
August | 619.54 | 196.60 | 422.95 | 856.07 | 124.86 | 0.00 | 0.00 | 0.00 |
September | 725.19 | 351.94 | 373.25 | 920.65 | 208.33 | 0.00 | 0.00 | 0.00 |
October | 697.37 | 398.71 | 298.66 | 764.59 | 348.40 | 0.00 | 0.00 | 0.00 |
November | 500.22 | 283.03 | 217.20 | 476.97 | 466.92 | 0.00 | 0.00 | 0.00 |
December | 465.94 | 241.51 | 224.43 | 350.74 | 704.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 606.20 | 266.73 | 339.47 | 657.37 | 383.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 465.94 | 113.98 | 217.20 | 350.74 | 91.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 775.39 | 435.63 | 430.36 | 920.65 | 722.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1569.08 | 916.37 | 652.71 | 1229.73 | 2074.31 | 0.00 | 0.00 | 0.00 |
February | 1776.95 | 849.85 | 927.10 | 1371.43 | 2017.75 | 0.00 | 0.00 | 0.00 |
March | 2183.46 | 1226.71 | 956.75 | 2110.70 | 1478.01 | 0.00 | 0.00 | 0.00 |
April | 1805.87 | 719.99 | 1085.87 | 1844.67 | 1139.63 | 0.00 | 0.00 | 0.00 |
May | 1592.46 | 469.45 | 1123.01 | 1802.84 | 727.65 | 0.00 | 0.00 | 0.00 |
June | 1532.82 | 320.96 | 1211.86 | 1940.88 | 450.61 | 0.00 | 0.00 | 0.00 |
July | 1558.02 | 369.09 | 1188.92 | 2185.49 | 290.59 | 0.00 | 0.00 | 0.00 |
August | 1744.59 | 553.60 | 1190.99 | 2383.66 | 395.51 | 0.00 | 0.00 | 0.00 |
September | 2042.09 | 991.05 | 1051.05 | 2558.51 | 659.25 | 0.00 | 0.00 | 0.00 |
October | 1963.76 | 1122.74 | 841.02 | 2120.85 | 1063.21 | 0.00 | 0.00 | 0.00 |
November | 1408.59 | 796.99 | 611.61 | 1318.83 | 1392.42 | 0.00 | 0.00 | 0.00 |
December | 1312.06 | 680.08 | 631.98 | 972.88 | 2028.92 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1707.02 | 751.08 | 955.94 | 1822.68 | 1138.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1312.06 | 320.96 | 611.61 | 972.88 | 290.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2183.46 | 1226.71 | 1211.86 | 2558.51 | 2074.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2038.32 | 1190.42 | 847.90 | 1614.61 | 2835.85 | 0.00 | 0.00 | 0.00 |
February | 2308.35 | 1104.00 | 1204.35 | 1801.66 | 2753.97 | 0.00 | 0.00 | 0.00 |
March | 2836.44 | 1593.56 | 1242.87 | 2789.96 | 2006.93 | 0.00 | 0.00 | 0.00 |
April | 2345.92 | 935.31 | 1410.61 | 2435.29 | 1555.87 | 0.00 | 0.00 | 0.00 |
May | 2068.69 | 609.84 | 1458.85 | 2382.06 | 996.27 | 0.00 | 0.00 | 0.00 |
June | 1991.23 | 416.95 | 1574.28 | 2570.09 | 610.21 | 0.00 | 0.00 | 0.00 |
July | 2023.95 | 479.47 | 1544.48 | 2902.66 | 387.22 | 0.00 | 0.00 | 0.00 |
August | 2266.32 | 719.16 | 1547.16 | 3161.50 | 526.18 | 0.00 | 0.00 | 0.00 |
September | 2652.80 | 1287.43 | 1365.37 | 3384.99 | 889.03 | 0.00 | 0.00 | 0.00 |
October | 2551.04 | 1458.51 | 1092.53 | 2792.29 | 1455.93 | 0.00 | 0.00 | 0.00 |
November | 1829.85 | 1035.33 | 794.51 | 1733.24 | 1920.31 | 0.00 | 0.00 | 0.00 |
December | 1704.44 | 883.46 | 820.98 | 1276.59 | 2783.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2217.52 | 975.70 | 1241.82 | 2407.30 | 1553.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1704.44 | 416.95 | 794.51 | 1276.59 | 387.22 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2836.44 | 1593.56 | 1574.28 | 3384.99 | 2835.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 110.17 | 64.34 | 45.83 | 87.99 | 146.97 | 0.00 | 0.00 | 0.00 |
February | 124.77 | 59.67 | 65.10 | 97.18 | 144.49 | 0.00 | 0.00 | 0.00 |
March | 153.31 | 86.13 | 67.18 | 149.92 | 101.88 | 0.00 | 0.00 | 0.00 |
April | 126.80 | 50.55 | 76.24 | 130.69 | 77.25 | 0.00 | 0.00 | 0.00 |
May | 111.81 | 32.96 | 78.85 | 127.87 | 46.32 | 0.00 | 0.00 | 0.00 |
June | 107.63 | 22.54 | 85.09 | 138.97 | 25.78 | 0.00 | 0.00 | 0.00 |
July | 109.39 | 25.92 | 83.48 | 159.11 | 14.27 | 0.00 | 0.00 | 0.00 |
August | 122.49 | 38.87 | 83.62 | 172.30 | 20.47 | 0.00 | 0.00 | 0.00 |
September | 143.38 | 69.59 | 73.80 | 183.81 | 38.66 | 0.00 | 0.00 | 0.00 |
October | 137.88 | 78.83 | 59.05 | 151.71 | 68.82 | 0.00 | 0.00 | 0.00 |
November | 98.90 | 55.96 | 42.94 | 94.72 | 93.57 | 0.00 | 0.00 | 0.00 |
December | 92.12 | 47.75 | 44.37 | 69.35 | 143.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 119.86 | 52.74 | 67.12 | 130.50 | 76.49 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 92.12 | 22.54 | 42.94 | 69.35 | 14.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 153.31 | 86.13 | 85.09 | 183.81 | 146.97 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.23 | 17.73 | 57.50 | 18.95 | 307.31 | 0.00 | 0.00 | 0.00 |
February | 122.17 | 31.64 | 90.52 | 48.18 | 290.49 | 0.00 | 0.00 | 0.00 |
March | 191.26 | 82.14 | 109.12 | 148.84 | 197.80 | 0.00 | 0.00 | 0.00 |
April | 233.17 | 95.52 | 137.65 | 219.05 | 139.10 | 0.00 | 0.00 | 0.00 |
May | 275.37 | 124.58 | 150.79 | 308.92 | 83.53 | 0.00 | 0.00 | 0.00 |
June | 331.83 | 155.93 | 175.90 | 421.25 | 46.94 | 0.00 | 0.00 | 0.00 |
July | 296.61 | 129.84 | 166.77 | 407.68 | 26.51 | 0.00 | 0.00 | 0.00 |
August | 268.13 | 113.66 | 154.48 | 359.41 | 37.98 | 0.00 | 0.00 | 0.00 |
September | 210.80 | 90.93 | 119.86 | 250.92 | 71.82 | 0.00 | 0.00 | 0.00 |
October | 137.26 | 48.62 | 88.64 | 120.70 | 133.51 | 0.00 | 0.00 | 0.00 |
November | 80.88 | 23.20 | 57.68 | 46.14 | 185.24 | 0.00 | 0.00 | 0.00 |
December | 69.98 | 15.08 | 54.90 | 17.56 | 294.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 191.37 | 77.63 | 113.74 | 198.12 | 150.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 69.98 | 15.08 | 54.90 | 17.56 | 26.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 331.83 | 155.93 | 175.90 | 421.25 | 307.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 25.59 | 0.00 | 25.59 | 0.03 | 172.10 | 0.00 | 0.00 | 0.00 |
February | 38.98 | 0.00 | 38.98 | 1.52 | 163.42 | 0.00 | 0.00 | 0.00 |
March | 47.28 | 0.00 | 47.28 | 15.23 | 113.04 | 0.00 | 0.00 | 0.00 |
April | 60.37 | 0.34 | 60.03 | 32.44 | 76.25 | 0.00 | 0.00 | 0.00 |
May | 69.94 | 2.91 | 67.04 | 56.82 | 43.46 | 0.00 | 0.00 | 0.00 |
June | 84.37 | 7.31 | 77.06 | 93.61 | 25.94 | 0.00 | 0.00 | 0.00 |
July | 78.58 | 5.46 | 73.12 | 104.41 | 15.13 | 0.00 | 0.00 | 0.00 |
August | 67.97 | 1.34 | 66.63 | 84.73 | 21.60 | 0.00 | 0.00 | 0.00 |
September | 51.47 | 0.03 | 51.44 | 49.24 | 40.86 | 0.00 | 0.00 | 0.00 |
October | 38.44 | 0.00 | 38.44 | 19.96 | 72.99 | 0.00 | 0.00 | 0.00 |
November | 25.83 | 0.00 | 25.83 | 5.46 | 100.83 | 0.00 | 0.00 | 0.00 |
December | 23.95 | 0.00 | 23.95 | 0.28 | 164.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 51.12 | 1.45 | 49.66 | 38.88 | 83.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 23.95 | 0.00 | 23.95 | 0.03 | 15.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 84.37 | 7.31 | 77.06 | 104.41 | 172.10 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.23 | 17.73 | 57.50 | 20.22 | 304.82 | 0.00 | 0.00 | 0.00 |
February | 122.17 | 31.64 | 90.52 | 50.31 | 288.39 | 0.00 | 0.00 | 0.00 |
March | 191.26 | 82.14 | 109.12 | 153.14 | 195.09 | 0.00 | 0.00 | 0.00 |
April | 233.17 | 95.52 | 137.65 | 222.04 | 138.09 | 0.00 | 0.00 | 0.00 |
May | 275.37 | 124.58 | 150.79 | 307.60 | 84.90 | 0.00 | 0.00 | 0.00 |
June | 331.83 | 155.93 | 175.90 | 415.16 | 51.58 | 0.00 | 0.00 | 0.00 |
July | 296.61 | 129.84 | 166.77 | 403.37 | 30.13 | 0.00 | 0.00 | 0.00 |
August | 268.13 | 113.66 | 154.48 | 356.44 | 41.72 | 0.00 | 0.00 | 0.00 |
September | 210.80 | 90.93 | 119.86 | 250.39 | 74.63 | 0.00 | 0.00 | 0.00 |
October | 137.26 | 48.62 | 88.64 | 124.26 | 132.13 | 0.00 | 0.00 | 0.00 |
November | 80.88 | 23.20 | 57.68 | 48.83 | 182.81 | 0.00 | 0.00 | 0.00 |
December | 69.98 | 15.08 | 54.90 | 18.79 | 292.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 191.37 | 77.63 | 113.74 | 198.35 | 150.73 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 69.98 | 15.08 | 54.90 | 18.79 | 30.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 331.83 | 155.93 | 175.90 | 415.16 | 304.82 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.12 | 51.46 | 36.66 | 72.41 | 105.59 | 0.00 | 0.00 | 0.00 |
February | 99.79 | 47.73 | 52.07 | 81.07 | 102.46 | 0.00 | 0.00 | 0.00 |
March | 122.62 | 68.89 | 53.73 | 110.52 | 100.81 | 0.00 | 0.00 | 0.00 |
April | 101.42 | 40.43 | 60.98 | 93.50 | 84.40 | 0.00 | 0.00 | 0.00 |
May | 89.43 | 26.36 | 63.07 | 90.19 | 57.60 | 0.00 | 0.00 | 0.00 |
June | 86.08 | 18.03 | 68.06 | 97.60 | 36.70 | 0.00 | 0.00 | 0.00 |
July | 87.50 | 20.73 | 66.77 | 112.35 | 25.35 | 0.00 | 0.00 | 0.00 |
August | 97.98 | 31.09 | 66.89 | 124.59 | 32.82 | 0.00 | 0.00 | 0.00 |
September | 114.68 | 55.66 | 59.03 | 135.11 | 51.53 | 0.00 | 0.00 | 0.00 |
October | 110.28 | 63.05 | 47.23 | 109.73 | 80.18 | 0.00 | 0.00 | 0.00 |
November | 79.11 | 44.76 | 34.35 | 68.40 | 99.11 | 0.00 | 0.00 | 0.00 |
December | 73.69 | 38.19 | 35.49 | 57.03 | 105.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.87 | 42.18 | 53.69 | 96.14 | 73.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 18.03 | 34.35 | 57.03 | 25.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 122.62 | 68.89 | 68.06 | 135.11 | 105.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.47 | 0.00 | 20.47 | 0.00 | 144.14 | 0.00 | 0.00 | 0.00 |
February | 31.19 | 0.00 | 31.19 | 0.80 | 136.42 | 0.00 | 0.00 | 0.00 |
March | 37.83 | 0.00 | 37.83 | 11.70 | 92.71 | 0.00 | 0.00 | 0.00 |
April | 48.30 | 0.27 | 48.03 | 26.40 | 61.87 | 0.00 | 0.00 | 0.00 |
May | 55.96 | 2.32 | 53.64 | 48.54 | 34.17 | 0.00 | 0.00 | 0.00 |
June | 67.50 | 5.85 | 61.66 | 80.04 | 18.97 | 0.00 | 0.00 | 0.00 |
July | 62.87 | 4.37 | 58.51 | 88.02 | 10.73 | 0.00 | 0.00 | 0.00 |
August | 54.38 | 1.07 | 53.31 | 71.81 | 15.85 | 0.00 | 0.00 | 0.00 |
September | 41.18 | 0.02 | 41.16 | 41.83 | 31.25 | 0.00 | 0.00 | 0.00 |
October | 30.76 | 0.00 | 30.76 | 15.83 | 60.04 | 0.00 | 0.00 | 0.00 |
November | 20.67 | 0.00 | 20.67 | 3.89 | 84.96 | 0.00 | 0.00 | 0.00 |
December | 19.16 | 0.00 | 19.16 | 0.13 | 137.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.90 | 1.16 | 39.73 | 32.61 | 68.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 19.16 | 0.00 | 19.16 | 0.00 | 10.73 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.50 | 5.85 | 61.66 | 88.02 | 144.14 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 87.36 | 28.13 | 59.22 | 29.97 | 297.93 | 0.00 | 0.00 | 0.00 |
February | 128.97 | 39.07 | 89.90 | 54.28 | 282.03 | 0.00 | 0.00 | 0.00 |
March | 185.06 | 77.82 | 107.24 | 140.27 | 194.54 | 0.00 | 0.00 | 0.00 |
April | 243.61 | 107.60 | 136.00 | 228.42 | 134.20 | 0.00 | 0.00 | 0.00 |
May | 272.93 | 120.76 | 152.18 | 304.19 | 79.72 | 0.00 | 0.00 | 0.00 |
June | 304.56 | 134.47 | 170.09 | 383.36 | 43.55 | 0.00 | 0.00 | 0.00 |
July | 292.50 | 128.62 | 163.88 | 401.11 | 24.12 | 0.00 | 0.00 | 0.00 |
August | 264.19 | 110.66 | 153.53 | 352.37 | 35.69 | 0.00 | 0.00 | 0.00 |
September | 220.07 | 97.63 | 122.45 | 262.04 | 68.72 | 0.00 | 0.00 | 0.00 |
October | 149.26 | 61.66 | 87.60 | 133.23 | 129.60 | 0.00 | 0.00 | 0.00 |
November | 84.61 | 27.09 | 57.52 | 49.94 | 182.18 | 0.00 | 0.00 | 0.00 |
December | 68.16 | 14.12 | 54.04 | 15.01 | 291.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 192.06 | 79.16 | 112.90 | 196.97 | 146.31 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 68.16 | 14.12 | 54.04 | 15.01 | 24.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 304.56 | 134.47 | 170.09 | 401.11 | 297.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 110.17 | 64.34 | 45.83 | 87.58 | 147.01 | 0.00 | 0.00 | 0.00 |
February | 124.77 | 59.67 | 65.10 | 96.62 | 144.45 | 0.00 | 0.00 | 0.00 |
March | 153.31 | 86.13 | 67.18 | 148.91 | 101.31 | 0.00 | 0.00 | 0.00 |
April | 126.80 | 50.55 | 76.24 | 129.41 | 76.90 | 0.00 | 0.00 | 0.00 |
May | 111.81 | 32.96 | 78.85 | 127.04 | 45.83 | 0.00 | 0.00 | 0.00 |
June | 107.63 | 22.54 | 85.09 | 138.59 | 25.16 | 0.00 | 0.00 | 0.00 |
July | 109.39 | 25.92 | 83.48 | 158.58 | 13.90 | 0.00 | 0.00 | 0.00 |
August | 122.49 | 38.87 | 83.62 | 171.89 | 20.18 | 0.00 | 0.00 | 0.00 |
September | 143.38 | 69.59 | 73.80 | 183.08 | 38.31 | 0.00 | 0.00 | 0.00 |
October | 137.88 | 78.83 | 59.05 | 150.83 | 68.68 | 0.00 | 0.00 | 0.00 |
November | 98.90 | 55.96 | 42.94 | 94.45 | 93.49 | 0.00 | 0.00 | 0.00 |
December | 92.12 | 47.75 | 44.37 | 69.25 | 143.56 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 119.86 | 52.74 | 67.12 | 129.88 | 76.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 92.12 | 22.54 | 42.94 | 69.25 | 13.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 153.31 | 86.13 | 85.09 | 183.08 | 147.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 25.59 | 0.00 | 25.59 | 0.02 | 172.34 | 0.00 | 0.00 | 0.00 |
February | 38.98 | 0.00 | 38.98 | 1.38 | 163.63 | 0.00 | 0.00 | 0.00 |
March | 47.28 | 0.00 | 47.28 | 14.61 | 112.82 | 0.00 | 0.00 | 0.00 |
April | 60.37 | 0.34 | 60.03 | 31.28 | 76.22 | 0.00 | 0.00 | 0.00 |
May | 69.94 | 2.91 | 67.04 | 56.60 | 42.86 | 0.00 | 0.00 | 0.00 |
June | 84.37 | 7.31 | 77.06 | 94.21 | 24.58 | 0.00 | 0.00 | 0.00 |
July | 78.58 | 5.46 | 73.12 | 103.52 | 14.51 | 0.00 | 0.00 | 0.00 |
August | 67.97 | 1.34 | 66.63 | 84.07 | 20.93 | 0.00 | 0.00 | 0.00 |
September | 51.47 | 0.03 | 51.44 | 48.64 | 39.85 | 0.00 | 0.00 | 0.00 |
October | 38.44 | 0.00 | 38.44 | 19.15 | 72.86 | 0.00 | 0.00 | 0.00 |
November | 25.83 | 0.00 | 25.83 | 5.21 | 100.75 | 0.00 | 0.00 | 0.00 |
December | 23.95 | 0.00 | 23.95 | 0.27 | 164.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 51.12 | 1.45 | 49.66 | 38.48 | 83.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 23.95 | 0.00 | 23.95 | 0.02 | 14.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 84.37 | 7.31 | 77.06 | 103.52 | 172.34 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 87.36 | 28.13 | 59.22 | 30.78 | 294.73 | 0.00 | 0.00 | 0.00 |
February | 128.97 | 39.07 | 89.90 | 55.88 | 279.20 | 0.00 | 0.00 | 0.00 |
March | 185.06 | 77.82 | 107.24 | 143.16 | 190.34 | 0.00 | 0.00 | 0.00 |
April | 243.61 | 107.60 | 136.00 | 231.03 | 133.08 | 0.00 | 0.00 | 0.00 |
May | 272.93 | 120.76 | 152.18 | 304.26 | 80.69 | 0.00 | 0.00 | 0.00 |
June | 304.56 | 134.47 | 170.09 | 379.84 | 47.08 | 0.00 | 0.00 | 0.00 |
July | 292.50 | 128.62 | 163.88 | 396.21 | 27.39 | 0.00 | 0.00 | 0.00 |
August | 264.19 | 110.66 | 153.53 | 349.15 | 38.90 | 0.00 | 0.00 | 0.00 |
September | 220.07 | 97.63 | 122.45 | 262.50 | 70.69 | 0.00 | 0.00 | 0.00 |
October | 149.26 | 61.66 | 87.60 | 136.58 | 127.92 | 0.00 | 0.00 | 0.00 |
November | 84.61 | 27.09 | 57.52 | 51.93 | 179.06 | 0.00 | 0.00 | 0.00 |
December | 68.16 | 14.12 | 54.04 | 15.49 | 288.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 192.06 | 79.16 | 112.90 | 197.17 | 145.84 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 68.16 | 14.12 | 54.04 | 15.49 | 27.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 304.56 | 134.47 | 170.09 | 396.21 | 294.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.40 | 0.00 | 32.40 | 0.00 | 234.27 | 0.00 | 0.00 | 0.00 |
February | 49.37 | 0.00 | 49.37 | 0.93 | 221.43 | 0.00 | 0.00 | 0.00 |
March | 59.88 | 0.00 | 59.88 | 18.29 | 150.34 | 0.00 | 0.00 | 0.00 |
April | 76.46 | 0.43 | 76.03 | 41.75 | 100.35 | 0.00 | 0.00 | 0.00 |
May | 88.58 | 3.68 | 84.90 | 76.10 | 57.95 | 0.00 | 0.00 | 0.00 |
June | 106.85 | 9.26 | 97.59 | 123.81 | 34.44 | 0.00 | 0.00 | 0.00 |
July | 99.52 | 6.91 | 92.61 | 133.91 | 21.73 | 0.00 | 0.00 | 0.00 |
August | 86.08 | 1.69 | 84.38 | 108.97 | 31.03 | 0.00 | 0.00 | 0.00 |
September | 65.18 | 0.04 | 65.14 | 63.75 | 55.69 | 0.00 | 0.00 | 0.00 |
October | 48.69 | 0.00 | 48.69 | 24.63 | 97.88 | 0.00 | 0.00 | 0.00 |
November | 32.72 | 0.00 | 32.72 | 6.02 | 136.87 | 0.00 | 0.00 | 0.00 |
December | 30.33 | 0.00 | 30.33 | 0.19 | 223.87 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 64.73 | 1.84 | 62.89 | 50.17 | 113.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.33 | 0.00 | 30.33 | 0.00 | 21.73 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 106.85 | 9.26 | 97.59 | 133.91 | 234.27 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 11.95 | 0.00 | 11.95 | 0.00 | 86.36 | 0.00 | 0.00 | 0.00 |
February | 18.20 | 0.00 | 18.20 | 0.34 | 81.63 | 0.00 | 0.00 | 0.00 |
March | 22.07 | 0.00 | 22.07 | 6.74 | 55.42 | 0.00 | 0.00 | 0.00 |
April | 28.19 | 0.16 | 28.03 | 15.39 | 36.99 | 0.00 | 0.00 | 0.00 |
May | 32.65 | 1.36 | 31.30 | 28.05 | 21.36 | 0.00 | 0.00 | 0.00 |
June | 39.39 | 3.41 | 35.98 | 45.64 | 12.70 | 0.00 | 0.00 | 0.00 |
July | 36.69 | 2.55 | 34.14 | 49.37 | 8.01 | 0.00 | 0.00 | 0.00 |
August | 31.73 | 0.62 | 31.11 | 40.17 | 11.44 | 0.00 | 0.00 | 0.00 |
September | 24.03 | 0.01 | 24.01 | 23.50 | 20.53 | 0.00 | 0.00 | 0.00 |
October | 17.95 | 0.00 | 17.95 | 9.08 | 36.08 | 0.00 | 0.00 | 0.00 |
November | 12.06 | 0.00 | 12.06 | 2.22 | 50.46 | 0.00 | 0.00 | 0.00 |
December | 11.18 | 0.00 | 11.18 | 0.07 | 82.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 23.86 | 0.68 | 23.18 | 18.49 | 41.76 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 11.18 | 0.00 | 11.18 | 0.00 | 8.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 39.39 | 3.41 | 35.98 | 49.37 | 86.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.41 | 30.02 | 21.38 | 40.09 | 72.49 | 0.00 | 0.00 | 0.00 |
February | 58.22 | 27.84 | 30.37 | 44.24 | 70.83 | 0.00 | 0.00 | 0.00 |
March | 71.53 | 40.19 | 31.34 | 70.26 | 49.05 | 0.00 | 0.00 | 0.00 |
April | 59.16 | 23.59 | 35.58 | 61.89 | 37.13 | 0.00 | 0.00 | 0.00 |
May | 52.17 | 15.38 | 36.79 | 60.86 | 23.04 | 0.00 | 0.00 | 0.00 |
June | 50.22 | 10.52 | 39.70 | 65.47 | 14.01 | 0.00 | 0.00 | 0.00 |
July | 51.04 | 12.09 | 38.95 | 73.89 | 8.71 | 0.00 | 0.00 | 0.00 |
August | 57.16 | 18.14 | 39.02 | 80.36 | 11.99 | 0.00 | 0.00 | 0.00 |
September | 66.90 | 32.47 | 34.43 | 86.24 | 20.32 | 0.00 | 0.00 | 0.00 |
October | 64.34 | 36.78 | 27.55 | 71.43 | 33.62 | 0.00 | 0.00 | 0.00 |
November | 46.15 | 26.11 | 20.04 | 44.21 | 45.93 | 0.00 | 0.00 | 0.00 |
December | 42.99 | 22.28 | 20.70 | 31.55 | 71.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.92 | 24.61 | 31.32 | 60.97 | 38.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 42.99 | 10.52 | 20.04 | 31.55 | 8.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.53 | 40.19 | 39.70 | 86.24 | 72.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 139.52 | 81.49 | 58.04 | 108.83 | 196.74 | 0.00 | 0.00 | 0.00 |
February | 158.01 | 75.57 | 82.44 | 120.08 | 192.26 | 0.00 | 0.00 | 0.00 |
March | 194.16 | 109.08 | 85.08 | 190.71 | 133.14 | 0.00 | 0.00 | 0.00 |
April | 160.58 | 64.02 | 96.56 | 167.98 | 100.78 | 0.00 | 0.00 | 0.00 |
May | 141.60 | 41.74 | 99.86 | 165.20 | 62.54 | 0.00 | 0.00 | 0.00 |
June | 136.30 | 28.54 | 107.76 | 177.70 | 38.03 | 0.00 | 0.00 | 0.00 |
July | 138.54 | 32.82 | 105.72 | 200.56 | 23.65 | 0.00 | 0.00 | 0.00 |
August | 155.13 | 49.23 | 105.91 | 218.12 | 32.55 | 0.00 | 0.00 | 0.00 |
September | 181.59 | 88.13 | 93.46 | 234.07 | 55.16 | 0.00 | 0.00 | 0.00 |
October | 174.62 | 99.84 | 74.78 | 193.88 | 91.24 | 0.00 | 0.00 | 0.00 |
November | 125.25 | 70.87 | 54.39 | 119.99 | 124.65 | 0.00 | 0.00 | 0.00 |
December | 116.67 | 60.47 | 56.20 | 85.64 | 192.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 151.79 | 66.79 | 85.00 | 165.49 | 103.18 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 116.67 | 28.54 | 54.39 | 85.64 | 23.65 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 194.16 | 109.08 | 107.76 | 234.07 | 196.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 110.17 | 64.34 | 45.83 | 87.73 | 146.87 | 0.00 | 0.00 | 0.00 |
February | 124.77 | 59.67 | 65.10 | 96.56 | 144.70 | 0.00 | 0.00 | 0.00 |
March | 153.31 | 86.13 | 67.18 | 149.18 | 101.69 | 0.00 | 0.00 | 0.00 |
April | 126.80 | 50.55 | 76.24 | 129.63 | 77.14 | 0.00 | 0.00 | 0.00 |
May | 111.81 | 32.96 | 78.85 | 126.57 | 46.11 | 0.00 | 0.00 | 0.00 |
June | 107.63 | 22.54 | 85.09 | 137.61 | 25.48 | 0.00 | 0.00 | 0.00 |
July | 109.39 | 25.92 | 83.48 | 157.85 | 13.93 | 0.00 | 0.00 | 0.00 |
August | 122.49 | 38.87 | 83.62 | 171.09 | 20.06 | 0.00 | 0.00 | 0.00 |
September | 143.38 | 69.59 | 73.80 | 182.72 | 38.15 | 0.00 | 0.00 | 0.00 |
October | 137.88 | 78.83 | 59.05 | 151.00 | 68.30 | 0.00 | 0.00 | 0.00 |
November | 98.90 | 55.96 | 42.94 | 94.48 | 92.91 | 0.00 | 0.00 | 0.00 |
December | 92.12 | 47.75 | 44.37 | 69.02 | 143.65 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 119.86 | 52.74 | 67.12 | 129.65 | 76.22 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 92.12 | 22.54 | 42.94 | 69.02 | 13.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 153.31 | 86.13 | 85.09 | 182.72 | 146.87 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.23 | 17.73 | 57.50 | 19.02 | 307.29 | 0.00 | 0.00 | 0.00 |
February | 122.17 | 31.64 | 90.52 | 47.92 | 290.93 | 0.00 | 0.00 | 0.00 |
March | 191.26 | 82.14 | 109.12 | 147.86 | 197.25 | 0.00 | 0.00 | 0.00 |
April | 233.17 | 95.52 | 137.65 | 217.00 | 138.66 | 0.00 | 0.00 | 0.00 |
May | 275.37 | 124.58 | 150.79 | 306.09 | 82.98 | 0.00 | 0.00 | 0.00 |
June | 331.83 | 155.93 | 175.90 | 417.73 | 46.34 | 0.00 | 0.00 | 0.00 |
July | 296.61 | 129.84 | 166.77 | 404.81 | 25.85 | 0.00 | 0.00 | 0.00 |
August | 268.13 | 113.66 | 154.48 | 357.08 | 37.19 | 0.00 | 0.00 | 0.00 |
September | 210.80 | 90.93 | 119.86 | 249.15 | 70.72 | 0.00 | 0.00 | 0.00 |
October | 137.26 | 48.62 | 88.64 | 120.02 | 132.40 | 0.00 | 0.00 | 0.00 |
November | 80.88 | 23.20 | 57.68 | 46.22 | 183.70 | 0.00 | 0.00 | 0.00 |
December | 69.98 | 15.08 | 54.90 | 17.55 | 294.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 191.37 | 77.63 | 113.74 | 196.69 | 149.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 69.98 | 15.08 | 54.90 | 17.55 | 25.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 331.83 | 155.93 | 175.90 | 417.73 | 307.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 25.59 | 0.00 | 25.59 | 0.04 | 172.07 | 0.00 | 0.00 | 0.00 |
February | 38.98 | 0.00 | 38.98 | 1.54 | 163.42 | 0.00 | 0.00 | 0.00 |
March | 47.28 | 0.00 | 47.28 | 15.31 | 112.71 | 0.00 | 0.00 | 0.00 |
April | 60.37 | 0.34 | 60.03 | 32.15 | 76.00 | 0.00 | 0.00 | 0.00 |
May | 69.94 | 2.91 | 67.04 | 55.80 | 43.51 | 0.00 | 0.00 | 0.00 |
June | 84.37 | 7.31 | 77.06 | 92.15 | 26.41 | 0.00 | 0.00 | 0.00 |
July | 78.58 | 5.46 | 73.12 | 103.39 | 15.27 | 0.00 | 0.00 | 0.00 |
August | 67.97 | 1.34 | 66.63 | 83.96 | 21.70 | 0.00 | 0.00 | 0.00 |
September | 51.47 | 0.03 | 51.44 | 48.77 | 40.85 | 0.00 | 0.00 | 0.00 |
October | 38.44 | 0.00 | 38.44 | 20.14 | 72.29 | 0.00 | 0.00 | 0.00 |
November | 25.83 | 0.00 | 25.83 | 5.68 | 99.68 | 0.00 | 0.00 | 0.00 |
December | 23.95 | 0.00 | 23.95 | 0.30 | 164.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 51.12 | 1.45 | 49.66 | 38.50 | 83.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 23.95 | 0.00 | 23.95 | 0.04 | 15.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 84.37 | 7.31 | 77.06 | 103.39 | 172.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.23 | 17.73 | 57.50 | 20.15 | 305.14 | 0.00 | 0.00 | 0.00 |
February | 122.17 | 31.64 | 90.52 | 49.91 | 289.02 | 0.00 | 0.00 | 0.00 |
March | 191.26 | 82.14 | 109.12 | 152.45 | 194.66 | 0.00 | 0.00 | 0.00 |
April | 233.17 | 95.52 | 137.65 | 220.19 | 137.59 | 0.00 | 0.00 | 0.00 |
May | 275.37 | 124.58 | 150.79 | 304.24 | 84.93 | 0.00 | 0.00 | 0.00 |
June | 331.83 | 155.93 | 175.90 | 410.66 | 52.34 | 0.00 | 0.00 | 0.00 |
July | 296.61 | 129.84 | 166.77 | 400.05 | 30.26 | 0.00 | 0.00 | 0.00 |
August | 268.13 | 113.66 | 154.48 | 353.79 | 41.74 | 0.00 | 0.00 | 0.00 |
September | 210.80 | 90.93 | 119.86 | 248.32 | 74.32 | 0.00 | 0.00 | 0.00 |
October | 137.26 | 48.62 | 88.64 | 123.97 | 130.87 | 0.00 | 0.00 | 0.00 |
November | 80.88 | 23.20 | 57.68 | 49.22 | 181.15 | 0.00 | 0.00 | 0.00 |
December | 69.98 | 15.08 | 54.90 | 18.73 | 292.97 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 191.37 | 77.63 | 113.74 | 196.78 | 150.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 69.98 | 15.08 | 54.90 | 18.73 | 30.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 331.83 | 155.93 | 175.90 | 410.66 | 305.14 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 161.58 | 94.36 | 67.21 | 123.11 | 222.74 | 0.00 | 0.00 | 0.00 |
February | 182.98 | 87.51 | 95.47 | 135.90 | 218.70 | 0.00 | 0.00 | 0.00 |
March | 224.84 | 126.32 | 98.52 | 212.95 | 153.18 | 0.00 | 0.00 | 0.00 |
April | 185.96 | 74.14 | 111.82 | 187.58 | 114.62 | 0.00 | 0.00 | 0.00 |
May | 163.98 | 48.34 | 115.64 | 186.19 | 67.04 | 0.00 | 0.00 | 0.00 |
June | 157.84 | 33.05 | 124.79 | 204.95 | 35.69 | 0.00 | 0.00 | 0.00 |
July | 160.44 | 38.01 | 122.43 | 234.57 | 19.14 | 0.00 | 0.00 | 0.00 |
August | 179.65 | 57.01 | 122.64 | 252.83 | 28.44 | 0.00 | 0.00 | 0.00 |
September | 210.29 | 102.05 | 108.23 | 267.02 | 56.11 | 0.00 | 0.00 | 0.00 |
October | 202.22 | 115.61 | 86.60 | 217.18 | 103.64 | 0.00 | 0.00 | 0.00 |
November | 145.05 | 82.07 | 62.98 | 134.28 | 142.40 | 0.00 | 0.00 | 0.00 |
December | 135.11 | 70.03 | 65.08 | 96.95 | 217.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 175.78 | 77.34 | 98.44 | 188.10 | 114.38 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 135.11 | 33.05 | 62.98 | 96.95 | 19.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 224.84 | 126.32 | 124.79 | 267.02 | 222.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 179.10 | 0.00 | 179.10 | 0.00 | 1421.40 | 0.00 | 0.00 | 0.00 |
February | 272.88 | 0.00 | 272.88 | 2.21 | 1348.58 | 0.00 | 0.00 | 0.00 |
March | 330.96 | 0.00 | 330.96 | 78.20 | 940.29 | 0.00 | 0.00 | 0.00 |
April | 422.60 | 2.38 | 420.21 | 185.70 | 645.74 | 0.00 | 0.00 | 0.00 |
May | 489.58 | 20.34 | 469.24 | 362.62 | 371.44 | 0.00 | 0.00 | 0.00 |
June | 590.57 | 51.17 | 539.40 | 634.74 | 214.24 | 0.00 | 0.00 | 0.00 |
July | 550.04 | 38.19 | 511.84 | 703.48 | 134.72 | 0.00 | 0.00 | 0.00 |
August | 475.75 | 9.36 | 466.39 | 569.90 | 190.56 | 0.00 | 0.00 | 0.00 |
September | 360.26 | 0.20 | 360.06 | 318.74 | 347.95 | 0.00 | 0.00 | 0.00 |
October | 269.10 | 0.00 | 269.10 | 104.52 | 635.90 | 0.00 | 0.00 | 0.00 |
November | 180.83 | 0.00 | 180.83 | 21.24 | 883.48 | 0.00 | 0.00 | 0.00 |
December | 167.63 | 0.00 | 167.63 | 0.50 | 1366.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 357.79 | 10.18 | 347.61 | 250.06 | 705.18 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 167.63 | 0.00 | 167.63 | 0.00 | 134.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 590.57 | 51.17 | 539.40 | 703.48 | 1421.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 179.10 | 0.00 | 179.10 | 0.00 | 1458.41 | 0.00 | 0.00 | 0.00 |
February | 272.88 | 0.00 | 272.88 | 1.57 | 1385.16 | 0.00 | 0.00 | 0.00 |
March | 330.96 | 0.00 | 330.96 | 72.54 | 966.73 | 0.00 | 0.00 | 0.00 |
April | 422.60 | 2.38 | 420.21 | 175.05 | 663.26 | 0.00 | 0.00 | 0.00 |
May | 489.58 | 20.34 | 469.24 | 350.54 | 381.32 | 0.00 | 0.00 | 0.00 |
June | 590.57 | 51.17 | 539.40 | 624.18 | 220.30 | 0.00 | 0.00 | 0.00 |
July | 550.04 | 38.19 | 511.84 | 694.70 | 139.48 | 0.00 | 0.00 | 0.00 |
August | 475.75 | 9.36 | 466.39 | 561.45 | 196.83 | 0.00 | 0.00 | 0.00 |
September | 360.26 | 0.20 | 360.06 | 309.90 | 358.28 | 0.00 | 0.00 | 0.00 |
October | 269.10 | 0.00 | 269.10 | 96.52 | 655.46 | 0.00 | 0.00 | 0.00 |
November | 180.83 | 0.00 | 180.83 | 18.70 | 912.91 | 0.00 | 0.00 | 0.00 |
December | 167.63 | 0.00 | 167.63 | 0.37 | 1403.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 357.79 | 10.18 | 347.61 | 243.67 | 725.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 167.63 | 0.00 | 167.63 | 0.00 | 139.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 590.57 | 51.17 | 539.40 | 694.70 | 1458.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 25.59 | 0.00 | 25.59 | 0.06 | 181.71 | 0.00 | 0.00 | 0.00 |
February | 38.98 | 0.00 | 38.98 | 1.30 | 172.54 | 0.00 | 0.00 | 0.00 |
March | 47.28 | 0.00 | 47.28 | 17.69 | 118.83 | 0.00 | 0.00 | 0.00 |
April | 60.37 | 0.34 | 60.03 | 39.42 | 82.13 | 0.00 | 0.00 | 0.00 |
May | 69.94 | 2.91 | 67.04 | 72.24 | 48.54 | 0.00 | 0.00 | 0.00 |
June | 84.37 | 7.31 | 77.06 | 116.47 | 29.47 | 0.00 | 0.00 | 0.00 |
July | 78.58 | 5.46 | 73.12 | 128.56 | 18.71 | 0.00 | 0.00 | 0.00 |
August | 67.97 | 1.34 | 66.63 | 107.14 | 24.89 | 0.00 | 0.00 | 0.00 |
September | 51.47 | 0.03 | 51.44 | 64.60 | 42.73 | 0.00 | 0.00 | 0.00 |
October | 38.44 | 0.00 | 38.44 | 25.07 | 77.43 | 0.00 | 0.00 | 0.00 |
November | 25.83 | 0.00 | 25.83 | 6.71 | 107.52 | 0.00 | 0.00 | 0.00 |
December | 23.95 | 0.00 | 23.95 | 0.34 | 174.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 51.12 | 1.45 | 49.66 | 48.59 | 89.48 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 23.95 | 0.00 | 23.95 | 0.06 | 18.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 84.37 | 7.31 | 77.06 | 128.56 | 181.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 174.70 | 56.27 | 118.44 | 63.02 | 623.91 | 0.00 | 0.00 | 0.00 |
February | 257.93 | 78.13 | 179.80 | 113.88 | 594.26 | 0.00 | 0.00 | 0.00 |
March | 370.10 | 155.64 | 214.46 | 302.54 | 406.44 | 0.00 | 0.00 | 0.00 |
April | 487.18 | 215.19 | 271.98 | 497.14 | 292.20 | 0.00 | 0.00 | 0.00 |
May | 545.83 | 241.49 | 304.34 | 667.39 | 182.44 | 0.00 | 0.00 | 0.00 |
June | 609.09 | 268.93 | 340.16 | 842.21 | 110.69 | 0.00 | 0.00 | 0.00 |
July | 584.95 | 257.21 | 327.74 | 886.19 | 70.19 | 0.00 | 0.00 | 0.00 |
August | 528.34 | 221.31 | 307.03 | 785.06 | 92.97 | 0.00 | 0.00 | 0.00 |
September | 440.12 | 195.24 | 244.88 | 589.63 | 154.98 | 0.00 | 0.00 | 0.00 |
October | 298.49 | 123.31 | 175.18 | 300.63 | 275.55 | 0.00 | 0.00 | 0.00 |
November | 169.22 | 54.18 | 115.03 | 111.95 | 385.64 | 0.00 | 0.00 | 0.00 |
December | 136.32 | 28.24 | 108.08 | 32.26 | 617.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 384.08 | 158.31 | 225.78 | 434.43 | 315.80 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 136.32 | 28.24 | 108.08 | 32.26 | 70.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 609.09 | 268.93 | 340.16 | 886.19 | 623.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 110.17 | 64.34 | 45.83 | 88.70 | 155.05 | 0.00 | 0.00 | 0.00 |
February | 124.77 | 59.67 | 65.10 | 97.28 | 153.08 | 0.00 | 0.00 | 0.00 |
March | 153.31 | 86.13 | 67.18 | 156.10 | 107.28 | 0.00 | 0.00 | 0.00 |
April | 126.80 | 50.55 | 76.24 | 139.83 | 83.08 | 0.00 | 0.00 | 0.00 |
May | 111.81 | 32.96 | 78.85 | 141.92 | 51.81 | 0.00 | 0.00 | 0.00 |
June | 107.63 | 22.54 | 85.09 | 157.77 | 31.47 | 0.00 | 0.00 | 0.00 |
July | 109.39 | 25.92 | 83.48 | 180.09 | 19.70 | 0.00 | 0.00 | 0.00 |
August | 122.49 | 38.87 | 83.62 | 192.72 | 25.62 | 0.00 | 0.00 | 0.00 |
September | 143.38 | 69.59 | 73.80 | 200.22 | 42.78 | 0.00 | 0.00 | 0.00 |
October | 137.88 | 78.83 | 59.05 | 160.80 | 73.92 | 0.00 | 0.00 | 0.00 |
November | 98.90 | 55.96 | 42.94 | 98.51 | 100.54 | 0.00 | 0.00 | 0.00 |
December | 92.12 | 47.75 | 44.37 | 69.61 | 152.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 119.86 | 52.74 | 67.12 | 140.55 | 82.74 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 92.12 | 22.54 | 42.94 | 69.61 | 19.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 153.31 | 86.13 | 85.09 | 200.22 | 155.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.40 | 0.00 | 32.40 | 0.00 | 238.62 | 0.00 | 0.00 | 0.00 |
February | 49.37 | 0.00 | 49.37 | 0.69 | 225.51 | 0.00 | 0.00 | 0.00 |
March | 59.88 | 0.00 | 59.88 | 16.75 | 153.79 | 0.00 | 0.00 | 0.00 |
April | 76.46 | 0.43 | 76.03 | 38.82 | 102.63 | 0.00 | 0.00 | 0.00 |
May | 88.58 | 3.68 | 84.90 | 71.98 | 59.62 | 0.00 | 0.00 | 0.00 |
June | 106.85 | 9.26 | 97.59 | 118.86 | 35.94 | 0.00 | 0.00 | 0.00 |
July | 99.52 | 6.91 | 92.61 | 128.31 | 23.48 | 0.00 | 0.00 | 0.00 |
August | 86.08 | 1.69 | 84.38 | 104.49 | 32.82 | 0.00 | 0.00 | 0.00 |
September | 65.18 | 0.04 | 65.14 | 60.67 | 56.89 | 0.00 | 0.00 | 0.00 |
October | 48.69 | 0.00 | 48.69 | 22.47 | 100.44 | 0.00 | 0.00 | 0.00 |
November | 32.72 | 0.00 | 32.72 | 5.27 | 140.43 | 0.00 | 0.00 | 0.00 |
December | 30.33 | 0.00 | 30.33 | 0.16 | 227.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 64.73 | 1.84 | 62.89 | 47.66 | 115.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.33 | 0.00 | 30.33 | 0.00 | 23.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 106.85 | 9.26 | 97.59 | 128.31 | 238.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.99 | 0.00 | 28.99 | 0.00 | 213.49 | 0.00 | 0.00 | 0.00 |
February | 44.17 | 0.00 | 44.17 | 0.62 | 201.77 | 0.00 | 0.00 | 0.00 |
March | 53.58 | 0.00 | 53.57 | 14.98 | 137.60 | 0.00 | 0.00 | 0.00 |
April | 68.41 | 0.39 | 68.02 | 34.74 | 91.82 | 0.00 | 0.00 | 0.00 |
May | 79.25 | 3.29 | 75.96 | 64.40 | 53.34 | 0.00 | 0.00 | 0.00 |
June | 95.60 | 8.28 | 87.32 | 106.35 | 32.15 | 0.00 | 0.00 | 0.00 |
July | 89.04 | 6.18 | 82.85 | 114.80 | 21.01 | 0.00 | 0.00 | 0.00 |
August | 77.01 | 1.51 | 75.50 | 93.48 | 29.37 | 0.00 | 0.00 | 0.00 |
September | 58.32 | 0.03 | 58.28 | 54.28 | 50.90 | 0.00 | 0.00 | 0.00 |
October | 43.56 | 0.00 | 43.56 | 20.11 | 89.86 | 0.00 | 0.00 | 0.00 |
November | 29.27 | 0.00 | 29.27 | 4.72 | 125.65 | 0.00 | 0.00 | 0.00 |
December | 27.14 | 0.00 | 27.14 | 0.14 | 203.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 57.92 | 1.65 | 56.27 | 42.64 | 103.76 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 27.14 | 0.00 | 27.14 | 0.00 | 21.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 95.60 | 8.28 | 87.32 | 114.80 | 213.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 411.30 | 240.21 | 171.09 | 315.14 | 590.03 | 0.00 | 0.00 | 0.00 |
February | 465.79 | 222.77 | 243.02 | 345.92 | 576.82 | 0.00 | 0.00 | 0.00 |
March | 572.35 | 321.56 | 250.79 | 550.91 | 400.32 | 0.00 | 0.00 | 0.00 |
April | 473.37 | 188.73 | 284.64 | 483.12 | 304.30 | 0.00 | 0.00 | 0.00 |
May | 417.43 | 123.06 | 294.38 | 473.07 | 190.60 | 0.00 | 0.00 | 0.00 |
June | 401.80 | 84.13 | 317.67 | 508.02 | 117.19 | 0.00 | 0.00 | 0.00 |
July | 408.40 | 96.75 | 311.65 | 573.15 | 75.44 | 0.00 | 0.00 | 0.00 |
August | 457.31 | 145.11 | 312.20 | 627.74 | 101.71 | 0.00 | 0.00 | 0.00 |
September | 535.29 | 259.78 | 275.51 | 678.20 | 166.54 | 0.00 | 0.00 | 0.00 |
October | 514.76 | 294.30 | 220.46 | 560.69 | 275.89 | 0.00 | 0.00 | 0.00 |
November | 369.23 | 208.91 | 160.32 | 346.63 | 377.15 | 0.00 | 0.00 | 0.00 |
December | 343.93 | 178.27 | 165.66 | 247.20 | 580.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 447.46 | 196.88 | 250.58 | 476.58 | 311.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 343.93 | 84.13 | 160.32 | 247.20 | 75.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 572.35 | 321.56 | 317.67 | 678.20 | 590.03 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.149244E+10 | 0.871616E+09 | 0.620826E+09 | 0.118634E+10 | 0.193463E+10 |
February | 0.152659E+10 | 0.730113E+09 | 0.796480E+09 | 0.119597E+10 | 0.170109E+10 |
March | 0.207681E+10 | 0.116679E+10 | 0.910020E+09 | 0.203730E+10 | 0.134121E+10 |
April | 0.166226E+10 | 0.662735E+09 | 0.999522E+09 | 0.172830E+10 | 0.979047E+09 |
May | 0.151468E+10 | 0.446521E+09 | 0.106816E+10 | 0.175426E+10 | 0.619627E+09 |
June | 0.141093E+10 | 0.295438E+09 | 0.111549E+10 | 0.182040E+10 | 0.367158E+09 |
July | 0.148192E+10 | 0.351066E+09 | 0.113085E+10 | 0.210558E+10 | 0.243738E+09 |
August | 0.165938E+10 | 0.526561E+09 | 0.113282E+10 | 0.229289E+10 | 0.334416E+09 |
September | 0.187970E+10 | 0.912236E+09 | 0.967463E+09 | 0.238633E+10 | 0.539992E+09 |
October | 0.186785E+10 | 0.106791E+10 | 0.799941E+09 | 0.204787E+10 | 0.933166E+09 |
November | 0.129658E+10 | 0.733608E+09 | 0.562970E+09 | 0.123630E+10 | 0.121026E+10 |
December | 0.124798E+10 | 0.646864E+09 | 0.601115E+09 | 0.939424E+09 | 0.188699E+10 |
Annual Sum or Average | 0.191171E+11 | 0.841146E+10 | 0.107057E+11 | 0.207310E+11 | 0.120913E+11 |
Minimum of Months | 0.124798E+10 | 0.295438E+09 | 0.562970E+09 | 0.939424E+09 | 0.243738E+09 |
Maximum of Months | 0.207681E+10 | 0.116679E+10 | 0.113282E+10 | 0.238633E+10 | 0.193463E+10 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.420262E+10 | 0.245441E+10 | 0.174821E+10 | 0.329371E+10 | 0.555584E+10 |
February | 0.429879E+10 | 0.205595E+10 | 0.224284E+10 | 0.331776E+10 | 0.488135E+10 |
March | 0.584817E+10 | 0.328562E+10 | 0.256256E+10 | 0.565331E+10 | 0.395869E+10 |
April | 0.468081E+10 | 0.186622E+10 | 0.281459E+10 | 0.478139E+10 | 0.295391E+10 |
May | 0.426524E+10 | 0.125737E+10 | 0.300787E+10 | 0.482872E+10 | 0.194893E+10 |
June | 0.397308E+10 | 0.831935E+09 | 0.314115E+10 | 0.503076E+10 | 0.116798E+10 |
July | 0.417299E+10 | 0.988579E+09 | 0.318441E+10 | 0.585361E+10 | 0.778328E+09 |
August | 0.467271E+10 | 0.148276E+10 | 0.318995E+10 | 0.638440E+10 | 0.105933E+10 |
September | 0.529311E+10 | 0.256880E+10 | 0.272431E+10 | 0.663165E+10 | 0.170878E+10 |
October | 0.525974E+10 | 0.300716E+10 | 0.225258E+10 | 0.568049E+10 | 0.284769E+10 |
November | 0.365108E+10 | 0.206579E+10 | 0.158529E+10 | 0.341842E+10 | 0.360916E+10 |
December | 0.351423E+10 | 0.182153E+10 | 0.169270E+10 | 0.260576E+10 | 0.543427E+10 |
Annual Sum or Average | 0.538326E+11 | 0.236861E+11 | 0.301464E+11 | 0.574800E+11 | 0.359043E+11 |
Minimum of Months | 0.351423E+10 | 0.831935E+09 | 0.158529E+10 | 0.260576E+10 | 0.778328E+09 |
Maximum of Months | 0.584817E+10 | 0.328562E+10 | 0.318995E+10 | 0.663165E+10 | 0.555584E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.545944E+10 | 0.318842E+10 | 0.227102E+10 | 0.432458E+10 | 0.759553E+10 |
February | 0.558437E+10 | 0.267080E+10 | 0.291357E+10 | 0.435857E+10 | 0.666240E+10 |
March | 0.759711E+10 | 0.426820E+10 | 0.332891E+10 | 0.747262E+10 | 0.537536E+10 |
April | 0.608063E+10 | 0.242432E+10 | 0.365631E+10 | 0.631227E+10 | 0.403281E+10 |
May | 0.554079E+10 | 0.163340E+10 | 0.390739E+10 | 0.638010E+10 | 0.266840E+10 |
June | 0.516126E+10 | 0.108073E+10 | 0.408053E+10 | 0.666168E+10 | 0.158165E+10 |
July | 0.542095E+10 | 0.128422E+10 | 0.413673E+10 | 0.777447E+10 | 0.103714E+10 |
August | 0.607012E+10 | 0.192619E+10 | 0.414393E+10 | 0.846776E+10 | 0.140933E+10 |
September | 0.687605E+10 | 0.333701E+10 | 0.353904E+10 | 0.877389E+10 | 0.230438E+10 |
October | 0.683270E+10 | 0.390647E+10 | 0.292623E+10 | 0.747886E+10 | 0.389957E+10 |
November | 0.474296E+10 | 0.268358E+10 | 0.205938E+10 | 0.449256E+10 | 0.497745E+10 |
December | 0.456518E+10 | 0.236627E+10 | 0.219891E+10 | 0.341921E+10 | 0.745604E+10 |
Annual Sum or Average | 0.699316E+11 | 0.307696E+11 | 0.391619E+11 | 0.759166E+11 | 0.490001E+11 |
Minimum of Months | 0.456518E+10 | 0.108073E+10 | 0.205938E+10 | 0.341921E+10 | 0.103714E+10 |
Maximum of Months | 0.759711E+10 | 0.426820E+10 | 0.414393E+10 | 0.877389E+10 | 0.759553E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.295082E+09 | 0.172333E+09 | 0.122749E+09 | 0.235664E+09 | 0.393639E+09 |
February | 0.301835E+09 | 0.144356E+09 | 0.157479E+09 | 0.235097E+09 | 0.349544E+09 |
March | 0.410623E+09 | 0.230695E+09 | 0.179928E+09 | 0.401555E+09 | 0.272869E+09 |
April | 0.328659E+09 | 0.131034E+09 | 0.197624E+09 | 0.338751E+09 | 0.200232E+09 |
May | 0.299481E+09 | 88284801.45 | 0.211196E+09 | 0.342496E+09 | 0.124060E+09 |
June | 0.278967E+09 | 58413251.87 | 0.220554E+09 | 0.360206E+09 | 66809306.70 |
July | 0.293003E+09 | 69411819.14 | 0.223592E+09 | 0.426150E+09 | 38233398.39 |
August | 0.328090E+09 | 0.104110E+09 | 0.223980E+09 | 0.461498E+09 | 54840040.39 |
September | 0.371650E+09 | 0.180365E+09 | 0.191286E+09 | 0.476444E+09 | 0.100216E+09 |
October | 0.369307E+09 | 0.211144E+09 | 0.158163E+09 | 0.406335E+09 | 0.184330E+09 |
November | 0.256356E+09 | 0.145047E+09 | 0.111309E+09 | 0.245526E+09 | 0.242533E+09 |
December | 0.246747E+09 | 0.127896E+09 | 0.118851E+09 | 0.185736E+09 | 0.384727E+09 |
Annual Sum or Average | 0.377980E+10 | 0.166309E+10 | 0.211671E+10 | 0.411546E+10 | 0.241203E+10 |
Minimum of Months | 0.246747E+09 | 58413251.87 | 0.111309E+09 | 0.185736E+09 | 38233398.39 |
Maximum of Months | 0.410623E+09 | 0.230695E+09 | 0.223980E+09 | 0.476444E+09 | 0.393639E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201500E+09 | 47495878.30 | 0.154004E+09 | 50762266.90 | 0.823087E+09 |
February | 0.295544E+09 | 76547281.39 | 0.218996E+09 | 0.116550E+09 | 0.702756E+09 |
March | 0.512275E+09 | 0.219998E+09 | 0.292277E+09 | 0.398656E+09 | 0.529780E+09 |
April | 0.604369E+09 | 0.247592E+09 | 0.356777E+09 | 0.567770E+09 | 0.360552E+09 |
May | 0.737547E+09 | 0.333676E+09 | 0.403871E+09 | 0.827416E+09 | 0.223721E+09 |
June | 0.860098E+09 | 0.404159E+09 | 0.455939E+09 | 0.109188E+10 | 0.121661E+09 |
July | 0.794440E+09 | 0.347755E+09 | 0.446684E+09 | 0.109192E+10 | 71005164.55 |
August | 0.718166E+09 | 0.304420E+09 | 0.413746E+09 | 0.962647E+09 | 0.101716E+09 |
September | 0.546382E+09 | 0.235695E+09 | 0.310687E+09 | 0.650384E+09 | 0.186148E+09 |
October | 0.367649E+09 | 0.130229E+09 | 0.237420E+09 | 0.323273E+09 | 0.357592E+09 |
November | 0.209628E+09 | 60128040.21 | 0.149500E+09 | 0.119604E+09 | 0.480151E+09 |
December | 0.187434E+09 | 40382403.54 | 0.147052E+09 | 47045360.36 | 0.789430E+09 |
Annual Sum or Average | 0.603503E+10 | 0.244808E+10 | 0.358695E+10 | 0.624791E+10 | 0.474760E+10 |
Minimum of Months | 0.187434E+09 | 40382403.54 | 0.147052E+09 | 47045360.36 | 71005164.55 |
Maximum of Months | 0.860098E+09 | 0.404159E+09 | 0.455939E+09 | 0.109192E+10 | 0.823087E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 68530415.20 | 0.00 | 68530415.20 | 81822.16 | 0.460940E+09 |
February | 94310011.14 | 0.00 | 94310011.14 | 3674157.03 | 0.395348E+09 |
March | 0.126641E+09 | 1824.39 | 0.126639E+09 | 40791647.24 | 0.302778E+09 |
April | 0.156487E+09 | 882160.03 | 0.155605E+09 | 84082651.55 | 0.197633E+09 |
May | 0.187336E+09 | 7782830.51 | 0.179553E+09 | 0.152195E+09 | 0.116414E+09 |
June | 0.218686E+09 | 18947034.31 | 0.199739E+09 | 0.242639E+09 | 67224138.47 |
July | 0.210467E+09 | 14614645.10 | 0.195853E+09 | 0.279650E+09 | 40524728.33 |
August | 0.182042E+09 | 3580014.66 | 0.178462E+09 | 0.226930E+09 | 57848936.46 |
September | 0.133406E+09 | 75507.70 | 0.133330E+09 | 0.127630E+09 | 0.105907E+09 |
October | 0.102968E+09 | 0.00 | 0.102968E+09 | 53474026.26 | 0.195493E+09 |
November | 66959962.50 | 0.00 | 66959962.50 | 14139960.84 | 0.261363E+09 |
December | 64142384.00 | 0.00 | 64142384.00 | 744501.18 | 0.440346E+09 |
Annual Sum or Average | 0.161198E+10 | 45884016.69 | 0.156609E+10 | 0.122603E+10 | 0.264182E+10 |
Minimum of Months | 64142384.00 | 0.00 | 64142384.00 | 81822.16 | 40524728.33 |
Maximum of Months | 0.218686E+09 | 18947034.31 | 0.199739E+09 | 0.279650E+09 | 0.460940E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201500E+09 | 47495878.30 | 0.154004E+09 | 54145063.00 | 0.816426E+09 |
February | 0.295544E+09 | 76547281.39 | 0.218996E+09 | 0.121703E+09 | 0.697684E+09 |
March | 0.512275E+09 | 0.219998E+09 | 0.292277E+09 | 0.410180E+09 | 0.522542E+09 |
April | 0.604369E+09 | 0.247592E+09 | 0.356777E+09 | 0.575526E+09 | 0.357922E+09 |
May | 0.737547E+09 | 0.333676E+09 | 0.403871E+09 | 0.823862E+09 | 0.227389E+09 |
June | 0.860098E+09 | 0.404159E+09 | 0.455939E+09 | 0.107610E+10 | 0.133698E+09 |
July | 0.794440E+09 | 0.347755E+09 | 0.446684E+09 | 0.108040E+10 | 80708192.28 |
August | 0.718166E+09 | 0.304420E+09 | 0.413746E+09 | 0.954687E+09 | 0.111746E+09 |
September | 0.546382E+09 | 0.235695E+09 | 0.310687E+09 | 0.649003E+09 | 0.193429E+09 |
October | 0.367649E+09 | 0.130229E+09 | 0.237420E+09 | 0.332809E+09 | 0.353886E+09 |
November | 0.209628E+09 | 60128040.21 | 0.149500E+09 | 0.126572E+09 | 0.473842E+09 |
December | 0.187434E+09 | 40382403.54 | 0.147052E+09 | 50314915.78 | 0.784261E+09 |
Annual Sum or Average | 0.603503E+10 | 0.244808E+10 | 0.358695E+10 | 0.625529E+10 | 0.475354E+10 |
Minimum of Months | 0.187434E+09 | 40382403.54 | 0.147052E+09 | 50314915.78 | 80708192.28 |
Maximum of Months | 0.860098E+09 | 0.404159E+09 | 0.455939E+09 | 0.108040E+10 | 0.816426E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.236019E+09 | 0.137839E+09 | 98179314.65 | 0.193934E+09 | 0.282824E+09 |
February | 0.241420E+09 | 0.115462E+09 | 0.125958E+09 | 0.196129E+09 | 0.247864E+09 |
March | 0.328433E+09 | 0.184520E+09 | 0.143914E+09 | 0.296007E+09 | 0.270020E+09 |
April | 0.262875E+09 | 0.104806E+09 | 0.158068E+09 | 0.242349E+09 | 0.218771E+09 |
May | 0.239537E+09 | 70613797.98 | 0.168923E+09 | 0.241553E+09 | 0.154275E+09 |
June | 0.223129E+09 | 46721309.88 | 0.176408E+09 | 0.252992E+09 | 95129248.90 |
July | 0.234356E+09 | 55518414.20 | 0.178838E+09 | 0.300927E+09 | 67905484.87 |
August | 0.262420E+09 | 83271556.86 | 0.179149E+09 | 0.333703E+09 | 87909283.34 |
September | 0.297261E+09 | 0.144263E+09 | 0.152998E+09 | 0.350217E+09 | 0.133573E+09 |
October | 0.295387E+09 | 0.168881E+09 | 0.126505E+09 | 0.293913E+09 | 0.214742E+09 |
November | 0.205044E+09 | 0.116014E+09 | 89029868.95 | 0.177296E+09 | 0.256901E+09 |
December | 0.197359E+09 | 0.102297E+09 | 95062038.89 | 0.152741E+09 | 0.283589E+09 |
Annual Sum or Average | 0.302324E+10 | 0.133021E+10 | 0.169303E+10 | 0.303176E+10 | 0.231350E+10 |
Minimum of Months | 0.197359E+09 | 46721309.88 | 89029868.95 | 0.152741E+09 | 67905484.87 |
Maximum of Months | 0.328433E+09 | 0.184520E+09 | 0.179149E+09 | 0.350217E+09 | 0.283589E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54831599.44 | 0.00 | 54831599.44 | 171.99 | 0.386063E+09 |
February | 75458009.98 | 0.00 | 75458009.98 | 1942818.36 | 0.330026E+09 |
March | 0.101326E+09 | 1459.70 | 0.101325E+09 | 31325914.95 | 0.248320E+09 |
April | 0.125206E+09 | 705821.57 | 0.124501E+09 | 68424377.32 | 0.160367E+09 |
May | 0.149888E+09 | 6227089.73 | 0.143661E+09 | 0.130003E+09 | 91532824.08 |
June | 0.174972E+09 | 15159636.67 | 0.159813E+09 | 0.207463E+09 | 49171840.19 |
July | 0.168396E+09 | 11693265.88 | 0.156703E+09 | 0.235755E+09 | 28744166.31 |
August | 0.145653E+09 | 2864391.37 | 0.142789E+09 | 0.192340E+09 | 42441858.57 |
September | 0.106739E+09 | 60414.17 | 0.106678E+09 | 0.108413E+09 | 80991561.17 |
October | 82385417.85 | 0.00 | 82385417.85 | 42400306.37 | 0.160819E+09 |
November | 53575070.74 | 0.00 | 53575070.74 | 10077377.33 | 0.220226E+09 |
December | 51320709.15 | 0.00 | 51320709.15 | 359182.00 | 0.369479E+09 |
Annual Sum or Average | 0.128975E+10 | 36712079.10 | 0.125304E+10 | 0.102851E+10 | 0.216818E+10 |
Minimum of Months | 51320709.15 | 0.00 | 51320709.15 | 171.99 | 28744166.31 |
Maximum of Months | 0.174972E+09 | 15159636.67 | 0.159813E+09 | 0.235755E+09 | 0.386063E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.233977E+09 | 75355657.08 | 0.158622E+09 | 80276547.64 | 0.797979E+09 |
February | 0.312010E+09 | 94512709.61 | 0.217497E+09 | 0.131323E+09 | 0.682292E+09 |
March | 0.495671E+09 | 0.208446E+09 | 0.287225E+09 | 0.375703E+09 | 0.521058E+09 |
April | 0.631427E+09 | 0.278911E+09 | 0.352516E+09 | 0.592064E+09 | 0.347857E+09 |
May | 0.731029E+09 | 0.323430E+09 | 0.407599E+09 | 0.814752E+09 | 0.213523E+09 |
June | 0.789431E+09 | 0.348558E+09 | 0.440873E+09 | 0.993672E+09 | 0.112875E+09 |
July | 0.783424E+09 | 0.344484E+09 | 0.438939E+09 | 0.107433E+10 | 64602013.21 |
August | 0.707599E+09 | 0.296396E+09 | 0.411203E+09 | 0.943794E+09 | 95598447.28 |
September | 0.570434E+09 | 0.253046E+09 | 0.317388E+09 | 0.679216E+09 | 0.178130E+09 |
October | 0.399768E+09 | 0.165145E+09 | 0.234623E+09 | 0.356849E+09 | 0.347117E+09 |
November | 0.219319E+09 | 70227577.39 | 0.149092E+09 | 0.129453E+09 | 0.472211E+09 |
December | 0.182568E+09 | 37820722.34 | 0.144747E+09 | 40202389.57 | 0.780806E+09 |
Annual Sum or Average | 0.605666E+10 | 0.249633E+10 | 0.356032E+10 | 0.621163E+10 | 0.461405E+10 |
Minimum of Months | 0.182568E+09 | 37820722.34 | 0.144747E+09 | 40202389.57 | 64602013.21 |
Maximum of Months | 0.789431E+09 | 0.348558E+09 | 0.440873E+09 | 0.107433E+10 | 0.797979E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.295082E+09 | 0.172333E+09 | 0.122749E+09 | 0.234563E+09 | 0.393762E+09 |
February | 0.301835E+09 | 0.144356E+09 | 0.157479E+09 | 0.233755E+09 | 0.349445E+09 |
March | 0.410623E+09 | 0.230695E+09 | 0.179928E+09 | 0.398853E+09 | 0.271361E+09 |
April | 0.328659E+09 | 0.131034E+09 | 0.197624E+09 | 0.335434E+09 | 0.199336E+09 |
May | 0.299481E+09 | 88284801.45 | 0.211196E+09 | 0.340257E+09 | 0.122748E+09 |
June | 0.278967E+09 | 58413251.87 | 0.220554E+09 | 0.359223E+09 | 65208825.85 |
July | 0.293003E+09 | 69411819.14 | 0.223592E+09 | 0.424732E+09 | 37230815.83 |
August | 0.328090E+09 | 0.104110E+09 | 0.223980E+09 | 0.460391E+09 | 54063271.17 |
September | 0.371650E+09 | 0.180365E+09 | 0.191286E+09 | 0.474538E+09 | 99307517.09 |
October | 0.369307E+09 | 0.211144E+09 | 0.158163E+09 | 0.403983E+09 | 0.183963E+09 |
November | 0.256356E+09 | 0.145047E+09 | 0.111309E+09 | 0.244813E+09 | 0.242335E+09 |
December | 0.246747E+09 | 0.127896E+09 | 0.118851E+09 | 0.185469E+09 | 0.384522E+09 |
Annual Sum or Average | 0.377980E+10 | 0.166309E+10 | 0.211671E+10 | 0.409601E+10 | 0.240328E+10 |
Minimum of Months | 0.246747E+09 | 58413251.87 | 0.111309E+09 | 0.185469E+09 | 37230815.83 |
Maximum of Months | 0.410623E+09 | 0.230695E+09 | 0.223980E+09 | 0.474538E+09 | 0.393762E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 68530415.20 | 0.00 | 68530415.20 | 60786.44 | 0.461592E+09 |
February | 94310011.14 | 0.00 | 94310011.14 | 3346010.51 | 0.395856E+09 |
March | 0.126641E+09 | 1824.39 | 0.126639E+09 | 39118636.74 | 0.302182E+09 |
April | 0.156487E+09 | 882160.03 | 0.155605E+09 | 81065512.03 | 0.197570E+09 |
May | 0.187336E+09 | 7782830.51 | 0.179553E+09 | 0.151586E+09 | 0.114794E+09 |
June | 0.218686E+09 | 18947034.31 | 0.199739E+09 | 0.244187E+09 | 63717580.60 |
July | 0.210467E+09 | 14614645.10 | 0.195853E+09 | 0.277273E+09 | 38871889.47 |
August | 0.182042E+09 | 3580014.66 | 0.178462E+09 | 0.225161E+09 | 56071192.81 |
September | 0.133406E+09 | 75507.70 | 0.133330E+09 | 0.126082E+09 | 0.103292E+09 |
October | 0.102968E+09 | 0.00 | 0.102968E+09 | 51295687.41 | 0.195143E+09 |
November | 66959962.50 | 0.00 | 66959962.50 | 13496796.70 | 0.261157E+09 |
December | 64142384.00 | 0.00 | 64142384.00 | 709970.41 | 0.440497E+09 |
Annual Sum or Average | 0.161198E+10 | 45884016.69 | 0.156609E+10 | 0.121338E+10 | 0.263074E+10 |
Minimum of Months | 64142384.00 | 0.00 | 64142384.00 | 60786.44 | 38871889.47 |
Maximum of Months | 0.218686E+09 | 18947034.31 | 0.199739E+09 | 0.277273E+09 | 0.461592E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.233977E+09 | 75355657.08 | 0.158622E+09 | 82441589.38 | 0.789410E+09 |
February | 0.312010E+09 | 94512709.61 | 0.217497E+09 | 0.135193E+09 | 0.675443E+09 |
March | 0.495671E+09 | 0.208446E+09 | 0.287225E+09 | 0.383435E+09 | 0.509815E+09 |
April | 0.631427E+09 | 0.278911E+09 | 0.352516E+09 | 0.598837E+09 | 0.344955E+09 |
May | 0.731029E+09 | 0.323430E+09 | 0.407599E+09 | 0.814920E+09 | 0.216113E+09 |
June | 0.789431E+09 | 0.348558E+09 | 0.440873E+09 | 0.984548E+09 | 0.122030E+09 |
July | 0.783424E+09 | 0.344484E+09 | 0.438939E+09 | 0.106121E+10 | 73355706.19 |
August | 0.707599E+09 | 0.296396E+09 | 0.411203E+09 | 0.935170E+09 | 0.104200E+09 |
September | 0.570434E+09 | 0.253046E+09 | 0.317388E+09 | 0.680402E+09 | 0.183217E+09 |
October | 0.399768E+09 | 0.165145E+09 | 0.234623E+09 | 0.365808E+09 | 0.342611E+09 |
November | 0.219319E+09 | 70227577.39 | 0.149092E+09 | 0.134610E+09 | 0.464115E+09 |
December | 0.182568E+09 | 37820722.34 | 0.144747E+09 | 41491132.56 | 0.773789E+09 |
Annual Sum or Average | 0.605666E+10 | 0.249633E+10 | 0.356032E+10 | 0.621807E+10 | 0.459905E+10 |
Minimum of Months | 0.182568E+09 | 37820722.34 | 0.144747E+09 | 41491132.56 | 73355706.19 |
Maximum of Months | 0.789431E+09 | 0.348558E+09 | 0.440873E+09 | 0.106121E+10 | 0.789410E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 86789446.82 | 0.00 | 86789446.82 | 0.00 | 0.627466E+09 |
February | 0.119438E+09 | 0.00 | 0.119438E+09 | 2257363.67 | 0.535673E+09 |
March | 0.160383E+09 | 2310.47 | 0.160381E+09 | 48995262.98 | 0.402678E+09 |
April | 0.198181E+09 | 1117200.01 | 0.197064E+09 | 0.108221E+09 | 0.260098E+09 |
May | 0.237249E+09 | 9856463.77 | 0.227392E+09 | 0.203824E+09 | 0.155224E+09 |
June | 0.276953E+09 | 23995223.46 | 0.252957E+09 | 0.320914E+09 | 89275113.77 |
July | 0.266544E+09 | 18508525.88 | 0.248035E+09 | 0.358672E+09 | 58198915.91 |
August | 0.230545E+09 | 4533862.69 | 0.226011E+09 | 0.291856E+09 | 83110191.57 |
September | 0.168950E+09 | 95625.74 | 0.168854E+09 | 0.165252E+09 | 0.144341E+09 |
October | 0.130403E+09 | 0.00 | 0.130403E+09 | 65968805.39 | 0.262152E+09 |
November | 84800567.57 | 0.00 | 84800567.57 | 15594579.69 | 0.354764E+09 |
December | 81232282.17 | 0.00 | 81232282.17 | 510655.19 | 0.599620E+09 |
Annual Sum or Average | 0.204147E+10 | 58109212.02 | 0.198336E+10 | 0.158207E+10 | 0.357260E+10 |
Minimum of Months | 81232282.17 | 0.00 | 81232282.17 | 0.00 | 58198915.91 |
Maximum of Months | 0.276953E+09 | 23995223.46 | 0.252957E+09 | 0.358672E+09 | 0.627466E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 31994183.77 | 0.00 | 31994183.77 | 0.00 | 0.231310E+09 |
February | 44029673.81 | 0.00 | 44029673.81 | 832157.72 | 0.197471E+09 |
March | 59123826.66 | 851.74 | 59122974.93 | 18061682.67 | 0.148444E+09 |
April | 73057843.33 | 411846.18 | 72645997.15 | 39894918.74 | 95882985.71 |
May | 87459788.61 | 3633500.67 | 83826287.94 | 75137797.67 | 57221866.73 |
June | 0.102096E+09 | 8845632.93 | 93250550.55 | 0.118302E+09 | 32910503.53 |
July | 98258997.70 | 6823009.02 | 91435988.69 | 0.132221E+09 | 21454530.23 |
August | 84988325.95 | 1671369.52 | 83316956.43 | 0.107590E+09 | 30637857.93 |
September | 62281914.85 | 35251.61 | 62246663.24 | 60918781.77 | 53210214.39 |
October | 48071809.42 | 0.00 | 48071809.42 | 24318833.22 | 96640434.52 |
November | 31261000.52 | 0.00 | 31261000.52 | 5748807.79 | 0.130781E+09 |
December | 29945582.77 | 0.00 | 29945582.77 | 188248.65 | 0.221045E+09 |
Annual Sum or Average | 0.752569E+09 | 21421461.66 | 0.731148E+09 | 0.583215E+09 | 0.131701E+10 |
Minimum of Months | 29945582.77 | 0.00 | 29945582.77 | 0.00 | 21454530.23 |
Maximum of Months | 0.102096E+09 | 8845632.93 | 93250550.55 | 0.132221E+09 | 0.231310E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.137684E+09 | 80410099.32 | 57273978.71 | 0.107390E+09 | 0.194146E+09 |
February | 0.140835E+09 | 67355863.12 | 73478917.38 | 0.107027E+09 | 0.171360E+09 |
March | 0.191595E+09 | 0.107641E+09 | 83953688.63 | 0.188191E+09 | 0.131379E+09 |
April | 0.153351E+09 | 61140012.77 | 92210720.89 | 0.160422E+09 | 96246314.98 |
May | 0.139736E+09 | 41193332.60 | 98543115.21 | 0.163016E+09 | 61718458.19 |
June | 0.130165E+09 | 27255387.93 | 0.102910E+09 | 0.169702E+09 | 36321406.90 |
July | 0.136714E+09 | 32387275.10 | 0.104327E+09 | 0.197911E+09 | 23340615.41 |
August | 0.153086E+09 | 48577374.90 | 0.104508E+09 | 0.215239E+09 | 32124532.63 |
September | 0.173411E+09 | 84157492.03 | 89253060.55 | 0.223531E+09 | 52679263.41 |
October | 0.172317E+09 | 98518817.23 | 73798234.82 | 0.191318E+09 | 90040035.60 |
November | 0.119615E+09 | 67678273.20 | 51936549.34 | 0.114588E+09 | 0.119041E+09 |
December | 0.115131E+09 | 59675840.18 | 55455481.75 | 84508906.33 | 0.190434E+09 |
Annual Sum or Average | 0.176364E+10 | 0.775991E+09 | 0.987649E+09 | 0.192284E+10 | 0.119883E+10 |
Minimum of Months | 0.115131E+09 | 27255387.93 | 51936549.34 | 84508906.33 | 23340615.41 |
Maximum of Months | 0.191595E+09 | 0.107641E+09 | 0.104508E+09 | 0.223531E+09 | 0.194146E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.373703E+09 | 0.218249E+09 | 0.155453E+09 | 0.291477E+09 | 0.526952E+09 |
February | 0.382254E+09 | 0.182818E+09 | 0.199437E+09 | 0.290492E+09 | 0.465107E+09 |
March | 0.520028E+09 | 0.292161E+09 | 0.227867E+09 | 0.510789E+09 | 0.356590E+09 |
April | 0.416225E+09 | 0.165947E+09 | 0.250279E+09 | 0.435417E+09 | 0.261232E+09 |
May | 0.379273E+09 | 0.111807E+09 | 0.267466E+09 | 0.442459E+09 | 0.167517E+09 |
June | 0.353294E+09 | 73976697.82 | 0.279318E+09 | 0.460606E+09 | 98583727.70 |
July | 0.371070E+09 | 87905689.30 | 0.283165E+09 | 0.537170E+09 | 63351204.43 |
August | 0.415506E+09 | 0.131849E+09 | 0.283657E+09 | 0.584202E+09 | 87192552.49 |
September | 0.470672E+09 | 0.228421E+09 | 0.242251E+09 | 0.606708E+09 | 0.142982E+09 |
October | 0.467704E+09 | 0.267400E+09 | 0.200304E+09 | 0.519277E+09 | 0.244387E+09 |
November | 0.324659E+09 | 0.183693E+09 | 0.140966E+09 | 0.311014E+09 | 0.323102E+09 |
December | 0.312490E+09 | 0.161972E+09 | 0.150518E+09 | 0.229374E+09 | 0.516876E+09 |
Annual Sum or Average | 0.478688E+10 | 0.210620E+10 | 0.268068E+10 | 0.521899E+10 | 0.325387E+10 |
Minimum of Months | 0.312490E+09 | 73976697.82 | 0.140966E+09 | 0.229374E+09 | 63351204.43 |
Maximum of Months | 0.520028E+09 | 0.292161E+09 | 0.283657E+09 | 0.606708E+09 | 0.526952E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.295082E+09 | 0.172333E+09 | 0.122749E+09 | 0.234988E+09 | 0.393364E+09 |
February | 0.301835E+09 | 0.144356E+09 | 0.157479E+09 | 0.233589E+09 | 0.350056E+09 |
March | 0.410623E+09 | 0.230695E+09 | 0.179928E+09 | 0.399554E+09 | 0.272358E+09 |
April | 0.328659E+09 | 0.131034E+09 | 0.197624E+09 | 0.336000E+09 | 0.199939E+09 |
May | 0.299481E+09 | 88284801.45 | 0.211196E+09 | 0.339001E+09 | 0.123498E+09 |
June | 0.278967E+09 | 58413251.87 | 0.220554E+09 | 0.356694E+09 | 66053276.66 |
July | 0.293003E+09 | 69411819.14 | 0.223592E+09 | 0.422788E+09 | 37303940.27 |
August | 0.328090E+09 | 0.104110E+09 | 0.223980E+09 | 0.458241E+09 | 53726666.49 |
September | 0.371650E+09 | 0.180365E+09 | 0.191286E+09 | 0.473598E+09 | 98882442.48 |
October | 0.369307E+09 | 0.211144E+09 | 0.158163E+09 | 0.404432E+09 | 0.182923E+09 |
November | 0.256356E+09 | 0.145047E+09 | 0.111309E+09 | 0.244884E+09 | 0.240821E+09 |
December | 0.246747E+09 | 0.127896E+09 | 0.118851E+09 | 0.184864E+09 | 0.384745E+09 |
Annual Sum or Average | 0.377980E+10 | 0.166309E+10 | 0.211671E+10 | 0.408863E+10 | 0.240367E+10 |
Minimum of Months | 0.246747E+09 | 58413251.87 | 0.111309E+09 | 0.184864E+09 | 37303940.27 |
Maximum of Months | 0.410623E+09 | 0.230695E+09 | 0.223980E+09 | 0.473598E+09 | 0.393364E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201500E+09 | 47495878.30 | 0.154004E+09 | 50933300.87 | 0.823053E+09 |
February | 0.295544E+09 | 76547281.39 | 0.218996E+09 | 0.115920E+09 | 0.703809E+09 |
March | 0.512275E+09 | 0.219998E+09 | 0.292277E+09 | 0.396020E+09 | 0.528307E+09 |
April | 0.604369E+09 | 0.247592E+09 | 0.356777E+09 | 0.562475E+09 | 0.359395E+09 |
May | 0.737547E+09 | 0.333676E+09 | 0.403871E+09 | 0.819838E+09 | 0.222252E+09 |
June | 0.860098E+09 | 0.404159E+09 | 0.455939E+09 | 0.108276E+10 | 0.120123E+09 |
July | 0.794440E+09 | 0.347755E+09 | 0.446684E+09 | 0.108426E+10 | 69227523.30 |
August | 0.718166E+09 | 0.304420E+09 | 0.413746E+09 | 0.956402E+09 | 99607275.49 |
September | 0.546382E+09 | 0.235695E+09 | 0.310687E+09 | 0.645792E+09 | 0.183305E+09 |
October | 0.367649E+09 | 0.130229E+09 | 0.237420E+09 | 0.321449E+09 | 0.354632E+09 |
November | 0.209628E+09 | 60128040.21 | 0.149500E+09 | 0.119813E+09 | 0.476148E+09 |
December | 0.187434E+09 | 40382403.54 | 0.147052E+09 | 47014546.60 | 0.789412E+09 |
Annual Sum or Average | 0.603503E+10 | 0.244808E+10 | 0.358695E+10 | 0.620268E+10 | 0.472927E+10 |
Minimum of Months | 0.187434E+09 | 40382403.54 | 0.147052E+09 | 47014546.60 | 69227523.30 |
Maximum of Months | 0.860098E+09 | 0.404159E+09 | 0.455939E+09 | 0.108426E+10 | 0.823053E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 68530415.20 | 0.00 | 68530415.20 | 99439.78 | 0.460861E+09 |
February | 94310011.14 | 0.00 | 94310011.14 | 3724265.96 | 0.395348E+09 |
March | 0.126641E+09 | 1824.39 | 0.126639E+09 | 41018734.36 | 0.301885E+09 |
April | 0.156487E+09 | 882160.03 | 0.155605E+09 | 83344524.11 | 0.196997E+09 |
May | 0.187336E+09 | 7782830.51 | 0.179553E+09 | 0.149452E+09 | 0.116544E+09 |
June | 0.218686E+09 | 18947034.31 | 0.199739E+09 | 0.238866E+09 | 68452313.55 |
July | 0.210467E+09 | 14614645.10 | 0.195853E+09 | 0.276913E+09 | 40890780.80 |
August | 0.182042E+09 | 3580014.66 | 0.178462E+09 | 0.224890E+09 | 58112482.25 |
September | 0.133406E+09 | 75507.70 | 0.133330E+09 | 0.126412E+09 | 0.105885E+09 |
October | 0.102968E+09 | 0.00 | 0.102968E+09 | 53945774.14 | 0.193626E+09 |
November | 66959962.50 | 0.00 | 66959962.50 | 14729006.71 | 0.258369E+09 |
December | 64142384.00 | 0.00 | 64142384.00 | 795907.49 | 0.439585E+09 |
Annual Sum or Average | 0.161198E+10 | 45884016.69 | 0.156609E+10 | 0.121419E+10 | 0.263656E+10 |
Minimum of Months | 64142384.00 | 0.00 | 64142384.00 | 99439.78 | 40890780.80 |
Maximum of Months | 0.218686E+09 | 18947034.31 | 0.199739E+09 | 0.276913E+09 | 0.460861E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201500E+09 | 47495878.30 | 0.154004E+09 | 53961453.23 | 0.817280E+09 |
February | 0.295544E+09 | 76547281.39 | 0.218996E+09 | 0.120736E+09 | 0.699189E+09 |
March | 0.512275E+09 | 0.219998E+09 | 0.292277E+09 | 0.408316E+09 | 0.521373E+09 |
April | 0.604369E+09 | 0.247592E+09 | 0.356777E+09 | 0.570742E+09 | 0.356626E+09 |
May | 0.737547E+09 | 0.333676E+09 | 0.403871E+09 | 0.814864E+09 | 0.227469E+09 |
June | 0.860098E+09 | 0.404159E+09 | 0.455939E+09 | 0.106442E+10 | 0.135661E+09 |
July | 0.794440E+09 | 0.347755E+09 | 0.446684E+09 | 0.107149E+10 | 81050237.49 |
August | 0.718166E+09 | 0.304420E+09 | 0.413746E+09 | 0.947583E+09 | 0.111801E+09 |
September | 0.546382E+09 | 0.235695E+09 | 0.310687E+09 | 0.643639E+09 | 0.192628E+09 |
October | 0.367649E+09 | 0.130229E+09 | 0.237420E+09 | 0.332044E+09 | 0.350533E+09 |
November | 0.209628E+09 | 60128040.21 | 0.149500E+09 | 0.127589E+09 | 0.469537E+09 |
December | 0.187434E+09 | 40382403.54 | 0.147052E+09 | 50166451.43 | 0.784681E+09 |
Annual Sum or Average | 0.603503E+10 | 0.244808E+10 | 0.358695E+10 | 0.620556E+10 | 0.474783E+10 |
Minimum of Months | 0.187434E+09 | 40382403.54 | 0.147052E+09 | 50166451.43 | 81050237.49 |
Maximum of Months | 0.860098E+09 | 0.404159E+09 | 0.455939E+09 | 0.107149E+10 | 0.817280E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.432766E+09 | 0.252744E+09 | 0.180023E+09 | 0.329725E+09 | 0.596577E+09 |
February | 0.442669E+09 | 0.211712E+09 | 0.230958E+09 | 0.328775E+09 | 0.529071E+09 |
March | 0.602218E+09 | 0.338337E+09 | 0.263882E+09 | 0.570373E+09 | 0.410265E+09 |
April | 0.482009E+09 | 0.192174E+09 | 0.289835E+09 | 0.486212E+09 | 0.297102E+09 |
May | 0.439217E+09 | 0.129478E+09 | 0.309739E+09 | 0.498693E+09 | 0.179563E+09 |
June | 0.409132E+09 | 85668639.80 | 0.323464E+09 | 0.531231E+09 | 92517456.72 |
July | 0.429718E+09 | 0.101799E+09 | 0.327918E+09 | 0.628260E+09 | 51264885.61 |
August | 0.481176E+09 | 0.152688E+09 | 0.328488E+09 | 0.677188E+09 | 76180253.77 |
September | 0.545061E+09 | 0.264522E+09 | 0.280539E+09 | 0.692124E+09 | 0.145442E+09 |
October | 0.541624E+09 | 0.309663E+09 | 0.231961E+09 | 0.581708E+09 | 0.277603E+09 |
November | 0.375971E+09 | 0.212725E+09 | 0.163246E+09 | 0.348058E+09 | 0.369105E+09 |
December | 0.361879E+09 | 0.187572E+09 | 0.174307E+09 | 0.259682E+09 | 0.582244E+09 |
Annual Sum or Average | 0.554344E+10 | 0.243908E+10 | 0.310436E+10 | 0.593203E+10 | 0.360693E+10 |
Minimum of Months | 0.361879E+09 | 85668639.80 | 0.163246E+09 | 0.259682E+09 | 51264885.61 |
Maximum of Months | 0.602218E+09 | 0.338337E+09 | 0.328488E+09 | 0.692124E+09 | 0.596577E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.479695E+09 | 0.00 | 0.479695E+09 | 0.00 | 0.380709E+10 |
February | 0.660145E+09 | 0.00 | 0.660145E+09 | 5350301.78 | 0.326247E+10 |
March | 0.886455E+09 | 12770.23 | 0.886442E+09 | 0.209452E+09 | 0.251849E+10 |
April | 0.109537E+10 | 6174886.32 | 0.108919E+10 | 0.481327E+09 | 0.167377E+10 |
May | 0.131130E+10 | 54477750.25 | 0.125682E+10 | 0.971244E+09 | 0.994867E+09 |
June | 0.153075E+10 | 0.132624E+09 | 0.139812E+10 | 0.164526E+10 | 0.555302E+09 |
July | 0.147322E+10 | 0.102299E+09 | 0.137092E+10 | 0.188421E+10 | 0.360832E+09 |
August | 0.127425E+10 | 25059153.55 | 0.124919E+10 | 0.152642E+10 | 0.510386E+09 |
September | 0.933804E+09 | 528533.88 | 0.933276E+09 | 0.826181E+09 | 0.901897E+09 |
October | 0.720750E+09 | 0.00 | 0.720750E+09 | 0.279939E+09 | 0.170319E+10 |
November | 0.468702E+09 | 0.00 | 0.468702E+09 | 55051357.41 | 0.228999E+10 |
December | 0.448980E+09 | 0.00 | 0.448980E+09 | 1349660.78 | 0.366035E+10 |
Annual Sum or Average | 0.112834E+11 | 0.321176E+09 | 0.109622E+11 | 0.788578E+10 | 0.222386E+11 |
Minimum of Months | 0.448980E+09 | 0.00 | 0.448980E+09 | 0.00 | 0.360832E+09 |
Maximum of Months | 0.153075E+10 | 0.132624E+09 | 0.139812E+10 | 0.188421E+10 | 0.380709E+10 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.479695E+09 | 0.00 | 0.479695E+09 | 0.00 | 0.390621E+10 |
February | 0.660145E+09 | 0.00 | 0.660145E+09 | 3801253.73 | 0.335097E+10 |
March | 0.886455E+09 | 12770.23 | 0.886442E+09 | 0.194291E+09 | 0.258929E+10 |
April | 0.109537E+10 | 6174886.32 | 0.108919E+10 | 0.453720E+09 | 0.171916E+10 |
May | 0.131130E+10 | 54477750.25 | 0.125682E+10 | 0.938897E+09 | 0.102134E+10 |
June | 0.153075E+10 | 0.132624E+09 | 0.139812E+10 | 0.161787E+10 | 0.571030E+09 |
July | 0.147322E+10 | 0.102299E+09 | 0.137092E+10 | 0.186069E+10 | 0.373595E+09 |
August | 0.127425E+10 | 25059153.55 | 0.124919E+10 | 0.150377E+10 | 0.527201E+09 |
September | 0.933804E+09 | 528533.88 | 0.933276E+09 | 0.803254E+09 | 0.928660E+09 |
October | 0.720750E+09 | 0.00 | 0.720750E+09 | 0.258528E+09 | 0.175559E+10 |
November | 0.468702E+09 | 0.00 | 0.468702E+09 | 48479014.80 | 0.236627E+10 |
December | 0.448980E+09 | 0.00 | 0.448980E+09 | 984874.65 | 0.375801E+10 |
Annual Sum or Average | 0.112834E+11 | 0.321176E+09 | 0.109622E+11 | 0.768429E+10 | 0.228673E+11 |
Minimum of Months | 0.448980E+09 | 0.00 | 0.448980E+09 | 0.00 | 0.373595E+09 |
Maximum of Months | 0.153075E+10 | 0.132624E+09 | 0.139812E+10 | 0.186069E+10 | 0.390621E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 68530415.20 | 0.00 | 68530415.20 | 163459.01 | 0.486704E+09 |
February | 94310011.14 | 0.00 | 94310011.14 | 3134990.74 | 0.417400E+09 |
March | 0.126641E+09 | 1824.39 | 0.126639E+09 | 47377507.34 | 0.318281E+09 |
April | 0.156487E+09 | 882160.03 | 0.155605E+09 | 0.102183E+09 | 0.212882E+09 |
May | 0.187336E+09 | 7782830.51 | 0.179553E+09 | 0.193495E+09 | 0.130003E+09 |
June | 0.218686E+09 | 18947034.31 | 0.199739E+09 | 0.301880E+09 | 76373444.04 |
July | 0.210467E+09 | 14614645.10 | 0.195853E+09 | 0.344338E+09 | 50116883.81 |
August | 0.182042E+09 | 3580014.66 | 0.178462E+09 | 0.286958E+09 | 66678043.74 |
September | 0.133406E+09 | 75507.70 | 0.133330E+09 | 0.167454E+09 | 0.110768E+09 |
October | 0.102968E+09 | 0.00 | 0.102968E+09 | 67139584.05 | 0.207390E+09 |
November | 66959962.50 | 0.00 | 66959962.50 | 17382260.30 | 0.278692E+09 |
December | 64142384.00 | 0.00 | 64142384.00 | 921321.47 | 0.466672E+09 |
Annual Sum or Average | 0.161198E+10 | 45884016.69 | 0.156609E+10 | 0.153243E+10 | 0.282196E+10 |
Minimum of Months | 64142384.00 | 0.00 | 64142384.00 | 163459.01 | 50116883.81 |
Maximum of Months | 0.218686E+09 | 18947034.31 | 0.199739E+09 | 0.344338E+09 | 0.486704E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.467921E+09 | 0.150701E+09 | 0.317221E+09 | 0.168796E+09 | 0.167108E+10 |
February | 0.623975E+09 | 0.189012E+09 | 0.434963E+09 | 0.275502E+09 | 0.143762E+10 |
March | 0.991272E+09 | 0.416862E+09 | 0.574409E+09 | 0.810328E+09 | 0.108861E+10 |
April | 0.126276E+10 | 0.557782E+09 | 0.704981E+09 | 0.128859E+10 | 0.757386E+09 |
May | 0.146195E+10 | 0.646815E+09 | 0.815139E+09 | 0.178754E+10 | 0.488653E+09 |
June | 0.157875E+10 | 0.697066E+09 | 0.881683E+09 | 0.218301E+10 | 0.286897E+09 |
July | 0.156674E+10 | 0.688920E+09 | 0.877817E+09 | 0.237356E+10 | 0.187985E+09 |
August | 0.141510E+10 | 0.592750E+09 | 0.822347E+09 | 0.210270E+10 | 0.248998E+09 |
September | 0.114079E+10 | 0.506056E+09 | 0.634732E+09 | 0.152833E+10 | 0.401700E+09 |
October | 0.799480E+09 | 0.330267E+09 | 0.469212E+09 | 0.805199E+09 | 0.738026E+09 |
November | 0.438607E+09 | 0.140445E+09 | 0.298162E+09 | 0.290168E+09 | 0.999567E+09 |
December | 0.365110E+09 | 75636073.19 | 0.289474E+09 | 86417391.13 | 0.165259E+10 |
Annual Sum or Average | 0.121125E+11 | 0.499231E+10 | 0.712014E+10 | 0.137001E+11 | 0.995911E+10 |
Minimum of Months | 0.365110E+09 | 75636073.19 | 0.289474E+09 | 86417391.13 | 0.187985E+09 |
Maximum of Months | 0.157875E+10 | 0.697066E+09 | 0.881683E+09 | 0.237356E+10 | 0.167108E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.295082E+09 | 0.172333E+09 | 0.122749E+09 | 0.237573E+09 | 0.415277E+09 |
February | 0.301835E+09 | 0.144356E+09 | 0.157479E+09 | 0.235334E+09 | 0.370342E+09 |
March | 0.410623E+09 | 0.230695E+09 | 0.179928E+09 | 0.418103E+09 | 0.287342E+09 |
April | 0.328659E+09 | 0.131034E+09 | 0.197624E+09 | 0.362429E+09 | 0.215336E+09 |
May | 0.299481E+09 | 88284801.45 | 0.211196E+09 | 0.380105E+09 | 0.138779E+09 |
June | 0.278967E+09 | 58413251.87 | 0.220554E+09 | 0.408934E+09 | 81573569.18 |
July | 0.293003E+09 | 69411819.14 | 0.223592E+09 | 0.482351E+09 | 52772301.43 |
August | 0.328090E+09 | 0.104110E+09 | 0.223980E+09 | 0.516170E+09 | 68614431.56 |
September | 0.371650E+09 | 0.180365E+09 | 0.191286E+09 | 0.518957E+09 | 0.110878E+09 |
October | 0.369307E+09 | 0.211144E+09 | 0.158163E+09 | 0.430698E+09 | 0.197991E+09 |
November | 0.256356E+09 | 0.145047E+09 | 0.111309E+09 | 0.255338E+09 | 0.260596E+09 |
December | 0.246747E+09 | 0.127896E+09 | 0.118851E+09 | 0.186453E+09 | 0.409671E+09 |
Annual Sum or Average | 0.377980E+10 | 0.166309E+10 | 0.211671E+10 | 0.443245E+10 | 0.260917E+10 |
Minimum of Months | 0.246747E+09 | 58413251.87 | 0.111309E+09 | 0.186453E+09 | 52772301.43 |
Maximum of Months | 0.410623E+09 | 0.230695E+09 | 0.223980E+09 | 0.518957E+09 | 0.415277E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 86789446.82 | 0.00 | 86789446.82 | 0.00 | 0.639112E+09 |
February | 0.119438E+09 | 0.00 | 0.119438E+09 | 1673489.47 | 0.545559E+09 |
March | 0.160383E+09 | 2310.47 | 0.160381E+09 | 44856520.85 | 0.411919E+09 |
April | 0.198181E+09 | 1117200.01 | 0.197064E+09 | 0.100631E+09 | 0.266016E+09 |
May | 0.237249E+09 | 9856463.77 | 0.227392E+09 | 0.192779E+09 | 0.159693E+09 |
June | 0.276953E+09 | 23995223.46 | 0.252957E+09 | 0.308096E+09 | 93152841.19 |
July | 0.266544E+09 | 18508525.88 | 0.248035E+09 | 0.343672E+09 | 62901227.41 |
August | 0.230545E+09 | 4533862.69 | 0.226011E+09 | 0.279853E+09 | 87909938.62 |
September | 0.168950E+09 | 95625.74 | 0.168854E+09 | 0.157257E+09 | 0.147471E+09 |
October | 0.130403E+09 | 0.00 | 0.130403E+09 | 60187276.94 | 0.269020E+09 |
November | 84800567.57 | 0.00 | 84800567.57 | 13664106.89 | 0.364006E+09 |
December | 81232282.17 | 0.00 | 81232282.17 | 432077.69 | 0.610655E+09 |
Annual Sum or Average | 0.204147E+10 | 58109212.02 | 0.198336E+10 | 0.150310E+10 | 0.365741E+10 |
Minimum of Months | 81232282.17 | 0.00 | 81232282.17 | 0.00 | 62901227.41 |
Maximum of Months | 0.276953E+09 | 23995223.46 | 0.252957E+09 | 0.343672E+09 | 0.639112E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 77650846.92 | 0.00 | 77650846.92 | 0.00 | 0.571802E+09 |
February | 0.106861E+09 | 0.00 | 0.106861E+09 | 1497277.37 | 0.488115E+09 |
March | 0.143495E+09 | 2067.19 | 0.143493E+09 | 40133299.17 | 0.368546E+09 |
April | 0.177314E+09 | 999563.08 | 0.176314E+09 | 90034761.41 | 0.238005E+09 |
May | 0.212268E+09 | 8818615.48 | 0.203449E+09 | 0.172480E+09 | 0.142878E+09 |
June | 0.247791E+09 | 21468617.35 | 0.226322E+09 | 0.275654E+09 | 83344199.97 |
July | 0.238478E+09 | 16559648.24 | 0.221918E+09 | 0.307484E+09 | 56277966.50 |
August | 0.206269E+09 | 4056464.12 | 0.202213E+09 | 0.250385E+09 | 78653355.17 |
September | 0.151160E+09 | 85556.71 | 0.151075E+09 | 0.140698E+09 | 0.131943E+09 |
October | 0.116672E+09 | 0.00 | 0.116672E+09 | 53849784.72 | 0.240694E+09 |
November | 75871389.11 | 0.00 | 75871389.11 | 12225328.20 | 0.325672E+09 |
December | 72678830.65 | 0.00 | 72678830.65 | 386581.54 | 0.546344E+09 |
Annual Sum or Average | 0.182651E+10 | 51990532.17 | 0.177452E+10 | 0.134483E+10 | 0.327227E+10 |
Minimum of Months | 72678830.65 | 0.00 | 72678830.65 | 0.00 | 56277966.50 |
Maximum of Months | 0.247791E+09 | 21468617.35 | 0.226322E+09 | 0.307484E+09 | 0.571802E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.110163E+10 | 0.643372E+09 | 0.458257E+09 | 0.844069E+09 | 0.158034E+10 |
February | 0.112684E+10 | 0.538923E+09 | 0.587915E+09 | 0.836843E+09 | 0.139545E+10 |
March | 0.153298E+10 | 0.861254E+09 | 0.671725E+09 | 0.147556E+10 | 0.107223E+10 |
April | 0.122698E+10 | 0.489190E+09 | 0.737791E+09 | 0.125225E+10 | 0.788736E+09 |
May | 0.111805E+10 | 0.329593E+09 | 0.788457E+09 | 0.126708E+10 | 0.510503E+09 |
June | 0.104147E+10 | 0.218074E+09 | 0.823394E+09 | 0.131679E+10 | 0.303766E+09 |
July | 0.109387E+10 | 0.259135E+09 | 0.834734E+09 | 0.153512E+10 | 0.202068E+09 |
August | 0.122486E+10 | 0.388674E+09 | 0.836185E+09 | 0.168134E+10 | 0.272427E+09 |
September | 0.138748E+10 | 0.673356E+09 | 0.714126E+09 | 0.175791E+10 | 0.431667E+09 |
October | 0.137873E+10 | 0.788262E+09 | 0.590470E+09 | 0.150175E+10 | 0.738951E+09 |
November | 0.957055E+09 | 0.541503E+09 | 0.415551E+09 | 0.898472E+09 | 0.977566E+09 |
December | 0.921181E+09 | 0.477475E+09 | 0.443707E+09 | 0.662112E+09 | 0.155371E+10 |
Annual Sum or Average | 0.141111E+11 | 0.620881E+10 | 0.790231E+10 | 0.150293E+11 | 0.982741E+10 |
Minimum of Months | 0.921181E+09 | 0.218074E+09 | 0.415551E+09 | 0.662112E+09 | 0.202068E+09 |
Maximum of Months | 0.153298E+10 | 0.861254E+09 | 0.836185E+09 | 0.175791E+10 | 0.158034E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 442.93 | 722.31 | 557.21 | 325.42 | 231.79 | 0.00 | 0.00 |
February | 494.36 | 703.16 | 631.03 | 301.80 | 329.23 | 0.00 | 0.00 |
March | 760.64 | 500.75 | 775.39 | 435.63 | 339.76 | 0.00 | 0.00 |
April | 666.78 | 377.72 | 641.30 | 255.68 | 385.62 | 0.00 | 0.00 |
May | 654.96 | 231.34 | 565.52 | 166.71 | 398.81 | 0.00 | 0.00 |
June | 702.32 | 141.65 | 544.34 | 113.98 | 430.36 | 0.00 | 0.00 |
July | 786.13 | 91.00 | 553.29 | 131.07 | 422.21 | 0.00 | 0.00 |
August | 856.07 | 124.86 | 619.54 | 196.60 | 422.95 | 0.00 | 0.00 |
September | 920.65 | 208.33 | 725.19 | 351.94 | 373.25 | 0.00 | 0.00 |
October | 764.59 | 348.40 | 697.37 | 398.71 | 298.66 | 0.00 | 0.00 |
November | 476.97 | 466.92 | 500.22 | 283.03 | 217.20 | 0.00 | 0.00 |
December | 350.74 | 704.52 | 465.94 | 241.51 | 224.43 | 0.00 | 0.00 |
Annual Sum or Average | 657.37 | 383.41 | 606.20 | 266.73 | 339.47 | 0.00 | 0.00 |
Minimum of Months | 350.74 | 91.00 | 465.94 | 113.98 | 217.20 | 0.00 | 0.00 |
Maximum of Months | 920.65 | 722.31 | 775.39 | 435.63 | 430.36 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1229.73 | 2074.31 | 1569.08 | 916.37 | 652.71 | 0.00 | 0.00 |
February | 1371.43 | 2017.75 | 1776.95 | 849.85 | 927.10 | 0.00 | 0.00 |
March | 2110.70 | 1478.01 | 2183.46 | 1226.71 | 956.75 | 0.00 | 0.00 |
April | 1844.67 | 1139.63 | 1805.87 | 719.99 | 1085.87 | 0.00 | 0.00 |
May | 1802.84 | 727.65 | 1592.46 | 469.45 | 1123.01 | 0.00 | 0.00 |
June | 1940.88 | 450.61 | 1532.82 | 320.96 | 1211.86 | 0.00 | 0.00 |
July | 2185.49 | 290.59 | 1558.02 | 369.09 | 1188.92 | 0.00 | 0.00 |
August | 2383.66 | 395.51 | 1744.59 | 553.60 | 1190.99 | 0.00 | 0.00 |
September | 2558.51 | 659.25 | 2042.09 | 991.05 | 1051.05 | 0.00 | 0.00 |
October | 2120.85 | 1063.21 | 1963.76 | 1122.74 | 841.02 | 0.00 | 0.00 |
November | 1318.83 | 1392.42 | 1408.59 | 796.99 | 611.61 | 0.00 | 0.00 |
December | 972.88 | 2028.92 | 1312.06 | 680.08 | 631.98 | 0.00 | 0.00 |
Annual Sum or Average | 1822.68 | 1138.52 | 1707.02 | 751.08 | 955.94 | 0.00 | 0.00 |
Minimum of Months | 972.88 | 290.59 | 1312.06 | 320.96 | 611.61 | 0.00 | 0.00 |
Maximum of Months | 2558.51 | 2074.31 | 2183.46 | 1226.71 | 1211.86 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1614.61 | 2835.85 | 2038.32 | 1190.42 | 847.90 | 0.00 | 0.00 |
February | 1801.66 | 2753.97 | 2308.35 | 1104.00 | 1204.35 | 0.00 | 0.00 |
March | 2789.96 | 2006.93 | 2836.44 | 1593.56 | 1242.87 | 0.00 | 0.00 |
April | 2435.29 | 1555.87 | 2345.92 | 935.31 | 1410.61 | 0.00 | 0.00 |
May | 2382.06 | 996.27 | 2068.69 | 609.84 | 1458.85 | 0.00 | 0.00 |
June | 2570.09 | 610.21 | 1991.23 | 416.95 | 1574.28 | 0.00 | 0.00 |
July | 2902.66 | 387.22 | 2023.95 | 479.47 | 1544.48 | 0.00 | 0.00 |
August | 3161.50 | 526.18 | 2266.32 | 719.16 | 1547.16 | 0.00 | 0.00 |
September | 3384.99 | 889.03 | 2652.80 | 1287.43 | 1365.37 | 0.00 | 0.00 |
October | 2792.29 | 1455.93 | 2551.04 | 1458.51 | 1092.53 | 0.00 | 0.00 |
November | 1733.24 | 1920.31 | 1829.85 | 1035.33 | 794.51 | 0.00 | 0.00 |
December | 1276.59 | 2783.77 | 1704.44 | 883.46 | 820.98 | 0.00 | 0.00 |
Annual Sum or Average | 2407.30 | 1553.78 | 2217.52 | 975.70 | 1241.82 | 0.00 | 0.00 |
Minimum of Months | 1276.59 | 387.22 | 1704.44 | 416.95 | 794.51 | 0.00 | 0.00 |
Maximum of Months | 3384.99 | 2835.85 | 2836.44 | 1593.56 | 1574.28 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 87.67 | 435.01 | 185.40 | 82.07 | 103.33 | 0.00 | 0.00 |
February | 132.46 | 422.09 | 246.93 | 91.31 | 155.62 | 0.00 | 0.00 |
March | 287.88 | 288.79 | 344.57 | 168.27 | 176.30 | 0.00 | 0.00 |
April | 346.30 | 212.92 | 359.96 | 146.08 | 213.89 | 0.00 | 0.00 |
May | 435.43 | 128.48 | 387.18 | 157.54 | 229.64 | 0.00 | 0.00 |
June | 559.60 | 72.10 | 439.45 | 178.46 | 260.99 | 0.00 | 0.00 |
July | 566.70 | 40.71 | 406.00 | 155.75 | 250.25 | 0.00 | 0.00 |
August | 531.61 | 58.34 | 390.63 | 152.53 | 238.10 | 0.00 | 0.00 |
September | 433.82 | 109.57 | 354.18 | 160.52 | 193.66 | 0.00 | 0.00 |
October | 269.00 | 198.93 | 275.15 | 127.45 | 147.69 | 0.00 | 0.00 |
November | 135.72 | 273.67 | 179.78 | 79.16 | 100.62 | 0.00 | 0.00 |
December | 74.25 | 425.72 | 162.10 | 62.83 | 99.28 | 0.00 | 0.00 |
Annual Sum or Average | 322.74 | 221.15 | 311.23 | 130.36 | 180.86 | 0.00 | 0.00 |
Minimum of Months | 74.25 | 40.71 | 162.10 | 62.83 | 99.28 | 0.00 | 0.00 |
Maximum of Months | 566.70 | 435.01 | 439.45 | 178.46 | 260.99 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 15.26 | 471.93 | 100.82 | 17.73 | 83.08 | 0.00 | 0.00 |
February | 45.53 | 445.52 | 161.15 | 31.64 | 129.51 | 0.00 | 0.00 |
March | 160.58 | 300.34 | 238.54 | 82.14 | 156.41 | 0.00 | 0.00 |
April | 251.95 | 211.81 | 293.54 | 95.86 | 197.68 | 0.00 | 0.00 |
May | 363.44 | 127.38 | 345.31 | 127.49 | 217.83 | 0.00 | 0.00 |
June | 506.82 | 75.57 | 416.20 | 163.24 | 252.96 | 0.00 | 0.00 |
July | 506.50 | 43.98 | 375.19 | 135.29 | 239.90 | 0.00 | 0.00 |
August | 440.58 | 62.73 | 336.10 | 114.99 | 221.11 | 0.00 | 0.00 |
September | 298.67 | 114.53 | 262.26 | 90.96 | 171.30 | 0.00 | 0.00 |
October | 142.56 | 203.45 | 175.71 | 48.62 | 127.09 | 0.00 | 0.00 |
November | 51.99 | 281.35 | 106.71 | 23.20 | 83.51 | 0.00 | 0.00 |
December | 14.61 | 452.77 | 93.93 | 15.08 | 78.85 | 0.00 | 0.00 |
Annual Sum or Average | 234.27 | 231.54 | 242.49 | 79.08 | 163.40 | 0.00 | 0.00 |
Minimum of Months | 14.61 | 43.98 | 93.93 | 15.08 | 78.85 | 0.00 | 0.00 |
Maximum of Months | 506.82 | 471.93 | 416.20 | 163.24 | 252.96 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 72.41 | 105.59 | 88.12 | 51.46 | 36.66 | 0.00 | 0.00 |
February | 81.07 | 102.46 | 99.79 | 47.73 | 52.07 | 0.00 | 0.00 |
March | 110.52 | 100.81 | 122.62 | 68.89 | 53.73 | 0.00 | 0.00 |
April | 93.50 | 84.40 | 101.42 | 40.43 | 60.98 | 0.00 | 0.00 |
May | 90.19 | 57.60 | 89.43 | 26.36 | 63.07 | 0.00 | 0.00 |
June | 97.60 | 36.70 | 86.08 | 18.03 | 68.06 | 0.00 | 0.00 |
July | 112.35 | 25.35 | 87.50 | 20.73 | 66.77 | 0.00 | 0.00 |
August | 124.59 | 32.82 | 97.98 | 31.09 | 66.89 | 0.00 | 0.00 |
September | 135.11 | 51.53 | 114.68 | 55.66 | 59.03 | 0.00 | 0.00 |
October | 109.73 | 80.18 | 110.28 | 63.05 | 47.23 | 0.00 | 0.00 |
November | 68.40 | 99.11 | 79.11 | 44.76 | 34.35 | 0.00 | 0.00 |
December | 57.03 | 105.88 | 73.69 | 38.19 | 35.49 | 0.00 | 0.00 |
Annual Sum or Average | 96.14 | 73.36 | 95.87 | 42.18 | 53.69 | 0.00 | 0.00 |
Minimum of Months | 57.03 | 25.35 | 73.69 | 18.03 | 34.35 | 0.00 | 0.00 |
Maximum of Months | 135.11 | 105.88 | 122.62 | 68.89 | 68.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 144.14 | 20.47 | 0.00 | 20.47 | 0.00 | 0.00 |
February | 0.80 | 136.42 | 31.19 | 0.00 | 31.19 | 0.00 | 0.00 |
March | 11.70 | 92.71 | 37.83 | 0.00 | 37.83 | 0.00 | 0.00 |
April | 26.40 | 61.87 | 48.30 | 0.27 | 48.03 | 0.00 | 0.00 |
May | 48.54 | 34.17 | 55.96 | 2.32 | 53.64 | 0.00 | 0.00 |
June | 80.04 | 18.97 | 67.50 | 5.85 | 61.66 | 0.00 | 0.00 |
July | 88.02 | 10.73 | 62.87 | 4.37 | 58.51 | 0.00 | 0.00 |
August | 71.81 | 15.85 | 54.38 | 1.07 | 53.31 | 0.00 | 0.00 |
September | 41.83 | 31.25 | 41.18 | 0.02 | 41.16 | 0.00 | 0.00 |
October | 15.83 | 60.04 | 30.76 | 0.00 | 30.76 | 0.00 | 0.00 |
November | 3.89 | 84.96 | 20.67 | 0.00 | 20.67 | 0.00 | 0.00 |
December | 0.13 | 137.95 | 19.16 | 0.00 | 19.16 | 0.00 | 0.00 |
Annual Sum or Average | 32.61 | 68.75 | 40.90 | 1.16 | 39.73 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 10.73 | 19.16 | 0.00 | 19.16 | 0.00 | 0.00 |
Maximum of Months | 88.02 | 144.14 | 67.50 | 5.85 | 61.66 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 104.51 | 431.91 | 197.53 | 92.48 | 105.05 | 0.00 | 0.00 |
February | 141.81 | 417.38 | 253.74 | 98.74 | 155.00 | 0.00 | 0.00 |
March | 279.33 | 286.00 | 338.37 | 163.96 | 174.42 | 0.00 | 0.00 |
April | 353.69 | 206.96 | 370.40 | 158.16 | 212.25 | 0.00 | 0.00 |
May | 428.52 | 122.83 | 384.75 | 153.72 | 231.03 | 0.00 | 0.00 |
June | 520.23 | 66.99 | 412.19 | 157.01 | 255.18 | 0.00 | 0.00 |
July | 558.72 | 37.06 | 401.89 | 154.53 | 247.36 | 0.00 | 0.00 |
August | 523.27 | 54.89 | 386.68 | 149.53 | 237.15 | 0.00 | 0.00 |
September | 443.63 | 105.55 | 363.46 | 167.21 | 196.25 | 0.00 | 0.00 |
October | 282.27 | 196.49 | 287.14 | 140.49 | 146.65 | 0.00 | 0.00 |
November | 140.52 | 271.80 | 183.52 | 83.05 | 100.46 | 0.00 | 0.00 |
December | 71.82 | 422.64 | 160.29 | 61.87 | 98.42 | 0.00 | 0.00 |
Annual Sum or Average | 321.68 | 217.35 | 311.91 | 131.89 | 180.02 | 0.00 | 0.00 |
Minimum of Months | 71.82 | 37.06 | 160.29 | 61.87 | 98.42 | 0.00 | 0.00 |
Maximum of Months | 558.72 | 431.91 | 412.19 | 167.21 | 255.18 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 21.85 | 458.12 | 112.94 | 28.13 | 84.81 | 0.00 | 0.00 |
February | 48.14 | 433.71 | 167.96 | 39.07 | 128.89 | 0.00 | 0.00 |
March | 148.81 | 294.21 | 232.34 | 77.83 | 154.52 | 0.00 | 0.00 |
April | 257.88 | 204.88 | 303.98 | 107.94 | 196.03 | 0.00 | 0.00 |
May | 359.24 | 121.94 | 342.88 | 123.66 | 219.22 | 0.00 | 0.00 |
June | 473.09 | 70.70 | 388.93 | 141.78 | 247.15 | 0.00 | 0.00 |
July | 499.50 | 41.67 | 371.08 | 134.07 | 237.00 | 0.00 | 0.00 |
August | 432.89 | 59.52 | 332.15 | 112.00 | 220.16 | 0.00 | 0.00 |
September | 309.25 | 108.65 | 271.54 | 97.65 | 173.89 | 0.00 | 0.00 |
October | 152.30 | 197.34 | 187.70 | 61.66 | 126.04 | 0.00 | 0.00 |
November | 53.92 | 276.59 | 110.45 | 27.09 | 83.35 | 0.00 | 0.00 |
December | 11.00 | 448.60 | 92.11 | 14.12 | 77.99 | 0.00 | 0.00 |
Annual Sum or Average | 231.69 | 225.29 | 243.17 | 80.61 | 162.56 | 0.00 | 0.00 |
Minimum of Months | 11.00 | 41.67 | 92.11 | 14.12 | 77.99 | 0.00 | 0.00 |
Maximum of Months | 499.50 | 458.12 | 388.93 | 141.78 | 247.15 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 118.35 | 559.29 | 235.28 | 111.51 | 123.77 | 0.00 | 0.00 |
February | 143.38 | 543.92 | 283.79 | 103.41 | 180.38 | 0.00 | 0.00 |
March | 270.47 | 372.41 | 347.64 | 149.27 | 198.37 | 0.00 | 0.00 |
April | 286.01 | 274.24 | 324.39 | 88.20 | 236.19 | 0.00 | 0.00 |
May | 328.23 | 162.92 | 315.01 | 62.16 | 252.85 | 0.00 | 0.00 |
June | 409.30 | 95.86 | 332.76 | 51.73 | 281.03 | 0.00 | 0.00 |
July | 455.91 | 60.29 | 325.79 | 54.37 | 271.42 | 0.00 | 0.00 |
August | 446.76 | 86.16 | 330.09 | 69.68 | 260.41 | 0.00 | 0.00 |
September | 407.15 | 151.29 | 337.70 | 120.64 | 217.05 | 0.00 | 0.00 |
October | 294.27 | 254.07 | 305.59 | 136.62 | 168.97 | 0.00 | 0.00 |
November | 163.31 | 348.78 | 216.18 | 96.98 | 119.20 | 0.00 | 0.00 |
December | 93.91 | 546.94 | 201.16 | 82.75 | 118.41 | 0.00 | 0.00 |
Annual Sum or Average | 285.57 | 286.68 | 296.31 | 93.92 | 202.40 | 0.00 | 0.00 |
Minimum of Months | 93.91 | 60.29 | 201.16 | 51.73 | 118.41 | 0.00 | 0.00 |
Maximum of Months | 455.91 | 559.29 | 347.64 | 149.27 | 281.03 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 87.63 | 435.03 | 185.40 | 82.07 | 103.33 | 0.00 | 0.00 |
February | 131.54 | 422.69 | 246.93 | 91.31 | 155.62 | 0.00 | 0.00 |
March | 286.19 | 288.09 | 344.57 | 168.27 | 176.30 | 0.00 | 0.00 |
April | 343.16 | 212.32 | 359.96 | 146.08 | 213.89 | 0.00 | 0.00 |
May | 431.23 | 127.66 | 387.18 | 157.54 | 229.64 | 0.00 | 0.00 |
June | 554.70 | 71.18 | 439.45 | 178.46 | 260.99 | 0.00 | 0.00 |
July | 562.58 | 39.69 | 406.00 | 155.75 | 250.25 | 0.00 | 0.00 |
August | 528.05 | 57.13 | 390.63 | 152.53 | 238.10 | 0.00 | 0.00 |
September | 430.96 | 107.96 | 354.18 | 160.52 | 193.66 | 0.00 | 0.00 |
October | 267.71 | 197.40 | 275.15 | 127.45 | 147.69 | 0.00 | 0.00 |
November | 135.70 | 271.61 | 179.78 | 79.16 | 100.62 | 0.00 | 0.00 |
December | 73.95 | 425.75 | 162.10 | 62.83 | 99.28 | 0.00 | 0.00 |
Annual Sum or Average | 320.48 | 220.33 | 311.23 | 130.36 | 180.86 | 0.00 | 0.00 |
Minimum of Months | 73.95 | 39.69 | 162.10 | 62.83 | 99.28 | 0.00 | 0.00 |
Maximum of Months | 562.58 | 435.03 | 439.45 | 178.46 | 260.99 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 15.28 | 472.30 | 100.82 | 17.73 | 83.08 | 0.00 | 0.00 |
February | 45.25 | 446.24 | 161.15 | 31.64 | 129.51 | 0.00 | 0.00 |
March | 160.03 | 299.64 | 238.54 | 82.14 | 156.41 | 0.00 | 0.00 |
April | 249.76 | 211.00 | 293.54 | 95.86 | 197.68 | 0.00 | 0.00 |
May | 359.04 | 127.44 | 345.31 | 127.49 | 217.83 | 0.00 | 0.00 |
June | 500.88 | 76.82 | 416.20 | 163.24 | 252.96 | 0.00 | 0.00 |
July | 502.19 | 44.28 | 375.19 | 135.29 | 239.90 | 0.00 | 0.00 |
August | 437.15 | 62.84 | 336.10 | 114.99 | 221.11 | 0.00 | 0.00 |
September | 295.99 | 114.07 | 262.26 | 90.96 | 171.30 | 0.00 | 0.00 |
October | 142.44 | 201.49 | 175.71 | 48.62 | 127.09 | 0.00 | 0.00 |
November | 52.70 | 278.62 | 106.71 | 23.20 | 83.51 | 0.00 | 0.00 |
December | 14.66 | 452.72 | 93.93 | 15.08 | 78.85 | 0.00 | 0.00 |
Annual Sum or Average | 232.33 | 231.21 | 242.49 | 79.08 | 163.40 | 0.00 | 0.00 |
Minimum of Months | 14.66 | 44.28 | 93.93 | 15.08 | 78.85 | 0.00 | 0.00 |
Maximum of Months | 502.19 | 472.30 | 416.20 | 163.24 | 252.96 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 123.11 | 222.74 | 161.58 | 94.36 | 67.21 | 0.00 | 0.00 |
February | 135.90 | 218.70 | 182.98 | 87.51 | 95.47 | 0.00 | 0.00 |
March | 212.95 | 153.18 | 224.84 | 126.32 | 98.52 | 0.00 | 0.00 |
April | 187.58 | 114.62 | 185.96 | 74.14 | 111.82 | 0.00 | 0.00 |
May | 186.19 | 67.04 | 163.98 | 48.34 | 115.64 | 0.00 | 0.00 |
June | 204.95 | 35.69 | 157.84 | 33.05 | 124.79 | 0.00 | 0.00 |
July | 234.57 | 19.14 | 160.44 | 38.01 | 122.43 | 0.00 | 0.00 |
August | 252.83 | 28.44 | 179.65 | 57.01 | 122.64 | 0.00 | 0.00 |
September | 267.02 | 56.11 | 210.29 | 102.05 | 108.23 | 0.00 | 0.00 |
October | 217.18 | 103.64 | 202.22 | 115.61 | 86.60 | 0.00 | 0.00 |
November | 134.28 | 142.40 | 145.05 | 82.07 | 62.98 | 0.00 | 0.00 |
December | 96.95 | 217.38 | 135.11 | 70.03 | 65.08 | 0.00 | 0.00 |
Annual Sum or Average | 188.10 | 114.38 | 175.78 | 77.34 | 98.44 | 0.00 | 0.00 |
Minimum of Months | 96.95 | 19.14 | 135.11 | 33.05 | 62.98 | 0.00 | 0.00 |
Maximum of Months | 267.02 | 222.74 | 224.84 | 126.32 | 124.79 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 1421.40 | 179.10 | 0.00 | 179.10 | 0.00 | 0.00 |
February | 2.21 | 1348.58 | 272.88 | 0.00 | 272.88 | 0.00 | 0.00 |
March | 78.20 | 940.29 | 330.96 | 0.00 | 330.96 | 0.00 | 0.00 |
April | 185.70 | 645.74 | 422.60 | 2.38 | 420.21 | 0.00 | 0.00 |
May | 362.62 | 371.44 | 489.58 | 20.34 | 469.24 | 0.00 | 0.00 |
June | 634.74 | 214.24 | 590.57 | 51.17 | 539.40 | 0.00 | 0.00 |
July | 703.48 | 134.72 | 550.04 | 38.19 | 511.84 | 0.00 | 0.00 |
August | 569.90 | 190.56 | 475.75 | 9.36 | 466.39 | 0.00 | 0.00 |
September | 318.74 | 347.95 | 360.26 | 0.20 | 360.06 | 0.00 | 0.00 |
October | 104.52 | 635.90 | 269.10 | 0.00 | 269.10 | 0.00 | 0.00 |
November | 21.24 | 883.48 | 180.83 | 0.00 | 180.83 | 0.00 | 0.00 |
December | 0.50 | 1366.62 | 167.63 | 0.00 | 167.63 | 0.00 | 0.00 |
Annual Sum or Average | 250.06 | 705.18 | 357.79 | 10.18 | 347.61 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 134.72 | 167.63 | 0.00 | 167.63 | 0.00 | 0.00 |
Maximum of Months | 703.48 | 1421.40 | 590.57 | 51.17 | 539.40 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 1458.41 | 179.10 | 0.00 | 179.10 | 0.00 | 0.00 |
February | 1.57 | 1385.16 | 272.88 | 0.00 | 272.88 | 0.00 | 0.00 |
March | 72.54 | 966.73 | 330.96 | 0.00 | 330.96 | 0.00 | 0.00 |
April | 175.05 | 663.26 | 422.60 | 2.38 | 420.21 | 0.00 | 0.00 |
May | 350.54 | 381.32 | 489.58 | 20.34 | 469.24 | 0.00 | 0.00 |
June | 624.18 | 220.30 | 590.57 | 51.17 | 539.40 | 0.00 | 0.00 |
July | 694.70 | 139.48 | 550.04 | 38.19 | 511.84 | 0.00 | 0.00 |
August | 561.45 | 196.83 | 475.75 | 9.36 | 466.39 | 0.00 | 0.00 |
September | 309.90 | 358.28 | 360.26 | 0.20 | 360.06 | 0.00 | 0.00 |
October | 96.52 | 655.46 | 269.10 | 0.00 | 269.10 | 0.00 | 0.00 |
November | 18.70 | 912.91 | 180.83 | 0.00 | 180.83 | 0.00 | 0.00 |
December | 0.37 | 1403.08 | 167.63 | 0.00 | 167.63 | 0.00 | 0.00 |
Annual Sum or Average | 243.67 | 725.12 | 357.79 | 10.18 | 347.61 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 139.48 | 167.63 | 0.00 | 167.63 | 0.00 | 0.00 |
Maximum of Months | 694.70 | 1458.41 | 590.57 | 51.17 | 539.40 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 117.25 | 926.14 | 310.46 | 120.61 | 189.85 | 0.00 | 0.00 |
February | 186.72 | 894.14 | 421.68 | 137.80 | 283.88 | 0.00 | 0.00 |
March | 453.26 | 609.48 | 570.69 | 241.77 | 328.92 | 0.00 | 0.00 |
April | 669.20 | 450.22 | 674.35 | 266.09 | 408.26 | 0.00 | 0.00 |
May | 877.82 | 279.06 | 727.59 | 277.36 | 450.23 | 0.00 | 0.00 |
June | 1114.08 | 169.26 | 801.08 | 298.78 | 502.31 | 0.00 | 0.00 |
July | 1193.90 | 107.66 | 772.93 | 288.59 | 484.34 | 0.00 | 0.00 |
August | 1084.05 | 142.62 | 718.80 | 261.51 | 457.28 | 0.00 | 0.00 |
September | 852.14 | 238.18 | 634.97 | 264.85 | 370.12 | 0.00 | 0.00 |
October | 482.09 | 422.49 | 474.82 | 202.14 | 272.68 | 0.00 | 0.00 |
November | 208.03 | 584.56 | 293.95 | 110.14 | 183.81 | 0.00 | 0.00 |
December | 74.62 | 916.59 | 252.39 | 75.99 | 176.40 | 0.00 | 0.00 |
Annual Sum or Average | 611.79 | 476.24 | 555.06 | 212.50 | 342.56 | 0.00 | 0.00 |
Minimum of Months | 74.62 | 107.66 | 252.39 | 75.99 | 176.40 | 0.00 | 0.00 |
Maximum of Months | 1193.90 | 926.14 | 801.08 | 298.78 | 502.31 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 269.24 | 996.23 | 472.70 | 240.21 | 232.49 | 0.00 | 0.00 |
February | 313.01 | 969.89 | 559.33 | 222.77 | 336.56 | 0.00 | 0.00 |
March | 558.53 | 667.61 | 685.80 | 321.56 | 364.25 | 0.00 | 0.00 |
April | 555.00 | 497.07 | 618.24 | 189.55 | 428.69 | 0.00 | 0.00 |
May | 605.64 | 299.76 | 585.26 | 130.03 | 455.23 | 0.00 | 0.00 |
June | 726.65 | 178.70 | 604.25 | 101.67 | 502.57 | 0.00 | 0.00 |
July | 812.54 | 116.22 | 596.96 | 109.84 | 487.11 | 0.00 | 0.00 |
August | 824.17 | 162.36 | 620.40 | 148.32 | 472.08 | 0.00 | 0.00 |
September | 792.51 | 273.69 | 658.79 | 259.85 | 398.94 | 0.00 | 0.00 |
October | 595.77 | 458.71 | 607.01 | 294.30 | 312.70 | 0.00 | 0.00 |
November | 342.27 | 628.88 | 431.22 | 208.91 | 222.31 | 0.00 | 0.00 |
December | 212.01 | 976.56 | 401.39 | 178.27 | 223.12 | 0.00 | 0.00 |
Annual Sum or Average | 551.98 | 516.46 | 570.11 | 200.37 | 369.74 | 0.00 | 0.00 |
Minimum of Months | 212.01 | 116.22 | 401.39 | 101.67 | 222.31 | 0.00 | 0.00 |
Maximum of Months | 824.17 | 996.23 | 685.80 | 321.56 | 502.57 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.118634E+10 | 0.193463E+10 | 0.149244E+10 | 0.871616E+09 | 0.620826E+09 | 0.00 | 0.00 |
February | 0.119597E+10 | 0.170109E+10 | 0.152659E+10 | 0.730113E+09 | 0.796480E+09 | 0.00 | 0.00 |
March | 0.203730E+10 | 0.134121E+10 | 0.207681E+10 | 0.116679E+10 | 0.910020E+09 | 0.00 | 0.00 |
April | 0.172830E+10 | 0.979047E+09 | 0.166226E+10 | 0.662735E+09 | 0.999522E+09 | 0.00 | 0.00 |
May | 0.175426E+10 | 0.619627E+09 | 0.151468E+10 | 0.446521E+09 | 0.106816E+10 | 0.00 | 0.00 |
June | 0.182040E+10 | 0.367158E+09 | 0.141093E+10 | 0.295438E+09 | 0.111549E+10 | 0.00 | 0.00 |
July | 0.210558E+10 | 0.243738E+09 | 0.148192E+10 | 0.351066E+09 | 0.113085E+10 | 0.00 | 0.00 |
August | 0.229289E+10 | 0.334416E+09 | 0.165938E+10 | 0.526561E+09 | 0.113282E+10 | 0.00 | 0.00 |
September | 0.238633E+10 | 0.539992E+09 | 0.187970E+10 | 0.912236E+09 | 0.967463E+09 | 0.00 | 0.00 |
October | 0.204787E+10 | 0.933166E+09 | 0.186785E+10 | 0.106791E+10 | 0.799941E+09 | 0.00 | 0.00 |
November | 0.123630E+10 | 0.121026E+10 | 0.129658E+10 | 0.733608E+09 | 0.562970E+09 | 0.00 | 0.00 |
December | 0.939424E+09 | 0.188699E+10 | 0.124798E+10 | 0.646864E+09 | 0.601115E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.207310E+11 | 0.120913E+11 | 0.191171E+11 | 0.841146E+10 | 0.107057E+11 | 0.00 | 0.00 |
Minimum of Months | 0.939424E+09 | 0.243738E+09 | 0.124798E+10 | 0.295438E+09 | 0.562970E+09 | 0.00 | 0.00 |
Maximum of Months | 0.238633E+10 | 0.193463E+10 | 0.207681E+10 | 0.116679E+10 | 0.113282E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.329371E+10 | 0.555584E+10 | 0.420262E+10 | 0.245441E+10 | 0.174821E+10 | 0.00 | 0.00 |
February | 0.331776E+10 | 0.488135E+10 | 0.429879E+10 | 0.205595E+10 | 0.224284E+10 | 0.00 | 0.00 |
March | 0.565331E+10 | 0.395869E+10 | 0.584817E+10 | 0.328562E+10 | 0.256256E+10 | 0.00 | 0.00 |
April | 0.478139E+10 | 0.295391E+10 | 0.468081E+10 | 0.186622E+10 | 0.281459E+10 | 0.00 | 0.00 |
May | 0.482872E+10 | 0.194893E+10 | 0.426524E+10 | 0.125737E+10 | 0.300787E+10 | 0.00 | 0.00 |
June | 0.503076E+10 | 0.116798E+10 | 0.397308E+10 | 0.831935E+09 | 0.314115E+10 | 0.00 | 0.00 |
July | 0.585361E+10 | 0.778328E+09 | 0.417299E+10 | 0.988579E+09 | 0.318441E+10 | 0.00 | 0.00 |
August | 0.638440E+10 | 0.105933E+10 | 0.467271E+10 | 0.148276E+10 | 0.318995E+10 | 0.00 | 0.00 |
September | 0.663165E+10 | 0.170878E+10 | 0.529311E+10 | 0.256880E+10 | 0.272431E+10 | 0.00 | 0.00 |
October | 0.568049E+10 | 0.284769E+10 | 0.525974E+10 | 0.300716E+10 | 0.225258E+10 | 0.00 | 0.00 |
November | 0.341842E+10 | 0.360916E+10 | 0.365108E+10 | 0.206579E+10 | 0.158529E+10 | 0.00 | 0.00 |
December | 0.260576E+10 | 0.543427E+10 | 0.351423E+10 | 0.182153E+10 | 0.169270E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.574800E+11 | 0.359043E+11 | 0.538326E+11 | 0.236861E+11 | 0.301464E+11 | 0.00 | 0.00 |
Minimum of Months | 0.260576E+10 | 0.778328E+09 | 0.351423E+10 | 0.831935E+09 | 0.158529E+10 | 0.00 | 0.00 |
Maximum of Months | 0.663165E+10 | 0.555584E+10 | 0.584817E+10 | 0.328562E+10 | 0.318995E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.432458E+10 | 0.759553E+10 | 0.545944E+10 | 0.318842E+10 | 0.227102E+10 | 0.00 | 0.00 |
February | 0.435857E+10 | 0.666240E+10 | 0.558437E+10 | 0.267080E+10 | 0.291357E+10 | 0.00 | 0.00 |
March | 0.747262E+10 | 0.537536E+10 | 0.759711E+10 | 0.426820E+10 | 0.332891E+10 | 0.00 | 0.00 |
April | 0.631227E+10 | 0.403281E+10 | 0.608063E+10 | 0.242432E+10 | 0.365631E+10 | 0.00 | 0.00 |
May | 0.638010E+10 | 0.266840E+10 | 0.554079E+10 | 0.163340E+10 | 0.390739E+10 | 0.00 | 0.00 |
June | 0.666168E+10 | 0.158165E+10 | 0.516126E+10 | 0.108073E+10 | 0.408053E+10 | 0.00 | 0.00 |
July | 0.777447E+10 | 0.103714E+10 | 0.542095E+10 | 0.128422E+10 | 0.413673E+10 | 0.00 | 0.00 |
August | 0.846776E+10 | 0.140933E+10 | 0.607012E+10 | 0.192619E+10 | 0.414393E+10 | 0.00 | 0.00 |
September | 0.877389E+10 | 0.230438E+10 | 0.687605E+10 | 0.333701E+10 | 0.353904E+10 | 0.00 | 0.00 |
October | 0.747886E+10 | 0.389957E+10 | 0.683270E+10 | 0.390647E+10 | 0.292623E+10 | 0.00 | 0.00 |
November | 0.449256E+10 | 0.497745E+10 | 0.474296E+10 | 0.268358E+10 | 0.205938E+10 | 0.00 | 0.00 |
December | 0.341921E+10 | 0.745604E+10 | 0.456518E+10 | 0.236627E+10 | 0.219891E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.759166E+11 | 0.490001E+11 | 0.699316E+11 | 0.307696E+11 | 0.391619E+11 | 0.00 | 0.00 |
Minimum of Months | 0.341921E+10 | 0.103714E+10 | 0.456518E+10 | 0.108073E+10 | 0.205938E+10 | 0.00 | 0.00 |
Maximum of Months | 0.877389E+10 | 0.759553E+10 | 0.759711E+10 | 0.426820E+10 | 0.414393E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.234828E+09 | 0.116513E+10 | 0.496582E+09 | 0.219829E+09 | 0.276753E+09 | 0.00 | 0.00 |
February | 0.320459E+09 | 0.102111E+10 | 0.597378E+09 | 0.220903E+09 | 0.376475E+09 | 0.00 | 0.00 |
March | 0.771045E+09 | 0.773482E+09 | 0.922898E+09 | 0.450693E+09 | 0.472205E+09 | 0.00 | 0.00 |
April | 0.897614E+09 | 0.551877E+09 | 0.933028E+09 | 0.378627E+09 | 0.554401E+09 | 0.00 | 0.00 |
May | 0.116626E+10 | 0.344133E+09 | 0.103703E+10 | 0.421961E+09 | 0.615067E+09 | 0.00 | 0.00 |
June | 0.145049E+10 | 0.186878E+09 | 0.113907E+10 | 0.462572E+09 | 0.676493E+09 | 0.00 | 0.00 |
July | 0.151786E+10 | 0.109026E+09 | 0.108744E+10 | 0.417167E+09 | 0.670276E+09 | 0.00 | 0.00 |
August | 0.142385E+10 | 0.156266E+09 | 0.104626E+10 | 0.408530E+09 | 0.637726E+09 | 0.00 | 0.00 |
September | 0.112447E+10 | 0.284002E+09 | 0.918033E+09 | 0.416060E+09 | 0.501973E+09 | 0.00 | 0.00 |
October | 0.720501E+09 | 0.532814E+09 | 0.736956E+09 | 0.341373E+09 | 0.395583E+09 | 0.00 | 0.00 |
November | 0.351792E+09 | 0.709347E+09 | 0.465984E+09 | 0.205175E+09 | 0.260809E+09 | 0.00 | 0.00 |
December | 0.198870E+09 | 0.114025E+10 | 0.434182E+09 | 0.168279E+09 | 0.265903E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.101780E+11 | 0.697431E+10 | 0.981483E+10 | 0.411117E+10 | 0.570366E+10 | 0.00 | 0.00 |
Minimum of Months | 0.198870E+09 | 0.109026E+09 | 0.434182E+09 | 0.168279E+09 | 0.260809E+09 | 0.00 | 0.00 |
Maximum of Months | 0.151786E+10 | 0.116513E+10 | 0.113907E+10 | 0.462572E+09 | 0.676493E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 40866925.03 | 0.126401E+10 | 0.270031E+09 | 47495878.30 | 0.222535E+09 | 0.00 | 0.00 |
February | 0.110144E+09 | 0.107780E+10 | 0.389854E+09 | 76547281.39 | 0.313306E+09 | 0.00 | 0.00 |
March | 0.430087E+09 | 0.804435E+09 | 0.638916E+09 | 0.219999E+09 | 0.418917E+09 | 0.00 | 0.00 |
April | 0.653060E+09 | 0.549007E+09 | 0.760857E+09 | 0.248475E+09 | 0.512382E+09 | 0.00 | 0.00 |
May | 0.973435E+09 | 0.341180E+09 | 0.924883E+09 | 0.341459E+09 | 0.583424E+09 | 0.00 | 0.00 |
June | 0.131368E+10 | 0.195868E+09 | 0.107878E+10 | 0.423106E+09 | 0.655679E+09 | 0.00 | 0.00 |
July | 0.135661E+10 | 0.117792E+09 | 0.100491E+10 | 0.362370E+09 | 0.642537E+09 | 0.00 | 0.00 |
August | 0.118004E+10 | 0.168018E+09 | 0.900208E+09 | 0.308000E+09 | 0.592208E+09 | 0.00 | 0.00 |
September | 0.774152E+09 | 0.296855E+09 | 0.679788E+09 | 0.235770E+09 | 0.444017E+09 | 0.00 | 0.00 |
October | 0.381820E+09 | 0.544916E+09 | 0.470617E+09 | 0.130229E+09 | 0.340388E+09 | 0.00 | 0.00 |
November | 0.134755E+09 | 0.729249E+09 | 0.276588E+09 | 60128040.21 | 0.216460E+09 | 0.00 | 0.00 |
December | 39137729.24 | 0.121269E+10 | 0.251577E+09 | 40382403.54 | 0.211194E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.738778E+10 | 0.730181E+10 | 0.764701E+10 | 0.249396E+10 | 0.515305E+10 | 0.00 | 0.00 |
Minimum of Months | 39137729.24 | 0.117792E+09 | 0.251577E+09 | 40382403.54 | 0.211194E+09 | 0.00 | 0.00 |
Maximum of Months | 0.135661E+10 | 0.126401E+10 | 0.107878E+10 | 0.423106E+09 | 0.655679E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.193934E+09 | 0.282824E+09 | 0.236019E+09 | 0.137839E+09 | 98179314.65 | 0.00 | 0.00 |
February | 0.196129E+09 | 0.247864E+09 | 0.241420E+09 | 0.115462E+09 | 0.125958E+09 | 0.00 | 0.00 |
March | 0.296007E+09 | 0.270020E+09 | 0.328433E+09 | 0.184520E+09 | 0.143914E+09 | 0.00 | 0.00 |
April | 0.242349E+09 | 0.218771E+09 | 0.262875E+09 | 0.104806E+09 | 0.158068E+09 | 0.00 | 0.00 |
May | 0.241553E+09 | 0.154275E+09 | 0.239537E+09 | 70613797.98 | 0.168923E+09 | 0.00 | 0.00 |
June | 0.252992E+09 | 95129248.90 | 0.223129E+09 | 46721309.88 | 0.176408E+09 | 0.00 | 0.00 |
July | 0.300927E+09 | 67905484.87 | 0.234356E+09 | 55518414.20 | 0.178838E+09 | 0.00 | 0.00 |
August | 0.333703E+09 | 87909283.34 | 0.262420E+09 | 83271556.86 | 0.179149E+09 | 0.00 | 0.00 |
September | 0.350217E+09 | 0.133573E+09 | 0.297261E+09 | 0.144263E+09 | 0.152998E+09 | 0.00 | 0.00 |
October | 0.293913E+09 | 0.214742E+09 | 0.295387E+09 | 0.168881E+09 | 0.126505E+09 | 0.00 | 0.00 |
November | 0.177296E+09 | 0.256901E+09 | 0.205044E+09 | 0.116014E+09 | 89029868.95 | 0.00 | 0.00 |
December | 0.152741E+09 | 0.283589E+09 | 0.197359E+09 | 0.102297E+09 | 95062038.89 | 0.00 | 0.00 |
Annual Sum or Average | 0.303176E+10 | 0.231350E+10 | 0.302324E+10 | 0.133021E+10 | 0.169303E+10 | 0.00 | 0.00 |
Minimum of Months | 0.152741E+09 | 67905484.87 | 0.197359E+09 | 46721309.88 | 89029868.95 | 0.00 | 0.00 |
Maximum of Months | 0.350217E+09 | 0.283589E+09 | 0.328433E+09 | 0.184520E+09 | 0.179149E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 171.99 | 0.386063E+09 | 54831599.44 | 0.00 | 54831599.44 | 0.00 | 0.00 |
February | 1942818.36 | 0.330026E+09 | 75458009.98 | 0.00 | 75458009.98 | 0.00 | 0.00 |
March | 31325914.95 | 0.248320E+09 | 0.101326E+09 | 1459.70 | 0.101325E+09 | 0.00 | 0.00 |
April | 68424377.32 | 0.160367E+09 | 0.125206E+09 | 705821.57 | 0.124501E+09 | 0.00 | 0.00 |
May | 0.130003E+09 | 91532824.08 | 0.149888E+09 | 6227089.73 | 0.143661E+09 | 0.00 | 0.00 |
June | 0.207463E+09 | 49171840.19 | 0.174972E+09 | 15159636.67 | 0.159813E+09 | 0.00 | 0.00 |
July | 0.235755E+09 | 28744166.31 | 0.168396E+09 | 11693265.88 | 0.156703E+09 | 0.00 | 0.00 |
August | 0.192340E+09 | 42441858.57 | 0.145653E+09 | 2864391.37 | 0.142789E+09 | 0.00 | 0.00 |
September | 0.108413E+09 | 80991561.17 | 0.106739E+09 | 60414.17 | 0.106678E+09 | 0.00 | 0.00 |
October | 42400306.37 | 0.160819E+09 | 82385417.85 | 0.00 | 82385417.85 | 0.00 | 0.00 |
November | 10077377.33 | 0.220226E+09 | 53575070.74 | 0.00 | 53575070.74 | 0.00 | 0.00 |
December | 359182.00 | 0.369479E+09 | 51320709.15 | 0.00 | 51320709.15 | 0.00 | 0.00 |
Annual Sum or Average | 0.102851E+10 | 0.216818E+10 | 0.128975E+10 | 36712079.10 | 0.125304E+10 | 0.00 | 0.00 |
Minimum of Months | 171.99 | 28744166.31 | 51320709.15 | 0.00 | 51320709.15 | 0.00 | 0.00 |
Maximum of Months | 0.235755E+09 | 0.386063E+09 | 0.174972E+09 | 15159636.67 | 0.159813E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.279927E+09 | 0.115683E+10 | 0.529059E+09 | 0.247689E+09 | 0.281370E+09 | 0.00 | 0.00 |
February | 0.343076E+09 | 0.100974E+10 | 0.613844E+09 | 0.238869E+09 | 0.374976E+09 | 0.00 | 0.00 |
March | 0.748152E+09 | 0.766015E+09 | 0.906294E+09 | 0.439141E+09 | 0.467153E+09 | 0.00 | 0.00 |
April | 0.916754E+09 | 0.536449E+09 | 0.960085E+09 | 0.409945E+09 | 0.550140E+09 | 0.00 | 0.00 |
May | 0.114774E+10 | 0.328998E+09 | 0.103051E+10 | 0.411715E+09 | 0.618794E+09 | 0.00 | 0.00 |
June | 0.134844E+10 | 0.173631E+09 | 0.106840E+10 | 0.406971E+09 | 0.661427E+09 | 0.00 | 0.00 |
July | 0.149648E+10 | 99251197.67 | 0.107643E+10 | 0.413896E+09 | 0.662531E+09 | 0.00 | 0.00 |
August | 0.140153E+10 | 0.147004E+09 | 0.103569E+10 | 0.400506E+09 | 0.635183E+09 | 0.00 | 0.00 |
September | 0.114990E+10 | 0.273583E+09 | 0.942085E+09 | 0.433411E+09 | 0.508674E+09 | 0.00 | 0.00 |
October | 0.756041E+09 | 0.526290E+09 | 0.769075E+09 | 0.376289E+09 | 0.392786E+09 | 0.00 | 0.00 |
November | 0.364222E+09 | 0.704501E+09 | 0.475675E+09 | 0.215274E+09 | 0.260401E+09 | 0.00 | 0.00 |
December | 0.192353E+09 | 0.113201E+10 | 0.429316E+09 | 0.165717E+09 | 0.263599E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.101446E+11 | 0.685429E+10 | 0.983646E+10 | 0.415942E+10 | 0.567703E+10 | 0.00 | 0.00 |
Minimum of Months | 0.192353E+09 | 99251197.67 | 0.429316E+09 | 0.165717E+09 | 0.260401E+09 | 0.00 | 0.00 |
Maximum of Months | 0.149648E+10 | 0.115683E+10 | 0.107643E+10 | 0.439141E+09 | 0.662531E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 58523267.48 | 0.122702E+10 | 0.302508E+09 | 75355657.08 | 0.227152E+09 | 0.00 | 0.00 |
February | 0.116469E+09 | 0.104923E+10 | 0.406320E+09 | 94512709.61 | 0.311807E+09 | 0.00 | 0.00 |
March | 0.398574E+09 | 0.788017E+09 | 0.622312E+09 | 0.208448E+09 | 0.413864E+09 | 0.00 | 0.00 |
April | 0.668433E+09 | 0.531056E+09 | 0.787914E+09 | 0.279793E+09 | 0.508121E+09 | 0.00 | 0.00 |
May | 0.962200E+09 | 0.326600E+09 | 0.918365E+09 | 0.331213E+09 | 0.587152E+09 | 0.00 | 0.00 |
June | 0.122624E+10 | 0.183254E+09 | 0.100812E+10 | 0.367505E+09 | 0.640612E+09 | 0.00 | 0.00 |
July | 0.133787E+10 | 0.111615E+09 | 0.993891E+09 | 0.359099E+09 | 0.634792E+09 | 0.00 | 0.00 |
August | 0.115947E+10 | 0.159405E+09 | 0.889641E+09 | 0.299976E+09 | 0.589665E+09 | 0.00 | 0.00 |
September | 0.801583E+09 | 0.281608E+09 | 0.703840E+09 | 0.253121E+09 | 0.450719E+09 | 0.00 | 0.00 |
October | 0.407918E+09 | 0.528568E+09 | 0.502736E+09 | 0.165145E+09 | 0.337591E+09 | 0.00 | 0.00 |
November | 0.139751E+09 | 0.716916E+09 | 0.286279E+09 | 70227577.39 | 0.216051E+09 | 0.00 | 0.00 |
December | 29453671.75 | 0.120154E+10 | 0.246711E+09 | 37820722.34 | 0.208890E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.730648E+10 | 0.710483E+10 | 0.766863E+10 | 0.254222E+10 | 0.512642E+10 | 0.00 | 0.00 |
Minimum of Months | 29453671.75 | 0.111615E+09 | 0.246711E+09 | 37820722.34 | 0.208890E+09 | 0.00 | 0.00 |
Maximum of Months | 0.133787E+10 | 0.122702E+10 | 0.100812E+10 | 0.367505E+09 | 0.640612E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.316996E+09 | 0.149800E+10 | 0.630170E+09 | 0.298660E+09 | 0.331511E+09 | 0.00 | 0.00 |
February | 0.346858E+09 | 0.131586E+10 | 0.686557E+09 | 0.250173E+09 | 0.436383E+09 | 0.00 | 0.00 |
March | 0.724421E+09 | 0.997475E+09 | 0.931130E+09 | 0.399806E+09 | 0.531325E+09 | 0.00 | 0.00 |
April | 0.741330E+09 | 0.710835E+09 | 0.840815E+09 | 0.228616E+09 | 0.612200E+09 | 0.00 | 0.00 |
May | 0.879124E+09 | 0.436368E+09 | 0.843718E+09 | 0.166490E+09 | 0.677228E+09 | 0.00 | 0.00 |
June | 0.106090E+10 | 0.248465E+09 | 0.862508E+09 | 0.134073E+09 | 0.728435E+09 | 0.00 | 0.00 |
July | 0.122111E+10 | 0.161476E+09 | 0.872587E+09 | 0.145624E+09 | 0.726962E+09 | 0.00 | 0.00 |
August | 0.119660E+10 | 0.230778E+09 | 0.884124E+09 | 0.186632E+09 | 0.697493E+09 | 0.00 | 0.00 |
September | 0.105534E+10 | 0.392140E+09 | 0.875314E+09 | 0.312709E+09 | 0.562605E+09 | 0.00 | 0.00 |
October | 0.788166E+09 | 0.680502E+09 | 0.818495E+09 | 0.365919E+09 | 0.452576E+09 | 0.00 | 0.00 |
November | 0.423308E+09 | 0.904050E+09 | 0.560335E+09 | 0.251371E+09 | 0.308965E+09 | 0.00 | 0.00 |
December | 0.251539E+09 | 0.146493E+10 | 0.538799E+09 | 0.221648E+09 | 0.317151E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.900568E+10 | 0.904089E+10 | 0.934455E+10 | 0.296172E+10 | 0.638283E+10 | 0.00 | 0.00 |
Minimum of Months | 0.251539E+09 | 0.161476E+09 | 0.538799E+09 | 0.134073E+09 | 0.308965E+09 | 0.00 | 0.00 |
Maximum of Months | 0.122111E+10 | 0.149800E+10 | 0.931130E+09 | 0.399806E+09 | 0.728435E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.234698E+09 | 0.116519E+10 | 0.496582E+09 | 0.219829E+09 | 0.276753E+09 | 0.00 | 0.00 |
February | 0.318210E+09 | 0.102257E+10 | 0.597378E+09 | 0.220903E+09 | 0.376475E+09 | 0.00 | 0.00 |
March | 0.766531E+09 | 0.771622E+09 | 0.922898E+09 | 0.450693E+09 | 0.472205E+09 | 0.00 | 0.00 |
April | 0.889463E+09 | 0.550322E+09 | 0.933028E+09 | 0.378627E+09 | 0.554401E+09 | 0.00 | 0.00 |
May | 0.115500E+10 | 0.341911E+09 | 0.103703E+10 | 0.421961E+09 | 0.615067E+09 | 0.00 | 0.00 |
June | 0.143778E+10 | 0.184503E+09 | 0.113907E+10 | 0.462572E+09 | 0.676493E+09 | 0.00 | 0.00 |
July | 0.150681E+10 | 0.106302E+09 | 0.108744E+10 | 0.417167E+09 | 0.670276E+09 | 0.00 | 0.00 |
August | 0.141432E+10 | 0.153010E+09 | 0.104626E+10 | 0.408530E+09 | 0.637726E+09 | 0.00 | 0.00 |
September | 0.111705E+10 | 0.279843E+09 | 0.918033E+09 | 0.416060E+09 | 0.501973E+09 | 0.00 | 0.00 |
October | 0.717042E+09 | 0.528717E+09 | 0.736956E+09 | 0.341373E+09 | 0.395583E+09 | 0.00 | 0.00 |
November | 0.351729E+09 | 0.704000E+09 | 0.465984E+09 | 0.205175E+09 | 0.260809E+09 | 0.00 | 0.00 |
December | 0.198059E+09 | 0.114034E+10 | 0.434182E+09 | 0.168279E+09 | 0.265903E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.101067E+11 | 0.694833E+10 | 0.981483E+10 | 0.411117E+10 | 0.570366E+10 | 0.00 | 0.00 |
Minimum of Months | 0.198059E+09 | 0.106302E+09 | 0.434182E+09 | 0.168279E+09 | 0.260809E+09 | 0.00 | 0.00 |
Maximum of Months | 0.150681E+10 | 0.116519E+10 | 0.113907E+10 | 0.462572E+09 | 0.676493E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 40917829.08 | 0.126500E+10 | 0.270031E+09 | 47495878.30 | 0.222535E+09 | 0.00 | 0.00 |
February | 0.109460E+09 | 0.107954E+10 | 0.389854E+09 | 76547281.39 | 0.313306E+09 | 0.00 | 0.00 |
March | 0.428633E+09 | 0.802556E+09 | 0.638916E+09 | 0.219999E+09 | 0.418917E+09 | 0.00 | 0.00 |
April | 0.647366E+09 | 0.546902E+09 | 0.760857E+09 | 0.248475E+09 | 0.512382E+09 | 0.00 | 0.00 |
May | 0.961648E+09 | 0.341345E+09 | 0.924883E+09 | 0.341459E+09 | 0.583424E+09 | 0.00 | 0.00 |
June | 0.129828E+10 | 0.199111E+09 | 0.107878E+10 | 0.423106E+09 | 0.655679E+09 | 0.00 | 0.00 |
July | 0.134506E+10 | 0.118591E+09 | 0.100491E+10 | 0.362370E+09 | 0.642537E+09 | 0.00 | 0.00 |
August | 0.117087E+10 | 0.168313E+09 | 0.900208E+09 | 0.308000E+09 | 0.592208E+09 | 0.00 | 0.00 |
September | 0.767212E+09 | 0.295674E+09 | 0.679788E+09 | 0.235770E+09 | 0.444017E+09 | 0.00 | 0.00 |
October | 0.381511E+09 | 0.539680E+09 | 0.470617E+09 | 0.130229E+09 | 0.340388E+09 | 0.00 | 0.00 |
November | 0.136602E+09 | 0.722190E+09 | 0.276588E+09 | 60128040.21 | 0.216460E+09 | 0.00 | 0.00 |
December | 39270377.96 | 0.121257E+10 | 0.251577E+09 | 40382403.54 | 0.211194E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.732683E+10 | 0.729147E+10 | 0.764701E+10 | 0.249396E+10 | 0.515305E+10 | 0.00 | 0.00 |
Minimum of Months | 39270377.96 | 0.118591E+09 | 0.251577E+09 | 40382403.54 | 0.211194E+09 | 0.00 | 0.00 |
Maximum of Months | 0.134506E+10 | 0.126500E+10 | 0.107878E+10 | 0.423106E+09 | 0.655679E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.329725E+09 | 0.596577E+09 | 0.432766E+09 | 0.252744E+09 | 0.180023E+09 | 0.00 | 0.00 |
February | 0.328775E+09 | 0.529071E+09 | 0.442669E+09 | 0.211712E+09 | 0.230958E+09 | 0.00 | 0.00 |
March | 0.570373E+09 | 0.410265E+09 | 0.602218E+09 | 0.338337E+09 | 0.263882E+09 | 0.00 | 0.00 |
April | 0.486212E+09 | 0.297102E+09 | 0.482009E+09 | 0.192174E+09 | 0.289835E+09 | 0.00 | 0.00 |
May | 0.498693E+09 | 0.179563E+09 | 0.439217E+09 | 0.129478E+09 | 0.309739E+09 | 0.00 | 0.00 |
June | 0.531231E+09 | 92517456.72 | 0.409132E+09 | 85668639.80 | 0.323464E+09 | 0.00 | 0.00 |
July | 0.628260E+09 | 51264885.61 | 0.429718E+09 | 0.101799E+09 | 0.327918E+09 | 0.00 | 0.00 |
August | 0.677188E+09 | 76180253.77 | 0.481176E+09 | 0.152688E+09 | 0.328488E+09 | 0.00 | 0.00 |
September | 0.692124E+09 | 0.145442E+09 | 0.545061E+09 | 0.264522E+09 | 0.280539E+09 | 0.00 | 0.00 |
October | 0.581708E+09 | 0.277603E+09 | 0.541624E+09 | 0.309663E+09 | 0.231961E+09 | 0.00 | 0.00 |
November | 0.348058E+09 | 0.369105E+09 | 0.375971E+09 | 0.212725E+09 | 0.163246E+09 | 0.00 | 0.00 |
December | 0.259682E+09 | 0.582244E+09 | 0.361879E+09 | 0.187572E+09 | 0.174307E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.593203E+10 | 0.360693E+10 | 0.554344E+10 | 0.243908E+10 | 0.310436E+10 | 0.00 | 0.00 |
Minimum of Months | 0.259682E+09 | 51264885.61 | 0.361879E+09 | 85668639.80 | 0.163246E+09 | 0.00 | 0.00 |
Maximum of Months | 0.692124E+09 | 0.596577E+09 | 0.602218E+09 | 0.338337E+09 | 0.328488E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.380709E+10 | 0.479695E+09 | 0.00 | 0.479695E+09 | 0.00 | 0.00 |
February | 5350301.78 | 0.326247E+10 | 0.660145E+09 | 0.00 | 0.660145E+09 | 0.00 | 0.00 |
March | 0.209452E+09 | 0.251849E+10 | 0.886455E+09 | 12770.23 | 0.886442E+09 | 0.00 | 0.00 |
April | 0.481327E+09 | 0.167377E+10 | 0.109537E+10 | 6174886.32 | 0.108919E+10 | 0.00 | 0.00 |
May | 0.971244E+09 | 0.994867E+09 | 0.131130E+10 | 54477750.25 | 0.125682E+10 | 0.00 | 0.00 |
June | 0.164526E+10 | 0.555302E+09 | 0.153075E+10 | 0.132624E+09 | 0.139812E+10 | 0.00 | 0.00 |
July | 0.188421E+10 | 0.360832E+09 | 0.147322E+10 | 0.102299E+09 | 0.137092E+10 | 0.00 | 0.00 |
August | 0.152642E+10 | 0.510386E+09 | 0.127425E+10 | 25059153.55 | 0.124919E+10 | 0.00 | 0.00 |
September | 0.826181E+09 | 0.901897E+09 | 0.933804E+09 | 528533.88 | 0.933276E+09 | 0.00 | 0.00 |
October | 0.279939E+09 | 0.170319E+10 | 0.720750E+09 | 0.00 | 0.720750E+09 | 0.00 | 0.00 |
November | 55051357.41 | 0.228999E+10 | 0.468702E+09 | 0.00 | 0.468702E+09 | 0.00 | 0.00 |
December | 1349660.78 | 0.366035E+10 | 0.448980E+09 | 0.00 | 0.448980E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.788578E+10 | 0.222386E+11 | 0.112834E+11 | 0.321176E+09 | 0.109622E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.360832E+09 | 0.448980E+09 | 0.00 | 0.448980E+09 | 0.00 | 0.00 |
Maximum of Months | 0.188421E+10 | 0.380709E+10 | 0.153075E+10 | 0.132624E+09 | 0.139812E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.390621E+10 | 0.479695E+09 | 0.00 | 0.479695E+09 | 0.00 | 0.00 |
February | 3801253.73 | 0.335097E+10 | 0.660145E+09 | 0.00 | 0.660145E+09 | 0.00 | 0.00 |
March | 0.194291E+09 | 0.258929E+10 | 0.886455E+09 | 12770.23 | 0.886442E+09 | 0.00 | 0.00 |
April | 0.453720E+09 | 0.171916E+10 | 0.109537E+10 | 6174886.32 | 0.108919E+10 | 0.00 | 0.00 |
May | 0.938897E+09 | 0.102134E+10 | 0.131130E+10 | 54477750.25 | 0.125682E+10 | 0.00 | 0.00 |
June | 0.161787E+10 | 0.571030E+09 | 0.153075E+10 | 0.132624E+09 | 0.139812E+10 | 0.00 | 0.00 |
July | 0.186069E+10 | 0.373595E+09 | 0.147322E+10 | 0.102299E+09 | 0.137092E+10 | 0.00 | 0.00 |
August | 0.150377E+10 | 0.527201E+09 | 0.127425E+10 | 25059153.55 | 0.124919E+10 | 0.00 | 0.00 |
September | 0.803254E+09 | 0.928660E+09 | 0.933804E+09 | 528533.88 | 0.933276E+09 | 0.00 | 0.00 |
October | 0.258528E+09 | 0.175559E+10 | 0.720750E+09 | 0.00 | 0.720750E+09 | 0.00 | 0.00 |
November | 48479014.80 | 0.236627E+10 | 0.468702E+09 | 0.00 | 0.468702E+09 | 0.00 | 0.00 |
December | 984874.65 | 0.375801E+10 | 0.448980E+09 | 0.00 | 0.448980E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.768429E+10 | 0.228673E+11 | 0.112834E+11 | 0.321176E+09 | 0.109622E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.373595E+09 | 0.448980E+09 | 0.00 | 0.448980E+09 | 0.00 | 0.00 |
Maximum of Months | 0.186069E+10 | 0.390621E+10 | 0.153075E+10 | 0.132624E+09 | 0.139812E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.314053E+09 | 0.248059E+10 | 0.831534E+09 | 0.323034E+09 | 0.508500E+09 | 0.00 | 0.00 |
February | 0.451703E+09 | 0.216310E+10 | 0.102012E+10 | 0.333368E+09 | 0.686752E+09 | 0.00 | 0.00 |
March | 0.121402E+10 | 0.163244E+10 | 0.152854E+10 | 0.647559E+09 | 0.880977E+09 | 0.00 | 0.00 |
April | 0.173456E+10 | 0.116697E+10 | 0.174791E+10 | 0.689699E+09 | 0.105821E+10 | 0.00 | 0.00 |
May | 0.235114E+10 | 0.747439E+09 | 0.194877E+10 | 0.742882E+09 | 0.120589E+10 | 0.00 | 0.00 |
June | 0.288770E+10 | 0.438725E+09 | 0.207640E+10 | 0.774426E+09 | 0.130198E+10 | 0.00 | 0.00 |
July | 0.319774E+10 | 0.288365E+09 | 0.207021E+10 | 0.772947E+09 | 0.129726E+10 | 0.00 | 0.00 |
August | 0.290353E+10 | 0.381989E+09 | 0.192523E+10 | 0.700440E+09 | 0.122479E+10 | 0.00 | 0.00 |
September | 0.220875E+10 | 0.617359E+09 | 0.164584E+10 | 0.686496E+09 | 0.959347E+09 | 0.00 | 0.00 |
October | 0.129122E+10 | 0.113159E+10 | 0.127175E+10 | 0.541411E+09 | 0.730344E+09 | 0.00 | 0.00 |
November | 0.539222E+09 | 0.151519E+10 | 0.761923E+09 | 0.285492E+09 | 0.476431E+09 | 0.00 | 0.00 |
December | 0.199859E+09 | 0.245500E+10 | 0.676000E+09 | 0.203532E+09 | 0.472468E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.192935E+11 | 0.150187E+11 | 0.175042E+11 | 0.670129E+10 | 0.108029E+11 | 0.00 | 0.00 |
Minimum of Months | 0.199859E+09 | 0.288365E+09 | 0.676000E+09 | 0.203532E+09 | 0.472468E+09 | 0.00 | 0.00 |
Maximum of Months | 0.319774E+10 | 0.248059E+10 | 0.207640E+10 | 0.774426E+09 | 0.130198E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.721132E+09 | 0.266831E+10 | 0.126607E+10 | 0.643372E+09 | 0.622697E+09 | 0.00 | 0.00 |
February | 0.757239E+09 | 0.234635E+10 | 0.135314E+10 | 0.538923E+09 | 0.814214E+09 | 0.00 | 0.00 |
March | 0.149597E+10 | 0.178812E+10 | 0.183686E+10 | 0.861259E+09 | 0.975599E+09 | 0.00 | 0.00 |
April | 0.143856E+10 | 0.128841E+10 | 0.160248E+10 | 0.491306E+09 | 0.111117E+10 | 0.00 | 0.00 |
May | 0.162215E+10 | 0.802884E+09 | 0.156757E+10 | 0.348269E+09 | 0.121930E+10 | 0.00 | 0.00 |
June | 0.188347E+10 | 0.463191E+09 | 0.156621E+10 | 0.263538E+09 | 0.130267E+10 | 0.00 | 0.00 |
July | 0.217630E+10 | 0.311271E+09 | 0.159889E+10 | 0.294203E+09 | 0.130469E+10 | 0.00 | 0.00 |
August | 0.220747E+10 | 0.434878E+09 | 0.166167E+10 | 0.397265E+09 | 0.126441E+10 | 0.00 | 0.00 |
September | 0.205417E+10 | 0.709393E+09 | 0.170759E+10 | 0.673537E+09 | 0.103405E+10 | 0.00 | 0.00 |
October | 0.159572E+10 | 0.122861E+10 | 0.162581E+10 | 0.788262E+09 | 0.837544E+09 | 0.00 | 0.00 |
November | 0.887172E+09 | 0.163006E+10 | 0.111773E+10 | 0.541503E+09 | 0.576223E+09 | 0.00 | 0.00 |
December | 0.567837E+09 | 0.261561E+10 | 0.107509E+10 | 0.477475E+09 | 0.597618E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.174072E+11 | 0.162871E+11 | 0.179791E+11 | 0.631891E+10 | 0.116602E+11 | 0.00 | 0.00 |
Minimum of Months | 0.567837E+09 | 0.311271E+09 | 0.107509E+10 | 0.263538E+09 | 0.576223E+09 | 0.00 | 0.00 |
Maximum of Months | 0.220747E+10 | 0.266831E+10 | 0.183686E+10 | 0.861259E+09 | 0.130469E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -3.4 | -4.9 | -8.7 | 5.96 | -14.4 | 41.15 | 62.17 | 0.00 |
February | -4.2 | -5.4 | -8.1 | 6.66 | -15.1 | 65.72 | 71.39 | 0.00 |
March | 2.67 | 0.66 | -2.8 | 5.20 | -8.9 | 69.76 | 141.76 | 0.00 |
April | 7.47 | 4.95 | 1.92 | 5.29 | -2.7 | 89.32 | 159.79 | 0.00 |
May | 13.73 | 9.66 | 5.81 | 4.79 | 3.34 | 93.75 | 203.34 | 0.03 |
June | 18.63 | 14.47 | 11.49 | 5.10 | 8.69 | 105.42 | 236.95 | 0.00 |
July | 22.03 | 18.19 | 16.11 | 4.43 | 13.39 | 102.98 | 214.28 | 0.00 |
August | 20.69 | 16.39 | 13.72 | 4.23 | 11.88 | 99.24 | 178.64 | 0.00 |
September | 16.55 | 13.42 | 11.22 | 4.10 | 7.08 | 75.66 | 154.97 | 0.03 |
October | 9.73 | 7.36 | 4.97 | 4.79 | 0.13 | 58.70 | 104.01 | 0.00 |
November | 6.03 | 3.70 | 0.77 | 5.87 | -3.2 | 41.19 | 58.47 | 0.00 |
December | -2.2 | -3.2 | -5.3 | 6.59 | -12.0 | 40.52 | 44.30 | 0.00 |
Annual Sum or Average | 9.05 | 6.33 | 3.49 | 5.24 | -0.9 | 73.64 | 136.19 | 0.01 |
Minimum of Months | -4.2 | -5.4 | -8.7 | 4.10 | -15.1 | 40.52 | 44.30 | 0.00 |
Maximum of Months | 22.03 | 18.19 | 16.11 | 6.66 | 13.39 | 105.42 | 236.95 | 0.03 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.70 | 11-JAN-15:00 | 10.14 | 8.90 | 13.40 | 7.15 | 65.50 | 1.00 |
February | 12.80 | 22-FEB-17:00 | 6.18 | -2.2 | 14.90 | 3.48 | 0.00 | 0.00 |
March | 26.10 | 15-MAR-13:00 | 16.06 | 9.40 | 6.70 | 14.65 | 249.50 | 400.00 |
April | 21.10 | 08-APR-12:00 | 13.43 | 7.80 | 8.20 | 11.46 | 330.00 | 283.50 |
May | 26.10 | 10-MAY-13:00 | 17.84 | 13.30 | 5.20 | 13.35 | 258.50 | 457.00 |
June | 30.60 | 12-JUN-13:00 | 20.23 | 15.00 | 8.20 | 17.93 | 252.00 | 572.00 |
July | 31.70 | 21-JUL-13:00 | 21.73 | 17.20 | 5.20 | 22.47 | 330.00 | 231.00 |
August | 30.60 | 10-AUG-13:00 | 20.24 | 15.00 | 5.70 | 19.70 | 220.50 | 635.00 |
September | 27.20 | 16-SEP-13:09 | 19.53 | 15.68 | 8.80 | 17.30 | 207.00 | 564.67 |
October | 22.20 | 11-OCT-12:00 | 14.14 | 8.30 | 6.20 | 6.95 | 121.00 | 665.00 |
November | 19.40 | 05-NOV-13:00 | 13.85 | 10.00 | 12.40 | 14.84 | 133.00 | 3.50 |
December | 15.00 | 01-DEC-10:00 | 12.41 | 10.60 | 12.90 | 10.69 | 56.50 | 11.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 11.70 | 6.18 | -2.2 | 5.20 | 3.48 | 0.00 | 0.00 | |
Maximum of Months | 31.70 | 21.73 | 17.20 | 14.90 | 22.47 | 330.00 | 665.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -13.9 | 31-JAN-01:00 | -14.5 | -17.2 | 1.50 | -25.9 | 0.00 | 0.00 |
February | -16.7 | 07-FEB-06:00 | -17.3 | -20.6 | 6.20 | -35.1 | 0.00 | 0.00 |
March | -13.3 | 07-MAR-05:19 | -13.9 | -16.7 | 2.43 | -32.2 | 0.00 | 0.00 |
April | -4.4 | 17-APR-05:00 | -5.4 | -7.8 | 2.10 | -20.5 | 35.00 | 151.50 |
May | 1.70 | 01-MAY-04:00 | 0.96 | 0.00 | 0.00 | -14.2 | 0.00 | 0.00 |
June | 6.70 | 04-JUN-04:00 | 5.40 | 3.90 | 2.10 | -7.3 | 20.00 | 104.00 |
July | 11.70 | 03-JUL-03:00 | 11.07 | 10.60 | 2.10 | -1.2 | 0.00 | 0.00 |
August | 11.10 | 01-AUG-04:00 | 10.75 | 10.60 | 2.10 | -0.8 | 0.00 | 0.00 |
September | 6.10 | 05-SEP-05:00 | 5.59 | 5.00 | 2.10 | -6.2 | 24.50 | 41.00 |
October | -2.8 | 17-OCT-04:10 | -3.2 | -4.0 | 2.18 | -19.4 | 0.00 | 0.00 |
November | -3.9 | 24-NOV-05:00 | -4.5 | -5.6 | 2.10 | -18.1 | 0.00 | 0.00 |
December | -18.9 | 11-DEC-05:00 | -19.4 | -23.3 | 2.10 | -35.1 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -18.9 | -19.4 | -23.3 | 0.00 | -35.1 | 0.00 | 0.00 | |
Maximum of Months | 11.70 | 11.07 | 10.60 | 6.20 | -0.8 | 35.00 | 151.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.21 | 11-JAN-17:00 | 11.10 | 9.40 | 10.30 | 6.55 | 0.00 | 0.00 |
February | 6.89 | 01-FEB-03:00 | 7.20 | 6.70 | 3.60 | 2.22 | 0.00 | 0.00 |
March | 17.83 | 14-MAR-12:00 | 25.00 | 13.90 | 6.20 | 14.10 | 197.00 | 562.50 |
April | 13.78 | 08-APR-13:00 | 20.60 | 8.90 | 10.30 | 9.72 | 268.50 | 325.50 |
May | 18.19 | 10-MAY-14:00 | 26.10 | 13.90 | 5.20 | 16.85 | 273.00 | 238.00 |
June | 23.75 | 27-JUN-12:00 | 30.60 | 21.10 | 9.30 | 21.09 | 304.00 | 606.00 |
July | 24.79 | 21-JUL-01:00 | 28.90 | 23.30 | 8.80 | 27.46 | 0.00 | 0.00 |
August | 23.42 | 13-AUG-15:00 | 29.40 | 21.10 | 9.80 | 19.87 | 212.00 | 276.00 |
September | 21.17 | 15-SEP-11:00 | 26.10 | 18.90 | 3.60 | 16.30 | 204.00 | 464.50 |
October | 15.23 | 12-OCT-14:00 | 18.30 | 13.30 | 10.30 | 9.13 | 148.00 | 367.50 |
November | 13.96 | 05-NOV-14:00 | 18.30 | 11.10 | 11.30 | 14.10 | 72.00 | 6.00 |
December | 12.41 | 01-DEC-10:00 | 15.00 | 10.60 | 12.90 | 10.69 | 56.50 | 11.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.89 | 7.20 | 6.70 | 3.60 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 24.79 | 30.60 | 23.30 | 12.90 | 27.46 | 304.00 | 606.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.40 | 11-JAN-13:00 | 10.00 | 9.66 | 12.90 | 5.54 | 95.50 | 2.00 |
February | 6.70 | 01-FEB-04:10 | 7.20 | 6.89 | 3.52 | 2.22 | 0.00 | 0.00 |
March | 15.00 | 14-MAR-10:20 | 20.33 | 16.97 | 4.80 | 10.50 | 159.17 | 592.83 |
April | 11.10 | 08-APR-21:00 | 13.90 | 12.23 | 12.90 | 9.72 | 0.00 | 0.00 |
May | 15.60 | 17-MAY-12:00 | 16.70 | 15.97 | 6.70 | 13.54 | 184.00 | 0.00 |
June | 21.70 | 27-JUN-14:00 | 25.60 | 22.78 | 8.20 | 16.85 | 255.50 | 530.00 |
July | 23.30 | 20-JUL-20:00 | 25.60 | 24.03 | 4.60 | 24.16 | 0.00 | 0.00 |
August | 21.70 | 14-AUG-03:20 | 23.70 | 22.19 | 5.00 | 21.90 | 0.00 | 0.00 |
September | 20.00 | 15-SEP-18:00 | 21.70 | 20.51 | 0.00 | 19.52 | 0.00 | 0.00 |
October | 14.40 | 01-OCT-07:19 | 14.60 | 14.50 | 3.77 | 10.56 | 67.50 | 30.17 |
November | 11.70 | 05-NOV-15:00 | 12.80 | 12.14 | 7.20 | 8.74 | 28.00 | 4.50 |
December | 11.10 | 01-DEC-12:00 | 13.90 | 12.22 | 10.30 | 6.35 | 158.00 | 84.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.70 | 7.20 | 6.89 | 0.00 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 23.30 | 25.60 | 24.03 | 12.90 | 24.16 | 255.50 | 592.83 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 7.32 | 12.49 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 6.57 | 19.26 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 7.29 | 28.63 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 9.34 | 37.44 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 12.19 | 46.60 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 15.07 | 54.01 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.20 | 50.29 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 18.01 | 43.20 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.27 | 32.93 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 15.18 | 21.28 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 12.32 | 12.54 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 9.45 | 10.96 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 12.30 | 30.86 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 6.57 | 10.96 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 18.01 | 54.01 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH LAUNDRY G WATER HEATER
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.128368E+12 | -0.126591E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.177683E+10 | 82.14 | 0.00 | 0.00 |
February | 0.116445E+12 | -0.114836E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.160845E+10 | 82.02 | 0.00 | 0.00 |
March | 0.128432E+12 | -0.126631E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.180117E+10 | 82.14 | 0.00 | 0.00 |
April | 0.121102E+12 | -0.119353E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.174908E+10 | 82.17 | 0.00 | 0.00 |
May | 0.120315E+12 | -0.118505E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.180973E+10 | 82.17 | 0.00 | 0.00 |
June | 0.111700E+12 | -0.109963E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.173708E+10 | 82.17 | 0.00 | 0.00 |
July | 0.111803E+12 | -0.110020E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.178329E+10 | 82.17 | 0.00 | 0.00 |
August | 0.110408E+12 | -0.108640E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.176822E+10 | 82.17 | 0.00 | 0.00 |
September | 0.108059E+12 | -0.106356E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.170321E+10 | 82.17 | 0.00 | 0.00 |
October | 0.115196E+12 | -0.113439E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175703E+10 | 82.17 | 0.00 | 0.00 |
November | 0.116169E+12 | -0.114468E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.170112E+10 | 82.17 | 0.00 | 0.00 |
December | 0.124901E+12 | -0.123137E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.176362E+10 | 82.17 | 0.00 | 0.00 |
Annual Sum or Average | 0.141290E+13 | -0.139194E+13 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.209588E+11 | 82.15 | 0.00 | 0.00 |
Minimum of Months | 0.108059E+12 | -0.126631E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.180973E+10 | 82.02 | 0.00 | 0.00 |
Maximum of Months | 0.128432E+12 | -0.106356E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.160845E+10 | 82.17 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.804796E+10 | -0.788296E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -165003521.7 | 82.17 | 0.00 | 0.00 |
February | 0.727242E+10 | -0.712336E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -149065543.4 | 82.17 | 0.00 | 0.00 |
March | 0.804632E+10 | -0.788155E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164771802.4 | 82.17 | 0.00 | 0.00 |
April | 0.779749E+10 | -0.763820E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -159290043.9 | 82.17 | 0.00 | 0.00 |
May | 0.804737E+10 | -0.788296E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164410518.0 | 82.17 | 0.00 | 0.00 |
June | 0.778873E+10 | -0.762976E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -158969501.1 | 82.17 | 0.00 | 0.00 |
July | 0.805559E+10 | -0.789140E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164193901.8 | 82.17 | 0.00 | 0.00 |
August | 0.804718E+10 | -0.788296E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164217985.2 | 82.17 | 0.00 | 0.00 |
September | 0.779863E+10 | -0.763961E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -159028186.2 | 82.17 | 0.00 | 0.00 |
October | 0.804609E+10 | -0.788155E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164536179.6 | 82.17 | 0.00 | 0.00 |
November | 0.778070E+10 | -0.762132E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -159375158.6 | 82.17 | 0.00 | 0.00 |
December | 0.805637E+10 | -0.789140E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164966889.9 | 82.17 | 0.00 | 0.00 |
Annual Sum or Average | 0.947849E+11 | -0.928470E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.193783E+10 | 82.17 | 0.00 | 0.00 |
Minimum of Months | 0.727242E+10 | -0.789140E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -165003521.7 | 82.17 | 0.00 | 0.00 |
Maximum of Months | 0.805637E+10 | -0.712336E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -149065543.4 | 82.17 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.785164E+11 | -0.769765E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.153990E+10 | 60.05 | 0.00 | 0.00 |
February | 0.719326E+11 | -0.705321E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.140047E+10 | 60.05 | 0.00 | 0.00 |
March | 0.786696E+11 | -0.770958E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.157377E+10 | 60.05 | 0.00 | 0.00 |
April | 0.731982E+11 | -0.716680E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.153016E+10 | 60.05 | 0.00 | 0.00 |
May | 0.714842E+11 | -0.698998E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.158443E+10 | 60.05 | 0.00 | 0.00 |
June | 0.651064E+11 | -0.635929E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.151353E+10 | 60.05 | 0.00 | 0.00 |
July | 0.640821E+11 | -0.625344E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.154777E+10 | 60.05 | 0.00 | 0.00 |
August | 0.629333E+11 | -0.614064E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.152688E+10 | 60.05 | 0.00 | 0.00 |
September | 0.619143E+11 | -0.604478E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.146658E+10 | 60.05 | 0.00 | 0.00 |
October | 0.669979E+11 | -0.654866E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.151137E+10 | 60.05 | 0.00 | 0.00 |
November | 0.688853E+11 | -0.674217E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.146367E+10 | 60.05 | 0.00 | 0.00 |
December | 0.753787E+11 | -0.738581E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.152050E+10 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.839099E+12 | -0.820920E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.181790E+11 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.619143E+11 | -0.770958E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.158443E+10 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.786696E+11 | -0.604478E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.140047E+10 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: LOBBY_FLR_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.87 | 0.86 | 01-JAN-09:30 | 3798.15 | 32.91 | 238.17 | 252.83 | 2518.52 | 32.49 | 239.83 | 218.17 |
February | 262.50 | 0.87 | 0.86 | 01-FEB-09:00 | 4822.05 | 32.96 | 249.00 | 259.00 | 973.74 | 25.68 | 228.83 | 231.83 |
March | 339.33 | 0.87 | 0.86 | 01-MAR-07:00 | 4848.52 | 27.15 | 206.00 | 329.50 | 682.92 | 22.11 | 239.00 | 281.17 |
April | 371.17 | 0.87 | 0.86 | 01-APR-07:10 | 1474.63 | 20.01 | 103.33 | 350.17 | 573.20 | 21.72 | 243.17 | 294.33 |
May | 332.17 | 0.87 | 0.86 | 01-MAY-07:10 | 1299.36 | 20.31 | 102.67 | 389.00 | 531.24 | 22.05 | 252.33 | 312.67 |
June | 430.67 | 0.87 | 0.86 | 01-JUN-06:40 | 1195.87 | 19.97 | 101.67 | 397.17 | 483.51 | 21.70 | 297.67 | 330.17 |
July | 439.00 | 0.87 | 0.86 | 01-JUL-06:00 | 1258.98 | 19.89 | 113.50 | 404.17 | 501.71 | 21.62 | 288.50 | 330.00 |
August | 406.00 | 0.87 | 0.86 | 01-AUG-06:40 | 1515.81 | 20.29 | 138.83 | 381.33 | 590.46 | 22.00 | 289.33 | 320.17 |
September | 289.17 | 0.87 | 0.86 | 01-SEP-07:49 | 1906.11 | 21.52 | 147.00 | 327.83 | 739.83 | 22.73 | 236.33 | 279.00 |
October | 314.33 | 0.87 | 0.86 | 01-OCT-07:49 | 5720.05 | 32.51 | 280.50 | 303.00 | 775.43 | 22.94 | 215.83 | 271.00 |
November | 258.33 | 0.87 | 0.86 | 01-NOV-07:40 | 3616.42 | 32.80 | 242.50 | 246.50 | 1444.80 | 29.14 | 219.33 | 211.67 |
December | 230.67 | 0.87 | 0.86 | 01-DEC-08:09 | 3173.97 | 31.67 | 213.50 | 242.17 | 2344.93 | 32.69 | 220.17 | 200.83 |
Annual Sum or Average | 3928.50 | 0.87 | 2687.50 | 25.00 | 2136.67 | 3882.67 | 906.00 | 24.07 | 2970.33 | 3281.00 | ||
Minimum of Months | 230.67 | 0.87 | 0.86 | 1195.87 | 19.89 | 101.67 | 242.17 | 483.51 | 21.62 | 215.83 | 200.83 | |
Maximum of Months | 439.00 | 0.87 | 0.86 | 5720.05 | 32.96 | 280.50 | 404.17 | 2518.52 | 32.69 | 297.67 | 330.17 |
Report: DaylightingReportMonthly
For: CAFE_FLR_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.25 | 0.22 | 01-JAN-08:00 | 4113.88 | 33.04 | 239.67 | 264.67 | 2832.67 | 32.60 | 242.83 | 237.50 |
February | 262.50 | 0.25 | 0.22 | 01-FEB-09:39 | 5161.03 | 33.06 | 250.00 | 266.33 | 1309.79 | 25.78 | 234.17 | 247.67 |
March | 339.33 | 0.25 | 0.22 | 01-MAR-07:30 | 5211.07 | 27.39 | 215.67 | 339.33 | 1044.32 | 22.23 | 230.00 | 310.50 |
April | 371.17 | 0.26 | 0.22 | 01-APR-06:00 | 1752.12 | 20.47 | 126.50 | 362.17 | 849.74 | 22.02 | 260.17 | 331.67 |
May | 332.17 | 0.27 | 0.22 | 01-MAY-06:19 | 1562.80 | 20.75 | 126.50 | 405.83 | 793.94 | 22.32 | 276.33 | 362.00 |
June | 430.67 | 0.27 | 0.22 | 01-JUN-06:10 | 1413.26 | 20.56 | 158.17 | 412.17 | 700.19 | 22.11 | 317.67 | 375.00 |
July | 439.00 | 0.27 | 0.22 | 01-JUL-06:10 | 1483.33 | 20.47 | 161.67 | 418.00 | 725.30 | 22.02 | 317.00 | 378.17 |
August | 406.00 | 0.26 | 0.22 | 01-AUG-06:10 | 1779.81 | 20.78 | 173.00 | 394.83 | 853.48 | 22.32 | 307.67 | 358.67 |
September | 289.17 | 0.26 | 0.22 | 01-SEP-07:40 | 2281.09 | 21.69 | 135.00 | 339.67 | 1113.57 | 22.79 | 258.83 | 309.00 |
October | 314.33 | 0.25 | 0.22 | 01-OCT-07:19 | 6065.90 | 32.69 | 282.67 | 312.83 | 1121.23 | 23.10 | 221.67 | 289.67 |
November | 258.33 | 0.26 | 0.22 | 01-NOV-07:40 | 3894.70 | 32.90 | 243.83 | 256.83 | 1724.44 | 29.26 | 224.83 | 230.83 |
December | 230.67 | 0.24 | 0.22 | 01-DEC-07:00 | 3457.19 | 31.81 | 216.00 | 252.33 | 2626.79 | 32.81 | 222.17 | 225.50 |
Annual Sum or Average | 3928.50 | 0.26 | 2976.85 | 25.34 | 2328.67 | 4025.00 | 1194.45 | 24.29 | 3113.33 | 3656.17 | ||
Minimum of Months | 230.67 | 0.24 | 0.22 | 1413.26 | 20.47 | 126.50 | 252.33 | 700.19 | 22.02 | 221.67 | 225.50 | |
Maximum of Months | 439.00 | 0.27 | 0.22 | 6065.90 | 33.06 | 282.67 | 418.00 | 2832.67 | 32.81 | 317.67 | 378.17 |
Report: DaylightingReportMonthly
For: DINING_FLR_6_DAYLCTRL
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.66 | 0.60 | 01-JAN-11:20 | 461.13 | 15.29 | 0.00 | 238.67 | 201.55 | 18.56 | 0.00 | 129.00 |
February | 262.50 | 0.64 | 0.60 | 01-FEB-12:50 | 607.30 | 16.35 | 0.00 | 251.67 | 261.29 | 19.52 | 1.67 | 191.33 |
March | 339.33 | 0.63 | 0.60 | 01-MAR-08:00 | 617.43 | 16.89 | 0.00 | 328.33 | 278.67 | 20.12 | 5.83 | 263.00 |
April | 371.17 | 0.63 | 0.60 | 01-APR-07:10 | 719.83 | 17.52 | 0.00 | 361.67 | 320.21 | 20.67 | 100.50 | 315.67 |
May | 332.17 | 0.62 | 0.60 | 01-MAY-06:10 | 827.89 | 18.72 | 8.67 | 411.00 | 388.42 | 22.47 | 205.83 | 365.83 |
June | 430.67 | 0.62 | 0.60 | 01-JUN-06:10 | 972.72 | 21.06 | 72.00 | 422.00 | 444.10 | 22.93 | 282.17 | 394.33 |
July | 439.00 | 0.62 | 0.60 | 01-JUL-05:19 | 927.49 | 20.61 | 67.17 | 427.00 | 420.74 | 22.71 | 272.50 | 393.83 |
August | 406.00 | 0.62 | 0.60 | 01-AUG-06:10 | 815.85 | 18.31 | 5.33 | 398.00 | 375.83 | 21.49 | 189.50 | 360.33 |
September | 289.17 | 0.63 | 0.60 | 01-SEP-07:40 | 651.62 | 17.68 | 0.00 | 332.83 | 316.30 | 20.89 | 71.33 | 275.67 |
October | 314.33 | 0.64 | 0.60 | 01-OCT-07:00 | 552.94 | 16.25 | 0.00 | 295.00 | 246.75 | 19.49 | 0.17 | 214.33 |
November | 258.33 | 0.67 | 0.60 | 01-NOV-08:39 | 451.23 | 14.98 | 0.00 | 233.33 | 195.48 | 18.19 | 0.00 | 121.83 |
December | 230.67 | 0.66 | 0.60 | 01-DEC-12:20 | 471.76 | 15.27 | 0.00 | 229.17 | 201.16 | 18.49 | 0.00 | 113.50 |
Annual Sum or Average | 3928.50 | 0.63 | 706.05 | 17.77 | 153.17 | 3928.67 | 319.95 | 20.75 | 1129.50 | 3138.67 | ||
Minimum of Months | 230.67 | 0.62 | 0.60 | 451.23 | 14.98 | 0.00 | 229.17 | 195.48 | 18.19 | 0.00 | 113.50 | |
Maximum of Months | 439.00 | 0.67 | 0.60 | 972.72 | 21.06 | 72.00 | 427.00 | 444.10 | 22.93 | 282.17 | 394.33 |
Report: DaylightingReportMonthly
For: BANQUET_FLR_6_DAYLCTRL
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.66 | 0.60 | 01-JAN-11:20 | 461.13 | 15.29 | 0.00 | 238.67 | 201.55 | 18.56 | 0.00 | 129.00 |
February | 262.50 | 0.64 | 0.60 | 01-FEB-12:50 | 607.30 | 16.35 | 0.00 | 251.67 | 261.29 | 19.52 | 1.67 | 191.33 |
March | 339.33 | 0.63 | 0.60 | 01-MAR-08:00 | 617.43 | 16.89 | 0.00 | 328.33 | 278.67 | 20.12 | 5.83 | 263.00 |
April | 371.17 | 0.63 | 0.60 | 01-APR-07:10 | 719.83 | 17.52 | 0.00 | 361.67 | 320.21 | 20.67 | 100.33 | 315.67 |
May | 332.17 | 0.62 | 0.60 | 01-MAY-06:10 | 827.89 | 18.72 | 8.67 | 411.00 | 388.42 | 22.47 | 205.83 | 365.83 |
June | 430.67 | 0.62 | 0.60 | 01-JUN-06:10 | 972.72 | 21.06 | 72.00 | 422.00 | 444.10 | 22.93 | 282.17 | 394.33 |
July | 439.00 | 0.62 | 0.60 | 01-JUL-05:19 | 927.49 | 20.61 | 67.17 | 427.00 | 420.74 | 22.71 | 272.50 | 393.83 |
August | 406.00 | 0.62 | 0.60 | 01-AUG-06:10 | 815.85 | 18.31 | 5.33 | 398.00 | 375.83 | 21.49 | 189.50 | 360.33 |
September | 289.17 | 0.63 | 0.60 | 01-SEP-07:40 | 651.62 | 17.68 | 0.00 | 332.83 | 316.30 | 20.89 | 71.33 | 275.67 |
October | 314.33 | 0.64 | 0.60 | 01-OCT-07:00 | 552.94 | 16.25 | 0.00 | 295.00 | 246.75 | 19.49 | 0.17 | 214.33 |
November | 258.33 | 0.67 | 0.60 | 01-NOV-08:39 | 451.23 | 14.98 | 0.00 | 233.33 | 195.48 | 18.19 | 0.00 | 121.83 |
December | 230.67 | 0.66 | 0.60 | 01-DEC-12:20 | 471.76 | 15.27 | 0.00 | 229.17 | 201.16 | 18.49 | 0.00 | 113.50 |
Annual Sum or Average | 3928.50 | 0.63 | 706.05 | 17.77 | 153.17 | 3928.67 | 319.95 | 20.75 | 1129.33 | 3138.67 | ||
Minimum of Months | 230.67 | 0.62 | 0.60 | 451.23 | 14.98 | 0.00 | 229.17 | 195.48 | 18.19 | 0.00 | 113.50 | |
Maximum of Months | 439.00 | 0.67 | 0.60 | 972.72 | 21.06 | 72.00 | 427.00 | 444.10 | 22.93 | 282.17 | 394.33 |
Report: CoilReportMonthly
For: FLR_3_DOAS HEATING COIL
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.396169E+10 | 7565.21 | 31-JAN-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.418659E+10 | 8696.42 | 06-FEB-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.161210E+10 | 5490.40 | 07-MAR-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 80335264.71 | 1649.36 | 17-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 9601.52 | 0.32 | 17-MAY-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 13260.88 | 0.31 | 22-JUN-00:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 14248.98 | 0.32 | 05-JUL-15:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 18258.21 | 0.32 | 16-AUG-05:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17725.41 | 0.32 | 07-SEP-02:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 15771371.99 | 960.77 | 17-OCT-04:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 63736683.96 | 1435.83 | 24-NOV-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.328049E+10 | 7905.67 | 11-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.132008E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 9601.52 | 0.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.418659E+10 | 8696.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.976921E+11 | 113362.23 | 11-JAN-18:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.975484E+11 | 126383.00 | 07-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.631024E+11 | 118095.32 | 29-MAR-17:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.524666E+11 | 126271.92 | 13-APR-10:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.615605E+11 | 111365.88 | 06-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.195483E+11 | 112641.64 | 06-JUN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.302295E+10 | 47594.78 | 13-JUL-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.651101E+10 | 60060.64 | 01-AUG-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.354149E+11 | 110706.20 | 05-SEP-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.720877E+11 | 117994.71 | 15-OCT-09:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.424255E+11 | 132517.16 | 12-NOV-11:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.811522E+11 | 123733.63 | 11-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.632533E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.302295E+10 | 47594.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.976921E+11 | 132517.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.357428E+10 | 2458.30 | 04-JAN-07:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.316406E+10 | 2632.73 | 07-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.166169E+10 | 2057.53 | 05-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.998464E+09 | 1581.45 | 17-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.288856E+09 | 907.38 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 25858826.41 | 444.04 | 14-JUN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 3544205.09 | 348.33 | 31-AUG-10:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 80265600.44 | 875.38 | 30-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.810620E+09 | 1402.28 | 30-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172501E+10 | 1741.33 | 24-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.360073E+10 | 2488.33 | 11-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.159334E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.360073E+10 | 2632.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.177837E+09 | 510.83 | 29-JAN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.164066E+09 | 623.47 | 06-FEB-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 3972622.27 | 248.49 | 21-MAR-10:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 179557.84 | 262.78 | 17-APR-10:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 3929687.97 | 172.58 | 24-NOV-11:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.165496E+09 | 498.90 | 12-DEC-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.515482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.177837E+09 | 623.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.123704E+10 | 970.19 | 31-JAN-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.119550E+10 | 1179.72 | 07-FEB-11:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.481860E+09 | 846.42 | 07-MAR-11:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 53985762.21 | 600.26 | 17-APR-10:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.103339E+09 | 544.85 | 24-NOV-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.107028E+10 | 1020.07 | 11-DEC-11:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.414200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.123704E+10 | 1179.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.122315E+10 | 783.68 | 31-JAN-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.115199E+10 | 898.11 | 07-FEB-11:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.571755E+09 | 645.40 | 07-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.125845E+09 | 465.37 | 17-APR-10:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 18075899.74 | 211.73 | 17-OCT-10:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.236211E+09 | 427.17 | 23-NOV-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.110878E+10 | 810.40 | 11-DEC-10:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.443580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.122315E+10 | 898.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.258398E+09 | 1879.74 | 30-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.252042E+09 | 2152.60 | 07-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.133673E+09 | 1592.54 | 06-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 48790447.11 | 1237.45 | 17-APR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6332541.76 | 449.65 | 01-MAY-03:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 41152.68 | 68.59 | 14-JUN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2148438.90 | 449.65 | 30-SEP-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 28551901.41 | 969.11 | 30-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 74934618.73 | 1289.60 | 24-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.248497E+09 | 2063.16 | 11-DEC-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.105341E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.258398E+09 | 2152.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.261756E+10 | 5059.18 | 26-JAN-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.217287E+10 | 6569.37 | 06-FEB-09:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.540041E+09 | 3834.63 | 20-MAR-08:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.240814E+09 | 2830.53 | 14-APR-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 29266210.20 | 1928.37 | 12-MAY-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 22958.36 | 76.53 | 31-AUG-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 13246395.49 | 1843.54 | 29-SEP-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.127684E+09 | 2056.38 | 08-OCT-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.932502E+09 | 4003.79 | 30-NOV-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.288410E+10 | 5563.69 | 11-DEC-09:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.955810E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.288410E+10 | 6569.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.123478E+10 | 8123.50 | 29-JAN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.107778E+10 | 10032.56 | 06-FEB-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 10984688.61 | 2764.28 | 20-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 22472486.06 | 2163.90 | 30-NOV-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.121596E+10 | 7797.19 | 12-DEC-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.356197E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.123478E+10 | 10032.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.108492E+11 | 7485.93 | 29-JAN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.947147E+10 | 8918.57 | 06-FEB-09:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.340479E+10 | 5505.74 | 07-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.748566E+09 | 3924.58 | 17-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.436538E+09 | 3627.08 | 30-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.358240E+10 | 5548.04 | 30-NOV-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.107006E+11 | 8148.64 | 11-DEC-09:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.391936E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.108492E+11 | 8918.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.656400E+10 | 4550.73 | 10-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.587437E+10 | 5461.82 | 07-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.264953E+10 | 4103.57 | 07-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.663307E+09 | 2757.89 | 17-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1786897.99 | 411.15 | 01-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.506002E+09 | 2398.93 | 17-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.206955E+10 | 2910.91 | 24-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.629505E+10 | 5171.33 | 11-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.246236E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.656400E+10 | 5461.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.611980E+10 | 6693.70 | 14-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.531935E+10 | 6694.00 | 01-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.241537E+10 | 6678.83 | 20-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.949629E+09 | 6569.41 | 16-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 95555381.81 | 5838.94 | 02-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 9774653.13 | 4214.82 | 14-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7766952.32 | 4171.31 | 02-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 10449722.40 | 4427.84 | 30-AUG-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 47993478.52 | 4889.54 | 24-SEP-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.919636E+09 | 6525.08 | 30-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.241150E+10 | 6692.90 | 29-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.593948E+10 | 6694.45 | 14-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.242463E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 7766952.32 | 4171.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.611980E+10 | 6694.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.696807E+10 | 6651.54 | 14-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.603075E+10 | 6652.00 | 01-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.311993E+10 | 6650.17 | 01-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115508E+10 | 6551.41 | 17-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.108080E+09 | 4903.50 | 02-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 7030240.99 | 4385.76 | 04-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 3330723.57 | 4409.82 | 06-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6847243.55 | 4460.71 | 31-AUG-18:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 53522601.42 | 5207.30 | 23-SEP-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.121709E+10 | 6598.93 | 17-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.290463E+10 | 6651.19 | 28-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.658604E+10 | 6652.30 | 14-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.281604E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 3330723.57 | 4385.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.696807E+10 | 6652.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.131563E+10 | 13612.82 | 04-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176445E+10 | 17769.49 | 07-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.214083E+09 | 4749.07 | 10-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.329417E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.176445E+10 | 17769.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.243073E+11 | 37786.37 | 31-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.216744E+11 | 37786.19 | 06-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.107674E+11 | 37486.45 | 06-MAR-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.140017E+10 | 35771.08 | 22-APR-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.106724E+09 | 35657.82 | 02-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 32991880.32 | 30623.04 | 05-JUN-15:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 10317873.84 | 17646.49 | 31-JUL-21:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 23147487.28 | 29219.82 | 31-AUG-15:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 71213818.31 | 33160.40 | 18-SEP-15:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120583E+10 | 35789.45 | 10-OCT-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.497433E+10 | 36587.17 | 24-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.220047E+11 | 37787.49 | 28-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.865786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 10317873.84 | 17646.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.243073E+11 | 37787.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.593901E+10 | 6554.73 | 14-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.519207E+10 | 6555.05 | 01-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.244668E+10 | 6533.72 | 04-MAR-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.943080E+09 | 6361.22 | 16-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.121098E+09 | 6193.59 | 03-MAY-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 9676188.20 | 4259.63 | 13-JUN-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1197942.27 | 2670.04 | 02-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 4776672.84 | 4390.36 | 30-AUG-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 48615450.13 | 4951.13 | 23-SEP-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.898906E+09 | 6353.58 | 29-OCT-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.241727E+10 | 6554.15 | 23-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.592521E+10 | 6555.53 | 14-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.239476E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1197942.27 | 2670.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.593901E+10 | 6555.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.675663E+10 | 6511.92 | 14-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.587754E+10 | 6512.24 | 01-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.317284E+10 | 6509.68 | 04-MAR-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.113325E+10 | 6350.10 | 16-APR-18:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.137608E+09 | 6153.24 | 03-MAY-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 7438464.58 | 3689.46 | 03-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1196950.76 | 2077.42 | 11-JUL-21:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 3838216.21 | 4165.08 | 24-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 56082697.71 | 5301.82 | 23-SEP-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.115456E+10 | 6355.03 | 29-OCT-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.287205E+10 | 6511.54 | 28-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.657726E+10 | 6512.72 | 14-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.277503E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1196950.76 | 2077.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.675663E+10 | 6512.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.212072E+10 | 1984.33 | 11-JAN-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.184971E+10 | 1984.37 | 01-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.918495E+09 | 1984.02 | 19-MAR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.408119E+09 | 1980.07 | 16-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 71375850.52 | 1284.09 | 17-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 7048566.63 | 1070.65 | 21-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1966808.11 | 1038.34 | 28-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 3227869.24 | 1043.80 | 07-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 29856542.80 | 1257.94 | 23-SEP-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.405648E+09 | 1969.68 | 17-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.920438E+09 | 1984.36 | 20-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.205503E+10 | 1984.35 | 14-DEC-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.879163E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1966808.11 | 1038.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.212072E+10 | 1984.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.236547E+10 | 1969.02 | 11-JAN-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.205626E+10 | 1969.07 | 01-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.113851E+10 | 1968.71 | 19-MAR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.478229E+09 | 1968.36 | 17-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 73729226.08 | 1258.53 | 03-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3406898.70 | 971.69 | 04-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 861039.14 | 953.75 | 06-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1903738.80 | 1051.98 | 31-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 30866284.08 | 1261.15 | 23-SEP-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.513364E+09 | 1968.74 | 30-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.108096E+10 | 1969.06 | 20-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.224773E+10 | 1969.29 | 01-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.999129E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 861039.14 | 953.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.236547E+10 | 1969.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.682833E+10 | 9482.90 | 18-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.615006E+10 | 9483.78 | 01-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.239913E+10 | 9369.38 | 20-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.109051E+10 | 9212.45 | 17-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.159380E+09 | 7975.91 | 17-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 24739197.14 | 5907.53 | 07-JUN-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6292087.94 | 5110.33 | 05-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 10391807.19 | 5798.33 | 09-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 45194341.35 | 6864.48 | 23-SEP-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.789546E+09 | 9130.11 | 24-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.239947E+10 | 9482.07 | 30-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.700490E+10 | 9484.45 | 14-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.269079E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 6292087.94 | 5110.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.700490E+10 | 9484.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.105566E+10 | 0.101810E+10 | 20597.44 | 14-MAR-12:15 | 16101.69 | 0.05 |
April | 0.00 | 0.00 | 0.441673E+09 | 0.441673E+09 | 13334.54 | 08-APR-13:00 | 13334.54 | 0.02 |
May | 0.00 | 0.00 | 0.484402E+10 | 0.463670E+10 | 20799.01 | 10-MAY-15:02 | 17571.75 | 0.18 |
June | 0.00 | 0.00 | 0.221055E+11 | 0.153086E+11 | 42305.96 | 18-JUN-08:62 | 18551.87 | 0.54 |
July | 0.00 | 0.00 | 0.401031E+11 | 0.246561E+11 | 41895.96 | 17-JUL-18:03 | 17674.97 | 0.74 |
August | 0.00 | 0.00 | 0.294595E+11 | 0.202800E+11 | 40550.07 | 14-AUG-08:61 | 17962.72 | 0.69 |
September | 0.00 | 0.00 | 0.146686E+11 | 0.100012E+11 | 37049.81 | 15-SEP-20:00 | 15150.12 | 0.47 |
October | 0.00 | 0.00 | 0.151414E+10 | 0.151414E+10 | 14829.38 | 11-OCT-15:01 | 14829.38 | 0.12 |
November | 0.00 | 0.00 | 0.566791E+09 | 0.566791E+09 | 8665.56 | 05-NOV-13:00 | 8665.56 | 0.04 |
December | 0.00 | 0.00 | 849913.39 | 849913.39 | 572.03 | 01-DEC-11:00 | 572.03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.114760E+12 | 0.784241E+11 | 0.24 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.401031E+11 | 0.246561E+11 | 42305.96 | 18551.87 | 0.74 |
Report: CoilReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 338043.09 | 338043.09 | 103.29 | 23-JAN-02:70 | 103.29 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.145278E+11 | 0.142819E+11 | 205907.65 | 14-MAR-10:45 | 140788.53 | 0.06 |
April | 0.00 | 0.00 | 0.839677E+10 | 0.839677E+10 | 104138.67 | 08-APR-13:00 | 104138.67 | 0.04 |
May | 0.00 | 0.00 | 0.684660E+11 | 0.673118E+11 | 182921.32 | 10-MAY-15:30 | 161794.84 | 0.25 |
June | 0.00 | 0.00 | 0.278497E+12 | 0.205124E+12 | 514969.43 | 27-JUN-20:04 | 204494.81 | 0.69 |
July | 0.00 | 0.00 | 0.517479E+12 | 0.328081E+12 | 513583.00 | 21-JUL-20:04 | 202959.71 | 0.94 |
August | 0.00 | 0.00 | 0.379345E+12 | 0.276101E+12 | 451679.04 | 14-AUG-22:00 | 205404.68 | 0.89 |
September | 0.00 | 0.00 | 0.183876E+12 | 0.136664E+12 | 424208.73 | 15-SEP-20:20 | 171987.71 | 0.62 |
October | 0.00 | 0.00 | 0.227346E+11 | 0.227346E+11 | 132621.08 | 11-OCT-15:15 | 132621.08 | 0.16 |
November | 0.00 | 0.00 | 0.720306E+10 | 0.720306E+10 | 79919.23 | 05-NOV-10:45 | 79919.23 | 0.06 |
December | 0.00 | 0.00 | 9040451.82 | 9040451.82 | 6525.92 | 01-DEC-11:35 | 6525.92 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.148053E+13 | 0.106591E+13 | 0.31 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.517479E+12 | 0.328081E+12 | 514969.43 | 205404.68 | 0.94 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 9168842.12 | 5660350.46 | 12549.94 | 15-JAN-16:01 | 12549.94 | 0.00 |
February | 0.00 | 0.00 | 34949429.23 | 29843659.68 | 16624.63 | 28-FEB-16:01 | 16624.63 | 0.00 |
March | 0.00 | 0.00 | 0.704715E+09 | 0.454767E+09 | 16629.73 | 25-MAR-15:01 | 16629.73 | 0.10 |
April | 0.00 | 0.00 | 0.152344E+10 | 0.950491E+09 | 16627.66 | 17-APR-15:01 | 16627.66 | 0.29 |
May | 0.00 | 0.00 | 0.397971E+10 | 0.234668E+10 | 16985.17 | 17-MAY-15:01 | 13399.83 | 0.64 |
June | 0.00 | 0.00 | 0.797928E+10 | 0.445103E+10 | 18314.98 | 08-JUN-08:62 | 11598.11 | 0.90 |
July | 0.00 | 0.00 | 0.101385E+11 | 0.553522E+10 | 18344.25 | 29-JUL-08:61 | 12339.27 | 0.95 |
August | 0.00 | 0.00 | 0.902738E+10 | 0.493855E+10 | 18043.91 | 14-AUG-08:61 | 12593.13 | 0.93 |
September | 0.00 | 0.00 | 0.539363E+10 | 0.257557E+10 | 18100.59 | 13-SEP-18:01 | 12544.91 | 0.86 |
October | 0.00 | 0.00 | 0.128945E+10 | 0.569638E+09 | 17233.64 | 01-OCT-08:62 | 11984.42 | 0.34 |
November | 0.00 | 0.00 | 0.115419E+09 | 46987661.77 | 15687.14 | 04-NOV-15:01 | 13309.36 | 0.06 |
December | 0.00 | 0.00 | 4835728.48 | 3830820.49 | 14008.77 | 04-DEC-16:02 | 14008.77 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.402004E+11 | 0.219083E+11 | 0.42 | |||
Minimum of Months | 0.00 | 0.00 | 4835728.48 | 3830820.49 | 12549.94 | 11598.11 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.101385E+11 | 0.553522E+10 | 18344.25 | 16629.73 | 0.95 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 985643.07 | 374769.12 | 3463.28 | 15-JAN-16:01 | 2018.54 | 0.00 |
February | 0.00 | 0.00 | 5647898.61 | 4637152.37 | 9821.21 | 28-FEB-16:01 | 9821.21 | 0.00 |
March | 0.00 | 0.00 | 0.304729E+09 | 0.170075E+09 | 16439.15 | 14-MAR-15:01 | 13026.69 | 0.07 |
April | 0.00 | 0.00 | 0.905528E+09 | 0.530122E+09 | 17809.96 | 19-APR-18:11 | 17809.96 | 0.20 |
May | 0.00 | 0.00 | 0.255619E+10 | 0.134465E+10 | 18165.10 | 03-MAY-18:01 | 18165.10 | 0.49 |
June | 0.00 | 0.00 | 0.575391E+10 | 0.310413E+10 | 20446.82 | 18-JUN-08:21 | 11909.87 | 0.67 |
July | 0.00 | 0.00 | 0.793029E+10 | 0.447873E+10 | 20487.50 | 16-JUL-08:21 | 11738.92 | 0.71 |
August | 0.00 | 0.00 | 0.653946E+10 | 0.353526E+10 | 20179.61 | 14-AUG-08:21 | 11495.76 | 0.68 |
September | 0.00 | 0.00 | 0.284487E+10 | 0.110729E+10 | 17917.65 | 15-SEP-21:51 | 12266.60 | 0.59 |
October | 0.00 | 0.00 | 0.417823E+09 | 0.153363E+09 | 16661.66 | 01-OCT-08:62 | 11343.45 | 0.17 |
November | 0.00 | 0.00 | 21880168.20 | 10235781.90 | 13800.95 | 05-NOV-15:01 | 11813.08 | 0.01 |
December | 0.00 | 0.00 | 633692.73 | 264518.19 | 2437.12 | 01-DEC-19:05 | 799.61 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.272819E+11 | 0.144391E+11 | 0.30 | |||
Minimum of Months | 0.00 | 0.00 | 633692.73 | 264518.19 | 2437.12 | 799.61 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.793029E+10 | 0.447873E+10 | 20487.50 | 18165.10 | 0.71 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.339702E+10 | 0.167305E+10 | 41451.63 | 15-MAR-13:30 | 29412.52 | 0.09 |
April | 0.00 | 0.00 | 0.993089E+10 | 0.728227E+10 | 31583.18 | 22-APR-13:00 | 31583.18 | 0.18 |
May | 0.00 | 0.00 | 0.219075E+11 | 0.103185E+11 | 30209.42 | 14-MAY-13:15 | 16657.63 | 0.60 |
June | 0.00 | 0.00 | 0.344396E+11 | 0.128544E+11 | 34761.39 | 27-JUN-13:00 | 20785.80 | 0.94 |
July | 0.00 | 0.00 | 0.471008E+11 | 0.193918E+11 | 39114.03 | 30-JUL-12:30 | 25953.90 | 1.00 |
August | 0.00 | 0.00 | 0.467554E+11 | 0.207455E+11 | 44000.29 | 18-AUG-13:30 | 35122.10 | 0.99 |
September | 0.00 | 0.00 | 0.379538E+11 | 0.177556E+11 | 54111.00 | 21-SEP-13:00 | 39289.74 | 0.91 |
October | 0.00 | 0.00 | 0.175918E+11 | 0.977417E+10 | 55542.68 | 11-OCT-12:30 | 41370.87 | 0.44 |
November | 0.00 | 0.00 | 0.335997E+10 | 0.224833E+10 | 31703.93 | 03-NOV-12:30 | 31703.93 | 0.09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.222437E+12 | 0.102044E+12 | 0.44 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.471008E+11 | 0.207455E+11 | 55542.68 | 41370.87 | 1.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.117800E+09 | 64018015.27 | 61557.12 | 15-JAN-09:02 | 61557.12 | 0.01 |
February | 0.00 | 0.00 | 94390571.65 | 77345743.16 | 61682.92 | 20-FEB-09:02 | 61682.92 | 0.01 |
March | 0.00 | 0.00 | 0.554412E+10 | 0.272399E+10 | 86524.36 | 14-MAR-15:01 | 74124.14 | 0.18 |
April | 0.00 | 0.00 | 0.106562E+11 | 0.588415E+10 | 87203.27 | 22-APR-18:01 | 87203.27 | 0.39 |
May | 0.00 | 0.00 | 0.252850E+11 | 0.154963E+11 | 92240.40 | 17-MAY-18:01 | 72326.74 | 0.51 |
June | 0.00 | 0.00 | 0.410297E+11 | 0.255538E+11 | 112708.63 | 18-JUN-08:21 | 64116.65 | 0.58 |
July | 0.00 | 0.00 | 0.544687E+11 | 0.338215E+11 | 112782.61 | 16-JUL-08:21 | 62069.56 | 0.63 |
August | 0.00 | 0.00 | 0.462865E+11 | 0.278703E+11 | 111733.78 | 14-AUG-08:21 | 59246.29 | 0.61 |
September | 0.00 | 0.00 | 0.282288E+11 | 0.147953E+11 | 101365.58 | 15-SEP-21:51 | 70708.55 | 0.55 |
October | 0.00 | 0.00 | 0.113166E+11 | 0.457539E+10 | 88345.45 | 12-OCT-21:42 | 70908.17 | 0.47 |
November | 0.00 | 0.00 | 0.330059E+10 | 0.139331E+10 | 78139.40 | 04-NOV-15:01 | 72013.89 | 0.21 |
December | 0.00 | 0.00 | 0.213465E+09 | 85776735.38 | 75687.49 | 03-DEC-09:02 | 75687.49 | 0.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.226542E+12 | 0.132341E+12 | 0.35 | |||
Minimum of Months | 0.00 | 0.00 | 94390571.65 | 64018015.27 | 61557.12 | 59246.29 | 0.01 | |
Maximum of Months | 0.00 | 0.00 | 0.544687E+11 | 0.338215E+11 | 112782.61 | 87203.27 | 0.63 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 3138068.26 | 1412475.11 | 5621.77 | 15-JAN-16:01 | 4833.99 | 0.00 |
February | 0.00 | 0.00 | 34704453.42 | 33246110.05 | 14384.69 | 28-FEB-09:02 | 14384.69 | 0.00 |
March | 0.00 | 0.00 | 0.650601E+09 | 0.392371E+09 | 15334.67 | 14-MAR-08:62 | 11514.78 | 0.10 |
April | 0.00 | 0.00 | 0.162047E+10 | 0.959351E+09 | 15207.54 | 22-APR-18:01 | 15207.54 | 0.33 |
May | 0.00 | 0.00 | 0.396120E+10 | 0.222334E+10 | 15510.59 | 17-MAY-15:01 | 12300.87 | 0.67 |
June | 0.00 | 0.00 | 0.754870E+10 | 0.407002E+10 | 16788.81 | 08-JUN-08:62 | 10713.51 | 0.92 |
July | 0.00 | 0.00 | 0.101643E+11 | 0.563124E+10 | 16648.36 | 29-JUL-08:61 | 11420.28 | 0.97 |
August | 0.00 | 0.00 | 0.896560E+10 | 0.489120E+10 | 16433.90 | 28-AUG-18:02 | 11608.19 | 0.95 |
September | 0.00 | 0.00 | 0.555045E+10 | 0.268390E+10 | 16573.81 | 17-SEP-08:61 | 11478.60 | 0.88 |
October | 0.00 | 0.00 | 0.140034E+10 | 0.611582E+09 | 15850.18 | 01-OCT-08:62 | 11388.34 | 0.37 |
November | 0.00 | 0.00 | 0.186802E+09 | 75219812.24 | 14190.56 | 04-NOV-15:01 | 11887.85 | 0.07 |
December | 0.00 | 0.00 | 13451606.10 | 6057372.30 | 1940.47 | 16-DEC-09:03 | 752.41 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.400997E+11 | 0.215789E+11 | 0.44 | |||
Minimum of Months | 0.00 | 0.00 | 3138068.26 | 1412475.11 | 1940.47 | 752.41 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.101643E+11 | 0.563124E+10 | 16788.81 | 15207.54 | 0.97 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 1018592.21 | 310478.38 | 1872.86 | 17-JAN-19:05 | 677.09 | 0.00 |
February | 0.00 | 0.00 | 3894996.18 | 3707182.22 | 6176.12 | 28-FEB-09:02 | 6176.12 | 0.00 |
March | 0.00 | 0.00 | 0.283618E+09 | 0.134796E+09 | 14781.67 | 14-MAR-08:62 | 11001.87 | 0.07 |
April | 0.00 | 0.00 | 0.958967E+09 | 0.552500E+09 | 14750.52 | 22-APR-18:01 | 14750.52 | 0.23 |
May | 0.00 | 0.00 | 0.277674E+10 | 0.150504E+10 | 15815.89 | 17-MAY-18:01 | 11331.22 | 0.55 |
June | 0.00 | 0.00 | 0.565362E+10 | 0.308095E+10 | 19124.41 | 18-JUN-08:21 | 12199.43 | 0.69 |
July | 0.00 | 0.00 | 0.789796E+10 | 0.444223E+10 | 19443.58 | 17-JUL-08:32 | 14570.17 | 0.72 |
August | 0.00 | 0.00 | 0.650177E+10 | 0.351002E+10 | 18577.83 | 14-AUG-08:21 | 10622.04 | 0.70 |
September | 0.00 | 0.00 | 0.322544E+10 | 0.142499E+10 | 17248.95 | 16-SEP-08:51 | 13487.75 | 0.64 |
October | 0.00 | 0.00 | 0.513760E+09 | 0.201771E+09 | 15407.63 | 01-OCT-08:62 | 10789.13 | 0.19 |
November | 0.00 | 0.00 | 40887136.32 | 13835252.63 | 13231.57 | 05-NOV-15:01 | 11918.14 | 0.03 |
December | 0.00 | 0.00 | 1008168.36 | 283395.69 | 2040.69 | 01-DEC-19:05 | 632.91 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.278587E+11 | 0.148704E+11 | 0.32 | |||
Minimum of Months | 0.00 | 0.00 | 1008168.36 | 283395.69 | 1872.86 | 632.91 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.789796E+10 | 0.444223E+10 | 19443.58 | 14750.52 | 0.72 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 1706070.63 | 1017062.93 | 3310.27 | 15-JAN-16:01 | 3310.27 | 0.00 |
February | 0.00 | 0.00 | 7717265.78 | 6527670.64 | 4334.55 | 28-FEB-16:01 | 4334.55 | 0.00 |
March | 0.00 | 0.00 | 0.165028E+09 | 0.107123E+09 | 4335.89 | 25-MAR-15:01 | 4335.89 | 0.09 |
April | 0.00 | 0.00 | 0.388268E+09 | 0.252771E+09 | 4335.43 | 17-APR-15:01 | 4335.43 | 0.24 |
May | 0.00 | 0.00 | 0.992208E+09 | 0.620248E+09 | 4443.29 | 17-MAY-15:01 | 3477.07 | 0.55 |
June | 0.00 | 0.00 | 0.201475E+10 | 0.116137E+10 | 4920.41 | 08-JUN-08:62 | 2785.17 | 0.87 |
July | 0.00 | 0.00 | 0.258187E+10 | 0.143792E+10 | 5041.33 | 29-JUL-08:61 | 3001.83 | 0.94 |
August | 0.00 | 0.00 | 0.224924E+10 | 0.126341E+10 | 4977.95 | 14-AUG-08:61 | 3057.38 | 0.92 |
September | 0.00 | 0.00 | 0.127438E+10 | 0.641182E+09 | 4912.65 | 17-SEP-08:61 | 3107.80 | 0.78 |
October | 0.00 | 0.00 | 0.289638E+09 | 0.139662E+09 | 4676.52 | 01-OCT-08:62 | 2811.85 | 0.25 |
November | 0.00 | 0.00 | 21224363.71 | 10052993.42 | 4120.96 | 04-NOV-15:01 | 3362.22 | 0.04 |
December | 0.00 | 0.00 | 866999.55 | 682677.29 | 2664.86 | 16-DEC-16:01 | 2652.50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.998690E+10 | 0.564197E+10 | 0.39 | |||
Minimum of Months | 0.00 | 0.00 | 866999.55 | 682677.29 | 2664.86 | 2652.50 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.258187E+10 | 0.143792E+10 | 5041.33 | 4335.89 | 0.94 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 76983.04 | 35454.31 | 479.28 | 15-JAN-16:03 | 173.12 | 0.00 |
February | 0.00 | 0.00 | 295406.10 | 269210.47 | 546.69 | 22-FEB-16:03 | 546.69 | 0.00 |
March | 0.00 | 0.00 | 63776133.90 | 33748393.26 | 4218.96 | 14-MAR-15:01 | 3429.39 | 0.05 |
April | 0.00 | 0.00 | 0.229023E+09 | 0.139533E+09 | 4772.58 | 19-APR-18:11 | 4772.58 | 0.16 |
May | 0.00 | 0.00 | 0.637104E+09 | 0.351868E+09 | 4790.16 | 03-MAY-18:01 | 4790.16 | 0.43 |
June | 0.00 | 0.00 | 0.151001E+10 | 0.843407E+09 | 5486.21 | 18-JUN-08:21 | 2979.81 | 0.66 |
July | 0.00 | 0.00 | 0.208287E+10 | 0.120092E+10 | 5512.28 | 16-JUL-08:21 | 2878.57 | 0.71 |
August | 0.00 | 0.00 | 0.167187E+10 | 0.925621E+09 | 5454.00 | 14-AUG-08:21 | 2772.99 | 0.68 |
September | 0.00 | 0.00 | 0.651275E+09 | 0.265032E+09 | 4812.32 | 15-SEP-21:51 | 3105.45 | 0.54 |
October | 0.00 | 0.00 | 78929016.08 | 31260531.58 | 4303.21 | 01-OCT-15:01 | 3028.65 | 0.11 |
November | 0.00 | 0.00 | 3151222.75 | 1301739.47 | 3320.59 | 05-NOV-15:01 | 2448.91 | 0.01 |
December | 0.00 | 0.00 | 144335.10 | 62691.98 | 455.71 | 16-DEC-16:04 | 160.05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.692853E+10 | 0.379306E+10 | 0.28 | |||
Minimum of Months | 0.00 | 0.00 | 76983.04 | 35454.31 | 455.71 | 160.05 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.208287E+10 | 0.120092E+10 | 5512.28 | 4790.16 | 0.71 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.291301E+09 | 0.238634E+09 | 20485.55 | 06-JAN-16:01 | 20485.55 | 0.02 |
February | 0.00 | 0.00 | 0.297270E+09 | 0.257896E+09 | 20491.07 | 28-FEB-16:01 | 20491.07 | 0.01 |
March | 0.00 | 0.00 | 0.224609E+10 | 0.163849E+10 | 20491.56 | 22-MAR-15:01 | 20491.56 | 0.17 |
April | 0.00 | 0.00 | 0.283559E+10 | 0.166331E+10 | 20479.36 | 19-APR-18:01 | 20479.36 | 0.40 |
May | 0.00 | 0.00 | 0.509110E+10 | 0.282556E+10 | 21130.40 | 17-MAY-15:01 | 16454.36 | 0.63 |
June | 0.00 | 0.00 | 0.890831E+10 | 0.447554E+10 | 23100.11 | 08-JUN-08:62 | 13212.89 | 0.86 |
July | 0.00 | 0.00 | 0.127137E+11 | 0.670166E+10 | 23796.05 | 28-JUL-18:02 | 14362.21 | 0.94 |
August | 0.00 | 0.00 | 0.120829E+11 | 0.668538E+10 | 24003.33 | 14-AUG-08:61 | 14211.83 | 0.93 |
September | 0.00 | 0.00 | 0.905733E+10 | 0.498767E+10 | 23206.06 | 17-SEP-08:61 | 14843.29 | 0.87 |
October | 0.00 | 0.00 | 0.412370E+10 | 0.230223E+10 | 20732.85 | 01-OCT-08:62 | 16169.96 | 0.52 |
November | 0.00 | 0.00 | 0.136303E+10 | 0.677272E+09 | 20012.28 | 04-NOV-15:01 | 17313.04 | 0.24 |
December | 0.00 | 0.00 | 0.319652E+09 | 0.217237E+09 | 20449.43 | 11-DEC-16:01 | 20449.43 | 0.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.593299E+11 | 0.326709E+11 | 0.47 | |||
Minimum of Months | 0.00 | 0.00 | 0.291301E+09 | 0.217237E+09 | 20012.28 | 13212.89 | 0.01 | |
Maximum of Months | 0.00 | 0.00 | 0.127137E+11 | 0.670166E+10 | 24003.33 | 20491.56 | 0.94 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 71159.96 | 201281.64 | 31-JAN-09:05 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 74723.29 | 238326.29 | 06-FEB-09:06 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 37223.78 | 156741.90 | 06-MAR-19:03 |
April | 0.00 | 0.00 | 01-APR-00:10 | 24091.02 | 140584.62 | 02-APR-15:04 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 23258.58 | 122933.10 | 11-MAY-15:05 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 7541.01 | 107075.77 | 13-JUN-08:05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1136.55 | 47513.01 | 13-JUL-04:00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 2430.84 | 59651.60 | 01-AUG-06:00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 13751.09 | 111858.23 | 30-SEP-06:30 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 30063.74 | 138937.15 | 19-OCT-08:62 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27216.56 | 167513.21 | 12-NOV-19:03 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 63056.02 | 218600.88 | 11-DEC-09:06 |
Annual Sum or Average | 0.00 | 31091.66 | ||||
Minimum of Months | 0.00 | 0.00 | 1136.55 | 47513.01 | ||
Maximum of Months | 0.00 | 0.00 | 74723.29 | 238326.29 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 360.28 | 38961.39 | 01-JAN-09:02 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 392.93 | 34001.73 | 19-FEB-09:02 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 12039.25 | 346630.20 | 15-MAR-15:03 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 16560.62 | 237624.06 | 08-APR-15:03 | 0.00 | 0.00 | 01-APR-00:10 |
May | 55147.16 | 369971.93 | 10-MAY-15:03 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 162997.60 | 595292.51 | 27-JUN-20:10 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 268764.75 | 630698.27 | 21-JUL-21:52 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 207653.25 | 567325.30 | 14-AUG-18:03 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 115636.50 | 553178.42 | 15-SEP-21:53 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 25020.93 | 331075.56 | 11-OCT-15:03 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 7415.89 | 190821.63 | 04-NOV-15:01 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 429.30 | 38494.26 | 01-DEC-19:02 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 73263.51 | 0.00 | ||||
Minimum of Months | 360.28 | 34001.73 | 0.00 | 0.00 | ||
Maximum of Months | 268764.75 | 630698.27 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 28628.22 | 60520.96 | 31-JAN-07:20 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 29043.15 | 60735.37 | 15-FEB-07:30 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 28672.74 | 60540.88 | 01-MAR-07:40 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27539.38 | 58680.09 | 03-APR-06:30 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 25989.30 | 55945.72 | 01-MAY-06:40 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 24428.32 | 52480.17 | 01-JUN-06:17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 23243.43 | 49402.00 | 03-JUL-06:20 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 22822.94 | 47806.08 | 01-AUG-06:15 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 23216.71 | 49337.91 | 29-SEP-06:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 24344.02 | 52389.51 | 31-OCT-06:40 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 25903.26 | 55744.89 | 30-NOV-07:40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 27465.23 | 58611.51 | 29-DEC-07:20 |
Annual Sum or Average | 0.00 | 25923.24 | ||||
Minimum of Months | 0.00 | 0.00 | 22822.94 | 47806.08 | ||
Maximum of Months | 0.00 | 0.00 | 29043.15 | 60735.37 |
Report: FanReportMonthly
For: FLR_3_DOAS FAN
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.271000E+10 | 0.71 | 1299.30 | 02-JAN-09:05 | 0.90 |
February | 0.244774E+10 | 0.71 | 1299.30 | 04-FEB-19:06 | 0.90 |
March | 0.271000E+10 | 0.71 | 1299.30 | 01-MAR-16:09 | 0.90 |
April | 0.262258E+10 | 0.71 | 1299.30 | 02-APR-15:10 | 0.90 |
May | 0.271000E+10 | 0.71 | 1299.30 | 01-MAY-15:50 | 0.90 |
June | 0.262258E+10 | 0.71 | 1299.30 | 01-JUN-15:05 | 0.89 |
July | 0.271000E+10 | 0.71 | 1299.30 | 01-JUL-08:15 | 0.89 |
August | 0.271000E+10 | 0.71 | 1299.30 | 05-AUG-08:04 | 0.89 |
September | 0.262258E+10 | 0.71 | 1299.30 | 01-SEP-16:05 | 0.90 |
October | 0.271000E+10 | 0.71 | 1299.30 | 02-OCT-15:23 | 0.90 |
November | 0.262258E+10 | 0.71 | 1299.30 | 02-NOV-08:62 | 0.90 |
December | 0.271000E+10 | 0.71 | 1299.30 | 03-DEC-19:05 | 0.90 |
Annual Sum or Average | 0.319080E+11 | 0.71 | |||
Minimum of Months | 0.244774E+10 | 0.71 | 1299.30 | 0.89 | |
Maximum of Months | 0.271000E+10 | 0.71 | 1299.30 | 0.90 |
Report: FanReportMonthly
For: VAV WITH REHEAT FAN
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.324077E+11 | 0.80 | 17619.41 | 17-JAN-19:50 | 0.99 |
February | 0.292876E+11 | 0.80 | 17921.75 | 22-FEB-21:10 | 1.00 |
March | 0.338101E+11 | 0.82 | 24152.51 | 15-MAR-21:10 | 1.19 |
April | 0.335274E+11 | 0.83 | 20966.92 | 07-APR-21:10 | 1.10 |
May | 0.360461E+11 | 0.85 | 24305.75 | 23-MAY-21:10 | 1.20 |
June | 0.366684E+11 | 0.87 | 26557.66 | 29-JUN-21:10 | 1.25 |
July | 0.390930E+11 | 0.88 | 27665.84 | 21-JUL-21:10 | 1.29 |
August | 0.390628E+11 | 0.88 | 28649.36 | 11-AUG-21:10 | 1.32 |
September | 0.363441E+11 | 0.86 | 29197.73 | 21-SEP-21:10 | 1.33 |
October | 0.357669E+11 | 0.84 | 26308.18 | 11-OCT-21:10 | 1.26 |
November | 0.334240E+11 | 0.83 | 20523.59 | 16-NOV-22:10 | 1.08 |
December | 0.327433E+11 | 0.81 | 19216.09 | 01-DEC-22:10 | 1.04 |
Annual Sum or Average | 0.418182E+12 | 0.84 | |||
Minimum of Months | 0.292876E+11 | 0.80 | 17619.41 | 0.99 | |
Maximum of Months | 0.390930E+11 | 0.88 | 29197.73 | 1.33 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205205E+09 | 0.27 | 76.61 | 01-JAN-00:10 | 0.27 |
February | 0.185347E+09 | 0.27 | 76.61 | 01-FEB-00:03 | 0.27 |
March | 0.205205E+09 | 0.27 | 76.61 | 01-MAR-00:03 | 0.27 |
April | 0.198586E+09 | 0.27 | 76.61 | 01-APR-00:10 | 0.27 |
May | 0.205205E+09 | 0.27 | 76.61 | 01-MAY-00:05 | 0.27 |
June | 0.198586E+09 | 0.27 | 76.61 | 01-JUN-00:05 | 0.27 |
July | 0.205205E+09 | 0.27 | 76.61 | 01-JUL-00:10 | 0.27 |
August | 0.205205E+09 | 0.27 | 76.61 | 01-AUG-00:05 | 0.27 |
September | 0.198586E+09 | 0.27 | 76.61 | 01-SEP-00:05 | 0.27 |
October | 0.205205E+09 | 0.27 | 76.61 | 01-OCT-00:10 | 0.27 |
November | 0.198586E+09 | 0.27 | 76.61 | 01-NOV-00:05 | 0.27 |
December | 0.205205E+09 | 0.27 | 76.61 | 01-DEC-00:03 | 0.27 |
Annual Sum or Average | 0.241613E+10 | 0.27 | |||
Minimum of Months | 0.185347E+09 | 0.27 | 76.61 | 0.27 | |
Maximum of Months | 0.205205E+09 | 0.27 | 76.61 | 0.27 |
Report: FanReportMonthly
For: LOBBY_FLR_1 EXHAUST FAN
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:03 | -0.0 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | -0.0 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | -0.0 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 EXHAUST FAN
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 EXHAUST FAN
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116283E+10 | 0.19 | 612.92 | 01-JAN-07:05 | 0.27 |
February | 0.105030E+10 | 0.19 | 612.92 | 01-FEB-07:05 | 0.27 |
March | 0.116283E+10 | 0.19 | 612.92 | 01-MAR-07:05 | 0.27 |
April | 0.112532E+10 | 0.19 | 612.92 | 01-APR-06:05 | 0.27 |
May | 0.116283E+10 | 0.19 | 612.92 | 01-MAY-06:05 | 0.27 |
June | 0.112532E+10 | 0.19 | 612.92 | 01-JUN-06:05 | 0.27 |
July | 0.116283E+10 | 0.19 | 612.92 | 01-JUL-06:10 | 0.27 |
August | 0.116283E+10 | 0.19 | 612.92 | 01-AUG-06:05 | 0.27 |
September | 0.112532E+10 | 0.19 | 612.92 | 01-SEP-06:05 | 0.27 |
October | 0.116283E+10 | 0.19 | 612.92 | 01-OCT-06:10 | 0.27 |
November | 0.112532E+10 | 0.19 | 612.92 | 01-NOV-06:05 | 0.27 |
December | 0.116283E+10 | 0.19 | 612.92 | 01-DEC-07:05 | 0.27 |
Annual Sum or Average | 0.136914E+11 | 0.19 | |||
Minimum of Months | 0.105030E+10 | 0.19 | 612.92 | 0.27 | |
Maximum of Months | 0.116283E+10 | 0.19 | 612.92 | 0.27 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.435640E+09 | 0.48 | 809.33 | 01-JAN-09:02 | 0.59 |
February | 0.389967E+09 | 0.47 | 809.33 | 01-FEB-09:02 | 0.59 |
March | 0.234076E+09 | 0.44 | 809.33 | 01-MAR-09:02 | 0.59 |
April | 0.176054E+09 | 0.46 | 809.33 | 02-APR-15:01 | 0.59 |
May | 0.212687E+09 | 0.50 | 809.33 | 01-MAY-15:01 | 0.59 |
June | 0.354821E+09 | 0.54 | 809.33 | 01-JUN-08:62 | 0.59 |
July | 0.425195E+09 | 0.56 | 809.33 | 01-JUL-08:61 | 0.59 |
August | 0.388195E+09 | 0.55 | 809.33 | 01-AUG-08:62 | 0.59 |
September | 0.248658E+09 | 0.52 | 809.33 | 01-SEP-15:01 | 0.59 |
October | 0.159087E+09 | 0.45 | 809.33 | 01-OCT-08:62 | 0.58 |
November | 0.215335E+09 | 0.42 | 809.33 | 01-NOV-15:01 | 0.59 |
December | 0.434230E+09 | 0.49 | 809.33 | 01-DEC-09:02 | 0.59 |
Annual Sum or Average | 0.367395E+10 | 0.49 | |||
Minimum of Months | 0.159087E+09 | 0.42 | 809.33 | 0.58 | |
Maximum of Months | 0.435640E+09 | 0.56 | 809.33 | 0.59 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.494474E+09 | 0.53 | 783.98 | 01-JAN-09:02 | 0.59 |
February | 0.433318E+09 | 0.51 | 783.98 | 01-FEB-09:02 | 0.59 |
March | 0.253827E+09 | 0.42 | 783.98 | 01-MAR-09:02 | 0.59 |
April | 0.159682E+09 | 0.42 | 783.98 | 02-APR-15:01 | 0.59 |
May | 0.139940E+09 | 0.40 | 783.98 | 01-MAY-15:01 | 0.59 |
June | 0.249642E+09 | 0.39 | 783.98 | 01-JUN-08:51 | 0.58 |
July | 0.333493E+09 | 0.41 | 783.98 | 01-JUL-08:51 | 0.58 |
August | 0.277764E+09 | 0.40 | 783.98 | 01-AUG-08:51 | 0.59 |
September | 0.133090E+09 | 0.37 | 783.98 | 01-SEP-15:01 | 0.59 |
October | 0.140320E+09 | 0.39 | 783.98 | 01-OCT-08:62 | 0.58 |
November | 0.237971E+09 | 0.41 | 783.98 | 02-NOV-08:62 | 0.59 |
December | 0.492869E+09 | 0.51 | 783.98 | 01-DEC-09:02 | 0.59 |
Annual Sum or Average | 0.334639E+10 | 0.43 | |||
Minimum of Months | 0.133090E+09 | 0.37 | 783.98 | 0.58 | |
Maximum of Months | 0.494474E+09 | 0.53 | 783.98 | 0.59 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.138663E+09 | 0.07 | 968.31 | 04-JAN-05:00 | 0.59 |
February | 0.164454E+09 | 0.08 | 1149.95 | 07-FEB-05:00 | 0.59 |
March | 0.136837E+09 | 0.09 | 1259.26 | 15-MAR-13:30 | 0.59 |
April | 0.412195E+09 | 0.23 | 1032.71 | 22-APR-13:00 | 0.59 |
May | 0.872303E+09 | 0.44 | 961.45 | 14-MAY-13:40 | 0.59 |
June | 0.124455E+10 | 0.56 | 1072.93 | 12-JUN-13:10 | 0.59 |
July | 0.160059E+10 | 0.59 | 1206.18 | 21-JUL-13:30 | 0.59 |
August | 0.160903E+10 | 0.58 | 1367.22 | 18-AUG-13:30 | 0.59 |
September | 0.134101E+10 | 0.53 | 2394.79 | 21-SEP-12:50 | 0.59 |
October | 0.679745E+09 | 0.32 | 2474.11 | 31-OCT-13:40 | 0.59 |
November | 0.144414E+09 | 0.10 | 1089.64 | 01-NOV-11:40 | 0.59 |
December | 27338053.94 | 0.02 | 503.47 | 10-DEC-06:00 | 0.59 |
Annual Sum or Average | 0.837113E+10 | 0.30 | |||
Minimum of Months | 27338053.94 | 0.02 | 503.47 | 0.59 | |
Maximum of Months | 0.160903E+10 | 0.59 | 2474.11 | 0.59 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.179420E+10 | 0.42 | 4285.15 | 01-JAN-16:02 | 0.59 |
February | 0.161428E+10 | 0.42 | 4285.15 | 01-FEB-09:02 | 0.59 |
March | 0.111874E+10 | 0.41 | 4285.15 | 01-MAR-09:02 | 0.59 |
April | 0.723972E+09 | 0.40 | 4285.15 | 01-APR-08:62 | 0.59 |
May | 0.117441E+10 | 0.36 | 4285.15 | 01-MAY-08:62 | 0.59 |
June | 0.177447E+10 | 0.34 | 4285.15 | 01-JUN-08:51 | 0.59 |
July | 0.229568E+10 | 0.37 | 4285.15 | 01-JUL-08:51 | 0.59 |
August | 0.192945E+10 | 0.36 | 4285.15 | 01-AUG-08:51 | 0.59 |
September | 0.118175E+10 | 0.32 | 4285.15 | 01-SEP-08:62 | 0.59 |
October | 0.698022E+09 | 0.38 | 4285.15 | 01-OCT-08:62 | 0.59 |
November | 0.699788E+09 | 0.41 | 4285.15 | 01-NOV-15:01 | 0.59 |
December | 0.167474E+10 | 0.42 | 4285.15 | 02-DEC-09:02 | 0.59 |
Annual Sum or Average | 0.166795E+11 | 0.39 | |||
Minimum of Months | 0.698022E+09 | 0.32 | 4285.15 | 0.59 | |
Maximum of Months | 0.229568E+10 | 0.42 | 4285.15 | 0.59 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.404242E+09 | 0.48 | 740.02 | 01-JAN-09:02 | 0.59 |
February | 0.362222E+09 | 0.46 | 740.02 | 01-FEB-09:02 | 0.59 |
March | 0.219320E+09 | 0.43 | 740.02 | 01-MAR-09:02 | 0.59 |
April | 0.172865E+09 | 0.47 | 740.02 | 01-APR-08:62 | 0.59 |
May | 0.205061E+09 | 0.52 | 740.02 | 01-MAY-08:62 | 0.59 |
June | 0.323387E+09 | 0.56 | 740.02 | 01-JUN-08:62 | 0.59 |
July | 0.413241E+09 | 0.57 | 740.02 | 01-JUL-08:61 | 0.59 |
August | 0.373728E+09 | 0.56 | 740.02 | 01-AUG-08:62 | 0.59 |
September | 0.245856E+09 | 0.54 | 740.02 | 01-SEP-08:62 | 0.58 |
October | 0.154373E+09 | 0.46 | 740.02 | 01-OCT-08:62 | 0.58 |
November | 0.205325E+09 | 0.42 | 740.02 | 01-NOV-15:01 | 0.59 |
December | 0.424475E+09 | 0.49 | 740.02 | 01-DEC-16:02 | 0.59 |
Annual Sum or Average | 0.350409E+10 | 0.50 | |||
Minimum of Months | 0.154373E+09 | 0.42 | 740.02 | 0.58 | |
Maximum of Months | 0.424475E+09 | 0.57 | 740.02 | 0.59 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.466183E+09 | 0.52 | 717.50 | 01-JAN-09:02 | 0.59 |
February | 0.407614E+09 | 0.50 | 717.50 | 01-FEB-09:02 | 0.59 |
March | 0.241807E+09 | 0.42 | 717.50 | 01-MAR-16:01 | 0.59 |
April | 0.153031E+09 | 0.43 | 717.50 | 01-APR-08:62 | 0.59 |
May | 0.151537E+09 | 0.43 | 717.50 | 01-MAY-08:62 | 0.59 |
June | 0.246956E+09 | 0.41 | 717.50 | 01-JUN-08:51 | 0.58 |
July | 0.327769E+09 | 0.42 | 717.50 | 01-JUL-08:51 | 0.58 |
August | 0.272394E+09 | 0.41 | 717.50 | 01-AUG-08:51 | 0.59 |
September | 0.149101E+09 | 0.40 | 717.50 | 01-SEP-08:62 | 0.59 |
October | 0.130863E+09 | 0.39 | 717.50 | 01-OCT-08:62 | 0.58 |
November | 0.222230E+09 | 0.42 | 717.50 | 02-NOV-08:62 | 0.59 |
December | 0.477945E+09 | 0.52 | 717.50 | 01-DEC-16:02 | 0.59 |
Annual Sum or Average | 0.324743E+10 | 0.44 | |||
Minimum of Months | 0.130863E+09 | 0.39 | 717.50 | 0.58 | |
Maximum of Months | 0.477945E+09 | 0.52 | 717.50 | 0.59 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.146284E+09 | 0.52 | 211.07 | 01-JAN-09:02 | 0.59 |
February | 0.127736E+09 | 0.51 | 211.07 | 01-FEB-09:02 | 0.59 |
March | 72187156.28 | 0.44 | 211.07 | 01-MAR-09:02 | 0.59 |
April | 54385382.60 | 0.46 | 211.07 | 01-APR-08:62 | 0.59 |
May | 58077819.20 | 0.50 | 211.07 | 01-MAY-15:01 | 0.59 |
June | 91139109.89 | 0.54 | 211.07 | 01-JUN-08:62 | 0.58 |
July | 0.109980E+09 | 0.55 | 211.07 | 01-JUL-08:61 | 0.58 |
August | 99047929.81 | 0.55 | 211.07 | 01-AUG-08:62 | 0.59 |
September | 61364459.52 | 0.52 | 211.07 | 01-SEP-15:01 | 0.59 |
October | 48871148.89 | 0.45 | 211.07 | 01-OCT-08:62 | 0.58 |
November | 68782388.83 | 0.44 | 211.07 | 02-NOV-08:62 | 0.59 |
December | 0.145263E+09 | 0.52 | 211.07 | 01-DEC-09:02 | 0.59 |
Annual Sum or Average | 0.108312E+10 | 0.50 | |||
Minimum of Months | 48871148.89 | 0.44 | 211.07 | 0.58 | |
Maximum of Months | 0.146284E+09 | 0.55 | 211.07 | 0.59 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.169698E+09 | 0.56 | 203.93 | 01-JAN-09:02 | 0.59 |
February | 0.145285E+09 | 0.55 | 203.93 | 01-FEB-09:02 | 0.59 |
March | 82006693.67 | 0.45 | 203.93 | 01-MAR-09:02 | 0.59 |
April | 50310780.84 | 0.43 | 203.93 | 01-APR-08:62 | 0.59 |
May | 39189136.99 | 0.41 | 203.93 | 01-MAY-15:01 | 0.59 |
June | 66263166.83 | 0.40 | 203.93 | 01-JUN-08:51 | 0.58 |
July | 88857620.36 | 0.42 | 203.93 | 01-JUL-08:51 | 0.58 |
August | 72390847.20 | 0.40 | 203.93 | 01-AUG-08:51 | 0.59 |
September | 32410629.11 | 0.37 | 203.93 | 01-SEP-15:01 | 0.59 |
October | 45347694.04 | 0.39 | 203.93 | 01-OCT-15:01 | 0.58 |
November | 75407754.91 | 0.44 | 203.93 | 01-NOV-08:62 | 0.59 |
December | 0.159319E+09 | 0.55 | 203.93 | 01-DEC-09:02 | 0.59 |
Annual Sum or Average | 0.102649E+10 | 0.45 | |||
Minimum of Months | 32410629.11 | 0.37 | 203.93 | 0.58 | |
Maximum of Months | 0.169698E+09 | 0.56 | 203.93 | 0.59 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.464117E+09 | 0.46 | 993.30 | 01-JAN-09:02 | 0.59 |
February | 0.421579E+09 | 0.44 | 993.30 | 01-FEB-09:02 | 0.59 |
March | 0.292329E+09 | 0.47 | 993.30 | 01-MAR-16:01 | 0.59 |
April | 0.240622E+09 | 0.48 | 993.30 | 01-APR-15:01 | 0.59 |
May | 0.259844E+09 | 0.51 | 993.30 | 01-MAY-15:01 | 0.59 |
June | 0.372669E+09 | 0.53 | 993.30 | 01-JUN-08:62 | 0.59 |
July | 0.504901E+09 | 0.55 | 993.30 | 01-JUL-08:61 | 0.58 |
August | 0.496091E+09 | 0.55 | 993.30 | 01-AUG-08:62 | 0.59 |
September | 0.391194E+09 | 0.53 | 993.30 | 01-SEP-08:62 | 0.59 |
October | 0.268801E+09 | 0.48 | 993.30 | 01-OCT-08:62 | 0.58 |
November | 0.259732E+09 | 0.46 | 993.30 | 01-NOV-15:01 | 0.59 |
December | 0.475849E+09 | 0.47 | 993.30 | 01-DEC-16:02 | 0.59 |
Annual Sum or Average | 0.444773E+10 | 0.49 | |||
Minimum of Months | 0.240622E+09 | 0.44 | 993.30 | 0.58 | |
Maximum of Months | 0.504901E+09 | 0.55 | 993.30 | 0.59 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.142791E+10 | 0.128512E+10 | 961.86 | 31-JAN-09:05 | 865.67 | 865.67 | 32.51 | 1.75 |
February | 0.131515E+10 | 0.118363E+10 | 1048.26 | 06-FEB-09:13 | 943.43 | 943.43 | 35.19 | 2.25 |
March | 0.827989E+09 | 0.745190E+09 | 900.50 | 07-MAR-07:10 | 810.45 | 810.45 | 35.71 | 1.51 |
April | 0.505104E+09 | 0.454593E+09 | 827.87 | 29-APR-08:06 | 745.08 | 745.08 | 36.65 | 1.29 |
May | 0.407506E+09 | 0.366755E+09 | 726.65 | 11-MAY-15:05 | 653.98 | 653.98 | 31.71 | 1.04 |
June | 0.124924E+09 | 0.112432E+09 | 688.67 | 06-JUN-06:05 | 619.80 | 619.80 | 37.79 | 0.96 |
July | 19503689.34 | 17553320.41 | 301.75 | 13-JUL-05:00 | 271.58 | 271.58 | 27.01 | 0.34 |
August | 41823017.94 | 37640716.14 | 378.94 | 01-AUG-06:00 | 341.05 | 341.05 | 27.94 | 0.45 |
September | 0.230365E+09 | 0.207329E+09 | 740.79 | 30-SEP-06:05 | 666.71 | 666.71 | 42.95 | 1.07 |
October | 0.600938E+09 | 0.540844E+09 | 862.98 | 25-OCT-08:04 | 776.68 | 776.68 | 38.29 | 1.39 |
November | 0.653628E+09 | 0.588265E+09 | 882.99 | 06-NOV-09:04 | 794.69 | 794.69 | 33.06 | 1.45 |
December | 0.130315E+10 | 0.117284E+10 | 1003.03 | 11-DEC-09:04 | 902.73 | 902.73 | 33.33 | 1.96 |
Annual Sum or Average | 0.745799E+10 | 0.671219E+10 | ||||||
Minimum of Months | 19503689.34 | 17553320.41 | 301.75 | 271.58 | 271.58 | 27.01 | 0.34 | |
Maximum of Months | 0.142791E+10 | 0.128512E+10 | 1048.26 | 943.43 | 943.43 | 42.95 | 2.25 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 126388.40 | 113749.56 | 17.77 | 15-JAN-09:02 | 16.00 | 16.00 | 6.72 | 2.00 |
February | 145130.94 | 130617.84 | 17.77 | 20-FEB-09:02 | 16.00 | 16.00 | 6.72 | 2.00 |
March | 17252940.99 | 15527646.89 | 400.29 | 15-MAR-15:01 | 360.26 | 360.26 | 6.72 | 9.83 |
April | 19459006.32 | 17513105.69 | 262.36 | 08-APR-15:01 | 236.12 | 236.12 | 6.72 | 8.11 |
May | 81305680.64 | 73175112.57 | 395.73 | 13-MAY-15:01 | 356.16 | 356.16 | 6.72 | 9.78 |
June | 0.339140E+09 | 0.305226E+09 | 1062.61 | 17-JUN-19:00 | 956.35 | 956.35 | 6.72 | 15.02 |
July | 0.680045E+09 | 0.612040E+09 | 1281.39 | 21-JUL-20:00 | 1153.25 | 1153.25 | 6.72 | 16.25 |
August | 0.501683E+09 | 0.451515E+09 | 982.36 | 14-AUG-18:03 | 884.13 | 884.13 | 6.72 | 14.53 |
September | 0.218443E+09 | 0.196599E+09 | 711.95 | 15-SEP-21:53 | 640.76 | 640.76 | 6.72 | 12.67 |
October | 35004821.39 | 31504339.25 | 468.70 | 11-OCT-15:01 | 421.83 | 421.83 | 6.72 | 10.55 |
November | 6429655.33 | 5786689.80 | 136.96 | 04-NOV-15:01 | 123.26 | 123.26 | 6.72 | 5.96 |
December | 174139.74 | 156725.77 | 22.48 | 17-DEC-09:02 | 20.24 | 20.24 | 6.72 | 2.30 |
Annual Sum or Average | 0.189921E+10 | 0.170929E+10 | ||||||
Minimum of Months | 126388.40 | 113749.56 | 17.77 | 16.00 | 16.00 | 6.72 | 2.00 | |
Maximum of Months | 0.680045E+09 | 0.612040E+09 | 1281.39 | 1153.25 | 1153.25 | 6.72 | 16.25 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.594639E+09 | 0.535175E+09 | 3020.29 | 01-JAN-09:02 | 2718.26 | 2718.26 | 7.05 | 26.72 |
February | 0.524655E+09 | 0.472189E+09 | 3020.29 | 01-FEB-09:03 | 2718.26 | 2718.26 | 6.75 | 26.72 |
March | 0.365990E+10 | 0.329391E+10 | 3020.29 | 01-MAR-08:00 | 2718.26 | 2718.26 | 6.73 | 26.72 |
April | 0.558962E+10 | 0.503066E+10 | 3020.29 | 01-APR-00:10 | 2718.26 | 2718.26 | 6.73 | 26.72 |
May | 0.798592E+10 | 0.718733E+10 | 3020.29 | 01-MAY-00:05 | 2718.26 | 2718.26 | 6.79 | 26.72 |
June | 0.782860E+10 | 0.704574E+10 | 3020.29 | 01-JUN-00:05 | 2718.26 | 2718.26 | 7.47 | 26.72 |
July | 0.808955E+10 | 0.728059E+10 | 3020.29 | 01-JUL-00:10 | 2718.26 | 2718.26 | 7.53 | 26.72 |
August | 0.808955E+10 | 0.728059E+10 | 3020.29 | 01-AUG-00:05 | 2718.26 | 2718.26 | 8.27 | 26.72 |
September | 0.776426E+10 | 0.698784E+10 | 3020.29 | 01-SEP-00:05 | 2718.26 | 2718.26 | 6.92 | 26.72 |
October | 0.636094E+10 | 0.572485E+10 | 3020.29 | 01-OCT-00:10 | 2718.26 | 2718.26 | 6.84 | 26.72 |
November | 0.337213E+10 | 0.303491E+10 | 3020.29 | 01-NOV-00:05 | 2718.26 | 2718.26 | 6.75 | 26.72 |
December | 0.654769E+09 | 0.589292E+09 | 3020.29 | 01-DEC-06:15 | 2718.26 | 2718.26 | 6.74 | 26.72 |
Annual Sum or Average | 0.605145E+11 | 0.544631E+11 | ||||||
Minimum of Months | 0.524655E+09 | 0.472189E+09 | 3020.29 | 2718.26 | 2718.26 | 6.73 | 26.72 | |
Maximum of Months | 0.808955E+10 | 0.728059E+10 | 3020.29 | 2718.26 | 2718.26 | 8.27 | 26.72 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:10 | 14.37 | 14.37 | 48.33 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:03 | 14.37 | 14.37 | 48.62 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:03 | 14.37 | 14.37 | 48.62 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 52.02 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:05 | 14.37 | 14.37 | 52.17 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:05 | 14.37 | 14.37 | 52.66 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 53.29 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:05 | 14.37 | 14.37 | 53.32 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:05 | 14.37 | 14.37 | 53.32 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:10 | 14.37 | 14.37 | 52.49 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:05 | 14.37 | 14.37 | 52.67 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:03 | 14.37 | 14.37 | 49.51 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 48.33 | 0.37 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 53.32 | 0.37 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 40.57 | 60.00 | 71159.96 | 201281.64 | 31-JAN-09:05 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 38.63 | 60.00 | 74723.29 | 238326.29 | 06-FEB-09:06 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 37.59 | 60.00 | 37223.78 | 156741.90 | 06-MAR-19:03 |
April | 0.00 | 0.00 | 01-APR-00:10 | 50.14 | 60.00 | 24091.02 | 140584.62 | 02-APR-15:04 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 42.41 | 60.00 | 23258.58 | 122933.10 | 11-MAY-15:05 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.97 | 25.97 | 7541.01 | 107075.77 | 13-JUN-08:05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.46 | 32.46 | 1136.55 | 47513.01 | 13-JUL-04:00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 41.02 | 41.02 | 2430.84 | 59651.60 | 01-AUG-06:00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.21 | 60.00 | 13751.09 | 111858.23 | 30-SEP-06:30 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 23.82 | 60.00 | 30063.74 | 138937.15 | 19-OCT-08:62 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 47.35 | 60.00 | 27216.56 | 167513.21 | 12-NOV-19:03 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 45.93 | 60.00 | 63056.02 | 218600.88 | 11-DEC-09:06 |
Annual Sum or Average | 0.00 | 31091.66 | ||||||
Minimum of Months | 0.00 | 0.00 | 22.21 | 25.97 | 1136.55 | 47513.01 | ||
Maximum of Months | 0.00 | 0.00 | 50.14 | 60.00 | 74723.29 | 238326.29 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 360.28 | 38961.39 | 01-JAN-09:02 | 7.05 | 6.70 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 392.93 | 34001.73 | 19-FEB-09:02 | 7.00 | 6.70 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 12039.25 | 346630.20 | 15-MAR-15:03 | 9.80 | 6.70 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 16560.62 | 237624.06 | 08-APR-15:03 | 8.82 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 55147.16 | 369971.93 | 10-MAY-15:03 | 10.00 | 6.70 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 162997.60 | 595292.51 | 27-JUN-20:10 | 12.02 | 6.70 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 268764.75 | 630698.27 | 21-JUL-21:52 | 12.34 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 207653.25 | 567325.30 | 14-AUG-18:03 | 11.77 | 6.70 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 115636.50 | 553178.42 | 15-SEP-21:53 | 11.64 | 6.70 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 25020.93 | 331075.56 | 11-OCT-15:03 | 9.66 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 7415.89 | 190821.63 | 04-NOV-15:01 | 8.40 | 6.70 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 429.30 | 38494.26 | 01-DEC-19:02 | 7.04 | 6.70 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 73263.51 | 0.00 | ||||||
Minimum of Months | 360.28 | 34001.73 | 7.00 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 268764.75 | 630698.27 | 12.34 | 6.70 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 48.33 | 60.05 | 28628.22 | 60520.96 | 31-JAN-07:20 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 48.62 | 60.05 | 29043.15 | 60735.37 | 15-FEB-07:30 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 48.62 | 60.05 | 28672.74 | 60540.88 | 01-MAR-07:40 |
April | 0.00 | 0.00 | 01-APR-00:10 | 52.02 | 60.05 | 27539.38 | 58680.09 | 03-APR-06:30 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 52.17 | 60.05 | 25989.30 | 55945.72 | 01-MAY-06:40 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 52.66 | 60.05 | 24428.32 | 52480.17 | 01-JUN-06:17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 53.29 | 60.05 | 23243.43 | 49402.00 | 03-JUL-06:20 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 53.32 | 60.05 | 22822.94 | 47806.08 | 01-AUG-06:15 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 53.32 | 60.05 | 23216.71 | 49337.91 | 29-SEP-06:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 52.49 | 60.05 | 24344.02 | 52389.51 | 31-OCT-06:40 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 52.67 | 60.05 | 25903.26 | 55744.89 | 30-NOV-07:40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 49.51 | 60.05 | 27465.23 | 58611.51 | 29-DEC-07:20 |
Annual Sum or Average | 0.00 | 25923.24 | ||||||
Minimum of Months | 0.00 | 0.00 | 48.33 | 60.05 | 22822.94 | 47806.08 | ||
Maximum of Months | 0.00 | 0.00 | 53.32 | 60.05 | 29043.15 | 60735.37 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.396169E+10 | 0.00 | 0.00 | 0.271000E+10 | 0.00 | 0.00 |
February | 0.418659E+10 | 0.00 | 0.00 | 0.244774E+10 | 0.00 | 0.00 |
March | 0.161210E+10 | 0.00 | 0.105566E+10 | 0.271000E+10 | 0.00 | 0.00 |
April | 80335264.71 | 0.00 | 0.441673E+09 | 0.262258E+10 | 0.00 | 0.00 |
May | 9601.52 | 0.00 | 0.484402E+10 | 0.271000E+10 | 0.00 | 0.00 |
June | 13260.88 | 0.00 | 0.221055E+11 | 0.262258E+10 | 0.00 | 0.00 |
July | 14248.98 | 0.00 | 0.401031E+11 | 0.271000E+10 | 0.00 | 0.00 |
August | 18258.21 | 0.00 | 0.294595E+11 | 0.271000E+10 | 0.00 | 0.00 |
September | 17725.41 | 0.00 | 0.146686E+11 | 0.262258E+10 | 0.00 | 0.00 |
October | 15771371.99 | 0.00 | 0.151414E+10 | 0.271000E+10 | 0.00 | 0.00 |
November | 63736683.96 | 0.00 | 0.566791E+09 | 0.262258E+10 | 0.00 | 0.00 |
December | 0.328049E+10 | 0.00 | 849913.39 | 0.271000E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.132008E+11 | 0.00 | 0.114760E+12 | 0.319080E+11 | 0.00 | 0.00 |
Minimum of Months | 9601.52 | 0.00 | 0.00 | 0.244774E+10 | 0.00 | 0.00 |
Maximum of Months | 0.418659E+10 | 0.00 | 0.401031E+11 | 0.271000E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.125428E+12 | 0.00 | 338043.09 | 0.324077E+11 | 0.00 | 0.00 |
February | 0.122073E+12 | 0.00 | 0.00 | 0.292876E+11 | 0.00 | 0.00 |
March | 0.725607E+11 | 0.00 | 0.145278E+11 | 0.338101E+11 | 0.00 | 0.00 |
April | 0.553465E+11 | 0.00 | 0.839677E+10 | 0.335274E+11 | 0.00 | 0.00 |
May | 0.618867E+11 | 0.00 | 0.684660E+11 | 0.360461E+11 | 0.00 | 0.00 |
June | 0.195742E+11 | 0.00 | 0.278497E+12 | 0.366684E+11 | 0.00 | 0.00 |
July | 0.302295E+10 | 0.00 | 0.517479E+12 | 0.390930E+11 | 0.00 | 0.00 |
August | 0.651458E+10 | 0.00 | 0.379345E+12 | 0.390628E+11 | 0.00 | 0.00 |
September | 0.355105E+11 | 0.00 | 0.183876E+12 | 0.363441E+11 | 0.00 | 0.00 |
October | 0.740152E+11 | 0.00 | 0.227346E+11 | 0.357669E+11 | 0.00 | 0.00 |
November | 0.511758E+11 | 0.00 | 0.720306E+10 | 0.334240E+11 | 0.00 | 0.00 |
December | 0.108442E+12 | 0.00 | 9040451.82 | 0.327433E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.735550E+12 | 0.00 | 0.148053E+13 | 0.418182E+12 | 0.00 | 0.00 |
Minimum of Months | 0.302295E+10 | 0.00 | 0.00 | 0.292876E+11 | 0.00 | 0.00 |
Maximum of Months | 0.125428E+12 | 0.00 | 0.517479E+12 | 0.390930E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.271000E+10 | 0.00 | 0.396169E+10 | 0.654741E+11 | 88311.21 | 0.00 | 0.00 | 0.00 |
February | 0.244774E+10 | 0.00 | 0.418659E+10 | 0.608024E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.271000E+10 | 0.105566E+10 | 0.161210E+10 | 0.476263E+11 | 45307329.63 | 0.00 | 0.00 | 0.00 |
April | 0.262258E+10 | 0.441673E+09 | 80335264.71 | 0.311023E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.271000E+10 | 0.484402E+10 | 9601.52 | 0.109662E+11 | 98851611.33 | 0.00 | 0.00 | 0.00 |
June | 0.262258E+10 | 0.221055E+11 | 13260.88 | 0.304364E+10 | 0.326975E+10 | 0.00 | 0.00 | 0.00 |
July | 0.271000E+10 | 0.401031E+11 | 14248.98 | 0.283620E+09 | 0.103728E+11 | 0.00 | 0.00 | 0.00 |
August | 0.271000E+10 | 0.294595E+11 | 18258.21 | 0.702473E+09 | 0.524831E+10 | 0.00 | 0.00 | 0.00 |
September | 0.262258E+10 | 0.146686E+11 | 17725.41 | 0.479997E+10 | 0.103336E+10 | 0.00 | 0.00 | 0.00 |
October | 0.271000E+10 | 0.151414E+10 | 15771371.99 | 0.236936E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.262258E+10 | 0.566791E+09 | 63736683.96 | 0.363133E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.271000E+10 | 849913.39 | 0.328049E+10 | 0.618086E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319080E+11 | 0.114760E+12 | 0.132008E+11 | 0.346616E+12 | 0.200685E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244774E+10 | 0.00 | 9601.52 | 0.283620E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.271000E+10 | 0.401031E+11 | 0.418659E+10 | 0.654741E+11 | 0.103728E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.324077E+11 | 338043.09 | 0.125428E+12 | 0.743232E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.292876E+11 | 0.00 | 0.122073E+12 | 0.692026E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.338101E+11 | 0.145278E+11 | 0.725607E+11 | 0.523468E+12 | 87830833.85 | 0.00 | 0.00 | 0.00 |
April | 0.335274E+11 | 0.839677E+10 | 0.553465E+11 | 0.295491E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.360461E+11 | 0.684660E+11 | 0.618867E+11 | 0.411230E+11 | 0.192246E+09 | 0.00 | 0.00 | 0.00 |
June | 0.366684E+11 | 0.278497E+12 | 0.195742E+11 | 0.108021E+11 | 0.223274E+11 | 0.00 | 0.00 | 0.00 |
July | 0.390930E+11 | 0.517479E+12 | 0.302295E+10 | 0.122452E+10 | 0.702187E+11 | 0.00 | 0.00 | 0.00 |
August | 0.390628E+11 | 0.379345E+12 | 0.651458E+10 | 0.348604E+10 | 0.336154E+11 | 0.00 | 0.00 | 0.00 |
September | 0.363441E+11 | 0.183876E+12 | 0.355105E+11 | 0.988094E+10 | 0.437178E+10 | 0.00 | 0.00 | 0.00 |
October | 0.357669E+11 | 0.227346E+11 | 0.740152E+11 | 0.186564E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.334240E+11 | 0.720306E+10 | 0.511758E+11 | 0.379392E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.327433E+11 | 9040451.82 | 0.108442E+12 | 0.710591E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.418182E+12 | 0.148053E+13 | 0.735550E+12 | 0.359728E+13 | 0.130813E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.292876E+11 | 0.00 | 0.302295E+10 | 0.122452E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.390930E+11 | 0.517479E+12 | 0.125428E+12 | 0.743232E+12 | 0.702187E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.271000E+10 | 0.396169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244774E+10 | 0.418659E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.271000E+10 | 0.161210E+10 | 0.105566E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.262258E+10 | 80335264.71 | 0.441673E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.271000E+10 | 9601.52 | 0.484402E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.262258E+10 | 13260.88 | 0.221055E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.271000E+10 | 14248.98 | 0.401031E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.271000E+10 | 18258.21 | 0.294595E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.262258E+10 | 17725.41 | 0.146686E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.271000E+10 | 15771371.99 | 0.151414E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.262258E+10 | 63736683.96 | 0.566791E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.271000E+10 | 0.328049E+10 | 849913.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319080E+11 | 0.132008E+11 | 0.114760E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244774E+10 | 9601.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.271000E+10 | 0.418659E+10 | 0.401031E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.324077E+11 | 0.125428E+12 | 338043.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.292876E+11 | 0.122073E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.338101E+11 | 0.725607E+11 | 0.145278E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.335274E+11 | 0.553465E+11 | 0.839677E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.360461E+11 | 0.618867E+11 | 0.684660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.366684E+11 | 0.195742E+11 | 0.278497E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.390930E+11 | 0.302295E+10 | 0.517479E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.390628E+11 | 0.651458E+10 | 0.379345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363441E+11 | 0.355105E+11 | 0.183876E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.357669E+11 | 0.740152E+11 | 0.227346E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.334240E+11 | 0.511758E+11 | 0.720306E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.327433E+11 | 0.108442E+12 | 9040451.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.418182E+12 | 0.735550E+12 | 0.148053E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.292876E+11 | 0.302295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.390930E+11 | 0.125428E+12 | 0.517479E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.437194E+11 | 0.00 | 0.00 | 4092525.19 | 0.00 | 0.00 | 0.901225E+10 | 0.00 | 0.98 |
February | 0.453265E+11 | 0.00 | 0.00 | 526121.39 | 0.00 | 0.00 | 0.312737E+10 | 0.00 | 0.98 |
March | 0.490897E+11 | 0.00 | 0.00 | 0.00 | 3525359.25 | 0.00 | 0.00 | 0.00 | 0.97 |
April | 0.480779E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.98 |
May | 0.462693E+11 | 0.00 | 0.00 | 0.00 | 2029691.41 | 0.00 | 0.00 | 0.00 | 0.98 |
June | 0.260504E+11 | 0.00 | 0.00 | 0.00 | 0.302638E+10 | 0.00 | 0.00 | 0.00 | 0.99 |
July | 0.112427E+11 | 0.877694E+09 | 0.00 | 422363.19 | 0.901504E+10 | 0.00 | 0.568572E+09 | 0.00 | 0.99 |
August | 0.679412E+10 | 0.167857E+10 | 0.00 | 15188248.04 | 0.273873E+10 | 0.00 | 0.129343E+11 | 0.00 | 1.00 |
September | 0.495562E+10 | 0.106801E+10 | 0.00 | 40356694.26 | 0.617636E+09 | 0.00 | 0.316575E+11 | 0.00 | 1.03 |
October | 0.242283E+10 | 0.00 | 0.00 | 59583421.74 | 0.00 | 0.00 | 0.533584E+11 | 0.00 | 1.07 |
November | 0.345880E+10 | 0.00 | 0.00 | 51119023.76 | 0.00 | 0.00 | 0.467828E+11 | 0.00 | 1.06 |
December | 0.195714E+11 | 0.00 | 0.00 | 24146018.34 | 0.00 | 0.00 | 0.331923E+11 | 0.00 | 1.01 |
Annual Sum or Average | 0.306979E+12 | 0.362427E+10 | 0.00 | 0.195434E+09 | 0.154033E+11 | 0.00 | 0.190633E+12 | 0.00 | 1.00 |
Minimum of Months | 0.242283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.97 |
Maximum of Months | 0.490897E+11 | 0.167857E+10 | 0.00 | 59583421.74 | 0.901504E+10 | 0.00 | 0.533584E+11 | 0.00 | 1.07 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.297000E+10 | 0.00 | 0.00 | 39251.33 | 0.00 | 0.497287E+10 | 66072647.79 | 0.00 | 2.68 |
February | 0.287471E+10 | 0.00 | 0.00 | 54092.39 | 0.00 | 0.440326E+10 | 80758715.42 | 0.00 | 2.68 |
March | 0.606212E+10 | 190695.06 | 0.00 | 361158.85 | 345001.40 | 0.105671E+10 | 0.341454E+09 | 0.00 | 2.68 |
April | 0.678363E+10 | 0.00 | 0.00 | 323265.45 | 0.00 | 0.158165E+09 | 0.362972E+09 | 0.00 | 2.71 |
May | 0.673037E+10 | 298747.66 | 0.00 | 294791.36 | 9501.87 | 0.00 | 0.296263E+09 | 0.00 | 2.70 |
June | 0.374269E+10 | 0.195671E+09 | 0.00 | 355554.99 | 0.268500E+09 | 0.00 | 0.213486E+09 | 0.00 | 2.72 |
July | 0.161894E+10 | 0.856229E+09 | 0.00 | 479509.88 | 0.679168E+09 | 0.00 | 0.174587E+09 | 0.00 | 2.76 |
August | 0.256784E+10 | 0.401660E+09 | 0.00 | 1659935.26 | 0.289065E+09 | 0.00 | 0.411128E+09 | 0.00 | 2.80 |
September | 0.468248E+10 | 82870502.79 | 0.00 | 2153494.19 | 0.164559E+09 | 0.00 | 0.703358E+09 | 0.00 | 2.80 |
October | 0.726030E+10 | 0.00 | 0.00 | 1120321.98 | 0.00 | 27421230.49 | 0.596861E+09 | 0.00 | 2.74 |
November | 0.636157E+10 | 0.00 | 0.00 | 172732.87 | 0.00 | 0.524009E+09 | 0.257328E+09 | 0.00 | 2.70 |
December | 0.272760E+10 | 0.00 | 0.00 | 54660.56 | 0.00 | 0.501036E+10 | 68819858.13 | 0.00 | 2.69 |
Annual Sum or Average | 0.543822E+11 | 0.153692E+10 | 0.00 | 7068769.11 | 0.140165E+10 | 0.161528E+11 | 0.357309E+10 | 0.00 | 2.72 |
Minimum of Months | 0.161894E+10 | 0.00 | 0.00 | 39251.33 | 0.00 | 0.00 | 66072647.79 | 0.00 | 2.68 |
Maximum of Months | 0.726030E+10 | 0.856229E+09 | 0.00 | 2153494.19 | 0.679168E+09 | 0.501036E+10 | 0.703358E+09 | 0.00 | 2.80 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.487707E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.41 |
February | 0.448113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.41 |
March | 0.442852E+10 | 0.00 | 0.00 | 68776.78 | 326030.10 | 0.00 | 0.111709E+09 | 0.00 | 1.41 |
April | 0.416377E+10 | 0.00 | 0.00 | 87655.50 | 0.00 | 0.00 | 0.282453E+09 | 0.00 | 1.43 |
May | 0.338718E+10 | 0.00 | 0.00 | 516011.54 | 187708.67 | 0.00 | 0.893792E+09 | 0.00 | 1.43 |
June | 0.114063E+10 | 0.128799E+09 | 0.00 | 1877066.23 | 0.160755E+09 | 0.00 | 0.129667E+10 | 0.00 | 1.46 |
July | 0.207096E+09 | 0.621135E+09 | 0.00 | 1885354.56 | 0.342213E+09 | 0.00 | 0.912290E+09 | 0.00 | 1.50 |
August | 0.436591E+09 | 0.248945E+09 | 0.00 | 2683870.61 | 0.173251E+09 | 0.00 | 0.143207E+10 | 0.00 | 1.49 |
September | 0.184312E+10 | 59950434.62 | 0.00 | 1392696.38 | 90768173.14 | 0.00 | 0.143155E+10 | 0.00 | 1.45 |
October | 0.421006E+10 | 0.00 | 0.00 | 284573.30 | 0.00 | 0.00 | 0.542091E+09 | 0.00 | 1.42 |
November | 0.428282E+10 | 0.00 | 0.00 | 10379.84 | 0.00 | 0.00 | 62442338.44 | 0.00 | 1.42 |
December | 0.475397E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.42 |
Annual Sum or Average | 0.382120E+11 | 0.105883E+10 | 0.00 | 8806384.74 | 0.767501E+09 | 0.00 | 0.696507E+10 | 0.00 | 1.44 |
Minimum of Months | 0.207096E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.41 |
Maximum of Months | 0.487707E+10 | 0.621135E+09 | 0.00 | 2683870.61 | 0.342213E+09 | 0.00 | 0.143207E+10 | 0.00 | 1.50 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.246156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137479E+10 | 0.00 | 0.00 | 0.52 |
February | 0.213757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138733E+10 | 0.00 | 0.00 | 0.52 |
March | 0.335256E+10 | 0.00 | 0.00 | 0.00 | 256458.21 | 0.218551E+09 | 0.00 | 0.00 | 0.52 |
April | 0.349751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
May | 0.336594E+10 | 0.00 | 0.00 | 0.00 | 147653.33 | 0.00 | 0.00 | 0.00 | 0.53 |
June | 0.185502E+10 | 26901344.02 | 0.00 | 88595.21 | 0.194420E+09 | 0.00 | 40141035.73 | 0.00 | 0.53 |
July | 0.753767E+09 | 0.308959E+09 | 0.00 | 256049.01 | 0.434772E+09 | 0.00 | 0.105988E+09 | 0.00 | 0.54 |
August | 0.118023E+10 | 85690302.64 | 0.00 | 498763.37 | 0.235952E+09 | 0.00 | 0.247843E+09 | 0.00 | 0.54 |
September | 0.251760E+10 | 10650173.66 | 0.00 | 10127.82 | 0.105667E+09 | 0.00 | 30171498.24 | 0.00 | 0.53 |
October | 0.373556E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
November | 0.341803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
December | 0.260858E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113094E+10 | 0.00 | 0.00 | 0.53 |
Annual Sum or Average | 0.308839E+11 | 0.432201E+09 | 0.00 | 853535.42 | 0.971215E+09 | 0.411161E+10 | 0.424143E+09 | 0.00 | 0.53 |
Minimum of Months | 0.753767E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
Maximum of Months | 0.373556E+10 | 0.308959E+09 | 0.00 | 498763.37 | 0.434772E+09 | 0.138733E+10 | 0.247843E+09 | 0.00 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.569702E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171549E+10 | 0.00 | 0.00 | 0.54 |
February | 0.452280E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164739E+10 | 0.00 | 0.00 | 0.54 |
March | 0.161538E+10 | 0.00 | 0.00 | 0.00 | 152763.88 | 0.511821E+09 | 0.00 | 0.00 | 0.54 |
April | 0.207717E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6179224.73 | 0.00 | 0.00 | 0.55 |
May | 0.200498E+10 | 0.00 | 0.00 | 0.00 | 87952.33 | 0.00 | 0.00 | 0.00 | 0.55 |
June | 0.112884E+10 | 0.00 | 0.00 | 0.00 | 0.131142E+09 | 0.00 | 0.00 | 0.00 | 0.55 |
July | 0.511802E+09 | 78909941.28 | 0.00 | 179.62 | 0.350992E+09 | 0.00 | 34637.18 | 0.00 | 0.55 |
August | 0.836591E+09 | 10389492.18 | 0.00 | 7768.62 | 0.179479E+09 | 0.00 | 10741355.58 | 0.00 | 0.55 |
September | 0.151763E+10 | 0.00 | 0.00 | 0.00 | 69286506.13 | 0.00 | 0.00 | 0.00 | 0.55 |
October | 0.222515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 |
November | 0.200606E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29948600.40 | 0.00 | 0.00 | 0.54 |
December | 0.833484E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139403E+10 | 0.00 | 0.00 | 0.54 |
Annual Sum or Average | 0.157791E+11 | 89299433.46 | 0.00 | 7948.25 | 0.731140E+09 | 0.530485E+10 | 10775992.76 | 0.00 | 0.55 |
Minimum of Months | 0.452280E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 |
Maximum of Months | 0.222515E+10 | 78909941.28 | 0.00 | 7768.62 | 0.350992E+09 | 0.171549E+10 | 10741355.58 | 0.00 | 0.55 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.414818E+09 | 0.00 | 0.00 | 92965120.35 | 0.00 | 0.00 | 0.813743E+11 | 0.00 | 23.53 |
February | 0.391005E+09 | 0.00 | 0.00 | 83523804.60 | 0.00 | 0.00 | 0.746871E+11 | 0.00 | 23.56 |
March | 0.239702E+09 | 4713906.66 | 0.00 | 93168069.52 | 0.00 | 0.00 | 0.763433E+11 | 0.00 | 23.64 |
April | 0.203710E+09 | 0.00 | 0.00 | 93100496.97 | 0.00 | 0.00 | 0.748401E+11 | 0.00 | 23.84 |
May | 0.183967E+09 | 2713986.06 | 0.00 | 0.109424E+09 | 0.00 | 0.00 | 0.723700E+11 | 0.00 | 23.88 |
June | 37201330.78 | 0.477503E+10 | 0.00 | 95553106.54 | 8125795.52 | 0.00 | 0.398933E+11 | 0.00 | 23.91 |
July | 5618554.15 | 0.155502E+11 | 0.00 | 63351860.69 | 17481749.89 | 0.00 | 0.175827E+11 | 0.00 | 23.89 |
August | 12992216.37 | 0.695784E+10 | 0.00 | 90399795.91 | 18682199.83 | 0.00 | 0.298674E+11 | 0.00 | 23.95 |
September | 0.103679E+09 | 0.258602E+10 | 0.00 | 96199493.75 | 989761.69 | 0.00 | 0.542112E+11 | 0.00 | 23.89 |
October | 0.188774E+09 | 0.00 | 0.00 | 95598584.73 | 0.00 | 0.00 | 0.798099E+11 | 0.00 | 23.81 |
November | 0.224573E+09 | 0.00 | 0.00 | 90332159.02 | 0.00 | 0.00 | 0.729183E+11 | 0.00 | 23.84 |
December | 0.416809E+09 | 0.00 | 0.00 | 92229642.18 | 0.00 | 0.00 | 0.791690E+11 | 0.00 | 23.63 |
Annual Sum or Average | 0.242285E+10 | 0.298765E+11 | 0.00 | 0.109585E+10 | 45279506.93 | 0.00 | 0.753066E+12 | 0.00 | 23.78 |
Minimum of Months | 5618554.15 | 0.00 | 0.00 | 63351860.69 | 0.00 | 0.00 | 0.175827E+11 | 0.00 | 23.53 |
Maximum of Months | 0.416809E+09 | 0.155502E+11 | 0.00 | 0.109424E+09 | 18682199.83 | 0.00 | 0.813743E+11 | 0.00 | 23.95 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.316033E+11 | 0.00 | 0.00 | 518461.51 | 0.00 | 0.00 | 0.191199E+10 | 0.00 | 3.99 |
February | 0.288103E+11 | 0.00 | 0.00 | 688529.86 | 0.00 | 0.304812E+09 | 0.167877E+10 | 0.00 | 4.00 |
March | 0.207340E+11 | 2152333.32 | 0.00 | 6250833.18 | 88788.98 | 0.00 | 0.105036E+11 | 0.00 | 4.00 |
April | 0.155852E+11 | 0.00 | 0.00 | 7891714.24 | 0.00 | 0.00 | 0.149835E+11 | 0.00 | 4.04 |
May | 0.101754E+11 | 1289886.43 | 0.00 | 13008743.69 | 0.00 | 0.00 | 0.192301E+11 | 0.00 | 4.04 |
June | 0.409064E+10 | 0.157641E+10 | 0.00 | 18321508.21 | 0.367223E+09 | 0.00 | 0.125379E+11 | 0.00 | 4.09 |
July | 0.986731E+09 | 0.553732E+10 | 0.00 | 15878674.43 | 0.970098E+09 | 0.00 | 0.661556E+10 | 0.00 | 4.18 |
August | 0.214485E+10 | 0.253942E+10 | 0.00 | 25215522.12 | 0.359336E+09 | 0.00 | 0.105205E+11 | 0.00 | 4.20 |
September | 0.487475E+10 | 0.780732E+09 | 0.00 | 24757232.60 | 0.257665E+09 | 0.00 | 0.177298E+11 | 0.00 | 4.17 |
October | 0.154087E+11 | 0.00 | 0.00 | 14302783.20 | 0.00 | 0.00 | 0.175759E+11 | 0.00 | 4.09 |
November | 0.190375E+11 | 0.00 | 0.00 | 4502660.39 | 0.00 | 0.00 | 0.108623E+11 | 0.00 | 4.03 |
December | 0.303745E+11 | 0.00 | 0.00 | 796550.80 | 0.00 | 60020480.10 | 0.224276E+10 | 0.00 | 4.02 |
Annual Sum or Average | 0.183826E+12 | 0.104373E+11 | 0.00 | 0.132133E+09 | 0.195441E+10 | 0.364833E+09 | 0.126393E+12 | 0.00 | 4.07 |
Minimum of Months | 0.986731E+09 | 0.00 | 0.00 | 518461.51 | 0.00 | 0.00 | 0.167877E+10 | 0.00 | 3.99 |
Maximum of Months | 0.316033E+11 | 0.553732E+10 | 0.00 | 25215522.12 | 0.970098E+09 | 0.304812E+09 | 0.192301E+11 | 0.00 | 4.20 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.103953E+12 | 0.00 | 0.00 | 122512.95 | 0.00 | 0.00 | 0.117437E+10 | 0.00 | 1.81 |
February | 0.952493E+11 | 0.00 | 0.00 | 232286.24 | 0.00 | 0.00 | 0.134363E+10 | 0.00 | 1.81 |
March | 0.782369E+11 | 0.00 | 0.00 | 9676930.07 | 7027746.84 | 0.00 | 0.197143E+11 | 0.00 | 1.81 |
April | 0.615362E+11 | 0.00 | 0.00 | 16378703.09 | 0.00 | 0.00 | 0.343394E+11 | 0.00 | 1.83 |
May | 0.391114E+11 | 0.00 | 0.00 | 40811421.20 | 4046157.11 | 0.00 | 0.535648E+11 | 0.00 | 1.84 |
June | 0.143174E+11 | 0.370190E+10 | 0.00 | 67468371.02 | 0.252594E+10 | 0.00 | 0.391857E+11 | 0.00 | 1.90 |
July | 0.284793E+10 | 0.155541E+11 | 0.00 | 56947191.12 | 0.540723E+10 | 0.00 | 0.220890E+11 | 0.00 | 1.96 |
August | 0.600860E+10 | 0.680543E+10 | 0.00 | 78993884.75 | 0.242469E+10 | 0.00 | 0.356452E+11 | 0.00 | 1.95 |
September | 0.177949E+11 | 0.196498E+10 | 0.00 | 65387953.23 | 0.134649E+10 | 0.00 | 0.540145E+11 | 0.00 | 1.89 |
October | 0.555426E+11 | 0.00 | 0.00 | 31612135.97 | 0.00 | 0.00 | 0.473252E+11 | 0.00 | 1.84 |
November | 0.694088E+11 | 0.00 | 0.00 | 9516960.48 | 0.00 | 0.00 | 0.242551E+11 | 0.00 | 1.83 |
December | 0.100796E+12 | 0.00 | 0.00 | 249055.81 | 0.00 | 0.00 | 0.167846E+10 | 0.00 | 1.82 |
Annual Sum or Average | 0.644803E+12 | 0.280264E+11 | 0.00 | 0.377397E+09 | 0.117154E+11 | 0.00 | 0.334330E+12 | 0.00 | 1.86 |
Minimum of Months | 0.284793E+10 | 0.00 | 0.00 | 122512.95 | 0.00 | 0.00 | 0.117437E+10 | 0.00 | 1.81 |
Maximum of Months | 0.103953E+12 | 0.155541E+11 | 0.00 | 78993884.75 | 0.540723E+10 | 0.00 | 0.540145E+11 | 0.00 | 1.96 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 46086340.55 | 0.00 | 0.00 | 94321.53 | 0.00 | 0.160045E+10 | 5418897.24 | 0.00 | 0.35 |
February | 52562124.06 | 0.00 | 0.00 | 213779.61 | 0.00 | 0.144640E+10 | 19339806.26 | 0.00 | 0.35 |
March | 73363256.63 | 685924.29 | 0.00 | 2360162.85 | 0.00 | 0.111918E+10 | 0.299857E+09 | 0.00 | 0.35 |
April | 61953448.49 | 0.00 | 0.00 | 5448336.68 | 0.00 | 0.645184E+09 | 0.711454E+09 | 0.00 | 0.36 |
May | 28505399.26 | 2904377.90 | 0.00 | 12799359.88 | 0.00 | 65770860.93 | 0.113351E+10 | 0.00 | 0.36 |
June | 2479967.54 | 0.195401E+09 | 78381.30 | 12263878.31 | 361138.36 | 1539132.95 | 0.570868E+09 | 20496.05 | 0.36 |
July | 0.00 | 0.554574E+09 | 297636.47 | 5064687.53 | 0.00 | 267989.10 | 0.155211E+09 | 26747.52 | 0.36 |
August | 2050875.34 | 0.299449E+09 | 126799.80 | 9434609.91 | 207431.05 | 947789.41 | 0.337570E+09 | 9804.13 | 0.35 |
September | 8564280.47 | 0.111226E+09 | 97281.94 | 11355785.60 | 77.92 | 35326474.14 | 0.749276E+09 | 16179.88 | 0.35 |
October | 65238162.04 | 0.00 | 0.00 | 4391073.52 | 0.00 | 0.633071E+09 | 0.682938E+09 | 0.00 | 0.35 |
November | 70588789.57 | 0.00 | 0.00 | 800647.18 | 0.00 | 0.112518E+10 | 0.221020E+09 | 0.00 | 0.36 |
December | 38063529.25 | 0.00 | 0.00 | 57615.90 | 0.00 | 0.157549E+10 | 5011018.14 | 0.00 | 0.36 |
Annual Sum or Average | 0.449456E+09 | 0.116424E+10 | 600099.51 | 64284258.52 | 568647.33 | 0.824880E+10 | 0.489147E+10 | 73227.59 | 0.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 57615.90 | 0.00 | 267989.10 | 5011018.14 | 0.00 | 0.35 |
Maximum of Months | 73363256.63 | 0.554574E+09 | 297636.47 | 12799359.88 | 361138.36 | 0.160045E+10 | 0.113351E+10 | 26747.52 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 10699229.12 | 0.00 | 0.00 | 16367.78 | 0.00 | 0.163866E+10 | 2483870.39 | 0.00 | 0.35 |
February | 19231790.56 | 0.00 | 0.00 | 53214.48 | 0.00 | 0.148887E+10 | 10183335.34 | 0.00 | 0.35 |
March | 82009668.06 | 357756.36 | 0.00 | 1219529.24 | 328087.56 | 0.119551E+10 | 0.215845E+09 | 0.00 | 0.35 |
April | 0.112991E+09 | 0.00 | 0.00 | 3953370.96 | 0.00 | 0.758637E+09 | 0.548292E+09 | 0.00 | 0.36 |
May | 0.198662E+09 | 2440663.70 | 0.00 | 9629310.76 | 463373.91 | 86617675.74 | 0.945526E+09 | 0.00 | 0.36 |
June | 0.146159E+09 | 0.162833E+09 | 130333.39 | 8835517.58 | 32862147.44 | 1238808.13 | 0.430849E+09 | 12577.90 | 0.36 |
July | 47981334.19 | 0.459027E+09 | 400933.74 | 3437459.83 | 95386317.38 | 108948.80 | 0.108997E+09 | 19093.59 | 0.36 |
August | 0.103592E+09 | 0.254522E+09 | 232814.81 | 6367971.27 | 44974236.53 | 653162.05 | 0.239349E+09 | 29105.64 | 0.36 |
September | 0.157558E+09 | 83063237.19 | 136358.72 | 6866258.40 | 28111019.51 | 42738257.70 | 0.597265E+09 | 16015.75 | 0.36 |
October | 0.138098E+09 | 0.00 | 0.00 | 2149800.91 | 0.00 | 0.776107E+09 | 0.469120E+09 | 0.00 | 0.35 |
November | 85115420.20 | 0.00 | 0.00 | 255322.28 | 0.00 | 0.124390E+10 | 88144475.57 | 0.00 | 0.36 |
December | 21151763.14 | 0.00 | 0.00 | 11130.92 | 0.00 | 0.159580E+10 | 1474392.28 | 0.00 | 0.36 |
Annual Sum or Average | 0.112325E+10 | 0.962244E+09 | 900440.66 | 42795254.40 | 0.202125E+09 | 0.882884E+10 | 0.365753E+10 | 76792.88 | 0.36 |
Minimum of Months | 10699229.12 | 0.00 | 0.00 | 11130.92 | 0.00 | 108948.80 | 1474392.28 | 0.00 | 0.35 |
Maximum of Months | 0.198662E+09 | 0.459027E+09 | 400933.74 | 9629310.76 | 95386317.38 | 0.163866E+10 | 0.945526E+09 | 29105.64 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.768294E+09 | 0.00 | 0.00 | 0.00 | 3382044.99 | 49915987.97 | 0.00 | 0.00 | 0.02 |
February | 0.745348E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
March | 0.100557E+10 | 2182247.04 | 0.00 | 486411.64 | 0.00 | 0.00 | 0.269328E+09 | 0.00 | 0.02 |
April | 0.608714E+09 | 0.00 | 0.00 | 1846649.75 | 0.00 | 0.00 | 0.849148E+09 | 0.00 | 0.02 |
May | 0.216348E+09 | 34090967.60 | 0.00 | 2399404.10 | 0.00 | 0.00 | 0.107185E+10 | 0.00 | 0.02 |
June | 0.00 | 0.330251E+09 | 0.00 | 1835649.56 | 0.00 | 0.00 | 0.516194E+09 | 0.00 | 0.02 |
July | 0.00 | 0.659654E+09 | 0.00 | 481326.86 | 0.00 | 0.00 | 57387268.92 | 0.00 | 0.02 |
August | 0.00 | 0.376143E+09 | 0.00 | 1983856.73 | 0.00 | 0.00 | 0.186699E+09 | 0.00 | 0.02 |
September | 62348827.98 | 0.185190E+09 | 0.00 | 3048876.83 | 0.00 | 0.00 | 0.574862E+09 | 0.00 | 0.02 |
October | 0.611716E+09 | 0.00 | 0.00 | 2715565.48 | 0.00 | 0.00 | 0.823520E+09 | 0.00 | 0.02 |
November | 0.103546E+10 | 0.00 | 0.00 | 399640.76 | 0.00 | 0.00 | 0.239393E+09 | 0.00 | 0.02 |
December | 0.822148E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
Annual Sum or Average | 0.587595E+10 | 0.158751E+10 | 0.00 | 15197381.72 | 3382044.99 | 49915987.97 | 0.458838E+10 | 0.00 | 0.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
Maximum of Months | 0.103546E+10 | 0.659654E+09 | 0.00 | 3048876.83 | 3382044.99 | 49915987.97 | 0.107185E+10 | 0.00 | 0.02 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.107643E+10 | 0.00 | 0.00 | 2222500.89 | 0.00 | 0.188734E+11 | 0.245433E+10 | 0.00 | 0.40 |
February | 0.100423E+10 | 0.00 | 0.00 | 1812139.04 | 0.00 | 0.174039E+11 | 0.218539E+10 | 0.00 | 0.40 |
March | 0.119103E+10 | 4852750.45 | 0.00 | 24045911.44 | 4450310.94 | 0.934456E+10 | 0.971352E+10 | 0.00 | 0.40 |
April | 0.153266E+10 | 0.00 | 0.00 | 56888939.01 | 0.00 | 0.639137E+09 | 0.170853E+11 | 0.00 | 0.40 |
May | 0.284085E+10 | 26364079.00 | 342293.42 | 0.115242E+09 | 12664432.96 | 45441705.87 | 0.138242E+11 | 20722.68 | 0.40 |
June | 0.226997E+10 | 0.214092E+10 | 844576.27 | 99746995.04 | 0.514626E+09 | 10015024.89 | 0.558369E+10 | 39445.22 | 0.40 |
July | 0.680924E+09 | 0.614015E+10 | 1951654.77 | 42047823.18 | 0.138385E+10 | 377851.98 | 0.145407E+10 | 35734.94 | 0.41 |
August | 0.146622E+10 | 0.339373E+10 | 1009604.51 | 73809655.29 | 0.671231E+09 | 2533334.65 | 0.320447E+10 | 64035.67 | 0.40 |
September | 0.229708E+10 | 0.101218E+10 | 565153.11 | 90411590.54 | 0.497318E+09 | 25759954.45 | 0.849833E+10 | 12333.87 | 0.40 |
October | 0.187322E+10 | 0.00 | 0.00 | 52679346.10 | 0.00 | 0.687700E+09 | 0.161795E+11 | 0.00 | 0.40 |
November | 0.120643E+10 | 0.00 | 0.00 | 21978334.25 | 0.00 | 0.394866E+10 | 0.140494E+11 | 0.00 | 0.40 |
December | 0.107796E+10 | 0.00 | 0.00 | 3458257.49 | 0.00 | 0.170774E+11 | 0.379422E+10 | 0.00 | 0.40 |
Annual Sum or Average | 0.185170E+11 | 0.127182E+11 | 4713282.08 | 0.584344E+09 | 0.308413E+10 | 0.680590E+11 | 0.980265E+11 | 172272.38 | 0.40 |
Minimum of Months | 0.680924E+09 | 0.00 | 0.00 | 1812139.04 | 0.00 | 377851.98 | 0.145407E+10 | 0.00 | 0.40 |
Maximum of Months | 0.284085E+10 | 0.614015E+10 | 1951654.77 | 0.115242E+09 | 0.138385E+10 | 0.188734E+11 | 0.170853E+11 | 64035.67 | 0.41 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 50532533.00 | 0.00 | 0.00 | 43263.08 | 0.00 | 0.157878E+10 | 22689618.25 | 0.00 | 0.35 |
February | 56631805.00 | 0.00 | 0.00 | 164754.90 | 0.00 | 0.142508E+10 | 36641740.73 | 0.00 | 0.35 |
March | 71877780.62 | 685924.29 | 0.00 | 2023882.82 | 0.00 | 0.110697E+10 | 0.313885E+09 | 0.00 | 0.35 |
April | 46383676.20 | 0.00 | 0.00 | 5558235.06 | 0.00 | 0.632733E+09 | 0.739365E+09 | 0.00 | 0.36 |
May | 15671629.06 | 2892015.39 | 12229.72 | 12024389.89 | 0.00 | 0.108160E+09 | 0.110473E+10 | 132.79 | 0.36 |
June | 0.00 | 0.195181E+09 | 108264.20 | 11522262.52 | 565873.80 | 2847912.30 | 0.572781E+09 | 6483.50 | 0.36 |
July | 0.00 | 0.554657E+09 | 236145.21 | 6132662.94 | 0.00 | 17198.77 | 0.154393E+09 | 5619.34 | 0.36 |
August | 1675559.21 | 0.299606E+09 | 180691.10 | 9968547.67 | 0.00 | 605013.04 | 0.337754E+09 | 6303.75 | 0.35 |
September | 7338280.30 | 0.111167E+09 | 160405.86 | 11123994.04 | 77.92 | 35769561.44 | 0.750290E+09 | 12471.55 | 0.35 |
October | 59150011.10 | 0.00 | 0.00 | 4621882.53 | 0.00 | 0.617798E+09 | 0.704068E+09 | 0.00 | 0.35 |
November | 71138538.15 | 0.00 | 0.00 | 949450.02 | 0.00 | 0.110999E+10 | 0.235512E+09 | 0.00 | 0.36 |
December | 35419037.59 | 0.00 | 0.00 | 61016.95 | 0.00 | 0.156650E+10 | 16637718.08 | 0.00 | 0.36 |
Annual Sum or Average | 0.415819E+09 | 0.116419E+10 | 697736.09 | 64194342.43 | 565951.71 | 0.818525E+10 | 0.498874E+10 | 31010.94 | 0.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 43263.08 | 0.00 | 17198.77 | 16637718.08 | 0.00 | 0.35 |
Maximum of Months | 71877780.62 | 0.554657E+09 | 236145.21 | 12024389.89 | 565873.80 | 0.157878E+10 | 0.110473E+10 | 12471.55 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 12066320.08 | 0.00 | 0.00 | 15710.65 | 0.00 | 0.163798E+10 | 1794186.55 | 0.00 | 0.35 |
February | 25272898.58 | 0.00 | 0.00 | 30899.45 | 0.00 | 0.148358E+10 | 9456052.85 | 0.00 | 0.35 |
March | 82855846.62 | 382526.65 | 0.00 | 991933.51 | 303317.27 | 0.120310E+10 | 0.207640E+09 | 0.00 | 0.35 |
April | 0.102163E+09 | 0.00 | 0.00 | 3968552.99 | 0.00 | 0.727838E+09 | 0.589903E+09 | 0.00 | 0.36 |
May | 0.175421E+09 | 2579970.85 | 22842.32 | 9397092.66 | 299960.87 | 0.126156E+09 | 0.929461E+09 | 1263.57 | 0.36 |
June | 0.140717E+09 | 0.163198E+09 | 136738.87 | 8784812.77 | 32495962.04 | 969601.30 | 0.436611E+09 | 7652.54 | 0.36 |
July | 46754338.59 | 0.460838E+09 | 179104.76 | 3841290.96 | 93810686.52 | 48135.80 | 0.109881E+09 | 5880.01 | 0.36 |
August | 0.101310E+09 | 0.255529E+09 | 141800.69 | 6507496.31 | 44076717.86 | 472074.21 | 0.241672E+09 | 10063.60 | 0.36 |
September | 0.144628E+09 | 83487454.96 | 201629.51 | 7341416.24 | 27626050.21 | 42547717.86 | 0.609911E+09 | 11496.49 | 0.36 |
October | 0.138285E+09 | 0.00 | 0.00 | 2288551.77 | 0.00 | 0.745608E+09 | 0.499295E+09 | 0.00 | 0.35 |
November | 85485028.19 | 0.00 | 0.00 | 313579.61 | 0.00 | 0.120480E+10 | 0.126824E+09 | 0.00 | 0.36 |
December | 18791460.18 | 0.00 | 0.00 | 15710.21 | 0.00 | 0.159735E+10 | 2271565.02 | 0.00 | 0.36 |
Annual Sum or Average | 0.107375E+10 | 0.966015E+09 | 682116.15 | 43497047.12 | 0.198613E+09 | 0.877044E+10 | 0.376472E+10 | 36356.20 | 0.36 |
Minimum of Months | 12066320.08 | 0.00 | 0.00 | 15710.21 | 0.00 | 48135.80 | 1794186.55 | 0.00 | 0.35 |
Maximum of Months | 0.175421E+09 | 0.460838E+09 | 201629.51 | 9397092.66 | 93810686.52 | 0.163798E+10 | 0.929461E+09 | 11496.49 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.249805E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.813141E+10 | 0.00 | 0.00 | 0.62 |
February | 0.234000E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.702376E+10 | 0.00 | 0.00 | 0.62 |
March | 0.307857E+11 | 0.00 | 0.00 | 0.00 | 2213513.14 | 36915882.52 | 0.00 | 0.00 | 0.62 |
April | 0.301873E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.63 |
May | 0.290517E+11 | 0.00 | 0.00 | 0.00 | 1274408.73 | 0.00 | 0.00 | 0.00 | 0.63 |
June | 0.163566E+11 | 0.00 | 0.00 | 0.00 | 0.190021E+10 | 0.00 | 0.00 | 0.00 | 0.63 |
July | 0.741639E+10 | 0.504338E+09 | 0.00 | 0.00 | 0.570714E+10 | 0.00 | 0.00 | 0.00 | 0.63 |
August | 0.121555E+11 | 27420382.03 | 0.00 | 47135.11 | 0.272373E+10 | 0.00 | 0.122253E+09 | 0.00 | 0.63 |
September | 0.219901E+11 | 0.00 | 0.00 | 0.00 | 0.100395E+10 | 0.00 | 0.00 | 0.00 | 0.63 |
October | 0.322419E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.62 |
November | 0.294460E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 55293702.02 | 0.00 | 0.00 | 0.62 |
December | 0.231493E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.912678E+10 | 0.00 | 0.00 | 0.62 |
Annual Sum or Average | 0.281161E+12 | 0.531758E+09 | 0.00 | 47135.11 | 0.113385E+11 | 0.243742E+11 | 0.122253E+09 | 0.00 | 0.63 |
Minimum of Months | 0.741639E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.62 |
Maximum of Months | 0.322419E+11 | 0.504338E+09 | 0.00 | 47135.11 | 0.570714E+10 | 0.912678E+10 | 0.122253E+09 | 0.00 | 0.63 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 5419550.56 | 0.00 | 0.00 | 17266.71 | 0.00 | 0.406601E+09 | 974583.35 | 0.00 | 0.35 |
February | 6179093.31 | 0.00 | 0.00 | 46025.78 | 0.00 | 0.369634E+09 | 3769412.36 | 0.00 | 0.35 |
March | 17839979.06 | 171481.07 | 0.00 | 523416.89 | 0.00 | 0.300712E+09 | 54614647.79 | 0.00 | 0.35 |
April | 13921714.04 | 0.00 | 0.00 | 1321483.16 | 0.00 | 0.206863E+09 | 0.133904E+09 | 0.00 | 0.36 |
May | 6222016.52 | 726094.48 | 0.00 | 3112994.82 | 0.00 | 58838029.48 | 0.241972E+09 | 0.00 | 0.36 |
June | 1386557.99 | 48923541.37 | 19111.83 | 2981911.60 | 18007.63 | 4362592.24 | 0.138057E+09 | 4674.63 | 0.36 |
July | 0.00 | 0.138655E+09 | 62260.25 | 1180202.70 | 0.00 | 70950.43 | 38884684.83 | 7687.03 | 0.36 |
August | 512718.84 | 74889183.22 | 32074.67 | 2210940.07 | 24876.89 | 301109.95 | 84476043.97 | 2076.31 | 0.35 |
September | 2146248.81 | 27804449.74 | 25010.00 | 2645005.59 | 2103.86 | 17727827.35 | 0.178611E+09 | 3355.46 | 0.36 |
October | 16532192.37 | 0.00 | 0.00 | 965243.00 | 0.00 | 0.202627E+09 | 0.126285E+09 | 0.00 | 0.35 |
November | 16121492.09 | 0.00 | 0.00 | 152438.87 | 0.00 | 0.308284E+09 | 29838126.38 | 0.00 | 0.36 |
December | 5252471.53 | 0.00 | 0.00 | 10150.33 | 0.00 | 0.398819E+09 | 574185.30 | 0.00 | 0.36 |
Annual Sum or Average | 91534035.12 | 0.291169E+09 | 138456.75 | 15167079.51 | 44988.38 | 0.227484E+10 | 0.103196E+10 | 17793.43 | 0.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 10150.33 | 0.00 | 70950.43 | 574185.30 | 0.00 | 0.35 |
Maximum of Months | 17839979.06 | 0.138655E+09 | 62260.25 | 3112994.82 | 24876.89 | 0.406601E+09 | 0.241972E+09 | 7687.03 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 552977.74 | 0.00 | 0.00 | 1292.75 | 0.00 | 0.412294E+09 | 114997.21 | 0.00 | 0.35 |
February | 902209.79 | 0.00 | 0.00 | 4372.42 | 0.00 | 0.377200E+09 | 1477832.19 | 0.00 | 0.35 |
March | 14747435.43 | 89439.09 | 0.00 | 232208.21 | 82021.89 | 0.320158E+09 | 38508357.81 | 0.00 | 0.35 |
April | 27716424.51 | 0.00 | 0.00 | 949900.30 | 0.00 | 0.228594E+09 | 98708372.75 | 0.00 | 0.36 |
May | 47358071.37 | 651019.19 | 0.00 | 2378464.32 | 74990.22 | 61189572.37 | 0.199183E+09 | 0.00 | 0.36 |
June | 36024974.74 | 40705266.42 | 36198.72 | 2264608.92 | 8215536.86 | 2320856.04 | 0.106160E+09 | 2596.46 | 0.36 |
July | 11831263.55 | 0.114748E+09 | 107384.24 | 849428.26 | 23846579.35 | 22676.55 | 27427767.10 | 6197.33 | 0.36 |
August | 25685587.78 | 63628455.56 | 60345.88 | 1539757.49 | 11243559.13 | 223253.94 | 60041961.62 | 7069.25 | 0.36 |
September | 37925162.48 | 20839134.33 | 35705.36 | 1567282.68 | 6953455.87 | 17375262.24 | 0.144239E+09 | 3362.23 | 0.36 |
October | 34641356.95 | 0.00 | 0.00 | 420124.89 | 0.00 | 0.238325E+09 | 72982696.46 | 0.00 | 0.35 |
November | 17620319.81 | 0.00 | 0.00 | 34523.04 | 0.00 | 0.328026E+09 | 8674273.52 | 0.00 | 0.36 |
December | 1770377.97 | 0.00 | 0.00 | 1843.40 | 0.00 | 0.402684E+09 | 151753.60 | 0.00 | 0.36 |
Annual Sum or Average | 0.256776E+09 | 0.240661E+09 | 239634.20 | 10243806.66 | 50416143.32 | 0.238841E+10 | 0.757670E+09 | 19225.26 | 0.36 |
Minimum of Months | 552977.74 | 0.00 | 0.00 | 1292.75 | 0.00 | 22676.55 | 114997.21 | 0.00 | 0.35 |
Maximum of Months | 47358071.37 | 0.114748E+09 | 107384.24 | 2378464.32 | 23846579.35 | 0.412294E+09 | 0.199183E+09 | 7069.25 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 79527316.17 | 0.00 | 0.00 | 856527.30 | 0.00 | 0.239703E+10 | 0.175974E+09 | 0.00 | 0.40 |
February | 95942418.05 | 0.00 | 0.00 | 956549.95 | 0.00 | 0.216412E+10 | 0.177900E+09 | 0.00 | 0.40 |
March | 60458669.54 | 1101678.32 | 0.00 | 5664820.99 | 0.00 | 0.142328E+10 | 0.911368E+09 | 0.00 | 0.40 |
April | 55869068.63 | 0.00 | 0.00 | 8809065.95 | 0.00 | 0.808795E+09 | 0.141371E+10 | 0.00 | 0.40 |
May | 19601608.34 | 4664786.22 | 0.00 | 15813171.31 | 0.00 | 0.119671E+09 | 0.183744E+10 | 0.00 | 0.40 |
June | 3956179.84 | 0.313574E+09 | 76641.72 | 13141169.20 | 908862.54 | 8428689.33 | 0.917511E+09 | 17279.33 | 0.40 |
July | 0.00 | 0.890987E+09 | 231367.29 | 6038214.99 | 0.00 | 515375.10 | 0.251299E+09 | 16572.38 | 0.40 |
August | 3293956.70 | 0.480759E+09 | 88207.66 | 12313588.50 | 656344.07 | 1416177.55 | 0.545124E+09 | 863.17 | 0.40 |
September | 6701109.46 | 0.178815E+09 | 9025.49 | 17381554.35 | 0.00 | 28936466.55 | 0.123914E+10 | 1424.93 | 0.40 |
October | 72785023.07 | 0.00 | 0.00 | 10908180.98 | 0.00 | 0.619895E+09 | 0.152192E+10 | 0.00 | 0.40 |
November | 76495902.21 | 0.00 | 0.00 | 4073897.07 | 0.00 | 0.134385E+10 | 0.852399E+09 | 0.00 | 0.40 |
December | 80063566.45 | 0.00 | 0.00 | 858389.23 | 0.00 | 0.238719E+10 | 0.131596E+09 | 0.00 | 0.40 |
Annual Sum or Average | 0.554695E+09 | 0.186990E+10 | 405242.16 | 96815129.82 | 1565206.61 | 0.113031E+11 | 0.997538E+10 | 36139.81 | 0.40 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 856527.30 | 0.00 | 515375.10 | 0.131596E+09 | 0.00 | 0.40 |
Maximum of Months | 95942418.05 | 0.890987E+09 | 231367.29 | 17381554.35 | 908862.54 | 0.239703E+10 | 0.183744E+10 | 17279.33 | 0.40 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.125797E+11 | 0.00 | 0.00 | 34613735.73 | 0.00 | 0.00 | 0.354415E+11 | 0.00 | 4.27 |
February | 0.112053E+11 | 0.00 | 0.00 | 30999697.70 | 0.00 | 0.00 | 0.328349E+11 | 0.00 | 4.27 |
March | 0.510125E+10 | 1976778.01 | 0.00 | 48472212.06 | 1113458.46 | 0.00 | 0.420948E+11 | 0.00 | 4.48 |
April | 0.140206E+10 | 0.00 | 0.00 | 61064132.77 | 0.00 | 0.00 | 0.467882E+11 | 0.00 | 4.71 |
May | 0.243236E+09 | 1856168.99 | 0.00 | 85504747.09 | 0.00 | 0.00 | 0.500228E+11 | 0.00 | 5.01 |
June | 40824904.37 | 0.326712E+10 | 0.00 | 82303997.65 | 0.00 | 0.00 | 0.302210E+11 | 0.00 | 5.34 |
July | 780532.84 | 0.111309E+11 | 0.00 | 56617386.15 | 0.00 | 0.00 | 0.145414E+11 | 0.00 | 5.52 |
August | 3469154.44 | 0.482011E+10 | 0.00 | 77510194.50 | 218874.08 | 0.00 | 0.234502E+11 | 0.00 | 5.41 |
September | 0.113501E+09 | 0.169314E+10 | 0.00 | 75807292.43 | 1021137.94 | 0.00 | 0.384992E+11 | 0.00 | 5.10 |
October | 0.127839E+10 | 0.00 | 0.00 | 62374978.27 | 0.00 | 0.00 | 0.507274E+11 | 0.00 | 4.73 |
November | 0.281586E+10 | 0.00 | 0.00 | 48989364.47 | 0.00 | 0.00 | 0.428753E+11 | 0.00 | 4.57 |
December | 0.113757E+11 | 0.00 | 0.00 | 36485359.81 | 0.00 | 0.00 | 0.357090E+11 | 0.00 | 4.32 |
Annual Sum or Average | 0.461601E+11 | 0.209151E+11 | 0.00 | 0.700743E+09 | 2353470.47 | 0.00 | 0.443206E+12 | 0.00 | 4.81 |
Minimum of Months | 780532.84 | 0.00 | 0.00 | 30999697.70 | 0.00 | 0.00 | 0.145414E+11 | 0.00 | 4.27 |
Maximum of Months | 0.125797E+11 | 0.111309E+11 | 0.00 | 85504747.09 | 1113458.46 | 0.00 | 0.507274E+11 | 0.00 | 5.52 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.779788E+10 | 0.00 | 0.00 | 47823418.09 | 0.00 | 0.00 | 0.441222E+11 | 0.00 | 4.62 |
February | 0.537913E+10 | 0.00 | 0.00 | 43389823.84 | 0.00 | 0.00 | 0.422700E+11 | 0.00 | 4.62 |
March | 0.194751E+10 | 3239310.24 | 0.00 | 63101435.19 | 0.00 | 0.00 | 0.495024E+11 | 0.00 | 4.89 |
April | 0.315593E+09 | 0.00 | 0.00 | 76027749.55 | 0.00 | 0.00 | 0.524578E+11 | 0.00 | 5.16 |
May | 0.00 | 2085606.82 | 0.00 | 99541696.60 | 0.00 | 0.00 | 0.546909E+11 | 0.00 | 5.46 |
June | 1624769.75 | 0.351960E+10 | 0.00 | 91545256.12 | 0.00 | 0.00 | 0.324798E+11 | 0.00 | 5.74 |
July | 0.00 | 0.118977E+11 | 0.00 | 62061249.88 | 0.00 | 0.00 | 0.154474E+11 | 0.00 | 5.89 |
August | 0.00 | 0.517278E+10 | 0.00 | 85820053.10 | 0.00 | 0.00 | 0.249767E+11 | 0.00 | 5.78 |
September | 4503333.29 | 0.183084E+10 | 0.00 | 86596172.41 | 0.00 | 0.00 | 0.417359E+11 | 0.00 | 5.51 |
October | 0.294495E+09 | 0.00 | 0.00 | 76903205.76 | 0.00 | 0.00 | 0.565307E+11 | 0.00 | 5.17 |
November | 0.786199E+09 | 0.00 | 0.00 | 64290678.79 | 0.00 | 0.00 | 0.491673E+11 | 0.00 | 4.99 |
December | 0.656407E+10 | 0.00 | 0.00 | 50182831.76 | 0.00 | 0.00 | 0.444373E+11 | 0.00 | 4.68 |
Annual Sum or Average | 0.230910E+11 | 0.224262E+11 | 0.00 | 0.847284E+09 | 0.00 | 0.00 | 0.507818E+12 | 0.00 | 5.21 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 43389823.84 | 0.00 | 0.00 | 0.154474E+11 | 0.00 | 4.62 |
Maximum of Months | 0.779788E+10 | 0.118977E+11 | 0.00 | 99541696.60 | 0.00 | 0.00 | 0.565307E+11 | 0.00 | 5.89 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 12268722.03 | 0.00 | 0.00 | 0.110406E+09 | 0.00 | 0.00 | 0.730291E+11 | 0.00 | 20.88 |
February | 6207798.69 | 0.00 | 0.00 | 99493873.48 | 0.00 | 0.00 | 0.673401E+11 | 0.00 | 20.99 |
March | 3145136.93 | 6267724.58 | 0.00 | 0.113554E+09 | 0.00 | 0.00 | 0.700883E+11 | 0.00 | 21.75 |
April | 0.00 | 0.00 | 0.00 | 0.117266E+09 | 0.00 | 0.00 | 0.705336E+11 | 0.00 | 22.47 |
May | 0.00 | 3587782.85 | 0.00 | 0.142268E+09 | 0.00 | 0.00 | 0.669597E+11 | 0.00 | 22.93 |
June | 0.00 | 0.514500E+10 | 0.00 | 0.119796E+09 | 0.00 | 0.00 | 0.362971E+11 | 0.00 | 23.31 |
July | 0.00 | 0.164151E+11 | 0.00 | 77377181.04 | 0.00 | 0.00 | 0.151945E+11 | 0.00 | 23.53 |
August | 0.00 | 0.735970E+10 | 0.00 | 0.111977E+09 | 0.00 | 0.00 | 0.263477E+11 | 0.00 | 23.33 |
September | 0.00 | 0.273177E+10 | 0.00 | 0.122164E+09 | 0.00 | 0.00 | 0.494229E+11 | 0.00 | 23.01 |
October | 0.00 | 0.00 | 0.00 | 0.117701E+09 | 0.00 | 0.00 | 0.745767E+11 | 0.00 | 22.34 |
November | 0.00 | 0.00 | 0.00 | 0.108302E+09 | 0.00 | 0.00 | 0.671643E+11 | 0.00 | 21.86 |
December | 8813413.65 | 0.00 | 0.00 | 0.109542E+09 | 0.00 | 0.00 | 0.709928E+11 | 0.00 | 21.00 |
Annual Sum or Average | 30435071.30 | 0.316614E+11 | 0.00 | 0.134985E+10 | 0.00 | 0.00 | 0.687947E+12 | 0.00 | 22.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 77377181.04 | 0.00 | 0.00 | 0.151945E+11 | 0.00 | 20.88 |
Maximum of Months | 12268722.03 | 0.164151E+11 | 0.00 | 0.142268E+09 | 0.00 | 0.00 | 0.745767E+11 | 0.00 | 23.53 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.900048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.745326E+10 | 0.00 | 0.00 | 1.17 |
February | 0.853178E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.658618E+10 | 0.00 | 0.00 | 1.17 |
March | 0.140205E+11 | 0.00 | 0.00 | 0.00 | 1099925.03 | 0.129568E+10 | 0.00 | 0.00 | 1.16 |
April | 0.149814E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 19069194.78 | 0.00 | 0.00 | 1.18 |
May | 0.144362E+11 | 0.00 | 0.00 | 0.00 | 633271.17 | 0.00 | 0.00 | 0.00 | 1.18 |
June | 0.787197E+10 | 0.365363E+09 | 0.00 | 488682.74 | 0.579772E+09 | 0.00 | 0.255358E+09 | 0.00 | 1.18 |
July | 0.319751E+10 | 0.218321E+10 | 0.00 | 1224080.00 | 0.972084E+09 | 0.00 | 0.486596E+09 | 0.00 | 1.20 |
August | 0.521843E+10 | 0.719722E+09 | 0.00 | 2898490.74 | 0.657111E+09 | 0.00 | 0.884065E+09 | 0.00 | 1.19 |
September | 0.108646E+11 | 39641829.44 | 0.00 | 170330.99 | 0.459232E+09 | 0.00 | 62435908.38 | 0.00 | 1.18 |
October | 0.160215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 |
November | 0.146148E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 44825745.58 | 0.00 | 0.00 | 1.17 |
December | 0.925497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.678346E+10 | 0.00 | 0.00 | 1.17 |
Annual Sum or Average | 0.128014E+12 | 0.330793E+10 | 0.00 | 4781584.46 | 0.266993E+10 | 0.221825E+11 | 0.168846E+10 | 0.00 | 1.18 |
Minimum of Months | 0.319751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.16 |
Maximum of Months | 0.160215E+11 | 0.218321E+10 | 0.00 | 2898490.74 | 0.972084E+09 | 0.745326E+10 | 0.884065E+09 | 0.00 | 1.20 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:21:40
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.152208E+12 | 0.108728E+11 | 0.314681E+12 | 0.124844E+13 | 0.942326E+11 |
February | 0.248627E+12 | 0.101154E+11 | 0.290578E+12 | 0.115690E+13 | 0.885836E+11 |
March | 0.376837E+12 | 0.863244E+10 | 0.247516E+12 | 0.100649E+13 | 0.105176E+12 |
April | 0.456662E+12 | 0.649326E+10 | 0.187064E+12 | 0.779619E+12 | 0.100313E+12 |
May | 0.573415E+12 | 0.454287E+10 | 0.121895E+12 | 0.513119E+12 | 0.225082E+12 |
June | 0.639730E+12 | 0.176445E+10 | 0.488446E+11 | 0.217578E+12 | 0.546645E+12 |
July | 0.579748E+12 | -957123767.0 | -0.157527E+11 | -0.666878E+11 | 0.914204E+12 |
August | 0.486911E+12 | 0.703642E+09 | 0.250222E+11 | 0.113640E+12 | 0.710165E+12 |
September | 0.359950E+12 | 0.280385E+10 | 0.793060E+11 | 0.340405E+12 | 0.399910E+12 |
October | 0.237536E+12 | 0.586568E+10 | 0.169528E+12 | 0.705917E+12 | 0.140215E+12 |
November | 0.123053E+12 | 0.698421E+10 | 0.208174E+12 | 0.846231E+12 | 0.774323E+11 |
December | 0.137048E+12 | 0.103508E+11 | 0.304225E+12 | 0.120425E+13 | 0.871495E+11 |
Annual Sum or Average | 0.437172E+13 | 0.681724E+11 | 0.198108E+13 | 0.806589E+13 | 0.348911E+13 |
Minimum of Months | 0.123053E+12 | -957123767.0 | -0.157527E+11 | -0.666878E+11 | 0.774323E+11 |
Maximum of Months | 0.639730E+12 | 0.108728E+11 | 0.314681E+12 | 0.124844E+13 | 0.914204E+12 |