Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:24
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470
Simulation Timestamp: 2024-07-03 12:24:43
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:43
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 12842.56 | 1131.97 | 1131.97 |
Net Site Energy | 12842.56 | 1131.97 | 1131.97 |
Total Source Energy | 24059.83 | 2120.69 | 2120.69 |
Net Source Energy | 24059.83 | 2120.69 | 2120.69 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 3170.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 462.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 780.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 193.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1658.18 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 813.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 513.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 96.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 193.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 94.79 | 3015.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | 61.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 4867.25 | 7975.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 3170.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 462.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 780.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 193.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 872.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 14.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 8.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 21.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 789.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 2.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 513.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 96.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 193.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 94.79 | 3015.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5742.51 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.69 | |
Refrigeration | General | 7.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 20.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 33.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 3170.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 462.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 780.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 193.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 1658.18 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 813.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 513.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 96.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 193.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 94.79 | 3015.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | Unassigned | 61.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 85.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 102.85 | 545.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 240.28 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 429.01 | 702.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 85.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 102.85 | 545.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 240.28 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 429.01 | 702.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 4867.254 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 4867.254 | 100.00 |
Total On-Site and Utility Electric Sources | 4867.254 | 100.00 |
Total Electricity End Uses | 4867.254 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 126.63 | 2.36 |
Air to Air Heat Recovery for Heating | 5233.16 | 97.64 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 5359.79 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9857.19 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9857.19 | 100.00 |
Total Water End Uses | 9857.19 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 551.33 |
Time Setpoint Not Met During Occupied Cooling | 45.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 7907.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER1 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| FLR_3_DOAS COOLING COIL | VAV WITH REHEAT COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH LAUNDRY G WATER HEATER | SWH BOOSTER E WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |CoilReportMonthly
| FLR_3_DOAS HEATING COIL | VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | FLR_3_DOAS COOLING COIL | VAV WITH REHEAT COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |FanReportMonthly
| FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL_FANCOILFAN | ROOM_2_FLR_3 FAN COIL_FANCOILFAN | ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | ROOM_5_FLR_3 FAN COIL_FANCOILFAN | ROOM_6_FLR_3 FAN COIL_FANCOILFAN | ROOM_1_FLR_6 FAN COIL_FANCOILFAN | ROOM_2_FLR_6 FAN COIL_FANCOILFAN | ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| FLR_3_DOAS | VAV WITH REHEAT |AirLoopSystemComponentLoadsMonthly
| FLR_3_DOAS | VAV WITH REHEAT |AirLoopSystemComponentEnergyUseMonthly
| FLR_3_DOAS | VAV WITH REHEAT |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:43
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:24 |
RunPeriod | RUNPERIOD 1 |
Weather File | International Falls Intl Ap MN USA TMY3 WMO#=727470 |
Latitude [deg] | 48.57 |
Longitude [deg] | -93.4 |
Elevation [m] | 359.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 8.8143 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.26 | 23.26 | 11.3140 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 11.3140 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 4.6285 | 61.93 | 5.3800 |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 5.7199 | 46.45 | 2.6900 |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 4.6285 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.50 | 65.50 | 10.0104 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.08 | 85.08 | 10.7639 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 8.2882 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 8.2882 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 7.1042 | 18.58 | 0.0000 |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.74 | 6.74 | 8.2882 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 10.0104 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 10.0104 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.37 | 26.37 | 11.4097 | 4.65 | 2934.4875 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.20 | 28.20 | 7.1042 | 18.58 | 0.0000 |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 8.5566 | 7.07 | 41.0709 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 8.5566 | 7.07 | 41.0709 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 1978.83 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 8.8143 | 18.58 | 5.3800 | |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 1.00 | RETAIL_1_FLR_1 | GENERAL | RETAIL_1_FLR_1 | 11.3140 | 6.19 | 10.7600 | |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 1.00 | RETAIL_2_FLR_1 | GENERAL | RETAIL_2_FLR_1 | 11.3140 | 6.19 | 10.7600 | |
MECH_FLR_1 | 164.24 | Yes | Yes | 1.00 | MECH_FLR_1 | GENERAL | MECH_FLR_1 | 4.6285 | 61.93 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 1.00 | STORAGE_FLR_1 | GENERAL | STORAGE_FLR_1 | 5.7199 | 46.45 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 1.00 | LAUNDRY_FLR_1 | GENERAL | LAUNDRY_FLR_1 | 4.6285 | 9.29 | 597.5300 | |
CAFE_FLR_1 | 188.86 | Yes | Yes | 1.00 | CAFE_FLR_1 | GENERAL | CAFE_FLR_1 | 10.0104 | 1.33 | 5.3800 | |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 1.00 | LOBBY_FLR_1 | GENERAL | LOBBY_FLR_1 | 10.7639 | 3.10 | 8.0700 | |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_1_FLR_3 | GENERAL | ROOM_1_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_2_FLR_3 | GENERAL | ROOM_2_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 76.00 | ROOM_3_MULT19_FLR_3 | GENERAL | ROOM_3_MULT19_FLR_3 | 8.2882 | 16.35 | 10.5200 | |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 76.00 | ROOM_4_MULT19_FLR_3 | GENERAL | ROOM_4_MULT19_FLR_3 | 8.2882 | 16.35 | 10.5200 | |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_5_FLR_3 | GENERAL | ROOM_5_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_6_FLR_3 | GENERAL | ROOM_6_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 4.00 | CORRIDOR_FLR_3 | GENERAL | CORRIDOR_FLR_3 | 7.1042 | 18.58 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_1_FLR_6 | GENERAL | ROOM_1_FLR_6 | 8.2882 | 26.01 | 6.7500 | |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_2_FLR_6 | GENERAL | ROOM_2_FLR_6 | 8.2882 | 26.01 | 6.7500 | |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 9.00 | ROOM_3_MULT9_FLR_6 | GENERAL | ROOM_3_MULT9_FLR_6 | 8.2882 | 16.35 | 10.5200 | |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1.00 | BANQUET_FLR_6 | GENERAL | BANQUET_FLR_6 | 10.0104 | 1.33 | 67.8200 | |
DINING_FLR_6 | 331.66 | Yes | Yes | 1.00 | DINING_FLR_6 | GENERAL | DINING_FLR_6 | 10.0104 | 1.33 | 67.8200 | |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 1.00 | KITCHEN_FLR_6 | GENERAL | KITCHEN_FLR_6 | 11.4097 | 4.65 | 2934.4875 | |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1.00 | CORRIDOR_FLR_6 | GENERAL | CORRIDOR_FLR_6 | 7.1042 | 18.58 | 0.0000 | |
Total | 11345.29 | 8.5566 | 3.54 | 41.0709 | |||||||
Conditioned Total | 11345.29 | 8.5566 | 3.54 | 41.0709 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 11345.29 | 11345.29 | 0.00 | 0.00 | 4.6520 | 8.82 | 37.1989 |
Total | 11345.29 | 11345.29 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:43
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 29-JUN-18:10 | 05-JAN-21:00 | - | - | - | - | - | - | - | - | - | - | 12-JAN-21:10 |
Heating | 0.00 | 766086.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 202899.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 52987.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 77573.37 | 75123.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 28157.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 28190.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6534.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 4751.03 | 267550.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 2416.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 413449.13 | 1108761.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 766086.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 202899.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 52987.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 47590.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 37635.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1038.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 26968.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 150.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 28190.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 6534.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 4751.03 | 267550.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 228.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 1093.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1094.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:43
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 3437.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1463.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2473.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 612.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5251.45 | 1939.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2577.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1627.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 304.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 611.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 300.21 | 3269.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 193.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 15414.59 | 8645.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 302.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 128.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 218.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 54.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 462.88 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 227.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 143.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 26.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 53.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 26.46 | 288.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1358.68 | 762.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 302.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 128.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 218.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 54.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 462.88 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 227.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 143.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 26.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 53.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 26.46 | 288.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1358.68 | 762.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:43
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
BASEMENT VAV BOX COMPONENT | 2.59 | 0.582350 | 0.496000 | 1.28 | 1.00 | 0.500000 | 0.000654 | 0.000069 | 1.28 | 16.70 | 0.008000 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.451492 | 0.113199 | 0.496000 | 0.223940 | 0.496000 | 0.500000 | 0.003366 | 0.000043 | 0.223940 | 16.70 | 0.008000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.238528 | 0.248121 | 0.496000 | 0.118310 | 0.661655 | 0.500000 | 0.001536 | 0.000016 | 0.118310 | 16.70 | 0.008000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.182020 | 0.687581 | 0.496000 | 0.090282 | 1.00 | 0.500000 | 0.000554 | 0.000023 | 0.095343 | 16.70 | 0.008000 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.109014 | 0.662361 | 0.496000 | 0.054071 | 1.00 | 0.500000 | 0.000575 | 0.000017 | 0.070620 | 16.70 | 0.008000 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 3.39 | 0.017539 | 0.496000 | 1.68 | 0.496000 | 0.500000 | 0.021724 | 0.000099 | 1.68 | 16.70 | 0.008000 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.81 | 0.079635 | 0.496000 | 0.896354 | 0.496000 | 0.500000 | 0.004784 | 0.000124 | 0.896354 | 16.70 | 0.008000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 5.30 | 0.188108 | 0.496000 | 2.63 | 0.501621 | 0.500000 | 0.002025 | 0.000306 | 2.63 | 16.70 | 0.008000 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.70 | 0.697665 | 0.496000 | 0.843823 | 1.00 | 0.500000 | 0.000546 | 0.000151 | 0.843823 | 16.70 | 0.008000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.22 | 0.114070 | 0.496000 | 1.10 | 0.496000 | 0.500000 | 0.003340 | 0.000123 | 1.10 | 16.70 | 0.008000 |
DINING_FLR_6 VAV BOX COMPONENT | 2.32 | 0.108838 | 0.496000 | 1.15 | 0.496000 | 0.500000 | 0.003501 | 0.000127 | 1.15 | 16.70 | 0.008000 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.39 | 0.059156 | 0.496000 | 1.19 | 0.496000 | 0.500000 | 0.011584 | 0.000083 | 1.19 | 16.70 | 0.008000 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 0.829645 | 0.378522 | 0.496000 | 0.411504 | 1.00 | 0.500000 | 0.001007 | 0.000096 | 0.411504 | 16.70 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
BASEMENT VAV BOX REHEAT COIL | 7836.56 | 0.000069 | 165.18 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 4890.22 | 0.000043 | 123.69 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1807.68 | 0.000016 | 42.16 |
MECH_FLR_1 VAV BOX REHEAT COIL | 2613.62 | 0.000023 | 71.33 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 1935.96 | 0.000017 | 52.84 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 11339.68 | 0.000099 | 240.63 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 14159.14 | 0.000124 | 332.27 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 35024.97 | 0.000306 | 798.61 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | 8506.80 | 0.000074 | 243.06 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | 8514.75 | 0.000074 | 243.29 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 48441.18 | 0.000424 | 1384.10 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 48604.01 | 0.000425 | 1388.75 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | 8523.48 | 0.000075 | 243.54 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | 8531.43 | 0.000075 | 243.77 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 17265.47 | 0.000151 | 429.02 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | 2604.98 | 0.000023 | 74.43 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | 2605.23 | 0.000023 | 74.44 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 12480.18 | 0.000109 | 356.58 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 14032.54 | 0.000123 | 317.94 |
DINING_FLR_6 VAV BOX REHEAT COIL | 14472.89 | 0.000127 | 327.16 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 9542.33 | 0.000083 | 205.27 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 10981.72 | 0.000096 | 296.62 |
FLR_3_DOAS HEATING COIL | 35250.36 | 0.000308 | 490.61 |
VAV WITH REHEAT HEATING COIL | 401918.23 | 0.003516 | 5593.80 |
Design Size Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 0.061735 |
ROOM_2_FLR_3 DIRECT AIR | 0.061728 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 0.837072 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 0.837300 |
ROOM_5_FLR_3 DIRECT AIR | 0.061735 |
ROOM_6_FLR_3 DIRECT AIR | 0.061728 |
ROOM_1_FLR_6 DIRECT AIR | 0.015434 |
ROOM_2_FLR_6 DIRECT AIR | 0.015432 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 0.099154 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Hot Water Flow [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 1.32 | 0.000074 | 0.000407 |
ROOM_2_FLR_3 FAN COIL | 1.26 | 0.000074 | 0.000388 |
ROOM_3_MULT19_FLR_3 FAN COIL | 8.40 | 0.000424 | 0.002539 |
ROOM_4_MULT19_FLR_3 FAN COIL | 6.26 | 0.000425 | 0.002018 |
ROOM_5_FLR_3 FAN COIL | 1.21 | 0.000075 | 0.000373 |
ROOM_6_FLR_3 FAN COIL | 1.15 | 0.000075 | 0.000355 |
ROOM_1_FLR_6 FAN COIL | 0.344651 | 0.000023 | 0.000106 |
ROOM_2_FLR_6 FAN COIL | 0.326927 | 0.000023 | 0.000101 |
ROOM_3_MULT9_FLR_6 FAN COIL | 1.69 | 0.000109 | 0.000524 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COIL_FANCOILFAN | 1.32 |
ROOM_2_FLR_3 FAN COIL_FANCOILFAN | 1.26 |
ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | 8.40 |
ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | 6.26 |
ROOM_5_FLR_3 FAN COIL_FANCOILFAN | 1.21 |
ROOM_6_FLR_3 FAN COIL_FANCOILFAN | 1.15 |
ROOM_1_FLR_6 FAN COIL_FANCOILFAN | 0.344651 |
ROOM_2_FLR_6 FAN COIL_FANCOILFAN | 0.326927 |
ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN | 1.69 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Coil Load [W] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | 21.71 | 6.70 | 0.008589 | 12.80 | 0.008500 | 0.000407 | 1.32 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | 21.71 | 6.70 | 0.008593 | 12.80 | 0.008500 | 0.000388 | 1.26 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 21.71 | 6.70 | 0.008526 | 12.80 | 0.008500 | 0.002539 | 8.40 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 21.71 | 6.70 | 0.008767 | 12.80 | 0.008500 | 0.002018 | 6.26 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | 21.71 | 6.70 | 0.008597 | 12.80 | 0.008500 | 0.000373 | 1.21 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | 21.71 | 6.70 | 0.008603 | 12.80 | 0.008500 | 0.000355 | 1.15 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | 21.71 | 6.70 | 0.008585 | 12.80 | 0.008500 | 0.000106 | 0.344651 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | 21.71 | 6.70 | 0.008590 | 12.80 | 0.008500 | 0.000101 | 0.326927 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 21.71 | 6.70 | 0.008630 | 12.80 | 0.008500 | 0.000524 | 1.69 | |
FLR_3_DOAS COOLING COIL | 30.10 | 6.70 | 0.012726 | 11.90 | 0.008500 | 0.001989 | 2.05 | 69550.09 |
VAV WITH REHEAT COOLING COIL | 27.04 | 6.70 | 0.011172 | 10.91 | 0.008500 | 0.017969 | 23.39 | 628300.66 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
VAV WITH REHEAT | 11.76 | 11.67 | 23.53 | 11.67 | 23.39 | 23.39 | 0.300000 | 0.498978 | 23.39 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
VAV WITH REHEAT_OA_CONTROLLER | 23.39 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
FLR_3_DOAS OA HEAT RECOVERY | 2.05 |
VAV WITH REHEAT OA HEAT RECOVERY | 11.66 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS FAN | 2.05 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.001989 | 0.000239 |
FLR_3_DOAS_HEATC_CONTROLLER | 0.000308 | |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.017969 | 0.000027 |
VAV WITH REHEAT_HEATC_CONTROLLER | 0.003516 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT FAN | 23.39 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.026771 | 4370.89 | |
HEATSYS1 PUMP | 0.006403 | 1928.25 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.006403 | 0.768340 |
COOLSYS1 | 0.026771 | 3.21 |
SWHSYS1 | 0.000375 | 0.045004 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 731883.39 | 731883.39 | 0.006403 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.026771 | 3026.11 |
SWHSYS1 PUMP | 0.000375 | 47.91 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.026771 | 936053.58 | 936690.90 | 106.78 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000375 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:43
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:43
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:43
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 5.40 | -2.00 | -14.60 | -16.90 | -11.50 | -6.20 | 4.00 | 13.40 | 18.00 | 19.70 | 17.90 | 12.30 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | International Falls Intl Ap MN USA TMY3 WMO#=727470 | 48.57 | -93.40 | -6.00 | 359.00 | 97086 | 1.1539 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 3.29 | 36.60 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.58 | 23.26 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.72 | 65.50 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.80 | 85.08 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.70 | 6.74 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.96 | 26.37 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.27 | 28.20 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 8.814 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 14.194 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 11.314 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 22.074 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 11.314 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 22.074 | No |
4 | MECH_FLR_1 | 164.24 | 2.7 | 61.932 | 1.615E-002 | 4.628 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 10.008 | No |
5 | STORAGE_FLR_1 | 94.76 | 2.0 | 46.451 | 2.153E-002 | 5.720 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 8.410 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 4.628 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 602.158 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 10.010 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 15.390 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 10.764 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.834 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 8.288 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 18.808 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 8.288 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 18.808 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 21.0 | 18.581 | 5.382E-002 | 7.104 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.104 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 8.288 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 18.808 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 10.010 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 77.830 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 10.010 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 77.830 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 11.410 | 515.227 | 2419.260 | 0.000 | 0.000 | 0.000 | 2945.897 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 22.2 | 18.581 | 5.382E-002 | 7.104 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.104 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | STORAGE_FLR_1 PEOPLE | BLDG_OCC_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.0 | 2.153E-002 | 46.451 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | CORRIDOR_FLR_3 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 21.0 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 21 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
21 | CORRIDOR_FLR_6 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 22.2 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
22 | MECH_FLR_1 PEOPLE | BLDG_OCC_SCH | MECH_FLR_1 | 164.24 | 2.7 | 2.7 | 1.615E-002 | 61.932 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 3 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_BASEMENT | BASEMENT | 1978.83 | 106.5 | 17441.963 | 8.814 | 163.776 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 17441.963 |
2 | RETAIL_1_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_1_FLR_1 | 67.07 | 10.8 | 758.849 | 11.314 | 70.076 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 758.849 |
3 | RETAIL_2_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_2_FLR_1 | 77.67 | 12.5 | 878.750 | 11.314 | 70.076 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 878.750 |
4 | MECH_FLR_1_LIGHTS | LTG_SCH_MECHANIC | MECH_FLR_1 | 164.24 | 2.7 | 760.196 | 4.628 | 286.650 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 760.196 |
5 | STORAGE_FLR_1_LIGHTS | LTG_SCH_STORAGE | STORAGE_FLR_1 | 94.76 | 2.0 | 542.017 | 5.720 | 265.695 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 542.017 |
6 | LAUNDRY_FLR_1_LIGHTS | LTG_SCH_LAUNDRY | LAUNDRY_FLR_1 | 78.04 | 8.4 | 361.204 | 4.628 | 43.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 361.204 |
7 | CAFE_FLR_1_LIGHTS | LTG_SCH_DINING | CAFE_FLR_1 | 188.86 | 142.3 | 1890.589 | 10.010 | 13.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1890.589 |
8 | LOBBY_FLR_1_LIGHTS | LTG_SCH_LOBBY | LOBBY_FLR_1 | 1308.19 | 422.4 | 14081.185 | 10.764 | 33.333 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14081.185 |
9 | ROOM_1_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_3 | 39.02 | 1.5 | 323.422 | 8.288 | 215.615 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.422 |
10 | ROOM_2_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_3 | 39.02 | 1.5 | 323.384 | 8.288 | 215.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.384 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 203.259 | 8.288 | 135.506 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 203.259 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 203.314 | 8.288 | 135.543 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 203.314 |
13 | ROOM_5_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_5_FLR_3 | 39.02 | 1.5 | 323.422 | 8.288 | 215.615 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.422 |
14 | ROOM_6_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_6_FLR_3 | 39.02 | 1.5 | 323.384 | 8.288 | 215.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.384 |
15 | CORRIDOR_FLR_3_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2766.397 | 7.104 | 132.003 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2766.397 |
16 | ROOM_1_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_6 | 39.02 | 1.5 | 323.422 | 8.288 | 215.615 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.422 |
17 | ROOM_2_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_6 | 39.02 | 1.5 | 323.384 | 8.288 | 215.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.384 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 203.314 | 8.288 | 135.543 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 203.314 |
19 | BANQUET_FLR_6_LIGHTS | LTG_SCH_DINING | BANQUET_FLR_6 | 331.66 | 249.9 | 3320.034 | 10.010 | 13.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3320.034 |
20 | DINING_FLR_6_LIGHTS | LTG_SCH_DINING | DINING_FLR_6 | 331.66 | 249.9 | 3320.034 | 10.010 | 13.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3320.034 |
21 | KITCHEN_FLR_6_LIGHTS | LTG_SCH_KITCHEN | KITCHEN_FLR_6 | 103.30 | 22.2 | 1178.676 | 11.410 | 53.003 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1178.676 |
22 | CORRIDOR_FLR_6_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_6 | 412.12 | 22.2 | 2927.804 | 7.104 | 132.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2927.804 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 2.7 | 883.628 | 5.380 | 333.193 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 254.902 | 2.690 | 124.952 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 457.500 | 4.429 | 20.573 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 457.500 | 457.500 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 285.000 | 2.759 | 12.816 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 285.000 | 285.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 2.390 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.1625 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
6 | RES_ROOF | 19 | 3 | 3 | 0.167 | 0.1625 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
7 | NONRES_EXT_WALL_GRD | 21 | 3 | 9 | 0.167 | 0.5913 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | NONRES_EXT_WALL_MID | 22 | 3 | 9 | 0.167 | 0.7799 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | NONRES_EXT_WALL_TOP | 23 | 3 | 9 | 0.167 | 0.7924 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | RES_EXT_WALL_MID | 25 | 3 | 9 | 0.167 | 0.7799 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | RES_EXT_WALL_TOP | 26 | 3 | 9 | 0.167 | 0.7924 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | NONRES_FLOOR | 30 | 3 | 7 | 0.167 | 0.1901 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
13 | NONRES_FLOOR_CEILING | 33 | 3 | 7 | 0.167 | 0.1901 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
14 | BASEMENT_FLOOR | 36 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
15 | BASEMENT_WALL_NORTH_CFACTOR | 39 | 2 | 7 | 0.167 | 0.2699 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | BASEMENT_WALL_EAST_CFACTOR | 40 | 2 | 7 | 0.167 | 0.2699 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | BASEMENT_WALL_SOUTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.2699 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
18 | BASEMENT_WALL_WEST_CFACTOR | 42 | 2 | 7 | 0.167 | 0.2699 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4184 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.093 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
10 | RES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.093 |
11 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
12 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.524 |
14 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.115 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 1.095 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | RES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.115 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
25 | RES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 1.095 |
26 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
27 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.000 |
28 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
29 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
30 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
31 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
32 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.000 |
33 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
34 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
35 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.628 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.628 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
39 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.628 |
40 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
41 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.628 |
42 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 2.3900722 | 2.3900722 | 2.3900722 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.63083111E-06 | 0.74112372E-09 | -0.38647046E-05 | 0.15329585E-16 |
21 | 2 | 0.78415922 | 0.99752939E-03 | 1.0633801 | -0.74093433E-06 |
22 | 1 | -22.010056 | 0.66447931E-01 | -6.3131541 | 0.20386814 |
23 | 0 | 21.355302 | 0.61958938E-01 | 5.3791822 | |
24 | 3 | -0.63083111E-06 | 0.74112372E-09 | -0.38647046E-05 | 0.15329585E-16 |
25 | 2 | 0.78415922 | 0.99752939E-03 | 1.0633801 | -0.74093433E-06 |
26 | 1 | -22.010056 | 0.66447931E-01 | -6.3131541 | 0.20386814 |
27 | 0 | 21.355302 | 0.61958938E-01 | 5.3791822 | |
28 | 9 | 0.57998040E-15 | -0.30968906E-15 | -0.16543531E-09 | -0.94394381E-17 |
29 | 8 | 0.24079056E-07 | 0.80583727E-13 | 0.40057412E-03 | -0.27378716E-09 |
30 | 7 | -0.12920082E-01 | 0.41010748E-08 | -0.24062383E-01 | 0.14690605E-03 |
31 | 6 | 0.42378547 | 0.14160748E-05 | 0.48776087 | -0.49650686E-02 |
32 | 5 | -5.3704470 | 0.52534619E-04 | -4.5614765 | 0.65414341E-01 |
33 | 4 | 33.798395 | 0.42724899E-03 | 21.909926 | -0.43268566 |
34 | 3 | -112.91846 | 0.92631763E-03 | -56.552255 | 1.5396438 |
35 | 2 | 198.80798 | 0.51863526E-03 | 78.726696 | -2.9273457 |
36 | 1 | -171.78376 | 0.55128408E-04 | -55.503401 | 2.7564403 |
37 | 0 | 57.057407 | 0.31226006E-06 | 15.518392 | |
38 | 9 | -0.46044427E-14 | 0.27900089E-16 | -0.15673021E-09 | 0.84433218E-16 |
39 | 8 | 0.22857479E-07 | 0.10577188E-12 | 0.38804207E-03 | -0.25989740E-09 |
40 | 7 | -0.12547140E-01 | 0.54349272E-08 | -0.23525725E-01 | 0.14266556E-03 |
41 | 6 | 0.41365335 | 0.18858798E-05 | 0.47915629 | -0.48456347E-02 |
42 | 5 | -5.2715868 | 0.70260405E-04 | -4.4954992 | 0.64188504E-01 |
43 | 4 | 33.361217 | 0.57360532E-03 | 21.652286 | -0.42688098 |
44 | 3 | -111.98862 | 0.12479141E-02 | -56.043016 | 1.5262094 |
45 | 2 | 197.88677 | 0.70084509E-03 | 78.259217 | -2.9127162 |
46 | 1 | -171.44362 | 0.74708721E-04 | -55.366651 | 2.7504789 |
47 | 0 | 57.057407 | 0.42455547E-06 | 15.540314 | |
48 | 9 | -0.14490010E-14 | 0.30537737E-16 | -0.15613140E-09 | 0.37153042E-16 |
49 | 8 | 0.22775399E-07 | 0.10742354E-12 | 0.38719206E-03 | -0.25896410E-09 |
50 | 7 | -0.12521818E-01 | 0.55241817E-08 | -0.23489278E-01 | 0.14237764E-03 |
51 | 6 | 0.41296535 | 0.19175017E-05 | 0.47857136 | -0.48375248E-02 |
52 | 5 | -5.2648734 | 0.71459421E-04 | -4.4910111 | 0.64105260E-01 |
53 | 4 | 33.331527 | 0.58354868E-03 | 21.634754 | -0.42648676 |
54 | 3 | -111.92546 | 0.12698472E-02 | -56.008360 | 1.5252969 |
55 | 2 | 197.82418 | 0.71331385E-03 | 78.227414 | -2.9117223 |
56 | 1 | -171.42051 | 0.76052751E-04 | -55.357370 | 2.7500739 |
57 | 0 | 57.057407 | 0.43228786E-06 | 15.541820 | |
58 | 9 | -0.46044427E-14 | 0.27900089E-16 | -0.15673021E-09 | 0.84433218E-16 |
59 | 8 | 0.22857479E-07 | 0.10577188E-12 | 0.38804207E-03 | -0.25989740E-09 |
60 | 7 | -0.12547140E-01 | 0.54349272E-08 | -0.23525725E-01 | 0.14266556E-03 |
61 | 6 | 0.41365335 | 0.18858798E-05 | 0.47915629 | -0.48456347E-02 |
62 | 5 | -5.2715868 | 0.70260405E-04 | -4.4954992 | 0.64188504E-01 |
63 | 4 | 33.361217 | 0.57360532E-03 | 21.652286 | -0.42688098 |
64 | 3 | -111.98862 | 0.12479141E-02 | -56.043016 | 1.5262094 |
65 | 2 | 197.88677 | 0.70084509E-03 | 78.259217 | -2.9127162 |
66 | 1 | -171.44362 | 0.74708721E-04 | -55.366651 | 2.7504789 |
67 | 0 | 57.057407 | 0.42455547E-06 | 15.540314 | |
68 | 9 | -0.14490010E-14 | 0.30537737E-16 | -0.15613140E-09 | 0.37153042E-16 |
69 | 8 | 0.22775399E-07 | 0.10742354E-12 | 0.38719206E-03 | -0.25896410E-09 |
70 | 7 | -0.12521818E-01 | 0.55241817E-08 | -0.23489278E-01 | 0.14237764E-03 |
71 | 6 | 0.41296535 | 0.19175017E-05 | 0.47857136 | -0.48375248E-02 |
72 | 5 | -5.2648734 | 0.71459421E-04 | -4.4910111 | 0.64105260E-01 |
73 | 4 | 33.331527 | 0.58354868E-03 | 21.634754 | -0.42648676 |
74 | 3 | -111.92546 | 0.12698472E-02 | -56.008360 | 1.5252969 |
75 | 2 | 197.82418 | 0.71331385E-03 | 78.227414 | -2.9117223 |
76 | 1 | -171.42051 | 0.76052751E-04 | -55.357370 | 2.7500739 |
77 | 0 | 57.057407 | 0.43228786E-06 | 15.541820 | |
78 | 7 | -0.16359629E-14 | -0.14530353E-16 | -0.22331004E-13 | 0.54056000E-15 |
79 | 6 | 0.18262352E-10 | 0.22801053E-11 | 0.52333849E-09 | -0.18642118E-10 |
80 | 5 | -0.59540244E-07 | 0.11129510E-07 | -0.21928235E-05 | 0.17164558E-06 |
81 | 4 | 0.60861605E-04 | 0.41961443E-05 | 0.17683552E-02 | -0.28248824E-03 |
82 | 3 | -0.87523238E-02 | 0.14809838E-03 | -0.21562890 | 0.43346081E-01 |
83 | 2 | 0.12409989 | 0.64146884E-03 | 2.9009744 | -0.61915653 |
84 | 1 | -0.31397648 | 0.40472017E-03 | -7.1381115 | 1.5697592 |
85 | 0 | 0.19977219 | 0.56546383E-05 | 4.4522022 | |
86 | 7 | -0.22331004E-13 | -0.14530353E-16 | -0.16359629E-14 | 0.54056000E-15 |
87 | 6 | 0.52333849E-09 | 0.22801053E-11 | 0.18262352E-10 | -0.18642118E-10 |
88 | 5 | -0.21928235E-05 | 0.11129510E-07 | -0.59540244E-07 | 0.17164558E-06 |
89 | 4 | 0.17683552E-02 | 0.41961443E-05 | 0.60861605E-04 | -0.28248824E-03 |
90 | 3 | -0.21562890 | 0.14809838E-03 | -0.87523238E-02 | 0.43346081E-01 |
91 | 2 | 2.9009744 | 0.64146884E-03 | 0.12409989 | -0.61915653 |
92 | 1 | -7.1381115 | 0.40472017E-03 | -0.31397648 | 1.5697592 |
93 | 0 | 4.4522022 | 0.56546383E-05 | 0.19977219 | |
94 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
95 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
96 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
97 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
98 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
99 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
100 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
101 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
102 | 7 | -0.15524988E-08 | -0.27599222E-15 | 0.12191615E-13 | -0.17961055E-15 |
103 | 6 | 0.75408527E-05 | 0.51820635E-08 | 0.31843202E-02 | -0.26712746E-04 |
104 | 5 | -0.54428247E-03 | 0.30714476E-05 | -0.22340912 | 0.19533659E-02 |
105 | 4 | 0.12532102E-01 | 0.13984121E-03 | 4.8242913 | -0.45214473E-01 |
106 | 3 | -0.11008570 | 0.11123587E-02 | -37.991733 | 0.39832565 |
107 | 2 | 0.39093855 | 0.18508074E-02 | 116.42617 | -1.4171665 |
108 | 1 | -0.56428968 | 0.56416853E-03 | -143.87330 | 2.0484809 |
109 | 0 | 0.27512533 | 0.13606908E-04 | 60.838472 | |
110 | 7 | -0.15524988E-08 | -0.27599222E-15 | 0.12191615E-13 | -0.17961055E-15 |
111 | 6 | 0.75408527E-05 | 0.51820635E-08 | 0.31843202E-02 | -0.26712746E-04 |
112 | 5 | -0.54428247E-03 | 0.30714476E-05 | -0.22340912 | 0.19533659E-02 |
113 | 4 | 0.12532102E-01 | 0.13984121E-03 | 4.8242913 | -0.45214473E-01 |
114 | 3 | -0.11008570 | 0.11123587E-02 | -37.991733 | 0.39832565 |
115 | 2 | 0.39093855 | 0.18508074E-02 | 116.42617 | -1.4171665 |
116 | 1 | -0.56428968 | 0.56416853E-03 | -143.87330 | 2.0484809 |
117 | 0 | 0.27512533 | 0.13606908E-04 | 60.838472 | |
118 | 7 | -0.15524988E-08 | -0.27599222E-15 | 0.12191615E-13 | -0.17961055E-15 |
119 | 6 | 0.75408527E-05 | 0.51820635E-08 | 0.31843202E-02 | -0.26712746E-04 |
120 | 5 | -0.54428247E-03 | 0.30714476E-05 | -0.22340912 | 0.19533659E-02 |
121 | 4 | 0.12532102E-01 | 0.13984121E-03 | 4.8242913 | -0.45214473E-01 |
122 | 3 | -0.11008570 | 0.11123587E-02 | -37.991733 | 0.39832565 |
123 | 2 | 0.39093855 | 0.18508074E-02 | 116.42617 | -1.4171665 |
124 | 1 | -0.56428968 | 0.56416853E-03 | -143.87330 | 2.0484809 |
125 | 0 | 0.27512533 | 0.13606908E-04 | 60.838472 | |
126 | 7 | -0.15524988E-08 | -0.27599222E-15 | 0.12191615E-13 | -0.17961055E-15 |
127 | 6 | 0.75408527E-05 | 0.51820635E-08 | 0.31843202E-02 | -0.26712746E-04 |
128 | 5 | -0.54428247E-03 | 0.30714476E-05 | -0.22340912 | 0.19533659E-02 |
129 | 4 | 0.12532102E-01 | 0.13984121E-03 | 4.8242913 | -0.45214473E-01 |
130 | 3 | -0.11008570 | 0.11123587E-02 | -37.991733 | 0.39832565 |
131 | 2 | 0.39093855 | 0.18508074E-02 | 116.42617 | -1.4171665 |
132 | 1 | -0.56428968 | 0.56416853E-03 | -143.87330 | 2.0484809 |
133 | 0 | 0.27512533 | 0.13606908E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.33_SHGC_0.45 | 37 | 1 | VerySmooth | 1.875 | 1.875 | 1.000 | 0.451 | ||
2 | RESWINDOW_U_0.33_SHGC_0.45 | 38 | 1 | VerySmooth | 1.875 | 1.875 | 1.000 | 0.451 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 3.93105E-002 | 0.36619 | 0.43710 | 0.43710 | 0.49500 | 0.13079 | 0.16089 | 0.00000 | 0.84000 | 0.84000 | 0.10917 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 3.93105E-002 | 0.36619 | 0.43710 | 0.43710 | 0.49500 | 0.13079 | 0.16089 | 0.00000 | 0.84000 | 0.84000 | 0.10917 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | CAFE_FLR_1 | 1 | 0 |
2 | LOBBY_FLR_1 | 1 | 0 |
3 | BANQUET_FLR_6 | 1 | 0 |
4 | DINING_FLR_6 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | CAFE_FLR_1 | 0 | |
2 | LOBBY_FLR_1 | 0 | |
3 | BANQUET_FLR_6 | 0 | |
4 | DINING_FLR_6 | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH LAUNDRY G WATER HEATER | 1.1356 | 163316.0 | 11.511 | 0.4388 |
2 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.219 | 1.1187 |
3 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 2.2712 | 175842.6 | 5.775 | 0.3748 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 1.764E-002 | 2.631E-004 | 1.298E-004 | 0.239 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.811E-003 | 8.769E-005 | 2.388E-004 | 7.967E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 2.7 | 1.610E-002 | 9.800E-005 | 2.563E-004 | 8.904E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 9.287E-003 | 9.800E-005 | 2.127E-004 | 8.904E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 2.198E-002 | 2.816E-004 | 2.506E-004 | 0.256 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 3.900E-002 | 2.065E-004 | 1.137E-004 | 0.188 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 0.111 | 8.519E-005 | 1.629E-004 | 7.740E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 2.563E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 2.563E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 2.857E-003 | 1.165E-004 | 2.563E-004 | 0.138 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 2.858E-003 | 1.165E-004 | 2.563E-004 | 0.138 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 2.563E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 2.563E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 1.238E-002 | 3.180E-005 | 2.563E-004 | 3.755E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 1.297E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 1.297E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 5.239E-003 | 2.136E-004 | 1.165E-004 | 0.252 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 2.500E-002 | 7.539E-005 | 5.825E-005 | 8.904E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 2.500E-002 | 7.539E-005 | 5.825E-005 | 8.904E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 2.238E-002 | 2.167E-004 | 1.174E-004 | 0.256 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 2.191E-002 | 5.316E-005 | 4.403E-005 | 6.278E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1899 |
2 | Clear Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 0.1095 |
3 | Clear Turbid Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.2170 |
4 | Clear Turbid Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 0.1276 |
5 | Intermediate Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1259 |
6 | Intermediate Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 5.1187E-002 |
7 | Overcast Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 5.2070E-002 |
8 | Overcast Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 1.7298E-002 |
9 | Clear Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.2163 |
10 | Clear Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 0.1307 |
11 | Clear Turbid Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.2480 |
12 | Clear Turbid Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 0.1518 |
13 | Intermediate Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1392 |
14 | Intermediate Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 6.3753E-002 |
15 | Overcast Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 5.8462E-002 |
16 | Overcast Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 2.3647E-002 |
17 | Clear Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 4.7877E-002 |
18 | Clear Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 2.7663E-002 |
19 | Clear Turbid Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 3.6897E-002 |
20 | Clear Turbid Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 2.0957E-002 |
21 | Intermediate Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 3.5066E-002 |
22 | Intermediate Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.3987E-002 |
23 | Overcast Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 5.1255E-002 |
24 | Overcast Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.8174E-002 |
25 | Clear Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 4.7877E-002 |
26 | Clear Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 2.7663E-002 |
27 | Clear Turbid Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 3.6897E-002 |
28 | Clear Turbid Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 2.0957E-002 |
29 | Intermediate Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 3.5066E-002 |
30 | Intermediate Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.3987E-002 |
31 | Overcast Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 5.1255E-002 |
32 | Overcast Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.8174E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 34149.91091 | 34149.91091 | 2.58928 | 2.58928 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 25.03667 | 1.27170E-002 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
2 | BASEMENT | Heating | 1339.31674 | 1339.31674 | 5.99066E-002 | 0.85446 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
3 | RETAIL_1_FLR_1 | Cooling | 5954.06744 | 5954.06744 | 0.45149 | 0.45149 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 29.79000 | 1.27253E-002 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 3757.86446 | 3757.86446 | 0.16808 | 0.16808 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | -32.70000 | 1.83376E-004 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 3145.55023 | 3145.55023 | 0.23853 | 0.23853 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 29.85200 | 1.27254E-002 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 1209.43318 | 1209.43318 | 5.40960E-002 | 9.17347E-002 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 2400.88336 | 2400.88336 | 0.18202 | 0.18202 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 29.85200 | 1.27254E-002 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 2131.60365 | 2131.60365 | 9.53429E-002 | 9.53429E-002 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 1437.90777 | 1437.90777 | 0.10901 | 0.10901 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 30.10000 | 1.27259E-002 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 1578.87313 | 1578.87313 | 7.06203E-002 | 7.06203E-002 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 44718.07520 | 44718.07520 | 3.39059 | 3.39059 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 30.10000 | 1.27259E-002 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 2838.44177 | 2838.44177 | 0.12695 | 0.12695 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | -32.70000 | 1.83376E-004 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 23812.75496 | 23812.75496 | 1.80717 | 1.80717 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 29.79000 | 1.27253E-002 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 9626.29980 | 9626.29980 | 0.43056 | 0.67639 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | -32.70000 | 1.83376E-004 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 69864.38536 | 69864.38536 | 5.29929 | 5.29929 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 29.89333 | 1.27255E-002 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 21733.43522 | 21733.43522 | 0.97210 | 1.89399 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 12964.78124 | 12964.78124 | 1.32462 | 1.32462 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 28.15733 | 1.27224E-002 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 8506.86182 | 8506.86182 | 0.38272 | 0.38272 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | -32.70000 | 1.83376E-004 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 12349.24396 | 12349.24396 | 1.26173 | 1.26173 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 27.95067 | 1.27221E-002 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 8514.80988 | 8514.80988 | 0.38308 | 0.38308 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | -32.70000 | 1.83376E-004 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 82247.45678 | 82247.45678 | 8.40279 | 8.40279 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 29.89333 | 1.27255E-002 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 48441.36008 | 48441.36008 | 2.17942 | 2.17942 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | -32.70000 | 1.83376E-004 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 61263.00214 | 61263.00214 | 6.25942 | 6.25942 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 24.80933 | 1.27166E-002 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 48604.18991 | 48604.18991 | 2.18675 | 2.18675 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | -32.70000 | 1.83376E-004 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 11845.00470 | 11845.00470 | 1.21021 | 1.21021 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 25.03667 | 1.27170E-002 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 8523.54264 | 8523.54264 | 0.38347 | 0.38347 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | -32.70000 | 1.83376E-004 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 11265.58924 | 11265.58924 | 1.15101 | 1.15101 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 23.63133 | 1.27146E-002 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 8531.48915 | 8531.48915 | 0.38383 | 0.38383 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | -32.70000 | 1.83376E-004 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 22438.28759 | 22438.28759 | 1.70126 | 1.70126 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 30.10000 | 1.27259E-002 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 12997.67315 | 12997.67315 | 0.58137 | 0.58137 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | -32.70000 | 1.83376E-004 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 3373.29548 | 3373.29548 | 0.34465 | 0.34465 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 28.36400 | 1.27228E-002 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 2604.99103 | 2604.99103 | 0.11720 | 0.11720 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -32.70000 | 1.83376E-004 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 3199.81709 | 3199.81709 | 0.32693 | 0.32693 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 27.95067 | 1.27221E-002 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 2605.23837 | 2605.23837 | 0.11721 | 0.11721 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -32.70000 | 1.83376E-004 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 16505.84331 | 16505.84331 | 1.68644 | 1.68644 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 29.89333 | 1.27255E-002 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 12480.21578 | 12480.21578 | 0.56149 | 0.56149 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -32.70000 | 1.83376E-004 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 29183.96501 | 29183.96501 | 2.21551 | 2.21551 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 30.10000 | 1.27259E-002 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 8474.46098 | 8474.46098 | 0.37905 | 1.18780 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | -32.70000 | 1.83376E-004 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 30587.36029 | 30587.36029 | 2.32201 | 2.32201 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 30.10000 | 1.27259E-002 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
40 | DINING_FLR_6 | Heating | 8647.59821 | 8647.59821 | 0.38679 | 1.18780 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | -32.70000 | 1.83376E-004 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 31485.10697 | 31485.10697 | 2.39340 | 2.39340 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 25.03667 | 1.27170E-002 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 3546.07324 | 3546.07324 | 0.15859 | 0.36735 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | -32.70000 | 1.83376E-004 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
43 | CORRIDOR_FLR_6 | Cooling | 10942.46035 | 10942.46035 | 0.82965 | 0.82965 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 30.10000 | 1.27259E-002 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 8900.23568 | 8900.23568 | 0.39810 | 0.39810 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | -32.70000 | 1.83376E-004 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | FLR_3_DOAS | Cooling | Sensible | 41147.75 | 20.32361 | 2.05125 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | FLR_3_DOAS | Heating | Sensible | 117497.06 | 6.69516 | 2.05125 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 |
3 | VAV WITH REHEAT | Cooling | Sensible | 386013.72 | 23.38875 | 23.38875 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | VAV WITH REHEAT | Heating | Sensible | 441061.26 | 7.69998 | 7.69998 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.58928 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.58235 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.49600 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.28428 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.54246E-004 |
8 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.85576E-005 |
9 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.28428 |
10 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7836.55759 |
13 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.85576E-005 |
14 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 165.18288 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.45149 |
16 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11320 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.49600 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.22394 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.49600 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.36575E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.27817E-005 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.22394 |
24 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 4890.21661 |
27 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.27817E-005 |
28 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 123.68810 |
29 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.23853 |
30 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24812 |
31 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.49600 |
32 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.11831 |
33 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.66166 |
34 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.53554E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.58143E-005 |
37 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.11831 |
38 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1807.67696 |
41 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.58143E-005 |
42 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 42.16228 |
43 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.18202 |
44 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.68758 |
45 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.49600 |
46 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 9.02818E-002 |
47 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.54117E-004 |
50 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.28651E-005 |
51 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 9.53429E-002 |
52 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2613.62420 |
55 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.28651E-005 |
56 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 71.32922 |
57 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.10901 |
58 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.66236 |
59 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.49600 |
60 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 5.40709E-002 |
61 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.75215E-004 |
64 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.69366E-005 |
65 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 7.06203E-002 |
66 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1935.95859 |
69 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.69366E-005 |
70 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 52.83541 |
71 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.39059 |
72 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 1.75386E-002 |
73 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.49600 |
74 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.68173 |
75 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.49600 |
76 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.17235E-002 |
78 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.92044E-005 |
79 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.68173 |
80 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11339.67582 |
83 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.92044E-005 |
84 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 240.62514 |
85 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.80717 |
86 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.96345E-002 |
87 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.49600 |
88 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.89635 |
89 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.49600 |
90 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.78436E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.23870E-004 |
93 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.89635 |
94 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14159.14251 |
97 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.23870E-004 |
98 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 332.27227 |
99 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.29929 |
100 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18811 |
101 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.49600 |
102 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.62845 |
103 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.50162 |
104 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
105 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.02543E-003 |
106 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.06414E-004 |
107 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.62845 |
108 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
110 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 35024.97175 |
111 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.06414E-004 |
112 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 798.61293 |
113 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
114 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.32462 |
115 | Fan:OnOff | ROOM_1_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 1.32462 |
116 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 7.44212E-005 |
117 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.07297E-004 |
118 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70779 |
119 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
120 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.58877E-003 |
121 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
122 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
123 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.07297E-004 |
124 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.32462 |
125 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 8506.79997 |
126 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.44212E-005 |
127 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 243.06331 |
128 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
129 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.26173 |
130 | Fan:OnOff | ROOM_2_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 1.26173 |
131 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 7.44907E-005 |
132 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.88392E-004 |
133 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70778 |
134 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
135 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.59286E-003 |
136 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
137 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
138 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.88392E-004 |
139 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.26173 |
140 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 8514.74798 |
141 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.44907E-005 |
142 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 243.29038 |
143 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83707 |
144 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 8.40279 |
145 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 8.40279 |
146 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.23785E-004 |
147 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.53944E-003 |
148 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70833 |
149 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
150 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.52572E-003 |
151 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
152 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
153 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.53944E-003 |
154 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 8.40279 |
155 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 48441.17827 |
156 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.23785E-004 |
157 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1384.09547 |
158 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83730 |
159 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 6.25942 |
160 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 6.25942 |
161 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.25209E-004 |
162 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.01839E-003 |
163 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70740 |
164 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
165 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.76747E-003 |
166 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
167 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
168 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.01839E-003 |
169 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 6.25942 |
170 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 48604.00759 |
171 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.25209E-004 |
172 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1388.74739 |
173 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
174 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.21021 |
175 | Fan:OnOff | ROOM_5_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 1.21021 |
176 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 7.45671E-005 |
177 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.72990E-004 |
178 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70777 |
179 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
180 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.59735E-003 |
181 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
182 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
183 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.72990E-004 |
184 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.21021 |
185 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 8523.48070 |
186 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.45671E-005 |
187 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 243.53986 |
188 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
189 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.15101 |
190 | Fan:OnOff | ROOM_6_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 1.15101 |
191 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 7.46366E-005 |
192 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.55243E-004 |
193 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70776 |
194 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
195 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.60252E-003 |
196 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
197 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
198 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.55243E-004 |
199 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.15101 |
200 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 8531.42716 |
201 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.46366E-005 |
202 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 243.76688 |
203 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.70126 |
204 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.69766 |
205 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.49600 |
206 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.84382 |
207 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.46108E-004 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.51046E-004 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.84382 |
212 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
213 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
214 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17265.47050 |
215 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.51046E-004 |
216 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 429.02180 |
217 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54338E-002 |
218 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.34465 |
219 | Fan:OnOff | ROOM_1_FLR_6 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 0.34465 |
220 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.27895E-005 |
221 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.05872E-004 |
222 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70780 |
223 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
224 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.58523E-003 |
225 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
226 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
227 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.05872E-004 |
228 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.34465 |
229 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 2604.98185 |
230 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.27895E-005 |
231 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 74.42980 |
232 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54319E-002 |
233 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.32693 |
234 | Fan:OnOff | ROOM_2_FLR_6 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 0.32693 |
235 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.27917E-005 |
236 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.00549E-004 |
237 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70779 |
238 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
239 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.58966E-003 |
240 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
241 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
242 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.00549E-004 |
243 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.32693 |
244 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 2605.22919 |
245 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.27917E-005 |
246 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 74.43686 |
247 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 9.91540E-002 |
248 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.68644 |
249 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 1.68644 |
250 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.09182E-004 |
251 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 5.24398E-004 |
252 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70758 |
253 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
254 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.63018E-003 |
255 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
256 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
257 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.24398E-004 |
258 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.68644 |
259 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 12480.18155 |
260 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.09182E-004 |
261 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 356.58404 |
262 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.21551 |
263 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11407 |
264 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.49600 |
265 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.09889 |
266 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.49600 |
267 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
268 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.34005E-003 |
269 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.22763E-004 |
270 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.09889 |
271 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
272 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
273 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14032.53646 |
274 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.22763E-004 |
275 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 317.94041 |
276 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.32201 |
277 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10884 |
278 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.49600 |
279 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.15172 |
280 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.49600 |
281 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
282 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.50061E-003 |
283 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.26615E-004 |
284 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.15172 |
285 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
286 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
287 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14472.89076 |
288 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.26615E-004 |
289 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 327.16299 |
290 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.39340 |
291 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 5.91560E-002 |
292 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.49600 |
293 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.18713 |
294 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.49600 |
295 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
296 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.15842E-002 |
297 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.34805E-005 |
298 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.18713 |
299 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
300 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
301 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9542.33059 |
302 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.34805E-005 |
303 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 205.27295 |
304 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.82965 |
305 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.37852 |
306 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.49600 |
307 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.41150 |
308 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
309 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
310 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.00655E-003 |
311 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.60729E-005 |
312 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.41150 |
313 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
314 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
315 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10981.72190 |
316 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.60729E-005 |
317 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 296.62161 |
318 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05132 |
319 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05132 |
320 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05132 |
321 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05132 |
322 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05132 |
323 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05132 |
324 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
325 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
326 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 11.76460 |
327 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 11.67048 |
328 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 23.52920 |
329 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 11.67048 |
330 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 23.38875 |
331 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 23.38875 |
332 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
333 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.49898 |
334 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05132 |
335 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 23.38875 |
336 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05132 |
337 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05125 |
338 | HeatExchanger:AirToAir:SensibleAndLatent | FLR_3_DOAS OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.05125 |
339 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 30.10000 |
340 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
341 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.89838 |
342 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.27259E-002 |
343 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
344 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Coil Load [W] | 69550.08568 |
345 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.98912E-003 |
346 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 2.05132 |
347 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Rated Capacity [W] | 35250.35631 |
348 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.08385E-004 |
349 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 490.60592 |
350 | Fan:ConstantVolume | FLR_3_DOAS FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05125 |
351 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.98912E-003 |
352 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 2.39397E-004 |
353 | Controller:WaterCoil | FLR_3_DOAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.08385E-004 |
354 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 23.38875 |
355 | HeatExchanger:AirToAir:SensibleAndLatent | VAV WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 11.66146 |
356 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 27.03655 |
357 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
358 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.90673 |
359 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.11722E-002 |
360 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
361 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 628300.65873 |
362 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.79693E-002 |
363 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 23.38875 |
364 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 401918.22604 |
365 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.51616E-003 |
366 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 5593.80051 |
367 | Fan:VariableVolume | VAV WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 23.38875 |
368 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.79693E-002 |
369 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 2.65002E-005 |
370 | Controller:WaterCoil | VAV WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.51616E-003 |
371 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 2.67710E-002 |
372 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 4370.88851 |
373 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 6.40284E-003 |
374 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.76834 |
375 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 6.40284E-003 |
376 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 1928.25278 |
377 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
378 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 731883.39086 |
379 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 731883.39000 |
380 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 6.40284E-003 |
381 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 2.67710E-002 |
382 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 3.21252 |
383 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 2.67710E-002 |
384 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 3026.11354 |
385 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 2.67710E-002 |
386 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 936053.57616 |
387 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 936690.90000 |
388 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 106.78276 |
389 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
390 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
391 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
392 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
393 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | 7876.79 |
2 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 4910.85 |
3 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1816.03 |
4 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | 2623.72 |
5 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | 1943.44 |
6 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 11397.55 |
7 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | 14224.19 |
8 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | 35190.11 |
9 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | 9162.48 |
10 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | 9171.04 |
11 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 52175.04 |
12 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 52350.41 |
13 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | 9180.45 |
14 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | 9189.01 |
15 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 17339.52 |
16 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | 2805.73 |
17 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | 2805.99 |
18 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 13441.93 |
19 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | 14099.09 |
20 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | 14541.68 |
21 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | 9590.46 |
22 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 11024.55 |
23 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | 20221.20 |
24 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | 230558.45 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | 21698.77 | 18422.57 | 3276.20 | 0.85 | 5110.56 | 51.83 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | 20684.35 | 17553.01 | 3131.33 | 0.85 | 4863.18 | 49.33 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 136005.59 | 116333.07 | 19672.52 | 0.86 | 32907.95 | 333.77 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 105930.82 | 88179.89 | 17750.93 | 0.83 | 23379.33 | 237.13 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | 19856.40 | 16841.67 | 3014.73 | 0.85 | 4659.65 | 47.26 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | 18903.22 | 16023.70 | 2879.52 | 0.85 | 4426.38 | 44.89 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | 5642.05 | 4792.15 | 849.90 | 0.85 | 1330.85 | 13.50 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | 5356.33 | 4547.14 | 809.20 | 0.85 | 1261.06 | 12.79 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 27841.52 | 23525.70 | 4315.82 | 0.84 | 6452.44 | 65.44 |
10 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | 60070.69 | 38934.02 | 21136.67 | 0.65 | 8372.83 | 84.92 |
11 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | 649097.17 | 429415.92 | 219681.25 | 0.66 | 102864.40 | 1043.31 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 4.09 | 13.95 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.270 | 0.259 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.270 | 0.259 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.270 | 0.259 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.270 | 0.259 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.591 | 0.543 | 22.63 | 45.89 | 22.63 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.33_SHGC_0.45 | N/A | 1.875 | No | 23.26 | 23.26 | 23.26 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.591 | 0.543 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.591 | 0.543 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.591 | 0.543 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.591 | 0.543 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 2.390 | 2.390 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.591 | 0.543 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.591 | 0.543 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.591 | 0.543 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.591 | 0.543 | 63.73 | 129.23 | 63.73 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.33_SHGC_0.45 | N/A | 1.875 | No | 65.50 | 65.50 | 65.50 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.591 | 0.543 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.591 | 0.543 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.591 | 0.543 | 82.79 | 167.88 | 82.79 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.33_SHGC_0.45 | N/A | 1.875 | No | 85.08 | 85.08 | 85.08 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.591 | 0.543 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.780 | 0.698 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.33_SHGC_0.45 | N/A | 1.875 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.780 | 0.698 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.33_SHGC_0.45 | N/A | 1.875 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.780 | 0.698 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.33_SHGC_0.45 | N/A | 1.875 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.780 | 0.698 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.33_SHGC_0.45 | N/A | 1.875 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.780 | 0.698 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.33_SHGC_0.45 | N/A | 1.875 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.780 | 0.698 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.33_SHGC_0.45 | N/A | 1.875 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.780 | 0.698 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.33_SHGC_0.45 | N/A | 1.875 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.780 | 0.698 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.33_SHGC_0.45 | N/A | 1.875 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.780 | 0.698 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.33_SHGC_0.45 | N/A | 1.875 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.780 | 0.698 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.33_SHGC_0.45 | N/A | 1.875 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.780 | 0.698 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.33_SHGC_0.45 | N/A | 1.875 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.780 | 0.698 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.33_SHGC_0.45 | N/A | 1.875 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.780 | 0.698 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.33_SHGC_0.45 | N/A | 1.875 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.780 | 0.698 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.33_SHGC_0.45 | N/A | 1.875 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.792 | 0.708 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.33_SHGC_0.45 | N/A | 1.875 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.792 | 0.708 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.33_SHGC_0.45 | N/A | 1.875 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.163 | 0.158 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.792 | 0.708 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.33_SHGC_0.45 | N/A | 1.875 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.792 | 0.708 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.33_SHGC_0.45 | N/A | 1.875 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.163 | 0.158 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.792 | 0.708 | 13.70 | 20.44 | 13.70 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.33_SHGC_0.45 | N/A | 1.875 | No | 6.74 | 6.74 | 6.74 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.163 | 0.158 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.792 | 0.708 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.33_SHGC_0.45 | N/A | 1.875 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.792 | 0.708 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.33_SHGC_0.45 | N/A | 1.875 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.792 | 0.708 | 16.77 | 21.37 | 16.77 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.33_SHGC_0.45 | N/A | 1.875 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.792 | 0.708 | 34.86 | 52.03 | 34.86 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.33_SHGC_0.45 | N/A | 1.875 | No | 17.17 | 17.17 | 17.17 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.792 | 0.708 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.33_SHGC_0.45 | N/A | 1.875 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.792 | 0.708 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.33_SHGC_0.45 | N/A | 1.875 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.792 | 0.708 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.33_SHGC_0.45 | N/A | 1.875 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.792 | 0.708 | 34.86 | 52.03 | 34.86 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.33_SHGC_0.45 | N/A | 1.875 | No | 17.17 | 17.17 | 17.17 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 3.7357825631E-002 | 8.5958995930E-002 | Pass | Pass | 6.0409768139E-002 | 0.3608898952 | Pass | Pass |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 9.4221214144E-002 | 0.1634793617 | Pass | Pass | 0.2285486952 | 0.6662896563 | Pass | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.0119449738E-002 | 9.9260676961E-002 | Pass | Pass | 0.1387523506 | 0.3948382325 | Pass | Pass |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.6041699585E-002 | 4.4847631930E-002 | Pass | Pass | 7.1283043100E-002 | 0.4160652193 | Pass | Pass |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 3.1411687179E-002 | 4.9807814679E-002 | Pass | Pass | 2.6654658618E-002 | 0.1880527243 | Pass | Pass |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 0.1833067261 | 0.5687734571 | Pass | Pass | 2.6311047217E-002 | 6.7189106015E-002 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 9.2971916727E-002 | 0.1448626372 | Pass | Pass | 4.0810485621E-002 | 8.4861297454E-002 | Pass | Pass |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 5.1990805163E-002 | 0.1081055467 | Pass | Pass | 4.4682548881E-002 | 0.1196813800 | Pass | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.4871799417E-002 | 0.2933166392 | Pass | Pass | 7.7034649206E-002 | 0.2487283073 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.2691171840E-002 | 0.3317795481 | Pass | Pass | 8.1343070769E-002 | 0.2551178113 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 8.9187889197E-002 | 7.6660565983E-002 | Pass | Pass | 7.3662803179E-003 | 7.7607371904E-002 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 8.7610920099E-002 | 0.2062166456 | Pass | Pass | 6.2206441236E-002 | 0.2371013985 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.3694136680E-002 | 0.3161924877 | Pass | Pass | 0.1173056982 | 0.3152794358 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.2699810320E-002 | 0.3246805350 | Pass | Pass | 8.1834991511E-002 | 0.2649613515 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 2.3351245568E-002 | 5.5819611301E-002 | Pass | Pass | 5.5119901777E-002 | 0.1000784922 | Pass | Pass |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.8308800443E-002 | 0.3318678228 | Pass | Pass | 0.1089988011 | 0.3435263471 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.2774870724E-002 | 0.3408984713 | Pass | Pass | 6.5141189488E-002 | 0.2199557264 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 8.1059640232E-002 | 0.2923402452 | Pass | Pass | 0.2092428039 | 0.6536963240 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 8.1177356338E-002 | 0.1878443811 | Pass | Pass | 1.8752383921E-002 | 4.6780357383E-002 | Pass | Pass |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 8.5849495708E-002 | 0.1912778484 | Pass | Pass | 1.7081119678E-002 | 4.2012446258E-002 | Pass | Pass |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 0.1359712327 | 0.3780935674 | Pass | Pass | 2.5653425378E-002 | 4.9519017192E-002 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 3.7232754199E-002 | 8.1946181353E-002 | Pass | Pass | 0.1347760858 | 0.8866906108 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:43
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3852.01 | 92.96 | 2563.19 | 10718.53 | 3427.08 | 20653.78 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:43
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | -32.70 | 0.00 | -32.70 | Wetbulb [C] | 2.40 | 210.00 |
INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 30.10 | 12.40 | 21.10 | Wetbulb [C] | 4.70 | 200.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 12.00 | 13 | |||
Apr | 16.00 | 23 | |||
May | 0.00 | 0 | |||
Jun | 190.00 | 53 | |||
Jul | 136.00 | 41 | |||
Aug | 87.00 | 42 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:43
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.261 | 0.270 | 211.13 | 211.13 | 0.00 | 90.00 | N |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.261 | 0.270 | 55.76 | 55.76 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.261 | 0.270 | 211.13 | 211.13 | 180.00 | 90.00 | S |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.261 | 0.270 | 55.76 | 55.76 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.543 | 0.591 | 45.89 | 22.63 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.543 | 0.591 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.543 | 0.591 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.543 | 0.591 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.543 | 0.591 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.543 | 0.591 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.543 | 0.591 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.543 | 0.591 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.543 | 0.591 | 129.23 | 63.73 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.543 | 0.591 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.543 | 0.591 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.543 | 0.591 | 167.88 | 82.79 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.543 | 0.591 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 104.06 | 69.72 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 847.14 | 567.58 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 847.37 | 567.71 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 104.06 | 69.72 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 26.02 | 17.43 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.708 | 0.792 | 13.94 | 9.34 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.708 | 0.792 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | RES_ROOF | 0.23 | 0.159 | 0.163 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | RES_EXT_WALL_TOP | 0.30 | 0.708 | 0.792 | 13.94 | 9.34 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.708 | 0.792 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | RES_ROOF | 0.23 | 0.159 | 0.163 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.708 | 0.792 | 183.96 | 123.26 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | RES_ROOF | 0.23 | 0.159 | 0.163 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.708 | 0.792 | 97.55 | 65.36 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.708 | 0.792 | 97.55 | 65.36 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.708 | 0.792 | 21.37 | 16.77 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.708 | 0.792 | 52.03 | 34.86 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.708 | 0.792 | 13.94 | 9.34 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.708 | 0.792 | 17.65 | 11.83 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.708 | 0.792 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.708 | 0.792 | 52.03 | 34.86 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 167.42 | 167.42 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_FLOOR | BASEMENT_FLOOR | 0.30 | 1.441 | 2.705 | 1978.83 | 1978.83 | 0.00 | 180.00 | |
BASEMENT_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 67.07 | 67.07 | 180.00 | 0.00 | |
BASEMENT_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 77.67 | 77.67 | 180.00 | 0.00 | |
BASEMENT_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 164.24 | 164.24 | 180.00 | 0.00 | |
BASEMENT_CEILING_4 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 94.76 | 94.76 | 180.00 | 0.00 | |
BASEMENT_CEILING_5 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 78.04 | 78.04 | 180.00 | 0.00 | |
BASEMENT_CEILING_6 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 188.86 | 188.86 | 180.00 | 0.00 | |
BASEMENT_CEILING_7 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 1088.56 | 1088.56 | 180.00 | 0.00 | |
BASEMENT_CEILING_8 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 219.63 | 219.63 | 90.00 | 0.00 | |
RETAIL_1_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_1_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
RETAIL_1_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 67.07 | 67.07 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
RETAIL_2_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_2_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 90.00 | 90.00 | E |
RETAIL_2_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 77.67 | 77.67 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 77.67 | 77.67 | 180.00 | 0.00 | |
MECH_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
MECH_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 180.00 | 90.00 | S |
MECH_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
MECH_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 164.24 | 164.24 | 0.00 | 180.00 | |
MECH_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 164.24 | 164.24 | 180.00 | 0.00 | |
STORAGE_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
STORAGE_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 180.00 | 90.00 | S |
STORAGE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
STORAGE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 94.76 | 94.76 | 0.00 | 180.00 | |
STORAGE_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 94.76 | 94.76 | 180.00 | 0.00 | |
LAUNDRY_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 180.00 | 90.00 | S |
LAUNDRY_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 270.00 | 90.00 | W |
LAUNDRY_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 78.04 | 78.04 | 0.00 | 180.00 | |
LAUNDRY_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 78.04 | 78.04 | 180.00 | 0.00 | |
CAFE_FLR_1_WALL_1_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_2_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
CAFE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 188.86 | 188.86 | 0.00 | 180.00 | |
LOBBY_FLR_1_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 90.00 | 90.00 | E |
LOBBY_FLR_1_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 1088.56 | 1088.56 | 180.00 | 180.00 | |
LOBBY_FLR_1_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 219.63 | 219.63 | 90.00 | 180.00 | |
LOBBY_FLR_1_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 1062.83 | 1062.83 | 270.00 | 0.00 | |
ROOM_1_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_1_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
ROOM_1_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_1_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_2_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
ROOM_2_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_2_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_2_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 156.07 | 156.07 | 180.00 | 0.00 | |
ROOM_3_MULT19_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.14 | 847.14 | 0.00 | 90.00 | N |
ROOM_3_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_3_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 1863.81 | 1863.81 | 0.00 | 180.00 | |
ROOM_3_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 1863.81 | 1863.81 | 180.00 | 0.00 | |
ROOM_4_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_4_MULT19_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.37 | 847.37 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_4_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 1864.32 | 1864.32 | 0.00 | 180.00 | |
ROOM_4_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 1864.32 | 1864.32 | 180.00 | 0.00 | |
ROOM_5_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
ROOM_5_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_5_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_6_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
ROOM_6_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_6_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 156.07 | 156.07 | 180.00 | 0.00 | |
CORRIDOR_FLR_3_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.28 | 847.28 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_4_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.27 | 847.27 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 297.29 | 297.29 | 180.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 963.06 | 963.06 | 270.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_3 | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 297.26 | 297.26 | 90.00 | 180.00 | |
CORRIDOR_FLR_3_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 297.29 | 297.29 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 963.06 | 963.06 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 297.26 | 297.26 | 90.00 | 0.00 | |
ROOM_1_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 0.00 | 90.00 | N |
ROOM_1_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_1_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_2_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_2_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 180.00 | 90.00 | S |
ROOM_2_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_3_MULT9_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.96 | 183.96 | 0.00 | 90.00 | N |
ROOM_3_MULT9_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 90.00 | 90.00 | E |
ROOM_3_MULT9_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 270.00 | 90.00 | W |
ROOM_3_MULT9_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 220.77 | 220.77 | 0.00 | 180.00 | |
BANQUET_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
BANQUET_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
BANQUET_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
BANQUET_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 331.66 | 331.66 | 0.00 | 180.00 | |
DINING_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
DINING_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
DINING_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
DINING_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 331.66 | 331.66 | 0.00 | 180.00 | |
KITCHEN_FLR_6_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 7.43 | 7.43 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 103.30 | 103.30 | 180.00 | 180.00 | |
CORRIDOR_FLR_6_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 104.98 | 104.98 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_1_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.95 | 183.95 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 11.15 | 11.15 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 40.88 | 40.88 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 412.12 | 412.12 | 180.00 | 180.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3957.66 | 0.00 | 90.00 | N | ||
RETAIL_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 134.14 | 0.00 | 90.00 | N | ||
RETAIL_2_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 155.34 | 0.00 | 90.00 | N | ||
MECH_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 328.49 | 0.00 | 90.00 | N | ||
STORAGE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 189.52 | 0.00 | 90.00 | N | ||
LAUNDRY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 156.08 | 0.00 | 90.00 | N | ||
CAFE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 377.72 | 0.00 | 90.00 | N | ||
LOBBY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 2616.37 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3727.63 | 0.00 | 90.00 | N | ||
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3728.64 | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3115.24 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.04 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.03 | 0.00 | 90.00 | N | ||
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 441.55 | 0.00 | 90.00 | N | ||
BANQUET_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
DINING_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 206.61 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 824.25 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.33_SHGC_0.45 | 23.26 | 0.00 | 0.00 | 23.26 | 23.26 | 1.875 | 0.451 | 0.497 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.33_SHGC_0.45 | 65.50 | 0.00 | 0.00 | 65.50 | 65.50 | 1.875 | 0.451 | 0.497 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.33_SHGC_0.45 | 85.08 | 0.00 | 0.00 | 85.08 | 85.08 | 1.875 | 0.451 | 0.497 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.33_SHGC_0.45 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 1.875 | 0.451 | 0.497 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.33_SHGC_0.45 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 1.875 | 0.451 | 0.497 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.33_SHGC_0.45 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 1.875 | 0.451 | 0.497 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.33_SHGC_0.45 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 1.875 | 0.451 | 0.497 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.33_SHGC_0.45 | 3.68 | 0.00 | 0.00 | 3.68 | 279.56 | 1.875 | 0.451 | 0.497 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.33_SHGC_0.45 | 3.68 | 0.00 | 0.00 | 3.68 | 279.65 | 1.875 | 0.451 | 0.497 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.33_SHGC_0.45 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 1.875 | 0.451 | 0.497 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.33_SHGC_0.45 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 1.875 | 0.451 | 0.497 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.33_SHGC_0.45 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 1.875 | 0.451 | 0.497 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.33_SHGC_0.45 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 1.875 | 0.451 | 0.497 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.33_SHGC_0.45 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 1.875 | 0.451 | 0.497 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.33_SHGC_0.45 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 1.875 | 0.451 | 0.497 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.33_SHGC_0.45 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 1.875 | 0.451 | 0.497 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.33_SHGC_0.45 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 1.875 | 0.451 | 0.497 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.33_SHGC_0.45 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 1.875 | 0.451 | 0.497 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.33_SHGC_0.45 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 1.875 | 0.451 | 0.497 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.33_SHGC_0.45 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 1.875 | 0.451 | 0.497 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.33_SHGC_0.45 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 1.875 | 0.451 | 0.497 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.33_SHGC_0.45 | 6.74 | 0.00 | 0.00 | 6.74 | 60.70 | 1.875 | 0.451 | 0.497 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.33_SHGC_0.45 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 1.875 | 0.451 | 0.497 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.33_SHGC_0.45 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 1.875 | 0.451 | 0.497 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.33_SHGC_0.45 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 1.875 | 0.451 | 0.497 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.33_SHGC_0.45 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 1.875 | 0.451 | 0.497 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | |||||||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.33_SHGC_0.45 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 1.875 | 0.451 | 0.497 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.33_SHGC_0.45 | 5.82 | 0.00 | 0.00 | 5.82 | 5.82 | 1.875 | 0.451 | 0.497 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.33_SHGC_0.45 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 1.875 | 0.451 | 0.497 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.33_SHGC_0.45 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 1.875 | 0.451 | 0.497 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 1213.79 | 1.875 | 0.451 | 0.497 | |||||||||||||||||
North Total or Average | 432.95 | 1.875 | 0.451 | 0.497 | |||||||||||||||||
Non-North Total or Average | 780.84 | 1.875 | 0.451 | 0.497 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 1.760 | 2.390 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:43
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:43
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 8.8143 | 1978.83 | 17441.96 | LightsWired | LTG_SCH_BASEMENT | 49.32 | 168.00 | 49.26 | 0.0000 | Y | 161.29 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | RETAIL_1_FLR_1 | GENERAL | 11.3140 | 67.07 | 758.85 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 7.31 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | RETAIL_2_FLR_1 | GENERAL | 11.3140 | 77.67 | 878.75 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 8.46 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | MECH_FLR_1 | GENERAL | 4.6285 | 164.24 | 760.20 | LightsWired | LTG_SCH_MECHANIC | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 8.37 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | STORAGE_FLR_1 | GENERAL | 5.7199 | 94.76 | 542.02 | LightsWired | LTG_SCH_STORAGE | 30.30 | 168.00 | 30.27 | 0.0000 | Y | 3.08 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | LAUNDRY_FLR_1 | GENERAL | 4.6285 | 78.04 | 361.20 | LightsWired | LTG_SCH_LAUNDRY | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 3.98 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | CAFE_FLR_1 | GENERAL | 10.0104 | 188.86 | 1890.59 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 39.02 | 0.0000 | Y | 13.85 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | LOBBY_FLR_1 | GENERAL | 10.7639 | 1308.19 | 14081.18 | LightsWired | LTG_SCH_LOBBY | 44.02 | 168.00 | 41.49 | 0.0000 | Y | 109.66 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | ROOM_1_FLR_3 | GENERAL | 8.2882 | 156.09 | 1293.69 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | ROOM_2_FLR_3 | GENERAL | 8.2882 | 156.07 | 1293.54 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | GENERAL | 8.2882 | 1863.81 | 15447.65 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 110.38 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | GENERAL | 8.2882 | 1864.32 | 15451.87 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 110.41 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | ROOM_5_FLR_3 | GENERAL | 8.2882 | 156.09 | 1293.69 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | ROOM_6_FLR_3 | GENERAL | 8.2882 | 156.07 | 1293.54 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | CORRIDOR_FLR_3 | GENERAL | 7.1042 | 1557.62 | 11065.59 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 91.33 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | ROOM_1_FLR_6 | GENERAL | 8.2882 | 39.02 | 323.42 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 2.31 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | ROOM_2_FLR_6 | GENERAL | 8.2882 | 39.02 | 323.38 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 2.31 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | GENERAL | 8.2882 | 220.77 | 1829.83 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 13.08 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | BANQUET_FLR_6 | GENERAL | 10.0104 | 331.66 | 3320.03 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 48.94 | 0.0000 | Y | 30.50 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | DINING_FLR_6 | GENERAL | 10.0104 | 331.66 | 3320.03 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 48.94 | 0.0000 | Y | 30.50 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | KITCHEN_FLR_6 | GENERAL | 11.4097 | 103.30 | 1178.68 | LightsWired | LTG_SCH_KITCHEN | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 12.97 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | CORRIDOR_FLR_6 | GENERAL | 7.1042 | 412.12 | 2927.80 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 24.17 |
Interior Lighting Total | 8.5566 | 11345.29 | 97077.49 | 455.19 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
LOBBY_FLR_1_DAYLREFPT1 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.07 | 14081.18 | 985.68 |
LOBBY_FLR_1_DAYLREFPT2 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.07 | 14081.18 | 985.68 |
CAFE_FLR_1_DAYLREFPT1 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1890.59 | 737.33 |
CAFE_FLR_1_DAYLREFPT2 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1890.59 | 737.33 |
DINING_FLR_6_DAYLREFPT1 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
DINING_FLR_6_DAYLREFPT2 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
BANQUET_FLR_6_DAYLREFPT1 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
BANQUET_FLR_6_DAYLREFPT2 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 12338.45 | AstronomicalClock | - | 83.52 | 83.52 | 193.43 | |
Exterior Lighting Total | 12338.45 | 193.43 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:43
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 731883.39 | 0.80 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 936690.90 | 2.96 | 936690.90 | 2.96 | 4.09 | 13.95 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 14241.49 | 21698.77 | 18422.57 | 3276.20 | 0.85 | - | 5110.56 | 51.83 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 13580.47 | 20684.35 | 17553.01 | 3131.33 | 0.85 | - | 4863.18 | 49.33 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 88793.52 | 136005.59 | 116333.07 | 19672.52 | 0.86 | - | 32907.95 | 333.77 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 70574.85 | 105930.82 | 88179.89 | 17750.93 | 0.83 | - | 23379.33 | 237.13 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 13041.91 | 19856.40 | 16841.67 | 3014.73 | 0.85 | - | 4659.65 | 47.26 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 12421.36 | 18903.22 | 16023.70 | 2879.52 | 0.85 | - | 4426.38 | 44.89 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3701.91 | 5642.05 | 4792.15 | 849.90 | 0.85 | - | 1330.85 | 13.50 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3515.78 | 5356.33 | 4547.14 | 809.20 | 0.85 | - | 1261.06 | 12.79 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 18336.01 | 27841.52 | 23525.70 | 4315.82 | 0.84 | - | 6452.44 | 65.44 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | 69550.09 | 60070.69 | 38934.02 | 21136.67 | 0.65 | - | 8372.83 | 84.92 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | 628300.66 | 649097.17 | 429415.92 | 219681.25 | 0.66 | - | 102864.40 | 1043.31 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 7836.56 | 7876.79 | - |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 4890.22 | 4910.85 | - |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1807.68 | 1816.03 | - |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2613.62 | 2623.72 | - |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1935.96 | 1943.44 | - |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 11339.68 | 11397.55 | - |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 14159.14 | 14224.19 | - |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 35024.97 | 35190.11 | - |
ROOM_1_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 8506.80 | 9162.48 | - |
ROOM_2_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 8514.75 | 9171.04 | - |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 48441.18 | 52175.04 | - |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 48604.01 | 52350.41 | - |
ROOM_5_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 8523.48 | 9180.45 | - |
ROOM_6_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 8531.43 | 9189.01 | - |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 17265.47 | 17339.52 | - |
ROOM_1_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 2604.98 | 2805.73 | - |
ROOM_2_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 2605.23 | 2805.99 | - |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 12480.18 | 13441.93 | - |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 14032.54 | 14099.09 | - |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 14472.89 | 14541.68 | - |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 9542.33 | 9590.46 | - |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 10981.72 | 11024.55 | - |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | 35250.36 | 20221.20 | - |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | 401918.23 | 230558.45 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 0.24 | 76.61 | 324.68 | 1.00 | 2.78 | General | ||
LOBBY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.24 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
ROOM_1_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 1.32 | 932.05 | 703.64 | 1.00 | 1.13 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 |
ROOM_2_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 1.26 | 887.80 | 703.64 | 1.00 | 1.14 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 |
ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 8.40 | 5912.51 | 703.64 | 1.00 | 0.94 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 6.26 | 4404.35 | 703.64 | 1.00 | 0.96 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 |
ROOM_5_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 1.21 | 851.55 | 703.64 | 1.00 | 1.15 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 |
ROOM_6_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 1.15 | 809.89 | 703.64 | 1.00 | 1.16 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 |
ROOM_1_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 0.34 | 242.51 | 703.64 | 1.00 | 1.62 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
ROOM_2_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 0.33 | 230.04 | 703.64 | 1.00 | 1.66 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 |
ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 1.69 | 1186.64 | 703.64 | 1.00 | 1.09 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
BANQUET_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
DINING_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 1.89 | 612.92 | 324.68 | 1.00 | 1.48 | General | ||
FLR_3_DOAS FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.93 | 1070.05 | 1.00 | 1.30 | General | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 |
VAV WITH REHEAT FAN | Fan:VariableVolume | 0.62 | 1389.42 | 23.39 | 52405.74 | 2240.64 | 1.00 | 1.11 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.026771 | 4370.89 | 163269.44 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.006403 | 1928.25 | 301156.09 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.026771 | 3026.11 | 113036.94 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH LAUNDRY G WATER HEATER | WaterHeater:Mixed | 1.14 | 163316.00 | 0.80 | 11.51 | 0.44 |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.22 | 1.12 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.60 | 0.80 | 5.78 | 0.37 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:43
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 34149.91 | 34149.91 | 17.26 | 2.589 | 2.589 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 24.00 | 24.00 | 0.00921 | 25.04 | 0.01272 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 5954.07 | 5954.07 | 88.77 | 0.451 | 0.451 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 24.00 | 0.00895 | 29.79 | 0.01273 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 3145.55 | 3145.55 | 40.50 | 0.239 | 0.239 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 24.00 | 24.00 | 0.00943 | 29.85 | 0.01273 | 0.092 | 0.00 |
MECH_FLR_1 | 2400.88 | 2400.88 | 14.62 | 0.182 | 0.182 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 24.00 | 24.00 | 0.00883 | 29.85 | 0.01273 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1437.91 | 1437.91 | 15.17 | 0.109 | 0.109 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00890 | 30.10 | 0.01273 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 44718.08 | 44718.08 | 573.02 | 3.391 | 3.391 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00855 | 30.10 | 0.01273 | 0.000 | 0.00 |
CAFE_FLR_1 | 23812.75 | 23812.75 | 126.09 | 1.807 | 1.807 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 23.99 | 0.00987 | 29.79 | 0.01273 | 0.676 | 0.00 |
LOBBY_FLR_1 | 69864.39 | 69864.39 | 53.41 | 5.299 | 5.299 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 23.99 | 0.00988 | 29.89 | 0.01273 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 12964.78 | 12964.78 | 332.24 | 1.325 | 1.325 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 21.11 | 21.11 | 0.00859 | 28.16 | 0.01272 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 12349.24 | 12349.24 | 316.51 | 1.262 | 1.262 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 21.11 | 21.11 | 0.00859 | 27.95 | 0.01272 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 82247.46 | 82247.46 | 3353.78 | 8.403 | 8.403 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 21.11 | 21.11 | 0.00853 | 29.89 | 0.01273 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 61263.00 | 61263.00 | 2497.42 | 6.259 | 6.259 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 21.11 | 21.11 | 0.00877 | 24.81 | 0.01272 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 11845.00 | 11845.00 | 303.55 | 1.210 | 1.210 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 21.11 | 21.11 | 0.00860 | 25.04 | 0.01272 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 11265.59 | 11265.59 | 288.73 | 1.151 | 1.151 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 21.11 | 21.11 | 0.00860 | 23.63 | 0.01271 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 22438.29 | 22438.29 | 57.62 | 1.701 | 1.701 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00937 | 30.10 | 0.01273 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 3373.30 | 3373.30 | 86.45 | 0.345 | 0.345 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 21.11 | 21.11 | 0.00859 | 28.36 | 0.01272 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 3199.82 | 3199.82 | 82.01 | 0.327 | 0.327 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 21.11 | 21.11 | 0.00859 | 27.95 | 0.01272 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 16505.84 | 16505.84 | 672.87 | 1.686 | 1.686 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 21.11 | 21.11 | 0.00863 | 29.89 | 0.01273 | 0.099 | 0.00 |
BANQUET_FLR_6 | 29183.97 | 29183.97 | 87.99 | 2.216 | 2.216 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 23.98 | 0.01044 | 30.10 | 0.01273 | 1.188 | 0.00 |
DINING_FLR_6 | 30587.36 | 30587.36 | 92.23 | 2.322 | 2.322 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 23.98 | 0.01035 | 30.10 | 0.01273 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 31485.11 | 31485.11 | 304.78 | 2.393 | 2.393 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 24.00 | 23.97 | 0.00997 | 25.04 | 0.01272 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 10942.46 | 10942.46 | 26.55 | 0.830 | 0.830 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 24.00 | 0.00898 | 30.10 | 0.01273 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 1339.32 | 1339.32 | 0.68 | 0.060 | 0.854 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00793 | -32.70 | 0.00018 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 3757.86 | 3757.86 | 56.03 | 0.168 | 0.168 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 21.00 | 21.00 | 0.00776 | -32.70 | 0.00018 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 1209.43 | 1209.43 | 15.57 | 0.054 | 0.092 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00771 | -32.70 | 0.00018 | 0.092 | 0.00 |
MECH_FLR_1 | 2131.60 | 2131.60 | 12.98 | 0.095 | 0.095 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00762 | -32.70 | 0.00018 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1578.87 | 1578.87 | 16.66 | 0.071 | 0.071 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00770 | -32.70 | 0.00018 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 2838.44 | 2838.44 | 36.37 | 0.127 | 0.127 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 21.00 | 21.00 | 0.00761 | -32.70 | 0.00018 | 0.000 | 0.00 |
CAFE_FLR_1 | 9626.30 | 9626.30 | 50.97 | 0.431 | 0.676 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 21.00 | 21.00 | 0.00779 | -32.70 | 0.00018 | 0.676 | 0.00 |
LOBBY_FLR_1 | 21733.44 | 21733.44 | 16.61 | 0.972 | 1.894 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00774 | -32.70 | 0.00018 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 8506.86 | 8506.86 | 218.00 | 0.383 | 0.383 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 21.11 | 21.11 | 0.00775 | -32.70 | 0.00018 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 8514.81 | 8514.81 | 218.23 | 0.383 | 0.383 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 21.11 | 21.11 | 0.00775 | -32.70 | 0.00018 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 48441.36 | 48441.36 | 1975.28 | 2.179 | 2.179 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 21.11 | 21.11 | 0.00777 | -32.70 | 0.00018 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 48604.19 | 48604.19 | 1981.37 | 2.187 | 2.187 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 21.11 | 21.11 | 0.00777 | -32.70 | 0.00018 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 8523.54 | 8523.54 | 218.43 | 0.383 | 0.383 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 21.11 | 21.11 | 0.00775 | -32.70 | 0.00018 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 8531.49 | 8531.49 | 218.66 | 0.384 | 0.384 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 21.11 | 21.11 | 0.00775 | -32.70 | 0.00018 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 12997.67 | 12997.67 | 33.38 | 0.581 | 0.581 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 21.00 | 21.00 | 0.00780 | -32.70 | 0.00018 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 2604.99 | 2604.99 | 66.76 | 0.117 | 0.117 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00780 | -32.70 | 0.00018 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2605.24 | 2605.24 | 66.77 | 0.117 | 0.117 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00780 | -32.70 | 0.00018 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 12480.22 | 12480.22 | 508.76 | 0.561 | 0.561 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00780 | -32.70 | 0.00018 | 0.099 | 0.00 |
BANQUET_FLR_6 | 8474.46 | 8474.46 | 25.55 | 0.379 | 1.188 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 21.00 | 21.00 | 0.00785 | -32.70 | 0.00018 | 1.188 | 0.00 |
DINING_FLR_6 | 8647.60 | 8647.60 | 26.07 | 0.387 | 1.188 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 21.00 | 21.00 | 0.00785 | -32.70 | 0.00018 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 3546.07 | 3546.07 | 34.33 | 0.159 | 0.367 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 21.00 | 21.00 | 0.00735 | -32.70 | 0.00018 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 8900.24 | 8900.24 | 21.60 | 0.398 | 0.398 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 21.00 | 21.00 | 0.00787 | -32.70 | 0.00018 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
FLR_3_DOAS | 20.32 | 2.05 | 6.70 | 2.05 | 2.0513 | 2.0513 | 2.0513 | 1.0000 | 0.3000 |
VAV WITH REHEAT | 23.39 | 23.39 | 7.70 | 7.70 | 23.3888 | 11.6705 | 23.3888 | 0.4990 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 7836.558 | 7836.558 | 1.284284 | 0.00006856 | 165.183 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 7836.56 | 7836.56 | 1.284284 | 16.70 | 12.79 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00793097 | 49.1373 | 1339.32 | 0.00 | 7880.43 | 7880.43 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 4890.217 | 4890.217 | 0.223940 | 0.00004278 | 123.688 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 4890.22 | 4890.22 | 0.223940 | 16.70 | 12.79 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00775772 | 48.0795 | 3757.86 | 0.00 | 4915.34 | 4915.34 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 1807.677 | 1807.677 | 0.118310 | 0.00001581 | 42.162 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 1807.68 | 1807.68 | 0.118310 | 16.70 | 12.79 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00771121 | 47.7935 | 1209.43 | 0.00 | 1817.33 | 1817.33 |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 2613.624 | 2613.624 | 0.095343 | 0.00002287 | 71.329 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 2613.62 | 2613.62 | 0.095343 | 16.70 | 12.79 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00761756 | 47.2203 | 2131.60 | 0.00 | 2626.59 | 2626.59 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 1935.959 | 1935.959 | 0.070620 | 0.00001694 | 52.835 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 1935.96 | 1935.96 | 0.070620 | 16.70 | 12.79 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00769886 | 47.7180 | 1578.87 | 0.00 | 1945.56 | 1945.56 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 11339.676 | 11339.676 | 1.681732 | 0.00009920 | 240.625 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 11339.68 | 11339.68 | 1.681732 | 16.70 | 12.79 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00760831 | 47.1649 | 2838.44 | 0.00 | 11403.02 | 11403.02 |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 14159.143 | 14159.143 | 0.896354 | 0.00012387 | 332.272 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 14159.14 | 14159.14 | 0.896354 | 16.70 | 12.79 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00779003 | 48.2768 | 9626.30 | 0.00 | 14234.61 | 14234.61 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 35024.972 | 35024.972 | 2.628446 | 0.00030641 | 798.613 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 35024.97 | 35024.97 | 2.628446 | 16.70 | 12.79 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00773617 | 47.9463 | 21733.44 | 0.00 | 35213.39 | 35213.39 |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 14241.490 | -999.000 | 1.324618 | 0.00040730 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | 7/21 17:10:00 | 14241.49 | 13954.63 | 1.324618 | 21.71 | 15.22 | 0.00858877 | 12.80 | 11.72 | 0.00850000 | 28.16 | 0.01272245 | 20.56 | 0.0000 | 21.11 | 0.00858877 | 52.7977 | 12964.78 | 0.00 | 14862.57 | 14862.57 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 8506.800 | 8506.800 | 0.382720 | 0.00007442 | 243.063 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 8506.80 | 8506.80 | 0.382720 | 21.11 | 14.25 | 0.00775311 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.11 | 0.00775311 | 47.7250 | 8506.86 | 0.00 | 9170.50 | 9170.50 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 13580.466 | -999.000 | 1.261729 | 0.00038839 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | 7/21 17:20:00 | 13580.47 | 13294.59 | 1.261729 | 21.71 | 15.22 | 0.00859286 | 12.80 | 11.72 | 0.00850000 | 27.95 | 0.01272209 | 20.50 | 0.0000 | 21.11 | 0.00859286 | 52.8225 | 12349.24 | 0.00 | 14172.25 | 14172.25 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 8514.748 | 8514.748 | 0.383077 | 0.00007449 | 243.290 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 8514.75 | 8514.75 | 0.383077 | 21.11 | 14.25 | 0.00775335 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.11 | 0.00775335 | 47.7265 | 8514.81 | 0.00 | 9179.06 | 9179.06 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 88793.516 | -999.000 | 8.402788 | 0.00253944 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | unknown | 7/21 13:40:00 | 88793.52 | 88267.76 | 8.402788 | 21.71 | 15.16 | 0.00852572 | 12.80 | 11.72 | 0.00850000 | 29.89 | 0.01272550 | 21.07 | 0.0000 | 21.11 | 0.00852572 | 52.4139 | 82247.46 | 0.00 | 92701.17 | 92701.17 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 48441.178 | 48441.178 | 2.179419 | 0.00042378 | 1384.095 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 48441.18 | 48441.18 | 2.179419 | 21.11 | 14.27 | 0.00776966 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.11 | 0.00776966 | 47.8242 | 48441.36 | 0.00 | 52220.96 | 52220.96 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 70574.845 | -999.000 | 6.259418 | 0.00201839 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | unknown | 7/21 19:20:00 | 70574.85 | 66458.26 | 6.259418 | 21.71 | 15.37 | 0.00876747 | 12.80 | 11.72 | 0.00850000 | 24.81 | 0.01271660 | 19.55 | 0.0000 | 21.11 | 0.00876747 | 53.8817 | 61263.00 | 0.00 | 73582.97 | 71404.87 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 48604.008 | 48604.008 | 2.186745 | 0.00042521 | 1388.747 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 48604.01 | 48604.01 | 2.186745 | 21.11 | 14.27 | 0.00777035 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.11 | 0.00777035 | 47.8284 | 48604.19 | 0.00 | 52396.50 | 52396.50 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 13041.910 | -999.000 | 1.210211 | 0.00037299 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | unknown | 7/21 09:50:00 | 13041.91 | 12754.36 | 1.210211 | 21.71 | 15.22 | 0.00859735 | 12.80 | 11.72 | 0.00850000 | 25.04 | 0.01271700 | 19.62 | 0.0000 | 21.11 | 0.00859735 | 52.8498 | 11845.00 | 0.00 | 13609.74 | 13609.74 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 8523.481 | 8523.481 | 0.383470 | 0.00007457 | 243.540 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 8523.48 | 8523.48 | 0.383470 | 21.11 | 14.25 | 0.00775357 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.11 | 0.00775357 | 47.7279 | 8523.54 | 0.00 | 9188.48 | 9188.48 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 12421.362 | -999.000 | 1.151013 | 0.00035524 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | unknown | 7/21 09:10:00 | 12421.36 | 12133.31 | 1.151013 | 21.71 | 15.23 | 0.00860252 | 12.80 | 11.72 | 0.00850000 | 23.63 | 0.01271456 | 19.19 | 0.0000 | 21.11 | 0.00860252 | 52.8812 | 11265.59 | 0.00 | 12961.64 | 12961.64 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 8531.427 | 8531.427 | 0.383828 | 0.00007464 | 243.767 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 8531.43 | 8531.43 | 0.383828 | 21.11 | 14.25 | 0.00775382 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.11 | 0.00775382 | 47.7293 | 8531.49 | 0.00 | 9197.04 | 9197.04 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 17265.470 | 17265.470 | 0.843823 | 0.00015105 | 429.022 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 17265.47 | 17265.47 | 0.843823 | 16.70 | 12.79 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00780219 | 48.3497 | 12997.67 | 0.00 | 17354.63 | 17354.63 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 3701.905 | -999.000 | 0.344651 | 0.00010587 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | 7/21 17:00:00 | 3701.91 | 3630.26 | 0.344651 | 21.71 | 15.21 | 0.00858523 | 12.80 | 11.72 | 0.00850000 | 28.36 | 0.01272282 | 20.62 | 0.0000 | 21.11 | 0.00858523 | 52.7763 | 3373.30 | 0.00 | 3863.46 | 3863.46 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 2604.982 | 2604.982 | 0.117198 | 0.00002279 | 74.430 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 2604.98 | 2604.98 | 0.117198 | 21.11 | 14.29 | 0.00779722 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.11 | 0.00779722 | 47.9931 | 2604.99 | 0.00 | 2808.22 | 2808.22 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 3515.776 | -999.000 | 0.326927 | 0.00010055 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | 7/21 17:20:00 | 3515.78 | 3444.26 | 0.326927 | 21.71 | 15.22 | 0.00858966 | 12.80 | 11.72 | 0.00850000 | 27.95 | 0.01272209 | 20.50 | 0.0000 | 21.11 | 0.00858966 | 52.8032 | 3199.82 | 0.00 | 3669.07 | 3669.07 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 2605.229 | 2605.229 | 0.117209 | 0.00002279 | 74.437 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 2605.23 | 2605.23 | 0.117209 | 21.11 | 14.29 | 0.00779725 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.11 | 0.00779725 | 47.9933 | 2605.24 | 0.00 | 2808.49 | 2808.49 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 18336.009 | -999.000 | 1.686445 | 0.00052440 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | unknown | 7/21 13:40:00 | 18336.01 | 17799.41 | 1.686445 | 21.71 | 15.25 | 0.00863018 | 12.80 | 11.72 | 0.00850000 | 29.89 | 0.01272550 | 21.07 | 0.0000 | 21.11 | 0.00863018 | 53.0494 | 16505.84 | 0.00 | 19131.98 | 19131.98 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 12480.182 | 12480.182 | 0.561488 | 0.00010918 | 356.584 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 12480.18 | 12480.18 | 0.561488 | 21.11 | 14.30 | 0.00780490 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.11 | 0.00780490 | 48.0393 | 12480.22 | 0.00 | 13453.93 | 13453.93 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 14032.536 | 14032.536 | 1.098891 | 0.00012276 | 317.940 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 14032.54 | 14032.54 | 1.098891 | 16.70 | 12.79 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00784592 | 48.6179 | 8474.46 | 0.00 | 14108.20 | 14108.20 |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 14472.891 | 14472.891 | 1.151717 | 0.00012662 | 327.163 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 14472.89 | 14472.89 | 1.151717 | 16.70 | 12.79 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00784895 | 48.6364 | 8647.60 | 0.00 | 14550.99 | 14550.99 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 9542.331 | 9542.331 | 1.187128 | 0.00008348 | 205.273 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 9542.33 | 9542.33 | 1.187128 | 16.70 | 12.79 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00734586 | 45.5607 | 3546.07 | 0.00 | 9595.40 | 9595.40 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 10981.722 | 10981.722 | 0.411504 | 0.00009607 | 296.622 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 10981.72 | 10981.72 | 0.411504 | 16.70 | 12.79 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00787104 | 48.7712 | 8900.24 | 0.00 | 11036.32 | 11036.32 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 69550.086 | -999.000 | 2.051317 | 0.00198912 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 69550.09 | 44784.57 | 2.051317 | 30.10 | 21.13 | 0.01272586 | 11.90 | 11.35 | 0.00850000 | 30.10 | 0.01272586 | 21.13 | 99.9965 | 21.11 | 0.00863123 | 53.0546 | 198921.22 | 0.00 | 71135.90 | 45208.06 |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | FLR_3_DOAS | 35250.356 | 35250.356 | 0.615395 | 0.00030839 | 490.606 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 35250.36 | 35250.36 | 0.615395 | -32.70 | -32.70 | 0.00018338 | 16.70 | 12.79 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 333.3216 | 21.11 | 0.00777024 | 47.8278 | 148812.46 | 0.00 | 24421.86 | 24421.86 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 628300.659 | -999.000 | 23.388750 | 0.01796932 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 628300.66 | 443913.87 | 23.388750 | 27.04 | 19.09 | 0.01117217 | 10.91 | 10.91 | 0.00850000 | 30.10 | 0.01272586 | 21.13 | 49.8593 | 23.99 | 0.00958165 | 49.3642 | 308207.11 | 0.00 | 645498.37 | 441040.57 |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV WITH REHEAT | 401918.226 | 401918.226 | 7.016625 | 0.00351616 | 5593.801 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 401918.23 | 401918.23 | 7.016625 | -32.70 | -32.70 | 0.00018338 | 16.70 | 12.79 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 166.1976 | 21.00 | 0.00777926 | 48.2027 | 86045.49 | 0.00 | 278453.62 | 278453.62 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:24:43
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | Yes | Yes | No | 7836.558 | 7836.558 | 1.284284 | 0.00006856 | 165.183 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.40218202 | 54.44 | 82.22 | 27.78 | 746612.83 | 1.0496 | 1.070739 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 7836.56 | 7836.56 | 1.0000 | 1.48196693 | 1.284284 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.06855063 | 60.00 | 32.22 | 27.78 | 0.000 | 7836.56 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00793097 | 21.00 | 0.00793097 | 49.1373 | 1339.32 | 0.00 | 7880.43 | 7880.43 | 1.48196693 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.81 | 15.16 | 0.00800000 | 42252.3 | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4890.217 | 4890.217 | 0.223940 | 0.00004278 | 123.688 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.40218202 | 54.44 | 82.22 | 27.78 | 746612.83 | 0.6550 | 0.668169 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | Sensible | 4890.22 | 4890.22 | 1.0000 | 0.25840970 | 0.223940 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.04277738 | 60.00 | 32.22 | 27.78 | 0.000 | 4890.22 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00775772 | 21.00 | 0.00775772 | 48.0795 | 3757.86 | 0.00 | 4915.34 | 4915.34 | 0.25840970 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 35.25 | 19.74 | 0.00800000 | 55956.2 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1807.677 | 1807.677 | 0.118310 | 0.00001581 | 42.162 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.40218202 | 54.44 | 82.22 | 27.78 | 746612.83 | 0.2421 | 0.246990 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 1807.68 | 1807.68 | 1.0000 | 0.13652061 | 0.118310 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.01581273 | 60.00 | 32.22 | 27.78 | 0.000 | 1807.68 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00771121 | 21.00 | 0.00771121 | 47.7935 | 1209.43 | 0.00 | 1817.33 | 1817.33 | 0.13652061 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 29.65 | 17.92 | 0.00800000 | 50246.5 | |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2613.624 | 2613.624 | 0.095343 | 0.00002287 | 71.329 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.40218202 | 54.44 | 82.22 | 27.78 | 746612.83 | 0.3501 | 0.357109 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 2613.62 | 2613.62 | 1.0000 | 0.11001851 | 0.095343 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.02286279 | 60.00 | 32.22 | 27.78 | 0.000 | 2613.62 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00761756 | 21.00 | 0.00761756 | 47.2203 | 2131.60 | 0.00 | 2626.59 | 2626.59 | 0.11001851 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 40.01 | 21.19 | 0.00800000 | 60808.8 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1935.959 | 1935.959 | 0.070620 | 0.00001694 | 52.835 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.40218202 | 54.44 | 82.22 | 27.78 | 746612.83 | 0.2593 | 0.264517 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 1935.96 | 1935.96 | 1.0000 | 0.08149046 | 0.070620 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.01693488 | 60.00 | 32.22 | 27.78 | 0.000 | 1935.96 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00769886 | 21.00 | 0.00769886 | 47.7180 | 1578.87 | 0.00 | 1945.56 | 1945.56 | 0.08149046 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 40.01 | 21.19 | 0.00800000 | 60809.4 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11339.676 | 11339.676 | 1.681732 | 0.00009920 | 240.625 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.40218202 | 54.44 | 82.22 | 27.78 | 746612.83 | 1.5188 | 1.549383 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | Sensible | 11339.68 | 11339.68 | 1.0000 | 1.94059180 | 1.681732 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.09919431 | 60.00 | 32.22 | 27.78 | 0.000 | 11339.68 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00760831 | 21.00 | 0.00760831 | 47.1649 | 2838.44 | 0.00 | 11403.02 | 11403.02 | 1.94059180 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 22.36 | 15.36 | 0.00800000 | 42810.8 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14159.143 | 14159.143 | 0.896354 | 0.00012387 | 332.272 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.40218202 | 54.44 | 82.22 | 27.78 | 746612.83 | 1.8965 | 1.934617 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | Sensible | 14159.14 | 14159.14 | 1.0000 | 1.03432540 | 0.896354 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.12385772 | 60.00 | 32.22 | 27.78 | 0.000 | 14159.14 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00779003 | 21.00 | 0.00779003 | 48.2768 | 9626.30 | 0.00 | 14234.61 | 14234.61 | 1.03432540 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 30.10 | 18.07 | 0.00800000 | 50697.0 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 35024.972 | 35024.972 | 2.628446 | 0.00030641 | 798.613 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.40218202 | 54.44 | 82.22 | 27.78 | 746612.83 | 4.6912 | 4.785595 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 35024.97 | 35024.97 | 1.0000 | 3.03302973 | 2.628446 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.30638247 | 60.00 | 32.22 | 27.78 | 0.000 | 35024.97 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00773617 | 21.00 | 0.00773617 | 47.9463 | 21733.44 | 0.00 | 35213.39 | 35213.39 | 3.03302973 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 27.99 | 17.36 | 0.00800000 | 48544.7 | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14241.490 | -999.000 | 1.324618 | 0.00040730 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8061 | 1004.8586 | 1.1539 | ROOM_1_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.324618 | 1.52850951 | 4197.9300 | 999.8980 | 26.76828287 | 15.03 | 6.70 | 8.33 | 936053.58 | 1.5214 | 1.521411 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | unknown | unknown | 7/21 17:10:00 | Sensible | 14241.49 | 13954.63 | 1.0000 | 1.52850951 | 1.324618 | 21.71 | 15.22 | 0.00858877 | 43639.4 | 12.80 | 11.72 | 0.00850000 | 34322.2 | 0.40725567 | 6.70 | 15.03 | 8.33 | 0.000 | 14241.49 | 28.16 | 0.01272245 | 20.56 | 0.00000000 | 0.0000 | 21.11 | 0.00858877 | 21.11 | 0.00858877 | 52.7977 | 12964.78 | 0.00 | 14862.57 | 14862.57 | 1.52850951 | 21.71 | 15.64 | 0.00858877 | 43639.4 | 12.18 | 11.93 | 0.00858877 | 33915.9 | |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8506.800 | 8506.800 | 0.382720 | 0.00007442 | 243.063 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | ROOM_1_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.324618 | 1.52850951 | 4197.9300 | 999.8980 | 6.40218202 | 54.44 | 82.22 | 27.78 | 746612.83 | 1.1394 | 1.162316 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | Sensible | 8506.80 | 8506.80 | 1.0000 | 0.44162982 | 0.382720 | 21.11 | 14.25 | 0.00775311 | 40906.5 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.07441361 | 60.00 | 32.22 | 27.78 | 0.000 | 8506.80 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.11 | 0.00775311 | 21.11 | 0.00775311 | 47.7250 | 8506.86 | 0.00 | 9170.50 | 9170.50 | 0.44162982 | 16.60 | 12.91 | 0.00775311 | 36309.6 | 36.97 | 20.08 | 0.00775311 | 57074.8 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13580.466 | -999.000 | 1.261729 | 0.00038839 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8137 | 1004.8586 | 1.1539 | ROOM_2_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.261729 | 1.45594085 | 4197.9300 | 999.8980 | 26.76828287 | 15.03 | 6.70 | 8.33 | 936053.58 | 1.4508 | 1.450794 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | unknown | unknown | 7/21 17:20:00 | Sensible | 13580.47 | 13294.59 | 1.0000 | 1.45594085 | 1.261729 | 21.71 | 15.22 | 0.00859286 | 43649.8 | 12.80 | 11.72 | 0.00850000 | 34322.2 | 0.38835272 | 6.70 | 15.03 | 8.33 | 0.000 | 13580.47 | 27.95 | 0.01272209 | 20.50 | 0.00000000 | 0.0000 | 21.11 | 0.00859286 | 21.11 | 0.00859286 | 52.8225 | 12349.24 | 0.00 | 14172.25 | 14172.25 | 1.45594085 | 21.71 | 15.65 | 0.00859286 | 43649.8 | 12.17 | 11.93 | 0.00859286 | 33915.7 | |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8514.748 | 8514.748 | 0.383077 | 0.00007449 | 243.290 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | ROOM_2_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.261729 | 1.45594085 | 4197.9300 | 999.8980 | 6.40218202 | 54.44 | 82.22 | 27.78 | 746612.83 | 1.1405 | 1.163402 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | Sensible | 8514.75 | 8514.75 | 1.0000 | 0.44204244 | 0.383077 | 21.11 | 14.25 | 0.00775335 | 40907.2 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.07448313 | 60.00 | 32.22 | 27.78 | 0.000 | 8514.75 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.11 | 0.00775335 | 21.11 | 0.00775335 | 47.7265 | 8514.81 | 0.00 | 9179.06 | 9179.06 | 0.44204244 | 16.60 | 12.91 | 0.00775335 | 36310.3 | 36.97 | 20.08 | 0.00775335 | 57075.4 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 88793.516 | -999.000 | 8.402788 | 0.00253944 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6889 | 1004.8586 | 1.1539 | ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 8.402788 | 9.69618636 | 4197.9300 | 999.8980 | 26.76828287 | 15.03 | 6.70 | 8.33 | 936053.58 | 9.4859 | 9.485767 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | unknown | unknown | unknown | 7/21 13:40:00 | Sensible | 88793.52 | 88267.76 | 1.0000 | 9.69618636 | 8.402788 | 21.71 | 15.16 | 0.00852572 | 43479.8 | 12.80 | 11.72 | 0.00850000 | 34322.2 | 2.53917685 | 6.70 | 15.03 | 8.33 | 0.000 | 88793.52 | 29.89 | 0.01272550 | 21.07 | 0.00000000 | 0.0000 | 21.11 | 0.00852572 | 21.11 | 0.00852572 | 52.4139 | 82247.46 | 0.00 | 92701.17 | 92701.17 | 9.69618636 | 21.71 | 15.59 | 0.00852572 | 43479.8 | 12.34 | 11.94 | 0.00852572 | 33919.2 | |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 48441.178 | 48441.178 | 2.179419 | 0.00042378 | 1384.095 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 8.402788 | 9.69618636 | 4197.9300 | 999.8980 | 6.40218202 | 54.44 | 82.22 | 27.78 | 746612.83 | 6.4881 | 6.618702 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | Sensible | 48441.18 | 48441.18 | 1.0000 | 2.51488612 | 2.179419 | 21.11 | 14.27 | 0.00776966 | 40949.1 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.42374133 | 60.00 | 32.22 | 27.78 | 0.000 | 48441.18 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.11 | 0.00776966 | 21.11 | 0.00776966 | 47.8242 | 48441.36 | 0.00 | 52220.96 | 52220.96 | 2.51488612 | 16.60 | 12.93 | 0.00776966 | 36351.6 | 36.97 | 20.10 | 0.00776966 | 57116.3 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 70574.845 | -999.000 | 6.259418 | 0.00201839 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1383 | 1004.8586 | 1.1539 | ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 6.259418 | 7.22289815 | 4197.9300 | 999.8980 | 26.76828287 | 15.03 | 6.70 | 8.33 | 936053.58 | 7.5396 | 7.539475 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | unknown | unknown | unknown | 7/21 19:20:00 | Sensible | 70574.85 | 66458.26 | 1.0000 | 7.22289815 | 6.259418 | 21.71 | 15.37 | 0.00876747 | 44093.2 | 12.80 | 11.72 | 0.00850000 | 34322.2 | 2.01818805 | 6.70 | 15.03 | 8.33 | 0.000 | 70574.85 | 24.81 | 0.01271660 | 19.55 | 0.00000000 | 0.0000 | 21.11 | 0.00876747 | 21.11 | 0.00876747 | 53.8817 | 61263.00 | 0.00 | 73582.97 | 71404.87 | 7.22289815 | 21.71 | 15.80 | 0.00876747 | 44093.2 | 12.03 | 11.93 | 0.00864796 | 33905.7 | |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 48604.008 | 48604.008 | 2.186745 | 0.00042521 | 1388.747 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 6.259418 | 7.22289815 | 4197.9300 | 999.8980 | 6.40218202 | 54.44 | 82.22 | 27.78 | 746612.83 | 6.5099 | 6.640950 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | Sensible | 48604.01 | 48604.01 | 1.0000 | 2.52333963 | 2.186745 | 21.11 | 14.27 | 0.00777035 | 40950.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.42516569 | 60.00 | 32.22 | 27.78 | 0.000 | 48604.01 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.11 | 0.00777035 | 21.11 | 0.00777035 | 47.8284 | 48604.19 | 0.00 | 52396.50 | 52396.50 | 2.52333963 | 16.60 | 12.93 | 0.00777035 | 36353.3 | 36.97 | 20.10 | 0.00777035 | 57118.0 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13041.910 | -999.000 | 1.210211 | 0.00037299 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8221 | 1004.8586 | 1.1539 | ROOM_5_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.210211 | 1.39649308 | 4197.9300 | 999.8980 | 26.76828287 | 15.03 | 6.70 | 8.33 | 936053.58 | 1.3933 | 1.393261 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | unknown | unknown | unknown | 7/21 09:50:00 | Sensible | 13041.91 | 12754.36 | 1.0000 | 1.39649308 | 1.210211 | 21.71 | 15.22 | 0.00859735 | 43661.2 | 12.80 | 11.72 | 0.00850000 | 34322.2 | 0.37295197 | 6.70 | 15.03 | 8.33 | 0.000 | 13041.91 | 25.04 | 0.01271700 | 19.62 | 0.00000000 | 0.0000 | 21.11 | 0.00859735 | 21.11 | 0.00859735 | 52.8498 | 11845.00 | 0.00 | 13609.74 | 13609.74 | 1.39649308 | 21.71 | 15.65 | 0.00859735 | 43661.2 | 12.16 | 11.93 | 0.00859735 | 33915.6 | |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8523.481 | 8523.481 | 0.383470 | 0.00007457 | 243.540 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | ROOM_5_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.210211 | 1.39649308 | 4197.9300 | 999.8980 | 6.40218202 | 54.44 | 82.22 | 27.78 | 746612.83 | 1.1416 | 1.164595 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | Sensible | 8523.48 | 8523.48 | 1.0000 | 0.44249580 | 0.383470 | 21.11 | 14.25 | 0.00775357 | 40907.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.07455952 | 60.00 | 32.22 | 27.78 | 0.000 | 8523.48 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.11 | 0.00775357 | 21.11 | 0.00775357 | 47.7279 | 8523.54 | 0.00 | 9188.48 | 9188.48 | 0.44249580 | 16.60 | 12.91 | 0.00775357 | 36310.8 | 36.97 | 20.08 | 0.00775357 | 57076.0 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12421.362 | -999.000 | 1.151013 | 0.00035524 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8316 | 1004.8586 | 1.1539 | ROOM_6_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.151013 | 1.32818235 | 4197.9300 | 999.8980 | 26.76828287 | 15.03 | 6.70 | 8.33 | 936053.58 | 1.3270 | 1.326968 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | unknown | unknown | unknown | 7/21 09:10:00 | Sensible | 12421.36 | 12133.31 | 1.0000 | 1.32818235 | 1.151013 | 21.71 | 15.23 | 0.00860252 | 43674.3 | 12.80 | 11.72 | 0.00850000 | 34322.2 | 0.35520649 | 6.70 | 15.03 | 8.33 | 0.000 | 12421.36 | 23.63 | 0.01271456 | 19.19 | 0.00000000 | 0.0000 | 21.11 | 0.00860252 | 21.11 | 0.00860252 | 52.8812 | 11265.59 | 0.00 | 12961.64 | 12961.64 | 1.32818235 | 21.71 | 15.65 | 0.00860252 | 43674.3 | 12.15 | 11.93 | 0.00860252 | 33915.4 | |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8531.427 | 8531.427 | 0.383828 | 0.00007464 | 243.767 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | ROOM_6_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.151013 | 1.32818235 | 4197.9300 | 999.8980 | 6.40218202 | 54.44 | 82.22 | 27.78 | 746612.83 | 1.1427 | 1.165681 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | Sensible | 8531.43 | 8531.43 | 1.0000 | 0.44290834 | 0.383828 | 21.11 | 14.25 | 0.00775382 | 40908.3 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.07462903 | 60.00 | 32.22 | 27.78 | 0.000 | 8531.43 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.11 | 0.00775382 | 21.11 | 0.00775382 | 47.7293 | 8531.49 | 0.00 | 9197.04 | 9197.04 | 0.44290834 | 16.60 | 12.91 | 0.00775382 | 36311.4 | 36.97 | 20.09 | 0.00775382 | 57076.6 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 17265.470 | 17265.470 | 0.843823 | 0.00015105 | 429.022 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.40218202 | 54.44 | 82.22 | 27.78 | 746612.83 | 2.3125 | 2.359047 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | Sensible | 17265.47 | 17265.47 | 1.0000 | 0.97370785 | 0.843823 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.15103046 | 60.00 | 32.22 | 27.78 | 0.000 | 17265.47 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00780219 | 21.00 | 0.00780219 | 48.3497 | 12997.67 | 0.00 | 17354.63 | 17354.63 | 0.97370785 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 34.08 | 19.37 | 0.00800000 | 54758.0 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3701.905 | -999.000 | 0.344651 | 0.00010587 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7995 | 1004.8586 | 1.1539 | ROOM_1_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.344651 | 0.39770149 | 4197.9300 | 999.8980 | 26.76828287 | 15.03 | 6.70 | 8.33 | 936053.58 | 0.3955 | 0.395473 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | unknown | unknown | 7/21 17:00:00 | Sensible | 3701.91 | 3630.26 | 1.0000 | 0.39770149 | 0.344651 | 21.71 | 15.21 | 0.00858523 | 43630.4 | 12.80 | 11.72 | 0.00850000 | 34322.2 | 0.10586125 | 6.70 | 15.03 | 8.33 | 0.000 | 3701.91 | 28.36 | 0.01272282 | 20.62 | 0.00000000 | 0.0000 | 21.11 | 0.00858523 | 21.11 | 0.00858523 | 52.7763 | 3373.30 | 0.00 | 3863.46 | 3863.46 | 0.39770149 | 21.71 | 15.64 | 0.00858523 | 43630.4 | 12.19 | 11.93 | 0.00858523 | 33916.0 | |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2604.982 | 2604.982 | 0.117198 | 0.00002279 | 74.430 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | ROOM_1_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.344651 | 0.39770149 | 4197.9300 | 999.8980 | 6.40218202 | 54.44 | 82.22 | 27.78 | 746612.83 | 0.3489 | 0.355929 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 2604.98 | 2604.98 | 1.0000 | 0.13523776 | 0.117198 | 21.11 | 14.29 | 0.00779722 | 41018.6 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.02278719 | 60.00 | 32.22 | 27.78 | 0.000 | 2604.98 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.11 | 0.00779722 | 21.11 | 0.00779722 | 47.9931 | 2604.99 | 0.00 | 2808.22 | 2808.22 | 0.13523776 | 16.60 | 12.95 | 0.00779722 | 36421.3 | 36.97 | 20.12 | 0.00779722 | 57186.4 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3515.776 | -999.000 | 0.326927 | 0.00010055 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8077 | 1004.8586 | 1.1539 | ROOM_2_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.326927 | 0.37724920 | 4197.9300 | 999.8980 | 26.76828287 | 15.03 | 6.70 | 8.33 | 936053.58 | 0.3756 | 0.375589 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | unknown | unknown | 7/21 17:20:00 | Sensible | 3515.78 | 3444.26 | 1.0000 | 0.37724920 | 0.326927 | 21.71 | 15.22 | 0.00858966 | 43641.7 | 12.80 | 11.72 | 0.00850000 | 34322.2 | 0.10053862 | 6.70 | 15.03 | 8.33 | 0.000 | 3515.78 | 27.95 | 0.01272209 | 20.50 | 0.00000000 | 0.0000 | 21.11 | 0.00858966 | 21.11 | 0.00858966 | 52.8032 | 3199.82 | 0.00 | 3669.07 | 3669.07 | 0.37724920 | 21.71 | 15.64 | 0.00858966 | 43641.7 | 12.18 | 11.93 | 0.00858966 | 33915.8 | |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2605.229 | 2605.229 | 0.117209 | 0.00002279 | 74.437 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | ROOM_2_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.326927 | 0.37724920 | 4197.9300 | 999.8980 | 6.40218202 | 54.44 | 82.22 | 27.78 | 746612.83 | 0.3489 | 0.355962 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 2605.23 | 2605.23 | 1.0000 | 0.13525060 | 0.117209 | 21.11 | 14.29 | 0.00779725 | 41018.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.02278936 | 60.00 | 32.22 | 27.78 | 0.000 | 2605.23 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.11 | 0.00779725 | 21.11 | 0.00779725 | 47.9933 | 2605.24 | 0.00 | 2808.49 | 2808.49 | 0.13525060 | 16.60 | 12.95 | 0.00779725 | 36421.4 | 36.97 | 20.12 | 0.00779725 | 57186.5 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 18336.009 | -999.000 | 1.686445 | 0.00052440 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8831 | 1004.8586 | 1.1539 | ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 1.686445 | 1.94603054 | 4197.9300 | 999.8980 | 26.76828287 | 15.03 | 6.70 | 8.33 | 936053.58 | 1.9589 | 1.958827 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | unknown | unknown | unknown | 7/21 13:40:00 | Sensible | 18336.01 | 17799.41 | 1.0000 | 1.94603054 | 1.686445 | 21.71 | 15.25 | 0.00863018 | 43744.5 | 12.80 | 11.72 | 0.00850000 | 34322.2 | 0.52434425 | 6.70 | 15.03 | 8.33 | 0.000 | 18336.01 | 29.89 | 0.01272550 | 21.07 | 0.00000000 | 0.0000 | 21.11 | 0.00863018 | 21.11 | 0.00863018 | 53.0494 | 16505.84 | 0.00 | 19131.98 | 19131.98 | 1.94603054 | 21.71 | 15.68 | 0.00863018 | 43744.5 | 12.08 | 11.93 | 0.00863018 | 33913.2 | |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12480.182 | 12480.182 | 0.561488 | 0.00010918 | 356.584 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 1.686445 | 1.94603054 | 4197.9300 | 999.8980 | 6.40218202 | 54.44 | 82.22 | 27.78 | 746612.83 | 1.6716 | 1.705214 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 12480.18 | 12480.18 | 1.0000 | 0.64791507 | 0.561488 | 21.11 | 14.30 | 0.00780490 | 41038.3 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.10917093 | 60.00 | 32.22 | 27.78 | 0.000 | 12480.18 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.11 | 0.00780490 | 21.11 | 0.00780490 | 48.0393 | 12480.22 | 0.00 | 13453.93 | 13453.93 | 0.64791507 | 16.60 | 12.96 | 0.00780490 | 36440.8 | 36.97 | 20.12 | 0.00780490 | 57205.7 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14032.536 | 14032.536 | 1.098891 | 0.00012276 | 317.940 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.40218202 | 54.44 | 82.22 | 27.78 | 746612.83 | 1.8795 | 1.917319 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | Sensible | 14032.54 | 14032.54 | 1.0000 | 1.26803817 | 1.098891 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.12275023 | 60.00 | 32.22 | 27.78 | 0.000 | 14032.54 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00784592 | 21.00 | 0.00784592 | 48.6179 | 8474.46 | 0.00 | 14108.20 | 14108.20 | 1.26803817 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 27.51 | 17.19 | 0.00800000 | 48060.7 | |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14472.891 | 14472.891 | 1.151717 | 0.00012662 | 327.163 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.40218202 | 54.44 | 82.22 | 27.78 | 746612.83 | 1.9385 | 1.977486 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | Sensible | 14472.89 | 14472.89 | 1.0000 | 1.32899444 | 1.151717 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.12660225 | 60.00 | 32.22 | 27.78 | 0.000 | 14472.89 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00784895 | 21.00 | 0.00784895 | 48.6364 | 8647.60 | 0.00 | 14550.99 | 14550.99 | 1.32899444 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 27.34 | 17.13 | 0.00800000 | 47883.6 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9542.331 | 9542.331 | 1.187128 | 0.00008348 | 205.273 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.40218202 | 54.44 | 82.22 | 27.78 | 746612.83 | 1.2781 | 1.303805 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | Sensible | 9542.33 | 9542.33 | 1.0000 | 1.36985634 | 1.187128 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.08347195 | 60.00 | 32.22 | 27.78 | 0.000 | 9542.33 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.72 | 0.00734586 | 21.00 | 0.00734586 | 45.5607 | 3546.07 | 0.00 | 9595.40 | 9595.40 | 1.36985634 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 23.47 | 15.76 | 0.00800000 | 43939.4 | |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10981.722 | 10981.722 | 0.411504 | 0.00009607 | 296.622 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.40218202 | 54.44 | 82.22 | 27.78 | 746612.83 | 1.4709 | 1.500474 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | Sensible | 10981.72 | 10981.72 | 1.0000 | 0.47484467 | 0.411504 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.09606309 | 60.00 | 32.22 | 27.78 | 0.000 | 10981.72 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00787104 | 21.00 | 0.00787104 | 48.7712 | 8900.24 | 0.00 | 11036.32 | 11036.32 | 0.47484467 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 39.39 | 21.00 | 0.00800000 | 60176.7 | |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 69550.086 | -999.000 | 2.051317 | 0.00198912 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1028.4967 | 1004.8586 | 1.1539 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.36698273 | 4197.9300 | 999.8980 | 26.76828287 | 15.03 | 6.70 | 8.33 | 936053.58 | 7.4301 | 7.430139 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | Sensible | 69550.09 | 44784.57 | 1.0000 | 2.36706595 | 2.051317 | 30.10 | 21.13 | 0.01272586 | 62784.4 | 11.90 | 11.35 | 0.00850000 | 33402.0 | 1.98892074 | 6.70 | 15.03 | 8.33 | 2195.006 | 67355.08 | 30.10 | 0.01272586 | 21.13 | 2.05124512 | 99.9965 | 21.11 | 0.00862951 | 21.11 | 0.00863123 | 53.0546 | 198921.22 | 0.00 | 71135.90 | 45208.06 | 2.36706595 | 30.10 | 21.63 | 0.01272586 | 62784.4 | 11.53 | 11.45 | 0.00838330 | 32732.0 | |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 35250.356 | 35250.356 | 0.615395 | 0.00030839 | 490.606 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.36698273 | 4197.9300 | 999.8980 | 6.40218202 | 54.44 | 82.22 | 27.78 | 746612.83 | 4.7214 | 4.816390 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 35250.36 | 35250.36 | 1.0000 | 0.71011979 | 0.615395 | -32.70 | -32.70 | 0.00018338 | -32410.8 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 0.30835404 | 60.00 | 32.22 | 27.78 | 0.000 | 35250.36 | -32.70 | 0.00018338 | -32.70 | 2.05124512 | 333.3216 | 21.11 | 0.00777010 | 21.11 | 0.00777024 | 47.8278 | 148812.46 | 0.00 | 24421.86 | 24421.86 | 0.71011979 | 2.80 | -4.17 | 0.00018338 | 3273.1 | 37.01 | 13.61 | 0.00018338 | 37664.3 | |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 628300.659 | -999.000 | 23.388750 | 0.01796932 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.6085 | 1004.8586 | 1.1539 | VAV WITH REHEAT FAN | Fan:VariableVolume | 23.388750 | 26.98886047 | 4197.9300 | 999.8980 | 26.76828287 | 15.03 | 6.70 | 8.33 | 936053.58 | 67.1223 | 67.122297 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | Sensible | 628300.66 | 443913.87 | 1.0000 | 26.98886047 | 23.388750 | 27.04 | 19.09 | 0.01117217 | 55669.8 | 10.91 | 10.91 | 0.00850000 | 32389.8 | 17.96748625 | 6.70 | 15.03 | 8.33 | 52405.737 | 575894.92 | 30.10 | 0.01272586 | 21.13 | 11.66146000 | 49.8593 | 23.99 | 0.00962655 | 23.99 | 0.00958165 | 49.3642 | 308207.11 | 0.00 | 645498.37 | 441040.57 | 26.98886047 | 27.04 | 19.57 | 0.01117217 | 55669.8 | 11.10 | 11.05 | 0.00816785 | 31752.6 | |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 401918.226 | 401918.226 | 7.016625 | 0.00351616 | 5593.801 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | VAV WITH REHEAT FAN | Fan:VariableVolume | 23.388750 | 26.98886047 | 4197.9300 | 999.8980 | 6.40218202 | 54.44 | 82.22 | 27.78 | 746612.83 | 53.8322 | 54.915610 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | Sensible | 401918.23 | 401918.23 | 1.0000 | 8.09665814 | 7.016625 | -32.70 | -32.70 | 0.00018338 | -32410.8 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 3.51579729 | 60.00 | 32.22 | 27.78 | 0.000 | 401918.23 | -32.70 | 0.00018338 | -32.70 | 11.66146000 | 166.1976 | 20.99 | 0.00777852 | 21.00 | 0.00777926 | 48.2027 | 86045.49 | 0.00 | 278453.62 | 278453.62 | 8.09665814 | 2.80 | -4.17 | 0.00018338 | 3273.1 | 37.01 | 13.61 | 0.00018338 | 37664.3 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:43
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - | |||
VAV WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 23.39 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | VAV WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000610 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LAUNDRY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CAFE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001448 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_3 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
KITCHEN_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003556 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 1014.33 | 6943.67 | 597.50 |
RETAIL_1_FLR_1 | 3523.00 | 7576.67 | 2738.67 |
RETAIL_2_FLR_1 | 2179.83 | 7219.50 | 1467.83 |
MECH_FLR_1 | 2852.33 | 7820.33 | 2568.83 |
STORAGE_FLR_1 | 3001.50 | 8296.83 | 2923.33 |
LAUNDRY_FLR_1 | 6666.33 | 3596.50 | 2637.33 |
CAFE_FLR_1 | 3519.50 | 6491.50 | 1966.83 |
LOBBY_FLR_1 | 2540.50 | 6351.17 | 1247.50 |
ROOM_1_FLR_3 | 3333.17 | 8268.17 | 3205.33 |
ROOM_2_FLR_3 | 4238.83 | 8074.83 | 3891.67 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 2952.00 | 8640.50 | 2926.50 |
ROOM_5_FLR_3 | 3212.33 | 8180.50 | 3144.17 |
ROOM_6_FLR_3 | 4007.67 | 7945.17 | 3699.83 |
CORRIDOR_FLR_3 | 2767.67 | 8349.50 | 2696.00 |
ROOM_1_FLR_6 | 3816.50 | 8199.67 | 3634.00 |
ROOM_2_FLR_6 | 4706.00 | 8060.67 | 4362.33 |
ROOM_3_MULT9_FLR_6 | 2762.83 | 8142.83 | 2597.33 |
BANQUET_FLR_6 | 3667.00 | 4259.67 | 963.67 |
DINING_FLR_6 | 4127.33 | 3302.83 | 812.83 |
KITCHEN_FLR_6 | 7940.83 | 6253.50 | 5818.00 |
CORRIDOR_FLR_6 | 3066.33 | 7676.17 | 2549.00 |
Facility | 8757.33 | 8760.00 | 7907.17 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 207.83 | 0.00 | 207.83 | 0.00 |
RETAIL_1_FLR_1 | 397.17 | 0.00 | 397.17 | 0.00 |
RETAIL_2_FLR_1 | 355.67 | 0.00 | 355.67 | 0.00 |
MECH_FLR_1 | 378.17 | 0.00 | 378.17 | 0.00 |
STORAGE_FLR_1 | 492.67 | 0.00 | 492.67 | 0.00 |
LAUNDRY_FLR_1 | 228.33 | 0.00 | 228.33 | 0.00 |
CAFE_FLR_1 | 345.17 | 0.00 | 345.17 | 0.00 |
LOBBY_FLR_1 | 316.17 | 0.00 | 316.17 | 0.00 |
ROOM_1_FLR_3 | 8.67 | 4.67 | 8.67 | 4.67 |
ROOM_2_FLR_3 | 34.50 | 9.17 | 34.50 | 9.17 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 115.33 | 19.67 | 115.33 | 19.67 |
ROOM_5_FLR_3 | 11.00 | 0.50 | 11.00 | 0.50 |
ROOM_6_FLR_3 | 44.83 | 15.67 | 44.83 | 15.67 |
CORRIDOR_FLR_3 | 391.00 | 0.00 | 391.00 | 0.00 |
ROOM_1_FLR_6 | 9.67 | 7.17 | 9.67 | 7.17 |
ROOM_2_FLR_6 | 44.17 | 15.50 | 44.17 | 15.50 |
ROOM_3_MULT9_FLR_6 | 1.33 | 2.67 | 1.33 | 2.67 |
BANQUET_FLR_6 | 116.33 | 0.00 | 116.33 | 0.00 |
DINING_FLR_6 | 103.67 | 0.00 | 103.67 | 0.00 |
KITCHEN_FLR_6 | 143.33 | 0.00 | 143.33 | 0.00 |
CORRIDOR_FLR_6 | 404.17 | 0.00 | 404.17 | 0.00 |
Facility | 551.33 | 45.50 | 551.33 | 45.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:43
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.80 | 106.50 | 4826.41 | 1.003 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 3.130 | 0.064 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.28 | 12.54 | 307.76 | 1.423 | 0.021 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.508 | 0.024 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.525 | 0.024 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 23.477 | 0.069 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.58 | 142.30 | 748.35 | 4.458 | 0.050 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.14 | 422.44 | 5183.56 | 1.893 | 0.021 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.355 | 0.083 | 0.000 | 0.041 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.355 | 0.083 | 0.000 | 0.030 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.403 | 0.037 | 0.000 | 0.068 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.355 | 0.083 | 0.000 | 0.041 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.355 | 0.083 | 0.000 | 0.041 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 0.649 | 0.010 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.355 | 0.083 | 0.000 | 0.048 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.355 | 0.083 | 0.000 | 0.032 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.403 | 0.068 | 0.000 | 0.076 |
BANQUET_FLR_6 | 145.01 | 249.90 | 1010.89 | 4.748 | 0.024 | 0.000 | 0.000 |
DINING_FLR_6 | 145.01 | 249.90 | 1010.89 | 5.145 | 0.024 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 22.348 | 0.069 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 1.199 | 0.017 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.80 | 106.50 | 4826.41 | 0.637 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 2.020 | 0.001 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.28 | 12.54 | 307.76 | 1.340 | 0.000 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.487 | 0.000 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.472 | 0.000 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 18.416 | 0.001 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.58 | 142.30 | 748.35 | 3.047 | 0.001 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.14 | 422.44 | 5183.56 | 1.543 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 0.500 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.000 | 0.001 | 0.000 | 0.000 |
BANQUET_FLR_6 | 145.01 | 249.90 | 1010.89 | 3.790 | 0.000 | 0.000 | 0.000 |
DINING_FLR_6 | 145.01 | 249.90 | 1010.89 | 3.973 | 0.000 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 12.949 | 0.001 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 1.013 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:24:43
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | VAV WITH REHEAT | 61.80 | 106.50 | 4826.41 | 1978.83 | 0.0000 | 0.854 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 6.28 | 10.83 | 265.76 | 67.07 | 0.0000 | 0.079 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 7.28 | 12.54 | 307.76 | 77.67 | 0.0000 | 0.092 |
MECH_FLR_1 | VAV WITH REHEAT | 1.54 | 2.65 | 650.80 | 164.24 | 0.0000 | 0.000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 1.18 | 2.04 | 375.47 | 94.76 | 0.0000 | 0.058 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 4.87 | 8.40 | 309.22 | 78.04 | 0.0000 | 0.000 |
CAFE_FLR_1 | VAV WITH REHEAT | 82.58 | 142.30 | 748.35 | 188.86 | 0.0000 | 0.676 |
LOBBY_FLR_1 | VAV WITH REHEAT | 245.14 | 422.44 | 5183.56 | 1308.19 | 0.0000 | 1.894 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 1.50 | 74.75 | 24.52 | 0.0000 | 0.837 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.837 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 12.16 | 20.96 | 1186.91 | 389.40 | 0.0000 | 0.475 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.015 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.015 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.099 |
BANQUET_FLR_6 | VAV WITH REHEAT | 145.01 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
DINING_FLR_6 | VAV WITH REHEAT | 145.01 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 12.90 | 22.24 | 314.87 | 103.30 | 0.0000 | 0.367 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 12.87 | 22.18 | 1256.16 | 412.12 | 0.0000 | 0.126 |
Total Facility | 873.39 | 1604.23 | 35184.81 | 11345.29 | 0.0000 | 137.584 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 41671980.44 | 0.00 | 41671980.44 | 0.00 | 41671980.44 | 26946214.98 | 0.33 | 0.33 | 8759.33 | 0.00 |
RETAIL_1_FLR_1 | 7202481.35 | 0.00 | 7202481.35 | 147042.48 | 7349523.82 | 2498216.28 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_2_FLR_1 | 3778386.03 | 0.00 | 3778386.03 | 56758.58 | 3835144.62 | 2892943.94 | 0.00 | 0.00 | 8760.00 | 0.00 |
MECH_FLR_1 | 2856375.52 | 0.00 | 2856375.52 | 134143.57 | 2990519.09 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
STORAGE_FLR_1 | 1706334.63 | 0.00 | 1706334.63 | 77393.45 | 1783728.08 | 1821682.01 | 8756.50 | 1.00 | 2.50 | 0.00 |
LAUNDRY_FLR_1 | 62562988.55 | 0.00 | 62562988.55 | 183166.19 | 62746154.74 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
CAFE_FLR_1 | 28771487.42 | 0.00 | 28771487.42 | 325045.72 | 29096533.14 | 21330615.53 | 1.50 | 0.17 | 8758.33 | 0.00 |
LOBBY_FLR_1 | 84498896.93 | 0.00 | 84498896.93 | 928729.87 | 85427626.80 | 59728886.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
ROOM_1_FLR_3 | 1460156.71 | 41812.29 | 1501969.00 | 85348.37 | 1587317.37 | 1946875.62 | 2190.00 | 6051.00 | 519.00 | 0.00 |
ROOM_2_FLR_3 | 1459985.63 | 30717.94 | 1490703.58 | 85341.86 | 1576045.43 | 1946647.51 | 2190.00 | 6208.37 | 361.63 | 0.00 |
ROOM_3_MULT19_FLR_3 | 1099911.97 | 157.43 | 1100069.40 | 23813.15 | 1123882.55 | 26397887.27 | 8395.00 | 365.00 | 0.00 | 367.17 |
ROOM_4_MULT19_FLR_3 | 19803829.30 | 43515.96 | 19847345.25 | 23819.66 | 19871164.92 | 26405105.73 | 2190.00 | 6064.21 | 505.79 | 0.00 |
ROOM_5_FLR_3 | 1460156.71 | 41883.98 | 1502040.70 | 85348.37 | 1587389.07 | 1946875.62 | 2190.00 | 6051.00 | 519.00 | 0.00 |
ROOM_6_FLR_3 | 1459985.63 | 42125.08 | 1502110.71 | 85341.86 | 1587452.57 | 1946647.51 | 2190.00 | 6068.54 | 501.46 | 0.00 |
CORRIDOR_FLR_3 | 26621504.58 | 0.00 | 26621504.58 | 103203.35 | 26724707.93 | 14972100.18 | 0.00 | 0.00 | 8760.00 | 0.00 |
ROOM_1_FLR_6 | 365039.18 | 49223.02 | 414262.20 | 85366.84 | 499629.03 | 486718.90 | 2061.14 | 6050.95 | 647.90 | 0.00 |
ROOM_2_FLR_6 | 364996.41 | 32698.70 | 397695.10 | 85360.32 | 483055.43 | 486661.88 | 2104.88 | 6231.88 | 423.24 | 0.00 |
ROOM_3_MULT9_FLR_6 | 2345190.31 | 49183.87 | 2394374.18 | 43676.66 | 2438050.84 | 3126920.42 | 2190.00 | 6050.33 | 519.67 | 0.00 |
BANQUET_FLR_6 | 41149772.38 | 0.00 | 41149772.38 | 208444.36 | 41358216.74 | 37458366.31 | 4358.36 | 167.92 | 4233.72 | 0.00 |
DINING_FLR_6 | 44576271.45 | 0.00 | 44576271.45 | 208444.36 | 44784715.81 | 37458366.31 | 3087.06 | 182.61 | 5490.33 | 0.00 |
KITCHEN_FLR_6 | 60343885.36 | 0.00 | 60343885.36 | 186606.03 | 60530491.39 | 11584760.86 | 0.00 | 0.00 | 8760.00 | 0.00 |
CORRIDOR_FLR_6 | 13020468.02 | 0.00 | 13020468.02 | 182639.57 | 13203107.59 | 3961413.96 | 0.00 | 0.00 | 8760.00 | 0.00 |
Total Facility | 0.21E+10 | 4469911.17 | 0.21E+10 | 8600660.63 | 0.21E+10 | 0.43E+10 | 8760.00 | 6726.19 | 8760.00 | 367.17 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 1.3214 | 0.0000 | 1.3214 | 0.0000 | 1.3214 | 0.8545 | 0.33 | 0.33 | 8759.33 |
RETAIL_1_FLR_1 | 0.2284 | 0.0000 | 0.2284 | 0.0047 | 0.2331 | 0.0792 | 0.00 | 0.00 | 8760.00 |
RETAIL_2_FLR_1 | 0.1198 | 0.0000 | 0.1198 | 0.0018 | 0.1216 | 0.0917 | 0.00 | 0.00 | 8760.00 |
MECH_FLR_1 | 0.0906 | 0.0000 | 0.0906 | 0.0043 | 0.0948 | 0.0000 | 0.00 | 0.00 | 8760.00 |
STORAGE_FLR_1 | 0.0541 | 0.0000 | 0.0541 | 0.0025 | 0.0566 | 0.0578 | 8756.50 | 1.00 | 2.50 |
LAUNDRY_FLR_1 | 1.9839 | 0.0000 | 1.9839 | 0.0058 | 1.9897 | 0.0000 | 0.00 | 0.00 | 8760.00 |
CAFE_FLR_1 | 0.9123 | 0.0000 | 0.9123 | 0.0103 | 0.9226 | 0.6764 | 1.50 | 0.17 | 8758.33 |
LOBBY_FLR_1 | 2.6794 | 0.0000 | 2.6794 | 0.0294 | 2.7089 | 1.8940 | 0.00 | 0.00 | 8760.00 |
ROOM_1_FLR_3 | 0.0463 | 0.0013 | 0.0476 | 0.0027 | 0.0503 | 0.0617 | 2190.00 | 6051.00 | 519.00 |
ROOM_2_FLR_3 | 0.0463 | 0.0010 | 0.0473 | 0.0027 | 0.0500 | 0.0617 | 2190.00 | 6208.37 | 361.63 |
ROOM_4_MULT19_FLR_3 | 0.6280 | 0.0014 | 0.6294 | 0.0008 | 0.6301 | 0.8373 | 2190.00 | 6064.21 | 505.79 |
ROOM_5_FLR_3 | 0.0463 | 0.0013 | 0.0476 | 0.0027 | 0.0503 | 0.0617 | 2190.00 | 6051.00 | 519.00 |
ROOM_6_FLR_3 | 0.0463 | 0.0013 | 0.0476 | 0.0027 | 0.0503 | 0.0617 | 2190.00 | 6068.54 | 501.46 |
CORRIDOR_FLR_3 | 0.8442 | 0.0000 | 0.8442 | 0.0033 | 0.8474 | 0.4748 | 0.00 | 0.00 | 8760.00 |
ROOM_1_FLR_6 | 0.0116 | 0.0016 | 0.0131 | 0.0027 | 0.0158 | 0.0154 | 2061.14 | 6050.95 | 647.90 |
ROOM_2_FLR_6 | 0.0116 | 0.0010 | 0.0126 | 0.0027 | 0.0153 | 0.0154 | 2104.88 | 6231.88 | 423.24 |
ROOM_3_MULT9_FLR_6 | 0.0744 | 0.0016 | 0.0759 | 0.0014 | 0.0773 | 0.0992 | 2190.00 | 6050.33 | 519.67 |
BANQUET_FLR_6 | 1.3049 | 0.0000 | 1.3049 | 0.0066 | 1.3115 | 1.1878 | 4358.36 | 167.92 | 4233.72 |
DINING_FLR_6 | 1.4135 | 0.0000 | 1.4135 | 0.0066 | 1.4201 | 1.1878 | 3087.06 | 182.61 | 5490.33 |
KITCHEN_FLR_6 | 1.9135 | 0.0000 | 1.9135 | 0.0059 | 1.9194 | 0.3674 | 0.00 | 0.00 | 8760.00 |
CORRIDOR_FLR_6 | 0.4129 | 0.0000 | 0.4129 | 0.0058 | 0.4187 | 0.1256 | 0.00 | 0.00 | 8760.00 |
Total Facility | 64.9706 | 0.1414 | 65.1120 | 0.2153 | 65.3273 | 73.9670 | 8760.00 | 6726.19 | 8760.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
FLR_3_DOAS | 39705603.39 | 331318.26 | 40036921.65 | 64690340.46 | 8760.00 | 0.00 | 0.00 | 0.00 |
VAV WITH REHEAT | 0.56E+09 | 0.00 | 0.56E+09 | 0.22E+09 | 0.00 | 0.00 | 8760.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
FLR_3_DOAS | 1.2591 | 0.0105 | 1.2696 | 2.0513 | 8760.00 | 0.00 | 0.00 |
VAV WITH REHEAT | 17.6813 | 0.0000 | 17.6813 | 6.9969 | 0.00 | 0.00 | 8760.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
FLR_3_DOAS | 0.00 | 0.00 | 0.00 | 0.00 | 6935.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
VAV WITH REHEAT | 0.00 | 0.00 | 3217.43 | 0.00 | 0.00 | 0.00 | 5542.57 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
FLR_3_DOAS | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.5904 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
VAV WITH REHEAT | 0.0000 | 0.0000 | 18.3667 | 0.0000 | 0.0000 | 0.0000 | 17.2866 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:43
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1333 |
Defaulted Fields | 1182 |
Fields with Defaults | 4000 |
Autosized Fields | 349 |
Autosizable Fields | 402 |
Autocalculated Fields | 280 |
Autocalculatable Fields | 539 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:24:43
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 4867.25 | 67394.18 | 10-JUN-04:30 | 413449.13 | 29-JUN-18:10 |
Electricity:Building | 2446.22 | 31038.60 | 03-JUN-05:00 | 151313.73 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 304.40 | 3493.55 | 02-JAN-02:10 | 22822.84 | 02-JAN-20:10 |
Electricity:SpaceType:GENERAL | 2439.12 | 30897.46 | 03-JUN-05:00 | 151072.40 | 02-JAN-20:10 |
InteriorLights:Electricity | 780.95 | 6695.48 | 03-JUN-05:00 | 64632.59 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 161.29 | 1465.65 | 02-JAN-02:10 | 13190.31 | 02-JAN-20:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 780.95 | 6695.48 | 03-JUN-05:00 | 64632.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 780.95 | 6695.48 | 03-JUN-05:00 | 64632.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 161.29 | 1465.65 | 02-JAN-02:10 | 13190.31 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 780.95 | 6695.48 | 03-JUN-05:00 | 64632.59 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 17.49 | 210.74 | 02-JAN-02:10 | 1283.20 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 7.31 | 66.40 | 02-JAN-02:10 | 597.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 7.31 | 66.40 | 02-JAN-02:10 | 597.59 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 20.26 | 244.03 | 02-JAN-02:10 | 1485.95 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 8.46 | 76.89 | 02-JAN-02:10 | 692.02 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 8.46 | 76.89 | 02-JAN-02:10 | 692.02 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 20.84 | 252.75 | 02-JAN-02:10 | 1523.62 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.37 | 76.02 | 02-JAN-02:10 | 684.18 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.37 | 76.02 | 02-JAN-02:10 | 684.18 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 6.68 | 78.96 | 02-JAN-02:10 | 493.99 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 3.08 | 27.98 | 02-JAN-02:10 | 251.84 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 3.08 | 27.98 | 02-JAN-02:10 | 251.84 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 71.91 | 998.82 | 02-JAN-02:10 | 4897.88 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 3.98 | 36.12 | 02-JAN-02:10 | 325.08 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 3.98 | 36.12 | 02-JAN-02:10 | 325.08 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 28.19 | 269.39 | 03-JUN-05:00 | 2666.80 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 13.85 | 66.17 | 03-JUN-05:00 | 1701.53 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 | 13.85 | 66.17 | 03-JUN-05:00 | 1701.53 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 258.66 | 3093.58 | 27-MAY-05:00 | 19534.01 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 109.67 | 982.16 | 27-MAY-05:00 | 9504.80 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 109.67 | 982.16 | 27-MAY-05:00 | 9504.80 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 19.72 | 257.38 | 01-JAN-02:10 | 1438.51 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 19.72 | 257.35 | 01-JAN-02:10 | 1438.34 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 305.38 | 4267.82 | 01-JAN-02:10 | 22404.45 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 110.39 | 934.58 | 01-JAN-02:10 | 8496.21 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 110.39 | 934.58 | 01-JAN-02:10 | 8496.21 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 305.47 | 4268.99 | 01-JAN-02:10 | 22410.58 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 110.42 | 934.84 | 01-JAN-02:10 | 8498.53 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 110.42 | 934.84 | 01-JAN-02:10 | 8498.53 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 19.72 | 257.38 | 01-JAN-02:10 | 1438.51 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 19.72 | 257.35 | 01-JAN-02:10 | 1438.34 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 4.93 | 64.34 | 01-JAN-02:10 | 359.63 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 2.31 | 19.57 | 01-JAN-02:10 | 177.88 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 2.31 | 19.57 | 01-JAN-02:10 | 177.88 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 4.93 | 64.34 | 01-JAN-02:10 | 359.59 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 2.31 | 19.56 | 01-JAN-02:10 | 177.86 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 2.31 | 19.56 | 01-JAN-02:10 | 177.86 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 36.17 | 505.54 | 01-JAN-02:10 | 2653.88 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 13.08 | 110.70 | 01-JAN-02:10 | 1006.40 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 13.08 | 110.70 | 01-JAN-02:10 | 1006.40 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 206.36 | 2448.50 | 27-MAY-05:00 | 9735.93 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 30.50 | 199.20 | 27-MAY-05:00 | 2988.03 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 30.50 | 199.20 | 27-MAY-05:00 | 2988.03 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 206.36 | 2448.50 | 27-MAY-05:00 | 9735.93 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 30.50 | 199.20 | 27-MAY-05:00 | 2988.03 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 | 30.50 | 199.20 | 27-MAY-05:00 | 2988.03 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 453.81 | 6249.79 | 02-JAN-02:10 | 18934.39 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 12.97 | 117.87 | 02-JAN-02:10 | 1060.81 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 12.97 | 117.87 | 02-JAN-02:10 | 1060.81 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1658.18 | 24201.97 | 02-JAN-02:10 | 89171.45 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 1658.18 | 24201.97 | 02-JAN-02:10 | 89171.45 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 433.74 | 5990.78 | 01-JAN-00:10 | 16487.34 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 410.33 | 5248.28 | 01-JAN-00:10 | 15744.84 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
Refrigeration:Electricity | 61.05 | 870.87 | 05-JAN-23:30 | 3263.08 | 19-SEP-06:30 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
Electricity:Plant | 706.90 | 2752.54 | 13-APR-02:20 | 216372.62 | 29-JUN-18:10 |
LowTempRefrigeration:Refrigeration:Electricity | 20.23 | 0.00 | 01-JAN-11:10 | 1895.38 | 29-JUL-10:50 |
MedTempRefrigeration:Refrigeration:Electricity | 33.73 | 588.98 | 06-JAN-04:10 | 1203.59 | 14-AUG-13:10 |
Fans:Electricity | 513.88 | 10396.37 | 19-FEB-08:10 | 34581.75 | 24-AUG-21:30 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 728.71 | 12244.14 | 20-NOV-15:00 | 44715.78 | 30-JUN-19:20 |
ExteriorEquipment:Electricity | 813.77 | 9999.82 | 02-JAN-02:20 | 49607.07 | 02-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 21.77 | 380.95 | 03-JUN-05:00 | 1291.59 | 02-JAN-21:10 |
ElectricityPurchased:Facility | 4867.25 | 67394.18 | 10-JUN-04:30 | 413449.13 | 29-JUN-18:10 |
ElectricityPurchased:Plant | 4867.25 | 67394.18 | 10-JUN-04:30 | 413449.13 | 29-JUN-18:10 |
Cogeneration:ElectricityPurchased | 4867.25 | 67394.18 | 10-JUN-04:30 | 413449.13 | 29-JUN-18:10 |
General:Cogeneration:ElectricityPurchased | 4867.25 | 67394.18 | 10-JUN-04:30 | 413449.13 | 29-JUN-18:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 4867.25 | 67394.18 | 10-JUN-04:30 | 413449.13 | 29-JUN-18:10 |
ElectricityNet:Plant | 4867.25 | 67394.18 | 10-JUN-04:30 | 413449.13 | 29-JUN-18:10 |
Cogeneration:ElectricityNet | 4867.25 | 67394.18 | 10-JUN-04:30 | 413449.13 | 29-JUN-18:10 |
General:Cogeneration:ElectricityNet | 4867.25 | 67394.18 | 10-JUN-04:30 | 413449.13 | 29-JUN-18:10 |
General:Fans:Electricity | 513.88 | 10396.37 | 19-FEB-08:10 | 34581.75 | 24-AUG-21:30 |
ExteriorLights:Electricity | 193.43 | 0.00 | 01-JAN-08:20 | 12338.45 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 193.43 | 0.00 | 01-JAN-08:20 | 12338.45 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 789.09 | 9600.00 | 01-JAN-00:10 | 48128.80 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 2.91 | 18.80 | 01-JAN-00:10 | 188.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 193.06 | 0.00 | 04-FEB-14:10 | 9938.94 | 01-JAN-00:40 |
General:HeatRecovery:Electricity | 193.06 | 0.00 | 04-FEB-14:10 | 9938.94 | 01-JAN-00:40 |
WaterSystems:Electricity | 94.79 | 1222.48 | 28-JUL-00:20 | 4765.07 | 06-JAN-07:10 |
Water Heater:WaterSystems:Electricity | 94.79 | 1222.48 | 28-JUL-00:20 | 4765.07 | 06-JAN-07:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 462.08 | 0.00 | 01-JAN-00:10 | 202899.63 | 29-JUN-18:10 |
General:Cooling:Electricity | 462.08 | 0.00 | 01-JAN-00:10 | 202899.63 | 29-JUN-18:10 |
Pumps:Electricity | 96.06 | 50.71 | 27-OCT-14:10 | 6537.81 | 21-JUL-19:20 |
General:Pumps:Electricity | 96.06 | 50.71 | 27-OCT-14:10 | 6537.81 | 21-JUL-19:20 |
WIRED_LTG_ELECTRICITY | 27.49 | 0.00 | 01-JAN-00:10 | 2275.07 | 02-JAN-20:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 7975.31 | 27582.15 | 31-AUG-01:10 | 1108761.49 | 05-JAN-22:00 |
NaturalGas:Building | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Laundry:InteriorEquipment:NaturalGas | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
NaturalGas:Plant | 6186.47 | 14220.25 | 31-AUG-01:10 | 1033637.73 | 05-JAN-22:00 |
WaterSystems:NaturalGas | 3015.71 | 14220.25 | 31-AUG-01:10 | 273062.52 | 21-FEB-21:20 |
Water Heater:WaterSystems:NaturalGas | 3015.71 | 14220.25 | 31-AUG-01:10 | 273062.52 | 21-FEB-21:20 |
Heating:NaturalGas | 3170.77 | 0.00 | 27-MAR-18:30 | 816095.99 | 09-JAN-05:00 |
Boiler:Heating:NaturalGas | 3170.77 | 0.00 | 27-MAR-18:30 | 816095.99 | 09-JAN-05:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 1891.23 | 0.00 | 01-JAN-00:10 | 659356.95 | 21-JUL-19:20 |
PlantLoopCoolingDemand:HVAC | 1891.23 | 0.00 | 01-JAN-00:10 | 659356.95 | 21-JUL-19:20 |
CoolingCoils:PlantLoopCoolingDemand | 1891.23 | 0.00 | 01-JAN-00:10 | 659356.95 | 21-JUL-19:20 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 12-JAN-21:10 |
Water:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 12-JAN-21:10 |
WaterSystems:Water | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 12-JAN-21:10 |
Water Heater:WaterSystems:Water | 5742.51 | 0.00 | 07-MAR-01:40 | 0.00 | 02-JAN-19:20 |
MainsWater:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 12-JAN-21:10 |
MainsWater:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 12-JAN-21:10 |
WaterSystems:MainsWater | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 12-JAN-21:10 |
Water Heater:WaterSystems:MainsWater | 5742.51 | 0.00 | 07-MAR-01:40 | 0.00 | 02-JAN-19:20 |
WaterUse:WaterSystems:Water | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 04-JAN-07:10 |
WaterUse:WaterSystems:MainsWater | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 04-JAN-07:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 22346.76 | 139087.40 | 21-NOV-12:50 | 2806560.07 | 29-JUN-18:10 |
EnergyTransfer:Building | 4960.52 | 61103.40 | 09-JAN-11:10 | 361243.08 | 29-JUN-18:20 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 707.87 | 5967.06 | 07-JAN-04:20 | 37177.60 | 29-JUL-10:50 |
Refrigeration:EnergyTransfer | 179.17 | 1858.53 | 06-JAN-04:00 | 10368.38 | 19-SEP-06:30 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 89.59 | 929.27 | 06-JAN-04:00 | 5184.19 | 19-SEP-06:30 |
General:Refrigeration:EnergyTransfer | 89.59 | 929.27 | 06-JAN-04:00 | 5184.19 | 19-SEP-06:30 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 89.59 | 929.27 | 06-JAN-04:00 | 5184.19 | 19-SEP-06:30 |
EnergyTransfer:Plant | 7757.37 | 19476.50 | 24-OCT-03:00 | 1540975.90 | 29-JUN-18:10 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 21.50 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 68.08 | 716.94 | 06-JAN-04:10 | 2560.78 | 14-AUG-13:10 |
EnergyTransfer:Zone:BASEMENT | 397.81 | 2.92 | 06-JAN-15:00 | 32832.21 | 02-DEC-06:00 |
Heating:EnergyTransfer | 371.84 | 0.00 | 04-FEB-18:10 | 117203.41 | 25-DEC-16:20 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 1851.33 | 06-JAN-13:40 |
General:Heating:EnergyTransfer | 371.84 | 0.00 | 04-FEB-18:10 | 117203.41 | 25-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 1851.33 | 06-JAN-13:40 |
Cooling:EnergyTransfer | 4499.10 | 21028.21 | 09-JAN-10:50 | 357632.39 | 29-JUN-18:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 397.80 | 0.00 | 06-JAN-13:40 | 32832.21 | 02-DEC-06:00 |
General:Cooling:EnergyTransfer | 4499.10 | 21028.21 | 09-JAN-10:50 | 357632.39 | 29-JUN-18:20 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 397.80 | 0.00 | 06-JAN-13:40 | 32832.21 | 02-DEC-06:00 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 39.79 | 0.08 | 27-NOV-20:30 | 5193.68 | 22-OCT-12:40 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 3.76 | 0.00 | 01-JAN-00:40 | 2563.74 | 07-JAN-04:30 |
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 3.76 | 0.00 | 01-JAN-00:40 | 2563.74 | 07-JAN-04:30 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 36.03 | 0.00 | 01-JAN-00:10 | 5193.68 | 22-OCT-12:40 |
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 36.03 | 0.00 | 01-JAN-00:10 | 5193.68 | 22-OCT-12:40 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 30.82 | 0.36 | 15-FEB-10:30 | 2127.47 | 30-JUN-20:10 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.11 | 0.00 | 01-JAN-00:10 | 899.41 | 06-JAN-13:40 |
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.11 | 0.00 | 01-JAN-00:10 | 899.41 | 06-JAN-13:40 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 30.70 | 0.00 | 01-JAN-10:40 | 2127.47 | 30-JUN-20:10 |
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 30.70 | 0.00 | 01-JAN-10:40 | 2127.47 | 30-JUN-20:10 |
EnergyTransfer:Zone:MECH_FLR_1 | 19.50 | 0.02 | 04-FEB-13:40 | 1699.08 | 30-JUN-20:00 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 2.22 | 0.00 | 02-JAN-20:10 | 1489.81 | 06-JAN-13:40 |
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 | 2.22 | 0.00 | 02-JAN-20:10 | 1489.81 | 06-JAN-13:40 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 17.28 | 0.00 | 01-JAN-00:10 | 1699.08 | 30-JUN-20:00 |
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 17.28 | 0.00 | 01-JAN-00:10 | 1699.08 | 30-JUN-20:00 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 11.95 | 0.02 | 23-NOV-04:10 | 1032.14 | 06-JAN-13:40 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 3.12 | 0.00 | 18-JAN-20:20 | 1032.14 | 06-JAN-13:40 |
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 3.12 | 0.00 | 18-JAN-20:20 | 1032.14 | 06-JAN-13:40 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 8.82 | 0.00 | 01-JAN-00:10 | 835.09 | 30-JUN-19:20 |
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 8.82 | 0.00 | 01-JAN-00:10 | 835.09 | 30-JUN-19:20 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 588.19 | 2825.66 | 07-JAN-04:30 | 38867.73 | 28-JUN-20:00 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 1233.34 | 14-JAN-05:00 |
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 1233.34 | 14-JAN-05:00 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 588.18 | 1682.35 | 14-JAN-05:00 | 38867.73 | 28-JUN-20:00 |
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 588.18 | 1682.35 | 14-JAN-05:00 | 38867.73 | 28-JUN-20:00 |
EnergyTransfer:Zone:CAFE_FLR_1 | 223.35 | 3.64 | 22-DEC-14:40 | 18167.63 | 22-OCT-12:00 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.26 | 0.00 | 01-JAN-00:10 | 6021.53 | 21-DEC-11:00 |
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.26 | 0.00 | 01-JAN-00:10 | 6021.53 | 21-DEC-11:00 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 223.09 | 0.00 | 06-JAN-17:10 | 18167.63 | 22-OCT-12:00 |
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 223.09 | 0.00 | 06-JAN-17:10 | 18167.63 | 22-OCT-12:00 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 738.53 | 70.52 | 25-DEC-18:00 | 44654.84 | 24-FEB-22:50 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.51 | 0.00 | 01-JAN-00:10 | 13990.43 | 06-JAN-13:40 |
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.51 | 0.00 | 01-JAN-00:10 | 13990.43 | 06-JAN-13:40 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 738.01 | 0.00 | 06-JAN-13:30 | 44654.84 | 24-FEB-22:50 |
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 738.01 | 0.00 | 06-JAN-13:30 | 44654.84 | 24-FEB-22:50 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 76.28 | 0.00 | 01-JAN-11:10 | 13790.74 | 30-JUN-18:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 32.95 | 0.00 | 01-JAN-11:10 | 7310.74 | 25-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 32.95 | 0.00 | 01-JAN-11:10 | 7310.74 | 25-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 43.33 | 0.00 | 01-JAN-00:10 | 13790.74 | 30-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 43.33 | 0.00 | 01-JAN-00:10 | 13790.74 | 30-JUN-18:10 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 70.01 | 0.00 | 03-JAN-08:10 | 13617.76 | 30-JUN-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 40.06 | 0.00 | 03-JAN-08:10 | 7817.25 | 25-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 40.06 | 0.00 | 03-JAN-08:10 | 7817.25 | 25-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 29.96 | 0.00 | 01-JAN-00:10 | 13617.76 | 30-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 29.96 | 0.00 | 01-JAN-00:10 | 13617.76 | 30-JUN-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 270.78 | 0.00 | 01-JAN-00:10 | 69099.08 | 22-OCT-12:30 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 15.37 | 0.00 | 01-JAN-00:10 | 26064.75 | 24-DEC-06:00 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 15.37 | 0.00 | 01-JAN-00:10 | 26064.75 | 24-DEC-06:00 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 255.40 | 0.00 | 01-JAN-00:10 | 69099.08 | 22-OCT-12:30 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 255.40 | 0.00 | 01-JAN-00:10 | 69099.08 | 22-OCT-12:30 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 388.45 | 0.00 | 01-JAN-08:10 | 73756.07 | 05-JUL-22:10 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 124.03 | 0.00 | 01-JAN-08:10 | 44133.67 | 06-JAN-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 124.03 | 0.00 | 01-JAN-08:10 | 44133.67 | 06-JAN-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 264.42 | 0.00 | 01-JAN-00:10 | 73756.07 | 05-JUL-22:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 264.42 | 0.00 | 01-JAN-00:10 | 73756.07 | 05-JUL-22:10 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 75.73 | 0.00 | 01-JAN-11:10 | 12506.37 | 29-JUL-08:10 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 32.83 | 0.00 | 01-JAN-11:10 | 7327.35 | 25-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 32.83 | 0.00 | 01-JAN-11:10 | 7327.35 | 25-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 42.90 | 0.00 | 01-JAN-00:10 | 12506.37 | 29-JUL-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 42.90 | 0.00 | 01-JAN-00:10 | 12506.37 | 29-JUL-08:10 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 70.37 | 0.00 | 01-JAN-11:10 | 13678.25 | 19-JUL-09:00 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 39.96 | 0.00 | 01-JAN-11:10 | 8020.21 | 06-JAN-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 39.96 | 0.00 | 01-JAN-11:10 | 8020.21 | 06-JAN-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 30.41 | 0.00 | 01-JAN-00:10 | 13678.25 | 19-JUL-09:00 |
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 30.41 | 0.00 | 01-JAN-00:10 | 13678.25 | 19-JUL-09:00 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 167.72 | 0.09 | 27-JAN-19:00 | 12057.40 | 30-JUN-19:20 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 8.29 | 0.00 | 01-JAN-00:40 | 8077.88 | 06-JAN-13:40 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 8.29 | 0.00 | 01-JAN-00:40 | 8077.88 | 06-JAN-13:40 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 159.43 | 0.00 | 01-JAN-00:10 | 12057.40 | 30-JUN-19:20 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 159.43 | 0.00 | 01-JAN-00:10 | 12057.40 | 30-JUN-19:20 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 22.43 | 0.00 | 01-JAN-11:10 | 3653.72 | 30-JUN-18:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 11.82 | 0.00 | 01-JAN-11:10 | 2258.52 | 25-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 11.82 | 0.00 | 01-JAN-11:10 | 2258.52 | 25-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 10.62 | 0.00 | 01-JAN-00:10 | 3653.72 | 30-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 10.62 | 0.00 | 01-JAN-00:10 | 3653.72 | 30-JUN-18:10 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 21.45 | 0.00 | 16-JAN-08:10 | 4022.65 | 06-MAY-19:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 14.00 | 0.00 | 16-JAN-08:10 | 2374.39 | 25-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 14.00 | 0.00 | 16-JAN-08:10 | 2374.39 | 25-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 7.45 | 0.00 | 01-JAN-00:10 | 4022.65 | 06-MAY-19:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 7.45 | 0.00 | 01-JAN-00:10 | 4022.65 | 06-MAY-19:10 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 101.27 | 0.00 | 01-JAN-08:10 | 17810.66 | 19-OCT-15:10 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 33.73 | 0.00 | 01-JAN-08:10 | 9969.12 | 11-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 33.73 | 0.00 | 01-JAN-08:10 | 9969.12 | 11-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 67.54 | 0.00 | 01-JAN-00:10 | 17810.66 | 19-OCT-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 67.54 | 0.00 | 01-JAN-00:10 | 17810.66 | 19-OCT-15:10 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 408.82 | 24.59 | 06-JAN-14:50 | 23828.32 | 24-FEB-23:00 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.02 | 0.00 | 01-JAN-00:10 | 4124.05 | 06-JAN-13:40 |
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.02 | 0.00 | 01-JAN-00:10 | 4124.05 | 06-JAN-13:40 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 408.80 | 0.00 | 06-JAN-13:40 | 23828.32 | 24-FEB-23:00 |
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 408.80 | 0.00 | 06-JAN-13:40 | 23828.32 | 24-FEB-23:00 |
EnergyTransfer:Zone:DINING_FLR_6 | 449.22 | 352.43 | 06-JAN-14:20 | 26098.64 | 24-FEB-23:00 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.02 | 0.00 | 01-JAN-00:10 | 3820.32 | 06-JAN-13:40 |
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.02 | 0.00 | 01-JAN-00:10 | 3820.32 | 06-JAN-13:40 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 449.21 | 0.00 | 06-JAN-13:40 | 26098.64 | 24-FEB-23:00 |
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 449.21 | 0.00 | 06-JAN-13:40 | 26098.64 | 24-FEB-23:00 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 454.05 | 14-JAN-05:00 |
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 454.05 | 14-JAN-05:00 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 618.29 | 3366.01 | 07-JAN-04:20 | 32111.35 | 29-JUL-10:50 |
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 618.29 | 3366.01 | 07-JAN-04:20 | 32111.35 | 29-JUL-10:50 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 80.20 | 0.09 | 01-FEB-23:50 | 6815.56 | 30-JUN-13:20 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 8.77 | 0.00 | 02-JAN-11:40 | 5924.77 | 07-JAN-04:30 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 8.77 | 0.00 | 02-JAN-11:40 | 5924.77 | 07-JAN-04:30 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 71.43 | 0.00 | 01-JAN-00:10 | 6815.56 | 30-JUN-13:20 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 71.43 | 0.00 | 01-JAN-00:10 | 6815.56 | 30-JUN-13:20 |
PlantLoopHeatingDemand:Facility | 3295.85 | 11091.24 | 26-AUG-00:10 | 710637.18 | 06-JAN-07:10 |
PlantLoopHeatingDemand:Plant | 918.00 | 11091.24 | 26-AUG-02:10 | 67757.32 | 24-FEB-07:20 |
WaterSystems:PlantLoopHeatingDemand | 918.00 | 11091.24 | 26-AUG-02:10 | 67757.32 | 24-FEB-07:20 |
General:WaterSystems:PlantLoopHeatingDemand | 918.00 | 11091.24 | 26-AUG-02:10 | 67757.32 | 24-FEB-07:20 |
EnergyTransfer:HVAC | 9628.87 | 768.69 | 19-SEP-14:40 | 908160.22 | 29-JUN-18:10 |
HeatingCoils:EnergyTransfer | 2377.85 | 0.00 | 27-MAR-18:30 | 658272.19 | 09-JAN-05:00 |
PlantLoopHeatingDemand:HVAC | 2377.85 | 0.00 | 27-MAR-18:30 | 658272.19 | 09-JAN-05:00 |
HeatingCoils:PlantLoopHeatingDemand | 2377.85 | 0.00 | 27-MAR-18:30 | 658272.19 | 09-JAN-05:00 |
CoolingCoils:EnergyTransfer | 1891.23 | 0.00 | 01-JAN-00:10 | 659356.95 | 21-JUL-19:20 |
HeatRecoveryForHeating:EnergyTransfer | 5233.16 | 0.00 | 01-JAN-00:40 | 581855.35 | 24-FEB-06:20 |
HeatRecoveryForCooling:EnergyTransfer | 126.63 | 0.00 | 01-JAN-00:10 | 263982.02 | 29-JUN-18:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 918.00 | 11091.24 | 26-AUG-02:10 | 67757.32 | 24-FEB-07:20 |
WaterUse:WaterSystems:EnergyTransfer | 918.00 | 11091.24 | 26-AUG-02:10 | 67757.32 | 24-FEB-07:20 |
Boilers:EnergyTransfer | 2362.57 | 0.00 | 27-MAR-18:30 | 655634.37 | 09-JAN-05:00 |
Chillers:EnergyTransfer | 1962.56 | 0.00 | 01-JAN-00:10 | 661693.13 | 21-JUL-19:20 |
HeatRejection:EnergyTransfer | 2424.65 | 0.00 | 01-JAN-00:10 | 851501.63 | 29-JUN-18:10 |
General:HeatRejection:EnergyTransfer | 2424.65 | 0.00 | 01-JAN-00:10 | 851501.63 | 29-JUN-18:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:43
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.004 | -397.805 | 0.000 | 0.000 | 142.169 | 161.294 | 143.105 | 0.000 | 0.000 | 0.000 | 0.012 | 0.000 | 0.000 | 0.000 | 0.000 | -48.767 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 3.762 | -36.028 | 0.000 | 0.000 | 15.912 | 7.307 | 10.186 | 28.508 | 0.000 | 0.025 | 0.001 | 0.000 | -14.661 | 0.000 | -3.262 | -11.748 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.115 | -30.703 | 0.000 | 0.000 | 17.298 | 8.462 | 11.795 | 0.000 | 0.000 | 0.009 | 0.000 | 0.000 | 0.000 | 0.000 | -1.318 | -5.659 |
MECH_FLR_1 | 0.000 | 0.000 | 2.222 | -17.276 | 0.000 | 0.000 | 3.754 | 8.366 | 12.471 | 0.000 | 0.000 | 0.023 | 0.000 | 0.000 | 0.000 | 0.000 | -3.057 | -6.502 |
STORAGE_FLR_1 | 0.000 | 0.000 | 3.123 | -8.824 | 0.000 | 0.000 | 2.928 | 3.079 | 3.598 | 0.000 | 0.000 | 0.014 | 0.000 | 0.000 | 0.000 | 0.000 | -1.743 | -2.174 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.003 | -588.186 | 0.000 | 0.000 | 11.421 | 3.975 | 658.131 | 0.000 | 0.000 | 0.034 | 0.001 | 0.000 | 0.000 | 0.000 | -4.345 | -81.033 |
CAFE_FLR_1 | 0.000 | 0.000 | 0.256 | -223.096 | 0.000 | 0.000 | 198.749 | 13.850 | 14.341 | 79.436 | 0.000 | 0.051 | 0.002 | 0.000 | -42.554 | 0.000 | -7.477 | -33.556 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.515 | -738.018 | 0.000 | 0.000 | 571.129 | 109.666 | 148.998 | 104.578 | 0.000 | 0.149 | 0.004 | 0.000 | -57.874 | 0.000 | -21.880 | -117.263 |
ROOM_1_FLR_3 | 39.248 | -37.775 | 0.000 | -11.849 | 0.000 | 0.000 | 9.752 | 9.244 | 10.478 | 51.606 | 0.000 | 0.140 | 0.000 | 0.000 | -34.586 | 0.000 | -8.047 | -28.212 |
ROOM_2_FLR_3 | 46.615 | -24.098 | 0.000 | -12.414 | 0.000 | 0.000 | 9.596 | 9.243 | 10.477 | 35.207 | 0.000 | 0.083 | 0.000 | 0.000 | -36.913 | 0.000 | -8.263 | -29.534 |
ROOM_3_MULT19_FLR_3 | 15.367 | -243.147 | 0.009 | -12.255 | 0.000 | 0.000 | 0.000 | 110.385 | 194.997 | 326.804 | 0.000 | 0.072 | 0.002 | 0.000 | -203.535 | 0.000 | -44.951 | -143.745 |
ROOM_4_MULT19_FLR_3 | 196.524 | -172.740 | 0.000 | -164.166 | 0.000 | 0.000 | 183.874 | 110.415 | 195.050 | 86.804 | 0.000 | 0.635 | 0.000 | 0.000 | -208.930 | 0.000 | -54.406 | -173.062 |
ROOM_5_FLR_3 | 39.101 | -37.320 | 0.000 | -11.853 | 0.000 | 0.000 | 9.748 | 9.244 | 10.478 | 51.082 | 0.000 | 0.141 | 0.000 | 0.000 | -33.990 | 0.000 | -8.062 | -28.568 |
ROOM_6_FLR_3 | 46.541 | -24.692 | 0.000 | -12.293 | 0.000 | 0.000 | 9.645 | 9.243 | 10.477 | 34.496 | 0.000 | 0.084 | 0.000 | 0.000 | -35.989 | 0.000 | -8.471 | -29.041 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 8.291 | -159.434 | 0.000 | 0.000 | 119.895 | 91.336 | 0.000 | 46.633 | 0.000 | 0.070 | 0.004 | 0.000 | -43.991 | 0.000 | -9.353 | -53.446 |
ROOM_1_FLR_6 | 13.493 | -9.333 | 0.000 | -2.958 | 0.000 | 0.000 | 2.442 | 2.311 | 2.620 | 12.851 | 0.000 | 0.037 | 0.000 | 0.000 | -8.628 | 0.000 | -2.030 | -10.804 |
ROOM_2_FLR_6 | 15.725 | -6.060 | 0.000 | -3.113 | 0.000 | 0.000 | 2.397 | 2.311 | 2.619 | 8.757 | 0.000 | 0.021 | 0.000 | 0.000 | -9.229 | 0.000 | -2.073 | -11.355 |
ROOM_3_MULT9_FLR_6 | 42.929 | -57.591 | 0.000 | -19.147 | 0.000 | 0.000 | 21.869 | 13.076 | 23.098 | 73.642 | 0.000 | 0.243 | 0.000 | 0.000 | -39.846 | 0.000 | -10.057 | -48.216 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.024 | -408.801 | 0.000 | 0.000 | 321.976 | 30.499 | 175.857 | 9.102 | 0.000 | 0.027 | 0.000 | 0.000 | -26.391 | 0.000 | -5.134 | -97.159 |
DINING_FLR_6 | 0.000 | 0.000 | 0.016 | -449.210 | 0.000 | 0.000 | 320.454 | 30.499 | 175.857 | 8.928 | 0.000 | 0.027 | 0.000 | 0.000 | -26.926 | 0.000 | -5.165 | -54.480 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.000 | -618.270 | 0.000 | 0.000 | 28.903 | 12.972 | 550.372 | 24.195 | 0.000 | 0.024 | 23.159 | 0.000 | -16.736 | 0.000 | -4.620 | -0.000 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 8.771 | -71.429 | 0.000 | 0.000 | 31.860 | 24.166 | 0.000 | 23.238 | 0.000 | 0.026 | 7.027 | 0.000 | -19.523 | 0.000 | -4.136 | -0.000 |
Total Facility | 455.542 | -612.755 | 27.109 | -3997.128 | 0.000 | 0.000 | 2035.770 | 780.945 | 2365.005 | 1005.867 | 0.000 | 1.934 | 30.214 | 0.000 | -860.302 | 0.000 | -217.850 | -1014.325 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 25-JAN-23:33 | 0.00 | 0.00 | 0.00 | -33032.68 | 0.00 | 0.00 | 7928.41 | 4396.77 | 4055.80 | 0.00 | 0.00 | 0.00 | 16651.69 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 22-OCT-12:40 | 0.00 | 0.00 | 0.00 | -5193.44 | 0.00 | 0.00 | 150.60 | 132.80 | 216.51 | 8321.83 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -32.20 | -3596.09 |
RETAIL_2_FLR_1 | 25-JAN-20:01 | 0.00 | 0.00 | 0.00 | -2645.70 | 0.00 | 0.00 | 702.86 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 563.30 | 0.00 | -0.00 | 0.00 | -106.42 | 0.00 |
MECH_FLR_1 | 30-JUN-20:00 | 0.00 | 0.00 | 0.00 | -1699.06 | 0.00 | 0.00 | 129.08 | 684.18 | 839.45 | 0.00 | 0.00 | 1.83 | 44.52 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 30-JUN-19:20 | 0.00 | 0.00 | 0.00 | -835.08 | 0.00 | 0.00 | 99.30 | 251.84 | 242.16 | 0.00 | 0.00 | 7.02 | 234.78 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 25-JAN-20:01 | 0.00 | 0.00 | 0.00 | -41168.34 | 0.00 | 0.00 | 408.89 | 325.08 | 44299.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -357.48 | -3507.52 |
CAFE_FLR_1 | 22-OCT-12:00 | 0.00 | 0.00 | 0.00 | -18168.01 | 0.00 | 0.00 | 2968.69 | 124.78 | 406.43 | 23804.18 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -83.66 | -9052.41 |
LOBBY_FLR_1 | 25-JAN-20:01 | 0.00 | 0.00 | 0.00 | -60136.03 | 0.00 | 0.00 | 23065.60 | 9504.80 | 10029.21 | 0.00 | 0.00 | 0.00 | 25477.93 | 0.00 | -6184.02 | 0.00 | -1757.49 | 0.00 |
ROOM_1_FLR_3 | 14-MAY-18:01 | 0.00 | -17063.26 | 0.00 | -647.99 | 0.00 | 0.00 | 283.22 | 711.53 | 484.65 | 10133.92 | 0.00 | 0.00 | 6462.71 | 0.00 | -0.00 | 0.00 | -364.79 | 0.00 |
ROOM_2_FLR_3 | 06-MAY-18:42 | 0.00 | -20132.95 | 0.00 | -776.48 | 0.00 | 0.00 | 192.00 | 711.45 | 484.60 | 5723.25 | 0.00 | 0.00 | 13939.96 | 0.00 | -0.00 | 0.00 | -141.83 | 0.00 |
ROOM_3_MULT19_FLR_3 | 22-OCT-12:30 | 0.00 | -69100.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2803.75 | 2548.95 | 100276.33 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -586.12 | -35942.48 |
ROOM_4_MULT19_FLR_3 | 21-MAY-21:01 | 0.00 | -87879.49 | 0.00 | -7796.96 | 0.00 | 0.00 | 6149.38 | 7223.75 | 6668.31 | 0.00 | 0.00 | 0.00 | 82171.62 | 0.00 | -5863.56 | 0.00 | -673.04 | 0.00 |
ROOM_5_FLR_3 | 22-APR-08:62 | 0.00 | -15549.76 | 0.00 | -500.13 | 0.00 | 0.00 | 130.71 | 398.46 | 653.23 | 13115.01 | 0.00 | 0.00 | 1923.51 | 0.00 | -0.00 | 0.00 | -171.03 | 0.00 |
ROOM_6_FLR_3 | 31-JUL-08:32 | 0.00 | -16304.68 | 0.00 | -925.05 | 0.00 | 0.00 | 59.19 | 313.04 | 452.99 | 11100.09 | 0.00 | 0.00 | 5399.00 | 0.00 | -0.00 | 0.00 | -94.59 | 0.00 |
CORRIDOR_FLR_3 | 30-JUN-19:20 | 0.00 | 0.00 | 0.00 | -12057.69 | 0.00 | 0.00 | 4080.33 | 7469.27 | 0.00 | 2758.69 | 0.00 | 36.83 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2287.42 |
ROOM_1_FLR_6 | 14-MAY-18:01 | 0.00 | -4446.26 | 0.00 | -162.31 | 0.00 | 0.00 | 70.80 | 177.88 | 121.16 | 2520.86 | 0.00 | 0.00 | 1829.08 | 0.00 | -0.00 | 0.00 | -111.22 | 0.00 |
ROOM_2_FLR_6 | 06-MAY-18:42 | 0.00 | -5269.17 | 0.00 | -196.91 | 0.00 | 0.00 | 47.81 | 177.86 | 121.15 | 1400.73 | 0.00 | 0.00 | 3754.64 | 0.00 | -0.00 | 0.00 | -36.11 | 0.00 |
ROOM_3_MULT9_FLR_6 | 05-JAN-16:01 | 0.00 | -20710.99 | 0.00 | -2769.00 | 0.00 | 0.00 | 536.67 | 281.79 | 441.28 | 65.02 | 0.00 | 0.00 | 22964.83 | 0.00 | -0.00 | 0.00 | -809.61 | 0.00 |
BANQUET_FLR_6 | 25-JAN-20:01 | 0.00 | 0.00 | 0.00 | -26672.82 | 0.00 | 0.00 | 12525.54 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 7234.24 | 0.00 | -2417.61 | 0.00 | -405.29 | 0.00 |
DINING_FLR_6 | 25-JAN-20:01 | 0.00 | 0.00 | 0.00 | -28344.47 | 0.00 | 0.00 | 12271.01 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 9198.74 | 0.00 | -2453.43 | 0.00 | -407.79 | 0.00 |
KITCHEN_FLR_6 | 29-JUL-10:40 | 0.00 | 0.00 | 0.00 | -32129.65 | 0.00 | 0.00 | 464.23 | 294.67 | 24259.91 | 4647.91 | 0.00 | 20.01 | 2442.92 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 30-JUN-13:20 | 0.00 | 0.00 | 0.00 | -6816.37 | 0.00 | 0.00 | 308.45 | 548.96 | 0.00 | 4095.53 | 0.00 | 45.16 | 1818.27 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 29-JUN-18:02 | 0.00 | -180204.91 | 0.00 | -204012.57 | 0.00 | 0.00 | 74638.55 | 52987.32 | 120482.43 | 75963.60 | 0.00 | 2434.29 | 57711.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 06-JAN-13:31 | 0.00 | 0.00 | 2517.85 | 0.00 | 0.00 | 0.00 | 2035.51 | 3664.03 | 3548.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -11766.22 |
RETAIL_1_FLR_1 | 14-JAN-04:51 | 0.00 | 0.00 | 2874.69 | 0.00 | 0.00 | 0.00 | 948.06 | 66.40 | 144.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1425.37 | 0.00 | -244.42 | -2363.71 |
RETAIL_2_FLR_1 | 06-JAN-13:31 | 0.00 | 0.00 | 990.51 | 0.00 | 0.00 | 0.00 | 241.56 | 192.23 | 292.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -95.27 | -1621.53 |
MECH_FLR_1 | 06-JAN-13:31 | 0.00 | 0.00 | 1512.16 | 0.00 | 0.00 | 0.00 | 51.22 | 190.05 | 309.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -225.67 | -1837.03 |
STORAGE_FLR_1 | 06-JAN-13:31 | 0.00 | 0.00 | 1045.20 | 0.00 | 0.00 | 0.00 | 40.03 | 69.95 | 89.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -128.63 | -1115.77 |
LAUNDRY_FLR_1 | 14-JAN-04:51 | 0.00 | 0.00 | 7467.87 | 0.00 | 0.00 | 0.00 | 784.61 | 36.12 | 9326.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -294.56 | -17320.22 |
CAFE_FLR_1 | 21-DEC-10:51 | 0.00 | 0.00 | 7557.15 | 0.00 | 0.00 | 0.00 | 2846.51 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -334.04 | 0.00 | -538.49 | -9990.74 |
LOBBY_FLR_1 | 09-JAN-10:41 | 0.00 | 0.00 | 17066.45 | 0.00 | 0.00 | 0.00 | 8113.63 | 2270.59 | 3694.97 | 26209.32 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1561.68 | -55793.29 |
ROOM_1_FLR_3 | 25-DEC-16:13 | 8308.64 | 370.32 | 0.00 | -370.32 | 0.00 | 0.00 | 147.99 | 234.80 | 221.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2907.51 | 0.00 | -485.54 | -5519.63 |
ROOM_2_FLR_3 | 06-JAN-08:04 | 8686.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.35 | 313.04 | 452.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4392.92 | 0.00 | -806.64 | -4474.49 |
ROOM_3_MULT19_FLR_3 | 24-DEC-06:00 | 26064.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 934.58 | 3333.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -21318.77 | 0.00 | -3642.00 | -5371.59 |
ROOM_4_MULT19_FLR_3 | 06-JAN-16:02 | 45149.76 | 3462.10 | 0.00 | -3462.10 | 0.00 | 0.00 | 5585.69 | 2379.59 | 3726.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -17655.23 | 0.00 | -3110.52 | -36075.68 |
ROOM_5_FLR_3 | 25-DEC-16:13 | 8132.79 | 366.24 | 0.00 | -366.24 | 0.00 | 0.00 | 148.01 | 234.80 | 221.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2916.53 | 0.00 | -484.78 | -5335.56 |
ROOM_6_FLR_3 | 06-JAN-16:02 | 8214.65 | 264.81 | 0.00 | -264.81 | 0.00 | 0.00 | 293.98 | 199.20 | 200.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3273.01 | 0.00 | -588.36 | -5046.64 |
CORRIDOR_FLR_3 | 06-JAN-13:31 | 0.00 | 0.00 | 8375.53 | 0.00 | 0.00 | 0.00 | 1532.26 | 2074.80 | 0.00 | 7581.94 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -721.00 | -18843.53 |
ROOM_1_FLR_6 | 25-DEC-16:13 | 2456.67 | 92.05 | 0.00 | -92.05 | 0.00 | 0.00 | 37.00 | 58.70 | 55.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -726.34 | 0.00 | -121.51 | -1759.84 |
ROOM_2_FLR_6 | 05-JAN-08:04 | 2654.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.03 | 78.26 | 113.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1122.40 | 0.00 | -188.63 | -1590.34 |
ROOM_3_MULT9_FLR_6 | 11-DEC-16:13 | 11615.26 | 604.33 | 0.00 | -604.33 | 0.00 | 0.00 | 599.32 | 281.79 | 441.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3618.36 | 0.00 | -599.11 | -8720.19 |
BANQUET_FLR_6 | 09-JAN-10:41 | 0.00 | 0.00 | 6385.91 | 0.00 | 0.00 | 0.00 | 4788.01 | 553.34 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1546.42 | 0.00 | -353.72 | -16575.02 |
DINING_FLR_6 | 09-JAN-10:41 | 0.00 | 0.00 | 6218.22 | 0.00 | 0.00 | 0.00 | 4751.57 | 553.34 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1568.23 | 0.00 | -355.77 | -16347.03 |
KITCHEN_FLR_6 | 14-JAN-04:51 | 0.00 | 0.00 | 3226.05 | 0.00 | 0.00 | 0.00 | 1923.43 | 117.87 | 5415.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1700.79 | 0.00 | -317.88 | -8664.65 |
CORRIDOR_FLR_6 | 06-JAN-13:31 | 0.00 | 0.00 | 6049.10 | 0.00 | 0.00 | 0.00 | 413.13 | 548.96 | 0.00 | 4379.49 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -315.18 | -11075.50 |
Total Facility | 14-JAN-04:51 | 69973.89 | 23152.40 | 45486.09 | -23152.40 | 0.00 | 0.00 | 116557.30 | 7157.90 | 31990.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -82617.98 | 0.00 | -15137.99 | -173409.87 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:43
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV WITH REHEAT | 23.5292 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 23.3888 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV WITH REHEAT | 11.7646 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 11.6705 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.6520 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.0400 | 0.000610 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.000000 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.000000 | 142.3000 | 0.003581 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.000000 | 422.4350 | 0.001448 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 83.8280 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003556 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.1800 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 | |
VAV WITH REHEAT | 0.00 | 0.001045 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.5893 | 2.5893 | 1.2843 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4515 | 0.4515 | 0.2239 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2385 | 0.2385 | 0.1183 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1820 | 0.1820 | 0.0903 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1090 | 0.1090 | 0.0541 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.3906 | 3.3906 | 1.6817 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8072 | 1.8072 | 0.8964 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.2993 | 5.2993 | 2.6284 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7013 | 1.7013 | 0.8438 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2155 | 2.2155 | 1.0989 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3220 | 2.3220 | 1.1517 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3934 | 2.3934 | 1.1871 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8296 | 0.8296 | 0.4115 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
VAV WITH REHEAT | 23.5292 | 23.3888 | 23.5292 | 11.6705 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2946 | 1.2946 | 1.2843 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2257 | 0.2257 | 0.2239 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1193 | 0.1193 | 0.1183 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0910 | 0.0910 | 0.0903 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0545 | 0.0545 | 0.0541 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6953 | 1.6953 | 1.6817 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9036 | 0.9036 | 0.8964 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6496 | 2.6496 | 2.6284 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8506 | 0.8506 | 0.8438 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1078 | 1.1078 | 1.0989 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1610 | 1.1610 | 1.1517 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1967 | 1.1967 | 1.1871 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4148 | 0.4148 | 0.4115 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
VAV WITH REHEAT | 11.7646 | 11.6705 | 11.6705 | 11.6705 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:43
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 168.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 168.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 551.33 |
Number of hours cooling loads not met | 45.50 |
Number of hours not met | 596.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 3170.77 | 816095.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 462.08 | 202899.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 780.95 | 64632.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 193.43 | 12338.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 872.72 | 59188.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 14.43 | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 8.99 | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.20 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 21.77 | 1291.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 789.09 | 48128.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 2.91 | 188.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 513.88 | 34581.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 96.06 | 6537.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 193.06 | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 94.79 | 4765.07 | 3015.71 | 273062.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.09 | 2093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 20.23 | 1895.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 33.73 | 1203.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1719.23 | 4867.25 |
Natural Gas | 1788.84 | 7975.31 |
Additional | 0.00 | 0.00 |
Total | 3508.07 | 12842.56 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 68.83 |
Space Heating | 0.00 |
Space Cooling | 40.73 |
Fans (All) | 45.29 |
Service Water Heating | 8.36 |
Receptacle Equipment | 146.16 |
Miscellaneous (All) | 429.01 |
Subtotal | 429.01 |
Natural Gas [MJ/m2] | |
Space Heating | 279.48 |
Service Water Heating | 265.81 |
Miscellaneous (All) | 702.96 |
Subtotal | 702.96 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 6.08 |
Space Heating | 24.69 |
Space Cooling | 3.60 |
Fans (All) | 4.00 |
Service Water Heating | 24.22 |
Receptacle Equipment | 26.84 |
Miscellaneous | 10.57 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 486. | 5110. |
ELEVATOR_STANDBY_SCH | 7671. | 8760. |
LTG_SCH_KITCHEN | 3061. | 8760. |
LTG_SCH_DINING | 3061. | 8760. |
LTG_SCH_BASEMENT | 2572. | 8760. |
LTG_SCH_LOBBY | 2295. | 8760. |
LTG_SCH_STORAGE | 1580. | 8760. |
LTG_SCH_MECHANIC | 3061. | 8760. |
LTG_SCH_LAUNDRY | 3061. | 8760. |
LTG_SCH_GUESTROOM | 1980. | 8760. |
LTG_SCH_CORRIDOR | 2295. | 8760. |
LTG_SCH_RETAIL | 2678. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 1591. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3737. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 5740. | 6205. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 8760. | 8760. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 26.67 | 365 | 26.67 | 365 |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
HTGSETP_SCH | BASEMENT DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:43
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8627.67 | 132.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8585.33 | 174.67 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8717.17 | 42.83 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8585.00 | 175.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 175.00 | 0.00 | 0.00 | 0.00 |
Average | 8736.14 | 23.86 | 0.00 | 0.00 | 0.00 |
Sum | 192195.17 | 524.83 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4106.83 | 47.17 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4083.67 | 70.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108269.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 70.33 | 0.00 | 0.00 | 0.00 |
Average | 288881.70 | 5.34 | 0.00 | 0.00 | 0.00 |
Sum | 6355397.50 | 117.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8691.83 | 68.17 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8443.00 | 317.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8402.33 | 357.67 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8533.50 | 226.50 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8348.67 | 411.33 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8733.83 | 26.17 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8643.17 | 116.83 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8472.83 | 287.17 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8759.83 | 0.17 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8381.67 | 378.33 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8418.83 | 341.17 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8716.67 | 43.33 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8348.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 411.33 | 0.00 | 0.00 | 0.00 |
Average | 8643.01 | 116.99 | 0.00 | 0.00 | 0.00 |
Sum | 190146.17 | 2573.83 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 58418.67 | 737.33 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 670817.67 | 39599.33 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 1987932.33 | 127496.67 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4042.17 | 111.83 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4142.67 | 11.33 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4128.33 | 25.67 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 3999.83 | 154.17 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1167014.17 | 78700.83 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1173827.00 | 71888.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 107952.50 | 316.50 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 1987932.33 | 127496.67 | 0.00 | 0.00 | 0.00 |
Average | 274385.15 | 14501.89 | 0.00 | 0.00 | 0.00 |
Sum | 6036473.33 | 319041.67 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:43
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:43
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 1592.73 | 0.00 | 0.00 |
Sum | 0.00 | 35040.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 710417.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 2115429.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 2115429.00 | 0.00 | 0.00 |
Average | 0.00 | 241694.36 | 0.00 | 0.00 |
Sum | 0.00 | 5317276.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7
For: Environment
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Environment
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS
For: Environment
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.345793E+11 | 33032.77 | 25-JAN-23:33 | -28.3 | -28.5 | 0.655006E+10 | 4836.92 | 24-JAN-22:19 | -28.3 | -28.5 |
February | 0.289056E+11 | 30953.63 | 13-FEB-23:01 | -26.2 | -26.5 | 0.642565E+10 | 4752.88 | 10-FEB-22:10 | -26.2 | -26.5 |
March | 0.285449E+11 | 29750.22 | 12-MAR-03:51 | -23.9 | -24.1 | 0.710026E+10 | 4598.40 | 01-MAR-22:10 | -23.9 | -24.1 |
April | 0.272962E+11 | 13449.95 | 22-APR-10:33 | 14.43 | 5.29 | 0.688142E+10 | 4423.54 | 26-APR-21:10 | 0.00 | -0.6 |
May | 0.299458E+11 | 14110.81 | 18-MAY-10:33 | 26.07 | 16.42 | 0.728158E+10 | 4542.78 | 12-MAY-22:10 | 26.07 | 16.42 |
June | 0.305766E+11 | 14848.06 | 25-JUN-10:33 | 27.43 | 22.06 | 0.725172E+10 | 4667.16 | 23-JUN-22:10 | 27.43 | 22.06 |
July | 0.341254E+11 | 15707.84 | 23-JUL-10:33 | 27.77 | 23.32 | 0.785441E+10 | 4837.10 | 26-JUL-21:30 | 12.50 | 11.71 |
August | 0.368743E+11 | 19605.66 | 31-AUG-21:00 | 22.80 | 20.41 | 0.815261E+10 | 4837.09 | 11-AUG-22:10 | 22.80 | 20.41 |
September | 0.368645E+11 | 20849.16 | 08-SEP-21:00 | 11.70 | 7.35 | 0.792881E+10 | 4837.08 | 01-SEP-21:40 | 11.70 | 7.35 |
October | 0.380040E+11 | 21280.06 | 20-OCT-21:00 | 6.10 | 4.28 | 0.819891E+10 | 4837.06 | 29-OCT-23:19 | -7.6 | -8.4 |
November | 0.354700E+11 | 20587.64 | 17-NOV-22:00 | 2.80 | -0.9 | 0.791336E+10 | 4837.15 | 01-NOV-01:10 | 2.80 | -0.9 |
December | 0.366180E+11 | 32832.21 | 02-DEC-06:00 | -27.8 | -28.0 | 0.715363E+10 | 4837.04 | 01-DEC-00:20 | -27.8 | -28.0 |
Annual Sum or Average | 0.397805E+12 | 0.886924E+11 | ||||||||
Minimum of Months | 0.272962E+11 | 13449.95 | -28.3 | -28.5 | 0.642565E+10 | 4423.54 | -28.3 | -28.5 | ||
Maximum of Months | 0.380040E+11 | 33032.77 | 27.77 | 23.32 | 0.819891E+10 | 4837.15 | 27.43 | 22.06 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.609123E+09 | 2453.75 | 27-JAN-13:30 | -15.0 | -16.1 | 0.548027E+09 | 364.19 | 25-JAN-04:49 | -15.0 | -16.1 |
February | 0.134679E+10 | 3803.05 | 28-FEB-13:30 | 3.05 | -0.7 | 0.546203E+09 | 369.60 | 28-FEB-22:30 | -0.3 | -3.2 |
March | 0.193029E+10 | 3684.34 | 20-MAR-12:30 | 1.70 | -1.1 | 0.628874E+09 | 386.87 | 31-MAR-21:30 | 4.75 | 0.82 |
April | 0.311452E+10 | 3925.00 | 13-APR-13:10 | 17.98 | 6.86 | 0.627022E+09 | 433.93 | 13-APR-21:30 | 12.50 | 6.57 |
May | 0.459089E+10 | 3843.75 | 18-MAY-13:10 | 28.25 | 16.75 | 0.673824E+09 | 462.67 | 25-MAY-21:19 | 22.50 | 16.44 |
June | 0.475222E+10 | 3917.45 | 30-JUN-13:00 | 31.70 | 24.46 | 0.665713E+09 | 478.98 | 29-JUN-21:19 | 31.70 | 24.46 |
July | 0.542488E+10 | 4057.34 | 23-JUL-13:10 | 30.00 | 22.77 | 0.711588E+09 | 469.55 | 24-JUL-21:30 | 19.15 | 17.68 |
August | 0.526005E+10 | 4488.59 | 26-AUG-12:40 | 25.40 | 19.23 | 0.702886E+09 | 465.37 | 25-AUG-21:30 | 25.40 | 19.23 |
September | 0.435726E+10 | 4500.65 | 01-SEP-13:15 | 24.80 | 18.00 | 0.644896E+09 | 454.90 | 01-SEP-21:30 | 14.45 | 13.76 |
October | 0.294917E+10 | 5193.68 | 22-OCT-12:40 | 17.77 | 12.92 | 0.640759E+09 | 441.98 | 19-OCT-21:30 | 17.77 | 12.92 |
November | 0.130343E+10 | 3562.97 | 17-NOV-12:40 | 9.63 | 3.12 | 0.604386E+09 | 372.83 | 17-NOV-22:30 | 2.25 | -1.2 |
December | 0.389552E+09 | 2716.51 | 10-DEC-12:30 | -23.6 | -24.1 | 0.568338E+09 | 364.24 | 13-DEC-04:19 | -23.7 | -24.0 |
Annual Sum or Average | 0.360282E+11 | 0.756252E+10 | ||||||||
Minimum of Months | 0.389552E+09 | 2453.75 | -23.6 | -24.1 | 0.546203E+09 | 364.19 | -23.7 | -24.0 | ||
Maximum of Months | 0.542488E+10 | 5193.68 | 31.70 | 24.46 | 0.711588E+09 | 478.98 | 31.70 | 24.46 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.174354E+10 | 2645.76 | 25-JAN-20:01 | -24.0 | -24.2 | 0.680688E+09 | 485.45 | 19-JAN-23:10 | -24.0 | -24.2 |
February | 0.185529E+10 | 2595.20 | 24-FEB-22:52 | -23.9 | -24.3 | 0.675675E+09 | 527.88 | 22-FEB-22:40 | -23.9 | -24.3 |
March | 0.229579E+10 | 2640.99 | 07-MAR-00:51 | -24.4 | -24.6 | 0.796387E+09 | 549.05 | 31-MAR-22:10 | 4.43 | 0.70 |
April | 0.258109E+10 | 1465.42 | 13-APR-21:00 | 13.30 | 6.73 | 0.830248E+09 | 569.53 | 14-APR-21:40 | 8.17 | 4.97 |
May | 0.304180E+10 | 1907.23 | 25-MAY-20:55 | 22.80 | 16.44 | 0.913924E+09 | 569.55 | 25-MAY-22:10 | 21.73 | 16.39 |
June | 0.308352E+10 | 2127.47 | 30-JUN-20:10 | 23.77 | 17.76 | 0.896614E+09 | 569.55 | 15-JUN-21:40 | 23.77 | 17.76 |
July | 0.336286E+10 | 2008.26 | 24-JUL-20:05 | 21.32 | 18.93 | 0.943305E+09 | 569.55 | 26-JUL-21:30 | 12.50 | 11.71 |
August | 0.325165E+10 | 1916.92 | 25-AUG-21:00 | 17.80 | 16.38 | 0.940152E+09 | 569.55 | 01-AUG-21:30 | 17.80 | 16.38 |
September | 0.288615E+10 | 1833.93 | 01-SEP-20:10 | 16.42 | 15.15 | 0.879926E+09 | 569.55 | 01-SEP-21:40 | 14.27 | 13.58 |
October | 0.264835E+10 | 1526.53 | 20-OCT-21:00 | 6.10 | 4.28 | 0.856101E+09 | 569.52 | 20-OCT-22:30 | 6.65 | 4.95 |
November | 0.220279E+10 | 1200.55 | 17-NOV-21:00 | 3.30 | -0.9 | 0.768509E+09 | 543.66 | 17-NOV-22:40 | 2.07 | -1.2 |
December | 0.174980E+10 | 1994.73 | 02-DEC-00:22 | -23.8 | -24.0 | 0.704127E+09 | 486.68 | 05-DEC-23:10 | 0.00 | -0.0 |
Annual Sum or Average | 0.307026E+11 | 0.988566E+10 | ||||||||
Minimum of Months | 0.174354E+10 | 1200.55 | -24.4 | -24.6 | 0.675675E+09 | 485.45 | -24.0 | -24.3 | ||
Maximum of Months | 0.336286E+10 | 2645.76 | 23.77 | 18.93 | 0.943305E+09 | 569.55 | 23.77 | 17.76 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.100854E+09 | 658.08 | 19-JAN-21:00 | -3.3 | -3.9 | 0.142713E+09 | 90.52 | 19-JAN-22:10 | -3.9 | -4.6 |
February | 0.344908E+09 | 714.88 | 08-FEB-21:00 | -3.3 | -5.0 | 0.136301E+09 | 94.45 | 22-FEB-22:10 | -6.1 | -7.6 |
March | 0.822354E+09 | 779.16 | 29-MAR-10:33 | 1.13 | -1.2 | 0.153903E+09 | 99.06 | 29-MAR-21:10 | 1.60 | 0.74 |
April | 0.163532E+10 | 918.41 | 18-APR-10:33 | 17.57 | 11.16 | 0.157965E+09 | 108.07 | 14-APR-21:19 | 17.57 | 11.16 |
May | 0.215376E+10 | 1153.43 | 25-MAY-20:55 | 22.80 | 16.44 | 0.183754E+09 | 120.45 | 25-MAY-22:10 | 21.73 | 16.39 |
June | 0.227196E+10 | 1699.08 | 30-JUN-20:00 | 24.40 | 17.93 | 0.185614E+09 | 120.45 | 26-JUN-21:19 | 24.40 | 17.93 |
July | 0.248131E+10 | 1507.13 | 24-JUL-19:55 | 21.70 | 19.11 | 0.197936E+09 | 120.45 | 01-JUL-01:10 | 21.70 | 19.11 |
August | 0.236127E+10 | 1281.08 | 09-AUG-21:00 | 21.10 | 18.81 | 0.195015E+09 | 120.45 | 25-AUG-21:19 | 17.43 | 16.14 |
September | 0.207669E+10 | 1188.22 | 01-SEP-21:00 | 15.00 | 14.30 | 0.178412E+09 | 120.45 | 01-SEP-21:40 | 14.27 | 13.58 |
October | 0.180334E+10 | 985.25 | 22-OCT-10:33 | 15.20 | 11.90 | 0.166806E+09 | 110.76 | 20-OCT-21:10 | 15.20 | 11.90 |
November | 0.108582E+10 | 774.00 | 01-NOV-20:00 | 13.30 | 11.34 | 0.149261E+09 | 99.67 | 01-NOV-21:10 | 12.62 | 11.43 |
December | 0.138155E+09 | 661.49 | 05-DEC-21:00 | 0.00 | -0.0 | 0.147597E+09 | 90.93 | 05-DEC-22:10 | 0.00 | -0.0 |
Annual Sum or Average | 0.172757E+11 | 0.199528E+10 | ||||||||
Minimum of Months | 0.100854E+09 | 658.08 | -3.3 | -5.0 | 0.136301E+09 | 90.52 | -6.1 | -7.6 | ||
Maximum of Months | 0.248131E+10 | 1699.08 | 24.40 | 19.11 | 0.197936E+09 | 120.45 | 24.40 | 19.11 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1820745.98 | 122.72 | 19-JAN-22:00 | -3.9 | -4.6 | 0.107437E+09 | 68.57 | 03-JAN-22:19 | -3.9 | -4.6 |
February | 55162350.80 | 354.63 | 22-FEB-22:00 | -6.1 | -7.6 | 0.104099E+09 | 68.57 | 13-FEB-05:10 | -6.1 | -7.6 |
March | 0.230396E+09 | 425.56 | 28-MAR-20:00 | 4.40 | 0.82 | 0.117186E+09 | 71.80 | 31-MAR-22:10 | 4.43 | 0.70 |
April | 0.790393E+09 | 535.50 | 18-APR-10:33 | 17.57 | 11.16 | 0.117512E+09 | 79.79 | 23-APR-23:10 | 14.63 | 10.70 |
May | 0.122995E+10 | 637.26 | 18-MAY-10:33 | 26.07 | 16.42 | 0.136372E+09 | 90.31 | 25-MAY-22:10 | 21.73 | 16.39 |
June | 0.129922E+10 | 835.09 | 30-JUN-19:20 | 26.67 | 18.68 | 0.138668E+09 | 92.66 | 30-JUN-21:19 | 20.10 | 16.56 |
July | 0.141648E+10 | 689.51 | 23-JUL-10:33 | 27.77 | 23.32 | 0.148260E+09 | 92.66 | 24-JUL-21:19 | 19.23 | 17.76 |
August | 0.135408E+10 | 659.39 | 26-AUG-10:33 | 22.43 | 17.42 | 0.145280E+09 | 91.18 | 09-AUG-22:10 | 22.43 | 17.42 |
September | 0.117920E+10 | 650.45 | 01-SEP-10:33 | 22.77 | 18.04 | 0.131794E+09 | 89.76 | 01-SEP-21:30 | 14.45 | 13.76 |
October | 0.929778E+09 | 572.17 | 22-OCT-10:33 | 15.20 | 11.90 | 0.123007E+09 | 80.46 | 20-OCT-21:40 | 15.20 | 11.90 |
November | 0.333334E+09 | 429.62 | 01-NOV-20:00 | 13.30 | 11.34 | 0.113140E+09 | 73.06 | 01-NOV-22:10 | 11.52 | 10.61 |
December | 3948340.55 | 175.95 | 05-DEC-22:00 | 0.00 | -0.0 | 0.111748E+09 | 68.58 | 13-DEC-04:19 | -23.7 | -24.0 |
Annual Sum or Average | 0.882376E+10 | 0.149450E+10 | ||||||||
Minimum of Months | 1820745.98 | 122.72 | -6.1 | -7.6 | 0.104099E+09 | 68.57 | -23.7 | -24.0 | ||
Maximum of Months | 0.141648E+10 | 835.09 | 27.77 | 23.32 | 0.148260E+09 | 92.66 | 22.43 | 17.76 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.471074E+11 | 41178.81 | 25-JAN-20:01 | -24.0 | -24.2 | 0.484110E+09 | 381.60 | 23-JAN-22:10 | -24.0 | -24.2 |
February | 0.429574E+11 | 39364.57 | 13-FEB-21:22 | -23.9 | -24.3 | 0.493573E+09 | 381.58 | 17-FEB-22:10 | -10.5 | -11.2 |
March | 0.484511E+11 | 37271.80 | 31-MAR-20:00 | 5.60 | 1.28 | 0.580287E+09 | 381.60 | 29-MAR-21:10 | 5.60 | 1.28 |
April | 0.483299E+11 | 37961.78 | 13-APR-19:55 | 14.40 | 6.82 | 0.577480E+09 | 381.66 | 13-APR-21:10 | 13.03 | 6.68 |
May | 0.518049E+11 | 38669.93 | 18-MAY-20:00 | 21.10 | 14.14 | 0.601768E+09 | 381.64 | 18-MAY-21:10 | 17.77 | 12.61 |
June | 0.508380E+11 | 38867.73 | 28-JUN-20:00 | 25.00 | 19.70 | 0.583520E+09 | 381.73 | 08-JUN-21:10 | 25.00 | 19.70 |
July | 0.527358E+11 | 38747.12 | 21-JUL-20:00 | 22.20 | 20.61 | 0.602731E+09 | 381.70 | 18-JUL-21:19 | 22.20 | 20.61 |
August | 0.525088E+11 | 38642.74 | 08-AUG-20:00 | 25.00 | 20.33 | 0.603364E+09 | 381.71 | 25-AUG-21:19 | 17.43 | 16.14 |
September | 0.496950E+11 | 38494.05 | 01-SEP-20:00 | 16.70 | 15.32 | 0.581515E+09 | 381.71 | 18-SEP-21:19 | 16.10 | 15.51 |
October | 0.499005E+11 | 37965.84 | 19-OCT-20:00 | 13.30 | 10.24 | 0.597321E+09 | 381.72 | 25-OCT-21:10 | 6.70 | 5.12 |
November | 0.468412E+11 | 37282.12 | 01-NOV-20:00 | 13.30 | 11.34 | 0.573018E+09 | 381.63 | 01-NOV-21:10 | 12.62 | 11.43 |
December | 0.470136E+11 | 39654.82 | 23-DEC-21:42 | -23.9 | -24.3 | 0.509134E+09 | 381.60 | 04-DEC-22:10 | -23.9 | -24.3 |
Annual Sum or Average | 0.588184E+12 | 0.678782E+10 | ||||||||
Minimum of Months | 0.429574E+11 | 37271.80 | -24.0 | -24.3 | 0.484110E+09 | 381.58 | -24.0 | -24.3 | ||
Maximum of Months | 0.527358E+11 | 41178.81 | 25.00 | 20.61 | 0.603364E+09 | 381.73 | 25.00 | 20.61 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.125616E+11 | 10205.21 | 27-JAN-13:30 | -15.0 | -16.1 | 0.753769E+10 | 5330.63 | 19-JAN-22:40 | -15.0 | -16.1 |
February | 0.141936E+11 | 13973.99 | 28-FEB-13:20 | 2.77 | -0.9 | 0.759323E+10 | 6106.64 | 28-FEB-22:40 | -0.4 | -3.3 |
March | 0.168989E+11 | 15751.46 | 07-MAR-00:41 | -23.8 | -24.0 | 0.896569E+10 | 6221.12 | 31-MAR-21:40 | 4.67 | 0.78 |
April | 0.192386E+11 | 14605.10 | 22-APR-13:10 | 16.38 | 6.81 | 0.921985E+10 | 6460.66 | 13-APR-22:30 | 16.38 | 6.81 |
May | 0.222967E+11 | 13402.01 | 06-MAY-13:00 | 15.30 | 7.47 | 0.101035E+11 | 6462.76 | 24-MAY-22:10 | 18.07 | 13.07 |
June | 0.222788E+11 | 12890.14 | 30-JUN-15:03 | 32.12 | 24.53 | 0.994899E+10 | 6462.77 | 15-JUN-21:40 | 32.12 | 24.53 |
July | 0.242322E+11 | 14203.37 | 29-JUL-13:00 | 28.90 | 20.61 | 0.104738E+11 | 6462.77 | 06-JUL-22:10 | 28.90 | 20.61 |
August | 0.239837E+11 | 15633.14 | 26-AUG-12:40 | 25.40 | 19.23 | 0.104711E+11 | 6462.77 | 01-AUG-21:30 | 25.40 | 19.23 |
September | 0.216667E+11 | 15187.86 | 01-SEP-13:15 | 24.80 | 18.00 | 0.972972E+10 | 6462.70 | 01-SEP-21:40 | 14.27 | 13.58 |
October | 0.192847E+11 | 18167.63 | 22-OCT-12:00 | 16.70 | 12.57 | 0.942440E+10 | 6461.54 | 19-OCT-23:19 | 16.70 | 12.57 |
November | 0.148578E+11 | 13168.89 | 17-NOV-12:40 | 9.63 | 3.12 | 0.850112E+10 | 6142.75 | 17-NOV-22:40 | 2.07 | -1.2 |
December | 0.116003E+11 | 11493.65 | 10-DEC-12:22 | -23.6 | -24.1 | 0.775049E+10 | 5385.86 | 05-DEC-22:40 | -23.6 | -24.1 |
Annual Sum or Average | 0.223094E+12 | 0.109720E+12 | ||||||||
Minimum of Months | 0.116003E+11 | 10205.21 | -23.8 | -24.1 | 0.753769E+10 | 5330.63 | -23.6 | -24.1 | ||
Maximum of Months | 0.242322E+11 | 18167.63 | 32.12 | 24.53 | 0.104738E+11 | 6462.77 | 32.12 | 24.53 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.493783E+11 | 60138.00 | 25-JAN-20:01 | -24.0 | -24.2 | 0.238383E+11 | 17455.62 | 19-JAN-23:10 | -24.0 | -24.2 |
February | 0.483699E+11 | 58504.01 | 24-FEB-22:52 | -23.9 | -24.3 | 0.240024E+11 | 18826.13 | 22-FEB-22:49 | -23.9 | -24.3 |
March | 0.562294E+11 | 59650.33 | 07-MAR-00:51 | -24.4 | -24.6 | 0.283037E+11 | 19183.02 | 31-MAR-21:49 | 4.58 | 0.73 |
April | 0.606158E+11 | 33849.01 | 13-APR-21:10 | 13.03 | 6.68 | 0.291202E+11 | 19184.77 | 18-APR-23:19 | 4.43 | 0.42 |
May | 0.699511E+11 | 38861.57 | 25-MAY-21:10 | 22.65 | 16.44 | 0.315072E+11 | 19186.20 | 24-MAY-22:10 | 22.65 | 16.44 |
June | 0.707498E+11 | 41179.65 | 29-JUN-21:10 | 27.62 | 23.70 | 0.308053E+11 | 19186.23 | 15-JUN-21:40 | 27.62 | 23.70 |
July | 0.763988E+11 | 40150.31 | 24-JUL-21:10 | 19.32 | 17.84 | 0.320519E+11 | 19186.24 | 06-JUL-22:10 | 19.32 | 17.84 |
August | 0.748692E+11 | 39388.15 | 25-AUG-21:10 | 17.62 | 16.26 | 0.321351E+11 | 19186.23 | 01-AUG-21:30 | 17.62 | 16.26 |
September | 0.672783E+11 | 38739.86 | 01-SEP-21:10 | 14.82 | 14.12 | 0.305471E+11 | 19186.10 | 01-SEP-21:40 | 14.27 | 13.58 |
October | 0.625401E+11 | 35770.19 | 19-OCT-21:10 | 12.70 | 9.80 | 0.301402E+11 | 19185.19 | 21-OCT-01:19 | 5.20 | 4.04 |
November | 0.533458E+11 | 27680.54 | 17-NOV-21:00 | 3.30 | -0.9 | 0.273706E+11 | 19183.14 | 17-NOV-22:49 | 1.88 | -1.3 |
December | 0.482873E+11 | 57881.55 | 02-DEC-00:31 | -23.9 | -24.2 | 0.247748E+11 | 17524.00 | 05-DEC-23:10 | 0.00 | -0.0 |
Annual Sum or Average | 0.738014E+12 | 0.344597E+12 | ||||||||
Minimum of Months | 0.482873E+11 | 27680.54 | -24.4 | -24.6 | 0.238383E+11 | 17455.62 | -24.0 | -24.3 | ||
Maximum of Months | 0.763988E+11 | 60138.00 | 27.62 | 23.70 | 0.321351E+11 | 19186.24 | 27.62 | 23.70 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5776133.12 | 3993.61 | 27-JAN-16:01 | -14.8 | -15.9 | 92614975.46 | 56.69 | 14-JAN-05:10 | -14.8 | -15.9 |
February | 67596387.25 | 4297.37 | 28-FEB-16:01 | 6.02 | 1.46 | 85039686.27 | 56.69 | 03-FEB-04:19 | 6.02 | 1.46 |
March | 0.225673E+09 | 4334.61 | 31-MAR-15:01 | 8.40 | 2.82 | 95262118.18 | 56.69 | 07-MAR-05:30 | 8.40 | 2.82 |
April | 0.703991E+09 | 4418.87 | 13-APR-15:01 | 20.00 | 8.11 | 93920670.89 | 56.69 | 13-APR-22:00 | 10.60 | 6.30 |
May | 0.172487E+10 | 4427.85 | 14-MAY-18:01 | 19.63 | 8.56 | 98797322.44 | 56.70 | 26-MAY-21:19 | 17.07 | 14.16 |
June | 0.199973E+10 | 3847.56 | 12-JUN-15:01 | 17.98 | 14.52 | 95747799.44 | 56.70 | 30-JUN-01:00 | 26.70 | 23.80 |
July | 0.249920E+10 | 3797.44 | 25-JUL-15:01 | 20.82 | 19.48 | 99000516.00 | 56.70 | 03-JUL-22:40 | 20.82 | 19.48 |
August | 0.204064E+10 | 3758.83 | 29-AUG-18:02 | 23.03 | 19.85 | 98899778.32 | 56.70 | 01-AUG-22:10 | 23.03 | 19.85 |
September | 0.114998E+10 | 4368.76 | 09-SEP-18:01 | 15.37 | 9.79 | 95080359.42 | 56.69 | 01-SEP-21:30 | 15.37 | 9.79 |
October | 0.384781E+09 | 4226.80 | 21-OCT-18:01 | 14.35 | 8.39 | 96188222.51 | 56.69 | 19-OCT-23:30 | 14.35 | 8.39 |
November | 27505436.34 | 4226.41 | 17-NOV-16:01 | 9.45 | 2.90 | 91112104.87 | 56.69 | 07-NOV-04:19 | 9.45 | 2.90 |
December | 2341612.75 | 348.42 | 28-DEC-16:05 | -2.2 | -3.9 | 92473534.56 | 56.69 | 15-DEC-04:19 | -2.2 | -3.9 |
Annual Sum or Average | 0.108321E+11 | 0.113414E+10 | ||||||||
Minimum of Months | 2341612.75 | 348.42 | -14.8 | -15.9 | 85039686.27 | 56.69 | -14.8 | -15.9 | ||
Maximum of Months | 0.249920E+10 | 4427.85 | 23.03 | 19.85 | 99000516.00 | 56.70 | 26.70 | 23.80 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 128549.08 | 566.69 | 27-JAN-16:04 | -14.8 | -15.9 | 91941368.29 | 56.69 | 07-JAN-04:40 | -14.8 | -15.9 |
February | 14563347.66 | 3960.94 | 28-FEB-16:01 | 6.02 | 1.46 | 83905551.89 | 56.69 | 26-FEB-02:20 | 6.02 | 1.46 |
March | 98721978.87 | 4069.42 | 31-MAR-15:01 | 8.40 | 2.82 | 93959400.21 | 56.69 | 07-MAR-05:30 | 8.40 | 2.82 |
April | 0.403556E+09 | 4848.04 | 11-APR-18:11 | 13.90 | 5.53 | 94369262.13 | 77.05 | 17-APR-18:10 | 15.63 | 7.70 |
May | 0.127356E+10 | 5227.37 | 06-MAY-18:42 | 14.68 | 6.91 | 0.105634E+09 | 92.36 | 04-MAY-18:10 | 14.68 | 6.91 |
June | 0.154417E+10 | 4231.39 | 07-JUN-21:41 | 13.27 | 10.80 | 0.106029E+09 | 94.45 | 15-JUN-18:10 | 21.23 | 13.09 |
July | 0.190461E+10 | 4272.84 | 04-JUL-16:51 | 25.00 | 20.01 | 0.111047E+09 | 102.27 | 06-JUL-18:10 | 23.12 | 15.53 |
August | 0.141140E+10 | 4260.80 | 07-AUG-16:21 | 24.15 | 19.94 | 0.109236E+09 | 97.38 | 02-AUG-18:10 | 24.15 | 19.94 |
September | 0.677588E+09 | 4598.16 | 23-SEP-17:41 | 13.68 | 8.37 | 98765306.30 | 86.78 | 05-SEP-18:10 | 13.68 | 8.37 |
October | 0.152360E+09 | 3887.10 | 21-OCT-18:32 | 12.40 | 7.64 | 95865633.80 | 56.69 | 19-OCT-21:19 | 12.40 | 7.64 |
November | 8288948.75 | 3272.53 | 17-NOV-16:01 | 9.45 | 2.90 | 90191058.62 | 56.69 | 26-NOV-02:20 | -12.0 | -12.5 |
December | 49019.51 | 244.72 | 05-DEC-19:06 | 0.00 | -0.0 | 92184152.32 | 56.69 | 05-DEC-04:19 | 0.00 | -0.0 |
Annual Sum or Average | 0.748900E+10 | 0.117313E+10 | ||||||||
Minimum of Months | 49019.51 | 244.72 | -14.8 | -15.9 | 83905551.89 | 56.69 | -14.8 | -15.9 | ||
Maximum of Months | 0.190461E+10 | 5227.37 | 25.00 | 20.01 | 0.111047E+09 | 102.27 | 24.15 | 19.94 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5277212.29 | 235.06 | 04-JAN-15:03 | -27.7 | -28.0 | 0.00 | 0.00 | 01-JAN-00:10 | -27.7 | -28.0 |
February | 14147874.49 | 300.08 | 28-FEB-14:35 | 5.37 | 1.09 | 0.00 | 0.00 | 01-FEB-00:10 | 5.37 | 1.09 |
March | 84162033.90 | 599.44 | 20-MAR-12:30 | 1.70 | -1.1 | 0.00 | 0.00 | 01-MAR-00:10 | 1.70 | -1.1 |
April | 0.263086E+09 | 671.76 | 13-APR-13:00 | 17.80 | 6.75 | 0.00 | 0.00 | 01-APR-00:10 | 17.80 | 6.75 |
May | 0.474343E+09 | 629.05 | 18-MAY-13:05 | 28.25 | 16.75 | 0.00 | 0.00 | 01-MAY-00:10 | 28.25 | 16.75 |
June | 0.516020E+09 | 612.63 | 30-JUN-13:00 | 31.70 | 24.46 | 0.00 | 0.00 | 01-JUN-00:10 | 31.70 | 24.46 |
July | 0.650889E+09 | 657.23 | 23-JUL-13:20 | 30.00 | 22.71 | 0.00 | 0.00 | 01-JUL-00:10 | 30.00 | 22.71 |
August | 0.618082E+09 | 732.88 | 25-AUG-13:05 | 27.38 | 18.58 | 0.00 | 0.00 | 01-AUG-00:10 | 27.38 | 18.58 |
September | 0.458563E+09 | 746.14 | 01-SEP-13:05 | 24.60 | 17.97 | 0.00 | 0.00 | 01-SEP-00:10 | 24.60 | 17.97 |
October | 0.241164E+09 | 909.20 | 22-OCT-12:30 | 17.50 | 12.84 | 0.00 | 0.00 | 01-OCT-00:10 | 17.50 | 12.84 |
November | 32536933.82 | 530.17 | 17-NOV-12:20 | 9.27 | 3.02 | 0.00 | 0.00 | 01-NOV-00:10 | 9.27 | 3.02 |
December | 2287158.05 | 95.04 | 02-DEC-15:20 | -17.6 | -18.4 | 0.00 | 0.00 | 01-DEC-00:10 | -17.6 | -18.4 |
Annual Sum or Average | 0.336056E+10 | 0.00 | ||||||||
Minimum of Months | 2287158.05 | 95.04 | -27.7 | -28.0 | 0.00 | 0.00 | -27.7 | -28.0 | ||
Maximum of Months | 0.650889E+09 | 909.20 | 31.70 | 24.46 | 0.00 | 0.00 | 31.70 | 24.46 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2805594.52 | 232.87 | 20-JAN-19:05 | -11.4 | -11.8 | 91672025.32 | 56.69 | 10-JAN-04:19 | -11.4 | -11.8 |
February | 9428642.70 | 605.32 | 05-FEB-09:01 | -2.2 | -3.2 | 84715493.59 | 56.69 | 03-FEB-04:19 | -2.2 | -3.2 |
March | 40766816.78 | 1105.66 | 28-MAR-18:01 | 6.93 | 2.56 | 94810083.59 | 56.69 | 07-MAR-05:30 | 6.93 | 2.56 |
April | 0.206857E+09 | 1175.01 | 13-APR-19:41 | 14.60 | 6.84 | 93564715.49 | 56.69 | 14-APR-21:30 | 8.35 | 5.00 |
May | 0.552307E+09 | 1258.90 | 21-MAY-21:01 | 13.12 | 7.18 | 0.101309E+09 | 77.19 | 26-MAY-21:49 | 16.87 | 14.10 |
June | 0.669703E+09 | 1248.52 | 07-JUN-08:51 | 21.10 | 11.94 | 0.100833E+09 | 79.95 | 15-JUN-21:10 | 14.22 | 10.92 |
July | 0.732006E+09 | 1204.43 | 01-JUL-21:01 | 12.93 | 11.86 | 0.105013E+09 | 80.59 | 26-JUL-21:10 | 13.03 | 11.94 |
August | 0.602793E+09 | 1149.80 | 01-AUG-21:11 | 15.37 | 12.90 | 0.104072E+09 | 78.12 | 04-AUG-21:10 | 14.45 | 11.90 |
September | 0.412365E+09 | 1243.23 | 04-SEP-18:01 | 14.03 | 8.92 | 96040821.17 | 75.42 | 01-SEP-21:10 | 14.03 | 8.92 |
October | 0.201366E+09 | 1122.98 | 20-OCT-18:11 | 12.23 | 7.41 | 96381922.00 | 56.69 | 02-OCT-21:10 | 12.23 | 7.41 |
November | 45045618.50 | 947.65 | 21-NOV-19:02 | 2.02 | 0.66 | 91767845.01 | 56.69 | 01-NOV-21:30 | 2.02 | 0.66 |
December | 3766879.63 | 272.54 | 05-DEC-19:03 | 0.00 | -0.0 | 92666451.52 | 56.69 | 15-DEC-04:19 | -14.2 | -15.1 |
Annual Sum or Average | 0.347921E+10 | 0.115285E+10 | ||||||||
Minimum of Months | 2805594.52 | 232.87 | -11.4 | -11.8 | 84715493.59 | 56.69 | -14.2 | -15.1 | ||
Maximum of Months | 0.732006E+09 | 1258.90 | 21.10 | 12.90 | 0.105013E+09 | 80.59 | 16.87 | 14.10 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3682581.82 | 543.98 | 17-JAN-16:04 | -4.2 | -5.3 | 92409429.87 | 56.69 | 14-JAN-05:10 | -4.2 | -5.3 |
February | 48898552.62 | 3872.74 | 28-FEB-16:01 | 6.02 | 1.46 | 85081954.78 | 56.69 | 24-FEB-04:19 | 6.02 | 1.46 |
March | 0.189318E+09 | 3930.82 | 11-MAR-09:01 | -9.4 | -9.9 | 95573411.66 | 56.69 | 07-MAR-05:30 | -9.4 | -9.9 |
April | 0.734978E+09 | 4012.50 | 22-APR-08:62 | 8.77 | 2.60 | 94373978.13 | 56.69 | 13-APR-22:40 | 8.77 | 2.60 |
May | 0.163411E+10 | 3997.54 | 14-MAY-15:01 | 20.00 | 8.26 | 98993926.48 | 56.70 | 25-MAY-21:00 | 21.90 | 16.42 |
June | 0.212440E+10 | 3988.47 | 01-JUN-18:01 | 20.73 | 11.87 | 95888717.68 | 56.70 | 26-JUN-21:40 | 17.77 | 16.68 |
July | 0.249815E+10 | 3620.47 | 29-JUL-08:61 | 24.18 | 20.45 | 99079143.07 | 56.70 | 14-JUL-21:40 | 24.18 | 20.45 |
August | 0.196991E+10 | 3537.72 | 24-AUG-08:62 | 18.77 | 17.13 | 99015111.96 | 56.70 | 22-AUG-21:30 | 18.77 | 17.13 |
September | 0.112427E+10 | 3932.89 | 09-SEP-18:01 | 15.37 | 9.79 | 95151549.65 | 56.70 | 01-SEP-21:19 | 15.37 | 9.79 |
October | 0.351947E+09 | 3892.65 | 21-OCT-18:01 | 14.35 | 8.39 | 96211285.02 | 56.69 | 19-OCT-22:19 | 14.35 | 8.39 |
November | 43174600.84 | 3748.21 | 17-NOV-16:01 | 9.45 | 2.90 | 91045135.82 | 56.69 | 26-NOV-02:20 | -12.0 | -12.5 |
December | 2532378.37 | 691.09 | 01-DEC-09:03 | -21.5 | -21.7 | 92418669.23 | 56.69 | 22-DEC-04:19 | -15.3 | -15.8 |
Annual Sum or Average | 0.107254E+11 | 0.113524E+10 | ||||||||
Minimum of Months | 2532378.37 | 543.98 | -21.5 | -21.7 | 85081954.78 | 56.69 | -15.3 | -15.8 | ||
Maximum of Months | 0.249815E+10 | 4012.50 | 24.18 | 20.45 | 99079143.07 | 56.70 | 24.18 | 20.45 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 36162.47 | 227.67 | 19-JAN-19:06 | -3.3 | -3.9 | 91699172.26 | 56.69 | 10-JAN-04:19 | -3.3 | -3.9 |
February | 6325184.34 | 1375.62 | 27-FEB-09:02 | -15.7 | -16.5 | 83822229.82 | 56.69 | 28-FEB-04:19 | -15.6 | -16.0 |
March | 63678654.12 | 3597.07 | 11-MAR-09:01 | -9.4 | -9.9 | 94152522.06 | 56.69 | 07-MAR-05:40 | -9.4 | -9.9 |
April | 0.432142E+09 | 3845.47 | 22-APR-19:21 | 13.05 | 5.48 | 94252195.48 | 56.69 | 12-APR-21:19 | 13.05 | 5.48 |
May | 0.124206E+10 | 3998.91 | 06-MAY-19:01 | 14.13 | 6.69 | 0.103129E+09 | 77.46 | 18-MAY-21:40 | 17.67 | 12.46 |
June | 0.169738E+10 | 4229.12 | 28-JUN-07:52 | 25.00 | 20.32 | 0.103646E+09 | 81.63 | 07-JUN-21:19 | 25.00 | 20.32 |
July | 0.191492E+10 | 4307.35 | 31-JUL-08:32 | 18.70 | 13.63 | 0.108835E+09 | 82.13 | 26-JUL-21:10 | 18.70 | 13.63 |
August | 0.139661E+10 | 4013.90 | 11-AUG-08:51 | 20.00 | 17.15 | 0.106381E+09 | 78.70 | 04-AUG-21:10 | 20.00 | 17.15 |
September | 0.706900E+09 | 4026.72 | 04-SEP-18:01 | 14.03 | 8.92 | 97033486.87 | 76.14 | 01-SEP-21:10 | 14.03 | 8.92 |
October | 0.130231E+09 | 3289.01 | 21-OCT-18:32 | 12.40 | 7.64 | 95639473.43 | 56.69 | 22-OCT-04:10 | 10.78 | 9.49 |
November | 11064986.02 | 1719.94 | 16-NOV-09:01 | -0.2 | -1.8 | 90148801.20 | 56.69 | 24-NOV-04:19 | -10.9 | -11.5 |
December | 53760.33 | 226.71 | 05-DEC-19:06 | 0.00 | -0.0 | 92132326.48 | 56.69 | 15-DEC-04:19 | -14.2 | -15.1 |
Annual Sum or Average | 0.760139E+10 | 0.116087E+10 | ||||||||
Minimum of Months | 36162.47 | 226.71 | -15.7 | -16.5 | 83822229.82 | 56.69 | -15.6 | -16.0 | ||
Maximum of Months | 0.191492E+10 | 4307.35 | 25.00 | 20.32 | 0.108835E+09 | 82.13 | 25.00 | 20.32 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.100032E+10 | 1960.55 | 26-JAN-07:00 | -33.3 | -33.4 | 0.113782E+10 | 704.46 | 11-JAN-04:00 | -33.3 | -33.4 |
February | 0.132757E+10 | 1988.53 | 14-FEB-07:00 | -33.3 | -33.4 | 0.107260E+10 | 723.03 | 22-FEB-22:40 | -6.1 | -7.8 |
March | 0.228937E+10 | 1833.14 | 20-MAR-10:33 | 0.03 | -2.1 | 0.121101E+10 | 754.58 | 31-MAR-21:40 | 4.67 | 0.78 |
April | 0.372922E+10 | 2232.24 | 22-APR-10:33 | 14.43 | 5.29 | 0.123586E+10 | 839.00 | 23-APR-23:19 | 14.27 | 10.45 |
May | 0.490575E+10 | 2512.01 | 18-MAY-10:33 | 26.07 | 16.42 | 0.141978E+10 | 917.33 | 25-MAY-21:49 | 22.05 | 16.43 |
June | 0.510091E+10 | 3014.35 | 30-JUN-19:20 | 26.67 | 18.68 | 0.143225E+10 | 951.85 | 30-JUN-22:10 | 18.85 | 15.86 |
July | 0.559104E+10 | 2688.19 | 01-JUL-10:33 | 21.50 | 16.30 | 0.153504E+10 | 951.85 | 24-JUL-22:10 | 18.43 | 17.18 |
August | 0.528647E+10 | 2602.77 | 26-AUG-10:33 | 22.43 | 17.42 | 0.149147E+10 | 928.61 | 01-AUG-21:30 | 22.43 | 17.42 |
September | 0.455831E+10 | 2519.58 | 01-SEP-10:33 | 22.77 | 18.04 | 0.134369E+10 | 913.53 | 01-SEP-21:30 | 14.45 | 13.76 |
October | 0.349898E+10 | 2256.20 | 22-OCT-10:33 | 15.20 | 11.90 | 0.125289E+10 | 820.62 | 22-OCT-23:19 | 6.50 | 5.21 |
November | 0.178730E+10 | 1714.08 | 17-NOV-11:33 | 8.17 | 2.57 | 0.116128E+10 | 732.36 | 17-NOV-22:40 | 2.07 | -1.2 |
December | 0.783131E+09 | 1634.11 | 24-DEC-23:53 | -31.1 | -31.3 | 0.116172E+10 | 704.53 | 14-DEC-05:30 | -31.1 | -31.3 |
Annual Sum or Average | 0.398584E+11 | 0.154554E+11 | ||||||||
Minimum of Months | 0.783131E+09 | 1634.11 | -33.3 | -33.4 | 0.107260E+10 | 704.46 | -33.3 | -33.4 | ||
Maximum of Months | 0.559104E+10 | 3014.35 | 26.67 | 18.68 | 0.153504E+10 | 951.85 | 22.43 | 17.42 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2788505.23 | 3457.67 | 27-JAN-16:01 | -14.8 | -15.9 | 92333518.42 | 56.69 | 14-JAN-05:10 | -14.8 | -15.9 |
February | 62773330.84 | 4456.88 | 28-FEB-16:01 | 6.02 | 1.46 | 84574120.90 | 56.69 | 10-FEB-04:19 | 6.02 | 1.46 |
March | 0.222746E+09 | 4495.77 | 19-MAR-15:01 | 4.50 | 1.41 | 94795328.21 | 56.69 | 07-MAR-05:30 | 4.50 | 1.41 |
April | 0.688757E+09 | 4591.61 | 13-APR-15:01 | 20.00 | 8.11 | 93525171.43 | 56.69 | 13-APR-22:19 | 11.33 | 6.36 |
May | 0.171291E+10 | 4608.60 | 14-MAY-18:01 | 19.63 | 8.56 | 98677638.37 | 56.70 | 25-MAY-22:00 | 20.90 | 16.25 |
June | 0.200254E+10 | 4584.30 | 16-JUN-18:01 | 20.50 | 11.25 | 95660451.83 | 56.70 | 28-JUN-22:49 | 22.20 | 18.56 |
July | 0.249740E+10 | 3936.12 | 30-JUL-18:01 | 23.80 | 20.38 | 98930016.47 | 56.70 | 13-JUL-21:00 | 23.80 | 20.38 |
August | 0.200543E+10 | 3928.44 | 30-AUG-18:01 | 23.53 | 19.54 | 98777749.58 | 56.70 | 11-AUG-21:00 | 23.53 | 19.54 |
September | 0.105495E+10 | 4571.38 | 04-SEP-18:01 | 14.03 | 8.92 | 94848260.28 | 56.69 | 01-SEP-21:10 | 14.03 | 8.92 |
October | 0.343736E+09 | 4375.50 | 21-OCT-18:01 | 14.35 | 8.39 | 95688898.67 | 56.69 | 19-OCT-21:00 | 14.35 | 8.39 |
November | 20064061.62 | 4380.83 | 17-NOV-16:01 | 9.45 | 2.90 | 90571986.06 | 56.69 | 01-NOV-04:19 | 9.45 | 2.90 |
December | 904654.87 | 428.69 | 28-DEC-16:05 | -2.2 | -3.9 | 92292535.49 | 56.69 | 08-DEC-04:19 | -2.2 | -3.9 |
Annual Sum or Average | 0.106150E+11 | 0.113068E+10 | ||||||||
Minimum of Months | 904654.87 | 428.69 | -14.8 | -15.9 | 84574120.90 | 56.69 | -14.8 | -15.9 | ||
Maximum of Months | 0.249740E+10 | 4608.60 | 23.80 | 20.38 | 98930016.47 | 56.70 | 23.80 | 20.38 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 130593.28 | 799.02 | 20-JAN-16:04 | -5.9 | -7.4 | 91754104.52 | 56.69 | 07-JAN-04:40 | -5.9 | -7.4 |
February | 10206767.00 | 3887.23 | 28-FEB-16:01 | 6.02 | 1.46 | 83658081.20 | 56.69 | 01-FEB-04:19 | 6.02 | 1.46 |
March | 90990300.50 | 4203.04 | 31-MAR-18:01 | 7.93 | 2.65 | 93589877.70 | 56.69 | 07-MAR-05:30 | 7.93 | 2.65 |
April | 0.387390E+09 | 5062.07 | 11-APR-18:11 | 13.90 | 5.53 | 94161678.71 | 81.97 | 17-APR-18:10 | 15.63 | 7.70 |
May | 0.127830E+10 | 5466.05 | 06-MAY-18:42 | 14.68 | 6.91 | 0.106542E+09 | 100.65 | 04-MAY-18:10 | 14.68 | 6.91 |
June | 0.159063E+10 | 4416.21 | 07-JUN-21:41 | 13.27 | 10.80 | 0.107249E+09 | 103.06 | 20-JUN-21:10 | 16.65 | 12.83 |
July | 0.196313E+10 | 4595.69 | 26-JUL-20:52 | 13.30 | 12.05 | 0.112103E+09 | 113.00 | 06-JUL-20:10 | 13.30 | 12.05 |
August | 0.141836E+10 | 4687.88 | 02-AUG-20:02 | 13.62 | 11.96 | 0.110292E+09 | 103.82 | 02-AUG-18:10 | 13.62 | 11.96 |
September | 0.587414E+09 | 5034.47 | 04-SEP-18:01 | 14.03 | 8.92 | 98952775.82 | 93.77 | 05-SEP-18:10 | 14.77 | 9.16 |
October | 0.116741E+09 | 4024.40 | 21-OCT-18:32 | 12.40 | 7.64 | 95338055.82 | 57.26 | 20-OCT-18:10 | 12.40 | 7.64 |
November | 4943897.29 | 2019.86 | 17-NOV-16:01 | 9.45 | 2.90 | 89767127.69 | 56.69 | 01-NOV-04:19 | 9.45 | 2.90 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -8.8 | -9.9 | 92080657.49 | 56.69 | 22-DEC-04:19 | -15.3 | -15.8 |
Annual Sum or Average | 0.744824E+10 | 0.117549E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | -8.8 | -9.9 | 83658081.20 | 56.69 | -15.3 | -15.8 | ||
Maximum of Months | 0.196313E+10 | 5466.05 | 14.68 | 12.05 | 0.112103E+09 | 113.00 | 16.65 | 12.83 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.101920E+09 | 2608.94 | 05-JAN-16:01 | -26.9 | -27.2 | 94395134.27 | 56.69 | 07-JAN-04:30 | -23.4 | -23.7 |
February | 0.239766E+09 | 2514.85 | 28-FEB-16:01 | 6.02 | 1.46 | 86670430.94 | 56.69 | 21-FEB-00:20 | 6.02 | 1.46 |
March | 0.321091E+09 | 2529.26 | 17-MAR-15:01 | -2.1 | -5.6 | 96472974.50 | 56.69 | 29-MAR-21:19 | 1.50 | 0.53 |
April | 0.566285E+09 | 2558.76 | 13-APR-15:01 | 20.00 | 8.11 | 94384503.80 | 56.69 | 13-APR-21:40 | 12.23 | 6.51 |
May | 0.978107E+09 | 2528.86 | 14-MAY-15:01 | 20.00 | 8.26 | 98783585.13 | 56.69 | 24-MAY-21:00 | 18.20 | 13.12 |
June | 0.109010E+10 | 2497.13 | 16-JUN-18:01 | 20.50 | 11.25 | 95656045.24 | 56.70 | 26-JUN-21:49 | 17.48 | 16.57 |
July | 0.134873E+10 | 2206.12 | 04-JUL-18:01 | 22.62 | 19.34 | 98886580.44 | 56.70 | 12-JUL-21:30 | 20.85 | 17.42 |
August | 0.125234E+10 | 2193.30 | 30-AUG-18:01 | 23.53 | 19.54 | 98821384.97 | 56.70 | 29-AUG-21:30 | 23.53 | 19.54 |
September | 0.889199E+09 | 2467.17 | 05-SEP-18:01 | 14.77 | 9.16 | 95217535.38 | 56.70 | 01-SEP-22:10 | 14.77 | 9.16 |
October | 0.495622E+09 | 2465.06 | 21-OCT-18:01 | 14.35 | 8.39 | 96898450.83 | 56.69 | 19-OCT-21:40 | 14.35 | 8.39 |
November | 0.160407E+09 | 2467.38 | 10-NOV-16:01 | -2.2 | -4.9 | 92347464.53 | 56.69 | 01-NOV-21:10 | -2.2 | -4.9 |
December | 60836467.07 | 2444.06 | 02-DEC-16:01 | -18.7 | -19.4 | 93840969.45 | 56.69 | 22-DEC-00:20 | -14.6 | -15.3 |
Annual Sum or Average | 0.750440E+10 | 0.114238E+10 | ||||||||
Minimum of Months | 60836467.07 | 2193.30 | -26.9 | -27.2 | 86670430.94 | 56.69 | -23.4 | -23.7 | ||
Maximum of Months | 0.134873E+10 | 2608.94 | 23.53 | 19.54 | 98886580.44 | 56.70 | 23.53 | 19.54 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.281250E+11 | 26674.63 | 25-JAN-20:01 | -24.0 | -24.2 | 0.164056E+11 | 11347.87 | 17-JAN-00:20 | -24.0 | -24.2 |
February | 0.258609E+11 | 25682.63 | 24-FEB-22:52 | -23.9 | -24.3 | 0.161570E+11 | 11347.89 | 28-FEB-00:20 | -15.3 | -15.9 |
March | 0.303456E+11 | 25963.64 | 12-MAR-03:51 | -23.9 | -24.1 | 0.187414E+11 | 11347.92 | 12-MAR-23:19 | -12.0 | -13.6 |
April | 0.329450E+11 | 19790.27 | 13-APR-21:10 | 13.03 | 6.68 | 0.185457E+11 | 11347.92 | 02-APR-23:19 | 13.03 | 6.68 |
May | 0.394404E+11 | 22364.92 | 25-MAY-21:10 | 22.65 | 16.44 | 0.193154E+11 | 11352.85 | 18-MAY-21:19 | 22.65 | 16.44 |
June | 0.404574E+11 | 23154.88 | 29-JUN-21:20 | 27.43 | 23.63 | 0.187473E+11 | 11359.94 | 30-JUN-21:19 | 20.10 | 16.56 |
July | 0.427557E+11 | 22631.01 | 21-JUL-21:52 | 21.70 | 20.13 | 0.193024E+11 | 11366.24 | 24-JUL-21:19 | 19.23 | 17.76 |
August | 0.411240E+11 | 22149.35 | 08-AUG-21:52 | 21.70 | 18.33 | 0.193693E+11 | 11352.80 | 09-AUG-21:19 | 20.93 | 18.90 |
September | 0.364887E+11 | 21192.98 | 01-SEP-21:22 | 14.45 | 13.76 | 0.186507E+11 | 11349.03 | 01-SEP-21:40 | 14.27 | 13.58 |
October | 0.338298E+11 | 19446.87 | 19-OCT-22:00 | 12.20 | 9.84 | 0.191350E+11 | 11347.92 | 29-OCT-23:19 | -7.6 | -8.4 |
November | 0.294576E+11 | 18731.62 | 01-NOV-22:00 | 11.70 | 10.79 | 0.182442E+11 | 11347.92 | 13-NOV-00:20 | -9.4 | -10.0 |
December | 0.279677E+11 | 25092.33 | 13-DEC-04:21 | -23.9 | -24.2 | 0.171177E+11 | 11347.87 | 30-DEC-00:20 | -8.6 | -9.4 |
Annual Sum or Average | 0.408798E+12 | 0.219732E+12 | ||||||||
Minimum of Months | 0.258609E+11 | 18731.62 | -24.0 | -24.3 | 0.161570E+11 | 11347.87 | -24.0 | -24.2 | ||
Maximum of Months | 0.427557E+11 | 26674.63 | 27.43 | 23.63 | 0.193693E+11 | 11366.24 | 22.65 | 18.90 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.311182E+11 | 28346.48 | 25-JAN-20:01 | -24.0 | -24.2 | 0.166991E+11 | 11347.95 | 30-JAN-00:20 | -4.0 | -4.5 |
February | 0.287947E+11 | 27215.08 | 24-FEB-22:52 | -23.9 | -24.3 | 0.164082E+11 | 11347.95 | 28-FEB-00:20 | -15.3 | -15.9 |
March | 0.339701E+11 | 27536.43 | 12-MAR-03:51 | -23.9 | -24.1 | 0.189431E+11 | 11347.99 | 12-MAR-23:19 | -12.0 | -13.6 |
April | 0.366575E+11 | 21468.01 | 13-APR-21:10 | 13.03 | 6.68 | 0.186455E+11 | 11347.97 | 02-APR-23:19 | 13.03 | 6.68 |
May | 0.429508E+11 | 23613.12 | 25-MAY-21:10 | 22.65 | 16.44 | 0.193417E+11 | 11380.32 | 17-MAY-21:19 | 22.65 | 16.44 |
June | 0.436977E+11 | 24366.53 | 29-JUN-21:20 | 27.43 | 23.63 | 0.187587E+11 | 11377.35 | 08-JUN-21:19 | 27.43 | 23.63 |
July | 0.458429E+11 | 23812.65 | 21-JUL-21:20 | 21.70 | 20.13 | 0.193090E+11 | 11380.57 | 24-JUL-21:19 | 19.23 | 17.76 |
August | 0.443467E+11 | 23441.62 | 08-AUG-21:05 | 22.62 | 18.95 | 0.193863E+11 | 11380.04 | 23-AUG-21:19 | 20.00 | 17.61 |
September | 0.399577E+11 | 22460.32 | 01-SEP-21:10 | 14.82 | 14.12 | 0.186896E+11 | 11349.03 | 01-SEP-21:40 | 14.27 | 13.58 |
October | 0.376963E+11 | 21131.39 | 19-OCT-21:10 | 12.70 | 9.80 | 0.192360E+11 | 11347.98 | 29-OCT-23:19 | -7.6 | -8.4 |
November | 0.330578E+11 | 20741.72 | 01-NOV-21:10 | 12.62 | 11.43 | 0.184445E+11 | 11347.99 | 13-NOV-00:20 | -9.4 | -10.0 |
December | 0.311161E+11 | 26676.60 | 23-DEC-21:42 | -23.9 | -24.3 | 0.173923E+11 | 11347.95 | 04-DEC-00:20 | -23.9 | -24.3 |
Annual Sum or Average | 0.449206E+12 | 0.221254E+12 | ||||||||
Minimum of Months | 0.287947E+11 | 20741.72 | -24.0 | -24.3 | 0.164082E+11 | 11347.95 | -23.9 | -24.3 | ||
Maximum of Months | 0.458429E+11 | 28346.48 | 27.43 | 23.63 | 0.193863E+11 | 11380.57 | 27.43 | 23.63 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.459376E+11 | 29138.60 | 25-JAN-20:01 | -24.0 | -24.2 | 0.185638E+11 | 11319.68 | 07-JAN-18:19 | -24.0 | -24.2 |
February | 0.430281E+11 | 28737.14 | 01-FEB-18:11 | -23.9 | -24.3 | 0.168938E+11 | 11319.65 | 25-FEB-18:19 | -12.2 | -13.9 |
March | 0.496599E+11 | 29131.52 | 26-MAR-10:37 | 3.87 | 1.06 | 0.187910E+11 | 11319.60 | 04-MAR-18:19 | 3.87 | 1.06 |
April | 0.513118E+11 | 30613.97 | 22-APR-10:33 | 14.43 | 5.29 | 0.182264E+11 | 11319.67 | 22-APR-17:19 | 17.93 | 7.72 |
May | 0.565078E+11 | 31537.05 | 18-MAY-10:33 | 26.07 | 16.42 | 0.188551E+11 | 11319.68 | 20-MAY-17:19 | 13.43 | 7.88 |
June | 0.564297E+11 | 32072.56 | 25-JUN-10:40 | 27.43 | 22.06 | 0.182571E+11 | 11319.67 | 24-JUN-17:19 | 27.43 | 22.06 |
July | 0.589488E+11 | 32139.23 | 29-JUL-10:40 | 27.43 | 19.77 | 0.188621E+11 | 11319.68 | 22-JUL-17:19 | 27.43 | 19.77 |
August | 0.576209E+11 | 31588.85 | 25-AUG-10:33 | 24.27 | 17.99 | 0.188673E+11 | 11319.68 | 12-AUG-17:19 | 24.27 | 17.99 |
September | 0.534350E+11 | 31374.90 | 01-SEP-10:33 | 22.77 | 18.04 | 0.182444E+11 | 11319.66 | 23-SEP-17:19 | 14.83 | 8.58 |
October | 0.520221E+11 | 30082.99 | 22-OCT-10:33 | 15.20 | 11.90 | 0.188356E+11 | 11319.58 | 21-OCT-17:19 | 15.20 | 11.90 |
November | 0.474077E+11 | 27243.58 | 17-NOV-11:50 | 8.53 | 2.74 | 0.182063E+11 | 11319.64 | 25-NOV-18:19 | -15.0 | -15.5 |
December | 0.459766E+11 | 28102.59 | 23-DEC-21:42 | -23.9 | -24.3 | 0.186301E+11 | 11319.68 | 02-DEC-18:19 | -23.9 | -24.3 |
Annual Sum or Average | 0.618286E+12 | 0.221233E+12 | ||||||||
Minimum of Months | 0.430281E+11 | 27243.58 | -24.0 | -24.3 | 0.168938E+11 | 11319.58 | -24.0 | -24.3 | ||
Maximum of Months | 0.589488E+11 | 32139.23 | 27.43 | 22.06 | 0.188673E+11 | 11319.68 | 27.43 | 22.06 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.275994E+09 | 1445.71 | 27-JAN-13:50 | -14.6 | -15.8 | 0.117589E+10 | 745.64 | 27-JAN-04:10 | -14.6 | -15.8 |
February | 0.143580E+10 | 3381.40 | 22-FEB-11:33 | -2.2 | -4.8 | 0.112778E+10 | 746.01 | 28-FEB-22:19 | -0.2 | -3.1 |
March | 0.332940E+10 | 3662.93 | 26-MAR-10:33 | 3.87 | 1.06 | 0.127897E+10 | 791.27 | 31-MAR-21:40 | 4.67 | 0.78 |
April | 0.664865E+10 | 4387.78 | 18-APR-10:33 | 17.57 | 11.16 | 0.128929E+10 | 883.31 | 23-APR-23:10 | 14.63 | 10.70 |
May | 0.958122E+10 | 5499.93 | 18-MAY-14:10 | 28.57 | 16.73 | 0.149394E+10 | 1000.17 | 25-MAY-21:30 | 22.35 | 16.43 |
June | 0.101559E+11 | 6815.56 | 30-JUN-13:20 | 31.50 | 24.23 | 0.151285E+10 | 1007.40 | 30-JUN-22:10 | 18.85 | 15.86 |
July | 0.110821E+11 | 6670.37 | 23-JUL-13:20 | 30.00 | 22.71 | 0.161345E+10 | 1007.40 | 21-JUL-22:10 | 30.00 | 22.71 |
August | 0.103746E+11 | 5672.53 | 24-AUG-14:20 | 25.37 | 17.76 | 0.157035E+10 | 991.04 | 08-AUG-21:40 | 25.37 | 17.76 |
September | 0.876069E+10 | 5405.10 | 01-SEP-15:03 | 26.10 | 17.79 | 0.139752E+10 | 971.77 | 01-SEP-21:30 | 14.45 | 13.76 |
October | 0.656992E+10 | 4526.21 | 22-OCT-10:33 | 15.20 | 11.90 | 0.131697E+10 | 866.07 | 19-OCT-21:40 | 15.20 | 11.90 |
November | 0.298850E+10 | 3470.00 | 17-NOV-11:33 | 8.17 | 2.57 | 0.122903E+10 | 781.35 | 01-NOV-21:40 | 8.17 | 2.57 |
December | 0.225926E+09 | 1567.03 | 05-DEC-22:10 | 0.00 | -0.0 | 0.121380E+10 | 745.72 | 14-DEC-05:30 | -23.6 | -23.9 |
Annual Sum or Average | 0.714288E+11 | 0.162198E+11 | ||||||||
Minimum of Months | 0.225926E+09 | 1445.71 | -14.6 | -15.8 | 0.112778E+10 | 745.64 | -23.6 | -23.9 | ||
Maximum of Months | 0.110821E+11 | 6815.56 | 31.50 | 24.23 | 0.161345E+10 | 1007.40 | 30.00 | 22.71 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3848318.87 | 2517.84 | 06-JAN-13:31 | -23.3 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -23.1 |
March | 0.00 | 0.00 | 01-MAR-00:05 | -1.3 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 |
May | 0.00 | 0.00 | 01-MAY-00:05 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 19.75 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 3.60 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -8.8 |
Annual Sum or Average | 3848318.87 | |||
Minimum of Months | 0.00 | 0.00 | -23.3 | |
Maximum of Months | 3848318.87 | 2517.84 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.121688E+10 | 2874.61 | 14-JAN-04:51 | -23.3 |
February | 0.593787E+09 | 2436.37 | 02-FEB-10:11 | -23.3 |
March | 0.313461E+09 | 2728.45 | 05-MAR-08:31 | -23.4 |
April | 12088364.17 | 402.50 | 04-APR-06:10 | -9.2 |
May | 0.00 | 0.00 | 01-MAY-00:05 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 19.75 |
October | 12283258.57 | 560.57 | 30-OCT-07:00 | -9.4 |
November | 0.311547E+09 | 1375.68 | 25-NOV-07:20 | -19.0 |
December | 0.130151E+10 | 2756.02 | 21-DEC-10:51 | -23.4 |
Annual Sum or Average | 0.376156E+10 | |||
Minimum of Months | 0.00 | 0.00 | -23.4 | |
Maximum of Months | 0.130151E+10 | 2874.61 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 59353952.50 | 990.51 | 06-JAN-13:31 | -23.3 |
February | 10246904.25 | 707.18 | 14-FEB-10:42 | -23.2 |
March | 718766.92 | 648.26 | 05-MAR-08:31 | -23.4 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 |
May | 0.00 | 0.00 | 01-MAY-00:05 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 19.75 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 3.60 |
December | 44674288.34 | 824.99 | 25-DEC-10:11 | -23.0 |
Annual Sum or Average | 0.114994E+09 | |||
Minimum of Months | 0.00 | 0.00 | -23.4 | |
Maximum of Months | 59353952.50 | 990.51 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.975355E+09 | 1512.16 | 06-JAN-13:31 | -23.3 |
February | 0.356976E+09 | 1218.72 | 14-FEB-10:42 | -23.2 |
March | 96309543.97 | 1146.66 | 05-MAR-08:31 | -23.4 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 |
May | 0.00 | 0.00 | 01-MAY-00:05 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 19.75 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 |
November | 31495473.10 | 278.65 | 25-NOV-17:00 | -15.6 |
December | 0.761667E+09 | 1337.33 | 25-DEC-10:11 | -23.0 |
Annual Sum or Average | 0.222180E+10 | |||
Minimum of Months | 0.00 | 0.00 | -23.4 | |
Maximum of Months | 0.975355E+09 | 1512.16 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.113249E+10 | 1045.20 | 06-JAN-13:31 | -23.3 |
February | 0.597320E+09 | 868.72 | 14-FEB-10:42 | -23.2 |
March | 0.266981E+09 | 826.19 | 05-MAR-08:31 | -23.4 |
April | 3165433.47 | 96.80 | 05-APR-04:00 | -12.2 |
May | 0.00 | 0.00 | 01-MAY-00:05 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 19.75 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 |
November | 0.127184E+09 | 444.69 | 25-NOV-17:00 | -15.6 |
December | 0.995678E+09 | 946.10 | 25-DEC-10:11 | -23.0 |
Annual Sum or Average | 0.312282E+10 | |||
Minimum of Months | 0.00 | 0.00 | -23.4 | |
Maximum of Months | 0.113249E+10 | 1045.20 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2128360.93 | 7466.88 | 14-JAN-04:51 | -23.3 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -23.1 |
March | 78015.09 | 1177.12 | 05-MAR-08:31 | -23.4 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 |
May | 0.00 | 0.00 | 01-MAY-00:05 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 19.75 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 3.60 |
December | 409521.98 | 3899.60 | 21-DEC-10:51 | -23.4 |
Annual Sum or Average | 2615898.00 | |||
Minimum of Months | 0.00 | 0.00 | -23.4 | |
Maximum of Months | 2128360.93 | 7466.88 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 67097290.61 | 5873.07 | 09-JAN-10:41 | -23.4 |
February | 32003170.70 | 5973.78 | 02-FEB-10:11 | -23.3 |
March | 3682340.96 | 6607.96 | 05-MAR-08:31 | -23.4 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 |
May | 0.00 | 0.00 | 01-MAY-00:05 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 19.75 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 3.60 |
December | 0.153094E+09 | 7557.06 | 21-DEC-10:51 | -23.4 |
Annual Sum or Average | 0.255877E+09 | |||
Minimum of Months | 0.00 | 0.00 | -23.4 | |
Maximum of Months | 0.153094E+09 | 7557.06 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.218013E+09 | 17066.36 | 09-JAN-10:41 | -23.4 |
February | 49644022.79 | 11528.98 | 17-FEB-09:52 | -22.8 |
March | 5284756.05 | 10938.67 | 05-MAR-08:31 | -23.4 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 |
May | 0.00 | 0.00 | 01-MAY-00:05 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 19.75 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 3.60 |
December | 0.241750E+09 | 14755.41 | 21-DEC-10:51 | -23.4 |
Annual Sum or Average | 0.514692E+09 | |||
Minimum of Months | 0.00 | 0.00 | -23.4 | |
Maximum of Months | 0.241750E+09 | 17066.36 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.225359E+10 | 2066.42 | 07-JAN-09:13 | -20.2 |
February | 0.132767E+10 | 2040.82 | 02-FEB-16:02 | -15.1 |
March | 0.890070E+09 | 2006.47 | 16-MAR-08:62 | -19.0 |
April | 0.240099E+09 | 1983.15 | 04-APR-08:61 | -7.6 |
May | 9806125.53 | 1260.63 | 30-MAY-08:03 | 10.93 |
June | 2626975.05 | 1064.70 | 03-JUN-18:04 | 14.32 |
July | 1324299.17 | 855.77 | 03-JUL-08:04 | 19.50 |
August | 2769975.44 | 1133.44 | 17-AUG-18:03 | 13.12 |
September | 14730661.71 | 1232.85 | 29-SEP-15:03 | 11.10 |
October | 0.287558E+09 | 1985.72 | 30-OCT-15:01 | 5.00 |
November | 0.978775E+09 | 2020.08 | 25-NOV-19:02 | -15.0 |
December | 0.222888E+10 | 2077.17 | 25-DEC-16:13 | -15.3 |
Annual Sum or Average | 0.823790E+10 | |||
Minimum of Months | 1324299.17 | 855.77 | -20.2 | |
Maximum of Months | 0.225359E+10 | 2077.17 | 19.50 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.269926E+10 | 2171.58 | 06-JAN-08:04 | -35.1 |
February | 0.169623E+10 | 2038.19 | 02-FEB-16:02 | -15.1 |
March | 0.115320E+10 | 2017.92 | 15-MAR-08:62 | -22.3 |
April | 0.311605E+09 | 1989.13 | 05-APR-08:61 | -8.5 |
May | 12618105.54 | 1310.83 | 01-MAY-08:62 | 1.73 |
June | 2187972.54 | 987.09 | 02-JUN-08:04 | 11.20 |
July | 821683.22 | 840.47 | 09-JUL-08:04 | 13.40 |
August | 2912901.10 | 1354.37 | 04-AUG-08:53 | 18.30 |
September | 17587906.06 | 1211.01 | 24-SEP-08:03 | 8.95 |
October | 0.359548E+09 | 1981.16 | 30-OCT-15:01 | 5.00 |
November | 0.118153E+10 | 2008.78 | 25-NOV-19:02 | -15.0 |
December | 0.257696E+10 | 2071.04 | 25-DEC-16:13 | -15.3 |
Annual Sum or Average | 0.100144E+11 | |||
Minimum of Months | 821683.22 | 840.47 | -35.1 | |
Maximum of Months | 0.269926E+10 | 2171.58 | 18.30 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 75685461.51 | 315.85 | 13-JAN-06:00 | -31.1 |
February | 1249831.23 | 73.93 | 03-FEB-06:00 | -11.7 |
March | 0.00 | 0.00 | 01-MAR-00:05 | -1.3 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 |
May | 0.00 | 0.00 | 01-MAY-00:05 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 19.75 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 |
November | 126719.48 | 38.92 | 29-NOV-06:00 | -20.6 |
December | 0.125217E+09 | 342.96 | 24-DEC-06:00 | -31.1 |
Annual Sum or Average | 0.202279E+09 | |||
Minimum of Months | 0.00 | 0.00 | -31.1 | |
Maximum of Months | 0.125217E+09 | 342.96 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.531071E+09 | 594.07 | 06-JAN-16:02 | -22.4 |
February | 0.311499E+09 | 584.70 | 01-FEB-16:01 | -20.2 |
March | 0.172965E+09 | 577.17 | 15-MAR-15:01 | -11.0 |
April | 12920100.13 | 538.52 | 04-APR-15:01 | -3.4 |
May | 409302.05 | 539.54 | 02-MAY-15:04 | 18.30 |
June | 216811.09 | 372.97 | 12-JUN-15:06 | 17.98 |
July | 59220.46 | 367.07 | 09-JUL-15:06 | 18.48 |
August | 374874.54 | 380.38 | 10-AUG-15:06 | 16.97 |
September | 758441.84 | 414.11 | 09-SEP-18:54 | 11.70 |
October | 4819946.59 | 537.71 | 30-OCT-15:01 | 5.00 |
November | 0.119769E+09 | 577.85 | 25-NOV-16:02 | -14.2 |
December | 0.477063E+09 | 590.80 | 20-DEC-16:01 | -20.4 |
Annual Sum or Average | 0.163193E+10 | |||
Minimum of Months | 59220.46 | 367.07 | -22.4 | |
Maximum of Months | 0.531071E+09 | 594.07 | 18.48 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.224204E+10 | 2022.84 | 07-JAN-09:02 | -20.4 |
February | 0.132296E+10 | 2009.20 | 02-FEB-16:02 | -15.1 |
March | 0.881194E+09 | 1980.25 | 07-MAR-16:01 | -8.3 |
April | 0.231849E+09 | 1930.43 | 26-APR-15:01 | -0.6 |
May | 10745720.29 | 1046.10 | 12-MAY-18:04 | 12.65 |
June | 1340507.95 | 961.31 | 23-JUN-08:04 | 19.82 |
July | 846308.47 | 949.06 | 03-JUL-08:04 | 19.50 |
August | 2414281.26 | 1167.34 | 17-AUG-18:03 | 13.12 |
September | 16683609.91 | 1130.32 | 29-SEP-15:03 | 11.10 |
October | 0.298071E+09 | 1942.63 | 29-OCT-18:01 | -3.0 |
November | 0.986105E+09 | 1992.69 | 25-NOV-16:02 | -14.2 |
December | 0.221289E+10 | 2033.21 | 25-DEC-16:13 | -15.3 |
Annual Sum or Average | 0.820713E+10 | |||
Minimum of Months | 846308.47 | 949.06 | -20.4 | |
Maximum of Months | 0.224204E+10 | 2033.21 | 19.82 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.269428E+10 | 2053.68 | 06-JAN-16:02 | -22.4 |
February | 0.169550E+10 | 2018.18 | 01-FEB-16:01 | -20.2 |
March | 0.114009E+10 | 1981.73 | 07-MAR-16:01 | -8.3 |
April | 0.296181E+09 | 1922.36 | 03-APR-08:61 | -1.5 |
May | 14369689.97 | 1499.16 | 02-MAY-19:43 | 13.25 |
June | 1166601.33 | 1046.73 | 12-JUN-08:04 | 13.17 |
July | 735345.11 | 901.82 | 09-JUL-08:04 | 13.40 |
August | 2435615.71 | 1019.12 | 18-AUG-08:04 | 12.30 |
September | 20946272.90 | 1223.51 | 22-SEP-18:03 | 12.93 |
October | 0.377350E+09 | 1933.71 | 29-OCT-15:01 | 0.50 |
November | 0.118179E+10 | 1992.02 | 25-NOV-16:02 | -14.2 |
December | 0.256504E+10 | 2044.05 | 20-DEC-16:01 | -20.4 |
Annual Sum or Average | 0.998988E+10 | |||
Minimum of Months | 735345.11 | 901.82 | -22.4 | |
Maximum of Months | 0.269428E+10 | 2053.68 | 13.40 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.904460E+09 | 2093.88 | 06-JAN-13:31 | -23.3 |
February | 0.212969E+09 | 1762.63 | 17-FEB-09:52 | -22.8 |
March | 51770288.63 | 1742.40 | 05-MAR-08:31 | -23.4 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 |
May | 0.00 | 0.00 | 01-MAY-00:05 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 19.75 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 |
November | 70381565.64 | 652.02 | 25-NOV-17:00 | -15.6 |
December | 0.833199E+09 | 1933.47 | 25-DEC-10:11 | -23.0 |
Annual Sum or Average | 0.207278E+10 | |||
Minimum of Months | 0.00 | 0.00 | -23.4 | |
Maximum of Months | 0.904460E+09 | 2093.88 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.303859E+10 | 2444.92 | 12-JAN-19:13 | -22.4 |
February | 0.189580E+10 | 2416.38 | 02-FEB-16:13 | -15.2 |
March | 0.133876E+10 | 2374.69 | 15-MAR-08:62 | -22.3 |
April | 0.438893E+09 | 2345.79 | 04-APR-08:61 | -7.6 |
May | 31257732.52 | 1795.61 | 01-MAY-08:62 | 1.73 |
June | 6128073.46 | 1194.73 | 09-JUN-08:03 | 11.10 |
July | 1466649.91 | 827.85 | 08-JUL-15:04 | 13.90 |
August | 6935700.58 | 1012.99 | 22-AUG-08:03 | 18.58 |
September | 52962459.72 | 1250.84 | 28-SEP-08:62 | 7.30 |
October | 0.525482E+09 | 2344.97 | 29-OCT-18:01 | -3.0 |
November | 0.145765E+10 | 2392.55 | 25-NOV-19:02 | -15.0 |
December | 0.302267E+10 | 2456.69 | 25-DEC-16:13 | -15.3 |
Annual Sum or Average | 0.118166E+11 | |||
Minimum of Months | 1466649.91 | 827.85 | -22.4 | |
Maximum of Months | 0.303859E+10 | 2456.69 | 18.58 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.355214E+10 | 2654.70 | 05-JAN-08:04 | -32.3 |
February | 0.234624E+10 | 2409.99 | 02-FEB-16:13 | -15.2 |
March | 0.167316E+10 | 2382.31 | 15-MAR-08:62 | -22.3 |
April | 0.543370E+09 | 2332.71 | 05-APR-08:61 | -8.5 |
May | 35500187.88 | 2181.81 | 01-MAY-08:62 | 1.73 |
June | 4846263.88 | 1028.40 | 05-JUN-08:53 | 17.80 |
July | 724340.50 | 1138.60 | 31-JUL-08:53 | 18.90 |
August | 6775975.44 | 1206.50 | 20-AUG-08:53 | 20.60 |
September | 61401639.62 | 1400.39 | 28-SEP-08:62 | 7.30 |
October | 0.640517E+09 | 2321.00 | 29-OCT-18:01 | -3.0 |
November | 0.171808E+10 | 2372.34 | 25-NOV-19:02 | -15.0 |
December | 0.341729E+10 | 2443.15 | 18-DEC-16:13 | -23.3 |
Annual Sum or Average | 0.140001E+11 | |||
Minimum of Months | 724340.50 | 1028.40 | -32.3 | |
Maximum of Months | 0.355214E+10 | 2654.70 | 20.60 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.102925E+10 | 1282.49 | 12-JAN-19:13 | -22.4 |
February | 0.576384E+09 | 1263.29 | 02-FEB-16:02 | -15.1 |
March | 0.388476E+09 | 1251.21 | 07-MAR-16:01 | -8.3 |
April | 0.107673E+09 | 1232.24 | 26-APR-15:01 | -0.6 |
May | 5728971.12 | 628.21 | 11-MAY-18:04 | 14.15 |
June | 2123674.20 | 745.49 | 22-JUN-15:04 | 18.40 |
July | 1270311.83 | 540.17 | 08-JUL-15:04 | 13.90 |
August | 1487515.24 | 590.74 | 28-AUG-18:04 | 20.40 |
September | 4287653.62 | 594.23 | 28-SEP-15:04 | 10.00 |
October | 0.114935E+09 | 1222.74 | 29-OCT-15:01 | 0.50 |
November | 0.434028E+09 | 1260.43 | 24-NOV-16:02 | -6.1 |
December | 0.108206E+10 | 1290.58 | 11-DEC-16:13 | -17.3 |
Annual Sum or Average | 0.374771E+10 | |||
Minimum of Months | 1270311.83 | 540.17 | -22.4 | |
Maximum of Months | 0.108206E+10 | 1290.58 | 20.40 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 15607960.31 | 6385.84 | 09-JAN-10:41 | -23.4 |
February | 1540976.48 | 3186.63 | 14-FEB-10:42 | -23.2 |
March | 0.00 | 0.00 | 01-MAR-00:05 | -1.3 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 |
May | 0.00 | 0.00 | 01-MAY-00:05 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 19.75 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 3.60 |
December | 6625999.41 | 4343.31 | 21-DEC-10:51 | -23.4 |
Annual Sum or Average | 23774936.21 | |||
Minimum of Months | 0.00 | 0.00 | -23.4 | |
Maximum of Months | 15607960.31 | 6385.84 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 10867545.66 | 6218.14 | 09-JAN-10:41 | -23.4 |
February | 831435.92 | 2868.75 | 14-FEB-10:42 | -23.2 |
March | 0.00 | 0.00 | 01-MAR-00:05 | -1.3 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 |
May | 0.00 | 0.00 | 01-MAY-00:05 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 19.75 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 3.60 |
December | 4360428.11 | 4112.16 | 21-DEC-10:51 | -23.4 |
Annual Sum or Average | 16059409.69 | |||
Minimum of Months | 0.00 | 0.00 | -23.4 | |
Maximum of Months | 10867545.66 | 6218.14 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 272431.83 | 3225.23 | 14-JAN-04:51 | -23.3 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -23.1 |
March | 0.00 | 0.00 | 01-MAR-00:05 | -1.3 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 |
May | 0.00 | 0.00 | 01-MAY-00:05 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 19.75 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 3.60 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -8.8 |
Annual Sum or Average | 272431.83 | |||
Minimum of Months | 0.00 | 0.00 | -23.3 | |
Maximum of Months | 272431.83 | 3225.23 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.348448E+10 | 6049.08 | 06-JAN-13:31 | -23.3 |
February | 0.144727E+10 | 5285.03 | 17-FEB-09:52 | -22.8 |
March | 0.465383E+09 | 5291.95 | 05-MAR-08:31 | -23.4 |
April | 3515831.36 | 627.24 | 05-APR-06:05 | -13.5 |
May | 0.00 | 0.00 | 01-MAY-00:05 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 19.75 |
October | 4293630.22 | 528.03 | 30-OCT-06:10 | -9.4 |
November | 0.299352E+09 | 2044.77 | 25-NOV-07:20 | -19.0 |
December | 0.306629E+10 | 5830.12 | 25-DEC-10:11 | -23.0 |
Annual Sum or Average | 0.877058E+10 | |||
Minimum of Months | 0.00 | 0.00 | -23.4 | |
Maximum of Months | 0.348448E+10 | 6049.08 | 19.75 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.136942E+11 | 13190.31 | 02-JAN-20:10 | 0.121516E+11 | 9632.53 | 02-JAN-20:10 |
February | 0.123646E+11 | 13190.31 | 01-FEB-20:10 | 0.109726E+11 | 9632.53 | 01-FEB-20:10 |
March | 0.137364E+11 | 13190.31 | 01-MAR-20:10 | 0.121771E+11 | 9632.53 | 01-MAR-20:10 |
April | 0.132299E+11 | 13190.31 | 03-APR-19:10 | 0.117446E+11 | 9632.53 | 03-APR-19:10 |
May | 0.137180E+11 | 13190.31 | 01-MAY-19:10 | 0.121662E+11 | 9632.53 | 01-MAY-19:10 |
June | 0.132906E+11 | 13190.31 | 01-JUN-19:10 | 0.117829E+11 | 9632.53 | 01-JUN-19:10 |
July | 0.136573E+11 | 13190.31 | 03-JUL-19:10 | 0.121279E+11 | 9632.53 | 03-JUL-19:10 |
August | 0.137417E+11 | 13190.31 | 01-AUG-19:10 | 0.121808E+11 | 9632.53 | 01-AUG-19:10 |
September | 0.132352E+11 | 13190.31 | 01-SEP-19:10 | 0.117482E+11 | 9632.53 | 01-SEP-19:10 |
October | 0.136889E+11 | 13190.31 | 02-OCT-19:10 | 0.121479E+11 | 9632.53 | 02-OCT-19:10 |
November | 0.132800E+11 | 13190.31 | 01-NOV-19:10 | 0.117774E+11 | 9632.53 | 01-NOV-19:10 |
December | 0.136573E+11 | 13190.31 | 01-DEC-20:10 | 0.121279E+11 | 9632.53 | 01-DEC-20:10 |
Annual Sum or Average | 0.161294E+12 | 0.143105E+12 | ||||
Minimum of Months | 0.123646E+11 | 13190.31 | 0.109726E+11 | 9632.53 | ||
Maximum of Months | 0.137417E+11 | 13190.31 | 0.121808E+11 | 9632.53 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.620421E+09 | 597.59 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.560184E+09 | 597.59 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.622334E+09 | 597.59 | 01-MAR-20:10 | 0.866718E+09 | 685.60 | 01-MAR-20:10 |
April | 0.599386E+09 | 597.59 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.621497E+09 | 597.59 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.602135E+09 | 597.59 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.618748E+09 | 597.59 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.622573E+09 | 597.59 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.599625E+09 | 597.59 | 01-SEP-19:10 | 0.836191E+09 | 685.60 | 01-SEP-19:10 |
October | 0.620182E+09 | 597.59 | 02-OCT-19:10 | 0.864640E+09 | 685.60 | 02-OCT-19:10 |
November | 0.601657E+09 | 597.59 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.618748E+09 | 597.59 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.730749E+10 | 0.101856E+11 | ||||
Minimum of Months | 0.560184E+09 | 597.59 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.622573E+09 | 597.59 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.718450E+09 | 692.02 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.648695E+09 | 692.02 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.720665E+09 | 692.02 | 01-MAR-20:10 | 0.100366E+10 | 793.93 | 01-MAR-20:10 |
April | 0.694091E+09 | 692.02 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.719696E+09 | 692.02 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.697275E+09 | 692.02 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.716513E+09 | 692.02 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.720942E+09 | 692.02 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.694368E+09 | 692.02 | 01-SEP-19:10 | 0.968312E+09 | 793.93 | 01-SEP-19:10 |
October | 0.718174E+09 | 692.02 | 02-OCT-19:10 | 0.100126E+10 | 793.93 | 02-OCT-19:10 |
November | 0.696721E+09 | 692.02 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.716513E+09 | 692.02 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.846210E+10 | 0.117950E+11 | ||||
Minimum of Months | 0.648695E+09 | 692.02 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.720942E+09 | 692.02 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.710312E+09 | 684.18 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.641347E+09 | 684.18 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.712502E+09 | 684.18 | 01-MAR-20:10 | 0.106120E+10 | 839.45 | 01-MAR-20:10 |
April | 0.686229E+09 | 684.18 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.711544E+09 | 684.18 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.689376E+09 | 684.18 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.708397E+09 | 684.18 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.712775E+09 | 684.18 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.686503E+09 | 684.18 | 01-SEP-19:10 | 0.102382E+10 | 839.45 | 01-SEP-19:10 |
October | 0.710039E+09 | 684.18 | 02-OCT-19:10 | 0.105866E+10 | 839.45 | 02-OCT-19:10 |
November | 0.688829E+09 | 684.18 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.708397E+09 | 684.18 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.836625E+10 | 0.124712E+11 | ||||
Minimum of Months | 0.641347E+09 | 684.18 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.712775E+09 | 684.18 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.261454E+09 | 251.84 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.236069E+09 | 251.84 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.262260E+09 | 251.84 | 01-MAR-20:10 | 0.306128E+09 | 242.16 | 01-MAR-20:10 |
April | 0.252589E+09 | 251.84 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.261907E+09 | 251.84 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.253748E+09 | 251.84 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.260749E+09 | 251.84 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.262360E+09 | 251.84 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.252690E+09 | 251.84 | 01-SEP-19:10 | 0.295345E+09 | 242.16 | 01-SEP-19:10 |
October | 0.261353E+09 | 251.84 | 02-OCT-19:10 | 0.305393E+09 | 242.16 | 02-OCT-19:10 |
November | 0.253546E+09 | 251.84 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.260749E+09 | 251.84 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.307947E+10 | 0.359760E+10 | ||||
Minimum of Months | 0.236069E+09 | 251.84 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.262360E+09 | 251.84 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.337502E+09 | 325.08 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.304733E+09 | 325.08 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.338542E+09 | 325.08 | 01-MAR-20:10 | 0.578079E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.326059E+09 | 325.08 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.338087E+09 | 325.08 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.327554E+09 | 325.08 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.336592E+09 | 325.08 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.338672E+09 | 325.08 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.326189E+09 | 325.08 | 01-SEP-19:10 | 0.557718E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.337372E+09 | 325.08 | 02-OCT-19:10 | 0.576693E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.327294E+09 | 325.08 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.336592E+09 | 325.08 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.397519E+10 | 0.679355E+11 | ||||
Minimum of Months | 0.304733E+09 | 325.08 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.338672E+09 | 325.08 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.139303E+10 | 1701.53 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.118837E+10 | 1701.53 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.123433E+10 | 1701.53 | 01-MAR-20:10 | 0.122027E+10 | 965.27 | 01-MAR-20:10 |
April | 0.105668E+10 | 1701.53 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.959059E+09 | 1701.53 | 01-MAY-19:19 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.864991E+09 | 1701.53 | 01-JUN-19:40 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.918620E+09 | 1701.53 | 07-JUL-19:30 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.106084E+10 | 1701.53 | 01-AUG-19:30 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.113931E+10 | 1701.53 | 01-SEP-19:10 | 0.117729E+10 | 965.27 | 01-SEP-19:10 |
October | 0.130162E+10 | 1701.53 | 02-OCT-19:10 | 0.121734E+10 | 965.27 | 02-OCT-19:10 |
November | 0.132577E+10 | 1701.53 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.140704E+10 | 1701.53 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.138497E+11 | 0.143405E+11 | ||||
Minimum of Months | 0.864991E+09 | 1701.53 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.140704E+10 | 1701.53 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.950561E+10 | 9504.80 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.851334E+10 | 9504.80 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.939133E+10 | 9504.80 | 01-MAR-20:10 | 0.126786E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.892880E+10 | 9504.80 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.912850E+10 | 9504.80 | 01-MAY-19:19 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.878720E+10 | 9504.80 | 01-JUN-19:40 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.905410E+10 | 9504.80 | 07-JUL-19:30 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.923560E+10 | 9504.80 | 01-AUG-19:30 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.900325E+10 | 9504.80 | 01-SEP-19:10 | 0.122320E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.942058E+10 | 9504.80 | 02-OCT-19:10 | 0.126482E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.919679E+10 | 9504.80 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.950098E+10 | 9504.80 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.109666E+12 | 0.148998E+12 | ||||
Minimum of Months | 0.851334E+10 | 9504.80 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.950561E+10 | 9504.80 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196602E+09 | 177.88 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.177551E+09 | 177.88 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.195039E+09 | 177.88 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.190486E+09 | 177.88 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.195821E+09 | 177.88 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.188975E+09 | 177.88 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.197358E+09 | 177.88 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.195039E+09 | 177.88 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.190538E+09 | 177.88 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.196576E+09 | 177.88 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.189731E+09 | 177.88 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.197383E+09 | 177.88 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.231110E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.177551E+09 | 177.88 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.197383E+09 | 177.88 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196579E+09 | 177.86 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.177530E+09 | 177.86 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.195017E+09 | 177.86 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.190464E+09 | 177.86 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.195798E+09 | 177.86 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.188953E+09 | 177.86 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.197334E+09 | 177.86 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.195017E+09 | 177.86 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.190515E+09 | 177.86 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.196553E+09 | 177.86 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.189708E+09 | 177.86 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.197360E+09 | 177.86 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.231083E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.177530E+09 | 177.86 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.197360E+09 | 177.86 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123557E+09 | 111.79 | 01-JAN-19:10 | 0.217935E+09 | 232.19 | 01-JAN-08:09 |
February | 0.111584E+09 | 111.79 | 01-FEB-20:10 | 0.196843E+09 | 232.19 | 01-FEB-07:10 |
March | 0.122575E+09 | 111.79 | 01-MAR-20:10 | 0.217824E+09 | 232.19 | 01-MAR-07:10 |
April | 0.119713E+09 | 111.79 | 01-APR-18:10 | 0.210923E+09 | 232.19 | 01-APR-07:10 |
May | 0.123066E+09 | 111.79 | 01-MAY-19:10 | 0.217879E+09 | 232.19 | 01-MAY-06:10 |
June | 0.118764E+09 | 111.79 | 01-JUN-19:10 | 0.210812E+09 | 232.19 | 01-JUN-06:10 |
July | 0.124032E+09 | 111.79 | 01-JUL-18:10 | 0.217991E+09 | 232.19 | 01-JUL-07:10 |
August | 0.122575E+09 | 111.79 | 01-AUG-19:10 | 0.217824E+09 | 232.19 | 01-AUG-06:10 |
September | 0.119746E+09 | 111.79 | 01-SEP-19:10 | 0.210923E+09 | 232.19 | 01-SEP-06:10 |
October | 0.123541E+09 | 111.79 | 01-OCT-18:10 | 0.217935E+09 | 232.19 | 01-OCT-07:10 |
November | 0.119238E+09 | 111.79 | 01-NOV-19:10 | 0.210867E+09 | 232.19 | 01-NOV-06:10 |
December | 0.124048E+09 | 111.79 | 01-DEC-20:10 | 0.217991E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.145244E+10 | 0.256575E+10 | ||||
Minimum of Months | 0.111584E+09 | 111.79 | 0.196843E+09 | 232.19 | ||
Maximum of Months | 0.124048E+09 | 111.79 | 0.217991E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123591E+09 | 111.82 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 0.111614E+09 | 111.82 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 0.122608E+09 | 111.82 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 0.119746E+09 | 111.82 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 0.123099E+09 | 111.82 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 0.118796E+09 | 111.82 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 0.124066E+09 | 111.82 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 0.122608E+09 | 111.82 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 0.119778E+09 | 111.82 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 0.123574E+09 | 111.82 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 0.119271E+09 | 111.82 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 0.124082E+09 | 111.82 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.145283E+10 | 0.256645E+10 | ||||
Minimum of Months | 0.111614E+09 | 111.82 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 0.124082E+09 | 111.82 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196602E+09 | 177.88 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.177551E+09 | 177.88 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.195039E+09 | 177.88 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.190486E+09 | 177.88 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.195821E+09 | 177.88 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.188975E+09 | 177.88 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.197358E+09 | 177.88 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.195039E+09 | 177.88 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.190538E+09 | 177.88 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.196576E+09 | 177.88 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.189731E+09 | 177.88 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.197383E+09 | 177.88 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.231110E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.177551E+09 | 177.88 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.197383E+09 | 177.88 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196579E+09 | 177.86 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.177530E+09 | 177.86 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.195017E+09 | 177.86 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.190464E+09 | 177.86 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.195798E+09 | 177.86 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.188953E+09 | 177.86 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.197334E+09 | 177.86 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.195017E+09 | 177.86 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.190515E+09 | 177.86 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.196553E+09 | 177.86 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.189708E+09 | 177.86 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.197360E+09 | 177.86 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.231083E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.177530E+09 | 177.86 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.197360E+09 | 177.86 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.193865E+10 | 1867.32 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.175042E+10 | 1867.32 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.194462E+10 | 1867.32 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.187292E+10 | 1867.32 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.194201E+10 | 1867.32 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.188151E+10 | 1867.32 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.193342E+10 | 1867.32 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.194537E+10 | 1867.32 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.187367E+10 | 1867.32 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.193790E+10 | 1867.32 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.188002E+10 | 1867.32 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.193342E+10 | 1867.32 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.228339E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.175042E+10 | 1867.32 | 0.00 | 0.00 | |
Maximum of Months | 0.194537E+10 | 1867.32 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196602E+09 | 177.88 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.177551E+09 | 177.88 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.195039E+09 | 177.88 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.190486E+09 | 177.88 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.195821E+09 | 177.88 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.188975E+09 | 177.88 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.197358E+09 | 177.88 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.195039E+09 | 177.88 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.190538E+09 | 177.88 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.196576E+09 | 177.88 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.189731E+09 | 177.88 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.197383E+09 | 177.88 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.231110E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.177551E+09 | 177.88 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.197383E+09 | 177.88 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196579E+09 | 177.86 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.177530E+09 | 177.86 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.195017E+09 | 177.86 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.190464E+09 | 177.86 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.195798E+09 | 177.86 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.188953E+09 | 177.86 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.197334E+09 | 177.86 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.195017E+09 | 177.86 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.190515E+09 | 177.86 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.196553E+09 | 177.86 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.189708E+09 | 177.86 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.197360E+09 | 177.86 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.231083E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.177530E+09 | 177.86 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.197360E+09 | 177.86 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123591E+09 | 111.82 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 0.111614E+09 | 111.82 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 0.122608E+09 | 111.82 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 0.119746E+09 | 111.82 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 0.123099E+09 | 111.82 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 0.118796E+09 | 111.82 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 0.124066E+09 | 111.82 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 0.122608E+09 | 111.82 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 0.119778E+09 | 111.82 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 0.123574E+09 | 111.82 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 0.119271E+09 | 111.82 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 0.124082E+09 | 111.82 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.145283E+10 | 0.256645E+10 | ||||
Minimum of Months | 0.111614E+09 | 111.82 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 0.124082E+09 | 111.82 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.282066E+10 | 2988.03 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.246967E+10 | 2988.03 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.266158E+10 | 2988.03 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.241957E+10 | 2988.03 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.235546E+10 | 2988.03 | 01-MAY-19:30 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.221315E+10 | 2988.03 | 01-JUN-19:49 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.230957E+10 | 2988.03 | 07-JUL-19:30 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.247184E+10 | 2988.03 | 01-AUG-19:40 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.250918E+10 | 2988.03 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.272402E+10 | 2988.03 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.271283E+10 | 2988.03 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.283138E+10 | 2988.03 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.304989E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.221315E+10 | 2988.03 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.283138E+10 | 2988.03 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.282066E+10 | 2988.03 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.246967E+10 | 2988.03 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.266158E+10 | 2988.03 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.241957E+10 | 2988.03 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.235546E+10 | 2988.03 | 01-MAY-19:30 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.221315E+10 | 2988.03 | 01-JUN-19:49 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.230957E+10 | 2988.03 | 07-JUL-19:30 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.247184E+10 | 2988.03 | 01-AUG-19:40 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.250918E+10 | 2988.03 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.272402E+10 | 2988.03 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.271283E+10 | 2988.03 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.283138E+10 | 2988.03 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.304989E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.221315E+10 | 2988.03 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.283138E+10 | 2988.03 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.110133E+10 | 1060.81 | 02-JAN-20:10 | 0.368383E+11 | 16487.34 | 01-JAN-07:10 |
February | 0.994402E+09 | 1060.81 | 01-FEB-20:10 | 0.332733E+11 | 16487.34 | 01-FEB-07:10 |
March | 0.110473E+10 | 1060.81 | 01-MAR-20:10 | 0.368383E+11 | 16487.34 | 01-MAR-07:10 |
April | 0.106399E+10 | 1060.81 | 03-APR-19:10 | 0.356500E+11 | 16487.34 | 01-APR-06:10 |
May | 0.110324E+10 | 1060.81 | 01-MAY-19:10 | 0.368383E+11 | 16487.34 | 01-MAY-06:10 |
June | 0.106887E+10 | 1060.81 | 01-JUN-19:10 | 0.356500E+11 | 16487.34 | 01-JUN-06:10 |
July | 0.109836E+10 | 1060.81 | 03-JUL-19:10 | 0.368383E+11 | 16487.34 | 01-JUL-06:10 |
August | 0.110515E+10 | 1060.81 | 01-AUG-19:10 | 0.368383E+11 | 16487.34 | 01-AUG-06:10 |
September | 0.106442E+10 | 1060.81 | 01-SEP-19:10 | 0.356500E+11 | 16487.34 | 01-SEP-06:10 |
October | 0.110091E+10 | 1060.81 | 02-OCT-19:10 | 0.368383E+11 | 16487.34 | 01-OCT-06:10 |
November | 0.106802E+10 | 1060.81 | 01-NOV-19:10 | 0.356500E+11 | 16487.34 | 01-NOV-06:10 |
December | 0.109836E+10 | 1060.81 | 01-DEC-20:10 | 0.368383E+11 | 16487.34 | 01-DEC-07:10 |
Annual Sum or Average | 0.129718E+11 | 0.433742E+12 | ||||
Minimum of Months | 0.994402E+09 | 1060.81 | 0.332733E+11 | 16487.34 | ||
Maximum of Months | 0.110515E+10 | 1060.81 | 0.368383E+11 | 16487.34 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.205176E+10 | 1976.27 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.185255E+10 | 1976.27 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.205809E+10 | 1976.27 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.198220E+10 | 1976.27 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.205532E+10 | 1976.27 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.199129E+10 | 1976.27 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.204623E+10 | 1976.27 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.205888E+10 | 1976.27 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.198299E+10 | 1976.27 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.205097E+10 | 1976.27 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.198971E+10 | 1976.27 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.204623E+10 | 1976.27 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.241662E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.185255E+10 | 1976.27 | 0.00 | 0.00 | |
Maximum of Months | 0.205888E+10 | 1976.27 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.136942E+11 | 0.121516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.123646E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196682E+11 | 0.137364E+11 | 0.121771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.132299E+11 | 0.117446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.137180E+11 | 0.121662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.132906E+11 | 0.117829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.136573E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.137417E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189689E+11 | 0.132352E+11 | 0.117482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195854E+11 | 0.136889E+11 | 0.121479E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.132800E+11 | 0.117774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.136573E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230861E+12 | 0.161294E+12 | 0.143105E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.176991E+11 | 0.123646E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196682E+11 | 0.137417E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.620421E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.584983E+09 |
February | 0.179968E+10 | 0.560184E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.457308E+09 |
March | 0.199990E+10 | 0.622334E+09 | 0.866718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.417712E+09 |
April | 0.192973E+10 | 0.599386E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 196694.80 | 0.250113E+09 |
May | 0.199475E+10 | 0.621497E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2826984.98 | 0.124003E+09 |
June | 0.193394E+10 | 0.602135E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8037563.02 | 63554311.87 |
July | 0.199054E+10 | 0.618748E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10018843.15 | 49599220.69 |
August | 0.199896E+10 | 0.622573E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3392999.77 | 64522740.93 |
September | 0.192879E+10 | 0.599625E+09 | 0.836191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 129067.23 | 0.131427E+09 |
October | 0.199148E+10 | 0.620182E+09 | 0.864640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233219E+09 |
November | 0.192552E+10 | 0.601657E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.334509E+09 |
December | 0.199054E+10 | 0.618748E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.551174E+09 |
Annual Sum or Average | 0.234744E+11 | 0.730749E+10 | 0.101856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 24602152.96 | 0.326212E+10 |
Minimum of Months | 0.179968E+10 | 0.560184E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49599220.69 |
Maximum of Months | 0.199990E+10 | 0.622573E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10018843.15 | 0.584983E+09 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.718450E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228629E+09 |
February | 0.208403E+10 | 0.648695E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178410E+09 |
March | 0.231589E+10 | 0.720665E+09 | 0.100366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164284E+09 |
April | 0.223463E+10 | 0.694091E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 84735.04 | 0.101765E+09 |
May | 0.230993E+10 | 0.719696E+09 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1136099.98 | 54866140.93 |
June | 0.223950E+10 | 0.697275E+09 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2939503.21 | 30872452.95 |
July | 0.230505E+10 | 0.716513E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3750033.87 | 24984730.34 |
August | 0.231480E+10 | 0.720942E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1427675.65 | 31448174.31 |
September | 0.223354E+10 | 0.694368E+09 | 0.968312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 74754.94 | 57783354.83 |
October | 0.230614E+10 | 0.718174E+09 | 0.100126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96268483.35 |
November | 0.222975E+10 | 0.696721E+09 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132608E+09 |
December | 0.230505E+10 | 0.716513E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215768E+09 |
Annual Sum or Average | 0.271834E+11 | 0.846210E+10 | 0.117950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 9412802.70 | 0.131769E+10 |
Minimum of Months | 0.208403E+10 | 0.648695E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24984730.34 |
Maximum of Months | 0.231589E+10 | 0.720942E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3750033.87 | 0.228629E+09 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.487480E+09 | 0.710312E+09 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.540245E+09 |
February | 0.440737E+09 | 0.641347E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.417457E+09 |
March | 0.489771E+09 | 0.712502E+09 | 0.106120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.378579E+09 |
April | 0.472586E+09 | 0.686229E+09 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 293958.90 | 0.228766E+09 |
May | 0.488511E+09 | 0.711544E+09 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3001761.66 | 0.124456E+09 |
June | 0.473617E+09 | 0.689376E+09 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6849925.28 | 71268415.30 |
July | 0.487480E+09 | 0.708397E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8656296.37 | 58737779.04 |
August | 0.489542E+09 | 0.712775E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3531351.79 | 72912844.79 |
September | 0.472357E+09 | 0.686503E+09 | 0.102382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 216136.76 | 0.132327E+09 |
October | 0.487709E+09 | 0.710039E+09 | 0.105866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218275E+09 |
November | 0.471555E+09 | 0.688829E+09 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.304477E+09 |
December | 0.487480E+09 | 0.708397E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.509800E+09 |
Annual Sum or Average | 0.574883E+10 | 0.836625E+10 | 0.124712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 22549430.76 | 0.305730E+10 |
Minimum of Months | 0.440737E+09 | 0.641347E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58737779.04 |
Maximum of Months | 0.489771E+09 | 0.712775E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8656296.37 | 0.540245E+09 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.374985E+09 | 0.261454E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309935E+09 |
February | 0.339028E+09 | 0.236069E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240389E+09 |
March | 0.376747E+09 | 0.262260E+09 | 0.306128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217837E+09 |
April | 0.363528E+09 | 0.252589E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 178966.20 | 0.129899E+09 |
May | 0.375778E+09 | 0.261907E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1833512.45 | 69420604.12 |
June | 0.364321E+09 | 0.253748E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4113072.14 | 39297386.93 |
July | 0.374985E+09 | 0.260749E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5264851.65 | 32273718.37 |
August | 0.376571E+09 | 0.262360E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2191794.62 | 39936113.92 |
September | 0.363352E+09 | 0.252690E+09 | 0.295345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 144660.98 | 73580746.52 |
October | 0.375161E+09 | 0.261353E+09 | 0.305393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 330.29 | 0.123085E+09 |
November | 0.362735E+09 | 0.253546E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174842E+09 |
December | 0.374985E+09 | 0.260749E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292835E+09 |
Annual Sum or Average | 0.442217E+10 | 0.307947E+10 | 0.359760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13727188.33 | 0.174333E+10 |
Minimum of Months | 0.339028E+09 | 0.236069E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32273718.37 |
Maximum of Months | 0.376747E+09 | 0.262360E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5264851.65 | 0.309935E+09 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.337502E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.744063E+09 |
February | 0.139600E+10 | 0.304733E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.591222E+09 |
March | 0.155131E+10 | 0.338542E+09 | 0.578079E+10 | 0.502211E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.550072E+09 |
April | 0.149688E+10 | 0.326059E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 320905.99 | 0.339391E+09 |
May | 0.154732E+10 | 0.338087E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 3956395.81 | 0.177842E+09 |
June | 0.150015E+10 | 0.327554E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 10482843.05 | 98822036.07 |
July | 0.154405E+10 | 0.336592E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 13659011.44 | 76223779.55 |
August | 0.155059E+10 | 0.338672E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 5661574.16 | 97973788.01 |
September | 0.149615E+10 | 0.326189E+09 | 0.557718E+10 | 0.484522E+11 | 0.00 | 0.00 | 0.00 | 358904.67 | 0.187741E+09 |
October | 0.154478E+10 | 0.337372E+09 | 0.576693E+10 | 0.501006E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322497E+09 |
November | 0.149361E+10 | 0.327294E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.450904E+09 |
December | 0.154405E+10 | 0.336592E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.708304E+09 |
Annual Sum or Average | 0.182090E+11 | 0.397519E+10 | 0.679355E+11 | 0.590196E+12 | 0.00 | 0.00 | 0.00 | 34439635.13 | 0.434506E+10 |
Minimum of Months | 0.139600E+10 | 0.304733E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 76223779.55 |
Maximum of Months | 0.155131E+10 | 0.338672E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 13659011.44 | 0.744063E+09 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.139303E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130450E+10 |
February | 0.236489E+11 | 0.118837E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102366E+10 |
March | 0.262800E+11 | 0.123433E+10 | 0.122027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.942772E+09 |
April | 0.253579E+11 | 0.105668E+10 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 402799.43 | 0.578506E+09 |
May | 0.262123E+11 | 0.959059E+09 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5810289.46 | 0.305453E+09 |
June | 0.254132E+11 | 0.864991E+09 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16441982.67 | 0.168890E+09 |
July | 0.261570E+11 | 0.918620E+09 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20883101.27 | 0.135242E+09 |
August | 0.262677E+11 | 0.106084E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7050374.22 | 0.172042E+09 |
September | 0.253456E+11 | 0.113931E+10 | 0.117729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 276944.72 | 0.322376E+09 |
October | 0.261693E+11 | 0.130162E+10 | 0.121734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.541211E+09 |
November | 0.253025E+11 | 0.132577E+10 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.753950E+09 |
December | 0.261570E+11 | 0.140704E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122827E+10 |
Annual Sum or Average | 0.308468E+12 | 0.138497E+11 | 0.143405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 50865491.78 | 0.747688E+10 |
Minimum of Months | 0.236489E+11 | 0.864991E+09 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135242E+09 |
Maximum of Months | 0.262800E+11 | 0.140704E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20883101.27 | 0.130450E+10 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.950561E+10 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.376633E+10 |
February | 0.702046E+11 | 0.851334E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295796E+10 |
March | 0.780153E+11 | 0.939133E+10 | 0.126786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273238E+10 |
April | 0.752779E+11 | 0.892880E+10 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1309926.30 | 0.169832E+10 |
May | 0.778146E+11 | 0.912850E+10 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 17885062.64 | 0.915616E+09 |
June | 0.754422E+11 | 0.878720E+10 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 47312001.61 | 0.519055E+09 |
July | 0.776503E+11 | 0.905410E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 60276572.47 | 0.414174E+09 |
August | 0.779788E+11 | 0.923560E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 21587262.16 | 0.524666E+09 |
September | 0.752414E+11 | 0.900325E+10 | 0.122320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 854504.38 | 0.969548E+09 |
October | 0.776868E+11 | 0.942058E+10 | 0.126482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161087E+10 |
November | 0.751137E+11 | 0.919679E+10 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221156E+10 |
December | 0.776503E+11 | 0.950098E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.355942E+10 |
Annual Sum or Average | 0.915726E+12 | 0.109666E+12 | 0.148998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149225E+09 | 0.218799E+11 |
Minimum of Months | 0.702046E+11 | 0.851334E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.414174E+09 |
Maximum of Months | 0.780153E+11 | 0.950561E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 60276572.47 | 0.376633E+10 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196602E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.345626E+09 |
February | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265415E+09 |
March | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240876E+09 |
April | 0.293479E+09 | 0.190486E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 196182.06 | 0.144110E+09 |
May | 0.303504E+09 | 0.195821E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2421261.10 | 71288245.12 |
June | 0.293842E+09 | 0.188975E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6435766.79 | 36220189.76 |
July | 0.303141E+09 | 0.197358E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8262495.91 | 25783657.17 |
August | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3490228.68 | 34533075.76 |
September | 0.293479E+09 | 0.190538E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 222668.85 | 74939754.52 |
October | 0.303322E+09 | 0.196576E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7710.56 | 0.134142E+09 |
November | 0.293661E+09 | 0.189731E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191924E+09 |
December | 0.303141E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323004E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231110E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21036313.95 | 0.188786E+10 |
Minimum of Months | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25783657.17 |
Maximum of Months | 0.303685E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8262495.91 | 0.345626E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196579E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344465E+09 |
February | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263146E+09 |
March | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238335E+09 |
April | 0.293479E+09 | 0.190464E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 180962.18 | 0.143456E+09 |
May | 0.303504E+09 | 0.195798E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2226371.86 | 75333848.71 |
June | 0.293842E+09 | 0.188953E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5720731.54 | 42061324.92 |
July | 0.303141E+09 | 0.197334E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7424829.85 | 32802715.75 |
August | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3008855.90 | 40742085.30 |
September | 0.293479E+09 | 0.190515E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 177805.10 | 77245587.38 |
October | 0.303322E+09 | 0.196553E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1417.32 | 0.133207E+09 |
November | 0.293661E+09 | 0.189708E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190126E+09 |
December | 0.303141E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322375E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231083E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18740973.75 | 0.190330E+10 |
Minimum of Months | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32802715.75 |
Maximum of Months | 0.303685E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7424829.85 | 0.344465E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.123557E+09 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88325660.10 |
February | 0.00 | 0.111584E+09 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73695873.36 |
March | 0.00 | 0.122575E+09 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73680525.44 |
April | 0.00 | 0.119713E+09 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50824547.97 |
May | 0.00 | 0.123066E+09 | 0.217879E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 72140.77 | 30508145.89 |
June | 0.00 | 0.118764E+09 | 0.210812E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 438137.74 | 19478266.47 |
July | 0.00 | 0.124032E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 354794.63 | 16247038.34 |
August | 0.00 | 0.122575E+09 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 78595.67 | 19904974.91 |
September | 0.00 | 0.119746E+09 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31929789.97 |
October | 0.00 | 0.123541E+09 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48308911.07 |
November | 0.00 | 0.119238E+09 | 0.210867E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57517942.14 |
December | 0.00 | 0.124048E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79894665.16 |
Annual Sum or Average | 0.00 | 0.145244E+10 | 0.256575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 943668.81 | 0.590316E+09 |
Minimum of Months | 0.00 | 0.111584E+09 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16247038.34 |
Maximum of Months | 0.00 | 0.124048E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 438137.74 | 88325660.10 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.123591E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96252672.09 |
February | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73802856.79 |
March | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66953058.00 |
April | 0.293479E+09 | 0.119746E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 55606.73 | 39968108.99 |
May | 0.303504E+09 | 0.123099E+09 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 647580.98 | 20196829.10 |
June | 0.293842E+09 | 0.118796E+09 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1626618.71 | 10862094.58 |
July | 0.303141E+09 | 0.124066E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2123830.27 | 8136397.88 |
August | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 881607.92 | 10436429.03 |
September | 0.293479E+09 | 0.119778E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 58969.39 | 20980856.21 |
October | 0.303322E+09 | 0.123574E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.87 | 37478801.48 |
November | 0.293661E+09 | 0.119271E+09 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53732653.96 |
December | 0.303141E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90278451.09 |
Annual Sum or Average | 0.357224E+10 | 0.145283E+10 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5395445.87 | 0.529079E+09 |
Minimum of Months | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8136397.88 |
Maximum of Months | 0.303685E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2123830.27 | 96252672.09 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196602E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.345425E+09 |
February | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265559E+09 |
March | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241673E+09 |
April | 0.293479E+09 | 0.190486E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 198991.76 | 0.144919E+09 |
May | 0.303504E+09 | 0.195821E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2431020.07 | 71567492.24 |
June | 0.293842E+09 | 0.188975E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6439977.82 | 36421359.67 |
July | 0.303141E+09 | 0.197358E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8271466.57 | 25903442.96 |
August | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3504714.78 | 34676729.57 |
September | 0.293479E+09 | 0.190538E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 225034.36 | 75076964.24 |
October | 0.303322E+09 | 0.196576E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7963.62 | 0.134267E+09 |
November | 0.293661E+09 | 0.189731E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191799E+09 |
December | 0.303141E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322901E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231110E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21079168.98 | 0.189019E+10 |
Minimum of Months | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25903442.96 |
Maximum of Months | 0.303685E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8271466.57 | 0.345425E+09 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196579E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344348E+09 |
February | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263076E+09 |
March | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239095E+09 |
April | 0.293479E+09 | 0.190464E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 186806.06 | 0.144309E+09 |
May | 0.303504E+09 | 0.195798E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2235442.59 | 74246952.73 |
June | 0.293842E+09 | 0.188953E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5704393.17 | 41341886.42 |
July | 0.303141E+09 | 0.197334E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7395086.24 | 32399462.73 |
August | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3024330.43 | 39524359.37 |
September | 0.293479E+09 | 0.190515E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 179870.47 | 76322311.01 |
October | 0.303322E+09 | 0.196553E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1587.38 | 0.133238E+09 |
November | 0.293661E+09 | 0.189708E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190045E+09 |
December | 0.303141E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322384E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231083E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18727516.34 | 0.190033E+10 |
Minimum of Months | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32399462.73 |
Maximum of Months | 0.303685E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7395086.24 | 0.344348E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.385223E+10 | 0.193865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.417323E+09 |
February | 0.348285E+10 | 0.175042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.321297E+09 |
March | 0.387034E+10 | 0.194462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291480E+09 |
April | 0.373454E+10 | 0.187292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196886.30 | 0.175773E+09 |
May | 0.386038E+10 | 0.194201E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2272694.45 | 94230993.64 |
June | 0.374269E+10 | 0.188151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5326261.07 | 53200141.48 |
July | 0.385223E+10 | 0.193342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6642952.69 | 43931470.32 |
August | 0.386853E+10 | 0.194537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2789945.11 | 53511278.81 |
September | 0.373273E+10 | 0.187367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160269.83 | 97791291.89 |
October | 0.385404E+10 | 0.193790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163841E+09 |
November | 0.372639E+10 | 0.188002E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233552E+09 |
December | 0.385223E+10 | 0.193342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.392432E+09 |
Annual Sum or Average | 0.454292E+11 | 0.228339E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17389009.45 | 0.233836E+10 |
Minimum of Months | 0.348285E+10 | 0.175042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43931470.32 |
Maximum of Months | 0.387034E+10 | 0.194537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6642952.69 | 0.417323E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196602E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.345674E+09 |
February | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265060E+09 |
March | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240574E+09 |
April | 0.293479E+09 | 0.190486E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 191529.44 | 0.143987E+09 |
May | 0.303504E+09 | 0.195821E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2364245.11 | 71579617.37 |
June | 0.293842E+09 | 0.188975E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6320639.52 | 36471123.68 |
July | 0.303141E+09 | 0.197358E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8103250.64 | 26027879.44 |
August | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3398448.54 | 34769482.42 |
September | 0.293479E+09 | 0.190538E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 212087.31 | 75085871.54 |
October | 0.303322E+09 | 0.196576E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6922.54 | 0.133839E+09 |
November | 0.293661E+09 | 0.189731E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191537E+09 |
December | 0.303141E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323222E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231110E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20597123.10 | 0.188783E+10 |
Minimum of Months | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26027879.44 |
Maximum of Months | 0.303685E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8103250.64 | 0.345674E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196579E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344858E+09 |
February | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263235E+09 |
March | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238258E+09 |
April | 0.293479E+09 | 0.190464E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 177171.71 | 0.143383E+09 |
May | 0.303504E+09 | 0.195798E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2180021.00 | 76188454.47 |
June | 0.293842E+09 | 0.188953E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5632273.06 | 42979052.81 |
July | 0.303141E+09 | 0.197334E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7294104.90 | 33589203.39 |
August | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2941279.75 | 41615714.69 |
September | 0.293479E+09 | 0.190515E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 170915.17 | 77604274.62 |
October | 0.303322E+09 | 0.196553E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1341.46 | 0.132806E+09 |
November | 0.293661E+09 | 0.189708E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189938E+09 |
December | 0.303141E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322842E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231083E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18397107.05 | 0.190730E+10 |
Minimum of Months | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33589203.39 |
Maximum of Months | 0.303685E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7294104.90 | 0.344858E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.123591E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179026E+09 |
February | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137579E+09 |
March | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124666E+09 |
April | 0.293479E+09 | 0.119746E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 98845.65 | 74404362.16 |
May | 0.303504E+09 | 0.123099E+09 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1216314.16 | 36699736.09 |
June | 0.293842E+09 | 0.118796E+09 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3245291.79 | 18658181.21 |
July | 0.303141E+09 | 0.124066E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4158851.80 | 13290950.12 |
August | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1744101.79 | 17819337.97 |
September | 0.293479E+09 | 0.119778E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 109484.57 | 38701608.45 |
October | 0.303322E+09 | 0.123574E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3126.69 | 69465870.91 |
November | 0.293661E+09 | 0.119271E+09 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99513725.34 |
December | 0.303141E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167019E+09 |
Annual Sum or Average | 0.357224E+10 | 0.145283E+10 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10576016.45 | 0.976843E+09 |
Minimum of Months | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13290950.12 |
Maximum of Months | 0.303685E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4158851.80 | 0.179026E+09 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.282066E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.874730E+09 |
February | 0.415303E+11 | 0.246967E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.688575E+09 |
March | 0.461508E+11 | 0.266158E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.639699E+09 |
April | 0.445315E+11 | 0.241957E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 189897.65 | 0.400349E+09 |
May | 0.460320E+11 | 0.235546E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3019671.27 | 0.217476E+09 |
June | 0.446286E+11 | 0.221315E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 8857888.72 | 0.125903E+09 |
July | 0.459349E+11 | 0.230957E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 10801214.74 | 98813700.09 |
August | 0.461292E+11 | 0.247184E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3875118.84 | 0.125562E+09 |
September | 0.445099E+11 | 0.250918E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 152951.74 | 0.228565E+09 |
October | 0.459565E+11 | 0.272402E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.380943E+09 |
November | 0.444343E+11 | 0.271283E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.523413E+09 |
December | 0.459349E+11 | 0.283138E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.830203E+09 |
Annual Sum or Average | 0.541708E+12 | 0.304989E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 26896742.96 | 0.513423E+10 |
Minimum of Months | 0.415303E+11 | 0.221315E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98813700.09 |
Maximum of Months | 0.461508E+11 | 0.283138E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 10801214.74 | 0.874730E+09 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.282066E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.879697E+09 |
February | 0.415303E+11 | 0.246967E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.693040E+09 |
March | 0.461508E+11 | 0.266158E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.643946E+09 |
April | 0.445315E+11 | 0.241957E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 188772.14 | 0.402803E+09 |
May | 0.460320E+11 | 0.235546E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3003306.85 | 0.218240E+09 |
June | 0.446286E+11 | 0.221315E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 8849147.01 | 0.126225E+09 |
July | 0.459349E+11 | 0.230957E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 10759637.24 | 98958146.81 |
August | 0.461292E+11 | 0.247184E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3852753.86 | 0.126040E+09 |
September | 0.445099E+11 | 0.250918E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 152870.44 | 0.229692E+09 |
October | 0.459565E+11 | 0.272402E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383485E+09 |
November | 0.444343E+11 | 0.271283E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.527500E+09 |
December | 0.459349E+11 | 0.283138E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.835002E+09 |
Annual Sum or Average | 0.541708E+12 | 0.304989E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 26806487.54 | 0.516463E+10 |
Minimum of Months | 0.415303E+11 | 0.221315E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98958146.81 |
Maximum of Months | 0.461508E+11 | 0.283138E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 10759637.24 | 0.879697E+09 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.110133E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.787212E+09 |
February | 0.369574E+10 | 0.994402E+09 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.620362E+09 |
March | 0.410691E+10 | 0.110473E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.576650E+09 |
April | 0.396281E+10 | 0.106399E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 170019.88 | 0.359620E+09 |
May | 0.409635E+10 | 0.110324E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 2695134.09 | 0.194268E+09 |
June | 0.397146E+10 | 0.106887E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 7932770.03 | 0.112336E+09 |
July | 0.408770E+10 | 0.109836E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 9644096.58 | 88124681.93 |
August | 0.410499E+10 | 0.110515E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 3455162.10 | 0.112319E+09 |
September | 0.396089E+10 | 0.106442E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 137860.04 | 0.204832E+09 |
October | 0.408962E+10 | 0.110091E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.342800E+09 |
November | 0.395417E+10 | 0.106802E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.473179E+09 |
December | 0.408770E+10 | 0.109836E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.747798E+09 |
Annual Sum or Average | 0.482060E+11 | 0.129718E+11 | 0.392709E+12 | 0.359593E+12 | 0.00 | 0.00 | 0.00 | 24035042.72 | 0.461950E+10 |
Minimum of Months | 0.369574E+10 | 0.994402E+09 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 88124681.93 |
Maximum of Months | 0.410691E+10 | 0.110515E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 9644096.58 | 0.787212E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.407704E+10 | 0.205176E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.735409E+09 |
February | 0.368610E+10 | 0.185255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.568776E+09 |
March | 0.409620E+10 | 0.205809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.517103E+09 |
April | 0.395248E+10 | 0.198220E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 297708.34 | 0.310673E+09 |
May | 0.408566E+10 | 0.205532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3147785.72 | 0.167036E+09 |
June | 0.396110E+10 | 0.199129E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8285724.51 | 94748073.35 |
July | 0.407704E+10 | 0.204623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10160472.16 | 77025167.29 |
August | 0.409429E+10 | 0.205888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3797525.37 | 94717232.29 |
September | 0.395056E+10 | 0.198299E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160366.92 | 0.172050E+09 |
October | 0.407896E+10 | 0.205097E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290583E+09 |
November | 0.394385E+10 | 0.198971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.414503E+09 |
December | 0.407704E+10 | 0.204623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.693413E+09 |
Annual Sum or Average | 0.480803E+11 | 0.241662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25849583.03 | 0.413604E+10 |
Minimum of Months | 0.368610E+10 | 0.185255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77025167.29 |
Maximum of Months | 0.409620E+10 | 0.205888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10160472.16 | 0.735409E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 13190.31 | 02-JAN-20:10 | 9632.53 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 13190.31 | 01-FEB-20:10 | 9632.53 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 13190.31 | 01-MAR-20:10 | 9632.53 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 13190.31 | 03-APR-19:10 | 9632.53 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 13190.31 | 01-MAY-19:10 | 9632.53 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 13190.31 | 01-JUN-19:10 | 9632.53 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 13190.31 | 03-JUL-19:10 | 9632.53 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 13190.31 | 01-AUG-19:10 | 9632.53 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 13190.31 | 01-SEP-19:10 | 9632.53 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 01-OCT-23:10 | 13190.31 | 02-OCT-19:10 | 9632.53 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 13190.31 | 01-NOV-19:10 | 9632.53 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 13190.31 | 01-DEC-20:10 | 9632.53 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 11501.89 | 13190.31 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 13190.31 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 597.59 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 309.06 | 06-JAN-09:00 |
February | 1169.53 | 01-FEB-00:10 | 597.59 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 304.62 | 14-FEB-07:00 |
March | 1169.53 | 01-MAR-00:10 | 597.59 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 278.20 | 05-MAR-04:00 |
April | 1169.53 | 01-APR-00:10 | 597.59 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.42 | 23-APR-17:00 | 203.19 | 05-APR-06:00 |
May | 1169.53 | 01-MAY-00:10 | 597.59 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.86 | 25-MAY-18:00 | 140.47 | 01-MAY-06:00 |
June | 1169.53 | 01-JUN-00:10 | 597.59 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.50 | 29-JUN-16:00 | 109.06 | 04-JUN-05:00 |
July | 1169.53 | 01-JUL-00:10 | 597.59 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.94 | 15-JUL-15:10 | 79.57 | 02-JUL-05:00 |
August | 1169.53 | 01-AUG-00:10 | 597.59 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.89 | 08-AUG-15:00 | 89.93 | 19-AUG-04:20 |
September | 1169.53 | 01-SEP-00:10 | 597.59 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.52 | 01-SEP-15:30 | 109.18 | 06-SEP-04:30 |
October | 1169.53 | 01-OCT-23:10 | 597.59 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 179.28 | 30-OCT-04:00 |
November | 1169.53 | 01-NOV-00:10 | 597.59 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 248.85 | 29-NOV-06:00 |
December | 1169.53 | 01-DEC-00:10 | 597.59 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 301.13 | 24-DEC-11:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1169.53 | 597.59 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.57 | |||||
Maximum of Months | 1169.53 | 597.59 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 53.50 | 309.06 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 692.02 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 124.62 | 26-JAN-07:00 |
February | 1354.32 | 01-FEB-00:10 | 692.02 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 125.75 | 14-FEB-07:00 |
March | 1354.32 | 01-MAR-00:10 | 692.02 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 114.61 | 05-MAR-07:00 |
April | 1354.32 | 01-APR-00:10 | 692.02 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.90 | 23-APR-16:00 | 80.63 | 05-APR-06:00 |
May | 1354.32 | 01-MAY-00:10 | 692.02 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.72 | 25-MAY-17:01 | 57.29 | 01-MAY-06:00 |
June | 1354.32 | 01-JUN-00:10 | 692.02 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.97 | 29-JUN-16:00 | 45.43 | 04-JUN-05:00 |
July | 1354.32 | 01-JUL-00:10 | 692.02 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.60 | 15-JUL-14:00 | 35.77 | 02-JUL-05:00 |
August | 1354.32 | 01-AUG-00:10 | 692.02 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.52 | 08-AUG-15:00 | 38.58 | 19-AUG-04:00 |
September | 1354.32 | 01-SEP-00:10 | 692.02 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.63 | 01-SEP-15:00 | 47.27 | 06-SEP-04:50 |
October | 1354.32 | 01-OCT-23:10 | 692.02 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 71.05 | 30-OCT-04:30 |
November | 1354.32 | 01-NOV-00:10 | 692.02 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 96.73 | 29-NOV-06:00 |
December | 1354.32 | 01-DEC-00:10 | 692.02 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 119.60 | 24-DEC-23:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1354.32 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.77 | |||||
Maximum of Months | 1354.32 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 20.97 | 125.75 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 286.42 | 02-JAN-00:10 | 684.18 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 304.76 | 06-JAN-09:00 |
February | 286.42 | 01-FEB-00:10 | 684.18 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 305.21 | 14-FEB-07:00 |
March | 286.42 | 01-MAR-00:10 | 684.18 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 278.09 | 05-MAR-07:00 |
April | 286.42 | 01-APR-00:10 | 684.18 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.33 | 23-APR-16:00 | 185.36 | 05-APR-06:00 |
May | 286.42 | 01-MAY-00:10 | 684.18 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.84 | 25-MAY-17:01 | 130.29 | 01-MAY-06:00 |
June | 286.42 | 01-JUN-00:10 | 684.18 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.68 | 29-JUN-16:00 | 106.58 | 04-JUN-05:00 |
July | 286.42 | 01-JUL-00:10 | 684.18 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.20 | 15-JUL-14:00 | 85.02 | 02-JUL-05:00 |
August | 286.42 | 01-AUG-00:10 | 684.18 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.02 | 08-AUG-16:00 | 89.74 | 19-AUG-04:00 |
September | 286.42 | 01-SEP-00:10 | 684.18 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.91 | 01-SEP-16:00 | 108.82 | 06-SEP-04:50 |
October | 286.42 | 01-OCT-23:10 | 684.18 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 163.56 | 30-OCT-04:00 |
November | 286.42 | 01-NOV-00:10 | 684.18 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 227.02 | 29-NOV-06:00 |
December | 286.42 | 01-DEC-00:10 | 684.18 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 290.80 | 24-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 286.42 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.02 | |||||
Maximum of Months | 286.42 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 49.68 | 305.21 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 220.32 | 02-JAN-00:10 | 251.84 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 173.33 | 06-JAN-09:00 |
February | 220.32 | 01-FEB-00:10 | 251.84 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 174.25 | 14-FEB-07:00 |
March | 220.32 | 01-MAR-00:10 | 251.84 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 158.84 | 05-MAR-07:00 |
April | 220.32 | 01-APR-00:10 | 251.84 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.93 | 23-APR-16:00 | 106.94 | 05-APR-06:00 |
May | 220.32 | 01-MAY-00:10 | 251.84 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.77 | 25-MAY-17:25 | 73.98 | 01-MAY-06:00 |
June | 220.32 | 01-JUN-00:10 | 251.84 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.68 | 29-JUN-16:00 | 60.28 | 04-JUN-05:00 |
July | 220.32 | 01-JUL-00:10 | 251.84 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.92 | 15-JUL-14:00 | 48.12 | 02-JUL-05:00 |
August | 220.32 | 01-AUG-00:10 | 251.84 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.23 | 08-AUG-16:00 | 50.61 | 19-AUG-04:00 |
September | 220.32 | 01-SEP-00:10 | 251.84 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.21 | 01-SEP-16:00 | 61.44 | 06-SEP-04:10 |
October | 220.32 | 01-OCT-23:10 | 251.84 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 19-OCT-15:00 | 94.36 | 30-OCT-04:00 |
November | 220.32 | 01-NOV-00:10 | 251.84 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 130.98 | 29-NOV-06:00 |
December | 220.32 | 01-DEC-00:10 | 251.84 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 166.07 | 24-DEC-06:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 220.32 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.12 | |||||
Maximum of Months | 220.32 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 28.68 | 174.25 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 325.08 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 393.80 | 13-JAN-21:00 |
February | 907.20 | 01-FEB-00:10 | 325.08 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 363.32 | 24-FEB-22:40 |
March | 907.20 | 01-MAR-00:10 | 325.08 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 357.41 | 15-MAR-07:30 |
April | 907.20 | 01-APR-00:10 | 325.08 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 29.15 | 23-APR-16:00 | 274.80 | 05-APR-06:00 |
May | 907.20 | 01-MAY-00:10 | 325.08 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 42.42 | 25-MAY-17:00 | 196.01 | 01-MAY-06:00 |
June | 907.20 | 01-JUN-00:10 | 325.08 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 75.90 | 29-JUN-16:00 | 148.19 | 04-JUN-05:10 |
July | 907.20 | 01-JUL-00:10 | 325.08 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 50.53 | 23-JUL-16:00 | 112.44 | 02-JUL-05:10 |
August | 907.20 | 01-AUG-00:10 | 325.08 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 50.35 | 08-AUG-16:00 | 124.12 | 19-AUG-05:08 |
September | 907.20 | 01-SEP-00:10 | 325.08 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 22.18 | 01-SEP-16:00 | 154.62 | 06-SEP-05:10 |
October | 907.20 | 01-OCT-23:10 | 325.08 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 243.35 | 30-OCT-05:10 |
November | 907.20 | 01-NOV-00:10 | 325.08 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 328.11 | 29-NOV-06:10 |
December | 907.20 | 01-DEC-00:10 | 325.08 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 372.37 | 19-DEC-22:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 907.20 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 112.44 | ||||||
Maximum of Months | 907.20 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 75.90 | 393.80 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 1701.53 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 701.87 | 06-JAN-05:00 |
February | 15368.40 | 01-FEB-00:10 | 1701.53 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 687.38 | 14-FEB-07:00 |
March | 15368.40 | 01-MAR-00:10 | 1701.53 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 627.07 | 07-MAR-04:00 |
April | 15368.40 | 01-APR-00:10 | 1701.53 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.09 | 23-APR-17:20 | 450.70 | 05-APR-06:00 |
May | 15368.40 | 01-MAY-00:10 | 1701.53 | 01-MAY-19:19 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.29 | 25-MAY-18:00 | 319.40 | 01-MAY-06:00 |
June | 15368.40 | 01-JUN-00:10 | 1701.53 | 01-JUN-19:40 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.30 | 29-JUN-16:00 | 250.95 | 04-JUN-05:00 |
July | 15368.40 | 01-JUL-00:10 | 1701.53 | 07-JUL-19:30 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.84 | 15-JUL-15:10 | 194.52 | 02-JUL-05:00 |
August | 15368.40 | 01-AUG-00:10 | 1701.53 | 01-AUG-19:30 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.73 | 08-AUG-15:40 | 218.82 | 19-AUG-04:00 |
September | 15368.40 | 01-SEP-00:10 | 1701.53 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.26 | 01-SEP-15:40 | 267.32 | 06-SEP-04:10 |
October | 15368.40 | 01-OCT-23:10 | 1701.53 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 401.26 | 30-OCT-04:30 |
November | 15368.40 | 01-NOV-00:10 | 1701.53 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 550.15 | 29-NOV-06:00 |
December | 15368.40 | 01-DEC-00:10 | 1701.53 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 665.83 | 24-DEC-23:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 15368.40 | 1701.53 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 194.52 | |||||
Maximum of Months | 15368.40 | 1701.53 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 118.30 | 701.87 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 9504.80 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2053.52 | 06-JAN-05:00 |
February | 45622.98 | 01-FEB-00:10 | 9504.80 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 2049.82 | 14-FEB-07:00 |
March | 45622.98 | 01-MAR-00:10 | 9504.80 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 1870.95 | 05-MAR-07:00 |
April | 45622.98 | 01-APR-00:10 | 9504.80 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 110.84 | 23-APR-16:00 | 1337.30 | 05-APR-06:00 |
May | 45622.98 | 01-MAY-00:10 | 9504.80 | 01-MAY-19:19 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 179.99 | 25-MAY-17:01 | 955.21 | 01-MAY-06:00 |
June | 45622.98 | 01-JUN-00:10 | 9504.80 | 01-JUN-19:40 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 343.64 | 29-JUN-16:00 | 759.66 | 04-JUN-05:00 |
July | 45622.98 | 01-JUL-00:10 | 9504.80 | 07-JUL-19:30 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 233.66 | 15-JUL-15:00 | 592.38 | 02-JUL-05:00 |
August | 45622.98 | 01-AUG-00:10 | 9504.80 | 01-AUG-19:30 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 213.29 | 08-AUG-16:00 | 655.90 | 19-AUG-04:00 |
September | 45622.98 | 01-SEP-00:10 | 9504.80 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.63 | 01-SEP-16:00 | 790.89 | 06-SEP-05:00 |
October | 45622.98 | 01-OCT-23:10 | 9504.80 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1191.18 | 30-OCT-04:40 |
November | 45622.98 | 01-NOV-00:10 | 9504.80 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 1615.22 | 29-NOV-06:00 |
December | 45622.98 | 01-DEC-00:10 | 9504.80 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 1956.27 | 24-DEC-23:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 45622.98 | 9504.80 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 592.38 | |||||
Maximum of Months | 45622.98 | 9504.80 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 343.64 | 2053.52 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.88 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 208.22 | 06-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 177.88 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 200.47 | 14-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 177.88 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 180.04 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 177.88 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.83 | 23-APR-16:00 | 118.45 | 05-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 177.88 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.14 | 25-MAY-17:00 | 82.03 | 01-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 177.88 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.09 | 29-JUN-16:00 | 63.78 | 04-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 177.88 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.78 | 15-JUL-15:10 | 46.66 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 177.88 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.32 | 08-AUG-16:00 | 52.67 | 19-AUG-04:00 |
September | 180.00 | 01-SEP-00:10 | 177.88 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.38 | 01-SEP-16:00 | 63.85 | 06-SEP-04:10 |
October | 180.00 | 01-OCT-00:10 | 177.88 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.85 | 19-OCT-15:10 | 104.57 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 177.88 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 144.97 | 29-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 177.88 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 192.37 | 24-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.66 | |||||
Maximum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 39.09 | 208.22 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.86 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 206.11 | 06-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 177.86 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 200.46 | 14-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 177.86 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 180.03 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 177.86 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.82 | 23-APR-16:00 | 118.45 | 05-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 177.86 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.14 | 25-MAY-17:00 | 82.02 | 01-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 177.86 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.09 | 29-JUN-16:00 | 63.78 | 04-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 177.86 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.78 | 15-JUL-15:10 | 46.66 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 177.86 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.33 | 08-AUG-15:10 | 52.67 | 19-AUG-04:00 |
September | 180.00 | 01-SEP-00:10 | 177.86 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.38 | 01-SEP-15:10 | 63.85 | 06-SEP-04:10 |
October | 180.00 | 01-OCT-00:10 | 177.86 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.85 | 19-OCT-15:07 | 104.56 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 177.86 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 144.96 | 29-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 177.86 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 192.36 | 24-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.66 | |||||
Maximum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 39.09 | 206.11 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 111.79 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 54.35 | 06-JAN-09:00 |
February | 0.00 | 01-FEB-00:10 | 111.79 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 53.79 | 14-FEB-07:00 |
March | 0.00 | 01-MAR-00:10 | 111.79 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 47.68 | 16-MAR-04:00 |
April | 0.00 | 01-APR-00:10 | 111.79 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 35.95 | 05-APR-06:00 |
May | 0.00 | 01-MAY-00:10 | 111.79 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.16 | 25-MAY-18:00 | 27.14 | 01-MAY-06:00 |
June | 0.00 | 01-JUN-00:10 | 111.79 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.53 | 29-JUN-16:00 | 21.97 | 04-JUN-05:00 |
July | 0.00 | 01-JUL-00:10 | 111.79 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 15-JUL-14:00 | 17.82 | 02-JUL-05:00 |
August | 0.00 | 01-AUG-00:10 | 111.79 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.14 | 08-AUG-15:10 | 18.97 | 19-AUG-04:00 |
September | 0.00 | 01-SEP-00:10 | 111.79 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 | 06-SEP-04:20 |
October | 0.00 | 01-OCT-00:10 | 111.79 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 31.16 | 30-OCT-07:00 |
November | 0.00 | 01-NOV-00:10 | 111.79 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 35.67 | 25-NOV-06:40 |
December | 0.00 | 01-DEC-00:10 | 111.79 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 47.99 | 24-DEC-09:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 0.00 | 111.79 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.82 | |||||
Maximum of Months | 0.00 | 111.79 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 6.53 | 54.35 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 111.82 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 56.92 | 06-JAN-09:00 |
February | 180.00 | 01-FEB-00:10 | 111.82 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 55.62 | 14-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 111.82 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 50.25 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 111.82 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.42 | 23-APR-16:00 | 33.06 | 05-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 111.82 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.46 | 25-MAY-17:00 | 22.89 | 01-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 111.82 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.91 | 29-JUN-16:00 | 17.80 | 04-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 111.82 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.75 | 15-JUL-15:10 | 13.02 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 111.82 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.63 | 08-AUG-15:10 | 14.70 | 19-AUG-04:00 |
September | 180.00 | 01-SEP-00:10 | 111.82 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.01 | 01-SEP-15:10 | 17.82 | 06-SEP-04:10 |
October | 180.00 | 01-OCT-00:10 | 111.82 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.80 | 19-OCT-15:07 | 29.19 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 111.82 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 40.46 | 29-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 111.82 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 53.28 | 24-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.02 | |||||
Maximum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 10.91 | 56.92 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.88 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 209.17 | 06-JAN-09:10 |
February | 180.00 | 01-FEB-00:10 | 177.88 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 200.47 | 14-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 177.88 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 180.04 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 177.88 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.83 | 23-APR-16:00 | 118.45 | 05-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 177.88 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.14 | 25-MAY-17:00 | 82.03 | 01-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 177.88 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.09 | 29-JUN-16:00 | 63.78 | 04-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 177.88 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.78 | 15-JUL-15:10 | 46.66 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 177.88 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.33 | 08-AUG-15:08 | 52.67 | 19-AUG-04:00 |
September | 180.00 | 01-SEP-00:10 | 177.88 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.38 | 01-SEP-15:08 | 63.85 | 06-SEP-04:10 |
October | 180.00 | 01-OCT-00:10 | 177.88 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.85 | 19-OCT-15:09 | 104.57 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 177.88 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 144.97 | 29-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 177.88 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 192.37 | 24-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.66 | |||||
Maximum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 39.09 | 209.17 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.86 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 206.34 | 06-JAN-09:10 |
February | 180.00 | 01-FEB-00:10 | 177.86 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 200.46 | 14-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 177.86 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 180.03 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 177.86 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.82 | 23-APR-16:00 | 118.44 | 05-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 177.86 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.14 | 25-MAY-17:00 | 82.02 | 01-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 177.86 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.09 | 29-JUN-16:00 | 63.78 | 04-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 177.86 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.78 | 15-JUL-15:10 | 46.66 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 177.86 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.33 | 08-AUG-15:10 | 52.67 | 19-AUG-04:00 |
September | 180.00 | 01-SEP-00:10 | 177.86 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.38 | 01-SEP-15:10 | 63.85 | 06-SEP-04:10 |
October | 180.00 | 01-OCT-00:10 | 177.86 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.85 | 19-OCT-15:07 | 104.56 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 177.86 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 144.96 | 29-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 177.86 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 191.84 | 24-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.66 | |||||
Maximum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 39.09 | 206.34 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2263.36 | 02-JAN-00:10 | 1867.32 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 238.88 | 06-JAN-09:00 |
February | 2263.36 | 01-FEB-00:10 | 1867.32 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 234.04 | 14-FEB-07:00 |
March | 2263.36 | 01-MAR-00:10 | 1867.32 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 211.64 | 05-MAR-07:00 |
April | 2263.36 | 01-APR-00:10 | 1867.32 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.18 | 23-APR-16:00 | 142.79 | 05-APR-06:00 |
May | 2263.36 | 01-MAY-00:10 | 1867.32 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.09 | 25-MAY-18:00 | 99.34 | 01-MAY-06:00 |
June | 2263.36 | 01-JUN-00:10 | 1867.32 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.05 | 29-JUN-16:00 | 80.87 | 04-JUN-05:00 |
July | 2263.36 | 01-JUL-00:10 | 1867.32 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.09 | 15-JUL-14:00 | 64.71 | 02-JUL-05:00 |
August | 2263.36 | 01-AUG-00:10 | 1867.32 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.96 | 08-AUG-16:00 | 67.31 | 19-AUG-04:00 |
September | 2263.36 | 01-SEP-00:10 | 1867.32 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.27 | 01-SEP-16:00 | 83.17 | 06-SEP-04:10 |
October | 2263.36 | 01-OCT-23:10 | 1867.32 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 126.00 | 30-OCT-04:00 |
November | 2263.36 | 01-NOV-00:10 | 1867.32 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 174.84 | 29-NOV-06:00 |
December | 2263.36 | 01-DEC-00:10 | 1867.32 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 223.20 | 24-DEC-06:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.71 | ||||
Maximum of Months | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.05 | 238.88 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.88 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 208.19 | 06-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 177.88 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 200.74 | 14-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 177.88 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 180.30 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 177.88 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.66 | 23-APR-16:00 | 118.68 | 05-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 177.88 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.98 | 25-MAY-17:00 | 82.24 | 01-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 177.88 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.92 | 29-JUN-16:00 | 63.98 | 04-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 177.88 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.61 | 15-JUL-15:10 | 46.85 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 177.88 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.16 | 08-AUG-16:00 | 52.87 | 19-AUG-04:00 |
September | 180.00 | 01-SEP-00:10 | 177.88 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.19 | 01-SEP-16:00 | 64.05 | 06-SEP-04:10 |
October | 180.00 | 01-OCT-00:10 | 177.88 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.68 | 19-OCT-15:10 | 104.80 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 177.88 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 145.21 | 29-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 177.88 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 192.64 | 24-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.85 | |||||
Maximum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 38.92 | 208.19 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.86 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 205.59 | 06-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 177.86 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 200.73 | 14-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 177.86 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 180.28 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 177.86 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.66 | 23-APR-16:00 | 118.67 | 05-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 177.86 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.97 | 25-MAY-17:00 | 82.24 | 01-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 177.86 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.92 | 29-JUN-16:00 | 63.98 | 04-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 177.86 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.61 | 15-JUL-15:10 | 46.85 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 177.86 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.16 | 08-AUG-15:10 | 52.86 | 19-AUG-04:00 |
September | 180.00 | 01-SEP-00:10 | 177.86 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.21 | 01-SEP-15:10 | 64.05 | 06-SEP-04:10 |
October | 180.00 | 01-OCT-00:10 | 177.86 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.68 | 19-OCT-15:07 | 104.79 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 177.86 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 145.20 | 29-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 177.86 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 192.08 | 24-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.85 | |||||
Maximum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 38.92 | 205.59 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 111.82 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 107.32 | 06-JAN-07:10 |
February | 180.00 | 01-FEB-00:10 | 111.82 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 102.70 | 14-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 111.82 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 92.25 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 111.82 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.01 | 23-APR-16:00 | 60.72 | 05-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 111.82 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.75 | 25-MAY-17:00 | 42.08 | 01-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 111.82 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.92 | 29-JUN-16:00 | 32.74 | 04-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 111.82 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.13 | 15-JUL-15:08 | 23.97 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 111.82 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.90 | 08-AUG-15:10 | 27.05 | 19-AUG-04:00 |
September | 180.00 | 01-SEP-00:10 | 111.82 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.27 | 01-SEP-16:00 | 32.77 | 06-SEP-04:10 |
October | 180.00 | 01-OCT-00:10 | 111.82 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.25 | 19-OCT-15:10 | 53.62 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 111.82 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 74.30 | 29-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 111.82 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 98.56 | 24-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.97 | |||||
Maximum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 19.92 | 107.32 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2988.03 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 475.61 | 06-JAN-05:00 |
February | 26988.77 | 01-FEB-00:10 | 2988.03 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 470.61 | 14-FEB-07:00 |
March | 26988.77 | 01-MAR-00:10 | 2988.03 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 434.44 | 05-MAR-07:00 |
April | 26988.77 | 01-APR-00:10 | 2988.03 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.11 | 23-APR-16:00 | 313.59 | 05-APR-06:00 |
May | 26988.77 | 01-MAY-00:10 | 2988.03 | 01-MAY-19:30 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.21 | 25-MAY-18:00 | 223.88 | 01-MAY-06:00 |
June | 26988.77 | 01-JUN-00:10 | 2988.03 | 01-JUN-19:49 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.16 | 29-JUN-16:00 | 178.63 | 04-JUN-05:00 |
July | 26988.77 | 01-JUL-00:10 | 2988.03 | 07-JUL-19:30 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.81 | 15-JUL-14:00 | 136.24 | 02-JUL-05:00 |
August | 26988.77 | 01-AUG-00:10 | 2988.03 | 01-AUG-19:40 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.93 | 08-AUG-15:50 | 151.23 | 19-AUG-04:00 |
September | 26988.77 | 01-SEP-00:10 | 2988.03 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.20 | 01-SEP-15:40 | 178.85 | 06-SEP-04:10 |
October | 26988.77 | 01-OCT-23:10 | 2988.03 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 279.52 | 30-OCT-04:00 |
November | 26988.77 | 01-NOV-00:10 | 2988.03 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 378.09 | 29-NOV-06:00 |
December | 26988.77 | 01-DEC-00:10 | 2988.03 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 455.08 | 24-DEC-23:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.24 | |||||
Maximum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 75.16 | 475.61 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2988.03 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 475.17 | 06-JAN-05:00 |
February | 26988.77 | 01-FEB-00:10 | 2988.03 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 470.83 | 14-FEB-07:00 |
March | 26988.77 | 01-MAR-00:10 | 2988.03 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 435.24 | 05-MAR-07:00 |
April | 26988.77 | 01-APR-00:10 | 2988.03 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.11 | 23-APR-16:00 | 313.60 | 05-APR-06:00 |
May | 26988.77 | 01-MAY-00:10 | 2988.03 | 01-MAY-19:30 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.21 | 25-MAY-18:00 | 223.88 | 01-MAY-06:00 |
June | 26988.77 | 01-JUN-00:10 | 2988.03 | 01-JUN-19:49 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.16 | 29-JUN-16:00 | 178.63 | 04-JUN-05:00 |
July | 26988.77 | 01-JUL-00:10 | 2988.03 | 07-JUL-19:30 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.81 | 15-JUL-14:00 | 136.24 | 02-JUL-05:00 |
August | 26988.77 | 01-AUG-00:10 | 2988.03 | 01-AUG-19:40 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.93 | 08-AUG-15:50 | 151.23 | 19-AUG-04:00 |
September | 26988.77 | 01-SEP-00:10 | 2988.03 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.20 | 01-SEP-15:40 | 178.85 | 06-SEP-04:10 |
October | 26988.77 | 01-OCT-23:10 | 2988.03 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 279.53 | 30-OCT-04:00 |
November | 26988.77 | 01-NOV-00:10 | 2988.03 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 379.02 | 29-NOV-06:00 |
December | 26988.77 | 01-DEC-00:10 | 2988.03 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 456.22 | 24-DEC-23:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.24 | |||||
Maximum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 75.16 | 475.17 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 1060.81 | 02-JAN-20:10 | 14912.86 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 410.38 | 06-JAN-08:20 |
February | 2401.70 | 01-FEB-00:10 | 1060.81 | 01-FEB-20:10 | 14912.86 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 397.52 | 14-FEB-07:30 |
March | 2401.70 | 01-MAR-00:10 | 1060.81 | 01-MAR-20:10 | 14912.86 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 366.65 | 15-MAR-07:20 |
April | 2401.70 | 01-APR-00:10 | 1060.81 | 03-APR-19:10 | 14912.86 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 16.29 | 23-APR-16:00 | 280.70 | 05-APR-06:00 |
May | 2401.70 | 01-MAY-00:10 | 1060.81 | 01-MAY-19:10 | 14912.86 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 33.39 | 25-MAY-18:00 | 200.39 | 01-MAY-06:00 |
June | 2401.70 | 01-JUN-00:10 | 1060.81 | 01-JUN-19:10 | 14912.86 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 67.36 | 29-JUN-16:00 | 159.86 | 04-JUN-05:00 |
July | 2401.70 | 01-JUL-00:10 | 1060.81 | 03-JUL-19:10 | 14912.86 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 43.74 | 15-JUL-14:00 | 121.96 | 02-JUL-05:00 |
August | 2401.70 | 01-AUG-00:10 | 1060.81 | 01-AUG-19:10 | 14912.86 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 41.19 | 08-AUG-15:50 | 134.37 | 19-AUG-05:00 |
September | 2401.70 | 01-SEP-00:10 | 1060.81 | 01-SEP-19:10 | 14912.86 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 12.79 | 01-SEP-15:40 | 159.10 | 06-SEP-05:00 |
October | 2401.70 | 01-OCT-23:10 | 1060.81 | 02-OCT-19:10 | 14912.86 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 249.14 | 30-OCT-05:10 |
November | 2401.70 | 01-NOV-00:10 | 1060.81 | 01-NOV-19:10 | 14912.86 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 334.60 | 29-NOV-06:10 |
December | 2401.70 | 01-DEC-00:10 | 1060.81 | 01-DEC-20:10 | 14912.86 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 391.18 | 24-DEC-09:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2401.70 | 1060.81 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 0.00 | 121.96 | ||||||
Maximum of Months | 2401.70 | 1060.81 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 67.36 | 410.38 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2395.44 | 02-JAN-00:10 | 1976.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 405.05 | 06-JAN-09:00 |
February | 2395.44 | 01-FEB-00:10 | 1976.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 405.24 | 14-FEB-07:00 |
March | 2395.44 | 01-MAR-00:10 | 1976.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 369.67 | 05-MAR-07:00 |
April | 2395.44 | 01-APR-00:10 | 1976.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.43 | 23-APR-16:00 | 253.13 | 05-APR-06:00 |
May | 2395.44 | 01-MAY-00:10 | 1976.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.28 | 25-MAY-18:00 | 175.18 | 01-MAY-06:00 |
June | 2395.44 | 01-JUN-00:10 | 1976.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.84 | 29-JUN-16:00 | 138.83 | 04-JUN-05:00 |
July | 2395.44 | 01-JUL-00:10 | 1976.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.76 | 15-JUL-14:00 | 110.52 | 02-JUL-05:00 |
August | 2395.44 | 01-AUG-00:10 | 1976.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.30 | 08-AUG-16:00 | 115.99 | 19-AUG-04:00 |
September | 2395.44 | 01-SEP-00:10 | 1976.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.42 | 01-SEP-15:30 | 142.23 | 06-SEP-04:00 |
October | 2395.44 | 01-OCT-23:10 | 1976.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 223.42 | 30-OCT-04:00 |
November | 2395.44 | 01-NOV-00:10 | 1976.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 309.87 | 29-NOV-06:00 |
December | 2395.44 | 01-DEC-00:10 | 1976.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 386.85 | 24-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.52 | ||||
Maximum of Months | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.84 | 405.24 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 33032.77 | 25-JAN-23:33 | 34505.68 | 13190.31 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 30953.63 | 13-FEB-23:01 | 92015.14 | 35174.16 | 32446.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 29750.22 | 12-MAR-03:51 | 89459.16 | 29311.22 | 30418.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 13449.95 | 22-APR-10:33 | 11501.89 | 10992.10 | 10646.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 14110.81 | 18-MAY-10:33 | 7667.93 | 10992.10 | 10646.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 14848.06 | 25-JUN-10:33 | 11501.89 | 13190.31 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 15707.84 | 23-JUL-10:33 | 11501.89 | 13190.31 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 19605.66 | 31-AUG-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 20849.16 | 08-SEP-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 21280.06 | 20-OCT-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 20587.64 | 17-NOV-22:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 32832.21 | 02-DEC-06:00 | 11501.89 | 1465.65 | 2027.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 13449.95 | 7667.93 | 1465.65 | 2027.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33032.77 | 92015.14 | 35174.16 | 32446.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2453.75 | 27-JAN-13:30 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 229.17 |
February | 3803.05 | 28-FEB-13:30 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.29 |
March | 3684.34 | 20-MAR-12:30 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.45 |
April | 3925.00 | 13-APR-13:10 | 519.79 | 332.00 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.47 |
May | 3843.75 | 18-MAY-13:10 | 519.79 | 332.00 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 21.28 | 0.00 |
June | 3917.45 | 30-JUN-13:00 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 37.82 | 0.00 |
July | 4057.34 | 23-JUL-13:10 | 259.90 | 132.80 | 216.51 | 0.00 | 0.00 | 0.00 | 0.00 | 29.71 | 0.00 |
August | 4488.59 | 26-AUG-12:40 | 389.84 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 7.09 | 0.00 |
September | 4500.65 | 01-SEP-13:15 | 519.79 | 332.00 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 4.02 | 0.00 |
October | 5193.68 | 22-OCT-12:40 | 259.90 | 132.80 | 216.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.20 |
November | 3562.97 | 17-NOV-12:40 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.53 |
December | 2716.51 | 10-DEC-12:30 | 1949.22 | 995.99 | 1443.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 270.81 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2453.75 | 259.90 | 132.80 | 216.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5193.68 | 1949.22 | 995.99 | 1443.38 | 0.00 | 0.00 | 0.00 | 0.00 | 37.82 | 270.81 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2645.76 | 25-JAN-20:01 | 8426.88 | 5536.12 | 6351.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.42 |
February | 2595.20 | 24-FEB-22:52 | 6771.60 | 2306.72 | 2925.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.77 |
March | 2640.99 | 07-MAR-00:51 | 12188.88 | 1384.03 | 2256.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.81 |
April | 1465.42 | 13-APR-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.22 |
May | 1907.23 | 25-MAY-20:55 | 2407.68 | 1230.25 | 1504.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.35 |
June | 2127.47 | 30-JUN-20:10 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.46 |
July | 2008.26 | 24-JUL-20:05 | 2407.68 | 1230.25 | 1504.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.30 |
August | 1916.92 | 25-AUG-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.41 |
September | 1833.93 | 01-SEP-20:10 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.19 |
October | 1526.53 | 20-OCT-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.34 |
November | 1200.55 | 17-NOV-21:00 | 1053.36 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.79 |
December | 1994.73 | 02-DEC-00:22 | 6771.60 | 768.91 | 1253.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1200.55 | 1053.36 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.46 | |
Maximum of Months | 2645.76 | 12188.88 | 5536.12 | 6351.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.81 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 658.08 | 19-JAN-21:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.07 |
February | 714.88 | 08-FEB-21:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.14 |
March | 779.16 | 29-MAR-10:33 | 190.94 | 570.15 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.81 |
April | 918.41 | 18-APR-10:33 | 190.94 | 570.15 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.79 |
May | 1153.43 | 25-MAY-20:55 | 509.18 | 1216.31 | 1590.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.56 |
June | 1699.08 | 30-JUN-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 0.00 |
July | 1507.13 | 24-JUL-19:55 | 445.54 | 1368.35 | 1678.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.73 |
August | 1281.08 | 09-AUG-21:00 | 254.59 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.57 |
September | 1188.22 | 01-SEP-21:00 | 254.59 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.80 |
October | 985.25 | 22-OCT-10:33 | 286.42 | 684.18 | 1060.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.19 |
November | 774.00 | 01-NOV-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.81 |
December | 661.49 | 05-DEC-21:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.95 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 658.08 | 190.94 | 570.15 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1699.08 | 509.18 | 1368.35 | 1678.89 | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 124.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 122.72 | 19-JAN-22:00 | 195.84 | 223.85 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.27 |
February | 354.63 | 22-FEB-22:00 | 195.84 | 223.85 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.89 |
March | 425.56 | 28-MAR-20:00 | 171.36 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.82 |
April | 535.50 | 18-APR-10:33 | 146.88 | 209.86 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.80 |
May | 637.26 | 18-MAY-10:33 | 146.88 | 209.86 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 8.57 | 0.00 |
June | 835.09 | 30-JUN-19:20 | 171.36 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 7.02 | 0.00 |
July | 689.51 | 23-JUL-10:33 | 220.32 | 251.83 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 11.01 | 0.00 |
August | 659.39 | 26-AUG-10:33 | 220.32 | 209.86 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.99 |
September | 650.45 | 01-SEP-10:33 | 146.88 | 209.86 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.82 |
October | 572.17 | 22-OCT-10:33 | 220.32 | 251.83 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.53 |
November | 429.62 | 01-NOV-20:00 | 171.36 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.09 |
December | 175.95 | 05-DEC-22:00 | 195.84 | 223.85 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.87 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 122.72 | 146.88 | 209.86 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 835.09 | 220.32 | 251.84 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 11.01 | 79.89 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 41178.81 | 25-JAN-20:01 | 5644.80 | 2600.67 | 36582.41 | 317812.61 | 0.00 | 0.00 | 0.00 | 0.00 | 357.48 |
February | 39364.57 | 13-FEB-21:22 | 4838.40 | 1733.78 | 25992.76 | 225814.22 | 0.00 | 0.00 | 0.00 | 0.00 | 357.89 |
March | 37271.80 | 31-MAR-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 123.65 |
April | 37961.78 | 13-APR-19:55 | 1411.20 | 650.17 | 9145.60 | 79453.15 | 0.00 | 0.00 | 0.00 | 0.00 | 61.22 |
May | 38669.93 | 18-MAY-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 18.52 |
June | 38867.73 | 28-JUN-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 6.26 | 0.00 |
July | 38747.12 | 21-JUL-20:00 | 1411.20 | 650.17 | 9145.60 | 79453.15 | 0.00 | 0.00 | 0.00 | 0.00 | 11.46 |
August | 38642.74 | 08-AUG-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 6.31 | 0.00 |
September | 38494.05 | 01-SEP-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 47.14 |
October | 37965.84 | 19-OCT-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 70.41 |
November | 37282.12 | 01-NOV-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 69.01 |
December | 39654.82 | 23-DEC-21:42 | 4233.60 | 1517.06 | 23104.68 | 200723.75 | 0.00 | 0.00 | 0.00 | 0.00 | 353.84 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 37271.80 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 41178.81 | 5644.80 | 2600.67 | 36582.41 | 317812.61 | 0.00 | 0.00 | 0.00 | 6.31 | 357.89 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10205.21 | 27-JAN-13:30 | 3415.20 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 506.57 |
February | 13973.99 | 28-FEB-13:20 | 3415.20 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 258.60 |
March | 15751.46 | 07-MAR-00:41 | 122947.20 | 3024.94 | 2438.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 604.37 |
April | 14605.10 | 22-APR-13:10 | 10245.60 | 207.96 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.90 |
May | 13402.01 | 06-MAY-13:00 | 5122.80 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.22 |
June | 12890.14 | 30-JUN-15:03 | 51228.00 | 623.89 | 2133.76 | 0.00 | 0.00 | 0.00 | 0.00 | 88.11 | 0.00 |
July | 14203.37 | 29-JUL-13:00 | 5122.80 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 53.53 | 0.00 |
August | 15633.14 | 26-AUG-12:40 | 5122.80 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 15.68 | 0.00 |
September | 15187.86 | 01-SEP-13:15 | 6830.40 | 207.96 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 8.88 | 0.00 |
October | 18167.63 | 22-OCT-12:00 | 5122.80 | 124.78 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.66 |
November | 13168.89 | 17-NOV-12:40 | 3415.20 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.17 |
December | 11493.65 | 10-DEC-12:22 | 25614.00 | 623.89 | 2032.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 598.67 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10205.21 | 3415.20 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18167.63 | 122947.20 | 3024.94 | 2438.58 | 0.00 | 0.00 | 0.00 | 0.00 | 88.11 | 604.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 60138.00 | 25-JAN-20:01 | 283876.32 | 76038.40 | 80233.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1757.49 |
February | 58504.01 | 24-FEB-22:52 | 228114.90 | 31682.67 | 36949.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1756.83 |
March | 59650.33 | 07-MAR-00:51 | 410606.82 | 19009.60 | 28504.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1758.80 |
April | 33849.01 | 13-APR-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 356.29 |
May | 38861.57 | 25-MAY-21:10 | 91245.96 | 12673.07 | 14779.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.29 |
June | 41179.65 | 29-JUN-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 113.95 | 0.00 |
July | 40150.31 | 24-JUL-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.21 |
August | 39388.15 | 25-AUG-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 209.20 |
September | 38739.86 | 01-SEP-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 302.51 |
October | 35770.19 | 19-OCT-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 377.75 |
November | 27680.54 | 17-NOV-21:00 | 35484.54 | 9504.80 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 694.61 |
December | 57881.55 | 02-DEC-00:31 | 364983.84 | 16897.42 | 25336.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1740.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 27680.54 | 35484.54 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 60138.00 | 410606.82 | 76038.40 | 80233.67 | 0.00 | 0.00 | 0.00 | 0.00 | 113.95 | 1758.80 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3993.61 | 27-JAN-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.15 |
February | 4297.37 | 28-FEB-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.25 |
March | 4334.61 | 31-MAR-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.23 |
April | 4418.87 | 13-APR-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.18 |
May | 4427.85 | 14-MAY-18:01 | 819.00 | 1245.18 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.57 |
June | 3847.56 | 12-JUN-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.38 |
July | 3797.44 | 25-JUL-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.39 |
August | 3758.83 | 29-AUG-18:02 | 831.60 | 949.89 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 2.32 | 0.00 |
September | 4368.76 | 09-SEP-18:01 | 819.00 | 1245.18 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.30 |
October | 4226.80 | 21-OCT-18:01 | 819.00 | 1245.18 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.46 |
November | 4226.41 | 17-NOV-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.97 |
December | 348.42 | 28-DEC-16:05 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 348.42 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4427.85 | 831.60 | 1245.18 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 2.32 | 123.15 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 566.69 | 27-JAN-16:04 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.58 |
February | 3960.94 | 28-FEB-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.86 |
March | 4069.42 | 31-MAR-15:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.70 |
April | 4848.04 | 11-APR-18:11 | 1386.00 | 1582.97 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.55 |
May | 5227.37 | 06-MAY-18:42 | 702.00 | 1067.17 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.46 |
June | 4231.39 | 07-JUN-21:41 | 1800.00 | 1191.67 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.72 |
July | 4272.84 | 04-JUL-16:51 | 954.00 | 586.94 | 1053.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.21 |
August | 4260.80 | 07-AUG-16:21 | 972.00 | 498.01 | 1264.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.98 |
September | 4598.16 | 23-SEP-17:41 | 777.60 | 1209.46 | 1011.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.12 |
October | 3887.10 | 21-OCT-18:32 | 702.00 | 1067.17 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.14 |
November | 3272.53 | 17-NOV-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.45 |
December | 244.72 | 05-DEC-19:06 | 970.20 | 1108.08 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.54 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 244.72 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.21 | |
Maximum of Months | 5227.37 | 1800.00 | 1582.97 | 1264.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.58 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 235.06 | 04-JAN-15:03 | 0.00 | 93.91 | 92.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.66 |
February | 300.08 | 28-FEB-14:35 | 0.00 | 62.60 | 61.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.84 |
March | 599.44 | 20-MAR-12:30 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.06 |
April | 671.76 | 13-APR-13:00 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.31 |
May | 629.05 | 18-MAY-13:05 | 0.00 | 62.60 | 61.92 | 0.00 | 0.00 | 0.00 | 0.00 | 1.25 | 0.00 |
June | 612.63 | 30-JUN-13:00 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 3.97 | 0.00 |
July | 657.23 | 23-JUL-13:20 | 0.00 | 36.89 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 2.64 | 0.00 |
August | 732.88 | 25-AUG-13:05 | 0.00 | 62.60 | 61.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.55 | 0.00 |
September | 746.14 | 01-SEP-13:05 | 0.00 | 62.60 | 61.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.73 |
October | 909.20 | 22-OCT-12:30 | 0.00 | 36.89 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.71 |
November | 530.17 | 17-NOV-12:20 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.08 |
December | 95.04 | 02-DEC-15:20 | 0.00 | 36.89 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 95.04 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 909.20 | 0.00 | 93.91 | 92.88 | 0.00 | 0.00 | 0.00 | 0.00 | 3.97 | 48.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 232.87 | 20-JAN-19:05 | 831.60 | 597.13 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.27 |
February | 605.32 | 05-FEB-09:01 | 378.00 | 438.35 | 1119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.81 |
March | 1105.66 | 28-MAR-18:01 | 970.20 | 696.66 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.71 |
April | 1175.01 | 13-APR-19:41 | 1386.00 | 1118.23 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.56 |
May | 1258.90 | 21-MAY-21:01 | 1386.00 | 950.49 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.86 |
June | 1248.52 | 07-JUN-08:51 | 288.00 | 393.62 | 887.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.54 |
July | 1204.43 | 01-JUL-21:01 | 1386.00 | 950.49 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.74 |
August | 1149.80 | 01-AUG-21:11 | 1800.00 | 749.21 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.20 |
September | 1243.23 | 04-SEP-18:01 | 1170.00 | 1118.23 | 1187.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.90 |
October | 1122.98 | 20-OCT-18:11 | 970.20 | 696.66 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.32 |
November | 947.65 | 21-NOV-19:02 | 831.60 | 597.13 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.68 |
December | 272.54 | 05-DEC-19:03 | 970.20 | 696.66 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.85 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 232.87 | 288.00 | 393.62 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.54 | |
Maximum of Months | 1258.90 | 1800.00 | 1118.23 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.27 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 543.98 | 17-JAN-16:04 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.96 |
February | 3872.74 | 28-FEB-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.63 |
March | 3930.82 | 11-MAR-09:01 | 378.00 | 697.30 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.25 |
April | 4012.50 | 22-APR-08:62 | 324.00 | 597.68 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.76 |
May | 3997.54 | 14-MAY-15:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.89 |
June | 3988.47 | 01-JUN-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.53 |
July | 3620.47 | 29-JUL-08:61 | 378.00 | 697.30 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 3.90 | 0.00 |
August | 3537.72 | 24-AUG-08:62 | 216.00 | 469.61 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.60 |
September | 3932.89 | 09-SEP-18:01 | 819.00 | 1245.18 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.73 |
October | 3892.65 | 21-OCT-18:01 | 819.00 | 1245.18 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.61 |
November | 3748.21 | 17-NOV-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.49 |
December | 691.09 | 01-DEC-09:03 | 216.00 | 469.61 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 543.98 | 216.00 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4012.50 | 970.20 | 1245.18 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 3.90 | 149.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 227.67 | 19-JAN-19:06 | 970.20 | 1108.08 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.25 |
February | 1375.62 | 27-FEB-09:02 | 216.00 | 469.55 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.25 |
March | 3597.07 | 11-MAR-09:01 | 378.00 | 697.22 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.35 |
April | 3845.47 | 22-APR-19:21 | 1170.00 | 1778.61 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.89 |
May | 3998.91 | 06-MAY-19:01 | 1170.00 | 1778.61 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.51 |
June | 4229.12 | 28-JUN-07:52 | 464.40 | 469.55 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.16 |
July | 4307.35 | 31-JUL-08:32 | 216.00 | 469.55 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.65 |
August | 4013.90 | 11-AUG-08:51 | 360.00 | 782.59 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.55 |
September | 4026.72 | 04-SEP-18:01 | 1170.00 | 1778.61 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.01 |
October | 3289.01 | 21-OCT-18:32 | 702.00 | 1067.17 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.19 |
November | 1719.94 | 16-NOV-09:01 | 252.00 | 547.81 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.94 |
December | 226.71 | 05-DEC-19:06 | 970.20 | 1108.08 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.54 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 226.71 | 216.00 | 469.55 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.16 | |
Maximum of Months | 4307.35 | 1170.00 | 1778.61 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.25 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1960.55 | 26-JAN-07:00 | 1760.39 | 829.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 232.35 |
February | 1988.53 | 14-FEB-07:00 | 1760.39 | 829.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 234.04 |
March | 1833.14 | 20-MAR-10:33 | 1508.90 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.28 |
April | 2232.24 | 22-APR-10:33 | 2263.36 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.49 |
May | 2512.01 | 18-MAY-10:33 | 1508.90 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.94 | 0.00 |
June | 3014.35 | 30-JUN-19:20 | 1760.39 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.21 | 0.00 |
July | 2688.19 | 01-JUL-10:33 | 2263.36 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.60 |
August | 2602.77 | 26-AUG-10:33 | 2263.36 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.22 |
September | 2519.58 | 01-SEP-10:33 | 1508.90 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.97 |
October | 2256.20 | 22-OCT-10:33 | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.52 |
November | 1714.08 | 17-NOV-11:33 | 1508.90 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.22 |
December | 1634.11 | 24-DEC-23:53 | 8047.49 | 2489.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 222.18 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 1634.11 | 1508.90 | 829.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3014.35 | 8047.49 | 2489.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.94 | 234.04 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3457.67 | 27-JAN-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.24 |
February | 4456.88 | 28-FEB-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.37 |
March | 4495.77 | 19-MAR-15:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.95 |
April | 4591.61 | 13-APR-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.35 |
May | 4608.60 | 14-MAY-18:01 | 819.00 | 1245.18 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.81 |
June | 4584.30 | 16-JUN-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.89 |
July | 3936.12 | 30-JUL-18:01 | 819.00 | 1245.18 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 4.32 | 0.00 |
August | 3928.44 | 30-AUG-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 3.47 | 0.00 |
September | 4571.38 | 04-SEP-18:01 | 1170.00 | 1778.82 | 1211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.02 |
October | 4375.50 | 21-OCT-18:01 | 819.00 | 1245.18 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.52 |
November | 4380.83 | 17-NOV-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.07 |
December | 428.69 | 28-DEC-16:05 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.73 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 428.69 | 378.00 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4608.60 | 1170.00 | 1778.82 | 1211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 4.32 | 123.24 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 799.02 | 20-JAN-16:04 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.25 |
February | 3887.23 | 28-FEB-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.42 |
March | 4203.04 | 31-MAR-18:01 | 970.20 | 1108.08 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.30 |
April | 5062.07 | 11-APR-18:11 | 1386.00 | 1582.97 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.15 |
May | 5466.05 | 06-MAY-18:42 | 702.00 | 1067.17 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.11 |
June | 4416.21 | 07-JUN-21:41 | 1800.00 | 1191.67 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.69 |
July | 4595.69 | 26-JUL-20:52 | 961.20 | 949.78 | 1090.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.78 |
August | 4687.88 | 02-AUG-20:02 | 961.20 | 949.78 | 1090.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.20 |
September | 5034.47 | 04-SEP-18:01 | 1170.00 | 1778.61 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.32 |
October | 4024.40 | 21-OCT-18:32 | 702.00 | 1067.17 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.40 |
November | 2019.86 | 17-NOV-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.41 |
December | 0.00 | 01-DEC-00:03 | 540.00 | 117.39 | 134.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.46 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 540.00 | 117.39 | 134.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.40 | |
Maximum of Months | 5466.05 | 1800.00 | 1778.61 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2608.94 | 05-JAN-16:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.96 |
February | 2514.85 | 28-FEB-16:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.72 |
March | 2529.26 | 17-MAR-15:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.10 |
April | 2558.76 | 13-APR-15:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.93 |
May | 2528.86 | 14-MAY-15:01 | 378.00 | 258.31 | 379.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.82 |
June | 2497.13 | 16-JUN-18:01 | 970.20 | 696.66 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.82 |
July | 2206.12 | 04-JUL-18:01 | 819.00 | 782.76 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 | 0.00 |
August | 2193.30 | 30-AUG-18:01 | 970.20 | 696.66 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 1.53 | 0.00 |
September | 2467.17 | 05-SEP-18:01 | 970.20 | 696.66 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.79 |
October | 2465.06 | 21-OCT-18:01 | 819.00 | 782.76 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.43 |
November | 2467.38 | 10-NOV-16:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.47 |
December | 2444.06 | 02-DEC-16:01 | 378.00 | 258.31 | 379.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.11 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2193.30 | 378.00 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2608.94 | 970.20 | 782.76 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 1.53 | 89.96 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 26674.63 | 25-JAN-20:01 | 167930.11 | 23904.24 | 53983.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 405.29 |
February | 25682.63 | 24-FEB-22:52 | 134943.84 | 9960.10 | 33739.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 403.22 |
March | 25963.64 | 12-MAR-03:51 | 209912.64 | 6640.07 | 22493.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 403.39 |
April | 19790.27 | 13-APR-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.68 |
May | 22364.92 | 25-MAY-21:10 | 53977.54 | 3984.04 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.43 |
June | 23154.88 | 29-JUN-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 23.59 | 0.00 |
July | 22631.01 | 21-JUL-21:52 | 269887.68 | 19920.20 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.41 |
August | 22149.35 | 08-AUG-21:52 | 215910.14 | 15936.16 | 53983.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.49 |
September | 21192.98 | 01-SEP-21:22 | 242898.91 | 17928.18 | 60731.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.45 |
October | 19446.87 | 19-OCT-22:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.43 |
November | 18731.62 | 01-NOV-22:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.47 |
December | 25092.33 | 13-DEC-04:21 | 269887.68 | 3320.03 | 22493.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 394.66 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 18731.62 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26674.63 | 269887.68 | 23904.24 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 23.59 | 405.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 28346.48 | 25-JAN-20:01 | 167930.11 | 23904.24 | 53983.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 407.79 |
February | 27215.08 | 24-FEB-22:52 | 134943.84 | 9960.10 | 33739.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 405.23 |
March | 27536.43 | 12-MAR-03:51 | 209912.64 | 6640.07 | 22493.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 405.51 |
April | 21468.01 | 13-APR-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.68 |
May | 23613.12 | 25-MAY-21:10 | 53977.54 | 3984.04 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.43 |
June | 24366.53 | 29-JUN-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 23.57 | 0.00 |
July | 23812.65 | 21-JUL-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.44 |
August | 23441.62 | 08-AUG-21:05 | 53977.54 | 3984.04 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.77 |
September | 22460.32 | 01-SEP-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.62 |
October | 21131.39 | 19-OCT-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.52 |
November | 20741.72 | 01-NOV-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.45 |
December | 26676.60 | 23-DEC-21:42 | 125947.58 | 13944.14 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 399.61 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 20741.72 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28346.48 | 209912.64 | 23904.24 | 53983.22 | 0.00 | 0.00 | 0.00 | 0.00 | 23.57 | 407.79 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 29138.60 | 25-JAN-20:01 | 14943.94 | 8486.47 | 119302.85 | 119961.77 | 0.00 | 0.00 | 0.00 | 0.00 | 364.94 |
February | 28737.14 | 01-FEB-18:11 | 9339.96 | 4950.44 | 104389.99 | 157449.82 | 0.00 | 0.00 | 0.00 | 0.00 | 365.06 |
March | 29131.52 | 26-MAR-10:37 | 2401.70 | 1060.81 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 137.35 |
April | 30613.97 | 22-APR-10:33 | 2401.70 | 884.01 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 64.57 |
May | 31537.05 | 18-MAY-10:33 | 1601.14 | 884.01 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 12.63 | 0.00 |
June | 32072.56 | 25-JUN-10:40 | 2401.70 | 1060.81 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 20.29 | 0.00 |
July | 32139.23 | 29-JUL-10:40 | 2401.70 | 884.01 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 20.01 | 0.00 |
August | 31588.85 | 25-AUG-10:33 | 1601.14 | 884.01 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 1.13 | 0.00 |
September | 31374.90 | 01-SEP-10:33 | 1601.14 | 884.01 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 8.53 |
October | 30082.99 | 22-OCT-10:33 | 2401.70 | 1060.81 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 58.81 |
November | 27243.58 | 17-NOV-11:50 | 533.71 | 294.67 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 105.74 |
December | 28102.59 | 23-DEC-21:42 | 11207.95 | 4950.44 | 89477.13 | 67478.50 | 0.00 | 0.00 | 0.00 | 0.00 | 361.21 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 27243.58 | 533.71 | 294.67 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32139.23 | 14943.94 | 8486.47 | 119302.85 | 157449.82 | 0.00 | 0.00 | 0.00 | 20.29 | 365.06 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1445.71 | 27-JAN-13:50 | 532.32 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 260.19 |
February | 3381.40 | 22-FEB-11:33 | 1596.96 | 1646.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.40 |
March | 3662.93 | 26-MAR-10:33 | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.88 |
April | 4387.78 | 18-APR-10:33 | 1596.96 | 1646.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.19 |
May | 5499.93 | 18-MAY-14:10 | 798.48 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.71 | 0.00 |
June | 6815.56 | 30-JUN-13:20 | 532.32 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.16 | 0.00 |
July | 6670.37 | 23-JUL-13:20 | 532.32 | 439.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.27 | 0.00 |
August | 5672.53 | 24-AUG-14:20 | 798.48 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.93 | 0.00 |
September | 5405.10 | 01-SEP-15:03 | 7984.80 | 3293.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.42 | 0.00 |
October | 4526.21 | 22-OCT-10:33 | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.01 |
November | 3470.00 | 17-NOV-11:33 | 1596.96 | 1646.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.29 |
December | 1567.03 | 05-DEC-22:10 | 2395.44 | 1317.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.35 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 1445.71 | 532.32 | 439.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6815.56 | 7984.80 | 3293.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.16 | 260.19 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.384828E+12 | 228557.70 | 13-JAN-07:10 | 0.128661E+13 | 1108761.49 | 05-JAN-21:00 |
February | 0.344138E+12 | 226743.77 | 14-FEB-07:10 | 0.878310E+12 | 1041522.45 | 01-FEB-19:10 |
March | 0.379570E+12 | 224512.86 | 28-MAR-18:40 | 0.742323E+12 | 863438.71 | 05-MAR-07:10 |
April | 0.372712E+12 | 282443.16 | 23-APR-18:10 | 0.513509E+12 | 548792.98 | 19-APR-17:10 |
May | 0.418650E+12 | 331873.65 | 25-MAY-18:10 | 0.487205E+12 | 527787.31 | 08-MAY-18:49 |
June | 0.460171E+12 | 413449.13 | 29-JUN-18:10 | 0.426267E+12 | 503528.88 | 02-JUN-20:00 |
July | 0.511017E+12 | 382018.19 | 21-JUL-19:19 | 0.420091E+12 | 438607.41 | 07-JUL-21:00 |
August | 0.467631E+12 | 356356.57 | 08-AUG-18:10 | 0.415263E+12 | 468533.25 | 18-AUG-20:00 |
September | 0.390792E+12 | 273533.97 | 01-SEP-18:10 | 0.475782E+12 | 499603.77 | 28-SEP-19:30 |
October | 0.385102E+12 | 233939.27 | 20-OCT-18:19 | 0.522982E+12 | 546076.36 | 03-OCT-17:49 |
November | 0.367862E+12 | 225797.21 | 03-NOV-06:00 | 0.617003E+12 | 595946.79 | 25-NOV-19:10 |
December | 0.384781E+12 | 227392.51 | 19-DEC-07:10 | 0.118997E+13 | 1069870.89 | 19-DEC-19:19 |
Annual Sum or Average | 0.486725E+13 | 0.797531E+13 | ||||
Minimum of Months | 0.344138E+12 | 224512.86 | 0.415263E+12 | 438607.41 | ||
Maximum of Months | 0.511017E+12 | 413449.13 | 0.128661E+13 | 1108761.49 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.672242E+11 | 0.212246E+11 | 0.140828E+12 | 0.691146E+11 | 0.433761E+11 | 0.399065E+10 | 0.00 | 0.306465E+09 | 0.00 | 0.00 | 0.257713E+11 | 0.805216E+10 | 0.00 |
February | 0.604087E+11 | 0.174342E+11 | 0.127191E+12 | 0.624261E+11 | 0.368232E+11 | 0.395575E+10 | 0.00 | 0.950337E+09 | 0.00 | 0.00 | 0.231056E+11 | 0.727379E+10 | 0.00 |
March | 0.665308E+11 | 0.169456E+11 | 0.140882E+12 | 0.691168E+11 | 0.401607E+11 | 0.456562E+10 | 0.00 | 0.295347E+10 | 0.00 | 0.00 | 0.252309E+11 | 0.804677E+10 | 0.00 |
April | 0.638559E+11 | 0.140288E+11 | 0.136245E+12 | 0.668842E+11 | 0.396741E+11 | 0.712406E+10 | 0.00 | 0.135404E+11 | 0.00 | 0.00 | 0.185564E+11 | 0.779743E+10 | 0.00 |
May | 0.654368E+11 | 0.123631E+11 | 0.140860E+12 | 0.691148E+11 | 0.450457E+11 | 0.118938E+11 | 0.00 | 0.520139E+11 | 0.00 | 0.00 | 0.863041E+10 | 0.804726E+10 | 0.00 |
June | 0.630504E+11 | 0.108085E+11 | 0.136336E+12 | 0.668860E+11 | 0.456884E+11 | 0.128649E+11 | 0.00 | 0.105218E+12 | 0.00 | 0.00 | 0.638127E+10 | 0.778868E+10 | 0.00 |
July | 0.652926E+11 | 0.117117E+11 | 0.140770E+12 | 0.691122E+11 | 0.486205E+11 | 0.141064E+11 | 0.00 | 0.140857E+12 | 0.00 | 0.00 | 0.716598E+10 | 0.805558E+10 | 0.00 |
August | 0.658326E+11 | 0.135402E+11 | 0.140892E+12 | 0.691164E+11 | 0.474964E+11 | 0.131909E+11 | 0.00 | 0.100006E+12 | 0.00 | 0.00 | 0.416389E+10 | 0.804716E+10 | 0.00 |
September | 0.642088E+11 | 0.153614E+11 | 0.136256E+12 | 0.668845E+11 | 0.429941E+11 | 0.108400E+11 | 0.00 | 0.343896E+11 | 0.00 | 0.00 | 0.694468E+10 | 0.779862E+10 | 0.00 |
October | 0.668409E+11 | 0.183300E+11 | 0.140818E+12 | 0.691144E+11 | 0.416331E+11 | 0.660330E+10 | 0.00 | 0.101683E+11 | 0.00 | 0.00 | 0.183278E+11 | 0.804606E+10 | 0.00 |
November | 0.649892E+11 | 0.198920E+11 | 0.136330E+12 | 0.668858E+11 | 0.391928E+11 | 0.329825E+10 | 0.00 | 0.148444E+10 | 0.00 | 0.00 | 0.230112E+11 | 0.778076E+10 | 0.00 |
December | 0.672746E+11 | 0.217946E+11 | 0.140770E+12 | 0.691135E+11 | 0.431733E+11 | 0.362736E+10 | 0.00 | 0.194968E+09 | 0.00 | 0.00 | 0.257713E+11 | 0.805933E+10 | 0.00 |
Annual Sum or Average | 0.780945E+12 | 0.193435E+12 | 0.165818E+13 | 0.813769E+12 | 0.513878E+12 | 0.960610E+11 | 0.00 | 0.462083E+12 | 0.00 | 0.00 | 0.193061E+12 | 0.947936E+11 | 0.00 |
Minimum of Months | 0.604087E+11 | 0.108085E+11 | 0.127191E+12 | 0.624261E+11 | 0.368232E+11 | 0.329825E+10 | 0.00 | 0.194968E+09 | 0.00 | 0.00 | 0.416389E+10 | 0.727379E+10 | 0.00 |
Maximum of Months | 0.672746E+11 | 0.217946E+11 | 0.140892E+12 | 0.691168E+11 | 0.486205E+11 | 0.141064E+11 | 0.00 | 0.140857E+12 | 0.00 | 0.00 | 0.257713E+11 | 0.805933E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.151918E+12 | 0.00 | 0.865723E+12 | 0.00 | 0.268964E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.495811E+12 | 0.00 | 0.245295E+12 | 0.00 | 0.00 |
March | 0.152024E+12 | 0.00 | 0.319069E+12 | 0.00 | 0.271230E+12 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.107580E+12 | 0.00 | 0.258974E+12 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.733336E+11 | 0.00 | 0.261893E+12 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 0.345877E+11 | 0.00 | 0.244565E+12 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 0.260610E+11 | 0.00 | 0.242210E+12 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 0.264796E+11 | 0.00 | 0.236744E+12 | 0.00 | 0.00 |
September | 0.146971E+12 | 0.00 | 0.988140E+11 | 0.00 | 0.229997E+12 | 0.00 | 0.00 |
October | 0.151903E+12 | 0.00 | 0.126339E+12 | 0.00 | 0.244739E+12 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.222423E+12 | 0.00 | 0.247488E+12 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.774546E+12 | 0.00 | 0.263606E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178884E+13 | 0.00 | 0.317077E+13 | 0.00 | 0.301571E+13 | 0.00 | 0.00 |
Minimum of Months | 0.137204E+12 | 0.00 | 0.260610E+11 | 0.00 | 0.229997E+12 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.865723E+12 | 0.00 | 0.271230E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 64632.59 | 02-JAN-20:10 | 12338.45 | 01-JAN-00:10 | 89171.45 | 02-JAN-07:10 | 49607.07 | 02-JAN-07:19 | 25053.64 | 12-JAN-19:10 | 4950.15 | 26-JAN-10:50 | 0.00 | 01-JAN-00:10 |
February | 64632.59 | 01-FEB-20:10 | 12338.45 | 01-FEB-00:10 | 89171.45 | 01-FEB-07:10 | 49607.07 | 01-FEB-07:19 | 22986.76 | 13-FEB-19:10 | 4874.00 | 14-FEB-10:39 | 0.00 | 01-FEB-00:10 |
March | 64632.59 | 01-MAR-20:10 | 12338.45 | 01-MAR-00:10 | 89171.45 | 01-MAR-07:10 | 49607.07 | 01-MAR-07:19 | 22316.56 | 28-MAR-18:10 | 5188.87 | 31-MAR-15:09 | 0.00 | 01-MAR-00:10 |
April | 64632.59 | 03-APR-19:10 | 12338.45 | 01-APR-00:10 | 89171.45 | 03-APR-06:10 | 49606.67 | 03-APR-06:19 | 27583.97 | 13-APR-21:10 | 6082.32 | 23-APR-18:30 | 0.00 | 01-APR-00:10 |
May | 64632.59 | 01-MAY-19:30 | 12338.45 | 01-MAY-00:10 | 89171.45 | 01-MAY-06:10 | 49605.09 | 22-MAY-06:19 | 31931.93 | 18-MAY-21:00 | 6292.03 | 18-MAY-18:10 | 0.00 | 01-MAY-00:10 |
June | 64632.59 | 01-JUN-19:49 | 12338.45 | 01-JUN-00:10 | 89171.45 | 01-JUN-06:10 | 49605.70 | 09-JUN-06:19 | 34184.40 | 30-JUN-20:10 | 6534.12 | 29-JUN-18:10 | 0.00 | 01-JUN-00:10 |
July | 64632.59 | 07-JUL-19:30 | 12338.45 | 01-JUL-00:10 | 89171.45 | 03-JUL-06:10 | 49605.20 | 03-JUL-06:19 | 33485.66 | 24-JUL-21:00 | 6537.81 | 21-JUL-19:19 | 0.00 | 01-JUL-00:10 |
August | 64632.59 | 01-AUG-19:40 | 12338.45 | 01-AUG-00:10 | 89171.45 | 01-AUG-06:10 | 49606.78 | 31-AUG-06:19 | 34581.75 | 24-AUG-21:30 | 6402.85 | 08-AUG-15:20 | 0.00 | 01-AUG-00:10 |
September | 64632.59 | 01-SEP-19:10 | 12338.45 | 01-SEP-00:10 | 89171.45 | 01-SEP-06:10 | 49607.07 | 18-SEP-06:19 | 34310.71 | 01-SEP-21:40 | 6188.86 | 01-SEP-15:30 | 0.00 | 01-SEP-00:10 |
October | 64632.59 | 02-OCT-19:10 | 12338.45 | 01-OCT-00:10 | 89171.45 | 02-OCT-06:10 | 49607.07 | 02-OCT-06:19 | 30397.31 | 19-OCT-21:10 | 6163.28 | 19-OCT-15:09 | 0.00 | 01-OCT-00:10 |
November | 64632.59 | 01-NOV-19:10 | 12338.45 | 01-NOV-00:10 | 89171.45 | 01-NOV-06:10 | 49607.07 | 01-NOV-06:19 | 23421.46 | 24-NOV-19:10 | 4722.50 | 17-NOV-11:30 | 0.00 | 01-NOV-00:10 |
December | 64632.59 | 01-DEC-20:10 | 12338.45 | 01-DEC-00:10 | 89171.45 | 01-DEC-07:10 | 49607.07 | 01-DEC-07:19 | 24116.61 | 01-DEC-19:10 | 4941.12 | 20-DEC-10:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 64632.59 | 12338.45 | 89171.45 | 49605.09 | 22316.56 | 4722.50 | 0.00 | |||||||
Maximum of Months | 64632.59 | 12338.45 | 89171.45 | 49607.07 | 34581.75 | 6537.81 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 3244.14 | 27-JAN-16:10 | 0.00 | 0.00 | 9938.94 | 01-JAN-00:40 | 4765.07 | 06-JAN-07:10 | 0.00 |
February | 10449.65 | 28-FEB-16:10 | 0.00 | 0.00 | 9938.94 | 14-FEB-10:39 | 4761.50 | 14-FEB-07:10 | 0.00 |
March | 17303.62 | 31-MAR-15:09 | 0.00 | 0.00 | 9938.94 | 07-MAR-02:20 | 4753.08 | 15-MAR-06:00 | 0.00 |
April | 82641.55 | 23-APR-18:10 | 0.00 | 0.00 | 9938.94 | 01-APR-00:10 | 4751.13 | 17-APR-06:30 | 0.00 |
May | 123324.60 | 25-MAY-18:10 | 0.00 | 0.00 | 9938.94 | 01-MAY-00:10 | 4751.13 | 08-MAY-18:30 | 0.00 |
June | 202899.63 | 29-JUN-18:10 | 0.00 | 0.00 | 9938.94 | 23-JUN-16:00 | 4751.12 | 15-JUN-06:30 | 0.00 |
July | 171254.05 | 21-JUL-19:19 | 0.00 | 0.00 | 9938.94 | 04-JUL-16:00 | 4751.12 | 27-JUL-06:19 | 0.00 |
August | 163341.36 | 08-AUG-15:20 | 0.00 | 0.00 | 9938.94 | 07-AUG-16:30 | 4751.12 | 02-AUG-06:49 | 0.00 |
September | 103114.85 | 01-SEP-15:20 | 0.00 | 0.00 | 9938.94 | 01-SEP-12:09 | 4751.13 | 25-SEP-18:00 | 0.00 |
October | 67581.43 | 19-OCT-15:09 | 0.00 | 0.00 | 9938.94 | 01-OCT-00:40 | 4751.13 | 02-OCT-06:00 | 0.00 |
November | 20218.01 | 01-NOV-15:09 | 0.00 | 0.00 | 9938.94 | 01-NOV-00:10 | 4751.12 | 07-NOV-19:49 | 0.00 |
December | 2121.56 | 02-DEC-14:09 | 0.00 | 0.00 | 9938.94 | 13-DEC-04:30 | 4756.87 | 20-DEC-07:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 2121.56 | 0.00 | 0.00 | 9938.94 | 4751.12 | 0.00 | |||
Maximum of Months | 202899.63 | 0.00 | 0.00 | 9938.94 | 4765.07 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 228557.70 | 13-JAN-07:10 | 36001.17 | 89171.45 | 12338.45 | 49600.84 | 22129.73 | 1962.64 | 0.00 | 0.00 | 0.00 |
February | 226743.77 | 14-FEB-07:10 | 36001.17 | 89171.45 | 12338.45 | 49600.84 | 20413.49 | 1892.17 | 0.00 | 0.00 | 0.00 |
March | 224512.86 | 28-MAR-18:40 | 57474.69 | 77573.37 | 12338.45 | 28169.74 | 21441.63 | 3991.13 | 0.00 | 7038.67 | 0.00 |
April | 282443.16 | 23-APR-18:10 | 51227.63 | 74651.16 | 0.00 | 28100.03 | 23458.04 | 6063.28 | 0.00 | 82641.55 | 0.00 |
May | 331873.65 | 25-MAY-18:10 | 53184.46 | 77573.37 | 0.00 | 28157.33 | 26236.79 | 6289.34 | 0.00 | 123324.60 | 0.00 |
June | 413449.13 | 29-JUN-18:10 | 52987.32 | 77573.37 | 0.00 | 28157.23 | 28190.84 | 6534.12 | 0.00 | 202899.63 | 0.00 |
July | 382018.19 | 21-JUL-19:19 | 61533.41 | 86439.81 | 0.00 | 10996.16 | 29460.47 | 6537.81 | 0.00 | 171254.05 | 0.00 |
August | 356356.57 | 08-AUG-18:10 | 52987.32 | 77573.37 | 0.00 | 28157.23 | 26682.39 | 6392.01 | 0.00 | 148018.74 | 0.00 |
September | 273533.97 | 01-SEP-18:10 | 53932.35 | 77573.37 | 0.00 | 28157.33 | 23059.93 | 5879.60 | 0.00 | 77307.97 | 0.00 |
October | 233939.27 | 20-OCT-18:19 | 57474.69 | 77573.37 | 12338.45 | 28169.74 | 26308.76 | 4914.94 | 0.00 | 19081.82 | 0.00 |
November | 225797.21 | 03-NOV-06:00 | 36001.17 | 89171.45 | 12338.45 | 49607.07 | 16044.26 | 3572.47 | 0.00 | 1172.11 | 0.00 |
December | 227392.51 | 19-DEC-07:10 | 36001.17 | 89171.45 | 12338.45 | 49600.84 | 20782.98 | 1936.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 224512.86 | 36001.17 | 74651.16 | 0.00 | 10996.16 | 16044.26 | 1892.17 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 413449.13 | 61533.41 | 89171.45 | 12338.45 | 49607.07 | 29460.47 | 6537.81 | 0.00 | 202899.63 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 816095.99 | 09-JAN-04:00 | 0.00 | 271750.09 | 31-JAN-21:00 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 780282.15 | 14-FEB-07:10 | 0.00 | 273062.52 | 21-FEB-21:19 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 741832.06 | 05-MAR-06:00 | 0.00 | 273058.79 | 01-MAR-21:30 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 208427.81 | 24-APR-10:50 | 0.00 | 270240.34 | 03-APR-20:30 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 202792.91 | 05-MAY-06:00 | 0.00 | 269070.13 | 02-MAY-20:30 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 178774.93 | 16-JUN-22:19 | 0.00 | 264904.44 | 01-JUN-20:30 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 182394.07 | 02-JUL-04:30 | 0.00 | 252887.37 | 03-JUL-20:40 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 177320.16 | 19-AUG-00:30 | 0.00 | 246220.65 | 02-AUG-20:00 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 198785.64 | 28-SEP-08:09 | 0.00 | 247689.69 | 29-SEP-20:49 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 223248.70 | 09-OCT-10:50 | 0.00 | 256879.81 | 31-OCT-20:30 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 286880.14 | 25-NOV-07:10 | 0.00 | 265315.42 | 30-NOV-21:30 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 804572.27 | 24-DEC-05:00 | 0.00 | 269416.28 | 29-DEC-21:49 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 104248.32 | 0.00 | 177320.16 | 0.00 | 246220.65 | 0.00 | |||
Maximum of Months | 104248.32 | 0.00 | 816095.99 | 0.00 | 273062.52 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 145.83 | 18.93 | 145.83 | 18.93 | 0.00 | 18.93 | 0.00 | 18.93 |
February | 11.50 | 20.07 | 11.50 | 20.07 | 0.00 | 20.07 | 0.00 | 20.07 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 50.50 | 19.67 | 50.50 | 19.67 | 0.00 | 19.67 | 0.00 | 19.67 |
Annual Sum or Average | 207.83 | 19.17 | 207.83 | 19.17 | 0.00 | 19.17 | 0.00 | 19.17 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 145.83 | 20.07 | 145.83 | 20.07 | 0.00 | 20.07 | 0.00 | 20.07 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 179.00 | 16.60 | 179.00 | 16.60 | 0.00 | 16.60 | 0.00 | 16.60 |
February | 63.67 | 17.44 | 63.67 | 17.44 | 0.00 | 17.44 | 0.00 | 17.44 |
March | 19.67 | 18.08 | 19.67 | 18.08 | 0.00 | 18.08 | 0.00 | 18.08 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 134.83 | 16.89 | 134.83 | 16.89 | 0.00 | 16.89 | 0.00 | 16.89 |
Annual Sum or Average | 397.17 | 16.91 | 397.17 | 16.91 | 0.00 | 16.91 | 0.00 | 16.91 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 179.00 | 18.08 | 179.00 | 18.08 | 0.00 | 18.08 | 0.00 | 18.08 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 165.50 | 18.05 | 165.50 | 18.05 | 0.00 | 18.05 | 0.00 | 18.05 |
February | 48.83 | 19.19 | 48.83 | 19.19 | 0.00 | 19.19 | 0.00 | 19.19 |
March | 8.50 | 19.64 | 8.50 | 19.64 | 0.00 | 19.64 | 0.00 | 19.64 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 132.83 | 18.89 | 132.83 | 18.89 | 0.00 | 18.89 | 0.00 | 18.89 |
Annual Sum or Average | 355.67 | 18.56 | 355.67 | 18.56 | 0.00 | 18.56 | 0.00 | 18.56 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 165.50 | 19.64 | 165.50 | 19.64 | 0.00 | 19.64 | 0.00 | 19.64 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 200.33 | 18.97 | 200.33 | 18.97 | 0.00 | 18.97 | 0.00 | 18.97 |
February | 40.17 | 19.91 | 40.17 | 19.91 | 0.00 | 19.91 | 0.00 | 19.91 |
March | 3.67 | 20.37 | 3.67 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 134.00 | 19.67 | 134.00 | 19.67 | 0.00 | 19.67 | 0.00 | 19.67 |
Annual Sum or Average | 378.17 | 19.33 | 378.17 | 19.33 | 0.00 | 19.33 | 0.00 | 19.33 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 200.33 | 20.37 | 200.33 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 249.00 | 18.76 | 249.00 | 18.76 | 0.00 | 18.76 | 0.00 | 18.76 |
February | 52.50 | 19.68 | 52.50 | 19.68 | 0.00 | 19.68 | 0.00 | 19.68 |
March | 10.33 | 20.13 | 10.33 | 20.13 | 0.00 | 20.13 | 0.00 | 20.13 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 180.83 | 19.40 | 180.83 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 |
Annual Sum or Average | 492.67 | 19.12 | 492.67 | 19.12 | 0.00 | 19.12 | 0.00 | 19.12 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 249.00 | 20.13 | 249.00 | 20.13 | 0.00 | 20.13 | 0.00 | 20.13 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 108.50 | 12.19 | 108.50 | 12.19 | 0.00 | 12.19 | 0.00 | 12.19 |
February | 35.17 | 12.96 | 35.17 | 12.96 | 0.00 | 12.96 | 0.00 | 12.96 |
March | 10.50 | 14.62 | 10.50 | 14.62 | 0.00 | 14.62 | 0.00 | 14.62 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 74.17 | 13.56 | 74.17 | 13.56 | 0.00 | 13.56 | 0.00 | 13.56 |
Annual Sum or Average | 228.33 | 12.87 | 228.33 | 12.87 | 0.00 | 12.87 | 0.00 | 12.87 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 108.50 | 14.62 | 108.50 | 14.62 | 0.00 | 14.62 | 0.00 | 14.62 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 155.33 | 17.08 | 155.33 | 17.08 | 0.00 | 17.08 | 0.00 | 17.08 |
February | 52.50 | 18.09 | 52.50 | 18.09 | 0.00 | 18.09 | 0.00 | 18.09 |
March | 12.00 | 18.40 | 12.00 | 18.40 | 0.00 | 18.40 | 0.00 | 18.40 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 125.33 | 17.76 | 125.33 | 17.76 | 0.00 | 17.76 | 0.00 | 17.76 |
Annual Sum or Average | 345.17 | 17.53 | 345.17 | 17.53 | 0.00 | 17.53 | 0.00 | 17.53 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 155.33 | 18.40 | 155.33 | 18.40 | 0.00 | 18.40 | 0.00 | 18.40 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 150.83 | 17.93 | 150.83 | 17.93 | 0.00 | 17.93 | 0.00 | 17.93 |
February | 40.83 | 19.09 | 40.83 | 19.09 | 0.00 | 19.09 | 0.00 | 19.09 |
March | 6.67 | 19.41 | 6.67 | 19.41 | 0.00 | 19.41 | 0.00 | 19.41 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 117.83 | 18.81 | 117.83 | 18.81 | 0.00 | 18.81 | 0.00 | 18.81 |
Annual Sum or Average | 316.17 | 18.44 | 316.17 | 18.44 | 0.00 | 18.44 | 0.00 | 18.44 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 150.83 | 19.41 | 150.83 | 19.41 | 0.00 | 19.41 | 0.00 | 19.41 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.83 | 20.39 | 4.83 | 20.39 | 0.00 | 20.39 | 0.00 | 20.39 |
February | 0.83 | 20.49 | 0.83 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.72 | 0.83 | 21.72 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.76 | 1.00 | 21.76 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.73 | 1.83 | 21.73 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.76 | 0.83 | 21.76 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.79 | 0.17 | 21.79 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 3.00 | 20.42 | 3.00 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 |
Annual Sum or Average | 8.67 | 20.41 | 8.67 | 20.41 | 4.67 | 20.69 | 4.67 | 20.88 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.83 | 20.49 | 4.83 | 20.49 | 1.83 | 21.79 | 1.83 | 21.79 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 26.67 | 20.26 | 26.67 | 20.26 | 0.00 | 20.26 | 0.00 | 20.26 |
February | 1.50 | 20.36 | 1.50 | 20.36 | 0.00 | 20.36 | 0.00 | 20.36 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.75 | 0.17 | 21.75 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.81 | 1.33 | 21.81 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 21.80 | 2.50 | 21.80 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 21.83 | 3.50 | 21.83 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.87 | 1.00 | 21.87 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.99 | 0.67 | 21.99 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6.33 | 20.30 | 6.33 | 20.30 | 0.00 | 20.30 | 0.00 | 20.30 |
Annual Sum or Average | 34.50 | 20.27 | 34.50 | 20.27 | 9.17 | 20.45 | 9.17 | 20.60 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 26.67 | 20.36 | 26.67 | 20.36 | 3.50 | 21.99 | 3.50 | 21.99 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 77.83 | 19.97 | 77.83 | 19.97 | 0.00 | 19.97 | 0.00 | 19.97 |
February | 4.83 | 20.31 | 4.83 | 20.31 | 0.00 | 20.31 | 0.00 | 20.31 |
March | 0.50 | 20.40 | 0.50 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 21.76 | 2.33 | 21.76 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 21.91 | 6.33 | 21.91 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 21.87 | 6.33 | 21.87 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 21.80 | 4.33 | 21.80 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.76 | 0.33 | 21.76 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.33 | 20.35 | 0.33 | 20.35 | 0.00 | 20.35 | 0.00 | 20.35 |
December | 31.83 | 20.26 | 31.83 | 20.26 | 0.00 | 20.26 | 0.00 | 20.26 |
Annual Sum or Average | 115.33 | 20.07 | 115.33 | 20.07 | 19.67 | 20.21 | 19.67 | 20.33 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 77.83 | 20.40 | 77.83 | 20.40 | 6.33 | 21.91 | 6.33 | 21.91 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 8.50 | 20.39 | 8.50 | 20.39 | 0.00 | 20.39 | 0.00 | 20.39 |
February | 0.33 | 20.48 | 0.33 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.75 | 0.17 | 21.75 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.76 | 0.33 | 21.76 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.17 | 20.43 | 2.17 | 20.43 | 0.00 | 20.43 | 0.00 | 20.43 |
Annual Sum or Average | 11.00 | 20.40 | 11.00 | 20.40 | 0.50 | 20.43 | 0.50 | 20.46 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 8.50 | 20.48 | 8.50 | 20.48 | 0.33 | 21.76 | 0.33 | 21.76 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 37.17 | 20.20 | 37.17 | 20.20 | 0.00 | 20.20 | 0.00 | 20.20 |
February | 1.17 | 20.45 | 1.17 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 22.07 | 1.50 | 22.07 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 22.31 | 4.67 | 22.31 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 22.25 | 6.67 | 22.25 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 22.24 | 2.67 | 22.24 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 22.44 | 0.17 | 22.44 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 20.54 | 0.17 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 |
December | 6.33 | 20.37 | 6.33 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 |
Annual Sum or Average | 44.83 | 20.23 | 44.83 | 20.23 | 15.67 | 20.53 | 15.67 | 20.75 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 37.17 | 20.54 | 37.17 | 20.54 | 6.67 | 22.44 | 6.67 | 22.44 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 182.50 | 19.20 | 182.50 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 |
February | 51.33 | 19.87 | 51.33 | 19.87 | 0.00 | 19.87 | 0.00 | 19.87 |
March | 11.50 | 20.13 | 11.50 | 20.13 | 0.00 | 20.13 | 0.00 | 20.13 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 145.67 | 19.63 | 145.67 | 19.63 | 0.00 | 19.63 | 0.00 | 19.63 |
Annual Sum or Average | 391.00 | 19.47 | 391.00 | 19.47 | 0.00 | 19.47 | 0.00 | 19.47 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 182.50 | 20.13 | 182.50 | 20.13 | 0.00 | 20.13 | 0.00 | 20.13 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.00 | 20.37 | 6.00 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 |
February | 0.67 | 20.45 | 0.67 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.71 | 0.17 | 21.71 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.80 | 1.00 | 21.80 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.81 | 1.67 | 21.81 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 21.77 | 2.33 | 21.77 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.78 | 1.67 | 21.78 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.81 | 0.33 | 21.81 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 3.00 | 20.38 | 3.00 | 20.38 | 0.00 | 20.38 | 0.00 | 20.38 |
Annual Sum or Average | 9.67 | 20.38 | 9.67 | 20.38 | 7.17 | 20.76 | 7.17 | 20.98 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6.00 | 20.45 | 6.00 | 20.45 | 2.33 | 21.81 | 2.33 | 21.81 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 34.33 | 20.19 | 34.33 | 20.19 | 0.00 | 20.19 | 0.00 | 20.19 |
February | 1.67 | 20.32 | 1.67 | 20.32 | 0.00 | 20.32 | 0.00 | 20.32 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.76 | 0.50 | 21.76 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 21.89 | 3.17 | 21.89 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 21.84 | 4.00 | 21.84 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 21.86 | 4.83 | 21.86 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.88 | 1.83 | 21.88 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.93 | 1.17 | 21.93 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8.17 | 20.29 | 8.17 | 20.29 | 0.00 | 20.29 | 0.00 | 20.29 |
Annual Sum or Average | 44.17 | 20.21 | 44.17 | 20.21 | 15.50 | 20.46 | 15.50 | 20.64 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 34.33 | 20.32 | 34.33 | 20.32 | 4.83 | 21.93 | 4.83 | 21.93 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.83 | 20.47 | 0.83 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.80 | 0.17 | 21.80 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.71 | 0.17 | 21.71 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.71 | 0.17 | 21.71 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.70 | 0.33 | 21.70 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.70 | 0.83 | 21.70 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.73 | 0.50 | 21.73 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.80 | 0.50 | 21.80 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.50 | 20.47 | 0.50 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
Annual Sum or Average | 1.33 | 20.47 | 1.33 | 20.47 | 2.67 | 21.10 | 2.67 | 21.31 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.83 | 20.47 | 0.83 | 20.47 | 0.83 | 21.80 | 0.83 | 21.80 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 69.17 | 17.63 | 69.17 | 17.63 | 0.00 | 17.63 | 0.00 | 17.63 |
February | 10.33 | 18.85 | 10.33 | 18.85 | 0.00 | 18.85 | 0.00 | 18.85 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 36.83 | 18.60 | 36.83 | 18.60 | 0.00 | 18.60 | 0.00 | 18.60 |
Annual Sum or Average | 116.33 | 18.05 | 116.33 | 18.05 | 0.00 | 18.05 | 0.00 | 18.05 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 69.17 | 18.85 | 69.17 | 18.85 | 0.00 | 18.85 | 0.00 | 18.85 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 62.33 | 17.55 | 62.33 | 17.55 | 0.00 | 17.55 | 0.00 | 17.55 |
February | 8.67 | 18.83 | 8.67 | 18.83 | 0.00 | 18.83 | 0.00 | 18.83 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 32.67 | 18.64 | 32.67 | 18.64 | 0.00 | 18.64 | 0.00 | 18.64 |
Annual Sum or Average | 103.67 | 18.00 | 103.67 | 18.00 | 0.00 | 18.00 | 0.00 | 18.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 62.33 | 18.83 | 62.33 | 18.83 | 0.00 | 18.83 | 0.00 | 18.83 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 68.67 | 14.19 | 68.67 | 14.19 | 0.00 | 14.19 | 0.00 | 14.19 |
February | 23.17 | 15.08 | 23.17 | 15.08 | 0.00 | 15.08 | 0.00 | 15.08 |
March | 6.33 | 16.50 | 6.33 | 16.50 | 0.00 | 16.50 | 0.00 | 16.50 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 45.17 | 14.99 | 45.17 | 14.99 | 0.00 | 14.99 | 0.00 | 14.99 |
Annual Sum or Average | 143.33 | 14.69 | 143.33 | 14.69 | 0.00 | 14.69 | 0.00 | 14.69 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 68.67 | 16.50 | 68.67 | 16.50 | 0.00 | 16.50 | 0.00 | 16.50 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 186.33 | 18.37 | 186.33 | 18.37 | 0.00 | 18.37 | 0.00 | 18.37 |
February | 57.17 | 19.32 | 57.17 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 |
March | 15.33 | 19.82 | 15.33 | 19.82 | 0.00 | 19.82 | 0.00 | 19.82 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 145.33 | 19.05 | 145.33 | 19.05 | 0.00 | 19.05 | 0.00 | 19.05 |
Annual Sum or Average | 404.17 | 18.81 | 404.17 | 18.81 | 0.00 | 18.81 | 0.00 | 18.81 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 186.33 | 19.82 | 186.33 | 19.82 | 0.00 | 19.82 | 0.00 | 19.82 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.57 | 246.00 | 21.11 | 246.00 | 20.84 |
February | 672.00 | 22.38 | 48.50 | 22.26 | 48.50 | 22.16 |
March | 744.00 | 22.32 | 8.00 | 22.30 | 8.00 | 22.28 |
April | 720.00 | 22.36 | 0.00 | 22.36 | 0.00 | 22.36 |
May | 744.00 | 22.59 | 0.00 | 22.59 | 0.00 | 22.59 |
June | 715.83 | 22.85 | 43.67 | 22.86 | 43.67 | 22.87 |
July | 476.50 | 23.21 | 143.50 | 23.32 | 77.50 | 23.34 |
August | 137.50 | 23.60 | 294.33 | 23.83 | 50.00 | 23.84 |
September | 202.17 | 23.73 | 120.00 | 23.81 | 13.50 | 23.82 |
October | 395.33 | 23.84 | 0.00 | 23.84 | 0.00 | 23.84 |
November | 648.33 | 23.87 | 0.00 | 23.87 | 0.00 | 23.87 |
December | 744.00 | 22.44 | 110.33 | 22.16 | 110.33 | 21.95 |
Annual Sum or Average | 6943.67 | 22.70 | 1014.33 | 22.65 | 597.50 | 22.54 |
Minimum of Months | 137.50 | 21.57 | 0.00 | 21.11 | 0.00 | 20.84 |
Maximum of Months | 744.00 | 23.87 | 294.33 | 23.87 | 246.00 | 23.87 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 740.00 | 19.99 | 671.67 | 19.91 | 671.67 | 19.88 |
February | 636.83 | 20.79 | 458.50 | 20.70 | 448.67 | 20.64 |
March | 699.83 | 21.09 | 391.00 | 21.04 | 377.67 | 20.99 |
April | 649.83 | 21.33 | 125.33 | 21.39 | 95.17 | 21.35 |
May | 619.00 | 21.58 | 78.00 | 21.80 | 5.00 | 21.80 |
June | 551.33 | 21.64 | 120.00 | 22.01 | 0.00 | 22.01 |
July | 460.67 | 21.89 | 204.50 | 22.42 | 0.00 | 22.42 |
August | 507.83 | 21.73 | 178.00 | 22.24 | 0.00 | 22.24 |
September | 595.50 | 21.43 | 97.50 | 21.78 | 0.00 | 21.78 |
October | 676.50 | 21.17 | 115.00 | 21.34 | 61.67 | 21.32 |
November | 695.33 | 21.08 | 397.00 | 21.07 | 392.33 | 21.05 |
December | 744.00 | 20.28 | 686.50 | 20.24 | 686.50 | 20.22 |
Annual Sum or Average | 7576.67 | 21.10 | 3523.00 | 21.12 | 2738.67 | 20.98 |
Minimum of Months | 460.67 | 19.99 | 78.00 | 19.91 | 0.00 | 19.88 |
Maximum of Months | 744.00 | 21.89 | 686.50 | 22.42 | 686.50 | 22.42 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.45 | 459.00 | 20.25 | 459.00 | 20.16 |
February | 672.00 | 21.29 | 193.33 | 21.12 | 193.33 | 21.01 |
March | 744.00 | 21.78 | 73.17 | 21.69 | 73.17 | 21.62 |
April | 711.50 | 22.51 | 1.83 | 22.52 | 0.00 | 22.52 |
May | 582.50 | 23.02 | 54.33 | 23.09 | 0.00 | 23.09 |
June | 463.33 | 23.08 | 202.00 | 23.31 | 77.83 | 23.36 |
July | 275.33 | 23.39 | 382.33 | 23.66 | 122.67 | 23.69 |
August | 299.00 | 23.18 | 314.00 | 23.52 | 82.67 | 23.55 |
September | 546.83 | 22.96 | 59.67 | 23.04 | 19.00 | 23.06 |
October | 717.00 | 22.47 | 0.00 | 22.47 | 0.00 | 22.47 |
November | 720.00 | 21.81 | 32.83 | 21.78 | 32.83 | 21.74 |
December | 744.00 | 20.76 | 407.33 | 20.60 | 407.33 | 20.52 |
Annual Sum or Average | 7219.50 | 22.03 | 2179.83 | 22.00 | 1467.83 | 21.86 |
Minimum of Months | 275.33 | 20.45 | 0.00 | 20.25 | 0.00 | 20.16 |
Maximum of Months | 744.00 | 23.39 | 459.00 | 23.66 | 459.00 | 23.69 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.43 | 702.83 | 20.42 | 702.83 | 20.41 |
February | 672.00 | 20.94 | 545.50 | 20.93 | 545.50 | 20.93 |
March | 744.00 | 21.07 | 386.33 | 21.04 | 386.33 | 21.03 |
April | 720.00 | 21.61 | 51.67 | 21.57 | 51.67 | 21.53 |
May | 705.83 | 22.70 | 5.17 | 22.71 | 0.00 | 22.71 |
June | 542.17 | 23.00 | 74.00 | 23.11 | 0.00 | 23.11 |
July | 298.00 | 23.30 | 153.17 | 23.50 | 0.00 | 23.50 |
August | 498.67 | 23.19 | 47.50 | 23.26 | 0.00 | 23.26 |
September | 687.67 | 22.77 | 3.67 | 22.78 | 0.00 | 22.78 |
October | 744.00 | 21.82 | 0.00 | 21.82 | 0.00 | 21.82 |
November | 720.00 | 21.13 | 231.50 | 21.10 | 231.50 | 21.08 |
December | 744.00 | 20.74 | 651.00 | 20.73 | 651.00 | 20.72 |
Annual Sum or Average | 7820.33 | 21.74 | 2852.33 | 21.56 | 2568.83 | 21.40 |
Minimum of Months | 298.00 | 20.43 | 0.00 | 20.42 | 0.00 | 20.41 |
Maximum of Months | 744.00 | 23.30 | 702.83 | 23.50 | 702.83 | 23.50 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.23 | 720.83 | 20.22 | 720.83 | 20.21 |
February | 672.00 | 20.88 | 587.00 | 20.88 | 587.00 | 20.87 |
March | 744.00 | 21.00 | 461.33 | 20.99 | 461.33 | 20.98 |
April | 720.00 | 21.32 | 103.50 | 21.28 | 103.50 | 21.25 |
May | 734.00 | 22.41 | 3.50 | 22.40 | 3.50 | 22.39 |
June | 608.17 | 22.76 | 47.50 | 22.84 | 0.00 | 22.84 |
July | 481.83 | 23.15 | 30.67 | 23.19 | 0.00 | 23.19 |
August | 671.50 | 22.99 | 0.00 | 22.99 | 0.00 | 22.99 |
September | 713.33 | 22.42 | 0.00 | 22.42 | 0.00 | 22.42 |
October | 744.00 | 21.45 | 11.33 | 21.45 | 11.33 | 21.44 |
November | 720.00 | 21.02 | 341.50 | 21.01 | 341.50 | 21.01 |
December | 744.00 | 20.59 | 694.33 | 20.58 | 694.33 | 20.57 |
Annual Sum or Average | 8296.83 | 21.62 | 3001.50 | 21.39 | 2923.33 | 21.24 |
Minimum of Months | 481.83 | 20.23 | 0.00 | 20.22 | 0.00 | 20.21 |
Maximum of Months | 744.00 | 23.15 | 720.83 | 23.19 | 720.83 | 23.19 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 428.33 | 19.16 | 384.17 | 19.53 | 213.17 | 19.00 |
February | 302.17 | 21.07 | 362.17 | 21.82 | 147.67 | 21.63 |
March | 255.67 | 22.24 | 455.00 | 22.95 | 147.00 | 22.95 |
April | 222.33 | 23.15 | 550.67 | 23.43 | 152.83 | 23.52 |
May | 269.33 | 23.66 | 650.00 | 23.50 | 235.83 | 23.60 |
June | 299.00 | 23.93 | 680.50 | 23.50 | 293.17 | 23.61 |
July | 338.50 | 23.96 | 726.33 | 23.49 | 337.33 | 23.60 |
August | 320.83 | 23.96 | 721.67 | 23.48 | 319.17 | 23.60 |
September | 288.33 | 23.80 | 654.17 | 23.52 | 267.50 | 23.63 |
October | 245.17 | 23.34 | 623.67 | 23.44 | 187.17 | 23.54 |
November | 230.17 | 22.92 | 478.83 | 23.40 | 138.50 | 23.50 |
December | 396.67 | 19.98 | 379.17 | 20.52 | 198.00 | 20.15 |
Annual Sum or Average | 3596.50 | 22.39 | 6666.33 | 22.79 | 2637.33 | 22.79 |
Minimum of Months | 222.33 | 19.16 | 362.17 | 19.53 | 138.50 | 19.00 |
Maximum of Months | 428.33 | 23.96 | 726.33 | 23.52 | 337.33 | 23.63 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 734.67 | 20.28 | 484.50 | 20.06 | 483.50 | 19.96 |
February | 618.67 | 21.15 | 289.17 | 21.03 | 259.33 | 20.88 |
March | 676.17 | 21.65 | 144.67 | 21.63 | 108.00 | 21.51 |
April | 590.00 | 22.10 | 71.17 | 22.29 | 1.50 | 22.29 |
May | 442.00 | 22.50 | 183.33 | 22.87 | 7.67 | 22.88 |
June | 377.00 | 22.72 | 346.33 | 23.15 | 108.50 | 23.22 |
July | 306.33 | 23.22 | 560.50 | 23.47 | 200.33 | 23.52 |
August | 326.17 | 22.94 | 503.50 | 23.38 | 164.33 | 23.44 |
September | 395.00 | 22.29 | 222.50 | 22.81 | 26.00 | 22.84 |
October | 602.83 | 21.84 | 87.67 | 22.11 | 1.33 | 22.10 |
November | 681.83 | 21.52 | 122.00 | 21.51 | 102.17 | 21.46 |
December | 740.83 | 20.55 | 504.17 | 20.40 | 504.17 | 20.34 |
Annual Sum or Average | 6491.50 | 21.67 | 3519.50 | 21.86 | 1966.83 | 21.73 |
Minimum of Months | 306.33 | 20.28 | 71.17 | 20.06 | 1.33 | 19.96 |
Maximum of Months | 740.83 | 23.22 | 560.50 | 23.47 | 504.17 | 23.52 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.71 | 340.67 | 20.37 | 340.67 | 20.19 |
February | 672.00 | 21.73 | 104.50 | 21.52 | 104.50 | 21.36 |
March | 742.83 | 22.24 | 29.50 | 22.18 | 29.50 | 22.12 |
April | 663.83 | 22.82 | 7.17 | 22.83 | 0.00 | 22.83 |
May | 410.00 | 23.07 | 125.33 | 23.26 | 6.50 | 23.27 |
June | 311.33 | 23.23 | 339.83 | 23.55 | 109.33 | 23.60 |
July | 226.00 | 23.74 | 568.00 | 23.79 | 186.17 | 23.82 |
August | 236.67 | 23.56 | 541.50 | 23.75 | 163.83 | 23.78 |
September | 302.67 | 22.97 | 183.50 | 23.31 | 30.83 | 23.34 |
October | 579.67 | 22.65 | 24.33 | 22.70 | 0.00 | 22.70 |
November | 718.17 | 22.27 | 2.17 | 22.26 | 2.17 | 22.26 |
December | 744.00 | 21.06 | 274.00 | 20.78 | 274.00 | 20.62 |
Annual Sum or Average | 6351.17 | 22.21 | 2540.50 | 22.34 | 1247.50 | 22.24 |
Minimum of Months | 226.00 | 20.71 | 2.17 | 20.37 | 0.00 | 20.19 |
Maximum of Months | 744.00 | 23.74 | 568.00 | 23.79 | 340.67 | 23.82 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.56 | 730.83 | 20.56 | 730.83 | 20.55 |
February | 672.00 | 20.88 | 535.83 | 20.80 | 535.83 | 20.77 |
March | 742.83 | 21.03 | 455.50 | 20.92 | 455.50 | 20.87 |
April | 699.67 | 21.33 | 112.50 | 21.26 | 110.33 | 21.21 |
May | 682.67 | 21.54 | 15.50 | 21.58 | 1.17 | 21.58 |
June | 628.17 | 21.47 | 24.00 | 21.54 | 1.33 | 21.54 |
July | 607.67 | 21.38 | 44.50 | 21.52 | 0.00 | 21.52 |
August | 634.17 | 21.42 | 34.67 | 21.52 | 0.17 | 21.52 |
September | 667.83 | 21.46 | 10.83 | 21.49 | 1.83 | 21.50 |
October | 725.17 | 21.17 | 119.50 | 21.09 | 118.83 | 21.03 |
November | 720.00 | 20.87 | 510.83 | 20.79 | 510.83 | 20.76 |
December | 744.00 | 20.53 | 738.67 | 20.53 | 738.67 | 20.53 |
Annual Sum or Average | 8268.17 | 21.12 | 3333.17 | 21.01 | 3205.33 | 20.93 |
Minimum of Months | 607.67 | 20.53 | 10.83 | 20.53 | 0.00 | 20.53 |
Maximum of Months | 744.00 | 21.54 | 738.67 | 21.58 | 738.67 | 21.58 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.44 | 744.00 | 20.44 | 744.00 | 20.44 |
February | 672.00 | 20.59 | 638.00 | 20.57 | 638.00 | 20.57 |
March | 744.00 | 20.74 | 574.83 | 20.67 | 574.83 | 20.65 |
April | 697.83 | 21.19 | 182.00 | 21.17 | 170.00 | 21.09 |
May | 636.17 | 21.85 | 78.67 | 22.28 | 22.33 | 22.44 |
June | 577.50 | 22.14 | 135.17 | 22.79 | 62.83 | 23.05 |
July | 549.83 | 22.29 | 170.83 | 23.02 | 79.33 | 23.36 |
August | 589.83 | 22.12 | 138.67 | 22.72 | 61.00 | 22.97 |
September | 661.83 | 21.67 | 52.17 | 21.93 | 16.83 | 22.02 |
October | 737.83 | 21.09 | 159.67 | 21.01 | 157.67 | 20.94 |
November | 720.00 | 20.65 | 620.83 | 20.62 | 620.83 | 20.61 |
December | 744.00 | 20.47 | 744.00 | 20.47 | 744.00 | 20.47 |
Annual Sum or Average | 8074.83 | 21.21 | 4238.83 | 21.21 | 3891.67 | 21.13 |
Minimum of Months | 549.83 | 20.44 | 52.17 | 20.44 | 16.83 | 20.44 |
Maximum of Months | 744.00 | 22.29 | 744.00 | 23.02 | 744.00 | 23.36 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.49 | 689.50 | 20.47 | 689.50 | 20.46 |
February | 672.00 | 20.75 | 590.33 | 20.73 | 590.33 | 20.72 |
March | 744.00 | 20.91 | 461.83 | 20.86 | 461.83 | 20.84 |
April | 720.00 | 21.27 | 57.33 | 21.25 | 57.33 | 21.22 |
May | 733.67 | 21.80 | 0.83 | 21.81 | 0.00 | 21.81 |
June | 681.83 | 22.02 | 30.83 | 22.09 | 23.00 | 22.14 |
July | 692.00 | 22.10 | 50.33 | 22.22 | 33.83 | 22.28 |
August | 725.33 | 22.05 | 19.50 | 22.08 | 19.17 | 22.12 |
September | 719.67 | 21.63 | 2.67 | 21.63 | 2.67 | 21.63 |
October | 744.00 | 21.23 | 9.17 | 21.23 | 9.17 | 21.22 |
November | 720.00 | 20.94 | 363.33 | 20.88 | 363.33 | 20.85 |
December | 744.00 | 20.59 | 676.33 | 20.57 | 676.33 | 20.56 |
Annual Sum or Average | 8640.50 | 21.31 | 2952.00 | 21.16 | 2926.50 | 21.07 |
Minimum of Months | 672.00 | 20.49 | 0.83 | 20.47 | 0.00 | 20.46 |
Maximum of Months | 744.00 | 22.10 | 689.50 | 22.22 | 689.50 | 22.28 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.54 | 729.83 | 20.54 | 729.83 | 20.54 |
February | 672.00 | 20.89 | 533.50 | 20.82 | 533.50 | 20.79 |
March | 744.00 | 21.12 | 429.17 | 20.99 | 429.17 | 20.93 |
April | 701.33 | 21.43 | 97.50 | 21.37 | 97.50 | 21.31 |
May | 670.00 | 21.54 | 2.33 | 21.55 | 0.00 | 21.55 |
June | 595.83 | 21.40 | 17.33 | 21.45 | 1.50 | 21.46 |
July | 586.33 | 21.32 | 35.17 | 21.44 | 0.00 | 21.44 |
August | 624.00 | 21.40 | 13.33 | 21.44 | 0.00 | 21.44 |
September | 653.00 | 21.44 | 3.33 | 21.44 | 1.83 | 21.45 |
October | 726.00 | 21.18 | 109.00 | 21.12 | 109.00 | 21.06 |
November | 720.00 | 20.85 | 505.67 | 20.78 | 505.67 | 20.76 |
December | 744.00 | 20.52 | 736.17 | 20.52 | 736.17 | 20.52 |
Annual Sum or Average | 8180.50 | 21.12 | 3212.33 | 21.00 | 3144.17 | 20.92 |
Minimum of Months | 586.33 | 20.52 | 2.33 | 20.52 | 0.00 | 20.52 |
Maximum of Months | 744.00 | 21.54 | 736.17 | 21.55 | 736.17 | 21.55 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.43 | 743.83 | 20.43 | 743.83 | 20.43 |
February | 672.00 | 20.58 | 638.33 | 20.57 | 638.33 | 20.57 |
March | 744.00 | 20.83 | 539.83 | 20.75 | 539.83 | 20.72 |
April | 719.00 | 21.41 | 139.33 | 21.32 | 139.33 | 21.26 |
May | 650.50 | 21.82 | 27.33 | 21.94 | 3.83 | 21.96 |
June | 500.33 | 21.79 | 127.00 | 22.41 | 36.83 | 22.55 |
July | 471.50 | 21.97 | 176.33 | 22.80 | 57.17 | 23.06 |
August | 537.17 | 21.81 | 108.00 | 22.25 | 34.67 | 22.36 |
September | 698.67 | 21.72 | 9.00 | 21.75 | 7.33 | 21.76 |
October | 744.00 | 21.11 | 149.83 | 21.03 | 149.83 | 20.97 |
November | 720.00 | 20.64 | 606.67 | 20.61 | 606.67 | 20.60 |
December | 744.00 | 20.47 | 742.17 | 20.47 | 742.17 | 20.47 |
Annual Sum or Average | 7945.17 | 21.15 | 4007.67 | 21.11 | 3699.83 | 21.01 |
Minimum of Months | 471.50 | 20.43 | 9.00 | 20.43 | 3.83 | 20.43 |
Maximum of Months | 744.00 | 21.97 | 743.83 | 22.80 | 743.83 | 23.06 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.54 | 673.17 | 20.51 | 673.17 | 20.51 |
February | 672.00 | 20.92 | 493.33 | 20.90 | 493.33 | 20.89 |
March | 744.00 | 21.05 | 325.00 | 21.02 | 325.00 | 21.01 |
April | 720.00 | 21.54 | 32.00 | 21.52 | 32.00 | 21.50 |
May | 736.00 | 22.56 | 0.00 | 22.56 | 0.00 | 22.56 |
June | 645.67 | 22.88 | 96.17 | 22.96 | 68.50 | 22.98 |
July | 490.83 | 23.27 | 154.33 | 23.33 | 110.33 | 23.35 |
August | 675.50 | 22.99 | 64.33 | 23.01 | 64.33 | 23.02 |
September | 713.50 | 22.34 | 15.17 | 22.35 | 15.17 | 22.35 |
October | 744.00 | 21.38 | 7.83 | 21.38 | 7.83 | 21.37 |
November | 720.00 | 21.01 | 262.50 | 21.01 | 262.50 | 21.01 |
December | 744.00 | 20.72 | 643.83 | 20.70 | 643.83 | 20.69 |
Annual Sum or Average | 8349.50 | 21.71 | 2767.67 | 21.54 | 2696.00 | 21.44 |
Minimum of Months | 490.83 | 20.54 | 0.00 | 20.51 | 0.00 | 20.51 |
Maximum of Months | 744.00 | 23.27 | 673.17 | 23.33 | 673.17 | 23.35 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.50 | 737.00 | 20.50 | 737.00 | 20.50 |
February | 672.00 | 20.76 | 582.50 | 20.71 | 582.50 | 20.69 |
March | 740.83 | 20.92 | 532.67 | 20.82 | 532.67 | 20.78 |
April | 696.50 | 21.24 | 209.33 | 21.15 | 207.00 | 21.08 |
May | 667.67 | 21.49 | 26.83 | 21.53 | 6.33 | 21.53 |
June | 609.33 | 21.41 | 40.83 | 21.52 | 6.33 | 21.53 |
July | 597.83 | 21.35 | 60.83 | 21.53 | 1.67 | 21.54 |
August | 625.00 | 21.37 | 54.83 | 21.52 | 5.17 | 21.53 |
September | 658.67 | 21.39 | 22.83 | 21.44 | 10.00 | 21.44 |
October | 723.83 | 21.06 | 224.33 | 20.97 | 220.83 | 20.90 |
November | 720.00 | 20.75 | 581.67 | 20.70 | 581.67 | 20.68 |
December | 744.00 | 20.49 | 742.83 | 20.49 | 742.83 | 20.49 |
Annual Sum or Average | 8199.67 | 21.04 | 3816.50 | 20.94 | 3634.00 | 20.86 |
Minimum of Months | 597.83 | 20.49 | 22.83 | 20.49 | 1.67 | 20.49 |
Maximum of Months | 744.00 | 21.49 | 742.83 | 21.53 | 742.83 | 21.54 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.42 | 744.00 | 20.42 | 744.00 | 20.42 |
February | 672.00 | 20.53 | 651.00 | 20.52 | 651.00 | 20.52 |
March | 744.00 | 20.66 | 631.33 | 20.61 | 631.33 | 20.59 |
April | 696.17 | 21.11 | 310.67 | 21.08 | 295.33 | 21.01 |
May | 628.67 | 21.92 | 98.00 | 22.42 | 40.33 | 22.64 |
June | 577.00 | 22.30 | 156.17 | 22.99 | 88.00 | 23.34 |
July | 554.67 | 22.44 | 188.67 | 23.21 | 101.17 | 23.60 |
August | 587.17 | 22.21 | 161.00 | 22.89 | 85.00 | 23.20 |
September | 657.17 | 21.63 | 64.33 | 21.95 | 28.17 | 22.07 |
October | 735.83 | 20.96 | 298.83 | 20.86 | 296.00 | 20.79 |
November | 720.00 | 20.56 | 658.00 | 20.54 | 658.00 | 20.54 |
December | 744.00 | 20.45 | 744.00 | 20.45 | 744.00 | 20.45 |
Annual Sum or Average | 8060.67 | 21.20 | 4706.00 | 21.21 | 4362.33 | 21.15 |
Minimum of Months | 554.67 | 20.42 | 64.33 | 20.42 | 28.17 | 20.42 |
Maximum of Months | 744.00 | 22.44 | 744.00 | 23.21 | 744.00 | 23.60 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 741.17 | 20.95 | 628.33 | 20.85 | 628.33 | 20.81 |
February | 646.00 | 21.16 | 412.50 | 21.04 | 412.50 | 20.99 |
March | 715.17 | 21.20 | 346.67 | 21.08 | 346.67 | 21.02 |
April | 672.17 | 21.35 | 97.83 | 21.30 | 95.17 | 21.25 |
May | 676.50 | 21.52 | 11.00 | 21.55 | 0.00 | 21.55 |
June | 632.00 | 21.46 | 15.33 | 21.50 | 3.17 | 21.51 |
July | 630.00 | 21.42 | 36.50 | 21.52 | 3.67 | 21.53 |
August | 641.33 | 21.42 | 45.17 | 21.54 | 1.17 | 21.54 |
September | 645.67 | 21.43 | 37.00 | 21.53 | 1.50 | 21.53 |
October | 699.50 | 21.23 | 97.00 | 21.25 | 70.00 | 21.21 |
November | 700.17 | 21.05 | 370.33 | 20.96 | 370.00 | 20.91 |
December | 743.17 | 20.84 | 665.17 | 20.75 | 665.17 | 20.72 |
Annual Sum or Average | 8142.83 | 21.24 | 2762.83 | 21.16 | 2597.33 | 21.08 |
Minimum of Months | 630.00 | 20.84 | 11.00 | 20.75 | 0.00 | 20.72 |
Maximum of Months | 743.17 | 21.52 | 665.17 | 21.55 | 665.17 | 21.55 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 730.83 | 21.90 | 203.67 | 21.38 | 203.67 | 21.04 |
February | 634.83 | 22.82 | 52.33 | 22.62 | 52.33 | 22.46 |
March | 586.83 | 23.21 | 3.83 | 23.19 | 3.83 | 23.17 |
April | 270.50 | 23.41 | 32.83 | 23.47 | 0.00 | 23.47 |
May | 26.33 | 23.54 | 369.17 | 23.95 | 6.17 | 23.95 |
June | 123.67 | 24.00 | 674.00 | 23.98 | 123.67 | 23.98 |
July | 192.83 | 24.00 | 744.00 | 23.99 | 192.83 | 23.99 |
August | 174.50 | 24.00 | 738.50 | 23.97 | 174.50 | 23.98 |
September | 69.67 | 23.75 | 520.33 | 23.95 | 45.67 | 23.95 |
October | 214.17 | 23.25 | 138.17 | 23.54 | 0.00 | 23.54 |
November | 510.33 | 23.31 | 29.17 | 23.35 | 0.00 | 23.35 |
December | 725.17 | 22.34 | 161.00 | 21.95 | 161.00 | 21.68 |
Annual Sum or Average | 4259.67 | 22.91 | 3667.00 | 23.18 | 963.67 | 23.08 |
Minimum of Months | 26.33 | 21.90 | 3.83 | 21.38 | 0.00 | 21.04 |
Maximum of Months | 730.83 | 24.00 | 744.00 | 23.99 | 203.67 | 23.99 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 677.17 | 21.98 | 167.50 | 21.44 | 167.50 | 21.08 |
February | 552.67 | 22.92 | 32.67 | 22.76 | 32.67 | 22.61 |
March | 424.33 | 23.27 | 6.50 | 23.27 | 1.83 | 23.25 |
April | 112.67 | 23.43 | 88.50 | 23.68 | 0.00 | 23.68 |
May | 8.83 | 23.84 | 506.83 | 23.99 | 6.00 | 23.99 |
June | 112.83 | 24.00 | 703.67 | 23.99 | 112.83 | 23.99 |
July | 176.67 | 24.00 | 744.00 | 23.99 | 176.67 | 23.99 |
August | 159.00 | 24.00 | 744.00 | 23.99 | 159.00 | 23.99 |
September | 32.67 | 24.00 | 648.17 | 23.98 | 32.67 | 23.98 |
October | 78.50 | 23.33 | 307.33 | 23.85 | 0.00 | 23.85 |
November | 322.67 | 23.37 | 54.50 | 23.45 | 0.00 | 23.45 |
December | 644.83 | 22.38 | 123.67 | 22.01 | 123.67 | 21.74 |
Annual Sum or Average | 3302.83 | 22.90 | 4127.33 | 23.31 | 812.83 | 23.21 |
Minimum of Months | 8.83 | 21.98 | 6.50 | 21.44 | 0.00 | 21.08 |
Maximum of Months | 677.17 | 24.00 | 744.00 | 23.99 | 176.67 | 23.99 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.50 | 21.52 | 555.00 | 22.03 | 359.67 | 21.96 |
February | 476.17 | 22.96 | 523.83 | 23.20 | 382.50 | 23.21 |
March | 516.17 | 23.61 | 624.83 | 23.71 | 464.83 | 23.73 |
April | 494.83 | 23.97 | 668.00 | 23.94 | 489.83 | 23.95 |
May | 542.33 | 23.99 | 738.67 | 23.95 | 542.33 | 23.96 |
June | 559.33 | 23.99 | 720.00 | 23.97 | 559.33 | 23.98 |
July | 592.33 | 23.99 | 744.00 | 23.98 | 592.33 | 23.98 |
August | 577.50 | 23.99 | 744.00 | 23.97 | 577.50 | 23.98 |
September | 525.83 | 23.99 | 720.00 | 23.95 | 525.83 | 23.96 |
October | 514.67 | 23.98 | 720.50 | 23.92 | 512.50 | 23.94 |
November | 479.33 | 23.88 | 616.00 | 23.91 | 446.17 | 23.93 |
December | 478.50 | 22.19 | 566.00 | 22.60 | 365.17 | 22.57 |
Annual Sum or Average | 6253.50 | 23.54 | 7940.83 | 23.64 | 5818.00 | 23.65 |
Minimum of Months | 476.17 | 21.52 | 523.83 | 22.03 | 359.67 | 21.96 |
Maximum of Months | 592.33 | 23.99 | 744.00 | 23.98 | 592.33 | 23.98 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.33 | 692.33 | 20.31 | 692.33 | 20.30 |
February | 672.00 | 20.87 | 496.33 | 20.84 | 496.33 | 20.83 |
March | 744.00 | 21.06 | 355.00 | 21.02 | 355.00 | 21.00 |
April | 720.00 | 21.47 | 35.67 | 21.45 | 35.67 | 21.43 |
May | 657.33 | 22.44 | 31.00 | 22.50 | 0.00 | 22.50 |
June | 500.17 | 22.73 | 122.00 | 22.95 | 0.00 | 22.95 |
July | 253.83 | 22.90 | 251.83 | 23.36 | 0.00 | 23.36 |
August | 479.83 | 22.76 | 103.67 | 22.95 | 0.00 | 22.95 |
September | 697.00 | 22.20 | 8.83 | 22.22 | 0.00 | 22.22 |
October | 744.00 | 21.36 | 19.00 | 21.35 | 19.00 | 21.34 |
November | 720.00 | 21.02 | 284.50 | 21.01 | 284.50 | 21.01 |
December | 744.00 | 20.61 | 666.17 | 20.59 | 666.17 | 20.58 |
Annual Sum or Average | 7676.17 | 21.49 | 3066.33 | 21.40 | 2549.00 | 21.26 |
Minimum of Months | 253.83 | 20.33 | 8.83 | 20.31 | 0.00 | 20.30 |
Maximum of Months | 744.00 | 22.90 | 692.33 | 23.36 | 692.33 | 23.36 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.56907 | 14.49674 | -0.4150 | 11.58497 |
February | 672.00000 | 22.38130 | 16.95507 | -0.2154 | 6.67073 |
March | 744.00000 | 22.31812 | 21.27426 | -0.2131 | 6.25551 |
April | 720.00000 | 22.35804 | 25.49279 | -0.1793 | 5.86069 |
May | 744.00000 | 22.58835 | 36.55871 | -1.1025 | 30.90692 |
June | 720.00000 | 22.85765 | 50.73432 | -0.9122 | 22.91182 |
July | 744.00000 | 23.39007 | 56.05636 | -0.6804 | 14.99530 |
August | 744.00000 | 23.77321 | 53.74402 | -0.5497 | 11.48387 |
September | 720.00000 | 23.88144 | 41.57297 | -0.5890 | 12.44951 |
October | 744.00000 | 23.90636 | 30.92068 | 0.26269 | 6.50424 |
November | 720.00000 | 23.88127 | 23.22180 | 0.19954 | 5.92923 |
December | 744.00000 | 22.43966 | 15.74089 | -0.1949 | 7.64227 |
Annual Sum or Average | 8760.00000 | 22.94674 | 32.32312 | -0.3840 | 11.97776 |
Minimum of Months | 672.00000 | 21.56907 | 14.49674 | -1.1025 | 5.86069 |
Maximum of Months | 744.00000 | 23.90636 | 56.05636 | 0.26269 | 30.90692 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.00683 | 13.41056 | -0.9046 | 25.49403 |
February | 672.00000 | 20.95089 | 16.01114 | -0.6042 | 15.98959 |
March | 744.00000 | 21.26085 | 20.45649 | -0.4710 | 11.79363 |
April | 720.00000 | 21.57606 | 24.76294 | -0.2981 | 8.85072 |
May | 744.00000 | 21.91566 | 35.99165 | -1.1395 | 35.37264 |
June | 720.00000 | 22.06980 | 51.30870 | -0.9735 | 28.20188 |
July | 744.00000 | 22.46101 | 57.36911 | -0.7693 | 20.37685 |
August | 744.00000 | 22.29231 | 56.79091 | -0.8439 | 23.53645 |
September | 720.00000 | 21.83196 | 45.06527 | -1.1232 | 35.09810 |
October | 744.00000 | 21.41292 | 33.59623 | -0.2988 | 8.94068 |
November | 720.00000 | 21.17818 | 24.87701 | -0.5009 | 11.35963 |
December | 744.00000 | 20.28370 | 15.17856 | -0.8502 | 22.74608 |
Annual Sum or Average | 8760.00000 | 21.43818 | 33.00090 | -0.7326 | 20.68244 |
Minimum of Months | 672.00000 | 20.00683 | 13.41056 | -1.1395 | 8.85072 |
Maximum of Months | 744.00000 | 22.46101 | 57.36911 | -0.2981 | 35.37264 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.45227 | 15.93464 | -0.6967 | 17.45633 |
February | 672.00000 | 21.28835 | 18.52525 | -0.4664 | 10.48081 |
March | 744.00000 | 21.78205 | 22.61323 | -0.3128 | 7.75725 |
April | 720.00000 | 22.52829 | 26.26049 | -0.0967 | 5.85695 |
May | 744.00000 | 23.18593 | 36.34059 | -0.8303 | 20.52764 |
June | 720.00000 | 23.31509 | 50.46719 | -0.6847 | 15.75499 |
July | 744.00000 | 23.57069 | 56.44755 | -0.5440 | 11.62079 |
August | 744.00000 | 23.48140 | 55.71706 | -0.5874 | 12.77876 |
September | 720.00000 | 23.15459 | 44.51236 | -0.7906 | 19.00013 |
October | 744.00000 | 22.52378 | 34.39437 | -0.0460 | 5.78583 |
November | 720.00000 | 21.81132 | 26.69769 | -0.2839 | 7.19001 |
December | 744.00000 | 20.76480 | 17.69397 | -0.6128 | 14.19144 |
Annual Sum or Average | 8760.00000 | 22.32587 | 33.89102 | -0.4966 | 12.38681 |
Minimum of Months | 672.00000 | 20.45227 | 15.93464 | -0.8303 | 5.78583 |
Maximum of Months | 744.00000 | 23.57069 | 56.44755 | -0.0460 | 20.52764 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.84729 | 10.63997 | -0.0334 | 20.74385 |
February | 672.00000 | 22.22058 | 12.92502 | 0.31313 | 15.42521 |
March | 744.00000 | 22.84856 | 16.85612 | 0.50521 | 14.60531 |
April | 720.00000 | 23.14885 | 20.74740 | 0.63671 | 15.87216 |
May | 744.00000 | 23.21399 | 31.62714 | 0.06429 | 9.79245 |
June | 720.00000 | 23.20721 | 46.02797 | 0.17855 | 10.33677 |
July | 744.00000 | 23.22460 | 52.74703 | 0.23946 | 10.62180 |
August | 744.00000 | 23.21822 | 51.75665 | 0.21921 | 10.55222 |
September | 720.00000 | 23.22168 | 39.53822 | 0.10713 | 9.83537 |
October | 744.00000 | 23.17447 | 28.60708 | 0.69352 | 17.41800 |
November | 720.00000 | 23.09536 | 20.56909 | 0.58515 | 14.70347 |
December | 744.00000 | 21.43918 | 12.14062 | 0.11278 | 17.50010 |
Annual Sum or Average | 8760.00000 | 22.73788 | 28.77807 | 0.30090 | 13.95229 |
Minimum of Months | 672.00000 | 20.84729 | 10.63997 | -0.0334 | 9.79245 |
Maximum of Months | 744.00000 | 23.22460 | 52.74703 | 0.69352 | 20.74385 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.32341 | 18.13699 | -0.7268 | 19.67392 |
February | 672.00000 | 21.36576 | 20.76180 | -0.4024 | 11.77023 |
March | 744.00000 | 21.84568 | 25.01619 | -0.2371 | 8.47085 |
April | 720.00000 | 22.39865 | 28.97644 | -0.0249 | 6.82486 |
May | 744.00000 | 22.93058 | 39.42967 | -0.7296 | 18.55596 |
June | 720.00000 | 23.06432 | 53.76492 | -0.5713 | 13.88503 |
July | 744.00000 | 23.33503 | 59.77158 | -0.4067 | 9.88859 |
August | 744.00000 | 23.25840 | 59.00033 | -0.4483 | 11.34773 |
September | 720.00000 | 22.88146 | 47.67402 | -0.6961 | 18.13249 |
October | 744.00000 | 22.21316 | 37.31183 | -0.0286 | 7.27314 |
November | 720.00000 | 21.63888 | 29.35544 | -0.2924 | 8.18982 |
December | 744.00000 | 20.56000 | 19.99720 | -0.6808 | 17.13239 |
Annual Sum or Average | 8760.00000 | 22.15396 | 36.69324 | -0.4378 | 12.61138 |
Minimum of Months | 672.00000 | 20.32341 | 18.13699 | -0.7296 | 6.82486 |
Maximum of Months | 744.00000 | 23.33503 | 59.77158 | -0.0249 | 19.67392 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.71114 | 18.21503 | -0.6019 | 15.32204 |
February | 672.00000 | 21.73187 | 20.79960 | -0.3258 | 8.52229 |
March | 744.00000 | 22.24605 | 24.85491 | -0.1678 | 6.50308 |
April | 720.00000 | 22.90019 | 28.51141 | 0.03406 | 5.67294 |
May | 744.00000 | 23.39257 | 38.60417 | -0.6951 | 16.00706 |
June | 720.00000 | 23.48664 | 52.50856 | -0.5562 | 12.22953 |
July | 744.00000 | 23.64386 | 58.56238 | -0.4447 | 9.50345 |
August | 744.00000 | 23.61624 | 57.69663 | -0.4678 | 10.06233 |
September | 720.00000 | 23.43713 | 46.43116 | -0.6286 | 14.13563 |
October | 744.00000 | 22.91263 | 36.40618 | 0.08926 | 6.08373 |
November | 720.00000 | 22.27159 | 28.81419 | -0.1427 | 6.17854 |
December | 744.00000 | 21.06009 | 19.98305 | -0.5128 | 12.20173 |
Annual Sum or Average | 8760.00000 | 22.62033 | 36.03929 | -0.3692 | 10.22277 |
Minimum of Months | 672.00000 | 20.71114 | 18.21503 | -0.6951 | 5.67294 |
Maximum of Months | 744.00000 | 23.64386 | 58.56238 | 0.08926 | 16.00706 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.56431 | 26.93480 | -0.8066 | 19.25922 |
February | 672.00000 | 20.87740 | 29.30447 | -0.6567 | 15.07675 |
March | 744.00000 | 21.03002 | 33.86519 | -0.5406 | 12.29152 |
April | 720.00000 | 21.38641 | 37.26057 | -0.3451 | 8.70737 |
May | 744.00000 | 21.68551 | 43.21097 | -1.2312 | 38.45368 |
June | 720.00000 | 21.70547 | 51.11438 | -1.1404 | 34.09999 |
July | 744.00000 | 21.73027 | 52.15129 | -1.0789 | 31.41645 |
August | 744.00000 | 21.69504 | 53.63269 | -1.1302 | 33.67559 |
September | 720.00000 | 21.59600 | 51.57827 | -1.2720 | 40.26762 |
October | 744.00000 | 21.22024 | 46.18862 | -0.3691 | 8.83274 |
November | 720.00000 | 20.86717 | 38.63137 | -0.5908 | 13.03364 |
December | 744.00000 | 20.53346 | 28.89243 | -0.8062 | 19.21114 |
Annual Sum or Average | 8760.00000 | 21.24231 | 41.12115 | -0.8320 | 22.91167 |
Minimum of Months | 672.00000 | 20.53346 | 26.93480 | -1.2720 | 8.70737 |
Maximum of Months | 744.00000 | 21.73027 | 53.63269 | -0.3451 | 40.26762 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.44120 | 27.16273 | -0.8697 | 21.59238 |
February | 672.00000 | 20.59191 | 29.81693 | -0.7619 | 17.87758 |
March | 744.00000 | 20.73876 | 34.39828 | -0.6424 | 14.48597 |
April | 720.00000 | 21.31461 | 37.51879 | -0.3946 | 9.67382 |
May | 744.00000 | 22.21705 | 42.89500 | -1.1023 | 35.54261 |
June | 720.00000 | 22.55573 | 50.41308 | -0.9036 | 28.63072 |
July | 744.00000 | 22.71634 | 51.89649 | -0.8043 | 25.46574 |
August | 744.00000 | 22.53048 | 53.71452 | -0.9092 | 28.24205 |
September | 720.00000 | 21.90055 | 51.86552 | -1.2220 | 39.46604 |
October | 744.00000 | 21.11134 | 46.73043 | -0.4212 | 9.47186 |
November | 720.00000 | 20.65064 | 39.11795 | -0.6614 | 14.69950 |
December | 744.00000 | 20.46772 | 29.05021 | -0.8482 | 20.78890 |
Annual Sum or Average | 8760.00000 | 21.44145 | 41.27017 | -0.7953 | 22.18616 |
Minimum of Months | 672.00000 | 20.44120 | 27.16273 | -1.2220 | 9.47186 |
Maximum of Months | 744.00000 | 22.71634 | 53.71452 | -0.3946 | 39.46604 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.49381 | 23.79823 | -0.7645 | 18.07624 |
February | 672.00000 | 20.75230 | 26.73650 | -0.6662 | 14.73233 |
March | 744.00000 | 20.91491 | 31.41172 | -0.5767 | 12.26748 |
April | 720.00000 | 21.27273 | 34.80214 | -0.4227 | 8.97978 |
May | 744.00000 | 21.83404 | 41.23271 | -1.3158 | 42.03135 |
June | 720.00000 | 22.13377 | 50.23007 | -1.1301 | 33.48891 |
July | 744.00000 | 22.23481 | 54.11416 | -1.0632 | 30.61464 |
August | 744.00000 | 22.09275 | 54.47764 | -1.1345 | 33.47351 |
September | 720.00000 | 21.62761 | 49.43103 | -1.3603 | 43.88577 |
October | 744.00000 | 21.23471 | 43.70164 | -0.3806 | 8.15503 |
November | 720.00000 | 20.93953 | 35.86904 | -0.5413 | 11.41341 |
December | 744.00000 | 20.59230 | 25.73030 | -0.7252 | 16.69832 |
Annual Sum or Average | 8760.00000 | 21.34682 | 39.36178 | -0.8413 | 22.86673 |
Minimum of Months | 672.00000 | 20.49381 | 23.79823 | -1.3603 | 8.15503 |
Maximum of Months | 744.00000 | 22.23481 | 54.47764 | -0.3806 | 43.88577 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.54246 | 26.93149 | -0.8102 | 19.37827 |
February | 672.00000 | 20.89384 | 29.28287 | -0.6535 | 14.89912 |
March | 744.00000 | 21.11983 | 33.70644 | -0.5206 | 11.94355 |
April | 720.00000 | 21.48373 | 37.14515 | -0.3163 | 8.47086 |
May | 744.00000 | 21.71787 | 43.00052 | -1.2270 | 38.28085 |
June | 720.00000 | 21.73058 | 50.39827 | -1.1195 | 33.24843 |
July | 744.00000 | 21.74399 | 51.60955 | -1.0751 | 31.33324 |
August | 744.00000 | 21.71084 | 53.34283 | -1.1314 | 33.73429 |
September | 720.00000 | 21.61272 | 51.50235 | -1.2692 | 40.17004 |
October | 744.00000 | 21.23462 | 46.05572 | -0.3703 | 8.81544 |
November | 720.00000 | 20.85199 | 38.64457 | -0.5932 | 13.05950 |
December | 744.00000 | 20.52220 | 28.88183 | -0.8070 | 19.26808 |
Annual Sum or Average | 8760.00000 | 21.26505 | 40.93154 | -0.8258 | 22.76988 |
Minimum of Months | 672.00000 | 20.52220 | 26.93149 | -1.2692 | 8.47086 |
Maximum of Months | 744.00000 | 21.74399 | 53.34283 | -0.3163 | 40.17004 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.42905 | 27.09862 | -0.8729 | 21.76137 |
February | 672.00000 | 20.58077 | 29.82405 | -0.7649 | 17.88852 |
March | 744.00000 | 20.82513 | 34.18241 | -0.6241 | 13.94391 |
April | 720.00000 | 21.41475 | 37.23412 | -0.3659 | 8.89942 |
May | 744.00000 | 22.07842 | 42.58696 | -1.1501 | 35.42590 |
June | 720.00000 | 22.46417 | 49.92103 | -0.9169 | 27.28004 |
July | 744.00000 | 22.66946 | 51.75549 | -0.8168 | 24.71086 |
August | 744.00000 | 22.37529 | 53.85205 | -0.9600 | 27.85209 |
September | 720.00000 | 21.78050 | 51.76842 | -1.2604 | 39.71154 |
October | 744.00000 | 21.11368 | 46.50465 | -0.4268 | 9.40342 |
November | 720.00000 | 20.64044 | 39.09643 | -0.6631 | 14.79082 |
December | 744.00000 | 20.46889 | 28.99336 | -0.8478 | 20.81346 |
Annual Sum or Average | 8760.00000 | 21.40826 | 41.12289 | -0.8062 | 21.89747 |
Minimum of Months | 672.00000 | 20.42905 | 27.09862 | -1.2604 | 8.89942 |
Maximum of Months | 744.00000 | 22.66946 | 53.85205 | -0.3659 | 39.71154 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.50067 | 27.44008 | -0.8734 | 21.63812 |
February | 672.00000 | 20.76474 | 29.89869 | -0.7282 | 17.23782 |
March | 744.00000 | 20.92919 | 34.61716 | -0.5985 | 13.89464 |
April | 720.00000 | 21.30887 | 38.08189 | -0.3833 | 9.57108 |
May | 744.00000 | 21.66726 | 43.84051 | -1.2445 | 39.35222 |
June | 720.00000 | 21.69247 | 52.12491 | -1.1432 | 34.47518 |
July | 744.00000 | 21.72107 | 53.33326 | -1.0784 | 31.64388 |
August | 744.00000 | 21.67568 | 55.25755 | -1.1362 | 34.16250 |
September | 720.00000 | 21.55466 | 53.15518 | -1.3016 | 41.90903 |
October | 744.00000 | 21.12164 | 47.48092 | -0.4148 | 9.80080 |
November | 720.00000 | 20.75495 | 39.63644 | -0.6534 | 14.75316 |
December | 744.00000 | 20.48985 | 29.40915 | -0.8688 | 21.45625 |
Annual Sum or Average | 8760.00000 | 21.18358 | 42.08179 | -0.8698 | 24.20360 |
Minimum of Months | 672.00000 | 20.48985 | 27.44008 | -1.3016 | 9.57108 |
Maximum of Months | 744.00000 | 21.72107 | 55.25755 | -0.3833 | 41.90903 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.41642 | 27.59578 | -0.9293 | 23.88555 |
February | 672.00000 | 20.53373 | 30.36920 | -0.8250 | 20.01559 |
March | 744.00000 | 20.66300 | 35.12751 | -0.6987 | 16.18632 |
April | 720.00000 | 21.24385 | 38.41599 | -0.4330 | 10.79173 |
May | 744.00000 | 22.26763 | 43.35360 | -1.0901 | 36.56164 |
June | 720.00000 | 22.62531 | 50.90263 | -0.8746 | 29.46762 |
July | 744.00000 | 22.77107 | 52.36872 | -0.7781 | 26.25692 |
August | 744.00000 | 22.58734 | 54.52854 | -0.8875 | 29.03070 |
September | 720.00000 | 21.88602 | 53.32291 | -1.2432 | 41.25543 |
October | 744.00000 | 21.00073 | 48.09290 | -0.4718 | 10.61074 |
November | 720.00000 | 20.56223 | 40.10348 | -0.7213 | 16.52381 |
December | 744.00000 | 20.45160 | 29.53488 | -0.9055 | 22.93931 |
Annual Sum or Average | 8760.00000 | 21.42290 | 42.03109 | -0.8215 | 23.64712 |
Minimum of Months | 672.00000 | 20.41642 | 27.59578 | -1.2432 | 10.61074 |
Maximum of Months | 744.00000 | 22.77107 | 54.52854 | -0.4330 | 41.25543 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.96329 | 28.40285 | -0.6549 | 15.49888 |
February | 672.00000 | 21.24381 | 30.69397 | -0.5096 | 12.40620 |
March | 744.00000 | 21.28252 | 34.93231 | -0.4433 | 10.85279 |
April | 720.00000 | 21.48390 | 38.08138 | -0.3138 | 8.57801 |
May | 744.00000 | 21.68370 | 43.72068 | -1.2771 | 40.79816 |
June | 720.00000 | 21.68903 | 51.96638 | -1.1991 | 36.87125 |
July | 744.00000 | 21.71153 | 53.74325 | -1.1430 | 34.36210 |
August | 744.00000 | 21.68153 | 54.41863 | -1.1671 | 35.52956 |
September | 720.00000 | 21.62424 | 51.01554 | -1.2678 | 40.37430 |
October | 744.00000 | 21.35152 | 46.03487 | -0.3162 | 8.40162 |
November | 720.00000 | 21.11489 | 39.28554 | -0.4946 | 11.43869 |
December | 744.00000 | 20.83944 | 30.30855 | -0.6888 | 16.22484 |
Annual Sum or Average | 8760.00000 | 21.38934 | 41.94052 | -0.7916 | 22.67657 |
Minimum of Months | 672.00000 | 20.83944 | 28.40285 | -1.2771 | 8.40162 |
Maximum of Months | 744.00000 | 21.71153 | 54.41863 | -0.3138 | 40.79816 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.93681 | 20.63803 | -0.3188 | 11.49734 |
February | 672.00000 | 22.88064 | 22.99570 | -0.0617 | 6.87675 |
March | 744.00000 | 23.37603 | 26.31690 | 0.10720 | 6.15943 |
April | 720.00000 | 23.76155 | 29.14920 | 0.26838 | 6.82996 |
May | 744.00000 | 23.94244 | 38.40249 | -0.4217 | 9.06360 |
June | 720.00000 | 23.97458 | 51.69000 | -0.2814 | 6.86859 |
July | 744.00000 | 23.98400 | 57.97836 | -0.2184 | 6.08412 |
August | 744.00000 | 23.96186 | 57.29507 | -0.2581 | 6.51217 |
September | 720.00000 | 23.90345 | 46.30161 | -0.4085 | 8.78306 |
October | 744.00000 | 23.75037 | 36.73351 | 0.31564 | 7.38358 |
November | 720.00000 | 23.49895 | 29.72391 | 0.16173 | 6.19359 |
December | 744.00000 | 22.37820 | 22.20833 | -0.2007 | 8.85632 |
Annual Sum or Average | 8760.00000 | 23.44667 | 36.70294 | -0.1106 | 7.60290 |
Minimum of Months | 672.00000 | 21.93681 | 20.63803 | -0.4217 | 6.08412 |
Maximum of Months | 744.00000 | 23.98400 | 57.97836 | 0.31564 | 11.49734 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.16197 | 19.89703 | -0.2259 | 10.68531 |
February | 672.00000 | 23.10892 | 22.09128 | 0.03305 | 6.78484 |
March | 744.00000 | 23.57483 | 25.27313 | 0.19548 | 6.53613 |
April | 720.00000 | 23.88490 | 28.16058 | 0.33713 | 7.56975 |
May | 744.00000 | 23.98169 | 37.69073 | -0.3594 | 7.96055 |
June | 720.00000 | 23.99200 | 51.07750 | -0.2300 | 6.29168 |
July | 744.00000 | 23.99357 | 57.44682 | -0.1738 | 5.71319 |
August | 744.00000 | 23.98736 | 56.66449 | -0.2054 | 5.97389 |
September | 720.00000 | 23.96186 | 45.47296 | -0.3375 | 7.57734 |
October | 744.00000 | 23.87436 | 35.67201 | 0.38501 | 8.26874 |
November | 720.00000 | 23.70035 | 28.62895 | 0.25193 | 6.76013 |
December | 744.00000 | 22.59638 | 21.37010 | -0.1079 | 8.35076 |
Annual Sum or Average | 8760.00000 | 23.56849 | 35.87178 | -0.0375 | 7.38106 |
Minimum of Months | 672.00000 | 22.16197 | 19.89703 | -0.3594 | 5.71319 |
Maximum of Months | 744.00000 | 23.99357 | 57.44682 | 0.38501 | 10.68531 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.17634 | 20.12724 | 0.40559 | 22.38539 |
February | 672.00000 | 23.12568 | 20.85813 | 0.67430 | 22.47420 |
March | 744.00000 | 23.59247 | 23.76447 | 0.84766 | 24.38048 |
April | 720.00000 | 23.83262 | 26.94818 | 0.99550 | 28.15971 |
May | 744.00000 | 23.92111 | 36.96212 | 0.60083 | 17.34466 |
June | 720.00000 | 23.95310 | 50.26134 | 0.74891 | 21.03354 |
July | 744.00000 | 23.96677 | 56.54116 | 0.81448 | 23.00862 |
August | 744.00000 | 23.95824 | 55.64532 | 0.76501 | 21.35202 |
September | 720.00000 | 23.91700 | 44.37902 | 0.60877 | 17.02559 |
October | 744.00000 | 23.84847 | 34.34244 | 1.02801 | 29.25929 |
November | 720.00000 | 23.75516 | 27.12612 | 0.89442 | 24.29885 |
December | 744.00000 | 22.63223 | 21.05328 | 0.52171 | 21.38478 |
Annual Sum or Average | 8760.00000 | 23.55677 | 34.92325 | 0.74189 | 22.67775 |
Minimum of Months | 672.00000 | 22.17634 | 20.12724 | 0.40559 | 17.02559 |
Maximum of Months | 744.00000 | 23.96677 | 56.54116 | 1.02801 | 29.25929 |
Report: OccupantComfortDataSummaryMonthly
For: STORAGE_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.22795 | 12.98016 | -0.8352 | 21.43708 |
February | 672.00000 | 20.88386 | 15.58534 | -0.6482 | 14.11033 |
March | 744.00000 | 20.99526 | 20.10453 | -0.5711 | 11.95178 |
April | 720.00000 | 21.32150 | 24.31303 | -0.4321 | 9.21741 |
May | 744.00000 | 22.42324 | 34.23743 | -1.1537 | 33.99608 |
June | 720.00000 | 22.90705 | 48.35716 | -0.8940 | 22.74313 |
July | 744.00000 | 23.30452 | 54.32203 | -0.7140 | 16.02113 |
August | 744.00000 | 23.04637 | 53.88492 | -0.8101 | 19.17867 |
September | 720.00000 | 22.42611 | 42.89619 | -1.0991 | 31.02923 |
October | 744.00000 | 21.45189 | 32.94047 | -0.3431 | 7.85732 |
November | 720.00000 | 21.01550 | 24.37391 | -0.5300 | 10.99147 |
December | 744.00000 | 20.59266 | 14.65629 | -0.7378 | 17.32041 |
Annual Sum or Average | 8760.00000 | 21.72096 | 31.64794 | -0.7313 | 18.01415 |
Minimum of Months | 672.00000 | 20.22795 | 12.98016 | -1.1537 | 7.85732 |
Maximum of Months | 744.00000 | 23.30452 | 54.32203 | -0.3431 | 33.99608 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.53740 | 15.82233 | -0.7158 | 16.66244 |
February | 672.00000 | 20.91596 | 18.58840 | -0.5966 | 12.66200 |
March | 744.00000 | 21.04871 | 23.08210 | -0.5261 | 10.91736 |
April | 720.00000 | 21.54464 | 27.08845 | -0.3665 | 8.22755 |
May | 744.00000 | 22.56589 | 37.06519 | -1.1008 | 31.36430 |
June | 720.00000 | 22.96600 | 51.13536 | -0.8689 | 21.68303 |
July | 744.00000 | 23.39365 | 56.90346 | -0.6778 | 14.87181 |
August | 744.00000 | 23.04417 | 56.83202 | -0.8050 | 19.04516 |
September | 720.00000 | 22.35391 | 46.07916 | -1.1192 | 32.13461 |
October | 744.00000 | 21.38055 | 36.05304 | -0.3559 | 8.01199 |
November | 720.00000 | 21.01262 | 27.38476 | -0.5183 | 10.69818 |
December | 744.00000 | 20.72092 | 17.59057 | -0.6668 | 14.82404 |
Annual Sum or Average | 8760.00000 | 21.79559 | 34.56142 | -0.6936 | 16.77657 |
Minimum of Months | 672.00000 | 20.53740 | 15.82233 | -1.1192 | 8.01199 |
Maximum of Months | 744.00000 | 23.39365 | 56.90346 | -0.3559 | 32.13461 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.33033 | 13.79686 | -0.8030 | 20.37315 |
February | 672.00000 | 20.87080 | 16.53444 | -0.6308 | 13.84565 |
March | 744.00000 | 21.05813 | 21.00052 | -0.5313 | 11.16779 |
April | 720.00000 | 21.46830 | 25.11305 | -0.3704 | 8.36283 |
May | 744.00000 | 22.57835 | 34.84445 | -1.0483 | 29.69211 |
June | 720.00000 | 23.01545 | 48.79605 | -0.7976 | 19.66472 |
July | 744.00000 | 23.38980 | 54.63970 | -0.6220 | 13.78298 |
August | 744.00000 | 23.05567 | 54.58916 | -0.7482 | 17.64586 |
September | 720.00000 | 22.24583 | 44.16895 | -1.1111 | 32.03168 |
October | 744.00000 | 21.35816 | 34.00109 | -0.3461 | 7.99796 |
November | 720.00000 | 21.01996 | 25.34126 | -0.5187 | 10.75087 |
December | 744.00000 | 20.61246 | 15.53777 | -0.7267 | 17.10760 |
Annual Sum or Average | 8760.00000 | 21.75545 | 32.45545 | -0.6882 | 16.88431 |
Minimum of Months | 672.00000 | 20.33033 | 13.79686 | -1.1111 | 7.99796 |
Maximum of Months | 744.00000 | 23.38980 | 54.63970 | -0.3461 | 32.03168 |
Report: OccupantComfortDataSummaryMonthly
For: MECH_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.43203 | 12.57462 | -0.7733 | 18.94554 |
February | 672.00000 | 20.94424 | 15.18528 | -0.6164 | 13.17705 |
March | 744.00000 | 21.06973 | 19.63358 | -0.5397 | 11.24974 |
April | 720.00000 | 21.60546 | 23.55440 | -0.3660 | 8.22068 |
May | 744.00000 | 22.75784 | 33.23490 | -1.0506 | 29.38550 |
June | 720.00000 | 23.18665 | 47.21520 | -0.8076 | 19.54936 |
July | 744.00000 | 23.56375 | 53.13098 | -0.6332 | 13.68744 |
August | 744.00000 | 23.35834 | 52.54608 | -0.7131 | 16.04709 |
September | 720.00000 | 22.81236 | 41.59316 | -0.9789 | 25.84298 |
October | 744.00000 | 21.82455 | 31.88006 | -0.2590 | 6.85925 |
November | 720.00000 | 21.12649 | 23.82653 | -0.4921 | 10.23442 |
December | 744.00000 | 20.74273 | 14.25823 | -0.6862 | 15.46292 |
Annual Sum or Average | 8760.00000 | 21.95777 | 30.81063 | -0.6600 | 15.74012 |
Minimum of Months | 672.00000 | 20.43203 | 12.57462 | -1.0506 | 6.85925 |
Maximum of Months | 744.00000 | 23.56375 | 53.13098 | -0.2590 | 29.38550 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.306465E+09 | 5123.11 | 27-JAN-16:01 | 60.75 | 0.144541E+10 | 0.00 | 0.175188E+10 | 0.39 | 4.72 | 01-JAN-10:24 | 0.00 | 0.00 |
February | 0.950337E+09 | 15278.07 | 28-FEB-16:06 | 148.72 | 0.448218E+10 | 0.00 | 0.543252E+10 | 1.04 | 4.72 | 01-FEB-16:10 | 0.00 | 0.00 |
March | 0.295347E+10 | 25507.18 | 31-MAR-15:01 | 232.77 | 0.139298E+11 | 0.00 | 0.168832E+11 | 1.48 | 4.72 | 02-MAR-16:30 | 0.00 | 0.00 |
April | 0.135404E+11 | 94165.62 | 23-APR-18:03 | 476.02 | 0.616109E+11 | 0.00 | 0.751513E+11 | 3.09 | 4.72 | 01-APR-08:50 | 0.00 | 0.00 |
May | 0.520139E+11 | 135404.44 | 25-MAY-18:03 | 734.14 | 0.223924E+12 | 0.00 | 0.275938E+12 | 4.49 | 4.72 | 01-MAY-00:50 | 0.00 | 0.00 |
June | 0.105218E+12 | 212166.57 | 29-JUN-18:03 | 720.00 | 0.435648E+12 | 0.00 | 0.540867E+12 | 4.40 | 4.72 | 01-JUN-00:40 | 0.00 | 0.00 |
July | 0.140857E+12 | 173885.84 | 15-JUL-15:03 | 744.00 | 0.585688E+12 | 0.00 | 0.726545E+12 | 4.33 | 4.72 | 01-JUL-03:20 | 0.00 | 0.00 |
August | 0.100006E+12 | 172806.35 | 08-AUG-15:03 | 743.00 | 0.427043E+12 | 0.00 | 0.527049E+12 | 4.43 | 4.72 | 02-AUG-05:03 | 0.00 | 0.00 |
September | 0.343896E+11 | 112736.29 | 01-SEP-15:03 | 703.86 | 0.154245E+12 | 0.00 | 0.188634E+12 | 4.52 | 4.72 | 02-SEP-01:07 | 0.00 | 0.00 |
October | 0.101683E+11 | 79310.90 | 19-OCT-15:03 | 443.85 | 0.466902E+11 | 0.00 | 0.568585E+11 | 2.80 | 4.72 | 01-OCT-00:20 | 0.00 | 0.00 |
November | 0.148444E+10 | 37692.84 | 01-NOV-15:02 | 160.60 | 0.693822E+10 | 0.00 | 0.842266E+10 | 1.05 | 4.72 | 01-NOV-05:15 | 0.00 | 0.00 |
December | 0.194968E+09 | 4390.36 | 05-DEC-19:03 | 43.23 | 0.919547E+09 | 0.00 | 0.111452E+10 | 0.27 | 4.72 | 01-DEC-10:30 | 0.00 | 0.00 |
Annual Sum or Average | 0.462083E+12 | 5210.95 | 0.196256E+13 | 0.00 | 0.242465E+13 | 2.70 | 0.00 | 0.00 | ||||
Minimum of Months | 0.194968E+09 | 4390.36 | 43.23 | 0.919547E+09 | 0.00 | 0.111452E+10 | 0.27 | 4.72 | 0.00 | 0.00 | ||
Maximum of Months | 0.140857E+12 | 212166.57 | 744.00 | 0.585688E+12 | 0.00 | 0.726545E+12 | 4.52 | 4.72 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.677912E+12 | 0.00 | 744.00 | 655634.37 | 09-JAN-05:00 | 0.00 | 36.20 | 60.00 | 2.54 | 0.00 | 0.35 | 0.90 | 09-JAN-05:00 |
February | 0.373306E+12 | 0.00 | 672.00 | 628235.66 | 14-FEB-07:00 | 0.00 | 37.42 | 60.00 | 1.57 | 0.00 | 0.21 | 0.86 | 14-FEB-07:00 |
March | 0.224950E+12 | 0.00 | 740.39 | 599727.90 | 05-MAR-07:00 | 0.00 | 37.83 | 59.89 | 0.86 | 0.00 | 0.11 | 0.82 | 05-MAR-07:00 |
April | 0.694378E+11 | 0.00 | 617.31 | 174279.17 | 05-APR-08:61 | 0.00 | 37.40 | 55.47 | 0.28 | 0.00 | 0.04 | 0.24 | 05-APR-08:61 |
May | 0.528468E+11 | 0.00 | 397.45 | 148976.28 | 05-MAY-08:05 | 0.00 | 29.40 | 44.52 | 0.16 | 0.00 | 0.03 | 0.20 | 05-MAY-08:05 |
June | 0.261192E+11 | 0.00 | 236.01 | 111296.39 | 16-JUN-22:20 | 0.00 | 28.80 | 39.28 | 0.08 | 0.00 | 0.01 | 0.15 | 16-JUN-22:20 |
July | 0.200714E+11 | 0.00 | 137.71 | 113549.49 | 02-JUL-04:30 | 0.00 | 28.08 | 34.18 | 0.06 | 0.00 | 0.01 | 0.16 | 02-JUL-04:30 |
August | 0.198648E+11 | 0.00 | 189.59 | 110390.72 | 19-AUG-00:30 | 0.00 | 27.87 | 36.18 | 0.06 | 0.00 | 0.01 | 0.15 | 19-AUG-00:30 |
September | 0.676000E+11 | 0.00 | 467.94 | 148452.77 | 25-SEP-08:05 | 0.00 | 30.21 | 48.75 | 0.21 | 0.00 | 0.04 | 0.20 | 25-SEP-08:05 |
October | 0.806515E+11 | 0.00 | 687.81 | 176598.60 | 31-OCT-08:62 | 0.00 | 39.18 | 57.73 | 0.31 | 0.00 | 0.04 | 0.24 | 31-OCT-08:62 |
November | 0.147794E+12 | 0.00 | 720.00 | 243842.37 | 25-NOV-09:02 | 0.00 | 38.67 | 60.00 | 0.62 | 0.00 | 0.08 | 0.33 | 25-NOV-09:02 |
December | 0.602017E+12 | 0.00 | 744.00 | 646733.32 | 24-DEC-06:00 | 0.00 | 36.67 | 60.00 | 2.30 | 0.00 | 0.31 | 0.88 | 24-DEC-06:00 |
Annual Sum or Average | 0.236257E+13 | 0.00 | 6354.21 | 0.00 | 33.95 | 51.27 | 0.75 | 0.00 | 0.10 | ||||
Minimum of Months | 0.198648E+11 | 0.00 | 137.71 | 110390.72 | 0.00 | 27.87 | 34.18 | 0.06 | 0.00 | 0.01 | 0.15 | ||
Maximum of Months | 0.677912E+12 | 0.00 | 744.00 | 655634.37 | 0.00 | 39.18 | 60.00 | 2.54 | 0.00 | 0.35 | 0.90 |
Report: DXReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 |
April | 0.823559E+09 | 0.00 | 40.83 | 0.823559E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17162.23 | 23-APR-15:01 | 17162.23 | 23-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.698346E+10 | 0.00 | 227.00 | 0.673692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22951.99 | 26-MAY-09:03 | 18449.18 | 25-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.193787E+11 | 0.00 | 366.83 | 0.130069E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 37981.96 | 25-JUN-08:03 | 20613.49 | 29-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.280739E+11 | 0.00 | 464.17 | 0.170906E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 41145.79 | 05-JUL-13:00 | 19336.59 | 15-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.191298E+11 | 0.00 | 436.17 | 0.124591E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 36218.62 | 31-AUG-20:40 | 19164.59 | 08-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.390652E+10 | 0.00 | 149.17 | 0.315389E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24121.93 | 01-SEP-01:00 | 17387.99 | 01-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.525223E+09 | 0.00 | 24.67 | 0.525223E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14575.81 | 19-OCT-15:01 | 14575.81 | 19-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 78594968.24 | 0.00 | 4.83 | 78594968.24 | 0.00 | 0.00 | 0.00 | 0.00 | 7087.99 | 01-NOV-15:04 | 7087.99 | 01-NOV-15:04 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.788998E+11 | 0.00 | 1713.67 | 0.538748E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.280739E+11 | 0.00 | 464.17 | 0.170906E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 41145.79 | 20613.49 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 |
April | 0.135661E+11 | 0.00 | 70.00 | 0.135661E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 185628.07 | 23-APR-18:10 | 185628.07 | 23-APR-18:10 | 0.00 | 0.00 | 0.00 |
May | 0.104453E+12 | 0.00 | 324.73 | 0.102121E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 280256.76 | 25-MAY-18:03 | 234058.39 | 25-MAY-18:20 | 0.00 | 0.00 | 0.00 |
June | 0.275197E+12 | 0.00 | 505.33 | 0.191595E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 474950.68 | 27-JUN-19:50 | 273495.53 | 29-JUN-18:07 | 0.00 | 0.00 | 0.00 |
July | 0.385290E+12 | 0.00 | 612.67 | 0.247095E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 507283.06 | 21-JUL-19:20 | 237904.48 | 24-JUL-18:07 | 0.00 | 0.00 | 0.00 |
August | 0.261261E+12 | 0.00 | 573.33 | 0.182030E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 459077.91 | 31-AUG-19:05 | 232494.76 | 08-AUG-18:20 | 0.00 | 0.00 | 0.00 |
September | 0.588244E+11 | 0.00 | 239.47 | 0.506791E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 256614.20 | 01-SEP-10:50 | 189075.27 | 01-SEP-15:13 | 0.00 | 0.00 | 0.00 |
October | 0.829179E+10 | 0.00 | 46.83 | 0.829179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 132997.37 | 19-OCT-15:03 | 132997.37 | 19-OCT-15:03 | 0.00 | 0.00 | 0.00 |
November | 0.105207E+10 | 0.00 | 8.00 | 0.105207E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54893.61 | 01-NOV-15:30 | 54893.61 | 01-NOV-15:30 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.110793E+13 | 0.00 | 2380.37 | 0.796430E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.385290E+12 | 0.00 | 612.67 | 0.247095E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 507283.06 | 273495.53 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 8188557.81 | 0.00 | 1.60 | 8178341.77 | 0.00 | 0.00 | 0.00 | 0.00 | 18448.26 | 27-JAN-16:01 | 18448.26 | 27-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.223274E+09 | 0.00 | 28.42 | 0.220874E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19376.86 | 04-FEB-16:01 | 19376.86 | 04-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.806201E+09 | 0.00 | 88.59 | 0.718509E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19382.02 | 29-MAR-15:01 | 19382.02 | 29-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.257540E+10 | 0.00 | 274.70 | 0.231806E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19379.91 | 14-APR-15:01 | 19379.91 | 14-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.665880E+10 | 0.00 | 620.96 | 0.447988E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19377.21 | 13-MAY-18:01 | 19377.21 | 13-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.831075E+10 | 0.00 | 649.27 | 0.462578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20574.16 | 10-JUN-15:01 | 17212.84 | 25-JUN-15:01 | 0.00 | 0.00 | 0.00 |
July | 0.108563E+11 | 0.00 | 701.78 | 0.602882E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19920.69 | 05-JUL-08:61 | 17126.65 | 25-JUL-15:01 | 0.00 | 0.00 | 0.00 |
August | 0.878062E+10 | 0.00 | 664.53 | 0.452709E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20012.50 | 30-AUG-08:61 | 17042.31 | 29-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.444106E+10 | 0.00 | 516.39 | 0.228380E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20443.50 | 19-SEP-15:01 | 19380.96 | 23-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.133701E+10 | 0.00 | 193.40 | 0.731958E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19380.80 | 21-OCT-18:01 | 19380.80 | 21-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 56559443.62 | 0.00 | 18.67 | 50458581.04 | 0.00 | 0.00 | 0.00 | 0.00 | 19376.45 | 09-NOV-16:01 | 19376.45 | 09-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 304633.58 | 0.00 | 0.17 | 257788.24 | 0.00 | 0.00 | 0.00 | 0.00 | 1046.71 | 28-DEC-16:05 | 1046.71 | 28-DEC-16:05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.440545E+11 | 0.00 | 3758.49 | 0.259937E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 304633.58 | 0.00 | 0.17 | 257788.24 | 0.00 | 0.00 | 0.00 | 0.00 | 1046.71 | 1046.71 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.108563E+11 | 0.00 | 701.78 | 0.602882E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20574.16 | 19382.02 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 256323.97 | 0.00 | 0.07 | 236132.05 | 0.00 | 0.00 | 0.00 | 0.00 | 1946.31 | 27-JAN-16:04 | 1946.31 | 27-JAN-16:04 | 0.00 | 0.00 | 0.00 |
February | 38799200.68 | 0.00 | 7.86 | 38500533.37 | 0.00 | 0.00 | 0.00 | 0.00 | 18099.38 | 28-FEB-16:01 | 18099.38 | 28-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.327889E+09 | 0.00 | 46.43 | 0.286867E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18464.15 | 31-MAR-18:01 | 18464.15 | 31-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.136294E+10 | 0.00 | 174.54 | 0.118800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21216.08 | 11-APR-18:11 | 21216.08 | 11-APR-18:11 | 0.00 | 0.00 | 0.00 |
May | 0.462536E+10 | 0.00 | 491.75 | 0.287530E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23291.46 | 06-MAY-18:42 | 23291.46 | 06-MAY-18:42 | 0.00 | 0.00 | 0.00 |
June | 0.613026E+10 | 0.00 | 494.85 | 0.328610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21815.86 | 25-JUN-08:51 | 18539.34 | 07-JUN-21:41 | 0.00 | 0.00 | 0.00 |
July | 0.796136E+10 | 0.00 | 514.65 | 0.434656E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21992.99 | 30-JUL-08:41 | 18403.05 | 07-JUL-21:11 | 0.00 | 0.00 | 0.00 |
August | 0.571912E+10 | 0.00 | 483.80 | 0.268974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20253.17 | 25-AUG-21:51 | 18359.97 | 07-AUG-16:21 | 0.00 | 0.00 | 0.00 |
September | 0.231752E+10 | 0.00 | 381.75 | 0.927991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21235.60 | 23-SEP-17:41 | 21235.60 | 23-SEP-17:41 | 0.00 | 0.00 | 0.00 |
October | 0.412946E+09 | 0.00 | 89.28 | 0.181662E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18064.07 | 21-OCT-18:32 | 18064.07 | 21-OCT-18:32 | 0.00 | 0.00 | 0.00 |
November | 7071614.48 | 0.00 | 1.52 | 5203387.82 | 0.00 | 0.00 | 0.00 | 0.00 | 14806.32 | 17-NOV-16:01 | 14806.32 | 17-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 98811.62 | 0.00 | 0.07 | 12163.85 | 0.00 | 0.00 | 0.00 | 0.00 | 612.87 | 05-DEC-19:06 | 90.23 | 05-DEC-19:06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.289036E+11 | 0.00 | 2686.56 | 0.158262E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 98811.62 | 0.00 | 0.07 | 12163.85 | 0.00 | 0.00 | 0.00 | 0.00 | 612.87 | 90.23 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.796136E+10 | 0.00 | 514.65 | 0.434656E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23291.46 | 23291.46 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 |
February | 0.443088E+09 | 0.00 | 11.44 | 0.443088E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23628.53 | 28-FEB-14:35 | 23628.53 | 28-FEB-14:35 | 0.00 | 0.00 | 0.00 |
March | 0.564493E+10 | 0.00 | 112.40 | 0.564493E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47042.71 | 20-MAR-12:30 | 47042.71 | 20-MAR-12:30 | 0.00 | 0.00 | 0.00 |
April | 0.195631E+11 | 0.00 | 341.31 | 0.188183E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 52698.72 | 13-APR-13:00 | 52698.72 | 13-APR-13:00 | 0.00 | 0.00 | 0.00 |
May | 0.363696E+11 | 0.00 | 635.72 | 0.229825E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 50329.80 | 18-MAY-13:00 | 46629.72 | 06-MAY-13:00 | 0.00 | 0.00 | 0.00 |
June | 0.407380E+11 | 0.00 | 665.56 | 0.171734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 50401.13 | 30-JUN-13:00 | 38498.65 | 30-JUN-13:00 | 0.00 | 0.00 | 0.00 |
July | 0.523436E+11 | 0.00 | 733.54 | 0.221538E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 54020.28 | 23-JUL-13:00 | 44038.78 | 23-JUL-13:20 | 0.00 | 0.00 | 0.00 |
August | 0.492495E+11 | 0.00 | 719.56 | 0.220432E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 59267.47 | 25-AUG-12:50 | 54230.49 | 25-AUG-13:00 | 0.00 | 0.00 | 0.00 |
September | 0.354223E+11 | 0.00 | 602.37 | 0.176412E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 60502.62 | 01-SEP-12:50 | 56162.41 | 01-SEP-13:10 | 0.00 | 0.00 | 0.00 |
October | 0.178991E+11 | 0.00 | 283.71 | 0.128140E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 72284.26 | 22-OCT-12:30 | 61326.96 | 19-OCT-13:00 | 0.00 | 0.00 | 0.00 |
November | 0.176255E+10 | 0.00 | 37.51 | 0.176255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41624.23 | 17-NOV-12:20 | 41624.23 | 17-NOV-12:20 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.259436E+12 | 0.00 | 4143.13 | 0.141477E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.523436E+11 | 0.00 | 733.54 | 0.229825E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 72284.26 | 61326.96 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 7557026.01 | 0.00 | 0.46 | 6802785.08 | 0.00 | 0.00 | 0.00 | 0.00 | 12801.36 | 20-JAN-19:05 | 12801.36 | 20-JAN-19:05 | 0.00 | 0.00 | 0.00 |
February | 48967628.90 | 0.00 | 5.36 | 32553239.97 | 0.00 | 0.00 | 0.00 | 0.00 | 43799.72 | 05-FEB-09:01 | 43799.72 | 05-FEB-09:01 | 0.00 | 0.00 | 0.00 |
March | 0.847777E+09 | 0.00 | 50.45 | 0.791243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 86381.26 | 28-MAR-18:01 | 86381.26 | 28-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.825290E+10 | 0.00 | 267.94 | 0.686759E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 91016.64 | 18-APR-18:01 | 91016.64 | 18-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.327061E+11 | 0.00 | 468.05 | 0.233736E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 95471.63 | 21-MAY-21:01 | 95471.63 | 21-MAY-21:01 | 0.00 | 0.00 | 0.00 |
June | 0.455464E+11 | 0.00 | 453.40 | 0.294082E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 106284.81 | 19-JUN-21:51 | 92987.40 | 07-JUN-08:51 | 0.00 | 0.00 | 0.00 |
July | 0.523826E+11 | 0.00 | 465.45 | 0.322509E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 106288.48 | 30-JUL-08:41 | 90224.45 | 01-JUL-21:01 | 0.00 | 0.00 | 0.00 |
August | 0.416894E+11 | 0.00 | 434.77 | 0.235062E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 102087.60 | 28-AUG-21:51 | 86352.69 | 01-AUG-21:11 | 0.00 | 0.00 | 0.00 |
September | 0.240145E+11 | 0.00 | 443.96 | 0.120678E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 97373.28 | 18-SEP-21:52 | 94556.35 | 04-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.699753E+10 | 0.00 | 294.26 | 0.317586E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 88123.62 | 20-OCT-18:11 | 88123.62 | 20-OCT-18:11 | 0.00 | 0.00 | 0.00 |
November | 0.872212E+09 | 0.00 | 58.13 | 0.390426E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 75460.87 | 01-NOV-18:03 | 75460.87 | 01-NOV-18:03 | 0.00 | 0.00 | 0.00 |
December | 13814665.87 | 0.00 | 0.57 | 9935759.58 | 0.00 | 0.00 | 0.00 | 0.00 | 15968.68 | 05-DEC-19:03 | 12923.40 | 17-DEC-19:05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.213380E+12 | 0.00 | 2942.80 | 0.131881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 7557026.01 | 0.00 | 0.46 | 6802785.08 | 0.00 | 0.00 | 0.00 | 0.00 | 12801.36 | 12801.36 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.523826E+11 | 0.00 | 468.05 | 0.322509E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 106288.48 | 95471.63 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 628602.90 | 0.00 | 0.19 | 587603.82 | 0.00 | 0.00 | 0.00 | 0.00 | 1856.39 | 17-JAN-16:04 | 1856.39 | 17-JAN-16:04 | 0.00 | 0.00 | 0.00 |
February | 0.129750E+09 | 0.00 | 30.22 | 0.126372E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17620.92 | 28-FEB-16:01 | 17620.92 | 28-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.635183E+09 | 0.00 | 112.96 | 0.530868E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17714.37 | 31-MAR-15:01 | 17714.37 | 31-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.268434E+10 | 0.00 | 313.36 | 0.233229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17715.19 | 14-APR-15:01 | 17715.19 | 14-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.629808E+10 | 0.00 | 632.55 | 0.407162E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17714.38 | 01-MAY-08:62 | 17714.38 | 01-MAY-08:62 | 0.00 | 0.00 | 0.00 |
June | 0.887099E+10 | 0.00 | 676.99 | 0.509587E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18801.23 | 10-JUN-15:01 | 17714.60 | 01-JUN-18:01 | 0.00 | 0.00 | 0.00 |
July | 0.109014E+11 | 0.00 | 718.22 | 0.614353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18125.39 | 25-JUL-18:02 | 15763.14 | 09-JUL-18:01 | 0.00 | 0.00 | 0.00 |
August | 0.850583E+10 | 0.00 | 681.44 | 0.435609E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18036.63 | 09-AUG-08:61 | 15780.73 | 10-AUG-15:01 | 0.00 | 0.00 | 0.00 |
September | 0.433975E+10 | 0.00 | 512.86 | 0.219581E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18648.35 | 19-SEP-15:01 | 17713.86 | 09-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.122801E+10 | 0.00 | 181.41 | 0.642295E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17713.64 | 21-OCT-18:01 | 17713.64 | 21-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.114641E+09 | 0.00 | 17.11 | 81969382.53 | 0.00 | 0.00 | 0.00 | 0.00 | 17123.92 | 17-NOV-16:01 | 17123.92 | 17-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 730813.27 | 0.00 | 0.69 | 550235.08 | 0.00 | 0.00 | 0.00 | 0.00 | 2468.77 | 01-DEC-09:03 | 2468.77 | 01-DEC-09:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.437093E+11 | 0.00 | 3878.00 | 0.255778E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 628602.90 | 0.00 | 0.19 | 550235.08 | 0.00 | 0.00 | 0.00 | 0.00 | 1856.39 | 1856.39 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.109014E+11 | 0.00 | 718.22 | 0.614353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18801.23 | 17715.19 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 47510.47 | 0.00 | 0.05 | 8329.30 | 0.00 | 0.00 | 0.00 | 0.00 | 542.89 | 19-JAN-19:06 | 85.78 | 19-JAN-19:06 | 0.00 | 0.00 | 0.00 |
February | 8403946.52 | 0.00 | 3.94 | 8171149.30 | 0.00 | 0.00 | 0.00 | 0.00 | 5505.04 | 27-FEB-09:02 | 5505.04 | 27-FEB-09:02 | 0.00 | 0.00 | 0.00 |
March | 0.177809E+09 | 0.00 | 34.99 | 0.137176E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16258.44 | 11-MAR-09:01 | 16258.44 | 11-MAR-09:01 | 0.00 | 0.00 | 0.00 |
April | 0.145831E+10 | 0.00 | 226.32 | 0.121980E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16852.89 | 17-APR-15:01 | 16852.89 | 17-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.454958E+10 | 0.00 | 515.56 | 0.281842E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17815.27 | 26-MAY-08:51 | 17426.82 | 06-MAY-19:01 | 0.00 | 0.00 | 0.00 |
June | 0.681485E+10 | 0.00 | 521.78 | 0.390436E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21508.81 | 28-JUN-07:52 | 19826.60 | 28-JUN-07:52 | 0.00 | 0.00 | 0.00 |
July | 0.805110E+10 | 0.00 | 526.31 | 0.449300E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21436.16 | 23-JUL-08:32 | 18919.07 | 31-JUL-08:32 | 0.00 | 0.00 | 0.00 |
August | 0.568612E+10 | 0.00 | 499.33 | 0.275661E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19536.20 | 30-AUG-08:51 | 17132.73 | 05-AUG-08:32 | 0.00 | 0.00 | 0.00 |
September | 0.248054E+10 | 0.00 | 393.87 | 0.114130E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18735.10 | 01-SEP-08:51 | 17612.24 | 04-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.365378E+09 | 0.00 | 79.77 | 0.174661E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15191.46 | 22-OCT-08:61 | 15003.82 | 21-OCT-18:32 | 0.00 | 0.00 | 0.00 |
November | 12762771.66 | 0.00 | 5.93 | 4483530.01 | 0.00 | 0.00 | 0.00 | 0.00 | 7241.78 | 16-NOV-09:01 | 5527.45 | 16-NOV-09:01 | 0.00 | 0.00 | 0.00 |
December | 106283.64 | 0.00 | 0.08 | 48475.89 | 0.00 | 0.00 | 0.00 | 0.00 | 535.18 | 05-DEC-19:06 | 402.11 | 01-DEC-09:05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.296050E+11 | 0.00 | 2807.92 | 0.166580E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 47510.47 | 0.00 | 0.05 | 8329.30 | 0.00 | 0.00 | 0.00 | 0.00 | 535.18 | 85.78 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.805110E+10 | 0.00 | 526.31 | 0.449300E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21508.81 | 19826.60 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 1010576.79 | 0.00 | 0.89 | 1010576.79 | 0.00 | 0.00 | 0.00 | 0.00 | 3933.65 | 27-JAN-16:01 | 3933.65 | 27-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 54137700.46 | 0.00 | 24.81 | 53700566.65 | 0.00 | 0.00 | 0.00 | 0.00 | 5040.80 | 04-FEB-16:01 | 5040.80 | 04-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.204810E+09 | 0.00 | 77.07 | 0.183332E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5041.85 | 19-MAR-15:01 | 5041.85 | 19-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.644225E+09 | 0.00 | 238.99 | 0.586374E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5041.84 | 14-APR-15:01 | 5041.84 | 14-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.167106E+10 | 0.00 | 563.51 | 0.115789E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5041.05 | 13-MAY-18:01 | 5041.05 | 13-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.208676E+10 | 0.00 | 616.09 | 0.120804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5426.91 | 10-JUN-15:01 | 5041.98 | 01-JUN-18:01 | 0.00 | 0.00 | 0.00 |
July | 0.270989E+10 | 0.00 | 694.58 | 0.154156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5401.43 | 05-JUL-08:61 | 4463.88 | 30-JUL-18:01 | 0.00 | 0.00 | 0.00 |
August | 0.215522E+10 | 0.00 | 648.87 | 0.115369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5419.39 | 30-AUG-08:61 | 4436.58 | 30-AUG-18:01 | 0.00 | 0.00 | 0.00 |
September | 0.102838E+10 | 0.00 | 437.16 | 0.564249E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5403.95 | 19-SEP-15:01 | 5041.86 | 04-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.313611E+09 | 0.00 | 138.77 | 0.185109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5041.42 | 21-OCT-18:01 | 5041.42 | 21-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 11741047.89 | 0.00 | 11.08 | 10968859.64 | 0.00 | 0.00 | 0.00 | 0.00 | 5041.00 | 09-NOV-16:01 | 5041.00 | 09-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 71957.97 | 0.00 | 0.08 | 71957.97 | 0.00 | 0.00 | 0.00 | 0.00 | 341.54 | 28-DEC-16:05 | 341.54 | 28-DEC-16:05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.108809E+11 | 0.00 | 3451.88 | 0.664600E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 71957.97 | 0.00 | 0.08 | 71957.97 | 0.00 | 0.00 | 0.00 | 0.00 | 341.54 | 341.54 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.270989E+10 | 0.00 | 694.58 | 0.154156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5426.91 | 5041.98 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 117975.13 | 0.00 | 0.05 | 117975.13 | 0.00 | 0.00 | 0.00 | 0.00 | 727.65 | 20-JAN-16:04 | 727.65 | 20-JAN-16:04 | 0.00 | 0.00 | 0.00 |
February | 6864324.15 | 0.00 | 6.93 | 6834333.06 | 0.00 | 0.00 | 0.00 | 0.00 | 4463.62 | 28-FEB-16:01 | 4463.62 | 28-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 78591369.15 | 0.00 | 40.33 | 67574161.22 | 0.00 | 0.00 | 0.00 | 0.00 | 4783.50 | 31-MAR-18:01 | 4783.50 | 31-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.337144E+09 | 0.00 | 152.85 | 0.299338E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5529.22 | 11-APR-18:11 | 5529.22 | 11-APR-18:11 | 0.00 | 0.00 | 0.00 |
May | 0.117744E+10 | 0.00 | 455.09 | 0.752434E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6049.19 | 06-MAY-18:42 | 6049.19 | 06-MAY-18:42 | 0.00 | 0.00 | 0.00 |
June | 0.158818E+10 | 0.00 | 473.41 | 0.885163E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5755.18 | 25-JUN-08:51 | 4835.54 | 07-JUN-21:41 | 0.00 | 0.00 | 0.00 |
July | 0.205447E+10 | 0.00 | 515.79 | 0.114942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5785.23 | 30-JUL-08:41 | 5260.53 | 26-JUL-20:52 | 0.00 | 0.00 | 0.00 |
August | 0.143974E+10 | 0.00 | 475.54 | 0.700748E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5525.28 | 10-AUG-21:41 | 5339.31 | 02-AUG-20:02 | 0.00 | 0.00 | 0.00 |
September | 0.506439E+09 | 0.00 | 303.71 | 0.218784E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5535.48 | 04-SEP-18:01 | 5535.48 | 04-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 86451538.12 | 0.00 | 59.44 | 39864025.18 | 0.00 | 0.00 | 0.00 | 0.00 | 4702.30 | 21-OCT-18:32 | 4702.30 | 21-OCT-18:32 | 0.00 | 0.00 | 0.00 |
November | 1071732.84 | 0.00 | 0.83 | 633033.26 | 0.00 | 0.00 | 0.00 | 0.00 | 2131.87 | 17-NOV-16:01 | 2131.87 | 17-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.727652E+10 | 0.00 | 2483.98 | 0.412092E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.205447E+10 | 0.00 | 515.79 | 0.114942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6049.19 | 6049.19 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.808670E+09 | 0.00 | 59.85 | 0.807655E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 24708.26 | 27-JAN-16:01 | 24708.26 | 27-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.199088E+10 | 0.00 | 144.20 | 0.193352E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24734.81 | 08-FEB-16:02 | 24734.81 | 08-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.264457E+10 | 0.00 | 192.59 | 0.232617E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24732.86 | 11-MAR-16:01 | 24732.86 | 11-MAR-16:01 | 0.00 | 0.00 | 0.00 |
April | 0.461792E+10 | 0.00 | 342.55 | 0.406351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24730.39 | 19-APR-15:01 | 24730.39 | 19-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.827640E+10 | 0.00 | 605.37 | 0.535848E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24731.00 | 14-MAY-15:01 | 24731.00 | 14-MAY-15:01 | 0.00 | 0.00 | 0.00 |
June | 0.100260E+11 | 0.00 | 641.31 | 0.526509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27101.54 | 19-JUN-18:01 | 24727.76 | 16-JUN-18:01 | 0.00 | 0.00 | 0.00 |
July | 0.131205E+11 | 0.00 | 691.76 | 0.692047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27720.28 | 25-JUL-18:02 | 21924.69 | 17-JUL-08:61 | 0.00 | 0.00 | 0.00 |
August | 0.120984E+11 | 0.00 | 663.74 | 0.639580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26668.95 | 30-AUG-08:61 | 21737.78 | 10-AUG-15:01 | 0.00 | 0.00 | 0.00 |
September | 0.777519E+10 | 0.00 | 536.59 | 0.461202E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26211.49 | 19-SEP-15:01 | 24732.89 | 05-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.405631E+10 | 0.00 | 285.25 | 0.273148E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24730.66 | 21-OCT-18:01 | 24730.66 | 21-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.127016E+10 | 0.00 | 98.90 | 0.109803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24731.21 | 10-NOV-16:01 | 24731.21 | 10-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.466463E+09 | 0.00 | 42.15 | 0.448659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 24701.43 | 02-DEC-16:01 | 24701.43 | 02-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.671515E+11 | 0.00 | 4304.26 | 0.419609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.466463E+09 | 0.00 | 42.15 | 0.448659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 24701.43 | 21737.78 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.131205E+11 | 0.00 | 691.76 | 0.692047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27720.28 | 24734.81 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 955.44 | 665.88 | 289.56 | 802.35 | 920.56 | 0.00 | 0.00 | 0.00 |
February | 1192.84 | 802.58 | 390.26 | 1116.73 | 788.89 | 0.00 | 0.00 | 0.00 |
March | 1048.51 | 659.96 | 388.55 | 1005.89 | 653.05 | 0.00 | 0.00 | 0.00 |
April | 957.67 | 519.22 | 438.45 | 1003.73 | 425.65 | 0.00 | 0.00 | 0.00 |
May | 819.75 | 289.21 | 530.53 | 953.54 | 221.08 | 0.00 | 0.00 | 0.00 |
June | 720.29 | 189.77 | 530.53 | 899.11 | 140.29 | 0.00 | 0.00 | 0.00 |
July | 792.53 | 252.19 | 540.34 | 1026.14 | 128.16 | 0.00 | 0.00 | 0.00 |
August | 840.95 | 349.61 | 491.34 | 1053.36 | 150.81 | 0.00 | 0.00 | 0.00 |
September | 886.96 | 464.05 | 422.92 | 1023.02 | 255.04 | 0.00 | 0.00 | 0.00 |
October | 788.67 | 470.16 | 318.50 | 802.75 | 406.54 | 0.00 | 0.00 | 0.00 |
November | 688.88 | 431.96 | 256.92 | 611.23 | 606.69 | 0.00 | 0.00 | 0.00 |
December | 733.86 | 481.50 | 252.36 | 568.08 | 899.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 866.80 | 462.59 | 404.21 | 903.99 | 464.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 688.88 | 189.77 | 252.36 | 568.08 | 128.16 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1192.84 | 802.58 | 540.34 | 1116.73 | 920.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2690.46 | 1875.07 | 815.40 | 2243.04 | 2613.37 | 0.00 | 0.00 | 0.00 |
February | 3358.95 | 2260.01 | 1098.94 | 3121.20 | 2248.21 | 0.00 | 0.00 | 0.00 |
March | 2952.53 | 1858.39 | 1094.13 | 2809.18 | 1879.51 | 0.00 | 0.00 | 0.00 |
April | 2696.73 | 1462.08 | 1234.65 | 2798.87 | 1250.57 | 0.00 | 0.00 | 0.00 |
May | 2308.35 | 814.40 | 1493.95 | 2648.77 | 671.55 | 0.00 | 0.00 | 0.00 |
June | 2028.29 | 534.37 | 1493.93 | 2490.52 | 438.54 | 0.00 | 0.00 | 0.00 |
July | 2231.71 | 710.16 | 1521.56 | 2855.56 | 396.23 | 0.00 | 0.00 | 0.00 |
August | 2368.05 | 984.47 | 1383.58 | 2933.81 | 472.21 | 0.00 | 0.00 | 0.00 |
September | 2497.62 | 1306.72 | 1190.90 | 2849.98 | 778.80 | 0.00 | 0.00 | 0.00 |
October | 2220.83 | 1323.95 | 896.88 | 2237.81 | 1197.65 | 0.00 | 0.00 | 0.00 |
November | 1939.83 | 1216.37 | 723.46 | 1703.53 | 1742.96 | 0.00 | 0.00 | 0.00 |
December | 2066.49 | 1355.87 | 710.62 | 1585.40 | 2551.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2440.87 | 1302.62 | 1138.24 | 2518.91 | 1349.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1939.83 | 534.37 | 710.62 | 1585.40 | 396.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3358.95 | 2260.01 | 1521.56 | 3121.20 | 2613.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3495.06 | 2435.82 | 1059.24 | 2948.96 | 3527.54 | 0.00 | 0.00 | 0.00 |
February | 4363.46 | 2935.88 | 1427.58 | 4117.06 | 3032.71 | 0.00 | 0.00 | 0.00 |
March | 3835.50 | 2414.16 | 1421.34 | 3708.32 | 2541.75 | 0.00 | 0.00 | 0.00 |
April | 3503.21 | 1899.33 | 1603.88 | 3692.03 | 1705.74 | 0.00 | 0.00 | 0.00 |
May | 2998.68 | 1057.96 | 1940.72 | 3490.39 | 919.09 | 0.00 | 0.00 | 0.00 |
June | 2634.87 | 694.17 | 1940.70 | 3280.29 | 604.08 | 0.00 | 0.00 | 0.00 |
July | 2899.12 | 922.53 | 1976.59 | 3767.27 | 536.74 | 0.00 | 0.00 | 0.00 |
August | 3076.23 | 1278.88 | 1797.35 | 3865.26 | 641.05 | 0.00 | 0.00 | 0.00 |
September | 3244.55 | 1697.51 | 1547.05 | 3746.30 | 1070.17 | 0.00 | 0.00 | 0.00 |
October | 2884.99 | 1719.89 | 1165.10 | 2932.94 | 1651.71 | 0.00 | 0.00 | 0.00 |
November | 2519.95 | 1580.13 | 939.82 | 2235.37 | 2392.36 | 0.00 | 0.00 | 0.00 |
December | 2684.49 | 1761.35 | 923.13 | 2076.91 | 3464.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3170.82 | 1692.18 | 1478.64 | 3316.14 | 1835.16 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 2519.95 | 694.17 | 923.13 | 2076.91 | 536.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4363.46 | 2935.88 | 1976.59 | 4117.06 | 3527.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 188.91 | 131.66 | 57.25 | 158.57 | 192.77 | 0.00 | 0.00 | 0.00 |
February | 235.84 | 158.68 | 77.16 | 221.39 | 161.50 | 0.00 | 0.00 | 0.00 |
March | 207.31 | 130.48 | 76.82 | 200.11 | 132.41 | 0.00 | 0.00 | 0.00 |
April | 189.35 | 102.66 | 86.69 | 198.97 | 85.96 | 0.00 | 0.00 | 0.00 |
May | 162.08 | 57.18 | 104.90 | 188.19 | 43.66 | 0.00 | 0.00 | 0.00 |
June | 142.41 | 37.52 | 104.90 | 178.38 | 26.72 | 0.00 | 0.00 | 0.00 |
July | 156.70 | 49.86 | 106.84 | 204.68 | 23.13 | 0.00 | 0.00 | 0.00 |
August | 166.27 | 69.12 | 97.15 | 209.44 | 27.59 | 0.00 | 0.00 | 0.00 |
September | 175.37 | 91.75 | 83.62 | 202.96 | 50.10 | 0.00 | 0.00 | 0.00 |
October | 155.93 | 92.96 | 62.97 | 159.94 | 80.75 | 0.00 | 0.00 | 0.00 |
November | 136.20 | 85.41 | 50.80 | 121.89 | 121.92 | 0.00 | 0.00 | 0.00 |
December | 145.10 | 95.20 | 49.90 | 112.25 | 186.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 171.38 | 91.46 | 79.92 | 179.43 | 94.16 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 136.20 | 37.52 | 49.90 | 112.25 | 23.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 235.84 | 158.68 | 106.84 | 221.39 | 192.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 114.25 | 48.36 | 65.89 | 47.04 | 415.75 | 0.00 | 0.00 | 0.00 |
February | 184.83 | 84.82 | 100.00 | 116.51 | 335.25 | 0.00 | 0.00 | 0.00 |
March | 242.50 | 124.39 | 118.11 | 188.64 | 260.10 | 0.00 | 0.00 | 0.00 |
April | 309.48 | 157.00 | 152.48 | 292.04 | 157.53 | 0.00 | 0.00 | 0.00 |
May | 380.58 | 182.10 | 198.48 | 430.56 | 79.02 | 0.00 | 0.00 | 0.00 |
June | 365.65 | 157.92 | 207.72 | 443.39 | 48.91 | 0.00 | 0.00 | 0.00 |
July | 390.91 | 181.80 | 209.10 | 489.27 | 42.64 | 0.00 | 0.00 | 0.00 |
August | 320.89 | 145.42 | 175.47 | 388.22 | 51.06 | 0.00 | 0.00 | 0.00 |
September | 251.92 | 113.10 | 138.81 | 269.19 | 92.92 | 0.00 | 0.00 | 0.00 |
October | 159.31 | 64.11 | 95.20 | 131.32 | 156.08 | 0.00 | 0.00 | 0.00 |
November | 96.94 | 32.95 | 63.99 | 48.39 | 249.33 | 0.00 | 0.00 | 0.00 |
December | 85.45 | 29.60 | 55.84 | 25.67 | 401.97 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 242.21 | 110.28 | 131.92 | 239.93 | 190.28 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 85.45 | 29.60 | 55.84 | 25.67 | 42.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 390.91 | 182.10 | 209.10 | 489.27 | 415.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.24 | 0.00 | 27.24 | 0.21 | 240.08 | 0.00 | 0.00 | 0.00 |
February | 41.84 | 0.00 | 41.84 | 3.14 | 190.91 | 0.00 | 0.00 | 0.00 |
March | 51.48 | 0.00 | 51.48 | 9.09 | 146.00 | 0.00 | 0.00 | 0.00 |
April | 67.70 | 0.70 | 67.00 | 32.65 | 85.69 | 0.00 | 0.00 | 0.00 |
May | 94.95 | 5.04 | 89.91 | 85.91 | 40.72 | 0.00 | 0.00 | 0.00 |
June | 106.11 | 11.81 | 94.30 | 118.22 | 26.42 | 0.00 | 0.00 | 0.00 |
July | 101.44 | 8.91 | 92.54 | 118.00 | 23.74 | 0.00 | 0.00 | 0.00 |
August | 77.03 | 1.47 | 75.57 | 81.09 | 28.92 | 0.00 | 0.00 | 0.00 |
September | 59.98 | 0.06 | 59.91 | 47.48 | 51.49 | 0.00 | 0.00 | 0.00 |
October | 41.58 | 0.00 | 41.58 | 17.04 | 85.56 | 0.00 | 0.00 | 0.00 |
November | 27.53 | 0.00 | 27.53 | 2.62 | 139.45 | 0.00 | 0.00 | 0.00 |
December | 23.08 | 0.00 | 23.08 | 0.00 | 229.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 60.09 | 2.34 | 57.75 | 43.20 | 107.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 23.08 | 0.00 | 23.08 | 0.00 | 23.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 106.11 | 11.81 | 94.30 | 118.22 | 240.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 114.25 | 48.36 | 65.89 | 48.86 | 413.24 | 0.00 | 0.00 | 0.00 |
February | 184.83 | 84.82 | 100.00 | 120.99 | 331.73 | 0.00 | 0.00 | 0.00 |
March | 242.50 | 124.39 | 118.11 | 193.44 | 256.96 | 0.00 | 0.00 | 0.00 |
April | 309.48 | 157.00 | 152.48 | 295.82 | 156.49 | 0.00 | 0.00 | 0.00 |
May | 380.58 | 182.10 | 198.48 | 428.73 | 81.06 | 0.00 | 0.00 | 0.00 |
June | 365.65 | 157.92 | 207.72 | 438.21 | 52.12 | 0.00 | 0.00 | 0.00 |
July | 390.91 | 181.80 | 209.10 | 483.86 | 46.43 | 0.00 | 0.00 | 0.00 |
August | 320.89 | 145.42 | 175.47 | 385.43 | 55.12 | 0.00 | 0.00 | 0.00 |
September | 251.92 | 113.10 | 138.81 | 269.92 | 93.78 | 0.00 | 0.00 | 0.00 |
October | 159.31 | 64.11 | 95.20 | 134.29 | 154.67 | 0.00 | 0.00 | 0.00 |
November | 96.94 | 32.95 | 63.99 | 51.08 | 246.97 | 0.00 | 0.00 | 0.00 |
December | 85.45 | 29.60 | 55.84 | 26.81 | 400.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 242.21 | 110.28 | 131.92 | 240.50 | 190.16 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 85.45 | 29.60 | 55.84 | 26.81 | 46.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 390.91 | 182.10 | 209.10 | 483.86 | 413.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 151.10 | 105.30 | 45.79 | 128.72 | 142.96 | 0.00 | 0.00 | 0.00 |
February | 188.64 | 126.92 | 61.72 | 174.74 | 130.98 | 0.00 | 0.00 | 0.00 |
March | 165.81 | 104.37 | 61.45 | 153.85 | 119.61 | 0.00 | 0.00 | 0.00 |
April | 151.45 | 82.11 | 69.34 | 149.34 | 88.49 | 0.00 | 0.00 | 0.00 |
May | 129.64 | 45.74 | 83.90 | 139.12 | 50.32 | 0.00 | 0.00 | 0.00 |
June | 113.91 | 30.01 | 83.90 | 129.79 | 34.87 | 0.00 | 0.00 | 0.00 |
July | 125.33 | 39.88 | 85.45 | 151.50 | 31.29 | 0.00 | 0.00 | 0.00 |
August | 132.99 | 55.29 | 77.70 | 156.32 | 37.46 | 0.00 | 0.00 | 0.00 |
September | 140.27 | 73.39 | 66.88 | 151.61 | 58.62 | 0.00 | 0.00 | 0.00 |
October | 124.72 | 74.35 | 50.37 | 118.55 | 85.38 | 0.00 | 0.00 | 0.00 |
November | 108.94 | 68.31 | 40.63 | 92.94 | 108.31 | 0.00 | 0.00 | 0.00 |
December | 116.05 | 76.15 | 39.91 | 92.78 | 133.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 137.08 | 73.16 | 63.92 | 136.35 | 84.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 108.94 | 30.01 | 39.91 | 92.78 | 31.29 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 188.64 | 126.92 | 85.45 | 174.74 | 142.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 21.79 | 0.00 | 21.79 | 0.10 | 197.64 | 0.00 | 0.00 | 0.00 |
February | 33.47 | 0.00 | 33.47 | 2.19 | 157.05 | 0.00 | 0.00 | 0.00 |
March | 41.19 | 0.00 | 41.19 | 6.98 | 119.22 | 0.00 | 0.00 | 0.00 |
April | 54.17 | 0.56 | 53.61 | 27.30 | 68.87 | 0.00 | 0.00 | 0.00 |
May | 75.97 | 4.03 | 71.94 | 72.88 | 31.49 | 0.00 | 0.00 | 0.00 |
June | 84.90 | 9.45 | 75.45 | 99.09 | 19.97 | 0.00 | 0.00 | 0.00 |
July | 81.17 | 7.12 | 74.04 | 99.55 | 17.31 | 0.00 | 0.00 | 0.00 |
August | 61.63 | 1.17 | 60.46 | 68.92 | 21.50 | 0.00 | 0.00 | 0.00 |
September | 47.99 | 0.05 | 47.94 | 40.00 | 40.16 | 0.00 | 0.00 | 0.00 |
October | 33.27 | 0.00 | 33.27 | 13.30 | 70.20 | 0.00 | 0.00 | 0.00 |
November | 22.03 | 0.00 | 22.03 | 1.77 | 116.27 | 0.00 | 0.00 | 0.00 |
December | 18.46 | 0.00 | 18.46 | 0.00 | 189.80 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 48.08 | 1.87 | 46.20 | 36.22 | 87.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.46 | 0.00 | 18.46 | 0.00 | 17.31 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 84.90 | 9.45 | 75.45 | 99.55 | 197.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 111.18 | 46.10 | 65.08 | 39.96 | 410.34 | 0.00 | 0.00 | 0.00 |
February | 176.67 | 75.98 | 100.69 | 98.65 | 324.70 | 0.00 | 0.00 | 0.00 |
March | 240.14 | 120.73 | 119.42 | 177.16 | 251.87 | 0.00 | 0.00 | 0.00 |
April | 330.74 | 178.31 | 152.43 | 313.33 | 151.22 | 0.00 | 0.00 | 0.00 |
May | 359.21 | 158.43 | 200.78 | 398.81 | 73.86 | 0.00 | 0.00 | 0.00 |
June | 405.32 | 193.86 | 211.46 | 492.60 | 46.68 | 0.00 | 0.00 | 0.00 |
July | 397.90 | 187.19 | 210.71 | 495.74 | 40.25 | 0.00 | 0.00 | 0.00 |
August | 306.28 | 133.85 | 172.43 | 366.68 | 49.16 | 0.00 | 0.00 | 0.00 |
September | 245.93 | 110.35 | 135.58 | 258.97 | 89.86 | 0.00 | 0.00 | 0.00 |
October | 148.07 | 55.67 | 92.39 | 113.40 | 152.13 | 0.00 | 0.00 | 0.00 |
November | 94.85 | 31.59 | 63.26 | 43.12 | 245.16 | 0.00 | 0.00 | 0.00 |
December | 87.20 | 32.73 | 54.47 | 25.05 | 397.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 242.20 | 110.48 | 131.71 | 235.95 | 185.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 87.20 | 31.59 | 54.47 | 25.05 | 40.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 405.32 | 193.86 | 211.46 | 495.74 | 410.34 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 188.91 | 131.66 | 57.25 | 158.41 | 192.53 | 0.00 | 0.00 | 0.00 |
February | 235.84 | 158.68 | 77.16 | 220.93 | 161.15 | 0.00 | 0.00 | 0.00 |
March | 207.31 | 130.48 | 76.82 | 198.98 | 131.95 | 0.00 | 0.00 | 0.00 |
April | 189.35 | 102.66 | 86.69 | 197.50 | 85.58 | 0.00 | 0.00 | 0.00 |
May | 162.08 | 57.18 | 104.90 | 187.69 | 43.14 | 0.00 | 0.00 | 0.00 |
June | 142.41 | 37.52 | 104.90 | 177.17 | 26.36 | 0.00 | 0.00 | 0.00 |
July | 156.70 | 49.86 | 106.84 | 204.00 | 22.59 | 0.00 | 0.00 | 0.00 |
August | 166.27 | 69.12 | 97.15 | 209.13 | 27.18 | 0.00 | 0.00 | 0.00 |
September | 175.37 | 91.75 | 83.62 | 202.49 | 49.62 | 0.00 | 0.00 | 0.00 |
October | 155.93 | 92.96 | 62.97 | 159.70 | 80.37 | 0.00 | 0.00 | 0.00 |
November | 136.20 | 85.41 | 50.80 | 121.76 | 121.73 | 0.00 | 0.00 | 0.00 |
December | 145.10 | 95.20 | 49.90 | 112.09 | 186.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 171.38 | 91.46 | 79.92 | 178.86 | 93.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 136.20 | 37.52 | 49.90 | 112.09 | 22.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 235.84 | 158.68 | 106.84 | 220.93 | 192.53 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.24 | 0.00 | 27.24 | 0.20 | 240.00 | 0.00 | 0.00 | 0.00 |
February | 41.84 | 0.00 | 41.84 | 2.98 | 190.78 | 0.00 | 0.00 | 0.00 |
March | 51.48 | 0.00 | 51.48 | 8.40 | 145.93 | 0.00 | 0.00 | 0.00 |
April | 67.70 | 0.70 | 67.00 | 31.36 | 85.58 | 0.00 | 0.00 | 0.00 |
May | 94.95 | 5.04 | 89.91 | 86.16 | 39.92 | 0.00 | 0.00 | 0.00 |
June | 106.11 | 11.81 | 94.30 | 117.32 | 25.69 | 0.00 | 0.00 | 0.00 |
July | 101.44 | 8.91 | 92.54 | 117.31 | 22.83 | 0.00 | 0.00 | 0.00 |
August | 77.03 | 1.47 | 75.57 | 81.15 | 27.85 | 0.00 | 0.00 | 0.00 |
September | 59.98 | 0.06 | 59.91 | 47.16 | 50.41 | 0.00 | 0.00 | 0.00 |
October | 41.58 | 0.00 | 41.58 | 16.65 | 84.97 | 0.00 | 0.00 | 0.00 |
November | 27.53 | 0.00 | 27.53 | 2.55 | 139.40 | 0.00 | 0.00 | 0.00 |
December | 23.08 | 0.00 | 23.08 | 0.00 | 229.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 60.09 | 2.34 | 57.75 | 42.85 | 106.59 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 23.08 | 0.00 | 23.08 | 0.00 | 22.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 106.11 | 11.81 | 94.30 | 117.32 | 240.00 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 111.18 | 46.10 | 65.08 | 40.93 | 406.92 | 0.00 | 0.00 | 0.00 |
February | 176.67 | 75.98 | 100.69 | 101.63 | 319.41 | 0.00 | 0.00 | 0.00 |
March | 240.14 | 120.73 | 119.42 | 180.90 | 247.49 | 0.00 | 0.00 | 0.00 |
April | 330.74 | 178.31 | 152.43 | 316.79 | 149.79 | 0.00 | 0.00 | 0.00 |
May | 359.21 | 158.43 | 200.78 | 398.60 | 75.26 | 0.00 | 0.00 | 0.00 |
June | 405.32 | 193.86 | 211.46 | 488.55 | 49.49 | 0.00 | 0.00 | 0.00 |
July | 397.90 | 187.19 | 210.71 | 490.65 | 43.57 | 0.00 | 0.00 | 0.00 |
August | 306.28 | 133.85 | 172.43 | 365.06 | 52.25 | 0.00 | 0.00 | 0.00 |
September | 245.93 | 110.35 | 135.58 | 260.77 | 90.04 | 0.00 | 0.00 | 0.00 |
October | 148.07 | 55.67 | 92.39 | 116.21 | 150.24 | 0.00 | 0.00 | 0.00 |
November | 94.85 | 31.59 | 63.26 | 44.45 | 241.52 | 0.00 | 0.00 | 0.00 |
December | 87.20 | 32.73 | 54.47 | 25.59 | 395.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 242.20 | 110.48 | 131.71 | 236.49 | 184.59 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 87.20 | 31.59 | 54.47 | 25.59 | 43.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 405.32 | 193.86 | 211.46 | 490.65 | 406.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.49 | 0.00 | 34.49 | 0.10 | 318.25 | 0.00 | 0.00 | 0.00 |
February | 52.98 | 0.00 | 52.98 | 2.92 | 254.70 | 0.00 | 0.00 | 0.00 |
March | 65.20 | 0.00 | 65.20 | 10.10 | 193.56 | 0.00 | 0.00 | 0.00 |
April | 85.74 | 0.88 | 84.86 | 41.63 | 112.87 | 0.00 | 0.00 | 0.00 |
May | 120.24 | 6.38 | 113.86 | 112.66 | 54.33 | 0.00 | 0.00 | 0.00 |
June | 134.38 | 14.95 | 119.43 | 153.63 | 35.56 | 0.00 | 0.00 | 0.00 |
July | 128.47 | 11.28 | 117.20 | 152.70 | 32.69 | 0.00 | 0.00 | 0.00 |
August | 97.56 | 1.86 | 95.70 | 105.51 | 39.60 | 0.00 | 0.00 | 0.00 |
September | 75.96 | 0.08 | 75.88 | 60.96 | 69.50 | 0.00 | 0.00 | 0.00 |
October | 52.65 | 0.00 | 52.65 | 20.30 | 114.39 | 0.00 | 0.00 | 0.00 |
November | 34.86 | 0.00 | 34.86 | 2.67 | 188.44 | 0.00 | 0.00 | 0.00 |
December | 29.23 | 0.00 | 29.23 | 0.00 | 306.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 76.10 | 2.97 | 73.13 | 55.59 | 142.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.23 | 0.00 | 29.23 | 0.00 | 32.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 134.38 | 14.95 | 119.43 | 153.63 | 318.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 12.72 | 0.00 | 12.72 | 0.04 | 117.32 | 0.00 | 0.00 | 0.00 |
February | 19.53 | 0.00 | 19.53 | 1.08 | 93.89 | 0.00 | 0.00 | 0.00 |
March | 24.04 | 0.00 | 24.04 | 3.72 | 71.35 | 0.00 | 0.00 | 0.00 |
April | 31.61 | 0.32 | 31.28 | 15.35 | 41.61 | 0.00 | 0.00 | 0.00 |
May | 44.33 | 2.35 | 41.98 | 41.53 | 20.03 | 0.00 | 0.00 | 0.00 |
June | 49.54 | 5.51 | 44.03 | 56.63 | 13.11 | 0.00 | 0.00 | 0.00 |
July | 47.36 | 4.16 | 43.20 | 56.29 | 12.05 | 0.00 | 0.00 | 0.00 |
August | 35.96 | 0.68 | 35.28 | 38.90 | 14.60 | 0.00 | 0.00 | 0.00 |
September | 28.00 | 0.03 | 27.97 | 22.47 | 25.62 | 0.00 | 0.00 | 0.00 |
October | 19.41 | 0.00 | 19.41 | 7.48 | 42.17 | 0.00 | 0.00 | 0.00 |
November | 12.85 | 0.00 | 12.85 | 0.99 | 69.47 | 0.00 | 0.00 | 0.00 |
December | 10.77 | 0.00 | 10.77 | 0.00 | 112.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 28.05 | 1.09 | 26.96 | 20.49 | 52.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 10.77 | 0.00 | 10.77 | 0.00 | 12.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 49.54 | 5.51 | 44.03 | 56.63 | 117.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.14 | 61.43 | 26.71 | 73.25 | 92.55 | 0.00 | 0.00 | 0.00 |
February | 110.04 | 74.04 | 36.00 | 103.12 | 77.71 | 0.00 | 0.00 | 0.00 |
March | 96.73 | 60.88 | 35.85 | 93.67 | 63.61 | 0.00 | 0.00 | 0.00 |
April | 88.35 | 47.90 | 40.45 | 93.77 | 41.39 | 0.00 | 0.00 | 0.00 |
May | 75.63 | 26.68 | 48.94 | 88.78 | 22.01 | 0.00 | 0.00 | 0.00 |
June | 66.45 | 17.51 | 48.94 | 83.45 | 14.30 | 0.00 | 0.00 | 0.00 |
July | 73.11 | 23.27 | 49.85 | 95.46 | 12.98 | 0.00 | 0.00 | 0.00 |
August | 77.58 | 32.25 | 45.33 | 98.14 | 15.11 | 0.00 | 0.00 | 0.00 |
September | 81.83 | 42.81 | 39.02 | 95.33 | 25.31 | 0.00 | 0.00 | 0.00 |
October | 72.76 | 43.37 | 29.38 | 74.95 | 39.29 | 0.00 | 0.00 | 0.00 |
November | 63.55 | 39.85 | 23.70 | 56.54 | 59.47 | 0.00 | 0.00 | 0.00 |
December | 67.70 | 44.42 | 23.28 | 51.56 | 90.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 79.97 | 42.68 | 37.29 | 83.86 | 46.06 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 63.55 | 17.51 | 23.28 | 51.56 | 12.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 110.04 | 74.04 | 49.85 | 103.12 | 92.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 239.24 | 166.73 | 72.51 | 198.81 | 251.20 | 0.00 | 0.00 | 0.00 |
February | 298.68 | 200.96 | 97.72 | 279.89 | 210.92 | 0.00 | 0.00 | 0.00 |
March | 262.54 | 165.25 | 97.29 | 254.24 | 172.64 | 0.00 | 0.00 | 0.00 |
April | 239.80 | 130.01 | 109.79 | 254.52 | 112.35 | 0.00 | 0.00 | 0.00 |
May | 205.26 | 72.42 | 132.84 | 240.97 | 59.74 | 0.00 | 0.00 | 0.00 |
June | 180.36 | 47.52 | 132.84 | 226.50 | 38.82 | 0.00 | 0.00 | 0.00 |
July | 198.45 | 63.15 | 135.30 | 259.11 | 35.22 | 0.00 | 0.00 | 0.00 |
August | 210.57 | 87.54 | 123.03 | 266.37 | 41.01 | 0.00 | 0.00 | 0.00 |
September | 222.09 | 116.20 | 105.90 | 258.74 | 68.70 | 0.00 | 0.00 | 0.00 |
October | 197.48 | 117.73 | 79.75 | 203.42 | 106.65 | 0.00 | 0.00 | 0.00 |
November | 172.49 | 108.16 | 64.33 | 153.45 | 161.43 | 0.00 | 0.00 | 0.00 |
December | 183.76 | 120.57 | 63.19 | 139.94 | 245.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 217.05 | 115.83 | 101.21 | 227.62 | 125.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 172.49 | 47.52 | 63.19 | 139.94 | 35.22 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 298.68 | 200.96 | 135.30 | 279.89 | 251.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 188.91 | 131.66 | 57.25 | 158.20 | 193.10 | 0.00 | 0.00 | 0.00 |
February | 235.84 | 158.68 | 77.16 | 220.76 | 161.47 | 0.00 | 0.00 | 0.00 |
March | 207.31 | 130.48 | 76.82 | 199.70 | 132.21 | 0.00 | 0.00 | 0.00 |
April | 189.35 | 102.66 | 86.69 | 198.27 | 85.65 | 0.00 | 0.00 | 0.00 |
May | 162.08 | 57.18 | 104.90 | 187.10 | 43.43 | 0.00 | 0.00 | 0.00 |
June | 142.41 | 37.52 | 104.90 | 177.46 | 26.41 | 0.00 | 0.00 | 0.00 |
July | 156.70 | 49.86 | 106.84 | 203.74 | 22.76 | 0.00 | 0.00 | 0.00 |
August | 166.27 | 69.12 | 97.15 | 208.46 | 27.23 | 0.00 | 0.00 | 0.00 |
September | 175.37 | 91.75 | 83.62 | 202.16 | 49.71 | 0.00 | 0.00 | 0.00 |
October | 155.93 | 92.96 | 62.97 | 159.72 | 80.14 | 0.00 | 0.00 | 0.00 |
November | 136.20 | 85.41 | 50.80 | 121.77 | 121.47 | 0.00 | 0.00 | 0.00 |
December | 145.10 | 95.20 | 49.90 | 111.92 | 187.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 171.38 | 91.46 | 79.92 | 178.81 | 93.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 136.20 | 37.52 | 49.90 | 111.92 | 22.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 235.84 | 158.68 | 106.84 | 220.76 | 193.10 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 114.25 | 48.36 | 65.89 | 46.87 | 416.66 | 0.00 | 0.00 | 0.00 |
February | 184.83 | 84.82 | 100.00 | 116.08 | 335.36 | 0.00 | 0.00 | 0.00 |
March | 242.50 | 124.39 | 118.11 | 188.00 | 259.64 | 0.00 | 0.00 | 0.00 |
April | 309.48 | 157.00 | 152.48 | 290.61 | 156.81 | 0.00 | 0.00 | 0.00 |
May | 380.58 | 182.10 | 198.48 | 428.40 | 78.46 | 0.00 | 0.00 | 0.00 |
June | 365.65 | 157.92 | 207.72 | 441.46 | 48.27 | 0.00 | 0.00 | 0.00 |
July | 390.91 | 181.80 | 209.10 | 487.22 | 41.92 | 0.00 | 0.00 | 0.00 |
August | 320.89 | 145.42 | 175.47 | 386.54 | 50.34 | 0.00 | 0.00 | 0.00 |
September | 251.92 | 113.10 | 138.81 | 267.99 | 92.05 | 0.00 | 0.00 | 0.00 |
October | 159.31 | 64.11 | 95.20 | 131.14 | 154.82 | 0.00 | 0.00 | 0.00 |
November | 96.94 | 32.95 | 63.99 | 48.57 | 248.46 | 0.00 | 0.00 | 0.00 |
December | 85.45 | 29.60 | 55.84 | 25.57 | 403.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 242.21 | 110.28 | 131.92 | 238.95 | 189.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 85.45 | 29.60 | 55.84 | 25.57 | 41.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 390.91 | 182.10 | 209.10 | 487.22 | 416.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.24 | 0.00 | 27.24 | 0.21 | 240.46 | 0.00 | 0.00 | 0.00 |
February | 41.84 | 0.00 | 41.84 | 3.24 | 190.95 | 0.00 | 0.00 | 0.00 |
March | 51.48 | 0.00 | 51.48 | 9.18 | 145.88 | 0.00 | 0.00 | 0.00 |
April | 67.70 | 0.70 | 67.00 | 32.64 | 85.51 | 0.00 | 0.00 | 0.00 |
May | 94.95 | 5.04 | 89.91 | 84.86 | 40.90 | 0.00 | 0.00 | 0.00 |
June | 106.11 | 11.81 | 94.30 | 117.12 | 26.64 | 0.00 | 0.00 | 0.00 |
July | 101.44 | 8.91 | 92.54 | 117.09 | 23.93 | 0.00 | 0.00 | 0.00 |
August | 77.03 | 1.47 | 75.57 | 80.42 | 29.16 | 0.00 | 0.00 | 0.00 |
September | 59.98 | 0.06 | 59.91 | 47.38 | 51.36 | 0.00 | 0.00 | 0.00 |
October | 41.58 | 0.00 | 41.58 | 17.37 | 84.81 | 0.00 | 0.00 | 0.00 |
November | 27.53 | 0.00 | 27.53 | 2.75 | 138.75 | 0.00 | 0.00 | 0.00 |
December | 23.08 | 0.00 | 23.08 | 0.00 | 230.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 60.09 | 2.34 | 57.75 | 42.93 | 107.06 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 23.08 | 0.00 | 23.08 | 0.00 | 23.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 106.11 | 11.81 | 94.30 | 117.12 | 240.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 114.25 | 48.36 | 65.89 | 48.56 | 414.28 | 0.00 | 0.00 | 0.00 |
February | 184.83 | 84.82 | 100.00 | 120.57 | 332.07 | 0.00 | 0.00 | 0.00 |
March | 242.50 | 124.39 | 118.11 | 192.98 | 256.56 | 0.00 | 0.00 | 0.00 |
April | 309.48 | 157.00 | 152.48 | 294.64 | 155.84 | 0.00 | 0.00 | 0.00 |
May | 380.58 | 182.10 | 198.48 | 426.00 | 81.23 | 0.00 | 0.00 | 0.00 |
June | 365.65 | 157.92 | 207.72 | 435.39 | 52.44 | 0.00 | 0.00 | 0.00 |
July | 390.91 | 181.80 | 209.10 | 481.12 | 46.66 | 0.00 | 0.00 | 0.00 |
August | 320.89 | 145.42 | 175.47 | 383.15 | 55.50 | 0.00 | 0.00 | 0.00 |
September | 251.92 | 113.10 | 138.81 | 268.70 | 93.30 | 0.00 | 0.00 | 0.00 |
October | 159.31 | 64.11 | 95.20 | 134.48 | 153.31 | 0.00 | 0.00 | 0.00 |
November | 96.94 | 32.95 | 63.99 | 51.35 | 246.19 | 0.00 | 0.00 | 0.00 |
December | 85.45 | 29.60 | 55.84 | 26.61 | 401.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 242.21 | 110.28 | 131.92 | 239.34 | 190.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 85.45 | 29.60 | 55.84 | 26.61 | 46.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 390.91 | 182.10 | 209.10 | 481.12 | 414.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 277.05 | 193.09 | 83.97 | 224.39 | 290.29 | 0.00 | 0.00 | 0.00 |
February | 345.89 | 232.72 | 113.16 | 315.63 | 243.31 | 0.00 | 0.00 | 0.00 |
March | 304.04 | 191.37 | 112.67 | 287.21 | 198.44 | 0.00 | 0.00 | 0.00 |
April | 277.70 | 150.56 | 127.14 | 287.78 | 127.05 | 0.00 | 0.00 | 0.00 |
May | 237.70 | 83.86 | 153.84 | 275.48 | 62.72 | 0.00 | 0.00 | 0.00 |
June | 208.87 | 55.03 | 153.84 | 262.41 | 37.79 | 0.00 | 0.00 | 0.00 |
July | 229.81 | 73.13 | 156.68 | 301.38 | 32.05 | 0.00 | 0.00 | 0.00 |
August | 243.85 | 101.38 | 142.48 | 306.76 | 39.12 | 0.00 | 0.00 | 0.00 |
September | 257.19 | 134.56 | 122.63 | 294.94 | 73.38 | 0.00 | 0.00 | 0.00 |
October | 228.69 | 136.33 | 92.36 | 230.53 | 120.81 | 0.00 | 0.00 | 0.00 |
November | 199.75 | 125.26 | 74.50 | 173.45 | 183.83 | 0.00 | 0.00 | 0.00 |
December | 212.80 | 139.62 | 73.18 | 158.41 | 281.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 251.35 | 134.14 | 117.21 | 259.46 | 140.39 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 199.75 | 55.03 | 73.18 | 158.41 | 32.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 345.89 | 232.72 | 156.68 | 315.63 | 290.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 190.65 | 0.00 | 190.65 | 0.32 | 1796.84 | 0.00 | 0.00 | 0.00 |
February | 292.85 | 0.00 | 292.85 | 11.70 | 1475.35 | 0.00 | 0.00 | 0.00 |
March | 360.38 | 0.01 | 360.37 | 43.50 | 1150.89 | 0.00 | 0.00 | 0.00 |
April | 473.88 | 4.87 | 469.02 | 198.39 | 688.22 | 0.00 | 0.00 | 0.00 |
May | 664.60 | 35.26 | 629.34 | 583.13 | 321.69 | 0.00 | 0.00 | 0.00 |
June | 742.73 | 82.63 | 660.10 | 814.81 | 209.08 | 0.00 | 0.00 | 0.00 |
July | 710.09 | 62.33 | 647.75 | 824.19 | 183.92 | 0.00 | 0.00 | 0.00 |
August | 539.20 | 10.26 | 528.94 | 558.53 | 231.01 | 0.00 | 0.00 | 0.00 |
September | 419.81 | 0.43 | 419.38 | 308.05 | 418.32 | 0.00 | 0.00 | 0.00 |
October | 291.02 | 0.00 | 291.02 | 89.71 | 707.59 | 0.00 | 0.00 | 0.00 |
November | 192.69 | 0.00 | 192.69 | 9.97 | 1142.12 | 0.00 | 0.00 | 0.00 |
December | 161.53 | 0.00 | 161.53 | 0.00 | 1750.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 420.59 | 16.39 | 404.20 | 288.62 | 836.85 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 161.53 | 0.00 | 161.53 | 0.00 | 183.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 742.73 | 82.63 | 660.10 | 824.19 | 1796.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 190.65 | 0.00 | 190.65 | 0.23 | 1826.00 | 0.00 | 0.00 | 0.00 |
February | 292.85 | 0.00 | 292.85 | 9.85 | 1503.85 | 0.00 | 0.00 | 0.00 |
March | 360.38 | 0.01 | 360.37 | 39.35 | 1175.55 | 0.00 | 0.00 | 0.00 |
April | 473.88 | 4.87 | 469.02 | 189.14 | 703.23 | 0.00 | 0.00 | 0.00 |
May | 664.60 | 35.26 | 629.34 | 573.37 | 328.12 | 0.00 | 0.00 | 0.00 |
June | 742.73 | 82.63 | 660.10 | 805.81 | 213.99 | 0.00 | 0.00 | 0.00 |
July | 710.09 | 62.33 | 647.75 | 816.56 | 188.28 | 0.00 | 0.00 | 0.00 |
August | 539.20 | 10.26 | 528.94 | 550.68 | 237.19 | 0.00 | 0.00 | 0.00 |
September | 419.81 | 0.43 | 419.38 | 299.61 | 428.02 | 0.00 | 0.00 | 0.00 |
October | 291.02 | 0.00 | 291.02 | 83.08 | 724.98 | 0.00 | 0.00 | 0.00 |
November | 192.69 | 0.00 | 192.69 | 8.77 | 1170.66 | 0.00 | 0.00 | 0.00 |
December | 161.53 | 0.00 | 161.53 | 0.00 | 1779.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 420.59 | 16.39 | 404.20 | 283.12 | 853.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 161.53 | 0.00 | 161.53 | 0.00 | 188.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 742.73 | 82.63 | 660.10 | 816.56 | 1826.00 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.24 | 0.00 | 27.24 | 0.50 | 222.67 | 0.00 | 0.00 | 0.00 |
February | 41.84 | 0.00 | 41.84 | 4.52 | 181.75 | 0.00 | 0.00 | 0.00 |
March | 51.48 | 0.00 | 51.48 | 12.92 | 140.07 | 0.00 | 0.00 | 0.00 |
April | 67.70 | 0.70 | 67.00 | 45.05 | 84.49 | 0.00 | 0.00 | 0.00 |
May | 94.95 | 5.04 | 89.91 | 113.65 | 41.56 | 0.00 | 0.00 | 0.00 |
June | 106.11 | 11.81 | 94.30 | 149.24 | 27.76 | 0.00 | 0.00 | 0.00 |
July | 101.44 | 8.91 | 92.54 | 151.46 | 23.97 | 0.00 | 0.00 | 0.00 |
August | 77.03 | 1.47 | 75.57 | 109.99 | 27.99 | 0.00 | 0.00 | 0.00 |
September | 59.98 | 0.06 | 59.91 | 66.74 | 48.83 | 0.00 | 0.00 | 0.00 |
October | 41.58 | 0.00 | 41.58 | 25.80 | 81.26 | 0.00 | 0.00 | 0.00 |
November | 27.53 | 0.00 | 27.53 | 4.66 | 134.81 | 0.00 | 0.00 | 0.00 |
December | 23.08 | 0.00 | 23.08 | 0.06 | 215.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 60.09 | 2.34 | 57.75 | 57.38 | 102.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 23.08 | 0.00 | 23.08 | 0.06 | 23.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 106.11 | 11.81 | 94.30 | 151.46 | 222.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 222.34 | 92.18 | 130.15 | 96.47 | 761.39 | 0.00 | 0.00 | 0.00 |
February | 353.32 | 151.95 | 201.37 | 221.57 | 614.99 | 0.00 | 0.00 | 0.00 |
March | 480.26 | 241.44 | 238.82 | 390.06 | 482.23 | 0.00 | 0.00 | 0.00 |
April | 661.43 | 356.59 | 304.84 | 694.37 | 301.22 | 0.00 | 0.00 | 0.00 |
May | 718.37 | 316.83 | 401.53 | 898.80 | 155.43 | 0.00 | 0.00 | 0.00 |
June | 810.58 | 387.70 | 422.89 | 1093.38 | 104.27 | 0.00 | 0.00 | 0.00 |
July | 795.75 | 374.36 | 421.39 | 1107.98 | 89.78 | 0.00 | 0.00 | 0.00 |
August | 612.52 | 267.68 | 344.83 | 837.67 | 104.67 | 0.00 | 0.00 | 0.00 |
September | 491.82 | 220.68 | 271.14 | 600.65 | 178.44 | 0.00 | 0.00 | 0.00 |
October | 296.11 | 111.34 | 184.77 | 274.22 | 291.83 | 0.00 | 0.00 | 0.00 |
November | 189.68 | 63.17 | 126.51 | 103.97 | 471.17 | 0.00 | 0.00 | 0.00 |
December | 174.39 | 65.46 | 108.93 | 60.74 | 746.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 484.36 | 220.95 | 263.40 | 533.20 | 357.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 174.39 | 63.17 | 108.93 | 60.74 | 89.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 810.58 | 387.70 | 422.89 | 1107.98 | 761.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 188.91 | 131.66 | 57.25 | 166.90 | 180.26 | 0.00 | 0.00 | 0.00 |
February | 235.84 | 158.68 | 77.16 | 231.17 | 154.92 | 0.00 | 0.00 | 0.00 |
March | 207.31 | 130.48 | 76.82 | 211.57 | 127.90 | 0.00 | 0.00 | 0.00 |
April | 189.35 | 102.66 | 86.69 | 215.50 | 84.23 | 0.00 | 0.00 | 0.00 |
May | 162.08 | 57.18 | 104.90 | 214.42 | 44.31 | 0.00 | 0.00 | 0.00 |
June | 142.41 | 37.52 | 104.90 | 206.02 | 29.27 | 0.00 | 0.00 | 0.00 |
July | 156.70 | 49.86 | 106.84 | 234.91 | 24.98 | 0.00 | 0.00 | 0.00 |
August | 166.27 | 69.12 | 97.15 | 236.59 | 28.49 | 0.00 | 0.00 | 0.00 |
September | 175.37 | 91.75 | 83.62 | 224.41 | 48.66 | 0.00 | 0.00 | 0.00 |
October | 155.93 | 92.96 | 62.97 | 173.94 | 77.81 | 0.00 | 0.00 | 0.00 |
November | 136.20 | 85.41 | 50.80 | 129.25 | 118.94 | 0.00 | 0.00 | 0.00 |
December | 145.10 | 95.20 | 49.90 | 118.43 | 176.87 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 171.38 | 91.46 | 79.92 | 196.68 | 91.10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 136.20 | 37.52 | 49.90 | 118.43 | 24.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 235.84 | 158.68 | 106.84 | 236.59 | 180.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.49 | 0.00 | 34.49 | 0.08 | 318.94 | 0.00 | 0.00 | 0.00 |
February | 52.98 | 0.00 | 52.98 | 2.53 | 257.42 | 0.00 | 0.00 | 0.00 |
March | 65.20 | 0.00 | 65.20 | 8.99 | 196.41 | 0.00 | 0.00 | 0.00 |
April | 85.74 | 0.88 | 84.86 | 39.33 | 114.10 | 0.00 | 0.00 | 0.00 |
May | 120.24 | 6.38 | 113.86 | 108.95 | 55.19 | 0.00 | 0.00 | 0.00 |
June | 134.38 | 14.95 | 119.43 | 149.67 | 36.39 | 0.00 | 0.00 | 0.00 |
July | 128.47 | 11.28 | 117.20 | 149.21 | 33.39 | 0.00 | 0.00 | 0.00 |
August | 97.56 | 1.86 | 95.70 | 102.28 | 40.64 | 0.00 | 0.00 | 0.00 |
September | 75.96 | 0.08 | 75.88 | 58.56 | 70.29 | 0.00 | 0.00 | 0.00 |
October | 52.65 | 0.00 | 52.65 | 18.64 | 116.38 | 0.00 | 0.00 | 0.00 |
November | 34.86 | 0.00 | 34.86 | 2.39 | 191.88 | 0.00 | 0.00 | 0.00 |
December | 29.23 | 0.00 | 29.23 | 0.00 | 308.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 76.10 | 2.97 | 73.13 | 53.70 | 144.48 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.23 | 0.00 | 29.23 | 0.00 | 33.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 134.38 | 14.95 | 119.43 | 149.67 | 318.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.86 | 0.00 | 30.86 | 0.07 | 285.31 | 0.00 | 0.00 | 0.00 |
February | 47.40 | 0.00 | 47.40 | 2.26 | 230.31 | 0.00 | 0.00 | 0.00 |
March | 58.34 | 0.00 | 58.33 | 8.04 | 175.73 | 0.00 | 0.00 | 0.00 |
April | 76.71 | 0.79 | 75.92 | 35.19 | 102.09 | 0.00 | 0.00 | 0.00 |
May | 107.58 | 5.71 | 101.88 | 97.47 | 49.38 | 0.00 | 0.00 | 0.00 |
June | 120.23 | 13.38 | 106.85 | 133.91 | 32.56 | 0.00 | 0.00 | 0.00 |
July | 114.95 | 10.09 | 104.86 | 133.50 | 29.87 | 0.00 | 0.00 | 0.00 |
August | 87.28 | 1.66 | 85.62 | 91.51 | 36.36 | 0.00 | 0.00 | 0.00 |
September | 67.96 | 0.07 | 67.89 | 52.39 | 62.89 | 0.00 | 0.00 | 0.00 |
October | 47.11 | 0.00 | 47.11 | 16.67 | 104.13 | 0.00 | 0.00 | 0.00 |
November | 31.19 | 0.00 | 31.19 | 2.14 | 171.67 | 0.00 | 0.00 | 0.00 |
December | 26.15 | 0.00 | 26.15 | 0.00 | 275.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 68.08 | 2.65 | 65.43 | 48.05 | 129.26 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 26.15 | 0.00 | 26.15 | 0.00 | 29.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 120.23 | 13.38 | 106.85 | 133.91 | 285.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 705.25 | 491.51 | 213.74 | 582.14 | 741.63 | 0.00 | 0.00 | 0.00 |
February | 880.48 | 592.41 | 288.06 | 816.31 | 626.11 | 0.00 | 0.00 | 0.00 |
March | 773.94 | 487.14 | 286.81 | 741.03 | 514.43 | 0.00 | 0.00 | 0.00 |
April | 706.89 | 383.25 | 323.64 | 740.74 | 334.40 | 0.00 | 0.00 | 0.00 |
May | 605.09 | 213.48 | 391.61 | 698.24 | 179.17 | 0.00 | 0.00 | 0.00 |
June | 531.68 | 140.07 | 391.60 | 655.17 | 117.46 | 0.00 | 0.00 | 0.00 |
July | 585.00 | 186.15 | 398.85 | 752.15 | 106.17 | 0.00 | 0.00 | 0.00 |
August | 620.74 | 258.06 | 362.68 | 773.53 | 124.40 | 0.00 | 0.00 | 0.00 |
September | 654.70 | 342.53 | 312.17 | 753.14 | 205.20 | 0.00 | 0.00 | 0.00 |
October | 582.15 | 347.05 | 235.10 | 591.59 | 319.54 | 0.00 | 0.00 | 0.00 |
November | 508.49 | 318.84 | 189.64 | 446.03 | 483.46 | 0.00 | 0.00 | 0.00 |
December | 541.69 | 355.41 | 186.27 | 408.84 | 729.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 639.82 | 341.46 | 298.37 | 662.14 | 372.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 508.49 | 140.07 | 186.27 | 408.84 | 106.17 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 880.48 | 592.41 | 398.85 | 816.31 | 741.63 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.255906E+10 | 0.178349E+10 | 0.775570E+09 | 0.214901E+10 | 0.246564E+10 |
February | 0.288571E+10 | 0.194160E+10 | 0.944108E+09 | 0.270159E+10 | 0.190848E+10 |
March | 0.280832E+10 | 0.176763E+10 | 0.104070E+10 | 0.269418E+10 | 0.174914E+10 |
April | 0.248228E+10 | 0.134581E+10 | 0.113646E+10 | 0.260168E+10 | 0.110328E+10 |
May | 0.219561E+10 | 0.774627E+09 | 0.142098E+10 | 0.255396E+10 | 0.592137E+09 |
June | 0.186699E+10 | 0.491871E+09 | 0.137512E+10 | 0.233050E+10 | 0.363643E+09 |
July | 0.212271E+10 | 0.675472E+09 | 0.144724E+10 | 0.274840E+10 | 0.343252E+09 |
August | 0.225239E+10 | 0.936387E+09 | 0.131600E+10 | 0.282132E+10 | 0.403936E+09 |
September | 0.229900E+10 | 0.120281E+10 | 0.109620E+10 | 0.265167E+10 | 0.661053E+09 |
October | 0.211236E+10 | 0.125929E+10 | 0.853077E+09 | 0.215010E+10 | 0.108886E+10 |
November | 0.178557E+10 | 0.111964E+10 | 0.665932E+09 | 0.158430E+10 | 0.157254E+10 |
December | 0.196556E+10 | 0.128965E+10 | 0.675911E+09 | 0.152154E+10 | 0.240879E+10 |
Annual Sum or Average | 0.273356E+11 | 0.145883E+11 | 0.127473E+11 | 0.285082E+11 | 0.146607E+11 |
Minimum of Months | 0.178557E+10 | 0.491871E+09 | 0.665932E+09 | 0.152154E+10 | 0.343252E+09 |
Maximum of Months | 0.288571E+10 | 0.194160E+10 | 0.144724E+10 | 0.282132E+10 | 0.246564E+10 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.720613E+10 | 0.502218E+10 | 0.218395E+10 | 0.600776E+10 | 0.699964E+10 |
February | 0.812596E+10 | 0.546742E+10 | 0.265854E+10 | 0.755080E+10 | 0.543887E+10 |
March | 0.790805E+10 | 0.497752E+10 | 0.293053E+10 | 0.752410E+10 | 0.503407E+10 |
April | 0.698993E+10 | 0.378972E+10 | 0.320021E+10 | 0.725468E+10 | 0.324147E+10 |
May | 0.618268E+10 | 0.218130E+10 | 0.400138E+10 | 0.709448E+10 | 0.179867E+10 |
June | 0.525733E+10 | 0.138508E+10 | 0.387226E+10 | 0.645542E+10 | 0.113670E+10 |
July | 0.597742E+10 | 0.190208E+10 | 0.407534E+10 | 0.764832E+10 | 0.106127E+10 |
August | 0.634258E+10 | 0.263680E+10 | 0.370578E+10 | 0.785792E+10 | 0.126477E+10 |
September | 0.647384E+10 | 0.338702E+10 | 0.308682E+10 | 0.738715E+10 | 0.201866E+10 |
October | 0.594828E+10 | 0.354607E+10 | 0.240221E+10 | 0.599374E+10 | 0.320778E+10 |
November | 0.502804E+10 | 0.315282E+10 | 0.187522E+10 | 0.441555E+10 | 0.451776E+10 |
December | 0.553489E+10 | 0.363157E+10 | 0.190332E+10 | 0.424633E+10 | 0.683391E+10 |
Annual Sum or Average | 0.769751E+11 | 0.410796E+11 | 0.358956E+11 | 0.794363E+11 | 0.425536E+11 |
Minimum of Months | 0.502804E+10 | 0.138508E+10 | 0.187522E+10 | 0.424633E+10 | 0.106127E+10 |
Maximum of Months | 0.812596E+10 | 0.546742E+10 | 0.407534E+10 | 0.785792E+10 | 0.699964E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.936118E+10 | 0.652410E+10 | 0.283708E+10 | 0.789850E+10 | 0.944816E+10 |
February | 0.105561E+11 | 0.710249E+10 | 0.345360E+10 | 0.995999E+10 | 0.733674E+10 |
March | 0.102730E+11 | 0.646608E+10 | 0.380693E+10 | 0.993238E+10 | 0.680782E+10 |
April | 0.908032E+10 | 0.492306E+10 | 0.415725E+10 | 0.956973E+10 | 0.442127E+10 |
May | 0.803166E+10 | 0.283363E+10 | 0.519802E+10 | 0.934866E+10 | 0.246170E+10 |
June | 0.682958E+10 | 0.179929E+10 | 0.503028E+10 | 0.850252E+10 | 0.156577E+10 |
July | 0.776501E+10 | 0.247092E+10 | 0.529410E+10 | 0.100903E+11 | 0.143761E+10 |
August | 0.823937E+10 | 0.342536E+10 | 0.481402E+10 | 0.103527E+11 | 0.171700E+10 |
September | 0.840988E+10 | 0.439993E+10 | 0.400995E+10 | 0.971041E+10 | 0.277387E+10 |
October | 0.772715E+10 | 0.460654E+10 | 0.312061E+10 | 0.785557E+10 | 0.442395E+10 |
November | 0.653171E+10 | 0.409570E+10 | 0.243602E+10 | 0.579409E+10 | 0.620100E+10 |
December | 0.719013E+10 | 0.471761E+10 | 0.247252E+10 | 0.556281E+10 | 0.927880E+10 |
Annual Sum or Average | 0.999951E+11 | 0.533647E+11 | 0.466304E+11 | 0.104578E+12 | 0.578737E+11 |
Minimum of Months | 0.653171E+10 | 0.179929E+10 | 0.243602E+10 | 0.556281E+10 | 0.143761E+10 |
Maximum of Months | 0.105561E+11 | 0.710249E+10 | 0.529410E+10 | 0.103527E+11 | 0.944816E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.505970E+09 | 0.352626E+09 | 0.153344E+09 | 0.424723E+09 | 0.516307E+09 |
February | 0.570555E+09 | 0.383888E+09 | 0.186667E+09 | 0.535580E+09 | 0.390713E+09 |
March | 0.555255E+09 | 0.349490E+09 | 0.205765E+09 | 0.535974E+09 | 0.354634E+09 |
April | 0.490791E+09 | 0.266090E+09 | 0.224701E+09 | 0.515732E+09 | 0.222820E+09 |
May | 0.434112E+09 | 0.153157E+09 | 0.280955E+09 | 0.504042E+09 | 0.116948E+09 |
June | 0.369140E+09 | 97251340.98 | 0.271888E+09 | 0.462363E+09 | 69262026.72 |
July | 0.419700E+09 | 0.133552E+09 | 0.286148E+09 | 0.548217E+09 | 61945956.82 |
August | 0.445338E+09 | 0.185140E+09 | 0.260199E+09 | 0.560974E+09 | 73904804.71 |
September | 0.454554E+09 | 0.237815E+09 | 0.216738E+09 | 0.526065E+09 | 0.129846E+09 |
October | 0.417652E+09 | 0.248983E+09 | 0.168669E+09 | 0.428384E+09 | 0.216271E+09 |
November | 0.353038E+09 | 0.221371E+09 | 0.131667E+09 | 0.315933E+09 | 0.316012E+09 |
December | 0.388625E+09 | 0.254986E+09 | 0.133640E+09 | 0.300653E+09 | 0.500610E+09 |
Annual Sum or Average | 0.540473E+10 | 0.288435E+10 | 0.252038E+10 | 0.565864E+10 | 0.296927E+10 |
Minimum of Months | 0.353038E+09 | 97251340.98 | 0.131667E+09 | 0.300653E+09 | 61945956.82 |
Maximum of Months | 0.570555E+09 | 0.383888E+09 | 0.286148E+09 | 0.560974E+09 | 0.516307E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.306009E+09 | 0.129524E+09 | 0.176485E+09 | 0.125979E+09 | 0.111356E+10 |
February | 0.447137E+09 | 0.205208E+09 | 0.241929E+09 | 0.281870E+09 | 0.811042E+09 |
March | 0.649507E+09 | 0.333167E+09 | 0.316340E+09 | 0.505262E+09 | 0.696641E+09 |
April | 0.802168E+09 | 0.406948E+09 | 0.395220E+09 | 0.756971E+09 | 0.408329E+09 |
May | 0.101935E+10 | 0.487740E+09 | 0.531607E+09 | 0.115321E+10 | 0.211650E+09 |
June | 0.947760E+09 | 0.409340E+09 | 0.538420E+09 | 0.114927E+10 | 0.126763E+09 |
July | 0.104701E+10 | 0.486944E+09 | 0.560065E+09 | 0.131046E+10 | 0.114215E+09 |
August | 0.859479E+09 | 0.389498E+09 | 0.469981E+09 | 0.103981E+10 | 0.136755E+09 |
September | 0.652966E+09 | 0.293158E+09 | 0.359808E+09 | 0.697738E+09 | 0.240850E+09 |
October | 0.426698E+09 | 0.171705E+09 | 0.254993E+09 | 0.351722E+09 | 0.418043E+09 |
November | 0.251269E+09 | 85417046.86 | 0.165852E+09 | 0.125436E+09 | 0.646261E+09 |
December | 0.228859E+09 | 79291862.18 | 0.149567E+09 | 68741710.21 | 0.107665E+10 |
Annual Sum or Average | 0.763821E+10 | 0.347794E+10 | 0.416027E+10 | 0.756648E+10 | 0.600075E+10 |
Minimum of Months | 0.228859E+09 | 79291862.18 | 0.149567E+09 | 68741710.21 | 0.114215E+09 |
Maximum of Months | 0.104701E+10 | 0.487740E+09 | 0.560065E+09 | 0.131046E+10 | 0.111356E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 72949479.92 | 0.00 | 72949479.92 | 556752.37 | 0.643038E+09 |
February | 0.101212E+09 | 0.00 | 0.101212E+09 | 7605538.67 | 0.461838E+09 |
March | 0.137897E+09 | 5272.04 | 0.137892E+09 | 24353704.11 | 0.391055E+09 |
April | 0.175479E+09 | 1802380.52 | 0.173676E+09 | 84621841.30 | 0.222117E+09 |
May | 0.254305E+09 | 13491232.00 | 0.240813E+09 | 0.230096E+09 | 0.109065E+09 |
June | 0.275033E+09 | 30599089.35 | 0.244433E+09 | 0.306438E+09 | 68477251.24 |
July | 0.271710E+09 | 23851214.90 | 0.247859E+09 | 0.316044E+09 | 63582916.61 |
August | 0.206320E+09 | 3925180.00 | 0.202395E+09 | 0.217191E+09 | 77457808.62 |
September | 0.155457E+09 | 160463.95 | 0.155296E+09 | 0.123067E+09 | 0.133470E+09 |
October | 0.111358E+09 | 0.00 | 0.111358E+09 | 45629768.61 | 0.229175E+09 |
November | 71354840.64 | 0.00 | 71354840.64 | 6793923.44 | 0.361445E+09 |
December | 61808589.18 | 0.00 | 61808589.18 | 3139.45 | 0.615711E+09 |
Annual Sum or Average | 0.189488E+10 | 73834832.75 | 0.182105E+10 | 0.136240E+10 | 0.337643E+10 |
Minimum of Months | 61808589.18 | 0.00 | 61808589.18 | 3139.45 | 63582916.61 |
Maximum of Months | 0.275033E+09 | 30599089.35 | 0.247859E+09 | 0.316044E+09 | 0.643038E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.306009E+09 | 0.129524E+09 | 0.176485E+09 | 0.130878E+09 | 0.110683E+10 |
February | 0.447137E+09 | 0.205208E+09 | 0.241929E+09 | 0.292687E+09 | 0.802521E+09 |
March | 0.649507E+09 | 0.333167E+09 | 0.316340E+09 | 0.518107E+09 | 0.688251E+09 |
April | 0.802168E+09 | 0.406948E+09 | 0.395220E+09 | 0.766772E+09 | 0.405631E+09 |
May | 0.101935E+10 | 0.487740E+09 | 0.531607E+09 | 0.114830E+10 | 0.217103E+09 |
June | 0.947760E+09 | 0.409340E+09 | 0.538420E+09 | 0.113585E+10 | 0.135086E+09 |
July | 0.104701E+10 | 0.486944E+09 | 0.560065E+09 | 0.129597E+10 | 0.124364E+09 |
August | 0.859479E+09 | 0.389498E+09 | 0.469981E+09 | 0.103232E+10 | 0.147637E+09 |
September | 0.652966E+09 | 0.293158E+09 | 0.359808E+09 | 0.699630E+09 | 0.243076E+09 |
October | 0.426698E+09 | 0.171705E+09 | 0.254993E+09 | 0.359691E+09 | 0.414272E+09 |
November | 0.251269E+09 | 85417046.86 | 0.165852E+09 | 0.132398E+09 | 0.640137E+09 |
December | 0.228859E+09 | 79291862.18 | 0.149567E+09 | 71815960.89 | 0.107211E+10 |
Annual Sum or Average | 0.763821E+10 | 0.347794E+10 | 0.416027E+10 | 0.758443E+10 | 0.599701E+10 |
Minimum of Months | 0.228859E+09 | 79291862.18 | 0.149567E+09 | 71815960.89 | 0.124364E+09 |
Maximum of Months | 0.104701E+10 | 0.487740E+09 | 0.560065E+09 | 0.129597E+10 | 0.110683E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.404696E+09 | 0.282045E+09 | 0.122651E+09 | 0.344774E+09 | 0.382911E+09 |
February | 0.456353E+09 | 0.307049E+09 | 0.149304E+09 | 0.422724E+09 | 0.316870E+09 |
March | 0.444116E+09 | 0.279536E+09 | 0.164579E+09 | 0.412062E+09 | 0.320373E+09 |
April | 0.392555E+09 | 0.212830E+09 | 0.179725E+09 | 0.387098E+09 | 0.229373E+09 |
May | 0.347220E+09 | 0.122501E+09 | 0.224719E+09 | 0.372615E+09 | 0.134768E+09 |
June | 0.295253E+09 | 77785603.32 | 0.217467E+09 | 0.336424E+09 | 90373954.23 |
July | 0.335693E+09 | 0.106821E+09 | 0.228873E+09 | 0.405773E+09 | 83797312.91 |
August | 0.356200E+09 | 0.148082E+09 | 0.208118E+09 | 0.418674E+09 | 0.100341E+09 |
September | 0.363571E+09 | 0.190214E+09 | 0.173356E+09 | 0.392968E+09 | 0.151942E+09 |
October | 0.334055E+09 | 0.199146E+09 | 0.134908E+09 | 0.317527E+09 | 0.228679E+09 |
November | 0.282374E+09 | 0.177062E+09 | 0.105312E+09 | 0.240911E+09 | 0.280749E+09 |
December | 0.310839E+09 | 0.203948E+09 | 0.106891E+09 | 0.248499E+09 | 0.357915E+09 |
Annual Sum or Average | 0.432292E+10 | 0.230702E+10 | 0.201590E+10 | 0.430005E+10 | 0.267809E+10 |
Minimum of Months | 0.282374E+09 | 77785603.32 | 0.105312E+09 | 0.240911E+09 | 83797312.91 |
Maximum of Months | 0.456353E+09 | 0.307049E+09 | 0.228873E+09 | 0.422724E+09 | 0.382911E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 58367319.83 | 0.00 | 58367319.83 | 266634.48 | 0.529365E+09 |
February | 80980322.72 | 0.00 | 80980322.72 | 5301061.09 | 0.379936E+09 |
March | 0.110332E+09 | 4218.19 | 0.110328E+09 | 18690853.65 | 0.319329E+09 |
April | 0.140402E+09 | 1442095.54 | 0.138960E+09 | 70752039.02 | 0.178510E+09 |
May | 0.203471E+09 | 10794416.27 | 0.192676E+09 | 0.195210E+09 | 84352104.66 |
June | 0.220055E+09 | 24482516.34 | 0.195573E+09 | 0.256829E+09 | 51771251.54 |
July | 0.217397E+09 | 19083501.21 | 0.198313E+09 | 0.266645E+09 | 46370930.32 |
August | 0.165078E+09 | 3140560.24 | 0.161937E+09 | 0.184597E+09 | 57588718.29 |
September | 0.124382E+09 | 128388.17 | 0.124253E+09 | 0.103673E+09 | 0.104088E+09 |
October | 89098491.50 | 0.00 | 89098491.50 | 35609916.67 | 0.188032E+09 |
November | 57091439.30 | 0.00 | 57091439.30 | 4588572.98 | 0.301372E+09 |
December | 49453425.81 | 0.00 | 49453425.81 | 0.00 | 0.508360E+09 |
Annual Sum or Average | 0.151611E+10 | 59075695.98 | 0.145703E+10 | 0.114216E+10 | 0.274907E+10 |
Minimum of Months | 49453425.81 | 0.00 | 49453425.81 | 0.00 | 46370930.32 |
Maximum of Months | 0.220055E+09 | 24482516.34 | 0.198313E+09 | 0.266645E+09 | 0.529365E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.297774E+09 | 0.123462E+09 | 0.174311E+09 | 0.107024E+09 | 0.109906E+10 |
February | 0.427402E+09 | 0.183814E+09 | 0.243589E+09 | 0.238648E+09 | 0.785504E+09 |
March | 0.643204E+09 | 0.323358E+09 | 0.319845E+09 | 0.474494E+09 | 0.674600E+09 |
April | 0.857276E+09 | 0.462179E+09 | 0.395098E+09 | 0.812149E+09 | 0.391973E+09 |
May | 0.962106E+09 | 0.424335E+09 | 0.537771E+09 | 0.106818E+10 | 0.197814E+09 |
June | 0.105059E+10 | 0.502492E+09 | 0.548099E+09 | 0.127681E+10 | 0.120987E+09 |
July | 0.106574E+10 | 0.501379E+09 | 0.564361E+09 | 0.132779E+10 | 0.107805E+09 |
August | 0.820339E+09 | 0.358507E+09 | 0.461832E+09 | 0.982115E+09 | 0.131676E+09 |
September | 0.637450E+09 | 0.286023E+09 | 0.351427E+09 | 0.671248E+09 | 0.232925E+09 |
October | 0.396582E+09 | 0.149118E+09 | 0.247464E+09 | 0.303725E+09 | 0.407469E+09 |
November | 0.245847E+09 | 81876671.53 | 0.163970E+09 | 0.111774E+09 | 0.635463E+09 |
December | 0.233566E+09 | 87671849.66 | 0.145894E+09 | 67091999.17 | 0.106571E+10 |
Annual Sum or Average | 0.763788E+10 | 0.348422E+10 | 0.415366E+10 | 0.744105E+10 | 0.585099E+10 |
Minimum of Months | 0.233566E+09 | 81876671.53 | 0.145894E+09 | 67091999.17 | 0.107805E+09 |
Maximum of Months | 0.106574E+10 | 0.502492E+09 | 0.564361E+09 | 0.132779E+10 | 0.109906E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.505970E+09 | 0.352626E+09 | 0.153344E+09 | 0.424280E+09 | 0.515681E+09 |
February | 0.570555E+09 | 0.383888E+09 | 0.186667E+09 | 0.534465E+09 | 0.389857E+09 |
March | 0.555255E+09 | 0.349490E+09 | 0.205765E+09 | 0.532947E+09 | 0.353410E+09 |
April | 0.490791E+09 | 0.266090E+09 | 0.224701E+09 | 0.511921E+09 | 0.221823E+09 |
May | 0.434112E+09 | 0.153157E+09 | 0.280955E+09 | 0.502706E+09 | 0.115542E+09 |
June | 0.369140E+09 | 97251340.98 | 0.271888E+09 | 0.459222E+09 | 68328985.88 |
July | 0.419700E+09 | 0.133552E+09 | 0.286148E+09 | 0.546385E+09 | 60492787.71 |
August | 0.445338E+09 | 0.185140E+09 | 0.260199E+09 | 0.560124E+09 | 72791633.33 |
September | 0.454554E+09 | 0.237815E+09 | 0.216738E+09 | 0.524843E+09 | 0.128613E+09 |
October | 0.417652E+09 | 0.248983E+09 | 0.168669E+09 | 0.427737E+09 | 0.215275E+09 |
November | 0.353038E+09 | 0.221371E+09 | 0.131667E+09 | 0.315591E+09 | 0.315531E+09 |
December | 0.388625E+09 | 0.254986E+09 | 0.133640E+09 | 0.300214E+09 | 0.500266E+09 |
Annual Sum or Average | 0.540473E+10 | 0.288435E+10 | 0.252038E+10 | 0.564043E+10 | 0.295761E+10 |
Minimum of Months | 0.353038E+09 | 97251340.98 | 0.131667E+09 | 0.300214E+09 | 60492787.71 |
Maximum of Months | 0.570555E+09 | 0.383888E+09 | 0.286148E+09 | 0.560124E+09 | 0.515681E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 72949479.92 | 0.00 | 72949479.92 | 547116.19 | 0.642813E+09 |
February | 0.101212E+09 | 0.00 | 0.101212E+09 | 7203734.09 | 0.461539E+09 |
March | 0.137897E+09 | 5272.04 | 0.137892E+09 | 22492618.29 | 0.390846E+09 |
April | 0.175479E+09 | 1802380.52 | 0.173676E+09 | 81278802.35 | 0.221814E+09 |
May | 0.254305E+09 | 13491232.00 | 0.240813E+09 | 0.230779E+09 | 0.106923E+09 |
June | 0.275033E+09 | 30599089.35 | 0.244433E+09 | 0.304097E+09 | 66592437.32 |
July | 0.271710E+09 | 23851214.90 | 0.247859E+09 | 0.314209E+09 | 61141830.42 |
August | 0.206320E+09 | 3925180.00 | 0.202395E+09 | 0.217349E+09 | 74591156.73 |
September | 0.155457E+09 | 160463.95 | 0.155296E+09 | 0.122239E+09 | 0.130673E+09 |
October | 0.111358E+09 | 0.00 | 0.111358E+09 | 44607222.01 | 0.227571E+09 |
November | 71354840.64 | 0.00 | 71354840.64 | 6607589.45 | 0.361318E+09 |
December | 61808589.18 | 0.00 | 61808589.18 | 3092.03 | 0.615510E+09 |
Annual Sum or Average | 0.189488E+10 | 73834832.75 | 0.182105E+10 | 0.135141E+10 | 0.336133E+10 |
Minimum of Months | 61808589.18 | 0.00 | 61808589.18 | 3092.03 | 61141830.42 |
Maximum of Months | 0.275033E+09 | 30599089.35 | 0.247859E+09 | 0.314209E+09 | 0.642813E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.297774E+09 | 0.123462E+09 | 0.174311E+09 | 0.109619E+09 | 0.108990E+10 |
February | 0.427402E+09 | 0.183814E+09 | 0.243589E+09 | 0.245869E+09 | 0.772709E+09 |
March | 0.643204E+09 | 0.323358E+09 | 0.319845E+09 | 0.484533E+09 | 0.662887E+09 |
April | 0.857276E+09 | 0.462179E+09 | 0.395098E+09 | 0.821131E+09 | 0.388256E+09 |
May | 0.962106E+09 | 0.424335E+09 | 0.537771E+09 | 0.106760E+10 | 0.201569E+09 |
June | 0.105059E+10 | 0.502492E+09 | 0.548099E+09 | 0.126633E+10 | 0.128283E+09 |
July | 0.106574E+10 | 0.501379E+09 | 0.564361E+09 | 0.131417E+10 | 0.116703E+09 |
August | 0.820339E+09 | 0.358507E+09 | 0.461832E+09 | 0.977789E+09 | 0.139933E+09 |
September | 0.637450E+09 | 0.286023E+09 | 0.351427E+09 | 0.675906E+09 | 0.233385E+09 |
October | 0.396582E+09 | 0.149118E+09 | 0.247464E+09 | 0.311256E+09 | 0.402401E+09 |
November | 0.245847E+09 | 81876671.53 | 0.163970E+09 | 0.115225E+09 | 0.626029E+09 |
December | 0.233566E+09 | 87671849.66 | 0.145894E+09 | 68530401.31 | 0.105932E+10 |
Annual Sum or Average | 0.763788E+10 | 0.348422E+10 | 0.415366E+10 | 0.745796E+10 | 0.582137E+10 |
Minimum of Months | 0.233566E+09 | 81876671.53 | 0.145894E+09 | 68530401.31 | 0.116703E+09 |
Maximum of Months | 0.106574E+10 | 0.502492E+09 | 0.564361E+09 | 0.131417E+10 | 0.108990E+10 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 92385913.46 | 0.00 | 92385913.46 | 277666.14 | 0.852409E+09 |
February | 0.128179E+09 | 0.00 | 0.128179E+09 | 7066269.99 | 0.616167E+09 |
March | 0.174638E+09 | 6676.71 | 0.174632E+09 | 27057604.00 | 0.518429E+09 |
April | 0.222233E+09 | 2282601.20 | 0.219950E+09 | 0.107899E+09 | 0.292558E+09 |
May | 0.322061E+09 | 17085794.07 | 0.304975E+09 | 0.301749E+09 | 0.145511E+09 |
June | 0.348311E+09 | 38751815.96 | 0.309560E+09 | 0.398197E+09 | 92167300.00 |
July | 0.344104E+09 | 30206058.75 | 0.313897E+09 | 0.408999E+09 | 87550131.58 |
August | 0.261291E+09 | 4970992.81 | 0.256320E+09 | 0.282608E+09 | 0.106071E+09 |
September | 0.196876E+09 | 203217.46 | 0.196673E+09 | 0.158004E+09 | 0.180148E+09 |
October | 0.141028E+09 | 0.00 | 0.141028E+09 | 54358653.21 | 0.306393E+09 |
November | 90366403.43 | 0.00 | 90366403.43 | 6927780.89 | 0.488442E+09 |
December | 78276678.29 | 0.00 | 78276678.29 | 0.00 | 0.820256E+09 |
Annual Sum or Average | 0.239975E+10 | 93507156.96 | 0.230624E+10 | 0.175314E+10 | 0.450610E+10 |
Minimum of Months | 78276678.29 | 0.00 | 78276678.29 | 0.00 | 87550131.58 |
Maximum of Months | 0.348311E+09 | 38751815.96 | 0.313897E+09 | 0.408999E+09 | 0.852409E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 34057273.10 | 0.00 | 34057273.10 | 102359.24 | 0.314233E+09 |
February | 47251937.81 | 0.00 | 47251937.81 | 2604919.71 | 0.227145E+09 |
March | 64378875.70 | 2461.31 | 64376414.39 | 9974553.20 | 0.191114E+09 |
April | 81924229.66 | 841461.32 | 81082768.34 | 39775895.18 | 0.107849E+09 |
May | 0.118725E+09 | 6298531.16 | 0.112426E+09 | 0.111237E+09 | 53641214.09 |
June | 0.128402E+09 | 14285523.95 | 0.114116E+09 | 0.146792E+09 | 33976683.13 |
July | 0.126851E+09 | 11135203.99 | 0.115716E+09 | 0.150774E+09 | 32274603.67 |
August | 96322837.24 | 1832513.78 | 94490323.46 | 0.104181E+09 | 39102019.15 |
September | 72576611.07 | 74914.37 | 72501696.70 | 58246989.77 | 66410049.07 |
October | 51988881.22 | 0.00 | 51988881.22 | 20038850.39 | 0.112949E+09 |
November | 33312798.08 | 0.00 | 33312798.08 | 2553866.89 | 0.180060E+09 |
December | 28856024.80 | 0.00 | 28856024.80 | 0.00 | 0.302380E+09 |
Annual Sum or Average | 0.884647E+09 | 34470609.88 | 0.850177E+09 | 0.646282E+09 | 0.166114E+10 |
Minimum of Months | 28856024.80 | 0.00 | 28856024.80 | 0.00 | 32274603.67 |
Maximum of Months | 0.128402E+09 | 14285523.95 | 0.115716E+09 | 0.150774E+09 | 0.314233E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.236084E+09 | 0.164534E+09 | 71549800.91 | 0.196189E+09 | 0.247887E+09 |
February | 0.266219E+09 | 0.179120E+09 | 87098230.94 | 0.249471E+09 | 0.187993E+09 |
March | 0.259080E+09 | 0.163071E+09 | 96009120.53 | 0.250883E+09 | 0.170365E+09 |
April | 0.229001E+09 | 0.124157E+09 | 0.104844E+09 | 0.243064E+09 | 0.107291E+09 |
May | 0.202555E+09 | 71462483.28 | 0.131092E+09 | 0.237786E+09 | 58954928.28 |
June | 0.172239E+09 | 45377083.81 | 0.126862E+09 | 0.216302E+09 | 37073016.54 |
July | 0.195830E+09 | 62315011.60 | 0.133515E+09 | 0.255688E+09 | 34753138.61 |
August | 0.207793E+09 | 86385450.33 | 0.121408E+09 | 0.262854E+09 | 40465493.70 |
September | 0.212093E+09 | 0.110964E+09 | 0.101129E+09 | 0.247086E+09 | 65604978.64 |
October | 0.194875E+09 | 0.116174E+09 | 78700257.98 | 0.200741E+09 | 0.105245E+09 |
November | 0.164726E+09 | 0.103291E+09 | 61435163.42 | 0.146542E+09 | 0.154158E+09 |
December | 0.181331E+09 | 0.118975E+09 | 62355771.56 | 0.138095E+09 | 0.242662E+09 |
Annual Sum or Average | 0.252183E+10 | 0.134583E+10 | 0.117600E+10 | 0.264470E+10 | 0.145245E+10 |
Minimum of Months | 0.164726E+09 | 45377083.81 | 61435163.42 | 0.138095E+09 | 34753138.61 |
Maximum of Months | 0.266219E+09 | 0.179120E+09 | 0.133515E+09 | 0.262854E+09 | 0.247887E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.640779E+09 | 0.446578E+09 | 0.194201E+09 | 0.532496E+09 | 0.672817E+09 |
February | 0.722572E+09 | 0.486170E+09 | 0.236402E+09 | 0.677116E+09 | 0.510252E+09 |
March | 0.703195E+09 | 0.442607E+09 | 0.260588E+09 | 0.680949E+09 | 0.462404E+09 |
April | 0.621556E+09 | 0.336987E+09 | 0.284569E+09 | 0.659726E+09 | 0.291211E+09 |
May | 0.549775E+09 | 0.193964E+09 | 0.355811E+09 | 0.645401E+09 | 0.160016E+09 |
June | 0.467492E+09 | 0.123163E+09 | 0.344329E+09 | 0.587087E+09 | 0.100624E+09 |
July | 0.531524E+09 | 0.169136E+09 | 0.362388E+09 | 0.693988E+09 | 94327126.77 |
August | 0.563993E+09 | 0.234468E+09 | 0.329525E+09 | 0.713438E+09 | 0.109832E+09 |
September | 0.575664E+09 | 0.301178E+09 | 0.274486E+09 | 0.670642E+09 | 0.178065E+09 |
October | 0.528929E+09 | 0.315321E+09 | 0.213609E+09 | 0.544853E+09 | 0.285656E+09 |
November | 0.447101E+09 | 0.280353E+09 | 0.166748E+09 | 0.397746E+09 | 0.418416E+09 |
December | 0.492170E+09 | 0.322923E+09 | 0.169246E+09 | 0.374817E+09 | 0.658634E+09 |
Annual Sum or Average | 0.684475E+10 | 0.365285E+10 | 0.319190E+10 | 0.717826E+10 | 0.394225E+10 |
Minimum of Months | 0.447101E+09 | 0.123163E+09 | 0.166748E+09 | 0.374817E+09 | 94327126.77 |
Maximum of Months | 0.722572E+09 | 0.486170E+09 | 0.362388E+09 | 0.713438E+09 | 0.672817E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.505970E+09 | 0.352626E+09 | 0.153344E+09 | 0.423735E+09 | 0.517189E+09 |
February | 0.570555E+09 | 0.383888E+09 | 0.186667E+09 | 0.534060E+09 | 0.390617E+09 |
March | 0.555255E+09 | 0.349490E+09 | 0.205765E+09 | 0.534872E+09 | 0.354109E+09 |
April | 0.490791E+09 | 0.266090E+09 | 0.224701E+09 | 0.513919E+09 | 0.222002E+09 |
May | 0.434112E+09 | 0.153157E+09 | 0.280955E+09 | 0.501137E+09 | 0.116321E+09 |
June | 0.369140E+09 | 97251340.98 | 0.271888E+09 | 0.459969E+09 | 68444699.82 |
July | 0.419700E+09 | 0.133552E+09 | 0.286148E+09 | 0.545693E+09 | 60964027.83 |
August | 0.445338E+09 | 0.185140E+09 | 0.260199E+09 | 0.558344E+09 | 72937354.38 |
September | 0.454554E+09 | 0.237815E+09 | 0.216738E+09 | 0.523989E+09 | 0.128836E+09 |
October | 0.417652E+09 | 0.248983E+09 | 0.168669E+09 | 0.427803E+09 | 0.214659E+09 |
November | 0.353038E+09 | 0.221371E+09 | 0.131667E+09 | 0.315633E+09 | 0.314849E+09 |
December | 0.388625E+09 | 0.254986E+09 | 0.133640E+09 | 0.299765E+09 | 0.501641E+09 |
Annual Sum or Average | 0.540473E+10 | 0.288435E+10 | 0.252038E+10 | 0.563892E+10 | 0.296257E+10 |
Minimum of Months | 0.353038E+09 | 97251340.98 | 0.131667E+09 | 0.299765E+09 | 60964027.83 |
Maximum of Months | 0.570555E+09 | 0.383888E+09 | 0.286148E+09 | 0.558344E+09 | 0.517189E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.306009E+09 | 0.129524E+09 | 0.176485E+09 | 0.125536E+09 | 0.111599E+10 |
February | 0.447137E+09 | 0.205208E+09 | 0.241929E+09 | 0.280829E+09 | 0.811292E+09 |
March | 0.649507E+09 | 0.333167E+09 | 0.316340E+09 | 0.503534E+09 | 0.695422E+09 |
April | 0.802168E+09 | 0.406948E+09 | 0.395220E+09 | 0.753261E+09 | 0.406458E+09 |
May | 0.101935E+10 | 0.487740E+09 | 0.531607E+09 | 0.114742E+10 | 0.210157E+09 |
June | 0.947760E+09 | 0.409340E+09 | 0.538420E+09 | 0.114426E+10 | 0.125121E+09 |
July | 0.104701E+10 | 0.486944E+09 | 0.560065E+09 | 0.130498E+10 | 0.112274E+09 |
August | 0.859479E+09 | 0.389498E+09 | 0.469981E+09 | 0.103530E+10 | 0.134830E+09 |
September | 0.652966E+09 | 0.293158E+09 | 0.359808E+09 | 0.694620E+09 | 0.238593E+09 |
October | 0.426698E+09 | 0.171705E+09 | 0.254993E+09 | 0.351254E+09 | 0.414675E+09 |
November | 0.251269E+09 | 85417046.86 | 0.165852E+09 | 0.125893E+09 | 0.644007E+09 |
December | 0.228859E+09 | 79291862.18 | 0.149567E+09 | 68477070.24 | 0.107989E+10 |
Annual Sum or Average | 0.763821E+10 | 0.347794E+10 | 0.416027E+10 | 0.753537E+10 | 0.598871E+10 |
Minimum of Months | 0.228859E+09 | 79291862.18 | 0.149567E+09 | 68477070.24 | 0.112274E+09 |
Maximum of Months | 0.104701E+10 | 0.487740E+09 | 0.560065E+09 | 0.130498E+10 | 0.111599E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 72949479.92 | 0.00 | 72949479.92 | 554609.90 | 0.644044E+09 |
February | 0.101212E+09 | 0.00 | 0.101212E+09 | 7846073.29 | 0.461939E+09 |
March | 0.137897E+09 | 5272.04 | 0.137892E+09 | 24596701.11 | 0.390718E+09 |
April | 0.175479E+09 | 1802380.52 | 0.173676E+09 | 84611425.53 | 0.221644E+09 |
May | 0.254305E+09 | 13491232.00 | 0.240813E+09 | 0.227297E+09 | 0.109540E+09 |
June | 0.275033E+09 | 30599089.35 | 0.244433E+09 | 0.303579E+09 | 69057339.26 |
July | 0.271710E+09 | 23851214.90 | 0.247859E+09 | 0.313619E+09 | 64088193.99 |
August | 0.206320E+09 | 3925180.00 | 0.202395E+09 | 0.215392E+09 | 78114193.95 |
September | 0.155457E+09 | 160463.95 | 0.155296E+09 | 0.122797E+09 | 0.133116E+09 |
October | 0.111358E+09 | 0.00 | 0.111358E+09 | 46512650.60 | 0.227150E+09 |
November | 71354840.64 | 0.00 | 71354840.64 | 7132692.57 | 0.359648E+09 |
December | 61808589.18 | 0.00 | 61808589.18 | 4341.02 | 0.617053E+09 |
Annual Sum or Average | 0.189488E+10 | 73834832.75 | 0.182105E+10 | 0.135394E+10 | 0.337611E+10 |
Minimum of Months | 61808589.18 | 0.00 | 61808589.18 | 4341.02 | 64088193.99 |
Maximum of Months | 0.275033E+09 | 30599089.35 | 0.247859E+09 | 0.313619E+09 | 0.644044E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.306009E+09 | 0.129524E+09 | 0.176485E+09 | 0.130050E+09 | 0.110960E+10 |
February | 0.447137E+09 | 0.205208E+09 | 0.241929E+09 | 0.291674E+09 | 0.803350E+09 |
March | 0.649507E+09 | 0.333167E+09 | 0.316340E+09 | 0.516876E+09 | 0.687178E+09 |
April | 0.802168E+09 | 0.406948E+09 | 0.395220E+09 | 0.763715E+09 | 0.403933E+09 |
May | 0.101935E+10 | 0.487740E+09 | 0.531607E+09 | 0.114099E+10 | 0.217562E+09 |
June | 0.947760E+09 | 0.409340E+09 | 0.538420E+09 | 0.112854E+10 | 0.135917E+09 |
July | 0.104701E+10 | 0.486944E+09 | 0.560065E+09 | 0.128863E+10 | 0.124980E+09 |
August | 0.859479E+09 | 0.389498E+09 | 0.469981E+09 | 0.102622E+10 | 0.148647E+09 |
September | 0.652966E+09 | 0.293158E+09 | 0.359808E+09 | 0.696481E+09 | 0.241830E+09 |
October | 0.426698E+09 | 0.171705E+09 | 0.254993E+09 | 0.360186E+09 | 0.410616E+09 |
November | 0.251269E+09 | 85417046.86 | 0.165852E+09 | 0.133100E+09 | 0.638133E+09 |
December | 0.228859E+09 | 79291862.18 | 0.149567E+09 | 71283526.02 | 0.107561E+10 |
Annual Sum or Average | 0.763821E+10 | 0.347794E+10 | 0.416027E+10 | 0.754775E+10 | 0.599735E+10 |
Minimum of Months | 0.228859E+09 | 79291862.18 | 0.149567E+09 | 71283526.02 | 0.124980E+09 |
Maximum of Months | 0.104701E+10 | 0.487740E+09 | 0.560065E+09 | 0.128863E+10 | 0.110960E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.742054E+09 | 0.517160E+09 | 0.224894E+09 | 0.601019E+09 | 0.777508E+09 |
February | 0.836774E+09 | 0.563008E+09 | 0.273766E+09 | 0.763581E+09 | 0.588619E+09 |
March | 0.814335E+09 | 0.512561E+09 | 0.301774E+09 | 0.769272E+09 | 0.531503E+09 |
April | 0.719792E+09 | 0.390247E+09 | 0.329545E+09 | 0.745930E+09 | 0.329302E+09 |
May | 0.636666E+09 | 0.224620E+09 | 0.412047E+09 | 0.737845E+09 | 0.167996E+09 |
June | 0.541379E+09 | 0.142628E+09 | 0.398750E+09 | 0.680171E+09 | 97942750.48 |
July | 0.615530E+09 | 0.195867E+09 | 0.419663E+09 | 0.807226E+09 | 85844859.20 |
August | 0.653132E+09 | 0.271525E+09 | 0.381606E+09 | 0.821618E+09 | 0.104773E+09 |
September | 0.666647E+09 | 0.348779E+09 | 0.317868E+09 | 0.764495E+09 | 0.190213E+09 |
October | 0.612526E+09 | 0.365157E+09 | 0.247369E+09 | 0.617452E+09 | 0.323578E+09 |
November | 0.517764E+09 | 0.324662E+09 | 0.193102E+09 | 0.449594E+09 | 0.476493E+09 |
December | 0.569956E+09 | 0.373961E+09 | 0.195996E+09 | 0.424277E+09 | 0.753591E+09 |
Annual Sum or Average | 0.792655E+10 | 0.423018E+10 | 0.369638E+10 | 0.818248E+10 | 0.442736E+10 |
Minimum of Months | 0.517764E+09 | 0.142628E+09 | 0.193102E+09 | 0.424277E+09 | 85844859.20 |
Maximum of Months | 0.836774E+09 | 0.563008E+09 | 0.419663E+09 | 0.821618E+09 | 0.777508E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.510627E+09 | 0.00 | 0.510627E+09 | 851337.29 | 0.481265E+10 |
February | 0.708457E+09 | 0.00 | 0.708457E+09 | 28309527.75 | 0.356916E+10 |
March | 0.965244E+09 | 36902.88 | 0.965208E+09 | 0.116503E+09 | 0.308255E+10 |
April | 0.122831E+10 | 12616185.78 | 0.121569E+10 | 0.514222E+09 | 0.178387E+10 |
May | 0.178006E+10 | 94435047.30 | 0.168563E+10 | 0.156186E+10 | 0.861621E+09 |
June | 0.192515E+10 | 0.214186E+09 | 0.171097E+10 | 0.211200E+10 | 0.541937E+09 |
July | 0.190190E+10 | 0.166952E+09 | 0.173495E+10 | 0.220751E+10 | 0.492616E+09 |
August | 0.144419E+10 | 27475219.40 | 0.141671E+10 | 0.149595E+10 | 0.618740E+09 |
September | 0.108815E+10 | 1123205.09 | 0.108703E+10 | 0.798475E+09 | 0.108430E+10 |
October | 0.779479E+09 | 0.00 | 0.779479E+09 | 0.240274E+09 | 0.189521E+10 |
November | 0.499465E+09 | 0.00 | 0.499465E+09 | 25829505.45 | 0.296036E+10 |
December | 0.432644E+09 | 0.00 | 0.432644E+09 | 0.00 | 0.468803E+10 |
Annual Sum or Average | 0.132637E+11 | 0.516824E+09 | 0.127469E+11 | 0.910179E+10 | 0.263910E+11 |
Minimum of Months | 0.432644E+09 | 0.00 | 0.432644E+09 | 0.00 | 0.492616E+09 |
Maximum of Months | 0.192515E+10 | 0.214186E+09 | 0.173495E+10 | 0.220751E+10 | 0.481265E+10 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.510627E+09 | 0.00 | 0.510627E+09 | 607071.82 | 0.489076E+10 |
February | 0.708457E+09 | 0.00 | 0.708457E+09 | 23818554.16 | 0.363812E+10 |
March | 0.965244E+09 | 36902.88 | 0.965208E+09 | 0.105407E+09 | 0.314858E+10 |
April | 0.122831E+10 | 12616185.78 | 0.121569E+10 | 0.490262E+09 | 0.182278E+10 |
May | 0.178006E+10 | 94435047.30 | 0.168563E+10 | 0.153570E+10 | 0.878833E+09 |
June | 0.192515E+10 | 0.214186E+09 | 0.171097E+10 | 0.208867E+10 | 0.554657E+09 |
July | 0.190190E+10 | 0.166952E+09 | 0.173495E+10 | 0.218707E+10 | 0.504280E+09 |
August | 0.144419E+10 | 27475219.40 | 0.141671E+10 | 0.147495E+10 | 0.635277E+09 |
September | 0.108815E+10 | 1123205.09 | 0.108703E+10 | 0.776587E+09 | 0.110944E+10 |
October | 0.779479E+09 | 0.00 | 0.779479E+09 | 0.222516E+09 | 0.194177E+10 |
November | 0.499465E+09 | 0.00 | 0.499465E+09 | 22720147.45 | 0.303435E+10 |
December | 0.432644E+09 | 0.00 | 0.432644E+09 | 0.00 | 0.476726E+10 |
Annual Sum or Average | 0.132637E+11 | 0.516824E+09 | 0.127469E+11 | 0.892832E+10 | 0.269261E+11 |
Minimum of Months | 0.432644E+09 | 0.00 | 0.432644E+09 | 0.00 | 0.504280E+09 |
Maximum of Months | 0.192515E+10 | 0.214186E+09 | 0.173495E+10 | 0.218707E+10 | 0.489076E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 72949479.92 | 0.00 | 72949479.92 | 1333081.67 | 0.596399E+09 |
February | 0.101212E+09 | 0.00 | 0.101212E+09 | 10943280.29 | 0.439692E+09 |
March | 0.137897E+09 | 5272.04 | 0.137892E+09 | 34609957.48 | 0.375164E+09 |
April | 0.175479E+09 | 1802380.52 | 0.173676E+09 | 0.116770E+09 | 0.218995E+09 |
May | 0.254305E+09 | 13491232.00 | 0.240813E+09 | 0.304395E+09 | 0.111323E+09 |
June | 0.275033E+09 | 30599089.35 | 0.244433E+09 | 0.386842E+09 | 71962953.51 |
July | 0.271710E+09 | 23851214.90 | 0.247859E+09 | 0.405658E+09 | 64190763.69 |
August | 0.206320E+09 | 3925180.00 | 0.202395E+09 | 0.294598E+09 | 74964738.36 |
September | 0.155457E+09 | 160463.95 | 0.155296E+09 | 0.172994E+09 | 0.126569E+09 |
October | 0.111358E+09 | 0.00 | 0.111358E+09 | 69112410.23 | 0.217654E+09 |
November | 71354840.64 | 0.00 | 71354840.64 | 12090086.83 | 0.349440E+09 |
December | 61808589.18 | 0.00 | 61808589.18 | 167657.10 | 0.577908E+09 |
Annual Sum or Average | 0.189488E+10 | 73834832.75 | 0.182105E+10 | 0.180951E+10 | 0.322426E+10 |
Minimum of Months | 61808589.18 | 0.00 | 61808589.18 | 167657.10 | 64190763.69 |
Maximum of Months | 0.275033E+09 | 30599089.35 | 0.247859E+09 | 0.405658E+09 | 0.596399E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.595505E+09 | 0.246907E+09 | 0.348598E+09 | 0.258377E+09 | 0.203930E+10 |
February | 0.854744E+09 | 0.367601E+09 | 0.487143E+09 | 0.536027E+09 | 0.148779E+10 |
March | 0.128632E+10 | 0.646670E+09 | 0.639645E+09 | 0.104475E+10 | 0.129160E+10 |
April | 0.171443E+10 | 0.924292E+09 | 0.790139E+09 | 0.179980E+10 | 0.780749E+09 |
May | 0.192408E+10 | 0.848610E+09 | 0.107547E+10 | 0.240735E+10 | 0.416292E+09 |
June | 0.210103E+10 | 0.100491E+10 | 0.109612E+10 | 0.283405E+10 | 0.270263E+09 |
July | 0.213133E+10 | 0.100269E+10 | 0.112864E+10 | 0.296761E+10 | 0.240469E+09 |
August | 0.164056E+10 | 0.716963E+09 | 0.923598E+09 | 0.224362E+10 | 0.280351E+09 |
September | 0.127481E+10 | 0.572005E+09 | 0.702805E+09 | 0.155689E+10 | 0.462516E+09 |
October | 0.793108E+09 | 0.298216E+09 | 0.494892E+09 | 0.734467E+09 | 0.781635E+09 |
November | 0.491659E+09 | 0.163742E+09 | 0.327917E+09 | 0.269502E+09 | 0.122126E+10 |
December | 0.467099E+09 | 0.175331E+09 | 0.291768E+09 | 0.162694E+09 | 0.199922E+10 |
Annual Sum or Average | 0.152747E+11 | 0.696794E+10 | 0.830673E+10 | 0.168151E+11 | 0.112714E+11 |
Minimum of Months | 0.467099E+09 | 0.163742E+09 | 0.291768E+09 | 0.162694E+09 | 0.240469E+09 |
Maximum of Months | 0.213133E+10 | 0.100491E+10 | 0.112864E+10 | 0.296761E+10 | 0.203930E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.505970E+09 | 0.352626E+09 | 0.153344E+09 | 0.447015E+09 | 0.482804E+09 |
February | 0.570555E+09 | 0.383888E+09 | 0.186667E+09 | 0.559253E+09 | 0.374781E+09 |
March | 0.555255E+09 | 0.349490E+09 | 0.205765E+09 | 0.566661E+09 | 0.342574E+09 |
April | 0.490791E+09 | 0.266090E+09 | 0.224701E+09 | 0.558580E+09 | 0.218322E+09 |
May | 0.434112E+09 | 0.153157E+09 | 0.280955E+09 | 0.574296E+09 | 0.118676E+09 |
June | 0.369140E+09 | 97251340.98 | 0.271888E+09 | 0.534009E+09 | 75880344.50 |
July | 0.419700E+09 | 0.133552E+09 | 0.286148E+09 | 0.629190E+09 | 66905754.06 |
August | 0.445338E+09 | 0.185140E+09 | 0.260199E+09 | 0.633692E+09 | 76300186.99 |
September | 0.454554E+09 | 0.237815E+09 | 0.216738E+09 | 0.581680E+09 | 0.126133E+09 |
October | 0.417652E+09 | 0.248983E+09 | 0.168669E+09 | 0.465873E+09 | 0.208400E+09 |
November | 0.353038E+09 | 0.221371E+09 | 0.131667E+09 | 0.335029E+09 | 0.308286E+09 |
December | 0.388625E+09 | 0.254986E+09 | 0.133640E+09 | 0.317199E+09 | 0.473717E+09 |
Annual Sum or Average | 0.540473E+10 | 0.288435E+10 | 0.252038E+10 | 0.620248E+10 | 0.287278E+10 |
Minimum of Months | 0.353038E+09 | 97251340.98 | 0.131667E+09 | 0.317199E+09 | 66905754.06 |
Maximum of Months | 0.570555E+09 | 0.383888E+09 | 0.286148E+09 | 0.633692E+09 | 0.482804E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 92385913.46 | 0.00 | 92385913.46 | 216128.28 | 0.854249E+09 |
February | 0.128179E+09 | 0.00 | 0.128179E+09 | 6113484.14 | 0.622760E+09 |
March | 0.174638E+09 | 6676.71 | 0.174632E+09 | 24068628.56 | 0.526059E+09 |
April | 0.222233E+09 | 2282601.20 | 0.219950E+09 | 0.101934E+09 | 0.295755E+09 |
May | 0.322061E+09 | 17085794.07 | 0.304975E+09 | 0.291800E+09 | 0.147828E+09 |
June | 0.348311E+09 | 38751815.96 | 0.309560E+09 | 0.387939E+09 | 94334148.33 |
July | 0.344104E+09 | 30206058.75 | 0.313897E+09 | 0.399634E+09 | 89426429.04 |
August | 0.261291E+09 | 4970992.81 | 0.256320E+09 | 0.273939E+09 | 0.108838E+09 |
September | 0.196876E+09 | 203217.46 | 0.196673E+09 | 0.151780E+09 | 0.182191E+09 |
October | 0.141028E+09 | 0.00 | 0.141028E+09 | 49915169.91 | 0.311715E+09 |
November | 90366403.43 | 0.00 | 90366403.43 | 6186484.76 | 0.497358E+09 |
December | 78276678.29 | 0.00 | 78276678.29 | 0.00 | 0.825763E+09 |
Annual Sum or Average | 0.239975E+10 | 93507156.96 | 0.230624E+10 | 0.169352E+10 | 0.455628E+10 |
Minimum of Months | 78276678.29 | 0.00 | 78276678.29 | 0.00 | 89426429.04 |
Maximum of Months | 0.348311E+09 | 38751815.96 | 0.313897E+09 | 0.399634E+09 | 0.854249E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 82658026.82 | 0.00 | 82658026.82 | 193370.79 | 0.764175E+09 |
February | 0.114682E+09 | 0.00 | 0.114682E+09 | 5469757.42 | 0.557176E+09 |
March | 0.156249E+09 | 5973.67 | 0.156243E+09 | 21534293.17 | 0.470667E+09 |
April | 0.198833E+09 | 2042251.94 | 0.196790E+09 | 91200306.57 | 0.264614E+09 |
May | 0.288149E+09 | 15286724.70 | 0.272862E+09 | 0.261074E+09 | 0.132262E+09 |
June | 0.311635E+09 | 34671396.57 | 0.276964E+09 | 0.347090E+09 | 84401119.94 |
July | 0.307871E+09 | 27025475.21 | 0.280845E+09 | 0.357554E+09 | 80010164.90 |
August | 0.233778E+09 | 4447566.10 | 0.229331E+09 | 0.245094E+09 | 97377684.32 |
September | 0.176146E+09 | 181819.44 | 0.175964E+09 | 0.135798E+09 | 0.163007E+09 |
October | 0.126179E+09 | 0.00 | 0.126179E+09 | 44659291.65 | 0.278893E+09 |
November | 80851163.55 | 0.00 | 80851163.55 | 5535071.36 | 0.444963E+09 |
December | 70034440.66 | 0.00 | 70034440.66 | 0.00 | 0.738729E+09 |
Annual Sum or Average | 0.214707E+10 | 83661207.63 | 0.206340E+10 | 0.151520E+10 | 0.407627E+10 |
Minimum of Months | 70034440.66 | 0.00 | 70034440.66 | 0.00 | 80010164.90 |
Maximum of Months | 0.311635E+09 | 34671396.57 | 0.280845E+09 | 0.357554E+09 | 0.764175E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188894E+10 | 0.131646E+10 | 0.572480E+09 | 0.155921E+10 | 0.198638E+10 |
February | 0.213005E+10 | 0.143317E+10 | 0.696885E+09 | 0.197482E+10 | 0.151468E+10 |
March | 0.207293E+10 | 0.130475E+10 | 0.768182E+09 | 0.198477E+10 | 0.137786E+10 |
April | 0.183227E+10 | 0.993394E+09 | 0.838875E+09 | 0.192000E+10 | 0.866773E+09 |
May | 0.162067E+10 | 0.571781E+09 | 0.104889E+10 | 0.187016E+10 | 0.479884E+09 |
June | 0.137811E+10 | 0.363068E+09 | 0.101504E+10 | 0.169819E+10 | 0.304455E+09 |
July | 0.156686E+10 | 0.498591E+09 | 0.106827E+10 | 0.201456E+10 | 0.284356E+09 |
August | 0.166258E+10 | 0.691182E+09 | 0.971399E+09 | 0.207182E+10 | 0.333198E+09 |
September | 0.169698E+10 | 0.887836E+09 | 0.809149E+09 | 0.195213E+10 | 0.531879E+09 |
October | 0.155922E+10 | 0.929526E+09 | 0.629691E+09 | 0.158450E+10 | 0.855853E+09 |
November | 0.131800E+10 | 0.826446E+09 | 0.491551E+09 | 0.115612E+10 | 0.125313E+10 |
December | 0.145085E+10 | 0.951937E+09 | 0.498917E+09 | 0.109504E+10 | 0.195441E+10 |
Annual Sum or Average | 0.201775E+11 | 0.107681E+11 | 0.940933E+10 | 0.208813E+11 | 0.117429E+11 |
Minimum of Months | 0.131800E+10 | 0.363068E+09 | 0.491551E+09 | 0.109504E+10 | 0.284356E+09 |
Maximum of Months | 0.213005E+10 | 0.143317E+10 | 0.106827E+10 | 0.207182E+10 | 0.198638E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 802.35 | 920.56 | 955.44 | 665.88 | 289.56 | 0.00 | 0.00 |
February | 1116.73 | 788.89 | 1192.84 | 802.58 | 390.26 | 0.00 | 0.00 |
March | 1005.89 | 653.05 | 1048.51 | 659.96 | 388.55 | 0.00 | 0.00 |
April | 1003.73 | 425.65 | 957.67 | 519.22 | 438.45 | 0.00 | 0.00 |
May | 953.54 | 221.08 | 819.75 | 289.21 | 530.53 | 0.00 | 0.00 |
June | 899.11 | 140.29 | 720.29 | 189.77 | 530.53 | 0.00 | 0.00 |
July | 1026.14 | 128.16 | 792.53 | 252.19 | 540.34 | 0.00 | 0.00 |
August | 1053.36 | 150.81 | 840.95 | 349.61 | 491.34 | 0.00 | 0.00 |
September | 1023.02 | 255.04 | 886.96 | 464.05 | 422.92 | 0.00 | 0.00 |
October | 802.75 | 406.54 | 788.67 | 470.16 | 318.50 | 0.00 | 0.00 |
November | 611.23 | 606.69 | 688.88 | 431.96 | 256.92 | 0.00 | 0.00 |
December | 568.08 | 899.34 | 733.86 | 481.50 | 252.36 | 0.00 | 0.00 |
Annual Sum or Average | 903.99 | 464.89 | 866.80 | 462.59 | 404.21 | 0.00 | 0.00 |
Minimum of Months | 568.08 | 128.16 | 688.88 | 189.77 | 252.36 | 0.00 | 0.00 |
Maximum of Months | 1116.73 | 920.56 | 1192.84 | 802.58 | 540.34 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2243.04 | 2613.37 | 2690.46 | 1875.07 | 815.40 | 0.00 | 0.00 |
February | 3121.20 | 2248.21 | 3358.95 | 2260.01 | 1098.94 | 0.00 | 0.00 |
March | 2809.18 | 1879.51 | 2952.53 | 1858.39 | 1094.13 | 0.00 | 0.00 |
April | 2798.87 | 1250.57 | 2696.73 | 1462.08 | 1234.65 | 0.00 | 0.00 |
May | 2648.77 | 671.55 | 2308.35 | 814.40 | 1493.95 | 0.00 | 0.00 |
June | 2490.52 | 438.54 | 2028.29 | 534.37 | 1493.93 | 0.00 | 0.00 |
July | 2855.56 | 396.23 | 2231.71 | 710.16 | 1521.56 | 0.00 | 0.00 |
August | 2933.81 | 472.21 | 2368.05 | 984.47 | 1383.58 | 0.00 | 0.00 |
September | 2849.98 | 778.80 | 2497.62 | 1306.72 | 1190.90 | 0.00 | 0.00 |
October | 2237.81 | 1197.65 | 2220.83 | 1323.95 | 896.88 | 0.00 | 0.00 |
November | 1703.53 | 1742.96 | 1939.83 | 1216.37 | 723.46 | 0.00 | 0.00 |
December | 1585.40 | 2551.49 | 2066.49 | 1355.87 | 710.62 | 0.00 | 0.00 |
Annual Sum or Average | 2518.91 | 1349.36 | 2440.87 | 1302.62 | 1138.24 | 0.00 | 0.00 |
Minimum of Months | 1585.40 | 396.23 | 1939.83 | 534.37 | 710.62 | 0.00 | 0.00 |
Maximum of Months | 3121.20 | 2613.37 | 3358.95 | 2260.01 | 1521.56 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2948.96 | 3527.54 | 3495.06 | 2435.82 | 1059.24 | 0.00 | 0.00 |
February | 4117.06 | 3032.71 | 4363.46 | 2935.88 | 1427.58 | 0.00 | 0.00 |
March | 3708.32 | 2541.75 | 3835.50 | 2414.16 | 1421.34 | 0.00 | 0.00 |
April | 3692.03 | 1705.74 | 3503.21 | 1899.33 | 1603.88 | 0.00 | 0.00 |
May | 3490.39 | 919.09 | 2998.68 | 1057.96 | 1940.72 | 0.00 | 0.00 |
June | 3280.29 | 604.08 | 2634.87 | 694.17 | 1940.70 | 0.00 | 0.00 |
July | 3767.27 | 536.74 | 2899.12 | 922.53 | 1976.59 | 0.00 | 0.00 |
August | 3865.26 | 641.05 | 3076.23 | 1278.88 | 1797.35 | 0.00 | 0.00 |
September | 3746.30 | 1070.17 | 3244.55 | 1697.51 | 1547.05 | 0.00 | 0.00 |
October | 2932.94 | 1651.71 | 2884.99 | 1719.89 | 1165.10 | 0.00 | 0.00 |
November | 2235.37 | 2392.36 | 2519.95 | 1580.13 | 939.82 | 0.00 | 0.00 |
December | 2076.91 | 3464.31 | 2684.49 | 1761.35 | 923.13 | 0.00 | 0.00 |
Annual Sum or Average | 3316.14 | 1835.16 | 3170.82 | 1692.18 | 1478.64 | 0.00 | 0.00 |
Minimum of Months | 2076.91 | 536.74 | 2519.95 | 694.17 | 923.13 | 0.00 | 0.00 |
Maximum of Months | 4117.06 | 3527.54 | 4363.46 | 2935.88 | 1976.59 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 168.99 | 571.90 | 303.16 | 180.01 | 123.14 | 0.00 | 0.00 |
February | 315.11 | 473.96 | 420.67 | 243.51 | 177.16 | 0.00 | 0.00 |
March | 376.73 | 380.48 | 449.81 | 254.87 | 194.93 | 0.00 | 0.00 |
April | 486.66 | 239.14 | 498.83 | 259.66 | 239.17 | 0.00 | 0.00 |
May | 617.56 | 121.50 | 542.66 | 239.28 | 303.38 | 0.00 | 0.00 |
June | 621.20 | 75.06 | 508.06 | 195.44 | 312.62 | 0.00 | 0.00 |
July | 693.64 | 65.46 | 547.61 | 231.67 | 315.94 | 0.00 | 0.00 |
August | 597.39 | 78.37 | 487.16 | 214.55 | 272.62 | 0.00 | 0.00 |
September | 471.01 | 141.88 | 427.28 | 204.85 | 222.43 | 0.00 | 0.00 |
October | 287.99 | 233.55 | 315.24 | 157.07 | 158.18 | 0.00 | 0.00 |
November | 159.25 | 360.22 | 233.14 | 118.36 | 114.78 | 0.00 | 0.00 |
December | 107.95 | 558.92 | 230.54 | 124.80 | 105.74 | 0.00 | 0.00 |
Annual Sum or Average | 409.11 | 274.18 | 413.59 | 201.75 | 211.84 | 0.00 | 0.00 |
Minimum of Months | 107.95 | 65.46 | 230.54 | 118.36 | 105.74 | 0.00 | 0.00 |
Maximum of Months | 693.64 | 571.90 | 547.61 | 259.66 | 315.94 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 36.37 | 640.63 | 141.49 | 48.36 | 93.13 | 0.00 | 0.00 |
February | 113.70 | 512.21 | 226.67 | 84.82 | 141.84 | 0.00 | 0.00 |
March | 194.98 | 395.41 | 293.98 | 124.39 | 169.59 | 0.00 | 0.00 |
April | 325.74 | 239.46 | 377.18 | 157.70 | 219.48 | 0.00 | 0.00 |
May | 513.17 | 120.31 | 475.53 | 187.14 | 288.39 | 0.00 | 0.00 |
June | 554.70 | 76.80 | 471.76 | 169.73 | 302.03 | 0.00 | 0.00 |
July | 600.49 | 68.80 | 492.35 | 190.71 | 301.64 | 0.00 | 0.00 |
August | 466.07 | 83.60 | 397.92 | 146.89 | 251.04 | 0.00 | 0.00 |
September | 316.21 | 144.08 | 311.89 | 113.16 | 198.73 | 0.00 | 0.00 |
October | 149.46 | 238.36 | 200.89 | 64.11 | 136.78 | 0.00 | 0.00 |
November | 48.74 | 381.45 | 124.47 | 32.95 | 91.51 | 0.00 | 0.00 |
December | 17.72 | 621.06 | 108.52 | 29.60 | 78.92 | 0.00 | 0.00 |
Annual Sum or Average | 279.10 | 292.63 | 302.29 | 112.63 | 189.67 | 0.00 | 0.00 |
Minimum of Months | 17.72 | 68.80 | 108.52 | 29.60 | 78.92 | 0.00 | 0.00 |
Maximum of Months | 600.49 | 640.63 | 492.35 | 190.71 | 302.03 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 128.72 | 142.96 | 151.10 | 105.30 | 45.79 | 0.00 | 0.00 |
February | 174.74 | 130.98 | 188.64 | 126.92 | 61.72 | 0.00 | 0.00 |
March | 153.85 | 119.61 | 165.81 | 104.37 | 61.45 | 0.00 | 0.00 |
April | 149.34 | 88.49 | 151.45 | 82.11 | 69.34 | 0.00 | 0.00 |
May | 139.12 | 50.32 | 129.64 | 45.74 | 83.90 | 0.00 | 0.00 |
June | 129.79 | 34.87 | 113.91 | 30.01 | 83.90 | 0.00 | 0.00 |
July | 151.50 | 31.29 | 125.33 | 39.88 | 85.45 | 0.00 | 0.00 |
August | 156.32 | 37.46 | 132.99 | 55.29 | 77.70 | 0.00 | 0.00 |
September | 151.61 | 58.62 | 140.27 | 73.39 | 66.88 | 0.00 | 0.00 |
October | 118.55 | 85.38 | 124.72 | 74.35 | 50.37 | 0.00 | 0.00 |
November | 92.94 | 108.31 | 108.94 | 68.31 | 40.63 | 0.00 | 0.00 |
December | 92.78 | 133.63 | 116.05 | 76.15 | 39.91 | 0.00 | 0.00 |
Annual Sum or Average | 136.35 | 84.92 | 137.08 | 73.16 | 63.92 | 0.00 | 0.00 |
Minimum of Months | 92.78 | 31.29 | 108.94 | 30.01 | 39.91 | 0.00 | 0.00 |
Maximum of Months | 174.74 | 142.96 | 188.64 | 126.92 | 85.45 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.10 | 197.64 | 21.79 | 0.00 | 21.79 | 0.00 | 0.00 |
February | 2.19 | 157.05 | 33.47 | 0.00 | 33.47 | 0.00 | 0.00 |
March | 6.98 | 119.22 | 41.19 | 0.00 | 41.19 | 0.00 | 0.00 |
April | 27.30 | 68.87 | 54.17 | 0.56 | 53.61 | 0.00 | 0.00 |
May | 72.88 | 31.49 | 75.97 | 4.03 | 71.94 | 0.00 | 0.00 |
June | 99.09 | 19.97 | 84.90 | 9.45 | 75.45 | 0.00 | 0.00 |
July | 99.55 | 17.31 | 81.17 | 7.12 | 74.04 | 0.00 | 0.00 |
August | 68.92 | 21.50 | 61.63 | 1.17 | 60.46 | 0.00 | 0.00 |
September | 40.00 | 40.16 | 47.99 | 0.05 | 47.94 | 0.00 | 0.00 |
October | 13.30 | 70.20 | 33.27 | 0.00 | 33.27 | 0.00 | 0.00 |
November | 1.77 | 116.27 | 22.03 | 0.00 | 22.03 | 0.00 | 0.00 |
December | 0.00 | 189.80 | 18.46 | 0.00 | 18.46 | 0.00 | 0.00 |
Annual Sum or Average | 36.22 | 87.17 | 48.08 | 1.87 | 46.20 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 17.31 | 18.46 | 0.00 | 18.46 | 0.00 | 0.00 |
Maximum of Months | 99.55 | 197.64 | 84.90 | 9.45 | 75.45 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 163.90 | 568.41 | 300.08 | 177.75 | 122.33 | 0.00 | 0.00 |
February | 300.15 | 466.42 | 412.52 | 234.66 | 177.85 | 0.00 | 0.00 |
March | 364.59 | 372.27 | 447.45 | 251.21 | 196.24 | 0.00 | 0.00 |
April | 505.37 | 231.35 | 520.09 | 280.97 | 239.12 | 0.00 | 0.00 |
May | 583.29 | 113.79 | 521.29 | 215.61 | 305.68 | 0.00 | 0.00 |
June | 668.46 | 71.73 | 547.74 | 231.38 | 316.35 | 0.00 | 0.00 |
July | 698.78 | 61.87 | 554.60 | 237.06 | 317.54 | 0.00 | 0.00 |
August | 574.96 | 75.49 | 472.55 | 202.97 | 269.58 | 0.00 | 0.00 |
September | 459.89 | 137.91 | 421.30 | 202.10 | 219.20 | 0.00 | 0.00 |
October | 271.22 | 230.63 | 304.00 | 148.63 | 155.37 | 0.00 | 0.00 |
November | 154.44 | 356.46 | 231.05 | 116.99 | 114.06 | 0.00 | 0.00 |
December | 109.61 | 557.14 | 232.30 | 127.93 | 104.37 | 0.00 | 0.00 |
Annual Sum or Average | 404.95 | 269.45 | 413.58 | 201.95 | 211.63 | 0.00 | 0.00 |
Minimum of Months | 109.61 | 61.87 | 231.05 | 116.99 | 104.37 | 0.00 | 0.00 |
Maximum of Months | 698.78 | 568.41 | 554.60 | 280.97 | 317.54 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 26.56 | 632.35 | 138.41 | 46.10 | 92.32 | 0.00 | 0.00 |
February | 90.19 | 495.77 | 218.51 | 75.98 | 142.53 | 0.00 | 0.00 |
March | 177.57 | 381.69 | 291.63 | 120.73 | 170.90 | 0.00 | 0.00 |
April | 342.40 | 229.62 | 398.44 | 179.01 | 219.43 | 0.00 | 0.00 |
May | 483.18 | 113.60 | 454.16 | 163.47 | 290.69 | 0.00 | 0.00 |
June | 604.70 | 74.01 | 511.43 | 205.67 | 305.76 | 0.00 | 0.00 |
July | 607.23 | 65.66 | 499.35 | 196.10 | 303.25 | 0.00 | 0.00 |
August | 445.71 | 79.59 | 383.31 | 135.32 | 247.99 | 0.00 | 0.00 |
September | 305.92 | 138.45 | 305.91 | 110.41 | 195.50 | 0.00 | 0.00 |
October | 129.92 | 232.26 | 189.64 | 55.67 | 133.97 | 0.00 | 0.00 |
November | 41.53 | 375.45 | 122.38 | 31.59 | 90.79 | 0.00 | 0.00 |
December | 15.37 | 615.09 | 110.28 | 32.73 | 77.55 | 0.00 | 0.00 |
Annual Sum or Average | 273.46 | 285.30 | 302.28 | 112.83 | 189.46 | 0.00 | 0.00 |
Minimum of Months | 15.37 | 65.66 | 110.28 | 31.59 | 77.55 | 0.00 | 0.00 |
Maximum of Months | 607.23 | 632.35 | 511.43 | 205.67 | 305.76 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 206.82 | 713.95 | 374.59 | 228.16 | 146.43 | 0.00 | 0.00 |
February | 346.60 | 596.81 | 481.24 | 275.00 | 206.24 | 0.00 | 0.00 |
March | 343.71 | 483.14 | 448.51 | 226.14 | 222.37 | 0.00 | 0.00 |
April | 403.10 | 306.04 | 445.49 | 179.12 | 266.38 | 0.00 | 0.00 |
May | 480.90 | 153.07 | 445.46 | 107.83 | 337.63 | 0.00 | 0.00 |
June | 516.85 | 98.44 | 430.73 | 85.48 | 345.24 | 0.00 | 0.00 |
July | 560.99 | 90.36 | 447.40 | 101.85 | 345.55 | 0.00 | 0.00 |
August | 508.11 | 109.51 | 421.67 | 122.33 | 299.34 | 0.00 | 0.00 |
September | 436.93 | 188.57 | 407.87 | 159.11 | 248.76 | 0.00 | 0.00 |
October | 301.08 | 297.44 | 342.30 | 161.10 | 181.20 | 0.00 | 0.00 |
November | 192.35 | 457.51 | 283.76 | 148.01 | 135.75 | 0.00 | 0.00 |
December | 138.74 | 702.89 | 291.46 | 164.99 | 126.47 | 0.00 | 0.00 |
Annual Sum or Average | 369.68 | 348.74 | 401.16 | 162.57 | 238.59 | 0.00 | 0.00 |
Minimum of Months | 138.74 | 90.36 | 283.76 | 85.48 | 126.47 | 0.00 | 0.00 |
Maximum of Months | 560.99 | 713.95 | 481.24 | 275.00 | 345.55 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 168.42 | 573.11 | 303.16 | 180.01 | 123.14 | 0.00 | 0.00 |
February | 314.03 | 474.01 | 420.67 | 243.51 | 177.16 | 0.00 | 0.00 |
March | 375.76 | 379.91 | 449.81 | 254.87 | 194.93 | 0.00 | 0.00 |
April | 484.49 | 238.07 | 498.83 | 259.66 | 239.17 | 0.00 | 0.00 |
May | 614.26 | 120.65 | 542.66 | 239.28 | 303.38 | 0.00 | 0.00 |
June | 618.33 | 74.09 | 508.06 | 195.44 | 312.62 | 0.00 | 0.00 |
July | 690.63 | 64.35 | 547.61 | 231.67 | 315.94 | 0.00 | 0.00 |
August | 594.70 | 77.27 | 487.16 | 214.55 | 272.62 | 0.00 | 0.00 |
September | 469.00 | 140.62 | 427.28 | 204.85 | 222.43 | 0.00 | 0.00 |
October | 287.68 | 231.78 | 315.24 | 157.07 | 158.18 | 0.00 | 0.00 |
November | 159.44 | 359.03 | 233.14 | 118.36 | 114.78 | 0.00 | 0.00 |
December | 107.51 | 560.50 | 230.54 | 124.80 | 105.74 | 0.00 | 0.00 |
Annual Sum or Average | 407.50 | 273.59 | 413.59 | 201.75 | 211.84 | 0.00 | 0.00 |
Minimum of Months | 107.51 | 64.35 | 230.54 | 118.36 | 105.74 | 0.00 | 0.00 |
Maximum of Months | 690.63 | 573.11 | 547.61 | 259.66 | 315.94 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 36.15 | 642.12 | 141.49 | 48.36 | 93.13 | 0.00 | 0.00 |
February | 113.48 | 512.69 | 226.67 | 84.82 | 141.84 | 0.00 | 0.00 |
March | 194.60 | 394.88 | 293.98 | 124.39 | 169.59 | 0.00 | 0.00 |
April | 324.45 | 238.51 | 377.18 | 157.70 | 219.48 | 0.00 | 0.00 |
May | 509.39 | 120.65 | 475.53 | 187.14 | 288.39 | 0.00 | 0.00 |
June | 550.81 | 77.38 | 471.76 | 169.73 | 302.03 | 0.00 | 0.00 |
July | 596.86 | 69.24 | 492.35 | 190.71 | 301.64 | 0.00 | 0.00 |
August | 463.10 | 84.19 | 397.92 | 146.89 | 251.04 | 0.00 | 0.00 |
September | 314.77 | 143.35 | 311.89 | 113.16 | 198.73 | 0.00 | 0.00 |
October | 149.98 | 236.25 | 200.89 | 64.11 | 136.78 | 0.00 | 0.00 |
November | 49.29 | 380.13 | 124.47 | 32.95 | 91.51 | 0.00 | 0.00 |
December | 17.58 | 622.93 | 108.52 | 29.60 | 78.92 | 0.00 | 0.00 |
Annual Sum or Average | 277.68 | 292.64 | 302.29 | 112.63 | 189.67 | 0.00 | 0.00 |
Minimum of Months | 17.58 | 69.24 | 108.52 | 29.60 | 78.92 | 0.00 | 0.00 |
Maximum of Months | 596.86 | 642.12 | 492.35 | 190.71 | 302.03 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 224.39 | 290.29 | 277.05 | 193.09 | 83.97 | 0.00 | 0.00 |
February | 315.63 | 243.31 | 345.89 | 232.72 | 113.16 | 0.00 | 0.00 |
March | 287.21 | 198.44 | 304.04 | 191.37 | 112.67 | 0.00 | 0.00 |
April | 287.78 | 127.05 | 277.70 | 150.56 | 127.14 | 0.00 | 0.00 |
May | 275.48 | 62.72 | 237.70 | 83.86 | 153.84 | 0.00 | 0.00 |
June | 262.41 | 37.79 | 208.87 | 55.03 | 153.84 | 0.00 | 0.00 |
July | 301.38 | 32.05 | 229.81 | 73.13 | 156.68 | 0.00 | 0.00 |
August | 306.76 | 39.12 | 243.85 | 101.38 | 142.48 | 0.00 | 0.00 |
September | 294.94 | 73.38 | 257.19 | 134.56 | 122.63 | 0.00 | 0.00 |
October | 230.53 | 120.81 | 228.69 | 136.33 | 92.36 | 0.00 | 0.00 |
November | 173.45 | 183.83 | 199.75 | 125.26 | 74.50 | 0.00 | 0.00 |
December | 158.41 | 281.36 | 212.80 | 139.62 | 73.18 | 0.00 | 0.00 |
Annual Sum or Average | 259.46 | 140.39 | 251.35 | 134.14 | 117.21 | 0.00 | 0.00 |
Minimum of Months | 158.41 | 32.05 | 199.75 | 55.03 | 73.18 | 0.00 | 0.00 |
Maximum of Months | 315.63 | 290.29 | 345.89 | 232.72 | 156.68 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.32 | 1796.84 | 190.65 | 0.00 | 190.65 | 0.00 | 0.00 |
February | 11.70 | 1475.35 | 292.85 | 0.00 | 292.85 | 0.00 | 0.00 |
March | 43.50 | 1150.89 | 360.38 | 0.01 | 360.37 | 0.00 | 0.00 |
April | 198.39 | 688.22 | 473.88 | 4.87 | 469.02 | 0.00 | 0.00 |
May | 583.13 | 321.69 | 664.60 | 35.26 | 629.34 | 0.00 | 0.00 |
June | 814.81 | 209.08 | 742.73 | 82.63 | 660.10 | 0.00 | 0.00 |
July | 824.19 | 183.92 | 710.09 | 62.33 | 647.75 | 0.00 | 0.00 |
August | 558.53 | 231.01 | 539.20 | 10.26 | 528.94 | 0.00 | 0.00 |
September | 308.05 | 418.32 | 419.81 | 0.43 | 419.38 | 0.00 | 0.00 |
October | 89.71 | 707.59 | 291.02 | 0.00 | 291.02 | 0.00 | 0.00 |
November | 9.97 | 1142.12 | 192.69 | 0.00 | 192.69 | 0.00 | 0.00 |
December | 0.00 | 1750.31 | 161.53 | 0.00 | 161.53 | 0.00 | 0.00 |
Annual Sum or Average | 288.62 | 836.85 | 420.59 | 16.39 | 404.20 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 183.92 | 161.53 | 0.00 | 161.53 | 0.00 | 0.00 |
Maximum of Months | 824.19 | 1796.84 | 742.73 | 82.63 | 660.10 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.23 | 1826.00 | 190.65 | 0.00 | 190.65 | 0.00 | 0.00 |
February | 9.85 | 1503.85 | 292.85 | 0.00 | 292.85 | 0.00 | 0.00 |
March | 39.35 | 1175.55 | 360.38 | 0.01 | 360.37 | 0.00 | 0.00 |
April | 189.14 | 703.23 | 473.88 | 4.87 | 469.02 | 0.00 | 0.00 |
May | 573.37 | 328.12 | 664.60 | 35.26 | 629.34 | 0.00 | 0.00 |
June | 805.81 | 213.99 | 742.73 | 82.63 | 660.10 | 0.00 | 0.00 |
July | 816.56 | 188.28 | 710.09 | 62.33 | 647.75 | 0.00 | 0.00 |
August | 550.68 | 237.19 | 539.20 | 10.26 | 528.94 | 0.00 | 0.00 |
September | 299.61 | 428.02 | 419.81 | 0.43 | 419.38 | 0.00 | 0.00 |
October | 83.08 | 724.98 | 291.02 | 0.00 | 291.02 | 0.00 | 0.00 |
November | 8.77 | 1170.66 | 192.69 | 0.00 | 192.69 | 0.00 | 0.00 |
December | 0.00 | 1779.89 | 161.53 | 0.00 | 161.53 | 0.00 | 0.00 |
Annual Sum or Average | 283.12 | 853.82 | 420.59 | 16.39 | 404.20 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 188.28 | 161.53 | 0.00 | 161.53 | 0.00 | 0.00 |
Maximum of Months | 816.56 | 1826.00 | 742.73 | 82.63 | 660.10 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 190.28 | 1090.73 | 438.48 | 223.84 | 214.64 | 0.00 | 0.00 |
February | 413.18 | 907.57 | 631.00 | 310.64 | 320.36 | 0.00 | 0.00 |
March | 592.17 | 727.82 | 739.05 | 371.93 | 367.12 | 0.00 | 0.00 |
April | 946.54 | 461.56 | 918.48 | 459.95 | 458.53 | 0.00 | 0.00 |
May | 1223.31 | 237.74 | 975.39 | 379.05 | 596.34 | 0.00 | 0.00 |
June | 1446.90 | 159.55 | 1059.11 | 437.02 | 622.08 | 0.00 | 0.00 |
July | 1493.29 | 137.67 | 1053.89 | 433.13 | 620.76 | 0.00 | 0.00 |
August | 1183.54 | 160.43 | 855.82 | 338.27 | 517.54 | 0.00 | 0.00 |
September | 889.78 | 273.91 | 727.17 | 312.49 | 414.68 | 0.00 | 0.00 |
October | 470.55 | 447.49 | 493.62 | 204.30 | 289.32 | 0.00 | 0.00 |
November | 217.50 | 704.53 | 353.42 | 148.58 | 204.84 | 0.00 | 0.00 |
December | 119.30 | 1079.13 | 342.57 | 160.66 | 181.91 | 0.00 | 0.00 |
Annual Sum or Average | 767.22 | 530.71 | 715.83 | 314.76 | 401.07 | 0.00 | 0.00 |
Minimum of Months | 119.30 | 137.67 | 342.57 | 148.58 | 181.91 | 0.00 | 0.00 |
Maximum of Months | 1493.29 | 1090.73 | 1059.11 | 459.95 | 622.08 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 487.00 | 1250.58 | 770.60 | 491.51 | 279.09 | 0.00 | 0.00 |
February | 760.34 | 1053.09 | 980.87 | 592.41 | 388.45 | 0.00 | 0.00 |
March | 730.38 | 858.89 | 897.48 | 487.14 | 410.34 | 0.00 | 0.00 |
April | 811.79 | 547.13 | 869.34 | 384.92 | 484.42 | 0.00 | 0.00 |
May | 899.28 | 278.37 | 832.91 | 225.57 | 607.35 | 0.00 | 0.00 |
June | 931.94 | 179.61 | 786.29 | 168.40 | 617.89 | 0.00 | 0.00 |
July | 1029.68 | 164.26 | 828.42 | 207.52 | 620.90 | 0.00 | 0.00 |
August | 965.77 | 199.84 | 805.57 | 261.57 | 544.00 | 0.00 | 0.00 |
September | 863.21 | 337.50 | 798.61 | 342.68 | 455.94 | 0.00 | 0.00 |
October | 618.90 | 532.05 | 681.91 | 347.05 | 334.86 | 0.00 | 0.00 |
November | 417.90 | 814.36 | 574.54 | 318.84 | 255.70 | 0.00 | 0.00 |
December | 331.05 | 1236.02 | 597.06 | 355.41 | 241.65 | 0.00 | 0.00 |
Annual Sum or Average | 736.87 | 619.08 | 784.00 | 347.07 | 436.93 | 0.00 | 0.00 |
Minimum of Months | 331.05 | 164.26 | 574.54 | 168.40 | 241.65 | 0.00 | 0.00 |
Maximum of Months | 1029.68 | 1250.58 | 980.87 | 592.41 | 620.90 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.214901E+10 | 0.246564E+10 | 0.255906E+10 | 0.178349E+10 | 0.775570E+09 | 0.00 | 0.00 |
February | 0.270159E+10 | 0.190848E+10 | 0.288571E+10 | 0.194160E+10 | 0.944108E+09 | 0.00 | 0.00 |
March | 0.269418E+10 | 0.174914E+10 | 0.280832E+10 | 0.176763E+10 | 0.104070E+10 | 0.00 | 0.00 |
April | 0.260168E+10 | 0.110328E+10 | 0.248228E+10 | 0.134581E+10 | 0.113646E+10 | 0.00 | 0.00 |
May | 0.255396E+10 | 0.592137E+09 | 0.219561E+10 | 0.774627E+09 | 0.142098E+10 | 0.00 | 0.00 |
June | 0.233050E+10 | 0.363643E+09 | 0.186699E+10 | 0.491871E+09 | 0.137512E+10 | 0.00 | 0.00 |
July | 0.274840E+10 | 0.343252E+09 | 0.212271E+10 | 0.675472E+09 | 0.144724E+10 | 0.00 | 0.00 |
August | 0.282132E+10 | 0.403936E+09 | 0.225239E+10 | 0.936387E+09 | 0.131600E+10 | 0.00 | 0.00 |
September | 0.265167E+10 | 0.661053E+09 | 0.229900E+10 | 0.120281E+10 | 0.109620E+10 | 0.00 | 0.00 |
October | 0.215010E+10 | 0.108886E+10 | 0.211236E+10 | 0.125929E+10 | 0.853077E+09 | 0.00 | 0.00 |
November | 0.158430E+10 | 0.157254E+10 | 0.178557E+10 | 0.111964E+10 | 0.665932E+09 | 0.00 | 0.00 |
December | 0.152154E+10 | 0.240879E+10 | 0.196556E+10 | 0.128965E+10 | 0.675911E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.285082E+11 | 0.146607E+11 | 0.273356E+11 | 0.145883E+11 | 0.127473E+11 | 0.00 | 0.00 |
Minimum of Months | 0.152154E+10 | 0.343252E+09 | 0.178557E+10 | 0.491871E+09 | 0.665932E+09 | 0.00 | 0.00 |
Maximum of Months | 0.282132E+10 | 0.246564E+10 | 0.288571E+10 | 0.194160E+10 | 0.144724E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.600776E+10 | 0.699964E+10 | 0.720613E+10 | 0.502218E+10 | 0.218395E+10 | 0.00 | 0.00 |
February | 0.755080E+10 | 0.543887E+10 | 0.812596E+10 | 0.546742E+10 | 0.265854E+10 | 0.00 | 0.00 |
March | 0.752410E+10 | 0.503407E+10 | 0.790805E+10 | 0.497752E+10 | 0.293053E+10 | 0.00 | 0.00 |
April | 0.725468E+10 | 0.324147E+10 | 0.698993E+10 | 0.378972E+10 | 0.320021E+10 | 0.00 | 0.00 |
May | 0.709448E+10 | 0.179867E+10 | 0.618268E+10 | 0.218130E+10 | 0.400138E+10 | 0.00 | 0.00 |
June | 0.645542E+10 | 0.113670E+10 | 0.525733E+10 | 0.138508E+10 | 0.387226E+10 | 0.00 | 0.00 |
July | 0.764832E+10 | 0.106127E+10 | 0.597742E+10 | 0.190208E+10 | 0.407534E+10 | 0.00 | 0.00 |
August | 0.785792E+10 | 0.126477E+10 | 0.634258E+10 | 0.263680E+10 | 0.370578E+10 | 0.00 | 0.00 |
September | 0.738715E+10 | 0.201866E+10 | 0.647384E+10 | 0.338702E+10 | 0.308682E+10 | 0.00 | 0.00 |
October | 0.599374E+10 | 0.320778E+10 | 0.594828E+10 | 0.354607E+10 | 0.240221E+10 | 0.00 | 0.00 |
November | 0.441555E+10 | 0.451776E+10 | 0.502804E+10 | 0.315282E+10 | 0.187522E+10 | 0.00 | 0.00 |
December | 0.424633E+10 | 0.683391E+10 | 0.553489E+10 | 0.363157E+10 | 0.190332E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.794363E+11 | 0.425536E+11 | 0.769751E+11 | 0.410796E+11 | 0.358956E+11 | 0.00 | 0.00 |
Minimum of Months | 0.424633E+10 | 0.106127E+10 | 0.502804E+10 | 0.138508E+10 | 0.187522E+10 | 0.00 | 0.00 |
Maximum of Months | 0.785792E+10 | 0.699964E+10 | 0.812596E+10 | 0.546742E+10 | 0.407534E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.789850E+10 | 0.944816E+10 | 0.936118E+10 | 0.652410E+10 | 0.283708E+10 | 0.00 | 0.00 |
February | 0.995999E+10 | 0.733674E+10 | 0.105561E+11 | 0.710249E+10 | 0.345360E+10 | 0.00 | 0.00 |
March | 0.993238E+10 | 0.680782E+10 | 0.102730E+11 | 0.646608E+10 | 0.380693E+10 | 0.00 | 0.00 |
April | 0.956973E+10 | 0.442127E+10 | 0.908032E+10 | 0.492306E+10 | 0.415725E+10 | 0.00 | 0.00 |
May | 0.934866E+10 | 0.246170E+10 | 0.803166E+10 | 0.283363E+10 | 0.519802E+10 | 0.00 | 0.00 |
June | 0.850252E+10 | 0.156577E+10 | 0.682958E+10 | 0.179929E+10 | 0.503028E+10 | 0.00 | 0.00 |
July | 0.100903E+11 | 0.143761E+10 | 0.776501E+10 | 0.247092E+10 | 0.529410E+10 | 0.00 | 0.00 |
August | 0.103527E+11 | 0.171700E+10 | 0.823937E+10 | 0.342536E+10 | 0.481402E+10 | 0.00 | 0.00 |
September | 0.971041E+10 | 0.277387E+10 | 0.840988E+10 | 0.439993E+10 | 0.400995E+10 | 0.00 | 0.00 |
October | 0.785557E+10 | 0.442395E+10 | 0.772715E+10 | 0.460654E+10 | 0.312061E+10 | 0.00 | 0.00 |
November | 0.579409E+10 | 0.620100E+10 | 0.653171E+10 | 0.409570E+10 | 0.243602E+10 | 0.00 | 0.00 |
December | 0.556281E+10 | 0.927880E+10 | 0.719013E+10 | 0.471761E+10 | 0.247252E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.104578E+12 | 0.578737E+11 | 0.999951E+11 | 0.533647E+11 | 0.466304E+11 | 0.00 | 0.00 |
Minimum of Months | 0.556281E+10 | 0.143761E+10 | 0.653171E+10 | 0.179929E+10 | 0.243602E+10 | 0.00 | 0.00 |
Maximum of Months | 0.103527E+11 | 0.944816E+10 | 0.105561E+11 | 0.710249E+10 | 0.529410E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.452628E+09 | 0.153179E+10 | 0.811979E+09 | 0.482150E+09 | 0.329829E+09 | 0.00 | 0.00 |
February | 0.762309E+09 | 0.114661E+10 | 0.101769E+10 | 0.589096E+09 | 0.428596E+09 | 0.00 | 0.00 |
March | 0.100903E+10 | 0.101907E+10 | 0.120476E+10 | 0.682657E+09 | 0.522105E+09 | 0.00 | 0.00 |
April | 0.126142E+10 | 0.619861E+09 | 0.129296E+10 | 0.673039E+09 | 0.619921E+09 | 0.00 | 0.00 |
May | 0.165408E+10 | 0.325429E+09 | 0.145346E+10 | 0.640897E+09 | 0.812562E+09 | 0.00 | 0.00 |
June | 0.161016E+10 | 0.194544E+09 | 0.131690E+10 | 0.506592E+09 | 0.810308E+09 | 0.00 | 0.00 |
July | 0.185784E+10 | 0.175321E+09 | 0.146671E+10 | 0.620496E+09 | 0.846213E+09 | 0.00 | 0.00 |
August | 0.160004E+10 | 0.209914E+09 | 0.130482E+10 | 0.574637E+09 | 0.730180E+09 | 0.00 | 0.00 |
September | 0.122085E+10 | 0.367747E+09 | 0.110752E+10 | 0.530973E+09 | 0.576547E+09 | 0.00 | 0.00 |
October | 0.771344E+09 | 0.625553E+09 | 0.844350E+09 | 0.420688E+09 | 0.423662E+09 | 0.00 | 0.00 |
November | 0.412777E+09 | 0.933681E+09 | 0.604307E+09 | 0.306789E+09 | 0.297519E+09 | 0.00 | 0.00 |
December | 0.289139E+09 | 0.149700E+10 | 0.617484E+09 | 0.334278E+09 | 0.283207E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.129016E+11 | 0.864653E+10 | 0.130429E+11 | 0.636229E+10 | 0.668065E+10 | 0.00 | 0.00 |
Minimum of Months | 0.289139E+09 | 0.175321E+09 | 0.604307E+09 | 0.306789E+09 | 0.283207E+09 | 0.00 | 0.00 |
Maximum of Months | 0.185784E+10 | 0.153179E+10 | 0.146671E+10 | 0.682657E+09 | 0.846213E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 97421561.14 | 0.171585E+10 | 0.378959E+09 | 0.129524E+09 | 0.249434E+09 | 0.00 | 0.00 |
February | 0.275063E+09 | 0.123913E+10 | 0.548349E+09 | 0.205208E+09 | 0.343141E+09 | 0.00 | 0.00 |
March | 0.522230E+09 | 0.105908E+10 | 0.787404E+09 | 0.333172E+09 | 0.454232E+09 | 0.00 | 0.00 |
April | 0.844326E+09 | 0.620680E+09 | 0.977647E+09 | 0.408751E+09 | 0.568897E+09 | 0.00 | 0.00 |
May | 0.137446E+10 | 0.322230E+09 | 0.127365E+10 | 0.501231E+09 | 0.772420E+09 | 0.00 | 0.00 |
June | 0.143778E+10 | 0.199055E+09 | 0.122279E+10 | 0.439939E+09 | 0.782853E+09 | 0.00 | 0.00 |
July | 0.160835E+10 | 0.184276E+09 | 0.131872E+10 | 0.510795E+09 | 0.807924E+09 | 0.00 | 0.00 |
August | 0.124833E+10 | 0.223906E+09 | 0.106580E+10 | 0.393423E+09 | 0.672376E+09 | 0.00 | 0.00 |
September | 0.819606E+09 | 0.373455E+09 | 0.808423E+09 | 0.293318E+09 | 0.515104E+09 | 0.00 | 0.00 |
October | 0.400302E+09 | 0.638429E+09 | 0.538056E+09 | 0.171705E+09 | 0.366351E+09 | 0.00 | 0.00 |
November | 0.126325E+09 | 0.988714E+09 | 0.322624E+09 | 85417046.86 | 0.237207E+09 | 0.00 | 0.00 |
December | 47457779.46 | 0.166346E+10 | 0.290667E+09 | 79291862.18 | 0.211376E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.880165E+10 | 0.922826E+10 | 0.953309E+10 | 0.355178E+10 | 0.598132E+10 | 0.00 | 0.00 |
Minimum of Months | 47457779.46 | 0.184276E+09 | 0.290667E+09 | 79291862.18 | 0.211376E+09 | 0.00 | 0.00 |
Maximum of Months | 0.160835E+10 | 0.171585E+10 | 0.131872E+10 | 0.510795E+09 | 0.807924E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.344774E+09 | 0.382911E+09 | 0.404696E+09 | 0.282045E+09 | 0.122651E+09 | 0.00 | 0.00 |
February | 0.422724E+09 | 0.316870E+09 | 0.456353E+09 | 0.307049E+09 | 0.149304E+09 | 0.00 | 0.00 |
March | 0.412062E+09 | 0.320373E+09 | 0.444116E+09 | 0.279536E+09 | 0.164579E+09 | 0.00 | 0.00 |
April | 0.387098E+09 | 0.229373E+09 | 0.392555E+09 | 0.212830E+09 | 0.179725E+09 | 0.00 | 0.00 |
May | 0.372615E+09 | 0.134768E+09 | 0.347220E+09 | 0.122501E+09 | 0.224719E+09 | 0.00 | 0.00 |
June | 0.336424E+09 | 90373954.23 | 0.295253E+09 | 77785603.32 | 0.217467E+09 | 0.00 | 0.00 |
July | 0.405773E+09 | 83797312.91 | 0.335693E+09 | 0.106821E+09 | 0.228873E+09 | 0.00 | 0.00 |
August | 0.418674E+09 | 0.100341E+09 | 0.356200E+09 | 0.148082E+09 | 0.208118E+09 | 0.00 | 0.00 |
September | 0.392968E+09 | 0.151942E+09 | 0.363571E+09 | 0.190214E+09 | 0.173356E+09 | 0.00 | 0.00 |
October | 0.317527E+09 | 0.228679E+09 | 0.334055E+09 | 0.199146E+09 | 0.134908E+09 | 0.00 | 0.00 |
November | 0.240911E+09 | 0.280749E+09 | 0.282374E+09 | 0.177062E+09 | 0.105312E+09 | 0.00 | 0.00 |
December | 0.248499E+09 | 0.357915E+09 | 0.310839E+09 | 0.203948E+09 | 0.106891E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.430005E+10 | 0.267809E+10 | 0.432292E+10 | 0.230702E+10 | 0.201590E+10 | 0.00 | 0.00 |
Minimum of Months | 0.240911E+09 | 83797312.91 | 0.282374E+09 | 77785603.32 | 0.105312E+09 | 0.00 | 0.00 |
Maximum of Months | 0.422724E+09 | 0.382911E+09 | 0.456353E+09 | 0.307049E+09 | 0.228873E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 266634.48 | 0.529365E+09 | 58367319.83 | 0.00 | 58367319.83 | 0.00 | 0.00 |
February | 5301061.09 | 0.379936E+09 | 80980322.72 | 0.00 | 80980322.72 | 0.00 | 0.00 |
March | 18690853.65 | 0.319329E+09 | 0.110332E+09 | 4218.19 | 0.110328E+09 | 0.00 | 0.00 |
April | 70752039.02 | 0.178510E+09 | 0.140402E+09 | 1442095.54 | 0.138960E+09 | 0.00 | 0.00 |
May | 0.195210E+09 | 84352104.66 | 0.203471E+09 | 10794416.27 | 0.192676E+09 | 0.00 | 0.00 |
June | 0.256829E+09 | 51771251.54 | 0.220055E+09 | 24482516.34 | 0.195573E+09 | 0.00 | 0.00 |
July | 0.266645E+09 | 46370930.32 | 0.217397E+09 | 19083501.21 | 0.198313E+09 | 0.00 | 0.00 |
August | 0.184597E+09 | 57588718.29 | 0.165078E+09 | 3140560.24 | 0.161937E+09 | 0.00 | 0.00 |
September | 0.103673E+09 | 0.104088E+09 | 0.124382E+09 | 128388.17 | 0.124253E+09 | 0.00 | 0.00 |
October | 35609916.67 | 0.188032E+09 | 89098491.50 | 0.00 | 89098491.50 | 0.00 | 0.00 |
November | 4588572.98 | 0.301372E+09 | 57091439.30 | 0.00 | 57091439.30 | 0.00 | 0.00 |
December | 0.00 | 0.508360E+09 | 49453425.81 | 0.00 | 49453425.81 | 0.00 | 0.00 |
Annual Sum or Average | 0.114216E+10 | 0.274907E+10 | 0.151611E+10 | 59075695.98 | 0.145703E+10 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 46370930.32 | 49453425.81 | 0.00 | 49453425.81 | 0.00 | 0.00 |
Maximum of Months | 0.266645E+09 | 0.529365E+09 | 0.220055E+09 | 24482516.34 | 0.198313E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.438984E+09 | 0.152242E+10 | 0.803744E+09 | 0.476088E+09 | 0.327656E+09 | 0.00 | 0.00 |
February | 0.726113E+09 | 0.112836E+10 | 0.997957E+09 | 0.567701E+09 | 0.430256E+09 | 0.00 | 0.00 |
March | 0.976523E+09 | 0.997092E+09 | 0.119846E+10 | 0.672848E+09 | 0.525610E+09 | 0.00 | 0.00 |
April | 0.130993E+10 | 0.599658E+09 | 0.134807E+10 | 0.728269E+09 | 0.619798E+09 | 0.00 | 0.00 |
May | 0.156229E+10 | 0.304769E+09 | 0.139622E+10 | 0.577492E+09 | 0.818725E+09 | 0.00 | 0.00 |
June | 0.173265E+10 | 0.185935E+09 | 0.141973E+10 | 0.599743E+09 | 0.819988E+09 | 0.00 | 0.00 |
July | 0.187160E+10 | 0.165721E+09 | 0.148544E+10 | 0.634931E+09 | 0.850508E+09 | 0.00 | 0.00 |
August | 0.153996E+10 | 0.202192E+09 | 0.126568E+10 | 0.543647E+09 | 0.722031E+09 | 0.00 | 0.00 |
September | 0.119203E+10 | 0.357474E+09 | 0.109200E+10 | 0.523838E+09 | 0.568166E+09 | 0.00 | 0.00 |
October | 0.726430E+09 | 0.617712E+09 | 0.814234E+09 | 0.398101E+09 | 0.416133E+09 | 0.00 | 0.00 |
November | 0.400307E+09 | 0.923936E+09 | 0.598885E+09 | 0.303248E+09 | 0.295637E+09 | 0.00 | 0.00 |
December | 0.293586E+09 | 0.149225E+10 | 0.622191E+09 | 0.342657E+09 | 0.279534E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.127704E+11 | 0.849753E+10 | 0.130426E+11 | 0.636856E+10 | 0.667404E+10 | 0.00 | 0.00 |
Minimum of Months | 0.293586E+09 | 0.165721E+09 | 0.598885E+09 | 0.303248E+09 | 0.279534E+09 | 0.00 | 0.00 |
Maximum of Months | 0.187160E+10 | 0.152242E+10 | 0.148544E+10 | 0.728269E+09 | 0.850508E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 71137726.79 | 0.169369E+10 | 0.370723E+09 | 0.123462E+09 | 0.247261E+09 | 0.00 | 0.00 |
February | 0.218197E+09 | 0.119937E+10 | 0.528614E+09 | 0.183814E+09 | 0.344801E+09 | 0.00 | 0.00 |
March | 0.475609E+09 | 0.102232E+10 | 0.781101E+09 | 0.323363E+09 | 0.457737E+09 | 0.00 | 0.00 |
April | 0.887502E+09 | 0.595162E+09 | 0.103276E+10 | 0.463981E+09 | 0.568774E+09 | 0.00 | 0.00 |
May | 0.129416E+10 | 0.304268E+09 | 0.121641E+10 | 0.437826E+09 | 0.778584E+09 | 0.00 | 0.00 |
June | 0.156739E+10 | 0.191836E+09 | 0.132562E+10 | 0.533091E+09 | 0.792533E+09 | 0.00 | 0.00 |
July | 0.162639E+10 | 0.175862E+09 | 0.133745E+10 | 0.525230E+09 | 0.812220E+09 | 0.00 | 0.00 |
August | 0.119379E+10 | 0.213176E+09 | 0.102666E+10 | 0.362432E+09 | 0.664227E+09 | 0.00 | 0.00 |
September | 0.792945E+09 | 0.358857E+09 | 0.792907E+09 | 0.286183E+09 | 0.506723E+09 | 0.00 | 0.00 |
October | 0.347979E+09 | 0.622088E+09 | 0.507940E+09 | 0.149118E+09 | 0.358822E+09 | 0.00 | 0.00 |
November | 0.107640E+09 | 0.973154E+09 | 0.317202E+09 | 81876671.53 | 0.235325E+09 | 0.00 | 0.00 |
December | 41162563.06 | 0.164745E+10 | 0.295375E+09 | 87671849.66 | 0.207703E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.862390E+10 | 0.899724E+10 | 0.953276E+10 | 0.355805E+10 | 0.597471E+10 | 0.00 | 0.00 |
Minimum of Months | 41162563.06 | 0.175862E+09 | 0.295375E+09 | 81876671.53 | 0.207703E+09 | 0.00 | 0.00 |
Maximum of Months | 0.162639E+10 | 0.169369E+10 | 0.133745E+10 | 0.533091E+09 | 0.812220E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.553958E+09 | 0.191224E+10 | 0.100331E+10 | 0.611112E+09 | 0.392194E+09 | 0.00 | 0.00 |
February | 0.838504E+09 | 0.144380E+10 | 0.116422E+10 | 0.665290E+09 | 0.498931E+09 | 0.00 | 0.00 |
March | 0.920601E+09 | 0.129405E+10 | 0.120129E+10 | 0.605687E+09 | 0.595605E+09 | 0.00 | 0.00 |
April | 0.104482E+10 | 0.793268E+09 | 0.115471E+10 | 0.464267E+09 | 0.690447E+09 | 0.00 | 0.00 |
May | 0.128803E+10 | 0.409979E+09 | 0.119312E+10 | 0.288811E+09 | 0.904305E+09 | 0.00 | 0.00 |
June | 0.133968E+10 | 0.255145E+09 | 0.111644E+10 | 0.221577E+09 | 0.894867E+09 | 0.00 | 0.00 |
July | 0.150257E+10 | 0.242021E+09 | 0.119831E+10 | 0.272792E+09 | 0.925516E+09 | 0.00 | 0.00 |
August | 0.136092E+10 | 0.293307E+09 | 0.112940E+10 | 0.327657E+09 | 0.801744E+09 | 0.00 | 0.00 |
September | 0.113252E+10 | 0.488772E+09 | 0.105721E+10 | 0.412420E+09 | 0.644789E+09 | 0.00 | 0.00 |
October | 0.806419E+09 | 0.796671E+09 | 0.916821E+09 | 0.431495E+09 | 0.485326E+09 | 0.00 | 0.00 |
November | 0.498569E+09 | 0.118588E+10 | 0.735506E+09 | 0.383644E+09 | 0.351862E+09 | 0.00 | 0.00 |
December | 0.371600E+09 | 0.188262E+10 | 0.780633E+09 | 0.441899E+09 | 0.338735E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.116582E+11 | 0.109977E+11 | 0.126510E+11 | 0.512665E+10 | 0.752432E+10 | 0.00 | 0.00 |
Minimum of Months | 0.371600E+09 | 0.242021E+09 | 0.735506E+09 | 0.221577E+09 | 0.338735E+09 | 0.00 | 0.00 |
Maximum of Months | 0.150257E+10 | 0.191224E+10 | 0.120129E+10 | 0.665290E+09 | 0.925516E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.451101E+09 | 0.153501E+10 | 0.811979E+09 | 0.482150E+09 | 0.329829E+09 | 0.00 | 0.00 |
February | 0.759696E+09 | 0.114672E+10 | 0.101769E+10 | 0.589096E+09 | 0.428596E+09 | 0.00 | 0.00 |
March | 0.100642E+10 | 0.101755E+10 | 0.120476E+10 | 0.682657E+09 | 0.522105E+09 | 0.00 | 0.00 |
April | 0.125579E+10 | 0.617072E+09 | 0.129296E+10 | 0.673039E+09 | 0.619921E+09 | 0.00 | 0.00 |
May | 0.164524E+10 | 0.323154E+09 | 0.145346E+10 | 0.640897E+09 | 0.812562E+09 | 0.00 | 0.00 |
June | 0.160270E+10 | 0.192035E+09 | 0.131690E+10 | 0.506592E+09 | 0.810308E+09 | 0.00 | 0.00 |
July | 0.184979E+10 | 0.172354E+09 | 0.146671E+10 | 0.620496E+09 | 0.846213E+09 | 0.00 | 0.00 |
August | 0.159284E+10 | 0.206964E+09 | 0.130482E+10 | 0.574637E+09 | 0.730180E+09 | 0.00 | 0.00 |
September | 0.121565E+10 | 0.364475E+09 | 0.110752E+10 | 0.530973E+09 | 0.576547E+09 | 0.00 | 0.00 |
October | 0.770527E+09 | 0.620805E+09 | 0.844350E+09 | 0.420688E+09 | 0.423662E+09 | 0.00 | 0.00 |
November | 0.413268E+09 | 0.930599E+09 | 0.604307E+09 | 0.306789E+09 | 0.297519E+09 | 0.00 | 0.00 |
December | 0.287947E+09 | 0.150124E+10 | 0.617484E+09 | 0.334278E+09 | 0.283207E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.128510E+11 | 0.862797E+10 | 0.130429E+11 | 0.636229E+10 | 0.668065E+10 | 0.00 | 0.00 |
Minimum of Months | 0.287947E+09 | 0.172354E+09 | 0.604307E+09 | 0.306789E+09 | 0.283207E+09 | 0.00 | 0.00 |
Maximum of Months | 0.184979E+10 | 0.153501E+10 | 0.146671E+10 | 0.682657E+09 | 0.846213E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 96829371.39 | 0.171986E+10 | 0.378959E+09 | 0.129524E+09 | 0.249434E+09 | 0.00 | 0.00 |
February | 0.274531E+09 | 0.124030E+10 | 0.548349E+09 | 0.205208E+09 | 0.343141E+09 | 0.00 | 0.00 |
March | 0.521214E+09 | 0.105764E+10 | 0.787404E+09 | 0.333172E+09 | 0.454232E+09 | 0.00 | 0.00 |
April | 0.840980E+09 | 0.618230E+09 | 0.977647E+09 | 0.408751E+09 | 0.568897E+09 | 0.00 | 0.00 |
May | 0.136434E+10 | 0.323151E+09 | 0.127365E+10 | 0.501231E+09 | 0.772420E+09 | 0.00 | 0.00 |
June | 0.142771E+10 | 0.200562E+09 | 0.122279E+10 | 0.439939E+09 | 0.782853E+09 | 0.00 | 0.00 |
July | 0.159864E+10 | 0.185462E+09 | 0.131872E+10 | 0.510795E+09 | 0.807924E+09 | 0.00 | 0.00 |
August | 0.124035E+10 | 0.225503E+09 | 0.106580E+10 | 0.393423E+09 | 0.672376E+09 | 0.00 | 0.00 |
September | 0.815890E+09 | 0.371559E+09 | 0.808423E+09 | 0.293318E+09 | 0.515104E+09 | 0.00 | 0.00 |
October | 0.401697E+09 | 0.632764E+09 | 0.538056E+09 | 0.171705E+09 | 0.366351E+09 | 0.00 | 0.00 |
November | 0.127762E+09 | 0.985310E+09 | 0.322624E+09 | 85417046.86 | 0.237207E+09 | 0.00 | 0.00 |
December | 47081706.61 | 0.166846E+10 | 0.290667E+09 | 79291862.18 | 0.211376E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.875703E+10 | 0.922880E+10 | 0.953309E+10 | 0.355178E+10 | 0.598132E+10 | 0.00 | 0.00 |
Minimum of Months | 47081706.61 | 0.185462E+09 | 0.290667E+09 | 79291862.18 | 0.211376E+09 | 0.00 | 0.00 |
Maximum of Months | 0.159864E+10 | 0.171986E+10 | 0.131872E+10 | 0.510795E+09 | 0.807924E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.601019E+09 | 0.777508E+09 | 0.742054E+09 | 0.517160E+09 | 0.224894E+09 | 0.00 | 0.00 |
February | 0.763581E+09 | 0.588619E+09 | 0.836774E+09 | 0.563008E+09 | 0.273766E+09 | 0.00 | 0.00 |
March | 0.769272E+09 | 0.531503E+09 | 0.814335E+09 | 0.512561E+09 | 0.301774E+09 | 0.00 | 0.00 |
April | 0.745930E+09 | 0.329302E+09 | 0.719792E+09 | 0.390247E+09 | 0.329545E+09 | 0.00 | 0.00 |
May | 0.737845E+09 | 0.167996E+09 | 0.636666E+09 | 0.224620E+09 | 0.412047E+09 | 0.00 | 0.00 |
June | 0.680171E+09 | 97942750.48 | 0.541379E+09 | 0.142628E+09 | 0.398750E+09 | 0.00 | 0.00 |
July | 0.807226E+09 | 85844859.20 | 0.615530E+09 | 0.195867E+09 | 0.419663E+09 | 0.00 | 0.00 |
August | 0.821618E+09 | 0.104773E+09 | 0.653132E+09 | 0.271525E+09 | 0.381606E+09 | 0.00 | 0.00 |
September | 0.764495E+09 | 0.190213E+09 | 0.666647E+09 | 0.348779E+09 | 0.317868E+09 | 0.00 | 0.00 |
October | 0.617452E+09 | 0.323578E+09 | 0.612526E+09 | 0.365157E+09 | 0.247369E+09 | 0.00 | 0.00 |
November | 0.449594E+09 | 0.476493E+09 | 0.517764E+09 | 0.324662E+09 | 0.193102E+09 | 0.00 | 0.00 |
December | 0.424277E+09 | 0.753591E+09 | 0.569956E+09 | 0.373961E+09 | 0.195996E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.818248E+10 | 0.442736E+10 | 0.792655E+10 | 0.423018E+10 | 0.369638E+10 | 0.00 | 0.00 |
Minimum of Months | 0.424277E+09 | 85844859.20 | 0.517764E+09 | 0.142628E+09 | 0.193102E+09 | 0.00 | 0.00 |
Maximum of Months | 0.821618E+09 | 0.777508E+09 | 0.836774E+09 | 0.563008E+09 | 0.419663E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 851337.29 | 0.481265E+10 | 0.510627E+09 | 0.00 | 0.510627E+09 | 0.00 | 0.00 |
February | 28309527.75 | 0.356916E+10 | 0.708457E+09 | 0.00 | 0.708457E+09 | 0.00 | 0.00 |
March | 0.116503E+09 | 0.308255E+10 | 0.965244E+09 | 36902.88 | 0.965208E+09 | 0.00 | 0.00 |
April | 0.514222E+09 | 0.178387E+10 | 0.122831E+10 | 12616185.78 | 0.121569E+10 | 0.00 | 0.00 |
May | 0.156186E+10 | 0.861621E+09 | 0.178006E+10 | 94435047.30 | 0.168563E+10 | 0.00 | 0.00 |
June | 0.211200E+10 | 0.541937E+09 | 0.192515E+10 | 0.214186E+09 | 0.171097E+10 | 0.00 | 0.00 |
July | 0.220751E+10 | 0.492616E+09 | 0.190190E+10 | 0.166952E+09 | 0.173495E+10 | 0.00 | 0.00 |
August | 0.149595E+10 | 0.618740E+09 | 0.144419E+10 | 27475219.40 | 0.141671E+10 | 0.00 | 0.00 |
September | 0.798475E+09 | 0.108430E+10 | 0.108815E+10 | 1123205.09 | 0.108703E+10 | 0.00 | 0.00 |
October | 0.240274E+09 | 0.189521E+10 | 0.779479E+09 | 0.00 | 0.779479E+09 | 0.00 | 0.00 |
November | 25829505.45 | 0.296036E+10 | 0.499465E+09 | 0.00 | 0.499465E+09 | 0.00 | 0.00 |
December | 0.00 | 0.468803E+10 | 0.432644E+09 | 0.00 | 0.432644E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.910179E+10 | 0.263910E+11 | 0.132637E+11 | 0.516824E+09 | 0.127469E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.492616E+09 | 0.432644E+09 | 0.00 | 0.432644E+09 | 0.00 | 0.00 |
Maximum of Months | 0.220751E+10 | 0.481265E+10 | 0.192515E+10 | 0.214186E+09 | 0.173495E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 607071.82 | 0.489076E+10 | 0.510627E+09 | 0.00 | 0.510627E+09 | 0.00 | 0.00 |
February | 23818554.16 | 0.363812E+10 | 0.708457E+09 | 0.00 | 0.708457E+09 | 0.00 | 0.00 |
March | 0.105407E+09 | 0.314858E+10 | 0.965244E+09 | 36902.88 | 0.965208E+09 | 0.00 | 0.00 |
April | 0.490262E+09 | 0.182278E+10 | 0.122831E+10 | 12616185.78 | 0.121569E+10 | 0.00 | 0.00 |
May | 0.153570E+10 | 0.878833E+09 | 0.178006E+10 | 94435047.30 | 0.168563E+10 | 0.00 | 0.00 |
June | 0.208867E+10 | 0.554657E+09 | 0.192515E+10 | 0.214186E+09 | 0.171097E+10 | 0.00 | 0.00 |
July | 0.218707E+10 | 0.504280E+09 | 0.190190E+10 | 0.166952E+09 | 0.173495E+10 | 0.00 | 0.00 |
August | 0.147495E+10 | 0.635277E+09 | 0.144419E+10 | 27475219.40 | 0.141671E+10 | 0.00 | 0.00 |
September | 0.776587E+09 | 0.110944E+10 | 0.108815E+10 | 1123205.09 | 0.108703E+10 | 0.00 | 0.00 |
October | 0.222516E+09 | 0.194177E+10 | 0.779479E+09 | 0.00 | 0.779479E+09 | 0.00 | 0.00 |
November | 22720147.45 | 0.303435E+10 | 0.499465E+09 | 0.00 | 0.499465E+09 | 0.00 | 0.00 |
December | 0.00 | 0.476726E+10 | 0.432644E+09 | 0.00 | 0.432644E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.892832E+10 | 0.269261E+11 | 0.132637E+11 | 0.516824E+09 | 0.127469E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.504280E+09 | 0.432644E+09 | 0.00 | 0.432644E+09 | 0.00 | 0.00 |
Maximum of Months | 0.218707E+10 | 0.489076E+10 | 0.192515E+10 | 0.214186E+09 | 0.173495E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.509636E+09 | 0.292142E+10 | 0.117442E+10 | 0.599533E+09 | 0.574892E+09 | 0.00 | 0.00 |
February | 0.999559E+09 | 0.219559E+10 | 0.152651E+10 | 0.751489E+09 | 0.775022E+09 | 0.00 | 0.00 |
March | 0.158607E+10 | 0.194939E+10 | 0.197947E+10 | 0.996166E+09 | 0.983302E+09 | 0.00 | 0.00 |
April | 0.245344E+10 | 0.119636E+10 | 0.238070E+10 | 0.119218E+10 | 0.118852E+10 | 0.00 | 0.00 |
May | 0.327651E+10 | 0.636761E+09 | 0.261249E+10 | 0.101526E+10 | 0.159723E+10 | 0.00 | 0.00 |
June | 0.375035E+10 | 0.413556E+09 | 0.274521E+10 | 0.113276E+10 | 0.161244E+10 | 0.00 | 0.00 |
July | 0.399962E+10 | 0.368725E+09 | 0.282274E+10 | 0.116009E+10 | 0.166265E+10 | 0.00 | 0.00 |
August | 0.316998E+10 | 0.429683E+09 | 0.229222E+10 | 0.906028E+09 | 0.138619E+10 | 0.00 | 0.00 |
September | 0.230631E+10 | 0.709964E+09 | 0.188482E+10 | 0.809981E+09 | 0.107484E+10 | 0.00 | 0.00 |
October | 0.126031E+10 | 0.119855E+10 | 0.132212E+10 | 0.547198E+09 | 0.774919E+09 | 0.00 | 0.00 |
November | 0.563765E+09 | 0.182613E+10 | 0.916052E+09 | 0.385113E+09 | 0.530939E+09 | 0.00 | 0.00 |
December | 0.319546E+09 | 0.289033E+10 | 0.917533E+09 | 0.430317E+09 | 0.487216E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.241951E+11 | 0.167365E+11 | 0.225743E+11 | 0.992612E+10 | 0.126482E+11 | 0.00 | 0.00 |
Minimum of Months | 0.319546E+09 | 0.368725E+09 | 0.916052E+09 | 0.385113E+09 | 0.487216E+09 | 0.00 | 0.00 |
Maximum of Months | 0.399962E+10 | 0.292142E+10 | 0.282274E+10 | 0.119218E+10 | 0.166265E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.130438E+10 | 0.334956E+10 | 0.206398E+10 | 0.131646E+10 | 0.747524E+09 | 0.00 | 0.00 |
February | 0.183941E+10 | 0.254762E+10 | 0.237291E+10 | 0.143317E+10 | 0.939745E+09 | 0.00 | 0.00 |
March | 0.195624E+10 | 0.230045E+10 | 0.240382E+10 | 0.130476E+10 | 0.109906E+10 | 0.00 | 0.00 |
April | 0.210416E+10 | 0.141816E+10 | 0.225333E+10 | 0.997719E+09 | 0.125562E+10 | 0.00 | 0.00 |
May | 0.240864E+10 | 0.745583E+09 | 0.223088E+10 | 0.604154E+09 | 0.162672E+10 | 0.00 | 0.00 |
June | 0.241559E+10 | 0.465561E+09 | 0.203806E+10 | 0.436491E+09 | 0.160156E+10 | 0.00 | 0.00 |
July | 0.275790E+10 | 0.439950E+09 | 0.221884E+10 | 0.555822E+09 | 0.166302E+10 | 0.00 | 0.00 |
August | 0.258671E+10 | 0.535264E+09 | 0.215765E+10 | 0.700600E+09 | 0.145705E+10 | 0.00 | 0.00 |
September | 0.223743E+10 | 0.874799E+09 | 0.207001E+10 | 0.888221E+09 | 0.118179E+10 | 0.00 | 0.00 |
October | 0.165766E+10 | 0.142504E+10 | 0.182642E+10 | 0.929526E+09 | 0.896898E+09 | 0.00 | 0.00 |
November | 0.108320E+10 | 0.211082E+10 | 0.148921E+10 | 0.826446E+09 | 0.662769E+09 | 0.00 | 0.00 |
December | 0.886687E+09 | 0.331055E+10 | 0.159917E+10 | 0.951937E+09 | 0.647228E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.232380E+11 | 0.195234E+11 | 0.247243E+11 | 0.109453E+11 | 0.137790E+11 | 0.00 | 0.00 |
Minimum of Months | 0.886687E+09 | 0.439950E+09 | 0.148921E+10 | 0.436491E+09 | 0.647228E+09 | 0.00 | 0.00 |
Maximum of Months | 0.275790E+10 | 0.334956E+10 | 0.240382E+10 | 0.143317E+10 | 0.166302E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -16.9 | -17.4 | -20.0 | 3.73 | -31.9 | 33.25 | 98.18 | 0.00 |
February | -11.6 | -12.7 | -16.7 | 4.33 | -26.7 | 48.91 | 138.70 | 0.00 |
March | -6.2 | -7.6 | -10.8 | 3.55 | -19.4 | 56.69 | 163.76 | 0.01 |
April | 3.97 | 0.41 | -4.8 | 4.72 | -9.1 | 70.41 | 207.70 | 0.01 |
May | 13.43 | 8.45 | 3.53 | 3.60 | 2.20 | 102.27 | 202.62 | 0.00 |
June | 18.03 | 14.19 | 11.55 | 3.74 | 7.84 | 104.36 | 210.60 | 0.06 |
July | 19.67 | 16.51 | 14.78 | 3.14 | 8.97 | 101.67 | 223.82 | 0.04 |
August | 17.94 | 15.20 | 13.59 | 3.45 | 8.99 | 87.39 | 175.79 | 0.04 |
September | 12.29 | 9.87 | 7.80 | 3.78 | 3.34 | 70.27 | 143.96 | 0.00 |
October | 5.42 | 3.47 | 1.07 | 3.53 | -4.7 | 51.74 | 90.11 | 0.00 |
November | -2.0 | -3.6 | -6.9 | 4.42 | -13.7 | 34.68 | 65.95 | 0.00 |
December | -14.6 | -15.1 | -18.1 | 3.91 | -28.3 | 29.58 | 68.99 | 0.00 |
Annual Sum or Average | 3.36 | 1.04 | -2.0 | 3.82 | -8.4 | 66.03 | 149.18 | 0.01 |
Minimum of Months | -16.9 | -17.4 | -20.0 | 3.14 | -31.9 | 29.58 | 65.95 | 0.00 |
Maximum of Months | 19.67 | 16.51 | 14.78 | 4.72 | 8.99 | 104.36 | 223.82 | 0.06 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.10 | 29-JAN-14:00 | -1.0 | -4.4 | 2.60 | -11.4 | 145.00 | 110.00 |
February | 8.90 | 20-FEB-15:00 | 2.87 | -6.7 | 8.80 | -9.0 | 49.00 | 646.00 |
March | 11.10 | 26-MAR-15:00 | 5.48 | -1.1 | 5.20 | -5.7 | 53.00 | 842.00 |
April | 26.70 | 23-APR-15:00 | 16.95 | 11.10 | 11.30 | 12.03 | 75.50 | 811.00 |
May | 29.40 | 25-MAY-17:00 | 19.26 | 13.90 | 1.50 | 16.49 | 47.50 | 582.00 |
June | 35.00 | 29-JUN-15:00 | 24.72 | 21.10 | 6.70 | 24.66 | 132.00 | 705.00 |
July | 31.10 | 15-JUL-14:20 | 25.35 | 23.33 | 8.07 | 19.93 | 299.67 | 518.33 |
August | 30.60 | 08-AUG-14:00 | 23.36 | 20.60 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 26.10 | 01-SEP-14:00 | 17.82 | 13.30 | 3.60 | 14.28 | 112.00 | 751.50 |
October | 22.20 | 19-OCT-14:00 | 13.62 | 7.20 | 6.70 | 8.15 | 35.50 | 701.50 |
November | 18.30 | 01-NOV-14:00 | 13.44 | 10.00 | 3.10 | 11.84 | 105.00 | 30.50 |
December | 1.10 | 28-DEC-02:00 | 0.43 | -0.6 | 4.60 | -5.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.10 | -1.0 | -6.7 | 1.50 | -11.4 | 0.00 | 0.00 | |
Maximum of Months | 35.00 | 25.35 | 23.33 | 11.30 | 24.66 | 299.67 | 842.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -35.6 | 06-JAN-08:00 | -35.7 | -37.8 | 0.00 | -57.8 | 27.00 | 381.00 |
February | -33.3 | 14-FEB-06:00 | -33.4 | -36.7 | 0.00 | -55.6 | 0.00 | 0.00 |
March | -28.9 | 05-MAR-06:00 | -29.1 | -32.2 | 1.50 | -50.6 | 27.00 | 41.50 |
April | -13.9 | 05-APR-05:00 | -14.4 | -16.1 | 0.00 | -32.5 | 14.50 | 199.00 |
May | -3.9 | 01-MAY-05:00 | -6.2 | -12.2 | 0.00 | -22.4 | 35.00 | 415.00 |
June | 1.10 | 04-JUN-04:00 | 0.62 | 0.00 | 0.00 | -14.9 | 37.00 | 169.50 |
July | 6.10 | 02-JUL-04:00 | 6.10 | 6.10 | 0.00 | -8.8 | 33.50 | 204.50 |
August | 4.40 | 19-AUG-03:00 | 4.40 | 4.40 | 0.00 | -10.7 | 0.00 | 0.00 |
September | 1.10 | 06-SEP-03:00 | 1.10 | 1.10 | 0.00 | -14.7 | 0.00 | 0.00 |
October | -10.0 | 30-OCT-03:00 | -10.7 | -12.8 | 1.50 | -28.2 | 0.00 | 0.00 |
November | -20.6 | 29-NOV-05:00 | -20.8 | -22.2 | 2.10 | -37.8 | 0.00 | 0.00 |
December | -31.1 | 24-DEC-06:19 | -31.3 | -35.1 | 3.33 | -53.1 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -35.6 | -35.7 | -37.8 | 0.00 | -57.8 | 0.00 | 0.00 | |
Maximum of Months | 6.10 | 6.10 | 6.10 | 3.33 | -8.8 | 37.00 | 415.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -0.5 | 16-JAN-12:00 | 0.00 | -1.1 | 5.70 | -6.6 | 172.50 | 3.00 |
February | 3.34 | 21-FEB-12:00 | 6.70 | -1.1 | 7.70 | -6.0 | 270.00 | 303.00 |
March | 5.48 | 26-MAR-15:00 | 11.10 | -1.1 | 5.20 | -5.7 | 53.00 | 842.00 |
April | 16.95 | 23-APR-15:00 | 26.70 | 11.10 | 11.30 | 12.03 | 75.50 | 811.00 |
May | 19.91 | 26-MAY-11:00 | 25.60 | 17.20 | 6.20 | 22.64 | 300.50 | 6.00 |
June | 24.72 | 29-JUN-15:00 | 35.00 | 21.10 | 6.70 | 24.66 | 132.00 | 705.00 |
July | 25.76 | 15-JUL-13:00 | 31.10 | 23.90 | 7.70 | 18.99 | 333.00 | 421.00 |
August | 23.36 | 08-AUG-14:00 | 30.60 | 20.60 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 18.67 | 01-SEP-00:00 | 19.00 | 17.50 | 2.80 | 16.30 | 0.00 | 0.00 |
October | 13.72 | 19-OCT-13:00 | 21.70 | 7.80 | 5.70 | 7.75 | 54.50 | 739.00 |
November | 14.29 | 21-NOV-12:00 | 15.00 | 13.90 | 5.20 | 11.46 | 134.50 | 25.50 |
December | 0.43 | 28-DEC-02:00 | 1.10 | -0.6 | 4.60 | -5.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.5 | 0.00 | -1.1 | 2.80 | -6.6 | 0.00 | 0.00 | |
Maximum of Months | 25.76 | 35.00 | 23.90 | 11.30 | 24.66 | 333.00 | 842.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -1.1 | 16-JAN-11:00 | -0.6 | -0.8 | 5.70 | -7.3 | 164.50 | 5.00 |
February | -0.6 | 21-FEB-08:00 | 4.40 | 2.25 | 8.80 | -6.6 | 123.00 | 89.50 |
March | 0.00 | 29-MAR-20:00 | 1.70 | 0.95 | 1.50 | -4.8 | 0.00 | 0.00 |
April | 11.10 | 23-APR-13:00 | 24.40 | 16.08 | 10.80 | 9.72 | 98.50 | 903.50 |
May | 17.20 | 26-MAY-11:00 | 25.60 | 19.91 | 6.20 | 22.64 | 300.50 | 6.00 |
June | 22.80 | 29-JUN-23:19 | 26.30 | 23.71 | 5.20 | 14.28 | 0.00 | 0.00 |
July | 23.90 | 15-JUL-13:00 | 31.10 | 25.76 | 7.70 | 18.99 | 333.00 | 421.00 |
August | 20.60 | 08-AUG-14:00 | 30.60 | 23.36 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 17.92 | 01-SEP-00:10 | 19.75 | 18.15 | 3.22 | 13.23 | 0.00 | 0.00 |
October | 12.20 | 07-OCT-12:20 | 14.47 | 13.17 | 3.43 | 9.20 | 163.17 | 18.50 |
November | 13.90 | 21-NOV-12:00 | 15.00 | 14.29 | 5.20 | 11.46 | 134.50 | 25.50 |
December | -0.0 | 05-DEC-17:00 | 0.00 | -0.0 | 1.50 | -6.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -1.1 | -0.6 | -0.8 | 1.50 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 23.90 | 31.10 | 25.76 | 10.80 | 22.64 | 333.00 | 903.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 1.89 | 11.66 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 0.58 | 19.92 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 0.81 | 26.63 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 2.58 | 37.52 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 5.43 | 45.25 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 8.61 | 47.76 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 11.25 | 48.86 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 12.66 | 38.94 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 12.41 | 29.23 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 10.60 | 17.37 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 7.72 | 10.89 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 4.55 | 9.11 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 6.63 | 28.63 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 0.58 | 9.11 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 12.66 | 48.86 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH LAUNDRY G WATER HEATER
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.129613E+12 | -0.127828E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.178496E+10 | 80.79 | 0.00 | 0.00 |
February | 0.117221E+12 | -0.115641E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.158069E+10 | 80.44 | 0.00 | 0.00 |
March | 0.129749E+12 | -0.127995E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175380E+10 | 80.50 | 0.00 | 0.00 |
April | 0.125321E+12 | -0.123611E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.170963E+10 | 80.97 | 0.00 | 0.00 |
May | 0.129090E+12 | -0.127307E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.178240E+10 | 81.72 | 0.00 | 0.00 |
June | 0.122274E+12 | -0.120544E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.173018E+10 | 82.17 | 0.00 | 0.00 |
July | 0.121863E+12 | -0.120091E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.177181E+10 | 82.17 | 0.00 | 0.00 |
August | 0.119471E+12 | -0.117710E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.176023E+10 | 82.17 | 0.00 | 0.00 |
September | 0.116021E+12 | -0.114320E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.170030E+10 | 82.17 | 0.00 | 0.00 |
October | 0.122958E+12 | -0.121202E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175623E+10 | 82.17 | 0.00 | 0.00 |
November | 0.123475E+12 | -0.121776E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.169912E+10 | 82.13 | 0.00 | 0.00 |
December | 0.129220E+12 | -0.127440E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.177983E+10 | 81.49 | 0.00 | 0.00 |
Annual Sum or Average | 0.148627E+13 | -0.146547E+13 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.208092E+11 | 81.58 | 0.00 | 0.00 |
Minimum of Months | 0.116021E+12 | -0.127995E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.178496E+10 | 80.44 | 0.00 | 0.00 |
Maximum of Months | 0.129749E+12 | -0.114320E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.158069E+10 | 82.17 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.805217E+10 | -0.788296E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -169209330.2 | 82.17 | 0.00 | 0.00 |
February | 0.727378E+10 | -0.712336E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -150418540.8 | 82.17 | 0.00 | 0.00 |
March | 0.804677E+10 | -0.788155E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -165219864.5 | 82.17 | 0.00 | 0.00 |
April | 0.779744E+10 | -0.763820E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -159238070.4 | 82.17 | 0.00 | 0.00 |
May | 0.804726E+10 | -0.788296E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164302088.6 | 82.17 | 0.00 | 0.00 |
June | 0.778868E+10 | -0.762976E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -158916776.1 | 82.17 | 0.00 | 0.00 |
July | 0.805558E+10 | -0.789140E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164176926.7 | 82.17 | 0.00 | 0.00 |
August | 0.804716E+10 | -0.788296E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164200375.8 | 82.17 | 0.00 | 0.00 |
September | 0.779862E+10 | -0.763961E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -159012510.6 | 82.17 | 0.00 | 0.00 |
October | 0.804606E+10 | -0.788155E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164501591.3 | 82.17 | 0.00 | 0.00 |
November | 0.778077E+10 | -0.762132E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -159447640.6 | 82.17 | 0.00 | 0.00 |
December | 0.805933E+10 | -0.789140E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -167927141.4 | 82.17 | 0.00 | 0.00 |
Annual Sum or Average | 0.947936E+11 | -0.928470E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.194657E+10 | 82.17 | 0.00 | 0.00 |
Minimum of Months | 0.727378E+10 | -0.789140E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -169209330.2 | 82.17 | 0.00 | 0.00 |
Maximum of Months | 0.805933E+10 | -0.712336E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -150418540.8 | 82.17 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.865261E+11 | -0.849182E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.160792E+10 | 60.05 | 0.00 | 0.00 |
February | 0.798725E+11 | -0.784508E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.142167E+10 | 60.05 | 0.00 | 0.00 |
March | 0.881505E+11 | -0.865739E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.157661E+10 | 60.05 | 0.00 | 0.00 |
April | 0.827637E+11 | -0.812396E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.152413E+10 | 60.05 | 0.00 | 0.00 |
May | 0.813448E+11 | -0.797795E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.156533E+10 | 60.05 | 0.00 | 0.00 |
June | 0.742401E+11 | -0.727362E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.150396E+10 | 60.05 | 0.00 | 0.00 |
July | 0.727610E+11 | -0.712291E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.153185E+10 | 60.05 | 0.00 | 0.00 |
August | 0.707611E+11 | -0.692452E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.151581E+10 | 60.05 | 0.00 | 0.00 |
September | 0.687890E+11 | -0.673265E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.146254E+10 | 60.05 | 0.00 | 0.00 |
October | 0.736980E+11 | -0.721878E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.151025E+10 | 60.05 | 0.00 | 0.00 |
November | 0.753926E+11 | -0.739300E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.146255E+10 | 60.05 | 0.00 | 0.00 |
December | 0.826038E+11 | -0.810323E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.157154E+10 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.936903E+12 | -0.918649E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.182542E+11 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.687890E+11 | -0.865739E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.160792E+10 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.881505E+11 | -0.673265E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.142167E+10 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: LOBBY_FLR_1_DAYLCTRL
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.87 | 0.86 | 01-JAN-08:39 | 4819.80 | 35.99 | 235.33 | 243.67 | 3997.19 | 36.97 | 241.00 | 225.50 |
February | 265.33 | 0.87 | 0.86 | 01-FEB-08:39 | 7655.64 | 36.13 | 258.50 | 259.50 | 3210.03 | 32.22 | 259.17 | 241.50 |
March | 254.17 | 0.87 | 0.86 | 02-MAR-10:39 | 9970.23 | 33.91 | 213.50 | 326.33 | 897.95 | 23.19 | 239.50 | 277.83 |
April | 296.33 | 0.87 | 0.86 | 01-APR-08:09 | 1705.92 | 20.99 | 110.00 | 357.33 | 694.46 | 22.60 | 262.67 | 303.50 |
May | 437.50 | 0.87 | 0.86 | 01-MAY-06:49 | 1602.41 | 20.64 | 166.33 | 417.83 | 625.90 | 22.35 | 329.33 | 353.00 |
June | 401.83 | 0.87 | 0.86 | 01-JUN-05:40 | 1523.50 | 20.69 | 175.83 | 418.00 | 607.49 | 22.40 | 297.67 | 355.67 |
July | 409.17 | 0.87 | 0.86 | 01-JUL-05:49 | 1637.74 | 21.04 | 209.50 | 424.83 | 657.02 | 22.75 | 321.17 | 366.00 |
August | 352.83 | 0.87 | 0.86 | 01-AUG-07:40 | 1925.02 | 21.20 | 187.33 | 383.50 | 759.40 | 22.90 | 280.33 | 328.17 |
September | 344.17 | 0.87 | 0.86 | 01-SEP-06:00 | 3364.22 | 24.27 | 204.17 | 335.50 | 764.38 | 22.46 | 255.17 | 289.67 |
October | 299.00 | 0.87 | 0.86 | 01-OCT-06:49 | 5513.14 | 32.20 | 271.00 | 301.83 | 1085.70 | 24.94 | 232.33 | 265.17 |
November | 255.50 | 0.87 | 0.86 | 01-NOV-08:09 | 3835.37 | 34.60 | 245.83 | 246.00 | 3025.34 | 35.21 | 247.83 | 218.00 |
December | 226.33 | 0.87 | 0.86 | 01-DEC-08:20 | 3528.46 | 34.05 | 211.00 | 229.00 | 2800.49 | 35.09 | 216.50 | 202.50 |
Annual Sum or Average | 3785.50 | 0.87 | 3563.90 | 26.72 | 2488.33 | 3943.33 | 1402.09 | 26.00 | 3182.67 | 3426.50 | ||
Minimum of Months | 226.33 | 0.87 | 0.86 | 1523.50 | 20.64 | 110.00 | 229.00 | 607.49 | 22.35 | 216.50 | 202.50 | |
Maximum of Months | 437.50 | 0.87 | 0.86 | 9970.23 | 36.13 | 271.00 | 424.83 | 3997.19 | 36.97 | 329.33 | 366.00 |
Report: DaylightingReportMonthly
For: CAFE_FLR_1_DAYLCTRL
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.24 | 0.22 | 01-JAN-08:30 | 5293.54 | 36.08 | 237.17 | 249.50 | 4468.69 | 37.04 | 241.83 | 236.50 |
February | 265.33 | 0.24 | 0.22 | 01-FEB-08:39 | 8207.70 | 36.22 | 258.83 | 266.50 | 3756.81 | 32.08 | 240.50 | 252.50 |
March | 254.17 | 0.25 | 0.22 | 02-MAR-10:39 | 10529.02 | 34.08 | 214.67 | 335.83 | 1454.63 | 22.93 | 230.33 | 307.33 |
April | 296.33 | 0.26 | 0.22 | 01-APR-07:40 | 2142.65 | 21.01 | 113.83 | 371.17 | 1129.97 | 22.50 | 263.17 | 338.33 |
May | 437.50 | 0.26 | 0.22 | 01-MAY-05:00 | 1903.58 | 21.03 | 196.67 | 430.00 | 926.01 | 22.57 | 339.00 | 397.33 |
June | 401.83 | 0.26 | 0.22 | 01-JUN-05:10 | 1799.80 | 21.14 | 210.17 | 434.00 | 882.83 | 22.68 | 318.83 | 396.17 |
July | 409.17 | 0.25 | 0.22 | 01-JUL-05:19 | 1947.23 | 21.40 | 231.83 | 439.83 | 965.49 | 22.95 | 342.50 | 403.50 |
August | 352.83 | 0.25 | 0.22 | 01-AUG-07:40 | 2294.05 | 21.46 | 191.00 | 395.33 | 1127.09 | 23.02 | 299.33 | 361.67 |
September | 344.17 | 0.25 | 0.22 | 01-SEP-06:40 | 3748.01 | 24.45 | 204.17 | 345.17 | 1147.00 | 22.57 | 255.67 | 318.33 |
October | 299.00 | 0.24 | 0.22 | 01-OCT-06:49 | 5889.62 | 32.37 | 274.67 | 309.83 | 1463.02 | 25.03 | 226.00 | 286.67 |
November | 255.50 | 0.25 | 0.22 | 01-NOV-07:00 | 4174.22 | 34.69 | 246.67 | 253.00 | 3363.43 | 35.30 | 248.50 | 234.33 |
December | 226.33 | 0.24 | 0.22 | 01-DEC-08:09 | 3896.98 | 34.19 | 212.67 | 238.00 | 3166.85 | 35.20 | 217.83 | 217.67 |
Annual Sum or Average | 3785.50 | 0.25 | 3946.27 | 26.94 | 2592.33 | 4068.17 | 1783.04 | 26.09 | 3223.50 | 3750.33 | ||
Minimum of Months | 226.33 | 0.24 | 0.22 | 1799.80 | 21.01 | 113.83 | 238.00 | 882.83 | 22.50 | 217.83 | 217.67 | |
Maximum of Months | 437.50 | 0.26 | 0.22 | 10529.02 | 36.22 | 274.67 | 439.83 | 4468.69 | 37.04 | 342.50 | 403.50 |
Report: DaylightingReportMonthly
For: DINING_FLR_6_DAYLCTRL
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.66 | 0.60 | 01-JAN-11:20 | 479.20 | 15.50 | 0.00 | 222.33 | 219.27 | 18.95 | 0.00 | 138.67 |
February | 265.33 | 0.64 | 0.60 | 01-FEB-09:30 | 587.25 | 16.55 | 0.00 | 248.50 | 276.36 | 19.92 | 10.50 | 197.00 |
March | 254.17 | 0.63 | 0.60 | 02-MAR-10:39 | 601.52 | 17.25 | 0.00 | 324.50 | 300.20 | 20.58 | 42.67 | 254.67 |
April | 296.33 | 0.62 | 0.60 | 01-APR-08:09 | 687.88 | 17.97 | 0.00 | 371.33 | 334.92 | 21.27 | 107.67 | 326.00 |
May | 437.50 | 0.61 | 0.60 | 01-MAY-05:40 | 1001.27 | 19.54 | 22.67 | 438.33 | 452.99 | 23.33 | 298.67 | 414.17 |
June | 401.83 | 0.61 | 0.60 | 01-JUN-04:49 | 1199.64 | 21.33 | 62.50 | 445.50 | 559.90 | 24.96 | 320.83 | 419.00 |
July | 409.17 | 0.61 | 0.60 | 01-JUL-04:49 | 1137.20 | 21.02 | 51.50 | 448.67 | 534.71 | 24.46 | 331.33 | 421.67 |
August | 352.83 | 0.61 | 0.60 | 01-AUG-07:40 | 938.53 | 19.08 | 7.17 | 397.00 | 433.90 | 22.23 | 217.17 | 354.33 |
September | 344.17 | 0.63 | 0.60 | 01-SEP-06:40 | 709.75 | 17.53 | 0.00 | 339.50 | 321.91 | 20.70 | 61.50 | 287.17 |
October | 299.00 | 0.64 | 0.60 | 01-OCT-07:19 | 603.17 | 16.49 | 0.00 | 293.00 | 261.99 | 19.72 | 1.50 | 214.00 |
November | 255.50 | 0.66 | 0.60 | 01-NOV-08:00 | 472.72 | 15.26 | 0.00 | 228.83 | 205.95 | 18.54 | 0.00 | 141.33 |
December | 226.33 | 0.67 | 0.60 | 01-DEC-09:39 | 452.32 | 15.20 | 0.00 | 209.17 | 199.03 | 18.57 | 0.00 | 110.83 |
Annual Sum or Average | 3785.50 | 0.63 | 790.78 | 18.13 | 143.83 | 3966.67 | 365.63 | 21.52 | 1391.83 | 3278.83 | ||
Minimum of Months | 226.33 | 0.61 | 0.60 | 452.32 | 15.20 | 0.00 | 209.17 | 199.03 | 18.54 | 0.00 | 110.83 | |
Maximum of Months | 437.50 | 0.67 | 0.60 | 1199.64 | 21.33 | 62.50 | 448.67 | 559.90 | 24.96 | 331.33 | 421.67 |
Report: DaylightingReportMonthly
For: BANQUET_FLR_6_DAYLCTRL
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.66 | 0.60 | 01-JAN-11:20 | 479.20 | 15.50 | 0.00 | 222.33 | 219.27 | 18.95 | 0.00 | 138.67 |
February | 265.33 | 0.64 | 0.60 | 01-FEB-09:30 | 587.25 | 16.55 | 0.00 | 248.50 | 276.36 | 19.92 | 10.50 | 197.00 |
March | 254.17 | 0.63 | 0.60 | 02-MAR-10:39 | 601.52 | 17.25 | 0.00 | 324.50 | 300.20 | 20.58 | 42.67 | 254.67 |
April | 296.33 | 0.62 | 0.60 | 01-APR-08:09 | 687.88 | 17.97 | 0.00 | 371.33 | 334.92 | 21.27 | 107.67 | 326.00 |
May | 437.50 | 0.61 | 0.60 | 01-MAY-05:40 | 1001.27 | 19.54 | 22.67 | 438.33 | 452.99 | 23.33 | 298.67 | 414.17 |
June | 401.83 | 0.61 | 0.60 | 01-JUN-04:49 | 1199.64 | 21.33 | 62.50 | 445.50 | 559.90 | 24.96 | 320.83 | 419.00 |
July | 409.17 | 0.61 | 0.60 | 01-JUL-04:49 | 1137.20 | 21.02 | 51.50 | 448.67 | 534.71 | 24.46 | 331.33 | 421.67 |
August | 352.83 | 0.61 | 0.60 | 01-AUG-07:40 | 938.53 | 19.08 | 7.17 | 397.00 | 433.90 | 22.23 | 217.17 | 354.33 |
September | 344.17 | 0.63 | 0.60 | 01-SEP-06:40 | 709.75 | 17.53 | 0.00 | 339.50 | 321.91 | 20.70 | 61.50 | 287.17 |
October | 299.00 | 0.64 | 0.60 | 01-OCT-07:19 | 603.17 | 16.49 | 0.00 | 293.00 | 261.99 | 19.72 | 1.50 | 214.00 |
November | 255.50 | 0.66 | 0.60 | 01-NOV-08:00 | 472.72 | 15.26 | 0.00 | 228.83 | 205.95 | 18.54 | 0.00 | 141.33 |
December | 226.33 | 0.67 | 0.60 | 01-DEC-09:39 | 452.32 | 15.20 | 0.00 | 209.17 | 199.03 | 18.57 | 0.00 | 110.83 |
Annual Sum or Average | 3785.50 | 0.63 | 790.78 | 18.13 | 143.83 | 3966.67 | 365.63 | 21.52 | 1391.83 | 3278.83 | ||
Minimum of Months | 226.33 | 0.61 | 0.60 | 452.32 | 15.20 | 0.00 | 209.17 | 199.03 | 18.54 | 0.00 | 110.83 | |
Maximum of Months | 437.50 | 0.67 | 0.60 | 1199.64 | 21.33 | 62.50 | 448.67 | 559.90 | 24.96 | 331.33 | 421.67 |
Report: CoilReportMonthly
For: FLR_3_DOAS HEATING COIL
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.272126E+11 | 36176.29 | 06-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.146016E+11 | 35661.29 | 14-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.757299E+10 | 34299.09 | 05-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.825859E+09 | 5630.61 | 05-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17222180.67 | 1385.10 | 01-MAY-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 21140.94 | 0.34 | 26-JUN-21:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 23322.75 | 0.34 | 03-JUL-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 22703.79 | 0.34 | 21-AUG-15:24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6269.82 | 0.34 | 01-SEP-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.254204E+09 | 3978.18 | 30-OCT-04:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.312915E+10 | 8727.76 | 25-NOV-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.232925E+11 | 34985.37 | 24-DEC-23:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.769062E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 6269.82 | 0.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.272126E+11 | 36176.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.417436E+12 | 383916.46 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.240951E+12 | 376082.90 | 14-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.148196E+12 | 361909.91 | 05-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.537690E+11 | 132865.90 | 24-APR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.522260E+11 | 127844.04 | 05-MAY-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.260384E+11 | 110454.05 | 04-JUN-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.201551E+11 | 113590.64 | 02-JUL-04:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.197534E+11 | 120871.46 | 19-AUG-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.665087E+11 | 122739.21 | 27-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.636531E+11 | 148121.10 | 09-OCT-10:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.852399E+11 | 138623.77 | 25-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.365382E+12 | 369769.31 | 24-DEC-23:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.155931E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.197534E+11 | 110454.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.417436E+12 | 383916.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.467137E+10 | 7294.71 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.105743E+10 | 7116.64 | 14-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.377347E+09 | 6795.95 | 05-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.246064E+10 | 6980.74 | 24-DEC-23:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.856679E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.467137E+10 | 7294.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.635585E+10 | 4604.92 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.363080E+10 | 4497.73 | 14-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.275206E+10 | 4297.20 | 05-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.125860E+10 | 1811.98 | 04-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.265429E+09 | 1194.89 | 01-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124275E+09 | 989.90 | 04-JUN-04:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 20098705.38 | 509.57 | 09-JUL-10:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 70470138.20 | 853.41 | 19-AUG-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.378534E+09 | 959.10 | 23-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.151724E+10 | 1969.77 | 30-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.287805E+10 | 2781.30 | 25-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.617124E+10 | 4401.53 | 24-DEC-23:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.254227E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 20098705.38 | 509.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.635585E+10 | 4604.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.151906E+10 | 1693.68 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.552809E+09 | 1654.71 | 14-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.172166E+09 | 1581.72 | 05-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 145809.08 | 48.55 | 30-OCT-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 53712068.85 | 481.10 | 26-NOV-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.125436E+10 | 1619.71 | 24-DEC-24:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.355225E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.151906E+10 | 1693.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.331280E+10 | 2400.51 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.175249E+10 | 2344.21 | 14-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.953389E+09 | 2238.96 | 05-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 76004528.58 | 564.97 | 05-APR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11082019.49 | 270.69 | 30-OCT-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.478126E+09 | 845.37 | 25-NOV-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.287453E+10 | 2293.70 | 24-DEC-24:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.945843E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.331280E+10 | 2400.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.255693E+10 | 1589.67 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.157555E+10 | 1552.74 | 14-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.102978E+10 | 1483.64 | 05-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.191228E+09 | 489.43 | 05-APR-10:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2072380.89 | 171.63 | 01-MAY-10:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 93750165.16 | 354.26 | 30-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.693352E+09 | 784.03 | 25-NOV-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.231482E+10 | 1519.59 | 24-DEC-23:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.845749E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.255693E+10 | 1589.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.597764E+10 | 10560.27 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.218819E+10 | 10302.22 | 14-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.729315E+09 | 9837.55 | 05-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6853668.84 | 517.06 | 05-APR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3768163.02 | 637.33 | 30-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 45421908.48 | 1307.71 | 25-NOV-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.479325E+10 | 10105.29 | 24-DEC-24:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.137444E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.597764E+10 | 10560.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.114220E+11 | 13271.42 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.446733E+10 | 12965.79 | 14-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.228134E+10 | 12393.35 | 05-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.422216E+09 | 3883.61 | 26-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6174350.88 | 1304.23 | 01-MAY-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2109494.88 | 1257.45 | 09-JUN-10:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7604239.00 | 1405.25 | 15-AUG-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 51310710.90 | 1756.92 | 28-SEP-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.681734E+09 | 3735.87 | 06-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.191102E+10 | 5495.42 | 24-NOV-09:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.104011E+11 | 12691.28 | 24-DEC-24:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.316539E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.114220E+11 | 13271.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.241664E+11 | 32768.58 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.827773E+10 | 32017.12 | 14-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.246320E+10 | 30609.02 | 05-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.511332E+09 | 7986.13 | 26-NOV-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.201583E+11 | 31341.96 | 24-DEC-23:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.555769E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.241664E+11 | 32768.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.226866E+11 | 16240.31 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.117508E+11 | 15863.23 | 14-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.670215E+10 | 15157.58 | 05-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.937408E+09 | 4588.43 | 03-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.180035E+10 | 4675.72 | 30-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.717002E+10 | 7903.72 | 25-NOV-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.211853E+11 | 15524.75 | 24-DEC-23:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.722327E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.226866E+11 | 16240.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.141878E+11 | 10381.87 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.786024E+10 | 10138.03 | 14-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.477722E+10 | 9682.27 | 05-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.985879E+09 | 3216.06 | 05-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16000288.03 | 1037.97 | 01-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.110406E+10 | 3118.90 | 30-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.416307E+10 | 4626.38 | 25-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129303E+11 | 9919.33 | 24-DEC-23:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.460246E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.141878E+11 | 10381.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.730324E+10 | 13123.18 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.243135E+10 | 12799.34 | 14-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.624446E+09 | 12213.90 | 05-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.582347E+10 | 12552.37 | 24-DEC-23:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.161825E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.730324E+10 | 13123.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.731587E+10 | 13532.99 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.239516E+10 | 13199.15 | 14-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.610077E+09 | 12595.69 | 05-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.577015E+10 | 12944.55 | 24-DEC-23:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160913E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.731587E+10 | 13532.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.476362E+10 | 8870.28 | 06-JAN-08:27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.163725E+10 | 8676.69 | 14-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.537356E+09 | 8283.82 | 05-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.361416E+10 | 8510.50 | 24-DEC-23:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.105524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.476362E+10 | 8870.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.973897E+10 | 8310.16 | 16-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.582331E+10 | 8309.20 | 07-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.401383E+10 | 8309.10 | 02-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.125836E+10 | 8252.14 | 04-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 82446620.90 | 5068.04 | 30-MAY-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17847033.76 | 4361.82 | 03-JUN-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6530628.73 | 3720.43 | 03-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 20538122.96 | 4606.57 | 17-AUG-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.153437E+09 | 4978.77 | 29-SEP-15:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.152551E+10 | 8304.00 | 30-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.433031E+10 | 8309.25 | 05-NOV-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.952934E+10 | 8310.86 | 06-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.365004E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 6530628.73 | 3720.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.973897E+10 | 8310.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.113576E+11 | 8228.80 | 16-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.723323E+10 | 8227.83 | 08-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.505815E+10 | 8227.78 | 01-MAR-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.158553E+10 | 8227.50 | 04-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 97981275.95 | 5534.69 | 01-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 15141066.90 | 4175.82 | 10-JUN-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 4314674.07 | 3533.15 | 09-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 20989317.02 | 5363.79 | 04-AUG-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.178728E+09 | 4944.28 | 24-SEP-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.186632E+10 | 8227.40 | 30-OCT-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.513358E+10 | 8228.25 | 06-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.108063E+11 | 8229.49 | 06-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.433578E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 4314674.07 | 3533.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.113576E+11 | 8229.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.528553E+10 | 22604.83 | 13-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 83936621.57 | 5068.29 | 03-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 8137370.31 | 2588.76 | 29-NOV-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.875792E+10 | 24585.72 | 24-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.141355E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.875792E+10 | 24585.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.556133E+11 | 45432.95 | 03-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.338049E+11 | 45432.61 | 16-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.213057E+11 | 45331.58 | 15-MAR-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.349390E+10 | 43744.45 | 04-APR-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 97017086.53 | 42985.45 | 02-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 26236172.91 | 32357.56 | 12-JUN-15:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 12102362.03 | 32124.92 | 09-JUL-15:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 48768343.33 | 32426.39 | 10-AUG-15:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.111555E+09 | 34194.90 | 09-SEP-18:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.238189E+10 | 43738.98 | 30-OCT-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.159170E+11 | 45434.85 | 25-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.499843E+11 | 45437.59 | 27-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.182797E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 12102362.03 | 32124.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.556133E+11 | 45437.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.970901E+10 | 8158.42 | 16-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.580746E+10 | 8157.38 | 07-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.398334E+10 | 8157.31 | 02-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.121506E+10 | 8060.65 | 26-APR-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 95976681.85 | 4314.38 | 12-MAY-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 9125391.51 | 4138.35 | 23-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 4104290.98 | 4083.95 | 03-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17678023.70 | 4749.86 | 17-AUG-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.168773E+09 | 4621.71 | 29-SEP-15:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.159329E+10 | 8086.19 | 29-OCT-18:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.436952E+10 | 8157.44 | 27-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.949123E+10 | 8158.96 | 06-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.364646E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 4104290.98 | 4083.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.970901E+10 | 8158.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.113809E+11 | 8069.35 | 16-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.725064E+10 | 8068.29 | 07-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.503158E+10 | 8068.25 | 01-MAR-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.150704E+10 | 7995.78 | 03-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.117110E+09 | 5860.28 | 02-MAY-19:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 7792420.12 | 4346.27 | 10-JUN-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 3583828.18 | 3773.98 | 09-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17862600.23 | 4182.91 | 18-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.206600E+09 | 4997.83 | 22-SEP-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.197235E+10 | 8026.16 | 29-OCT-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.514663E+10 | 8068.60 | 19-NOV-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.107865E+11 | 8070.07 | 06-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.434286E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 3583828.18 | 3773.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.113809E+11 | 8070.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.317188E+10 | 2452.50 | 19-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.199870E+10 | 2452.31 | 08-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.143893E+10 | 2452.54 | 22-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.518129E+09 | 2452.48 | 26-APR-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 55640695.20 | 1907.67 | 01-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 13557350.42 | 1211.60 | 09-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1919336.42 | 909.08 | 05-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 12437662.28 | 1064.39 | 22-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 93951389.46 | 1357.64 | 28-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.627202E+09 | 2452.53 | 31-OCT-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.154714E+10 | 2452.49 | 06-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.313433E+10 | 2452.82 | 06-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.126138E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1919336.42 | 909.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.317188E+10 | 2452.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.364891E+10 | 2421.04 | 19-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.242457E+10 | 2420.85 | 08-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.176624E+10 | 2421.30 | 21-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.629904E+09 | 2421.02 | 26-APR-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 57809563.99 | 2347.81 | 01-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 9825504.28 | 1073.22 | 05-JUN-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 965537.33 | 1194.53 | 31-JUL-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11726822.05 | 1274.47 | 20-AUG-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.108512E+09 | 1516.82 | 28-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.753083E+09 | 2421.09 | 13-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.180047E+10 | 2421.36 | 20-NOV-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.349437E+10 | 2421.36 | 06-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.147064E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 965537.33 | 1073.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.364891E+10 | 2421.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.107892E+11 | 11806.42 | 30-JAN-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.611006E+10 | 11805.51 | 16-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.425961E+10 | 11806.50 | 04-MAR-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.140850E+10 | 11664.57 | 26-APR-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.138571E+09 | 5924.02 | 11-MAY-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 35936551.82 | 7121.33 | 22-JUN-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 13856895.47 | 5344.17 | 20-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 25841179.75 | 5876.66 | 28-AUG-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.148598E+09 | 5637.81 | 19-SEP-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.152603E+10 | 11606.73 | 30-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.461802E+10 | 11807.19 | 27-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.110389E+11 | 11808.37 | 05-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.401131E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 13856895.47 | 5344.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.110389E+11 | 11808.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.823559E+09 | 0.823559E+09 | 17162.23 | 23-APR-15:01 | 17162.23 | 0.01 |
May | 0.00 | 0.00 | 0.698346E+10 | 0.673692E+10 | 22951.99 | 26-MAY-09:03 | 13603.47 | 0.22 |
June | 0.00 | 0.00 | 0.193787E+11 | 0.130069E+11 | 37981.96 | 25-JUN-08:03 | 17634.05 | 0.45 |
July | 0.00 | 0.00 | 0.280739E+11 | 0.170906E+11 | 41145.79 | 05-JUL-13:00 | 16537.74 | 0.62 |
August | 0.00 | 0.00 | 0.191298E+11 | 0.124591E+11 | 36218.62 | 31-AUG-20:40 | 16016.84 | 0.59 |
September | 0.00 | 0.00 | 0.390652E+10 | 0.315389E+10 | 24121.93 | 01-SEP-01:00 | 8846.91 | 0.15 |
October | 0.00 | 0.00 | 0.525223E+09 | 0.525223E+09 | 14575.81 | 19-OCT-15:01 | 14575.81 | 0.01 |
November | 0.00 | 0.00 | 78594968.24 | 78594968.24 | 7087.99 | 01-NOV-15:04 | 7087.99 | 0.01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.788998E+11 | 0.538748E+11 | 0.17 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.280739E+11 | 0.170906E+11 | 41145.79 | 17634.05 | 0.62 |
Report: CoilReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.135661E+11 | 0.135661E+11 | 185628.07 | 23-APR-18:10 | 185628.07 | 0.02 |
May | 0.00 | 0.00 | 0.104453E+12 | 0.102121E+12 | 280256.76 | 25-MAY-18:03 | 232588.15 | 0.29 |
June | 0.00 | 0.00 | 0.275197E+12 | 0.191595E+12 | 474950.68 | 27-JUN-19:50 | 210437.78 | 0.60 |
July | 0.00 | 0.00 | 0.385290E+12 | 0.247095E+12 | 507283.06 | 21-JUL-19:20 | 207504.90 | 0.82 |
August | 0.00 | 0.00 | 0.261261E+12 | 0.182030E+12 | 459077.91 | 31-AUG-19:05 | 204487.71 | 0.77 |
September | 0.00 | 0.00 | 0.588244E+11 | 0.506791E+11 | 256614.20 | 01-SEP-10:50 | 166631.87 | 0.23 |
October | 0.00 | 0.00 | 0.829179E+10 | 0.829179E+10 | 132997.37 | 19-OCT-15:03 | 132997.37 | 0.03 |
November | 0.00 | 0.00 | 0.105207E+10 | 0.105207E+10 | 54893.61 | 01-NOV-15:30 | 54893.61 | 0.01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.110793E+13 | 0.796430E+12 | 0.23 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.385290E+12 | 0.247095E+12 | 507283.06 | 232588.15 | 0.82 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 8188557.81 | 8178341.77 | 18448.26 | 27-JAN-16:01 | 18448.26 | 0.00 |
February | 0.00 | 0.00 | 0.223274E+09 | 0.220874E+09 | 19376.86 | 04-FEB-16:01 | 19376.86 | 0.00 |
March | 0.00 | 0.00 | 0.806201E+09 | 0.718509E+09 | 19382.02 | 29-MAR-15:01 | 19382.02 | 0.04 |
April | 0.00 | 0.00 | 0.257540E+10 | 0.231806E+10 | 19379.91 | 14-APR-15:01 | 19379.91 | 0.10 |
May | 0.00 | 0.00 | 0.665880E+10 | 0.447988E+10 | 19377.21 | 13-MAY-18:01 | 19377.21 | 0.62 |
June | 0.00 | 0.00 | 0.831075E+10 | 0.462578E+10 | 20574.16 | 10-JUN-15:01 | 14083.20 | 0.90 |
July | 0.00 | 0.00 | 0.108563E+11 | 0.602882E+10 | 19920.69 | 05-JUL-08:61 | 14975.73 | 0.94 |
August | 0.00 | 0.00 | 0.878062E+10 | 0.452709E+10 | 20012.50 | 30-AUG-08:61 | 14941.21 | 0.89 |
September | 0.00 | 0.00 | 0.444106E+10 | 0.228380E+10 | 20443.50 | 19-SEP-15:01 | 14138.23 | 0.70 |
October | 0.00 | 0.00 | 0.133701E+10 | 0.731958E+09 | 19380.80 | 21-OCT-18:01 | 19380.80 | 0.25 |
November | 0.00 | 0.00 | 56559443.62 | 50458581.04 | 19376.45 | 09-NOV-16:01 | 19376.45 | 0.01 |
December | 0.00 | 0.00 | 304633.58 | 257788.24 | 1046.71 | 28-DEC-16:05 | 1046.71 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.440545E+11 | 0.259937E+11 | 0.37 | |||
Minimum of Months | 0.00 | 0.00 | 304633.58 | 257788.24 | 1046.71 | 1046.71 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.108563E+11 | 0.602882E+10 | 20574.16 | 19382.02 | 0.94 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 256323.97 | 236132.05 | 1946.31 | 27-JAN-16:04 | 1946.31 | 0.00 |
February | 0.00 | 0.00 | 38799200.68 | 38500533.37 | 18099.38 | 28-FEB-16:01 | 18099.38 | 0.00 |
March | 0.00 | 0.00 | 0.327889E+09 | 0.286867E+09 | 18464.15 | 31-MAR-18:01 | 18464.15 | 0.02 |
April | 0.00 | 0.00 | 0.136294E+10 | 0.118800E+10 | 21216.08 | 11-APR-18:11 | 21216.08 | 0.07 |
May | 0.00 | 0.00 | 0.462536E+10 | 0.287530E+10 | 23291.46 | 06-MAY-18:42 | 23291.46 | 0.53 |
June | 0.00 | 0.00 | 0.613026E+10 | 0.328610E+10 | 21815.86 | 25-JUN-08:51 | 14655.96 | 0.69 |
July | 0.00 | 0.00 | 0.796136E+10 | 0.434656E+10 | 21992.99 | 30-JUL-08:41 | 14344.75 | 0.69 |
August | 0.00 | 0.00 | 0.571912E+10 | 0.268974E+10 | 20253.17 | 25-AUG-21:51 | 15263.97 | 0.65 |
September | 0.00 | 0.00 | 0.231752E+10 | 0.927991E+09 | 21235.60 | 23-SEP-17:41 | 21235.60 | 0.53 |
October | 0.00 | 0.00 | 0.412946E+09 | 0.181662E+09 | 18064.07 | 21-OCT-18:32 | 18064.07 | 0.12 |
November | 0.00 | 0.00 | 7071614.48 | 5203387.82 | 14806.32 | 17-NOV-16:01 | 14806.32 | 0.00 |
December | 0.00 | 0.00 | 98811.62 | 12163.85 | 612.87 | 05-DEC-19:06 | 90.23 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.289036E+11 | 0.158262E+11 | 0.28 | |||
Minimum of Months | 0.00 | 0.00 | 98811.62 | 12163.85 | 612.87 | 90.23 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.796136E+10 | 0.434656E+10 | 23291.46 | 23291.46 | 0.69 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.443088E+09 | 0.443088E+09 | 23628.53 | 28-FEB-14:35 | 23628.53 | 0.00 |
March | 0.00 | 0.00 | 0.564493E+10 | 0.564493E+10 | 47042.71 | 20-MAR-12:30 | 47042.71 | 0.00 |
April | 0.00 | 0.00 | 0.195631E+11 | 0.188183E+11 | 52698.72 | 13-APR-13:00 | 52698.72 | 0.04 |
May | 0.00 | 0.00 | 0.363696E+11 | 0.229825E+11 | 50329.80 | 18-MAY-13:00 | 40287.90 | 0.52 |
June | 0.00 | 0.00 | 0.407380E+11 | 0.171734E+11 | 50401.13 | 30-JUN-13:00 | 38498.65 | 0.89 |
July | 0.00 | 0.00 | 0.523436E+11 | 0.221538E+11 | 54020.28 | 23-JUL-13:00 | 43813.78 | 0.99 |
August | 0.00 | 0.00 | 0.492495E+11 | 0.220432E+11 | 59267.47 | 25-AUG-12:50 | 54115.96 | 0.97 |
September | 0.00 | 0.00 | 0.354223E+11 | 0.176412E+11 | 60502.62 | 01-SEP-12:50 | 55807.21 | 0.83 |
October | 0.00 | 0.00 | 0.178991E+11 | 0.128140E+11 | 72284.26 | 22-OCT-12:30 | 59009.16 | 0.26 |
November | 0.00 | 0.00 | 0.176255E+10 | 0.176255E+10 | 41624.23 | 17-NOV-12:20 | 41624.23 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.259436E+12 | 0.141477E+12 | 0.38 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.523436E+11 | 0.229825E+11 | 72284.26 | 59009.16 | 0.99 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 7557026.01 | 6802785.08 | 12801.36 | 20-JAN-19:05 | 12801.36 | 0.00 |
February | 0.00 | 0.00 | 48967628.90 | 32553239.97 | 43799.72 | 05-FEB-09:01 | 43799.72 | 0.00 |
March | 0.00 | 0.00 | 0.847777E+09 | 0.791243E+09 | 86381.26 | 28-MAR-18:01 | 86381.26 | 0.01 |
April | 0.00 | 0.00 | 0.825290E+10 | 0.686759E+10 | 91016.64 | 18-APR-18:01 | 91016.64 | 0.12 |
May | 0.00 | 0.00 | 0.327061E+11 | 0.233736E+11 | 95471.63 | 21-MAY-21:01 | 95471.63 | 0.46 |
June | 0.00 | 0.00 | 0.455464E+11 | 0.294082E+11 | 106284.81 | 19-JUN-21:51 | 69970.49 | 0.61 |
July | 0.00 | 0.00 | 0.523826E+11 | 0.322509E+11 | 106288.48 | 30-JUL-08:41 | 68570.78 | 0.63 |
August | 0.00 | 0.00 | 0.416894E+11 | 0.235062E+11 | 102087.60 | 28-AUG-21:51 | 71456.39 | 0.58 |
September | 0.00 | 0.00 | 0.240145E+11 | 0.120678E+11 | 97373.28 | 18-SEP-21:52 | 70770.14 | 0.60 |
October | 0.00 | 0.00 | 0.699753E+10 | 0.317586E+10 | 88123.62 | 20-OCT-18:11 | 88123.62 | 0.35 |
November | 0.00 | 0.00 | 0.872212E+09 | 0.390426E+09 | 75460.87 | 01-NOV-18:03 | 75460.87 | 0.05 |
December | 0.00 | 0.00 | 13814665.87 | 9935759.58 | 15968.68 | 05-DEC-19:03 | 8689.93 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.213380E+12 | 0.131881E+12 | 0.29 | |||
Minimum of Months | 0.00 | 0.00 | 7557026.01 | 6802785.08 | 12801.36 | 8689.93 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.523826E+11 | 0.322509E+11 | 106288.48 | 95471.63 | 0.63 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 628602.90 | 587603.82 | 1856.39 | 17-JAN-16:04 | 1856.39 | 0.00 |
February | 0.00 | 0.00 | 0.129750E+09 | 0.126372E+09 | 17620.92 | 28-FEB-16:01 | 17620.92 | 0.00 |
March | 0.00 | 0.00 | 0.635183E+09 | 0.530868E+09 | 17714.37 | 31-MAR-15:01 | 17714.37 | 0.05 |
April | 0.00 | 0.00 | 0.268434E+10 | 0.233229E+10 | 17715.19 | 14-APR-15:01 | 17715.19 | 0.13 |
May | 0.00 | 0.00 | 0.629808E+10 | 0.407162E+10 | 17714.38 | 01-MAY-08:62 | 17714.38 | 0.65 |
June | 0.00 | 0.00 | 0.887099E+10 | 0.509587E+10 | 18801.23 | 10-JUN-15:01 | 12815.05 | 0.93 |
July | 0.00 | 0.00 | 0.109014E+11 | 0.614353E+10 | 18125.39 | 25-JUL-18:02 | 13776.96 | 0.97 |
August | 0.00 | 0.00 | 0.850583E+10 | 0.435609E+10 | 18036.63 | 09-AUG-08:61 | 13867.30 | 0.92 |
September | 0.00 | 0.00 | 0.433975E+10 | 0.219581E+10 | 18648.35 | 19-SEP-15:01 | 12779.57 | 0.70 |
October | 0.00 | 0.00 | 0.122801E+10 | 0.642295E+09 | 17713.64 | 21-OCT-18:01 | 17713.64 | 0.23 |
November | 0.00 | 0.00 | 0.114641E+09 | 81969382.53 | 17123.92 | 17-NOV-16:01 | 17123.92 | 0.01 |
December | 0.00 | 0.00 | 730813.27 | 550235.08 | 2468.77 | 01-DEC-09:03 | 2468.77 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.437093E+11 | 0.255778E+11 | 0.38 | |||
Minimum of Months | 0.00 | 0.00 | 628602.90 | 550235.08 | 1856.39 | 1856.39 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.109014E+11 | 0.614353E+10 | 18801.23 | 17715.19 | 0.97 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 47510.47 | 8329.30 | 542.89 | 19-JAN-19:06 | 85.78 | 0.00 |
February | 0.00 | 0.00 | 8403946.52 | 8171149.30 | 5505.04 | 27-FEB-09:02 | 5505.04 | 0.00 |
March | 0.00 | 0.00 | 0.177809E+09 | 0.137176E+09 | 16258.44 | 11-MAR-09:01 | 16258.44 | 0.02 |
April | 0.00 | 0.00 | 0.145831E+10 | 0.121980E+10 | 16852.89 | 17-APR-15:01 | 16852.89 | 0.11 |
May | 0.00 | 0.00 | 0.454958E+10 | 0.281842E+10 | 17815.27 | 26-MAY-08:51 | 15628.09 | 0.54 |
June | 0.00 | 0.00 | 0.681485E+10 | 0.390436E+10 | 21508.81 | 28-JUN-07:52 | 19826.60 | 0.72 |
July | 0.00 | 0.00 | 0.805110E+10 | 0.449300E+10 | 21436.16 | 23-JUL-08:32 | 16837.05 | 0.71 |
August | 0.00 | 0.00 | 0.568612E+10 | 0.275661E+10 | 19536.20 | 30-AUG-08:51 | 15072.30 | 0.67 |
September | 0.00 | 0.00 | 0.248054E+10 | 0.114130E+10 | 18735.10 | 01-SEP-08:51 | 15988.31 | 0.54 |
October | 0.00 | 0.00 | 0.365378E+09 | 0.174661E+09 | 15191.46 | 22-OCT-08:61 | 14707.51 | 0.11 |
November | 0.00 | 0.00 | 12762771.66 | 4483530.01 | 7241.78 | 16-NOV-09:01 | 5527.45 | 0.01 |
December | 0.00 | 0.00 | 106283.64 | 48475.89 | 535.18 | 05-DEC-19:06 | 76.56 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.296050E+11 | 0.166580E+11 | 0.29 | |||
Minimum of Months | 0.00 | 0.00 | 47510.47 | 8329.30 | 535.18 | 76.56 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.805110E+10 | 0.449300E+10 | 21508.81 | 19826.60 | 0.72 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 1010576.79 | 1010576.79 | 3933.65 | 27-JAN-16:01 | 3933.65 | 0.00 |
February | 0.00 | 0.00 | 54137700.46 | 53700566.65 | 5040.80 | 04-FEB-16:01 | 5040.80 | 0.00 |
March | 0.00 | 0.00 | 0.204810E+09 | 0.183332E+09 | 5041.85 | 19-MAR-15:01 | 5041.85 | 0.03 |
April | 0.00 | 0.00 | 0.644225E+09 | 0.586374E+09 | 5041.84 | 14-APR-15:01 | 5041.84 | 0.09 |
May | 0.00 | 0.00 | 0.167106E+10 | 0.115789E+10 | 5041.05 | 13-MAY-18:01 | 5041.05 | 0.58 |
June | 0.00 | 0.00 | 0.208676E+10 | 0.120804E+10 | 5426.91 | 10-JUN-15:01 | 3454.66 | 0.85 |
July | 0.00 | 0.00 | 0.270989E+10 | 0.154156E+10 | 5401.43 | 05-JUL-08:61 | 3715.71 | 0.93 |
August | 0.00 | 0.00 | 0.215522E+10 | 0.115369E+10 | 5419.39 | 30-AUG-08:61 | 3632.94 | 0.87 |
September | 0.00 | 0.00 | 0.102838E+10 | 0.564249E+09 | 5403.95 | 19-SEP-15:01 | 3579.96 | 0.59 |
October | 0.00 | 0.00 | 0.313611E+09 | 0.185109E+09 | 5041.42 | 21-OCT-18:01 | 5041.42 | 0.18 |
November | 0.00 | 0.00 | 11741047.89 | 10968859.64 | 5041.00 | 09-NOV-16:01 | 5041.00 | 0.00 |
December | 0.00 | 0.00 | 71957.97 | 71957.97 | 341.54 | 28-DEC-16:05 | 341.54 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.108809E+11 | 0.664600E+10 | 0.35 | |||
Minimum of Months | 0.00 | 0.00 | 71957.97 | 71957.97 | 341.54 | 341.54 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.270989E+10 | 0.154156E+10 | 5426.91 | 5041.85 | 0.93 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 117975.13 | 117975.13 | 727.65 | 20-JAN-16:04 | 727.65 | 0.00 |
February | 0.00 | 0.00 | 6864324.15 | 6834333.06 | 4463.62 | 28-FEB-16:01 | 4463.62 | 0.00 |
March | 0.00 | 0.00 | 78591369.15 | 67574161.22 | 4783.50 | 31-MAR-18:01 | 4783.50 | 0.02 |
April | 0.00 | 0.00 | 0.337144E+09 | 0.299338E+09 | 5529.22 | 11-APR-18:11 | 5529.22 | 0.06 |
May | 0.00 | 0.00 | 0.117744E+10 | 0.752434E+09 | 6049.19 | 06-MAY-18:42 | 6049.19 | 0.50 |
June | 0.00 | 0.00 | 0.158818E+10 | 0.885163E+09 | 5755.18 | 25-JUN-08:51 | 3776.28 | 0.66 |
July | 0.00 | 0.00 | 0.205447E+10 | 0.114942E+10 | 5785.23 | 30-JUL-08:41 | 3611.06 | 0.69 |
August | 0.00 | 0.00 | 0.143974E+10 | 0.700748E+09 | 5525.28 | 10-AUG-21:41 | 3866.61 | 0.64 |
September | 0.00 | 0.00 | 0.506439E+09 | 0.218784E+09 | 5535.48 | 04-SEP-18:01 | 5535.48 | 0.42 |
October | 0.00 | 0.00 | 86451538.12 | 39864025.18 | 4702.30 | 21-OCT-18:32 | 4702.30 | 0.08 |
November | 0.00 | 0.00 | 1071732.84 | 633033.26 | 2131.87 | 17-NOV-16:01 | 2131.87 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.727652E+10 | 0.412092E+10 | 0.26 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.205447E+10 | 0.114942E+10 | 6049.19 | 6049.19 | 0.69 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.808670E+09 | 0.807655E+09 | 24708.26 | 27-JAN-16:01 | 24708.26 | 0.00 |
February | 0.00 | 0.00 | 0.199088E+10 | 0.193352E+10 | 24734.81 | 08-FEB-16:02 | 24734.81 | 0.02 |
March | 0.00 | 0.00 | 0.264457E+10 | 0.232617E+10 | 24732.86 | 11-MAR-16:01 | 24732.86 | 0.09 |
April | 0.00 | 0.00 | 0.461792E+10 | 0.406351E+10 | 24730.39 | 19-APR-15:01 | 24730.39 | 0.16 |
May | 0.00 | 0.00 | 0.827640E+10 | 0.535848E+10 | 24731.00 | 14-MAY-15:01 | 24731.00 | 0.64 |
June | 0.00 | 0.00 | 0.100260E+11 | 0.526509E+10 | 27101.54 | 19-JUN-18:01 | 17895.22 | 0.88 |
July | 0.00 | 0.00 | 0.131205E+11 | 0.692047E+10 | 27720.28 | 25-JUL-18:02 | 17397.61 | 0.93 |
August | 0.00 | 0.00 | 0.120984E+11 | 0.639580E+10 | 26668.95 | 30-AUG-08:61 | 18024.74 | 0.89 |
September | 0.00 | 0.00 | 0.777519E+10 | 0.461202E+10 | 26211.49 | 19-SEP-15:01 | 18432.32 | 0.73 |
October | 0.00 | 0.00 | 0.405631E+10 | 0.273148E+10 | 24730.66 | 21-OCT-18:01 | 24730.66 | 0.37 |
November | 0.00 | 0.00 | 0.127016E+10 | 0.109803E+10 | 24731.21 | 10-NOV-16:01 | 24731.21 | 0.05 |
December | 0.00 | 0.00 | 0.466463E+09 | 0.448659E+09 | 24701.43 | 02-DEC-16:01 | 24701.43 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.671515E+11 | 0.419609E+11 | 0.40 | |||
Minimum of Months | 0.00 | 0.00 | 0.466463E+09 | 0.448659E+09 | 24701.43 | 17397.61 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.131205E+11 | 0.692047E+10 | 27720.28 | 24734.81 | 0.93 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 253103.16 | 655634.37 | 09-JAN-05:00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 154309.59 | 628235.66 | 14-FEB-07:00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 83986.69 | 599727.90 | 05-MAR-07:00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 26789.27 | 174279.17 | 05-APR-08:61 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 19730.75 | 148976.28 | 05-MAY-08:05 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 10076.87 | 111296.39 | 16-JUN-22:20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 7493.82 | 113549.49 | 02-JUL-04:30 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 7416.67 | 110390.72 | 19-AUG-00:30 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26080.26 | 148452.77 | 25-SEP-08:05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 30111.82 | 176598.60 | 31-OCT-08:62 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 57019.21 | 243842.37 | 25-NOV-09:02 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 224767.27 | 646733.32 | 24-DEC-06:00 |
Annual Sum or Average | 0.00 | 74916.58 | ||||
Minimum of Months | 0.00 | 0.00 | 7416.67 | 110390.72 | ||
Maximum of Months | 0.00 | 0.00 | 253103.16 | 655634.37 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 539.66 | 24162.67 | 27-JAN-16:01 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 1852.75 | 72057.64 | 28-FEB-16:06 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 5200.78 | 120302.30 | 31-MAR-15:01 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 23769.63 | 382340.52 | 23-APR-18:03 | 0.00 | 0.00 | 01-APR-00:10 |
May | 83603.64 | 492786.42 | 25-MAY-18:03 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 168074.17 | 674048.51 | 29-JUN-18:03 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 218670.97 | 661693.13 | 21-JUL-19:20 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 159439.63 | 588139.72 | 08-AUG-15:03 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 59507.98 | 443607.93 | 01-SEP-15:03 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 17432.11 | 341524.15 | 19-OCT-15:03 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 2676.78 | 167520.23 | 01-NOV-15:02 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 343.32 | 20706.73 | 05-DEC-19:03 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 62232.51 | 0.00 | ||||
Minimum of Months | 343.32 | 20706.73 | 0.00 | 0.00 | ||
Maximum of Months | 218670.97 | 674048.51 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 31589.91 | 67070.35 | 31-JAN-08:00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 32312.77 | 67722.44 | 24-FEB-07:20 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 32207.51 | 67707.37 | 01-MAR-07:20 |
April | 0.00 | 0.00 | 01-APR-00:10 | 31227.92 | 66333.14 | 03-APR-07:00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 29673.51 | 63722.25 | 01-MAY-06:20 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 27951.03 | 60047.42 | 01-JUN-06:44 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26484.88 | 56434.90 | 03-JUL-06:40 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25745.26 | 54209.83 | 01-AUG-06:50 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 25866.57 | 54666.02 | 29-SEP-06:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26842.37 | 57557.27 | 31-OCT-06:15 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 28411.10 | 61111.43 | 30-NOV-07:20 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 30140.68 | 64441.85 | 29-DEC-07:20 |
Annual Sum or Average | 0.00 | 29018.26 | ||||
Minimum of Months | 0.00 | 0.00 | 25745.26 | 54209.83 | ||
Maximum of Months | 0.00 | 0.00 | 32312.77 | 67722.44 |
Report: FanReportMonthly
For: FLR_3_DOAS FAN
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.271000E+10 | 0.73 | 1299.30 | 01-JAN-19:20 | 0.92 |
February | 0.244774E+10 | 0.73 | 1299.30 | 01-FEB-09:20 | 0.92 |
March | 0.271000E+10 | 0.73 | 1299.30 | 16-MAR-08:15 | 0.92 |
April | 0.262258E+10 | 0.72 | 1299.30 | 13-APR-15:03 | 0.92 |
May | 0.271000E+10 | 0.72 | 1299.30 | 05-MAY-15:03 | 0.92 |
June | 0.262258E+10 | 0.72 | 1299.30 | 03-JUN-08:06 | 0.91 |
July | 0.271000E+10 | 0.72 | 1299.30 | 03-JUL-15:15 | 0.91 |
August | 0.271000E+10 | 0.72 | 1299.30 | 07-AUG-15:03 | 0.91 |
September | 0.262258E+10 | 0.72 | 1299.30 | 03-SEP-08:03 | 0.91 |
October | 0.271000E+10 | 0.72 | 1299.30 | 01-OCT-18:03 | 0.91 |
November | 0.262258E+10 | 0.72 | 1299.30 | 25-NOV-16:20 | 0.92 |
December | 0.271000E+10 | 0.73 | 1299.30 | 01-DEC-16:20 | 0.92 |
Annual Sum or Average | 0.319080E+11 | 0.72 | |||
Minimum of Months | 0.244774E+10 | 0.72 | 1299.30 | 0.91 | |
Maximum of Months | 0.271000E+10 | 0.73 | 1299.30 | 0.92 |
Report: FanReportMonthly
For: VAV WITH REHEAT FAN
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.294978E+11 | 0.76 | 16956.05 | 19-JAN-21:10 | 0.96 |
February | 0.279124E+11 | 0.78 | 17370.59 | 21-FEB-19:30 | 0.97 |
March | 0.322452E+11 | 0.79 | 18320.24 | 31-MAR-21:20 | 1.00 |
April | 0.328801E+11 | 0.81 | 23337.00 | 13-APR-21:10 | 1.16 |
May | 0.364316E+11 | 0.84 | 26787.45 | 18-MAY-21:10 | 1.25 |
June | 0.363706E+11 | 0.85 | 27937.30 | 30-JUN-21:10 | 1.28 |
July | 0.382489E+11 | 0.86 | 28272.19 | 24-JUL-21:10 | 1.29 |
August | 0.381784E+11 | 0.86 | 29612.09 | 25-AUG-21:10 | 1.32 |
September | 0.354863E+11 | 0.84 | 29144.92 | 01-SEP-21:10 | 1.31 |
October | 0.349698E+11 | 0.82 | 26473.13 | 19-OCT-21:10 | 1.24 |
November | 0.320160E+11 | 0.80 | 20551.78 | 01-NOV-21:10 | 1.06 |
December | 0.299462E+11 | 0.76 | 17542.58 | 06-DEC-21:10 | 0.98 |
Annual Sum or Average | 0.404183E+12 | 0.82 | |||
Minimum of Months | 0.279124E+11 | 0.76 | 16956.05 | 0.96 | |
Maximum of Months | 0.382489E+11 | 0.86 | 29612.09 | 1.32 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205205E+09 | 0.28 | 76.61 | 01-JAN-00:03 | 0.28 |
February | 0.185347E+09 | 0.28 | 76.61 | 01-FEB-00:03 | 0.28 |
March | 0.205205E+09 | 0.28 | 76.61 | 01-MAR-00:05 | 0.28 |
April | 0.198586E+09 | 0.28 | 76.61 | 01-APR-00:10 | 0.28 |
May | 0.205205E+09 | 0.28 | 76.61 | 01-MAY-00:05 | 0.28 |
June | 0.198586E+09 | 0.28 | 76.61 | 01-JUN-00:05 | 0.28 |
July | 0.205205E+09 | 0.28 | 76.61 | 01-JUL-00:10 | 0.28 |
August | 0.205205E+09 | 0.28 | 76.61 | 01-AUG-00:05 | 0.27 |
September | 0.198586E+09 | 0.28 | 76.61 | 01-SEP-00:05 | 0.27 |
October | 0.205205E+09 | 0.28 | 76.61 | 01-OCT-00:10 | 0.28 |
November | 0.198586E+09 | 0.28 | 76.61 | 01-NOV-00:05 | 0.28 |
December | 0.205205E+09 | 0.28 | 76.61 | 01-DEC-00:03 | 0.28 |
Annual Sum or Average | 0.241613E+10 | 0.28 | |||
Minimum of Months | 0.185347E+09 | 0.28 | 76.61 | 0.27 | |
Maximum of Months | 0.205205E+09 | 0.28 | 76.61 | 0.28 |
Report: FanReportMonthly
For: LOBBY_FLR_1 EXHAUST FAN
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:05 | -0.0 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:05 | -0.0 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:05 | -0.0 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 EXHAUST FAN
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 EXHAUST FAN
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116283E+10 | 0.20 | 612.92 | 01-JAN-07:03 | 0.28 |
February | 0.105030E+10 | 0.20 | 612.92 | 01-FEB-07:05 | 0.28 |
March | 0.116283E+10 | 0.20 | 612.92 | 01-MAR-07:05 | 0.28 |
April | 0.112532E+10 | 0.20 | 612.92 | 01-APR-06:05 | 0.28 |
May | 0.116283E+10 | 0.20 | 612.92 | 01-MAY-06:05 | 0.28 |
June | 0.112532E+10 | 0.19 | 612.92 | 01-JUN-06:05 | 0.28 |
July | 0.116283E+10 | 0.19 | 612.92 | 01-JUL-06:10 | 0.28 |
August | 0.116283E+10 | 0.19 | 612.92 | 01-AUG-06:05 | 0.27 |
September | 0.112532E+10 | 0.20 | 612.92 | 01-SEP-06:05 | 0.27 |
October | 0.116283E+10 | 0.20 | 612.92 | 01-OCT-06:10 | 0.28 |
November | 0.112532E+10 | 0.20 | 612.92 | 01-NOV-06:05 | 0.28 |
December | 0.116283E+10 | 0.20 | 612.92 | 01-DEC-07:05 | 0.28 |
Annual Sum or Average | 0.136914E+11 | 0.20 | |||
Minimum of Months | 0.105030E+10 | 0.19 | 612.92 | 0.27 | |
Maximum of Months | 0.116283E+10 | 0.20 | 612.92 | 0.28 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.785295E+09 | 0.53 | 932.05 | 01-JAN-09:02 | 0.60 |
February | 0.439439E+09 | 0.48 | 932.05 | 01-FEB-09:02 | 0.60 |
March | 0.345480E+09 | 0.47 | 932.05 | 01-MAR-09:02 | 0.60 |
April | 0.244914E+09 | 0.48 | 932.05 | 02-APR-08:62 | 0.60 |
May | 0.329333E+09 | 0.54 | 932.05 | 01-MAY-15:01 | 0.60 |
June | 0.380698E+09 | 0.55 | 932.05 | 01-JUN-15:01 | 0.60 |
July | 0.466502E+09 | 0.56 | 932.05 | 01-JUL-08:61 | 0.60 |
August | 0.378729E+09 | 0.54 | 932.05 | 01-AUG-08:62 | 0.59 |
September | 0.232524E+09 | 0.51 | 932.05 | 01-SEP-08:62 | 0.59 |
October | 0.211846E+09 | 0.46 | 932.05 | 01-OCT-08:61 | 0.60 |
November | 0.329654E+09 | 0.46 | 932.05 | 02-NOV-08:62 | 0.60 |
December | 0.736921E+09 | 0.54 | 932.05 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.488133E+10 | 0.51 | |||
Minimum of Months | 0.211846E+09 | 0.46 | 932.05 | 0.59 | |
Maximum of Months | 0.785295E+09 | 0.56 | 932.05 | 0.60 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.961373E+09 | 0.57 | 887.80 | 01-JAN-09:02 | 0.60 |
February | 0.527999E+09 | 0.52 | 887.80 | 01-FEB-09:02 | 0.60 |
March | 0.378224E+09 | 0.48 | 887.80 | 01-MAR-09:02 | 0.60 |
April | 0.206819E+09 | 0.43 | 887.80 | 02-APR-08:62 | 0.60 |
May | 0.233885E+09 | 0.44 | 887.80 | 01-MAY-15:01 | 0.60 |
June | 0.272734E+09 | 0.42 | 887.80 | 01-JUN-08:51 | 0.60 |
July | 0.334835E+09 | 0.41 | 887.80 | 01-JUL-08:51 | 0.60 |
August | 0.241275E+09 | 0.40 | 887.80 | 01-AUG-08:51 | 0.59 |
September | 0.132733E+09 | 0.41 | 887.80 | 01-SEP-08:51 | 0.59 |
October | 0.189719E+09 | 0.43 | 887.80 | 01-OCT-15:01 | 0.60 |
November | 0.361957E+09 | 0.47 | 887.80 | 01-NOV-08:62 | 0.60 |
December | 0.863135E+09 | 0.58 | 887.80 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.470469E+10 | 0.46 | |||
Minimum of Months | 0.132733E+09 | 0.40 | 887.80 | 0.59 | |
Maximum of Months | 0.961373E+09 | 0.58 | 887.80 | 0.60 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.464375E+09 | 0.16 | 1400.15 | 13-JAN-06:00 | 0.60 |
February | 28855268.81 | 0.02 | 823.18 | 28-FEB-14:35 | 0.60 |
March | 0.212908E+09 | 0.09 | 1485.43 | 20-MAR-12:30 | 0.60 |
April | 0.716414E+09 | 0.29 | 1645.15 | 13-APR-13:00 | 0.60 |
May | 0.134248E+10 | 0.51 | 1593.75 | 18-MAY-13:05 | 0.60 |
June | 0.144378E+10 | 0.55 | 1560.99 | 30-JUN-13:00 | 0.60 |
July | 0.177605E+10 | 0.59 | 1664.75 | 23-JUL-13:20 | 0.60 |
August | 0.168887E+10 | 0.58 | 1839.15 | 25-AUG-13:00 | 0.60 |
September | 0.130269E+10 | 0.50 | 1870.69 | 01-SEP-13:10 | 0.60 |
October | 0.688082E+09 | 0.23 | 3190.28 | 22-OCT-12:15 | 0.60 |
November | 69022810.24 | 0.03 | 1331.51 | 17-NOV-12:20 | 0.60 |
December | 0.753986E+09 | 0.25 | 1479.08 | 24-DEC-06:00 | 0.60 |
Annual Sum or Average | 0.104875E+11 | 0.32 | |||
Minimum of Months | 28855268.81 | 0.02 | 823.18 | 0.60 | |
Maximum of Months | 0.177605E+10 | 0.59 | 3190.28 | 0.60 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.456364E+10 | 0.50 | 4404.35 | 01-JAN-00:31 | 0.60 |
February | 0.248423E+10 | 0.44 | 4404.35 | 01-FEB-09:02 | 0.60 |
March | 0.158218E+10 | 0.43 | 4404.35 | 01-MAR-16:01 | 0.60 |
April | 0.767601E+09 | 0.41 | 4404.35 | 01-APR-08:62 | 0.60 |
May | 0.154859E+10 | 0.39 | 4404.35 | 01-MAY-08:62 | 0.60 |
June | 0.198891E+10 | 0.38 | 4404.35 | 01-JUN-08:51 | 0.60 |
July | 0.218821E+10 | 0.37 | 4404.35 | 01-JUL-08:51 | 0.60 |
August | 0.168184E+10 | 0.35 | 4404.35 | 01-AUG-08:51 | 0.59 |
September | 0.106405E+10 | 0.37 | 4404.35 | 01-SEP-08:51 | 0.59 |
October | 0.645193E+09 | 0.42 | 4404.35 | 01-OCT-08:61 | 0.60 |
November | 0.120682E+10 | 0.42 | 4404.35 | 01-NOV-15:02 | 0.60 |
December | 0.396669E+10 | 0.48 | 4404.35 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.236880E+11 | 0.41 | |||
Minimum of Months | 0.645193E+09 | 0.35 | 4404.35 | 0.59 | |
Maximum of Months | 0.456364E+10 | 0.50 | 4404.35 | 0.60 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.766679E+09 | 0.53 | 851.55 | 01-JAN-09:02 | 0.60 |
February | 0.416703E+09 | 0.46 | 851.55 | 01-FEB-09:02 | 0.60 |
March | 0.315925E+09 | 0.47 | 851.55 | 01-MAR-09:02 | 0.60 |
April | 0.238327E+09 | 0.50 | 851.55 | 02-APR-08:62 | 0.60 |
May | 0.307366E+09 | 0.56 | 851.55 | 01-MAY-08:62 | 0.60 |
June | 0.387835E+09 | 0.57 | 851.55 | 01-JUN-08:62 | 0.60 |
July | 0.453119E+09 | 0.58 | 851.55 | 01-JUL-08:61 | 0.60 |
August | 0.354692E+09 | 0.56 | 851.55 | 01-AUG-08:62 | 0.59 |
September | 0.221806E+09 | 0.52 | 851.55 | 01-SEP-08:62 | 0.60 |
October | 0.201054E+09 | 0.46 | 851.55 | 01-OCT-08:61 | 0.60 |
November | 0.313237E+09 | 0.45 | 851.55 | 02-NOV-15:02 | 0.60 |
December | 0.707525E+09 | 0.54 | 851.55 | 01-DEC-16:02 | 0.60 |
Annual Sum or Average | 0.468427E+10 | 0.52 | |||
Minimum of Months | 0.201054E+09 | 0.45 | 851.55 | 0.59 | |
Maximum of Months | 0.766679E+09 | 0.58 | 851.55 | 0.60 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.913138E+09 | 0.58 | 809.89 | 01-JAN-09:02 | 0.60 |
February | 0.509792E+09 | 0.52 | 809.89 | 01-FEB-09:02 | 0.60 |
March | 0.346418E+09 | 0.46 | 809.89 | 01-MAR-09:02 | 0.60 |
April | 0.197661E+09 | 0.46 | 809.89 | 02-APR-08:62 | 0.60 |
May | 0.230683E+09 | 0.47 | 809.89 | 01-MAY-08:62 | 0.60 |
June | 0.299915E+09 | 0.44 | 809.89 | 01-JUN-08:51 | 0.60 |
July | 0.337299E+09 | 0.42 | 809.89 | 01-JUL-08:32 | 0.60 |
August | 0.238406E+09 | 0.41 | 809.89 | 01-AUG-08:51 | 0.59 |
September | 0.142984E+09 | 0.44 | 809.89 | 01-SEP-08:51 | 0.59 |
October | 0.183921E+09 | 0.43 | 809.89 | 01-OCT-08:61 | 0.60 |
November | 0.342773E+09 | 0.48 | 809.89 | 02-NOV-15:02 | 0.60 |
December | 0.830775E+09 | 0.57 | 809.89 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.457377E+10 | 0.47 | |||
Minimum of Months | 0.142984E+09 | 0.41 | 809.89 | 0.59 | |
Maximum of Months | 0.913138E+09 | 0.58 | 809.89 | 0.60 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.246485E+09 | 0.56 | 242.51 | 01-JAN-09:02 | 0.60 |
February | 0.138342E+09 | 0.50 | 242.51 | 01-FEB-09:02 | 0.60 |
March | 0.105977E+09 | 0.48 | 242.51 | 01-MAR-09:02 | 0.60 |
April | 72200985.02 | 0.48 | 242.51 | 02-APR-08:62 | 0.60 |
May | 87341075.50 | 0.54 | 242.51 | 01-MAY-15:01 | 0.60 |
June | 98614009.75 | 0.54 | 242.51 | 01-JUN-15:01 | 0.60 |
July | 0.118995E+09 | 0.56 | 242.51 | 01-JUL-08:61 | 0.60 |
August | 95549533.67 | 0.54 | 242.51 | 01-AUG-15:01 | 0.60 |
September | 60141472.98 | 0.51 | 242.51 | 01-SEP-08:62 | 0.59 |
October | 65695312.81 | 0.46 | 242.51 | 01-OCT-15:01 | 0.60 |
November | 0.102216E+09 | 0.48 | 242.51 | 01-NOV-08:62 | 0.60 |
December | 0.228322E+09 | 0.57 | 242.51 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.141988E+10 | 0.52 | |||
Minimum of Months | 60141472.98 | 0.46 | 242.51 | 0.59 | |
Maximum of Months | 0.246485E+09 | 0.57 | 242.51 | 0.60 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.284052E+09 | 0.59 | 230.04 | 01-JAN-09:02 | 0.60 |
February | 0.168005E+09 | 0.55 | 230.04 | 01-FEB-09:02 | 0.60 |
March | 0.117674E+09 | 0.51 | 230.04 | 01-MAR-09:02 | 0.60 |
April | 62863161.07 | 0.44 | 230.04 | 01-APR-18:03 | 0.60 |
May | 63578920.23 | 0.44 | 230.04 | 01-MAY-08:62 | 0.60 |
June | 72493201.11 | 0.42 | 230.04 | 01-JUN-08:51 | 0.60 |
July | 88642573.69 | 0.41 | 230.04 | 01-JUL-08:51 | 0.60 |
August | 61915413.99 | 0.40 | 230.04 | 01-AUG-08:51 | 0.59 |
September | 35370091.20 | 0.41 | 230.04 | 01-SEP-08:51 | 0.59 |
October | 61258767.89 | 0.43 | 230.04 | 01-OCT-15:01 | 0.60 |
November | 0.113130E+09 | 0.52 | 230.04 | 01-NOV-08:62 | 0.60 |
December | 0.264030E+09 | 0.59 | 230.04 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.139301E+10 | 0.48 | |||
Minimum of Months | 35370091.20 | 0.40 | 230.04 | 0.59 | |
Maximum of Months | 0.284052E+09 | 0.59 | 230.04 | 0.60 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.815230E+09 | 0.50 | 1186.64 | 01-JAN-09:02 | 0.60 |
February | 0.513998E+09 | 0.51 | 1186.64 | 01-FEB-09:02 | 0.60 |
March | 0.432630E+09 | 0.50 | 1186.64 | 01-MAR-16:01 | 0.60 |
April | 0.340706E+09 | 0.51 | 1186.64 | 01-APR-15:02 | 0.60 |
May | 0.392811E+09 | 0.54 | 1186.64 | 01-MAY-15:01 | 0.60 |
June | 0.426379E+09 | 0.54 | 1186.64 | 01-JUN-15:01 | 0.60 |
July | 0.529906E+09 | 0.56 | 1186.64 | 01-JUL-08:61 | 0.60 |
August | 0.498695E+09 | 0.54 | 1186.64 | 01-AUG-15:01 | 0.60 |
September | 0.369028E+09 | 0.51 | 1186.64 | 01-SEP-08:62 | 0.59 |
October | 0.338468E+09 | 0.47 | 1186.64 | 01-OCT-08:61 | 0.60 |
November | 0.391570E+09 | 0.48 | 1186.64 | 03-NOV-08:61 | 0.60 |
December | 0.797598E+09 | 0.51 | 1186.64 | 01-DEC-19:02 | 0.60 |
Annual Sum or Average | 0.584702E+10 | 0.51 | |||
Minimum of Months | 0.338468E+09 | 0.47 | 1186.64 | 0.59 | |
Maximum of Months | 0.815230E+09 | 0.56 | 1186.64 | 0.60 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.317630E+10 | 0.285867E+10 | 1951.11 | 13-JAN-06:00 | 1756.00 | 1756.00 | 35.37 | 6.26 |
February | 0.213319E+10 | 0.191987E+10 | 1851.18 | 02-FEB-09:02 | 1666.07 | 1666.07 | 36.66 | 5.96 |
March | 0.159191E+10 | 0.143272E+10 | 1840.81 | 05-MAR-07:03 | 1656.73 | 1656.73 | 35.92 | 5.93 |
April | 0.623249E+09 | 0.560924E+09 | 991.02 | 05-APR-06:10 | 891.92 | 891.92 | 36.22 | 1.41 |
May | 0.363705E+09 | 0.327334E+09 | 895.58 | 05-MAY-08:05 | 806.02 | 806.02 | 30.67 | 1.22 |
June | 0.173704E+09 | 0.156333E+09 | 721.14 | 04-JUN-06:40 | 649.03 | 649.03 | 41.27 | 0.91 |
July | 0.132550E+09 | 0.119295E+09 | 745.35 | 02-JUL-04:30 | 670.81 | 670.81 | 31.34 | 0.95 |
August | 0.133113E+09 | 0.119801E+09 | 810.75 | 19-AUG-06:20 | 729.67 | 729.67 | 41.56 | 1.06 |
September | 0.467370E+09 | 0.420633E+09 | 923.79 | 27-SEP-08:05 | 831.41 | 831.41 | 34.26 | 1.27 |
October | 0.715451E+09 | 0.643906E+09 | 1012.00 | 31-OCT-08:62 | 910.80 | 910.80 | 30.99 | 1.46 |
November | 0.128293E+10 | 0.115463E+10 | 1283.20 | 25-NOV-09:02 | 1154.88 | 1154.88 | 33.93 | 2.24 |
December | 0.301325E+10 | 0.271193E+10 | 1958.67 | 24-DEC-06:00 | 1762.81 | 1762.81 | 35.35 | 6.28 |
Annual Sum or Average | 0.138067E+11 | 0.124260E+11 | ||||||
Minimum of Months | 0.132550E+09 | 0.119295E+09 | 721.14 | 649.03 | 649.03 | 30.67 | 0.91 | |
Maximum of Months | 0.317630E+10 | 0.285867E+10 | 1958.67 | 1762.81 | 1762.81 | 41.56 | 6.28 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 24215869.88 | 21794282.89 | 512.56 | 27-JAN-16:01 | 461.30 | 461.30 | 6.72 | 1.02 |
February | 86492186.11 | 77842967.50 | 1331.73 | 28-FEB-16:06 | 1198.56 | 1198.56 | 6.72 | 2.96 |
March | 0.309573E+09 | 0.278615E+09 | 2096.30 | 26-MAR-15:01 | 1886.67 | 1886.67 | 6.72 | 5.34 |
April | 0.119090E+10 | 0.107181E+10 | 3076.28 | 23-APR-18:01 | 2768.65 | 2768.65 | 6.72 | 10.77 |
May | 0.340403E+10 | 0.306363E+10 | 3274.33 | 10-MAY-18:01 | 2946.90 | 2946.90 | 6.72 | 13.04 |
June | 0.472332E+10 | 0.425099E+10 | 3475.29 | 29-JUN-18:03 | 3127.76 | 3127.76 | 6.72 | 16.77 |
July | 0.574041E+10 | 0.516637E+10 | 3463.79 | 21-JUL-19:20 | 3117.41 | 3117.41 | 6.72 | 16.52 |
August | 0.483519E+10 | 0.435167E+10 | 3358.12 | 08-AUG-18:03 | 3022.31 | 3022.31 | 6.72 | 14.39 |
September | 0.258058E+10 | 0.232252E+10 | 3159.96 | 01-SEP-15:13 | 2843.96 | 2843.96 | 6.72 | 11.61 |
October | 0.924186E+09 | 0.831768E+09 | 3190.07 | 19-OCT-15:01 | 2871.06 | 2871.06 | 6.72 | 11.95 |
November | 0.141579E+09 | 0.127421E+09 | 2122.69 | 01-NOV-15:02 | 1910.42 | 1910.42 | 6.72 | 5.44 |
December | 14894156.97 | 13404741.27 | 548.45 | 05-DEC-19:03 | 493.61 | 493.61 | 6.72 | 1.10 |
Annual Sum or Average | 0.239754E+11 | 0.215778E+11 | ||||||
Minimum of Months | 14894156.97 | 13404741.27 | 512.56 | 461.30 | 461.30 | 6.72 | 1.02 | |
Maximum of Months | 0.574041E+10 | 0.516637E+10 | 3475.29 | 3127.76 | 3127.76 | 6.72 | 16.77 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.661815E+09 | 0.595634E+09 | 3026.11 | 01-JAN-10:21 | 2723.50 | 2723.50 | 6.74 | 26.77 |
February | 0.162017E+10 | 0.145815E+10 | 3026.11 | 01-FEB-10:35 | 2723.50 | 2723.50 | 6.73 | 26.77 |
March | 0.253583E+10 | 0.228224E+10 | 3026.11 | 01-MAR-09:03 | 2723.50 | 2723.50 | 6.82 | 26.77 |
April | 0.518574E+10 | 0.466716E+10 | 3026.11 | 01-APR-00:10 | 2723.50 | 2723.50 | 6.73 | 26.77 |
May | 0.799778E+10 | 0.719800E+10 | 3026.11 | 01-MAY-00:05 | 2723.50 | 2723.50 | 6.74 | 26.77 |
June | 0.784369E+10 | 0.705932E+10 | 3026.11 | 01-JUN-00:05 | 2723.50 | 2723.50 | 6.83 | 26.77 |
July | 0.810514E+10 | 0.729463E+10 | 3026.11 | 01-JUL-00:10 | 2723.50 | 2723.50 | 7.51 | 26.77 |
August | 0.809425E+10 | 0.728482E+10 | 3026.11 | 01-AUG-00:05 | 2723.50 | 2723.50 | 7.65 | 26.77 |
September | 0.766787E+10 | 0.690108E+10 | 3026.11 | 01-SEP-00:05 | 2723.50 | 2723.50 | 8.81 | 26.77 |
October | 0.483534E+10 | 0.435181E+10 | 3026.11 | 01-OCT-00:10 | 2723.50 | 2723.50 | 6.87 | 26.77 |
November | 0.174957E+10 | 0.157461E+10 | 3026.11 | 01-NOV-05:03 | 2723.50 | 2723.50 | 6.74 | 26.77 |
December | 0.470898E+09 | 0.423808E+09 | 3026.11 | 01-DEC-09:03 | 2723.50 | 2723.50 | 6.78 | 26.77 |
Annual Sum or Average | 0.567681E+11 | 0.510913E+11 | ||||||
Minimum of Months | 0.470898E+09 | 0.423808E+09 | 3026.11 | 2723.50 | 2723.50 | 6.73 | 26.77 | |
Maximum of Months | 0.810514E+10 | 0.729463E+10 | 3026.11 | 2723.50 | 2723.50 | 8.81 | 26.77 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:03 | 14.37 | 14.37 | 46.35 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:03 | 14.37 | 14.37 | 47.40 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:05 | 14.37 | 14.37 | 47.55 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 50.99 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:05 | 14.37 | 14.37 | 51.08 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:05 | 14.37 | 14.37 | 51.60 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 52.32 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:05 | 14.37 | 14.37 | 52.42 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:05 | 14.37 | 14.37 | 52.51 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:10 | 14.37 | 14.37 | 51.68 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:05 | 14.37 | 14.37 | 51.94 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:03 | 14.37 | 14.37 | 48.50 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 46.35 | 0.37 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 52.51 | 0.37 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 35.78 | 60.00 | 253103.16 | 655634.37 | 09-JAN-05:00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 36.64 | 60.00 | 154309.59 | 628235.66 | 14-FEB-07:00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 42.95 | 60.00 | 83986.69 | 599727.90 | 05-MAR-07:00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 53.19 | 60.00 | 26789.27 | 174279.17 | 05-APR-08:61 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 49.71 | 60.00 | 19730.75 | 148976.28 | 05-MAY-08:05 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 28.20 | 60.00 | 10076.87 | 111296.39 | 16-JUN-22:20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 34.11 | 34.11 | 7493.82 | 113549.49 | 02-JUL-04:30 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 30.40 | 30.40 | 7416.67 | 110390.72 | 19-AUG-00:30 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 32.41 | 32.41 | 26080.26 | 148452.77 | 25-SEP-08:05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 30.95 | 60.00 | 30111.82 | 176598.60 | 31-OCT-08:62 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 47.83 | 60.00 | 57019.21 | 243842.37 | 25-NOV-09:02 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 37.78 | 60.00 | 224767.27 | 646733.32 | 24-DEC-06:00 |
Annual Sum or Average | 0.00 | 74916.58 | ||||||
Minimum of Months | 0.00 | 0.00 | 28.20 | 30.40 | 7416.67 | 110390.72 | ||
Maximum of Months | 0.00 | 0.00 | 53.19 | 60.00 | 253103.16 | 655634.37 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 539.66 | 24162.67 | 27-JAN-16:01 | 6.92 | 6.70 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 1852.75 | 72057.64 | 28-FEB-16:06 | 7.34 | 6.70 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 5200.78 | 120302.30 | 31-MAR-15:01 | 7.77 | 6.70 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 23769.63 | 382340.52 | 23-APR-18:03 | 10.11 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 83603.64 | 492786.42 | 25-MAY-18:03 | 11.09 | 6.70 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 168074.17 | 674048.51 | 29-JUN-18:03 | 12.71 | 6.70 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 218670.97 | 661693.13 | 21-JUL-19:20 | 12.60 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 159439.63 | 588139.72 | 08-AUG-15:03 | 11.95 | 6.70 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 59507.98 | 443607.93 | 01-SEP-15:03 | 10.65 | 6.70 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 17432.11 | 341524.15 | 19-OCT-15:03 | 9.74 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 2676.78 | 167520.23 | 01-NOV-15:02 | 8.19 | 6.70 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 343.32 | 20706.73 | 05-DEC-19:03 | 6.88 | 6.70 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 62232.51 | 0.00 | ||||||
Minimum of Months | 343.32 | 20706.73 | 6.88 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 218670.97 | 674048.51 | 12.71 | 6.70 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 46.35 | 60.05 | 31589.91 | 67070.35 | 31-JAN-08:00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 47.40 | 60.05 | 32312.77 | 67722.44 | 24-FEB-07:20 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 47.55 | 60.05 | 32207.51 | 67707.37 | 01-MAR-07:20 |
April | 0.00 | 0.00 | 01-APR-00:10 | 50.99 | 60.05 | 31227.92 | 66333.14 | 03-APR-07:00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 51.08 | 60.05 | 29673.51 | 63722.25 | 01-MAY-06:20 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 51.60 | 60.05 | 27951.03 | 60047.42 | 01-JUN-06:44 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 52.32 | 60.05 | 26484.88 | 56434.90 | 03-JUL-06:40 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 52.42 | 60.05 | 25745.26 | 54209.83 | 01-AUG-06:50 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 52.51 | 60.05 | 25866.57 | 54666.02 | 29-SEP-06:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 51.68 | 60.05 | 26842.37 | 57557.27 | 31-OCT-06:15 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 51.94 | 60.05 | 28411.10 | 61111.43 | 30-NOV-07:20 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 48.50 | 60.05 | 30140.68 | 64441.85 | 29-DEC-07:20 |
Annual Sum or Average | 0.00 | 29018.26 | ||||||
Minimum of Months | 0.00 | 0.00 | 46.35 | 60.05 | 25745.26 | 54209.83 | ||
Maximum of Months | 0.00 | 0.00 | 52.51 | 60.05 | 32312.77 | 67722.44 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.272126E+11 | 0.00 | 0.00 | 0.271000E+10 | 0.00 | 0.00 |
February | 0.146016E+11 | 0.00 | 0.00 | 0.244774E+10 | 0.00 | 0.00 |
March | 0.757299E+10 | 0.00 | 0.00 | 0.271000E+10 | 0.00 | 0.00 |
April | 0.825859E+09 | 0.00 | 0.823559E+09 | 0.262258E+10 | 0.00 | 0.00 |
May | 17222180.67 | 0.00 | 0.698346E+10 | 0.271000E+10 | 0.00 | 0.00 |
June | 21140.94 | 0.00 | 0.193787E+11 | 0.262258E+10 | 0.00 | 0.00 |
July | 23322.75 | 0.00 | 0.280739E+11 | 0.271000E+10 | 0.00 | 0.00 |
August | 22703.79 | 0.00 | 0.191298E+11 | 0.271000E+10 | 0.00 | 0.00 |
September | 6269.82 | 0.00 | 0.390652E+10 | 0.262258E+10 | 0.00 | 0.00 |
October | 0.254204E+09 | 0.00 | 0.525223E+09 | 0.271000E+10 | 0.00 | 0.00 |
November | 0.312915E+10 | 0.00 | 78594968.24 | 0.262258E+10 | 0.00 | 0.00 |
December | 0.232925E+11 | 0.00 | 0.00 | 0.271000E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.769062E+11 | 0.00 | 0.788998E+11 | 0.319080E+11 | 0.00 | 0.00 |
Minimum of Months | 6269.82 | 0.00 | 0.00 | 0.244774E+10 | 0.00 | 0.00 |
Maximum of Months | 0.272126E+11 | 0.00 | 0.280739E+11 | 0.271000E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.533676E+12 | 0.00 | 0.00 | 0.294978E+11 | 0.00 | 0.00 |
February | 0.290528E+12 | 0.00 | 0.00 | 0.279124E+11 | 0.00 | 0.00 |
March | 0.172205E+12 | 0.00 | 0.00 | 0.322452E+11 | 0.00 | 0.00 |
April | 0.576472E+11 | 0.00 | 0.135661E+11 | 0.328801E+11 | 0.00 | 0.00 |
May | 0.525157E+11 | 0.00 | 0.104453E+12 | 0.364316E+11 | 0.00 | 0.00 |
June | 0.261648E+11 | 0.00 | 0.275197E+12 | 0.363706E+11 | 0.00 | 0.00 |
July | 0.201752E+11 | 0.00 | 0.385290E+12 | 0.382489E+11 | 0.00 | 0.00 |
August | 0.198315E+11 | 0.00 | 0.261261E+12 | 0.381784E+11 | 0.00 | 0.00 |
September | 0.669385E+11 | 0.00 | 0.588244E+11 | 0.354863E+11 | 0.00 | 0.00 |
October | 0.688652E+11 | 0.00 | 0.829179E+10 | 0.349698E+11 | 0.00 | 0.00 |
November | 0.103144E+12 | 0.00 | 0.105207E+10 | 0.320160E+11 | 0.00 | 0.00 |
December | 0.465134E+12 | 0.00 | 0.00 | 0.299462E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.187682E+13 | 0.00 | 0.110793E+13 | 0.404183E+12 | 0.00 | 0.00 |
Minimum of Months | 0.198315E+11 | 0.00 | 0.00 | 0.279124E+11 | 0.00 | 0.00 |
Maximum of Months | 0.533676E+12 | 0.00 | 0.385290E+12 | 0.382489E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.271000E+10 | 0.00 | 0.272126E+11 | 0.633128E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244774E+10 | 0.00 | 0.146016E+11 | 0.633954E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.271000E+10 | 0.00 | 0.757299E+10 | 0.677807E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.262258E+10 | 0.823559E+09 | 0.825859E+09 | 0.433977E+11 | 54918843.24 | 0.00 | 0.00 | 0.00 |
May | 0.271000E+10 | 0.698346E+10 | 17222180.67 | 0.156904E+11 | 0.635915E+09 | 0.00 | 0.00 | 0.00 |
June | 0.262258E+10 | 0.193787E+11 | 21140.94 | 0.457893E+10 | 0.460402E+10 | 0.00 | 0.00 | 0.00 |
July | 0.271000E+10 | 0.280739E+11 | 23322.75 | 0.199690E+10 | 0.608747E+10 | 0.00 | 0.00 | 0.00 |
August | 0.271000E+10 | 0.191298E+11 | 22703.79 | 0.238559E+10 | 0.243087E+10 | 0.00 | 0.00 | 0.00 |
September | 0.262258E+10 | 0.390652E+10 | 6269.82 | 0.146256E+11 | 80328436.17 | 0.00 | 0.00 | 0.00 |
October | 0.271000E+10 | 0.525223E+09 | 0.254204E+09 | 0.393056E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.262258E+10 | 78594968.24 | 0.312915E+10 | 0.592342E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.271000E+10 | 0.00 | 0.232925E+11 | 0.645117E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319080E+11 | 0.788998E+11 | 0.769062E+11 | 0.440216E+12 | 0.138935E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244774E+10 | 0.00 | 6269.82 | 0.199690E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.271000E+10 | 0.280739E+11 | 0.272126E+11 | 0.677807E+11 | 0.608747E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.294978E+11 | 0.00 | 0.533676E+12 | 0.743749E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.279124E+11 | 0.00 | 0.290528E+12 | 0.734608E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.322452E+11 | 0.00 | 0.172205E+12 | 0.784206E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.328801E+11 | 0.135661E+11 | 0.576472E+11 | 0.461501E+12 | 88330314.63 | 0.00 | 0.00 | 0.00 |
May | 0.364316E+11 | 0.104453E+12 | 0.525157E+11 | 0.111672E+12 | 0.253138E+10 | 0.00 | 0.00 | 0.00 |
June | 0.363706E+11 | 0.275197E+12 | 0.261648E+11 | 0.208564E+11 | 0.394466E+11 | 0.00 | 0.00 | 0.00 |
July | 0.382489E+11 | 0.385290E+12 | 0.201752E+11 | 0.149968E+10 | 0.520403E+11 | 0.00 | 0.00 | 0.00 |
August | 0.381784E+11 | 0.261261E+12 | 0.198315E+11 | 0.652266E+10 | 0.185127E+11 | 0.00 | 0.00 | 0.00 |
September | 0.354863E+11 | 0.588244E+11 | 0.669385E+11 | 0.911922E+11 | 0.120647E+09 | 0.00 | 0.00 | 0.00 |
October | 0.349698E+11 | 0.829179E+10 | 0.688652E+11 | 0.399595E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.320160E+11 | 0.105207E+10 | 0.103144E+12 | 0.677966E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.299462E+11 | 0.00 | 0.465134E+12 | 0.759574E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.404183E+12 | 0.110793E+13 | 0.187682E+13 | 0.479294E+13 | 0.112740E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.279124E+11 | 0.00 | 0.198315E+11 | 0.149968E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.382489E+11 | 0.385290E+12 | 0.533676E+12 | 0.784206E+12 | 0.520403E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.271000E+10 | 0.272126E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244774E+10 | 0.146016E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.271000E+10 | 0.757299E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.262258E+10 | 0.825859E+09 | 0.823559E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.271000E+10 | 17222180.67 | 0.698346E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.262258E+10 | 21140.94 | 0.193787E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.271000E+10 | 23322.75 | 0.280739E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.271000E+10 | 22703.79 | 0.191298E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.262258E+10 | 6269.82 | 0.390652E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.271000E+10 | 0.254204E+09 | 0.525223E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.262258E+10 | 0.312915E+10 | 78594968.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.271000E+10 | 0.232925E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319080E+11 | 0.769062E+11 | 0.788998E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244774E+10 | 6269.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.271000E+10 | 0.272126E+11 | 0.280739E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.294978E+11 | 0.533676E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.279124E+11 | 0.290528E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.322452E+11 | 0.172205E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.328801E+11 | 0.576472E+11 | 0.135661E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.364316E+11 | 0.525157E+11 | 0.104453E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.363706E+11 | 0.261648E+11 | 0.275197E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.382489E+11 | 0.201752E+11 | 0.385290E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.381784E+11 | 0.198315E+11 | 0.261261E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.354863E+11 | 0.669385E+11 | 0.588244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.349698E+11 | 0.688652E+11 | 0.829179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.320160E+11 | 0.103144E+12 | 0.105207E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.299462E+11 | 0.465134E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.404183E+12 | 0.187682E+13 | 0.110793E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.279124E+11 | 0.198315E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.382489E+11 | 0.533676E+12 | 0.385290E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.567635E+11 | 0.00 | 0.00 | 1167884.69 | 0.00 | 0.352313E+11 | 0.280762E+10 | 0.00 | 0.97 |
February | 0.603739E+11 | 0.00 | 0.00 | 399252.59 | 0.00 | 0.372966E+10 | 0.209168E+10 | 0.00 | 0.97 |
March | 0.582633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250627E+09 | 0.00 | 0.00 | 0.97 |
April | 0.469080E+11 | 0.00 | 0.00 | 0.00 | 70979.43 | 0.00 | 0.00 | 0.00 | 0.97 |
May | 0.422004E+11 | 0.00 | 0.00 | 0.00 | 0.114958E+09 | 0.00 | 0.00 | 0.00 | 0.98 |
June | 0.269223E+11 | 0.115107E+09 | 0.00 | 107693.02 | 0.383087E+10 | 0.00 | 0.804632E+09 | 0.00 | 0.98 |
July | 0.123239E+11 | 0.149880E+10 | 0.00 | 9640243.22 | 0.503306E+10 | 0.00 | 0.100646E+11 | 0.00 | 0.99 |
August | 0.317021E+10 | 0.116821E+10 | 0.00 | 42020494.73 | 0.142468E+10 | 0.00 | 0.271906E+11 | 0.00 | 1.03 |
September | 0.211051E+10 | 777032.32 | 0.00 | 61267732.06 | 15950358.39 | 0.00 | 0.487923E+11 | 0.00 | 1.07 |
October | 0.171801E+10 | 0.00 | 0.00 | 63201771.45 | 0.00 | 0.00 | 0.538938E+11 | 0.00 | 1.08 |
November | 0.261241E+10 | 0.00 | 0.00 | 57083647.58 | 0.00 | 0.00 | 0.516356E+11 | 0.00 | 1.06 |
December | 0.622207E+11 | 0.00 | 0.00 | 7095467.46 | 0.00 | 0.136716E+11 | 0.118188E+11 | 0.00 | 0.97 |
Annual Sum or Average | 0.375587E+12 | 0.278289E+10 | 0.00 | 0.241984E+09 | 0.104196E+11 | 0.528832E+11 | 0.209100E+12 | 0.00 | 1.00 |
Minimum of Months | 0.171801E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.97 |
Maximum of Months | 0.622207E+11 | 0.149880E+10 | 0.00 | 63201771.45 | 0.503306E+10 | 0.352313E+11 | 0.538938E+11 | 0.00 | 1.08 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.193928E+10 | 0.00 | 0.00 | 72754.89 | 0.00 | 0.144366E+11 | 0.170045E+09 | 0.00 | 3.04 |
February | 0.370174E+10 | 0.00 | 0.00 | 747803.32 | 0.00 | 0.725742E+10 | 0.684090E+09 | 0.00 | 3.09 |
March | 0.573917E+10 | 0.00 | 0.00 | 985135.34 | 0.00 | 0.379472E+10 | 0.775152E+09 | 0.00 | 3.09 |
April | 0.692394E+10 | 12376.64 | 0.00 | 1632034.25 | 0.00 | 0.365177E+09 | 0.102503E+10 | 0.00 | 3.14 |
May | 0.680989E+10 | 19035588.81 | 0.00 | 1593945.45 | 3232094.10 | 0.00 | 0.590855E+09 | 0.00 | 3.14 |
June | 0.457228E+10 | 0.435077E+09 | 0.00 | 858047.30 | 0.301692E+09 | 0.00 | 0.266825E+09 | 0.00 | 3.13 |
July | 0.355876E+10 | 0.709956E+09 | 0.00 | 957077.77 | 0.493304E+09 | 0.00 | 0.344158E+09 | 0.00 | 3.19 |
August | 0.459409E+10 | 0.303382E+09 | 0.00 | 1902609.10 | 0.166911E+09 | 0.00 | 0.504054E+09 | 0.00 | 3.22 |
September | 0.718652E+10 | 3919717.02 | 0.00 | 2668235.91 | 23513.10 | 0.00 | 0.105107E+10 | 0.00 | 3.22 |
October | 0.780732E+10 | 0.00 | 0.00 | 1964278.36 | 0.00 | 0.188924E+09 | 0.979160E+09 | 0.00 | 3.18 |
November | 0.547172E+10 | 0.00 | 0.00 | 543677.51 | 0.00 | 0.280558E+10 | 0.468910E+09 | 0.00 | 3.09 |
December | 0.160967E+10 | 0.00 | 0.00 | 12777.63 | 0.00 | 0.135576E+11 | 49884837.66 | 0.00 | 3.03 |
Annual Sum or Average | 0.599144E+11 | 0.147138E+10 | 0.00 | 13938376.82 | 0.965163E+09 | 0.424060E+11 | 0.690924E+10 | 0.00 | 3.13 |
Minimum of Months | 0.160967E+10 | 0.00 | 0.00 | 12777.63 | 0.00 | 0.00 | 49884837.66 | 0.00 | 3.03 |
Maximum of Months | 0.780732E+10 | 0.709956E+09 | 0.00 | 2668235.91 | 0.493304E+09 | 0.144366E+11 | 0.105107E+10 | 0.00 | 3.22 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.449404E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.424396E+10 | 0.00 | 0.00 | 1.39 |
February | 0.480072E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130447E+10 | 0.00 | 0.00 | 1.39 |
March | 0.506033E+10 | 0.00 | 0.00 | 18752.75 | 0.00 | 0.262121E+09 | 69810197.53 | 0.00 | 1.40 |
April | 0.376358E+10 | 0.00 | 0.00 | 404706.73 | 6538.71 | 0.00 | 0.563205E+09 | 0.00 | 1.41 |
May | 0.231159E+10 | 5114601.53 | 0.00 | 1818703.93 | 5625556.10 | 0.00 | 0.163150E+10 | 0.00 | 1.44 |
June | 0.130939E+10 | 0.245288E+09 | 0.00 | 1756817.10 | 0.141025E+09 | 0.00 | 0.129129E+10 | 0.00 | 1.46 |
July | 0.538234E+09 | 0.437202E+09 | 0.00 | 2470769.52 | 0.202225E+09 | 0.00 | 0.159407E+10 | 0.00 | 1.49 |
August | 0.866878E+09 | 0.126912E+09 | 0.00 | 2578763.98 | 0.110953E+09 | 0.00 | 0.188588E+10 | 0.00 | 1.47 |
September | 0.257679E+10 | 112585.83 | 0.00 | 1401094.58 | 1429118.83 | 0.00 | 0.173536E+10 | 0.00 | 1.43 |
October | 0.397565E+10 | 0.00 | 0.00 | 368699.30 | 0.00 | 0.00 | 0.655166E+09 | 0.00 | 1.41 |
November | 0.457685E+10 | 0.00 | 0.00 | 3714.83 | 0.00 | 0.00 | 15910506.12 | 0.00 | 1.40 |
December | 0.461291E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.342571E+10 | 0.00 | 0.00 | 1.39 |
Annual Sum or Average | 0.388870E+11 | 0.814629E+09 | 0.00 | 10822022.73 | 0.461263E+09 | 0.923626E+10 | 0.944220E+10 | 0.00 | 1.42 |
Minimum of Months | 0.538234E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.39 |
Maximum of Months | 0.506033E+10 | 0.437202E+09 | 0.00 | 2578763.98 | 0.202225E+09 | 0.424396E+10 | 0.188588E+10 | 0.00 | 1.49 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.817109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.585598E+10 | 0.00 | 0.00 | 0.50 |
February | 0.174780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291190E+10 | 0.00 | 0.00 | 0.50 |
March | 0.288525E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123028E+10 | 0.00 | 0.00 | 0.50 |
April | 0.329751E+10 | 0.00 | 0.00 | 0.00 | 4989.67 | 0.00 | 0.00 | 0.00 | 0.50 |
May | 0.287755E+10 | 328264.77 | 0.00 | 131173.40 | 7752963.95 | 0.00 | 90409867.27 | 0.00 | 0.51 |
June | 0.187554E+10 | 0.144310E+09 | 0.00 | 205384.68 | 0.146001E+09 | 0.00 | 78544960.11 | 0.00 | 0.52 |
July | 0.118539E+10 | 0.191365E+09 | 0.00 | 724097.83 | 0.283300E+09 | 0.00 | 0.395845E+09 | 0.00 | 0.52 |
August | 0.183114E+10 | 28488345.11 | 0.00 | 360892.83 | 0.147370E+09 | 0.00 | 0.214991E+09 | 0.00 | 0.51 |
September | 0.320406E+10 | 20906.33 | 0.00 | 51197.93 | 1154986.14 | 0.00 | 48035381.72 | 0.00 | 0.51 |
October | 0.352468E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 |
November | 0.308221E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.422513E+09 | 0.00 | 0.00 | 0.51 |
December | 0.106118E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.507573E+10 | 0.00 | 0.00 | 0.50 |
Annual Sum or Average | 0.273894E+11 | 0.364512E+09 | 0.00 | 1472746.67 | 0.585584E+09 | 0.154964E+11 | 0.827826E+09 | 0.00 | 0.51 |
Minimum of Months | 0.817109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 |
Maximum of Months | 0.352468E+10 | 0.191365E+09 | 0.00 | 724097.83 | 0.283300E+09 | 0.585598E+10 | 0.395845E+09 | 0.00 | 0.52 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 27787067.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.397124E+10 | 0.00 | 0.00 | 0.52 |
February | 0.374833E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241729E+10 | 0.00 | 0.00 | 0.52 |
March | 0.995940E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146924E+10 | 0.00 | 0.00 | 0.52 |
April | 0.190652E+10 | 0.00 | 0.00 | 0.00 | 2988.38 | 68402671.77 | 0.00 | 0.00 | 0.52 |
May | 0.177605E+10 | 0.00 | 0.00 | 57.72 | 4839950.03 | 0.00 | 672088.09 | 0.00 | 0.53 |
June | 0.115841E+10 | 59427963.56 | 0.00 | 34457.82 | 0.108210E+09 | 0.00 | 9519855.89 | 0.00 | 0.53 |
July | 0.919902E+09 | 38840695.18 | 0.00 | 20875.75 | 0.235538E+09 | 0.00 | 19654356.26 | 0.00 | 0.53 |
August | 0.122326E+10 | 1587335.14 | 0.00 | 112.64 | 0.102532E+09 | 0.00 | 27298.71 | 0.00 | 0.53 |
September | 0.194661E+10 | 0.00 | 0.00 | 0.00 | 704256.86 | 0.00 | 0.00 | 0.00 | 0.53 |
October | 0.211098E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
November | 0.132963E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.769397E+09 | 0.00 | 0.00 | 0.52 |
December | 63131954.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.361432E+10 | 0.00 | 0.00 | 0.52 |
Annual Sum or Average | 0.138331E+11 | 99855993.88 | 0.00 | 55503.93 | 0.451827E+09 | 0.123099E+11 | 29873598.95 | 0.00 | 0.53 |
Minimum of Months | 27787067.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
Maximum of Months | 0.211098E+10 | 59427963.56 | 0.00 | 34457.82 | 0.235538E+09 | 0.397124E+10 | 19654356.26 | 0.00 | 0.53 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.915789E+10 | 0.00 | 0.00 | 73632384.37 | 0.00 | 0.368825E+11 | 0.890757E+11 | 0.00 | 22.16 |
February | 0.494949E+10 | 0.00 | 0.00 | 78199799.67 | 0.00 | 0.122421E+11 | 0.818904E+11 | 0.00 | 23.03 |
March | 0.280919E+10 | 0.00 | 0.00 | 95720294.96 | 0.00 | 0.356890E+10 | 0.840735E+11 | 0.00 | 23.54 |
April | 0.148270E+09 | 92945.46 | 0.00 | 0.100173E+09 | 0.00 | 0.00 | 0.733323E+11 | 0.00 | 23.69 |
May | 43131931.92 | 0.161717E+09 | 0.00 | 0.122146E+09 | 0.00 | 0.00 | 0.663639E+11 | 0.00 | 23.87 |
June | 26096361.05 | 0.627335E+10 | 0.00 | 0.100824E+09 | 6755055.22 | 0.00 | 0.427440E+11 | 0.00 | 23.84 |
July | 29021674.73 | 0.104082E+11 | 0.00 | 88126012.62 | 18227580.55 | 0.00 | 0.337582E+11 | 0.00 | 23.85 |
August | 20817163.18 | 0.398778E+10 | 0.00 | 0.103928E+09 | 7188652.84 | 0.00 | 0.446333E+11 | 0.00 | 23.96 |
September | 18815519.13 | 22204577.85 | 0.00 | 0.108983E+09 | 0.00 | 0.00 | 0.731363E+11 | 0.00 | 23.92 |
October | 0.129194E+09 | 0.00 | 0.00 | 97086137.92 | 0.00 | 0.00 | 0.784427E+11 | 0.00 | 23.72 |
November | 0.223577E+09 | 0.00 | 0.00 | 94017346.53 | 0.00 | 0.00 | 0.775017E+11 | 0.00 | 23.70 |
December | 0.117787E+11 | 0.00 | 0.00 | 76015433.61 | 0.00 | 0.249040E+11 | 0.895271E+11 | 0.00 | 22.42 |
Annual Sum or Average | 0.293342E+11 | 0.208534E+11 | 0.00 | 0.113885E+10 | 32171288.62 | 0.775975E+11 | 0.834479E+12 | 0.00 | 23.48 |
Minimum of Months | 18815519.13 | 0.00 | 0.00 | 73632384.37 | 0.00 | 0.00 | 0.337582E+11 | 0.00 | 22.16 |
Maximum of Months | 0.117787E+11 | 0.104082E+11 | 0.00 | 0.122146E+09 | 18227580.55 | 0.368825E+11 | 0.895271E+11 | 0.00 | 23.96 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.347504E+11 | 0.00 | 0.00 | 582983.69 | 0.00 | 0.300669E+11 | 0.138718E+10 | 0.00 | 4.34 |
February | 0.299562E+11 | 0.00 | 0.00 | 4828938.66 | 0.00 | 0.993592E+10 | 0.671454E+10 | 0.00 | 4.40 |
March | 0.285957E+11 | 0.00 | 0.00 | 7042353.35 | 0.00 | 0.228372E+10 | 0.103990E+11 | 0.00 | 4.41 |
April | 0.165855E+11 | 49539.45 | 0.00 | 13869759.82 | 0.00 | 0.00 | 0.166375E+11 | 0.00 | 4.47 |
May | 0.915899E+10 | 76927919.67 | 0.00 | 21778852.33 | 8812362.40 | 0.00 | 0.205068E+11 | 0.00 | 4.47 |
June | 0.525577E+10 | 0.242365E+10 | 0.00 | 18658107.64 | 0.474103E+09 | 0.00 | 0.141470E+11 | 0.00 | 4.47 |
July | 0.244263E+10 | 0.409028E+10 | 0.00 | 20745783.40 | 0.657094E+09 | 0.00 | 0.132256E+11 | 0.00 | 4.54 |
August | 0.427994E+10 | 0.158935E+10 | 0.00 | 26930568.38 | 0.252664E+09 | 0.00 | 0.161769E+11 | 0.00 | 4.57 |
September | 0.101936E+11 | 14118688.00 | 0.00 | 24080411.56 | 0.00 | 0.00 | 0.227161E+11 | 0.00 | 4.57 |
October | 0.193480E+11 | 0.00 | 0.00 | 14309487.64 | 0.00 | 0.00 | 0.164514E+11 | 0.00 | 4.51 |
November | 0.281291E+11 | 0.00 | 0.00 | 3669736.25 | 0.00 | 0.00 | 0.686655E+10 | 0.00 | 4.40 |
December | 0.353211E+11 | 0.00 | 0.00 | 199116.71 | 0.00 | 0.249211E+11 | 0.648256E+09 | 0.00 | 4.32 |
Annual Sum or Average | 0.224017E+12 | 0.819439E+10 | 0.00 | 0.156696E+09 | 0.139267E+10 | 0.672076E+11 | 0.145877E+12 | 0.00 | 4.46 |
Minimum of Months | 0.244263E+10 | 0.00 | 0.00 | 199116.71 | 0.00 | 0.00 | 0.648256E+09 | 0.00 | 4.32 |
Maximum of Months | 0.353211E+11 | 0.409028E+10 | 0.00 | 26930568.38 | 0.657094E+09 | 0.300669E+11 | 0.227161E+11 | 0.00 | 4.57 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.111540E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.825341E+11 | 0.00 | 0.00 | 1.84 |
February | 0.108238E+12 | 0.00 | 0.00 | 1370631.61 | 0.00 | 0.225215E+11 | 0.483538E+10 | 0.00 | 1.84 |
March | 0.101499E+12 | 0.00 | 0.00 | 5331239.20 | 0.00 | 0.428874E+10 | 0.140002E+11 | 0.00 | 1.85 |
April | 0.587105E+11 | 145268.23 | 0.00 | 26080427.55 | 0.00 | 0.00 | 0.377712E+11 | 0.00 | 1.87 |
May | 0.299870E+11 | 0.143033E+09 | 0.00 | 68564499.03 | 93475005.91 | 0.00 | 0.586541E+11 | 0.00 | 1.92 |
June | 0.138689E+11 | 0.649021E+10 | 0.00 | 67679503.95 | 0.204673E+10 | 0.00 | 0.450104E+11 | 0.00 | 1.95 |
July | 0.647395E+10 | 0.111693E+11 | 0.00 | 75681076.54 | 0.284498E+10 | 0.00 | 0.425403E+11 | 0.00 | 2.00 |
August | 0.110297E+11 | 0.390339E+10 | 0.00 | 87379616.21 | 0.135013E+10 | 0.00 | 0.520903E+11 | 0.00 | 1.98 |
September | 0.283326E+11 | 24363491.82 | 0.00 | 73333714.20 | 9873484.58 | 0.00 | 0.687038E+11 | 0.00 | 1.92 |
October | 0.576002E+11 | 0.00 | 0.00 | 35283103.01 | 0.00 | 0.00 | 0.458777E+11 | 0.00 | 1.87 |
November | 0.886987E+11 | 0.00 | 0.00 | 4157941.62 | 0.00 | 0.00 | 0.133374E+11 | 0.00 | 1.86 |
December | 0.113959E+12 | 0.00 | 0.00 | 2936.87 | 0.00 | 0.644697E+11 | 89424481.04 | 0.00 | 1.83 |
Annual Sum or Average | 0.729937E+12 | 0.217304E+11 | 0.00 | 0.444865E+09 | 0.634519E+10 | 0.173814E+12 | 0.382910E+12 | 0.00 | 1.89 |
Minimum of Months | 0.647395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 |
Maximum of Months | 0.113959E+12 | 0.111693E+11 | 0.00 | 87379616.21 | 0.284498E+10 | 0.825341E+11 | 0.687038E+11 | 0.00 | 2.00 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 39599849.21 | 0.00 | 0.00 | 97290.73 | 0.00 | 0.344751E+10 | 8995824.95 | 0.00 | 0.35 |
February | 63030013.86 | 0.00 | 0.00 | 792134.50 | 0.00 | 0.218040E+10 | 66174815.58 | 0.00 | 0.35 |
March | 67543728.17 | 0.00 | 0.00 | 2631061.23 | 0.00 | 0.163811E+10 | 0.217338E+09 | 0.00 | 0.35 |
April | 51932448.85 | 1098099.74 | 0.00 | 7348399.85 | 0.00 | 0.712059E+09 | 0.673183E+09 | 0.00 | 0.35 |
May | 12711504.73 | 16377817.74 | 3719.87 | 15987969.42 | 0.00 | 67626732.51 | 0.109150E+10 | 1152.75 | 0.36 |
June | 8649036.32 | 0.216302E+09 | 197862.21 | 13819703.48 | 368940.81 | 10403656.97 | 0.626829E+09 | 16934.99 | 0.36 |
July | 2118425.25 | 0.385625E+09 | 372873.84 | 11488834.43 | 0.00 | 537707.61 | 0.376878E+09 | 20396.39 | 0.36 |
August | 5795417.25 | 0.164070E+09 | 156546.27 | 12469041.03 | 0.00 | 12368776.54 | 0.516039E+09 | 14361.57 | 0.36 |
September | 25151506.37 | 10506975.98 | 8505.56 | 12049646.24 | 0.00 | 0.144388E+09 | 0.964762E+09 | 3286.69 | 0.36 |
October | 57378912.22 | 0.00 | 0.00 | 4108587.14 | 0.00 | 0.876881E+09 | 0.524909E+09 | 0.00 | 0.35 |
November | 61324199.40 | 0.00 | 0.00 | 377634.67 | 0.00 | 0.143782E+10 | 58624470.89 | 0.00 | 0.36 |
December | 35902735.99 | 0.00 | 0.00 | 5868.37 | 0.00 | 0.310425E+10 | 559935.94 | 0.00 | 0.35 |
Annual Sum or Average | 0.431138E+09 | 0.793979E+09 | 739507.76 | 81176171.09 | 368940.81 | 0.136324E+11 | 0.512579E+10 | 56132.39 | 0.35 |
Minimum of Months | 2118425.25 | 0.00 | 0.00 | 5868.37 | 0.00 | 537707.61 | 559935.94 | 0.00 | 0.35 |
Maximum of Months | 67543728.17 | 0.385625E+09 | 372873.84 | 15987969.42 | 368940.81 | 0.344751E+10 | 0.109150E+10 | 20396.39 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 759531.46 | 0.00 | 0.00 | 5063.17 | 0.00 | 0.349446E+10 | 568427.38 | 0.00 | 0.35 |
February | 27788293.66 | 0.00 | 0.00 | 236392.67 | 0.00 | 0.225657E+10 | 25528540.19 | 0.00 | 0.35 |
March | 51752716.92 | 0.00 | 0.00 | 1346696.89 | 0.00 | 0.172794E+10 | 0.144359E+09 | 0.00 | 0.35 |
April | 0.110359E+09 | 1058189.41 | 0.00 | 4503415.31 | 39781.67 | 0.821624E+09 | 0.507867E+09 | 0.00 | 0.35 |
May | 0.162408E+09 | 15811907.50 | 17543.97 | 11559695.29 | 547294.54 | 82045651.15 | 0.931673E+09 | 4024.89 | 0.36 |
June | 0.140136E+09 | 0.182987E+09 | 241895.47 | 9540901.85 | 33606695.32 | 8834444.60 | 0.501112E+09 | 24449.29 | 0.36 |
July | 0.104528E+09 | 0.303439E+09 | 374468.68 | 7904092.80 | 82143472.36 | 598852.26 | 0.277946E+09 | 15581.42 | 0.36 |
August | 0.136758E+09 | 0.127760E+09 | 198805.18 | 8779244.76 | 36240382.21 | 12775536.68 | 0.388295E+09 | 22384.24 | 0.36 |
September | 0.149274E+09 | 8974512.48 | 11329.65 | 7523694.32 | 1524539.67 | 0.171539E+09 | 0.817880E+09 | 7154.02 | 0.36 |
October | 94526494.34 | 0.00 | 0.00 | 1913397.72 | 0.00 | 0.991237E+09 | 0.375430E+09 | 0.00 | 0.35 |
November | 49351779.74 | 0.00 | 0.00 | 92418.97 | 0.00 | 0.149552E+10 | 13002753.04 | 0.00 | 0.36 |
December | 0.00 | 0.00 | 0.00 | 2269.34 | 0.00 | 0.314015E+10 | 190263.73 | 0.00 | 0.35 |
Annual Sum or Average | 0.102764E+10 | 0.640031E+09 | 844042.94 | 53407283.07 | 0.154102E+09 | 0.142033E+11 | 0.398385E+10 | 73593.86 | 0.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 2269.34 | 0.00 | 598852.26 | 190263.73 | 0.00 | 0.35 |
Maximum of Months | 0.162408E+09 | 0.303439E+09 | 374468.68 | 11559695.29 | 82143472.36 | 0.349446E+10 | 0.931673E+09 | 24449.29 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.128006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149455E+09 | 0.00 | 0.00 | 0.02 |
February | 0.981294E+09 | 0.00 | 0.00 | 225237.92 | 0.00 | 0.00 | 0.105950E+09 | 0.00 | 0.02 |
March | 0.799445E+09 | 0.00 | 0.00 | 1920838.53 | 0.00 | 0.00 | 0.523686E+09 | 0.00 | 0.02 |
April | 0.507203E+09 | 18942106.27 | 0.00 | 3297438.70 | 0.00 | 0.00 | 0.960326E+09 | 0.00 | 0.02 |
May | 22178290.71 | 30409309.66 | 0.00 | 3465585.45 | 0.00 | 0.00 | 0.984939E+09 | 0.00 | 0.02 |
June | 35006950.96 | 0.278179E+09 | 0.00 | 2208790.32 | 0.00 | 0.00 | 0.508189E+09 | 0.00 | 0.02 |
July | 19885500.82 | 0.509690E+09 | 0.00 | 1600039.31 | 0.00 | 0.00 | 0.158337E+09 | 0.00 | 0.02 |
August | 42754007.07 | 0.372761E+09 | 0.00 | 2285551.13 | 0.00 | 0.00 | 0.210190E+09 | 0.00 | 0.02 |
September | 0.262320E+09 | 23635044.89 | 0.00 | 4235739.80 | 0.00 | 0.00 | 0.810269E+09 | 0.00 | 0.02 |
October | 0.766793E+09 | 0.00 | 0.00 | 3155570.98 | 0.00 | 0.00 | 0.640297E+09 | 0.00 | 0.02 |
November | 0.939459E+09 | 0.00 | 0.00 | 309935.41 | 0.00 | 0.00 | 0.213639E+09 | 0.00 | 0.02 |
December | 0.778960E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310419E+09 | 0.00 | 0.00 | 0.02 |
Annual Sum or Average | 0.643535E+10 | 0.123362E+10 | 0.00 | 22704727.55 | 0.00 | 0.459874E+09 | 0.511582E+10 | 0.00 | 0.02 |
Minimum of Months | 19885500.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
Maximum of Months | 0.128006E+10 | 0.509690E+09 | 0.00 | 4235739.80 | 0.00 | 0.310419E+09 | 0.984939E+09 | 0.00 | 0.02 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.516470E+09 | 0.00 | 0.00 | 225363.96 | 0.00 | 0.466411E+11 | 0.260579E+09 | 0.00 | 0.40 |
February | 0.909157E+09 | 0.00 | 0.00 | 1113179.66 | 0.00 | 0.291529E+11 | 0.127224E+10 | 0.00 | 0.40 |
March | 0.112735E+10 | 0.00 | 0.00 | 7170025.23 | 0.00 | 0.198453E+11 | 0.513703E+10 | 0.00 | 0.40 |
April | 0.152061E+10 | 13234683.50 | 0.00 | 44327900.84 | 1658635.50 | 0.296216E+10 | 0.150647E+11 | 0.00 | 0.40 |
May | 0.260256E+10 | 0.204233E+09 | 172577.82 | 0.130581E+09 | 17783497.59 | 33279743.65 | 0.133438E+11 | 5942.72 | 0.40 |
June | 0.212229E+10 | 0.245004E+10 | 658337.61 | 0.118259E+09 | 0.490823E+09 | 7158746.82 | 0.669970E+10 | 55188.92 | 0.41 |
July | 0.157681E+10 | 0.407041E+10 | 1244931.29 | 90664205.10 | 0.116381E+10 | 1590752.96 | 0.363430E+10 | 18715.42 | 0.41 |
August | 0.195969E+10 | 0.160037E+10 | 4299480.75 | 0.107501E+09 | 0.622782E+09 | 7704819.40 | 0.533951E+10 | 115057.30 | 0.40 |
September | 0.224266E+10 | 0.116193E+09 | 194999.87 | 96268476.28 | 26262235.73 | 38209638.31 | 0.131706E+11 | 13632.43 | 0.40 |
October | 0.130552E+10 | 0.00 | 0.00 | 39183773.46 | 0.00 | 0.126607E+10 | 0.172354E+11 | 0.00 | 0.40 |
November | 0.107545E+10 | 0.00 | 0.00 | 7232180.31 | 0.00 | 0.140589E+11 | 0.599133E+10 | 0.00 | 0.40 |
December | 0.732011E+09 | 0.00 | 0.00 | 361725.48 | 0.00 | 0.414940E+11 | 0.370523E+09 | 0.00 | 0.40 |
Annual Sum or Average | 0.176906E+11 | 0.845449E+10 | 6570327.33 | 0.642888E+09 | 0.232312E+10 | 0.155508E+12 | 0.875197E+11 | 208536.80 | 0.40 |
Minimum of Months | 0.516470E+09 | 0.00 | 0.00 | 225363.96 | 0.00 | 1590752.96 | 0.260579E+09 | 0.00 | 0.40 |
Maximum of Months | 0.260256E+10 | 0.407041E+10 | 4299480.75 | 0.130581E+09 | 0.116381E+10 | 0.466411E+11 | 0.172354E+11 | 115057.30 | 0.41 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 39097553.28 | 0.00 | 0.00 | 14386.61 | 0.00 | 0.344620E+10 | 10888150.39 | 0.00 | 0.35 |
February | 66813592.63 | 0.00 | 0.00 | 613484.81 | 0.00 | 0.213869E+10 | 0.104281E+09 | 0.00 | 0.35 |
March | 53459373.52 | 0.00 | 0.00 | 2152522.05 | 0.00 | 0.159434E+10 | 0.275670E+09 | 0.00 | 0.35 |
April | 39389056.60 | 1094018.29 | 2496.92 | 7432889.23 | 0.00 | 0.684580E+09 | 0.713121E+09 | 1584.52 | 0.35 |
May | 10687219.87 | 16377817.74 | 3724.81 | 15067748.15 | 0.00 | 81715222.72 | 0.108036E+10 | 1147.81 | 0.36 |
June | 2061930.50 | 0.216358E+09 | 148169.05 | 15460759.76 | 368940.81 | 1290807.98 | 0.640888E+09 | 10713.08 | 0.36 |
July | 1991788.64 | 0.385775E+09 | 232838.35 | 12243432.76 | 0.00 | 464038.97 | 0.376323E+09 | 9855.46 | 0.36 |
August | 5778956.58 | 0.163413E+09 | 159837.51 | 12463104.41 | 650609.06 | 10003444.39 | 0.518426E+09 | 16876.29 | 0.36 |
September | 25151506.37 | 10506975.98 | 6282.04 | 11103229.03 | 0.00 | 0.156141E+09 | 0.953955E+09 | 5510.21 | 0.36 |
October | 55415801.14 | 0.00 | 0.00 | 3728608.02 | 0.00 | 0.912884E+09 | 0.491250E+09 | 0.00 | 0.35 |
November | 62309316.58 | 0.00 | 0.00 | 532429.55 | 0.00 | 0.141902E+10 | 76293476.57 | 0.00 | 0.36 |
December | 25561960.59 | 0.00 | 0.00 | 13776.62 | 0.00 | 0.309752E+10 | 17619517.48 | 0.00 | 0.35 |
Annual Sum or Average | 0.387718E+09 | 0.793525E+09 | 553348.69 | 80826371.00 | 1019549.87 | 0.135428E+11 | 0.525907E+10 | 45687.37 | 0.35 |
Minimum of Months | 1991788.64 | 0.00 | 0.00 | 13776.62 | 0.00 | 464038.97 | 10888150.39 | 0.00 | 0.35 |
Maximum of Months | 66813592.63 | 0.385775E+09 | 232838.35 | 15460759.76 | 650609.06 | 0.344620E+10 | 0.108036E+10 | 16876.29 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 1661.99 | 0.00 | 0.349560E+10 | 190395.63 | 0.00 | 0.35 |
February | 25226557.54 | 0.00 | 0.00 | 75245.69 | 0.00 | 0.226453E+10 | 20294764.14 | 0.00 | 0.35 |
March | 57357870.03 | 0.00 | 0.00 | 756571.03 | 0.00 | 0.171620E+10 | 0.151082E+09 | 0.00 | 0.35 |
April | 96010648.35 | 1086515.46 | 6756.44 | 4890941.77 | 0.00 | 0.771689E+09 | 0.571764E+09 | 4699.18 | 0.35 |
May | 0.154440E+09 | 15917355.21 | 0.00 | 11156373.69 | 463415.68 | 95834125.23 | 0.926256E+09 | 0.00 | 0.36 |
June | 0.131832E+09 | 0.183823E+09 | 94994.43 | 11590548.29 | 32931838.42 | 1414334.91 | 0.514787E+09 | 10618.76 | 0.36 |
July | 0.104463E+09 | 0.305895E+09 | 291635.29 | 8459445.10 | 79774752.19 | 551445.80 | 0.277503E+09 | 11275.52 | 0.36 |
August | 0.134768E+09 | 0.128392E+09 | 198521.33 | 8862625.76 | 35614580.49 | 10514867.94 | 0.392463E+09 | 16073.16 | 0.36 |
September | 0.138174E+09 | 8977496.21 | 5939.04 | 7190533.68 | 1524539.67 | 0.189919E+09 | 0.810933E+09 | 9560.89 | 0.36 |
October | 94831221.60 | 0.00 | 0.00 | 1621309.89 | 0.00 | 0.105239E+10 | 0.314266E+09 | 0.00 | 0.35 |
November | 45782921.27 | 0.00 | 0.00 | 121660.01 | 0.00 | 0.148094E+10 | 31122816.36 | 0.00 | 0.36 |
December | 0.00 | 0.00 | 0.00 | 2291.28 | 0.00 | 0.313985E+10 | 496351.44 | 0.00 | 0.35 |
Annual Sum or Average | 0.982886E+09 | 0.644092E+09 | 597846.53 | 54729208.20 | 0.150309E+09 | 0.142194E+11 | 0.401116E+10 | 52227.51 | 0.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 1661.99 | 0.00 | 551445.80 | 190395.63 | 0.00 | 0.35 |
Maximum of Months | 0.154440E+09 | 0.305895E+09 | 291635.29 | 11590548.29 | 79774752.19 | 0.349560E+10 | 0.926256E+09 | 16073.16 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.117830E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.505801E+11 | 0.00 | 0.00 | 0.64 |
February | 0.239665E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195969E+11 | 0.00 | 0.00 | 0.64 |
March | 0.320589E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.641225E+10 | 0.00 | 0.00 | 0.64 |
April | 0.308203E+11 | 0.00 | 0.00 | 0.00 | 46636.15 | 0.00 | 0.00 | 0.00 | 0.65 |
May | 0.277273E+11 | 0.00 | 0.00 | 0.00 | 75531507.57 | 0.00 | 0.00 | 0.00 | 0.65 |
June | 0.180293E+11 | 0.858568E+09 | 0.00 | 525643.87 | 0.173759E+10 | 0.00 | 0.193076E+09 | 0.00 | 0.65 |
July | 0.132984E+11 | 0.929714E+09 | 0.00 | 1359726.87 | 0.335198E+10 | 0.00 | 0.136332E+10 | 0.00 | 0.66 |
August | 0.189485E+11 | 7514099.05 | 0.00 | 27469.34 | 0.161735E+10 | 0.00 | 0.141868E+09 | 0.00 | 0.65 |
September | 0.303786E+11 | 0.00 | 0.00 | 0.00 | 10990523.06 | 0.00 | 0.00 | 0.00 | 0.65 |
October | 0.329436E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.65 |
November | 0.287723E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.398468E+10 | 0.00 | 0.00 | 0.65 |
December | 0.121406E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.452212E+11 | 0.00 | 0.00 | 0.64 |
Annual Sum or Average | 0.280867E+12 | 0.179580E+10 | 0.00 | 1912840.08 | 0.679349E+10 | 0.125795E+12 | 0.169827E+10 | 0.00 | 0.65 |
Minimum of Months | 0.117830E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.64 |
Maximum of Months | 0.329436E+11 | 0.929714E+09 | 0.00 | 1359726.87 | 0.335198E+10 | 0.505801E+11 | 0.136332E+10 | 0.00 | 0.66 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 5248805.03 | 0.00 | 0.00 | 12943.67 | 0.00 | 0.867512E+09 | 1276882.24 | 0.00 | 0.35 |
February | 13443943.42 | 0.00 | 0.00 | 176009.03 | 0.00 | 0.552456E+09 | 11522438.52 | 0.00 | 0.35 |
March | 15160143.13 | 0.00 | 0.00 | 650716.71 | 0.00 | 0.422129E+09 | 43465358.18 | 0.00 | 0.35 |
April | 12741596.01 | 274524.93 | 0.00 | 1802400.57 | 0.00 | 0.213286E+09 | 0.133301E+09 | 0.00 | 0.35 |
May | 3161623.83 | 4094454.44 | 1038.08 | 3910951.30 | 0.00 | 41221220.34 | 0.248663E+09 | 180.07 | 0.36 |
June | 2347702.82 | 54061719.65 | 49728.04 | 3373644.78 | 106018.16 | 5236177.21 | 0.153968E+09 | 3971.26 | 0.36 |
July | 772123.59 | 96414431.68 | 84936.95 | 2730800.83 | 0.00 | 173405.36 | 94079351.62 | 5108.91 | 0.36 |
August | 1656249.65 | 41021802.49 | 35464.93 | 2933517.52 | 0.00 | 8328107.01 | 0.123750E+09 | 2909.82 | 0.36 |
September | 6383590.44 | 2626744.00 | 2352.39 | 2810325.71 | 0.00 | 68483301.43 | 0.208911E+09 | 595.67 | 0.36 |
October | 13339057.49 | 0.00 | 0.00 | 938442.21 | 0.00 | 0.254886E+09 | 96655723.19 | 0.00 | 0.35 |
November | 12266756.72 | 0.00 | 0.00 | 80999.25 | 0.00 | 0.370960E+09 | 6229654.43 | 0.00 | 0.36 |
December | 3435562.40 | 0.00 | 0.00 | 1031.72 | 0.00 | 0.781681E+09 | 60761.11 | 0.00 | 0.35 |
Annual Sum or Average | 89957154.53 | 0.198494E+09 | 173520.40 | 19421783.31 | 106018.16 | 0.358635E+10 | 0.112188E+10 | 12765.74 | 0.35 |
Minimum of Months | 772123.59 | 0.00 | 0.00 | 1031.72 | 0.00 | 173405.36 | 60761.11 | 0.00 | 0.35 |
Maximum of Months | 15160143.13 | 96414431.68 | 84936.95 | 3910951.30 | 106018.16 | 0.867512E+09 | 0.248663E+09 | 5108.91 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 1508.99 | 0.00 | 0.873914E+09 | 32682.38 | 0.00 | 0.35 |
February | 2833938.13 | 0.00 | 0.00 | 38526.51 | 0.00 | 0.569121E+09 | 5537492.82 | 0.00 | 0.35 |
March | 6867601.37 | 0.00 | 0.00 | 301654.75 | 0.00 | 0.445933E+09 | 28247134.96 | 0.00 | 0.35 |
April | 25349171.99 | 271782.85 | 0.00 | 1109225.60 | 2709.92 | 0.238853E+09 | 95776728.85 | 0.00 | 0.35 |
May | 39724167.28 | 3952976.88 | 3965.59 | 2961972.74 | 136823.63 | 41140393.48 | 0.213095E+09 | 1426.62 | 0.36 |
June | 34264244.39 | 45745472.37 | 62918.03 | 2469856.30 | 8401673.83 | 4507684.44 | 0.123664E+09 | 5020.05 | 0.36 |
July | 25283692.58 | 75862378.16 | 97805.59 | 2019914.19 | 20529826.81 | 122329.58 | 70318291.54 | 3160.08 | 0.36 |
August | 33599934.93 | 31776652.86 | 49252.90 | 2187143.80 | 9223416.24 | 7796011.41 | 93068834.27 | 6044.45 | 0.36 |
September | 37176447.42 | 2243628.12 | 2653.05 | 1714392.54 | 381134.92 | 79454279.20 | 0.168209E+09 | 1967.86 | 0.36 |
October | 22928234.64 | 0.00 | 0.00 | 402160.24 | 0.00 | 0.294039E+09 | 48407004.04 | 0.00 | 0.35 |
November | 8265441.11 | 0.00 | 0.00 | 12424.61 | 0.00 | 0.380441E+09 | 773091.77 | 0.00 | 0.36 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.785087E+09 | 0.00 | 0.00 | 0.35 |
Annual Sum or Average | 0.236293E+09 | 0.159853E+09 | 216595.17 | 13218780.27 | 38675585.35 | 0.372041E+10 | 0.847130E+09 | 17619.06 | 0.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122329.58 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 39724167.28 | 75862378.16 | 97805.59 | 2961972.74 | 20529826.81 | 0.873914E+09 | 0.213095E+09 | 6044.45 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 85164826.67 | 0.00 | 0.00 | 1944773.74 | 0.00 | 0.522793E+10 | 0.300287E+09 | 0.00 | 0.40 |
February | 49894315.07 | 0.00 | 0.00 | 4112330.91 | 0.00 | 0.315357E+10 | 0.503201E+09 | 0.00 | 0.40 |
March | 54489105.86 | 0.00 | 0.00 | 6283994.28 | 0.00 | 0.230579E+10 | 0.726223E+09 | 0.00 | 0.40 |
April | 36934685.65 | 1763682.51 | 0.00 | 11498715.82 | 0.00 | 0.935860E+09 | 0.133579E+10 | 0.00 | 0.40 |
May | 18708361.82 | 26312604.91 | 0.00 | 19749841.94 | 0.00 | 0.123422E+09 | 0.174591E+10 | 0.00 | 0.40 |
June | 9619349.92 | 0.346589E+09 | 303159.75 | 16425962.49 | 1418421.48 | 21941432.64 | 0.101157E+10 | 34583.12 | 0.40 |
July | 3814392.29 | 0.617460E+09 | 565872.65 | 12994771.80 | 1922396.12 | 1404381.68 | 0.609817E+09 | 43411.37 | 0.41 |
August | 8668932.59 | 0.262927E+09 | 240931.92 | 16007795.31 | 601909.69 | 15604369.70 | 0.837741E+09 | 20677.04 | 0.40 |
September | 38886905.78 | 16886226.06 | 5292.00 | 18834244.54 | 0.00 | 0.115002E+09 | 0.166846E+10 | 2910.55 | 0.40 |
October | 88321316.73 | 0.00 | 0.00 | 9934919.86 | 0.00 | 0.102525E+10 | 0.122670E+10 | 0.00 | 0.40 |
November | 61745761.95 | 0.00 | 0.00 | 2862312.37 | 0.00 | 0.200975E+10 | 0.428220E+09 | 0.00 | 0.40 |
December | 54274778.41 | 0.00 | 0.00 | 986169.99 | 0.00 | 0.475758E+10 | 0.231531E+09 | 0.00 | 0.40 |
Annual Sum or Average | 0.510523E+09 | 0.127194E+10 | 1115256.31 | 0.121636E+09 | 3942727.28 | 0.196931E+11 | 0.106255E+11 | 101582.07 | 0.40 |
Minimum of Months | 3814392.29 | 0.00 | 0.00 | 986169.99 | 0.00 | 1404381.68 | 0.231531E+09 | 0.00 | 0.40 |
Maximum of Months | 88321316.73 | 0.617460E+09 | 565872.65 | 19749841.94 | 1922396.12 | 0.522793E+10 | 0.174591E+10 | 43411.37 | 0.41 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.407820E+11 | 0.00 | 0.00 | 17763270.81 | 0.00 | 0.153589E+11 | 0.258387E+11 | 0.00 | 4.03 |
February | 0.240801E+11 | 0.00 | 0.00 | 25831135.33 | 0.00 | 0.226433E+10 | 0.321006E+11 | 0.00 | 4.13 |
March | 0.127558E+11 | 0.00 | 0.00 | 42621854.26 | 0.00 | 0.00 | 0.412064E+11 | 0.00 | 4.32 |
April | 0.121285E+10 | 60900.97 | 0.00 | 63758914.90 | 0.00 | 0.00 | 0.459065E+11 | 0.00 | 4.67 |
May | 91017529.51 | 0.115788E+09 | 0.00 | 96455247.29 | 0.00 | 0.00 | 0.478713E+11 | 0.00 | 5.22 |
June | 0.00 | 0.449169E+10 | 0.00 | 85787126.02 | 0.00 | 0.00 | 0.333973E+11 | 0.00 | 5.44 |
July | 0.00 | 0.734759E+10 | 0.00 | 77704147.97 | 0.00 | 0.00 | 0.277782E+11 | 0.00 | 5.56 |
August | 1044605.17 | 0.262782E+10 | 0.00 | 87351760.49 | 0.00 | 0.00 | 0.348274E+11 | 0.00 | 5.39 |
September | 88931604.57 | 14495362.29 | 0.00 | 82313947.96 | 0.00 | 0.00 | 0.506323E+11 | 0.00 | 5.06 |
October | 0.982618E+09 | 0.00 | 0.00 | 61705103.71 | 0.00 | 0.00 | 0.494836E+11 | 0.00 | 4.67 |
November | 0.618803E+10 | 0.00 | 0.00 | 43767308.40 | 0.00 | 0.00 | 0.407250E+11 | 0.00 | 4.40 |
December | 0.398992E+11 | 0.00 | 0.00 | 22073174.11 | 0.00 | 0.817352E+10 | 0.277463E+11 | 0.00 | 4.05 |
Annual Sum or Average | 0.126082E+12 | 0.145975E+11 | 0.00 | 0.707133E+09 | 0.00 | 0.257967E+11 | 0.457514E+12 | 0.00 | 4.75 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 17763270.81 | 0.00 | 0.00 | 0.258387E+11 | 0.00 | 4.03 |
Maximum of Months | 0.407820E+11 | 0.734759E+10 | 0.00 | 96455247.29 | 0.00 | 0.153589E+11 | 0.506323E+11 | 0.00 | 5.56 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.387938E+11 | 0.00 | 0.00 | 25112016.28 | 0.00 | 0.145893E+11 | 0.334205E+11 | 0.00 | 4.30 |
February | 0.206645E+11 | 0.00 | 0.00 | 36031271.13 | 0.00 | 0.203411E+10 | 0.399642E+11 | 0.00 | 4.45 |
March | 0.889724E+10 | 0.00 | 0.00 | 57095226.57 | 0.00 | 0.00 | 0.499067E+11 | 0.00 | 4.72 |
April | 0.332236E+09 | 68507.10 | 0.00 | 78110955.57 | 0.00 | 0.00 | 0.514299E+11 | 0.00 | 5.13 |
May | 6865861.20 | 0.125700E+09 | 0.00 | 0.108389E+09 | 0.00 | 0.00 | 0.520012E+11 | 0.00 | 5.66 |
June | 0.00 | 0.482639E+10 | 0.00 | 94820226.98 | 0.00 | 0.00 | 0.359701E+11 | 0.00 | 5.87 |
July | 0.00 | 0.789924E+10 | 0.00 | 84425114.37 | 0.00 | 0.00 | 0.296276E+11 | 0.00 | 5.95 |
August | 0.00 | 0.284616E+10 | 0.00 | 96266281.88 | 0.00 | 0.00 | 0.373370E+11 | 0.00 | 5.80 |
September | 4143902.99 | 15357803.01 | 0.00 | 93826036.78 | 0.00 | 0.00 | 0.552175E+11 | 0.00 | 5.51 |
October | 0.182054E+09 | 0.00 | 0.00 | 75847866.93 | 0.00 | 0.00 | 0.553460E+11 | 0.00 | 5.13 |
November | 0.158433E+10 | 0.00 | 0.00 | 58971737.73 | 0.00 | 0.00 | 0.498297E+11 | 0.00 | 4.82 |
December | 0.369952E+11 | 0.00 | 0.00 | 30637470.63 | 0.00 | 0.756951E+10 | 0.361118E+11 | 0.00 | 4.34 |
Annual Sum or Average | 0.107460E+12 | 0.157129E+11 | 0.00 | 0.839534E+09 | 0.00 | 0.241929E+11 | 0.526162E+12 | 0.00 | 5.14 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 25112016.28 | 0.00 | 0.00 | 0.296276E+11 | 0.00 | 4.30 |
Maximum of Months | 0.387938E+11 | 0.789924E+10 | 0.00 | 0.108389E+09 | 0.00 | 0.145893E+11 | 0.553460E+11 | 0.00 | 5.95 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.881407E+10 | 0.00 | 0.00 | 90692665.04 | 0.00 | 0.167635E+11 | 0.854394E+11 | 0.00 | 19.11 |
February | 0.446437E+10 | 0.00 | 0.00 | 95814233.82 | 0.00 | 0.561971E+10 | 0.762739E+11 | 0.00 | 20.78 |
March | 0.248541E+10 | 0.00 | 0.00 | 0.116181E+09 | 0.00 | 0.149688E+10 | 0.793446E+11 | 0.00 | 21.91 |
April | 0.00 | 132079.90 | 0.00 | 0.123511E+09 | 0.00 | 0.00 | 0.712245E+11 | 0.00 | 22.93 |
May | 0.00 | 0.213976E+09 | 0.00 | 0.150811E+09 | 0.00 | 0.00 | 0.634306E+11 | 0.00 | 23.75 |
June | 0.00 | 0.710609E+10 | 0.00 | 0.126501E+09 | 0.00 | 0.00 | 0.396562E+11 | 0.00 | 24.07 |
July | 0.00 | 0.116113E+11 | 0.00 | 0.108704E+09 | 0.00 | 0.00 | 0.307023E+11 | 0.00 | 24.23 |
August | 0.00 | 0.458395E+10 | 0.00 | 0.127805E+09 | 0.00 | 0.00 | 0.409307E+11 | 0.00 | 23.92 |
September | 0.00 | 31138827.89 | 0.00 | 0.133871E+09 | 0.00 | 0.00 | 0.696029E+11 | 0.00 | 23.50 |
October | 0.00 | 0.00 | 0.00 | 0.116461E+09 | 0.00 | 0.00 | 0.751751E+11 | 0.00 | 22.63 |
November | 0.00 | 0.00 | 0.00 | 0.109290E+09 | 0.00 | 0.00 | 0.722847E+11 | 0.00 | 21.91 |
December | 0.878858E+10 | 0.00 | 0.00 | 94923483.93 | 0.00 | 0.107691E+11 | 0.853379E+11 | 0.00 | 19.39 |
Annual Sum or Average | 0.245524E+11 | 0.235466E+11 | 0.00 | 0.139457E+10 | 0.00 | 0.346492E+11 | 0.789403E+12 | 0.00 | 22.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 90692665.04 | 0.00 | 0.00 | 0.307023E+11 | 0.00 | 19.11 |
Maximum of Months | 0.881407E+10 | 0.116113E+11 | 0.00 | 0.150811E+09 | 0.00 | 0.167635E+11 | 0.854394E+11 | 0.00 | 24.23 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.314228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272655E+11 | 0.00 | 0.00 | 1.18 |
February | 0.713279E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141114E+11 | 0.00 | 0.00 | 1.19 |
March | 0.128472E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.591385E+10 | 0.00 | 0.00 | 1.19 |
April | 0.149064E+11 | 0.00 | 0.00 | 0.00 | 22742.89 | 0.123635E+09 | 0.00 | 0.00 | 1.19 |
May | 0.131613E+11 | 33613445.79 | 0.00 | 804843.85 | 4408314.13 | 0.00 | 0.359617E+09 | 0.00 | 1.20 |
June | 0.838766E+10 | 0.957365E+09 | 0.00 | 1177221.21 | 0.425482E+09 | 0.00 | 0.497518E+09 | 0.00 | 1.22 |
July | 0.595863E+10 | 0.156346E+10 | 0.00 | 2469553.34 | 0.621661E+09 | 0.00 | 0.119051E+10 | 0.00 | 1.23 |
August | 0.871446E+10 | 0.423235E+09 | 0.00 | 1144221.67 | 0.378912E+09 | 0.00 | 0.595358E+09 | 0.00 | 1.21 |
September | 0.146235E+11 | 3764356.13 | 0.00 | 234887.85 | 1623602.69 | 0.00 | 0.191343E+09 | 0.00 | 1.20 |
October | 0.159344E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131090E+09 | 0.00 | 0.00 | 1.19 |
November | 0.125296E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344489E+10 | 0.00 | 0.00 | 1.19 |
December | 0.320934E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247588E+11 | 0.00 | 0.00 | 1.18 |
Annual Sum or Average | 0.120548E+12 | 0.298144E+10 | 0.00 | 5830727.91 | 0.143211E+10 | 0.757492E+11 | 0.283434E+10 | 0.00 | 1.20 |
Minimum of Months | 0.314228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.18 |
Maximum of Months | 0.159344E+11 | 0.156346E+10 | 0.00 | 2469553.34 | 0.621661E+09 | 0.272655E+11 | 0.119051E+10 | 0.00 | 1.23 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:24:43
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.144285E+12 | 0.154350E+11 | 0.420364E+12 | 0.162997E+13 | 0.205561E+12 |
February | 0.231820E+12 | 0.124465E+11 | 0.337485E+12 | 0.137199E+13 | 0.142109E+12 |
March | 0.330595E+12 | 0.118720E+11 | 0.326977E+12 | 0.136511E+13 | 0.126444E+12 |
April | 0.445670E+12 | 0.786354E+10 | 0.216096E+12 | 0.947913E+12 | 0.127899E+12 |
May | 0.500589E+12 | 0.455622E+10 | 0.119037E+12 | 0.556596E+12 | 0.313468E+12 |
June | 0.522834E+12 | 0.176077E+10 | 0.445676E+11 | 0.226833E+12 | 0.567585E+12 |
July | 0.532602E+12 | 0.559758E+09 | 0.146630E+11 | 0.103969E+12 | 0.752415E+12 |
August | 0.441463E+12 | 0.183400E+10 | 0.530873E+11 | 0.258095E+12 | 0.552223E+12 |
September | 0.332306E+12 | 0.461952E+10 | 0.128879E+12 | 0.578203E+12 | 0.235480E+12 |
October | 0.177601E+12 | 0.741656E+10 | 0.213387E+12 | 0.921156E+12 | 0.117009E+12 |
November | 0.915720E+11 | 0.986322E+10 | 0.283351E+12 | 0.117944E+13 | 0.973165E+11 |
December | 0.100677E+12 | 0.147329E+11 | 0.405298E+12 | 0.157911E+13 | 0.189555E+12 |
Annual Sum or Average | 0.385201E+13 | 0.929600E+11 | 0.256319E+13 | 0.107184E+14 | 0.342706E+13 |
Minimum of Months | 0.915720E+11 | 0.559758E+09 | 0.146630E+11 | 0.103969E+12 | 0.973165E+11 |
Maximum of Months | 0.532602E+12 | 0.154350E+11 | 0.420364E+12 | 0.162997E+13 | 0.752415E+12 |