Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745
Simulation Timestamp: 2024-07-03 12:21:26
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:26
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 10218.40 | 900.67 | 900.67 |
Net Site Energy | 10218.40 | 900.67 | 900.67 |
Total Source Energy | 24018.45 | 2117.04 | 2117.04 |
Net Source Energy | 24018.45 | 2117.04 | 2117.04 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 298.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1482.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 783.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 194.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1658.18 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 813.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 585.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 90.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 149.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 94.78 | 2216.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | 61.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 6213.01 | 4005.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 298.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 1482.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 783.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 194.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 872.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 14.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 8.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 21.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 789.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 2.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 585.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 90.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 149.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 94.78 | 2216.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5742.51 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.69 | |
Refrigeration | General | 7.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 20.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 34.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 298.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 1482.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 783.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 194.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 1658.18 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 813.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 585.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 90.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 149.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 94.78 | 2216.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | Unassigned | 61.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 86.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 224.96 | 195.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 236.52 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 547.63 | 353.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 86.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 224.96 | 195.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 236.52 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 547.63 | 353.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 6213.013 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 6213.013 | 100.00 |
Total On-Site and Utility Electric Sources | 6213.013 | 100.00 |
Total Electricity End Uses | 6213.013 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 507.45 | 63.80 |
Air to Air Heat Recovery for Heating | 287.88 | 36.20 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 795.34 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9857.19 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9857.19 | 100.00 |
Total Water End Uses | 9857.19 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 86.83 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 7217.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2B
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AZ_TUCSON
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER1 |DXReportMonthly
| FLR_3_DOAS COOLING COIL | VAV WITH REHEAT COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH LAUNDRY G WATER HEATER | SWH BOOSTER E WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |CoilReportMonthly
| FLR_3_DOAS HEATING COIL | VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | FLR_3_DOAS COOLING COIL | VAV WITH REHEAT COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |PlantLoopDemandReportMonthly
| COOLSYS1 | SWHSYS1 |FanReportMonthly
| FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL_FANCOILFAN | ROOM_2_FLR_3 FAN COIL_FANCOILFAN | ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | ROOM_5_FLR_3 FAN COIL_FANCOILFAN | ROOM_6_FLR_3 FAN COIL_FANCOILFAN | ROOM_1_FLR_6 FAN COIL_FANCOILFAN | ROOM_2_FLR_6 FAN COIL_FANCOILFAN | ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN |PumpReportMonthly
| COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| COOLSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| FLR_3_DOAS | VAV WITH REHEAT |AirLoopSystemComponentLoadsMonthly
| FLR_3_DOAS | VAV WITH REHEAT |AirLoopSystemComponentEnergyUseMonthly
| FLR_3_DOAS | VAV WITH REHEAT |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:26
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21 |
RunPeriod | RUNPERIOD 1 |
Weather File | Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 |
Latitude [deg] | 32.17 |
Longitude [deg] | -110.9 |
Elevation [m] | 809.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 8.8143 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.26 | 23.26 | 11.3140 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 11.3140 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 4.6285 | 61.93 | 5.3800 |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 5.7199 | 46.45 | 2.6900 |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 4.6285 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.50 | 65.50 | 10.0104 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.08 | 85.08 | 10.7639 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 8.2882 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 8.2882 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 7.1042 | 18.58 | 0.0000 |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.74 | 6.74 | 8.2882 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 10.0104 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 10.0104 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.37 | 26.37 | 11.4097 | 4.65 | 2934.4875 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.20 | 28.20 | 7.1042 | 18.58 | 0.0000 |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 8.5566 | 7.07 | 41.0709 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 8.5566 | 7.07 | 41.0709 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 1978.83 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 8.8143 | 18.58 | 5.3800 | |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 1.00 | RETAIL_1_FLR_1 | GENERAL | RETAIL_1_FLR_1 | 11.3140 | 6.19 | 10.7600 | |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 1.00 | RETAIL_2_FLR_1 | GENERAL | RETAIL_2_FLR_1 | 11.3140 | 6.19 | 10.7600 | |
MECH_FLR_1 | 164.24 | Yes | Yes | 1.00 | MECH_FLR_1 | GENERAL | MECH_FLR_1 | 4.6285 | 61.93 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 1.00 | STORAGE_FLR_1 | GENERAL | STORAGE_FLR_1 | 5.7199 | 46.45 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 1.00 | LAUNDRY_FLR_1 | GENERAL | LAUNDRY_FLR_1 | 4.6285 | 9.29 | 597.5300 | |
CAFE_FLR_1 | 188.86 | Yes | Yes | 1.00 | CAFE_FLR_1 | GENERAL | CAFE_FLR_1 | 10.0104 | 1.33 | 5.3800 | |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 1.00 | LOBBY_FLR_1 | GENERAL | LOBBY_FLR_1 | 10.7639 | 3.10 | 8.0700 | |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_1_FLR_3 | GENERAL | ROOM_1_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_2_FLR_3 | GENERAL | ROOM_2_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 76.00 | ROOM_3_MULT19_FLR_3 | GENERAL | ROOM_3_MULT19_FLR_3 | 8.2882 | 16.35 | 10.5200 | |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 76.00 | ROOM_4_MULT19_FLR_3 | GENERAL | ROOM_4_MULT19_FLR_3 | 8.2882 | 16.35 | 10.5200 | |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_5_FLR_3 | GENERAL | ROOM_5_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_6_FLR_3 | GENERAL | ROOM_6_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 4.00 | CORRIDOR_FLR_3 | GENERAL | CORRIDOR_FLR_3 | 7.1042 | 18.58 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_1_FLR_6 | GENERAL | ROOM_1_FLR_6 | 8.2882 | 26.01 | 6.7500 | |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_2_FLR_6 | GENERAL | ROOM_2_FLR_6 | 8.2882 | 26.01 | 6.7500 | |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 9.00 | ROOM_3_MULT9_FLR_6 | GENERAL | ROOM_3_MULT9_FLR_6 | 8.2882 | 16.35 | 10.5200 | |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1.00 | BANQUET_FLR_6 | GENERAL | BANQUET_FLR_6 | 10.0104 | 1.33 | 67.8200 | |
DINING_FLR_6 | 331.66 | Yes | Yes | 1.00 | DINING_FLR_6 | GENERAL | DINING_FLR_6 | 10.0104 | 1.33 | 67.8200 | |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 1.00 | KITCHEN_FLR_6 | GENERAL | KITCHEN_FLR_6 | 11.4097 | 4.65 | 2934.4875 | |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1.00 | CORRIDOR_FLR_6 | GENERAL | CORRIDOR_FLR_6 | 7.1042 | 18.58 | 0.0000 | |
Total | 11345.29 | 8.5566 | 3.54 | 41.0709 | |||||||
Conditioned Total | 11345.29 | 8.5566 | 3.54 | 41.0709 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 11345.29 | 11345.29 | 0.00 | 0.00 | 4.6520 | 8.82 | 37.1989 |
Total | 11345.29 | 11345.29 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:26
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 28-JUN-18:19 | 10-FEB-18:19 | - | - | - | - | - | - | - | - | - | - | 17-JAN-21:19 |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 191833.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 53381.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 77573.37 | 104248.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 28166.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 36465.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 4195.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 4751.04 | 219808.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 2388.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 408694.68 | 324056.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 191833.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 53381.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 47590.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 29272.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1047.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 26968.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 150.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 36465.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 4195.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 4751.04 | 219808.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 228.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 1090.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1069.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:26
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 946.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 4695.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2480.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 614.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5251.45 | 1939.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2577.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1853.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 287.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 474.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 300.17 | 2402.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 195.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 19676.61 | 4341.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 83.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 413.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 218.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 54.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 462.88 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 227.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 163.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 25.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 41.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 26.46 | 211.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1734.34 | 382.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 83.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 413.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 218.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 54.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 462.88 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 227.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 163.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 25.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 41.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 26.46 | 211.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1734.34 | 382.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:26
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
BASEMENT VAV BOX COMPONENT | 2.89 | 0.522181 | 0.476000 | 1.37 | 1.00 | 0.500000 | 0.000730 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.367084 | 0.139228 | 0.476000 | 0.174732 | 0.476000 | 0.500000 | 0.002737 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.266489 | 0.222087 | 0.476000 | 0.126849 | 0.592232 | 0.500000 | 0.001716 |
MECH_FLR_1 VAV BOX COMPONENT | 0.240428 | 0.520544 | 0.476000 | 0.114444 | 1.00 | 0.500000 | 0.000732 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.143801 | 0.502127 | 0.476000 | 0.068449 | 1.00 | 0.500000 | 0.000759 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 3.61 | 0.016455 | 0.476000 | 1.72 | 0.476000 | 0.500000 | 0.023154 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.56 | 0.092414 | 0.476000 | 0.741255 | 0.476000 | 0.500000 | 0.004123 |
LOBBY_FLR_1 VAV BOX COMPONENT | 5.30 | 0.188124 | 0.476000 | 2.52 | 0.501663 | 0.500000 | 0.002025 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.74 | 0.681038 | 0.476000 | 0.829567 | 1.00 | 0.500000 | 0.000559 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.45 | 0.103174 | 0.476000 | 1.17 | 0.476000 | 0.500000 | 0.003693 |
DINING_FLR_6 VAV BOX COMPONENT | 2.56 | 0.098591 | 0.476000 | 1.22 | 0.476000 | 0.500000 | 0.003864 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.49 | 0.056970 | 0.476000 | 1.18 | 0.476000 | 0.500000 | 0.012029 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 0.881937 | 0.356079 | 0.476000 | 0.419802 | 0.949543 | 0.500000 | 0.001070 |
Design Size Nominal Capacity [W] | |
BASEMENT VAV BOX REHEAT COIL | 35700.98 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 4538.41 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 3294.70 |
MECH_FLR_1 VAV BOX REHEAT COIL | 2972.50 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 1777.87 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 44679.09 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 19252.99 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 65511.69 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | 4659.45 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | 4664.00 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 27088.22 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 27188.53 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | 4649.79 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | 4654.33 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 21546.77 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | 1439.14 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | 1439.68 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 6951.57 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 30283.77 |
DINING_FLR_6 VAV BOX REHEAT COIL | 31691.71 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 30726.14 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 10903.73 |
FLR_3_DOAS HEATING COIL | 10951.44 |
VAV WITH REHEAT HEATING COIL | 130085.84 |
Design Size Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 0.061735 |
ROOM_2_FLR_3 DIRECT AIR | 0.061728 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 0.837072 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 0.837300 |
ROOM_5_FLR_3 DIRECT AIR | 0.061735 |
ROOM_6_FLR_3 DIRECT AIR | 0.061728 |
ROOM_1_FLR_6 DIRECT AIR | 0.015434 |
ROOM_2_FLR_6 DIRECT AIR | 0.015432 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 0.099154 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 1.21 | 0.000350 |
ROOM_2_FLR_3 FAN COIL | 1.20 | 0.000348 |
ROOM_3_MULT19_FLR_3 FAN COIL | 7.08 | 0.002021 |
ROOM_4_MULT19_FLR_3 FAN COIL | 7.62 | 0.002284 |
ROOM_5_FLR_3 FAN COIL | 1.07 | 0.000310 |
ROOM_6_FLR_3 FAN COIL | 1.07 | 0.000308 |
ROOM_1_FLR_6 FAN COIL | 0.321429 | 0.000093 |
ROOM_2_FLR_6 FAN COIL | 0.319200 | 0.000092 |
ROOM_3_MULT9_FLR_6 FAN COIL | 1.42 | 0.000418 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COIL_FANCOILFAN | 1.21 |
ROOM_2_FLR_3 FAN COIL_FANCOILFAN | 1.20 |
ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | 7.08 |
ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | 7.62 |
ROOM_5_FLR_3 FAN COIL_FANCOILFAN | 1.07 |
ROOM_6_FLR_3 FAN COIL_FANCOILFAN | 1.07 |
ROOM_1_FLR_6 FAN COIL_FANCOILFAN | 0.321429 |
ROOM_2_FLR_6 FAN COIL_FANCOILFAN | 0.319200 |
ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN | 1.42 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Coil Load [W] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | 21.74 | 6.70 | 0.008544 | 12.80 | 0.008500 | 0.000350 | 1.21 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | 21.74 | 6.70 | 0.008545 | 12.80 | 0.008500 | 0.000348 | 1.20 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 21.74 | 6.70 | 0.008480 | 12.80 | 0.008480 | 0.002021 | 7.08 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 21.74 | 6.70 | 0.008683 | 12.80 | 0.008500 | 0.002284 | 7.62 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | 21.74 | 6.70 | 0.008550 | 12.80 | 0.008500 | 0.000310 | 1.07 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | 21.74 | 6.70 | 0.008550 | 12.80 | 0.008500 | 0.000308 | 1.07 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | 21.74 | 6.70 | 0.008542 | 12.80 | 0.008500 | 0.000093 | 0.321429 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | 21.74 | 6.70 | 0.008542 | 12.80 | 0.008500 | 0.000092 | 0.319200 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 21.74 | 6.70 | 0.008606 | 12.80 | 0.008500 | 0.000418 | 1.42 | |
FLR_3_DOAS COOLING COIL | 40.80 | 6.70 | 0.005631 | 11.84 | 0.005631 | 0.001886 | 2.05 | 65945.86 |
VAV WITH REHEAT COOLING COIL | 32.03 | 6.70 | 0.007709 | 10.79 | 0.007709 | 0.016496 | 24.37 | 576771.07 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
VAV WITH REHEAT | 12.25 | 11.66 | 24.50 | 11.66 | 24.37 | 24.37 | 0.300000 | 0.478574 | 24.37 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
VAV WITH REHEAT_OA_CONTROLLER | 24.37 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
FLR_3_DOAS OA HEAT RECOVERY | 2.05 |
VAV WITH REHEAT OA HEAT RECOVERY | 11.66 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS FAN | 2.05 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.001886 | 0.000252 |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.016496 | 0.000029 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT FAN | 24.37 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP SECONDARY | 0.024606 | 4017.43 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1 | 0.024606 | 2.95 |
SWHSYS1 | 0.000375 | 0.045004 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.024606 | 2781.40 |
SWHSYS1 PUMP | 0.000375 | 47.91 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.024606 | 860358.77 | 861018.80 | 98.16 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000375 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:26
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:26
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:26
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 20.90 | 15.40 | 11.90 | 14.80 | 12.70 | 15.40 | 23.30 | 26.30 | 31.20 | 30.40 | 29.80 | 27.80 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 | 32.17 | -110.88 | -7.00 | 809.00 | 91976 | 1.0932 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 21.66 | 19.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.58 | 23.26 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.72 | 65.50 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.80 | 85.08 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.70 | 6.74 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.96 | 26.37 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.27 | 28.20 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 8.814 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 14.194 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 11.314 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 22.074 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 11.314 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 22.074 | No |
4 | MECH_FLR_1 | 164.24 | 2.7 | 61.932 | 1.615E-002 | 4.628 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 10.008 | No |
5 | STORAGE_FLR_1 | 94.76 | 2.0 | 46.451 | 2.153E-002 | 5.720 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 8.410 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 4.628 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 602.158 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 10.010 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 15.390 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 10.764 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.834 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 8.288 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 18.808 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 8.288 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 18.808 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 21.0 | 18.581 | 5.382E-002 | 7.104 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.104 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 8.288 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 18.808 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 10.010 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 77.830 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 10.010 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 77.830 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 11.410 | 515.227 | 2419.260 | 0.000 | 0.000 | 0.000 | 2945.897 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 22.2 | 18.581 | 5.382E-002 | 7.104 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.104 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | STORAGE_FLR_1 PEOPLE | BLDG_OCC_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.0 | 2.153E-002 | 46.451 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | CORRIDOR_FLR_3 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 21.0 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 21 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
21 | CORRIDOR_FLR_6 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 22.2 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
22 | MECH_FLR_1 PEOPLE | BLDG_OCC_SCH | MECH_FLR_1 | 164.24 | 2.7 | 2.7 | 1.615E-002 | 61.932 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 3 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_BASEMENT | BASEMENT | 1978.83 | 106.5 | 17441.963 | 8.814 | 163.776 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 17441.963 |
2 | RETAIL_1_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_1_FLR_1 | 67.07 | 10.8 | 758.849 | 11.314 | 70.076 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 758.849 |
3 | RETAIL_2_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_2_FLR_1 | 77.67 | 12.5 | 878.750 | 11.314 | 70.076 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 878.750 |
4 | MECH_FLR_1_LIGHTS | LTG_SCH_MECHANIC | MECH_FLR_1 | 164.24 | 2.7 | 760.196 | 4.628 | 286.650 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 760.196 |
5 | STORAGE_FLR_1_LIGHTS | LTG_SCH_STORAGE | STORAGE_FLR_1 | 94.76 | 2.0 | 542.017 | 5.720 | 265.695 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 542.017 |
6 | LAUNDRY_FLR_1_LIGHTS | LTG_SCH_LAUNDRY | LAUNDRY_FLR_1 | 78.04 | 8.4 | 361.204 | 4.628 | 43.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 361.204 |
7 | CAFE_FLR_1_LIGHTS | LTG_SCH_DINING | CAFE_FLR_1 | 188.86 | 142.3 | 1890.589 | 10.010 | 13.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1890.589 |
8 | LOBBY_FLR_1_LIGHTS | LTG_SCH_LOBBY | LOBBY_FLR_1 | 1308.19 | 422.4 | 14081.185 | 10.764 | 33.333 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14081.185 |
9 | ROOM_1_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_3 | 39.02 | 1.5 | 323.422 | 8.288 | 215.615 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.422 |
10 | ROOM_2_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_3 | 39.02 | 1.5 | 323.384 | 8.288 | 215.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.384 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 203.259 | 8.288 | 135.506 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 203.259 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 203.314 | 8.288 | 135.543 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 203.314 |
13 | ROOM_5_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_5_FLR_3 | 39.02 | 1.5 | 323.422 | 8.288 | 215.615 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.422 |
14 | ROOM_6_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_6_FLR_3 | 39.02 | 1.5 | 323.384 | 8.288 | 215.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.384 |
15 | CORRIDOR_FLR_3_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2766.397 | 7.104 | 132.003 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2766.397 |
16 | ROOM_1_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_6 | 39.02 | 1.5 | 323.422 | 8.288 | 215.615 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.422 |
17 | ROOM_2_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_6 | 39.02 | 1.5 | 323.384 | 8.288 | 215.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.384 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 203.314 | 8.288 | 135.543 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 203.314 |
19 | BANQUET_FLR_6_LIGHTS | LTG_SCH_DINING | BANQUET_FLR_6 | 331.66 | 249.9 | 3320.034 | 10.010 | 13.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3320.034 |
20 | DINING_FLR_6_LIGHTS | LTG_SCH_DINING | DINING_FLR_6 | 331.66 | 249.9 | 3320.034 | 10.010 | 13.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3320.034 |
21 | KITCHEN_FLR_6_LIGHTS | LTG_SCH_KITCHEN | KITCHEN_FLR_6 | 103.30 | 22.2 | 1178.676 | 11.410 | 53.003 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1178.676 |
22 | CORRIDOR_FLR_6_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_6 | 412.12 | 22.2 | 2927.804 | 7.104 | 132.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2927.804 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 2.7 | 883.628 | 5.380 | 333.193 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 254.902 | 2.690 | 124.952 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 457.500 | 4.429 | 20.573 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 457.500 | 457.500 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 285.000 | 2.759 | 12.816 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 285.000 | 285.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 2.390 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
6 | RES_ROOF | 19 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
7 | NONRES_EXT_WALL_GRD | 21 | 3 | 9 | 0.167 | 1.173 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | NONRES_EXT_WALL_MID | 22 | 3 | 9 | 0.167 | 1.393 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | NONRES_EXT_WALL_TOP | 23 | 3 | 9 | 0.167 | 1.408 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | RES_EXT_WALL_MID | 25 | 3 | 9 | 0.167 | 1.167 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | RES_EXT_WALL_TOP | 26 | 3 | 9 | 0.167 | 1.181 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | NONRES_FLOOR | 30 | 3 | 7 | 0.167 | 0.2277 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
13 | NONRES_FLOOR_CEILING | 33 | 3 | 7 | 0.167 | 0.2277 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
14 | BASEMENT_FLOOR | 36 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
15 | BASEMENT_WALL_NORTH_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | BASEMENT_WALL_EAST_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | BASEMENT_WALL_SOUTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
18 | BASEMENT_WALL_WEST_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4184 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
10 | RES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
11 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
12 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6855 |
14 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5506 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5431 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | RES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6894 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
25 | RES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6793 |
26 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
27 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.131 |
28 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
29 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
30 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
31 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
32 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.131 |
33 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
34 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
35 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
39 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
40 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
41 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
42 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 2.3900722 | 2.3900722 | 2.3900722 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
21 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
22 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
23 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
24 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
25 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
26 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
27 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
28 | 9 | 0.12938067E-14 | 0.41601190E-16 | -0.13825196E-09 | -0.61617685E-17 |
29 | 8 | 0.20259350E-07 | 0.15574452E-12 | 0.36060849E-03 | -0.23035579E-09 |
30 | 7 | -0.11728067E-01 | 0.82340017E-08 | -0.22346249E-01 | 0.13335239E-03 |
31 | 6 | 0.39139693 | 0.28900057E-05 | 0.46018966 | -0.45832853E-02 |
32 | 5 | -5.0543823 | 0.10873450E-03 | -4.3497742 | 0.61495273E-01 |
33 | 4 | 32.400414 | 0.89561747E-03 | 21.082566 | -0.41412424 |
34 | 3 | -109.94425 | 0.19639160E-02 | -54.916625 | 1.4966738 |
35 | 2 | 195.86041 | 0.11107406E-02 | 77.226367 | -2.8805378 |
36 | 1 | -170.69506 | 0.11917429E-03 | -55.066722 | 2.7373596 |
37 | 0 | 57.057407 | 0.68218560E-06 | 15.590186 | |
38 | 9 | 0.75525440E-15 | 0.44740194E-16 | -0.12773695E-09 | -0.17413973E-17 |
39 | 8 | 0.18775242E-07 | 0.18212309E-12 | 0.34440251E-03 | -0.21348098E-09 |
40 | 7 | -0.11242372E-01 | 0.98045077E-08 | -0.21646224E-01 | 0.12782986E-03 |
41 | 6 | 0.37819669 | 0.34662877E-05 | 0.44889448 | -0.44276875E-02 |
42 | 5 | -4.9255264 | 0.13123097E-03 | -4.2627871 | 0.59897552E-01 |
43 | 4 | 31.830222 | 0.10869568E-02 | 20.742026 | -0.40655401 |
44 | 3 | -108.73045 | 0.23952585E-02 | -54.243141 | 1.4791387 |
45 | 2 | 194.65663 | 0.13606195E-02 | 76.609648 | -2.8614229 |
46 | 1 | -170.25011 | 0.14657319E-03 | -54.889188 | 2.7295613 |
47 | 0 | 57.057407 | 0.84265852E-06 | 15.620975 | |
48 | 9 | 0.85297796E-15 | 0.46957990E-16 | -0.12703153E-09 | -0.54240268E-18 |
49 | 8 | 0.18675511E-07 | 0.18384479E-12 | 0.34329809E-03 | -0.21234699E-09 |
50 | 7 | -0.11209220E-01 | 0.99091673E-08 | -0.21598424E-01 | 0.12745291E-03 |
51 | 6 | 0.37729561 | 0.35050755E-05 | 0.44812211 | -0.44170661E-02 |
52 | 5 | -4.9167295 | 0.13275736E-03 | -4.2568331 | 0.59788477E-01 |
53 | 4 | 31.791289 | 0.11000280E-02 | 20.718704 | -0.40603713 |
54 | 3 | -108.64755 | 0.24248953E-02 | -54.197012 | 1.4779412 |
55 | 2 | 194.57440 | 0.13778728E-02 | 76.567430 | -2.8601173 |
56 | 1 | -170.21971 | 0.14847322E-03 | -54.877080 | 2.7290284 |
57 | 0 | 57.057407 | 0.85387380E-06 | 15.623112 | |
58 | 9 | 0.13788181E-14 | 0.42316407E-16 | -0.13850765E-09 | -0.36591458E-17 |
59 | 8 | 0.20295421E-07 | 0.15509090E-12 | 0.36099725E-03 | -0.23076592E-09 |
60 | 7 | -0.11739701E-01 | 0.81955471E-08 | -0.22363010E-01 | 0.13348467E-03 |
61 | 6 | 0.39171309 | 0.28760220E-05 | 0.46045976 | -0.45870120E-02 |
62 | 5 | -5.0574682 | 0.10819265E-03 | -4.3518524 | 0.61533536E-01 |
63 | 4 | 32.414067 | 0.89103805E-03 | 21.090697 | -0.41430552 |
64 | 3 | -109.97331 | 0.19536482E-02 | -54.932704 | 1.4970936 |
65 | 2 | 195.88922 | 0.11048200E-02 | 77.241099 | -2.8809953 |
66 | 1 | -170.70571 | 0.11852782E-03 | -55.070977 | 2.7375462 |
67 | 0 | 57.057407 | 0.67841551E-06 | 15.589460 | |
68 | 9 | 0.13857471E-14 | 0.43057560E-16 | -0.13784678E-09 | -0.68945926E-17 |
69 | 8 | 0.20202246E-07 | 0.15680163E-12 | 0.35999259E-03 | -0.22970649E-09 |
70 | 7 | -0.11709634E-01 | 0.82948599E-08 | -0.22319691E-01 | 0.13314280E-03 |
71 | 6 | 0.39089600 | 0.29121450E-05 | 0.45976168 | -0.45773805E-02 |
72 | 5 | -5.0494928 | 0.10959277E-03 | -4.3464810 | 0.61434646E-01 |
73 | 4 | 32.378781 | 0.90287364E-03 | 21.069680 | -0.41383702 |
74 | 3 | -109.89821 | 0.19801908E-02 | -54.891143 | 1.4960086 |
75 | 2 | 195.81476 | 0.11201274E-02 | 77.203021 | -2.8798128 |
76 | 1 | -170.67819 | 0.12019965E-03 | -55.059979 | 2.7370639 |
77 | 0 | 57.057407 | 0.68811227E-06 | 15.591337 | |
78 | 7 | -0.14139450E-14 | -0.18802902E-16 | -0.22311785E-13 | 0.54375338E-15 |
79 | 6 | 0.16999971E-10 | 0.27590984E-11 | 0.52267399E-09 | -0.18616555E-10 |
80 | 5 | -0.63950587E-07 | 0.13451749E-07 | -0.21905428E-05 | 0.17144787E-06 |
81 | 4 | 0.72477507E-04 | 0.50724086E-05 | 0.17668371E-02 | -0.28223350E-03 |
82 | 3 | -0.10573811E-01 | 0.17927531E-03 | -0.21549182 | 0.43318087E-01 |
83 | 2 | 0.15010112 | 0.77388015E-03 | 2.8998331 | -0.61891034 |
84 | 1 | -0.37982851 | 0.49528818E-03 | -7.1368477 | 1.5694772 |
85 | 0 | 0.24168561 | 0.34021171E-05 | 4.4521969 | |
86 | 7 | -0.22311785E-13 | -0.18802902E-16 | -0.14139450E-14 | 0.54375338E-15 |
87 | 6 | 0.52267399E-09 | 0.27590984E-11 | 0.16999971E-10 | -0.18616555E-10 |
88 | 5 | -0.21905428E-05 | 0.13451749E-07 | -0.63950587E-07 | 0.17144787E-06 |
89 | 4 | 0.17668371E-02 | 0.50724086E-05 | 0.72477507E-04 | -0.28223350E-03 |
90 | 3 | -0.21549182 | 0.17927531E-03 | -0.10573811E-01 | 0.43318087E-01 |
91 | 2 | 2.8998331 | 0.77388015E-03 | 0.15010112 | -0.61891034 |
92 | 1 | -7.1368477 | 0.49528818E-03 | -0.37982851 | 1.5694772 |
93 | 0 | 4.4521969 | 0.34021171E-05 | 0.24168561 | |
94 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
95 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
96 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
97 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
98 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
99 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
100 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
101 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
102 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
103 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
104 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
105 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
106 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
107 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
108 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
109 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
110 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
111 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
112 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
113 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
114 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
115 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
116 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
117 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
118 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
119 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
120 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
121 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
122 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
123 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
124 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
125 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
126 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
127 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
128 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
129 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
130 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
131 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
132 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
133 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.535_SHGC_0.25 | 37 | 1 | VerySmooth | 3.042 | 3.042 | 1.000 | 0.251 | ||
2 | RESWINDOW_U_0.535_SHGC_0.25 | 38 | 1 | VerySmooth | 3.042 | 3.042 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 1.42074E-002 | 0.16139 | 0.60667 | 0.60667 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 8.94082E-002 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 1.42074E-002 | 0.16139 | 0.60667 | 0.60667 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 8.94082E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | CAFE_FLR_1 | 1 | 0 |
2 | LOBBY_FLR_1 | 1 | 0 |
3 | BANQUET_FLR_6 | 1 | 0 |
4 | DINING_FLR_6 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | CAFE_FLR_1 | 0 | |
2 | LOBBY_FLR_1 | 0 | |
3 | BANQUET_FLR_6 | 0 | |
4 | DINING_FLR_6 | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH LAUNDRY G WATER HEATER | 1.1356 | 163316.0 | 11.511 | 0.4388 |
2 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.219 | 1.1187 |
3 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 2.2712 | 175842.6 | 5.775 | 0.3748 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 1.764E-002 | 2.631E-004 | 1.298E-004 | 0.239 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.811E-003 | 8.769E-005 | 2.388E-004 | 7.967E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 2.7 | 1.610E-002 | 9.800E-005 | 2.563E-004 | 8.904E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 9.287E-003 | 9.800E-005 | 2.127E-004 | 8.904E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 2.198E-002 | 2.816E-004 | 2.506E-004 | 0.256 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 3.900E-002 | 2.065E-004 | 1.137E-004 | 0.188 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 0.111 | 8.519E-005 | 1.629E-004 | 7.740E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 2.563E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 2.563E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 2.857E-003 | 1.165E-004 | 2.563E-004 | 0.138 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 2.858E-003 | 1.165E-004 | 2.563E-004 | 0.138 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 2.563E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 2.563E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 1.238E-002 | 3.180E-005 | 2.563E-004 | 3.755E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 1.297E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 1.297E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 5.239E-003 | 2.136E-004 | 1.165E-004 | 0.252 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 2.500E-002 | 7.539E-005 | 5.825E-005 | 8.904E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 2.500E-002 | 7.539E-005 | 5.825E-005 | 8.904E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 2.238E-002 | 2.167E-004 | 1.174E-004 | 0.256 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 2.191E-002 | 5.316E-005 | 4.403E-005 | 6.278E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 9.6041E-002 |
2 | Clear Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 4.2579E-002 |
3 | Clear Turbid Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1068 |
4 | Clear Turbid Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 4.6408E-002 |
5 | Intermediate Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 7.2226E-002 |
6 | Intermediate Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 2.6724E-002 |
7 | Overcast Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 2.9162E-002 |
8 | Overcast Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 9.6591E-003 |
9 | Clear Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1083 |
10 | Clear Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 5.2112E-002 |
11 | Clear Turbid Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1206 |
12 | Clear Turbid Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 5.6741E-002 |
13 | Intermediate Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 7.9915E-002 |
14 | Intermediate Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 3.3747E-002 |
15 | Overcast Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 3.2764E-002 |
16 | Overcast Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 1.3236E-002 |
17 | Clear Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.3261E-002 |
18 | Clear Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.3285E-002 |
19 | Clear Turbid Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 1.7936E-002 |
20 | Clear Turbid Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.0043E-002 |
21 | Intermediate Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 1.7153E-002 |
22 | Intermediate Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 6.8520E-003 |
23 | Overcast Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.8719E-002 |
24 | Overcast Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.0154E-002 |
25 | Clear Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.3261E-002 |
26 | Clear Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.3285E-002 |
27 | Clear Turbid Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 1.7936E-002 |
28 | Clear Turbid Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.0043E-002 |
29 | Intermediate Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 1.7153E-002 |
30 | Intermediate Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 6.8520E-003 |
31 | Overcast Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.8719E-002 |
32 | Overcast Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.0154E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 36080.40924 | 36080.40924 | 2.88764 | 2.88764 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 21:20:00 | 32.55400 | 5.61839E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 0.85446 | 00:10:00 | 0.50000 | 4.31558E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 | |
3 | RETAIL_1_FLR_1 | Cooling | 4586.25858 | 4586.25858 | 0.36708 | 0.36708 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 40.80000 | 5.63111E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 2175.03667 | 2175.03667 | 0.10269 | 0.10269 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 3329.35033 | 3329.35033 | 0.26649 | 0.26649 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 37.27550 | 5.62563E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 702.31887 | 702.31887 | 3.31592E-002 | 9.17347E-002 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 3004.43988 | 3004.43988 | 0.24043 | 0.24043 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 20:20:00 | 33.75100 | 5.62021E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 1275.10898 | 1275.10898 | 6.02027E-002 | 6.02027E-002 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 1796.95924 | 1796.95924 | 0.14380 | 0.14380 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 37.60800 | 5.62614E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 826.91105 | 826.91105 | 3.90416E-002 | 5.77652E-002 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 45155.09474 | 45155.09474 | 3.61382 | 3.61382 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 39.29267 | 5.62876E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 1717.69289 | 1717.69289 | 8.10980E-002 | 8.10980E-002 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 19438.96056 | 19438.96056 | 1.55726 | 1.55726 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 40.80000 | 5.63111E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 5502.37149 | 5502.37149 | 0.25979 | 0.67639 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 66181.35848 | 66181.35848 | 5.29885 | 5.29885 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 40.80000 | 5.63111E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 12566.04320 | 12566.04320 | 0.59329 | 1.89399 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 11235.68769 | 11235.68769 | 1.21168 | 1.21168 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 39.11533 | 5.62848E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 4659.47955 | 4659.47955 | 0.22128 | 0.22128 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 11165.58750 | 11165.58750 | 1.20412 | 1.20412 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 38.93800 | 5.62821E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 4664.02698 | 4664.02698 | 0.22150 | 0.22150 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 65675.90453 | 65675.90453 | 7.08238 | 7.08238 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 40.80000 | 5.63111E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 27088.30385 | 27088.30385 | 1.28645 | 1.28645 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 70631.21690 | 70631.21690 | 7.61736 | 7.61736 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 40.26800 | 5.63027E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 27188.61668 | 27188.61668 | 1.29122 | 1.29122 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 9938.74771 | 9938.74771 | 1.07182 | 1.07182 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 36.41100 | 5.62429E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 4649.81462 | 4649.81462 | 0.22082 | 0.22082 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 9884.25932 | 9884.25932 | 1.06594 | 1.06594 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 36.07850 | 5.62379E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 4654.36425 | 4654.36425 | 0.22104 | 0.22104 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 21776.39129 | 21776.39129 | 1.74279 | 1.74279 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 40.40100 | 5.63048E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 7795.95667 | 7795.95667 | 0.36808 | 0.47476 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 2980.54698 | 2980.54698 | 0.32143 | 0.32143 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 39.11533 | 5.62848E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 1439.15068 | 1439.15068 | 6.83463E-002 | 6.83463E-002 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 2959.87022 | 2959.87022 | 0.31920 | 0.31920 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 38.93800 | 5.62821E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 1439.69184 | 1439.69184 | 6.83720E-002 | 6.83720E-002 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 13205.56099 | 13205.56099 | 1.42416 | 1.42416 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 40.80000 | 5.63111E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 6951.59975 | 6951.59975 | 0.33014 | 0.33014 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 30567.34651 | 30567.34651 | 2.44947 | 2.44947 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 40.66700 | 5.63090E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 4973.37838 | 4973.37838 | 0.23481 | 1.18780 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 31988.96916 | 31988.96916 | 2.56335 | 2.56335 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 40.66700 | 5.63090E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
40 | DINING_FLR_6 | Heating | 5082.03813 | 5082.03813 | 0.23994 | 1.18780 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | 0.50000 | 4.31558E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 30969.86057 | 30969.86057 | 2.48525 | 2.48525 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 39.60300 | 5.62924E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 1125.66542 | 1125.66542 | 5.31408E-002 | 0.36735 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 0.50000 | 4.31558E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
43 | CORRIDOR_FLR_6 | Cooling | 11020.03356 | 11020.03356 | 0.88194 | 0.88194 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 40.80000 | 5.63111E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 5277.55449 | 5277.55449 | 0.24917 | 0.24917 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | 0.50000 | 4.31558E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | FLR_3_DOAS | Cooling | Sensible | 63092.52 | 20.77171 | 2.05125 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | FLR_3_DOAS | Heating | Sensible | 36503.53 | 3.92917 | 2.05125 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
3 | VAV WITH REHEAT | Cooling | Sensible | 514842.37 | 24.36641 | 24.36641 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | VAV WITH REHEAT | Heating | Sensible | 129645.47 | 7.28518 | 7.28518 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 19:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.88764 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.52218 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.47600 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.37452 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 7.29632E-004 |
8 | Coil:Heating:Electric | BASEMENT VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 35700.97946 |
9 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.36708 |
10 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13923 |
11 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.47600 |
12 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17473 |
13 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.47600 |
14 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.73652E-003 |
16 | Coil:Heating:Electric | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 4538.40668 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.26649 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22209 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.47600 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.12685 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.59223 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.71554E-003 |
24 | Coil:Heating:Electric | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 3294.70482 |
25 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.24043 |
26 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.52054 |
27 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.47600 |
28 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.11444 |
29 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
30 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
31 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 7.31926E-004 |
32 | Coil:Heating:Electric | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 2972.50138 |
33 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.14380 |
34 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.50213 |
35 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.47600 |
36 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 6.84494E-002 |
37 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
38 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 7.58772E-004 |
40 | Coil:Heating:Electric | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 1777.87212 |
41 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.61382 |
42 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 1.64552E-002 |
43 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.47600 |
44 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.72018 |
45 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.47600 |
46 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.31538E-002 |
48 | Coil:Heating:Electric | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 44679.09207 |
49 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.55726 |
50 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.24142E-002 |
51 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.47600 |
52 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.74125 |
53 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.47600 |
54 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
55 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.12274E-003 |
56 | Coil:Heating:Electric | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 19252.98957 |
57 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.29885 |
58 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18812 |
59 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.47600 |
60 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.52225 |
61 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.50166 |
62 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.02526E-003 |
64 | Coil:Heating:Electric | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 65511.68619 |
65 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
66 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.21168 |
67 | Fan:OnOff | ROOM_1_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 1.21168 |
68 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.49986E-004 |
69 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.74133 |
70 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
71 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.54437E-003 |
72 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
73 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
74 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.49986E-004 |
75 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.21168 |
76 | Coil:Heating:Electric | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Nominal Capacity [W] | 4659.45003 |
77 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
78 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.20412 |
79 | Fan:OnOff | ROOM_2_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 1.20412 |
80 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.47835E-004 |
81 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.74133 |
82 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
83 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.54471E-003 |
84 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
85 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
86 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.47835E-004 |
87 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.20412 |
88 | Coil:Heating:Electric | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Nominal Capacity [W] | 4663.99744 |
89 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83707 |
90 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 7.08238 |
91 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 7.08238 |
92 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.02074E-003 |
93 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.74172 |
94 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
95 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.47980E-003 |
96 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
97 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.47980E-003 |
98 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.02074E-003 |
99 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 7.08238 |
100 | Coil:Heating:Electric | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Nominal Capacity [W] | 27088.22017 |
101 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83730 |
102 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 7.61736 |
103 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 7.61736 |
104 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.28430E-003 |
105 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.74083 |
106 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
107 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.68349E-003 |
108 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
109 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
110 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.28430E-003 |
111 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 7.61736 |
112 | Coil:Heating:Electric | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Nominal Capacity [W] | 27188.53272 |
113 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
114 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.07182 |
115 | Fan:OnOff | ROOM_5_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 1.07182 |
116 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.10049E-004 |
117 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.74132 |
118 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
119 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.54980E-003 |
120 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
121 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
122 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.10049E-004 |
123 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.07182 |
124 | Coil:Heating:Electric | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Nominal Capacity [W] | 4649.78515 |
125 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
126 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.06594 |
127 | Fan:OnOff | ROOM_6_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 1.06594 |
128 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.08370E-004 |
129 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.74132 |
130 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
131 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.55004E-003 |
132 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
133 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
134 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.08370E-004 |
135 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.06594 |
136 | Coil:Heating:Electric | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Nominal Capacity [W] | 4654.33476 |
137 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.74279 |
138 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.68104 |
139 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.47600 |
140 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.82957 |
141 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
142 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
143 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.59440E-004 |
144 | Coil:Heating:Electric | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 21546.77473 |
145 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54338E-002 |
146 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.32143 |
147 | Fan:OnOff | ROOM_1_FLR_6 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 0.32143 |
148 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 9.27786E-005 |
149 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.74133 |
150 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
151 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.54186E-003 |
152 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
153 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
154 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 9.27786E-005 |
155 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.32143 |
156 | Coil:Heating:Electric | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Nominal Capacity [W] | 1439.14196 |
157 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54319E-002 |
158 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.31920 |
159 | Fan:OnOff | ROOM_2_FLR_6 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 0.31920 |
160 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 9.21437E-005 |
161 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.74133 |
162 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
163 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.54221E-003 |
164 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
165 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
166 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 9.21437E-005 |
167 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.31920 |
168 | Coil:Heating:Electric | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Nominal Capacity [W] | 1439.68312 |
169 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 9.91540E-002 |
170 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.42416 |
171 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 1.42416 |
172 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.18330E-004 |
173 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.74101 |
174 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
175 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.60610E-003 |
176 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
177 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
178 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.18330E-004 |
179 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.42416 |
180 | Coil:Heating:Electric | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Nominal Capacity [W] | 6951.56606 |
181 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.44947 |
182 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10317 |
183 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.47600 |
184 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.16595 |
185 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.47600 |
186 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
187 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.69277E-003 |
188 | Coil:Heating:Electric | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 30283.77158 |
189 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.56335 |
190 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.85909E-002 |
191 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.47600 |
192 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.22016 |
193 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.47600 |
194 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
195 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.86446E-003 |
196 | Coil:Heating:Electric | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 31691.70584 |
197 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.48525 |
198 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 5.69698E-002 |
199 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.47600 |
200 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.18298 |
201 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.47600 |
202 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
203 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.20288E-002 |
204 | Coil:Heating:Electric | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 30726.13612 |
205 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.88194 |
206 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.35608 |
207 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.47600 |
208 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.41980 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.94954 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.06999E-003 |
212 | Coil:Heating:Electric | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10903.72975 |
213 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05132 |
214 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05132 |
215 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05132 |
216 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05132 |
217 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05132 |
218 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05132 |
219 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
220 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
221 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 12.24908 |
222 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 11.66113 |
223 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 24.49816 |
224 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 11.66113 |
225 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 24.36641 |
226 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 24.36641 |
227 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
228 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.47857 |
229 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05132 |
230 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 24.36641 |
231 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05132 |
232 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05125 |
233 | HeatExchanger:AirToAir:SensibleAndLatent | FLR_3_DOAS OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.05125 |
234 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 40.80000 |
235 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
236 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.83593 |
237 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 5.63111E-003 |
238 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 5.63111E-003 |
239 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Coil Load [W] | 65945.85541 |
240 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.88604E-003 |
241 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 2.05132 |
242 | Coil:Heating:Electric | FLR_3_DOAS HEATING COIL | Design Size Nominal Capacity [W] | 10951.44367 |
243 | Fan:ConstantVolume | FLR_3_DOAS FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05125 |
244 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.88604E-003 |
245 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 2.52481E-004 |
246 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 24.36641 |
247 | HeatExchanger:AirToAir:SensibleAndLatent | VAV WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 11.66146 |
248 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 32.03448 |
249 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
250 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.78893 |
251 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.70854E-003 |
252 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.70854E-003 |
253 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 576771.07200 |
254 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.64956E-002 |
255 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 24.36641 |
256 | Coil:Heating:Electric | VAV WITH REHEAT HEATING COIL | Design Size Nominal Capacity [W] | 130085.83979 |
257 | Fan:VariableVolume | VAV WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 24.36641 |
258 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.64956E-002 |
259 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 2.88678E-005 |
260 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 2.46062E-002 |
261 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 4017.43273 |
262 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 2.46062E-002 |
263 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 2.95274 |
264 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 2.46062E-002 |
265 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 2781.40418 |
266 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 2.46062E-002 |
267 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 860358.77189 |
268 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 861018.80000 |
269 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 98.15614 |
270 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
271 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
272 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
273 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
274 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | 19645.13 | 16154.35 | 3490.78 | 0.82 | 11088.08 | 112.46 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | 19524.26 | 16054.15 | 3470.10 | 0.82 | 11019.62 | 111.77 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 113988.87 | 94132.97 | 19855.89 | 0.83 | 81030.93 | 821.86 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 126970.25 | 102756.73 | 24213.52 | 0.81 | 56072.77 | 568.72 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | 17401.64 | 14298.06 | 3103.58 | 0.82 | 9818.40 | 99.58 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | 17307.32 | 14220.05 | 3087.27 | 0.82 | 9765.03 | 99.04 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | 5208.01 | 4284.18 | 923.83 | 0.82 | 2939.97 | 29.82 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | 5172.34 | 4254.62 | 917.72 | 0.82 | 2919.77 | 29.61 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 23386.74 | 19090.06 | 4296.68 | 0.82 | 11758.28 | 119.26 |
10 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | 52598.14 | 33952.87 | 18645.27 | 0.65 | 5719.18 | 58.01 |
11 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | 678955.95 | 431120.68 | 247835.27 | 0.63 | 141559.94 | 1435.78 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 4.09 | 13.95 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.940 | 0.824 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.173 | 0.998 | 22.63 | 45.89 | 22.63 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.535_SHGC_0.25 | N/A | 3.042 | No | 23.26 | 23.26 | 23.26 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.173 | 0.998 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.173 | 0.998 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.173 | 0.998 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.173 | 0.998 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 2.390 | 2.390 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.173 | 0.998 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.173 | 0.998 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.173 | 0.998 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.173 | 0.998 | 63.73 | 129.23 | 63.73 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.535_SHGC_0.25 | N/A | 3.042 | No | 65.50 | 65.50 | 65.50 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.173 | 0.998 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.173 | 0.998 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.173 | 0.998 | 82.79 | 167.88 | 82.79 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.535_SHGC_0.25 | N/A | 3.042 | No | 85.08 | 85.08 | 85.08 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.173 | 0.998 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.167 | 0.994 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.535_SHGC_0.25 | N/A | 3.042 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.167 | 0.994 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.535_SHGC_0.25 | N/A | 3.042 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.167 | 0.994 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.535_SHGC_0.25 | N/A | 3.042 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.167 | 0.994 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.535_SHGC_0.25 | N/A | 3.042 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.167 | 0.994 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.535_SHGC_0.25 | N/A | 3.042 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.167 | 0.994 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.535_SHGC_0.25 | N/A | 3.042 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.167 | 0.994 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.535_SHGC_0.25 | N/A | 3.042 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.167 | 0.994 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.535_SHGC_0.25 | N/A | 3.042 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.167 | 0.994 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.535_SHGC_0.25 | N/A | 3.042 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.167 | 0.994 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.535_SHGC_0.25 | N/A | 3.042 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.393 | 1.153 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.535_SHGC_0.25 | N/A | 3.042 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.393 | 1.153 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.535_SHGC_0.25 | N/A | 3.042 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.393 | 1.153 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.535_SHGC_0.25 | N/A | 3.042 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.393 | 1.153 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.535_SHGC_0.25 | N/A | 3.042 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.181 | 1.004 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.535_SHGC_0.25 | N/A | 3.042 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.181 | 1.004 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.535_SHGC_0.25 | N/A | 3.042 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.181 | 1.004 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.535_SHGC_0.25 | N/A | 3.042 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.181 | 1.004 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.535_SHGC_0.25 | N/A | 3.042 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.181 | 1.004 | 13.70 | 20.44 | 13.70 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.535_SHGC_0.25 | N/A | 3.042 | No | 6.74 | 6.74 | 6.74 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.408 | 1.163 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.535_SHGC_0.25 | N/A | 3.042 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.408 | 1.163 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.535_SHGC_0.25 | N/A | 3.042 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.408 | 1.163 | 16.77 | 21.37 | 16.77 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.535_SHGC_0.25 | N/A | 3.042 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.408 | 1.163 | 34.86 | 52.03 | 34.86 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.535_SHGC_0.25 | N/A | 3.042 | No | 17.17 | 17.17 | 17.17 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.408 | 1.163 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.535_SHGC_0.25 | N/A | 3.042 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.408 | 1.163 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.535_SHGC_0.25 | N/A | 3.042 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.408 | 1.163 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.535_SHGC_0.25 | N/A | 3.042 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.408 | 1.163 | 34.86 | 52.03 | 34.86 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.535_SHGC_0.25 | N/A | 3.042 | No | 17.17 | 17.17 | 17.17 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 1.4137209363E-002 | 2.3394814382E-002 | Pass | Pass | 1.4546253396E-002 | 3.5185309467E-002 | Pass | Pass |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.6689235029E-002 | 6.6976751166E-002 | Pass | Pass | 3.1007186370E-002 | 3.3247300782E-002 | Pass | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.7752347768E-002 | 2.9598241144E-002 | Pass | Pass | 1.3910011972E-002 | 3.7413253804E-002 | Pass | Pass |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 8.8452969130E-003 | 1.3979571805E-002 | Pass | Pass | 1.7071843022E-002 | 3.9786476615E-002 | Pass | Pass |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 3.4832820803E-003 | 7.5542898361E-003 | Pass | Pass | 1.8413214192E-002 | 2.2895252883E-002 | Pass | Pass |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 6.0240007180E-002 | 0.1823277044 | Pass | Pass | 2.0600664034E-002 | 5.2504520780E-002 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 5.0049048076E-002 | 6.4925678887E-002 | Pass | Pass | 2.1736933807E-002 | 3.6379082119E-002 | Pass | Pass |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 3.5329342775E-002 | 4.1271283368E-002 | Pass | Pass | 1.4120549432E-002 | 3.4092163859E-002 | Pass | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 5.4998444452E-002 | 0.1952255936 | Pass | Pass | 0.1900554776 | 0.5244033779 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 6.4530141353E-002 | 0.2028123915 | Pass | Pass | 0.4012662159 | 2.5141214595 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 1.7927139739E-002 | 3.7487885303E-002 | Pass | Pass | 9.1005072471E-002 | 0.3951422763 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 2.2107552787E-002 | 6.5696505700E-002 | Pass | Pass | 0.6776863430 | 4.2614265082 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 6.7373797294E-002 | 0.2269809460 | Pass | Pass | 0.2403371359 | 0.7247634558 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 2.7979927725E-002 | 7.4225702041E-002 | Pass | Pass | 0.2297298966 | 1.1490033657 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 1.3754286249E-002 | 1.0149121649E-002 | Pass | Pass | 1.6986487503E-002 | 4.9746263280E-002 | Pass | Pass |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 5.9806678639E-002 | 0.2021201610 | Pass | Pass | 0.2703250655 | 1.1164021548 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 8.0166411604E-002 | 0.2257193357 | Pass | Pass | 0.1907581887 | 0.7429980294 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 8.9403368607E-002 | 0.2867117802 | Pass | Pass | 0.9521140479 | 3.9881797487 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 3.4185792878E-002 | 7.3910901370E-002 | Pass | Pass | 1.2357619445E-002 | 3.8481825842E-002 | Pass | Pass |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 2.1409169170E-002 | 5.2085588521E-002 | Pass | Pass | 1.4206741551E-002 | 4.1254219697E-002 | Pass | Pass |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 2.1777012956E-002 | 6.2184853874E-002 | Pass | Pass | 2.1622273209E-002 | 4.3651220898E-002 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 1.3574432538E-002 | 1.7414998874E-002 | Pass | Pass | 2.7747551353E-002 | 3.3868075991E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:26
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 2729.06 | 22.05 | 498.15 | 2484.08 | 7195.84 | 12929.18 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:26
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 0.50 | 0.00 | 0.50 | Wetbulb [C] | 2.10 | 140.00 |
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 40.80 | 13.30 | 18.50 | Wetbulb [C] | 4.80 | 310.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 3.00 | 2 | |||
Feb | 34.00 | 28 | |||
Mar | 40.00 | 18 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 81.00 | 18 | |||
Aug | 71.00 | 20 | |||
Sep | 27.00 | 12 | |||
Oct | 9.00 | 6 | |||
Nov | 35.00 | 14 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:26
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 211.13 | 211.13 | 0.00 | 90.00 | N |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 55.76 | 55.76 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 211.13 | 211.13 | 180.00 | 90.00 | S |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 55.76 | 55.76 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.998 | 1.173 | 45.89 | 22.63 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.998 | 1.173 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.998 | 1.173 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.998 | 1.173 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.998 | 1.173 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.998 | 1.173 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.998 | 1.173 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.998 | 1.173 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.998 | 1.173 | 129.23 | 63.73 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.998 | 1.173 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.998 | 1.173 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.998 | 1.173 | 167.88 | 82.79 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.998 | 1.173 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 104.06 | 69.72 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 847.14 | 567.58 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 847.37 | 567.71 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 104.06 | 69.72 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.153 | 1.393 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.153 | 1.393 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.153 | 1.393 | 26.02 | 17.43 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.153 | 1.393 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 13.94 | 9.34 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | RES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 13.94 | 9.34 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 183.96 | 123.26 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.163 | 1.408 | 97.55 | 65.36 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.163 | 1.408 | 97.55 | 65.36 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.163 | 1.408 | 21.37 | 16.77 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.163 | 1.408 | 52.03 | 34.86 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.163 | 1.408 | 13.94 | 9.34 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.163 | 1.408 | 17.65 | 11.83 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.163 | 1.408 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.163 | 1.408 | 52.03 | 34.86 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 167.42 | 167.42 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_FLOOR | BASEMENT_FLOOR | 0.30 | 1.441 | 2.705 | 1978.83 | 1978.83 | 0.00 | 180.00 | |
BASEMENT_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 67.07 | 67.07 | 180.00 | 0.00 | |
BASEMENT_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 77.67 | 77.67 | 180.00 | 0.00 | |
BASEMENT_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 164.24 | 164.24 | 180.00 | 0.00 | |
BASEMENT_CEILING_4 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 94.76 | 94.76 | 180.00 | 0.00 | |
BASEMENT_CEILING_5 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 78.04 | 78.04 | 180.00 | 0.00 | |
BASEMENT_CEILING_6 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 188.86 | 188.86 | 180.00 | 0.00 | |
BASEMENT_CEILING_7 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 1088.56 | 1088.56 | 180.00 | 0.00 | |
BASEMENT_CEILING_8 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 219.63 | 219.63 | 90.00 | 0.00 | |
RETAIL_1_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_1_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
RETAIL_1_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 67.07 | 67.07 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
RETAIL_2_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_2_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 90.00 | 90.00 | E |
RETAIL_2_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 77.67 | 77.67 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 77.67 | 77.67 | 180.00 | 0.00 | |
MECH_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
MECH_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 180.00 | 90.00 | S |
MECH_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
MECH_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 164.24 | 164.24 | 0.00 | 180.00 | |
MECH_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 164.24 | 164.24 | 180.00 | 0.00 | |
STORAGE_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
STORAGE_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 180.00 | 90.00 | S |
STORAGE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
STORAGE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 94.76 | 94.76 | 0.00 | 180.00 | |
STORAGE_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 94.76 | 94.76 | 180.00 | 0.00 | |
LAUNDRY_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 180.00 | 90.00 | S |
LAUNDRY_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 270.00 | 90.00 | W |
LAUNDRY_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 78.04 | 78.04 | 0.00 | 180.00 | |
LAUNDRY_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 78.04 | 78.04 | 180.00 | 0.00 | |
CAFE_FLR_1_WALL_1_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_2_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
CAFE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 188.86 | 188.86 | 0.00 | 180.00 | |
LOBBY_FLR_1_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 90.00 | 90.00 | E |
LOBBY_FLR_1_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 1088.56 | 1088.56 | 180.00 | 180.00 | |
LOBBY_FLR_1_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 219.63 | 219.63 | 90.00 | 180.00 | |
LOBBY_FLR_1_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 1062.83 | 1062.83 | 270.00 | 0.00 | |
ROOM_1_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_1_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
ROOM_1_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_1_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_2_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
ROOM_2_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_2_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_2_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 156.07 | 156.07 | 180.00 | 0.00 | |
ROOM_3_MULT19_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.14 | 847.14 | 0.00 | 90.00 | N |
ROOM_3_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_3_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 1863.81 | 1863.81 | 0.00 | 180.00 | |
ROOM_3_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 1863.81 | 1863.81 | 180.00 | 0.00 | |
ROOM_4_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_4_MULT19_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.37 | 847.37 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_4_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 1864.32 | 1864.32 | 0.00 | 180.00 | |
ROOM_4_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 1864.32 | 1864.32 | 180.00 | 0.00 | |
ROOM_5_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
ROOM_5_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_5_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_6_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
ROOM_6_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_6_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 156.07 | 156.07 | 180.00 | 0.00 | |
CORRIDOR_FLR_3_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.28 | 847.28 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_4_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.27 | 847.27 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 297.29 | 297.29 | 180.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 963.06 | 963.06 | 270.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_3 | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 297.26 | 297.26 | 90.00 | 180.00 | |
CORRIDOR_FLR_3_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 297.29 | 297.29 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 963.06 | 963.06 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 297.26 | 297.26 | 90.00 | 0.00 | |
ROOM_1_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 0.00 | 90.00 | N |
ROOM_1_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_1_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_2_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_2_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 180.00 | 90.00 | S |
ROOM_2_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_3_MULT9_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.96 | 183.96 | 0.00 | 90.00 | N |
ROOM_3_MULT9_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 90.00 | 90.00 | E |
ROOM_3_MULT9_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 270.00 | 90.00 | W |
ROOM_3_MULT9_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 220.77 | 220.77 | 0.00 | 180.00 | |
BANQUET_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
BANQUET_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
BANQUET_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
BANQUET_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 331.66 | 331.66 | 0.00 | 180.00 | |
DINING_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
DINING_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
DINING_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
DINING_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 331.66 | 331.66 | 0.00 | 180.00 | |
KITCHEN_FLR_6_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 7.43 | 7.43 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 103.30 | 103.30 | 180.00 | 180.00 | |
CORRIDOR_FLR_6_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 104.98 | 104.98 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_1_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.95 | 183.95 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 11.15 | 11.15 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 40.88 | 40.88 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 412.12 | 412.12 | 180.00 | 180.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3957.66 | 0.00 | 90.00 | N | ||
RETAIL_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 134.14 | 0.00 | 90.00 | N | ||
RETAIL_2_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 155.34 | 0.00 | 90.00 | N | ||
MECH_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 328.49 | 0.00 | 90.00 | N | ||
STORAGE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 189.52 | 0.00 | 90.00 | N | ||
LAUNDRY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 156.08 | 0.00 | 90.00 | N | ||
CAFE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 377.72 | 0.00 | 90.00 | N | ||
LOBBY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 2616.37 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3727.63 | 0.00 | 90.00 | N | ||
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3728.64 | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3115.24 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.04 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.03 | 0.00 | 90.00 | N | ||
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 441.55 | 0.00 | 90.00 | N | ||
BANQUET_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
DINING_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 206.61 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 824.25 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.535_SHGC_0.25 | 23.26 | 0.00 | 0.00 | 23.26 | 23.26 | 3.042 | 0.251 | 0.276 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.535_SHGC_0.25 | 65.50 | 0.00 | 0.00 | 65.50 | 65.50 | 3.042 | 0.251 | 0.276 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.535_SHGC_0.25 | 85.08 | 0.00 | 0.00 | 85.08 | 85.08 | 3.042 | 0.251 | 0.276 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.535_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 3.042 | 0.251 | 0.276 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.535_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 3.042 | 0.251 | 0.276 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.535_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 3.042 | 0.251 | 0.276 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.535_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 3.042 | 0.251 | 0.276 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.535_SHGC_0.25 | 3.68 | 0.00 | 0.00 | 3.68 | 279.56 | 3.042 | 0.251 | 0.276 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.535_SHGC_0.25 | 3.68 | 0.00 | 0.00 | 3.68 | 279.65 | 3.042 | 0.251 | 0.276 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.535_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 3.042 | 0.251 | 0.276 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.535_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 3.042 | 0.251 | 0.276 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.535_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 3.042 | 0.251 | 0.276 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.535_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 3.042 | 0.251 | 0.276 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.535_SHGC_0.25 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 3.042 | 0.251 | 0.276 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.535_SHGC_0.25 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 3.042 | 0.251 | 0.276 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.535_SHGC_0.25 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 3.042 | 0.251 | 0.276 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.535_SHGC_0.25 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 3.042 | 0.251 | 0.276 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.535_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 3.042 | 0.251 | 0.276 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.535_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 3.042 | 0.251 | 0.276 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.535_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 3.042 | 0.251 | 0.276 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.535_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 3.042 | 0.251 | 0.276 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.535_SHGC_0.25 | 6.74 | 0.00 | 0.00 | 6.74 | 60.70 | 3.042 | 0.251 | 0.276 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.535_SHGC_0.25 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 3.042 | 0.251 | 0.276 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.535_SHGC_0.25 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 3.042 | 0.251 | 0.276 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.535_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 3.042 | 0.251 | 0.276 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.535_SHGC_0.25 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 3.042 | 0.251 | 0.276 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | |||||||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.535_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 3.042 | 0.251 | 0.276 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.535_SHGC_0.25 | 5.82 | 0.00 | 0.00 | 5.82 | 5.82 | 3.042 | 0.251 | 0.276 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.535_SHGC_0.25 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 3.042 | 0.251 | 0.276 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.535_SHGC_0.25 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 3.042 | 0.251 | 0.276 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 1213.79 | 3.042 | 0.251 | 0.276 | |||||||||||||||||
North Total or Average | 432.95 | 3.042 | 0.251 | 0.276 | |||||||||||||||||
Non-North Total or Average | 780.84 | 3.042 | 0.251 | 0.276 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 1.760 | 2.390 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:26
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:26
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 8.8143 | 1978.83 | 17441.96 | LightsWired | LTG_SCH_BASEMENT | 49.32 | 168.00 | 49.26 | 0.0000 | Y | 161.29 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | RETAIL_1_FLR_1 | GENERAL | 11.3140 | 67.07 | 758.85 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 7.31 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | RETAIL_2_FLR_1 | GENERAL | 11.3140 | 77.67 | 878.75 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 8.46 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | MECH_FLR_1 | GENERAL | 4.6285 | 164.24 | 760.20 | LightsWired | LTG_SCH_MECHANIC | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 8.37 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | STORAGE_FLR_1 | GENERAL | 5.7199 | 94.76 | 542.02 | LightsWired | LTG_SCH_STORAGE | 30.30 | 168.00 | 30.27 | 0.0000 | Y | 3.08 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | LAUNDRY_FLR_1 | GENERAL | 4.6285 | 78.04 | 361.20 | LightsWired | LTG_SCH_LAUNDRY | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 3.98 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | CAFE_FLR_1 | GENERAL | 10.0104 | 188.86 | 1890.59 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 40.03 | 0.0000 | Y | 14.21 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | LOBBY_FLR_1 | GENERAL | 10.7639 | 1308.19 | 14081.18 | LightsWired | LTG_SCH_LOBBY | 44.02 | 168.00 | 41.68 | 0.0000 | Y | 110.18 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | ROOM_1_FLR_3 | GENERAL | 8.2882 | 156.09 | 1293.69 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | ROOM_2_FLR_3 | GENERAL | 8.2882 | 156.07 | 1293.54 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | GENERAL | 8.2882 | 1863.81 | 15447.65 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 110.38 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | GENERAL | 8.2882 | 1864.32 | 15451.87 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 110.41 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | ROOM_5_FLR_3 | GENERAL | 8.2882 | 156.09 | 1293.69 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | ROOM_6_FLR_3 | GENERAL | 8.2882 | 156.07 | 1293.54 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | CORRIDOR_FLR_3 | GENERAL | 7.1042 | 1557.62 | 11065.59 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 91.33 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | ROOM_1_FLR_6 | GENERAL | 8.2882 | 39.02 | 323.42 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 2.31 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | ROOM_2_FLR_6 | GENERAL | 8.2882 | 39.02 | 323.38 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 2.31 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | GENERAL | 8.2882 | 220.77 | 1829.83 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 13.08 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | BANQUET_FLR_6 | GENERAL | 10.0104 | 331.66 | 3320.03 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 50.08 | 0.0000 | Y | 31.21 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | DINING_FLR_6 | GENERAL | 10.0104 | 331.66 | 3320.03 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 50.08 | 0.0000 | Y | 31.21 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | KITCHEN_FLR_6 | GENERAL | 11.4097 | 103.30 | 1178.68 | LightsWired | LTG_SCH_KITCHEN | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 12.97 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | CORRIDOR_FLR_6 | GENERAL | 7.1042 | 412.12 | 2927.80 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 24.17 |
Interior Lighting Total | 8.5566 | 11345.29 | 97077.49 | 457.48 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
LOBBY_FLR_1_DAYLREFPT1 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.07 | 14081.18 | 985.68 |
LOBBY_FLR_1_DAYLREFPT2 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.07 | 14081.18 | 985.68 |
CAFE_FLR_1_DAYLREFPT1 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1890.59 | 737.33 |
CAFE_FLR_1_DAYLREFPT2 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1890.59 | 737.33 |
DINING_FLR_6_DAYLREFPT1 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
DINING_FLR_6_DAYLREFPT2 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
BANQUET_FLR_6_DAYLREFPT1 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
BANQUET_FLR_6_DAYLREFPT2 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 12338.45 | AstronomicalClock | - | 83.79 | 83.79 | 194.06 | |
Exterior Lighting Total | 12338.45 | 194.06 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:26
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 861018.80 | 2.96 | 861018.80 | 2.96 | 4.09 | 13.95 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 12237.57 | 19645.13 | 16154.35 | 3490.78 | 0.82 | - | 11088.08 | 112.46 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 12162.35 | 19524.26 | 16054.15 | 3470.10 | 0.82 | - | 11019.62 | 111.77 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 70656.91 | 113988.87 | 94132.97 | 19855.89 | 0.83 | - | 81030.93 | 821.86 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 79872.31 | 126970.25 | 102756.73 | 24213.52 | 0.81 | - | 56072.77 | 568.72 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 10841.13 | 17401.64 | 14298.06 | 3103.58 | 0.82 | - | 9818.40 | 99.58 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 10782.42 | 17307.32 | 14220.05 | 3087.27 | 0.82 | - | 9765.03 | 99.04 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3244.08 | 5208.01 | 4284.18 | 923.83 | 0.82 | - | 2939.97 | 29.82 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3221.88 | 5172.34 | 4254.62 | 917.72 | 0.82 | - | 2919.77 | 29.61 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 14627.24 | 23386.74 | 19090.06 | 4296.68 | 0.82 | - | 11758.28 | 119.26 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | 65945.86 | 52598.14 | 33952.87 | 18645.27 | 0.65 | - | 5719.18 | 58.01 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | 576771.07 | 678955.95 | 431120.68 | 247835.27 | 0.63 | - | 141559.94 | 1435.78 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Electric | 35700.98 | 1.00 | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4538.41 | 1.00 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 3294.70 | 1.00 | |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 2972.50 | 1.00 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 1777.87 | 1.00 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 44679.09 | 1.00 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 19252.99 | 1.00 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 65511.69 | 1.00 | |
ROOM_1_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Electric | 4659.45 | 1.00 | |
ROOM_2_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Electric | 4664.00 | 1.00 | |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Electric | 27088.22 | 1.00 | |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Electric | 27188.53 | 1.00 | |
ROOM_5_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Electric | 4649.79 | 1.00 | |
ROOM_6_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Electric | 4654.33 | 1.00 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 21546.77 | 1.00 | |
ROOM_1_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Electric | 1439.14 | 1.00 | |
ROOM_2_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Electric | 1439.68 | 1.00 | |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Electric | 6951.57 | 1.00 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Electric | 30283.77 | 1.00 | |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Electric | 31691.71 | 1.00 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Electric | 30726.14 | 1.00 | |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10903.73 | 1.00 | |
FLR_3_DOAS HEATING COIL | Coil:Heating:Electric | 10951.44 | 1.00 | |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Electric | 130085.84 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 0.24 | 76.61 | 324.68 | 1.00 | 2.78 | General | ||
LOBBY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.24 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
ROOM_1_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 1.21 | 852.59 | 703.64 | 1.00 | 1.15 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 |
ROOM_2_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 1.20 | 847.27 | 703.64 | 1.00 | 1.15 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 7.08 | 4983.42 | 703.64 | 1.00 | 0.95 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 |
ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 7.62 | 5359.85 | 703.64 | 1.00 | 0.95 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 |
ROOM_5_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 1.07 | 754.17 | 703.64 | 1.00 | 1.18 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 |
ROOM_6_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 1.07 | 750.04 | 703.64 | 1.00 | 1.18 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 |
ROOM_1_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 0.32 | 226.17 | 703.64 | 1.00 | 1.67 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 |
ROOM_2_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 0.32 | 224.60 | 703.64 | 1.00 | 1.67 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 1.42 | 1002.09 | 703.64 | 1.00 | 1.12 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 |
BANQUET_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
DINING_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 1.89 | 612.92 | 324.68 | 1.00 | 1.48 | General | ||
FLR_3_DOAS FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.93 | 1070.05 | 1.00 | 1.30 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
VAV WITH REHEAT FAN | Fan:VariableVolume | 0.62 | 1389.42 | 24.37 | 54596.31 | 2240.64 | 1.00 | 1.11 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.024606 | 4017.43 | 163269.44 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.024606 | 2781.40 | 113036.94 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH LAUNDRY G WATER HEATER | WaterHeater:Mixed | 1.14 | 163316.00 | 0.80 | 11.51 | 0.44 |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.22 | 1.12 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.60 | 0.80 | 5.78 | 0.37 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:26
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 36080.41 | 36080.41 | 18.23 | 2.888 | 2.888 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 21:20:00 | 24.00 | 24.00 | 0.00917 | 32.55 | 0.00562 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 4586.26 | 4586.26 | 68.38 | 0.367 | 0.367 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00900 | 40.80 | 0.00563 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 3329.35 | 3329.35 | 42.87 | 0.266 | 0.266 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 24.00 | 24.00 | 0.00933 | 37.28 | 0.00563 | 0.092 | 0.00 |
MECH_FLR_1 | 3004.44 | 3004.44 | 18.29 | 0.240 | 0.240 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 20:20:00 | 24.00 | 24.00 | 0.00865 | 33.75 | 0.00562 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1796.96 | 1796.96 | 18.96 | 0.144 | 0.144 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 24.00 | 24.00 | 0.00871 | 37.61 | 0.00563 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 45155.09 | 45155.09 | 578.62 | 3.614 | 3.614 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 24.00 | 24.00 | 0.00854 | 39.29 | 0.00563 | 0.000 | 0.00 |
CAFE_FLR_1 | 19438.96 | 19438.96 | 102.93 | 1.557 | 1.557 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 23.99 | 0.01013 | 40.80 | 0.00563 | 0.676 | 0.00 |
LOBBY_FLR_1 | 66181.36 | 66181.36 | 50.59 | 5.299 | 5.299 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 24.00 | 23.99 | 0.00992 | 40.80 | 0.00563 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 11235.69 | 11235.69 | 287.93 | 1.212 | 1.212 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 21.11 | 21.11 | 0.00854 | 39.12 | 0.00563 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 11165.59 | 11165.59 | 286.17 | 1.204 | 1.204 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 21.11 | 21.11 | 0.00854 | 38.94 | 0.00563 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 65675.90 | 65675.90 | 2678.04 | 7.082 | 7.082 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 21.11 | 21.11 | 0.00848 | 40.80 | 0.00563 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 70631.22 | 70631.22 | 2879.32 | 7.617 | 7.617 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 21.11 | 21.11 | 0.00868 | 40.27 | 0.00563 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 9938.75 | 9938.75 | 254.70 | 1.072 | 1.072 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 21.11 | 21.11 | 0.00855 | 36.41 | 0.00562 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 9884.26 | 9884.26 | 253.33 | 1.066 | 1.066 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 21.11 | 21.11 | 0.00855 | 36.08 | 0.00562 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 21776.39 | 21776.39 | 55.92 | 1.743 | 1.743 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 24.00 | 24.00 | 0.00935 | 40.40 | 0.00563 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 2980.55 | 2980.55 | 76.38 | 0.321 | 0.321 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 21.11 | 21.11 | 0.00854 | 39.12 | 0.00563 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2959.87 | 2959.87 | 75.86 | 0.319 | 0.319 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 21.11 | 21.11 | 0.00854 | 38.94 | 0.00563 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 13205.56 | 13205.56 | 538.33 | 1.424 | 1.424 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 21.11 | 21.11 | 0.00861 | 40.80 | 0.00563 | 0.099 | 0.00 |
BANQUET_FLR_6 | 30567.35 | 30567.35 | 92.17 | 2.449 | 2.449 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 23.98 | 0.01034 | 40.67 | 0.00563 | 1.188 | 0.00 |
DINING_FLR_6 | 31988.97 | 31988.97 | 96.45 | 2.563 | 2.563 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 23.98 | 0.01025 | 40.67 | 0.00563 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 30969.86 | 30969.86 | 299.79 | 2.485 | 2.485 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 24.00 | 23.97 | 0.01006 | 39.60 | 0.00563 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 11020.03 | 11020.03 | 26.74 | 0.882 | 0.882 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00894 | 40.80 | 0.00563 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 0.854 | 00:10:00 | 21.00 | 24.00 | 0.00846 | 0.50 | 0.00432 | 0.854 | 0.00 | |
RETAIL_1_FLR_1 | 2175.04 | 2175.04 | 32.43 | 0.103 | 0.103 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00784 | 0.50 | 0.00432 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 702.32 | 702.32 | 9.04 | 0.033 | 0.092 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00781 | 0.50 | 0.00432 | 0.092 | 0.00 |
MECH_FLR_1 | 1275.11 | 1275.11 | 7.76 | 0.060 | 0.060 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00776 | 0.50 | 0.00432 | 0.000 | 0.00 |
STORAGE_FLR_1 | 826.91 | 826.91 | 8.73 | 0.039 | 0.058 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00778 | 0.50 | 0.00432 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 1717.69 | 1717.69 | 22.01 | 0.081 | 0.081 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00775 | 0.50 | 0.00432 | 0.000 | 0.00 |
CAFE_FLR_1 | 5502.37 | 5502.37 | 29.13 | 0.260 | 0.676 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00786 | 0.50 | 0.00432 | 0.676 | 0.00 |
LOBBY_FLR_1 | 12566.04 | 12566.04 | 9.61 | 0.593 | 1.894 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00782 | 0.50 | 0.00432 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 4659.48 | 4659.48 | 119.41 | 0.221 | 0.221 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00783 | 0.50 | 0.00432 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 4664.03 | 4664.03 | 119.54 | 0.221 | 0.221 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00783 | 0.50 | 0.00432 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 27088.30 | 27088.30 | 1104.57 | 1.286 | 1.286 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00784 | 0.50 | 0.00432 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 27188.62 | 27188.62 | 1108.36 | 1.291 | 1.291 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00784 | 0.50 | 0.00432 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 4649.81 | 4649.81 | 119.16 | 0.221 | 0.221 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00783 | 0.50 | 0.00432 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 4654.36 | 4654.36 | 119.29 | 0.221 | 0.221 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00783 | 0.50 | 0.00432 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 7795.96 | 7795.96 | 20.02 | 0.368 | 0.475 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00787 | 0.50 | 0.00432 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 1439.15 | 1439.15 | 36.88 | 0.068 | 0.068 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00786 | 0.50 | 0.00432 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 1439.69 | 1439.69 | 36.90 | 0.068 | 0.068 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00786 | 0.50 | 0.00432 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 6951.60 | 6951.60 | 283.39 | 0.330 | 0.330 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00787 | 0.50 | 0.00432 | 0.099 | 0.00 |
BANQUET_FLR_6 | 4973.38 | 4973.38 | 15.00 | 0.235 | 1.188 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00790 | 0.50 | 0.00432 | 1.188 | 0.00 |
DINING_FLR_6 | 5082.04 | 5082.04 | 15.32 | 0.240 | 1.188 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | 21.00 | 21.00 | 0.00790 | 0.50 | 0.00432 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 1125.67 | 1125.67 | 10.90 | 0.053 | 0.367 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 21.00 | 21.00 | 0.00603 | 0.50 | 0.00432 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 5277.55 | 5277.55 | 12.81 | 0.249 | 0.249 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | 21.00 | 21.00 | 0.00792 | 0.50 | 0.00432 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
FLR_3_DOAS | 20.77 | 2.05 | 3.93 | 2.05 | 2.0513 | 2.0513 | 2.0513 | 1.0000 | 0.3000 |
VAV WITH REHEAT | 24.37 | 24.37 | 7.29 | 7.29 | 24.3664 | 11.6611 | 24.3664 | 0.4786 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 35700.979 | 35700.979 | -999.0 | -999.0 | -999.000 | 12/21 00:10:00 | 12/21 00:10:00 | 35700.98 | 22193.29 | 0.854459 | 16.70 | 12.29 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00800000 | 46.9512 | 0.00 | 0.00 | -999.00 | -999.00 | ||
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 4538.407 | 4538.407 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 4538.41 | 2667.24 | 0.102691 | 16.70 | 12.29 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00783898 | 46.0185 | 2175.04 | 0.00 | -999.00 | -999.00 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 3294.705 | 3294.705 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3294.70 | 2382.67 | 0.091735 | 16.70 | 12.29 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00780913 | 45.8451 | 702.32 | 0.00 | -999.00 | -999.00 |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 2972.501 | 2972.501 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 2972.50 | 1563.68 | 0.060203 | 16.70 | 12.29 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00775534 | 45.5333 | 1275.11 | 0.00 | -999.00 | -999.00 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 1777.872 | 1777.872 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1777.87 | 1500.36 | 0.057765 | 16.70 | 12.29 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00778074 | 45.6805 | 826.91 | 0.00 | -999.00 | -999.00 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Unknown | Unknown | 44679.092 | 44679.092 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 44679.09 | 2106.40 | 0.081098 | 16.70 | 12.29 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00775226 | 45.5157 | 1717.69 | 0.00 | -999.00 | -999.00 |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 19252.990 | 19252.990 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 19252.99 | 17568.20 | 0.676389 | 16.70 | 12.29 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00785852 | 46.1317 | 5502.37 | 0.00 | -999.00 | -999.00 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Unknown | Unknown | 65511.686 | 65511.686 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 65511.69 | 49193.58 | 1.893991 | 16.70 | 12.29 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00782467 | 45.9352 | 12566.04 | 0.00 | -999.00 | -999.00 |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 12237.572 | -999.000 | 1.211684 | 0.00034999 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | 7/21 16:50:00 | 12237.57 | 12122.08 | 1.211684 | 21.74 | 14.65 | 0.00854437 | 12.80 | 11.23 | 0.00850000 | 39.12 | 0.00562848 | 18.06 | 0.0000 | 21.11 | 0.00854437 | 49.7630 | 11235.69 | 0.00 | 13554.45 | 13554.45 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 4659.450 | 4659.450 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 4659.45 | 4615.48 | 0.221282 | 21.74 | 14.65 | 0.00854437 | 12.80 | 11.23 | 0.00850000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.11 | 0.00782709 | 45.6374 | 4659.48 | 0.00 | -999.00 | -999.00 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 12162.353 | -999.000 | 1.204125 | 0.00034784 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | 7/21 17:00:00 | 12162.35 | 12046.70 | 1.204125 | 21.74 | 14.65 | 0.00854471 | 12.80 | 11.23 | 0.00850000 | 38.94 | 0.00562821 | 18.00 | 0.0000 | 21.11 | 0.00854471 | 49.7650 | 11165.59 | 0.00 | 13471.41 | 13471.41 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 4663.997 | 4663.997 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 4664.00 | 4619.65 | 0.221498 | 21.74 | 14.65 | 0.00854471 | 12.80 | 11.23 | 0.00850000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.11 | 0.00782727 | 45.6384 | 4664.03 | 0.00 | -999.00 | -999.00 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 70656.905 | -999.000 | 7.082380 | 0.00202074 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | unknown | 7/21 14:20:00 | 70656.91 | 70656.91 | 7.082380 | 21.74 | 14.59 | 0.00847980 | 12.80 | 11.21 | 0.00847980 | 40.80 | 0.00563111 | 18.58 | 0.0000 | 21.11 | 0.00847980 | 49.3911 | 65675.90 | 0.00 | 78397.43 | 78397.43 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 27088.220 | 27088.220 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 27088.22 | 27088.22 | 1.286455 | 21.74 | 14.59 | 0.00847980 | 12.80 | 11.21 | 0.00847980 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.11 | 0.00784168 | 45.7210 | 27088.30 | 0.00 | -999.00 | -999.00 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 79872.310 | -999.000 | 7.617357 | 0.00228430 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | unknown | 7/21 15:40:00 | 79872.31 | 76844.56 | 7.617357 | 21.74 | 14.77 | 0.00868349 | 12.80 | 11.23 | 0.00850000 | 40.27 | 0.00563027 | 18.42 | 0.0000 | 21.11 | 0.00868349 | 50.5632 | 70631.22 | 0.00 | 88327.24 | 85416.46 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 27188.533 | 27188.533 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 27188.53 | 26157.89 | 1.291219 | 21.74 | 14.77 | 0.00868349 | 12.80 | 11.23 | 0.00850000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.11 | 0.00784219 | 45.7240 | 27188.62 | 0.00 | -999.00 | -999.00 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 10841.135 | -999.000 | 1.071819 | 0.00031005 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | unknown | 7/21 10:20:00 | 10841.13 | 10726.44 | 1.071819 | 21.74 | 14.65 | 0.00854980 | 12.80 | 11.23 | 0.00850000 | 36.41 | 0.00562429 | 17.20 | 0.0000 | 21.11 | 0.00854980 | 49.7942 | 9938.75 | 0.00 | 12011.69 | 12011.69 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 4649.785 | 4649.785 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 4649.79 | 4600.59 | 0.220823 | 21.74 | 14.65 | 0.00854980 | 12.80 | 11.23 | 0.00850000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.11 | 0.00782675 | 45.6354 | 4649.81 | 0.00 | -999.00 | -999.00 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 10782.424 | -999.000 | 1.065943 | 0.00030837 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | unknown | 7/21 10:10:00 | 10782.42 | 10667.79 | 1.065943 | 21.74 | 14.65 | 0.00855004 | 12.80 | 11.23 | 0.00850000 | 36.08 | 0.00562379 | 17.09 | 0.0000 | 21.11 | 0.00855004 | 49.7956 | 9884.26 | 0.00 | 11946.82 | 11946.82 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 4654.335 | 4654.335 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 4654.33 | 4604.85 | 0.221039 | 21.74 | 14.65 | 0.00855004 | 12.80 | 11.23 | 0.00850000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.11 | 0.00782693 | 45.6364 | 4654.36 | 0.00 | -999.00 | -999.00 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 21546.775 | 21546.775 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21546.77 | 12331.24 | 0.474762 | 16.70 | 12.29 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00787261 | 46.2130 | 7795.96 | 0.00 | -999.00 | -999.00 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 3244.082 | -999.000 | 0.321429 | 0.00009278 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | 7/21 16:50:00 | 3244.08 | 3215.18 | 0.321429 | 21.74 | 14.65 | 0.00854186 | 12.80 | 11.23 | 0.00850000 | 39.12 | 0.00562848 | 18.06 | 0.0000 | 21.11 | 0.00854186 | 49.7486 | 2980.55 | 0.00 | 3592.63 | 3592.63 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 1439.142 | 1439.142 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1439.14 | 1426.32 | 0.068346 | 21.74 | 14.65 | 0.00854186 | 12.80 | 11.23 | 0.00850000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.11 | 0.00785876 | 45.8197 | 1439.15 | 0.00 | -999.00 | -999.00 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 3221.883 | -999.000 | 0.319200 | 0.00009214 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | 7/21 17:00:00 | 3221.88 | 3192.95 | 0.319200 | 21.74 | 14.65 | 0.00854221 | 12.80 | 11.23 | 0.00850000 | 38.94 | 0.00562821 | 18.00 | 0.0000 | 21.11 | 0.00854221 | 49.7506 | 2959.87 | 0.00 | 3568.12 | 3568.12 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 1439.683 | 1439.683 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1439.68 | 1426.75 | 0.068372 | 21.74 | 14.65 | 0.00854221 | 12.80 | 11.23 | 0.00850000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.11 | 0.00785882 | 45.8200 | 1439.69 | 0.00 | -999.00 | -999.00 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 14627.245 | -999.000 | 1.424163 | 0.00041833 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | unknown | 7/21 14:20:00 | 14627.24 | 14301.43 | 1.424163 | 21.74 | 14.70 | 0.00860610 | 12.80 | 11.23 | 0.00850000 | 40.80 | 0.00563111 | 18.58 | 0.0000 | 21.11 | 0.00860610 | 50.1184 | 13205.56 | 0.00 | 16195.05 | 16195.05 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 6951.566 | 6951.566 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 6951.57 | 6796.72 | 0.330138 | 21.74 | 14.70 | 0.00860610 | 12.80 | 11.23 | 0.00850000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.11 | 0.00786511 | 45.8562 | 6951.60 | 0.00 | -999.00 | -999.00 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Electric | Unknown | Unknown | 30283.772 | 30283.772 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 30283.77 | 30283.77 | 1.187797 | 16.70 | 12.29 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00789849 | 46.3631 | 4973.38 | 0.00 | -999.00 | -999.00 |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Electric | Unknown | Unknown | 31691.706 | 31691.706 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | 31691.71 | 30851.25 | 1.187797 | 16.70 | 12.29 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00790059 | 46.3754 | 5082.04 | 0.00 | -999.00 | -999.00 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Electric | Unknown | Unknown | 30726.136 | 30726.136 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 30726.14 | 9541.38 | 0.367350 | 16.70 | 12.29 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00602609 | 35.4839 | 1125.67 | 0.00 | -999.00 | -999.00 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 10903.730 | 10903.730 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | 10903.73 | 6471.91 | 0.249174 | 16.70 | 12.29 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00791577 | 46.4633 | 5277.55 | 0.00 | -999.00 | -999.00 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 65945.855 | -999.000 | 2.051317 | 0.00188604 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 65945.86 | 65945.86 | 2.051317 | 40.80 | 18.58 | 0.00563111 | 11.84 | 7.85 | 0.00563111 | 40.80 | 0.00563111 | 18.58 | 99.9965 | 21.11 | 0.00858538 | 49.9987 | 192046.61 | 0.00 | 65994.93 | 65994.93 |
FLR_3_DOAS HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | FLR_3_DOAS | 10951.444 | 10951.444 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 10951.44 | 10951.44 | 0.615395 | 0.50 | 0.50 | 0.00431558 | 16.70 | 12.29 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 333.3216 | 21.11 | 0.00784203 | 45.7230 | 82735.05 | 0.00 | -999.00 | -999.00 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 576771.072 | -999.000 | 24.366406 | 0.01649558 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 576771.07 | 576771.07 | 24.366406 | 32.03 | 17.43 | 0.00770854 | 10.79 | 9.61 | 0.00770854 | 40.80 | 0.00563111 | 18.58 | 47.8588 | 23.99 | 0.00956939 | 46.7075 | 304253.14 | 0.00 | 616784.76 | 603506.26 |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | VAV WITH REHEAT | 130085.840 | 130085.840 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 19:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 19:10:00 | 130085.84 | 130085.84 | 7.309922 | 0.50 | 0.50 | 0.00431558 | 16.70 | 12.29 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 159.5292 | 21.63 | 0.00798185 | 45.0773 | 48533.85 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:26
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | No | unknown | No | 35700.979 | 35700.979 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | 12/21 00:10:00 | unknown | unknown | 12/21 00:10:00 | Sensible | 35700.98 | 22193.29 | 1.0000 | 0.93408950 | 0.854459 | 16.70 | 12.29 | 0.00800000 | 37036.7 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 35700.98 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 46.9512 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |||
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | No | unknown | No | 4538.407 | 4538.407 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 4538.41 | 2667.24 | 1.0000 | 0.11226104 | 0.102691 | 16.70 | 12.29 | 0.00800000 | 37036.7 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4538.41 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.00 | 0.00783898 | 21.00 | 0.00783898 | 46.0185 | 2175.04 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | No | unknown | No | 3294.705 | 3294.705 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 3294.70 | 2382.67 | 1.0000 | 0.10028379 | 0.091735 | 16.70 | 12.29 | 0.00800000 | 37036.7 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 3294.70 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.00 | 0.00780913 | 21.00 | 0.00780913 | 45.8451 | 702.32 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | No | unknown | No | 2972.501 | 2972.501 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 2972.50 | 1563.68 | 1.0000 | 0.06581328 | 0.060203 | 16.70 | 12.29 | 0.00800000 | 37036.7 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 2972.50 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.00 | 0.00775534 | 21.00 | 0.00775534 | 45.5333 | 1275.11 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | No | unknown | No | 1777.872 | 1777.872 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1777.87 | 1500.36 | 1.0000 | 0.06314854 | 0.057765 | 16.70 | 12.29 | 0.00800000 | 37036.7 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 1777.87 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.00 | 0.00778074 | 21.00 | 0.00778074 | 45.6805 | 826.91 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | No | unknown | No | 44679.092 | 44679.092 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 44679.09 | 2106.40 | 1.0000 | 0.08865588 | 0.081098 | 16.70 | 12.29 | 0.00800000 | 37036.7 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 44679.09 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.00 | 0.00775226 | 21.00 | 0.00775226 | 45.5157 | 1717.69 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | No | unknown | No | 19252.990 | 19252.990 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 19252.99 | 17568.20 | 1.0000 | 0.73942496 | 0.676389 | 16.70 | 12.29 | 0.00800000 | 37036.7 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19252.99 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.00 | 0.00785852 | 21.00 | 0.00785852 | 46.1317 | 5502.37 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | No | unknown | No | 65511.686 | 65511.686 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 65511.69 | 49193.58 | 1.0000 | 2.07049952 | 1.893991 | 16.70 | 12.29 | 0.00800000 | 37036.7 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 65511.69 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.00 | 0.00782467 | 21.00 | 0.00782467 | 45.9352 | 12566.04 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12237.572 | -999.000 | 1.211684 | 0.00034999 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7236 | 1004.8586 | 1.0932 | ROOM_1_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.211684 | 1.32460630 | 4197.9300 | 999.8980 | 24.60364188 | 15.03 | 6.70 | 8.33 | 860358.77 | 1.4224 | 1.422354 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | unknown | unknown | 7/21 16:50:00 | Sensible | 12237.57 | 12122.08 | 1.0000 | 1.32460630 | 1.211684 | 21.74 | 14.65 | 0.00854437 | 43560.8 | 12.80 | 11.23 | 0.00850000 | 34322.2 | 0.34995077 | 6.70 | 15.03 | 8.33 | 0.000 | 12237.57 | 39.12 | 0.00562848 | 18.06 | 0.00000000 | 0.0000 | 21.11 | 0.00854437 | 21.11 | 0.00854437 | 49.7630 | 11235.69 | 0.00 | 13554.45 | 13554.45 | 1.32460630 | 21.74 | 15.61 | 0.00854437 | 43560.8 | 11.72 | 11.69 | 0.00854437 | 33328.0 | |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | No | unknown | No | 4659.450 | 4659.450 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6411 | 1004.8586 | 1.0932 | ROOM_1_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.211684 | 1.32460630 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 4659.45 | 4615.48 | 1.0000 | 0.24190418 | 0.221282 | 21.74 | 14.65 | 0.00854437 | 43560.8 | 12.80 | 11.23 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4659.45 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.11 | 0.00782709 | 21.11 | 0.00782709 | 45.6374 | 4659.48 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12162.353 | -999.000 | 1.204125 | 0.00034784 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7242 | 1004.8586 | 1.0932 | ROOM_2_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.204125 | 1.31634197 | 4197.9300 | 999.8980 | 24.60364188 | 15.03 | 6.70 | 8.33 | 860358.77 | 1.4136 | 1.413611 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | unknown | unknown | 7/21 17:00:00 | Sensible | 12162.35 | 12046.70 | 1.0000 | 1.31634197 | 1.204125 | 21.74 | 14.65 | 0.00854471 | 43561.7 | 12.80 | 11.23 | 0.00850000 | 34322.2 | 0.34779977 | 6.70 | 15.03 | 8.33 | 0.000 | 12162.35 | 38.94 | 0.00562821 | 18.00 | 0.00000000 | 0.0000 | 21.11 | 0.00854471 | 21.11 | 0.00854471 | 49.7650 | 11165.59 | 0.00 | 13471.41 | 13471.41 | 1.31634197 | 21.74 | 15.61 | 0.00854471 | 43561.7 | 11.72 | 11.69 | 0.00854471 | 33327.7 | |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | No | unknown | No | 4663.997 | 4663.997 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6411 | 1004.8586 | 1.0932 | ROOM_2_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.204125 | 1.31634197 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 4664.00 | 4619.65 | 1.0000 | 0.24214027 | 0.221498 | 21.74 | 14.65 | 0.00854471 | 43561.7 | 12.80 | 11.23 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4664.00 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.11 | 0.00782727 | 21.11 | 0.00782727 | 45.6384 | 4664.03 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 70656.905 | -999.000 | 7.082380 | 0.00202074 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6035 | 1004.8586 | 1.0932 | ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 7.082380 | 7.74241650 | 4197.9300 | 999.8980 | 24.60364188 | 15.03 | 6.70 | 8.33 | 860358.77 | 8.2125 | 8.212340 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | unknown | unknown | unknown | 7/21 14:20:00 | Sensible | 70656.91 | 70656.91 | 1.0000 | 7.74241650 | 7.082380 | 21.74 | 14.59 | 0.00847980 | 43397.1 | 12.80 | 11.21 | 0.00847980 | 34271.2 | 2.02053467 | 6.70 | 15.03 | 8.33 | 0.000 | 70656.91 | 40.80 | 0.00563111 | 18.58 | 0.00000000 | 0.0000 | 21.11 | 0.00847980 | 21.11 | 0.00847980 | 49.3911 | 65675.90 | 0.00 | 78397.43 | 78397.43 | 7.74241650 | 21.74 | 15.56 | 0.00847980 | 43397.1 | 11.82 | 11.67 | 0.00847980 | 33271.4 | |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | No | unknown | No | 27088.220 | 27088.220 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6035 | 1004.8586 | 1.0932 | ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 7.082380 | 7.74241650 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 27088.22 | 27088.22 | 1.0000 | 1.40634499 | 1.286455 | 21.74 | 14.59 | 0.00847980 | 43397.1 | 12.80 | 11.21 | 0.00847980 | 34271.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27088.22 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.11 | 0.00784168 | 21.11 | 0.00784168 | 45.7210 | 27088.30 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 79872.310 | -999.000 | 7.617357 | 0.00228430 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9822 | 1004.8586 | 1.0932 | ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 7.617357 | 8.32725012 | 4197.9300 | 999.8980 | 24.60364188 | 15.03 | 6.70 | 8.33 | 860358.77 | 9.2836 | 9.283432 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | unknown | unknown | unknown | 7/21 15:40:00 | Sensible | 79872.31 | 76844.56 | 1.0000 | 8.32725012 | 7.617357 | 21.74 | 14.77 | 0.00868349 | 43913.9 | 12.80 | 11.23 | 0.00850000 | 34322.2 | 2.28406228 | 6.70 | 15.03 | 8.33 | 0.000 | 79872.31 | 40.27 | 0.00563027 | 18.42 | 0.00000000 | 0.0000 | 21.11 | 0.00868349 | 21.11 | 0.00868349 | 50.5632 | 70631.22 | 0.00 | 88327.24 | 85416.46 | 8.32725012 | 21.74 | 15.74 | 0.00868349 | 43913.9 | 11.69 | 11.69 | 0.00854492 | 33306.9 | |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | No | unknown | No | 27188.533 | 27188.533 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6411 | 1004.8586 | 1.0932 | ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 7.617357 | 8.32725012 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 27188.53 | 26157.89 | 1.0000 | 1.41155294 | 1.291219 | 21.74 | 14.77 | 0.00868349 | 43913.9 | 12.80 | 11.23 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27188.53 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.11 | 0.00784219 | 21.11 | 0.00784219 | 45.7240 | 27188.62 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10841.135 | -999.000 | 1.071819 | 0.00031005 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7336 | 1004.8586 | 1.0932 | ROOM_5_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.071819 | 1.17170659 | 4197.9300 | 999.8980 | 24.60364188 | 15.03 | 6.70 | 8.33 | 860358.77 | 1.2601 | 1.260048 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | unknown | unknown | unknown | 7/21 10:20:00 | Sensible | 10841.13 | 10726.44 | 1.0000 | 1.17170659 | 1.071819 | 21.74 | 14.65 | 0.00854980 | 43574.6 | 12.80 | 11.23 | 0.00850000 | 34322.2 | 0.31001766 | 6.70 | 15.03 | 8.33 | 0.000 | 10841.13 | 36.41 | 0.00562429 | 17.20 | 0.00000000 | 0.0000 | 21.11 | 0.00854980 | 21.11 | 0.00854980 | 49.7942 | 9938.75 | 0.00 | 12011.69 | 12011.69 | 1.17170659 | 21.74 | 15.62 | 0.00854980 | 43574.6 | 11.70 | 11.69 | 0.00854980 | 33323.2 | |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | No | unknown | No | 4649.785 | 4649.785 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6411 | 1004.8586 | 1.0932 | ROOM_5_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.071819 | 1.17170659 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 4649.79 | 4600.59 | 1.0000 | 0.24140241 | 0.220823 | 21.74 | 14.65 | 0.00854980 | 43574.6 | 12.80 | 11.23 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4649.79 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.11 | 0.00782675 | 21.11 | 0.00782675 | 45.6354 | 4649.81 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10782.424 | -999.000 | 1.065943 | 0.00030837 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7341 | 1004.8586 | 1.0932 | ROOM_6_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.065943 | 1.16528281 | 4197.9300 | 999.8980 | 24.60364188 | 15.03 | 6.70 | 8.33 | 860358.77 | 1.2532 | 1.253224 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | unknown | unknown | unknown | 7/21 10:10:00 | Sensible | 10782.42 | 10667.79 | 1.0000 | 1.16528281 | 1.065943 | 21.74 | 14.65 | 0.00855004 | 43575.2 | 12.80 | 11.23 | 0.00850000 | 34322.2 | 0.30833876 | 6.70 | 15.03 | 8.33 | 0.000 | 10782.42 | 36.08 | 0.00562379 | 17.09 | 0.00000000 | 0.0000 | 21.11 | 0.00855004 | 21.11 | 0.00855004 | 49.7956 | 9884.26 | 0.00 | 11946.82 | 11946.82 | 1.16528281 | 21.74 | 15.62 | 0.00855004 | 43575.2 | 11.70 | 11.69 | 0.00855004 | 33323.0 | |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | No | unknown | No | 4654.335 | 4654.335 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6411 | 1004.8586 | 1.0932 | ROOM_6_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.065943 | 1.16528281 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 4654.33 | 4604.85 | 1.0000 | 0.24163861 | 0.221039 | 21.74 | 14.65 | 0.00855004 | 43575.2 | 12.80 | 11.23 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4654.33 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.11 | 0.00782693 | 21.11 | 0.00782693 | 45.6364 | 4654.36 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | No | unknown | No | 21546.775 | 21546.775 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 21546.77 | 12331.24 | 1.0000 | 0.51900727 | 0.474762 | 16.70 | 12.29 | 0.00800000 | 37036.7 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21546.77 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.00 | 0.00787261 | 21.00 | 0.00787261 | 46.2130 | 7795.96 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3244.082 | -999.000 | 0.321429 | 0.00009278 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7189 | 1004.8586 | 1.0932 | ROOM_1_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.321429 | 0.35138480 | 4197.9300 | 999.8980 | 24.60364188 | 15.03 | 6.70 | 8.33 | 860358.77 | 0.3771 | 0.377054 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | unknown | unknown | 7/21 16:50:00 | Sensible | 3244.08 | 3215.18 | 1.0000 | 0.35138480 | 0.321429 | 21.74 | 14.65 | 0.00854186 | 43554.5 | 12.80 | 11.23 | 0.00850000 | 34322.2 | 0.09276914 | 6.70 | 15.03 | 8.33 | 0.000 | 3244.08 | 39.12 | 0.00562848 | 18.06 | 0.00000000 | 0.0000 | 21.11 | 0.00854186 | 21.11 | 0.00854186 | 49.7486 | 2980.55 | 0.00 | 3592.63 | 3592.63 | 0.35138480 | 21.74 | 15.61 | 0.00854186 | 43554.5 | 11.72 | 11.69 | 0.00854186 | 33330.3 | |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | No | unknown | No | 1439.142 | 1439.142 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6411 | 1004.8586 | 1.0932 | ROOM_1_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.321429 | 0.35138480 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1439.14 | 1426.32 | 1.0000 | 0.07471579 | 0.068346 | 21.74 | 14.65 | 0.00854186 | 43554.5 | 12.80 | 11.23 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 1439.14 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.11 | 0.00785876 | 21.11 | 0.00785876 | 45.8197 | 1439.15 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3221.883 | -999.000 | 0.319200 | 0.00009214 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7195 | 1004.8586 | 1.0932 | ROOM_2_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.319200 | 0.34894716 | 4197.9300 | 999.8980 | 24.60364188 | 15.03 | 6.70 | 8.33 | 860358.77 | 0.3745 | 0.374474 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | unknown | unknown | 7/21 17:00:00 | Sensible | 3221.88 | 3192.95 | 1.0000 | 0.34894716 | 0.319200 | 21.74 | 14.65 | 0.00854221 | 43555.3 | 12.80 | 11.23 | 0.00850000 | 34322.2 | 0.09213432 | 6.70 | 15.03 | 8.33 | 0.000 | 3221.88 | 38.94 | 0.00562821 | 18.00 | 0.00000000 | 0.0000 | 21.11 | 0.00854221 | 21.11 | 0.00854221 | 49.7506 | 2959.87 | 0.00 | 3568.12 | 3568.12 | 0.34894716 | 21.74 | 15.61 | 0.00854221 | 43555.3 | 11.72 | 11.69 | 0.00854221 | 33330.0 | |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | No | unknown | No | 1439.683 | 1439.683 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6411 | 1004.8586 | 1.0932 | ROOM_2_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.319200 | 0.34894716 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1439.68 | 1426.75 | 1.0000 | 0.07474389 | 0.068372 | 21.74 | 14.65 | 0.00854221 | 43555.3 | 12.80 | 11.23 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 1439.68 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.11 | 0.00785882 | 21.11 | 0.00785882 | 45.8200 | 1439.69 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14627.245 | -999.000 | 1.424163 | 0.00041833 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8383 | 1004.8586 | 1.0932 | ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 1.424163 | 1.55688694 | 4197.9300 | 999.8980 | 24.60364188 | 15.03 | 6.70 | 8.33 | 860358.77 | 1.7001 | 1.700101 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | unknown | unknown | unknown | 7/21 14:20:00 | Sensible | 14627.24 | 14301.43 | 1.0000 | 1.55688694 | 1.424163 | 21.74 | 14.70 | 0.00860610 | 43717.4 | 12.80 | 11.23 | 0.00850000 | 34322.2 | 0.41828687 | 6.70 | 15.03 | 8.33 | 0.000 | 14627.24 | 40.80 | 0.00563111 | 18.58 | 0.00000000 | 0.0000 | 21.11 | 0.00860610 | 21.11 | 0.00860610 | 50.1184 | 13205.56 | 0.00 | 16195.05 | 16195.05 | 1.55688694 | 21.74 | 15.67 | 0.00860610 | 43717.4 | 11.55 | 11.55 | 0.00860610 | 33315.2 | |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | No | unknown | No | 6951.566 | 6951.566 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6411 | 1004.8586 | 1.0932 | ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 1.424163 | 1.55688694 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 6951.57 | 6796.72 | 1.0000 | 0.36090454 | 0.330138 | 21.74 | 14.70 | 0.00860610 | 43717.4 | 12.80 | 11.23 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6951.57 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.11 | 0.00786511 | 21.11 | 0.00786511 | 45.8562 | 6951.60 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Electric | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | No | unknown | No | 30283.772 | 30283.772 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 30283.77 | 30283.77 | 1.0000 | 1.29849281 | 1.187797 | 16.70 | 12.29 | 0.00800000 | 37036.7 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30283.77 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.00 | 0.00789849 | 21.00 | 0.00789849 | 46.3631 | 4973.38 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Electric | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | No | unknown | No | 31691.706 | 31691.706 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | Sensible | 31691.71 | 30851.25 | 1.0000 | 1.29849281 | 1.187797 | 16.70 | 12.29 | 0.00800000 | 37036.7 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31691.71 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.00 | 0.00790059 | 21.00 | 0.00790059 | 46.3754 | 5082.04 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Electric | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | No | unknown | No | 30726.136 | 30726.136 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | Sensible | 30726.14 | 9541.38 | 1.0000 | 0.40158529 | 0.367350 | 16.70 | 12.29 | 0.00800000 | 37036.7 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30726.14 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.05 | 0.00602609 | 21.00 | 0.00602609 | 35.4839 | 1125.67 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | No | unknown | No | 10903.730 | 10903.730 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | Sensible | 10903.73 | 6471.91 | 1.0000 | 0.27239523 | 0.249174 | 16.70 | 12.29 | 0.00800000 | 37036.7 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10903.73 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.00 | 0.00791577 | 21.00 | 0.00791577 | 46.4633 | 5277.55 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 65945.855 | -999.000 | 2.051317 | 0.00188604 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1015.3079 | 1004.8586 | 1.0932 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.24240930 | 4197.9300 | 999.8980 | 24.60364188 | 15.03 | 6.70 | 8.33 | 860358.77 | 7.6649 | 7.664925 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | Sensible | 65945.86 | 65945.86 | 1.0000 | 2.24248814 | 2.051317 | 40.80 | 18.58 | 0.00563111 | 55507.6 | 11.84 | 7.85 | 0.00563111 | 26100.2 | 1.88585072 | 6.70 | 15.03 | 8.33 | 2195.006 | 63750.85 | 40.80 | 0.00563111 | 18.58 | 2.05124512 | 99.9965 | 21.11 | 0.00857951 | 21.11 | 0.00858538 | 49.9987 | 192046.61 | 0.00 | 65994.93 | 65994.93 | 2.24248814 | 40.80 | 19.66 | 0.00563111 | 55507.6 | 11.81 | 8.61 | 0.00563111 | 26078.3 | |
FLR_3_DOAS HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10951.444 | 10951.444 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.24240930 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 10951.44 | 10951.44 | 1.0000 | 0.67274644 | 0.615395 | 0.50 | 0.50 | 0.00431558 | 11299.5 | 16.70 | 12.29 | 0.00800000 | 37036.7 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10951.44 | 0.50 | 0.00431558 | 0.50 | 2.05124512 | 333.3216 | 21.11 | 0.00784111 | 21.11 | 0.00784203 | 45.7230 | 82735.05 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 576771.072 | -999.000 | 24.366406 | 0.01649558 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.1698 | 1004.8586 | 1.0932 | VAV WITH REHEAT FAN | Fan:VariableVolume | 24.366406 | 26.63721441 | 4197.9300 | 999.8980 | 24.60364188 | 15.03 | 6.70 | 8.33 | 860358.77 | 67.0384 | 67.038437 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | Sensible | 576771.07 | 576771.07 | 1.0000 | 26.63721441 | 24.366406 | 32.03 | 17.43 | 0.00770854 | 51927.2 | 10.79 | 9.61 | 0.00770854 | 30274.3 | 16.49389693 | 6.70 | 15.03 | 8.33 | 54596.311 | 522174.76 | 40.80 | 0.00563111 | 18.58 | 11.66146000 | 47.8588 | 23.99 | 0.00961535 | 23.99 | 0.00956939 | 46.7075 | 304253.14 | 0.00 | 616784.76 | 603506.26 | 26.63721441 | 32.03 | 18.48 | 0.00770854 | 51927.2 | 9.80 | 9.78 | 0.00751066 | 28772.2 | |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 130085.840 | 130085.840 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | VAV WITH REHEAT FAN | Fan:VariableVolume | 24.366406 | 26.63721441 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 19:10:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 19:10:00 | Sensible | 130085.84 | 130085.84 | 1.0000 | 7.99116432 | 7.309922 | 0.50 | 0.50 | 0.00431558 | 11299.5 | 16.70 | 12.29 | 0.00800000 | 37036.7 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 130085.84 | 0.50 | 0.00431558 | 0.50 | 11.66146000 | 159.5292 | 18.47 | 0.00785756 | 21.63 | 0.00798185 | 45.0773 | 48533.85 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:26
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - | |||
VAV WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 24.37 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | VAV WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000610 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LAUNDRY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CAFE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001448 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_3 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
KITCHEN_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003556 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 1894.00 | 6223.50 | 563.50 |
RETAIL_1_FLR_1 | 3161.33 | 4598.17 | 595.00 |
RETAIL_2_FLR_1 | 2303.33 | 5161.83 | 693.00 |
MECH_FLR_1 | 1715.17 | 6028.50 | 37.17 |
STORAGE_FLR_1 | 1621.67 | 6218.17 | 90.67 |
LAUNDRY_FLR_1 | 8015.50 | 3519.67 | 3280.33 |
CAFE_FLR_1 | 4763.50 | 2969.67 | 1187.50 |
LOBBY_FLR_1 | 3003.67 | 3840.67 | 1039.17 |
ROOM_1_FLR_3 | 192.83 | 8006.67 | 122.67 |
ROOM_2_FLR_3 | 455.50 | 8077.83 | 368.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 187.67 | 8752.33 | 187.33 |
ROOM_5_FLR_3 | 134.83 | 7882.67 | 128.67 |
ROOM_6_FLR_3 | 536.83 | 7726.17 | 360.17 |
CORRIDOR_FLR_3 | 1540.67 | 7092.33 | 780.50 |
ROOM_1_FLR_6 | 559.00 | 7805.67 | 387.50 |
ROOM_2_FLR_6 | 974.83 | 7910.17 | 827.00 |
ROOM_3_MULT9_FLR_6 | 103.67 | 7791.67 | 63.17 |
BANQUET_FLR_6 | 4761.83 | 2099.67 | 1116.33 |
DINING_FLR_6 | 5504.83 | 1351.50 | 1050.67 |
KITCHEN_FLR_6 | 8608.00 | 6691.33 | 6686.50 |
CORRIDOR_FLR_6 | 2024.67 | 5939.50 | 509.50 |
Facility | 8742.67 | 8760.00 | 7217.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 23.17 | 0.00 | 23.17 |
ROOM_2_FLR_3 | 0.00 | 21.50 | 0.00 | 21.50 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 10.33 | 0.00 | 10.33 |
ROOM_5_FLR_3 | 0.00 | 12.83 | 0.00 | 12.83 |
ROOM_6_FLR_3 | 0.00 | 35.17 | 0.00 | 35.17 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 34.67 | 0.00 | 34.67 |
ROOM_2_FLR_6 | 0.00 | 30.83 | 0.00 | 30.83 |
ROOM_3_MULT9_FLR_6 | 0.00 | 27.83 | 0.00 | 27.83 |
BANQUET_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 86.83 | 0.00 | 86.83 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:26
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.79 | 106.50 | 4826.41 | 1.026 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 2.343 | 0.060 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.28 | 12.54 | 307.76 | 1.442 | 0.020 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.592 | 0.022 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.597 | 0.022 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 21.519 | 0.064 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.56 | 142.30 | 748.35 | 3.681 | 0.047 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.09 | 422.44 | 5183.56 | 1.752 | 0.020 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.355 | 0.078 | 0.000 | 0.052 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.356 | 0.078 | 0.000 | 0.052 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.404 | 0.034 | 0.000 | 0.080 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.355 | 0.078 | 0.000 | 0.052 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.356 | 0.078 | 0.000 | 0.051 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 0.566 | 0.009 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.355 | 0.078 | 0.000 | 0.061 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.356 | 0.078 | 0.000 | 0.058 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.404 | 0.063 | 0.000 | 0.097 |
BANQUET_FLR_6 | 144.99 | 249.90 | 1010.89 | 4.846 | 0.023 | 0.000 | 0.000 |
DINING_FLR_6 | 144.99 | 249.90 | 1010.89 | 5.204 | 0.023 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 21.521 | 0.065 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 1.126 | 0.016 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.79 | 106.50 | 4826.41 | 0.495 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 1.364 | 0.001 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.28 | 12.54 | 307.76 | 0.957 | 0.000 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.452 | 0.000 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.419 | 0.000 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 10.325 | 0.001 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.56 | 142.30 | 748.35 | 2.587 | 0.001 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.09 | 422.44 | 5183.56 | 1.173 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 0.330 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.000 | 0.001 | 0.000 | 0.000 |
BANQUET_FLR_6 | 144.99 | 249.90 | 1010.89 | 3.433 | 0.000 | 0.000 | 0.000 |
DINING_FLR_6 | 144.99 | 249.90 | 1010.89 | 3.623 | 0.000 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 8.669 | 0.001 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 0.710 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:26
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | VAV WITH REHEAT | 61.79 | 106.50 | 4826.41 | 1978.83 | 0.0000 | 0.854 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 6.28 | 10.83 | 265.76 | 67.07 | 0.0000 | 0.079 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 7.28 | 12.54 | 307.76 | 77.67 | 0.0000 | 0.092 |
MECH_FLR_1 | VAV WITH REHEAT | 1.54 | 2.65 | 650.80 | 164.24 | 0.0000 | 0.000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 1.18 | 2.04 | 375.47 | 94.76 | 0.0000 | 0.058 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 4.87 | 8.40 | 309.22 | 78.04 | 0.0000 | 0.000 |
CAFE_FLR_1 | VAV WITH REHEAT | 82.56 | 142.30 | 748.35 | 188.86 | 0.0000 | 0.676 |
LOBBY_FLR_1 | VAV WITH REHEAT | 245.09 | 422.44 | 5183.56 | 1308.19 | 0.0000 | 1.894 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 1.50 | 74.75 | 24.52 | 0.0000 | 0.837 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.837 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 12.16 | 20.96 | 1186.91 | 389.40 | 0.0000 | 0.475 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.015 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.015 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.099 |
BANQUET_FLR_6 | VAV WITH REHEAT | 144.99 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
DINING_FLR_6 | VAV WITH REHEAT | 144.99 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 12.90 | 22.24 | 314.87 | 103.30 | 0.0000 | 0.367 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 12.87 | 22.18 | 1256.16 | 412.12 | 0.0000 | 0.126 |
Total Facility | 873.25 | 1604.23 | 35184.81 | 11345.29 | 0.0000 | 137.584 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 42484888.87 | 0.00 | 42484888.87 | 0.00 | 42484888.87 | 26946214.98 | 268.68 | 35.76 | 8455.56 | 0.00 |
RETAIL_1_FLR_1 | 5353941.41 | 0.00 | 5353941.41 | 137347.52 | 5491288.94 | 2498216.28 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_2_FLR_1 | 3807600.20 | 0.00 | 3807600.20 | 53016.32 | 3860616.52 | 2892943.94 | 74.10 | 32.20 | 8653.70 | 0.00 |
MECH_FLR_1 | 3314918.20 | 0.00 | 3314918.20 | 125299.08 | 3440217.28 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
STORAGE_FLR_1 | 1929025.63 | 0.00 | 1929025.63 | 72290.67 | 2001316.30 | 1821682.01 | 2661.17 | 266.06 | 5832.77 | 0.00 |
LAUNDRY_FLR_1 | 57170942.28 | 0.00 | 57170942.28 | 171089.49 | 57342031.77 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
CAFE_FLR_1 | 23589727.56 | 0.00 | 23589727.56 | 303614.48 | 23893342.04 | 21330615.53 | 3273.10 | 249.59 | 5237.30 | 0.00 |
LOBBY_FLR_1 | 77780542.06 | 0.00 | 77780542.06 | 867495.92 | 78648037.97 | 59728886.00 | 143.08 | 68.14 | 8548.78 | 0.00 |
ROOM_1_FLR_3 | 1460156.71 | 53653.37 | 1513810.08 | 79720.28 | 1593530.36 | 1946875.62 | 2190.00 | 5876.17 | 693.83 | 0.00 |
ROOM_2_FLR_3 | 1459985.63 | 52876.67 | 1512862.30 | 79714.20 | 1592576.50 | 1946647.51 | 2190.00 | 5880.95 | 689.05 | 0.00 |
ROOM_3_MULT19_FLR_3 | 1099911.97 | 0.00 | 1099911.97 | 22242.85 | 1122154.82 | 26397887.27 | 8395.00 | 365.00 | 0.00 | 365.00 |
ROOM_4_MULT19_FLR_3 | 19803829.30 | 51636.47 | 19855465.77 | 22248.93 | 19877714.70 | 26405105.73 | 2190.00 | 5907.56 | 662.44 | 0.00 |
ROOM_5_FLR_3 | 1460156.71 | 53747.55 | 1513904.26 | 79720.28 | 1593624.54 | 1946875.62 | 2190.00 | 5876.17 | 693.83 | 0.00 |
ROOM_6_FLR_3 | 1459985.63 | 52291.09 | 1512276.72 | 79714.20 | 1591990.92 | 1946647.51 | 2190.00 | 5877.42 | 692.58 | 0.00 |
CORRIDOR_FLR_3 | 23117630.43 | 0.00 | 23117630.43 | 96397.86 | 23214028.29 | 14972100.18 | 12.61 | 16.24 | 8731.15 | 0.00 |
ROOM_1_FLR_6 | 365039.18 | 62565.27 | 427604.45 | 79736.38 | 507340.83 | 486718.90 | 2021.55 | 5878.58 | 859.87 | 0.00 |
ROOM_2_FLR_6 | 364996.41 | 59382.66 | 424379.07 | 79730.30 | 504109.37 | 486661.88 | 2042.16 | 5888.36 | 829.48 | 0.00 |
ROOM_3_MULT9_FLR_6 | 2345190.31 | 62750.29 | 2407940.60 | 40795.93 | 2448736.53 | 3126920.42 | 2190.00 | 5876.17 | 693.83 | 0.00 |
BANQUET_FLR_6 | 41912694.30 | 0.00 | 41912694.30 | 194696.21 | 42107390.51 | 37458366.31 | 3339.27 | 538.44 | 4882.28 | 0.00 |
DINING_FLR_6 | 45006273.76 | 0.00 | 45006273.76 | 194696.21 | 45200969.97 | 37458366.31 | 486.95 | 192.53 | 8080.52 | 0.00 |
KITCHEN_FLR_6 | 58030107.54 | 0.00 | 58030107.54 | 174298.25 | 58204405.79 | 11584760.86 | 0.00 | 0.00 | 8760.00 | 0.00 |
CORRIDOR_FLR_6 | 12169760.36 | 0.00 | 12169760.36 | 170593.40 | 12340353.75 | 3961413.96 | 0.00 | 0.00 | 8760.00 | 0.00 |
Total Facility | 0.21E+10 | 5461347.11 | 0.21E+10 | 8033510.48 | 0.21E+10 | 0.43E+10 | 8760.00 | 6616.50 | 8760.00 | 365.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 1.3472 | 0.0000 | 1.3472 | 0.0000 | 1.3472 | 0.8545 | 268.68 | 35.76 | 8455.56 |
RETAIL_1_FLR_1 | 0.1698 | 0.0000 | 0.1698 | 0.0044 | 0.1741 | 0.0792 | 0.00 | 0.00 | 8760.00 |
RETAIL_2_FLR_1 | 0.1207 | 0.0000 | 0.1207 | 0.0017 | 0.1224 | 0.0917 | 74.10 | 32.20 | 8653.70 |
MECH_FLR_1 | 0.1051 | 0.0000 | 0.1051 | 0.0040 | 0.1091 | 0.0000 | 0.00 | 0.00 | 8760.00 |
STORAGE_FLR_1 | 0.0612 | 0.0000 | 0.0612 | 0.0023 | 0.0635 | 0.0578 | 2661.17 | 266.06 | 5832.77 |
LAUNDRY_FLR_1 | 1.8129 | 0.0000 | 1.8129 | 0.0054 | 1.8183 | 0.0000 | 0.00 | 0.00 | 8760.00 |
CAFE_FLR_1 | 0.7480 | 0.0000 | 0.7480 | 0.0096 | 0.7577 | 0.6764 | 3273.10 | 249.59 | 5237.30 |
LOBBY_FLR_1 | 2.4664 | 0.0000 | 2.4664 | 0.0275 | 2.4939 | 1.8940 | 143.08 | 68.14 | 8548.78 |
ROOM_1_FLR_3 | 0.0463 | 0.0017 | 0.0480 | 0.0025 | 0.0505 | 0.0617 | 2190.00 | 5876.17 | 693.83 |
ROOM_2_FLR_3 | 0.0463 | 0.0017 | 0.0480 | 0.0025 | 0.0505 | 0.0617 | 2190.00 | 5880.95 | 689.05 |
ROOM_4_MULT19_FLR_3 | 0.6280 | 0.0016 | 0.6296 | 0.0007 | 0.6303 | 0.8373 | 2190.00 | 5907.56 | 662.44 |
ROOM_5_FLR_3 | 0.0463 | 0.0017 | 0.0480 | 0.0025 | 0.0505 | 0.0617 | 2190.00 | 5876.17 | 693.83 |
ROOM_6_FLR_3 | 0.0463 | 0.0017 | 0.0480 | 0.0025 | 0.0505 | 0.0617 | 2190.00 | 5877.42 | 692.58 |
CORRIDOR_FLR_3 | 0.7331 | 0.0000 | 0.7331 | 0.0031 | 0.7361 | 0.4748 | 12.61 | 16.24 | 8731.15 |
ROOM_1_FLR_6 | 0.0116 | 0.0020 | 0.0136 | 0.0025 | 0.0161 | 0.0154 | 2021.55 | 5878.58 | 859.87 |
ROOM_2_FLR_6 | 0.0116 | 0.0019 | 0.0135 | 0.0025 | 0.0160 | 0.0154 | 2042.16 | 5888.36 | 829.48 |
ROOM_3_MULT9_FLR_6 | 0.0744 | 0.0020 | 0.0764 | 0.0013 | 0.0776 | 0.0992 | 2190.00 | 5876.17 | 693.83 |
BANQUET_FLR_6 | 1.3290 | 0.0000 | 1.3290 | 0.0062 | 1.3352 | 1.1878 | 3339.27 | 538.44 | 4882.28 |
DINING_FLR_6 | 1.4271 | 0.0000 | 1.4271 | 0.0062 | 1.4333 | 1.1878 | 486.95 | 192.53 | 8080.52 |
KITCHEN_FLR_6 | 1.8401 | 0.0000 | 1.8401 | 0.0055 | 1.8456 | 0.3674 | 0.00 | 0.00 | 8760.00 |
CORRIDOR_FLR_6 | 0.3859 | 0.0000 | 0.3859 | 0.0054 | 0.3913 | 0.1256 | 0.00 | 0.00 | 8760.00 |
Total Facility | 63.9051 | 0.1732 | 64.0782 | 0.2011 | 64.2794 | 73.9670 | 8760.00 | 6616.50 | 8760.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
FLR_3_DOAS | 35636200.53 | 448903.37 | 36085103.90 | 64690340.46 | 8760.00 | 0.00 | 0.00 | 0.00 |
VAV WITH REHEAT | 0.47E+09 | 0.00 | 0.47E+09 | 0.22E+09 | 0.00 | 0.00 | 8760.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
FLR_3_DOAS | 1.1300 | 0.0142 | 1.1443 | 2.0513 | 8760.00 | 0.00 | 0.00 |
VAV WITH REHEAT | 14.9941 | 0.0000 | 14.9941 | 6.9969 | 0.00 | 0.00 | 8760.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
FLR_3_DOAS | 0.00 | 0.00 | 0.00 | 0.00 | 6935.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
VAV WITH REHEAT | 0.00 | 0.00 | 4717.18 | 0.00 | 0.00 | 0.00 | 4042.82 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
FLR_3_DOAS | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.4274 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
VAV WITH REHEAT | 0.0000 | 0.0000 | 16.0783 | 0.0000 | 0.0000 | 0.0000 | 13.7324 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:26
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1269 |
Defaulted Fields | 1144 |
Fields with Defaults | 3764 |
Autosized Fields | 294 |
Autosizable Fields | 344 |
Autocalculated Fields | 279 |
Autocalculatable Fields | 538 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:21:26
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 6213.01 | 74547.24 | 24-JAN-02:50 | 408694.68 | 28-JUN-18:20 |
Electricity:Building | 2448.51 | 31501.02 | 02-JAN-02:10 | 151313.73 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 304.40 | 3493.55 | 02-JAN-02:10 | 22822.84 | 02-JAN-20:10 |
Electricity:SpaceType:GENERAL | 2441.42 | 31359.87 | 02-JAN-02:10 | 151072.40 | 02-JAN-20:10 |
InteriorLights:Electricity | 783.24 | 7157.90 | 02-JAN-02:10 | 64632.59 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 161.29 | 1465.65 | 02-JAN-02:10 | 13190.31 | 02-JAN-20:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 783.24 | 7157.90 | 02-JAN-02:10 | 64632.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 783.24 | 7157.90 | 02-JAN-02:10 | 64632.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 161.29 | 1465.65 | 02-JAN-02:10 | 13190.31 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 783.24 | 7157.90 | 02-JAN-02:10 | 64632.59 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 17.49 | 210.74 | 02-JAN-02:10 | 1283.20 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 7.31 | 66.40 | 02-JAN-02:10 | 597.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 7.31 | 66.40 | 02-JAN-02:10 | 597.59 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 20.26 | 244.03 | 02-JAN-02:10 | 1485.95 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 8.46 | 76.89 | 02-JAN-02:10 | 692.02 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 8.46 | 76.89 | 02-JAN-02:10 | 692.02 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 20.84 | 252.75 | 02-JAN-02:10 | 1523.62 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.37 | 76.02 | 02-JAN-02:10 | 684.18 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.37 | 76.02 | 02-JAN-02:10 | 684.18 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 6.68 | 78.96 | 02-JAN-02:10 | 493.99 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 3.08 | 27.98 | 02-JAN-02:10 | 251.84 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 3.08 | 27.98 | 02-JAN-02:10 | 251.84 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 71.91 | 998.82 | 02-JAN-02:10 | 4897.88 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 3.98 | 36.12 | 02-JAN-02:10 | 325.08 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 3.98 | 36.12 | 02-JAN-02:10 | 325.08 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 28.55 | 388.01 | 01-JAN-13:10 | 2666.80 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 14.21 | 83.19 | 01-JAN-13:10 | 1701.53 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 | 14.21 | 83.19 | 01-JAN-13:10 | 1701.53 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 259.18 | 3167.50 | 02-JAN-02:10 | 19534.01 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 110.18 | 1056.09 | 02-JAN-02:10 | 9504.80 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 110.18 | 1056.09 | 02-JAN-02:10 | 9504.80 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 19.72 | 257.38 | 01-JAN-02:10 | 1438.51 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 19.72 | 257.35 | 01-JAN-02:10 | 1438.34 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 305.38 | 4267.82 | 01-JAN-02:10 | 22404.45 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 110.39 | 934.58 | 01-JAN-02:10 | 8496.21 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 110.39 | 934.58 | 01-JAN-02:10 | 8496.21 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 305.47 | 4268.99 | 01-JAN-02:10 | 22410.58 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 110.42 | 934.84 | 01-JAN-02:10 | 8498.53 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 110.42 | 934.84 | 01-JAN-02:10 | 8498.53 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 19.72 | 257.38 | 01-JAN-02:10 | 1438.51 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 19.72 | 257.35 | 01-JAN-02:10 | 1438.34 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 4.93 | 64.34 | 01-JAN-02:10 | 359.63 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 2.31 | 19.57 | 01-JAN-02:10 | 177.88 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 2.31 | 19.57 | 01-JAN-02:10 | 177.88 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 4.93 | 64.34 | 01-JAN-02:10 | 359.59 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 2.31 | 19.56 | 01-JAN-02:10 | 177.86 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 2.31 | 19.56 | 01-JAN-02:10 | 177.86 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 36.17 | 505.54 | 01-JAN-02:10 | 2653.88 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 13.08 | 110.70 | 01-JAN-02:10 | 1006.40 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 13.08 | 110.70 | 01-JAN-02:10 | 1006.40 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 207.07 | 2581.30 | 02-JAN-02:10 | 9735.93 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 31.21 | 332.00 | 02-JAN-02:10 | 2988.03 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 31.21 | 332.00 | 02-JAN-02:10 | 2988.03 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 207.07 | 2581.30 | 02-JAN-02:10 | 9735.93 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 31.21 | 332.00 | 02-JAN-02:10 | 2988.03 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 | 31.21 | 332.00 | 02-JAN-02:10 | 2988.03 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 453.81 | 6249.79 | 02-JAN-02:10 | 18934.39 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 12.97 | 117.87 | 02-JAN-02:10 | 1060.81 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 12.97 | 117.87 | 02-JAN-02:10 | 1060.81 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1658.18 | 24201.97 | 02-JAN-02:10 | 89171.45 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 1658.18 | 24201.97 | 02-JAN-02:10 | 89171.45 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 433.74 | 5990.78 | 01-JAN-00:10 | 16487.34 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 410.33 | 5248.28 | 01-JAN-00:10 | 15744.84 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
Refrigeration:Electricity | 61.73 | 1114.47 | 23-APR-22:30 | 3261.45 | 01-SEP-06:20 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
Electricity:Plant | 1722.85 | 2619.42 | 07-DEC-03:40 | 204015.00 | 28-JUN-18:10 |
LowTempRefrigeration:Refrigeration:Electricity | 20.48 | 0.00 | 01-JAN-11:10 | 1893.83 | 17-JUN-10:50 |
MedTempRefrigeration:Refrigeration:Electricity | 34.17 | 975.78 | 08-DEC-04:10 | 1202.92 | 13-NOV-14:10 |
Fans:Electricity | 585.27 | 10941.60 | 22-JAN-04:30 | 47693.26 | 07-SEP-21:10 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 1055.59 | 12067.85 | 06-MAR-14:20 | 159015.33 | 08-FEB-07:10 |
ExteriorEquipment:Electricity | 813.77 | 9999.82 | 02-JAN-02:20 | 49607.07 | 02-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 21.77 | 381.02 | 02-JAN-02:20 | 1291.59 | 02-JAN-21:10 |
ElectricityPurchased:Facility | 6213.01 | 74547.24 | 24-JAN-02:50 | 408694.68 | 28-JUN-18:20 |
ElectricityPurchased:Plant | 6213.01 | 74547.24 | 24-JAN-02:50 | 408694.68 | 28-JUN-18:20 |
Cogeneration:ElectricityPurchased | 6213.01 | 74547.24 | 24-JAN-02:50 | 408694.68 | 28-JUN-18:20 |
General:Cogeneration:ElectricityPurchased | 6213.01 | 74547.24 | 24-JAN-02:50 | 408694.68 | 28-JUN-18:20 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 6213.01 | 74547.24 | 24-JAN-02:50 | 408694.68 | 28-JUN-18:20 |
ElectricityNet:Plant | 6213.01 | 74547.24 | 24-JAN-02:50 | 408694.68 | 28-JUN-18:20 |
Cogeneration:ElectricityNet | 6213.01 | 74547.24 | 24-JAN-02:50 | 408694.68 | 28-JUN-18:20 |
General:Cogeneration:ElectricityNet | 6213.01 | 74547.24 | 24-JAN-02:50 | 408694.68 | 28-JUN-18:20 |
Heating:Electricity | 298.81 | 0.00 | 02-JAN-13:10 | 141230.50 | 08-FEB-07:10 |
General:Heating:Electricity | 298.81 | 0.00 | 02-JAN-13:10 | 141230.50 | 08-FEB-07:10 |
General:Fans:Electricity | 585.27 | 10941.60 | 22-JAN-04:30 | 47693.26 | 07-SEP-21:10 |
ExteriorLights:Electricity | 194.06 | 0.00 | 01-JAN-07:30 | 12338.45 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 194.06 | 0.00 | 01-JAN-07:30 | 12338.45 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 789.09 | 9600.00 | 01-JAN-00:10 | 48128.80 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 2.91 | 18.80 | 01-JAN-00:10 | 188.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 149.74 | 0.00 | 01-JAN-11:10 | 9938.94 | 01-APR-09:00 |
General:HeatRecovery:Electricity | 149.74 | 0.00 | 01-JAN-11:10 | 9938.94 | 01-APR-09:00 |
WaterSystems:Electricity | 94.78 | 1222.48 | 06-APR-02:00 | 4751.13 | 16-OCT-07:00 |
Water Heater:WaterSystems:Electricity | 94.78 | 1222.48 | 06-APR-02:00 | 4751.13 | 16-OCT-07:00 |
Cooling:Electricity | 1482.55 | 0.00 | 01-JAN-00:30 | 192789.78 | 28-JUN-18:10 |
General:Cooling:Electricity | 1482.55 | 0.00 | 01-JAN-00:30 | 192789.78 | 28-JUN-18:10 |
Pumps:Electricity | 90.87 | 47.91 | 04-JAN-05:40 | 4332.22 | 29-JUN-18:10 |
General:Pumps:Electricity | 90.87 | 47.91 | 04-JAN-05:40 | 4332.22 | 29-JUN-18:10 |
WIRED_LTG_ELECTRICITY | 27.57 | 0.00 | 01-JAN-00:10 | 2275.07 | 02-JAN-20:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 4005.38 | 21457.33 | 25-JUL-02:20 | 324056.54 | 10-FEB-18:20 |
NaturalGas:Building | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Laundry:InteriorEquipment:NaturalGas | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
NaturalGas:Plant | 2216.54 | 8095.43 | 25-JUL-02:20 | 222242.78 | 23-JAN-21:40 |
WaterSystems:NaturalGas | 2216.54 | 8095.43 | 25-JUL-02:20 | 222242.78 | 23-JAN-21:40 |
Water Heater:WaterSystems:NaturalGas | 2216.54 | 8095.43 | 25-JUL-02:20 | 222242.78 | 23-JAN-21:40 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 5443.55 | 0.00 | 01-JAN-00:30 | 609387.99 | 10-SEP-22:00 |
PlantLoopCoolingDemand:HVAC | 5443.55 | 0.00 | 01-JAN-00:30 | 609387.99 | 10-SEP-22:00 |
CoolingCoils:PlantLoopCoolingDemand | 5443.55 | 0.00 | 01-JAN-00:30 | 609387.99 | 10-SEP-22:00 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 9857.19 | 0.00 | 02-JAN-01:30 | 0.00 | 17-JAN-21:20 |
Water:Plant | 9857.19 | 0.00 | 02-JAN-01:30 | 0.00 | 17-JAN-21:20 |
WaterSystems:Water | 9857.19 | 0.00 | 02-JAN-01:30 | 0.00 | 17-JAN-21:20 |
Water Heater:WaterSystems:Water | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:10 |
MainsWater:Facility | 9857.19 | 0.00 | 02-JAN-01:30 | 0.00 | 17-JAN-21:20 |
MainsWater:Plant | 9857.19 | 0.00 | 02-JAN-01:30 | 0.00 | 17-JAN-21:20 |
WaterSystems:MainsWater | 9857.19 | 0.00 | 02-JAN-01:30 | 0.00 | 17-JAN-21:20 |
Water Heater:WaterSystems:MainsWater | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:10 |
WaterUse:WaterSystems:Water | 4114.69 | 0.00 | 02-JAN-01:30 | 0.00 | 27-MAR-06:20 |
WaterUse:WaterSystems:MainsWater | 4114.69 | 0.00 | 02-JAN-01:30 | 0.00 | 27-MAR-06:20 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 25804.83 | 125486.23 | 12-FEB-15:10 | 2327934.28 | 10-SEP-22:00 |
EnergyTransfer:Building | 6053.35 | 93812.45 | 12-FEB-15:00 | 395567.24 | 28-JUN-18:20 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 749.37 | 10745.89 | 07-DEC-04:00 | 36558.46 | 13-AUG-10:50 |
Refrigeration:EnergyTransfer | 181.91 | 4015.95 | 23-APR-22:20 | 10358.28 | 01-SEP-06:20 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 90.95 | 2007.97 | 23-APR-22:20 | 5179.14 | 01-SEP-06:20 |
General:Refrigeration:EnergyTransfer | 90.95 | 2007.97 | 23-APR-22:20 | 5179.14 | 01-SEP-06:20 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 90.95 | 2007.97 | 23-APR-22:20 | 5179.14 | 01-SEP-06:20 |
EnergyTransfer:Plant | 13213.78 | 10452.84 | 26-OCT-02:50 | 1416221.58 | 10-SEP-22:00 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 21.56 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 69.39 | 1877.33 | 08-DEC-04:10 | 2558.77 | 13-NOV-14:10 |
EnergyTransfer:Zone:BASEMENT | 456.73 | 9870.18 | 25-MAR-07:10 | 26076.76 | 08-SEP-21:00 |
Heating:EnergyTransfer | 12.23 | 0.00 | 01-JAN-08:10 | 21120.25 | 27-MAR-06:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 12.23 | 0.00 | 01-JAN-08:10 | 21120.25 | 27-MAR-06:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 5950.17 | 90931.11 | 12-FEB-15:00 | 392023.93 | 28-JUN-18:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 456.73 | 9870.18 | 25-MAR-07:10 | 26076.76 | 08-SEP-21:00 |
General:Cooling:EnergyTransfer | 5950.17 | 90931.11 | 12-FEB-15:00 | 392023.93 | 28-JUN-18:20 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 456.73 | 9870.18 | 25-MAR-07:10 | 26076.76 | 08-SEP-21:00 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 54.88 | 1.52 | 06-DEC-07:10 | 3908.28 | 02-OCT-12:40 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 42.65 | 16-DEC-07:20 |
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 42.65 | 16-DEC-07:20 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 54.88 | 0.00 | 16-DEC-07:10 | 3908.28 | 02-OCT-12:40 |
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 54.88 | 0.00 | 16-DEC-07:10 | 3908.28 | 02-OCT-12:40 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 41.76 | 793.19 | 17-DEC-06:50 | 2559.28 | 28-JUN-21:00 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 41.76 | 793.19 | 17-DEC-06:50 | 2559.28 | 28-JUN-21:00 |
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 41.76 | 793.19 | 17-DEC-06:50 | 2559.28 | 28-JUN-21:00 |
EnergyTransfer:Zone:MECH_FLR_1 | 34.09 | 512.24 | 07-DEC-10:50 | 2446.56 | 28-JUN-20:00 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 34.09 | 512.24 | 07-DEC-10:50 | 2446.56 | 28-JUN-20:00 |
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 34.09 | 512.24 | 07-DEC-10:50 | 2446.56 | 28-JUN-20:00 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 19.18 | 192.04 | 07-DEC-05:00 | 1284.83 | 28-JUN-19:10 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 19.18 | 192.04 | 07-DEC-05:00 | 1284.83 | 28-JUN-19:10 |
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 19.18 | 192.04 | 07-DEC-05:00 | 1284.83 | 28-JUN-19:10 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 618.53 | 9904.45 | 07-DEC-05:00 | 39834.47 | 28-JUN-20:00 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 618.53 | 9904.45 | 07-DEC-05:00 | 39834.47 | 28-JUN-20:00 |
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 618.53 | 9904.45 | 07-DEC-05:00 | 39834.47 | 28-JUN-20:00 |
EnergyTransfer:Zone:CAFE_FLR_1 | 261.98 | 3154.77 | 12-FEB-16:00 | 14179.12 | 01-NOV-15:10 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 261.98 | 3154.77 | 12-FEB-16:00 | 14179.12 | 01-NOV-15:10 |
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 261.98 | 3154.77 | 12-FEB-16:00 | 14179.12 | 01-NOV-15:10 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 867.11 | 16768.07 | 12-FEB-16:00 | 46472.96 | 28-JUN-21:10 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 867.11 | 16768.07 | 12-FEB-16:00 | 46472.96 | 28-JUN-21:10 |
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 867.11 | 16768.07 | 12-FEB-16:00 | 46472.96 | 28-JUN-21:10 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 90.56 | 0.00 | 01-JAN-08:10 | 12552.91 | 15-JUN-18:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 0.96 | 0.00 | 01-JAN-08:10 | 2051.62 | 07-DEC-06:00 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 0.96 | 0.00 | 01-JAN-08:10 | 2051.62 | 07-DEC-06:00 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 89.60 | 0.00 | 01-JAN-00:10 | 12552.91 | 15-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 89.60 | 0.00 | 01-JAN-00:10 | 12552.91 | 15-JUN-18:10 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 75.74 | 0.00 | 01-JAN-08:10 | 12894.15 | 14-JUN-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 2.07 | 0.00 | 01-JAN-08:10 | 3207.78 | 07-DEC-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 2.07 | 0.00 | 01-JAN-08:10 | 3207.78 | 07-DEC-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 73.67 | 0.00 | 01-JAN-00:10 | 12894.15 | 14-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 73.67 | 0.00 | 01-JAN-00:10 | 12894.15 | 14-JUN-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 507.64 | 0.00 | 01-JAN-00:10 | 48602.07 | 20-NOV-14:30 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 507.64 | 0.00 | 01-JAN-00:10 | 48602.07 | 20-NOV-14:30 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 507.64 | 0.00 | 01-JAN-00:10 | 48602.07 | 20-NOV-14:30 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 573.33 | 0.00 | 01-JAN-08:10 | 82429.64 | 01-JUL-08:10 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 3.35 | 0.00 | 01-JAN-00:10 | 16174.26 | 30-MAR-04:30 |
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 3.35 | 0.00 | 01-JAN-00:10 | 16174.26 | 30-MAR-04:30 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 569.98 | 0.00 | 01-JAN-01:20 | 82429.64 | 01-JUL-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 569.98 | 0.00 | 01-JAN-01:20 | 82429.64 | 01-JUL-08:10 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 93.56 | 0.00 | 01-JAN-08:10 | 10178.67 | 17-JUN-08:10 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 0.97 | 0.00 | 01-JAN-08:10 | 2061.24 | 07-DEC-06:00 |
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 0.97 | 0.00 | 01-JAN-08:10 | 2061.24 | 07-DEC-06:00 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 92.60 | 0.00 | 01-JAN-00:10 | 10178.67 | 17-JUN-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 92.60 | 0.00 | 01-JAN-00:10 | 10178.67 | 17-JUN-08:10 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 78.25 | 0.00 | 01-JAN-08:10 | 12134.95 | 01-JUL-08:20 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 2.06 | 0.00 | 01-JAN-08:10 | 2730.27 | 07-DEC-06:00 |
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 2.06 | 0.00 | 01-JAN-08:10 | 2730.27 | 07-DEC-06:00 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 76.20 | 0.00 | 01-JAN-00:10 | 12134.95 | 01-JUL-08:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 76.20 | 0.00 | 01-JAN-00:10 | 12134.95 | 01-JUL-08:20 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 232.06 | 3009.59 | 12-FEB-16:00 | 14665.01 | 28-JUN-18:40 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 232.06 | 3009.59 | 12-FEB-16:00 | 14665.01 | 28-JUN-18:40 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 232.06 | 3009.59 | 12-FEB-16:00 | 14665.01 | 28-JUN-18:40 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 22.99 | 0.00 | 01-JAN-08:10 | 3444.00 | 15-JUN-18:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 0.73 | 0.00 | 01-JAN-08:10 | 814.13 | 07-DEC-06:00 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 0.73 | 0.00 | 01-JAN-08:10 | 814.13 | 07-DEC-06:00 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 22.25 | 0.00 | 01-JAN-00:10 | 3444.00 | 15-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 22.25 | 0.00 | 01-JAN-00:10 | 3444.00 | 15-JUN-18:10 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 19.88 | 0.00 | 01-JAN-08:10 | 3460.28 | 15-JUN-18:20 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 1.31 | 0.00 | 01-JAN-08:10 | 1008.93 | 06-DEC-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 1.31 | 0.00 | 01-JAN-08:10 | 1008.93 | 06-DEC-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 18.58 | 0.00 | 01-JAN-00:10 | 3460.28 | 15-JUN-18:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 18.58 | 0.00 | 01-JAN-00:10 | 3460.28 | 15-JUN-18:20 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 137.81 | 0.00 | 01-JAN-08:10 | 16976.18 | 18-OCT-15:10 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 0.78 | 0.00 | 01-JAN-00:20 | 3568.64 | 06-DEC-23:20 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 0.78 | 0.00 | 01-JAN-00:20 | 3568.64 | 06-DEC-23:20 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 137.03 | 0.00 | 01-JAN-02:40 | 16976.18 | 18-OCT-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 137.03 | 0.00 | 01-JAN-02:40 | 16976.18 | 18-OCT-15:10 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 479.05 | 9011.08 | 07-DEC-10:20 | 24848.18 | 28-JUN-21:20 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 479.05 | 9011.08 | 07-DEC-10:20 | 24848.18 | 28-JUN-21:20 |
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 479.05 | 9011.08 | 07-DEC-10:20 | 24848.18 | 28-JUN-21:20 |
EnergyTransfer:Zone:DINING_FLR_6 | 515.61 | 9953.29 | 07-DEC-10:20 | 26025.66 | 28-JUN-21:20 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 515.61 | 9953.29 | 07-DEC-10:20 | 26025.66 | 28-JUN-21:20 |
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 515.61 | 9953.29 | 07-DEC-10:20 | 26025.66 | 28-JUN-21:20 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 658.42 | 8624.50 | 07-DEC-04:00 | 31493.72 | 13-AUG-10:50 |
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 658.42 | 8624.50 | 07-DEC-04:00 | 31493.72 | 13-AUG-10:50 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 123.23 | 93.32 | 07-DEC-07:10 | 7996.11 | 28-JUN-18:20 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 123.23 | 93.32 | 07-DEC-07:10 | 7996.11 | 28-JUN-18:20 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 123.23 | 93.32 | 07-DEC-07:10 | 7996.11 | 28-JUN-18:20 |
PlantLoopHeatingDemand:Facility | 602.08 | 6712.17 | 25-JUL-02:00 | 47162.69 | 23-JAN-07:20 |
PlantLoopHeatingDemand:Plant | 602.08 | 6712.17 | 25-JUL-02:00 | 47162.69 | 23-JAN-07:20 |
WaterSystems:PlantLoopHeatingDemand | 602.08 | 6712.17 | 25-JUL-02:00 | 47162.69 | 23-JAN-07:20 |
General:WaterSystems:PlantLoopHeatingDemand | 602.08 | 6712.17 | 25-JUL-02:00 | 47162.69 | 23-JAN-07:20 |
EnergyTransfer:HVAC | 6537.70 | 244.71 | 24-MAR-14:20 | 706822.73 | 13-JUL-18:10 |
HeatingCoils:EnergyTransfer | 298.81 | 0.00 | 02-JAN-13:10 | 141230.50 | 08-FEB-07:10 |
CoolingCoils:EnergyTransfer | 5443.55 | 0.00 | 01-JAN-00:30 | 609387.99 | 10-SEP-22:00 |
HeatRecoveryForHeating:EnergyTransfer | 287.88 | 0.00 | 01-JAN-11:10 | 300962.24 | 05-DEC-07:10 |
HeatRecoveryForCooling:EnergyTransfer | 507.45 | 0.00 | 01-JAN-00:10 | 176540.39 | 17-JUN-16:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 602.08 | 6712.17 | 25-JUL-02:00 | 47162.69 | 23-JAN-07:20 |
WaterUse:WaterSystems:EnergyTransfer | 602.08 | 6712.17 | 25-JUL-02:00 | 47162.69 | 23-JAN-07:20 |
Chillers:EnergyTransfer | 5519.10 | 0.00 | 01-JAN-00:30 | 614407.50 | 10-SEP-22:00 |
HeatRejection:EnergyTransfer | 7001.65 | 0.00 | 01-JAN-00:30 | 774117.24 | 10-SEP-22:00 |
General:HeatRejection:EnergyTransfer | 7001.65 | 0.00 | 01-JAN-00:30 | 774117.24 | 10-SEP-22:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:26
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -456.736 | 0.000 | 0.000 | 137.510 | 161.294 | 143.105 | 0.000 | 0.000 | 0.000 | 14.827 | 0.000 | 0.000 | 0.000 | 0.000 | -0.002 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 0.000 | -54.878 | 0.000 | 0.000 | 14.484 | 7.307 | 10.186 | 26.239 | 0.000 | 0.408 | 4.457 | 0.000 | -7.544 | 0.000 | -0.659 | -0.000 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.000 | -41.762 | 0.000 | 0.000 | 16.106 | 8.462 | 11.795 | 0.000 | 0.000 | 0.159 | 5.522 | 0.000 | 0.000 | 0.000 | -0.284 | -0.000 |
MECH_FLR_1 | 0.000 | 0.000 | 0.000 | -34.091 | 0.000 | 0.000 | 3.533 | 8.366 | 12.471 | 0.000 | 0.000 | 0.383 | 9.937 | 0.000 | 0.000 | 0.000 | -0.599 | -0.000 |
STORAGE_FLR_1 | 0.000 | 0.000 | 0.000 | -19.178 | 0.000 | 0.000 | 2.746 | 3.079 | 3.598 | 0.000 | 0.000 | 0.223 | 9.867 | 0.000 | 0.000 | 0.000 | -0.335 | 0.000 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.000 | -618.538 | 0.000 | 0.000 | 11.011 | 3.975 | 658.131 | 0.000 | 0.000 | 0.539 | 0.000 | 0.000 | 0.000 | 0.000 | -0.912 | -54.206 |
CAFE_FLR_1 | 0.000 | 0.000 | 0.000 | -261.980 | 0.000 | 0.000 | 181.212 | 14.206 | 14.341 | 72.899 | 0.000 | 0.900 | 3.341 | 0.000 | -23.251 | 0.000 | -1.668 | -0.001 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.000 | -867.121 | 0.000 | 0.000 | 536.219 | 110.180 | 148.998 | 97.540 | 0.000 | 2.595 | 6.896 | 0.000 | -30.498 | 0.000 | -4.808 | -0.002 |
ROOM_1_FLR_3 | 1.987 | -78.783 | 0.000 | -11.838 | 0.000 | 0.000 | 9.642 | 9.244 | 10.478 | 57.886 | 0.000 | 1.326 | 17.221 | 0.000 | -15.205 | 0.000 | -1.959 | -0.000 |
ROOM_2_FLR_3 | 3.728 | -63.166 | 0.000 | -12.154 | 0.000 | 0.000 | 9.571 | 9.243 | 10.477 | 45.019 | 0.000 | 1.255 | 14.075 | 0.000 | -15.837 | 0.000 | -2.212 | -0.001 |
ROOM_3_MULT19_FLR_3 | 0.000 | -491.364 | 0.000 | -16.271 | 0.000 | 0.000 | 0.000 | 110.385 | 194.997 | 289.317 | 0.000 | 3.088 | 53.946 | 0.000 | -131.211 | 0.000 | -12.888 | -0.003 |
ROOM_4_MULT19_FLR_3 | 8.773 | -412.480 | 0.000 | -162.910 | 0.000 | 0.000 | 182.589 | 110.415 | 195.050 | 141.025 | 0.000 | 7.127 | 34.308 | 0.000 | -83.392 | 0.000 | -20.506 | -0.002 |
ROOM_5_FLR_3 | 1.993 | -81.784 | 0.000 | -11.841 | 0.000 | 0.000 | 9.634 | 9.244 | 10.478 | 59.617 | 0.000 | 1.324 | 17.794 | 0.000 | -14.479 | 0.000 | -1.980 | -0.001 |
ROOM_6_FLR_3 | 3.577 | -65.540 | 0.000 | -12.176 | 0.000 | 0.000 | 9.562 | 9.243 | 10.477 | 46.016 | 0.000 | 1.253 | 14.262 | 0.000 | -14.475 | 0.000 | -2.199 | -0.001 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 0.000 | -232.060 | 0.000 | 0.000 | 112.115 | 91.336 | 0.000 | 51.587 | 0.000 | 1.177 | 0.000 | 0.000 | -20.506 | 0.000 | -1.841 | -1.809 |
ROOM_1_FLR_6 | 1.163 | -19.724 | 0.000 | -2.960 | 0.000 | 0.000 | 2.412 | 2.311 | 2.620 | 14.406 | 0.000 | 0.331 | 3.682 | 0.000 | -3.731 | 0.000 | -0.511 | -0.000 |
ROOM_2_FLR_6 | 1.867 | -16.111 | 0.000 | -3.028 | 0.000 | 0.000 | 2.397 | 2.311 | 2.619 | 11.229 | 0.000 | 0.312 | 2.836 | 0.000 | -3.867 | 0.000 | -0.566 | -0.000 |
ROOM_3_MULT9_FLR_6 | 1.600 | -118.805 | 0.000 | -19.037 | 0.000 | 0.000 | 21.672 | 13.076 | 23.098 | 72.851 | 0.000 | 1.612 | 24.366 | 0.000 | -17.257 | 0.000 | -3.176 | -0.002 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.000 | -479.053 | 0.000 | 0.000 | 314.664 | 31.213 | 175.857 | 13.207 | 0.000 | 0.559 | 0.000 | 0.000 | -12.996 | 0.000 | -1.118 | -42.333 |
DINING_FLR_6 | 0.000 | 0.000 | 0.000 | -515.619 | 0.000 | 0.000 | 314.265 | 31.213 | 175.857 | 12.911 | 0.000 | 0.558 | 0.001 | 0.000 | -13.388 | 0.000 | -1.126 | -4.670 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.000 | -658.400 | 0.000 | 0.000 | 28.061 | 12.972 | 550.372 | 26.182 | 0.000 | 0.499 | 51.358 | 0.000 | -10.039 | 0.000 | -1.006 | -0.001 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 0.000 | -123.231 | 0.000 | 0.000 | 29.788 | 24.166 | 0.000 | 24.387 | 0.000 | 0.501 | 54.405 | 0.000 | -9.215 | 0.000 | -0.803 | -0.000 |
Total Facility | 24.688 | -1347.758 | 0.000 | -4614.860 | 0.000 | 0.000 | 1949.194 | 783.243 | 2365.005 | 1062.318 | 0.000 | 26.130 | 343.101 | 0.000 | -426.888 | 0.000 | -61.153 | -103.035 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 08-SEP-21:00 | 0.00 | 0.00 | 0.00 | -26077.30 | 0.00 | 0.00 | 5924.43 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -697.35 |
RETAIL_1_FLR_1 | 02-OCT-12:40 | 0.00 | 0.00 | 0.00 | -3908.37 | 0.00 | 0.00 | 150.59 | 166.00 | 252.59 | 4203.44 | 0.00 | 46.36 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -910.61 |
RETAIL_2_FLR_1 | 28-JUN-21:00 | 0.00 | 0.00 | 0.00 | -2559.04 | 0.00 | 0.00 | 697.62 | 615.12 | 752.15 | 0.00 | 0.00 | 19.55 | 474.61 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 28-JUN-20:00 | 0.00 | 0.00 | 0.00 | -2446.21 | 0.00 | 0.00 | 129.09 | 684.18 | 839.45 | 0.00 | 0.00 | 54.25 | 739.25 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 28-JUN-19:10 | 0.00 | 0.00 | 0.00 | -1284.67 | 0.00 | 0.00 | 99.30 | 251.84 | 242.16 | 0.00 | 0.00 | 37.06 | 654.32 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 28-JUN-20:00 | 0.00 | 0.00 | 0.00 | -39828.15 | 0.00 | 0.00 | 408.91 | 325.08 | 44299.38 | 0.00 | 0.00 | 74.08 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5279.30 |
CAFE_FLR_1 | 01-NOV-15:03 | 0.00 | 0.00 | 0.00 | -14195.24 | 0.00 | 0.00 | 4947.96 | 103.98 | 355.63 | 10365.48 | 0.00 | 50.32 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1628.13 |
LOBBY_FLR_1 | 28-JUN-21:10 | 0.00 | 0.00 | 0.00 | -46471.12 | 0.00 | 0.00 | 26440.55 | 6336.53 | 7389.94 | 1312.18 | 0.00 | 310.56 | 4681.35 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 15-JUN-15:01 | 0.00 | -17031.90 | 0.00 | -662.25 | 0.00 | 0.00 | 235.29 | 199.23 | 200.18 | 8382.10 | 0.00 | 194.59 | 8482.76 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 01-JUL-08:61 | 0.00 | -19152.08 | 0.00 | -803.96 | 0.00 | 0.00 | 109.82 | 398.41 | 653.15 | 1157.73 | 0.00 | 31.96 | 17604.98 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 20-NOV-14:30 | 0.00 | -48602.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2378.94 | 2352.88 | 54712.65 | 0.00 | 16.76 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -10858.95 |
ROOM_4_MULT19_FLR_3 | 01-JUL-08:61 | 0.00 | -118510.64 | 0.00 | -10591.34 | 0.00 | 0.00 | 2232.93 | 4759.18 | 12159.85 | 8737.37 | 0.00 | 187.89 | 101024.76 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 01-JUL-08:61 | 0.00 | -15351.03 | 0.00 | -677.31 | 0.00 | 0.00 | 130.71 | 398.46 | 653.23 | 7039.09 | 0.00 | 52.37 | 7754.49 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 21-MAY-08:61 | 0.00 | -18698.46 | 0.00 | -931.75 | 0.00 | 0.00 | 88.26 | 398.41 | 653.15 | 7260.54 | 0.00 | 0.00 | 11241.99 | 0.00 | -0.00 | 0.00 | -12.13 | 0.00 |
CORRIDOR_FLR_3 | 28-JUN-18:40 | 0.00 | 0.00 | 0.00 | -14663.92 | 0.00 | 0.00 | 4080.38 | 6639.35 | 0.00 | 4176.66 | 0.00 | 207.24 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -439.71 |
ROOM_1_FLR_6 | 15-JUN-15:01 | 0.00 | -4521.25 | 0.00 | -165.79 | 0.00 | 0.00 | 58.81 | 49.81 | 50.05 | 2079.21 | 0.00 | 48.47 | 2400.69 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 01-JUL-08:61 | 0.00 | -4979.76 | 0.00 | -195.55 | 0.00 | 0.00 | 28.08 | 99.60 | 163.29 | 298.75 | 0.00 | 8.70 | 4576.89 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 18-OCT-15:01 | 0.00 | -20270.54 | 0.00 | -1087.00 | 0.00 | 0.00 | 529.39 | 281.79 | 441.28 | 8214.86 | 0.00 | 90.79 | 11799.42 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 28-JUN-21:20 | 0.00 | 0.00 | 0.00 | -24848.28 | 0.00 | 0.00 | 15620.74 | 1992.02 | 6747.90 | 532.54 | 0.00 | 66.92 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -111.85 |
DINING_FLR_6 | 28-JUN-21:20 | 0.00 | 0.00 | 0.00 | -26025.84 | 0.00 | 0.00 | 15616.96 | 1992.02 | 6747.90 | 517.38 | 0.00 | 66.91 | 1084.67 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 13-AUG-10:50 | 0.00 | 0.00 | 0.00 | -31496.24 | 0.00 | 0.00 | 460.59 | 353.60 | 24259.91 | 3044.36 | 0.00 | 56.87 | 3320.92 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 28-JUN-18:13 | 0.00 | 0.00 | 0.00 | -7996.04 | 0.00 | 0.00 | 1079.60 | 1756.68 | 0.00 | 1822.94 | 0.00 | 93.13 | 3243.69 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 01-JUL-18:01 | 0.00 | -228978.57 | 0.00 | -205082.21 | 0.00 | 0.00 | 63277.32 | 51400.13 | 113378.48 | 68167.85 | 0.00 | 3199.04 | 134637.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 16-DEC-07:20 | 0.00 | 0.00 | 42.64 | 0.00 | 0.00 | 0.00 | 447.54 | 199.20 | 288.68 | 0.00 | 0.00 | 0.00 | 236.44 | 0.00 | -1113.51 | 0.00 | -100.98 | 0.00 |
RETAIL_2_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 02-FEB-19:03 | 5488.69 | 378.81 | 0.00 | -378.81 | 0.00 | 0.00 | 350.02 | 633.26 | 484.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1792.71 | 0.00 | -119.35 | -5044.57 |
ROOM_2_FLR_3 | 05-DEC-16:03 | 5564.84 | 390.72 | 0.00 | -390.72 | 0.00 | 0.00 | 242.08 | 199.20 | 200.16 | 1380.57 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -595.94 | -6990.92 |
ROOM_3_MULT19_FLR_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 11-MAR-16:04 | 29280.12 | 5340.84 | 0.00 | -5340.84 | 0.00 | 0.00 | 2540.92 | 2804.51 | 4118.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -223.13 | 0.00 | -16829.65 | -21691.44 |
ROOM_5_FLR_3 | 05-DEC-09:03 | 5254.07 | 383.98 | 0.00 | -383.98 | 0.00 | 0.00 | 90.67 | 313.07 | 453.05 | 2850.52 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -163.36 | -8798.01 |
ROOM_6_FLR_3 | 26-MAR-15:03 | 5280.37 | 446.17 | 0.00 | -446.17 | 0.00 | 0.00 | 136.51 | 234.78 | 221.23 | 285.41 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -317.37 | -5840.93 |
CORRIDOR_FLR_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 01-DEC-19:03 | 1641.32 | 95.63 | 0.00 | -95.63 | 0.00 | 0.00 | 87.34 | 158.32 | 121.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -420.29 | 0.00 | -27.09 | -1560.75 |
ROOM_2_FLR_6 | 26-APR-21:53 | 1627.93 | 100.75 | 0.00 | -100.75 | 0.00 | 0.00 | 102.42 | 119.17 | 89.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -351.82 | 0.00 | -14.91 | -1572.33 |
ROOM_3_MULT9_FLR_6 | 07-FEB-16:04 | 7409.86 | 647.84 | 0.00 | -647.84 | 0.00 | 0.00 | 529.39 | 281.79 | 441.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -466.76 | 0.00 | -1568.98 | -6626.59 |
BANQUET_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 02-FEB-19:03 | -128381.63 | 157795.60 | 0.00 | -157795.60 | 0.00 | 0.00 | 76233.70 | 57474.69 | 120482.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -44625.31 | 0.00 | -3601.92 | -77581.96 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:26
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV WITH REHEAT | 24.4982 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 24.3664 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV WITH REHEAT | 12.2491 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 11.6611 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.6520 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.0400 | 0.000610 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.000000 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.000000 | 142.3000 | 0.003581 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.000000 | 422.4350 | 0.001448 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 83.8280 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003556 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.1800 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 | |
VAV WITH REHEAT | 0.00 | 0.001045 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8876 | 2.8876 | 1.3745 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3671 | 0.3671 | 0.1747 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2665 | 0.2665 | 0.1268 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2404 | 0.2404 | 0.1144 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1438 | 0.1438 | 0.0684 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.6138 | 3.6138 | 1.7202 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5573 | 1.5573 | 0.7413 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.2988 | 5.2988 | 2.5223 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7428 | 1.7428 | 0.8296 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.4495 | 2.4495 | 1.1659 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.5634 | 2.5634 | 1.2202 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.4853 | 2.4853 | 1.1830 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8819 | 0.8819 | 0.4198 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
VAV WITH REHEAT | 24.4982 | 24.3664 | 24.4982 | 11.6611 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4438 | 1.4438 | 1.3745 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1835 | 0.1835 | 0.1747 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1332 | 0.1332 | 0.1268 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1202 | 0.1202 | 0.1144 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0719 | 0.0719 | 0.0684 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8069 | 1.8069 | 1.7202 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7786 | 0.7786 | 0.7413 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6494 | 2.6494 | 2.5223 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8714 | 0.8714 | 0.8296 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2247 | 1.2247 | 1.1659 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2817 | 1.2817 | 1.2202 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2426 | 1.2426 | 1.1830 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4410 | 0.4410 | 0.4198 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
VAV WITH REHEAT | 12.2491 | 11.6611 | 11.6611 | 11.6611 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:26
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 168.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 168.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 86.83 |
Number of hours not met | 86.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 298.81 | 141230.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 1482.55 | 192789.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 783.24 | 64632.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 194.06 | 12338.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 872.72 | 59188.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 14.43 | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 8.99 | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.20 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 21.77 | 1291.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 789.09 | 48128.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 2.91 | 188.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 585.27 | 47693.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 90.87 | 4332.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 149.74 | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 94.78 | 4751.13 | 2216.54 | 222242.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.09 | 2093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 20.48 | 1893.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 34.17 | 1202.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1719.91 | 6213.01 |
Natural Gas | 1788.84 | 4005.38 |
Additional | 0.00 | 0.00 |
Total | 3508.75 | 10218.40 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 69.04 |
Space Heating | 26.34 |
Space Cooling | 130.68 |
Fans (All) | 51.59 |
Service Water Heating | 8.35 |
Receptacle Equipment | 146.16 |
Miscellaneous (All) | 547.63 |
Subtotal | 547.63 |
Natural Gas [MJ/m2] | |
Space Heating | 0.00 |
Service Water Heating | 195.37 |
Miscellaneous (All) | 353.04 |
Subtotal | 353.04 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 7.67 |
Space Heating | 2.92 |
Space Cooling | 14.51 |
Fans (All) | 5.73 |
Service Water Heating | 22.62 |
Receptacle Equipment | 33.73 |
Miscellaneous | 12.82 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 486. | 5110. |
ELEVATOR_STANDBY_SCH | 7671. | 8760. |
LTG_SCH_KITCHEN | 3061. | 8760. |
LTG_SCH_DINING | 3061. | 8760. |
LTG_SCH_BASEMENT | 2572. | 8760. |
LTG_SCH_LOBBY | 2295. | 8760. |
LTG_SCH_STORAGE | 1580. | 8760. |
LTG_SCH_MECHANIC | 3061. | 8760. |
LTG_SCH_LAUNDRY | 3061. | 8760. |
LTG_SCH_GUESTROOM | 1980. | 8760. |
LTG_SCH_CORRIDOR | 2295. | 8760. |
LTG_SCH_RETAIL | 2678. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 1591. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3737. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 5740. | 6205. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 8760. | 8760. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 26.67 | 365 | 26.67 | 365 |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
HTGSETP_SCH | BASEMENT DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:26
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8745.33 | 14.67 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8755.17 | 4.83 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8745.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 14.67 | 0.00 | 0.00 | 0.00 |
Average | 8759.11 | 0.89 | 0.00 | 0.00 | 0.00 |
Sum | 192700.50 | 19.50 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108269.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 288887.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 6355515.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8744.00 | 16.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8164.50 | 595.50 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8287.33 | 472.67 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8749.83 | 10.17 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8718.50 | 41.50 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8756.00 | 4.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8729.00 | 31.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8759.67 | 0.33 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8747.67 | 12.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8251.50 | 508.50 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8292.33 | 467.67 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8734.33 | 25.67 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8164.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 595.50 | 0.00 | 0.00 | 0.00 |
Average | 8660.67 | 99.33 | 0.00 | 0.00 | 0.00 |
Sum | 190534.67 | 2185.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 58981.50 | 174.50 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 640159.17 | 70257.83 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 1948890.50 | 166538.50 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4151.83 | 2.17 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4152.67 | 1.33 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4151.83 | 2.17 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100352.00 | 6.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4150.67 | 3.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1139431.83 | 106283.17 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1147011.83 | 98703.17 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108090.50 | 178.50 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 1948890.50 | 166538.50 | 0.00 | 0.00 | 0.00 |
Average | 268789.29 | 20097.76 | 0.00 | 0.00 | 0.00 |
Sum | 5913364.33 | 442150.67 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:26
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:26
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 1592.73 | 0.00 | 0.00 |
Sum | 0.00 | 35040.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 710417.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 2115429.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 2115429.00 | 0.00 | 0.00 |
Average | 0.00 | 241694.36 | 0.00 | 0.00 |
Sum | 0.00 | 5317276.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2B
For: Environment
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Environment
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AZ_TUCSON
For: Environment
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.366439E+11 | 19725.67 | 19-JAN-22:00 | 15.00 | 6.90 | 0.814620E+10 | 4839.75 | 09-JAN-22:19 | 15.00 | 6.90 |
February | 0.290548E+11 | 17888.13 | 01-FEB-21:50 | 10.17 | 5.40 | 0.699705E+10 | 4837.93 | 01-FEB-01:10 | 10.17 | 5.40 |
March | 0.300462E+11 | 13688.31 | 01-MAR-21:00 | 15.50 | 11.31 | 0.736846E+10 | 4715.77 | 01-MAR-22:10 | 14.30 | 10.92 |
April | 0.313482E+11 | 15040.94 | 30-APR-10:33 | 30.00 | 11.09 | 0.733734E+10 | 4734.51 | 21-APR-22:10 | 30.00 | 11.09 |
May | 0.315396E+11 | 14630.72 | 07-MAY-10:33 | 30.00 | 12.89 | 0.737232E+10 | 4654.28 | 01-MAY-22:10 | 30.00 | 12.89 |
June | 0.325402E+11 | 15651.30 | 28-JUN-18:10 | 40.83 | 17.83 | 0.734865E+10 | 4706.56 | 23-JUN-21:19 | 40.83 | 17.83 |
July | 0.394906E+11 | 21203.12 | 14-JUL-21:00 | 28.00 | 20.32 | 0.814188E+10 | 4837.16 | 07-JUL-22:10 | 28.00 | 20.32 |
August | 0.431995E+11 | 23228.56 | 04-AUG-21:00 | 23.00 | 18.90 | 0.823649E+10 | 4837.10 | 21-AUG-00:20 | 26.00 | 16.49 |
September | 0.468920E+11 | 26076.76 | 08-SEP-21:00 | 32.20 | 19.39 | 0.797524E+10 | 4837.16 | 15-SEP-03:09 | 19.90 | 14.65 |
October | 0.473933E+11 | 25705.87 | 05-OCT-21:00 | 24.00 | 13.11 | 0.823501E+10 | 4839.63 | 30-OCT-00:00 | 12.00 | 6.98 |
November | 0.448728E+11 | 25364.26 | 01-NOV-21:00 | 18.00 | 13.11 | 0.796291E+10 | 4840.10 | 15-NOV-01:39 | 12.00 | 12.00 |
December | 0.437127E+11 | 24551.44 | 01-DEC-22:00 | 10.00 | 4.18 | 0.822943E+10 | 4840.10 | 27-DEC-23:49 | 11.18 | 5.51 |
Annual Sum or Average | 0.456734E+12 | 0.933510E+11 | ||||||||
Minimum of Months | 0.290548E+11 | 13688.31 | 10.00 | 4.18 | 0.699705E+10 | 4654.28 | 10.17 | 5.40 | ||
Maximum of Months | 0.473933E+11 | 26076.76 | 40.83 | 20.32 | 0.823649E+10 | 4840.10 | 40.83 | 20.32 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.449978E+10 | 3662.57 | 14-JAN-13:40 | 26.67 | 10.98 | 0.727480E+09 | 476.43 | 19-JAN-22:19 | 14.33 | 6.76 |
February | 0.289822E+10 | 2749.10 | 01-FEB-14:00 | 16.00 | 7.74 | 0.606407E+09 | 447.01 | 01-FEB-00:10 | 16.00 | 7.74 |
March | 0.341343E+10 | 2782.21 | 18-MAR-13:40 | 26.27 | 12.12 | 0.693681E+09 | 488.40 | 16-MAR-21:30 | 26.27 | 12.12 |
April | 0.456412E+10 | 3073.04 | 14-APR-14:10 | 34.17 | 14.15 | 0.760132E+09 | 491.84 | 12-APR-23:19 | 34.17 | 14.15 |
May | 0.469336E+10 | 2567.70 | 31-MAY-18:15 | 35.33 | 13.34 | 0.798440E+09 | 491.85 | 10-MAY-23:10 | 35.33 | 13.34 |
June | 0.544521E+10 | 3372.08 | 28-JUN-18:17 | 40.67 | 17.68 | 0.801888E+09 | 491.85 | 09-JUN-23:19 | 40.67 | 17.68 |
July | 0.542487E+10 | 3129.00 | 21-JUL-18:30 | 38.00 | 19.28 | 0.824197E+09 | 491.85 | 01-JUL-00:10 | 38.00 | 19.28 |
August | 0.560623E+10 | 3578.32 | 28-AUG-12:30 | 37.00 | 20.85 | 0.824361E+09 | 491.84 | 04-AUG-22:10 | 37.00 | 20.85 |
September | 0.540410E+10 | 3874.65 | 28-SEP-13:30 | 36.10 | 16.03 | 0.791814E+09 | 491.83 | 20-SEP-21:19 | 36.10 | 16.03 |
October | 0.498701E+10 | 3908.28 | 02-OCT-12:40 | 34.00 | 19.29 | 0.771351E+09 | 491.86 | 19-OCT-21:00 | 20.00 | 11.28 |
November | 0.420438E+10 | 3848.67 | 21-NOV-13:30 | 25.00 | 10.74 | 0.700744E+09 | 491.84 | 01-NOV-22:10 | 25.00 | 10.74 |
December | 0.373704E+10 | 3552.58 | 25-DEC-13:00 | 25.00 | 11.61 | 0.689642E+09 | 472.65 | 26-DEC-22:19 | 14.67 | 7.12 |
Annual Sum or Average | 0.548777E+11 | 0.899014E+10 | ||||||||
Minimum of Months | 0.289822E+10 | 2567.70 | 16.00 | 7.74 | 0.606407E+09 | 447.01 | 14.33 | 6.76 | ||
Maximum of Months | 0.560623E+10 | 3908.28 | 40.67 | 20.85 | 0.824361E+09 | 491.86 | 40.67 | 20.85 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.310180E+10 | 1751.18 | 27-JAN-21:10 | 16.17 | 6.63 | 0.925110E+09 | 569.93 | 09-JAN-22:19 | 16.17 | 6.63 |
February | 0.255629E+10 | 1538.20 | 01-FEB-21:50 | 10.17 | 5.40 | 0.800283E+09 | 569.61 | 01-FEB-00:40 | 10.17 | 5.40 |
March | 0.295973E+10 | 1789.92 | 17-MAR-21:00 | 21.60 | 12.64 | 0.908615E+09 | 569.87 | 22-MAR-22:30 | 11.65 | 6.51 |
April | 0.354253E+10 | 2284.32 | 14-APR-21:00 | 29.00 | 13.30 | 0.927148E+09 | 569.56 | 16-APR-23:10 | 18.83 | 12.52 |
May | 0.382957E+10 | 2231.33 | 31-MAY-21:00 | 29.00 | 11.22 | 0.963115E+09 | 569.56 | 10-MAY-23:19 | 29.00 | 11.22 |
June | 0.419005E+10 | 2559.28 | 28-JUN-21:00 | 35.00 | 14.57 | 0.939047E+09 | 569.56 | 09-JUN-23:19 | 35.00 | 14.57 |
July | 0.415623E+10 | 2420.35 | 20-JUL-20:10 | 35.17 | 18.52 | 0.965449E+09 | 569.55 | 01-JUL-00:10 | 35.17 | 18.52 |
August | 0.414260E+10 | 2461.97 | 15-AUG-20:10 | 34.67 | 18.05 | 0.969259E+09 | 569.55 | 04-AUG-22:10 | 34.67 | 18.05 |
September | 0.385200E+10 | 2424.28 | 07-SEP-21:00 | 33.30 | 19.43 | 0.935001E+09 | 569.55 | 21-SEP-22:10 | 20.92 | 16.58 |
October | 0.350861E+10 | 2265.04 | 05-OCT-20:10 | 26.50 | 13.28 | 0.948839E+09 | 569.57 | 19-OCT-21:00 | 20.00 | 11.28 |
November | 0.303298E+10 | 1994.06 | 01-NOV-20:10 | 20.50 | 13.68 | 0.897715E+09 | 569.55 | 02-NOV-22:10 | 19.83 | 16.01 |
December | 0.288879E+10 | 1667.30 | 26-DEC-22:00 | 15.00 | 7.29 | 0.897526E+09 | 569.91 | 27-DEC-23:49 | 11.18 | 5.51 |
Annual Sum or Average | 0.417612E+11 | 0.110771E+11 | ||||||||
Minimum of Months | 0.255629E+10 | 1538.20 | 10.17 | 5.40 | 0.800283E+09 | 569.55 | 10.17 | 5.40 | ||
Maximum of Months | 0.419005E+10 | 2559.28 | 35.17 | 19.43 | 0.969259E+09 | 569.93 | 35.17 | 18.52 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.230065E+10 | 1098.48 | 08-JAN-11:33 | 20.33 | 13.54 | 0.172360E+09 | 110.42 | 27-JAN-22:10 | 11.83 | 4.49 |
February | 0.196462E+10 | 1021.37 | 18-FEB-11:33 | 19.33 | 14.12 | 0.150422E+09 | 106.65 | 01-FEB-00:10 | 19.33 | 14.12 |
March | 0.230432E+10 | 1147.81 | 18-MAR-10:33 | 23.83 | 14.74 | 0.172943E+09 | 114.10 | 17-MAR-21:19 | 23.83 | 14.74 |
April | 0.271407E+10 | 1569.75 | 25-APR-21:00 | 27.00 | 14.17 | 0.187134E+09 | 120.46 | 11-APR-22:10 | 27.00 | 14.17 |
May | 0.310164E+10 | 1796.60 | 18-MAY-20:00 | 30.00 | 12.86 | 0.201291E+09 | 120.46 | 10-MAY-23:30 | 30.00 | 12.86 |
June | 0.382062E+10 | 2446.56 | 28-JUN-20:00 | 37.00 | 15.57 | 0.199030E+09 | 120.46 | 09-JUN-23:49 | 37.00 | 15.57 |
July | 0.381570E+10 | 2334.06 | 21-JUL-20:00 | 37.00 | 20.84 | 0.204650E+09 | 120.46 | 07-JUL-22:10 | 37.00 | 20.84 |
August | 0.361071E+10 | 2220.63 | 15-AUG-20:00 | 35.00 | 18.06 | 0.204942E+09 | 120.46 | 30-AUG-21:19 | 31.67 | 17.46 |
September | 0.325070E+10 | 2105.24 | 08-SEP-20:00 | 33.80 | 19.77 | 0.197137E+09 | 120.46 | 20-SEP-21:19 | 27.20 | 17.73 |
October | 0.276875E+10 | 1951.31 | 02-OCT-20:00 | 27.00 | 20.01 | 0.190108E+09 | 120.46 | 06-OCT-22:10 | 26.00 | 14.45 |
November | 0.230865E+10 | 1175.67 | 02-NOV-18:04 | 23.67 | 15.30 | 0.170516E+09 | 115.91 | 02-NOV-21:19 | 20.00 | 15.69 |
December | 0.213059E+10 | 1049.76 | 25-DEC-11:33 | 22.33 | 10.13 | 0.165259E+09 | 107.85 | 26-DEC-22:19 | 14.67 | 7.12 |
Annual Sum or Average | 0.340910E+11 | 0.221579E+10 | ||||||||
Minimum of Months | 0.196462E+10 | 1021.37 | 19.33 | 10.13 | 0.150422E+09 | 106.65 | 11.83 | 4.49 | ||
Maximum of Months | 0.382062E+10 | 2446.56 | 37.00 | 20.84 | 0.204942E+09 | 120.46 | 37.00 | 20.84 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.132616E+10 | 647.47 | 08-JAN-11:33 | 20.33 | 13.54 | 0.129362E+09 | 81.37 | 27-JAN-22:40 | 11.33 | 4.24 |
February | 0.113038E+10 | 602.05 | 18-FEB-11:33 | 19.33 | 14.12 | 0.112586E+09 | 79.73 | 01-FEB-00:10 | 19.33 | 14.12 |
March | 0.132846E+10 | 676.32 | 18-MAR-10:33 | 23.83 | 14.74 | 0.129550E+09 | 84.63 | 17-MAR-21:40 | 23.83 | 14.74 |
April | 0.157047E+10 | 792.99 | 15-APR-10:33 | 28.00 | 13.04 | 0.140608E+09 | 92.54 | 14-APR-21:49 | 28.00 | 13.04 |
May | 0.174624E+10 | 812.58 | 09-MAY-21:00 | 29.00 | 12.81 | 0.152286E+09 | 92.66 | 11-MAY-21:19 | 25.67 | 12.70 |
June | 0.209208E+10 | 1284.83 | 28-JUN-19:10 | 39.50 | 16.83 | 0.152885E+09 | 92.66 | 09-JUN-23:49 | 39.50 | 16.83 |
July | 0.208654E+10 | 1188.33 | 21-JUL-19:10 | 37.83 | 19.56 | 0.157140E+09 | 92.66 | 07-JUL-22:10 | 37.83 | 19.56 |
August | 0.197708E+10 | 1102.21 | 15-AUG-20:00 | 35.00 | 18.06 | 0.156970E+09 | 92.66 | 27-AUG-23:49 | 30.17 | 17.39 |
September | 0.179290E+10 | 1033.23 | 08-SEP-20:00 | 33.80 | 19.77 | 0.150365E+09 | 92.66 | 20-SEP-21:19 | 27.20 | 17.73 |
October | 0.158256E+10 | 901.01 | 02-OCT-19:50 | 27.50 | 19.95 | 0.142964E+09 | 92.66 | 06-OCT-22:10 | 26.00 | 14.45 |
November | 0.133446E+10 | 681.81 | 02-NOV-18:04 | 23.67 | 15.30 | 0.127693E+09 | 85.88 | 02-NOV-22:10 | 19.83 | 16.01 |
December | 0.121031E+10 | 620.58 | 25-DEC-11:33 | 22.33 | 10.13 | 0.123912E+09 | 79.82 | 26-DEC-22:40 | 14.33 | 6.96 |
Annual Sum or Average | 0.191776E+11 | 0.167632E+10 | ||||||||
Minimum of Months | 0.113038E+10 | 602.05 | 19.33 | 10.13 | 0.112586E+09 | 79.73 | 11.33 | 4.24 | ||
Maximum of Months | 0.209208E+10 | 1284.83 | 39.50 | 19.95 | 0.157140E+09 | 92.66 | 39.50 | 19.56 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.507070E+11 | 37958.52 | 27-JAN-21:00 | 17.00 | 6.99 | 0.606244E+09 | 383.39 | 09-JAN-22:19 | 17.00 | 6.99 |
February | 0.452570E+11 | 37642.99 | 22-FEB-21:00 | 13.00 | 10.72 | 0.545746E+09 | 383.00 | 10-FEB-23:30 | 13.00 | 10.72 |
March | 0.509169E+11 | 38275.97 | 16-MAR-20:00 | 22.20 | 12.56 | 0.607639E+09 | 382.97 | 24-MAR-21:40 | 11.97 | 4.05 |
April | 0.513938E+11 | 39118.82 | 14-APR-20:00 | 31.00 | 13.66 | 0.593719E+09 | 381.77 | 05-APR-21:10 | 31.00 | 13.66 |
May | 0.538992E+11 | 39243.33 | 18-MAY-20:00 | 30.00 | 12.86 | 0.615938E+09 | 381.78 | 09-MAY-21:10 | 30.00 | 12.86 |
June | 0.534632E+11 | 39834.47 | 28-JUN-20:00 | 37.00 | 15.57 | 0.599190E+09 | 381.87 | 23-JUN-21:10 | 37.00 | 15.57 |
July | 0.546375E+11 | 39665.71 | 21-JUL-20:00 | 37.00 | 20.84 | 0.615993E+09 | 381.86 | 07-JUL-21:10 | 37.00 | 20.84 |
August | 0.546569E+11 | 39576.39 | 15-AUG-20:00 | 35.00 | 18.06 | 0.616651E+09 | 382.23 | 09-AUG-21:10 | 35.00 | 18.06 |
September | 0.521304E+11 | 39428.28 | 08-SEP-20:00 | 33.80 | 19.77 | 0.594423E+09 | 381.90 | 19-SEP-21:10 | 28.02 | 15.82 |
October | 0.523205E+11 | 39067.59 | 03-OCT-20:00 | 30.00 | 18.25 | 0.611027E+09 | 381.85 | 06-OCT-21:10 | 26.00 | 13.09 |
November | 0.492932E+11 | 38240.66 | 01-NOV-20:00 | 21.00 | 13.76 | 0.587178E+09 | 384.88 | 29-NOV-22:10 | 10.00 | 3.82 |
December | 0.498579E+11 | 37707.75 | 22-DEC-21:00 | 14.00 | 5.51 | 0.604160E+09 | 383.11 | 27-DEC-23:49 | 11.18 | 5.51 |
Annual Sum or Average | 0.618533E+12 | 0.719791E+10 | ||||||||
Minimum of Months | 0.452570E+11 | 37642.99 | 13.00 | 5.51 | 0.545746E+09 | 381.77 | 10.00 | 3.82 | ||
Maximum of Months | 0.546569E+11 | 39834.47 | 37.00 | 20.84 | 0.616651E+09 | 384.88 | 37.00 | 20.84 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.219553E+11 | 13947.29 | 14-JAN-13:30 | 26.50 | 10.97 | 0.108002E+11 | 6470.64 | 09-JAN-22:19 | 26.50 | 10.97 |
February | 0.163074E+11 | 10753.19 | 25-FEB-14:25 | 17.50 | 9.25 | 0.940356E+10 | 6468.88 | 17-FEB-00:00 | 17.50 | 9.25 |
March | 0.183974E+11 | 10876.85 | 18-MAR-13:30 | 26.35 | 12.25 | 0.105643E+11 | 6470.65 | 20-MAR-00:40 | 12.37 | 8.39 |
April | 0.215413E+11 | 12108.70 | 14-APR-21:10 | 28.67 | 13.19 | 0.105467E+11 | 6468.96 | 22-APR-02:20 | 12.67 | 2.64 |
May | 0.221382E+11 | 11662.37 | 09-MAY-21:10 | 28.83 | 12.76 | 0.109021E+11 | 6461.96 | 31-MAY-04:19 | 19.00 | 9.54 |
June | 0.239542E+11 | 13171.69 | 28-JUN-21:10 | 34.67 | 14.46 | 0.106309E+11 | 6462.28 | 05-JUN-04:19 | 34.67 | 14.46 |
July | 0.244957E+11 | 13080.84 | 21-JUL-21:10 | 33.83 | 20.81 | 0.109469E+11 | 6462.03 | 07-JUL-04:19 | 33.83 | 20.81 |
August | 0.250910E+11 | 12970.75 | 15-AUG-21:10 | 32.67 | 17.73 | 0.109929E+11 | 6462.69 | 04-AUG-22:10 | 32.67 | 17.73 |
September | 0.243470E+11 | 13748.80 | 28-SEP-15:03 | 37.52 | 15.49 | 0.106154E+11 | 6462.64 | 21-SEP-22:10 | 37.52 | 15.49 |
October | 0.233353E+11 | 13737.85 | 05-OCT-15:03 | 34.00 | 15.75 | 0.108804E+11 | 6470.15 | 27-OCT-04:10 | 12.83 | 4.70 |
November | 0.205935E+11 | 14194.21 | 01-NOV-15:03 | 28.83 | 16.12 | 0.104085E+11 | 6472.61 | 15-NOV-01:39 | 12.00 | 12.00 |
December | 0.198212E+11 | 13500.71 | 25-DEC-13:00 | 25.00 | 11.61 | 0.105642E+11 | 6471.21 | 27-DEC-23:49 | 11.18 | 5.51 |
Annual Sum or Average | 0.261978E+12 | 0.127256E+12 | ||||||||
Minimum of Months | 0.163074E+11 | 10753.19 | 17.50 | 9.25 | 0.940356E+10 | 6461.96 | 11.18 | 2.64 | ||
Maximum of Months | 0.250910E+11 | 14194.21 | 37.52 | 20.81 | 0.109929E+11 | 6472.61 | 37.52 | 20.81 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.672139E+11 | 36330.87 | 17-JAN-19:04 | 17.83 | 6.84 | 0.321786E+11 | 19202.58 | 09-JAN-22:19 | 17.83 | 6.84 |
February | 0.553241E+11 | 33086.65 | 01-FEB-22:10 | 9.67 | 5.16 | 0.283522E+11 | 19199.34 | 10-FEB-23:30 | 13.00 | 11.83 |
March | 0.633384E+11 | 36548.48 | 17-MAR-21:10 | 21.42 | 12.50 | 0.317482E+11 | 19201.63 | 20-MAR-00:40 | 12.37 | 8.39 |
April | 0.720645E+11 | 42093.26 | 14-APR-21:10 | 28.67 | 13.19 | 0.313262E+11 | 19198.72 | 22-APR-02:20 | 12.67 | 2.64 |
May | 0.770328E+11 | 41525.00 | 09-MAY-21:10 | 28.83 | 12.76 | 0.324075E+11 | 19185.56 | 26-MAY-03:09 | 21.00 | 13.54 |
June | 0.821188E+11 | 46472.96 | 28-JUN-21:10 | 34.67 | 14.46 | 0.315766E+11 | 19186.01 | 05-JUN-04:19 | 34.67 | 14.46 |
July | 0.838533E+11 | 45750.12 | 21-JUL-21:10 | 33.83 | 20.81 | 0.324985E+11 | 19185.36 | 07-JUL-04:19 | 33.83 | 20.81 |
August | 0.837529E+11 | 45362.57 | 15-AUG-21:10 | 32.67 | 17.73 | 0.326578E+11 | 19186.12 | 04-AUG-22:10 | 32.67 | 17.73 |
September | 0.797789E+11 | 45348.25 | 07-SEP-21:10 | 32.75 | 19.42 | 0.315361E+11 | 19186.06 | 21-SEP-22:10 | 20.92 | 16.58 |
October | 0.744641E+11 | 43553.18 | 03-OCT-21:10 | 29.50 | 18.57 | 0.324059E+11 | 19199.50 | 30-OCT-00:00 | 12.00 | 6.98 |
November | 0.653400E+11 | 38948.03 | 01-NOV-20:10 | 20.50 | 13.68 | 0.311159E+11 | 19203.35 | 15-NOV-01:39 | 12.00 | 12.00 |
December | 0.628314E+11 | 35487.53 | 26-DEC-22:10 | 14.83 | 7.20 | 0.317039E+11 | 19202.75 | 27-DEC-23:49 | 11.18 | 5.51 |
Annual Sum or Average | 0.867113E+12 | 0.379507E+12 | ||||||||
Minimum of Months | 0.553241E+11 | 33086.65 | 9.67 | 5.16 | 0.283522E+11 | 19185.36 | 11.18 | 2.64 | ||
Maximum of Months | 0.838533E+11 | 46472.96 | 34.67 | 20.81 | 0.326578E+11 | 19203.35 | 34.67 | 20.81 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.104197E+10 | 4379.34 | 24-JAN-16:01 | 24.83 | 10.77 | 98433145.08 | 56.69 | 10-JAN-22:10 | 24.83 | 10.77 |
February | 0.427507E+09 | 4276.61 | 03-FEB-16:01 | 16.83 | 7.75 | 87922802.53 | 56.69 | 21-FEB-22:10 | 14.00 | 12.80 |
March | 0.845577E+09 | 4313.94 | 31-MAR-15:01 | 22.80 | 8.55 | 98187460.72 | 59.47 | 28-MAR-23:00 | 22.80 | 8.55 |
April | 0.221357E+10 | 4416.97 | 14-APR-15:01 | 35.00 | 14.57 | 95733622.95 | 56.69 | 27-APR-00:30 | 14.50 | 8.96 |
May | 0.258995E+10 | 4409.89 | 31-MAY-18:01 | 35.67 | 13.49 | 99123173.25 | 56.69 | 26-MAY-02:39 | 35.67 | 13.49 |
June | 0.327710E+10 | 4423.58 | 15-JUN-15:01 | 41.00 | 16.66 | 96142579.98 | 56.70 | 19-JUN-21:10 | 31.67 | 14.77 |
July | 0.299794E+10 | 4423.09 | 01-JUL-18:01 | 35.83 | 13.66 | 99131763.19 | 56.69 | 20-JUL-21:10 | 31.33 | 18.49 |
August | 0.294625E+10 | 4276.01 | 25-AUG-08:61 | 27.50 | 12.82 | 99250272.87 | 56.70 | 14-AUG-21:10 | 27.50 | 12.82 |
September | 0.260200E+10 | 3431.30 | 25-SEP-08:61 | 24.68 | 18.23 | 95920776.66 | 56.70 | 08-SEP-21:10 | 24.68 | 18.23 |
October | 0.184365E+10 | 4409.11 | 15-OCT-15:01 | 31.00 | 12.59 | 98815288.06 | 56.69 | 21-OCT-23:00 | 17.00 | 15.01 |
November | 0.103982E+10 | 4399.47 | 09-NOV-16:01 | 27.83 | 11.18 | 95234670.61 | 56.69 | 03-NOV-00:49 | 27.83 | 11.18 |
December | 0.573794E+09 | 4376.70 | 22-DEC-16:01 | 24.83 | 10.00 | 97799836.85 | 56.69 | 12-DEC-22:10 | 24.83 | 10.00 |
Annual Sum or Average | 0.223991E+11 | 0.116170E+10 | ||||||||
Minimum of Months | 0.427507E+09 | 3431.30 | 16.83 | 7.75 | 87922802.53 | 56.69 | 14.00 | 8.55 | ||
Maximum of Months | 0.327710E+10 | 4423.58 | 41.00 | 18.23 | 99250272.87 | 59.47 | 35.67 | 18.49 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.373459E+09 | 4293.20 | 31-JAN-16:01 | 29.00 | 10.73 | 99548254.12 | 67.56 | 31-JAN-22:10 | 14.48 | 5.13 |
February | 0.155784E+09 | 4208.32 | 01-FEB-17:11 | 14.67 | 6.54 | 87663670.84 | 59.00 | 09-FEB-22:40 | 14.67 | 8.47 |
March | 0.468513E+09 | 4250.11 | 31-MAR-15:01 | 22.80 | 8.55 | 0.101199E+09 | 73.43 | 23-MAR-21:10 | 22.80 | 8.55 |
April | 0.186720E+10 | 4534.14 | 26-APR-21:51 | 16.00 | 9.61 | 98572603.85 | 78.28 | 26-APR-21:40 | 16.00 | 9.61 |
May | 0.245357E+10 | 4816.93 | 20-MAY-08:61 | 26.50 | 11.05 | 0.100762E+09 | 57.25 | 13-MAY-21:00 | 26.50 | 11.05 |
June | 0.325966E+10 | 4861.45 | 14-JUN-08:61 | 27.67 | 11.24 | 97639673.50 | 56.70 | 15-JUN-21:00 | 33.00 | 14.80 |
July | 0.296386E+10 | 4989.05 | 01-JUL-08:61 | 27.50 | 10.46 | 99750715.46 | 56.69 | 20-JUL-21:10 | 31.33 | 18.49 |
August | 0.275276E+10 | 4626.09 | 24-AUG-08:21 | 27.50 | 13.17 | 0.100629E+09 | 79.31 | 04-AUG-21:10 | 27.50 | 13.17 |
September | 0.227313E+10 | 3574.92 | 25-SEP-20:41 | 24.40 | 19.40 | 97714165.52 | 76.58 | 21-SEP-21:10 | 24.40 | 19.40 |
October | 0.124060E+10 | 4381.60 | 16-OCT-21:51 | 23.00 | 8.96 | 0.102084E+09 | 74.60 | 17-OCT-21:10 | 20.67 | 7.69 |
November | 0.455680E+09 | 4318.08 | 09-NOV-16:01 | 27.83 | 11.18 | 96959002.82 | 72.78 | 01-NOV-21:40 | 27.83 | 11.18 |
December | 0.152855E+09 | 4279.38 | 22-DEC-16:01 | 24.83 | 10.00 | 96912570.38 | 59.05 | 26-DEC-21:40 | 15.00 | 7.15 |
Annual Sum or Average | 0.184171E+11 | 0.117943E+10 | ||||||||
Minimum of Months | 0.152855E+09 | 3574.92 | 14.67 | 6.54 | 87663670.84 | 56.69 | 14.48 | 5.13 | ||
Maximum of Months | 0.325966E+10 | 4989.05 | 29.00 | 19.40 | 0.102084E+09 | 79.31 | 33.00 | 19.40 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.610236E+09 | 620.15 | 14-JAN-13:40 | 26.67 | 10.98 | 0.00 | 0.00 | 01-JAN-00:10 | 26.67 | 10.98 |
February | 0.244759E+09 | 477.99 | 01-FEB-14:15 | 15.67 | 7.45 | 0.00 | 0.00 | 01-FEB-00:10 | 15.67 | 7.45 |
March | 0.277913E+09 | 429.29 | 18-MAR-14:10 | 26.28 | 11.98 | 0.00 | 0.00 | 01-MAR-00:10 | 26.28 | 11.98 |
April | 0.540834E+09 | 434.01 | 14-APR-13:40 | 34.00 | 14.40 | 0.00 | 0.00 | 01-APR-00:10 | 34.00 | 14.40 |
May | 0.534242E+09 | 364.47 | 09-MAY-17:13 | 34.67 | 14.40 | 0.00 | 0.00 | 01-MAY-00:10 | 34.67 | 14.40 |
June | 0.674449E+09 | 453.96 | 28-JUN-19:10 | 39.50 | 16.83 | 0.00 | 0.00 | 01-JUN-00:10 | 39.50 | 16.83 |
July | 0.686194E+09 | 441.81 | 21-JUL-20:20 | 36.00 | 20.94 | 0.00 | 0.00 | 01-JUL-00:10 | 36.00 | 20.94 |
August | 0.727815E+09 | 492.41 | 28-AUG-12:30 | 37.00 | 20.85 | 0.00 | 0.00 | 01-AUG-00:10 | 37.00 | 20.85 |
September | 0.733954E+09 | 574.40 | 28-SEP-13:30 | 36.10 | 16.03 | 0.00 | 0.00 | 01-SEP-00:10 | 36.10 | 16.03 |
October | 0.665743E+09 | 603.53 | 18-OCT-13:20 | 30.33 | 11.95 | 0.00 | 0.00 | 01-OCT-00:10 | 30.33 | 11.95 |
November | 0.523321E+09 | 639.50 | 20-NOV-14:30 | 27.00 | 11.68 | 0.00 | 0.00 | 01-NOV-00:10 | 27.00 | 11.68 |
December | 0.460005E+09 | 614.95 | 25-DEC-13:30 | 25.50 | 11.81 | 0.00 | 0.00 | 01-DEC-00:10 | 25.50 | 11.81 |
Annual Sum or Average | 0.667946E+10 | 0.00 | ||||||||
Minimum of Months | 0.244759E+09 | 364.47 | 15.67 | 7.45 | 0.00 | 0.00 | 15.67 | 7.45 | ||
Maximum of Months | 0.733954E+09 | 639.50 | 39.50 | 20.94 | 0.00 | 0.00 | 39.50 | 20.94 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.268800E+09 | 1496.01 | 31-JAN-19:01 | 23.00 | 8.93 | 98060453.10 | 68.78 | 27-JAN-22:10 | 23.00 | 8.93 |
February | 0.232053E+09 | 1392.21 | 27-FEB-19:01 | 13.67 | 7.91 | 87556203.39 | 63.59 | 09-FEB-22:49 | 13.67 | 7.91 |
March | 0.356506E+09 | 1505.97 | 19-MAR-21:51 | 18.30 | 11.45 | 99931630.00 | 72.50 | 23-MAR-21:10 | 14.80 | 7.70 |
April | 0.666441E+09 | 1553.56 | 30-APR-08:51 | 25.00 | 9.17 | 97200486.38 | 73.06 | 26-APR-21:49 | 25.00 | 9.17 |
May | 0.867878E+09 | 1658.35 | 20-MAY-08:61 | 26.50 | 11.05 | 0.100188E+09 | 56.69 | 05-MAY-21:10 | 26.50 | 11.05 |
June | 0.111524E+10 | 1652.58 | 14-JUN-08:61 | 27.67 | 11.24 | 97036867.24 | 56.69 | 07-JUN-21:49 | 27.67 | 11.24 |
July | 0.109296E+10 | 1698.72 | 01-JUL-08:61 | 27.50 | 10.46 | 99480964.49 | 56.70 | 25-JUL-21:40 | 28.67 | 18.00 |
August | 0.100051E+10 | 1561.89 | 24-AUG-08:21 | 27.50 | 13.17 | 0.100199E+09 | 77.03 | 04-AUG-21:10 | 27.50 | 13.17 |
September | 0.874231E+09 | 1552.15 | 29-SEP-08:21 | 27.75 | 14.34 | 97219115.57 | 75.02 | 21-SEP-21:10 | 27.75 | 14.34 |
October | 0.545070E+09 | 1529.38 | 19-OCT-18:01 | 25.67 | 11.41 | 0.100709E+09 | 72.40 | 11-OCT-21:19 | 25.67 | 11.41 |
November | 0.298329E+09 | 1497.40 | 10-NOV-16:01 | 24.50 | 12.16 | 95658573.42 | 71.18 | 02-NOV-21:00 | 24.50 | 12.16 |
December | 0.181696E+09 | 1444.76 | 25-DEC-16:01 | 25.67 | 11.87 | 96513682.74 | 59.67 | 26-DEC-21:40 | 15.00 | 7.15 |
Annual Sum or Average | 0.749972E+10 | 0.116975E+10 | ||||||||
Minimum of Months | 0.181696E+09 | 1392.21 | 13.67 | 7.91 | 87556203.39 | 56.69 | 13.67 | 7.15 | ||
Maximum of Months | 0.111524E+10 | 1698.72 | 27.75 | 14.34 | 0.100709E+09 | 77.03 | 28.67 | 18.00 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.996036E+09 | 3883.02 | 31-JAN-16:01 | 29.00 | 10.73 | 98714503.24 | 56.69 | 10-JAN-22:10 | 29.00 | 10.73 |
February | 0.486811E+09 | 3783.83 | 03-FEB-16:01 | 16.83 | 7.75 | 88339896.88 | 56.69 | 21-FEB-22:10 | 14.00 | 12.80 |
March | 0.886756E+09 | 3847.83 | 31-MAR-15:01 | 22.80 | 8.55 | 98610484.24 | 56.69 | 17-MAR-01:10 | 22.80 | 8.55 |
April | 0.225187E+10 | 3924.68 | 14-APR-15:01 | 35.00 | 14.57 | 95941149.79 | 56.69 | 12-APR-21:30 | 35.00 | 14.57 |
May | 0.268248E+10 | 4003.98 | 17-MAY-08:61 | 27.17 | 13.67 | 99201354.33 | 56.69 | 26-MAY-02:39 | 22.00 | 13.14 |
June | 0.335731E+10 | 4000.73 | 14-JUN-08:61 | 27.67 | 11.24 | 96039707.72 | 56.70 | 15-JUN-21:00 | 33.00 | 14.80 |
July | 0.320381E+10 | 4007.12 | 01-JUL-08:61 | 27.50 | 10.46 | 99137733.69 | 56.70 | 20-JUL-22:10 | 33.00 | 18.27 |
August | 0.311766E+10 | 3925.62 | 25-AUG-08:61 | 27.50 | 12.82 | 99242762.73 | 56.70 | 16-AUG-21:10 | 27.50 | 12.82 |
September | 0.269375E+10 | 3094.66 | 26-SEP-08:61 | 23.85 | 17.52 | 95951643.65 | 56.70 | 07-SEP-21:30 | 23.85 | 17.52 |
October | 0.191383E+10 | 3908.90 | 15-OCT-15:01 | 31.00 | 12.59 | 99023414.31 | 56.69 | 22-OCT-00:49 | 16.17 | 15.32 |
November | 0.975148E+09 | 3893.24 | 10-NOV-09:01 | 21.33 | 9.26 | 95427469.19 | 56.69 | 03-NOV-00:00 | 21.33 | 9.26 |
December | 0.584268E+09 | 3870.27 | 26-DEC-16:01 | 23.00 | 10.75 | 98177775.05 | 56.69 | 12-DEC-22:10 | 23.00 | 10.75 |
Annual Sum or Average | 0.231497E+11 | 0.116381E+10 | ||||||||
Minimum of Months | 0.486811E+09 | 3094.66 | 16.83 | 7.75 | 88339896.88 | 56.69 | 14.00 | 8.55 | ||
Maximum of Months | 0.335731E+10 | 4007.12 | 35.00 | 17.52 | 99242762.73 | 56.70 | 35.00 | 18.27 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.364074E+09 | 3949.56 | 27-JAN-09:51 | 20.00 | 7.78 | 99082352.30 | 66.37 | 31-JAN-22:10 | 14.48 | 5.13 |
February | 0.222809E+09 | 2975.15 | 26-FEB-09:01 | 11.33 | 8.84 | 87802089.53 | 59.98 | 09-FEB-22:40 | 11.33 | 8.84 |
March | 0.529077E+09 | 3794.06 | 31-MAR-15:01 | 22.80 | 8.55 | 0.100937E+09 | 71.71 | 16-MAR-21:10 | 22.80 | 8.55 |
April | 0.185942E+10 | 4572.27 | 14-APR-08:41 | 26.50 | 12.19 | 99074557.95 | 73.87 | 19-APR-21:30 | 20.50 | 9.19 |
May | 0.246924E+10 | 4907.68 | 21-MAY-08:61 | 25.33 | 11.05 | 0.102174E+09 | 56.74 | 13-MAY-21:00 | 25.33 | 11.05 |
June | 0.331696E+10 | 4586.85 | 13-JUN-08:11 | 26.00 | 10.40 | 97993413.35 | 58.57 | 19-JUN-05:00 | 23.00 | 10.71 |
July | 0.315777E+10 | 4590.37 | 01-JUL-08:61 | 27.50 | 10.46 | 99990787.00 | 56.92 | 05-JUL-05:00 | 23.00 | 11.31 |
August | 0.290686E+10 | 4575.39 | 24-AUG-08:21 | 27.50 | 13.17 | 0.100935E+09 | 78.97 | 04-AUG-21:10 | 27.50 | 13.17 |
September | 0.233928E+10 | 3628.44 | 15-SEP-08:51 | 25.00 | 16.27 | 98156922.12 | 76.50 | 21-SEP-21:10 | 22.02 | 16.74 |
October | 0.128952E+10 | 4481.62 | 17-OCT-08:51 | 24.00 | 9.54 | 0.102312E+09 | 73.16 | 17-OCT-21:10 | 20.67 | 7.69 |
November | 0.417884E+09 | 4232.20 | 10-NOV-09:51 | 23.00 | 9.98 | 96495146.28 | 70.92 | 02-NOV-21:30 | 23.00 | 9.98 |
December | 0.176048E+09 | 3792.71 | 25-DEC-09:51 | 18.00 | 8.29 | 96725128.59 | 56.93 | 26-DEC-21:40 | 15.00 | 7.15 |
Annual Sum or Average | 0.190490E+11 | 0.118168E+10 | ||||||||
Minimum of Months | 0.176048E+09 | 2975.15 | 11.33 | 7.78 | 87802089.53 | 56.74 | 11.33 | 5.13 | ||
Maximum of Months | 0.331696E+10 | 4907.68 | 27.50 | 16.27 | 0.102312E+09 | 78.97 | 27.50 | 16.74 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.425544E+10 | 2036.84 | 29-JAN-11:33 | 21.33 | 8.67 | 0.137263E+10 | 865.12 | 31-JAN-22:40 | 13.83 | 4.56 |
February | 0.349254E+10 | 1911.76 | 01-FEB-11:33 | 13.67 | 6.91 | 0.117251E+10 | 853.78 | 01-FEB-00:10 | 13.67 | 6.91 |
March | 0.414011E+10 | 2066.88 | 18-MAR-10:45 | 24.12 | 14.75 | 0.135352E+10 | 864.99 | 17-MAR-21:49 | 24.12 | 14.75 |
April | 0.483634E+10 | 2433.27 | 15-APR-10:33 | 28.00 | 13.04 | 0.146104E+10 | 951.84 | 14-APR-21:40 | 28.00 | 13.04 |
May | 0.526986E+10 | 2445.43 | 20-MAY-10:33 | 31.33 | 12.44 | 0.156199E+10 | 951.85 | 11-MAY-21:40 | 31.33 | 12.44 |
June | 0.590311E+10 | 3666.25 | 28-JUN-18:40 | 40.33 | 17.38 | 0.156438E+10 | 951.87 | 09-JUN-23:49 | 40.33 | 17.38 |
July | 0.586468E+10 | 3310.50 | 21-JUL-19:10 | 37.83 | 19.56 | 0.160638E+10 | 951.86 | 07-JUL-22:10 | 37.83 | 19.56 |
August | 0.578184E+10 | 3160.95 | 15-AUG-18:17 | 37.67 | 18.63 | 0.160694E+10 | 951.85 | 27-AUG-23:49 | 30.17 | 17.39 |
September | 0.539276E+10 | 3013.52 | 08-SEP-18:15 | 35.90 | 20.02 | 0.154501E+10 | 951.86 | 20-SEP-21:19 | 27.20 | 17.73 |
October | 0.497126E+10 | 2782.48 | 04-OCT-18:04 | 32.67 | 17.42 | 0.150463E+10 | 951.86 | 06-OCT-23:19 | 25.67 | 15.00 |
November | 0.420604E+10 | 2115.25 | 01-NOV-18:10 | 23.67 | 14.38 | 0.134630E+10 | 889.45 | 02-NOV-22:10 | 19.83 | 16.01 |
December | 0.390058E+10 | 1955.31 | 25-DEC-11:33 | 22.33 | 10.13 | 0.130514E+10 | 842.91 | 26-DEC-22:40 | 14.33 | 6.96 |
Annual Sum or Average | 0.580146E+11 | 0.174005E+11 | ||||||||
Minimum of Months | 0.349254E+10 | 1911.76 | 13.67 | 6.91 | 0.117251E+10 | 842.91 | 13.67 | 4.56 | ||
Maximum of Months | 0.590311E+10 | 3666.25 | 40.33 | 20.02 | 0.160694E+10 | 951.87 | 40.33 | 19.56 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.908948E+09 | 4621.84 | 24-JAN-16:01 | 24.83 | 10.77 | 98195814.78 | 56.69 | 04-JAN-05:49 | 24.83 | 10.77 |
February | 0.352870E+09 | 4493.34 | 03-FEB-16:01 | 16.83 | 7.75 | 87615540.02 | 56.69 | 10-FEB-01:10 | 15.00 | 8.37 |
March | 0.776999E+09 | 4556.36 | 31-MAR-15:01 | 22.80 | 8.55 | 97964615.14 | 56.70 | 01-MAR-01:30 | 22.80 | 8.55 |
April | 0.222437E+10 | 4677.01 | 14-APR-15:01 | 35.00 | 14.57 | 95644612.77 | 56.69 | 17-APR-00:40 | 17.33 | 11.89 |
May | 0.263524E+10 | 4662.67 | 07-MAY-15:01 | 35.17 | 13.95 | 99088281.57 | 56.69 | 26-MAY-03:30 | 21.00 | 13.13 |
June | 0.343165E+10 | 4687.08 | 15-JUN-15:01 | 41.00 | 16.66 | 96229871.80 | 56.70 | 29-JUN-22:10 | 33.83 | 15.97 |
July | 0.312400E+10 | 4672.70 | 01-JUL-18:01 | 35.83 | 13.66 | 99138024.87 | 56.70 | 20-JUL-21:10 | 31.33 | 18.49 |
August | 0.305203E+10 | 4486.50 | 25-AUG-08:61 | 27.50 | 12.82 | 99270828.16 | 56.69 | 07-AUG-03:39 | 27.50 | 12.82 |
September | 0.262698E+10 | 3626.77 | 01-SEP-08:61 | 27.98 | 20.85 | 95899610.94 | 56.69 | 03-SEP-03:49 | 22.20 | 20.84 |
October | 0.173165E+10 | 4658.22 | 15-OCT-15:01 | 31.00 | 12.59 | 98652194.59 | 56.69 | 04-OCT-04:49 | 31.00 | 12.59 |
November | 0.906361E+09 | 4650.07 | 09-NOV-16:01 | 27.83 | 11.18 | 94974234.24 | 56.69 | 15-NOV-22:10 | 11.83 | 11.28 |
December | 0.483629E+09 | 4625.87 | 22-DEC-16:01 | 24.83 | 10.00 | 97451057.80 | 56.69 | 12-DEC-22:10 | 24.83 | 10.00 |
Annual Sum or Average | 0.222547E+11 | 0.116012E+10 | ||||||||
Minimum of Months | 0.352870E+09 | 3626.77 | 16.83 | 7.75 | 87615540.02 | 56.69 | 11.83 | 8.37 | ||
Maximum of Months | 0.343165E+10 | 4687.08 | 41.00 | 20.85 | 99270828.16 | 56.70 | 33.83 | 20.84 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.283672E+09 | 4519.67 | 31-JAN-16:01 | 29.00 | 10.73 | 98965387.33 | 65.18 | 19-JAN-22:10 | 29.00 | 10.73 |
February | 0.111398E+09 | 4411.71 | 01-FEB-17:11 | 14.67 | 6.54 | 87223061.80 | 56.69 | 21-FEB-22:19 | 14.00 | 12.80 |
March | 0.411934E+09 | 4483.49 | 31-MAR-15:01 | 22.80 | 8.55 | 0.101012E+09 | 73.97 | 31-MAR-18:10 | 21.23 | 7.98 |
April | 0.189785E+10 | 4771.21 | 26-APR-21:51 | 16.00 | 9.61 | 98350031.83 | 80.45 | 20-APR-18:10 | 16.00 | 9.61 |
May | 0.252604E+10 | 4987.84 | 20-MAY-08:61 | 26.50 | 11.05 | 0.100384E+09 | 56.69 | 26-MAY-03:30 | 21.00 | 13.13 |
June | 0.343292E+10 | 5050.05 | 14-JUN-08:61 | 27.67 | 11.24 | 97555825.38 | 56.70 | 30-JUN-21:00 | 32.70 | 14.93 |
July | 0.309733E+10 | 5175.33 | 01-JUL-08:61 | 27.50 | 10.46 | 99663469.93 | 56.70 | 20-JUL-21:10 | 31.33 | 18.49 |
August | 0.286998E+10 | 4789.17 | 24-AUG-08:21 | 27.50 | 13.17 | 0.100497E+09 | 78.96 | 04-AUG-21:10 | 27.50 | 13.17 |
September | 0.231463E+10 | 3680.84 | 27-SEP-08:51 | 26.60 | 16.37 | 97429266.79 | 75.45 | 21-SEP-21:10 | 26.60 | 16.37 |
October | 0.115643E+10 | 4574.34 | 15-OCT-15:01 | 31.00 | 12.59 | 0.101456E+09 | 73.18 | 17-OCT-21:10 | 20.67 | 7.69 |
November | 0.362046E+09 | 4552.75 | 09-NOV-16:01 | 27.83 | 11.18 | 96304081.08 | 72.15 | 01-NOV-21:30 | 27.83 | 11.18 |
December | 0.113080E+09 | 4508.86 | 22-DEC-16:01 | 24.83 | 10.00 | 96281817.58 | 57.07 | 26-DEC-21:40 | 15.00 | 7.15 |
Annual Sum or Average | 0.185773E+11 | 0.117512E+10 | ||||||||
Minimum of Months | 0.111398E+09 | 3680.84 | 14.67 | 6.54 | 87223061.80 | 56.69 | 14.00 | 7.15 | ||
Maximum of Months | 0.343292E+10 | 5175.33 | 31.00 | 16.37 | 0.101456E+09 | 80.45 | 32.70 | 18.49 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.121849E+10 | 2364.81 | 19-JAN-16:01 | 24.67 | 9.83 | 98945857.42 | 59.64 | 12-JAN-02:49 | 24.67 | 9.83 |
February | 0.567405E+09 | 2292.16 | 03-FEB-16:01 | 16.83 | 7.75 | 88567251.39 | 61.84 | 01-FEB-05:19 | 16.83 | 7.75 |
March | 0.683031E+09 | 2321.07 | 31-MAR-15:01 | 22.80 | 8.55 | 98482431.28 | 59.59 | 28-MAR-23:00 | 22.80 | 8.55 |
April | 0.126647E+10 | 2351.16 | 05-APR-15:01 | 32.00 | 12.11 | 95689497.84 | 56.69 | 17-APR-01:10 | 17.00 | 11.67 |
May | 0.132341E+10 | 2339.35 | 08-MAY-08:61 | 27.17 | 12.22 | 99080100.60 | 56.69 | 26-MAY-03:09 | 21.00 | 13.54 |
June | 0.166065E+10 | 2335.36 | 14-JUN-08:61 | 27.67 | 11.24 | 96007559.67 | 56.69 | 06-JUN-21:10 | 27.67 | 11.24 |
July | 0.167793E+10 | 2339.66 | 01-JUL-08:61 | 27.50 | 10.46 | 99110181.35 | 56.70 | 20-JUL-21:49 | 32.67 | 18.26 |
August | 0.173256E+10 | 2282.11 | 25-AUG-08:61 | 27.50 | 12.82 | 99216176.91 | 56.70 | 15-AUG-21:00 | 27.50 | 12.82 |
September | 0.167901E+10 | 1874.68 | 24-SEP-08:61 | 24.18 | 17.45 | 95928435.47 | 56.70 | 05-SEP-21:10 | 24.18 | 17.45 |
October | 0.141779E+10 | 2373.09 | 18-OCT-15:01 | 30.00 | 11.77 | 98932244.07 | 59.63 | 26-OCT-00:40 | 7.33 | 2.70 |
November | 0.106348E+10 | 2365.83 | 09-NOV-16:01 | 27.83 | 11.18 | 95595408.87 | 63.55 | 07-NOV-05:30 | 27.83 | 11.18 |
December | 0.934843E+09 | 2370.63 | 22-DEC-16:01 | 24.83 | 10.00 | 98693082.44 | 62.04 | 01-DEC-04:30 | 24.83 | 10.00 |
Annual Sum or Average | 0.152251E+11 | 0.116425E+10 | ||||||||
Minimum of Months | 0.567405E+09 | 1874.68 | 16.83 | 7.75 | 88567251.39 | 56.69 | 7.33 | 2.70 | ||
Maximum of Months | 0.173256E+10 | 2373.09 | 32.00 | 17.45 | 99216176.91 | 63.55 | 32.67 | 18.26 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.353054E+11 | 19477.32 | 06-JAN-22:10 | 17.67 | 9.28 | 0.191965E+11 | 11367.87 | 09-JAN-22:19 | 10.33 | 8.87 |
February | 0.311651E+11 | 19081.18 | 21-FEB-23:00 | 14.00 | 12.80 | 0.173258E+11 | 11368.03 | 10-FEB-23:30 | 14.00 | 12.80 |
March | 0.364063E+11 | 21014.58 | 17-MAR-21:53 | 20.50 | 11.82 | 0.193003E+11 | 11368.46 | 20-MAR-00:40 | 12.37 | 8.39 |
April | 0.406012E+11 | 23009.37 | 14-APR-21:10 | 28.67 | 13.19 | 0.187062E+11 | 11364.64 | 22-APR-02:20 | 12.67 | 2.64 |
May | 0.442304E+11 | 23245.75 | 09-MAY-21:10 | 28.83 | 12.76 | 0.193478E+11 | 11349.42 | 26-MAY-21:19 | 25.00 | 9.45 |
June | 0.463748E+11 | 24848.18 | 28-JUN-21:20 | 34.33 | 14.34 | 0.187609E+11 | 11375.10 | 09-JUN-21:19 | 34.33 | 14.34 |
July | 0.471276E+11 | 24521.41 | 21-JUL-21:20 | 33.67 | 20.69 | 0.193097E+11 | 11375.44 | 07-JUL-21:19 | 33.67 | 20.69 |
August | 0.463931E+11 | 24082.59 | 10-AUG-21:20 | 32.67 | 17.86 | 0.193907E+11 | 11368.96 | 14-AUG-22:00 | 31.00 | 17.56 |
September | 0.434700E+11 | 23878.78 | 07-SEP-21:10 | 32.75 | 19.42 | 0.187087E+11 | 11367.20 | 07-SEP-22:00 | 28.30 | 20.20 |
October | 0.397625E+11 | 23063.89 | 03-OCT-21:10 | 29.50 | 18.57 | 0.192766E+11 | 11367.59 | 27-OCT-04:10 | 12.83 | 4.70 |
November | 0.348107E+11 | 20886.03 | 02-NOV-21:53 | 20.00 | 16.05 | 0.185895E+11 | 11373.60 | 15-NOV-01:39 | 12.00 | 12.00 |
December | 0.334018E+11 | 19091.50 | 26-DEC-22:10 | 14.83 | 7.20 | 0.191308E+11 | 11370.01 | 27-DEC-23:49 | 11.18 | 5.51 |
Annual Sum or Average | 0.479049E+12 | 0.227043E+12 | ||||||||
Minimum of Months | 0.311651E+11 | 19081.18 | 14.00 | 7.20 | 0.173258E+11 | 11349.42 | 10.33 | 2.64 | ||
Maximum of Months | 0.471276E+11 | 24848.18 | 34.33 | 20.69 | 0.193907E+11 | 11375.44 | 34.33 | 20.69 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.386792E+11 | 21132.11 | 06-JAN-22:10 | 17.67 | 9.28 | 0.192626E+11 | 11368.98 | 09-JAN-22:19 | 10.33 | 8.87 |
February | 0.344574E+11 | 20780.34 | 21-FEB-22:10 | 14.00 | 12.80 | 0.174033E+11 | 11369.21 | 10-FEB-23:30 | 14.00 | 12.80 |
March | 0.399511E+11 | 22448.48 | 17-MAR-21:10 | 21.42 | 12.50 | 0.193626E+11 | 11369.38 | 20-MAR-00:40 | 12.37 | 8.39 |
April | 0.435202E+11 | 24189.52 | 14-APR-21:10 | 28.67 | 13.19 | 0.187162E+11 | 11365.40 | 22-APR-02:20 | 12.67 | 2.64 |
May | 0.470992E+11 | 24414.47 | 09-MAY-21:20 | 28.67 | 12.70 | 0.193499E+11 | 11365.65 | 26-MAY-21:19 | 25.00 | 9.45 |
June | 0.490567E+11 | 26025.66 | 28-JUN-21:20 | 34.33 | 14.34 | 0.187617E+11 | 11383.27 | 09-JUN-21:19 | 34.33 | 14.34 |
July | 0.498640E+11 | 25697.36 | 21-JUL-21:20 | 33.67 | 20.69 | 0.193105E+11 | 11382.63 | 07-JUL-21:19 | 33.67 | 20.69 |
August | 0.491327E+11 | 25262.00 | 10-AUG-21:20 | 32.67 | 17.86 | 0.193916E+11 | 11369.06 | 17-AUG-22:00 | 30.00 | 18.25 |
September | 0.461091E+11 | 25019.27 | 07-SEP-21:10 | 32.75 | 19.42 | 0.187103E+11 | 11367.87 | 19-SEP-21:19 | 27.73 | 15.69 |
October | 0.427946E+11 | 24214.77 | 03-OCT-21:10 | 29.50 | 18.57 | 0.193016E+11 | 11368.18 | 27-OCT-04:10 | 12.83 | 4.70 |
November | 0.380473E+11 | 22229.30 | 02-NOV-21:53 | 20.00 | 16.05 | 0.186441E+11 | 11375.11 | 15-NOV-01:39 | 12.00 | 12.00 |
December | 0.369031E+11 | 20639.08 | 26-DEC-22:10 | 14.83 | 7.20 | 0.192284E+11 | 11371.10 | 27-DEC-23:49 | 11.18 | 5.51 |
Annual Sum or Average | 0.515615E+12 | 0.227443E+12 | ||||||||
Minimum of Months | 0.344574E+11 | 20639.08 | 14.00 | 7.20 | 0.174033E+11 | 11365.40 | 10.33 | 2.64 | ||
Maximum of Months | 0.498640E+11 | 26025.66 | 34.33 | 20.69 | 0.193916E+11 | 11383.27 | 34.33 | 20.69 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.525276E+11 | 28353.60 | 29-JAN-11:33 | 21.33 | 8.67 | 0.188472E+11 | 11319.61 | 14-JAN-18:19 | 21.33 | 8.67 |
February | 0.468163E+11 | 28283.64 | 18-FEB-11:33 | 19.33 | 14.12 | 0.170247E+11 | 11319.52 | 25-FEB-18:19 | 15.67 | 9.08 |
March | 0.529509E+11 | 29221.81 | 18-MAR-10:45 | 24.12 | 14.75 | 0.188588E+11 | 11319.67 | 18-MAR-17:19 | 26.63 | 12.71 |
April | 0.550716E+11 | 30536.15 | 30-APR-10:33 | 30.00 | 11.09 | 0.182592E+11 | 11319.67 | 08-APR-17:19 | 30.00 | 11.09 |
May | 0.581351E+11 | 30749.76 | 07-MAY-10:45 | 30.50 | 13.03 | 0.188710E+11 | 11319.66 | 27-MAY-17:19 | 30.00 | 11.00 |
June | 0.586898E+11 | 31472.27 | 18-JUN-10:50 | 35.67 | 17.76 | 0.182662E+11 | 11319.66 | 10-JUN-17:19 | 35.67 | 17.76 |
July | 0.601229E+11 | 31468.17 | 22-JUL-10:40 | 35.67 | 19.48 | 0.188684E+11 | 11319.66 | 29-JUL-17:19 | 35.90 | 19.14 |
August | 0.598161E+11 | 31506.06 | 13-AUG-10:40 | 33.67 | 21.36 | 0.188756E+11 | 11319.65 | 12-AUG-17:19 | 33.67 | 21.36 |
September | 0.567516E+11 | 31289.22 | 09-SEP-10:37 | 33.43 | 20.70 | 0.182618E+11 | 11319.66 | 23-SEP-17:19 | 33.27 | 17.89 |
October | 0.553831E+11 | 30568.75 | 02-OCT-10:45 | 32.67 | 19.11 | 0.188614E+11 | 11319.70 | 07-OCT-17:19 | 20.00 | 13.38 |
November | 0.510654E+11 | 29107.19 | 01-NOV-10:45 | 24.67 | 16.10 | 0.182418E+11 | 11319.56 | 04-NOV-17:19 | 17.67 | 8.15 |
December | 0.510856E+11 | 28210.73 | 25-DEC-11:50 | 22.67 | 10.24 | 0.188382E+11 | 11319.55 | 16-DEC-18:19 | 22.67 | 10.24 |
Annual Sum or Average | 0.658416E+12 | 0.222074E+12 | ||||||||
Minimum of Months | 0.468163E+11 | 28210.73 | 19.33 | 8.67 | 0.170247E+11 | 11319.52 | 15.67 | 8.15 | ||
Maximum of Months | 0.601229E+11 | 31506.06 | 35.67 | 21.36 | 0.188756E+11 | 11319.70 | 35.90 | 21.36 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.836746E+10 | 4162.52 | 29-JAN-11:33 | 21.33 | 8.67 | 0.142025E+10 | 898.87 | 31-JAN-22:19 | 14.27 | 4.94 |
February | 0.690640E+10 | 3941.87 | 26-FEB-11:33 | 15.33 | 10.16 | 0.122126E+10 | 879.75 | 01-FEB-00:10 | 15.33 | 10.16 |
March | 0.826041E+10 | 4457.70 | 18-MAR-17:12 | 26.63 | 12.71 | 0.141782E+10 | 939.63 | 17-MAR-21:40 | 26.63 | 12.71 |
April | 0.101908E+11 | 6352.70 | 14-APR-15:03 | 35.00 | 14.57 | 0.156267E+10 | 1007.41 | 12-APR-22:00 | 35.00 | 14.57 |
May | 0.113848E+11 | 6024.47 | 09-MAY-15:03 | 35.00 | 14.52 | 0.166800E+10 | 1007.44 | 10-MAY-23:19 | 25.67 | 15.01 |
June | 0.135891E+11 | 7996.35 | 28-JUN-18:17 | 40.67 | 17.68 | 0.165502E+10 | 1007.44 | 09-JUN-23:30 | 40.67 | 17.68 |
July | 0.135255E+11 | 7344.68 | 20-JUL-18:17 | 38.33 | 19.15 | 0.170447E+10 | 1007.43 | 07-JUL-22:10 | 38.33 | 19.15 |
August | 0.132553E+11 | 7386.24 | 11-AUG-15:25 | 38.00 | 21.21 | 0.170540E+10 | 1007.41 | 21-AUG-00:10 | 26.00 | 16.49 |
September | 0.119777E+11 | 7421.12 | 07-SEP-14:10 | 36.70 | 19.71 | 0.163697E+10 | 1007.41 | 20-SEP-21:19 | 27.20 | 17.73 |
October | 0.101361E+11 | 6985.08 | 02-OCT-13:10 | 34.17 | 19.45 | 0.156217E+10 | 1007.41 | 06-OCT-23:19 | 25.67 | 15.00 |
November | 0.829431E+10 | 4435.79 | 01-NOV-17:12 | 25.33 | 14.39 | 0.138834E+10 | 949.61 | 01-NOV-21:30 | 18.00 | 13.11 |
December | 0.734205E+10 | 4062.61 | 25-DEC-11:33 | 22.33 | 10.13 | 0.134952E+10 | 882.13 | 26-DEC-22:30 | 14.50 | 7.04 |
Annual Sum or Average | 0.123230E+12 | 0.182919E+11 | ||||||||
Minimum of Months | 0.690640E+10 | 3941.87 | 15.33 | 8.67 | 0.122126E+10 | 879.75 | 14.27 | 4.94 | ||
Maximum of Months | 0.135891E+11 | 7996.35 | 40.67 | 21.21 | 0.170540E+10 | 1007.44 | 40.67 | 19.15 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 17.23 |
December | 46025.59 | 42.65 | 16-DEC-07:20 | 1.33 |
Annual Sum or Average | 46025.59 | |||
Minimum of Months | 0.00 | 0.00 | 1.33 | |
Maximum of Months | 46025.59 | 42.65 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 20126683.85 | 1358.47 | 17-JAN-09:03 | 15.50 |
February | 51385220.50 | 1372.16 | 02-FEB-19:03 | 10.83 |
March | 34475643.67 | 1356.13 | 07-MAR-19:03 | 18.80 |
April | 1236386.97 | 1326.93 | 08-APR-08:03 | 17.50 |
May | 762001.43 | 1256.70 | 17-MAY-08:03 | 27.17 |
June | 100470.61 | 1082.85 | 14-JUN-08:03 | 27.67 |
July | 724506.86 | 963.58 | 01-JUL-08:03 | 27.50 |
August | 943510.76 | 887.89 | 30-AUG-08:03 | 26.67 |
September | 1388905.63 | 895.35 | 03-SEP-08:04 | 20.18 |
October | 2901646.67 | 1355.58 | 27-OCT-18:03 | 17.50 |
November | 13801820.76 | 1355.21 | 29-NOV-19:03 | 14.50 |
December | 0.112497E+09 | 1360.86 | 19-DEC-19:03 | 11.50 |
Annual Sum or Average | 0.240344E+09 | |||
Minimum of Months | 100470.61 | 887.89 | 10.83 | |
Maximum of Months | 0.112497E+09 | 1372.16 | 27.67 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 61939862.10 | 1360.76 | 31-JAN-22:03 | 14.48 |
February | 97179277.94 | 1354.85 | 03-FEB-19:03 | 13.83 |
March | 48810130.97 | 1350.97 | 28-MAR-20:23 | 13.55 |
April | 2370854.13 | 1343.34 | 06-APR-21:53 | 15.00 |
May | 1398502.53 | 1345.40 | 05-MAY-08:23 | 26.50 |
June | 147602.13 | 762.28 | 14-JUN-08:04 | 27.67 |
July | 611316.66 | 856.09 | 01-JUL-08:04 | 27.50 |
August | 682556.26 | 803.61 | 29-AUG-08:04 | 26.67 |
September | 950347.89 | 976.72 | 11-SEP-08:24 | 26.60 |
October | 6813261.26 | 1227.07 | 31-OCT-21:43 | 15.58 |
November | 39143036.08 | 1371.50 | 26-NOV-19:03 | 14.00 |
December | 0.258699E+09 | 1391.38 | 05-DEC-16:03 | 15.67 |
Annual Sum or Average | 0.518746E+09 | |||
Minimum of Months | 147602.13 | 762.28 | 13.55 | |
Maximum of Months | 0.258699E+09 | 1391.38 | 27.67 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5986085.63 | 378.16 | 05-JAN-09:03 | 14.33 |
February | 5250455.52 | 384.38 | 01-FEB-16:03 | 15.83 |
March | 10452988.60 | 385.25 | 11-MAR-16:04 | 15.78 |
April | 832987.07 | 368.38 | 06-APR-21:54 | 15.00 |
May | 377433.35 | 343.62 | 16-MAY-08:24 | 26.50 |
June | 13451.95 | 114.66 | 05-JUN-08:06 | 30.17 |
July | 157980.72 | 165.63 | 19-JUL-08:06 | 29.67 |
August | 256476.68 | 342.59 | 24-AUG-08:24 | 27.50 |
September | 374049.22 | 290.14 | 03-SEP-21:55 | 23.30 |
October | 1385046.38 | 374.45 | 26-OCT-08:03 | 12.33 |
November | 5134629.27 | 379.93 | 23-NOV-09:03 | 5.45 |
December | 13878931.68 | 378.94 | 26-DEC-09:03 | 13.83 |
Annual Sum or Average | 44100516.08 | |||
Minimum of Months | 13451.95 | 114.66 | 5.45 | |
Maximum of Months | 13878931.68 | 385.25 | 30.17 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 25251132.81 | 1293.26 | 23-JAN-19:03 | 16.67 |
February | 49980947.78 | 1309.07 | 02-FEB-19:03 | 10.83 |
March | 33572548.09 | 1298.88 | 12-MAR-18:03 | 16.23 |
April | 54938.65 | 368.50 | 29-APR-08:04 | 24.33 |
May | 25632.65 | 299.05 | 25-MAY-08:04 | 25.33 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 3014.20 | 35.17 | 09-JUL-08:04 | 26.33 |
August | 104698.78 | 652.27 | 04-AUG-08:04 | 22.33 |
September | 171055.30 | 902.64 | 03-SEP-08:04 | 20.18 |
October | 1631324.58 | 1304.48 | 27-OCT-18:03 | 17.50 |
November | 17913166.76 | 1296.89 | 28-NOV-19:03 | 15.77 |
December | 0.112815E+09 | 1313.55 | 05-DEC-09:03 | 7.33 |
Annual Sum or Average | 0.241524E+09 | |||
Minimum of Months | 0.00 | 0.00 | 7.33 | |
Maximum of Months | 0.112815E+09 | 1313.55 | 26.33 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 76351807.99 | 1305.61 | 31-JAN-22:03 | 14.48 |
February | 90287041.55 | 1280.41 | 03-FEB-16:03 | 16.83 |
March | 49126966.29 | 1320.26 | 26-MAR-15:03 | 17.38 |
April | 957624.27 | 1295.41 | 26-APR-21:53 | 16.00 |
May | 134588.05 | 1079.89 | 13-MAY-21:54 | 22.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 17230.92 | 287.18 | 03-AUG-19:45 | 24.00 |
September | 80857.11 | 357.32 | 25-SEP-08:25 | 25.25 |
October | 5691960.48 | 1096.46 | 12-OCT-20:13 | 14.67 |
November | 49457513.24 | 1282.32 | 22-NOV-19:03 | 11.83 |
December | 0.241670E+09 | 1289.75 | 29-DEC-16:03 | 18.83 |
Annual Sum or Average | 0.513776E+09 | |||
Minimum of Months | 0.00 | 0.00 | 11.83 | |
Maximum of Months | 0.241670E+09 | 1320.26 | 27.73 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 88004359.54 | 1391.03 | 01-JAN-09:02 | 5.90 |
February | 0.161629E+09 | 1412.01 | 02-FEB-19:03 | 10.83 |
March | 0.105858E+09 | 1591.71 | 07-MAR-19:03 | 18.80 |
April | 1981331.89 | 1470.55 | 22-APR-08:03 | 19.67 |
May | 910215.04 | 1578.58 | 01-MAY-08:03 | 19.50 |
June | 327177.77 | 1098.88 | 14-JUN-08:03 | 27.67 |
July | 802893.31 | 980.34 | 01-JUL-08:03 | 27.50 |
August | 1029991.42 | 1173.99 | 30-AUG-08:03 | 26.67 |
September | 1568471.29 | 850.98 | 28-SEP-08:04 | 24.37 |
October | 21142148.77 | 1515.70 | 14-OCT-08:03 | 20.67 |
November | 68334694.64 | 1627.00 | 30-NOV-19:03 | 14.00 |
December | 0.281251E+09 | 1641.29 | 01-DEC-19:03 | 11.83 |
Annual Sum or Average | 0.732838E+09 | |||
Minimum of Months | 327177.77 | 850.98 | 5.90 | |
Maximum of Months | 0.281251E+09 | 1641.29 | 27.67 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.196554E+09 | 1418.24 | 13-JAN-09:01 | 9.83 |
February | 0.263206E+09 | 1420.83 | 02-FEB-16:03 | 14.67 |
March | 0.134129E+09 | 1622.84 | 08-MAR-16:03 | 19.30 |
April | 2538093.00 | 1627.88 | 26-APR-21:53 | 16.00 |
May | 2006243.40 | 1627.53 | 25-MAY-08:13 | 25.67 |
June | 204929.80 | 732.80 | 24-JUN-06:44 | 26.50 |
July | 644231.07 | 904.05 | 27-JUL-08:14 | 25.67 |
August | 943155.44 | 1621.37 | 24-AUG-08:23 | 27.50 |
September | 1230442.21 | 1209.65 | 08-SEP-06:53 | 25.00 |
October | 35586408.06 | 1557.47 | 19-OCT-08:52 | 23.00 |
November | 0.138464E+09 | 1591.57 | 26-NOV-19:03 | 14.00 |
December | 0.529552E+09 | 1616.88 | 05-DEC-16:03 | 15.67 |
Annual Sum or Average | 0.130506E+10 | |||
Minimum of Months | 204929.80 | 732.80 | 9.83 | |
Maximum of Months | 0.529552E+09 | 1627.88 | 27.50 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 10618125.94 | 708.03 | 01-JAN-00:32 | 5.07 |
February | 17016096.60 | 823.46 | 07-FEB-16:04 | 16.00 |
March | 14428309.94 | 775.67 | 26-MAR-18:03 | 16.83 |
April | 672708.14 | 711.85 | 19-APR-08:03 | 19.50 |
May | 847784.20 | 811.99 | 09-MAY-08:03 | 26.33 |
June | 205118.68 | 810.34 | 14-JUN-08:03 | 27.67 |
July | 641136.79 | 608.23 | 01-JUL-08:03 | 27.50 |
August | 670050.10 | 508.12 | 29-AUG-08:04 | 26.67 |
September | 639779.07 | 516.55 | 14-SEP-08:04 | 23.67 |
October | 1136188.54 | 707.96 | 26-OCT-01:03 | 7.33 |
November | 6793689.06 | 712.03 | 23-NOV-01:42 | 4.17 |
December | 33004070.22 | 711.73 | 14-DEC-00:32 | 4.67 |
Annual Sum or Average | 86673057.27 | |||
Minimum of Months | 205118.68 | 508.12 | 4.17 | |
Maximum of Months | 33004070.22 | 823.46 | 27.67 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.136942E+11 | 13190.31 | 02-JAN-20:10 | 0.121516E+11 | 9632.53 | 02-JAN-20:10 |
February | 0.123646E+11 | 13190.31 | 01-FEB-20:10 | 0.109726E+11 | 9632.53 | 01-FEB-20:10 |
March | 0.137364E+11 | 13190.31 | 01-MAR-20:10 | 0.121771E+11 | 9632.53 | 01-MAR-20:10 |
April | 0.132299E+11 | 13190.31 | 03-APR-19:10 | 0.117446E+11 | 9632.53 | 03-APR-19:10 |
May | 0.137180E+11 | 13190.31 | 01-MAY-19:10 | 0.121662E+11 | 9632.53 | 01-MAY-19:10 |
June | 0.132906E+11 | 13190.31 | 01-JUN-19:10 | 0.117829E+11 | 9632.53 | 01-JUN-19:10 |
July | 0.136573E+11 | 13190.31 | 03-JUL-19:10 | 0.121279E+11 | 9632.53 | 03-JUL-19:10 |
August | 0.137417E+11 | 13190.31 | 01-AUG-19:10 | 0.121808E+11 | 9632.53 | 01-AUG-19:10 |
September | 0.132352E+11 | 13190.31 | 01-SEP-19:10 | 0.117482E+11 | 9632.53 | 01-SEP-19:10 |
October | 0.136889E+11 | 13190.31 | 02-OCT-19:10 | 0.121479E+11 | 9632.53 | 02-OCT-19:10 |
November | 0.132800E+11 | 13190.31 | 01-NOV-19:10 | 0.117774E+11 | 9632.53 | 01-NOV-19:10 |
December | 0.136573E+11 | 13190.31 | 01-DEC-20:10 | 0.121279E+11 | 9632.53 | 01-DEC-20:10 |
Annual Sum or Average | 0.161294E+12 | 0.143105E+12 | ||||
Minimum of Months | 0.123646E+11 | 13190.31 | 0.109726E+11 | 9632.53 | ||
Maximum of Months | 0.137417E+11 | 13190.31 | 0.121808E+11 | 9632.53 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.620421E+09 | 597.59 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.560184E+09 | 597.59 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.622334E+09 | 597.59 | 01-MAR-20:10 | 0.866718E+09 | 685.60 | 01-MAR-20:10 |
April | 0.599386E+09 | 597.59 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.621497E+09 | 597.59 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.602135E+09 | 597.59 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.618748E+09 | 597.59 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.622573E+09 | 597.59 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.599625E+09 | 597.59 | 01-SEP-19:10 | 0.836191E+09 | 685.60 | 01-SEP-19:10 |
October | 0.620182E+09 | 597.59 | 02-OCT-19:10 | 0.864640E+09 | 685.60 | 02-OCT-19:10 |
November | 0.601657E+09 | 597.59 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.618748E+09 | 597.59 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.730749E+10 | 0.101856E+11 | ||||
Minimum of Months | 0.560184E+09 | 597.59 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.622573E+09 | 597.59 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.718450E+09 | 692.02 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.648695E+09 | 692.02 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.720665E+09 | 692.02 | 01-MAR-20:10 | 0.100366E+10 | 793.93 | 01-MAR-20:10 |
April | 0.694091E+09 | 692.02 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.719696E+09 | 692.02 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.697275E+09 | 692.02 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.716513E+09 | 692.02 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.720942E+09 | 692.02 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.694368E+09 | 692.02 | 01-SEP-19:10 | 0.968312E+09 | 793.93 | 01-SEP-19:10 |
October | 0.718174E+09 | 692.02 | 02-OCT-19:10 | 0.100126E+10 | 793.93 | 02-OCT-19:10 |
November | 0.696721E+09 | 692.02 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.716513E+09 | 692.02 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.846210E+10 | 0.117950E+11 | ||||
Minimum of Months | 0.648695E+09 | 692.02 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.720942E+09 | 692.02 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.710312E+09 | 684.18 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.641347E+09 | 684.18 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.712502E+09 | 684.18 | 01-MAR-20:10 | 0.106120E+10 | 839.45 | 01-MAR-20:10 |
April | 0.686229E+09 | 684.18 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.711544E+09 | 684.18 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.689376E+09 | 684.18 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.708397E+09 | 684.18 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.712775E+09 | 684.18 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.686503E+09 | 684.18 | 01-SEP-19:10 | 0.102382E+10 | 839.45 | 01-SEP-19:10 |
October | 0.710039E+09 | 684.18 | 02-OCT-19:10 | 0.105866E+10 | 839.45 | 02-OCT-19:10 |
November | 0.688829E+09 | 684.18 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.708397E+09 | 684.18 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.836625E+10 | 0.124712E+11 | ||||
Minimum of Months | 0.641347E+09 | 684.18 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.712775E+09 | 684.18 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.261454E+09 | 251.84 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.236069E+09 | 251.84 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.262260E+09 | 251.84 | 01-MAR-20:10 | 0.306128E+09 | 242.16 | 01-MAR-20:10 |
April | 0.252589E+09 | 251.84 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.261907E+09 | 251.84 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.253748E+09 | 251.84 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.260749E+09 | 251.84 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.262360E+09 | 251.84 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.252690E+09 | 251.84 | 01-SEP-19:10 | 0.295345E+09 | 242.16 | 01-SEP-19:10 |
October | 0.261353E+09 | 251.84 | 02-OCT-19:10 | 0.305393E+09 | 242.16 | 02-OCT-19:10 |
November | 0.253546E+09 | 251.84 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.260749E+09 | 251.84 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.307947E+10 | 0.359760E+10 | ||||
Minimum of Months | 0.236069E+09 | 251.84 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.262360E+09 | 251.84 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.337502E+09 | 325.08 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.304733E+09 | 325.08 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.338542E+09 | 325.08 | 01-MAR-20:10 | 0.578079E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.326059E+09 | 325.08 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.338087E+09 | 325.08 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.327554E+09 | 325.08 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.336592E+09 | 325.08 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.338672E+09 | 325.08 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.326189E+09 | 325.08 | 01-SEP-19:10 | 0.557718E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.337372E+09 | 325.08 | 02-OCT-19:10 | 0.576693E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.327294E+09 | 325.08 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.336592E+09 | 325.08 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.397519E+10 | 0.679355E+11 | ||||
Minimum of Months | 0.304733E+09 | 325.08 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.338672E+09 | 325.08 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.131164E+10 | 1701.53 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.118120E+10 | 1701.53 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.122987E+10 | 1701.53 | 01-MAR-20:10 | 0.122027E+10 | 965.27 | 01-MAR-20:10 |
April | 0.112540E+10 | 1701.53 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.110891E+10 | 1701.53 | 01-MAY-19:10 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.100416E+10 | 1701.53 | 01-JUN-19:19 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.106539E+10 | 1701.53 | 03-JUL-19:19 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.117264E+10 | 1701.53 | 01-AUG-19:10 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.116624E+10 | 1701.53 | 01-SEP-19:10 | 0.117729E+10 | 965.27 | 01-SEP-19:10 |
October | 0.126210E+10 | 1701.53 | 02-OCT-19:10 | 0.121734E+10 | 965.27 | 02-OCT-19:10 |
November | 0.125740E+10 | 1701.53 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.132084E+10 | 1701.53 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.142058E+11 | 0.143405E+11 | ||||
Minimum of Months | 0.100416E+10 | 1701.53 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.132084E+10 | 1701.53 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.941761E+10 | 9504.80 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.852043E+10 | 9504.80 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.939752E+10 | 9504.80 | 01-MAR-20:10 | 0.126786E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.899636E+10 | 9504.80 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.929742E+10 | 9504.80 | 01-MAY-19:10 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.898034E+10 | 9504.80 | 01-JUN-19:19 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.924329E+10 | 9504.80 | 03-JUL-19:19 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.937166E+10 | 9504.80 | 01-AUG-19:10 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.903632E+10 | 9504.80 | 01-SEP-19:10 | 0.122320E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.938587E+10 | 9504.80 | 02-OCT-19:10 | 0.126482E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.912659E+10 | 9504.80 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.940611E+10 | 9504.80 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.110180E+12 | 0.148998E+12 | ||||
Minimum of Months | 0.852043E+10 | 9504.80 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.941761E+10 | 9504.80 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196602E+09 | 177.88 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.177551E+09 | 177.88 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.195039E+09 | 177.88 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.190486E+09 | 177.88 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.195821E+09 | 177.88 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.188975E+09 | 177.88 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.197358E+09 | 177.88 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.195039E+09 | 177.88 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.190538E+09 | 177.88 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.196576E+09 | 177.88 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.189731E+09 | 177.88 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.197383E+09 | 177.88 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.231110E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.177551E+09 | 177.88 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.197383E+09 | 177.88 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196579E+09 | 177.86 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.177530E+09 | 177.86 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.195017E+09 | 177.86 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.190464E+09 | 177.86 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.195798E+09 | 177.86 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.188953E+09 | 177.86 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.197334E+09 | 177.86 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.195017E+09 | 177.86 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.190515E+09 | 177.86 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.196553E+09 | 177.86 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.189708E+09 | 177.86 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.197360E+09 | 177.86 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.231083E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.177530E+09 | 177.86 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.197360E+09 | 177.86 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123557E+09 | 111.79 | 01-JAN-19:10 | 0.217935E+09 | 232.19 | 01-JAN-08:09 |
February | 0.111584E+09 | 111.79 | 01-FEB-20:10 | 0.196843E+09 | 232.19 | 01-FEB-07:10 |
March | 0.122575E+09 | 111.79 | 01-MAR-20:10 | 0.217824E+09 | 232.19 | 01-MAR-07:10 |
April | 0.119713E+09 | 111.79 | 01-APR-18:10 | 0.210923E+09 | 232.19 | 01-APR-07:10 |
May | 0.123066E+09 | 111.79 | 01-MAY-19:10 | 0.217879E+09 | 232.19 | 01-MAY-06:10 |
June | 0.118764E+09 | 111.79 | 01-JUN-19:10 | 0.210812E+09 | 232.19 | 01-JUN-06:10 |
July | 0.124032E+09 | 111.79 | 01-JUL-18:10 | 0.217991E+09 | 232.19 | 01-JUL-07:10 |
August | 0.122575E+09 | 111.79 | 01-AUG-19:10 | 0.217824E+09 | 232.19 | 01-AUG-06:10 |
September | 0.119746E+09 | 111.79 | 01-SEP-19:10 | 0.210923E+09 | 232.19 | 01-SEP-06:10 |
October | 0.123541E+09 | 111.79 | 01-OCT-18:10 | 0.217935E+09 | 232.19 | 01-OCT-07:10 |
November | 0.119238E+09 | 111.79 | 01-NOV-19:10 | 0.210867E+09 | 232.19 | 01-NOV-06:10 |
December | 0.124048E+09 | 111.79 | 01-DEC-20:10 | 0.217991E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.145244E+10 | 0.256575E+10 | ||||
Minimum of Months | 0.111584E+09 | 111.79 | 0.196843E+09 | 232.19 | ||
Maximum of Months | 0.124048E+09 | 111.79 | 0.217991E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123591E+09 | 111.82 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 0.111614E+09 | 111.82 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 0.122608E+09 | 111.82 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 0.119746E+09 | 111.82 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 0.123099E+09 | 111.82 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 0.118796E+09 | 111.82 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 0.124066E+09 | 111.82 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 0.122608E+09 | 111.82 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 0.119778E+09 | 111.82 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 0.123574E+09 | 111.82 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 0.119271E+09 | 111.82 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 0.124082E+09 | 111.82 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.145283E+10 | 0.256645E+10 | ||||
Minimum of Months | 0.111614E+09 | 111.82 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 0.124082E+09 | 111.82 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196602E+09 | 177.88 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.177551E+09 | 177.88 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.195039E+09 | 177.88 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.190486E+09 | 177.88 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.195821E+09 | 177.88 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.188975E+09 | 177.88 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.197358E+09 | 177.88 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.195039E+09 | 177.88 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.190538E+09 | 177.88 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.196576E+09 | 177.88 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.189731E+09 | 177.88 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.197383E+09 | 177.88 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.231110E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.177551E+09 | 177.88 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.197383E+09 | 177.88 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196579E+09 | 177.86 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.177530E+09 | 177.86 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.195017E+09 | 177.86 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.190464E+09 | 177.86 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.195798E+09 | 177.86 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.188953E+09 | 177.86 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.197334E+09 | 177.86 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.195017E+09 | 177.86 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.190515E+09 | 177.86 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.196553E+09 | 177.86 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.189708E+09 | 177.86 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.197360E+09 | 177.86 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.231083E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.177530E+09 | 177.86 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.197360E+09 | 177.86 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.193865E+10 | 1867.32 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.175042E+10 | 1867.32 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.194462E+10 | 1867.32 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.187292E+10 | 1867.32 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.194201E+10 | 1867.32 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.188151E+10 | 1867.32 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.193342E+10 | 1867.32 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.194537E+10 | 1867.32 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.187367E+10 | 1867.32 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.193790E+10 | 1867.32 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.188002E+10 | 1867.32 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.193342E+10 | 1867.32 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.228339E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.175042E+10 | 1867.32 | 0.00 | 0.00 | |
Maximum of Months | 0.194537E+10 | 1867.32 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196602E+09 | 177.88 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.177551E+09 | 177.88 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.195039E+09 | 177.88 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.190486E+09 | 177.88 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.195821E+09 | 177.88 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.188975E+09 | 177.88 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.197358E+09 | 177.88 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.195039E+09 | 177.88 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.190538E+09 | 177.88 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.196576E+09 | 177.88 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.189731E+09 | 177.88 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.197383E+09 | 177.88 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.231110E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.177551E+09 | 177.88 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.197383E+09 | 177.88 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196579E+09 | 177.86 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.177530E+09 | 177.86 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.195017E+09 | 177.86 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.190464E+09 | 177.86 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.195798E+09 | 177.86 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.188953E+09 | 177.86 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.197334E+09 | 177.86 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.195017E+09 | 177.86 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.190515E+09 | 177.86 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.196553E+09 | 177.86 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.189708E+09 | 177.86 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.197360E+09 | 177.86 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.231083E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.177530E+09 | 177.86 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.197360E+09 | 177.86 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123591E+09 | 111.82 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 0.111614E+09 | 111.82 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 0.122608E+09 | 111.82 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 0.119746E+09 | 111.82 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 0.123099E+09 | 111.82 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 0.118796E+09 | 111.82 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 0.124066E+09 | 111.82 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 0.122608E+09 | 111.82 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 0.119778E+09 | 111.82 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 0.123574E+09 | 111.82 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 0.119271E+09 | 111.82 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 0.124082E+09 | 111.82 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.145283E+10 | 0.256645E+10 | ||||
Minimum of Months | 0.111614E+09 | 111.82 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 0.124082E+09 | 111.82 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.282599E+10 | 2988.03 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.252316E+10 | 2988.03 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.268928E+10 | 2988.03 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.249094E+10 | 2988.03 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.247993E+10 | 2988.03 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.231901E+10 | 2988.03 | 01-JUN-19:19 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.243156E+10 | 2988.03 | 03-JUL-19:30 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.259008E+10 | 2988.03 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.254782E+10 | 2988.03 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.276953E+10 | 2988.03 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.272091E+10 | 2988.03 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.282446E+10 | 2988.03 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.312127E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.231901E+10 | 2988.03 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.282599E+10 | 2988.03 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.282599E+10 | 2988.03 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.252316E+10 | 2988.03 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.268928E+10 | 2988.03 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.249094E+10 | 2988.03 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.247993E+10 | 2988.03 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.231901E+10 | 2988.03 | 01-JUN-19:19 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.243156E+10 | 2988.03 | 03-JUL-19:30 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.259008E+10 | 2988.03 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.254782E+10 | 2988.03 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.276953E+10 | 2988.03 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.272091E+10 | 2988.03 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.282446E+10 | 2988.03 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.312127E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.231901E+10 | 2988.03 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.282599E+10 | 2988.03 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.110133E+10 | 1060.81 | 02-JAN-20:10 | 0.368383E+11 | 16487.34 | 01-JAN-07:10 |
February | 0.994402E+09 | 1060.81 | 01-FEB-20:10 | 0.332733E+11 | 16487.34 | 01-FEB-07:10 |
March | 0.110473E+10 | 1060.81 | 01-MAR-20:10 | 0.368383E+11 | 16487.34 | 01-MAR-07:10 |
April | 0.106399E+10 | 1060.81 | 03-APR-19:10 | 0.356500E+11 | 16487.34 | 01-APR-06:10 |
May | 0.110324E+10 | 1060.81 | 01-MAY-19:10 | 0.368383E+11 | 16487.34 | 01-MAY-06:10 |
June | 0.106887E+10 | 1060.81 | 01-JUN-19:10 | 0.356500E+11 | 16487.34 | 01-JUN-06:10 |
July | 0.109836E+10 | 1060.81 | 03-JUL-19:10 | 0.368383E+11 | 16487.34 | 01-JUL-06:10 |
August | 0.110515E+10 | 1060.81 | 01-AUG-19:10 | 0.368383E+11 | 16487.34 | 01-AUG-06:10 |
September | 0.106442E+10 | 1060.81 | 01-SEP-19:10 | 0.356500E+11 | 16487.34 | 01-SEP-06:10 |
October | 0.110091E+10 | 1060.81 | 02-OCT-19:10 | 0.368383E+11 | 16487.34 | 01-OCT-06:10 |
November | 0.106802E+10 | 1060.81 | 01-NOV-19:10 | 0.356500E+11 | 16487.34 | 01-NOV-06:10 |
December | 0.109836E+10 | 1060.81 | 01-DEC-20:10 | 0.368383E+11 | 16487.34 | 01-DEC-07:10 |
Annual Sum or Average | 0.129718E+11 | 0.433742E+12 | ||||
Minimum of Months | 0.994402E+09 | 1060.81 | 0.332733E+11 | 16487.34 | ||
Maximum of Months | 0.110515E+10 | 1060.81 | 0.368383E+11 | 16487.34 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.205176E+10 | 1976.27 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.185255E+10 | 1976.27 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.205809E+10 | 1976.27 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.198220E+10 | 1976.27 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.205532E+10 | 1976.27 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.199129E+10 | 1976.27 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.204623E+10 | 1976.27 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.205888E+10 | 1976.27 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.198299E+10 | 1976.27 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.205097E+10 | 1976.27 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.198971E+10 | 1976.27 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.204623E+10 | 1976.27 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.241662E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.185255E+10 | 1976.27 | 0.00 | 0.00 | |
Maximum of Months | 0.205888E+10 | 1976.27 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.136942E+11 | 0.121516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.123646E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196682E+11 | 0.137364E+11 | 0.121771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.132299E+11 | 0.117446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.137180E+11 | 0.121662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.132906E+11 | 0.117829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.136573E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.137417E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189689E+11 | 0.132352E+11 | 0.117482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195854E+11 | 0.136889E+11 | 0.121479E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.132800E+11 | 0.117774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.136573E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230861E+12 | 0.161294E+12 | 0.143105E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.176991E+11 | 0.123646E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196682E+11 | 0.137417E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.620421E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1049702.65 | 0.108313E+09 |
February | 0.179968E+10 | 0.560184E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111223E+09 |
March | 0.199990E+10 | 0.622334E+09 | 0.866718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3065341.35 | 92961354.98 |
April | 0.192973E+10 | 0.599386E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 28789823.05 | 30681780.85 |
May | 0.199475E+10 | 0.621497E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 49555654.92 | 14864684.01 |
June | 0.193394E+10 | 0.602135E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 90096503.54 | 2419886.07 |
July | 0.199054E+10 | 0.618748E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 83449330.69 | 1468077.73 |
August | 0.199896E+10 | 0.622573E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 76928058.19 | 2097464.87 |
September | 0.192879E+10 | 0.599625E+09 | 0.836191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 53238000.55 | 5090143.59 |
October | 0.199148E+10 | 0.620182E+09 | 0.864640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19508322.43 | 52053586.49 |
November | 0.192552E+10 | 0.601657E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1961929.82 | 96357648.15 |
December | 0.199054E+10 | 0.618748E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 281520.13 | 0.141471E+09 |
Annual Sum or Average | 0.234744E+11 | 0.730749E+10 | 0.101856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.407924E+09 | 0.659001E+09 |
Minimum of Months | 0.179968E+10 | 0.560184E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1468077.73 |
Maximum of Months | 0.199990E+10 | 0.622573E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 90096503.54 | 0.141471E+09 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.718450E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 706206.65 | 45168464.75 |
February | 0.208403E+10 | 0.648695E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47372456.27 |
March | 0.231589E+10 | 0.720665E+09 | 0.100366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1392874.30 | 40977991.46 |
April | 0.223463E+10 | 0.694091E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11584508.30 | 14251115.94 |
May | 0.230993E+10 | 0.719696E+09 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19225155.06 | 7476484.24 |
June | 0.223950E+10 | 0.697275E+09 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 34770907.44 | 1290864.61 |
July | 0.230505E+10 | 0.716513E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 32122383.07 | 824257.09 |
August | 0.231480E+10 | 0.720942E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29619176.02 | 1264108.66 |
September | 0.223354E+10 | 0.694368E+09 | 0.968312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20686887.09 | 2749383.54 |
October | 0.230614E+10 | 0.718174E+09 | 0.100126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7883456.41 | 22626160.81 |
November | 0.222975E+10 | 0.696721E+09 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 964492.99 | 40892150.66 |
December | 0.230505E+10 | 0.716513E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 218525.87 | 58613026.00 |
Annual Sum or Average | 0.271834E+11 | 0.846210E+10 | 0.117950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159175E+09 | 0.283506E+09 |
Minimum of Months | 0.208403E+10 | 0.648695E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 824257.09 |
Maximum of Months | 0.231589E+10 | 0.720942E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34770907.44 | 58613026.00 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.487480E+09 | 0.710312E+09 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3312180.03 | 93562886.22 |
February | 0.440737E+09 | 0.641347E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5786.35 | 0.100232E+09 |
March | 0.489771E+09 | 0.712502E+09 | 0.106120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4348277.29 | 86353857.25 |
April | 0.472586E+09 | 0.686229E+09 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29610934.90 | 30622138.94 |
May | 0.488511E+09 | 0.711544E+09 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45679755.59 | 16806569.99 |
June | 0.473617E+09 | 0.689376E+09 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81514652.08 | 3047014.24 |
July | 0.487480E+09 | 0.708397E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75164109.38 | 1923895.54 |
August | 0.489542E+09 | 0.712775E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69591901.75 | 2891963.51 |
September | 0.472357E+09 | 0.686503E+09 | 0.102382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48784365.70 | 6263990.54 |
October | 0.487709E+09 | 0.710039E+09 | 0.105866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20006521.35 | 48513710.06 |
November | 0.471555E+09 | 0.688829E+09 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3547445.32 | 85835222.57 |
December | 0.487480E+09 | 0.708397E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1172061.27 | 0.123250E+09 |
Annual Sum or Average | 0.574883E+10 | 0.836625E+10 | 0.124712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382738E+09 | 0.599304E+09 |
Minimum of Months | 0.440737E+09 | 0.641347E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5786.35 | 1923895.54 |
Maximum of Months | 0.489771E+09 | 0.712775E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81514652.08 | 0.123250E+09 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.374985E+09 | 0.261454E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1955562.31 | 52547829.78 |
February | 0.339028E+09 | 0.236069E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4768.02 | 56312037.42 |
March | 0.376747E+09 | 0.262260E+09 | 0.306128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2596184.37 | 48294444.23 |
April | 0.363528E+09 | 0.252589E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17597508.06 | 16753540.46 |
May | 0.375778E+09 | 0.261907E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26880326.72 | 9101236.64 |
June | 0.364321E+09 | 0.253748E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 47093753.07 | 1709015.77 |
July | 0.374985E+09 | 0.260749E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 43460760.99 | 1072008.55 |
August | 0.376571E+09 | 0.262360E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40336464.05 | 1541036.73 |
September | 0.363352E+09 | 0.252690E+09 | 0.295345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 28447952.29 | 3321527.14 |
October | 0.375161E+09 | 0.261353E+09 | 0.305393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11803769.04 | 26773787.13 |
November | 0.362735E+09 | 0.253546E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2102761.14 | 47978667.22 |
December | 0.374985E+09 | 0.260749E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 690153.42 | 69622225.40 |
Annual Sum or Average | 0.442217E+10 | 0.307947E+10 | 0.359760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222970E+09 | 0.335027E+09 |
Minimum of Months | 0.339028E+09 | 0.236069E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4768.02 | 1072008.55 |
Maximum of Months | 0.376747E+09 | 0.262360E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 47093753.07 | 69622225.40 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.337502E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 2184404.06 | 0.145450E+09 |
February | 0.139600E+10 | 0.304733E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159525E+09 |
March | 0.155131E+10 | 0.338542E+09 | 0.578079E+10 | 0.502211E+11 | 0.00 | 0.00 | 0.00 | 3969812.65 | 0.136008E+09 |
April | 0.149688E+10 | 0.326059E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 38331651.70 | 42042313.21 |
May | 0.154732E+10 | 0.338087E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 63310968.61 | 19789037.22 |
June | 0.150015E+10 | 0.327554E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 0.117399E+09 | 2592752.20 |
July | 0.154405E+10 | 0.336592E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.109709E+09 | 1738359.38 |
August | 0.155059E+10 | 0.338672E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 0.101686E+09 | 2882595.85 |
September | 0.149615E+10 | 0.326189E+09 | 0.557718E+10 | 0.484522E+11 | 0.00 | 0.00 | 0.00 | 71388938.78 | 6437197.69 |
October | 0.154478E+10 | 0.337372E+09 | 0.576693E+10 | 0.501006E+11 | 0.00 | 0.00 | 0.00 | 27148541.25 | 70674317.79 |
November | 0.149361E+10 | 0.327294E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 3110397.58 | 0.131345E+09 |
December | 0.154405E+10 | 0.336592E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 639994.28 | 0.193711E+09 |
Annual Sum or Average | 0.182090E+11 | 0.397519E+10 | 0.679355E+11 | 0.590196E+12 | 0.00 | 0.00 | 0.00 | 0.538878E+09 | 0.912196E+09 |
Minimum of Months | 0.139600E+10 | 0.304733E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1738359.38 |
Maximum of Months | 0.155131E+10 | 0.338672E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 0.117399E+09 | 0.193711E+09 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.131164E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2307351.71 | 0.268589E+09 |
February | 0.236489E+11 | 0.118120E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281313E+09 |
March | 0.262800E+11 | 0.122987E+10 | 0.122027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6093907.75 | 0.240305E+09 |
April | 0.253579E+11 | 0.112540E+10 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63292298.60 | 79906931.01 |
May | 0.262123E+11 | 0.110891E+10 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109760E+09 | 41376910.09 |
June | 0.254132E+11 | 0.100416E+10 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200274E+09 | 7250371.82 |
July | 0.261570E+11 | 0.106539E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184291E+09 | 4644046.39 |
August | 0.262677E+11 | 0.117264E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169453E+09 | 6982771.15 |
September | 0.253456E+11 | 0.116624E+10 | 0.117729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117269E+09 | 15187370.77 |
October | 0.261693E+11 | 0.126210E+10 | 0.121734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42811270.52 | 0.132167E+09 |
November | 0.253025E+11 | 0.125740E+10 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4216942.85 | 0.241202E+09 |
December | 0.261570E+11 | 0.132084E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 594466.63 | 0.349276E+09 |
Annual Sum or Average | 0.308468E+12 | 0.142058E+11 | 0.143405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.900363E+09 | 0.166820E+10 |
Minimum of Months | 0.236489E+11 | 0.100416E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4644046.39 |
Maximum of Months | 0.262800E+11 | 0.132084E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200274E+09 | 0.349276E+09 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.941761E+10 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 7523029.53 | 0.766651E+09 |
February | 0.702046E+11 | 0.852043E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.812576E+09 |
March | 0.780153E+11 | 0.939752E+10 | 0.126786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 20305114.54 | 0.697968E+09 |
April | 0.752779E+11 | 0.899636E+10 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188097E+09 | 0.234139E+09 |
May | 0.778146E+11 | 0.929742E+10 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.316703E+09 | 0.122114E+09 |
June | 0.754422E+11 | 0.898034E+10 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.572346E+09 | 21089694.28 |
July | 0.776503E+11 | 0.924329E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.527427E+09 | 13523079.31 |
August | 0.779788E+11 | 0.937166E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.485266E+09 | 20933634.47 |
September | 0.752414E+11 | 0.903632E+10 | 0.122320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.336900E+09 | 45126269.12 |
October | 0.776868E+11 | 0.938587E+10 | 0.126482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124924E+09 | 0.380546E+09 |
November | 0.751137E+11 | 0.912659E+10 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 12953022.22 | 0.692655E+09 |
December | 0.776503E+11 | 0.940611E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2161588.03 | 0.100039E+10 |
Annual Sum or Average | 0.915726E+12 | 0.110180E+12 | 0.148998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259461E+10 | 0.480771E+10 |
Minimum of Months | 0.702046E+11 | 0.852043E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13523079.31 |
Maximum of Months | 0.780153E+11 | 0.941761E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.572346E+09 | 0.100039E+10 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196602E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1538184.55 | 55302426.52 |
February | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1021.07 | 61626277.83 |
March | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2689956.49 | 50953434.45 |
April | 0.293479E+09 | 0.190486E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23463962.26 | 13078544.96 |
May | 0.303504E+09 | 0.195821E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37674430.09 | 4930581.95 |
June | 0.293842E+09 | 0.188975E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 65496359.29 | 245774.63 |
July | 0.303141E+09 | 0.197358E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 62748947.86 | 195486.80 |
August | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 58378201.47 | 266893.56 |
September | 0.293479E+09 | 0.190538E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 42952043.87 | 890780.55 |
October | 0.303322E+09 | 0.196576E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16444794.03 | 24100128.30 |
November | 0.293661E+09 | 0.189731E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2038179.55 | 49163469.96 |
December | 0.303141E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 422730.76 | 76852454.62 |
Annual Sum or Average | 0.357224E+10 | 0.231110E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313849E+09 | 0.337606E+09 |
Minimum of Months | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1021.07 | 195486.80 |
Maximum of Months | 0.303685E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 65496359.29 | 76852454.62 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196579E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1718989.67 | 55385488.41 |
February | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2203.34 | 60697190.20 |
March | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2529790.86 | 52156550.41 |
April | 0.293479E+09 | 0.190464E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22937215.09 | 14477954.72 |
May | 0.303504E+09 | 0.195798E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37014661.44 | 5891656.57 |
June | 0.293842E+09 | 0.188953E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 64628509.73 | 556376.72 |
July | 0.303141E+09 | 0.197334E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 62407977.03 | 351873.68 |
August | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 57785421.20 | 704133.34 |
September | 0.293479E+09 | 0.190515E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 42161818.14 | 1576087.52 |
October | 0.303322E+09 | 0.196553E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16055579.71 | 25535164.88 |
November | 0.293661E+09 | 0.189708E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2078604.33 | 49824517.16 |
December | 0.303141E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 543791.18 | 75135584.56 |
Annual Sum or Average | 0.357224E+10 | 0.231083E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309865E+09 | 0.342293E+09 |
Minimum of Months | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2203.34 | 351873.68 |
Maximum of Months | 0.303685E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 64628509.73 | 75135584.56 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.123557E+09 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21383.04 | 25781131.53 |
February | 0.00 | 0.111584E+09 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26896314.50 |
March | 0.00 | 0.122575E+09 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 57218.00 | 24113622.25 |
April | 0.00 | 0.119713E+09 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2302366.71 | 9393217.74 |
May | 0.00 | 0.123066E+09 | 0.217879E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4581841.57 | 5625369.99 |
June | 0.00 | 0.118764E+09 | 0.210812E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10179893.31 | 1592177.56 |
July | 0.00 | 0.124032E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8689085.78 | 1278142.93 |
August | 0.00 | 0.122575E+09 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8002717.56 | 1844861.68 |
September | 0.00 | 0.119746E+09 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5087468.86 | 3163726.75 |
October | 0.00 | 0.123541E+09 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1678912.13 | 14241384.94 |
November | 0.00 | 0.119238E+09 | 0.210867E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30662.57 | 23531336.40 |
December | 0.00 | 0.124048E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32121878.42 |
Annual Sum or Average | 0.00 | 0.145244E+10 | 0.256575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40631549.52 | 0.169583E+09 |
Minimum of Months | 0.00 | 0.111584E+09 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1278142.93 |
Maximum of Months | 0.00 | 0.124048E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10179893.31 | 32121878.42 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.123591E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 657486.07 | 15215083.05 |
February | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 493.70 | 16934722.30 |
March | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 779018.31 | 14354039.31 |
April | 0.293479E+09 | 0.119746E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6539476.25 | 3856769.47 |
May | 0.303504E+09 | 0.123099E+09 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10436099.27 | 1566759.43 |
June | 0.293842E+09 | 0.118796E+09 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18145761.49 | 118269.17 |
July | 0.303141E+09 | 0.124066E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17487031.31 | 81815.41 |
August | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16214772.83 | 162536.11 |
September | 0.293479E+09 | 0.119778E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11857414.13 | 387353.14 |
October | 0.303322E+09 | 0.123574E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4622433.98 | 6936606.51 |
November | 0.293661E+09 | 0.119271E+09 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 711560.65 | 13654525.48 |
December | 0.303141E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 222766.83 | 20914099.36 |
Annual Sum or Average | 0.357224E+10 | 0.145283E+10 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 87674314.83 | 94182578.73 |
Minimum of Months | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 493.70 | 81815.41 |
Maximum of Months | 0.303685E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18145761.49 | 20914099.36 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196602E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1540544.62 | 55664534.69 |
February | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1013.68 | 62205220.40 |
March | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2667602.85 | 51597452.22 |
April | 0.293479E+09 | 0.190486E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23423301.00 | 13276642.89 |
May | 0.303504E+09 | 0.195821E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37602488.57 | 4992526.54 |
June | 0.293842E+09 | 0.188975E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 65492368.89 | 245823.51 |
July | 0.303141E+09 | 0.197358E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 62682071.77 | 196695.26 |
August | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 58343668.39 | 278134.97 |
September | 0.293479E+09 | 0.190538E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 42917852.15 | 919411.97 |
October | 0.303322E+09 | 0.196576E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16437090.28 | 24359483.10 |
November | 0.293661E+09 | 0.189731E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2028160.05 | 49398216.20 |
December | 0.303141E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 422181.55 | 77347435.81 |
Annual Sum or Average | 0.357224E+10 | 0.231110E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313558E+09 | 0.340482E+09 |
Minimum of Months | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1013.68 | 196695.26 |
Maximum of Months | 0.303685E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 65492368.89 | 77347435.81 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196579E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1645029.33 | 55332442.08 |
February | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1011.23 | 61183380.06 |
March | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2461055.85 | 52620680.96 |
April | 0.293479E+09 | 0.190464E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22769028.20 | 15316238.79 |
May | 0.303504E+09 | 0.195798E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 36786345.53 | 7076520.14 |
June | 0.293842E+09 | 0.188953E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 64517715.45 | 831957.14 |
July | 0.303141E+09 | 0.197334E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 62310389.10 | 501202.25 |
August | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 57652376.06 | 922162.54 |
September | 0.293479E+09 | 0.190515E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41981568.28 | 1936454.22 |
October | 0.303322E+09 | 0.196553E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15941654.28 | 26156706.07 |
November | 0.293661E+09 | 0.189708E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2036190.74 | 49741212.46 |
December | 0.303141E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 518116.28 | 75148494.24 |
Annual Sum or Average | 0.357224E+10 | 0.231083E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308620E+09 | 0.346767E+09 |
Minimum of Months | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1011.23 | 501202.25 |
Maximum of Months | 0.303685E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 64517715.45 | 75148494.24 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.385223E+10 | 0.193865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1983576.88 | 72902788.20 |
February | 0.348285E+10 | 0.175042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9321.95 | 76555023.70 |
March | 0.387034E+10 | 0.194462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3203921.99 | 66052957.53 |
April | 0.373454E+10 | 0.187292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22709501.28 | 23007825.59 |
May | 0.386038E+10 | 0.194201E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35716302.23 | 12217538.66 |
June | 0.374269E+10 | 0.188151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62936952.81 | 2231457.58 |
July | 0.385223E+10 | 0.193342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58253165.49 | 1417950.72 |
August | 0.386853E+10 | 0.194537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53891795.45 | 2057474.32 |
September | 0.373273E+10 | 0.187367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37680844.46 | 4517003.11 |
October | 0.385404E+10 | 0.193790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14853931.19 | 37560488.43 |
November | 0.372639E+10 | 0.188002E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2371730.50 | 66314344.75 |
December | 0.385223E+10 | 0.193342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 728918.21 | 95364978.45 |
Annual Sum or Average | 0.454292E+11 | 0.228339E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.294340E+09 | 0.460200E+09 |
Minimum of Months | 0.348285E+10 | 0.175042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9321.95 | 1417950.72 |
Maximum of Months | 0.387034E+10 | 0.194537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62936952.81 | 95364978.45 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196602E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1489574.58 | 55455965.02 |
February | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 836.35 | 61655822.83 |
March | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2634605.01 | 51081282.69 |
April | 0.293479E+09 | 0.190486E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23213719.53 | 13171794.46 |
May | 0.303504E+09 | 0.195821E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37358688.50 | 5021435.63 |
June | 0.293842E+09 | 0.188975E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 65041651.63 | 260805.53 |
July | 0.303141E+09 | 0.197358E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 62328051.95 | 206112.88 |
August | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 57947731.76 | 280343.95 |
September | 0.293479E+09 | 0.190538E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 42575315.27 | 912498.67 |
October | 0.303322E+09 | 0.196576E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16268594.54 | 24184381.02 |
November | 0.293661E+09 | 0.189731E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1994535.45 | 49276337.67 |
December | 0.303141E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 404896.68 | 76896249.36 |
Annual Sum or Average | 0.357224E+10 | 0.231110E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311258E+09 | 0.338403E+09 |
Minimum of Months | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 836.35 | 206112.88 |
Maximum of Months | 0.303685E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 65041651.63 | 76896249.36 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196579E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1739080.16 | 55272750.09 |
February | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1876.19 | 60567475.19 |
March | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2475494.04 | 52264668.39 |
April | 0.293479E+09 | 0.190464E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22725361.92 | 14443999.90 |
May | 0.303504E+09 | 0.195798E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 36752970.95 | 5737509.88 |
June | 0.293842E+09 | 0.188953E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 64230655.43 | 503371.04 |
July | 0.303141E+09 | 0.197334E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 62015721.94 | 322156.06 |
August | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 57405335.21 | 652941.36 |
September | 0.293479E+09 | 0.190515E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41856403.29 | 1448886.16 |
October | 0.303322E+09 | 0.196553E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15939861.17 | 25301477.57 |
November | 0.293661E+09 | 0.189708E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2069050.16 | 49584440.56 |
December | 0.303141E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 558261.58 | 74855760.80 |
Annual Sum or Average | 0.357224E+10 | 0.231083E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.307770E+09 | 0.340955E+09 |
Minimum of Months | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1876.19 | 322156.06 |
Maximum of Months | 0.303685E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 64230655.43 | 74855760.80 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.123591E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 741771.76 | 28790954.65 |
February | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 414.79 | 32171864.39 |
March | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1332503.29 | 26524914.01 |
April | 0.293479E+09 | 0.119746E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11866017.15 | 6753963.59 |
May | 0.303504E+09 | 0.123099E+09 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19123614.77 | 2569432.05 |
June | 0.293842E+09 | 0.118796E+09 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 33373732.18 | 133424.03 |
July | 0.303141E+09 | 0.124066E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 31909913.67 | 105454.55 |
August | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 29673627.85 | 143989.43 |
September | 0.293479E+09 | 0.119778E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21767332.30 | 473531.37 |
October | 0.303322E+09 | 0.123574E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8297267.67 | 12534765.42 |
November | 0.293661E+09 | 0.119271E+09 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 993986.75 | 25550850.86 |
December | 0.303141E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 201172.91 | 40087266.42 |
Annual Sum or Average | 0.357224E+10 | 0.145283E+10 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159281E+09 | 0.175840E+09 |
Minimum of Months | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 414.79 | 105454.55 |
Maximum of Months | 0.303685E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 33373732.18 | 40087266.42 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.282599E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1620383.80 | 0.175740E+09 |
February | 0.415303E+11 | 0.252316E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191561E+09 |
March | 0.461508E+11 | 0.268928E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3360224.36 | 0.165335E+09 |
April | 0.445315E+11 | 0.249094E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 38790951.97 | 54489275.51 |
May | 0.460320E+11 | 0.247993E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 66392550.85 | 28356668.88 |
June | 0.446286E+11 | 0.231901E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124963E+09 | 4995329.86 |
July | 0.459349E+11 | 0.243156E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114726E+09 | 3222226.19 |
August | 0.461292E+11 | 0.259008E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105640E+09 | 5008410.25 |
September | 0.445099E+11 | 0.254782E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 73087397.53 | 10692989.22 |
October | 0.459565E+11 | 0.276953E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 26998448.26 | 88084529.69 |
November | 0.444343E+11 | 0.272091E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2631608.81 | 0.159495E+09 |
December | 0.459349E+11 | 0.282446E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 451442.17 | 0.230536E+09 |
Annual Sum or Average | 0.541708E+12 | 0.312127E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.558662E+09 | 0.111752E+10 |
Minimum of Months | 0.415303E+11 | 0.231901E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3222226.19 |
Maximum of Months | 0.461508E+11 | 0.282599E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124963E+09 | 0.230536E+09 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.282599E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1425934.31 | 0.177101E+09 |
February | 0.415303E+11 | 0.252316E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193385E+09 |
March | 0.461508E+11 | 0.268928E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3225296.08 | 0.166734E+09 |
April | 0.445315E+11 | 0.249094E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 38645386.90 | 54617311.01 |
May | 0.460320E+11 | 0.247993E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 66344125.23 | 28362231.42 |
June | 0.446286E+11 | 0.231901E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124948E+09 | 4995457.05 |
July | 0.459349E+11 | 0.243156E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114710E+09 | 3222333.16 |
August | 0.461292E+11 | 0.259008E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105619E+09 | 5008578.39 |
September | 0.445099E+11 | 0.254782E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 73048275.65 | 10695234.16 |
October | 0.459565E+11 | 0.276953E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 26857133.46 | 88602514.88 |
November | 0.444343E+11 | 0.272091E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2410824.33 | 0.160624E+09 |
December | 0.459349E+11 | 0.282446E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 365597.04 | 0.232585E+09 |
Annual Sum or Average | 0.541708E+12 | 0.312127E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.557600E+09 | 0.112593E+10 |
Minimum of Months | 0.415303E+11 | 0.231901E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3222333.16 |
Maximum of Months | 0.461508E+11 | 0.282599E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124948E+09 | 0.232585E+09 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.110133E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 1245630.86 | 0.158068E+09 |
February | 0.369574E+10 | 0.994402E+09 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173032E+09 |
March | 0.410691E+10 | 0.110473E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 2860480.04 | 0.148872E+09 |
April | 0.396281E+10 | 0.106399E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 34601107.07 | 48705117.89 |
May | 0.409635E+10 | 0.110324E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 59429362.04 | 25324176.34 |
June | 0.397146E+10 | 0.106887E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.111915E+09 | 4468974.80 |
July | 0.408770E+10 | 0.109836E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.102741E+09 | 2882445.06 |
August | 0.410499E+10 | 0.110515E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 94588323.02 | 4475062.03 |
September | 0.396089E+10 | 0.106442E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 65416499.38 | 9560555.27 |
October | 0.408962E+10 | 0.110091E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 24031658.44 | 79150067.27 |
November | 0.395417E+10 | 0.106802E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 2104223.05 | 0.143305E+09 |
December | 0.408770E+10 | 0.109836E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 306174.35 | 0.207816E+09 |
Annual Sum or Average | 0.482060E+11 | 0.129718E+11 | 0.392709E+12 | 0.359593E+12 | 0.00 | 0.00 | 0.00 | 0.499240E+09 | 0.100566E+10 |
Minimum of Months | 0.369574E+10 | 0.994402E+09 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2882445.06 |
Maximum of Months | 0.410691E+10 | 0.110515E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.111915E+09 | 0.207816E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.407704E+10 | 0.205176E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2630790.13 | 0.126847E+09 |
February | 0.368610E+10 | 0.185255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135109E+09 |
March | 0.409620E+10 | 0.205809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4628219.01 | 0.116115E+09 |
April | 0.395248E+10 | 0.198220E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36261539.25 | 40355078.04 |
May | 0.408566E+10 | 0.205532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59519659.73 | 21311763.10 |
June | 0.396110E+10 | 0.199129E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109819E+09 | 3762104.65 |
July | 0.407704E+10 | 0.204623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100987E+09 | 2395707.23 |
August | 0.409429E+10 | 0.205888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93278975.87 | 3549588.49 |
September | 0.395056E+10 | 0.198299E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64777555.88 | 7750862.85 |
October | 0.407896E+10 | 0.205097E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25031755.86 | 63828736.36 |
November | 0.394385E+10 | 0.198971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3451918.15 | 0.114747E+09 |
December | 0.407704E+10 | 0.204623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 880125.44 | 0.167120E+09 |
Annual Sum or Average | 0.480803E+11 | 0.241662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.501266E+09 | 0.802891E+09 |
Minimum of Months | 0.368610E+10 | 0.185255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2395707.23 |
Maximum of Months | 0.409620E+10 | 0.205888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109819E+09 | 0.167120E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 13190.31 | 02-JAN-20:10 | 9632.53 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 13190.31 | 01-FEB-20:10 | 9632.53 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 13190.31 | 01-MAR-20:10 | 9632.53 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 13190.31 | 03-APR-19:10 | 9632.53 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 13190.31 | 01-MAY-19:10 | 9632.53 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 13190.31 | 01-JUN-19:10 | 9632.53 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 13190.31 | 03-JUL-19:10 | 9632.53 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 13190.31 | 01-AUG-19:10 | 9632.53 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 13190.31 | 01-SEP-19:10 | 9632.53 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 01-OCT-23:10 | 13190.31 | 02-OCT-19:10 | 9632.53 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 13190.31 | 01-NOV-19:10 | 9632.53 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 13190.31 | 01-DEC-20:10 | 9632.53 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 11501.89 | 13190.31 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 13190.31 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 597.59 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.64 | 31-JAN-16:00 | 106.77 | 01-JAN-08:00 |
February | 1169.53 | 01-FEB-00:10 | 597.59 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 84.17 | 01-FEB-04:52 |
March | 1169.53 | 01-MAR-00:10 | 597.59 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.68 | 20-MAR-17:00 | 106.40 | 26-MAR-06:00 |
April | 1169.53 | 01-APR-00:10 | 597.59 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.63 | 14-APR-16:00 | 67.92 | 21-APR-04:10 |
May | 1169.53 | 01-MAY-00:10 | 597.59 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.57 | 31-MAY-17:00 | 51.40 | 01-MAY-04:00 |
June | 1169.53 | 01-JUN-00:10 | 597.59 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.28 | 28-JUN-16:00 | 24.90 | 21-JUN-05:00 |
July | 1169.53 | 01-JUL-00:10 | 597.59 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.17 | 19-JUL-13:00 | 25.78 | 01-JUL-05:55 |
August | 1169.53 | 01-AUG-00:10 | 597.59 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.36 | 25-AUG-14:00 | 30.00 | 05-AUG-18:00 |
September | 1169.53 | 01-SEP-00:10 | 597.59 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.57 | 08-SEP-15:00 | 28.65 | 22-SEP-06:00 |
October | 1169.53 | 01-OCT-23:10 | 597.59 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.78 | 01-OCT-13:00 | 81.46 | 25-OCT-07:00 |
November | 1169.53 | 01-NOV-00:10 | 597.59 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.53 | 01-NOV-15:00 | 109.55 | 23-NOV-06:10 |
December | 1169.53 | 01-DEC-00:10 | 597.59 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.54 | 21-DEC-15:00 | 115.18 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1169.53 | 597.59 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.90 | |||||
Maximum of Months | 1169.53 | 597.59 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 81.28 | 115.18 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 692.02 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.07 | 31-JAN-16:00 | 44.47 | 01-JAN-08:00 |
February | 1354.32 | 01-FEB-00:10 | 692.02 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 36.43 | 01-FEB-05:50 |
March | 1354.32 | 01-MAR-00:10 | 692.02 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 20-MAR-17:00 | 44.28 | 26-MAR-06:00 |
April | 1354.32 | 01-APR-00:10 | 692.02 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.80 | 14-APR-15:00 | 30.56 | 21-APR-04:40 |
May | 1354.32 | 01-MAY-00:10 | 692.02 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.37 | 15-MAY-17:00 | 23.00 | 01-MAY-04:00 |
June | 1354.32 | 01-JUN-00:10 | 692.02 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.37 | 28-JUN-16:00 | 11.26 | 21-JUN-06:00 |
July | 1354.32 | 01-JUL-00:10 | 692.02 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.90 | 19-JUL-13:00 | 11.34 | 01-JUL-06:00 |
August | 1354.32 | 01-AUG-00:10 | 692.02 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.95 | 25-AUG-14:00 | 13.28 | 05-AUG-18:00 |
September | 1354.32 | 01-SEP-00:10 | 692.02 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.31 | 08-SEP-15:00 | 14.04 | 22-SEP-06:00 |
October | 1354.32 | 01-OCT-23:10 | 692.02 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.62 | 01-OCT-13:00 | 36.00 | 25-OCT-06:00 |
November | 1354.32 | 01-NOV-00:10 | 692.02 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 01-NOV-15:00 | 46.73 | 23-NOV-06:10 |
December | 1354.32 | 01-DEC-00:10 | 692.02 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.49 | 21-DEC-15:00 | 48.23 | 05-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1354.32 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.26 | |||||
Maximum of Months | 1354.32 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 31.37 | 48.23 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 286.42 | 02-JAN-00:10 | 684.18 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.08 | 31-JAN-16:50 | 97.42 | 01-JAN-08:00 |
February | 286.42 | 01-FEB-00:10 | 684.18 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.84 | 18-FEB-14:00 | 80.92 | 01-FEB-07:40 |
March | 286.42 | 01-MAR-00:10 | 684.18 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.50 | 20-MAR-17:00 | 99.88 | 26-MAR-04:00 |
April | 286.42 | 01-APR-00:10 | 684.18 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.49 | 14-APR-15:50 | 68.48 | 21-APR-04:40 |
May | 286.42 | 01-MAY-00:10 | 684.18 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.78 | 15-MAY-17:00 | 51.95 | 01-MAY-04:00 |
June | 286.42 | 01-JUN-00:10 | 684.18 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.15 | 28-JUN-16:00 | 26.60 | 21-JUN-06:00 |
July | 286.42 | 01-JUL-00:10 | 684.18 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.78 | 19-JUL-13:00 | 26.80 | 01-JUL-06:00 |
August | 286.42 | 01-AUG-00:10 | 684.18 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.83 | 25-AUG-14:00 | 31.19 | 05-AUG-18:00 |
September | 286.42 | 01-SEP-00:10 | 684.18 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.81 | 08-SEP-15:00 | 32.38 | 22-SEP-06:00 |
October | 286.42 | 01-OCT-23:10 | 684.18 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.20 | 01-OCT-13:00 | 81.76 | 25-OCT-06:30 |
November | 286.42 | 01-NOV-00:10 | 684.18 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.22 | 01-NOV-15:00 | 105.63 | 23-NOV-06:10 |
December | 286.42 | 01-DEC-00:10 | 684.18 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.99 | 21-DEC-15:00 | 107.96 | 05-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 286.42 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.84 | 26.60 | |||||
Maximum of Months | 286.42 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 74.15 | 107.96 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 220.32 | 02-JAN-00:10 | 251.84 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.80 | 31-JAN-17:00 | 56.20 | 01-JAN-08:00 |
February | 220.32 | 01-FEB-00:10 | 251.84 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 | 18-FEB-14:00 | 45.64 | 01-FEB-06:30 |
March | 220.32 | 01-MAR-00:10 | 251.84 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.94 | 20-MAR-17:00 | 56.59 | 26-MAR-04:00 |
April | 220.32 | 01-APR-00:10 | 251.84 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.04 | 14-APR-16:40 | 38.60 | 21-APR-04:10 |
May | 220.32 | 01-MAY-00:10 | 251.84 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.74 | 15-MAY-17:00 | 29.23 | 01-MAY-04:00 |
June | 220.32 | 01-JUN-00:10 | 251.84 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.78 | 28-JUN-16:00 | 15.27 | 21-JUN-06:00 |
July | 220.32 | 01-JUL-00:10 | 251.84 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.51 | 19-JUL-13:00 | 15.46 | 01-JUL-06:00 |
August | 220.32 | 01-AUG-00:10 | 251.84 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.78 | 25-AUG-14:00 | 17.07 | 05-AUG-18:00 |
September | 220.32 | 01-SEP-00:10 | 251.84 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.51 | 08-SEP-15:00 | 17.87 | 22-SEP-06:00 |
October | 220.32 | 01-OCT-23:10 | 251.84 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.83 | 01-OCT-13:00 | 46.04 | 25-OCT-06:00 |
November | 220.32 | 01-NOV-00:10 | 251.84 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.73 | 01-NOV-15:00 | 59.86 | 23-NOV-06:10 |
December | 220.32 | 01-DEC-00:10 | 251.84 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.96 | 21-DEC-15:00 | 61.35 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 220.32 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 | 15.27 | |||||
Maximum of Months | 220.32 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 42.78 | 61.35 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 325.08 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 35.26 | 31-JAN-17:00 | 152.42 | 01-JAN-08:00 |
February | 907.20 | 01-FEB-00:10 | 325.08 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 121.22 | 28-FEB-06:53 |
March | 907.20 | 01-MAR-00:10 | 325.08 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 35.78 | 20-MAR-17:00 | 151.37 | 26-MAR-06:00 |
April | 907.20 | 01-APR-00:10 | 325.08 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 70.38 | 14-APR-17:00 | 98.23 | 21-APR-05:10 |
May | 907.20 | 01-MAY-00:10 | 325.08 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 81.82 | 15-MAY-17:00 | 68.12 | 01-MAY-06:00 |
June | 907.20 | 01-JUN-00:10 | 325.08 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 108.84 | 28-JUN-17:00 | 36.33 | 21-JUN-06:00 |
July | 907.20 | 01-JUL-00:10 | 325.08 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 94.99 | 19-JUL-13:00 | 36.59 | 01-JUL-06:00 |
August | 907.20 | 01-AUG-00:10 | 325.08 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 103.89 | 25-AUG-17:00 | 42.87 | 05-AUG-18:00 |
September | 907.20 | 01-SEP-00:10 | 325.08 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 87.97 | 08-SEP-16:00 | 45.30 | 22-SEP-06:00 |
October | 907.20 | 01-OCT-23:10 | 325.08 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 81.04 | 01-OCT-13:00 | 120.49 | 25-OCT-07:00 |
November | 907.20 | 01-NOV-00:10 | 325.08 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 33.42 | 01-NOV-15:00 | 155.64 | 23-NOV-07:00 |
December | 907.20 | 01-DEC-00:10 | 325.08 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 18.50 | 25-DEC-16:00 | 163.00 | 05-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 907.20 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 36.33 | ||||||
Maximum of Months | 907.20 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 108.84 | 163.00 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 1701.53 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.27 | 31-JAN-17:00 | 255.86 | 01-JAN-08:00 |
February | 15368.40 | 01-FEB-00:10 | 1701.53 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 212.39 | 01-FEB-04:52 |
March | 15368.40 | 01-MAR-00:10 | 1701.53 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.81 | 20-MAR-17:00 | 248.67 | 26-MAR-05:10 |
April | 15368.40 | 01-APR-00:10 | 1701.53 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 111.95 | 14-APR-16:00 | 175.86 | 21-APR-04:10 |
May | 15368.40 | 01-MAY-00:10 | 1701.53 | 01-MAY-19:10 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 131.70 | 31-MAY-17:00 | 132.23 | 01-MAY-04:00 |
June | 15368.40 | 01-JUN-00:10 | 1701.53 | 01-JUN-19:19 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 179.69 | 28-JUN-16:00 | 64.44 | 21-JUN-06:00 |
July | 15368.40 | 01-JUL-00:10 | 1701.53 | 03-JUL-19:19 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 161.75 | 19-JUL-13:00 | 64.91 | 01-JUL-06:00 |
August | 15368.40 | 01-AUG-00:10 | 1701.53 | 01-AUG-19:10 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 171.02 | 25-AUG-14:00 | 71.69 | 05-AUG-18:00 |
September | 15368.40 | 01-SEP-00:10 | 1701.53 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.95 | 08-SEP-15:00 | 79.28 | 22-SEP-06:00 |
October | 15368.40 | 01-OCT-23:10 | 1701.53 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.16 | 01-OCT-13:00 | 203.20 | 25-OCT-06:00 |
November | 15368.40 | 01-NOV-00:10 | 1701.53 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.05 | 01-NOV-15:00 | 262.30 | 23-NOV-06:10 |
December | 15368.40 | 01-DEC-00:10 | 1701.53 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.10 | 21-DEC-15:00 | 279.82 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 15368.40 | 1701.53 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.44 | |||||
Maximum of Months | 15368.40 | 1701.53 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 179.69 | 279.82 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 9504.80 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 150.23 | 31-JAN-16:00 | 748.28 | 01-JAN-08:00 |
February | 45622.98 | 01-FEB-00:10 | 9504.80 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 611.74 | 01-FEB-06:00 |
March | 45622.98 | 01-MAR-00:10 | 9504.80 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 161.07 | 20-MAR-17:00 | 740.97 | 26-MAR-06:00 |
April | 45622.98 | 01-APR-00:10 | 9504.80 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 321.99 | 14-APR-17:00 | 510.37 | 21-APR-04:10 |
May | 45622.98 | 01-MAY-00:10 | 9504.80 | 01-MAY-19:10 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 384.03 | 15-MAY-17:00 | 377.89 | 01-MAY-04:00 |
June | 45622.98 | 01-JUN-00:10 | 9504.80 | 01-JUN-19:19 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 513.38 | 28-JUN-16:00 | 184.16 | 21-JUN-06:00 |
July | 45622.98 | 01-JUL-00:10 | 9504.80 | 03-JUL-19:19 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 471.43 | 19-JUL-13:00 | 185.49 | 01-JUL-06:00 |
August | 45622.98 | 01-AUG-00:10 | 9504.80 | 01-AUG-19:10 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 490.23 | 26-AUG-16:00 | 217.34 | 05-AUG-18:00 |
September | 45622.98 | 01-SEP-00:10 | 9504.80 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 414.13 | 08-SEP-15:00 | 229.75 | 22-SEP-06:00 |
October | 45622.98 | 01-OCT-23:10 | 9504.80 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 384.56 | 01-OCT-13:00 | 605.17 | 25-OCT-06:00 |
November | 45622.98 | 01-NOV-00:10 | 9504.80 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 148.70 | 01-NOV-15:00 | 777.15 | 23-NOV-06:10 |
December | 45622.98 | 01-DEC-00:10 | 9504.80 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.84 | 21-DEC-15:00 | 814.70 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 45622.98 | 9504.80 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184.16 | |||||
Maximum of Months | 45622.98 | 9504.80 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 513.38 | 814.70 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.88 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 21.53 | 31-JAN-16:50 | 62.43 | 01-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 177.88 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.43 | 18-FEB-16:07 | 48.02 | 28-FEB-06:53 |
March | 180.00 | 01-MAR-00:10 | 177.88 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.89 | 16-MAR-15:10 | 62.22 | 26-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 177.88 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.00 | 14-APR-16:00 | 38.56 | 21-APR-04:07 |
May | 180.00 | 01-MAY-00:10 | 177.88 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.15 | 31-MAY-17:00 | 26.50 | 01-MAY-04:00 |
June | 180.00 | 01-JUN-00:10 | 177.88 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.14 | 28-JUN-17:00 | 8.90 | 21-JUN-05:55 |
July | 180.00 | 01-JUL-00:10 | 177.88 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.44 | 20-JUL-15:10 | 8.96 | 01-JUL-06:00 |
August | 180.00 | 01-AUG-00:10 | 177.88 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.54 | 25-AUG-16:00 | 18.20 | 05-AUG-18:00 |
September | 180.00 | 01-SEP-00:10 | 177.88 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.55 | 08-SEP-16:00 | 13.00 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 177.88 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.09 | 03-OCT-16:00 | 47.73 | 25-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 177.88 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.00 | 01-NOV-15:10 | 64.05 | 23-NOV-06:07 |
December | 180.00 | 01-DEC-00:10 | 177.88 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.47 | 25-DEC-16:10 | 67.32 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 1.43 | 8.90 | |||||
Maximum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 54.14 | 67.32 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.86 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 21.53 | 31-JAN-17:00 | 62.43 | 01-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 177.86 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.43 | 18-FEB-16:07 | 48.02 | 28-FEB-06:53 |
March | 180.00 | 01-MAR-00:10 | 177.86 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.89 | 16-MAR-15:10 | 62.22 | 26-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 177.86 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.99 | 14-APR-16:00 | 38.56 | 21-APR-04:07 |
May | 180.00 | 01-MAY-00:10 | 177.86 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.14 | 31-MAY-17:00 | 26.49 | 01-MAY-04:00 |
June | 180.00 | 01-JUN-00:10 | 177.86 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.98 | 28-JUN-16:00 | 14.42 | 21-JUN-06:00 |
July | 180.00 | 01-JUL-00:10 | 177.86 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.45 | 20-JUL-15:10 | 14.15 | 01-JUL-06:00 |
August | 180.00 | 01-AUG-00:10 | 177.86 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.05 | 25-AUG-16:00 | 18.41 | 05-AUG-18:00 |
September | 180.00 | 01-SEP-00:10 | 177.86 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.61 | 08-SEP-15:10 | 15.71 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 177.86 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.09 | 03-OCT-16:00 | 47.73 | 25-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 177.86 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.00 | 01-NOV-15:09 | 64.05 | 23-NOV-06:07 |
December | 180.00 | 01-DEC-00:10 | 177.86 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.47 | 25-DEC-16:09 | 67.32 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 1.43 | 14.15 | |||||
Maximum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 53.98 | 67.32 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 111.79 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1.75 | 31-JAN-16:00 | 21.66 | 01-JAN-08:00 |
February | 0.00 | 01-FEB-00:10 | 111.79 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 18.00 | 02-FEB-07:00 |
March | 0.00 | 01-MAR-00:10 | 111.79 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.59 | 16-MAR-15:00 | 20.72 | 26-MAR-04:00 |
April | 0.00 | 01-APR-00:10 | 111.79 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.18 | 14-APR-15:00 | 14.93 | 21-APR-04:00 |
May | 0.00 | 01-MAY-00:10 | 111.79 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.64 | 31-MAY-17:00 | 11.88 | 01-MAY-04:00 |
June | 0.00 | 01-JUN-00:10 | 111.79 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.18 | 28-JUN-16:00 | 6.85 | 21-JUN-06:00 |
July | 0.00 | 01-JUL-00:10 | 111.79 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.84 | 19-JUL-13:00 | 6.90 | 01-JUL-05:55 |
August | 0.00 | 01-AUG-00:10 | 111.79 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.53 | 25-AUG-14:00 | 7.73 | 05-AUG-18:00 |
September | 0.00 | 01-SEP-00:10 | 111.79 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.61 | 08-SEP-15:00 | 8.05 | 22-SEP-06:00 |
October | 0.00 | 01-OCT-00:10 | 111.79 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.66 | 01-OCT-13:00 | 17.90 | 25-OCT-07:00 |
November | 0.00 | 01-NOV-00:10 | 111.79 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.74 | 01-NOV-15:00 | 21.85 | 23-NOV-06:20 |
December | 0.00 | 01-DEC-00:10 | 111.79 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 22.90 | 05-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 0.00 | 111.79 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.85 | |||||
Maximum of Months | 0.00 | 111.79 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 11.18 | 22.90 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 111.82 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6.01 | 31-JAN-16:04 | 17.42 | 01-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 111.82 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 | 18-FEB-16:04 | 13.70 | 28-FEB-06:55 |
March | 180.00 | 01-MAR-00:10 | 111.82 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 16-MAR-15:09 | 17.36 | 26-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 111.82 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.32 | 14-APR-16:00 | 10.76 | 21-APR-04:07 |
May | 180.00 | 01-MAY-00:10 | 111.82 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.76 | 31-MAY-17:00 | 7.39 | 01-MAY-04:00 |
June | 180.00 | 01-JUN-00:10 | 111.82 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.25 | 28-JUN-16:00 | 3.63 | 21-JUN-06:00 |
July | 180.00 | 01-JUL-00:10 | 111.82 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.80 | 20-JUL-15:10 | 3.36 | 01-JUL-06:00 |
August | 180.00 | 01-AUG-00:10 | 111.82 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.62 | 25-AUG-16:10 | 4.63 | 05-AUG-18:00 |
September | 180.00 | 01-SEP-00:10 | 111.82 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.73 | 08-SEP-15:10 | 4.33 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 111.82 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.35 | 03-OCT-16:00 | 13.32 | 25-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 111.82 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.86 | 01-NOV-15:07 | 17.88 | 23-NOV-06:10 |
December | 180.00 | 01-DEC-00:10 | 111.82 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.48 | 25-DEC-16:06 | 18.79 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 | 3.36 | |||||
Maximum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 15.25 | 18.79 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.88 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 21.53 | 31-JAN-16:50 | 62.43 | 01-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 177.88 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.42 | 18-FEB-16:07 | 48.74 | 01-FEB-08:10 |
March | 180.00 | 01-MAR-00:10 | 177.88 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.90 | 16-MAR-15:10 | 62.22 | 26-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 177.88 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.00 | 14-APR-15:50 | 38.56 | 21-APR-04:07 |
May | 180.00 | 01-MAY-00:10 | 177.88 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.15 | 31-MAY-17:00 | 26.50 | 01-MAY-04:00 |
June | 180.00 | 01-JUN-00:10 | 177.88 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.64 | 28-JUN-16:00 | 8.90 | 21-JUN-05:55 |
July | 180.00 | 01-JUL-00:10 | 177.88 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.45 | 20-JUL-15:10 | 8.96 | 01-JUL-06:00 |
August | 180.00 | 01-AUG-00:10 | 177.88 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.37 | 25-AUG-16:30 | 18.20 | 05-AUG-18:00 |
September | 180.00 | 01-SEP-00:10 | 177.88 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.61 | 08-SEP-15:10 | 13.00 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 177.88 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.09 | 03-OCT-16:00 | 48.40 | 25-OCT-07:10 |
November | 180.00 | 01-NOV-00:10 | 177.88 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.00 | 01-NOV-15:10 | 64.05 | 23-NOV-06:07 |
December | 180.00 | 01-DEC-00:10 | 177.88 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.47 | 25-DEC-16:10 | 67.32 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 1.42 | 8.90 | |||||
Maximum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 54.64 | 67.32 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.86 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 21.53 | 31-JAN-17:00 | 62.43 | 01-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 177.86 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.42 | 18-FEB-16:07 | 48.02 | 28-FEB-06:53 |
March | 180.00 | 01-MAR-00:10 | 177.86 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.89 | 16-MAR-15:07 | 62.22 | 26-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 177.86 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.99 | 14-APR-15:50 | 38.56 | 21-APR-04:07 |
May | 180.00 | 01-MAY-00:10 | 177.86 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.14 | 31-MAY-17:00 | 26.49 | 01-MAY-04:00 |
June | 180.00 | 01-JUN-00:10 | 177.86 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.63 | 28-JUN-16:00 | 16.26 | 21-JUN-06:00 |
July | 180.00 | 01-JUL-00:10 | 177.86 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.45 | 20-JUL-15:10 | 15.36 | 01-JUL-06:00 |
August | 180.00 | 01-AUG-00:10 | 177.86 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.37 | 25-AUG-16:20 | 18.76 | 05-AUG-18:00 |
September | 180.00 | 01-SEP-00:10 | 177.86 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.62 | 08-SEP-15:10 | 15.70 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 177.86 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.09 | 03-OCT-16:00 | 48.09 | 25-OCT-07:10 |
November | 180.00 | 01-NOV-00:10 | 177.86 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.00 | 01-NOV-15:07 | 64.05 | 23-NOV-06:07 |
December | 180.00 | 01-DEC-00:10 | 177.86 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.47 | 25-DEC-16:10 | 67.32 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 1.42 | 15.36 | |||||
Maximum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 54.63 | 67.32 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2263.36 | 02-JAN-00:10 | 1867.32 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.24 | 31-JAN-17:00 | 75.29 | 01-JAN-08:00 |
February | 2263.36 | 01-FEB-00:10 | 1867.32 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.27 | 18-FEB-14:00 | 62.59 | 01-FEB-04:52 |
March | 2263.36 | 01-MAR-00:10 | 1867.32 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.67 | 16-MAR-15:00 | 77.01 | 26-MAR-04:00 |
April | 2263.36 | 01-APR-00:10 | 1867.32 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.70 | 14-APR-17:00 | 52.99 | 21-APR-04:03 |
May | 2263.36 | 01-MAY-00:10 | 1867.32 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.41 | 15-MAY-17:00 | 39.28 | 01-MAY-04:00 |
June | 2263.36 | 01-JUN-00:10 | 1867.32 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.91 | 28-JUN-16:00 | 20.06 | 21-JUN-05:00 |
July | 2263.36 | 01-JUL-00:10 | 1867.32 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.69 | 19-JUL-13:00 | 20.42 | 01-JUL-06:00 |
August | 2263.36 | 01-AUG-00:10 | 1867.32 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.20 | 25-AUG-14:00 | 22.65 | 05-AUG-18:00 |
September | 2263.36 | 01-SEP-00:10 | 1867.32 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.88 | 08-SEP-15:00 | 23.87 | 22-SEP-06:00 |
October | 2263.36 | 01-OCT-23:10 | 1867.32 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.60 | 01-OCT-13:00 | 62.20 | 25-OCT-06:00 |
November | 2263.36 | 01-NOV-00:10 | 1867.32 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.65 | 01-NOV-15:00 | 81.37 | 23-NOV-06:10 |
December | 2263.36 | 01-DEC-00:10 | 1867.32 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.48 | 21-DEC-15:00 | 83.58 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.27 | 20.06 | ||||
Maximum of Months | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.91 | 83.58 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.88 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 21.37 | 31-JAN-16:50 | 62.63 | 01-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 177.88 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.26 | 18-FEB-16:07 | 48.21 | 28-FEB-06:53 |
March | 180.00 | 01-MAR-00:10 | 177.88 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.74 | 16-MAR-15:10 | 62.41 | 26-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 177.88 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.84 | 14-APR-16:00 | 38.74 | 21-APR-04:07 |
May | 180.00 | 01-MAY-00:10 | 177.88 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.00 | 31-MAY-17:00 | 26.67 | 01-MAY-04:00 |
June | 180.00 | 01-JUN-00:10 | 177.88 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.60 | 16-JUN-16:20 | 9.07 | 21-JUN-05:55 |
July | 180.00 | 01-JUL-00:10 | 177.88 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.81 | 20-JUL-15:10 | 9.13 | 01-JUL-06:00 |
August | 180.00 | 01-AUG-00:10 | 177.88 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.74 | 25-AUG-16:00 | 18.15 | 05-AUG-18:00 |
September | 180.00 | 01-SEP-00:10 | 177.88 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.13 | 08-SEP-16:00 | 13.17 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 177.88 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.94 | 03-OCT-16:00 | 47.92 | 25-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 177.88 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.83 | 01-NOV-15:10 | 64.25 | 23-NOV-06:07 |
December | 180.00 | 01-DEC-00:10 | 177.88 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.31 | 25-DEC-16:10 | 67.52 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 1.26 | 9.07 | |||||
Maximum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 53.60 | 67.52 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.86 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 21.37 | 31-JAN-17:00 | 62.62 | 01-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 177.86 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.26 | 18-FEB-16:06 | 48.20 | 28-FEB-06:53 |
March | 180.00 | 01-MAR-00:10 | 177.86 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.74 | 16-MAR-15:10 | 62.41 | 26-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 177.86 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.84 | 14-APR-16:00 | 38.74 | 21-APR-04:07 |
May | 180.00 | 01-MAY-00:10 | 177.86 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.99 | 31-MAY-17:00 | 26.67 | 01-MAY-04:00 |
June | 180.00 | 01-JUN-00:10 | 177.86 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.59 | 16-JUN-16:20 | 13.44 | 21-JUN-06:00 |
July | 180.00 | 01-JUL-00:10 | 177.86 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.95 | 20-JUL-15:10 | 13.27 | 01-JUL-06:00 |
August | 180.00 | 01-AUG-00:10 | 177.86 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.30 | 25-AUG-16:00 | 17.96 | 05-AUG-18:00 |
September | 180.00 | 01-SEP-00:10 | 177.86 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.41 | 08-SEP-16:00 | 14.58 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 177.86 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.94 | 03-OCT-16:00 | 47.91 | 25-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 177.86 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.84 | 01-NOV-15:09 | 64.24 | 23-NOV-06:07 |
December | 180.00 | 01-DEC-00:10 | 177.86 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.31 | 25-DEC-16:09 | 67.51 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 1.26 | 13.27 | |||||
Maximum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 53.59 | 67.51 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 111.82 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10.94 | 31-JAN-17:00 | 32.04 | 01-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 111.82 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.64 | 18-FEB-16:07 | 25.78 | 01-FEB-05:10 |
March | 180.00 | 01-MAR-00:10 | 111.82 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.61 | 16-MAR-15:10 | 31.93 | 26-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 111.82 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.84 | 14-APR-16:20 | 19.82 | 21-APR-04:07 |
May | 180.00 | 01-MAY-00:10 | 111.82 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.49 | 31-MAY-17:00 | 13.65 | 01-MAY-04:00 |
June | 180.00 | 01-JUN-00:10 | 111.82 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.88 | 28-JUN-16:00 | 4.64 | 21-JUN-05:55 |
July | 180.00 | 01-JUL-00:10 | 111.82 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.23 | 20-JUL-15:10 | 4.67 | 01-JUL-06:00 |
August | 180.00 | 01-AUG-00:10 | 111.82 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.72 | 25-AUG-17:00 | 8.95 | 05-AUG-18:00 |
September | 180.00 | 01-SEP-00:10 | 111.82 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.23 | 08-SEP-16:00 | 6.74 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 111.82 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.90 | 03-OCT-16:00 | 24.52 | 25-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 111.82 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.08 | 01-NOV-15:10 | 32.87 | 23-NOV-06:10 |
December | 180.00 | 01-DEC-00:10 | 111.82 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.25 | 25-DEC-16:10 | 34.54 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.64 | 4.64 | |||||
Maximum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 27.88 | 34.54 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2988.03 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.84 | 31-JAN-17:00 | 174.21 | 01-JAN-08:00 |
February | 26988.77 | 01-FEB-00:10 | 2988.03 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 138.67 | 28-FEB-06:53 |
March | 26988.77 | 01-MAR-00:10 | 2988.03 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.36 | 16-MAR-15:00 | 173.61 | 26-MAR-06:00 |
April | 26988.77 | 01-APR-00:10 | 2988.03 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.13 | 14-APR-16:00 | 115.26 | 21-APR-04:10 |
May | 26988.77 | 01-MAY-00:10 | 2988.03 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.79 | 31-MAY-17:00 | 85.51 | 01-MAY-04:00 |
June | 26988.77 | 01-JUN-00:10 | 2988.03 | 01-JUN-19:19 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 114.58 | 28-JUN-16:00 | 42.02 | 21-JUN-06:00 |
July | 26988.77 | 01-JUL-00:10 | 2988.03 | 03-JUL-19:30 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 103.07 | 19-JUL-13:00 | 42.32 | 01-JUL-06:00 |
August | 26988.77 | 01-AUG-00:10 | 2988.03 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 109.01 | 25-AUG-14:00 | 49.47 | 05-AUG-18:00 |
September | 26988.77 | 01-SEP-00:10 | 2988.03 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 92.29 | 08-SEP-15:00 | 52.26 | 22-SEP-06:00 |
October | 26988.77 | 01-OCT-23:10 | 2988.03 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.09 | 01-OCT-13:00 | 137.80 | 25-OCT-06:00 |
November | 26988.77 | 01-NOV-00:10 | 2988.03 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.70 | 01-NOV-15:00 | 178.21 | 23-NOV-06:10 |
December | 26988.77 | 01-DEC-00:10 | 2988.03 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.54 | 21-DEC-15:00 | 186.25 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.02 | |||||
Maximum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 114.58 | 186.25 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2988.03 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.84 | 31-JAN-17:00 | 174.21 | 01-JAN-08:00 |
February | 26988.77 | 01-FEB-00:10 | 2988.03 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 138.67 | 28-FEB-06:53 |
March | 26988.77 | 01-MAR-00:10 | 2988.03 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.36 | 16-MAR-15:00 | 173.62 | 26-MAR-06:00 |
April | 26988.77 | 01-APR-00:10 | 2988.03 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.13 | 14-APR-16:00 | 115.26 | 21-APR-04:10 |
May | 26988.77 | 01-MAY-00:10 | 2988.03 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.79 | 31-MAY-17:00 | 85.51 | 01-MAY-04:00 |
June | 26988.77 | 01-JUN-00:10 | 2988.03 | 01-JUN-19:19 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 114.58 | 28-JUN-16:00 | 42.02 | 21-JUN-06:00 |
July | 26988.77 | 01-JUL-00:10 | 2988.03 | 03-JUL-19:30 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 103.07 | 19-JUL-13:00 | 42.32 | 01-JUL-06:00 |
August | 26988.77 | 01-AUG-00:10 | 2988.03 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 109.01 | 25-AUG-14:00 | 49.47 | 05-AUG-18:00 |
September | 26988.77 | 01-SEP-00:10 | 2988.03 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 92.29 | 08-SEP-15:00 | 52.26 | 22-SEP-06:00 |
October | 26988.77 | 01-OCT-23:10 | 2988.03 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.09 | 01-OCT-13:00 | 137.83 | 25-OCT-07:00 |
November | 26988.77 | 01-NOV-00:10 | 2988.03 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.70 | 01-NOV-15:00 | 178.22 | 23-NOV-06:10 |
December | 26988.77 | 01-DEC-00:10 | 2988.03 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.25 | 21-DEC-15:00 | 186.25 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.02 | |||||
Maximum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 114.58 | 186.25 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 1060.81 | 02-JAN-20:10 | 14912.86 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 29.48 | 31-JAN-16:40 | 155.92 | 01-JAN-08:00 |
February | 2401.70 | 01-FEB-00:10 | 1060.81 | 01-FEB-20:10 | 14912.86 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 124.12 | 28-FEB-06:53 |
March | 2401.70 | 01-MAR-00:10 | 1060.81 | 01-MAR-20:10 | 14912.86 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 28.14 | 16-MAR-15:40 | 155.45 | 26-MAR-05:20 |
April | 2401.70 | 01-APR-00:10 | 1060.81 | 03-APR-19:10 | 14912.86 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 63.76 | 14-APR-15:40 | 103.19 | 21-APR-04:10 |
May | 2401.70 | 01-MAY-00:10 | 1060.81 | 01-MAY-19:10 | 14912.86 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 75.09 | 31-MAY-17:00 | 76.55 | 01-MAY-04:00 |
June | 2401.70 | 01-JUN-00:10 | 1060.81 | 01-JUN-19:10 | 14912.86 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 102.65 | 28-JUN-16:00 | 37.59 | 21-JUN-05:55 |
July | 2401.70 | 01-JUL-00:10 | 1060.81 | 03-JUL-19:10 | 14912.86 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 92.33 | 19-JUL-13:00 | 37.86 | 01-JUL-06:00 |
August | 2401.70 | 01-AUG-00:10 | 1060.81 | 01-AUG-19:10 | 14912.86 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 97.64 | 25-AUG-14:00 | 44.22 | 05-AUG-18:00 |
September | 2401.70 | 01-SEP-00:10 | 1060.81 | 01-SEP-19:10 | 14912.86 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 82.67 | 08-SEP-15:00 | 46.76 | 22-SEP-06:00 |
October | 2401.70 | 01-OCT-23:10 | 1060.81 | 02-OCT-19:10 | 14912.86 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 75.34 | 01-OCT-13:00 | 123.35 | 25-OCT-06:05 |
November | 2401.70 | 01-NOV-00:10 | 1060.81 | 01-NOV-19:10 | 14912.86 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 29.34 | 01-NOV-15:00 | 159.50 | 23-NOV-07:00 |
December | 2401.70 | 01-DEC-00:10 | 1060.81 | 01-DEC-20:10 | 14912.86 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 11.55 | 21-DEC-15:00 | 166.70 | 05-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2401.70 | 1060.81 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 0.00 | 37.59 | ||||||
Maximum of Months | 2401.70 | 1060.81 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 102.65 | 166.70 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2395.44 | 02-JAN-00:10 | 1976.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.38 | 31-JAN-17:00 | 133.27 | 01-JAN-08:00 |
February | 2395.44 | 01-FEB-00:10 | 1976.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 107.28 | 01-FEB-04:52 |
March | 2395.44 | 01-MAR-00:10 | 1976.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.75 | 15-MAR-15:40 | 132.82 | 26-MAR-06:00 |
April | 2395.44 | 01-APR-00:10 | 1976.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.30 | 14-APR-15:00 | 89.42 | 21-APR-04:00 |
May | 2395.44 | 01-MAY-00:10 | 1976.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.40 | 31-MAY-17:00 | 68.46 | 01-MAY-04:00 |
June | 2395.44 | 01-JUN-00:10 | 1976.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.38 | 28-JUN-16:00 | 33.97 | 21-JUN-05:00 |
July | 2395.44 | 01-JUL-00:10 | 1976.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.30 | 19-JUL-13:00 | 34.98 | 01-JUL-06:00 |
August | 2395.44 | 01-AUG-00:10 | 1976.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.51 | 25-AUG-14:00 | 40.93 | 05-AUG-18:00 |
September | 2395.44 | 01-SEP-00:10 | 1976.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.85 | 08-SEP-15:00 | 40.01 | 22-SEP-06:00 |
October | 2395.44 | 01-OCT-23:10 | 1976.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.67 | 01-OCT-13:00 | 105.49 | 25-OCT-06:00 |
November | 2395.44 | 01-NOV-00:10 | 1976.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.01 | 01-NOV-15:00 | 137.97 | 23-NOV-06:10 |
December | 2395.44 | 01-DEC-00:10 | 1976.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.83 | 21-DEC-15:00 | 143.73 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.97 | ||||
Maximum of Months | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.38 | 143.73 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 19725.67 | 19-JAN-22:00 | 20447.81 | 23449.32 | 18251.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17888.13 | 01-FEB-21:50 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 13688.31 | 01-MAR-21:00 | 8945.92 | 13190.31 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 15040.94 | 30-APR-10:33 | 11501.89 | 13190.31 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 14630.72 | 07-MAY-10:33 | 11501.89 | 13190.31 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 15651.30 | 28-JUN-18:10 | 44729.58 | 58623.31 | 45627.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 21203.12 | 14-JUL-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 23228.56 | 04-AUG-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 26076.76 | 08-SEP-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 25705.87 | 05-OCT-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 25364.26 | 01-NOV-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 24551.44 | 01-DEC-22:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 13688.31 | 8945.92 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26076.76 | 44729.58 | 58623.31 | 45627.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3662.57 | 14-JAN-13:40 | 389.84 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 12.73 | 0.00 |
February | 2749.10 | 01-FEB-14:00 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.36 |
March | 2782.21 | 18-MAR-13:40 | 389.84 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 0.00 |
April | 3073.04 | 14-APR-14:10 | 389.84 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 46.97 | 0.00 |
May | 2567.70 | 31-MAY-18:15 | 1819.27 | 1062.39 | 1299.04 | 0.00 | 0.00 | 0.00 | 0.00 | 52.13 | 0.00 |
June | 3372.08 | 28-JUN-18:17 | 2728.91 | 1593.58 | 1948.56 | 0.00 | 0.00 | 0.00 | 0.00 | 75.45 | 0.00 |
July | 3129.00 | 21-JUL-18:30 | 909.64 | 531.19 | 649.52 | 0.00 | 0.00 | 0.00 | 0.00 | 64.03 | 0.00 |
August | 3578.32 | 28-AUG-12:30 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 59.78 | 0.00 |
September | 3874.65 | 28-SEP-13:30 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 55.85 | 0.00 |
October | 3908.28 | 02-OCT-12:40 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 46.36 | 0.00 |
November | 3848.67 | 21-NOV-13:30 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 4.76 | 0.00 |
December | 3552.58 | 25-DEC-13:00 | 389.84 | 199.20 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 4.76 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2567.70 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3908.28 | 2728.91 | 1593.58 | 1948.56 | 0.00 | 0.00 | 0.00 | 0.00 | 75.45 | 39.36 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1751.18 | 27-JAN-21:10 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.89 |
February | 1538.20 | 01-FEB-21:50 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.83 |
March | 1789.92 | 17-MAR-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.49 |
April | 2284.32 | 14-APR-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 9.04 | 0.00 |
May | 2231.33 | 31-MAY-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 9.06 | 0.00 |
June | 2559.28 | 28-JUN-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 19.55 | 0.00 |
July | 2420.35 | 20-JUL-20:10 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 19.91 | 0.00 |
August | 2461.97 | 15-AUG-20:10 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 19.02 | 0.00 |
September | 2424.28 | 07-SEP-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 16.73 | 0.00 |
October | 2265.04 | 05-OCT-20:10 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 4.56 | 0.00 |
November | 1994.06 | 01-NOV-20:10 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.55 |
December | 1667.30 | 26-DEC-22:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.21 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1538.20 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2559.28 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 19.91 | 26.83 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1098.48 | 08-JAN-11:33 | 286.42 | 684.18 | 1060.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 |
February | 1021.37 | 18-FEB-11:33 | 286.42 | 570.15 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.94 |
March | 1147.81 | 18-MAR-10:33 | 286.42 | 570.15 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 5.84 | 0.00 |
April | 1569.75 | 25-APR-21:00 | 254.59 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 12.95 | 0.00 |
May | 1796.60 | 18-MAY-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 25.69 | 0.00 |
June | 2446.56 | 28-JUN-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 54.25 | 0.00 |
July | 2334.06 | 21-JUL-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 54.45 | 0.00 |
August | 2220.63 | 15-AUG-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 46.29 | 0.00 |
September | 2105.24 | 08-SEP-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 41.52 | 0.00 |
October | 1951.31 | 02-OCT-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 12.94 | 0.00 |
November | 1175.67 | 02-NOV-18:04 | 1559.38 | 4257.10 | 5566.86 | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 0.00 |
December | 1049.76 | 25-DEC-11:33 | 286.42 | 684.18 | 1060.35 | 0.00 | 0.00 | 0.00 | 0.00 | 1.23 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1021.37 | 222.77 | 570.15 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2446.56 | 1559.38 | 4257.10 | 5566.86 | 0.00 | 0.00 | 0.00 | 0.00 | 54.45 | 10.94 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 647.47 | 08-JAN-11:33 | 220.32 | 251.83 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.16 |
February | 602.05 | 18-FEB-11:33 | 220.32 | 209.86 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.01 |
March | 676.32 | 18-MAR-10:33 | 220.32 | 209.86 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 3.71 | 0.00 |
April | 792.99 | 15-APR-10:33 | 220.32 | 209.86 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 11.47 | 0.00 |
May | 812.58 | 09-MAY-21:00 | 195.84 | 223.85 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 12.35 | 0.00 |
June | 1284.83 | 28-JUN-19:10 | 171.36 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 37.06 | 0.00 |
July | 1188.33 | 21-JUL-19:10 | 171.36 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 33.32 | 0.00 |
August | 1102.21 | 15-AUG-20:00 | 171.36 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 26.71 | 0.00 |
September | 1033.23 | 08-SEP-20:00 | 171.36 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 23.95 | 0.00 |
October | 901.01 | 02-OCT-19:50 | 171.36 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 8.70 | 0.00 |
November | 681.81 | 02-NOV-18:04 | 1199.52 | 1566.97 | 1605.89 | 0.00 | 0.00 | 0.00 | 0.00 | 2.15 | 0.00 |
December | 620.58 | 25-DEC-11:33 | 220.32 | 251.83 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.96 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 602.05 | 171.36 | 209.86 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1284.83 | 1199.52 | 1566.97 | 1605.89 | 0.00 | 0.00 | 0.00 | 0.00 | 37.06 | 6.01 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 37958.52 | 27-JAN-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 42.84 |
February | 37642.99 | 22-FEB-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 68.04 |
March | 38275.97 | 16-MAR-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 10.82 |
April | 39118.82 | 14-APR-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 40.57 | 0.00 |
May | 39243.33 | 18-MAY-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 35.07 | 0.00 |
June | 39834.47 | 28-JUN-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 74.08 | 0.00 |
July | 39665.71 | 21-JUL-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 74.35 | 0.00 |
August | 39576.39 | 15-AUG-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 63.20 | 0.00 |
September | 39428.28 | 08-SEP-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 56.69 | 0.00 |
October | 39067.59 | 03-OCT-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 35.05 | 0.00 |
November | 38240.66 | 01-NOV-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 18.09 |
December | 37707.75 | 22-DEC-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 61.83 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 37642.99 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 39834.47 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 74.35 | 68.04 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13947.29 | 14-JAN-13:30 | 5122.80 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 26.42 | 0.00 |
February | 10753.19 | 25-FEB-14:25 | 10245.60 | 207.96 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.04 |
March | 10876.85 | 18-MAR-13:30 | 5122.80 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 24.83 | 0.00 |
April | 12108.70 | 14-APR-21:10 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 48.41 | 0.00 |
May | 11662.37 | 09-MAY-21:10 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 50.21 | 0.00 |
June | 13171.69 | 28-JUN-21:10 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 108.72 | 0.00 |
July | 13080.84 | 21-JUL-21:10 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 100.98 | 0.00 |
August | 12970.75 | 15-AUG-21:10 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 89.18 | 0.00 |
September | 13748.80 | 28-SEP-15:03 | 51228.00 | 623.89 | 2133.76 | 0.00 | 0.00 | 0.00 | 0.00 | 137.03 | 0.00 |
October | 13737.85 | 05-OCT-15:03 | 59766.00 | 727.88 | 2489.39 | 0.00 | 0.00 | 0.00 | 0.00 | 102.22 | 0.00 |
November | 14194.21 | 01-NOV-15:03 | 59766.00 | 727.88 | 2489.39 | 0.00 | 0.00 | 0.00 | 0.00 | 50.32 | 0.00 |
December | 13500.71 | 25-DEC-13:00 | 5122.80 | 124.78 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 10.54 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10753.19 | 5122.80 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14194.21 | 59766.00 | 1134.35 | 2489.39 | 0.00 | 0.00 | 0.00 | 0.00 | 137.03 | 70.04 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 36330.87 | 17-JAN-19:04 | 248391.78 | 59140.98 | 66509.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.99 |
February | 33086.65 | 01-FEB-22:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 455.71 |
March | 36548.48 | 17-MAR-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.10 |
April | 42093.26 | 14-APR-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 138.25 | 0.00 |
May | 41525.00 | 09-MAY-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 143.40 | 0.00 |
June | 46472.96 | 28-JUN-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 310.56 | 0.00 |
July | 45750.12 | 21-JUL-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 288.47 | 0.00 |
August | 45362.57 | 15-AUG-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 254.75 | 0.00 |
September | 45348.25 | 07-SEP-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 258.05 | 0.00 |
October | 43553.18 | 03-OCT-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 163.44 | 0.00 |
November | 38948.03 | 01-NOV-20:10 | 40553.76 | 8448.71 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.09 |
December | 35487.53 | 26-DEC-22:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 286.83 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 33086.65 | 40553.76 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 46472.96 | 248391.78 | 59140.98 | 66509.49 | 0.00 | 0.00 | 0.00 | 0.00 | 310.56 | 455.71 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4379.34 | 24-JAN-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 6.85 | 0.00 |
February | 4276.61 | 03-FEB-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.26 |
March | 4313.94 | 31-MAR-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 1.68 | 0.00 |
April | 4416.97 | 14-APR-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 33.46 | 0.00 |
May | 4409.89 | 31-MAY-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 35.24 | 0.00 |
June | 4423.58 | 15-JUN-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 48.65 | 0.00 |
July | 4423.09 | 01-JUL-18:01 | 819.00 | 1245.18 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 35.69 | 0.00 |
August | 4276.01 | 25-AUG-08:61 | 252.00 | 547.88 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 14.95 | 0.00 |
September | 3431.30 | 25-SEP-08:61 | 252.00 | 547.88 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 6.53 | 0.00 |
October | 4409.11 | 15-OCT-15:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 23.30 | 0.00 |
November | 4399.47 | 09-NOV-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 14.86 | 0.00 |
December | 4376.70 | 22-DEC-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3431.30 | 252.00 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4423.58 | 970.20 | 1245.18 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 48.65 | 15.26 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4293.20 | 31-JAN-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 18.63 | 0.00 |
February | 4208.32 | 01-FEB-17:11 | 680.40 | 348.61 | 884.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.38 |
March | 4250.11 | 31-MAR-15:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 1.99 | 0.00 |
April | 4534.14 | 26-APR-21:51 | 1620.00 | 1072.50 | 805.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.40 |
May | 4816.93 | 20-MAY-08:61 | 540.00 | 996.02 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 6.90 | 0.00 |
June | 4861.45 | 14-JUN-08:61 | 360.00 | 782.59 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 9.66 | 0.00 |
July | 4989.05 | 01-JUL-08:61 | 540.00 | 996.02 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 7.99 | 0.00 |
August | 4626.09 | 24-AUG-08:21 | 360.00 | 782.59 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 11.54 | 0.00 |
September | 3574.92 | 25-SEP-20:41 | 1602.00 | 1582.97 | 1817.24 | 0.00 | 0.00 | 0.00 | 0.00 | 1.65 | 0.00 |
October | 4381.60 | 16-OCT-21:51 | 1440.00 | 953.34 | 716.36 | 0.00 | 0.00 | 0.00 | 0.00 | 1.30 | 0.00 |
November | 4318.08 | 09-NOV-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 15.29 | 0.00 |
December | 4279.38 | 22-DEC-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 7.39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3574.92 | 360.00 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4989.05 | 1620.00 | 1582.97 | 1817.24 | 0.00 | 0.00 | 0.00 | 0.00 | 18.63 | 21.38 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 620.15 | 14-JAN-13:40 | 0.00 | 36.89 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
February | 477.99 | 01-FEB-14:15 | 0.00 | 62.60 | 61.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.80 |
March | 429.29 | 18-MAR-14:10 | 0.00 | 36.89 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 |
April | 434.01 | 14-APR-13:40 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 5.46 | 0.00 |
May | 364.47 | 09-MAY-17:13 | 0.00 | 224.70 | 371.51 | 0.00 | 0.00 | 0.00 | 0.00 | 5.94 | 0.00 |
June | 453.96 | 28-JUN-19:10 | 0.00 | 111.79 | 159.95 | 0.00 | 0.00 | 0.00 | 0.00 | 9.41 | 0.00 |
July | 441.81 | 21-JUL-20:20 | 0.00 | 99.50 | 178.01 | 0.00 | 0.00 | 0.00 | 0.00 | 6.93 | 0.00 |
August | 492.41 | 28-AUG-12:30 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 7.66 | 0.00 |
September | 574.40 | 28-SEP-13:30 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 7.02 | 0.00 |
October | 603.53 | 18-OCT-13:20 | 0.00 | 62.60 | 61.92 | 0.00 | 0.00 | 0.00 | 0.00 | 2.76 | 0.00 |
November | 639.50 | 20-NOV-14:30 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.22 | 0.00 |
December | 614.95 | 25-DEC-13:30 | 0.00 | 36.89 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.94 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 364.47 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 639.50 | 0.00 | 224.70 | 371.51 | 0.00 | 0.00 | 0.00 | 0.00 | 9.41 | 8.80 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1496.01 | 31-JAN-19:01 | 970.20 | 696.66 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 | 0.00 |
February | 1392.21 | 27-FEB-19:01 | 970.20 | 696.66 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.40 |
March | 1505.97 | 19-MAR-21:51 | 970.20 | 665.35 | 614.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.37 |
April | 1553.56 | 30-APR-08:51 | 540.00 | 626.21 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 1.64 | 0.00 |
May | 1658.35 | 20-MAY-08:61 | 540.00 | 626.21 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 2.01 | 0.00 |
June | 1652.58 | 14-JUN-08:61 | 360.00 | 492.02 | 1109.66 | 0.00 | 0.00 | 0.00 | 0.00 | 2.94 | 0.00 |
July | 1698.72 | 01-JUL-08:61 | 540.00 | 626.21 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 2.47 | 0.00 |
August | 1561.89 | 24-AUG-08:21 | 360.00 | 492.02 | 1109.66 | 0.00 | 0.00 | 0.00 | 0.00 | 3.53 | 0.00 |
September | 1552.15 | 29-SEP-08:21 | 324.00 | 442.82 | 998.70 | 0.00 | 0.00 | 0.00 | 0.00 | 3.78 | 0.00 |
October | 1529.38 | 19-OCT-18:01 | 970.20 | 696.66 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 2.35 | 0.00 |
November | 1497.40 | 10-NOV-16:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 1.68 | 0.00 |
December | 1444.76 | 25-DEC-16:01 | 378.00 | 258.31 | 379.35 | 0.00 | 0.00 | 0.00 | 0.00 | 2.97 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1392.21 | 324.00 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1698.72 | 970.20 | 696.66 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 3.78 | 6.40 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3883.02 | 31-JAN-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 18.28 | 0.00 |
February | 3783.83 | 03-FEB-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.11 |
March | 3847.83 | 31-MAR-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 1.59 | 0.00 |
April | 3924.68 | 14-APR-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 33.49 | 0.00 |
May | 4003.98 | 17-MAY-08:61 | 360.00 | 782.68 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 12.23 | 0.00 |
June | 4000.73 | 14-JUN-08:61 | 360.00 | 782.68 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 13.59 | 0.00 |
July | 4007.12 | 01-JUL-08:61 | 540.00 | 996.14 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 13.09 | 0.00 |
August | 3925.62 | 25-AUG-08:61 | 252.00 | 547.88 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 13.88 | 0.00 |
September | 3094.66 | 26-SEP-08:61 | 252.00 | 547.88 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 3.59 | 0.00 |
October | 3908.90 | 15-OCT-15:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 23.41 | 0.00 |
November | 3893.24 | 10-NOV-09:01 | 252.00 | 547.88 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.94 |
December | 3870.27 | 26-DEC-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 1.98 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3094.66 | 252.00 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4007.12 | 680.40 | 996.14 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 33.49 | 15.11 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3949.56 | 27-JAN-09:51 | 288.00 | 626.07 | 905.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.72 |
February | 2975.15 | 26-FEB-09:01 | 378.00 | 697.22 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.21 |
March | 3794.06 | 31-MAR-15:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 1.89 | 0.00 |
April | 4572.27 | 14-APR-08:41 | 360.00 | 782.59 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 4.01 | 0.00 |
May | 4907.68 | 21-MAY-08:61 | 378.00 | 697.22 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.03 |
June | 4586.85 | 13-JUN-08:11 | 360.00 | 782.59 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 2.49 | 0.00 |
July | 4590.37 | 01-JUL-08:61 | 540.00 | 996.02 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 6.57 | 0.00 |
August | 4575.39 | 24-AUG-08:21 | 360.00 | 782.59 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 6.78 | 0.00 |
September | 3628.44 | 15-SEP-08:51 | 360.00 | 782.59 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.68 |
October | 4481.62 | 17-OCT-08:51 | 360.00 | 782.59 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.03 |
November | 4232.20 | 10-NOV-09:51 | 360.00 | 782.59 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.09 |
December | 3792.71 | 25-DEC-09:51 | 378.00 | 697.22 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.95 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2975.15 | 288.00 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4907.68 | 680.40 | 996.02 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 6.78 | 32.21 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2036.84 | 29-JAN-11:33 | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.34 |
February | 1911.76 | 01-FEB-11:33 | 1508.90 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.57 |
March | 2066.88 | 18-MAR-10:45 | 1508.90 | 1037.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 0.00 |
April | 2433.27 | 15-APR-10:33 | 2263.36 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.74 | 0.00 |
May | 2445.43 | 20-MAY-10:33 | 2263.36 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.65 | 0.00 |
June | 3666.25 | 28-JUN-18:40 | 1760.39 | 1659.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.81 | 0.00 |
July | 3310.50 | 21-JUL-19:10 | 1760.39 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.30 | 0.00 |
August | 3160.95 | 15-AUG-18:17 | 5281.16 | 4979.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.77 | 0.00 |
September | 3013.52 | 08-SEP-18:15 | 3520.78 | 3319.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.38 | 0.00 |
October | 2782.48 | 04-OCT-18:04 | 12322.72 | 11618.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.16 | 0.00 |
November | 2115.25 | 01-NOV-18:10 | 12322.72 | 11618.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.03 | 0.00 |
December | 1955.31 | 25-DEC-11:33 | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 1911.76 | 1508.90 | 1037.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3666.25 | 12322.72 | 11618.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.81 | 30.57 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4621.84 | 24-JAN-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 6.79 | 0.00 |
February | 4493.34 | 03-FEB-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.17 |
March | 4556.36 | 31-MAR-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 1.59 | 0.00 |
April | 4677.01 | 14-APR-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 33.29 | 0.00 |
May | 4662.67 | 07-MAY-15:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 34.04 | 0.00 |
June | 4687.08 | 15-JUN-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 48.47 | 0.00 |
July | 4672.70 | 01-JUL-18:01 | 819.00 | 1245.18 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 35.61 | 0.00 |
August | 4486.50 | 25-AUG-08:61 | 252.00 | 547.88 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 15.08 | 0.00 |
September | 3626.77 | 01-SEP-08:61 | 252.00 | 547.88 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 15.60 | 0.00 |
October | 4658.22 | 15-OCT-15:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 23.20 | 0.00 |
November | 4650.07 | 09-NOV-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 14.75 | 0.00 |
December | 4625.87 | 22-DEC-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 6.72 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3626.77 | 252.00 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4687.08 | 819.00 | 1245.18 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 48.47 | 15.17 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4519.67 | 31-JAN-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 18.63 | 0.00 |
February | 4411.71 | 01-FEB-17:11 | 680.40 | 348.61 | 884.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.19 |
March | 4483.49 | 31-MAR-15:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 1.91 | 0.00 |
April | 4771.21 | 26-APR-21:51 | 1620.00 | 1072.50 | 805.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.37 |
May | 4987.84 | 20-MAY-08:61 | 540.00 | 996.02 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 7.66 | 0.00 |
June | 5050.05 | 14-JUN-08:61 | 360.00 | 782.59 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 10.28 | 0.00 |
July | 5175.33 | 01-JUL-08:61 | 540.00 | 996.02 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 8.70 | 0.00 |
August | 4789.17 | 24-AUG-08:21 | 360.00 | 782.59 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 12.28 | 0.00 |
September | 3680.84 | 27-SEP-08:51 | 360.00 | 782.59 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 10.70 | 0.00 |
October | 4574.34 | 15-OCT-15:01 | 378.00 | 410.86 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 23.59 | 0.00 |
November | 4552.75 | 09-NOV-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 15.24 | 0.00 |
December | 4508.86 | 22-DEC-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 7.37 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3680.84 | 360.00 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5175.33 | 1620.00 | 1072.50 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 23.59 | 21.19 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2364.81 | 19-JAN-16:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 2.78 | 0.00 |
February | 2292.16 | 03-FEB-16:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.23 |
March | 2321.07 | 31-MAR-15:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 | 0.00 |
April | 2351.16 | 05-APR-15:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 12.97 | 0.00 |
May | 2339.35 | 08-MAY-08:61 | 360.00 | 492.02 | 1109.66 | 0.00 | 0.00 | 0.00 | 0.00 | 6.45 | 0.00 |
June | 2335.36 | 14-JUN-08:61 | 360.00 | 492.02 | 1109.66 | 0.00 | 0.00 | 0.00 | 0.00 | 7.14 | 0.00 |
July | 2339.66 | 01-JUL-08:61 | 540.00 | 626.21 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 6.89 | 0.00 |
August | 2282.11 | 25-AUG-08:61 | 252.00 | 344.41 | 776.76 | 0.00 | 0.00 | 0.00 | 0.00 | 7.35 | 0.00 |
September | 1874.68 | 24-SEP-08:61 | 378.00 | 438.35 | 1119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 2.35 | 0.00 |
October | 2373.09 | 18-OCT-15:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 10.09 | 0.00 |
November | 2365.83 | 09-NOV-16:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 7.18 | 0.00 |
December | 2370.63 | 22-DEC-16:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 2.94 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1874.68 | 252.00 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2373.09 | 680.40 | 626.21 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 12.97 | 8.23 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19477.32 | 06-JAN-22:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.84 |
February | 19081.18 | 21-FEB-23:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.92 |
March | 21014.58 | 17-MAR-21:53 | 188921.38 | 13944.14 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.86 |
April | 23009.37 | 14-APR-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 30.37 | 0.00 |
May | 23245.75 | 09-MAY-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 31.53 | 0.00 |
June | 24848.18 | 28-JUN-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 66.92 | 0.00 |
July | 24521.41 | 21-JUL-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 62.99 | 0.00 |
August | 24082.59 | 10-AUG-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 56.46 | 0.00 |
September | 23878.78 | 07-SEP-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 57.26 | 0.00 |
October | 23063.89 | 03-OCT-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 36.02 | 0.00 |
November | 20886.03 | 02-NOV-21:53 | 188921.38 | 13944.14 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.24 |
December | 19091.50 | 26-DEC-22:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 19081.18 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24848.18 | 188921.38 | 13944.14 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 66.92 | 70.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 21132.11 | 06-JAN-22:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.84 |
February | 20780.34 | 21-FEB-22:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.93 |
March | 22448.48 | 17-MAR-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.43 |
April | 24189.52 | 14-APR-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 30.37 | 0.00 |
May | 24414.47 | 09-MAY-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 30.41 | 0.00 |
June | 26025.66 | 28-JUN-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 66.91 | 0.00 |
July | 25697.36 | 21-JUL-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 62.98 | 0.00 |
August | 25262.00 | 10-AUG-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 56.45 | 0.00 |
September | 25019.27 | 07-SEP-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 57.24 | 0.00 |
October | 24214.77 | 03-OCT-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 36.02 | 0.00 |
November | 22229.30 | 02-NOV-21:53 | 188921.38 | 13944.14 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.24 |
December | 20639.08 | 26-DEC-22:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 20639.08 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26025.66 | 188921.38 | 13944.14 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 66.91 | 70.93 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 28353.60 | 29-JAN-11:33 | 2401.70 | 1060.81 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 17.07 |
February | 28283.64 | 18-FEB-11:33 | 2401.70 | 884.01 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 29.38 |
March | 29221.81 | 18-MAR-10:45 | 1601.14 | 589.34 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.14 | 0.00 |
April | 30536.15 | 30-APR-10:33 | 2401.70 | 1060.81 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 35.22 | 0.00 |
May | 30749.76 | 07-MAY-10:45 | 1601.14 | 707.21 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 38.29 | 0.00 |
June | 31472.27 | 18-JUN-10:50 | 800.57 | 353.60 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 66.92 | 0.00 |
July | 31468.17 | 22-JUL-10:40 | 2401.70 | 884.01 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 67.25 | 0.00 |
August | 31506.06 | 13-AUG-10:40 | 2401.70 | 1060.81 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 55.92 | 0.00 |
September | 31289.22 | 09-SEP-10:37 | 2401.70 | 884.01 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 55.16 | 0.00 |
October | 30568.75 | 02-OCT-10:45 | 1067.42 | 589.34 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 50.73 | 0.00 |
November | 29107.19 | 01-NOV-10:45 | 1067.42 | 589.34 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 3.48 | 0.00 |
December | 28210.73 | 25-DEC-11:50 | 800.57 | 353.60 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 8.71 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 28210.73 | 800.57 | 353.60 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31506.06 | 2401.70 | 1060.81 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 67.25 | 29.38 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4162.52 | 29-JAN-11:33 | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.60 |
February | 3941.87 | 26-FEB-11:33 | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.72 |
March | 4457.70 | 18-MAR-17:12 | 6387.84 | 5270.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.22 | 0.00 |
April | 6352.70 | 14-APR-15:03 | 9315.60 | 3842.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.30 | 0.00 |
May | 6024.47 | 09-MAY-15:03 | 9315.60 | 3842.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.37 | 0.00 |
June | 7996.35 | 28-JUN-18:17 | 5589.36 | 5270.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.13 | 0.00 |
July | 7344.68 | 20-JUL-18:17 | 5589.36 | 5270.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.90 | 0.00 |
August | 7386.24 | 11-AUG-15:25 | 2661.60 | 1097.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.09 | 0.00 |
September | 7421.12 | 07-SEP-14:10 | 798.48 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.12 | 0.00 |
October | 6985.08 | 02-OCT-13:10 | 532.32 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.90 | 0.00 |
November | 4435.79 | 01-NOV-17:12 | 5323.20 | 5270.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.30 | 0.00 |
December | 4062.61 | 25-DEC-11:33 | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.65 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 3941.87 | 532.32 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7996.35 | 9315.60 | 5270.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.13 | 42.72 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.466493E+12 | 347059.60 | 13-JAN-07:10 | 0.365036E+12 | 323319.99 | 23-JAN-18:40 |
February | 0.402844E+12 | 356816.62 | 08-FEB-07:10 | 0.328295E+12 | 324056.54 | 10-FEB-18:19 |
March | 0.448600E+12 | 344902.03 | 13-MAR-06:10 | 0.356104E+12 | 318855.54 | 01-MAR-18:40 |
April | 0.486653E+12 | 337463.78 | 14-APR-18:19 | 0.332854E+12 | 306813.48 | 03-APR-17:30 |
May | 0.539289E+12 | 347869.60 | 31-MAY-18:10 | 0.331168E+12 | 295641.31 | 01-MAY-17:40 |
June | 0.603962E+12 | 408694.68 | 28-JUN-18:19 | 0.310367E+12 | 283829.88 | 01-JUN-17:19 |
July | 0.636823E+12 | 403488.14 | 21-JUL-19:00 | 0.315218E+12 | 275308.44 | 03-JUL-17:00 |
August | 0.629893E+12 | 388499.05 | 25-AUG-18:19 | 0.317053E+12 | 279346.51 | 30-AUG-17:40 |
September | 0.587148E+12 | 389491.48 | 08-SEP-19:10 | 0.314227E+12 | 288872.79 | 28-SEP-17:30 |
October | 0.498960E+12 | 365602.39 | 02-OCT-18:10 | 0.336720E+12 | 301636.39 | 31-OCT-17:19 |
November | 0.442853E+12 | 322827.15 | 17-NOV-07:10 | 0.338448E+12 | 312980.37 | 30-NOV-18:19 |
December | 0.469494E+12 | 345739.43 | 27-DEC-07:10 | 0.359893E+12 | 321681.31 | 28-DEC-18:49 |
Annual Sum or Average | 0.621301E+13 | 0.400538E+13 | ||||
Minimum of Months | 0.402844E+12 | 322827.15 | 0.310367E+12 | 275308.44 | ||
Maximum of Months | 0.636823E+12 | 408694.68 | 0.365036E+12 | 324056.54 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.670654E+11 | 0.190037E+11 | 0.140828E+12 | 0.691145E+11 | 0.431873E+11 | 0.732910E+10 | 0.557594E+11 | 0.463275E+11 | 0.00 | 0.00 | 0.463043E+10 | 0.804731E+10 | 0.00 |
February | 0.605156E+11 | 0.163016E+11 | 0.127191E+12 | 0.624261E+11 | 0.357793E+11 | 0.610116E+10 | 0.644532E+11 | 0.157854E+11 | 0.00 | 0.00 | 0.227022E+10 | 0.727181E+10 | 0.00 |
March | 0.665879E+11 | 0.167606E+11 | 0.140882E+12 | 0.691169E+11 | 0.411787E+11 | 0.726968E+10 | 0.450312E+11 | 0.433526E+11 | 0.00 | 0.00 | 0.514933E+10 | 0.804586E+10 | 0.00 |
April | 0.641350E+11 | 0.149024E+11 | 0.136245E+12 | 0.668844E+11 | 0.471384E+11 | 0.763317E+10 | 0.244426E+10 | 0.121657E+12 | 0.00 | 0.00 | 0.127957E+11 | 0.779705E+10 | 0.00 |
May | 0.660045E+11 | 0.142657E+11 | 0.140860E+12 | 0.691152E+11 | 0.511498E+11 | 0.794738E+10 | 85870382.10 | 0.159839E+12 | 0.00 | 0.00 | 0.167797E+11 | 0.804708E+10 | 0.00 |
June | 0.635945E+11 | 0.133329E+11 | 0.136336E+12 | 0.668864E+11 | 0.571389E+11 | 0.810101E+10 | 7651139.87 | 0.223772E+12 | 0.00 | 0.00 | 0.219222E+11 | 0.778858E+10 | 0.00 |
July | 0.658726E+11 | 0.139548E+11 | 0.140770E+12 | 0.691126E+11 | 0.579254E+11 | 0.847246E+10 | 42080395.34 | 0.243230E+12 | 0.00 | 0.00 | 0.240842E+11 | 0.805551E+10 | 0.00 |
August | 0.663169E+11 | 0.148876E+11 | 0.140892E+12 | 0.691167E+11 | 0.583775E+11 | 0.844030E+10 | 58361435.79 | 0.235764E+12 | 0.00 | 0.00 | 0.226511E+11 | 0.804707E+10 | 0.00 |
September | 0.643461E+11 | 0.156353E+11 | 0.136256E+12 | 0.668846E+11 | 0.561560E+11 | 0.816097E+10 | 73772332.09 | 0.207329E+12 | 0.00 | 0.00 | 0.193408E+11 | 0.779842E+10 | 0.00 |
October | 0.668577E+11 | 0.175305E+11 | 0.140818E+12 | 0.691144E+11 | 0.508138E+11 | 0.788183E+10 | 0.145132E+11 | 0.108657E+12 | 0.00 | 0.00 | 0.949166E+10 | 0.804575E+10 | 0.00 |
November | 0.648668E+11 | 0.181153E+11 | 0.136330E+12 | 0.668857E+11 | 0.439706E+11 | 0.716390E+10 | 0.388784E+11 | 0.494731E+11 | 0.00 | 0.00 | 0.433888E+10 | 0.778033E+10 | 0.00 |
December | 0.670797E+11 | 0.193664E+11 | 0.140770E+12 | 0.691134E+11 | 0.424583E+11 | 0.637033E+10 | 0.774596E+11 | 0.273663E+11 | 0.00 | 0.00 | 0.628859E+10 | 0.805586E+10 | 0.00 |
Annual Sum or Average | 0.783243E+12 | 0.194057E+12 | 0.165818E+13 | 0.813771E+12 | 0.585274E+12 | 0.908713E+11 | 0.298807E+12 | 0.148255E+13 | 0.00 | 0.00 | 0.149743E+12 | 0.947806E+11 | 0.00 |
Minimum of Months | 0.605156E+11 | 0.133329E+11 | 0.127191E+12 | 0.624261E+11 | 0.357793E+11 | 0.610116E+10 | 7651139.87 | 0.157854E+11 | 0.00 | 0.00 | 0.227022E+10 | 0.727181E+10 | 0.00 |
Maximum of Months | 0.670797E+11 | 0.193664E+11 | 0.140892E+12 | 0.691169E+11 | 0.583775E+11 | 0.847246E+10 | 0.774596E+11 | 0.243230E+12 | 0.00 | 0.00 | 0.240842E+11 | 0.805586E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.151918E+12 | 0.00 | 0.00 | 0.00 | 0.213118E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.00 | 0.00 | 0.191091E+12 | 0.00 | 0.00 |
March | 0.152024E+12 | 0.00 | 0.00 | 0.00 | 0.204081E+12 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.00 | 0.00 | 0.185898E+12 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.00 | 0.00 | 0.179189E+12 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 0.00 | 0.00 | 0.163253E+12 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 0.00 | 0.00 | 0.163398E+12 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 0.00 | 0.00 | 0.165014E+12 | 0.00 | 0.00 |
September | 0.146971E+12 | 0.00 | 0.00 | 0.00 | 0.167256E+12 | 0.00 | 0.00 |
October | 0.151903E+12 | 0.00 | 0.00 | 0.00 | 0.184817E+12 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.00 | 0.00 | 0.191357E+12 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.00 | 0.00 | 0.208073E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178884E+13 | 0.00 | 0.00 | 0.00 | 0.221654E+13 | 0.00 | 0.00 |
Minimum of Months | 0.137204E+12 | 0.00 | 0.00 | 0.00 | 0.163253E+12 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.00 | 0.00 | 0.213118E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 64632.59 | 02-JAN-20:10 | 12338.45 | 01-JAN-00:10 | 89171.45 | 02-JAN-07:10 | 49607.07 | 02-JAN-07:19 | 32535.26 | 31-JAN-22:10 | 3066.50 | 31-JAN-16:10 | 136337.42 | 01-JAN-09:09 |
February | 64632.59 | 01-FEB-20:10 | 12338.45 | 01-FEB-00:10 | 89171.45 | 01-FEB-07:10 | 49607.07 | 01-FEB-07:19 | 26655.80 | 01-FEB-22:10 | 2987.03 | 18-FEB-16:10 | 141230.50 | 08-FEB-07:10 |
March | 64632.59 | 01-MAR-20:10 | 12338.45 | 01-MAR-00:10 | 89171.45 | 01-MAR-07:10 | 49607.07 | 13-MAR-06:19 | 31416.90 | 16-MAR-21:00 | 3519.27 | 16-MAR-18:30 | 130868.94 | 13-MAR-06:10 |
April | 64632.59 | 03-APR-19:10 | 12338.45 | 01-APR-00:10 | 89171.45 | 03-APR-06:10 | 49607.07 | 03-APR-06:19 | 37444.11 | 14-APR-21:10 | 3748.34 | 25-APR-19:10 | 78233.15 | 21-APR-06:10 |
May | 64632.59 | 01-MAY-19:10 | 12338.45 | 01-MAY-00:10 | 89171.45 | 01-MAY-06:10 | 49606.97 | 26-MAY-06:19 | 37681.69 | 09-MAY-21:10 | 3503.66 | 29-MAY-20:49 | 6816.69 | 01-MAY-03:00 |
June | 64632.59 | 01-JUN-19:19 | 12338.45 | 01-JUN-00:10 | 89171.45 | 01-JUN-06:10 | 49605.53 | 02-JUN-06:19 | 43743.56 | 28-JUN-21:10 | 4332.22 | 29-JUN-18:10 | 2260.67 | 05-JUN-08:09 |
July | 64632.59 | 03-JUL-19:30 | 12338.45 | 01-JUL-00:10 | 89171.45 | 03-JUL-06:10 | 49606.78 | 14-JUL-06:19 | 45362.19 | 21-JUL-21:10 | 4015.99 | 07-JUL-20:19 | 3972.34 | 24-JUL-08:09 |
August | 64632.59 | 01-AUG-19:10 | 12338.45 | 01-AUG-00:10 | 89171.45 | 01-AUG-06:10 | 49607.07 | 04-AUG-06:19 | 46051.28 | 15-AUG-21:10 | 4035.47 | 27-AUG-18:10 | 4239.47 | 10-AUG-08:09 |
September | 64632.59 | 01-SEP-19:10 | 12338.45 | 01-SEP-00:10 | 89171.45 | 01-SEP-06:10 | 49607.07 | 01-SEP-06:19 | 47693.26 | 07-SEP-21:10 | 4231.86 | 18-SEP-18:19 | 4898.45 | 12-SEP-08:09 |
October | 64632.59 | 02-OCT-19:10 | 12338.45 | 01-OCT-00:10 | 89171.45 | 02-OCT-06:10 | 49607.07 | 02-OCT-06:19 | 45847.41 | 06-OCT-21:10 | 3884.39 | 05-OCT-20:10 | 117780.70 | 25-OCT-07:40 |
November | 64632.59 | 01-NOV-19:10 | 12338.45 | 01-NOV-00:10 | 89171.45 | 01-NOV-06:10 | 49607.07 | 01-NOV-06:19 | 36151.81 | 01-NOV-21:10 | 3510.70 | 01-NOV-18:10 | 139838.16 | 18-NOV-07:10 |
December | 64632.59 | 01-DEC-20:10 | 12338.45 | 01-DEC-00:10 | 89171.45 | 01-DEC-07:10 | 49607.07 | 01-DEC-07:19 | 32587.62 | 26-DEC-22:10 | 3048.89 | 25-DEC-16:10 | 137572.07 | 07-DEC-09:09 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 64632.59 | 12338.45 | 89171.45 | 49605.53 | 26655.80 | 2987.03 | 2260.67 | |||||||
Maximum of Months | 64632.59 | 12338.45 | 89171.45 | 49607.07 | 47693.26 | 4332.22 | 141230.50 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 88809.06 | 31-JAN-16:10 | 0.00 | 0.00 | 9938.94 | 01-JAN-00:20 | 4751.13 | 27-JAN-07:40 | 0.00 |
February | 51235.57 | 22-FEB-16:10 | 0.00 | 0.00 | 9938.94 | 01-FEB-07:10 | 4751.13 | 10-FEB-19:00 | 0.00 |
March | 85869.85 | 16-MAR-18:10 | 0.00 | 0.00 | 9938.94 | 09-MAR-13:50 | 4751.13 | 07-MAR-07:00 | 0.00 |
April | 125198.00 | 14-APR-18:10 | 0.00 | 0.00 | 9938.94 | 01-APR-08:00 | 4751.13 | 25-APR-06:40 | 0.00 |
May | 141274.88 | 31-MAY-18:10 | 0.00 | 0.00 | 9938.94 | 02-MAY-08:50 | 4751.13 | 23-MAY-18:00 | 0.00 |
June | 192789.78 | 28-JUN-18:10 | 0.00 | 0.00 | 9938.94 | 04-JUN-06:49 | 4751.12 | 26-JUN-06:30 | 0.00 |
July | 171659.87 | 20-JUL-18:10 | 0.00 | 0.00 | 9938.94 | 01-JUL-08:09 | 4751.12 | 05-JUL-06:00 | 0.00 |
August | 168132.10 | 25-AUG-18:19 | 0.00 | 0.00 | 9938.94 | 03-AUG-19:49 | 4751.12 | 28-AUG-06:30 | 0.00 |
September | 162285.80 | 08-SEP-18:10 | 0.00 | 0.00 | 9938.94 | 04-SEP-08:00 | 4751.12 | 18-SEP-06:30 | 0.00 |
October | 137942.36 | 01-OCT-18:10 | 0.00 | 0.00 | 9938.94 | 03-OCT-08:09 | 4751.13 | 16-OCT-06:00 | 0.00 |
November | 97679.48 | 01-NOV-15:09 | 0.00 | 0.00 | 9938.94 | 01-NOV-12:09 | 4751.13 | 30-NOV-07:49 | 0.00 |
December | 73015.36 | 25-DEC-16:10 | 0.00 | 0.00 | 9938.94 | 02-DEC-13:09 | 4751.13 | 06-DEC-07:40 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 51235.57 | 0.00 | 0.00 | 9938.94 | 4751.12 | 0.00 | |||
Maximum of Months | 192789.78 | 0.00 | 0.00 | 9938.94 | 4751.13 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 347059.60 | 13-JAN-07:10 | 36001.17 | 89171.45 | 12338.45 | 49600.84 | 14640.02 | 2831.76 | 130656.60 | 2339.35 | 0.00 |
February | 356816.62 | 08-FEB-07:10 | 36001.17 | 89171.45 | 12338.45 | 49600.84 | 14978.97 | 2138.34 | 141230.50 | 3231.48 | 0.00 |
March | 344902.03 | 13-MAR-06:10 | 36001.17 | 89171.45 | 12338.45 | 49600.84 | 13788.44 | 2831.34 | 130868.94 | 2185.55 | 0.00 |
April | 337463.78 | 14-APR-18:19 | 56726.79 | 77573.37 | 0.00 | 28168.00 | 31412.04 | 3203.92 | 0.00 | 123889.49 | 0.00 |
May | 347869.60 | 31-MAY-18:10 | 53184.46 | 77573.37 | 0.00 | 28157.33 | 27428.43 | 3212.31 | 0.00 | 141274.88 | 0.00 |
June | 408694.68 | 28-JUN-18:19 | 53381.59 | 77573.37 | 0.00 | 28166.69 | 36465.90 | 4195.21 | 0.00 | 191833.30 | 0.00 |
July | 403488.14 | 21-JUL-19:00 | 64632.59 | 86439.81 | 12338.45 | 10999.77 | 39404.55 | 3623.79 | 0.00 | 170273.34 | 0.00 |
August | 388499.05 | 25-AUG-18:19 | 56726.79 | 77573.37 | 0.00 | 28168.42 | 38027.58 | 3364.59 | 0.00 | 168132.10 | 0.00 |
September | 389491.48 | 08-SEP-19:10 | 64632.59 | 86439.81 | 12338.45 | 10993.88 | 39103.90 | 3576.98 | 0.00 | 156635.55 | 0.00 |
October | 365602.39 | 02-OCT-18:10 | 57474.69 | 77573.37 | 12338.45 | 28159.10 | 29931.21 | 3543.25 | 1684.63 | 137793.36 | 0.00 |
November | 322827.15 | 17-NOV-07:10 | 35632.18 | 89171.45 | 0.00 | 49600.84 | 16064.47 | 2834.19 | 116048.48 | 3978.15 | 0.00 |
December | 345739.43 | 27-DEC-07:10 | 36001.17 | 89171.45 | 12338.45 | 49600.84 | 14919.24 | 2833.31 | 129555.58 | 3227.59 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 322827.15 | 35632.18 | 77573.37 | 0.00 | 10993.88 | 13788.44 | 2138.34 | 0.00 | 2185.55 | 0.00 | |
Maximum of Months | 408694.68 | 64632.59 | 89171.45 | 12338.45 | 49600.84 | 39404.55 | 4195.21 | 141230.50 | 191833.30 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 0.00 | 0.00 | 222242.78 | 23-JAN-21:40 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 0.00 | 0.00 | 221864.83 | 02-FEB-21:00 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 0.00 | 0.00 | 216041.10 | 01-MAR-21:10 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 0.00 | 0.00 | 205500.68 | 03-APR-20:49 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 0.00 | 0.00 | 193484.38 | 01-MAY-20:10 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 0.00 | 0.00 | 182254.58 | 01-JUN-20:30 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 0.00 | 0.00 | 173480.63 | 03-JUL-20:00 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 0.00 | 0.00 | 175993.11 | 31-AUG-20:19 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 0.00 | 0.00 | 185286.59 | 29-SEP-20:00 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 0.00 | 0.00 | 199589.77 | 30-OCT-20:49 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 0.00 | 0.00 | 212538.96 | 29-NOV-21:49 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 0.00 | 0.00 | 218717.90 | 28-DEC-21:19 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 104248.32 | 0.00 | 0.00 | 0.00 | 173480.63 | 0.00 | ||
Maximum of Months | 104248.32 | 0.00 | 0.00 | 0.00 | 222242.78 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.71 | 1.17 | 21.71 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.75 | 0.67 | 21.75 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 21.88 | 10.67 | 21.88 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 21.81 | 2.83 | 21.81 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 21.84 | 4.50 | 21.84 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.82 | 1.83 | 21.82 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.81 | 1.00 | 21.81 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.74 | 0.50 | 21.74 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 23.17 | 21.84 | 23.17 | 21.84 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 21.88 | 10.67 | 21.88 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.78 | 0.50 | 21.78 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.79 | 1.00 | 21.79 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 13.67 | 21.91 | 13.67 | 21.91 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 21.82 | 3.00 | 21.82 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 21.82 | 2.67 | 21.82 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.70 | 0.67 | 21.70 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 21.50 | 21.87 | 21.50 | 21.87 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 13.67 | 21.91 | 13.67 | 21.91 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.70 | 0.33 | 21.70 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 21.77 | 7.00 | 21.77 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.75 | 1.50 | 21.75 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.73 | 0.83 | 21.73 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.77 | 0.50 | 21.77 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.69 | 0.17 | 21.69 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 10.33 | 21.76 | 10.33 | 21.76 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 21.77 | 7.00 | 21.77 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.69 | 0.33 | 21.69 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 21.77 | 7.50 | 21.77 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.69 | 1.50 | 21.69 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 21.74 | 2.33 | 21.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.71 | 0.83 | 21.71 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.69 | 0.33 | 21.69 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 12.83 | 21.75 | 12.83 | 21.75 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 21.77 | 7.50 | 21.77 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.79 | 0.33 | 21.79 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 21.94 | 4.50 | 21.94 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 21.98 | 6.33 | 21.98 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | 21.87 | 13.33 | 21.87 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 21.80 | 2.67 | 21.80 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 21.89 | 2.83 | 21.89 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 22.02 | 3.00 | 22.02 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 21.97 | 2.17 | 21.97 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 35.17 | 21.91 | 35.17 | 21.91 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | 22.02 | 13.33 | 22.02 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.77 | 1.17 | 21.77 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.72 | 1.00 | 21.72 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 14.83 | 21.91 | 14.83 | 21.91 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 21.85 | 3.33 | 21.85 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 21.84 | 10.00 | 21.84 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 21.87 | 2.67 | 21.87 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.86 | 1.17 | 21.86 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.78 | 0.50 | 21.78 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 34.67 | 21.87 | 34.67 | 21.87 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 14.83 | 21.91 | 14.83 | 21.91 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.73 | 0.67 | 21.73 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.79 | 1.00 | 21.79 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 19.33 | 21.93 | 19.33 | 21.93 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 21.87 | 3.50 | 21.87 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 21.83 | 5.50 | 21.83 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.77 | 0.83 | 21.77 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 30.83 | 21.89 | 30.83 | 21.89 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 19.33 | 21.93 | 19.33 | 21.93 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 21.95 | 4.50 | 21.95 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.71 | 0.17 | 21.71 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.76 | 0.33 | 21.76 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 21.87 | 2.00 | 21.87 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.68 | 0.50 | 21.68 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.75 | 1.83 | 21.75 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.70 | 0.83 | 21.70 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 21.86 | 3.67 | 21.86 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 21.87 | 4.83 | 21.87 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 21.91 | 4.17 | 21.91 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 21.91 | 2.83 | 21.91 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 21.86 | 2.17 | 21.86 |
Annual Sum or Average | 0.00 | 0.00 | 27.83 | 21.87 | 27.83 | 21.87 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.68 | 0.17 | 21.68 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 21.95 | 4.83 | 21.95 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 604.17 | 23.80 | 8.67 | 23.80 | 0.00 | 23.80 |
February | 643.17 | 23.22 | 1.83 | 23.23 | 0.00 | 23.23 |
March | 744.00 | 22.69 | 0.00 | 22.69 | 0.00 | 22.69 |
April | 720.00 | 23.00 | 0.00 | 23.00 | 0.00 | 23.00 |
May | 744.00 | 22.71 | 0.00 | 22.71 | 0.00 | 22.71 |
June | 719.33 | 22.99 | 2.33 | 22.99 | 2.33 | 22.99 |
July | 317.50 | 23.81 | 440.17 | 23.89 | 192.17 | 23.91 |
August | 259.50 | 23.97 | 584.67 | 23.95 | 195.33 | 23.96 |
September | 122.67 | 24.00 | 544.50 | 24.00 | 121.83 | 24.00 |
October | 294.50 | 24.00 | 150.33 | 24.00 | 22.67 | 24.00 |
November | 374.83 | 24.00 | 155.83 | 24.00 | 29.17 | 24.00 |
December | 679.83 | 23.99 | 5.67 | 23.99 | 0.00 | 23.99 |
Annual Sum or Average | 6223.50 | 23.34 | 1894.00 | 23.49 | 563.50 | 23.52 |
Minimum of Months | 122.67 | 22.69 | 0.00 | 22.69 | 0.00 | 22.69 |
Maximum of Months | 744.00 | 24.00 | 584.67 | 24.00 | 195.33 | 24.00 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 520.17 | 22.29 | 112.67 | 22.60 | 0.00 | 22.60 |
February | 583.50 | 21.63 | 31.83 | 21.75 | 0.00 | 21.75 |
March | 652.83 | 21.90 | 39.67 | 21.96 | 11.67 | 21.95 |
April | 351.67 | 22.75 | 96.67 | 23.02 | 0.00 | 23.02 |
May | 344.33 | 22.98 | 25.67 | 23.04 | 0.00 | 23.04 |
June | 103.00 | 23.37 | 444.83 | 23.87 | 1.67 | 23.87 |
July | 211.17 | 23.64 | 646.50 | 23.81 | 171.33 | 23.79 |
August | 211.33 | 23.58 | 673.17 | 23.77 | 183.83 | 23.75 |
September | 175.17 | 23.42 | 616.83 | 23.76 | 132.33 | 23.73 |
October | 366.17 | 22.55 | 250.67 | 23.11 | 24.83 | 23.13 |
November | 490.67 | 22.16 | 134.67 | 22.43 | 30.67 | 22.39 |
December | 588.17 | 21.87 | 88.17 | 21.98 | 38.67 | 21.92 |
Annual Sum or Average | 4598.17 | 22.38 | 3161.33 | 22.97 | 595.00 | 22.99 |
Minimum of Months | 103.00 | 21.63 | 25.67 | 21.75 | 0.00 | 21.75 |
Maximum of Months | 652.83 | 23.64 | 673.17 | 23.87 | 183.83 | 23.87 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 628.00 | 23.27 | 4.67 | 23.27 | 0.00 | 23.27 |
February | 612.83 | 22.78 | 12.67 | 22.79 | 7.00 | 22.80 |
March | 636.00 | 22.93 | 0.00 | 22.93 | 0.00 | 22.93 |
April | 415.83 | 23.57 | 14.50 | 23.58 | 0.00 | 23.58 |
May | 398.50 | 23.65 | 7.50 | 23.66 | 0.00 | 23.66 |
June | 96.00 | 23.65 | 245.00 | 23.89 | 2.67 | 23.89 |
July | 258.00 | 23.96 | 573.50 | 23.93 | 206.17 | 23.95 |
August | 235.00 | 23.96 | 617.83 | 23.93 | 226.50 | 23.94 |
September | 174.67 | 23.97 | 576.67 | 23.93 | 170.83 | 23.94 |
October | 414.67 | 23.47 | 154.67 | 23.59 | 35.00 | 23.61 |
November | 558.83 | 23.28 | 96.33 | 23.34 | 44.83 | 23.34 |
December | 733.50 | 23.03 | 0.00 | 23.03 | 0.00 | 23.03 |
Annual Sum or Average | 5161.83 | 23.30 | 2303.33 | 23.49 | 693.00 | 23.53 |
Minimum of Months | 96.00 | 22.78 | 0.00 | 22.79 | 0.00 | 22.80 |
Maximum of Months | 733.50 | 23.97 | 617.83 | 23.93 | 226.50 | 23.95 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 22.15 | 2.83 | 22.15 | 2.83 | 22.14 |
February | 672.00 | 21.80 | 0.00 | 21.80 | 0.00 | 21.80 |
March | 744.00 | 22.12 | 0.00 | 22.12 | 0.00 | 22.12 |
April | 702.67 | 23.26 | 0.00 | 23.26 | 0.00 | 23.26 |
May | 690.50 | 23.69 | 0.00 | 23.69 | 0.00 | 23.69 |
June | 212.50 | 23.95 | 67.67 | 23.96 | 0.00 | 23.96 |
July | 81.83 | 23.98 | 531.17 | 23.98 | 0.00 | 23.98 |
August | 62.33 | 23.89 | 565.17 | 23.95 | 0.00 | 23.95 |
September | 63.67 | 23.76 | 421.50 | 23.91 | 0.00 | 23.91 |
October | 592.83 | 22.93 | 92.50 | 23.06 | 0.00 | 23.06 |
November | 718.17 | 22.37 | 0.00 | 22.37 | 0.00 | 22.37 |
December | 744.00 | 21.74 | 34.33 | 21.71 | 34.33 | 21.69 |
Annual Sum or Average | 6028.50 | 22.59 | 1715.17 | 22.88 | 37.17 | 22.87 |
Minimum of Months | 62.33 | 21.74 | 0.00 | 21.71 | 0.00 | 21.69 |
Maximum of Months | 744.00 | 23.98 | 565.17 | 23.98 | 34.33 | 23.98 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.94 | 0.00 | 21.94 | 0.00 | 21.94 |
February | 672.00 | 21.56 | 0.00 | 21.56 | 0.00 | 21.56 |
March | 744.00 | 21.88 | 1.33 | 21.88 | 1.33 | 21.88 |
April | 715.50 | 23.05 | 0.00 | 23.05 | 0.00 | 23.05 |
May | 728.50 | 23.54 | 0.00 | 23.54 | 0.00 | 23.54 |
June | 237.33 | 23.91 | 58.17 | 23.93 | 0.00 | 23.93 |
July | 106.17 | 23.94 | 526.00 | 23.95 | 15.00 | 23.95 |
August | 77.33 | 23.79 | 531.00 | 23.91 | 6.67 | 23.91 |
September | 119.17 | 23.68 | 374.00 | 23.82 | 15.17 | 23.82 |
October | 610.17 | 22.71 | 80.83 | 22.85 | 2.17 | 22.85 |
November | 720.00 | 22.14 | 2.33 | 22.14 | 2.33 | 22.14 |
December | 744.00 | 21.53 | 48.00 | 21.50 | 48.00 | 21.47 |
Annual Sum or Average | 6218.17 | 22.42 | 1621.67 | 22.71 | 90.67 | 22.71 |
Minimum of Months | 77.33 | 21.53 | 0.00 | 21.50 | 0.00 | 21.47 |
Maximum of Months | 744.00 | 23.94 | 531.00 | 23.95 | 48.00 | 23.95 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 232.17 | 23.49 | 637.33 | 23.59 | 185.50 | 23.66 |
February | 250.33 | 23.72 | 604.83 | 23.57 | 224.17 | 23.66 |
March | 257.50 | 23.69 | 650.50 | 23.60 | 226.67 | 23.68 |
April | 236.83 | 23.88 | 643.00 | 23.68 | 224.67 | 23.74 |
May | 248.00 | 23.98 | 674.17 | 23.71 | 246.33 | 23.77 |
June | 336.00 | 23.98 | 694.67 | 23.67 | 336.00 | 23.75 |
July | 416.17 | 23.91 | 734.50 | 23.64 | 416.17 | 23.71 |
August | 420.67 | 23.91 | 737.00 | 23.62 | 420.67 | 23.70 |
September | 385.50 | 23.94 | 715.67 | 23.62 | 385.50 | 23.70 |
October | 276.67 | 23.79 | 676.50 | 23.63 | 255.17 | 23.70 |
November | 246.00 | 23.66 | 640.17 | 23.59 | 212.83 | 23.67 |
December | 213.83 | 23.20 | 607.17 | 23.53 | 146.67 | 23.60 |
Annual Sum or Average | 3519.67 | 23.80 | 8015.50 | 23.62 | 3280.33 | 23.70 |
Minimum of Months | 213.83 | 23.20 | 604.83 | 23.53 | 146.67 | 23.60 |
Maximum of Months | 420.67 | 23.98 | 737.00 | 23.71 | 420.67 | 23.77 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 181.17 | 23.24 | 276.33 | 23.68 | 11.67 | 23.67 |
February | 347.17 | 22.73 | 213.17 | 23.15 | 49.17 | 23.18 |
March | 377.83 | 22.84 | 181.00 | 23.20 | 6.50 | 23.20 |
April | 135.33 | 23.19 | 279.33 | 23.72 | 0.00 | 23.72 |
May | 125.50 | 23.14 | 258.83 | 23.71 | 0.00 | 23.71 |
June | 28.33 | 23.62 | 550.17 | 23.95 | 16.83 | 23.95 |
July | 323.33 | 23.92 | 682.50 | 23.91 | 318.50 | 23.91 |
August | 363.00 | 23.91 | 711.33 | 23.90 | 360.83 | 23.91 |
September | 284.33 | 23.91 | 708.67 | 23.92 | 284.33 | 23.92 |
October | 165.67 | 23.47 | 419.00 | 23.82 | 61.00 | 23.83 |
November | 234.67 | 23.26 | 352.00 | 23.58 | 78.67 | 23.53 |
December | 403.33 | 23.19 | 131.17 | 23.39 | 0.00 | 23.39 |
Annual Sum or Average | 2969.67 | 23.35 | 4763.50 | 23.70 | 1187.50 | 23.72 |
Minimum of Months | 28.33 | 22.73 | 131.17 | 23.15 | 0.00 | 23.18 |
Maximum of Months | 403.33 | 23.92 | 711.33 | 23.95 | 360.83 | 23.95 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 316.83 | 23.52 | 43.67 | 23.56 | 9.17 | 23.57 |
February | 424.00 | 23.07 | 101.00 | 23.23 | 33.00 | 23.27 |
March | 445.67 | 23.12 | 55.17 | 23.21 | 5.17 | 23.22 |
April | 288.67 | 23.52 | 43.67 | 23.58 | 0.00 | 23.58 |
May | 268.00 | 23.47 | 33.17 | 23.53 | 0.00 | 23.53 |
June | 68.17 | 23.50 | 356.67 | 23.90 | 11.83 | 23.90 |
July | 299.83 | 23.95 | 622.50 | 23.91 | 284.50 | 23.93 |
August | 323.33 | 23.96 | 668.17 | 23.92 | 321.50 | 23.93 |
September | 245.50 | 23.96 | 667.67 | 23.93 | 245.50 | 23.94 |
October | 232.50 | 23.62 | 227.17 | 23.79 | 54.17 | 23.81 |
November | 343.33 | 23.56 | 181.83 | 23.63 | 74.33 | 23.63 |
December | 584.83 | 23.45 | 3.00 | 23.45 | 0.00 | 23.45 |
Annual Sum or Average | 3840.67 | 23.52 | 3003.67 | 23.69 | 1039.17 | 23.72 |
Minimum of Months | 68.17 | 23.07 | 3.00 | 23.21 | 0.00 | 23.22 |
Maximum of Months | 584.83 | 23.96 | 668.17 | 23.93 | 321.50 | 23.94 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 719.67 | 21.59 | 0.00 | 21.59 | 0.00 | 21.59 |
February | 666.67 | 21.44 | 9.67 | 21.44 | 9.67 | 21.43 |
March | 735.33 | 21.55 | 10.17 | 21.54 | 10.17 | 21.53 |
April | 663.17 | 21.58 | 0.83 | 21.58 | 0.00 | 21.58 |
May | 684.50 | 21.60 | 0.00 | 21.60 | 0.00 | 21.60 |
June | 597.50 | 21.46 | 25.33 | 21.54 | 0.00 | 21.54 |
July | 621.00 | 21.44 | 11.17 | 21.47 | 0.00 | 21.47 |
August | 610.33 | 21.41 | 20.17 | 21.47 | 0.00 | 21.47 |
September | 596.17 | 21.42 | 10.33 | 21.45 | 0.50 | 21.45 |
October | 683.17 | 21.55 | 2.50 | 21.56 | 0.00 | 21.56 |
November | 691.83 | 21.57 | 25.50 | 21.57 | 25.17 | 21.57 |
December | 737.33 | 21.54 | 77.17 | 21.49 | 77.17 | 21.46 |
Annual Sum or Average | 8006.67 | 21.51 | 192.83 | 21.53 | 122.67 | 21.52 |
Minimum of Months | 596.17 | 21.41 | 0.00 | 21.44 | 0.00 | 21.43 |
Maximum of Months | 737.33 | 21.60 | 77.17 | 21.60 | 77.17 | 21.60 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 742.83 | 21.63 | 23.33 | 21.61 | 23.33 | 21.59 |
February | 671.50 | 21.32 | 12.50 | 21.32 | 12.50 | 21.31 |
March | 730.33 | 21.69 | 21.33 | 21.70 | 16.33 | 21.69 |
April | 669.00 | 21.83 | 8.67 | 21.88 | 0.00 | 21.88 |
May | 678.50 | 21.80 | 0.33 | 21.80 | 0.00 | 21.80 |
June | 576.50 | 21.56 | 30.33 | 21.66 | 0.00 | 21.66 |
July | 621.83 | 21.51 | 14.50 | 21.56 | 3.33 | 21.57 |
August | 619.67 | 21.59 | 31.33 | 21.69 | 11.33 | 21.73 |
September | 609.33 | 21.67 | 23.17 | 21.75 | 13.67 | 21.80 |
October | 703.17 | 21.84 | 3.33 | 21.85 | 1.33 | 21.86 |
November | 711.50 | 21.70 | 57.50 | 21.70 | 57.00 | 21.70 |
December | 743.67 | 21.31 | 229.17 | 21.22 | 229.17 | 21.17 |
Annual Sum or Average | 8077.83 | 21.62 | 455.50 | 21.63 | 368.00 | 21.62 |
Minimum of Months | 576.50 | 21.31 | 0.33 | 21.22 | 0.00 | 21.17 |
Maximum of Months | 743.67 | 21.84 | 229.17 | 21.88 | 229.17 | 21.88 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.43 | 6.17 | 21.43 | 6.17 | 21.43 |
February | 672.00 | 21.32 | 1.17 | 21.32 | 1.17 | 21.32 |
March | 744.00 | 21.62 | 2.50 | 21.62 | 2.50 | 21.61 |
April | 720.00 | 21.82 | 0.00 | 21.82 | 0.00 | 21.82 |
May | 744.00 | 21.86 | 0.00 | 21.86 | 0.00 | 21.86 |
June | 719.67 | 21.86 | 0.00 | 21.86 | 0.00 | 21.86 |
July | 742.83 | 21.77 | 1.33 | 21.77 | 1.33 | 21.78 |
August | 740.83 | 21.82 | 8.83 | 21.84 | 8.50 | 21.86 |
September | 717.17 | 21.87 | 10.83 | 21.89 | 10.83 | 21.91 |
October | 743.83 | 21.78 | 0.33 | 21.78 | 0.33 | 21.78 |
November | 720.00 | 21.53 | 32.00 | 21.55 | 32.00 | 21.56 |
December | 744.00 | 21.25 | 124.50 | 21.21 | 124.50 | 21.19 |
Annual Sum or Average | 8752.33 | 21.66 | 187.67 | 21.66 | 187.33 | 21.65 |
Minimum of Months | 672.00 | 21.25 | 0.00 | 21.21 | 0.00 | 21.19 |
Maximum of Months | 744.00 | 21.87 | 124.50 | 21.89 | 124.50 | 21.91 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.69 | 1.50 | 21.69 | 1.50 | 21.69 |
February | 672.00 | 21.54 | 9.17 | 21.53 | 9.17 | 21.53 |
March | 742.83 | 21.65 | 8.50 | 21.65 | 8.50 | 21.64 |
April | 673.33 | 21.64 | 0.00 | 21.64 | 0.00 | 21.64 |
May | 679.00 | 21.60 | 0.00 | 21.60 | 0.00 | 21.60 |
June | 535.50 | 21.23 | 1.17 | 21.23 | 0.00 | 21.23 |
July | 567.17 | 21.27 | 0.83 | 21.27 | 0.00 | 21.27 |
August | 559.50 | 21.24 | 3.67 | 21.25 | 0.00 | 21.25 |
September | 567.50 | 21.33 | 0.83 | 21.33 | 0.33 | 21.33 |
October | 683.83 | 21.59 | 0.00 | 21.59 | 0.00 | 21.59 |
November | 714.00 | 21.65 | 39.33 | 21.64 | 39.33 | 21.63 |
December | 744.00 | 21.61 | 69.83 | 21.57 | 69.83 | 21.54 |
Annual Sum or Average | 7882.67 | 21.52 | 134.83 | 21.52 | 128.67 | 21.51 |
Minimum of Months | 535.50 | 21.23 | 0.00 | 21.23 | 0.00 | 21.23 |
Maximum of Months | 744.00 | 21.69 | 69.83 | 21.69 | 69.83 | 21.69 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.63 | 26.17 | 21.62 | 26.17 | 21.60 |
February | 672.00 | 21.39 | 12.00 | 21.39 | 12.00 | 21.38 |
March | 741.50 | 21.81 | 16.50 | 21.80 | 15.67 | 21.79 |
April | 657.00 | 21.87 | 27.83 | 22.03 | 0.50 | 22.03 |
May | 619.50 | 21.68 | 43.50 | 21.98 | 1.00 | 21.99 |
June | 499.50 | 21.27 | 37.67 | 21.52 | 0.17 | 21.53 |
July | 551.33 | 21.29 | 13.17 | 21.38 | 3.17 | 21.41 |
August | 540.67 | 21.35 | 30.50 | 21.54 | 11.33 | 21.60 |
September | 550.50 | 21.54 | 41.17 | 21.76 | 13.33 | 21.83 |
October | 688.67 | 21.88 | 12.00 | 21.94 | 1.17 | 21.95 |
November | 717.50 | 21.70 | 73.33 | 21.68 | 72.67 | 21.66 |
December | 744.00 | 21.32 | 203.00 | 21.25 | 203.00 | 21.21 |
Annual Sum or Average | 7726.17 | 21.58 | 536.83 | 21.65 | 360.17 | 21.64 |
Minimum of Months | 499.50 | 21.27 | 12.00 | 21.25 | 0.17 | 21.21 |
Maximum of Months | 744.00 | 21.88 | 203.00 | 22.03 | 203.00 | 22.03 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 22.27 | 0.00 | 22.27 | 0.00 | 22.27 |
February | 672.00 | 21.69 | 0.00 | 21.69 | 0.00 | 21.69 |
March | 744.00 | 22.05 | 0.00 | 22.05 | 0.00 | 22.05 |
April | 718.33 | 23.18 | 0.00 | 23.18 | 0.00 | 23.18 |
May | 737.17 | 23.53 | 0.00 | 23.53 | 0.00 | 23.53 |
June | 367.00 | 23.83 | 45.33 | 23.84 | 3.50 | 23.85 |
July | 357.67 | 23.87 | 477.00 | 23.88 | 234.00 | 23.88 |
August | 358.33 | 23.81 | 506.67 | 23.84 | 264.33 | 23.83 |
September | 300.67 | 23.76 | 382.33 | 23.80 | 197.83 | 23.80 |
October | 629.17 | 23.05 | 84.83 | 23.14 | 36.33 | 23.18 |
November | 720.00 | 22.40 | 44.50 | 22.40 | 44.50 | 22.39 |
December | 744.00 | 21.78 | 0.00 | 21.78 | 0.00 | 21.78 |
Annual Sum or Average | 7092.33 | 22.75 | 1540.67 | 22.94 | 780.50 | 23.00 |
Minimum of Months | 300.67 | 21.69 | 0.00 | 21.69 | 0.00 | 21.69 |
Maximum of Months | 744.00 | 23.87 | 506.67 | 23.88 | 264.33 | 23.88 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 710.50 | 21.53 | 18.17 | 21.52 | 18.17 | 21.50 |
February | 661.33 | 21.37 | 45.33 | 21.34 | 45.33 | 21.32 |
March | 729.33 | 21.50 | 52.67 | 21.46 | 52.67 | 21.43 |
April | 641.50 | 21.51 | 6.00 | 21.52 | 1.33 | 21.52 |
May | 658.17 | 21.52 | 2.67 | 21.53 | 0.00 | 21.53 |
June | 556.17 | 21.37 | 48.50 | 21.52 | 0.00 | 21.52 |
July | 593.67 | 21.36 | 28.83 | 21.45 | 0.00 | 21.45 |
August | 582.67 | 21.34 | 46.67 | 21.49 | 0.83 | 21.49 |
September | 578.50 | 21.36 | 31.50 | 21.46 | 2.00 | 21.47 |
October | 673.67 | 21.50 | 22.17 | 21.52 | 13.17 | 21.51 |
November | 686.17 | 21.51 | 74.00 | 21.49 | 71.50 | 21.47 |
December | 734.00 | 21.47 | 182.50 | 21.39 | 182.50 | 21.33 |
Annual Sum or Average | 7805.67 | 21.45 | 559.00 | 21.47 | 387.50 | 21.45 |
Minimum of Months | 556.17 | 21.34 | 2.67 | 21.34 | 0.00 | 21.32 |
Maximum of Months | 734.00 | 21.53 | 182.50 | 21.53 | 182.50 | 21.53 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 742.50 | 21.55 | 74.33 | 21.49 | 74.33 | 21.45 |
February | 670.00 | 21.24 | 85.83 | 21.19 | 85.83 | 21.15 |
March | 724.33 | 21.63 | 69.50 | 21.62 | 61.67 | 21.57 |
April | 649.17 | 21.74 | 10.67 | 21.81 | 0.00 | 21.81 |
May | 662.17 | 21.73 | 3.33 | 21.74 | 0.00 | 21.74 |
June | 539.83 | 21.49 | 50.83 | 21.65 | 0.00 | 21.65 |
July | 591.50 | 21.42 | 29.17 | 21.51 | 4.17 | 21.53 |
August | 589.33 | 21.50 | 51.83 | 21.66 | 15.33 | 21.71 |
September | 591.50 | 21.60 | 32.00 | 21.70 | 21.67 | 21.76 |
October | 697.67 | 21.75 | 32.17 | 21.74 | 30.17 | 21.72 |
November | 708.67 | 21.60 | 143.50 | 21.54 | 142.17 | 21.50 |
December | 743.50 | 21.21 | 391.67 | 21.10 | 391.67 | 21.05 |
Annual Sum or Average | 7910.17 | 21.54 | 974.83 | 21.53 | 827.00 | 21.50 |
Minimum of Months | 539.83 | 21.21 | 3.33 | 21.10 | 0.00 | 21.05 |
Maximum of Months | 743.50 | 21.75 | 391.67 | 21.81 | 391.67 | 21.81 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 630.83 | 21.43 | 2.83 | 21.44 | 0.00 | 21.44 |
February | 627.50 | 21.45 | 9.00 | 21.45 | 9.00 | 21.44 |
March | 718.67 | 21.58 | 6.67 | 21.57 | 6.67 | 21.57 |
April | 664.67 | 21.58 | 0.00 | 21.58 | 0.00 | 21.58 |
May | 727.00 | 21.69 | 0.00 | 21.69 | 0.00 | 21.69 |
June | 629.83 | 21.52 | 0.00 | 21.52 | 0.00 | 21.52 |
July | 640.33 | 21.49 | 0.00 | 21.49 | 0.00 | 21.49 |
August | 614.50 | 21.41 | 0.83 | 21.42 | 0.50 | 21.42 |
September | 593.33 | 21.41 | 14.33 | 21.45 | 2.67 | 21.46 |
October | 639.17 | 21.46 | 16.33 | 21.50 | 0.00 | 21.50 |
November | 636.33 | 21.48 | 31.67 | 21.50 | 23.17 | 21.51 |
December | 669.50 | 21.50 | 22.00 | 21.49 | 21.17 | 21.48 |
Annual Sum or Average | 7791.67 | 21.50 | 103.67 | 21.51 | 63.17 | 21.51 |
Minimum of Months | 593.33 | 21.41 | 0.00 | 21.42 | 0.00 | 21.42 |
Maximum of Months | 727.00 | 21.69 | 31.67 | 21.69 | 23.17 | 21.69 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 178.83 | 23.48 | 109.17 | 23.67 | 8.33 | 23.67 |
February | 142.83 | 23.47 | 310.17 | 23.82 | 44.83 | 23.83 |
March | 117.33 | 23.47 | 312.67 | 23.85 | 4.83 | 23.85 |
April | 10.67 | 23.75 | 275.83 | 23.99 | 0.00 | 23.99 |
May | 0.00 | 0.00 | 349.17 | 23.99 | 0.00 | 23.99 |
June | 14.50 | 24.00 | 670.00 | 24.00 | 14.50 | 24.00 |
July | 296.17 | 24.00 | 699.00 | 24.00 | 296.17 | 24.00 |
August | 341.17 | 24.00 | 724.00 | 23.99 | 341.17 | 24.00 |
September | 269.00 | 24.00 | 720.00 | 23.99 | 269.00 | 23.99 |
October | 107.50 | 23.75 | 337.67 | 23.93 | 58.83 | 23.94 |
November | 205.83 | 23.70 | 243.67 | 23.83 | 78.67 | 23.84 |
December | 415.83 | 23.61 | 10.50 | 23.62 | 0.00 | 23.62 |
Annual Sum or Average | 2099.67 | 23.77 | 4761.83 | 23.92 | 1116.33 | 23.93 |
Minimum of Months | 0.00 | 0.00 | 10.50 | 23.62 | 0.00 | 23.62 |
Maximum of Months | 415.83 | 24.00 | 724.00 | 24.00 | 341.17 | 24.00 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 46.50 | 23.58 | 195.50 | 23.91 | 7.17 | 23.91 |
February | 53.33 | 23.82 | 452.50 | 23.95 | 37.17 | 23.95 |
March | 31.50 | 23.60 | 437.67 | 23.96 | 4.33 | 23.96 |
April | 0.00 | 0.00 | 373.33 | 23.99 | 0.00 | 23.99 |
May | 0.00 | 0.00 | 450.17 | 24.00 | 0.00 | 24.00 |
June | 13.50 | 24.00 | 694.17 | 24.00 | 13.50 | 24.00 |
July | 282.83 | 24.00 | 709.50 | 24.00 | 282.83 | 24.00 |
August | 319.33 | 24.00 | 730.67 | 24.00 | 319.33 | 24.00 |
September | 250.83 | 24.00 | 720.00 | 24.00 | 250.83 | 24.00 |
October | 74.67 | 23.89 | 429.50 | 23.98 | 57.67 | 23.98 |
November | 114.00 | 23.84 | 296.33 | 23.93 | 77.83 | 23.94 |
December | 165.00 | 23.59 | 15.50 | 23.62 | 0.00 | 23.62 |
Annual Sum or Average | 1351.50 | 23.90 | 5504.83 | 23.97 | 1050.67 | 23.97 |
Minimum of Months | 0.00 | 0.00 | 15.50 | 23.62 | 0.00 | 23.62 |
Maximum of Months | 319.33 | 24.00 | 730.67 | 24.00 | 319.33 | 24.00 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 504.67 | 23.99 | 722.67 | 23.95 | 504.67 | 23.96 |
February | 472.33 | 23.99 | 666.67 | 23.94 | 472.33 | 23.96 |
March | 514.83 | 23.99 | 727.50 | 23.96 | 514.83 | 23.97 |
April | 511.00 | 23.99 | 718.33 | 23.98 | 511.00 | 23.99 |
May | 534.67 | 23.99 | 744.00 | 23.99 | 534.67 | 23.99 |
June | 566.17 | 23.99 | 720.00 | 23.99 | 566.17 | 23.99 |
July | 696.00 | 23.99 | 744.00 | 23.99 | 696.00 | 23.99 |
August | 705.50 | 23.99 | 744.00 | 23.99 | 705.50 | 23.99 |
September | 643.83 | 23.99 | 720.00 | 23.99 | 643.83 | 23.99 |
October | 547.67 | 23.99 | 737.83 | 23.98 | 547.67 | 23.98 |
November | 517.50 | 23.98 | 697.17 | 23.96 | 516.83 | 23.97 |
December | 477.17 | 23.98 | 665.83 | 23.96 | 473.00 | 23.97 |
Annual Sum or Average | 6691.33 | 23.99 | 8608.00 | 23.98 | 6686.50 | 23.98 |
Minimum of Months | 472.33 | 23.98 | 665.83 | 23.94 | 472.33 | 23.96 |
Maximum of Months | 705.50 | 23.99 | 744.00 | 23.99 | 705.50 | 23.99 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 22.14 | 0.00 | 22.14 | 0.00 | 22.14 |
February | 672.00 | 21.61 | 0.00 | 21.61 | 0.00 | 21.61 |
March | 744.00 | 22.01 | 0.00 | 22.01 | 0.00 | 22.01 |
April | 596.00 | 23.24 | 0.00 | 23.24 | 0.00 | 23.24 |
May | 483.00 | 23.53 | 1.00 | 23.53 | 0.00 | 23.53 |
June | 114.17 | 23.69 | 141.17 | 23.86 | 0.00 | 23.86 |
July | 192.17 | 23.84 | 580.33 | 23.92 | 146.00 | 23.91 |
August | 195.00 | 23.77 | 627.00 | 23.87 | 160.00 | 23.86 |
September | 164.33 | 23.65 | 499.33 | 23.83 | 116.83 | 23.82 |
October | 579.83 | 22.79 | 110.33 | 22.97 | 21.17 | 22.99 |
November | 711.00 | 22.22 | 23.17 | 22.21 | 23.17 | 22.20 |
December | 744.00 | 21.65 | 42.33 | 21.62 | 42.33 | 21.59 |
Annual Sum or Average | 5939.50 | 22.48 | 2024.67 | 22.82 | 509.50 | 22.86 |
Minimum of Months | 114.17 | 21.61 | 0.00 | 21.61 | 0.00 | 21.59 |
Maximum of Months | 744.00 | 23.84 | 627.00 | 23.92 | 160.00 | 23.91 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.82373 | 25.46236 | 0.20138 | 5.98013 |
February | 672.00000 | 23.24581 | 39.16377 | 0.13759 | 5.57119 |
March | 744.00000 | 22.68715 | 32.07410 | -0.0511 | 5.28254 |
April | 720.00000 | 23.00489 | 23.86065 | -0.0217 | 5.21935 |
May | 744.00000 | 22.70959 | 23.57906 | -1.1374 | 32.44693 |
June | 720.00000 | 22.98954 | 35.14908 | -0.9587 | 24.73568 |
July | 744.00000 | 23.81274 | 49.53397 | -0.5529 | 11.89114 |
August | 744.00000 | 23.92243 | 51.64631 | -0.4871 | 10.12040 |
September | 720.00000 | 23.99449 | 50.03734 | -0.4536 | 9.40856 |
October | 744.00000 | 23.99580 | 30.29768 | 0.30531 | 7.13626 |
November | 720.00000 | 23.99760 | 29.50597 | 0.29755 | 7.06467 |
December | 744.00000 | 23.99048 | 18.15686 | 0.21037 | 5.95554 |
Annual Sum or Average | 8760.00000 | 23.51693 | 33.99024 | -0.2112 | 10.93710 |
Minimum of Months | 672.00000 | 22.68715 | 18.15686 | -1.1374 | 5.21935 |
Maximum of Months | 744.00000 | 23.99760 | 51.64631 | 0.30531 | 32.44693 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.79297 | 26.09920 | 0.06116 | 6.93771 |
February | 672.00000 | 21.92093 | 41.42261 | -0.1131 | 6.67913 |
March | 744.00000 | 22.12821 | 32.17754 | -0.1056 | 6.71443 |
April | 720.00000 | 23.35074 | 22.39162 | 0.18561 | 6.79725 |
May | 744.00000 | 23.48421 | 21.67745 | -0.6964 | 16.38848 |
June | 720.00000 | 23.84905 | 32.28644 | -0.4452 | 9.69984 |
July | 744.00000 | 23.83655 | 48.66122 | -0.3478 | 8.10700 |
August | 744.00000 | 23.79609 | 51.42099 | -0.3348 | 8.00807 |
September | 720.00000 | 23.76249 | 50.51732 | -0.3533 | 8.40481 |
October | 744.00000 | 23.23859 | 31.30621 | 0.22774 | 8.02953 |
November | 720.00000 | 22.71353 | 31.72923 | 0.07189 | 7.01178 |
December | 744.00000 | 22.31210 | 19.49768 | -0.1296 | 7.66685 |
Annual Sum or Average | 8760.00000 | 23.10496 | 34.03732 | -0.1657 | 8.38860 |
Minimum of Months | 672.00000 | 21.92093 | 19.49768 | -0.6964 | 6.67913 |
Maximum of Months | 744.00000 | 23.84905 | 51.42099 | 0.22774 | 16.38848 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.37111 | 27.09435 | 0.13294 | 5.64491 |
February | 672.00000 | 22.86857 | 40.95232 | 0.08713 | 5.52538 |
March | 744.00000 | 23.07153 | 32.37425 | 0.08834 | 5.68896 |
April | 720.00000 | 23.74020 | 23.49052 | 0.22055 | 6.26124 |
May | 744.00000 | 23.80838 | 22.71457 | -0.6653 | 14.56212 |
June | 720.00000 | 23.92294 | 33.40747 | -0.5254 | 11.00270 |
July | 744.00000 | 23.90419 | 49.72198 | -0.4283 | 9.10434 |
August | 744.00000 | 23.90039 | 52.38992 | -0.4125 | 8.74755 |
September | 720.00000 | 23.89417 | 51.51055 | -0.4277 | 9.01174 |
October | 744.00000 | 23.65952 | 32.34447 | 0.25646 | 6.88641 |
November | 720.00000 | 23.40592 | 32.23785 | 0.17725 | 6.10176 |
December | 744.00000 | 23.04811 | 20.70019 | 0.00256 | 5.36299 |
Annual Sum or Average | 8760.00000 | 23.55309 | 34.85915 | -0.1261 | 7.84096 |
Minimum of Months | 672.00000 | 22.86857 | 20.70019 | -0.6653 | 5.36299 |
Maximum of Months | 744.00000 | 23.92294 | 52.38992 | 0.25646 | 14.56212 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.36136 | 22.57200 | 0.71494 | 17.81770 |
February | 672.00000 | 23.31589 | 35.44914 | 0.77554 | 19.81175 |
March | 744.00000 | 23.33618 | 27.45888 | 0.74445 | 18.75308 |
April | 720.00000 | 23.42860 | 19.71701 | 0.76780 | 19.32312 |
May | 744.00000 | 23.45886 | 19.12222 | 0.13008 | 9.09938 |
June | 720.00000 | 23.47689 | 30.66090 | 0.25606 | 9.96735 |
July | 744.00000 | 23.46144 | 47.23398 | 0.34513 | 11.03975 |
August | 744.00000 | 23.43693 | 50.01118 | 0.35165 | 11.18211 |
September | 720.00000 | 23.43390 | 48.93640 | 0.32215 | 10.83408 |
October | 744.00000 | 23.40833 | 28.60452 | 0.80421 | 20.63875 |
November | 720.00000 | 23.36976 | 27.82678 | 0.75639 | 19.22551 |
December | 744.00000 | 23.32915 | 15.92929 | 0.64399 | 15.75999 |
Annual Sum or Average | 8760.00000 | 23.40186 | 31.08412 | 0.54947 | 15.25546 |
Minimum of Months | 672.00000 | 23.31589 | 15.92929 | 0.13008 | 9.09938 |
Maximum of Months | 744.00000 | 23.47689 | 50.01118 | 0.80421 | 20.63875 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.77130 | 30.45207 | 0.36107 | 8.26515 |
February | 672.00000 | 23.24735 | 44.56262 | 0.26093 | 7.29547 |
March | 744.00000 | 23.33277 | 36.29161 | 0.23764 | 7.00853 |
April | 720.00000 | 23.79275 | 27.29924 | 0.35725 | 8.09021 |
May | 744.00000 | 23.77169 | 26.70207 | -0.5208 | 11.16310 |
June | 720.00000 | 23.87578 | 37.10322 | -0.3532 | 8.00479 |
July | 744.00000 | 23.89066 | 53.24907 | -0.2410 | 6.58528 |
August | 744.00000 | 23.89856 | 55.74878 | -0.2112 | 6.25647 |
September | 720.00000 | 23.91934 | 54.67338 | -0.2093 | 6.29093 |
October | 744.00000 | 23.83262 | 35.67290 | 0.43852 | 9.75144 |
November | 720.00000 | 23.70251 | 35.79073 | 0.37022 | 8.53691 |
December | 744.00000 | 23.53533 | 24.48682 | 0.22634 | 6.92712 |
Annual Sum or Average | 8760.00000 | 23.71687 | 38.45056 | 0.05825 | 7.85378 |
Minimum of Months | 672.00000 | 23.24735 | 24.48682 | -0.5208 | 6.25647 |
Maximum of Months | 744.00000 | 23.91934 | 55.74878 | 0.43852 | 11.16310 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.74750 | 29.59988 | 0.26385 | 6.61562 |
February | 672.00000 | 23.36055 | 43.09848 | 0.23847 | 6.55994 |
March | 744.00000 | 23.42857 | 34.92767 | 0.20892 | 6.37832 |
April | 720.00000 | 23.77087 | 26.23487 | 0.26917 | 6.71698 |
May | 744.00000 | 23.77889 | 25.44827 | -0.6227 | 13.39831 |
June | 720.00000 | 23.87777 | 36.07883 | -0.4836 | 10.16344 |
July | 744.00000 | 23.88169 | 52.26487 | -0.3742 | 8.22211 |
August | 744.00000 | 23.89574 | 54.88145 | -0.3527 | 7.77823 |
September | 720.00000 | 23.91685 | 53.85689 | -0.3558 | 7.79876 |
October | 744.00000 | 23.83378 | 34.77315 | 0.34385 | 7.83990 |
November | 720.00000 | 23.73169 | 34.68596 | 0.29571 | 7.15056 |
December | 744.00000 | 23.55329 | 23.46005 | 0.15984 | 5.79798 |
Annual Sum or Average | 8760.00000 | 23.73346 | 37.39307 | -0.0360 | 7.87812 |
Minimum of Months | 672.00000 | 23.36055 | 23.46005 | -0.6227 | 5.79798 |
Maximum of Months | 744.00000 | 23.91685 | 54.88145 | 0.34385 | 13.39831 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.64429 | 37.38789 | -0.2321 | 7.15213 |
February | 672.00000 | 21.45675 | 50.75697 | -0.2560 | 6.99987 |
March | 744.00000 | 21.56924 | 41.54443 | -0.2454 | 7.10406 |
April | 720.00000 | 21.71530 | 32.99271 | -0.1454 | 6.53885 |
May | 744.00000 | 21.73428 | 33.33055 | -1.1868 | 36.02226 |
June | 720.00000 | 21.76650 | 40.27522 | -1.0610 | 30.37388 |
July | 744.00000 | 21.75006 | 43.77430 | -1.0795 | 31.05957 |
August | 744.00000 | 21.75242 | 45.28121 | -1.0752 | 30.96796 |
September | 720.00000 | 21.74393 | 46.04434 | -1.0947 | 31.84392 |
October | 744.00000 | 21.69639 | 37.61357 | -0.1543 | 6.64442 |
November | 720.00000 | 21.63499 | 40.23154 | -0.2129 | 6.97940 |
December | 744.00000 | 21.55126 | 31.47672 | -0.3411 | 8.45354 |
Annual Sum or Average | 8760.00000 | 21.66917 | 39.97309 | -0.5927 | 17.58247 |
Minimum of Months | 672.00000 | 21.45675 | 31.47672 | -1.1868 | 6.53885 |
Maximum of Months | 744.00000 | 21.76650 | 50.75697 | -0.1454 | 36.02226 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.63193 | 37.84351 | -0.2978 | 7.61550 |
February | 672.00000 | 21.32335 | 51.99237 | -0.3173 | 7.53472 |
March | 744.00000 | 21.75057 | 41.65989 | -0.2362 | 7.17953 |
April | 720.00000 | 21.97990 | 32.81588 | -0.1120 | 6.46838 |
May | 744.00000 | 21.95032 | 33.09428 | -1.1348 | 33.61969 |
June | 720.00000 | 21.92995 | 40.05582 | -1.0117 | 28.32944 |
July | 744.00000 | 21.81594 | 43.83904 | -1.0613 | 30.27207 |
August | 744.00000 | 21.88905 | 45.61825 | -1.0474 | 29.80857 |
September | 720.00000 | 21.94671 | 46.86998 | -1.0576 | 30.24638 |
October | 744.00000 | 21.93871 | 37.77962 | -0.1440 | 6.59595 |
November | 720.00000 | 21.72023 | 41.10487 | -0.2431 | 7.29223 |
December | 744.00000 | 21.31202 | 31.82586 | -0.4543 | 9.97485 |
Annual Sum or Average | 8760.00000 | 21.76795 | 40.28125 | -0.5953 | 17.14552 |
Minimum of Months | 672.00000 | 21.31202 | 31.82586 | -1.1348 | 6.46838 |
Maximum of Months | 744.00000 | 21.97990 | 51.99237 | -0.1120 | 33.61969 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.43104 | 35.01075 | -0.3748 | 8.11539 |
February | 672.00000 | 21.31844 | 47.72298 | -0.3286 | 7.40794 |
March | 744.00000 | 21.61755 | 38.70487 | -0.2941 | 7.21953 |
April | 720.00000 | 21.82011 | 30.36595 | -0.2505 | 6.89555 |
May | 744.00000 | 21.86207 | 30.41238 | -1.3223 | 42.08032 |
June | 720.00000 | 21.85672 | 39.30471 | -1.2240 | 37.32558 |
July | 744.00000 | 21.77460 | 45.19805 | -1.2238 | 37.30958 |
August | 744.00000 | 21.83047 | 47.26882 | -1.2084 | 36.65746 |
September | 720.00000 | 21.87567 | 48.49986 | -1.2005 | 36.29306 |
October | 744.00000 | 21.77950 | 36.05946 | -0.2437 | 6.89562 |
November | 720.00000 | 21.53123 | 38.53307 | -0.3205 | 7.67150 |
December | 744.00000 | 21.24897 | 28.58809 | -0.4741 | 9.85086 |
Annual Sum or Average | 8760.00000 | 21.66383 | 38.72840 | -0.7081 | 20.39722 |
Minimum of Months | 672.00000 | 21.24897 | 28.58809 | -1.3223 | 6.89555 |
Maximum of Months | 744.00000 | 21.87567 | 48.49986 | -0.2437 | 42.08032 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.69050 | 37.15995 | -0.2243 | 7.09915 |
February | 672.00000 | 21.53964 | 49.46973 | -0.2348 | 6.89235 |
March | 744.00000 | 21.65595 | 40.86358 | -0.2218 | 6.96827 |
April | 720.00000 | 21.74785 | 32.89217 | -0.1318 | 6.50351 |
May | 744.00000 | 21.75221 | 33.27027 | -1.1678 | 35.20213 |
June | 720.00000 | 21.76669 | 40.49551 | -1.0483 | 29.90941 |
July | 744.00000 | 21.75926 | 43.82286 | -1.0542 | 30.08686 |
August | 744.00000 | 21.75840 | 45.24819 | -1.0543 | 30.16353 |
September | 720.00000 | 21.75257 | 45.97904 | -1.0810 | 31.31116 |
October | 744.00000 | 21.73115 | 37.39797 | -0.1396 | 6.61391 |
November | 720.00000 | 21.66760 | 40.29811 | -0.2093 | 6.92487 |
December | 744.00000 | 21.61485 | 31.41122 | -0.3240 | 8.23685 |
Annual Sum or Average | 8760.00000 | 21.70406 | 39.77943 | -0.5766 | 17.22725 |
Minimum of Months | 672.00000 | 21.53964 | 31.41122 | -1.1678 | 6.50351 |
Maximum of Months | 744.00000 | 21.76669 | 49.46973 | -0.1318 | 35.20213 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.63362 | 37.63277 | -0.3008 | 7.47724 |
February | 672.00000 | 21.39272 | 50.63218 | -0.2984 | 7.24146 |
March | 744.00000 | 21.81933 | 40.95123 | -0.2164 | 6.88119 |
April | 720.00000 | 22.11799 | 32.50754 | -0.0780 | 6.71475 |
May | 744.00000 | 22.13933 | 33.02980 | -1.0663 | 32.11997 |
June | 720.00000 | 21.98324 | 40.26893 | -0.9836 | 27.82460 |
July | 744.00000 | 21.84906 | 43.91803 | -1.0290 | 29.25201 |
August | 744.00000 | 21.93596 | 45.52223 | -1.0148 | 28.88234 |
September | 720.00000 | 22.02145 | 46.45143 | -1.0263 | 29.56943 |
October | 744.00000 | 22.03572 | 37.34550 | -0.1172 | 6.61941 |
November | 720.00000 | 21.71404 | 41.13756 | -0.2493 | 7.19574 |
December | 744.00000 | 21.31547 | 31.78594 | -0.4491 | 9.69579 |
Annual Sum or Average | 8760.00000 | 21.83200 | 40.01210 | -0.5711 | 16.68675 |
Minimum of Months | 672.00000 | 21.31547 | 31.78594 | -1.0663 | 6.61941 |
Maximum of Months | 744.00000 | 22.13933 | 50.63218 | -0.0780 | 32.11997 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.60974 | 38.10778 | -0.2604 | 7.64673 |
February | 672.00000 | 21.39964 | 52.40839 | -0.2851 | 7.49308 |
March | 744.00000 | 21.53256 | 42.34942 | -0.2668 | 7.51199 |
April | 720.00000 | 21.70391 | 33.10430 | -0.1487 | 6.79303 |
May | 744.00000 | 21.73085 | 33.31337 | -1.1841 | 36.18625 |
June | 720.00000 | 21.77600 | 40.29286 | -1.0403 | 29.82609 |
July | 744.00000 | 21.75139 | 43.97040 | -1.0635 | 30.60567 |
August | 744.00000 | 21.75532 | 45.58744 | -1.0606 | 30.62315 |
September | 720.00000 | 21.74163 | 46.60088 | -1.0895 | 31.84283 |
October | 744.00000 | 21.67175 | 38.09899 | -0.1717 | 6.98780 |
November | 720.00000 | 21.59538 | 41.37619 | -0.2387 | 7.41580 |
December | 744.00000 | 21.49756 | 31.92610 | -0.3806 | 9.24733 |
Annual Sum or Average | 8760.00000 | 21.64855 | 40.50033 | -0.6014 | 17.75127 |
Minimum of Months | 672.00000 | 21.39964 | 31.92610 | -1.1841 | 6.79303 |
Maximum of Months | 744.00000 | 21.77600 | 52.40839 | -0.1487 | 36.18625 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.55346 | 38.64308 | -0.3394 | 8.31591 |
February | 672.00000 | 21.24324 | 53.62622 | -0.3546 | 8.21078 |
March | 744.00000 | 21.71126 | 42.46790 | -0.2579 | 7.65181 |
April | 720.00000 | 21.94581 | 32.99573 | -0.1179 | 6.71924 |
May | 744.00000 | 21.90704 | 33.18901 | -1.1414 | 34.12065 |
June | 720.00000 | 21.92212 | 40.11058 | -0.9947 | 27.87342 |
July | 744.00000 | 21.80806 | 44.02291 | -1.0476 | 29.88286 |
August | 744.00000 | 21.87657 | 45.87863 | -1.0369 | 29.55878 |
September | 720.00000 | 21.91403 | 47.36860 | -1.0607 | 30.48916 |
October | 744.00000 | 21.86399 | 38.34540 | -0.1719 | 6.97588 |
November | 720.00000 | 21.62811 | 42.40165 | -0.2820 | 7.91604 |
December | 744.00000 | 21.21164 | 32.42144 | -0.5070 | 11.16764 |
Annual Sum or Average | 8760.00000 | 21.71782 | 40.85438 | -0.6114 | 17.47320 |
Minimum of Months | 672.00000 | 21.21164 | 32.42144 | -1.1414 | 6.71924 |
Maximum of Months | 744.00000 | 21.94581 | 53.62622 | -0.1179 | 34.12065 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.72056 | 37.22458 | -0.1675 | 7.05515 |
February | 672.00000 | 21.57566 | 48.89651 | -0.2079 | 6.84872 |
March | 744.00000 | 21.63602 | 41.15619 | -0.2288 | 7.16802 |
April | 720.00000 | 21.71085 | 33.83645 | -0.1771 | 6.88544 |
May | 744.00000 | 21.72834 | 34.25410 | -1.2611 | 39.57968 |
June | 720.00000 | 21.74871 | 41.07650 | -1.1544 | 34.48700 |
July | 744.00000 | 21.74574 | 44.91361 | -1.1366 | 33.63555 |
August | 744.00000 | 21.74842 | 46.28684 | -1.1204 | 33.05342 |
September | 720.00000 | 21.74772 | 47.01158 | -1.1146 | 32.91245 |
October | 744.00000 | 21.71982 | 37.90681 | -0.1392 | 6.81055 |
November | 720.00000 | 21.69144 | 40.25437 | -0.1686 | 6.92073 |
December | 744.00000 | 21.68719 | 32.20154 | -0.2439 | 7.77782 |
Annual Sum or Average | 8760.00000 | 21.70589 | 40.34719 | -0.5958 | 18.67238 |
Minimum of Months | 672.00000 | 21.57566 | 32.20154 | -1.2611 | 6.81055 |
Maximum of Months | 744.00000 | 21.74871 | 48.89651 | -0.1392 | 39.57968 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.84297 | 30.38189 | 0.31229 | 7.22456 |
February | 672.00000 | 23.79892 | 42.88083 | 0.37693 | 8.23024 |
March | 744.00000 | 23.85608 | 34.79718 | 0.35861 | 7.91517 |
April | 720.00000 | 23.97457 | 26.47617 | 0.39459 | 8.38184 |
May | 744.00000 | 23.99171 | 25.59336 | -0.4197 | 8.78980 |
June | 720.00000 | 23.99555 | 36.32779 | -0.2901 | 6.90031 |
July | 744.00000 | 23.99532 | 52.33872 | -0.1892 | 5.95426 |
August | 744.00000 | 23.99448 | 55.03644 | -0.1829 | 5.83184 |
September | 720.00000 | 23.99248 | 54.16432 | -0.2096 | 6.04516 |
October | 744.00000 | 23.93327 | 35.35386 | 0.42138 | 9.10842 |
November | 720.00000 | 23.86732 | 35.24259 | 0.36009 | 8.09151 |
December | 744.00000 | 23.76910 | 24.31098 | 0.22784 | 6.30186 |
Annual Sum or Average | 8760.00000 | 23.91819 | 37.69637 | 0.09474 | 7.39155 |
Minimum of Months | 672.00000 | 23.76910 | 24.31098 | -0.4197 | 5.83184 |
Maximum of Months | 744.00000 | 23.99555 | 55.03644 | 0.42138 | 9.10842 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.92635 | 29.58560 | 0.36587 | 7.92232 |
February | 672.00000 | 23.90661 | 41.92165 | 0.43982 | 9.22447 |
March | 744.00000 | 23.93847 | 33.99207 | 0.41346 | 8.72517 |
April | 720.00000 | 23.99008 | 25.97552 | 0.42639 | 8.91933 |
May | 744.00000 | 23.99471 | 25.17068 | -0.3806 | 8.13570 |
June | 720.00000 | 23.99642 | 35.97373 | -0.2541 | 6.49478 |
July | 744.00000 | 23.99621 | 51.97780 | -0.1535 | 5.70128 |
August | 744.00000 | 23.99567 | 54.66475 | -0.1468 | 5.58629 |
September | 720.00000 | 23.99486 | 53.77081 | -0.1729 | 5.75337 |
October | 744.00000 | 23.96897 | 34.77512 | 0.45884 | 9.74124 |
November | 720.00000 | 23.94249 | 34.46608 | 0.41113 | 8.85492 |
December | 744.00000 | 23.88295 | 23.44240 | 0.29156 | 6.90308 |
Annual Sum or Average | 8760.00000 | 23.96138 | 37.09932 | 0.13958 | 7.65240 |
Minimum of Months | 672.00000 | 23.88295 | 23.44240 | -0.3806 | 5.58629 |
Maximum of Months | 744.00000 | 23.99642 | 54.66475 | 0.45884 | 9.74124 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.90239 | 28.71049 | 1.01082 | 28.46395 |
February | 672.00000 | 23.90204 | 40.67804 | 1.07468 | 31.04384 |
March | 744.00000 | 23.91846 | 33.18484 | 1.05337 | 30.18766 |
April | 720.00000 | 23.97807 | 25.77496 | 1.10285 | 32.33147 |
May | 744.00000 | 23.98842 | 25.17005 | 0.59494 | 16.26029 |
June | 720.00000 | 23.99244 | 35.94773 | 0.73929 | 20.00132 |
July | 744.00000 | 23.99296 | 51.49344 | 0.82616 | 22.71103 |
August | 744.00000 | 23.99291 | 54.06631 | 0.83120 | 22.87761 |
September | 720.00000 | 23.99257 | 53.11555 | 0.79147 | 21.50039 |
October | 744.00000 | 23.96005 | 34.17351 | 1.12186 | 33.26295 |
November | 720.00000 | 23.91742 | 33.56723 | 1.05251 | 30.23623 |
December | 744.00000 | 23.86408 | 22.46226 | 0.92957 | 25.36808 |
Annual Sum or Average | 8760.00000 | 23.95033 | 36.48832 | 0.92625 | 26.14901 |
Minimum of Months | 672.00000 | 23.86408 | 22.46226 | 0.59494 | 16.26029 |
Maximum of Months | 744.00000 | 23.99296 | 54.06631 | 1.12186 | 33.26295 |
Report: OccupantComfortDataSummaryMonthly
For: STORAGE_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.94084 | 25.72611 | -0.2560 | 6.58029 |
February | 672.00000 | 21.56193 | 40.45026 | -0.2611 | 6.57657 |
March | 744.00000 | 21.88467 | 30.99612 | -0.2361 | 6.59498 |
April | 720.00000 | 23.05932 | 21.22954 | -0.0062 | 5.32732 |
May | 744.00000 | 23.54830 | 20.10218 | -0.8428 | 20.20239 |
June | 720.00000 | 23.96577 | 30.79031 | -0.6086 | 12.89577 |
July | 744.00000 | 23.94860 | 47.02866 | -0.5057 | 10.54474 |
August | 744.00000 | 23.88183 | 49.88803 | -0.5149 | 10.71319 |
September | 720.00000 | 23.79214 | 49.19182 | -0.5554 | 11.64325 |
October | 744.00000 | 22.91487 | 30.33178 | 0.01981 | 6.05798 |
November | 720.00000 | 22.13755 | 30.95431 | -0.1732 | 6.14996 |
December | 744.00000 | 21.53308 | 18.73031 | -0.3989 | 8.57076 |
Annual Sum or Average | 8760.00000 | 22.85369 | 32.88900 | -0.3627 | 9.34747 |
Minimum of Months | 672.00000 | 21.53308 | 18.73031 | -0.8428 | 5.32732 |
Maximum of Months | 744.00000 | 23.96577 | 49.88803 | 0.01981 | 20.20239 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.26930 | 28.70615 | -0.1789 | 5.86803 |
February | 672.00000 | 21.69182 | 43.58174 | -0.2329 | 6.22176 |
March | 744.00000 | 22.04788 | 34.14613 | -0.1992 | 6.12650 |
April | 720.00000 | 23.17967 | 24.69524 | 0.02110 | 5.30687 |
May | 744.00000 | 23.52921 | 23.79062 | -0.8598 | 20.78630 |
June | 720.00000 | 23.90135 | 34.37910 | -0.6498 | 14.02418 |
July | 744.00000 | 23.87079 | 50.67096 | -0.5517 | 11.58048 |
August | 744.00000 | 23.82789 | 53.48748 | -0.5489 | 11.45797 |
September | 720.00000 | 23.78945 | 52.66635 | -0.5695 | 11.94283 |
October | 744.00000 | 23.17293 | 33.48690 | 0.07969 | 5.95617 |
November | 720.00000 | 22.40300 | 34.03781 | -0.1118 | 5.60302 |
December | 744.00000 | 21.78047 | 21.87674 | -0.3409 | 7.69329 |
Annual Sum or Average | 8760.00000 | 22.96172 | 36.23221 | -0.3464 | 9.40835 |
Minimum of Months | 672.00000 | 21.69182 | 21.87674 | -0.8598 | 5.30687 |
Maximum of Months | 744.00000 | 23.90135 | 53.48748 | 0.07969 | 20.78630 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.13746 | 26.62822 | -0.1863 | 6.10818 |
February | 672.00000 | 21.61209 | 41.51952 | -0.2298 | 6.34414 |
March | 744.00000 | 22.01008 | 31.94040 | -0.1834 | 6.26114 |
April | 720.00000 | 23.35740 | 22.09613 | 0.09949 | 5.71470 |
May | 744.00000 | 23.68781 | 21.15209 | -0.7424 | 17.02857 |
June | 720.00000 | 23.93452 | 31.88211 | -0.5525 | 11.59955 |
July | 744.00000 | 23.93957 | 47.97888 | -0.4455 | 9.42195 |
August | 744.00000 | 23.89718 | 50.78007 | -0.4451 | 9.36820 |
September | 720.00000 | 23.84057 | 50.01654 | -0.4800 | 10.07362 |
October | 744.00000 | 23.03351 | 31.27924 | 0.07972 | 6.40782 |
November | 720.00000 | 22.23206 | 31.96235 | -0.1270 | 6.04011 |
December | 744.00000 | 21.65153 | 19.75264 | -0.3539 | 8.06714 |
Annual Sum or Average | 8760.00000 | 22.95109 | 33.85238 | -0.2981 | 8.55624 |
Minimum of Months | 672.00000 | 21.61209 | 19.75264 | -0.7424 | 5.71470 |
Maximum of Months | 744.00000 | 23.93957 | 50.78007 | 0.09949 | 17.02857 |
Report: OccupantComfortDataSummaryMonthly
For: MECH_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.15060 | 25.11117 | -0.2123 | 6.21920 |
February | 672.00000 | 21.80097 | 39.59436 | -0.2109 | 6.11801 |
March | 744.00000 | 22.11568 | 30.29258 | -0.1874 | 6.20143 |
April | 720.00000 | 23.27575 | 20.66089 | 0.04035 | 5.39792 |
May | 744.00000 | 23.71440 | 19.60934 | -0.7886 | 18.31958 |
June | 720.00000 | 23.98331 | 30.40087 | -0.5976 | 12.60868 |
July | 744.00000 | 23.96842 | 46.62116 | -0.4944 | 10.30862 |
August | 744.00000 | 23.92828 | 49.40139 | -0.4957 | 10.29311 |
September | 720.00000 | 23.88321 | 48.59340 | -0.5231 | 10.89314 |
October | 744.00000 | 23.12922 | 29.68624 | 0.06625 | 6.07597 |
November | 720.00000 | 22.37354 | 30.23567 | -0.1234 | 5.87729 |
December | 744.00000 | 21.74486 | 18.21357 | -0.3545 | 7.91941 |
Annual Sum or Average | 8760.00000 | 23.01150 | 32.30785 | -0.3246 | 8.87691 |
Minimum of Months | 672.00000 | 21.74486 | 18.21357 | -0.7886 | 5.39792 |
Maximum of Months | 744.00000 | 23.98331 | 49.40139 | 0.06625 | 18.31958 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.463275E+11 | 118725.94 | 31-JAN-16:01 | 710.83 | 0.198437E+12 | 0.00 | 0.244764E+12 | 4.31 | 4.72 | 01-JAN-00:07 | 0.00 | 0.00 |
February | 0.157854E+11 | 69159.14 | 22-FEB-16:01 | 595.29 | 0.718331E+11 | 0.00 | 0.876186E+11 | 4.11 | 4.72 | 01-FEB-01:00 | 0.00 | 0.00 |
March | 0.433526E+11 | 109089.98 | 20-MAR-18:01 | 704.47 | 0.183906E+12 | 0.00 | 0.227259E+12 | 4.25 | 4.72 | 01-MAR-02:65 | 0.00 | 0.00 |
April | 0.121657E+12 | 152986.28 | 14-APR-18:03 | 720.00 | 0.471607E+12 | 0.00 | 0.593264E+12 | 4.09 | 4.72 | 07-APR-04:07 | 0.00 | 0.00 |
May | 0.159839E+12 | 168444.23 | 31-MAY-18:03 | 744.00 | 0.597084E+12 | 0.00 | 0.756923E+12 | 3.90 | 4.72 | 01-MAY-04:03 | 0.00 | 0.00 |
June | 0.223772E+12 | 201173.10 | 15-JUN-18:03 | 720.00 | 0.761334E+12 | 0.00 | 0.985106E+12 | 3.54 | 4.46 | 21-JUN-05:00 | 0.00 | 0.00 |
July | 0.243230E+12 | 180962.30 | 20-JUL-18:03 | 744.00 | 0.860119E+12 | 0.00 | 0.110335E+13 | 3.61 | 4.46 | 01-JUL-05:55 | 0.00 | 0.00 |
August | 0.235764E+12 | 187551.20 | 25-AUG-15:03 | 744.00 | 0.840974E+12 | 0.00 | 0.107674E+13 | 3.66 | 4.52 | 05-AUG-18:00 | 0.00 | 0.00 |
September | 0.207329E+12 | 177086.89 | 08-SEP-18:03 | 720.00 | 0.773318E+12 | 0.00 | 0.980647E+12 | 3.81 | 4.54 | 22-SEP-06:00 | 0.00 | 0.00 |
October | 0.108657E+12 | 158040.53 | 02-OCT-18:03 | 741.10 | 0.428045E+12 | 0.00 | 0.536702E+12 | 4.21 | 4.72 | 08-OCT-06:30 | 0.00 | 0.00 |
November | 0.494731E+11 | 114810.64 | 09-NOV-16:01 | 692.75 | 0.212642E+12 | 0.00 | 0.262115E+12 | 4.33 | 4.72 | 04-NOV-01:07 | 0.00 | 0.00 |
December | 0.273663E+11 | 104264.00 | 22-DEC-16:01 | 619.13 | 0.119797E+12 | 0.00 | 0.147163E+12 | 3.81 | 4.72 | 01-DEC-02:65 | 0.00 | 0.00 |
Annual Sum or Average | 0.148255E+13 | 8455.57 | 0.551910E+13 | 0.00 | 0.700165E+13 | 3.97 | 0.00 | 0.00 | ||||
Minimum of Months | 0.157854E+11 | 69159.14 | 595.29 | 0.718331E+11 | 0.00 | 0.876186E+11 | 3.54 | 4.46 | 0.00 | 0.00 | ||
Maximum of Months | 0.243230E+12 | 201173.10 | 744.00 | 0.860119E+12 | 0.00 | 0.110335E+13 | 4.33 | 4.72 | 0.00 | 0.00 |
Report: DXReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.673140E+10 | 0.00 | 239.17 | 0.667614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16913.69 | 31-JAN-16:01 | 16913.69 | 31-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.173107E+10 | 0.00 | 131.67 | 0.173107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13696.42 | 18-FEB-14:00 | 13696.42 | 18-FEB-14:00 | 0.00 | 0.00 | 0.00 |
March | 0.788858E+10 | 0.00 | 282.00 | 0.788858E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17352.00 | 16-MAR-15:01 | 17352.00 | 16-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.209364E+11 | 0.00 | 514.83 | 0.209364E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 19396.98 | 14-APR-15:01 | 19396.98 | 14-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.271449E+11 | 0.00 | 580.50 | 0.271449E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 19771.08 | 31-MAY-15:01 | 19771.08 | 31-MAY-15:01 | 0.00 | 0.00 | 0.00 |
June | 0.322280E+11 | 0.00 | 570.00 | 0.322132E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 22035.42 | 17-JUN-16:00 | 21841.07 | 28-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.365742E+11 | 0.00 | 589.00 | 0.329298E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 30440.72 | 27-JUL-06:50 | 21332.52 | 19-JUL-13:00 | 0.00 | 0.00 | 0.00 |
August | 0.364052E+11 | 0.00 | 589.00 | 0.325697E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 35354.65 | 05-AUG-08:15 | 21446.91 | 25-AUG-15:01 | 0.00 | 0.00 | 0.00 |
September | 0.345802E+11 | 0.00 | 570.00 | 0.298804E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 39084.40 | 04-SEP-08:15 | 20630.16 | 08-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.179529E+11 | 0.00 | 461.33 | 0.174483E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 28096.49 | 03-OCT-06:40 | 20187.68 | 01-OCT-13:00 | 0.00 | 0.00 | 0.00 |
November | 0.849251E+10 | 0.00 | 283.00 | 0.711766E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24520.20 | 12-NOV-13:07 | 17435.90 | 01-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 0.357276E+10 | 0.00 | 152.17 | 0.357276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15710.75 | 25-DEC-16:01 | 15710.75 | 25-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.234238E+12 | 0.00 | 4962.67 | 0.220109E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.173107E+10 | 0.00 | 131.67 | 0.173107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13696.42 | 13696.42 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.365742E+11 | 0.00 | 589.00 | 0.329298E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 39084.40 | 21841.07 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.107972E+12 | 0.00 | 369.25 | 0.107511E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 180591.53 | 31-JAN-16:20 | 180591.53 | 31-JAN-16:20 | 0.00 | 0.00 | 0.00 |
February | 0.264415E+11 | 0.00 | 219.92 | 0.264047E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 104882.16 | 18-FEB-14:00 | 104882.16 | 18-FEB-14:00 | 0.00 | 0.00 | 0.00 |
March | 0.116734E+12 | 0.00 | 411.78 | 0.116734E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 198409.83 | 16-MAR-18:20 | 198409.83 | 16-MAR-18:20 | 0.00 | 0.00 | 0.00 |
April | 0.319960E+12 | 0.00 | 658.83 | 0.319960E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 259996.46 | 14-APR-18:10 | 259996.46 | 14-APR-18:10 | 0.00 | 0.00 | 0.00 |
May | 0.415918E+12 | 0.00 | 734.67 | 0.415918E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 271206.36 | 31-MAY-18:20 | 271206.36 | 31-MAY-18:20 | 0.00 | 0.00 | 0.00 |
June | 0.523412E+12 | 0.00 | 720.00 | 0.522504E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 331193.25 | 17-JUN-17:17 | 314400.12 | 28-JUN-18:30 | 0.00 | 0.00 | 0.00 |
July | 0.609911E+12 | 0.00 | 744.00 | 0.533141E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 411961.92 | 13-JUL-18:01 | 310177.38 | 21-JUL-20:10 | 0.00 | 0.00 | 0.00 |
August | 0.596575E+12 | 0.00 | 744.00 | 0.526328E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 443465.59 | 18-AUG-22:00 | 304102.17 | 10-AUG-18:30 | 0.00 | 0.00 | 0.00 |
September | 0.549704E+12 | 0.00 | 720.00 | 0.474730E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 471103.92 | 10-SEP-19:15 | 300089.05 | 08-SEP-20:10 | 0.00 | 0.00 | 0.00 |
October | 0.282087E+12 | 0.00 | 604.50 | 0.274082E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 334728.63 | 02-OCT-20:00 | 274172.58 | 03-OCT-20:10 | 0.00 | 0.00 | 0.00 |
November | 0.123583E+12 | 0.00 | 417.61 | 0.109564E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 202220.42 | 01-NOV-18:10 | 202220.42 | 01-NOV-18:10 | 0.00 | 0.00 | 0.00 |
December | 0.573642E+11 | 0.00 | 266.95 | 0.573642E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 159214.32 | 22-DEC-16:03 | 159214.32 | 22-DEC-16:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.372966E+13 | 0.00 | 6611.50 | 0.348424E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.264415E+11 | 0.00 | 219.92 | 0.264047E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 104882.16 | 104882.16 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.609911E+12 | 0.00 | 744.00 | 0.533141E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 471103.92 | 314400.12 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.367030E+10 | 0.00 | 524.26 | 0.298155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19075.52 | 06-JAN-16:01 | 19075.52 | 06-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.142915E+10 | 0.00 | 283.58 | 0.748481E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19071.45 | 25-FEB-19:01 | 19071.45 | 25-FEB-19:01 | 0.00 | 0.00 | 0.00 |
March | 0.291697E+10 | 0.00 | 459.70 | 0.176629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19072.80 | 08-MAR-16:01 | 19072.80 | 08-MAR-16:01 | 0.00 | 0.00 | 0.00 |
April | 0.829385E+10 | 0.00 | 675.92 | 0.733655E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19076.75 | 14-APR-18:01 | 19076.75 | 14-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.973121E+10 | 0.00 | 711.98 | 0.895066E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19075.78 | 19-MAY-18:01 | 19075.78 | 19-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.129149E+11 | 0.00 | 702.22 | 0.998079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19077.68 | 07-JUN-18:02 | 19077.68 | 07-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.124804E+11 | 0.00 | 721.75 | 0.822548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19057.93 | 03-JUL-15:01 | 19057.93 | 03-JUL-15:01 | 0.00 | 0.00 | 0.00 |
August | 0.123536E+11 | 0.00 | 720.43 | 0.794137E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19075.36 | 25-AUG-08:61 | 19075.36 | 25-AUG-08:61 | 0.00 | 0.00 | 0.00 |
September | 0.109269E+11 | 0.00 | 692.91 | 0.636313E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17807.60 | 03-SEP-08:61 | 15366.77 | 15-SEP-08:61 | 0.00 | 0.00 | 0.00 |
October | 0.707140E+10 | 0.00 | 652.25 | 0.511785E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19076.37 | 28-OCT-18:01 | 19076.37 | 28-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.384873E+10 | 0.00 | 529.06 | 0.270755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19075.36 | 25-NOV-16:01 | 19075.36 | 25-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.188651E+10 | 0.00 | 347.91 | 0.181007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19076.14 | 24-DEC-16:01 | 19076.14 | 24-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.875240E+11 | 0.00 | 7021.98 | 0.639298E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.142915E+10 | 0.00 | 283.58 | 0.748481E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17807.60 | 15366.77 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.129149E+11 | 0.00 | 721.75 | 0.998079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19077.68 | 19077.68 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.951881E+09 | 0.00 | 226.26 | 0.765302E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18958.37 | 05-JAN-16:01 | 18958.37 | 05-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.350666E+09 | 0.00 | 105.91 | 0.161981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19113.99 | 01-FEB-17:11 | 19113.99 | 01-FEB-17:11 | 0.00 | 0.00 | 0.00 |
March | 0.129768E+10 | 0.00 | 257.22 | 0.673274E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19186.23 | 23-MAR-21:11 | 19186.23 | 23-MAR-21:11 | 0.00 | 0.00 | 0.00 |
April | 0.679896E+10 | 0.00 | 576.25 | 0.592701E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19997.31 | 26-APR-21:51 | 19997.31 | 26-APR-21:51 | 0.00 | 0.00 | 0.00 |
May | 0.913124E+10 | 0.00 | 631.29 | 0.839500E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20890.81 | 20-MAY-08:61 | 20890.81 | 20-MAY-08:61 | 0.00 | 0.00 | 0.00 |
June | 0.128361E+11 | 0.00 | 662.69 | 0.100430E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 21070.36 | 14-JUN-08:61 | 21070.36 | 14-JUN-08:61 | 0.00 | 0.00 | 0.00 |
July | 0.123219E+11 | 0.00 | 701.16 | 0.816621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21587.03 | 01-JUL-08:61 | 21587.03 | 01-JUL-08:61 | 0.00 | 0.00 | 0.00 |
August | 0.114650E+11 | 0.00 | 673.88 | 0.729138E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20083.37 | 24-AUG-08:21 | 20083.37 | 24-AUG-08:21 | 0.00 | 0.00 | 0.00 |
September | 0.939964E+10 | 0.00 | 616.51 | 0.531407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19220.11 | 05-SEP-08:31 | 15501.63 | 25-SEP-20:41 | 0.00 | 0.00 | 0.00 |
October | 0.446063E+10 | 0.00 | 463.79 | 0.298364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19385.67 | 17-OCT-21:51 | 19385.67 | 17-OCT-21:51 | 0.00 | 0.00 | 0.00 |
November | 0.133928E+10 | 0.00 | 267.06 | 0.808235E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18957.52 | 25-NOV-16:01 | 18957.52 | 25-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.315399E+09 | 0.00 | 91.43 | 0.301043E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18957.53 | 24-DEC-16:01 | 18957.53 | 24-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.706683E+11 | 0.00 | 5273.45 | 0.508301E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.315399E+09 | 0.00 | 91.43 | 0.161981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18957.52 | 15501.63 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.128361E+11 | 0.00 | 701.16 | 0.100430E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 21587.03 | 21587.03 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.466116E+11 | 0.00 | 632.67 | 0.423058E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 48635.17 | 14-JAN-13:40 | 48635.17 | 14-JAN-13:40 | 0.00 | 0.00 | 0.00 |
February | 0.184492E+11 | 0.00 | 411.62 | 0.107218E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 37490.25 | 01-FEB-14:15 | 37490.25 | 01-FEB-14:15 | 0.00 | 0.00 | 0.00 |
March | 0.206120E+11 | 0.00 | 526.51 | 0.113455E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 34236.05 | 18-MAR-13:30 | 33554.44 | 18-MAR-15:03 | 0.00 | 0.00 | 0.00 |
April | 0.410611E+11 | 0.00 | 698.81 | 0.389954E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 34042.36 | 14-APR-13:40 | 34042.36 | 14-APR-13:40 | 0.00 | 0.00 | 0.00 |
May | 0.404797E+11 | 0.00 | 742.58 | 0.402102E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 28591.55 | 09-MAY-17:13 | 28591.55 | 09-MAY-17:13 | 0.00 | 0.00 | 0.00 |
June | 0.516330E+11 | 0.00 | 720.00 | 0.408430E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 35676.44 | 28-JUN-19:10 | 33796.74 | 27-JUN-19:10 | 0.00 | 0.00 | 0.00 |
July | 0.543426E+11 | 0.00 | 744.00 | 0.293069E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 35373.47 | 21-JUL-20:20 | 31683.28 | 07-JUL-20:20 | 0.00 | 0.00 | 0.00 |
August | 0.577572E+11 | 0.00 | 743.67 | 0.298933E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 39873.50 | 28-AUG-12:30 | 38446.53 | 27-AUG-14:00 | 0.00 | 0.00 | 0.00 |
September | 0.582558E+11 | 0.00 | 720.00 | 0.288441E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 45086.68 | 28-SEP-13:30 | 43377.83 | 28-SEP-15:03 | 0.00 | 0.00 | 0.00 |
October | 0.514197E+11 | 0.00 | 696.73 | 0.389386E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 47335.30 | 18-OCT-13:20 | 47335.30 | 18-OCT-13:20 | 0.00 | 0.00 | 0.00 |
November | 0.402148E+11 | 0.00 | 600.80 | 0.326320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 50931.76 | 20-NOV-14:30 | 49693.72 | 20-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 0.347546E+11 | 0.00 | 538.84 | 0.344794E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 48230.09 | 25-DEC-13:30 | 48230.09 | 25-DEC-13:30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.515591E+12 | 0.00 | 7776.21 | 0.378516E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.184492E+11 | 0.00 | 411.62 | 0.107218E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 28591.55 | 28591.55 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.582558E+11 | 0.00 | 744.00 | 0.423058E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 50931.76 | 49693.72 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.103573E+11 | 0.00 | 338.93 | 0.803946E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 116664.68 | 31-JAN-19:01 | 116664.68 | 31-JAN-19:01 | 0.00 | 0.00 | 0.00 |
February | 0.106031E+11 | 0.00 | 328.22 | 0.402703E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 111547.54 | 27-FEB-19:01 | 111547.54 | 27-FEB-19:01 | 0.00 | 0.00 | 0.00 |
March | 0.170812E+11 | 0.00 | 366.10 | 0.102807E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 119292.56 | 22-MAR-21:21 | 119292.56 | 22-MAR-21:21 | 0.00 | 0.00 | 0.00 |
April | 0.387800E+11 | 0.00 | 504.34 | 0.353476E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 120729.47 | 26-APR-21:51 | 120729.47 | 26-APR-21:51 | 0.00 | 0.00 | 0.00 |
May | 0.533159E+11 | 0.00 | 575.04 | 0.506016E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 126473.99 | 20-MAY-08:61 | 126473.99 | 20-MAY-08:61 | 0.00 | 0.00 | 0.00 |
June | 0.745968E+11 | 0.00 | 638.10 | 0.599782E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 127160.46 | 25-JUN-07:31 | 127160.46 | 25-JUN-07:31 | 0.00 | 0.00 | 0.00 |
July | 0.794651E+11 | 0.00 | 665.93 | 0.529482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 129302.56 | 01-JUL-08:61 | 129302.56 | 01-JUL-08:61 | 0.00 | 0.00 | 0.00 |
August | 0.722636E+11 | 0.00 | 628.49 | 0.453949E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 119908.18 | 28-AUG-18:31 | 119451.20 | 24-AUG-08:21 | 0.00 | 0.00 | 0.00 |
September | 0.620603E+11 | 0.00 | 565.29 | 0.365260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 120231.57 | 10-SEP-21:51 | 119272.48 | 29-SEP-08:21 | 0.00 | 0.00 | 0.00 |
October | 0.313486E+11 | 0.00 | 449.03 | 0.224159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 118883.49 | 19-OCT-18:01 | 118883.49 | 19-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.138918E+11 | 0.00 | 332.20 | 0.868061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 116882.80 | 10-NOV-16:01 | 116882.80 | 10-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.583954E+10 | 0.00 | 240.34 | 0.563150E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 114564.07 | 03-DEC-09:02 | 114564.07 | 03-DEC-09:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.469603E+12 | 0.00 | 5632.02 | 0.339872E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.583954E+10 | 0.00 | 240.34 | 0.402703E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 111547.54 | 111547.54 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.794651E+11 | 0.00 | 665.93 | 0.599782E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 129302.56 | 129302.56 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.351302E+10 | 0.00 | 535.63 | 0.281480E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16884.38 | 04-JAN-16:01 | 16884.38 | 04-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.173270E+10 | 0.00 | 337.46 | 0.856442E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16879.48 | 02-FEB-16:01 | 16879.48 | 02-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.311308E+10 | 0.00 | 507.36 | 0.184161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16873.86 | 22-MAR-18:01 | 16873.86 | 22-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.844489E+10 | 0.00 | 702.51 | 0.751029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16885.76 | 14-APR-18:01 | 16885.76 | 14-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.101108E+11 | 0.00 | 730.74 | 0.938220E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16885.32 | 19-MAY-18:01 | 16885.32 | 19-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.132144E+11 | 0.00 | 711.52 | 0.104064E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 16883.99 | 07-JUN-15:01 | 16883.99 | 07-JUN-15:01 | 0.00 | 0.00 | 0.00 |
July | 0.133372E+11 | 0.00 | 733.07 | 0.924042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16869.08 | 03-JUL-15:01 | 16869.08 | 03-JUL-15:01 | 0.00 | 0.00 | 0.00 |
August | 0.130687E+11 | 0.00 | 731.64 | 0.880086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16883.54 | 25-AUG-08:61 | 16883.54 | 25-AUG-08:61 | 0.00 | 0.00 | 0.00 |
September | 0.113267E+11 | 0.00 | 703.43 | 0.695467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15715.79 | 03-SEP-08:61 | 13437.86 | 26-SEP-08:61 | 0.00 | 0.00 | 0.00 |
October | 0.737404E+10 | 0.00 | 676.11 | 0.545489E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16884.53 | 28-OCT-18:01 | 16884.53 | 28-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.357757E+10 | 0.00 | 527.28 | 0.254344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16883.82 | 20-NOV-09:01 | 16883.82 | 20-NOV-09:01 | 0.00 | 0.00 | 0.00 |
December | 0.193693E+10 | 0.00 | 364.91 | 0.182865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16885.02 | 31-DEC-09:01 | 16885.02 | 31-DEC-09:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.907500E+11 | 0.00 | 7261.68 | 0.676346E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.173270E+10 | 0.00 | 337.46 | 0.856442E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15715.79 | 13437.86 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.133372E+11 | 0.00 | 733.07 | 0.104064E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 16885.76 | 16885.76 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.943566E+09 | 0.00 | 220.04 | 0.694770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17215.88 | 27-JAN-09:51 | 17215.88 | 27-JAN-09:51 | 0.00 | 0.00 | 0.00 |
February | 0.636621E+09 | 0.00 | 144.51 | 0.246177E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15437.76 | 18-FEB-09:01 | 13318.18 | 21-FEB-09:01 | 0.00 | 0.00 | 0.00 |
March | 0.156582E+10 | 0.00 | 305.94 | 0.805606E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16778.47 | 31-MAR-15:01 | 16778.47 | 31-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.675562E+10 | 0.00 | 602.65 | 0.591888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19385.60 | 11-APR-08:51 | 19385.60 | 11-APR-08:51 | 0.00 | 0.00 | 0.00 |
May | 0.918633E+10 | 0.00 | 644.70 | 0.848777E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21363.84 | 21-MAY-08:61 | 21363.84 | 21-MAY-08:61 | 0.00 | 0.00 | 0.00 |
June | 0.130447E+11 | 0.00 | 672.77 | 0.104290E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 20450.60 | 13-JUN-07:52 | 20450.60 | 13-JUN-07:52 | 0.00 | 0.00 | 0.00 |
July | 0.131298E+11 | 0.00 | 711.61 | 0.911626E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20494.68 | 01-JUL-07:42 | 20494.68 | 01-JUL-07:42 | 0.00 | 0.00 | 0.00 |
August | 0.121167E+11 | 0.00 | 684.10 | 0.801026E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19403.32 | 25-AUG-07:31 | 19403.32 | 25-AUG-07:31 | 0.00 | 0.00 | 0.00 |
September | 0.971656E+10 | 0.00 | 626.91 | 0.583064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18180.72 | 04-SEP-08:51 | 15360.33 | 15-SEP-08:51 | 0.00 | 0.00 | 0.00 |
October | 0.468725E+10 | 0.00 | 495.15 | 0.318816E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19072.73 | 17-OCT-08:51 | 19072.73 | 17-OCT-08:51 | 0.00 | 0.00 | 0.00 |
November | 0.119144E+10 | 0.00 | 252.17 | 0.706814E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18081.74 | 10-NOV-09:51 | 18081.74 | 10-NOV-09:51 | 0.00 | 0.00 | 0.00 |
December | 0.379290E+09 | 0.00 | 102.20 | 0.331824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16824.74 | 25-DEC-09:51 | 16824.74 | 25-DEC-09:51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.733538E+11 | 0.00 | 5462.78 | 0.537661E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.379290E+09 | 0.00 | 102.20 | 0.246177E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15437.76 | 13318.18 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.131298E+11 | 0.00 | 711.61 | 0.104290E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 21363.84 | 21363.84 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.814578E+09 | 0.00 | 414.12 | 0.668600E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5058.56 | 04-JAN-16:01 | 5058.56 | 04-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.306332E+09 | 0.00 | 216.03 | 0.168030E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5057.50 | 25-FEB-19:01 | 5057.50 | 25-FEB-19:01 | 0.00 | 0.00 | 0.00 |
March | 0.681204E+09 | 0.00 | 388.30 | 0.433983E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5058.92 | 21-MAR-18:01 | 5058.92 | 21-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.208709E+10 | 0.00 | 664.36 | 0.184427E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5058.95 | 14-APR-18:01 | 5058.95 | 14-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.248115E+10 | 0.00 | 709.30 | 0.226624E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5058.85 | 09-MAY-08:61 | 5058.85 | 09-MAY-08:61 | 0.00 | 0.00 | 0.00 |
June | 0.339930E+10 | 0.00 | 702.23 | 0.262255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5059.04 | 07-JUN-18:02 | 5059.04 | 07-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.326322E+10 | 0.00 | 722.18 | 0.214237E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5053.90 | 03-JUL-15:01 | 5053.90 | 03-JUL-15:01 | 0.00 | 0.00 | 0.00 |
August | 0.320927E+10 | 0.00 | 719.30 | 0.206026E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5058.64 | 25-AUG-08:61 | 5058.64 | 25-AUG-08:61 | 0.00 | 0.00 | 0.00 |
September | 0.276090E+10 | 0.00 | 690.65 | 0.158977E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5003.34 | 03-SEP-08:61 | 4092.22 | 01-SEP-08:61 | 0.00 | 0.00 | 0.00 |
October | 0.166465E+10 | 0.00 | 599.63 | 0.119141E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5058.52 | 31-OCT-15:01 | 5058.52 | 31-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.843009E+09 | 0.00 | 429.26 | 0.603731E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5058.32 | 21-NOV-19:01 | 5058.32 | 21-NOV-19:01 | 0.00 | 0.00 | 0.00 |
December | 0.409967E+09 | 0.00 | 271.53 | 0.393166E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5058.01 | 30-DEC-16:01 | 5058.01 | 30-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.219207E+11 | 0.00 | 6526.90 | 0.159844E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.306332E+09 | 0.00 | 216.03 | 0.168030E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5003.34 | 4092.22 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.339930E+10 | 0.00 | 722.18 | 0.262255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5059.04 | 5059.04 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.183945E+09 | 0.00 | 137.18 | 0.152407E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5023.78 | 04-JAN-16:01 | 5023.78 | 04-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 61973587.16 | 0.00 | 64.98 | 30411660.87 | 0.00 | 0.00 | 0.00 | 0.00 | 5042.22 | 01-FEB-17:11 | 5042.22 | 01-FEB-17:11 | 0.00 | 0.00 | 0.00 |
March | 0.286723E+09 | 0.00 | 197.10 | 0.156694E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5081.70 | 23-MAR-21:11 | 5081.70 | 23-MAR-21:11 | 0.00 | 0.00 | 0.00 |
April | 0.173382E+10 | 0.00 | 574.22 | 0.150788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5296.87 | 26-APR-21:51 | 5296.87 | 26-APR-21:51 | 0.00 | 0.00 | 0.00 |
May | 0.236077E+10 | 0.00 | 632.53 | 0.215450E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5448.18 | 20-MAY-08:61 | 5448.18 | 20-MAY-08:61 | 0.00 | 0.00 | 0.00 |
June | 0.339916E+10 | 0.00 | 663.54 | 0.265503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5514.71 | 14-JUN-08:61 | 5514.71 | 14-JUN-08:61 | 0.00 | 0.00 | 0.00 |
July | 0.323182E+10 | 0.00 | 701.95 | 0.213294E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5639.93 | 01-JUL-08:61 | 5639.93 | 01-JUL-08:61 | 0.00 | 0.00 | 0.00 |
August | 0.299954E+10 | 0.00 | 674.63 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5236.74 | 24-AUG-08:21 | 5236.74 | 24-AUG-08:21 | 0.00 | 0.00 | 0.00 |
September | 0.239756E+10 | 0.00 | 617.01 | 0.134063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5180.30 | 04-SEP-08:51 | 4033.33 | 27-SEP-08:51 | 0.00 | 0.00 | 0.00 |
October | 0.104597E+10 | 0.00 | 413.43 | 0.688805E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5078.81 | 16-OCT-21:51 | 5078.81 | 16-OCT-21:51 | 0.00 | 0.00 | 0.00 |
November | 0.258184E+09 | 0.00 | 188.06 | 0.159791E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5022.38 | 05-NOV-15:01 | 5022.38 | 05-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 57577185.31 | 0.00 | 49.36 | 53965362.82 | 0.00 | 0.00 | 0.00 | 0.00 | 5023.10 | 30-DEC-16:01 | 5023.10 | 30-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.180170E+11 | 0.00 | 4913.99 | 0.129363E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 57577185.31 | 0.00 | 49.36 | 30411660.87 | 0.00 | 0.00 | 0.00 | 0.00 | 5022.38 | 4033.33 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.339916E+10 | 0.00 | 701.95 | 0.265503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5639.93 | 5639.93 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.102965E+11 | 0.00 | 646.94 | 0.898523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22330.46 | 19-JAN-16:01 | 22330.46 | 19-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.471671E+10 | 0.00 | 443.45 | 0.276071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22332.82 | 27-FEB-19:01 | 22332.82 | 27-FEB-19:01 | 0.00 | 0.00 | 0.00 |
March | 0.538537E+10 | 0.00 | 535.03 | 0.348060E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22330.37 | 09-MAR-19:01 | 22330.37 | 09-MAR-19:01 | 0.00 | 0.00 | 0.00 |
April | 0.103643E+11 | 0.00 | 672.89 | 0.909956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22329.68 | 09-APR-15:01 | 22329.68 | 09-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.106900E+11 | 0.00 | 703.67 | 0.943366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22332.45 | 23-MAY-18:01 | 22332.45 | 23-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.142338E+11 | 0.00 | 695.39 | 0.101495E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 22332.84 | 10-JUN-08:61 | 22332.84 | 10-JUN-08:61 | 0.00 | 0.00 | 0.00 |
July | 0.154820E+11 | 0.00 | 717.67 | 0.994014E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22322.57 | 02-JUL-18:01 | 22322.57 | 02-JUL-18:01 | 0.00 | 0.00 | 0.00 |
August | 0.161644E+11 | 0.00 | 717.68 | 0.104884E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 22323.96 | 25-AUG-08:61 | 22323.96 | 25-AUG-08:61 | 0.00 | 0.00 | 0.00 |
September | 0.157469E+11 | 0.00 | 693.34 | 0.100625E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 22171.28 | 03-SEP-08:61 | 18243.15 | 24-SEP-08:61 | 0.00 | 0.00 | 0.00 |
October | 0.122792E+11 | 0.00 | 681.77 | 0.972857E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22328.74 | 28-OCT-18:01 | 22328.74 | 28-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.915706E+10 | 0.00 | 605.59 | 0.736490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22331.98 | 27-NOV-16:01 | 22331.98 | 27-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.771177E+10 | 0.00 | 535.68 | 0.749714E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22332.91 | 31-DEC-09:01 | 22332.91 | 31-DEC-09:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.132228E+12 | 0.00 | 7649.10 | 0.989910E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.471671E+10 | 0.00 | 443.45 | 0.276071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22171.28 | 18243.15 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.161644E+11 | 0.00 | 717.68 | 0.104884E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 22332.91 | 22332.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 835.71 | 667.64 | 168.07 | 1279.62 | 426.82 | 0.00 | 0.00 | 0.00 |
February | 521.47 | 349.59 | 171.87 | 720.56 | 397.09 | 0.00 | 0.00 | 0.00 |
March | 431.69 | 218.75 | 212.94 | 651.57 | 360.70 | 0.00 | 0.00 | 0.00 |
April | 378.88 | 156.07 | 222.81 | 729.43 | 206.58 | 0.00 | 0.00 | 0.00 |
May | 253.16 | 44.04 | 209.12 | 546.52 | 139.09 | 0.00 | 0.00 | 0.00 |
June | 214.28 | 16.35 | 197.94 | 623.43 | 52.57 | 0.00 | 0.00 | 0.00 |
July | 217.14 | 20.65 | 196.50 | 613.54 | 34.94 | 0.00 | 0.00 | 0.00 |
August | 268.51 | 75.62 | 192.88 | 702.84 | 46.80 | 0.00 | 0.00 | 0.00 |
September | 381.40 | 161.20 | 220.20 | 832.71 | 71.70 | 0.00 | 0.00 | 0.00 |
October | 612.22 | 423.82 | 188.40 | 1041.33 | 255.76 | 0.00 | 0.00 | 0.00 |
November | 719.63 | 552.71 | 166.92 | 1090.72 | 380.92 | 0.00 | 0.00 | 0.00 |
December | 778.28 | 616.61 | 161.67 | 1139.53 | 504.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 467.74 | 275.23 | 192.51 | 832.02 | 239.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 214.28 | 16.35 | 161.67 | 546.52 | 34.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 835.71 | 667.64 | 222.81 | 1279.62 | 504.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2353.32 | 1880.03 | 473.29 | 3554.98 | 1305.72 | 0.00 | 0.00 | 0.00 |
February | 1468.41 | 984.43 | 483.99 | 1977.00 | 1266.05 | 0.00 | 0.00 | 0.00 |
March | 1215.60 | 615.98 | 599.62 | 1779.04 | 1139.52 | 0.00 | 0.00 | 0.00 |
April | 1066.89 | 439.48 | 627.41 | 2028.14 | 620.26 | 0.00 | 0.00 | 0.00 |
May | 712.87 | 124.01 | 588.87 | 1521.22 | 414.89 | 0.00 | 0.00 | 0.00 |
June | 603.41 | 46.04 | 557.38 | 1753.35 | 150.88 | 0.00 | 0.00 | 0.00 |
July | 611.46 | 58.14 | 553.32 | 1719.29 | 105.44 | 0.00 | 0.00 | 0.00 |
August | 756.09 | 212.94 | 543.15 | 1967.35 | 143.19 | 0.00 | 0.00 | 0.00 |
September | 1074.00 | 453.93 | 620.07 | 2326.80 | 216.96 | 0.00 | 0.00 | 0.00 |
October | 1723.96 | 1193.45 | 530.51 | 2896.46 | 778.86 | 0.00 | 0.00 | 0.00 |
November | 2026.44 | 1556.40 | 470.05 | 3024.60 | 1176.09 | 0.00 | 0.00 | 0.00 |
December | 2191.58 | 1736.32 | 455.26 | 3155.10 | 1555.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1317.12 | 775.03 | 542.09 | 2311.61 | 737.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 603.41 | 46.04 | 455.26 | 1521.22 | 105.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2353.32 | 1880.03 | 627.41 | 3554.98 | 1555.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3057.09 | 2442.27 | 614.83 | 4727.73 | 1702.46 | 0.00 | 0.00 | 0.00 |
February | 1907.55 | 1278.83 | 628.73 | 2636.69 | 1692.01 | 0.00 | 0.00 | 0.00 |
March | 1579.13 | 800.19 | 778.94 | 2374.74 | 1516.73 | 0.00 | 0.00 | 0.00 |
April | 1385.95 | 570.91 | 815.04 | 2725.96 | 808.50 | 0.00 | 0.00 | 0.00 |
May | 926.06 | 161.09 | 764.97 | 2051.91 | 542.11 | 0.00 | 0.00 | 0.00 |
June | 783.87 | 59.80 | 724.06 | 2371.19 | 193.70 | 0.00 | 0.00 | 0.00 |
July | 794.32 | 75.52 | 718.79 | 2326.25 | 133.03 | 0.00 | 0.00 | 0.00 |
August | 982.21 | 276.63 | 705.58 | 2651.46 | 178.70 | 0.00 | 0.00 | 0.00 |
September | 1395.19 | 589.68 | 805.51 | 3121.68 | 271.69 | 0.00 | 0.00 | 0.00 |
October | 2239.52 | 1550.35 | 689.17 | 3863.35 | 1012.75 | 0.00 | 0.00 | 0.00 |
November | 2632.46 | 2021.85 | 610.62 | 4021.33 | 1541.16 | 0.00 | 0.00 | 0.00 |
December | 2846.99 | 2255.58 | 591.41 | 4194.83 | 2048.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1711.02 | 1006.81 | 704.21 | 3092.96 | 967.10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 783.87 | 59.80 | 591.41 | 2051.91 | 133.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3057.09 | 2442.27 | 815.04 | 4727.73 | 2048.53 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 165.24 | 132.00 | 33.23 | 259.00 | 77.75 | 0.00 | 0.00 | 0.00 |
February | 103.10 | 69.12 | 33.98 | 145.11 | 75.85 | 0.00 | 0.00 | 0.00 |
March | 85.35 | 43.25 | 42.10 | 130.94 | 68.60 | 0.00 | 0.00 | 0.00 |
April | 74.91 | 30.86 | 44.05 | 152.41 | 31.79 | 0.00 | 0.00 | 0.00 |
May | 50.05 | 8.71 | 41.35 | 119.73 | 18.96 | 0.00 | 0.00 | 0.00 |
June | 42.37 | 3.23 | 39.14 | 143.77 | 4.90 | 0.00 | 0.00 | 0.00 |
July | 42.93 | 4.08 | 38.85 | 143.44 | 3.08 | 0.00 | 0.00 | 0.00 |
August | 53.09 | 14.95 | 38.14 | 158.12 | 3.49 | 0.00 | 0.00 | 0.00 |
September | 75.41 | 31.87 | 43.54 | 180.63 | 6.04 | 0.00 | 0.00 | 0.00 |
October | 121.05 | 83.80 | 37.25 | 214.10 | 41.75 | 0.00 | 0.00 | 0.00 |
November | 142.28 | 109.28 | 33.00 | 220.65 | 68.82 | 0.00 | 0.00 | 0.00 |
December | 153.88 | 121.91 | 31.97 | 231.09 | 95.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 92.48 | 54.42 | 38.06 | 175.17 | 41.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 42.37 | 3.23 | 31.97 | 119.73 | 3.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 165.24 | 132.00 | 44.05 | 259.00 | 95.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 127.00 | 79.12 | 47.88 | 185.79 | 160.70 | 0.00 | 0.00 | 0.00 |
February | 102.87 | 49.92 | 52.94 | 120.98 | 153.78 | 0.00 | 0.00 | 0.00 |
March | 136.12 | 65.10 | 71.02 | 191.35 | 130.93 | 0.00 | 0.00 | 0.00 |
April | 208.46 | 118.98 | 89.48 | 376.38 | 59.10 | 0.00 | 0.00 | 0.00 |
May | 209.22 | 117.24 | 91.97 | 411.41 | 35.12 | 0.00 | 0.00 | 0.00 |
June | 221.79 | 130.41 | 91.37 | 510.32 | 8.88 | 0.00 | 0.00 | 0.00 |
July | 161.33 | 75.18 | 86.15 | 402.43 | 5.64 | 0.00 | 0.00 | 0.00 |
August | 154.44 | 77.66 | 76.78 | 375.79 | 6.40 | 0.00 | 0.00 | 0.00 |
September | 134.39 | 56.51 | 77.89 | 309.82 | 11.41 | 0.00 | 0.00 | 0.00 |
October | 138.07 | 79.18 | 58.89 | 239.99 | 83.74 | 0.00 | 0.00 | 0.00 |
November | 126.39 | 76.26 | 50.13 | 182.53 | 141.42 | 0.00 | 0.00 | 0.00 |
December | 101.41 | 57.49 | 43.91 | 131.52 | 199.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 151.96 | 82.04 | 69.93 | 287.25 | 82.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.41 | 49.92 | 43.91 | 120.98 | 5.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 221.79 | 130.41 | 91.97 | 510.32 | 199.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.04 | 0.00 | 20.04 | 18.41 | 85.42 | 0.00 | 0.00 | 0.00 |
February | 22.83 | 0.00 | 22.83 | 12.58 | 82.34 | 0.00 | 0.00 | 0.00 |
March | 30.35 | 0.00 | 30.35 | 32.00 | 72.76 | 0.00 | 0.00 | 0.00 |
April | 37.17 | 0.55 | 36.63 | 71.19 | 31.52 | 0.00 | 0.00 | 0.00 |
May | 43.60 | 3.70 | 39.90 | 99.50 | 16.97 | 0.00 | 0.00 | 0.00 |
June | 50.36 | 9.20 | 41.15 | 156.56 | 4.32 | 0.00 | 0.00 | 0.00 |
July | 43.08 | 4.63 | 38.45 | 141.25 | 2.78 | 0.00 | 0.00 | 0.00 |
August | 34.66 | 0.85 | 33.81 | 115.96 | 3.60 | 0.00 | 0.00 | 0.00 |
September | 32.69 | 0.02 | 32.67 | 96.01 | 6.52 | 0.00 | 0.00 | 0.00 |
October | 25.27 | 0.00 | 25.27 | 45.17 | 46.18 | 0.00 | 0.00 | 0.00 |
November | 21.06 | 0.00 | 21.06 | 18.81 | 76.20 | 0.00 | 0.00 | 0.00 |
December | 18.72 | 0.00 | 18.72 | 11.37 | 105.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 31.68 | 1.58 | 30.10 | 68.50 | 44.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.72 | 0.00 | 18.72 | 11.37 | 2.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 50.36 | 9.20 | 41.15 | 156.56 | 105.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 127.00 | 79.12 | 47.88 | 192.47 | 157.97 | 0.00 | 0.00 | 0.00 |
February | 102.87 | 49.92 | 52.94 | 125.50 | 150.27 | 0.00 | 0.00 | 0.00 |
March | 136.12 | 65.10 | 71.02 | 193.67 | 131.80 | 0.00 | 0.00 | 0.00 |
April | 208.46 | 118.98 | 89.48 | 376.73 | 60.62 | 0.00 | 0.00 | 0.00 |
May | 209.22 | 117.24 | 91.97 | 409.77 | 35.75 | 0.00 | 0.00 | 0.00 |
June | 221.79 | 130.41 | 91.37 | 508.04 | 9.30 | 0.00 | 0.00 | 0.00 |
July | 161.33 | 75.18 | 86.15 | 401.82 | 5.81 | 0.00 | 0.00 | 0.00 |
August | 154.44 | 77.66 | 76.78 | 375.91 | 7.07 | 0.00 | 0.00 | 0.00 |
September | 134.39 | 56.51 | 77.89 | 310.48 | 12.17 | 0.00 | 0.00 | 0.00 |
October | 138.07 | 79.18 | 58.89 | 243.30 | 84.73 | 0.00 | 0.00 | 0.00 |
November | 126.39 | 76.26 | 50.13 | 187.44 | 140.00 | 0.00 | 0.00 | 0.00 |
December | 101.41 | 57.49 | 43.91 | 138.72 | 193.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 151.96 | 82.04 | 69.93 | 289.37 | 82.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.41 | 49.92 | 43.91 | 125.50 | 5.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 221.79 | 130.41 | 91.97 | 508.04 | 193.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 132.16 | 105.58 | 26.58 | 190.37 | 91.70 | 0.00 | 0.00 | 0.00 |
February | 82.47 | 55.29 | 27.18 | 102.19 | 93.51 | 0.00 | 0.00 | 0.00 |
March | 68.27 | 34.59 | 33.67 | 88.94 | 83.70 | 0.00 | 0.00 | 0.00 |
April | 59.92 | 24.68 | 35.24 | 105.32 | 47.16 | 0.00 | 0.00 | 0.00 |
May | 40.04 | 6.96 | 33.07 | 77.09 | 33.04 | 0.00 | 0.00 | 0.00 |
June | 33.89 | 2.59 | 31.30 | 90.10 | 13.88 | 0.00 | 0.00 | 0.00 |
July | 34.34 | 3.26 | 31.07 | 86.69 | 11.02 | 0.00 | 0.00 | 0.00 |
August | 42.46 | 11.96 | 30.50 | 101.73 | 14.80 | 0.00 | 0.00 | 0.00 |
September | 60.32 | 25.49 | 34.82 | 121.76 | 20.31 | 0.00 | 0.00 | 0.00 |
October | 96.82 | 67.02 | 29.79 | 153.39 | 57.42 | 0.00 | 0.00 | 0.00 |
November | 113.80 | 87.41 | 26.40 | 160.47 | 84.38 | 0.00 | 0.00 | 0.00 |
December | 123.08 | 97.51 | 25.57 | 168.56 | 108.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 73.97 | 43.53 | 30.44 | 120.71 | 54.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 33.89 | 2.59 | 25.57 | 77.09 | 11.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 132.16 | 105.58 | 35.24 | 190.37 | 108.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.03 | 0.00 | 16.03 | 16.10 | 67.57 | 0.00 | 0.00 | 0.00 |
February | 18.27 | 0.00 | 18.27 | 10.47 | 67.20 | 0.00 | 0.00 | 0.00 |
March | 24.29 | 0.00 | 24.28 | 27.11 | 57.78 | 0.00 | 0.00 | 0.00 |
April | 29.74 | 0.44 | 29.30 | 62.17 | 23.14 | 0.00 | 0.00 | 0.00 |
May | 34.89 | 2.96 | 31.92 | 85.69 | 12.06 | 0.00 | 0.00 | 0.00 |
June | 40.29 | 7.36 | 32.93 | 133.65 | 2.58 | 0.00 | 0.00 | 0.00 |
July | 34.47 | 3.70 | 30.76 | 120.36 | 1.78 | 0.00 | 0.00 | 0.00 |
August | 27.73 | 0.68 | 27.05 | 99.78 | 2.23 | 0.00 | 0.00 | 0.00 |
September | 26.15 | 0.02 | 26.14 | 82.57 | 4.14 | 0.00 | 0.00 | 0.00 |
October | 20.22 | 0.00 | 20.22 | 39.46 | 35.35 | 0.00 | 0.00 | 0.00 |
November | 16.85 | 0.00 | 16.85 | 16.53 | 59.97 | 0.00 | 0.00 | 0.00 |
December | 14.98 | 0.00 | 14.98 | 9.44 | 85.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 25.35 | 1.27 | 24.08 | 58.84 | 34.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.98 | 0.00 | 14.98 | 9.44 | 1.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 40.29 | 7.36 | 32.93 | 133.65 | 85.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 120.94 | 75.91 | 45.03 | 158.58 | 145.02 | 0.00 | 0.00 | 0.00 |
February | 120.23 | 69.17 | 51.05 | 139.14 | 143.48 | 0.00 | 0.00 | 0.00 |
March | 149.29 | 76.81 | 72.48 | 202.10 | 120.99 | 0.00 | 0.00 | 0.00 |
April | 212.74 | 126.76 | 85.99 | 379.30 | 52.66 | 0.00 | 0.00 | 0.00 |
May | 220.85 | 131.04 | 89.80 | 429.29 | 30.64 | 0.00 | 0.00 | 0.00 |
June | 229.78 | 142.76 | 87.03 | 528.33 | 7.73 | 0.00 | 0.00 | 0.00 |
July | 194.36 | 109.67 | 84.69 | 461.92 | 5.03 | 0.00 | 0.00 | 0.00 |
August | 184.63 | 105.48 | 79.14 | 428.00 | 6.13 | 0.00 | 0.00 | 0.00 |
September | 151.29 | 72.97 | 78.32 | 337.91 | 10.64 | 0.00 | 0.00 | 0.00 |
October | 151.83 | 92.35 | 59.47 | 256.42 | 76.77 | 0.00 | 0.00 | 0.00 |
November | 116.83 | 70.11 | 46.72 | 152.75 | 129.43 | 0.00 | 0.00 | 0.00 |
December | 106.72 | 64.54 | 42.18 | 121.98 | 182.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 163.49 | 94.92 | 68.57 | 300.41 | 75.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 106.72 | 64.54 | 42.18 | 121.98 | 5.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 229.78 | 142.76 | 89.80 | 528.33 | 182.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 165.24 | 132.00 | 33.23 | 258.05 | 77.12 | 0.00 | 0.00 | 0.00 |
February | 103.10 | 69.12 | 33.98 | 143.51 | 75.84 | 0.00 | 0.00 | 0.00 |
March | 85.35 | 43.25 | 42.10 | 129.22 | 68.42 | 0.00 | 0.00 | 0.00 |
April | 74.91 | 30.86 | 44.05 | 151.52 | 31.67 | 0.00 | 0.00 | 0.00 |
May | 50.05 | 8.71 | 41.35 | 118.76 | 18.78 | 0.00 | 0.00 | 0.00 |
June | 42.37 | 3.23 | 39.14 | 143.07 | 4.68 | 0.00 | 0.00 | 0.00 |
July | 42.93 | 4.08 | 38.85 | 142.16 | 3.01 | 0.00 | 0.00 | 0.00 |
August | 53.09 | 14.95 | 38.14 | 157.08 | 3.49 | 0.00 | 0.00 | 0.00 |
September | 75.41 | 31.87 | 43.54 | 179.92 | 6.00 | 0.00 | 0.00 | 0.00 |
October | 121.05 | 83.80 | 37.25 | 212.88 | 41.47 | 0.00 | 0.00 | 0.00 |
November | 142.28 | 109.28 | 33.00 | 219.94 | 68.10 | 0.00 | 0.00 | 0.00 |
December | 153.88 | 121.91 | 31.97 | 229.92 | 95.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 92.48 | 54.42 | 38.06 | 174.09 | 41.04 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 42.37 | 3.23 | 31.97 | 118.76 | 3.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 165.24 | 132.00 | 44.05 | 258.05 | 95.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.04 | 0.00 | 20.04 | 17.46 | 84.29 | 0.00 | 0.00 | 0.00 |
February | 22.83 | 0.00 | 22.83 | 11.56 | 82.76 | 0.00 | 0.00 | 0.00 |
March | 30.35 | 0.00 | 30.35 | 30.35 | 72.44 | 0.00 | 0.00 | 0.00 |
April | 37.17 | 0.55 | 36.63 | 69.40 | 31.42 | 0.00 | 0.00 | 0.00 |
May | 43.60 | 3.70 | 39.90 | 96.96 | 16.74 | 0.00 | 0.00 | 0.00 |
June | 50.36 | 9.20 | 41.15 | 155.45 | 4.16 | 0.00 | 0.00 | 0.00 |
July | 43.08 | 4.63 | 38.45 | 139.76 | 2.72 | 0.00 | 0.00 | 0.00 |
August | 34.66 | 0.85 | 33.81 | 114.53 | 3.60 | 0.00 | 0.00 | 0.00 |
September | 32.69 | 0.02 | 32.67 | 94.80 | 6.56 | 0.00 | 0.00 | 0.00 |
October | 25.27 | 0.00 | 25.27 | 43.64 | 46.16 | 0.00 | 0.00 | 0.00 |
November | 21.06 | 0.00 | 21.06 | 18.06 | 75.05 | 0.00 | 0.00 | 0.00 |
December | 18.72 | 0.00 | 18.72 | 10.64 | 104.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 31.68 | 1.58 | 30.10 | 67.15 | 44.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.72 | 0.00 | 18.72 | 10.64 | 2.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 50.36 | 9.20 | 41.15 | 155.45 | 104.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 120.94 | 75.91 | 45.03 | 165.63 | 141.40 | 0.00 | 0.00 | 0.00 |
February | 120.23 | 69.17 | 51.05 | 143.85 | 139.82 | 0.00 | 0.00 | 0.00 |
March | 149.29 | 76.81 | 72.48 | 204.57 | 121.48 | 0.00 | 0.00 | 0.00 |
April | 212.74 | 126.76 | 85.99 | 377.19 | 53.71 | 0.00 | 0.00 | 0.00 |
May | 220.85 | 131.04 | 89.80 | 423.74 | 30.85 | 0.00 | 0.00 | 0.00 |
June | 229.78 | 142.76 | 87.03 | 524.49 | 7.84 | 0.00 | 0.00 | 0.00 |
July | 194.36 | 109.67 | 84.69 | 460.66 | 5.07 | 0.00 | 0.00 | 0.00 |
August | 184.63 | 105.48 | 79.14 | 427.13 | 6.68 | 0.00 | 0.00 | 0.00 |
September | 151.29 | 72.97 | 78.32 | 337.00 | 11.19 | 0.00 | 0.00 | 0.00 |
October | 151.83 | 92.35 | 59.47 | 258.47 | 77.56 | 0.00 | 0.00 | 0.00 |
November | 116.83 | 70.11 | 46.72 | 157.54 | 126.98 | 0.00 | 0.00 | 0.00 |
December | 106.72 | 64.54 | 42.18 | 128.98 | 175.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 163.49 | 94.92 | 68.57 | 301.53 | 74.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 106.72 | 64.54 | 42.18 | 128.98 | 5.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 229.78 | 142.76 | 89.80 | 524.49 | 175.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 25.38 | 0.00 | 25.38 | 21.44 | 118.42 | 0.00 | 0.00 | 0.00 |
February | 28.92 | 0.00 | 28.92 | 15.23 | 113.55 | 0.00 | 0.00 | 0.00 |
March | 38.44 | 0.00 | 38.44 | 41.03 | 97.99 | 0.00 | 0.00 | 0.00 |
April | 47.08 | 0.69 | 46.38 | 90.70 | 47.08 | 0.00 | 0.00 | 0.00 |
May | 55.22 | 4.69 | 50.53 | 124.15 | 28.57 | 0.00 | 0.00 | 0.00 |
June | 63.77 | 11.65 | 52.12 | 191.83 | 9.22 | 0.00 | 0.00 | 0.00 |
July | 54.55 | 5.86 | 48.69 | 167.95 | 6.29 | 0.00 | 0.00 | 0.00 |
August | 43.90 | 1.08 | 42.82 | 137.71 | 8.55 | 0.00 | 0.00 | 0.00 |
September | 41.39 | 0.03 | 41.37 | 113.96 | 14.61 | 0.00 | 0.00 | 0.00 |
October | 32.01 | 0.00 | 32.01 | 53.99 | 68.15 | 0.00 | 0.00 | 0.00 |
November | 26.67 | 0.00 | 26.67 | 22.49 | 106.64 | 0.00 | 0.00 | 0.00 |
December | 23.71 | 0.00 | 23.71 | 12.53 | 144.76 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.13 | 2.00 | 38.12 | 83.06 | 63.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 23.71 | 0.00 | 23.71 | 12.53 | 6.29 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.77 | 11.65 | 52.12 | 191.83 | 144.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 9.36 | 0.00 | 9.36 | 7.91 | 43.65 | 0.00 | 0.00 | 0.00 |
February | 10.66 | 0.00 | 10.66 | 5.61 | 41.86 | 0.00 | 0.00 | 0.00 |
March | 14.17 | 0.00 | 14.17 | 15.13 | 36.12 | 0.00 | 0.00 | 0.00 |
April | 17.35 | 0.26 | 17.10 | 33.43 | 17.36 | 0.00 | 0.00 | 0.00 |
May | 20.36 | 1.73 | 18.63 | 45.77 | 10.53 | 0.00 | 0.00 | 0.00 |
June | 23.51 | 4.30 | 19.21 | 70.72 | 3.40 | 0.00 | 0.00 | 0.00 |
July | 20.11 | 2.16 | 17.95 | 61.91 | 2.32 | 0.00 | 0.00 | 0.00 |
August | 16.18 | 0.40 | 15.78 | 50.77 | 3.15 | 0.00 | 0.00 | 0.00 |
September | 15.26 | 0.01 | 15.25 | 42.01 | 5.39 | 0.00 | 0.00 | 0.00 |
October | 11.80 | 0.00 | 11.80 | 19.90 | 25.12 | 0.00 | 0.00 | 0.00 |
November | 9.83 | 0.00 | 9.83 | 8.29 | 39.31 | 0.00 | 0.00 | 0.00 |
December | 8.74 | 0.00 | 8.74 | 4.62 | 53.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 14.79 | 0.74 | 14.05 | 30.62 | 23.39 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 8.74 | 0.00 | 8.74 | 4.62 | 2.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 23.51 | 4.30 | 19.21 | 70.72 | 53.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.10 | 61.59 | 15.51 | 121.74 | 39.00 | 0.00 | 0.00 | 0.00 |
February | 48.11 | 32.25 | 15.86 | 68.41 | 37.71 | 0.00 | 0.00 | 0.00 |
March | 39.82 | 20.18 | 19.64 | 61.86 | 34.43 | 0.00 | 0.00 | 0.00 |
April | 34.95 | 14.40 | 20.56 | 71.33 | 17.90 | 0.00 | 0.00 | 0.00 |
May | 23.36 | 4.06 | 19.29 | 54.93 | 11.83 | 0.00 | 0.00 | 0.00 |
June | 19.77 | 1.51 | 18.26 | 64.23 | 3.92 | 0.00 | 0.00 | 0.00 |
July | 20.03 | 1.90 | 18.13 | 62.77 | 2.57 | 0.00 | 0.00 | 0.00 |
August | 24.77 | 6.98 | 17.79 | 70.42 | 3.33 | 0.00 | 0.00 | 0.00 |
September | 35.19 | 14.87 | 20.31 | 81.45 | 5.34 | 0.00 | 0.00 | 0.00 |
October | 56.48 | 39.10 | 17.38 | 99.19 | 23.07 | 0.00 | 0.00 | 0.00 |
November | 66.39 | 50.99 | 15.40 | 103.51 | 35.12 | 0.00 | 0.00 | 0.00 |
December | 71.80 | 56.88 | 14.92 | 108.74 | 47.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 43.15 | 25.39 | 17.76 | 80.82 | 21.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 19.77 | 1.51 | 14.92 | 54.93 | 2.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 77.10 | 61.59 | 20.56 | 121.74 | 47.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 209.26 | 167.17 | 42.09 | 330.43 | 105.85 | 0.00 | 0.00 | 0.00 |
February | 130.57 | 87.54 | 43.04 | 185.69 | 102.35 | 0.00 | 0.00 | 0.00 |
March | 108.09 | 54.77 | 53.32 | 167.91 | 93.45 | 0.00 | 0.00 | 0.00 |
April | 94.87 | 39.08 | 55.79 | 193.60 | 48.58 | 0.00 | 0.00 | 0.00 |
May | 63.39 | 11.03 | 52.36 | 149.08 | 32.11 | 0.00 | 0.00 | 0.00 |
June | 53.66 | 4.09 | 49.56 | 174.33 | 10.65 | 0.00 | 0.00 | 0.00 |
July | 54.37 | 5.17 | 49.20 | 170.38 | 6.97 | 0.00 | 0.00 | 0.00 |
August | 67.23 | 18.94 | 48.30 | 191.14 | 9.05 | 0.00 | 0.00 | 0.00 |
September | 95.50 | 40.36 | 55.14 | 221.07 | 14.49 | 0.00 | 0.00 | 0.00 |
October | 153.30 | 106.12 | 47.17 | 269.23 | 62.61 | 0.00 | 0.00 | 0.00 |
November | 180.19 | 138.40 | 41.80 | 280.94 | 95.33 | 0.00 | 0.00 | 0.00 |
December | 194.88 | 154.40 | 40.48 | 295.14 | 127.71 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 117.12 | 68.92 | 48.20 | 219.37 | 58.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 53.66 | 4.09 | 40.48 | 149.08 | 6.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 209.26 | 167.17 | 55.79 | 330.43 | 127.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 165.24 | 132.00 | 33.23 | 257.41 | 76.91 | 0.00 | 0.00 | 0.00 |
February | 103.10 | 69.12 | 33.98 | 144.03 | 74.92 | 0.00 | 0.00 | 0.00 |
March | 85.35 | 43.25 | 42.10 | 129.72 | 68.07 | 0.00 | 0.00 | 0.00 |
April | 74.91 | 30.86 | 44.05 | 151.27 | 30.83 | 0.00 | 0.00 | 0.00 |
May | 50.05 | 8.71 | 41.35 | 119.65 | 18.02 | 0.00 | 0.00 | 0.00 |
June | 42.37 | 3.23 | 39.14 | 144.23 | 4.42 | 0.00 | 0.00 | 0.00 |
July | 42.93 | 4.08 | 38.85 | 143.78 | 2.86 | 0.00 | 0.00 | 0.00 |
August | 53.09 | 14.95 | 38.14 | 158.14 | 3.18 | 0.00 | 0.00 | 0.00 |
September | 75.41 | 31.87 | 43.54 | 180.16 | 5.48 | 0.00 | 0.00 | 0.00 |
October | 121.05 | 83.80 | 37.25 | 212.82 | 40.64 | 0.00 | 0.00 | 0.00 |
November | 142.28 | 109.28 | 33.00 | 219.20 | 67.93 | 0.00 | 0.00 | 0.00 |
December | 153.88 | 121.91 | 31.97 | 230.18 | 94.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 92.48 | 54.42 | 38.06 | 174.47 | 40.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 42.37 | 3.23 | 31.97 | 119.65 | 2.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 165.24 | 132.00 | 44.05 | 257.41 | 94.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 127.00 | 79.12 | 47.88 | 184.21 | 158.02 | 0.00 | 0.00 | 0.00 |
February | 102.87 | 49.92 | 52.94 | 119.39 | 151.27 | 0.00 | 0.00 | 0.00 |
March | 136.12 | 65.10 | 71.02 | 189.27 | 129.32 | 0.00 | 0.00 | 0.00 |
April | 208.46 | 118.98 | 89.48 | 373.24 | 57.29 | 0.00 | 0.00 | 0.00 |
May | 209.22 | 117.24 | 91.97 | 409.27 | 33.48 | 0.00 | 0.00 | 0.00 |
June | 221.79 | 130.41 | 91.37 | 508.54 | 8.13 | 0.00 | 0.00 | 0.00 |
July | 161.33 | 75.18 | 86.15 | 401.57 | 5.30 | 0.00 | 0.00 | 0.00 |
August | 154.44 | 77.66 | 76.78 | 374.92 | 5.91 | 0.00 | 0.00 | 0.00 |
September | 134.39 | 56.51 | 77.89 | 309.05 | 10.47 | 0.00 | 0.00 | 0.00 |
October | 138.07 | 79.18 | 58.89 | 238.61 | 81.22 | 0.00 | 0.00 | 0.00 |
November | 126.39 | 76.26 | 50.13 | 180.86 | 138.90 | 0.00 | 0.00 | 0.00 |
December | 101.41 | 57.49 | 43.91 | 130.49 | 196.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 151.96 | 82.04 | 69.93 | 285.68 | 81.06 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.41 | 49.92 | 43.91 | 119.39 | 5.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 221.79 | 130.41 | 91.97 | 508.54 | 196.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.04 | 0.00 | 20.04 | 18.95 | 83.66 | 0.00 | 0.00 | 0.00 |
February | 22.83 | 0.00 | 22.83 | 12.64 | 80.83 | 0.00 | 0.00 | 0.00 |
March | 30.35 | 0.00 | 30.35 | 31.88 | 72.07 | 0.00 | 0.00 | 0.00 |
April | 37.17 | 0.55 | 36.63 | 71.09 | 30.69 | 0.00 | 0.00 | 0.00 |
May | 43.60 | 3.70 | 39.90 | 99.84 | 16.20 | 0.00 | 0.00 | 0.00 |
June | 50.36 | 9.20 | 41.15 | 156.85 | 3.98 | 0.00 | 0.00 | 0.00 |
July | 43.08 | 4.63 | 38.45 | 141.56 | 2.62 | 0.00 | 0.00 | 0.00 |
August | 34.66 | 0.85 | 33.81 | 116.31 | 3.34 | 0.00 | 0.00 | 0.00 |
September | 32.69 | 0.02 | 32.67 | 96.44 | 5.94 | 0.00 | 0.00 | 0.00 |
October | 25.27 | 0.00 | 25.27 | 45.65 | 44.64 | 0.00 | 0.00 | 0.00 |
November | 21.06 | 0.00 | 21.06 | 19.23 | 74.55 | 0.00 | 0.00 | 0.00 |
December | 18.72 | 0.00 | 18.72 | 11.87 | 103.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 31.68 | 1.58 | 30.10 | 68.79 | 43.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.72 | 0.00 | 18.72 | 11.87 | 2.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 50.36 | 9.20 | 41.15 | 156.85 | 103.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 127.00 | 79.12 | 47.88 | 191.89 | 154.69 | 0.00 | 0.00 | 0.00 |
February | 102.87 | 49.92 | 52.94 | 124.52 | 147.39 | 0.00 | 0.00 | 0.00 |
March | 136.12 | 65.10 | 71.02 | 191.81 | 130.41 | 0.00 | 0.00 | 0.00 |
April | 208.46 | 118.98 | 89.48 | 373.71 | 58.87 | 0.00 | 0.00 | 0.00 |
May | 209.22 | 117.24 | 91.97 | 407.83 | 33.90 | 0.00 | 0.00 | 0.00 |
June | 221.79 | 130.41 | 91.37 | 506.28 | 8.45 | 0.00 | 0.00 | 0.00 |
July | 161.33 | 75.18 | 86.15 | 400.99 | 5.43 | 0.00 | 0.00 | 0.00 |
August | 154.44 | 77.66 | 76.78 | 375.12 | 6.52 | 0.00 | 0.00 | 0.00 |
September | 134.39 | 56.51 | 77.89 | 309.91 | 11.08 | 0.00 | 0.00 | 0.00 |
October | 138.07 | 79.18 | 58.89 | 242.53 | 81.88 | 0.00 | 0.00 | 0.00 |
November | 126.39 | 76.26 | 50.13 | 186.68 | 136.94 | 0.00 | 0.00 | 0.00 |
December | 101.41 | 57.49 | 43.91 | 138.70 | 190.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 151.96 | 82.04 | 69.93 | 288.22 | 80.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.41 | 49.92 | 43.91 | 124.52 | 5.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 221.79 | 130.41 | 91.97 | 506.28 | 190.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 242.33 | 193.60 | 48.74 | 371.88 | 117.02 | 0.00 | 0.00 | 0.00 |
February | 151.21 | 101.37 | 49.84 | 206.54 | 114.81 | 0.00 | 0.00 | 0.00 |
March | 125.18 | 63.43 | 61.75 | 187.64 | 101.44 | 0.00 | 0.00 | 0.00 |
April | 109.86 | 45.26 | 64.61 | 225.30 | 43.84 | 0.00 | 0.00 | 0.00 |
May | 73.41 | 12.77 | 60.64 | 181.73 | 24.86 | 0.00 | 0.00 | 0.00 |
June | 62.14 | 4.74 | 57.40 | 221.19 | 5.44 | 0.00 | 0.00 | 0.00 |
July | 62.97 | 5.99 | 56.98 | 218.00 | 3.75 | 0.00 | 0.00 | 0.00 |
August | 77.86 | 21.93 | 55.93 | 237.84 | 4.21 | 0.00 | 0.00 | 0.00 |
September | 110.60 | 46.74 | 63.85 | 267.27 | 7.61 | 0.00 | 0.00 | 0.00 |
October | 177.53 | 122.90 | 54.63 | 310.37 | 60.60 | 0.00 | 0.00 | 0.00 |
November | 208.67 | 160.27 | 48.40 | 317.10 | 102.90 | 0.00 | 0.00 | 0.00 |
December | 225.68 | 178.80 | 46.88 | 330.52 | 145.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 135.63 | 79.81 | 55.82 | 256.68 | 60.80 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 62.14 | 4.74 | 46.88 | 181.73 | 3.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 242.33 | 193.60 | 64.61 | 371.88 | 145.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 140.27 | 0.00 | 140.27 | 86.86 | 752.68 | 0.00 | 0.00 | 0.00 |
February | 159.84 | 0.00 | 159.84 | 50.61 | 769.41 | 0.00 | 0.00 | 0.00 |
March | 212.46 | 0.01 | 212.45 | 170.76 | 649.66 | 0.00 | 0.00 | 0.00 |
April | 260.20 | 3.83 | 256.37 | 448.90 | 302.31 | 0.00 | 0.00 | 0.00 |
May | 305.21 | 25.92 | 279.29 | 634.99 | 182.09 | 0.00 | 0.00 | 0.00 |
June | 352.47 | 64.40 | 288.07 | 1017.71 | 61.31 | 0.00 | 0.00 | 0.00 |
July | 301.52 | 32.40 | 269.12 | 881.25 | 45.29 | 0.00 | 0.00 | 0.00 |
August | 242.62 | 5.96 | 236.66 | 719.42 | 63.29 | 0.00 | 0.00 | 0.00 |
September | 228.79 | 0.14 | 228.65 | 592.69 | 102.13 | 0.00 | 0.00 | 0.00 |
October | 176.90 | 0.00 | 176.90 | 266.10 | 426.66 | 0.00 | 0.00 | 0.00 |
November | 147.39 | 0.00 | 147.39 | 92.26 | 683.97 | 0.00 | 0.00 | 0.00 |
December | 131.03 | 0.00 | 131.03 | 43.76 | 924.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 221.78 | 11.08 | 210.70 | 418.80 | 412.10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 131.03 | 0.00 | 131.03 | 43.76 | 45.29 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 352.47 | 64.40 | 288.07 | 1017.71 | 924.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 140.27 | 0.00 | 140.27 | 78.40 | 772.42 | 0.00 | 0.00 | 0.00 |
February | 159.84 | 0.00 | 159.84 | 43.75 | 795.10 | 0.00 | 0.00 | 0.00 |
March | 212.46 | 0.01 | 212.45 | 159.69 | 668.03 | 0.00 | 0.00 | 0.00 |
April | 260.20 | 3.83 | 256.37 | 439.21 | 310.88 | 0.00 | 0.00 | 0.00 |
May | 305.21 | 25.92 | 279.29 | 624.80 | 187.75 | 0.00 | 0.00 | 0.00 |
June | 352.47 | 64.40 | 288.07 | 1006.15 | 64.05 | 0.00 | 0.00 | 0.00 |
July | 301.52 | 32.40 | 269.12 | 869.58 | 47.94 | 0.00 | 0.00 | 0.00 |
August | 242.62 | 5.96 | 236.66 | 708.77 | 67.17 | 0.00 | 0.00 | 0.00 |
September | 228.79 | 0.14 | 228.65 | 583.05 | 107.48 | 0.00 | 0.00 | 0.00 |
October | 176.90 | 0.00 | 176.90 | 257.43 | 438.95 | 0.00 | 0.00 | 0.00 |
November | 147.39 | 0.00 | 147.39 | 84.34 | 703.28 | 0.00 | 0.00 | 0.00 |
December | 131.03 | 0.00 | 131.03 | 37.73 | 950.71 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 221.78 | 11.08 | 210.70 | 409.41 | 424.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 131.03 | 0.00 | 131.03 | 37.73 | 47.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 352.47 | 64.40 | 288.07 | 1006.15 | 950.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.04 | 0.00 | 20.04 | 15.82 | 107.21 | 0.00 | 0.00 | 0.00 |
February | 22.83 | 0.00 | 22.83 | 9.17 | 110.09 | 0.00 | 0.00 | 0.00 |
March | 30.35 | 0.00 | 30.35 | 28.62 | 94.63 | 0.00 | 0.00 | 0.00 |
April | 37.17 | 0.55 | 36.63 | 72.51 | 46.41 | 0.00 | 0.00 | 0.00 |
May | 43.60 | 3.70 | 39.90 | 101.07 | 30.35 | 0.00 | 0.00 | 0.00 |
June | 50.36 | 9.20 | 41.15 | 155.67 | 12.23 | 0.00 | 0.00 | 0.00 |
July | 43.08 | 4.63 | 38.45 | 135.73 | 9.56 | 0.00 | 0.00 | 0.00 |
August | 34.66 | 0.85 | 33.81 | 113.42 | 12.66 | 0.00 | 0.00 | 0.00 |
September | 32.69 | 0.02 | 32.67 | 94.88 | 18.27 | 0.00 | 0.00 | 0.00 |
October | 25.27 | 0.00 | 25.27 | 44.18 | 63.24 | 0.00 | 0.00 | 0.00 |
November | 21.06 | 0.00 | 21.06 | 16.58 | 97.76 | 0.00 | 0.00 | 0.00 |
December | 18.72 | 0.00 | 18.72 | 8.73 | 129.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 31.68 | 1.58 | 30.10 | 66.63 | 60.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.72 | 0.00 | 18.72 | 8.73 | 9.56 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 50.36 | 9.20 | 41.15 | 155.67 | 129.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 241.87 | 151.81 | 90.06 | 318.46 | 362.15 | 0.00 | 0.00 | 0.00 |
February | 240.43 | 138.34 | 102.10 | 273.49 | 376.29 | 0.00 | 0.00 | 0.00 |
March | 298.56 | 153.60 | 144.96 | 396.82 | 321.27 | 0.00 | 0.00 | 0.00 |
April | 425.45 | 253.49 | 171.96 | 765.32 | 162.97 | 0.00 | 0.00 | 0.00 |
May | 441.66 | 262.07 | 179.60 | 861.59 | 112.16 | 0.00 | 0.00 | 0.00 |
June | 459.53 | 285.49 | 174.04 | 1047.38 | 45.83 | 0.00 | 0.00 | 0.00 |
July | 388.70 | 219.32 | 169.38 | 904.29 | 35.67 | 0.00 | 0.00 | 0.00 |
August | 369.23 | 210.95 | 158.27 | 847.59 | 47.41 | 0.00 | 0.00 | 0.00 |
September | 302.56 | 145.93 | 156.63 | 672.35 | 66.76 | 0.00 | 0.00 | 0.00 |
October | 303.63 | 184.69 | 118.94 | 516.62 | 216.49 | 0.00 | 0.00 | 0.00 |
November | 233.65 | 140.21 | 93.44 | 304.50 | 333.60 | 0.00 | 0.00 | 0.00 |
December | 213.43 | 129.08 | 84.35 | 243.54 | 436.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 326.95 | 189.82 | 137.13 | 597.54 | 208.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 213.43 | 129.08 | 84.35 | 243.54 | 35.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 459.53 | 285.49 | 179.60 | 1047.38 | 436.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 165.24 | 132.00 | 33.23 | 259.71 | 96.29 | 0.00 | 0.00 | 0.00 |
February | 103.10 | 69.12 | 33.98 | 142.86 | 98.98 | 0.00 | 0.00 | 0.00 |
March | 85.35 | 43.25 | 42.10 | 128.43 | 90.14 | 0.00 | 0.00 | 0.00 |
April | 74.91 | 30.86 | 44.05 | 153.64 | 47.58 | 0.00 | 0.00 | 0.00 |
May | 50.05 | 8.71 | 41.35 | 120.33 | 33.00 | 0.00 | 0.00 | 0.00 |
June | 42.37 | 3.23 | 39.14 | 141.49 | 13.18 | 0.00 | 0.00 | 0.00 |
July | 42.93 | 4.08 | 38.85 | 137.82 | 10.05 | 0.00 | 0.00 | 0.00 |
August | 53.09 | 14.95 | 38.14 | 155.72 | 12.95 | 0.00 | 0.00 | 0.00 |
September | 75.41 | 31.87 | 43.54 | 179.52 | 18.24 | 0.00 | 0.00 | 0.00 |
October | 121.05 | 83.80 | 37.25 | 214.43 | 58.31 | 0.00 | 0.00 | 0.00 |
November | 142.28 | 109.28 | 33.00 | 220.72 | 87.88 | 0.00 | 0.00 | 0.00 |
December | 153.88 | 121.91 | 31.97 | 231.18 | 114.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 92.48 | 54.42 | 38.06 | 174.07 | 56.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 42.37 | 3.23 | 31.97 | 120.33 | 10.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 165.24 | 132.00 | 44.05 | 259.71 | 114.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 25.38 | 0.00 | 25.38 | 19.15 | 119.10 | 0.00 | 0.00 | 0.00 |
February | 28.92 | 0.00 | 28.92 | 13.00 | 115.59 | 0.00 | 0.00 | 0.00 |
March | 38.44 | 0.00 | 38.44 | 37.73 | 99.65 | 0.00 | 0.00 | 0.00 |
April | 47.08 | 0.69 | 46.38 | 85.13 | 49.12 | 0.00 | 0.00 | 0.00 |
May | 55.22 | 4.69 | 50.53 | 118.47 | 30.17 | 0.00 | 0.00 | 0.00 |
June | 63.77 | 11.65 | 52.12 | 186.51 | 9.94 | 0.00 | 0.00 | 0.00 |
July | 54.55 | 5.86 | 48.69 | 161.75 | 7.08 | 0.00 | 0.00 | 0.00 |
August | 43.90 | 1.08 | 42.82 | 132.04 | 9.76 | 0.00 | 0.00 | 0.00 |
September | 41.39 | 0.03 | 41.37 | 108.98 | 16.17 | 0.00 | 0.00 | 0.00 |
October | 32.01 | 0.00 | 32.01 | 51.08 | 68.25 | 0.00 | 0.00 | 0.00 |
November | 26.67 | 0.00 | 26.67 | 20.26 | 107.12 | 0.00 | 0.00 | 0.00 |
December | 23.71 | 0.00 | 23.71 | 10.82 | 145.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.13 | 2.00 | 38.12 | 79.05 | 64.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 23.71 | 0.00 | 23.71 | 10.82 | 7.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.77 | 11.65 | 52.12 | 186.51 | 145.68 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.71 | 0.00 | 22.71 | 17.13 | 106.55 | 0.00 | 0.00 | 0.00 |
February | 25.87 | 0.00 | 25.87 | 11.63 | 103.42 | 0.00 | 0.00 | 0.00 |
March | 34.39 | 0.00 | 34.39 | 33.76 | 89.16 | 0.00 | 0.00 | 0.00 |
April | 42.12 | 0.62 | 41.50 | 76.17 | 43.95 | 0.00 | 0.00 | 0.00 |
May | 49.41 | 4.20 | 45.21 | 106.00 | 27.00 | 0.00 | 0.00 | 0.00 |
June | 57.06 | 10.43 | 46.63 | 166.88 | 8.90 | 0.00 | 0.00 | 0.00 |
July | 48.81 | 5.24 | 43.56 | 144.72 | 6.33 | 0.00 | 0.00 | 0.00 |
August | 39.27 | 0.96 | 38.31 | 118.13 | 8.73 | 0.00 | 0.00 | 0.00 |
September | 37.04 | 0.02 | 37.01 | 97.51 | 14.46 | 0.00 | 0.00 | 0.00 |
October | 28.64 | 0.00 | 28.64 | 45.70 | 61.06 | 0.00 | 0.00 | 0.00 |
November | 23.86 | 0.00 | 23.86 | 18.12 | 95.84 | 0.00 | 0.00 | 0.00 |
December | 21.21 | 0.00 | 21.21 | 9.68 | 130.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 35.90 | 1.79 | 34.11 | 70.72 | 57.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 21.21 | 0.00 | 21.21 | 9.68 | 6.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 57.06 | 10.43 | 46.63 | 166.88 | 130.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 616.87 | 492.81 | 124.06 | 959.41 | 314.82 | 0.00 | 0.00 | 0.00 |
February | 384.91 | 258.05 | 126.87 | 535.30 | 307.68 | 0.00 | 0.00 | 0.00 |
March | 318.65 | 161.47 | 157.18 | 480.72 | 281.45 | 0.00 | 0.00 | 0.00 |
April | 279.66 | 115.20 | 164.46 | 550.77 | 149.47 | 0.00 | 0.00 | 0.00 |
May | 186.87 | 32.51 | 154.36 | 422.21 | 99.54 | 0.00 | 0.00 | 0.00 |
June | 158.17 | 12.07 | 146.11 | 499.07 | 33.50 | 0.00 | 0.00 | 0.00 |
July | 160.28 | 15.24 | 145.04 | 483.99 | 22.84 | 0.00 | 0.00 | 0.00 |
August | 198.20 | 55.82 | 142.38 | 545.57 | 30.18 | 0.00 | 0.00 | 0.00 |
September | 281.53 | 118.99 | 162.54 | 633.84 | 47.12 | 0.00 | 0.00 | 0.00 |
October | 451.90 | 312.84 | 139.06 | 779.24 | 185.50 | 0.00 | 0.00 | 0.00 |
November | 531.19 | 407.98 | 123.21 | 814.77 | 283.22 | 0.00 | 0.00 | 0.00 |
December | 574.48 | 455.14 | 119.34 | 858.03 | 379.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 345.26 | 203.16 | 142.10 | 631.09 | 177.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 158.17 | 12.07 | 119.34 | 422.21 | 22.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 616.87 | 492.81 | 164.46 | 959.41 | 379.22 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.223838E+10 | 0.178821E+10 | 0.450171E+09 | 0.342734E+10 | 0.114319E+10 |
February | 0.126153E+10 | 0.845731E+09 | 0.415798E+09 | 0.174318E+10 | 0.960649E+09 |
March | 0.115623E+10 | 0.585894E+09 | 0.570335E+09 | 0.174516E+10 | 0.966102E+09 |
April | 0.982044E+09 | 0.404532E+09 | 0.577512E+09 | 0.189070E+10 | 0.535448E+09 |
May | 0.678057E+09 | 0.117952E+09 | 0.560105E+09 | 0.146380E+10 | 0.372544E+09 |
June | 0.555427E+09 | 42376069.35 | 0.513050E+09 | 0.161592E+10 | 0.136249E+09 |
July | 0.581591E+09 | 55297824.35 | 0.526293E+09 | 0.164330E+10 | 93594508.08 |
August | 0.719166E+09 | 0.202544E+09 | 0.516622E+09 | 0.188247E+10 | 0.125360E+09 |
September | 0.988595E+09 | 0.417832E+09 | 0.570763E+09 | 0.215838E+10 | 0.185854E+09 |
October | 0.163976E+10 | 0.113516E+10 | 0.504604E+09 | 0.278909E+10 | 0.685015E+09 |
November | 0.186529E+10 | 0.143263E+10 | 0.432667E+09 | 0.282715E+10 | 0.987347E+09 |
December | 0.208454E+10 | 0.165152E+10 | 0.433026E+09 | 0.305212E+10 | 0.135242E+10 |
Annual Sum or Average | 0.147506E+11 | 0.867966E+10 | 0.607095E+10 | 0.262386E+11 | 0.754378E+10 |
Minimum of Months | 0.555427E+09 | 42376069.35 | 0.415798E+09 | 0.146380E+10 | 93594508.08 |
Maximum of Months | 0.223838E+10 | 0.178821E+10 | 0.577512E+09 | 0.342734E+10 | 0.135242E+10 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.630312E+10 | 0.503547E+10 | 0.126765E+10 | 0.952166E+10 | 0.349725E+10 |
February | 0.355238E+10 | 0.238152E+10 | 0.117086E+10 | 0.478275E+10 | 0.306283E+10 |
March | 0.325586E+10 | 0.164984E+10 | 0.160603E+10 | 0.476498E+10 | 0.305209E+10 |
April | 0.276537E+10 | 0.113914E+10 | 0.162624E+10 | 0.525694E+10 | 0.160772E+10 |
May | 0.190936E+10 | 0.332145E+09 | 0.157722E+10 | 0.407443E+10 | 0.111125E+10 |
June | 0.156404E+10 | 0.119328E+09 | 0.144472E+10 | 0.454467E+10 | 0.391093E+09 |
July | 0.163772E+10 | 0.155715E+09 | 0.148201E+10 | 0.460495E+10 | 0.282419E+09 |
August | 0.202512E+10 | 0.570351E+09 | 0.145477E+10 | 0.526936E+10 | 0.383527E+09 |
September | 0.278382E+10 | 0.117659E+10 | 0.160723E+10 | 0.603106E+10 | 0.562363E+09 |
October | 0.461746E+10 | 0.319653E+10 | 0.142093E+10 | 0.775788E+10 | 0.208610E+10 |
November | 0.525254E+10 | 0.403418E+10 | 0.121836E+10 | 0.783977E+10 | 0.304843E+10 |
December | 0.586993E+10 | 0.465056E+10 | 0.121937E+10 | 0.845063E+10 | 0.416557E+10 |
Annual Sum or Average | 0.415367E+11 | 0.244414E+11 | 0.170954E+11 | 0.728991E+11 | 0.232506E+11 |
Minimum of Months | 0.156404E+10 | 0.119328E+09 | 0.117086E+10 | 0.407443E+10 | 0.282419E+09 |
Maximum of Months | 0.630312E+10 | 0.503547E+10 | 0.162624E+10 | 0.952166E+10 | 0.416557E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.818812E+10 | 0.654136E+10 | 0.164675E+10 | 0.126627E+11 | 0.455988E+10 |
February | 0.461475E+10 | 0.309374E+10 | 0.152101E+10 | 0.637869E+10 | 0.409330E+10 |
March | 0.422955E+10 | 0.214323E+10 | 0.208632E+10 | 0.636051E+10 | 0.406240E+10 |
April | 0.359238E+10 | 0.147980E+10 | 0.211257E+10 | 0.706568E+10 | 0.209562E+10 |
May | 0.248037E+10 | 0.431476E+09 | 0.204890E+10 | 0.549583E+10 | 0.145198E+10 |
June | 0.203178E+10 | 0.155014E+09 | 0.187677E+10 | 0.614612E+10 | 0.502074E+09 |
July | 0.212749E+10 | 0.202283E+09 | 0.192521E+10 | 0.623063E+10 | 0.356302E+09 |
August | 0.263075E+10 | 0.740919E+09 | 0.188983E+10 | 0.710166E+10 | 0.478630E+09 |
September | 0.361634E+10 | 0.152845E+10 | 0.208788E+10 | 0.809140E+10 | 0.704210E+09 |
October | 0.599834E+10 | 0.415247E+10 | 0.184587E+10 | 0.103476E+11 | 0.271254E+10 |
November | 0.682335E+10 | 0.524063E+10 | 0.158272E+10 | 0.104233E+11 | 0.399470E+10 |
December | 0.762538E+10 | 0.604134E+10 | 0.158404E+10 | 0.112354E+11 | 0.548677E+10 |
Annual Sum or Average | 0.539586E+11 | 0.317507E+11 | 0.222079E+11 | 0.975396E+11 | 0.304984E+11 |
Minimum of Months | 0.203178E+10 | 0.155014E+09 | 0.152101E+10 | 0.549583E+10 | 0.356302E+09 |
Maximum of Months | 0.818812E+10 | 0.654136E+10 | 0.211257E+10 | 0.126627E+11 | 0.548677E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.442566E+09 | 0.353559E+09 | 89007348.67 | 0.693712E+09 | 0.208240E+09 |
February | 0.249427E+09 | 0.167216E+09 | 82211105.16 | 0.351056E+09 | 0.183485E+09 |
March | 0.228607E+09 | 0.115841E+09 | 0.112766E+09 | 0.350696E+09 | 0.183743E+09 |
April | 0.194169E+09 | 79982898.78 | 0.114186E+09 | 0.395043E+09 | 82394836.66 |
May | 0.134065E+09 | 23321164.89 | 0.110744E+09 | 0.320695E+09 | 50776602.62 |
June | 0.109819E+09 | 8378476.71 | 0.101441E+09 | 0.372651E+09 | 12693523.88 |
July | 0.114992E+09 | 10933329.61 | 0.104059E+09 | 0.384185E+09 | 8243263.53 |
August | 0.142193E+09 | 40046470.60 | 0.102146E+09 | 0.423520E+09 | 9355743.25 |
September | 0.195463E+09 | 82612529.72 | 0.112851E+09 | 0.468185E+09 | 15665373.29 |
October | 0.324210E+09 | 0.224440E+09 | 99769849.61 | 0.573453E+09 | 0.111833E+09 |
November | 0.368801E+09 | 0.283255E+09 | 85546508.11 | 0.571934E+09 | 0.178390E+09 |
December | 0.412151E+09 | 0.326533E+09 | 85617432.54 | 0.618963E+09 | 0.256793E+09 |
Annual Sum or Average | 0.291646E+10 | 0.171612E+10 | 0.120034E+10 | 0.552409E+10 | 0.130161E+10 |
Minimum of Months | 0.109819E+09 | 8378476.71 | 82211105.16 | 0.320695E+09 | 8243263.53 |
Maximum of Months | 0.442566E+09 | 0.353559E+09 | 0.114186E+09 | 0.693712E+09 | 0.256793E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.340154E+09 | 0.211926E+09 | 0.128229E+09 | 0.497609E+09 | 0.430410E+09 |
February | 0.248858E+09 | 0.120775E+09 | 0.128083E+09 | 0.292679E+09 | 0.372027E+09 |
March | 0.364588E+09 | 0.174372E+09 | 0.190216E+09 | 0.512506E+09 | 0.350688E+09 |
April | 0.540336E+09 | 0.308393E+09 | 0.231943E+09 | 0.975580E+09 | 0.153195E+09 |
May | 0.560366E+09 | 0.314023E+09 | 0.246343E+09 | 0.110192E+10 | 94054451.54 |
June | 0.574867E+09 | 0.338034E+09 | 0.236833E+09 | 0.132275E+10 | 23022035.09 |
July | 0.432114E+09 | 0.201359E+09 | 0.230755E+09 | 0.107787E+10 | 15109807.02 |
August | 0.413642E+09 | 0.208000E+09 | 0.205642E+09 | 0.100651E+10 | 17145620.86 |
September | 0.348351E+09 | 0.146469E+09 | 0.201882E+09 | 0.803044E+09 | 29581584.58 |
October | 0.369811E+09 | 0.212073E+09 | 0.157738E+09 | 0.642792E+09 | 0.224281E+09 |
November | 0.327596E+09 | 0.197665E+09 | 0.129932E+09 | 0.473116E+09 | 0.366567E+09 |
December | 0.271608E+09 | 0.153993E+09 | 0.117616E+09 | 0.352273E+09 | 0.534729E+09 |
Annual Sum or Average | 0.479229E+10 | 0.258708E+10 | 0.220521E+10 | 0.905866E+10 | 0.261081E+10 |
Minimum of Months | 0.248858E+09 | 0.120775E+09 | 0.117616E+09 | 0.292679E+09 | 15109807.02 |
Maximum of Months | 0.574867E+09 | 0.338034E+09 | 0.246343E+09 | 0.132275E+10 | 0.534729E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 53674072.02 | 0.00 | 53674072.02 | 49319010.59 | 0.228789E+09 |
February | 55241433.50 | 0.00 | 55241433.50 | 30441671.26 | 0.199198E+09 |
March | 81295770.76 | 3216.16 | 81292554.60 | 85705304.06 | 0.194883E+09 |
April | 96350800.51 | 1418628.78 | 94932171.74 | 0.184528E+09 | 81710250.09 |
May | 0.116786E+09 | 9916509.70 | 0.106870E+09 | 0.266494E+09 | 45453877.23 |
June | 0.130521E+09 | 23848337.92 | 0.106672E+09 | 0.405816E+09 | 11199648.53 |
July | 0.115375E+09 | 12397170.40 | 0.102978E+09 | 0.378314E+09 | 7442795.41 |
August | 92836668.46 | 2279405.50 | 90557262.96 | 0.310586E+09 | 9643152.78 |
September | 84720382.40 | 52432.38 | 84667950.02 | 0.248850E+09 | 16893652.21 |
October | 67690153.51 | 0.00 | 67690153.51 | 0.120973E+09 | 0.123698E+09 |
November | 54578999.93 | 0.00 | 54578999.93 | 48757240.31 | 0.197514E+09 |
December | 50136496.34 | 0.00 | 50136496.34 | 30456388.78 | 0.281866E+09 |
Annual Sum or Average | 0.999207E+09 | 49915700.83 | 0.949291E+09 | 0.216024E+10 | 0.139829E+10 |
Minimum of Months | 50136496.34 | 0.00 | 50136496.34 | 30441671.26 | 7442795.41 |
Maximum of Months | 0.130521E+09 | 23848337.92 | 0.106870E+09 | 0.405816E+09 | 0.281866E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.340154E+09 | 0.211926E+09 | 0.128229E+09 | 0.515523E+09 | 0.423114E+09 |
February | 0.248858E+09 | 0.120775E+09 | 0.128083E+09 | 0.303620E+09 | 0.363528E+09 |
March | 0.364588E+09 | 0.174372E+09 | 0.190216E+09 | 0.518717E+09 | 0.353024E+09 |
April | 0.540336E+09 | 0.308393E+09 | 0.231943E+09 | 0.976489E+09 | 0.157125E+09 |
May | 0.560366E+09 | 0.314023E+09 | 0.246343E+09 | 0.109753E+10 | 95751256.15 |
June | 0.574867E+09 | 0.338034E+09 | 0.236833E+09 | 0.131684E+10 | 24098572.54 |
July | 0.432114E+09 | 0.201359E+09 | 0.230755E+09 | 0.107623E+10 | 15564361.97 |
August | 0.413642E+09 | 0.208000E+09 | 0.205642E+09 | 0.100684E+10 | 18944196.15 |
September | 0.348351E+09 | 0.146469E+09 | 0.201882E+09 | 0.804753E+09 | 31545879.03 |
October | 0.369811E+09 | 0.212073E+09 | 0.157738E+09 | 0.651658E+09 | 0.226948E+09 |
November | 0.327596E+09 | 0.197665E+09 | 0.129932E+09 | 0.485849E+09 | 0.362870E+09 |
December | 0.271608E+09 | 0.153993E+09 | 0.117616E+09 | 0.371535E+09 | 0.519482E+09 |
Annual Sum or Average | 0.479229E+10 | 0.258708E+10 | 0.220521E+10 | 0.912558E+10 | 0.259200E+10 |
Minimum of Months | 0.248858E+09 | 0.120775E+09 | 0.117616E+09 | 0.303620E+09 | 15564361.97 |
Maximum of Months | 0.574867E+09 | 0.338034E+09 | 0.246343E+09 | 0.131684E+10 | 0.519482E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.353983E+09 | 0.282791E+09 | 71191720.82 | 0.509879E+09 | 0.245600E+09 |
February | 0.199502E+09 | 0.133746E+09 | 65755807.07 | 0.247208E+09 | 0.226224E+09 |
March | 0.182850E+09 | 92654621.17 | 90194909.73 | 0.238221E+09 | 0.224177E+09 |
April | 0.155304E+09 | 63973596.40 | 91330373.15 | 0.272996E+09 | 0.122236E+09 |
May | 0.107231E+09 | 18653222.29 | 88577606.46 | 0.206467E+09 | 88485979.64 |
June | 87837819.98 | 6701448.63 | 81136371.35 | 0.233536E+09 | 35986493.20 |
July | 91975290.32 | 8744924.55 | 83230365.76 | 0.232184E+09 | 29510363.05 |
August | 0.113732E+09 | 32030806.41 | 81700800.92 | 0.272470E+09 | 39644922.76 |
September | 0.156339E+09 | 66076882.86 | 90262586.66 | 0.315593E+09 | 52641222.72 |
October | 0.259316E+09 | 0.179516E+09 | 79800009.62 | 0.410836E+09 | 0.153797E+09 |
November | 0.294982E+09 | 0.226559E+09 | 68423598.87 | 0.415941E+09 | 0.218711E+09 |
December | 0.329655E+09 | 0.261175E+09 | 68480327.14 | 0.451477E+09 | 0.289441E+09 |
Annual Sum or Average | 0.233271E+10 | 0.137262E+10 | 0.960084E+09 | 0.380681E+10 | 0.172646E+10 |
Minimum of Months | 87837819.98 | 6701448.63 | 65755807.07 | 0.206467E+09 | 29510363.05 |
Maximum of Months | 0.353983E+09 | 0.282791E+09 | 91330373.15 | 0.509879E+09 | 0.289441E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 42944949.46 | 0.00 | 42944949.46 | 43126826.28 | 0.180977E+09 |
February | 44199004.85 | 0.00 | 44199004.85 | 25337863.75 | 0.162562E+09 |
March | 65045237.58 | 2573.27 | 65042664.31 | 72602461.42 | 0.154762E+09 |
April | 77090857.89 | 1135053.46 | 75955804.43 | 0.161138E+09 | 59983089.50 |
May | 93441433.49 | 7934259.35 | 85507174.14 | 0.229509E+09 | 32293390.84 |
June | 0.104430E+09 | 19081199.32 | 85349110.47 | 0.346421E+09 | 6680821.10 |
July | 92312481.83 | 9919050.97 | 82393430.86 | 0.322366E+09 | 4755290.91 |
August | 74279179.59 | 1823766.12 | 72455413.47 | 0.267261E+09 | 5966905.64 |
September | 67785290.05 | 41951.47 | 67743338.59 | 0.214018E+09 | 10738945.32 |
October | 54159300.98 | 0.00 | 54159300.98 | 0.105677E+09 | 94682300.52 |
November | 43668987.75 | 0.00 | 43668987.75 | 42842610.63 | 0.155441E+09 |
December | 40114513.77 | 0.00 | 40114513.77 | 25287949.73 | 0.228415E+09 |
Annual Sum or Average | 0.799472E+09 | 39937853.95 | 0.759534E+09 | 0.185559E+10 | 0.109726E+10 |
Minimum of Months | 40114513.77 | 0.00 | 40114513.77 | 25287949.73 | 4755290.91 |
Maximum of Months | 0.104430E+09 | 19081199.32 | 85507174.14 | 0.346421E+09 | 0.228415E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.323939E+09 | 0.203319E+09 | 0.120620E+09 | 0.424750E+09 | 0.388430E+09 |
February | 0.290851E+09 | 0.167343E+09 | 0.123508E+09 | 0.336612E+09 | 0.347096E+09 |
March | 0.399855E+09 | 0.205717E+09 | 0.194139E+09 | 0.541293E+09 | 0.324057E+09 |
April | 0.551427E+09 | 0.328551E+09 | 0.222876E+09 | 0.983140E+09 | 0.136485E+09 |
May | 0.591518E+09 | 0.350985E+09 | 0.240533E+09 | 0.114981E+10 | 82060609.76 |
June | 0.595597E+09 | 0.370022E+09 | 0.225575E+09 | 0.136942E+10 | 20041869.44 |
July | 0.520577E+09 | 0.293732E+09 | 0.226845E+09 | 0.123720E+10 | 13463538.00 |
August | 0.494504E+09 | 0.282527E+09 | 0.211977E+09 | 0.114635E+10 | 16429984.22 |
September | 0.392148E+09 | 0.189135E+09 | 0.203013E+09 | 0.875871E+09 | 27583206.44 |
October | 0.406651E+09 | 0.247359E+09 | 0.159292E+09 | 0.686800E+09 | 0.205623E+09 |
November | 0.302834E+09 | 0.181731E+09 | 0.121103E+09 | 0.395928E+09 | 0.335477E+09 |
December | 0.285842E+09 | 0.172873E+09 | 0.112970E+09 | 0.326701E+09 | 0.488356E+09 |
Annual Sum or Average | 0.515574E+10 | 0.299329E+10 | 0.216245E+10 | 0.947388E+10 | 0.238510E+10 |
Minimum of Months | 0.285842E+09 | 0.167343E+09 | 0.112970E+09 | 0.326701E+09 | 13463538.00 |
Maximum of Months | 0.595597E+09 | 0.370022E+09 | 0.240533E+09 | 0.136942E+10 | 0.488356E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.442566E+09 | 0.353559E+09 | 89007348.67 | 0.691167E+09 | 0.206549E+09 |
February | 0.249427E+09 | 0.167216E+09 | 82211105.16 | 0.347173E+09 | 0.183472E+09 |
March | 0.228607E+09 | 0.115841E+09 | 0.112766E+09 | 0.346105E+09 | 0.183248E+09 |
April | 0.194169E+09 | 79982898.78 | 0.114186E+09 | 0.392746E+09 | 82086731.64 |
May | 0.134065E+09 | 23321164.89 | 0.110744E+09 | 0.318090E+09 | 50288813.95 |
June | 0.109819E+09 | 8378476.71 | 0.101441E+09 | 0.370845E+09 | 12139856.40 |
July | 0.114992E+09 | 10933329.61 | 0.104059E+09 | 0.380768E+09 | 8070843.86 |
August | 0.142193E+09 | 40046470.60 | 0.102146E+09 | 0.420728E+09 | 9342094.73 |
September | 0.195463E+09 | 82612529.72 | 0.112851E+09 | 0.466343E+09 | 15556552.37 |
October | 0.324210E+09 | 0.224440E+09 | 99769849.61 | 0.570169E+09 | 0.111082E+09 |
November | 0.368801E+09 | 0.283255E+09 | 85546508.11 | 0.570089E+09 | 0.176526E+09 |
December | 0.412151E+09 | 0.326533E+09 | 85617432.54 | 0.615825E+09 | 0.255983E+09 |
Annual Sum or Average | 0.291646E+10 | 0.171612E+10 | 0.120034E+10 | 0.549005E+10 | 0.129434E+10 |
Minimum of Months | 0.109819E+09 | 8378476.71 | 82211105.16 | 0.318090E+09 | 8070843.86 |
Maximum of Months | 0.442566E+09 | 0.353559E+09 | 0.114186E+09 | 0.691167E+09 | 0.255983E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 53674072.02 | 0.00 | 53674072.02 | 46772229.57 | 0.225765E+09 |
February | 55241433.50 | 0.00 | 55241433.50 | 27964857.56 | 0.200212E+09 |
March | 81295770.76 | 3216.16 | 81292554.60 | 81301330.56 | 0.194026E+09 |
April | 96350800.51 | 1418628.78 | 94932171.74 | 0.179875E+09 | 81445018.00 |
May | 0.116786E+09 | 9916509.70 | 0.106870E+09 | 0.259702E+09 | 44828756.41 |
June | 0.130521E+09 | 23848337.92 | 0.106672E+09 | 0.402922E+09 | 10784400.09 |
July | 0.115375E+09 | 12397170.40 | 0.102978E+09 | 0.374327E+09 | 7296531.79 |
August | 92836668.46 | 2279405.50 | 90557262.96 | 0.306744E+09 | 9651245.25 |
September | 84720382.40 | 52432.38 | 84667950.02 | 0.245710E+09 | 16993984.91 |
October | 67690153.51 | 0.00 | 67690153.51 | 0.116878E+09 | 0.123640E+09 |
November | 54578999.93 | 0.00 | 54578999.93 | 46823832.92 | 0.194523E+09 |
December | 50136496.34 | 0.00 | 50136496.34 | 28485696.73 | 0.280649E+09 |
Annual Sum or Average | 0.999207E+09 | 49915700.83 | 0.949291E+09 | 0.211751E+10 | 0.138982E+10 |
Minimum of Months | 50136496.34 | 0.00 | 50136496.34 | 27964857.56 | 7296531.79 |
Maximum of Months | 0.130521E+09 | 23848337.92 | 0.106870E+09 | 0.402922E+09 | 0.280649E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.323939E+09 | 0.203319E+09 | 0.120620E+09 | 0.443630E+09 | 0.378724E+09 |
February | 0.290851E+09 | 0.167343E+09 | 0.123508E+09 | 0.348013E+09 | 0.338241E+09 |
March | 0.399855E+09 | 0.205717E+09 | 0.194139E+09 | 0.547918E+09 | 0.325381E+09 |
April | 0.551427E+09 | 0.328551E+09 | 0.222876E+09 | 0.977676E+09 | 0.139226E+09 |
May | 0.591518E+09 | 0.350985E+09 | 0.240533E+09 | 0.113495E+10 | 82626574.16 |
June | 0.595597E+09 | 0.370022E+09 | 0.225575E+09 | 0.135949E+10 | 20309913.43 |
July | 0.520577E+09 | 0.293732E+09 | 0.226845E+09 | 0.123382E+10 | 13568036.57 |
August | 0.494504E+09 | 0.282527E+09 | 0.211977E+09 | 0.114401E+10 | 17878535.56 |
September | 0.392148E+09 | 0.189135E+09 | 0.203013E+09 | 0.873510E+09 | 28998971.75 |
October | 0.406651E+09 | 0.247359E+09 | 0.159292E+09 | 0.692296E+09 | 0.207748E+09 |
November | 0.302834E+09 | 0.181731E+09 | 0.121103E+09 | 0.408345E+09 | 0.329126E+09 |
December | 0.285842E+09 | 0.172873E+09 | 0.112970E+09 | 0.345466E+09 | 0.469747E+09 |
Annual Sum or Average | 0.515574E+10 | 0.299329E+10 | 0.216245E+10 | 0.950913E+10 | 0.235157E+10 |
Minimum of Months | 0.285842E+09 | 0.167343E+09 | 0.112970E+09 | 0.345466E+09 | 13568036.57 |
Maximum of Months | 0.595597E+09 | 0.370022E+09 | 0.240533E+09 | 0.135949E+10 | 0.469747E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 67974825.56 | 0.00 | 67974825.56 | 57435208.57 | 0.317166E+09 |
February | 69959789.98 | 0.00 | 69959789.98 | 36841383.60 | 0.274708E+09 |
March | 0.102956E+09 | 4073.06 | 0.102952E+09 | 0.109900E+09 | 0.262469E+09 |
April | 0.122022E+09 | 1796603.83 | 0.120226E+09 | 0.235084E+09 | 0.122041E+09 |
May | 0.147902E+09 | 12558633.84 | 0.135344E+09 | 0.332514E+09 | 76529621.71 |
June | 0.165296E+09 | 30202415.22 | 0.135094E+09 | 0.497217E+09 | 23895318.90 |
July | 0.146116E+09 | 15700234.09 | 0.130415E+09 | 0.449834E+09 | 16859490.58 |
August | 0.117572E+09 | 2886723.24 | 0.114685E+09 | 0.368847E+09 | 22902295.71 |
September | 0.107293E+09 | 66402.30 | 0.107227E+09 | 0.295395E+09 | 37876994.10 |
October | 85725308.41 | 0.00 | 85725308.41 | 0.144597E+09 | 0.182541E+09 |
November | 69120859.66 | 0.00 | 69120859.66 | 58302171.64 | 0.276409E+09 |
December | 63494709.17 | 0.00 | 63494709.17 | 33554485.37 | 0.387724E+09 |
Annual Sum or Average | 0.126543E+10 | 63215085.59 | 0.120222E+10 | 0.261952E+10 | 0.200112E+10 |
Minimum of Months | 63494709.17 | 0.00 | 63494709.17 | 33554485.37 | 16859490.58 |
Maximum of Months | 0.165296E+09 | 30202415.22 | 0.135344E+09 | 0.497217E+09 | 0.387724E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 25058335.32 | 0.00 | 25058335.32 | 21172996.08 | 0.116920E+09 |
February | 25790075.39 | 0.00 | 25790075.39 | 13581259.48 | 0.101269E+09 |
March | 37953831.47 | 1501.50 | 37952329.97 | 40513723.42 | 96756841.75 |
April | 44982438.94 | 662302.56 | 44320136.38 | 86661532.74 | 44989271.64 |
May | 54522983.56 | 4629632.44 | 49893351.11 | 0.122578E+09 | 28211987.40 |
June | 60934981.96 | 11133860.83 | 49801121.12 | 0.183295E+09 | 8808803.97 |
July | 53864241.38 | 5787756.38 | 48076485.00 | 0.165828E+09 | 6215106.32 |
August | 43341827.45 | 1064165.72 | 42277661.74 | 0.135972E+09 | 8442734.51 |
September | 39552649.37 | 24478.64 | 39528170.73 | 0.108895E+09 | 13963028.39 |
October | 31601898.29 | 0.00 | 31601898.29 | 53304415.99 | 67292172.56 |
November | 25480810.94 | 0.00 | 25480810.94 | 21492594.57 | 0.101896E+09 |
December | 23406778.91 | 0.00 | 23406778.91 | 12369572.69 | 0.142931E+09 |
Annual Sum or Average | 0.466491E+09 | 23303698.08 | 0.443187E+09 | 0.965664E+09 | 0.737696E+09 |
Minimum of Months | 23406778.91 | 0.00 | 23406778.91 | 12369572.69 | 6215106.32 |
Maximum of Months | 60934981.96 | 11133860.83 | 49893351.11 | 0.183295E+09 | 0.142931E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206500E+09 | 0.164969E+09 | 41530470.22 | 0.326075E+09 | 0.104454E+09 |
February | 0.116382E+09 | 78022138.43 | 38359370.38 | 0.165505E+09 | 91229320.74 |
March | 0.106667E+09 | 54051088.25 | 52616188.64 | 0.165698E+09 | 92215969.36 |
April | 90598271.93 | 37319698.27 | 53278573.67 | 0.184884E+09 | 46395855.98 |
May | 62554278.62 | 10881561.56 | 51672717.06 | 0.147116E+09 | 31691291.84 |
June | 51241154.51 | 3909363.47 | 47331791.04 | 0.166477E+09 | 10170068.33 |
July | 53654793.16 | 5101447.54 | 48553345.62 | 0.168128E+09 | 6880189.16 |
August | 66346579.02 | 18685521.81 | 47661057.22 | 0.188617E+09 | 8928085.77 |
September | 91202342.18 | 38546673.46 | 52655668.72 | 0.211118E+09 | 13838508.23 |
October | 0.151275E+09 | 0.104723E+09 | 46552209.79 | 0.265683E+09 | 61781122.65 |
November | 0.172081E+09 | 0.132165E+09 | 39915655.96 | 0.268295E+09 | 91038665.01 |
December | 0.192308E+09 | 0.152359E+09 | 39948749.01 | 0.291250E+09 | 0.126026E+09 |
Annual Sum or Average | 0.136081E+10 | 0.800734E+09 | 0.560076E+09 | 0.254885E+10 | 0.684649E+09 |
Minimum of Months | 51241154.51 | 3909363.47 | 38359370.38 | 0.147116E+09 | 6880189.16 |
Maximum of Months | 0.206500E+09 | 0.164969E+09 | 53278573.67 | 0.326075E+09 | 0.126026E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.560483E+09 | 0.447760E+09 | 0.112722E+09 | 0.885033E+09 | 0.283511E+09 |
February | 0.315883E+09 | 0.211768E+09 | 0.104115E+09 | 0.449214E+09 | 0.247615E+09 |
March | 0.289517E+09 | 0.146706E+09 | 0.142811E+09 | 0.449739E+09 | 0.250293E+09 |
April | 0.245902E+09 | 0.101293E+09 | 0.144609E+09 | 0.501812E+09 | 0.125928E+09 |
May | 0.169785E+09 | 29534783.85 | 0.140250E+09 | 0.399304E+09 | 86016648.36 |
June | 0.139079E+09 | 10610812.10 | 0.128468E+09 | 0.451852E+09 | 27603645.70 |
July | 0.145630E+09 | 13846372.09 | 0.131784E+09 | 0.456335E+09 | 18674240.71 |
August | 0.180078E+09 | 50716328.22 | 0.129362E+09 | 0.511945E+09 | 24232650.97 |
September | 0.247542E+09 | 0.104624E+09 | 0.142918E+09 | 0.573017E+09 | 37560541.95 |
October | 0.410591E+09 | 0.284239E+09 | 0.126352E+09 | 0.721118E+09 | 0.167687E+09 |
November | 0.467063E+09 | 0.358724E+09 | 0.108339E+09 | 0.728208E+09 | 0.247098E+09 |
December | 0.521963E+09 | 0.413534E+09 | 0.108429E+09 | 0.790511E+09 | 0.342059E+09 |
Annual Sum or Average | 0.369352E+10 | 0.217336E+10 | 0.152016E+10 | 0.691809E+10 | 0.185828E+10 |
Minimum of Months | 0.139079E+09 | 10610812.10 | 0.104115E+09 | 0.399304E+09 | 18674240.71 |
Maximum of Months | 0.560483E+09 | 0.447760E+09 | 0.144609E+09 | 0.885033E+09 | 0.342059E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.442566E+09 | 0.353559E+09 | 89007348.67 | 0.689451E+09 | 0.205998E+09 |
February | 0.249427E+09 | 0.167216E+09 | 82211105.16 | 0.348426E+09 | 0.181236E+09 |
March | 0.228607E+09 | 0.115841E+09 | 0.112766E+09 | 0.347429E+09 | 0.182313E+09 |
April | 0.194169E+09 | 79982898.78 | 0.114186E+09 | 0.392094E+09 | 79918796.10 |
May | 0.134065E+09 | 23321164.89 | 0.110744E+09 | 0.320470E+09 | 48272993.49 |
June | 0.109819E+09 | 8378476.71 | 0.101441E+09 | 0.373847E+09 | 11445987.88 |
July | 0.114992E+09 | 10933329.61 | 0.104059E+09 | 0.385112E+09 | 7669003.76 |
August | 0.142193E+09 | 40046470.60 | 0.102146E+09 | 0.423562E+09 | 8523432.81 |
September | 0.195463E+09 | 82612529.72 | 0.112851E+09 | 0.466962E+09 | 14204760.07 |
October | 0.324210E+09 | 0.224440E+09 | 99769849.61 | 0.570020E+09 | 0.108862E+09 |
November | 0.368801E+09 | 0.283255E+09 | 85546508.11 | 0.568158E+09 | 0.176083E+09 |
December | 0.412151E+09 | 0.326533E+09 | 85617432.54 | 0.616501E+09 | 0.254409E+09 |
Annual Sum or Average | 0.291646E+10 | 0.171612E+10 | 0.120034E+10 | 0.550203E+10 | 0.127893E+10 |
Minimum of Months | 0.109819E+09 | 8378476.71 | 82211105.16 | 0.320470E+09 | 7669003.76 |
Maximum of Months | 0.442566E+09 | 0.353559E+09 | 0.114186E+09 | 0.689451E+09 | 0.254409E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.340154E+09 | 0.211926E+09 | 0.128229E+09 | 0.493390E+09 | 0.423249E+09 |
February | 0.248858E+09 | 0.120775E+09 | 0.128083E+09 | 0.288821E+09 | 0.365964E+09 |
March | 0.364588E+09 | 0.174372E+09 | 0.190216E+09 | 0.506954E+09 | 0.346374E+09 |
April | 0.540336E+09 | 0.308393E+09 | 0.231943E+09 | 0.967436E+09 | 0.148503E+09 |
May | 0.560366E+09 | 0.314023E+09 | 0.246343E+09 | 0.109620E+10 | 89669876.48 |
June | 0.574867E+09 | 0.338034E+09 | 0.236833E+09 | 0.131814E+10 | 21069470.05 |
July | 0.432114E+09 | 0.201359E+09 | 0.230755E+09 | 0.107556E+10 | 14186944.51 |
August | 0.413642E+09 | 0.208000E+09 | 0.205642E+09 | 0.100418E+10 | 15825856.77 |
September | 0.348351E+09 | 0.146469E+09 | 0.201882E+09 | 0.801060E+09 | 27147558.39 |
October | 0.369811E+09 | 0.212073E+09 | 0.157738E+09 | 0.639098E+09 | 0.217552E+09 |
November | 0.327596E+09 | 0.197665E+09 | 0.129932E+09 | 0.468788E+09 | 0.360041E+09 |
December | 0.271608E+09 | 0.153993E+09 | 0.117616E+09 | 0.349503E+09 | 0.526743E+09 |
Annual Sum or Average | 0.479229E+10 | 0.258708E+10 | 0.220521E+10 | 0.900913E+10 | 0.255633E+10 |
Minimum of Months | 0.248858E+09 | 0.120775E+09 | 0.117616E+09 | 0.288821E+09 | 14186944.51 |
Maximum of Months | 0.574867E+09 | 0.338034E+09 | 0.246343E+09 | 0.131814E+10 | 0.526743E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 53674072.02 | 0.00 | 53674072.02 | 50752115.23 | 0.224068E+09 |
February | 55241433.50 | 0.00 | 55241433.50 | 30569933.01 | 0.195539E+09 |
March | 81295770.76 | 3216.16 | 81292554.60 | 85380513.43 | 0.193030E+09 |
April | 96350800.51 | 1418628.78 | 94932171.74 | 0.184257E+09 | 79545351.23 |
May | 0.116786E+09 | 9916509.70 | 0.106870E+09 | 0.267402E+09 | 43394393.16 |
June | 0.130521E+09 | 23848337.92 | 0.106672E+09 | 0.406557E+09 | 10311574.80 |
July | 0.115375E+09 | 12397170.40 | 0.102978E+09 | 0.379164E+09 | 7004426.91 |
August | 92836668.46 | 2279405.50 | 90557262.96 | 0.311517E+09 | 8950520.09 |
September | 84720382.40 | 52432.38 | 84667950.02 | 0.249982E+09 | 15405503.67 |
October | 67690153.51 | 0.00 | 67690153.51 | 0.122259E+09 | 0.119552E+09 |
November | 54578999.93 | 0.00 | 54578999.93 | 49848425.96 | 0.193228E+09 |
December | 50136496.34 | 0.00 | 50136496.34 | 31781389.18 | 0.276535E+09 |
Annual Sum or Average | 0.999207E+09 | 49915700.83 | 0.949291E+09 | 0.216947E+10 | 0.136656E+10 |
Minimum of Months | 50136496.34 | 0.00 | 50136496.34 | 30569933.01 | 7004426.91 |
Maximum of Months | 0.130521E+09 | 23848337.92 | 0.106870E+09 | 0.406557E+09 | 0.276535E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.340154E+09 | 0.211926E+09 | 0.128229E+09 | 0.513952E+09 | 0.414325E+09 |
February | 0.248858E+09 | 0.120775E+09 | 0.128083E+09 | 0.301227E+09 | 0.356563E+09 |
March | 0.364588E+09 | 0.174372E+09 | 0.190216E+09 | 0.513737E+09 | 0.349297E+09 |
April | 0.540336E+09 | 0.308393E+09 | 0.231943E+09 | 0.968656E+09 | 0.152604E+09 |
May | 0.560366E+09 | 0.314023E+09 | 0.246343E+09 | 0.109233E+10 | 90800737.68 |
June | 0.574867E+09 | 0.338034E+09 | 0.236833E+09 | 0.131226E+10 | 21889550.12 |
July | 0.432114E+09 | 0.201359E+09 | 0.230755E+09 | 0.107401E+10 | 14533041.33 |
August | 0.413642E+09 | 0.208000E+09 | 0.205642E+09 | 0.100473E+10 | 17451123.10 |
September | 0.348351E+09 | 0.146469E+09 | 0.201882E+09 | 0.803282E+09 | 28708379.91 |
October | 0.369811E+09 | 0.212073E+09 | 0.157738E+09 | 0.649596E+09 | 0.219317E+09 |
November | 0.327596E+09 | 0.197665E+09 | 0.129932E+09 | 0.483880E+09 | 0.354946E+09 |
December | 0.271608E+09 | 0.153993E+09 | 0.117616E+09 | 0.371504E+09 | 0.509922E+09 |
Annual Sum or Average | 0.479229E+10 | 0.258708E+10 | 0.220521E+10 | 0.908918E+10 | 0.253036E+10 |
Minimum of Months | 0.248858E+09 | 0.120775E+09 | 0.117616E+09 | 0.301227E+09 | 14533041.33 |
Maximum of Months | 0.574867E+09 | 0.338034E+09 | 0.246343E+09 | 0.131226E+10 | 0.509922E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.649066E+09 | 0.518528E+09 | 0.130538E+09 | 0.996054E+09 | 0.313434E+09 |
February | 0.365808E+09 | 0.245238E+09 | 0.120570E+09 | 0.499670E+09 | 0.277759E+09 |
March | 0.335275E+09 | 0.169892E+09 | 0.165382E+09 | 0.502568E+09 | 0.271700E+09 |
April | 0.284767E+09 | 0.117303E+09 | 0.167464E+09 | 0.583979E+09 | 0.113639E+09 |
May | 0.196619E+09 | 34202726.45 | 0.162417E+09 | 0.486737E+09 | 66571659.71 |
June | 0.161060E+09 | 12287840.18 | 0.148772E+09 | 0.573334E+09 | 14096348.67 |
July | 0.168647E+09 | 16034777.14 | 0.152612E+09 | 0.583899E+09 | 10030816.52 |
August | 0.208539E+09 | 58731992.40 | 0.149807E+09 | 0.637037E+09 | 11283952.84 |
September | 0.286666E+09 | 0.121159E+09 | 0.165506E+09 | 0.692753E+09 | 19720269.55 |
October | 0.475485E+09 | 0.329163E+09 | 0.146322E+09 | 0.831307E+09 | 0.162313E+09 |
November | 0.540882E+09 | 0.415420E+09 | 0.125462E+09 | 0.821919E+09 | 0.266725E+09 |
December | 0.604458E+09 | 0.478892E+09 | 0.125566E+09 | 0.885263E+09 | 0.390140E+09 |
Annual Sum or Average | 0.427727E+10 | 0.251685E+10 | 0.176042E+10 | 0.809452E+10 | 0.191741E+10 |
Minimum of Months | 0.161060E+09 | 12287840.18 | 0.120570E+09 | 0.486737E+09 | 10030816.52 |
Maximum of Months | 0.649066E+09 | 0.518528E+09 | 0.167464E+09 | 0.996054E+09 | 0.390140E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.375704E+09 | 0.00 | 0.375704E+09 | 0.232634E+09 | 0.201597E+10 |
February | 0.386675E+09 | 0.00 | 0.386675E+09 | 0.122425E+09 | 0.186136E+10 |
March | 0.569049E+09 | 22512.27 | 0.569026E+09 | 0.457352E+09 | 0.174005E+10 |
April | 0.674430E+09 | 9930025.34 | 0.664500E+09 | 0.116356E+10 | 0.783584E+09 |
May | 0.817473E+09 | 69412938.91 | 0.748060E+09 | 0.170077E+10 | 0.487707E+09 |
June | 0.913609E+09 | 0.166932E+09 | 0.746677E+09 | 0.263790E+10 | 0.158903E+09 |
July | 0.807597E+09 | 86776906.14 | 0.720820E+09 | 0.236033E+10 | 0.121294E+09 |
August | 0.649832E+09 | 15955234.21 | 0.633877E+09 | 0.192691E+10 | 0.169515E+09 |
September | 0.593020E+09 | 367012.78 | 0.592653E+09 | 0.153625E+10 | 0.264719E+09 |
October | 0.473813E+09 | 0.00 | 0.473813E+09 | 0.712717E+09 | 0.114277E+10 |
November | 0.382039E+09 | 0.00 | 0.382039E+09 | 0.239134E+09 | 0.177284E+10 |
December | 0.350942E+09 | 0.00 | 0.350942E+09 | 0.117218E+09 | 0.247723E+10 |
Annual Sum or Average | 0.699418E+10 | 0.349397E+09 | 0.664479E+10 | 0.132072E+11 | 0.129959E+11 |
Minimum of Months | 0.350942E+09 | 0.00 | 0.350942E+09 | 0.117218E+09 | 0.121294E+09 |
Maximum of Months | 0.913609E+09 | 0.166932E+09 | 0.748060E+09 | 0.263790E+10 | 0.247723E+10 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.375704E+09 | 0.00 | 0.375704E+09 | 0.209979E+09 | 0.206884E+10 |
February | 0.386675E+09 | 0.00 | 0.386675E+09 | 0.105832E+09 | 0.192351E+10 |
March | 0.569049E+09 | 22512.27 | 0.569026E+09 | 0.427713E+09 | 0.178925E+10 |
April | 0.674430E+09 | 9930025.34 | 0.664500E+09 | 0.113843E+10 | 0.805800E+09 |
May | 0.817473E+09 | 69412938.91 | 0.748060E+09 | 0.167346E+10 | 0.502858E+09 |
June | 0.913609E+09 | 0.166932E+09 | 0.746677E+09 | 0.260793E+10 | 0.166009E+09 |
July | 0.807597E+09 | 86776906.14 | 0.720820E+09 | 0.232909E+10 | 0.128395E+09 |
August | 0.649832E+09 | 15955234.21 | 0.633877E+09 | 0.189838E+10 | 0.179902E+09 |
September | 0.593020E+09 | 367012.78 | 0.592653E+09 | 0.151126E+10 | 0.278585E+09 |
October | 0.473813E+09 | 0.00 | 0.473813E+09 | 0.689495E+09 | 0.117568E+10 |
November | 0.382039E+09 | 0.00 | 0.382039E+09 | 0.218606E+09 | 0.182289E+10 |
December | 0.350942E+09 | 0.00 | 0.350942E+09 | 0.101048E+09 | 0.254638E+10 |
Annual Sum or Average | 0.699418E+10 | 0.349397E+09 | 0.664479E+10 | 0.129112E+11 | 0.133881E+11 |
Minimum of Months | 0.350942E+09 | 0.00 | 0.350942E+09 | 0.101048E+09 | 0.128395E+09 |
Maximum of Months | 0.913609E+09 | 0.166932E+09 | 0.748060E+09 | 0.260793E+10 | 0.254638E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 53674072.02 | 0.00 | 53674072.02 | 42375878.70 | 0.287148E+09 |
February | 55241433.50 | 0.00 | 55241433.50 | 22188037.93 | 0.266331E+09 |
March | 81295770.76 | 3216.16 | 81292554.60 | 76662537.06 | 0.253456E+09 |
April | 96350800.51 | 1418628.78 | 94932171.74 | 0.187953E+09 | 0.120283E+09 |
May | 0.116786E+09 | 9916509.70 | 0.106870E+09 | 0.270697E+09 | 81298635.90 |
June | 0.130521E+09 | 23848337.92 | 0.106672E+09 | 0.403497E+09 | 31703203.85 |
July | 0.115375E+09 | 12397170.40 | 0.102978E+09 | 0.363552E+09 | 25607712.99 |
August | 92836668.46 | 2279405.50 | 90557262.96 | 0.303774E+09 | 33908135.19 |
September | 84720382.40 | 52432.38 | 84667950.02 | 0.245920E+09 | 47367640.74 |
October | 67690153.51 | 0.00 | 67690153.51 | 0.118318E+09 | 0.169393E+09 |
November | 54578999.93 | 0.00 | 54578999.93 | 42970515.95 | 0.253386E+09 |
December | 50136496.34 | 0.00 | 50136496.34 | 23395470.40 | 0.347137E+09 |
Annual Sum or Average | 0.999207E+09 | 49915700.83 | 0.949291E+09 | 0.210130E+10 | 0.191702E+10 |
Minimum of Months | 50136496.34 | 0.00 | 50136496.34 | 22188037.93 | 25607712.99 |
Maximum of Months | 0.130521E+09 | 23848337.92 | 0.106870E+09 | 0.403497E+09 | 0.347137E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.647832E+09 | 0.406608E+09 | 0.241223E+09 | 0.852968E+09 | 0.969982E+09 |
February | 0.581660E+09 | 0.334662E+09 | 0.246998E+09 | 0.661630E+09 | 0.910312E+09 |
March | 0.799654E+09 | 0.411405E+09 | 0.388250E+09 | 0.106285E+10 | 0.860489E+09 |
April | 0.110278E+10 | 0.657056E+09 | 0.445720E+09 | 0.198372E+10 | 0.422406E+09 |
May | 0.118295E+10 | 0.701920E+09 | 0.481032E+09 | 0.230769E+10 | 0.300402E+09 |
June | 0.119111E+10 | 0.739991E+09 | 0.451119E+09 | 0.271481E+10 | 0.118783E+09 |
July | 0.104108E+10 | 0.587423E+09 | 0.453658E+09 | 0.242204E+10 | 95534258.39 |
August | 0.988937E+09 | 0.565014E+09 | 0.423923E+09 | 0.227019E+10 | 0.126993E+09 |
September | 0.784240E+09 | 0.378243E+09 | 0.405997E+09 | 0.174272E+10 | 0.173050E+09 |
October | 0.813243E+09 | 0.494683E+09 | 0.318561E+09 | 0.138371E+10 | 0.579848E+09 |
November | 0.605626E+09 | 0.363437E+09 | 0.242189E+09 | 0.789264E+09 | 0.864678E+09 |
December | 0.571644E+09 | 0.345721E+09 | 0.225923E+09 | 0.652308E+09 | 0.116809E+10 |
Annual Sum or Average | 0.103108E+11 | 0.598616E+10 | 0.432459E+10 | 0.188439E+11 | 0.659057E+10 |
Minimum of Months | 0.571644E+09 | 0.334662E+09 | 0.225923E+09 | 0.652308E+09 | 95534258.39 |
Maximum of Months | 0.119111E+10 | 0.739991E+09 | 0.481032E+09 | 0.271481E+10 | 0.116809E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.442566E+09 | 0.353559E+09 | 89007348.67 | 0.695599E+09 | 0.257890E+09 |
February | 0.249427E+09 | 0.167216E+09 | 82211105.16 | 0.345597E+09 | 0.239453E+09 |
March | 0.228607E+09 | 0.115841E+09 | 0.112766E+09 | 0.343999E+09 | 0.241438E+09 |
April | 0.194169E+09 | 79982898.78 | 0.114186E+09 | 0.398227E+09 | 0.123322E+09 |
May | 0.134065E+09 | 23321164.89 | 0.110744E+09 | 0.322294E+09 | 88374577.81 |
June | 0.109819E+09 | 8378476.71 | 0.101441E+09 | 0.366734E+09 | 34162953.28 |
July | 0.114992E+09 | 10933329.61 | 0.104059E+09 | 0.369132E+09 | 26928652.74 |
August | 0.142193E+09 | 40046470.60 | 0.102146E+09 | 0.417081E+09 | 34681208.50 |
September | 0.195463E+09 | 82612529.72 | 0.112851E+09 | 0.465311E+09 | 47270827.77 |
October | 0.324210E+09 | 0.224440E+09 | 99769849.61 | 0.574329E+09 | 0.156165E+09 |
November | 0.368801E+09 | 0.283255E+09 | 85546508.11 | 0.572099E+09 | 0.227784E+09 |
December | 0.412151E+09 | 0.326533E+09 | 85617432.54 | 0.619199E+09 | 0.306211E+09 |
Annual Sum or Average | 0.291646E+10 | 0.171612E+10 | 0.120034E+10 | 0.548960E+10 | 0.178368E+10 |
Minimum of Months | 0.109819E+09 | 8378476.71 | 82211105.16 | 0.322294E+09 | 26928652.74 |
Maximum of Months | 0.442566E+09 | 0.353559E+09 | 0.114186E+09 | 0.695599E+09 | 0.306211E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 67974825.56 | 0.00 | 67974825.56 | 51293336.25 | 0.318995E+09 |
February | 69959789.98 | 0.00 | 69959789.98 | 31440278.02 | 0.279642E+09 |
March | 0.102956E+09 | 4073.06 | 0.102952E+09 | 0.101063E+09 | 0.266903E+09 |
April | 0.122022E+09 | 1796603.83 | 0.120226E+09 | 0.220654E+09 | 0.127315E+09 |
May | 0.147902E+09 | 12558633.84 | 0.135344E+09 | 0.317311E+09 | 80814741.41 |
June | 0.165296E+09 | 30202415.22 | 0.135094E+09 | 0.483445E+09 | 25770245.64 |
July | 0.146116E+09 | 15700234.09 | 0.130415E+09 | 0.433229E+09 | 18957211.66 |
August | 0.117572E+09 | 2886723.24 | 0.114685E+09 | 0.353646E+09 | 26132094.39 |
September | 0.107293E+09 | 66402.30 | 0.107227E+09 | 0.282485E+09 | 41904488.16 |
October | 85725308.41 | 0.00 | 85725308.41 | 0.136803E+09 | 0.182799E+09 |
November | 69120859.66 | 0.00 | 69120859.66 | 52501021.62 | 0.277666E+09 |
December | 63494709.17 | 0.00 | 63494709.17 | 28969274.60 | 0.390195E+09 |
Annual Sum or Average | 0.126543E+10 | 63215085.59 | 0.120222E+10 | 0.249284E+10 | 0.203709E+10 |
Minimum of Months | 63494709.17 | 0.00 | 63494709.17 | 28969274.60 | 18957211.66 |
Maximum of Months | 0.165296E+09 | 30202415.22 | 0.135344E+09 | 0.483445E+09 | 0.390195E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 60817333.99 | 0.00 | 60817333.99 | 45892342.30 | 0.285374E+09 |
February | 62593289.17 | 0.00 | 62593289.17 | 28129735.87 | 0.250197E+09 |
March | 92115091.26 | 3644.19 | 92111447.08 | 90421628.18 | 0.238799E+09 |
April | 0.109174E+09 | 1607428.26 | 0.107566E+09 | 0.197420E+09 | 0.113909E+09 |
May | 0.132329E+09 | 11236257.28 | 0.121093E+09 | 0.283899E+09 | 72305255.35 |
June | 0.147891E+09 | 27022215.34 | 0.120869E+09 | 0.432540E+09 | 23056736.42 |
July | 0.130730E+09 | 14047058.93 | 0.116683E+09 | 0.387612E+09 | 16961089.10 |
August | 0.105192E+09 | 2582762.23 | 0.102609E+09 | 0.316409E+09 | 23380483.86 |
September | 95995470.41 | 59410.39 | 95936060.02 | 0.252740E+09 | 37492104.33 |
October | 76698758.25 | 0.00 | 76698758.25 | 0.122398E+09 | 0.163553E+09 |
November | 61842695.04 | 0.00 | 61842695.04 | 46972862.97 | 0.248419E+09 |
December | 56808956.88 | 0.00 | 56808956.88 | 25918919.75 | 0.349065E+09 |
Annual Sum or Average | 0.113219E+10 | 56558776.60 | 0.107563E+10 | 0.223035E+10 | 0.182251E+10 |
Minimum of Months | 56808956.88 | 0.00 | 56808956.88 | 25918919.75 | 16961089.10 |
Maximum of Months | 0.147891E+09 | 27022215.34 | 0.121093E+09 | 0.432540E+09 | 0.349065E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.165223E+10 | 0.131994E+10 | 0.332291E+09 | 0.256968E+10 | 0.843226E+09 |
February | 0.931184E+09 | 0.624266E+09 | 0.306919E+09 | 0.129501E+10 | 0.744342E+09 |
March | 0.853459E+09 | 0.432470E+09 | 0.420989E+09 | 0.128757E+10 | 0.753829E+09 |
April | 0.724889E+09 | 0.298600E+09 | 0.426289E+09 | 0.142760E+10 | 0.387418E+09 |
May | 0.500505E+09 | 87064857.88 | 0.413440E+09 | 0.113086E+10 | 0.266607E+09 |
June | 0.409987E+09 | 31279350.23 | 0.378708E+09 | 0.129360E+10 | 86822548.62 |
July | 0.429299E+09 | 40817377.39 | 0.388482E+09 | 0.129631E+10 | 61187176.65 |
August | 0.530848E+09 | 0.149505E+09 | 0.381343E+09 | 0.146127E+10 | 80827700.10 |
September | 0.729722E+09 | 0.308417E+09 | 0.421305E+09 | 0.164290E+10 | 0.122124E+09 |
October | 0.121037E+10 | 0.837901E+09 | 0.372471E+09 | 0.208712E+10 | 0.496841E+09 |
November | 0.137684E+10 | 0.105747E+10 | 0.319371E+09 | 0.211189E+10 | 0.734102E+09 |
December | 0.153868E+10 | 0.121905E+10 | 0.319635E+09 | 0.229816E+10 | 0.101570E+10 |
Annual Sum or Average | 0.108880E+11 | 0.640678E+10 | 0.448124E+10 | 0.199020E+11 | 0.559303E+10 |
Minimum of Months | 0.409987E+09 | 31279350.23 | 0.306919E+09 | 0.113086E+10 | 61187176.65 |
Maximum of Months | 0.165223E+10 | 0.131994E+10 | 0.426289E+09 | 0.256968E+10 | 0.101570E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1279.62 | 426.82 | 835.71 | 667.64 | 168.07 | 0.00 | 0.00 |
February | 720.56 | 397.09 | 521.47 | 349.59 | 171.87 | 0.00 | 0.00 |
March | 651.57 | 360.70 | 431.69 | 218.75 | 212.94 | 0.00 | 0.00 |
April | 729.43 | 206.58 | 378.88 | 156.07 | 222.81 | 0.00 | 0.00 |
May | 546.52 | 139.09 | 253.16 | 44.04 | 209.12 | 0.00 | 0.00 |
June | 623.43 | 52.57 | 214.28 | 16.35 | 197.94 | 0.00 | 0.00 |
July | 613.54 | 34.94 | 217.14 | 20.65 | 196.50 | 0.00 | 0.00 |
August | 702.84 | 46.80 | 268.51 | 75.62 | 192.88 | 0.00 | 0.00 |
September | 832.71 | 71.70 | 381.40 | 161.20 | 220.20 | 0.00 | 0.00 |
October | 1041.33 | 255.76 | 612.22 | 423.82 | 188.40 | 0.00 | 0.00 |
November | 1090.72 | 380.92 | 719.63 | 552.71 | 166.92 | 0.00 | 0.00 |
December | 1139.53 | 504.94 | 778.28 | 616.61 | 161.67 | 0.00 | 0.00 |
Annual Sum or Average | 832.02 | 239.21 | 467.74 | 275.23 | 192.51 | 0.00 | 0.00 |
Minimum of Months | 546.52 | 34.94 | 214.28 | 16.35 | 161.67 | 0.00 | 0.00 |
Maximum of Months | 1279.62 | 504.94 | 835.71 | 667.64 | 222.81 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3554.98 | 1305.72 | 2353.32 | 1880.03 | 473.29 | 0.00 | 0.00 |
February | 1977.00 | 1266.05 | 1468.41 | 984.43 | 483.99 | 0.00 | 0.00 |
March | 1779.04 | 1139.52 | 1215.60 | 615.98 | 599.62 | 0.00 | 0.00 |
April | 2028.14 | 620.26 | 1066.89 | 439.48 | 627.41 | 0.00 | 0.00 |
May | 1521.22 | 414.89 | 712.87 | 124.01 | 588.87 | 0.00 | 0.00 |
June | 1753.35 | 150.88 | 603.41 | 46.04 | 557.38 | 0.00 | 0.00 |
July | 1719.29 | 105.44 | 611.46 | 58.14 | 553.32 | 0.00 | 0.00 |
August | 1967.35 | 143.19 | 756.09 | 212.94 | 543.15 | 0.00 | 0.00 |
September | 2326.80 | 216.96 | 1074.00 | 453.93 | 620.07 | 0.00 | 0.00 |
October | 2896.46 | 778.86 | 1723.96 | 1193.45 | 530.51 | 0.00 | 0.00 |
November | 3024.60 | 1176.09 | 2026.44 | 1556.40 | 470.05 | 0.00 | 0.00 |
December | 3155.10 | 1555.24 | 2191.58 | 1736.32 | 455.26 | 0.00 | 0.00 |
Annual Sum or Average | 2311.61 | 737.27 | 1317.12 | 775.03 | 542.09 | 0.00 | 0.00 |
Minimum of Months | 1521.22 | 105.44 | 603.41 | 46.04 | 455.26 | 0.00 | 0.00 |
Maximum of Months | 3554.98 | 1555.24 | 2353.32 | 1880.03 | 627.41 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4727.73 | 1702.46 | 3057.09 | 2442.27 | 614.83 | 0.00 | 0.00 |
February | 2636.69 | 1692.01 | 1907.55 | 1278.83 | 628.73 | 0.00 | 0.00 |
March | 2374.74 | 1516.73 | 1579.13 | 800.19 | 778.94 | 0.00 | 0.00 |
April | 2725.96 | 808.50 | 1385.95 | 570.91 | 815.04 | 0.00 | 0.00 |
May | 2051.91 | 542.11 | 926.06 | 161.09 | 764.97 | 0.00 | 0.00 |
June | 2371.19 | 193.70 | 783.87 | 59.80 | 724.06 | 0.00 | 0.00 |
July | 2326.25 | 133.03 | 794.32 | 75.52 | 718.79 | 0.00 | 0.00 |
August | 2651.46 | 178.70 | 982.21 | 276.63 | 705.58 | 0.00 | 0.00 |
September | 3121.68 | 271.69 | 1395.19 | 589.68 | 805.51 | 0.00 | 0.00 |
October | 3863.35 | 1012.75 | 2239.52 | 1550.35 | 689.17 | 0.00 | 0.00 |
November | 4021.33 | 1541.16 | 2632.46 | 2021.85 | 610.62 | 0.00 | 0.00 |
December | 4194.83 | 2048.53 | 2846.99 | 2255.58 | 591.41 | 0.00 | 0.00 |
Annual Sum or Average | 3092.96 | 967.10 | 1711.02 | 1006.81 | 704.21 | 0.00 | 0.00 |
Minimum of Months | 2051.91 | 133.03 | 783.87 | 59.80 | 591.41 | 0.00 | 0.00 |
Maximum of Months | 4727.73 | 2048.53 | 3057.09 | 2442.27 | 815.04 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 435.52 | 229.17 | 292.23 | 211.13 | 81.11 | 0.00 | 0.00 |
February | 259.18 | 222.71 | 205.97 | 119.04 | 86.93 | 0.00 | 0.00 |
March | 319.69 | 196.94 | 221.47 | 108.35 | 113.12 | 0.00 | 0.00 |
April | 528.57 | 90.67 | 283.37 | 149.84 | 133.54 | 0.00 | 0.00 |
May | 531.14 | 54.07 | 259.27 | 125.95 | 133.32 | 0.00 | 0.00 |
June | 654.09 | 13.78 | 264.15 | 133.65 | 130.51 | 0.00 | 0.00 |
July | 545.87 | 8.72 | 204.27 | 79.26 | 125.00 | 0.00 | 0.00 |
August | 533.90 | 9.88 | 207.52 | 92.61 | 114.91 | 0.00 | 0.00 |
September | 490.43 | 17.44 | 209.80 | 88.38 | 121.42 | 0.00 | 0.00 |
October | 451.04 | 122.43 | 259.12 | 162.98 | 96.14 | 0.00 | 0.00 |
November | 395.39 | 202.45 | 268.67 | 185.54 | 83.13 | 0.00 | 0.00 |
December | 350.05 | 282.95 | 255.29 | 179.41 | 75.88 | 0.00 | 0.00 |
Annual Sum or Average | 458.89 | 120.54 | 244.44 | 136.45 | 107.99 | 0.00 | 0.00 |
Minimum of Months | 259.18 | 8.72 | 204.27 | 79.26 | 75.88 | 0.00 | 0.00 |
Maximum of Months | 654.09 | 282.95 | 292.23 | 211.13 | 133.54 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 209.94 | 242.44 | 147.04 | 79.12 | 67.91 | 0.00 | 0.00 |
February | 136.22 | 230.74 | 125.70 | 49.92 | 75.78 | 0.00 | 0.00 |
March | 223.55 | 202.45 | 166.47 | 65.10 | 101.37 | 0.00 | 0.00 |
April | 447.69 | 91.91 | 245.64 | 119.53 | 126.11 | 0.00 | 0.00 |
May | 507.67 | 51.12 | 252.82 | 120.95 | 131.87 | 0.00 | 0.00 |
June | 663.58 | 12.60 | 272.14 | 139.62 | 132.53 | 0.00 | 0.00 |
July | 542.72 | 8.24 | 204.41 | 79.81 | 124.60 | 0.00 | 0.00 |
August | 491.70 | 10.50 | 189.10 | 78.51 | 110.59 | 0.00 | 0.00 |
September | 406.48 | 18.68 | 167.08 | 56.53 | 110.55 | 0.00 | 0.00 |
October | 287.79 | 130.24 | 163.34 | 79.18 | 84.17 | 0.00 | 0.00 |
November | 204.97 | 214.92 | 147.44 | 76.26 | 71.18 | 0.00 | 0.00 |
December | 148.52 | 297.62 | 120.13 | 57.49 | 62.63 | 0.00 | 0.00 |
Annual Sum or Average | 356.89 | 125.55 | 183.65 | 83.62 | 100.03 | 0.00 | 0.00 |
Minimum of Months | 136.22 | 8.24 | 120.13 | 49.92 | 62.63 | 0.00 | 0.00 |
Maximum of Months | 663.58 | 297.62 | 272.14 | 139.62 | 132.53 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 190.37 | 91.70 | 132.16 | 105.58 | 26.58 | 0.00 | 0.00 |
February | 102.19 | 93.51 | 82.47 | 55.29 | 27.18 | 0.00 | 0.00 |
March | 88.94 | 83.70 | 68.27 | 34.59 | 33.67 | 0.00 | 0.00 |
April | 105.32 | 47.16 | 59.92 | 24.68 | 35.24 | 0.00 | 0.00 |
May | 77.09 | 33.04 | 40.04 | 6.96 | 33.07 | 0.00 | 0.00 |
June | 90.10 | 13.88 | 33.89 | 2.59 | 31.30 | 0.00 | 0.00 |
July | 86.69 | 11.02 | 34.34 | 3.26 | 31.07 | 0.00 | 0.00 |
August | 101.73 | 14.80 | 42.46 | 11.96 | 30.50 | 0.00 | 0.00 |
September | 121.76 | 20.31 | 60.32 | 25.49 | 34.82 | 0.00 | 0.00 |
October | 153.39 | 57.42 | 96.82 | 67.02 | 29.79 | 0.00 | 0.00 |
November | 160.47 | 84.38 | 113.80 | 87.41 | 26.40 | 0.00 | 0.00 |
December | 168.56 | 108.07 | 123.08 | 97.51 | 25.57 | 0.00 | 0.00 |
Annual Sum or Average | 120.71 | 54.75 | 73.97 | 43.53 | 30.44 | 0.00 | 0.00 |
Minimum of Months | 77.09 | 11.02 | 33.89 | 2.59 | 25.57 | 0.00 | 0.00 |
Maximum of Months | 190.37 | 108.07 | 132.16 | 105.58 | 35.24 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 16.10 | 67.57 | 16.03 | 0.00 | 16.03 | 0.00 | 0.00 |
February | 10.47 | 67.20 | 18.27 | 0.00 | 18.27 | 0.00 | 0.00 |
March | 27.11 | 57.78 | 24.29 | 0.00 | 24.28 | 0.00 | 0.00 |
April | 62.17 | 23.14 | 29.74 | 0.44 | 29.30 | 0.00 | 0.00 |
May | 85.69 | 12.06 | 34.89 | 2.96 | 31.92 | 0.00 | 0.00 |
June | 133.65 | 2.58 | 40.29 | 7.36 | 32.93 | 0.00 | 0.00 |
July | 120.36 | 1.78 | 34.47 | 3.70 | 30.76 | 0.00 | 0.00 |
August | 99.78 | 2.23 | 27.73 | 0.68 | 27.05 | 0.00 | 0.00 |
September | 82.57 | 4.14 | 26.15 | 0.02 | 26.14 | 0.00 | 0.00 |
October | 39.46 | 35.35 | 20.22 | 0.00 | 20.22 | 0.00 | 0.00 |
November | 16.53 | 59.97 | 16.85 | 0.00 | 16.85 | 0.00 | 0.00 |
December | 9.44 | 85.28 | 14.98 | 0.00 | 14.98 | 0.00 | 0.00 |
Annual Sum or Average | 58.84 | 34.79 | 25.35 | 1.27 | 24.08 | 0.00 | 0.00 |
Minimum of Months | 9.44 | 1.78 | 14.98 | 0.00 | 14.98 | 0.00 | 0.00 |
Maximum of Months | 133.65 | 85.28 | 40.29 | 7.36 | 32.93 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 414.83 | 220.33 | 286.18 | 207.91 | 78.27 | 0.00 | 0.00 |
February | 279.81 | 216.48 | 223.33 | 138.29 | 85.04 | 0.00 | 0.00 |
March | 327.43 | 185.52 | 234.64 | 120.06 | 114.59 | 0.00 | 0.00 |
April | 527.36 | 80.86 | 287.65 | 157.61 | 130.04 | 0.00 | 0.00 |
May | 545.80 | 47.16 | 270.90 | 139.75 | 131.15 | 0.00 | 0.00 |
June | 670.91 | 11.93 | 272.15 | 145.99 | 126.16 | 0.00 | 0.00 |
July | 603.78 | 7.74 | 237.29 | 113.75 | 123.55 | 0.00 | 0.00 |
August | 584.89 | 9.43 | 237.72 | 120.44 | 117.28 | 0.00 | 0.00 |
September | 517.55 | 16.36 | 226.70 | 104.84 | 121.86 | 0.00 | 0.00 |
October | 468.07 | 117.01 | 272.87 | 176.15 | 96.72 | 0.00 | 0.00 |
November | 370.42 | 195.26 | 259.12 | 179.39 | 79.73 | 0.00 | 0.00 |
December | 348.13 | 274.14 | 260.60 | 186.46 | 74.14 | 0.00 | 0.00 |
Annual Sum or Average | 472.61 | 114.78 | 255.97 | 149.33 | 106.63 | 0.00 | 0.00 |
Minimum of Months | 279.81 | 7.74 | 223.33 | 104.84 | 74.14 | 0.00 | 0.00 |
Maximum of Months | 670.91 | 274.14 | 287.65 | 207.91 | 131.15 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 175.24 | 217.84 | 140.98 | 75.91 | 65.07 | 0.00 | 0.00 |
February | 147.88 | 215.05 | 143.06 | 69.17 | 73.89 | 0.00 | 0.00 |
March | 228.45 | 187.45 | 179.64 | 76.81 | 102.83 | 0.00 | 0.00 |
April | 443.82 | 82.37 | 249.91 | 127.30 | 122.61 | 0.00 | 0.00 |
May | 520.48 | 47.36 | 264.45 | 134.75 | 129.71 | 0.00 | 0.00 |
June | 679.94 | 11.99 | 280.14 | 151.96 | 128.18 | 0.00 | 0.00 |
July | 600.39 | 7.76 | 237.44 | 114.30 | 123.14 | 0.00 | 0.00 |
August | 541.61 | 10.23 | 219.29 | 106.33 | 112.95 | 0.00 | 0.00 |
September | 431.31 | 17.25 | 183.98 | 72.99 | 110.99 | 0.00 | 0.00 |
October | 297.64 | 119.25 | 177.10 | 92.35 | 84.75 | 0.00 | 0.00 |
November | 168.66 | 195.08 | 137.89 | 70.11 | 67.78 | 0.00 | 0.00 |
December | 129.62 | 270.17 | 125.44 | 64.54 | 60.90 | 0.00 | 0.00 |
Annual Sum or Average | 364.79 | 114.75 | 195.17 | 96.50 | 98.67 | 0.00 | 0.00 |
Minimum of Months | 129.62 | 7.76 | 125.44 | 64.54 | 60.90 | 0.00 | 0.00 |
Maximum of Months | 679.94 | 270.17 | 280.14 | 151.96 | 129.71 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 469.60 | 294.99 | 321.09 | 228.77 | 92.33 | 0.00 | 0.00 |
February | 265.69 | 286.23 | 218.26 | 119.79 | 98.47 | 0.00 | 0.00 |
March | 283.81 | 259.87 | 200.53 | 74.96 | 125.57 | 0.00 | 0.00 |
April | 388.88 | 130.74 | 194.25 | 54.43 | 139.83 | 0.00 | 0.00 |
May | 371.87 | 81.01 | 162.32 | 21.51 | 140.82 | 0.00 | 0.00 |
June | 499.70 | 25.79 | 160.71 | 21.55 | 139.16 | 0.00 | 0.00 |
July | 462.47 | 17.62 | 149.07 | 15.10 | 133.97 | 0.00 | 0.00 |
August | 449.78 | 23.83 | 152.08 | 27.39 | 124.70 | 0.00 | 0.00 |
September | 458.45 | 39.78 | 187.34 | 55.27 | 132.07 | 0.00 | 0.00 |
October | 438.17 | 174.81 | 253.58 | 145.22 | 108.36 | 0.00 | 0.00 |
November | 404.40 | 265.57 | 283.08 | 189.39 | 93.69 | 0.00 | 0.00 |
December | 404.49 | 356.35 | 299.12 | 211.28 | 87.84 | 0.00 | 0.00 |
Annual Sum or Average | 408.95 | 162.56 | 215.19 | 97.05 | 118.14 | 0.00 | 0.00 |
Minimum of Months | 265.69 | 17.62 | 149.07 | 15.10 | 87.84 | 0.00 | 0.00 |
Maximum of Months | 499.70 | 356.35 | 321.09 | 228.77 | 140.82 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 432.96 | 226.27 | 292.23 | 211.13 | 81.11 | 0.00 | 0.00 |
February | 256.84 | 219.62 | 205.97 | 119.04 | 86.93 | 0.00 | 0.00 |
March | 316.48 | 194.88 | 221.47 | 108.35 | 113.12 | 0.00 | 0.00 |
April | 524.29 | 87.91 | 283.37 | 149.84 | 133.54 | 0.00 | 0.00 |
May | 528.92 | 51.50 | 259.27 | 125.95 | 133.32 | 0.00 | 0.00 |
June | 652.77 | 12.54 | 264.15 | 133.65 | 130.51 | 0.00 | 0.00 |
July | 545.35 | 8.16 | 204.27 | 79.26 | 125.00 | 0.00 | 0.00 |
August | 533.04 | 9.08 | 207.52 | 92.61 | 114.91 | 0.00 | 0.00 |
September | 489.19 | 15.94 | 209.80 | 88.38 | 121.42 | 0.00 | 0.00 |
October | 448.64 | 119.08 | 259.12 | 162.98 | 96.14 | 0.00 | 0.00 |
November | 392.71 | 199.49 | 268.67 | 185.54 | 83.13 | 0.00 | 0.00 |
December | 348.82 | 279.80 | 255.29 | 179.41 | 75.88 | 0.00 | 0.00 |
Annual Sum or Average | 456.83 | 118.30 | 244.44 | 136.45 | 107.99 | 0.00 | 0.00 |
Minimum of Months | 256.84 | 8.16 | 204.27 | 79.26 | 75.88 | 0.00 | 0.00 |
Maximum of Months | 652.77 | 279.80 | 292.23 | 211.13 | 133.54 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 209.89 | 237.41 | 147.04 | 79.12 | 67.91 | 0.00 | 0.00 |
February | 135.26 | 226.33 | 125.70 | 49.92 | 75.78 | 0.00 | 0.00 |
March | 221.51 | 200.30 | 166.47 | 65.10 | 101.37 | 0.00 | 0.00 |
April | 444.53 | 89.30 | 245.64 | 119.53 | 126.11 | 0.00 | 0.00 |
May | 506.18 | 48.62 | 252.82 | 120.95 | 131.87 | 0.00 | 0.00 |
June | 662.25 | 11.54 | 272.14 | 139.62 | 132.53 | 0.00 | 0.00 |
July | 542.25 | 7.73 | 204.41 | 79.81 | 124.60 | 0.00 | 0.00 |
August | 491.28 | 9.70 | 189.10 | 78.51 | 110.59 | 0.00 | 0.00 |
September | 406.35 | 17.02 | 167.08 | 56.53 | 110.55 | 0.00 | 0.00 |
October | 287.52 | 125.87 | 163.34 | 79.18 | 84.17 | 0.00 | 0.00 |
November | 204.65 | 210.22 | 147.44 | 76.26 | 71.18 | 0.00 | 0.00 |
December | 149.09 | 292.15 | 120.13 | 57.49 | 62.63 | 0.00 | 0.00 |
Annual Sum or Average | 356.05 | 122.62 | 183.65 | 83.62 | 100.03 | 0.00 | 0.00 |
Minimum of Months | 135.26 | 7.73 | 120.13 | 49.92 | 62.63 | 0.00 | 0.00 |
Maximum of Months | 662.25 | 292.15 | 272.14 | 139.62 | 132.53 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 371.88 | 117.02 | 242.33 | 193.60 | 48.74 | 0.00 | 0.00 |
February | 206.54 | 114.81 | 151.21 | 101.37 | 49.84 | 0.00 | 0.00 |
March | 187.64 | 101.44 | 125.18 | 63.43 | 61.75 | 0.00 | 0.00 |
April | 225.30 | 43.84 | 109.86 | 45.26 | 64.61 | 0.00 | 0.00 |
May | 181.73 | 24.86 | 73.41 | 12.77 | 60.64 | 0.00 | 0.00 |
June | 221.19 | 5.44 | 62.14 | 4.74 | 57.40 | 0.00 | 0.00 |
July | 218.00 | 3.75 | 62.97 | 5.99 | 56.98 | 0.00 | 0.00 |
August | 237.84 | 4.21 | 77.86 | 21.93 | 55.93 | 0.00 | 0.00 |
September | 267.27 | 7.61 | 110.60 | 46.74 | 63.85 | 0.00 | 0.00 |
October | 310.37 | 60.60 | 177.53 | 122.90 | 54.63 | 0.00 | 0.00 |
November | 317.10 | 102.90 | 208.67 | 160.27 | 48.40 | 0.00 | 0.00 |
December | 330.52 | 145.66 | 225.68 | 178.80 | 46.88 | 0.00 | 0.00 |
Annual Sum or Average | 256.68 | 60.80 | 135.63 | 79.81 | 55.82 | 0.00 | 0.00 |
Minimum of Months | 181.73 | 3.75 | 62.14 | 4.74 | 46.88 | 0.00 | 0.00 |
Maximum of Months | 371.88 | 145.66 | 242.33 | 193.60 | 64.61 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 86.86 | 752.68 | 140.27 | 0.00 | 140.27 | 0.00 | 0.00 |
February | 50.61 | 769.41 | 159.84 | 0.00 | 159.84 | 0.00 | 0.00 |
March | 170.76 | 649.66 | 212.46 | 0.01 | 212.45 | 0.00 | 0.00 |
April | 448.90 | 302.31 | 260.20 | 3.83 | 256.37 | 0.00 | 0.00 |
May | 634.99 | 182.09 | 305.21 | 25.92 | 279.29 | 0.00 | 0.00 |
June | 1017.71 | 61.31 | 352.47 | 64.40 | 288.07 | 0.00 | 0.00 |
July | 881.25 | 45.29 | 301.52 | 32.40 | 269.12 | 0.00 | 0.00 |
August | 719.42 | 63.29 | 242.62 | 5.96 | 236.66 | 0.00 | 0.00 |
September | 592.69 | 102.13 | 228.79 | 0.14 | 228.65 | 0.00 | 0.00 |
October | 266.10 | 426.66 | 176.90 | 0.00 | 176.90 | 0.00 | 0.00 |
November | 92.26 | 683.97 | 147.39 | 0.00 | 147.39 | 0.00 | 0.00 |
December | 43.76 | 924.89 | 131.03 | 0.00 | 131.03 | 0.00 | 0.00 |
Annual Sum or Average | 418.80 | 412.10 | 221.78 | 11.08 | 210.70 | 0.00 | 0.00 |
Minimum of Months | 43.76 | 45.29 | 131.03 | 0.00 | 131.03 | 0.00 | 0.00 |
Maximum of Months | 1017.71 | 924.89 | 352.47 | 64.40 | 288.07 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 78.40 | 772.42 | 140.27 | 0.00 | 140.27 | 0.00 | 0.00 |
February | 43.75 | 795.10 | 159.84 | 0.00 | 159.84 | 0.00 | 0.00 |
March | 159.69 | 668.03 | 212.46 | 0.01 | 212.45 | 0.00 | 0.00 |
April | 439.21 | 310.88 | 260.20 | 3.83 | 256.37 | 0.00 | 0.00 |
May | 624.80 | 187.75 | 305.21 | 25.92 | 279.29 | 0.00 | 0.00 |
June | 1006.15 | 64.05 | 352.47 | 64.40 | 288.07 | 0.00 | 0.00 |
July | 869.58 | 47.94 | 301.52 | 32.40 | 269.12 | 0.00 | 0.00 |
August | 708.77 | 67.17 | 242.62 | 5.96 | 236.66 | 0.00 | 0.00 |
September | 583.05 | 107.48 | 228.79 | 0.14 | 228.65 | 0.00 | 0.00 |
October | 257.43 | 438.95 | 176.90 | 0.00 | 176.90 | 0.00 | 0.00 |
November | 84.34 | 703.28 | 147.39 | 0.00 | 147.39 | 0.00 | 0.00 |
December | 37.73 | 950.71 | 131.03 | 0.00 | 131.03 | 0.00 | 0.00 |
Annual Sum or Average | 409.41 | 424.53 | 221.78 | 11.08 | 210.70 | 0.00 | 0.00 |
Minimum of Months | 37.73 | 47.94 | 131.03 | 0.00 | 131.03 | 0.00 | 0.00 |
Maximum of Months | 1006.15 | 950.71 | 352.47 | 64.40 | 288.07 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 580.41 | 552.06 | 427.15 | 283.81 | 143.33 | 0.00 | 0.00 |
February | 410.02 | 569.86 | 366.37 | 207.46 | 158.92 | 0.00 | 0.00 |
March | 541.83 | 493.99 | 414.26 | 196.85 | 217.41 | 0.00 | 0.00 |
April | 984.29 | 249.77 | 537.54 | 284.90 | 252.64 | 0.00 | 0.00 |
May | 1079.62 | 172.14 | 535.32 | 274.48 | 260.84 | 0.00 | 0.00 |
June | 1343.60 | 70.30 | 552.26 | 297.92 | 254.33 | 0.00 | 0.00 |
July | 1177.25 | 54.69 | 474.70 | 228.03 | 246.68 | 0.00 | 0.00 |
August | 1116.35 | 72.64 | 456.98 | 226.75 | 230.22 | 0.00 | 0.00 |
September | 945.78 | 102.31 | 410.66 | 177.82 | 232.84 | 0.00 | 0.00 |
October | 768.13 | 330.94 | 449.95 | 268.49 | 181.46 | 0.00 | 0.00 |
November | 527.91 | 505.34 | 396.99 | 249.50 | 147.50 | 0.00 | 0.00 |
December | 462.54 | 659.13 | 386.03 | 250.99 | 135.03 | 0.00 | 0.00 |
Annual Sum or Average | 830.24 | 318.33 | 451.12 | 245.82 | 205.30 | 0.00 | 0.00 |
Minimum of Months | 410.02 | 54.69 | 366.37 | 177.82 | 135.03 | 0.00 | 0.00 |
Maximum of Months | 1343.60 | 659.13 | 552.26 | 297.92 | 260.84 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 977.93 | 522.71 | 664.96 | 492.81 | 172.15 | 0.00 | 0.00 |
February | 545.66 | 512.43 | 439.71 | 258.05 | 181.66 | 0.00 | 0.00 |
March | 548.86 | 466.90 | 391.48 | 161.47 | 230.01 | 0.00 | 0.00 |
April | 711.78 | 242.25 | 368.86 | 116.51 | 252.35 | 0.00 | 0.00 |
May | 643.16 | 153.19 | 291.49 | 41.39 | 250.10 | 0.00 | 0.00 |
June | 849.67 | 49.54 | 279.00 | 34.15 | 244.86 | 0.00 | 0.00 |
July | 789.37 | 35.17 | 263.64 | 26.35 | 237.30 | 0.00 | 0.00 |
August | 795.19 | 48.11 | 281.37 | 57.86 | 223.51 | 0.00 | 0.00 |
September | 840.25 | 77.67 | 359.96 | 119.04 | 240.92 | 0.00 | 0.00 |
October | 869.95 | 308.75 | 512.54 | 312.84 | 199.71 | 0.00 | 0.00 |
November | 836.97 | 470.01 | 581.72 | 407.98 | 173.74 | 0.00 | 0.00 |
December | 853.55 | 630.25 | 619.39 | 455.14 | 164.25 | 0.00 | 0.00 |
Annual Sum or Average | 773.31 | 292.19 | 421.29 | 206.96 | 214.33 | 0.00 | 0.00 |
Minimum of Months | 545.66 | 35.17 | 263.64 | 26.35 | 164.25 | 0.00 | 0.00 |
Maximum of Months | 977.93 | 630.25 | 664.96 | 492.81 | 252.35 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.342734E+10 | 0.114319E+10 | 0.223838E+10 | 0.178821E+10 | 0.450171E+09 | 0.00 | 0.00 |
February | 0.174318E+10 | 0.960649E+09 | 0.126153E+10 | 0.845731E+09 | 0.415798E+09 | 0.00 | 0.00 |
March | 0.174516E+10 | 0.966102E+09 | 0.115623E+10 | 0.585894E+09 | 0.570335E+09 | 0.00 | 0.00 |
April | 0.189070E+10 | 0.535448E+09 | 0.982044E+09 | 0.404532E+09 | 0.577512E+09 | 0.00 | 0.00 |
May | 0.146380E+10 | 0.372544E+09 | 0.678057E+09 | 0.117952E+09 | 0.560105E+09 | 0.00 | 0.00 |
June | 0.161592E+10 | 0.136249E+09 | 0.555427E+09 | 42376069.35 | 0.513050E+09 | 0.00 | 0.00 |
July | 0.164330E+10 | 93594508.08 | 0.581591E+09 | 55297824.35 | 0.526293E+09 | 0.00 | 0.00 |
August | 0.188247E+10 | 0.125360E+09 | 0.719166E+09 | 0.202544E+09 | 0.516622E+09 | 0.00 | 0.00 |
September | 0.215838E+10 | 0.185854E+09 | 0.988595E+09 | 0.417832E+09 | 0.570763E+09 | 0.00 | 0.00 |
October | 0.278909E+10 | 0.685015E+09 | 0.163976E+10 | 0.113516E+10 | 0.504604E+09 | 0.00 | 0.00 |
November | 0.282715E+10 | 0.987347E+09 | 0.186529E+10 | 0.143263E+10 | 0.432667E+09 | 0.00 | 0.00 |
December | 0.305212E+10 | 0.135242E+10 | 0.208454E+10 | 0.165152E+10 | 0.433026E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.262386E+11 | 0.754378E+10 | 0.147506E+11 | 0.867966E+10 | 0.607095E+10 | 0.00 | 0.00 |
Minimum of Months | 0.146380E+10 | 93594508.08 | 0.555427E+09 | 42376069.35 | 0.415798E+09 | 0.00 | 0.00 |
Maximum of Months | 0.342734E+10 | 0.135242E+10 | 0.223838E+10 | 0.178821E+10 | 0.577512E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.952166E+10 | 0.349725E+10 | 0.630312E+10 | 0.503547E+10 | 0.126765E+10 | 0.00 | 0.00 |
February | 0.478275E+10 | 0.306283E+10 | 0.355238E+10 | 0.238152E+10 | 0.117086E+10 | 0.00 | 0.00 |
March | 0.476498E+10 | 0.305209E+10 | 0.325586E+10 | 0.164984E+10 | 0.160603E+10 | 0.00 | 0.00 |
April | 0.525694E+10 | 0.160772E+10 | 0.276537E+10 | 0.113914E+10 | 0.162624E+10 | 0.00 | 0.00 |
May | 0.407443E+10 | 0.111125E+10 | 0.190936E+10 | 0.332145E+09 | 0.157722E+10 | 0.00 | 0.00 |
June | 0.454467E+10 | 0.391093E+09 | 0.156404E+10 | 0.119328E+09 | 0.144472E+10 | 0.00 | 0.00 |
July | 0.460495E+10 | 0.282419E+09 | 0.163772E+10 | 0.155715E+09 | 0.148201E+10 | 0.00 | 0.00 |
August | 0.526936E+10 | 0.383527E+09 | 0.202512E+10 | 0.570351E+09 | 0.145477E+10 | 0.00 | 0.00 |
September | 0.603106E+10 | 0.562363E+09 | 0.278382E+10 | 0.117659E+10 | 0.160723E+10 | 0.00 | 0.00 |
October | 0.775788E+10 | 0.208610E+10 | 0.461746E+10 | 0.319653E+10 | 0.142093E+10 | 0.00 | 0.00 |
November | 0.783977E+10 | 0.304843E+10 | 0.525254E+10 | 0.403418E+10 | 0.121836E+10 | 0.00 | 0.00 |
December | 0.845063E+10 | 0.416557E+10 | 0.586993E+10 | 0.465056E+10 | 0.121937E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.728991E+11 | 0.232506E+11 | 0.415367E+11 | 0.244414E+11 | 0.170954E+11 | 0.00 | 0.00 |
Minimum of Months | 0.407443E+10 | 0.282419E+09 | 0.156404E+10 | 0.119328E+09 | 0.117086E+10 | 0.00 | 0.00 |
Maximum of Months | 0.952166E+10 | 0.416557E+10 | 0.630312E+10 | 0.503547E+10 | 0.162624E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.126627E+11 | 0.455988E+10 | 0.818812E+10 | 0.654136E+10 | 0.164675E+10 | 0.00 | 0.00 |
February | 0.637869E+10 | 0.409330E+10 | 0.461475E+10 | 0.309374E+10 | 0.152101E+10 | 0.00 | 0.00 |
March | 0.636051E+10 | 0.406240E+10 | 0.422955E+10 | 0.214323E+10 | 0.208632E+10 | 0.00 | 0.00 |
April | 0.706568E+10 | 0.209562E+10 | 0.359238E+10 | 0.147980E+10 | 0.211257E+10 | 0.00 | 0.00 |
May | 0.549583E+10 | 0.145198E+10 | 0.248037E+10 | 0.431476E+09 | 0.204890E+10 | 0.00 | 0.00 |
June | 0.614612E+10 | 0.502074E+09 | 0.203178E+10 | 0.155014E+09 | 0.187677E+10 | 0.00 | 0.00 |
July | 0.623063E+10 | 0.356302E+09 | 0.212749E+10 | 0.202283E+09 | 0.192521E+10 | 0.00 | 0.00 |
August | 0.710166E+10 | 0.478630E+09 | 0.263075E+10 | 0.740919E+09 | 0.188983E+10 | 0.00 | 0.00 |
September | 0.809140E+10 | 0.704210E+09 | 0.361634E+10 | 0.152845E+10 | 0.208788E+10 | 0.00 | 0.00 |
October | 0.103476E+11 | 0.271254E+10 | 0.599834E+10 | 0.415247E+10 | 0.184587E+10 | 0.00 | 0.00 |
November | 0.104233E+11 | 0.399470E+10 | 0.682335E+10 | 0.524063E+10 | 0.158272E+10 | 0.00 | 0.00 |
December | 0.112354E+11 | 0.548677E+10 | 0.762538E+10 | 0.604134E+10 | 0.158404E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.975396E+11 | 0.304984E+11 | 0.539586E+11 | 0.317507E+11 | 0.222079E+11 | 0.00 | 0.00 |
Minimum of Months | 0.549583E+10 | 0.356302E+09 | 0.203178E+10 | 0.155014E+09 | 0.152101E+10 | 0.00 | 0.00 |
Maximum of Months | 0.126627E+11 | 0.548677E+10 | 0.818812E+10 | 0.654136E+10 | 0.211257E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.116649E+10 | 0.613820E+09 | 0.782721E+09 | 0.565485E+09 | 0.217236E+09 | 0.00 | 0.00 |
February | 0.627006E+09 | 0.538783E+09 | 0.498285E+09 | 0.287991E+09 | 0.210294E+09 | 0.00 | 0.00 |
March | 0.856262E+09 | 0.527490E+09 | 0.593196E+09 | 0.290214E+09 | 0.302982E+09 | 0.00 | 0.00 |
April | 0.137005E+10 | 0.235019E+09 | 0.734505E+09 | 0.388376E+09 | 0.346129E+09 | 0.00 | 0.00 |
May | 0.142261E+10 | 0.144828E+09 | 0.694431E+09 | 0.337345E+09 | 0.357087E+09 | 0.00 | 0.00 |
June | 0.169540E+10 | 35713302.42 | 0.684686E+09 | 0.346412E+09 | 0.338274E+09 | 0.00 | 0.00 |
July | 0.146206E+10 | 23351161.97 | 0.547106E+09 | 0.212292E+09 | 0.334813E+09 | 0.00 | 0.00 |
August | 0.143000E+10 | 26464120.07 | 0.555835E+09 | 0.248047E+09 | 0.307788E+09 | 0.00 | 0.00 |
September | 0.127119E+10 | 45208719.85 | 0.543814E+09 | 0.229081E+09 | 0.314733E+09 | 0.00 | 0.00 |
October | 0.120806E+10 | 0.327926E+09 | 0.694021E+09 | 0.436513E+09 | 0.257508E+09 | 0.00 | 0.00 |
November | 0.102484E+10 | 0.524748E+09 | 0.696397E+09 | 0.480919E+09 | 0.215478E+09 | 0.00 | 0.00 |
December | 0.937561E+09 | 0.757846E+09 | 0.683759E+09 | 0.480526E+09 | 0.203233E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.144715E+11 | 0.380120E+10 | 0.770875E+10 | 0.430320E+10 | 0.340555E+10 | 0.00 | 0.00 |
Minimum of Months | 0.627006E+09 | 23351161.97 | 0.498285E+09 | 0.212292E+09 | 0.203233E+09 | 0.00 | 0.00 |
Maximum of Months | 0.169540E+10 | 0.757846E+09 | 0.782721E+09 | 0.565485E+09 | 0.357087E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.562295E+09 | 0.649355E+09 | 0.393828E+09 | 0.211926E+09 | 0.181903E+09 | 0.00 | 0.00 |
February | 0.329533E+09 | 0.558198E+09 | 0.304099E+09 | 0.120775E+09 | 0.183324E+09 | 0.00 | 0.00 |
March | 0.598748E+09 | 0.542233E+09 | 0.445884E+09 | 0.174376E+09 | 0.271508E+09 | 0.00 | 0.00 |
April | 0.116040E+10 | 0.238219E+09 | 0.636687E+09 | 0.309812E+09 | 0.326875E+09 | 0.00 | 0.00 |
May | 0.135975E+10 | 0.136927E+09 | 0.677152E+09 | 0.323940E+09 | 0.353213E+09 | 0.00 | 0.00 |
June | 0.172001E+10 | 32652881.42 | 0.705388E+09 | 0.361882E+09 | 0.343505E+09 | 0.00 | 0.00 |
July | 0.145361E+10 | 22075983.38 | 0.547489E+09 | 0.213756E+09 | 0.333733E+09 | 0.00 | 0.00 |
August | 0.131696E+10 | 28123788.07 | 0.506479E+09 | 0.210280E+09 | 0.296199E+09 | 0.00 | 0.00 |
September | 0.105359E+10 | 48429163.32 | 0.433071E+09 | 0.146521E+09 | 0.286550E+09 | 0.00 | 0.00 |
October | 0.770813E+09 | 0.348828E+09 | 0.437501E+09 | 0.212073E+09 | 0.225428E+09 | 0.00 | 0.00 |
November | 0.531291E+09 | 0.557068E+09 | 0.382175E+09 | 0.197665E+09 | 0.184511E+09 | 0.00 | 0.00 |
December | 0.397790E+09 | 0.797147E+09 | 0.321745E+09 | 0.153993E+09 | 0.167752E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.112548E+11 | 0.395926E+10 | 0.579150E+10 | 0.263700E+10 | 0.315450E+10 | 0.00 | 0.00 |
Minimum of Months | 0.329533E+09 | 22075983.38 | 0.304099E+09 | 0.120775E+09 | 0.167752E+09 | 0.00 | 0.00 |
Maximum of Months | 0.172001E+10 | 0.797147E+09 | 0.705388E+09 | 0.361882E+09 | 0.353213E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.509879E+09 | 0.245600E+09 | 0.353983E+09 | 0.282791E+09 | 71191720.82 | 0.00 | 0.00 |
February | 0.247208E+09 | 0.226224E+09 | 0.199502E+09 | 0.133746E+09 | 65755807.07 | 0.00 | 0.00 |
March | 0.238221E+09 | 0.224177E+09 | 0.182850E+09 | 92654621.17 | 90194909.73 | 0.00 | 0.00 |
April | 0.272996E+09 | 0.122236E+09 | 0.155304E+09 | 63973596.40 | 91330373.15 | 0.00 | 0.00 |
May | 0.206467E+09 | 88485979.64 | 0.107231E+09 | 18653222.29 | 88577606.46 | 0.00 | 0.00 |
June | 0.233536E+09 | 35986493.20 | 87837819.98 | 6701448.63 | 81136371.35 | 0.00 | 0.00 |
July | 0.232184E+09 | 29510363.05 | 91975290.32 | 8744924.55 | 83230365.76 | 0.00 | 0.00 |
August | 0.272470E+09 | 39644922.76 | 0.113732E+09 | 32030806.41 | 81700800.92 | 0.00 | 0.00 |
September | 0.315593E+09 | 52641222.72 | 0.156339E+09 | 66076882.86 | 90262586.66 | 0.00 | 0.00 |
October | 0.410836E+09 | 0.153797E+09 | 0.259316E+09 | 0.179516E+09 | 79800009.62 | 0.00 | 0.00 |
November | 0.415941E+09 | 0.218711E+09 | 0.294982E+09 | 0.226559E+09 | 68423598.87 | 0.00 | 0.00 |
December | 0.451477E+09 | 0.289441E+09 | 0.329655E+09 | 0.261175E+09 | 68480327.14 | 0.00 | 0.00 |
Annual Sum or Average | 0.380681E+10 | 0.172646E+10 | 0.233271E+10 | 0.137262E+10 | 0.960084E+09 | 0.00 | 0.00 |
Minimum of Months | 0.206467E+09 | 29510363.05 | 87837819.98 | 6701448.63 | 65755807.07 | 0.00 | 0.00 |
Maximum of Months | 0.509879E+09 | 0.289441E+09 | 0.353983E+09 | 0.282791E+09 | 91330373.15 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 43126826.28 | 0.180977E+09 | 42944949.46 | 0.00 | 42944949.46 | 0.00 | 0.00 |
February | 25337863.75 | 0.162562E+09 | 44199004.85 | 0.00 | 44199004.85 | 0.00 | 0.00 |
March | 72602461.42 | 0.154762E+09 | 65045237.58 | 2573.27 | 65042664.31 | 0.00 | 0.00 |
April | 0.161138E+09 | 59983089.50 | 77090857.89 | 1135053.46 | 75955804.43 | 0.00 | 0.00 |
May | 0.229509E+09 | 32293390.84 | 93441433.49 | 7934259.35 | 85507174.14 | 0.00 | 0.00 |
June | 0.346421E+09 | 6680821.10 | 0.104430E+09 | 19081199.32 | 85349110.47 | 0.00 | 0.00 |
July | 0.322366E+09 | 4755290.91 | 92312481.83 | 9919050.97 | 82393430.86 | 0.00 | 0.00 |
August | 0.267261E+09 | 5966905.64 | 74279179.59 | 1823766.12 | 72455413.47 | 0.00 | 0.00 |
September | 0.214018E+09 | 10738945.32 | 67785290.05 | 41951.47 | 67743338.59 | 0.00 | 0.00 |
October | 0.105677E+09 | 94682300.52 | 54159300.98 | 0.00 | 54159300.98 | 0.00 | 0.00 |
November | 42842610.63 | 0.155441E+09 | 43668987.75 | 0.00 | 43668987.75 | 0.00 | 0.00 |
December | 25287949.73 | 0.228415E+09 | 40114513.77 | 0.00 | 40114513.77 | 0.00 | 0.00 |
Annual Sum or Average | 0.185559E+10 | 0.109726E+10 | 0.799472E+09 | 39937853.95 | 0.759534E+09 | 0.00 | 0.00 |
Minimum of Months | 25287949.73 | 4755290.91 | 40114513.77 | 0.00 | 40114513.77 | 0.00 | 0.00 |
Maximum of Months | 0.346421E+09 | 0.228415E+09 | 0.104430E+09 | 19081199.32 | 85507174.14 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.111107E+10 | 0.590134E+09 | 0.766505E+09 | 0.556878E+09 | 0.209627E+09 | 0.00 | 0.00 |
February | 0.676923E+09 | 0.523706E+09 | 0.540277E+09 | 0.334558E+09 | 0.205719E+09 | 0.00 | 0.00 |
March | 0.877002E+09 | 0.496908E+09 | 0.628463E+09 | 0.321558E+09 | 0.306905E+09 | 0.00 | 0.00 |
April | 0.136691E+10 | 0.209594E+09 | 0.745596E+09 | 0.408534E+09 | 0.337062E+09 | 0.00 | 0.00 |
May | 0.146187E+10 | 0.126316E+09 | 0.725583E+09 | 0.374306E+09 | 0.351277E+09 | 0.00 | 0.00 |
June | 0.173901E+10 | 30919778.11 | 0.705417E+09 | 0.378400E+09 | 0.327016E+09 | 0.00 | 0.00 |
July | 0.161716E+10 | 20730170.32 | 0.635569E+09 | 0.304666E+09 | 0.330904E+09 | 0.00 | 0.00 |
August | 0.156656E+10 | 25261234.45 | 0.636696E+09 | 0.322574E+09 | 0.314123E+09 | 0.00 | 0.00 |
September | 0.134148E+10 | 42408485.69 | 0.587611E+09 | 0.271747E+09 | 0.315864E+09 | 0.00 | 0.00 |
October | 0.125367E+10 | 0.313410E+09 | 0.730860E+09 | 0.471799E+09 | 0.259061E+09 | 0.00 | 0.00 |
November | 0.960118E+09 | 0.506104E+09 | 0.671635E+09 | 0.464986E+09 | 0.206650E+09 | 0.00 | 0.00 |
December | 0.932438E+09 | 0.734251E+09 | 0.697993E+09 | 0.499406E+09 | 0.198587E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.149042E+11 | 0.361974E+10 | 0.807221E+10 | 0.470941E+10 | 0.336279E+10 | 0.00 | 0.00 |
Minimum of Months | 0.676923E+09 | 20730170.32 | 0.540277E+09 | 0.271747E+09 | 0.198587E+09 | 0.00 | 0.00 |
Maximum of Months | 0.173901E+10 | 0.734251E+09 | 0.766505E+09 | 0.556878E+09 | 0.351277E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.469368E+09 | 0.583455E+09 | 0.377613E+09 | 0.203319E+09 | 0.174294E+09 | 0.00 | 0.00 |
February | 0.357762E+09 | 0.520238E+09 | 0.346092E+09 | 0.167343E+09 | 0.178749E+09 | 0.00 | 0.00 |
March | 0.611888E+09 | 0.502075E+09 | 0.481151E+09 | 0.205720E+09 | 0.275431E+09 | 0.00 | 0.00 |
April | 0.115039E+10 | 0.213512E+09 | 0.647778E+09 | 0.329970E+09 | 0.317808E+09 | 0.00 | 0.00 |
May | 0.139405E+10 | 0.126845E+09 | 0.708304E+09 | 0.360901E+09 | 0.347403E+09 | 0.00 | 0.00 |
June | 0.176240E+10 | 31088314.61 | 0.726118E+09 | 0.393870E+09 | 0.332248E+09 | 0.00 | 0.00 |
July | 0.160808E+10 | 20793728.30 | 0.635953E+09 | 0.306130E+09 | 0.329823E+09 | 0.00 | 0.00 |
August | 0.145064E+10 | 27409750.30 | 0.587340E+09 | 0.284806E+09 | 0.302534E+09 | 0.00 | 0.00 |
September | 0.111795E+10 | 44720570.11 | 0.476868E+09 | 0.189187E+09 | 0.287681E+09 | 0.00 | 0.00 |
October | 0.797192E+09 | 0.319406E+09 | 0.474341E+09 | 0.247359E+09 | 0.226982E+09 | 0.00 | 0.00 |
November | 0.437166E+09 | 0.505646E+09 | 0.357413E+09 | 0.181731E+09 | 0.175682E+09 | 0.00 | 0.00 |
December | 0.347173E+09 | 0.723619E+09 | 0.335979E+09 | 0.172873E+09 | 0.163106E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.115041E+11 | 0.361881E+10 | 0.615495E+10 | 0.304321E+10 | 0.311174E+10 | 0.00 | 0.00 |
Minimum of Months | 0.347173E+09 | 20793728.30 | 0.335979E+09 | 0.167343E+09 | 0.163106E+09 | 0.00 | 0.00 |
Maximum of Months | 0.176240E+10 | 0.723619E+09 | 0.726118E+09 | 0.393870E+09 | 0.347403E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.125778E+10 | 0.790114E+09 | 0.860015E+09 | 0.612730E+09 | 0.247286E+09 | 0.00 | 0.00 |
February | 0.642760E+09 | 0.692439E+09 | 0.528015E+09 | 0.289790E+09 | 0.238224E+09 | 0.00 | 0.00 |
March | 0.760150E+09 | 0.696034E+09 | 0.537094E+09 | 0.200762E+09 | 0.336332E+09 | 0.00 | 0.00 |
April | 0.100797E+10 | 0.338881E+09 | 0.503505E+09 | 0.141072E+09 | 0.362433E+09 | 0.00 | 0.00 |
May | 0.996028E+09 | 0.216965E+09 | 0.434765E+09 | 57604611.69 | 0.377160E+09 | 0.00 | 0.00 |
June | 0.129521E+10 | 66847864.79 | 0.416551E+09 | 55856451.63 | 0.360695E+09 | 0.00 | 0.00 |
July | 0.123869E+10 | 47194561.41 | 0.399265E+09 | 40435810.09 | 0.358829E+09 | 0.00 | 0.00 |
August | 0.120470E+10 | 63822164.97 | 0.407338E+09 | 73352738.99 | 0.333986E+09 | 0.00 | 0.00 |
September | 0.118831E+10 | 0.103121E+09 | 0.485590E+09 | 0.143261E+09 | 0.342329E+09 | 0.00 | 0.00 |
October | 0.117360E+10 | 0.468202E+09 | 0.679193E+09 | 0.388962E+09 | 0.290232E+09 | 0.00 | 0.00 |
November | 0.104821E+10 | 0.688349E+09 | 0.733746E+09 | 0.490890E+09 | 0.242857E+09 | 0.00 | 0.00 |
December | 0.108339E+10 | 0.954445E+09 | 0.801172E+09 | 0.565893E+09 | 0.235279E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.128968E+11 | 0.512641E+10 | 0.678625E+10 | 0.306061E+10 | 0.372564E+10 | 0.00 | 0.00 |
Minimum of Months | 0.642760E+09 | 47194561.41 | 0.399265E+09 | 40435810.09 | 0.235279E+09 | 0.00 | 0.00 |
Maximum of Months | 0.129521E+10 | 0.954445E+09 | 0.860015E+09 | 0.612730E+09 | 0.377160E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.115965E+10 | 0.606055E+09 | 0.782721E+09 | 0.565485E+09 | 0.217236E+09 | 0.00 | 0.00 |
February | 0.621346E+09 | 0.531300E+09 | 0.498285E+09 | 0.287991E+09 | 0.210294E+09 | 0.00 | 0.00 |
March | 0.847669E+09 | 0.521973E+09 | 0.593196E+09 | 0.290214E+09 | 0.302982E+09 | 0.00 | 0.00 |
April | 0.135896E+10 | 0.227855E+09 | 0.734505E+09 | 0.388376E+09 | 0.346129E+09 | 0.00 | 0.00 |
May | 0.141666E+10 | 0.137935E+09 | 0.694431E+09 | 0.337345E+09 | 0.357087E+09 | 0.00 | 0.00 |
June | 0.169198E+10 | 32510972.25 | 0.684686E+09 | 0.346412E+09 | 0.338274E+09 | 0.00 | 0.00 |
July | 0.146067E+10 | 21855882.73 | 0.547106E+09 | 0.212292E+09 | 0.334813E+09 | 0.00 | 0.00 |
August | 0.142771E+10 | 24310540.03 | 0.555835E+09 | 0.248047E+09 | 0.307788E+09 | 0.00 | 0.00 |
September | 0.126798E+10 | 41314142.78 | 0.543814E+09 | 0.229081E+09 | 0.314733E+09 | 0.00 | 0.00 |
October | 0.120164E+10 | 0.318932E+09 | 0.694021E+09 | 0.436513E+09 | 0.257508E+09 | 0.00 | 0.00 |
November | 0.101791E+10 | 0.517089E+09 | 0.696397E+09 | 0.480919E+09 | 0.215478E+09 | 0.00 | 0.00 |
December | 0.934279E+09 | 0.749427E+09 | 0.683759E+09 | 0.480526E+09 | 0.203233E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.144065E+11 | 0.373056E+10 | 0.770875E+10 | 0.430320E+10 | 0.340555E+10 | 0.00 | 0.00 |
Minimum of Months | 0.621346E+09 | 21855882.73 | 0.498285E+09 | 0.212292E+09 | 0.203233E+09 | 0.00 | 0.00 |
Maximum of Months | 0.169198E+10 | 0.749427E+09 | 0.782721E+09 | 0.565485E+09 | 0.357087E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.562180E+09 | 0.635868E+09 | 0.393828E+09 | 0.211926E+09 | 0.181903E+09 | 0.00 | 0.00 |
February | 0.327223E+09 | 0.547528E+09 | 0.304099E+09 | 0.120775E+09 | 0.183324E+09 | 0.00 | 0.00 |
March | 0.593283E+09 | 0.536493E+09 | 0.445884E+09 | 0.174376E+09 | 0.271508E+09 | 0.00 | 0.00 |
April | 0.115222E+10 | 0.231459E+09 | 0.636687E+09 | 0.309812E+09 | 0.326875E+09 | 0.00 | 0.00 |
May | 0.135575E+10 | 0.130212E+09 | 0.677152E+09 | 0.323940E+09 | 0.353213E+09 | 0.00 | 0.00 |
June | 0.171654E+10 | 29922445.17 | 0.705388E+09 | 0.361882E+09 | 0.343505E+09 | 0.00 | 0.00 |
July | 0.145235E+10 | 20712081.66 | 0.547489E+09 | 0.213756E+09 | 0.333733E+09 | 0.00 | 0.00 |
August | 0.131583E+10 | 25983828.68 | 0.506479E+09 | 0.210280E+09 | 0.296199E+09 | 0.00 | 0.00 |
September | 0.105325E+10 | 44104597.23 | 0.433071E+09 | 0.146521E+09 | 0.286550E+09 | 0.00 | 0.00 |
October | 0.770105E+09 | 0.337119E+09 | 0.437501E+09 | 0.212073E+09 | 0.225428E+09 | 0.00 | 0.00 |
November | 0.530450E+09 | 0.544895E+09 | 0.382175E+09 | 0.197665E+09 | 0.184511E+09 | 0.00 | 0.00 |
December | 0.399333E+09 | 0.782504E+09 | 0.321745E+09 | 0.153993E+09 | 0.167752E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.112285E+11 | 0.386680E+10 | 0.579150E+10 | 0.263700E+10 | 0.315450E+10 | 0.00 | 0.00 |
Minimum of Months | 0.327223E+09 | 20712081.66 | 0.304099E+09 | 0.120775E+09 | 0.167752E+09 | 0.00 | 0.00 |
Maximum of Months | 0.171654E+10 | 0.782504E+09 | 0.705388E+09 | 0.361882E+09 | 0.353213E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.996054E+09 | 0.313434E+09 | 0.649066E+09 | 0.518528E+09 | 0.130538E+09 | 0.00 | 0.00 |
February | 0.499670E+09 | 0.277759E+09 | 0.365808E+09 | 0.245238E+09 | 0.120570E+09 | 0.00 | 0.00 |
March | 0.502568E+09 | 0.271700E+09 | 0.335275E+09 | 0.169892E+09 | 0.165382E+09 | 0.00 | 0.00 |
April | 0.583979E+09 | 0.113639E+09 | 0.284767E+09 | 0.117303E+09 | 0.167464E+09 | 0.00 | 0.00 |
May | 0.486737E+09 | 66571659.71 | 0.196619E+09 | 34202726.45 | 0.162417E+09 | 0.00 | 0.00 |
June | 0.573334E+09 | 14096348.67 | 0.161060E+09 | 12287840.18 | 0.148772E+09 | 0.00 | 0.00 |
July | 0.583899E+09 | 10030816.52 | 0.168647E+09 | 16034777.14 | 0.152612E+09 | 0.00 | 0.00 |
August | 0.637037E+09 | 11283952.84 | 0.208539E+09 | 58731992.40 | 0.149807E+09 | 0.00 | 0.00 |
September | 0.692753E+09 | 19720269.55 | 0.286666E+09 | 0.121159E+09 | 0.165506E+09 | 0.00 | 0.00 |
October | 0.831307E+09 | 0.162313E+09 | 0.475485E+09 | 0.329163E+09 | 0.146322E+09 | 0.00 | 0.00 |
November | 0.821919E+09 | 0.266725E+09 | 0.540882E+09 | 0.415420E+09 | 0.125462E+09 | 0.00 | 0.00 |
December | 0.885263E+09 | 0.390140E+09 | 0.604458E+09 | 0.478892E+09 | 0.125566E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.809452E+10 | 0.191741E+10 | 0.427727E+10 | 0.251685E+10 | 0.176042E+10 | 0.00 | 0.00 |
Minimum of Months | 0.486737E+09 | 10030816.52 | 0.161060E+09 | 12287840.18 | 0.120570E+09 | 0.00 | 0.00 |
Maximum of Months | 0.996054E+09 | 0.390140E+09 | 0.649066E+09 | 0.518528E+09 | 0.167464E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.232634E+09 | 0.201597E+10 | 0.375704E+09 | 0.00 | 0.375704E+09 | 0.00 | 0.00 |
February | 0.122425E+09 | 0.186136E+10 | 0.386675E+09 | 0.00 | 0.386675E+09 | 0.00 | 0.00 |
March | 0.457352E+09 | 0.174005E+10 | 0.569049E+09 | 22512.27 | 0.569026E+09 | 0.00 | 0.00 |
April | 0.116356E+10 | 0.783584E+09 | 0.674430E+09 | 9930025.34 | 0.664500E+09 | 0.00 | 0.00 |
May | 0.170077E+10 | 0.487707E+09 | 0.817473E+09 | 69412938.91 | 0.748060E+09 | 0.00 | 0.00 |
June | 0.263790E+10 | 0.158903E+09 | 0.913609E+09 | 0.166932E+09 | 0.746677E+09 | 0.00 | 0.00 |
July | 0.236033E+10 | 0.121294E+09 | 0.807597E+09 | 86776906.14 | 0.720820E+09 | 0.00 | 0.00 |
August | 0.192691E+10 | 0.169515E+09 | 0.649832E+09 | 15955234.21 | 0.633877E+09 | 0.00 | 0.00 |
September | 0.153625E+10 | 0.264719E+09 | 0.593020E+09 | 367012.78 | 0.592653E+09 | 0.00 | 0.00 |
October | 0.712717E+09 | 0.114277E+10 | 0.473813E+09 | 0.00 | 0.473813E+09 | 0.00 | 0.00 |
November | 0.239134E+09 | 0.177284E+10 | 0.382039E+09 | 0.00 | 0.382039E+09 | 0.00 | 0.00 |
December | 0.117218E+09 | 0.247723E+10 | 0.350942E+09 | 0.00 | 0.350942E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.132072E+11 | 0.129959E+11 | 0.699418E+10 | 0.349397E+09 | 0.664479E+10 | 0.00 | 0.00 |
Minimum of Months | 0.117218E+09 | 0.121294E+09 | 0.350942E+09 | 0.00 | 0.350942E+09 | 0.00 | 0.00 |
Maximum of Months | 0.263790E+10 | 0.247723E+10 | 0.913609E+09 | 0.166932E+09 | 0.748060E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.209979E+09 | 0.206884E+10 | 0.375704E+09 | 0.00 | 0.375704E+09 | 0.00 | 0.00 |
February | 0.105832E+09 | 0.192351E+10 | 0.386675E+09 | 0.00 | 0.386675E+09 | 0.00 | 0.00 |
March | 0.427713E+09 | 0.178925E+10 | 0.569049E+09 | 22512.27 | 0.569026E+09 | 0.00 | 0.00 |
April | 0.113843E+10 | 0.805800E+09 | 0.674430E+09 | 9930025.34 | 0.664500E+09 | 0.00 | 0.00 |
May | 0.167346E+10 | 0.502858E+09 | 0.817473E+09 | 69412938.91 | 0.748060E+09 | 0.00 | 0.00 |
June | 0.260793E+10 | 0.166009E+09 | 0.913609E+09 | 0.166932E+09 | 0.746677E+09 | 0.00 | 0.00 |
July | 0.232909E+10 | 0.128395E+09 | 0.807597E+09 | 86776906.14 | 0.720820E+09 | 0.00 | 0.00 |
August | 0.189838E+10 | 0.179902E+09 | 0.649832E+09 | 15955234.21 | 0.633877E+09 | 0.00 | 0.00 |
September | 0.151126E+10 | 0.278585E+09 | 0.593020E+09 | 367012.78 | 0.592653E+09 | 0.00 | 0.00 |
October | 0.689495E+09 | 0.117568E+10 | 0.473813E+09 | 0.00 | 0.473813E+09 | 0.00 | 0.00 |
November | 0.218606E+09 | 0.182289E+10 | 0.382039E+09 | 0.00 | 0.382039E+09 | 0.00 | 0.00 |
December | 0.101048E+09 | 0.254638E+10 | 0.350942E+09 | 0.00 | 0.350942E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.129112E+11 | 0.133881E+11 | 0.699418E+10 | 0.349397E+09 | 0.664479E+10 | 0.00 | 0.00 |
Minimum of Months | 0.101048E+09 | 0.128395E+09 | 0.350942E+09 | 0.00 | 0.350942E+09 | 0.00 | 0.00 |
Maximum of Months | 0.260793E+10 | 0.254638E+10 | 0.913609E+09 | 0.166932E+09 | 0.748060E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.155457E+10 | 0.147865E+10 | 0.114407E+10 | 0.760168E+09 | 0.383905E+09 | 0.00 | 0.00 |
February | 0.991931E+09 | 0.137861E+10 | 0.886328E+09 | 0.501877E+09 | 0.384451E+09 | 0.00 | 0.00 |
March | 0.145123E+10 | 0.132310E+10 | 0.110956E+10 | 0.527249E+09 | 0.582308E+09 | 0.00 | 0.00 |
April | 0.255128E+10 | 0.647394E+09 | 0.139330E+10 | 0.738458E+09 | 0.654838E+09 | 0.00 | 0.00 |
May | 0.289165E+10 | 0.461047E+09 | 0.143380E+10 | 0.735158E+09 | 0.698645E+09 | 0.00 | 0.00 |
June | 0.348260E+10 | 0.182206E+09 | 0.143145E+10 | 0.772218E+09 | 0.659232E+09 | 0.00 | 0.00 |
July | 0.315314E+10 | 0.146483E+09 | 0.127145E+10 | 0.610754E+09 | 0.660695E+09 | 0.00 | 0.00 |
August | 0.299002E+10 | 0.194561E+09 | 0.122397E+10 | 0.607340E+09 | 0.616627E+09 | 0.00 | 0.00 |
September | 0.245146E+10 | 0.265196E+09 | 0.106442E+10 | 0.460908E+09 | 0.603516E+09 | 0.00 | 0.00 |
October | 0.205735E+10 | 0.886397E+09 | 0.120514E+10 | 0.719123E+09 | 0.486021E+09 | 0.00 | 0.00 |
November | 0.136833E+10 | 0.130985E+10 | 0.102901E+10 | 0.646691E+09 | 0.382315E+09 | 0.00 | 0.00 |
December | 0.123887E+10 | 0.176541E+10 | 0.103393E+10 | 0.672254E+09 | 0.361677E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.261824E+11 | 0.100389E+11 | 0.142264E+11 | 0.775220E+10 | 0.647423E+10 | 0.00 | 0.00 |
Minimum of Months | 0.991931E+09 | 0.146483E+09 | 0.886328E+09 | 0.460908E+09 | 0.361677E+09 | 0.00 | 0.00 |
Maximum of Months | 0.348260E+10 | 0.176541E+10 | 0.143380E+10 | 0.772218E+09 | 0.698645E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.261930E+10 | 0.140002E+10 | 0.178102E+10 | 0.131994E+10 | 0.461083E+09 | 0.00 | 0.00 |
February | 0.132006E+10 | 0.123966E+10 | 0.106374E+10 | 0.624266E+09 | 0.439472E+09 | 0.00 | 0.00 |
March | 0.147007E+10 | 0.125054E+10 | 0.104853E+10 | 0.432478E+09 | 0.616053E+09 | 0.00 | 0.00 |
April | 0.184494E+10 | 0.627909E+09 | 0.956085E+09 | 0.302004E+09 | 0.654081E+09 | 0.00 | 0.00 |
May | 0.172264E+10 | 0.410299E+09 | 0.780737E+09 | 0.110860E+09 | 0.669877E+09 | 0.00 | 0.00 |
June | 0.220235E+10 | 0.128417E+09 | 0.723175E+09 | 88503980.79 | 0.634671E+09 | 0.00 | 0.00 |
July | 0.211424E+10 | 94199378.42 | 0.706145E+09 | 70564670.40 | 0.635580E+09 | 0.00 | 0.00 |
August | 0.212984E+10 | 0.128860E+09 | 0.753612E+09 | 0.154975E+09 | 0.598637E+09 | 0.00 | 0.00 |
September | 0.217794E+10 | 0.201332E+09 | 0.933011E+09 | 0.308543E+09 | 0.624468E+09 | 0.00 | 0.00 |
October | 0.233008E+10 | 0.826948E+09 | 0.137280E+10 | 0.837901E+09 | 0.534895E+09 | 0.00 | 0.00 |
November | 0.216943E+10 | 0.121826E+10 | 0.150781E+10 | 0.105747E+10 | 0.450334E+09 | 0.00 | 0.00 |
December | 0.228616E+10 | 0.168807E+10 | 0.165898E+10 | 0.121905E+10 | 0.439939E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.243870E+11 | 0.921452E+10 | 0.132856E+11 | 0.652656E+10 | 0.675909E+10 | 0.00 | 0.00 |
Minimum of Months | 0.132006E+10 | 94199378.42 | 0.706145E+09 | 70564670.40 | 0.439472E+09 | 0.00 | 0.00 |
Maximum of Months | 0.261930E+10 | 0.168807E+10 | 0.178102E+10 | 0.131994E+10 | 0.669877E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 14.83 | 7.47 | -0.8 | 2.99 | -0.8 | 34.08 | 283.26 | 0.00 |
February | 12.72 | 9.35 | 6.24 | 2.64 | 2.53 | 52.02 | 191.85 | 0.02 |
March | 15.42 | 8.67 | 1.96 | 3.53 | 3.02 | 74.19 | 207.67 | 0.01 |
April | 23.31 | 10.14 | -4.1 | 3.42 | 6.81 | 72.47 | 350.22 | 0.00 |
May | 26.31 | 11.07 | -4.9 | 3.62 | 8.60 | 75.22 | 359.64 | 0.00 |
June | 31.20 | 14.28 | 0.18 | 3.69 | 15.53 | 67.31 | 396.02 | 0.00 |
July | 30.42 | 17.99 | 9.86 | 3.72 | 19.28 | 82.46 | 278.62 | 0.02 |
August | 29.82 | 18.15 | 11.14 | 3.33 | 18.26 | 71.82 | 270.19 | 0.02 |
September | 27.75 | 17.59 | 11.45 | 3.72 | 17.29 | 82.54 | 200.28 | 0.01 |
October | 20.87 | 10.99 | 1.63 | 3.42 | 6.03 | 49.01 | 269.00 | 0.00 |
November | 15.43 | 8.80 | 1.49 | 3.02 | 1.83 | 40.49 | 251.35 | 0.01 |
December | 11.86 | 4.25 | -5.9 | 2.21 | -4.3 | 34.74 | 244.35 | 0.00 |
Annual Sum or Average | 21.70 | 11.57 | 2.33 | 3.28 | 7.86 | 61.39 | 275.62 | 0.01 |
Minimum of Months | 11.86 | 4.25 | -5.9 | 2.21 | -4.3 | 34.08 | 191.85 | 0.00 |
Maximum of Months | 31.20 | 18.15 | 11.45 | 3.72 | 19.28 | 82.54 | 396.02 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 29.00 | 31-JAN-15:00 | 10.73 | -14.0 | 2.10 | 7.75 | 109.00 | 697.00 |
February | 22.00 | 18-FEB-14:09 | 14.42 | 9.67 | 5.20 | 14.10 | 264.00 | 225.33 |
March | 28.80 | 16-MAR-15:20 | 13.79 | 1.47 | 3.77 | 14.35 | 156.17 | 666.17 |
April | 35.00 | 14-APR-14:00 | 14.57 | -4.0 | 1.50 | 19.70 | 150.00 | 819.50 |
May | 37.00 | 15-MAY-16:00 | 15.57 | -2.0 | 4.60 | 20.75 | 127.50 | 679.00 |
June | 42.00 | 16-JUN-15:00 | 16.74 | -5.0 | 5.70 | 25.49 | 135.00 | 753.50 |
July | 40.00 | 12-JUL-13:00 | 19.40 | 7.00 | 2.10 | 27.95 | 147.00 | 3.00 |
August | 41.00 | 25-AUG-14:09 | 17.27 | -0.7 | 3.43 | 25.74 | 162.33 | 768.67 |
September | 38.30 | 08-SEP-14:00 | 19.81 | 10.00 | 3.00 | 25.82 | 142.00 | 699.00 |
October | 37.00 | 01-OCT-12:00 | 19.01 | 9.00 | 4.10 | 27.14 | 262.50 | 136.00 |
November | 29.00 | 01-NOV-14:00 | 16.20 | 8.00 | 2.60 | 16.49 | 73.50 | 907.50 |
December | 26.00 | 21-DEC-14:00 | 10.90 | -5.0 | 2.60 | 7.35 | 68.50 | 756.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 22.00 | 10.73 | -14.0 | 1.50 | 7.35 | 68.50 | 3.00 | |
Maximum of Months | 42.00 | 19.81 | 10.00 | 5.70 | 27.95 | 264.00 | 907.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 0.50 | 01-JAN-07:00 | -1.2 | -3.3 | 3.30 | -16.2 | 17.50 | 352.00 |
February | 5.00 | 01-FEB-04:00 | 3.59 | 2.00 | 3.10 | -10.7 | 0.00 | 0.00 |
March | 0.50 | 26-MAR-03:00 | -2.4 | -6.7 | 2.50 | -17.0 | 0.00 | 0.00 |
April | 8.00 | 21-APR-03:00 | 0.42 | -14.0 | 1.00 | -11.7 | 0.00 | 0.00 |
May | 12.00 | 01-MAY-03:00 | 3.97 | -7.0 | 2.60 | -6.2 | 0.00 | 0.00 |
June | 18.00 | 21-JUN-04:00 | 8.24 | -2.0 | 1.50 | 3.48 | 0.00 | 0.00 |
July | 18.00 | 01-JUL-05:00 | 6.53 | -9.0 | 3.10 | -1.2 | 16.00 | 325.00 |
August | 17.00 | 05-AUG-17:00 | 15.02 | 14.00 | 5.70 | 11.46 | 29.00 | 0.00 |
September | 16.60 | 22-SEP-05:00 | 13.83 | 12.20 | 3.00 | 4.92 | 0.00 | 0.00 |
October | 5.00 | 25-OCT-05:00 | 0.48 | -6.0 | 3.10 | -12.7 | 0.00 | 0.00 |
November | 0.00 | 23-NOV-05:00 | -2.5 | -6.0 | 2.10 | -17.3 | 0.00 | 0.00 |
December | -1.1 | 07-DEC-04:00 | -5.6 | -16.0 | 3.10 | -20.8 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -1.1 | -5.6 | -16.0 | 1.00 | -20.8 | 0.00 | 0.00 | |
Maximum of Months | 18.00 | 15.02 | 14.00 | 5.70 | 11.46 | 29.00 | 352.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.66 | 08-JAN-15:00 | 18.00 | 16.00 | 4.60 | 11.46 | 102.00 | 332.00 |
February | 14.73 | 18-FEB-17:00 | 16.00 | 14.00 | 6.20 | 10.50 | 0.00 | 0.00 |
March | 15.18 | 17-MAR-10:00 | 25.50 | 8.30 | 2.50 | 18.46 | 167.50 | 459.00 |
April | 15.71 | 11-APR-14:00 | 33.00 | 3.00 | 2.10 | 15.94 | 178.50 | 758.00 |
May | 15.57 | 15-MAY-16:00 | 37.00 | -2.0 | 4.60 | 20.75 | 127.50 | 679.00 |
June | 23.18 | 17-JUN-15:00 | 41.00 | 16.00 | 3.60 | 31.13 | 257.00 | 9.00 |
July | 23.11 | 13-JUL-17:00 | 26.00 | 22.00 | 4.60 | 22.13 | 79.00 | 56.50 |
August | 22.19 | 16-AUG-10:00 | 35.00 | 17.00 | 2.10 | 24.33 | 140.50 | 837.00 |
September | 22.23 | 01-SEP-11:00 | 34.40 | 17.20 | 4.60 | 23.82 | 193.50 | 725.50 |
October | 21.53 | 01-OCT-17:00 | 32.00 | 17.00 | 2.10 | 25.33 | 30.50 | 1.50 |
November | 18.59 | 12-NOV-14:00 | 20.00 | 18.00 | 3.10 | 15.39 | 115.00 | 0.00 |
December | 12.06 | 12-DEC-12:00 | 20.00 | 6.00 | 1.50 | 12.60 | 182.50 | 6.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 12.06 | 16.00 | -2.0 | 1.50 | 10.50 | 0.00 | 0.00 | |
Maximum of Months | 23.18 | 41.00 | 22.00 | 6.20 | 31.13 | 257.00 | 837.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.00 | 08-JAN-15:00 | 18.00 | 16.66 | 4.60 | 11.46 | 102.00 | 332.00 |
February | 14.00 | 18-FEB-17:00 | 16.00 | 14.73 | 6.20 | 10.50 | 0.00 | 0.00 |
March | 13.30 | 06-MAR-10:00 | 14.40 | 13.70 | 6.10 | 10.69 | 254.50 | 82.00 |
April | 8.00 | 15-APR-20:00 | 23.00 | 14.00 | 6.20 | 7.75 | 0.00 | 0.00 |
May | 9.00 | 26-MAY-02:00 | 21.00 | 13.75 | 3.60 | 16.30 | 0.00 | 0.00 |
June | 16.00 | 17-JUN-15:00 | 41.00 | 23.18 | 3.60 | 31.13 | 257.00 | 9.00 |
July | 22.00 | 13-JUL-17:00 | 26.00 | 23.11 | 4.60 | 22.13 | 79.00 | 56.50 |
August | 20.00 | 09-AUG-17:00 | 25.00 | 21.44 | 5.10 | 19.17 | 35.00 | 0.00 |
September | 20.50 | 02-SEP-22:10 | 22.62 | 21.05 | 3.18 | 20.17 | 0.00 | 0.00 |
October | 19.00 | 03-OCT-02:00 | 23.00 | 20.15 | 2.10 | 10.30 | 0.00 | 0.00 |
November | 18.00 | 12-NOV-14:00 | 20.00 | 18.59 | 3.10 | 15.39 | 115.00 | 0.00 |
December | 10.00 | 12-DEC-23:00 | 12.00 | 10.87 | 1.50 | 7.55 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 8.00 | 12.00 | 10.87 | 1.50 | 7.55 | 0.00 | 0.00 | |
Maximum of Months | 22.00 | 41.00 | 23.18 | 6.20 | 31.13 | 257.00 | 332.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 18.65 | 31.23 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 19.06 | 29.93 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 20.99 | 39.76 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 24.03 | 60.89 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 27.32 | 65.75 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 29.99 | 69.24 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 31.31 | 56.42 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 30.91 | 52.05 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 28.91 | 42.71 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 25.85 | 39.20 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 22.56 | 30.64 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 19.93 | 27.41 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 24.99 | 45.50 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 18.65 | 27.41 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 31.31 | 69.24 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH LAUNDRY G WATER HEATER
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.109321E+12 | -0.107562E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175870E+10 | 82.17 | 0.00 | 0.00 |
February | 0.981258E+11 | -0.965216E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.160424E+10 | 82.17 | 0.00 | 0.00 |
March | 0.105386E+12 | -0.103594E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.179295E+10 | 82.17 | 0.00 | 0.00 |
April | 0.970057E+11 | -0.952798E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.172586E+10 | 82.17 | 0.00 | 0.00 |
May | 0.946690E+11 | -0.928767E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.179229E+10 | 82.17 | 0.00 | 0.00 |
June | 0.872312E+11 | -0.855049E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.172631E+10 | 82.17 | 0.00 | 0.00 |
July | 0.878837E+11 | -0.861246E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175904E+10 | 82.17 | 0.00 | 0.00 |
August | 0.885588E+11 | -0.868030E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175574E+10 | 82.17 | 0.00 | 0.00 |
September | 0.889753E+11 | -0.872783E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.169702E+10 | 82.17 | 0.00 | 0.00 |
October | 0.971210E+11 | -0.953675E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175355E+10 | 82.17 | 0.00 | 0.00 |
November | 0.993786E+11 | -0.976816E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.169693E+10 | 82.17 | 0.00 | 0.00 |
December | 0.107149E+12 | -0.105395E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175371E+10 | 82.17 | 0.00 | 0.00 |
Annual Sum or Average | 0.116081E+13 | -0.113999E+13 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.208164E+11 | 82.17 | 0.00 | 0.00 |
Minimum of Months | 0.872312E+11 | -0.107562E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.179295E+10 | 82.17 | 0.00 | 0.00 |
Maximum of Months | 0.109321E+12 | -0.855049E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.160424E+10 | 82.17 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.804731E+10 | -0.788296E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164352858.0 | 82.17 | 0.00 | 0.00 |
February | 0.727181E+10 | -0.712336E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -148449034.3 | 82.17 | 0.00 | 0.00 |
March | 0.804586E+10 | -0.788155E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164308478.3 | 82.17 | 0.00 | 0.00 |
April | 0.779705E+10 | -0.763820E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -158850385.6 | 82.17 | 0.00 | 0.00 |
May | 0.804708E+10 | -0.788296E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164116966.8 | 82.17 | 0.00 | 0.00 |
June | 0.778857E+10 | -0.762976E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -158811816.9 | 82.17 | 0.00 | 0.00 |
July | 0.805551E+10 | -0.789140E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164104005.8 | 82.17 | 0.00 | 0.00 |
August | 0.804707E+10 | -0.788296E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164104188.4 | 82.17 | 0.00 | 0.00 |
September | 0.779842E+10 | -0.763961E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -158811495.3 | 82.17 | 0.00 | 0.00 |
October | 0.804575E+10 | -0.788156E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164194739.5 | 82.17 | 0.00 | 0.00 |
November | 0.778033E+10 | -0.762132E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -159011555.2 | 82.17 | 0.00 | 0.00 |
December | 0.805586E+10 | -0.789140E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164459547.4 | 82.17 | 0.00 | 0.00 |
Annual Sum or Average | 0.947806E+11 | -0.928471E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.193358E+10 | 82.17 | 0.00 | 0.00 |
Minimum of Months | 0.727181E+10 | -0.789140E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -164459547.4 | 82.17 | 0.00 | 0.00 |
Maximum of Months | 0.805586E+10 | -0.712336E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -148449034.3 | 82.17 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.619302E+11 | -0.604165E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.151369E+10 | 60.05 | 0.00 | 0.00 |
February | 0.554247E+11 | -0.540357E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.138901E+10 | 60.05 | 0.00 | 0.00 |
March | 0.586022E+11 | -0.570410E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.156117E+10 | 60.05 | 0.00 | 0.00 |
April | 0.523744E+11 | -0.508765E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.149798E+10 | 60.05 | 0.00 | 0.00 |
May | 0.493219E+11 | -0.477617E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.156025E+10 | 60.05 | 0.00 | 0.00 |
June | 0.439557E+11 | -0.424571E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.149860E+10 | 60.05 | 0.00 | 0.00 |
July | 0.434191E+11 | -0.419050E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.151415E+10 | 60.05 | 0.00 | 0.00 |
August | 0.440439E+11 | -0.425343E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.150958E+10 | 60.05 | 0.00 | 0.00 |
September | 0.454278E+11 | -0.439698E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.145800E+10 | 60.05 | 0.00 | 0.00 |
October | 0.513915E+11 | -0.498849E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.150655E+10 | 60.05 | 0.00 | 0.00 |
November | 0.543871E+11 | -0.529292E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.145788E+10 | 60.05 | 0.00 | 0.00 |
December | 0.600481E+11 | -0.585413E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.150677E+10 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.620327E+12 | -0.602353E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.179736E+11 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.434191E+11 | -0.604165E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.156117E+10 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.619302E+11 | -0.419050E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.138901E+10 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: LOBBY_FLR_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.87 | 0.86 | 01-JAN-07:00 | 8303.49 | 39.08 | 307.00 | 292.67 | 1154.85 | 28.03 | 189.17 | 287.50 |
February | 241.00 | 0.87 | 0.86 | 01-FEB-07:49 | 4813.81 | 32.61 | 187.33 | 267.33 | 592.11 | 23.38 | 134.33 | 205.83 |
March | 344.33 | 0.88 | 0.86 | 01-MAR-07:00 | 1114.22 | 19.69 | 11.50 | 326.67 | 422.82 | 21.05 | 162.83 | 258.17 |
April | 380.33 | 0.88 | 0.86 | 01-APR-08:50 | 772.00 | 19.30 | 0.00 | 333.17 | 336.58 | 21.05 | 183.00 | 267.33 |
May | 403.17 | 0.88 | 0.86 | 01-MAY-08:09 | 622.65 | 19.09 | 0.00 | 359.67 | 275.63 | 20.87 | 100.83 | 235.67 |
June | 418.17 | 0.89 | 0.86 | 01-JUN-08:20 | 503.83 | 18.46 | 0.00 | 361.33 | 229.43 | 20.28 | 29.00 | 129.50 |
July | 399.50 | 0.88 | 0.86 | 01-JUL-09:30 | 620.48 | 18.53 | 0.00 | 362.67 | 264.72 | 20.32 | 90.00 | 195.83 |
August | 361.83 | 0.88 | 0.86 | 01-AUG-08:50 | 691.97 | 18.90 | 0.00 | 340.33 | 294.45 | 20.66 | 96.33 | 212.83 |
September | 350.17 | 0.88 | 0.86 | 01-SEP-07:30 | 1020.11 | 19.22 | 0.50 | 322.00 | 409.17 | 20.97 | 176.33 | 265.00 |
October | 348.00 | 0.87 | 0.86 | 01-OCT-07:49 | 2798.30 | 25.74 | 135.33 | 321.00 | 455.52 | 21.69 | 142.83 | 273.67 |
November | 288.50 | 0.87 | 0.86 | 01-NOV-08:09 | 7916.24 | 37.84 | 282.83 | 287.00 | 904.39 | 26.57 | 167.83 | 264.67 |
December | 290.67 | 0.87 | 0.86 | 01-DEC-07:40 | 7638.18 | 38.90 | 287.83 | 280.83 | 1321.43 | 28.77 | 185.33 | 273.33 |
Annual Sum or Average | 4135.50 | 0.88 | 2709.49 | 24.58 | 1212.33 | 3854.67 | 517.54 | 22.48 | 1657.83 | 2869.33 | ||
Minimum of Months | 241.00 | 0.87 | 0.86 | 503.83 | 18.46 | 0.00 | 267.33 | 229.43 | 20.28 | 29.00 | 129.50 | |
Maximum of Months | 418.17 | 0.89 | 0.86 | 8303.49 | 39.08 | 307.00 | 362.67 | 1321.43 | 28.77 | 189.17 | 287.50 |
Report: DaylightingReportMonthly
For: CAFE_FLR_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.26 | 0.22 | 01-JAN-07:49 | 8767.75 | 39.13 | 307.00 | 295.17 | 1616.31 | 27.50 | 165.00 | 292.67 |
February | 241.00 | 0.26 | 0.22 | 01-FEB-07:49 | 5159.06 | 32.56 | 187.67 | 273.17 | 936.90 | 23.24 | 132.00 | 249.00 |
March | 344.33 | 0.28 | 0.22 | 01-MAR-07:30 | 1351.04 | 20.13 | 23.50 | 338.67 | 660.27 | 21.32 | 186.83 | 306.83 |
April | 380.33 | 0.29 | 0.22 | 01-APR-07:30 | 967.61 | 19.83 | 22.67 | 345.00 | 531.77 | 21.38 | 219.33 | 321.00 |
May | 403.17 | 0.28 | 0.22 | 01-MAY-07:10 | 762.05 | 19.86 | 0.33 | 378.00 | 414.67 | 21.41 | 235.17 | 342.17 |
June | 418.17 | 0.29 | 0.22 | 01-JUN-06:00 | 619.25 | 19.33 | 0.00 | 383.33 | 344.55 | 20.92 | 140.67 | 345.33 |
July | 399.50 | 0.29 | 0.22 | 01-JUL-07:19 | 742.53 | 19.40 | 0.50 | 386.50 | 386.40 | 20.95 | 177.83 | 335.50 |
August | 361.83 | 0.28 | 0.22 | 01-AUG-07:40 | 846.46 | 19.63 | 2.17 | 355.67 | 448.53 | 21.17 | 172.83 | 315.17 |
September | 350.17 | 0.28 | 0.22 | 01-SEP-06:00 | 1229.75 | 19.79 | 24.33 | 332.33 | 618.23 | 21.34 | 206.67 | 305.17 |
October | 348.00 | 0.27 | 0.22 | 01-OCT-07:19 | 3119.56 | 25.77 | 140.17 | 326.50 | 775.82 | 21.62 | 140.33 | 308.67 |
November | 288.50 | 0.25 | 0.22 | 01-NOV-07:40 | 8331.06 | 37.91 | 283.33 | 292.50 | 1319.63 | 26.16 | 148.67 | 279.83 |
December | 290.67 | 0.24 | 0.22 | 01-DEC-07:30 | 8096.77 | 38.96 | 287.83 | 285.33 | 1778.08 | 28.28 | 168.33 | 278.00 |
Annual Sum or Average | 4135.50 | 0.27 | 2958.63 | 25.04 | 1279.50 | 3992.17 | 766.08 | 22.67 | 2093.67 | 3679.33 | ||
Minimum of Months | 241.00 | 0.24 | 0.22 | 619.25 | 19.33 | 0.00 | 273.17 | 344.55 | 20.92 | 132.00 | 249.00 | |
Maximum of Months | 418.17 | 0.29 | 0.22 | 8767.75 | 39.13 | 307.00 | 386.50 | 1778.08 | 28.28 | 235.17 | 345.33 |
Report: DaylightingReportMonthly
For: DINING_FLR_6_DAYLCTRL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.73 | 0.60 | 01-JAN-11:50 | 266.73 | 13.67 | 0.00 | 219.17 | 147.98 | 17.31 | 0.00 | 34.67 |
February | 241.00 | 0.71 | 0.60 | 02-FEB-14:00 | 347.56 | 14.56 | 0.00 | 223.00 | 173.80 | 17.97 | 0.00 | 88.50 |
March | 344.33 | 0.67 | 0.60 | 01-MAR-08:20 | 409.52 | 15.79 | 0.00 | 314.67 | 197.02 | 19.05 | 0.00 | 174.67 |
April | 380.33 | 0.65 | 0.60 | 01-APR-09:20 | 459.69 | 16.79 | 0.00 | 344.00 | 234.93 | 20.05 | 24.83 | 265.83 |
May | 403.17 | 0.62 | 0.60 | 01-MAY-06:10 | 574.19 | 18.43 | 23.67 | 392.67 | 299.59 | 22.01 | 93.33 | 360.50 |
June | 418.17 | 0.62 | 0.60 | 01-JUN-05:49 | 612.57 | 19.73 | 60.67 | 401.67 | 334.59 | 23.56 | 132.00 | 372.83 |
July | 399.50 | 0.62 | 0.60 | 01-JUL-05:49 | 595.61 | 19.20 | 48.00 | 401.17 | 308.99 | 23.02 | 116.67 | 330.83 |
August | 361.83 | 0.65 | 0.60 | 01-AUG-06:30 | 478.41 | 16.75 | 0.00 | 358.67 | 235.02 | 20.29 | 30.50 | 231.00 |
September | 350.17 | 0.65 | 0.60 | 01-SEP-07:10 | 474.65 | 16.29 | 0.00 | 325.83 | 224.71 | 19.50 | 1.83 | 227.83 |
October | 348.00 | 0.71 | 0.60 | 01-OCT-07:00 | 315.35 | 14.67 | 0.00 | 255.50 | 163.79 | 18.13 | 0.00 | 95.50 |
November | 288.50 | 0.72 | 0.60 | 01-NOV-08:50 | 298.70 | 14.24 | 0.00 | 235.17 | 156.71 | 17.83 | 0.00 | 46.83 |
December | 290.67 | 0.73 | 0.60 | 02-DEC-10:39 | 276.53 | 13.81 | 0.00 | 209.83 | 149.00 | 17.48 | 0.00 | 30.00 |
Annual Sum or Average | 4135.50 | 0.67 | 440.93 | 16.42 | 132.33 | 3681.33 | 226.89 | 19.95 | 399.17 | 2259.00 | ||
Minimum of Months | 241.00 | 0.62 | 0.60 | 266.73 | 13.67 | 0.00 | 209.83 | 147.98 | 17.31 | 0.00 | 30.00 | |
Maximum of Months | 418.17 | 0.73 | 0.60 | 612.57 | 19.73 | 60.67 | 401.67 | 334.59 | 23.56 | 132.00 | 372.83 |
Report: DaylightingReportMonthly
For: BANQUET_FLR_6_DAYLCTRL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.73 | 0.60 | 01-JAN-11:50 | 266.73 | 13.67 | 0.00 | 219.17 | 147.98 | 17.31 | 0.00 | 34.67 |
February | 241.00 | 0.71 | 0.60 | 02-FEB-14:00 | 347.56 | 14.56 | 0.00 | 223.00 | 173.80 | 17.97 | 0.00 | 88.50 |
March | 344.33 | 0.67 | 0.60 | 01-MAR-08:20 | 409.52 | 15.79 | 0.00 | 314.67 | 197.02 | 19.05 | 0.00 | 174.67 |
April | 380.33 | 0.65 | 0.60 | 01-APR-09:20 | 459.69 | 16.79 | 0.00 | 344.00 | 234.93 | 20.05 | 24.83 | 265.83 |
May | 403.17 | 0.62 | 0.60 | 01-MAY-06:10 | 574.19 | 18.43 | 23.67 | 392.67 | 299.59 | 22.01 | 93.33 | 360.50 |
June | 418.17 | 0.62 | 0.60 | 01-JUN-05:49 | 612.57 | 19.73 | 60.67 | 401.67 | 334.59 | 23.56 | 132.00 | 372.83 |
July | 399.50 | 0.62 | 0.60 | 01-JUL-05:49 | 595.61 | 19.20 | 48.00 | 401.17 | 308.99 | 23.02 | 116.67 | 330.83 |
August | 361.83 | 0.65 | 0.60 | 01-AUG-06:30 | 478.41 | 16.75 | 0.00 | 358.67 | 235.02 | 20.29 | 30.50 | 231.00 |
September | 350.17 | 0.65 | 0.60 | 01-SEP-07:10 | 474.65 | 16.29 | 0.00 | 325.83 | 224.71 | 19.50 | 1.83 | 227.83 |
October | 348.00 | 0.71 | 0.60 | 01-OCT-07:00 | 315.35 | 14.67 | 0.00 | 255.50 | 163.79 | 18.13 | 0.00 | 95.50 |
November | 288.50 | 0.72 | 0.60 | 01-NOV-08:50 | 298.70 | 14.24 | 0.00 | 235.17 | 156.71 | 17.83 | 0.00 | 46.83 |
December | 290.67 | 0.73 | 0.60 | 02-DEC-10:39 | 276.53 | 13.81 | 0.00 | 209.83 | 149.00 | 17.48 | 0.00 | 30.00 |
Annual Sum or Average | 4135.50 | 0.67 | 440.93 | 16.42 | 132.33 | 3681.33 | 226.89 | 19.95 | 399.17 | 2259.00 | ||
Minimum of Months | 241.00 | 0.62 | 0.60 | 266.73 | 13.67 | 0.00 | 209.83 | 147.98 | 17.31 | 0.00 | 30.00 | |
Maximum of Months | 418.17 | 0.73 | 0.60 | 612.57 | 19.73 | 60.67 | 401.67 | 334.59 | 23.56 | 132.00 | 372.83 |
Report: CoilReportMonthly
For: FLR_3_DOAS HEATING COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.523853E+11 | 127053.36 | 13-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.598013E+11 | 126811.15 | 02-FEB-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.415380E+11 | 130085.84 | 25-MAR-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.232458E+10 | 78536.48 | 21-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 22887272.29 | 6816.69 | 01-MAY-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.139957E+11 | 117791.82 | 25-OCT-07:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.364968E+11 | 127876.59 | 04-NOV-06:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.675204E+11 | 130085.84 | 30-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.274085E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.675204E+11 | 130085.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 29191698.11 | 745.36 | 01-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.241613E+09 | 884.67 | 13-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.160853E+09 | 1074.12 | 25-MAR-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 7887348.47 | 368.23 | 28-OCT-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 23247569.36 | 489.76 | 24-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.204379E+09 | 1084.51 | 16-DEC-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.667172E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.241613E+09 | 1084.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 4486557.76 | 218.89 | 02-JAN-11:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 666735.19 | 241.80 | 27-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8180117.41 | 295.28 | 07-DEC-11:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 13333410.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8180117.41 | 295.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 10059208.60 | 210.76 | 01-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 718823.55 | 117.18 | 13-FEB-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 3282249.32 | 206.36 | 27-MAR-10:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 26091950.25 | 213.07 | 07-DEC-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40152231.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26091950.25 | 213.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 18475785.99 | 1304.20 | 12-FEB-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 444402.31 | 714.37 | 27-MAR-08:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 18920188.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18475785.99 | 1304.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 109015.07 | 181.69 | 02-JAN-07:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 41630520.74 | 1980.73 | 12-FEB-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6764806.20 | 1578.46 | 18-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 48504342.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 41630520.74 | 1980.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 74946931.77 | 1928.77 | 01-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 89163914.79 | 1252.08 | 13-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 66272793.93 | 1471.19 | 27-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6534012.95 | 865.97 | 24-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.390213E+09 | 2409.36 | 07-DEC-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.627130E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.390213E+09 | 2409.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.195637E+09 | 4659.45 | 01-JAN-19:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.451251E+09 | 4659.45 | 02-FEB-19:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.290791E+09 | 4659.45 | 07-MAR-19:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5883051.52 | 4659.45 | 01-APR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 4108875.49 | 4659.45 | 17-MAY-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 558396.37 | 4590.08 | 14-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 3741982.56 | 4139.07 | 01-JUL-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 4767972.10 | 3805.63 | 30-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6713754.34 | 3865.29 | 03-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 38884953.34 | 4659.45 | 27-OCT-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.146527E+09 | 4659.45 | 06-NOV-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.721444E+09 | 4659.45 | 04-DEC-19:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.187031E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 558396.37 | 3805.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.721444E+09 | 4659.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.493359E+09 | 4664.00 | 01-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.749636E+09 | 4664.00 | 01-FEB-19:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.386956E+09 | 4664.00 | 26-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 9826281.15 | 4664.00 | 06-APR-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5511356.51 | 4664.00 | 02-MAY-08:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 786088.62 | 3394.94 | 14-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 3221886.39 | 3708.63 | 01-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 3729444.01 | 3554.83 | 29-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 4858281.09 | 4209.81 | 11-SEP-08:24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 73019501.85 | 4598.21 | 24-OCT-21:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.331339E+09 | 4664.00 | 10-NOV-09:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.145257E+10 | 4664.00 | 02-DEC-16:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.351482E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 786088.62 | 3394.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.145257E+10 | 4664.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.118674E+10 | 27188.53 | 01-JAN-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.995657E+09 | 27188.53 | 01-FEB-04:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.127149E+10 | 27188.53 | 02-MAR-03:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 80702355.58 | 27188.53 | 01-APR-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 39020739.64 | 27188.53 | 01-MAY-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3209722.98 | 15311.00 | 05-JUN-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 26052964.58 | 19016.46 | 19-JUL-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 39272551.55 | 27188.53 | 24-AUG-08:24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 50314286.93 | 26837.23 | 29-SEP-08:24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.164765E+09 | 27188.53 | 14-OCT-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.862028E+09 | 27188.53 | 04-NOV-04:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.350239E+10 | 27188.53 | 01-DEC-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.822165E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 3209722.98 | 15311.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.350239E+10 | 27188.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.234275E+09 | 4649.79 | 02-JAN-19:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.432302E+09 | 4649.79 | 02-FEB-19:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.279094E+09 | 4649.79 | 07-MAR-19:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 831034.13 | 1933.32 | 29-APR-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 326315.63 | 1671.67 | 25-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 57264.98 | 668.09 | 09-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 475827.81 | 2990.41 | 04-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 916640.43 | 3907.44 | 03-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 31507662.71 | 4649.79 | 27-OCT-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.182061E+09 | 4649.79 | 18-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.728339E+09 | 4649.79 | 04-DEC-19:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.189019E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.728339E+09 | 4649.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.550661E+09 | 4654.33 | 01-JAN-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.665106E+09 | 4654.33 | 03-FEB-16:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.366488E+09 | 4654.33 | 08-MAR-16:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 4671099.71 | 4654.33 | 06-APR-21:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 748318.19 | 4605.40 | 13-MAY-21:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 115977.12 | 1631.55 | 03-AUG-19:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 630715.51 | 1897.40 | 25-SEP-08:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 66040314.96 | 4461.45 | 12-OCT-20:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.381185E+09 | 4654.33 | 09-NOV-09:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.135929E+10 | 4654.33 | 06-DEC-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.339494E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.135929E+10 | 4654.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.150137E+09 | 1439.14 | 01-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.248228E+09 | 1439.14 | 08-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.165424E+09 | 1439.14 | 25-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3872110.46 | 1432.21 | 28-APR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1316818.53 | 1434.49 | 01-MAY-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 513186.71 | 1174.96 | 14-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1066635.64 | 1061.86 | 01-JUL-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1346586.39 | 1233.91 | 30-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1866668.99 | 939.12 | 28-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 42050776.24 | 1435.06 | 25-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.116952E+09 | 1439.14 | 30-NOV-19:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.372370E+09 | 1439.14 | 01-DEC-19:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.110514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 513186.71 | 939.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.372370E+09 | 1439.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.289858E+09 | 1439.68 | 01-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.367629E+09 | 1439.68 | 01-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.199732E+09 | 1439.68 | 08-MAR-16:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3287110.75 | 1439.68 | 01-APR-08:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1955752.24 | 1439.68 | 03-MAY-08:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 292419.76 | 829.34 | 24-JUN-06:44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 885065.52 | 991.01 | 27-JUL-08:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1203484.80 | 1439.68 | 24-AUG-08:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1516586.27 | 1271.58 | 08-SEP-06:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 63559121.90 | 1439.68 | 19-OCT-08:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.204449E+09 | 1439.68 | 04-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.641745E+09 | 1439.68 | 01-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.177611E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 292419.76 | 829.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.641745E+09 | 1439.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.154642E+09 | 6951.57 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.350474E+09 | 6951.57 | 01-FEB-04:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.301759E+09 | 6951.57 | 27-MAR-23:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 10612315.42 | 6866.97 | 19-APR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 9994933.59 | 6951.57 | 08-MAY-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2291325.44 | 6951.57 | 14-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7054595.67 | 6013.55 | 01-JUL-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7449592.01 | 5203.76 | 29-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6955398.53 | 5274.49 | 14-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 29777483.10 | 6951.57 | 26-OCT-00:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.127254E+09 | 6951.57 | 05-NOV-01:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.525449E+09 | 6951.57 | 01-DEC-03:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.153371E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 2291325.44 | 5203.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.525449E+09 | 6951.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.673140E+10 | 0.667614E+10 | 16913.69 | 31-JAN-16:01 | 16913.69 | 0.02 |
February | 0.00 | 0.00 | 0.173107E+10 | 0.173107E+10 | 13696.42 | 18-FEB-14:00 | 13696.42 | 0.08 |
March | 0.00 | 0.00 | 0.788858E+10 | 0.788858E+10 | 17352.00 | 16-MAR-15:01 | 17352.00 | 0.10 |
April | 0.00 | 0.00 | 0.209364E+11 | 0.209364E+11 | 19396.98 | 14-APR-15:01 | 19396.98 | 0.04 |
May | 0.00 | 0.00 | 0.271449E+11 | 0.271449E+11 | 19771.08 | 31-MAY-15:01 | 19771.08 | 0.02 |
June | 0.00 | 0.00 | 0.322280E+11 | 0.322132E+11 | 22035.42 | 17-JUN-16:00 | 19492.35 | 0.16 |
July | 0.00 | 0.00 | 0.365742E+11 | 0.329298E+11 | 30440.72 | 27-JUL-06:50 | 15040.23 | 0.63 |
August | 0.00 | 0.00 | 0.364052E+11 | 0.325697E+11 | 35354.65 | 05-AUG-08:15 | 16213.38 | 0.69 |
September | 0.00 | 0.00 | 0.345802E+11 | 0.298804E+11 | 39084.40 | 04-SEP-08:15 | 15974.13 | 0.69 |
October | 0.00 | 0.00 | 0.179529E+11 | 0.174483E+11 | 28096.49 | 03-OCT-06:40 | 14795.55 | 0.23 |
November | 0.00 | 0.00 | 0.849251E+10 | 0.711766E+10 | 24520.20 | 12-NOV-13:07 | 13863.49 | 0.18 |
December | 0.00 | 0.00 | 0.357276E+10 | 0.357276E+10 | 15710.75 | 25-DEC-16:01 | 15710.75 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.234238E+12 | 0.220109E+12 | 0.24 | |||
Minimum of Months | 0.00 | 0.00 | 0.173107E+10 | 0.173107E+10 | 13696.42 | 13696.42 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.365742E+11 | 0.329298E+11 | 39084.40 | 19771.08 | 0.69 |
Report: CoilReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.107972E+12 | 0.107511E+12 | 180591.53 | 31-JAN-16:20 | 180591.53 | 0.04 |
February | 0.00 | 0.00 | 0.264415E+11 | 0.264047E+11 | 104882.16 | 18-FEB-14:00 | 104882.16 | 0.13 |
March | 0.00 | 0.00 | 0.116734E+12 | 0.116734E+12 | 198409.83 | 16-MAR-18:20 | 198409.83 | 0.12 |
April | 0.00 | 0.00 | 0.319960E+12 | 0.319960E+12 | 259996.46 | 14-APR-18:10 | 259996.46 | 0.05 |
May | 0.00 | 0.00 | 0.415918E+12 | 0.415918E+12 | 271206.36 | 31-MAY-18:20 | 271206.36 | 0.01 |
June | 0.00 | 0.00 | 0.523412E+12 | 0.522504E+12 | 331193.25 | 17-JUN-17:17 | 271208.58 | 0.34 |
July | 0.00 | 0.00 | 0.609911E+12 | 0.533141E+12 | 411961.92 | 13-JUL-18:01 | 221269.86 | 0.81 |
August | 0.00 | 0.00 | 0.596575E+12 | 0.526328E+12 | 443465.59 | 18-AUG-22:00 | 207932.92 | 0.86 |
September | 0.00 | 0.00 | 0.549704E+12 | 0.474730E+12 | 471103.92 | 10-SEP-19:15 | 196279.38 | 0.87 |
October | 0.00 | 0.00 | 0.282087E+12 | 0.274082E+12 | 334728.63 | 02-OCT-20:00 | 251542.89 | 0.29 |
November | 0.00 | 0.00 | 0.123583E+12 | 0.109564E+12 | 202220.42 | 01-NOV-18:10 | 202220.42 | 0.24 |
December | 0.00 | 0.00 | 0.573642E+11 | 0.573642E+11 | 159214.32 | 22-DEC-16:03 | 159214.32 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.372966E+13 | 0.348424E+13 | 0.31 | |||
Minimum of Months | 0.00 | 0.00 | 0.264415E+11 | 0.264047E+11 | 104882.16 | 104882.16 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.609911E+12 | 0.533141E+12 | 471103.92 | 271208.58 | 0.87 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.367030E+10 | 0.298155E+10 | 19075.52 | 06-JAN-16:01 | 19075.52 | 0.26 |
February | 0.00 | 0.00 | 0.142915E+10 | 0.748481E+09 | 19071.45 | 25-FEB-19:01 | 19071.45 | 0.34 |
March | 0.00 | 0.00 | 0.291697E+10 | 0.176629E+10 | 19072.80 | 08-MAR-16:01 | 19072.80 | 0.45 |
April | 0.00 | 0.00 | 0.829385E+10 | 0.733655E+10 | 19076.75 | 14-APR-18:01 | 19076.75 | 0.28 |
May | 0.00 | 0.00 | 0.973121E+10 | 0.895066E+10 | 19075.78 | 19-MAY-18:01 | 19075.78 | 0.22 |
June | 0.00 | 0.00 | 0.129149E+11 | 0.998079E+10 | 19077.68 | 07-JUN-18:02 | 19077.68 | 0.84 |
July | 0.00 | 0.00 | 0.124804E+11 | 0.822548E+10 | 19057.93 | 03-JUL-15:01 | 19057.93 | 0.87 |
August | 0.00 | 0.00 | 0.123536E+11 | 0.794137E+10 | 19075.36 | 25-AUG-08:61 | 19075.36 | 0.92 |
September | 0.00 | 0.00 | 0.109269E+11 | 0.636313E+10 | 17807.60 | 03-SEP-08:61 | 13378.73 | 0.96 |
October | 0.00 | 0.00 | 0.707140E+10 | 0.511785E+10 | 19076.37 | 28-OCT-18:01 | 19076.37 | 0.49 |
November | 0.00 | 0.00 | 0.384873E+10 | 0.270755E+10 | 19075.36 | 25-NOV-16:01 | 19075.36 | 0.37 |
December | 0.00 | 0.00 | 0.188651E+10 | 0.181007E+10 | 19076.14 | 24-DEC-16:01 | 19076.14 | 0.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.875240E+11 | 0.639298E+11 | 0.50 | |||
Minimum of Months | 0.00 | 0.00 | 0.142915E+10 | 0.748481E+09 | 17807.60 | 13378.73 | 0.03 | |
Maximum of Months | 0.00 | 0.00 | 0.129149E+11 | 0.998079E+10 | 19077.68 | 19077.68 | 0.96 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.951881E+09 | 0.765302E+09 | 18958.37 | 05-JAN-16:01 | 18958.37 | 0.11 |
February | 0.00 | 0.00 | 0.350666E+09 | 0.161981E+09 | 19113.99 | 01-FEB-17:11 | 19113.99 | 0.13 |
March | 0.00 | 0.00 | 0.129768E+10 | 0.673274E+09 | 19186.23 | 23-MAR-21:11 | 19186.23 | 0.28 |
April | 0.00 | 0.00 | 0.679896E+10 | 0.592701E+10 | 19997.31 | 26-APR-21:51 | 19997.31 | 0.25 |
May | 0.00 | 0.00 | 0.913124E+10 | 0.839500E+10 | 20890.81 | 20-MAY-08:61 | 20890.81 | 0.21 |
June | 0.00 | 0.00 | 0.128361E+11 | 0.100430E+11 | 21070.36 | 14-JUN-08:61 | 21070.36 | 0.81 |
July | 0.00 | 0.00 | 0.123219E+11 | 0.816621E+10 | 21587.03 | 01-JUL-08:61 | 21587.03 | 0.86 |
August | 0.00 | 0.00 | 0.114650E+11 | 0.729138E+10 | 20083.37 | 24-AUG-08:21 | 20083.37 | 0.87 |
September | 0.00 | 0.00 | 0.939964E+10 | 0.531407E+10 | 19220.11 | 05-SEP-08:31 | 12992.21 | 0.86 |
October | 0.00 | 0.00 | 0.446063E+10 | 0.298364E+10 | 19385.67 | 17-OCT-21:51 | 19385.67 | 0.38 |
November | 0.00 | 0.00 | 0.133928E+10 | 0.808235E+09 | 18957.52 | 25-NOV-16:01 | 18957.52 | 0.21 |
December | 0.00 | 0.00 | 0.315399E+09 | 0.301043E+09 | 18957.53 | 24-DEC-16:01 | 18957.53 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.706683E+11 | 0.508301E+11 | 0.42 | |||
Minimum of Months | 0.00 | 0.00 | 0.315399E+09 | 0.161981E+09 | 18957.52 | 12992.21 | 0.01 | |
Maximum of Months | 0.00 | 0.00 | 0.128361E+11 | 0.100430E+11 | 21587.03 | 21587.03 | 0.87 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.466116E+11 | 0.423058E+11 | 48635.17 | 14-JAN-13:40 | 48635.17 | 0.18 |
February | 0.00 | 0.00 | 0.184492E+11 | 0.107218E+11 | 37490.25 | 01-FEB-14:15 | 37490.25 | 0.41 |
March | 0.00 | 0.00 | 0.206120E+11 | 0.113455E+11 | 34236.05 | 18-MAR-13:30 | 22079.61 | 0.46 |
April | 0.00 | 0.00 | 0.410611E+11 | 0.389954E+11 | 34042.36 | 14-APR-13:40 | 34042.36 | 0.09 |
May | 0.00 | 0.00 | 0.404797E+11 | 0.402102E+11 | 28591.55 | 09-MAY-17:13 | 28591.55 | 0.01 |
June | 0.00 | 0.00 | 0.516330E+11 | 0.408430E+11 | 35676.44 | 28-JUN-19:10 | 25504.71 | 0.37 |
July | 0.00 | 0.00 | 0.543426E+11 | 0.293069E+11 | 35373.47 | 21-JUL-20:20 | 23516.16 | 0.78 |
August | 0.00 | 0.00 | 0.577572E+11 | 0.298933E+11 | 39873.50 | 28-AUG-12:30 | 29147.26 | 0.88 |
September | 0.00 | 0.00 | 0.582558E+11 | 0.288441E+11 | 45086.68 | 28-SEP-13:30 | 39267.71 | 0.98 |
October | 0.00 | 0.00 | 0.514197E+11 | 0.389386E+11 | 47335.30 | 18-OCT-13:20 | 47335.30 | 0.46 |
November | 0.00 | 0.00 | 0.402148E+11 | 0.326320E+11 | 50931.76 | 20-NOV-14:30 | 36077.70 | 0.34 |
December | 0.00 | 0.00 | 0.347546E+11 | 0.344794E+11 | 48230.09 | 25-DEC-13:30 | 48230.09 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.515591E+12 | 0.378516E+12 | 0.41 | |||
Minimum of Months | 0.00 | 0.00 | 0.184492E+11 | 0.107218E+11 | 28591.55 | 22079.61 | 0.01 | |
Maximum of Months | 0.00 | 0.00 | 0.582558E+11 | 0.423058E+11 | 50931.76 | 48635.17 | 0.98 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.103573E+11 | 0.803946E+10 | 116664.68 | 31-JAN-19:01 | 116664.68 | 0.15 |
February | 0.00 | 0.00 | 0.106031E+11 | 0.402703E+10 | 111547.54 | 27-FEB-19:01 | 111547.54 | 0.43 |
March | 0.00 | 0.00 | 0.170812E+11 | 0.102807E+11 | 119292.56 | 22-MAR-21:21 | 119292.56 | 0.36 |
April | 0.00 | 0.00 | 0.387800E+11 | 0.353476E+11 | 120729.47 | 26-APR-21:51 | 120729.47 | 0.16 |
May | 0.00 | 0.00 | 0.533159E+11 | 0.506016E+11 | 126473.99 | 20-MAY-08:61 | 126473.99 | 0.11 |
June | 0.00 | 0.00 | 0.745968E+11 | 0.599782E+11 | 127160.46 | 25-JUN-07:31 | 127160.46 | 0.65 |
July | 0.00 | 0.00 | 0.794651E+11 | 0.529482E+11 | 129302.56 | 01-JUL-08:61 | 129302.56 | 0.80 |
August | 0.00 | 0.00 | 0.722636E+11 | 0.453949E+11 | 119908.18 | 28-AUG-18:31 | 85994.21 | 0.78 |
September | 0.00 | 0.00 | 0.620603E+11 | 0.365260E+11 | 120231.57 | 10-SEP-21:51 | 87205.18 | 0.78 |
October | 0.00 | 0.00 | 0.313486E+11 | 0.224159E+11 | 118883.49 | 19-OCT-18:01 | 118883.49 | 0.33 |
November | 0.00 | 0.00 | 0.138918E+11 | 0.868061E+10 | 116882.80 | 10-NOV-16:01 | 116882.80 | 0.21 |
December | 0.00 | 0.00 | 0.583954E+10 | 0.563150E+10 | 114564.07 | 03-DEC-09:02 | 114564.07 | 0.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.469603E+12 | 0.339872E+12 | 0.40 | |||
Minimum of Months | 0.00 | 0.00 | 0.583954E+10 | 0.402703E+10 | 111547.54 | 85994.21 | 0.02 | |
Maximum of Months | 0.00 | 0.00 | 0.794651E+11 | 0.599782E+11 | 129302.56 | 129302.56 | 0.80 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.351302E+10 | 0.281480E+10 | 16884.38 | 04-JAN-16:01 | 16884.38 | 0.28 |
February | 0.00 | 0.00 | 0.173270E+10 | 0.856442E+09 | 16879.48 | 02-FEB-16:01 | 16879.48 | 0.41 |
March | 0.00 | 0.00 | 0.311308E+10 | 0.184161E+10 | 16873.86 | 22-MAR-18:01 | 16873.86 | 0.49 |
April | 0.00 | 0.00 | 0.844489E+10 | 0.751029E+10 | 16885.76 | 14-APR-18:01 | 16885.76 | 0.29 |
May | 0.00 | 0.00 | 0.101108E+11 | 0.938220E+10 | 16885.32 | 19-MAY-18:01 | 16885.32 | 0.22 |
June | 0.00 | 0.00 | 0.132144E+11 | 0.104064E+11 | 16883.99 | 07-JUN-15:01 | 16883.99 | 0.86 |
July | 0.00 | 0.00 | 0.133372E+11 | 0.924042E+10 | 16869.08 | 03-JUL-15:01 | 16869.08 | 0.89 |
August | 0.00 | 0.00 | 0.130687E+11 | 0.880086E+10 | 16883.54 | 25-AUG-08:61 | 16883.54 | 0.93 |
September | 0.00 | 0.00 | 0.113267E+11 | 0.695467E+10 | 15715.79 | 03-SEP-08:61 | 11889.92 | 0.98 |
October | 0.00 | 0.00 | 0.737404E+10 | 0.545489E+10 | 16884.53 | 28-OCT-18:01 | 16884.53 | 0.51 |
November | 0.00 | 0.00 | 0.357757E+10 | 0.254344E+10 | 16883.82 | 20-NOV-09:01 | 16883.82 | 0.37 |
December | 0.00 | 0.00 | 0.193693E+10 | 0.182865E+10 | 16885.02 | 31-DEC-09:01 | 16885.02 | 0.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.907500E+11 | 0.676346E+11 | 0.52 | |||
Minimum of Months | 0.00 | 0.00 | 0.173270E+10 | 0.856442E+09 | 15715.79 | 11889.92 | 0.05 | |
Maximum of Months | 0.00 | 0.00 | 0.133372E+11 | 0.104064E+11 | 16885.76 | 16885.76 | 0.98 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.943566E+09 | 0.694770E+09 | 17215.88 | 27-JAN-09:51 | 17215.88 | 0.12 |
February | 0.00 | 0.00 | 0.636621E+09 | 0.246177E+09 | 15437.76 | 18-FEB-09:01 | 11611.29 | 0.19 |
March | 0.00 | 0.00 | 0.156582E+10 | 0.805606E+09 | 16778.47 | 31-MAR-15:01 | 16778.47 | 0.33 |
April | 0.00 | 0.00 | 0.675562E+10 | 0.591888E+10 | 19385.60 | 11-APR-08:51 | 19385.60 | 0.26 |
May | 0.00 | 0.00 | 0.918633E+10 | 0.848777E+10 | 21363.84 | 21-MAY-08:61 | 21363.84 | 0.22 |
June | 0.00 | 0.00 | 0.130447E+11 | 0.104290E+11 | 20450.60 | 13-JUN-07:52 | 20450.60 | 0.84 |
July | 0.00 | 0.00 | 0.131298E+11 | 0.911626E+10 | 20494.68 | 01-JUL-07:42 | 20494.68 | 0.87 |
August | 0.00 | 0.00 | 0.121167E+11 | 0.801026E+10 | 19403.32 | 25-AUG-07:31 | 19403.32 | 0.88 |
September | 0.00 | 0.00 | 0.971656E+10 | 0.583064E+10 | 18180.72 | 04-SEP-08:51 | 13345.04 | 0.87 |
October | 0.00 | 0.00 | 0.468725E+10 | 0.318816E+10 | 19072.73 | 17-OCT-08:51 | 19072.73 | 0.42 |
November | 0.00 | 0.00 | 0.119144E+10 | 0.706814E+09 | 18081.74 | 10-NOV-09:51 | 18081.74 | 0.19 |
December | 0.00 | 0.00 | 0.379290E+09 | 0.331824E+09 | 16824.74 | 25-DEC-09:51 | 16824.74 | 0.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.733538E+11 | 0.537661E+11 | 0.44 | |||
Minimum of Months | 0.00 | 0.00 | 0.379290E+09 | 0.246177E+09 | 15437.76 | 11611.29 | 0.02 | |
Maximum of Months | 0.00 | 0.00 | 0.131298E+11 | 0.104290E+11 | 21363.84 | 21363.84 | 0.88 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.814578E+09 | 0.668600E+09 | 5058.56 | 04-JAN-16:01 | 5058.56 | 0.22 |
February | 0.00 | 0.00 | 0.306332E+09 | 0.168030E+09 | 5057.50 | 25-FEB-19:01 | 5057.50 | 0.26 |
March | 0.00 | 0.00 | 0.681204E+09 | 0.433983E+09 | 5058.92 | 21-MAR-18:01 | 5058.92 | 0.37 |
April | 0.00 | 0.00 | 0.208709E+10 | 0.184427E+10 | 5058.95 | 14-APR-18:01 | 5058.95 | 0.28 |
May | 0.00 | 0.00 | 0.248115E+10 | 0.226624E+10 | 5058.85 | 09-MAY-08:61 | 5058.85 | 0.23 |
June | 0.00 | 0.00 | 0.339930E+10 | 0.262255E+10 | 5059.04 | 07-JUN-18:02 | 5059.04 | 0.84 |
July | 0.00 | 0.00 | 0.326322E+10 | 0.214237E+10 | 5053.90 | 03-JUL-15:01 | 5053.90 | 0.87 |
August | 0.00 | 0.00 | 0.320927E+10 | 0.206026E+10 | 5058.64 | 25-AUG-08:61 | 5058.64 | 0.92 |
September | 0.00 | 0.00 | 0.276090E+10 | 0.158977E+10 | 5003.34 | 03-SEP-08:61 | 3311.14 | 0.96 |
October | 0.00 | 0.00 | 0.166465E+10 | 0.119141E+10 | 5058.52 | 31-OCT-15:01 | 5058.52 | 0.47 |
November | 0.00 | 0.00 | 0.843009E+09 | 0.603731E+09 | 5058.32 | 21-NOV-19:01 | 5058.32 | 0.30 |
December | 0.00 | 0.00 | 0.409967E+09 | 0.393166E+09 | 5058.01 | 30-DEC-16:01 | 5058.01 | 0.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.219207E+11 | 0.159844E+11 | 0.48 | |||
Minimum of Months | 0.00 | 0.00 | 0.306332E+09 | 0.168030E+09 | 5003.34 | 3311.14 | 0.03 | |
Maximum of Months | 0.00 | 0.00 | 0.339930E+10 | 0.262255E+10 | 5059.04 | 5059.04 | 0.96 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.183945E+09 | 0.152407E+09 | 5023.78 | 04-JAN-16:01 | 5023.78 | 0.07 |
February | 0.00 | 0.00 | 61973587.16 | 30411660.87 | 5042.22 | 01-FEB-17:11 | 5042.22 | 0.08 |
March | 0.00 | 0.00 | 0.286723E+09 | 0.156694E+09 | 5081.70 | 23-MAR-21:11 | 5081.70 | 0.22 |
April | 0.00 | 0.00 | 0.173382E+10 | 0.150788E+10 | 5296.87 | 26-APR-21:51 | 5296.87 | 0.26 |
May | 0.00 | 0.00 | 0.236077E+10 | 0.215450E+10 | 5448.18 | 20-MAY-08:61 | 5448.18 | 0.22 |
June | 0.00 | 0.00 | 0.339916E+10 | 0.265503E+10 | 5514.71 | 14-JUN-08:61 | 5514.71 | 0.82 |
July | 0.00 | 0.00 | 0.323182E+10 | 0.213294E+10 | 5639.93 | 01-JUL-08:61 | 5639.93 | 0.86 |
August | 0.00 | 0.00 | 0.299954E+10 | 0.190321E+10 | 5236.74 | 24-AUG-08:21 | 5236.74 | 0.87 |
September | 0.00 | 0.00 | 0.239756E+10 | 0.134063E+10 | 5180.30 | 04-SEP-08:51 | 3238.97 | 0.86 |
October | 0.00 | 0.00 | 0.104597E+10 | 0.688805E+09 | 5078.81 | 16-OCT-21:51 | 5078.81 | 0.36 |
November | 0.00 | 0.00 | 0.258184E+09 | 0.159791E+09 | 5022.38 | 05-NOV-15:01 | 5022.38 | 0.16 |
December | 0.00 | 0.00 | 57577185.31 | 53965362.82 | 5023.10 | 30-DEC-16:01 | 5023.10 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.180170E+11 | 0.129363E+11 | 0.40 | |||
Minimum of Months | 0.00 | 0.00 | 57577185.31 | 30411660.87 | 5022.38 | 3238.97 | 0.01 | |
Maximum of Months | 0.00 | 0.00 | 0.339916E+10 | 0.265503E+10 | 5639.93 | 5639.93 | 0.87 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.102965E+11 | 0.898523E+10 | 22330.46 | 19-JAN-16:01 | 22330.46 | 0.39 |
February | 0.00 | 0.00 | 0.471671E+10 | 0.276071E+10 | 22332.82 | 27-FEB-19:01 | 22332.82 | 0.56 |
March | 0.00 | 0.00 | 0.538537E+10 | 0.348060E+10 | 22330.37 | 09-MAR-19:01 | 22330.37 | 0.52 |
April | 0.00 | 0.00 | 0.103643E+11 | 0.909956E+10 | 22329.68 | 09-APR-15:01 | 22329.68 | 0.31 |
May | 0.00 | 0.00 | 0.106900E+11 | 0.943366E+10 | 22332.45 | 23-MAY-18:01 | 22332.45 | 0.29 |
June | 0.00 | 0.00 | 0.142338E+11 | 0.101495E+11 | 22332.84 | 10-JUN-08:61 | 22332.84 | 0.87 |
July | 0.00 | 0.00 | 0.154820E+11 | 0.994014E+10 | 22322.57 | 02-JUL-18:01 | 22322.57 | 0.87 |
August | 0.00 | 0.00 | 0.161644E+11 | 0.104884E+11 | 22323.96 | 25-AUG-08:61 | 22323.96 | 0.93 |
September | 0.00 | 0.00 | 0.157469E+11 | 0.100625E+11 | 22171.28 | 03-SEP-08:61 | 15028.64 | 0.96 |
October | 0.00 | 0.00 | 0.122792E+11 | 0.972857E+10 | 22328.74 | 28-OCT-18:01 | 22328.74 | 0.52 |
November | 0.00 | 0.00 | 0.915706E+10 | 0.736490E+10 | 22331.98 | 27-NOV-16:01 | 22331.98 | 0.42 |
December | 0.00 | 0.00 | 0.771177E+10 | 0.749714E+10 | 22332.91 | 31-DEC-09:01 | 22332.91 | 0.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.132228E+12 | 0.989910E+11 | 0.56 | |||
Minimum of Months | 0.00 | 0.00 | 0.471671E+10 | 0.276071E+10 | 22171.28 | 15028.64 | 0.07 | |
Maximum of Months | 0.00 | 0.00 | 0.161644E+11 | 0.104884E+11 | 22332.91 | 22332.91 | 0.96 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 74087.76 | 435150.16 | 31-JAN-16:01 | 0.00 | 0.00 | 01-JAN-00:02 |
February | 29692.92 | 303856.58 | 22-FEB-16:01 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 68662.61 | 422579.19 | 20-MAR-18:01 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 181947.14 | 493662.01 | 14-APR-18:03 | 0.00 | 0.00 | 01-APR-00:10 |
May | 222925.55 | 511472.59 | 31-MAY-18:03 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 293724.72 | 575192.00 | 01-JUN-18:03 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 321131.75 | 637900.21 | 13-JUL-18:01 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 313983.84 | 585250.21 | 09-AUG-18:01 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 298347.82 | 670188.07 | 10-SEP-21:52 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 159813.65 | 522287.65 | 01-OCT-18:01 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 82037.77 | 432167.22 | 09-NOV-16:01 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 44727.12 | 419292.09 | 22-DEC-16:01 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 175009.39 | 0.00 | ||||
Minimum of Months | 29692.92 | 303856.58 | 0.00 | 0.00 | ||
Maximum of Months | 321131.75 | 670188.07 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 22453.88 | 47070.48 | 23-JAN-07:40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 22233.48 | 46982.91 | 01-FEB-07:15 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 21195.41 | 45630.74 | 01-MAR-07:15 |
April | 0.00 | 0.00 | 01-APR-00:10 | 19529.24 | 42353.55 | 03-APR-06:30 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 17735.71 | 38873.09 | 01-MAY-07:00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 16285.69 | 35277.79 | 01-JUN-06:35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15552.20 | 32869.77 | 03-JUL-06:20 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 15786.82 | 33841.57 | 31-AUG-06:40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16868.43 | 36670.72 | 29-SEP-07:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18527.32 | 40622.01 | 31-OCT-06:30 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 20320.15 | 45453.45 | 14-NOV-07:15 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21754.71 | 46393.78 | 29-DEC-08:00 |
Annual Sum or Average | 0.00 | 19002.28 | ||||
Minimum of Months | 0.00 | 0.00 | 15552.20 | 32869.77 | ||
Maximum of Months | 0.00 | 0.00 | 22453.88 | 47070.48 |
Report: FanReportMonthly
For: FLR_3_DOAS FAN
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.271000E+10 | 0.76 | 1299.30 | 12-JAN-09:03 | 0.96 |
February | 0.244774E+10 | 0.76 | 1299.30 | 01-FEB-09:01 | 0.96 |
March | 0.271000E+10 | 0.76 | 1299.30 | 02-MAR-16:04 | 0.96 |
April | 0.262258E+10 | 0.77 | 1299.30 | 15-APR-18:15 | 0.96 |
May | 0.271000E+10 | 0.77 | 1299.30 | 10-MAY-15:17 | 0.96 |
June | 0.262258E+10 | 0.76 | 1299.30 | 01-JUN-18:25 | 0.96 |
July | 0.271000E+10 | 0.76 | 1299.30 | 04-JUL-18:20 | 0.96 |
August | 0.271000E+10 | 0.76 | 1299.30 | 03-AUG-15:15 | 0.96 |
September | 0.262258E+10 | 0.76 | 1299.30 | 11-SEP-18:15 | 0.96 |
October | 0.271000E+10 | 0.76 | 1299.30 | 01-OCT-08:61 | 0.96 |
November | 0.262258E+10 | 0.76 | 1299.30 | 01-NOV-08:52 | 0.96 |
December | 0.271000E+10 | 0.77 | 1299.30 | 07-DEC-16:03 | 0.97 |
Annual Sum or Average | 0.319080E+11 | 0.76 | |||
Minimum of Months | 0.244774E+10 | 0.76 | 1299.30 | 0.96 | |
Maximum of Months | 0.271000E+10 | 0.77 | 1299.30 | 0.97 |
Report: FanReportMonthly
For: VAV WITH REHEAT FAN
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.360182E+11 | 0.86 | 27356.25 | 19-JAN-22:10 | 1.31 |
February | 0.303744E+11 | 0.83 | 23514.81 | 01-FEB-22:10 | 1.20 |
March | 0.347257E+11 | 0.85 | 27128.34 | 16-MAR-21:10 | 1.30 |
April | 0.381210E+11 | 0.91 | 31887.28 | 14-APR-21:20 | 1.44 |
May | 0.409497E+11 | 0.93 | 32129.42 | 09-MAY-21:10 | 1.44 |
June | 0.442326E+11 | 0.98 | 36109.16 | 29-JUN-21:10 | 1.55 |
July | 0.455009E+11 | 0.97 | 38234.79 | 21-JUL-21:10 | 1.60 |
August | 0.463265E+11 | 0.98 | 39268.47 | 15-AUG-21:10 | 1.62 |
September | 0.451183E+11 | 0.99 | 40973.69 | 07-SEP-21:10 | 1.67 |
October | 0.419940E+11 | 0.94 | 40398.70 | 06-OCT-21:10 | 1.66 |
November | 0.371171E+11 | 0.89 | 32870.98 | 01-NOV-21:10 | 1.46 |
December | 0.358554E+11 | 0.86 | 28630.92 | 26-DEC-22:10 | 1.35 |
Annual Sum or Average | 0.476334E+12 | 0.92 | |||
Minimum of Months | 0.303744E+11 | 0.83 | 23514.81 | 1.20 | |
Maximum of Months | 0.463265E+11 | 0.99 | 40973.69 | 1.67 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205205E+09 | 0.29 | 76.61 | 01-JAN-00:02 | 0.29 |
February | 0.185347E+09 | 0.29 | 76.61 | 01-FEB-00:10 | 0.29 |
March | 0.205205E+09 | 0.29 | 76.61 | 01-MAR-00:05 | 0.29 |
April | 0.198586E+09 | 0.29 | 76.61 | 01-APR-00:10 | 0.29 |
May | 0.205205E+09 | 0.29 | 76.61 | 01-MAY-00:05 | 0.29 |
June | 0.198586E+09 | 0.29 | 76.61 | 01-JUN-00:05 | 0.29 |
July | 0.205205E+09 | 0.29 | 76.61 | 01-JUL-00:10 | 0.29 |
August | 0.205205E+09 | 0.29 | 76.61 | 01-AUG-00:05 | 0.29 |
September | 0.198586E+09 | 0.29 | 76.61 | 01-SEP-00:05 | 0.29 |
October | 0.205205E+09 | 0.29 | 76.61 | 01-OCT-00:10 | 0.29 |
November | 0.198586E+09 | 0.29 | 76.61 | 01-NOV-00:05 | 0.29 |
December | 0.205205E+09 | 0.29 | 76.61 | 01-DEC-00:10 | 0.29 |
Annual Sum or Average | 0.241613E+10 | 0.29 | |||
Minimum of Months | 0.185347E+09 | 0.29 | 76.61 | 0.29 | |
Maximum of Months | 0.205205E+09 | 0.29 | 76.61 | 0.29 |
Report: FanReportMonthly
For: LOBBY_FLR_1 EXHAUST FAN
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | -0.0 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:05 | -0.0 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:05 | -0.0 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 EXHAUST FAN
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 EXHAUST FAN
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:02 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116283E+10 | 0.21 | 612.92 | 01-JAN-07:10 | 0.29 |
February | 0.105030E+10 | 0.21 | 612.92 | 01-FEB-07:05 | 0.29 |
March | 0.116283E+10 | 0.21 | 612.92 | 01-MAR-07:05 | 0.29 |
April | 0.112532E+10 | 0.21 | 612.92 | 01-APR-06:05 | 0.29 |
May | 0.116283E+10 | 0.21 | 612.92 | 01-MAY-06:05 | 0.29 |
June | 0.112532E+10 | 0.21 | 612.92 | 01-JUN-06:05 | 0.29 |
July | 0.116283E+10 | 0.21 | 612.92 | 01-JUL-06:05 | 0.29 |
August | 0.116283E+10 | 0.21 | 612.92 | 01-AUG-06:10 | 0.29 |
September | 0.112532E+10 | 0.21 | 612.92 | 01-SEP-06:05 | 0.29 |
October | 0.116283E+10 | 0.21 | 612.92 | 01-OCT-06:10 | 0.29 |
November | 0.112532E+10 | 0.21 | 612.92 | 01-NOV-06:05 | 0.29 |
December | 0.116283E+10 | 0.21 | 612.92 | 01-DEC-07:05 | 0.29 |
Annual Sum or Average | 0.136914E+11 | 0.21 | |||
Minimum of Months | 0.105030E+10 | 0.21 | 612.92 | 0.29 | |
Maximum of Months | 0.116283E+10 | 0.21 | 612.92 | 0.29 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.177123E+09 | 0.56 | 852.59 | 01-JAN-16:01 | 0.63 |
February | 91367974.77 | 0.49 | 852.59 | 01-FEB-16:01 | 0.63 |
March | 0.151167E+09 | 0.52 | 852.59 | 01-MAR-16:01 | 0.63 |
April | 0.374436E+09 | 0.60 | 852.59 | 01-APR-08:61 | 0.63 |
May | 0.432539E+09 | 0.61 | 852.59 | 01-MAY-08:61 | 0.63 |
June | 0.644925E+09 | 0.62 | 852.59 | 01-JUN-08:61 | 0.63 |
July | 0.537818E+09 | 0.61 | 852.59 | 01-JUL-08:61 | 0.64 |
August | 0.534915E+09 | 0.61 | 852.59 | 01-AUG-08:61 | 0.63 |
September | 0.457721E+09 | 0.61 | 852.59 | 01-SEP-08:61 | 0.63 |
October | 0.313756E+09 | 0.58 | 852.59 | 01-OCT-08:61 | 0.63 |
November | 0.175712E+09 | 0.55 | 852.59 | 01-NOV-08:62 | 0.63 |
December | 0.129477E+09 | 0.53 | 852.59 | 01-DEC-09:01 | 0.63 |
Annual Sum or Average | 0.402096E+10 | 0.57 | |||
Minimum of Months | 91367974.77 | 0.49 | 852.59 | 0.63 | |
Maximum of Months | 0.644925E+09 | 0.62 | 852.59 | 0.64 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 74313291.50 | 0.40 | 847.27 | 01-JAN-09:02 | 0.63 |
February | 61966811.54 | 0.41 | 847.27 | 01-FEB-16:01 | 0.63 |
March | 83637269.60 | 0.38 | 847.27 | 01-MAR-16:01 | 0.63 |
April | 0.309606E+09 | 0.51 | 847.27 | 01-APR-08:51 | 0.63 |
May | 0.407893E+09 | 0.54 | 847.27 | 01-MAY-08:51 | 0.64 |
June | 0.653132E+09 | 0.58 | 847.27 | 01-JUN-07:21 | 0.63 |
July | 0.532903E+09 | 0.60 | 847.27 | 01-JUL-08:61 | 0.64 |
August | 0.493176E+09 | 0.57 | 847.27 | 01-AUG-08:61 | 0.63 |
September | 0.390156E+09 | 0.54 | 847.27 | 01-SEP-08:61 | 0.63 |
October | 0.198365E+09 | 0.44 | 847.27 | 01-OCT-08:61 | 0.63 |
November | 78915009.79 | 0.39 | 847.27 | 01-NOV-08:52 | 0.63 |
December | 0.104619E+09 | 0.41 | 847.27 | 01-DEC-16:01 | 0.63 |
Annual Sum or Average | 0.338868E+10 | 0.48 | |||
Minimum of Months | 61966811.54 | 0.38 | 847.27 | 0.63 | |
Maximum of Months | 0.653132E+09 | 0.60 | 847.27 | 0.64 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.148228E+10 | 0.54 | 1503.68 | 14-JAN-13:40 | 0.63 |
February | 0.605480E+09 | 0.39 | 1163.73 | 01-FEB-14:15 | 0.63 |
March | 0.696016E+09 | 0.45 | 1082.63 | 18-MAR-13:40 | 0.63 |
April | 0.131608E+10 | 0.62 | 1057.54 | 14-APR-13:40 | 0.63 |
May | 0.129768E+10 | 0.63 | 891.99 | 09-MAY-17:13 | 0.63 |
June | 0.166399E+10 | 0.63 | 1185.64 | 28-JUN-17:13 | 0.63 |
July | 0.170818E+10 | 0.63 | 1114.74 | 21-JUL-20:20 | 0.63 |
August | 0.181498E+10 | 0.63 | 1239.79 | 28-AUG-12:30 | 0.63 |
September | 0.184210E+10 | 0.63 | 1432.28 | 28-SEP-13:30 | 0.63 |
October | 0.164048E+10 | 0.59 | 1466.66 | 18-OCT-13:20 | 0.63 |
November | 0.128419E+10 | 0.53 | 2329.82 | 20-NOV-14:30 | 0.63 |
December | 0.110604E+10 | 0.46 | 1493.95 | 25-DEC-13:30 | 0.63 |
Annual Sum or Average | 0.164575E+11 | 0.56 | |||
Minimum of Months | 0.605480E+09 | 0.39 | 891.99 | 0.63 | |
Maximum of Months | 0.184210E+10 | 0.63 | 2329.82 | 0.63 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.581286E+09 | 0.36 | 5359.85 | 01-JAN-09:03 | 0.63 |
February | 0.535763E+09 | 0.40 | 5359.85 | 01-FEB-09:01 | 0.63 |
March | 0.881373E+09 | 0.35 | 5359.85 | 01-MAR-09:02 | 0.63 |
April | 0.175582E+10 | 0.45 | 5359.85 | 01-APR-08:51 | 0.63 |
May | 0.242836E+10 | 0.49 | 5359.85 | 01-MAY-08:51 | 0.64 |
June | 0.369060E+10 | 0.56 | 5359.85 | 01-JUN-07:21 | 0.63 |
July | 0.347591E+10 | 0.57 | 5359.85 | 01-JUL-08:61 | 0.64 |
August | 0.307913E+10 | 0.53 | 5359.85 | 01-AUG-08:61 | 0.63 |
September | 0.263508E+10 | 0.50 | 5359.85 | 01-SEP-08:61 | 0.63 |
October | 0.138732E+10 | 0.39 | 5359.85 | 01-OCT-08:61 | 0.63 |
November | 0.666565E+09 | 0.34 | 5359.85 | 01-NOV-08:52 | 0.63 |
December | 0.532878E+09 | 0.39 | 5359.85 | 01-DEC-09:01 | 0.63 |
Annual Sum or Average | 0.216501E+11 | 0.44 | |||
Minimum of Months | 0.532878E+09 | 0.34 | 5359.85 | 0.63 | |
Maximum of Months | 0.369060E+10 | 0.57 | 5359.85 | 0.64 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.166822E+09 | 0.58 | 754.17 | 01-JAN-09:02 | 0.63 |
February | 97779652.77 | 0.53 | 754.17 | 01-FEB-09:01 | 0.63 |
March | 0.153416E+09 | 0.55 | 754.17 | 01-MAR-09:02 | 0.63 |
April | 0.371427E+09 | 0.62 | 754.17 | 01-APR-08:61 | 0.63 |
May | 0.443949E+09 | 0.62 | 754.17 | 01-MAY-08:61 | 0.63 |
June | 0.642456E+09 | 0.62 | 754.17 | 01-JUN-08:61 | 0.63 |
July | 0.577885E+09 | 0.62 | 754.17 | 01-JUL-08:61 | 0.64 |
August | 0.563957E+09 | 0.62 | 754.17 | 01-AUG-08:61 | 0.63 |
September | 0.475161E+09 | 0.62 | 754.17 | 01-SEP-08:61 | 0.63 |
October | 0.321784E+09 | 0.60 | 754.17 | 01-OCT-08:61 | 0.63 |
November | 0.161604E+09 | 0.56 | 754.17 | 01-NOV-08:62 | 0.63 |
December | 0.126878E+09 | 0.54 | 754.17 | 01-DEC-09:01 | 0.63 |
Annual Sum or Average | 0.410312E+10 | 0.59 | |||
Minimum of Months | 97779652.77 | 0.53 | 754.17 | 0.63 | |
Maximum of Months | 0.642456E+09 | 0.62 | 754.17 | 0.64 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 73439449.47 | 0.39 | 750.04 | 01-JAN-19:01 | 0.63 |
February | 62738509.75 | 0.40 | 750.04 | 01-FEB-09:01 | 0.63 |
March | 91017613.69 | 0.40 | 750.04 | 01-MAR-16:01 | 0.63 |
April | 0.298796E+09 | 0.53 | 750.04 | 01-APR-08:51 | 0.63 |
May | 0.408847E+09 | 0.55 | 750.04 | 01-MAY-08:51 | 0.64 |
June | 0.647749E+09 | 0.59 | 750.04 | 01-JUN-07:21 | 0.63 |
July | 0.572269E+09 | 0.60 | 750.04 | 01-JUL-08:61 | 0.63 |
August | 0.524534E+09 | 0.58 | 750.04 | 01-AUG-08:61 | 0.63 |
September | 0.403962E+09 | 0.55 | 750.04 | 01-SEP-07:02 | 0.63 |
October | 0.205921E+09 | 0.46 | 750.04 | 01-OCT-07:42 | 0.63 |
November | 72216017.85 | 0.37 | 750.04 | 01-NOV-08:52 | 0.63 |
December | 91503231.55 | 0.40 | 750.04 | 01-DEC-09:01 | 0.63 |
Annual Sum or Average | 0.345299E+10 | 0.49 | |||
Minimum of Months | 62738509.75 | 0.37 | 750.04 | 0.63 | |
Maximum of Months | 0.647749E+09 | 0.60 | 750.04 | 0.64 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 44455939.91 | 0.55 | 226.17 | 01-JAN-09:02 | 0.63 |
February | 26610167.47 | 0.50 | 226.17 | 01-FEB-16:01 | 0.63 |
March | 39887495.60 | 0.52 | 226.17 | 01-MAR-16:01 | 0.63 |
April | 95014775.24 | 0.59 | 226.17 | 01-APR-15:01 | 0.63 |
May | 0.110707E+09 | 0.60 | 226.17 | 01-MAY-15:01 | 0.63 |
June | 0.172029E+09 | 0.62 | 226.17 | 01-JUN-08:61 | 0.63 |
July | 0.142416E+09 | 0.61 | 226.17 | 01-JUL-08:61 | 0.64 |
August | 0.141344E+09 | 0.61 | 226.17 | 01-AUG-08:61 | 0.63 |
September | 0.116915E+09 | 0.61 | 226.17 | 01-SEP-08:61 | 0.63 |
October | 75986242.84 | 0.58 | 226.17 | 01-OCT-08:61 | 0.63 |
November | 42888387.57 | 0.54 | 226.17 | 01-NOV-15:01 | 0.63 |
December | 38004455.91 | 0.52 | 226.17 | 01-DEC-16:01 | 0.63 |
Annual Sum or Average | 0.104626E+10 | 0.57 | |||
Minimum of Months | 26610167.47 | 0.50 | 226.17 | 0.63 | |
Maximum of Months | 0.172029E+09 | 0.62 | 226.17 | 0.64 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 23595067.22 | 0.40 | 224.60 | 01-JAN-09:02 | 0.63 |
February | 22152530.52 | 0.41 | 224.60 | 01-FEB-09:01 | 0.63 |
March | 23713007.04 | 0.38 | 224.60 | 01-MAR-16:01 | 0.63 |
April | 79536777.74 | 0.51 | 224.60 | 01-APR-08:52 | 0.63 |
May | 0.105808E+09 | 0.54 | 224.60 | 01-MAY-08:51 | 0.63 |
June | 0.173810E+09 | 0.58 | 224.60 | 01-JUN-07:21 | 0.63 |
July | 0.141506E+09 | 0.60 | 224.60 | 01-JUL-08:61 | 0.64 |
August | 0.131194E+09 | 0.57 | 224.60 | 01-AUG-08:61 | 0.63 |
September | 0.100381E+09 | 0.54 | 224.60 | 01-SEP-08:61 | 0.63 |
October | 48940385.57 | 0.44 | 224.60 | 01-OCT-08:61 | 0.63 |
November | 22074381.99 | 0.38 | 224.60 | 01-NOV-15:01 | 0.63 |
December | 36780250.97 | 0.41 | 224.60 | 01-DEC-09:01 | 0.63 |
Annual Sum or Average | 0.909491E+09 | 0.48 | |||
Minimum of Months | 22074381.99 | 0.38 | 224.60 | 0.63 | |
Maximum of Months | 0.173810E+09 | 0.60 | 224.60 | 0.64 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.467788E+09 | 0.59 | 1002.09 | 01-JAN-09:02 | 0.63 |
February | 0.217581E+09 | 0.54 | 1002.09 | 01-FEB-09:01 | 0.63 |
March | 0.254699E+09 | 0.55 | 1002.09 | 01-MAR-09:02 | 0.63 |
April | 0.470239E+09 | 0.60 | 1002.09 | 01-APR-08:61 | 0.63 |
May | 0.486259E+09 | 0.60 | 1002.09 | 01-MAY-08:61 | 0.64 |
June | 0.671077E+09 | 0.61 | 1002.09 | 01-JUN-08:61 | 0.63 |
July | 0.657606E+09 | 0.61 | 1002.09 | 01-JUL-08:61 | 0.64 |
August | 0.689760E+09 | 0.61 | 1002.09 | 01-AUG-08:61 | 0.63 |
September | 0.669774E+09 | 0.61 | 1002.09 | 01-SEP-08:61 | 0.63 |
October | 0.549213E+09 | 0.60 | 1002.09 | 01-OCT-08:61 | 0.63 |
November | 0.402941E+09 | 0.58 | 1002.09 | 01-NOV-08:62 | 0.63 |
December | 0.358620E+09 | 0.58 | 1002.09 | 01-DEC-09:01 | 0.63 |
Annual Sum or Average | 0.589556E+10 | 0.59 | |||
Minimum of Months | 0.217581E+09 | 0.54 | 1002.09 | 0.63 | |
Maximum of Months | 0.689760E+09 | 0.61 | 1002.09 | 0.64 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 83227116.88 | 74904405.19 | 354.91 | 31-JAN-16:01 | 319.42 | 319.42 | 6.72 | 8.90 |
February | 24577017.85 | 22119316.07 | 283.52 | 18-FEB-16:01 | 255.17 | 255.17 | 6.72 | 8.04 |
March | 87460887.76 | 78714798.98 | 738.44 | 16-MAR-18:09 | 664.60 | 664.60 | 6.72 | 12.28 |
April | 0.299600E+09 | 0.269640E+09 | 919.03 | 25-APR-19:10 | 827.12 | 827.12 | 6.72 | 13.47 |
May | 0.369349E+09 | 0.332414E+09 | 674.35 | 29-MAY-20:50 | 606.92 | 606.92 | 6.72 | 11.81 |
June | 0.767439E+09 | 0.690695E+09 | 1561.50 | 29-JUN-18:02 | 1405.35 | 1405.35 | 6.72 | 16.80 |
July | 0.894436E+09 | 0.804993E+09 | 1186.67 | 07-JUL-20:20 | 1068.01 | 1068.01 | 6.72 | 15.00 |
August | 0.862272E+09 | 0.776045E+09 | 1298.55 | 27-AUG-18:02 | 1168.70 | 1168.70 | 6.72 | 15.57 |
September | 0.827395E+09 | 0.744656E+09 | 1445.82 | 18-SEP-18:15 | 1301.24 | 1301.24 | 6.72 | 16.28 |
October | 0.332870E+09 | 0.299583E+09 | 1055.08 | 05-OCT-20:10 | 949.57 | 949.57 | 6.72 | 14.28 |
November | 0.103201E+09 | 92881051.79 | 809.19 | 01-NOV-18:01 | 728.27 | 728.27 | 6.72 | 12.77 |
December | 42625447.77 | 38362902.99 | 347.56 | 22-DEC-16:01 | 312.80 | 312.80 | 6.72 | 8.82 |
Annual Sum or Average | 0.469445E+10 | 0.422501E+10 | ||||||
Minimum of Months | 24577017.85 | 22119316.07 | 283.52 | 255.17 | 255.17 | 6.72 | 8.04 | |
Maximum of Months | 0.894436E+09 | 0.804993E+09 | 1561.50 | 1405.35 | 1405.35 | 6.72 | 16.80 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.711756E+10 | 0.640580E+10 | 2781.40 | 01-JAN-00:02 | 2503.26 | 2503.26 | 6.72 | 24.60 |
February | 0.596069E+10 | 0.536462E+10 | 2781.40 | 01-FEB-00:10 | 2503.26 | 2503.26 | 6.97 | 24.60 |
March | 0.705390E+10 | 0.634851E+10 | 2781.40 | 01-MAR-00:05 | 2503.26 | 2503.26 | 6.83 | 24.60 |
April | 0.720940E+10 | 0.648846E+10 | 2781.40 | 01-APR-00:10 | 2503.26 | 2503.26 | 6.97 | 24.60 |
May | 0.744971E+10 | 0.670474E+10 | 2781.40 | 01-MAY-00:05 | 2503.26 | 2503.26 | 7.89 | 24.60 |
June | 0.720940E+10 | 0.648846E+10 | 2781.40 | 01-JUN-00:05 | 2503.26 | 2503.26 | 8.95 | 24.60 |
July | 0.744971E+10 | 0.670474E+10 | 2781.40 | 01-JUL-00:10 | 2503.26 | 2503.26 | 9.39 | 24.60 |
August | 0.744971E+10 | 0.670474E+10 | 2781.40 | 01-AUG-00:05 | 2503.26 | 2503.26 | 9.67 | 24.60 |
September | 0.720940E+10 | 0.648846E+10 | 2781.40 | 01-SEP-00:05 | 2503.26 | 2503.26 | 9.20 | 24.60 |
October | 0.742065E+10 | 0.667858E+10 | 2781.40 | 01-OCT-00:10 | 2503.26 | 2503.26 | 8.98 | 24.60 |
November | 0.693653E+10 | 0.624288E+10 | 2781.40 | 01-NOV-00:05 | 2503.26 | 2503.26 | 7.45 | 24.60 |
December | 0.619939E+10 | 0.557945E+10 | 2781.40 | 01-DEC-00:10 | 2503.26 | 2503.26 | 6.81 | 24.60 |
Annual Sum or Average | 0.846661E+11 | 0.761994E+11 | ||||||
Minimum of Months | 0.596069E+10 | 0.536462E+10 | 2781.40 | 2503.26 | 2503.26 | 6.72 | 24.60 | |
Maximum of Months | 0.744971E+10 | 0.670474E+10 | 2781.40 | 2503.26 | 2503.26 | 9.67 | 24.60 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:02 | 14.37 | 14.37 | 49.59 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:10 | 14.37 | 14.37 | 51.57 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:05 | 14.37 | 14.37 | 51.61 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 54.24 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:05 | 14.37 | 14.37 | 54.57 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:05 | 14.37 | 14.37 | 55.08 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 55.55 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:05 | 14.37 | 14.37 | 55.49 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:05 | 14.37 | 14.37 | 55.28 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:10 | 14.37 | 14.37 | 54.41 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:05 | 14.37 | 14.37 | 54.32 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:10 | 14.37 | 14.37 | 52.07 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 49.59 | 0.37 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 55.55 | 0.37 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 74087.76 | 435150.16 | 31-JAN-16:01 | 10.92 | 6.70 | 0.00 | 0.00 | 01-JAN-00:02 |
February | 29692.92 | 303856.58 | 22-FEB-16:01 | 9.65 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 68662.61 | 422579.19 | 20-MAR-18:01 | 10.80 | 6.70 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 181947.14 | 493662.01 | 14-APR-18:03 | 11.49 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 222925.55 | 511472.59 | 31-MAY-18:03 | 11.66 | 6.70 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 293724.72 | 575192.00 | 01-JUN-18:03 | 12.28 | 6.70 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 321131.75 | 637900.21 | 13-JUL-18:01 | 12.89 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 313983.84 | 585250.21 | 09-AUG-18:01 | 12.38 | 6.70 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 298347.82 | 670188.07 | 10-SEP-21:52 | 13.21 | 6.70 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 159813.65 | 522287.65 | 01-OCT-18:01 | 11.77 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 82037.77 | 432167.22 | 09-NOV-16:01 | 10.89 | 6.70 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 44727.12 | 419292.09 | 22-DEC-16:01 | 10.77 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 175009.39 | 0.00 | ||||||
Minimum of Months | 29692.92 | 303856.58 | 9.65 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 321131.75 | 670188.07 | 13.21 | 6.70 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 49.59 | 60.06 | 22453.88 | 47070.48 | 23-JAN-07:40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 51.57 | 60.05 | 22233.48 | 46982.91 | 01-FEB-07:15 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 51.61 | 60.05 | 21195.41 | 45630.74 | 01-MAR-07:15 |
April | 0.00 | 0.00 | 01-APR-00:10 | 54.24 | 60.05 | 19529.24 | 42353.55 | 03-APR-06:30 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 54.57 | 60.05 | 17735.71 | 38873.09 | 01-MAY-07:00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 55.08 | 60.05 | 16285.69 | 35277.79 | 01-JUN-06:35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 55.55 | 60.05 | 15552.20 | 32869.77 | 03-JUL-06:20 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 55.49 | 60.05 | 15786.82 | 33841.57 | 31-AUG-06:40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 55.28 | 60.05 | 16868.43 | 36670.72 | 29-SEP-07:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 54.41 | 60.05 | 18527.32 | 40622.01 | 31-OCT-06:30 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 54.32 | 60.05 | 20320.15 | 45453.45 | 14-NOV-07:15 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 52.07 | 60.05 | 21754.71 | 46393.78 | 29-DEC-08:00 |
Annual Sum or Average | 0.00 | 19002.28 | ||||||
Minimum of Months | 0.00 | 0.00 | 49.59 | 60.05 | 15552.20 | 32869.77 | ||
Maximum of Months | 0.00 | 0.00 | 55.55 | 60.06 | 22453.88 | 47070.48 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.673140E+10 | 0.271000E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.173107E+10 | 0.244774E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.788858E+10 | 0.271000E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.209364E+11 | 0.262258E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.271449E+11 | 0.271000E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.322280E+11 | 0.262258E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.365742E+11 | 0.271000E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.364052E+11 | 0.271000E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.345802E+11 | 0.262258E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.179529E+11 | 0.271000E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.849251E+10 | 0.262258E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.357276E+10 | 0.271000E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.234238E+12 | 0.319080E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.173107E+10 | 0.244774E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.365742E+11 | 0.271000E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.107972E+12 | 0.885223E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.264415E+11 | 0.905673E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.116734E+12 | 0.764952E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.319960E+12 | 0.404455E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.415918E+12 | 0.409726E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.523412E+12 | 0.442326E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.609911E+12 | 0.455009E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.596575E+12 | 0.463265E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.549704E+12 | 0.451183E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.282087E+12 | 0.559977E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.123583E+12 | 0.736436E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.573642E+11 | 0.104011E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.372966E+13 | 0.751834E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.264415E+11 | 0.404455E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.609911E+12 | 0.104011E+12 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.271000E+10 | 0.673140E+10 | 0.00 | 0.117032E+11 | 2516532.88 | 0.00 | 0.00 | 0.00 |
February | 0.244774E+10 | 0.173107E+10 | 0.00 | 0.104045E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.271000E+10 | 0.788858E+10 | 0.00 | 0.970799E+10 | 64932453.20 | 0.00 | 0.00 | 0.00 |
April | 0.262258E+10 | 0.209364E+11 | 0.00 | 0.224662E+10 | 0.151848E+10 | 0.00 | 0.00 | 0.00 |
May | 0.271000E+10 | 0.271449E+11 | 0.00 | 0.209804E+10 | 0.295917E+10 | 0.00 | 0.00 | 0.00 |
June | 0.262258E+10 | 0.322280E+11 | 0.00 | 0.161146E+10 | 0.874248E+10 | 0.00 | 0.00 | 0.00 |
July | 0.271000E+10 | 0.365742E+11 | 0.00 | 0.467799E+09 | 0.240381E+11 | 0.00 | 0.00 | 0.00 |
August | 0.271000E+10 | 0.364052E+11 | 0.00 | 0.441114E+09 | 0.218518E+11 | 0.00 | 0.00 | 0.00 |
September | 0.262258E+10 | 0.345802E+11 | 0.00 | 0.246724E+09 | 0.165436E+11 | 0.00 | 0.00 | 0.00 |
October | 0.271000E+10 | 0.179529E+11 | 0.00 | 0.324914E+10 | 0.351062E+10 | 0.00 | 0.00 | 0.00 |
November | 0.262258E+10 | 0.849251E+10 | 0.00 | 0.887658E+10 | 95836563.47 | 0.00 | 0.00 | 0.00 |
December | 0.271000E+10 | 0.357276E+10 | 0.00 | 0.195570E+11 | 663951.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319080E+11 | 0.234238E+12 | 0.00 | 0.706102E+11 | 0.793282E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244774E+10 | 0.173107E+10 | 0.00 | 0.246724E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.271000E+10 | 0.365742E+11 | 0.00 | 0.195570E+11 | 0.240381E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.360182E+11 | 0.107972E+12 | 0.525041E+11 | 0.134431E+11 | 0.248746E+09 | 0.00 | 0.00 | 0.00 |
February | 0.303744E+11 | 0.264415E+11 | 0.601929E+11 | 0.143110E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.347257E+11 | 0.116734E+12 | 0.417695E+11 | 0.202650E+11 | 0.866883E+09 | 0.00 | 0.00 | 0.00 |
April | 0.381210E+11 | 0.319960E+12 | 0.232458E+10 | 0.108352E+11 | 0.204218E+11 | 0.00 | 0.00 | 0.00 |
May | 0.409497E+11 | 0.415918E+12 | 22887272.29 | 0.141299E+11 | 0.406602E+11 | 0.00 | 0.00 | 0.00 |
June | 0.442326E+11 | 0.523412E+12 | 0.00 | 0.263842E+11 | 0.766673E+11 | 0.00 | 0.00 | 0.00 |
July | 0.455009E+11 | 0.609911E+12 | 0.00 | 0.122786E+11 | 0.107482E+12 | 0.00 | 0.00 | 0.00 |
August | 0.463265E+11 | 0.596575E+12 | 0.00 | 0.137007E+11 | 0.940866E+11 | 0.00 | 0.00 | 0.00 |
September | 0.451183E+11 | 0.549704E+12 | 0.00 | 0.116437E+11 | 0.688842E+11 | 0.00 | 0.00 | 0.00 |
October | 0.419940E+11 | 0.282087E+12 | 0.140036E+11 | 0.824007E+10 | 0.182475E+11 | 0.00 | 0.00 | 0.00 |
November | 0.371171E+11 | 0.123583E+12 | 0.365266E+11 | 0.127378E+11 | 0.536805E+09 | 0.00 | 0.00 | 0.00 |
December | 0.358554E+11 | 0.573642E+11 | 0.681560E+11 | 0.721825E+11 | 24576869.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.476334E+12 | 0.372966E+13 | 0.275500E+12 | 0.217272E+12 | 0.428126E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.303744E+11 | 0.264415E+11 | 0.00 | 0.143110E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.463265E+11 | 0.609911E+12 | 0.681560E+11 | 0.721825E+11 | 0.107482E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.271000E+10 | 0.00 | 0.673140E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244774E+10 | 0.00 | 0.173107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.271000E+10 | 0.00 | 0.788858E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.262258E+10 | 0.00 | 0.209364E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.271000E+10 | 0.00 | 0.271449E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.262258E+10 | 0.00 | 0.322280E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.271000E+10 | 0.00 | 0.365742E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.271000E+10 | 0.00 | 0.364052E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.262258E+10 | 0.00 | 0.345802E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.271000E+10 | 0.00 | 0.179529E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.262258E+10 | 0.00 | 0.849251E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.271000E+10 | 0.00 | 0.357276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319080E+11 | 0.00 | 0.234238E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244774E+10 | 0.00 | 0.173107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.271000E+10 | 0.00 | 0.365742E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.360182E+11 | 0.00 | 0.107972E+12 | 0.00 | 0.00 | 0.525041E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.303744E+11 | 0.00 | 0.264415E+11 | 0.00 | 0.00 | 0.601929E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.347257E+11 | 0.00 | 0.116734E+12 | 0.00 | 0.00 | 0.417695E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.381210E+11 | 0.00 | 0.319960E+12 | 0.00 | 0.00 | 0.232458E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.409497E+11 | 0.00 | 0.415918E+12 | 0.00 | 0.00 | 22887272.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.442326E+11 | 0.00 | 0.523412E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455009E+11 | 0.00 | 0.609911E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.463265E+11 | 0.00 | 0.596575E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.451183E+11 | 0.00 | 0.549704E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.419940E+11 | 0.00 | 0.282087E+12 | 0.00 | 0.00 | 0.140036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.371171E+11 | 0.00 | 0.123583E+12 | 0.00 | 0.00 | 0.365266E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.358554E+11 | 0.00 | 0.573642E+11 | 0.00 | 0.00 | 0.681560E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.476334E+12 | 0.00 | 0.372966E+13 | 0.00 | 0.00 | 0.275500E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.303744E+11 | 0.00 | 0.264415E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.463265E+11 | 0.00 | 0.609911E+12 | 0.00 | 0.00 | 0.681560E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.313390E+10 | 755044.11 | 0.00 | 50106444.09 | 249484.78 | 0.00 | 0.430377E+11 | 0.00 | 1.03 |
February | 0.351824E+11 | 0.00 | 0.00 | 5809582.81 | 0.00 | 0.00 | 0.110913E+11 | 0.00 | 0.98 |
March | 0.399411E+11 | 0.00 | 0.00 | 121676.60 | 11541286.11 | 0.00 | 0.436111E+09 | 0.00 | 0.99 |
April | 0.177968E+11 | 0.00 | 0.00 | 1279825.02 | 0.586641E+09 | 0.00 | 0.117489E+10 | 0.00 | 0.95 |
May | 0.126991E+11 | 0.00 | 0.00 | 36022.18 | 0.134901E+10 | 0.00 | 79573160.48 | 0.00 | 0.92 |
June | 0.567116E+10 | 22043342.00 | 0.00 | 1095806.82 | 0.315510E+10 | 0.00 | 0.202749E+09 | 0.00 | 0.78 |
July | 0.522727E+09 | 0.542105E+10 | 0.00 | 21531187.96 | 0.976868E+09 | 0.00 | 0.224301E+10 | 0.00 | 0.82 |
August | 118594.71 | 0.533338E+10 | 0.00 | 36255735.38 | 0.300290E+09 | 0.00 | 0.383271E+10 | 0.00 | 0.93 |
September | 0.00 | 0.586836E+10 | 0.00 | 50345562.88 | 5021251.76 | 0.00 | 0.725374E+10 | 0.00 | 1.12 |
October | 0.00 | 0.814102E+09 | 0.00 | 0.103120E+09 | 0.00 | 0.00 | 0.362251E+11 | 0.00 | 1.27 |
November | 0.00 | 15407750.76 | 0.00 | 0.110705E+09 | 0.00 | 0.00 | 0.527788E+11 | 0.00 | 1.29 |
December | 3927167.66 | 0.00 | 0.00 | 0.105729E+09 | 0.00 | 0.00 | 0.628288E+11 | 0.00 | 1.21 |
Annual Sum or Average | 0.114951E+12 | 0.174751E+11 | 0.00 | 0.486136E+09 | 0.638472E+10 | 0.00 | 0.221184E+12 | 0.00 | 1.03 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 36022.18 | 0.00 | 0.00 | 79573160.48 | 0.00 | 0.78 |
Maximum of Months | 0.399411E+11 | 0.586836E+10 | 0.00 | 0.110705E+09 | 0.315510E+10 | 0.00 | 0.628288E+11 | 0.00 | 1.29 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.396583E+10 | 253394.87 | 0.00 | 5655813.05 | 0.00 | 0.00 | 0.178951E+10 | 0.00 | 2.61 |
February | 0.520320E+10 | 0.00 | 0.00 | 1216974.31 | 0.00 | 0.00 | 0.746659E+09 | 0.00 | 2.31 |
March | 0.472554E+10 | 1251040.51 | 0.00 | 1159972.14 | 375406.12 | 0.00 | 0.412935E+09 | 0.00 | 2.30 |
April | 0.158339E+10 | 0.102367E+09 | 0.00 | 3716020.59 | 128235.33 | 0.00 | 0.843545E+09 | 0.00 | 2.37 |
May | 0.971896E+09 | 0.193934E+09 | 0.00 | 2581749.96 | 3352474.94 | 0.00 | 0.664269E+09 | 0.00 | 2.24 |
June | 0.114375E+09 | 0.520570E+09 | 0.00 | 3524864.89 | 1256839.24 | 0.00 | 0.658168E+09 | 0.00 | 2.09 |
July | 62368255.42 | 0.883903E+09 | 0.00 | 1929790.43 | 28567854.19 | 0.00 | 0.286321E+09 | 0.00 | 2.03 |
August | 85291007.16 | 0.816746E+09 | 0.00 | 2197609.65 | 21286043.46 | 0.00 | 0.333655E+09 | 0.00 | 2.19 |
September | 0.176823E+09 | 0.684703E+09 | 0.00 | 2715005.11 | 82235122.35 | 0.00 | 0.489859E+09 | 0.00 | 2.38 |
October | 0.216399E+10 | 0.144382E+09 | 0.00 | 5052937.34 | 1456620.12 | 0.00 | 0.121424E+10 | 0.00 | 2.59 |
November | 0.356754E+10 | 208000.68 | 0.00 | 4771856.63 | 1845946.83 | 0.00 | 0.156149E+10 | 0.00 | 2.56 |
December | 0.505736E+10 | 0.00 | 0.00 | 3507592.42 | 0.00 | 2977291.04 | 0.131138E+10 | 0.00 | 2.44 |
Annual Sum or Average | 0.276776E+11 | 0.334832E+10 | 0.00 | 38030186.53 | 0.140505E+09 | 2977291.04 | 0.103120E+11 | 0.00 | 2.34 |
Minimum of Months | 62368255.42 | 0.00 | 0.00 | 1159972.14 | 0.00 | 0.00 | 0.286321E+09 | 0.00 | 2.03 |
Maximum of Months | 0.520320E+10 | 0.883903E+09 | 0.00 | 5655813.05 | 82235122.35 | 2977291.04 | 0.178951E+10 | 0.00 | 2.61 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.189710E+10 | 9094.11 | 0.00 | 1916786.11 | 83609.96 | 0.00 | 0.221192E+10 | 0.00 | 1.45 |
February | 0.331647E+10 | 0.00 | 0.00 | 594988.73 | 0.00 | 0.00 | 0.958199E+09 | 0.00 | 1.42 |
March | 0.234032E+10 | 0.00 | 0.00 | 1380361.24 | 1065100.50 | 0.00 | 0.142223E+10 | 0.00 | 1.45 |
April | 0.155443E+09 | 41274341.92 | 0.00 | 4863163.93 | 12985497.06 | 0.00 | 0.177878E+10 | 0.00 | 1.53 |
May | 22640407.06 | 0.107018E+09 | 0.00 | 4988501.45 | 18592763.81 | 0.00 | 0.132551E+10 | 0.00 | 1.52 |
June | 188722.16 | 0.298043E+09 | 0.00 | 5327566.41 | 10767051.96 | 0.00 | 0.704081E+09 | 0.00 | 1.38 |
July | 451462.90 | 0.598883E+09 | 0.00 | 2758528.99 | 33020179.89 | 0.00 | 0.312160E+09 | 0.00 | 1.33 |
August | 1092418.81 | 0.490870E+09 | 0.00 | 3252574.43 | 37245401.12 | 0.00 | 0.364448E+09 | 0.00 | 1.38 |
September | 4057500.22 | 0.449778E+09 | 0.00 | 3434963.57 | 39047456.70 | 0.00 | 0.554714E+09 | 0.00 | 1.45 |
October | 0.676584E+09 | 66536659.42 | 0.00 | 4048683.18 | 5166907.28 | 0.00 | 0.188820E+10 | 0.00 | 1.52 |
November | 0.157809E+10 | 73438.95 | 0.00 | 2107629.15 | 1343854.52 | 0.00 | 0.209405E+10 | 0.00 | 1.47 |
December | 0.302534E+10 | 0.00 | 0.00 | 900474.10 | 0.00 | 0.00 | 0.149176E+10 | 0.00 | 1.42 |
Annual Sum or Average | 0.130178E+11 | 0.205249E+10 | 0.00 | 35574221.28 | 0.159318E+09 | 0.00 | 0.151061E+11 | 0.00 | 1.44 |
Minimum of Months | 188722.16 | 0.00 | 0.00 | 594988.73 | 0.00 | 0.00 | 0.312160E+09 | 0.00 | 1.33 |
Maximum of Months | 0.331647E+10 | 0.598883E+09 | 0.00 | 5327566.41 | 39047456.70 | 0.00 | 0.221192E+10 | 0.00 | 1.53 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.361178E+10 | 0.00 | 0.00 | 0.00 | 83638.14 | 0.00 | 0.00 | 0.00 | 0.60 |
February | 0.384312E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
March | 0.336186E+10 | 0.00 | 0.00 | 0.00 | 960939.71 | 0.00 | 0.00 | 0.00 | 0.61 |
April | 0.135084E+10 | 209339.82 | 0.00 | 576864.35 | 48635025.72 | 0.00 | 0.233215E+09 | 0.00 | 0.59 |
May | 0.416672E+09 | 27615244.90 | 0.00 | 1954951.97 | 84822309.78 | 0.00 | 0.669171E+09 | 0.00 | 0.59 |
June | 34785.44 | 0.288838E+09 | 0.00 | 4849511.92 | 3582832.27 | 0.00 | 0.601154E+09 | 0.00 | 0.59 |
July | 4524588.95 | 0.564799E+09 | 0.00 | 2428217.28 | 24025692.70 | 0.00 | 0.267861E+09 | 0.00 | 0.57 |
August | 28754963.70 | 0.429073E+09 | 0.00 | 2529266.43 | 47731609.99 | 0.00 | 0.269588E+09 | 0.00 | 0.57 |
September | 37028105.78 | 0.341159E+09 | 0.00 | 2125112.60 | 90909492.75 | 0.00 | 0.415657E+09 | 0.00 | 0.58 |
October | 0.192974E+10 | 43385458.59 | 0.00 | 805799.61 | 20348776.81 | 0.00 | 0.246521E+09 | 0.00 | 0.60 |
November | 0.321550E+10 | 0.00 | 0.00 | 0.00 | 1278690.21 | 0.00 | 0.00 | 0.00 | 0.61 |
December | 0.404448E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
Annual Sum or Average | 0.218443E+11 | 0.169508E+10 | 0.00 | 15269724.18 | 0.322379E+09 | 0.00 | 0.270317E+10 | 0.00 | 0.59 |
Minimum of Months | 34785.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 |
Maximum of Months | 0.404448E+10 | 0.564799E+09 | 0.00 | 4849511.92 | 90909492.75 | 0.00 | 0.669171E+09 | 0.00 | 0.61 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.216023E+10 | 0.00 | 0.00 | 0.00 | 50024.51 | 0.00 | 0.00 | 0.00 | 0.62 |
February | 0.229859E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.62 |
March | 0.201075E+10 | 0.00 | 0.00 | 0.00 | 574744.20 | 0.00 | 0.00 | 0.00 | 0.63 |
April | 0.922221E+09 | 0.00 | 0.00 | 44922.76 | 29214127.92 | 0.00 | 22569343.51 | 0.00 | 0.61 |
May | 0.500534E+09 | 10825495.63 | 0.00 | 430094.67 | 56353690.12 | 0.00 | 0.136377E+09 | 0.00 | 0.59 |
June | 7226499.69 | 0.169180E+09 | 0.00 | 2279646.28 | 4114803.85 | 0.00 | 0.309397E+09 | 0.00 | 0.56 |
July | 6696099.40 | 0.310475E+09 | 0.00 | 1181674.22 | 20207305.68 | 0.00 | 0.136367E+09 | 0.00 | 0.55 |
August | 31344482.57 | 0.226951E+09 | 0.00 | 964431.32 | 42471844.28 | 0.00 | 0.132894E+09 | 0.00 | 0.55 |
September | 0.105579E+09 | 0.155601E+09 | 0.00 | 616619.22 | 89194269.18 | 0.00 | 0.152441E+09 | 0.00 | 0.56 |
October | 0.124280E+10 | 22682934.04 | 0.00 | 164585.54 | 14277921.54 | 0.00 | 54566465.28 | 0.00 | 0.62 |
November | 0.192321E+10 | 0.00 | 0.00 | 0.00 | 764792.81 | 0.00 | 0.00 | 0.00 | 0.63 |
December | 0.241903E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.62 |
Annual Sum or Average | 0.136282E+11 | 0.895716E+09 | 0.00 | 5681974.02 | 0.257224E+09 | 0.00 | 0.944612E+09 | 0.00 | 0.60 |
Minimum of Months | 6696099.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.55 |
Maximum of Months | 0.241903E+10 | 0.310475E+09 | 0.00 | 2279646.28 | 89194269.18 | 0.00 | 0.309397E+09 | 0.00 | 0.63 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.580931E+09 | 1257148.67 | 0.00 | 0.115555E+09 | 0.00 | 0.00 | 0.664036E+11 | 0.00 | 23.23 |
February | 0.366999E+09 | 0.00 | 0.00 | 94549960.60 | 0.00 | 0.00 | 0.696985E+11 | 0.00 | 23.15 |
March | 0.600977E+09 | 14443698.53 | 0.00 | 0.116355E+09 | 0.00 | 0.00 | 0.609594E+11 | 0.00 | 23.64 |
April | 0.00 | 0.740960E+09 | 0.00 | 0.109459E+09 | 0.00 | 0.00 | 0.279767E+11 | 0.00 | 22.46 |
May | 0.00 | 0.174348E+10 | 0.00 | 94248066.93 | 0.00 | 0.00 | 0.182227E+11 | 0.00 | 21.67 |
June | 0.00 | 0.427590E+10 | 0.00 | 65467908.53 | 0.00 | 0.00 | 0.810585E+10 | 0.00 | 18.04 |
July | 0.00 | 0.900693E+10 | 0.00 | 32558666.14 | 0.00 | 0.00 | 0.366781E+10 | 0.00 | 17.91 |
August | 0.00 | 0.760290E+10 | 0.00 | 40367467.62 | 0.00 | 0.00 | 0.448174E+10 | 0.00 | 18.78 |
September | 0.00 | 0.709211E+10 | 0.00 | 51347357.24 | 0.00 | 0.00 | 0.735134E+10 | 0.00 | 20.09 |
October | 61097003.54 | 0.100979E+10 | 0.00 | 0.108007E+09 | 0.00 | 0.00 | 0.397307E+11 | 0.00 | 22.95 |
November | 0.296013E+09 | 19219744.70 | 0.00 | 0.112323E+09 | 0.00 | 0.00 | 0.593646E+11 | 0.00 | 23.50 |
December | 0.428948E+09 | 0.00 | 0.00 | 0.109880E+09 | 0.00 | 0.00 | 0.747767E+11 | 0.00 | 22.90 |
Annual Sum or Average | 0.233497E+10 | 0.315070E+11 | 0.00 | 0.105012E+10 | 0.00 | 0.00 | 0.440740E+12 | 0.00 | 21.52 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 32558666.14 | 0.00 | 0.00 | 0.366781E+10 | 0.00 | 17.91 |
Maximum of Months | 0.600977E+09 | 0.900693E+10 | 0.00 | 0.116355E+09 | 0.00 | 0.00 | 0.747767E+11 | 0.00 | 23.64 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.214334E+10 | 918996.46 | 0.00 | 46235813.07 | 0.00 | 0.00 | 0.234906E+11 | 0.00 | 4.03 |
February | 0.586815E+10 | 0.00 | 0.00 | 21311888.74 | 0.00 | 0.00 | 0.197810E+11 | 0.00 | 3.56 |
March | 0.517797E+10 | 6815513.50 | 0.00 | 25082582.54 | 17175.10 | 0.00 | 0.171662E+11 | 0.00 | 3.58 |
April | 0.896611E+09 | 0.381274E+09 | 0.00 | 32296001.93 | 1381399.13 | 0.00 | 0.106381E+11 | 0.00 | 3.81 |
May | 0.296054E+09 | 0.757983E+09 | 0.00 | 26248296.54 | 15569409.27 | 0.00 | 0.771397E+10 | 0.00 | 3.66 |
June | 27099054.13 | 0.187425E+10 | 0.00 | 25563744.42 | 27802807.61 | 0.00 | 0.407447E+10 | 0.00 | 3.28 |
July | 4575942.09 | 0.366957E+10 | 0.00 | 14725425.38 | 84997754.44 | 0.00 | 0.181817E+10 | 0.00 | 3.23 |
August | 16661121.18 | 0.323500E+10 | 0.00 | 17560189.73 | 51252690.44 | 0.00 | 0.219355E+10 | 0.00 | 3.46 |
September | 44990314.23 | 0.306646E+10 | 0.00 | 20218029.46 | 58399422.23 | 0.00 | 0.343894E+10 | 0.00 | 3.77 |
October | 0.124940E+10 | 0.540378E+09 | 0.00 | 40025410.61 | 3257246.34 | 0.00 | 0.144289E+11 | 0.00 | 4.07 |
November | 0.144959E+10 | 760060.70 | 0.00 | 40938499.94 | 7830941.02 | 0.00 | 0.213679E+11 | 0.00 | 3.96 |
December | 0.365506E+10 | 0.00 | 0.00 | 33937817.45 | 0.00 | 0.00 | 0.240269E+11 | 0.00 | 3.76 |
Annual Sum or Average | 0.208295E+11 | 0.135334E+11 | 0.00 | 0.344144E+09 | 0.250509E+09 | 0.00 | 0.150139E+12 | 0.00 | 3.68 |
Minimum of Months | 4575942.09 | 0.00 | 0.00 | 14725425.38 | 0.00 | 0.00 | 0.181817E+10 | 0.00 | 3.23 |
Maximum of Months | 0.586815E+10 | 0.366957E+10 | 0.00 | 46235813.07 | 84997754.44 | 0.00 | 0.240269E+11 | 0.00 | 4.07 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.928810E+10 | 1843321.46 | 0.00 | 0.103659E+09 | 0.00 | 0.00 | 0.762481E+11 | 0.00 | 1.78 |
February | 0.297151E+11 | 0.00 | 0.00 | 46836876.14 | 0.00 | 0.00 | 0.568639E+11 | 0.00 | 1.71 |
March | 0.220211E+11 | 6087911.31 | 0.00 | 64651153.72 | 15090474.41 | 0.00 | 0.549808E+11 | 0.00 | 1.76 |
April | 0.224318E+10 | 0.100161E+10 | 0.00 | 0.103481E+09 | 76625550.44 | 0.00 | 0.386211E+11 | 0.00 | 1.85 |
May | 0.436688E+09 | 0.224374E+10 | 0.00 | 0.101248E+09 | 0.242130E+09 | 0.00 | 0.283943E+11 | 0.00 | 1.84 |
June | 21252107.81 | 0.571972E+10 | 0.00 | 0.102011E+09 | 0.303785E+09 | 0.00 | 0.146789E+11 | 0.00 | 1.62 |
July | 2759086.29 | 0.119810E+11 | 0.00 | 56787080.11 | 0.623497E+09 | 0.00 | 0.656823E+10 | 0.00 | 1.60 |
August | 7668954.66 | 0.989041E+10 | 0.00 | 66802320.87 | 0.589034E+09 | 0.00 | 0.776619E+10 | 0.00 | 1.67 |
September | 69883133.80 | 0.961352E+10 | 0.00 | 72969379.59 | 0.373011E+09 | 0.00 | 0.122013E+11 | 0.00 | 1.79 |
October | 0.480605E+10 | 0.145089E+10 | 0.00 | 0.113489E+09 | 25226103.20 | 0.00 | 0.494595E+11 | 0.00 | 1.88 |
November | 0.729308E+10 | 1505806.78 | 0.00 | 97564208.65 | 26708092.34 | 0.00 | 0.692191E+11 | 0.00 | 1.80 |
December | 0.222126E+11 | 0.00 | 0.00 | 70860298.05 | 0.00 | 0.00 | 0.699876E+11 | 0.00 | 1.71 |
Annual Sum or Average | 0.981175E+11 | 0.419103E+11 | 0.00 | 0.100036E+10 | 0.227511E+10 | 0.00 | 0.484989E+12 | 0.00 | 1.75 |
Minimum of Months | 2759086.29 | 0.00 | 0.00 | 46836876.14 | 0.00 | 0.00 | 0.656823E+10 | 0.00 | 1.60 |
Maximum of Months | 0.297151E+11 | 0.119810E+11 | 0.00 | 0.113489E+09 | 0.623497E+09 | 0.00 | 0.762481E+11 | 0.00 | 1.88 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 5372944.09 | 558863.60 | 20556.50 | 10858049.77 | 0.00 | 0.139464E+09 | 0.104463E+10 | 1878.08 | 0.35 |
February | 36671651.89 | 25928.20 | 0.00 | 4941653.70 | 0.00 | 0.349897E+09 | 0.749833E+09 | 0.00 | 0.36 |
March | 37483996.83 | 81935.23 | 0.00 | 9311473.86 | 0.00 | 0.229575E+09 | 0.849125E+09 | 0.00 | 0.36 |
April | 0.00 | 3722861.14 | 0.00 | 16315851.58 | 0.00 | 906179.42 | 0.650021E+09 | 0.00 | 0.35 |
May | 0.00 | 7027487.80 | 971.73 | 16427497.53 | 0.00 | 315862.84 | 0.475087E+09 | 5019.77 | 0.36 |
June | 0.00 | 57649736.48 | 0.00 | 13967650.28 | 0.00 | 22048.28 | 0.161517E+09 | 0.00 | 0.36 |
July | 0.00 | 0.537300E+09 | 479962.33 | 2824686.06 | 0.00 | 4173.30 | 59764677.13 | 28945.96 | 0.36 |
August | 0.00 | 0.500705E+09 | 441079.64 | 2199338.03 | 0.00 | 32842.98 | 39845066.96 | 37881.39 | 0.36 |
September | 0.00 | 0.412293E+09 | 346142.49 | 3451703.82 | 0.00 | 74224.98 | 41090937.92 | 31396.05 | 0.36 |
October | 3546832.18 | 72404832.22 | 28339.78 | 11827172.24 | 0.00 | 26333064.29 | 0.695409E+09 | 7167.19 | 0.36 |
November | 3916758.23 | 12559072.74 | 19685.30 | 9797539.00 | 784405.74 | 0.114188E+09 | 0.892146E+09 | 3510.94 | 0.36 |
December | 26108980.93 | 0.00 | 0.00 | 6175030.78 | 380863.76 | 0.479560E+09 | 0.828221E+09 | 0.00 | 0.35 |
Annual Sum or Average | 0.113101E+09 | 0.160433E+10 | 1336737.76 | 0.108098E+09 | 1165269.50 | 0.134037E+10 | 0.648669E+10 | 115799.40 | 0.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 2199338.03 | 0.00 | 4173.30 | 39845066.96 | 0.00 | 0.35 |
Maximum of Months | 37483996.83 | 0.537300E+09 | 479962.33 | 16427497.53 | 784405.74 | 0.479560E+09 | 0.104463E+10 | 37881.39 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.188553E+09 | 115092.52 | 19737.56 | 3688178.38 | 443705.61 | 0.374218E+09 | 0.633724E+09 | 2694.39 | 0.35 |
February | 0.160057E+09 | 25925.16 | 0.00 | 1949860.23 | 0.00 | 0.579964E+09 | 0.399239E+09 | 0.00 | 0.36 |
March | 0.228548E+09 | 81925.63 | 0.00 | 4826081.99 | 0.00 | 0.298898E+09 | 0.593091E+09 | 0.00 | 0.36 |
April | 0.109517E+09 | 3700397.81 | 0.00 | 12967343.01 | 16065.34 | 828801.60 | 0.543852E+09 | 5961.80 | 0.36 |
May | 85520394.24 | 7024465.80 | 6096.22 | 13924667.41 | 0.00 | 86192.90 | 0.392242E+09 | 2093.20 | 0.36 |
June | 34573418.49 | 57640755.27 | 0.00 | 12394585.61 | 2226.70 | 27130.73 | 0.128491E+09 | 0.00 | 0.36 |
July | 11778664.20 | 0.528856E+09 | 512814.55 | 2388849.35 | 8351337.66 | 5891.74 | 48412797.45 | 25286.39 | 0.36 |
August | 9245707.01 | 0.479950E+09 | 494820.17 | 1662090.53 | 20647529.26 | 0.00 | 31164520.47 | 33427.99 | 0.36 |
September | 14955861.78 | 0.371196E+09 | 414578.44 | 2660534.84 | 40969666.91 | 22771.17 | 26972471.42 | 42638.09 | 0.36 |
October | 0.171061E+09 | 67841365.73 | 39690.25 | 6907826.81 | 4534404.34 | 53809927.28 | 0.505252E+09 | 16391.43 | 0.36 |
November | 0.200967E+09 | 11096838.72 | 17649.49 | 3861054.80 | 2245076.38 | 0.262460E+09 | 0.552640E+09 | 5544.04 | 0.36 |
December | 0.169423E+09 | 0.00 | 0.00 | 1799203.48 | 380819.13 | 0.850706E+09 | 0.317980E+09 | 0.00 | 0.35 |
Annual Sum or Average | 0.138420E+10 | 0.152753E+10 | 1505386.69 | 69030276.43 | 77590831.33 | 0.242103E+10 | 0.417306E+10 | 134037.33 | 0.36 |
Minimum of Months | 9245707.01 | 0.00 | 0.00 | 1662090.53 | 0.00 | 0.00 | 26972471.42 | 0.00 | 0.35 |
Maximum of Months | 0.228548E+09 | 0.528856E+09 | 512814.55 | 13924667.41 | 40969666.91 | 0.850706E+09 | 0.633724E+09 | 42638.09 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 2068385.32 | 0.00 | 6738627.98 | 0.00 | 0.00 | 0.917410E+09 | 0.00 | 0.02 |
February | 0.273820E+09 | 0.00 | 0.00 | 2468724.00 | 0.00 | 0.00 | 0.891604E+09 | 0.00 | 0.02 |
March | 0.131085E+09 | 0.00 | 0.00 | 2723297.84 | 0.00 | 0.00 | 0.812730E+09 | 0.00 | 0.02 |
April | 0.00 | 2075549.49 | 0.00 | 4343454.90 | 0.00 | 0.00 | 0.245357E+09 | 0.00 | 0.02 |
May | 0.00 | 3599680.12 | 0.00 | 3529151.89 | 0.00 | 0.00 | 0.135982E+09 | 0.00 | 0.02 |
June | 0.00 | 0.101845E+09 | 0.00 | 1396176.97 | 0.00 | 0.00 | 27447601.59 | 0.00 | 0.02 |
July | 0.00 | 0.357838E+09 | 0.00 | 466340.18 | 0.00 | 0.00 | 8498648.79 | 0.00 | 0.02 |
August | 0.00 | 0.398704E+09 | 0.00 | 257049.87 | 0.00 | 0.00 | 2806511.50 | 0.00 | 0.02 |
September | 0.00 | 0.343771E+09 | 0.00 | 962934.27 | 0.00 | 0.00 | 6801858.58 | 0.00 | 0.02 |
October | 0.00 | 67124567.11 | 0.00 | 4660090.52 | 0.00 | 0.00 | 0.468710E+09 | 0.00 | 0.02 |
November | 0.00 | 6114502.31 | 0.00 | 4904584.05 | 8876921.32 | 0.00 | 0.825708E+09 | 0.00 | 0.02 |
December | 56244210.17 | 0.00 | 0.00 | 5143557.09 | 0.00 | 0.00 | 0.112459E+10 | 0.00 | 0.02 |
Annual Sum or Average | 0.461149E+09 | 0.128314E+10 | 0.00 | 37593989.57 | 8876921.32 | 0.00 | 0.546765E+10 | 0.00 | 0.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 257049.87 | 0.00 | 0.00 | 2806511.50 | 0.00 | 0.02 |
Maximum of Months | 0.273820E+09 | 0.398704E+09 | 0.00 | 6738627.98 | 8876921.32 | 0.00 | 0.112459E+10 | 0.00 | 0.02 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.255679E+10 | 1561160.94 | 263286.54 | 53314418.96 | 6018600.38 | 0.722469E+09 | 0.129472E+11 | 40989.40 | 0.40 |
February | 0.217108E+10 | 351659.21 | 0.00 | 46425018.40 | 0.00 | 0.254807E+09 | 0.130075E+11 | 0.00 | 0.41 |
March | 0.312653E+10 | 1111272.00 | 0.00 | 77790573.42 | 0.00 | 0.300876E+09 | 0.117597E+11 | 0.00 | 0.40 |
April | 0.157026E+10 | 38037575.67 | 163539.58 | 0.111045E+09 | 12257810.21 | 11177909.67 | 0.735720E+10 | 33535.97 | 0.40 |
May | 0.118182E+10 | 93517051.79 | 7244.99 | 0.116419E+09 | 1839125.46 | 1625432.71 | 0.537074E+10 | 30326.96 | 0.40 |
June | 0.468968E+09 | 0.781453E+09 | 406996.22 | 0.105276E+09 | 30203.86 | 82707.94 | 0.180604E+10 | 2700.53 | 0.40 |
July | 0.159771E+09 | 0.716658E+10 | 8134096.74 | 20155278.52 | 0.119358E+09 | 27057.36 | 0.668991E+09 | 131097.45 | 0.40 |
August | 0.125412E+09 | 0.649648E+10 | 10898914.68 | 13284349.11 | 0.289866E+09 | 21967.33 | 0.431967E+09 | 222194.05 | 0.40 |
September | 0.203531E+09 | 0.497768E+10 | 10677562.69 | 23587760.78 | 0.608281E+09 | 63789.33 | 0.377948E+09 | 344269.77 | 0.40 |
October | 0.234796E+10 | 0.895629E+09 | 1464388.15 | 73971217.40 | 85293740.33 | 35403739.07 | 0.754004E+10 | 107596.82 | 0.40 |
November | 0.275358E+10 | 0.149270E+09 | 329646.15 | 52885771.25 | 31630522.43 | 0.326545E+09 | 0.107017E+11 | 59078.27 | 0.40 |
December | 0.229813E+10 | 0.00 | 0.00 | 34726190.01 | 5165583.09 | 0.253005E+10 | 0.133121E+11 | 0.00 | 0.40 |
Annual Sum or Average | 0.189638E+11 | 0.206017E+11 | 32345675.73 | 0.728881E+09 | 0.115974E+10 | 0.418315E+10 | 0.852812E+11 | 971789.21 | 0.40 |
Minimum of Months | 0.125412E+09 | 0.00 | 0.00 | 13284349.11 | 0.00 | 21967.33 | 0.377948E+09 | 0.00 | 0.40 |
Maximum of Months | 0.312653E+10 | 0.716658E+10 | 10898914.68 | 0.116419E+09 | 0.608281E+09 | 0.253005E+10 | 0.133121E+11 | 344269.77 | 0.41 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 5119979.84 | 558863.60 | 19139.64 | 10633118.31 | 0.00 | 0.177796E+09 | 0.100677E+10 | 3294.94 | 0.35 |
February | 28340322.49 | 25928.20 | 0.00 | 5717206.44 | 0.00 | 0.340383E+09 | 0.766903E+09 | 0.00 | 0.36 |
March | 18943518.17 | 81935.23 | 0.00 | 9853704.47 | 0.00 | 0.199241E+09 | 0.897456E+09 | 0.00 | 0.36 |
April | 0.00 | 3722861.14 | 0.00 | 17160278.64 | 0.00 | 106164.09 | 0.649977E+09 | 0.00 | 0.35 |
May | 0.00 | 7033479.30 | 0.00 | 17730207.01 | 0.00 | 8989.35 | 0.474091E+09 | 0.00 | 0.36 |
June | 0.00 | 57649736.48 | 0.00 | 14743638.62 | 0.00 | 0.00 | 0.160763E+09 | 0.00 | 0.36 |
July | 0.00 | 0.537796E+09 | 13143.17 | 2896620.97 | 0.00 | 0.00 | 59696915.53 | 117.21 | 0.36 |
August | 0.00 | 0.501167E+09 | 14371.96 | 2173976.45 | 0.00 | 28580.47 | 39874691.05 | 2567.58 | 0.36 |
September | 0.00 | 0.412581E+09 | 87803.19 | 3549851.60 | 0.00 | 7079.66 | 41059935.46 | 2390.91 | 0.36 |
October | 931746.27 | 72440339.19 | 0.00 | 12329369.32 | 0.00 | 17923939.48 | 0.705931E+09 | 0.00 | 0.36 |
November | 3548237.39 | 12552158.50 | 25758.32 | 9724430.39 | 784405.74 | 0.147512E+09 | 0.859264E+09 | 4352.17 | 0.36 |
December | 23682749.55 | 0.00 | 0.00 | 6761182.82 | 380863.76 | 0.485119E+09 | 0.824502E+09 | 0.00 | 0.35 |
Annual Sum or Average | 80566553.71 | 0.160561E+10 | 160216.28 | 0.113274E+09 | 1165269.50 | 0.136813E+10 | 0.648629E+10 | 12722.81 | 0.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 2173976.45 | 0.00 | 0.00 | 39874691.05 | 0.00 | 0.35 |
Maximum of Months | 28340322.49 | 0.537796E+09 | 87803.19 | 17730207.01 | 784405.74 | 0.485119E+09 | 0.100677E+10 | 4352.17 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.188186E+09 | 115092.52 | 19456.76 | 4132893.37 | 443705.61 | 0.408415E+09 | 0.599450E+09 | 2975.18 | 0.35 |
February | 0.160057E+09 | 25925.16 | 0.00 | 2792637.47 | 0.00 | 0.489282E+09 | 0.489078E+09 | 0.00 | 0.36 |
March | 0.222639E+09 | 81925.63 | 0.00 | 5929578.27 | 0.00 | 0.279271E+09 | 0.617524E+09 | 0.00 | 0.36 |
April | 0.104102E+09 | 3721596.92 | 0.00 | 13218807.56 | 828.04 | 443962.88 | 0.549401E+09 | 0.00 | 0.36 |
May | 82962822.65 | 7032655.22 | 0.00 | 14059730.52 | 0.00 | 27224.68 | 0.394723E+09 | 0.00 | 0.36 |
June | 33647493.67 | 57640755.27 | 0.00 | 12633298.49 | 2226.70 | 0.00 | 0.129206E+09 | 0.00 | 0.36 |
July | 11667833.97 | 0.529500E+09 | 0.00 | 2354498.47 | 8245481.20 | 0.00 | 48563870.31 | 0.00 | 0.36 |
August | 9215675.56 | 0.480653E+09 | 7458.94 | 1596602.47 | 20464264.72 | 0.00 | 31260039.98 | 1142.39 | 0.36 |
September | 14879089.82 | 0.372349E+09 | 106542.18 | 2632554.60 | 40164322.43 | 223.63 | 27099771.15 | 2489.25 | 0.36 |
October | 0.167860E+09 | 68022953.44 | 15967.36 | 7349081.86 | 4387752.51 | 35467142.66 | 0.526354E+09 | 5178.44 | 0.36 |
November | 0.200995E+09 | 11087530.42 | 27590.88 | 4035210.91 | 2245076.38 | 0.304163E+09 | 0.510735E+09 | 4910.95 | 0.36 |
December | 0.169423E+09 | 0.00 | 0.00 | 2064300.10 | 380819.13 | 0.771525E+09 | 0.396895E+09 | 0.00 | 0.35 |
Annual Sum or Average | 0.136564E+10 | 0.153023E+10 | 177016.13 | 72799194.07 | 76334476.71 | 0.228859E+10 | 0.432029E+10 | 16696.21 | 0.36 |
Minimum of Months | 9215675.56 | 0.00 | 0.00 | 1596602.47 | 0.00 | 0.00 | 27099771.15 | 0.00 | 0.35 |
Maximum of Months | 0.222639E+09 | 0.529500E+09 | 106542.18 | 14059730.52 | 40164322.43 | 0.771525E+09 | 0.617524E+09 | 5178.44 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.261807E+11 | 0.00 | 0.00 | 0.00 | 606267.90 | 0.00 | 0.00 | 0.00 | 0.60 |
February | 0.278576E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
March | 0.243691E+11 | 0.00 | 0.00 | 0.00 | 6965564.97 | 0.00 | 0.00 | 0.00 | 0.60 |
April | 0.111440E+11 | 5214368.97 | 0.00 | 620222.39 | 0.348844E+09 | 0.00 | 0.306408E+09 | 0.00 | 0.58 |
May | 0.626743E+10 | 88755151.89 | 0.00 | 3717213.47 | 0.725417E+09 | 0.00 | 0.144414E+10 | 0.00 | 0.57 |
June | 0.495398E+09 | 0.174815E+10 | 0.00 | 16935008.99 | 0.231587E+09 | 0.00 | 0.317687E+10 | 0.00 | 0.51 |
July | 0.227948E+09 | 0.297823E+10 | 0.00 | 8411797.99 | 0.800019E+09 | 0.00 | 0.142635E+10 | 0.00 | 0.49 |
August | 0.527156E+09 | 0.223751E+10 | 0.00 | 9088776.37 | 0.939373E+09 | 0.00 | 0.143965E+10 | 0.00 | 0.51 |
September | 0.125679E+10 | 0.170066E+10 | 0.00 | 6879567.93 | 0.123809E+10 | 0.00 | 0.186530E+10 | 0.00 | 0.54 |
October | 0.147064E+11 | 0.289992E+09 | 0.00 | 2507719.57 | 0.157095E+09 | 0.00 | 0.102797E+10 | 0.00 | 0.60 |
November | 0.233082E+11 | 0.00 | 0.00 | 0.00 | 9268843.44 | 0.00 | 0.00 | 0.00 | 0.60 |
December | 0.293172E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
Annual Sum or Average | 0.165658E+12 | 0.904851E+10 | 0.00 | 48160306.71 | 0.445727E+10 | 0.00 | 0.106867E+11 | 0.00 | 0.57 |
Minimum of Months | 0.227948E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.49 |
Maximum of Months | 0.293172E+11 | 0.297823E+10 | 0.00 | 16935008.99 | 0.123809E+10 | 0.00 | 0.317687E+10 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 1553158.20 | 139715.90 | 5253.86 | 2391581.49 | 0.00 | 0.109114E+09 | 0.187022E+09 | 354.78 | 0.35 |
February | 10244990.18 | 6482.05 | 0.00 | 1049222.78 | 0.00 | 0.151079E+09 | 0.122963E+09 | 0.00 | 0.36 |
March | 9290736.56 | 20483.81 | 0.00 | 2148319.83 | 0.00 | 0.103961E+09 | 0.165974E+09 | 0.00 | 0.36 |
April | 0.00 | 930715.29 | 0.00 | 3899851.01 | 0.00 | 1245453.86 | 0.161665E+09 | 0.00 | 0.35 |
May | 0.00 | 1756871.95 | 270.47 | 3949287.36 | 0.00 | 109083.06 | 0.118899E+09 | 1227.40 | 0.36 |
June | 0.00 | 14409736.59 | 2546.67 | 3417394.45 | 0.00 | 18966.14 | 40440400.84 | 150.86 | 0.36 |
July | 0.00 | 0.134309E+09 | 135905.31 | 674011.95 | 0.00 | 2005.54 | 14972366.63 | 7816.02 | 0.36 |
August | 0.00 | 0.125136E+09 | 150056.56 | 523873.08 | 0.00 | 8210.74 | 9987228.17 | 10188.94 | 0.36 |
September | 0.00 | 0.103070E+09 | 89326.55 | 808862.82 | 0.00 | 18556.24 | 10326797.62 | 8614.86 | 0.36 |
October | 1370660.39 | 18098120.60 | 9465.61 | 2647439.66 | 0.00 | 32682652.74 | 0.147578E+09 | 2498.58 | 0.36 |
November | 1904792.81 | 3141580.92 | 3060.08 | 2119423.67 | 196101.44 | 81276837.77 | 0.169711E+09 | 926.25 | 0.36 |
December | 8225431.01 | 0.00 | 0.00 | 1315085.61 | 95215.94 | 0.188997E+09 | 0.136479E+09 | 0.00 | 0.35 |
Annual Sum or Average | 32589769.15 | 0.401018E+09 | 395885.12 | 24944353.70 | 291317.37 | 0.668513E+09 | 0.128602E+10 | 31777.70 | 0.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 523873.08 | 0.00 | 2005.54 | 9987228.17 | 0.00 | 0.35 |
Maximum of Months | 10244990.18 | 0.134309E+09 | 150056.56 | 3949287.36 | 196101.44 | 0.188997E+09 | 0.187022E+09 | 10188.94 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 47363252.72 | 28773.13 | 4920.37 | 719776.72 | 110926.40 | 0.175408E+09 | 76555050.53 | 687.62 | 0.35 |
February | 40014322.15 | 6481.29 | 0.00 | 382067.01 | 0.00 | 0.199468E+09 | 45437950.45 | 0.00 | 0.36 |
March | 57003009.52 | 20481.41 | 0.00 | 1052984.64 | 0.00 | 0.118478E+09 | 0.104807E+09 | 0.00 | 0.36 |
April | 27012150.56 | 925099.45 | 0.00 | 3134614.25 | 4016.34 | 294968.35 | 0.136349E+09 | 1490.45 | 0.36 |
May | 21380098.56 | 1756302.94 | 1151.30 | 3427966.34 | 0.00 | 25104.34 | 98110043.49 | 709.57 | 0.36 |
June | 8643354.62 | 14407571.06 | 2617.47 | 3089178.80 | 556.68 | 6486.56 | 32132600.64 | 0.28 | 0.36 |
July | 2944666.05 | 0.132206E+09 | 135504.15 | 583478.86 | 2087834.41 | 2435.04 | 12115970.74 | 7396.45 | 0.36 |
August | 2311426.75 | 0.119953E+09 | 156566.88 | 403872.68 | 5161882.32 | 0.00 | 7802780.07 | 10244.89 | 0.36 |
September | 3738965.45 | 92783808.54 | 115481.09 | 630427.36 | 10242416.73 | 5636.88 | 6777880.11 | 13963.41 | 0.36 |
October | 42827653.97 | 16944991.25 | 13188.33 | 1487897.55 | 1145694.11 | 47058951.50 | 92883040.45 | 4089.25 | 0.36 |
November | 50411777.64 | 2776022.20 | 2472.72 | 758136.45 | 561269.09 | 0.123013E+09 | 80799255.08 | 1513.14 | 0.36 |
December | 42355836.92 | 0.00 | 0.00 | 351392.62 | 95204.78 | 0.255209E+09 | 37060387.11 | 0.00 | 0.35 |
Annual Sum or Average | 0.346007E+09 | 0.381808E+09 | 431902.33 | 16021793.28 | 19409800.86 | 0.918970E+09 | 0.730832E+09 | 40095.06 | 0.36 |
Minimum of Months | 2311426.75 | 0.00 | 0.00 | 351392.62 | 0.00 | 0.00 | 6777880.11 | 0.00 | 0.35 |
Maximum of Months | 57003009.52 | 0.132206E+09 | 156566.88 | 3427966.34 | 10242416.73 | 0.255209E+09 | 0.136349E+09 | 13963.41 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 933635.99 | 0.00 | 26275731.81 | 0.00 | 58887914.31 | 0.184270E+10 | 0.00 | 0.40 |
February | 24451317.56 | 41643.85 | 0.00 | 12838143.76 | 0.00 | 0.224709E+09 | 0.157114E+10 | 0.00 | 0.41 |
March | 17385872.51 | 131598.00 | 0.00 | 15847091.95 | 0.00 | 0.224081E+09 | 0.155037E+10 | 0.00 | 0.40 |
April | 0.00 | 5979370.43 | 0.00 | 21391741.80 | 0.00 | 1614856.51 | 0.104867E+10 | 0.00 | 0.40 |
May | 0.00 | 11286710.79 | 1523.47 | 20333119.70 | 0.00 | 473856.03 | 0.769133E+09 | 8393.94 | 0.40 |
June | 0.00 | 92592529.40 | 0.00 | 16877964.63 | 0.00 | 61155.02 | 0.264947E+09 | 0.00 | 0.40 |
July | 0.00 | 0.863069E+09 | 666050.62 | 3422681.47 | 0.00 | 31452.81 | 97078742.75 | 52031.41 | 0.40 |
August | 0.00 | 0.804298E+09 | 606299.51 | 2800087.82 | 0.00 | 50739.05 | 64730380.91 | 58571.63 | 0.40 |
September | 0.00 | 0.662509E+09 | 252941.53 | 4963111.73 | 0.00 | 40372.33 | 66656662.13 | 38466.48 | 0.40 |
October | 0.00 | 0.116269E+09 | 69524.91 | 20286990.37 | 0.00 | 4180299.51 | 0.115943E+10 | 9140.73 | 0.40 |
November | 1559852.51 | 20175254.15 | 29606.58 | 21231906.60 | 1259851.58 | 57964130.05 | 0.155757E+10 | 3802.53 | 0.40 |
December | 4153501.61 | 0.00 | 0.00 | 19858833.44 | 611713.79 | 0.315201E+09 | 0.181310E+10 | 0.00 | 0.40 |
Annual Sum or Average | 47550544.20 | 0.257729E+10 | 1625946.61 | 0.186127E+09 | 1871565.37 | 0.887296E+09 | 0.118055E+11 | 170406.72 | 0.40 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 2800087.82 | 0.00 | 31452.81 | 64730380.91 | 0.00 | 0.40 |
Maximum of Months | 24451317.56 | 0.863069E+09 | 666050.62 | 26275731.81 | 1259851.58 | 0.315201E+09 | 0.184270E+10 | 58571.63 | 0.41 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.376221E+09 | 853700.88 | 0.00 | 78391180.63 | 0.00 | 0.00 | 0.451959E+11 | 0.00 | 4.70 |
February | 0.446955E+09 | 0.00 | 0.00 | 62918798.05 | 0.00 | 0.00 | 0.463646E+11 | 0.00 | 4.65 |
March | 0.266745E+09 | 10314561.57 | 0.00 | 81121916.61 | 0.00 | 0.00 | 0.429409E+11 | 0.00 | 4.91 |
April | 3925067.19 | 0.581872E+09 | 0.00 | 83512627.20 | 0.00 | 0.00 | 0.231189E+11 | 0.00 | 5.24 |
May | 0.00 | 0.140039E+10 | 0.00 | 77229705.28 | 0.00 | 0.00 | 0.165109E+11 | 0.00 | 5.30 |
June | 0.00 | 0.348099E+10 | 0.00 | 61406987.08 | 0.00 | 0.00 | 0.816779E+10 | 0.00 | 4.66 |
July | 0.00 | 0.701665E+10 | 0.00 | 33231105.92 | 0.00 | 0.00 | 0.363663E+10 | 0.00 | 4.57 |
August | 0.00 | 0.575620E+10 | 0.00 | 39499817.33 | 0.00 | 0.00 | 0.429007E+10 | 0.00 | 4.71 |
September | 0.00 | 0.541578E+10 | 0.00 | 44620272.51 | 0.00 | 0.00 | 0.674014E+10 | 0.00 | 4.96 |
October | 0.129558E+09 | 0.759580E+09 | 0.00 | 79240965.28 | 0.00 | 0.00 | 0.293807E+11 | 0.00 | 5.10 |
November | 0.233169E+09 | 13071395.45 | 0.00 | 76053859.07 | 0.00 | 0.00 | 0.407361E+11 | 0.00 | 4.83 |
December | 0.914055E+09 | 0.00 | 0.00 | 68924902.53 | 0.00 | 0.00 | 0.477039E+11 | 0.00 | 4.51 |
Annual Sum or Average | 0.237063E+10 | 0.244357E+11 | 0.00 | 0.786152E+09 | 0.00 | 0.00 | 0.314787E+12 | 0.00 | 4.85 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 33231105.92 | 0.00 | 0.00 | 0.363663E+10 | 0.00 | 4.51 |
Maximum of Months | 0.914055E+09 | 0.701665E+10 | 0.00 | 83512627.20 | 0.00 | 0.00 | 0.477039E+11 | 0.00 | 5.30 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 75574031.05 | 915401.51 | 0.00 | 91726040.29 | 0.00 | 0.00 | 0.494859E+11 | 0.00 | 5.11 |
February | 73509638.60 | 0.00 | 0.00 | 75388117.45 | 0.00 | 0.00 | 0.511413E+11 | 0.00 | 5.09 |
March | 10109220.47 | 11475638.99 | 0.00 | 94831203.62 | 0.00 | 0.00 | 0.470048E+11 | 0.00 | 5.34 |
April | 0.00 | 0.631881E+09 | 0.00 | 91353733.32 | 0.00 | 0.00 | 0.246029E+11 | 0.00 | 5.61 |
May | 0.00 | 0.150948E+10 | 0.00 | 82434066.57 | 0.00 | 0.00 | 0.174116E+11 | 0.00 | 5.64 |
June | 0.00 | 0.372232E+10 | 0.00 | 64684661.33 | 0.00 | 0.00 | 0.854486E+10 | 0.00 | 4.93 |
July | 0.00 | 0.746996E+10 | 0.00 | 34949201.44 | 0.00 | 0.00 | 0.380797E+10 | 0.00 | 4.84 |
August | 0.00 | 0.614750E+10 | 0.00 | 41601338.83 | 0.00 | 0.00 | 0.449684E+10 | 0.00 | 4.99 |
September | 0.00 | 0.577654E+10 | 0.00 | 47344331.82 | 0.00 | 0.00 | 0.708498E+10 | 0.00 | 5.26 |
October | 2004853.67 | 0.814407E+09 | 0.00 | 88481650.22 | 0.00 | 0.00 | 0.316895E+11 | 0.00 | 5.48 |
November | 23976684.95 | 13721927.16 | 0.00 | 89163807.23 | 0.00 | 0.00 | 0.444908E+11 | 0.00 | 5.24 |
December | 0.256430E+09 | 0.00 | 0.00 | 83418334.16 | 0.00 | 0.00 | 0.529467E+11 | 0.00 | 4.92 |
Annual Sum or Average | 0.441604E+09 | 0.260982E+11 | 0.00 | 0.885376E+09 | 0.00 | 0.00 | 0.342708E+12 | 0.00 | 5.20 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 34949201.44 | 0.00 | 0.00 | 0.380797E+10 | 0.00 | 4.84 |
Maximum of Months | 0.256430E+09 | 0.746996E+10 | 0.00 | 94831203.62 | 0.00 | 0.00 | 0.529467E+11 | 0.00 | 5.64 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 1753457.91 | 0.00 | 0.135898E+09 | 0.00 | 0.00 | 0.586087E+11 | 0.00 | 22.63 |
February | 0.00 | 0.00 | 0.00 | 0.110746E+09 | 0.00 | 0.00 | 0.646216E+11 | 0.00 | 22.51 |
March | 0.00 | 20239140.46 | 0.00 | 0.133966E+09 | 0.00 | 0.00 | 0.546320E+11 | 0.00 | 22.93 |
April | 0.00 | 0.105911E+10 | 0.00 | 0.118817E+09 | 0.00 | 0.00 | 0.241710E+11 | 0.00 | 22.40 |
May | 0.00 | 0.243534E+10 | 0.00 | 99920528.72 | 0.00 | 0.00 | 0.156166E+11 | 0.00 | 21.93 |
June | 0.00 | 0.573661E+10 | 0.00 | 68460140.15 | 0.00 | 0.00 | 0.708641E+10 | 0.00 | 19.04 |
July | 0.00 | 0.104630E+11 | 0.00 | 34814800.56 | 0.00 | 0.00 | 0.318087E+10 | 0.00 | 18.93 |
August | 0.00 | 0.914761E+10 | 0.00 | 42296022.84 | 0.00 | 0.00 | 0.385406E+10 | 0.00 | 19.58 |
September | 0.00 | 0.802999E+10 | 0.00 | 54055444.72 | 0.00 | 0.00 | 0.641917E+10 | 0.00 | 20.63 |
October | 0.00 | 0.126740E+10 | 0.00 | 0.120162E+09 | 0.00 | 0.00 | 0.349683E+11 | 0.00 | 22.66 |
November | 0.00 | 24647778.10 | 0.00 | 0.130145E+09 | 0.00 | 0.00 | 0.528430E+11 | 0.00 | 22.86 |
December | 0.00 | 0.00 | 0.00 | 0.127060E+09 | 0.00 | 0.00 | 0.671817E+11 | 0.00 | 22.20 |
Annual Sum or Average | 0.00 | 0.381857E+11 | 0.00 | 0.117634E+10 | 0.00 | 0.00 | 0.393183E+12 | 0.00 | 21.52 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 34814800.56 | 0.00 | 0.00 | 0.318087E+10 | 0.00 | 18.93 |
Maximum of Months | 0.00 | 0.104630E+11 | 0.00 | 0.135898E+09 | 0.00 | 0.00 | 0.671817E+11 | 0.00 | 22.93 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.132487E+11 | 0.00 | 0.00 | 0.00 | 306801.43 | 0.00 | 0.00 | 0.00 | 1.14 |
February | 0.140973E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.15 |
March | 0.123237E+11 | 0.00 | 0.00 | 20803.23 | 3524919.11 | 0.00 | 8275984.85 | 0.00 | 1.16 |
April | 0.478143E+10 | 0.178854E+09 | 0.00 | 3549396.46 | 17500486.57 | 0.00 | 0.101618E+10 | 0.00 | 1.13 |
May | 0.245631E+10 | 0.459104E+09 | 0.00 | 5750513.89 | 12062689.60 | 0.00 | 0.146108E+10 | 0.00 | 1.13 |
June | 0.277584E+09 | 0.134165E+10 | 0.00 | 9053400.71 | 563007.02 | 0.00 | 0.158897E+10 | 0.00 | 1.10 |
July | 0.147375E+09 | 0.224086E+10 | 0.00 | 5162304.80 | 37577968.08 | 0.00 | 0.695563E+09 | 0.00 | 1.06 |
August | 0.226629E+09 | 0.190586E+10 | 0.00 | 5189220.34 | 46179973.99 | 0.00 | 0.773313E+09 | 0.00 | 1.09 |
September | 0.544939E+09 | 0.147301E+10 | 0.00 | 5114305.57 | 0.199837E+09 | 0.00 | 0.104292E+10 | 0.00 | 1.11 |
October | 0.718412E+10 | 0.252790E+09 | 0.00 | 2364879.04 | 9760333.21 | 0.00 | 0.775102E+09 | 0.00 | 1.16 |
November | 0.117811E+11 | 119388.80 | 0.00 | 55287.70 | 4571102.71 | 0.00 | 13974586.74 | 0.00 | 1.15 |
December | 0.148360E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.13 |
Annual Sum or Average | 0.819052E+11 | 0.785224E+10 | 0.00 | 36260111.75 | 0.331885E+09 | 0.00 | 0.737538E+10 | 0.00 | 1.13 |
Minimum of Months | 0.147375E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.06 |
Maximum of Months | 0.148360E+11 | 0.224086E+10 | 0.00 | 9053400.71 | 0.199837E+09 | 0.00 | 0.158897E+10 | 0.00 | 1.16 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:21:26
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.149291E+12 | 0.417392E+10 | 0.100153E+12 | 0.451661E+12 | 0.261168E+12 |
February | 0.186223E+12 | 0.403471E+10 | 0.112600E+12 | 0.449151E+12 | 0.101669E+12 |
March | 0.247926E+12 | 0.396250E+10 | 0.952432E+11 | 0.421133E+12 | 0.243612E+12 |
April | 0.295444E+12 | 0.175180E+10 | 0.329177E+11 | 0.187406E+12 | 0.609658E+12 |
May | 0.301083E+12 | 0.100861E+10 | 0.113079E+11 | 0.104326E+12 | 0.773873E+12 |
June | 0.315275E+12 | -107397826.7 | -0.217120E+11 | -0.119519E+11 | 0.100149E+13 |
July | 0.299498E+12 | -0.152451E+10 | -0.458383E+11 | -0.152699E+12 | 0.111947E+13 |
August | 0.251093E+12 | -0.131409E+10 | -0.371284E+11 | -0.124110E+12 | 0.109346E+13 |
September | 0.211682E+12 | -902753813.5 | -0.208040E+11 | -0.728091E+11 | 0.997257E+12 |
October | 0.191305E+12 | 0.225487E+10 | 0.514073E+11 | 0.254236E+12 | 0.553348E+12 |
November | 0.162286E+12 | 0.370840E+10 | 0.916760E+11 | 0.411372E+12 | 0.277849E+12 |
December | 0.117951E+12 | 0.500013E+10 | 0.128332E+12 | 0.566329E+12 | 0.162979E+12 |
Annual Sum or Average | 0.272906E+13 | 0.220462E+11 | 0.498155E+12 | 0.248404E+13 | 0.719583E+13 |
Minimum of Months | 0.117951E+12 | -0.152451E+10 | -0.458383E+11 | -0.152699E+12 | 0.101669E+12 |
Maximum of Months | 0.315275E+12 | 0.500013E+10 | 0.128332E+12 | 0.566329E+12 | 0.111947E+13 |