Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** Albuquerque Intl Sunport NM USA TMY3 WMO#=723650
Simulation Timestamp: 2024-07-03 12:21:37
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:37
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 10465.10 | 922.42 | 922.42 |
Net Site Energy | 10465.10 | 922.42 | 922.42 |
Total Source Energy | 22225.63 | 1959.02 | 1959.02 |
Net Source Energy | 22225.63 | 1959.02 | 1959.02 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 864.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 786.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 781.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 193.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1658.18 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 813.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 611.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 80.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 141.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 94.78 | 2587.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | 61.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 5223.94 | 5241.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 864.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 786.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 781.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 193.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 872.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 14.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 8.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 21.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 789.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 2.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 611.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 80.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 141.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 94.78 | 2587.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5742.51 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.69 | |
Refrigeration | General | 7.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 20.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 33.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 864.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 786.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 781.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 193.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 1658.18 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 813.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 611.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 80.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 141.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 94.78 | 2587.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | Unassigned | 61.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 86.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 138.69 | 304.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 235.76 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 460.45 | 461.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 86.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 138.69 | 304.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 235.76 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 460.45 | 461.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 5223.936 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 5223.936 | 100.00 |
Total On-Site and Utility Electric Sources | 5223.936 | 100.00 |
Total Electricity End Uses | 5223.936 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 82.06 | 3.80 |
Air to Air Heat Recovery for Heating | 2075.30 | 96.20 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 2157.36 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9857.19 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9857.19 | 100.00 |
Total Water End Uses | 9857.19 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 633.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 7569.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4B
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NM_ALBUQUERQUE
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER1 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| FLR_3_DOAS COOLING COIL | VAV WITH REHEAT COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH LAUNDRY G WATER HEATER | SWH BOOSTER E WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |CoilReportMonthly
| FLR_3_DOAS HEATING COIL | VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | FLR_3_DOAS COOLING COIL | VAV WITH REHEAT COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |FanReportMonthly
| FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL_FANCOILFAN | ROOM_2_FLR_3 FAN COIL_FANCOILFAN | ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | ROOM_5_FLR_3 FAN COIL_FANCOILFAN | ROOM_6_FLR_3 FAN COIL_FANCOILFAN | ROOM_1_FLR_6 FAN COIL_FANCOILFAN | ROOM_2_FLR_6 FAN COIL_FANCOILFAN | ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| FLR_3_DOAS | VAV WITH REHEAT |AirLoopSystemComponentLoadsMonthly
| FLR_3_DOAS | VAV WITH REHEAT |AirLoopSystemComponentEnergyUseMonthly
| FLR_3_DOAS | VAV WITH REHEAT |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:37
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21 |
RunPeriod | RUNPERIOD 1 |
Weather File | Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 |
Latitude [deg] | 35.04 |
Longitude [deg] | -106.6 |
Elevation [m] | 1619.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 8.8143 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.26 | 23.26 | 11.3140 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 11.3140 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 4.6285 | 61.93 | 5.3800 |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 5.7199 | 46.45 | 2.6900 |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 4.6285 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.50 | 65.50 | 10.0104 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.08 | 85.08 | 10.7639 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 8.2882 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 8.2882 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 7.1042 | 18.58 | 0.0000 |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.74 | 6.74 | 8.2882 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 10.0104 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 10.0104 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.37 | 26.37 | 11.4097 | 4.65 | 2934.4875 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.20 | 28.20 | 7.1042 | 18.58 | 0.0000 |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 8.5566 | 7.07 | 41.0709 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 8.5566 | 7.07 | 41.0709 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 1978.83 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 8.8143 | 18.58 | 5.3800 | |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 1.00 | RETAIL_1_FLR_1 | GENERAL | RETAIL_1_FLR_1 | 11.3140 | 6.19 | 10.7600 | |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 1.00 | RETAIL_2_FLR_1 | GENERAL | RETAIL_2_FLR_1 | 11.3140 | 6.19 | 10.7600 | |
MECH_FLR_1 | 164.24 | Yes | Yes | 1.00 | MECH_FLR_1 | GENERAL | MECH_FLR_1 | 4.6285 | 61.93 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 1.00 | STORAGE_FLR_1 | GENERAL | STORAGE_FLR_1 | 5.7199 | 46.45 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 1.00 | LAUNDRY_FLR_1 | GENERAL | LAUNDRY_FLR_1 | 4.6285 | 9.29 | 597.5300 | |
CAFE_FLR_1 | 188.86 | Yes | Yes | 1.00 | CAFE_FLR_1 | GENERAL | CAFE_FLR_1 | 10.0104 | 1.33 | 5.3800 | |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 1.00 | LOBBY_FLR_1 | GENERAL | LOBBY_FLR_1 | 10.7639 | 3.10 | 8.0700 | |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_1_FLR_3 | GENERAL | ROOM_1_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_2_FLR_3 | GENERAL | ROOM_2_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 76.00 | ROOM_3_MULT19_FLR_3 | GENERAL | ROOM_3_MULT19_FLR_3 | 8.2882 | 16.35 | 10.5200 | |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 76.00 | ROOM_4_MULT19_FLR_3 | GENERAL | ROOM_4_MULT19_FLR_3 | 8.2882 | 16.35 | 10.5200 | |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_5_FLR_3 | GENERAL | ROOM_5_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_6_FLR_3 | GENERAL | ROOM_6_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 4.00 | CORRIDOR_FLR_3 | GENERAL | CORRIDOR_FLR_3 | 7.1042 | 18.58 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_1_FLR_6 | GENERAL | ROOM_1_FLR_6 | 8.2882 | 26.01 | 6.7500 | |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_2_FLR_6 | GENERAL | ROOM_2_FLR_6 | 8.2882 | 26.01 | 6.7500 | |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 9.00 | ROOM_3_MULT9_FLR_6 | GENERAL | ROOM_3_MULT9_FLR_6 | 8.2882 | 16.35 | 10.5200 | |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1.00 | BANQUET_FLR_6 | GENERAL | BANQUET_FLR_6 | 10.0104 | 1.33 | 67.8200 | |
DINING_FLR_6 | 331.66 | Yes | Yes | 1.00 | DINING_FLR_6 | GENERAL | DINING_FLR_6 | 10.0104 | 1.33 | 67.8200 | |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 1.00 | KITCHEN_FLR_6 | GENERAL | KITCHEN_FLR_6 | 11.4097 | 4.65 | 2934.4875 | |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1.00 | CORRIDOR_FLR_6 | GENERAL | CORRIDOR_FLR_6 | 7.1042 | 18.58 | 0.0000 | |
Total | 11345.29 | 8.5566 | 3.54 | 41.0709 | |||||||
Conditioned Total | 11345.29 | 8.5566 | 3.54 | 41.0709 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 11345.29 | 11345.29 | 0.00 | 0.00 | 4.6520 | 8.82 | 37.1989 |
Total | 11345.29 | 11345.29 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:37
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 21-JUL-19:19 | 27-JAN-18:40 | - | - | - | - | - | - | - | - | - | - | 20-APR-20:00 |
Heating | 0.00 | 213115.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 127604.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 64632.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 12338.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 86439.81 | 104248.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 10999.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 45669.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 3017.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 3981.45 | 246938.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1830.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 366453.59 | 564302.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 213115.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 127604.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 64632.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 12338.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 56456.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 29272.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1249.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 9600.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 150.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 45669.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 3017.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 3981.45 | 246938.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 530.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1058.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:37
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 937.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2490.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2476.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 613.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5251.45 | 1939.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2577.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1937.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 255.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 447.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 300.17 | 2804.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 194.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 16544.20 | 5681.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 82.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 219.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 218.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 54.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 462.88 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 227.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 170.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 22.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 39.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 26.46 | 247.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1458.24 | 500.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 82.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 219.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 218.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 54.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 462.88 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 227.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 170.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 22.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 39.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 26.46 | 247.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1458.24 | 500.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:37
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
BASEMENT VAV BOX COMPONENT | 3.06 | 0.492209 | 0.440000 | 1.35 | 1.00 | 0.500000 | 0.000774 | 0.000051 | 1.35 | 16.70 | 0.008000 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.404225 | 0.126435 | 0.440000 | 0.177859 | 0.440000 | 0.500000 | 0.003013 | 0.000027 | 0.177859 | 16.70 | 0.008000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.277252 | 0.213465 | 0.440000 | 0.121991 | 0.569240 | 0.500000 | 0.001785 | 0.000012 | 0.121991 | 16.70 | 0.008000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.226054 | 0.553642 | 0.440000 | 0.099464 | 1.00 | 0.500000 | 0.000688 | 0.000016 | 0.099464 | 16.70 | 0.008000 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.136168 | 0.530277 | 0.440000 | 0.059914 | 1.00 | 0.500000 | 0.000718 | 0.000011 | 0.059914 | 16.70 | 0.008000 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 3.95 | 0.015041 | 0.440000 | 1.74 | 0.440000 | 0.500000 | 0.025330 | 0.000082 | 1.74 | 16.70 | 0.008000 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.74 | 0.082645 | 0.440000 | 0.766191 | 0.440000 | 0.500000 | 0.004610 | 0.000082 | 0.766191 | 16.70 | 0.008000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 5.74 | 0.173759 | 0.440000 | 2.52 | 0.463359 | 0.500000 | 0.002193 | 0.000217 | 2.52 | 16.70 | 0.008000 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.82 | 0.650965 | 0.440000 | 0.802253 | 1.00 | 0.500000 | 0.000585 | 0.000104 | 0.802253 | 16.70 | 0.008000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.65 | 0.095241 | 0.440000 | 1.17 | 0.440000 | 0.500000 | 0.004000 | 0.000092 | 1.17 | 16.70 | 0.008000 |
DINING_FLR_6 VAV BOX COMPONENT | 2.78 | 0.090893 | 0.440000 | 1.22 | 0.440000 | 0.500000 | 0.004192 | 0.000095 | 1.22 | 16.70 | 0.008000 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.74 | 0.051623 | 0.440000 | 1.21 | 0.440000 | 0.500000 | 0.013275 | 0.000059 | 1.21 | 16.70 | 0.008000 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 0.945303 | 0.332210 | 0.440000 | 0.415933 | 0.885893 | 0.500000 | 0.001147 | 0.000066 | 0.415933 | 16.70 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
BASEMENT VAV BOX REHEAT COIL | 5853.65 | 0.000051 | 122.07 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 3143.13 | 0.000027 | 78.23 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1316.11 | 0.000012 | 29.75 |
MECH_FLR_1 VAV BOX REHEAT COIL | 1828.33 | 0.000016 | 45.99 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 1229.71 | 0.000011 | 31.97 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 9419.86 | 0.000082 | 198.98 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 9349.48 | 0.000082 | 215.38 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 24778.19 | 0.000217 | 553.06 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | 5181.18 | 0.000045 | 148.04 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | 5180.92 | 0.000045 | 148.03 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 29953.44 | 0.000262 | 855.84 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 29963.02 | 0.000262 | 856.12 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | 5181.18 | 0.000045 | 148.04 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | 5180.92 | 0.000045 | 148.03 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 11928.62 | 0.000104 | 285.08 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | 1601.26 | 0.000014 | 45.75 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | 1602.13 | 0.000014 | 45.78 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 7700.30 | 0.000067 | 220.01 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 10480.32 | 0.000092 | 231.41 |
DINING_FLR_6 VAV BOX REHEAT COIL | 10844.26 | 0.000095 | 239.10 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 6762.67 | 0.000059 | 143.18 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 7533.90 | 0.000066 | 188.75 |
FLR_3_DOAS HEATING COIL | 15066.37 | 0.000132 | 252.13 |
VAV WITH REHEAT HEATING COIL | 193415.68 | 0.001692 | 3236.72 |
Design Size Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 0.061735 |
ROOM_2_FLR_3 DIRECT AIR | 0.061728 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 0.837072 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 0.837300 |
ROOM_5_FLR_3 DIRECT AIR | 0.061735 |
ROOM_6_FLR_3 DIRECT AIR | 0.061728 |
ROOM_1_FLR_6 DIRECT AIR | 0.015434 |
ROOM_2_FLR_6 DIRECT AIR | 0.015432 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 0.099154 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Hot Water Flow [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 1.39 | 0.000045 | 0.000366 |
ROOM_2_FLR_3 FAN COIL | 1.37 | 0.000045 | 0.000362 |
ROOM_3_MULT19_FLR_3 FAN COIL | 7.57 | 0.000262 | 0.001971 |
ROOM_4_MULT19_FLR_3 FAN COIL | 7.59 | 0.000262 | 0.002088 |
ROOM_5_FLR_3 FAN COIL | 1.23 | 0.000045 | 0.000325 |
ROOM_6_FLR_3 FAN COIL | 1.22 | 0.000045 | 0.000322 |
ROOM_1_FLR_6 FAN COIL | 0.367990 | 0.000014 | 0.000097 |
ROOM_2_FLR_6 FAN COIL | 0.363430 | 0.000014 | 0.000096 |
ROOM_3_MULT9_FLR_6 FAN COIL | 1.53 | 0.000067 | 0.000410 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COIL_FANCOILFAN | 1.39 |
ROOM_2_FLR_3 FAN COIL_FANCOILFAN | 1.37 |
ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | 7.57 |
ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | 7.59 |
ROOM_5_FLR_3 FAN COIL_FANCOILFAN | 1.23 |
ROOM_6_FLR_3 FAN COIL_FANCOILFAN | 1.22 |
ROOM_1_FLR_6 FAN COIL_FANCOILFAN | 0.367990 |
ROOM_2_FLR_6 FAN COIL_FANCOILFAN | 0.363430 |
ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN | 1.53 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Coil Load [W] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | 21.81 | 6.70 | 0.008545 | 12.80 | 0.008500 | 0.000366 | 1.39 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | 21.81 | 6.70 | 0.008545 | 12.80 | 0.008500 | 0.000362 | 1.37 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 21.81 | 6.70 | 0.008481 | 12.80 | 0.008481 | 0.001971 | 7.57 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 21.81 | 6.70 | 0.008705 | 12.80 | 0.008500 | 0.002088 | 7.59 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | 21.81 | 6.70 | 0.008550 | 12.80 | 0.008500 | 0.000325 | 1.23 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | 21.81 | 6.70 | 0.008551 | 12.80 | 0.008500 | 0.000322 | 1.22 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | 21.81 | 6.70 | 0.008542 | 12.80 | 0.008500 | 0.000097 | 0.367990 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | 21.81 | 6.70 | 0.008543 | 12.80 | 0.008500 | 0.000096 | 0.363430 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 21.81 | 6.70 | 0.008612 | 12.80 | 0.008500 | 0.000410 | 1.53 | |
FLR_3_DOAS COOLING COIL | 35.10 | 6.70 | 0.005699 | 11.74 | 0.005699 | 0.001379 | 2.05 | 48199.93 |
VAV WITH REHEAT COOLING COIL | 28.91 | 6.70 | 0.007895 | 10.58 | 0.007895 | 0.013938 | 26.33 | 487346.86 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
VAV WITH REHEAT | 13.24 | 11.65 | 26.48 | 11.65 | 26.33 | 26.33 | 0.300000 | 0.442510 | 26.33 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
VAV WITH REHEAT_OA_CONTROLLER | 26.33 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
FLR_3_DOAS OA HEAT RECOVERY | 2.05 |
VAV WITH REHEAT OA HEAT RECOVERY | 11.66 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS FAN | 2.05 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.001379 | 0.000345 |
FLR_3_DOAS_HEATC_CONTROLLER | 0.000132 | |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.013938 | 0.000034 |
VAV WITH REHEAT_HEATC_CONTROLLER | 0.001692 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT FAN | 26.33 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.021354 | 3486.46 | |
HEATSYS1 PUMP | 0.003539 | 1065.70 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.003539 | 0.424643 |
COOLSYS1 | 0.021354 | 2.56 |
SWHSYS1 | 0.000375 | 0.045004 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 404494.63 | 404494.63 | 0.003539 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.021354 | 2413.80 |
SWHSYS1 PUMP | 0.000375 | 47.91 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.021354 | 746648.51 | 747346.94 | 85.20 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000375 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:37
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:37
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:37
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.70 | 7.00 | 2.10 | 2.60 | 4.30 | 8.80 | 13.90 | 17.80 | 23.20 | 25.60 | 24.10 | 20.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 | 35.04 | -106.62 | -7.00 | 1619.00 | 83328 | 0.9904 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 13.63 | 23.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.58 | 23.26 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.72 | 65.50 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.80 | 85.08 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.70 | 6.74 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.96 | 26.37 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.27 | 28.20 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 8.814 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 14.194 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 11.314 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 22.074 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 11.314 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 22.074 | No |
4 | MECH_FLR_1 | 164.24 | 2.7 | 61.932 | 1.615E-002 | 4.628 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 10.008 | No |
5 | STORAGE_FLR_1 | 94.76 | 2.0 | 46.451 | 2.153E-002 | 5.720 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 8.410 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 4.628 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 602.158 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 10.010 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 15.390 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 10.764 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.834 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 8.288 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 18.808 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 8.288 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 18.808 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 21.0 | 18.581 | 5.382E-002 | 7.104 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.104 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 8.288 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 18.808 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 10.010 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 77.830 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 10.010 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 77.830 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 11.410 | 515.227 | 2419.260 | 0.000 | 0.000 | 0.000 | 2945.897 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 22.2 | 18.581 | 5.382E-002 | 7.104 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.104 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | STORAGE_FLR_1 PEOPLE | BLDG_OCC_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.0 | 2.153E-002 | 46.451 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | CORRIDOR_FLR_3 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 21.0 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 21 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
21 | CORRIDOR_FLR_6 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 22.2 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
22 | MECH_FLR_1 PEOPLE | BLDG_OCC_SCH | MECH_FLR_1 | 164.24 | 2.7 | 2.7 | 1.615E-002 | 61.932 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 3 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_BASEMENT | BASEMENT | 1978.83 | 106.5 | 17441.963 | 8.814 | 163.776 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 17441.963 |
2 | RETAIL_1_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_1_FLR_1 | 67.07 | 10.8 | 758.849 | 11.314 | 70.076 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 758.849 |
3 | RETAIL_2_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_2_FLR_1 | 77.67 | 12.5 | 878.750 | 11.314 | 70.076 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 878.750 |
4 | MECH_FLR_1_LIGHTS | LTG_SCH_MECHANIC | MECH_FLR_1 | 164.24 | 2.7 | 760.196 | 4.628 | 286.650 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 760.196 |
5 | STORAGE_FLR_1_LIGHTS | LTG_SCH_STORAGE | STORAGE_FLR_1 | 94.76 | 2.0 | 542.017 | 5.720 | 265.695 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 542.017 |
6 | LAUNDRY_FLR_1_LIGHTS | LTG_SCH_LAUNDRY | LAUNDRY_FLR_1 | 78.04 | 8.4 | 361.204 | 4.628 | 43.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 361.204 |
7 | CAFE_FLR_1_LIGHTS | LTG_SCH_DINING | CAFE_FLR_1 | 188.86 | 142.3 | 1890.589 | 10.010 | 13.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1890.589 |
8 | LOBBY_FLR_1_LIGHTS | LTG_SCH_LOBBY | LOBBY_FLR_1 | 1308.19 | 422.4 | 14081.185 | 10.764 | 33.333 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14081.185 |
9 | ROOM_1_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_3 | 39.02 | 1.5 | 323.422 | 8.288 | 215.615 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.422 |
10 | ROOM_2_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_3 | 39.02 | 1.5 | 323.384 | 8.288 | 215.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.384 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 203.259 | 8.288 | 135.506 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 203.259 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 203.314 | 8.288 | 135.543 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 203.314 |
13 | ROOM_5_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_5_FLR_3 | 39.02 | 1.5 | 323.422 | 8.288 | 215.615 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.422 |
14 | ROOM_6_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_6_FLR_3 | 39.02 | 1.5 | 323.384 | 8.288 | 215.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.384 |
15 | CORRIDOR_FLR_3_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2766.397 | 7.104 | 132.003 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2766.397 |
16 | ROOM_1_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_6 | 39.02 | 1.5 | 323.422 | 8.288 | 215.615 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.422 |
17 | ROOM_2_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_6 | 39.02 | 1.5 | 323.384 | 8.288 | 215.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.384 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 203.314 | 8.288 | 135.543 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 203.314 |
19 | BANQUET_FLR_6_LIGHTS | LTG_SCH_DINING | BANQUET_FLR_6 | 331.66 | 249.9 | 3320.034 | 10.010 | 13.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3320.034 |
20 | DINING_FLR_6_LIGHTS | LTG_SCH_DINING | DINING_FLR_6 | 331.66 | 249.9 | 3320.034 | 10.010 | 13.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3320.034 |
21 | KITCHEN_FLR_6_LIGHTS | LTG_SCH_KITCHEN | KITCHEN_FLR_6 | 103.30 | 22.2 | 1178.676 | 11.410 | 53.003 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1178.676 |
22 | CORRIDOR_FLR_6_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_6 | 412.12 | 22.2 | 2927.804 | 7.104 | 132.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2927.804 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 2.7 | 883.628 | 5.380 | 333.193 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 254.902 | 2.690 | 124.952 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 457.500 | 4.429 | 20.573 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 457.500 | 457.500 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 285.000 | 2.759 | 12.816 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 285.000 | 285.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 2.390 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
6 | RES_ROOF | 19 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
7 | NONRES_EXT_WALL_GRD | 21 | 3 | 9 | 0.167 | 0.8203 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | NONRES_EXT_WALL_MID | 22 | 3 | 9 | 0.167 | 1.021 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | NONRES_EXT_WALL_TOP | 23 | 3 | 9 | 0.167 | 1.034 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | RES_EXT_WALL_MID | 25 | 3 | 9 | 0.167 | 0.9169 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | RES_EXT_WALL_TOP | 26 | 3 | 9 | 0.167 | 0.9299 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | NONRES_FLOOR | 30 | 3 | 7 | 0.167 | 0.2277 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
13 | NONRES_FLOOR_CEILING | 33 | 3 | 7 | 0.167 | 0.2277 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
14 | BASEMENT_FLOOR | 36 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
15 | BASEMENT_WALL_NORTH_CFACTOR | 39 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | BASEMENT_WALL_EAST_CFACTOR | 40 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | BASEMENT_WALL_SOUTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
18 | BASEMENT_WALL_WEST_CFACTOR | 42 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4184 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
10 | RES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
11 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
12 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.052 |
14 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8120 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7993 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | RES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9233 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
25 | RES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9080 |
26 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
27 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.131 |
28 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
29 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
30 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
31 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
32 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.131 |
33 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
34 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
35 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
39 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
40 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
41 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
42 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 2.3900722 | 2.3900722 | 2.3900722 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
21 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
22 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
23 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
24 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
25 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
26 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
27 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
28 | 9 | -0.15703352E-14 | 0.29012323E-16 | -0.15483104E-09 | 0.40370831E-16 |
29 | 8 | 0.22592825E-07 | 0.11106548E-12 | 0.38529762E-03 | -0.25688817E-09 |
30 | 7 | -0.12465369E-01 | 0.57225352E-08 | -0.23408026E-01 | 0.14173579E-03 |
31 | 6 | 0.41143163 | 0.19878644E-05 | 0.47726710 | -0.48194459E-02 |
32 | 5 | -5.2499075 | 0.74130146E-04 | -4.4810026 | 0.63919688E-01 |
33 | 4 | 33.265337 | 0.60571720E-03 | 21.595652 | -0.42560793 |
34 | 3 | -111.78466 | 0.13187857E-02 | -55.931065 | 1.5232626 |
35 | 2 | 197.68466 | 0.74115454E-03 | 78.156489 | -2.9095067 |
36 | 1 | -171.36898 | 0.79055603E-04 | -55.336681 | 2.7491709 |
37 | 0 | 57.057407 | 0.44959794E-06 | 15.545184 | |
38 | 9 | 0.14302076E-15 | 0.35792568E-16 | -0.14541430E-09 | -0.27421543E-17 |
39 | 8 | 0.21269444E-07 | 0.13686051E-12 | 0.37140784E-03 | -0.24184090E-09 |
40 | 7 | -0.12050952E-01 | 0.71525680E-08 | -0.22811354E-01 | 0.13702371E-03 |
41 | 6 | 0.40017121 | 0.24988627E-05 | 0.46767819 | -0.46867126E-02 |
42 | 5 | -5.1400200 | 0.93645327E-04 | -4.4073602 | 0.62557131E-01 |
43 | 4 | 32.779281 | 0.76858103E-03 | 21.307814 | -0.41915444 |
44 | 3 | -110.75053 | 0.16800125E-02 | -55.362013 | 1.5083221 |
45 | 2 | 196.65975 | 0.94749847E-03 | 77.634567 | -2.8932310 |
46 | 1 | -170.99041 | 0.10139533E-03 | -55.184883 | 2.7425359 |
47 | 0 | 57.057407 | 0.57877233E-06 | 15.570231 | |
48 | 9 | 0.33566835E-16 | 0.35384250E-16 | -0.14478218E-09 | -0.87565041E-18 |
49 | 8 | 0.21180494E-07 | 0.13854999E-12 | 0.37046393E-03 | -0.24082951E-09 |
50 | 7 | -0.12022754E-01 | 0.72481687E-08 | -0.22770744E-01 | 0.13670309E-03 |
51 | 6 | 0.39940498 | 0.25332696E-05 | 0.46702484 | -0.46776806E-02 |
52 | 5 | -5.1325420 | 0.94967185E-04 | -4.4023386 | 0.62464408E-01 |
53 | 4 | 32.746200 | 0.77967008E-03 | 21.288178 | -0.41871522 |
54 | 3 | -110.68014 | 0.17047184E-02 | -55.323188 | 1.5073051 |
55 | 2 | 196.58997 | 0.96166638E-03 | 77.598974 | -2.8921229 |
56 | 1 | -170.96463 | 0.10293464E-03 | -55.174560 | 2.7420841 |
57 | 0 | 57.057407 | 0.58770932E-06 | 15.571958 | |
58 | 9 | -0.29206544E-14 | 0.31488305E-16 | -0.15031727E-09 | 0.48064473E-16 |
59 | 8 | 0.21958778E-07 | 0.12356532E-12 | 0.37867817E-03 | -0.24967887E-09 |
60 | 7 | -0.12267989E-01 | 0.64094198E-08 | -0.23123879E-01 | 0.13949151E-03 |
61 | 6 | 0.40606866 | 0.22324768E-05 | 0.47270315 | -0.47562292E-02 |
62 | 5 | -5.1975737 | 0.83445227E-04 | -4.4459647 | 0.63270770E-01 |
63 | 4 | 33.033866 | 0.68326082E-03 | 21.458733 | -0.42253461 |
64 | 3 | -111.29222 | 0.14903991E-02 | -55.660391 | 1.5161481 |
65 | 2 | 197.19665 | 0.83899866E-03 | 77.908180 | -2.9017570 |
66 | 1 | -171.18874 | 0.89630080E-04 | -55.264364 | 2.7460119 |
67 | 0 | 57.057407 | 0.51068186E-06 | 15.557036 | |
68 | 9 | -0.29497736E-14 | 0.32939851E-16 | -0.14970570E-09 | 0.45584202E-16 |
69 | 8 | 0.21872815E-07 | 0.12523736E-12 | 0.37777579E-03 | -0.24870145E-09 |
70 | 7 | -0.12241065E-01 | 0.65023057E-08 | -0.23085114E-01 | 0.13918537E-03 |
71 | 6 | 0.40533708 | 0.22656711E-05 | 0.47208016 | -0.47476058E-02 |
72 | 5 | -5.1904345 | 0.84713026E-04 | -4.4411801 | 0.63182247E-01 |
73 | 4 | 33.002288 | 0.69384191E-03 | 21.440032 | -0.42211534 |
74 | 3 | -111.22504 | 0.15138688E-02 | -55.623419 | 1.5151774 |
75 | 2 | 197.13007 | 0.85240592E-03 | 77.874271 | -2.9006996 |
76 | 1 | -171.16415 | 0.91081681E-04 | -55.254501 | 2.7455809 |
77 | 0 | 57.057407 | 0.51907125E-06 | 15.558664 | |
78 | 7 | -0.14139450E-14 | -0.18802902E-16 | -0.22311785E-13 | 0.54375338E-15 |
79 | 6 | 0.16999971E-10 | 0.27590984E-11 | 0.52267399E-09 | -0.18616555E-10 |
80 | 5 | -0.63950587E-07 | 0.13451749E-07 | -0.21905428E-05 | 0.17144787E-06 |
81 | 4 | 0.72477507E-04 | 0.50724086E-05 | 0.17668371E-02 | -0.28223350E-03 |
82 | 3 | -0.10573811E-01 | 0.17927531E-03 | -0.21549182 | 0.43318087E-01 |
83 | 2 | 0.15010112 | 0.77388015E-03 | 2.8998331 | -0.61891034 |
84 | 1 | -0.37982851 | 0.49528818E-03 | -7.1368477 | 1.5694772 |
85 | 0 | 0.24168561 | 0.34021171E-05 | 4.4521969 | |
86 | 7 | -0.22311785E-13 | -0.18802902E-16 | -0.14139450E-14 | 0.54375338E-15 |
87 | 6 | 0.52267399E-09 | 0.27590984E-11 | 0.16999971E-10 | -0.18616555E-10 |
88 | 5 | -0.21905428E-05 | 0.13451749E-07 | -0.63950587E-07 | 0.17144787E-06 |
89 | 4 | 0.17668371E-02 | 0.50724086E-05 | 0.72477507E-04 | -0.28223350E-03 |
90 | 3 | -0.21549182 | 0.17927531E-03 | -0.10573811E-01 | 0.43318087E-01 |
91 | 2 | 2.8998331 | 0.77388015E-03 | 0.15010112 | -0.61891034 |
92 | 1 | -7.1368477 | 0.49528818E-03 | -0.37982851 | 1.5694772 |
93 | 0 | 4.4521969 | 0.34021171E-05 | 0.24168561 | |
94 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
95 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
96 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
97 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
98 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
99 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
100 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
101 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
102 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
103 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
104 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
105 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
106 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
107 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
108 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
109 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
110 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
111 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
112 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
113 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
114 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
115 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
116 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
117 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
118 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
119 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
120 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
121 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
122 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
123 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
124 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
125 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
126 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
127 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
128 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
129 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
130 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
131 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
132 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
133 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.38_SHGC_0.36 | 37 | 1 | VerySmooth | 2.159 | 2.159 | 1.000 | 0.361 | ||
2 | RESWINDOW_U_0.38_SHGC_0.36 | 38 | 1 | VerySmooth | 2.159 | 2.159 | 1.000 | 0.361 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 3.45900E-002 | 0.27318 | 0.51781 | 0.51781 | 0.39600 | 0.13802 | 0.18068 | 0.00000 | 0.84000 | 0.84000 | 0.11893 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 3.45900E-002 | 0.27318 | 0.51781 | 0.51781 | 0.39600 | 0.13802 | 0.18068 | 0.00000 | 0.84000 | 0.84000 | 0.11893 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | CAFE_FLR_1 | 1 | 0 |
2 | LOBBY_FLR_1 | 1 | 0 |
3 | BANQUET_FLR_6 | 1 | 0 |
4 | DINING_FLR_6 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | CAFE_FLR_1 | 0 | |
2 | LOBBY_FLR_1 | 0 | |
3 | BANQUET_FLR_6 | 0 | |
4 | DINING_FLR_6 | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH LAUNDRY G WATER HEATER | 1.1356 | 163316.0 | 11.511 | 0.4388 |
2 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.219 | 1.1187 |
3 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 2.2712 | 175842.6 | 5.775 | 0.3748 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 1.764E-002 | 2.631E-004 | 1.298E-004 | 0.239 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.811E-003 | 8.769E-005 | 2.388E-004 | 7.967E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 2.7 | 1.610E-002 | 9.800E-005 | 2.563E-004 | 8.904E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 9.287E-003 | 9.800E-005 | 2.127E-004 | 8.904E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 2.198E-002 | 2.816E-004 | 2.506E-004 | 0.256 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 3.900E-002 | 2.065E-004 | 1.137E-004 | 0.188 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 0.111 | 8.519E-005 | 1.629E-004 | 7.740E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 2.563E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 2.563E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 2.857E-003 | 1.165E-004 | 2.563E-004 | 0.138 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 2.858E-003 | 1.165E-004 | 2.563E-004 | 0.138 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 2.563E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 2.563E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 1.238E-002 | 3.180E-005 | 2.563E-004 | 3.755E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 1.297E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 1.297E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 5.239E-003 | 2.136E-004 | 1.165E-004 | 0.252 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 2.500E-002 | 7.539E-005 | 5.825E-005 | 8.904E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 2.500E-002 | 7.539E-005 | 5.825E-005 | 8.904E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 2.238E-002 | 2.167E-004 | 1.174E-004 | 0.256 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 2.191E-002 | 5.316E-005 | 4.403E-005 | 6.278E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1396 |
2 | Clear Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 6.6122E-002 |
3 | Clear Turbid Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1557 |
4 | Clear Turbid Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 7.3070E-002 |
5 | Intermediate Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1038 |
6 | Intermediate Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 3.9477E-002 |
7 | Overcast Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 4.1657E-002 |
8 | Overcast Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 1.3839E-002 |
9 | Clear Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1583 |
10 | Clear Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 8.0437E-002 |
11 | Clear Turbid Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1770 |
12 | Clear Turbid Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 8.8740E-002 |
13 | Intermediate Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1149 |
14 | Intermediate Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 4.9604E-002 |
15 | Overcast Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 4.6776E-002 |
16 | Overcast Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 1.8924E-002 |
17 | Clear Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 3.3896E-002 |
18 | Clear Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.9493E-002 |
19 | Clear Turbid Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.6047E-002 |
20 | Clear Turbid Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.4692E-002 |
21 | Intermediate Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.5028E-002 |
22 | Intermediate Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.0023E-002 |
23 | Overcast Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 4.1005E-002 |
24 | Overcast Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.4540E-002 |
25 | Clear Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 3.3896E-002 |
26 | Clear Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.9493E-002 |
27 | Clear Turbid Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.6047E-002 |
28 | Clear Turbid Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.4692E-002 |
29 | Intermediate Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.5028E-002 |
30 | Intermediate Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.0023E-002 |
31 | Overcast Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 4.1005E-002 |
32 | Overcast Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.4540E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 34678.15768 | 34678.15768 | 3.06347 | 3.06347 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 20:00:00 | 28.35000 | 5.68899E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 0.85446 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
3 | RETAIL_1_FLR_1 | Cooling | 4575.37980 | 4575.37980 | 0.40422 | 0.40422 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 34.76250 | 5.69886E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 2371.08667 | 2371.08667 | 0.12356 | 0.12356 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 3138.09090 | 3138.09090 | 0.27725 | 0.27725 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 32.98500 | 5.69610E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 786.58667 | 786.58667 | 4.09918E-002 | 9.17347E-002 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 2559.22282 | 2559.22282 | 0.22605 | 0.22605 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 29.09250 | 5.69012E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 1396.64764 | 1396.64764 | 7.27842E-002 | 7.27842E-002 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 1541.57715 | 1541.57715 | 0.13617 | 0.13617 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 32.08500 | 5.69471E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 969.66104 | 969.66104 | 5.05324E-002 | 5.77652E-002 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 44754.80192 | 44754.80192 | 3.95353 | 3.95353 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 34.83000 | 5.69897E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 1870.48660 | 1870.48660 | 9.74761E-002 | 9.74761E-002 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 19692.00515 | 19692.00515 | 1.74134 | 1.74134 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 34.76250 | 5.69886E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 6023.41929 | 6023.41929 | 0.31390 | 0.67639 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 64913.11563 | 64913.11563 | 5.73688 | 5.73688 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 34.87500 | 5.69904E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 13821.03744 | 13821.03744 | 0.72026 | 1.89399 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 11662.42048 | 11662.42048 | 1.38823 | 1.38823 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 33.39000 | 5.69673E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 5181.23637 | 5181.23637 | 0.27159 | 0.27159 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 11538.63688 | 11538.63688 | 1.37350 | 1.37350 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 33.21000 | 5.69645E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 5180.98506 | 5180.98506 | 0.27158 | 0.27158 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 63605.41939 | 63605.41939 | 7.57095 | 7.57095 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 34.87500 | 5.69904E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 29953.61358 | 29953.61358 | 1.57016 | 1.57016 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 63759.58906 | 63759.58906 | 7.58994 | 7.58994 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 31.52250 | 5.69384E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 29963.19618 | 29963.19618 | 1.57066 | 1.57066 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 10343.33338 | 10343.33338 | 1.23122 | 1.23122 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 29.20500 | 5.69029E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 5181.23637 | 5181.23637 | 0.27159 | 0.27159 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 10256.28428 | 10256.28428 | 1.22085 | 1.22085 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 28.82250 | 5.68971E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 5180.98506 | 5180.98506 | 0.27158 | 0.27158 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 20640.20194 | 20640.20194 | 1.82330 | 1.82330 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 35.10000 | 5.69938E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 8445.78341 | 8445.78341 | 0.44014 | 0.47476 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 3091.45222 | 3091.45222 | 0.36799 | 0.36799 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 33.39000 | 5.69673E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 1601.27991 | 1601.27991 | 8.39373E-002 | 8.39373E-002 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 3053.14307 | 3053.14307 | 0.36343 | 0.36343 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 33.21000 | 5.69645E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 1602.15078 | 1602.15078 | 8.39829E-002 | 8.39829E-002 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 12828.20887 | 12828.20887 | 1.52705 | 1.52705 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 34.98750 | 5.69921E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 7700.37053 | 7700.37053 | 0.40365 | 0.40365 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 29997.97972 | 29997.97972 | 2.65352 | 2.65352 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 35.10000 | 5.69938E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 5411.34583 | 5411.34583 | 0.28200 | 1.18780 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 31433.29022 | 31433.29022 | 2.78044 | 2.78044 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 35.10000 | 5.69938E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
40 | DINING_FLR_6 | Heating | 5533.00218 | 5533.00218 | 0.28834 | 1.18780 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | -7.90000 | 2.34317E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 30960.50493 | 30960.50493 | 2.74265 | 2.74265 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 33.88500 | 5.69749E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 1539.26205 | 1539.26205 | 8.02058E-002 | 0.36735 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | -7.90000 | 2.34317E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
43 | CORRIDOR_FLR_6 | Cooling | 10701.16761 | 10701.16761 | 0.94530 | 0.94530 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 35.10000 | 5.69938E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 5728.05847 | 5728.05847 | 0.29851 | 0.29851 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 19:30:00 | -7.90000 | 2.34317E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | FLR_3_DOAS | Cooling | Sensible | 45524.16 | 21.37636 | 2.05125 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | FLR_3_DOAS | Heating | Sensible | 50219.47 | 4.79873 | 2.05125 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
3 | VAV WITH REHEAT | Cooling | Sensible | 422183.36 | 26.33394 | 26.33394 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | VAV WITH REHEAT | Heating | Sensible | 180787.07 | 7.38436 | 7.38436 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:50:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.06347 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.49221 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.44000 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.34793 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 7.74061E-004 |
8 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.12103E-005 |
9 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.34793 |
10 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 5853.65022 |
13 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.12103E-005 |
14 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 122.06778 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.40422 |
16 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12644 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.44000 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17786 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.44000 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.01339E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.74975E-005 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.17786 |
24 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3143.13216 |
27 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.74975E-005 |
28 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 78.23050 |
29 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.27725 |
30 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21347 |
31 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.44000 |
32 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.12199 |
33 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.56924 |
34 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.78483E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.15139E-005 |
37 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.12199 |
38 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1316.10836 |
41 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.15139E-005 |
42 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 29.75207 |
43 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.22605 |
44 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.55364 |
45 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.44000 |
46 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 9.94639E-002 |
47 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.88170E-004 |
50 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.59950E-005 |
51 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 9.94639E-002 |
52 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1828.32514 |
55 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.59950E-005 |
56 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 45.99195 |
57 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.13617 |
58 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.53028 |
59 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.44000 |
60 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 5.99138E-002 |
61 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 7.18493E-004 |
64 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.07581E-005 |
65 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.99138E-002 |
66 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1229.71412 |
69 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.07581E-005 |
70 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 31.96735 |
71 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.95353 |
72 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 1.50413E-002 |
73 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.44000 |
74 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.73955 |
75 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.44000 |
76 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.53303E-002 |
78 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.24091E-005 |
79 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.73955 |
80 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9419.86189 |
83 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.24091E-005 |
84 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 198.98460 |
85 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.74134 |
86 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.26447E-002 |
87 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.44000 |
88 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.76619 |
89 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.44000 |
90 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.61010E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.17933E-005 |
93 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.76619 |
94 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9349.47863 |
97 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.17933E-005 |
98 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 215.37964 |
99 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.73688 |
100 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17376 |
101 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.44000 |
102 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.52423 |
103 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46336 |
104 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
105 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.19269E-003 |
106 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.16770E-004 |
107 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.52423 |
108 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
110 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 24778.18843 |
111 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.16770E-004 |
112 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 553.05984 |
113 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
114 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.38823 |
115 | Fan:OnOff | ROOM_1_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 1.38823 |
116 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.53272E-005 |
117 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.65958E-004 |
118 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.80675 |
119 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
120 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.54490E-003 |
121 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
122 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
123 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.65958E-004 |
124 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.38823 |
125 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 5181.17502 |
126 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.53272E-005 |
127 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 148.04000 |
128 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
129 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.37350 |
130 | Fan:OnOff | ROOM_2_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 1.37350 |
131 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.53250E-005 |
132 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.62120E-004 |
133 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.80675 |
134 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
135 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.54536E-003 |
136 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
137 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
138 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.62120E-004 |
139 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.37350 |
140 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 5180.92371 |
141 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.53250E-005 |
142 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 148.03282 |
143 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83707 |
144 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 7.57095 |
145 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 7.57095 |
146 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.62046E-004 |
147 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.97136E-003 |
148 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.80716 |
149 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
150 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.48118E-003 |
151 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
152 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.48118E-003 |
153 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.97136E-003 |
154 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 7.57095 |
155 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 29953.44138 |
156 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.62046E-004 |
157 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 855.84218 |
158 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83730 |
159 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 7.58994 |
160 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 7.58994 |
161 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.62130E-004 |
162 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.08812E-003 |
163 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.80618 |
164 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
165 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.70490E-003 |
166 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
167 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
168 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.08812E-003 |
169 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 7.58994 |
170 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 29963.02392 |
171 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.62130E-004 |
172 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 856.11597 |
173 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
174 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.23122 |
175 | Fan:OnOff | ROOM_5_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 1.23122 |
176 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.53272E-005 |
177 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.25034E-004 |
178 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.80674 |
179 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
180 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.55018E-003 |
181 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
182 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
183 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.25034E-004 |
184 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.23122 |
185 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 5181.17502 |
186 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.53272E-005 |
187 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 148.04000 |
188 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
189 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.22085 |
190 | Fan:OnOff | ROOM_6_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 1.22085 |
191 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.53250E-005 |
192 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.22335E-004 |
193 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.80674 |
194 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
195 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.55059E-003 |
196 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
197 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
198 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.22335E-004 |
199 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.22085 |
200 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 5180.92371 |
201 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.53250E-005 |
202 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 148.03282 |
203 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.82330 |
204 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.65096 |
205 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.44000 |
206 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.80225 |
207 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.85285E-004 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.04357E-004 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.80225 |
212 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
213 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
214 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11928.62008 |
215 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.04357E-004 |
216 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 285.07697 |
217 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54338E-002 |
218 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.36799 |
219 | Fan:OnOff | ROOM_1_FLR_6 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 0.36799 |
220 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.40085E-005 |
221 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 9.69415E-005 |
222 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.80675 |
223 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
224 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.54240E-003 |
225 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
226 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
227 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 9.69415E-005 |
228 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.36799 |
229 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1601.26178 |
230 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.40085E-005 |
231 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 45.75120 |
232 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54319E-002 |
233 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.36343 |
234 | Fan:OnOff | ROOM_2_FLR_6 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 0.36343 |
235 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.40162E-005 |
236 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 9.57536E-005 |
237 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.80675 |
238 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
239 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.54292E-003 |
240 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
241 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
242 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 9.57536E-005 |
243 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.36343 |
244 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1602.13264 |
245 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.40162E-005 |
246 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 45.77608 |
247 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 9.91540E-002 |
248 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.52705 |
249 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 1.52705 |
250 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 6.73656E-005 |
251 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.09860E-004 |
252 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.80640 |
253 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
254 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.61151E-003 |
255 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
256 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
257 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.09860E-004 |
258 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.52705 |
259 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 7700.30074 |
260 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.73656E-005 |
261 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 220.01191 |
262 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.65352 |
263 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.52406E-002 |
264 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.44000 |
265 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.16755 |
266 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.44000 |
267 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
268 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.00040E-003 |
269 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.16864E-005 |
270 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.16755 |
271 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
272 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
273 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10480.31735 |
274 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.16864E-005 |
275 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 231.40730 |
276 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.78044 |
277 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.08933E-002 |
278 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.44000 |
279 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.22339 |
280 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.44000 |
281 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
282 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.19173E-003 |
283 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.48703E-005 |
284 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.22339 |
285 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
286 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
287 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10844.25527 |
288 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.48703E-005 |
289 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 239.09967 |
290 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.74265 |
291 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 5.16232E-002 |
292 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.44000 |
293 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.20677 |
294 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.44000 |
295 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
296 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.32746E-002 |
297 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.91627E-005 |
298 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.20677 |
299 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
300 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
301 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6762.66501 |
302 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.91627E-005 |
303 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 143.18203 |
304 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.94530 |
305 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.33221 |
306 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.44000 |
307 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.41593 |
308 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.88589 |
309 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
310 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.14687E-003 |
311 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.59098E-005 |
312 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.41593 |
313 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
314 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
315 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7533.89617 |
316 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.59098E-005 |
317 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 188.75324 |
318 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05132 |
319 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05132 |
320 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05132 |
321 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05132 |
322 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05132 |
323 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05132 |
324 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
325 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
326 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 13.24207 |
327 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 11.65302 |
328 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 26.48414 |
329 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 11.65302 |
330 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 26.33394 |
331 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 26.33394 |
332 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
333 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.44251 |
334 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05132 |
335 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 26.33394 |
336 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05132 |
337 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05125 |
338 | HeatExchanger:AirToAir:SensibleAndLatent | FLR_3_DOAS OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.05125 |
339 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 35.10000 |
340 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
341 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.73601 |
342 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 5.69938E-003 |
343 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 5.69938E-003 |
344 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Coil Load [W] | 48199.92810 |
345 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.37851E-003 |
346 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 2.05132 |
347 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Rated Capacity [W] | 15066.37152 |
348 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.31807E-004 |
349 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 252.12846 |
350 | Fan:ConstantVolume | FLR_3_DOAS FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05125 |
351 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.37851E-003 |
352 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 3.45438E-004 |
353 | Controller:WaterCoil | FLR_3_DOAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.31807E-004 |
354 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 26.33394 |
355 | HeatExchanger:AirToAir:SensibleAndLatent | VAV WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 11.66146 |
356 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 28.90890 |
357 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
358 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.58097 |
359 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.89537E-003 |
360 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.89537E-003 |
361 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 487346.85667 |
362 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.39381E-002 |
363 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 26.33394 |
364 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 193415.68421 |
365 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.69208E-003 |
366 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 3236.71812 |
367 | Fan:VariableVolume | VAV WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 26.33394 |
368 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.39381E-002 |
369 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 3.41648E-005 |
370 | Controller:WaterCoil | VAV WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.69208E-003 |
371 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 2.13541E-002 |
372 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 3486.46431 |
373 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 3.53870E-003 |
374 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.42464 |
375 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 3.53870E-003 |
376 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 1065.69967 |
377 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
378 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 404494.62648 |
379 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 404494.63000 |
380 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 3.53870E-003 |
381 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 2.13541E-002 |
382 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 2.56249 |
383 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 2.13541E-002 |
384 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 2413.79683 |
385 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 2.13541E-002 |
386 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 746648.50695 |
387 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 747346.94000 |
388 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 85.19755 |
389 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
390 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
391 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
392 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
393 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | 5884.40 |
2 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 3157.57 |
3 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1322.60 |
4 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | 1836.67 |
5 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | 1235.14 |
6 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 9468.96 |
7 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | 9395.08 |
8 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | 24901.48 |
9 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | 5582.52 |
10 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | 5582.25 |
11 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 32273.59 |
12 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 32283.91 |
13 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | 5582.52 |
14 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | 5582.25 |
15 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 11984.84 |
16 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | 1725.27 |
17 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | 1726.21 |
18 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 8296.65 |
19 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | 10532.84 |
20 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | 10898.66 |
21 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | 6797.87 |
22 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 7568.36 |
23 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | 11009.80 |
24 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | 141339.12 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | 14756.27 | 11468.87 | 3287.40 | 0.78 | 1270.38 | 12.88 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | 14601.23 | 11348.10 | 3253.14 | 0.78 | 1257.05 | 12.75 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 85296.21 | 67348.59 | 17947.63 | 0.79 | 8226.62 | 83.44 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 83714.49 | 64513.10 | 19201.40 | 0.77 | 7250.01 | 73.53 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | 13103.62 | 10181.51 | 2922.12 | 0.78 | 1128.32 | 11.44 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | 12994.61 | 10096.58 | 2898.03 | 0.78 | 1118.95 | 11.35 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | 3909.25 | 3038.76 | 870.49 | 0.78 | 336.52 | 3.41 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | 3861.28 | 3001.38 | 859.89 | 0.78 | 332.40 | 3.37 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 16487.06 | 12768.48 | 3718.58 | 0.77 | 1422.90 | 14.43 |
10 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | 45555.12 | 28738.39 | 16816.73 | 0.63 | 4996.71 | 50.68 |
11 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | 695927.60 | 417064.40 | 278863.20 | 0.60 | 325179.71 | 3298.15 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 4.09 | 13.95 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.419 | 0.394 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.419 | 0.394 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.820 | 0.731 | 22.63 | 45.89 | 22.63 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 23.26 | 23.26 | 23.26 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.820 | 0.731 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.820 | 0.731 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.820 | 0.731 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.820 | 0.731 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 2.390 | 2.390 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.820 | 0.731 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.820 | 0.731 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.820 | 0.731 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.820 | 0.731 | 63.73 | 129.23 | 63.73 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 65.50 | 65.50 | 65.50 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.820 | 0.731 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.820 | 0.731 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.820 | 0.731 | 82.79 | 167.88 | 82.79 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 85.08 | 85.08 | 85.08 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.820 | 0.731 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.917 | 0.806 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.917 | 0.806 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.917 | 0.806 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.917 | 0.806 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.917 | 0.806 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.917 | 0.806 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.917 | 0.806 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.917 | 0.806 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.917 | 0.806 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.917 | 0.806 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.021 | 0.886 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.021 | 0.886 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.021 | 0.886 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.021 | 0.886 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.930 | 0.816 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.930 | 0.816 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.930 | 0.816 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.930 | 0.816 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.930 | 0.816 | 13.70 | 20.44 | 13.70 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 6.74 | 6.74 | 6.74 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.034 | 0.896 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.034 | 0.896 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.034 | 0.896 | 16.77 | 21.37 | 16.77 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.034 | 0.896 | 34.86 | 52.03 | 34.86 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 17.17 | 17.17 | 17.17 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.034 | 0.896 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.034 | 0.896 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.034 | 0.896 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.034 | 0.896 | 34.86 | 52.03 | 34.86 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 17.17 | 17.17 | 17.17 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 9.8532202174E-003 | 1.9127023079E-002 | Pass | Pass | 1.2771993760E-002 | 2.4320982313E-002 | Pass | Pass |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.8253218533E-002 | 8.0391801619E-002 | Pass | Pass | 2.6832844504E-002 | 3.1897593754E-002 | Pass | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.4213391824E-002 | 2.5022694971E-002 | Pass | Pass | 8.4266637851E-003 | 1.1687469271E-002 | Pass | Pass |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.3831659430E-002 | 1.3426565075E-002 | Pass | Pass | 8.7814656394E-003 | 1.2970130439E-002 | Pass | Pass |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.2057848966E-002 | 8.4064780463E-003 | Pass | Pass | 9.0755920017E-003 | 1.3319128414E-002 | Pass | Pass |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.5708149039E-002 | 0.1344423782 | Pass | Pass | 2.0366368697E-002 | 5.3731519953E-002 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.5952944944E-002 | 5.0519262832E-002 | Pass | Pass | 1.9826611039E-002 | 2.5597898069E-002 | Pass | Pass |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.5744601689E-002 | 2.8915122786E-002 | Pass | Pass | 1.3793058891E-002 | 2.2261826447E-002 | Pass | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 6.6834243778E-002 | 0.2365373565 | Pass | Pass | 0.1566502560 | 0.2527291483 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 5.1177378855E-002 | 0.1857563458 | Pass | Pass | 0.9060006400 | 9.3718049701 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.2682585555E-003 | 2.7819266643E-002 | Pass | Pass | 7.5348718540E-002 | 0.1875547167 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 2.6142063613E-002 | 8.2319478361E-002 | Pass | Pass | 0.2722708026 | 1.1989725195 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 7.9091131154E-002 | 0.2762154788 | Pass | Pass | 0.5247949942 | 3.4765831688 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.7710317672E-002 | 0.1753798169 | Pass | Pass | 0.6626877702 | 4.5721973316 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 1.5159727229E-002 | 1.1187147906E-002 | Pass | Pass | 8.5496743640E-003 | 1.1893585177E-002 | Pass | Pass |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 5.3900992153E-002 | 0.2044864843 | Pass | Pass | 0.1243189942 | 0.2255247557 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 6.9516682906E-002 | 0.2201012943 | Pass | Pass | 0.1374404359 | 0.3901574636 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 0.1140839580 | 0.2856631221 | Pass | Pass | 0.1435604816 | 0.3621977435 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 1.6362119155E-002 | 3.8311680401E-002 | Pass | Pass | 1.6094514812E-002 | 4.3716031501E-002 | Pass | Pass |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 1.0697588031E-002 | 2.8345469999E-002 | Pass | Pass | 1.5766112561E-002 | 4.1814602999E-002 | Pass | Pass |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 1.3453955595E-002 | 4.2052717851E-002 | Pass | Pass | 2.1766421469E-002 | 4.2737417562E-002 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 2.7731100482E-002 | 2.1628062968E-002 | Pass | Pass | 1.0464377001E-002 | 1.1910910332E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:37
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 5170.18 | 51.21 | 1297.42 | 6390.44 | 4468.42 | 17377.69 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:37
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | -7.90 | 0.00 | -7.90 | Wetbulb [C] | 3.20 | 0.00 |
ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 35.10 | 13.50 | 15.70 | Wetbulb [C] | 4.40 | 220.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 9.00 | 6 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 5.00 | 4 | |||
Nov | 9.00 | 7 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:37
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 211.13 | 211.13 | 0.00 | 90.00 | N |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.399 | 0.419 | 55.76 | 55.76 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 211.13 | 211.13 | 180.00 | 90.00 | S |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.399 | 0.419 | 55.76 | 55.76 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.731 | 0.820 | 45.89 | 22.63 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.731 | 0.820 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.731 | 0.820 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.731 | 0.820 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.731 | 0.820 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.731 | 0.820 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.731 | 0.820 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.731 | 0.820 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.731 | 0.820 | 129.23 | 63.73 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.731 | 0.820 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.731 | 0.820 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.731 | 0.820 | 167.88 | 82.79 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.731 | 0.820 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.806 | 0.917 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.806 | 0.917 | 104.06 | 69.72 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.806 | 0.917 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.806 | 0.917 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.806 | 0.917 | 847.14 | 567.58 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.806 | 0.917 | 847.37 | 567.71 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.806 | 0.917 | 104.06 | 69.72 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.806 | 0.917 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.806 | 0.917 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.806 | 0.917 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 26.02 | 17.43 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.816 | 0.930 | 13.94 | 9.34 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.816 | 0.930 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | RES_ROOF | 0.23 | 0.182 | 0.186 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | RES_EXT_WALL_TOP | 0.30 | 0.816 | 0.930 | 13.94 | 9.34 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.816 | 0.930 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | RES_ROOF | 0.23 | 0.182 | 0.186 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.816 | 0.930 | 183.96 | 123.26 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | RES_ROOF | 0.23 | 0.182 | 0.186 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 97.55 | 65.36 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 97.55 | 65.36 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 21.37 | 16.77 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 52.03 | 34.86 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 13.94 | 9.34 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 17.65 | 11.83 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 52.03 | 34.86 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 167.42 | 167.42 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_FLOOR | BASEMENT_FLOOR | 0.30 | 1.441 | 2.705 | 1978.83 | 1978.83 | 0.00 | 180.00 | |
BASEMENT_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 67.07 | 67.07 | 180.00 | 0.00 | |
BASEMENT_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 77.67 | 77.67 | 180.00 | 0.00 | |
BASEMENT_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 164.24 | 164.24 | 180.00 | 0.00 | |
BASEMENT_CEILING_4 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 94.76 | 94.76 | 180.00 | 0.00 | |
BASEMENT_CEILING_5 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 78.04 | 78.04 | 180.00 | 0.00 | |
BASEMENT_CEILING_6 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 188.86 | 188.86 | 180.00 | 0.00 | |
BASEMENT_CEILING_7 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 1088.56 | 1088.56 | 180.00 | 0.00 | |
BASEMENT_CEILING_8 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 219.63 | 219.63 | 90.00 | 0.00 | |
RETAIL_1_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_1_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
RETAIL_1_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 67.07 | 67.07 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
RETAIL_2_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_2_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 90.00 | 90.00 | E |
RETAIL_2_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 77.67 | 77.67 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 77.67 | 77.67 | 180.00 | 0.00 | |
MECH_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
MECH_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 180.00 | 90.00 | S |
MECH_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
MECH_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 164.24 | 164.24 | 0.00 | 180.00 | |
MECH_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 164.24 | 164.24 | 180.00 | 0.00 | |
STORAGE_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
STORAGE_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 180.00 | 90.00 | S |
STORAGE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
STORAGE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 94.76 | 94.76 | 0.00 | 180.00 | |
STORAGE_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 94.76 | 94.76 | 180.00 | 0.00 | |
LAUNDRY_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 180.00 | 90.00 | S |
LAUNDRY_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 270.00 | 90.00 | W |
LAUNDRY_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 78.04 | 78.04 | 0.00 | 180.00 | |
LAUNDRY_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 78.04 | 78.04 | 180.00 | 0.00 | |
CAFE_FLR_1_WALL_1_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_2_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
CAFE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 188.86 | 188.86 | 0.00 | 180.00 | |
LOBBY_FLR_1_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 90.00 | 90.00 | E |
LOBBY_FLR_1_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 1088.56 | 1088.56 | 180.00 | 180.00 | |
LOBBY_FLR_1_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 219.63 | 219.63 | 90.00 | 180.00 | |
LOBBY_FLR_1_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 1062.83 | 1062.83 | 270.00 | 0.00 | |
ROOM_1_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_1_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
ROOM_1_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_1_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_2_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
ROOM_2_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_2_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_2_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 156.07 | 156.07 | 180.00 | 0.00 | |
ROOM_3_MULT19_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.14 | 847.14 | 0.00 | 90.00 | N |
ROOM_3_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_3_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 1863.81 | 1863.81 | 0.00 | 180.00 | |
ROOM_3_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 1863.81 | 1863.81 | 180.00 | 0.00 | |
ROOM_4_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_4_MULT19_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.37 | 847.37 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_4_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 1864.32 | 1864.32 | 0.00 | 180.00 | |
ROOM_4_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 1864.32 | 1864.32 | 180.00 | 0.00 | |
ROOM_5_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
ROOM_5_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_5_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_6_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
ROOM_6_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_6_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 156.07 | 156.07 | 180.00 | 0.00 | |
CORRIDOR_FLR_3_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.28 | 847.28 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_4_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.27 | 847.27 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 297.29 | 297.29 | 180.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 963.06 | 963.06 | 270.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_3 | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 297.26 | 297.26 | 90.00 | 180.00 | |
CORRIDOR_FLR_3_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 297.29 | 297.29 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 963.06 | 963.06 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 297.26 | 297.26 | 90.00 | 0.00 | |
ROOM_1_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 0.00 | 90.00 | N |
ROOM_1_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_1_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_2_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_2_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 180.00 | 90.00 | S |
ROOM_2_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_3_MULT9_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.96 | 183.96 | 0.00 | 90.00 | N |
ROOM_3_MULT9_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 90.00 | 90.00 | E |
ROOM_3_MULT9_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 270.00 | 90.00 | W |
ROOM_3_MULT9_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 220.77 | 220.77 | 0.00 | 180.00 | |
BANQUET_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
BANQUET_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
BANQUET_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
BANQUET_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 331.66 | 331.66 | 0.00 | 180.00 | |
DINING_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
DINING_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
DINING_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
DINING_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 331.66 | 331.66 | 0.00 | 180.00 | |
KITCHEN_FLR_6_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 7.43 | 7.43 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 103.30 | 103.30 | 180.00 | 180.00 | |
CORRIDOR_FLR_6_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 104.98 | 104.98 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_1_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.95 | 183.95 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 11.15 | 11.15 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 40.88 | 40.88 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 412.12 | 412.12 | 180.00 | 180.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3957.66 | 0.00 | 90.00 | N | ||
RETAIL_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 134.14 | 0.00 | 90.00 | N | ||
RETAIL_2_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 155.34 | 0.00 | 90.00 | N | ||
MECH_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 328.49 | 0.00 | 90.00 | N | ||
STORAGE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 189.52 | 0.00 | 90.00 | N | ||
LAUNDRY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 156.08 | 0.00 | 90.00 | N | ||
CAFE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 377.72 | 0.00 | 90.00 | N | ||
LOBBY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 2616.37 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3727.63 | 0.00 | 90.00 | N | ||
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3728.64 | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3115.24 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.04 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.03 | 0.00 | 90.00 | N | ||
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 441.55 | 0.00 | 90.00 | N | ||
BANQUET_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
DINING_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 206.61 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 824.25 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.36 | 23.26 | 0.00 | 0.00 | 23.26 | 23.26 | 2.159 | 0.361 | 0.397 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.36 | 65.50 | 0.00 | 0.00 | 65.50 | 65.50 | 2.159 | 0.361 | 0.397 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.36 | 85.08 | 0.00 | 0.00 | 85.08 | 85.08 | 2.159 | 0.361 | 0.397 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.38_SHGC_0.36 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.159 | 0.361 | 0.397 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.38_SHGC_0.36 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.159 | 0.361 | 0.397 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.38_SHGC_0.36 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.159 | 0.361 | 0.397 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.38_SHGC_0.36 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.159 | 0.361 | 0.397 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.38_SHGC_0.36 | 3.68 | 0.00 | 0.00 | 3.68 | 279.56 | 2.159 | 0.361 | 0.397 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.38_SHGC_0.36 | 3.68 | 0.00 | 0.00 | 3.68 | 279.65 | 2.159 | 0.361 | 0.397 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.38_SHGC_0.36 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.159 | 0.361 | 0.397 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.38_SHGC_0.36 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.159 | 0.361 | 0.397 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.38_SHGC_0.36 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.159 | 0.361 | 0.397 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.38_SHGC_0.36 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.159 | 0.361 | 0.397 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.36 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.159 | 0.361 | 0.397 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.36 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 2.159 | 0.361 | 0.397 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.36 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 2.159 | 0.361 | 0.397 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.36 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.159 | 0.361 | 0.397 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.38_SHGC_0.36 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.159 | 0.361 | 0.397 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.38_SHGC_0.36 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.159 | 0.361 | 0.397 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.38_SHGC_0.36 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.159 | 0.361 | 0.397 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.38_SHGC_0.36 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.159 | 0.361 | 0.397 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.38_SHGC_0.36 | 6.74 | 0.00 | 0.00 | 6.74 | 60.70 | 2.159 | 0.361 | 0.397 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.36 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.159 | 0.361 | 0.397 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.36 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.159 | 0.361 | 0.397 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.36 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.159 | 0.361 | 0.397 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.36 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.159 | 0.361 | 0.397 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | |||||||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.36 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.159 | 0.361 | 0.397 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.36 | 5.82 | 0.00 | 0.00 | 5.82 | 5.82 | 2.159 | 0.361 | 0.397 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.36 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 2.159 | 0.361 | 0.397 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.36 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.159 | 0.361 | 0.397 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 1213.79 | 2.159 | 0.361 | 0.397 | |||||||||||||||||
North Total or Average | 432.95 | 2.159 | 0.361 | 0.397 | |||||||||||||||||
Non-North Total or Average | 780.84 | 2.159 | 0.361 | 0.397 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 1.760 | 2.390 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:37
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:37
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 8.8143 | 1978.83 | 17441.96 | LightsWired | LTG_SCH_BASEMENT | 49.32 | 168.00 | 49.26 | 0.0000 | Y | 161.29 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | RETAIL_1_FLR_1 | GENERAL | 11.3140 | 67.07 | 758.85 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 7.31 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | RETAIL_2_FLR_1 | GENERAL | 11.3140 | 77.67 | 878.75 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 8.46 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | MECH_FLR_1 | GENERAL | 4.6285 | 164.24 | 760.20 | LightsWired | LTG_SCH_MECHANIC | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 8.37 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | STORAGE_FLR_1 | GENERAL | 5.7199 | 94.76 | 542.02 | LightsWired | LTG_SCH_STORAGE | 30.30 | 168.00 | 30.27 | 0.0000 | Y | 3.08 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | LAUNDRY_FLR_1 | GENERAL | 4.6285 | 78.04 | 361.20 | LightsWired | LTG_SCH_LAUNDRY | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 3.98 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | CAFE_FLR_1 | GENERAL | 10.0104 | 188.86 | 1890.59 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 39.50 | 0.0000 | Y | 14.02 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | LOBBY_FLR_1 | GENERAL | 10.7639 | 1308.19 | 14081.18 | LightsWired | LTG_SCH_LOBBY | 44.02 | 168.00 | 41.55 | 0.0000 | Y | 109.83 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | ROOM_1_FLR_3 | GENERAL | 8.2882 | 156.09 | 1293.69 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | ROOM_2_FLR_3 | GENERAL | 8.2882 | 156.07 | 1293.54 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | GENERAL | 8.2882 | 1863.81 | 15447.65 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 110.38 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | GENERAL | 8.2882 | 1864.32 | 15451.87 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 110.41 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | ROOM_5_FLR_3 | GENERAL | 8.2882 | 156.09 | 1293.69 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | ROOM_6_FLR_3 | GENERAL | 8.2882 | 156.07 | 1293.54 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | CORRIDOR_FLR_3 | GENERAL | 7.1042 | 1557.62 | 11065.59 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 91.33 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | ROOM_1_FLR_6 | GENERAL | 8.2882 | 39.02 | 323.42 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 2.31 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | ROOM_2_FLR_6 | GENERAL | 8.2882 | 39.02 | 323.38 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 2.31 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | GENERAL | 8.2882 | 220.77 | 1829.83 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 13.08 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | BANQUET_FLR_6 | GENERAL | 10.0104 | 331.66 | 3320.03 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 49.43 | 0.0000 | Y | 30.81 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | DINING_FLR_6 | GENERAL | 10.0104 | 331.66 | 3320.03 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 49.43 | 0.0000 | Y | 30.81 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | KITCHEN_FLR_6 | GENERAL | 11.4097 | 103.30 | 1178.68 | LightsWired | LTG_SCH_KITCHEN | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 12.97 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | CORRIDOR_FLR_6 | GENERAL | 7.1042 | 412.12 | 2927.80 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 24.17 |
Interior Lighting Total | 8.5566 | 11345.29 | 97077.49 | 456.14 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
LOBBY_FLR_1_DAYLREFPT1 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.07 | 14081.18 | 985.68 |
LOBBY_FLR_1_DAYLREFPT2 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.07 | 14081.18 | 985.68 |
CAFE_FLR_1_DAYLREFPT1 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1890.59 | 737.33 |
CAFE_FLR_1_DAYLREFPT2 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1890.59 | 737.33 |
DINING_FLR_6_DAYLREFPT1 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
DINING_FLR_6_DAYLREFPT2 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
BANQUET_FLR_6_DAYLREFPT1 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
BANQUET_FLR_6_DAYLREFPT2 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 12338.45 | AstronomicalClock | - | 83.71 | 83.71 | 193.87 | |
Exterior Lighting Total | 12338.45 | 193.87 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:37
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 404494.63 | 0.80 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 747346.94 | 2.96 | 747346.94 | 2.96 | 4.09 | 13.95 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 12796.05 | 14756.27 | 11468.87 | 3287.40 | 0.78 | - | 1270.38 | 12.88 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 12661.82 | 14601.23 | 11348.10 | 3253.14 | 0.78 | - | 1257.05 | 12.75 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 68930.43 | 85296.21 | 67348.59 | 17947.63 | 0.79 | - | 8226.62 | 83.44 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 73012.71 | 83714.49 | 64513.10 | 19201.40 | 0.77 | - | 7250.01 | 73.53 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 11365.10 | 13103.62 | 10181.51 | 2922.12 | 0.78 | - | 1128.32 | 11.44 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 11270.72 | 12994.61 | 10096.58 | 2898.03 | 0.78 | - | 1118.95 | 11.35 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3389.64 | 3909.25 | 3038.76 | 870.49 | 0.78 | - | 336.52 | 3.41 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3348.11 | 3861.28 | 3001.38 | 859.89 | 0.78 | - | 332.40 | 3.37 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 14331.10 | 16487.06 | 12768.48 | 3718.58 | 0.77 | - | 1422.90 | 14.43 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | 48199.93 | 45555.12 | 28738.39 | 16816.73 | 0.63 | - | 4996.71 | 50.68 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | 487346.86 | 695927.60 | 417064.40 | 278863.20 | 0.60 | - | 325179.71 | 3298.15 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 5853.65 | 5884.40 | - |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 3143.13 | 3157.57 | - |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1316.11 | 1322.60 | - |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1828.33 | 1836.67 | - |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1229.71 | 1235.14 | - |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 9419.86 | 9468.96 | - |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 9349.48 | 9395.08 | - |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 24778.19 | 24901.48 | - |
ROOM_1_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 5181.18 | 5582.52 | - |
ROOM_2_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 5180.92 | 5582.25 | - |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 29953.44 | 32273.59 | - |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 29963.02 | 32283.91 | - |
ROOM_5_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 5181.18 | 5582.52 | - |
ROOM_6_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 5180.92 | 5582.25 | - |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 11928.62 | 11984.84 | - |
ROOM_1_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 1601.26 | 1725.27 | - |
ROOM_2_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 1602.13 | 1726.21 | - |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 7700.30 | 8296.65 | - |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 10480.32 | 10532.84 | - |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 10844.26 | 10898.66 | - |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 6762.67 | 6797.87 | - |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 7533.90 | 7568.36 | - |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | 15066.37 | 11009.80 | - |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | 193415.68 | 141339.12 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 0.24 | 76.61 | 324.68 | 1.00 | 2.78 | General | ||
LOBBY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.24 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
ROOM_1_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 1.39 | 976.81 | 703.64 | 1.00 | 1.13 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 |
ROOM_2_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 1.37 | 966.44 | 703.64 | 1.00 | 1.13 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 7.57 | 5327.19 | 703.64 | 1.00 | 0.95 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 7.59 | 5340.56 | 703.64 | 1.00 | 0.95 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 |
ROOM_5_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 1.23 | 866.33 | 703.64 | 1.00 | 1.15 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 |
ROOM_6_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 1.22 | 859.04 | 703.64 | 1.00 | 1.15 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 |
ROOM_1_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 0.37 | 258.93 | 703.64 | 1.00 | 1.58 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 |
ROOM_2_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 0.36 | 255.72 | 703.64 | 1.00 | 1.59 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 1.53 | 1074.49 | 703.64 | 1.00 | 1.11 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 |
BANQUET_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
DINING_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 1.89 | 612.92 | 324.68 | 1.00 | 1.48 | General | ||
FLR_3_DOAS FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.93 | 1070.05 | 1.00 | 1.30 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
VAV WITH REHEAT FAN | Fan:VariableVolume | 0.62 | 1389.42 | 26.33 | 59004.84 | 2240.64 | 1.00 | 1.11 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.021354 | 3486.46 | 163269.44 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.003539 | 1065.70 | 301156.09 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.021354 | 2413.80 | 113036.94 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH LAUNDRY G WATER HEATER | WaterHeater:Mixed | 1.14 | 163316.00 | 0.80 | 11.51 | 0.44 |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.22 | 1.12 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.60 | 0.80 | 5.78 | 0.37 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:37
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 34678.16 | 34678.16 | 17.52 | 3.063 | 3.063 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 20:00:00 | 24.00 | 24.00 | 0.00920 | 28.35 | 0.00569 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 4575.38 | 4575.38 | 68.22 | 0.404 | 0.404 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 24.00 | 0.00900 | 34.76 | 0.00570 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 3138.09 | 3138.09 | 40.40 | 0.277 | 0.277 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 24.00 | 24.00 | 0.00938 | 32.98 | 0.00570 | 0.092 | 0.00 |
MECH_FLR_1 | 2559.22 | 2559.22 | 15.58 | 0.226 | 0.226 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 24.00 | 24.00 | 0.00868 | 29.09 | 0.00569 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1541.58 | 1541.58 | 16.27 | 0.136 | 0.136 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 24.00 | 24.00 | 0.00875 | 32.09 | 0.00569 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 44754.80 | 44754.80 | 573.49 | 3.954 | 3.954 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 24.00 | 24.00 | 0.00854 | 34.83 | 0.00570 | 0.000 | 0.00 |
CAFE_FLR_1 | 19692.01 | 19692.01 | 104.27 | 1.741 | 1.741 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 23.99 | 0.01011 | 34.76 | 0.00570 | 0.676 | 0.00 |
LOBBY_FLR_1 | 64913.12 | 64913.12 | 49.62 | 5.737 | 5.737 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 23.99 | 0.00995 | 34.88 | 0.00570 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 11662.42 | 11662.42 | 298.87 | 1.388 | 1.388 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 21.11 | 21.11 | 0.00854 | 33.39 | 0.00570 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 11538.64 | 11538.64 | 295.73 | 1.373 | 1.373 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 21.11 | 21.11 | 0.00855 | 33.21 | 0.00570 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 63605.42 | 63605.42 | 2593.62 | 7.571 | 7.571 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 21.11 | 21.11 | 0.00848 | 34.88 | 0.00570 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 63759.59 | 63759.59 | 2599.19 | 7.590 | 7.590 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 21.11 | 21.11 | 0.00870 | 31.52 | 0.00569 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 10343.33 | 10343.33 | 265.06 | 1.231 | 1.231 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 21.11 | 21.11 | 0.00855 | 29.21 | 0.00569 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 10256.28 | 10256.28 | 262.86 | 1.221 | 1.221 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 21.11 | 21.11 | 0.00855 | 28.82 | 0.00569 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 20640.20 | 20640.20 | 53.00 | 1.823 | 1.823 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 24.00 | 0.00940 | 35.10 | 0.00570 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 3091.45 | 3091.45 | 79.22 | 0.368 | 0.368 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 21.11 | 21.11 | 0.00854 | 33.39 | 0.00570 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 3053.14 | 3053.14 | 78.25 | 0.363 | 0.363 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 21.11 | 21.11 | 0.00854 | 33.21 | 0.00570 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 12828.21 | 12828.21 | 522.95 | 1.527 | 1.527 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 21.11 | 21.11 | 0.00861 | 34.99 | 0.00570 | 0.099 | 0.00 |
BANQUET_FLR_6 | 29997.98 | 29997.98 | 90.45 | 2.654 | 2.654 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 23.98 | 0.01037 | 35.10 | 0.00570 | 1.188 | 0.00 |
DINING_FLR_6 | 31433.29 | 31433.29 | 94.78 | 2.780 | 2.780 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 23.98 | 0.01029 | 35.10 | 0.00570 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 30960.50 | 30960.50 | 299.70 | 2.743 | 2.743 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 24.00 | 23.97 | 0.01007 | 33.89 | 0.00570 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 10701.17 | 10701.17 | 25.97 | 0.945 | 0.945 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00895 | 35.10 | 0.00570 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 0.854 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 22.76 | 0.00234 | -7.90 | 0.00234 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 2371.09 | 2371.09 | 35.35 | 0.124 | 0.124 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00779 | -7.90 | 0.00234 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 786.59 | 786.59 | 10.13 | 0.041 | 0.092 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00775 | -7.90 | 0.00234 | 0.092 | 0.00 |
MECH_FLR_1 | 1396.65 | 1396.65 | 8.50 | 0.073 | 0.073 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00768 | -7.90 | 0.00234 | 0.000 | 0.00 |
STORAGE_FLR_1 | 969.66 | 969.66 | 10.23 | 0.051 | 0.058 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00773 | -7.90 | 0.00234 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 1870.49 | 1870.49 | 23.97 | 0.097 | 0.097 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00767 | -7.90 | 0.00234 | 0.000 | 0.00 |
CAFE_FLR_1 | 6023.42 | 6023.42 | 31.89 | 0.314 | 0.676 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00781 | -7.90 | 0.00234 | 0.676 | 0.00 |
LOBBY_FLR_1 | 13821.04 | 13821.04 | 10.57 | 0.720 | 1.894 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00777 | -7.90 | 0.00234 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 5181.24 | 5181.24 | 132.78 | 0.272 | 0.272 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00777 | -7.90 | 0.00234 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 5180.99 | 5180.99 | 132.79 | 0.272 | 0.272 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00777 | -7.90 | 0.00234 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 29953.61 | 29953.61 | 1221.41 | 1.570 | 1.570 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00779 | -7.90 | 0.00234 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 29963.20 | 29963.20 | 1221.46 | 1.571 | 1.571 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00779 | -7.90 | 0.00234 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 5181.24 | 5181.24 | 132.78 | 0.272 | 0.272 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00777 | -7.90 | 0.00234 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 5180.99 | 5180.99 | 132.79 | 0.272 | 0.272 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00777 | -7.90 | 0.00234 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 8445.78 | 8445.78 | 21.69 | 0.440 | 0.475 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00783 | -7.90 | 0.00234 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 1601.28 | 1601.28 | 41.04 | 0.084 | 0.084 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00782 | -7.90 | 0.00234 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 1602.15 | 1602.15 | 41.06 | 0.084 | 0.084 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00782 | -7.90 | 0.00234 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 7700.37 | 7700.37 | 313.91 | 0.404 | 0.404 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00782 | -7.90 | 0.00234 | 0.099 | 0.00 |
BANQUET_FLR_6 | 5411.35 | 5411.35 | 16.32 | 0.282 | 1.188 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00787 | -7.90 | 0.00234 | 1.188 | 0.00 |
DINING_FLR_6 | 5533.00 | 5533.00 | 16.68 | 0.288 | 1.188 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | 21.00 | 21.00 | 0.00787 | -7.90 | 0.00234 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 1539.26 | 1539.26 | 14.90 | 0.080 | 0.367 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 21.00 | 21.00 | 0.00655 | -7.90 | 0.00234 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 5728.06 | 5728.06 | 13.90 | 0.299 | 0.299 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 19:30:00 | 21.00 | 21.00 | 0.00789 | -7.90 | 0.00234 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
FLR_3_DOAS | 21.38 | 2.05 | 4.80 | 2.05 | 2.0513 | 2.0513 | 2.0513 | 1.0000 | 0.3000 |
VAV WITH REHEAT | 26.33 | 26.33 | 7.38 | 7.38 | 26.3339 | 11.6530 | 26.3339 | 0.4425 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 5853.650 | 5853.650 | 1.347927 | 0.00005121 | 122.068 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 5853.65 | 5853.65 | 1.347927 | 16.70 | 11.36 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00800000 | 42.5367 | 0.00 | 0.00 | 5886.55 | 5886.55 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 3143.132 | 3143.132 | 0.177859 | 0.00002750 | 78.231 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3143.13 | 3143.13 | 0.177859 | 16.70 | 11.36 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00778608 | 41.4140 | 2371.09 | 0.00 | 3159.36 | 3159.36 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 1316.108 | 1316.108 | 0.121991 | 0.00001151 | 29.752 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1316.11 | 1316.11 | 0.121991 | 16.70 | 11.36 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00775258 | 41.2376 | 786.59 | 0.00 | 1323.21 | 1323.21 |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 1828.325 | 1828.325 | 0.099464 | 0.00001599 | 45.992 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1828.33 | 1828.33 | 0.099464 | 16.70 | 11.36 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00767533 | 40.8317 | 1396.65 | 0.00 | 1837.73 | 1837.73 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 1229.714 | 1229.714 | 0.059914 | 0.00001076 | 31.967 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1229.71 | 1229.71 | 0.059914 | 16.70 | 11.36 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00772758 | 41.1063 | 969.66 | 0.00 | 1235.90 | 1235.90 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 9419.862 | 9419.862 | 1.739553 | 0.00008241 | 198.985 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 9419.86 | 9419.86 | 1.739553 | 16.70 | 11.36 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00766944 | 40.8011 | 1870.49 | 0.00 | 9472.56 | 9472.56 |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 9349.479 | 9349.479 | 0.766191 | 0.00008179 | 215.380 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 9349.48 | 9349.48 | 0.766191 | 16.70 | 11.36 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00781294 | 41.5549 | 6023.42 | 0.00 | 9399.60 | 9399.60 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 24778.188 | 24778.188 | 2.524229 | 0.00021677 | 553.060 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 24778.19 | 24778.19 | 2.524229 | 16.70 | 11.36 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00776890 | 41.3233 | 13821.04 | 0.00 | 24912.55 | 24912.55 |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 12796.045 | -999.000 | 1.388233 | 0.00036596 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | 7/21 16:50:00 | 12796.05 | 12687.99 | 1.388233 | 21.81 | 13.68 | 0.00854490 | 12.80 | 10.33 | 0.00850000 | 33.39 | 0.00569673 | 15.22 | 0.0000 | 21.11 | 0.00854490 | 45.0870 | 11662.42 | 0.00 | 9568.84 | 9568.84 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 5181.175 | 5181.175 | 0.271594 | 0.00004533 | 148.040 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 5181.18 | 5181.18 | 0.271594 | 21.11 | 12.78 | 0.00777452 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.11 | 0.00777452 | 41.0723 | 5181.24 | 0.00 | 5585.47 | 5585.47 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 12661.817 | -999.000 | 1.373499 | 0.00036212 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | 7/21 17:00:00 | 12661.82 | 12553.81 | 1.373499 | 21.81 | 13.68 | 0.00854536 | 12.80 | 10.33 | 0.00850000 | 33.21 | 0.00569645 | 15.16 | 0.0000 | 21.11 | 0.00854536 | 45.0894 | 11538.64 | 0.00 | 9468.71 | 9468.71 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 5180.924 | 5180.924 | 0.271581 | 0.00004532 | 148.033 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 5180.92 | 5180.92 | 0.271581 | 21.11 | 12.78 | 0.00777453 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.11 | 0.00777453 | 41.0723 | 5180.99 | 0.00 | 5585.20 | 5585.20 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 68930.430 | -999.000 | 7.570947 | 0.00197136 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | unknown | 7/21 13:40:00 | 68930.43 | 68930.43 | 7.570947 | 21.81 | 13.62 | 0.00848118 | 12.80 | 10.32 | 0.00848118 | 34.88 | 0.00569904 | 15.70 | 0.0000 | 21.11 | 0.00848118 | 44.7544 | 63605.42 | 0.00 | 55322.05 | 55322.05 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 29953.441 | 29953.441 | 1.570156 | 0.00026205 | 855.842 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 29953.44 | 29953.44 | 1.570156 | 21.11 | 12.79 | 0.00779255 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.11 | 0.00779255 | 41.1660 | 29953.61 | 0.00 | 32290.82 | 32290.82 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 73012.705 | -999.000 | 7.589937 | 0.00208812 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | unknown | 7/21 18:10:00 | 73012.71 | 70281.18 | 7.589937 | 21.81 | 13.81 | 0.00870490 | 12.80 | 10.33 | 0.00850000 | 31.52 | 0.00569384 | 14.61 | 0.0000 | 21.11 | 0.00870490 | 45.9206 | 63759.59 | 0.00 | 55073.40 | 54116.97 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 29963.024 | 29963.024 | 1.570658 | 0.00026213 | 856.116 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 29963.02 | 29963.02 | 1.570658 | 21.11 | 12.79 | 0.00779256 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.11 | 0.00779256 | 41.1660 | 29963.20 | 0.00 | 32301.15 | 32301.15 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 11365.099 | -999.000 | 1.231216 | 0.00032503 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | unknown | 7/21 09:40:00 | 11365.10 | 11257.95 | 1.231216 | 21.81 | 13.68 | 0.00855018 | 12.80 | 10.33 | 0.00850000 | 29.21 | 0.00569029 | 13.82 | 0.0000 | 21.11 | 0.00855018 | 45.1145 | 10343.33 | 0.00 | 8501.25 | 8501.25 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 5181.175 | 5181.175 | 0.271594 | 0.00004533 | 148.040 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 5181.18 | 5181.18 | 0.271594 | 21.11 | 12.78 | 0.00777452 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.11 | 0.00777452 | 41.0723 | 5181.24 | 0.00 | 5585.47 | 5585.47 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 11270.720 | -999.000 | 1.220854 | 0.00032234 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | unknown | 7/21 09:30:00 | 11270.72 | 11163.59 | 1.220854 | 21.81 | 13.68 | 0.00855059 | 12.80 | 10.33 | 0.00850000 | 28.82 | 0.00568971 | 13.69 | 0.0000 | 21.11 | 0.00855059 | 45.1166 | 10256.28 | 0.00 | 8430.85 | 8430.85 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 5180.924 | 5180.924 | 0.271581 | 0.00004532 | 148.033 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 5180.92 | 5180.92 | 0.271581 | 21.11 | 12.78 | 0.00777453 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.11 | 0.00777453 | 41.0723 | 5180.99 | 0.00 | 5585.20 | 5585.20 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 11928.620 | 11928.620 | 0.802253 | 0.00010436 | 285.077 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 11928.62 | 11928.62 | 0.802253 | 16.70 | 11.36 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00782997 | 41.6440 | 8445.78 | 0.00 | 11991.09 | 11991.09 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 3389.642 | -999.000 | 0.367990 | 0.00009694 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | 7/21 16:50:00 | 3389.64 | 3362.60 | 0.367990 | 21.81 | 13.68 | 0.00854240 | 12.80 | 10.33 | 0.00850000 | 33.39 | 0.00569673 | 15.22 | 0.0000 | 21.11 | 0.00854240 | 45.0740 | 3091.45 | 0.00 | 2534.42 | 2534.42 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 1601.262 | 1601.262 | 0.083937 | 0.00001401 | 45.751 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1601.26 | 1601.26 | 0.083937 | 21.11 | 12.81 | 0.00781617 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.11 | 0.00781617 | 41.2896 | 1601.28 | 0.00 | 1726.21 | 1726.21 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 3348.106 | -999.000 | 0.363430 | 0.00009575 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | 7/21 17:00:00 | 3348.11 | 3321.07 | 0.363430 | 21.81 | 13.68 | 0.00854292 | 12.80 | 10.33 | 0.00850000 | 33.21 | 0.00569645 | 15.16 | 0.0000 | 21.11 | 0.00854292 | 45.0767 | 3053.14 | 0.00 | 2503.43 | 2503.43 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 1602.133 | 1602.133 | 0.083983 | 0.00001402 | 45.776 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1602.13 | 1602.13 | 0.083983 | 21.11 | 12.81 | 0.00781628 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.11 | 0.00781628 | 41.2902 | 1602.15 | 0.00 | 1727.15 | 1727.15 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 14331.100 | -999.000 | 1.527051 | 0.00040986 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | unknown | 7/21 13:50:00 | 14331.10 | 14034.26 | 1.527051 | 21.81 | 13.73 | 0.00861151 | 12.80 | 10.33 | 0.00850000 | 34.99 | 0.00569921 | 15.74 | 0.0000 | 21.11 | 0.00861151 | 45.4344 | 12828.21 | 0.00 | 10755.81 | 10755.81 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 7700.301 | 7700.301 | 0.403647 | 0.00006737 | 220.012 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 7700.30 | 7700.30 | 0.403647 | 21.11 | 12.82 | 0.00782373 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.11 | 0.00782373 | 41.3289 | 7700.37 | 0.00 | 8301.17 | 8301.17 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 10480.317 | 10480.317 | 1.167550 | 0.00009169 | 231.407 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 10480.32 | 10480.32 | 1.167550 | 16.70 | 11.36 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00786519 | 41.8292 | 5411.35 | 0.00 | 10537.39 | 10537.39 |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 10844.255 | 10844.255 | 1.223392 | 0.00009487 | 239.100 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | 10844.26 | 10844.26 | 1.223392 | 16.70 | 11.36 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00786809 | 41.8447 | 5533.00 | 0.00 | 10903.35 | 10903.35 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 6762.665 | 6762.665 | 1.206766 | 0.00005916 | 143.182 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 6762.67 | 6762.67 | 1.206766 | 16.70 | 11.36 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00655147 | 34.9210 | 1539.26 | 0.00 | 6800.47 | 6800.47 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 7533.896 | 7533.896 | 0.415933 | 0.00006591 | 188.753 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 19:30:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 19:30:00 | 7533.90 | 7533.90 | 0.415933 | 16.70 | 11.36 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00788795 | 41.9489 | 5728.06 | 0.00 | 7572.71 | 7572.71 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 48199.928 | -999.000 | 2.051317 | 0.00137851 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 48199.93 | 48199.93 | 2.051317 | 35.10 | 15.77 | 0.00569938 | 11.74 | 7.07 | 0.00569938 | 35.10 | 0.00569938 | 15.77 | 99.9965 | 21.11 | 0.00859435 | 45.3444 | 179580.09 | 0.00 | 48235.98 | 48235.98 |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | FLR_3_DOAS | 15066.372 | 15066.372 | 0.615395 | 0.00013181 | 252.128 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 15066.37 | 15066.37 | 0.615395 | -7.90 | -7.90 | 0.00234317 | 16.70 | 11.36 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 333.3216 | 21.11 | 0.00779271 | 41.1668 | 91545.05 | 0.00 | 13307.58 | 13307.58 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 487346.857 | -999.000 | 26.333940 | 0.01393806 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 487346.86 | 487346.86 | 26.333940 | 28.91 | 15.51 | 0.00789537 | 10.58 | 8.86 | 0.00789537 | 35.10 | 0.00569938 | 15.77 | 44.2830 | 23.99 | 0.00959994 | 42.4503 | 297889.59 | 0.00 | 574720.29 | 526921.86 |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV WITH REHEAT | 193415.684 | 193415.684 | 7.900182 | 0.00169208 | 3236.718 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:50:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:50:00 | 193415.68 | 193415.68 | 7.900182 | -7.90 | -7.90 | 0.00234317 | 16.70 | 11.36 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 147.6100 | 21.33 | 0.00682240 | 35.6094 | 53475.14 | 0.00 | 170837.04 | 170837.04 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:37
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | Yes | Yes | No | 5853.650 | 5853.650 | 1.347927 | 0.00005121 | 122.068 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.53833447 | 54.44 | 82.22 | 27.78 | 412635.24 | 1.4186 | 1.447152 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 5853.65 | 5853.65 | 1.0000 | 1.33499904 | 1.347927 | 16.70 | 11.36 | 0.00800000 | 37036.7 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.05120506 | 60.00 | 32.22 | 27.78 | 0.000 | 5853.65 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 42.5367 | 0.00 | 0.00 | 5886.55 | 5886.55 | 1.33499904 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 20.92 | 14.82 | 0.00800000 | 41344.1 | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3143.132 | 3143.132 | 0.177859 | 0.00002750 | 78.231 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.53833447 | 54.44 | 82.22 | 27.78 | 412635.24 | 0.7617 | 0.777052 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 3143.13 | 3143.13 | 1.0000 | 0.17615309 | 0.177859 | 16.70 | 11.36 | 0.00800000 | 37036.7 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.02749469 | 60.00 | 32.22 | 27.78 | 0.000 | 3143.13 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.00 | 0.00778608 | 21.00 | 0.00778608 | 41.4140 | 2371.09 | 0.00 | 3159.36 | 3159.36 | 0.17615309 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 34.19 | 19.40 | 0.00800000 | 54870.0 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1316.108 | 1316.108 | 0.121991 | 0.00001151 | 29.752 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.53833447 | 54.44 | 82.22 | 27.78 | 412635.24 | 0.3190 | 0.325371 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1316.11 | 1316.11 | 1.0000 | 0.12082095 | 0.121991 | 16.70 | 11.36 | 0.00800000 | 37036.7 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.01151272 | 60.00 | 32.22 | 27.78 | 0.000 | 1316.11 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.00 | 0.00775258 | 21.00 | 0.00775258 | 41.2376 | 786.59 | 0.00 | 1323.21 | 1323.21 | 0.12082095 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 27.34 | 17.13 | 0.00800000 | 47886.6 | |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1828.325 | 1828.325 | 0.099464 | 0.00001599 | 45.992 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.53833447 | 54.44 | 82.22 | 27.78 | 412635.24 | 0.4431 | 0.452002 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1828.33 | 1828.33 | 1.0000 | 0.09850996 | 0.099464 | 16.70 | 11.36 | 0.00800000 | 37036.7 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.01599335 | 60.00 | 32.22 | 27.78 | 0.000 | 1828.33 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.00 | 0.00767533 | 21.00 | 0.00767533 | 40.8317 | 1396.65 | 0.00 | 1837.73 | 1837.73 | 0.09850996 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 34.89 | 19.62 | 0.00800000 | 55590.0 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1229.714 | 1229.714 | 0.059914 | 0.00001076 | 31.967 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.53833447 | 54.44 | 82.22 | 27.78 | 412635.24 | 0.2980 | 0.304012 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1229.71 | 1229.71 | 1.0000 | 0.05933915 | 0.059914 | 16.70 | 11.36 | 0.00800000 | 37036.7 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.01075698 | 60.00 | 32.22 | 27.78 | 0.000 | 1229.71 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.00 | 0.00772758 | 21.00 | 0.00772758 | 41.1063 | 969.66 | 0.00 | 1235.90 | 1235.90 | 0.05933915 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 37.03 | 20.29 | 0.00800000 | 57762.5 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9419.862 | 9419.862 | 1.739553 | 0.00008241 | 198.985 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.53833447 | 54.44 | 82.22 | 27.78 | 412635.24 | 2.2829 | 2.328798 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 9419.86 | 9419.86 | 1.0000 | 1.72286914 | 1.739553 | 16.70 | 11.36 | 0.00800000 | 37036.7 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.08240065 | 60.00 | 32.22 | 27.78 | 0.000 | 9419.86 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.00 | 0.00766944 | 21.00 | 0.00766944 | 40.8011 | 1870.49 | 0.00 | 9472.56 | 9472.56 | 1.72286914 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.99 | 15.22 | 0.00800000 | 42432.9 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9349.479 | 9349.479 | 0.766191 | 0.00008179 | 215.380 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.53833447 | 54.44 | 82.22 | 27.78 | 412635.24 | 2.2658 | 2.311397 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 9349.48 | 9349.48 | 1.0000 | 0.75884208 | 0.766191 | 16.70 | 11.36 | 0.00800000 | 37036.7 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.08178497 | 60.00 | 32.22 | 27.78 | 0.000 | 9349.48 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.00 | 0.00781294 | 21.00 | 0.00781294 | 41.5549 | 6023.42 | 0.00 | 9399.60 | 9399.60 | 0.75884208 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 28.75 | 17.62 | 0.00800000 | 49321.5 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 24778.188 | 24778.188 | 2.524229 | 0.00021677 | 553.060 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.53833447 | 54.44 | 82.22 | 27.78 | 412635.24 | 6.0049 | 6.125715 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 24778.19 | 24778.19 | 1.0000 | 2.50001840 | 2.524229 | 16.70 | 11.36 | 0.00800000 | 37036.7 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.21674829 | 60.00 | 32.22 | 27.78 | 0.000 | 24778.19 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.00 | 0.00776890 | 21.00 | 0.00776890 | 41.3233 | 13821.04 | 0.00 | 24912.55 | 24912.55 | 2.50001840 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 26.37 | 16.80 | 0.00800000 | 46899.7 | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12796.045 | -999.000 | 1.388233 | 0.00036596 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7245 | 1004.8586 | 0.9904 | ROOM_1_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.388233 | 1.37491871 | 4197.9300 | 999.8980 | 21.35187445 | 15.03 | 6.70 | 8.33 | 746648.51 | 1.7138 | 1.713766 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | unknown | unknown | 7/21 16:50:00 | Sensible | 12796.05 | 12687.99 | 1.0000 | 1.37491871 | 1.388233 | 21.81 | 13.68 | 0.00854490 | 43629.0 | 12.80 | 10.33 | 0.00850000 | 34322.2 | 0.36592111 | 6.70 | 15.03 | 8.33 | 0.000 | 12796.05 | 33.39 | 0.00569673 | 15.22 | 0.00000000 | 0.0000 | 21.11 | 0.00854490 | 21.11 | 0.00854490 | 45.0870 | 11662.42 | 0.00 | 9568.84 | 9568.84 | 1.37491871 | 21.81 | 15.64 | 0.00854490 | 43629.0 | 14.99 | 13.03 | 0.00854490 | 36669.4 | |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5181.175 | 5181.175 | 0.271594 | 0.00004533 | 148.040 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | ROOM_1_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.388233 | 1.37491871 | 4197.9300 | 999.8980 | 3.53833447 | 54.44 | 82.22 | 27.78 | 412635.24 | 1.2556 | 1.280901 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 5181.18 | 5181.18 | 1.0000 | 0.26898950 | 0.271594 | 21.11 | 12.78 | 0.00777452 | 40961.6 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.04532256 | 60.00 | 32.22 | 27.78 | 0.000 | 5181.18 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.11 | 0.00777452 | 21.11 | 0.00777452 | 41.0723 | 5181.24 | 0.00 | 5585.47 | 5585.47 | 0.26898950 | 16.60 | 12.93 | 0.00777452 | 36363.9 | 36.97 | 20.10 | 0.00777452 | 57128.5 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12661.817 | -999.000 | 1.373499 | 0.00036212 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7254 | 1004.8586 | 0.9904 | ROOM_2_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.373499 | 1.36032554 | 4197.9300 | 999.8980 | 21.35187445 | 15.03 | 6.70 | 8.33 | 746648.51 | 1.6958 | 1.695789 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | unknown | unknown | 7/21 17:00:00 | Sensible | 12661.82 | 12553.81 | 1.0000 | 1.36032554 | 1.373499 | 21.81 | 13.68 | 0.00854536 | 43630.1 | 12.80 | 10.33 | 0.00850000 | 34322.2 | 0.36208267 | 6.70 | 15.03 | 8.33 | 0.000 | 12661.82 | 33.21 | 0.00569645 | 15.16 | 0.00000000 | 0.0000 | 21.11 | 0.00854536 | 21.11 | 0.00854536 | 45.0894 | 11538.64 | 0.00 | 9468.71 | 9468.71 | 1.36032554 | 21.81 | 15.64 | 0.00854536 | 43630.1 | 14.99 | 13.03 | 0.00854536 | 36669.5 | |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5180.924 | 5180.924 | 0.271581 | 0.00004532 | 148.033 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | ROOM_2_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.373499 | 1.36032554 | 4197.9300 | 999.8980 | 3.53833447 | 54.44 | 82.22 | 27.78 | 412635.24 | 1.2556 | 1.280839 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 5180.92 | 5180.92 | 1.0000 | 0.26897645 | 0.271581 | 21.11 | 12.78 | 0.00777453 | 40961.6 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.04532036 | 60.00 | 32.22 | 27.78 | 0.000 | 5180.92 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.11 | 0.00777453 | 21.11 | 0.00777453 | 41.0723 | 5180.99 | 0.00 | 5585.20 | 5585.20 | 0.26897645 | 16.60 | 12.93 | 0.00777453 | 36363.9 | 36.97 | 20.10 | 0.00777453 | 57128.5 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 68930.430 | -999.000 | 7.570947 | 0.00197136 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6061 | 1004.8586 | 0.9904 | ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 7.570947 | 7.49833346 | 4197.9300 | 999.8980 | 21.35187445 | 15.03 | 6.70 | 8.33 | 746648.51 | 9.2320 | 9.231806 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | unknown | unknown | unknown | 7/21 13:40:00 | Sensible | 68930.43 | 68930.43 | 1.0000 | 7.49833346 | 7.570947 | 21.81 | 13.62 | 0.00848118 | 43467.5 | 12.80 | 10.32 | 0.00848118 | 34274.7 | 1.97116364 | 6.70 | 15.03 | 8.33 | 0.000 | 68930.43 | 34.88 | 0.00569904 | 15.70 | 0.00000000 | 0.0000 | 21.11 | 0.00848118 | 21.11 | 0.00848118 | 44.7544 | 63605.42 | 0.00 | 55322.05 | 55322.05 | 7.49833346 | 21.81 | 15.58 | 0.00848118 | 43467.5 | 14.58 | 12.81 | 0.00848118 | 36089.5 | |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 29953.441 | 29953.441 | 1.570156 | 0.00026205 | 855.842 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 7.570947 | 7.49833346 | 4197.9300 | 999.8980 | 3.53833447 | 54.44 | 82.22 | 27.78 | 412635.24 | 7.2591 | 7.405152 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 29953.44 | 29953.44 | 1.0000 | 1.55509659 | 1.570156 | 21.11 | 12.79 | 0.00779255 | 41007.6 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.26201904 | 60.00 | 32.22 | 27.78 | 0.000 | 29953.44 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.11 | 0.00779255 | 21.11 | 0.00779255 | 41.1660 | 29953.61 | 0.00 | 32290.82 | 32290.82 | 1.55509659 | 16.60 | 12.95 | 0.00779255 | 36409.5 | 36.97 | 20.11 | 0.00779255 | 57174.0 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 73012.705 | -999.000 | 7.589937 | 0.00208812 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0220 | 1004.8586 | 0.9904 | ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 7.589937 | 7.51714115 | 4197.9300 | 999.8980 | 21.35187445 | 15.03 | 6.70 | 8.33 | 746648.51 | 9.7787 | 9.778542 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | unknown | unknown | unknown | 7/21 18:10:00 | Sensible | 73012.71 | 70281.18 | 1.0000 | 7.51714115 | 7.589937 | 21.81 | 13.81 | 0.00870490 | 44035.0 | 12.80 | 10.33 | 0.00850000 | 34322.2 | 2.08790212 | 6.70 | 15.03 | 8.33 | 0.000 | 73012.71 | 31.52 | 0.00569384 | 14.61 | 0.00000000 | 0.0000 | 21.11 | 0.00870490 | 21.11 | 0.00870490 | 45.9206 | 63759.59 | 0.00 | 55073.40 | 54116.97 | 7.51714115 | 21.81 | 15.78 | 0.00870490 | 44035.0 | 14.76 | 13.05 | 0.00865458 | 36708.6 | |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 29963.024 | 29963.024 | 1.570658 | 0.00026213 | 856.116 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 7.589937 | 7.51714115 | 4197.9300 | 999.8980 | 3.53833447 | 54.44 | 82.22 | 27.78 | 412635.24 | 7.2614 | 7.407521 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 29963.02 | 29963.02 | 1.0000 | 1.55559409 | 1.570658 | 21.11 | 12.79 | 0.00779256 | 41007.6 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.26210286 | 60.00 | 32.22 | 27.78 | 0.000 | 29963.02 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.11 | 0.00779256 | 21.11 | 0.00779256 | 41.1660 | 29963.20 | 0.00 | 32301.15 | 32301.15 | 1.55559409 | 16.60 | 12.95 | 0.00779256 | 36409.5 | 36.97 | 20.11 | 0.00779256 | 57174.0 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11365.099 | -999.000 | 1.231216 | 0.00032503 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7344 | 1004.8586 | 0.9904 | ROOM_5_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.231216 | 1.21940759 | 4197.9300 | 999.8980 | 21.35187445 | 15.03 | 6.70 | 8.33 | 746648.51 | 1.5221 | 1.522120 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | unknown | unknown | unknown | 7/21 09:40:00 | Sensible | 11365.10 | 11257.95 | 1.0000 | 1.21940759 | 1.231216 | 21.81 | 13.68 | 0.00855018 | 43642.4 | 12.80 | 10.33 | 0.00850000 | 34322.2 | 0.32500117 | 6.70 | 15.03 | 8.33 | 0.000 | 11365.10 | 29.21 | 0.00569029 | 13.82 | 0.00000000 | 0.0000 | 21.11 | 0.00855018 | 21.11 | 0.00855018 | 45.1145 | 10343.33 | 0.00 | 8501.25 | 8501.25 | 1.21940759 | 21.81 | 15.64 | 0.00855018 | 43642.4 | 14.98 | 13.03 | 0.00855018 | 36670.8 | |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5181.175 | 5181.175 | 0.271594 | 0.00004533 | 148.040 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | ROOM_5_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.231216 | 1.21940759 | 4197.9300 | 999.8980 | 3.53833447 | 54.44 | 82.22 | 27.78 | 412635.24 | 1.2556 | 1.280901 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 5181.18 | 5181.18 | 1.0000 | 0.26898950 | 0.271594 | 21.11 | 12.78 | 0.00777452 | 40961.6 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.04532256 | 60.00 | 32.22 | 27.78 | 0.000 | 5181.18 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.11 | 0.00777452 | 21.11 | 0.00777452 | 41.0723 | 5181.24 | 0.00 | 5585.47 | 5585.47 | 0.26898950 | 16.60 | 12.93 | 0.00777452 | 36363.9 | 36.97 | 20.10 | 0.00777452 | 57128.5 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11270.720 | -999.000 | 1.220854 | 0.00032234 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7351 | 1004.8586 | 0.9904 | ROOM_6_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.220854 | 1.20914511 | 4197.9300 | 999.8980 | 21.35187445 | 15.03 | 6.70 | 8.33 | 746648.51 | 1.5095 | 1.509480 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | unknown | unknown | unknown | 7/21 09:30:00 | Sensible | 11270.72 | 11163.59 | 1.0000 | 1.20914511 | 1.220854 | 21.81 | 13.68 | 0.00855059 | 43643.4 | 12.80 | 10.33 | 0.00850000 | 34322.2 | 0.32230227 | 6.70 | 15.03 | 8.33 | 0.000 | 11270.72 | 28.82 | 0.00568971 | 13.69 | 0.00000000 | 0.0000 | 21.11 | 0.00855059 | 21.11 | 0.00855059 | 45.1166 | 10256.28 | 0.00 | 8430.85 | 8430.85 | 1.20914511 | 21.81 | 15.64 | 0.00855059 | 43643.4 | 14.98 | 13.03 | 0.00855059 | 36670.9 | |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5180.924 | 5180.924 | 0.271581 | 0.00004532 | 148.033 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | ROOM_6_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.220854 | 1.20914511 | 4197.9300 | 999.8980 | 3.53833447 | 54.44 | 82.22 | 27.78 | 412635.24 | 1.2556 | 1.280839 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 5180.92 | 5180.92 | 1.0000 | 0.26897645 | 0.271581 | 21.11 | 12.78 | 0.00777453 | 40961.6 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.04532036 | 60.00 | 32.22 | 27.78 | 0.000 | 5180.92 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.11 | 0.00777453 | 21.11 | 0.00777453 | 41.0723 | 5180.99 | 0.00 | 5585.20 | 5585.20 | 0.26897645 | 16.60 | 12.93 | 0.00777453 | 36363.9 | 36.97 | 20.10 | 0.00777453 | 57128.5 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11928.620 | 11928.620 | 0.802253 | 0.00010436 | 285.077 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.53833447 | 54.44 | 82.22 | 27.78 | 412635.24 | 2.8908 | 2.949018 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 11928.62 | 11928.62 | 1.0000 | 0.79455852 | 0.802253 | 16.70 | 11.36 | 0.00800000 | 37036.7 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.10434613 | 60.00 | 32.22 | 27.78 | 0.000 | 11928.62 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.00 | 0.00782997 | 21.00 | 0.00782997 | 41.6440 | 8445.78 | 0.00 | 11991.09 | 11991.09 | 0.79455852 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 31.40 | 18.50 | 0.00800000 | 52026.3 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3389.642 | -999.000 | 0.367990 | 0.00009694 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7199 | 1004.8586 | 0.9904 | ROOM_1_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.367990 | 0.36446069 | 4197.9300 | 999.8980 | 21.35187445 | 15.03 | 6.70 | 8.33 | 746648.51 | 0.4540 | 0.453972 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | unknown | unknown | 7/21 16:50:00 | Sensible | 3389.64 | 3362.60 | 1.0000 | 0.36446069 | 0.367990 | 21.81 | 13.68 | 0.00854240 | 43622.6 | 12.80 | 10.33 | 0.00850000 | 34322.2 | 0.09693163 | 6.70 | 15.03 | 8.33 | 0.000 | 3389.64 | 33.39 | 0.00569673 | 15.22 | 0.00000000 | 0.0000 | 21.11 | 0.00854240 | 21.11 | 0.00854240 | 45.0740 | 3091.45 | 0.00 | 2534.42 | 2534.42 | 0.36446069 | 21.81 | 15.64 | 0.00854240 | 43622.6 | 14.99 | 13.03 | 0.00854240 | 36668.7 | |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1601.262 | 1601.262 | 0.083937 | 0.00001401 | 45.751 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | ROOM_1_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.367990 | 0.36446069 | 4197.9300 | 999.8980 | 3.53833447 | 54.44 | 82.22 | 27.78 | 412635.24 | 0.3881 | 0.395867 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1601.26 | 1601.26 | 1.0000 | 0.08313224 | 0.083937 | 21.11 | 12.81 | 0.00781617 | 41067.4 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.01400711 | 60.00 | 32.22 | 27.78 | 0.000 | 1601.26 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.11 | 0.00781617 | 21.11 | 0.00781617 | 41.2896 | 1601.28 | 0.00 | 1726.21 | 1726.21 | 0.08313224 | 16.60 | 12.97 | 0.00781617 | 36469.3 | 36.97 | 20.13 | 0.00781617 | 57233.9 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3348.106 | -999.000 | 0.363430 | 0.00009575 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7209 | 1004.8586 | 0.9904 | ROOM_2_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.363430 | 0.35994433 | 4197.9300 | 999.8980 | 21.35187445 | 15.03 | 6.70 | 8.33 | 746648.51 | 0.4484 | 0.448410 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | unknown | unknown | 7/21 17:00:00 | Sensible | 3348.11 | 3321.07 | 1.0000 | 0.35994433 | 0.363430 | 21.81 | 13.68 | 0.00854292 | 43623.9 | 12.80 | 10.33 | 0.00850000 | 34322.2 | 0.09574384 | 6.70 | 15.03 | 8.33 | 0.000 | 3348.11 | 33.21 | 0.00569645 | 15.16 | 0.00000000 | 0.0000 | 21.11 | 0.00854292 | 21.11 | 0.00854292 | 45.0767 | 3053.14 | 0.00 | 2503.43 | 2503.43 | 0.35994433 | 21.81 | 15.64 | 0.00854292 | 43623.9 | 14.99 | 13.03 | 0.00854292 | 36668.9 | |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1602.133 | 1602.133 | 0.083983 | 0.00001402 | 45.776 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | ROOM_2_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.363430 | 0.35994433 | 4197.9300 | 999.8980 | 3.53833447 | 54.44 | 82.22 | 27.78 | 412635.24 | 0.3883 | 0.396083 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1602.13 | 1602.13 | 1.0000 | 0.08317745 | 0.083983 | 21.11 | 12.81 | 0.00781628 | 41067.7 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.01401473 | 60.00 | 32.22 | 27.78 | 0.000 | 1602.13 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.11 | 0.00781628 | 21.11 | 0.00781628 | 41.2902 | 1602.15 | 0.00 | 1727.15 | 1727.15 | 0.08317745 | 16.60 | 12.97 | 0.00781628 | 36469.6 | 36.97 | 20.13 | 0.00781628 | 57234.2 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14331.100 | -999.000 | 1.527051 | 0.00040986 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8484 | 1004.8586 | 0.9904 | ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 1.527051 | 1.51240477 | 4197.9300 | 999.8980 | 21.35187445 | 15.03 | 6.70 | 8.33 | 746648.51 | 1.9194 | 1.919355 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | unknown | unknown | unknown | 7/21 13:50:00 | Sensible | 14331.10 | 14034.26 | 1.0000 | 1.51240477 | 1.527051 | 21.81 | 13.73 | 0.00861151 | 43797.9 | 12.80 | 10.33 | 0.00850000 | 34322.2 | 0.40981818 | 6.70 | 15.03 | 8.33 | 0.000 | 14331.10 | 34.99 | 0.00569921 | 15.74 | 0.00000000 | 0.0000 | 21.11 | 0.00861151 | 21.11 | 0.00861151 | 45.4344 | 12828.21 | 0.00 | 10755.81 | 10755.81 | 1.51240477 | 21.81 | 15.70 | 0.00861151 | 43797.9 | 14.84 | 13.04 | 0.00861151 | 36686.2 | |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7700.301 | 7700.301 | 0.403647 | 0.00006737 | 220.012 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 1.527051 | 1.51240477 | 4197.9300 | 999.8980 | 3.53833447 | 54.44 | 82.22 | 27.78 | 412635.24 | 1.8661 | 1.903684 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 7700.30 | 7700.30 | 1.0000 | 0.39977539 | 0.403647 | 21.11 | 12.82 | 0.00782373 | 41086.7 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.06735872 | 60.00 | 32.22 | 27.78 | 0.000 | 7700.30 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.11 | 0.00782373 | 21.11 | 0.00782373 | 41.3289 | 7700.37 | 0.00 | 8301.17 | 8301.17 | 0.39977539 | 16.60 | 12.98 | 0.00782373 | 36488.5 | 36.97 | 20.14 | 0.00782373 | 57253.0 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10480.317 | 10480.317 | 1.167550 | 0.00009169 | 231.407 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.53833447 | 54.44 | 82.22 | 27.78 | 412635.24 | 2.5399 | 2.590966 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 10480.32 | 10480.32 | 1.0000 | 1.15635175 | 1.167550 | 16.70 | 11.36 | 0.00800000 | 37036.7 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.09167704 | 60.00 | 32.22 | 27.78 | 0.000 | 10480.32 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.00 | 0.00786519 | 21.00 | 0.00786519 | 41.8292 | 5411.35 | 0.00 | 10537.39 | 10537.39 | 1.15635175 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 25.54 | 16.50 | 0.00800000 | 46047.4 | |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10844.255 | 10844.255 | 1.223392 | 0.00009487 | 239.100 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.53833447 | 54.44 | 82.22 | 27.78 | 412635.24 | 2.6280 | 2.680939 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | Sensible | 10844.26 | 10844.26 | 1.0000 | 1.21165786 | 1.223392 | 16.70 | 11.36 | 0.00800000 | 37036.7 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.09486060 | 60.00 | 32.22 | 27.78 | 0.000 | 10844.26 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.00 | 0.00786809 | 21.00 | 0.00786809 | 41.8447 | 5533.00 | 0.00 | 10903.35 | 10903.35 | 1.21165786 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 25.42 | 16.46 | 0.00800000 | 45933.4 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6762.665 | 6762.665 | 1.206766 | 0.00005916 | 143.182 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.53833447 | 54.44 | 82.22 | 27.78 | 412635.24 | 1.6389 | 1.671880 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | Sensible | 6762.67 | 6762.67 | 1.0000 | 1.19519156 | 1.206766 | 16.70 | 11.36 | 0.00800000 | 37036.7 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.05915671 | 60.00 | 32.22 | 27.78 | 0.000 | 6762.67 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.33 | 0.00655147 | 21.00 | 0.00655147 | 34.9210 | 1539.26 | 0.00 | 6800.47 | 6800.47 | 1.19519156 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 22.18 | 15.29 | 0.00800000 | 42624.6 | |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7533.896 | 7533.896 | 0.415933 | 0.00006591 | 188.753 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.53833447 | 54.44 | 82.22 | 27.78 | 412635.24 | 1.8258 | 1.862545 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 19:30:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 19:30:00 | Sensible | 7533.90 | 7533.90 | 1.0000 | 0.41194412 | 0.415933 | 16.70 | 11.36 | 0.00800000 | 37036.7 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.06590309 | 60.00 | 32.22 | 27.78 | 0.000 | 7533.90 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.00 | 0.00788795 | 21.00 | 0.00788795 | 41.9489 | 5728.06 | 0.00 | 7572.71 | 7572.71 | 0.41194412 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 34.63 | 19.54 | 0.00800000 | 55317.6 | |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 48199.928 | -999.000 | 2.051317 | 0.00137851 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1015.4349 | 1004.8586 | 0.9904 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.03157141 | 4197.9300 | 999.8980 | 21.35187445 | 15.03 | 6.70 | 8.33 | 746648.51 | 6.4555 | 6.455505 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | Sensible | 48199.93 | 48199.93 | 1.0000 | 2.03164284 | 2.051317 | 35.10 | 15.77 | 0.00569938 | 49895.6 | 11.74 | 7.07 | 0.00569938 | 26171.0 | 1.37837122 | 6.70 | 15.03 | 8.33 | 2195.006 | 46004.92 | 35.10 | 0.00569938 | 15.77 | 2.05124512 | 99.9965 | 21.11 | 0.00858728 | 21.11 | 0.00859435 | 45.3444 | 179580.09 | 0.00 | 48235.98 | 48235.98 | 2.03164284 | 35.10 | 17.86 | 0.00569938 | 49895.6 | 11.72 | 8.65 | 0.00569938 | 26153.2 | |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 15066.372 | 15066.372 | 0.615395 | 0.00013181 | 252.128 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.03157141 | 4197.9300 | 999.8980 | 3.53833447 | 54.44 | 82.22 | 27.78 | 412635.24 | 3.6513 | 3.724740 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 15066.37 | 15066.37 | 1.0000 | 0.60949285 | 0.615395 | -7.90 | -7.90 | 0.00234317 | -2112.5 | 16.70 | 11.36 | 0.00800000 | 37036.7 | 0.13179374 | 60.00 | 32.22 | 27.78 | 0.000 | 15066.37 | -7.90 | 0.00234317 | -7.90 | 2.05124512 | 333.3216 | 21.11 | 0.00779192 | 21.11 | 0.00779271 | 41.1668 | 91545.05 | 0.00 | 13307.58 | 13307.58 | 0.60949285 | 2.80 | -0.65 | 0.00234317 | 8685.9 | 24.43 | 10.64 | 0.00234317 | 30519.7 | |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 487346.857 | -999.000 | 26.333940 | 0.01393806 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.5171 | 1004.8586 | 0.9904 | VAV WITH REHEAT FAN | Fan:VariableVolume | 26.333940 | 26.08136863 | 4197.9300 | 999.8980 | 21.35187445 | 15.03 | 6.70 | 8.33 | 746648.51 | 65.2713 | 65.271256 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | Sensible | 487346.86 | 487346.86 | 1.0000 | 26.08136863 | 26.333940 | 28.91 | 15.51 | 0.00789537 | 49219.0 | 10.58 | 8.86 | 0.00789537 | 30533.3 | 13.93663658 | 6.70 | 15.03 | 8.33 | 59004.843 | 428342.01 | 35.10 | 0.00569938 | 15.77 | 11.66146000 | 44.2830 | 23.99 | 0.00964071 | 23.99 | 0.00959994 | 42.4503 | 297889.59 | 0.00 | 574720.29 | 526921.86 | 26.08136863 | 28.91 | 17.58 | 0.00789537 | 49219.0 | 9.09 | 9.09 | 0.00716750 | 27183.3 | |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 193415.684 | 193415.684 | 7.900182 | 0.00169208 | 3236.718 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | VAV WITH REHEAT FAN | Fan:VariableVolume | 26.333940 | 26.08136863 | 4197.9300 | 999.8980 | 3.53833447 | 54.44 | 82.22 | 27.78 | 412635.24 | 46.8733 | 47.816626 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:50:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:50:00 | Sensible | 193415.68 | 193415.68 | 1.0000 | 7.82441059 | 7.900182 | -7.90 | -7.90 | 0.00234317 | -2112.5 | 16.70 | 11.36 | 0.00800000 | 37036.7 | 1.69191217 | 60.00 | 32.22 | 27.78 | 0.000 | 193415.68 | -7.90 | 0.00234317 | -7.90 | 11.66146000 | 147.6100 | 18.54 | 0.00712508 | 21.33 | 0.00682240 | 35.6094 | 53475.14 | 0.00 | 170837.04 | 170837.04 | 7.82441059 | 2.80 | -0.65 | 0.00234317 | 8685.9 | 24.43 | 10.64 | 0.00234317 | 30519.7 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:37
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - | |||
VAV WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 26.33 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | VAV WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000610 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LAUNDRY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CAFE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001448 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_3 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
KITCHEN_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003556 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 1371.33 | 6155.00 | 515.17 |
RETAIL_1_FLR_1 | 2693.67 | 5225.17 | 541.67 |
RETAIL_2_FLR_1 | 2283.00 | 5752.50 | 597.17 |
MECH_FLR_1 | 1268.17 | 6622.50 | 260.83 |
STORAGE_FLR_1 | 1171.33 | 7039.17 | 362.00 |
LAUNDRY_FLR_1 | 8082.67 | 3426.17 | 3218.17 |
CAFE_FLR_1 | 4267.50 | 3412.33 | 994.00 |
LOBBY_FLR_1 | 2843.33 | 3833.50 | 872.50 |
ROOM_1_FLR_3 | 826.33 | 7747.83 | 357.17 |
ROOM_2_FLR_3 | 1796.00 | 7524.67 | 1152.33 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 401.17 | 8696.50 | 392.17 |
ROOM_5_FLR_3 | 936.33 | 7687.00 | 358.83 |
ROOM_6_FLR_3 | 1945.50 | 7541.17 | 1253.50 |
CORRIDOR_FLR_3 | 1376.83 | 7001.67 | 678.33 |
ROOM_1_FLR_6 | 1687.83 | 7609.83 | 1030.83 |
ROOM_2_FLR_6 | 2977.17 | 7419.00 | 2150.00 |
ROOM_3_MULT9_FLR_6 | 722.33 | 7437.50 | 152.17 |
BANQUET_FLR_6 | 3665.00 | 2373.50 | 914.00 |
DINING_FLR_6 | 3990.83 | 1327.00 | 869.67 |
KITCHEN_FLR_6 | 8658.33 | 6377.50 | 6377.17 |
CORRIDOR_FLR_6 | 1740.17 | 6391.50 | 401.67 |
Facility | 8758.83 | 8760.00 | 7569.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 186.33 | 0.00 | 186.33 |
ROOM_2_FLR_3 | 0.00 | 183.33 | 0.00 | 183.33 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 103.50 | 0.00 | 103.50 |
ROOM_5_FLR_3 | 0.00 | 194.67 | 0.00 | 194.67 |
ROOM_6_FLR_3 | 0.00 | 203.00 | 0.00 | 203.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 223.00 | 0.00 | 223.00 |
ROOM_2_FLR_6 | 0.00 | 212.83 | 0.00 | 212.83 |
ROOM_3_MULT9_FLR_6 | 0.00 | 235.17 | 0.00 | 235.17 |
BANQUET_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 633.00 | 0.00 | 633.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:37
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.80 | 106.50 | 4826.41 | 1.102 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 2.699 | 0.062 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.28 | 12.54 | 307.76 | 1.532 | 0.021 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.559 | 0.023 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.566 | 0.023 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 25.104 | 0.066 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.58 | 142.30 | 748.35 | 4.339 | 0.049 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.14 | 422.44 | 5183.56 | 1.978 | 0.020 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.354 | 0.080 | 0.000 | 0.058 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.354 | 0.080 | 0.000 | 0.057 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.401 | 0.035 | 0.000 | 0.094 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.354 | 0.080 | 0.000 | 0.058 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.354 | 0.080 | 0.000 | 0.057 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 0.603 | 0.010 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.354 | 0.080 | 0.000 | 0.070 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.354 | 0.080 | 0.000 | 0.063 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.402 | 0.065 | 0.000 | 0.111 |
BANQUET_FLR_6 | 145.01 | 249.90 | 1010.89 | 5.587 | 0.023 | 0.000 | 0.000 |
DINING_FLR_6 | 145.01 | 249.90 | 1010.89 | 6.045 | 0.023 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 25.581 | 0.067 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 1.215 | 0.016 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.80 | 106.50 | 4826.41 | 0.514 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 1.416 | 0.001 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.28 | 12.54 | 307.76 | 0.989 | 0.000 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.440 | 0.000 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.407 | 0.000 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 12.951 | 0.001 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.58 | 142.30 | 748.35 | 2.533 | 0.001 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.14 | 422.44 | 5183.56 | 1.191 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 0.404 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.000 | 0.001 | 0.000 | 0.000 |
BANQUET_FLR_6 | 145.01 | 249.90 | 1010.89 | 3.637 | 0.000 | 0.000 | 0.000 |
DINING_FLR_6 | 145.01 | 249.90 | 1010.89 | 3.843 | 0.000 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 11.339 | 0.001 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 0.752 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:37
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | VAV WITH REHEAT | 61.80 | 106.50 | 4826.41 | 1978.83 | 0.0000 | 0.854 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 6.28 | 10.83 | 265.76 | 67.07 | 0.0000 | 0.079 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 7.28 | 12.54 | 307.76 | 77.67 | 0.0000 | 0.092 |
MECH_FLR_1 | VAV WITH REHEAT | 1.54 | 2.65 | 650.80 | 164.24 | 0.0000 | 0.000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 1.18 | 2.04 | 375.47 | 94.76 | 0.0000 | 0.058 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 4.87 | 8.40 | 309.22 | 78.04 | 0.0000 | 0.000 |
CAFE_FLR_1 | VAV WITH REHEAT | 82.58 | 142.30 | 748.35 | 188.86 | 0.0000 | 0.676 |
LOBBY_FLR_1 | VAV WITH REHEAT | 245.14 | 422.44 | 5183.56 | 1308.19 | 0.0000 | 1.894 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 1.50 | 74.75 | 24.52 | 0.0000 | 0.837 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.837 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 12.16 | 20.96 | 1186.91 | 389.40 | 0.0000 | 0.475 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.015 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.015 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.099 |
BANQUET_FLR_6 | VAV WITH REHEAT | 145.01 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
DINING_FLR_6 | VAV WITH REHEAT | 145.01 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 12.90 | 22.24 | 314.87 | 103.30 | 0.0000 | 0.367 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 12.87 | 22.18 | 1256.16 | 412.12 | 0.0000 | 0.126 |
Total Facility | 873.39 | 1604.23 | 35184.81 | 11345.29 | 0.0000 | 137.584 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 45898249.73 | 0.00 | 45898249.73 | 0.00 | 45898249.73 | 26946214.98 | 37.53 | 9.48 | 8712.99 | 0.00 |
RETAIL_1_FLR_1 | 6207415.13 | 0.00 | 6207415.13 | 142189.15 | 6349604.28 | 2498216.28 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_2_FLR_1 | 4068590.56 | 0.00 | 4068590.56 | 54885.19 | 4123475.75 | 2892943.94 | 6.50 | 3.15 | 8750.35 | 0.00 |
MECH_FLR_1 | 3149688.82 | 0.00 | 3149688.82 | 129715.99 | 3279404.81 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
STORAGE_FLR_1 | 1841817.34 | 0.00 | 1841817.34 | 74838.98 | 1916656.31 | 1821682.01 | 2249.55 | 1947.28 | 4563.17 | 0.00 |
LAUNDRY_FLR_1 | 67072410.33 | 0.00 | 67072410.33 | 177120.55 | 67249530.89 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
CAFE_FLR_1 | 27978445.92 | 0.00 | 27978445.92 | 314317.16 | 28292763.09 | 21330615.53 | 229.27 | 18.47 | 8512.26 | 0.00 |
LOBBY_FLR_1 | 88312491.21 | 0.00 | 88312491.21 | 898075.93 | 89210567.15 | 59728886.00 | 9.29 | 4.10 | 8746.61 | 0.00 |
ROOM_1_FLR_3 | 1460156.71 | 59857.91 | 1520014.62 | 82530.83 | 1602545.46 | 1946875.62 | 2190.00 | 5920.33 | 649.67 | 0.00 |
ROOM_2_FLR_3 | 1459985.63 | 58141.00 | 1518126.64 | 82524.54 | 1600651.17 | 1946647.51 | 2190.00 | 5966.13 | 603.87 | 0.00 |
ROOM_3_MULT19_FLR_3 | 1099911.97 | 0.00 | 1099911.97 | 23027.03 | 1122939.00 | 26397887.27 | 8395.00 | 365.00 | 0.00 | 365.00 |
ROOM_4_MULT19_FLR_3 | 19803829.30 | 60875.42 | 19864704.71 | 23033.32 | 19887738.04 | 26405105.73 | 2190.00 | 5937.12 | 632.88 | 0.00 |
ROOM_5_FLR_3 | 1460156.71 | 60001.51 | 1520158.22 | 82530.83 | 1602689.06 | 1946875.62 | 2190.00 | 5920.33 | 649.67 | 0.00 |
ROOM_6_FLR_3 | 1459985.63 | 58388.08 | 1518373.71 | 82524.54 | 1600898.25 | 1946647.51 | 2189.83 | 5942.15 | 628.01 | 0.00 |
CORRIDOR_FLR_3 | 24764359.41 | 0.00 | 24764359.41 | 99796.38 | 24864155.79 | 14972100.18 | 0.00 | 0.00 | 8760.00 | 0.00 |
ROOM_1_FLR_6 | 365039.18 | 71796.43 | 436835.61 | 82547.98 | 519383.59 | 486718.90 | 2049.43 | 5921.20 | 789.37 | 0.00 |
ROOM_2_FLR_6 | 364996.41 | 64872.20 | 429868.61 | 82541.69 | 512410.30 | 486661.88 | 2073.48 | 5993.27 | 693.25 | 0.00 |
ROOM_3_MULT9_FLR_6 | 2345190.31 | 71855.72 | 2417046.03 | 42234.44 | 2459280.47 | 3126920.42 | 2190.00 | 5919.50 | 650.50 | 0.00 |
BANQUET_FLR_6 | 48607995.07 | 0.00 | 48607995.07 | 201561.43 | 48809556.50 | 37458366.31 | 1564.46 | 259.29 | 6936.25 | 0.00 |
DINING_FLR_6 | 52598435.11 | 0.00 | 52598435.11 | 201561.43 | 52799996.54 | 37458366.31 | 39.35 | 17.31 | 8703.33 | 0.00 |
KITCHEN_FLR_6 | 69392131.69 | 0.00 | 69392131.69 | 180444.21 | 69572575.90 | 11584760.86 | 0.00 | 0.00 | 8760.00 | 0.00 |
CORRIDOR_FLR_6 | 13214838.14 | 0.00 | 13214838.14 | 176608.72 | 13391446.86 | 3961413.96 | 0.00 | 0.00 | 8760.00 | 0.00 |
Total Facility | 0.22E+10 | 6355455.94 | 0.22E+10 | 8316733.59 | 0.22E+10 | 0.43E+10 | 8760.00 | 6791.70 | 8760.00 | 365.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 1.4554 | 0.0000 | 1.4554 | 0.0000 | 1.4554 | 0.8545 | 37.53 | 9.48 | 8712.99 |
RETAIL_1_FLR_1 | 0.1968 | 0.0000 | 0.1968 | 0.0045 | 0.2013 | 0.0792 | 0.00 | 0.00 | 8760.00 |
RETAIL_2_FLR_1 | 0.1290 | 0.0000 | 0.1290 | 0.0017 | 0.1308 | 0.0917 | 6.50 | 3.15 | 8750.35 |
MECH_FLR_1 | 0.0999 | 0.0000 | 0.0999 | 0.0041 | 0.1040 | 0.0000 | 0.00 | 0.00 | 8760.00 |
STORAGE_FLR_1 | 0.0584 | 0.0000 | 0.0584 | 0.0024 | 0.0608 | 0.0578 | 2249.55 | 1947.28 | 4563.17 |
LAUNDRY_FLR_1 | 2.1269 | 0.0000 | 2.1269 | 0.0056 | 2.1325 | 0.0000 | 0.00 | 0.00 | 8760.00 |
CAFE_FLR_1 | 0.8872 | 0.0000 | 0.8872 | 0.0100 | 0.8972 | 0.6764 | 229.27 | 18.47 | 8512.26 |
LOBBY_FLR_1 | 2.8004 | 0.0000 | 2.8004 | 0.0285 | 2.8288 | 1.8940 | 9.29 | 4.10 | 8746.61 |
ROOM_1_FLR_3 | 0.0463 | 0.0019 | 0.0482 | 0.0026 | 0.0508 | 0.0617 | 2190.00 | 5920.33 | 649.67 |
ROOM_2_FLR_3 | 0.0463 | 0.0018 | 0.0481 | 0.0026 | 0.0508 | 0.0617 | 2190.00 | 5966.13 | 603.87 |
ROOM_4_MULT19_FLR_3 | 0.6280 | 0.0019 | 0.6299 | 0.0007 | 0.6306 | 0.8373 | 2190.00 | 5937.12 | 632.88 |
ROOM_5_FLR_3 | 0.0463 | 0.0019 | 0.0482 | 0.0026 | 0.0508 | 0.0617 | 2190.00 | 5920.33 | 649.67 |
ROOM_6_FLR_3 | 0.0463 | 0.0019 | 0.0481 | 0.0026 | 0.0508 | 0.0617 | 2189.83 | 5942.15 | 628.01 |
CORRIDOR_FLR_3 | 0.7853 | 0.0000 | 0.7853 | 0.0032 | 0.7884 | 0.4748 | 0.00 | 0.00 | 8760.00 |
ROOM_1_FLR_6 | 0.0116 | 0.0023 | 0.0139 | 0.0026 | 0.0165 | 0.0154 | 2049.43 | 5921.20 | 789.37 |
ROOM_2_FLR_6 | 0.0116 | 0.0021 | 0.0136 | 0.0026 | 0.0162 | 0.0154 | 2073.48 | 5993.27 | 693.25 |
ROOM_3_MULT9_FLR_6 | 0.0744 | 0.0023 | 0.0766 | 0.0013 | 0.0780 | 0.0992 | 2190.00 | 5919.50 | 650.50 |
BANQUET_FLR_6 | 1.5413 | 0.0000 | 1.5413 | 0.0064 | 1.5477 | 1.1878 | 1564.46 | 259.29 | 6936.25 |
DINING_FLR_6 | 1.6679 | 0.0000 | 1.6679 | 0.0064 | 1.6743 | 1.1878 | 39.35 | 17.31 | 8703.33 |
KITCHEN_FLR_6 | 2.2004 | 0.0000 | 2.2004 | 0.0057 | 2.2061 | 0.3674 | 0.00 | 0.00 | 8760.00 |
CORRIDOR_FLR_6 | 0.4190 | 0.0000 | 0.4190 | 0.0056 | 0.4246 | 0.1256 | 0.00 | 0.00 | 8760.00 |
Total Facility | 65.8831 | 0.2015 | 66.0846 | 0.2082 | 66.2928 | 73.9670 | 8760.00 | 6791.70 | 8760.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
FLR_3_DOAS | 29249995.70 | 505788.27 | 29755783.97 | 64690340.46 | 8760.00 | 0.00 | 0.00 | 0.00 |
VAV WITH REHEAT | 0.44E+09 | 0.00 | 0.44E+09 | 0.22E+09 | 0.00 | 0.00 | 8760.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
FLR_3_DOAS | 0.9275 | 0.0160 | 0.9435 | 2.0513 | 8760.00 | 0.00 | 0.00 |
VAV WITH REHEAT | 14.0936 | 0.0000 | 14.0936 | 6.9969 | 0.00 | 0.00 | 8760.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
FLR_3_DOAS | 0.00 | 0.00 | 0.00 | 0.00 | 6935.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
VAV WITH REHEAT | 0.00 | 0.00 | 4780.96 | 0.00 | 0.00 | 0.00 | 3979.04 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
FLR_3_DOAS | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.1716 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
VAV WITH REHEAT | 0.0000 | 0.0000 | 14.6616 | 0.0000 | 0.0000 | 0.0000 | 13.4149 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:37
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1333 |
Defaulted Fields | 1182 |
Fields with Defaults | 4000 |
Autosized Fields | 349 |
Autosizable Fields | 402 |
Autocalculated Fields | 280 |
Autocalculatable Fields | 539 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:21:37
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 5223.94 | 70120.78 | 10-JUN-05:00 | 366453.59 | 21-JUL-19:20 |
Electricity:Building | 2447.17 | 31250.15 | 17-JUN-05:00 | 151313.73 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 304.40 | 3493.55 | 02-JAN-02:10 | 22822.84 | 02-JAN-20:10 |
Electricity:SpaceType:GENERAL | 2440.07 | 31109.01 | 17-JUN-05:00 | 151072.40 | 02-JAN-20:10 |
InteriorLights:Electricity | 781.90 | 6907.03 | 17-JUN-05:00 | 64632.59 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 161.29 | 1465.65 | 02-JAN-02:10 | 13190.31 | 02-JAN-20:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 781.90 | 6907.03 | 17-JUN-05:00 | 64632.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 781.90 | 6907.03 | 17-JUN-05:00 | 64632.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 161.29 | 1465.65 | 02-JAN-02:10 | 13190.31 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 781.90 | 6907.03 | 17-JUN-05:00 | 64632.59 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 17.49 | 210.74 | 02-JAN-02:10 | 1283.20 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 7.31 | 66.40 | 02-JAN-02:10 | 597.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 7.31 | 66.40 | 02-JAN-02:10 | 597.59 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 20.26 | 244.03 | 02-JAN-02:10 | 1485.95 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 8.46 | 76.89 | 02-JAN-02:10 | 692.02 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 8.46 | 76.89 | 02-JAN-02:10 | 692.02 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 20.84 | 252.75 | 02-JAN-02:10 | 1523.62 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.37 | 76.02 | 02-JAN-02:10 | 684.18 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.37 | 76.02 | 02-JAN-02:10 | 684.18 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 6.68 | 78.96 | 02-JAN-02:10 | 493.99 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 3.08 | 27.98 | 02-JAN-02:10 | 251.84 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 3.08 | 27.98 | 02-JAN-02:10 | 251.84 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 71.91 | 998.82 | 02-JAN-02:10 | 4897.88 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 3.98 | 36.12 | 02-JAN-02:10 | 325.08 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 3.98 | 36.12 | 02-JAN-02:10 | 325.08 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 28.36 | 343.12 | 17-JUN-05:00 | 2666.80 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 14.02 | 83.19 | 01-JAN-13:10 | 1701.53 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 | 14.02 | 83.19 | 01-JAN-13:10 | 1701.53 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 258.83 | 3142.86 | 03-JUN-05:00 | 19534.01 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 109.83 | 1031.45 | 03-JUN-05:00 | 9504.80 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 109.83 | 1031.45 | 03-JUN-05:00 | 9504.80 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 19.72 | 257.38 | 01-JAN-02:10 | 1438.51 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 19.72 | 257.35 | 01-JAN-02:10 | 1438.34 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 305.38 | 4267.82 | 01-JAN-02:10 | 22404.45 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 110.39 | 934.58 | 01-JAN-02:10 | 8496.21 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 110.39 | 934.58 | 01-JAN-02:10 | 8496.21 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 305.47 | 4268.99 | 01-JAN-02:10 | 22410.58 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 110.42 | 934.84 | 01-JAN-02:10 | 8498.53 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 110.42 | 934.84 | 01-JAN-02:10 | 8498.53 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 19.72 | 257.38 | 01-JAN-02:10 | 1438.51 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 19.72 | 257.35 | 01-JAN-02:10 | 1438.34 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 4.93 | 64.34 | 01-JAN-02:10 | 359.63 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 2.31 | 19.57 | 01-JAN-02:10 | 177.88 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 2.31 | 19.57 | 01-JAN-02:10 | 177.88 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 4.93 | 64.34 | 01-JAN-02:10 | 359.59 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 2.31 | 19.56 | 01-JAN-02:10 | 177.86 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 2.31 | 19.56 | 01-JAN-02:10 | 177.86 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 36.17 | 505.54 | 01-JAN-02:10 | 2653.88 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 13.08 | 110.70 | 01-JAN-02:10 | 1006.40 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 13.08 | 110.70 | 01-JAN-02:10 | 1006.40 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 206.66 | 2492.77 | 17-JUN-05:00 | 9735.93 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 30.81 | 243.47 | 17-JUN-05:00 | 2988.03 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 30.81 | 243.47 | 17-JUN-05:00 | 2988.03 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 206.66 | 2492.77 | 17-JUN-05:00 | 9735.93 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 30.81 | 243.47 | 17-JUN-05:00 | 2988.03 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 | 30.81 | 243.47 | 17-JUN-05:00 | 2988.03 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 453.81 | 6249.79 | 02-JAN-02:10 | 18934.39 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 12.97 | 117.87 | 02-JAN-02:10 | 1060.81 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 12.97 | 117.87 | 02-JAN-02:10 | 1060.81 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1658.18 | 24201.97 | 02-JAN-02:10 | 89171.45 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 1658.18 | 24201.97 | 02-JAN-02:10 | 89171.45 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 433.74 | 5990.78 | 01-JAN-00:10 | 16487.34 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 410.33 | 5248.28 | 01-JAN-00:10 | 15744.84 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
Refrigeration:Electricity | 61.47 | 1114.53 | 09-MAY-22:30 | 3259.49 | 15-AUG-06:10 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
Electricity:Plant | 1016.12 | 2759.80 | 10-MAR-02:50 | 149762.94 | 20-JUL-18:10 |
LowTempRefrigeration:Refrigeration:Electricity | 20.46 | 0.00 | 01-JAN-11:10 | 1897.59 | 22-JUL-10:50 |
MedTempRefrigeration:Refrigeration:Electricity | 33.92 | 983.11 | 15-DEC-04:10 | 1199.51 | 23-AUG-13:50 |
Fans:Electricity | 611.69 | 10809.68 | 16-FEB-15:00 | 52176.78 | 21-JUL-21:10 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 774.78 | 11447.62 | 25-OCT-13:50 | 62957.53 | 21-JUL-21:10 |
ExteriorEquipment:Electricity | 813.77 | 9999.82 | 02-JAN-02:20 | 49607.07 | 02-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 21.77 | 381.02 | 02-JAN-02:20 | 1291.59 | 02-JAN-21:10 |
ElectricityPurchased:Facility | 5223.94 | 70120.78 | 10-JUN-05:00 | 366453.59 | 21-JUL-19:20 |
ElectricityPurchased:Plant | 5223.94 | 70120.78 | 10-JUN-05:00 | 366453.59 | 21-JUL-19:20 |
Cogeneration:ElectricityPurchased | 5223.94 | 70120.78 | 10-JUN-05:00 | 366453.59 | 21-JUL-19:20 |
General:Cogeneration:ElectricityPurchased | 5223.94 | 70120.78 | 10-JUN-05:00 | 366453.59 | 21-JUL-19:20 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 5223.94 | 70120.78 | 10-JUN-05:00 | 366453.59 | 21-JUL-19:20 |
ElectricityNet:Plant | 5223.94 | 70120.78 | 10-JUN-05:00 | 366453.59 | 21-JUL-19:20 |
Cogeneration:ElectricityNet | 5223.94 | 70120.78 | 10-JUN-05:00 | 366453.59 | 21-JUL-19:20 |
General:Cogeneration:ElectricityNet | 5223.94 | 70120.78 | 10-JUN-05:00 | 366453.59 | 21-JUL-19:20 |
General:Fans:Electricity | 611.69 | 10809.68 | 16-FEB-15:00 | 52176.78 | 21-JUL-21:10 |
ExteriorLights:Electricity | 193.87 | 0.00 | 01-JAN-07:20 | 12338.45 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 193.87 | 0.00 | 01-JAN-07:20 | 12338.45 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 789.09 | 9600.00 | 01-JAN-00:10 | 48128.80 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 2.91 | 18.80 | 01-JAN-00:10 | 188.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 141.32 | 0.00 | 01-JAN-11:10 | 9938.94 | 12-APR-16:30 |
General:HeatRecovery:Electricity | 141.32 | 0.00 | 01-JAN-11:10 | 9938.94 | 12-APR-16:30 |
WaterSystems:Electricity | 94.78 | 1222.48 | 20-OCT-01:20 | 4751.13 | 05-DEC-20:00 |
Water Heater:WaterSystems:Electricity | 94.78 | 1222.48 | 20-OCT-01:20 | 4751.13 | 05-DEC-20:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 786.28 | 0.00 | 01-JAN-04:20 | 139778.98 | 20-JUL-18:10 |
General:Cooling:Electricity | 786.28 | 0.00 | 01-JAN-04:20 | 139778.98 | 20-JUL-18:10 |
Pumps:Electricity | 80.68 | 47.91 | 22-FEB-11:30 | 3910.75 | 20-JUL-20:10 |
General:Pumps:Electricity | 80.68 | 47.91 | 22-FEB-11:30 | 3910.75 | 20-JUL-20:10 |
WIRED_LTG_ELECTRICITY | 27.52 | 0.00 | 01-JAN-00:10 | 2275.07 | 02-JAN-20:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 5241.16 | 23599.95 | 08-AUG-02:20 | 564302.97 | 27-JAN-18:40 |
NaturalGas:Building | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Laundry:InteriorEquipment:NaturalGas | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
NaturalGas:Plant | 3452.32 | 10238.06 | 08-AUG-02:20 | 460054.65 | 27-JAN-18:40 |
WaterSystems:NaturalGas | 2587.45 | 10238.06 | 08-AUG-02:20 | 251615.12 | 07-FEB-21:50 |
Water Heater:WaterSystems:NaturalGas | 2587.45 | 10238.06 | 08-AUG-02:20 | 251615.12 | 07-FEB-21:50 |
Heating:NaturalGas | 864.87 | 0.00 | 01-JAN-13:00 | 232007.61 | 06-FEB-11:50 |
Boiler:Heating:NaturalGas | 864.87 | 0.00 | 01-JAN-13:00 | 232007.61 | 06-FEB-11:50 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 3128.42 | 0.00 | 01-JAN-04:20 | 426346.73 | 21-JUL-18:10 |
PlantLoopCoolingDemand:HVAC | 3128.42 | 0.00 | 01-JAN-04:20 | 426346.73 | 21-JUL-18:10 |
CoolingCoils:PlantLoopCoolingDemand | 3128.42 | 0.00 | 01-JAN-04:20 | 426346.73 | 21-JUL-18:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 9857.19 | 0.00 | 02-JAN-01:20 | 0.00 | 20-APR-21:00 |
Water:Plant | 9857.19 | 0.00 | 02-JAN-01:20 | 0.00 | 20-APR-21:00 |
WaterSystems:Water | 9857.19 | 0.00 | 02-JAN-01:20 | 0.00 | 20-APR-21:00 |
Water Heater:WaterSystems:Water | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:10 |
MainsWater:Facility | 9857.19 | 0.00 | 02-JAN-01:20 | 0.00 | 20-APR-21:00 |
MainsWater:Plant | 9857.19 | 0.00 | 02-JAN-01:20 | 0.00 | 20-APR-21:00 |
WaterSystems:MainsWater | 9857.19 | 0.00 | 02-JAN-01:20 | 0.00 | 20-APR-21:00 |
Water Heater:WaterSystems:MainsWater | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:10 |
WaterUse:WaterSystems:Water | 4114.69 | 0.00 | 02-JAN-01:20 | 0.00 | 15-MAY-06:10 |
WaterUse:WaterSystems:MainsWater | 4114.69 | 0.00 | 02-JAN-01:20 | 0.00 | 15-MAY-06:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 19896.44 | 134507.77 | 28-MAR-10:20 | 1821011.62 | 20-JUL-18:10 |
EnergyTransfer:Building | 5465.12 | 84235.95 | 19-JAN-11:10 | 338456.18 | 18-AUG-18:20 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 738.66 | 10817.54 | 15-DEC-04:00 | 36826.49 | 23-JUL-10:50 |
Refrigeration:EnergyTransfer | 180.36 | 4016.63 | 10-APR-22:20 | 10346.66 | 15-AUG-06:10 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 90.18 | 2008.31 | 10-APR-22:20 | 5173.33 | 15-AUG-06:10 |
General:Refrigeration:EnergyTransfer | 90.18 | 2008.31 | 10-APR-22:20 | 5173.33 | 15-AUG-06:10 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 90.18 | 2008.31 | 10-APR-22:20 | 5173.33 | 15-AUG-06:10 |
EnergyTransfer:Plant | 8572.39 | 16955.27 | 08-APR-02:10 | 1024451.33 | 20-JUL-18:10 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 21.52 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 68.66 | 1899.34 | 15-DEC-04:10 | 2548.54 | 23-AUG-13:50 |
EnergyTransfer:Zone:BASEMENT | 415.60 | 9916.93 | 03-APR-14:10 | 23217.66 | 12-OCT-21:00 |
Heating:EnergyTransfer | 45.36 | 0.00 | 01-JAN-08:10 | 37511.17 | 21-DEC-16:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 45.36 | 0.00 | 01-JAN-08:10 | 37511.17 | 21-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 5329.58 | 81949.64 | 19-JAN-11:10 | 335796.50 | 18-AUG-18:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 415.60 | 9916.93 | 03-APR-14:10 | 23217.66 | 12-OCT-21:00 |
General:Cooling:EnergyTransfer | 5329.58 | 81949.64 | 19-JAN-11:10 | 335796.50 | 18-AUG-18:20 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 415.60 | 9916.93 | 03-APR-14:10 | 23217.66 | 12-OCT-21:00 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 49.95 | 0.70 | 26-OCT-03:50 | 4545.87 | 19-OCT-12:30 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.03 | 0.00 | 01-JAN-00:10 | 413.98 | 09-DEC-07:20 |
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.03 | 0.00 | 01-JAN-00:10 | 413.98 | 09-DEC-07:20 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 49.93 | 0.00 | 17-JAN-04:40 | 4545.87 | 19-OCT-12:30 |
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 49.93 | 0.00 | 17-JAN-04:40 | 4545.87 | 19-OCT-12:30 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 36.25 | 688.23 | 19-JAN-12:00 | 2299.23 | 21-JUL-21:00 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 36.25 | 688.23 | 19-JAN-12:00 | 2299.23 | 21-JUL-21:00 |
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 36.25 | 688.23 | 19-JAN-12:00 | 2299.23 | 21-JUL-21:00 |
EnergyTransfer:Zone:MECH_FLR_1 | 25.73 | 154.48 | 19-JAN-11:50 | 1947.15 | 21-JUL-20:00 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 25.73 | 154.48 | 19-JAN-11:50 | 1947.15 | 21-JUL-20:00 |
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 25.73 | 154.48 | 19-JAN-11:50 | 1947.15 | 21-JUL-20:00 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 14.26 | 0.98 | 19-JAN-10:20 | 971.68 | 21-JUL-18:40 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 12.23 | 19-JAN-11:40 |
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 12.23 | 19-JAN-11:40 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 14.26 | 0.00 | 19-JAN-10:40 | 971.68 | 21-JUL-18:40 |
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 14.26 | 0.00 | 19-JAN-10:40 | 971.68 | 21-JUL-18:40 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 603.91 | 9913.63 | 21-JAN-06:00 | 39386.60 | 21-JUL-20:00 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 603.91 | 9913.63 | 21-JAN-06:00 | 39386.60 | 21-JUL-20:00 |
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 603.91 | 9913.63 | 21-JAN-06:00 | 39386.60 | 21-JUL-20:00 |
EnergyTransfer:Zone:CAFE_FLR_1 | 252.93 | 2529.34 | 19-JAN-09:20 | 16174.45 | 31-DEC-13:00 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 252.93 | 2529.34 | 19-JAN-09:20 | 16174.45 | 31-DEC-13:00 |
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 252.93 | 2529.34 | 19-JAN-09:20 | 16174.45 | 31-DEC-13:00 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 805.81 | 15188.74 | 19-JAN-11:30 | 43028.96 | 21-JUL-21:10 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 805.81 | 15188.74 | 19-JAN-11:30 | 43028.96 | 21-JUL-21:10 |
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 805.81 | 15188.74 | 19-JAN-11:30 | 43028.96 | 21-JUL-21:10 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 73.84 | 0.00 | 01-JAN-08:10 | 9897.73 | 20-JUN-18:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 4.38 | 0.00 | 01-JAN-00:10 | 3498.12 | 21-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 4.38 | 0.00 | 01-JAN-00:10 | 3498.12 | 21-DEC-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 69.46 | 0.00 | 01-JAN-01:10 | 9897.73 | 20-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 69.46 | 0.00 | 01-JAN-01:10 | 9897.73 | 20-JUN-18:10 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 58.53 | 0.00 | 01-JAN-08:10 | 10061.80 | 25-APR-16:30 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 8.21 | 0.00 | 01-JAN-08:10 | 4037.43 | 15-DEC-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 8.21 | 0.00 | 01-JAN-08:10 | 4037.43 | 15-DEC-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 50.32 | 0.00 | 01-JAN-00:10 | 10061.80 | 25-APR-16:30 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 50.32 | 0.00 | 01-JAN-00:10 | 10061.80 | 25-APR-16:30 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 456.44 | 0.00 | 01-JAN-01:50 | 56338.73 | 14-FEB-13:00 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 456.44 | 0.00 | 01-JAN-01:50 | 56338.73 | 14-FEB-13:00 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 456.44 | 0.00 | 01-JAN-01:50 | 56338.73 | 14-FEB-13:00 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 397.31 | 0.00 | 01-JAN-08:10 | 59203.94 | 17-JUN-18:20 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 10.58 | 0.00 | 01-JAN-00:10 | 18963.20 | 21-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 10.58 | 0.00 | 01-JAN-00:10 | 18963.20 | 21-DEC-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 386.73 | 0.00 | 01-JAN-03:10 | 59203.94 | 17-JUN-18:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 386.73 | 0.00 | 01-JAN-03:10 | 59203.94 | 17-JUN-18:20 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 78.57 | 0.00 | 01-JAN-08:10 | 8974.16 | 18-JUN-08:10 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 4.66 | 0.00 | 01-JAN-00:10 | 3518.63 | 20-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 4.66 | 0.00 | 01-JAN-00:10 | 3518.63 | 20-JAN-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 73.91 | 0.00 | 01-JAN-00:20 | 8974.16 | 18-JUN-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 73.91 | 0.00 | 01-JAN-00:20 | 8974.16 | 18-JUN-08:10 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 62.35 | 0.00 | 01-JAN-08:10 | 9836.32 | 14-JUN-08:30 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 8.35 | 0.00 | 01-JAN-07:50 | 3795.63 | 20-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 8.35 | 0.00 | 01-JAN-07:50 | 3795.63 | 20-JAN-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 54.00 | 0.00 | 01-JAN-00:10 | 9836.32 | 14-JUN-08:30 |
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 54.00 | 0.00 | 01-JAN-00:10 | 9836.32 | 14-JUN-08:30 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 199.96 | 101.54 | 19-JAN-09:10 | 13133.22 | 21-JUL-18:40 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 199.96 | 101.54 | 19-JAN-09:10 | 13133.22 | 21-JUL-18:40 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 199.96 | 101.54 | 19-JAN-09:10 | 13133.22 | 21-JUL-18:40 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 19.36 | 0.00 | 01-JAN-08:10 | 2653.04 | 20-JUN-18:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 2.36 | 0.00 | 01-JAN-08:10 | 1068.58 | 17-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 2.36 | 0.00 | 01-JAN-08:10 | 1068.58 | 17-JAN-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 16.99 | 0.00 | 01-JAN-00:10 | 2653.04 | 20-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 16.99 | 0.00 | 01-JAN-00:10 | 2653.04 | 20-JUN-18:10 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 16.39 | 0.00 | 01-JAN-08:10 | 2723.35 | 25-APR-16:30 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 3.84 | 0.00 | 01-JAN-08:10 | 1287.71 | 21-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 3.84 | 0.00 | 01-JAN-08:10 | 1287.71 | 21-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 12.55 | 0.00 | 01-JAN-00:10 | 2723.35 | 25-APR-16:30 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 12.55 | 0.00 | 01-JAN-00:10 | 2723.35 | 25-APR-16:30 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 117.07 | 0.00 | 01-JAN-08:10 | 12182.21 | 19-OCT-12:30 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 2.95 | 0.00 | 01-JAN-00:10 | 3806.54 | 19-JAN-02:00 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 2.95 | 0.00 | 01-JAN-00:10 | 3806.54 | 19-JAN-02:00 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 114.12 | 0.00 | 01-JAN-04:40 | 12182.21 | 19-OCT-12:30 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 114.12 | 0.00 | 01-JAN-04:40 | 12182.21 | 19-OCT-12:30 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 449.94 | 8303.10 | 21-DEC-15:00 | 23701.60 | 21-JUL-21:20 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 449.94 | 8303.10 | 21-DEC-15:00 | 23701.60 | 21-JUL-21:20 |
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 449.94 | 8303.10 | 21-DEC-15:00 | 23701.60 | 21-JUL-21:20 |
EnergyTransfer:Zone:DINING_FLR_6 | 488.40 | 9247.20 | 15-DEC-09:40 | 24884.71 | 21-JUL-21:20 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 488.40 | 9247.20 | 15-DEC-09:40 | 24884.71 | 21-JUL-21:20 |
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 488.40 | 9247.20 | 15-DEC-09:40 | 24884.71 | 21-JUL-21:20 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 648.48 | 8672.38 | 15-DEC-04:00 | 31769.85 | 23-JUL-10:50 |
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 648.48 | 8672.38 | 15-DEC-04:00 | 31769.85 | 23-JUL-10:50 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 103.86 | 2.83 | 22-DEC-06:20 | 7245.12 | 20-AUG-13:10 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 447.70 | 21-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 447.70 | 21-JAN-07:10 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 103.86 | 0.00 | 18-JAN-07:10 | 7245.12 | 20-AUG-13:10 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 103.86 | 0.00 | 18-JAN-07:10 | 7245.12 | 20-AUG-13:10 |
PlantLoopHeatingDemand:Facility | 1313.26 | 8667.52 | 08-AUG-00:30 | 188271.01 | 10-MAR-08:20 |
PlantLoopHeatingDemand:Plant | 740.12 | 8667.52 | 08-AUG-00:30 | 55958.08 | 06-FEB-07:10 |
WaterSystems:PlantLoopHeatingDemand | 740.12 | 8667.52 | 08-AUG-00:30 | 55958.08 | 06-FEB-07:10 |
General:WaterSystems:PlantLoopHeatingDemand | 740.12 | 8667.52 | 08-AUG-00:30 | 55958.08 | 06-FEB-07:10 |
EnergyTransfer:HVAC | 5858.93 | 800.66 | 28-MAR-14:10 | 476495.63 | 28-JUN-18:10 |
HeatingCoils:EnergyTransfer | 573.15 | 0.00 | 01-JAN-13:00 | 149189.76 | 09-DEC-16:10 |
PlantLoopHeatingDemand:HVAC | 573.15 | 0.00 | 01-JAN-13:00 | 149189.76 | 09-DEC-16:10 |
HeatingCoils:PlantLoopHeatingDemand | 573.15 | 0.00 | 01-JAN-13:00 | 149189.76 | 09-DEC-16:10 |
CoolingCoils:EnergyTransfer | 3128.42 | 0.00 | 01-JAN-04:20 | 426346.73 | 21-JUL-18:10 |
HeatRecoveryForHeating:EnergyTransfer | 2075.30 | 0.00 | 01-JAN-11:10 | 407125.55 | 15-DEC-07:00 |
HeatRecoveryForCooling:EnergyTransfer | 82.06 | 0.00 | 01-JAN-00:10 | 79875.59 | 21-JUN-14:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 740.12 | 8667.52 | 08-AUG-00:30 | 55958.08 | 06-FEB-07:10 |
WaterUse:WaterSystems:EnergyTransfer | 740.12 | 8667.52 | 08-AUG-00:30 | 55958.08 | 06-FEB-07:10 |
Boilers:EnergyTransfer | 568.77 | 0.00 | 01-JAN-13:00 | 150046.34 | 09-DEC-16:10 |
Chillers:EnergyTransfer | 3193.52 | 0.00 | 01-JAN-04:20 | 427387.06 | 21-JUL-18:20 |
HeatRejection:EnergyTransfer | 3979.80 | 0.00 | 01-JAN-04:20 | 566698.36 | 21-JUL-18:20 |
General:HeatRejection:EnergyTransfer | 3979.80 | 0.00 | 01-JAN-04:20 | 566698.36 | 21-JUL-18:20 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:37
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -415.600 | 0.000 | 0.000 | 135.280 | 161.294 | 143.105 | 0.000 | 0.000 | 0.000 | 0.002 | 0.000 | 0.000 | 0.000 | 0.000 | -24.079 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 0.025 | -49.926 | 0.000 | 0.000 | 14.741 | 7.307 | 10.186 | 33.695 | 0.000 | 0.102 | 0.000 | 0.000 | -10.221 | 0.000 | -1.461 | -4.448 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.000 | -36.253 | 0.000 | 0.000 | 16.116 | 8.462 | 11.795 | 0.000 | 0.000 | 0.040 | 0.443 | 0.000 | 0.000 | 0.000 | -0.603 | -0.000 |
MECH_FLR_1 | 0.000 | 0.000 | 0.000 | -25.727 | 0.000 | 0.000 | 3.569 | 8.366 | 12.471 | 0.000 | 0.000 | 0.096 | 2.556 | 0.000 | 0.000 | 0.000 | -1.332 | -0.000 |
STORAGE_FLR_1 | 0.000 | 0.000 | 0.000 | -14.259 | 0.000 | 0.000 | 2.790 | 3.079 | 3.598 | 0.000 | 0.000 | 0.057 | 5.485 | 0.000 | 0.000 | 0.000 | -0.750 | 0.000 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.000 | -603.908 | 0.000 | 0.000 | 10.900 | 3.975 | 658.131 | 0.000 | 0.000 | 0.134 | 0.000 | 0.000 | 0.000 | 0.000 | -1.956 | -67.276 |
CAFE_FLR_1 | 0.000 | 0.000 | 0.000 | -252.929 | 0.000 | 0.000 | 181.530 | 14.018 | 14.341 | 93.868 | 0.000 | 0.226 | 0.002 | 0.000 | -30.616 | 0.000 | -3.497 | -16.940 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.000 | -805.820 | 0.000 | 0.000 | 534.885 | 109.829 | 148.998 | 124.303 | 0.000 | 0.653 | 0.000 | 0.000 | -40.531 | 0.000 | -10.091 | -62.227 |
ROOM_1_FLR_3 | 6.268 | -61.588 | 0.000 | -9.766 | 0.000 | 0.000 | 9.648 | 9.244 | 10.478 | 65.760 | 0.000 | 0.417 | 0.001 | 0.000 | -21.760 | 0.000 | -3.648 | -5.054 |
ROOM_2_FLR_3 | 10.847 | -42.725 | 0.000 | -10.227 | 0.000 | 0.000 | 9.519 | 9.243 | 10.477 | 45.889 | 0.000 | 0.343 | 0.000 | 0.000 | -22.719 | 0.000 | -4.099 | -6.548 |
ROOM_3_MULT19_FLR_3 | 0.000 | -442.685 | 0.000 | -13.747 | 0.000 | 0.000 | 0.000 | 110.385 | 194.997 | 384.768 | 0.000 | 0.627 | 0.001 | 0.000 | -161.475 | 0.000 | -23.879 | -48.991 |
ROOM_4_MULT19_FLR_3 | 30.633 | -271.466 | 0.000 | -135.317 | 0.000 | 0.000 | 182.379 | 110.415 | 195.050 | 108.103 | 0.000 | 2.188 | 0.000 | 0.000 | -122.140 | 0.000 | -31.096 | -68.749 |
ROOM_5_FLR_3 | 6.565 | -66.053 | 0.000 | -9.766 | 0.000 | 0.000 | 9.643 | 9.244 | 10.478 | 69.068 | 0.000 | 0.421 | 0.001 | 0.000 | -21.098 | 0.000 | -3.671 | -4.832 |
ROOM_6_FLR_3 | 10.900 | -46.288 | 0.000 | -10.259 | 0.000 | 0.000 | 9.517 | 9.243 | 10.477 | 48.525 | 0.000 | 0.343 | 0.000 | 0.000 | -21.485 | 0.000 | -4.102 | -6.871 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 0.000 | -199.961 | 0.000 | 0.000 | 113.111 | 91.336 | 0.000 | 57.529 | 0.000 | 0.291 | 0.003 | 0.000 | -28.747 | 0.000 | -4.103 | -29.457 |
ROOM_1_FLR_6 | 2.997 | -15.186 | 0.000 | -2.443 | 0.000 | 0.000 | 2.414 | 2.311 | 2.620 | 16.352 | 0.000 | 0.106 | 0.000 | 0.000 | -5.372 | 0.000 | -0.935 | -2.863 |
ROOM_2_FLR_6 | 4.617 | -10.763 | 0.000 | -2.557 | 0.000 | 0.000 | 2.382 | 2.311 | 2.619 | 11.416 | 0.000 | 0.085 | 0.000 | 0.000 | -5.611 | 0.000 | -1.041 | -3.459 |
ROOM_3_MULT9_FLR_6 | 5.002 | -100.442 | 0.000 | -15.723 | 0.000 | 0.000 | 21.672 | 13.076 | 23.098 | 89.146 | 0.000 | 0.590 | 0.000 | 0.000 | -24.941 | 0.000 | -5.044 | -6.434 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.000 | -449.948 | 0.000 | 0.000 | 314.608 | 30.808 | 175.857 | 10.898 | 0.000 | 0.139 | 0.000 | 0.000 | -16.945 | 0.000 | -2.303 | -63.114 |
DINING_FLR_6 | 0.000 | 0.000 | 0.000 | -488.410 | 0.000 | 0.000 | 314.210 | 30.808 | 175.857 | 10.708 | 0.000 | 0.139 | 0.000 | 0.000 | -17.329 | 0.000 | -2.312 | -23.672 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.000 | -648.460 | 0.000 | 0.000 | 28.029 | 12.972 | 550.372 | 32.306 | 0.000 | 0.125 | 38.215 | 0.000 | -11.491 | 0.000 | -2.069 | -0.001 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 0.004 | -103.860 | 0.000 | 0.000 | 30.262 | 24.166 | 0.000 | 28.447 | 0.000 | 0.123 | 35.415 | 0.000 | -12.759 | 0.000 | -1.798 | -0.001 |
Total Facility | 77.829 | -1057.195 | 0.029 | -4304.866 | 0.000 | 0.000 | 1947.205 | 781.895 | 2365.005 | 1230.781 | 0.000 | 7.247 | 82.126 | 0.000 | -575.241 | 0.000 | -109.790 | -445.016 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 12-OCT-21:00 | 0.00 | 0.00 | 0.00 | -23220.63 | 0.00 | 0.00 | 5924.36 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -3553.95 |
RETAIL_1_FLR_1 | 19-OCT-12:30 | 0.00 | 0.00 | 0.00 | -4547.31 | 0.00 | 0.00 | 150.48 | 166.00 | 252.59 | 6368.82 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -15.38 | -2375.19 |
RETAIL_2_FLR_1 | 21-JUL-21:00 | 0.00 | 0.00 | 0.00 | -2300.20 | 0.00 | 0.00 | 697.58 | 615.12 | 752.15 | 0.00 | 0.00 | 9.91 | 225.44 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 21-JUL-20:00 | 0.00 | 0.00 | 0.00 | -1947.25 | 0.00 | 0.00 | 129.08 | 684.18 | 839.45 | 0.00 | 0.00 | 25.66 | 268.88 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 21-JUL-18:40 | 0.00 | 0.00 | 0.00 | -971.72 | 0.00 | 0.00 | 99.29 | 223.85 | 229.41 | 0.00 | 0.00 | 24.26 | 394.90 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 21-JUL-20:00 | 0.00 | 0.00 | 0.00 | -39385.18 | 0.00 | 0.00 | 408.85 | 325.08 | 44299.38 | 0.00 | 0.00 | 35.04 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5683.18 |
CAFE_FLR_1 | 31-DEC-13:00 | 0.00 | 0.00 | 0.00 | -16173.62 | 0.00 | 0.00 | 2968.80 | 124.78 | 406.43 | 20381.61 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -160.06 | -7547.94 |
LOBBY_FLR_1 | 21-JUL-21:10 | 0.00 | 0.00 | 0.00 | -43050.26 | 0.00 | 0.00 | 26438.46 | 6336.53 | 7389.94 | 384.91 | 0.00 | 154.66 | 2345.76 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 20-JUN-18:02 | 0.00 | -9709.42 | 0.00 | -634.95 | 0.00 | 0.00 | 335.50 | 633.26 | 484.65 | 8719.25 | 0.00 | 71.17 | 100.54 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 25-APR-16:21 | 0.00 | -10858.96 | 0.00 | -777.05 | 0.00 | 0.00 | 193.48 | 199.20 | 505.67 | 10594.85 | 0.00 | 0.00 | 152.40 | 0.00 | -0.00 | 0.00 | -9.58 | 0.00 |
ROOM_3_MULT19_FLR_3 | 14-FEB-13:00 | 0.00 | -56338.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2378.94 | 2352.88 | 81986.67 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -396.95 | -29982.94 |
ROOM_4_MULT19_FLR_3 | 14-JUN-08:21 | 0.00 | -58262.27 | 0.00 | -9301.95 | 0.00 | 0.00 | 1575.64 | 3739.35 | 8433.45 | 13463.73 | 0.00 | 118.32 | 40233.73 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 18-JUN-08:62 | 0.00 | -8687.06 | 0.00 | -638.63 | 0.00 | 0.00 | 130.71 | 398.46 | 653.23 | 10485.60 | 0.00 | 1.64 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2343.94 |
ROOM_6_FLR_3 | 04-JUL-08:62 | 0.00 | -10715.22 | 0.00 | -999.51 | 0.00 | 0.00 | 68.95 | 398.41 | 653.15 | 10056.98 | 0.00 | 0.00 | 577.18 | 0.00 | -0.00 | 0.00 | -39.95 | 0.00 |
CORRIDOR_FLR_3 | 21-JUL-18:40 | 0.00 | 0.00 | 0.00 | -13133.88 | 0.00 | 0.00 | 4080.28 | 6639.35 | 0.00 | 2523.11 | 0.00 | 128.90 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -237.77 |
ROOM_1_FLR_6 | 20-JUN-18:02 | 0.00 | -2590.15 | 0.00 | -159.49 | 0.00 | 0.00 | 83.87 | 158.32 | 121.16 | 2168.88 | 0.00 | 17.53 | 199.88 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 25-APR-16:21 | 0.00 | -2886.52 | 0.00 | -194.92 | 0.00 | 0.00 | 48.37 | 49.80 | 126.42 | 2625.05 | 0.00 | 0.00 | 234.45 | 0.00 | -0.00 | 0.00 | -2.65 | 0.00 |
ROOM_3_MULT9_FLR_6 | 15-OCT-15:08 | 0.00 | -11414.49 | 0.00 | -1088.38 | 0.00 | 0.00 | 275.47 | 332.11 | 487.74 | 9731.41 | 0.00 | 0.00 | 2063.11 | 0.00 | -0.00 | 0.00 | -386.96 | 0.00 |
BANQUET_FLR_6 | 21-JUL-21:20 | 0.00 | 0.00 | 0.00 | -23712.60 | 0.00 | 0.00 | 15599.89 | 1992.02 | 6747.90 | 181.91 | 0.00 | 32.35 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -841.47 |
DINING_FLR_6 | 21-JUL-21:20 | 0.00 | 0.00 | 0.00 | -24896.29 | 0.00 | 0.00 | 15592.54 | 1992.02 | 6747.90 | 169.46 | 0.00 | 32.33 | 362.03 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 23-JUL-10:40 | 0.00 | 0.00 | 0.00 | -31773.27 | 0.00 | 0.00 | 464.27 | 353.60 | 24259.91 | 3606.87 | 0.00 | 40.74 | 3047.88 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 21-AUG-14:10 | 0.00 | 0.00 | 0.00 | -7244.72 | 0.00 | 0.00 | 462.68 | 548.96 | 0.00 | 2826.61 | 0.00 | 42.96 | 3363.49 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 18-AUG-18:02 | 0.00 | -131333.29 | 0.00 | -211177.17 | 0.00 | 0.00 | 73669.09 | 53932.35 | 120482.43 | 39222.30 | 0.00 | 1952.29 | 53251.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 09-DEC-07:20 | 0.00 | 0.00 | 413.88 | 0.00 | 0.00 | 0.00 | 447.48 | 199.20 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1000.21 | 0.00 | -115.19 | -233.82 |
RETAIL_2_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 19-JAN-11:15 | 0.00 | 0.00 | 12.37 | 0.00 | 0.00 | 0.00 | 33.72 | 69.95 | 89.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -53.13 | -152.13 |
LAUNDRY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 17-JAN-09:02 | 5364.40 | 257.22 | 0.00 | -257.22 | 0.00 | 0.00 | 108.00 | 313.07 | 453.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -787.94 | 0.00 | -249.48 | -5201.09 |
ROOM_2_FLR_3 | 22-DEC-09:02 | 5454.82 | 241.77 | 0.00 | -241.77 | 0.00 | 0.00 | 108.88 | 313.04 | 452.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1485.08 | 0.00 | -277.60 | -4567.05 |
ROOM_3_MULT19_FLR_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 19-FEB-16:03 | 30783.01 | 4870.65 | 0.00 | -4870.65 | 0.00 | 0.00 | 2708.68 | 2804.51 | 4118.66 | 1733.16 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -17934.34 | -24213.68 |
ROOM_5_FLR_3 | 17-JAN-16:02 | 5256.52 | 250.90 | 0.00 | -250.90 | 0.00 | 0.00 | 292.69 | 199.23 | 200.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -860.40 | 0.00 | -202.00 | -4886.21 |
ROOM_6_FLR_3 | 20-JAN-09:02 | 5300.01 | 242.96 | 0.00 | -242.96 | 0.00 | 0.00 | 108.88 | 313.04 | 452.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -677.05 | 0.00 | -252.73 | -5245.14 |
CORRIDOR_FLR_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 17-JAN-09:02 | 1615.72 | 61.83 | 0.00 | -61.83 | 0.00 | 0.00 | 27.22 | 78.27 | 113.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -191.82 | 0.00 | -62.10 | -1580.55 |
ROOM_2_FLR_6 | 21-DEC-16:02 | 1636.02 | 60.75 | 0.00 | -60.75 | 0.00 | 0.00 | 73.50 | 49.80 | 50.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -422.09 | 0.00 | -56.77 | -1330.50 |
ROOM_3_MULT9_FLR_6 | 17-JAN-09:02 | 7296.52 | 475.13 | 0.00 | -475.13 | 0.00 | 0.00 | 236.53 | 442.82 | 998.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -593.42 | 0.00 | -296.06 | -8085.08 |
BANQUET_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 21-JAN-07:10 | 0.00 | 0.00 | 447.76 | 0.00 | 0.00 | 0.00 | 916.64 | 658.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1496.34 | 0.00 | -176.16 | -350.67 |
Total Facility | 21-DEC-16:02 | -31651.24 | 98523.41 | 0.00 | -98523.41 | 0.00 | 0.00 | 58157.39 | 17766.95 | 73912.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -45370.14 | 0.00 | -6376.27 | -66439.29 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:37
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV WITH REHEAT | 26.4841 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 26.3339 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV WITH REHEAT | 13.2421 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 11.6530 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.6520 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.0400 | 0.000610 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.000000 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.000000 | 142.3000 | 0.003581 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.000000 | 422.4350 | 0.001448 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 83.8280 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003556 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.1800 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 | |
VAV WITH REHEAT | 0.00 | 0.001045 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.0635 | 3.0635 | 1.3479 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4042 | 0.4042 | 0.1779 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2773 | 0.2773 | 0.1220 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2261 | 0.2261 | 0.0995 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1362 | 0.1362 | 0.0599 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.9535 | 3.9535 | 1.7396 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7413 | 1.7413 | 0.7662 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.7369 | 5.7369 | 2.5242 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8233 | 1.8233 | 0.8023 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6535 | 2.6535 | 1.1675 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.7804 | 2.7804 | 1.2234 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.7426 | 2.7426 | 1.2068 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9453 | 0.9453 | 0.4159 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
VAV WITH REHEAT | 26.4841 | 26.3339 | 26.4841 | 11.6530 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5317 | 1.5317 | 1.3479 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2021 | 0.2021 | 0.1779 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1386 | 0.1386 | 0.1220 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1130 | 0.1130 | 0.0995 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0681 | 0.0681 | 0.0599 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.9768 | 1.9768 | 1.7396 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8707 | 0.8707 | 0.7662 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8684 | 2.8684 | 2.5242 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9117 | 0.9117 | 0.8023 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3268 | 1.3268 | 1.1675 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3902 | 1.3902 | 1.2234 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3713 | 1.3713 | 1.2068 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4727 | 0.4727 | 0.4159 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
VAV WITH REHEAT | 13.2421 | 11.6530 | 11.6530 | 11.6530 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:37
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 168.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 168.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 633.00 |
Number of hours not met | 633.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 864.87 | 232007.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 786.28 | 139778.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 781.90 | 64632.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 193.87 | 12338.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 872.72 | 59188.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 14.43 | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 8.99 | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.20 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 21.77 | 1291.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 789.09 | 48128.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 2.91 | 188.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 611.69 | 52176.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 80.68 | 3910.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 141.32 | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 94.78 | 4751.13 | 2587.45 | 251615.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.09 | 2093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 20.46 | 1897.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 33.92 | 1199.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1719.65 | 5223.94 |
Natural Gas | 1788.84 | 5241.16 |
Additional | 0.00 | 0.00 |
Total | 3508.49 | 10465.10 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 68.92 |
Space Heating | 0.00 |
Space Cooling | 69.30 |
Fans (All) | 53.92 |
Service Water Heating | 8.35 |
Receptacle Equipment | 146.16 |
Miscellaneous (All) | 460.45 |
Subtotal | 460.45 |
Natural Gas [MJ/m2] | |
Space Heating | 76.23 |
Service Water Heating | 228.06 |
Miscellaneous (All) | 461.97 |
Subtotal | 461.97 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 7.47 |
Space Heating | 8.26 |
Space Cooling | 7.51 |
Fans (All) | 5.85 |
Service Water Heating | 25.63 |
Receptacle Equipment | 32.94 |
Miscellaneous | 12.34 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 486. | 5110. |
ELEVATOR_STANDBY_SCH | 7671. | 8760. |
LTG_SCH_KITCHEN | 3061. | 8760. |
LTG_SCH_DINING | 3061. | 8760. |
LTG_SCH_BASEMENT | 2572. | 8760. |
LTG_SCH_LOBBY | 2295. | 8760. |
LTG_SCH_STORAGE | 1580. | 8760. |
LTG_SCH_MECHANIC | 3061. | 8760. |
LTG_SCH_LAUNDRY | 3061. | 8760. |
LTG_SCH_GUESTROOM | 1980. | 8760. |
LTG_SCH_CORRIDOR | 2295. | 8760. |
LTG_SCH_RETAIL | 2678. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 1591. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3737. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 5740. | 6205. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 8760. | 8760. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 26.67 | 365 | 26.67 | 365 |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
HTGSETP_SCH | BASEMENT DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:37
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8752.00 | 8.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8587.50 | 172.50 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8663.50 | 96.50 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8743.33 | 16.67 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8587.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 172.50 | 0.00 | 0.00 | 0.00 |
Average | 8746.65 | 13.35 | 0.00 | 0.00 | 0.00 |
Sum | 192426.33 | 293.67 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4151.67 | 2.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4148.50 | 5.50 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108269.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 5.50 | 0.00 | 0.00 | 0.00 |
Average | 288886.69 | 0.36 | 0.00 | 0.00 | 0.00 |
Sum | 6355507.17 | 7.83 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8759.83 | 0.17 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8634.50 | 125.50 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8688.33 | 71.67 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8734.50 | 25.50 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8333.00 | 427.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8759.33 | 0.67 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8630.83 | 129.17 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8731.33 | 28.67 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8674.67 | 85.33 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8686.50 | 73.50 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8759.67 | 0.33 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8333.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 427.00 | 0.00 | 0.00 | 0.00 |
Average | 8716.02 | 43.98 | 0.00 | 0.00 | 0.00 |
Sum | 191752.50 | 967.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59154.17 | 1.83 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 695917.83 | 14499.17 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2090928.67 | 24500.33 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4145.17 | 8.83 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4148.33 | 5.67 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4143.33 | 10.67 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1228167.00 | 17548.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1230651.00 | 15064.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108267.67 | 1.33 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2090928.67 | 24500.33 | 0.00 | 0.00 | 0.00 |
Average | 285630.69 | 3256.36 | 0.00 | 0.00 | 0.00 |
Sum | 6283875.17 | 71639.83 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:37
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:37
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 1592.73 | 0.00 | 0.00 |
Sum | 0.00 | 35040.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 710417.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 2115429.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 2115429.00 | 0.00 | 0.00 |
Average | 0.00 | 241694.36 | 0.00 | 0.00 |
Sum | 0.00 | 5317276.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4B
For: Environment
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Environment
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NM_ALBUQUERQUE
For: Environment
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.343769E+11 | 19640.85 | 06-JAN-22:00 | 1.10 | -1.8 | 0.819044E+10 | 4837.10 | 31-JAN-00:10 | 2.62 | 0.23 |
February | 0.285363E+11 | 18412.51 | 01-FEB-22:00 | -0.6 | -1.1 | 0.730556E+10 | 4837.02 | 01-FEB-01:19 | -0.6 | -1.1 |
March | 0.297532E+11 | 15625.68 | 01-MAR-22:00 | 10.00 | 2.95 | 0.793502E+10 | 4837.02 | 21-MAR-21:19 | 4.23 | 0.87 |
April | 0.291080E+11 | 13850.94 | 07-APR-21:00 | 6.10 | 1.61 | 0.762991E+10 | 4837.16 | 07-APR-21:10 | 5.82 | 1.46 |
May | 0.308172E+11 | 14746.38 | 11-MAY-21:00 | 17.20 | 6.35 | 0.793640E+10 | 4837.27 | 17-MAY-21:00 | 18.90 | 9.98 |
June | 0.319609E+11 | 17240.61 | 08-JUN-21:00 | 11.70 | 10.04 | 0.783325E+10 | 4837.38 | 23-JUN-21:10 | 26.60 | 15.77 |
July | 0.355372E+11 | 19322.70 | 27-JUL-21:00 | 21.70 | 14.57 | 0.815755E+10 | 4837.18 | 21-JUL-21:19 | 21.70 | 14.57 |
August | 0.377579E+11 | 20837.68 | 23-AUG-21:00 | 21.10 | 15.01 | 0.822513E+10 | 4837.21 | 21-AUG-00:49 | 21.10 | 15.01 |
September | 0.391178E+11 | 22566.41 | 08-SEP-21:00 | 16.10 | 12.69 | 0.795933E+10 | 4837.55 | 22-SEP-21:00 | 19.40 | 14.15 |
October | 0.414955E+11 | 23217.66 | 12-OCT-21:00 | 7.20 | 0.52 | 0.822783E+10 | 4837.29 | 20-OCT-21:10 | 14.22 | 8.62 |
November | 0.390826E+11 | 22861.18 | 03-NOV-21:00 | 5.60 | 2.41 | 0.795912E+10 | 4837.55 | 01-NOV-01:10 | 5.60 | 2.41 |
December | 0.380538E+11 | 22163.84 | 01-DEC-22:00 | 9.40 | 2.31 | 0.822198E+10 | 4837.06 | 02-DEC-04:19 | 3.67 | -1.9 |
Annual Sum or Average | 0.415597E+12 | 0.955815E+11 | ||||||||
Minimum of Months | 0.285363E+11 | 13850.94 | -0.6 | -1.8 | 0.730556E+10 | 4837.02 | -0.6 | -1.9 | ||
Maximum of Months | 0.414955E+11 | 23217.66 | 21.70 | 15.01 | 0.822783E+10 | 4837.55 | 26.60 | 15.77 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.336797E+10 | 4213.84 | 03-JAN-13:00 | 13.90 | 5.34 | 0.672876E+09 | 444.19 | 09-JAN-22:19 | 6.50 | 0.58 |
February | 0.325695E+10 | 4454.34 | 14-FEB-13:10 | 19.60 | 6.70 | 0.619318E+09 | 478.60 | 14-FEB-22:30 | 10.60 | 3.54 |
March | 0.363833E+10 | 3936.50 | 08-MAR-13:30 | 21.40 | 9.29 | 0.697653E+09 | 476.54 | 08-MAR-22:19 | 10.53 | 4.18 |
April | 0.374013E+10 | 3093.60 | 13-APR-12:50 | 23.62 | 8.92 | 0.711097E+09 | 491.84 | 13-APR-22:10 | 17.75 | 6.12 |
May | 0.382296E+10 | 2433.41 | 13-MAY-13:00 | 28.30 | 11.84 | 0.747031E+09 | 491.84 | 31-MAY-22:10 | 20.52 | 8.76 |
June | 0.425914E+10 | 2813.07 | 29-JUN-14:30 | 37.25 | 15.80 | 0.762929E+09 | 491.86 | 23-JUN-21:10 | 37.25 | 15.80 |
July | 0.492826E+10 | 3004.39 | 22-JUL-13:30 | 36.95 | 17.78 | 0.812481E+09 | 491.85 | 21-JUL-21:19 | 36.95 | 17.78 |
August | 0.525149E+10 | 3712.21 | 22-AUG-13:10 | 30.87 | 16.50 | 0.816927E+09 | 491.85 | 21-AUG-00:40 | 30.87 | 16.50 |
September | 0.517554E+10 | 4424.89 | 28-SEP-13:05 | 29.08 | 15.59 | 0.774026E+09 | 491.88 | 22-SEP-21:00 | 29.08 | 15.59 |
October | 0.494945E+10 | 4547.29 | 19-OCT-12:30 | 20.55 | 8.60 | 0.760935E+09 | 491.84 | 04-OCT-22:10 | 20.55 | 8.60 |
November | 0.405555E+10 | 4335.18 | 01-NOV-12:30 | 13.30 | 7.71 | 0.683159E+09 | 475.07 | 02-NOV-21:19 | 11.87 | 5.90 |
December | 0.348072E+10 | 4326.45 | 31-DEC-13:00 | 8.30 | 1.00 | 0.675072E+09 | 435.21 | 29-DEC-22:19 | 8.30 | 1.00 |
Annual Sum or Average | 0.499265E+11 | 0.873350E+10 | ||||||||
Minimum of Months | 0.325695E+10 | 2433.41 | 8.30 | 1.00 | 0.619318E+09 | 435.21 | 6.50 | 0.58 | ||
Maximum of Months | 0.525149E+10 | 4547.29 | 37.25 | 17.78 | 0.816927E+09 | 491.88 | 37.25 | 17.78 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.252029E+10 | 1398.90 | 03-JAN-21:10 | 3.25 | -0.5 | 0.894760E+09 | 569.52 | 24-JAN-22:19 | 0.37 | -3.8 |
February | 0.235161E+10 | 1659.24 | 15-FEB-21:10 | 7.62 | 2.97 | 0.820456E+09 | 569.53 | 15-FEB-01:19 | 7.62 | 2.97 |
March | 0.272128E+10 | 1696.34 | 08-MAR-21:03 | 13.62 | 5.13 | 0.928415E+09 | 569.54 | 09-MAR-01:19 | 4.63 | 1.00 |
April | 0.288862E+10 | 1937.86 | 13-APR-21:00 | 21.10 | 7.69 | 0.916604E+09 | 569.55 | 17-APR-22:10 | 13.62 | 3.75 |
May | 0.312569E+10 | 1998.17 | 19-MAY-20:54 | 23.30 | 8.29 | 0.953508E+09 | 569.63 | 01-MAY-01:10 | 23.30 | 8.29 |
June | 0.341812E+10 | 2235.37 | 28-JUN-20:10 | 29.82 | 16.20 | 0.934788E+09 | 569.64 | 01-JUN-01:10 | 29.82 | 16.20 |
July | 0.374404E+10 | 2299.23 | 21-JUL-21:00 | 30.00 | 14.72 | 0.966902E+09 | 569.63 | 01-JUL-00:40 | 30.00 | 14.72 |
August | 0.374965E+10 | 2240.84 | 18-AUG-20:10 | 27.02 | 13.59 | 0.971300E+09 | 569.56 | 29-AUG-22:49 | 18.07 | 16.08 |
September | 0.341883E+10 | 2091.68 | 13-SEP-20:04 | 23.53 | 12.84 | 0.935774E+09 | 569.60 | 22-SEP-21:00 | 19.40 | 14.15 |
October | 0.315210E+10 | 2028.15 | 05-OCT-20:10 | 18.90 | 9.66 | 0.951334E+09 | 569.56 | 20-OCT-21:10 | 14.22 | 8.62 |
November | 0.265194E+10 | 1674.94 | 02-NOV-21:00 | 12.80 | 4.93 | 0.897238E+09 | 569.59 | 01-NOV-01:10 | 12.80 | 4.93 |
December | 0.251088E+10 | 1333.64 | 29-DEC-22:00 | 2.20 | -1.3 | 0.895954E+09 | 569.52 | 01-DEC-22:49 | 2.20 | -1.3 |
Annual Sum or Average | 0.362531E+11 | 0.110670E+11 | ||||||||
Minimum of Months | 0.235161E+10 | 1333.64 | 2.20 | -1.3 | 0.820456E+09 | 569.52 | 0.37 | -3.8 | ||
Maximum of Months | 0.374965E+10 | 2299.23 | 30.00 | 16.20 | 0.971300E+09 | 569.64 | 30.00 | 16.20 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.160579E+10 | 807.72 | 01-JAN-13:00 | 13.30 | 4.92 | 0.162340E+09 | 105.15 | 05-JAN-22:10 | 3.72 | -1.3 |
February | 0.153555E+10 | 889.74 | 14-FEB-13:10 | 19.60 | 6.70 | 0.149553E+09 | 110.46 | 15-FEB-22:10 | 6.60 | 2.40 |
March | 0.186373E+10 | 898.96 | 26-MAR-10:35 | 14.80 | 5.60 | 0.175416E+09 | 111.10 | 16-MAR-21:19 | 14.80 | 5.60 |
April | 0.200097E+10 | 1031.50 | 29-APR-10:33 | 20.20 | 8.15 | 0.179929E+09 | 120.45 | 14-APR-22:10 | 20.20 | 8.15 |
May | 0.225124E+10 | 1364.28 | 19-MAY-20:54 | 23.30 | 8.29 | 0.194727E+09 | 120.46 | 17-MAY-21:00 | 23.30 | 8.29 |
June | 0.266041E+10 | 1932.48 | 29-JUN-20:00 | 26.70 | 13.56 | 0.196501E+09 | 120.46 | 23-JUN-21:10 | 26.70 | 13.56 |
July | 0.300987E+10 | 1947.15 | 21-JUL-20:00 | 30.60 | 12.57 | 0.204754E+09 | 120.46 | 01-JUL-00:40 | 30.60 | 12.57 |
August | 0.285836E+10 | 1842.13 | 18-AUG-20:00 | 27.20 | 13.67 | 0.205067E+09 | 120.46 | 21-AUG-00:00 | 24.40 | 16.61 |
September | 0.240032E+10 | 1534.82 | 01-SEP-20:00 | 22.80 | 14.95 | 0.194782E+09 | 120.46 | 22-SEP-21:00 | 19.40 | 14.15 |
October | 0.214343E+10 | 1350.44 | 02-OCT-20:00 | 18.90 | 14.94 | 0.188160E+09 | 120.45 | 10-OCT-21:10 | 20.00 | 14.31 |
November | 0.177996E+10 | 920.67 | 01-NOV-12:30 | 13.30 | 7.71 | 0.167616E+09 | 113.04 | 01-NOV-21:10 | 7.88 | 4.75 |
December | 0.161762E+10 | 820.93 | 31-DEC-13:00 | 8.30 | 1.00 | 0.161093E+09 | 106.17 | 01-DEC-22:10 | 8.30 | 1.00 |
Annual Sum or Average | 0.257272E+11 | 0.217994E+10 | ||||||||
Minimum of Months | 0.153555E+10 | 807.72 | 8.30 | 1.00 | 0.149553E+09 | 105.15 | 3.72 | -1.3 | ||
Maximum of Months | 0.300987E+10 | 1947.15 | 30.60 | 14.95 | 0.205067E+09 | 120.46 | 30.60 | 16.61 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.853981E+09 | 474.67 | 01-JAN-13:00 | 13.30 | 4.92 | 0.120351E+09 | 76.16 | 05-JAN-22:30 | 3.35 | -1.3 |
February | 0.843725E+09 | 528.65 | 14-FEB-13:10 | 19.60 | 6.70 | 0.110780E+09 | 80.33 | 15-FEB-22:30 | 6.40 | 2.29 |
March | 0.106578E+10 | 526.41 | 26-MAR-10:35 | 14.80 | 5.60 | 0.129727E+09 | 81.38 | 16-MAR-21:30 | 14.80 | 5.60 |
April | 0.115483E+10 | 607.42 | 29-APR-10:33 | 20.20 | 8.15 | 0.133678E+09 | 88.99 | 14-APR-21:40 | 20.20 | 8.15 |
May | 0.128999E+10 | 632.17 | 21-MAY-10:35 | 23.67 | 13.17 | 0.145284E+09 | 92.50 | 19-MAY-21:49 | 23.67 | 13.17 |
June | 0.145990E+10 | 925.67 | 28-JUN-19:10 | 31.83 | 17.06 | 0.149086E+09 | 92.66 | 23-JUN-21:10 | 31.83 | 17.06 |
July | 0.161178E+10 | 971.68 | 21-JUL-18:40 | 34.97 | 14.35 | 0.156876E+09 | 92.66 | 01-JUL-00:40 | 34.97 | 14.35 |
August | 0.153871E+10 | 860.92 | 18-AUG-19:40 | 28.33 | 14.33 | 0.156574E+09 | 92.66 | 21-AUG-00:00 | 24.40 | 16.61 |
September | 0.134240E+10 | 660.01 | 03-SEP-10:35 | 28.53 | 16.32 | 0.146581E+09 | 92.66 | 15-SEP-21:30 | 16.15 | 12.67 |
October | 0.122631E+10 | 642.97 | 01-OCT-10:35 | 22.97 | 13.29 | 0.139935E+09 | 92.09 | 02-OCT-21:40 | 18.30 | 13.96 |
November | 0.101600E+10 | 541.18 | 01-NOV-12:30 | 13.30 | 7.71 | 0.123886E+09 | 82.56 | 02-NOV-21:30 | 11.40 | 6.31 |
December | 0.855559E+09 | 481.79 | 31-DEC-13:00 | 8.30 | 1.00 | 0.119507E+09 | 77.27 | 01-DEC-22:30 | 8.30 | 1.00 |
Annual Sum or Average | 0.142590E+11 | 0.163227E+10 | ||||||||
Minimum of Months | 0.843725E+09 | 474.67 | 8.30 | 1.00 | 0.110780E+09 | 76.16 | 3.35 | -1.3 | ||
Maximum of Months | 0.161178E+10 | 971.68 | 34.97 | 17.06 | 0.156876E+09 | 92.66 | 34.97 | 17.06 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.489797E+11 | 37422.31 | 05-JAN-21:00 | 5.00 | -0.9 | 0.613868E+09 | 381.78 | 09-JAN-22:10 | 6.60 | 0.62 |
February | 0.445913E+11 | 37791.99 | 14-FEB-21:00 | 10.00 | 3.10 | 0.555633E+09 | 381.81 | 13-FEB-22:10 | 10.00 | 3.10 |
March | 0.503898E+11 | 38084.76 | 08-MAR-21:00 | 13.90 | 5.15 | 0.620302E+09 | 381.78 | 30-MAR-21:10 | 10.40 | 4.53 |
April | 0.497518E+11 | 38694.67 | 28-APR-20:00 | 22.20 | 8.52 | 0.602205E+09 | 381.86 | 07-APR-21:10 | 22.20 | 8.52 |
May | 0.520885E+11 | 38871.53 | 19-MAY-20:00 | 25.60 | 9.31 | 0.623850E+09 | 381.81 | 22-MAY-21:10 | 21.83 | 11.87 |
June | 0.515545E+11 | 39366.66 | 28-JUN-20:00 | 30.00 | 16.25 | 0.606457E+09 | 382.03 | 23-JUN-21:10 | 30.00 | 16.25 |
July | 0.535457E+11 | 39386.60 | 21-JUL-20:00 | 30.60 | 12.57 | 0.625514E+09 | 382.01 | 21-JUL-21:10 | 29.72 | 14.71 |
August | 0.535451E+11 | 39230.16 | 17-AUG-20:00 | 28.30 | 14.86 | 0.626563E+09 | 381.96 | 22-AUG-21:10 | 21.52 | 15.46 |
September | 0.509216E+11 | 38873.97 | 13-SEP-20:00 | 23.90 | 12.88 | 0.603131E+09 | 381.91 | 11-SEP-21:10 | 23.90 | 12.88 |
October | 0.513327E+11 | 38597.75 | 02-OCT-20:00 | 18.90 | 14.94 | 0.619795E+09 | 381.85 | 05-OCT-21:10 | 18.98 | 9.83 |
November | 0.483818E+11 | 37730.91 | 09-NOV-21:00 | 12.20 | 8.48 | 0.597455E+09 | 381.83 | 07-NOV-22:10 | 12.20 | 8.48 |
December | 0.488227E+11 | 37412.56 | 01-DEC-21:00 | 9.40 | 2.54 | 0.614211E+09 | 381.77 | 29-DEC-22:10 | 2.12 | -1.4 |
Annual Sum or Average | 0.603905E+12 | 0.730898E+10 | ||||||||
Minimum of Months | 0.445913E+11 | 37412.56 | 5.00 | -0.9 | 0.555633E+09 | 381.77 | 2.12 | -1.4 | ||
Maximum of Months | 0.535457E+11 | 39386.60 | 30.60 | 16.25 | 0.626563E+09 | 382.03 | 30.00 | 16.25 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.193182E+11 | 15628.12 | 01-JAN-13:00 | 13.30 | 4.92 | 0.104403E+11 | 6461.36 | 03-JAN-01:19 | 1.50 | -0.5 |
February | 0.179448E+11 | 15548.23 | 14-FEB-13:10 | 19.60 | 6.70 | 0.955580E+10 | 6461.83 | 11-FEB-02:20 | 19.60 | 6.70 |
March | 0.194729E+11 | 14192.81 | 11-MAR-13:30 | 16.40 | 4.98 | 0.107254E+11 | 6462.12 | 25-MAR-01:19 | 4.83 | -0.5 |
April | 0.193921E+11 | 11843.73 | 01-APR-13:30 | 21.65 | 7.61 | 0.104817E+11 | 6462.65 | 25-APR-22:10 | 17.33 | 6.17 |
May | 0.197798E+11 | 10645.12 | 19-MAY-21:05 | 23.12 | 8.19 | 0.108370E+11 | 6462.74 | 17-MAY-22:10 | 23.12 | 8.19 |
June | 0.209095E+11 | 11729.85 | 27-JUN-21:10 | 28.85 | 14.13 | 0.105858E+11 | 6462.79 | 01-JUN-00:00 | 28.85 | 14.13 |
July | 0.233899E+11 | 11975.89 | 21-JUL-21:10 | 29.72 | 14.71 | 0.109598E+11 | 6463.29 | 01-JUL-00:40 | 29.72 | 14.71 |
August | 0.244677E+11 | 12559.92 | 20-AUG-12:00 | 32.80 | 17.08 | 0.110082E+11 | 6462.71 | 23-AUG-22:10 | 19.40 | 14.62 |
September | 0.239937E+11 | 14367.47 | 28-SEP-13:10 | 29.08 | 15.59 | 0.106153E+11 | 6462.74 | 22-SEP-22:10 | 29.08 | 15.59 |
October | 0.237573E+11 | 15465.21 | 15-OCT-12:00 | 16.70 | 6.24 | 0.108600E+11 | 6462.61 | 04-OCT-22:10 | 16.70 | 6.24 |
November | 0.207246E+11 | 16013.15 | 23-NOV-11:00 | 8.90 | 2.63 | 0.103800E+11 | 6461.99 | 01-NOV-00:00 | 8.90 | 2.63 |
December | 0.197767E+11 | 16174.45 | 31-DEC-13:00 | 8.30 | 1.00 | 0.104891E+11 | 6461.78 | 30-DEC-02:20 | 8.30 | 1.00 |
Annual Sum or Average | 0.252927E+12 | 0.126938E+12 | ||||||||
Minimum of Months | 0.179448E+11 | 10645.12 | 8.30 | 1.00 | 0.955580E+10 | 6461.36 | 1.50 | -0.5 | ||
Maximum of Months | 0.244677E+11 | 16174.45 | 32.80 | 17.08 | 0.110082E+11 | 6463.29 | 29.72 | 15.59 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.585149E+11 | 32666.10 | 03-JAN-21:10 | 3.25 | -0.5 | 0.318051E+11 | 19185.07 | 28-JAN-02:20 | -2.4 | -5.6 |
February | 0.542896E+11 | 35750.41 | 14-FEB-22:10 | 10.60 | 3.54 | 0.289510E+11 | 19185.07 | 11-FEB-02:20 | 10.60 | 3.54 |
March | 0.622879E+11 | 35771.20 | 08-MAR-21:03 | 13.62 | 5.13 | 0.323310E+11 | 19185.49 | 25-MAR-01:19 | 4.83 | -0.5 |
April | 0.643159E+11 | 38389.68 | 13-APR-21:10 | 20.63 | 7.48 | 0.313179E+11 | 19186.06 | 25-APR-22:10 | 17.33 | 6.17 |
May | 0.687335E+11 | 39007.20 | 19-MAY-21:05 | 23.12 | 8.19 | 0.323726E+11 | 19188.48 | 01-MAY-01:10 | 23.12 | 8.19 |
June | 0.725835E+11 | 42394.38 | 28-JUN-21:10 | 28.62 | 15.82 | 0.315303E+11 | 19188.72 | 01-JUN-01:10 | 28.62 | 15.82 |
July | 0.787747E+11 | 43028.96 | 21-JUL-21:10 | 29.72 | 14.71 | 0.325646E+11 | 19188.67 | 01-JUL-00:40 | 29.72 | 14.71 |
August | 0.795336E+11 | 42547.33 | 18-AUG-21:10 | 25.73 | 12.99 | 0.327281E+11 | 19186.15 | 23-AUG-22:10 | 19.40 | 14.62 |
September | 0.748583E+11 | 41053.03 | 13-SEP-21:10 | 21.60 | 12.51 | 0.315877E+11 | 19186.54 | 22-SEP-21:00 | 19.40 | 14.15 |
October | 0.714236E+11 | 40367.26 | 06-OCT-21:10 | 19.90 | 11.23 | 0.324991E+11 | 19186.05 | 04-OCT-22:10 | 19.90 | 11.23 |
November | 0.619111E+11 | 35803.95 | 01-NOV-21:10 | 7.88 | 4.75 | 0.312510E+11 | 19186.65 | 01-NOV-01:10 | 7.88 | 4.75 |
December | 0.585845E+11 | 32108.48 | 19-DEC-19:05 | 4.22 | -2.4 | 0.319024E+11 | 19185.07 | 16-DEC-02:20 | 4.22 | -2.4 |
Annual Sum or Average | 0.805811E+12 | 0.380841E+12 | ||||||||
Minimum of Months | 0.542896E+11 | 32108.48 | 3.25 | -2.4 | 0.289510E+11 | 19185.07 | -2.4 | -5.6 | ||
Maximum of Months | 0.795336E+11 | 43028.96 | 29.72 | 15.82 | 0.327281E+11 | 19188.72 | 29.72 | 15.82 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.362419E+09 | 2444.46 | 15-JAN-16:01 | 11.42 | 3.23 | 96894416.53 | 56.69 | 25-JAN-05:19 | -3.0 | -5.1 |
February | 0.500090E+09 | 2560.96 | 14-FEB-16:01 | 22.02 | 7.76 | 88033910.97 | 56.69 | 14-FEB-22:00 | 10.60 | 3.54 |
March | 0.801695E+09 | 2558.87 | 07-MAR-16:01 | 21.52 | 8.96 | 98122228.94 | 56.69 | 08-MAR-22:00 | 7.20 | 2.38 |
April | 0.143374E+10 | 2567.58 | 13-APR-15:02 | 25.10 | 9.79 | 95523749.67 | 56.69 | 20-APR-21:30 | 13.90 | 5.53 |
May | 0.173244E+10 | 2555.83 | 20-MAY-15:02 | 26.78 | 10.96 | 98966233.42 | 56.70 | 17-MAY-21:40 | 26.78 | 10.96 |
June | 0.232803E+10 | 2586.10 | 20-JUN-18:02 | 30.22 | 11.49 | 96721310.13 | 56.70 | 23-JUN-21:10 | 26.60 | 15.77 |
July | 0.267539E+10 | 2448.20 | 02-JUL-18:02 | 31.42 | 16.51 | 99664767.37 | 56.70 | 10-JUL-21:10 | 25.13 | 16.69 |
August | 0.267522E+10 | 2545.22 | 23-AUG-18:01 | 23.62 | 15.24 | 99616296.72 | 56.70 | 11-AUG-21:10 | 23.62 | 15.24 |
September | 0.224494E+10 | 2393.22 | 08-SEP-15:02 | 20.92 | 13.55 | 96227878.40 | 56.70 | 22-SEP-21:40 | 19.23 | 13.09 |
October | 0.161139E+10 | 2582.34 | 19-OCT-15:02 | 22.80 | 8.67 | 98812990.15 | 56.69 | 02-OCT-21:00 | 22.80 | 8.67 |
November | 0.680526E+09 | 2465.60 | 03-NOV-15:02 | 12.70 | 2.73 | 94822718.83 | 56.69 | 01-NOV-01:10 | 12.70 | 2.73 |
December | 0.319953E+09 | 2428.49 | 31-DEC-16:02 | 9.82 | 1.41 | 96831183.42 | 56.69 | 26-DEC-05:19 | 9.82 | 1.41 |
Annual Sum or Average | 0.173658E+11 | 0.116024E+10 | ||||||||
Minimum of Months | 0.319953E+09 | 2393.22 | 9.82 | 1.41 | 88033910.97 | 56.69 | -3.0 | -5.1 | ||
Maximum of Months | 0.267539E+10 | 2586.10 | 31.42 | 16.51 | 99664767.37 | 56.70 | 26.78 | 16.69 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 77638142.89 | 2342.96 | 02-JAN-16:01 | 13.85 | 5.45 | 95026333.57 | 56.69 | 12-JAN-05:19 | -2.1 | -2.7 |
February | 0.168728E+09 | 2462.38 | 14-FEB-16:01 | 22.02 | 7.76 | 86868912.83 | 56.69 | 15-FEB-22:10 | 6.60 | 2.40 |
March | 0.360512E+09 | 2779.78 | 30-MAR-18:11 | 13.50 | 4.61 | 99286369.85 | 73.12 | 24-MAR-18:10 | 13.50 | 4.61 |
April | 0.954682E+09 | 2909.00 | 25-APR-16:21 | 24.40 | 9.58 | 0.101361E+09 | 81.60 | 24-APR-18:10 | 24.40 | 9.58 |
May | 0.144176E+10 | 2676.52 | 20-MAY-21:51 | 21.10 | 7.48 | 0.104928E+09 | 87.14 | 26-MAY-18:10 | 22.43 | 11.72 |
June | 0.216755E+10 | 2766.52 | 14-JUN-08:21 | 26.10 | 11.81 | 0.101323E+09 | 89.27 | 09-JUN-18:10 | 26.10 | 11.81 |
July | 0.243536E+10 | 2796.96 | 06-JUL-08:61 | 25.87 | 16.03 | 0.104208E+09 | 84.26 | 31-JUL-21:30 | 21.60 | 17.59 |
August | 0.226503E+10 | 2776.36 | 29-AUG-16:31 | 24.07 | 16.33 | 0.104988E+09 | 87.61 | 23-AUG-21:10 | 24.07 | 16.33 |
September | 0.160036E+10 | 2605.35 | 01-SEP-21:51 | 20.00 | 13.77 | 0.102878E+09 | 80.02 | 12-SEP-21:10 | 21.32 | 12.19 |
October | 0.842309E+09 | 2497.59 | 17-OCT-19:21 | 14.15 | 5.78 | 0.103492E+09 | 78.24 | 04-OCT-21:10 | 14.15 | 5.78 |
November | 0.213789E+09 | 2373.85 | 03-NOV-15:02 | 12.70 | 2.73 | 93462385.65 | 58.76 | 02-NOV-18:10 | 12.70 | 2.73 |
December | 52397176.70 | 2341.68 | 02-DEC-16:01 | 11.10 | 3.02 | 94653340.34 | 56.69 | 12-DEC-05:19 | -3.5 | -6.2 |
Annual Sum or Average | 0.125801E+11 | 0.119248E+10 | ||||||||
Minimum of Months | 52397176.70 | 2341.68 | 11.10 | 2.73 | 86868912.83 | 56.69 | -3.5 | -6.2 | ||
Maximum of Months | 0.243536E+10 | 2909.00 | 26.10 | 16.33 | 0.104988E+09 | 89.27 | 26.10 | 17.59 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.388232E+09 | 726.54 | 03-JAN-12:40 | 13.17 | 5.04 | 0.00 | 0.00 | 01-JAN-00:10 | 13.17 | 5.04 |
February | 0.372750E+09 | 741.30 | 14-FEB-13:00 | 19.40 | 6.65 | 0.00 | 0.00 | 01-FEB-00:10 | 19.40 | 6.65 |
March | 0.364297E+09 | 626.27 | 08-MAR-13:30 | 21.40 | 9.29 | 0.00 | 0.00 | 01-MAR-00:10 | 21.40 | 9.29 |
April | 0.384490E+09 | 458.24 | 13-APR-13:15 | 24.07 | 9.13 | 0.00 | 0.00 | 01-APR-00:10 | 24.07 | 9.13 |
May | 0.364884E+09 | 326.21 | 13-MAY-13:05 | 28.40 | 11.85 | 0.00 | 0.00 | 01-MAY-00:10 | 28.40 | 11.85 |
June | 0.467692E+09 | 366.41 | 29-JUN-16:10 | 35.03 | 16.44 | 0.00 | 0.00 | 01-JUN-00:10 | 35.03 | 16.44 |
July | 0.616199E+09 | 400.08 | 23-JUL-13:30 | 36.15 | 17.47 | 0.00 | 0.00 | 01-JUL-00:10 | 36.15 | 17.47 |
August | 0.688326E+09 | 522.77 | 22-AUG-13:30 | 31.40 | 16.68 | 0.00 | 0.00 | 01-AUG-00:10 | 31.40 | 16.68 |
September | 0.714727E+09 | 676.02 | 28-SEP-13:30 | 29.45 | 15.27 | 0.00 | 0.00 | 01-SEP-00:10 | 29.45 | 15.27 |
October | 0.688296E+09 | 730.93 | 19-OCT-12:25 | 20.55 | 8.60 | 0.00 | 0.00 | 01-OCT-00:10 | 20.55 | 8.60 |
November | 0.526588E+09 | 730.01 | 20-NOV-12:10 | 12.88 | 3.87 | 0.00 | 0.00 | 01-NOV-00:10 | 12.88 | 3.87 |
December | 0.429279E+09 | 741.06 | 31-DEC-13:40 | 9.43 | 1.41 | 0.00 | 0.00 | 01-DEC-00:10 | 9.43 | 1.41 |
Annual Sum or Average | 0.600576E+10 | 0.00 | ||||||||
Minimum of Months | 0.364297E+09 | 326.21 | 9.43 | 1.41 | 0.00 | 0.00 | 9.43 | 1.41 | ||
Maximum of Months | 0.714727E+09 | 741.30 | 36.15 | 17.47 | 0.00 | 0.00 | 36.15 | 17.47 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 57735431.09 | 702.35 | 01-JAN-09:02 | 2.67 | -1.3 | 95398890.44 | 56.69 | 24-JAN-05:19 | -1.9 | -4.3 |
February | 0.101257E+09 | 746.15 | 15-FEB-19:01 | 9.50 | 2.34 | 86601934.18 | 56.69 | 15-FEB-22:10 | 6.60 | 2.40 |
March | 0.251446E+09 | 773.59 | 27-MAR-15:02 | 18.40 | 7.10 | 97347754.87 | 60.12 | 13-MAR-20:49 | 18.40 | 7.10 |
April | 0.419706E+09 | 838.66 | 27-APR-21:51 | 17.80 | 7.06 | 97647692.95 | 73.94 | 27-APR-21:49 | 17.80 | 7.06 |
May | 0.589858E+09 | 855.82 | 20-MAY-21:51 | 21.10 | 7.48 | 0.102267E+09 | 76.71 | 26-MAY-21:49 | 16.88 | 10.38 |
June | 0.800402E+09 | 889.00 | 14-JUN-08:21 | 26.10 | 11.81 | 99221931.67 | 76.67 | 05-JUN-21:49 | 26.10 | 11.81 |
July | 0.891118E+09 | 860.78 | 27-JUL-21:51 | 22.20 | 15.31 | 0.102644E+09 | 78.15 | 31-JUL-21:49 | 21.53 | 17.38 |
August | 0.807867E+09 | 868.36 | 22-AUG-21:51 | 20.60 | 15.18 | 0.102940E+09 | 78.08 | 23-AUG-21:00 | 19.40 | 14.71 |
September | 0.590175E+09 | 839.19 | 30-SEP-21:51 | 18.00 | 8.68 | 0.100343E+09 | 74.67 | 12-SEP-21:10 | 18.00 | 8.68 |
October | 0.369758E+09 | 824.32 | 05-OCT-21:51 | 19.40 | 9.99 | 99890813.43 | 74.96 | 02-OCT-21:49 | 19.40 | 9.99 |
November | 0.162038E+09 | 746.65 | 02-NOV-18:11 | 15.00 | 7.63 | 93122855.72 | 56.69 | 01-NOV-00:49 | 15.00 | 7.63 |
December | 47234284.75 | 712.85 | 01-DEC-19:02 | 11.52 | 3.77 | 95080287.62 | 56.69 | 28-DEC-05:19 | -1.3 | -2.8 |
Annual Sum or Average | 0.508860E+10 | 0.117251E+10 | ||||||||
Minimum of Months | 47234284.75 | 702.35 | 2.67 | -1.3 | 86601934.18 | 56.69 | -1.9 | -4.3 | ||
Maximum of Months | 0.891118E+09 | 889.00 | 26.10 | 15.31 | 0.102940E+09 | 78.15 | 26.10 | 17.38 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.357182E+09 | 2152.43 | 27-JAN-09:02 | 0.97 | -3.6 | 97177996.14 | 56.69 | 19-JAN-05:19 | 0.97 | -3.6 |
February | 0.453263E+09 | 2234.02 | 14-FEB-16:01 | 22.02 | 7.76 | 88287858.34 | 56.69 | 14-FEB-22:00 | 10.60 | 3.54 |
March | 0.867155E+09 | 2217.88 | 11-MAR-09:02 | 6.23 | 0.26 | 98543026.67 | 56.69 | 08-MAR-22:10 | 6.23 | 0.26 |
April | 0.160634E+10 | 2278.99 | 29-APR-08:61 | 15.37 | 5.61 | 95896414.54 | 56.69 | 17-APR-21:00 | 15.37 | 5.61 |
May | 0.191526E+10 | 2283.32 | 14-MAY-08:62 | 19.27 | 8.83 | 99183089.74 | 56.69 | 21-MAY-00:00 | 18.30 | 10.90 |
June | 0.254187E+10 | 2331.44 | 18-JUN-08:62 | 23.27 | 11.60 | 96329551.70 | 56.70 | 30-JUN-21:49 | 24.17 | 15.25 |
July | 0.293965E+10 | 2321.96 | 04-JUL-08:62 | 24.78 | 18.10 | 99353977.63 | 56.70 | 21-JUL-21:10 | 29.72 | 14.71 |
August | 0.287111E+10 | 2294.25 | 17-AUG-08:61 | 25.78 | 17.70 | 99415688.11 | 56.70 | 14-AUG-21:00 | 25.78 | 17.70 |
September | 0.231063E+10 | 2227.97 | 02-SEP-08:62 | 20.87 | 14.42 | 96118148.33 | 56.70 | 05-SEP-21:30 | 16.70 | 14.72 |
October | 0.162155E+10 | 2241.20 | 19-OCT-15:02 | 22.80 | 8.67 | 98908051.73 | 56.69 | 02-OCT-22:49 | 22.80 | 8.67 |
November | 0.686081E+09 | 2199.25 | 18-NOV-09:02 | 5.78 | 0.04 | 95074605.50 | 56.69 | 01-NOV-01:10 | 5.78 | 0.04 |
December | 0.308498E+09 | 2167.91 | 31-DEC-09:02 | -0.3 | -4.0 | 97204385.03 | 56.69 | 08-DEC-05:19 | -0.3 | -4.0 |
Annual Sum or Average | 0.184786E+11 | 0.116149E+10 | ||||||||
Minimum of Months | 0.308498E+09 | 2152.43 | -0.3 | -4.0 | 88287858.34 | 56.69 | -0.3 | -4.0 | ||
Maximum of Months | 0.293965E+10 | 2331.44 | 25.78 | 18.10 | 99415688.11 | 56.70 | 29.72 | 17.70 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 74611074.86 | 2021.05 | 27-JAN-09:02 | 0.97 | -3.6 | 94988021.36 | 56.69 | 19-JAN-05:19 | 0.97 | -3.6 |
February | 0.137839E+09 | 2144.36 | 14-FEB-16:01 | 22.02 | 7.76 | 86692458.55 | 56.69 | 14-FEB-22:10 | 10.60 | 3.54 |
March | 0.444758E+09 | 2171.98 | 26-MAR-08:62 | 8.27 | 2.30 | 98922184.37 | 61.41 | 13-MAR-20:40 | 8.27 | 2.30 |
April | 0.117647E+10 | 2612.36 | 28-APR-08:51 | 18.30 | 7.75 | 99989087.08 | 76.70 | 27-APR-21:40 | 18.30 | 7.75 |
May | 0.161628E+10 | 2775.61 | 14-MAY-08:32 | 20.37 | 9.41 | 0.104550E+09 | 78.14 | 26-MAY-21:30 | 17.25 | 10.44 |
June | 0.229838E+10 | 2877.01 | 14-JUN-08:62 | 25.37 | 11.65 | 0.102172E+09 | 79.62 | 13-JUN-21:00 | 25.37 | 11.65 |
July | 0.259289E+10 | 2929.13 | 04-JUL-08:62 | 24.78 | 18.10 | 0.106017E+09 | 82.09 | 31-JUL-21:30 | 21.60 | 17.59 |
August | 0.236207E+10 | 2810.35 | 05-AUG-08:32 | 23.50 | 15.12 | 0.106469E+09 | 83.79 | 03-AUG-21:10 | 23.50 | 15.12 |
September | 0.162288E+10 | 2686.89 | 02-SEP-08:32 | 21.67 | 14.85 | 0.103180E+09 | 79.22 | 12-SEP-21:10 | 21.32 | 12.19 |
October | 0.892454E+09 | 2496.10 | 11-OCT-08:51 | 20.60 | 15.46 | 0.102147E+09 | 77.66 | 02-OCT-21:40 | 20.60 | 15.46 |
November | 0.224695E+09 | 2115.83 | 24-NOV-09:02 | 6.47 | 0.37 | 93479272.34 | 56.69 | 01-NOV-00:49 | 6.47 | 0.37 |
December | 56253559.94 | 2069.48 | 31-DEC-09:02 | -0.3 | -4.0 | 94494777.58 | 56.69 | 15-DEC-05:19 | -0.3 | -4.0 |
Annual Sum or Average | 0.134996E+11 | 0.119310E+10 | ||||||||
Minimum of Months | 56253559.94 | 2021.05 | -0.3 | -4.0 | 86692458.55 | 56.69 | -0.3 | -4.0 | ||
Maximum of Months | 0.259289E+10 | 2929.13 | 25.37 | 18.10 | 0.106469E+09 | 83.79 | 25.37 | 17.59 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.319660E+10 | 1759.28 | 01-JAN-13:00 | 13.30 | 4.92 | 0.127863E+10 | 823.83 | 03-JAN-22:40 | 0.00 | -2.3 |
February | 0.308767E+10 | 1898.80 | 14-FEB-13:20 | 19.80 | 6.75 | 0.117317E+10 | 855.76 | 15-FEB-22:40 | 6.30 | 2.24 |
March | 0.373094E+10 | 1872.07 | 12-MAR-10:35 | 12.23 | 3.02 | 0.137248E+10 | 868.03 | 13-MAR-21:40 | 12.43 | 3.82 |
April | 0.403262E+10 | 2083.57 | 29-APR-10:33 | 20.20 | 8.15 | 0.141507E+10 | 925.64 | 28-APR-21:40 | 20.20 | 8.15 |
May | 0.440359E+10 | 2149.22 | 21-MAY-10:35 | 23.67 | 13.17 | 0.151404E+10 | 951.84 | 19-MAY-22:10 | 23.67 | 13.17 |
June | 0.485747E+10 | 3121.98 | 23-JUN-18:17 | 33.17 | 12.63 | 0.153298E+10 | 951.90 | 23-JUN-21:10 | 26.60 | 15.77 |
July | 0.532912E+10 | 3283.31 | 21-JUL-18:40 | 34.97 | 14.35 | 0.161153E+10 | 951.89 | 01-JUL-00:40 | 34.97 | 14.35 |
August | 0.533923E+10 | 3071.01 | 18-AUG-18:17 | 31.67 | 15.79 | 0.161761E+10 | 951.87 | 21-AUG-00:49 | 24.78 | 16.59 |
September | 0.477839E+10 | 2488.88 | 21-SEP-18:03 | 26.55 | 12.24 | 0.154350E+10 | 951.89 | 22-SEP-21:00 | 19.40 | 14.15 |
October | 0.442883E+10 | 2403.95 | 05-OCT-18:03 | 23.67 | 10.39 | 0.150774E+10 | 951.85 | 04-OCT-22:10 | 23.67 | 10.39 |
November | 0.361143E+10 | 1936.01 | 01-NOV-12:30 | 13.30 | 7.71 | 0.132288E+10 | 875.41 | 02-NOV-21:40 | 10.93 | 6.67 |
December | 0.319409E+10 | 1753.73 | 31-DEC-13:00 | 8.30 | 1.00 | 0.126176E+10 | 804.20 | 01-DEC-22:40 | 8.30 | 1.00 |
Annual Sum or Average | 0.499900E+11 | 0.171514E+11 | ||||||||
Minimum of Months | 0.308767E+10 | 1753.73 | 8.30 | 1.00 | 0.117317E+10 | 804.20 | 0.00 | -2.3 | ||
Maximum of Months | 0.533923E+10 | 3283.31 | 34.97 | 15.79 | 0.161761E+10 | 951.90 | 34.97 | 16.59 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.319532E+09 | 2588.40 | 05-JAN-16:01 | 15.63 | 6.64 | 96397792.49 | 56.69 | 19-JAN-05:19 | -3.0 | -3.1 |
February | 0.468164E+09 | 2709.87 | 14-FEB-16:01 | 22.02 | 7.76 | 87707781.10 | 56.69 | 14-FEB-22:00 | 10.60 | 3.54 |
March | 0.731791E+09 | 2706.73 | 07-MAR-16:01 | 21.52 | 8.96 | 97817694.87 | 56.69 | 08-MAR-22:19 | 10.53 | 4.18 |
April | 0.137823E+10 | 2723.23 | 13-APR-15:02 | 25.10 | 9.79 | 95380121.23 | 56.70 | 02-APR-04:49 | 25.10 | 9.79 |
May | 0.170092E+10 | 2714.70 | 20-MAY-18:02 | 26.23 | 10.63 | 98905845.37 | 56.69 | 17-MAY-23:10 | 26.23 | 10.63 |
June | 0.238621E+10 | 2749.64 | 20-JUN-18:02 | 30.22 | 11.49 | 96943581.54 | 57.91 | 23-JUN-18:10 | 33.53 | 12.64 |
July | 0.275921E+10 | 2636.32 | 28-JUL-18:02 | 28.95 | 17.44 | 99817732.80 | 56.70 | 11-JUL-21:10 | 28.95 | 17.44 |
August | 0.273115E+10 | 2659.32 | 23-AUG-18:01 | 23.62 | 15.24 | 99708210.21 | 56.70 | 01-AUG-21:10 | 23.62 | 15.24 |
September | 0.219047E+10 | 2556.60 | 02-SEP-18:02 | 29.45 | 14.81 | 96193611.70 | 56.70 | 24-SEP-04:00 | 11.70 | 11.03 |
October | 0.148488E+10 | 2732.31 | 19-OCT-15:02 | 22.80 | 8.67 | 98600355.55 | 56.70 | 10-OCT-21:10 | 22.80 | 8.67 |
November | 0.569428E+09 | 2608.69 | 20-NOV-16:02 | 14.63 | 5.01 | 94428936.58 | 56.69 | 03-NOV-01:19 | 14.63 | 5.01 |
December | 0.274266E+09 | 2573.30 | 31-DEC-16:02 | 9.82 | 1.41 | 96319654.48 | 56.69 | 06-DEC-05:19 | 9.82 | 1.41 |
Annual Sum or Average | 0.169942E+11 | 0.115822E+10 | ||||||||
Minimum of Months | 0.274266E+09 | 2556.60 | 9.82 | 1.41 | 87707781.10 | 56.69 | -3.0 | -3.1 | ||
Maximum of Months | 0.275921E+10 | 2749.64 | 30.22 | 17.44 | 99817732.80 | 57.91 | 33.53 | 17.44 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 66393531.87 | 2468.32 | 05-JAN-16:01 | 15.63 | 6.64 | 94374726.23 | 56.69 | 20-JAN-05:19 | -4.4 | -4.4 |
February | 0.146657E+09 | 2588.80 | 14-FEB-16:01 | 22.02 | 7.76 | 86467635.18 | 56.69 | 01-FEB-05:19 | 22.02 | 7.76 |
March | 0.301675E+09 | 2990.41 | 30-MAR-18:11 | 13.50 | 4.61 | 99197071.55 | 78.03 | 24-MAR-18:10 | 13.50 | 4.61 |
April | 0.908852E+09 | 3081.43 | 25-APR-16:21 | 24.40 | 9.58 | 0.101963E+09 | 87.53 | 24-APR-18:10 | 24.40 | 9.58 |
May | 0.143920E+10 | 2884.40 | 06-MAY-19:41 | 14.18 | 3.71 | 0.105219E+09 | 92.55 | 26-MAY-18:10 | 22.43 | 11.72 |
June | 0.226132E+10 | 2909.46 | 14-JUN-08:21 | 26.10 | 11.81 | 0.101640E+09 | 94.41 | 09-JUN-18:10 | 26.10 | 11.81 |
July | 0.256130E+10 | 2933.00 | 06-JUL-08:61 | 25.87 | 16.03 | 0.104079E+09 | 88.17 | 31-JUL-21:10 | 21.67 | 17.79 |
August | 0.236173E+10 | 2949.97 | 23-AUG-17:01 | 24.32 | 16.96 | 0.104828E+09 | 90.24 | 23-AUG-21:10 | 20.82 | 14.97 |
September | 0.157591E+10 | 2675.79 | 01-SEP-21:51 | 20.00 | 13.77 | 0.102540E+09 | 79.61 | 12-SEP-21:10 | 21.32 | 12.19 |
October | 0.730379E+09 | 2678.61 | 21-OCT-19:01 | 13.12 | 5.12 | 0.103460E+09 | 77.79 | 04-OCT-21:10 | 13.12 | 5.12 |
November | 0.150709E+09 | 2478.70 | 06-NOV-16:02 | 14.40 | 4.29 | 92865793.93 | 59.66 | 02-NOV-18:10 | 14.40 | 4.29 |
December | 41627152.88 | 2456.12 | 02-DEC-16:01 | 11.10 | 3.02 | 93973604.42 | 56.69 | 15-DEC-05:19 | -8.9 | -11.6 |
Annual Sum or Average | 0.125457E+11 | 0.119061E+10 | ||||||||
Minimum of Months | 41627152.88 | 2456.12 | 11.10 | 3.02 | 86467635.18 | 56.69 | -8.9 | -11.6 | ||
Maximum of Months | 0.256130E+10 | 3081.43 | 26.10 | 16.96 | 0.105219E+09 | 94.41 | 26.10 | 17.79 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.747986E+09 | 1369.03 | 03-JAN-13:53 | 15.00 | 5.83 | 98374168.00 | 56.69 | 26-JAN-22:10 | 1.28 | -4.0 |
February | 0.732279E+09 | 1364.56 | 13-FEB-13:25 | 19.45 | 6.81 | 89053038.53 | 56.69 | 15-FEB-22:00 | 6.10 | 2.13 |
March | 0.741791E+09 | 1318.07 | 12-MAR-15:02 | 19.90 | 6.21 | 98547876.12 | 56.69 | 24-MAR-21:30 | 9.45 | 1.97 |
April | 0.843517E+09 | 1314.68 | 01-APR-15:02 | 24.40 | 8.92 | 95514384.89 | 56.69 | 14-APR-21:19 | 18.53 | 9.74 |
May | 0.870356E+09 | 1287.31 | 20-MAY-15:02 | 26.78 | 10.96 | 98744690.49 | 56.69 | 17-MAY-22:49 | 26.78 | 10.96 |
June | 0.112585E+10 | 1282.56 | 20-JUN-15:02 | 31.10 | 11.59 | 95954690.21 | 56.69 | 24-JUN-01:39 | 23.67 | 15.60 |
July | 0.143799E+10 | 1274.66 | 27-JUL-18:02 | 27.43 | 15.80 | 99185092.30 | 56.70 | 24-JUL-22:10 | 27.43 | 15.80 |
August | 0.153792E+10 | 1284.74 | 27-AUG-15:02 | 27.93 | 16.23 | 99304458.08 | 56.70 | 22-AUG-21:49 | 27.93 | 16.23 |
September | 0.148605E+10 | 1285.18 | 25-SEP-15:02 | 27.30 | 14.24 | 96217842.40 | 56.69 | 22-SEP-23:40 | 27.30 | 14.24 |
October | 0.135282E+10 | 1389.48 | 15-OCT-15:08 | 21.02 | 8.07 | 99352061.10 | 56.81 | 06-OCT-21:10 | 21.02 | 8.07 |
November | 0.986957E+09 | 1369.40 | 07-NOV-13:23 | 13.85 | 4.69 | 95769885.08 | 56.69 | 02-NOV-22:19 | 13.85 | 4.69 |
December | 0.816486E+09 | 1348.49 | 30-DEC-13:35 | 10.20 | 2.31 | 98261484.96 | 56.69 | 29-DEC-22:19 | 10.20 | 2.31 |
Annual Sum or Average | 0.126800E+11 | 0.116428E+10 | ||||||||
Minimum of Months | 0.732279E+09 | 1274.66 | 10.20 | 2.31 | 89053038.53 | 56.69 | 1.28 | -4.0 | ||
Maximum of Months | 0.153792E+10 | 1389.48 | 31.10 | 16.23 | 99352061.10 | 56.81 | 27.93 | 16.23 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.313812E+11 | 17751.44 | 05-JAN-22:10 | 3.72 | -1.3 | 0.191507E+11 | 11346.95 | 28-JAN-02:20 | -2.4 | -5.6 |
February | 0.294009E+11 | 19091.31 | 14-FEB-23:00 | 10.60 | 3.54 | 0.173574E+11 | 11346.98 | 11-FEB-02:20 | 10.60 | 3.54 |
March | 0.351590E+11 | 19639.74 | 16-MAR-21:10 | 14.17 | 4.07 | 0.193544E+11 | 11347.75 | 25-MAR-01:19 | 4.83 | -0.5 |
April | 0.373178E+11 | 21517.66 | 28-APR-21:10 | 19.90 | 7.11 | 0.187078E+11 | 11348.91 | 25-APR-22:10 | 19.90 | 7.11 |
May | 0.409801E+11 | 22271.57 | 19-MAY-21:05 | 23.12 | 8.19 | 0.193458E+11 | 11367.88 | 31-MAY-21:19 | 21.37 | 8.56 |
June | 0.429944E+11 | 23552.36 | 27-JUN-21:20 | 28.30 | 13.90 | 0.187608E+11 | 11389.81 | 23-JUN-21:19 | 28.30 | 13.90 |
July | 0.456244E+11 | 23701.60 | 21-JUL-21:20 | 29.43 | 14.70 | 0.193106E+11 | 11388.88 | 21-JUL-21:19 | 29.43 | 14.70 |
August | 0.448351E+11 | 23004.85 | 17-AUG-22:00 | 27.20 | 14.57 | 0.193916E+11 | 11371.60 | 22-AUG-21:19 | 21.33 | 15.41 |
September | 0.408124E+11 | 22069.38 | 01-SEP-21:10 | 20.92 | 14.02 | 0.187096E+11 | 11349.00 | 22-SEP-22:10 | 19.03 | 14.04 |
October | 0.378930E+11 | 21572.95 | 02-OCT-21:52 | 18.30 | 13.73 | 0.192841E+11 | 11348.80 | 04-OCT-22:10 | 17.70 | 10.79 |
November | 0.325606E+11 | 19393.52 | 02-NOV-21:10 | 12.33 | 5.44 | 0.185964E+11 | 11347.00 | 14-NOV-05:19 | 4.23 | -0.3 |
December | 0.309834E+11 | 18279.27 | 01-DEC-22:10 | 8.95 | 2.17 | 0.191305E+11 | 11346.93 | 16-DEC-02:20 | -1.9 | -6.9 |
Annual Sum or Average | 0.449942E+12 | 0.227099E+12 | ||||||||
Minimum of Months | 0.294009E+11 | 17751.44 | 3.72 | -1.3 | 0.173574E+11 | 11346.93 | -2.4 | -6.9 | ||
Maximum of Months | 0.456244E+11 | 23701.60 | 29.43 | 14.70 | 0.193916E+11 | 11389.81 | 29.43 | 15.41 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.350604E+11 | 19497.50 | 05-JAN-22:10 | 3.72 | -1.3 | 0.192483E+11 | 11347.04 | 28-JAN-02:20 | -2.4 | -5.6 |
February | 0.327298E+11 | 20584.23 | 14-FEB-23:00 | 10.60 | 3.54 | 0.174216E+11 | 11347.06 | 25-FEB-02:20 | -1.8 | -3.5 |
March | 0.388218E+11 | 21176.23 | 16-MAR-21:10 | 14.17 | 4.07 | 0.193902E+11 | 11347.85 | 25-MAR-01:19 | 4.83 | -0.5 |
April | 0.405959E+11 | 22756.34 | 28-APR-21:10 | 19.90 | 7.11 | 0.187183E+11 | 11348.92 | 25-APR-22:10 | 19.90 | 7.11 |
May | 0.441427E+11 | 23471.06 | 19-MAY-21:05 | 23.12 | 8.19 | 0.193501E+11 | 11385.38 | 31-MAY-21:19 | 21.37 | 8.56 |
June | 0.458354E+11 | 24738.17 | 27-JUN-21:20 | 28.30 | 13.90 | 0.187615E+11 | 11399.22 | 23-JUN-21:19 | 28.30 | 13.90 |
July | 0.484179E+11 | 24884.71 | 21-JUL-21:20 | 29.43 | 14.70 | 0.193109E+11 | 11396.22 | 21-JUL-21:19 | 29.43 | 14.70 |
August | 0.476178E+11 | 24177.55 | 17-AUG-21:20 | 26.87 | 14.49 | 0.193923E+11 | 11381.83 | 02-AUG-21:19 | 26.87 | 14.49 |
September | 0.435513E+11 | 23226.22 | 01-SEP-21:20 | 20.73 | 13.98 | 0.187107E+11 | 11360.92 | 29-SEP-21:19 | 20.40 | 12.01 |
October | 0.409979E+11 | 22696.94 | 02-OCT-21:10 | 18.30 | 14.29 | 0.193063E+11 | 11348.81 | 04-OCT-22:10 | 17.70 | 10.79 |
November | 0.359860E+11 | 20972.80 | 08-NOV-22:10 | 13.62 | 7.41 | 0.186515E+11 | 11347.20 | 01-NOV-00:49 | 13.62 | 7.41 |
December | 0.346473E+11 | 20079.74 | 01-DEC-22:10 | 8.95 | 2.17 | 0.192358E+11 | 11347.03 | 16-DEC-02:20 | -1.9 | -6.9 |
Annual Sum or Average | 0.488404E+12 | 0.227497E+12 | ||||||||
Minimum of Months | 0.327298E+11 | 19497.50 | 3.72 | -1.3 | 0.174216E+11 | 11347.03 | -2.4 | -6.9 | ||
Maximum of Months | 0.484179E+11 | 24884.71 | 29.43 | 14.70 | 0.193923E+11 | 11399.22 | 29.43 | 14.70 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.503660E+11 | 28127.91 | 01-JAN-11:40 | 9.83 | 3.02 | 0.188476E+11 | 11319.48 | 14-JAN-18:19 | 3.30 | -2.2 |
February | 0.463054E+11 | 28779.56 | 14-FEB-11:40 | 16.47 | 5.70 | 0.170278E+11 | 11319.53 | 25-FEB-18:19 | 9.43 | 2.53 |
March | 0.530792E+11 | 29785.96 | 12-MAR-10:40 | 12.23 | 3.02 | 0.188676E+11 | 11319.66 | 11-MAR-18:19 | 12.23 | 3.02 |
April | 0.537772E+11 | 30806.48 | 29-APR-10:33 | 20.20 | 8.15 | 0.182596E+11 | 11319.65 | 01-APR-17:19 | 20.20 | 8.15 |
May | 0.567860E+11 | 30860.90 | 20-MAY-10:37 | 22.40 | 8.51 | 0.188708E+11 | 11319.63 | 13-MAY-17:19 | 22.40 | 8.51 |
June | 0.571636E+11 | 31481.11 | 29-JUN-10:40 | 32.60 | 16.86 | 0.182661E+11 | 11319.66 | 03-JUN-17:19 | 32.60 | 16.86 |
July | 0.600060E+11 | 31783.26 | 23-JUL-10:40 | 31.83 | 17.15 | 0.188685E+11 | 11319.64 | 29-JUL-17:19 | 29.80 | 16.42 |
August | 0.596113E+11 | 31748.10 | 20-AUG-10:40 | 30.17 | 17.03 | 0.188757E+11 | 11319.64 | 19-AUG-17:19 | 30.17 | 17.03 |
September | 0.559382E+11 | 31569.11 | 03-SEP-10:40 | 28.53 | 16.32 | 0.182617E+11 | 11319.64 | 09-SEP-17:19 | 23.70 | 15.03 |
October | 0.549384E+11 | 30911.27 | 01-OCT-10:40 | 22.97 | 13.29 | 0.188653E+11 | 11319.64 | 14-OCT-17:19 | 18.67 | 7.28 |
November | 0.503426E+11 | 29104.29 | 01-NOV-10:33 | 13.13 | 7.69 | 0.182482E+11 | 11319.88 | 18-NOV-18:19 | 10.20 | 1.74 |
December | 0.501638E+11 | 28044.72 | 30-DEC-11:45 | 8.03 | 1.40 | 0.188472E+11 | 11319.58 | 09-DEC-18:19 | 8.03 | 1.40 |
Annual Sum or Average | 0.648478E+12 | 0.222106E+12 | ||||||||
Minimum of Months | 0.463054E+11 | 28044.72 | 8.03 | 1.40 | 0.170278E+11 | 11319.48 | 3.30 | -2.2 | ||
Maximum of Months | 0.600060E+11 | 31783.26 | 32.60 | 17.15 | 0.188757E+11 | 11319.88 | 32.60 | 17.03 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.575011E+10 | 3728.08 | 01-JAN-13:00 | 13.30 | 4.92 | 0.131254E+10 | 824.12 | 02-JAN-22:30 | 2.80 | -0.5 |
February | 0.582825E+10 | 4217.00 | 14-FEB-13:20 | 19.80 | 6.75 | 0.121248E+10 | 894.20 | 14-FEB-22:30 | 10.60 | 3.54 |
March | 0.748161E+10 | 3912.52 | 08-MAR-11:33 | 17.07 | 7.88 | 0.141231E+10 | 908.12 | 13-MAR-21:30 | 12.25 | 3.71 |
April | 0.831092E+10 | 4742.32 | 13-APR-15:02 | 25.10 | 9.79 | 0.147461E+10 | 996.73 | 13-APR-21:30 | 19.70 | 7.05 |
May | 0.931787E+10 | 5385.39 | 20-MAY-14:20 | 25.97 | 10.20 | 0.159393E+10 | 1007.40 | 31-MAY-22:10 | 20.52 | 8.76 |
June | 0.108388E+11 | 7114.41 | 28-JUN-15:05 | 38.40 | 14.30 | 0.161745E+10 | 1007.46 | 23-JUN-21:10 | 38.40 | 14.30 |
July | 0.122709E+11 | 7179.05 | 22-JUL-13:30 | 36.95 | 17.78 | 0.169840E+10 | 1007.50 | 01-JUL-00:40 | 36.95 | 17.78 |
August | 0.120816E+11 | 7245.12 | 20-AUG-13:10 | 33.07 | 17.06 | 0.170014E+10 | 1007.44 | 21-AUG-00:40 | 25.17 | 16.57 |
September | 0.103562E+11 | 7136.49 | 03-SEP-13:30 | 31.95 | 16.76 | 0.160816E+10 | 1007.47 | 22-SEP-21:00 | 19.40 | 14.15 |
October | 0.895846E+10 | 6491.99 | 01-OCT-13:30 | 27.75 | 13.90 | 0.154401E+10 | 1007.39 | 06-OCT-22:10 | 19.22 | 11.09 |
November | 0.706108E+10 | 4097.22 | 01-NOV-12:30 | 13.30 | 7.71 | 0.133917E+10 | 904.35 | 02-NOV-21:30 | 11.40 | 6.31 |
December | 0.560380E+10 | 3790.93 | 31-DEC-13:00 | 8.30 | 1.00 | 0.130534E+10 | 817.63 | 01-DEC-22:40 | 8.30 | 1.00 |
Annual Sum or Average | 0.103860E+12 | 0.178185E+11 | ||||||||
Minimum of Months | 0.560380E+10 | 3728.08 | 8.30 | 1.00 | 0.121248E+10 | 817.63 | 2.80 | -0.5 | ||
Maximum of Months | 0.122709E+11 | 7245.12 | 38.40 | 17.78 | 0.170014E+10 | 1007.50 | 38.40 | 17.78 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 13795522.14 | 336.40 | 19-JAN-07:10 | -2.8 |
February | 1175621.79 | 171.02 | 06-FEB-07:05 | -5.4 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.88 |
October | 203857.39 | 128.39 | 26-OCT-06:15 | -1.7 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 12.83 |
December | 9851545.59 | 413.98 | 09-DEC-07:20 | -2.9 |
Annual Sum or Average | 25026546.91 | |||
Minimum of Months | 0.00 | 0.00 | -5.4 | |
Maximum of Months | 13795522.14 | 413.98 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 57723.83 | 12.37 | 19-JAN-11:15 | -0.2 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 |
Annual Sum or Average | 57723.83 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 57723.83 | 12.37 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.343577E+09 | 1341.14 | 17-JAN-09:02 | -2.5 |
February | 0.209012E+09 | 1306.49 | 06-FEB-09:02 | -2.0 |
March | 63871737.49 | 853.33 | 22-MAR-08:62 | 4.87 |
April | 4628517.13 | 714.20 | 30-APR-08:04 | 15.10 |
May | 2209056.53 | 908.62 | 24-MAY-15:04 | 16.52 |
June | 388188.88 | 706.07 | 08-JUN-15:05 | 15.50 |
July | 79942.42 | 276.30 | 28-JUL-08:05 | 22.57 |
August | 420990.76 | 467.99 | 28-AUG-08:05 | 19.08 |
September | 601487.15 | 421.92 | 18-SEP-08:05 | 15.97 |
October | 32053133.02 | 1299.34 | 25-OCT-08:62 | 0.22 |
November | 85768830.71 | 1109.69 | 10-NOV-19:02 | 6.10 |
December | 0.351283E+09 | 1340.01 | 21-DEC-16:02 | -1.1 |
Annual Sum or Average | 0.109389E+10 | |||
Minimum of Months | 79942.42 | 276.30 | -2.5 | |
Maximum of Months | 0.351283E+09 | 1341.14 | 22.57 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.612358E+09 | 1351.96 | 17-JAN-09:02 | -2.5 |
February | 0.383569E+09 | 1348.95 | 06-FEB-09:02 | -2.0 |
March | 0.107609E+09 | 1261.05 | 04-MAR-09:02 | 2.15 |
April | 6530335.06 | 713.16 | 03-APR-08:03 | 10.28 |
May | 1929113.97 | 846.91 | 24-MAY-15:04 | 16.52 |
June | 224727.48 | 493.11 | 08-JUN-15:05 | 15.50 |
July | 15398.18 | 114.50 | 29-JUL-21:55 | 23.30 |
August | 43354.56 | 225.05 | 30-AUG-21:55 | 22.80 |
September | 273077.70 | 534.44 | 18-SEP-08:05 | 15.97 |
October | 51057875.68 | 1322.78 | 26-OCT-08:62 | 1.97 |
November | 0.204664E+09 | 1317.43 | 27-NOV-09:02 | -1.2 |
December | 0.685252E+09 | 1363.74 | 22-DEC-09:02 | -5.2 |
Annual Sum or Average | 0.205353E+10 | |||
Minimum of Months | 15398.18 | 114.50 | -5.2 | |
Maximum of Months | 0.685252E+09 | 1363.74 | 23.30 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 42397518.93 | 382.74 | 19-JAN-16:02 | 3.62 |
February | 24811266.30 | 405.14 | 19-FEB-16:03 | 15.82 |
March | 1127365.99 | 398.88 | 14-MAR-15:04 | 16.42 |
April | 175900.67 | 218.73 | 08-APR-15:05 | 13.98 |
May | 54047.53 | 182.40 | 06-MAY-15:05 | 17.88 |
June | 2696.64 | 26.97 | 08-JUN-08:57 | 17.20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 9.24 | 0.14 | 29-AUG-08:56 | 20.00 |
September | 9723.20 | 81.03 | 21-SEP-08:56 | 21.10 |
October | 717424.22 | 328.70 | 29-OCT-15:04 | 17.88 |
November | 4946226.13 | 393.46 | 09-NOV-16:05 | 16.52 |
December | 64913651.60 | 390.09 | 15-DEC-16:02 | 4.13 |
Annual Sum or Average | 0.139156E+09 | |||
Minimum of Months | 0.00 | 0.00 | 3.62 | |
Maximum of Months | 64913651.60 | 405.14 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.368095E+09 | 1314.15 | 17-JAN-16:02 | 1.32 |
February | 0.229307E+09 | 1285.51 | 16-FEB-16:02 | 1.70 |
March | 64489887.29 | 848.59 | 22-MAR-08:62 | 4.87 |
April | 4134657.86 | 537.54 | 07-APR-18:05 | 10.92 |
May | 532013.75 | 553.72 | 04-MAY-18:05 | 10.92 |
June | 103526.29 | 468.55 | 08-JUN-18:05 | 11.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 20.95 |
September | 35159.16 | 168.10 | 23-SEP-08:05 | 17.38 |
October | 32636470.50 | 1269.03 | 25-OCT-08:62 | 0.22 |
November | 95286396.83 | 1071.38 | 10-NOV-19:02 | 6.10 |
December | 0.370059E+09 | 1301.07 | 08-DEC-09:02 | -0.5 |
Annual Sum or Average | 0.116468E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.5 | |
Maximum of Months | 0.370059E+09 | 1314.15 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.626771E+09 | 1325.04 | 20-JAN-09:02 | -3.2 |
February | 0.399502E+09 | 1297.91 | 05-FEB-19:02 | -1.2 |
March | 0.103870E+09 | 996.98 | 14-MAR-15:04 | 16.42 |
April | 7677026.19 | 531.89 | 08-APR-15:05 | 13.98 |
May | 779034.18 | 565.24 | 04-MAY-18:05 | 10.92 |
June | 75108.37 | 453.15 | 08-JUN-18:05 | 11.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 25384.35 | 201.31 | 30-AUG-21:55 | 22.80 |
September | 85238.63 | 341.64 | 08-SEP-21:55 | 15.60 |
October | 49519512.29 | 1272.03 | 25-OCT-08:62 | 0.22 |
November | 0.205815E+09 | 1257.23 | 27-NOV-16:02 | 6.52 |
December | 0.693507E+09 | 1323.93 | 08-DEC-16:02 | 1.70 |
Annual Sum or Average | 0.208763E+10 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.693507E+09 | 1325.04 | 22.80 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.660466E+09 | 1615.77 | 17-JAN-09:02 | -2.5 |
February | 0.434545E+09 | 1594.73 | 16-FEB-16:02 | 1.70 |
March | 0.201978E+09 | 1485.82 | 23-MAR-08:62 | 7.07 |
April | 36941234.79 | 692.13 | 18-APR-08:03 | 8.48 |
May | 12479039.89 | 930.69 | 03-MAY-15:04 | 18.62 |
June | 1854041.98 | 612.60 | 20-JUN-08:04 | 21.05 |
July | 373384.95 | 384.85 | 17-JUL-08:05 | 20.87 |
August | 558882.29 | 385.01 | 23-AUG-08:05 | 19.13 |
September | 807672.40 | 516.07 | 08-SEP-08:04 | 15.10 |
October | 91267658.83 | 1581.70 | 25-OCT-08:62 | 0.22 |
November | 0.252738E+09 | 1517.76 | 27-NOV-09:02 | -1.2 |
December | 0.667565E+09 | 1613.97 | 21-DEC-16:02 | -1.1 |
Annual Sum or Average | 0.236157E+10 | |||
Minimum of Months | 373384.95 | 384.85 | -2.5 | |
Maximum of Months | 0.667565E+09 | 1615.77 | 21.05 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.105098E+10 | 1620.77 | 17-JAN-09:02 | -2.5 |
February | 0.687586E+09 | 1614.09 | 06-FEB-09:02 | -2.0 |
March | 0.286251E+09 | 1534.16 | 15-MAR-08:62 | 5.37 |
April | 42996830.68 | 859.45 | 07-APR-08:62 | 5.37 |
May | 11263866.24 | 933.04 | 24-MAY-15:04 | 16.52 |
June | 1269841.58 | 637.34 | 08-JUN-15:05 | 15.50 |
July | 40796.65 | 161.99 | 09-JUL-21:55 | 21.70 |
August | 67081.33 | 318.39 | 31-AUG-08:54 | 22.20 |
September | 632364.48 | 593.06 | 17-SEP-08:54 | 17.80 |
October | 0.137065E+09 | 1600.95 | 26-OCT-08:62 | 1.97 |
November | 0.485568E+09 | 1596.73 | 27-NOV-09:02 | -1.2 |
December | 0.114012E+10 | 1636.05 | 21-DEC-16:02 | -1.1 |
Annual Sum or Average | 0.384384E+10 | |||
Minimum of Months | 40796.65 | 161.99 | -2.5 | |
Maximum of Months | 0.114012E+10 | 1636.05 | 22.20 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.101672E+09 | 810.75 | 17-JAN-09:02 | -2.5 |
February | 63283016.56 | 801.05 | 16-FEB-16:02 | 1.70 |
March | 23909658.95 | 527.17 | 22-MAR-08:62 | 4.87 |
April | 4145414.34 | 328.07 | 04-APR-08:03 | 5.18 |
May | 1619757.11 | 421.38 | 03-MAY-15:04 | 18.62 |
June | 39956.32 | 332.24 | 04-JUN-18:05 | 15.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 99878.20 | 232.20 | 23-AUG-08:05 | 19.13 |
September | 13080.45 | 113.23 | 05-SEP-08:05 | 17.38 |
October | 14957995.74 | 794.36 | 25-OCT-08:62 | 0.22 |
November | 22049311.95 | 565.25 | 09-NOV-16:05 | 16.52 |
December | 96405829.13 | 805.04 | 08-DEC-09:02 | -0.5 |
Annual Sum or Average | 0.328195E+09 | |||
Minimum of Months | 0.00 | 0.00 | -2.5 | |
Maximum of Months | 0.101672E+09 | 810.75 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1577053.57 | 447.84 | 21-JAN-07:10 | -7.8 |
February | 214843.08 | 163.66 | 06-FEB-07:10 | -5.4 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 12.83 |
December | 2471081.22 | 342.93 | 15-DEC-07:10 | -8.1 |
Annual Sum or Average | 4262977.87 | |||
Minimum of Months | 0.00 | 0.00 | -8.1 | |
Maximum of Months | 2471081.22 | 447.84 | 21.95 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.136942E+11 | 13190.31 | 02-JAN-20:10 | 0.121516E+11 | 9632.53 | 02-JAN-20:10 |
February | 0.123646E+11 | 13190.31 | 01-FEB-20:10 | 0.109726E+11 | 9632.53 | 01-FEB-20:10 |
March | 0.137364E+11 | 13190.31 | 01-MAR-20:10 | 0.121771E+11 | 9632.53 | 01-MAR-20:10 |
April | 0.132299E+11 | 13190.31 | 03-APR-19:10 | 0.117446E+11 | 9632.53 | 03-APR-19:10 |
May | 0.137180E+11 | 13190.31 | 01-MAY-19:10 | 0.121662E+11 | 9632.53 | 01-MAY-19:10 |
June | 0.132906E+11 | 13190.31 | 01-JUN-19:10 | 0.117829E+11 | 9632.53 | 01-JUN-19:10 |
July | 0.136573E+11 | 13190.31 | 03-JUL-19:10 | 0.121279E+11 | 9632.53 | 03-JUL-19:10 |
August | 0.137417E+11 | 13190.31 | 01-AUG-19:10 | 0.121808E+11 | 9632.53 | 01-AUG-19:10 |
September | 0.132352E+11 | 13190.31 | 01-SEP-19:10 | 0.117482E+11 | 9632.53 | 01-SEP-19:10 |
October | 0.136889E+11 | 13190.31 | 02-OCT-19:10 | 0.121479E+11 | 9632.53 | 02-OCT-19:10 |
November | 0.132800E+11 | 13190.31 | 01-NOV-19:10 | 0.117774E+11 | 9632.53 | 01-NOV-19:10 |
December | 0.136573E+11 | 13190.31 | 01-DEC-20:10 | 0.121279E+11 | 9632.53 | 01-DEC-20:10 |
Annual Sum or Average | 0.161294E+12 | 0.143105E+12 | ||||
Minimum of Months | 0.123646E+11 | 13190.31 | 0.109726E+11 | 9632.53 | ||
Maximum of Months | 0.137417E+11 | 13190.31 | 0.121808E+11 | 9632.53 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.620421E+09 | 597.59 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.560184E+09 | 597.59 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.622334E+09 | 597.59 | 01-MAR-20:10 | 0.866718E+09 | 685.60 | 01-MAR-20:10 |
April | 0.599386E+09 | 597.59 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.621497E+09 | 597.59 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.602135E+09 | 597.59 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.618748E+09 | 597.59 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.622573E+09 | 597.59 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.599625E+09 | 597.59 | 01-SEP-19:10 | 0.836191E+09 | 685.60 | 01-SEP-19:10 |
October | 0.620182E+09 | 597.59 | 02-OCT-19:10 | 0.864640E+09 | 685.60 | 02-OCT-19:10 |
November | 0.601657E+09 | 597.59 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.618748E+09 | 597.59 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.730749E+10 | 0.101856E+11 | ||||
Minimum of Months | 0.560184E+09 | 597.59 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.622573E+09 | 597.59 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.718450E+09 | 692.02 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.648695E+09 | 692.02 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.720665E+09 | 692.02 | 01-MAR-20:10 | 0.100366E+10 | 793.93 | 01-MAR-20:10 |
April | 0.694091E+09 | 692.02 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.719696E+09 | 692.02 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.697275E+09 | 692.02 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.716513E+09 | 692.02 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.720942E+09 | 692.02 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.694368E+09 | 692.02 | 01-SEP-19:10 | 0.968312E+09 | 793.93 | 01-SEP-19:10 |
October | 0.718174E+09 | 692.02 | 02-OCT-19:10 | 0.100126E+10 | 793.93 | 02-OCT-19:10 |
November | 0.696721E+09 | 692.02 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.716513E+09 | 692.02 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.846210E+10 | 0.117950E+11 | ||||
Minimum of Months | 0.648695E+09 | 692.02 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.720942E+09 | 692.02 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.710312E+09 | 684.18 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.641347E+09 | 684.18 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.712502E+09 | 684.18 | 01-MAR-20:10 | 0.106120E+10 | 839.45 | 01-MAR-20:10 |
April | 0.686229E+09 | 684.18 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.711544E+09 | 684.18 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.689376E+09 | 684.18 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.708397E+09 | 684.18 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.712775E+09 | 684.18 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.686503E+09 | 684.18 | 01-SEP-19:10 | 0.102382E+10 | 839.45 | 01-SEP-19:10 |
October | 0.710039E+09 | 684.18 | 02-OCT-19:10 | 0.105866E+10 | 839.45 | 02-OCT-19:10 |
November | 0.688829E+09 | 684.18 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.708397E+09 | 684.18 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.836625E+10 | 0.124712E+11 | ||||
Minimum of Months | 0.641347E+09 | 684.18 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.712775E+09 | 684.18 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.261454E+09 | 251.84 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.236069E+09 | 251.84 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.262260E+09 | 251.84 | 01-MAR-20:10 | 0.306128E+09 | 242.16 | 01-MAR-20:10 |
April | 0.252589E+09 | 251.84 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.261907E+09 | 251.84 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.253748E+09 | 251.84 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.260749E+09 | 251.84 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.262360E+09 | 251.84 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.252690E+09 | 251.84 | 01-SEP-19:10 | 0.295345E+09 | 242.16 | 01-SEP-19:10 |
October | 0.261353E+09 | 251.84 | 02-OCT-19:10 | 0.305393E+09 | 242.16 | 02-OCT-19:10 |
November | 0.253546E+09 | 251.84 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.260749E+09 | 251.84 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.307947E+10 | 0.359760E+10 | ||||
Minimum of Months | 0.236069E+09 | 251.84 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.262360E+09 | 251.84 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.337502E+09 | 325.08 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.304733E+09 | 325.08 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.338542E+09 | 325.08 | 01-MAR-20:10 | 0.578079E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.326059E+09 | 325.08 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.338087E+09 | 325.08 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.327554E+09 | 325.08 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.336592E+09 | 325.08 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.338672E+09 | 325.08 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.326189E+09 | 325.08 | 01-SEP-19:10 | 0.557718E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.337372E+09 | 325.08 | 02-OCT-19:10 | 0.576693E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.327294E+09 | 325.08 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.336592E+09 | 325.08 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.397519E+10 | 0.679355E+11 | ||||
Minimum of Months | 0.304733E+09 | 325.08 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.338672E+09 | 325.08 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.130747E+10 | 1701.53 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.115394E+10 | 1701.53 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.122072E+10 | 1701.53 | 01-MAR-20:10 | 0.122027E+10 | 965.27 | 01-MAR-20:10 |
April | 0.108916E+10 | 1701.53 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.109154E+10 | 1701.53 | 01-MAY-19:10 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.997593E+09 | 1701.53 | 01-JUN-19:10 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.106586E+10 | 1701.53 | 03-JUL-19:19 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.109763E+10 | 1701.53 | 01-AUG-19:10 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.114669E+10 | 1701.53 | 01-SEP-19:10 | 0.117729E+10 | 965.27 | 01-SEP-19:10 |
October | 0.126365E+10 | 1701.53 | 02-OCT-19:10 | 0.121734E+10 | 965.27 | 02-OCT-19:10 |
November | 0.125135E+10 | 1701.53 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.133266E+10 | 1701.53 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.140183E+11 | 0.143405E+11 | ||||
Minimum of Months | 0.997593E+09 | 1701.53 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.133266E+10 | 1701.53 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.941834E+10 | 9504.80 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.848095E+10 | 9504.80 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.937874E+10 | 9504.80 | 01-MAR-20:10 | 0.126786E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.894821E+10 | 9504.80 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.925342E+10 | 9504.80 | 01-MAY-19:10 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.895318E+10 | 9504.80 | 01-JUN-19:10 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.920374E+10 | 9504.80 | 03-JUL-19:19 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.926815E+10 | 9504.80 | 01-AUG-19:10 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.901050E+10 | 9504.80 | 01-SEP-19:10 | 0.122320E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.937809E+10 | 9504.80 | 02-OCT-19:10 | 0.126482E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.911670E+10 | 9504.80 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.941941E+10 | 9504.80 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.109829E+12 | 0.148998E+12 | ||||
Minimum of Months | 0.848095E+10 | 9504.80 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.941941E+10 | 9504.80 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196602E+09 | 177.88 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.177551E+09 | 177.88 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.195039E+09 | 177.88 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.190486E+09 | 177.88 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.195821E+09 | 177.88 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.188975E+09 | 177.88 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.197358E+09 | 177.88 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.195039E+09 | 177.88 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.190538E+09 | 177.88 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.196576E+09 | 177.88 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.189731E+09 | 177.88 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.197383E+09 | 177.88 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.231110E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.177551E+09 | 177.88 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.197383E+09 | 177.88 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196579E+09 | 177.86 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.177530E+09 | 177.86 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.195017E+09 | 177.86 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.190464E+09 | 177.86 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.195798E+09 | 177.86 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.188953E+09 | 177.86 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.197334E+09 | 177.86 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.195017E+09 | 177.86 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.190515E+09 | 177.86 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.196553E+09 | 177.86 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.189708E+09 | 177.86 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.197360E+09 | 177.86 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.231083E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.177530E+09 | 177.86 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.197360E+09 | 177.86 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123557E+09 | 111.79 | 01-JAN-19:10 | 0.217935E+09 | 232.19 | 01-JAN-08:09 |
February | 0.111584E+09 | 111.79 | 01-FEB-20:10 | 0.196843E+09 | 232.19 | 01-FEB-07:10 |
March | 0.122575E+09 | 111.79 | 01-MAR-20:10 | 0.217824E+09 | 232.19 | 01-MAR-07:10 |
April | 0.119713E+09 | 111.79 | 01-APR-18:10 | 0.210923E+09 | 232.19 | 01-APR-07:10 |
May | 0.123066E+09 | 111.79 | 01-MAY-19:10 | 0.217879E+09 | 232.19 | 01-MAY-06:10 |
June | 0.118764E+09 | 111.79 | 01-JUN-19:10 | 0.210812E+09 | 232.19 | 01-JUN-06:10 |
July | 0.124032E+09 | 111.79 | 01-JUL-18:10 | 0.217991E+09 | 232.19 | 01-JUL-07:10 |
August | 0.122575E+09 | 111.79 | 01-AUG-19:10 | 0.217824E+09 | 232.19 | 01-AUG-06:10 |
September | 0.119746E+09 | 111.79 | 01-SEP-19:10 | 0.210923E+09 | 232.19 | 01-SEP-06:10 |
October | 0.123541E+09 | 111.79 | 01-OCT-18:10 | 0.217935E+09 | 232.19 | 01-OCT-07:10 |
November | 0.119238E+09 | 111.79 | 01-NOV-19:10 | 0.210867E+09 | 232.19 | 01-NOV-06:10 |
December | 0.124048E+09 | 111.79 | 01-DEC-20:10 | 0.217991E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.145244E+10 | 0.256575E+10 | ||||
Minimum of Months | 0.111584E+09 | 111.79 | 0.196843E+09 | 232.19 | ||
Maximum of Months | 0.124048E+09 | 111.79 | 0.217991E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123591E+09 | 111.82 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 0.111614E+09 | 111.82 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 0.122608E+09 | 111.82 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 0.119746E+09 | 111.82 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 0.123099E+09 | 111.82 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 0.118796E+09 | 111.82 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 0.124066E+09 | 111.82 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 0.122608E+09 | 111.82 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 0.119778E+09 | 111.82 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 0.123574E+09 | 111.82 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 0.119271E+09 | 111.82 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 0.124082E+09 | 111.82 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.145283E+10 | 0.256645E+10 | ||||
Minimum of Months | 0.111614E+09 | 111.82 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 0.124082E+09 | 111.82 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196602E+09 | 177.88 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.177551E+09 | 177.88 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.195039E+09 | 177.88 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.190486E+09 | 177.88 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.195821E+09 | 177.88 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.188975E+09 | 177.88 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.197358E+09 | 177.88 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.195039E+09 | 177.88 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.190538E+09 | 177.88 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.196576E+09 | 177.88 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.189731E+09 | 177.88 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.197383E+09 | 177.88 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.231110E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.177551E+09 | 177.88 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.197383E+09 | 177.88 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196579E+09 | 177.86 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.177530E+09 | 177.86 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.195017E+09 | 177.86 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.190464E+09 | 177.86 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.195798E+09 | 177.86 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.188953E+09 | 177.86 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.197334E+09 | 177.86 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.195017E+09 | 177.86 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.190515E+09 | 177.86 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.196553E+09 | 177.86 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.189708E+09 | 177.86 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.197360E+09 | 177.86 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.231083E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.177530E+09 | 177.86 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.197360E+09 | 177.86 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.193865E+10 | 1867.32 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.175042E+10 | 1867.32 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.194462E+10 | 1867.32 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.187292E+10 | 1867.32 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.194201E+10 | 1867.32 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.188151E+10 | 1867.32 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.193342E+10 | 1867.32 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.194537E+10 | 1867.32 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.187367E+10 | 1867.32 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.193790E+10 | 1867.32 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.188002E+10 | 1867.32 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.193342E+10 | 1867.32 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.228339E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.175042E+10 | 1867.32 | 0.00 | 0.00 | |
Maximum of Months | 0.194537E+10 | 1867.32 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196602E+09 | 177.88 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.177551E+09 | 177.88 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.195039E+09 | 177.88 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.190486E+09 | 177.88 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.195821E+09 | 177.88 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.188975E+09 | 177.88 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.197358E+09 | 177.88 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.195039E+09 | 177.88 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.190538E+09 | 177.88 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.196576E+09 | 177.88 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.189731E+09 | 177.88 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.197383E+09 | 177.88 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.231110E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.177551E+09 | 177.88 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.197383E+09 | 177.88 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196579E+09 | 177.86 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.177530E+09 | 177.86 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.195017E+09 | 177.86 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.190464E+09 | 177.86 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.195798E+09 | 177.86 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.188953E+09 | 177.86 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.197334E+09 | 177.86 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.195017E+09 | 177.86 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.190515E+09 | 177.86 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.196553E+09 | 177.86 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.189708E+09 | 177.86 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.197360E+09 | 177.86 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.231083E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.177530E+09 | 177.86 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.197360E+09 | 177.86 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123591E+09 | 111.82 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 0.111614E+09 | 111.82 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 0.122608E+09 | 111.82 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 0.119746E+09 | 111.82 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 0.123099E+09 | 111.82 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 0.118796E+09 | 111.82 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 0.124066E+09 | 111.82 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 0.122608E+09 | 111.82 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 0.119778E+09 | 111.82 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 0.123574E+09 | 111.82 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 0.119271E+09 | 111.82 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 0.124082E+09 | 111.82 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.145283E+10 | 0.256645E+10 | ||||
Minimum of Months | 0.111614E+09 | 111.82 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 0.124082E+09 | 111.82 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.277321E+10 | 2988.03 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.246018E+10 | 2988.03 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.266532E+10 | 2988.03 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.244263E+10 | 2988.03 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.248125E+10 | 2988.03 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.234287E+10 | 2988.03 | 01-JUN-19:10 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.244825E+10 | 2988.03 | 03-JUL-19:19 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.250065E+10 | 2988.03 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.252218E+10 | 2988.03 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.272878E+10 | 2988.03 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.264983E+10 | 2988.03 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.279276E+10 | 2988.03 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.308079E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.234287E+10 | 2988.03 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.279276E+10 | 2988.03 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.277321E+10 | 2988.03 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.246018E+10 | 2988.03 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.266532E+10 | 2988.03 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.244263E+10 | 2988.03 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.248125E+10 | 2988.03 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.234287E+10 | 2988.03 | 01-JUN-19:10 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.244825E+10 | 2988.03 | 03-JUL-19:19 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.250065E+10 | 2988.03 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.252218E+10 | 2988.03 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.272878E+10 | 2988.03 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.264983E+10 | 2988.03 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.279276E+10 | 2988.03 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.308079E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.234287E+10 | 2988.03 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.279276E+10 | 2988.03 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.110133E+10 | 1060.81 | 02-JAN-20:10 | 0.368383E+11 | 16487.34 | 01-JAN-07:10 |
February | 0.994402E+09 | 1060.81 | 01-FEB-20:10 | 0.332733E+11 | 16487.34 | 01-FEB-07:10 |
March | 0.110473E+10 | 1060.81 | 01-MAR-20:10 | 0.368383E+11 | 16487.34 | 01-MAR-07:10 |
April | 0.106399E+10 | 1060.81 | 03-APR-19:10 | 0.356500E+11 | 16487.34 | 01-APR-06:10 |
May | 0.110324E+10 | 1060.81 | 01-MAY-19:10 | 0.368383E+11 | 16487.34 | 01-MAY-06:10 |
June | 0.106887E+10 | 1060.81 | 01-JUN-19:10 | 0.356500E+11 | 16487.34 | 01-JUN-06:10 |
July | 0.109836E+10 | 1060.81 | 03-JUL-19:10 | 0.368383E+11 | 16487.34 | 01-JUL-06:10 |
August | 0.110515E+10 | 1060.81 | 01-AUG-19:10 | 0.368383E+11 | 16487.34 | 01-AUG-06:10 |
September | 0.106442E+10 | 1060.81 | 01-SEP-19:10 | 0.356500E+11 | 16487.34 | 01-SEP-06:10 |
October | 0.110091E+10 | 1060.81 | 02-OCT-19:10 | 0.368383E+11 | 16487.34 | 01-OCT-06:10 |
November | 0.106802E+10 | 1060.81 | 01-NOV-19:10 | 0.356500E+11 | 16487.34 | 01-NOV-06:10 |
December | 0.109836E+10 | 1060.81 | 01-DEC-20:10 | 0.368383E+11 | 16487.34 | 01-DEC-07:10 |
Annual Sum or Average | 0.129718E+11 | 0.433742E+12 | ||||
Minimum of Months | 0.994402E+09 | 1060.81 | 0.332733E+11 | 16487.34 | ||
Maximum of Months | 0.110515E+10 | 1060.81 | 0.368383E+11 | 16487.34 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.205176E+10 | 1976.27 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.185255E+10 | 1976.27 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.205809E+10 | 1976.27 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.198220E+10 | 1976.27 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.205532E+10 | 1976.27 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.199129E+10 | 1976.27 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.204623E+10 | 1976.27 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.205888E+10 | 1976.27 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.198299E+10 | 1976.27 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.205097E+10 | 1976.27 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.198971E+10 | 1976.27 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.204623E+10 | 1976.27 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.241662E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.185255E+10 | 1976.27 | 0.00 | 0.00 | |
Maximum of Months | 0.205888E+10 | 1976.27 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.136942E+11 | 0.121516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.123646E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196682E+11 | 0.137364E+11 | 0.121771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.132299E+11 | 0.117446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.137180E+11 | 0.121662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.132906E+11 | 0.117829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.136573E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.137417E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189689E+11 | 0.132352E+11 | 0.117482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195854E+11 | 0.136889E+11 | 0.121479E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.132800E+11 | 0.117774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.136573E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230861E+12 | 0.161294E+12 | 0.143105E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.176991E+11 | 0.123646E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196682E+11 | 0.137417E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.620421E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246959E+09 |
February | 0.179968E+10 | 0.560184E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204316E+09 |
March | 0.199990E+10 | 0.622334E+09 | 0.866718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167515E+09 |
April | 0.192973E+10 | 0.599386E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 512960.59 | 0.105213E+09 |
May | 0.199475E+10 | 0.621497E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5182140.50 | 66386868.31 |
June | 0.193394E+10 | 0.602135E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 27370405.98 | 30747347.09 |
July | 0.199054E+10 | 0.618748E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 34950022.74 | 13770509.07 |
August | 0.199896E+10 | 0.622573E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 24150222.32 | 21060990.44 |
September | 0.192879E+10 | 0.599625E+09 | 0.836191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8666663.21 | 44989628.91 |
October | 0.199148E+10 | 0.620182E+09 | 0.864640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1460266.74 | 0.117241E+09 |
November | 0.192552E+10 | 0.601657E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188210E+09 |
December | 0.199054E+10 | 0.618748E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254259E+09 |
Annual Sum or Average | 0.234744E+11 | 0.730749E+10 | 0.101856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102293E+09 | 0.146067E+10 |
Minimum of Months | 0.179968E+10 | 0.560184E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13770509.07 |
Maximum of Months | 0.199990E+10 | 0.622573E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 34950022.74 | 0.254259E+09 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.718450E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100001E+09 |
February | 0.208403E+10 | 0.648695E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82920519.11 |
March | 0.231589E+10 | 0.720665E+09 | 0.100366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69720604.47 |
April | 0.223463E+10 | 0.694091E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 247592.61 | 44467786.11 |
May | 0.230993E+10 | 0.719696E+09 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2097302.84 | 29519600.12 |
June | 0.223950E+10 | 0.697275E+09 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10612346.71 | 14093577.63 |
July | 0.230505E+10 | 0.716513E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13585523.42 | 6416310.53 |
August | 0.231480E+10 | 0.720942E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9468666.08 | 9255268.26 |
September | 0.223354E+10 | 0.694368E+09 | 0.968312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3483252.73 | 19063018.35 |
October | 0.230614E+10 | 0.718174E+09 | 0.100126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 603113.58 | 48051310.96 |
November | 0.222975E+10 | 0.696721E+09 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76820006.11 |
December | 0.230505E+10 | 0.716513E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102560E+09 |
Annual Sum or Average | 0.271834E+11 | 0.846210E+10 | 0.117950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 40097797.97 | 0.602889E+09 |
Minimum of Months | 0.208403E+10 | 0.648695E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6416310.53 |
Maximum of Months | 0.231589E+10 | 0.720942E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13585523.42 | 0.102560E+09 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.487480E+09 | 0.710312E+09 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219776E+09 |
February | 0.440737E+09 | 0.641347E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21.54 | 0.181362E+09 |
March | 0.489771E+09 | 0.712502E+09 | 0.106120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9547.75 | 0.152777E+09 |
April | 0.472586E+09 | 0.686229E+09 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1114258.14 | 97916958.00 |
May | 0.488511E+09 | 0.711544E+09 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5507295.11 | 66820010.03 |
June | 0.473617E+09 | 0.689376E+09 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24907614.30 | 32853951.50 |
July | 0.487480E+09 | 0.708397E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31706424.51 | 15179326.57 |
August | 0.489542E+09 | 0.712775E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22304500.12 | 21764526.02 |
September | 0.472357E+09 | 0.686503E+09 | 0.102382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8915824.20 | 43926740.59 |
October | 0.487709E+09 | 0.710039E+09 | 0.105866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1758693.57 | 0.106332E+09 |
November | 0.471555E+09 | 0.688829E+09 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168265E+09 |
December | 0.487480E+09 | 0.708397E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224683E+09 |
Annual Sum or Average | 0.574883E+10 | 0.836625E+10 | 0.124712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 96224179.23 | 0.133166E+10 |
Minimum of Months | 0.440737E+09 | 0.641347E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15179326.57 |
Maximum of Months | 0.489771E+09 | 0.712775E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31706424.51 | 0.224683E+09 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.374985E+09 | 0.261454E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124701E+09 |
February | 0.339028E+09 | 0.236069E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 200.80 | 0.102698E+09 |
March | 0.376747E+09 | 0.262260E+09 | 0.306128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7580.27 | 85844687.44 |
April | 0.363528E+09 | 0.252589E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 714240.65 | 54564007.04 |
May | 0.375778E+09 | 0.261907E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3405067.04 | 36918691.49 |
June | 0.364321E+09 | 0.253748E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14528162.06 | 18250608.23 |
July | 0.374985E+09 | 0.260749E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18390071.17 | 8573971.36 |
August | 0.376571E+09 | 0.262360E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13001991.00 | 12162404.94 |
September | 0.363352E+09 | 0.252690E+09 | 0.295345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5374559.29 | 24212210.37 |
October | 0.375161E+09 | 0.261353E+09 | 0.305393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1091656.12 | 59347846.15 |
November | 0.362735E+09 | 0.253546E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94783427.91 |
December | 0.374985E+09 | 0.260749E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127566E+09 |
Annual Sum or Average | 0.442217E+10 | 0.307947E+10 | 0.359760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56513528.42 | 0.749623E+09 |
Minimum of Months | 0.339028E+09 | 0.236069E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8573971.36 |
Maximum of Months | 0.376747E+09 | 0.262360E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18390071.17 | 0.127566E+09 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.337502E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.330277E+09 |
February | 0.139600E+10 | 0.304733E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272454E+09 |
March | 0.155131E+10 | 0.338542E+09 | 0.578079E+10 | 0.502211E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228485E+09 |
April | 0.149688E+10 | 0.326059E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 797782.95 | 0.143623E+09 |
May | 0.154732E+10 | 0.338087E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 6693670.02 | 94411475.30 |
June | 0.150015E+10 | 0.327554E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 34750097.19 | 43064858.71 |
July | 0.154405E+10 | 0.336592E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 45020156.71 | 17658311.97 |
August | 0.155059E+10 | 0.338672E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 31859721.57 | 26628052.09 |
September | 0.149615E+10 | 0.326189E+09 | 0.557718E+10 | 0.484522E+11 | 0.00 | 0.00 | 0.00 | 12582485.98 | 58313132.08 |
October | 0.154478E+10 | 0.337372E+09 | 0.576693E+10 | 0.501006E+11 | 0.00 | 0.00 | 0.00 | 2441559.67 | 0.153236E+09 |
November | 0.149361E+10 | 0.327294E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249960E+09 |
December | 0.154405E+10 | 0.336592E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.338350E+09 |
Annual Sum or Average | 0.182090E+11 | 0.397519E+10 | 0.679355E+11 | 0.590196E+12 | 0.00 | 0.00 | 0.00 | 0.134145E+09 | 0.195646E+10 |
Minimum of Months | 0.139600E+10 | 0.304733E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 17658311.97 |
Maximum of Months | 0.155131E+10 | 0.338672E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 45020156.71 | 0.338350E+09 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.130747E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.582622E+09 |
February | 0.236489E+11 | 0.115394E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.483827E+09 |
March | 0.262800E+11 | 0.122072E+10 | 0.122027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.405294E+09 |
April | 0.253579E+11 | 0.108916E+10 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1014093.02 | 0.257575E+09 |
May | 0.262123E+11 | 0.109154E+10 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10971293.98 | 0.168397E+09 |
June | 0.254132E+11 | 0.997593E+09 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60456921.57 | 79338260.85 |
July | 0.261570E+11 | 0.106586E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77567052.48 | 36156069.59 |
August | 0.262677E+11 | 0.109763E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53600020.78 | 52087103.42 |
September | 0.253456E+11 | 0.114669E+10 | 0.117729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19168204.22 | 0.108763E+09 |
October | 0.261693E+11 | 0.126365E+10 | 0.121734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3230736.58 | 0.277785E+09 |
November | 0.253025E+11 | 0.125135E+10 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.446926E+09 |
December | 0.261570E+11 | 0.133266E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.598624E+09 |
Annual Sum or Average | 0.308468E+12 | 0.140183E+11 | 0.143405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226008E+09 | 0.349739E+10 |
Minimum of Months | 0.236489E+11 | 0.997593E+09 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36156069.59 |
Maximum of Months | 0.262800E+11 | 0.133266E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77567052.48 | 0.598624E+09 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.941834E+10 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168271E+10 |
February | 0.702046E+11 | 0.848095E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139365E+10 |
March | 0.780153E+11 | 0.937874E+10 | 0.126786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116985E+10 |
April | 0.752779E+11 | 0.894821E+10 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3369521.44 | 0.739772E+09 |
May | 0.778146E+11 | 0.925342E+10 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 33431045.72 | 0.488801E+09 |
June | 0.754422E+11 | 0.895318E+10 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174192E+09 | 0.231666E+09 |
July | 0.776503E+11 | 0.920374E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222759E+09 | 0.104936E+09 |
August | 0.779788E+11 | 0.926815E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154294E+09 | 0.151297E+09 |
September | 0.752414E+11 | 0.901050E+10 | 0.122320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 55250063.03 | 0.313483E+09 |
October | 0.776868E+11 | 0.937809E+10 | 0.126482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 9273000.96 | 0.800509E+09 |
November | 0.751137E+11 | 0.911670E+10 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128769E+10 |
December | 0.776503E+11 | 0.941941E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172681E+10 |
Annual Sum or Average | 0.915726E+12 | 0.109829E+12 | 0.148998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.652569E+09 | 0.100912E+11 |
Minimum of Months | 0.702046E+11 | 0.848095E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104936E+09 |
Maximum of Months | 0.780153E+11 | 0.941941E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222759E+09 | 0.172681E+10 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196602E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138712E+09 |
February | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1955.83 | 0.113898E+09 |
March | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12031.62 | 92441160.35 |
April | 0.293479E+09 | 0.190486E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1133783.85 | 54880042.58 |
May | 0.303504E+09 | 0.195821E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5190967.10 | 33044296.34 |
June | 0.293842E+09 | 0.188975E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21113965.78 | 13165518.72 |
July | 0.303141E+09 | 0.197358E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 27984735.88 | 3024292.79 |
August | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20550871.07 | 5850136.99 |
September | 0.293479E+09 | 0.190538E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7917092.96 | 17339922.76 |
October | 0.303322E+09 | 0.196576E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1534113.77 | 58966837.15 |
November | 0.293661E+09 | 0.189731E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102868E+09 |
December | 0.303141E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142427E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231110E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85439517.86 | 0.776618E+09 |
Minimum of Months | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3024292.79 |
Maximum of Months | 0.303685E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 27984735.88 | 0.142427E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196579E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135962E+09 |
February | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1253.41 | 0.111965E+09 |
March | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2300.07 | 92532445.22 |
April | 0.293479E+09 | 0.190464E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 914553.97 | 57586862.51 |
May | 0.303504E+09 | 0.195798E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4801855.68 | 35848783.96 |
June | 0.293842E+09 | 0.188953E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20330011.86 | 15393906.88 |
July | 0.303141E+09 | 0.197334E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26915748.41 | 5135810.85 |
August | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19780625.28 | 8576422.43 |
September | 0.293479E+09 | 0.190515E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7645517.45 | 20638253.14 |
October | 0.303322E+09 | 0.196553E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1426540.96 | 61035958.82 |
November | 0.293661E+09 | 0.189708E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100933E+09 |
December | 0.303141E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139162E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231083E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81818407.08 | 0.784771E+09 |
Minimum of Months | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5135810.85 |
Maximum of Months | 0.303685E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26915748.41 | 0.139162E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.123557E+09 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48409789.51 |
February | 0.00 | 0.111584E+09 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40732104.60 |
March | 0.00 | 0.122575E+09 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35603085.18 |
April | 0.00 | 0.119713E+09 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24313950.27 |
May | 0.00 | 0.123066E+09 | 0.217879E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 147038.01 | 17434784.46 |
June | 0.00 | 0.118764E+09 | 0.210812E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2487790.10 | 9207891.12 |
July | 0.00 | 0.124032E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3196278.48 | 5426199.47 |
August | 0.00 | 0.122575E+09 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1963783.26 | 7134625.06 |
September | 0.00 | 0.119746E+09 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 429156.08 | 12167150.72 |
October | 0.00 | 0.123541E+09 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21885.35 | 25675647.16 |
November | 0.00 | 0.119238E+09 | 0.210867E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38341660.39 |
December | 0.00 | 0.124048E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49746585.38 |
Annual Sum or Average | 0.00 | 0.145244E+10 | 0.256575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8245931.29 | 0.314193E+09 |
Minimum of Months | 0.00 | 0.111584E+09 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5426199.47 |
Maximum of Months | 0.00 | 0.124048E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3196278.48 | 49746585.38 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.123591E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38051033.27 |
February | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 938.67 | 31170125.23 |
March | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4357.58 | 25405623.54 |
April | 0.293479E+09 | 0.119746E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 288434.45 | 15417410.62 |
May | 0.303504E+09 | 0.123099E+09 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1399439.18 | 9591836.46 |
June | 0.293842E+09 | 0.118796E+09 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5821941.49 | 4054699.06 |
July | 0.303141E+09 | 0.124066E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7649746.93 | 1265991.47 |
August | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5651868.91 | 2131601.29 |
September | 0.293479E+09 | 0.119778E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2264444.56 | 5437561.69 |
October | 0.303322E+09 | 0.123574E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 462654.53 | 16385114.57 |
November | 0.293661E+09 | 0.119271E+09 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27999168.35 |
December | 0.303141E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38955145.97 |
Annual Sum or Average | 0.357224E+10 | 0.145283E+10 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23543826.29 | 0.215865E+09 |
Minimum of Months | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1265991.47 |
Maximum of Months | 0.303685E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7649746.93 | 38955145.97 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196602E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139032E+09 |
February | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3815.15 | 0.114262E+09 |
March | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12812.77 | 93025922.22 |
April | 0.293479E+09 | 0.190486E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1164552.71 | 55385331.87 |
May | 0.303504E+09 | 0.195821E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5253164.64 | 33484670.45 |
June | 0.293842E+09 | 0.188975E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21222561.42 | 13335612.80 |
July | 0.303141E+09 | 0.197358E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 28009732.18 | 3067682.01 |
August | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20593133.69 | 5958385.85 |
September | 0.293479E+09 | 0.190538E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8055252.60 | 17627387.02 |
October | 0.303322E+09 | 0.196576E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1681007.02 | 59371416.82 |
November | 0.293661E+09 | 0.189731E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103191E+09 |
December | 0.303141E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142885E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231110E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85996032.18 | 0.780627E+09 |
Minimum of Months | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3067682.01 |
Maximum of Months | 0.303685E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 28009732.18 | 0.142885E+09 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196579E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135938E+09 |
February | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1503.26 | 0.111947E+09 |
March | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2614.38 | 92924328.76 |
April | 0.293479E+09 | 0.190464E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 943031.76 | 57369642.61 |
May | 0.303504E+09 | 0.195798E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4837964.69 | 36348387.60 |
June | 0.293842E+09 | 0.188953E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20321544.28 | 16780334.29 |
July | 0.303141E+09 | 0.197334E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26671971.49 | 6710513.32 |
August | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19612789.83 | 10184246.41 |
September | 0.293479E+09 | 0.190515E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7681527.64 | 21563220.41 |
October | 0.303322E+09 | 0.196553E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1492985.01 | 60773216.42 |
November | 0.293661E+09 | 0.189708E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100957E+09 |
December | 0.303141E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138927E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231083E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81565932.32 | 0.790422E+09 |
Minimum of Months | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6710513.32 |
Maximum of Months | 0.303685E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26671971.49 | 0.138927E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.385223E+10 | 0.193865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169563E+09 |
February | 0.348285E+10 | 0.175042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139658E+09 |
March | 0.387034E+10 | 0.194462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 608.61 | 0.117362E+09 |
April | 0.373454E+10 | 0.187292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 728557.53 | 75427533.28 |
May | 0.386038E+10 | 0.194201E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4257180.91 | 50534132.05 |
June | 0.374269E+10 | 0.188151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19212717.33 | 24557042.97 |
July | 0.385223E+10 | 0.193342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24335570.49 | 11553000.95 |
August | 0.386853E+10 | 0.194537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16901039.99 | 16687723.73 |
September | 0.373273E+10 | 0.187367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6228515.95 | 33922918.53 |
October | 0.385404E+10 | 0.193790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1071815.21 | 83405211.04 |
November | 0.372639E+10 | 0.188002E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130090E+09 |
December | 0.385223E+10 | 0.193342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172905E+09 |
Annual Sum or Average | 0.454292E+11 | 0.228339E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72736006.02 | 0.102566E+10 |
Minimum of Months | 0.348285E+10 | 0.175042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11553000.95 |
Maximum of Months | 0.387034E+10 | 0.194537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24335570.49 | 0.172905E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196602E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138559E+09 |
February | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 756.61 | 0.113897E+09 |
March | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10570.06 | 92514966.84 |
April | 0.293479E+09 | 0.190486E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1080413.96 | 55091379.44 |
May | 0.303504E+09 | 0.195821E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5036006.24 | 33225290.83 |
June | 0.293842E+09 | 0.188975E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20735711.80 | 13304285.52 |
July | 0.303141E+09 | 0.197358E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 27579874.86 | 3118939.26 |
August | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20206577.44 | 5964530.85 |
September | 0.293479E+09 | 0.190538E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7726190.68 | 17503852.68 |
October | 0.303322E+09 | 0.196576E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1470940.32 | 59076028.98 |
November | 0.293661E+09 | 0.189731E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102873E+09 |
December | 0.303141E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142263E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231110E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83847041.95 | 0.777391E+09 |
Minimum of Months | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3118939.26 |
Maximum of Months | 0.303685E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 27579874.86 | 0.142263E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196579E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135534E+09 |
February | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1133.74 | 0.111800E+09 |
March | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2070.19 | 92684998.92 |
April | 0.293479E+09 | 0.190464E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 879587.13 | 58198645.54 |
May | 0.303504E+09 | 0.195798E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4657825.50 | 36178205.50 |
June | 0.293842E+09 | 0.188953E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19950590.58 | 15516294.03 |
July | 0.303141E+09 | 0.197334E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26520363.50 | 5029662.75 |
August | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19460169.63 | 8503258.93 |
September | 0.293479E+09 | 0.190515E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7487434.99 | 20611897.39 |
October | 0.303322E+09 | 0.196553E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1389357.07 | 61201944.96 |
November | 0.293661E+09 | 0.189708E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100609E+09 |
December | 0.303141E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138697E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231083E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80348532.33 | 0.784565E+09 |
Minimum of Months | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5029662.75 |
Maximum of Months | 0.303685E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26520363.50 | 0.138697E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.123591E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72106843.18 |
February | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59099851.51 |
March | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2901.67 | 47810708.94 |
April | 0.293479E+09 | 0.119746E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 564977.96 | 28305013.54 |
May | 0.303504E+09 | 0.123099E+09 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2643377.85 | 17024694.76 |
June | 0.293842E+09 | 0.118796E+09 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10936953.30 | 6800380.44 |
July | 0.303141E+09 | 0.124066E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14330267.88 | 1596695.68 |
August | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10480241.68 | 3051366.49 |
September | 0.293479E+09 | 0.119778E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3952536.19 | 8994802.74 |
October | 0.303322E+09 | 0.123574E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 702208.57 | 30611670.07 |
November | 0.293661E+09 | 0.119271E+09 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53413193.67 |
December | 0.303141E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73962174.41 |
Annual Sum or Average | 0.357224E+10 | 0.145283E+10 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43613465.10 | 0.402777E+09 |
Minimum of Months | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1596695.68 |
Maximum of Months | 0.303685E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14330267.88 | 73962174.41 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.277321E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382763E+09 |
February | 0.415303E+11 | 0.246018E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.316927E+09 |
March | 0.461508E+11 | 0.266532E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268000E+09 |
April | 0.445315E+11 | 0.244263E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 560860.32 | 0.170898E+09 |
May | 0.460320E+11 | 0.248125E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 6309003.91 | 0.113990E+09 |
June | 0.446286E+11 | 0.234287E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 37116727.36 | 53944425.18 |
July | 0.459349E+11 | 0.244825E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 48045676.59 | 24395412.67 |
August | 0.461292E+11 | 0.250065E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 33353978.94 | 35190825.47 |
September | 0.445099E+11 | 0.252218E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 11876513.48 | 72051010.41 |
October | 0.459565E+11 | 0.272878E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1975747.74 | 0.182146E+09 |
November | 0.444343E+11 | 0.264983E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291586E+09 |
December | 0.459349E+11 | 0.279276E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.391242E+09 |
Annual Sum or Average | 0.541708E+12 | 0.308079E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139239E+09 | 0.230313E+10 |
Minimum of Months | 0.415303E+11 | 0.234287E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24395412.67 |
Maximum of Months | 0.461508E+11 | 0.279276E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 48045676.59 | 0.391242E+09 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.277321E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.384913E+09 |
February | 0.415303E+11 | 0.246018E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318417E+09 |
March | 0.461508E+11 | 0.266532E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268925E+09 |
April | 0.445315E+11 | 0.244263E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 560826.52 | 0.171170E+09 |
May | 0.460320E+11 | 0.248125E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 6305621.84 | 0.114095E+09 |
June | 0.446286E+11 | 0.234287E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 37114712.02 | 53955334.87 |
July | 0.459349E+11 | 0.244825E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 48044231.66 | 24396294.14 |
August | 0.461292E+11 | 0.250065E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 33350307.99 | 35196588.42 |
September | 0.445099E+11 | 0.252218E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 11865438.49 | 72064807.05 |
October | 0.459565E+11 | 0.272878E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1964714.22 | 0.182704E+09 |
November | 0.444343E+11 | 0.264983E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292917E+09 |
December | 0.459349E+11 | 0.279276E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.393527E+09 |
Annual Sum or Average | 0.541708E+12 | 0.308079E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139206E+09 | 0.231228E+10 |
Minimum of Months | 0.415303E+11 | 0.234287E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24396294.14 |
Maximum of Months | 0.461508E+11 | 0.279276E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 48044231.66 | 0.393527E+09 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.110133E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344548E+09 |
February | 0.369574E+10 | 0.994402E+09 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284768E+09 |
March | 0.410691E+10 | 0.110473E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240344E+09 |
April | 0.396281E+10 | 0.106399E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 509339.48 | 0.153028E+09 |
May | 0.409635E+10 | 0.110324E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 5671172.62 | 0.102055E+09 |
June | 0.397146E+10 | 0.106887E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 33264551.48 | 48276035.82 |
July | 0.408770E+10 | 0.109836E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 43049102.80 | 21834627.36 |
August | 0.410499E+10 | 0.110515E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 29887238.33 | 31496665.47 |
September | 0.396089E+10 | 0.106442E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 10654196.10 | 64498149.48 |
October | 0.408962E+10 | 0.110091E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 1766640.48 | 0.163558E+09 |
November | 0.395417E+10 | 0.106802E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262085E+09 |
December | 0.408770E+10 | 0.109836E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.352498E+09 |
Annual Sum or Average | 0.482060E+11 | 0.129718E+11 | 0.392709E+12 | 0.359593E+12 | 0.00 | 0.00 | 0.00 | 0.124802E+09 | 0.206899E+10 |
Minimum of Months | 0.369574E+10 | 0.994402E+09 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 21834627.36 |
Maximum of Months | 0.410691E+10 | 0.110515E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 43049102.80 | 0.352498E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.407704E+10 | 0.205176E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.297914E+09 |
February | 0.368610E+10 | 0.185255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246190E+09 |
March | 0.409620E+10 | 0.205809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205732E+09 |
April | 0.395248E+10 | 0.198220E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 694410.44 | 0.132672E+09 |
May | 0.408566E+10 | 0.205532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5892599.96 | 88997590.23 |
June | 0.396110E+10 | 0.199129E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32666543.51 | 43258844.85 |
July | 0.407704E+10 | 0.204623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42140338.42 | 20153612.29 |
August | 0.409429E+10 | 0.205888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29243819.19 | 29036517.70 |
September | 0.395056E+10 | 0.198299E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10416203.92 | 58593846.56 |
October | 0.407896E+10 | 0.205097E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1757823.26 | 0.144353E+09 |
November | 0.394385E+10 | 0.198971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226115E+09 |
December | 0.407704E+10 | 0.204623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.305023E+09 |
Annual Sum or Average | 0.480803E+11 | 0.241662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122812E+09 | 0.179804E+10 |
Minimum of Months | 0.368610E+10 | 0.185255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20153612.29 |
Maximum of Months | 0.409620E+10 | 0.205888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42140338.42 | 0.305023E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 13190.31 | 02-JAN-20:10 | 9632.53 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 13190.31 | 01-FEB-20:10 | 9632.53 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 13190.31 | 01-MAR-20:10 | 9632.53 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 13190.31 | 03-APR-19:10 | 9632.53 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 13190.31 | 01-MAY-19:10 | 9632.53 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 13190.31 | 01-JUN-19:10 | 9632.53 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 13190.31 | 03-JUL-19:10 | 9632.53 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 13190.31 | 01-AUG-19:10 | 9632.53 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 13190.31 | 01-SEP-19:10 | 9632.53 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 01-OCT-23:10 | 13190.31 | 02-OCT-19:10 | 9632.53 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 13190.31 | 01-NOV-19:10 | 9632.53 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 13190.31 | 01-DEC-20:10 | 9632.53 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 11501.89 | 13190.31 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 13190.31 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 597.59 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 144.30 | 21-JAN-07:00 |
February | 1169.53 | 01-FEB-00:10 | 597.59 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 134.80 | 04-FEB-06:50 |
March | 1169.53 | 01-MAR-00:10 | 597.59 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 120.77 | 05-MAR-07:00 |
April | 1169.53 | 01-APR-00:10 | 597.59 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.04 | 13-APR-17:00 | 91.73 | 08-APR-06:00 |
May | 1169.53 | 01-MAY-00:10 | 597.59 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.97 | 22-MAY-13:00 | 77.47 | 07-MAY-05:00 |
June | 1169.53 | 01-JUN-00:10 | 597.59 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.96 | 28-JUN-16:00 | 62.04 | 09-JUN-04:10 |
July | 1169.53 | 01-JUL-00:10 | 597.59 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.42 | 22-JUL-15:00 | 30.02 | 08-JUL-03:00 |
August | 1169.53 | 01-AUG-00:10 | 597.59 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.42 | 20-AUG-15:00 | 45.18 | 31-AUG-06:00 |
September | 1169.53 | 01-SEP-00:10 | 597.59 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.21 | 03-SEP-14:00 | 55.16 | 20-SEP-06:00 |
October | 1169.53 | 01-OCT-23:10 | 597.59 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.06 | 01-OCT-16:00 | 114.58 | 26-OCT-07:00 |
November | 1169.53 | 01-NOV-00:10 | 597.59 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 122.84 | 27-NOV-06:20 |
December | 1169.53 | 01-DEC-00:10 | 597.59 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 150.63 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1169.53 | 597.59 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.02 | |||||
Maximum of Months | 1169.53 | 597.59 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 61.96 | 150.63 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 692.02 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 58.24 | 21-JAN-07:00 |
February | 1354.32 | 01-FEB-00:10 | 692.02 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 55.36 | 05-FEB-08:00 |
March | 1354.32 | 01-MAR-00:10 | 692.02 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 50.13 | 05-MAR-07:00 |
April | 1354.32 | 01-APR-00:10 | 692.02 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.63 | 13-APR-17:00 | 39.50 | 08-APR-06:00 |
May | 1354.32 | 01-MAY-00:10 | 692.02 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.15 | 22-MAY-13:00 | 34.02 | 07-MAY-05:00 |
June | 1354.32 | 01-JUN-00:10 | 692.02 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.92 | 28-JUN-16:00 | 28.31 | 09-JUN-05:00 |
July | 1354.32 | 01-JUL-00:10 | 692.02 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.94 | 22-JUL-15:00 | 13.70 | 08-JUL-04:00 |
August | 1354.32 | 01-AUG-00:10 | 692.02 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.92 | 20-AUG-15:00 | 19.64 | 31-AUG-06:00 |
September | 1354.32 | 01-SEP-00:10 | 692.02 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.38 | 03-SEP-14:00 | 23.70 | 25-SEP-05:00 |
October | 1354.32 | 01-OCT-23:10 | 692.02 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.25 | 01-OCT-16:00 | 47.79 | 27-OCT-07:00 |
November | 1354.32 | 01-NOV-00:10 | 692.02 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 51.25 | 27-NOV-07:00 |
December | 1354.32 | 01-DEC-00:10 | 692.02 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 61.64 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1354.32 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.70 | |||||
Maximum of Months | 1354.32 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 23.92 | 61.64 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 286.42 | 02-JAN-00:10 | 684.18 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 131.63 | 21-JAN-07:00 |
February | 286.42 | 01-FEB-00:10 | 684.18 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 | 14-FEB-16:00 | 123.68 | 04-FEB-06:50 |
March | 286.42 | 01-MAR-00:10 | 684.18 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.35 | 08-MAR-14:00 | 112.84 | 05-MAR-07:00 |
April | 286.42 | 01-APR-00:10 | 684.18 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.88 | 13-APR-17:00 | 88.79 | 08-APR-06:00 |
May | 286.42 | 01-MAY-00:10 | 684.18 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.44 | 22-MAY-13:00 | 76.95 | 07-MAY-05:00 |
June | 286.42 | 01-JUN-00:10 | 684.18 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.53 | 28-JUN-16:00 | 65.66 | 09-JUN-05:00 |
July | 286.42 | 01-JUL-00:10 | 684.18 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.21 | 22-JUL-15:00 | 32.16 | 08-JUL-03:00 |
August | 286.42 | 01-AUG-00:10 | 684.18 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.36 | 20-AUG-16:00 | 46.01 | 31-AUG-06:00 |
September | 286.42 | 01-SEP-00:10 | 684.18 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.57 | 03-SEP-14:00 | 54.59 | 20-SEP-06:00 |
October | 286.42 | 01-OCT-23:10 | 684.18 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.65 | 01-OCT-16:00 | 108.45 | 27-OCT-07:00 |
November | 286.42 | 01-NOV-00:10 | 684.18 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 115.16 | 27-NOV-07:00 |
December | 286.42 | 01-DEC-00:10 | 684.18 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 137.87 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 286.42 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.16 | |||||
Maximum of Months | 286.42 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 56.53 | 137.87 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 220.32 | 02-JAN-00:10 | 251.84 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 75.94 | 21-JAN-07:00 |
February | 220.32 | 01-FEB-00:10 | 251.84 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.23 | 14-FEB-16:00 | 70.94 | 04-FEB-06:00 |
March | 220.32 | 01-MAR-00:10 | 251.84 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.57 | 08-MAR-14:00 | 63.89 | 05-MAR-07:00 |
April | 220.32 | 01-APR-00:10 | 251.84 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.13 | 13-APR-17:00 | 50.15 | 08-APR-06:00 |
May | 220.32 | 01-MAY-00:10 | 251.84 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.09 | 22-MAY-13:00 | 43.40 | 07-MAY-05:00 |
June | 220.32 | 01-JUN-00:10 | 251.84 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.61 | 28-JUN-16:00 | 36.96 | 09-JUN-05:00 |
July | 220.32 | 01-JUL-00:10 | 251.84 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.27 | 22-JUL-15:00 | 18.12 | 08-JUL-03:00 |
August | 220.32 | 01-AUG-00:10 | 251.84 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.43 | 20-AUG-15:00 | 25.68 | 31-AUG-06:00 |
September | 220.32 | 01-SEP-00:10 | 251.84 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.94 | 03-SEP-14:00 | 30.48 | 20-SEP-06:00 |
October | 220.32 | 01-OCT-23:10 | 251.84 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.11 | 01-OCT-16:00 | 61.17 | 27-OCT-07:00 |
November | 220.32 | 01-NOV-00:10 | 251.84 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 65.17 | 27-NOV-07:00 |
December | 220.32 | 01-DEC-00:10 | 251.84 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 79.28 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 220.32 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.12 | |||||
Maximum of Months | 220.32 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 32.61 | 79.28 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 325.08 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 197.22 | 21-JAN-07:00 |
February | 907.20 | 01-FEB-00:10 | 325.08 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 185.83 | 05-FEB-07:50 |
March | 907.20 | 01-MAR-00:10 | 325.08 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 168.53 | 05-MAR-07:00 |
April | 907.20 | 01-APR-00:10 | 325.08 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 15.21 | 13-APR-17:00 | 131.92 | 08-APR-06:00 |
May | 907.20 | 01-MAY-00:10 | 325.08 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 35.79 | 19-MAY-17:00 | 111.57 | 07-MAY-05:10 |
June | 907.20 | 01-JUN-00:10 | 325.08 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 80.45 | 28-JUN-16:00 | 91.42 | 09-JUN-05:10 |
July | 907.20 | 01-JUL-00:10 | 325.08 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 75.88 | 21-JUL-17:00 | 40.52 | 08-JUL-01:00 |
August | 907.20 | 01-AUG-00:10 | 325.08 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 65.17 | 20-AUG-16:00 | 63.34 | 31-AUG-06:00 |
September | 907.20 | 01-SEP-00:10 | 325.08 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 50.42 | 03-SEP-14:00 | 76.81 | 09-SEP-06:00 |
October | 907.20 | 01-OCT-23:10 | 325.08 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 33.52 | 01-OCT-16:00 | 160.69 | 26-OCT-07:00 |
November | 907.20 | 01-NOV-00:10 | 325.08 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 171.05 | 27-NOV-07:00 |
December | 907.20 | 01-DEC-00:10 | 325.08 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 197.35 | 15-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 907.20 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 40.52 | ||||||
Maximum of Months | 907.20 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 80.45 | 197.35 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 1701.53 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 336.39 | 20-JAN-02:00 |
February | 15368.40 | 01-FEB-00:10 | 1701.53 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 320.57 | 04-FEB-06:00 |
March | 15368.40 | 01-MAR-00:10 | 1701.53 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 287.37 | 06-MAR-06:00 |
April | 15368.40 | 01-APR-00:10 | 1701.53 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.02 | 13-APR-17:00 | 224.13 | 08-APR-06:00 |
May | 15368.40 | 01-MAY-00:10 | 1701.53 | 01-MAY-19:10 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.20 | 22-MAY-13:00 | 193.03 | 07-MAY-05:00 |
June | 15368.40 | 01-JUN-00:10 | 1701.53 | 01-JUN-19:10 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 137.00 | 28-JUN-16:00 | 165.54 | 09-JUN-05:00 |
July | 15368.40 | 01-JUL-00:10 | 1701.53 | 03-JUL-19:19 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 131.37 | 22-JUL-15:00 | 78.43 | 08-JUL-03:20 |
August | 15368.40 | 01-AUG-00:10 | 1701.53 | 01-AUG-19:10 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.62 | 20-AUG-15:00 | 112.42 | 31-AUG-06:00 |
September | 15368.40 | 01-SEP-00:10 | 1701.53 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.33 | 03-SEP-14:00 | 135.67 | 25-SEP-05:00 |
October | 15368.40 | 01-OCT-23:10 | 1701.53 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.56 | 01-OCT-16:00 | 273.24 | 26-OCT-05:00 |
November | 15368.40 | 01-NOV-00:10 | 1701.53 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 297.17 | 27-NOV-06:00 |
December | 15368.40 | 01-DEC-00:10 | 1701.53 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 357.01 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 15368.40 | 1701.53 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.43 | |||||
Maximum of Months | 15368.40 | 1701.53 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 137.00 | 357.01 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 9504.80 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 979.05 | 20-JAN-02:00 |
February | 45622.98 | 01-FEB-00:10 | 9504.80 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 932.50 | 04-FEB-06:00 |
March | 45622.98 | 01-MAR-00:10 | 9504.80 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 840.32 | 05-MAR-07:00 |
April | 45622.98 | 01-APR-00:10 | 9504.80 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.39 | 13-APR-17:00 | 661.88 | 08-APR-06:00 |
May | 45622.98 | 01-MAY-00:10 | 9504.80 | 01-MAY-19:10 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 184.67 | 22-MAY-13:00 | 570.97 | 07-MAY-05:00 |
June | 45622.98 | 01-JUN-00:10 | 9504.80 | 01-JUN-19:10 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 391.39 | 28-JUN-16:00 | 473.70 | 09-JUN-05:00 |
July | 45622.98 | 01-JUL-00:10 | 9504.80 | 03-JUL-19:19 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 375.32 | 22-JUL-15:00 | 224.18 | 08-JUL-03:50 |
August | 45622.98 | 01-AUG-00:10 | 9504.80 | 01-AUG-19:10 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 293.31 | 20-AUG-16:00 | 321.26 | 31-AUG-06:00 |
September | 45622.98 | 01-SEP-00:10 | 9504.80 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 235.22 | 03-SEP-14:00 | 389.64 | 09-SEP-06:00 |
October | 45622.98 | 01-OCT-23:10 | 9504.80 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 133.02 | 01-OCT-16:00 | 804.38 | 26-OCT-05:00 |
November | 45622.98 | 01-NOV-00:10 | 9504.80 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 865.29 | 27-NOV-06:00 |
December | 45622.98 | 01-DEC-00:10 | 9504.80 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1036.67 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 45622.98 | 9504.80 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 224.18 | |||||
Maximum of Months | 45622.98 | 9504.80 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 391.39 | 1036.67 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.88 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 84.19 | 21-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 177.88 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.45 | 14-FEB-16:10 | 78.66 | 04-FEB-06:06 |
March | 180.00 | 01-MAR-00:10 | 177.88 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.86 | 08-MAR-16:10 | 70.53 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 177.88 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.21 | 13-APR-17:00 | 53.66 | 08-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 177.88 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.77 | 19-MAY-15:10 | 45.38 | 07-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 177.88 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.26 | 28-JUN-16:00 | 35.89 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 177.88 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.30 | 22-JUL-15:10 | 14.49 | 01-JUL-08:00 |
August | 180.00 | 01-AUG-00:10 | 177.88 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.21 | 04-AUG-17:00 | 22.03 | 31-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 177.88 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.15 | 03-SEP-14:00 | 28.21 | 09-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 177.88 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.87 | 01-OCT-16:00 | 66.93 | 26-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 177.88 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 71.72 | 27-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 177.88 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 87.87 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.49 | |||||
Maximum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 38.26 | 87.87 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.86 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 84.18 | 21-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 177.86 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.18 | 14-FEB-16:10 | 78.66 | 04-FEB-06:06 |
March | 180.00 | 01-MAR-00:10 | 177.86 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.88 | 08-MAR-16:10 | 70.52 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 177.86 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.35 | 13-APR-17:00 | 53.65 | 08-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 177.86 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.83 | 19-MAY-15:10 | 45.37 | 07-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 177.86 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.32 | 28-JUN-16:00 | 35.89 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 177.86 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.45 | 22-JUL-15:10 | 17.14 | 01-JUL-08:00 |
August | 180.00 | 01-AUG-00:10 | 177.86 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.20 | 04-AUG-17:00 | 22.02 | 31-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 177.86 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.78 | 02-SEP-15:10 | 28.20 | 09-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 177.86 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.08 | 01-OCT-16:00 | 66.92 | 26-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 177.86 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 71.71 | 27-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 177.86 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 87.87 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.14 | |||||
Maximum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 38.32 | 87.87 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 111.79 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 26.45 | 26-JAN-04:00 |
February | 0.00 | 01-FEB-00:10 | 111.79 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 25.58 | 05-FEB-08:10 |
March | 0.00 | 01-MAR-00:10 | 111.79 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 23.10 | 05-MAR-07:00 |
April | 0.00 | 01-APR-00:10 | 111.79 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 18.73 | 06-APR-06:10 |
May | 0.00 | 01-MAY-00:10 | 111.79 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.29 | 22-MAY-13:00 | 16.25 | 07-MAY-05:00 |
June | 0.00 | 01-JUN-00:10 | 111.79 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.21 | 28-JUN-16:00 | 13.76 | 09-JUN-05:10 |
July | 0.00 | 01-JUL-00:10 | 111.79 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.80 | 22-JUL-15:00 | 7.72 | 08-JUL-04:00 |
August | 0.00 | 01-AUG-00:10 | 111.79 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.66 | 20-AUG-15:00 | 10.23 | 31-AUG-06:00 |
September | 0.00 | 01-SEP-00:10 | 111.79 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 03-SEP-14:00 | 12.01 | 09-SEP-06:00 |
October | 0.00 | 01-OCT-00:10 | 111.79 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.52 | 01-OCT-16:00 | 22.98 | 27-OCT-07:00 |
November | 0.00 | 01-NOV-00:10 | 111.79 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 23.88 | 27-NOV-07:30 |
December | 0.00 | 01-DEC-00:10 | 111.79 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 27.82 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 0.00 | 111.79 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.72 | |||||
Maximum of Months | 0.00 | 111.79 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 8.21 | 27.82 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 111.82 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 23.50 | 21-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 111.82 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.61 | 14-FEB-16:06 | 21.95 | 04-FEB-06:10 |
March | 180.00 | 01-MAR-00:10 | 111.82 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.08 | 08-MAR-16:10 | 19.68 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 111.82 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.45 | 13-APR-17:00 | 14.98 | 08-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 111.82 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.98 | 19-MAY-16:00 | 12.66 | 07-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 111.82 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 28-JUN-16:00 | 10.02 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 111.82 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.22 | 21-JUL-17:00 | 4.52 | 07-JUL-21:50 |
August | 180.00 | 01-AUG-00:10 | 111.82 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.45 | 20-AUG-15:50 | 6.15 | 31-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 111.82 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 02-SEP-15:10 | 7.87 | 09-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 111.82 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.39 | 01-OCT-16:00 | 18.68 | 26-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 111.82 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 20.02 | 27-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 111.82 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 24.52 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.52 | |||||
Maximum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 24.52 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.88 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 84.19 | 21-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 177.88 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.18 | 14-FEB-16:10 | 78.66 | 04-FEB-06:06 |
March | 180.00 | 01-MAR-00:10 | 177.88 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.88 | 08-MAR-16:10 | 70.53 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 177.88 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.37 | 13-APR-17:00 | 56.25 | 08-APR-07:20 |
May | 180.00 | 01-MAY-00:10 | 177.88 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.90 | 19-MAY-16:00 | 45.38 | 07-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 177.88 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.88 | 28-JUN-16:00 | 35.89 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 177.88 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.24 | 21-JUL-17:00 | 14.49 | 01-JUL-08:00 |
August | 180.00 | 01-AUG-00:10 | 177.88 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.86 | 20-AUG-16:00 | 22.03 | 31-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 177.88 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.82 | 02-SEP-15:40 | 28.21 | 09-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 177.88 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.30 | 01-OCT-16:00 | 66.93 | 26-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 177.88 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 72.16 | 28-NOV-08:10 |
December | 180.00 | 01-DEC-00:10 | 177.88 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 87.87 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.49 | |||||
Maximum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 41.88 | 87.87 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.86 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 84.18 | 21-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 177.86 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.18 | 14-FEB-16:09 | 78.66 | 04-FEB-06:06 |
March | 180.00 | 01-MAR-00:10 | 177.86 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.88 | 08-MAR-16:08 | 70.52 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 177.86 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.37 | 13-APR-17:00 | 56.24 | 08-APR-07:20 |
May | 180.00 | 01-MAY-00:10 | 177.86 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.90 | 19-MAY-16:00 | 45.37 | 07-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 177.86 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.60 | 28-JUN-16:00 | 35.89 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 177.86 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.17 | 21-JUL-17:00 | 20.83 | 08-JUL-07:40 |
August | 180.00 | 01-AUG-00:10 | 177.86 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.82 | 01-AUG-16:00 | 24.34 | 11-AUG-07:50 |
September | 180.00 | 01-SEP-00:10 | 177.86 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.67 | 02-SEP-15:10 | 28.20 | 09-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 177.86 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.33 | 01-OCT-16:00 | 66.92 | 26-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 177.86 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 71.71 | 27-NOV-06:50 |
December | 180.00 | 01-DEC-00:10 | 177.86 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 87.86 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.83 | |||||
Maximum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 41.60 | 87.86 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2263.36 | 02-JAN-00:10 | 1867.32 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 101.42 | 21-JAN-07:00 |
February | 2263.36 | 01-FEB-00:10 | 1867.32 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 94.97 | 04-FEB-06:00 |
March | 2263.36 | 01-MAR-00:10 | 1867.32 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 | 08-MAR-14:00 | 86.11 | 05-MAR-07:00 |
April | 2263.36 | 01-APR-00:10 | 1867.32 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.46 | 13-APR-17:00 | 68.30 | 08-APR-06:00 |
May | 2263.36 | 01-MAY-00:10 | 1867.32 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.08 | 22-MAY-13:00 | 58.94 | 07-MAY-05:00 |
June | 2263.36 | 01-JUN-00:10 | 1867.32 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.36 | 28-JUN-16:00 | 49.63 | 09-JUN-05:00 |
July | 2263.36 | 01-JUL-00:10 | 1867.32 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.58 | 22-JUL-15:00 | 24.55 | 08-JUL-03:00 |
August | 2263.36 | 01-AUG-00:10 | 1867.32 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.45 | 20-AUG-15:00 | 34.74 | 31-AUG-06:00 |
September | 2263.36 | 01-SEP-00:10 | 1867.32 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.01 | 03-SEP-14:00 | 41.97 | 20-SEP-06:00 |
October | 2263.36 | 01-OCT-23:10 | 1867.32 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.70 | 01-OCT-16:00 | 82.81 | 26-OCT-05:00 |
November | 2263.36 | 01-NOV-00:10 | 1867.32 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 88.98 | 27-NOV-06:00 |
December | 2263.36 | 01-DEC-00:10 | 1867.32 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 106.55 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.55 | ||||
Maximum of Months | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.36 | 106.55 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.88 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 84.38 | 21-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 177.88 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 14-FEB-16:10 | 78.85 | 04-FEB-06:06 |
March | 180.00 | 01-MAR-00:10 | 177.88 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 08-MAR-16:10 | 70.71 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 177.88 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.69 | 13-APR-17:00 | 53.83 | 08-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 177.88 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.27 | 19-MAY-15:10 | 45.55 | 07-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 177.88 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.17 | 28-JUN-15:50 | 36.06 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 177.88 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.64 | 22-JUL-15:10 | 14.64 | 01-JUL-08:00 |
August | 180.00 | 01-AUG-00:10 | 177.88 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.94 | 04-AUG-17:00 | 22.19 | 31-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 177.88 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.00 | 03-SEP-14:00 | 28.37 | 09-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 177.88 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.29 | 01-OCT-16:00 | 67.11 | 26-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 177.88 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 71.90 | 27-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 177.88 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 88.06 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.64 | |||||
Maximum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 37.17 | 88.06 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.86 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 84.37 | 21-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 177.86 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.03 | 14-FEB-16:10 | 78.84 | 04-FEB-06:06 |
March | 180.00 | 01-MAR-00:10 | 177.86 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.73 | 08-MAR-16:10 | 70.70 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 177.86 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.14 | 13-APR-17:00 | 53.83 | 08-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 177.86 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.33 | 19-MAY-15:10 | 45.54 | 07-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 177.86 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.17 | 28-JUN-15:50 | 36.05 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 177.86 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.63 | 22-JUL-15:10 | 16.39 | 01-JUL-08:00 |
August | 180.00 | 01-AUG-00:10 | 177.86 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.91 | 04-AUG-17:00 | 22.18 | 31-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 177.86 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.27 | 02-SEP-15:10 | 28.37 | 09-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 177.86 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.78 | 01-OCT-16:00 | 67.10 | 26-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 177.86 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 71.90 | 27-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 177.86 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 88.06 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.39 | |||||
Maximum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 37.17 | 88.06 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 111.82 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 43.17 | 21-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 111.82 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 40.34 | 04-FEB-06:10 |
March | 180.00 | 01-MAR-00:10 | 111.82 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.14 | 08-MAR-17:00 | 36.18 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 111.82 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.26 | 13-APR-17:00 | 27.54 | 08-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 111.82 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.13 | 19-MAY-16:10 | 23.30 | 07-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 111.82 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.23 | 28-JUN-16:00 | 18.45 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 111.82 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.39 | 21-JUL-17:00 | 7.49 | 01-JUL-08:00 |
August | 180.00 | 01-AUG-00:10 | 111.82 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.00 | 01-AUG-16:00 | 11.35 | 31-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 111.82 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.45 | 02-SEP-16:50 | 14.52 | 09-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 111.82 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.62 | 01-OCT-16:00 | 34.33 | 26-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 111.82 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 36.79 | 27-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 111.82 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 45.06 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.49 | |||||
Maximum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 21.23 | 45.06 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2988.03 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 226.15 | 21-JAN-07:00 |
February | 26988.77 | 01-FEB-00:10 | 2988.03 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 212.44 | 04-FEB-06:10 |
March | 26988.77 | 01-MAR-00:10 | 2988.03 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 192.48 | 05-MAR-07:00 |
April | 26988.77 | 01-APR-00:10 | 2988.03 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.22 | 13-APR-17:00 | 150.87 | 08-APR-06:00 |
May | 26988.77 | 01-MAY-00:10 | 2988.03 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.00 | 22-MAY-13:00 | 130.29 | 07-MAY-05:00 |
June | 26988.77 | 01-JUN-00:10 | 2988.03 | 01-JUN-19:10 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.25 | 28-JUN-16:00 | 106.96 | 09-JUN-05:00 |
July | 26988.77 | 01-JUL-00:10 | 2988.03 | 03-JUL-19:19 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.64 | 22-JUL-15:00 | 50.94 | 08-JUL-03:30 |
August | 26988.77 | 01-AUG-00:10 | 2988.03 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.19 | 20-AUG-15:00 | 72.74 | 31-AUG-06:00 |
September | 26988.77 | 01-SEP-00:10 | 2988.03 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.18 | 03-SEP-14:00 | 88.10 | 09-SEP-06:00 |
October | 26988.77 | 01-OCT-23:10 | 2988.03 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.24 | 01-OCT-16:00 | 183.31 | 26-OCT-05:00 |
November | 26988.77 | 01-NOV-00:10 | 2988.03 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 195.35 | 27-NOV-06:10 |
December | 26988.77 | 01-DEC-00:10 | 2988.03 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 235.28 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.94 | |||||
Maximum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 87.25 | 235.28 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2988.03 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 226.15 | 21-JAN-07:00 |
February | 26988.77 | 01-FEB-00:10 | 2988.03 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 212.44 | 04-FEB-06:10 |
March | 26988.77 | 01-MAR-00:10 | 2988.03 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 192.48 | 05-MAR-07:00 |
April | 26988.77 | 01-APR-00:10 | 2988.03 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.22 | 13-APR-17:00 | 150.88 | 08-APR-06:00 |
May | 26988.77 | 01-MAY-00:10 | 2988.03 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.00 | 22-MAY-13:00 | 130.29 | 07-MAY-05:00 |
June | 26988.77 | 01-JUN-00:10 | 2988.03 | 01-JUN-19:10 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.25 | 28-JUN-16:00 | 106.96 | 09-JUN-05:00 |
July | 26988.77 | 01-JUL-00:10 | 2988.03 | 03-JUL-19:19 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.64 | 22-JUL-15:00 | 50.94 | 08-JUL-03:30 |
August | 26988.77 | 01-AUG-00:10 | 2988.03 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.19 | 20-AUG-15:00 | 72.74 | 31-AUG-06:00 |
September | 26988.77 | 01-SEP-00:10 | 2988.03 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.18 | 03-SEP-14:00 | 88.10 | 09-SEP-06:00 |
October | 26988.77 | 01-OCT-23:10 | 2988.03 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.24 | 01-OCT-16:00 | 183.55 | 26-OCT-07:00 |
November | 26988.77 | 01-NOV-00:10 | 2988.03 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 195.35 | 27-NOV-06:10 |
December | 26988.77 | 01-DEC-00:10 | 2988.03 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 235.28 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.94 | |||||
Maximum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 87.25 | 235.28 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 1060.81 | 02-JAN-20:10 | 14912.86 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 202.42 | 21-JAN-07:00 |
February | 2401.70 | 01-FEB-00:10 | 1060.81 | 01-FEB-20:10 | 14912.86 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 190.17 | 04-FEB-06:10 |
March | 2401.70 | 01-MAR-00:10 | 1060.81 | 01-MAR-20:10 | 14912.86 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 172.28 | 05-MAR-07:00 |
April | 2401.70 | 01-APR-00:10 | 1060.81 | 03-APR-19:10 | 14912.86 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 11.01 | 13-APR-17:00 | 135.04 | 08-APR-06:00 |
May | 2401.70 | 01-MAY-00:10 | 1060.81 | 01-MAY-19:10 | 14912.86 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 32.29 | 22-MAY-13:00 | 116.63 | 07-MAY-05:00 |
June | 2401.70 | 01-JUN-00:10 | 1060.81 | 01-JUN-19:10 | 14912.86 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 78.19 | 28-JUN-16:00 | 95.75 | 09-JUN-05:00 |
July | 2401.70 | 01-JUL-00:10 | 1060.81 | 03-JUL-19:10 | 14912.86 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 74.94 | 22-JUL-15:00 | 45.61 | 08-JUL-03:00 |
August | 2401.70 | 01-AUG-00:10 | 1060.81 | 01-AUG-19:10 | 14912.86 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 58.43 | 20-AUG-15:00 | 65.10 | 31-AUG-06:00 |
September | 2401.70 | 01-SEP-00:10 | 1060.81 | 01-SEP-19:10 | 14912.86 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 46.77 | 03-SEP-14:00 | 78.84 | 09-SEP-06:00 |
October | 2401.70 | 01-OCT-23:10 | 1060.81 | 02-OCT-19:10 | 14912.86 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 26.26 | 01-OCT-16:00 | 164.27 | 26-OCT-07:00 |
November | 2401.70 | 01-NOV-00:10 | 1060.81 | 01-NOV-19:10 | 14912.86 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 174.85 | 27-NOV-06:10 |
December | 2401.70 | 01-DEC-00:10 | 1060.81 | 01-DEC-20:10 | 14912.86 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 210.63 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2401.70 | 1060.81 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 0.00 | 45.61 | ||||||
Maximum of Months | 2401.70 | 1060.81 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 78.19 | 210.63 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2395.44 | 02-JAN-00:10 | 1976.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 179.85 | 21-JAN-07:00 |
February | 2395.44 | 01-FEB-00:10 | 1976.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 168.03 | 04-FEB-07:00 |
March | 2395.44 | 01-MAR-00:10 | 1976.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 150.61 | 05-MAR-07:00 |
April | 2395.44 | 01-APR-00:10 | 1976.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.11 | 13-APR-17:00 | 116.72 | 08-APR-06:00 |
May | 2395.44 | 01-MAY-00:10 | 1976.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.48 | 22-MAY-13:00 | 100.37 | 07-MAY-05:00 |
June | 2395.44 | 01-JUN-00:10 | 1976.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.43 | 28-JUN-16:00 | 85.09 | 09-JUN-04:03 |
July | 2395.44 | 01-JUL-00:10 | 1976.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.27 | 22-JUL-15:00 | 42.00 | 08-JUL-03:00 |
August | 2395.44 | 01-AUG-00:10 | 1976.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.11 | 20-AUG-15:00 | 59.42 | 31-AUG-06:00 |
September | 2395.44 | 01-SEP-00:10 | 1976.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.72 | 03-SEP-14:00 | 71.51 | 20-SEP-06:00 |
October | 2395.44 | 01-OCT-23:10 | 1976.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.61 | 01-OCT-16:00 | 142.91 | 26-OCT-07:00 |
November | 2395.44 | 01-NOV-00:10 | 1976.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 153.18 | 27-NOV-07:00 |
December | 2395.44 | 01-DEC-00:10 | 1976.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 187.74 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.00 | ||||
Maximum of Months | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.43 | 187.74 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 19640.85 | 06-JAN-22:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 18412.51 | 01-FEB-22:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 15625.68 | 01-MAR-22:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 13850.94 | 07-APR-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 14746.38 | 11-MAY-21:00 | 20447.81 | 23449.32 | 18251.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17240.61 | 08-JUN-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 19322.70 | 27-JUL-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 20837.68 | 23-AUG-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 22566.41 | 08-SEP-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 23217.66 | 12-OCT-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 22861.18 | 03-NOV-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 22163.84 | 01-DEC-22:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 13850.94 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23217.66 | 20447.81 | 23449.32 | 18251.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4213.84 | 03-JAN-13:00 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.86 |
February | 4454.34 | 14-FEB-13:10 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.40 |
March | 3936.50 | 08-MAR-13:30 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.36 |
April | 3093.60 | 13-APR-12:50 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.69 |
May | 2433.41 | 13-MAY-13:00 | 389.84 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 18.47 | 0.00 |
June | 2813.07 | 29-JUN-14:30 | 389.84 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 55.46 | 0.00 |
July | 3004.39 | 22-JUL-13:30 | 389.84 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 54.16 | 0.00 |
August | 3712.21 | 22-AUG-13:10 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 29.38 | 0.00 |
September | 4424.89 | 28-SEP-13:05 | 519.79 | 332.00 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 21.90 | 0.00 |
October | 4547.29 | 19-OCT-12:30 | 519.79 | 332.00 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.38 |
November | 4335.18 | 01-NOV-12:30 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.59 |
December | 4326.45 | 31-DEC-13:00 | 389.84 | 199.20 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.41 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2433.41 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4547.29 | 519.79 | 332.00 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 55.46 | 72.41 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1398.90 | 03-JAN-21:10 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.77 |
February | 1659.24 | 15-FEB-21:10 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.12 |
March | 1696.34 | 08-MAR-21:03 | 7223.04 | 3690.75 | 4512.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.98 |
April | 1937.86 | 13-APR-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.94 |
May | 1998.17 | 19-MAY-20:54 | 6019.20 | 3075.62 | 3760.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.18 |
June | 2235.37 | 28-JUN-20:10 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 9.63 | 0.00 |
July | 2299.23 | 21-JUL-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 9.91 | 0.00 |
August | 2240.84 | 18-AUG-20:10 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 5.05 | 0.00 |
September | 2091.68 | 13-SEP-20:04 | 6019.20 | 3075.62 | 3760.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.79 |
October | 2028.15 | 05-OCT-20:10 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.72 |
November | 1674.94 | 02-NOV-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.59 |
December | 1333.64 | 29-DEC-22:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.49 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1333.64 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2299.23 | 7223.04 | 3690.75 | 4512.87 | 0.00 | 0.00 | 0.00 | 0.00 | 9.91 | 39.49 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 807.72 | 01-JAN-13:00 | 95.47 | 228.06 | 353.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.26 |
February | 889.74 | 14-FEB-13:10 | 63.65 | 190.05 | 309.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.31 |
March | 898.96 | 26-MAR-10:35 | 190.94 | 456.12 | 706.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.22 |
April | 1031.50 | 29-APR-10:33 | 286.42 | 570.15 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.92 |
May | 1364.28 | 19-MAY-20:54 | 1272.96 | 3040.79 | 3976.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.80 |
June | 1932.48 | 29-JUN-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 10.69 | 0.00 |
July | 1947.15 | 21-JUL-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 25.66 | 0.00 |
August | 1842.13 | 18-AUG-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 12.66 | 0.00 |
September | 1534.82 | 01-SEP-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.80 |
October | 1350.44 | 02-OCT-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.64 |
November | 920.67 | 01-NOV-12:30 | 63.65 | 190.05 | 309.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.27 |
December | 820.93 | 31-DEC-13:00 | 95.47 | 228.06 | 353.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.70 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 807.72 | 63.65 | 190.05 | 309.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1947.15 | 1272.96 | 3040.79 | 3976.33 | 0.00 | 0.00 | 0.00 | 0.00 | 25.66 | 55.70 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 474.67 | 01-JAN-13:00 | 73.44 | 83.94 | 101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.87 |
February | 528.65 | 14-FEB-13:10 | 48.96 | 69.95 | 89.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.09 |
March | 526.41 | 26-MAR-10:35 | 146.88 | 167.88 | 203.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.84 |
April | 607.42 | 29-APR-10:33 | 220.32 | 209.86 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 |
May | 632.17 | 21-MAY-10:35 | 146.88 | 167.88 | 203.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.65 | 0.00 |
June | 925.67 | 28-JUN-19:10 | 171.36 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 17.56 | 0.00 |
July | 971.68 | 21-JUL-18:40 | 171.36 | 223.85 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 24.26 | 0.00 |
August | 860.92 | 18-AUG-19:40 | 171.36 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 9.85 | 0.00 |
September | 660.01 | 03-SEP-10:35 | 146.88 | 167.88 | 203.92 | 0.00 | 0.00 | 0.00 | 0.00 | 10.98 | 0.00 |
October | 642.97 | 01-OCT-10:35 | 146.88 | 167.88 | 203.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.18 |
November | 541.18 | 01-NOV-12:30 | 48.96 | 69.95 | 89.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.55 |
December | 481.79 | 31-DEC-13:00 | 73.44 | 83.94 | 101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.62 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 474.67 | 48.96 | 69.95 | 89.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 971.68 | 220.32 | 251.84 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 24.26 | 31.62 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 37422.31 | 05-JAN-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 110.20 |
February | 37791.99 | 14-FEB-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 79.40 |
March | 38084.76 | 08-MAR-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 56.37 |
April | 38694.67 | 28-APR-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 9.82 |
May | 38871.53 | 19-MAY-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 8.61 | 0.00 |
June | 39366.66 | 28-JUN-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 32.02 | 0.00 |
July | 39386.60 | 21-JUL-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 35.04 | 0.00 |
August | 39230.16 | 17-AUG-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 23.10 | 0.00 |
September | 38873.97 | 13-SEP-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
October | 38597.75 | 02-OCT-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 28.18 |
November | 37730.91 | 09-NOV-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 66.27 |
December | 37412.56 | 01-DEC-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 82.97 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 37412.56 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 39386.60 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 35.04 | 110.20 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 15628.12 | 01-JAN-13:00 | 5122.80 | 124.78 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.85 |
February | 15548.23 | 14-FEB-13:10 | 3415.20 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.87 |
March | 14192.81 | 11-MAR-13:30 | 5122.80 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.59 |
April | 11843.73 | 01-APR-13:30 | 5122.80 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.90 |
May | 10645.12 | 19-MAY-21:05 | 61473.60 | 4537.41 | 2845.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.53 |
June | 11729.85 | 27-JUN-21:10 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 46.24 | 0.00 |
July | 11975.89 | 21-JUL-21:10 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 54.15 | 0.00 |
August | 12559.92 | 20-AUG-12:00 | 5122.80 | 124.78 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 82.93 | 0.00 |
September | 14367.47 | 28-SEP-13:10 | 6830.40 | 207.96 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 48.41 | 0.00 |
October | 15465.21 | 15-OCT-12:00 | 5122.80 | 124.78 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.89 |
November | 16013.15 | 23-NOV-11:00 | 8538.00 | 124.78 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.82 |
December | 16174.45 | 31-DEC-13:00 | 5122.80 | 124.78 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10645.12 | 3415.20 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16174.45 | 61473.60 | 4537.41 | 2845.02 | 0.00 | 0.00 | 0.00 | 0.00 | 82.93 | 160.06 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 32666.10 | 03-JAN-21:10 | 40553.76 | 8448.71 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 617.93 |
February | 35750.41 | 14-FEB-22:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 384.49 |
March | 35771.20 | 08-MAR-21:03 | 243322.56 | 50692.26 | 57008.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 294.16 |
April | 38389.68 | 13-APR-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.95 |
May | 39007.20 | 19-MAY-21:05 | 182491.92 | 25346.13 | 29559.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.40 |
June | 42394.38 | 28-JUN-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 125.74 | 0.00 |
July | 43028.96 | 21-JUL-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 154.66 | 0.00 |
August | 42547.33 | 18-AUG-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 47.74 | 0.00 |
September | 41053.03 | 13-SEP-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.78 |
October | 40367.26 | 06-OCT-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.90 |
November | 35803.95 | 01-NOV-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 469.94 |
December | 32108.48 | 19-DEC-19:05 | 212907.24 | 50692.26 | 57008.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 582.60 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 32108.48 | 40553.76 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 43028.96 | 243322.56 | 50692.26 | 57008.13 | 0.00 | 0.00 | 0.00 | 0.00 | 154.66 | 617.93 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2444.46 | 15-JAN-16:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.94 |
February | 2560.96 | 14-FEB-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.45 |
March | 2558.87 | 07-MAR-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.73 |
April | 2567.58 | 13-APR-15:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 5.30 | 0.00 |
May | 2555.83 | 20-MAY-15:02 | 324.00 | 352.21 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 9.59 | 0.00 |
June | 2586.10 | 20-JUN-18:02 | 831.60 | 949.89 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 17.79 | 0.00 |
July | 2448.20 | 02-JUL-18:02 | 702.00 | 1067.29 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 20.80 | 0.00 |
August | 2545.22 | 23-AUG-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 1.75 | 0.00 |
September | 2393.22 | 08-SEP-15:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.46 |
October | 2582.34 | 19-OCT-15:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.62 |
November | 2465.60 | 03-NOV-15:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.72 |
December | 2428.49 | 31-DEC-16:02 | 324.00 | 352.21 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2393.22 | 324.00 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2586.10 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 20.80 | 34.30 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2342.96 | 02-JAN-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.91 |
February | 2462.38 | 14-FEB-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.94 |
March | 2779.78 | 30-MAR-18:11 | 1386.00 | 1582.97 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.86 |
April | 2909.00 | 25-APR-16:21 | 777.60 | 398.41 | 1011.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.40 |
May | 2676.52 | 20-MAY-21:51 | 1247.40 | 1360.64 | 805.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.69 |
June | 2766.52 | 14-JUN-08:21 | 360.00 | 782.59 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 3.88 | 0.00 |
July | 2796.96 | 06-JUL-08:61 | 360.00 | 782.59 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 2.68 | 0.00 |
August | 2776.36 | 29-AUG-16:31 | 972.00 | 498.01 | 1264.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.27 |
September | 2605.35 | 01-SEP-21:51 | 1440.00 | 953.34 | 716.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.60 |
October | 2497.59 | 17-OCT-19:21 | 1108.80 | 1422.89 | 1306.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.25 |
November | 2373.85 | 03-NOV-15:02 | 583.20 | 298.81 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.23 |
December | 2341.68 | 02-DEC-16:01 | 378.00 | 410.86 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.16 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2341.68 | 360.00 | 298.81 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2909.00 | 1440.00 | 1582.97 | 1306.30 | 0.00 | 0.00 | 0.00 | 0.00 | 3.88 | 30.16 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 726.54 | 03-JAN-12:40 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.99 |
February | 741.30 | 14-FEB-13:00 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.22 |
March | 626.27 | 08-MAR-13:30 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.76 |
April | 458.24 | 13-APR-13:15 | 0.00 | 62.60 | 61.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.88 |
May | 326.21 | 13-MAY-13:05 | 0.00 | 73.78 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 0.00 |
June | 366.41 | 29-JUN-16:10 | 0.00 | 31.30 | 123.84 | 0.00 | 0.00 | 0.00 | 0.00 | 5.69 | 0.00 |
July | 400.08 | 23-JUL-13:30 | 0.00 | 36.89 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 6.41 | 0.00 |
August | 522.77 | 22-AUG-13:30 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 3.24 | 0.00 |
September | 676.02 | 28-SEP-13:30 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 1.91 | 0.00 |
October | 730.93 | 19-OCT-12:25 | 0.00 | 62.60 | 61.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.41 |
November | 730.01 | 20-NOV-12:10 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.30 |
December | 741.06 | 31-DEC-13:40 | 0.00 | 36.89 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.84 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 326.21 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 741.30 | 0.00 | 73.78 | 123.84 | 0.00 | 0.00 | 0.00 | 0.00 | 6.41 | 12.84 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 702.35 | 01-JAN-09:02 | 324.00 | 375.72 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.41 |
February | 746.15 | 15-FEB-19:01 | 970.20 | 696.66 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.34 |
March | 773.59 | 27-MAR-15:02 | 583.20 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.89 |
April | 838.66 | 27-APR-21:51 | 1440.00 | 599.37 | 701.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.03 |
May | 855.82 | 20-MAY-21:51 | 1247.40 | 855.44 | 789.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.62 |
June | 889.00 | 14-JUN-08:21 | 360.00 | 492.02 | 1109.66 | 0.00 | 0.00 | 0.00 | 0.00 | 1.56 | 0.00 |
July | 860.78 | 27-JUL-21:51 | 1620.00 | 674.29 | 789.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.03 |
August | 868.36 | 22-AUG-21:51 | 1620.00 | 674.29 | 789.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.37 |
September | 839.19 | 30-SEP-21:51 | 970.20 | 665.35 | 614.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.92 |
October | 824.32 | 05-OCT-21:51 | 1260.00 | 524.45 | 614.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.60 |
November | 746.65 | 02-NOV-18:11 | 970.20 | 696.66 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.15 |
December | 712.85 | 01-DEC-19:02 | 831.60 | 597.13 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.39 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 702.35 | 324.00 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 889.00 | 1620.00 | 855.44 | 1109.66 | 0.00 | 0.00 | 0.00 | 0.00 | 1.56 | 14.41 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2152.43 | 27-JAN-09:02 | 216.00 | 469.61 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.48 |
February | 2234.02 | 14-FEB-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 |
March | 2217.88 | 11-MAR-09:02 | 324.00 | 597.68 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.22 |
April | 2278.99 | 29-APR-08:61 | 378.00 | 697.30 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.06 |
May | 2283.32 | 14-MAY-08:62 | 324.00 | 597.68 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.58 |
June | 2331.44 | 18-JUN-08:62 | 324.00 | 597.68 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 | 0.00 |
July | 2321.96 | 04-JUL-08:62 | 324.00 | 597.68 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 4.22 | 0.00 |
August | 2294.25 | 17-AUG-08:61 | 252.00 | 547.88 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 6.62 | 0.00 |
September | 2227.97 | 02-SEP-08:62 | 324.00 | 597.68 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.63 |
October | 2241.20 | 19-OCT-15:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.07 |
November | 2199.25 | 18-NOV-09:02 | 324.00 | 597.68 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.32 |
December | 2167.91 | 31-DEC-09:02 | 324.00 | 597.68 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.58 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2152.43 | 216.00 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2331.44 | 680.40 | 697.30 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 6.62 | 63.58 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2021.05 | 27-JAN-09:02 | 216.00 | 469.55 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.89 |
February | 2144.36 | 14-FEB-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.43 |
March | 2171.98 | 26-MAR-08:62 | 324.00 | 597.61 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.72 |
April | 2612.36 | 28-APR-08:51 | 288.00 | 626.07 | 905.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.41 |
May | 2775.61 | 14-MAY-08:32 | 324.00 | 597.61 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.31 |
June | 2877.01 | 14-JUN-08:62 | 216.00 | 469.55 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.48 |
July | 2929.13 | 04-JUL-08:62 | 324.00 | 597.61 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.99 |
August | 2810.35 | 05-AUG-08:32 | 324.00 | 597.61 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.07 |
September | 2686.89 | 02-SEP-08:32 | 324.00 | 597.61 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.65 |
October | 2496.10 | 11-OCT-08:51 | 360.00 | 782.59 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.93 |
November | 2115.83 | 24-NOV-09:02 | 216.00 | 469.55 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.43 |
December | 2069.48 | 31-DEC-09:02 | 324.00 | 597.61 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.81 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2021.05 | 216.00 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.43 | |
Maximum of Months | 2929.13 | 680.40 | 782.59 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.81 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1759.28 | 01-JAN-13:00 | 754.45 | 622.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.31 |
February | 1898.80 | 14-FEB-13:20 | 502.97 | 518.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.28 |
March | 1872.07 | 12-MAR-10:35 | 1508.90 | 1244.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.78 |
April | 2083.57 | 29-APR-10:33 | 2263.36 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.32 |
May | 2149.22 | 21-MAY-10:35 | 1508.90 | 1244.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 | 0.00 |
June | 3121.98 | 23-JUN-18:17 | 5281.16 | 4979.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.03 | 0.00 |
July | 3283.31 | 21-JUL-18:40 | 1760.39 | 1659.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.23 | 0.00 |
August | 3071.01 | 18-AUG-18:17 | 5281.16 | 4979.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.86 | 0.00 |
September | 2488.88 | 21-SEP-18:03 | 10562.33 | 9959.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.59 | 0.00 |
October | 2403.95 | 05-OCT-18:03 | 10562.33 | 9959.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.16 |
November | 1936.01 | 01-NOV-12:30 | 502.97 | 518.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.82 |
December | 1753.73 | 31-DEC-13:00 | 754.45 | 622.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 1753.73 | 502.97 | 518.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3283.31 | 10562.33 | 9959.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.23 | 44.55 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2588.40 | 05-JAN-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.70 |
February | 2709.87 | 14-FEB-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.64 |
March | 2706.73 | 07-MAR-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.91 |
April | 2723.23 | 13-APR-15:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 5.07 | 0.00 |
May | 2714.70 | 20-MAY-18:02 | 702.00 | 1067.29 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 7.96 | 0.00 |
June | 2749.64 | 20-JUN-18:02 | 831.60 | 949.89 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 17.53 | 0.00 |
July | 2636.32 | 28-JUL-18:02 | 831.60 | 949.89 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 14.76 | 0.00 |
August | 2659.32 | 23-AUG-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 1.53 | 0.00 |
September | 2556.60 | 02-SEP-18:02 | 702.00 | 1067.29 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 15.89 | 0.00 |
October | 2732.31 | 19-OCT-15:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.80 |
November | 2608.69 | 20-NOV-16:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.93 |
December | 2573.30 | 31-DEC-16:02 | 324.00 | 352.21 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2556.60 | 324.00 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2749.64 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 17.53 | 34.51 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2468.32 | 05-JAN-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.09 |
February | 2588.80 | 14-FEB-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.05 |
March | 2990.41 | 30-MAR-18:11 | 1386.00 | 1582.97 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.93 |
April | 3081.43 | 25-APR-16:21 | 777.60 | 398.41 | 1011.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.65 |
May | 2884.40 | 06-MAY-19:41 | 1170.00 | 1778.61 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.62 |
June | 2909.46 | 14-JUN-08:21 | 360.00 | 782.59 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 3.74 | 0.00 |
July | 2933.00 | 06-JUL-08:61 | 360.00 | 782.59 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 2.78 | 0.00 |
August | 2949.97 | 23-AUG-17:01 | 680.40 | 834.17 | 884.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.26 |
September | 2675.79 | 01-SEP-21:51 | 1440.00 | 953.34 | 716.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.60 |
October | 2678.61 | 21-OCT-19:01 | 936.00 | 1422.89 | 1306.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.94 |
November | 2478.70 | 06-NOV-16:02 | 583.20 | 298.81 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.82 |
December | 2456.12 | 02-DEC-16:01 | 378.00 | 410.86 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.22 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2456.12 | 360.00 | 298.81 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3081.43 | 1440.00 | 1778.61 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 3.74 | 30.93 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1369.03 | 03-JAN-13:53 | 108.00 | 93.93 | 92.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.10 |
February | 1364.56 | 13-FEB-13:25 | 72.00 | 62.62 | 61.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.72 |
March | 1318.07 | 12-MAR-15:02 | 324.00 | 221.41 | 325.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.24 |
April | 1314.68 | 01-APR-15:02 | 324.00 | 221.41 | 325.16 | 0.00 | 0.00 | 0.00 | 0.00 | 1.70 | 0.00 |
May | 1287.31 | 20-MAY-15:02 | 324.00 | 221.41 | 325.16 | 0.00 | 0.00 | 0.00 | 0.00 | 4.95 | 0.00 |
June | 1282.56 | 20-JUN-15:02 | 583.20 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 10.39 | 0.00 |
July | 1274.66 | 27-JUL-18:02 | 831.60 | 597.13 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 5.86 | 0.00 |
August | 1284.74 | 27-AUG-15:02 | 270.00 | 184.51 | 270.96 | 0.00 | 0.00 | 0.00 | 0.00 | 6.39 | 0.00 |
September | 1285.18 | 25-SEP-15:02 | 583.20 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 5.19 | 0.00 |
October | 1389.48 | 15-OCT-15:08 | 324.00 | 221.41 | 325.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.66 |
November | 1369.40 | 07-NOV-13:23 | 108.00 | 93.93 | 92.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.69 |
December | 1348.49 | 30-DEC-13:35 | 108.00 | 73.80 | 67.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.62 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1274.66 | 72.00 | 62.62 | 61.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1389.48 | 831.60 | 597.13 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 10.39 | 18.62 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 17751.44 | 05-JAN-22:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.32 |
February | 19091.31 | 14-FEB-23:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.92 |
March | 19639.74 | 16-MAR-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.00 |
April | 21517.66 | 28-APR-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.24 |
May | 22271.57 | 19-MAY-21:05 | 107955.07 | 7968.08 | 26991.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.10 |
June | 23552.36 | 27-JUN-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 25.65 | 0.00 |
July | 23701.60 | 21-JUL-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 32.35 | 0.00 |
August | 23004.85 | 17-AUG-22:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 19.06 | 0.00 |
September | 22069.38 | 01-SEP-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.88 |
October | 21572.95 | 02-OCT-21:52 | 215910.14 | 15936.16 | 53983.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.53 |
November | 19393.52 | 02-NOV-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.68 |
December | 18279.27 | 01-DEC-22:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.11 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 17751.44 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23701.60 | 215910.14 | 15936.16 | 53983.22 | 0.00 | 0.00 | 0.00 | 0.00 | 32.35 | 135.32 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19497.50 | 05-JAN-22:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.33 |
February | 20584.23 | 14-FEB-23:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.93 |
March | 21176.23 | 16-MAR-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.00 |
April | 22756.34 | 28-APR-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.24 |
May | 23471.06 | 19-MAY-21:05 | 107955.07 | 7968.08 | 26991.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.10 |
June | 24738.17 | 27-JUN-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 25.63 | 0.00 |
July | 24884.71 | 21-JUL-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 32.33 | 0.00 |
August | 24177.55 | 17-AUG-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 17.00 | 0.00 |
September | 23226.22 | 01-SEP-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.06 |
October | 22696.94 | 02-OCT-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.54 |
November | 20972.80 | 08-NOV-22:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.89 |
December | 20079.74 | 01-DEC-22:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.11 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 19497.50 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24884.71 | 107955.07 | 7968.08 | 26991.61 | 0.00 | 0.00 | 0.00 | 0.00 | 32.33 | 135.33 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 28127.91 | 01-JAN-11:40 | 1601.14 | 707.21 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 83.64 |
February | 28779.56 | 14-FEB-11:40 | 1067.42 | 589.34 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 43.18 |
March | 29785.96 | 12-MAR-10:40 | 1601.14 | 707.21 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 68.47 |
April | 30806.48 | 29-APR-10:33 | 2401.70 | 884.01 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 21.78 |
May | 30860.90 | 20-MAY-10:37 | 2401.70 | 884.01 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 9.54 |
June | 31481.11 | 29-JUN-10:40 | 1601.14 | 884.01 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 45.44 | 0.00 |
July | 31783.26 | 23-JUL-10:40 | 1601.14 | 707.21 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 40.74 | 0.00 |
August | 31748.10 | 20-AUG-10:40 | 1601.14 | 707.21 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 32.13 | 0.00 |
September | 31569.11 | 03-SEP-10:40 | 1601.14 | 707.21 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 23.51 | 0.00 |
October | 30911.27 | 01-OCT-10:40 | 1601.14 | 707.21 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 6.29 |
November | 29104.29 | 01-NOV-10:33 | 1601.14 | 884.01 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 63.16 |
December | 28044.72 | 30-DEC-11:45 | 1601.14 | 589.34 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 94.19 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 28044.72 | 1067.42 | 589.34 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31783.26 | 2401.70 | 884.01 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 45.44 | 94.19 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3728.08 | 01-JAN-13:00 | 798.48 | 658.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.35 |
February | 4217.00 | 14-FEB-13:20 | 532.32 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.69 |
March | 3912.52 | 08-MAR-11:33 | 1596.96 | 1646.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.50 |
April | 4742.32 | 13-APR-15:02 | 7984.80 | 3293.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.38 | 0.00 |
May | 5385.39 | 20-MAY-14:20 | 798.48 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.05 | 0.00 |
June | 7114.41 | 28-JUN-15:05 | 5323.20 | 2195.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.05 | 0.00 |
July | 7179.05 | 22-JUL-13:30 | 798.48 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.74 | 0.00 |
August | 7245.12 | 20-AUG-13:10 | 532.32 | 439.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.35 | 0.00 |
September | 7136.49 | 03-SEP-13:30 | 532.32 | 439.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.36 | 0.00 |
October | 6491.99 | 01-OCT-13:30 | 532.32 | 439.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.56 | 0.00 |
November | 4097.22 | 01-NOV-12:30 | 532.32 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.01 |
December | 3790.93 | 31-DEC-13:00 | 798.48 | 658.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.37 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 3728.08 | 532.32 | 439.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7245.12 | 7984.80 | 3293.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.05 | 81.37 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.387975E+12 | 230774.12 | 03-JAN-19:10 | 0.523207E+12 | 564302.97 | 27-JAN-18:40 |
February | 0.350912E+12 | 231837.85 | 14-FEB-19:10 | 0.467798E+12 | 559039.33 | 07-FEB-18:49 |
March | 0.386756E+12 | 235733.35 | 13-MAR-18:10 | 0.518656E+12 | 527364.26 | 03-MAR-18:00 |
April | 0.397218E+12 | 297255.91 | 28-APR-18:49 | 0.456276E+12 | 481742.97 | 07-APR-20:40 |
May | 0.439557E+12 | 318953.76 | 19-MAY-19:10 | 0.413368E+12 | 427882.17 | 01-MAY-21:10 |
June | 0.495520E+12 | 351800.21 | 27-JUN-19:49 | 0.352988E+12 | 335049.96 | 08-JUN-17:00 |
July | 0.557571E+12 | 366453.59 | 21-JUL-19:19 | 0.349451E+12 | 310583.59 | 03-JUL-17:49 |
August | 0.539538E+12 | 351838.92 | 18-AUG-18:49 | 0.348162E+12 | 307449.42 | 31-AUG-17:30 |
September | 0.469444E+12 | 328896.64 | 13-SEP-18:19 | 0.346144E+12 | 314420.08 | 29-SEP-17:00 |
October | 0.428095E+12 | 304139.01 | 05-OCT-18:10 | 0.443457E+12 | 461468.58 | 26-OCT-19:00 |
November | 0.380369E+12 | 239779.72 | 02-NOV-18:19 | 0.491309E+12 | 534366.22 | 15-NOV-18:00 |
December | 0.390981E+12 | 228807.00 | 29-DEC-19:30 | 0.530346E+12 | 551264.49 | 27-DEC-18:30 |
Annual Sum or Average | 0.522394E+13 | 0.524116E+13 | ||||
Minimum of Months | 0.350912E+12 | 228807.00 | 0.346144E+12 | 307449.42 | ||
Maximum of Months | 0.557571E+12 | 366453.59 | 0.530346E+12 | 564302.97 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.669564E+11 | 0.193220E+11 | 0.140828E+12 | 0.691145E+11 | 0.435553E+11 | 0.578221E+10 | 0.00 | 0.100744E+11 | 0.00 | 0.00 | 0.191190E+11 | 0.804731E+10 | 0.00 |
February | 0.603229E+11 | 0.164570E+11 | 0.127191E+12 | 0.624260E+11 | 0.394621E+11 | 0.566645E+10 | 0.00 | 0.119679E+11 | 0.00 | 0.00 | 0.154691E+11 | 0.727177E+10 | 0.00 |
March | 0.665120E+11 | 0.167828E+11 | 0.140882E+12 | 0.691168E+11 | 0.444189E+11 | 0.686624E+10 | 0.00 | 0.189106E+11 | 0.00 | 0.00 | 0.100406E+11 | 0.804576E+10 | 0.00 |
April | 0.639540E+11 | 0.147691E+11 | 0.136245E+12 | 0.668843E+11 | 0.468404E+11 | 0.690544E+10 | 0.00 | 0.437363E+11 | 0.00 | 0.00 | 0.508901E+10 | 0.779705E+10 | 0.00 |
May | 0.659458E+11 | 0.140066E+11 | 0.140860E+12 | 0.691152E+11 | 0.514287E+11 | 0.706963E+10 | 0.00 | 0.716865E+11 | 0.00 | 0.00 | 0.618487E+10 | 0.804709E+10 | 0.00 |
June | 0.636084E+11 | 0.128887E+11 | 0.136336E+12 | 0.668864E+11 | 0.574467E+11 | 0.707131E+10 | 0.00 | 0.126854E+12 | 0.00 | 0.00 | 0.115482E+11 | 0.778858E+10 | 0.00 |
July | 0.658669E+11 | 0.136661E+11 | 0.140770E+12 | 0.691127E+11 | 0.626353E+11 | 0.754970E+10 | 0.00 | 0.170229E+12 | 0.00 | 0.00 | 0.143803E+11 | 0.805550E+10 | 0.00 |
August | 0.659595E+11 | 0.146951E+11 | 0.140892E+12 | 0.691165E+11 | 0.631365E+11 | 0.753838E+10 | 0.00 | 0.152689E+12 | 0.00 | 0.00 | 0.121393E+11 | 0.804707E+10 | 0.00 |
September | 0.642495E+11 | 0.156205E+11 | 0.136256E+12 | 0.668845E+11 | 0.579254E+11 | 0.698939E+10 | 0.00 | 0.101572E+12 | 0.00 | 0.00 | 0.702986E+10 | 0.779842E+10 | 0.00 |
October | 0.667699E+11 | 0.176341E+11 | 0.140818E+12 | 0.691143E+11 | 0.540513E+11 | 0.701656E+10 | 0.00 | 0.527377E+11 | 0.00 | 0.00 | 0.669506E+10 | 0.804571E+10 | 0.00 |
November | 0.647087E+11 | 0.183522E+11 | 0.136330E+12 | 0.668856E+11 | 0.460964E+11 | 0.643283E+10 | 0.00 | 0.153724E+11 | 0.00 | 0.00 | 0.134052E+11 | 0.778026E+10 | 0.00 |
December | 0.670414E+11 | 0.196774E+11 | 0.140770E+12 | 0.691134E+11 | 0.446952E+11 | 0.579142E+10 | 0.00 | 0.104493E+11 | 0.00 | 0.00 | 0.202183E+11 | 0.805575E+10 | 0.00 |
Annual Sum or Average | 0.781895E+12 | 0.193872E+12 | 0.165818E+13 | 0.813770E+12 | 0.611692E+12 | 0.806796E+11 | 0.00 | 0.786279E+12 | 0.00 | 0.00 | 0.141319E+12 | 0.947803E+11 | 0.00 |
Minimum of Months | 0.603229E+11 | 0.128887E+11 | 0.127191E+12 | 0.624260E+11 | 0.394621E+11 | 0.566645E+10 | 0.00 | 0.100744E+11 | 0.00 | 0.00 | 0.508901E+10 | 0.727177E+10 | 0.00 |
Maximum of Months | 0.670414E+11 | 0.196774E+11 | 0.140892E+12 | 0.691168E+11 | 0.631365E+11 | 0.754970E+10 | 0.00 | 0.170229E+12 | 0.00 | 0.00 | 0.202183E+11 | 0.805575E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.151918E+12 | 0.00 | 0.129220E+12 | 0.00 | 0.242069E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.110619E+12 | 0.00 | 0.219974E+12 | 0.00 | 0.00 |
March | 0.152024E+12 | 0.00 | 0.127657E+12 | 0.00 | 0.238976E+12 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.875795E+11 | 0.00 | 0.221741E+12 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.445728E+11 | 0.00 | 0.216817E+12 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 0.719640E+10 | 0.00 | 0.198678E+12 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 7755512.91 | 0.00 | 0.197623E+12 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 66694245.69 | 0.00 | 0.196057E+12 | 0.00 | 0.00 |
September | 0.146971E+12 | 0.00 | 0.481009E+10 | 0.00 | 0.194363E+12 | 0.00 | 0.00 |
October | 0.151903E+12 | 0.00 | 0.808086E+11 | 0.00 | 0.210745E+12 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.128326E+12 | 0.00 | 0.215892E+12 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.144007E+12 | 0.00 | 0.234518E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178884E+13 | 0.00 | 0.864871E+12 | 0.00 | 0.258745E+13 | 0.00 | 0.00 |
Minimum of Months | 0.137204E+12 | 0.00 | 7755512.91 | 0.00 | 0.194363E+12 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.144007E+12 | 0.00 | 0.242069E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 64632.59 | 02-JAN-20:10 | 12338.45 | 01-JAN-00:10 | 89171.45 | 02-JAN-07:10 | 49607.07 | 02-JAN-07:19 | 29969.95 | 09-JAN-22:10 | 3261.39 | 03-JAN-09:39 | 0.00 | 01-JAN-00:10 |
February | 64632.59 | 01-FEB-20:10 | 12338.45 | 01-FEB-00:10 | 89171.45 | 01-FEB-07:10 | 49607.07 | 01-FEB-07:19 | 33783.30 | 14-FEB-22:10 | 3276.77 | 09-FEB-10:30 | 0.00 | 01-FEB-00:10 |
March | 64632.59 | 01-MAR-20:10 | 12338.45 | 01-MAR-00:10 | 89171.45 | 01-MAR-07:10 | 49607.07 | 13-MAR-06:19 | 33639.76 | 08-MAR-22:10 | 3251.77 | 12-MAR-08:09 | 0.00 | 01-MAR-00:10 |
April | 64632.59 | 03-APR-19:10 | 12338.45 | 01-APR-00:10 | 89171.45 | 03-APR-06:10 | 49605.49 | 03-APR-06:19 | 38257.41 | 13-APR-21:00 | 3219.40 | 23-APR-05:10 | 0.00 | 01-APR-00:10 |
May | 64632.59 | 01-MAY-19:10 | 12338.45 | 01-MAY-00:10 | 89171.45 | 01-MAY-06:10 | 49606.57 | 22-MAY-06:19 | 41413.56 | 19-MAY-21:00 | 3245.38 | 21-MAY-19:30 | 0.00 | 01-MAY-00:10 |
June | 64632.59 | 01-JUN-19:10 | 12338.45 | 01-JUN-00:10 | 89171.45 | 01-JUN-06:10 | 49605.80 | 08-JUN-06:19 | 50215.51 | 23-JUN-21:10 | 3858.17 | 28-JUN-18:19 | 0.00 | 01-JUN-00:10 |
July | 64632.59 | 03-JUL-19:19 | 12338.45 | 01-JUL-00:10 | 89171.45 | 03-JUL-06:10 | 49605.84 | 28-JUL-06:19 | 52176.78 | 21-JUL-21:10 | 3910.75 | 20-JUL-20:10 | 0.00 | 01-JUL-00:10 |
August | 64632.59 | 01-AUG-19:10 | 12338.45 | 01-AUG-00:10 | 89171.45 | 01-AUG-06:10 | 49605.59 | 23-AUG-06:19 | 50847.82 | 18-AUG-21:10 | 3752.66 | 16-AUG-18:19 | 0.00 | 01-AUG-00:10 |
September | 64632.59 | 01-SEP-19:10 | 12338.45 | 01-SEP-00:10 | 89171.45 | 01-SEP-06:10 | 49607.07 | 08-SEP-06:19 | 47278.46 | 13-SEP-21:00 | 3596.08 | 28-SEP-18:10 | 0.00 | 01-SEP-00:10 |
October | 64632.59 | 02-OCT-19:10 | 12338.45 | 01-OCT-00:10 | 89171.45 | 02-OCT-06:10 | 49607.07 | 02-OCT-06:19 | 46973.01 | 06-OCT-21:00 | 3239.49 | 04-OCT-15:20 | 0.00 | 01-OCT-00:10 |
November | 64632.59 | 01-NOV-19:10 | 12338.45 | 01-NOV-00:10 | 89171.45 | 01-NOV-06:10 | 49607.07 | 01-NOV-06:19 | 36797.52 | 02-NOV-21:10 | 3251.50 | 27-NOV-17:49 | 0.00 | 01-NOV-00:10 |
December | 64632.59 | 01-DEC-20:10 | 12338.45 | 01-DEC-00:10 | 89171.45 | 01-DEC-07:10 | 49607.07 | 01-DEC-07:19 | 30841.58 | 01-DEC-22:10 | 3268.26 | 20-DEC-17:19 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 64632.59 | 12338.45 | 89171.45 | 49605.49 | 29969.95 | 3219.40 | 0.00 | |||||||
Maximum of Months | 64632.59 | 12338.45 | 89171.45 | 49607.07 | 52176.78 | 3910.75 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 24479.96 | 01-JAN-14:09 | 0.00 | 0.00 | 9938.94 | 01-JAN-00:10 | 4751.13 | 06-JAN-19:10 | 0.00 |
February | 59681.54 | 14-FEB-16:10 | 0.00 | 0.00 | 9938.94 | 01-FEB-00:10 | 4751.13 | 16-FEB-07:00 | 0.00 |
March | 60370.93 | 08-MAR-16:10 | 0.00 | 0.00 | 9938.94 | 01-MAR-00:10 | 4751.13 | 22-MAR-06:00 | 0.00 |
April | 80291.22 | 13-APR-18:10 | 0.00 | 0.00 | 9938.94 | 12-APR-16:30 | 4751.13 | 06-APR-06:49 | 0.00 |
May | 97526.11 | 19-MAY-18:10 | 0.00 | 0.00 | 9938.94 | 01-MAY-21:19 | 4751.13 | 01-MAY-06:40 | 0.00 |
June | 132076.40 | 29-JUN-15:09 | 0.00 | 0.00 | 9938.94 | 14-JUN-08:30 | 4751.12 | 19-JUN-06:30 | 0.00 |
July | 139778.98 | 20-JUL-18:10 | 0.00 | 0.00 | 9938.94 | 06-JUL-08:09 | 4751.13 | 05-JUL-18:49 | 0.00 |
August | 123859.98 | 20-AUG-18:10 | 0.00 | 0.00 | 9938.94 | 19-AUG-08:50 | 4751.12 | 28-AUG-06:30 | 0.00 |
September | 102539.49 | 20-SEP-15:20 | 0.00 | 0.00 | 9938.94 | 01-SEP-09:39 | 4751.12 | 25-SEP-06:30 | 0.00 |
October | 92745.78 | 06-OCT-15:09 | 0.00 | 0.00 | 9938.94 | 01-OCT-12:20 | 4751.13 | 26-OCT-18:00 | 0.00 |
November | 32642.12 | 02-NOV-15:09 | 0.00 | 0.00 | 9938.94 | 01-NOV-20:19 | 4751.13 | 22-NOV-19:30 | 0.00 |
December | 17430.68 | 31-DEC-16:10 | 0.00 | 0.00 | 9938.94 | 01-DEC-00:10 | 4751.13 | 05-DEC-19:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17430.68 | 0.00 | 0.00 | 9938.94 | 4751.12 | 0.00 | |||
Maximum of Months | 139778.98 | 0.00 | 0.00 | 9938.94 | 4751.13 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 230774.12 | 03-JAN-19:10 | 57474.69 | 77573.37 | 12338.45 | 28159.60 | 26060.62 | 2570.18 | 0.00 | 10123.43 | 0.00 |
February | 231837.85 | 14-FEB-19:10 | 57474.69 | 77573.37 | 12338.45 | 28159.60 | 28157.76 | 2569.35 | 0.00 | 17510.77 | 0.00 |
March | 235733.35 | 13-MAR-18:10 | 57474.69 | 77573.37 | 12338.45 | 28158.42 | 22498.65 | 2545.62 | 0.00 | 28050.60 | 0.00 |
April | 297255.91 | 28-APR-18:49 | 57474.69 | 77573.37 | 12338.45 | 28169.74 | 31357.78 | 2809.27 | 0.00 | 71047.28 | 0.00 |
May | 318953.76 | 19-MAY-19:10 | 64632.59 | 86439.81 | 12338.45 | 10993.88 | 37484.62 | 2890.22 | 0.00 | 88465.52 | 0.00 |
June | 351800.21 | 27-JUN-19:49 | 64632.59 | 86439.81 | 12338.45 | 10999.77 | 41054.61 | 3843.41 | 0.00 | 116744.66 | 0.00 |
July | 366453.59 | 21-JUL-19:19 | 64632.59 | 86439.81 | 12338.45 | 10999.44 | 45669.71 | 3017.96 | 0.00 | 127604.62 | 0.00 |
August | 351838.92 | 18-AUG-18:49 | 57474.69 | 77573.37 | 12338.45 | 28169.74 | 41844.70 | 3348.45 | 0.00 | 114558.71 | 0.00 |
September | 328896.64 | 13-SEP-18:19 | 57474.69 | 77573.37 | 12338.45 | 28169.06 | 36125.03 | 3543.63 | 0.00 | 96596.61 | 0.00 |
October | 304139.01 | 05-OCT-18:10 | 57474.69 | 77573.37 | 12338.45 | 28159.60 | 35046.10 | 2928.71 | 0.00 | 81980.46 | 0.00 |
November | 239779.72 | 02-NOV-18:19 | 57474.69 | 77573.37 | 12338.45 | 28169.74 | 29842.25 | 2611.45 | 0.00 | 24654.69 | 0.00 |
December | 228807.00 | 29-DEC-19:30 | 57474.69 | 77573.37 | 12338.45 | 28169.74 | 27571.04 | 2551.63 | 0.00 | 6648.81 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 228807.00 | 57474.69 | 77573.37 | 12338.45 | 10993.88 | 22498.65 | 2545.62 | 0.00 | 6648.81 | 0.00 | |
Maximum of Months | 366453.59 | 64632.59 | 86439.81 | 12338.45 | 28169.74 | 45669.71 | 3843.41 | 0.00 | 127604.62 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 229719.68 | 10-JAN-11:50 | 0.00 | 251595.19 | 31-JAN-21:30 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 232007.61 | 06-FEB-11:50 | 0.00 | 251615.12 | 07-FEB-21:49 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 219061.62 | 10-MAR-08:20 | 0.00 | 249319.44 | 02-MAR-21:00 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 215834.31 | 23-APR-05:10 | 0.00 | 240340.68 | 03-APR-20:49 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 196452.24 | 07-MAY-04:00 | 0.00 | 229971.54 | 01-MAY-20:30 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 142313.92 | 09-JUN-04:00 | 0.00 | 217940.70 | 01-JUN-20:00 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 1408.33 | 26-JUL-08:00 | 0.00 | 207554.57 | 05-JUL-20:49 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 20136.17 | 31-AUG-05:00 | 0.00 | 205507.48 | 31-AUG-20:40 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 83572.16 | 09-SEP-05:00 | 0.00 | 213136.52 | 28-SEP-20:40 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 208070.28 | 24-OCT-14:30 | 0.00 | 223966.69 | 31-OCT-20:30 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 220188.87 | 07-NOV-08:20 | 0.00 | 235533.79 | 30-NOV-21:49 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 229980.19 | 09-DEC-11:50 | 0.00 | 245937.87 | 26-DEC-21:40 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 104248.32 | 0.00 | 1408.33 | 0.00 | 205507.48 | 0.00 | |||
Maximum of Months | 104248.32 | 0.00 | 232007.61 | 0.00 | 251615.12 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.85 | 1.33 | 21.85 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.88 | 1.83 | 21.88 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.86 | 1.83 | 21.86 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 22.10 | 8.83 | 22.10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 45.50 | 22.45 | 45.50 | 22.45 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 41.00 | 22.21 | 41.00 | 22.21 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 37.00 | 22.11 | 37.00 | 22.11 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 29.67 | 22.31 | 29.67 | 22.31 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 18.00 | 22.24 | 18.00 | 22.24 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.99 | 1.17 | 21.99 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.89 | 0.17 | 21.89 |
Annual Sum or Average | 0.00 | 0.00 | 186.33 | 22.25 | 186.33 | 22.25 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 45.50 | 22.45 | 45.50 | 22.45 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.79 | 0.50 | 21.79 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.99 | 1.50 | 21.99 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 22.09 | 9.17 | 22.09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 54.50 | 22.55 | 54.50 | 22.55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 50.00 | 22.17 | 50.00 | 22.17 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 38.50 | 22.04 | 38.50 | 22.04 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 22.17 | 22.02 | 22.17 | 22.02 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 21.90 | 7.00 | 21.90 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 183.33 | 22.22 | 183.33 | 22.22 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 54.50 | 22.55 | 54.50 | 22.55 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 21.77 | 2.50 | 21.77 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 21.86 | 11.00 | 21.86 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 34.67 | 21.96 | 34.67 | 21.96 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 23.83 | 21.89 | 23.83 | 21.89 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 16.50 | 21.85 | 16.50 | 21.85 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 21.82 | 11.83 | 21.82 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 21.83 | 3.17 | 21.83 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 103.50 | 21.89 | 103.50 | 21.89 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 34.67 | 21.96 | 34.67 | 21.96 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.75 | 0.67 | 21.75 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 21.82 | 2.50 | 21.82 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 21.90 | 4.83 | 21.90 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 21.91 | 6.67 | 21.91 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 22.00 | 12.33 | 22.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 44.00 | 22.12 | 44.00 | 22.12 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 36.17 | 21.98 | 36.17 | 21.98 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 31.83 | 21.95 | 31.83 | 21.95 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 33.50 | 22.16 | 33.50 | 22.16 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 18.00 | 22.03 | 18.00 | 22.03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 21.90 | 4.00 | 21.90 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.71 | 0.17 | 21.71 |
Annual Sum or Average | 0.00 | 0.00 | 194.67 | 22.03 | 194.67 | 22.03 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.71 | 0.17 | 21.71 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 44.00 | 22.16 | 44.00 | 22.16 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.68 | 0.17 | 21.68 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.78 | 1.33 | 21.78 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 21.99 | 6.33 | 21.99 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 16.83 | 22.25 | 16.83 | 22.25 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 51.83 | 22.56 | 51.83 | 22.56 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 52.83 | 22.50 | 52.83 | 22.50 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 43.67 | 22.43 | 43.67 | 22.43 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 23.83 | 22.34 | 23.83 | 22.34 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 21.94 | 6.00 | 21.94 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.68 | 0.17 | 21.68 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 203.00 | 22.42 | 203.00 | 22.42 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 52.83 | 22.56 | 52.83 | 22.56 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.90 | 1.67 | 21.90 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 21.88 | 2.33 | 21.88 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 21.84 | 4.17 | 21.84 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 14.33 | 22.07 | 14.33 | 22.07 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 56.33 | 22.66 | 56.33 | 22.66 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 48.33 | 22.33 | 48.33 | 22.33 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 42.00 | 22.26 | 42.00 | 22.26 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 32.50 | 22.39 | 32.50 | 22.39 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 19.83 | 22.29 | 19.83 | 22.29 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.90 | 1.33 | 21.90 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.96 | 0.17 | 21.96 |
Annual Sum or Average | 0.00 | 0.00 | 223.00 | 22.37 | 223.00 | 22.37 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 56.33 | 22.66 | 56.33 | 22.66 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.94 | 0.33 | 21.94 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 21.98 | 2.83 | 21.98 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 15.67 | 22.03 | 15.67 | 22.03 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 63.83 | 22.74 | 63.83 | 22.74 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 54.33 | 22.37 | 54.33 | 22.37 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 43.83 | 22.18 | 43.83 | 22.18 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 24.50 | 22.08 | 24.50 | 22.08 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 21.93 | 7.50 | 21.93 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 212.83 | 22.36 | 212.83 | 22.36 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 63.83 | 22.74 | 63.83 | 22.74 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 24.67 | 22.67 | 24.67 | 22.67 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 18.17 | 22.41 | 18.17 | 22.41 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 22.10 | 7.83 | 22.10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 21.89 | 4.67 | 21.89 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 21.84 | 4.50 | 21.84 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 21.94 | 11.67 | 21.94 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 21.93 | 13.00 | 21.93 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 18.67 | 21.98 | 18.67 | 21.98 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 32.83 | 22.46 | 32.83 | 22.46 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 43.83 | 22.77 | 43.83 | 22.77 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 36.17 | 22.34 | 36.17 | 22.34 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 19.17 | 22.63 | 19.17 | 22.63 |
Annual Sum or Average | 0.00 | 0.00 | 235.17 | 22.40 | 235.17 | 22.40 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 21.84 | 4.50 | 21.84 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 43.83 | 22.77 | 43.83 | 22.77 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 705.83 | 23.89 | 0.00 | 23.89 | 0.00 | 23.89 |
February | 657.50 | 23.71 | 0.00 | 23.71 | 0.00 | 23.71 |
March | 742.67 | 23.45 | 0.00 | 23.45 | 0.00 | 23.45 |
April | 720.00 | 23.41 | 0.00 | 23.41 | 0.00 | 23.41 |
May | 690.67 | 23.46 | 5.00 | 23.46 | 0.00 | 23.46 |
June | 456.50 | 23.57 | 61.83 | 23.61 | 20.67 | 23.62 |
July | 309.33 | 23.84 | 489.17 | 23.88 | 275.00 | 23.88 |
August | 183.17 | 23.93 | 491.50 | 23.93 | 170.33 | 23.94 |
September | 78.33 | 23.91 | 264.83 | 23.96 | 49.17 | 23.96 |
October | 403.33 | 23.97 | 59.00 | 23.97 | 0.00 | 23.97 |
November | 537.17 | 23.98 | 0.00 | 23.98 | 0.00 | 23.98 |
December | 670.50 | 23.97 | 0.00 | 23.97 | 0.00 | 23.97 |
Annual Sum or Average | 6155.00 | 23.71 | 1371.33 | 23.75 | 515.17 | 23.76 |
Minimum of Months | 78.33 | 23.41 | 0.00 | 23.41 | 0.00 | 23.41 |
Maximum of Months | 742.67 | 23.98 | 491.50 | 23.98 | 275.00 | 23.98 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 596.33 | 21.61 | 123.00 | 21.81 | 49.17 | 21.76 |
February | 519.17 | 21.75 | 71.67 | 21.97 | 11.33 | 21.95 |
March | 610.00 | 21.92 | 45.67 | 22.05 | 3.17 | 22.05 |
April | 541.83 | 22.39 | 11.17 | 22.42 | 0.00 | 22.42 |
May | 528.67 | 22.47 | 39.83 | 22.56 | 2.67 | 22.56 |
June | 303.67 | 22.75 | 252.00 | 23.28 | 15.83 | 23.28 |
July | 227.67 | 23.47 | 663.33 | 23.69 | 217.33 | 23.65 |
August | 184.67 | 23.41 | 613.67 | 23.74 | 140.33 | 23.71 |
September | 223.50 | 22.92 | 432.83 | 23.55 | 45.33 | 23.53 |
October | 385.00 | 22.38 | 225.83 | 22.95 | 5.00 | 22.93 |
November | 530.17 | 22.01 | 96.50 | 22.32 | 0.00 | 22.32 |
December | 574.50 | 21.61 | 118.17 | 21.79 | 51.50 | 21.74 |
Annual Sum or Average | 5225.17 | 22.19 | 2693.67 | 22.72 | 541.67 | 22.73 |
Minimum of Months | 184.67 | 21.61 | 11.17 | 21.79 | 0.00 | 21.74 |
Maximum of Months | 610.00 | 23.47 | 663.33 | 23.74 | 217.33 | 23.71 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 742.00 | 23.02 | 0.00 | 23.02 | 0.00 | 23.02 |
February | 662.67 | 23.16 | 0.00 | 23.16 | 0.00 | 23.16 |
March | 714.00 | 23.32 | 0.00 | 23.32 | 0.00 | 23.32 |
April | 653.33 | 23.56 | 0.00 | 23.56 | 0.00 | 23.56 |
May | 453.33 | 23.53 | 63.67 | 23.58 | 1.50 | 23.58 |
June | 132.33 | 23.55 | 236.17 | 23.82 | 24.50 | 23.83 |
July | 303.67 | 23.94 | 711.33 | 23.94 | 303.67 | 23.94 |
August | 198.33 | 23.95 | 712.67 | 23.95 | 198.33 | 23.95 |
September | 74.33 | 23.87 | 451.33 | 23.94 | 67.17 | 23.94 |
October | 406.67 | 23.51 | 107.83 | 23.60 | 2.00 | 23.61 |
November | 667.83 | 23.38 | 0.00 | 23.38 | 0.00 | 23.38 |
December | 744.00 | 23.05 | 0.00 | 23.05 | 0.00 | 23.05 |
Annual Sum or Average | 5752.50 | 23.36 | 2283.00 | 23.53 | 597.17 | 23.55 |
Minimum of Months | 74.33 | 23.02 | 0.00 | 23.02 | 0.00 | 23.02 |
Maximum of Months | 744.00 | 23.95 | 712.67 | 23.95 | 303.67 | 23.95 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.58 | 0.00 | 21.58 | 0.00 | 21.58 |
February | 672.00 | 21.76 | 8.17 | 21.75 | 8.17 | 21.74 |
March | 744.00 | 22.27 | 0.00 | 22.27 | 0.00 | 22.27 |
April | 720.00 | 22.88 | 0.00 | 22.88 | 0.00 | 22.88 |
May | 702.33 | 23.33 | 0.33 | 23.33 | 0.00 | 23.33 |
June | 364.50 | 23.70 | 79.17 | 23.75 | 5.00 | 23.75 |
July | 132.00 | 23.97 | 605.00 | 23.97 | 132.00 | 23.97 |
August | 82.33 | 23.91 | 468.83 | 23.94 | 81.50 | 23.94 |
September | 337.33 | 23.62 | 96.33 | 23.68 | 30.50 | 23.68 |
October | 660.00 | 22.92 | 6.67 | 22.93 | 0.00 | 22.93 |
November | 720.00 | 22.21 | 0.00 | 22.21 | 0.00 | 22.21 |
December | 744.00 | 21.51 | 3.67 | 21.51 | 3.67 | 21.51 |
Annual Sum or Average | 6622.50 | 22.49 | 1268.17 | 22.73 | 260.83 | 22.76 |
Minimum of Months | 82.33 | 21.51 | 0.00 | 21.51 | 0.00 | 21.51 |
Maximum of Months | 744.00 | 23.97 | 605.00 | 23.97 | 132.00 | 23.97 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.27 | 8.17 | 21.26 | 8.17 | 21.26 |
February | 672.00 | 21.43 | 13.83 | 21.42 | 13.83 | 21.41 |
March | 744.00 | 21.92 | 0.00 | 21.92 | 0.00 | 21.92 |
April | 720.00 | 22.55 | 0.00 | 22.55 | 0.00 | 22.55 |
May | 740.00 | 23.06 | 0.00 | 23.06 | 0.00 | 23.06 |
June | 440.17 | 23.51 | 56.83 | 23.57 | 6.33 | 23.57 |
July | 149.33 | 23.87 | 594.17 | 23.91 | 149.33 | 23.91 |
August | 112.83 | 23.72 | 386.17 | 23.85 | 95.00 | 23.83 |
September | 524.00 | 23.45 | 52.50 | 23.47 | 33.33 | 23.47 |
October | 728.83 | 22.68 | 3.67 | 22.69 | 0.00 | 22.69 |
November | 720.00 | 21.85 | 0.00 | 21.85 | 0.00 | 21.85 |
December | 744.00 | 21.20 | 56.00 | 21.19 | 56.00 | 21.18 |
Annual Sum or Average | 7039.17 | 22.27 | 1171.33 | 22.47 | 362.00 | 22.50 |
Minimum of Months | 112.83 | 21.20 | 0.00 | 21.19 | 0.00 | 21.18 |
Maximum of Months | 744.00 | 23.87 | 594.17 | 23.91 | 149.33 | 23.91 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 194.33 | 23.43 | 643.00 | 23.67 | 148.00 | 23.72 |
February | 179.33 | 23.55 | 585.67 | 23.70 | 145.50 | 23.75 |
March | 193.83 | 23.77 | 654.67 | 23.78 | 174.17 | 23.82 |
April | 188.83 | 23.84 | 639.33 | 23.80 | 174.83 | 23.84 |
May | 265.33 | 23.97 | 695.33 | 23.79 | 261.83 | 23.84 |
June | 347.17 | 23.98 | 707.50 | 23.77 | 347.17 | 23.82 |
July | 535.00 | 23.88 | 744.00 | 23.74 | 535.00 | 23.78 |
August | 507.33 | 23.89 | 744.00 | 23.74 | 507.33 | 23.78 |
September | 379.17 | 23.96 | 712.50 | 23.73 | 379.17 | 23.79 |
October | 247.67 | 23.91 | 687.33 | 23.73 | 237.83 | 23.79 |
November | 191.83 | 23.67 | 635.00 | 23.74 | 164.17 | 23.79 |
December | 196.33 | 23.36 | 634.33 | 23.68 | 143.17 | 23.73 |
Annual Sum or Average | 3426.17 | 23.82 | 8082.67 | 23.74 | 3218.17 | 23.79 |
Minimum of Months | 179.33 | 23.36 | 585.67 | 23.67 | 143.17 | 23.72 |
Maximum of Months | 535.00 | 23.98 | 744.00 | 23.80 | 535.00 | 23.84 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 439.83 | 22.98 | 140.83 | 23.23 | 0.00 | 23.23 |
February | 333.00 | 23.10 | 145.17 | 23.37 | 0.00 | 23.37 |
March | 352.67 | 23.14 | 120.50 | 23.36 | 0.00 | 23.36 |
April | 253.67 | 23.34 | 130.17 | 23.56 | 0.00 | 23.56 |
May | 217.00 | 23.24 | 291.83 | 23.63 | 27.00 | 23.63 |
June | 92.67 | 23.54 | 530.83 | 23.85 | 60.33 | 23.85 |
July | 434.00 | 23.93 | 744.00 | 23.93 | 434.00 | 23.93 |
August | 324.67 | 23.92 | 744.00 | 23.93 | 324.67 | 23.93 |
September | 133.50 | 23.85 | 675.33 | 23.94 | 128.33 | 23.93 |
October | 152.00 | 23.21 | 395.17 | 23.77 | 19.67 | 23.77 |
November | 245.67 | 23.13 | 191.33 | 23.51 | 0.00 | 23.51 |
December | 433.67 | 23.08 | 158.33 | 23.33 | 0.00 | 23.33 |
Annual Sum or Average | 3412.33 | 23.35 | 4267.50 | 23.68 | 994.00 | 23.71 |
Minimum of Months | 92.67 | 22.98 | 120.50 | 23.23 | 0.00 | 23.23 |
Maximum of Months | 439.83 | 23.93 | 744.00 | 23.94 | 434.00 | 23.93 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 511.33 | 23.44 | 0.00 | 23.44 | 0.00 | 23.44 |
February | 365.50 | 23.45 | 0.00 | 23.45 | 0.00 | 23.45 |
March | 412.50 | 23.51 | 0.00 | 23.51 | 0.00 | 23.51 |
April | 423.83 | 23.63 | 2.67 | 23.64 | 0.00 | 23.64 |
May | 263.33 | 23.53 | 149.67 | 23.68 | 8.50 | 23.68 |
June | 87.33 | 23.67 | 379.50 | 23.89 | 44.67 | 23.90 |
July | 399.17 | 23.94 | 737.33 | 23.93 | 399.17 | 23.94 |
August | 298.00 | 23.95 | 742.83 | 23.95 | 298.00 | 23.95 |
September | 109.50 | 23.94 | 616.67 | 23.96 | 109.00 | 23.96 |
October | 137.33 | 23.55 | 204.83 | 23.81 | 13.17 | 23.82 |
November | 269.83 | 23.57 | 9.83 | 23.58 | 0.00 | 23.58 |
December | 555.83 | 23.55 | 0.00 | 23.55 | 0.00 | 23.55 |
Annual Sum or Average | 3833.50 | 23.62 | 2843.33 | 23.76 | 872.50 | 23.78 |
Minimum of Months | 87.33 | 23.44 | 0.00 | 23.44 | 0.00 | 23.44 |
Maximum of Months | 555.83 | 23.95 | 742.83 | 23.96 | 399.17 | 23.96 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 729.83 | 21.36 | 107.50 | 21.29 | 107.50 | 21.23 |
February | 650.83 | 21.43 | 47.67 | 21.40 | 47.67 | 21.37 |
March | 723.50 | 21.52 | 4.50 | 21.52 | 4.50 | 21.52 |
April | 690.33 | 21.61 | 0.00 | 21.61 | 0.00 | 21.61 |
May | 683.67 | 21.57 | 11.83 | 21.60 | 2.17 | 21.60 |
June | 570.00 | 21.46 | 72.83 | 21.66 | 1.00 | 21.66 |
July | 540.67 | 21.32 | 128.33 | 21.67 | 7.83 | 21.68 |
August | 540.17 | 21.29 | 131.50 | 21.66 | 4.50 | 21.67 |
September | 542.00 | 21.32 | 108.00 | 21.63 | 5.33 | 21.63 |
October | 649.83 | 21.47 | 44.67 | 21.55 | 9.33 | 21.54 |
November | 690.00 | 21.50 | 6.33 | 21.50 | 4.17 | 21.50 |
December | 737.00 | 21.38 | 163.17 | 21.29 | 163.17 | 21.23 |
Annual Sum or Average | 7747.83 | 21.44 | 826.33 | 21.52 | 357.17 | 21.50 |
Minimum of Months | 540.17 | 21.29 | 0.00 | 21.29 | 0.00 | 21.23 |
Maximum of Months | 737.00 | 21.61 | 163.17 | 21.67 | 163.17 | 21.68 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.01 | 325.50 | 20.93 | 325.50 | 20.88 |
February | 668.50 | 21.18 | 140.67 | 21.10 | 140.67 | 21.04 |
March | 719.33 | 21.47 | 27.00 | 21.52 | 15.17 | 21.51 |
April | 662.33 | 21.86 | 27.67 | 22.04 | 2.17 | 22.06 |
May | 647.33 | 21.89 | 33.33 | 22.05 | 7.00 | 22.08 |
June | 498.50 | 21.67 | 127.17 | 22.13 | 5.50 | 22.17 |
July | 491.83 | 21.75 | 235.00 | 22.35 | 77.17 | 22.51 |
August | 491.50 | 21.72 | 217.67 | 22.33 | 58.33 | 22.45 |
September | 497.83 | 21.73 | 114.00 | 22.09 | 16.00 | 22.12 |
October | 642.50 | 21.64 | 61.83 | 21.83 | 19.83 | 21.82 |
November | 717.00 | 21.29 | 46.17 | 21.27 | 45.00 | 21.25 |
December | 744.00 | 20.95 | 440.00 | 20.87 | 440.00 | 20.83 |
Annual Sum or Average | 7524.67 | 21.48 | 1796.00 | 21.62 | 1152.33 | 21.57 |
Minimum of Months | 491.50 | 20.95 | 27.00 | 20.87 | 2.17 | 20.83 |
Maximum of Months | 744.00 | 21.89 | 440.00 | 22.35 | 440.00 | 22.51 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.06 | 63.33 | 21.02 | 63.33 | 20.99 |
February | 672.00 | 21.15 | 36.83 | 21.12 | 36.83 | 21.10 |
March | 744.00 | 21.37 | 0.33 | 21.37 | 0.33 | 21.37 |
April | 720.00 | 21.75 | 0.00 | 21.75 | 0.00 | 21.75 |
May | 743.33 | 21.92 | 0.00 | 21.92 | 0.00 | 21.92 |
June | 706.00 | 22.02 | 0.83 | 22.02 | 0.17 | 22.02 |
July | 719.67 | 22.05 | 51.50 | 22.14 | 50.00 | 22.22 |
August | 722.17 | 22.04 | 38.33 | 22.11 | 31.50 | 22.15 |
September | 717.67 | 22.07 | 5.00 | 22.07 | 5.00 | 22.07 |
October | 743.67 | 21.63 | 0.83 | 21.64 | 0.83 | 21.64 |
November | 720.00 | 21.21 | 9.00 | 21.20 | 9.00 | 21.19 |
December | 744.00 | 21.01 | 195.17 | 20.95 | 195.17 | 20.91 |
Annual Sum or Average | 8696.50 | 21.60 | 401.17 | 21.59 | 392.17 | 21.58 |
Minimum of Months | 672.00 | 21.01 | 0.00 | 20.95 | 0.00 | 20.91 |
Maximum of Months | 744.00 | 22.07 | 195.17 | 22.14 | 195.17 | 22.22 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.44 | 121.00 | 21.35 | 121.00 | 21.29 |
February | 671.33 | 21.55 | 49.67 | 21.51 | 49.67 | 21.47 |
March | 737.50 | 21.64 | 5.50 | 21.63 | 5.50 | 21.63 |
April | 693.50 | 21.69 | 0.00 | 21.69 | 0.00 | 21.69 |
May | 659.33 | 21.56 | 5.83 | 21.58 | 0.00 | 21.58 |
June | 529.67 | 21.33 | 76.17 | 21.58 | 0.50 | 21.58 |
July | 510.67 | 21.19 | 179.50 | 21.73 | 2.50 | 21.74 |
August | 515.83 | 21.19 | 168.00 | 21.71 | 0.17 | 21.71 |
September | 525.50 | 21.28 | 114.83 | 21.64 | 2.00 | 21.64 |
October | 642.17 | 21.47 | 46.33 | 21.57 | 8.00 | 21.56 |
November | 713.50 | 21.60 | 4.67 | 21.60 | 4.67 | 21.60 |
December | 744.00 | 21.46 | 164.83 | 21.37 | 164.83 | 21.30 |
Annual Sum or Average | 7687.00 | 21.47 | 936.33 | 21.57 | 358.83 | 21.54 |
Minimum of Months | 510.67 | 21.19 | 0.00 | 21.35 | 0.00 | 21.29 |
Maximum of Months | 744.00 | 21.69 | 179.50 | 21.73 | 164.83 | 21.74 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.01 | 321.83 | 20.95 | 321.83 | 20.92 |
February | 672.00 | 21.19 | 150.83 | 21.13 | 150.83 | 21.09 |
March | 743.83 | 21.64 | 11.50 | 21.63 | 11.50 | 21.62 |
April | 703.83 | 22.04 | 2.17 | 22.05 | 0.00 | 22.05 |
May | 625.83 | 21.94 | 40.83 | 22.13 | 5.83 | 22.17 |
June | 473.00 | 21.89 | 171.83 | 22.60 | 35.33 | 22.86 |
July | 492.50 | 22.08 | 303.00 | 22.87 | 89.00 | 23.16 |
August | 473.33 | 21.98 | 288.50 | 22.82 | 74.83 | 23.09 |
September | 462.83 | 21.73 | 105.00 | 22.22 | 21.17 | 22.31 |
October | 686.17 | 21.82 | 23.17 | 21.85 | 16.33 | 21.85 |
November | 719.83 | 21.30 | 53.00 | 21.28 | 53.00 | 21.26 |
December | 744.00 | 20.92 | 473.83 | 20.88 | 473.83 | 20.86 |
Annual Sum or Average | 7541.17 | 21.58 | 1945.50 | 21.77 | 1253.50 | 21.77 |
Minimum of Months | 462.83 | 20.92 | 2.17 | 20.88 | 0.00 | 20.86 |
Maximum of Months | 744.00 | 22.08 | 473.83 | 22.87 | 473.83 | 23.16 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.60 | 0.00 | 21.60 | 0.00 | 21.60 |
February | 672.00 | 21.73 | 0.00 | 21.73 | 0.00 | 21.73 |
March | 744.00 | 22.21 | 0.00 | 22.21 | 0.00 | 22.21 |
April | 720.00 | 22.86 | 0.00 | 22.86 | 0.00 | 22.86 |
May | 734.00 | 23.20 | 0.00 | 23.20 | 0.00 | 23.20 |
June | 471.00 | 23.55 | 75.33 | 23.60 | 28.67 | 23.60 |
July | 335.00 | 23.89 | 615.00 | 23.91 | 334.67 | 23.91 |
August | 229.17 | 23.89 | 515.00 | 23.91 | 229.17 | 23.91 |
September | 283.33 | 23.68 | 146.33 | 23.72 | 74.33 | 23.71 |
October | 605.17 | 23.05 | 16.83 | 23.08 | 3.17 | 23.08 |
November | 720.00 | 22.25 | 0.00 | 22.25 | 0.00 | 22.25 |
December | 744.00 | 21.48 | 8.33 | 21.47 | 8.33 | 21.47 |
Annual Sum or Average | 7001.67 | 22.55 | 1376.83 | 22.77 | 678.33 | 22.85 |
Minimum of Months | 229.17 | 21.48 | 0.00 | 21.47 | 0.00 | 21.47 |
Maximum of Months | 744.00 | 23.89 | 615.00 | 23.91 | 334.67 | 23.91 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 726.83 | 21.26 | 289.33 | 21.15 | 289.33 | 21.09 |
February | 644.67 | 21.35 | 136.33 | 21.27 | 135.17 | 21.21 |
March | 717.33 | 21.45 | 45.33 | 21.43 | 44.17 | 21.40 |
April | 676.33 | 21.55 | 11.50 | 21.55 | 11.33 | 21.54 |
May | 661.50 | 21.50 | 33.83 | 21.57 | 9.33 | 21.57 |
June | 539.50 | 21.39 | 117.33 | 21.70 | 8.50 | 21.70 |
July | 523.17 | 21.28 | 196.50 | 21.74 | 28.17 | 21.73 |
August | 526.67 | 21.27 | 192.83 | 21.73 | 22.83 | 21.73 |
September | 532.50 | 21.29 | 159.33 | 21.66 | 27.17 | 21.65 |
October | 641.00 | 21.41 | 83.17 | 21.50 | 35.17 | 21.46 |
November | 685.00 | 21.42 | 88.33 | 21.37 | 85.67 | 21.33 |
December | 735.33 | 21.29 | 334.00 | 21.16 | 334.00 | 21.10 |
Annual Sum or Average | 7609.83 | 21.38 | 1687.83 | 21.46 | 1030.83 | 21.41 |
Minimum of Months | 523.17 | 21.26 | 11.50 | 21.15 | 8.50 | 21.09 |
Maximum of Months | 735.33 | 21.55 | 334.00 | 21.74 | 334.00 | 21.73 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.89 | 572.17 | 20.83 | 572.17 | 20.80 |
February | 667.33 | 21.08 | 300.67 | 20.98 | 299.83 | 20.93 |
March | 712.00 | 21.38 | 122.33 | 21.42 | 104.83 | 21.36 |
April | 638.17 | 21.81 | 56.33 | 22.06 | 23.83 | 22.10 |
May | 630.83 | 21.86 | 58.00 | 22.09 | 17.83 | 22.15 |
June | 475.67 | 21.63 | 173.17 | 22.20 | 12.67 | 22.25 |
July | 490.17 | 21.75 | 293.83 | 22.37 | 90.33 | 22.51 |
August | 482.67 | 21.69 | 267.83 | 22.33 | 69.33 | 22.44 |
September | 485.50 | 21.66 | 152.50 | 22.06 | 32.67 | 22.07 |
October | 632.00 | 21.55 | 130.00 | 21.74 | 77.50 | 21.67 |
November | 716.67 | 21.17 | 241.17 | 21.10 | 239.83 | 21.06 |
December | 744.00 | 20.83 | 609.17 | 20.77 | 609.17 | 20.75 |
Annual Sum or Average | 7419.00 | 21.40 | 2977.17 | 21.53 | 2150.00 | 21.45 |
Minimum of Months | 475.67 | 20.83 | 56.33 | 20.77 | 12.67 | 20.75 |
Maximum of Months | 744.00 | 21.86 | 609.17 | 22.37 | 609.17 | 22.51 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 651.00 | 21.39 | 88.67 | 21.47 | 45.50 | 21.43 |
February | 578.50 | 21.40 | 48.00 | 21.50 | 14.17 | 21.49 |
March | 667.33 | 21.46 | 10.00 | 21.48 | 1.67 | 21.48 |
April | 677.83 | 21.59 | 0.00 | 21.59 | 0.00 | 21.59 |
May | 700.33 | 21.58 | 1.67 | 21.58 | 1.67 | 21.59 |
June | 623.67 | 21.49 | 12.67 | 21.52 | 3.83 | 21.52 |
July | 584.50 | 21.33 | 97.67 | 21.57 | 21.83 | 21.58 |
August | 570.50 | 21.30 | 124.50 | 21.64 | 11.17 | 21.64 |
September | 546.33 | 21.31 | 125.33 | 21.67 | 6.00 | 21.67 |
October | 597.17 | 21.39 | 97.33 | 21.66 | 4.83 | 21.65 |
November | 609.33 | 21.44 | 48.83 | 21.58 | 0.00 | 21.58 |
December | 631.00 | 21.32 | 67.67 | 21.38 | 41.50 | 21.35 |
Annual Sum or Average | 7437.50 | 21.42 | 722.33 | 21.55 | 152.17 | 21.55 |
Minimum of Months | 546.33 | 21.30 | 0.00 | 21.38 | 0.00 | 21.35 |
Maximum of Months | 700.33 | 21.59 | 125.33 | 21.67 | 45.50 | 21.67 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 361.83 | 23.56 | 0.00 | 23.56 | 0.00 | 23.56 |
February | 224.50 | 23.56 | 1.67 | 23.56 | 0.00 | 23.56 |
March | 102.17 | 23.60 | 31.83 | 23.69 | 0.00 | 23.69 |
April | 36.00 | 23.80 | 52.50 | 23.92 | 0.00 | 23.92 |
May | 24.00 | 23.87 | 380.67 | 23.99 | 9.50 | 23.99 |
June | 46.83 | 24.00 | 666.67 | 24.00 | 46.83 | 24.00 |
July | 416.17 | 24.00 | 744.00 | 24.00 | 416.17 | 24.00 |
August | 310.83 | 24.00 | 744.00 | 24.00 | 310.83 | 24.00 |
September | 112.50 | 23.99 | 718.33 | 23.99 | 112.50 | 23.99 |
October | 64.17 | 23.63 | 289.83 | 23.92 | 18.17 | 23.93 |
November | 210.33 | 23.62 | 35.50 | 23.67 | 0.00 | 23.67 |
December | 464.17 | 23.62 | 0.00 | 23.62 | 0.00 | 23.62 |
Annual Sum or Average | 2373.50 | 23.75 | 3665.00 | 23.90 | 914.00 | 23.91 |
Minimum of Months | 24.00 | 23.56 | 0.00 | 23.56 | 0.00 | 23.56 |
Maximum of Months | 464.17 | 24.00 | 744.00 | 24.00 | 416.17 | 24.00 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 129.83 | 23.54 | 3.00 | 23.55 | 0.00 | 23.55 |
February | 65.33 | 23.60 | 46.17 | 23.76 | 0.00 | 23.76 |
March | 1.67 | 23.63 | 78.83 | 23.99 | 0.00 | 23.99 |
April | 0.00 | 0.00 | 111.50 | 24.00 | 0.00 | 24.00 |
May | 8.33 | 23.98 | 426.83 | 24.00 | 8.00 | 24.00 |
June | 43.33 | 24.00 | 692.83 | 24.00 | 43.33 | 24.00 |
July | 401.33 | 24.00 | 744.00 | 24.00 | 401.33 | 24.00 |
August | 296.00 | 24.00 | 744.00 | 24.00 | 296.00 | 24.00 |
September | 105.83 | 24.00 | 720.00 | 24.00 | 105.83 | 24.00 |
October | 28.17 | 23.80 | 341.50 | 23.98 | 15.17 | 23.98 |
November | 39.67 | 23.63 | 79.50 | 23.87 | 0.00 | 23.87 |
December | 207.50 | 23.64 | 2.67 | 23.64 | 0.00 | 23.64 |
Annual Sum or Average | 1327.00 | 23.86 | 3990.83 | 23.96 | 869.67 | 23.97 |
Minimum of Months | 0.00 | 0.00 | 2.67 | 23.55 | 0.00 | 23.55 |
Maximum of Months | 401.33 | 24.00 | 744.00 | 24.00 | 401.33 | 24.00 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 480.17 | 23.99 | 714.50 | 23.96 | 480.17 | 23.97 |
February | 450.00 | 23.99 | 656.83 | 23.96 | 450.00 | 23.97 |
March | 509.17 | 23.99 | 742.17 | 23.97 | 509.17 | 23.98 |
April | 503.83 | 23.99 | 718.17 | 23.98 | 503.83 | 23.99 |
May | 537.50 | 23.99 | 743.67 | 23.99 | 537.50 | 23.99 |
June | 555.83 | 23.99 | 720.00 | 23.99 | 555.83 | 23.99 |
July | 664.50 | 23.99 | 744.00 | 23.99 | 664.50 | 23.99 |
August | 632.50 | 23.99 | 744.00 | 23.99 | 632.50 | 23.99 |
September | 558.00 | 23.99 | 720.00 | 23.99 | 558.00 | 23.99 |
October | 524.83 | 23.99 | 743.33 | 23.98 | 524.83 | 23.98 |
November | 489.00 | 23.99 | 714.33 | 23.97 | 489.00 | 23.97 |
December | 472.17 | 23.99 | 697.33 | 23.96 | 471.83 | 23.97 |
Annual Sum or Average | 6377.50 | 23.99 | 8658.33 | 23.98 | 6377.17 | 23.98 |
Minimum of Months | 450.00 | 23.99 | 656.83 | 23.96 | 450.00 | 23.97 |
Maximum of Months | 664.50 | 23.99 | 744.00 | 23.99 | 664.50 | 23.99 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.40 | 0.00 | 21.40 | 0.00 | 21.40 |
February | 672.00 | 21.61 | 0.00 | 21.61 | 0.00 | 21.61 |
March | 744.00 | 22.03 | 0.00 | 22.03 | 0.00 | 22.03 |
April | 711.67 | 22.78 | 0.00 | 22.78 | 0.00 | 22.78 |
May | 604.00 | 23.09 | 3.83 | 23.10 | 0.00 | 23.10 |
June | 266.50 | 23.37 | 163.50 | 23.60 | 13.67 | 23.60 |
July | 193.67 | 23.82 | 657.67 | 23.90 | 193.67 | 23.88 |
August | 140.17 | 23.75 | 601.67 | 23.89 | 129.00 | 23.87 |
September | 255.33 | 23.34 | 249.17 | 23.61 | 44.50 | 23.60 |
October | 596.17 | 22.72 | 43.50 | 22.80 | 0.00 | 22.80 |
November | 720.00 | 21.92 | 0.00 | 21.92 | 0.00 | 21.92 |
December | 744.00 | 21.36 | 20.83 | 21.35 | 20.83 | 21.34 |
Annual Sum or Average | 6391.50 | 22.27 | 1740.17 | 22.62 | 401.67 | 22.66 |
Minimum of Months | 140.17 | 21.36 | 0.00 | 21.35 | 0.00 | 21.34 |
Maximum of Months | 744.00 | 23.82 | 657.67 | 23.90 | 193.67 | 23.88 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.89328 | 20.75741 | 0.17837 | 5.73696 |
February | 672.00000 | 23.71895 | 22.28967 | 0.13800 | 5.51685 |
March | 744.00000 | 23.45465 | 21.01264 | 0.06021 | 5.22243 |
April | 720.00000 | 23.41338 | 17.98951 | 0.02984 | 5.16960 |
May | 744.00000 | 23.47988 | 26.53506 | -0.8624 | 20.98362 |
June | 720.00000 | 23.67856 | 36.41579 | -0.7181 | 16.10160 |
July | 744.00000 | 23.82711 | 50.73862 | -0.5572 | 11.65425 |
August | 744.00000 | 23.89445 | 48.77225 | -0.5376 | 11.14247 |
September | 720.00000 | 23.95082 | 40.76314 | -0.5610 | 11.69597 |
October | 744.00000 | 23.97425 | 26.08623 | 0.25572 | 6.46283 |
November | 720.00000 | 23.98462 | 20.26200 | 0.21475 | 6.00033 |
December | 744.00000 | 23.96847 | 18.54333 | 0.19242 | 5.81054 |
Annual Sum or Average | 8760.00000 | 23.77043 | 29.24065 | -0.1823 | 9.31754 |
Minimum of Months | 672.00000 | 23.41338 | 17.98951 | -0.8624 | 5.16960 |
Maximum of Months | 744.00000 | 23.98462 | 50.73862 | 0.25572 | 20.98362 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.07961 | 21.92087 | -0.1923 | 8.42395 |
February | 672.00000 | 22.25958 | 23.00193 | -0.1287 | 7.84575 |
March | 744.00000 | 22.29253 | 21.24734 | -0.1265 | 7.28845 |
April | 720.00000 | 22.77064 | 17.47593 | -0.0220 | 6.53495 |
May | 744.00000 | 22.86586 | 26.39123 | -0.9265 | 25.17940 |
June | 720.00000 | 23.36362 | 35.99525 | -0.6575 | 15.68713 |
July | 744.00000 | 23.71809 | 50.10420 | -0.4068 | 9.09764 |
August | 744.00000 | 23.72914 | 48.42249 | -0.3968 | 9.17002 |
September | 720.00000 | 23.57070 | 41.21055 | -0.4986 | 11.97218 |
October | 744.00000 | 23.12909 | 26.81925 | 0.16721 | 7.89050 |
November | 720.00000 | 22.53244 | 21.54430 | -0.0465 | 7.40879 |
December | 744.00000 | 22.15139 | 19.79723 | -0.1833 | 8.52651 |
Annual Sum or Average | 8760.00000 | 22.87487 | 29.55237 | -0.2859 | 10.44012 |
Minimum of Months | 672.00000 | 22.07961 | 17.47593 | -0.9265 | 6.53495 |
Maximum of Months | 744.00000 | 23.72914 | 50.10420 | 0.16721 | 25.17940 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.02119 | 23.01632 | -0.0062 | 5.32713 |
February | 672.00000 | 23.17132 | 23.98661 | 0.04049 | 5.31425 |
March | 744.00000 | 23.34211 | 22.12549 | 0.07459 | 5.37253 |
April | 720.00000 | 23.60033 | 18.62696 | 0.12488 | 5.54034 |
May | 744.00000 | 23.67819 | 26.94289 | -0.7222 | 16.44877 |
June | 720.00000 | 23.84685 | 36.48516 | -0.5755 | 12.21055 |
July | 744.00000 | 23.93608 | 50.78122 | -0.4330 | 8.98795 |
August | 744.00000 | 23.94017 | 49.20062 | -0.4421 | 9.15198 |
September | 720.00000 | 23.91430 | 41.92619 | -0.5122 | 10.60884 |
October | 744.00000 | 23.70427 | 27.93629 | 0.22204 | 6.41700 |
November | 720.00000 | 23.42234 | 22.65851 | 0.09864 | 5.41398 |
December | 744.00000 | 23.04908 | 21.10416 | -0.0123 | 5.26401 |
Annual Sum or Average | 8760.00000 | 23.55374 | 30.45711 | -0.1800 | 8.02208 |
Minimum of Months | 672.00000 | 23.02119 | 18.62696 | -0.7222 | 5.26401 |
Maximum of Months | 744.00000 | 23.94017 | 50.78122 | 0.22204 | 16.44877 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.50378 | 17.79144 | 0.67739 | 16.38247 |
February | 672.00000 | 23.51855 | 18.90603 | 0.69787 | 16.97077 |
March | 744.00000 | 23.57483 | 17.19812 | 0.72223 | 17.61600 |
April | 720.00000 | 23.61019 | 14.04265 | 0.73486 | 17.94251 |
May | 744.00000 | 23.62780 | 22.59403 | 0.15209 | 8.70880 |
June | 720.00000 | 23.64344 | 32.82686 | 0.26444 | 9.65970 |
July | 744.00000 | 23.64706 | 47.77592 | 0.37961 | 10.96044 |
August | 744.00000 | 23.63100 | 46.23570 | 0.35970 | 10.76865 |
September | 720.00000 | 23.59780 | 38.62184 | 0.27076 | 9.62397 |
October | 744.00000 | 23.54728 | 23.80882 | 0.78416 | 19.65936 |
November | 720.00000 | 23.56055 | 17.80755 | 0.71451 | 17.40281 |
December | 744.00000 | 23.51936 | 15.94386 | 0.66631 | 16.06549 |
Annual Sum or Average | 8760.00000 | 23.58209 | 26.19211 | 0.53442 | 14.29876 |
Minimum of Months | 672.00000 | 23.50378 | 14.04265 | 0.15209 | 8.70880 |
Maximum of Months | 744.00000 | 23.64706 | 47.77592 | 0.78416 | 19.65936 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.38326 | 26.29219 | 0.18682 | 7.06357 |
February | 672.00000 | 23.53355 | 27.19365 | 0.24170 | 7.18631 |
March | 744.00000 | 23.56702 | 25.53323 | 0.23745 | 6.89375 |
April | 720.00000 | 23.73157 | 22.07028 | 0.26936 | 6.93651 |
May | 744.00000 | 23.69442 | 30.55481 | -0.5762 | 12.73616 |
June | 720.00000 | 23.80647 | 40.04055 | -0.4277 | 9.31889 |
July | 744.00000 | 23.92319 | 53.98238 | -0.2473 | 6.47852 |
August | 744.00000 | 23.93001 | 52.20810 | -0.2362 | 6.51558 |
September | 720.00000 | 23.93028 | 44.82227 | -0.2854 | 7.40794 |
October | 744.00000 | 23.81096 | 30.76825 | 0.40203 | 9.31245 |
November | 720.00000 | 23.68507 | 25.71320 | 0.29488 | 7.68468 |
December | 744.00000 | 23.45492 | 24.33555 | 0.19803 | 7.11782 |
Annual Sum or Average | 8760.00000 | 23.70471 | 33.68417 | 0.00330 | 7.89400 |
Minimum of Months | 672.00000 | 23.38326 | 22.07028 | -0.5762 | 6.47852 |
Maximum of Months | 744.00000 | 23.93028 | 53.98238 | 0.40203 | 12.73616 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.60359 | 25.33966 | 0.17122 | 5.90886 |
February | 672.00000 | 23.68648 | 26.27241 | 0.20357 | 6.04585 |
March | 744.00000 | 23.71547 | 24.41622 | 0.20524 | 6.06046 |
April | 720.00000 | 23.77332 | 20.96103 | 0.20922 | 6.04575 |
May | 744.00000 | 23.76568 | 29.20683 | -0.6369 | 13.87329 |
June | 720.00000 | 23.85334 | 38.78243 | -0.5139 | 10.75892 |
July | 744.00000 | 23.92908 | 53.04076 | -0.3721 | 7.95813 |
August | 744.00000 | 23.94705 | 51.39255 | -0.3743 | 7.97964 |
September | 720.00000 | 23.96019 | 43.99360 | -0.4287 | 8.93645 |
October | 744.00000 | 23.89648 | 29.99628 | 0.31787 | 7.35155 |
November | 720.00000 | 23.82490 | 24.80555 | 0.24024 | 6.34121 |
December | 744.00000 | 23.65823 | 23.47239 | 0.17230 | 5.84263 |
Annual Sum or Average | 8760.00000 | 23.80153 | 32.69784 | -0.0688 | 7.76977 |
Minimum of Months | 672.00000 | 23.60359 | 20.96103 | -0.6369 | 5.84263 |
Maximum of Months | 744.00000 | 23.96019 | 53.04076 | 0.31787 | 13.87329 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.39610 | 35.43080 | -0.3945 | 9.36814 |
February | 672.00000 | 21.49289 | 36.43235 | -0.3380 | 8.56154 |
March | 744.00000 | 21.56991 | 33.71790 | -0.2982 | 7.88886 |
April | 720.00000 | 21.68194 | 28.82763 | -0.2383 | 7.37583 |
May | 744.00000 | 21.70883 | 37.04256 | -1.2595 | 39.65406 |
June | 720.00000 | 21.81905 | 45.98166 | -1.0977 | 32.44842 |
July | 744.00000 | 21.80992 | 52.19728 | -1.0342 | 29.55903 |
August | 744.00000 | 21.79500 | 52.20300 | -1.0378 | 29.76105 |
September | 720.00000 | 21.78244 | 49.20925 | -1.0940 | 32.41441 |
October | 744.00000 | 21.68858 | 38.71873 | -0.1689 | 7.07782 |
November | 720.00000 | 21.57461 | 35.76983 | -0.2947 | 7.97243 |
December | 744.00000 | 21.40163 | 33.75828 | -0.4073 | 9.62430 |
Annual Sum or Average | 8760.00000 | 21.64387 | 39.96954 | -0.6406 | 18.53969 |
Minimum of Months | 672.00000 | 21.39610 | 28.82763 | -1.2595 | 7.07782 |
Maximum of Months | 744.00000 | 21.81905 | 52.20300 | -0.1689 | 39.65406 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.01454 | 36.11069 | -0.5387 | 11.52900 |
February | 672.00000 | 21.19674 | 36.87556 | -0.4614 | 10.18150 |
March | 744.00000 | 21.58907 | 33.56080 | -0.3385 | 8.51130 |
April | 720.00000 | 22.12437 | 28.42434 | -0.1756 | 7.66470 |
May | 744.00000 | 22.17381 | 36.31088 | -1.1405 | 35.05727 |
June | 720.00000 | 22.27229 | 45.30195 | -0.9691 | 27.81363 |
July | 744.00000 | 22.27327 | 52.52918 | -0.9032 | 24.82763 |
August | 744.00000 | 22.30284 | 51.97506 | -0.9113 | 25.19214 |
September | 720.00000 | 22.31623 | 48.38297 | -0.9899 | 28.03017 |
October | 744.00000 | 22.00754 | 38.27962 | -0.1596 | 7.63429 |
November | 720.00000 | 21.29776 | 36.07181 | -0.4197 | 9.27717 |
December | 744.00000 | 20.95338 | 34.61154 | -0.5716 | 12.30871 |
Annual Sum or Average | 8760.00000 | 21.79610 | 39.89770 | -0.6329 | 17.38499 |
Minimum of Months | 672.00000 | 20.95338 | 28.42434 | -1.1405 | 7.63429 |
Maximum of Months | 744.00000 | 22.31623 | 52.52918 | -0.1596 | 35.05727 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.06059 | 33.12967 | -0.5204 | 10.69866 |
February | 672.00000 | 21.14661 | 34.05856 | -0.4811 | 9.91449 |
March | 744.00000 | 21.36691 | 30.74261 | -0.4173 | 8.75787 |
April | 720.00000 | 21.75294 | 25.59210 | -0.3290 | 7.77807 |
May | 744.00000 | 21.92649 | 33.66333 | -1.3276 | 42.42915 |
June | 720.00000 | 22.05957 | 43.81243 | -1.1783 | 35.32178 |
July | 744.00000 | 22.11156 | 53.59678 | -1.0907 | 31.53378 |
August | 744.00000 | 22.09599 | 53.23725 | -1.1107 | 32.31179 |
September | 720.00000 | 22.07132 | 47.39959 | -1.1901 | 35.76374 |
October | 744.00000 | 21.63462 | 36.03647 | -0.3035 | 7.57226 |
November | 720.00000 | 21.20628 | 33.21245 | -0.4590 | 9.49091 |
December | 744.00000 | 21.00665 | 31.62053 | -0.5470 | 11.34029 |
Annual Sum or Average | 8760.00000 | 21.62218 | 38.04647 | -0.7479 | 20.30739 |
Minimum of Months | 672.00000 | 21.00665 | 25.59210 | -1.3276 | 7.57226 |
Maximum of Months | 744.00000 | 22.11156 | 53.59678 | -0.3035 | 42.42915 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.43919 | 35.44532 | -0.3859 | 9.26165 |
February | 672.00000 | 21.54712 | 36.37830 | -0.3308 | 8.47020 |
March | 744.00000 | 21.65104 | 33.64801 | -0.2711 | 7.74115 |
April | 720.00000 | 21.75074 | 28.81938 | -0.2045 | 7.27055 |
May | 744.00000 | 21.76235 | 36.83342 | -1.2188 | 37.86764 |
June | 720.00000 | 21.82603 | 45.84532 | -1.0712 | 31.25788 |
July | 744.00000 | 21.81098 | 52.09549 | -1.0068 | 28.48373 |
August | 744.00000 | 21.80319 | 52.22134 | -1.0141 | 28.85401 |
September | 720.00000 | 21.80343 | 49.00820 | -1.0794 | 31.76989 |
October | 744.00000 | 21.72324 | 38.68131 | -0.1580 | 7.05554 |
November | 720.00000 | 21.62019 | 35.74640 | -0.2838 | 7.88146 |
December | 744.00000 | 21.46329 | 33.75321 | -0.3954 | 9.40120 |
Annual Sum or Average | 8760.00000 | 21.68379 | 39.90190 | -0.6202 | 18.00321 |
Minimum of Months | 672.00000 | 21.43919 | 28.81938 | -1.2188 | 7.05554 |
Maximum of Months | 744.00000 | 21.82603 | 52.22134 | -0.1580 | 37.86764 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.00827 | 36.05868 | -0.5407 | 11.43336 |
February | 672.00000 | 21.19069 | 36.83579 | -0.4675 | 10.03870 |
March | 744.00000 | 21.64091 | 33.47527 | -0.3173 | 7.95882 |
April | 720.00000 | 22.08356 | 28.33621 | -0.1648 | 6.99448 |
May | 744.00000 | 22.23883 | 36.05198 | -1.0966 | 33.28014 |
June | 720.00000 | 22.48026 | 44.95928 | -0.8828 | 27.00364 |
July | 744.00000 | 22.53756 | 51.27123 | -0.8013 | 24.34971 |
August | 744.00000 | 22.55995 | 51.09358 | -0.8162 | 24.51509 |
September | 720.00000 | 22.44805 | 48.20123 | -0.9411 | 27.11838 |
October | 744.00000 | 21.95635 | 38.26603 | -0.1658 | 7.13627 |
November | 720.00000 | 21.29893 | 36.07155 | -0.4176 | 9.09958 |
December | 744.00000 | 20.91823 | 34.55019 | -0.5791 | 12.30088 |
Annual Sum or Average | 8760.00000 | 21.86665 | 39.62254 | -0.6003 | 16.81581 |
Minimum of Months | 672.00000 | 20.91823 | 28.33621 | -1.0966 | 6.99448 |
Maximum of Months | 744.00000 | 22.55995 | 51.27123 | -0.1648 | 33.28014 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.31137 | 36.12447 | -0.4468 | 10.50536 |
February | 672.00000 | 21.42967 | 37.13873 | -0.3792 | 9.45795 |
March | 744.00000 | 21.51829 | 34.26690 | -0.3323 | 8.57844 |
April | 720.00000 | 21.66033 | 29.05673 | -0.2544 | 7.81242 |
May | 744.00000 | 21.69753 | 37.34824 | -1.2705 | 40.51943 |
June | 720.00000 | 21.83910 | 46.27374 | -1.0843 | 32.42716 |
July | 744.00000 | 21.82554 | 52.94607 | -1.0155 | 29.23837 |
August | 744.00000 | 21.80386 | 52.95726 | -1.0250 | 29.67120 |
September | 720.00000 | 21.77631 | 50.06042 | -1.0998 | 33.11694 |
October | 744.00000 | 21.65278 | 39.30851 | -0.1946 | 7.63057 |
November | 720.00000 | 21.51276 | 36.40981 | -0.3386 | 8.77278 |
December | 744.00000 | 21.31545 | 34.34875 | -0.4605 | 10.82492 |
Annual Sum or Average | 8760.00000 | 21.61248 | 40.54852 | -0.6604 | 19.10882 |
Minimum of Months | 672.00000 | 21.31137 | 29.05673 | -1.2705 | 7.63057 |
Maximum of Months | 744.00000 | 21.83910 | 52.95726 | -0.1946 | 40.51943 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.89102 | 36.95925 | -0.6029 | 13.15060 |
February | 672.00000 | 21.10796 | 37.67740 | -0.5122 | 11.41056 |
March | 744.00000 | 21.54878 | 34.22383 | -0.3714 | 9.37548 |
April | 720.00000 | 22.16003 | 28.77750 | -0.1761 | 8.30385 |
May | 744.00000 | 22.18255 | 36.67444 | -1.1399 | 35.74892 |
June | 720.00000 | 22.29007 | 45.52672 | -0.9523 | 27.85800 |
July | 744.00000 | 22.25846 | 52.97584 | -0.8918 | 24.71508 |
August | 744.00000 | 22.28114 | 52.50492 | -0.9047 | 25.28019 |
September | 720.00000 | 22.27677 | 49.16020 | -1.0027 | 28.85422 |
October | 744.00000 | 21.97625 | 38.94335 | -0.1848 | 8.37463 |
November | 720.00000 | 21.18827 | 36.87668 | -0.4795 | 10.50371 |
December | 744.00000 | 20.82526 | 35.36764 | -0.6378 | 14.06277 |
Annual Sum or Average | 8760.00000 | 21.75163 | 40.49953 | -0.6559 | 18.18363 |
Minimum of Months | 672.00000 | 20.82526 | 28.77750 | -1.1399 | 8.30385 |
Maximum of Months | 744.00000 | 22.29007 | 52.97584 | -0.1761 | 35.74892 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.63805 | 36.65770 | -0.2658 | 8.48548 |
February | 672.00000 | 21.67725 | 37.54685 | -0.2374 | 8.06297 |
March | 744.00000 | 21.65010 | 34.42725 | -0.2626 | 7.88745 |
April | 720.00000 | 21.69024 | 29.56656 | -0.2597 | 7.78894 |
May | 744.00000 | 21.68499 | 37.76603 | -1.3288 | 43.06427 |
June | 720.00000 | 21.73701 | 46.90266 | -1.2058 | 37.07233 |
July | 744.00000 | 21.76050 | 53.46171 | -1.1127 | 32.81796 |
August | 744.00000 | 21.76178 | 53.37809 | -1.0966 | 32.37026 |
September | 720.00000 | 21.78770 | 49.85582 | -1.1098 | 33.55255 |
October | 744.00000 | 21.77389 | 39.16321 | -0.1287 | 7.35359 |
November | 720.00000 | 21.73102 | 37.06727 | -0.1964 | 7.71046 |
December | 744.00000 | 21.62973 | 35.21034 | -0.2674 | 8.55327 |
Annual Sum or Average | 8760.00000 | 21.71017 | 40.94541 | -0.6250 | 19.63286 |
Minimum of Months | 672.00000 | 21.62973 | 29.56656 | -1.3288 | 7.35359 |
Maximum of Months | 744.00000 | 21.78770 | 53.46171 | -0.1287 | 43.06427 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.78239 | 25.98479 | 0.21703 | 6.14535 |
February | 672.00000 | 23.84131 | 26.80432 | 0.25247 | 6.46379 |
March | 744.00000 | 23.92700 | 24.60237 | 0.29089 | 6.82261 |
April | 720.00000 | 23.97742 | 21.00327 | 0.31923 | 7.20142 |
May | 744.00000 | 23.98870 | 28.97635 | -0.4468 | 9.38536 |
June | 720.00000 | 23.99574 | 38.57399 | -0.3246 | 7.33174 |
July | 744.00000 | 23.99658 | 53.02701 | -0.2042 | 5.91620 |
August | 744.00000 | 23.99602 | 51.56045 | -0.2275 | 6.13076 |
September | 720.00000 | 23.99422 | 44.40544 | -0.3174 | 7.21140 |
October | 744.00000 | 23.94387 | 30.59562 | 0.37006 | 8.09504 |
November | 720.00000 | 23.87427 | 25.53519 | 0.26607 | 6.59264 |
December | 744.00000 | 23.76004 | 24.25589 | 0.19436 | 5.98216 |
Annual Sum or Average | 8760.00000 | 23.92339 | 33.00037 | 0.03117 | 6.94220 |
Minimum of Months | 672.00000 | 23.76004 | 21.00327 | -0.4468 | 5.91620 |
Maximum of Months | 744.00000 | 23.99658 | 53.02701 | 0.37006 | 9.38536 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.90401 | 25.04101 | 0.28609 | 6.77886 |
February | 672.00000 | 23.93524 | 25.91041 | 0.31392 | 7.11461 |
March | 744.00000 | 23.98058 | 23.83469 | 0.34060 | 7.44864 |
April | 720.00000 | 23.99377 | 20.41003 | 0.35608 | 7.71064 |
May | 744.00000 | 23.99502 | 28.48225 | -0.4008 | 8.54672 |
June | 720.00000 | 23.99654 | 38.17770 | -0.2851 | 6.83248 |
July | 744.00000 | 23.99672 | 52.67279 | -0.1674 | 5.63857 |
August | 744.00000 | 23.99659 | 51.19397 | -0.1905 | 5.81383 |
September | 720.00000 | 23.99576 | 43.98634 | -0.2784 | 6.72926 |
October | 744.00000 | 23.97679 | 30.00620 | 0.40830 | 8.66869 |
November | 720.00000 | 23.95283 | 24.72303 | 0.32136 | 7.21812 |
December | 744.00000 | 23.88841 | 23.31425 | 0.26524 | 6.56241 |
Annual Sum or Average | 8760.00000 | 23.96777 | 32.37070 | 0.07943 | 7.08798 |
Minimum of Months | 672.00000 | 23.88841 | 20.41003 | -0.4008 | 5.63857 |
Maximum of Months | 744.00000 | 23.99672 | 52.67279 | 0.40830 | 8.66869 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.90411 | 23.77701 | 0.93405 | 25.21695 |
February | 672.00000 | 23.91697 | 24.75310 | 0.96315 | 26.35942 |
March | 744.00000 | 23.95531 | 23.00575 | 1.00000 | 27.77050 |
April | 720.00000 | 23.97938 | 19.99140 | 1.03865 | 29.55030 |
May | 744.00000 | 23.98766 | 28.16311 | 0.57611 | 15.96242 |
June | 720.00000 | 23.99201 | 37.90443 | 0.70802 | 19.44670 |
July | 744.00000 | 23.99369 | 52.13936 | 0.82987 | 23.15479 |
August | 744.00000 | 23.99363 | 50.64088 | 0.80674 | 22.45949 |
September | 720.00000 | 23.99239 | 43.42166 | 0.70672 | 19.39250 |
October | 744.00000 | 23.97634 | 29.32486 | 1.08680 | 31.58253 |
November | 720.00000 | 23.94432 | 23.71106 | 0.98052 | 26.94100 |
December | 744.00000 | 23.90256 | 22.03326 | 0.91787 | 24.61885 |
Annual Sum or Average | 8760.00000 | 23.96173 | 31.63166 | 0.87858 | 24.36085 |
Minimum of Months | 672.00000 | 23.90256 | 19.99140 | 0.57611 | 15.96242 |
Maximum of Months | 744.00000 | 23.99369 | 52.13936 | 1.08680 | 31.58253 |
Report: OccupantComfortDataSummaryMonthly
For: STORAGE_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.26690 | 21.42425 | -0.4591 | 9.46441 |
February | 672.00000 | 21.43096 | 22.56279 | -0.4105 | 8.65971 |
March | 744.00000 | 21.91780 | 20.24377 | -0.3050 | 7.02894 |
April | 720.00000 | 22.55435 | 16.34503 | -0.1753 | 5.88464 |
May | 744.00000 | 23.06328 | 24.65938 | -0.9998 | 26.68977 |
June | 720.00000 | 23.67967 | 34.06903 | -0.7172 | 16.17127 |
July | 744.00000 | 23.93041 | 48.31982 | -0.5276 | 10.85516 |
August | 744.00000 | 23.85250 | 47.02396 | -0.5674 | 11.81021 |
September | 720.00000 | 23.51773 | 40.21489 | -0.7362 | 16.61767 |
October | 744.00000 | 22.69977 | 26.21394 | -0.0737 | 5.89335 |
November | 720.00000 | 21.85193 | 20.94218 | -0.3163 | 7.23347 |
December | 744.00000 | 21.20197 | 19.40090 | -0.4858 | 9.99648 |
Annual Sum or Average | 8760.00000 | 22.58654 | 28.50619 | -0.4817 | 11.37965 |
Minimum of Months | 672.00000 | 21.20197 | 16.34503 | -0.9998 | 5.88464 |
Maximum of Months | 744.00000 | 23.93041 | 48.31982 | -0.0737 | 26.68977 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.59629 | 24.50523 | -0.3769 | 8.12320 |
February | 672.00000 | 21.73171 | 25.64032 | -0.3350 | 7.52695 |
March | 744.00000 | 22.21216 | 23.38717 | -0.2314 | 6.25495 |
April | 720.00000 | 22.86440 | 19.56769 | -0.0967 | 5.38867 |
May | 744.00000 | 23.20968 | 28.01627 | -0.9519 | 24.58713 |
June | 720.00000 | 23.68448 | 37.54961 | -0.7180 | 16.14226 |
July | 744.00000 | 23.92542 | 51.67733 | -0.5333 | 10.98171 |
August | 744.00000 | 23.91990 | 50.13067 | -0.5456 | 11.27342 |
September | 720.00000 | 23.79512 | 43.05485 | -0.6422 | 13.78704 |
October | 744.00000 | 23.20483 | 29.00347 | 0.05197 | 5.80304 |
November | 720.00000 | 22.24674 | 24.00319 | -0.2189 | 6.13359 |
December | 744.00000 | 21.47580 | 22.55424 | -0.4170 | 8.71441 |
Annual Sum or Average | 8760.00000 | 22.82761 | 31.64574 | -0.4186 | 10.41692 |
Minimum of Months | 672.00000 | 21.47580 | 19.56769 | -0.9519 | 5.38867 |
Maximum of Months | 744.00000 | 23.92542 | 51.67733 | 0.05197 | 24.58713 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.40290 | 22.38519 | -0.4135 | 8.80362 |
February | 672.00000 | 21.60886 | 23.47080 | -0.3505 | 7.93368 |
March | 744.00000 | 22.03057 | 21.20068 | -0.2534 | 6.69516 |
April | 720.00000 | 22.79675 | 17.13771 | -0.0857 | 5.69680 |
May | 744.00000 | 23.23790 | 25.45054 | -0.8917 | 22.85614 |
June | 720.00000 | 23.70853 | 34.92716 | -0.6440 | 14.21123 |
July | 744.00000 | 23.91105 | 49.15187 | -0.4625 | 9.58927 |
August | 744.00000 | 23.87369 | 47.72811 | -0.4881 | 10.16314 |
September | 720.00000 | 23.68060 | 40.76560 | -0.6198 | 13.52584 |
October | 744.00000 | 22.94522 | 26.85194 | 0.01805 | 6.19079 |
November | 720.00000 | 21.91656 | 21.94739 | -0.2779 | 6.96345 |
December | 744.00000 | 21.35641 | 20.31940 | -0.4380 | 9.20901 |
Annual Sum or Average | 8760.00000 | 22.71126 | 29.33216 | -0.4094 | 10.17201 |
Minimum of Months | 672.00000 | 21.35641 | 17.13771 | -0.8917 | 5.69680 |
Maximum of Months | 744.00000 | 23.91105 | 49.15187 | 0.01805 | 22.85614 |
Report: OccupantComfortDataSummaryMonthly
For: MECH_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.58195 | 20.72941 | -0.3903 | 8.30228 |
February | 672.00000 | 21.75568 | 21.81816 | -0.3405 | 7.62147 |
March | 744.00000 | 22.27194 | 19.51359 | -0.2295 | 6.22177 |
April | 720.00000 | 22.87864 | 15.72612 | -0.1062 | 5.49795 |
May | 744.00000 | 23.35847 | 23.87512 | -0.9088 | 23.05437 |
June | 720.00000 | 23.82153 | 33.40458 | -0.6704 | 14.68674 |
July | 744.00000 | 23.97566 | 47.79159 | -0.5090 | 10.45350 |
August | 744.00000 | 23.93715 | 46.36494 | -0.5373 | 11.09208 |
September | 720.00000 | 23.74158 | 39.26709 | -0.6655 | 14.49240 |
October | 744.00000 | 23.02358 | 25.40832 | -0.0042 | 5.73007 |
November | 720.00000 | 22.21342 | 20.19036 | -0.2390 | 6.36159 |
December | 744.00000 | 21.51238 | 18.74901 | -0.4179 | 8.75748 |
Annual Sum or Average | 8760.00000 | 22.84468 | 27.79163 | -0.4188 | 10.20964 |
Minimum of Months | 672.00000 | 21.51238 | 15.72612 | -0.9088 | 5.49795 |
Maximum of Months | 744.00000 | 23.97566 | 47.79159 | -0.0042 | 23.05437 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.100744E+11 | 26168.32 | 05-JAN-16:01 | 570.55 | 0.473661E+11 | 0.00 | 0.574405E+11 | 3.61 | 4.72 | 01-JAN-00:20 | 0.00 | 0.00 |
February | 0.119679E+11 | 73293.55 | 14-FEB-16:01 | 570.83 | 0.554688E+11 | 0.00 | 0.674366E+11 | 3.99 | 4.72 | 01-FEB-00:40 | 0.00 | 0.00 |
March | 0.189106E+11 | 69042.17 | 08-MAR-16:02 | 703.32 | 0.862886E+11 | 0.00 | 0.105199E+12 | 4.41 | 4.72 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.437363E+11 | 87511.67 | 13-APR-18:03 | 717.61 | 0.190473E+12 | 0.00 | 0.234209E+12 | 4.54 | 4.72 | 01-APR-00:20 | 0.00 | 0.00 |
May | 0.716865E+11 | 98940.29 | 19-MAY-18:04 | 743.69 | 0.300326E+12 | 0.00 | 0.372013E+12 | 4.41 | 4.72 | 01-MAY-02:30 | 0.00 | 0.00 |
June | 0.126854E+12 | 144564.52 | 28-JUN-18:10 | 720.00 | 0.488458E+12 | 0.00 | 0.615312E+12 | 4.10 | 4.72 | 01-JUN-17:55 | 0.00 | 0.00 |
July | 0.170229E+12 | 140960.21 | 21-JUL-18:08 | 744.00 | 0.653623E+12 | 0.00 | 0.823852E+12 | 3.96 | 4.59 | 07-JUL-21:54 | 0.00 | 0.00 |
August | 0.152689E+12 | 133579.46 | 04-AUG-18:02 | 744.00 | 0.600918E+12 | 0.00 | 0.753607E+12 | 4.07 | 4.72 | 31-AUG-06:00 | 0.00 | 0.00 |
September | 0.101572E+12 | 108298.74 | 02-SEP-18:03 | 720.00 | 0.420243E+12 | 0.00 | 0.521815E+12 | 4.30 | 4.72 | 08-SEP-24:00 | 0.00 | 0.00 |
October | 0.527377E+11 | 101355.43 | 04-OCT-15:05 | 723.63 | 0.228893E+12 | 0.00 | 0.281630E+12 | 4.42 | 4.72 | 04-OCT-03:30 | 0.00 | 0.00 |
November | 0.153724E+11 | 39536.63 | 02-NOV-15:03 | 654.14 | 0.721852E+11 | 0.00 | 0.875576E+11 | 4.28 | 4.72 | 01-NOV-00:40 | 0.00 | 0.00 |
December | 0.104493E+11 | 22795.93 | 31-DEC-16:03 | 564.04 | 0.492827E+11 | 0.00 | 0.597320E+11 | 3.58 | 4.72 | 01-DEC-00:40 | 0.00 | 0.00 |
Annual Sum or Average | 0.786279E+12 | 8175.80 | 0.319352E+13 | 0.00 | 0.397980E+13 | 4.14 | 0.00 | 0.00 | ||||
Minimum of Months | 0.100744E+11 | 22795.93 | 564.04 | 0.473661E+11 | 0.00 | 0.574405E+11 | 3.58 | 4.59 | 0.00 | 0.00 | ||
Maximum of Months | 0.170229E+12 | 144564.52 | 744.00 | 0.653623E+12 | 0.00 | 0.823852E+12 | 4.54 | 4.72 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.826125E+11 | 0.00 | 712.02 | 163839.24 | 05-JAN-09:03 | 0.00 | 38.92 | 58.68 | 0.32 | 0.00 | 0.08 | 0.41 | 05-JAN-09:03 |
February | 0.708033E+11 | 0.00 | 620.18 | 155697.25 | 06-FEB-16:03 | 0.00 | 38.81 | 57.92 | 0.30 | 0.00 | 0.07 | 0.38 | 06-FEB-16:03 |
March | 0.842994E+11 | 0.00 | 581.44 | 148850.93 | 06-MAR-09:04 | 0.00 | 33.60 | 52.75 | 0.28 | 0.00 | 0.08 | 0.37 | 06-MAR-09:04 |
April | 0.620718E+11 | 0.00 | 374.79 | 134367.71 | 23-APR-05:10 | 0.00 | 27.81 | 43.08 | 0.20 | 0.00 | 0.06 | 0.33 | 23-APR-05:10 |
May | 0.315293E+11 | 0.00 | 216.46 | 122301.40 | 07-MAY-05:00 | 0.00 | 25.38 | 34.99 | 0.09 | 0.00 | 0.03 | 0.30 | 07-MAY-05:00 |
June | 0.522440E+10 | 0.00 | 63.02 | 88597.58 | 09-JUN-05:00 | 0.00 | 23.93 | 27.02 | 0.01 | 0.00 | 0.00 | 0.22 | 09-JUN-05:00 |
July | 4828196.97 | 0.00 | 0.85 | 7014.05 | 26-JUL-08:58 | 0.00 | 26.04 | 26.08 | 0.00 | 0.00 | 0.00 | 0.02 | 26-JUL-08:58 |
August | 49824176.52 | 0.00 | 2.57 | 16108.93 | 31-AUG-06:00 | 0.00 | 30.71 | 30.81 | 0.00 | 0.00 | 0.00 | 0.04 | 31-AUG-06:00 |
September | 0.371579E+10 | 0.00 | 54.95 | 53283.88 | 20-SEP-06:00 | 0.00 | 25.58 | 28.28 | 0.01 | 0.00 | 0.00 | 0.13 | 20-SEP-06:00 |
October | 0.552396E+11 | 0.00 | 362.99 | 138199.20 | 13-OCT-08:05 | 0.00 | 29.09 | 42.14 | 0.18 | 0.00 | 0.05 | 0.34 | 13-OCT-08:05 |
November | 0.820465E+11 | 0.00 | 646.40 | 149124.30 | 25-NOV-19:03 | 0.00 | 37.00 | 57.01 | 0.30 | 0.00 | 0.08 | 0.37 | 25-NOV-19:03 |
December | 0.911744E+11 | 0.00 | 714.14 | 167856.56 | 09-DEC-16:03 | 0.00 | 40.91 | 59.31 | 0.37 | 0.00 | 0.08 | 0.41 | 09-DEC-16:03 |
Annual Sum or Average | 0.568772E+12 | 0.00 | 4349.80 | 0.00 | 31.45 | 43.10 | 0.17 | 0.00 | 0.04 | ||||
Minimum of Months | 4828196.97 | 0.00 | 0.85 | 7014.05 | 0.00 | 23.93 | 26.08 | 0.00 | 0.00 | 0.00 | 0.02 | ||
Maximum of Months | 0.911744E+11 | 0.00 | 714.14 | 167856.56 | 0.00 | 40.91 | 59.31 | 0.37 | 0.00 | 0.08 | 0.41 |
Report: DXReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 28570337.31 | 0.00 | 9.50 | 28570337.31 | 0.00 | 0.00 | 0.00 | 0.00 | 2387.65 | 05-JAN-14:00 | 2387.65 | 05-JAN-14:00 | 0.00 | 0.00 | 0.00 |
February | 0.355265E+09 | 0.00 | 21.67 | 0.355265E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12481.81 | 14-FEB-16:01 | 12481.81 | 14-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.140706E+10 | 0.00 | 85.67 | 0.140706E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13329.91 | 08-MAR-16:02 | 13329.91 | 08-MAR-16:02 | 0.00 | 0.00 | 0.00 |
April | 0.584266E+10 | 0.00 | 233.67 | 0.584266E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14831.72 | 29-APR-15:02 | 14831.72 | 29-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.112570E+11 | 0.00 | 378.83 | 0.112568E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 16218.48 | 19-MAY-15:02 | 16218.48 | 19-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.191799E+11 | 0.00 | 502.33 | 0.191374E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18782.37 | 28-JUN-15:02 | 18782.37 | 28-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.300006E+11 | 0.00 | 589.00 | 0.258977E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 28666.71 | 01-JUL-01:07 | 18731.80 | 22-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.258740E+11 | 0.00 | 587.50 | 0.235240E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 24316.33 | 13-AUG-08:51 | 17811.24 | 01-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.155563E+11 | 0.00 | 508.83 | 0.152250E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 23826.72 | 05-SEP-12:30 | 16799.70 | 02-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.634340E+10 | 0.00 | 253.17 | 0.630600E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15766.09 | 01-OCT-15:02 | 15766.09 | 01-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.142367E+09 | 0.00 | 25.33 | 0.142367E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8394.06 | 09-NOV-14:00 | 8394.06 | 09-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.115987E+12 | 0.00 | 3195.50 | 0.109123E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.300006E+11 | 0.00 | 589.00 | 0.258977E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 28666.71 | 18782.37 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.107850E+10 | 0.00 | 208.52 | 0.107850E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34757.21 | 01-JAN-14:00 | 34757.21 | 01-JAN-14:00 | 0.00 | 0.00 | 0.00 |
February | 0.641656E+10 | 0.00 | 214.20 | 0.641656E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 124499.57 | 14-FEB-16:03 | 124499.57 | 14-FEB-16:03 | 0.00 | 0.00 | 0.00 |
March | 0.235609E+11 | 0.00 | 280.62 | 0.235609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 130725.87 | 08-MAR-16:03 | 130725.87 | 08-MAR-16:03 | 0.00 | 0.00 | 0.00 |
April | 0.967900E+11 | 0.00 | 361.61 | 0.967900E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 198126.48 | 13-APR-18:03 | 198126.48 | 13-APR-18:03 | 0.00 | 0.00 | 0.00 |
May | 0.181877E+12 | 0.00 | 508.56 | 0.181877E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 230005.54 | 19-MAY-18:20 | 230005.54 | 19-MAY-18:20 | 0.00 | 0.00 | 0.00 |
June | 0.320255E+12 | 0.00 | 648.00 | 0.320027E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 264568.24 | 27-JUN-20:10 | 264568.24 | 27-JUN-20:10 | 0.00 | 0.00 | 0.00 |
July | 0.440332E+12 | 0.00 | 744.00 | 0.417714E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 344122.06 | 31-JUL-20:00 | 279380.67 | 21-JUL-18:17 | 0.00 | 0.00 | 0.00 |
August | 0.394622E+12 | 0.00 | 742.17 | 0.382925E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 288426.07 | 14-AUG-21:00 | 260837.15 | 18-AUG-18:30 | 0.00 | 0.00 | 0.00 |
September | 0.255256E+12 | 0.00 | 654.33 | 0.254317E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 232942.71 | 13-SEP-19:10 | 232942.71 | 13-SEP-19:10 | 0.00 | 0.00 | 0.00 |
October | 0.109028E+12 | 0.00 | 409.23 | 0.108946E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 203862.44 | 05-OCT-18:03 | 203862.44 | 05-OCT-18:03 | 0.00 | 0.00 | 0.00 |
November | 0.330358E+10 | 0.00 | 223.76 | 0.330358E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60997.22 | 09-NOV-14:00 | 60997.22 | 09-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 0.100805E+09 | 0.00 | 188.19 | 0.100805E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7684.51 | 03-DEC-19:05 | 7684.51 | 03-DEC-19:05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.183262E+13 | 0.00 | 5183.18 | 0.179706E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.100805E+09 | 0.00 | 188.19 | 0.100805E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7684.51 | 7684.51 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.440332E+12 | 0.00 | 744.00 | 0.417714E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 344122.06 | 279380.67 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.133589E+10 | 0.00 | 216.27 | 0.129248E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11144.57 | 08-JAN-16:02 | 11144.57 | 08-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 0.189704E+10 | 0.00 | 253.30 | 0.179456E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11144.34 | 18-FEB-16:02 | 11144.34 | 18-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.300979E+10 | 0.00 | 401.45 | 0.291922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11144.78 | 08-MAR-16:02 | 11144.78 | 08-MAR-16:02 | 0.00 | 0.00 | 0.00 |
April | 0.555116E+10 | 0.00 | 595.90 | 0.546411E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11144.39 | 19-APR-18:02 | 11144.39 | 19-APR-18:02 | 0.00 | 0.00 | 0.00 |
May | 0.678831E+10 | 0.00 | 656.88 | 0.598971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12167.12 | 24-MAY-15:01 | 11144.76 | 14-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.945167E+10 | 0.00 | 678.89 | 0.780178E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12140.93 | 08-JUN-15:02 | 11179.90 | 24-JUN-08:62 | 0.00 | 0.00 | 0.00 |
July | 0.114228E+11 | 0.00 | 719.43 | 0.856355E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12835.48 | 01-JUL-08:62 | 11178.26 | 26-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.113808E+11 | 0.00 | 715.54 | 0.853650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12945.75 | 26-AUG-08:62 | 11159.66 | 23-AUG-18:01 | 0.00 | 0.00 | 0.00 |
September | 0.923563E+10 | 0.00 | 682.66 | 0.709368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12489.96 | 06-SEP-08:62 | 11169.22 | 17-SEP-08:62 | 0.00 | 0.00 | 0.00 |
October | 0.639631E+10 | 0.00 | 601.96 | 0.555278E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11571.89 | 02-OCT-18:02 | 11143.47 | 17-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.253985E+10 | 0.00 | 383.16 | 0.236183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11143.61 | 13-NOV-16:02 | 11143.61 | 13-NOV-16:02 | 0.00 | 0.00 | 0.00 |
December | 0.115078E+10 | 0.00 | 216.05 | 0.111476E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11144.00 | 29-DEC-16:02 | 11144.00 | 29-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.701600E+11 | 0.00 | 6121.49 | 0.584849E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.115078E+10 | 0.00 | 216.05 | 0.111476E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11143.61 | 11143.47 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.114228E+11 | 0.00 | 719.43 | 0.856355E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12945.75 | 11179.90 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.250448E+09 | 0.00 | 46.78 | 0.246929E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11026.97 | 08-JAN-16:02 | 11026.97 | 08-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 0.564622E+09 | 0.00 | 98.99 | 0.549573E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11159.98 | 14-FEB-19:01 | 11159.98 | 14-FEB-19:01 | 0.00 | 0.00 | 0.00 |
March | 0.114144E+10 | 0.00 | 230.31 | 0.110594E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12515.80 | 30-MAR-18:11 | 12515.80 | 30-MAR-18:11 | 0.00 | 0.00 | 0.00 |
April | 0.339086E+10 | 0.00 | 442.51 | 0.331531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12783.95 | 25-APR-16:21 | 12783.95 | 25-APR-16:21 | 0.00 | 0.00 | 0.00 |
May | 0.543613E+10 | 0.00 | 529.95 | 0.478759E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11983.55 | 24-MAY-15:01 | 11973.81 | 20-MAY-21:51 | 0.00 | 0.00 | 0.00 |
June | 0.868419E+10 | 0.00 | 573.67 | 0.725433E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12407.90 | 24-JUN-08:51 | 12265.65 | 14-JUN-08:21 | 0.00 | 0.00 | 0.00 |
July | 0.102031E+11 | 0.00 | 591.88 | 0.779564E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14077.01 | 31-JUL-21:51 | 12424.83 | 06-JUL-08:61 | 0.00 | 0.00 | 0.00 |
August | 0.942155E+10 | 0.00 | 572.71 | 0.713951E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13837.38 | 26-AUG-08:51 | 13407.14 | 23-AUG-17:01 | 0.00 | 0.00 | 0.00 |
September | 0.628925E+10 | 0.00 | 513.43 | 0.469488E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13133.92 | 05-SEP-21:51 | 11838.36 | 01-SEP-21:51 | 0.00 | 0.00 | 0.00 |
October | 0.298338E+10 | 0.00 | 387.47 | 0.237878E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12665.23 | 02-OCT-21:51 | 12161.99 | 13-OCT-17:42 | 0.00 | 0.00 | 0.00 |
November | 0.681235E+09 | 0.00 | 162.64 | 0.618492E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11027.25 | 05-NOV-15:02 | 11027.25 | 05-NOV-15:02 | 0.00 | 0.00 | 0.00 |
December | 0.158745E+09 | 0.00 | 30.51 | 0.155835E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11026.35 | 29-DEC-16:02 | 11026.35 | 29-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.492050E+11 | 0.00 | 4180.85 | 0.400428E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.158745E+09 | 0.00 | 30.51 | 0.155835E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11026.35 | 11026.35 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.102031E+11 | 0.00 | 591.88 | 0.779564E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14077.01 | 13407.14 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.303091E+11 | 0.00 | 402.71 | 0.303091E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 58596.22 | 03-JAN-12:40 | 58596.22 | 03-JAN-12:40 | 0.00 | 0.00 | 0.00 |
February | 0.290957E+11 | 0.00 | 419.40 | 0.290957E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 59767.53 | 14-FEB-13:00 | 59767.53 | 14-FEB-13:00 | 0.00 | 0.00 | 0.00 |
March | 0.282799E+11 | 0.00 | 496.67 | 0.282799E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 50637.56 | 08-MAR-13:30 | 50637.56 | 08-MAR-13:30 | 0.00 | 0.00 | 0.00 |
April | 0.298575E+11 | 0.00 | 602.34 | 0.298575E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 36545.84 | 13-APR-13:15 | 36545.84 | 13-APR-13:15 | 0.00 | 0.00 | 0.00 |
May | 0.282843E+11 | 0.00 | 663.26 | 0.239116E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 26135.80 | 13-MAY-13:05 | 26135.80 | 13-MAY-13:05 | 0.00 | 0.00 | 0.00 |
June | 0.365435E+11 | 0.00 | 695.89 | 0.246875E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 29391.49 | 29-JUN-16:10 | 27754.74 | 23-JUN-17:15 | 0.00 | 0.00 | 0.00 |
July | 0.490089E+11 | 0.00 | 744.00 | 0.301002E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 32432.15 | 23-JUL-13:20 | 28055.64 | 23-JUL-13:30 | 0.00 | 0.00 | 0.00 |
August | 0.548672E+11 | 0.00 | 744.00 | 0.371928E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 42598.69 | 22-AUG-13:30 | 36736.17 | 18-AUG-11:40 | 0.00 | 0.00 | 0.00 |
September | 0.568582E+11 | 0.00 | 716.00 | 0.416083E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 56505.00 | 28-SEP-13:30 | 54428.00 | 28-SEP-13:15 | 0.00 | 0.00 | 0.00 |
October | 0.545160E+11 | 0.00 | 657.90 | 0.495728E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 58943.22 | 19-OCT-12:25 | 58943.22 | 19-OCT-12:25 | 0.00 | 0.00 | 0.00 |
November | 0.414911E+11 | 0.00 | 523.38 | 0.414911E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 58873.35 | 20-NOV-12:10 | 58873.35 | 20-NOV-12:10 | 0.00 | 0.00 | 0.00 |
December | 0.336108E+11 | 0.00 | 414.28 | 0.336108E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 59748.46 | 31-DEC-13:40 | 59748.46 | 31-DEC-13:40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.472722E+12 | 0.00 | 7079.84 | 0.399717E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.282799E+11 | 0.00 | 402.71 | 0.239116E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 26135.80 | 26135.80 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.568582E+11 | 0.00 | 744.00 | 0.495728E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 59767.53 | 59767.53 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.121803E+10 | 0.00 | 100.45 | 0.120754E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57461.06 | 16-JAN-09:02 | 57461.06 | 16-JAN-09:02 | 0.00 | 0.00 | 0.00 |
February | 0.335542E+10 | 0.00 | 165.83 | 0.323247E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59672.00 | 15-FEB-19:01 | 59672.00 | 15-FEB-19:01 | 0.00 | 0.00 | 0.00 |
March | 0.112215E+11 | 0.00 | 367.79 | 0.107363E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 61606.54 | 27-MAR-19:12 | 61606.54 | 27-MAR-19:12 | 0.00 | 0.00 | 0.00 |
April | 0.234142E+11 | 0.00 | 425.53 | 0.231877E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 64481.59 | 30-APR-21:51 | 64481.59 | 30-APR-21:51 | 0.00 | 0.00 | 0.00 |
May | 0.366945E+11 | 0.00 | 474.59 | 0.336188E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 64713.18 | 11-MAY-21:51 | 64713.18 | 11-MAY-21:51 | 0.00 | 0.00 | 0.00 |
June | 0.543537E+11 | 0.00 | 538.11 | 0.477900E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 68929.22 | 05-JUN-21:51 | 66337.26 | 17-JUN-08:31 | 0.00 | 0.00 | 0.00 |
July | 0.638372E+11 | 0.00 | 566.26 | 0.504711E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 76598.44 | 31-JUL-21:51 | 65454.01 | 11-JUL-07:52 | 0.00 | 0.00 | 0.00 |
August | 0.566379E+11 | 0.00 | 525.80 | 0.436740E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 75818.14 | 25-AUG-21:51 | 64787.74 | 22-AUG-21:51 | 0.00 | 0.00 | 0.00 |
September | 0.378451E+11 | 0.00 | 441.01 | 0.299701E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 73571.07 | 05-SEP-21:51 | 64758.39 | 30-SEP-21:51 | 0.00 | 0.00 | 0.00 |
October | 0.198150E+11 | 0.00 | 392.31 | 0.168531E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 69533.45 | 02-OCT-21:51 | 63869.30 | 11-OCT-21:21 | 0.00 | 0.00 | 0.00 |
November | 0.604763E+10 | 0.00 | 273.83 | 0.540168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60356.96 | 09-NOV-19:02 | 60356.96 | 09-NOV-19:02 | 0.00 | 0.00 | 0.00 |
December | 0.881727E+09 | 0.00 | 76.85 | 0.865441E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 58350.19 | 02-DEC-09:02 | 58350.19 | 02-DEC-09:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.315322E+12 | 0.00 | 4348.36 | 0.267008E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.881727E+09 | 0.00 | 76.85 | 0.865441E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 57461.06 | 57461.06 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.638372E+11 | 0.00 | 566.26 | 0.504711E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 76598.44 | 66337.26 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.133060E+10 | 0.00 | 224.78 | 0.126738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9895.28 | 05-JAN-16:01 | 9895.28 | 05-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.170617E+10 | 0.00 | 259.04 | 0.158515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9894.90 | 25-FEB-16:02 | 9894.90 | 25-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.329773E+10 | 0.00 | 440.68 | 0.314550E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9895.25 | 02-MAR-09:02 | 9895.25 | 02-MAR-09:02 | 0.00 | 0.00 | 0.00 |
April | 0.630548E+10 | 0.00 | 639.05 | 0.619367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9895.35 | 23-APR-08:62 | 9895.35 | 23-APR-08:62 | 0.00 | 0.00 | 0.00 |
May | 0.759950E+10 | 0.00 | 701.46 | 0.678503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10509.53 | 24-MAY-15:01 | 9895.29 | 02-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.104034E+11 | 0.00 | 703.92 | 0.893065E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10653.64 | 08-JUN-15:02 | 9894.93 | 18-JUN-08:62 | 0.00 | 0.00 | 0.00 |
July | 0.126049E+11 | 0.00 | 734.12 | 0.100461E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 11182.58 | 01-JUL-08:62 | 9830.85 | 04-JUL-08:62 | 0.00 | 0.00 | 0.00 |
August | 0.122497E+11 | 0.00 | 733.02 | 0.966153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10579.33 | 29-AUG-18:02 | 9933.69 | 23-AUG-18:01 | 0.00 | 0.00 | 0.00 |
September | 0.954147E+10 | 0.00 | 701.86 | 0.760891E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10888.99 | 06-SEP-08:62 | 9835.11 | 07-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.644841E+10 | 0.00 | 626.79 | 0.566927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10249.89 | 02-OCT-18:02 | 9895.04 | 17-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.259178E+10 | 0.00 | 394.30 | 0.241054E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9895.11 | 17-NOV-09:02 | 9895.11 | 17-NOV-09:02 | 0.00 | 0.00 | 0.00 |
December | 0.111369E+10 | 0.00 | 198.94 | 0.106769E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9895.31 | 11-DEC-09:02 | 9895.31 | 11-DEC-09:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.751928E+11 | 0.00 | 6357.96 | 0.643714E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.111369E+10 | 0.00 | 198.94 | 0.106769E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9894.90 | 9830.85 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.126049E+11 | 0.00 | 734.12 | 0.100461E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 11182.58 | 9933.69 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.227269E+09 | 0.00 | 43.66 | 0.198096E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9548.15 | 27-JAN-09:02 | 9548.15 | 27-JAN-09:02 | 0.00 | 0.00 | 0.00 |
February | 0.428457E+09 | 0.00 | 86.68 | 0.369191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9812.47 | 14-FEB-09:02 | 9812.47 | 14-FEB-09:02 | 0.00 | 0.00 | 0.00 |
March | 0.150248E+10 | 0.00 | 279.33 | 0.140718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9812.67 | 02-MAR-09:02 | 9812.67 | 02-MAR-09:02 | 0.00 | 0.00 | 0.00 |
April | 0.439783E+10 | 0.00 | 510.32 | 0.429797E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11376.71 | 27-APR-08:51 | 11376.71 | 27-APR-08:51 | 0.00 | 0.00 | 0.00 |
May | 0.622503E+10 | 0.00 | 576.52 | 0.553635E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12417.72 | 14-MAY-08:32 | 12417.72 | 14-MAY-08:32 | 0.00 | 0.00 | 0.00 |
June | 0.927336E+10 | 0.00 | 598.40 | 0.797632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13360.65 | 14-JUN-07:52 | 13360.65 | 14-JUN-07:52 | 0.00 | 0.00 | 0.00 |
July | 0.109697E+11 | 0.00 | 607.08 | 0.882293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14348.69 | 04-JUL-08:62 | 13072.31 | 04-JUL-08:62 | 0.00 | 0.00 | 0.00 |
August | 0.989016E+10 | 0.00 | 588.50 | 0.777676E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13900.97 | 14-AUG-08:32 | 12566.99 | 17-AUG-07:32 | 0.00 | 0.00 | 0.00 |
September | 0.638879E+10 | 0.00 | 533.67 | 0.477354E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12001.06 | 06-SEP-08:51 | 11972.96 | 02-SEP-08:32 | 0.00 | 0.00 | 0.00 |
October | 0.323647E+10 | 0.00 | 436.84 | 0.258263E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11309.73 | 02-OCT-21:51 | 10863.57 | 11-OCT-08:51 | 0.00 | 0.00 | 0.00 |
November | 0.708412E+09 | 0.00 | 158.13 | 0.617435E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9812.22 | 19-NOV-09:02 | 9812.22 | 19-NOV-09:02 | 0.00 | 0.00 | 0.00 |
December | 0.154583E+09 | 0.00 | 40.74 | 0.133268E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9784.21 | 31-DEC-09:02 | 9784.21 | 31-DEC-09:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.534025E+11 | 0.00 | 4459.87 | 0.444917E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.154583E+09 | 0.00 | 40.74 | 0.133268E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9548.15 | 9548.15 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.109697E+11 | 0.00 | 607.08 | 0.882293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14348.69 | 13360.65 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.305327E+09 | 0.00 | 155.96 | 0.297436E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2952.65 | 21-JAN-16:02 | 2952.65 | 21-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 0.457513E+09 | 0.00 | 201.40 | 0.435634E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2952.61 | 25-FEB-16:02 | 2952.61 | 25-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.709663E+09 | 0.00 | 315.56 | 0.690341E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2952.37 | 29-MAR-18:02 | 2952.37 | 29-MAR-18:02 | 0.00 | 0.00 | 0.00 |
April | 0.134792E+10 | 0.00 | 532.23 | 0.133040E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2952.63 | 20-APR-15:02 | 2952.63 | 20-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.167470E+10 | 0.00 | 619.69 | 0.148902E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3307.15 | 29-MAY-08:62 | 2952.68 | 14-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.243035E+10 | 0.00 | 672.52 | 0.201550E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3238.79 | 08-JUN-15:02 | 2967.86 | 25-JUN-08:62 | 0.00 | 0.00 | 0.00 |
July | 0.294585E+10 | 0.00 | 719.01 | 0.219985E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3568.77 | 01-JUL-08:62 | 2949.32 | 09-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.290273E+10 | 0.00 | 713.92 | 0.217290E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3581.34 | 26-AUG-08:62 | 2965.74 | 03-AUG-08:62 | 0.00 | 0.00 | 0.00 |
September | 0.224494E+10 | 0.00 | 672.40 | 0.171422E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3440.85 | 06-SEP-08:62 | 2934.48 | 07-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.147966E+10 | 0.00 | 531.90 | 0.127697E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3155.96 | 03-OCT-08:62 | 2952.49 | 28-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.542985E+09 | 0.00 | 286.14 | 0.508070E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2952.37 | 13-NOV-16:02 | 2952.37 | 13-NOV-16:02 | 0.00 | 0.00 | 0.00 |
December | 0.257232E+09 | 0.00 | 149.43 | 0.251595E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2952.54 | 28-DEC-16:02 | 2952.54 | 28-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.172989E+11 | 0.00 | 5570.17 | 0.143819E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.257232E+09 | 0.00 | 149.43 | 0.251595E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2952.37 | 2934.48 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.294585E+10 | 0.00 | 719.01 | 0.219985E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3581.34 | 2967.86 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 54986960.21 | 0.00 | 36.28 | 54413703.27 | 0.00 | 0.00 | 0.00 | 0.00 | 2916.25 | 05-JAN-16:01 | 2916.25 | 05-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.128909E+09 | 0.00 | 74.30 | 0.125270E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2977.44 | 14-FEB-19:01 | 2977.44 | 14-FEB-19:01 | 0.00 | 0.00 | 0.00 |
March | 0.249812E+09 | 0.00 | 155.22 | 0.244739E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3378.55 | 30-MAR-18:11 | 3378.55 | 30-MAR-18:11 | 0.00 | 0.00 | 0.00 |
April | 0.813084E+09 | 0.00 | 395.17 | 0.798652E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3381.02 | 25-APR-16:21 | 3381.02 | 25-APR-16:21 | 0.00 | 0.00 | 0.00 |
May | 0.136588E+10 | 0.00 | 505.41 | 0.121145E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3264.99 | 06-MAY-19:41 | 3264.99 | 06-MAY-19:41 | 0.00 | 0.00 | 0.00 |
June | 0.227712E+10 | 0.00 | 570.67 | 0.191427E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3281.37 | 05-JUN-21:51 | 3248.72 | 14-JUN-08:21 | 0.00 | 0.00 | 0.00 |
July | 0.268979E+10 | 0.00 | 593.97 | 0.205840E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3775.86 | 31-JUL-21:51 | 3285.48 | 06-JUL-08:61 | 0.00 | 0.00 | 0.00 |
August | 0.245918E+10 | 0.00 | 575.05 | 0.186369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3699.14 | 26-AUG-08:51 | 3555.02 | 23-AUG-17:01 | 0.00 | 0.00 | 0.00 |
September | 0.154315E+10 | 0.00 | 513.24 | 0.114106E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3504.71 | 05-SEP-21:51 | 3074.15 | 20-SEP-21:51 | 0.00 | 0.00 | 0.00 |
October | 0.642022E+09 | 0.00 | 325.92 | 0.503205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3375.66 | 02-OCT-21:51 | 3268.62 | 13-OCT-17:42 | 0.00 | 0.00 | 0.00 |
November | 0.127483E+09 | 0.00 | 90.47 | 0.119055E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2916.07 | 13-NOV-16:02 | 2916.07 | 13-NOV-16:02 | 0.00 | 0.00 | 0.00 |
December | 31756943.10 | 0.00 | 23.02 | 30777317.81 | 0.00 | 0.00 | 0.00 | 0.00 | 2916.17 | 29-DEC-16:02 | 2916.17 | 29-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.123832E+11 | 0.00 | 3858.74 | 0.100650E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 31756943.10 | 0.00 | 23.02 | 30777317.81 | 0.00 | 0.00 | 0.00 | 0.00 | 2916.07 | 2916.07 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.268979E+10 | 0.00 | 593.97 | 0.205840E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3775.86 | 3555.02 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.674786E+10 | 0.00 | 392.83 | 0.657123E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13132.48 | 03-JAN-13:53 | 13132.48 | 03-JAN-13:53 | 0.00 | 0.00 | 0.00 |
February | 0.657582E+10 | 0.00 | 402.96 | 0.631671E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13016.92 | 13-FEB-13:25 | 13016.92 | 13-FEB-13:25 | 0.00 | 0.00 | 0.00 |
March | 0.637075E+10 | 0.00 | 493.48 | 0.617643E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12432.59 | 18-MAR-18:01 | 12432.59 | 18-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.710485E+10 | 0.00 | 587.54 | 0.695939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12431.92 | 27-APR-15:02 | 12431.92 | 27-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.725541E+10 | 0.00 | 633.34 | 0.629857E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13716.27 | 24-MAY-15:01 | 12432.52 | 08-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.982239E+10 | 0.00 | 672.57 | 0.778794E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13729.90 | 08-JUN-15:02 | 12432.26 | 20-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.135784E+11 | 0.00 | 714.72 | 0.100091E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 14727.53 | 01-JUL-08:62 | 12454.06 | 14-JUL-08:62 | 0.00 | 0.00 | 0.00 |
August | 0.145065E+11 | 0.00 | 712.80 | 0.110653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 14629.32 | 26-AUG-08:62 | 12482.51 | 11-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.136512E+11 | 0.00 | 682.47 | 0.113463E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 13604.76 | 06-SEP-08:62 | 12435.75 | 23-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.122586E+11 | 0.00 | 649.52 | 0.113792E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 13099.83 | 15-OCT-12:55 | 13099.83 | 15-OCT-12:55 | 0.00 | 0.00 | 0.00 |
November | 0.885652E+10 | 0.00 | 526.97 | 0.856452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13114.42 | 07-NOV-13:23 | 13114.42 | 07-NOV-13:23 | 0.00 | 0.00 | 0.00 |
December | 0.739861E+10 | 0.00 | 395.69 | 0.726299E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13076.55 | 30-DEC-13:35 | 13076.55 | 30-DEC-13:35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.114127E+12 | 0.00 | 6864.91 | 0.997376E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.637075E+10 | 0.00 | 392.83 | 0.617643E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12431.92 | 12431.92 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.145065E+11 | 0.00 | 714.72 | 0.113792E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 14727.53 | 13132.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1186.63 | 922.80 | 263.83 | 1367.97 | 576.89 | 0.00 | 0.00 | 0.00 |
February | 1169.68 | 856.05 | 313.63 | 1375.64 | 531.95 | 0.00 | 0.00 | 0.00 |
March | 869.77 | 530.74 | 339.03 | 1049.84 | 421.88 | 0.00 | 0.00 | 0.00 |
April | 667.98 | 273.75 | 394.23 | 838.63 | 293.28 | 0.00 | 0.00 | 0.00 |
May | 449.56 | 101.70 | 347.85 | 577.80 | 206.68 | 0.00 | 0.00 | 0.00 |
June | 375.82 | 45.13 | 330.69 | 568.53 | 133.08 | 0.00 | 0.00 | 0.00 |
July | 416.00 | 65.27 | 350.73 | 682.69 | 82.03 | 0.00 | 0.00 | 0.00 |
August | 565.91 | 178.49 | 387.42 | 881.00 | 100.15 | 0.00 | 0.00 | 0.00 |
September | 803.38 | 452.23 | 351.15 | 1155.51 | 183.43 | 0.00 | 0.00 | 0.00 |
October | 1082.35 | 796.16 | 286.19 | 1395.93 | 320.61 | 0.00 | 0.00 | 0.00 |
November | 1220.92 | 939.64 | 281.28 | 1450.29 | 460.39 | 0.00 | 0.00 | 0.00 |
December | 1294.03 | 1068.21 | 225.82 | 1498.83 | 591.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 839.96 | 517.41 | 322.55 | 1068.45 | 324.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 375.82 | 45.13 | 225.82 | 568.53 | 82.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1294.03 | 1068.21 | 394.23 | 1498.83 | 591.81 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3341.48 | 2598.55 | 742.93 | 3809.35 | 1729.24 | 0.00 | 0.00 | 0.00 |
February | 3293.74 | 2410.57 | 883.17 | 3831.09 | 1598.78 | 0.00 | 0.00 | 0.00 |
March | 2449.21 | 1494.52 | 954.68 | 2912.08 | 1282.46 | 0.00 | 0.00 | 0.00 |
April | 1880.99 | 770.86 | 1110.14 | 2323.30 | 888.38 | 0.00 | 0.00 | 0.00 |
May | 1265.92 | 286.39 | 979.54 | 1590.90 | 629.84 | 0.00 | 0.00 | 0.00 |
June | 1058.28 | 127.08 | 931.20 | 1578.71 | 394.77 | 0.00 | 0.00 | 0.00 |
July | 1171.44 | 183.81 | 987.63 | 1907.36 | 235.59 | 0.00 | 0.00 | 0.00 |
August | 1593.56 | 502.60 | 1090.96 | 2464.80 | 287.00 | 0.00 | 0.00 | 0.00 |
September | 2262.26 | 1273.45 | 988.81 | 3232.23 | 533.11 | 0.00 | 0.00 | 0.00 |
October | 3047.83 | 2241.93 | 805.90 | 3901.49 | 948.69 | 0.00 | 0.00 | 0.00 |
November | 3438.04 | 2645.98 | 792.06 | 4044.24 | 1384.65 | 0.00 | 0.00 | 0.00 |
December | 3643.92 | 3008.01 | 635.91 | 4181.93 | 1776.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2365.28 | 1457.01 | 908.27 | 2976.52 | 970.84 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1058.28 | 127.08 | 635.91 | 1578.71 | 235.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3643.92 | 3008.01 | 1110.14 | 4181.93 | 1776.34 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 4340.77 | 3375.67 | 965.10 | 5024.66 | 2301.85 | 0.00 | 0.00 | 0.00 |
February | 4278.76 | 3131.47 | 1147.29 | 5062.17 | 2123.27 | 0.00 | 0.00 | 0.00 |
March | 3181.66 | 1941.47 | 1240.19 | 3851.09 | 1704.10 | 0.00 | 0.00 | 0.00 |
April | 2443.51 | 1001.39 | 1442.13 | 3089.27 | 1176.16 | 0.00 | 0.00 | 0.00 |
May | 1644.50 | 372.03 | 1272.47 | 2118.80 | 837.55 | 0.00 | 0.00 | 0.00 |
June | 1374.76 | 165.08 | 1209.68 | 2108.03 | 523.76 | 0.00 | 0.00 | 0.00 |
July | 1521.77 | 238.78 | 1282.99 | 2548.44 | 306.96 | 0.00 | 0.00 | 0.00 |
August | 2070.13 | 652.91 | 1417.22 | 3280.89 | 370.84 | 0.00 | 0.00 | 0.00 |
September | 2938.80 | 1654.29 | 1284.51 | 4283.02 | 691.55 | 0.00 | 0.00 | 0.00 |
October | 3959.30 | 2912.39 | 1046.91 | 5156.09 | 1245.69 | 0.00 | 0.00 | 0.00 |
November | 4466.21 | 3437.27 | 1028.93 | 5338.14 | 1830.42 | 0.00 | 0.00 | 0.00 |
December | 4733.66 | 3907.58 | 826.08 | 5516.77 | 2361.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3072.63 | 1892.73 | 1179.90 | 3941.63 | 1285.22 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1374.76 | 165.08 | 826.08 | 2108.03 | 306.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4733.66 | 3907.58 | 1442.13 | 5516.77 | 2361.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 234.62 | 182.45 | 52.16 | 274.51 | 112.70 | 0.00 | 0.00 | 0.00 |
February | 231.27 | 169.26 | 62.01 | 275.66 | 103.48 | 0.00 | 0.00 | 0.00 |
March | 171.97 | 104.94 | 67.03 | 209.79 | 81.52 | 0.00 | 0.00 | 0.00 |
April | 132.07 | 54.12 | 77.95 | 168.27 | 53.97 | 0.00 | 0.00 | 0.00 |
May | 88.89 | 20.11 | 68.78 | 117.04 | 36.13 | 0.00 | 0.00 | 0.00 |
June | 74.31 | 8.92 | 65.38 | 118.38 | 20.61 | 0.00 | 0.00 | 0.00 |
July | 82.25 | 12.91 | 69.35 | 143.13 | 9.47 | 0.00 | 0.00 | 0.00 |
August | 111.89 | 35.29 | 76.60 | 181.39 | 12.38 | 0.00 | 0.00 | 0.00 |
September | 158.84 | 89.41 | 69.43 | 233.77 | 28.20 | 0.00 | 0.00 | 0.00 |
October | 214.00 | 157.41 | 56.59 | 281.27 | 57.19 | 0.00 | 0.00 | 0.00 |
November | 241.40 | 185.78 | 55.61 | 291.47 | 87.28 | 0.00 | 0.00 | 0.00 |
December | 255.85 | 211.20 | 44.65 | 301.30 | 114.87 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 166.08 | 102.30 | 63.77 | 215.99 | 59.59 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 74.31 | 8.92 | 44.65 | 117.04 | 9.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 255.85 | 211.20 | 77.95 | 301.30 | 114.87 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 169.72 | 96.79 | 72.93 | 159.11 | 231.50 | 0.00 | 0.00 | 0.00 |
February | 218.05 | 125.81 | 92.23 | 220.69 | 207.65 | 0.00 | 0.00 | 0.00 |
March | 243.30 | 129.24 | 114.06 | 265.82 | 157.44 | 0.00 | 0.00 | 0.00 |
April | 311.27 | 165.66 | 145.61 | 371.76 | 98.50 | 0.00 | 0.00 | 0.00 |
May | 296.00 | 152.94 | 143.06 | 380.43 | 66.22 | 0.00 | 0.00 | 0.00 |
June | 315.40 | 175.65 | 139.75 | 460.45 | 38.41 | 0.00 | 0.00 | 0.00 |
July | 284.77 | 139.15 | 145.62 | 439.54 | 17.67 | 0.00 | 0.00 | 0.00 |
August | 291.29 | 134.53 | 156.75 | 430.71 | 23.12 | 0.00 | 0.00 | 0.00 |
September | 264.29 | 139.54 | 124.75 | 364.40 | 53.10 | 0.00 | 0.00 | 0.00 |
October | 241.87 | 150.65 | 91.21 | 292.81 | 115.07 | 0.00 | 0.00 | 0.00 |
November | 189.00 | 111.18 | 77.82 | 189.32 | 177.22 | 0.00 | 0.00 | 0.00 |
December | 162.29 | 101.34 | 60.95 | 148.54 | 238.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 248.96 | 135.15 | 113.81 | 310.64 | 118.23 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 162.29 | 96.79 | 60.95 | 148.54 | 17.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 315.40 | 175.65 | 156.75 | 460.45 | 238.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 31.79 | 0.00 | 31.79 | 7.16 | 125.52 | 0.00 | 0.00 | 0.00 |
February | 39.73 | 0.00 | 39.73 | 14.72 | 112.57 | 0.00 | 0.00 | 0.00 |
March | 50.13 | 0.00 | 50.13 | 32.30 | 85.82 | 0.00 | 0.00 | 0.00 |
April | 63.94 | 0.86 | 63.08 | 53.94 | 53.89 | 0.00 | 0.00 | 0.00 |
May | 69.21 | 4.50 | 64.71 | 76.22 | 35.63 | 0.00 | 0.00 | 0.00 |
June | 78.79 | 13.10 | 65.69 | 118.86 | 20.15 | 0.00 | 0.00 | 0.00 |
July | 72.25 | 6.16 | 66.09 | 119.87 | 10.01 | 0.00 | 0.00 | 0.00 |
August | 67.05 | 1.64 | 65.41 | 100.82 | 13.06 | 0.00 | 0.00 | 0.00 |
September | 53.53 | 0.04 | 53.49 | 67.88 | 30.41 | 0.00 | 0.00 | 0.00 |
October | 39.90 | 0.00 | 39.90 | 30.87 | 63.74 | 0.00 | 0.00 | 0.00 |
November | 33.89 | 0.00 | 33.89 | 10.88 | 95.99 | 0.00 | 0.00 | 0.00 |
December | 27.06 | 0.00 | 27.06 | 2.28 | 129.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 52.32 | 2.19 | 50.12 | 53.19 | 64.49 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 27.06 | 0.00 | 27.06 | 2.28 | 10.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 78.79 | 13.10 | 66.09 | 119.87 | 129.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 169.72 | 96.79 | 72.93 | 166.03 | 226.39 | 0.00 | 0.00 | 0.00 |
February | 218.05 | 125.81 | 92.23 | 227.51 | 203.47 | 0.00 | 0.00 | 0.00 |
March | 243.30 | 129.24 | 114.06 | 269.35 | 156.18 | 0.00 | 0.00 | 0.00 |
April | 311.27 | 165.66 | 145.61 | 372.02 | 101.32 | 0.00 | 0.00 | 0.00 |
May | 296.00 | 152.94 | 143.06 | 379.07 | 69.57 | 0.00 | 0.00 | 0.00 |
June | 315.40 | 175.65 | 139.75 | 457.23 | 40.35 | 0.00 | 0.00 | 0.00 |
July | 284.77 | 139.15 | 145.62 | 436.68 | 19.28 | 0.00 | 0.00 | 0.00 |
August | 291.29 | 134.53 | 156.75 | 429.02 | 25.40 | 0.00 | 0.00 | 0.00 |
September | 264.29 | 139.54 | 124.75 | 365.92 | 56.72 | 0.00 | 0.00 | 0.00 |
October | 241.87 | 150.65 | 91.21 | 296.18 | 116.15 | 0.00 | 0.00 | 0.00 |
November | 189.00 | 111.18 | 77.82 | 195.68 | 172.79 | 0.00 | 0.00 | 0.00 |
December | 162.29 | 101.34 | 60.95 | 155.31 | 231.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 248.96 | 135.15 | 113.81 | 312.81 | 117.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 162.29 | 96.79 | 60.95 | 155.31 | 19.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 315.40 | 175.65 | 156.75 | 457.23 | 231.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 187.66 | 145.93 | 41.72 | 207.35 | 114.24 | 0.00 | 0.00 | 0.00 |
February | 184.98 | 135.38 | 49.60 | 208.38 | 106.97 | 0.00 | 0.00 | 0.00 |
March | 137.55 | 83.93 | 53.62 | 155.81 | 87.68 | 0.00 | 0.00 | 0.00 |
April | 105.64 | 43.29 | 62.35 | 123.02 | 62.59 | 0.00 | 0.00 | 0.00 |
May | 71.09 | 16.08 | 55.01 | 81.66 | 46.50 | 0.00 | 0.00 | 0.00 |
June | 59.43 | 7.14 | 52.30 | 81.93 | 30.86 | 0.00 | 0.00 | 0.00 |
July | 65.79 | 10.32 | 55.47 | 100.66 | 20.60 | 0.00 | 0.00 | 0.00 |
August | 89.49 | 28.23 | 61.27 | 132.09 | 24.26 | 0.00 | 0.00 | 0.00 |
September | 127.05 | 71.52 | 55.53 | 175.60 | 40.10 | 0.00 | 0.00 | 0.00 |
October | 171.17 | 125.91 | 45.26 | 213.20 | 66.06 | 0.00 | 0.00 | 0.00 |
November | 193.08 | 148.60 | 44.48 | 220.91 | 93.37 | 0.00 | 0.00 | 0.00 |
December | 204.64 | 168.93 | 35.71 | 229.16 | 117.71 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 132.83 | 81.83 | 51.01 | 160.54 | 67.37 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 59.43 | 7.14 | 35.71 | 81.66 | 20.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 204.64 | 168.93 | 62.35 | 229.16 | 117.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 25.44 | 0.00 | 25.44 | 5.51 | 102.34 | 0.00 | 0.00 | 0.00 |
February | 31.79 | 0.00 | 31.79 | 12.23 | 90.85 | 0.00 | 0.00 | 0.00 |
March | 40.11 | 0.00 | 40.11 | 27.51 | 68.00 | 0.00 | 0.00 | 0.00 |
April | 51.16 | 0.69 | 50.47 | 46.68 | 41.16 | 0.00 | 0.00 | 0.00 |
May | 55.37 | 3.60 | 51.77 | 64.76 | 26.98 | 0.00 | 0.00 | 0.00 |
June | 63.04 | 10.48 | 52.56 | 100.07 | 14.70 | 0.00 | 0.00 | 0.00 |
July | 57.81 | 4.93 | 52.88 | 100.94 | 6.66 | 0.00 | 0.00 | 0.00 |
August | 53.65 | 1.31 | 52.34 | 85.65 | 8.84 | 0.00 | 0.00 | 0.00 |
September | 42.83 | 0.03 | 42.80 | 58.01 | 22.05 | 0.00 | 0.00 | 0.00 |
October | 31.93 | 0.00 | 31.93 | 27.07 | 48.72 | 0.00 | 0.00 | 0.00 |
November | 27.11 | 0.00 | 27.11 | 9.11 | 77.10 | 0.00 | 0.00 | 0.00 |
December | 21.65 | 0.00 | 21.65 | 1.63 | 106.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 41.86 | 1.76 | 40.10 | 45.10 | 50.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 21.65 | 0.00 | 21.65 | 1.63 | 6.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.04 | 10.48 | 52.88 | 100.94 | 106.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 164.57 | 92.11 | 72.46 | 137.86 | 218.44 | 0.00 | 0.00 | 0.00 |
February | 199.30 | 107.13 | 92.17 | 185.30 | 196.71 | 0.00 | 0.00 | 0.00 |
March | 264.85 | 150.88 | 113.96 | 285.33 | 147.32 | 0.00 | 0.00 | 0.00 |
April | 359.28 | 204.45 | 154.83 | 435.11 | 92.63 | 0.00 | 0.00 | 0.00 |
May | 343.23 | 195.50 | 147.73 | 444.09 | 63.32 | 0.00 | 0.00 | 0.00 |
June | 370.16 | 228.00 | 142.16 | 534.03 | 35.16 | 0.00 | 0.00 | 0.00 |
July | 342.34 | 195.70 | 146.64 | 520.24 | 16.92 | 0.00 | 0.00 | 0.00 |
August | 338.83 | 186.76 | 152.07 | 495.27 | 21.73 | 0.00 | 0.00 | 0.00 |
September | 282.54 | 158.10 | 124.45 | 386.25 | 49.90 | 0.00 | 0.00 | 0.00 |
October | 246.16 | 156.32 | 89.85 | 290.52 | 106.60 | 0.00 | 0.00 | 0.00 |
November | 191.45 | 112.31 | 79.14 | 184.82 | 169.80 | 0.00 | 0.00 | 0.00 |
December | 155.95 | 95.12 | 60.82 | 133.13 | 231.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 271.83 | 157.07 | 114.76 | 336.70 | 112.05 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 155.95 | 92.11 | 60.82 | 133.13 | 16.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 370.16 | 228.00 | 154.83 | 534.03 | 231.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 234.62 | 182.45 | 52.16 | 273.84 | 112.24 | 0.00 | 0.00 | 0.00 |
February | 231.27 | 169.26 | 62.01 | 274.92 | 102.78 | 0.00 | 0.00 | 0.00 |
March | 171.97 | 104.94 | 67.03 | 208.28 | 81.17 | 0.00 | 0.00 | 0.00 |
April | 132.07 | 54.12 | 77.95 | 166.48 | 53.77 | 0.00 | 0.00 | 0.00 |
May | 88.89 | 20.11 | 68.78 | 115.28 | 35.95 | 0.00 | 0.00 | 0.00 |
June | 74.31 | 8.92 | 65.38 | 117.00 | 20.24 | 0.00 | 0.00 | 0.00 |
July | 82.25 | 12.91 | 69.35 | 141.92 | 9.37 | 0.00 | 0.00 | 0.00 |
August | 111.89 | 35.29 | 76.60 | 180.32 | 12.20 | 0.00 | 0.00 | 0.00 |
September | 158.84 | 89.41 | 69.43 | 232.95 | 27.83 | 0.00 | 0.00 | 0.00 |
October | 214.00 | 157.41 | 56.59 | 280.37 | 56.66 | 0.00 | 0.00 | 0.00 |
November | 241.40 | 185.78 | 55.61 | 290.64 | 86.80 | 0.00 | 0.00 | 0.00 |
December | 255.85 | 211.20 | 44.65 | 300.56 | 114.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 166.08 | 102.30 | 63.77 | 214.87 | 59.23 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 74.31 | 8.92 | 44.65 | 115.28 | 9.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 255.85 | 211.20 | 77.95 | 300.56 | 114.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 31.79 | 0.00 | 31.79 | 6.60 | 124.92 | 0.00 | 0.00 | 0.00 |
February | 39.73 | 0.00 | 39.73 | 14.21 | 111.76 | 0.00 | 0.00 | 0.00 |
March | 50.13 | 0.00 | 50.13 | 31.12 | 85.60 | 0.00 | 0.00 | 0.00 |
April | 63.94 | 0.86 | 63.08 | 52.29 | 53.17 | 0.00 | 0.00 | 0.00 |
May | 69.21 | 4.50 | 64.71 | 74.14 | 35.17 | 0.00 | 0.00 | 0.00 |
June | 78.79 | 13.10 | 65.69 | 115.96 | 19.78 | 0.00 | 0.00 | 0.00 |
July | 72.25 | 6.16 | 66.09 | 116.94 | 10.09 | 0.00 | 0.00 | 0.00 |
August | 67.05 | 1.64 | 65.41 | 98.00 | 12.91 | 0.00 | 0.00 | 0.00 |
September | 53.53 | 0.04 | 53.49 | 66.23 | 30.04 | 0.00 | 0.00 | 0.00 |
October | 39.90 | 0.00 | 39.90 | 29.98 | 62.67 | 0.00 | 0.00 | 0.00 |
November | 33.89 | 0.00 | 33.89 | 10.21 | 95.45 | 0.00 | 0.00 | 0.00 |
December | 27.06 | 0.00 | 27.06 | 1.94 | 129.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 52.32 | 2.19 | 50.12 | 51.67 | 64.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 27.06 | 0.00 | 27.06 | 1.94 | 10.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 78.79 | 13.10 | 66.09 | 116.94 | 129.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 164.57 | 92.11 | 72.46 | 144.00 | 211.91 | 0.00 | 0.00 | 0.00 |
February | 199.30 | 107.13 | 92.17 | 191.98 | 191.47 | 0.00 | 0.00 | 0.00 |
March | 264.85 | 150.88 | 113.96 | 289.21 | 145.71 | 0.00 | 0.00 | 0.00 |
April | 359.28 | 204.45 | 154.83 | 436.24 | 94.64 | 0.00 | 0.00 | 0.00 |
May | 343.23 | 195.50 | 147.73 | 442.27 | 66.30 | 0.00 | 0.00 | 0.00 |
June | 370.16 | 228.00 | 142.16 | 527.58 | 36.99 | 0.00 | 0.00 | 0.00 |
July | 342.34 | 195.70 | 146.64 | 513.51 | 18.70 | 0.00 | 0.00 | 0.00 |
August | 338.83 | 186.76 | 152.07 | 489.69 | 23.94 | 0.00 | 0.00 | 0.00 |
September | 282.54 | 158.10 | 124.45 | 385.79 | 53.25 | 0.00 | 0.00 | 0.00 |
October | 246.16 | 156.32 | 89.85 | 294.28 | 106.71 | 0.00 | 0.00 | 0.00 |
November | 191.45 | 112.31 | 79.14 | 190.54 | 164.14 | 0.00 | 0.00 | 0.00 |
December | 155.95 | 95.12 | 60.82 | 137.55 | 220.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 271.83 | 157.07 | 114.76 | 337.55 | 110.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 155.95 | 92.11 | 60.82 | 137.55 | 18.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 370.16 | 228.00 | 154.83 | 527.58 | 220.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.26 | 0.00 | 40.26 | 6.59 | 170.94 | 0.00 | 0.00 | 0.00 |
February | 50.32 | 0.00 | 50.32 | 16.80 | 152.20 | 0.00 | 0.00 | 0.00 |
March | 63.49 | 0.00 | 63.48 | 40.26 | 116.30 | 0.00 | 0.00 | 0.00 |
April | 80.97 | 1.08 | 79.89 | 69.13 | 73.43 | 0.00 | 0.00 | 0.00 |
May | 87.64 | 5.69 | 81.95 | 96.67 | 50.35 | 0.00 | 0.00 | 0.00 |
June | 99.79 | 16.59 | 83.19 | 150.28 | 30.72 | 0.00 | 0.00 | 0.00 |
July | 91.50 | 7.80 | 83.70 | 150.15 | 18.35 | 0.00 | 0.00 | 0.00 |
August | 84.92 | 2.08 | 82.84 | 125.93 | 22.44 | 0.00 | 0.00 | 0.00 |
September | 67.79 | 0.05 | 67.74 | 84.33 | 45.94 | 0.00 | 0.00 | 0.00 |
October | 50.54 | 0.00 | 50.54 | 36.93 | 90.27 | 0.00 | 0.00 | 0.00 |
November | 42.92 | 0.00 | 42.92 | 11.30 | 134.21 | 0.00 | 0.00 | 0.00 |
December | 34.27 | 0.00 | 34.27 | 1.67 | 178.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.26 | 2.78 | 63.48 | 66.10 | 89.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.27 | 0.00 | 34.27 | 1.67 | 18.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 99.79 | 16.59 | 83.70 | 150.28 | 178.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.84 | 0.00 | 14.84 | 2.43 | 63.02 | 0.00 | 0.00 | 0.00 |
February | 18.55 | 0.00 | 18.55 | 6.19 | 56.11 | 0.00 | 0.00 | 0.00 |
March | 23.40 | 0.00 | 23.40 | 14.84 | 42.87 | 0.00 | 0.00 | 0.00 |
April | 29.85 | 0.40 | 29.45 | 25.48 | 27.07 | 0.00 | 0.00 | 0.00 |
May | 32.31 | 2.10 | 30.21 | 35.64 | 18.56 | 0.00 | 0.00 | 0.00 |
June | 36.79 | 6.12 | 30.67 | 55.40 | 11.32 | 0.00 | 0.00 | 0.00 |
July | 33.73 | 2.88 | 30.86 | 55.35 | 6.77 | 0.00 | 0.00 | 0.00 |
August | 31.30 | 0.77 | 30.54 | 46.42 | 8.27 | 0.00 | 0.00 | 0.00 |
September | 24.99 | 0.02 | 24.97 | 31.09 | 16.94 | 0.00 | 0.00 | 0.00 |
October | 18.63 | 0.00 | 18.63 | 13.61 | 33.28 | 0.00 | 0.00 | 0.00 |
November | 15.82 | 0.00 | 15.82 | 4.16 | 49.48 | 0.00 | 0.00 | 0.00 |
December | 12.63 | 0.00 | 12.63 | 0.62 | 65.71 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 24.43 | 1.02 | 23.40 | 24.37 | 33.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 12.63 | 0.00 | 12.63 | 0.62 | 6.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 36.79 | 6.12 | 30.86 | 55.40 | 65.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 109.47 | 85.13 | 24.34 | 128.69 | 54.88 | 0.00 | 0.00 | 0.00 |
February | 107.91 | 78.97 | 28.93 | 129.61 | 50.43 | 0.00 | 0.00 | 0.00 |
March | 80.24 | 48.96 | 31.28 | 98.48 | 40.50 | 0.00 | 0.00 | 0.00 |
April | 61.62 | 25.25 | 36.37 | 78.93 | 27.90 | 0.00 | 0.00 | 0.00 |
May | 41.47 | 9.38 | 32.09 | 54.44 | 19.83 | 0.00 | 0.00 | 0.00 |
June | 34.67 | 4.16 | 30.51 | 54.51 | 12.33 | 0.00 | 0.00 | 0.00 |
July | 38.38 | 6.02 | 32.36 | 65.47 | 7.03 | 0.00 | 0.00 | 0.00 |
August | 52.21 | 16.47 | 35.74 | 83.60 | 8.67 | 0.00 | 0.00 | 0.00 |
September | 74.12 | 41.72 | 32.40 | 108.63 | 16.76 | 0.00 | 0.00 | 0.00 |
October | 99.85 | 73.45 | 26.40 | 131.12 | 30.22 | 0.00 | 0.00 | 0.00 |
November | 112.64 | 86.69 | 25.95 | 136.50 | 43.52 | 0.00 | 0.00 | 0.00 |
December | 119.38 | 98.55 | 20.83 | 141.47 | 55.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 77.49 | 47.73 | 29.76 | 100.79 | 30.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.67 | 4.16 | 20.83 | 54.44 | 7.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 119.38 | 98.55 | 36.37 | 141.47 | 55.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 297.13 | 231.07 | 66.06 | 349.30 | 148.96 | 0.00 | 0.00 | 0.00 |
February | 292.88 | 214.35 | 78.53 | 351.78 | 136.88 | 0.00 | 0.00 | 0.00 |
March | 217.79 | 132.89 | 84.89 | 267.30 | 109.93 | 0.00 | 0.00 | 0.00 |
April | 167.26 | 68.55 | 98.72 | 214.23 | 75.74 | 0.00 | 0.00 | 0.00 |
May | 112.57 | 25.47 | 87.10 | 147.77 | 53.83 | 0.00 | 0.00 | 0.00 |
June | 94.10 | 11.30 | 82.80 | 147.94 | 33.47 | 0.00 | 0.00 | 0.00 |
July | 104.17 | 16.34 | 87.82 | 177.69 | 19.09 | 0.00 | 0.00 | 0.00 |
August | 141.70 | 44.69 | 97.01 | 226.91 | 23.53 | 0.00 | 0.00 | 0.00 |
September | 201.16 | 113.24 | 87.93 | 294.84 | 45.50 | 0.00 | 0.00 | 0.00 |
October | 271.02 | 199.35 | 71.66 | 355.88 | 82.02 | 0.00 | 0.00 | 0.00 |
November | 305.72 | 235.28 | 70.43 | 370.50 | 118.13 | 0.00 | 0.00 | 0.00 |
December | 324.02 | 267.48 | 56.55 | 383.97 | 151.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 210.32 | 129.56 | 80.77 | 273.56 | 82.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 94.10 | 11.30 | 56.55 | 147.77 | 19.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 324.02 | 267.48 | 98.72 | 383.97 | 151.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 234.62 | 182.45 | 52.16 | 273.67 | 111.94 | 0.00 | 0.00 | 0.00 |
February | 231.27 | 169.26 | 62.01 | 274.47 | 102.88 | 0.00 | 0.00 | 0.00 |
March | 171.97 | 104.94 | 67.03 | 208.69 | 80.86 | 0.00 | 0.00 | 0.00 |
April | 132.07 | 54.12 | 77.95 | 166.99 | 53.27 | 0.00 | 0.00 | 0.00 |
May | 88.89 | 20.11 | 68.78 | 116.06 | 35.43 | 0.00 | 0.00 | 0.00 |
June | 74.31 | 8.92 | 65.38 | 117.57 | 20.05 | 0.00 | 0.00 | 0.00 |
July | 82.25 | 12.91 | 69.35 | 142.21 | 8.96 | 0.00 | 0.00 | 0.00 |
August | 111.89 | 35.29 | 76.60 | 180.18 | 11.85 | 0.00 | 0.00 | 0.00 |
September | 158.84 | 89.41 | 69.43 | 232.41 | 27.45 | 0.00 | 0.00 | 0.00 |
October | 214.00 | 157.41 | 56.59 | 280.28 | 56.29 | 0.00 | 0.00 | 0.00 |
November | 241.40 | 185.78 | 55.61 | 290.65 | 86.24 | 0.00 | 0.00 | 0.00 |
December | 255.85 | 211.20 | 44.65 | 300.56 | 113.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 166.08 | 102.30 | 63.77 | 214.97 | 58.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 74.31 | 8.92 | 44.65 | 116.06 | 8.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 255.85 | 211.20 | 77.95 | 300.56 | 113.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 169.72 | 96.79 | 72.93 | 158.18 | 229.53 | 0.00 | 0.00 | 0.00 |
February | 218.05 | 125.81 | 92.23 | 218.95 | 206.29 | 0.00 | 0.00 | 0.00 |
March | 243.30 | 129.24 | 114.06 | 263.94 | 155.92 | 0.00 | 0.00 | 0.00 |
April | 311.27 | 165.66 | 145.61 | 368.95 | 97.05 | 0.00 | 0.00 | 0.00 |
May | 296.00 | 152.94 | 143.06 | 377.81 | 64.91 | 0.00 | 0.00 | 0.00 |
June | 315.40 | 175.65 | 139.75 | 457.82 | 37.41 | 0.00 | 0.00 | 0.00 |
July | 284.77 | 139.15 | 145.62 | 437.07 | 16.72 | 0.00 | 0.00 | 0.00 |
August | 291.29 | 134.53 | 156.75 | 428.25 | 22.14 | 0.00 | 0.00 | 0.00 |
September | 264.29 | 139.54 | 124.75 | 362.34 | 51.68 | 0.00 | 0.00 | 0.00 |
October | 241.87 | 150.65 | 91.21 | 291.31 | 112.97 | 0.00 | 0.00 | 0.00 |
November | 189.00 | 111.18 | 77.82 | 188.24 | 174.70 | 0.00 | 0.00 | 0.00 |
December | 162.29 | 101.34 | 60.95 | 147.60 | 235.71 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 248.96 | 135.15 | 113.81 | 308.71 | 116.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 162.29 | 96.79 | 60.95 | 147.60 | 16.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 315.40 | 175.65 | 156.75 | 457.82 | 235.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 31.79 | 0.00 | 31.79 | 7.52 | 124.29 | 0.00 | 0.00 | 0.00 |
February | 39.73 | 0.00 | 39.73 | 14.86 | 111.78 | 0.00 | 0.00 | 0.00 |
March | 50.13 | 0.00 | 50.13 | 32.29 | 85.20 | 0.00 | 0.00 | 0.00 |
April | 63.94 | 0.86 | 63.08 | 53.32 | 53.73 | 0.00 | 0.00 | 0.00 |
May | 69.21 | 4.50 | 64.71 | 75.48 | 35.31 | 0.00 | 0.00 | 0.00 |
June | 78.79 | 13.10 | 65.69 | 118.00 | 19.90 | 0.00 | 0.00 | 0.00 |
July | 72.25 | 6.16 | 66.09 | 119.21 | 9.57 | 0.00 | 0.00 | 0.00 |
August | 67.05 | 1.64 | 65.41 | 100.21 | 12.68 | 0.00 | 0.00 | 0.00 |
September | 53.53 | 0.04 | 53.49 | 67.56 | 29.76 | 0.00 | 0.00 | 0.00 |
October | 39.90 | 0.00 | 39.90 | 30.92 | 62.87 | 0.00 | 0.00 | 0.00 |
November | 33.89 | 0.00 | 33.89 | 11.24 | 94.41 | 0.00 | 0.00 | 0.00 |
December | 27.06 | 0.00 | 27.06 | 2.48 | 128.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 52.32 | 2.19 | 50.12 | 52.96 | 63.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 27.06 | 0.00 | 27.06 | 2.48 | 9.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 78.79 | 13.10 | 66.09 | 119.21 | 128.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 169.72 | 96.79 | 72.93 | 165.98 | 224.14 | 0.00 | 0.00 | 0.00 |
February | 218.05 | 125.81 | 92.23 | 226.56 | 201.86 | 0.00 | 0.00 | 0.00 |
March | 243.30 | 129.24 | 114.06 | 267.75 | 154.80 | 0.00 | 0.00 | 0.00 |
April | 311.27 | 165.66 | 145.61 | 368.93 | 100.77 | 0.00 | 0.00 | 0.00 |
May | 296.00 | 152.94 | 143.06 | 376.24 | 68.86 | 0.00 | 0.00 | 0.00 |
June | 315.40 | 175.65 | 139.75 | 454.50 | 39.69 | 0.00 | 0.00 | 0.00 |
July | 284.77 | 139.15 | 145.62 | 434.24 | 18.40 | 0.00 | 0.00 | 0.00 |
August | 291.29 | 134.53 | 156.75 | 426.64 | 24.58 | 0.00 | 0.00 | 0.00 |
September | 264.29 | 139.54 | 124.75 | 364.08 | 55.47 | 0.00 | 0.00 | 0.00 |
October | 241.87 | 150.65 | 91.21 | 295.05 | 114.40 | 0.00 | 0.00 | 0.00 |
November | 189.00 | 111.18 | 77.82 | 195.59 | 169.72 | 0.00 | 0.00 | 0.00 |
December | 162.29 | 101.34 | 60.95 | 155.39 | 228.71 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 248.96 | 135.15 | 113.81 | 311.22 | 116.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 162.29 | 96.79 | 60.95 | 155.39 | 18.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 315.40 | 175.65 | 156.75 | 454.50 | 228.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 344.09 | 267.59 | 76.50 | 394.10 | 170.41 | 0.00 | 0.00 | 0.00 |
February | 339.17 | 248.23 | 90.95 | 396.61 | 155.69 | 0.00 | 0.00 | 0.00 |
March | 252.21 | 153.90 | 98.31 | 302.89 | 120.63 | 0.00 | 0.00 | 0.00 |
April | 193.70 | 79.38 | 114.32 | 245.30 | 77.16 | 0.00 | 0.00 | 0.00 |
May | 130.36 | 29.49 | 100.87 | 172.80 | 50.42 | 0.00 | 0.00 | 0.00 |
June | 108.98 | 13.09 | 95.89 | 178.29 | 27.63 | 0.00 | 0.00 | 0.00 |
July | 120.63 | 18.93 | 101.70 | 213.87 | 11.90 | 0.00 | 0.00 | 0.00 |
August | 164.10 | 51.76 | 112.34 | 268.09 | 16.13 | 0.00 | 0.00 | 0.00 |
September | 232.96 | 131.13 | 101.82 | 341.35 | 39.50 | 0.00 | 0.00 | 0.00 |
October | 313.85 | 230.86 | 82.99 | 407.95 | 84.07 | 0.00 | 0.00 | 0.00 |
November | 354.03 | 272.47 | 81.56 | 420.23 | 131.06 | 0.00 | 0.00 | 0.00 |
December | 375.23 | 309.75 | 65.48 | 433.27 | 174.02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 243.57 | 150.04 | 93.53 | 314.09 | 87.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 108.98 | 13.09 | 65.48 | 172.80 | 11.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 375.23 | 309.75 | 114.32 | 433.27 | 174.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 222.53 | 0.00 | 222.53 | 23.02 | 1035.55 | 0.00 | 0.00 | 0.00 |
February | 278.13 | 0.00 | 278.13 | 69.47 | 925.33 | 0.00 | 0.00 | 0.00 |
March | 350.89 | 0.01 | 350.88 | 188.60 | 702.21 | 0.00 | 0.00 | 0.00 |
April | 447.55 | 6.00 | 441.55 | 345.89 | 434.95 | 0.00 | 0.00 | 0.00 |
May | 484.42 | 31.47 | 452.95 | 498.24 | 295.81 | 0.00 | 0.00 | 0.00 |
June | 551.53 | 91.72 | 459.81 | 807.91 | 178.03 | 0.00 | 0.00 | 0.00 |
July | 505.75 | 43.11 | 462.64 | 815.88 | 105.93 | 0.00 | 0.00 | 0.00 |
August | 469.36 | 11.49 | 457.87 | 683.09 | 128.01 | 0.00 | 0.00 | 0.00 |
September | 374.68 | 0.27 | 374.42 | 453.56 | 257.03 | 0.00 | 0.00 | 0.00 |
October | 279.31 | 0.00 | 279.31 | 191.28 | 519.75 | 0.00 | 0.00 | 0.00 |
November | 237.20 | 0.00 | 237.20 | 47.76 | 801.95 | 0.00 | 0.00 | 0.00 |
December | 189.41 | 0.00 | 189.41 | 4.19 | 1085.65 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 366.21 | 15.36 | 350.85 | 345.57 | 537.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 189.41 | 0.00 | 189.41 | 4.19 | 105.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 551.53 | 91.72 | 462.64 | 815.88 | 1085.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 222.53 | 0.00 | 222.53 | 19.16 | 1058.55 | 0.00 | 0.00 | 0.00 |
February | 278.13 | 0.00 | 278.13 | 63.44 | 944.24 | 0.00 | 0.00 | 0.00 |
March | 350.89 | 0.01 | 350.88 | 180.55 | 715.72 | 0.00 | 0.00 | 0.00 |
April | 447.55 | 6.00 | 441.55 | 338.00 | 443.83 | 0.00 | 0.00 | 0.00 |
May | 484.42 | 31.47 | 452.95 | 490.27 | 302.44 | 0.00 | 0.00 | 0.00 |
June | 551.53 | 91.72 | 459.81 | 800.43 | 182.80 | 0.00 | 0.00 | 0.00 |
July | 505.75 | 43.11 | 462.64 | 808.77 | 110.16 | 0.00 | 0.00 | 0.00 |
August | 469.36 | 11.49 | 457.87 | 676.27 | 132.73 | 0.00 | 0.00 | 0.00 |
September | 374.68 | 0.27 | 374.42 | 447.91 | 263.69 | 0.00 | 0.00 | 0.00 |
October | 279.31 | 0.00 | 279.31 | 185.79 | 530.75 | 0.00 | 0.00 | 0.00 |
November | 237.20 | 0.00 | 237.20 | 42.94 | 819.56 | 0.00 | 0.00 | 0.00 |
December | 189.41 | 0.00 | 189.41 | 3.16 | 1111.87 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 366.21 | 15.36 | 350.85 | 339.55 | 549.49 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 189.41 | 0.00 | 189.41 | 3.16 | 110.16 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 551.53 | 91.72 | 462.64 | 808.77 | 1111.87 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 31.79 | 0.00 | 31.79 | 9.03 | 129.67 | 0.00 | 0.00 | 0.00 |
February | 39.73 | 0.00 | 39.73 | 18.30 | 117.39 | 0.00 | 0.00 | 0.00 |
March | 50.13 | 0.00 | 50.13 | 40.07 | 90.52 | 0.00 | 0.00 | 0.00 |
April | 63.94 | 0.86 | 63.08 | 68.56 | 57.14 | 0.00 | 0.00 | 0.00 |
May | 69.21 | 4.50 | 64.71 | 94.32 | 40.07 | 0.00 | 0.00 | 0.00 |
June | 78.79 | 13.10 | 65.69 | 142.44 | 25.11 | 0.00 | 0.00 | 0.00 |
July | 72.25 | 6.16 | 66.09 | 144.65 | 15.33 | 0.00 | 0.00 | 0.00 |
August | 67.05 | 1.64 | 65.41 | 124.91 | 17.98 | 0.00 | 0.00 | 0.00 |
September | 53.53 | 0.04 | 53.49 | 87.36 | 32.24 | 0.00 | 0.00 | 0.00 |
October | 39.90 | 0.00 | 39.90 | 42.44 | 64.34 | 0.00 | 0.00 | 0.00 |
November | 33.89 | 0.00 | 33.89 | 14.59 | 98.36 | 0.00 | 0.00 | 0.00 |
December | 27.06 | 0.00 | 27.06 | 3.18 | 133.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 52.32 | 2.19 | 50.12 | 66.08 | 68.26 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 27.06 | 0.00 | 27.06 | 3.18 | 15.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 78.79 | 13.10 | 66.09 | 144.65 | 133.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 329.12 | 184.21 | 144.91 | 304.58 | 445.84 | 0.00 | 0.00 | 0.00 |
February | 398.57 | 214.25 | 184.32 | 406.88 | 406.42 | 0.00 | 0.00 | 0.00 |
March | 529.66 | 301.74 | 227.91 | 619.91 | 314.30 | 0.00 | 0.00 | 0.00 |
April | 718.50 | 408.87 | 309.63 | 939.19 | 207.07 | 0.00 | 0.00 | 0.00 |
May | 686.42 | 390.98 | 295.44 | 961.28 | 150.45 | 0.00 | 0.00 | 0.00 |
June | 740.27 | 455.98 | 284.29 | 1153.68 | 94.09 | 0.00 | 0.00 | 0.00 |
July | 684.63 | 391.38 | 293.26 | 1131.16 | 57.46 | 0.00 | 0.00 | 0.00 |
August | 677.61 | 373.49 | 304.12 | 1080.86 | 67.59 | 0.00 | 0.00 | 0.00 |
September | 565.05 | 316.17 | 248.88 | 854.38 | 118.24 | 0.00 | 0.00 | 0.00 |
October | 492.29 | 312.61 | 179.68 | 644.25 | 225.20 | 0.00 | 0.00 | 0.00 |
November | 382.88 | 224.61 | 158.27 | 406.07 | 343.19 | 0.00 | 0.00 | 0.00 |
December | 311.87 | 190.23 | 121.64 | 288.84 | 462.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 543.62 | 314.11 | 229.50 | 734.11 | 240.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 311.87 | 184.21 | 121.64 | 288.84 | 57.46 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 740.27 | 455.98 | 309.63 | 1153.68 | 462.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 234.62 | 182.45 | 52.16 | 285.41 | 116.41 | 0.00 | 0.00 | 0.00 |
February | 231.27 | 169.26 | 62.01 | 287.60 | 107.42 | 0.00 | 0.00 | 0.00 |
March | 171.97 | 104.94 | 67.03 | 221.94 | 86.30 | 0.00 | 0.00 | 0.00 |
April | 132.07 | 54.12 | 77.95 | 183.53 | 58.72 | 0.00 | 0.00 | 0.00 |
May | 88.89 | 20.11 | 68.78 | 134.03 | 41.87 | 0.00 | 0.00 | 0.00 |
June | 74.31 | 8.92 | 65.38 | 139.47 | 26.43 | 0.00 | 0.00 | 0.00 |
July | 82.25 | 12.91 | 69.35 | 165.89 | 15.47 | 0.00 | 0.00 | 0.00 |
August | 111.89 | 35.29 | 76.60 | 204.32 | 18.34 | 0.00 | 0.00 | 0.00 |
September | 158.84 | 89.41 | 69.43 | 254.46 | 32.19 | 0.00 | 0.00 | 0.00 |
October | 214.00 | 157.41 | 56.59 | 298.45 | 60.19 | 0.00 | 0.00 | 0.00 |
November | 241.40 | 185.78 | 55.61 | 304.56 | 89.79 | 0.00 | 0.00 | 0.00 |
December | 255.85 | 211.20 | 44.65 | 312.40 | 117.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 166.08 | 102.30 | 63.77 | 232.35 | 64.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 74.31 | 8.92 | 44.65 | 134.03 | 15.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 255.85 | 211.20 | 77.95 | 312.40 | 117.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.26 | 0.00 | 40.26 | 5.51 | 172.00 | 0.00 | 0.00 | 0.00 |
February | 50.32 | 0.00 | 50.32 | 14.75 | 153.57 | 0.00 | 0.00 | 0.00 |
March | 63.49 | 0.00 | 63.48 | 37.86 | 116.58 | 0.00 | 0.00 | 0.00 |
April | 80.97 | 1.08 | 79.89 | 65.75 | 73.78 | 0.00 | 0.00 | 0.00 |
May | 87.64 | 5.69 | 81.95 | 92.74 | 51.31 | 0.00 | 0.00 | 0.00 |
June | 99.79 | 16.59 | 83.19 | 146.36 | 31.89 | 0.00 | 0.00 | 0.00 |
July | 91.50 | 7.80 | 83.70 | 146.44 | 19.52 | 0.00 | 0.00 | 0.00 |
August | 84.92 | 2.08 | 82.84 | 122.46 | 23.62 | 0.00 | 0.00 | 0.00 |
September | 67.79 | 0.05 | 67.74 | 81.49 | 46.65 | 0.00 | 0.00 | 0.00 |
October | 50.54 | 0.00 | 50.54 | 34.82 | 89.76 | 0.00 | 0.00 | 0.00 |
November | 42.92 | 0.00 | 42.92 | 10.00 | 133.74 | 0.00 | 0.00 | 0.00 |
December | 34.27 | 0.00 | 34.27 | 1.18 | 180.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.26 | 2.78 | 63.48 | 63.54 | 90.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.27 | 0.00 | 34.27 | 1.18 | 19.52 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 99.79 | 16.59 | 83.70 | 146.44 | 180.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 36.02 | 0.00 | 36.02 | 4.93 | 153.87 | 0.00 | 0.00 | 0.00 |
February | 45.02 | 0.00 | 45.02 | 13.20 | 137.40 | 0.00 | 0.00 | 0.00 |
March | 56.80 | 0.00 | 56.80 | 33.87 | 104.31 | 0.00 | 0.00 | 0.00 |
April | 72.45 | 0.97 | 71.48 | 58.83 | 66.01 | 0.00 | 0.00 | 0.00 |
May | 78.42 | 5.09 | 73.32 | 82.97 | 45.90 | 0.00 | 0.00 | 0.00 |
June | 89.28 | 14.85 | 74.43 | 130.95 | 28.53 | 0.00 | 0.00 | 0.00 |
July | 81.87 | 6.98 | 74.89 | 131.02 | 17.47 | 0.00 | 0.00 | 0.00 |
August | 75.98 | 1.86 | 74.12 | 109.57 | 21.14 | 0.00 | 0.00 | 0.00 |
September | 60.65 | 0.04 | 60.61 | 72.91 | 41.74 | 0.00 | 0.00 | 0.00 |
October | 45.21 | 0.00 | 45.21 | 31.15 | 80.31 | 0.00 | 0.00 | 0.00 |
November | 38.40 | 0.00 | 38.40 | 8.95 | 119.65 | 0.00 | 0.00 | 0.00 |
December | 30.66 | 0.00 | 30.66 | 1.06 | 161.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 59.28 | 2.49 | 56.79 | 56.85 | 81.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 0.00 | 30.66 | 1.06 | 17.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.28 | 14.85 | 74.89 | 131.02 | 161.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 875.90 | 681.16 | 194.74 | 1019.32 | 439.75 | 0.00 | 0.00 | 0.00 |
February | 863.39 | 631.88 | 231.51 | 1024.66 | 405.47 | 0.00 | 0.00 | 0.00 |
March | 642.01 | 391.76 | 250.25 | 776.80 | 325.07 | 0.00 | 0.00 | 0.00 |
April | 493.07 | 202.06 | 291.00 | 618.81 | 224.84 | 0.00 | 0.00 | 0.00 |
May | 331.84 | 75.07 | 256.77 | 422.82 | 161.93 | 0.00 | 0.00 | 0.00 |
June | 277.41 | 33.31 | 244.10 | 424.66 | 102.26 | 0.00 | 0.00 | 0.00 |
July | 307.07 | 48.18 | 258.89 | 512.15 | 59.99 | 0.00 | 0.00 | 0.00 |
August | 417.72 | 131.75 | 285.97 | 656.99 | 73.16 | 0.00 | 0.00 | 0.00 |
September | 593.01 | 333.81 | 259.20 | 857.62 | 136.53 | 0.00 | 0.00 | 0.00 |
October | 798.93 | 587.67 | 211.25 | 1039.39 | 240.64 | 0.00 | 0.00 | 0.00 |
November | 901.21 | 693.59 | 207.62 | 1083.43 | 345.76 | 0.00 | 0.00 | 0.00 |
December | 955.18 | 788.49 | 166.69 | 1121.36 | 447.76 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 620.01 | 381.92 | 238.09 | 795.18 | 246.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 277.41 | 33.31 | 166.69 | 422.82 | 59.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 955.18 | 788.49 | 291.00 | 1121.36 | 447.76 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.317828E+10 | 0.247164E+10 | 0.706641E+09 | 0.366398E+10 | 0.154513E+10 |
February | 0.282969E+10 | 0.207095E+10 | 0.758744E+09 | 0.332794E+10 | 0.128690E+10 |
March | 0.232958E+10 | 0.142153E+10 | 0.908056E+09 | 0.281188E+10 | 0.112997E+10 |
April | 0.173141E+10 | 0.709555E+09 | 0.102185E+10 | 0.217373E+10 | 0.760176E+09 |
May | 0.120409E+10 | 0.272398E+09 | 0.931695E+09 | 0.154758E+10 | 0.553581E+09 |
June | 0.974117E+09 | 0.116970E+09 | 0.857147E+09 | 0.147363E+10 | 0.344941E+09 |
July | 0.111423E+10 | 0.174830E+09 | 0.939397E+09 | 0.182853E+10 | 0.219697E+09 |
August | 0.151573E+10 | 0.478055E+09 | 0.103767E+10 | 0.235967E+10 | 0.268245E+09 |
September | 0.208236E+10 | 0.117218E+10 | 0.910172E+09 | 0.299509E+10 | 0.475461E+09 |
October | 0.289897E+10 | 0.213243E+10 | 0.766540E+09 | 0.373885E+10 | 0.858722E+09 |
November | 0.316463E+10 | 0.243556E+10 | 0.729074E+09 | 0.375916E+10 | 0.119334E+10 |
December | 0.346594E+10 | 0.286110E+10 | 0.604848E+09 | 0.401447E+10 | 0.158510E+10 |
Annual Sum or Average | 0.264890E+11 | 0.163172E+11 | 0.101718E+11 | 0.336945E+11 | 0.102213E+11 |
Minimum of Months | 0.974117E+09 | 0.116970E+09 | 0.604848E+09 | 0.147363E+10 | 0.219697E+09 |
Maximum of Months | 0.346594E+10 | 0.286110E+10 | 0.103767E+10 | 0.401447E+10 | 0.158510E+10 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.894982E+10 | 0.695996E+10 | 0.198985E+10 | 0.102030E+11 | 0.463158E+10 |
February | 0.796823E+10 | 0.583165E+10 | 0.213657E+10 | 0.926816E+10 | 0.386777E+10 |
March | 0.655995E+10 | 0.400293E+10 | 0.255702E+10 | 0.779972E+10 | 0.343493E+10 |
April | 0.487553E+10 | 0.199806E+10 | 0.287747E+10 | 0.602198E+10 | 0.230269E+10 |
May | 0.339065E+10 | 0.767054E+09 | 0.262359E+10 | 0.426106E+10 | 0.168696E+10 |
June | 0.274305E+10 | 0.329380E+09 | 0.241367E+10 | 0.409203E+10 | 0.102323E+10 |
July | 0.313759E+10 | 0.492310E+09 | 0.264528E+10 | 0.510868E+10 | 0.631000E+09 |
August | 0.426819E+10 | 0.134617E+10 | 0.292202E+10 | 0.660173E+10 | 0.768701E+09 |
September | 0.586378E+10 | 0.330079E+10 | 0.256298E+10 | 0.837795E+10 | 0.138182E+10 |
October | 0.816330E+10 | 0.600478E+10 | 0.215853E+10 | 0.104497E+11 | 0.254097E+10 |
November | 0.891139E+10 | 0.685837E+10 | 0.205302E+10 | 0.104827E+11 | 0.358902E+10 |
December | 0.975987E+10 | 0.805665E+10 | 0.170321E+10 | 0.112009E+11 | 0.475776E+10 |
Annual Sum or Average | 0.745913E+11 | 0.459481E+11 | 0.286432E+11 | 0.938676E+11 | 0.306164E+11 |
Minimum of Months | 0.274305E+10 | 0.329380E+09 | 0.170321E+10 | 0.409203E+10 | 0.631000E+09 |
Maximum of Months | 0.975987E+10 | 0.805665E+10 | 0.292202E+10 | 0.112009E+11 | 0.475776E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.116263E+11 | 0.904139E+10 | 0.258493E+10 | 0.134581E+11 | 0.616529E+10 |
February | 0.103512E+11 | 0.757565E+10 | 0.277553E+10 | 0.122464E+11 | 0.513662E+10 |
March | 0.852175E+10 | 0.520003E+10 | 0.332172E+10 | 0.103148E+11 | 0.456427E+10 |
April | 0.633359E+10 | 0.259559E+10 | 0.373800E+10 | 0.800738E+10 | 0.304861E+10 |
May | 0.440464E+10 | 0.996447E+09 | 0.340819E+10 | 0.567499E+10 | 0.224331E+10 |
June | 0.356338E+10 | 0.427884E+09 | 0.313549E+10 | 0.546401E+10 | 0.135758E+10 |
July | 0.407591E+10 | 0.639539E+09 | 0.343637E+10 | 0.682574E+10 | 0.822170E+09 |
August | 0.554462E+10 | 0.174875E+10 | 0.379587E+10 | 0.878753E+10 | 0.993251E+09 |
September | 0.761738E+10 | 0.428792E+10 | 0.332946E+10 | 0.111016E+11 | 0.179250E+10 |
October | 0.106046E+11 | 0.780055E+10 | 0.280405E+10 | 0.138101E+11 | 0.333646E+10 |
November | 0.115764E+11 | 0.890941E+10 | 0.266700E+10 | 0.138365E+11 | 0.474444E+10 |
December | 0.126786E+11 | 0.104661E+11 | 0.221257E+10 | 0.147761E+11 | 0.632613E+10 |
Annual Sum or Average | 0.968984E+11 | 0.596892E+11 | 0.372092E+11 | 0.124303E+12 | 0.405306E+11 |
Minimum of Months | 0.356338E+10 | 0.427884E+09 | 0.221257E+10 | 0.546401E+10 | 0.822170E+09 |
Maximum of Months | 0.126786E+11 | 0.104661E+11 | 0.379587E+10 | 0.147761E+11 | 0.632613E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.628401E+09 | 0.488685E+09 | 0.139716E+09 | 0.735259E+09 | 0.301849E+09 |
February | 0.559480E+09 | 0.409462E+09 | 0.150018E+09 | 0.666885E+09 | 0.250348E+09 |
March | 0.460600E+09 | 0.281060E+09 | 0.179540E+09 | 0.561903E+09 | 0.218345E+09 |
April | 0.342331E+09 | 0.140291E+09 | 0.202040E+09 | 0.436143E+09 | 0.139896E+09 |
May | 0.238072E+09 | 53857719.31 | 0.184215E+09 | 0.313475E+09 | 96776096.39 |
June | 0.192602E+09 | 23127003.62 | 0.169475E+09 | 0.306844E+09 | 53429909.92 |
July | 0.220305E+09 | 34566908.48 | 0.185738E+09 | 0.383368E+09 | 25372800.27 |
August | 0.299688E+09 | 94519723.41 | 0.205168E+09 | 0.485842E+09 | 33165378.19 |
September | 0.411720E+09 | 0.231761E+09 | 0.179959E+09 | 0.605931E+09 | 73090567.19 |
October | 0.573177E+09 | 0.421618E+09 | 0.151560E+09 | 0.753361E+09 | 0.153170E+09 |
November | 0.625703E+09 | 0.481552E+09 | 0.144152E+09 | 0.755493E+09 | 0.226224E+09 |
December | 0.685278E+09 | 0.565688E+09 | 0.119590E+09 | 0.806990E+09 | 0.307662E+09 |
Annual Sum or Average | 0.523736E+10 | 0.322619E+10 | 0.201117E+10 | 0.681149E+10 | 0.187933E+10 |
Minimum of Months | 0.192602E+09 | 23127003.62 | 0.119590E+09 | 0.306844E+09 | 25372800.27 |
Maximum of Months | 0.685278E+09 | 0.565688E+09 | 0.205168E+09 | 0.806990E+09 | 0.307662E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.454587E+09 | 0.259253E+09 | 0.195335E+09 | 0.426151E+09 | 0.620057E+09 |
February | 0.527495E+09 | 0.304370E+09 | 0.223125E+09 | 0.533893E+09 | 0.502342E+09 |
March | 0.651650E+09 | 0.346153E+09 | 0.305497E+09 | 0.711960E+09 | 0.421693E+09 |
April | 0.806811E+09 | 0.429395E+09 | 0.377416E+09 | 0.963598E+09 | 0.255301E+09 |
May | 0.792803E+09 | 0.409630E+09 | 0.383173E+09 | 0.101896E+10 | 0.177369E+09 |
June | 0.817524E+09 | 0.455297E+09 | 0.362227E+09 | 0.119349E+10 | 99549939.67 |
July | 0.762720E+09 | 0.372697E+09 | 0.390023E+09 | 0.117726E+10 | 47328572.21 |
August | 0.780187E+09 | 0.360335E+09 | 0.419852E+09 | 0.115362E+10 | 61921750.90 |
September | 0.685042E+09 | 0.361685E+09 | 0.323357E+09 | 0.944537E+09 | 0.137643E+09 |
October | 0.647817E+09 | 0.403510E+09 | 0.244307E+09 | 0.784267E+09 | 0.308199E+09 |
November | 0.489878E+09 | 0.288175E+09 | 0.201704E+09 | 0.490722E+09 | 0.459349E+09 |
December | 0.434675E+09 | 0.271434E+09 | 0.163241E+09 | 0.397860E+09 | 0.637692E+09 |
Annual Sum or Average | 0.785119E+10 | 0.426193E+10 | 0.358926E+10 | 0.979631E+10 | 0.372845E+10 |
Minimum of Months | 0.434675E+09 | 0.259253E+09 | 0.163241E+09 | 0.397860E+09 | 47328572.21 |
Maximum of Months | 0.817524E+09 | 0.455297E+09 | 0.419852E+09 | 0.119349E+10 | 0.637692E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 85149799.43 | 0.00 | 85149799.43 | 19184318.55 | 0.336194E+09 |
February | 96123964.78 | 0.00 | 96123964.78 | 35602829.83 | 0.272325E+09 |
March | 0.134266E+09 | 4667.24 | 0.134261E+09 | 86510317.74 | 0.229858E+09 |
April | 0.165726E+09 | 2219973.94 | 0.163506E+09 | 0.139821E+09 | 0.139684E+09 |
May | 0.185361E+09 | 12043444.04 | 0.173317E+09 | 0.204141E+09 | 95421838.44 |
June | 0.204232E+09 | 33964118.59 | 0.170267E+09 | 0.308080E+09 | 52226857.91 |
July | 0.193520E+09 | 16494758.22 | 0.177025E+09 | 0.321061E+09 | 26805236.52 |
August | 0.179595E+09 | 4395223.56 | 0.175200E+09 | 0.270027E+09 | 34984183.85 |
September | 0.138746E+09 | 98869.42 | 0.138647E+09 | 0.175949E+09 | 78833438.00 |
October | 0.106878E+09 | 0.00 | 0.106878E+09 | 82684501.27 | 0.170727E+09 |
November | 87836488.38 | 0.00 | 87836488.38 | 28201393.96 | 0.248804E+09 |
December | 72475366.39 | 0.00 | 72475366.39 | 6115326.77 | 0.348008E+09 |
Annual Sum or Average | 0.164991E+10 | 69221055.01 | 0.158069E+10 | 0.167738E+10 | 0.203387E+10 |
Minimum of Months | 72475366.39 | 0.00 | 72475366.39 | 6115326.77 | 26805236.52 |
Maximum of Months | 0.204232E+09 | 33964118.59 | 0.177025E+09 | 0.321061E+09 | 0.348008E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.454587E+09 | 0.259253E+09 | 0.195335E+09 | 0.444690E+09 | 0.606363E+09 |
February | 0.527495E+09 | 0.304370E+09 | 0.223125E+09 | 0.550404E+09 | 0.492239E+09 |
March | 0.651650E+09 | 0.346153E+09 | 0.305497E+09 | 0.721423E+09 | 0.418306E+09 |
April | 0.806811E+09 | 0.429395E+09 | 0.377416E+09 | 0.964265E+09 | 0.262612E+09 |
May | 0.792803E+09 | 0.409630E+09 | 0.383173E+09 | 0.101531E+10 | 0.186334E+09 |
June | 0.817524E+09 | 0.455297E+09 | 0.362227E+09 | 0.118515E+10 | 0.104578E+09 |
July | 0.762720E+09 | 0.372697E+09 | 0.390023E+09 | 0.116959E+10 | 51644084.61 |
August | 0.780187E+09 | 0.360335E+09 | 0.419852E+09 | 0.114907E+10 | 68021433.61 |
September | 0.685042E+09 | 0.361685E+09 | 0.323357E+09 | 0.948459E+09 | 0.147007E+09 |
October | 0.647817E+09 | 0.403510E+09 | 0.244307E+09 | 0.793284E+09 | 0.311109E+09 |
November | 0.489878E+09 | 0.288175E+09 | 0.201704E+09 | 0.507206E+09 | 0.447880E+09 |
December | 0.434675E+09 | 0.271434E+09 | 0.163241E+09 | 0.415985E+09 | 0.619600E+09 |
Annual Sum or Average | 0.785119E+10 | 0.426193E+10 | 0.358926E+10 | 0.986485E+10 | 0.371569E+10 |
Minimum of Months | 0.434675E+09 | 0.259253E+09 | 0.163241E+09 | 0.415985E+09 | 51644084.61 |
Maximum of Months | 0.817524E+09 | 0.455297E+09 | 0.419852E+09 | 0.118515E+10 | 0.619600E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.502621E+09 | 0.390870E+09 | 0.111751E+09 | 0.555359E+09 | 0.305970E+09 |
February | 0.447495E+09 | 0.327504E+09 | 0.119991E+09 | 0.504122E+09 | 0.258780E+09 |
March | 0.368407E+09 | 0.224804E+09 | 0.143603E+09 | 0.417317E+09 | 0.234837E+09 |
April | 0.273811E+09 | 0.112211E+09 | 0.161600E+09 | 0.318871E+09 | 0.162239E+09 |
May | 0.190420E+09 | 43077608.47 | 0.147342E+09 | 0.218714E+09 | 0.124535E+09 |
June | 0.154051E+09 | 18497924.16 | 0.135553E+09 | 0.212371E+09 | 79996659.62 |
July | 0.176209E+09 | 27648028.33 | 0.148561E+09 | 0.269618E+09 | 55180178.65 |
August | 0.239703E+09 | 75600743.78 | 0.164102E+09 | 0.353785E+09 | 64982624.52 |
September | 0.329310E+09 | 0.185372E+09 | 0.143938E+09 | 0.455159E+09 | 0.103931E+09 |
October | 0.458451E+09 | 0.337227E+09 | 0.121224E+09 | 0.571044E+09 | 0.176928E+09 |
November | 0.500463E+09 | 0.385165E+09 | 0.115298E+09 | 0.572605E+09 | 0.242021E+09 |
December | 0.548113E+09 | 0.452460E+09 | 95652933.86 | 0.613778E+09 | 0.315273E+09 |
Annual Sum or Average | 0.418905E+10 | 0.258044E+10 | 0.160862E+10 | 0.506274E+10 | 0.212467E+10 |
Minimum of Months | 0.154051E+09 | 18497924.16 | 95652933.86 | 0.212371E+09 | 55180178.65 |
Maximum of Months | 0.548113E+09 | 0.452460E+09 | 0.164102E+09 | 0.613778E+09 | 0.315273E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 68128869.22 | 0.00 | 68128869.22 | 14746806.60 | 0.274094E+09 |
February | 76909365.24 | 0.00 | 76909365.24 | 29593211.49 | 0.219784E+09 |
March | 0.107427E+09 | 3734.29 | 0.107423E+09 | 73685379.65 | 0.182144E+09 |
April | 0.132599E+09 | 1776214.57 | 0.130822E+09 | 0.120988E+09 | 0.106681E+09 |
May | 0.148308E+09 | 9636032.37 | 0.138672E+09 | 0.173447E+09 | 72262714.78 |
June | 0.163407E+09 | 27174896.58 | 0.136232E+09 | 0.259371E+09 | 38106919.20 |
July | 0.154837E+09 | 13197555.76 | 0.141639E+09 | 0.270365E+09 | 17836596.97 |
August | 0.143695E+09 | 3516644.93 | 0.140179E+09 | 0.229398E+09 | 23673546.47 |
September | 0.111011E+09 | 79106.02 | 0.110932E+09 | 0.150357E+09 | 57157165.36 |
October | 85513450.69 | 0.00 | 85513450.69 | 72496800.86 | 0.130488E+09 |
November | 70278505.29 | 0.00 | 70278505.29 | 23600175.29 | 0.199845E+09 |
December | 57987978.73 | 0.00 | 57987978.73 | 4354523.40 | 0.285035E+09 |
Annual Sum or Average | 0.132010E+10 | 55384184.52 | 0.126472E+10 | 0.142240E+10 | 0.160711E+10 |
Minimum of Months | 57987978.73 | 0.00 | 57987978.73 | 4354523.40 | 17836596.97 |
Maximum of Months | 0.163407E+09 | 27174896.58 | 0.141639E+09 | 0.270365E+09 | 0.285035E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.440793E+09 | 0.246716E+09 | 0.194077E+09 | 0.369256E+09 | 0.585068E+09 |
February | 0.482140E+09 | 0.259172E+09 | 0.222967E+09 | 0.448281E+09 | 0.475877E+09 |
March | 0.709366E+09 | 0.404124E+09 | 0.305242E+09 | 0.764232E+09 | 0.394582E+09 |
April | 0.931246E+09 | 0.529931E+09 | 0.401315E+09 | 0.112781E+10 | 0.240108E+09 |
May | 0.919320E+09 | 0.523637E+09 | 0.395684E+09 | 0.118946E+10 | 0.169585E+09 |
June | 0.959453E+09 | 0.590986E+09 | 0.368467E+09 | 0.138421E+10 | 91144968.78 |
July | 0.916926E+09 | 0.524167E+09 | 0.392759E+09 | 0.139341E+10 | 45308163.17 |
August | 0.907525E+09 | 0.500213E+09 | 0.407312E+09 | 0.132654E+10 | 58208575.27 |
September | 0.732353E+09 | 0.409787E+09 | 0.322566E+09 | 0.100116E+10 | 0.129354E+09 |
October | 0.659325E+09 | 0.418683E+09 | 0.240642E+09 | 0.778126E+09 | 0.285513E+09 |
November | 0.496245E+09 | 0.291116E+09 | 0.205129E+09 | 0.479064E+09 | 0.440111E+09 |
December | 0.417691E+09 | 0.254778E+09 | 0.162912E+09 | 0.356580E+09 | 0.618807E+09 |
Annual Sum or Average | 0.857238E+10 | 0.495331E+10 | 0.361907E+10 | 0.106181E+11 | 0.353367E+10 |
Minimum of Months | 0.417691E+09 | 0.246716E+09 | 0.162912E+09 | 0.356580E+09 | 45308163.17 |
Maximum of Months | 0.959453E+09 | 0.590986E+09 | 0.407312E+09 | 0.139341E+10 | 0.618807E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.628401E+09 | 0.488685E+09 | 0.139716E+09 | 0.733463E+09 | 0.300625E+09 |
February | 0.559480E+09 | 0.409462E+09 | 0.150018E+09 | 0.665093E+09 | 0.248656E+09 |
March | 0.460600E+09 | 0.281060E+09 | 0.179540E+09 | 0.557856E+09 | 0.217393E+09 |
April | 0.342331E+09 | 0.140291E+09 | 0.202040E+09 | 0.431507E+09 | 0.139364E+09 |
May | 0.238072E+09 | 53857719.31 | 0.184215E+09 | 0.308753E+09 | 96301608.32 |
June | 0.192602E+09 | 23127003.62 | 0.169475E+09 | 0.303262E+09 | 52465296.64 |
July | 0.220305E+09 | 34566908.48 | 0.185738E+09 | 0.380120E+09 | 25107689.45 |
August | 0.299688E+09 | 94519723.41 | 0.205168E+09 | 0.482967E+09 | 32688044.42 |
September | 0.411720E+09 | 0.231761E+09 | 0.179959E+09 | 0.603810E+09 | 72138621.25 |
October | 0.573177E+09 | 0.421618E+09 | 0.151560E+09 | 0.750933E+09 | 0.151754E+09 |
November | 0.625703E+09 | 0.481552E+09 | 0.144152E+09 | 0.753349E+09 | 0.224995E+09 |
December | 0.685278E+09 | 0.565688E+09 | 0.119590E+09 | 0.805020E+09 | 0.306507E+09 |
Annual Sum or Average | 0.523736E+10 | 0.322619E+10 | 0.201117E+10 | 0.677613E+10 | 0.186799E+10 |
Minimum of Months | 0.192602E+09 | 23127003.62 | 0.119590E+09 | 0.303262E+09 | 25107689.45 |
Maximum of Months | 0.685278E+09 | 0.565688E+09 | 0.205168E+09 | 0.805020E+09 | 0.306507E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 85149799.43 | 0.00 | 85149799.43 | 17667036.79 | 0.334594E+09 |
February | 96123964.78 | 0.00 | 96123964.78 | 34388818.69 | 0.270360E+09 |
March | 0.134266E+09 | 4667.24 | 0.134261E+09 | 83358736.10 | 0.229278E+09 |
April | 0.165726E+09 | 2219973.94 | 0.163506E+09 | 0.135526E+09 | 0.137824E+09 |
May | 0.185361E+09 | 12043444.04 | 0.173317E+09 | 0.198567E+09 | 94201284.14 |
June | 0.204232E+09 | 33964118.59 | 0.170267E+09 | 0.300567E+09 | 51267854.95 |
July | 0.193520E+09 | 16494758.22 | 0.177025E+09 | 0.313211E+09 | 27027344.34 |
August | 0.179595E+09 | 4395223.56 | 0.175200E+09 | 0.262492E+09 | 34583302.11 |
September | 0.138746E+09 | 98869.42 | 0.138647E+09 | 0.171679E+09 | 77854455.22 |
October | 0.106878E+09 | 0.00 | 0.106878E+09 | 80295286.60 | 0.167848E+09 |
November | 87836488.38 | 0.00 | 87836488.38 | 26470121.25 | 0.247416E+09 |
December | 72475366.39 | 0.00 | 72475366.39 | 5208170.38 | 0.347086E+09 |
Annual Sum or Average | 0.164991E+10 | 69221055.01 | 0.158069E+10 | 0.162943E+10 | 0.201934E+10 |
Minimum of Months | 72475366.39 | 0.00 | 72475366.39 | 5208170.38 | 27027344.34 |
Maximum of Months | 0.204232E+09 | 33964118.59 | 0.177025E+09 | 0.313211E+09 | 0.347086E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.440793E+09 | 0.246716E+09 | 0.194077E+09 | 0.385689E+09 | 0.567585E+09 |
February | 0.482140E+09 | 0.259172E+09 | 0.222967E+09 | 0.464446E+09 | 0.463213E+09 |
March | 0.709366E+09 | 0.404124E+09 | 0.305242E+09 | 0.774630E+09 | 0.390282E+09 |
April | 0.931246E+09 | 0.529931E+09 | 0.401315E+09 | 0.113074E+10 | 0.245307E+09 |
May | 0.919320E+09 | 0.523637E+09 | 0.395684E+09 | 0.118458E+10 | 0.177568E+09 |
June | 0.959453E+09 | 0.590986E+09 | 0.368467E+09 | 0.136749E+10 | 95876316.55 |
July | 0.916926E+09 | 0.524167E+09 | 0.392759E+09 | 0.137538E+10 | 50091636.66 |
August | 0.907525E+09 | 0.500213E+09 | 0.407312E+09 | 0.131158E+10 | 64127815.99 |
September | 0.732353E+09 | 0.409787E+09 | 0.322566E+09 | 0.999979E+09 | 0.138019E+09 |
October | 0.659325E+09 | 0.418683E+09 | 0.240642E+09 | 0.788198E+09 | 0.285818E+09 |
November | 0.496245E+09 | 0.291116E+09 | 0.205129E+09 | 0.493886E+09 | 0.425448E+09 |
December | 0.417691E+09 | 0.254778E+09 | 0.162912E+09 | 0.368406E+09 | 0.591753E+09 |
Annual Sum or Average | 0.857238E+10 | 0.495331E+10 | 0.361907E+10 | 0.106450E+11 | 0.349509E+10 |
Minimum of Months | 0.417691E+09 | 0.246716E+09 | 0.162912E+09 | 0.368406E+09 | 50091636.66 |
Maximum of Months | 0.959453E+09 | 0.590986E+09 | 0.407312E+09 | 0.137538E+10 | 0.591753E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.107837E+09 | 0.00 | 0.107837E+09 | 17657723.35 | 0.457853E+09 |
February | 0.121735E+09 | 0.00 | 0.121735E+09 | 40644610.31 | 0.368203E+09 |
March | 0.170039E+09 | 5910.77 | 0.170034E+09 | 0.107845E+09 | 0.311497E+09 |
April | 0.209882E+09 | 2811456.93 | 0.207070E+09 | 0.179174E+09 | 0.190322E+09 |
May | 0.234747E+09 | 15252261.97 | 0.219495E+09 | 0.258932E+09 | 0.134858E+09 |
June | 0.258646E+09 | 43013413.18 | 0.215633E+09 | 0.389526E+09 | 79621019.62 |
July | 0.245081E+09 | 20889570.53 | 0.224191E+09 | 0.402156E+09 | 49156478.22 |
August | 0.227446E+09 | 5566273.31 | 0.221880E+09 | 0.337289E+09 | 60099254.45 |
September | 0.175713E+09 | 125211.88 | 0.175587E+09 | 0.218579E+09 | 0.119083E+09 |
October | 0.135354E+09 | 0.00 | 0.135354E+09 | 98908148.75 | 0.241770E+09 |
November | 0.111239E+09 | 0.00 | 0.111239E+09 | 29284849.42 | 0.347879E+09 |
December | 91785478.59 | 0.00 | 91785478.59 | 4482597.12 | 0.477407E+09 |
Annual Sum or Average | 0.208951E+10 | 87664098.56 | 0.200184E+10 | 0.208448E+10 | 0.283775E+10 |
Minimum of Months | 91785478.59 | 0.00 | 91785478.59 | 4482597.12 | 49156478.22 |
Maximum of Months | 0.258646E+09 | 43013413.18 | 0.224191E+09 | 0.402156E+09 | 0.477407E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 39753127.47 | 0.00 | 39753127.47 | 6509367.98 | 0.168784E+09 |
February | 44876538.17 | 0.00 | 44876538.17 | 14983286.32 | 0.135734E+09 |
March | 62683574.03 | 2178.95 | 62681395.08 | 39756249.02 | 0.114831E+09 |
April | 77371112.45 | 1036419.44 | 76334693.01 | 66051094.86 | 70160584.54 |
May | 86537607.89 | 5622615.31 | 80914992.58 | 95452996.45 | 49714334.61 |
June | 95347742.98 | 15856525.14 | 79491217.84 | 0.143595E+09 | 29351604.68 |
July | 90346984.62 | 7700760.67 | 82646223.96 | 0.148251E+09 | 18121113.28 |
August | 83846123.30 | 2051958.82 | 81794164.48 | 0.124339E+09 | 22155073.70 |
September | 64774917.93 | 46158.28 | 64728759.65 | 80577218.55 | 43898844.36 |
October | 49897013.47 | 0.00 | 49897013.47 | 36461639.09 | 89126414.95 |
November | 41007437.97 | 0.00 | 41007437.97 | 10795608.09 | 0.128243E+09 |
December | 33835927.95 | 0.00 | 33835927.95 | 1652470.91 | 0.175992E+09 |
Annual Sum or Average | 0.770278E+09 | 32316616.61 | 0.737961E+09 | 0.768425E+09 | 0.104611E+10 |
Minimum of Months | 33835927.95 | 0.00 | 33835927.95 | 1652470.91 | 18121113.28 |
Maximum of Months | 95347742.98 | 15856525.14 | 82646223.96 | 0.148251E+09 | 0.175992E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.293209E+09 | 0.228018E+09 | 65190972.91 | 0.344693E+09 | 0.146992E+09 |
February | 0.261051E+09 | 0.191053E+09 | 69997867.18 | 0.313544E+09 | 0.121999E+09 |
March | 0.214914E+09 | 0.131142E+09 | 83772641.65 | 0.263775E+09 | 0.108476E+09 |
April | 0.159730E+09 | 65459272.62 | 94271166.94 | 0.204584E+09 | 72328278.50 |
May | 0.111084E+09 | 25129794.80 | 85953812.25 | 0.145822E+09 | 53119691.03 |
June | 89867461.62 | 10790966.69 | 79076494.93 | 0.141277E+09 | 31967079.09 |
July | 0.102793E+09 | 16128780.20 | 86664444.25 | 0.175351E+09 | 18835877.41 |
August | 0.139833E+09 | 44102522.06 | 95730758.02 | 0.223915E+09 | 23223267.65 |
September | 0.192107E+09 | 0.108139E+09 | 83967969.21 | 0.281563E+09 | 43454280.14 |
October | 0.267442E+09 | 0.196725E+09 | 70717194.11 | 0.351181E+09 | 80935505.85 |
November | 0.291951E+09 | 0.224690E+09 | 67260585.57 | 0.353815E+09 | 0.112810E+09 |
December | 0.319748E+09 | 0.263948E+09 | 55800186.81 | 0.378908E+09 | 0.149380E+09 |
Annual Sum or Average | 0.244373E+10 | 0.150533E+10 | 0.938404E+09 | 0.317843E+10 | 0.963520E+09 |
Minimum of Months | 89867461.62 | 10790966.69 | 55800186.81 | 0.141277E+09 | 18835877.41 |
Maximum of Months | 0.319748E+09 | 0.263948E+09 | 95730758.02 | 0.378908E+09 | 0.149380E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.795830E+09 | 0.618889E+09 | 0.176942E+09 | 0.935567E+09 | 0.398965E+09 |
February | 0.708546E+09 | 0.518558E+09 | 0.189989E+09 | 0.851024E+09 | 0.331131E+09 |
March | 0.583321E+09 | 0.355945E+09 | 0.227376E+09 | 0.715940E+09 | 0.294425E+09 |
April | 0.433541E+09 | 0.177670E+09 | 0.255871E+09 | 0.555284E+09 | 0.196314E+09 |
May | 0.301504E+09 | 68207403.27 | 0.233296E+09 | 0.395790E+09 | 0.144178E+09 |
June | 0.243919E+09 | 29288890.85 | 0.214630E+09 | 0.383455E+09 | 86765191.36 |
July | 0.279002E+09 | 43776808.53 | 0.235225E+09 | 0.475938E+09 | 51124424.07 |
August | 0.379536E+09 | 0.119703E+09 | 0.259833E+09 | 0.607751E+09 | 63032497.08 |
September | 0.521417E+09 | 0.293511E+09 | 0.227906E+09 | 0.764219E+09 | 0.117944E+09 |
October | 0.725893E+09 | 0.533952E+09 | 0.191941E+09 | 0.953176E+09 | 0.219676E+09 |
November | 0.792414E+09 | 0.609855E+09 | 0.182559E+09 | 0.960326E+09 | 0.306189E+09 |
December | 0.867861E+09 | 0.716408E+09 | 0.151453E+09 | 0.102843E+10 | 0.405447E+09 |
Annual Sum or Average | 0.663278E+10 | 0.408576E+10 | 0.254702E+10 | 0.862690E+10 | 0.261519E+10 |
Minimum of Months | 0.243919E+09 | 29288890.85 | 0.151453E+09 | 0.383455E+09 | 51124424.07 |
Maximum of Months | 0.867861E+09 | 0.716408E+09 | 0.259833E+09 | 0.102843E+10 | 0.405447E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.628401E+09 | 0.488685E+09 | 0.139716E+09 | 0.732993E+09 | 0.299829E+09 |
February | 0.559480E+09 | 0.409462E+09 | 0.150018E+09 | 0.664009E+09 | 0.248883E+09 |
March | 0.460600E+09 | 0.281060E+09 | 0.179540E+09 | 0.558962E+09 | 0.216563E+09 |
April | 0.342331E+09 | 0.140291E+09 | 0.202040E+09 | 0.432845E+09 | 0.138078E+09 |
May | 0.238072E+09 | 53857719.31 | 0.184215E+09 | 0.310866E+09 | 94908330.36 |
June | 0.192602E+09 | 23127003.62 | 0.169475E+09 | 0.304744E+09 | 51966442.02 |
July | 0.220305E+09 | 34566908.48 | 0.185738E+09 | 0.380891E+09 | 23986333.37 |
August | 0.299688E+09 | 94519723.41 | 0.205168E+09 | 0.482595E+09 | 31739042.60 |
September | 0.411720E+09 | 0.231761E+09 | 0.179959E+09 | 0.602399E+09 | 71146988.58 |
October | 0.573177E+09 | 0.421618E+09 | 0.151560E+09 | 0.750705E+09 | 0.150764E+09 |
November | 0.625703E+09 | 0.481552E+09 | 0.144152E+09 | 0.753374E+09 | 0.223533E+09 |
December | 0.685278E+09 | 0.565688E+09 | 0.119590E+09 | 0.805008E+09 | 0.305186E+09 |
Annual Sum or Average | 0.523736E+10 | 0.322619E+10 | 0.201117E+10 | 0.677939E+10 | 0.185658E+10 |
Minimum of Months | 0.192602E+09 | 23127003.62 | 0.119590E+09 | 0.304744E+09 | 23986333.37 |
Maximum of Months | 0.685278E+09 | 0.565688E+09 | 0.205168E+09 | 0.805008E+09 | 0.305186E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.454587E+09 | 0.259253E+09 | 0.195335E+09 | 0.423668E+09 | 0.614786E+09 |
February | 0.527495E+09 | 0.304370E+09 | 0.223125E+09 | 0.529691E+09 | 0.499055E+09 |
March | 0.651650E+09 | 0.346153E+09 | 0.305497E+09 | 0.706936E+09 | 0.417618E+09 |
April | 0.806811E+09 | 0.429395E+09 | 0.377416E+09 | 0.956321E+09 | 0.251563E+09 |
May | 0.792803E+09 | 0.409630E+09 | 0.383173E+09 | 0.101193E+10 | 0.173848E+09 |
June | 0.817524E+09 | 0.455297E+09 | 0.362227E+09 | 0.118668E+10 | 96955234.02 |
July | 0.762720E+09 | 0.372697E+09 | 0.390023E+09 | 0.117064E+10 | 44778712.64 |
August | 0.780187E+09 | 0.360335E+09 | 0.419852E+09 | 0.114702E+10 | 59300464.64 |
September | 0.685042E+09 | 0.361685E+09 | 0.323357E+09 | 0.939189E+09 | 0.133945E+09 |
October | 0.647817E+09 | 0.403510E+09 | 0.244307E+09 | 0.780238E+09 | 0.302568E+09 |
November | 0.489878E+09 | 0.288175E+09 | 0.201704E+09 | 0.487906E+09 | 0.452829E+09 |
December | 0.434675E+09 | 0.271434E+09 | 0.163241E+09 | 0.395336E+09 | 0.631320E+09 |
Annual Sum or Average | 0.785119E+10 | 0.426193E+10 | 0.358926E+10 | 0.973556E+10 | 0.367857E+10 |
Minimum of Months | 0.434675E+09 | 0.259253E+09 | 0.163241E+09 | 0.395336E+09 | 44778712.64 |
Maximum of Months | 0.817524E+09 | 0.455297E+09 | 0.419852E+09 | 0.118668E+10 | 0.631320E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 85149799.43 | 0.00 | 85149799.43 | 20132027.38 | 0.332888E+09 |
February | 96123964.78 | 0.00 | 96123964.78 | 35957327.58 | 0.270408E+09 |
March | 0.134266E+09 | 4667.24 | 0.134261E+09 | 86497420.98 | 0.228189E+09 |
April | 0.165726E+09 | 2219973.94 | 0.163506E+09 | 0.138198E+09 | 0.139261E+09 |
May | 0.185361E+09 | 12043444.04 | 0.173317E+09 | 0.202153E+09 | 94561805.20 |
June | 0.204232E+09 | 33964118.59 | 0.170267E+09 | 0.305857E+09 | 51570235.34 |
July | 0.193520E+09 | 16494758.22 | 0.177025E+09 | 0.319283E+09 | 25628634.83 |
August | 0.179595E+09 | 4395223.56 | 0.175200E+09 | 0.268398E+09 | 33955404.80 |
September | 0.138746E+09 | 98869.42 | 0.138647E+09 | 0.175121E+09 | 77128636.19 |
October | 0.106878E+09 | 0.00 | 0.106878E+09 | 82829096.81 | 0.168390E+09 |
November | 87836488.38 | 0.00 | 87836488.38 | 29131693.01 | 0.244710E+09 |
December | 72475366.39 | 0.00 | 72475366.39 | 6629902.68 | 0.343837E+09 |
Annual Sum or Average | 0.164991E+10 | 69221055.01 | 0.158069E+10 | 0.167019E+10 | 0.201053E+10 |
Minimum of Months | 72475366.39 | 0.00 | 72475366.39 | 6629902.68 | 25628634.83 |
Maximum of Months | 0.204232E+09 | 33964118.59 | 0.177025E+09 | 0.319283E+09 | 0.343837E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.454587E+09 | 0.259253E+09 | 0.195335E+09 | 0.444569E+09 | 0.600332E+09 |
February | 0.527495E+09 | 0.304370E+09 | 0.223125E+09 | 0.548104E+09 | 0.488340E+09 |
March | 0.651650E+09 | 0.346153E+09 | 0.305497E+09 | 0.717136E+09 | 0.414625E+09 |
April | 0.806811E+09 | 0.429395E+09 | 0.377416E+09 | 0.956276E+09 | 0.261198E+09 |
May | 0.792803E+09 | 0.409630E+09 | 0.383173E+09 | 0.100771E+10 | 0.184443E+09 |
June | 0.817524E+09 | 0.455297E+09 | 0.362227E+09 | 0.117805E+10 | 0.102875E+09 |
July | 0.762720E+09 | 0.372697E+09 | 0.390023E+09 | 0.116307E+10 | 49272400.60 |
August | 0.780187E+09 | 0.360335E+09 | 0.419852E+09 | 0.114272E+10 | 65847086.70 |
September | 0.685042E+09 | 0.361685E+09 | 0.323357E+09 | 0.943688E+09 | 0.143772E+09 |
October | 0.647817E+09 | 0.403510E+09 | 0.244307E+09 | 0.790272E+09 | 0.306402E+09 |
November | 0.489878E+09 | 0.288175E+09 | 0.201704E+09 | 0.506960E+09 | 0.439917E+09 |
December | 0.434675E+09 | 0.271434E+09 | 0.163241E+09 | 0.416186E+09 | 0.612577E+09 |
Annual Sum or Average | 0.785119E+10 | 0.426193E+10 | 0.358926E+10 | 0.981475E+10 | 0.366960E+10 |
Minimum of Months | 0.434675E+09 | 0.259253E+09 | 0.163241E+09 | 0.416186E+09 | 49272400.60 |
Maximum of Months | 0.817524E+09 | 0.455297E+09 | 0.419852E+09 | 0.117805E+10 | 0.612577E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.921610E+09 | 0.716703E+09 | 0.204907E+09 | 0.105555E+10 | 0.456416E+09 |
February | 0.820531E+09 | 0.600515E+09 | 0.220016E+09 | 0.959483E+09 | 0.376648E+09 |
March | 0.675515E+09 | 0.412202E+09 | 0.263313E+09 | 0.811257E+09 | 0.323087E+09 |
April | 0.502062E+09 | 0.205750E+09 | 0.296311E+09 | 0.635823E+09 | 0.199992E+09 |
May | 0.349156E+09 | 78987514.10 | 0.270168E+09 | 0.462840E+09 | 0.135040E+09 |
June | 0.282470E+09 | 33917970.31 | 0.248552E+09 | 0.462117E+09 | 71609655.81 |
July | 0.323098E+09 | 50695688.68 | 0.272402E+09 | 0.572836E+09 | 31862637.41 |
August | 0.439521E+09 | 0.138622E+09 | 0.300899E+09 | 0.718057E+09 | 43205892.42 |
September | 0.603826E+09 | 0.339900E+09 | 0.263927E+09 | 0.884785E+09 | 0.102373E+09 |
October | 0.840620E+09 | 0.618343E+09 | 0.222277E+09 | 0.109265E+10 | 0.225171E+09 |
November | 0.917654E+09 | 0.706242E+09 | 0.211412E+09 | 0.108924E+10 | 0.339717E+09 |
December | 0.100503E+10 | 0.829635E+09 | 0.175390E+09 | 0.116048E+10 | 0.466086E+09 |
Annual Sum or Average | 0.768109E+10 | 0.473151E+10 | 0.294957E+10 | 0.990512E+10 | 0.277121E+10 |
Minimum of Months | 0.282470E+09 | 33917970.31 | 0.175390E+09 | 0.462117E+09 | 31862637.41 |
Maximum of Months | 0.100503E+10 | 0.829635E+09 | 0.300899E+09 | 0.116048E+10 | 0.466086E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.596026E+09 | 0.00 | 0.596026E+09 | 61661193.33 | 0.277361E+10 |
February | 0.672842E+09 | 0.00 | 0.672842E+09 | 0.168074E+09 | 0.223856E+10 |
March | 0.939826E+09 | 32669.46 | 0.939794E+09 | 0.505152E+09 | 0.188079E+10 |
April | 0.116004E+10 | 15539229.06 | 0.114450E+10 | 0.896535E+09 | 0.112738E+10 |
May | 0.129747E+10 | 84300915.40 | 0.121317E+10 | 0.133448E+10 | 0.792291E+09 |
June | 0.142957E+10 | 0.237740E+09 | 0.119183E+10 | 0.209411E+10 | 0.461460E+09 |
July | 0.135459E+10 | 0.115459E+09 | 0.123913E+10 | 0.218526E+10 | 0.283711E+09 |
August | 0.125712E+10 | 30765399.66 | 0.122636E+10 | 0.182959E+10 | 0.342871E+09 |
September | 0.971182E+09 | 692059.69 | 0.970490E+09 | 0.117564E+10 | 0.666221E+09 |
October | 0.748115E+09 | 0.00 | 0.748115E+09 | 0.512312E+09 | 0.139211E+10 |
November | 0.614832E+09 | 0.00 | 0.614832E+09 | 0.123794E+09 | 0.207865E+10 |
December | 0.507308E+09 | 0.00 | 0.507308E+09 | 11232591.76 | 0.290781E+10 |
Annual Sum or Average | 0.115489E+11 | 0.484529E+09 | 0.110644E+11 | 0.108978E+11 | 0.169455E+11 |
Minimum of Months | 0.507308E+09 | 0.00 | 0.507308E+09 | 11232591.76 | 0.283711E+09 |
Maximum of Months | 0.142957E+10 | 0.237740E+09 | 0.123913E+10 | 0.218526E+10 | 0.290781E+10 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.596026E+09 | 0.00 | 0.596026E+09 | 51312966.49 | 0.283521E+10 |
February | 0.672842E+09 | 0.00 | 0.672842E+09 | 0.153479E+09 | 0.228430E+10 |
March | 0.939826E+09 | 32669.46 | 0.939794E+09 | 0.483581E+09 | 0.191698E+10 |
April | 0.116004E+10 | 15539229.06 | 0.114450E+10 | 0.876089E+09 | 0.115042E+10 |
May | 0.129747E+10 | 84300915.40 | 0.121317E+10 | 0.131313E+10 | 0.810057E+09 |
June | 0.142957E+10 | 0.237740E+09 | 0.119183E+10 | 0.207472E+10 | 0.473820E+09 |
July | 0.135459E+10 | 0.115459E+09 | 0.123913E+10 | 0.216620E+10 | 0.295053E+09 |
August | 0.125712E+10 | 30765399.66 | 0.122636E+10 | 0.181133E+10 | 0.355508E+09 |
September | 0.971182E+09 | 692059.69 | 0.970490E+09 | 0.116098E+10 | 0.683482E+09 |
October | 0.748115E+09 | 0.00 | 0.748115E+09 | 0.497622E+09 | 0.142155E+10 |
November | 0.614832E+09 | 0.00 | 0.614832E+09 | 0.111300E+09 | 0.212431E+10 |
December | 0.507308E+09 | 0.00 | 0.507308E+09 | 8457367.76 | 0.297804E+10 |
Annual Sum or Average | 0.115489E+11 | 0.484529E+09 | 0.110644E+11 | 0.107082E+11 | 0.173287E+11 |
Minimum of Months | 0.507308E+09 | 0.00 | 0.507308E+09 | 8457367.76 | 0.295053E+09 |
Maximum of Months | 0.142957E+10 | 0.237740E+09 | 0.123913E+10 | 0.216620E+10 | 0.297804E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 85149799.43 | 0.00 | 85149799.43 | 24182436.53 | 0.347301E+09 |
February | 96123964.78 | 0.00 | 96123964.78 | 44283289.15 | 0.283989E+09 |
March | 0.134266E+09 | 4667.24 | 0.134261E+09 | 0.107319E+09 | 0.242437E+09 |
April | 0.165726E+09 | 2219973.94 | 0.163506E+09 | 0.177711E+09 | 0.148101E+09 |
May | 0.185361E+09 | 12043444.04 | 0.173317E+09 | 0.252628E+09 | 0.107326E+09 |
June | 0.204232E+09 | 33964118.59 | 0.170267E+09 | 0.369194E+09 | 65083580.12 |
July | 0.193520E+09 | 16494758.22 | 0.177025E+09 | 0.387440E+09 | 41048595.29 |
August | 0.179595E+09 | 4395223.56 | 0.175200E+09 | 0.334559E+09 | 48165509.44 |
September | 0.138746E+09 | 98869.42 | 0.138647E+09 | 0.226448E+09 | 83575032.80 |
October | 0.106878E+09 | 0.00 | 0.106878E+09 | 0.113672E+09 | 0.172333E+09 |
November | 87836488.38 | 0.00 | 87836488.38 | 37808833.77 | 0.254956E+09 |
December | 72475366.39 | 0.00 | 72475366.39 | 8518171.86 | 0.358181E+09 |
Annual Sum or Average | 0.164991E+10 | 69221055.01 | 0.158069E+10 | 0.208376E+10 | 0.215250E+10 |
Minimum of Months | 72475366.39 | 0.00 | 72475366.39 | 8518171.86 | 41048595.29 |
Maximum of Months | 0.204232E+09 | 33964118.59 | 0.177025E+09 | 0.387440E+09 | 0.358181E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.881523E+09 | 0.493396E+09 | 0.388127E+09 | 0.815789E+09 | 0.119414E+10 |
February | 0.964211E+09 | 0.518308E+09 | 0.445903E+09 | 0.984316E+09 | 0.983200E+09 |
March | 0.141863E+10 | 0.808191E+09 | 0.610440E+09 | 0.166036E+10 | 0.841813E+09 |
April | 0.186236E+10 | 0.105979E+10 | 0.802573E+09 | 0.243438E+10 | 0.536722E+09 |
May | 0.183851E+10 | 0.104720E+10 | 0.791311E+09 | 0.257470E+10 | 0.402969E+09 |
June | 0.191877E+10 | 0.118189E+10 | 0.736882E+09 | 0.299033E+10 | 0.243873E+09 |
July | 0.183372E+10 | 0.104826E+10 | 0.785462E+09 | 0.302969E+10 | 0.153896E+09 |
August | 0.181492E+10 | 0.100036E+10 | 0.814565E+09 | 0.289497E+10 | 0.181043E+09 |
September | 0.146460E+10 | 0.819516E+09 | 0.645087E+09 | 0.221454E+10 | 0.306485E+09 |
October | 0.131856E+10 | 0.837307E+09 | 0.481250E+09 | 0.172556E+10 | 0.603188E+09 |
November | 0.992419E+09 | 0.582190E+09 | 0.410229E+09 | 0.105253E+10 | 0.889556E+09 |
December | 0.835322E+09 | 0.509521E+09 | 0.325801E+09 | 0.773639E+09 | 0.123830E+10 |
Annual Sum or Average | 0.171435E+11 | 0.990592E+10 | 0.723763E+10 | 0.231508E+11 | 0.757519E+10 |
Minimum of Months | 0.835322E+09 | 0.493396E+09 | 0.325801E+09 | 0.773639E+09 | 0.153896E+09 |
Maximum of Months | 0.191877E+10 | 0.118189E+10 | 0.814565E+09 | 0.302969E+10 | 0.123830E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.628401E+09 | 0.488685E+09 | 0.139716E+09 | 0.764444E+09 | 0.311792E+09 |
February | 0.559480E+09 | 0.409462E+09 | 0.150018E+09 | 0.695752E+09 | 0.259874E+09 |
March | 0.460600E+09 | 0.281060E+09 | 0.179540E+09 | 0.594457E+09 | 0.231141E+09 |
April | 0.342331E+09 | 0.140291E+09 | 0.202040E+09 | 0.475722E+09 | 0.152200E+09 |
May | 0.238072E+09 | 53857719.31 | 0.184215E+09 | 0.358980E+09 | 0.112152E+09 |
June | 0.192602E+09 | 23127003.62 | 0.169475E+09 | 0.361496E+09 | 68502425.36 |
July | 0.220305E+09 | 34566908.48 | 0.185738E+09 | 0.444310E+09 | 41447773.87 |
August | 0.299688E+09 | 94519723.41 | 0.205168E+09 | 0.547244E+09 | 49132969.25 |
September | 0.411720E+09 | 0.231761E+09 | 0.179959E+09 | 0.659557E+09 | 83432739.47 |
October | 0.573177E+09 | 0.421618E+09 | 0.151560E+09 | 0.799365E+09 | 0.161202E+09 |
November | 0.625703E+09 | 0.481552E+09 | 0.144152E+09 | 0.789411E+09 | 0.232727E+09 |
December | 0.685278E+09 | 0.565688E+09 | 0.119590E+09 | 0.836722E+09 | 0.315678E+09 |
Annual Sum or Average | 0.523736E+10 | 0.322619E+10 | 0.201117E+10 | 0.732746E+10 | 0.201928E+10 |
Minimum of Months | 0.192602E+09 | 23127003.62 | 0.119590E+09 | 0.358980E+09 | 41447773.87 |
Maximum of Months | 0.685278E+09 | 0.565688E+09 | 0.205168E+09 | 0.836722E+09 | 0.315678E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.107837E+09 | 0.00 | 0.107837E+09 | 14746540.56 | 0.460693E+09 |
February | 0.121735E+09 | 0.00 | 0.121735E+09 | 35691639.50 | 0.371522E+09 |
March | 0.170039E+09 | 5910.77 | 0.170034E+09 | 0.101396E+09 | 0.312259E+09 |
April | 0.209882E+09 | 2811456.93 | 0.207070E+09 | 0.170424E+09 | 0.191233E+09 |
May | 0.234747E+09 | 15252261.97 | 0.219495E+09 | 0.248390E+09 | 0.137416E+09 |
June | 0.258646E+09 | 43013413.18 | 0.215633E+09 | 0.379354E+09 | 82646295.39 |
July | 0.245081E+09 | 20889570.53 | 0.224191E+09 | 0.392225E+09 | 52287785.95 |
August | 0.227446E+09 | 5566273.31 | 0.221880E+09 | 0.328005E+09 | 63274000.34 |
September | 0.175713E+09 | 125211.88 | 0.175587E+09 | 0.211212E+09 | 0.120926E+09 |
October | 0.135354E+09 | 0.00 | 0.135354E+09 | 93259808.14 | 0.240412E+09 |
November | 0.111239E+09 | 0.00 | 0.111239E+09 | 25921379.72 | 0.346662E+09 |
December | 91785478.59 | 0.00 | 91785478.59 | 3159167.44 | 0.483398E+09 |
Annual Sum or Average | 0.208951E+10 | 87664098.56 | 0.200184E+10 | 0.200378E+10 | 0.286273E+10 |
Minimum of Months | 91785478.59 | 0.00 | 91785478.59 | 3159167.44 | 52287785.95 |
Maximum of Months | 0.258646E+09 | 43013413.18 | 0.224191E+09 | 0.392225E+09 | 0.483398E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 96482036.79 | 0.00 | 96482036.79 | 13193785.72 | 0.412120E+09 |
February | 0.108917E+09 | 0.00 | 0.108917E+09 | 31933445.10 | 0.332405E+09 |
March | 0.152135E+09 | 5288.39 | 0.152130E+09 | 90719597.01 | 0.279379E+09 |
April | 0.187782E+09 | 2515421.16 | 0.185267E+09 | 0.152479E+09 | 0.171097E+09 |
May | 0.210029E+09 | 13646256.58 | 0.196383E+09 | 0.222235E+09 | 0.122947E+09 |
June | 0.231412E+09 | 38484263.75 | 0.192928E+09 | 0.339410E+09 | 73943953.63 |
July | 0.219275E+09 | 18689977.90 | 0.200585E+09 | 0.350925E+09 | 46782080.21 |
August | 0.203497E+09 | 4980165.82 | 0.198517E+09 | 0.293467E+09 | 56611487.85 |
September | 0.157211E+09 | 112027.54 | 0.157099E+09 | 0.188972E+09 | 0.108193E+09 |
October | 0.121102E+09 | 0.00 | 0.121102E+09 | 83439903.71 | 0.215098E+09 |
November | 99526286.15 | 0.00 | 99526286.15 | 23191956.65 | 0.310143E+09 |
December | 82120815.47 | 0.00 | 82120815.47 | 2826519.08 | 0.432468E+09 |
Annual Sum or Average | 0.186949E+10 | 78433401.14 | 0.179105E+10 | 0.179279E+10 | 0.256119E+10 |
Minimum of Months | 82120815.47 | 0.00 | 82120815.47 | 2826519.08 | 46782080.21 |
Maximum of Months | 0.231412E+09 | 38484263.75 | 0.200585E+09 | 0.350925E+09 | 0.432468E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.234601E+10 | 0.182441E+10 | 0.521602E+09 | 0.273013E+10 | 0.117782E+10 |
February | 0.208871E+10 | 0.152864E+10 | 0.560062E+09 | 0.247885E+10 | 0.980904E+09 |
March | 0.171956E+10 | 0.104928E+10 | 0.670276E+09 | 0.208059E+10 | 0.870656E+09 |
April | 0.127803E+10 | 0.523749E+09 | 0.754276E+09 | 0.160395E+10 | 0.582785E+09 |
May | 0.888795E+09 | 0.201067E+09 | 0.687728E+09 | 0.113249E+10 | 0.433723E+09 |
June | 0.719042E+09 | 86339996.01 | 0.632702E+09 | 0.110071E+10 | 0.265056E+09 |
July | 0.822463E+09 | 0.129049E+09 | 0.693414E+09 | 0.137174E+10 | 0.160688E+09 |
August | 0.111883E+10 | 0.352870E+09 | 0.765955E+09 | 0.175968E+10 | 0.195953E+09 |
September | 0.153707E+10 | 0.865233E+09 | 0.671839E+09 | 0.222296E+10 | 0.353884E+09 |
October | 0.213984E+10 | 0.157402E+10 | 0.565818E+09 | 0.278391E+10 | 0.644529E+09 |
November | 0.233594E+10 | 0.179778E+10 | 0.538161E+09 | 0.280825E+10 | 0.896222E+09 |
December | 0.255835E+10 | 0.211188E+10 | 0.446465E+09 | 0.300346E+10 | 0.119929E+10 |
Annual Sum or Average | 0.195526E+11 | 0.120443E+11 | 0.750830E+10 | 0.250767E+11 | 0.776151E+10 |
Minimum of Months | 0.719042E+09 | 86339996.01 | 0.446465E+09 | 0.110071E+10 | 0.160688E+09 |
Maximum of Months | 0.255835E+10 | 0.211188E+10 | 0.765955E+09 | 0.300346E+10 | 0.119929E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1367.97 | 576.89 | 1186.63 | 922.80 | 263.83 | 0.00 | 0.00 |
February | 1375.64 | 531.95 | 1169.68 | 856.05 | 313.63 | 0.00 | 0.00 |
March | 1049.84 | 421.88 | 869.77 | 530.74 | 339.03 | 0.00 | 0.00 |
April | 838.63 | 293.28 | 667.98 | 273.75 | 394.23 | 0.00 | 0.00 |
May | 577.80 | 206.68 | 449.56 | 101.70 | 347.85 | 0.00 | 0.00 |
June | 568.53 | 133.08 | 375.82 | 45.13 | 330.69 | 0.00 | 0.00 |
July | 682.69 | 82.03 | 416.00 | 65.27 | 350.73 | 0.00 | 0.00 |
August | 881.00 | 100.15 | 565.91 | 178.49 | 387.42 | 0.00 | 0.00 |
September | 1155.51 | 183.43 | 803.38 | 452.23 | 351.15 | 0.00 | 0.00 |
October | 1395.93 | 320.61 | 1082.35 | 796.16 | 286.19 | 0.00 | 0.00 |
November | 1450.29 | 460.39 | 1220.92 | 939.64 | 281.28 | 0.00 | 0.00 |
December | 1498.83 | 591.81 | 1294.03 | 1068.21 | 225.82 | 0.00 | 0.00 |
Annual Sum or Average | 1068.45 | 324.11 | 839.96 | 517.41 | 322.55 | 0.00 | 0.00 |
Minimum of Months | 568.53 | 82.03 | 375.82 | 45.13 | 225.82 | 0.00 | 0.00 |
Maximum of Months | 1498.83 | 591.81 | 1294.03 | 1068.21 | 394.23 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3809.35 | 1729.24 | 3341.48 | 2598.55 | 742.93 | 0.00 | 0.00 |
February | 3831.09 | 1598.78 | 3293.74 | 2410.57 | 883.17 | 0.00 | 0.00 |
March | 2912.08 | 1282.46 | 2449.21 | 1494.52 | 954.68 | 0.00 | 0.00 |
April | 2323.30 | 888.38 | 1880.99 | 770.86 | 1110.14 | 0.00 | 0.00 |
May | 1590.90 | 629.84 | 1265.92 | 286.39 | 979.54 | 0.00 | 0.00 |
June | 1578.71 | 394.77 | 1058.28 | 127.08 | 931.20 | 0.00 | 0.00 |
July | 1907.36 | 235.59 | 1171.44 | 183.81 | 987.63 | 0.00 | 0.00 |
August | 2464.80 | 287.00 | 1593.56 | 502.60 | 1090.96 | 0.00 | 0.00 |
September | 3232.23 | 533.11 | 2262.26 | 1273.45 | 988.81 | 0.00 | 0.00 |
October | 3901.49 | 948.69 | 3047.83 | 2241.93 | 805.90 | 0.00 | 0.00 |
November | 4044.24 | 1384.65 | 3438.04 | 2645.98 | 792.06 | 0.00 | 0.00 |
December | 4181.93 | 1776.34 | 3643.92 | 3008.01 | 635.91 | 0.00 | 0.00 |
Annual Sum or Average | 2976.52 | 970.84 | 2365.28 | 1457.01 | 908.27 | 0.00 | 0.00 |
Minimum of Months | 1578.71 | 235.59 | 1058.28 | 127.08 | 635.91 | 0.00 | 0.00 |
Maximum of Months | 4181.93 | 1776.34 | 3643.92 | 3008.01 | 1110.14 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 5024.66 | 2301.85 | 4340.77 | 3375.67 | 965.10 | 0.00 | 0.00 |
February | 5062.17 | 2123.27 | 4278.76 | 3131.47 | 1147.29 | 0.00 | 0.00 |
March | 3851.09 | 1704.10 | 3181.66 | 1941.47 | 1240.19 | 0.00 | 0.00 |
April | 3089.27 | 1176.16 | 2443.51 | 1001.39 | 1442.13 | 0.00 | 0.00 |
May | 2118.80 | 837.55 | 1644.50 | 372.03 | 1272.47 | 0.00 | 0.00 |
June | 2108.03 | 523.76 | 1374.76 | 165.08 | 1209.68 | 0.00 | 0.00 |
July | 2548.44 | 306.96 | 1521.77 | 238.78 | 1282.99 | 0.00 | 0.00 |
August | 3280.89 | 370.84 | 2070.13 | 652.91 | 1417.22 | 0.00 | 0.00 |
September | 4283.02 | 691.55 | 2938.80 | 1654.29 | 1284.51 | 0.00 | 0.00 |
October | 5156.09 | 1245.69 | 3959.30 | 2912.39 | 1046.91 | 0.00 | 0.00 |
November | 5338.14 | 1830.42 | 4466.21 | 3437.27 | 1028.93 | 0.00 | 0.00 |
December | 5516.77 | 2361.91 | 4733.66 | 3907.58 | 826.08 | 0.00 | 0.00 |
Annual Sum or Average | 3941.63 | 1285.22 | 3072.63 | 1892.73 | 1179.90 | 0.00 | 0.00 |
Minimum of Months | 2108.03 | 306.96 | 1374.76 | 165.08 | 826.08 | 0.00 | 0.00 |
Maximum of Months | 5516.77 | 2361.91 | 4733.66 | 3907.58 | 1442.13 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 419.65 | 330.23 | 404.34 | 279.25 | 125.09 | 0.00 | 0.00 |
February | 487.36 | 302.14 | 449.31 | 295.07 | 154.24 | 0.00 | 0.00 |
March | 471.22 | 234.57 | 415.27 | 234.17 | 181.09 | 0.00 | 0.00 |
April | 538.43 | 150.88 | 443.34 | 219.79 | 223.56 | 0.00 | 0.00 |
May | 496.74 | 101.62 | 384.88 | 173.05 | 211.84 | 0.00 | 0.00 |
June | 578.79 | 58.98 | 389.71 | 184.58 | 205.13 | 0.00 | 0.00 |
July | 582.67 | 27.14 | 367.02 | 152.05 | 214.96 | 0.00 | 0.00 |
August | 612.09 | 35.49 | 403.18 | 169.82 | 233.36 | 0.00 | 0.00 |
September | 597.91 | 81.04 | 423.13 | 228.95 | 194.18 | 0.00 | 0.00 |
October | 569.22 | 167.39 | 455.87 | 308.07 | 147.80 | 0.00 | 0.00 |
November | 470.31 | 254.02 | 430.39 | 296.96 | 133.43 | 0.00 | 0.00 |
December | 431.25 | 334.36 | 418.14 | 312.55 | 105.60 | 0.00 | 0.00 |
Annual Sum or Average | 521.31 | 172.50 | 415.04 | 237.45 | 177.59 | 0.00 | 0.00 |
Minimum of Months | 419.65 | 27.14 | 367.02 | 152.05 | 105.60 | 0.00 | 0.00 |
Maximum of Months | 612.09 | 334.36 | 455.87 | 312.55 | 233.36 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 169.40 | 348.12 | 201.51 | 96.79 | 104.72 | 0.00 | 0.00 |
February | 238.69 | 312.50 | 257.78 | 125.81 | 131.96 | 0.00 | 0.00 |
March | 299.47 | 239.82 | 293.43 | 129.24 | 164.19 | 0.00 | 0.00 |
April | 424.50 | 153.74 | 375.21 | 166.52 | 208.69 | 0.00 | 0.00 |
May | 454.15 | 104.05 | 365.20 | 157.43 | 207.77 | 0.00 | 0.00 |
June | 573.82 | 58.23 | 394.20 | 188.76 | 205.44 | 0.00 | 0.00 |
July | 556.10 | 28.84 | 357.02 | 145.31 | 211.71 | 0.00 | 0.00 |
August | 529.29 | 37.91 | 358.34 | 136.17 | 222.17 | 0.00 | 0.00 |
September | 433.70 | 87.03 | 317.82 | 139.58 | 178.24 | 0.00 | 0.00 |
October | 325.49 | 178.33 | 281.77 | 150.65 | 131.12 | 0.00 | 0.00 |
November | 203.14 | 265.36 | 222.88 | 111.18 | 111.71 | 0.00 | 0.00 |
December | 151.38 | 355.05 | 189.35 | 101.34 | 88.01 | 0.00 | 0.00 |
Annual Sum or Average | 363.78 | 180.10 | 301.28 | 137.34 | 163.94 | 0.00 | 0.00 |
Minimum of Months | 151.38 | 28.84 | 189.35 | 96.79 | 88.01 | 0.00 | 0.00 |
Maximum of Months | 573.82 | 355.05 | 394.20 | 188.76 | 222.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 207.35 | 114.24 | 187.66 | 145.93 | 41.72 | 0.00 | 0.00 |
February | 208.38 | 106.97 | 184.98 | 135.38 | 49.60 | 0.00 | 0.00 |
March | 155.81 | 87.68 | 137.55 | 83.93 | 53.62 | 0.00 | 0.00 |
April | 123.02 | 62.59 | 105.64 | 43.29 | 62.35 | 0.00 | 0.00 |
May | 81.66 | 46.50 | 71.09 | 16.08 | 55.01 | 0.00 | 0.00 |
June | 81.93 | 30.86 | 59.43 | 7.14 | 52.30 | 0.00 | 0.00 |
July | 100.66 | 20.60 | 65.79 | 10.32 | 55.47 | 0.00 | 0.00 |
August | 132.09 | 24.26 | 89.49 | 28.23 | 61.27 | 0.00 | 0.00 |
September | 175.60 | 40.10 | 127.05 | 71.52 | 55.53 | 0.00 | 0.00 |
October | 213.20 | 66.06 | 171.17 | 125.91 | 45.26 | 0.00 | 0.00 |
November | 220.91 | 93.37 | 193.08 | 148.60 | 44.48 | 0.00 | 0.00 |
December | 229.16 | 117.71 | 204.64 | 168.93 | 35.71 | 0.00 | 0.00 |
Annual Sum or Average | 160.54 | 67.37 | 132.83 | 81.83 | 51.01 | 0.00 | 0.00 |
Minimum of Months | 81.66 | 20.60 | 59.43 | 7.14 | 35.71 | 0.00 | 0.00 |
Maximum of Months | 229.16 | 117.71 | 204.64 | 168.93 | 62.35 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 5.51 | 102.34 | 25.44 | 0.00 | 25.44 | 0.00 | 0.00 |
February | 12.23 | 90.85 | 31.79 | 0.00 | 31.79 | 0.00 | 0.00 |
March | 27.51 | 68.00 | 40.11 | 0.00 | 40.11 | 0.00 | 0.00 |
April | 46.68 | 41.16 | 51.16 | 0.69 | 50.47 | 0.00 | 0.00 |
May | 64.76 | 26.98 | 55.37 | 3.60 | 51.77 | 0.00 | 0.00 |
June | 100.07 | 14.70 | 63.04 | 10.48 | 52.56 | 0.00 | 0.00 |
July | 100.94 | 6.66 | 57.81 | 4.93 | 52.88 | 0.00 | 0.00 |
August | 85.65 | 8.84 | 53.65 | 1.31 | 52.34 | 0.00 | 0.00 |
September | 58.01 | 22.05 | 42.83 | 0.03 | 42.80 | 0.00 | 0.00 |
October | 27.07 | 48.72 | 31.93 | 0.00 | 31.93 | 0.00 | 0.00 |
November | 9.11 | 77.10 | 27.11 | 0.00 | 27.11 | 0.00 | 0.00 |
December | 1.63 | 106.42 | 21.65 | 0.00 | 21.65 | 0.00 | 0.00 |
Annual Sum or Average | 45.10 | 50.96 | 41.86 | 1.76 | 40.10 | 0.00 | 0.00 |
Minimum of Months | 1.63 | 6.66 | 21.65 | 0.00 | 21.65 | 0.00 | 0.00 |
Maximum of Months | 100.94 | 106.42 | 63.04 | 10.48 | 52.88 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 404.58 | 323.56 | 399.19 | 274.57 | 124.62 | 0.00 | 0.00 |
February | 455.03 | 294.30 | 430.56 | 276.39 | 154.18 | 0.00 | 0.00 |
March | 490.21 | 225.09 | 436.82 | 255.82 | 181.00 | 0.00 | 0.00 |
April | 597.31 | 142.13 | 491.35 | 258.57 | 232.78 | 0.00 | 0.00 |
May | 557.34 | 97.24 | 432.12 | 215.61 | 216.51 | 0.00 | 0.00 |
June | 649.61 | 53.99 | 444.47 | 236.93 | 207.54 | 0.00 | 0.00 |
July | 661.93 | 26.06 | 424.59 | 208.61 | 215.99 | 0.00 | 0.00 |
August | 675.05 | 33.39 | 450.72 | 222.05 | 228.67 | 0.00 | 0.00 |
September | 618.07 | 76.60 | 441.39 | 247.51 | 193.88 | 0.00 | 0.00 |
October | 568.98 | 161.36 | 460.16 | 313.73 | 146.43 | 0.00 | 0.00 |
November | 469.02 | 250.15 | 432.85 | 298.10 | 134.75 | 0.00 | 0.00 |
December | 418.95 | 330.73 | 411.80 | 306.33 | 105.47 | 0.00 | 0.00 |
Annual Sum or Average | 547.53 | 167.25 | 437.90 | 259.37 | 178.53 | 0.00 | 0.00 |
Minimum of Months | 404.58 | 26.06 | 399.19 | 208.61 | 105.47 | 0.00 | 0.00 |
Maximum of Months | 675.05 | 330.73 | 491.35 | 313.73 | 232.78 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 140.62 | 326.86 | 196.36 | 92.11 | 104.25 | 0.00 | 0.00 |
February | 198.01 | 295.05 | 239.03 | 107.13 | 131.90 | 0.00 | 0.00 |
March | 313.22 | 224.20 | 314.98 | 150.88 | 164.09 | 0.00 | 0.00 |
April | 485.45 | 144.73 | 423.21 | 205.31 | 217.91 | 0.00 | 0.00 |
May | 515.45 | 100.51 | 412.44 | 200.00 | 212.44 | 0.00 | 0.00 |
June | 643.43 | 56.66 | 448.95 | 241.11 | 207.85 | 0.00 | 0.00 |
July | 630.42 | 28.77 | 414.59 | 201.86 | 212.73 | 0.00 | 0.00 |
August | 587.60 | 36.76 | 405.88 | 188.40 | 217.49 | 0.00 | 0.00 |
September | 450.54 | 81.79 | 336.07 | 158.13 | 177.94 | 0.00 | 0.00 |
October | 318.80 | 163.92 | 286.07 | 156.32 | 129.75 | 0.00 | 0.00 |
November | 193.38 | 252.21 | 225.34 | 112.31 | 113.03 | 0.00 | 0.00 |
December | 128.77 | 339.80 | 183.01 | 95.12 | 87.88 | 0.00 | 0.00 |
Annual Sum or Average | 384.68 | 170.32 | 324.15 | 159.26 | 164.88 | 0.00 | 0.00 |
Minimum of Months | 128.77 | 28.77 | 183.01 | 92.11 | 87.88 | 0.00 | 0.00 |
Maximum of Months | 643.43 | 339.80 | 448.95 | 241.11 | 217.91 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 464.99 | 415.77 | 461.70 | 316.20 | 145.51 | 0.00 | 0.00 |
February | 490.68 | 381.92 | 469.66 | 293.32 | 176.34 | 0.00 | 0.00 |
March | 416.32 | 305.02 | 384.92 | 181.86 | 203.06 | 0.00 | 0.00 |
April | 387.10 | 203.47 | 339.71 | 95.28 | 244.42 | 0.00 | 0.00 |
May | 332.38 | 140.43 | 274.00 | 42.64 | 231.35 | 0.00 | 0.00 |
June | 404.84 | 84.57 | 265.35 | 38.18 | 227.17 | 0.00 | 0.00 |
July | 447.84 | 50.41 | 267.78 | 33.04 | 234.74 | 0.00 | 0.00 |
August | 482.04 | 62.09 | 310.13 | 64.00 | 246.13 | 0.00 | 0.00 |
September | 518.58 | 124.85 | 368.06 | 155.02 | 213.04 | 0.00 | 0.00 |
October | 530.38 | 228.62 | 440.03 | 272.80 | 167.23 | 0.00 | 0.00 |
November | 504.75 | 327.63 | 477.09 | 321.97 | 155.12 | 0.00 | 0.00 |
December | 495.90 | 419.27 | 490.30 | 366.02 | 124.28 | 0.00 | 0.00 |
Annual Sum or Average | 456.06 | 227.89 | 378.50 | 181.10 | 197.40 | 0.00 | 0.00 |
Minimum of Months | 332.38 | 50.41 | 265.35 | 33.04 | 124.28 | 0.00 | 0.00 |
Maximum of Months | 530.38 | 419.27 | 490.30 | 366.02 | 246.13 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 418.28 | 327.91 | 404.34 | 279.25 | 125.09 | 0.00 | 0.00 |
February | 484.67 | 300.41 | 449.31 | 295.07 | 154.24 | 0.00 | 0.00 |
March | 468.36 | 232.51 | 415.27 | 234.17 | 181.09 | 0.00 | 0.00 |
April | 534.33 | 148.71 | 443.34 | 219.79 | 223.56 | 0.00 | 0.00 |
May | 493.12 | 99.59 | 384.88 | 173.05 | 211.84 | 0.00 | 0.00 |
June | 575.35 | 57.41 | 389.71 | 184.58 | 205.13 | 0.00 | 0.00 |
July | 579.27 | 25.67 | 367.02 | 152.05 | 214.96 | 0.00 | 0.00 |
August | 608.42 | 33.98 | 403.18 | 169.82 | 233.36 | 0.00 | 0.00 |
September | 594.49 | 78.87 | 423.13 | 228.95 | 194.18 | 0.00 | 0.00 |
October | 567.00 | 164.66 | 455.87 | 308.07 | 147.80 | 0.00 | 0.00 |
November | 468.84 | 250.89 | 430.39 | 296.96 | 133.43 | 0.00 | 0.00 |
December | 430.08 | 331.57 | 418.14 | 312.55 | 105.60 | 0.00 | 0.00 |
Annual Sum or Average | 518.52 | 170.36 | 415.04 | 237.45 | 177.59 | 0.00 | 0.00 |
Minimum of Months | 418.28 | 25.67 | 367.02 | 152.05 | 105.60 | 0.00 | 0.00 |
Maximum of Months | 608.42 | 331.57 | 455.87 | 312.55 | 233.36 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 169.80 | 344.73 | 201.51 | 96.79 | 104.72 | 0.00 | 0.00 |
February | 237.88 | 310.09 | 257.78 | 125.81 | 131.96 | 0.00 | 0.00 |
March | 297.76 | 237.72 | 293.43 | 129.24 | 164.19 | 0.00 | 0.00 |
April | 420.69 | 152.94 | 375.21 | 166.52 | 208.69 | 0.00 | 0.00 |
May | 450.59 | 103.04 | 365.20 | 157.43 | 207.77 | 0.00 | 0.00 |
June | 570.35 | 57.44 | 394.20 | 188.76 | 205.44 | 0.00 | 0.00 |
July | 553.07 | 27.59 | 357.02 | 145.31 | 211.71 | 0.00 | 0.00 |
August | 526.37 | 36.79 | 358.34 | 136.17 | 222.17 | 0.00 | 0.00 |
September | 431.53 | 85.11 | 317.82 | 139.58 | 178.24 | 0.00 | 0.00 |
October | 324.35 | 175.64 | 281.77 | 150.65 | 131.12 | 0.00 | 0.00 |
November | 203.44 | 260.75 | 222.88 | 111.18 | 111.71 | 0.00 | 0.00 |
December | 151.90 | 351.12 | 189.35 | 101.34 | 88.01 | 0.00 | 0.00 |
Annual Sum or Average | 362.00 | 177.93 | 301.28 | 137.34 | 163.94 | 0.00 | 0.00 |
Minimum of Months | 151.90 | 27.59 | 189.35 | 96.79 | 88.01 | 0.00 | 0.00 |
Maximum of Months | 570.35 | 351.12 | 394.20 | 188.76 | 222.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 394.10 | 170.41 | 344.09 | 267.59 | 76.50 | 0.00 | 0.00 |
February | 396.61 | 155.69 | 339.17 | 248.23 | 90.95 | 0.00 | 0.00 |
March | 302.89 | 120.63 | 252.21 | 153.90 | 98.31 | 0.00 | 0.00 |
April | 245.30 | 77.16 | 193.70 | 79.38 | 114.32 | 0.00 | 0.00 |
May | 172.80 | 50.42 | 130.36 | 29.49 | 100.87 | 0.00 | 0.00 |
June | 178.29 | 27.63 | 108.98 | 13.09 | 95.89 | 0.00 | 0.00 |
July | 213.87 | 11.90 | 120.63 | 18.93 | 101.70 | 0.00 | 0.00 |
August | 268.09 | 16.13 | 164.10 | 51.76 | 112.34 | 0.00 | 0.00 |
September | 341.35 | 39.50 | 232.96 | 131.13 | 101.82 | 0.00 | 0.00 |
October | 407.95 | 84.07 | 313.85 | 230.86 | 82.99 | 0.00 | 0.00 |
November | 420.23 | 131.06 | 354.03 | 272.47 | 81.56 | 0.00 | 0.00 |
December | 433.27 | 174.02 | 375.23 | 309.75 | 65.48 | 0.00 | 0.00 |
Annual Sum or Average | 314.09 | 87.87 | 243.57 | 150.04 | 93.53 | 0.00 | 0.00 |
Minimum of Months | 172.80 | 11.90 | 108.98 | 13.09 | 65.48 | 0.00 | 0.00 |
Maximum of Months | 433.27 | 174.02 | 375.23 | 309.75 | 114.32 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 23.02 | 1035.55 | 222.53 | 0.00 | 222.53 | 0.00 | 0.00 |
February | 69.47 | 925.33 | 278.13 | 0.00 | 278.13 | 0.00 | 0.00 |
March | 188.60 | 702.21 | 350.89 | 0.01 | 350.88 | 0.00 | 0.00 |
April | 345.89 | 434.95 | 447.55 | 6.00 | 441.55 | 0.00 | 0.00 |
May | 498.24 | 295.81 | 484.42 | 31.47 | 452.95 | 0.00 | 0.00 |
June | 807.91 | 178.03 | 551.53 | 91.72 | 459.81 | 0.00 | 0.00 |
July | 815.88 | 105.93 | 505.75 | 43.11 | 462.64 | 0.00 | 0.00 |
August | 683.09 | 128.01 | 469.36 | 11.49 | 457.87 | 0.00 | 0.00 |
September | 453.56 | 257.03 | 374.68 | 0.27 | 374.42 | 0.00 | 0.00 |
October | 191.28 | 519.75 | 279.31 | 0.00 | 279.31 | 0.00 | 0.00 |
November | 47.76 | 801.95 | 237.20 | 0.00 | 237.20 | 0.00 | 0.00 |
December | 4.19 | 1085.65 | 189.41 | 0.00 | 189.41 | 0.00 | 0.00 |
Annual Sum or Average | 345.57 | 537.34 | 366.21 | 15.36 | 350.85 | 0.00 | 0.00 |
Minimum of Months | 4.19 | 105.93 | 189.41 | 0.00 | 189.41 | 0.00 | 0.00 |
Maximum of Months | 815.88 | 1085.65 | 551.53 | 91.72 | 462.64 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 19.16 | 1058.55 | 222.53 | 0.00 | 222.53 | 0.00 | 0.00 |
February | 63.44 | 944.24 | 278.13 | 0.00 | 278.13 | 0.00 | 0.00 |
March | 180.55 | 715.72 | 350.89 | 0.01 | 350.88 | 0.00 | 0.00 |
April | 338.00 | 443.83 | 447.55 | 6.00 | 441.55 | 0.00 | 0.00 |
May | 490.27 | 302.44 | 484.42 | 31.47 | 452.95 | 0.00 | 0.00 |
June | 800.43 | 182.80 | 551.53 | 91.72 | 459.81 | 0.00 | 0.00 |
July | 808.77 | 110.16 | 505.75 | 43.11 | 462.64 | 0.00 | 0.00 |
August | 676.27 | 132.73 | 469.36 | 11.49 | 457.87 | 0.00 | 0.00 |
September | 447.91 | 263.69 | 374.68 | 0.27 | 374.42 | 0.00 | 0.00 |
October | 185.79 | 530.75 | 279.31 | 0.00 | 279.31 | 0.00 | 0.00 |
November | 42.94 | 819.56 | 237.20 | 0.00 | 237.20 | 0.00 | 0.00 |
December | 3.16 | 1111.87 | 189.41 | 0.00 | 189.41 | 0.00 | 0.00 |
Annual Sum or Average | 339.55 | 549.49 | 366.21 | 15.36 | 350.85 | 0.00 | 0.00 |
Minimum of Months | 3.16 | 110.16 | 189.41 | 0.00 | 189.41 | 0.00 | 0.00 |
Maximum of Months | 808.77 | 1111.87 | 551.53 | 91.72 | 462.64 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 581.69 | 674.59 | 595.53 | 366.67 | 228.87 | 0.00 | 0.00 |
February | 700.23 | 618.68 | 669.57 | 383.50 | 286.06 | 0.00 | 0.00 |
March | 873.16 | 482.35 | 751.75 | 406.68 | 345.07 | 0.00 | 0.00 |
April | 1185.76 | 317.40 | 914.51 | 463.85 | 450.66 | 0.00 | 0.00 |
May | 1187.19 | 229.95 | 844.51 | 415.58 | 428.93 | 0.00 | 0.00 |
June | 1434.19 | 144.23 | 893.37 | 478.00 | 415.36 | 0.00 | 0.00 |
July | 1441.54 | 88.10 | 839.14 | 410.44 | 428.70 | 0.00 | 0.00 |
August | 1409.68 | 103.51 | 856.56 | 410.42 | 446.14 | 0.00 | 0.00 |
September | 1194.75 | 181.22 | 777.42 | 405.62 | 371.79 | 0.00 | 0.00 |
October | 979.89 | 344.48 | 746.20 | 470.03 | 276.17 | 0.00 | 0.00 |
November | 712.39 | 518.52 | 658.16 | 410.39 | 247.77 | 0.00 | 0.00 |
December | 575.12 | 684.62 | 594.79 | 401.44 | 193.35 | 0.00 | 0.00 |
Annual Sum or Average | 1024.43 | 364.38 | 762.01 | 418.61 | 343.40 | 0.00 | 0.00 |
Minimum of Months | 575.12 | 88.10 | 594.79 | 366.67 | 193.35 | 0.00 | 0.00 |
Maximum of Months | 1441.54 | 684.62 | 914.51 | 478.00 | 450.66 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 996.26 | 732.14 | 952.18 | 681.16 | 271.03 | 0.00 | 0.00 |
February | 1031.38 | 675.21 | 958.73 | 631.88 | 326.85 | 0.00 | 0.00 |
March | 841.62 | 539.05 | 762.30 | 391.76 | 370.53 | 0.00 | 0.00 |
April | 742.31 | 363.55 | 646.48 | 204.12 | 442.37 | 0.00 | 0.00 |
May | 594.56 | 255.17 | 497.90 | 85.86 | 412.04 | 0.00 | 0.00 |
June | 695.40 | 156.12 | 466.47 | 64.75 | 401.72 | 0.00 | 0.00 |
July | 787.87 | 95.24 | 480.44 | 62.96 | 417.48 | 0.00 | 0.00 |
August | 887.45 | 116.35 | 578.62 | 135.68 | 442.93 | 0.00 | 0.00 |
September | 1011.57 | 224.48 | 721.45 | 333.90 | 387.55 | 0.00 | 0.00 |
October | 1094.77 | 400.12 | 894.67 | 587.67 | 307.00 | 0.00 | 0.00 |
November | 1076.03 | 572.82 | 982.52 | 693.59 | 288.94 | 0.00 | 0.00 |
December | 1075.03 | 741.14 | 1020.11 | 788.49 | 231.62 | 0.00 | 0.00 |
Annual Sum or Average | 902.04 | 404.58 | 745.55 | 387.19 | 358.36 | 0.00 | 0.00 |
Minimum of Months | 594.56 | 95.24 | 466.47 | 62.96 | 231.62 | 0.00 | 0.00 |
Maximum of Months | 1094.77 | 741.14 | 1020.11 | 788.49 | 442.93 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.366398E+10 | 0.154513E+10 | 0.317828E+10 | 0.247164E+10 | 0.706641E+09 | 0.00 | 0.00 |
February | 0.332794E+10 | 0.128690E+10 | 0.282969E+10 | 0.207095E+10 | 0.758744E+09 | 0.00 | 0.00 |
March | 0.281188E+10 | 0.112997E+10 | 0.232958E+10 | 0.142153E+10 | 0.908056E+09 | 0.00 | 0.00 |
April | 0.217373E+10 | 0.760176E+09 | 0.173141E+10 | 0.709555E+09 | 0.102185E+10 | 0.00 | 0.00 |
May | 0.154758E+10 | 0.553581E+09 | 0.120409E+10 | 0.272398E+09 | 0.931695E+09 | 0.00 | 0.00 |
June | 0.147363E+10 | 0.344941E+09 | 0.974117E+09 | 0.116970E+09 | 0.857147E+09 | 0.00 | 0.00 |
July | 0.182853E+10 | 0.219697E+09 | 0.111423E+10 | 0.174830E+09 | 0.939397E+09 | 0.00 | 0.00 |
August | 0.235967E+10 | 0.268245E+09 | 0.151573E+10 | 0.478055E+09 | 0.103767E+10 | 0.00 | 0.00 |
September | 0.299509E+10 | 0.475461E+09 | 0.208236E+10 | 0.117218E+10 | 0.910172E+09 | 0.00 | 0.00 |
October | 0.373885E+10 | 0.858722E+09 | 0.289897E+10 | 0.213243E+10 | 0.766540E+09 | 0.00 | 0.00 |
November | 0.375916E+10 | 0.119334E+10 | 0.316463E+10 | 0.243556E+10 | 0.729074E+09 | 0.00 | 0.00 |
December | 0.401447E+10 | 0.158510E+10 | 0.346594E+10 | 0.286110E+10 | 0.604848E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.336945E+11 | 0.102213E+11 | 0.264890E+11 | 0.163172E+11 | 0.101718E+11 | 0.00 | 0.00 |
Minimum of Months | 0.147363E+10 | 0.219697E+09 | 0.974117E+09 | 0.116970E+09 | 0.604848E+09 | 0.00 | 0.00 |
Maximum of Months | 0.401447E+10 | 0.158510E+10 | 0.346594E+10 | 0.286110E+10 | 0.103767E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.102030E+11 | 0.463158E+10 | 0.894982E+10 | 0.695996E+10 | 0.198985E+10 | 0.00 | 0.00 |
February | 0.926816E+10 | 0.386777E+10 | 0.796823E+10 | 0.583165E+10 | 0.213657E+10 | 0.00 | 0.00 |
March | 0.779972E+10 | 0.343493E+10 | 0.655995E+10 | 0.400293E+10 | 0.255702E+10 | 0.00 | 0.00 |
April | 0.602198E+10 | 0.230269E+10 | 0.487553E+10 | 0.199806E+10 | 0.287747E+10 | 0.00 | 0.00 |
May | 0.426106E+10 | 0.168696E+10 | 0.339065E+10 | 0.767054E+09 | 0.262359E+10 | 0.00 | 0.00 |
June | 0.409203E+10 | 0.102323E+10 | 0.274305E+10 | 0.329380E+09 | 0.241367E+10 | 0.00 | 0.00 |
July | 0.510868E+10 | 0.631000E+09 | 0.313759E+10 | 0.492310E+09 | 0.264528E+10 | 0.00 | 0.00 |
August | 0.660173E+10 | 0.768701E+09 | 0.426819E+10 | 0.134617E+10 | 0.292202E+10 | 0.00 | 0.00 |
September | 0.837795E+10 | 0.138182E+10 | 0.586378E+10 | 0.330079E+10 | 0.256298E+10 | 0.00 | 0.00 |
October | 0.104497E+11 | 0.254097E+10 | 0.816330E+10 | 0.600478E+10 | 0.215853E+10 | 0.00 | 0.00 |
November | 0.104827E+11 | 0.358902E+10 | 0.891139E+10 | 0.685837E+10 | 0.205302E+10 | 0.00 | 0.00 |
December | 0.112009E+11 | 0.475776E+10 | 0.975987E+10 | 0.805665E+10 | 0.170321E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.938676E+11 | 0.306164E+11 | 0.745913E+11 | 0.459481E+11 | 0.286432E+11 | 0.00 | 0.00 |
Minimum of Months | 0.409203E+10 | 0.631000E+09 | 0.274305E+10 | 0.329380E+09 | 0.170321E+10 | 0.00 | 0.00 |
Maximum of Months | 0.112009E+11 | 0.475776E+10 | 0.975987E+10 | 0.805665E+10 | 0.292202E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.134581E+11 | 0.616529E+10 | 0.116263E+11 | 0.904139E+10 | 0.258493E+10 | 0.00 | 0.00 |
February | 0.122464E+11 | 0.513662E+10 | 0.103512E+11 | 0.757565E+10 | 0.277553E+10 | 0.00 | 0.00 |
March | 0.103148E+11 | 0.456427E+10 | 0.852175E+10 | 0.520003E+10 | 0.332172E+10 | 0.00 | 0.00 |
April | 0.800738E+10 | 0.304861E+10 | 0.633359E+10 | 0.259559E+10 | 0.373800E+10 | 0.00 | 0.00 |
May | 0.567499E+10 | 0.224331E+10 | 0.440464E+10 | 0.996447E+09 | 0.340819E+10 | 0.00 | 0.00 |
June | 0.546401E+10 | 0.135758E+10 | 0.356338E+10 | 0.427884E+09 | 0.313549E+10 | 0.00 | 0.00 |
July | 0.682574E+10 | 0.822170E+09 | 0.407591E+10 | 0.639539E+09 | 0.343637E+10 | 0.00 | 0.00 |
August | 0.878753E+10 | 0.993251E+09 | 0.554462E+10 | 0.174875E+10 | 0.379587E+10 | 0.00 | 0.00 |
September | 0.111016E+11 | 0.179250E+10 | 0.761738E+10 | 0.428792E+10 | 0.332946E+10 | 0.00 | 0.00 |
October | 0.138101E+11 | 0.333646E+10 | 0.106046E+11 | 0.780055E+10 | 0.280405E+10 | 0.00 | 0.00 |
November | 0.138365E+11 | 0.474444E+10 | 0.115764E+11 | 0.890941E+10 | 0.266700E+10 | 0.00 | 0.00 |
December | 0.147761E+11 | 0.632613E+10 | 0.126786E+11 | 0.104661E+11 | 0.221257E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.124303E+12 | 0.405306E+11 | 0.968984E+11 | 0.596892E+11 | 0.372092E+11 | 0.00 | 0.00 |
Minimum of Months | 0.546401E+10 | 0.822170E+09 | 0.356338E+10 | 0.427884E+09 | 0.221257E+10 | 0.00 | 0.00 |
Maximum of Months | 0.147761E+11 | 0.632613E+10 | 0.126786E+11 | 0.104661E+11 | 0.379587E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.112398E+10 | 0.884477E+09 | 0.108299E+10 | 0.747937E+09 | 0.335051E+09 | 0.00 | 0.00 |
February | 0.117902E+10 | 0.730928E+09 | 0.108697E+10 | 0.713832E+09 | 0.373143E+09 | 0.00 | 0.00 |
March | 0.126211E+10 | 0.628280E+09 | 0.111225E+10 | 0.627213E+09 | 0.485037E+09 | 0.00 | 0.00 |
April | 0.139562E+10 | 0.391079E+09 | 0.114914E+10 | 0.569686E+09 | 0.579457E+09 | 0.00 | 0.00 |
May | 0.133046E+10 | 0.272168E+09 | 0.103088E+10 | 0.463488E+09 | 0.567388E+09 | 0.00 | 0.00 |
June | 0.150023E+10 | 0.152880E+09 | 0.101013E+10 | 0.478424E+09 | 0.531702E+09 | 0.00 | 0.00 |
July | 0.156062E+10 | 72694448.19 | 0.983024E+09 | 0.407264E+09 | 0.575761E+09 | 0.00 | 0.00 |
August | 0.163943E+10 | 95058306.56 | 0.107988E+10 | 0.454855E+09 | 0.625021E+09 | 0.00 | 0.00 |
September | 0.154979E+10 | 0.210057E+09 | 0.109676E+10 | 0.593446E+09 | 0.503316E+09 | 0.00 | 0.00 |
October | 0.152460E+10 | 0.448338E+09 | 0.122099E+10 | 0.825128E+09 | 0.395867E+09 | 0.00 | 0.00 |
November | 0.121905E+10 | 0.658407E+09 | 0.111558E+10 | 0.769726E+09 | 0.345855E+09 | 0.00 | 0.00 |
December | 0.115505E+10 | 0.895552E+09 | 0.111995E+10 | 0.837122E+09 | 0.282831E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.164400E+11 | 0.543992E+10 | 0.130885E+11 | 0.748812E+10 | 0.560043E+10 | 0.00 | 0.00 |
Minimum of Months | 0.112398E+10 | 72694448.19 | 0.983024E+09 | 0.407264E+09 | 0.282831E+09 | 0.00 | 0.00 |
Maximum of Months | 0.163943E+10 | 0.895552E+09 | 0.122099E+10 | 0.837122E+09 | 0.625021E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.453714E+09 | 0.932396E+09 | 0.539737E+09 | 0.259253E+09 | 0.280485E+09 | 0.00 | 0.00 |
February | 0.577440E+09 | 0.755997E+09 | 0.623619E+09 | 0.304370E+09 | 0.319249E+09 | 0.00 | 0.00 |
March | 0.802110E+09 | 0.642341E+09 | 0.785916E+09 | 0.346157E+09 | 0.439758E+09 | 0.00 | 0.00 |
April | 0.110030E+10 | 0.398506E+09 | 0.972537E+09 | 0.431614E+09 | 0.540923E+09 | 0.00 | 0.00 |
May | 0.121638E+10 | 0.278688E+09 | 0.978164E+09 | 0.421674E+09 | 0.556490E+09 | 0.00 | 0.00 |
June | 0.148735E+10 | 0.150924E+09 | 0.102176E+10 | 0.489261E+09 | 0.532494E+09 | 0.00 | 0.00 |
July | 0.148945E+10 | 77242797.23 | 0.956240E+09 | 0.389192E+09 | 0.567048E+09 | 0.00 | 0.00 |
August | 0.141764E+10 | 0.101541E+09 | 0.959782E+09 | 0.364730E+09 | 0.595052E+09 | 0.00 | 0.00 |
September | 0.112414E+10 | 0.225575E+09 | 0.823788E+09 | 0.361784E+09 | 0.462004E+09 | 0.00 | 0.00 |
October | 0.871782E+09 | 0.477649E+09 | 0.754694E+09 | 0.403510E+09 | 0.351184E+09 | 0.00 | 0.00 |
November | 0.526540E+09 | 0.687816E+09 | 0.577715E+09 | 0.288175E+09 | 0.289540E+09 | 0.00 | 0.00 |
December | 0.405467E+09 | 0.950975E+09 | 0.507150E+09 | 0.271434E+09 | 0.235716E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.114723E+11 | 0.567965E+10 | 0.950110E+10 | 0.433116E+10 | 0.516994E+10 | 0.00 | 0.00 |
Minimum of Months | 0.405467E+09 | 77242797.23 | 0.507150E+09 | 0.259253E+09 | 0.235716E+09 | 0.00 | 0.00 |
Maximum of Months | 0.148945E+10 | 0.950975E+09 | 0.102176E+10 | 0.489261E+09 | 0.595052E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.555359E+09 | 0.305970E+09 | 0.502621E+09 | 0.390870E+09 | 0.111751E+09 | 0.00 | 0.00 |
February | 0.504122E+09 | 0.258780E+09 | 0.447495E+09 | 0.327504E+09 | 0.119991E+09 | 0.00 | 0.00 |
March | 0.417317E+09 | 0.234837E+09 | 0.368407E+09 | 0.224804E+09 | 0.143603E+09 | 0.00 | 0.00 |
April | 0.318871E+09 | 0.162239E+09 | 0.273811E+09 | 0.112211E+09 | 0.161600E+09 | 0.00 | 0.00 |
May | 0.218714E+09 | 0.124535E+09 | 0.190420E+09 | 43077608.47 | 0.147342E+09 | 0.00 | 0.00 |
June | 0.212371E+09 | 79996659.62 | 0.154051E+09 | 18497924.16 | 0.135553E+09 | 0.00 | 0.00 |
July | 0.269618E+09 | 55180178.65 | 0.176209E+09 | 27648028.33 | 0.148561E+09 | 0.00 | 0.00 |
August | 0.353785E+09 | 64982624.52 | 0.239703E+09 | 75600743.78 | 0.164102E+09 | 0.00 | 0.00 |
September | 0.455159E+09 | 0.103931E+09 | 0.329310E+09 | 0.185372E+09 | 0.143938E+09 | 0.00 | 0.00 |
October | 0.571044E+09 | 0.176928E+09 | 0.458451E+09 | 0.337227E+09 | 0.121224E+09 | 0.00 | 0.00 |
November | 0.572605E+09 | 0.242021E+09 | 0.500463E+09 | 0.385165E+09 | 0.115298E+09 | 0.00 | 0.00 |
December | 0.613778E+09 | 0.315273E+09 | 0.548113E+09 | 0.452460E+09 | 95652933.86 | 0.00 | 0.00 |
Annual Sum or Average | 0.506274E+10 | 0.212467E+10 | 0.418905E+10 | 0.258044E+10 | 0.160862E+10 | 0.00 | 0.00 |
Minimum of Months | 0.212371E+09 | 55180178.65 | 0.154051E+09 | 18497924.16 | 95652933.86 | 0.00 | 0.00 |
Maximum of Months | 0.613778E+09 | 0.315273E+09 | 0.548113E+09 | 0.452460E+09 | 0.164102E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 14746806.60 | 0.274094E+09 | 68128869.22 | 0.00 | 68128869.22 | 0.00 | 0.00 |
February | 29593211.49 | 0.219784E+09 | 76909365.24 | 0.00 | 76909365.24 | 0.00 | 0.00 |
March | 73685379.65 | 0.182144E+09 | 0.107427E+09 | 3734.29 | 0.107423E+09 | 0.00 | 0.00 |
April | 0.120988E+09 | 0.106681E+09 | 0.132599E+09 | 1776214.57 | 0.130822E+09 | 0.00 | 0.00 |
May | 0.173447E+09 | 72262714.78 | 0.148308E+09 | 9636032.37 | 0.138672E+09 | 0.00 | 0.00 |
June | 0.259371E+09 | 38106919.20 | 0.163407E+09 | 27174896.58 | 0.136232E+09 | 0.00 | 0.00 |
July | 0.270365E+09 | 17836596.97 | 0.154837E+09 | 13197555.76 | 0.141639E+09 | 0.00 | 0.00 |
August | 0.229398E+09 | 23673546.47 | 0.143695E+09 | 3516644.93 | 0.140179E+09 | 0.00 | 0.00 |
September | 0.150357E+09 | 57157165.36 | 0.111011E+09 | 79106.02 | 0.110932E+09 | 0.00 | 0.00 |
October | 72496800.86 | 0.130488E+09 | 85513450.69 | 0.00 | 85513450.69 | 0.00 | 0.00 |
November | 23600175.29 | 0.199845E+09 | 70278505.29 | 0.00 | 70278505.29 | 0.00 | 0.00 |
December | 4354523.40 | 0.285035E+09 | 57987978.73 | 0.00 | 57987978.73 | 0.00 | 0.00 |
Annual Sum or Average | 0.142240E+10 | 0.160711E+10 | 0.132010E+10 | 55384184.52 | 0.126472E+10 | 0.00 | 0.00 |
Minimum of Months | 4354523.40 | 17836596.97 | 57987978.73 | 0.00 | 57987978.73 | 0.00 | 0.00 |
Maximum of Months | 0.270365E+09 | 0.285035E+09 | 0.163407E+09 | 27174896.58 | 0.141639E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.108364E+10 | 0.866613E+09 | 0.106919E+10 | 0.735400E+09 | 0.333794E+09 | 0.00 | 0.00 |
February | 0.110082E+10 | 0.711976E+09 | 0.104162E+10 | 0.668634E+09 | 0.372986E+09 | 0.00 | 0.00 |
March | 0.131298E+10 | 0.602871E+09 | 0.116997E+10 | 0.685185E+09 | 0.484782E+09 | 0.00 | 0.00 |
April | 0.154824E+10 | 0.368394E+09 | 0.127358E+10 | 0.670222E+09 | 0.603355E+09 | 0.00 | 0.00 |
May | 0.149277E+10 | 0.260440E+09 | 0.115739E+10 | 0.577494E+09 | 0.579898E+09 | 0.00 | 0.00 |
June | 0.168380E+10 | 0.139939E+09 | 0.115205E+10 | 0.614113E+09 | 0.537942E+09 | 0.00 | 0.00 |
July | 0.177292E+10 | 69804399.32 | 0.113723E+10 | 0.558734E+09 | 0.578497E+09 | 0.00 | 0.00 |
August | 0.180805E+10 | 89437922.09 | 0.120721E+10 | 0.594733E+09 | 0.612480E+09 | 0.00 | 0.00 |
September | 0.160203E+10 | 0.198546E+09 | 0.114407E+10 | 0.641548E+09 | 0.502525E+09 | 0.00 | 0.00 |
October | 0.152397E+10 | 0.432174E+09 | 0.123250E+10 | 0.840301E+09 | 0.392202E+09 | 0.00 | 0.00 |
November | 0.121570E+10 | 0.648397E+09 | 0.112195E+10 | 0.772667E+09 | 0.349281E+09 | 0.00 | 0.00 |
December | 0.112210E+10 | 0.885818E+09 | 0.110297E+10 | 0.820466E+09 | 0.282502E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.172670E+11 | 0.527441E+10 | 0.138097E+11 | 0.817950E+10 | 0.563024E+10 | 0.00 | 0.00 |
Minimum of Months | 0.108364E+10 | 69804399.32 | 0.104162E+10 | 0.558734E+09 | 0.282502E+09 | 0.00 | 0.00 |
Maximum of Months | 0.180805E+10 | 0.885818E+09 | 0.127358E+10 | 0.840301E+09 | 0.612480E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.376631E+09 | 0.875453E+09 | 0.525943E+09 | 0.246716E+09 | 0.279227E+09 | 0.00 | 0.00 |
February | 0.479035E+09 | 0.713773E+09 | 0.578264E+09 | 0.259172E+09 | 0.319091E+09 | 0.00 | 0.00 |
March | 0.838935E+09 | 0.600507E+09 | 0.843632E+09 | 0.404129E+09 | 0.439503E+09 | 0.00 | 0.00 |
April | 0.125828E+10 | 0.375143E+09 | 0.109697E+10 | 0.532151E+09 | 0.564821E+09 | 0.00 | 0.00 |
May | 0.138058E+10 | 0.269208E+09 | 0.110468E+10 | 0.535680E+09 | 0.569001E+09 | 0.00 | 0.00 |
June | 0.166777E+10 | 0.146857E+09 | 0.116368E+10 | 0.624950E+09 | 0.538734E+09 | 0.00 | 0.00 |
July | 0.168852E+10 | 77047387.70 | 0.111045E+10 | 0.540662E+09 | 0.569784E+09 | 0.00 | 0.00 |
August | 0.157383E+10 | 98469176.54 | 0.108712E+10 | 0.504609E+09 | 0.582512E+09 | 0.00 | 0.00 |
September | 0.116779E+10 | 0.212010E+09 | 0.871099E+09 | 0.409886E+09 | 0.461213E+09 | 0.00 | 0.00 |
October | 0.853877E+09 | 0.439049E+09 | 0.766203E+09 | 0.418683E+09 | 0.347520E+09 | 0.00 | 0.00 |
November | 0.501228E+09 | 0.653736E+09 | 0.584081E+09 | 0.291116E+09 | 0.292966E+09 | 0.00 | 0.00 |
December | 0.344887E+09 | 0.910111E+09 | 0.490166E+09 | 0.254778E+09 | 0.235388E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.121314E+11 | 0.537136E+10 | 0.102223E+11 | 0.502253E+10 | 0.519976E+10 | 0.00 | 0.00 |
Minimum of Months | 0.344887E+09 | 77047387.70 | 0.490166E+09 | 0.246716E+09 | 0.235388E+09 | 0.00 | 0.00 |
Maximum of Months | 0.168852E+10 | 0.910111E+09 | 0.116368E+10 | 0.624950E+09 | 0.582512E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.124543E+10 | 0.111359E+10 | 0.123663E+10 | 0.846907E+09 | 0.389723E+09 | 0.00 | 0.00 |
February | 0.118706E+10 | 0.923932E+09 | 0.113621E+10 | 0.709611E+09 | 0.426598E+09 | 0.00 | 0.00 |
March | 0.111507E+10 | 0.816977E+09 | 0.103096E+10 | 0.487095E+09 | 0.543864E+09 | 0.00 | 0.00 |
April | 0.100336E+10 | 0.527391E+09 | 0.880524E+09 | 0.246977E+09 | 0.633547E+09 | 0.00 | 0.00 |
May | 0.890259E+09 | 0.376133E+09 | 0.733872E+09 | 0.114212E+09 | 0.619660E+09 | 0.00 | 0.00 |
June | 0.104934E+10 | 0.219195E+09 | 0.687780E+09 | 98949795.87 | 0.588830E+09 | 0.00 | 0.00 |
July | 0.119949E+10 | 0.135029E+09 | 0.717223E+09 | 88495919.93 | 0.628727E+09 | 0.00 | 0.00 |
August | 0.129109E+10 | 0.166311E+09 | 0.830662E+09 | 0.171424E+09 | 0.659238E+09 | 0.00 | 0.00 |
September | 0.134417E+10 | 0.323608E+09 | 0.954011E+09 | 0.401821E+09 | 0.552190E+09 | 0.00 | 0.00 |
October | 0.142056E+10 | 0.612338E+09 | 0.117859E+10 | 0.730677E+09 | 0.447909E+09 | 0.00 | 0.00 |
November | 0.130832E+10 | 0.849219E+09 | 0.123661E+10 | 0.834545E+09 | 0.402066E+09 | 0.00 | 0.00 |
December | 0.132822E+10 | 0.112297E+10 | 0.131323E+10 | 0.980355E+09 | 0.332875E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.143824E+11 | 0.718670E+10 | 0.119363E+11 | 0.571107E+10 | 0.622523E+10 | 0.00 | 0.00 |
Minimum of Months | 0.890259E+09 | 0.135029E+09 | 0.687780E+09 | 88495919.93 | 0.332875E+09 | 0.00 | 0.00 |
Maximum of Months | 0.142056E+10 | 0.112297E+10 | 0.131323E+10 | 0.980355E+09 | 0.659238E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.112033E+10 | 0.878282E+09 | 0.108299E+10 | 0.747937E+09 | 0.335051E+09 | 0.00 | 0.00 |
February | 0.117250E+10 | 0.726741E+09 | 0.108697E+10 | 0.713832E+09 | 0.373143E+09 | 0.00 | 0.00 |
March | 0.125446E+10 | 0.622744E+09 | 0.111225E+10 | 0.627213E+09 | 0.485037E+09 | 0.00 | 0.00 |
April | 0.138499E+10 | 0.385466E+09 | 0.114914E+10 | 0.569686E+09 | 0.579457E+09 | 0.00 | 0.00 |
May | 0.132078E+10 | 0.266743E+09 | 0.103088E+10 | 0.463488E+09 | 0.567388E+09 | 0.00 | 0.00 |
June | 0.149131E+10 | 0.148808E+09 | 0.101013E+10 | 0.478424E+09 | 0.531702E+09 | 0.00 | 0.00 |
July | 0.155152E+10 | 68757669.09 | 0.983024E+09 | 0.407264E+09 | 0.575761E+09 | 0.00 | 0.00 |
August | 0.162959E+10 | 91007664.87 | 0.107988E+10 | 0.454855E+09 | 0.625021E+09 | 0.00 | 0.00 |
September | 0.154092E+10 | 0.204426E+09 | 0.109676E+10 | 0.593446E+09 | 0.503316E+09 | 0.00 | 0.00 |
October | 0.151865E+10 | 0.441035E+09 | 0.122099E+10 | 0.825128E+09 | 0.395867E+09 | 0.00 | 0.00 |
November | 0.121522E+10 | 0.650303E+09 | 0.111558E+10 | 0.769726E+09 | 0.345855E+09 | 0.00 | 0.00 |
December | 0.115192E+10 | 0.888082E+09 | 0.111995E+10 | 0.837122E+09 | 0.282831E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.163522E+11 | 0.537240E+10 | 0.130885E+11 | 0.748812E+10 | 0.560043E+10 | 0.00 | 0.00 |
Minimum of Months | 0.112033E+10 | 68757669.09 | 0.983024E+09 | 0.407264E+09 | 0.282831E+09 | 0.00 | 0.00 |
Maximum of Months | 0.162959E+10 | 0.888082E+09 | 0.122099E+10 | 0.837122E+09 | 0.625021E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.454801E+09 | 0.923319E+09 | 0.539737E+09 | 0.259253E+09 | 0.280485E+09 | 0.00 | 0.00 |
February | 0.575481E+09 | 0.750168E+09 | 0.623619E+09 | 0.304370E+09 | 0.319249E+09 | 0.00 | 0.00 |
March | 0.797531E+09 | 0.636712E+09 | 0.785916E+09 | 0.346157E+09 | 0.439758E+09 | 0.00 | 0.00 |
April | 0.109044E+10 | 0.396423E+09 | 0.972537E+09 | 0.431614E+09 | 0.540923E+09 | 0.00 | 0.00 |
May | 0.120686E+10 | 0.275995E+09 | 0.978164E+09 | 0.421674E+09 | 0.556490E+09 | 0.00 | 0.00 |
June | 0.147834E+10 | 0.148872E+09 | 0.102176E+10 | 0.489261E+09 | 0.532494E+09 | 0.00 | 0.00 |
July | 0.148135E+10 | 73898648.15 | 0.956240E+09 | 0.389192E+09 | 0.567048E+09 | 0.00 | 0.00 |
August | 0.140984E+10 | 98525157.78 | 0.959782E+09 | 0.364730E+09 | 0.595052E+09 | 0.00 | 0.00 |
September | 0.111851E+10 | 0.220607E+09 | 0.823788E+09 | 0.361784E+09 | 0.462004E+09 | 0.00 | 0.00 |
October | 0.868732E+09 | 0.470423E+09 | 0.754694E+09 | 0.403510E+09 | 0.351184E+09 | 0.00 | 0.00 |
November | 0.527316E+09 | 0.675852E+09 | 0.577715E+09 | 0.288175E+09 | 0.289540E+09 | 0.00 | 0.00 |
December | 0.406836E+09 | 0.940435E+09 | 0.507150E+09 | 0.271434E+09 | 0.235716E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.114160E+11 | 0.561123E+10 | 0.950110E+10 | 0.433116E+10 | 0.516994E+10 | 0.00 | 0.00 |
Minimum of Months | 0.406836E+09 | 73898648.15 | 0.507150E+09 | 0.259253E+09 | 0.235716E+09 | 0.00 | 0.00 |
Maximum of Months | 0.148135E+10 | 0.940435E+09 | 0.102176E+10 | 0.489261E+09 | 0.595052E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.105555E+10 | 0.456416E+09 | 0.921610E+09 | 0.716703E+09 | 0.204907E+09 | 0.00 | 0.00 |
February | 0.959483E+09 | 0.376648E+09 | 0.820531E+09 | 0.600515E+09 | 0.220016E+09 | 0.00 | 0.00 |
March | 0.811257E+09 | 0.323087E+09 | 0.675515E+09 | 0.412202E+09 | 0.263313E+09 | 0.00 | 0.00 |
April | 0.635823E+09 | 0.199992E+09 | 0.502062E+09 | 0.205750E+09 | 0.296311E+09 | 0.00 | 0.00 |
May | 0.462840E+09 | 0.135040E+09 | 0.349156E+09 | 78987514.10 | 0.270168E+09 | 0.00 | 0.00 |
June | 0.462117E+09 | 71609655.81 | 0.282470E+09 | 33917970.31 | 0.248552E+09 | 0.00 | 0.00 |
July | 0.572836E+09 | 31862637.41 | 0.323098E+09 | 50695688.68 | 0.272402E+09 | 0.00 | 0.00 |
August | 0.718057E+09 | 43205892.42 | 0.439521E+09 | 0.138622E+09 | 0.300899E+09 | 0.00 | 0.00 |
September | 0.884785E+09 | 0.102373E+09 | 0.603826E+09 | 0.339900E+09 | 0.263927E+09 | 0.00 | 0.00 |
October | 0.109265E+10 | 0.225171E+09 | 0.840620E+09 | 0.618343E+09 | 0.222277E+09 | 0.00 | 0.00 |
November | 0.108924E+10 | 0.339717E+09 | 0.917654E+09 | 0.706242E+09 | 0.211412E+09 | 0.00 | 0.00 |
December | 0.116048E+10 | 0.466086E+09 | 0.100503E+10 | 0.829635E+09 | 0.175390E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.990512E+10 | 0.277121E+10 | 0.768109E+10 | 0.473151E+10 | 0.294957E+10 | 0.00 | 0.00 |
Minimum of Months | 0.462117E+09 | 31862637.41 | 0.282470E+09 | 33917970.31 | 0.175390E+09 | 0.00 | 0.00 |
Maximum of Months | 0.116048E+10 | 0.466086E+09 | 0.100503E+10 | 0.829635E+09 | 0.300899E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 61661193.33 | 0.277361E+10 | 0.596026E+09 | 0.00 | 0.596026E+09 | 0.00 | 0.00 |
February | 0.168074E+09 | 0.223856E+10 | 0.672842E+09 | 0.00 | 0.672842E+09 | 0.00 | 0.00 |
March | 0.505152E+09 | 0.188079E+10 | 0.939826E+09 | 32669.46 | 0.939794E+09 | 0.00 | 0.00 |
April | 0.896535E+09 | 0.112738E+10 | 0.116004E+10 | 15539229.06 | 0.114450E+10 | 0.00 | 0.00 |
May | 0.133448E+10 | 0.792291E+09 | 0.129747E+10 | 84300915.40 | 0.121317E+10 | 0.00 | 0.00 |
June | 0.209411E+10 | 0.461460E+09 | 0.142957E+10 | 0.237740E+09 | 0.119183E+10 | 0.00 | 0.00 |
July | 0.218526E+10 | 0.283711E+09 | 0.135459E+10 | 0.115459E+09 | 0.123913E+10 | 0.00 | 0.00 |
August | 0.182959E+10 | 0.342871E+09 | 0.125712E+10 | 30765399.66 | 0.122636E+10 | 0.00 | 0.00 |
September | 0.117564E+10 | 0.666221E+09 | 0.971182E+09 | 692059.69 | 0.970490E+09 | 0.00 | 0.00 |
October | 0.512312E+09 | 0.139211E+10 | 0.748115E+09 | 0.00 | 0.748115E+09 | 0.00 | 0.00 |
November | 0.123794E+09 | 0.207865E+10 | 0.614832E+09 | 0.00 | 0.614832E+09 | 0.00 | 0.00 |
December | 11232591.76 | 0.290781E+10 | 0.507308E+09 | 0.00 | 0.507308E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.108978E+11 | 0.169455E+11 | 0.115489E+11 | 0.484529E+09 | 0.110644E+11 | 0.00 | 0.00 |
Minimum of Months | 11232591.76 | 0.283711E+09 | 0.507308E+09 | 0.00 | 0.507308E+09 | 0.00 | 0.00 |
Maximum of Months | 0.218526E+10 | 0.290781E+10 | 0.142957E+10 | 0.237740E+09 | 0.123913E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 51312966.49 | 0.283521E+10 | 0.596026E+09 | 0.00 | 0.596026E+09 | 0.00 | 0.00 |
February | 0.153479E+09 | 0.228430E+10 | 0.672842E+09 | 0.00 | 0.672842E+09 | 0.00 | 0.00 |
March | 0.483581E+09 | 0.191698E+10 | 0.939826E+09 | 32669.46 | 0.939794E+09 | 0.00 | 0.00 |
April | 0.876089E+09 | 0.115042E+10 | 0.116004E+10 | 15539229.06 | 0.114450E+10 | 0.00 | 0.00 |
May | 0.131313E+10 | 0.810057E+09 | 0.129747E+10 | 84300915.40 | 0.121317E+10 | 0.00 | 0.00 |
June | 0.207472E+10 | 0.473820E+09 | 0.142957E+10 | 0.237740E+09 | 0.119183E+10 | 0.00 | 0.00 |
July | 0.216620E+10 | 0.295053E+09 | 0.135459E+10 | 0.115459E+09 | 0.123913E+10 | 0.00 | 0.00 |
August | 0.181133E+10 | 0.355508E+09 | 0.125712E+10 | 30765399.66 | 0.122636E+10 | 0.00 | 0.00 |
September | 0.116098E+10 | 0.683482E+09 | 0.971182E+09 | 692059.69 | 0.970490E+09 | 0.00 | 0.00 |
October | 0.497622E+09 | 0.142155E+10 | 0.748115E+09 | 0.00 | 0.748115E+09 | 0.00 | 0.00 |
November | 0.111300E+09 | 0.212431E+10 | 0.614832E+09 | 0.00 | 0.614832E+09 | 0.00 | 0.00 |
December | 8457367.76 | 0.297804E+10 | 0.507308E+09 | 0.00 | 0.507308E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.107082E+11 | 0.173287E+11 | 0.115489E+11 | 0.484529E+09 | 0.110644E+11 | 0.00 | 0.00 |
Minimum of Months | 8457367.76 | 0.295053E+09 | 0.507308E+09 | 0.00 | 0.507308E+09 | 0.00 | 0.00 |
Maximum of Months | 0.216620E+10 | 0.297804E+10 | 0.142957E+10 | 0.237740E+09 | 0.123913E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.155801E+10 | 0.180683E+10 | 0.159507E+10 | 0.982081E+09 | 0.612993E+09 | 0.00 | 0.00 |
February | 0.169401E+10 | 0.149672E+10 | 0.161981E+10 | 0.927770E+09 | 0.692045E+09 | 0.00 | 0.00 |
March | 0.233868E+10 | 0.129193E+10 | 0.201350E+10 | 0.108926E+10 | 0.924242E+09 | 0.00 | 0.00 |
April | 0.307350E+10 | 0.822703E+09 | 0.237042E+10 | 0.120230E+10 | 0.116812E+10 | 0.00 | 0.00 |
May | 0.317976E+10 | 0.615896E+09 | 0.226194E+10 | 0.111310E+10 | 0.114884E+10 | 0.00 | 0.00 |
June | 0.371741E+10 | 0.373854E+09 | 0.231560E+10 | 0.123898E+10 | 0.107662E+10 | 0.00 | 0.00 |
July | 0.386102E+10 | 0.235975E+09 | 0.224755E+10 | 0.109932E+10 | 0.114823E+10 | 0.00 | 0.00 |
August | 0.377568E+10 | 0.277244E+09 | 0.229420E+10 | 0.109927E+10 | 0.119493E+10 | 0.00 | 0.00 |
September | 0.309678E+10 | 0.469730E+09 | 0.201507E+10 | 0.105138E+10 | 0.963692E+09 | 0.00 | 0.00 |
October | 0.262453E+10 | 0.922649E+09 | 0.199861E+10 | 0.125892E+10 | 0.739687E+09 | 0.00 | 0.00 |
November | 0.184651E+10 | 0.134400E+10 | 0.170596E+10 | 0.106374E+10 | 0.642217E+09 | 0.00 | 0.00 |
December | 0.154040E+10 | 0.183368E+10 | 0.159307E+10 | 0.107521E+10 | 0.517867E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.323063E+11 | 0.114912E+11 | 0.240308E+11 | 0.132013E+11 | 0.108295E+11 | 0.00 | 0.00 |
Minimum of Months | 0.154040E+10 | 0.235975E+09 | 0.159307E+10 | 0.927770E+09 | 0.517867E+09 | 0.00 | 0.00 |
Maximum of Months | 0.386102E+10 | 0.183368E+10 | 0.237042E+10 | 0.125892E+10 | 0.119493E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.266839E+10 | 0.196095E+10 | 0.255033E+10 | 0.182441E+10 | 0.725921E+09 | 0.00 | 0.00 |
February | 0.249513E+10 | 0.163348E+10 | 0.231936E+10 | 0.152864E+10 | 0.790714E+09 | 0.00 | 0.00 |
March | 0.225420E+10 | 0.144379E+10 | 0.204173E+10 | 0.104929E+10 | 0.992439E+09 | 0.00 | 0.00 |
April | 0.192407E+10 | 0.942328E+09 | 0.167569E+10 | 0.529075E+09 | 0.114661E+10 | 0.00 | 0.00 |
May | 0.159247E+10 | 0.683448E+09 | 0.133357E+10 | 0.229965E+09 | 0.110361E+10 | 0.00 | 0.00 |
June | 0.180249E+10 | 0.404655E+09 | 0.120910E+10 | 0.167838E+09 | 0.104126E+10 | 0.00 | 0.00 |
July | 0.211023E+10 | 0.255101E+09 | 0.128682E+10 | 0.168628E+09 | 0.111819E+10 | 0.00 | 0.00 |
August | 0.237694E+10 | 0.311625E+09 | 0.154977E+10 | 0.363417E+09 | 0.118635E+10 | 0.00 | 0.00 |
September | 0.262199E+10 | 0.581851E+09 | 0.187000E+10 | 0.865470E+09 | 0.100453E+10 | 0.00 | 0.00 |
October | 0.293224E+10 | 0.107167E+10 | 0.239630E+10 | 0.157402E+10 | 0.822273E+09 | 0.00 | 0.00 |
November | 0.278907E+10 | 0.148474E+10 | 0.254670E+10 | 0.179778E+10 | 0.748927E+09 | 0.00 | 0.00 |
December | 0.287937E+10 | 0.198508E+10 | 0.273225E+10 | 0.211188E+10 | 0.620371E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.284466E+11 | 0.127587E+11 | 0.235116E+11 | 0.122104E+11 | 0.113012E+11 | 0.00 | 0.00 |
Minimum of Months | 0.159247E+10 | 0.255101E+09 | 0.120910E+10 | 0.167838E+09 | 0.620371E+09 | 0.00 | 0.00 |
Maximum of Months | 0.293224E+10 | 0.198508E+10 | 0.273225E+10 | 0.211188E+10 | 0.118635E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 2.60 | -1.3 | -7.5 | 3.29 | -12.5 | 38.91 | 220.14 | 0.00 |
February | 4.28 | 0.13 | -5.8 | 3.80 | -10.7 | 48.21 | 247.44 | 0.00 |
March | 8.76 | 2.64 | -5.5 | 4.72 | -6.0 | 66.36 | 249.43 | 0.00 |
April | 13.90 | 4.70 | -6.4 | 4.61 | -1.8 | 81.54 | 308.98 | 0.00 |
May | 17.82 | 8.42 | -1.1 | 4.68 | 3.61 | 77.67 | 310.50 | 0.00 |
June | 23.21 | 12.42 | 4.15 | 4.28 | 9.16 | 70.88 | 348.57 | 0.00 |
July | 25.63 | 16.13 | 10.74 | 4.00 | 14.07 | 80.74 | 308.61 | 0.00 |
August | 24.08 | 15.39 | 10.38 | 3.96 | 13.00 | 86.20 | 290.42 | 0.00 |
September | 20.49 | 12.87 | 7.70 | 3.48 | 8.22 | 67.00 | 274.65 | 0.00 |
October | 13.71 | 6.72 | -0.1 | 3.54 | -0.8 | 42.11 | 283.53 | 0.00 |
November | 6.96 | 1.72 | -4.9 | 3.43 | -7.6 | 39.44 | 239.51 | 0.01 |
December | 2.07 | -2.2 | -8.9 | 2.95 | -13.5 | 27.44 | 240.96 | 0.00 |
Annual Sum or Average | 13.68 | 6.50 | -0.6 | 3.90 | -0.3 | 60.60 | 276.96 | 0.00 |
Minimum of Months | 2.07 | -2.2 | -8.9 | 2.95 | -13.5 | 27.44 | 220.14 | 0.00 |
Maximum of Months | 25.63 | 16.13 | 10.74 | 4.72 | 14.07 | 86.20 | 348.57 | 0.01 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.10 | 01-JAN-14:00 | 5.83 | -6.7 | 5.20 | -2.3 | 27.00 | 880.00 |
February | 22.20 | 14-FEB-15:00 | 7.86 | -10.0 | 4.60 | 4.72 | 61.50 | 778.50 |
March | 22.80 | 08-MAR-13:00 | 9.68 | -2.8 | 3.60 | 4.92 | 122.50 | 851.50 |
April | 26.10 | 13-APR-16:00 | 10.32 | -4.4 | 5.20 | 7.55 | 95.00 | 507.00 |
May | 30.00 | 19-MAY-15:20 | 12.71 | -1.5 | 8.93 | 13.35 | 108.33 | 887.00 |
June | 38.90 | 28-JUN-15:00 | 14.16 | -8.9 | 3.10 | 20.75 | 70.00 | 888.00 |
July | 38.30 | 22-JUL-14:00 | 16.71 | 3.30 | 5.20 | 24.16 | 99.00 | 907.50 |
August | 35.00 | 01-AUG-14:00 | 16.30 | 4.40 | 2.60 | 19.52 | 113.00 | 840.50 |
September | 32.80 | 03-SEP-13:00 | 16.76 | 7.80 | 3.60 | 21.78 | 263.50 | 532.50 |
October | 28.90 | 01-OCT-15:00 | 13.26 | 1.70 | 4.10 | 15.94 | 85.00 | 435.00 |
November | 19.40 | 09-NOV-13:00 | 9.81 | 1.70 | 10.80 | 8.35 | 157.50 | 0.00 |
December | 13.30 | 24-DEC-14:00 | 4.02 | -8.3 | 8.20 | -2.5 | 40.50 | 792.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.30 | 4.02 | -10.0 | 2.60 | -2.5 | 27.00 | 0.00 | |
Maximum of Months | 38.90 | 16.76 | 7.80 | 10.80 | 24.16 | 263.50 | 907.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -8.3 | 20-JAN-01:00 | -8.3 | -8.3 | 2.10 | -25.6 | 0.00 | 0.00 |
February | -6.7 | 04-FEB-06:10 | -8.2 | -11.7 | 5.10 | -25.0 | 0.00 | 0.00 |
March | -3.9 | 05-MAR-06:00 | -5.7 | -9.4 | 1.50 | -21.6 | 17.00 | 434.50 |
April | 1.70 | 06-APR-05:00 | -2.4 | -8.3 | 2.60 | -12.9 | 28.00 | 215.00 |
May | 4.40 | 07-MAY-04:00 | -1.0 | -8.3 | 1.50 | -13.7 | 0.00 | 0.00 |
June | 7.80 | 09-JUN-04:40 | 5.54 | 3.30 | 4.83 | -7.8 | 0.00 | 0.00 |
July | 16.10 | 08-JUL-02:00 | 14.67 | 13.90 | 0.00 | 4.72 | 0.00 | 0.00 |
August | 12.80 | 31-AUG-05:00 | 10.77 | 9.40 | 3.10 | -1.7 | 24.50 | 228.50 |
September | 10.60 | 09-SEP-05:00 | 9.95 | 9.40 | 2.10 | -2.5 | 15.50 | 177.00 |
October | -2.8 | 26-OCT-04:10 | -4.1 | -6.1 | 2.42 | -17.7 | 0.00 | 0.00 |
November | -4.4 | 27-NOV-05:00 | -6.9 | -11.7 | 2.60 | -22.7 | 0.00 | 0.00 |
December | -9.4 | 15-DEC-04:00 | -12.1 | -21.7 | 0.00 | -29.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -9.4 | -12.1 | -21.7 | 0.00 | -29.7 | 0.00 | 0.00 | |
Maximum of Months | 16.10 | 14.67 | 13.90 | 5.10 | 4.72 | 28.00 | 434.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 6.84 | 05-JAN-13:00 | 16.10 | -2.8 | 3.10 | -0.1 | 62.00 | 873.00 |
February | 7.86 | 14-FEB-15:00 | 22.20 | -10.0 | 4.60 | 4.72 | 61.50 | 778.50 |
March | 9.68 | 08-MAR-13:00 | 22.80 | -2.8 | 3.60 | 4.92 | 122.50 | 851.50 |
April | 10.95 | 14-APR-15:00 | 24.40 | -0.6 | 8.20 | 17.21 | 237.00 | 154.00 |
May | 15.08 | 22-MAY-12:30 | 28.60 | 6.40 | 5.15 | 16.76 | 167.00 | 0.00 |
June | 18.19 | 24-JUN-13:00 | 31.70 | 11.70 | 2.60 | 19.17 | 130.00 | 891.50 |
July | 19.21 | 31-JUL-14:00 | 32.80 | 12.80 | 6.20 | 22.98 | 264.50 | 624.50 |
August | 19.18 | 26-AUG-12:00 | 27.80 | 15.60 | 3.60 | 17.03 | 289.00 | 426.50 |
September | 18.19 | 05-SEP-12:00 | 23.90 | 15.60 | 3.10 | 13.35 | 196.50 | 796.00 |
October | 16.16 | 11-OCT-10:00 | 23.90 | 12.20 | 13.40 | 13.73 | 219.50 | 450.00 |
November | 9.81 | 09-NOV-13:00 | 19.40 | 1.70 | 10.80 | 8.35 | 157.50 | 0.00 |
December | 4.92 | 01-DEC-15:00 | 12.80 | -3.9 | 2.10 | 1.58 | 50.00 | 276.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 4.92 | 12.80 | -10.0 | 2.10 | -0.1 | 50.00 | 0.00 | |
Maximum of Months | 19.21 | 32.80 | 15.60 | 13.40 | 22.98 | 289.00 | 891.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -0.6 | 28-JAN-17:00 | 6.10 | 3.01 | 4.60 | -5.0 | 0.00 | 0.00 |
February | 2.20 | 17-FEB-10:00 | 7.20 | 4.72 | 3.10 | -4.1 | 212.50 | 561.00 |
March | 5.60 | 28-MAR-17:10 | 8.80 | 7.05 | 4.60 | 3.37 | 35.00 | 0.67 |
April | 7.20 | 15-APR-06:00 | 13.30 | 9.79 | 7.20 | 6.35 | 116.00 | 422.00 |
May | 13.90 | 24-MAY-14:00 | 16.70 | 14.90 | 4.60 | 11.07 | 128.00 | 0.00 |
June | 13.30 | 30-JUN-13:00 | 26.70 | 17.72 | 6.70 | 20.75 | 170.00 | 126.50 |
July | 17.80 | 01-JUL-13:00 | 22.20 | 19.05 | 3.60 | 13.91 | 361.00 | 125.00 |
August | 17.20 | 26-AUG-09:00 | 21.70 | 18.59 | 2.60 | 11.65 | 243.50 | 681.50 |
September | 15.60 | 05-SEP-11:00 | 22.20 | 17.61 | 3.10 | 12.79 | 231.00 | 705.00 |
October | 13.90 | 02-OCT-16:00 | 20.60 | 16.04 | 6.20 | 13.54 | 38.50 | 65.00 |
November | 6.10 | 09-NOV-21:00 | 8.90 | 7.38 | 11.80 | 3.69 | 0.00 | 0.00 |
December | 1.10 | 25-DEC-08:00 | 2.20 | 1.65 | 2.10 | -4.1 | 54.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.6 | 2.20 | 1.65 | 2.10 | -5.0 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 26.70 | 19.05 | 11.80 | 20.75 | 361.00 | 705.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 11.28 | 25.87 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 10.91 | 34.17 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 12.10 | 41.92 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 14.59 | 56.24 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 17.73 | 59.47 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 20.66 | 62.98 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 22.59 | 61.22 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 23.01 | 57.83 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 21.78 | 48.11 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 19.25 | 37.89 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 16.11 | 28.37 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 13.20 | 24.17 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 16.97 | 44.90 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 10.91 | 24.17 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 23.01 | 62.98 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH LAUNDRY G WATER HEATER
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.121804E+12 | -0.120048E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175662E+10 | 82.17 | 0.00 | 0.00 |
February | 0.110582E+12 | -0.108990E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.159136E+10 | 82.17 | 0.00 | 0.00 |
March | 0.120432E+12 | -0.118662E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.176982E+10 | 82.17 | 0.00 | 0.00 |
April | 0.112461E+12 | -0.110747E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.171393E+10 | 82.17 | 0.00 | 0.00 |
May | 0.110895E+12 | -0.109126E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.176908E+10 | 82.17 | 0.00 | 0.00 |
June | 0.102504E+12 | -0.100798E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.170623E+10 | 82.17 | 0.00 | 0.00 |
July | 0.102641E+12 | -0.100883E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175863E+10 | 82.17 | 0.00 | 0.00 |
August | 0.101937E+12 | -0.100180E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175660E+10 | 82.17 | 0.00 | 0.00 |
September | 0.100660E+12 | -0.989618E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.169829E+10 | 82.17 | 0.00 | 0.00 |
October | 0.108301E+12 | -0.106547E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175420E+10 | 82.17 | 0.00 | 0.00 |
November | 0.109957E+12 | -0.108260E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.169732E+10 | 82.17 | 0.00 | 0.00 |
December | 0.118551E+12 | -0.116797E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175437E+10 | 82.17 | 0.00 | 0.00 |
Annual Sum or Average | 0.132073E+13 | -0.130000E+13 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.207264E+11 | 82.17 | 0.00 | 0.00 |
Minimum of Months | 0.100660E+12 | -0.120048E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.176982E+10 | 82.17 | 0.00 | 0.00 |
Maximum of Months | 0.121804E+12 | -0.989618E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.159136E+10 | 82.17 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.804731E+10 | -0.788296E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164347882.1 | 82.17 | 0.00 | 0.00 |
February | 0.727177E+10 | -0.712336E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -148411411.8 | 82.17 | 0.00 | 0.00 |
March | 0.804576E+10 | -0.788155E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164207655.2 | 82.17 | 0.00 | 0.00 |
April | 0.779705E+10 | -0.763820E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -158847186.3 | 82.17 | 0.00 | 0.00 |
May | 0.804708E+10 | -0.788296E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164119061.9 | 82.17 | 0.00 | 0.00 |
June | 0.778858E+10 | -0.762976E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -158812945.0 | 82.17 | 0.00 | 0.00 |
July | 0.805550E+10 | -0.789140E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164101915.2 | 82.17 | 0.00 | 0.00 |
August | 0.804706E+10 | -0.788296E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164102138.8 | 82.17 | 0.00 | 0.00 |
September | 0.779842E+10 | -0.763961E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -158812034.2 | 82.17 | 0.00 | 0.00 |
October | 0.804570E+10 | -0.788155E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164150202.5 | 82.17 | 0.00 | 0.00 |
November | 0.778026E+10 | -0.762132E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -158939071.0 | 82.17 | 0.00 | 0.00 |
December | 0.805575E+10 | -0.789140E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164352288.2 | 82.17 | 0.00 | 0.00 |
Annual Sum or Average | 0.947803E+11 | -0.928471E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.193320E+10 | 82.17 | 0.00 | 0.00 |
Minimum of Months | 0.727177E+10 | -0.789140E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -164352288.2 | 82.17 | 0.00 | 0.00 |
Maximum of Months | 0.805575E+10 | -0.712336E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -148411411.8 | 82.17 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.727071E+11 | -0.711963E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.151080E+10 | 60.05 | 0.00 | 0.00 |
February | 0.661741E+11 | -0.648030E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.137116E+10 | 60.05 | 0.00 | 0.00 |
March | 0.715920E+11 | -0.700629E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.152910E+10 | 60.05 | 0.00 | 0.00 |
April | 0.657165E+11 | -0.642351E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.148144E+10 | 60.05 | 0.00 | 0.00 |
May | 0.633258E+11 | -0.617978E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.152808E+10 | 60.05 | 0.00 | 0.00 |
June | 0.571436E+11 | -0.556729E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.147076E+10 | 60.05 | 0.00 | 0.00 |
July | 0.561596E+11 | -0.546460E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.151358E+10 | 60.05 | 0.00 | 0.00 |
August | 0.556060E+11 | -0.540952E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.151078E+10 | 60.05 | 0.00 | 0.00 |
September | 0.555209E+11 | -0.540611E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.145976E+10 | 60.05 | 0.00 | 0.00 |
October | 0.610435E+11 | -0.595361E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.150745E+10 | 60.05 | 0.00 | 0.00 |
November | 0.635203E+11 | -0.620619E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.145841E+10 | 60.05 | 0.00 | 0.00 |
December | 0.698925E+11 | -0.683848E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.150768E+10 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.758402E+12 | -0.740553E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.178490E+11 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.555209E+11 | -0.711963E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.152910E+10 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.727071E+11 | -0.540611E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.137116E+10 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: LOBBY_FLR_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.87 | 0.86 | 01-JAN-07:40 | 9371.91 | 38.05 | 292.33 | 289.33 | 1586.89 | 28.56 | 224.17 | 276.17 |
February | 282.00 | 0.87 | 0.86 | 01-FEB-07:49 | 10946.29 | 36.91 | 265.17 | 275.83 | 926.17 | 25.01 | 197.00 | 255.67 |
March | 351.33 | 0.87 | 0.86 | 01-MAR-07:10 | 1730.64 | 21.55 | 103.67 | 332.50 | 586.81 | 21.95 | 207.50 | 281.00 |
April | 381.83 | 0.87 | 0.86 | 01-APR-06:00 | 1252.59 | 20.61 | 112.00 | 354.83 | 525.66 | 22.33 | 311.50 | 313.50 |
May | 378.00 | 0.87 | 0.86 | 01-MAY-06:40 | 951.02 | 20.15 | 33.17 | 378.33 | 410.29 | 21.90 | 289.33 | 311.67 |
June | 412.83 | 0.88 | 0.86 | 01-JUN-06:30 | 740.18 | 19.36 | 21.00 | 375.67 | 318.63 | 21.16 | 152.00 | 204.00 |
July | 395.33 | 0.87 | 0.86 | 01-JUL-07:10 | 916.77 | 19.86 | 43.33 | 379.17 | 391.01 | 21.65 | 249.17 | 291.50 |
August | 408.83 | 0.87 | 0.86 | 01-AUG-06:49 | 1173.21 | 20.33 | 115.50 | 376.00 | 490.45 | 22.07 | 294.67 | 322.17 |
September | 359.33 | 0.87 | 0.86 | 01-SEP-07:10 | 1295.74 | 20.30 | 90.83 | 331.83 | 543.81 | 22.08 | 238.00 | 286.33 |
October | 329.00 | 0.87 | 0.86 | 01-OCT-07:19 | 5895.25 | 29.33 | 198.00 | 321.33 | 674.21 | 22.70 | 191.00 | 293.50 |
November | 284.17 | 0.87 | 0.86 | 01-NOV-06:49 | 10685.46 | 38.77 | 278.67 | 284.50 | 1447.99 | 28.16 | 232.83 | 272.33 |
December | 265.67 | 0.87 | 0.86 | 01-DEC-07:49 | 10685.91 | 40.20 | 263.83 | 271.00 | 2639.11 | 31.75 | 208.50 | 258.67 |
Annual Sum or Average | 4149.83 | 0.87 | 4045.08 | 25.96 | 1817.50 | 3970.33 | 799.56 | 23.70 | 2795.67 | 3366.50 | ||
Minimum of Months | 265.67 | 0.87 | 0.86 | 740.18 | 19.36 | 21.00 | 271.00 | 318.63 | 21.16 | 152.00 | 204.00 | |
Maximum of Months | 412.83 | 0.88 | 0.86 | 10946.29 | 40.20 | 292.33 | 379.17 | 2639.11 | 31.75 | 311.50 | 322.17 |
Report: DaylightingReportMonthly
For: CAFE_FLR_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.24 | 0.22 | 01-JAN-07:40 | 9936.99 | 38.13 | 292.50 | 295.33 | 2150.46 | 28.01 | 204.83 | 285.33 |
February | 282.00 | 0.25 | 0.22 | 01-FEB-07:40 | 11509.82 | 36.96 | 261.17 | 282.67 | 1488.05 | 24.47 | 176.17 | 268.00 |
March | 351.33 | 0.26 | 0.22 | 01-MAR-06:00 | 2124.21 | 21.53 | 114.83 | 342.50 | 979.56 | 21.83 | 194.33 | 315.50 |
April | 381.83 | 0.26 | 0.22 | 01-APR-06:40 | 1541.69 | 20.93 | 136.00 | 363.67 | 814.06 | 22.49 | 305.83 | 343.00 |
May | 378.00 | 0.26 | 0.22 | 01-MAY-06:19 | 1162.16 | 20.69 | 91.83 | 387.83 | 620.91 | 22.25 | 303.17 | 357.00 |
June | 412.83 | 0.26 | 0.22 | 01-JUN-05:00 | 904.99 | 20.08 | 55.17 | 395.50 | 483.02 | 21.68 | 210.33 | 350.33 |
July | 395.33 | 0.26 | 0.22 | 01-JUL-06:49 | 1110.92 | 20.49 | 92.67 | 392.67 | 584.64 | 22.07 | 289.33 | 357.33 |
August | 408.83 | 0.26 | 0.22 | 01-AUG-06:19 | 1421.11 | 20.78 | 161.50 | 385.67 | 737.72 | 22.34 | 307.67 | 361.33 |
September | 359.33 | 0.26 | 0.22 | 01-SEP-06:40 | 1649.66 | 20.41 | 105.67 | 343.83 | 896.94 | 22.04 | 213.50 | 318.17 |
October | 329.00 | 0.26 | 0.22 | 01-OCT-06:49 | 6391.98 | 29.20 | 190.50 | 326.17 | 1169.67 | 22.26 | 152.17 | 312.50 |
November | 284.17 | 0.24 | 0.22 | 01-NOV-06:49 | 11286.17 | 38.84 | 278.67 | 290.33 | 2049.71 | 27.58 | 190.00 | 279.67 |
December | 265.67 | 0.24 | 0.22 | 01-DEC-07:49 | 11363.33 | 40.25 | 264.00 | 276.00 | 3319.21 | 31.11 | 178.50 | 268.67 |
Annual Sum or Average | 4149.83 | 0.26 | 4417.43 | 26.23 | 2044.50 | 4082.17 | 1171.42 | 23.66 | 2725.83 | 3816.83 | ||
Minimum of Months | 265.67 | 0.24 | 0.22 | 904.99 | 20.08 | 55.17 | 276.00 | 483.02 | 21.68 | 152.17 | 268.00 | |
Maximum of Months | 412.83 | 0.26 | 0.22 | 11509.82 | 40.25 | 292.50 | 395.50 | 3319.21 | 31.11 | 307.67 | 361.33 |
Report: DaylightingReportMonthly
For: DINING_FLR_6_DAYLCTRL
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.68 | 0.60 | 02-JAN-11:39 | 402.23 | 15.00 | 0.00 | 247.33 | 200.01 | 18.59 | 0.00 | 119.17 |
February | 282.00 | 0.66 | 0.60 | 01-FEB-08:30 | 458.03 | 15.75 | 0.00 | 260.67 | 234.83 | 19.26 | 2.50 | 140.67 |
March | 351.33 | 0.65 | 0.60 | 01-MAR-07:30 | 565.68 | 16.57 | 0.00 | 329.33 | 267.98 | 19.89 | 38.17 | 192.83 |
April | 381.83 | 0.62 | 0.60 | 01-APR-06:00 | 717.10 | 18.11 | 0.00 | 366.17 | 341.01 | 21.33 | 167.00 | 337.50 |
May | 378.00 | 0.62 | 0.60 | 01-MAY-06:30 | 867.27 | 18.46 | 4.33 | 398.33 | 367.55 | 21.60 | 167.83 | 360.33 |
June | 412.83 | 0.62 | 0.60 | 01-JUN-05:40 | 910.83 | 20.36 | 74.00 | 409.50 | 349.48 | 21.90 | 164.50 | 336.00 |
July | 395.33 | 0.61 | 0.60 | 01-JUL-06:49 | 880.84 | 19.17 | 27.00 | 401.50 | 379.36 | 21.69 | 187.17 | 367.33 |
August | 408.83 | 0.62 | 0.60 | 01-AUG-05:49 | 776.51 | 18.16 | 0.00 | 389.50 | 377.45 | 21.42 | 204.50 | 364.50 |
September | 359.33 | 0.64 | 0.60 | 01-SEP-06:40 | 586.57 | 17.06 | 0.00 | 336.33 | 287.39 | 20.37 | 80.33 | 257.50 |
October | 329.00 | 0.68 | 0.60 | 01-OCT-11:30 | 400.26 | 15.53 | 0.00 | 294.00 | 211.48 | 19.03 | 1.00 | 147.50 |
November | 284.17 | 0.66 | 0.60 | 01-NOV-07:40 | 414.60 | 15.48 | 0.00 | 263.17 | 218.23 | 19.07 | 0.00 | 161.33 |
December | 265.67 | 0.69 | 0.60 | 01-DEC-08:30 | 333.04 | 14.24 | 0.00 | 235.17 | 183.50 | 17.98 | 0.00 | 99.17 |
Annual Sum or Average | 4149.83 | 0.64 | 636.48 | 17.23 | 105.33 | 3931.00 | 294.47 | 20.36 | 1013.00 | 2883.83 | ||
Minimum of Months | 265.67 | 0.61 | 0.60 | 333.04 | 14.24 | 0.00 | 235.17 | 183.50 | 17.98 | 0.00 | 99.17 | |
Maximum of Months | 412.83 | 0.69 | 0.60 | 910.83 | 20.36 | 74.00 | 409.50 | 379.36 | 21.90 | 204.50 | 367.33 |
Report: DaylightingReportMonthly
For: BANQUET_FLR_6_DAYLCTRL
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.68 | 0.60 | 02-JAN-11:39 | 402.23 | 15.00 | 0.00 | 247.33 | 200.01 | 18.59 | 0.00 | 119.17 |
February | 282.00 | 0.66 | 0.60 | 01-FEB-08:30 | 458.03 | 15.75 | 0.00 | 260.67 | 234.83 | 19.26 | 2.50 | 140.67 |
March | 351.33 | 0.65 | 0.60 | 01-MAR-07:30 | 565.68 | 16.57 | 0.00 | 329.33 | 267.98 | 19.89 | 38.33 | 192.83 |
April | 381.83 | 0.62 | 0.60 | 01-APR-06:00 | 717.10 | 18.11 | 0.00 | 366.17 | 341.01 | 21.33 | 167.00 | 337.50 |
May | 378.00 | 0.62 | 0.60 | 01-MAY-06:30 | 867.27 | 18.46 | 4.33 | 398.33 | 367.55 | 21.60 | 167.83 | 360.33 |
June | 412.83 | 0.62 | 0.60 | 01-JUN-05:40 | 910.83 | 20.36 | 74.00 | 409.50 | 349.48 | 21.90 | 164.50 | 336.00 |
July | 395.33 | 0.61 | 0.60 | 01-JUL-06:49 | 880.84 | 19.17 | 27.00 | 401.50 | 379.36 | 21.69 | 187.17 | 367.33 |
August | 408.83 | 0.62 | 0.60 | 01-AUG-05:49 | 776.51 | 18.16 | 0.00 | 389.50 | 377.45 | 21.42 | 204.50 | 364.50 |
September | 359.33 | 0.64 | 0.60 | 01-SEP-06:40 | 586.57 | 17.06 | 0.00 | 336.33 | 287.39 | 20.37 | 80.33 | 257.50 |
October | 329.00 | 0.68 | 0.60 | 01-OCT-11:30 | 400.26 | 15.53 | 0.00 | 294.00 | 211.48 | 19.03 | 1.00 | 147.50 |
November | 284.17 | 0.66 | 0.60 | 01-NOV-07:40 | 414.60 | 15.48 | 0.00 | 263.17 | 218.23 | 19.07 | 0.00 | 161.33 |
December | 265.67 | 0.69 | 0.60 | 01-DEC-08:30 | 333.04 | 14.24 | 0.00 | 235.17 | 183.50 | 17.98 | 0.00 | 99.17 |
Annual Sum or Average | 4149.83 | 0.64 | 636.48 | 17.23 | 105.33 | 3931.00 | 294.47 | 20.36 | 1013.17 | 2883.83 | ||
Minimum of Months | 265.67 | 0.61 | 0.60 | 333.04 | 14.24 | 0.00 | 235.17 | 183.50 | 17.98 | 0.00 | 99.17 | |
Maximum of Months | 412.83 | 0.69 | 0.60 | 910.83 | 20.36 | 74.00 | 409.50 | 379.36 | 21.90 | 204.50 | 367.33 |
Report: CoilReportMonthly
For: FLR_3_DOAS HEATING COIL
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.542438E+09 | 2620.71 | 20-JAN-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.280905E+09 | 2031.49 | 01-FEB-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 10394084.45 | 1007.81 | 05-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11344.00 | 0.42 | 13-APR-23:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 20680.71 | 0.42 | 12-MAY-19:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 30215.22 | 0.42 | 18-JUN-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 30660.66 | 0.42 | 17-JUL-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 30814.97 | 0.42 | 13-AUG-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 30418.50 | 0.42 | 12-SEP-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 7733983.18 | 607.96 | 26-OCT-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 27119694.41 | 1188.79 | 27-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.486629E+09 | 3008.36 | 15-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.135537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 11344.00 | 0.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.542438E+09 | 3008.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.602160E+11 | 145742.40 | 10-JAN-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.571858E+11 | 146832.44 | 06-FEB-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.808740E+11 | 146618.03 | 10-MAR-08:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.619512E+11 | 134276.57 | 23-APR-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.315691E+11 | 120066.65 | 07-MAY-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.524448E+10 | 88616.64 | 09-JUN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 46174728.60 | 17844.92 | 31-AUG-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.373129E+10 | 53425.31 | 20-SEP-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.537152E+11 | 140309.98 | 13-OCT-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.756337E+11 | 145907.82 | 07-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.666338E+11 | 147103.27 | 09-DEC-11:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.496801E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.808740E+11 | 147103.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.487172E+09 | 1301.53 | 19-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.285332E+09 | 1133.53 | 06-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.129242E+09 | 944.13 | 04-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16451394.55 | 431.27 | 08-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 10271058.68 | 405.86 | 05-MAY-07:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 10679.71 | 40.08 | 09-JUN-07:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 67894901.77 | 1092.37 | 26-OCT-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.120533E+09 | 800.26 | 11-NOV-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.461984E+09 | 1376.54 | 09-DEC-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.157889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.487172E+09 | 1376.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 44106748.12 | 464.82 | 20-JAN-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6882387.84 | 263.99 | 06-FEB-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5108680.83 | 172.74 | 08-DEC-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 56097816.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 44106748.12 | 464.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 89299109.10 | 381.96 | 19-JAN-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 38230124.53 | 273.58 | 06-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 72068182.84 | 262.43 | 08-DEC-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.199597E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 89299109.10 | 381.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 54024773.67 | 2048.46 | 20-JAN-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5157689.73 | 944.60 | 16-FEB-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6421162.13 | 891.17 | 25-OCT-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 23281695.74 | 1956.66 | 08-DEC-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 88885321.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 54024773.67 | 2048.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.568664E+09 | 4326.71 | 20-JAN-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 59539883.00 | 3046.53 | 06-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.249666E+09 | 3367.55 | 08-DEC-11:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.877870E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.568664E+09 | 4326.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.952470E+09 | 2699.91 | 21-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.475341E+09 | 2413.75 | 06-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 45027138.88 | 1278.01 | 04-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 33867032.90 | 1659.68 | 26-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 63804455.08 | 1210.04 | 27-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.101189E+10 | 2588.26 | 15-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.258240E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.101189E+10 | 2699.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.164028E+10 | 5399.03 | 17-JAN-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.105468E+10 | 5309.70 | 06-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.417028E+09 | 3677.00 | 22-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 52095045.67 | 2883.42 | 30-APR-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 19663369.31 | 3641.26 | 24-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2663258.49 | 2869.39 | 08-JUN-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 622340.62 | 1422.04 | 28-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2021050.00 | 2089.92 | 28-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2933500.55 | 1823.12 | 23-SEP-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.177465E+09 | 5279.75 | 25-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.519219E+09 | 4613.38 | 10-NOV-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.166809E+10 | 5407.85 | 21-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.555676E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 622340.62 | 1422.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.166809E+10 | 5407.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.275858E+10 | 5415.42 | 18-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.179701E+10 | 5414.81 | 06-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.651375E+09 | 5239.38 | 04-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 68964735.56 | 2895.81 | 03-APR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17895430.44 | 3406.80 | 24-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1672159.34 | 2068.35 | 08-JUN-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 127392.70 | 834.63 | 29-JUL-21:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 419793.48 | 1247.13 | 30-AUG-21:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1518253.24 | 2249.89 | 18-SEP-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.283759E+09 | 5340.46 | 26-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.109968E+10 | 5317.93 | 27-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.304387E+10 | 5415.06 | 22-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.972488E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 127392.70 | 834.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.304387E+10 | 5415.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.828539E+10 | 30094.50 | 19-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.509850E+10 | 29934.92 | 06-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.722958E+09 | 29401.93 | 23-MAR-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 41197184.92 | 19633.81 | 08-APR-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 9943001.57 | 18076.21 | 03-MAY-15:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1291631.55 | 6677.54 | 08-JUN-08:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 126053.74 | 1680.72 | 26-JUL-08:58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 801235.49 | 5891.75 | 29-AUG-08:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3260717.83 | 11908.89 | 21-SEP-08:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.411933E+09 | 27009.01 | 29-OCT-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.226982E+10 | 29879.29 | 27-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.102966E+11 | 30346.83 | 21-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.271419E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 126053.74 | 1680.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.102966E+11 | 30346.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.175180E+10 | 5304.11 | 18-JAN-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.114192E+10 | 5228.26 | 16-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.418609E+09 | 3610.77 | 22-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 55561962.31 | 2255.61 | 07-APR-18:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11787229.32 | 2331.73 | 04-MAY-18:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 551360.58 | 1989.56 | 08-JUN-18:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 262927.36 | 922.84 | 23-SEP-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.182585E+09 | 5171.36 | 25-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.567924E+09 | 4510.67 | 10-NOV-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.175953E+10 | 5273.49 | 08-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.589053E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.175953E+10 | 5304.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.283079E+10 | 5310.90 | 20-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.186986E+10 | 5261.69 | 16-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.619879E+09 | 4217.08 | 22-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 80557066.52 | 2229.44 | 08-APR-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 13203838.40 | 2376.53 | 04-MAY-18:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 357212.22 | 1931.70 | 08-JUN-18:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 163221.60 | 1177.76 | 30-AUG-21:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 555839.26 | 1524.02 | 08-SEP-21:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.275550E+09 | 5179.08 | 25-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.109862E+10 | 5156.85 | 27-NOV-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.308388E+10 | 5310.00 | 21-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.987342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.308388E+10 | 5310.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.722926E+09 | 1634.35 | 19-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.489249E+09 | 1634.27 | 16-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.258603E+09 | 1597.86 | 22-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 58072919.21 | 707.00 | 18-APR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 21801646.20 | 956.28 | 03-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3399884.28 | 668.71 | 20-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 563606.17 | 456.27 | 17-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 761130.25 | 449.40 | 23-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1232125.82 | 540.32 | 08-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.114267E+09 | 1626.77 | 25-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.308643E+09 | 1601.78 | 10-NOV-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.730519E+09 | 1634.08 | 08-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.271004E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 563606.17 | 449.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.730519E+09 | 1634.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.110805E+10 | 1631.51 | 13-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.745538E+09 | 1631.46 | 02-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.352729E+09 | 1603.49 | 04-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 63914757.28 | 911.49 | 07-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 19511668.97 | 939.87 | 24-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2543578.59 | 657.46 | 08-JUN-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 79879.52 | 254.76 | 09-JUL-21:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 141377.62 | 394.91 | 31-AUG-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 842320.39 | 630.42 | 17-SEP-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.166671E+09 | 1631.39 | 26-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.558985E+09 | 1631.26 | 28-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.119425E+10 | 1631.51 | 26-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.421326E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 79879.52 | 254.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.119425E+10 | 1631.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.127192E+10 | 7495.20 | 19-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.841883E+09 | 7455.47 | 16-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.420894E+09 | 5197.55 | 22-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.116482E+09 | 3224.54 | 04-APR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 51254626.38 | 4116.17 | 03-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2966775.15 | 3263.24 | 04-JUN-18:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 20063.78 | 234.08 | 11-JUL-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1252736.41 | 2576.57 | 23-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 398322.44 | 1500.62 | 05-SEP-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.192988E+09 | 7399.28 | 25-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.370273E+09 | 5055.17 | 09-NOV-16:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.122525E+10 | 7458.97 | 08-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.449558E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 20063.78 | 234.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.127192E+10 | 7495.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 28570337.31 | 28570337.31 | 2387.65 | 05-JAN-14:00 | 2387.65 | 0.00 |
February | 0.00 | 0.00 | 0.355265E+09 | 0.355265E+09 | 12481.81 | 14-FEB-16:01 | 12481.81 | 0.00 |
March | 0.00 | 0.00 | 0.140706E+10 | 0.140706E+10 | 13329.91 | 08-MAR-16:02 | 13329.91 | 0.00 |
April | 0.00 | 0.00 | 0.584266E+10 | 0.584266E+10 | 14831.72 | 29-APR-15:02 | 14831.72 | 0.00 |
May | 0.00 | 0.00 | 0.112570E+11 | 0.112568E+11 | 16218.48 | 19-MAY-15:02 | 16218.48 | 0.13 |
June | 0.00 | 0.00 | 0.191799E+11 | 0.191374E+11 | 18782.37 | 28-JUN-15:02 | 18782.37 | 0.39 |
July | 0.00 | 0.00 | 0.300006E+11 | 0.258977E+11 | 28666.71 | 01-JUL-01:07 | 11556.10 | 0.77 |
August | 0.00 | 0.00 | 0.258740E+11 | 0.235240E+11 | 24316.33 | 13-AUG-08:51 | 12961.15 | 0.79 |
September | 0.00 | 0.00 | 0.155563E+11 | 0.152250E+11 | 23826.72 | 05-SEP-12:30 | 14001.63 | 0.54 |
October | 0.00 | 0.00 | 0.634340E+10 | 0.630600E+10 | 15766.09 | 01-OCT-15:02 | 15766.09 | 0.12 |
November | 0.00 | 0.00 | 0.142367E+09 | 0.142367E+09 | 8394.06 | 09-NOV-14:00 | 8394.06 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.115987E+12 | 0.109123E+12 | 0.23 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.300006E+11 | 0.258977E+11 | 28666.71 | 18782.37 | 0.79 |
Report: CoilReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.107850E+10 | 0.107850E+10 | 34757.21 | 01-JAN-14:00 | 34757.21 | 0.00 |
February | 0.00 | 0.00 | 0.641656E+10 | 0.641656E+10 | 124499.57 | 14-FEB-16:03 | 124499.57 | 0.00 |
March | 0.00 | 0.00 | 0.235609E+11 | 0.235609E+11 | 130725.87 | 08-MAR-16:03 | 130725.87 | 0.00 |
April | 0.00 | 0.00 | 0.967900E+11 | 0.967900E+11 | 198126.48 | 13-APR-18:03 | 198126.48 | 0.00 |
May | 0.00 | 0.00 | 0.181877E+12 | 0.181877E+12 | 230005.54 | 19-MAY-18:20 | 230005.54 | 0.14 |
June | 0.00 | 0.00 | 0.320255E+12 | 0.320027E+12 | 264568.24 | 27-JUN-20:10 | 264568.24 | 0.42 |
July | 0.00 | 0.00 | 0.440332E+12 | 0.417714E+12 | 344122.06 | 31-JUL-20:00 | 187390.72 | 0.94 |
August | 0.00 | 0.00 | 0.394622E+12 | 0.382925E+12 | 288426.07 | 14-AUG-21:00 | 240167.64 | 0.97 |
September | 0.00 | 0.00 | 0.255256E+12 | 0.254317E+12 | 232942.71 | 13-SEP-19:10 | 232942.71 | 0.67 |
October | 0.00 | 0.00 | 0.109028E+12 | 0.108946E+12 | 203862.44 | 05-OCT-18:03 | 203862.44 | 0.15 |
November | 0.00 | 0.00 | 0.330358E+10 | 0.330358E+10 | 60997.22 | 09-NOV-14:00 | 60997.22 | 0.00 |
December | 0.00 | 0.00 | 0.100805E+09 | 0.100805E+09 | 7684.51 | 03-DEC-19:05 | 7684.51 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.183262E+13 | 0.179706E+13 | 0.28 | |||
Minimum of Months | 0.00 | 0.00 | 0.100805E+09 | 0.100805E+09 | 7684.51 | 7684.51 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.440332E+12 | 0.417714E+12 | 344122.06 | 264568.24 | 0.97 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.133589E+10 | 0.129248E+10 | 11144.57 | 08-JAN-16:02 | 11144.57 | 0.03 |
February | 0.00 | 0.00 | 0.189704E+10 | 0.179456E+10 | 11144.34 | 18-FEB-16:02 | 11144.34 | 0.09 |
March | 0.00 | 0.00 | 0.300979E+10 | 0.291922E+10 | 11144.78 | 08-MAR-16:02 | 11144.78 | 0.07 |
April | 0.00 | 0.00 | 0.555116E+10 | 0.546411E+10 | 11144.39 | 19-APR-18:02 | 11144.39 | 0.06 |
May | 0.00 | 0.00 | 0.678831E+10 | 0.598971E+10 | 12167.12 | 24-MAY-15:01 | 10400.70 | 0.41 |
June | 0.00 | 0.00 | 0.945167E+10 | 0.780178E+10 | 12140.93 | 08-JUN-15:02 | 10416.73 | 0.80 |
July | 0.00 | 0.00 | 0.114228E+11 | 0.856355E+10 | 12835.48 | 01-JUL-08:62 | 9960.52 | 0.97 |
August | 0.00 | 0.00 | 0.113808E+11 | 0.853650E+10 | 12945.75 | 26-AUG-08:62 | 9887.51 | 0.96 |
September | 0.00 | 0.00 | 0.923563E+10 | 0.709368E+10 | 12489.96 | 06-SEP-08:62 | 9488.43 | 0.90 |
October | 0.00 | 0.00 | 0.639631E+10 | 0.555278E+10 | 11571.89 | 02-OCT-18:02 | 10787.08 | 0.42 |
November | 0.00 | 0.00 | 0.253985E+10 | 0.236183E+10 | 11143.61 | 13-NOV-16:02 | 11143.61 | 0.13 |
December | 0.00 | 0.00 | 0.115078E+10 | 0.111476E+10 | 11144.00 | 29-DEC-16:02 | 11144.00 | 0.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.701600E+11 | 0.584849E+11 | 0.41 | |||
Minimum of Months | 0.00 | 0.00 | 0.115078E+10 | 0.111476E+10 | 11143.61 | 9488.43 | 0.03 | |
Maximum of Months | 0.00 | 0.00 | 0.114228E+11 | 0.856355E+10 | 12945.75 | 11144.78 | 0.97 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.250448E+09 | 0.246929E+09 | 11026.97 | 08-JAN-16:02 | 11026.97 | 0.00 |
February | 0.00 | 0.00 | 0.564622E+09 | 0.549573E+09 | 11159.98 | 14-FEB-19:01 | 11159.98 | 0.01 |
March | 0.00 | 0.00 | 0.114144E+10 | 0.110594E+10 | 12515.80 | 30-MAR-18:11 | 12515.80 | 0.04 |
April | 0.00 | 0.00 | 0.339086E+10 | 0.331531E+10 | 12783.95 | 25-APR-16:21 | 12783.95 | 0.05 |
May | 0.00 | 0.00 | 0.543613E+10 | 0.478759E+10 | 11983.55 | 24-MAY-15:01 | 10327.58 | 0.33 |
June | 0.00 | 0.00 | 0.868419E+10 | 0.725433E+10 | 12407.90 | 24-JUN-08:51 | 11891.59 | 0.70 |
July | 0.00 | 0.00 | 0.102031E+11 | 0.779564E+10 | 14077.01 | 31-JUL-21:51 | 10868.25 | 0.80 |
August | 0.00 | 0.00 | 0.942155E+10 | 0.713951E+10 | 13837.38 | 26-AUG-08:51 | 9955.36 | 0.77 |
September | 0.00 | 0.00 | 0.628925E+10 | 0.469488E+10 | 13133.92 | 05-SEP-21:51 | 10064.20 | 0.67 |
October | 0.00 | 0.00 | 0.298338E+10 | 0.237878E+10 | 12665.23 | 02-OCT-21:51 | 10766.10 | 0.30 |
November | 0.00 | 0.00 | 0.681235E+09 | 0.618492E+09 | 11027.25 | 05-NOV-15:02 | 11027.25 | 0.06 |
December | 0.00 | 0.00 | 0.158745E+09 | 0.155835E+09 | 11026.35 | 29-DEC-16:02 | 11026.35 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.492050E+11 | 0.400428E+11 | 0.31 | |||
Minimum of Months | 0.00 | 0.00 | 0.158745E+09 | 0.155835E+09 | 11026.35 | 9955.36 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.102031E+11 | 0.779564E+10 | 14077.01 | 12783.95 | 0.80 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.303091E+11 | 0.303091E+11 | 58596.22 | 03-JAN-12:40 | 58596.22 | 0.00 |
February | 0.00 | 0.00 | 0.290957E+11 | 0.290957E+11 | 59767.53 | 14-FEB-13:00 | 59767.53 | 0.00 |
March | 0.00 | 0.00 | 0.282799E+11 | 0.282799E+11 | 50637.56 | 08-MAR-13:30 | 50637.56 | 0.00 |
April | 0.00 | 0.00 | 0.298575E+11 | 0.298575E+11 | 36545.84 | 13-APR-13:15 | 36545.84 | 0.00 |
May | 0.00 | 0.00 | 0.282843E+11 | 0.239116E+11 | 26135.80 | 13-MAY-13:05 | 26135.80 | 0.30 |
June | 0.00 | 0.00 | 0.365435E+11 | 0.246875E+11 | 29391.49 | 29-JUN-16:10 | 25815.82 | 0.79 |
July | 0.00 | 0.00 | 0.490089E+11 | 0.301002E+11 | 32432.15 | 23-JUL-13:20 | 27964.34 | 1.00 |
August | 0.00 | 0.00 | 0.548672E+11 | 0.371928E+11 | 42598.69 | 22-AUG-13:30 | 34745.71 | 1.00 |
September | 0.00 | 0.00 | 0.568582E+11 | 0.416083E+11 | 56505.00 | 28-SEP-13:30 | 54388.99 | 0.99 |
October | 0.00 | 0.00 | 0.545160E+11 | 0.495728E+11 | 58943.22 | 19-OCT-12:25 | 58943.22 | 0.36 |
November | 0.00 | 0.00 | 0.414911E+11 | 0.414911E+11 | 58873.35 | 20-NOV-12:10 | 58873.35 | 0.00 |
December | 0.00 | 0.00 | 0.336108E+11 | 0.336108E+11 | 59748.46 | 31-DEC-13:40 | 59748.46 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.472722E+12 | 0.399717E+12 | 0.37 | |||
Minimum of Months | 0.00 | 0.00 | 0.282799E+11 | 0.239116E+11 | 26135.80 | 25815.82 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.568582E+11 | 0.495728E+11 | 59767.53 | 59767.53 | 1.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.121803E+10 | 0.120754E+10 | 57461.06 | 16-JAN-09:02 | 57461.06 | 0.00 |
February | 0.00 | 0.00 | 0.335542E+10 | 0.323247E+10 | 59672.00 | 15-FEB-19:01 | 59672.00 | 0.02 |
March | 0.00 | 0.00 | 0.112215E+11 | 0.107363E+11 | 61606.54 | 27-MAR-19:12 | 61606.54 | 0.06 |
April | 0.00 | 0.00 | 0.234142E+11 | 0.231877E+11 | 64481.59 | 30-APR-21:51 | 64481.59 | 0.03 |
May | 0.00 | 0.00 | 0.366945E+11 | 0.336188E+11 | 64713.18 | 11-MAY-21:51 | 64713.18 | 0.27 |
June | 0.00 | 0.00 | 0.543537E+11 | 0.477900E+11 | 68929.22 | 05-JUN-21:51 | 63325.41 | 0.59 |
July | 0.00 | 0.00 | 0.638372E+11 | 0.504711E+11 | 76598.44 | 31-JUL-21:51 | 59686.43 | 0.76 |
August | 0.00 | 0.00 | 0.566379E+11 | 0.436740E+11 | 75818.14 | 25-AUG-21:51 | 56439.99 | 0.71 |
September | 0.00 | 0.00 | 0.378451E+11 | 0.299701E+11 | 73571.07 | 05-SEP-21:51 | 58426.00 | 0.55 |
October | 0.00 | 0.00 | 0.198150E+11 | 0.168531E+11 | 69533.45 | 02-OCT-21:51 | 61504.63 | 0.25 |
November | 0.00 | 0.00 | 0.604763E+10 | 0.540168E+10 | 60356.96 | 09-NOV-19:02 | 60356.96 | 0.08 |
December | 0.00 | 0.00 | 0.881727E+09 | 0.865441E+09 | 58350.19 | 02-DEC-09:02 | 58350.19 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.315322E+12 | 0.267008E+12 | 0.28 | |||
Minimum of Months | 0.00 | 0.00 | 0.881727E+09 | 0.865441E+09 | 57461.06 | 56439.99 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.638372E+11 | 0.504711E+11 | 76598.44 | 64713.18 | 0.76 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.133060E+10 | 0.126738E+10 | 9895.28 | 05-JAN-16:01 | 9895.28 | 0.05 |
February | 0.00 | 0.00 | 0.170617E+10 | 0.158515E+10 | 9894.90 | 25-FEB-16:02 | 9894.90 | 0.11 |
March | 0.00 | 0.00 | 0.329773E+10 | 0.314550E+10 | 9895.25 | 02-MAR-09:02 | 9895.25 | 0.12 |
April | 0.00 | 0.00 | 0.630548E+10 | 0.619367E+10 | 9895.35 | 23-APR-08:62 | 9895.35 | 0.09 |
May | 0.00 | 0.00 | 0.759950E+10 | 0.678503E+10 | 10509.53 | 24-MAY-15:01 | 9425.02 | 0.44 |
June | 0.00 | 0.00 | 0.104034E+11 | 0.893065E+10 | 10653.64 | 08-JUN-15:02 | 9330.41 | 0.82 |
July | 0.00 | 0.00 | 0.126049E+11 | 0.100461E+11 | 11182.58 | 01-JUL-08:62 | 8984.94 | 0.99 |
August | 0.00 | 0.00 | 0.122497E+11 | 0.966153E+10 | 10579.33 | 29-AUG-18:02 | 9379.61 | 0.99 |
September | 0.00 | 0.00 | 0.954147E+10 | 0.760891E+10 | 10888.99 | 06-SEP-08:62 | 9177.94 | 0.93 |
October | 0.00 | 0.00 | 0.644841E+10 | 0.566927E+10 | 10249.89 | 02-OCT-18:02 | 9592.18 | 0.45 |
November | 0.00 | 0.00 | 0.259178E+10 | 0.241054E+10 | 9895.11 | 17-NOV-09:02 | 9895.11 | 0.15 |
December | 0.00 | 0.00 | 0.111369E+10 | 0.106769E+10 | 9895.31 | 11-DEC-09:02 | 9895.31 | 0.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.751928E+11 | 0.643714E+11 | 0.43 | |||
Minimum of Months | 0.00 | 0.00 | 0.111369E+10 | 0.106769E+10 | 9894.90 | 8984.94 | 0.04 | |
Maximum of Months | 0.00 | 0.00 | 0.126049E+11 | 0.100461E+11 | 11182.58 | 9895.35 | 0.99 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.227269E+09 | 0.198096E+09 | 9548.15 | 27-JAN-09:02 | 9548.15 | 0.02 |
February | 0.00 | 0.00 | 0.428457E+09 | 0.369191E+09 | 9812.47 | 14-FEB-09:02 | 9812.47 | 0.05 |
March | 0.00 | 0.00 | 0.150248E+10 | 0.140718E+10 | 9812.67 | 02-MAR-09:02 | 9812.67 | 0.09 |
April | 0.00 | 0.00 | 0.439783E+10 | 0.429797E+10 | 11376.71 | 27-APR-08:51 | 11376.71 | 0.08 |
May | 0.00 | 0.00 | 0.622503E+10 | 0.553635E+10 | 12417.72 | 14-MAY-08:32 | 12417.72 | 0.37 |
June | 0.00 | 0.00 | 0.927336E+10 | 0.797632E+10 | 13360.65 | 14-JUN-07:52 | 13360.65 | 0.72 |
July | 0.00 | 0.00 | 0.109697E+11 | 0.882293E+10 | 14348.69 | 04-JUL-08:62 | 13072.31 | 0.82 |
August | 0.00 | 0.00 | 0.989016E+10 | 0.777676E+10 | 13900.97 | 14-AUG-08:32 | 11544.19 | 0.79 |
September | 0.00 | 0.00 | 0.638879E+10 | 0.477354E+10 | 12001.06 | 06-SEP-08:51 | 10153.76 | 0.70 |
October | 0.00 | 0.00 | 0.323647E+10 | 0.258263E+10 | 11309.73 | 02-OCT-21:51 | 9628.27 | 0.35 |
November | 0.00 | 0.00 | 0.708412E+09 | 0.617435E+09 | 9812.22 | 19-NOV-09:02 | 9812.22 | 0.08 |
December | 0.00 | 0.00 | 0.154583E+09 | 0.133268E+09 | 9784.21 | 31-DEC-09:02 | 9784.21 | 0.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.534025E+11 | 0.444917E+11 | 0.34 | |||
Minimum of Months | 0.00 | 0.00 | 0.154583E+09 | 0.133268E+09 | 9548.15 | 9548.15 | 0.02 | |
Maximum of Months | 0.00 | 0.00 | 0.109697E+11 | 0.882293E+10 | 14348.69 | 13360.65 | 0.82 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.305327E+09 | 0.297436E+09 | 2952.65 | 21-JAN-16:02 | 2952.65 | 0.03 |
February | 0.00 | 0.00 | 0.457513E+09 | 0.435634E+09 | 2952.61 | 25-FEB-16:02 | 2952.61 | 0.07 |
March | 0.00 | 0.00 | 0.709663E+09 | 0.690341E+09 | 2952.37 | 29-MAR-18:02 | 2952.37 | 0.06 |
April | 0.00 | 0.00 | 0.134792E+10 | 0.133040E+10 | 2952.63 | 20-APR-15:02 | 2952.63 | 0.05 |
May | 0.00 | 0.00 | 0.167470E+10 | 0.148902E+10 | 3307.15 | 29-MAY-08:62 | 2564.31 | 0.38 |
June | 0.00 | 0.00 | 0.243035E+10 | 0.201550E+10 | 3238.79 | 08-JUN-15:02 | 2714.91 | 0.79 |
July | 0.00 | 0.00 | 0.294585E+10 | 0.219985E+10 | 3568.77 | 01-JUL-08:62 | 2526.50 | 0.97 |
August | 0.00 | 0.00 | 0.290273E+10 | 0.217290E+10 | 3581.34 | 26-AUG-08:62 | 2518.19 | 0.96 |
September | 0.00 | 0.00 | 0.224494E+10 | 0.171422E+10 | 3440.85 | 06-SEP-08:62 | 2287.85 | 0.89 |
October | 0.00 | 0.00 | 0.147966E+10 | 0.127697E+10 | 3155.96 | 03-OCT-08:62 | 2716.10 | 0.39 |
November | 0.00 | 0.00 | 0.542985E+09 | 0.508070E+09 | 2952.37 | 13-NOV-16:02 | 2952.37 | 0.10 |
December | 0.00 | 0.00 | 0.257232E+09 | 0.251595E+09 | 2952.54 | 28-DEC-16:02 | 2952.54 | 0.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.172989E+11 | 0.143819E+11 | 0.39 | |||
Minimum of Months | 0.00 | 0.00 | 0.257232E+09 | 0.251595E+09 | 2952.37 | 2287.85 | 0.02 | |
Maximum of Months | 0.00 | 0.00 | 0.294585E+10 | 0.219985E+10 | 3581.34 | 2952.65 | 0.97 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 54986960.21 | 54413703.27 | 2916.25 | 05-JAN-16:01 | 2916.25 | 0.00 |
February | 0.00 | 0.00 | 0.128909E+09 | 0.125270E+09 | 2977.44 | 14-FEB-19:01 | 2977.44 | 0.01 |
March | 0.00 | 0.00 | 0.249812E+09 | 0.244739E+09 | 3378.55 | 30-MAR-18:11 | 3378.55 | 0.02 |
April | 0.00 | 0.00 | 0.813084E+09 | 0.798652E+09 | 3381.02 | 25-APR-16:21 | 3381.02 | 0.04 |
May | 0.00 | 0.00 | 0.136588E+10 | 0.121145E+10 | 3264.99 | 06-MAY-19:41 | 3264.99 | 0.31 |
June | 0.00 | 0.00 | 0.227712E+10 | 0.191427E+10 | 3281.37 | 05-JUN-21:51 | 2789.72 | 0.69 |
July | 0.00 | 0.00 | 0.268979E+10 | 0.205840E+10 | 3775.86 | 31-JUL-21:51 | 2906.61 | 0.80 |
August | 0.00 | 0.00 | 0.245918E+10 | 0.186369E+10 | 3699.14 | 26-AUG-08:51 | 2554.31 | 0.77 |
September | 0.00 | 0.00 | 0.154315E+10 | 0.114106E+10 | 3504.71 | 05-SEP-21:51 | 2561.42 | 0.67 |
October | 0.00 | 0.00 | 0.642022E+09 | 0.503205E+09 | 3375.66 | 02-OCT-21:51 | 2793.25 | 0.27 |
November | 0.00 | 0.00 | 0.127483E+09 | 0.119055E+09 | 2916.07 | 13-NOV-16:02 | 2916.07 | 0.03 |
December | 0.00 | 0.00 | 31756943.10 | 30777317.81 | 2916.17 | 29-DEC-16:02 | 2916.17 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.123832E+11 | 0.100650E+11 | 0.30 | |||
Minimum of Months | 0.00 | 0.00 | 31756943.10 | 30777317.81 | 2916.07 | 2554.31 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.268979E+10 | 0.205840E+10 | 3775.86 | 3381.02 | 0.80 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.674786E+10 | 0.657123E+10 | 13132.48 | 03-JAN-13:53 | 13132.48 | 0.17 |
February | 0.00 | 0.00 | 0.657582E+10 | 0.631671E+10 | 13016.92 | 13-FEB-13:25 | 13016.92 | 0.24 |
March | 0.00 | 0.00 | 0.637075E+10 | 0.617643E+10 | 12432.59 | 18-MAR-18:01 | 12432.59 | 0.14 |
April | 0.00 | 0.00 | 0.710485E+10 | 0.695939E+10 | 12431.92 | 27-APR-15:02 | 12431.92 | 0.09 |
May | 0.00 | 0.00 | 0.725541E+10 | 0.629857E+10 | 13716.27 | 24-MAY-15:01 | 11429.73 | 0.41 |
June | 0.00 | 0.00 | 0.982239E+10 | 0.778794E+10 | 13729.90 | 08-JUN-15:02 | 11486.85 | 0.81 |
July | 0.00 | 0.00 | 0.135784E+11 | 0.100091E+11 | 14727.53 | 01-JUL-08:62 | 10832.85 | 0.96 |
August | 0.00 | 0.00 | 0.145065E+11 | 0.110653E+11 | 14629.32 | 26-AUG-08:62 | 10899.19 | 0.96 |
September | 0.00 | 0.00 | 0.136512E+11 | 0.113463E+11 | 13604.76 | 06-SEP-08:62 | 10278.76 | 0.91 |
October | 0.00 | 0.00 | 0.122586E+11 | 0.113792E+11 | 13099.83 | 15-OCT-12:55 | 13099.83 | 0.47 |
November | 0.00 | 0.00 | 0.885652E+10 | 0.856452E+10 | 13114.42 | 07-NOV-13:23 | 13114.42 | 0.24 |
December | 0.00 | 0.00 | 0.739861E+10 | 0.726299E+10 | 13076.55 | 30-DEC-13:35 | 13076.55 | 0.12 |
Annual Sum or Average | 0.00 | 0.00 | 0.114127E+12 | 0.997376E+11 | 0.46 | |||
Minimum of Months | 0.00 | 0.00 | 0.637075E+10 | 0.617643E+10 | 12431.92 | 10278.76 | 0.09 | |
Maximum of Months | 0.00 | 0.00 | 0.145065E+11 | 0.113792E+11 | 14727.53 | 13132.48 | 0.96 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 30843.97 | 163839.24 | 05-JAN-09:03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 29267.23 | 155697.25 | 06-FEB-16:03 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 31473.78 | 148850.93 | 06-MAR-09:04 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23947.45 | 134367.71 | 23-APR-05:10 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 11771.69 | 122301.40 | 07-MAY-05:00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 2015.59 | 88597.58 | 09-JUN-05:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1.81 | 7014.05 | 26-JUL-08:58 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.61 | 16108.93 | 31-AUG-06:00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 1433.57 | 53283.88 | 20-SEP-06:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 20624.11 | 138199.20 | 13-OCT-08:05 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 31653.76 | 149124.30 | 25-NOV-19:03 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 34040.63 | 167856.56 | 09-DEC-16:03 |
Annual Sum or Average | 0.00 | 18035.63 | ||||
Minimum of Months | 0.00 | 0.00 | 1.81 | 7014.05 | ||
Maximum of Months | 0.00 | 0.00 | 34040.63 | 167856.56 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 17684.49 | 120091.25 | 05-JAN-16:01 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 22928.55 | 314937.80 | 14-FEB-16:01 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 32216.48 | 294142.12 | 08-MAR-16:02 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 73484.80 | 355601.71 | 13-APR-18:03 | 0.00 | 0.00 | 01-APR-00:10 |
May | 112128.97 | 372492.79 | 15-MAY-18:03 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 188448.24 | 455320.01 | 28-JUN-18:10 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 244034.91 | 430401.50 | 21-JUL-18:17 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 224356.94 | 459407.53 | 04-AUG-18:02 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 162130.88 | 390836.35 | 02-SEP-18:03 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 85458.69 | 396433.59 | 04-OCT-15:05 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 27849.22 | 178271.27 | 02-NOV-15:03 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 18400.05 | 107514.96 | 31-DEC-16:03 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 101266.00 | 0.00 | ||||
Minimum of Months | 17684.49 | 107514.96 | 0.00 | 0.00 | ||
Maximum of Months | 244034.91 | 459407.53 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 26472.64 | 55812.69 | 31-JAN-08:00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26677.67 | 55855.92 | 06-FEB-07:50 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 26050.08 | 55332.81 | 01-MAR-08:00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 24675.70 | 52886.41 | 03-APR-07:00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 22968.82 | 49773.22 | 01-MAY-07:00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 21377.17 | 46110.29 | 01-JUN-06:42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20302.37 | 43131.20 | 03-JUL-06:20 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 20097.06 | 42367.45 | 31-AUG-06:52 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 20756.19 | 44452.40 | 29-SEP-06:45 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22125.60 | 47965.42 | 31-OCT-07:00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 23838.55 | 51512.53 | 30-NOV-07:20 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 25424.49 | 54288.09 | 29-DEC-07:50 |
Annual Sum or Average | 0.00 | 23378.29 | ||||
Minimum of Months | 0.00 | 0.00 | 20097.06 | 42367.45 | ||
Maximum of Months | 0.00 | 0.00 | 26677.67 | 55855.92 |
Report: FanReportMonthly
For: FLR_3_DOAS FAN
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.271000E+10 | 0.84 | 1299.30 | 13-JAN-19:04 | 1.07 |
February | 0.244774E+10 | 0.84 | 1299.30 | 02-FEB-10:50 | 1.06 |
March | 0.271000E+10 | 0.84 | 1299.30 | 09-MAR-16:08 | 1.07 |
April | 0.262258E+10 | 0.85 | 1299.30 | 03-APR-18:48 | 1.07 |
May | 0.271000E+10 | 0.84 | 1299.30 | 01-MAY-02:20 | 1.06 |
June | 0.262258E+10 | 0.84 | 1299.30 | 01-JUN-21:50 | 1.06 |
July | 0.271000E+10 | 0.84 | 1299.30 | 01-JUL-09:20 | 1.05 |
August | 0.271000E+10 | 0.84 | 1299.30 | 01-AUG-19:00 | 1.06 |
September | 0.262258E+10 | 0.84 | 1299.30 | 02-SEP-05:15 | 1.06 |
October | 0.271000E+10 | 0.84 | 1299.30 | 02-OCT-03:30 | 1.06 |
November | 0.262258E+10 | 0.84 | 1299.30 | 01-NOV-16:30 | 1.06 |
December | 0.271000E+10 | 0.84 | 1299.30 | 01-DEC-19:03 | 1.07 |
Annual Sum or Average | 0.319080E+11 | 0.84 | |||
Minimum of Months | 0.244774E+10 | 0.84 | 1299.30 | 1.05 | |
Maximum of Months | 0.271000E+10 | 0.85 | 1299.30 | 1.07 |
Report: FanReportMonthly
For: VAV WITH REHEAT FAN
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.341957E+11 | 0.89 | 26145.92 | 09-JAN-22:10 | 1.35 |
February | 0.310091E+11 | 0.89 | 28813.97 | 14-FEB-22:10 | 1.43 |
March | 0.354890E+11 | 0.91 | 28205.96 | 08-MAR-22:10 | 1.41 |
April | 0.364315E+11 | 0.94 | 32863.41 | 13-APR-21:10 | 1.55 |
May | 0.390943E+11 | 0.95 | 33294.42 | 31-MAY-21:10 | 1.56 |
June | 0.416934E+11 | 1.00 | 38565.46 | 23-JUN-21:10 | 1.69 |
July | 0.454641E+11 | 1.02 | 40434.68 | 21-JUL-21:10 | 1.75 |
August | 0.464715E+11 | 1.04 | 41575.19 | 18-AUG-21:10 | 1.77 |
September | 0.434107E+11 | 1.02 | 41804.11 | 21-SEP-21:10 | 1.79 |
October | 0.416015E+11 | 0.99 | 41274.72 | 06-OCT-21:10 | 1.77 |
November | 0.365678E+11 | 0.94 | 31754.02 | 02-NOV-21:10 | 1.51 |
December | 0.349803E+11 | 0.90 | 27125.24 | 01-DEC-22:10 | 1.38 |
Annual Sum or Average | 0.466409E+12 | 0.96 | |||
Minimum of Months | 0.310091E+11 | 0.89 | 26145.92 | 1.35 | |
Maximum of Months | 0.464715E+11 | 1.04 | 41804.11 | 1.79 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205205E+09 | 0.32 | 76.61 | 01-JAN-00:10 | 0.32 |
February | 0.185347E+09 | 0.32 | 76.61 | 01-FEB-00:10 | 0.32 |
March | 0.205205E+09 | 0.32 | 76.61 | 01-MAR-00:10 | 0.32 |
April | 0.198586E+09 | 0.32 | 76.61 | 01-APR-00:10 | 0.32 |
May | 0.205205E+09 | 0.32 | 76.61 | 01-MAY-00:05 | 0.33 |
June | 0.198586E+09 | 0.32 | 76.61 | 01-JUN-00:05 | 0.32 |
July | 0.205205E+09 | 0.32 | 76.61 | 01-JUL-00:10 | 0.32 |
August | 0.205205E+09 | 0.32 | 76.61 | 01-AUG-00:05 | 0.32 |
September | 0.198586E+09 | 0.32 | 76.61 | 01-SEP-00:05 | 0.32 |
October | 0.205205E+09 | 0.32 | 76.61 | 01-OCT-00:10 | 0.32 |
November | 0.198586E+09 | 0.32 | 76.61 | 01-NOV-00:05 | 0.32 |
December | 0.205205E+09 | 0.32 | 76.61 | 01-DEC-00:10 | 0.32 |
Annual Sum or Average | 0.241613E+10 | 0.32 | |||
Minimum of Months | 0.185347E+09 | 0.32 | 76.61 | 0.32 | |
Maximum of Months | 0.205205E+09 | 0.32 | 76.61 | 0.33 |
Report: FanReportMonthly
For: LOBBY_FLR_1 EXHAUST FAN
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:10 | -0.0 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | -0.0 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | -0.0 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:05 | -0.0 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 EXHAUST FAN
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 EXHAUST FAN
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116283E+10 | 0.23 | 612.92 | 01-JAN-07:10 | 0.32 |
February | 0.105030E+10 | 0.23 | 612.92 | 01-FEB-07:05 | 0.32 |
March | 0.116283E+10 | 0.23 | 612.92 | 01-MAR-07:05 | 0.32 |
April | 0.112532E+10 | 0.23 | 612.92 | 01-APR-06:05 | 0.32 |
May | 0.116283E+10 | 0.23 | 612.92 | 01-MAY-06:05 | 0.32 |
June | 0.112532E+10 | 0.23 | 612.92 | 01-JUN-06:05 | 0.32 |
July | 0.116283E+10 | 0.23 | 612.92 | 01-JUL-06:10 | 0.32 |
August | 0.116283E+10 | 0.23 | 612.92 | 01-AUG-06:05 | 0.32 |
September | 0.112532E+10 | 0.23 | 612.92 | 01-SEP-06:10 | 0.32 |
October | 0.116283E+10 | 0.23 | 612.92 | 01-OCT-06:10 | 0.32 |
November | 0.112532E+10 | 0.23 | 612.92 | 01-NOV-06:05 | 0.32 |
December | 0.116283E+10 | 0.23 | 612.92 | 01-DEC-07:05 | 0.32 |
Annual Sum or Average | 0.136914E+11 | 0.23 | |||
Minimum of Months | 0.105030E+10 | 0.23 | 612.92 | 0.32 | |
Maximum of Months | 0.116283E+10 | 0.23 | 612.92 | 0.32 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.322091E+09 | 0.56 | 976.81 | 01-JAN-09:02 | 0.70 |
February | 0.312112E+09 | 0.57 | 976.81 | 01-FEB-09:02 | 0.70 |
March | 0.348213E+09 | 0.59 | 976.81 | 01-MAR-16:02 | 0.70 |
April | 0.512092E+09 | 0.63 | 976.81 | 01-APR-08:62 | 0.70 |
May | 0.611396E+09 | 0.63 | 976.81 | 01-MAY-08:62 | 0.69 |
June | 0.840250E+09 | 0.66 | 976.81 | 01-JUN-08:62 | 0.70 |
July | 0.907151E+09 | 0.67 | 976.81 | 01-JUL-08:62 | 0.69 |
August | 0.906210E+09 | 0.67 | 976.81 | 01-AUG-08:62 | 0.69 |
September | 0.767529E+09 | 0.66 | 976.81 | 01-SEP-08:62 | 0.69 |
October | 0.592508E+09 | 0.63 | 976.81 | 01-OCT-08:62 | 0.69 |
November | 0.313405E+09 | 0.59 | 976.81 | 01-NOV-08:62 | 0.69 |
December | 0.309932E+09 | 0.56 | 976.81 | 01-DEC-16:02 | 0.70 |
Annual Sum or Average | 0.674289E+10 | 0.62 | |||
Minimum of Months | 0.309932E+09 | 0.56 | 976.81 | 0.69 | |
Maximum of Months | 0.907151E+09 | 0.67 | 976.81 | 0.70 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.330609E+09 | 0.51 | 966.44 | 01-JAN-09:02 | 0.70 |
February | 0.263942E+09 | 0.51 | 966.44 | 01-FEB-09:02 | 0.70 |
March | 0.210356E+09 | 0.49 | 966.44 | 04-MAR-09:02 | 0.70 |
April | 0.327630E+09 | 0.49 | 966.44 | 01-APR-15:02 | 0.70 |
May | 0.491757E+09 | 0.51 | 966.44 | 01-MAY-08:62 | 0.70 |
June | 0.783339E+09 | 0.56 | 966.44 | 01-JUN-08:51 | 0.69 |
July | 0.830953E+09 | 0.55 | 966.44 | 01-JUL-08:51 | 0.69 |
August | 0.759877E+09 | 0.53 | 966.44 | 01-AUG-08:31 | 0.69 |
September | 0.528156E+09 | 0.50 | 966.44 | 01-SEP-08:51 | 0.69 |
October | 0.311051E+09 | 0.47 | 966.44 | 01-OCT-08:62 | 0.69 |
November | 0.220605E+09 | 0.52 | 966.44 | 01-NOV-15:02 | 0.70 |
December | 0.346502E+09 | 0.50 | 966.44 | 01-DEC-16:02 | 0.70 |
Annual Sum or Average | 0.540478E+10 | 0.51 | |||
Minimum of Months | 0.210356E+09 | 0.47 | 966.44 | 0.69 | |
Maximum of Months | 0.830953E+09 | 0.56 | 966.44 | 0.70 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.181310E+10 | 0.38 | 3379.08 | 03-JAN-12:40 | 0.70 |
February | 0.171687E+10 | 0.44 | 3428.72 | 14-FEB-13:00 | 0.70 |
March | 0.169721E+10 | 0.47 | 3041.27 | 08-MAR-13:30 | 0.70 |
April | 0.179313E+10 | 0.59 | 1719.60 | 13-APR-13:15 | 0.70 |
May | 0.179173E+10 | 0.62 | 1409.13 | 31-MAY-17:13 | 0.70 |
June | 0.222378E+10 | 0.67 | 1622.24 | 28-JUN-17:15 | 0.70 |
July | 0.262395E+10 | 0.69 | 1595.28 | 21-JUL-17:13 | 0.70 |
August | 0.291252E+10 | 0.69 | 2867.79 | 22-AUG-13:30 | 0.69 |
September | 0.336400E+10 | 0.69 | 5131.41 | 28-SEP-13:15 | 0.70 |
October | 0.334816E+10 | 0.62 | 5327.19 | 21-OCT-11:40 | 0.70 |
November | 0.246925E+10 | 0.51 | 3392.15 | 20-NOV-12:10 | 0.70 |
December | 0.199802E+10 | 0.39 | 3428.20 | 31-DEC-13:40 | 0.70 |
Annual Sum or Average | 0.277517E+11 | 0.56 | |||
Minimum of Months | 0.169721E+10 | 0.38 | 1409.13 | 0.69 | |
Maximum of Months | 0.336400E+10 | 0.69 | 5327.19 | 0.70 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.119978E+10 | 0.49 | 5340.56 | 01-JAN-09:02 | 0.70 |
February | 0.102671E+10 | 0.49 | 5340.56 | 02-FEB-16:01 | 0.70 |
March | 0.119191E+10 | 0.45 | 5340.56 | 01-MAR-09:02 | 0.70 |
April | 0.200511E+10 | 0.42 | 5340.56 | 01-APR-08:62 | 0.70 |
May | 0.320347E+10 | 0.45 | 5340.56 | 01-MAY-08:62 | 0.70 |
June | 0.495001E+10 | 0.52 | 5340.56 | 01-JUN-08:51 | 0.70 |
July | 0.532348E+10 | 0.53 | 5340.56 | 01-JUL-08:51 | 0.69 |
August | 0.466119E+10 | 0.49 | 5340.56 | 01-AUG-08:31 | 0.69 |
September | 0.307875E+10 | 0.43 | 5340.56 | 01-SEP-08:51 | 0.69 |
October | 0.180185E+10 | 0.41 | 5340.56 | 01-OCT-08:62 | 0.70 |
November | 0.994249E+09 | 0.49 | 5340.56 | 01-NOV-08:62 | 0.70 |
December | 0.134660E+10 | 0.50 | 5340.56 | 01-DEC-19:02 | 0.70 |
Annual Sum or Average | 0.307831E+11 | 0.47 | |||
Minimum of Months | 0.994249E+09 | 0.41 | 5340.56 | 0.69 | |
Maximum of Months | 0.532348E+10 | 0.53 | 5340.56 | 0.70 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.321681E+09 | 0.57 | 866.33 | 01-JAN-09:02 | 0.70 |
February | 0.300995E+09 | 0.58 | 866.33 | 01-FEB-16:02 | 0.70 |
March | 0.372155E+09 | 0.61 | 866.33 | 01-MAR-09:02 | 0.70 |
April | 0.568886E+09 | 0.67 | 866.33 | 01-APR-08:62 | 0.70 |
May | 0.676766E+09 | 0.67 | 866.33 | 01-MAY-08:62 | 0.70 |
June | 0.924508E+09 | 0.68 | 866.33 | 01-JUN-08:62 | 0.70 |
July | 0.101525E+10 | 0.68 | 866.33 | 01-JUL-08:62 | 0.69 |
August | 0.990067E+09 | 0.68 | 866.33 | 01-AUG-08:62 | 0.69 |
September | 0.803374E+09 | 0.68 | 866.33 | 01-SEP-08:62 | 0.69 |
October | 0.599093E+09 | 0.65 | 866.33 | 01-OCT-08:62 | 0.69 |
November | 0.331221E+09 | 0.61 | 866.33 | 01-NOV-08:62 | 0.69 |
December | 0.298487E+09 | 0.55 | 866.33 | 01-DEC-09:02 | 0.70 |
Annual Sum or Average | 0.720248E+10 | 0.64 | |||
Minimum of Months | 0.298487E+09 | 0.55 | 866.33 | 0.69 | |
Maximum of Months | 0.101525E+10 | 0.68 | 866.33 | 0.70 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.305564E+09 | 0.50 | 859.04 | 01-JAN-09:02 | 0.70 |
February | 0.239722E+09 | 0.49 | 859.04 | 01-FEB-16:02 | 0.70 |
March | 0.237782E+09 | 0.51 | 859.04 | 01-MAR-09:02 | 0.70 |
April | 0.421056E+09 | 0.56 | 859.04 | 01-APR-08:62 | 0.70 |
May | 0.557505E+09 | 0.56 | 859.04 | 01-MAY-08:62 | 0.70 |
June | 0.815318E+09 | 0.58 | 859.04 | 01-JUN-08:51 | 0.69 |
July | 0.875832E+09 | 0.57 | 859.04 | 01-JUL-08:51 | 0.69 |
August | 0.778504E+09 | 0.55 | 859.04 | 01-AUG-08:31 | 0.69 |
September | 0.521232E+09 | 0.52 | 859.04 | 01-SEP-08:32 | 0.69 |
October | 0.339439E+09 | 0.51 | 859.04 | 01-OCT-08:62 | 0.69 |
November | 0.206834E+09 | 0.50 | 859.04 | 01-NOV-08:62 | 0.69 |
December | 0.318138E+09 | 0.50 | 859.04 | 01-DEC-09:02 | 0.70 |
Annual Sum or Average | 0.561692E+10 | 0.53 | |||
Minimum of Months | 0.206834E+09 | 0.49 | 859.04 | 0.69 | |
Maximum of Months | 0.875832E+09 | 0.58 | 859.04 | 0.70 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 99620152.28 | 0.56 | 258.93 | 01-JAN-16:02 | 0.70 |
February | 93551874.86 | 0.57 | 258.93 | 01-FEB-09:02 | 0.70 |
March | 98231205.12 | 0.58 | 258.93 | 01-MAR-16:02 | 0.70 |
April | 0.130943E+09 | 0.63 | 258.93 | 01-APR-15:02 | 0.70 |
May | 0.155821E+09 | 0.63 | 258.93 | 01-MAY-08:62 | 0.69 |
June | 0.220062E+09 | 0.66 | 258.93 | 01-JUN-08:62 | 0.70 |
July | 0.236535E+09 | 0.67 | 258.93 | 01-JUL-08:62 | 0.69 |
August | 0.233734E+09 | 0.67 | 258.93 | 01-AUG-08:62 | 0.69 |
September | 0.189934E+09 | 0.65 | 258.93 | 01-SEP-08:62 | 0.69 |
October | 0.146642E+09 | 0.63 | 258.93 | 01-OCT-08:62 | 0.69 |
November | 86321427.40 | 0.58 | 258.93 | 01-NOV-08:62 | 0.69 |
December | 96260745.92 | 0.56 | 258.93 | 01-DEC-16:02 | 0.70 |
Annual Sum or Average | 0.178766E+10 | 0.62 | |||
Minimum of Months | 86321427.40 | 0.56 | 258.93 | 0.69 | |
Maximum of Months | 0.236535E+09 | 0.67 | 258.93 | 0.70 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.107654E+09 | 0.52 | 255.72 | 01-JAN-09:02 | 0.70 |
February | 84330324.60 | 0.52 | 255.72 | 01-FEB-09:02 | 0.70 |
March | 65374403.21 | 0.49 | 255.72 | 03-MAR-09:02 | 0.70 |
April | 84510219.18 | 0.49 | 255.72 | 01-APR-15:02 | 0.70 |
May | 0.127371E+09 | 0.51 | 255.72 | 01-MAY-08:62 | 0.69 |
June | 0.207416E+09 | 0.56 | 255.72 | 01-JUN-08:51 | 0.69 |
July | 0.220764E+09 | 0.55 | 255.72 | 01-JUL-08:51 | 0.69 |
August | 0.200122E+09 | 0.54 | 255.72 | 01-AUG-08:31 | 0.69 |
September | 0.133177E+09 | 0.50 | 255.72 | 01-SEP-08:51 | 0.69 |
October | 78630419.95 | 0.47 | 255.72 | 01-OCT-08:62 | 0.69 |
November | 72854532.39 | 0.51 | 255.72 | 01-NOV-15:02 | 0.70 |
December | 0.112265E+09 | 0.53 | 255.72 | 01-DEC-09:02 | 0.70 |
Annual Sum or Average | 0.149447E+10 | 0.52 | |||
Minimum of Months | 65374403.21 | 0.47 | 255.72 | 0.69 | |
Maximum of Months | 0.220764E+09 | 0.56 | 255.72 | 0.70 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.781427E+09 | 0.62 | 1074.49 | 01-JAN-09:02 | 0.70 |
February | 0.731382E+09 | 0.63 | 1074.49 | 01-FEB-16:02 | 0.70 |
March | 0.630590E+09 | 0.62 | 1074.49 | 01-MAR-09:02 | 0.70 |
April | 0.619132E+09 | 0.64 | 1074.49 | 01-APR-08:62 | 0.70 |
May | 0.640527E+09 | 0.63 | 1074.49 | 01-MAY-08:62 | 0.70 |
June | 0.842135E+09 | 0.65 | 1074.49 | 01-JUN-08:62 | 0.70 |
July | 0.105933E+10 | 0.67 | 1074.49 | 01-JUL-08:62 | 0.69 |
August | 0.114471E+10 | 0.66 | 1074.49 | 01-AUG-08:62 | 0.69 |
September | 0.118211E+10 | 0.66 | 1074.49 | 01-SEP-08:62 | 0.69 |
October | 0.115443E+10 | 0.65 | 1074.49 | 01-OCT-08:62 | 0.69 |
November | 0.887418E+09 | 0.64 | 1074.49 | 01-NOV-08:62 | 0.69 |
December | 0.810681E+09 | 0.62 | 1074.49 | 01-DEC-09:02 | 0.70 |
Annual Sum or Average | 0.104839E+11 | 0.64 | |||
Minimum of Months | 0.619132E+09 | 0.62 | 1074.49 | 0.69 | |
Maximum of Months | 0.118211E+10 | 0.67 | 1074.49 | 0.70 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.668990E+09 | 0.602091E+09 | 783.43 | 20-JAN-16:50 | 705.09 | 705.09 | 37.74 | 1.61 |
February | 0.552016E+09 | 0.496814E+09 | 785.91 | 04-FEB-17:25 | 707.32 | 707.32 | 37.62 | 1.62 |
March | 0.558633E+09 | 0.502770E+09 | 774.42 | 10-MAR-08:13 | 696.98 | 696.98 | 40.84 | 1.55 |
April | 0.385318E+09 | 0.346786E+09 | 749.17 | 23-APR-05:10 | 674.25 | 674.25 | 37.20 | 1.41 |
May | 0.194365E+09 | 0.174928E+09 | 715.89 | 07-MAY-05:00 | 644.30 | 644.30 | 36.81 | 1.26 |
June | 32307698.94 | 29076929.05 | 549.28 | 09-JUN-05:00 | 494.35 | 494.35 | 32.91 | 0.78 |
July | 33410.05 | 30069.05 | 49.06 | 26-JUL-08:58 | 44.16 | 44.16 | 27.12 | 0.05 |
August | 376631.74 | 338968.57 | 108.35 | 31-AUG-06:00 | 97.52 | 97.52 | 26.72 | 0.12 |
September | 23067508.57 | 20760757.72 | 328.92 | 20-SEP-06:00 | 296.03 | 296.03 | 27.81 | 0.40 |
October | 0.363188E+09 | 0.326869E+09 | 757.39 | 26-OCT-09:40 | 681.65 | 681.65 | 40.31 | 1.45 |
November | 0.572897E+09 | 0.515607E+09 | 777.21 | 27-NOV-17:50 | 699.49 | 699.49 | 38.01 | 1.57 |
December | 0.735349E+09 | 0.661814E+09 | 796.85 | 09-DEC-16:03 | 717.17 | 717.17 | 36.40 | 1.70 |
Annual Sum or Average | 0.408654E+10 | 0.367789E+10 | ||||||
Minimum of Months | 33410.05 | 30069.05 | 49.06 | 44.16 | 44.16 | 26.72 | 0.05 | |
Maximum of Months | 0.735349E+09 | 0.661814E+09 | 796.85 | 717.17 | 717.17 | 40.84 | 1.70 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 27039335.34 | 24335401.80 | 144.79 | 05-JAN-16:01 | 130.31 | 130.31 | 6.72 | 5.45 |
February | 38207854.18 | 34387068.76 | 344.06 | 14-FEB-16:01 | 309.66 | 309.66 | 6.72 | 8.12 |
March | 67679814.10 | 60911832.69 | 368.24 | 08-MAR-16:03 | 331.41 | 331.41 | 6.72 | 8.37 |
April | 0.160189E+09 | 0.144170E+09 | 425.54 | 13-APR-18:02 | 382.98 | 382.98 | 6.72 | 8.92 |
May | 0.284497E+09 | 0.256047E+09 | 783.67 | 21-MAY-19:30 | 705.31 | 705.31 | 6.72 | 11.61 |
June | 0.658264E+09 | 0.592438E+09 | 1446.40 | 28-JUN-18:10 | 1301.76 | 1301.76 | 6.72 | 14.98 |
July | 0.956240E+09 | 0.860616E+09 | 1449.05 | 20-JUL-20:10 | 1304.15 | 1304.15 | 6.72 | 14.99 |
August | 0.944579E+09 | 0.850121E+09 | 1330.21 | 16-AUG-18:02 | 1197.19 | 1197.19 | 6.72 | 14.47 |
September | 0.585588E+09 | 0.527029E+09 | 1193.69 | 28-SEP-18:03 | 1074.32 | 1074.32 | 6.72 | 13.84 |
October | 0.236972E+09 | 0.213275E+09 | 973.32 | 04-OCT-15:05 | 875.99 | 875.99 | 6.72 | 12.72 |
November | 51534575.96 | 46381118.37 | 231.56 | 02-NOV-15:02 | 208.40 | 208.40 | 6.72 | 6.79 |
December | 26448902.11 | 23804011.90 | 141.25 | 30-DEC-09:02 | 127.13 | 127.13 | 6.72 | 5.39 |
Annual Sum or Average | 0.403724E+10 | 0.363351E+10 | ||||||
Minimum of Months | 26448902.11 | 23804011.90 | 141.25 | 127.13 | 127.13 | 6.72 | 5.39 | |
Maximum of Months | 0.956240E+09 | 0.860616E+09 | 1449.05 | 1304.15 | 1304.15 | 6.72 | 14.99 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.495787E+10 | 0.446208E+10 | 2413.80 | 01-JAN-00:10 | 2172.42 | 2172.42 | 6.79 | 21.35 |
February | 0.496033E+10 | 0.446430E+10 | 2413.80 | 01-FEB-00:20 | 2172.42 | 2172.42 | 6.72 | 21.35 |
March | 0.611161E+10 | 0.550045E+10 | 2413.80 | 01-MAR-00:10 | 2172.42 | 2172.42 | 6.73 | 21.35 |
April | 0.623575E+10 | 0.561218E+10 | 2413.80 | 01-APR-00:10 | 2172.42 | 2172.42 | 6.76 | 21.35 |
May | 0.646246E+10 | 0.581621E+10 | 2413.80 | 01-MAY-00:05 | 2172.42 | 2172.42 | 7.17 | 21.35 |
June | 0.625656E+10 | 0.563091E+10 | 2413.80 | 01-JUN-00:05 | 2172.42 | 2172.42 | 7.99 | 21.35 |
July | 0.646511E+10 | 0.581860E+10 | 2413.80 | 01-JUL-00:10 | 2172.42 | 2172.42 | 8.82 | 21.35 |
August | 0.646511E+10 | 0.581860E+10 | 2413.80 | 01-AUG-00:05 | 2172.42 | 2172.42 | 9.03 | 21.35 |
September | 0.625656E+10 | 0.563091E+10 | 2413.80 | 01-SEP-00:05 | 2172.42 | 2172.42 | 8.82 | 21.35 |
October | 0.628809E+10 | 0.565928E+10 | 2413.80 | 01-OCT-00:10 | 2172.42 | 2172.42 | 7.83 | 21.35 |
November | 0.568423E+10 | 0.511580E+10 | 2413.80 | 01-NOV-00:05 | 2172.42 | 2172.42 | 7.04 | 21.35 |
December | 0.490131E+10 | 0.441118E+10 | 2413.80 | 01-DEC-00:10 | 2172.42 | 2172.42 | 6.73 | 21.35 |
Annual Sum or Average | 0.710450E+11 | 0.639405E+11 | ||||||
Minimum of Months | 0.490131E+10 | 0.441118E+10 | 2413.80 | 2172.42 | 2172.42 | 6.72 | 21.35 | |
Maximum of Months | 0.646511E+10 | 0.581860E+10 | 2413.80 | 2172.42 | 2172.42 | 9.03 | 21.35 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:10 | 14.37 | 14.37 | 49.19 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:10 | 14.37 | 14.37 | 49.98 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:10 | 14.37 | 14.37 | 50.06 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 52.81 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:05 | 14.37 | 14.37 | 53.04 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:05 | 14.37 | 14.37 | 53.56 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 54.15 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:05 | 14.37 | 14.37 | 54.16 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:05 | 14.37 | 14.37 | 54.08 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:10 | 14.37 | 14.37 | 53.23 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:05 | 14.37 | 14.37 | 53.28 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:10 | 14.37 | 14.37 | 50.74 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 49.19 | 0.37 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 54.16 | 0.37 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 49.31 | 60.00 | 30843.97 | 163839.24 | 05-JAN-09:03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 40.65 | 60.00 | 29267.23 | 155697.25 | 06-FEB-16:03 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 50.53 | 60.00 | 31473.78 | 148850.93 | 06-MAR-09:04 |
April | 0.00 | 0.00 | 01-APR-00:10 | 33.59 | 60.00 | 23947.45 | 134367.71 | 23-APR-05:10 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 24.01 | 24.01 | 11771.69 | 122301.40 | 07-MAY-05:00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 23.97 | 23.97 | 2015.59 | 88597.58 | 09-JUN-05:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 24.29 | 24.29 | 1.81 | 7014.05 | 26-JUL-08:58 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 28.02 | 28.02 | 18.61 | 16108.93 | 31-AUG-06:00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.27 | 26.27 | 1433.57 | 53283.88 | 20-SEP-06:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.41 | 25.41 | 20624.11 | 138199.20 | 13-OCT-08:05 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 23.69 | 60.00 | 31653.76 | 149124.30 | 25-NOV-19:03 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 50.64 | 60.00 | 34040.63 | 167856.56 | 09-DEC-16:03 |
Annual Sum or Average | 0.00 | 18035.63 | ||||||
Minimum of Months | 0.00 | 0.00 | 23.69 | 23.97 | 1.81 | 7014.05 | ||
Maximum of Months | 0.00 | 0.00 | 50.64 | 60.00 | 34040.63 | 167856.56 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 17684.49 | 120091.25 | 05-JAN-16:01 | 8.04 | 6.70 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 22928.55 | 314937.80 | 14-FEB-16:01 | 10.22 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 32216.48 | 294142.12 | 08-MAR-16:02 | 9.99 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 73484.80 | 355601.71 | 13-APR-18:03 | 10.67 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 112128.97 | 372492.79 | 15-MAY-18:03 | 10.86 | 6.70 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 188448.24 | 455320.01 | 28-JUN-18:10 | 11.79 | 6.70 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 244034.91 | 430401.50 | 21-JUL-18:17 | 11.51 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 224356.94 | 459407.53 | 04-AUG-18:02 | 11.84 | 6.70 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 162130.88 | 390836.35 | 02-SEP-18:03 | 11.07 | 6.70 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 85458.69 | 396433.59 | 04-OCT-15:05 | 11.13 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 27849.22 | 178271.27 | 02-NOV-15:03 | 8.69 | 6.70 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 18400.05 | 107514.96 | 31-DEC-16:03 | 7.90 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 101266.00 | 0.00 | ||||||
Minimum of Months | 17684.49 | 107514.96 | 7.90 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 244034.91 | 459407.53 | 11.84 | 6.70 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 49.19 | 60.05 | 26472.64 | 55812.69 | 31-JAN-08:00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 49.98 | 60.05 | 26677.67 | 55855.92 | 06-FEB-07:50 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 50.06 | 60.05 | 26050.08 | 55332.81 | 01-MAR-08:00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 52.81 | 60.05 | 24675.70 | 52886.41 | 03-APR-07:00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 53.04 | 60.05 | 22968.82 | 49773.22 | 01-MAY-07:00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 53.56 | 60.05 | 21377.17 | 46110.29 | 01-JUN-06:42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 54.15 | 60.05 | 20302.37 | 43131.20 | 03-JUL-06:20 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 54.16 | 60.05 | 20097.06 | 42367.45 | 31-AUG-06:52 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 54.08 | 60.05 | 20756.19 | 44452.40 | 29-SEP-06:45 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 53.23 | 60.05 | 22125.60 | 47965.42 | 31-OCT-07:00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 53.28 | 60.05 | 23838.55 | 51512.53 | 30-NOV-07:20 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 50.74 | 60.05 | 25424.49 | 54288.09 | 29-DEC-07:50 |
Annual Sum or Average | 0.00 | 23378.29 | ||||||
Minimum of Months | 0.00 | 0.00 | 49.19 | 60.05 | 20097.06 | 42367.45 | ||
Maximum of Months | 0.00 | 0.00 | 54.16 | 60.05 | 26677.67 | 55855.92 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.542438E+09 | 0.00 | 28570337.31 | 0.271000E+10 | 0.00 | 0.00 |
February | 0.280905E+09 | 0.00 | 0.355265E+09 | 0.244774E+10 | 0.00 | 0.00 |
March | 10394084.45 | 0.00 | 0.140706E+10 | 0.271000E+10 | 0.00 | 0.00 |
April | 11344.00 | 0.00 | 0.584266E+10 | 0.262258E+10 | 0.00 | 0.00 |
May | 20680.71 | 0.00 | 0.112570E+11 | 0.271000E+10 | 0.00 | 0.00 |
June | 30215.22 | 0.00 | 0.191799E+11 | 0.262258E+10 | 0.00 | 0.00 |
July | 30660.66 | 0.00 | 0.300006E+11 | 0.271000E+10 | 0.00 | 0.00 |
August | 30814.97 | 0.00 | 0.258740E+11 | 0.271000E+10 | 0.00 | 0.00 |
September | 30418.50 | 0.00 | 0.155563E+11 | 0.262258E+10 | 0.00 | 0.00 |
October | 7733983.18 | 0.00 | 0.634340E+10 | 0.271000E+10 | 0.00 | 0.00 |
November | 27119694.41 | 0.00 | 0.142367E+09 | 0.262258E+10 | 0.00 | 0.00 |
December | 0.486629E+09 | 0.00 | 0.00 | 0.271000E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.135537E+10 | 0.00 | 0.115987E+12 | 0.319080E+11 | 0.00 | 0.00 |
Minimum of Months | 11344.00 | 0.00 | 0.00 | 0.244774E+10 | 0.00 | 0.00 |
Maximum of Months | 0.542438E+09 | 0.00 | 0.300006E+11 | 0.271000E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.624117E+11 | 0.00 | 0.107850E+10 | 0.341957E+11 | 0.00 | 0.00 |
February | 0.580562E+11 | 0.00 | 0.641656E+10 | 0.310091E+11 | 0.00 | 0.00 |
March | 0.810483E+11 | 0.00 | 0.235609E+11 | 0.354890E+11 | 0.00 | 0.00 |
April | 0.619676E+11 | 0.00 | 0.967900E+11 | 0.364315E+11 | 0.00 | 0.00 |
May | 0.315793E+11 | 0.00 | 0.181877E+12 | 0.390943E+11 | 0.00 | 0.00 |
June | 0.524449E+10 | 0.00 | 0.320255E+12 | 0.416934E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.440332E+12 | 0.454641E+11 | 0.00 | 0.00 |
August | 46174728.60 | 0.00 | 0.394622E+12 | 0.464715E+11 | 0.00 | 0.00 |
September | 0.373129E+10 | 0.00 | 0.255256E+12 | 0.434107E+11 | 0.00 | 0.00 |
October | 0.538234E+11 | 0.00 | 0.109028E+12 | 0.416015E+11 | 0.00 | 0.00 |
November | 0.758180E+11 | 0.00 | 0.330358E+10 | 0.365678E+11 | 0.00 | 0.00 |
December | 0.684578E+11 | 0.00 | 0.100805E+09 | 0.349803E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.502184E+12 | 0.00 | 0.183262E+13 | 0.466409E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.100805E+09 | 0.310091E+11 | 0.00 | 0.00 |
Maximum of Months | 0.810483E+11 | 0.00 | 0.440332E+12 | 0.464715E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.271000E+10 | 28570337.31 | 0.542438E+09 | 0.446134E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244774E+10 | 0.355265E+09 | 0.280905E+09 | 0.356406E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.271000E+10 | 0.140706E+10 | 10394084.45 | 0.252956E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.262258E+10 | 0.584266E+10 | 11344.00 | 0.112756E+11 | 1745135.69 | 0.00 | 0.00 | 0.00 |
May | 0.271000E+10 | 0.112570E+11 | 20680.71 | 0.546111E+10 | 42197863.86 | 0.00 | 0.00 | 0.00 |
June | 0.262258E+10 | 0.191799E+11 | 30215.22 | 0.208402E+10 | 0.129373E+10 | 0.00 | 0.00 | 0.00 |
July | 0.271000E+10 | 0.300006E+11 | 30660.66 | 0.422327E+09 | 0.410935E+10 | 0.00 | 0.00 | 0.00 |
August | 0.271000E+10 | 0.258740E+11 | 30814.97 | 0.597826E+09 | 0.238174E+10 | 0.00 | 0.00 | 0.00 |
September | 0.262258E+10 | 0.155563E+11 | 30418.50 | 0.122428E+10 | 0.380739E+09 | 0.00 | 0.00 | 0.00 |
October | 0.271000E+10 | 0.634340E+10 | 7733983.18 | 0.128513E+11 | 10061989.85 | 0.00 | 0.00 | 0.00 |
November | 0.262258E+10 | 0.142367E+09 | 27119694.41 | 0.290421E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.271000E+10 | 0.00 | 0.486629E+09 | 0.457585E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319080E+11 | 0.115987E+12 | 0.135537E+10 | 0.214267E+12 | 0.821956E+10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244774E+10 | 0.00 | 11344.00 | 0.422327E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.271000E+10 | 0.300006E+11 | 0.542438E+09 | 0.457585E+11 | 0.410935E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.341957E+11 | 0.107850E+10 | 0.624117E+11 | 0.460353E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.310091E+11 | 0.641656E+10 | 0.580562E+11 | 0.345216E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.354890E+11 | 0.235609E+11 | 0.810483E+11 | 0.174484E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.364315E+11 | 0.967900E+11 | 0.619676E+11 | 0.402027E+11 | 1163910.07 | 0.00 | 0.00 | 0.00 |
May | 0.390943E+11 | 0.181877E+12 | 0.315793E+11 | 0.831236E+10 | 0.966101E+09 | 0.00 | 0.00 | 0.00 |
June | 0.416934E+11 | 0.320255E+12 | 0.524449E+10 | 0.992373E+10 | 0.217967E+11 | 0.00 | 0.00 | 0.00 |
July | 0.454641E+11 | 0.440332E+12 | 0.00 | 0.965164E+10 | 0.293927E+11 | 0.00 | 0.00 | 0.00 |
August | 0.464715E+11 | 0.394622E+12 | 46174728.60 | 0.947254E+10 | 0.179320E+11 | 0.00 | 0.00 | 0.00 |
September | 0.434107E+11 | 0.255256E+12 | 0.373129E+10 | 0.746309E+10 | 0.366367E+10 | 0.00 | 0.00 | 0.00 |
October | 0.416015E+11 | 0.109028E+12 | 0.538234E+11 | 0.737993E+11 | 91366773.13 | 0.00 | 0.00 | 0.00 |
November | 0.365678E+11 | 0.330358E+10 | 0.758180E+11 | 0.244015E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.349803E+11 | 0.100805E+09 | 0.684578E+11 | 0.478138E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.466409E+12 | 0.183262E+13 | 0.502184E+12 | 0.186103E+13 | 0.738437E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.310091E+11 | 0.100805E+09 | 0.00 | 0.746309E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.464715E+11 | 0.440332E+12 | 0.810483E+11 | 0.478138E+12 | 0.293927E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.271000E+10 | 0.542438E+09 | 28570337.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244774E+10 | 0.280905E+09 | 0.355265E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.271000E+10 | 10394084.45 | 0.140706E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.262258E+10 | 11344.00 | 0.584266E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.271000E+10 | 20680.71 | 0.112570E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.262258E+10 | 30215.22 | 0.191799E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.271000E+10 | 30660.66 | 0.300006E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.271000E+10 | 30814.97 | 0.258740E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.262258E+10 | 30418.50 | 0.155563E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.271000E+10 | 7733983.18 | 0.634340E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.262258E+10 | 27119694.41 | 0.142367E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.271000E+10 | 0.486629E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319080E+11 | 0.135537E+10 | 0.115987E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244774E+10 | 11344.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.271000E+10 | 0.542438E+09 | 0.300006E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.341957E+11 | 0.624117E+11 | 0.107850E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.310091E+11 | 0.580562E+11 | 0.641656E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.354890E+11 | 0.810483E+11 | 0.235609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.364315E+11 | 0.619676E+11 | 0.967900E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.390943E+11 | 0.315793E+11 | 0.181877E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.416934E+11 | 0.524449E+10 | 0.320255E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.454641E+11 | 0.00 | 0.440332E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.464715E+11 | 46174728.60 | 0.394622E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.434107E+11 | 0.373129E+10 | 0.255256E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.416015E+11 | 0.538234E+11 | 0.109028E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.365678E+11 | 0.758180E+11 | 0.330358E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.349803E+11 | 0.684578E+11 | 0.100805E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.466409E+12 | 0.502184E+12 | 0.183262E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.310091E+11 | 0.00 | 0.100805E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.464715E+11 | 0.810483E+11 | 0.440332E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.321689E+10 | 0.00 | 0.00 | 56418578.80 | 0.00 | 0.00 | 0.512350E+11 | 0.00 | 1.11 |
February | 0.148352E+11 | 0.00 | 0.00 | 25739334.82 | 0.00 | 0.00 | 0.312905E+11 | 0.00 | 1.03 |
March | 0.301478E+11 | 0.00 | 0.00 | 10648234.49 | 0.00 | 0.00 | 0.197257E+11 | 0.00 | 1.00 |
April | 0.260560E+11 | 0.00 | 0.00 | 9792608.96 | 0.00 | 0.00 | 0.150411E+11 | 0.00 | 1.00 |
May | 0.139781E+11 | 0.00 | 0.00 | 15271184.16 | 3511690.65 | 0.00 | 0.187199E+11 | 0.00 | 1.01 |
June | 0.289937E+10 | 37828341.19 | 0.00 | 30538590.34 | 0.464476E+09 | 0.00 | 0.160960E+11 | 0.00 | 0.97 |
July | 0.146708E+09 | 0.608231E+09 | 0.00 | 52264661.02 | 0.269382E+09 | 0.00 | 0.111612E+11 | 0.00 | 0.99 |
August | 0.146465E+09 | 0.291371E+09 | 0.00 | 72794753.46 | 57496594.20 | 0.00 | 0.164738E+11 | 0.00 | 1.09 |
September | 48227451.26 | 52878882.65 | 0.00 | 93578246.92 | 1536774.35 | 0.00 | 0.305632E+11 | 0.00 | 1.25 |
October | 17132494.44 | 304027.06 | 0.00 | 97271642.72 | 0.00 | 0.00 | 0.543662E+11 | 0.00 | 1.29 |
November | 11439681.03 | 0.00 | 0.00 | 85467652.58 | 0.00 | 0.00 | 0.634255E+11 | 0.00 | 1.27 |
December | 0.140256E+09 | 0.00 | 0.00 | 79744024.89 | 0.00 | 0.00 | 0.602762E+11 | 0.00 | 1.22 |
Annual Sum or Average | 0.916436E+11 | 0.990613E+09 | 0.00 | 0.629530E+09 | 0.796403E+09 | 0.00 | 0.388374E+12 | 0.00 | 1.10 |
Minimum of Months | 11439681.03 | 0.00 | 0.00 | 9792608.96 | 0.00 | 0.00 | 0.111612E+11 | 0.00 | 0.97 |
Maximum of Months | 0.301478E+11 | 0.608231E+09 | 0.00 | 97271642.72 | 0.464476E+09 | 0.00 | 0.634255E+11 | 0.00 | 1.29 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.458226E+10 | 0.00 | 0.00 | 3763630.75 | 0.00 | 0.273323E+09 | 0.266189E+10 | 0.00 | 2.74 |
February | 0.401621E+10 | 0.00 | 0.00 | 3749764.40 | 0.00 | 41776915.68 | 0.259899E+10 | 0.00 | 2.72 |
March | 0.502979E+10 | 0.00 | 0.00 | 3308386.93 | 0.00 | 0.00 | 0.195493E+10 | 0.00 | 2.61 |
April | 0.404279E+10 | 0.00 | 0.00 | 3433143.71 | 0.00 | 0.00 | 0.147869E+10 | 0.00 | 2.51 |
May | 0.343747E+10 | 467761.05 | 0.00 | 3085425.70 | 34975.28 | 0.00 | 0.854833E+09 | 0.00 | 2.44 |
June | 0.158255E+10 | 87141295.08 | 0.00 | 3385092.85 | 85817.02 | 0.00 | 0.874082E+09 | 0.00 | 2.41 |
July | 0.365811E+09 | 0.151494E+09 | 0.00 | 4629685.96 | 447420.42 | 0.00 | 0.103799E+10 | 0.00 | 2.50 |
August | 0.568136E+09 | 74549537.87 | 0.00 | 7740119.69 | 77764.50 | 0.00 | 0.135352E+10 | 0.00 | 2.75 |
September | 0.129353E+10 | 15399919.62 | 0.00 | 9765850.54 | 0.00 | 0.00 | 0.199790E+10 | 0.00 | 3.04 |
October | 0.293085E+10 | 52285.99 | 0.00 | 9000364.26 | 0.00 | 7249520.95 | 0.323434E+10 | 0.00 | 3.01 |
November | 0.416370E+10 | 0.00 | 0.00 | 4987520.68 | 0.00 | 0.00 | 0.372047E+10 | 0.00 | 2.86 |
December | 0.455326E+10 | 0.00 | 0.00 | 4197301.63 | 0.00 | 0.148516E+09 | 0.313983E+10 | 0.00 | 2.79 |
Annual Sum or Average | 0.365664E+11 | 0.329105E+09 | 0.00 | 61046287.11 | 645977.22 | 0.470865E+09 | 0.249074E+11 | 0.00 | 2.70 |
Minimum of Months | 0.365811E+09 | 0.00 | 0.00 | 3085425.70 | 0.00 | 0.00 | 0.854833E+09 | 0.00 | 2.41 |
Maximum of Months | 0.502979E+10 | 0.151494E+09 | 0.00 | 9765850.54 | 447420.42 | 0.273323E+09 | 0.372047E+10 | 0.00 | 3.04 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.342482E+10 | 0.00 | 0.00 | 689633.02 | 0.00 | 0.00 | 0.105396E+10 | 0.00 | 1.42 |
February | 0.275423E+10 | 0.00 | 0.00 | 969537.32 | 0.00 | 0.00 | 0.132332E+10 | 0.00 | 1.43 |
March | 0.233739E+10 | 0.00 | 0.00 | 1724317.14 | 0.00 | 0.00 | 0.228049E+10 | 0.00 | 1.45 |
April | 0.113798E+10 | 0.00 | 0.00 | 3416281.92 | 0.00 | 0.00 | 0.280175E+10 | 0.00 | 1.52 |
May | 0.677738E+09 | 310481.89 | 0.00 | 4646738.06 | 7335.42 | 0.00 | 0.250727E+10 | 0.00 | 1.56 |
June | 0.150178E+09 | 46977105.69 | 0.00 | 5930326.45 | 1260284.49 | 0.00 | 0.182611E+10 | 0.00 | 1.58 |
July | 1804389.97 | 81523632.53 | 0.00 | 6763829.33 | 2317874.26 | 0.00 | 0.121929E+10 | 0.00 | 1.60 |
August | 16185841.70 | 31476848.46 | 0.00 | 7788993.54 | 1453767.66 | 0.00 | 0.161458E+10 | 0.00 | 1.67 |
September | 56894486.38 | 4961867.96 | 0.00 | 7549018.39 | 0.00 | 0.00 | 0.252819E+10 | 0.00 | 1.71 |
October | 0.837273E+09 | 27515.25 | 0.00 | 4931524.58 | 0.00 | 0.00 | 0.323604E+10 | 0.00 | 1.58 |
November | 0.215624E+10 | 0.00 | 0.00 | 1614453.72 | 0.00 | 0.00 | 0.244590E+10 | 0.00 | 1.45 |
December | 0.354405E+10 | 0.00 | 0.00 | 667361.86 | 0.00 | 0.00 | 0.978917E+09 | 0.00 | 1.41 |
Annual Sum or Average | 0.170948E+11 | 0.165277E+09 | 0.00 | 46692015.33 | 5039261.83 | 0.00 | 0.238158E+11 | 0.00 | 1.53 |
Minimum of Months | 1804389.97 | 0.00 | 0.00 | 667361.86 | 0.00 | 0.00 | 0.978917E+09 | 0.00 | 1.41 |
Maximum of Months | 0.354405E+10 | 81523632.53 | 0.00 | 7788993.54 | 2317874.26 | 0.00 | 0.323604E+10 | 0.00 | 1.71 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.362709E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 |
February | 0.327789E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 |
March | 0.365971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 |
April | 0.295070E+10 | 0.00 | 0.00 | 87347.07 | 0.00 | 0.00 | 73004712.12 | 0.00 | 0.54 |
May | 0.201933E+10 | 0.00 | 0.00 | 795016.50 | 259128.66 | 0.00 | 0.391482E+09 | 0.00 | 0.55 |
June | 0.557877E+09 | 37619433.02 | 0.00 | 3755906.92 | 2547679.23 | 0.00 | 0.926903E+09 | 0.00 | 0.58 |
July | 1835690.49 | 68017990.14 | 0.00 | 5599702.19 | 1380706.77 | 0.00 | 0.930345E+09 | 0.00 | 0.60 |
August | 75791417.52 | 22425865.26 | 0.00 | 5278474.17 | 4085563.03 | 0.00 | 0.111602E+10 | 0.00 | 0.60 |
September | 0.826380E+09 | 1306777.08 | 0.00 | 2075615.56 | 2708569.79 | 0.00 | 0.986560E+09 | 0.00 | 0.58 |
October | 0.275753E+10 | 0.00 | 0.00 | 407457.16 | 22434.24 | 0.00 | 0.283303E+09 | 0.00 | 0.55 |
November | 0.365002E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 |
December | 0.367204E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 |
Annual Sum or Average | 0.270762E+11 | 0.129370E+09 | 0.00 | 17999519.59 | 11004081.72 | 0.00 | 0.470762E+10 | 0.00 | 0.56 |
Minimum of Months | 1835690.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 |
Maximum of Months | 0.367204E+10 | 68017990.14 | 0.00 | 5599702.19 | 4085563.03 | 0.00 | 0.111602E+10 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.217773E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7109704.76 | 0.00 | 0.00 | 0.56 |
February | 0.197449E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.56 |
March | 0.220449E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.56 |
April | 0.182126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 |
May | 0.140961E+10 | 0.00 | 0.00 | 34213.05 | 156090.55 | 0.00 | 32030064.76 | 0.00 | 0.57 |
June | 0.546346E+09 | 20855538.71 | 0.00 | 1276001.27 | 2915057.07 | 0.00 | 0.293552E+09 | 0.00 | 0.56 |
July | 41796348.10 | 37986396.81 | 0.00 | 2092329.72 | 2442601.05 | 0.00 | 0.449743E+09 | 0.00 | 0.57 |
August | 0.204990E+09 | 11929689.28 | 0.00 | 1676592.83 | 3927860.66 | 0.00 | 0.439854E+09 | 0.00 | 0.57 |
September | 0.873387E+09 | 562818.73 | 0.00 | 247651.67 | 1855893.62 | 0.00 | 0.170338E+09 | 0.00 | 0.57 |
October | 0.179097E+10 | 0.00 | 0.00 | 20154.63 | 13513.65 | 0.00 | 30554549.04 | 0.00 | 0.57 |
November | 0.219865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.56 |
December | 0.221192E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.56 |
Annual Sum or Average | 0.174556E+11 | 71334443.53 | 0.00 | 5346943.17 | 11311016.60 | 7109704.76 | 0.141607E+10 | 0.00 | 0.57 |
Minimum of Months | 41796348.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.56 |
Maximum of Months | 0.221192E+10 | 37986396.81 | 0.00 | 2092329.72 | 3927860.66 | 7109704.76 | 0.449743E+09 | 0.00 | 0.57 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 2807081.35 | 0.00 | 0.00 | 0.105605E+09 | 0.00 | 0.00 | 0.800539E+11 | 0.00 | 25.38 |
February | 0.00 | 0.00 | 0.00 | 96336557.24 | 0.00 | 0.00 | 0.728113E+11 | 0.00 | 25.38 |
March | 0.00 | 0.00 | 0.00 | 0.114197E+09 | 0.00 | 0.00 | 0.830379E+11 | 0.00 | 25.54 |
April | 0.00 | 0.00 | 0.00 | 0.126553E+09 | 0.00 | 0.00 | 0.671885E+11 | 0.00 | 25.70 |
May | 0.00 | 4584730.02 | 0.00 | 0.141131E+09 | 0.00 | 0.00 | 0.529900E+11 | 0.00 | 25.80 |
June | 0.00 | 0.699445E+09 | 0.00 | 0.122359E+09 | 0.00 | 0.00 | 0.297122E+11 | 0.00 | 23.87 |
July | 0.00 | 0.122368E+10 | 0.00 | 0.110171E+09 | 0.00 | 0.00 | 0.163774E+11 | 0.00 | 23.00 |
August | 0.00 | 0.462732E+09 | 0.00 | 0.130045E+09 | 0.00 | 0.00 | 0.227509E+11 | 0.00 | 24.08 |
September | 0.00 | 70315021.24 | 0.00 | 0.138027E+09 | 0.00 | 0.00 | 0.390670E+11 | 0.00 | 25.96 |
October | 0.00 | 392358.96 | 0.00 | 0.125730E+09 | 0.00 | 0.00 | 0.677901E+11 | 0.00 | 25.75 |
November | 0.00 | 0.00 | 0.00 | 0.105918E+09 | 0.00 | 0.00 | 0.814845E+11 | 0.00 | 25.48 |
December | 0.00 | 0.00 | 0.00 | 0.106983E+09 | 0.00 | 0.00 | 0.804474E+11 | 0.00 | 25.35 |
Annual Sum or Average | 2807081.35 | 0.246115E+10 | 0.00 | 0.142306E+10 | 0.00 | 0.00 | 0.693711E+12 | 0.00 | 25.10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 96336557.24 | 0.00 | 0.00 | 0.163774E+11 | 0.00 | 23.00 |
Maximum of Months | 2807081.35 | 0.122368E+10 | 0.00 | 0.141131E+09 | 0.00 | 0.00 | 0.830379E+11 | 0.00 | 25.96 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.457567E+10 | 0.00 | 0.00 | 31475695.16 | 0.00 | 0.00 | 0.279924E+11 | 0.00 | 4.24 |
February | 0.284195E+10 | 0.00 | 0.00 | 31406905.64 | 0.00 | 0.00 | 0.264913E+11 | 0.00 | 4.25 |
March | 0.385997E+10 | 0.00 | 0.00 | 34962790.95 | 0.00 | 0.00 | 0.273648E+11 | 0.00 | 4.13 |
April | 0.208427E+10 | 0.00 | 0.00 | 39005049.86 | 0.00 | 0.00 | 0.235131E+11 | 0.00 | 4.13 |
May | 0.207004E+10 | 2072961.05 | 0.00 | 37823887.90 | 35257.72 | 0.00 | 0.181402E+11 | 0.00 | 4.07 |
June | 0.759348E+09 | 0.328118E+09 | 0.00 | 34734838.61 | 1036413.35 | 0.00 | 0.115369E+11 | 0.00 | 4.03 |
July | 64706102.04 | 0.580542E+09 | 0.00 | 37180794.94 | 758884.28 | 0.00 | 0.758613E+10 | 0.00 | 4.18 |
August | 0.210805E+09 | 0.267017E+09 | 0.00 | 47863685.89 | 64006.43 | 0.00 | 0.100739E+11 | 0.00 | 4.53 |
September | 0.336566E+09 | 51370806.44 | 0.00 | 57378975.72 | 0.00 | 0.00 | 0.163887E+11 | 0.00 | 4.90 |
October | 0.148222E+10 | 212413.80 | 0.00 | 54950229.62 | 0.00 | 0.00 | 0.272727E+11 | 0.00 | 4.79 |
November | 0.208957E+10 | 0.00 | 0.00 | 40984037.51 | 0.00 | 0.00 | 0.325640E+11 | 0.00 | 4.48 |
December | 0.383577E+10 | 0.00 | 0.00 | 33969512.54 | 0.00 | 0.00 | 0.300490E+11 | 0.00 | 4.32 |
Annual Sum or Average | 0.242109E+11 | 0.122933E+10 | 0.00 | 0.481736E+09 | 1894561.78 | 0.00 | 0.258973E+12 | 0.00 | 4.34 |
Minimum of Months | 64706102.04 | 0.00 | 0.00 | 31406905.64 | 0.00 | 0.00 | 0.758613E+10 | 0.00 | 4.03 |
Maximum of Months | 0.457567E+10 | 0.580542E+09 | 0.00 | 57378975.72 | 1036413.35 | 0.00 | 0.325640E+11 | 0.00 | 4.90 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.201041E+11 | 0.00 | 0.00 | 73788147.75 | 0.00 | 0.00 | 0.760049E+11 | 0.00 | 1.82 |
February | 0.141991E+11 | 0.00 | 0.00 | 73686729.82 | 0.00 | 0.00 | 0.737747E+11 | 0.00 | 1.83 |
March | 0.159809E+11 | 0.00 | 0.00 | 93149518.87 | 0.00 | 0.00 | 0.853838E+11 | 0.00 | 1.88 |
April | 0.872363E+10 | 0.00 | 0.00 | 0.107263E+09 | 0.00 | 0.00 | 0.787034E+11 | 0.00 | 1.97 |
May | 0.645254E+10 | 6460095.69 | 0.00 | 0.122471E+09 | 116157.18 | 0.00 | 0.651972E+11 | 0.00 | 2.03 |
June | 0.182412E+10 | 0.951174E+09 | 0.00 | 0.130202E+09 | 28310190.15 | 0.00 | 0.427024E+11 | 0.00 | 2.01 |
July | 78402237.92 | 0.167630E+10 | 0.00 | 0.138874E+09 | 42000874.05 | 0.00 | 0.272708E+11 | 0.00 | 2.03 |
August | 0.329673E+09 | 0.682658E+09 | 0.00 | 0.163422E+09 | 9981357.21 | 0.00 | 0.358395E+11 | 0.00 | 2.13 |
September | 0.421570E+09 | 0.109398E+09 | 0.00 | 0.179285E+09 | 0.00 | 0.00 | 0.573996E+11 | 0.00 | 2.22 |
October | 0.449864E+10 | 573633.71 | 0.00 | 0.156560E+09 | 0.00 | 0.00 | 0.868850E+11 | 0.00 | 2.08 |
November | 0.763021E+10 | 0.00 | 0.00 | 0.108792E+09 | 0.00 | 0.00 | 0.946283E+11 | 0.00 | 1.91 |
December | 0.158775E+11 | 0.00 | 0.00 | 76183761.40 | 0.00 | 0.00 | 0.813266E+11 | 0.00 | 1.81 |
Annual Sum or Average | 0.961205E+11 | 0.342656E+10 | 0.00 | 0.142368E+10 | 80408578.58 | 0.00 | 0.805116E+12 | 0.00 | 1.98 |
Minimum of Months | 78402237.92 | 0.00 | 0.00 | 73686729.82 | 0.00 | 0.00 | 0.272708E+11 | 0.00 | 1.81 |
Maximum of Months | 0.201041E+11 | 0.167630E+10 | 0.00 | 0.179285E+09 | 42000874.05 | 0.00 | 0.946283E+11 | 0.00 | 2.22 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 31459937.82 | 0.00 | 0.00 | 3772586.69 | 0.00 | 0.863475E+09 | 0.500528E+09 | 0.00 | 0.35 |
February | 29418341.12 | 0.00 | 0.00 | 5631523.40 | 0.00 | 0.630714E+09 | 0.582353E+09 | 0.00 | 0.35 |
March | 34149075.22 | 0.00 | 0.00 | 9459455.00 | 0.00 | 0.348732E+09 | 0.934137E+09 | 0.00 | 0.35 |
April | 10090446.56 | 0.00 | 0.00 | 15861483.37 | 0.00 | 49797348.81 | 0.106917E+10 | 0.00 | 0.35 |
May | 10959465.61 | 425233.93 | 0.00 | 19143415.90 | 0.00 | 15880142.22 | 0.923012E+09 | 0.00 | 0.35 |
June | 2477728.79 | 6420581.61 | 0.00 | 22530847.50 | 0.00 | 612514.28 | 0.577029E+09 | 0.00 | 0.35 |
July | 0.00 | 0.100893E+09 | 0.00 | 11318805.80 | 0.00 | 78664.81 | 97294041.55 | 0.00 | 0.35 |
August | 0.00 | 49877192.12 | 0.00 | 16306165.63 | 0.00 | 339866.44 | 0.212520E+09 | 0.00 | 0.35 |
September | 0.00 | 4137173.21 | 0.00 | 20992619.69 | 0.00 | 814814.51 | 0.642720E+09 | 0.00 | 0.35 |
October | 13959767.21 | 272953.10 | 0.00 | 17968225.51 | 0.00 | 0.115848E+09 | 0.992144E+09 | 0.00 | 0.35 |
November | 14687694.12 | 0.00 | 0.00 | 7033392.53 | 0.00 | 0.434475E+09 | 0.889677E+09 | 0.00 | 0.35 |
December | 26659587.33 | 0.00 | 0.00 | 3572539.51 | 0.00 | 0.866666E+09 | 0.496733E+09 | 0.00 | 0.35 |
Annual Sum or Average | 0.173862E+09 | 0.162026E+09 | 0.00 | 0.153591E+09 | 0.00 | 0.332743E+10 | 0.791732E+10 | 0.00 | 0.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 3572539.51 | 0.00 | 78664.81 | 97294041.55 | 0.00 | 0.35 |
Maximum of Months | 34149075.22 | 0.100893E+09 | 0.00 | 22530847.50 | 0.00 | 0.866666E+09 | 0.106917E+10 | 0.00 | 0.35 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 86684505.04 | 0.00 | 0.00 | 1339266.34 | 0.00 | 0.116949E+10 | 0.141556E+09 | 0.00 | 0.35 |
February | 95752484.37 | 0.00 | 0.00 | 2343724.19 | 0.00 | 0.858252E+09 | 0.291623E+09 | 0.00 | 0.35 |
March | 0.168669E+09 | 0.00 | 0.00 | 4563544.15 | 0.00 | 0.511762E+09 | 0.641327E+09 | 0.00 | 0.35 |
April | 0.190107E+09 | 0.00 | 0.00 | 10567308.43 | 0.00 | 69462289.85 | 0.874647E+09 | 0.00 | 0.35 |
May | 0.181449E+09 | 425184.11 | 0.00 | 16069920.39 | 0.00 | 17598979.92 | 0.753763E+09 | 0.00 | 0.35 |
June | 0.115784E+09 | 6418908.07 | 259.96 | 19389194.54 | 0.00 | 472340.61 | 0.466934E+09 | 661.31 | 0.35 |
July | 39787205.84 | 93388357.34 | 2963.63 | 8056333.68 | 7489208.66 | 6395.35 | 60828842.49 | 399.90 | 0.36 |
August | 85088937.18 | 46845755.53 | 0.00 | 12331000.68 | 3025592.75 | 54836.73 | 0.131664E+09 | 0.00 | 0.35 |
September | 0.190385E+09 | 3914606.06 | 413.16 | 15569057.93 | 221645.86 | 555704.41 | 0.457940E+09 | 23.40 | 0.35 |
October | 0.205276E+09 | 104147.05 | 0.00 | 9140800.01 | 168774.07 | 0.188847E+09 | 0.736522E+09 | 0.00 | 0.35 |
November | 97611180.65 | 0.00 | 0.00 | 2821703.17 | 0.00 | 0.753164E+09 | 0.492118E+09 | 0.00 | 0.35 |
December | 75168131.18 | 0.00 | 0.00 | 1117402.61 | 0.00 | 0.121605E+10 | 0.101132E+09 | 0.00 | 0.35 |
Annual Sum or Average | 0.153176E+10 | 0.151097E+09 | 3636.75 | 0.103309E+09 | 10905221.35 | 0.478572E+10 | 0.515006E+10 | 1084.61 | 0.35 |
Minimum of Months | 39787205.84 | 0.00 | 0.00 | 1117402.61 | 0.00 | 6395.35 | 60828842.49 | 0.00 | 0.35 |
Maximum of Months | 0.205276E+09 | 93388357.34 | 2963.63 | 19389194.54 | 7489208.66 | 0.121605E+10 | 0.874647E+09 | 661.31 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.245708E+09 | 0.00 | 0.00 | 4914986.78 | 0.00 | 0.00 | 0.123276E+10 | 0.00 | 0.02 |
February | 73831333.39 | 0.00 | 0.00 | 4838445.69 | 0.00 | 0.00 | 0.126413E+10 | 0.00 | 0.02 |
March | 0.137402E+09 | 0.00 | 0.00 | 4239571.46 | 0.00 | 0.00 | 0.126957E+10 | 0.00 | 0.02 |
April | 0.00 | 0.00 | 0.00 | 3841902.75 | 0.00 | 0.00 | 0.108200E+10 | 0.00 | 0.02 |
May | 72250469.54 | 0.00 | 0.00 | 2891644.40 | 0.00 | 0.00 | 0.698617E+09 | 0.00 | 0.02 |
June | 20377552.20 | 6229363.24 | 0.00 | 2737368.92 | 0.00 | 0.00 | 0.321576E+09 | 0.00 | 0.02 |
July | 0.00 | 69431482.74 | 0.00 | 1013091.09 | 0.00 | 0.00 | 34007498.84 | 0.00 | 0.02 |
August | 0.00 | 50939071.02 | 0.00 | 2596382.30 | 0.00 | 0.00 | 37976165.79 | 0.00 | 0.02 |
September | 0.00 | 14399183.17 | 0.00 | 6217695.11 | 0.00 | 0.00 | 0.236698E+09 | 0.00 | 0.02 |
October | 84415964.69 | 0.00 | 0.00 | 7294115.66 | 0.00 | 0.00 | 0.942420E+09 | 0.00 | 0.02 |
November | 0.117538E+09 | 0.00 | 0.00 | 5690494.95 | 0.00 | 0.00 | 0.137592E+10 | 0.00 | 0.02 |
December | 0.195250E+09 | 0.00 | 0.00 | 5375144.47 | 0.00 | 0.00 | 0.127273E+10 | 0.00 | 0.02 |
Annual Sum or Average | 0.946773E+09 | 0.140999E+09 | 0.00 | 51650843.58 | 0.00 | 0.00 | 0.976841E+10 | 0.00 | 0.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 1013091.09 | 0.00 | 0.00 | 34007498.84 | 0.00 | 0.02 |
Maximum of Months | 0.245708E+09 | 69431482.74 | 0.00 | 7294115.66 | 0.00 | 0.00 | 0.137592E+10 | 0.00 | 0.02 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.117582E+10 | 0.00 | 0.00 | 9487299.70 | 0.00 | 0.926171E+10 | 0.853055E+10 | 0.00 | 0.40 |
February | 0.129994E+10 | 0.00 | 0.00 | 18829364.12 | 0.00 | 0.527624E+10 | 0.103330E+11 | 0.00 | 0.40 |
March | 0.230300E+10 | 0.00 | 0.00 | 51579869.92 | 0.00 | 0.348860E+09 | 0.152873E+11 | 0.00 | 0.40 |
April | 0.284908E+10 | 0.00 | 0.00 | 0.106275E+09 | 0.00 | 20226319.59 | 0.125527E+11 | 0.00 | 0.40 |
May | 0.272305E+10 | 5767367.39 | 0.00 | 0.161474E+09 | 0.00 | 3311831.41 | 0.102545E+11 | 0.00 | 0.40 |
June | 0.165059E+10 | 87081133.81 | 0.00 | 0.175774E+09 | 0.00 | 341660.31 | 0.634692E+10 | 0.00 | 0.40 |
July | 0.539690E+09 | 0.126680E+10 | 0.00 | 67671939.66 | 0.101587E+09 | 0.00 | 0.866801E+09 | 0.00 | 0.40 |
August | 0.115677E+10 | 0.632259E+09 | 0.00 | 0.114611E+09 | 44216202.30 | 0.00 | 0.183675E+10 | 0.00 | 0.40 |
September | 0.268001E+10 | 36067915.63 | 0.00 | 0.151606E+09 | 20043781.95 | 335758.50 | 0.618091E+10 | 0.00 | 0.40 |
October | 0.291833E+10 | 1412692.21 | 0.00 | 88466650.10 | 2289319.02 | 0.326226E+09 | 0.121275E+11 | 0.00 | 0.40 |
November | 0.132404E+10 | 0.00 | 0.00 | 30768537.05 | 0.00 | 0.154201E+10 | 0.153570E+11 | 0.00 | 0.40 |
December | 0.103757E+10 | 0.00 | 0.00 | 7658208.01 | 0.00 | 0.109168E+11 | 0.693954E+10 | 0.00 | 0.40 |
Annual Sum or Average | 0.216579E+11 | 0.202939E+10 | 0.00 | 0.984201E+09 | 0.168136E+09 | 0.276961E+11 | 0.106613E+12 | 0.00 | 0.40 |
Minimum of Months | 0.539690E+09 | 0.00 | 0.00 | 7658208.01 | 0.00 | 0.00 | 0.866801E+09 | 0.00 | 0.40 |
Maximum of Months | 0.291833E+10 | 0.126680E+10 | 0.00 | 0.175774E+09 | 0.101587E+09 | 0.109168E+11 | 0.153570E+11 | 0.00 | 0.40 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 35491021.60 | 0.00 | 0.00 | 4423790.85 | 0.00 | 0.874499E+09 | 0.484822E+09 | 0.00 | 0.35 |
February | 33611778.98 | 0.00 | 0.00 | 5484079.19 | 0.00 | 0.647659E+09 | 0.561362E+09 | 0.00 | 0.35 |
March | 23014048.19 | 0.00 | 0.00 | 9752720.30 | 0.00 | 0.335830E+09 | 0.957881E+09 | 0.00 | 0.35 |
April | 0.00 | 0.00 | 0.00 | 16957338.18 | 0.00 | 56058564.51 | 0.107190E+10 | 0.00 | 0.35 |
May | 1372935.80 | 425233.93 | 0.00 | 21985886.82 | 0.00 | 9343380.01 | 0.936293E+09 | 0.00 | 0.35 |
June | 0.00 | 6420581.61 | 0.00 | 24775171.48 | 0.00 | 229655.05 | 0.577645E+09 | 0.00 | 0.35 |
July | 0.00 | 0.100893E+09 | 0.00 | 11766686.31 | 0.00 | 0.00 | 96924825.84 | 0.00 | 0.35 |
August | 0.00 | 49877192.12 | 0.00 | 18070809.35 | 0.00 | 0.00 | 0.211095E+09 | 0.00 | 0.35 |
September | 0.00 | 4137173.21 | 0.00 | 23872617.37 | 0.00 | 221491.81 | 0.640434E+09 | 0.00 | 0.35 |
October | 7987081.16 | 272953.10 | 0.00 | 17565456.60 | 0.00 | 0.121199E+09 | 0.993168E+09 | 0.00 | 0.35 |
November | 17587768.80 | 0.00 | 0.00 | 7813751.90 | 0.00 | 0.453106E+09 | 0.867365E+09 | 0.00 | 0.35 |
December | 37971797.26 | 0.00 | 0.00 | 4228553.89 | 0.00 | 0.883273E+09 | 0.468158E+09 | 0.00 | 0.35 |
Annual Sum or Average | 0.157036E+09 | 0.162026E+09 | 0.00 | 0.166697E+09 | 0.00 | 0.338142E+10 | 0.786705E+10 | 0.00 | 0.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 4228553.89 | 0.00 | 0.00 | 96924825.84 | 0.00 | 0.35 |
Maximum of Months | 37971797.26 | 0.100893E+09 | 0.00 | 24775171.48 | 0.00 | 0.883273E+09 | 0.107190E+10 | 0.00 | 0.35 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 84709277.46 | 0.00 | 0.00 | 1076088.51 | 0.00 | 0.115179E+10 | 0.161495E+09 | 0.00 | 0.35 |
February | 95834752.09 | 0.00 | 0.00 | 1894313.82 | 0.00 | 0.856418E+09 | 0.293823E+09 | 0.00 | 0.35 |
March | 0.153451E+09 | 0.00 | 0.00 | 5410313.31 | 0.00 | 0.462604E+09 | 0.704858E+09 | 0.00 | 0.35 |
April | 0.151886E+09 | 0.00 | 0.00 | 12925723.65 | 0.00 | 90641041.79 | 0.889330E+09 | 0.00 | 0.35 |
May | 0.161072E+09 | 425184.11 | 0.00 | 19426692.54 | 0.00 | 11288110.06 | 0.777095E+09 | 0.00 | 0.35 |
June | 0.107857E+09 | 6419829.34 | 0.00 | 20318057.45 | 0.00 | 108834.78 | 0.474296E+09 | 0.00 | 0.35 |
July | 39127427.03 | 93760076.30 | 0.00 | 7320193.25 | 7120853.23 | 0.00 | 62231157.08 | 0.00 | 0.36 |
August | 82105291.29 | 47069910.12 | 0.00 | 12298147.11 | 2801438.16 | 18066.32 | 0.134717E+09 | 0.00 | 0.36 |
September | 0.184811E+09 | 3915042.62 | 0.00 | 16761567.12 | 221645.86 | 310903.10 | 0.462566E+09 | 0.00 | 0.35 |
October | 0.186105E+09 | 104147.05 | 0.00 | 10093356.61 | 168774.07 | 0.175136E+09 | 0.768453E+09 | 0.00 | 0.35 |
November | 97150573.27 | 0.00 | 0.00 | 3004217.84 | 0.00 | 0.705662E+09 | 0.539898E+09 | 0.00 | 0.35 |
December | 75537187.56 | 0.00 | 0.00 | 793535.04 | 0.00 | 0.118014E+10 | 0.136994E+09 | 0.00 | 0.35 |
Annual Sum or Average | 0.141965E+10 | 0.151694E+09 | 0.00 | 0.111322E+09 | 10312711.32 | 0.463412E+10 | 0.540576E+10 | 0.00 | 0.35 |
Minimum of Months | 39127427.03 | 0.00 | 0.00 | 793535.04 | 0.00 | 0.00 | 62231157.08 | 0.00 | 0.35 |
Maximum of Months | 0.186105E+09 | 93760076.30 | 0.00 | 20318057.45 | 7120853.23 | 0.118014E+10 | 0.889330E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.292553E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
February | 0.264387E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
March | 0.295184E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
April | 0.243869E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
May | 0.185688E+11 | 0.00 | 0.00 | 834611.20 | 2090071.72 | 0.00 | 0.735334E+09 | 0.00 | 0.60 |
June | 0.707225E+10 | 0.282336E+09 | 0.00 | 15061932.45 | 33008415.14 | 0.00 | 0.414122E+10 | 0.00 | 0.59 |
July | 0.744843E+09 | 0.510771E+09 | 0.00 | 23931233.88 | 28964160.19 | 0.00 | 0.577929E+10 | 0.00 | 0.59 |
August | 0.154212E+10 | 0.211405E+09 | 0.00 | 29095158.36 | 14236375.10 | 0.00 | 0.725506E+10 | 0.00 | 0.62 |
September | 0.629361E+10 | 33673155.98 | 0.00 | 20106007.92 | 0.00 | 0.00 | 0.798371E+10 | 0.00 | 0.63 |
October | 0.213519E+11 | 180949.41 | 0.00 | 6715731.99 | 0.00 | 0.00 | 0.315661E+10 | 0.00 | 0.61 |
November | 0.294402E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
December | 0.296179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
Annual Sum or Average | 0.224231E+12 | 0.103837E+10 | 0.00 | 95744675.80 | 78299022.16 | 0.00 | 0.290512E+11 | 0.00 | 0.60 |
Minimum of Months | 0.744843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
Maximum of Months | 0.296179E+11 | 0.510771E+09 | 0.00 | 29095158.36 | 33008415.14 | 0.00 | 0.798371E+10 | 0.00 | 0.63 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 7419178.85 | 0.00 | 0.00 | 843177.47 | 0.00 | 0.254735E+09 | 86812068.36 | 0.00 | 0.35 |
February | 8140082.18 | 0.00 | 0.00 | 1352554.78 | 0.00 | 0.194754E+09 | 0.107783E+09 | 0.00 | 0.35 |
March | 8760104.46 | 0.00 | 0.00 | 2240106.99 | 0.00 | 0.155810E+09 | 0.164809E+09 | 0.00 | 0.35 |
April | 2960502.20 | 0.00 | 0.00 | 3833674.80 | 0.00 | 48193388.03 | 0.231242E+09 | 0.00 | 0.35 |
May | 2734786.30 | 106308.48 | 0.00 | 4695824.05 | 0.00 | 19859609.71 | 0.214958E+09 | 0.00 | 0.35 |
June | 532546.62 | 1605145.40 | 0.00 | 5656638.94 | 0.00 | 3537901.09 | 0.140935E+09 | 0.00 | 0.35 |
July | 0.00 | 25221852.71 | 1081.82 | 2781412.29 | 0.00 | 43970.99 | 24347494.76 | 253.12 | 0.35 |
August | 0.00 | 12469298.03 | 0.00 | 3957718.29 | 0.00 | 128075.20 | 53205632.53 | 0.00 | 0.35 |
September | 0.00 | 1034293.30 | 0.00 | 4990209.92 | 0.00 | 303249.83 | 0.160838E+09 | 0.00 | 0.35 |
October | 3342621.14 | 68238.27 | 0.00 | 4206616.70 | 0.00 | 59461180.55 | 0.217970E+09 | 0.00 | 0.35 |
November | 4928588.73 | 0.00 | 0.00 | 1470318.05 | 0.00 | 0.165635E+09 | 0.164434E+09 | 0.00 | 0.35 |
December | 8065976.67 | 0.00 | 0.00 | 787333.46 | 0.00 | 0.256385E+09 | 83169935.59 | 0.00 | 0.35 |
Annual Sum or Average | 46884387.14 | 40505136.20 | 1081.82 | 36815585.75 | 0.00 | 0.115885E+10 | 0.165050E+10 | 253.12 | 0.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 787333.46 | 0.00 | 43970.99 | 24347494.76 | 0.00 | 0.35 |
Maximum of Months | 8760104.46 | 25221852.71 | 1081.82 | 5656638.94 | 0.00 | 0.256385E+09 | 0.231242E+09 | 253.12 | 0.35 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 20672784.66 | 0.00 | 0.00 | 296649.32 | 0.00 | 0.304820E+09 | 23978596.79 | 0.00 | 0.35 |
February | 23844634.72 | 0.00 | 0.00 | 518961.03 | 0.00 | 0.244086E+09 | 43543287.10 | 0.00 | 0.35 |
March | 41899249.38 | 0.00 | 0.00 | 1036802.48 | 0.00 | 0.192282E+09 | 96362424.92 | 0.00 | 0.35 |
April | 46694231.26 | 0.00 | 0.00 | 2531819.00 | 0.00 | 50279492.28 | 0.186690E+09 | 0.00 | 0.35 |
May | 44121622.64 | 106296.03 | 0.00 | 3983099.97 | 0.00 | 18190490.58 | 0.175925E+09 | 0.00 | 0.35 |
June | 29107710.20 | 1604957.34 | 0.00 | 4984967.47 | 0.00 | 2767813.56 | 0.113784E+09 | 0.00 | 0.35 |
July | 9946801.46 | 23347930.22 | 0.00 | 2066286.84 | 1872302.17 | 8752.60 | 15147853.44 | 0.00 | 0.36 |
August | 21272234.30 | 11711438.88 | 0.00 | 3087905.27 | 756398.19 | 11897.58 | 32912676.34 | 0.00 | 0.36 |
September | 47596350.71 | 978760.65 | 0.00 | 3696859.60 | 55411.46 | 261989.48 | 0.114557E+09 | 0.00 | 0.35 |
October | 51057086.49 | 26036.76 | 0.00 | 1997682.45 | 42193.52 | 84009234.89 | 0.147883E+09 | 0.00 | 0.35 |
November | 24402795.16 | 0.00 | 0.00 | 550880.77 | 0.00 | 0.247982E+09 | 63493481.29 | 0.00 | 0.35 |
December | 16816048.01 | 0.00 | 0.00 | 219229.66 | 0.00 | 0.312935E+09 | 18396712.88 | 0.00 | 0.35 |
Annual Sum or Average | 0.377432E+09 | 37775419.88 | 0.00 | 24971143.85 | 2726305.34 | 0.145763E+10 | 0.103267E+10 | 0.00 | 0.35 |
Minimum of Months | 9946801.46 | 0.00 | 0.00 | 219229.66 | 0.00 | 8752.60 | 15147853.44 | 0.00 | 0.35 |
Maximum of Months | 51057086.49 | 23347930.22 | 0.00 | 4984967.47 | 1872302.17 | 0.312935E+09 | 0.186690E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 13099476.15 | 0.00 | 0.00 | 16920138.94 | 0.00 | 0.862895E+09 | 0.135443E+10 | 0.00 | 0.40 |
February | 6624157.27 | 0.00 | 0.00 | 17092765.84 | 0.00 | 0.634428E+09 | 0.134648E+10 | 0.00 | 0.40 |
March | 20405525.18 | 0.00 | 0.00 | 18041844.91 | 0.00 | 0.376443E+09 | 0.171560E+10 | 0.00 | 0.40 |
April | 8098017.19 | 0.00 | 0.00 | 20375398.31 | 0.00 | 0.112543E+09 | 0.169786E+10 | 0.00 | 0.40 |
May | 9524430.47 | 682977.72 | 0.00 | 22016035.08 | 0.00 | 47053868.23 | 0.147773E+10 | 0.00 | 0.40 |
June | 2176782.72 | 10312239.53 | 0.00 | 24045763.74 | 0.00 | 402488.48 | 0.941305E+09 | 0.00 | 0.40 |
July | 0.00 | 0.162046E+09 | 0.00 | 13310128.58 | 0.00 | 0.00 | 0.161262E+09 | 0.00 | 0.40 |
August | 0.00 | 80108872.30 | 0.00 | 20967334.55 | 0.00 | 311958.40 | 0.346789E+09 | 0.00 | 0.40 |
September | 0.00 | 6644806.29 | 0.00 | 31067722.56 | 0.00 | 113853.53 | 0.103613E+10 | 0.00 | 0.40 |
October | 3525679.17 | 438396.07 | 0.00 | 33907761.44 | 0.00 | 0.135755E+09 | 0.165766E+10 | 0.00 | 0.40 |
November | 11178933.09 | 0.00 | 0.00 | 22184288.23 | 0.00 | 0.306214E+09 | 0.182206E+10 | 0.00 | 0.40 |
December | 16493164.27 | 0.00 | 0.00 | 17503679.82 | 0.00 | 0.867944E+09 | 0.133640E+10 | 0.00 | 0.40 |
Annual Sum or Average | 91126165.52 | 0.260233E+09 | 0.00 | 0.257433E+09 | 0.00 | 0.334410E+10 | 0.148937E+11 | 0.00 | 0.40 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 13310128.58 | 0.00 | 0.00 | 0.161262E+09 | 0.00 | 0.40 |
Maximum of Months | 20405525.18 | 0.162046E+09 | 0.00 | 33907761.44 | 0.00 | 0.867944E+09 | 0.182206E+10 | 0.00 | 0.40 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.833815E+09 | 0.00 | 0.00 | 58429306.13 | 0.00 | 0.00 | 0.492898E+11 | 0.00 | 4.87 |
February | 0.426757E+09 | 0.00 | 0.00 | 58191542.97 | 0.00 | 0.00 | 0.462236E+11 | 0.00 | 4.99 |
March | 60489552.16 | 0.00 | 0.00 | 76805830.15 | 0.00 | 0.00 | 0.562135E+11 | 0.00 | 5.31 |
April | 0.00 | 0.00 | 0.00 | 93671615.86 | 0.00 | 0.00 | 0.499416E+11 | 0.00 | 5.75 |
May | 1747101.76 | 3917736.88 | 0.00 | 0.108704E+09 | 0.00 | 0.00 | 0.420442E+11 | 0.00 | 6.07 |
June | 0.00 | 0.604409E+09 | 0.00 | 98519824.27 | 0.00 | 0.00 | 0.260160E+11 | 0.00 | 6.05 |
July | 0.00 | 0.102784E+10 | 0.00 | 90474497.30 | 0.00 | 0.00 | 0.155504E+11 | 0.00 | 6.01 |
August | 0.00 | 0.398459E+09 | 0.00 | 0.105125E+09 | 0.00 | 0.00 | 0.203073E+11 | 0.00 | 6.14 |
September | 0.00 | 54878811.14 | 0.00 | 0.107852E+09 | 0.00 | 0.00 | 0.320665E+11 | 0.00 | 6.21 |
October | 0.105794E+09 | 329698.37 | 0.00 | 90950598.30 | 0.00 | 0.00 | 0.490169E+11 | 0.00 | 5.65 |
November | 0.227856E+09 | 0.00 | 0.00 | 66069132.78 | 0.00 | 0.00 | 0.531319E+11 | 0.00 | 5.13 |
December | 0.100807E+10 | 0.00 | 0.00 | 57182987.53 | 0.00 | 0.00 | 0.493382E+11 | 0.00 | 4.84 |
Annual Sum or Average | 0.266453E+10 | 0.208983E+10 | 0.00 | 0.101198E+10 | 0.00 | 0.00 | 0.489140E+12 | 0.00 | 5.59 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 57182987.53 | 0.00 | 0.00 | 0.155504E+11 | 0.00 | 4.84 |
Maximum of Months | 0.100807E+10 | 0.102784E+10 | 0.00 | 0.108704E+09 | 0.00 | 0.00 | 0.562135E+11 | 0.00 | 6.21 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 96869559.55 | 0.00 | 0.00 | 72806700.84 | 0.00 | 0.00 | 0.551981E+11 | 0.00 | 5.38 |
February | 22391070.57 | 0.00 | 0.00 | 70190786.75 | 0.00 | 0.00 | 0.514318E+11 | 0.00 | 5.51 |
March | 0.00 | 0.00 | 0.00 | 88642648.60 | 0.00 | 0.00 | 0.617467E+11 | 0.00 | 5.84 |
April | 0.00 | 0.00 | 0.00 | 0.103477E+09 | 0.00 | 0.00 | 0.541672E+11 | 0.00 | 6.24 |
May | 0.00 | 4239132.46 | 0.00 | 0.117801E+09 | 0.00 | 0.00 | 0.451725E+11 | 0.00 | 6.53 |
June | 0.00 | 0.648500E+09 | 0.00 | 0.105304E+09 | 0.00 | 0.00 | 0.276040E+11 | 0.00 | 6.45 |
July | 0.00 | 0.110219E+10 | 0.00 | 95996746.12 | 0.00 | 0.00 | 0.163424E+11 | 0.00 | 6.37 |
August | 0.00 | 0.428229E+09 | 0.00 | 0.111905E+09 | 0.00 | 0.00 | 0.214096E+11 | 0.00 | 6.51 |
September | 0.00 | 59257766.43 | 0.00 | 0.115515E+09 | 0.00 | 0.00 | 0.340355E+11 | 0.00 | 6.62 |
October | 0.00 | 355223.91 | 0.00 | 0.100889E+09 | 0.00 | 0.00 | 0.530096E+11 | 0.00 | 6.09 |
November | 6032884.04 | 0.00 | 0.00 | 78269310.79 | 0.00 | 0.00 | 0.585210E+11 | 0.00 | 5.62 |
December | 0.181339E+09 | 0.00 | 0.00 | 71905273.40 | 0.00 | 0.00 | 0.553397E+11 | 0.00 | 5.34 |
Annual Sum or Average | 0.306633E+09 | 0.224277E+10 | 0.00 | 0.113270E+10 | 0.00 | 0.00 | 0.533978E+12 | 0.00 | 6.05 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 70190786.75 | 0.00 | 0.00 | 0.163424E+11 | 0.00 | 5.34 |
Maximum of Months | 0.181339E+09 | 0.110219E+10 | 0.00 | 0.117801E+09 | 0.00 | 0.00 | 0.617467E+11 | 0.00 | 6.62 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.118692E+09 | 0.00 | 0.00 | 0.804478E+11 | 0.00 | 24.76 |
February | 0.00 | 0.00 | 0.00 | 0.109800E+09 | 0.00 | 0.00 | 0.730677E+11 | 0.00 | 25.02 |
March | 0.00 | 0.00 | 0.00 | 0.129885E+09 | 0.00 | 0.00 | 0.812852E+11 | 0.00 | 25.62 |
April | 0.00 | 0.00 | 0.00 | 0.146018E+09 | 0.00 | 0.00 | 0.657636E+11 | 0.00 | 26.34 |
May | 0.00 | 7126575.71 | 0.00 | 0.160843E+09 | 0.00 | 0.00 | 0.508753E+11 | 0.00 | 26.65 |
June | 0.00 | 0.101601E+10 | 0.00 | 0.135761E+09 | 0.00 | 0.00 | 0.278051E+11 | 0.00 | 25.43 |
July | 0.00 | 0.173754E+10 | 0.00 | 0.118093E+09 | 0.00 | 0.00 | 0.149052E+11 | 0.00 | 24.82 |
August | 0.00 | 0.705975E+09 | 0.00 | 0.145643E+09 | 0.00 | 0.00 | 0.211308E+11 | 0.00 | 25.66 |
September | 0.00 | 0.103523E+09 | 0.00 | 0.157404E+09 | 0.00 | 0.00 | 0.362184E+11 | 0.00 | 26.78 |
October | 0.00 | 616885.26 | 0.00 | 0.145940E+09 | 0.00 | 0.00 | 0.655538E+11 | 0.00 | 25.93 |
November | 0.00 | 0.00 | 0.00 | 0.119787E+09 | 0.00 | 0.00 | 0.817721E+11 | 0.00 | 25.20 |
December | 0.00 | 0.00 | 0.00 | 0.119962E+09 | 0.00 | 0.00 | 0.811601E+11 | 0.00 | 24.77 |
Annual Sum or Average | 0.00 | 0.357079E+10 | 0.00 | 0.160783E+10 | 0.00 | 0.00 | 0.679985E+12 | 0.00 | 25.58 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.109800E+09 | 0.00 | 0.00 | 0.149052E+11 | 0.00 | 24.76 |
Maximum of Months | 0.00 | 0.173754E+10 | 0.00 | 0.160843E+09 | 0.00 | 0.00 | 0.817721E+11 | 0.00 | 26.78 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.150926E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 75010625.82 | 0.00 | 0.00 | 1.17 |
February | 0.136889E+11 | 0.00 | 0.00 | 157.98 | 0.00 | 12065112.59 | 6379420.88 | 0.00 | 1.17 |
March | 0.152883E+11 | 0.00 | 0.00 | 6024.65 | 0.00 | 0.00 | 15704329.27 | 0.00 | 1.17 |
April | 0.119347E+11 | 0.00 | 0.00 | 1632948.63 | 0.00 | 0.00 | 0.712031E+09 | 0.00 | 1.18 |
May | 0.843481E+10 | 1101082.06 | 0.00 | 6080471.09 | 45414.11 | 0.00 | 0.158988E+10 | 0.00 | 1.20 |
June | 0.337468E+10 | 0.229767E+09 | 0.00 | 10714376.77 | 0.00 | 0.00 | 0.240884E+10 | 0.00 | 1.24 |
July | 0.573224E+09 | 0.377450E+09 | 0.00 | 14739845.05 | 135384.60 | 0.00 | 0.275809E+10 | 0.00 | 1.29 |
August | 0.117547E+10 | 0.161044E+09 | 0.00 | 17948144.30 | 78454.39 | 0.00 | 0.330804E+10 | 0.00 | 1.32 |
September | 0.390657E+10 | 24804000.64 | 0.00 | 14279496.60 | 0.00 | 0.00 | 0.342310E+10 | 0.00 | 1.29 |
October | 0.109349E+11 | 105918.42 | 0.00 | 5553211.06 | 0.00 | 0.00 | 0.173629E+10 | 0.00 | 1.20 |
November | 0.152635E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 |
December | 0.152611E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 94473739.27 | 0.00 | 0.00 | 1.17 |
Annual Sum or Average | 0.114929E+12 | 0.794272E+09 | 0.00 | 70954676.13 | 259253.11 | 0.181549E+09 | 0.159583E+11 | 0.00 | 1.21 |
Minimum of Months | 0.573224E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 |
Maximum of Months | 0.152883E+11 | 0.377450E+09 | 0.00 | 17948144.30 | 135384.60 | 94473739.27 | 0.342310E+10 | 0.00 | 1.32 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:21:37
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.253882E+12 | 0.779459E+10 | 0.207782E+12 | 0.974981E+12 | 0.118638E+12 |
February | 0.323556E+12 | 0.652802E+10 | 0.171879E+12 | 0.813438E+12 | 0.120476E+12 |
March | 0.447532E+12 | 0.578752E+10 | 0.145098E+12 | 0.708091E+12 | 0.163475E+12 |
April | 0.562721E+12 | 0.417049E+10 | 0.986107E+11 | 0.488764E+12 | 0.275336E+12 |
May | 0.609191E+12 | 0.316040E+10 | 0.713221E+11 | 0.368886E+12 | 0.402302E+12 |
June | 0.570310E+12 | 0.166413E+10 | 0.312569E+11 | 0.198274E+12 | 0.634801E+12 |
July | 0.573230E+12 | 0.481873E+09 | 0.118786E+11 | 0.835840E+11 | 0.842198E+12 |
August | 0.546326E+12 | 0.106321E+10 | 0.258452E+11 | 0.145927E+12 | 0.772260E+12 |
September | 0.435011E+12 | 0.227390E+10 | 0.493585E+11 | 0.277773E+12 | 0.540293E+12 |
October | 0.345814E+12 | 0.433869E+10 | 0.106587E+12 | 0.539636E+12 | 0.323331E+12 |
November | 0.272401E+12 | 0.599987E+10 | 0.162361E+12 | 0.787691E+12 | 0.147982E+12 |
December | 0.230205E+12 | 0.795046E+10 | 0.215443E+12 | 0.100317E+13 | 0.127319E+12 |
Annual Sum or Average | 0.517018E+13 | 0.512131E+11 | 0.129742E+13 | 0.639021E+13 | 0.446841E+13 |
Minimum of Months | 0.230205E+12 | 0.481873E+09 | 0.118786E+11 | 0.835840E+11 | 0.118638E+12 |
Maximum of Months | 0.609191E+12 | 0.795046E+10 | 0.215443E+12 | 0.100317E+13 | 0.842198E+12 |