Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860
Simulation Timestamp: 2024-07-03 12:21:32
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:32
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 10732.36 | 945.97 | 945.97 |
Net Site Energy | 10732.36 | 945.97 | 945.97 |
Total Source Energy | 22744.72 | 2004.77 | 2004.77 |
Net Source Energy | 22744.72 | 2004.77 | 2004.77 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 967.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 932.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 782.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 193.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1658.18 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 813.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 525.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 88.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 183.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 94.78 | 2642.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | 61.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 5334.06 | 5398.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 967.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 932.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 782.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 193.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 872.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 14.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 8.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 21.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 789.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 2.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 525.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 88.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 183.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 94.78 | 2642.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5742.51 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.69 | |
Refrigeration | General | 7.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 20.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 34.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 967.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 932.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 782.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 193.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 1658.18 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 813.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 525.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 88.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 183.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 94.78 | 2642.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | Unassigned | 61.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 86.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 144.63 | 318.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 239.51 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 470.16 | 475.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 86.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 144.63 | 318.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 239.51 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 470.16 | 475.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 5334.058 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 5334.058 | 100.00 |
Total On-Site and Utility Electric Sources | 5334.058 | 100.00 |
Total Electricity End Uses | 5334.058 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 551.74 | 16.33 |
Air to Air Heat Recovery for Heating | 2826.58 | 83.67 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 3378.32 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9857.19 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9857.19 | 100.00 |
Total Water End Uses | 9857.19 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 14.00 |
Time Setpoint Not Met During Occupied Cooling | 66.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 7927.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4A
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_NEWYORK
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER1 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| FLR_3_DOAS COOLING COIL | VAV WITH REHEAT COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH LAUNDRY G WATER HEATER | SWH BOOSTER E WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |CoilReportMonthly
| FLR_3_DOAS HEATING COIL | VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | FLR_3_DOAS COOLING COIL | VAV WITH REHEAT COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |FanReportMonthly
| FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL_FANCOILFAN | ROOM_2_FLR_3 FAN COIL_FANCOILFAN | ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | ROOM_5_FLR_3 FAN COIL_FANCOILFAN | ROOM_6_FLR_3 FAN COIL_FANCOILFAN | ROOM_1_FLR_6 FAN COIL_FANCOILFAN | ROOM_2_FLR_6 FAN COIL_FANCOILFAN | ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| FLR_3_DOAS | VAV WITH REHEAT |AirLoopSystemComponentLoadsMonthly
| FLR_3_DOAS | VAV WITH REHEAT |AirLoopSystemComponentEnergyUseMonthly
| FLR_3_DOAS | VAV WITH REHEAT |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:32
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21 |
RunPeriod | RUNPERIOD 1 |
Weather File | New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 |
Latitude [deg] | 40.65 |
Longitude [deg] | -73.8 |
Elevation [m] | 5.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 8.8143 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.26 | 23.26 | 11.3140 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 11.3140 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 4.6285 | 61.93 | 5.3800 |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 5.7199 | 46.45 | 2.6900 |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 4.6285 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.50 | 65.50 | 10.0104 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.08 | 85.08 | 10.7639 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 8.2882 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 8.2882 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 7.1042 | 18.58 | 0.0000 |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.74 | 6.74 | 8.2882 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 10.0104 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 10.0104 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.37 | 26.37 | 11.4097 | 4.65 | 2934.4875 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.20 | 28.20 | 7.1042 | 18.58 | 0.0000 |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 8.5566 | 7.07 | 41.0709 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 8.5566 | 7.07 | 41.0709 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 1978.83 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 8.8143 | 18.58 | 5.3800 | |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 1.00 | RETAIL_1_FLR_1 | GENERAL | RETAIL_1_FLR_1 | 11.3140 | 6.19 | 10.7600 | |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 1.00 | RETAIL_2_FLR_1 | GENERAL | RETAIL_2_FLR_1 | 11.3140 | 6.19 | 10.7600 | |
MECH_FLR_1 | 164.24 | Yes | Yes | 1.00 | MECH_FLR_1 | GENERAL | MECH_FLR_1 | 4.6285 | 61.93 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 1.00 | STORAGE_FLR_1 | GENERAL | STORAGE_FLR_1 | 5.7199 | 46.45 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 1.00 | LAUNDRY_FLR_1 | GENERAL | LAUNDRY_FLR_1 | 4.6285 | 9.29 | 597.5300 | |
CAFE_FLR_1 | 188.86 | Yes | Yes | 1.00 | CAFE_FLR_1 | GENERAL | CAFE_FLR_1 | 10.0104 | 1.33 | 5.3800 | |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 1.00 | LOBBY_FLR_1 | GENERAL | LOBBY_FLR_1 | 10.7639 | 3.10 | 8.0700 | |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_1_FLR_3 | GENERAL | ROOM_1_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_2_FLR_3 | GENERAL | ROOM_2_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 76.00 | ROOM_3_MULT19_FLR_3 | GENERAL | ROOM_3_MULT19_FLR_3 | 8.2882 | 16.35 | 10.5200 | |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 76.00 | ROOM_4_MULT19_FLR_3 | GENERAL | ROOM_4_MULT19_FLR_3 | 8.2882 | 16.35 | 10.5200 | |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_5_FLR_3 | GENERAL | ROOM_5_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_6_FLR_3 | GENERAL | ROOM_6_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 4.00 | CORRIDOR_FLR_3 | GENERAL | CORRIDOR_FLR_3 | 7.1042 | 18.58 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_1_FLR_6 | GENERAL | ROOM_1_FLR_6 | 8.2882 | 26.01 | 6.7500 | |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_2_FLR_6 | GENERAL | ROOM_2_FLR_6 | 8.2882 | 26.01 | 6.7500 | |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 9.00 | ROOM_3_MULT9_FLR_6 | GENERAL | ROOM_3_MULT9_FLR_6 | 8.2882 | 16.35 | 10.5200 | |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1.00 | BANQUET_FLR_6 | GENERAL | BANQUET_FLR_6 | 10.0104 | 1.33 | 67.8200 | |
DINING_FLR_6 | 331.66 | Yes | Yes | 1.00 | DINING_FLR_6 | GENERAL | DINING_FLR_6 | 10.0104 | 1.33 | 67.8200 | |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 1.00 | KITCHEN_FLR_6 | GENERAL | KITCHEN_FLR_6 | 11.4097 | 4.65 | 2934.4875 | |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1.00 | CORRIDOR_FLR_6 | GENERAL | CORRIDOR_FLR_6 | 7.1042 | 18.58 | 0.0000 | |
Total | 11345.29 | 8.5566 | 3.54 | 41.0709 | |||||||
Conditioned Total | 11345.29 | 8.5566 | 3.54 | 41.0709 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 11345.29 | 11345.29 | 0.00 | 0.00 | 4.6520 | 8.82 | 37.1989 |
Total | 11345.29 | 11345.29 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:32
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 04-AUG-19:10 | 24-MAR-17:49 | - | - | - | - | - | - | - | - | - | - | 27-MAR-20:30 |
Heating | 0.00 | 190385.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 189455.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 64632.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 12338.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 86439.81 | 104248.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 10993.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 29588.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 4387.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 3955.81 | 245814.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1874.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 413605.13 | 540448.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 190385.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 189455.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 64632.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 12338.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 56456.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 29272.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1243.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 9600.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 150.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 29588.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 4387.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 3955.81 | 245814.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 536.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1097.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:32
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1048.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2951.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2477.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 613.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5251.45 | 1939.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2577.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1664.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 280.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 580.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 300.18 | 2863.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 196.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 16892.96 | 5851.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 92.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 260.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 218.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 54.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 462.88 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 227.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 146.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 24.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 51.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 26.46 | 252.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1488.98 | 515.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 92.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 260.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 218.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 54.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 462.88 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 227.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 146.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 24.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 51.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 26.46 | 252.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1488.98 | 515.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:32
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
BASEMENT VAV BOX COMPONENT | 2.48 | 0.608524 | 0.532000 | 1.32 | 1.00 | 0.500000 | 0.000626 | 0.000061 | 1.32 | 16.70 | 0.008000 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.360503 | 0.141770 | 0.532000 | 0.191787 | 0.532000 | 0.500000 | 0.002687 | 0.000032 | 0.191787 | 16.70 | 0.008000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.227897 | 0.259695 | 0.532000 | 0.121241 | 0.692520 | 0.500000 | 0.001467 | 0.000013 | 0.121241 | 16.70 | 0.008000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.186131 | 0.672395 | 0.532000 | 0.099021 | 1.00 | 0.500000 | 0.000567 | 0.000019 | 0.099021 | 16.70 | 0.008000 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.110955 | 0.650775 | 0.532000 | 0.059028 | 1.00 | 0.500000 | 0.000585 | 0.000013 | 0.059028 | 16.70 | 0.008000 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 3.25 | 0.018283 | 0.532000 | 1.73 | 0.532000 | 0.500000 | 0.020839 | 0.000098 | 1.73 | 16.70 | 0.008000 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.51 | 0.095156 | 0.532000 | 0.804586 | 0.532000 | 0.500000 | 0.004004 | 0.000097 | 0.804586 | 16.70 | 0.008000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 4.84 | 0.206111 | 0.532000 | 2.57 | 0.549629 | 0.500000 | 0.001849 | 0.000257 | 2.57 | 16.70 | 0.008000 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.54 | 0.772167 | 0.532000 | 0.817743 | 1.00 | 0.500000 | 0.000493 | 0.000121 | 0.817743 | 16.70 | 0.008000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.15 | 0.117368 | 0.532000 | 1.15 | 0.532000 | 0.500000 | 0.003246 | 0.000105 | 1.15 | 16.70 | 0.008000 |
DINING_FLR_6 VAV BOX COMPONENT | 2.26 | 0.112009 | 0.532000 | 1.20 | 0.532000 | 0.500000 | 0.003401 | 0.000109 | 1.20 | 16.70 | 0.008000 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.25 | 0.062835 | 0.532000 | 1.20 | 0.532000 | 0.500000 | 0.010906 | 0.000072 | 1.20 | 16.70 | 0.008000 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 0.770316 | 0.407675 | 0.532000 | 0.409808 | 1.00 | 0.500000 | 0.000935 | 0.000074 | 0.409808 | 16.70 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
BASEMENT VAV BOX REHEAT COIL | 6957.02 | 0.000061 | 145.08 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 3686.24 | 0.000032 | 89.29 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1535.40 | 0.000013 | 34.54 |
MECH_FLR_1 VAV BOX REHEAT COIL | 2129.94 | 0.000019 | 53.03 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 1429.72 | 0.000013 | 36.82 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 11241.14 | 0.000098 | 237.26 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 11034.08 | 0.000097 | 251.08 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 29358.71 | 0.000257 | 651.69 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | 5936.38 | 0.000052 | 169.62 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | 5953.66 | 0.000052 | 170.12 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 33970.38 | 0.000297 | 970.64 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 34303.28 | 0.000300 | 980.15 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | 5901.27 | 0.000052 | 168.62 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | 5918.56 | 0.000052 | 169.11 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 13876.81 | 0.000121 | 327.49 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | 1804.68 | 0.000016 | 51.56 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | 1810.35 | 0.000016 | 51.73 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 8606.17 | 0.000075 | 245.90 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 12018.88 | 0.000105 | 264.22 |
DINING_FLR_6 VAV BOX REHEAT COIL | 12443.19 | 0.000109 | 273.19 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 8247.63 | 0.000072 | 174.74 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 8406.08 | 0.000074 | 206.79 |
FLR_3_DOAS HEATING COIL | 20393.42 | 0.000178 | 336.60 |
VAV WITH REHEAT HEATING COIL | 216876.09 | 0.001897 | 3579.62 |
Design Size Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 0.061735 |
ROOM_2_FLR_3 DIRECT AIR | 0.061728 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 0.837072 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 0.837300 |
ROOM_5_FLR_3 DIRECT AIR | 0.061735 |
ROOM_6_FLR_3 DIRECT AIR | 0.061728 |
ROOM_1_FLR_6 DIRECT AIR | 0.015434 |
ROOM_2_FLR_6 DIRECT AIR | 0.015432 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 0.099154 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Hot Water Flow [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 1.10 | 0.000052 | 0.000354 |
ROOM_2_FLR_3 FAN COIL | 1.07 | 0.000052 | 0.000344 |
ROOM_3_MULT19_FLR_3 FAN COIL | 6.80 | 0.000297 | 0.002147 |
ROOM_4_MULT19_FLR_3 FAN COIL | 6.17 | 0.000300 | 0.002073 |
ROOM_5_FLR_3 FAN COIL | 1.01 | 0.000052 | 0.000327 |
ROOM_6_FLR_3 FAN COIL | 0.984253 | 0.000052 | 0.000318 |
ROOM_1_FLR_6 FAN COIL | 0.288352 | 0.000016 | 0.000093 |
ROOM_2_FLR_6 FAN COIL | 0.279657 | 0.000016 | 0.000090 |
ROOM_3_MULT9_FLR_6 FAN COIL | 1.36 | 0.000075 | 0.000443 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COIL_FANCOILFAN | 1.10 |
ROOM_2_FLR_3 FAN COIL_FANCOILFAN | 1.07 |
ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | 6.80 |
ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | 6.17 |
ROOM_5_FLR_3 FAN COIL_FANCOILFAN | 1.01 |
ROOM_6_FLR_3 FAN COIL_FANCOILFAN | 0.984253 |
ROOM_1_FLR_6 FAN COIL_FANCOILFAN | 0.288352 |
ROOM_2_FLR_6 FAN COIL_FANCOILFAN | 0.279657 |
ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN | 1.36 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Coil Load [W] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | 21.68 | 6.70 | 0.008615 | 12.80 | 0.008500 | 0.000354 | 1.10 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | 21.68 | 6.70 | 0.008619 | 12.80 | 0.008500 | 0.000344 | 1.07 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 21.68 | 6.70 | 0.008542 | 12.80 | 0.008500 | 0.002147 | 6.80 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 21.68 | 6.70 | 0.008773 | 12.80 | 0.008500 | 0.002073 | 6.17 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | 21.68 | 6.70 | 0.008626 | 12.80 | 0.008500 | 0.000327 | 1.01 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | 21.68 | 6.70 | 0.008629 | 12.80 | 0.008500 | 0.000318 | 0.984253 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | 21.68 | 6.70 | 0.008610 | 12.80 | 0.008500 | 0.000093 | 0.288352 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | 21.68 | 6.70 | 0.008614 | 12.80 | 0.008500 | 0.000090 | 0.279657 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 21.68 | 6.70 | 0.008667 | 12.80 | 0.008500 | 0.000443 | 1.36 | |
FLR_3_DOAS COOLING COIL | 32.10 | 6.70 | 0.014120 | 11.94 | 0.008500 | 0.002469 | 2.05 | 86334.71 |
VAV WITH REHEAT COOLING COIL | 28.33 | 6.70 | 0.012048 | 10.99 | 0.008500 | 0.020095 | 21.81 | 702620.51 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
VAV WITH REHEAT | 11.67 | 11.67 | 21.93 | 11.67 | 21.81 | 21.81 | 0.300000 | 0.534924 | 21.81 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
VAV WITH REHEAT_OA_CONTROLLER | 21.81 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
FLR_3_DOAS OA HEAT RECOVERY | 2.05 |
VAV WITH REHEAT OA HEAT RECOVERY | 11.66 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS FAN | 2.05 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.002469 | 0.000193 |
FLR_3_DOAS_HEATC_CONTROLLER | 0.000178 | |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.020095 | 0.000024 |
VAV WITH REHEAT_HEATC_CONTROLLER | 0.001897 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT FAN | 21.81 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.028754 | 4694.63 | |
HEATSYS1 PUMP | 0.004058 | 1222.05 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.004058 | 0.486944 |
COOLSYS1 | 0.028754 | 3.45 |
SWHSYS1 | 0.000375 | 0.045004 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 463839.09 | 463839.09 | 0.004058 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.028754 | 3250.25 |
SWHSYS1 PUMP | 0.000375 | 47.91 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.028754 | 1005385.82 | 1005991.43 | 114.68 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000375 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:32
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:32
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:32
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 14.00 | 7.30 | 3.30 | 1.20 | -0.20 | 5.60 | 10.90 | 16.10 | 21.70 | 25.00 | 24.80 | 19.90 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 | 40.65 | -73.80 | -5.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 12.47 | 25.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.58 | 23.26 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.72 | 65.50 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.80 | 85.08 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.70 | 6.74 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.96 | 26.37 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.27 | 28.20 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 8.814 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 14.194 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 11.314 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 22.074 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 11.314 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 22.074 | No |
4 | MECH_FLR_1 | 164.24 | 2.7 | 61.932 | 1.615E-002 | 4.628 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 10.008 | No |
5 | STORAGE_FLR_1 | 94.76 | 2.0 | 46.451 | 2.153E-002 | 5.720 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 8.410 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 4.628 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 602.158 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 10.010 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 15.390 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 10.764 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.834 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 8.288 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 18.808 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 8.288 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 18.808 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 21.0 | 18.581 | 5.382E-002 | 7.104 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.104 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 8.288 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 18.808 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 10.010 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 77.830 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 10.010 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 77.830 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 11.410 | 515.227 | 2419.260 | 0.000 | 0.000 | 0.000 | 2945.897 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 22.2 | 18.581 | 5.382E-002 | 7.104 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.104 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | STORAGE_FLR_1 PEOPLE | BLDG_OCC_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.0 | 2.153E-002 | 46.451 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | CORRIDOR_FLR_3 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 21.0 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 21 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
21 | CORRIDOR_FLR_6 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 22.2 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
22 | MECH_FLR_1 PEOPLE | BLDG_OCC_SCH | MECH_FLR_1 | 164.24 | 2.7 | 2.7 | 1.615E-002 | 61.932 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 3 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_BASEMENT | BASEMENT | 1978.83 | 106.5 | 17441.963 | 8.814 | 163.776 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 17441.963 |
2 | RETAIL_1_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_1_FLR_1 | 67.07 | 10.8 | 758.849 | 11.314 | 70.076 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 758.849 |
3 | RETAIL_2_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_2_FLR_1 | 77.67 | 12.5 | 878.750 | 11.314 | 70.076 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 878.750 |
4 | MECH_FLR_1_LIGHTS | LTG_SCH_MECHANIC | MECH_FLR_1 | 164.24 | 2.7 | 760.196 | 4.628 | 286.650 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 760.196 |
5 | STORAGE_FLR_1_LIGHTS | LTG_SCH_STORAGE | STORAGE_FLR_1 | 94.76 | 2.0 | 542.017 | 5.720 | 265.695 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 542.017 |
6 | LAUNDRY_FLR_1_LIGHTS | LTG_SCH_LAUNDRY | LAUNDRY_FLR_1 | 78.04 | 8.4 | 361.204 | 4.628 | 43.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 361.204 |
7 | CAFE_FLR_1_LIGHTS | LTG_SCH_DINING | CAFE_FLR_1 | 188.86 | 142.3 | 1890.589 | 10.010 | 13.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1890.589 |
8 | LOBBY_FLR_1_LIGHTS | LTG_SCH_LOBBY | LOBBY_FLR_1 | 1308.19 | 422.4 | 14081.185 | 10.764 | 33.333 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14081.185 |
9 | ROOM_1_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_3 | 39.02 | 1.5 | 323.422 | 8.288 | 215.615 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.422 |
10 | ROOM_2_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_3 | 39.02 | 1.5 | 323.384 | 8.288 | 215.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.384 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 203.259 | 8.288 | 135.506 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 203.259 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 203.314 | 8.288 | 135.543 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 203.314 |
13 | ROOM_5_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_5_FLR_3 | 39.02 | 1.5 | 323.422 | 8.288 | 215.615 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.422 |
14 | ROOM_6_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_6_FLR_3 | 39.02 | 1.5 | 323.384 | 8.288 | 215.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.384 |
15 | CORRIDOR_FLR_3_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2766.397 | 7.104 | 132.003 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2766.397 |
16 | ROOM_1_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_6 | 39.02 | 1.5 | 323.422 | 8.288 | 215.615 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.422 |
17 | ROOM_2_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_6 | 39.02 | 1.5 | 323.384 | 8.288 | 215.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.384 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 203.314 | 8.288 | 135.543 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 203.314 |
19 | BANQUET_FLR_6_LIGHTS | LTG_SCH_DINING | BANQUET_FLR_6 | 331.66 | 249.9 | 3320.034 | 10.010 | 13.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3320.034 |
20 | DINING_FLR_6_LIGHTS | LTG_SCH_DINING | DINING_FLR_6 | 331.66 | 249.9 | 3320.034 | 10.010 | 13.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3320.034 |
21 | KITCHEN_FLR_6_LIGHTS | LTG_SCH_KITCHEN | KITCHEN_FLR_6 | 103.30 | 22.2 | 1178.676 | 11.410 | 53.003 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1178.676 |
22 | CORRIDOR_FLR_6_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_6 | 412.12 | 22.2 | 2927.804 | 7.104 | 132.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2927.804 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 2.7 | 883.628 | 5.380 | 333.193 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 254.902 | 2.690 | 124.952 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 457.500 | 4.429 | 20.573 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 457.500 | 457.500 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 285.000 | 2.759 | 12.816 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 285.000 | 285.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 2.390 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
6 | RES_ROOF | 19 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
7 | NONRES_EXT_WALL_GRD | 21 | 3 | 9 | 0.167 | 0.8203 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | NONRES_EXT_WALL_MID | 22 | 3 | 9 | 0.167 | 1.021 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | NONRES_EXT_WALL_TOP | 23 | 3 | 9 | 0.167 | 1.034 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | RES_EXT_WALL_MID | 25 | 3 | 9 | 0.167 | 0.9169 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | RES_EXT_WALL_TOP | 26 | 3 | 9 | 0.167 | 0.9299 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | NONRES_FLOOR | 30 | 3 | 7 | 0.167 | 0.2277 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
13 | NONRES_FLOOR_CEILING | 33 | 3 | 7 | 0.167 | 0.2277 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
14 | BASEMENT_FLOOR | 36 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
15 | BASEMENT_WALL_NORTH_CFACTOR | 39 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | BASEMENT_WALL_EAST_CFACTOR | 40 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | BASEMENT_WALL_SOUTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
18 | BASEMENT_WALL_WEST_CFACTOR | 42 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4184 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
10 | RES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
11 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
12 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.052 |
14 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8120 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7993 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | RES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9233 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
25 | RES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9080 |
26 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
27 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.131 |
28 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
29 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
30 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
31 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
32 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.131 |
33 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
34 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
35 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
39 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
40 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
41 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
42 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 2.3900722 | 2.3900722 | 2.3900722 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
21 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
22 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
23 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
24 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
25 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
26 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
27 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
28 | 9 | -0.15703352E-14 | 0.29012323E-16 | -0.15483104E-09 | 0.40370831E-16 |
29 | 8 | 0.22592825E-07 | 0.11106548E-12 | 0.38529762E-03 | -0.25688817E-09 |
30 | 7 | -0.12465369E-01 | 0.57225352E-08 | -0.23408026E-01 | 0.14173579E-03 |
31 | 6 | 0.41143163 | 0.19878644E-05 | 0.47726710 | -0.48194459E-02 |
32 | 5 | -5.2499075 | 0.74130146E-04 | -4.4810026 | 0.63919688E-01 |
33 | 4 | 33.265337 | 0.60571720E-03 | 21.595652 | -0.42560793 |
34 | 3 | -111.78466 | 0.13187857E-02 | -55.931065 | 1.5232626 |
35 | 2 | 197.68466 | 0.74115454E-03 | 78.156489 | -2.9095067 |
36 | 1 | -171.36898 | 0.79055603E-04 | -55.336681 | 2.7491709 |
37 | 0 | 57.057407 | 0.44959794E-06 | 15.545184 | |
38 | 9 | 0.14302076E-15 | 0.35792568E-16 | -0.14541430E-09 | -0.27421543E-17 |
39 | 8 | 0.21269444E-07 | 0.13686051E-12 | 0.37140784E-03 | -0.24184090E-09 |
40 | 7 | -0.12050952E-01 | 0.71525680E-08 | -0.22811354E-01 | 0.13702371E-03 |
41 | 6 | 0.40017121 | 0.24988627E-05 | 0.46767819 | -0.46867126E-02 |
42 | 5 | -5.1400200 | 0.93645327E-04 | -4.4073602 | 0.62557131E-01 |
43 | 4 | 32.779281 | 0.76858103E-03 | 21.307814 | -0.41915444 |
44 | 3 | -110.75053 | 0.16800125E-02 | -55.362013 | 1.5083221 |
45 | 2 | 196.65975 | 0.94749847E-03 | 77.634567 | -2.8932310 |
46 | 1 | -170.99041 | 0.10139533E-03 | -55.184883 | 2.7425359 |
47 | 0 | 57.057407 | 0.57877233E-06 | 15.570231 | |
48 | 9 | 0.33566835E-16 | 0.35384250E-16 | -0.14478218E-09 | -0.87565041E-18 |
49 | 8 | 0.21180494E-07 | 0.13854999E-12 | 0.37046393E-03 | -0.24082951E-09 |
50 | 7 | -0.12022754E-01 | 0.72481687E-08 | -0.22770744E-01 | 0.13670309E-03 |
51 | 6 | 0.39940498 | 0.25332696E-05 | 0.46702484 | -0.46776806E-02 |
52 | 5 | -5.1325420 | 0.94967185E-04 | -4.4023386 | 0.62464408E-01 |
53 | 4 | 32.746200 | 0.77967008E-03 | 21.288178 | -0.41871522 |
54 | 3 | -110.68014 | 0.17047184E-02 | -55.323188 | 1.5073051 |
55 | 2 | 196.58997 | 0.96166638E-03 | 77.598974 | -2.8921229 |
56 | 1 | -170.96463 | 0.10293464E-03 | -55.174560 | 2.7420841 |
57 | 0 | 57.057407 | 0.58770932E-06 | 15.571958 | |
58 | 9 | -0.29206544E-14 | 0.31488305E-16 | -0.15031727E-09 | 0.48064473E-16 |
59 | 8 | 0.21958778E-07 | 0.12356532E-12 | 0.37867817E-03 | -0.24967887E-09 |
60 | 7 | -0.12267989E-01 | 0.64094198E-08 | -0.23123879E-01 | 0.13949151E-03 |
61 | 6 | 0.40606866 | 0.22324768E-05 | 0.47270315 | -0.47562292E-02 |
62 | 5 | -5.1975737 | 0.83445227E-04 | -4.4459647 | 0.63270770E-01 |
63 | 4 | 33.033866 | 0.68326082E-03 | 21.458733 | -0.42253461 |
64 | 3 | -111.29222 | 0.14903991E-02 | -55.660391 | 1.5161481 |
65 | 2 | 197.19665 | 0.83899866E-03 | 77.908180 | -2.9017570 |
66 | 1 | -171.18874 | 0.89630080E-04 | -55.264364 | 2.7460119 |
67 | 0 | 57.057407 | 0.51068186E-06 | 15.557036 | |
68 | 9 | -0.29497736E-14 | 0.32939851E-16 | -0.14970570E-09 | 0.45584202E-16 |
69 | 8 | 0.21872815E-07 | 0.12523736E-12 | 0.37777579E-03 | -0.24870145E-09 |
70 | 7 | -0.12241065E-01 | 0.65023057E-08 | -0.23085114E-01 | 0.13918537E-03 |
71 | 6 | 0.40533708 | 0.22656711E-05 | 0.47208016 | -0.47476058E-02 |
72 | 5 | -5.1904345 | 0.84713026E-04 | -4.4411801 | 0.63182247E-01 |
73 | 4 | 33.002288 | 0.69384191E-03 | 21.440032 | -0.42211534 |
74 | 3 | -111.22504 | 0.15138688E-02 | -55.623419 | 1.5151774 |
75 | 2 | 197.13007 | 0.85240592E-03 | 77.874271 | -2.9006996 |
76 | 1 | -171.16415 | 0.91081681E-04 | -55.254501 | 2.7455809 |
77 | 0 | 57.057407 | 0.51907125E-06 | 15.558664 | |
78 | 7 | -0.14139450E-14 | -0.18802902E-16 | -0.22311785E-13 | 0.54375338E-15 |
79 | 6 | 0.16999971E-10 | 0.27590984E-11 | 0.52267399E-09 | -0.18616555E-10 |
80 | 5 | -0.63950587E-07 | 0.13451749E-07 | -0.21905428E-05 | 0.17144787E-06 |
81 | 4 | 0.72477507E-04 | 0.50724086E-05 | 0.17668371E-02 | -0.28223350E-03 |
82 | 3 | -0.10573811E-01 | 0.17927531E-03 | -0.21549182 | 0.43318087E-01 |
83 | 2 | 0.15010112 | 0.77388015E-03 | 2.8998331 | -0.61891034 |
84 | 1 | -0.37982851 | 0.49528818E-03 | -7.1368477 | 1.5694772 |
85 | 0 | 0.24168561 | 0.34021171E-05 | 4.4521969 | |
86 | 7 | -0.22311785E-13 | -0.18802902E-16 | -0.14139450E-14 | 0.54375338E-15 |
87 | 6 | 0.52267399E-09 | 0.27590984E-11 | 0.16999971E-10 | -0.18616555E-10 |
88 | 5 | -0.21905428E-05 | 0.13451749E-07 | -0.63950587E-07 | 0.17144787E-06 |
89 | 4 | 0.17668371E-02 | 0.50724086E-05 | 0.72477507E-04 | -0.28223350E-03 |
90 | 3 | -0.21549182 | 0.17927531E-03 | -0.10573811E-01 | 0.43318087E-01 |
91 | 2 | 2.8998331 | 0.77388015E-03 | 0.15010112 | -0.61891034 |
92 | 1 | -7.1368477 | 0.49528818E-03 | -0.37982851 | 1.5694772 |
93 | 0 | 4.4521969 | 0.34021171E-05 | 0.24168561 | |
94 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
95 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
96 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
97 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
98 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
99 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
100 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
101 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
102 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
103 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
104 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
105 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
106 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
107 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
108 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
109 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
110 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
111 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
112 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
113 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
114 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
115 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
116 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
117 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
118 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
119 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
120 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
121 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
122 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
123 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
124 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
125 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
126 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
127 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
128 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
129 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
130 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
131 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
132 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
133 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.38_SHGC_0.36 | 37 | 1 | VerySmooth | 2.159 | 2.159 | 1.000 | 0.361 | ||
2 | RESWINDOW_U_0.38_SHGC_0.36 | 38 | 1 | VerySmooth | 2.159 | 2.159 | 1.000 | 0.361 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 3.45900E-002 | 0.27318 | 0.51781 | 0.51781 | 0.39600 | 0.13802 | 0.18068 | 0.00000 | 0.84000 | 0.84000 | 0.11893 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 3.45900E-002 | 0.27318 | 0.51781 | 0.51781 | 0.39600 | 0.13802 | 0.18068 | 0.00000 | 0.84000 | 0.84000 | 0.11893 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | CAFE_FLR_1 | 1 | 0 |
2 | LOBBY_FLR_1 | 1 | 0 |
3 | BANQUET_FLR_6 | 1 | 0 |
4 | DINING_FLR_6 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | CAFE_FLR_1 | 0 | |
2 | LOBBY_FLR_1 | 0 | |
3 | BANQUET_FLR_6 | 0 | |
4 | DINING_FLR_6 | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH LAUNDRY G WATER HEATER | 1.1356 | 163316.0 | 11.511 | 0.4388 |
2 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.219 | 1.1187 |
3 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 2.2712 | 175842.6 | 5.775 | 0.3748 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 1.764E-002 | 2.631E-004 | 1.298E-004 | 0.239 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.811E-003 | 8.769E-005 | 2.388E-004 | 7.967E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 2.7 | 1.610E-002 | 9.800E-005 | 2.563E-004 | 8.904E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 9.287E-003 | 9.800E-005 | 2.127E-004 | 8.904E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 2.198E-002 | 2.816E-004 | 2.506E-004 | 0.256 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 3.900E-002 | 2.065E-004 | 1.137E-004 | 0.188 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 0.111 | 8.519E-005 | 1.629E-004 | 7.740E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 2.563E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 2.563E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 2.857E-003 | 1.165E-004 | 2.563E-004 | 0.138 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 2.858E-003 | 1.165E-004 | 2.563E-004 | 0.138 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 2.563E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 2.563E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 1.238E-002 | 3.180E-005 | 2.563E-004 | 3.755E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 1.297E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 1.297E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 5.239E-003 | 2.136E-004 | 1.165E-004 | 0.252 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 2.500E-002 | 7.539E-005 | 5.825E-005 | 8.904E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 2.500E-002 | 7.539E-005 | 5.825E-005 | 8.904E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 2.238E-002 | 2.167E-004 | 1.174E-004 | 0.256 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 2.191E-002 | 5.316E-005 | 4.403E-005 | 6.278E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1423 |
2 | Clear Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 7.0301E-002 |
3 | Clear Turbid Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1593 |
4 | Clear Turbid Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 7.8534E-002 |
5 | Intermediate Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1038 |
6 | Intermediate Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 4.0146E-002 |
7 | Overcast Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 4.1657E-002 |
8 | Overcast Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 1.3839E-002 |
9 | Clear Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1617 |
10 | Clear Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 8.5181E-002 |
11 | Clear Turbid Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1816 |
12 | Clear Turbid Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 9.4949E-002 |
13 | Intermediate Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1149 |
14 | Intermediate Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 5.0322E-002 |
15 | Overcast Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 4.6776E-002 |
16 | Overcast Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 1.8924E-002 |
17 | Clear Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 3.4582E-002 |
18 | Clear Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.9928E-002 |
19 | Clear Turbid Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.6533E-002 |
20 | Clear Turbid Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.5003E-002 |
21 | Intermediate Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.5605E-002 |
22 | Intermediate Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.0249E-002 |
23 | Overcast Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 4.1005E-002 |
24 | Overcast Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.4540E-002 |
25 | Clear Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 3.4582E-002 |
26 | Clear Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.9928E-002 |
27 | Clear Turbid Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.6533E-002 |
28 | Clear Turbid Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.5003E-002 |
29 | Intermediate Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.5605E-002 |
30 | Intermediate Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.0249E-002 |
31 | Overcast Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 4.1005E-002 |
32 | Overcast Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.4540E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 34087.89191 | 34087.89191 | 2.47791 | 2.47791 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 28.94267 | 1.41140E-002 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 0.85446 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -10.70000 | 1.50390E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
3 | RETAIL_1_FLR_1 | Cooling | 4958.74596 | 4958.74596 | 0.36050 | 0.36050 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | 31.79167 | 1.41191E-002 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 2674.65682 | 2674.65682 | 0.11469 | 0.11469 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -10.70000 | 1.50390E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 3134.73147 | 3134.73147 | 0.22790 | 0.22790 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 31.73000 | 1.41190E-002 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 895.93069 | 895.93069 | 3.84201E-002 | 9.17347E-002 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -10.70000 | 1.50390E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 2560.77911 | 2560.77911 | 0.18613 | 0.18613 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | 29.95400 | 1.41158E-002 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 1607.75045 | 1607.75045 | 6.89448E-002 | 6.89448E-002 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -10.70000 | 1.50390E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 1526.49978 | 1526.49978 | 0.11095 | 0.11095 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 32.10000 | 1.41196E-002 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 1118.40112 | 1118.40112 | 4.79602E-002 | 5.77652E-002 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -10.70000 | 1.50390E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 44742.68990 | 44742.68990 | 3.25247 | 3.25247 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 32.10000 | 1.41196E-002 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 2117.03069 | 2117.03069 | 9.07825E-002 | 9.07825E-002 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -10.70000 | 1.50390E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 20786.07257 | 20786.07257 | 1.51238 | 1.51238 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | 31.79167 | 1.41191E-002 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 6789.96280 | 6789.96280 | 0.29117 | 0.67639 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -10.70000 | 1.50390E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 66507.02151 | 66507.02151 | 4.83641 | 4.83641 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 31.85333 | 1.41192E-002 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 15787.33591 | 15787.33591 | 0.67701 | 1.89399 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -10.70000 | 1.50390E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 11220.67973 | 11220.67973 | 1.09912 | 1.09912 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 31.36000 | 1.41183E-002 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 5936.45686 | 5936.45686 | 0.25606 | 0.25606 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -10.70000 | 1.50390E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 10905.09129 | 10905.09129 | 1.06821 | 1.06821 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 31.26133 | 1.41181E-002 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 5953.74138 | 5953.74138 | 0.25681 | 0.25681 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -10.70000 | 1.50390E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 69430.47567 | 69430.47567 | 6.80064 | 6.80064 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 31.85333 | 1.41192E-002 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 33970.60259 | 33970.60259 | 1.46531 | 1.46531 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -10.70000 | 1.50390E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 62990.91892 | 62990.91892 | 6.17037 | 6.17037 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 32.10000 | 1.41196E-002 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 34303.51064 | 34303.51064 | 1.47967 | 1.47967 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -10.70000 | 1.50390E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 10326.08478 | 10326.08478 | 1.01149 | 1.01149 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 28.86867 | 1.41138E-002 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 5901.34724 | 5901.34724 | 0.25455 | 0.25455 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -10.70000 | 1.50390E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 10048.00038 | 10048.00038 | 0.98425 | 0.98425 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 28.44933 | 1.41131E-002 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 5918.64481 | 5918.64481 | 0.25529 | 0.25529 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -10.70000 | 1.50390E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 21146.01192 | 21146.01192 | 1.53711 | 1.53711 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 32.10000 | 1.41196E-002 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 9562.91587 | 9562.91587 | 0.41009 | 0.47476 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -10.70000 | 1.50390E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 2943.72150 | 2943.72150 | 0.28835 | 0.28835 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:20:00 | 31.45867 | 1.41185E-002 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 1804.68854 | 1804.68854 | 7.78435E-002 | 7.78435E-002 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -10.70000 | 1.50390E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 2854.95575 | 2854.95575 | 0.27966 | 0.27966 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 31.26133 | 1.41181E-002 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 1810.36486 | 1810.36486 | 7.80884E-002 | 7.80884E-002 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -10.70000 | 1.50390E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 13850.88579 | 13850.88579 | 1.35679 | 1.35679 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 31.85333 | 1.41192E-002 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 8606.26390 | 8606.26390 | 0.37122 | 0.37122 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -10.70000 | 1.50390E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 29585.75583 | 29585.75583 | 2.15325 | 2.15325 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 32.10000 | 1.41196E-002 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 5975.45389 | 5975.45389 | 0.25624 | 1.18780 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -10.70000 | 1.50390E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 31001.62452 | 31001.62452 | 2.25626 | 2.25626 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 32.10000 | 1.41196E-002 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
40 | DINING_FLR_6 | Heating | 6110.64078 | 6110.64078 | 0.26204 | 1.18780 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | -10.70000 | 1.50390E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 30917.31403 | 30917.31403 | 2.25327 | 2.25327 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 31.43400 | 1.41184E-002 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 1941.34415 | 1941.34415 | 8.32392E-002 | 0.36735 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | -10.70000 | 1.50390E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
43 | CORRIDOR_FLR_6 | Cooling | 10597.28487 | 10597.28487 | 0.77032 | 0.77032 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 31.97667 | 1.41194E-002 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 6243.95614 | 6243.95614 | 0.26776 | 0.26776 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | -10.70000 | 1.50390E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | FLR_3_DOAS | Cooling | Sensible | 47880.67 | 18.02577 | 2.05125 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | FLR_3_DOAS | Heating | Sensible | 67975.66 | 4.49485 | 2.05125 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
3 | VAV WITH REHEAT | Cooling | Sensible | 409319.98 | 21.81497 | 21.81497 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | VAV WITH REHEAT | Heating | Sensible | 243046.32 | 7.33421 | 7.33421 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.47791 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.60852 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.53200 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.31825 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.26105E-004 |
8 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.08631E-005 |
9 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.31825 |
10 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6957.02345 |
13 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.08631E-005 |
14 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 145.07673 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.36050 |
16 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14177 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.53200 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.19179 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.53200 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.68746E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.22488E-005 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.19179 |
24 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3686.23998 |
27 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.22488E-005 |
28 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 89.29259 |
29 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.22790 |
30 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25970 |
31 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.53200 |
32 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.12124 |
33 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.69252 |
34 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.46711E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.34324E-005 |
37 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.12124 |
38 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1535.40378 |
41 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.34324E-005 |
42 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 34.54218 |
43 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.18613 |
44 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.67240 |
45 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.53200 |
46 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 9.90215E-002 |
47 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.66631E-004 |
50 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.86336E-005 |
51 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 9.90215E-002 |
52 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2129.94003 |
55 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.86336E-005 |
56 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 53.03482 |
57 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.11095 |
58 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.65077 |
59 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.53200 |
60 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 5.90279E-002 |
61 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.85456E-004 |
64 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.25078E-005 |
65 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.90279E-002 |
66 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1429.72125 |
69 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.25078E-005 |
70 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 36.82386 |
71 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.25247 |
72 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 1.82834E-002 |
73 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.53200 |
74 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.73031 |
75 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.53200 |
76 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.08386E-002 |
78 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.83424E-005 |
79 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.73031 |
80 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11241.13597 |
83 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.83424E-005 |
84 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 237.25802 |
85 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.51238 |
86 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.51565E-002 |
87 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.53200 |
88 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.80459 |
89 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.53200 |
90 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.00393E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.65309E-005 |
93 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.80459 |
94 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11034.07592 |
97 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.65309E-005 |
98 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 251.08155 |
99 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 4.83641 |
100 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20611 |
101 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.53200 |
102 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.57297 |
103 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.54963 |
104 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
105 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.84852E-003 |
106 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.56843E-004 |
107 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.57297 |
108 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
110 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 29358.70762 |
111 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.56843E-004 |
112 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 651.69308 |
113 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
114 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.09912 |
115 | Fan:OnOff | ROOM_1_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 1.09912 |
116 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.19340E-005 |
117 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.54115E-004 |
118 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68304 |
119 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
120 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.61542E-003 |
121 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
122 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
123 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.54115E-004 |
124 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.09912 |
125 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 5936.37550 |
126 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.19340E-005 |
127 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 169.62303 |
128 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
129 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.06821 |
130 | Fan:OnOff | ROOM_2_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 1.06821 |
131 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.20852E-005 |
132 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.44470E-004 |
133 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68303 |
134 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
135 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.61879E-003 |
136 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
137 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
138 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.44470E-004 |
139 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.06821 |
140 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 5953.65980 |
141 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.20852E-005 |
142 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 170.11683 |
143 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83707 |
144 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 6.80064 |
145 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 6.80064 |
146 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.97188E-004 |
147 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.14739E-003 |
148 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68362 |
149 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
150 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.54183E-003 |
151 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
152 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
153 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.14739E-003 |
154 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 6.80064 |
155 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 33970.37661 |
156 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.97188E-004 |
157 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 970.64376 |
158 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83730 |
159 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 6.17037 |
160 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 6.17037 |
161 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 3.00100E-004 |
162 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.07270E-003 |
163 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68274 |
164 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
165 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.77253E-003 |
166 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
167 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
168 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.07270E-003 |
169 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 6.17037 |
170 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 34303.28267 |
171 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.00100E-004 |
172 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 980.15462 |
173 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
174 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.01149 |
175 | Fan:OnOff | ROOM_5_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 1.01149 |
176 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.16269E-005 |
177 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.26805E-004 |
178 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68302 |
179 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
180 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.62585E-003 |
181 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
182 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
183 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.26805E-004 |
184 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.01149 |
185 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 5901.26630 |
186 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.16269E-005 |
187 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 168.62000 |
188 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
189 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.98425 |
190 | Fan:OnOff | ROOM_6_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 0.98425 |
191 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.17782E-005 |
192 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.18310E-004 |
193 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68301 |
194 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
195 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.62940E-003 |
196 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
197 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
198 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.18310E-004 |
199 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.98425 |
200 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 5918.56366 |
201 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.17782E-005 |
202 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 169.11417 |
203 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.53711 |
204 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.77217 |
205 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.53200 |
206 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.81774 |
207 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.93417E-004 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.21400E-004 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.81774 |
212 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
213 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
214 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13876.81376 |
215 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.21400E-004 |
216 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 327.48553 |
217 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54338E-002 |
218 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.28835 |
219 | Fan:OnOff | ROOM_1_FLR_6 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 0.28835 |
220 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.57881E-005 |
221 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 9.27651E-005 |
222 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68305 |
223 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
224 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.61002E-003 |
225 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
226 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
227 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 9.27651E-005 |
228 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.28835 |
229 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1804.67734 |
230 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.57881E-005 |
231 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 51.56448 |
232 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54319E-002 |
233 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.27966 |
234 | Fan:OnOff | ROOM_2_FLR_6 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 0.27966 |
235 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.58378E-005 |
236 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 9.00542E-005 |
237 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68304 |
238 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
239 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.61355E-003 |
240 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
241 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
242 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 9.00542E-005 |
243 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.27966 |
244 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1810.35362 |
245 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.58378E-005 |
246 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 51.72665 |
247 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 9.91540E-002 |
248 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.35679 |
249 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 1.35679 |
250 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 7.52906E-005 |
251 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.43271E-004 |
252 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68282 |
253 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
254 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.66725E-003 |
255 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
256 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
257 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.43271E-004 |
258 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.35679 |
259 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 8606.17293 |
260 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.52906E-005 |
261 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 245.90074 |
262 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.15325 |
263 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11737 |
264 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.53200 |
265 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.14553 |
266 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.53200 |
267 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
268 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.24620E-003 |
269 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.05146E-004 |
270 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.14553 |
271 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
272 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
273 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12018.88380 |
274 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.05146E-004 |
275 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 264.22067 |
276 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.25626 |
277 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11201 |
278 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.53200 |
279 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.20033 |
280 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.53200 |
281 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
282 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.40150E-003 |
283 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.08858E-004 |
284 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.20033 |
285 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
286 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
287 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12443.19314 |
288 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.08858E-004 |
289 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 273.18942 |
290 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.25327 |
291 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 6.28349E-002 |
292 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.53200 |
293 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.19874 |
294 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.53200 |
295 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
296 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.09060E-002 |
297 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.21539E-005 |
298 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.19874 |
299 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
300 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
301 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8247.63290 |
302 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.21539E-005 |
303 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 174.74484 |
304 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.77032 |
305 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.40768 |
306 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.53200 |
307 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.40981 |
308 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
309 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
310 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 9.34567E-004 |
311 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.35401E-005 |
312 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.40981 |
313 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
314 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
315 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8406.08396 |
316 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.35401E-005 |
317 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 206.78710 |
318 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05132 |
319 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05132 |
320 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05132 |
321 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05132 |
322 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05132 |
323 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05132 |
324 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
325 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
326 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 11.66935 |
327 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 11.66935 |
328 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 21.93487 |
329 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 11.66935 |
330 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 21.81497 |
331 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 21.81497 |
332 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
333 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.53492 |
334 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05132 |
335 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 21.81497 |
336 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05132 |
337 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05125 |
338 | HeatExchanger:AirToAir:SensibleAndLatent | FLR_3_DOAS OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.05125 |
339 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 32.10000 |
340 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
341 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.93776 |
342 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.41196E-002 |
343 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
344 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Coil Load [W] | 86334.70852 |
345 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.46916E-003 |
346 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 2.05132 |
347 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Rated Capacity [W] | 20393.41537 |
348 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.78410E-004 |
349 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 336.60104 |
350 | Fan:ConstantVolume | FLR_3_DOAS FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05125 |
351 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.46916E-003 |
352 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.92855E-004 |
353 | Controller:WaterCoil | FLR_3_DOAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.78410E-004 |
354 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 21.81497 |
355 | HeatExchanger:AirToAir:SensibleAndLatent | VAV WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 11.66146 |
356 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 28.32906 |
357 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
358 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.98774 |
359 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.20482E-002 |
360 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
361 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 702620.51039 |
362 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.00949E-002 |
363 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 21.81497 |
364 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 216876.08691 |
365 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.89733E-003 |
366 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 3579.62186 |
367 | Fan:VariableVolume | VAV WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 21.81497 |
368 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.00949E-002 |
369 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 2.36971E-005 |
370 | Controller:WaterCoil | VAV WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.89733E-003 |
371 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 2.87539E-002 |
372 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 4694.63443 |
373 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 4.05787E-003 |
374 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.48694 |
375 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 4.05787E-003 |
376 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 1222.05124 |
377 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
378 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 463839.08626 |
379 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 463839.09000 |
380 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 4.05787E-003 |
381 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 2.87539E-002 |
382 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 3.45047 |
383 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 2.87539E-002 |
384 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 3250.25376 |
385 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 2.87539E-002 |
386 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1005385.82262 |
387 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1005991.43000 |
388 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 114.68302 |
389 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
390 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
391 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
392 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
393 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | 6992.95 |
2 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 3702.19 |
3 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1542.67 |
4 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | 2138.89 |
5 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | 1435.44 |
6 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 11298.53 |
7 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | 11085.67 |
8 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | 29499.56 |
9 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | 6393.49 |
10 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | 6412.11 |
11 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 36586.08 |
12 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 36944.59 |
13 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | 6355.68 |
14 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | 6374.31 |
15 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 13939.43 |
16 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | 1943.61 |
17 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | 1949.72 |
18 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 9268.71 |
19 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | 12077.14 |
20 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | 12503.59 |
21 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | 8289.59 |
22 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 8441.87 |
23 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | 14451.42 |
24 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | 153685.23 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | 18076.69 | 15601.96 | 2474.73 | 0.86 | 3318.50 | 33.66 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | 17579.17 | 15167.08 | 2412.09 | 0.86 | 3224.82 | 32.71 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 110307.23 | 95974.08 | 14333.15 | 0.87 | 20566.07 | 208.59 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 104384.94 | 88657.00 | 15727.93 | 0.85 | 18585.70 | 188.51 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | 16667.35 | 14369.57 | 2297.77 | 0.86 | 3052.92 | 30.96 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | 16229.04 | 13986.41 | 2242.63 | 0.86 | 2970.38 | 30.13 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | 4737.67 | 4091.44 | 646.23 | 0.86 | 870.76 | 8.83 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | 4597.80 | 3969.15 | 628.65 | 0.86 | 844.40 | 8.56 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 22525.72 | 19336.14 | 3189.58 | 0.86 | 4090.44 | 41.49 |
10 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | 63706.66 | 41742.75 | 21963.91 | 0.66 | 8475.32 | 85.96 |
11 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | 636434.96 | 426104.57 | 210330.39 | 0.67 | 91575.43 | 928.81 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 4.09 | 13.95 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.419 | 0.394 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.419 | 0.394 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.820 | 0.731 | 22.63 | 45.89 | 22.63 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 23.26 | 23.26 | 23.26 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.820 | 0.731 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.820 | 0.731 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.820 | 0.731 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.820 | 0.731 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 2.390 | 2.390 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.820 | 0.731 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.820 | 0.731 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.820 | 0.731 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.820 | 0.731 | 63.73 | 129.23 | 63.73 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 65.50 | 65.50 | 65.50 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.820 | 0.731 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.820 | 0.731 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.820 | 0.731 | 82.79 | 167.88 | 82.79 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 85.08 | 85.08 | 85.08 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.820 | 0.731 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.917 | 0.806 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.917 | 0.806 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.917 | 0.806 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.917 | 0.806 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.917 | 0.806 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.917 | 0.806 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.917 | 0.806 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.917 | 0.806 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.917 | 0.806 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.917 | 0.806 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.021 | 0.886 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.021 | 0.886 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.021 | 0.886 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.021 | 0.886 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.930 | 0.816 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.930 | 0.816 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.930 | 0.816 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.930 | 0.816 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.930 | 0.816 | 13.70 | 20.44 | 13.70 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 6.74 | 6.74 | 6.74 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.034 | 0.896 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.034 | 0.896 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.034 | 0.896 | 16.77 | 21.37 | 16.77 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.034 | 0.896 | 34.86 | 52.03 | 34.86 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 17.17 | 17.17 | 17.17 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.034 | 0.896 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.034 | 0.896 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.034 | 0.896 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.034 | 0.896 | 34.86 | 52.03 | 34.86 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 17.17 | 17.17 | 17.17 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 1.8205267762E-002 | 2.1814489346E-002 | Pass | Pass | 3.8206684903E-003 | 1.1476017778E-002 | Pass | Pass |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 9.7311032290E-003 | 2.8068067730E-002 | Pass | Pass | 0.2873762853 | 1.0605128213 | Pass | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.0228410285E-002 | 1.8408981069E-002 | Pass | Pass | 2.2165644123E-002 | 4.8609427466E-002 | Pass | Pass |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.7296963039E-004 | 3.5261533354E-004 | Pass | Pass | 0.1083694160 | 0.2798056514 | Pass | Pass |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.4905000384E-004 | 3.4687231275E-004 | Pass | Pass | 2.7485604797E-002 | 4.1724663656E-002 | Pass | Pass |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 7.7496212494E-002 | 0.2211549440 | Pass | Pass | 1.9326829942E-002 | 5.1261029209E-002 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.2072204282E-002 | 8.1932779296E-002 | Pass | Pass | 4.4623162617E-002 | 8.8762211101E-002 | Pass | Pass |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 3.1371281810E-002 | 4.6688463171E-002 | Pass | Pass | 1.6626570147E-002 | 3.3301926190E-002 | Pass | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.6145911767E-002 | 0.2664085466 | Pass | Pass | 0.1260281044 | 0.6646110830 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.2619723451E-002 | 0.2934866988 | Pass | Pass | 7.5120346541E-002 | 0.1683448686 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 5.8244673226E-002 | 6.2349897407E-002 | Pass | Pass | 7.4930470297E-003 | 7.1367325895E-002 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.1794383823E-002 | 0.1221787640 | Pass | Pass | 6.1620171511E-002 | 0.1668326902 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 7.3395275550E-002 | 0.2244147272 | Pass | Pass | 0.1364233084 | 0.4702360204 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 7.6644534252E-002 | 0.2440263219 | Pass | Pass | 0.1210328366 | 0.6915545425 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.5953721906E-004 | 3.3089676752E-004 | Pass | Pass | 0.1858754388 | 0.4079401869 | Pass | Pass |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.3583770487E-002 | 0.3036162305 | Pass | Pass | 0.1309464109 | 0.4599431369 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.2660937118E-002 | 0.3107649932 | Pass | Pass | 0.1140550787 | 0.4946144648 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 7.0768959285E-002 | 0.1694280782 | Pass | Pass | 5.4133519335E-002 | 0.1456362022 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 5.3829437456E-002 | 9.8640134477E-002 | Pass | Pass | 9.2158094265E-003 | 2.1029729564E-002 | Pass | Pass |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 4.5860392710E-002 | 7.9877699662E-002 | Pass | Pass | 1.0108311367E-002 | 2.7388333770E-002 | Pass | Pass |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 3.3289021228E-002 | 0.1019267375 | Pass | Pass | 2.2141535152E-002 | 4.0768520114E-002 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 7.6988369817E-004 | 5.9978030426E-004 | Pass | Pass | 0.2309274155 | 0.5713351191 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:32
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 4381.71 | 46.19 | 1380.88 | 5459.46 | 5277.89 | 16546.13 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:32
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -10.70 | 0.00 | -10.70 | Wetbulb [C] | 7.50 | 320.00 |
NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 32.10 | 7.40 | 23.10 | Wetbulb [C] | 5.60 | 230.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 172.00 | 59 | |||
Feb | 49.00 | 37 | |||
Mar | 40.00 | 38 | |||
Apr | 70.00 | 48 | |||
May | 70.00 | 36 | |||
Jun | 25.00 | 15 | |||
Jul | 64.00 | 20 | |||
Aug | 2.00 | 4 | |||
Sep | 73.00 | 32 | |||
Oct | 7.00 | 8 | |||
Nov | 88.00 | 34 | |||
Dec | 62.00 | 39 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:32
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 211.13 | 211.13 | 0.00 | 90.00 | N |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.399 | 0.419 | 55.76 | 55.76 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 211.13 | 211.13 | 180.00 | 90.00 | S |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.399 | 0.419 | 55.76 | 55.76 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.731 | 0.820 | 45.89 | 22.63 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.731 | 0.820 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.731 | 0.820 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.731 | 0.820 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.731 | 0.820 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.731 | 0.820 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.731 | 0.820 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.731 | 0.820 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.731 | 0.820 | 129.23 | 63.73 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.731 | 0.820 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.731 | 0.820 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.731 | 0.820 | 167.88 | 82.79 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.731 | 0.820 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.806 | 0.917 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.806 | 0.917 | 104.06 | 69.72 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.806 | 0.917 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.806 | 0.917 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.806 | 0.917 | 847.14 | 567.58 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.806 | 0.917 | 847.37 | 567.71 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.806 | 0.917 | 104.06 | 69.72 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.806 | 0.917 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.806 | 0.917 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.806 | 0.917 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 26.02 | 17.43 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.816 | 0.930 | 13.94 | 9.34 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.816 | 0.930 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | RES_ROOF | 0.23 | 0.182 | 0.186 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | RES_EXT_WALL_TOP | 0.30 | 0.816 | 0.930 | 13.94 | 9.34 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.816 | 0.930 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | RES_ROOF | 0.23 | 0.182 | 0.186 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.816 | 0.930 | 183.96 | 123.26 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | RES_ROOF | 0.23 | 0.182 | 0.186 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 97.55 | 65.36 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 97.55 | 65.36 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 21.37 | 16.77 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 52.03 | 34.86 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 13.94 | 9.34 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 17.65 | 11.83 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 52.03 | 34.86 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 167.42 | 167.42 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_FLOOR | BASEMENT_FLOOR | 0.30 | 1.441 | 2.705 | 1978.83 | 1978.83 | 0.00 | 180.00 | |
BASEMENT_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 67.07 | 67.07 | 180.00 | 0.00 | |
BASEMENT_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 77.67 | 77.67 | 180.00 | 0.00 | |
BASEMENT_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 164.24 | 164.24 | 180.00 | 0.00 | |
BASEMENT_CEILING_4 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 94.76 | 94.76 | 180.00 | 0.00 | |
BASEMENT_CEILING_5 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 78.04 | 78.04 | 180.00 | 0.00 | |
BASEMENT_CEILING_6 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 188.86 | 188.86 | 180.00 | 0.00 | |
BASEMENT_CEILING_7 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 1088.56 | 1088.56 | 180.00 | 0.00 | |
BASEMENT_CEILING_8 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 219.63 | 219.63 | 90.00 | 0.00 | |
RETAIL_1_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_1_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
RETAIL_1_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 67.07 | 67.07 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
RETAIL_2_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_2_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 90.00 | 90.00 | E |
RETAIL_2_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 77.67 | 77.67 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 77.67 | 77.67 | 180.00 | 0.00 | |
MECH_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
MECH_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 180.00 | 90.00 | S |
MECH_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
MECH_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 164.24 | 164.24 | 0.00 | 180.00 | |
MECH_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 164.24 | 164.24 | 180.00 | 0.00 | |
STORAGE_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
STORAGE_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 180.00 | 90.00 | S |
STORAGE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
STORAGE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 94.76 | 94.76 | 0.00 | 180.00 | |
STORAGE_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 94.76 | 94.76 | 180.00 | 0.00 | |
LAUNDRY_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 180.00 | 90.00 | S |
LAUNDRY_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 270.00 | 90.00 | W |
LAUNDRY_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 78.04 | 78.04 | 0.00 | 180.00 | |
LAUNDRY_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 78.04 | 78.04 | 180.00 | 0.00 | |
CAFE_FLR_1_WALL_1_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_2_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
CAFE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 188.86 | 188.86 | 0.00 | 180.00 | |
LOBBY_FLR_1_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 90.00 | 90.00 | E |
LOBBY_FLR_1_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 1088.56 | 1088.56 | 180.00 | 180.00 | |
LOBBY_FLR_1_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 219.63 | 219.63 | 90.00 | 180.00 | |
LOBBY_FLR_1_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 1062.83 | 1062.83 | 270.00 | 0.00 | |
ROOM_1_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_1_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
ROOM_1_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_1_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_2_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
ROOM_2_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_2_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_2_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 156.07 | 156.07 | 180.00 | 0.00 | |
ROOM_3_MULT19_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.14 | 847.14 | 0.00 | 90.00 | N |
ROOM_3_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_3_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 1863.81 | 1863.81 | 0.00 | 180.00 | |
ROOM_3_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 1863.81 | 1863.81 | 180.00 | 0.00 | |
ROOM_4_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_4_MULT19_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.37 | 847.37 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_4_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 1864.32 | 1864.32 | 0.00 | 180.00 | |
ROOM_4_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 1864.32 | 1864.32 | 180.00 | 0.00 | |
ROOM_5_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
ROOM_5_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_5_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_6_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
ROOM_6_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_6_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 156.07 | 156.07 | 180.00 | 0.00 | |
CORRIDOR_FLR_3_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.28 | 847.28 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_4_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.27 | 847.27 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 297.29 | 297.29 | 180.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 963.06 | 963.06 | 270.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_3 | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 297.26 | 297.26 | 90.00 | 180.00 | |
CORRIDOR_FLR_3_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 297.29 | 297.29 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 963.06 | 963.06 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 297.26 | 297.26 | 90.00 | 0.00 | |
ROOM_1_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 0.00 | 90.00 | N |
ROOM_1_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_1_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_2_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_2_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 180.00 | 90.00 | S |
ROOM_2_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_3_MULT9_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.96 | 183.96 | 0.00 | 90.00 | N |
ROOM_3_MULT9_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 90.00 | 90.00 | E |
ROOM_3_MULT9_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 270.00 | 90.00 | W |
ROOM_3_MULT9_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 220.77 | 220.77 | 0.00 | 180.00 | |
BANQUET_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
BANQUET_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
BANQUET_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
BANQUET_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 331.66 | 331.66 | 0.00 | 180.00 | |
DINING_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
DINING_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
DINING_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
DINING_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 331.66 | 331.66 | 0.00 | 180.00 | |
KITCHEN_FLR_6_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 7.43 | 7.43 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 103.30 | 103.30 | 180.00 | 180.00 | |
CORRIDOR_FLR_6_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 104.98 | 104.98 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_1_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.95 | 183.95 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 11.15 | 11.15 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 40.88 | 40.88 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 412.12 | 412.12 | 180.00 | 180.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3957.66 | 0.00 | 90.00 | N | ||
RETAIL_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 134.14 | 0.00 | 90.00 | N | ||
RETAIL_2_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 155.34 | 0.00 | 90.00 | N | ||
MECH_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 328.49 | 0.00 | 90.00 | N | ||
STORAGE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 189.52 | 0.00 | 90.00 | N | ||
LAUNDRY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 156.08 | 0.00 | 90.00 | N | ||
CAFE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 377.72 | 0.00 | 90.00 | N | ||
LOBBY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 2616.37 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3727.63 | 0.00 | 90.00 | N | ||
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3728.64 | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3115.24 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.04 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.03 | 0.00 | 90.00 | N | ||
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 441.55 | 0.00 | 90.00 | N | ||
BANQUET_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
DINING_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 206.61 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 824.25 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.36 | 23.26 | 0.00 | 0.00 | 23.26 | 23.26 | 2.159 | 0.361 | 0.397 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.36 | 65.50 | 0.00 | 0.00 | 65.50 | 65.50 | 2.159 | 0.361 | 0.397 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.36 | 85.08 | 0.00 | 0.00 | 85.08 | 85.08 | 2.159 | 0.361 | 0.397 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.38_SHGC_0.36 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.159 | 0.361 | 0.397 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.38_SHGC_0.36 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.159 | 0.361 | 0.397 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.38_SHGC_0.36 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.159 | 0.361 | 0.397 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.38_SHGC_0.36 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.159 | 0.361 | 0.397 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.38_SHGC_0.36 | 3.68 | 0.00 | 0.00 | 3.68 | 279.56 | 2.159 | 0.361 | 0.397 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.38_SHGC_0.36 | 3.68 | 0.00 | 0.00 | 3.68 | 279.65 | 2.159 | 0.361 | 0.397 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.38_SHGC_0.36 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.159 | 0.361 | 0.397 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.38_SHGC_0.36 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.159 | 0.361 | 0.397 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.38_SHGC_0.36 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.159 | 0.361 | 0.397 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.38_SHGC_0.36 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.159 | 0.361 | 0.397 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.36 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.159 | 0.361 | 0.397 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.36 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 2.159 | 0.361 | 0.397 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.36 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 2.159 | 0.361 | 0.397 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.36 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.159 | 0.361 | 0.397 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.38_SHGC_0.36 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.159 | 0.361 | 0.397 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.38_SHGC_0.36 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.159 | 0.361 | 0.397 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.38_SHGC_0.36 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.159 | 0.361 | 0.397 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.38_SHGC_0.36 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.159 | 0.361 | 0.397 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.38_SHGC_0.36 | 6.74 | 0.00 | 0.00 | 6.74 | 60.70 | 2.159 | 0.361 | 0.397 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.36 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.159 | 0.361 | 0.397 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.36 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.159 | 0.361 | 0.397 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.36 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.159 | 0.361 | 0.397 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.36 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.159 | 0.361 | 0.397 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | |||||||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.36 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.159 | 0.361 | 0.397 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.36 | 5.82 | 0.00 | 0.00 | 5.82 | 5.82 | 2.159 | 0.361 | 0.397 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.36 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 2.159 | 0.361 | 0.397 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.36 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.159 | 0.361 | 0.397 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 1213.79 | 2.159 | 0.361 | 0.397 | |||||||||||||||||
North Total or Average | 432.95 | 2.159 | 0.361 | 0.397 | |||||||||||||||||
Non-North Total or Average | 780.84 | 2.159 | 0.361 | 0.397 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 1.760 | 2.390 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:32
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:32
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 8.8143 | 1978.83 | 17441.96 | LightsWired | LTG_SCH_BASEMENT | 49.32 | 168.00 | 49.26 | 0.0000 | Y | 161.29 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | RETAIL_1_FLR_1 | GENERAL | 11.3140 | 67.07 | 758.85 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 7.31 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | RETAIL_2_FLR_1 | GENERAL | 11.3140 | 77.67 | 878.75 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 8.46 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | MECH_FLR_1 | GENERAL | 4.6285 | 164.24 | 760.20 | LightsWired | LTG_SCH_MECHANIC | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 8.37 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | STORAGE_FLR_1 | GENERAL | 5.7199 | 94.76 | 542.02 | LightsWired | LTG_SCH_STORAGE | 30.30 | 168.00 | 30.27 | 0.0000 | Y | 3.08 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | LAUNDRY_FLR_1 | GENERAL | 4.6285 | 78.04 | 361.20 | LightsWired | LTG_SCH_LAUNDRY | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 3.98 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | CAFE_FLR_1 | GENERAL | 10.0104 | 188.86 | 1890.59 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 39.84 | 0.0000 | Y | 14.14 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | LOBBY_FLR_1 | GENERAL | 10.7639 | 1308.19 | 14081.18 | LightsWired | LTG_SCH_LOBBY | 44.02 | 168.00 | 41.60 | 0.0000 | Y | 109.96 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | ROOM_1_FLR_3 | GENERAL | 8.2882 | 156.09 | 1293.69 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | ROOM_2_FLR_3 | GENERAL | 8.2882 | 156.07 | 1293.54 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | GENERAL | 8.2882 | 1863.81 | 15447.65 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 110.38 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | GENERAL | 8.2882 | 1864.32 | 15451.87 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 110.41 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | ROOM_5_FLR_3 | GENERAL | 8.2882 | 156.09 | 1293.69 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | ROOM_6_FLR_3 | GENERAL | 8.2882 | 156.07 | 1293.54 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | CORRIDOR_FLR_3 | GENERAL | 7.1042 | 1557.62 | 11065.59 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 91.33 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | ROOM_1_FLR_6 | GENERAL | 8.2882 | 39.02 | 323.42 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 2.31 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | ROOM_2_FLR_6 | GENERAL | 8.2882 | 39.02 | 323.38 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 2.31 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | GENERAL | 8.2882 | 220.77 | 1829.83 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 13.08 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | BANQUET_FLR_6 | GENERAL | 10.0104 | 331.66 | 3320.03 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 49.49 | 0.0000 | Y | 30.84 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | DINING_FLR_6 | GENERAL | 10.0104 | 331.66 | 3320.03 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 49.49 | 0.0000 | Y | 30.84 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | KITCHEN_FLR_6 | GENERAL | 11.4097 | 103.30 | 1178.68 | LightsWired | LTG_SCH_KITCHEN | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 12.97 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | CORRIDOR_FLR_6 | GENERAL | 7.1042 | 412.12 | 2927.80 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 24.17 |
Interior Lighting Total | 8.5566 | 11345.29 | 97077.49 | 456.46 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
LOBBY_FLR_1_DAYLREFPT1 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.07 | 14081.18 | 985.68 |
LOBBY_FLR_1_DAYLREFPT2 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.07 | 14081.18 | 985.68 |
CAFE_FLR_1_DAYLREFPT1 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1890.59 | 737.33 |
CAFE_FLR_1_DAYLREFPT2 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1890.59 | 737.33 |
DINING_FLR_6_DAYLREFPT1 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
DINING_FLR_6_DAYLREFPT2 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
BANQUET_FLR_6_DAYLREFPT1 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
BANQUET_FLR_6_DAYLREFPT2 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 12338.45 | AstronomicalClock | - | 83.64 | 83.64 | 193.72 | |
Exterior Lighting Total | 12338.45 | 193.72 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:32
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 463839.09 | 0.80 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 1005991.43 | 2.96 | 1005991.43 | 2.96 | 4.09 | 13.95 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 12381.93 | 18076.69 | 15601.96 | 2474.73 | 0.86 | - | 3318.50 | 33.66 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 12044.70 | 17579.17 | 15167.08 | 2412.09 | 0.86 | - | 3224.82 | 32.71 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 75085.41 | 110307.23 | 95974.08 | 14333.15 | 0.87 | - | 20566.07 | 208.59 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 72473.87 | 104384.94 | 88657.00 | 15727.93 | 0.85 | - | 18585.70 | 188.51 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 11427.00 | 16667.35 | 14369.57 | 2297.77 | 0.86 | - | 3052.92 | 30.96 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 11129.96 | 16229.04 | 13986.41 | 2242.63 | 0.86 | - | 2970.38 | 30.13 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3243.61 | 4737.67 | 4091.44 | 646.23 | 0.86 | - | 870.76 | 8.83 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3148.82 | 4597.80 | 3969.15 | 628.65 | 0.86 | - | 844.40 | 8.56 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 15499.35 | 22525.72 | 19336.14 | 3189.58 | 0.86 | - | 4090.44 | 41.49 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | 86334.71 | 63706.66 | 41742.75 | 21963.91 | 0.66 | - | 8475.32 | 85.96 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | 702620.51 | 636434.96 | 426104.57 | 210330.39 | 0.67 | - | 91575.43 | 928.81 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 6957.02 | 6992.95 | - |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 3686.24 | 3702.19 | - |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1535.40 | 1542.67 | - |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2129.94 | 2138.89 | - |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1429.72 | 1435.44 | - |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 11241.14 | 11298.53 | - |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 11034.08 | 11085.67 | - |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 29358.71 | 29499.56 | - |
ROOM_1_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 5936.38 | 6393.49 | - |
ROOM_2_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 5953.66 | 6412.11 | - |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 33970.38 | 36586.08 | - |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 34303.28 | 36944.59 | - |
ROOM_5_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 5901.27 | 6355.68 | - |
ROOM_6_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 5918.56 | 6374.31 | - |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 13876.81 | 13939.43 | - |
ROOM_1_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 1804.68 | 1943.61 | - |
ROOM_2_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 1810.35 | 1949.72 | - |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 8606.17 | 9268.71 | - |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 12018.88 | 12077.14 | - |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 12443.19 | 12503.59 | - |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 8247.63 | 8289.59 | - |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 8406.08 | 8441.87 | - |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | 20393.42 | 14451.42 | - |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | 216876.09 | 153685.23 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 0.24 | 76.61 | 324.68 | 1.00 | 2.78 | General | ||
LOBBY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.24 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
ROOM_1_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 1.10 | 773.38 | 703.64 | 1.00 | 1.17 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 |
ROOM_2_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 1.07 | 751.63 | 703.64 | 1.00 | 1.18 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 |
ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 6.80 | 4785.18 | 703.64 | 1.00 | 0.95 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 |
ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 6.17 | 4341.70 | 703.64 | 1.00 | 0.96 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 |
ROOM_5_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 1.01 | 711.72 | 703.64 | 1.00 | 1.19 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 |
ROOM_6_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 0.98 | 692.56 | 703.64 | 1.00 | 1.20 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 |
ROOM_1_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 0.29 | 202.89 | 703.64 | 1.00 | 1.74 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:20:00 |
ROOM_2_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 0.28 | 196.78 | 703.64 | 1.00 | 1.76 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 |
ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 1.36 | 954.69 | 703.64 | 1.00 | 1.13 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 |
BANQUET_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
DINING_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 1.89 | 612.92 | 324.68 | 1.00 | 1.48 | General | ||
FLR_3_DOAS FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.93 | 1070.05 | 1.00 | 1.30 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
VAV WITH REHEAT FAN | Fan:VariableVolume | 0.62 | 1389.42 | 21.81 | 48879.45 | 2240.64 | 1.00 | 1.11 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.028754 | 4694.63 | 163269.44 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.004058 | 1222.05 | 301156.09 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.028754 | 3250.25 | 113036.94 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH LAUNDRY G WATER HEATER | WaterHeater:Mixed | 1.14 | 163316.00 | 0.80 | 11.51 | 0.44 |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.22 | 1.12 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.60 | 0.80 | 5.78 | 0.37 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:32
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 34087.89 | 34087.89 | 17.23 | 2.478 | 2.478 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 24.00 | 24.00 | 0.00921 | 28.94 | 0.01411 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 4958.75 | 4958.75 | 73.93 | 0.361 | 0.361 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | 24.00 | 24.00 | 0.00905 | 31.79 | 0.01412 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 3134.73 | 3134.73 | 40.36 | 0.228 | 0.228 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 24.00 | 24.00 | 0.00944 | 31.73 | 0.01412 | 0.092 | 0.00 |
MECH_FLR_1 | 2560.78 | 2560.78 | 15.59 | 0.186 | 0.186 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | 24.00 | 24.00 | 0.00884 | 29.95 | 0.01412 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1526.50 | 1526.50 | 16.11 | 0.111 | 0.111 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00891 | 32.10 | 0.01412 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 44742.69 | 44742.69 | 573.33 | 3.252 | 3.252 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00855 | 32.10 | 0.01412 | 0.000 | 0.00 |
CAFE_FLR_1 | 20786.07 | 20786.07 | 110.06 | 1.512 | 1.512 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | 24.00 | 23.99 | 0.01007 | 31.79 | 0.01412 | 0.676 | 0.00 |
LOBBY_FLR_1 | 66507.02 | 66507.02 | 50.84 | 4.836 | 4.836 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 23.99 | 0.00996 | 31.85 | 0.01412 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 11220.68 | 11220.68 | 287.55 | 1.099 | 1.099 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 21.11 | 21.11 | 0.00862 | 31.36 | 0.01412 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 10905.09 | 10905.09 | 279.49 | 1.068 | 1.068 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 21.11 | 21.11 | 0.00862 | 31.26 | 0.01412 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 69430.48 | 69430.48 | 2831.14 | 6.801 | 6.801 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 21.11 | 21.11 | 0.00854 | 31.85 | 0.01412 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 62990.92 | 62990.92 | 2567.86 | 6.170 | 6.170 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 21.11 | 21.11 | 0.00877 | 32.10 | 0.01412 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 10326.08 | 10326.08 | 264.62 | 1.011 | 1.011 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 21.11 | 21.11 | 0.00863 | 28.87 | 0.01411 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 10048.00 | 10048.00 | 257.53 | 0.984 | 0.984 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 21.11 | 21.11 | 0.00863 | 28.45 | 0.01411 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 21146.01 | 21146.01 | 54.30 | 1.537 | 1.537 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 24.00 | 0.00944 | 32.10 | 0.01412 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 2943.72 | 2943.72 | 75.44 | 0.288 | 0.288 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:20:00 | 21.11 | 21.11 | 0.00861 | 31.46 | 0.01412 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2854.96 | 2854.96 | 73.17 | 0.280 | 0.280 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 21.11 | 21.11 | 0.00861 | 31.26 | 0.01412 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 13850.89 | 13850.89 | 564.64 | 1.357 | 1.357 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 21.11 | 21.11 | 0.00867 | 31.85 | 0.01412 | 0.099 | 0.00 |
BANQUET_FLR_6 | 29585.76 | 29585.76 | 89.21 | 2.153 | 2.153 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 24.00 | 23.98 | 0.01042 | 32.10 | 0.01412 | 1.188 | 0.00 |
DINING_FLR_6 | 31001.62 | 31001.62 | 93.47 | 2.256 | 2.256 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 24.00 | 23.99 | 0.01033 | 32.10 | 0.01412 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 30917.31 | 30917.31 | 299.28 | 2.253 | 2.253 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 24.00 | 23.97 | 0.01008 | 31.43 | 0.01412 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 10597.28 | 10597.28 | 25.71 | 0.770 | 0.770 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 24.00 | 0.00901 | 31.98 | 0.01412 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 0.854 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.35 | 0.00150 | -10.70 | 0.00150 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 2674.66 | 2674.66 | 39.88 | 0.115 | 0.115 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00773 | -10.70 | 0.00150 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 895.93 | 895.93 | 11.54 | 0.038 | 0.092 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00769 | -10.70 | 0.00150 | 0.092 | 0.00 |
MECH_FLR_1 | 1607.75 | 1607.75 | 9.79 | 0.069 | 0.069 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00760 | -10.70 | 0.00150 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1118.40 | 1118.40 | 11.80 | 0.048 | 0.058 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00767 | -10.70 | 0.00150 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 2117.03 | 2117.03 | 27.13 | 0.091 | 0.091 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00759 | -10.70 | 0.00150 | 0.000 | 0.00 |
CAFE_FLR_1 | 6789.96 | 6789.96 | 35.95 | 0.291 | 0.676 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00777 | -10.70 | 0.00150 | 0.676 | 0.00 |
LOBBY_FLR_1 | 15787.34 | 15787.34 | 12.07 | 0.677 | 1.894 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00772 | -10.70 | 0.00150 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 5936.46 | 5936.46 | 152.13 | 0.256 | 0.256 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00772 | -10.70 | 0.00150 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 5953.74 | 5953.74 | 152.59 | 0.257 | 0.257 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00772 | -10.70 | 0.00150 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 33970.60 | 33970.60 | 1385.21 | 1.465 | 1.465 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00774 | -10.70 | 0.00150 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 34303.51 | 34303.51 | 1398.40 | 1.480 | 1.480 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00774 | -10.70 | 0.00150 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 5901.35 | 5901.35 | 151.23 | 0.255 | 0.255 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00772 | -10.70 | 0.00150 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 5918.64 | 5918.64 | 151.69 | 0.255 | 0.255 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00772 | -10.70 | 0.00150 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 9562.92 | 9562.92 | 24.56 | 0.410 | 0.475 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00779 | -10.70 | 0.00150 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 1804.69 | 1804.69 | 46.25 | 0.078 | 0.078 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.11 | 21.11 | 0.00777 | -10.70 | 0.00150 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 1810.36 | 1810.36 | 46.40 | 0.078 | 0.078 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.11 | 21.11 | 0.00777 | -10.70 | 0.00150 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8606.26 | 8606.26 | 350.84 | 0.371 | 0.371 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00778 | -10.70 | 0.00150 | 0.099 | 0.00 |
BANQUET_FLR_6 | 5975.45 | 5975.45 | 18.02 | 0.256 | 1.188 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00783 | -10.70 | 0.00150 | 1.188 | 0.00 |
DINING_FLR_6 | 6110.64 | 6110.64 | 18.42 | 0.262 | 1.188 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 21.00 | 21.00 | 0.00783 | -10.70 | 0.00150 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 1941.34 | 1941.34 | 18.79 | 0.083 | 0.367 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 21.00 | 21.00 | 0.00662 | -10.70 | 0.00150 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 6243.96 | 6243.96 | 15.15 | 0.268 | 0.268 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 21.00 | 21.00 | 0.00786 | -10.70 | 0.00150 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
FLR_3_DOAS | 18.03 | 2.05 | 4.49 | 2.05 | 2.0513 | 2.0513 | 2.0513 | 1.0000 | 0.3000 |
VAV WITH REHEAT | 21.81 | 21.81 | 7.33 | 7.33 | 21.8150 | 11.6694 | 21.8150 | 0.5349 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 6957.023 | 6957.023 | 1.318248 | 0.00006086 | 145.077 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 6957.02 | 6957.02 | 1.318248 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | 6996.12 | 6996.12 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 3686.240 | 3686.240 | 0.191787 | 0.00003225 | 89.293 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 3686.24 | 3686.24 | 0.191787 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00773310 | 49.9904 | 2674.66 | 0.00 | 3705.45 | 3705.45 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 1535.404 | 1535.404 | 0.121241 | 0.00001343 | 34.542 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 1535.40 | 1535.40 | 0.121241 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00769428 | 49.7419 | 895.93 | 0.00 | 1543.70 | 1543.70 |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 2129.940 | 2129.940 | 0.099021 | 0.00001863 | 53.035 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 2129.94 | 2129.94 | 0.099021 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00760323 | 49.1604 | 1607.75 | 0.00 | 2140.93 | 2140.93 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 1429.721 | 1429.721 | 0.059028 | 0.00001251 | 36.824 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 1429.72 | 1429.72 | 0.059028 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00766750 | 49.5709 | 1118.40 | 0.00 | 1436.94 | 1436.94 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 11241.136 | 11241.136 | 1.730313 | 0.00009834 | 237.258 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 11241.14 | 11241.14 | 1.730313 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00758961 | 49.0741 | 2117.03 | 0.00 | 11304.05 | 11304.05 |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 11034.076 | 11034.076 | 0.804586 | 0.00009653 | 251.082 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 11034.08 | 11034.08 | 0.804586 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00776635 | 50.2025 | 6789.96 | 0.00 | 11093.48 | 11093.48 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 29358.708 | 29358.708 | 2.572971 | 0.00025684 | 651.693 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 29358.71 | 29358.71 | 2.572971 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00771516 | 49.8752 | 15787.34 | 0.00 | 29518.25 | 29518.25 |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 12381.929 | -999.000 | 1.099121 | 0.00035411 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | unknown | 7/21 16:30:00 | 12381.93 | 12039.09 | 1.099121 | 21.68 | 15.65 | 0.00861542 | 12.80 | 12.09 | 0.00850000 | 31.36 | 0.01411830 | 22.93 | 0.0000 | 21.11 | 0.00861542 | 55.2392 | 11220.68 | 0.00 | 12403.08 | 12403.08 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 5936.375 | 5936.375 | 0.256062 | 0.00005193 | 169.623 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 5936.38 | 5936.38 | 0.256062 | 21.11 | 14.63 | 0.00772290 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.11 | 0.00772290 | 49.5861 | 5936.46 | 0.00 | 6399.58 | 6399.58 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 12044.698 | -999.000 | 1.068208 | 0.00034447 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | unknown | 7/21 16:40:00 | 12044.70 | 11701.73 | 1.068208 | 21.68 | 15.65 | 0.00861879 | 12.80 | 12.09 | 0.00850000 | 31.26 | 0.01411813 | 22.90 | 0.0000 | 21.11 | 0.00861879 | 55.2605 | 10905.09 | 0.00 | 12065.19 | 12065.19 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 5953.660 | 5953.660 | 0.256808 | 0.00005209 | 170.117 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 5953.66 | 5953.66 | 0.256808 | 21.11 | 14.63 | 0.00772369 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.11 | 0.00772369 | 49.5912 | 5953.74 | 0.00 | 6418.22 | 6418.22 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 75085.410 | -999.000 | 6.800645 | 0.00214739 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | unknown | 7/21 13:20:00 | 75085.41 | 74318.45 | 6.800645 | 21.68 | 15.59 | 0.00854183 | 12.80 | 12.09 | 0.00850000 | 31.85 | 0.01411920 | 23.06 | 0.0000 | 21.11 | 0.00854183 | 54.7721 | 69430.48 | 0.00 | 75210.17 | 75210.17 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 33970.377 | 33970.377 | 1.465310 | 0.00029719 | 970.644 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 33970.38 | 33970.38 | 1.465310 | 21.11 | 14.65 | 0.00774248 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.11 | 0.00774248 | 49.7097 | 33970.60 | 0.00 | 36621.18 | 36621.18 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 72473.869 | -999.000 | 6.170370 | 0.00207270 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | unknown | 7/21 15:00:00 | 72473.87 | 67907.72 | 6.170370 | 21.68 | 15.79 | 0.00877253 | 12.80 | 12.09 | 0.00850000 | 32.10 | 0.01411964 | 23.13 | 0.0000 | 21.11 | 0.00877253 | 56.2330 | 62990.92 | 0.00 | 72591.84 | 70942.27 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 34303.283 | 34303.283 | 1.479670 | 0.00030010 | 980.155 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 34303.28 | 34303.28 | 1.479670 | 21.11 | 14.65 | 0.00774482 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.11 | 0.00774482 | 49.7245 | 34303.51 | 0.00 | 36980.06 | 36980.06 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 11426.998 | -999.000 | 1.011493 | 0.00032680 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | unknown | 7/21 09:40:00 | 11427.00 | 11082.88 | 1.011493 | 21.68 | 15.66 | 0.00862585 | 12.80 | 12.09 | 0.00850000 | 28.87 | 0.01411382 | 22.22 | 0.0000 | 21.11 | 0.00862585 | 55.3052 | 10326.08 | 0.00 | 11446.29 | 11446.29 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 5901.266 | 5901.266 | 0.254548 | 0.00005163 | 168.620 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 5901.27 | 5901.27 | 0.254548 | 21.11 | 14.63 | 0.00772132 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.11 | 0.00772132 | 49.5761 | 5901.35 | 0.00 | 6361.74 | 6361.74 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 11129.961 | -999.000 | 0.984253 | 0.00031831 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | unknown | 7/21 09:20:00 | 11129.96 | 10785.62 | 0.984253 | 21.68 | 15.66 | 0.00862940 | 12.80 | 12.09 | 0.00850000 | 28.45 | 0.01411307 | 22.10 | 0.0000 | 21.11 | 0.00862940 | 55.3277 | 10048.00 | 0.00 | 11148.68 | 11148.68 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 5918.564 | 5918.564 | 0.255294 | 0.00005178 | 169.114 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 5918.56 | 5918.56 | 0.255294 | 21.11 | 14.63 | 0.00772212 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.11 | 0.00772212 | 49.5812 | 5918.64 | 0.00 | 6380.38 | 6380.38 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 13876.814 | 13876.814 | 0.817743 | 0.00012140 | 327.486 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 13876.81 | 13876.81 | 0.817743 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00778855 | 50.3436 | 9562.92 | 0.00 | 13950.66 | 13950.66 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 3243.610 | -999.000 | 0.288352 | 0.00009277 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:20:00 | unknown | 7/21 16:20:00 | 3243.61 | 3157.89 | 0.288352 | 21.68 | 15.65 | 0.00861002 | 12.80 | 12.09 | 0.00850000 | 31.46 | 0.01411849 | 22.95 | 0.0000 | 21.11 | 0.00861002 | 55.2050 | 2943.72 | 0.00 | 3249.18 | 3249.18 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 1804.677 | 1804.677 | 0.077844 | 0.00001579 | 51.564 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 1804.68 | 1804.68 | 0.077844 | 21.11 | 14.68 | 0.00777033 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.11 | 0.00777033 | 49.8871 | 1804.69 | 0.00 | 1945.49 | 1945.49 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 3148.821 | -999.000 | 0.279657 | 0.00009005 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | unknown | 7/21 16:40:00 | 3148.82 | 3063.01 | 0.279657 | 21.68 | 15.65 | 0.00861355 | 12.80 | 12.09 | 0.00850000 | 31.26 | 0.01411813 | 22.90 | 0.0000 | 21.11 | 0.00861355 | 55.2274 | 2854.96 | 0.00 | 3154.21 | 3154.21 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 1810.354 | 1810.354 | 0.078088 | 0.00001584 | 51.727 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 1810.35 | 1810.35 | 0.078088 | 21.11 | 14.68 | 0.00777104 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.11 | 0.00777104 | 49.8916 | 1810.36 | 0.00 | 1951.61 | 1951.61 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 15499.349 | -999.000 | 1.356790 | 0.00044327 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | unknown | 7/21 13:20:00 | 15499.35 | 14885.13 | 1.356790 | 21.68 | 15.70 | 0.00866725 | 12.80 | 12.09 | 0.00850000 | 31.85 | 0.01411920 | 23.06 | 0.0000 | 21.11 | 0.00866725 | 55.5675 | 13850.89 | 0.00 | 15524.38 | 15524.38 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 8606.173 | 8606.173 | 0.371224 | 0.00007529 | 245.901 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 8606.17 | 8606.17 | 0.371224 | 21.11 | 14.68 | 0.00777797 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.11 | 0.00777797 | 49.9351 | 8606.26 | 0.00 | 9277.72 | 9277.72 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 12018.884 | 12018.884 | 1.145530 | 0.00010515 | 264.221 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 12018.88 | 12018.88 | 1.145530 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00782807 | 50.5961 | 5975.45 | 0.00 | 12084.46 | 12084.46 |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 12443.193 | 12443.193 | 1.200333 | 0.00010886 | 273.189 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 12443.19 | 12443.19 | 1.200333 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00783177 | 50.6198 | 6110.64 | 0.00 | 12511.12 | 12511.12 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 8247.633 | 8247.633 | 1.198741 | 0.00007215 | 174.745 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 8247.63 | 8247.63 | 1.198741 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00662114 | 42.8845 | 1941.34 | 0.00 | 8293.73 | 8293.73 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 8406.084 | 8406.084 | 0.409808 | 0.00007354 | 206.787 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 8406.08 | 8406.08 | 0.409808 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00785521 | 50.7693 | 6243.96 | 0.00 | 8449.64 | 8449.64 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 86334.709 | -999.000 | 2.051317 | 0.00246916 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 86334.71 | 51162.86 | 2.051317 | 32.10 | 23.13 | 0.01411964 | 11.94 | 11.74 | 0.00850000 | 32.10 | 0.01411964 | 23.13 | 99.9965 | 21.11 | 0.00865334 | 55.4784 | 184023.70 | 0.00 | 86440.35 | 51650.49 |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | FLR_3_DOAS | 20393.415 | 20393.415 | 0.615395 | 0.00017841 | 336.601 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 20393.42 | 20393.42 | 0.615395 | -10.70 | -10.70 | 0.00150390 | 16.70 | 13.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 333.3216 | 21.11 | 0.00774379 | 49.7180 | 104205.62 | 0.00 | 17473.63 | 17473.63 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 702620.510 | -999.000 | 21.814966 | 0.02009486 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 702620.51 | 459113.38 | 21.814966 | 28.33 | 20.61 | 0.01204821 | 10.99 | 10.99 | 0.00850000 | 32.10 | 0.01411964 | 23.13 | 53.4562 | 23.99 | 0.00962472 | 51.7169 | 299616.09 | 0.00 | 703464.92 | 456313.39 |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV WITH REHEAT | 216876.087 | 216876.087 | 6.544490 | 0.00189733 | 3579.622 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | 216876.09 | 216876.09 | 6.544490 | -10.70 | -10.70 | 0.00150390 | 16.70 | 13.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 178.1875 | 21.08 | 0.00656330 | 42.3011 | 60269.55 | 0.00 | 185825.29 | 185825.29 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:32
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | Yes | Yes | No | 6957.023 | 6957.023 | 1.318248 | 0.00006086 | 145.077 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.05745273 | 54.44 | 82.22 | 27.78 | 473174.03 | 1.4703 | 1.499879 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 6957.02 | 6957.02 | 1.0000 | 1.58663727 | 1.318248 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.06085687 | 60.00 | 32.22 | 27.78 | 0.000 | 6957.02 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | 6996.12 | 6996.12 | 1.58663727 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 20.92 | 14.82 | 0.00800000 | 41344.1 | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3686.240 | 3686.240 | 0.191787 | 0.00003225 | 89.293 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.05745273 | 54.44 | 82.22 | 27.78 | 473174.03 | 0.7790 | 0.794724 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 3686.24 | 3686.24 | 1.0000 | 0.23083443 | 0.191787 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.03224555 | 60.00 | 32.22 | 27.78 | 0.000 | 3686.24 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00773310 | 21.00 | 0.00773310 | 49.9904 | 2674.66 | 0.00 | 3705.45 | 3705.45 | 0.23083443 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 32.34 | 18.81 | 0.00800000 | 52987.1 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1535.404 | 1535.404 | 0.121241 | 0.00001343 | 34.542 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.05745273 | 54.44 | 82.22 | 27.78 | 473174.03 | 0.3245 | 0.331021 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 1535.40 | 1535.40 | 1.0000 | 0.14592520 | 0.121241 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.01343101 | 60.00 | 32.22 | 27.78 | 0.000 | 1535.40 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00769428 | 21.00 | 0.00769428 | 49.7419 | 895.93 | 0.00 | 1543.70 | 1543.70 | 0.14592520 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 26.97 | 17.01 | 0.00800000 | 47513.5 | |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2129.940 | 2129.940 | 0.099021 | 0.00001863 | 53.035 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.05745273 | 54.44 | 82.22 | 27.78 | 473174.03 | 0.4501 | 0.459198 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 2129.94 | 2129.94 | 1.0000 | 0.11918176 | 0.099021 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.01863174 | 60.00 | 32.22 | 27.78 | 0.000 | 2129.94 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00760323 | 21.00 | 0.00760323 | 49.1604 | 1607.75 | 0.00 | 2140.93 | 2140.93 | 0.11918176 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 34.22 | 19.41 | 0.00800000 | 54898.3 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1429.721 | 1429.721 | 0.059028 | 0.00001251 | 36.824 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.05745273 | 54.44 | 82.22 | 27.78 | 473174.03 | 0.3022 | 0.308236 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 1429.72 | 1429.72 | 1.0000 | 0.07104571 | 0.059028 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.01250655 | 60.00 | 32.22 | 27.78 | 0.000 | 1429.72 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00766750 | 21.00 | 0.00766750 | 49.5709 | 1118.40 | 0.00 | 1436.94 | 1436.94 | 0.07104571 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 36.43 | 20.10 | 0.00800000 | 57160.3 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11241.136 | 11241.136 | 1.730313 | 0.00009834 | 237.258 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.05745273 | 54.44 | 82.22 | 27.78 | 473174.03 | 2.3757 | 2.423499 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 11241.14 | 11241.14 | 1.0000 | 2.08259581 | 1.730313 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.09833233 | 60.00 | 32.22 | 27.78 | 0.000 | 11241.14 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00758961 | 21.00 | 0.00758961 | 49.0741 | 2117.03 | 0.00 | 11304.05 | 11304.05 | 2.08259581 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.92 | 15.20 | 0.00800000 | 42362.6 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11034.076 | 11034.076 | 0.804586 | 0.00009653 | 251.082 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.05745273 | 54.44 | 82.22 | 27.78 | 473174.03 | 2.3319 | 2.378859 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 11034.08 | 11034.08 | 1.0000 | 0.96839602 | 0.804586 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.09652106 | 60.00 | 32.22 | 27.78 | 0.000 | 11034.08 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00776635 | 21.00 | 0.00776635 | 50.2025 | 6789.96 | 0.00 | 11093.48 | 11093.48 | 0.96839602 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 27.83 | 17.30 | 0.00800000 | 48390.2 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 29358.708 | 29358.708 | 2.572971 | 0.00025684 | 651.693 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.05745273 | 54.44 | 82.22 | 27.78 | 473174.03 | 6.2046 | 6.329503 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 29358.71 | 29358.71 | 1.0000 | 3.09681476 | 2.572971 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.25681658 | 60.00 | 32.22 | 27.78 | 0.000 | 29358.71 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00771516 | 21.00 | 0.00771516 | 49.8752 | 15787.34 | 0.00 | 29518.25 | 29518.25 | 3.09681476 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 25.95 | 16.65 | 0.00800000 | 46466.5 | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12381.929 | -999.000 | 1.099121 | 0.00035411 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8556 | 1004.8586 | 1.2036 | ROOM_1_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.099121 | 1.32289701 | 4197.9300 | 999.8980 | 28.75097406 | 15.03 | 6.70 | 8.33 | 1005385.82 | 1.2316 | 1.231537 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | unknown | unknown | unknown | 7/21 16:30:00 | Sensible | 12381.93 | 12039.09 | 1.0000 | 1.32289701 | 1.099121 | 21.68 | 15.65 | 0.00861542 | 43681.9 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.35407885 | 6.70 | 15.03 | 8.33 | 0.000 | 12381.93 | 31.36 | 0.01411830 | 22.93 | 0.00000000 | 0.0000 | 21.11 | 0.00861542 | 21.11 | 0.00861542 | 55.2392 | 11220.68 | 0.00 | 12403.08 | 12403.08 | 1.32289701 | 21.68 | 15.66 | 0.00861542 | 43681.9 | 12.50 | 12.09 | 0.00861542 | 34306.2 | |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5936.375 | 5936.375 | 0.256062 | 0.00005193 | 169.623 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_1_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.099121 | 1.32289701 | 4197.9300 | 999.8980 | 4.05745273 | 54.44 | 82.22 | 27.78 | 473174.03 | 1.2546 | 1.279835 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 5936.38 | 5936.38 | 1.0000 | 0.30819511 | 0.256062 | 21.11 | 14.63 | 0.00772290 | 40830.3 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.05192870 | 60.00 | 32.22 | 27.78 | 0.000 | 5936.38 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.11 | 0.00772290 | 21.11 | 0.00772290 | 49.5861 | 5936.46 | 0.00 | 6399.58 | 6399.58 | 0.30819511 | 16.60 | 12.88 | 0.00772290 | 36233.2 | 36.97 | 20.06 | 0.00772290 | 56997.9 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12044.698 | -999.000 | 1.068208 | 0.00034447 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8619 | 1004.8586 | 1.2036 | ROOM_2_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.068208 | 1.28569035 | 4197.9300 | 999.8980 | 28.75097406 | 15.03 | 6.70 | 8.33 | 1005385.82 | 1.1980 | 1.197995 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | unknown | unknown | unknown | 7/21 16:40:00 | Sensible | 12044.70 | 11701.73 | 1.0000 | 1.28569035 | 1.068208 | 21.68 | 15.65 | 0.00861879 | 43690.5 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.34443527 | 6.70 | 15.03 | 8.33 | 0.000 | 12044.70 | 31.26 | 0.01411813 | 22.90 | 0.00000000 | 0.0000 | 21.11 | 0.00861879 | 21.11 | 0.00861879 | 55.2605 | 10905.09 | 0.00 | 12065.19 | 12065.19 | 1.28569035 | 21.68 | 15.66 | 0.00861879 | 43690.5 | 12.49 | 12.09 | 0.00861879 | 34306.3 | |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5953.660 | 5953.660 | 0.256808 | 0.00005209 | 170.117 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_2_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.068208 | 1.28569035 | 4197.9300 | 999.8980 | 4.05745273 | 54.44 | 82.22 | 27.78 | 473174.03 | 1.2582 | 1.283561 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 5953.66 | 5953.66 | 1.0000 | 0.30909244 | 0.256808 | 21.11 | 14.63 | 0.00772369 | 40832.4 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.05207990 | 60.00 | 32.22 | 27.78 | 0.000 | 5953.66 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.11 | 0.00772369 | 21.11 | 0.00772369 | 49.5912 | 5953.74 | 0.00 | 6418.22 | 6418.22 | 0.30909244 | 16.60 | 12.88 | 0.00772369 | 36235.2 | 36.97 | 20.06 | 0.00772369 | 56999.9 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 75085.410 | -999.000 | 6.800645 | 0.00214739 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7188 | 1004.8586 | 1.2036 | ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 6.800645 | 8.18522179 | 4197.9300 | 999.8980 | 28.75097406 | 15.03 | 6.70 | 8.33 | 1005385.82 | 7.4683 | 7.468179 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | unknown | unknown | unknown | 7/21 13:20:00 | Sensible | 75085.41 | 74318.45 | 1.0000 | 8.18522179 | 6.800645 | 21.68 | 15.59 | 0.00854183 | 43495.5 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 2.14717408 | 6.70 | 15.03 | 8.33 | 0.000 | 75085.41 | 31.85 | 0.01411920 | 23.06 | 0.00000000 | 0.0000 | 21.11 | 0.00854183 | 21.11 | 0.00854183 | 54.7721 | 69430.48 | 0.00 | 75210.17 | 75210.17 | 8.18522179 | 21.68 | 15.59 | 0.00854183 | 43495.5 | 12.68 | 12.09 | 0.00854183 | 34307.0 | |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 33970.377 | 33970.377 | 1.465310 | 0.00029719 | 970.644 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 6.800645 | 8.18522179 | 4197.9300 | 999.8980 | 4.05745273 | 54.44 | 82.22 | 27.78 | 473174.03 | 7.1793 | 7.323742 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 33970.38 | 33970.38 | 1.0000 | 1.76363932 | 1.465310 | 21.11 | 14.65 | 0.00774248 | 40880.3 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.29715736 | 60.00 | 32.22 | 27.78 | 0.000 | 33970.38 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.11 | 0.00774248 | 21.11 | 0.00774248 | 49.7097 | 33970.60 | 0.00 | 36621.18 | 36621.18 | 1.76363932 | 16.60 | 12.90 | 0.00774248 | 36282.7 | 36.97 | 20.08 | 0.00774248 | 57047.3 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 72473.869 | -999.000 | 6.170370 | 0.00207270 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1477 | 1004.8586 | 1.2036 | ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 6.170370 | 7.42662678 | 4197.9300 | 999.8980 | 28.75097406 | 15.03 | 6.70 | 8.33 | 1005385.82 | 7.2086 | 7.208428 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | unknown | unknown | unknown | 7/21 15:00:00 | Sensible | 72473.87 | 67907.72 | 1.0000 | 7.42662678 | 6.170370 | 21.68 | 15.79 | 0.00877253 | 44080.8 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 2.07249333 | 6.70 | 15.03 | 8.33 | 0.000 | 72473.87 | 32.10 | 0.01411964 | 23.13 | 0.00000000 | 0.0000 | 21.11 | 0.00877253 | 21.11 | 0.00877253 | 56.2330 | 62990.92 | 0.00 | 72591.84 | 70942.27 | 7.42662678 | 21.68 | 15.79 | 0.00877253 | 44080.8 | 12.33 | 12.09 | 0.00868452 | 34306.3 | |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 34303.283 | 34303.283 | 1.479670 | 0.00030010 | 980.155 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 6.170370 | 7.42662678 | 4197.9300 | 999.8980 | 4.05745273 | 54.44 | 82.22 | 27.78 | 473174.03 | 7.2496 | 7.395514 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 34303.28 | 34303.28 | 1.0000 | 1.78092280 | 1.479670 | 21.11 | 14.65 | 0.00774482 | 40886.2 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.30006947 | 60.00 | 32.22 | 27.78 | 0.000 | 34303.28 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.11 | 0.00774482 | 21.11 | 0.00774482 | 49.7245 | 34303.51 | 0.00 | 36980.06 | 36980.06 | 1.78092280 | 16.60 | 12.90 | 0.00774482 | 36288.7 | 36.97 | 20.08 | 0.00774482 | 57053.2 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11426.998 | -999.000 | 1.011493 | 0.00032680 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8750 | 1004.8586 | 1.2036 | ROOM_5_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.011493 | 1.21742753 | 4197.9300 | 999.8980 | 28.75097406 | 15.03 | 6.70 | 8.33 | 1005385.82 | 1.1366 | 1.136557 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | unknown | unknown | unknown | 7/21 09:40:00 | Sensible | 11427.00 | 11082.88 | 1.0000 | 1.21742753 | 1.011493 | 21.68 | 15.66 | 0.00862585 | 43708.4 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.32677126 | 6.70 | 15.03 | 8.33 | 0.000 | 11427.00 | 28.87 | 0.01411382 | 22.22 | 0.00000000 | 0.0000 | 21.11 | 0.00862585 | 21.11 | 0.00862585 | 55.3052 | 10326.08 | 0.00 | 11446.29 | 11446.29 | 1.21742753 | 21.68 | 15.67 | 0.00862585 | 43708.4 | 12.47 | 12.09 | 0.00862585 | 34306.3 | |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5901.266 | 5901.266 | 0.254548 | 0.00005163 | 168.620 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_5_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.011493 | 1.21742753 | 4197.9300 | 999.8980 | 4.05745273 | 54.44 | 82.22 | 27.78 | 473174.03 | 1.2472 | 1.272266 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 5901.27 | 5901.27 | 1.0000 | 0.30637236 | 0.254548 | 21.11 | 14.63 | 0.00772132 | 40826.3 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.05162159 | 60.00 | 32.22 | 27.78 | 0.000 | 5901.27 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.11 | 0.00772132 | 21.11 | 0.00772132 | 49.5761 | 5901.35 | 0.00 | 6361.74 | 6361.74 | 0.30637236 | 16.60 | 12.88 | 0.00772132 | 36229.2 | 36.97 | 20.06 | 0.00772132 | 56993.9 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11129.961 | -999.000 | 0.984253 | 0.00031831 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8816 | 1004.8586 | 1.2036 | ROOM_6_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.984253 | 1.18464226 | 4197.9300 | 999.8980 | 28.75097406 | 15.03 | 6.70 | 8.33 | 1005385.82 | 1.1070 | 1.107013 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | unknown | unknown | unknown | 7/21 09:20:00 | Sensible | 11129.96 | 10785.62 | 1.0000 | 1.18464226 | 0.984253 | 21.68 | 15.66 | 0.00862940 | 43717.4 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.31827707 | 6.70 | 15.03 | 8.33 | 0.000 | 11129.96 | 28.45 | 0.01411307 | 22.10 | 0.00000000 | 0.0000 | 21.11 | 0.00862940 | 21.11 | 0.00862940 | 55.3277 | 10048.00 | 0.00 | 11148.68 | 11148.68 | 1.18464226 | 21.68 | 15.67 | 0.00862940 | 43717.4 | 12.46 | 12.09 | 0.00862940 | 34306.4 | |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5918.564 | 5918.564 | 0.255294 | 0.00005178 | 169.114 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_6_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.984253 | 1.18464226 | 4197.9300 | 999.8980 | 4.05745273 | 54.44 | 82.22 | 27.78 | 473174.03 | 1.2508 | 1.275995 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 5918.56 | 5918.56 | 1.0000 | 0.30727038 | 0.255294 | 21.11 | 14.63 | 0.00772212 | 40828.4 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.05177289 | 60.00 | 32.22 | 27.78 | 0.000 | 5918.56 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.11 | 0.00772212 | 21.11 | 0.00772212 | 49.5812 | 5918.64 | 0.00 | 6380.38 | 6380.38 | 0.30727038 | 16.60 | 12.88 | 0.00772212 | 36231.2 | 36.97 | 20.06 | 0.00772212 | 56995.9 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13876.814 | 13876.814 | 0.817743 | 0.00012140 | 327.486 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.05745273 | 54.44 | 82.22 | 27.78 | 473174.03 | 2.9327 | 2.991730 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 13876.81 | 13876.81 | 1.0000 | 0.98423103 | 0.817743 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.12138804 | 60.00 | 32.22 | 27.78 | 0.000 | 13876.81 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00778855 | 21.00 | 0.00778855 | 50.3436 | 9562.92 | 0.00 | 13950.66 | 13950.66 | 0.98423103 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 30.50 | 18.20 | 0.00800000 | 51108.9 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3243.610 | -999.000 | 0.288352 | 0.00009277 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8456 | 1004.8586 | 1.2036 | ROOM_1_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.288352 | 0.34705909 | 4197.9300 | 999.8980 | 28.75097406 | 15.03 | 6.70 | 8.33 | 1005385.82 | 0.3226 | 0.322617 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:20:00 | unknown | unknown | unknown | 7/21 16:20:00 | Sensible | 3243.61 | 3157.89 | 1.0000 | 0.34705909 | 0.288352 | 21.68 | 15.65 | 0.00861002 | 43668.2 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.09275564 | 6.70 | 15.03 | 8.33 | 0.000 | 3243.61 | 31.46 | 0.01411849 | 22.95 | 0.00000000 | 0.0000 | 21.11 | 0.00861002 | 21.11 | 0.00861002 | 55.2050 | 2943.72 | 0.00 | 3249.18 | 3249.18 | 0.34705909 | 21.68 | 15.65 | 0.00861002 | 43668.2 | 12.51 | 12.09 | 0.00861002 | 34306.1 | |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1804.677 | 1804.677 | 0.077844 | 0.00001579 | 51.564 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_1_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.288352 | 0.34705909 | 4197.9300 | 999.8980 | 4.05745273 | 54.44 | 82.22 | 27.78 | 473174.03 | 0.3814 | 0.389074 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 1804.68 | 1804.68 | 1.0000 | 0.09369208 | 0.077844 | 21.11 | 14.68 | 0.00777033 | 40950.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.01578649 | 60.00 | 32.22 | 27.78 | 0.000 | 1804.68 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.11 | 0.00777033 | 21.11 | 0.00777033 | 49.8871 | 1804.69 | 0.00 | 1945.49 | 1945.49 | 0.09369208 | 16.60 | 12.93 | 0.00777033 | 36353.3 | 36.97 | 20.10 | 0.00777033 | 57118.0 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3148.821 | -999.000 | 0.279657 | 0.00009005 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8522 | 1004.8586 | 1.2036 | ROOM_2_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.279657 | 0.33659386 | 4197.9300 | 999.8980 | 28.75097406 | 15.03 | 6.70 | 8.33 | 1005385.82 | 0.3132 | 0.313189 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | unknown | unknown | unknown | 7/21 16:40:00 | Sensible | 3148.82 | 3063.01 | 1.0000 | 0.33659386 | 0.279657 | 21.68 | 15.65 | 0.00861355 | 43677.2 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.09004500 | 6.70 | 15.03 | 8.33 | 0.000 | 3148.82 | 31.26 | 0.01411813 | 22.90 | 0.00000000 | 0.0000 | 21.11 | 0.00861355 | 21.11 | 0.00861355 | 55.2274 | 2854.96 | 0.00 | 3154.21 | 3154.21 | 0.33659386 | 21.68 | 15.65 | 0.00861355 | 43677.2 | 12.50 | 12.09 | 0.00861355 | 34306.2 | |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1810.354 | 1810.354 | 0.078088 | 0.00001584 | 51.727 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_2_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.279657 | 0.33659386 | 4197.9300 | 999.8980 | 4.05745273 | 54.44 | 82.22 | 27.78 | 473174.03 | 0.3826 | 0.390298 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 1810.35 | 1810.35 | 1.0000 | 0.09398677 | 0.078088 | 21.11 | 14.68 | 0.00777104 | 40952.6 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.01583615 | 60.00 | 32.22 | 27.78 | 0.000 | 1810.35 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.11 | 0.00777104 | 21.11 | 0.00777104 | 49.8916 | 1810.36 | 0.00 | 1951.61 | 1951.61 | 0.09398677 | 16.60 | 12.93 | 0.00777104 | 36355.1 | 36.97 | 20.10 | 0.00777104 | 57119.8 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15499.349 | -999.000 | 1.356790 | 0.00044327 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9520 | 1004.8586 | 1.2036 | ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 1.356790 | 1.63302518 | 4197.9300 | 999.8980 | 28.75097406 | 15.03 | 6.70 | 8.33 | 1005385.82 | 1.5416 | 1.541603 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | unknown | unknown | unknown | 7/21 13:20:00 | Sensible | 15499.35 | 14885.13 | 1.0000 | 1.63302518 | 1.356790 | 21.68 | 15.70 | 0.00866725 | 43813.4 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.44322593 | 6.70 | 15.03 | 8.33 | 0.000 | 15499.35 | 31.85 | 0.01411920 | 23.06 | 0.00000000 | 0.0000 | 21.11 | 0.00866725 | 21.11 | 0.00866725 | 55.5675 | 13850.89 | 0.00 | 15524.38 | 15524.38 | 1.63302518 | 21.68 | 15.70 | 0.00866725 | 43813.4 | 12.37 | 12.09 | 0.00866725 | 34306.9 | |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8606.173 | 8606.173 | 0.371224 | 0.00007529 | 245.901 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 1.356790 | 1.63302518 | 4197.9300 | 999.8980 | 4.05745273 | 54.44 | 82.22 | 27.78 | 473174.03 | 1.8188 | 1.855422 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 8606.17 | 8606.17 | 1.0000 | 0.44680319 | 0.371224 | 21.11 | 14.68 | 0.00777797 | 40970.3 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.07528287 | 60.00 | 32.22 | 27.78 | 0.000 | 8606.17 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.11 | 0.00777797 | 21.11 | 0.00777797 | 49.9351 | 8606.26 | 0.00 | 9277.72 | 9277.72 | 0.44680319 | 16.60 | 12.93 | 0.00777797 | 36372.6 | 36.97 | 20.10 | 0.00777797 | 57137.2 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12018.884 | 12018.884 | 1.145530 | 0.00010515 | 264.221 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.05745273 | 54.44 | 82.22 | 27.78 | 473174.03 | 2.5401 | 2.591175 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 12018.88 | 12018.88 | 1.0000 | 1.37875385 | 1.145530 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.10513571 | 60.00 | 32.22 | 27.78 | 0.000 | 12018.88 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00782807 | 21.00 | 0.00782807 | 50.5961 | 5975.45 | 0.00 | 12084.46 | 12084.46 | 1.37875385 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 25.20 | 16.38 | 0.00800000 | 45699.5 | |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12443.193 | 12443.193 | 1.200333 | 0.00010886 | 273.189 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.05745273 | 54.44 | 82.22 | 27.78 | 473174.03 | 2.6297 | 2.682653 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | Sensible | 12443.19 | 12443.19 | 1.0000 | 1.44471448 | 1.200333 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.10884738 | 60.00 | 32.22 | 27.78 | 0.000 | 12443.19 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00783177 | 21.00 | 0.00783177 | 50.6198 | 6110.64 | 0.00 | 12511.12 | 12511.12 | 1.44471448 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 25.09 | 16.35 | 0.00800000 | 45594.7 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8247.633 | 8247.633 | 1.198741 | 0.00007215 | 174.745 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.05745273 | 54.44 | 82.22 | 27.78 | 473174.03 | 1.7430 | 1.778124 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | Sensible | 8247.63 | 8247.63 | 1.0000 | 1.44279896 | 1.198741 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.07214653 | 60.00 | 32.22 | 27.78 | 0.000 | 8247.63 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.47 | 0.00662114 | 21.00 | 0.00662114 | 42.8845 | 1941.34 | 0.00 | 8293.73 | 8293.73 | 1.44279896 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 22.24 | 15.31 | 0.00800000 | 42683.1 | |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8406.084 | 8406.084 | 0.409808 | 0.00007354 | 206.787 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.05745273 | 54.44 | 82.22 | 27.78 | 473174.03 | 1.7765 | 1.812285 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | Sensible | 8406.08 | 8406.08 | 1.0000 | 0.49324329 | 0.409808 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.07353259 | 60.00 | 32.22 | 27.78 | 0.000 | 8406.08 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00785521 | 21.00 | 0.00785521 | 50.7693 | 6243.96 | 0.00 | 8449.64 | 8449.64 | 0.49324329 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 33.40 | 19.15 | 0.00800000 | 54065.5 | |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 86334.709 | -999.000 | 2.051317 | 0.00246916 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1031.0877 | 1004.8586 | 1.2036 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.46886833 | 4197.9300 | 999.8980 | 28.75097406 | 15.03 | 6.70 | 8.33 | 1005385.82 | 8.5872 | 8.587222 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | Sensible | 86334.71 | 51162.86 | 1.0000 | 2.46895513 | 2.051317 | 32.10 | 23.13 | 0.01411964 | 68410.3 | 11.94 | 11.74 | 0.00850000 | 33442.2 | 2.46890985 | 6.70 | 15.03 | 8.33 | 2195.006 | 84139.70 | 32.10 | 0.01411964 | 23.13 | 2.05124512 | 99.9965 | 21.11 | 0.00865308 | 21.11 | 0.00865334 | 55.4784 | 184023.70 | 0.00 | 86440.35 | 51650.49 | 2.46895513 | 32.10 | 23.14 | 0.01411964 | 68410.3 | 11.81 | 11.72 | 0.00853442 | 33399.4 | |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 20393.415 | 20393.415 | 0.615395 | 0.00017841 | 336.601 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.46886833 | 4197.9300 | 999.8980 | 4.05745273 | 54.44 | 82.22 | 27.78 | 473174.03 | 4.3099 | 4.396657 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 20393.42 | 20393.42 | 1.0000 | 0.74068654 | 0.615395 | -10.70 | -10.70 | 0.00150390 | -7020.5 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 0.17839229 | 60.00 | 32.22 | 27.78 | 0.000 | 20393.42 | -10.70 | 0.00150390 | -10.70 | 2.05124512 | 333.3216 | 21.11 | 0.00774262 | 21.11 | 0.00774379 | 49.7180 | 104205.62 | 0.00 | 17473.63 | 17473.63 | 0.74068654 | 2.80 | -1.97 | 0.00150390 | 6582.5 | 26.21 | 10.51 | 0.00150390 | 30173.7 | |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 702620.510 | -999.000 | 21.814966 | 0.02009486 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1027.2370 | 1004.8586 | 1.2036 | VAV WITH REHEAT FAN | Fan:VariableVolume | 21.814966 | 26.25638319 | 4197.9300 | 999.8980 | 28.75097406 | 15.03 | 6.70 | 8.33 | 1005385.82 | 69.8857 | 69.885659 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | Sensible | 702620.51 | 459113.38 | 1.0000 | 26.25638319 | 21.814966 | 28.33 | 20.61 | 0.01204821 | 59232.5 | 10.99 | 10.99 | 0.00850000 | 32472.5 | 20.09280777 | 6.70 | 15.03 | 8.33 | 48879.454 | 653741.06 | 32.10 | 0.01411964 | 23.13 | 11.66146000 | 53.4562 | 23.99 | 0.00966417 | 23.99 | 0.00962472 | 51.7169 | 299616.09 | 0.00 | 703464.92 | 456313.39 | 26.25638319 | 28.33 | 20.62 | 0.01204821 | 59232.5 | 11.41 | 11.33 | 0.00831608 | 32440.4 | |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 216876.087 | 216876.087 | 6.544490 | 0.00189733 | 3579.622 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | VAV WITH REHEAT FAN | Fan:VariableVolume | 21.814966 | 26.25638319 | 4197.9300 | 999.8980 | 4.05745273 | 54.44 | 82.22 | 27.78 | 473174.03 | 45.8343 | 46.756751 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | Sensible | 216876.09 | 216876.09 | 1.0000 | 7.87691496 | 6.544490 | -10.70 | -10.70 | 0.00150390 | -7020.5 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 1.89713307 | 60.00 | 32.22 | 27.78 | 0.000 | 216876.09 | -10.70 | 0.00150390 | -10.70 | 11.66146000 | 178.1875 | 18.53 | 0.00698592 | 21.08 | 0.00656330 | 42.3011 | 60269.55 | 0.00 | 185825.29 | 185825.29 | 7.87691496 | 2.80 | -1.97 | 0.00150390 | 6582.5 | 26.21 | 10.51 | 0.00150390 | 30173.7 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:32
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - | |||
VAV WITH REHEAT_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 21.81 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | VAV WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000610 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LAUNDRY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CAFE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001448 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_3 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
KITCHEN_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003556 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 601.17 | 6887.83 | 0.00 |
RETAIL_1_FLR_1 | 2495.50 | 6680.67 | 1193.17 |
RETAIL_2_FLR_1 | 1695.00 | 6273.67 | 176.50 |
MECH_FLR_1 | 1273.17 | 7173.50 | 796.50 |
STORAGE_FLR_1 | 1127.83 | 7742.17 | 1002.67 |
LAUNDRY_FLR_1 | 6817.00 | 3336.17 | 2570.67 |
CAFE_FLR_1 | 3318.83 | 5824.83 | 1144.00 |
LOBBY_FLR_1 | 2471.50 | 6113.00 | 888.67 |
ROOM_1_FLR_3 | 1741.50 | 8182.83 | 1670.67 |
ROOM_2_FLR_3 | 2858.50 | 7891.50 | 2540.50 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 1251.67 | 8687.17 | 1234.83 |
ROOM_5_FLR_3 | 1655.00 | 8141.83 | 1646.50 |
ROOM_6_FLR_3 | 2698.67 | 7947.50 | 2471.67 |
CORRIDOR_FLR_3 | 642.83 | 8113.83 | 630.17 |
ROOM_1_FLR_6 | 2455.50 | 8077.50 | 2285.50 |
ROOM_2_FLR_6 | 3540.00 | 7798.33 | 3135.50 |
ROOM_3_MULT9_FLR_6 | 1138.33 | 8073.33 | 1059.50 |
BANQUET_FLR_6 | 4286.00 | 3473.50 | 882.00 |
DINING_FLR_6 | 4985.00 | 2418.83 | 787.33 |
KITCHEN_FLR_6 | 8179.17 | 6431.83 | 6247.17 |
CORRIDOR_FLR_6 | 1762.33 | 6811.17 | 704.17 |
Facility | 8736.83 | 8760.00 | 7927.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.50 | 0.00 | 0.50 |
CAFE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 3.83 | 8.17 | 3.83 | 8.17 |
ROOM_2_FLR_3 | 8.50 | 14.67 | 8.50 | 14.67 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 2.50 | 22.50 | 2.50 | 22.50 |
ROOM_5_FLR_3 | 4.50 | 0.83 | 4.50 | 0.83 |
ROOM_6_FLR_3 | 10.83 | 24.33 | 10.83 | 24.33 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 3.00 | 12.50 | 3.00 | 12.50 |
ROOM_2_FLR_6 | 6.83 | 21.83 | 6.83 | 21.83 |
ROOM_3_MULT9_FLR_6 | 1.17 | 7.67 | 1.17 | 7.67 |
BANQUET_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 10.83 | 0.00 | 10.83 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 14.00 | 66.33 | 14.00 | 66.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:32
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.77 | 106.50 | 4826.41 | 1.011 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 2.654 | 0.062 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 1.446 | 0.021 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.551 | 0.023 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.567 | 0.023 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 23.200 | 0.066 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.53 | 142.30 | 748.35 | 3.985 | 0.049 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.01 | 422.44 | 5183.56 | 1.842 | 0.020 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.354 | 0.080 | 0.000 | 0.065 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.355 | 0.080 | 0.000 | 0.061 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.403 | 0.036 | 0.000 | 0.104 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.354 | 0.080 | 0.000 | 0.065 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.355 | 0.080 | 0.000 | 0.066 |
CORRIDOR_FLR_3 | 12.15 | 20.96 | 1186.91 | 0.622 | 0.010 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.355 | 0.080 | 0.000 | 0.079 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.355 | 0.080 | 0.000 | 0.068 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.403 | 0.065 | 0.000 | 0.126 |
BANQUET_FLR_6 | 144.94 | 249.90 | 1010.89 | 4.794 | 0.023 | 0.000 | 0.000 |
DINING_FLR_6 | 144.94 | 249.90 | 1010.89 | 5.169 | 0.023 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 21.799 | 0.067 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.86 | 22.18 | 1256.16 | 1.184 | 0.016 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.77 | 106.50 | 4826.41 | 0.703 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 1.924 | 0.001 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 1.335 | 0.000 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.513 | 0.000 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.475 | 0.000 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 19.030 | 0.001 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.53 | 142.30 | 748.35 | 3.490 | 0.001 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.01 | 422.44 | 5183.56 | 1.686 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
CORRIDOR_FLR_3 | 12.15 | 20.96 | 1186.91 | 0.433 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.000 | 0.001 | 0.000 | 0.000 |
BANQUET_FLR_6 | 144.94 | 249.90 | 1010.89 | 3.983 | 0.000 | 0.000 | 0.000 |
DINING_FLR_6 | 144.94 | 249.90 | 1010.89 | 4.179 | 0.000 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 13.019 | 0.001 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.86 | 22.18 | 1256.16 | 0.957 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:32
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | VAV WITH REHEAT | 61.77 | 106.50 | 4826.41 | 1978.83 | 0.0000 | 0.854 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 6.28 | 10.83 | 265.76 | 67.07 | 0.0000 | 0.079 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 7.27 | 12.54 | 307.76 | 77.67 | 0.0000 | 0.092 |
MECH_FLR_1 | VAV WITH REHEAT | 1.54 | 2.65 | 650.80 | 164.24 | 0.0000 | 0.000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 1.18 | 2.04 | 375.47 | 94.76 | 0.0000 | 0.058 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 4.87 | 8.40 | 309.22 | 78.04 | 0.0000 | 0.000 |
CAFE_FLR_1 | VAV WITH REHEAT | 82.53 | 142.30 | 748.35 | 188.86 | 0.0000 | 0.676 |
LOBBY_FLR_1 | VAV WITH REHEAT | 245.01 | 422.44 | 5183.56 | 1308.19 | 0.0000 | 1.894 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 1.50 | 74.75 | 24.52 | 0.0000 | 0.837 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.837 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 12.15 | 20.96 | 1186.91 | 389.40 | 0.0000 | 0.475 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.015 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.015 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.099 |
BANQUET_FLR_6 | VAV WITH REHEAT | 144.94 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
DINING_FLR_6 | VAV WITH REHEAT | 144.94 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 12.90 | 22.24 | 314.87 | 103.30 | 0.0000 | 0.367 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 12.86 | 22.18 | 1256.16 | 412.12 | 0.0000 | 0.126 |
Total Facility | 872.97 | 1604.23 | 35184.81 | 11345.29 | 0.0000 | 137.584 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 41995791.74 | 0.00 | 41995791.74 | 0.00 | 41995791.74 | 26946214.98 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_1_FLR_1 | 6095093.56 | 0.00 | 6095093.56 | 141822.98 | 6236916.54 | 2498216.28 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_2_FLR_1 | 3835615.72 | 0.00 | 3835615.72 | 54743.85 | 3890359.57 | 2892943.94 | 0.00 | 0.00 | 8760.00 | 0.00 |
MECH_FLR_1 | 3100744.30 | 0.00 | 3100744.30 | 129381.94 | 3230126.24 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
STORAGE_FLR_1 | 1840554.73 | 0.00 | 1840554.73 | 74646.25 | 1915200.98 | 1821682.01 | 1527.36 | 1357.25 | 5875.39 | 0.00 |
LAUNDRY_FLR_1 | 61817485.69 | 0.00 | 61817485.69 | 176664.43 | 61994150.13 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
CAFE_FLR_1 | 25668403.33 | 0.00 | 25668403.33 | 313507.73 | 25981911.07 | 21330615.53 | 0.00 | 0.00 | 8760.00 | 0.00 |
LOBBY_FLR_1 | 82102560.52 | 0.00 | 82102560.52 | 895763.20 | 82998323.72 | 59728886.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
ROOM_1_FLR_3 | 1460156.71 | 66919.35 | 1527076.06 | 82318.35 | 1609394.41 | 1946875.62 | 2190.00 | 5869.33 | 700.67 | 0.00 |
ROOM_2_FLR_3 | 1459985.63 | 62383.54 | 1522369.18 | 82312.07 | 1604681.24 | 1946647.51 | 2190.00 | 5924.52 | 645.48 | 0.00 |
ROOM_3_MULT19_FLR_3 | 1099911.97 | 0.00 | 1099911.97 | 22967.74 | 1122879.71 | 26397887.27 | 8395.00 | 365.00 | 0.00 | 365.00 |
ROOM_4_MULT19_FLR_3 | 19803829.30 | 66991.41 | 19870820.71 | 22974.02 | 19893794.73 | 26405105.73 | 2190.00 | 5881.48 | 688.52 | 0.00 |
ROOM_5_FLR_3 | 1460156.71 | 66970.66 | 1527127.37 | 82318.35 | 1609445.72 | 1946875.62 | 2190.00 | 5869.33 | 700.67 | 0.00 |
ROOM_6_FLR_3 | 1459985.63 | 66995.31 | 1526980.94 | 82312.07 | 1609293.01 | 1946647.51 | 2190.00 | 5873.08 | 696.92 | 0.00 |
CORRIDOR_FLR_3 | 25494034.97 | 0.00 | 25494034.97 | 99539.44 | 25593574.41 | 14972100.18 | 0.00 | 0.00 | 8760.00 | 0.00 |
ROOM_1_FLR_6 | 365039.18 | 81426.99 | 446466.17 | 82335.52 | 528801.69 | 486718.90 | 2014.33 | 5868.54 | 877.13 | 0.00 |
ROOM_2_FLR_6 | 364996.41 | 69669.45 | 434665.85 | 82329.24 | 516995.10 | 486661.88 | 2045.59 | 5965.33 | 749.08 | 0.00 |
ROOM_3_MULT9_FLR_6 | 2345190.31 | 81407.23 | 2426597.54 | 42125.74 | 2468723.27 | 3126920.42 | 2190.00 | 5867.33 | 702.67 | 0.00 |
BANQUET_FLR_6 | 41544000.53 | 0.00 | 41544000.53 | 201042.65 | 41745043.18 | 37458366.31 | 3900.65 | 501.26 | 4358.09 | 0.00 |
DINING_FLR_6 | 44780605.71 | 0.00 | 44780605.71 | 201042.65 | 44981648.36 | 37458366.31 | 0.06 | 0.00 | 8759.94 | 0.00 |
KITCHEN_FLR_6 | 58865973.68 | 0.00 | 58865973.68 | 179979.79 | 59045953.46 | 11584760.86 | 0.00 | 0.00 | 8760.00 | 0.00 |
CORRIDOR_FLR_6 | 12849672.74 | 0.00 | 12849672.74 | 176154.17 | 13025826.91 | 3961413.96 | 0.00 | 0.00 | 8760.00 | 0.00 |
Total Facility | 0.21E+10 | 7028184.43 | 0.21E+10 | 8295321.24 | 0.21E+10 | 0.43E+10 | 8760.00 | 6644.32 | 8760.00 | 365.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 1.3317 | 0.0000 | 1.3317 | 0.0000 | 1.3317 | 0.8545 | 0.00 | 0.00 | 8760.00 |
RETAIL_1_FLR_1 | 0.1933 | 0.0000 | 0.1933 | 0.0045 | 0.1978 | 0.0792 | 0.00 | 0.00 | 8760.00 |
RETAIL_2_FLR_1 | 0.1216 | 0.0000 | 0.1216 | 0.0017 | 0.1234 | 0.0917 | 0.00 | 0.00 | 8760.00 |
MECH_FLR_1 | 0.0983 | 0.0000 | 0.0983 | 0.0041 | 0.1024 | 0.0000 | 0.00 | 0.00 | 8760.00 |
STORAGE_FLR_1 | 0.0584 | 0.0000 | 0.0584 | 0.0024 | 0.0607 | 0.0578 | 1527.36 | 1357.25 | 5875.39 |
LAUNDRY_FLR_1 | 1.9602 | 0.0000 | 1.9602 | 0.0056 | 1.9658 | 0.0000 | 0.00 | 0.00 | 8760.00 |
CAFE_FLR_1 | 0.8139 | 0.0000 | 0.8139 | 0.0099 | 0.8239 | 0.6764 | 0.00 | 0.00 | 8760.00 |
LOBBY_FLR_1 | 2.6035 | 0.0000 | 2.6035 | 0.0284 | 2.6319 | 1.8940 | 0.00 | 0.00 | 8760.00 |
ROOM_1_FLR_3 | 0.0463 | 0.0021 | 0.0484 | 0.0026 | 0.0510 | 0.0617 | 2190.00 | 5869.33 | 700.67 |
ROOM_2_FLR_3 | 0.0463 | 0.0020 | 0.0483 | 0.0026 | 0.0509 | 0.0617 | 2190.00 | 5924.52 | 645.48 |
ROOM_4_MULT19_FLR_3 | 0.6280 | 0.0021 | 0.6301 | 0.0007 | 0.6308 | 0.8373 | 2190.00 | 5881.48 | 688.52 |
ROOM_5_FLR_3 | 0.0463 | 0.0021 | 0.0484 | 0.0026 | 0.0510 | 0.0617 | 2190.00 | 5869.33 | 700.67 |
ROOM_6_FLR_3 | 0.0463 | 0.0021 | 0.0484 | 0.0026 | 0.0510 | 0.0617 | 2190.00 | 5873.08 | 696.92 |
CORRIDOR_FLR_3 | 0.8084 | 0.0000 | 0.8084 | 0.0032 | 0.8116 | 0.4748 | 0.00 | 0.00 | 8760.00 |
ROOM_1_FLR_6 | 0.0116 | 0.0026 | 0.0142 | 0.0026 | 0.0168 | 0.0154 | 2014.33 | 5868.54 | 877.13 |
ROOM_2_FLR_6 | 0.0116 | 0.0022 | 0.0138 | 0.0026 | 0.0164 | 0.0154 | 2045.59 | 5965.33 | 749.08 |
ROOM_3_MULT9_FLR_6 | 0.0744 | 0.0026 | 0.0769 | 0.0013 | 0.0783 | 0.0992 | 2190.00 | 5867.33 | 702.67 |
BANQUET_FLR_6 | 1.3174 | 0.0000 | 1.3174 | 0.0064 | 1.3237 | 1.1878 | 3900.65 | 501.26 | 4358.09 |
DINING_FLR_6 | 1.4200 | 0.0000 | 1.4200 | 0.0064 | 1.4264 | 1.1878 | 0.06 | 0.00 | 8759.94 |
KITCHEN_FLR_6 | 1.8666 | 0.0000 | 1.8666 | 0.0057 | 1.8723 | 0.3674 | 0.00 | 0.00 | 8760.00 |
CORRIDOR_FLR_6 | 0.4075 | 0.0000 | 0.4075 | 0.0056 | 0.4130 | 0.1256 | 0.00 | 0.00 | 8760.00 |
Total Facility | 64.5853 | 0.2229 | 64.8081 | 0.2077 | 65.0158 | 73.9670 | 8760.00 | 6644.32 | 8760.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
FLR_3_DOAS | 43197387.25 | 562763.93 | 43760151.18 | 64690340.46 | 8699.31 | 32.16 | 28.52 | 0.00 |
VAV WITH REHEAT | 0.59E+09 | 0.00 | 0.59E+09 | 0.22E+09 | 0.00 | 0.00 | 8760.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
FLR_3_DOAS | 1.3698 | 0.0178 | 1.3876 | 2.0513 | 8699.31 | 32.16 | 28.52 |
VAV WITH REHEAT | 18.8333 | 0.0000 | 18.8333 | 6.9969 | 0.00 | 0.00 | 8760.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
FLR_3_DOAS | 0.00 | 0.00 | 0.00 | 0.00 | 6935.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
VAV WITH REHEAT | 0.00 | 0.00 | 3425.07 | 0.00 | 0.00 | 0.00 | 5334.93 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
FLR_3_DOAS | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.7302 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
VAV WITH REHEAT | 0.0000 | 0.0000 | 19.1401 | 0.0000 | 0.0000 | 0.0000 | 18.6398 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:32
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1333 |
Defaulted Fields | 1182 |
Fields with Defaults | 4000 |
Autosized Fields | 349 |
Autosizable Fields | 402 |
Autocalculated Fields | 280 |
Autocalculatable Fields | 539 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:21:32
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 5334.06 | 67272.24 | 06-MAY-05:00 | 413605.13 | 04-AUG-19:10 |
Electricity:Building | 2447.49 | 31112.40 | 03-JUN-05:00 | 151313.73 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 304.40 | 3493.55 | 02-JAN-02:10 | 22822.84 | 02-JAN-20:10 |
Electricity:SpaceType:GENERAL | 2440.40 | 30971.25 | 03-JUN-05:00 | 151072.40 | 02-JAN-20:10 |
InteriorLights:Electricity | 782.22 | 6769.28 | 03-JUN-05:00 | 64632.59 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 161.29 | 1465.65 | 02-JAN-02:10 | 13190.31 | 02-JAN-20:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 782.22 | 6769.28 | 03-JUN-05:00 | 64632.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 782.22 | 6769.28 | 03-JUN-05:00 | 64632.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 161.29 | 1465.65 | 02-JAN-02:10 | 13190.31 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 782.22 | 6769.28 | 03-JUN-05:00 | 64632.59 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 17.49 | 210.74 | 02-JAN-02:10 | 1283.20 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 7.31 | 66.40 | 02-JAN-02:10 | 597.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 7.31 | 66.40 | 02-JAN-02:10 | 597.59 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 20.26 | 244.03 | 02-JAN-02:10 | 1485.95 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 8.46 | 76.89 | 02-JAN-02:10 | 692.02 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 8.46 | 76.89 | 02-JAN-02:10 | 692.02 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 20.84 | 252.75 | 02-JAN-02:10 | 1523.62 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.37 | 76.02 | 02-JAN-02:10 | 684.18 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.37 | 76.02 | 02-JAN-02:10 | 684.18 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 6.68 | 78.96 | 02-JAN-02:10 | 493.99 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 3.08 | 27.98 | 02-JAN-02:10 | 251.84 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 3.08 | 27.98 | 02-JAN-02:10 | 251.84 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 71.91 | 998.82 | 02-JAN-02:10 | 4897.88 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 3.98 | 36.12 | 02-JAN-02:10 | 325.08 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 3.98 | 36.12 | 02-JAN-02:10 | 325.08 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 28.48 | 293.96 | 20-MAY-05:00 | 2666.80 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 14.14 | 83.19 | 01-JAN-13:10 | 1701.53 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 | 14.14 | 83.19 | 01-JAN-13:10 | 1701.53 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 258.96 | 3118.22 | 20-MAY-05:00 | 19534.01 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 109.97 | 1006.80 | 20-MAY-05:00 | 9504.80 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 109.97 | 1006.80 | 20-MAY-05:00 | 9504.80 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 19.72 | 257.38 | 01-JAN-02:10 | 1438.51 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 19.72 | 257.35 | 01-JAN-02:10 | 1438.34 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 305.38 | 4267.82 | 01-JAN-02:10 | 22404.45 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 110.39 | 934.58 | 01-JAN-02:10 | 8496.21 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 110.39 | 934.58 | 01-JAN-02:10 | 8496.21 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 305.47 | 4268.99 | 01-JAN-02:10 | 22410.58 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 110.42 | 934.84 | 01-JAN-02:10 | 8498.53 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 110.42 | 934.84 | 01-JAN-02:10 | 8498.53 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 19.72 | 257.38 | 01-JAN-02:10 | 1438.51 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 19.72 | 257.35 | 01-JAN-02:10 | 1438.34 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 4.93 | 64.34 | 01-JAN-02:10 | 359.63 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 2.31 | 19.57 | 01-JAN-02:10 | 177.88 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 2.31 | 19.57 | 01-JAN-02:10 | 177.88 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 4.93 | 64.34 | 01-JAN-02:10 | 359.59 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 2.31 | 19.56 | 01-JAN-02:10 | 177.86 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 2.31 | 19.56 | 01-JAN-02:10 | 177.86 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 36.17 | 505.54 | 01-JAN-02:10 | 2653.88 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 13.08 | 110.70 | 01-JAN-02:10 | 1006.40 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 13.08 | 110.70 | 01-JAN-02:10 | 1006.40 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 206.70 | 2448.50 | 03-JUN-05:00 | 9735.93 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 30.84 | 199.20 | 03-JUN-05:00 | 2988.03 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 30.84 | 199.20 | 03-JUN-05:00 | 2988.03 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 206.70 | 2448.50 | 03-JUN-05:00 | 9735.93 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 30.84 | 199.20 | 03-JUN-05:00 | 2988.03 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 | 30.84 | 199.20 | 03-JUN-05:00 | 2988.03 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 453.81 | 6249.79 | 02-JAN-02:10 | 18934.39 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 12.97 | 117.87 | 02-JAN-02:10 | 1060.81 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 12.97 | 117.87 | 02-JAN-02:10 | 1060.81 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1658.18 | 24201.97 | 02-JAN-02:10 | 89171.45 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 1658.18 | 24201.97 | 02-JAN-02:10 | 89171.45 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 433.74 | 5990.78 | 01-JAN-00:10 | 16487.34 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 410.33 | 5248.28 | 01-JAN-00:10 | 15744.84 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
Refrigeration:Electricity | 61.97 | 1114.61 | 15-MAR-22:30 | 3264.12 | 10-NOV-07:30 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
Electricity:Plant | 1170.25 | 2714.84 | 13-APR-02:10 | 202323.56 | 04-AUG-18:30 |
LowTempRefrigeration:Refrigeration:Electricity | 20.45 | 0.00 | 01-JAN-11:10 | 1903.58 | 23-AUG-10:50 |
MedTempRefrigeration:Refrigeration:Electricity | 34.43 | 943.07 | 06-FEB-04:10 | 1204.04 | 18-MAY-13:10 |
Fans:Electricity | 525.45 | 11954.90 | 14-JAN-08:10 | 35380.68 | 05-SEP-22:00 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 730.59 | 12857.72 | 18-JAN-15:00 | 46153.14 | 05-SEP-22:00 |
ExteriorEquipment:Electricity | 813.77 | 9999.82 | 02-JAN-02:20 | 49607.07 | 02-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 21.77 | 380.98 | 03-JUN-05:00 | 1291.59 | 02-JAN-21:10 |
ElectricityPurchased:Facility | 5334.06 | 67272.24 | 06-MAY-05:00 | 413605.13 | 04-AUG-19:10 |
ElectricityPurchased:Plant | 5334.06 | 67272.24 | 06-MAY-05:00 | 413605.13 | 04-AUG-19:10 |
Cogeneration:ElectricityPurchased | 5334.06 | 67272.24 | 06-MAY-05:00 | 413605.13 | 04-AUG-19:10 |
General:Cogeneration:ElectricityPurchased | 5334.06 | 67272.24 | 06-MAY-05:00 | 413605.13 | 04-AUG-19:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 5334.06 | 67272.24 | 06-MAY-05:00 | 413605.13 | 04-AUG-19:10 |
ElectricityNet:Plant | 5334.06 | 67272.24 | 06-MAY-05:00 | 413605.13 | 04-AUG-19:10 |
Cogeneration:ElectricityNet | 5334.06 | 67272.24 | 06-MAY-05:00 | 413605.13 | 04-AUG-19:10 |
General:Cogeneration:ElectricityNet | 5334.06 | 67272.24 | 06-MAY-05:00 | 413605.13 | 04-AUG-19:10 |
General:Fans:Electricity | 525.45 | 11954.90 | 14-JAN-08:10 | 35380.68 | 05-SEP-22:00 |
ExteriorLights:Electricity | 193.72 | 0.00 | 01-JAN-07:30 | 12338.45 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 193.72 | 0.00 | 01-JAN-07:30 | 12338.45 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 789.09 | 9600.00 | 01-JAN-00:10 | 48128.80 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 2.91 | 18.80 | 01-JAN-00:10 | 188.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 183.37 | 0.00 | 03-JAN-08:20 | 9938.94 | 29-MAY-18:40 |
General:HeatRecovery:Electricity | 183.37 | 0.00 | 03-JAN-08:20 | 9938.94 | 29-MAY-18:40 |
WaterSystems:Electricity | 94.78 | 1222.48 | 02-SEP-00:40 | 4751.13 | 13-APR-06:50 |
Water Heater:WaterSystems:Electricity | 94.78 | 1222.48 | 02-SEP-00:40 | 4751.13 | 13-APR-06:50 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 932.03 | 0.00 | 01-JAN-00:10 | 191431.37 | 04-AUG-18:30 |
General:Cooling:Electricity | 932.03 | 0.00 | 01-JAN-00:10 | 191431.37 | 04-AUG-18:30 |
Pumps:Electricity | 88.56 | 52.06 | 29-MAR-07:30 | 4814.23 | 11-AUG-21:00 |
General:Pumps:Electricity | 88.56 | 52.06 | 29-MAR-07:30 | 4814.23 | 11-AUG-21:00 |
WIRED_LTG_ELECTRICITY | 27.53 | 0.00 | 01-JAN-00:10 | 2275.07 | 02-JAN-20:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 5398.30 | 23614.63 | 10-AUG-02:20 | 540448.41 | 24-MAR-17:50 |
NaturalGas:Building | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Laundry:InteriorEquipment:NaturalGas | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
NaturalGas:Plant | 3609.46 | 10252.73 | 10-AUG-02:20 | 442965.45 | 05-FEB-23:00 |
WaterSystems:NaturalGas | 2642.03 | 10252.73 | 10-AUG-02:20 | 255357.24 | 03-FEB-21:20 |
Water Heater:WaterSystems:NaturalGas | 2642.03 | 10252.73 | 10-AUG-02:20 | 255357.24 | 03-FEB-21:20 |
Heating:NaturalGas | 967.43 | 0.00 | 02-MAR-21:00 | 220144.77 | 06-FEB-07:10 |
Boiler:Heating:NaturalGas | 967.43 | 0.00 | 02-MAR-21:00 | 220144.77 | 06-FEB-07:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 3760.56 | 0.00 | 01-JAN-00:10 | 717162.65 | 11-AUG-22:00 |
PlantLoopCoolingDemand:HVAC | 3760.56 | 0.00 | 01-JAN-00:10 | 717162.65 | 11-AUG-22:00 |
CoolingCoils:PlantLoopCoolingDemand | 3760.56 | 0.00 | 01-JAN-00:10 | 717162.65 | 11-AUG-22:00 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 27-MAR-20:30 |
Water:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 27-MAR-20:30 |
WaterSystems:Water | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 27-MAR-20:30 |
Water Heater:WaterSystems:Water | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:10 |
MainsWater:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 27-MAR-20:30 |
MainsWater:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 27-MAR-20:30 |
WaterSystems:MainsWater | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 27-MAR-20:30 |
Water Heater:WaterSystems:MainsWater | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:10 |
WaterUse:WaterSystems:Water | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 22-MAY-06:30 |
WaterUse:WaterSystems:MainsWater | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 22-MAY-06:30 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 22979.41 | 134339.58 | 06-MAR-14:50 | 2758709.95 | 03-AUG-20:10 |
EnergyTransfer:Building | 5099.07 | 81290.83 | 15-JAN-14:50 | 339087.70 | 19-JUN-18:10 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 724.82 | 10529.89 | 06-FEB-04:00 | 36486.32 | 09-JUL-10:40 |
Refrigeration:EnergyTransfer | 183.59 | 4017.13 | 15-MAR-22:30 | 10374.61 | 10-NOV-07:30 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 91.80 | 2008.57 | 15-MAR-22:30 | 5187.31 | 10-NOV-07:30 |
General:Refrigeration:EnergyTransfer | 91.80 | 2008.57 | 15-MAR-22:30 | 5187.31 | 10-NOV-07:30 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 91.80 | 2008.57 | 15-MAR-22:30 | 5187.31 | 10-NOV-07:30 |
EnergyTransfer:Plant | 10090.89 | 16212.15 | 13-APR-02:10 | 1668566.20 | 11-AUG-22:00 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 21.61 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 70.18 | 1779.21 | 06-FEB-04:10 | 2562.11 | 18-MAY-13:10 |
EnergyTransfer:Zone:BASEMENT | 412.29 | 9156.93 | 29-MAY-15:00 | 22031.16 | 27-OCT-21:00 |
Heating:EnergyTransfer | 112.60 | 0.00 | 03-JAN-18:10 | 70327.92 | 14-JAN-16:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 112.60 | 0.00 | 03-JAN-18:10 | 70327.92 | 14-JAN-16:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 4894.68 | 69135.90 | 08-JAN-15:00 | 335464.26 | 19-JUN-18:10 |
Cooling:EnergyTransfer:Zone:BASEMENT | 412.29 | 9156.93 | 29-MAY-15:00 | 22031.16 | 27-OCT-21:00 |
General:Cooling:EnergyTransfer | 4894.68 | 69135.90 | 08-JAN-15:00 | 335464.26 | 19-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 412.29 | 9156.93 | 29-MAY-15:00 | 22031.16 | 27-OCT-21:00 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 41.46 | 0.25 | 25-DEC-02:40 | 4042.35 | 04-OCT-12:10 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.68 | 0.00 | 01-JAN-08:20 | 1145.31 | 02-JAN-07:20 |
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.68 | 0.00 | 01-JAN-08:20 | 1145.31 | 02-JAN-07:20 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 40.79 | 0.00 | 01-JAN-00:10 | 4042.35 | 04-OCT-12:10 |
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 40.79 | 0.00 | 01-JAN-00:10 | 4042.35 | 04-OCT-12:10 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 34.94 | 289.93 | 02-JAN-15:00 | 2103.83 | 16-AUG-21:00 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 34.94 | 289.93 | 02-JAN-15:00 | 2103.83 | 16-AUG-21:00 |
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 34.94 | 289.93 | 02-JAN-15:00 | 2103.83 | 16-AUG-21:00 |
EnergyTransfer:Zone:MECH_FLR_1 | 23.65 | 0.04 | 09-JAN-02:20 | 1727.28 | 17-AUG-20:00 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.12 | 0.00 | 01-JAN-19:10 | 385.11 | 02-JAN-10:40 |
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.12 | 0.00 | 01-JAN-19:10 | 385.11 | 02-JAN-10:40 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 23.53 | 0.00 | 01-JAN-00:10 | 1727.28 | 17-AUG-20:00 |
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 23.53 | 0.00 | 01-JAN-00:10 | 1727.28 | 17-AUG-20:00 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 12.60 | 0.02 | 26-JAN-03:20 | 803.49 | 04-AUG-21:00 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.34 | 0.00 | 03-JAN-18:10 | 406.45 | 06-FEB-16:00 |
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.34 | 0.00 | 03-JAN-18:10 | 406.45 | 06-FEB-16:00 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 12.26 | 0.00 | 01-JAN-00:10 | 803.49 | 04-AUG-21:00 |
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 12.26 | 0.00 | 01-JAN-00:10 | 803.49 | 04-AUG-21:00 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 597.07 | 9022.84 | 02-JAN-05:00 | 38836.98 | 04-AUG-20:00 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 597.07 | 9022.84 | 02-JAN-05:00 | 38836.98 | 04-AUG-20:00 |
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 597.07 | 9022.84 | 02-JAN-05:00 | 38836.98 | 04-AUG-20:00 |
EnergyTransfer:Zone:CAFE_FLR_1 | 234.22 | 18.61 | 08-JAN-15:00 | 14097.01 | 30-SEP-12:40 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 65.25 | 08-JAN-15:50 |
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 65.25 | 08-JAN-15:50 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 234.22 | 0.00 | 08-JAN-15:00 | 14097.01 | 30-SEP-12:40 |
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 234.22 | 0.00 | 08-JAN-15:00 | 14097.01 | 30-SEP-12:40 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 784.51 | 8815.11 | 08-JAN-16:00 | 41586.16 | 04-AUG-21:10 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 784.51 | 8815.11 | 08-JAN-16:00 | 41586.16 | 04-AUG-21:10 |
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 784.51 | 8815.11 | 08-JAN-16:00 | 41586.16 | 04-AUG-21:10 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 63.98 | 0.00 | 01-JAN-08:10 | 11652.26 | 02-AUG-15:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 13.32 | 0.00 | 01-JAN-08:10 | 5671.17 | 14-JAN-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 13.32 | 0.00 | 01-JAN-08:10 | 5671.17 | 14-JAN-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 50.66 | 0.00 | 01-JAN-00:10 | 11652.26 | 02-AUG-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 50.66 | 0.00 | 01-JAN-00:10 | 11652.26 | 02-AUG-15:10 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 55.10 | 0.00 | 01-JAN-08:10 | 11007.97 | 02-AUG-15:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 17.36 | 0.00 | 01-JAN-08:10 | 5718.72 | 06-FEB-09:20 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 17.36 | 0.00 | 01-JAN-08:10 | 5718.72 | 06-FEB-09:20 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 37.73 | 0.00 | 01-JAN-00:10 | 11007.97 | 02-AUG-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 37.73 | 0.00 | 01-JAN-00:10 | 11007.97 | 02-AUG-15:10 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 298.18 | 0.00 | 01-JAN-00:10 | 50623.87 | 04-OCT-12:00 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 298.18 | 0.00 | 01-JAN-00:10 | 50623.87 | 04-OCT-12:00 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 298.18 | 0.00 | 01-JAN-00:10 | 50623.87 | 04-OCT-12:00 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 377.59 | 0.00 | 01-JAN-08:10 | 71444.35 | 29-MAY-18:50 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 26.73 | 0.00 | 01-JAN-08:10 | 31537.97 | 06-FEB-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 26.73 | 0.00 | 01-JAN-08:10 | 31537.97 | 06-FEB-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 350.85 | 0.00 | 01-JAN-00:10 | 71444.35 | 29-MAY-18:50 |
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 350.85 | 0.00 | 01-JAN-00:10 | 71444.35 | 29-MAY-18:50 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 63.46 | 0.00 | 01-JAN-08:10 | 10617.70 | 22-AUG-08:10 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 13.16 | 0.00 | 01-JAN-08:10 | 5581.40 | 14-JAN-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 13.16 | 0.00 | 01-JAN-08:10 | 5581.40 | 14-JAN-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 50.30 | 0.00 | 01-JAN-00:10 | 10617.70 | 22-AUG-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 50.30 | 0.00 | 01-JAN-00:10 | 10617.70 | 22-AUG-08:10 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 54.43 | 0.00 | 01-JAN-08:10 | 11759.28 | 29-MAY-09:00 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 16.93 | 0.00 | 01-JAN-08:10 | 5619.98 | 14-JAN-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 16.93 | 0.00 | 01-JAN-08:10 | 5619.98 | 14-JAN-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 37.49 | 0.00 | 01-JAN-00:10 | 11759.28 | 29-MAY-09:00 |
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 37.49 | 0.00 | 01-JAN-00:10 | 11759.28 | 29-MAY-09:00 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 187.76 | 1.28 | 02-JAN-12:20 | 10709.59 | 19-AUG-10:40 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.30 | 0.00 | 01-JAN-00:10 | 2672.99 | 14-JAN-16:30 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.30 | 0.00 | 01-JAN-00:10 | 2672.99 | 14-JAN-16:30 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 187.47 | 0.00 | 01-JAN-13:20 | 10709.59 | 19-AUG-10:40 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 187.47 | 0.00 | 01-JAN-13:20 | 10709.59 | 19-AUG-10:40 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 17.94 | 0.00 | 01-JAN-08:10 | 3173.07 | 02-AUG-15:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 5.29 | 0.00 | 01-JAN-08:10 | 1737.44 | 14-JAN-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 5.29 | 0.00 | 01-JAN-08:10 | 1737.44 | 14-JAN-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 12.65 | 0.00 | 01-JAN-00:10 | 3173.07 | 02-AUG-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 12.65 | 0.00 | 01-JAN-00:10 | 3173.07 | 02-AUG-15:10 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 16.23 | 0.00 | 01-JAN-08:10 | 2972.20 | 02-AUG-15:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 6.61 | 0.00 | 01-JAN-08:10 | 1743.55 | 06-FEB-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 6.61 | 0.00 | 01-JAN-08:10 | 1743.55 | 06-FEB-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 9.62 | 0.00 | 01-JAN-00:10 | 2972.20 | 02-AUG-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 9.62 | 0.00 | 01-JAN-00:10 | 2972.20 | 02-AUG-15:10 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 92.52 | 0.00 | 01-JAN-08:10 | 15892.32 | 04-OCT-15:10 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 11.30 | 0.00 | 01-JAN-08:10 | 8109.52 | 14-JAN-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 11.30 | 0.00 | 01-JAN-08:10 | 8109.52 | 14-JAN-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 81.23 | 0.00 | 01-JAN-00:10 | 15892.32 | 04-OCT-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 81.23 | 0.00 | 01-JAN-00:10 | 15892.32 | 04-OCT-15:10 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 436.66 | 8023.34 | 06-FEB-15:00 | 23504.44 | 04-AUG-21:20 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 436.66 | 8023.34 | 06-FEB-15:00 | 23504.44 | 04-AUG-21:20 |
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 436.66 | 8023.34 | 06-FEB-15:00 | 23504.44 | 04-AUG-21:20 |
EnergyTransfer:Zone:DINING_FLR_6 | 476.50 | 9019.96 | 06-FEB-15:00 | 24713.49 | 04-AUG-21:20 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 476.50 | 9019.96 | 06-FEB-15:00 | 24713.49 | 04-AUG-21:20 |
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 476.50 | 9019.96 | 06-FEB-15:00 | 24713.49 | 04-AUG-21:20 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 633.02 | 8509.44 | 06-FEB-04:00 | 31395.43 | 09-JUL-10:40 |
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 633.02 | 8509.44 | 06-FEB-04:00 | 31395.43 | 09-JUL-10:40 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 93.16 | 0.00 | 31-DEC-04:20 | 6694.95 | 11-JUL-16:50 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.45 | 0.00 | 01-JAN-08:40 | 2005.19 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.45 | 0.00 | 01-JAN-08:40 | 2005.19 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 92.70 | 0.00 | 01-JAN-00:10 | 6694.95 | 11-JUL-16:50 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 92.70 | 0.00 | 01-JAN-00:10 | 6694.95 | 11-JUL-16:50 |
PlantLoopHeatingDemand:Facility | 1410.76 | 8899.07 | 10-AUG-00:10 | 229746.82 | 06-FEB-07:10 |
PlantLoopHeatingDemand:Plant | 760.18 | 8899.07 | 10-AUG-00:10 | 57491.80 | 09-FEB-07:10 |
WaterSystems:PlantLoopHeatingDemand | 760.18 | 8899.07 | 10-AUG-00:10 | 57491.80 | 09-FEB-07:10 |
General:WaterSystems:PlantLoopHeatingDemand | 760.18 | 8899.07 | 10-AUG-00:10 | 57491.80 | 09-FEB-07:10 |
EnergyTransfer:HVAC | 7789.45 | 702.33 | 08-MAY-14:40 | 949199.48 | 03-AUG-20:10 |
HeatingCoils:EnergyTransfer | 650.58 | 0.00 | 02-MAR-21:00 | 172261.82 | 06-FEB-07:10 |
PlantLoopHeatingDemand:HVAC | 650.58 | 0.00 | 02-MAR-21:00 | 172261.82 | 06-FEB-07:10 |
HeatingCoils:PlantLoopHeatingDemand | 650.58 | 0.00 | 02-MAR-21:00 | 172261.82 | 06-FEB-07:10 |
CoolingCoils:EnergyTransfer | 3760.56 | 0.00 | 01-JAN-00:10 | 717162.65 | 11-AUG-22:00 |
HeatRecoveryForHeating:EnergyTransfer | 2826.58 | 0.00 | 03-JAN-08:20 | 471098.25 | 06-FEB-07:00 |
HeatRecoveryForCooling:EnergyTransfer | 551.74 | 0.00 | 01-JAN-00:10 | 301603.61 | 03-AUG-20:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 760.18 | 8899.07 | 10-AUG-00:10 | 57491.80 | 09-FEB-07:10 |
WaterUse:WaterSystems:EnergyTransfer | 760.18 | 8899.07 | 10-AUG-00:10 | 57491.80 | 09-FEB-07:10 |
Boilers:EnergyTransfer | 645.20 | 0.00 | 02-MAR-21:00 | 172539.59 | 06-FEB-07:10 |
Chillers:EnergyTransfer | 3830.84 | 0.00 | 01-JAN-00:10 | 723317.71 | 11-AUG-22:00 |
HeatRejection:EnergyTransfer | 4762.87 | 0.00 | 01-JAN-00:10 | 911932.13 | 11-AUG-22:00 |
General:HeatRejection:EnergyTransfer | 4762.87 | 0.00 | 01-JAN-00:10 | 911932.13 | 11-AUG-22:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:32
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -412.295 | 0.000 | 0.000 | 140.181 | 161.294 | 143.105 | 0.000 | 0.000 | 0.000 | 0.001 | 0.000 | 0.000 | 0.000 | 0.000 | -32.286 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 0.677 | -40.786 | 0.000 | 0.000 | 15.469 | 7.307 | 10.186 | 24.443 | 0.000 | 0.080 | 0.000 | 0.000 | -9.840 | 0.000 | -1.770 | -5.765 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.000 | -34.941 | 0.000 | 0.000 | 16.982 | 8.462 | 11.795 | 0.000 | 0.000 | 0.030 | 0.000 | 0.000 | 0.000 | 0.000 | -0.727 | -1.601 |
MECH_FLR_1 | 0.000 | 0.000 | 0.121 | -23.530 | 0.000 | 0.000 | 3.711 | 8.366 | 12.471 | 0.000 | 0.000 | 0.069 | 0.431 | 0.000 | 0.000 | 0.000 | -1.641 | -0.000 |
STORAGE_FLR_1 | 0.000 | 0.000 | 0.342 | -12.263 | 0.000 | 0.000 | 2.885 | 3.079 | 3.598 | 0.000 | 0.000 | 0.042 | 3.250 | 0.000 | 0.000 | 0.000 | -0.934 | -0.000 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.000 | -597.076 | 0.000 | 0.000 | 11.306 | 3.975 | 658.131 | 0.000 | 0.000 | 0.118 | 0.000 | 0.000 | 0.000 | 0.000 | -2.435 | -74.020 |
CAFE_FLR_1 | 0.000 | 0.000 | 0.000 | -234.219 | 0.000 | 0.000 | 191.779 | 14.140 | 14.341 | 67.905 | 0.000 | 0.165 | 0.000 | 0.000 | -29.564 | 0.000 | -4.202 | -20.346 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.000 | -784.512 | 0.000 | 0.000 | 559.417 | 109.966 | 148.998 | 89.963 | 0.000 | 0.487 | 0.000 | 0.000 | -40.017 | 0.000 | -12.262 | -72.040 |
ROOM_1_FLR_3 | 17.252 | -42.917 | 0.000 | -11.673 | 0.000 | 0.000 | 9.712 | 9.244 | 10.478 | 46.463 | 0.000 | 0.442 | 0.000 | 0.000 | -22.086 | 0.000 | -4.654 | -12.262 |
ROOM_2_FLR_3 | 21.645 | -29.782 | 0.000 | -12.232 | 0.000 | 0.000 | 9.581 | 9.243 | 10.477 | 32.893 | 0.000 | 0.283 | 0.000 | 0.000 | -23.124 | 0.000 | -5.160 | -13.824 |
ROOM_3_MULT19_FLR_3 | 0.000 | -283.079 | 0.000 | -15.096 | 0.000 | 0.000 | 0.000 | 110.385 | 194.997 | 271.185 | 0.000 | 0.259 | 0.013 | 0.000 | -159.932 | 0.000 | -28.905 | -89.814 |
ROOM_4_MULT19_FLR_3 | 60.957 | -221.611 | 0.000 | -163.445 | 0.000 | 0.000 | 182.727 | 110.415 | 195.050 | 89.443 | 0.000 | 1.906 | 0.000 | 0.000 | -130.371 | 0.000 | -39.204 | -85.866 |
ROOM_5_FLR_3 | 17.015 | -42.476 | 0.000 | -11.675 | 0.000 | 0.000 | 9.708 | 9.244 | 10.478 | 46.049 | 0.000 | 0.442 | 0.000 | 0.000 | -21.806 | 0.000 | -4.665 | -12.315 |
ROOM_6_FLR_3 | 21.157 | -29.525 | 0.000 | -12.187 | 0.000 | 0.000 | 9.599 | 9.243 | 10.477 | 32.189 | 0.000 | 0.284 | 0.000 | 0.000 | -22.498 | 0.000 | -5.159 | -13.580 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 0.296 | -187.467 | 0.000 | 0.000 | 118.440 | 91.336 | 0.000 | 42.758 | 0.000 | 0.226 | 0.000 | 0.000 | -28.771 | 0.000 | -5.013 | -31.806 |
ROOM_1_FLR_6 | 6.370 | -10.814 | 0.000 | -2.915 | 0.000 | 0.000 | 2.431 | 2.311 | 2.620 | 11.539 | 0.000 | 0.116 | 0.000 | 0.000 | -5.476 | 0.000 | -1.195 | -4.987 |
ROOM_2_FLR_6 | 7.760 | -7.708 | 0.000 | -3.061 | 0.000 | 0.000 | 2.396 | 2.311 | 2.619 | 8.165 | 0.000 | 0.071 | 0.000 | 0.000 | -5.749 | 0.000 | -1.315 | -5.489 |
ROOM_3_MULT9_FLR_6 | 16.189 | -67.286 | 0.000 | -18.833 | 0.000 | 0.000 | 21.790 | 13.076 | 23.098 | 63.708 | 0.000 | 0.734 | 0.000 | 0.000 | -25.767 | 0.000 | -6.414 | -20.296 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.000 | -436.665 | 0.000 | 0.000 | 317.310 | 30.842 | 175.857 | 9.033 | 0.000 | 0.090 | 0.000 | 0.000 | -17.991 | 0.000 | -2.938 | -75.537 |
DINING_FLR_6 | 0.000 | 0.000 | 0.000 | -476.505 | 0.000 | 0.000 | 315.893 | 30.842 | 175.857 | 8.824 | 0.000 | 0.089 | 0.000 | 0.000 | -18.556 | 0.000 | -2.967 | -33.478 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.000 | -633.007 | 0.000 | 0.000 | 28.391 | 12.972 | 550.372 | 21.704 | 0.000 | 0.079 | 34.125 | 0.000 | -11.976 | 0.000 | -2.661 | -0.000 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 0.452 | -92.705 | 0.000 | 0.000 | 31.296 | 24.166 | 0.000 | 20.724 | 0.000 | 0.085 | 31.201 | 0.000 | -12.990 | 0.000 | -2.229 | -0.000 |
Total Facility | 168.346 | -735.197 | 1.888 | -4217.088 | 0.000 | 0.000 | 2001.006 | 782.223 | 2365.005 | 886.988 | 0.000 | 6.098 | 69.021 | 0.000 | -586.513 | 0.000 | -136.450 | -605.312 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 27-OCT-21:00 | 0.00 | 0.00 | 0.00 | -22032.21 | 0.00 | 0.00 | 5924.40 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4742.41 |
RETAIL_1_FLR_1 | 04-OCT-12:10 | 0.00 | 0.00 | 0.00 | -4042.54 | 0.00 | 0.00 | 150.60 | 166.00 | 252.59 | 5779.47 | 0.00 | 2.63 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2308.75 |
RETAIL_2_FLR_1 | 16-AUG-21:00 | 0.00 | 0.00 | 0.00 | -2103.93 | 0.00 | 0.00 | 697.61 | 615.12 | 752.15 | 0.00 | 0.00 | 5.45 | 33.60 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 17-AUG-20:00 | 0.00 | 0.00 | 0.00 | -1727.25 | 0.00 | 0.00 | 129.08 | 684.18 | 839.45 | 0.00 | 0.00 | 23.15 | 51.39 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 24-AUG-18:23 | 0.00 | 0.00 | 0.00 | -805.00 | 0.00 | 0.00 | 101.62 | 223.85 | 229.41 | 0.00 | 0.00 | 18.01 | 232.10 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 01-SEP-19:25 | 0.00 | 0.00 | 0.00 | -39070.79 | 0.00 | 0.00 | 392.56 | 325.08 | 44299.38 | 0.00 | 0.00 | 16.90 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5963.14 |
CAFE_FLR_1 | 30-SEP-12:40 | 0.00 | 0.00 | 0.00 | -14096.10 | 0.00 | 0.00 | 2968.70 | 103.98 | 355.63 | 15562.06 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -43.03 | -4851.24 |
LOBBY_FLR_1 | 04-AUG-21:10 | 0.00 | 0.00 | 0.00 | -41591.95 | 0.00 | 0.00 | 26439.94 | 6336.53 | 7389.94 | 870.29 | 0.00 | 245.70 | 309.54 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 27-MAY-18:01 | 0.00 | -13817.15 | 0.00 | -733.52 | 0.00 | 0.00 | 283.21 | 711.53 | 484.65 | 3890.11 | 0.00 | 0.00 | 9360.26 | 0.00 | -0.00 | 0.00 | -179.10 | 0.00 |
ROOM_2_FLR_3 | 02-MAY-18:21 | 0.00 | -14518.40 | 0.00 | -620.45 | 0.00 | 0.00 | 311.66 | 633.19 | 484.60 | 0.00 | 0.00 | 0.00 | 14852.63 | 0.00 | -1020.62 | 0.00 | -122.59 | 0.00 |
ROOM_3_MULT19_FLR_3 | 04-OCT-12:00 | 0.00 | -50625.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2378.94 | 2352.88 | 69448.81 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -150.50 | -23404.20 |
ROOM_4_MULT19_FLR_3 | 27-MAY-21:51 | 0.00 | -84199.53 | 0.00 | -9753.18 | 0.00 | 0.00 | 6204.45 | 7223.75 | 6668.31 | 0.00 | 0.00 | 0.00 | 77241.71 | 0.00 | -3087.97 | 0.00 | -297.53 | 0.00 |
ROOM_5_FLR_3 | 27-MAY-18:01 | 0.00 | -12594.06 | 0.00 | -725.24 | 0.00 | 0.00 | 283.21 | 711.53 | 484.65 | 258.20 | 0.00 | 0.00 | 11748.26 | 0.00 | -0.00 | 0.00 | -166.55 | 0.00 |
ROOM_6_FLR_3 | 30-MAY-08:61 | 0.00 | -14059.28 | 0.00 | -1075.65 | 0.00 | 0.00 | 58.80 | 313.04 | 452.99 | 8703.90 | 0.00 | 0.00 | 5628.22 | 0.00 | -0.00 | 0.00 | -22.01 | 0.00 |
CORRIDOR_FLR_3 | 24-AUG-18:23 | 0.00 | 0.00 | 0.00 | -11239.28 | 0.00 | 0.00 | 4153.70 | 6639.35 | 0.00 | 700.56 | 0.00 | 94.36 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -348.69 |
ROOM_1_FLR_6 | 27-MAY-18:01 | 0.00 | -3621.40 | 0.00 | -183.26 | 0.00 | 0.00 | 70.80 | 177.88 | 121.16 | 960.54 | 0.00 | 0.00 | 2529.79 | 0.00 | -0.00 | 0.00 | -55.52 | 0.00 |
ROOM_2_FLR_6 | 02-MAY-18:21 | 0.00 | -3892.81 | 0.00 | -163.09 | 0.00 | 0.00 | 75.15 | 158.30 | 121.15 | 0.00 | 0.00 | 0.00 | 4004.99 | 0.00 | -271.50 | 0.00 | -32.19 | 0.00 |
ROOM_3_MULT9_FLR_6 | 10-SEP-18:01 | 0.00 | -17123.75 | 0.00 | -1176.58 | 0.00 | 0.00 | 637.23 | 1006.40 | 1068.37 | 0.00 | 0.00 | 0.00 | 16254.50 | 0.00 | -368.04 | 0.00 | -298.13 | 0.00 |
BANQUET_FLR_6 | 04-AUG-21:20 | 0.00 | 0.00 | 0.00 | -23509.70 | 0.00 | 0.00 | 15640.05 | 1992.02 | 6747.90 | 354.58 | 0.00 | 49.78 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1274.62 |
DINING_FLR_6 | 11-JUL-18:03 | 0.00 | 0.00 | 0.00 | -24947.46 | 0.00 | 0.00 | 12268.81 | 1593.62 | 6747.90 | 1200.23 | 0.00 | 19.50 | 3117.41 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 01-JUN-18:05 | 0.00 | 0.00 | 0.00 | -31761.75 | 0.00 | 0.00 | 1063.39 | 942.94 | 21760.70 | 644.17 | 0.00 | 23.14 | 7327.41 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 11-JUL-16:50 | 0.00 | 0.00 | 0.00 | -6695.58 | 0.00 | 0.00 | 771.13 | 548.96 | 0.00 | 1002.88 | 0.00 | 28.36 | 4344.25 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 16-AUG-18:02 | 0.00 | -168575.42 | 0.00 | -201041.20 | 0.00 | 0.00 | 74671.55 | 54680.24 | 120482.43 | 20675.53 | 0.00 | 1593.85 | 97513.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 02-JAN-07:15 | 0.00 | 0.00 | 1152.63 | 0.00 | 0.00 | 0.00 | 358.01 | 332.00 | 433.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1338.57 | 0.00 | -199.00 | -738.09 |
RETAIL_2_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 02-JAN-11:08 | 0.00 | 0.00 | 385.08 | 0.00 | 0.00 | 0.00 | 43.84 | 190.05 | 309.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -160.53 | -767.72 |
STORAGE_FLR_1 | 06-FEB-16:00 | 0.00 | 0.00 | 406.46 | 0.00 | 0.00 | 0.00 | 50.59 | 69.95 | 89.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -86.57 | -529.64 |
LAUNDRY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 08-JAN-15:50 | 0.00 | 0.00 | 65.26 | 0.00 | 0.00 | 0.00 | 2352.47 | 328.96 | 304.82 | 0.00 | 0.00 | 0.00 | 310.34 | 0.00 | -3074.94 | 0.00 | -286.91 | 0.00 |
LOBBY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 08-JAN-16:13 | 6036.68 | 378.11 | 0.00 | -378.11 | 0.00 | 0.00 | 148.02 | 234.80 | 221.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2421.32 | 0.00 | -290.03 | -3929.41 |
ROOM_2_FLR_3 | 03-MAY-15:04 | 6254.47 | 442.13 | 0.00 | -442.13 | 0.00 | 0.00 | 244.82 | 199.20 | 200.16 | 872.24 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1304.44 | -6466.47 |
ROOM_3_MULT19_FLR_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 06-FEB-16:02 | 33195.99 | 3749.94 | 0.00 | -3749.94 | 0.00 | 0.00 | 5585.68 | 2379.59 | 3726.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -12300.41 | 0.00 | -1890.88 | -30696.38 |
ROOM_5_FLR_3 | 08-JAN-16:13 | 5890.17 | 375.26 | 0.00 | -375.26 | 0.00 | 0.00 | 148.08 | 234.80 | 221.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2421.46 | 0.00 | -289.52 | -3783.32 |
ROOM_6_FLR_3 | 03-MAY-15:04 | 5993.66 | 442.78 | 0.00 | -442.78 | 0.00 | 0.00 | 247.15 | 199.20 | 200.16 | 750.41 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1305.99 | -6084.59 |
CORRIDOR_FLR_3 | 14-JAN-16:30 | 0.00 | 0.00 | 2673.03 | 0.00 | 0.00 | 0.00 | 2078.73 | 2074.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3398.47 | 0.00 | -454.84 | -2973.24 |
ROOM_1_FLR_6 | 08-JAN-16:13 | 1799.87 | 92.60 | 0.00 | -92.60 | 0.00 | 0.00 | 37.06 | 58.70 | 55.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -593.07 | 0.00 | -72.38 | -1285.50 |
ROOM_2_FLR_6 | 06-FEB-16:13 | 1803.53 | 90.37 | 0.00 | -90.37 | 0.00 | 0.00 | 67.09 | 49.80 | 50.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -545.10 | 0.00 | -92.88 | -1332.49 |
ROOM_3_MULT9_FLR_6 | 14-JAN-16:15 | 8379.15 | 648.81 | 0.00 | -648.81 | 0.00 | 0.00 | 338.78 | 332.11 | 487.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2936.28 | 0.00 | -431.82 | -6169.69 |
BANQUET_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 02-JAN-07:10 | 0.00 | 0.00 | 2006.55 | 0.00 | 0.00 | 0.00 | 733.27 | 1097.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1746.87 | 0.00 | -248.79 | -1842.08 |
Total Facility | 14-JAN-16:03 | -8008.62 | 81417.36 | 5438.71 | -81417.36 | 0.00 | 0.00 | 36153.71 | 18827.09 | 74838.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -56733.63 | 0.00 | -9031.87 | -61483.65 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:32
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV WITH REHEAT | 21.9349 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 21.8150 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV WITH REHEAT | 11.6694 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 11.6694 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.6520 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.0400 | 0.000610 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.000000 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.000000 | 142.3000 | 0.003581 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.000000 | 422.4350 | 0.001448 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 83.8280 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003556 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.1800 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 | |
VAV WITH REHEAT | 0.00 | 0.001045 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.4779 | 2.4779 | 1.3182 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3605 | 0.3605 | 0.1918 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2279 | 0.2279 | 0.1212 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1861 | 0.1861 | 0.0990 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1110 | 0.1110 | 0.0590 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.2525 | 3.2525 | 1.7303 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5124 | 1.5124 | 0.8046 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.8364 | 4.8364 | 2.5730 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5371 | 1.5371 | 0.8177 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1533 | 2.1533 | 1.1455 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2563 | 2.2563 | 1.2003 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2533 | 2.2533 | 1.1987 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7703 | 0.7703 | 0.4098 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
VAV WITH REHEAT | 21.9349 | 21.8150 | 21.9349 | 11.6694 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3182 | 1.3182 | 1.3182 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1918 | 0.1918 | 0.1918 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1212 | 0.1212 | 0.1212 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0990 | 0.0990 | 0.0990 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0590 | 0.0590 | 0.0590 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7303 | 1.7303 | 1.7303 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8046 | 0.8046 | 0.8046 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.5730 | 2.5730 | 2.5730 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8177 | 0.8177 | 0.8177 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1455 | 1.1455 | 1.1455 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2003 | 1.2003 | 1.2003 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1987 | 1.1987 | 1.1987 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4098 | 0.4098 | 0.4098 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
VAV WITH REHEAT | 11.6694 | 11.6694 | 11.6694 | 11.6694 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:32
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 168.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 168.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 14.00 |
Number of hours cooling loads not met | 66.33 |
Number of hours not met | 80.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 967.43 | 220144.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 932.03 | 191431.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 782.22 | 64632.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 193.72 | 12338.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 872.72 | 59188.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 14.43 | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 8.99 | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.20 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 21.77 | 1291.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 789.09 | 48128.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 2.91 | 188.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 525.45 | 35380.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 88.56 | 4814.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 183.37 | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 94.78 | 4751.13 | 2642.03 | 255357.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.09 | 2093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 20.45 | 1903.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 34.43 | 1204.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1720.15 | 5334.06 |
Natural Gas | 1788.84 | 5398.30 |
Additional | 0.00 | 0.00 |
Total | 3508.99 | 10732.36 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 68.95 |
Space Heating | 0.00 |
Space Cooling | 82.15 |
Fans (All) | 46.31 |
Service Water Heating | 8.35 |
Receptacle Equipment | 146.16 |
Miscellaneous (All) | 470.16 |
Subtotal | 470.16 |
Natural Gas [MJ/m2] | |
Space Heating | 85.27 |
Service Water Heating | 232.88 |
Miscellaneous (All) | 475.82 |
Subtotal | 475.82 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 7.29 |
Space Heating | 9.01 |
Space Cooling | 8.68 |
Fans (All) | 4.90 |
Service Water Heating | 25.50 |
Receptacle Equipment | 32.12 |
Miscellaneous | 12.50 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 486. | 5110. |
ELEVATOR_STANDBY_SCH | 7671. | 8760. |
LTG_SCH_KITCHEN | 3061. | 8760. |
LTG_SCH_DINING | 3061. | 8760. |
LTG_SCH_BASEMENT | 2572. | 8760. |
LTG_SCH_LOBBY | 2295. | 8760. |
LTG_SCH_STORAGE | 1580. | 8760. |
LTG_SCH_MECHANIC | 3061. | 8760. |
LTG_SCH_LAUNDRY | 3061. | 8760. |
LTG_SCH_GUESTROOM | 1980. | 8760. |
LTG_SCH_CORRIDOR | 2295. | 8760. |
LTG_SCH_RETAIL | 2678. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 1591. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3737. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 5740. | 6205. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 8760. | 8760. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 26.67 | 365 | 26.67 | 365 |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
HTGSETP_SCH | BASEMENT DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:32
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8734.17 | 25.83 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 7838.50 | 921.50 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8733.50 | 26.50 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8713.00 | 47.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 7838.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 921.50 | 0.00 | 0.00 | 0.00 |
Average | 8713.60 | 46.40 | 0.00 | 0.00 | 0.00 |
Sum | 191699.17 | 1020.83 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4150.50 | 3.50 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4143.50 | 10.50 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108269.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 10.50 | 0.00 | 0.00 | 0.00 |
Average | 288886.41 | 0.64 | 0.00 | 0.00 | 0.00 |
Sum | 6355501.00 | 14.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8533.83 | 226.17 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 7752.17 | 1007.83 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 7797.50 | 962.50 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8758.00 | 2.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8502.00 | 258.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 7371.17 | 1388.83 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8593.33 | 166.67 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8758.50 | 1.50 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8497.00 | 263.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8753.50 | 6.50 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8439.00 | 321.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8748.67 | 11.33 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 7703.17 | 1056.83 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 7798.67 | 961.33 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8608.83 | 151.17 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 7371.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 1388.83 | 0.00 | 0.00 | 0.00 |
Average | 8451.61 | 308.39 | 0.00 | 0.00 | 0.00 |
Sum | 185935.33 | 6784.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 56739.17 | 2416.83 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 588903.00 | 121514.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 1776190.33 | 339238.67 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4039.33 | 114.67 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4076.33 | 77.67 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4064.67 | 89.33 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4006.83 | 147.17 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1029501.00 | 216214.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1046584.67 | 199130.33 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 106985.17 | 1283.83 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 1776190.33 | 339238.67 | 0.00 | 0.00 | 0.00 |
Average | 248876.75 | 40010.30 | 0.00 | 0.00 | 0.00 |
Sum | 5475288.50 | 880226.50 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:32
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:32
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 1592.73 | 0.00 | 0.00 |
Sum | 0.00 | 35040.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 710417.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 2115429.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 2115429.00 | 0.00 | 0.00 |
Average | 0.00 | 241694.36 | 0.00 | 0.00 |
Sum | 0.00 | 5317276.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4A
For: Environment
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Environment
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_NEWYORK
For: Environment
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.337597E+11 | 15357.80 | 20-JAN-22:00 | 3.90 | 3.17 | 0.782041E+10 | 4836.98 | 20-JAN-22:19 | 3.53 | 2.88 |
February | 0.289187E+11 | 14580.63 | 01-FEB-21:00 | 5.60 | 3.16 | 0.680921E+10 | 4831.83 | 01-FEB-22:10 | 4.90 | 2.79 |
March | 0.309686E+11 | 13907.59 | 03-MAR-21:00 | 11.10 | 6.67 | 0.731417E+10 | 4576.45 | 01-MAR-22:10 | 11.10 | 6.67 |
April | 0.296100E+11 | 14725.19 | 08-APR-10:33 | 23.90 | 16.13 | 0.691698E+10 | 4469.67 | 13-APR-21:10 | 5.00 | 4.72 |
May | 0.306634E+11 | 14726.16 | 29-MAY-10:33 | 27.43 | 17.92 | 0.705079E+10 | 4389.61 | 04-MAY-21:10 | 27.43 | 17.92 |
June | 0.320024E+11 | 16267.77 | 22-JUN-18:08 | 28.72 | 17.28 | 0.712286E+10 | 4590.68 | 30-JUN-22:10 | 20.00 | 18.86 |
July | 0.352584E+11 | 16351.43 | 11-JUL-18:05 | 26.73 | 16.72 | 0.761979E+10 | 4766.33 | 28-JUL-22:10 | 24.32 | 20.84 |
August | 0.373741E+11 | 18029.17 | 24-AUG-18:23 | 30.25 | 17.47 | 0.795729E+10 | 4837.34 | 30-AUG-21:19 | 22.43 | 18.00 |
September | 0.380263E+11 | 20442.02 | 13-SEP-21:00 | 23.90 | 22.40 | 0.787411E+10 | 4837.11 | 28-SEP-21:10 | 16.42 | 11.03 |
October | 0.407690E+11 | 22031.16 | 27-OCT-21:00 | 7.20 | 3.64 | 0.819118E+10 | 4837.09 | 04-OCT-22:10 | 7.20 | 3.64 |
November | 0.382090E+11 | 21719.52 | 03-NOV-21:00 | 12.80 | 10.14 | 0.791640E+10 | 4837.07 | 25-NOV-00:20 | -1.5 | -2.5 |
December | 0.367336E+11 | 20229.42 | 01-DEC-22:00 | 1.10 | -2.2 | 0.808692E+10 | 4837.28 | 01-DEC-01:10 | 1.10 | -2.2 |
Annual Sum or Average | 0.412293E+12 | 0.906801E+11 | ||||||||
Minimum of Months | 0.289187E+11 | 13907.59 | 1.10 | -2.2 | 0.680921E+10 | 4389.61 | -1.5 | -2.5 | ||
Maximum of Months | 0.407690E+11 | 22031.16 | 30.25 | 22.40 | 0.819118E+10 | 4837.34 | 27.43 | 20.84 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.113056E+10 | 2492.35 | 17-JAN-13:10 | 10.18 | 5.51 | 0.624252E+09 | 367.13 | 19-JAN-22:30 | 5.60 | 1.07 |
February | 0.140022E+10 | 2218.22 | 02-FEB-13:40 | 5.97 | -0.5 | 0.567411E+09 | 364.14 | 07-FEB-04:10 | -8.9 | -9.9 |
March | 0.240984E+10 | 3033.74 | 03-MAR-13:20 | 14.60 | 8.23 | 0.637931E+09 | 411.40 | 03-MAR-22:30 | 10.30 | 6.29 |
April | 0.295574E+10 | 3216.60 | 08-APR-12:30 | 23.60 | 16.18 | 0.626924E+09 | 458.39 | 07-APR-21:30 | 23.60 | 16.18 |
May | 0.392837E+10 | 2502.14 | 30-MAY-12:50 | 29.90 | 17.93 | 0.664990E+09 | 462.85 | 31-MAY-21:40 | 20.13 | 17.44 |
June | 0.461054E+10 | 2993.12 | 01-JUN-14:30 | 28.85 | 16.91 | 0.703619E+09 | 491.82 | 19-JUN-21:19 | 28.53 | 20.50 |
July | 0.522062E+10 | 3015.98 | 08-JUL-12:10 | 32.02 | 26.06 | 0.759212E+09 | 491.82 | 10-JUL-21:40 | 26.87 | 19.82 |
August | 0.570328E+10 | 3831.05 | 20-AUG-13:53 | 28.90 | 15.02 | 0.779762E+09 | 491.82 | 17-AUG-21:19 | 28.90 | 15.02 |
September | 0.483740E+10 | 3844.61 | 07-SEP-12:40 | 26.50 | 22.82 | 0.701384E+09 | 491.82 | 01-SEP-21:10 | 26.50 | 22.82 |
October | 0.470168E+10 | 4042.35 | 04-OCT-12:10 | 24.50 | 18.64 | 0.699270E+09 | 469.12 | 04-OCT-21:30 | 16.95 | 15.74 |
November | 0.232337E+10 | 3145.19 | 02-NOV-12:40 | 15.40 | 8.14 | 0.613145E+09 | 419.89 | 03-NOV-21:30 | 12.80 | 10.23 |
December | 0.156436E+10 | 3013.54 | 17-DEC-12:50 | 12.20 | 4.87 | 0.627170E+09 | 366.78 | 18-DEC-22:30 | 2.20 | 0.79 |
Annual Sum or Average | 0.407860E+11 | 0.800507E+10 | ||||||||
Minimum of Months | 0.113056E+10 | 2218.22 | 5.97 | -0.5 | 0.567411E+09 | 364.14 | -8.9 | -9.9 | ||
Maximum of Months | 0.570328E+10 | 4042.35 | 32.02 | 26.06 | 0.779762E+09 | 491.82 | 28.90 | 22.82 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.226907E+10 | 1190.36 | 19-JAN-21:00 | 3.90 | 0.79 | 0.769758E+09 | 519.97 | 19-JAN-23:10 | 5.60 | 1.07 |
February | 0.211311E+10 | 1179.66 | 02-FEB-21:00 | -1.7 | -5.7 | 0.703096E+09 | 515.71 | 02-FEB-22:30 | -2.5 | -6.1 |
March | 0.262368E+10 | 1305.74 | 03-MAR-21:00 | 11.10 | 6.67 | 0.820593E+09 | 551.75 | 03-MAR-23:10 | 9.82 | 6.12 |
April | 0.272553E+10 | 1545.68 | 07-APR-21:00 | 19.40 | 13.83 | 0.821046E+09 | 569.55 | 07-APR-22:10 | 18.22 | 13.39 |
May | 0.306513E+10 | 1793.74 | 31-MAY-21:00 | 20.60 | 17.62 | 0.885994E+09 | 569.55 | 31-MAY-22:10 | 19.78 | 17.36 |
June | 0.331544E+10 | 2020.41 | 19-JUN-21:00 | 28.90 | 20.74 | 0.905885E+09 | 569.55 | 20-JUN-22:10 | 20.60 | 17.54 |
July | 0.362834E+10 | 2047.63 | 07-JUL-21:00 | 25.60 | 23.22 | 0.947388E+09 | 569.55 | 11-JUL-22:10 | 22.62 | 17.84 |
August | 0.376180E+10 | 2103.83 | 16-AUG-21:00 | 26.70 | 24.96 | 0.958381E+09 | 569.56 | 30-AUG-21:19 | 22.43 | 18.00 |
September | 0.327899E+10 | 2024.92 | 01-SEP-21:00 | 26.70 | 18.23 | 0.898620E+09 | 569.55 | 06-SEP-22:10 | 22.20 | 20.63 |
October | 0.316446E+10 | 1777.07 | 05-OCT-21:00 | 18.90 | 17.80 | 0.907607E+09 | 569.55 | 04-OCT-22:10 | 18.90 | 17.80 |
November | 0.255921E+10 | 1344.53 | 03-NOV-20:00 | 12.80 | 10.92 | 0.794161E+09 | 564.58 | 03-NOV-22:10 | 12.80 | 10.38 |
December | 0.243569E+10 | 1206.54 | 18-DEC-21:00 | 2.80 | 1.39 | 0.788972E+09 | 524.69 | 18-DEC-23:10 | 2.30 | 0.67 |
Annual Sum or Average | 0.349405E+11 | 0.102015E+11 | ||||||||
Minimum of Months | 0.211311E+10 | 1179.66 | -1.7 | -5.7 | 0.703096E+09 | 515.71 | -2.5 | -6.1 | ||
Maximum of Months | 0.376180E+10 | 2103.83 | 28.90 | 24.96 | 0.958381E+09 | 569.56 | 22.62 | 20.63 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.823717E+09 | 813.12 | 19-JAN-21:00 | 3.90 | 0.79 | 0.152305E+09 | 94.83 | 19-JAN-22:10 | 5.60 | 1.07 |
February | 0.720777E+09 | 794.08 | 24-FEB-21:00 | 1.10 | -2.8 | 0.137611E+09 | 93.56 | 24-FEB-22:10 | 0.32 | -3.7 |
March | 0.154929E+10 | 927.88 | 28-MAR-10:33 | 12.23 | 7.80 | 0.155919E+09 | 101.03 | 28-MAR-21:10 | 8.22 | 5.85 |
April | 0.191435E+10 | 1123.76 | 08-APR-10:33 | 23.90 | 16.13 | 0.157986E+09 | 110.10 | 10-APR-21:19 | 12.57 | 5.94 |
May | 0.233343E+10 | 1237.75 | 31-MAY-10:33 | 25.60 | 19.79 | 0.176618E+09 | 118.91 | 31-MAY-21:19 | 20.37 | 17.53 |
June | 0.260346E+10 | 1443.03 | 19-JUN-21:00 | 28.90 | 20.74 | 0.187365E+09 | 120.45 | 20-JUN-21:19 | 20.93 | 17.07 |
July | 0.289434E+10 | 1677.75 | 10-JUL-20:00 | 28.30 | 20.24 | 0.199372E+09 | 120.45 | 11-JUL-21:19 | 22.80 | 17.52 |
August | 0.293667E+10 | 1727.28 | 17-AUG-20:00 | 28.90 | 22.33 | 0.200987E+09 | 120.46 | 30-AUG-21:19 | 22.43 | 18.00 |
September | 0.253318E+10 | 1417.73 | 01-SEP-21:00 | 26.70 | 18.23 | 0.184394E+09 | 120.45 | 01-SEP-21:10 | 26.60 | 18.09 |
October | 0.233839E+10 | 1159.30 | 05-OCT-10:33 | 21.13 | 17.47 | 0.178176E+09 | 115.79 | 05-OCT-21:19 | 18.90 | 17.68 |
November | 0.165845E+10 | 1008.32 | 04-NOV-10:33 | 16.83 | 11.51 | 0.154111E+09 | 105.11 | 03-NOV-21:19 | 16.83 | 11.51 |
December | 0.122356E+10 | 819.23 | 19-DEC-21:00 | 8.30 | 3.94 | 0.152740E+09 | 95.14 | 19-DEC-22:10 | 5.40 | 2.50 |
Annual Sum or Average | 0.235296E+11 | 0.203759E+10 | ||||||||
Minimum of Months | 0.720777E+09 | 794.08 | 1.10 | -2.8 | 0.137611E+09 | 93.56 | 0.32 | -3.7 | ||
Maximum of Months | 0.293667E+10 | 1727.28 | 28.90 | 22.33 | 0.200987E+09 | 120.46 | 26.60 | 18.09 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.222396E+09 | 450.31 | 19-JAN-21:00 | 3.90 | 0.79 | 0.116707E+09 | 69.62 | 19-JAN-23:10 | 5.60 | 1.07 |
February | 0.192827E+09 | 391.55 | 22-FEB-22:00 | 2.20 | -1.1 | 0.105501E+09 | 68.57 | 16-FEB-02:30 | 2.20 | -1.1 |
March | 0.683647E+09 | 539.26 | 28-MAR-10:33 | 12.23 | 7.80 | 0.118071E+09 | 74.24 | 03-MAR-23:10 | 12.23 | 7.80 |
April | 0.101953E+10 | 664.17 | 08-APR-10:33 | 23.90 | 16.13 | 0.118447E+09 | 80.89 | 10-APR-21:40 | 11.83 | 5.31 |
May | 0.134034E+10 | 728.93 | 31-MAY-10:33 | 25.60 | 19.79 | 0.131973E+09 | 87.96 | 31-MAY-22:10 | 19.78 | 17.36 |
June | 0.150221E+10 | 771.22 | 22-JUN-18:08 | 28.72 | 17.28 | 0.140605E+09 | 91.93 | 19-JUN-22:10 | 28.72 | 17.28 |
July | 0.165517E+10 | 786.88 | 08-JUL-10:33 | 30.53 | 25.21 | 0.150512E+09 | 92.66 | 10-JUL-21:19 | 27.03 | 20.02 |
August | 0.166788E+10 | 805.01 | 24-AUG-18:23 | 30.25 | 17.47 | 0.151768E+09 | 92.66 | 18-AUG-22:10 | 30.25 | 17.47 |
September | 0.145666E+10 | 754.25 | 03-SEP-10:33 | 25.20 | 15.62 | 0.138016E+09 | 91.81 | 01-SEP-21:10 | 25.20 | 15.62 |
October | 0.133741E+10 | 678.53 | 05-OCT-10:33 | 21.13 | 17.47 | 0.132792E+09 | 85.54 | 05-OCT-22:10 | 18.98 | 17.65 |
November | 0.793987E+09 | 587.84 | 04-NOV-10:33 | 16.83 | 11.51 | 0.115862E+09 | 77.38 | 03-NOV-22:10 | 16.83 | 11.51 |
December | 0.390471E+09 | 456.94 | 19-DEC-21:00 | 8.30 | 3.94 | 0.116729E+09 | 69.85 | 19-DEC-22:40 | 4.80 | 2.97 |
Annual Sum or Average | 0.122625E+11 | 0.153698E+10 | ||||||||
Minimum of Months | 0.192827E+09 | 391.55 | 2.20 | -1.1 | 0.105501E+09 | 68.57 | 2.20 | -1.1 | ||
Maximum of Months | 0.166788E+10 | 805.01 | 30.53 | 25.21 | 0.151768E+09 | 92.66 | 30.25 | 20.02 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.477864E+11 | 36638.17 | 19-JAN-21:00 | 3.90 | 0.79 | 0.578511E+09 | 381.62 | 11-JAN-22:10 | 3.90 | 0.79 |
February | 0.432090E+11 | 36528.11 | 17-FEB-21:00 | 1.10 | -0.8 | 0.523189E+09 | 381.60 | 03-FEB-22:10 | 1.10 | -0.8 |
March | 0.492888E+11 | 37317.17 | 03-MAR-21:00 | 11.10 | 6.67 | 0.583911E+09 | 381.61 | 28-MAR-21:19 | 8.13 | 5.73 |
April | 0.486195E+11 | 38125.89 | 07-APR-20:00 | 21.70 | 14.73 | 0.566249E+09 | 381.66 | 11-APR-21:19 | 9.03 | 1.57 |
May | 0.516708E+11 | 38432.35 | 30-MAY-20:00 | 20.00 | 15.55 | 0.588208E+09 | 381.68 | 12-MAY-21:10 | 20.00 | 15.55 |
June | 0.512216E+11 | 39060.39 | 22-JUN-19:25 | 27.25 | 16.79 | 0.572552E+09 | 382.19 | 22-JUN-21:10 | 25.92 | 16.12 |
July | 0.533918E+11 | 38721.58 | 10-JUL-20:00 | 28.30 | 20.24 | 0.591345E+09 | 381.68 | 11-JUL-21:19 | 22.80 | 17.52 |
August | 0.537969E+11 | 38836.98 | 04-AUG-20:00 | 32.20 | 24.21 | 0.593497E+09 | 381.76 | 25-AUG-21:10 | 22.52 | 14.69 |
September | 0.507358E+11 | 39069.07 | 01-SEP-19:25 | 26.95 | 17.79 | 0.571444E+09 | 394.11 | 01-SEP-21:10 | 26.60 | 18.09 |
October | 0.513131E+11 | 38095.97 | 04-OCT-20:00 | 18.90 | 16.06 | 0.588229E+09 | 381.71 | 26-OCT-21:10 | 8.22 | 3.60 |
November | 0.477863E+11 | 37405.36 | 03-NOV-20:00 | 12.80 | 10.92 | 0.564826E+09 | 381.71 | 03-NOV-21:10 | 12.80 | 10.17 |
December | 0.482526E+11 | 36662.70 | 19-DEC-21:00 | 8.30 | 3.94 | 0.580568E+09 | 381.66 | 04-DEC-22:10 | 8.30 | 3.94 |
Annual Sum or Average | 0.597073E+12 | 0.690253E+10 | ||||||||
Minimum of Months | 0.432090E+11 | 36528.11 | 1.10 | -0.8 | 0.523189E+09 | 381.60 | 1.10 | -0.8 | ||
Maximum of Months | 0.537969E+11 | 39069.07 | 32.20 | 24.21 | 0.593497E+09 | 394.11 | 26.60 | 18.09 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.146131E+11 | 10080.66 | 17-JAN-13:00 | 10.00 | 5.56 | 0.885501E+10 | 6104.58 | 19-JAN-22:40 | 5.60 | 1.07 |
February | 0.143479E+11 | 10022.53 | 20-FEB-13:00 | 9.40 | 4.36 | 0.814835E+10 | 6034.25 | 22-FEB-22:40 | 2.20 | -0.9 |
March | 0.176640E+11 | 11630.84 | 03-MAR-13:10 | 14.50 | 8.14 | 0.948828E+10 | 6460.46 | 03-MAR-23:10 | 9.82 | 6.12 |
April | 0.181451E+11 | 12265.14 | 08-APR-12:20 | 23.87 | 16.21 | 0.939464E+10 | 6462.62 | 07-APR-22:10 | 23.87 | 16.21 |
May | 0.202730E+11 | 10611.27 | 29-MAY-10:33 | 27.43 | 17.92 | 0.100859E+11 | 6462.77 | 31-MAY-22:10 | 19.78 | 17.36 |
June | 0.216078E+11 | 11746.76 | 19-JUN-21:10 | 28.72 | 20.62 | 0.102380E+11 | 6462.78 | 20-JUN-22:10 | 20.60 | 17.54 |
July | 0.237965E+11 | 11621.43 | 10-JUL-21:10 | 27.12 | 20.12 | 0.107089E+11 | 6462.73 | 11-JUL-22:10 | 22.62 | 17.84 |
August | 0.253323E+11 | 12605.55 | 19-AUG-11:40 | 26.83 | 16.39 | 0.108662E+11 | 6462.76 | 25-AUG-22:10 | 20.92 | 14.50 |
September | 0.225728E+11 | 14097.01 | 30-SEP-12:40 | 20.40 | 12.36 | 0.102386E+11 | 6462.77 | 06-SEP-22:10 | 20.40 | 12.36 |
October | 0.227777E+11 | 13848.99 | 04-OCT-12:00 | 24.40 | 18.65 | 0.104699E+11 | 6462.68 | 04-OCT-22:10 | 16.88 | 15.73 |
November | 0.171441E+11 | 12422.98 | 04-NOV-12:30 | 17.80 | 12.61 | 0.911768E+10 | 6460.63 | 03-NOV-22:30 | 17.80 | 12.61 |
December | 0.159422E+11 | 12381.77 | 17-DEC-11:00 | 10.60 | 4.31 | 0.907754E+10 | 6108.13 | 18-DEC-22:40 | 2.20 | 0.72 |
Annual Sum or Average | 0.234217E+12 | 0.116689E+12 | ||||||||
Minimum of Months | 0.143479E+11 | 10022.53 | 9.40 | 4.31 | 0.814835E+10 | 6034.25 | 2.20 | -0.9 | ||
Maximum of Months | 0.253323E+11 | 14097.01 | 28.72 | 20.62 | 0.108662E+11 | 6462.78 | 23.87 | 17.84 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.540268E+11 | 26531.63 | 19-JAN-21:00 | 3.90 | 0.79 | 0.276416E+11 | 18683.64 | 19-JAN-23:10 | 5.60 | 1.07 |
February | 0.501467E+11 | 26813.25 | 19-FEB-11:33 | 7.97 | 4.38 | 0.252589E+11 | 18480.66 | 22-FEB-23:10 | 2.20 | -0.8 |
March | 0.598666E+11 | 28980.18 | 03-MAR-22:20 | 10.40 | 6.34 | 0.292162E+11 | 19183.60 | 15-MAR-22:10 | 8.72 | 2.71 |
April | 0.612106E+11 | 34282.35 | 07-APR-21:10 | 19.22 | 13.77 | 0.289219E+11 | 19186.01 | 07-APR-22:10 | 18.22 | 13.39 |
May | 0.679399E+11 | 36426.76 | 31-MAY-21:10 | 20.48 | 17.58 | 0.309072E+11 | 19186.24 | 31-MAY-22:10 | 19.78 | 17.36 |
June | 0.723204E+11 | 40018.74 | 19-JUN-21:10 | 28.72 | 20.62 | 0.308836E+11 | 19186.24 | 20-JUN-22:10 | 20.60 | 17.54 |
July | 0.787725E+11 | 40518.19 | 10-JUL-21:10 | 27.12 | 20.12 | 0.320225E+11 | 19186.18 | 11-JUL-22:10 | 22.62 | 17.84 |
August | 0.811647E+11 | 41586.16 | 04-AUG-21:10 | 31.55 | 23.93 | 0.323329E+11 | 19186.24 | 25-AUG-22:10 | 20.92 | 14.50 |
September | 0.725017E+11 | 40686.00 | 01-SEP-21:10 | 26.60 | 18.09 | 0.308493E+11 | 19186.23 | 06-SEP-22:10 | 22.20 | 20.63 |
October | 0.710054E+11 | 37681.23 | 05-OCT-21:10 | 18.90 | 17.74 | 0.315697E+11 | 19186.12 | 04-OCT-22:10 | 18.90 | 17.74 |
November | 0.587416E+11 | 31379.25 | 03-NOV-21:10 | 12.80 | 10.17 | 0.283772E+11 | 19185.27 | 03-NOV-23:19 | 12.97 | 10.62 |
December | 0.568088E+11 | 28377.32 | 17-DEC-11:33 | 11.67 | 4.45 | 0.283283E+11 | 18777.14 | 18-DEC-23:10 | 2.30 | 0.67 |
Annual Sum or Average | 0.784506E+12 | 0.356309E+12 | ||||||||
Minimum of Months | 0.501467E+11 | 26531.63 | 3.90 | 0.79 | 0.252589E+11 | 18480.66 | 2.20 | -0.8 | ||
Maximum of Months | 0.811647E+11 | 41586.16 | 31.55 | 23.93 | 0.323329E+11 | 19186.24 | 22.62 | 20.63 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 26183334.36 | 3500.95 | 20-JAN-16:01 | 6.93 | 3.71 | 94068632.84 | 56.69 | 03-JAN-04:19 | 6.93 | 3.71 |
February | 52292906.07 | 3525.25 | 22-FEB-16:01 | 4.22 | -0.7 | 85576908.68 | 56.69 | 07-FEB-04:19 | 4.22 | -0.7 |
March | 0.281184E+09 | 3572.58 | 11-MAR-16:01 | 11.20 | 5.40 | 96444173.16 | 56.69 | 27-MAR-21:19 | 13.87 | 10.67 |
April | 0.647494E+09 | 3606.97 | 11-APR-15:01 | 15.00 | 5.16 | 94090208.39 | 56.69 | 08-APR-23:19 | 15.00 | 5.16 |
May | 0.128309E+10 | 3637.70 | 27-MAY-18:01 | 21.02 | 11.62 | 98513051.86 | 56.69 | 30-MAY-21:00 | 18.90 | 14.84 |
June | 0.206858E+10 | 3363.89 | 23-JUN-08:61 | 26.70 | 18.47 | 95884524.00 | 56.70 | 23-JUN-22:00 | 22.20 | 21.37 |
July | 0.249563E+10 | 3272.88 | 01-JUL-18:02 | 22.12 | 19.58 | 99097057.63 | 56.70 | 09-JUL-23:10 | 27.48 | 23.83 |
August | 0.270025E+10 | 3273.55 | 13-AUG-08:62 | 26.38 | 19.14 | 99197970.57 | 56.70 | 17-AUG-00:40 | 25.93 | 25.25 |
September | 0.173374E+10 | 3581.72 | 28-SEP-18:01 | 19.90 | 10.33 | 95593628.14 | 56.70 | 01-SEP-23:40 | 19.90 | 10.33 |
October | 0.118472E+10 | 3557.06 | 28-OCT-15:01 | 10.60 | 3.72 | 98371159.69 | 56.69 | 04-OCT-01:10 | 10.60 | 3.72 |
November | 0.157066E+09 | 3353.70 | 02-NOV-18:01 | 13.80 | 7.37 | 92726924.13 | 56.69 | 03-NOV-21:10 | 12.80 | 10.17 |
December | 34531879.76 | 3480.75 | 02-DEC-16:01 | 5.92 | 0.97 | 94577891.45 | 56.69 | 01-DEC-01:19 | 5.92 | 0.97 |
Annual Sum or Average | 0.126648E+11 | 0.114414E+10 | ||||||||
Minimum of Months | 26183334.36 | 3272.88 | 4.22 | -0.7 | 85576908.68 | 56.69 | 4.22 | -0.7 | ||
Maximum of Months | 0.270025E+10 | 3637.70 | 26.70 | 19.58 | 99197970.57 | 56.70 | 27.48 | 25.25 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8154753.59 | 2793.11 | 20-JAN-16:01 | 6.93 | 3.71 | 93171901.26 | 56.69 | 03-JAN-04:19 | 6.93 | 3.71 |
February | 15191361.09 | 3209.81 | 22-FEB-16:01 | 4.22 | -0.7 | 84411263.26 | 56.69 | 10-FEB-04:19 | 4.22 | -0.7 |
March | 0.132771E+09 | 3439.83 | 11-MAR-16:01 | 11.20 | 5.40 | 95645175.47 | 66.19 | 27-MAR-21:10 | 14.13 | 10.87 |
April | 0.420939E+09 | 3697.67 | 09-APR-18:11 | 14.43 | 12.85 | 95051542.69 | 72.03 | 07-APR-21:30 | 14.43 | 12.85 |
May | 0.958661E+09 | 3784.68 | 02-MAY-18:21 | 14.15 | 8.82 | 0.104246E+09 | 84.51 | 31-MAY-21:10 | 20.48 | 17.58 |
June | 0.161126E+10 | 3470.79 | 10-JUN-08:51 | 23.30 | 15.08 | 0.106723E+09 | 82.22 | 28-JUN-21:30 | 21.40 | 18.80 |
July | 0.221595E+10 | 3556.19 | 03-JUL-18:51 | 24.40 | 21.27 | 0.104392E+09 | 81.23 | 05-JUL-21:30 | 22.50 | 21.72 |
August | 0.227000E+10 | 3407.87 | 23-AUG-08:51 | 22.80 | 15.80 | 0.103698E+09 | 82.08 | 10-AUG-21:10 | 22.80 | 15.80 |
September | 0.114435E+10 | 3411.53 | 03-SEP-08:51 | 22.80 | 14.85 | 0.102960E+09 | 81.78 | 06-SEP-21:10 | 22.70 | 20.80 |
October | 0.593657E+09 | 3423.05 | 26-OCT-15:01 | 12.62 | 5.07 | 0.101424E+09 | 74.40 | 04-OCT-21:40 | 12.62 | 5.07 |
November | 54380359.93 | 3108.48 | 04-NOV-15:01 | 17.30 | 12.80 | 91796950.30 | 56.69 | 24-NOV-04:19 | -3.5 | -5.8 |
December | 8123640.71 | 2116.85 | 17-DEC-16:01 | 9.82 | 4.16 | 93395523.79 | 56.69 | 08-DEC-04:19 | 9.82 | 4.16 |
Annual Sum or Average | 0.943344E+10 | 0.117692E+10 | ||||||||
Minimum of Months | 8123640.71 | 2116.85 | 4.22 | -0.7 | 84411263.26 | 56.69 | -3.5 | -5.8 | ||
Maximum of Months | 0.227000E+10 | 3784.68 | 24.40 | 21.27 | 0.106723E+09 | 84.51 | 22.80 | 21.72 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 9122220.67 | 145.12 | 31-JAN-15:20 | -1.5 | -6.0 | 0.00 | 0.00 | 01-JAN-00:10 | -1.5 | -6.0 |
February | 43769371.04 | 347.76 | 20-FEB-13:30 | 9.15 | 4.45 | 0.00 | 0.00 | 01-FEB-00:10 | 9.15 | 4.45 |
March | 0.106252E+09 | 410.14 | 15-MAR-13:05 | 13.40 | 6.62 | 0.00 | 0.00 | 01-MAR-00:10 | 13.40 | 6.62 |
April | 0.196078E+09 | 536.48 | 07-APR-12:30 | 26.15 | 15.90 | 0.00 | 0.00 | 01-APR-00:10 | 26.15 | 15.90 |
May | 0.325251E+09 | 402.65 | 30-MAY-12:50 | 29.90 | 17.93 | 0.00 | 0.00 | 01-MAY-00:10 | 29.90 | 17.93 |
June | 0.491345E+09 | 420.01 | 19-JUN-13:20 | 34.80 | 23.85 | 0.00 | 0.00 | 01-JUN-00:10 | 34.80 | 23.85 |
July | 0.635915E+09 | 444.19 | 10-JUL-13:10 | 32.30 | 20.52 | 0.00 | 0.00 | 01-JUL-00:10 | 32.30 | 20.52 |
August | 0.752102E+09 | 567.08 | 30-AUG-12:50 | 27.12 | 15.44 | 0.00 | 0.00 | 01-AUG-00:10 | 27.12 | 15.44 |
September | 0.581426E+09 | 626.39 | 28-SEP-12:30 | 23.05 | 14.08 | 0.00 | 0.00 | 01-SEP-00:10 | 23.05 | 14.08 |
October | 0.573741E+09 | 666.10 | 04-OCT-12:00 | 24.40 | 18.65 | 0.00 | 0.00 | 01-OCT-00:10 | 24.40 | 18.65 |
November | 0.148284E+09 | 563.23 | 02-NOV-12:40 | 15.40 | 8.14 | 0.00 | 0.00 | 01-NOV-00:10 | 15.40 | 8.14 |
December | 60120228.84 | 397.06 | 17-DEC-13:30 | 12.20 | 5.12 | 0.00 | 0.00 | 01-DEC-00:10 | 12.20 | 5.12 |
Annual Sum or Average | 0.392341E+10 | 0.00 | ||||||||
Minimum of Months | 9122220.67 | 145.12 | -1.5 | -6.0 | 0.00 | 0.00 | -1.5 | -6.0 | ||
Maximum of Months | 0.752102E+09 | 666.10 | 34.80 | 23.85 | 0.00 | 0.00 | 34.80 | 23.85 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 40136127.86 | 906.89 | 22-JAN-09:02 | 5.10 | 4.57 | 94739623.57 | 56.69 | 17-JAN-04:19 | 5.10 | 4.57 |
February | 30145762.81 | 809.91 | 25-FEB-09:01 | -2.0 | -5.5 | 85547085.30 | 56.69 | 03-FEB-04:19 | -2.0 | -5.5 |
March | 0.150700E+09 | 1080.23 | 03-MAR-19:02 | 12.12 | 7.02 | 96134173.76 | 66.47 | 27-MAR-21:10 | 14.13 | 10.87 |
April | 0.317710E+09 | 1174.26 | 10-APR-20:41 | 13.68 | 6.84 | 94476775.93 | 70.10 | 07-APR-21:00 | 13.68 | 6.84 |
May | 0.528928E+09 | 1236.22 | 27-MAY-21:51 | 18.90 | 10.64 | 0.101527E+09 | 77.10 | 31-MAY-21:40 | 20.13 | 17.44 |
June | 0.690714E+09 | 1227.24 | 04-JUN-08:51 | 23.30 | 12.88 | 0.102448E+09 | 78.25 | 28-JUN-21:40 | 21.50 | 18.92 |
July | 0.889041E+09 | 1143.51 | 03-JUL-18:51 | 24.40 | 21.27 | 0.103094E+09 | 77.79 | 25-JUL-21:10 | 22.70 | 20.79 |
August | 0.834207E+09 | 1121.68 | 28-AUG-21:51 | 19.40 | 14.50 | 0.102252E+09 | 76.33 | 10-AUG-21:10 | 19.40 | 14.50 |
September | 0.556934E+09 | 1200.32 | 10-SEP-21:51 | 16.70 | 9.96 | 0.100550E+09 | 77.24 | 05-SEP-21:10 | 16.70 | 9.96 |
October | 0.365492E+09 | 1157.97 | 06-OCT-18:01 | 14.90 | 8.94 | 99270216.94 | 71.48 | 04-OCT-21:00 | 14.90 | 8.94 |
November | 0.164057E+09 | 1083.19 | 02-NOV-18:01 | 13.80 | 7.37 | 92937013.99 | 56.69 | 09-NOV-22:49 | 12.20 | 12.20 |
December | 48444483.54 | 939.93 | 25-DEC-09:02 | 10.50 | 10.22 | 94963693.31 | 56.69 | 01-DEC-01:19 | 10.50 | 10.22 |
Annual Sum or Average | 0.461651E+10 | 0.116794E+10 | ||||||||
Minimum of Months | 30145762.81 | 809.91 | -2.0 | -5.5 | 85547085.30 | 56.69 | -2.0 | -5.5 | ||
Maximum of Months | 0.889041E+09 | 1236.22 | 24.40 | 21.27 | 0.103094E+09 | 78.25 | 22.70 | 20.79 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 38763638.73 | 2594.17 | 19-JAN-09:02 | 4.97 | 3.19 | 94048139.54 | 56.69 | 03-JAN-04:19 | 4.97 | 3.19 |
February | 61396511.01 | 3272.18 | 25-FEB-09:01 | -2.0 | -5.5 | 85693244.44 | 56.69 | 14-FEB-04:19 | -2.0 | -5.5 |
March | 0.248328E+09 | 3252.53 | 11-MAR-16:01 | 11.20 | 5.40 | 96547805.37 | 56.69 | 27-MAR-21:19 | 13.87 | 10.67 |
April | 0.653303E+09 | 3291.85 | 11-APR-15:01 | 15.00 | 5.16 | 94315924.85 | 56.69 | 08-APR-23:30 | 15.00 | 5.16 |
May | 0.131833E+10 | 3329.86 | 27-MAY-18:01 | 21.02 | 11.62 | 98649026.57 | 56.69 | 30-MAY-21:00 | 18.90 | 14.84 |
June | 0.195711E+10 | 3094.32 | 25-JUN-08:61 | 24.60 | 23.00 | 95932402.96 | 56.70 | 22-JUN-22:49 | 24.60 | 23.00 |
July | 0.246321E+10 | 3153.76 | 27-JUL-08:61 | 24.60 | 22.21 | 99120379.54 | 56.70 | 14-JUL-00:10 | 24.60 | 22.21 |
August | 0.267670E+10 | 3146.98 | 24-AUG-08:61 | 24.18 | 18.86 | 99233450.27 | 56.70 | 22-AUG-00:49 | 24.18 | 18.86 |
September | 0.174695E+10 | 3314.21 | 28-SEP-18:01 | 19.90 | 10.33 | 95679843.03 | 56.70 | 05-SEP-22:49 | 19.90 | 10.33 |
October | 0.113780E+10 | 3274.63 | 26-OCT-15:01 | 12.62 | 5.07 | 98502759.26 | 56.69 | 06-OCT-02:09 | 12.62 | 5.07 |
November | 0.207155E+09 | 3114.28 | 02-NOV-18:01 | 13.80 | 7.37 | 92945537.44 | 56.69 | 03-NOV-21:10 | 12.80 | 10.17 |
December | 65986118.60 | 3042.81 | 02-DEC-09:02 | 2.38 | -1.7 | 94610053.07 | 56.69 | 29-DEC-04:19 | -1.1 | -3.1 |
Annual Sum or Average | 0.125750E+11 | 0.114528E+10 | ||||||||
Minimum of Months | 38763638.73 | 2594.17 | -2.0 | -5.5 | 85693244.44 | 56.69 | -2.0 | -5.5 | ||
Maximum of Months | 0.267670E+10 | 3329.86 | 24.60 | 23.00 | 99233450.27 | 56.70 | 24.60 | 23.00 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 9269779.05 | 1654.11 | 19-JAN-09:02 | 4.97 | 3.19 | 93149669.30 | 56.69 | 03-JAN-04:30 | 4.97 | 3.19 |
February | 15887501.13 | 3026.22 | 25-FEB-09:01 | -2.0 | -5.5 | 84453036.76 | 56.69 | 10-FEB-04:19 | -2.0 | -5.5 |
March | 0.114026E+09 | 2933.25 | 23-MAR-08:62 | -0.8 | -4.6 | 95477299.52 | 59.98 | 27-MAR-21:10 | 14.13 | 10.87 |
April | 0.444058E+09 | 3453.81 | 08-APR-08:51 | 21.70 | 15.33 | 94791939.06 | 70.90 | 07-APR-21:30 | 21.70 | 15.33 |
May | 0.101803E+10 | 3784.02 | 30-MAY-08:61 | 25.18 | 15.91 | 0.103200E+09 | 80.47 | 31-MAY-21:30 | 20.25 | 17.49 |
June | 0.153755E+10 | 3614.57 | 26-JUN-08:32 | 24.63 | 19.00 | 0.104656E+09 | 79.09 | 20-JUN-21:19 | 24.63 | 19.00 |
July | 0.216385E+10 | 3467.42 | 11-JUL-08:51 | 23.90 | 16.36 | 0.104630E+09 | 79.82 | 25-JUL-21:10 | 22.70 | 20.79 |
August | 0.221665E+10 | 3592.18 | 30-AUG-08:51 | 22.80 | 14.85 | 0.104008E+09 | 79.56 | 10-AUG-21:10 | 22.80 | 14.85 |
September | 0.117359E+10 | 3475.51 | 03-SEP-08:51 | 22.80 | 14.85 | 0.102248E+09 | 80.24 | 05-SEP-21:10 | 23.90 | 20.42 |
October | 0.581032E+09 | 3238.26 | 15-OCT-08:51 | 17.20 | 12.24 | 0.100515E+09 | 71.42 | 05-OCT-21:40 | 17.20 | 12.24 |
November | 84573202.19 | 2825.84 | 08-NOV-09:02 | 10.18 | 8.38 | 91961218.07 | 56.69 | 24-NOV-04:19 | -3.5 | -5.8 |
December | 14399494.81 | 2267.86 | 17-DEC-09:02 | 6.05 | 2.94 | 93396216.54 | 56.69 | 15-DEC-04:19 | 6.05 | 2.94 |
Annual Sum or Average | 0.937292E+10 | 0.117249E+10 | ||||||||
Minimum of Months | 9269779.05 | 1654.11 | -2.0 | -5.5 | 84453036.76 | 56.69 | -3.5 | -5.8 | ||
Maximum of Months | 0.221665E+10 | 3784.02 | 25.18 | 19.00 | 0.104656E+09 | 80.47 | 24.63 | 20.79 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.167603E+10 | 1581.74 | 19-JAN-19:08 | 5.82 | 1.55 | 0.119952E+10 | 722.80 | 19-JAN-22:49 | 5.60 | 1.07 |
February | 0.180697E+10 | 1754.94 | 19-FEB-11:33 | 7.97 | 4.38 | 0.108479E+10 | 719.21 | 22-FEB-22:49 | 2.20 | -0.8 |
March | 0.324466E+10 | 1892.67 | 29-MAR-10:33 | 8.17 | 4.49 | 0.122231E+10 | 764.20 | 03-MAR-22:49 | 8.17 | 4.49 |
April | 0.383830E+10 | 2297.17 | 08-APR-10:33 | 23.90 | 16.13 | 0.123248E+10 | 837.66 | 10-APR-21:40 | 11.83 | 5.31 |
May | 0.468660E+10 | 2530.82 | 31-MAY-10:33 | 25.60 | 19.79 | 0.136409E+10 | 906.87 | 31-MAY-21:49 | 20.02 | 17.39 |
June | 0.521348E+10 | 2700.82 | 01-JUN-17:02 | 27.80 | 16.52 | 0.144574E+10 | 924.95 | 23-JUN-22:10 | 22.70 | 21.24 |
July | 0.563995E+10 | 2658.03 | 08-JUL-10:33 | 30.53 | 25.21 | 0.152543E+10 | 937.54 | 13-JUL-21:40 | 26.87 | 23.36 |
August | 0.573670E+10 | 2809.83 | 24-AUG-18:23 | 30.25 | 17.47 | 0.155076E+10 | 947.38 | 18-AUG-21:40 | 30.25 | 17.47 |
September | 0.506247E+10 | 2655.58 | 04-SEP-10:33 | 25.60 | 17.74 | 0.141973E+10 | 936.30 | 01-SEP-21:40 | 25.60 | 17.74 |
October | 0.474482E+10 | 2389.60 | 05-OCT-10:33 | 21.13 | 17.47 | 0.138435E+10 | 883.57 | 05-OCT-21:49 | 18.90 | 17.51 |
November | 0.302874E+10 | 2046.35 | 04-NOV-10:33 | 16.83 | 11.51 | 0.118968E+10 | 793.37 | 03-NOV-22:10 | 16.83 | 11.51 |
December | 0.218781E+10 | 1783.73 | 17-DEC-11:33 | 11.67 | 4.45 | 0.120029E+10 | 722.45 | 18-DEC-22:49 | 2.20 | 0.64 |
Annual Sum or Average | 0.468665E+11 | 0.158192E+11 | ||||||||
Minimum of Months | 0.167603E+10 | 1581.74 | 5.82 | 1.55 | 0.108479E+10 | 719.21 | 2.20 | -0.8 | ||
Maximum of Months | 0.573670E+10 | 2809.83 | 30.53 | 25.21 | 0.155076E+10 | 947.38 | 30.25 | 23.36 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 22241647.06 | 3651.16 | 20-JAN-16:01 | 6.93 | 3.71 | 93525347.69 | 56.69 | 15-JAN-02:20 | 6.93 | 3.71 |
February | 48184225.29 | 3677.93 | 22-FEB-16:01 | 4.22 | -0.7 | 85090297.23 | 56.69 | 10-FEB-04:19 | 4.22 | -0.7 |
March | 0.269236E+09 | 3739.30 | 11-MAR-16:01 | 11.20 | 5.40 | 96062173.71 | 56.70 | 28-MAR-00:49 | 11.10 | 8.78 |
April | 0.636928E+09 | 3767.21 | 11-APR-15:01 | 15.00 | 5.16 | 93847034.46 | 56.69 | 11-APR-02:09 | 15.00 | 5.16 |
May | 0.128518E+10 | 3804.69 | 27-MAY-18:01 | 21.02 | 11.62 | 98422710.52 | 56.70 | 30-MAY-21:00 | 18.90 | 14.84 |
June | 0.210875E+10 | 3459.67 | 23-JUN-08:61 | 26.70 | 18.47 | 95845278.34 | 56.70 | 19-JUN-23:49 | 26.70 | 18.47 |
July | 0.258541E+10 | 3402.84 | 01-JUL-18:02 | 22.12 | 19.58 | 99090988.78 | 56.70 | 20-JUL-22:30 | 26.40 | 24.40 |
August | 0.277251E+10 | 3447.76 | 26-AUG-18:02 | 23.80 | 18.78 | 99186079.20 | 56.70 | 29-AUG-21:49 | 22.20 | 19.55 |
September | 0.169955E+10 | 3742.03 | 28-SEP-18:01 | 19.90 | 10.33 | 95500299.54 | 56.70 | 26-SEP-01:10 | 19.90 | 10.33 |
October | 0.107744E+10 | 3706.95 | 28-OCT-15:01 | 10.60 | 3.72 | 98148872.63 | 56.69 | 16-OCT-21:30 | 10.60 | 3.72 |
November | 0.119761E+09 | 3447.81 | 02-NOV-18:01 | 13.80 | 7.37 | 92203729.53 | 56.69 | 24-NOV-04:19 | -3.5 | -5.8 |
December | 25753566.74 | 3641.60 | 02-DEC-16:01 | 5.92 | 0.97 | 94000250.40 | 56.69 | 15-DEC-04:19 | -2.8 | -5.2 |
Annual Sum or Average | 0.126509E+11 | 0.114092E+10 | ||||||||
Minimum of Months | 22241647.06 | 3402.84 | 4.22 | -0.7 | 85090297.23 | 56.69 | -3.5 | -5.8 | ||
Maximum of Months | 0.277251E+10 | 3804.69 | 26.70 | 19.58 | 99186079.20 | 56.70 | 26.70 | 24.40 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 4673935.29 | 2409.82 | 17-JAN-16:01 | 9.45 | 4.59 | 92728621.39 | 56.69 | 03-JAN-04:19 | 9.45 | 4.59 |
February | 10705633.07 | 2588.28 | 22-FEB-16:01 | 4.22 | -0.7 | 84028465.14 | 56.69 | 28-FEB-04:19 | 1.10 | 0.87 |
March | 0.119864E+09 | 3583.84 | 11-MAR-16:01 | 11.20 | 5.40 | 95240067.42 | 67.01 | 27-MAR-21:10 | 14.13 | 10.87 |
April | 0.407199E+09 | 3869.32 | 09-APR-18:11 | 14.43 | 12.85 | 95031708.10 | 75.48 | 10-APR-18:10 | 19.22 | 10.01 |
May | 0.978248E+09 | 4055.86 | 02-MAY-18:21 | 14.15 | 8.82 | 0.105035E+09 | 90.99 | 31-MAY-21:10 | 20.48 | 17.58 |
June | 0.171564E+10 | 3735.00 | 04-JUN-21:51 | 17.20 | 12.24 | 0.107812E+09 | 88.33 | 28-JUN-21:10 | 21.20 | 18.58 |
July | 0.233994E+10 | 3691.54 | 03-JUL-18:51 | 24.40 | 21.27 | 0.104461E+09 | 82.54 | 05-JUL-21:40 | 22.40 | 21.60 |
August | 0.236522E+10 | 3521.34 | 30-AUG-08:51 | 22.80 | 14.85 | 0.103625E+09 | 83.34 | 10-AUG-21:10 | 22.80 | 14.85 |
September | 0.113704E+10 | 3528.58 | 03-SEP-08:51 | 22.80 | 14.85 | 0.103249E+09 | 83.28 | 06-SEP-21:10 | 22.70 | 20.80 |
October | 0.502709E+09 | 3559.02 | 26-OCT-15:01 | 12.62 | 5.07 | 0.101258E+09 | 75.35 | 04-OCT-21:40 | 12.62 | 5.07 |
November | 32707101.08 | 3143.08 | 04-NOV-15:01 | 17.30 | 12.80 | 91228269.97 | 56.69 | 03-NOV-03:20 | 17.30 | 12.80 |
December | 4765279.25 | 2043.67 | 17-DEC-16:01 | 9.82 | 4.16 | 92849698.03 | 56.69 | 22-DEC-04:19 | -3.5 | -6.3 |
Annual Sum or Average | 0.961871E+10 | 0.117655E+10 | ||||||||
Minimum of Months | 4673935.29 | 2043.67 | 4.22 | -0.7 | 84028465.14 | 56.69 | -3.5 | -6.3 | ||
Maximum of Months | 0.236522E+10 | 4055.86 | 24.40 | 21.27 | 0.107812E+09 | 90.99 | 22.80 | 21.60 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.136094E+09 | 2002.78 | 31-JAN-16:01 | -1.3 | -5.8 | 95508957.85 | 56.69 | 01-JAN-02:20 | -1.3 | -5.8 |
February | 0.199414E+09 | 2002.53 | 22-FEB-16:01 | 4.22 | -0.7 | 87128366.33 | 56.69 | 24-FEB-04:19 | 4.60 | 4.19 |
March | 0.357060E+09 | 2003.87 | 22-MAR-15:01 | 2.12 | -3.4 | 97130666.30 | 56.69 | 03-MAR-22:40 | 2.12 | -3.4 |
April | 0.492622E+09 | 2018.02 | 11-APR-15:01 | 15.00 | 5.16 | 94371320.34 | 56.69 | 07-APR-21:00 | 15.00 | 5.16 |
May | 0.751162E+09 | 2020.51 | 20-MAY-18:01 | 22.02 | 11.72 | 98463699.20 | 56.69 | 31-MAY-21:40 | 20.13 | 17.44 |
June | 0.111231E+10 | 1872.23 | 23-JUN-08:61 | 26.70 | 18.47 | 95775523.16 | 56.69 | 20-JUN-00:10 | 26.70 | 18.47 |
July | 0.145624E+10 | 1863.47 | 19-JUL-18:02 | 26.02 | 23.34 | 99084547.72 | 56.69 | 10-JUL-00:49 | 26.02 | 23.34 |
August | 0.164191E+10 | 1859.65 | 03-AUG-18:02 | 26.60 | 24.94 | 99167286.99 | 56.69 | 30-AUG-22:49 | 21.70 | 17.49 |
September | 0.122391E+10 | 2033.40 | 10-SEP-18:01 | 21.52 | 11.58 | 95610681.35 | 56.69 | 08-SEP-21:19 | 21.52 | 11.58 |
October | 0.109278E+10 | 2012.85 | 26-OCT-15:01 | 12.62 | 5.07 | 98603763.25 | 56.69 | 12-OCT-21:40 | 12.62 | 5.07 |
November | 0.336759E+09 | 1980.88 | 02-NOV-18:01 | 13.80 | 7.37 | 94135654.68 | 56.69 | 08-NOV-22:30 | 11.95 | 11.14 |
December | 0.225047E+09 | 1993.15 | 21-DEC-16:01 | 2.62 | -2.3 | 96104648.98 | 56.69 | 04-DEC-00:20 | 2.62 | -2.3 |
Annual Sum or Average | 0.902531E+10 | 0.115109E+10 | ||||||||
Minimum of Months | 0.136094E+09 | 1859.65 | -1.3 | -5.8 | 87128366.33 | 56.69 | -1.3 | -5.8 | ||
Maximum of Months | 0.164191E+10 | 2033.40 | 26.70 | 24.94 | 99167286.99 | 56.69 | 26.70 | 23.34 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.305105E+11 | 17490.99 | 23-JAN-23:00 | 10.60 | 10.26 | 0.185964E+11 | 11348.02 | 30-JAN-00:20 | -3.1 | -4.6 |
February | 0.274150E+11 | 16838.85 | 23-FEB-23:00 | 5.00 | 4.23 | 0.168077E+11 | 11347.99 | 27-FEB-00:20 | -0.9 | -4.8 |
March | 0.332813E+11 | 19222.97 | 27-MAR-21:04 | 14.13 | 10.87 | 0.190099E+11 | 11348.33 | 27-MAR-21:19 | 13.87 | 10.67 |
April | 0.347456E+11 | 20678.38 | 07-APR-21:10 | 19.22 | 13.77 | 0.184949E+11 | 11348.84 | 07-APR-22:10 | 18.22 | 13.39 |
May | 0.394091E+11 | 22014.52 | 31-MAY-21:52 | 19.90 | 17.35 | 0.192636E+11 | 11349.21 | 31-MAY-22:10 | 19.78 | 17.36 |
June | 0.416480E+11 | 23395.30 | 19-JUN-21:20 | 28.53 | 20.50 | 0.187338E+11 | 11349.21 | 20-JUN-22:10 | 20.60 | 17.54 |
July | 0.447144E+11 | 23491.26 | 11-JUL-18:03 | 26.73 | 16.72 | 0.192999E+11 | 11358.01 | 21-JUL-21:19 | 25.60 | 23.73 |
August | 0.444875E+11 | 23504.44 | 04-AUG-21:20 | 30.90 | 23.99 | 0.193730E+11 | 11357.91 | 16-AUG-21:19 | 26.50 | 25.09 |
September | 0.396423E+11 | 22618.97 | 01-SEP-21:10 | 26.60 | 18.09 | 0.186529E+11 | 11349.20 | 06-SEP-22:10 | 22.20 | 20.63 |
October | 0.373630E+11 | 20838.70 | 05-OCT-21:53 | 18.90 | 17.46 | 0.191527E+11 | 11348.99 | 04-OCT-22:10 | 18.90 | 17.46 |
November | 0.321621E+11 | 18937.21 | 03-NOV-22:00 | 12.80 | 10.33 | 0.182769E+11 | 11347.99 | 24-NOV-00:20 | -3.3 | -5.8 |
December | 0.312824E+11 | 17284.79 | 04-DEC-23:00 | 8.30 | 7.50 | 0.187365E+11 | 11347.98 | 22-DEC-00:20 | -3.3 | -6.0 |
Annual Sum or Average | 0.436661E+12 | 0.224398E+12 | ||||||||
Minimum of Months | 0.274150E+11 | 16838.85 | 5.00 | 4.23 | 0.168077E+11 | 11347.98 | -3.3 | -6.0 | ||
Maximum of Months | 0.447144E+11 | 23504.44 | 30.90 | 23.99 | 0.193730E+11 | 11358.01 | 26.50 | 25.09 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.340016E+11 | 19540.94 | 23-JAN-23:00 | 10.60 | 10.26 | 0.188617E+11 | 11348.10 | 03-JAN-04:19 | 10.60 | 10.26 |
February | 0.305116E+11 | 18838.40 | 23-FEB-23:00 | 5.00 | 4.23 | 0.170579E+11 | 11348.05 | 27-FEB-00:20 | -0.9 | -4.8 |
March | 0.370004E+11 | 21140.24 | 27-MAR-21:04 | 14.13 | 10.87 | 0.191889E+11 | 11348.36 | 27-MAR-21:19 | 13.87 | 10.67 |
April | 0.383545E+11 | 22318.31 | 07-APR-21:10 | 19.22 | 13.77 | 0.186158E+11 | 11348.85 | 07-APR-22:10 | 18.22 | 13.39 |
May | 0.429930E+11 | 23260.91 | 31-MAY-21:52 | 19.90 | 17.35 | 0.193129E+11 | 11349.21 | 31-MAY-22:10 | 19.78 | 17.36 |
June | 0.446410E+11 | 24647.70 | 19-JUN-21:20 | 28.53 | 20.50 | 0.187510E+11 | 11366.91 | 23-JUN-21:19 | 22.80 | 20.95 |
July | 0.476232E+11 | 24945.59 | 11-JUL-18:03 | 26.73 | 16.72 | 0.193070E+11 | 11369.85 | 21-JUL-21:19 | 25.60 | 23.73 |
August | 0.473372E+11 | 24713.49 | 04-AUG-21:20 | 30.90 | 23.99 | 0.193842E+11 | 11370.68 | 24-AUG-21:19 | 25.20 | 14.99 |
September | 0.426956E+11 | 23853.01 | 01-SEP-21:10 | 26.60 | 18.09 | 0.186850E+11 | 11354.11 | 13-SEP-21:19 | 24.07 | 22.30 |
October | 0.407479E+11 | 22213.90 | 05-OCT-21:53 | 18.90 | 17.46 | 0.192358E+11 | 11349.00 | 04-OCT-22:10 | 18.90 | 17.46 |
November | 0.357185E+11 | 20732.15 | 03-NOV-22:00 | 12.80 | 10.33 | 0.184555E+11 | 11348.06 | 24-NOV-00:20 | -3.3 | -5.8 |
December | 0.348762E+11 | 19296.23 | 04-DEC-23:00 | 8.30 | 7.50 | 0.189593E+11 | 11348.02 | 22-DEC-00:20 | -3.3 | -6.0 |
Annual Sum or Average | 0.476501E+12 | 0.225815E+12 | ||||||||
Minimum of Months | 0.305116E+11 | 18838.40 | 5.00 | 4.23 | 0.170579E+11 | 11348.02 | -3.3 | -6.0 | ||
Maximum of Months | 0.476232E+11 | 24945.59 | 30.90 | 23.99 | 0.193842E+11 | 11370.68 | 25.60 | 23.73 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.484030E+11 | 26771.56 | 17-JAN-11:50 | 9.13 | 4.92 | 0.187967E+11 | 11319.66 | 14-JAN-18:19 | 9.13 | 4.92 |
February | 0.439078E+11 | 27393.20 | 19-FEB-11:50 | 7.88 | 4.27 | 0.169764E+11 | 11319.64 | 18-FEB-18:19 | 7.88 | 4.27 |
March | 0.511459E+11 | 28348.20 | 29-MAR-10:33 | 8.17 | 4.49 | 0.188210E+11 | 11319.68 | 18-MAR-17:19 | 8.17 | 4.49 |
April | 0.515437E+11 | 30630.81 | 07-APR-17:01 | 25.55 | 16.06 | 0.182231E+11 | 11319.66 | 29-APR-17:19 | 11.50 | 9.80 |
May | 0.558186E+11 | 31243.56 | 29-MAY-10:33 | 27.43 | 17.92 | 0.188456E+11 | 11319.68 | 20-MAY-17:19 | 27.43 | 17.92 |
June | 0.560304E+11 | 31760.52 | 01-JUN-18:05 | 27.70 | 16.11 | 0.182552E+11 | 11319.69 | 17-JUN-17:19 | 22.60 | 20.38 |
July | 0.590507E+11 | 31445.95 | 09-JUL-10:40 | 29.60 | 25.14 | 0.188616E+11 | 11319.69 | 15-JUL-17:19 | 25.93 | 22.25 |
August | 0.592804E+11 | 31465.65 | 30-AUG-18:08 | 27.43 | 14.44 | 0.188696E+11 | 11319.69 | 19-AUG-17:19 | 27.43 | 14.44 |
September | 0.549785E+11 | 31235.55 | 04-SEP-10:37 | 25.60 | 17.74 | 0.182461E+11 | 11319.67 | 30-SEP-17:19 | 17.77 | 12.98 |
October | 0.545035E+11 | 29950.39 | 04-OCT-10:33 | 22.23 | 17.92 | 0.188375E+11 | 11319.60 | 07-OCT-17:19 | 11.33 | 4.89 |
November | 0.492098E+11 | 28694.48 | 04-NOV-10:45 | 17.02 | 11.62 | 0.182071E+11 | 11319.64 | 04-NOV-17:19 | 17.23 | 10.99 |
December | 0.491501E+11 | 27265.59 | 17-DEC-11:50 | 11.93 | 4.48 | 0.188043E+11 | 11319.63 | 23-DEC-18:19 | 3.90 | 2.48 |
Annual Sum or Average | 0.633023E+12 | 0.221744E+12 | ||||||||
Minimum of Months | 0.439078E+11 | 26771.56 | 7.88 | 4.27 | 0.169764E+11 | 11319.60 | 3.90 | 2.48 | ||
Maximum of Months | 0.592804E+11 | 31760.52 | 29.60 | 25.14 | 0.188696E+11 | 11319.69 | 27.43 | 22.25 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.274642E+10 | 3445.73 | 19-JAN-11:33 | 7.40 | 4.13 | 0.126926E+10 | 750.54 | 19-JAN-22:40 | 5.60 | 1.07 |
February | 0.274832E+10 | 3674.43 | 19-FEB-11:33 | 7.97 | 4.38 | 0.114843E+10 | 745.60 | 02-FEB-05:30 | 7.97 | 4.38 |
March | 0.601401E+10 | 4012.73 | 03-MAR-11:33 | 13.53 | 7.78 | 0.129300E+10 | 819.67 | 27-MAR-21:40 | 13.33 | 10.26 |
April | 0.760579E+10 | 4919.87 | 08-APR-10:33 | 23.90 | 16.13 | 0.130420E+10 | 902.83 | 07-APR-21:40 | 23.90 | 16.13 |
May | 0.958358E+10 | 5425.27 | 31-MAY-10:33 | 25.60 | 19.79 | 0.145314E+10 | 979.38 | 31-MAY-21:40 | 20.13 | 17.44 |
June | 0.107564E+11 | 6005.12 | 19-JUN-14:10 | 34.22 | 23.63 | 0.154962E+10 | 1007.39 | 19-JUN-21:19 | 28.53 | 20.50 |
July | 0.119959E+11 | 6694.95 | 11-JUL-16:50 | 28.30 | 17.35 | 0.165399E+10 | 1007.40 | 11-JUL-22:10 | 22.62 | 17.84 |
August | 0.122457E+11 | 6676.81 | 16-AUG-12:50 | 31.93 | 25.44 | 0.166413E+10 | 1007.39 | 02-AUG-21:19 | 31.93 | 25.44 |
September | 0.102734E+11 | 5963.70 | 01-SEP-14:10 | 31.02 | 17.36 | 0.150045E+10 | 1007.39 | 01-SEP-21:10 | 26.60 | 18.09 |
October | 0.926639E+10 | 4949.54 | 05-OCT-10:33 | 21.13 | 17.47 | 0.143117E+10 | 934.43 | 05-OCT-21:40 | 18.90 | 17.57 |
November | 0.571484E+10 | 4166.73 | 04-NOV-10:45 | 17.02 | 11.62 | 0.124744E+10 | 826.70 | 03-NOV-21:40 | 17.02 | 11.62 |
December | 0.375354E+10 | 3742.37 | 17-DEC-11:33 | 11.67 | 4.45 | 0.126990E+10 | 749.42 | 04-DEC-22:40 | 11.67 | 4.45 |
Annual Sum or Average | 0.927042E+11 | 0.167847E+11 | ||||||||
Minimum of Months | 0.274642E+10 | 3445.73 | 7.40 | 4.13 | 0.114843E+10 | 745.60 | 5.60 | 1.07 | ||
Maximum of Months | 0.122457E+11 | 6694.95 | 34.22 | 25.44 | 0.166413E+10 | 1007.40 | 31.93 | 25.44 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -9.6 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 5.97 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -9.6 | |
Maximum of Months | 0.00 | 0.00 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.324142E+09 | 1152.59 | 02-JAN-07:15 | -11.5 |
February | 0.207291E+09 | 1062.97 | 06-FEB-07:05 | -13.2 |
March | 17051879.21 | 352.55 | 17-MAR-06:30 | -1.1 |
April | 225399.61 | 45.87 | 02-APR-05:00 | 3.90 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 15577624.97 | 394.78 | 23-NOV-06:00 | -3.9 |
December | 0.112353E+09 | 525.03 | 30-DEC-17:00 | 1.70 |
Annual Sum or Average | 0.676640E+09 | |||
Minimum of Months | 0.00 | 0.00 | -13.2 | |
Maximum of Months | 0.324142E+09 | 1152.59 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -9.6 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 5.97 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -9.6 | |
Maximum of Months | 0.00 | 0.00 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 54068068.83 | 385.11 | 02-JAN-10:40 | -8.5 |
February | 67251968.35 | 380.34 | 06-FEB-15:00 | -7.2 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.40 |
December | 123275.54 | 49.26 | 31-DEC-18:00 | -5.0 |
Annual Sum or Average | 0.121443E+09 | |||
Minimum of Months | 0.00 | 0.00 | -8.5 | |
Maximum of Months | 67251968.35 | 385.11 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.159569E+09 | 401.43 | 02-JAN-05:00 | -12.2 |
February | 0.155814E+09 | 406.45 | 06-FEB-16:00 | -7.2 |
March | 3148629.86 | 115.19 | 17-MAR-12:30 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 5369163.07 | 85.29 | 23-NOV-18:00 | 0.00 |
December | 17731270.06 | 202.40 | 31-DEC-18:00 | -5.0 |
Annual Sum or Average | 0.341632E+09 | |||
Minimum of Months | 0.00 | 0.00 | -12.2 | |
Maximum of Months | 0.159569E+09 | 406.45 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -9.6 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 5.97 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -9.6 | |
Maximum of Months | 0.00 | 0.00 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 165721.08 | 65.25 | 08-JAN-15:50 | -1.3 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 5.97 |
Annual Sum or Average | 165721.08 | |||
Minimum of Months | 0.00 | 0.00 | -1.3 | |
Maximum of Months | 165721.08 | 65.25 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -9.6 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 5.97 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -9.6 | |
Maximum of Months | 0.00 | 0.00 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.982496E+09 | 1509.18 | 08-JAN-16:13 | -0.9 |
February | 0.786401E+09 | 1495.35 | 06-FEB-19:13 | -8.1 |
March | 0.307761E+09 | 1469.54 | 16-MAR-15:02 | 0.68 |
April | 0.114002E+09 | 1424.07 | 21-APR-15:02 | 7.30 |
May | 4969470.74 | 1413.11 | 03-MAY-15:04 | 15.92 |
June | 1389593.52 | 978.23 | 11-JUN-18:04 | 18.40 |
July | 899193.45 | 812.09 | 24-JUL-08:04 | 22.07 |
August | 1119347.33 | 1066.17 | 08-AUG-08:04 | 21.47 |
September | 2792960.61 | 1314.08 | 23-SEP-15:04 | 16.60 |
October | 13322253.56 | 1267.89 | 23-OCT-15:04 | 18.80 |
November | 0.375074E+09 | 1465.03 | 25-NOV-16:02 | 4.32 |
December | 0.739688E+09 | 1479.69 | 11-DEC-16:13 | 1.10 |
Annual Sum or Average | 0.332991E+10 | |||
Minimum of Months | 899193.45 | 812.09 | -8.1 | |
Maximum of Months | 0.982496E+09 | 1509.18 | 22.07 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.120292E+10 | 1509.55 | 08-JAN-16:13 | -0.9 |
February | 0.105843E+10 | 1512.86 | 06-FEB-09:13 | -11.8 |
March | 0.420187E+09 | 1470.44 | 16-MAR-15:02 | 0.68 |
April | 0.135554E+09 | 1422.43 | 21-APR-15:02 | 7.30 |
May | 5178012.02 | 1563.94 | 03-MAY-15:04 | 15.92 |
June | 542685.33 | 664.99 | 05-JUN-08:54 | 19.40 |
July | 503395.78 | 793.78 | 18-JUL-08:04 | 24.32 |
August | 440327.26 | 632.77 | 25-AUG-08:54 | 20.60 |
September | 2106977.68 | 1421.74 | 23-SEP-15:04 | 16.60 |
October | 28292246.24 | 1358.08 | 26-OCT-08:03 | 12.38 |
November | 0.514883E+09 | 1472.31 | 25-NOV-16:02 | 4.32 |
December | 0.971597E+09 | 1476.27 | 11-DEC-16:13 | 1.10 |
Annual Sum or Average | 0.434064E+10 | |||
Minimum of Months | 440327.26 | 632.77 | -11.8 | |
Maximum of Months | 0.120292E+10 | 1563.94 | 24.32 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -9.6 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 5.97 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -9.6 | |
Maximum of Months | 0.00 | 0.00 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.123750E+09 | 435.10 | 02-JAN-16:02 | -6.0 |
February | 0.126651E+09 | 436.79 | 06-FEB-16:02 | -7.1 |
March | 14808411.36 | 418.18 | 07-MAR-16:03 | 7.93 |
April | 1460014.94 | 420.21 | 06-APR-15:04 | 16.93 |
May | 391711.54 | 415.32 | 23-MAY-15:06 | 15.68 |
June | 63895.56 | 247.01 | 06-JUN-15:06 | 18.98 |
July | 46543.47 | 122.42 | 14-JUL-08:07 | 27.98 |
August | 70937.11 | 184.49 | 05-AUG-18:07 | 24.40 |
September | 405179.70 | 324.68 | 24-SEP-15:06 | 17.70 |
October | 981060.12 | 421.85 | 07-OCT-15:05 | 12.30 |
November | 22886678.29 | 421.07 | 24-NOV-16:01 | 1.20 |
December | 60257912.84 | 420.08 | 15-DEC-16:01 | 4.32 |
Annual Sum or Average | 0.351774E+09 | |||
Minimum of Months | 46543.47 | 122.42 | -7.1 | |
Maximum of Months | 0.126651E+09 | 436.79 | 27.98 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.975091E+09 | 1472.55 | 08-JAN-16:13 | -0.9 |
February | 0.763903E+09 | 1446.74 | 06-FEB-19:13 | -8.1 |
March | 0.329395E+09 | 1441.03 | 16-MAR-15:02 | 0.68 |
April | 0.118111E+09 | 1396.94 | 21-APR-15:02 | 7.30 |
May | 4763175.71 | 1326.86 | 19-MAY-15:04 | 16.78 |
June | 650925.69 | 1056.19 | 08-JUN-08:04 | 22.70 |
July | 202835.76 | 408.10 | 18-JUL-08:04 | 24.32 |
August | 102285.82 | 584.47 | 07-AUG-08:05 | 20.28 |
September | 2074325.34 | 1170.81 | 23-SEP-15:04 | 16.60 |
October | 13986887.04 | 1076.11 | 22-OCT-18:04 | 17.70 |
November | 0.350698E+09 | 1440.63 | 25-NOV-16:02 | 4.32 |
December | 0.731768E+09 | 1446.96 | 12-DEC-16:02 | 4.82 |
Annual Sum or Average | 0.329075E+10 | |||
Minimum of Months | 102285.82 | 408.10 | -8.1 | |
Maximum of Months | 0.975091E+09 | 1472.55 | 24.32 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.118664E+10 | 1473.19 | 08-JAN-16:13 | -0.9 |
February | 0.102144E+10 | 1469.95 | 13-FEB-16:01 | -3.4 |
March | 0.444473E+09 | 1441.23 | 16-MAR-15:02 | 0.68 |
April | 0.139350E+09 | 1395.28 | 21-APR-15:02 | 7.30 |
May | 4771216.26 | 1498.73 | 03-MAY-15:04 | 15.92 |
June | 344429.61 | 862.86 | 07-JUN-21:54 | 22.80 |
July | 245778.44 | 590.15 | 22-JUL-21:54 | 23.90 |
August | 41881.55 | 286.39 | 30-AUG-21:55 | 21.70 |
September | 1422653.22 | 1328.65 | 25-SEP-15:04 | 18.03 |
October | 31597344.08 | 1309.80 | 10-OCT-15:04 | 19.32 |
November | 0.465455E+09 | 1461.64 | 23-NOV-16:01 | 1.52 |
December | 0.937960E+09 | 1452.68 | 15-DEC-16:01 | 4.32 |
Annual Sum or Average | 0.423375E+10 | |||
Minimum of Months | 41881.55 | 286.39 | -3.4 | |
Maximum of Months | 0.118664E+10 | 1498.73 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 46823163.05 | 668.25 | 14-JAN-16:30 | -6.1 |
February | 16901318.13 | 421.22 | 06-FEB-07:10 | -13.2 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.40 |
December | 10321381.14 | 280.46 | 11-DEC-15:00 | 1.10 |
Annual Sum or Average | 74045862.32 | |||
Minimum of Months | 0.00 | 0.00 | -13.2 | |
Maximum of Months | 46823163.05 | 668.25 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.145804E+10 | 1799.87 | 08-JAN-16:13 | -0.9 |
February | 0.120098E+10 | 1792.14 | 06-FEB-19:13 | -8.1 |
March | 0.538872E+09 | 1736.60 | 16-MAR-15:02 | 0.68 |
April | 0.227735E+09 | 1705.27 | 21-APR-15:02 | 7.30 |
May | 13992143.69 | 1506.96 | 03-MAY-15:04 | 15.92 |
June | 1357171.54 | 1053.24 | 08-JUN-08:04 | 22.70 |
July | 912343.76 | 783.65 | 18-JUL-08:04 | 24.32 |
August | 1266808.77 | 956.62 | 29-AUG-08:04 | 21.47 |
September | 3734785.89 | 1370.38 | 23-SEP-15:04 | 16.60 |
October | 54401887.96 | 1210.71 | 23-OCT-15:04 | 18.80 |
November | 0.637853E+09 | 1732.79 | 25-NOV-16:02 | 4.32 |
December | 0.115271E+10 | 1767.14 | 11-DEC-16:13 | 1.10 |
Annual Sum or Average | 0.529187E+10 | |||
Minimum of Months | 912343.76 | 783.65 | -8.1 | |
Maximum of Months | 0.145804E+10 | 1799.87 | 24.32 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.172845E+10 | 1796.94 | 08-JAN-16:13 | -0.9 |
February | 0.153234E+10 | 1803.55 | 06-FEB-16:13 | -7.0 |
March | 0.692936E+09 | 1738.17 | 16-MAR-15:02 | 0.68 |
April | 0.262113E+09 | 1700.76 | 21-APR-15:02 | 7.30 |
May | 14208090.52 | 1623.89 | 03-MAY-15:04 | 15.92 |
June | 473229.27 | 915.19 | 07-JUN-21:54 | 22.80 |
July | 502300.49 | 818.92 | 18-JUL-08:04 | 24.32 |
August | 595211.88 | 731.72 | 01-AUG-06:54 | 25.60 |
September | 3087217.12 | 1482.02 | 23-SEP-15:04 | 16.60 |
October | 97048634.68 | 1641.06 | 29-OCT-08:62 | 6.88 |
November | 0.832363E+09 | 1739.19 | 25-NOV-16:02 | 4.32 |
December | 0.144514E+10 | 1760.87 | 11-DEC-16:13 | 1.10 |
Annual Sum or Average | 0.660926E+10 | |||
Minimum of Months | 473229.27 | 731.72 | -7.0 | |
Maximum of Months | 0.172845E+10 | 1803.55 | 25.60 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.411887E+09 | 931.03 | 14-JAN-16:15 | -6.1 |
February | 0.286253E+09 | 918.78 | 27-FEB-16:13 | 0.60 |
March | 0.120648E+09 | 904.39 | 16-MAR-15:02 | 0.68 |
April | 48914473.01 | 878.29 | 21-APR-15:02 | 7.30 |
May | 2441599.14 | 880.17 | 23-MAY-15:04 | 15.68 |
June | 547088.73 | 519.93 | 01-JUN-08:04 | 19.13 |
July | 512440.47 | 493.40 | 18-JUL-08:04 | 24.32 |
August | 479876.03 | 510.91 | 08-AUG-08:04 | 21.47 |
September | 821327.11 | 706.22 | 23-SEP-15:04 | 16.60 |
October | 2382416.71 | 628.25 | 06-OCT-18:04 | 14.90 |
November | 0.102192E+09 | 872.11 | 28-NOV-16:02 | 9.32 |
December | 0.278002E+09 | 919.64 | 11-DEC-16:13 | 1.10 |
Annual Sum or Average | 0.125508E+10 | |||
Minimum of Months | 479876.03 | 493.40 | -6.1 | |
Maximum of Months | 0.411887E+09 | 931.03 | 24.32 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -9.6 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 5.97 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -9.6 | |
Maximum of Months | 0.00 | 0.00 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -9.6 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 5.97 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -9.6 | |
Maximum of Months | 0.00 | 0.00 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -9.6 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 5.97 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -9.6 | |
Maximum of Months | 0.00 | 0.00 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.253959E+09 | 2006.78 | 02-JAN-07:10 | -11.6 |
February | 0.189106E+09 | 1953.83 | 06-FEB-07:10 | -13.2 |
March | 605939.42 | 309.88 | 23-MAR-06:10 | -4.7 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 4166794.13 | 329.03 | 23-NOV-05:50 | -3.9 |
December | 4199688.45 | 313.44 | 31-DEC-18:00 | -5.0 |
Annual Sum or Average | 0.452037E+09 | |||
Minimum of Months | 0.00 | 0.00 | -13.2 | |
Maximum of Months | 0.253959E+09 | 2006.78 | 23.90 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.136942E+11 | 13190.31 | 02-JAN-20:10 | 0.121516E+11 | 9632.53 | 02-JAN-20:10 |
February | 0.123646E+11 | 13190.31 | 01-FEB-20:10 | 0.109726E+11 | 9632.53 | 01-FEB-20:10 |
March | 0.137364E+11 | 13190.31 | 01-MAR-20:10 | 0.121771E+11 | 9632.53 | 01-MAR-20:10 |
April | 0.132299E+11 | 13190.31 | 03-APR-19:10 | 0.117446E+11 | 9632.53 | 03-APR-19:10 |
May | 0.137180E+11 | 13190.31 | 01-MAY-19:10 | 0.121662E+11 | 9632.53 | 01-MAY-19:10 |
June | 0.132906E+11 | 13190.31 | 01-JUN-19:10 | 0.117829E+11 | 9632.53 | 01-JUN-19:10 |
July | 0.136573E+11 | 13190.31 | 03-JUL-19:10 | 0.121279E+11 | 9632.53 | 03-JUL-19:10 |
August | 0.137417E+11 | 13190.31 | 01-AUG-19:10 | 0.121808E+11 | 9632.53 | 01-AUG-19:10 |
September | 0.132352E+11 | 13190.31 | 01-SEP-19:10 | 0.117482E+11 | 9632.53 | 01-SEP-19:10 |
October | 0.136889E+11 | 13190.31 | 02-OCT-19:10 | 0.121479E+11 | 9632.53 | 02-OCT-19:10 |
November | 0.132800E+11 | 13190.31 | 01-NOV-19:10 | 0.117774E+11 | 9632.53 | 01-NOV-19:10 |
December | 0.136573E+11 | 13190.31 | 01-DEC-20:10 | 0.121279E+11 | 9632.53 | 01-DEC-20:10 |
Annual Sum or Average | 0.161294E+12 | 0.143105E+12 | ||||
Minimum of Months | 0.123646E+11 | 13190.31 | 0.109726E+11 | 9632.53 | ||
Maximum of Months | 0.137417E+11 | 13190.31 | 0.121808E+11 | 9632.53 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.620421E+09 | 597.59 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.560184E+09 | 597.59 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.622334E+09 | 597.59 | 01-MAR-20:10 | 0.866718E+09 | 685.60 | 01-MAR-20:10 |
April | 0.599386E+09 | 597.59 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.621497E+09 | 597.59 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.602135E+09 | 597.59 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.618748E+09 | 597.59 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.622573E+09 | 597.59 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.599625E+09 | 597.59 | 01-SEP-19:10 | 0.836191E+09 | 685.60 | 01-SEP-19:10 |
October | 0.620182E+09 | 597.59 | 02-OCT-19:10 | 0.864640E+09 | 685.60 | 02-OCT-19:10 |
November | 0.601657E+09 | 597.59 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.618748E+09 | 597.59 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.730749E+10 | 0.101856E+11 | ||||
Minimum of Months | 0.560184E+09 | 597.59 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.622573E+09 | 597.59 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.718450E+09 | 692.02 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.648695E+09 | 692.02 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.720665E+09 | 692.02 | 01-MAR-20:10 | 0.100366E+10 | 793.93 | 01-MAR-20:10 |
April | 0.694091E+09 | 692.02 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.719696E+09 | 692.02 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.697275E+09 | 692.02 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.716513E+09 | 692.02 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.720942E+09 | 692.02 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.694368E+09 | 692.02 | 01-SEP-19:10 | 0.968312E+09 | 793.93 | 01-SEP-19:10 |
October | 0.718174E+09 | 692.02 | 02-OCT-19:10 | 0.100126E+10 | 793.93 | 02-OCT-19:10 |
November | 0.696721E+09 | 692.02 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.716513E+09 | 692.02 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.846210E+10 | 0.117950E+11 | ||||
Minimum of Months | 0.648695E+09 | 692.02 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.720942E+09 | 692.02 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.710312E+09 | 684.18 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.641347E+09 | 684.18 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.712502E+09 | 684.18 | 01-MAR-20:10 | 0.106120E+10 | 839.45 | 01-MAR-20:10 |
April | 0.686229E+09 | 684.18 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.711544E+09 | 684.18 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.689376E+09 | 684.18 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.708397E+09 | 684.18 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.712775E+09 | 684.18 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.686503E+09 | 684.18 | 01-SEP-19:10 | 0.102382E+10 | 839.45 | 01-SEP-19:10 |
October | 0.710039E+09 | 684.18 | 02-OCT-19:10 | 0.105866E+10 | 839.45 | 02-OCT-19:10 |
November | 0.688829E+09 | 684.18 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.708397E+09 | 684.18 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.836625E+10 | 0.124712E+11 | ||||
Minimum of Months | 0.641347E+09 | 684.18 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.712775E+09 | 684.18 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.261454E+09 | 251.84 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.236069E+09 | 251.84 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.262260E+09 | 251.84 | 01-MAR-20:10 | 0.306128E+09 | 242.16 | 01-MAR-20:10 |
April | 0.252589E+09 | 251.84 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.261907E+09 | 251.84 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.253748E+09 | 251.84 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.260749E+09 | 251.84 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.262360E+09 | 251.84 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.252690E+09 | 251.84 | 01-SEP-19:10 | 0.295345E+09 | 242.16 | 01-SEP-19:10 |
October | 0.261353E+09 | 251.84 | 02-OCT-19:10 | 0.305393E+09 | 242.16 | 02-OCT-19:10 |
November | 0.253546E+09 | 251.84 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.260749E+09 | 251.84 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.307947E+10 | 0.359760E+10 | ||||
Minimum of Months | 0.236069E+09 | 251.84 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.262360E+09 | 251.84 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.337502E+09 | 325.08 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.304733E+09 | 325.08 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.338542E+09 | 325.08 | 01-MAR-20:10 | 0.578079E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.326059E+09 | 325.08 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.338087E+09 | 325.08 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.327554E+09 | 325.08 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.336592E+09 | 325.08 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.338672E+09 | 325.08 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.326189E+09 | 325.08 | 01-SEP-19:10 | 0.557718E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.337372E+09 | 325.08 | 02-OCT-19:10 | 0.576693E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.327294E+09 | 325.08 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.336592E+09 | 325.08 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.397519E+10 | 0.679355E+11 | ||||
Minimum of Months | 0.304733E+09 | 325.08 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.338672E+09 | 325.08 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.137273E+10 | 1701.53 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.117378E+10 | 1701.53 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.123424E+10 | 1701.53 | 01-MAR-20:10 | 0.122027E+10 | 965.27 | 01-MAR-20:10 |
April | 0.111384E+10 | 1701.53 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.104671E+10 | 1701.53 | 01-MAY-19:10 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.982301E+09 | 1701.53 | 01-JUN-19:19 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.102016E+10 | 1701.53 | 03-JUL-19:19 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.110585E+10 | 1701.53 | 01-AUG-19:10 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.116008E+10 | 1701.53 | 01-SEP-19:10 | 0.117729E+10 | 965.27 | 01-SEP-19:10 |
October | 0.128273E+10 | 1701.53 | 02-OCT-19:10 | 0.121734E+10 | 965.27 | 02-OCT-19:10 |
November | 0.128666E+10 | 1701.53 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.136102E+10 | 1701.53 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.141401E+11 | 0.143405E+11 | ||||
Minimum of Months | 0.982301E+09 | 1701.53 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.137273E+10 | 1701.53 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.949800E+10 | 9504.80 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.850654E+10 | 9504.80 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.939272E+10 | 9504.80 | 01-MAR-20:10 | 0.126786E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.898322E+10 | 9504.80 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.921372E+10 | 9504.80 | 01-MAY-19:10 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.890018E+10 | 9504.80 | 01-JUN-19:10 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.915875E+10 | 9504.80 | 03-JUL-19:19 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.927464E+10 | 9504.80 | 01-AUG-19:10 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.902359E+10 | 9504.80 | 01-SEP-19:10 | 0.122320E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.939694E+10 | 9504.80 | 02-OCT-19:10 | 0.126482E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.915818E+10 | 9504.80 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.945942E+10 | 9504.80 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.109966E+12 | 0.148998E+12 | ||||
Minimum of Months | 0.850654E+10 | 9504.80 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.949800E+10 | 9504.80 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196602E+09 | 177.88 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.177551E+09 | 177.88 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.195039E+09 | 177.88 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.190486E+09 | 177.88 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.195821E+09 | 177.88 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.188975E+09 | 177.88 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.197358E+09 | 177.88 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.195039E+09 | 177.88 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.190538E+09 | 177.88 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.196576E+09 | 177.88 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.189731E+09 | 177.88 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.197383E+09 | 177.88 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.231110E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.177551E+09 | 177.88 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.197383E+09 | 177.88 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196579E+09 | 177.86 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.177530E+09 | 177.86 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.195017E+09 | 177.86 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.190464E+09 | 177.86 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.195798E+09 | 177.86 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.188953E+09 | 177.86 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.197334E+09 | 177.86 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.195017E+09 | 177.86 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.190515E+09 | 177.86 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.196553E+09 | 177.86 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.189708E+09 | 177.86 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.197360E+09 | 177.86 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.231083E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.177530E+09 | 177.86 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.197360E+09 | 177.86 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123557E+09 | 111.79 | 01-JAN-19:10 | 0.217935E+09 | 232.19 | 01-JAN-08:09 |
February | 0.111584E+09 | 111.79 | 01-FEB-20:10 | 0.196843E+09 | 232.19 | 01-FEB-07:10 |
March | 0.122575E+09 | 111.79 | 01-MAR-20:10 | 0.217824E+09 | 232.19 | 01-MAR-07:10 |
April | 0.119713E+09 | 111.79 | 01-APR-18:10 | 0.210923E+09 | 232.19 | 01-APR-07:10 |
May | 0.123066E+09 | 111.79 | 01-MAY-19:10 | 0.217879E+09 | 232.19 | 01-MAY-06:10 |
June | 0.118764E+09 | 111.79 | 01-JUN-19:10 | 0.210812E+09 | 232.19 | 01-JUN-06:10 |
July | 0.124032E+09 | 111.79 | 01-JUL-18:10 | 0.217991E+09 | 232.19 | 01-JUL-07:10 |
August | 0.122575E+09 | 111.79 | 01-AUG-19:10 | 0.217824E+09 | 232.19 | 01-AUG-06:10 |
September | 0.119746E+09 | 111.79 | 01-SEP-19:10 | 0.210923E+09 | 232.19 | 01-SEP-06:10 |
October | 0.123541E+09 | 111.79 | 01-OCT-18:10 | 0.217935E+09 | 232.19 | 01-OCT-07:10 |
November | 0.119238E+09 | 111.79 | 01-NOV-19:10 | 0.210867E+09 | 232.19 | 01-NOV-06:10 |
December | 0.124048E+09 | 111.79 | 01-DEC-20:10 | 0.217991E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.145244E+10 | 0.256575E+10 | ||||
Minimum of Months | 0.111584E+09 | 111.79 | 0.196843E+09 | 232.19 | ||
Maximum of Months | 0.124048E+09 | 111.79 | 0.217991E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123591E+09 | 111.82 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 0.111614E+09 | 111.82 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 0.122608E+09 | 111.82 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 0.119746E+09 | 111.82 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 0.123099E+09 | 111.82 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 0.118796E+09 | 111.82 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 0.124066E+09 | 111.82 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 0.122608E+09 | 111.82 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 0.119778E+09 | 111.82 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 0.123574E+09 | 111.82 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 0.119271E+09 | 111.82 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 0.124082E+09 | 111.82 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.145283E+10 | 0.256645E+10 | ||||
Minimum of Months | 0.111614E+09 | 111.82 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 0.124082E+09 | 111.82 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196602E+09 | 177.88 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.177551E+09 | 177.88 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.195039E+09 | 177.88 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.190486E+09 | 177.88 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.195821E+09 | 177.88 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.188975E+09 | 177.88 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.197358E+09 | 177.88 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.195039E+09 | 177.88 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.190538E+09 | 177.88 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.196576E+09 | 177.88 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.189731E+09 | 177.88 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.197383E+09 | 177.88 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.231110E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.177551E+09 | 177.88 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.197383E+09 | 177.88 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196579E+09 | 177.86 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.177530E+09 | 177.86 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.195017E+09 | 177.86 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.190464E+09 | 177.86 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.195798E+09 | 177.86 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.188953E+09 | 177.86 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.197334E+09 | 177.86 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.195017E+09 | 177.86 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.190515E+09 | 177.86 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.196553E+09 | 177.86 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.189708E+09 | 177.86 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.197360E+09 | 177.86 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.231083E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.177530E+09 | 177.86 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.197360E+09 | 177.86 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.193865E+10 | 1867.32 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.175042E+10 | 1867.32 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.194462E+10 | 1867.32 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.187292E+10 | 1867.32 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.194201E+10 | 1867.32 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.188151E+10 | 1867.32 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.193342E+10 | 1867.32 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.194537E+10 | 1867.32 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.187367E+10 | 1867.32 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.193790E+10 | 1867.32 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.188002E+10 | 1867.32 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.193342E+10 | 1867.32 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.228339E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.175042E+10 | 1867.32 | 0.00 | 0.00 | |
Maximum of Months | 0.194537E+10 | 1867.32 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196602E+09 | 177.88 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.177551E+09 | 177.88 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.195039E+09 | 177.88 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.190486E+09 | 177.88 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.195821E+09 | 177.88 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.188975E+09 | 177.88 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.197358E+09 | 177.88 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.195039E+09 | 177.88 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.190538E+09 | 177.88 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.196576E+09 | 177.88 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.189731E+09 | 177.88 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.197383E+09 | 177.88 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.231110E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.177551E+09 | 177.88 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.197383E+09 | 177.88 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196579E+09 | 177.86 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.177530E+09 | 177.86 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.195017E+09 | 177.86 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.190464E+09 | 177.86 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.195798E+09 | 177.86 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.188953E+09 | 177.86 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.197334E+09 | 177.86 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.195017E+09 | 177.86 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.190515E+09 | 177.86 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.196553E+09 | 177.86 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.189708E+09 | 177.86 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.197360E+09 | 177.86 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.231083E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.177530E+09 | 177.86 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.197360E+09 | 177.86 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123591E+09 | 111.82 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 0.111614E+09 | 111.82 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 0.122608E+09 | 111.82 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 0.119746E+09 | 111.82 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 0.123099E+09 | 111.82 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 0.118796E+09 | 111.82 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 0.124066E+09 | 111.82 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 0.122608E+09 | 111.82 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 0.119778E+09 | 111.82 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 0.123574E+09 | 111.82 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 0.119271E+09 | 111.82 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 0.124082E+09 | 111.82 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.145283E+10 | 0.256645E+10 | ||||
Minimum of Months | 0.111614E+09 | 111.82 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 0.124082E+09 | 111.82 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.281023E+10 | 2988.03 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.247315E+10 | 2988.03 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.266201E+10 | 2988.03 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.247582E+10 | 2988.03 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.244548E+10 | 2988.03 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.233263E+10 | 2988.03 | 01-JUN-19:19 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.241252E+10 | 2988.03 | 03-JUL-19:30 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.250998E+10 | 2988.03 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.252766E+10 | 2988.03 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.269856E+10 | 2988.03 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.267468E+10 | 2988.03 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.281967E+10 | 2988.03 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.308424E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.233263E+10 | 2988.03 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.281967E+10 | 2988.03 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.281023E+10 | 2988.03 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.247315E+10 | 2988.03 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.266201E+10 | 2988.03 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.247582E+10 | 2988.03 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.244548E+10 | 2988.03 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.233263E+10 | 2988.03 | 01-JUN-19:19 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.241252E+10 | 2988.03 | 03-JUL-19:30 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.250998E+10 | 2988.03 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.252766E+10 | 2988.03 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.269856E+10 | 2988.03 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.267468E+10 | 2988.03 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.281967E+10 | 2988.03 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.308424E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.233263E+10 | 2988.03 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.281967E+10 | 2988.03 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.110133E+10 | 1060.81 | 02-JAN-20:10 | 0.368383E+11 | 16487.34 | 01-JAN-07:10 |
February | 0.994402E+09 | 1060.81 | 01-FEB-20:10 | 0.332733E+11 | 16487.34 | 01-FEB-07:10 |
March | 0.110473E+10 | 1060.81 | 01-MAR-20:10 | 0.368383E+11 | 16487.34 | 01-MAR-07:10 |
April | 0.106399E+10 | 1060.81 | 03-APR-19:10 | 0.356500E+11 | 16487.34 | 01-APR-06:10 |
May | 0.110324E+10 | 1060.81 | 01-MAY-19:10 | 0.368383E+11 | 16487.34 | 01-MAY-06:10 |
June | 0.106887E+10 | 1060.81 | 01-JUN-19:10 | 0.356500E+11 | 16487.34 | 01-JUN-06:10 |
July | 0.109836E+10 | 1060.81 | 03-JUL-19:10 | 0.368383E+11 | 16487.34 | 01-JUL-06:10 |
August | 0.110515E+10 | 1060.81 | 01-AUG-19:10 | 0.368383E+11 | 16487.34 | 01-AUG-06:10 |
September | 0.106442E+10 | 1060.81 | 01-SEP-19:10 | 0.356500E+11 | 16487.34 | 01-SEP-06:10 |
October | 0.110091E+10 | 1060.81 | 02-OCT-19:10 | 0.368383E+11 | 16487.34 | 01-OCT-06:10 |
November | 0.106802E+10 | 1060.81 | 01-NOV-19:10 | 0.356500E+11 | 16487.34 | 01-NOV-06:10 |
December | 0.109836E+10 | 1060.81 | 01-DEC-20:10 | 0.368383E+11 | 16487.34 | 01-DEC-07:10 |
Annual Sum or Average | 0.129718E+11 | 0.433742E+12 | ||||
Minimum of Months | 0.994402E+09 | 1060.81 | 0.332733E+11 | 16487.34 | ||
Maximum of Months | 0.110515E+10 | 1060.81 | 0.368383E+11 | 16487.34 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.205176E+10 | 1976.27 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.185255E+10 | 1976.27 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.205809E+10 | 1976.27 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.198220E+10 | 1976.27 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.205532E+10 | 1976.27 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.199129E+10 | 1976.27 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.204623E+10 | 1976.27 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.205888E+10 | 1976.27 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.198299E+10 | 1976.27 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.205097E+10 | 1976.27 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.198971E+10 | 1976.27 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.204623E+10 | 1976.27 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.241662E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.185255E+10 | 1976.27 | 0.00 | 0.00 | |
Maximum of Months | 0.205888E+10 | 1976.27 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.136942E+11 | 0.121516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.123646E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196682E+11 | 0.137364E+11 | 0.121771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.132299E+11 | 0.117446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.137180E+11 | 0.121662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.132906E+11 | 0.117829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.136573E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.137417E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189689E+11 | 0.132352E+11 | 0.117482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195854E+11 | 0.136889E+11 | 0.121479E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.132800E+11 | 0.117774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.136573E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230861E+12 | 0.161294E+12 | 0.143105E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.176991E+11 | 0.123646E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196682E+11 | 0.137417E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.620421E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310129E+09 |
February | 0.179968E+10 | 0.560184E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299181E+09 |
March | 0.199990E+10 | 0.622334E+09 | 0.866718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240534E+09 |
April | 0.192973E+10 | 0.599386E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 277132.79 | 0.153417E+09 |
May | 0.199475E+10 | 0.621497E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2072575.90 | 86015891.33 |
June | 0.193394E+10 | 0.602135E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11825112.77 | 24466047.68 |
July | 0.199054E+10 | 0.618748E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30763738.80 | 3046311.01 |
August | 0.199896E+10 | 0.622573E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30178968.00 | 9822929.18 |
September | 0.192879E+10 | 0.599625E+09 | 0.836191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4770413.50 | 42616639.62 |
October | 0.199148E+10 | 0.620182E+09 | 0.864640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 67360.04 | 0.124261E+09 |
November | 0.192552E+10 | 0.601657E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205134E+09 |
December | 0.199054E+10 | 0.618748E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.271811E+09 |
Annual Sum or Average | 0.234744E+11 | 0.730749E+10 | 0.101856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 79955301.80 | 0.177043E+10 |
Minimum of Months | 0.179968E+10 | 0.560184E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3046311.01 |
Maximum of Months | 0.199990E+10 | 0.622573E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30763738.80 | 0.310129E+09 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.718450E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121831E+09 |
February | 0.208403E+10 | 0.648695E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117438E+09 |
March | 0.231589E+10 | 0.720665E+09 | 0.100366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 140.50 | 96827321.86 |
April | 0.223463E+10 | 0.694091E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 173076.63 | 64244211.00 |
May | 0.230993E+10 | 0.719696E+09 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 892648.76 | 39488869.11 |
June | 0.223950E+10 | 0.697275E+09 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4394964.74 | 13796083.07 |
July | 0.230505E+10 | 0.716513E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10718080.06 | 3102866.67 |
August | 0.231480E+10 | 0.720942E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11434816.51 | 5870887.98 |
September | 0.223354E+10 | 0.694368E+09 | 0.968312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1920566.98 | 20720612.48 |
October | 0.230614E+10 | 0.718174E+09 | 0.100126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 71161.94 | 52418503.42 |
November | 0.222975E+10 | 0.696721E+09 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83489327.73 |
December | 0.230505E+10 | 0.716513E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107924E+09 |
Annual Sum or Average | 0.271834E+11 | 0.846210E+10 | 0.117950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 29605456.13 | 0.727151E+09 |
Minimum of Months | 0.208403E+10 | 0.648695E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3102866.67 |
Maximum of Months | 0.231589E+10 | 0.720942E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11434816.51 | 0.121831E+09 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.487480E+09 | 0.710312E+09 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281031E+09 |
February | 0.440737E+09 | 0.641347E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269981E+09 |
March | 0.489771E+09 | 0.712502E+09 | 0.106120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12727.15 | 0.216594E+09 |
April | 0.472586E+09 | 0.686229E+09 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 621263.31 | 0.141483E+09 |
May | 0.488511E+09 | 0.711544E+09 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2255934.13 | 86997237.57 |
June | 0.473617E+09 | 0.689376E+09 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10283696.62 | 30724828.78 |
July | 0.487480E+09 | 0.708397E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24537222.09 | 6826523.05 |
August | 0.489542E+09 | 0.712775E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26791345.45 | 13255581.08 |
September | 0.472357E+09 | 0.686503E+09 | 0.102382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4682016.83 | 46090787.22 |
October | 0.487709E+09 | 0.710039E+09 | 0.105866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 306259.16 | 0.114925E+09 |
November | 0.471555E+09 | 0.688829E+09 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187843E+09 |
December | 0.487480E+09 | 0.708397E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245308E+09 |
Annual Sum or Average | 0.574883E+10 | 0.836625E+10 | 0.124712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 69490464.74 | 0.164106E+10 |
Minimum of Months | 0.440737E+09 | 0.641347E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6826523.05 |
Maximum of Months | 0.489771E+09 | 0.712775E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26791345.45 | 0.281031E+09 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.374985E+09 | 0.261454E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161936E+09 |
February | 0.339028E+09 | 0.236069E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155603E+09 |
March | 0.376747E+09 | 0.262260E+09 | 0.306128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7962.44 | 0.124025E+09 |
April | 0.363528E+09 | 0.252589E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 372355.12 | 80025414.45 |
May | 0.375778E+09 | 0.261907E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1367163.90 | 48244566.47 |
June | 0.364321E+09 | 0.253748E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6254721.44 | 16345624.00 |
July | 0.374985E+09 | 0.260749E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14904089.73 | 3326511.74 |
August | 0.376571E+09 | 0.262360E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16103421.10 | 6925725.91 |
September | 0.363352E+09 | 0.252690E+09 | 0.295345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2948076.33 | 24911752.79 |
October | 0.375161E+09 | 0.261353E+09 | 0.305393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 201169.09 | 64056318.70 |
November | 0.362735E+09 | 0.253546E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106939E+09 |
December | 0.374985E+09 | 0.260749E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141180E+09 |
Annual Sum or Average | 0.442217E+10 | 0.307947E+10 | 0.359760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42158959.15 | 0.933519E+09 |
Minimum of Months | 0.339028E+09 | 0.236069E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3326511.74 |
Maximum of Months | 0.376747E+09 | 0.262360E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16103421.10 | 0.161936E+09 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.337502E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418047E+09 |
February | 0.139600E+10 | 0.304733E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.399794E+09 |
March | 0.155131E+10 | 0.338542E+09 | 0.578079E+10 | 0.502211E+11 | 0.00 | 0.00 | 0.00 | 614.57 | 0.327988E+09 |
April | 0.149688E+10 | 0.326059E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 622280.61 | 0.216403E+09 |
May | 0.154732E+10 | 0.338087E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 3229862.81 | 0.129594E+09 |
June | 0.150015E+10 | 0.327554E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 16987519.48 | 39707212.48 |
July | 0.154405E+10 | 0.336592E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 42630495.91 | 6848053.26 |
August | 0.155059E+10 | 0.338672E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 45310214.65 | 14605742.35 |
September | 0.149615E+10 | 0.326189E+09 | 0.557718E+10 | 0.484522E+11 | 0.00 | 0.00 | 0.00 | 8805272.49 | 62643086.66 |
October | 0.154478E+10 | 0.337372E+09 | 0.576693E+10 | 0.501006E+11 | 0.00 | 0.00 | 0.00 | 463507.89 | 0.166194E+09 |
November | 0.149361E+10 | 0.327294E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283740E+09 |
December | 0.154405E+10 | 0.336592E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.369134E+09 |
Annual Sum or Average | 0.182090E+11 | 0.397519E+10 | 0.679355E+11 | 0.590196E+12 | 0.00 | 0.00 | 0.00 | 0.118050E+09 | 0.243470E+10 |
Minimum of Months | 0.139600E+10 | 0.304733E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 6848053.26 |
Maximum of Months | 0.155131E+10 | 0.338672E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 45310214.65 | 0.418047E+09 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.137273E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.703861E+09 |
February | 0.236489E+11 | 0.117378E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.681628E+09 |
March | 0.262800E+11 | 0.123424E+10 | 0.122027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.561902E+09 |
April | 0.253579E+11 | 0.111384E+10 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 552499.26 | 0.369934E+09 |
May | 0.262123E+11 | 0.104671E+10 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4325880.51 | 0.225143E+09 |
June | 0.254132E+11 | 0.982301E+09 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24744847.05 | 75794062.51 |
July | 0.261570E+11 | 0.102016E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62224709.59 | 17015124.94 |
August | 0.262677E+11 | 0.110585E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63520258.26 | 32163696.83 |
September | 0.253456E+11 | 0.116008E+10 | 0.117729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9919900.48 | 0.119211E+09 |
October | 0.261693E+11 | 0.128273E+10 | 0.121734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 161422.03 | 0.308009E+09 |
November | 0.253025E+11 | 0.128666E+10 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.482719E+09 |
December | 0.261570E+11 | 0.136102E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.624183E+09 |
Annual Sum or Average | 0.308468E+12 | 0.141401E+11 | 0.143405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165450E+09 | 0.420156E+10 |
Minimum of Months | 0.236489E+11 | 0.982301E+09 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17015124.94 |
Maximum of Months | 0.262800E+11 | 0.137273E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63520258.26 | 0.703861E+09 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.949800E+10 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204457E+10 |
February | 0.702046E+11 | 0.850654E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196976E+10 |
March | 0.780153E+11 | 0.939272E+10 | 0.126786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163057E+10 |
April | 0.752779E+11 | 0.898322E+10 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2385439.43 | 0.108591E+10 |
May | 0.778146E+11 | 0.921372E+10 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 14076567.07 | 0.672662E+09 |
June | 0.754422E+11 | 0.890018E+10 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 72507605.20 | 0.233230E+09 |
July | 0.776503E+11 | 0.915875E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178394E+09 | 54048140.64 |
August | 0.779788E+11 | 0.927464E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188587E+09 | 97555425.66 |
September | 0.752414E+11 | 0.902359E+10 | 0.122320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 30700480.57 | 0.354090E+09 |
October | 0.776868E+11 | 0.939694E+10 | 0.126482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 808695.02 | 0.887469E+09 |
November | 0.751137E+11 | 0.915818E+10 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141391E+10 |
December | 0.776503E+11 | 0.945942E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181798E+10 |
Annual Sum or Average | 0.915726E+12 | 0.109966E+12 | 0.148998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.487459E+09 | 0.122618E+11 |
Minimum of Months | 0.702046E+11 | 0.850654E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54048140.64 |
Maximum of Months | 0.780153E+11 | 0.949800E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188587E+09 | 0.204457E+10 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196602E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177563E+09 |
February | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171738E+09 |
March | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7798.70 | 0.138848E+09 |
April | 0.293479E+09 | 0.190486E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 327351.32 | 88748395.75 |
May | 0.303504E+09 | 0.195821E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1706472.88 | 49753248.18 |
June | 0.293842E+09 | 0.188975E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10130378.75 | 10975932.67 |
July | 0.303141E+09 | 0.197358E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 27155927.42 | 576382.26 |
August | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 27347179.39 | 3105902.91 |
September | 0.293479E+09 | 0.190538E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5840254.52 | 20750597.76 |
October | 0.303322E+09 | 0.196576E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 216384.95 | 66297028.62 |
November | 0.293661E+09 | 0.189731E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117931E+09 |
December | 0.303141E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155632E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231110E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72731747.93 | 0.100192E+10 |
Minimum of Months | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 576382.26 |
Maximum of Months | 0.303685E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 27347179.39 | 0.177563E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196579E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175753E+09 |
February | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169487E+09 |
March | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137104E+09 |
April | 0.293479E+09 | 0.190464E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 285039.79 | 88992887.66 |
May | 0.303504E+09 | 0.195798E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1400971.28 | 53493115.14 |
June | 0.293842E+09 | 0.188953E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8866879.82 | 17487918.81 |
July | 0.303141E+09 | 0.197334E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25074763.83 | 2307215.22 |
August | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26189119.42 | 5211670.34 |
September | 0.293479E+09 | 0.190515E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4747212.69 | 24964244.44 |
October | 0.303322E+09 | 0.196553E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 114890.95 | 67898727.95 |
November | 0.293661E+09 | 0.189708E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116115E+09 |
December | 0.303141E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153419E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231083E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66678877.77 | 0.101223E+10 |
Minimum of Months | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2307215.22 |
Maximum of Months | 0.303685E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26189119.42 | 0.175753E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.123557E+09 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49991147.02 |
February | 0.00 | 0.111584E+09 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55926426.46 |
March | 0.00 | 0.122575E+09 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49553370.71 |
April | 0.00 | 0.119713E+09 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35618234.50 |
May | 0.00 | 0.123066E+09 | 0.217879E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 56230.18 | 25218729.69 |
June | 0.00 | 0.118764E+09 | 0.210812E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 495877.71 | 11785963.35 |
July | 0.00 | 0.124032E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1159981.65 | 5035038.70 |
August | 0.00 | 0.122575E+09 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1570382.56 | 6093546.51 |
September | 0.00 | 0.119746E+09 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 122931.13 | 15508764.84 |
October | 0.00 | 0.123541E+09 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30365773.15 |
November | 0.00 | 0.119238E+09 | 0.210867E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43590104.51 |
December | 0.00 | 0.124048E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51637068.66 |
Annual Sum or Average | 0.00 | 0.145244E+10 | 0.256575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3405403.23 | 0.380324E+09 |
Minimum of Months | 0.00 | 0.111584E+09 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5035038.70 |
Maximum of Months | 0.00 | 0.124048E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1570382.56 | 55926426.46 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.123591E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49759349.88 |
February | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47803386.66 |
March | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 220.17 | 38551923.19 |
April | 0.293479E+09 | 0.119746E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 91710.83 | 24777677.92 |
May | 0.303504E+09 | 0.123099E+09 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 405515.55 | 14356760.01 |
June | 0.293842E+09 | 0.118796E+09 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2518765.98 | 4072024.87 |
July | 0.303141E+09 | 0.124066E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7093550.30 | 468070.66 |
August | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7421502.68 | 1239600.54 |
September | 0.293479E+09 | 0.119778E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1376554.53 | 6471163.43 |
October | 0.303322E+09 | 0.123574E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 48724.47 | 18410888.12 |
November | 0.293661E+09 | 0.119271E+09 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32890556.50 |
December | 0.303141E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43509791.77 |
Annual Sum or Average | 0.357224E+10 | 0.145283E+10 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18956544.50 | 0.282311E+09 |
Minimum of Months | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 468070.66 |
Maximum of Months | 0.303685E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7421502.68 | 49759349.88 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196602E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177530E+09 |
February | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171917E+09 |
March | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7806.04 | 0.139287E+09 |
April | 0.293479E+09 | 0.190486E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 327516.60 | 89200529.65 |
May | 0.303504E+09 | 0.195821E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1699084.07 | 49969671.95 |
June | 0.293842E+09 | 0.188975E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10108355.85 | 11028767.04 |
July | 0.303141E+09 | 0.197358E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 27113507.14 | 583742.15 |
August | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 27337745.18 | 3156457.08 |
September | 0.293479E+09 | 0.190538E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5839165.52 | 20874496.47 |
October | 0.303322E+09 | 0.196576E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 217083.02 | 66538428.12 |
November | 0.293661E+09 | 0.189731E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118233E+09 |
December | 0.303141E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155636E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231110E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72650263.42 | 0.100396E+10 |
Minimum of Months | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 583742.15 |
Maximum of Months | 0.303685E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 27337745.18 | 0.177530E+09 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196579E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175702E+09 |
February | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169518E+09 |
March | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 926.86 | 0.137346E+09 |
April | 0.293479E+09 | 0.190464E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 279151.84 | 89257076.22 |
May | 0.303504E+09 | 0.195798E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1374687.50 | 53180566.95 |
June | 0.293842E+09 | 0.188953E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8832487.90 | 16518806.17 |
July | 0.303141E+09 | 0.197334E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 24973170.13 | 2620104.75 |
August | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26078929.42 | 5808802.29 |
September | 0.293479E+09 | 0.190515E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4723163.24 | 24886789.76 |
October | 0.303322E+09 | 0.196553E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 112123.83 | 67624079.04 |
November | 0.293661E+09 | 0.189708E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116384E+09 |
December | 0.303141E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153355E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231083E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66374640.73 | 0.101220E+10 |
Minimum of Months | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2620104.75 |
Maximum of Months | 0.303685E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26078929.42 | 0.175702E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.385223E+10 | 0.193865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216440E+09 |
February | 0.348285E+10 | 0.175042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207986E+09 |
March | 0.387034E+10 | 0.194462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6101.76 | 0.166521E+09 |
April | 0.373454E+10 | 0.187292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 448770.22 | 0.108277E+09 |
May | 0.386038E+10 | 0.194201E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1727498.92 | 65282162.96 |
June | 0.374269E+10 | 0.188151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8326465.49 | 22288689.04 |
July | 0.385223E+10 | 0.193342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20598627.00 | 4183047.52 |
August | 0.386853E+10 | 0.194537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21585114.06 | 9280082.52 |
September | 0.373273E+10 | 0.187367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3671924.25 | 33560697.45 |
October | 0.385404E+10 | 0.193790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 209241.91 | 87481688.83 |
November | 0.372639E+10 | 0.188002E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143037E+09 |
December | 0.385223E+10 | 0.193342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188813E+09 |
Annual Sum or Average | 0.454292E+11 | 0.228339E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56573743.61 | 0.125315E+10 |
Minimum of Months | 0.348285E+10 | 0.175042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4183047.52 |
Maximum of Months | 0.387034E+10 | 0.194537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21585114.06 | 0.216440E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196602E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177181E+09 |
February | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171413E+09 |
March | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6914.85 | 0.138729E+09 |
April | 0.293479E+09 | 0.190486E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 316289.07 | 88881761.25 |
May | 0.303504E+09 | 0.195821E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1662468.99 | 50110384.15 |
June | 0.293842E+09 | 0.188975E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9914063.02 | 11203276.67 |
July | 0.303141E+09 | 0.197358E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26696778.01 | 607886.07 |
August | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26945162.64 | 3182307.23 |
September | 0.293479E+09 | 0.190538E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5676637.50 | 20970520.43 |
October | 0.303322E+09 | 0.196576E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 203085.02 | 66504888.15 |
November | 0.293661E+09 | 0.189731E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117617E+09 |
December | 0.303141E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155232E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231110E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 71421399.10 | 0.100163E+10 |
Minimum of Months | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 607886.07 |
Maximum of Months | 0.303685E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26945162.64 | 0.177181E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196579E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175541E+09 |
February | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169340E+09 |
March | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136912E+09 |
April | 0.293479E+09 | 0.190464E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 273401.58 | 89275568.79 |
May | 0.303504E+09 | 0.195798E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1365649.49 | 54413527.07 |
June | 0.293842E+09 | 0.188953E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8695971.00 | 18368341.50 |
July | 0.303141E+09 | 0.197334E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 24686080.63 | 2431341.85 |
August | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25832101.06 | 5232279.13 |
September | 0.293479E+09 | 0.190515E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4626103.59 | 25427818.71 |
October | 0.303322E+09 | 0.196553E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 107358.47 | 68054577.82 |
November | 0.293661E+09 | 0.189708E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115695E+09 |
December | 0.303141E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153058E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231083E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65586665.82 | 0.101375E+10 |
Minimum of Months | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2431341.85 |
Maximum of Months | 0.303685E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25832101.06 | 0.175541E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.123591E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92461063.47 |
February | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89507735.42 |
March | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3540.54 | 71988184.60 |
April | 0.293479E+09 | 0.119746E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 161403.94 | 45936925.60 |
May | 0.303504E+09 | 0.123099E+09 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 853504.34 | 25686940.08 |
June | 0.293842E+09 | 0.118796E+09 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5083366.96 | 5689913.36 |
July | 0.303141E+09 | 0.124066E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13675226.77 | 311040.96 |
August | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13803446.54 | 1631548.15 |
September | 0.293479E+09 | 0.119778E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2904059.64 | 10805967.71 |
October | 0.303322E+09 | 0.123574E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 101706.41 | 34363660.62 |
November | 0.293661E+09 | 0.119271E+09 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61772928.22 |
December | 0.303141E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81213669.86 |
Annual Sum or Average | 0.357224E+10 | 0.145283E+10 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36586255.14 | 0.521370E+09 |
Minimum of Months | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 311040.96 |
Maximum of Months | 0.303685E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13803446.54 | 92461063.47 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.281023E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.488289E+09 |
February | 0.415303E+11 | 0.247315E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.466085E+09 |
March | 0.461508E+11 | 0.266201E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.389883E+09 |
April | 0.445315E+11 | 0.247582E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 357048.41 | 0.264416E+09 |
May | 0.460320E+11 | 0.244548E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2090291.98 | 0.167067E+09 |
June | 0.446286E+11 | 0.233263E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 12376007.70 | 59282796.40 |
July | 0.459349E+11 | 0.241252E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 32492103.77 | 13734887.93 |
August | 0.461292E+11 | 0.250998E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 36983262.37 | 23636060.29 |
September | 0.445099E+11 | 0.252766E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5329025.27 | 86800726.07 |
October | 0.459565E+11 | 0.269856E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 126456.42 | 0.207797E+09 |
November | 0.444343E+11 | 0.267468E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.337762E+09 |
December | 0.459349E+11 | 0.281967E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.433745E+09 |
Annual Sum or Average | 0.541708E+12 | 0.308424E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 89754195.91 | 0.293850E+10 |
Minimum of Months | 0.415303E+11 | 0.233263E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13734887.93 |
Maximum of Months | 0.461508E+11 | 0.281967E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 36983262.37 | 0.488289E+09 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.281023E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.493281E+09 |
February | 0.415303E+11 | 0.247315E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.470634E+09 |
March | 0.461508E+11 | 0.266201E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.393726E+09 |
April | 0.445315E+11 | 0.247582E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 325988.17 | 0.267098E+09 |
May | 0.460320E+11 | 0.244548E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2058786.94 | 0.168402E+09 |
June | 0.446286E+11 | 0.233263E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 12247121.78 | 59679405.11 |
July | 0.459349E+11 | 0.241252E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 32306756.67 | 13760736.93 |
August | 0.461292E+11 | 0.250998E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 36714570.75 | 23705241.22 |
September | 0.445099E+11 | 0.252766E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5200600.45 | 87571997.78 |
October | 0.459565E+11 | 0.269856E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 91752.96 | 0.209738E+09 |
November | 0.444343E+11 | 0.267468E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.341450E+09 |
December | 0.459349E+11 | 0.281967E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.438151E+09 |
Annual Sum or Average | 0.541708E+12 | 0.308424E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 88945577.73 | 0.296720E+10 |
Minimum of Months | 0.415303E+11 | 0.233263E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13760736.93 |
Maximum of Months | 0.461508E+11 | 0.281967E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 36714570.75 | 0.493281E+09 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.110133E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.444795E+09 |
February | 0.369574E+10 | 0.994402E+09 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.423995E+09 |
March | 0.410691E+10 | 0.110473E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.353032E+09 |
April | 0.396281E+10 | 0.106399E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 242848.71 | 0.238425E+09 |
May | 0.409635E+10 | 0.110324E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 1802320.19 | 0.149653E+09 |
June | 0.397146E+10 | 0.106887E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 10818720.37 | 52726055.53 |
July | 0.408770E+10 | 0.109836E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 28947656.81 | 11880766.37 |
August | 0.410499E+10 | 0.110515E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 32537103.76 | 20768010.35 |
September | 0.396089E+10 | 0.106442E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 4525105.89 | 77717006.45 |
October | 0.408962E+10 | 0.110091E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 49081.60 | 0.187212E+09 |
November | 0.395417E+10 | 0.106802E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306467E+09 |
December | 0.408770E+10 | 0.109836E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.394464E+09 |
Annual Sum or Average | 0.482060E+11 | 0.129718E+11 | 0.392709E+12 | 0.359593E+12 | 0.00 | 0.00 | 0.00 | 78922837.33 | 0.266113E+10 |
Minimum of Months | 0.369574E+10 | 0.994402E+09 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 11880766.37 |
Maximum of Months | 0.410691E+10 | 0.110515E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 32537103.76 | 0.444795E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.407704E+10 | 0.205176E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.384238E+09 |
February | 0.368610E+10 | 0.185255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.369360E+09 |
March | 0.409620E+10 | 0.205809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1237.91 | 0.296485E+09 |
April | 0.395248E+10 | 0.198220E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 526731.36 | 0.193435E+09 |
May | 0.408566E+10 | 0.205532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2214012.52 | 0.118288E+09 |
June | 0.396110E+10 | 0.199129E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12020307.39 | 41199012.05 |
July | 0.407704E+10 | 0.204623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30682909.96 | 8304270.15 |
August | 0.409429E+10 | 0.205888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33701963.75 | 16622997.20 |
September | 0.395056E+10 | 0.198299E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5229562.21 | 60034706.85 |
October | 0.407896E+10 | 0.205097E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 193285.27 | 0.152689E+09 |
November | 0.394385E+10 | 0.198971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253232E+09 |
December | 0.407704E+10 | 0.204623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.335380E+09 |
Annual Sum or Average | 0.480803E+11 | 0.241662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84570010.35 | 0.222927E+10 |
Minimum of Months | 0.368610E+10 | 0.185255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8304270.15 |
Maximum of Months | 0.409620E+10 | 0.205888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33701963.75 | 0.384238E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 13190.31 | 02-JAN-20:10 | 9632.53 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 13190.31 | 01-FEB-20:10 | 9632.53 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 13190.31 | 01-MAR-20:10 | 9632.53 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 13190.31 | 03-APR-19:10 | 9632.53 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 13190.31 | 01-MAY-19:10 | 9632.53 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 13190.31 | 01-JUN-19:10 | 9632.53 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 13190.31 | 03-JUL-19:10 | 9632.53 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 13190.31 | 01-AUG-19:10 | 9632.53 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 13190.31 | 01-SEP-19:10 | 9632.53 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 01-OCT-23:10 | 13190.31 | 02-OCT-19:10 | 9632.53 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 13190.31 | 01-NOV-19:10 | 9632.53 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 13190.31 | 01-DEC-20:10 | 9632.53 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 11501.89 | 13190.31 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 13190.31 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 597.59 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 203.62 | 02-JAN-05:00 |
February | 1169.53 | 01-FEB-00:10 | 597.59 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 209.20 | 06-FEB-03:00 |
March | 1169.53 | 01-MAR-00:10 | 597.59 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 154.44 | 23-MAR-06:00 |
April | 1169.53 | 01-APR-00:10 | 597.59 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.25 | 08-APR-09:55 | 108.92 | 03-APR-06:00 |
May | 1169.53 | 01-MAY-00:10 | 597.59 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.25 | 30-MAY-13:00 | 84.58 | 01-MAY-05:00 |
June | 1169.53 | 01-JUN-00:10 | 597.59 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.32 | 19-JUN-12:00 | 44.94 | 03-JUN-03:00 |
July | 1169.53 | 01-JUL-00:10 | 597.59 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.69 | 07-JUL-12:00 | 18.80 | 02-JUL-03:00 |
August | 1169.53 | 01-AUG-00:10 | 597.59 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.34 | 24-AUG-15:00 | 36.79 | 08-AUG-05:00 |
September | 1169.53 | 01-SEP-00:10 | 597.59 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.34 | 01-SEP-14:00 | 63.54 | 30-SEP-01:00 |
October | 1169.53 | 01-OCT-23:10 | 597.59 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.26 | 04-OCT-13:00 | 109.57 | 09-OCT-06:00 |
November | 1169.53 | 01-NOV-00:10 | 597.59 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 150.44 | 24-NOV-07:00 |
December | 1169.53 | 01-DEC-00:10 | 597.59 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 175.18 | 31-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1169.53 | 597.59 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.80 | |||||
Maximum of Months | 1169.53 | 597.59 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 64.32 | 209.20 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 692.02 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 78.60 | 02-JAN-05:00 |
February | 1354.32 | 01-FEB-00:10 | 692.02 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 80.85 | 06-FEB-03:00 |
March | 1354.32 | 01-MAR-00:10 | 692.02 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.24 | 27-MAR-15:55 | 61.81 | 23-MAR-06:00 |
April | 1354.32 | 01-APR-00:10 | 692.02 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.22 | 07-APR-13:00 | 44.31 | 03-APR-06:00 |
May | 1354.32 | 01-MAY-00:10 | 692.02 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.28 | 30-MAY-13:00 | 35.74 | 01-MAY-05:00 |
June | 1354.32 | 01-JUN-00:10 | 692.02 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.69 | 19-JUN-12:00 | 21.51 | 03-JUN-03:00 |
July | 1354.32 | 01-JUL-00:10 | 692.02 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.02 | 07-JUL-12:00 | 10.80 | 02-JUL-03:00 |
August | 1354.32 | 01-AUG-00:10 | 692.02 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.21 | 24-AUG-15:00 | 18.30 | 08-AUG-05:00 |
September | 1354.32 | 01-SEP-00:10 | 692.02 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.75 | 01-SEP-14:00 | 28.27 | 30-SEP-01:00 |
October | 1354.32 | 01-OCT-23:10 | 692.02 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.28 | 25-OCT-10:55 | 45.89 | 09-OCT-06:00 |
November | 1354.32 | 01-NOV-00:10 | 692.02 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 59.50 | 24-NOV-07:00 |
December | 1354.32 | 01-DEC-00:10 | 692.02 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 68.83 | 31-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1354.32 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.80 | |||||
Maximum of Months | 1354.32 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 26.69 | 80.85 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 286.42 | 02-JAN-00:10 | 684.18 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 185.75 | 02-JAN-05:00 |
February | 286.42 | 01-FEB-00:10 | 684.18 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 190.85 | 06-FEB-03:00 |
March | 286.42 | 01-MAR-00:10 | 684.18 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27-MAR-15:55 | 140.89 | 23-MAR-06:00 |
April | 286.42 | 01-APR-00:10 | 684.18 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.22 | 07-APR-13:00 | 99.35 | 03-APR-06:00 |
May | 286.42 | 01-MAY-00:10 | 684.18 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.82 | 30-MAY-13:00 | 80.48 | 01-MAY-05:00 |
June | 286.42 | 01-JUN-00:10 | 684.18 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 62.31 | 19-JUN-12:00 | 48.51 | 03-JUN-03:00 |
July | 286.42 | 01-JUL-00:10 | 684.18 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.52 | 07-JUL-12:00 | 24.53 | 02-JUL-03:00 |
August | 286.42 | 01-AUG-00:10 | 684.18 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.21 | 24-AUG-16:00 | 42.08 | 08-AUG-05:00 |
September | 286.42 | 01-SEP-00:10 | 684.18 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.41 | 01-SEP-14:00 | 64.18 | 24-SEP-06:00 |
October | 286.42 | 01-OCT-23:10 | 684.18 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.29 | 25-OCT-10:55 | 104.60 | 09-OCT-06:00 |
November | 286.42 | 01-NOV-00:10 | 684.18 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 137.22 | 24-NOV-07:00 |
December | 286.42 | 01-DEC-00:10 | 684.18 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 159.81 | 31-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 286.42 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.53 | |||||
Maximum of Months | 286.42 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 62.31 | 190.85 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 220.32 | 02-JAN-00:10 | 251.84 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 107.17 | 02-JAN-05:00 |
February | 220.32 | 01-FEB-00:10 | 251.84 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 110.11 | 06-FEB-03:00 |
March | 220.32 | 01-MAR-00:10 | 251.84 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.09 | 27-MAR-15:55 | 81.29 | 23-MAR-06:00 |
April | 220.32 | 01-APR-00:10 | 251.84 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.46 | 07-APR-13:00 | 57.32 | 03-APR-06:00 |
May | 220.32 | 01-MAY-00:10 | 251.84 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.64 | 30-MAY-13:00 | 45.49 | 01-MAY-05:00 |
June | 220.32 | 01-JUN-00:10 | 251.84 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.99 | 19-JUN-12:00 | 27.20 | 03-JUN-03:00 |
July | 220.32 | 01-JUL-00:10 | 251.84 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.08 | 07-JUL-12:00 | 13.35 | 02-JUL-03:00 |
August | 220.32 | 01-AUG-00:10 | 251.84 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.87 | 24-AUG-16:00 | 23.45 | 08-AUG-05:00 |
September | 220.32 | 01-SEP-00:10 | 251.84 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.61 | 01-SEP-14:00 | 35.89 | 24-SEP-06:00 |
October | 220.32 | 01-OCT-23:10 | 251.84 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.84 | 25-OCT-10:55 | 59.08 | 09-OCT-04:00 |
November | 220.32 | 01-NOV-00:10 | 251.84 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 79.17 | 24-NOV-07:00 |
December | 220.32 | 01-DEC-00:10 | 251.84 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 92.20 | 31-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 220.32 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.35 | |||||
Maximum of Months | 220.32 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 35.99 | 110.11 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 325.08 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 271.20 | 02-JAN-07:10 |
February | 907.20 | 01-FEB-00:10 | 325.08 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 277.02 | 06-FEB-07:10 |
March | 907.20 | 01-MAR-00:10 | 325.08 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 1.06 | 27-MAR-16:00 | 214.32 | 23-MAR-06:00 |
April | 907.20 | 01-APR-00:10 | 325.08 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 27.02 | 07-APR-13:00 | 157.12 | 03-APR-06:00 |
May | 907.20 | 01-MAY-00:10 | 325.08 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 49.06 | 30-MAY-13:00 | 123.13 | 01-MAY-05:10 |
June | 907.20 | 01-JUN-00:10 | 325.08 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 92.33 | 19-JUN-12:00 | 68.57 | 02-JUN-06:00 |
July | 907.20 | 01-JUL-00:10 | 325.08 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 75.37 | 07-JUL-12:00 | 34.22 | 01-JUL-23:20 |
August | 907.20 | 01-AUG-00:10 | 325.08 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 75.55 | 24-AUG-16:00 | 58.40 | 08-AUG-05:10 |
September | 907.20 | 01-SEP-00:10 | 325.08 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 52.16 | 01-SEP-14:20 | 94.37 | 24-SEP-06:10 |
October | 907.20 | 01-OCT-23:10 | 325.08 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 20.79 | 25-OCT-10:50 | 157.46 | 29-OCT-07:00 |
November | 907.20 | 01-NOV-00:10 | 325.08 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 208.92 | 24-NOV-07:00 |
December | 907.20 | 01-DEC-00:10 | 325.08 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 236.16 | 31-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 907.20 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 34.22 | ||||||
Maximum of Months | 907.20 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 92.33 | 277.02 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 1701.53 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 450.15 | 02-JAN-05:00 |
February | 15368.40 | 01-FEB-00:10 | 1701.53 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 463.95 | 06-FEB-03:00 |
March | 15368.40 | 01-MAR-00:10 | 1701.53 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 356.32 | 23-MAR-04:20 |
April | 15368.40 | 01-APR-00:10 | 1701.53 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.13 | 07-APR-13:00 | 253.47 | 01-APR-04:00 |
May | 15368.40 | 01-MAY-00:10 | 1701.53 | 01-MAY-19:10 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.64 | 30-MAY-13:00 | 207.46 | 01-MAY-05:00 |
June | 15368.40 | 01-JUN-00:10 | 1701.53 | 01-JUN-19:19 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 145.38 | 19-JUN-10:55 | 125.15 | 03-JUN-03:00 |
July | 15368.40 | 01-JUL-00:10 | 1701.53 | 03-JUL-19:19 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 113.46 | 07-JUL-10:55 | 58.82 | 02-JUL-03:00 |
August | 15368.40 | 01-AUG-00:10 | 1701.53 | 01-AUG-19:10 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 111.29 | 24-AUG-15:40 | 106.71 | 08-AUG-05:00 |
September | 15368.40 | 01-SEP-00:10 | 1701.53 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.34 | 01-SEP-14:00 | 164.94 | 30-SEP-01:00 |
October | 15368.40 | 01-OCT-23:10 | 1701.53 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.79 | 25-OCT-11:40 | 258.64 | 29-OCT-07:00 |
November | 15368.40 | 01-NOV-00:10 | 1701.53 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 344.65 | 24-NOV-06:00 |
December | 15368.40 | 01-DEC-00:10 | 1701.53 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 391.49 | 31-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 15368.40 | 1701.53 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.82 | |||||
Maximum of Months | 15368.40 | 1701.53 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 145.38 | 463.95 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 9504.80 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1316.22 | 02-JAN-05:00 |
February | 45622.98 | 01-FEB-00:10 | 9504.80 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 1357.92 | 06-FEB-03:00 |
March | 45622.98 | 01-MAR-00:10 | 9504.80 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 1040.43 | 23-MAR-04:40 |
April | 45622.98 | 01-APR-00:10 | 9504.80 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 119.46 | 07-APR-13:00 | 746.12 | 03-APR-06:00 |
May | 45622.98 | 01-MAY-00:10 | 9504.80 | 01-MAY-19:10 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 230.02 | 30-MAY-13:00 | 613.09 | 01-MAY-05:00 |
June | 45622.98 | 01-JUN-00:10 | 9504.80 | 01-JUN-19:10 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 437.68 | 19-JUN-12:00 | 368.16 | 03-JUN-03:00 |
July | 45622.98 | 01-JUL-00:10 | 9504.80 | 03-JUL-19:19 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 347.11 | 07-JUL-12:00 | 184.48 | 02-JUL-03:00 |
August | 45622.98 | 01-AUG-00:10 | 9504.80 | 01-AUG-19:10 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 330.10 | 24-AUG-15:00 | 312.60 | 08-AUG-05:00 |
September | 45622.98 | 01-SEP-00:10 | 9504.80 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 238.76 | 01-SEP-14:00 | 473.88 | 30-SEP-01:00 |
October | 45622.98 | 01-OCT-23:10 | 9504.80 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.66 | 25-OCT-10:55 | 767.56 | 09-OCT-06:00 |
November | 45622.98 | 01-NOV-00:10 | 9504.80 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 1007.57 | 24-NOV-06:00 |
December | 45622.98 | 01-DEC-00:10 | 9504.80 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 1152.13 | 31-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 45622.98 | 9504.80 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184.48 | |||||
Maximum of Months | 45622.98 | 9504.80 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 437.68 | 1357.92 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.88 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 118.73 | 02-JAN-05:00 |
February | 180.00 | 01-FEB-00:10 | 177.88 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 121.96 | 06-FEB-03:00 |
March | 180.00 | 01-MAR-00:10 | 177.88 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.23 | 27-MAR-16:00 | 90.17 | 23-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 177.88 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.04 | 08-APR-09:55 | 63.73 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 177.88 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.71 | 30-MAY-16:00 | 49.59 | 01-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 177.88 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.17 | 19-JUN-12:00 | 25.04 | 03-JUN-03:00 |
July | 180.00 | 01-JUL-00:10 | 177.88 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.01 | 10-JUL-15:10 | 8.96 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 177.88 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.61 | 24-AUG-16:00 | 19.65 | 08-AUG-05:00 |
September | 180.00 | 01-SEP-00:10 | 177.88 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.00 | 01-SEP-15:10 | 36.29 | 24-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 177.88 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.80 | 04-OCT-15:10 | 64.12 | 09-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 177.88 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 87.83 | 24-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 177.88 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 102.21 | 31-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.96 | |||||
Maximum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 39.17 | 121.96 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.86 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 118.72 | 02-JAN-05:00 |
February | 180.00 | 01-FEB-00:10 | 177.86 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 121.95 | 06-FEB-03:00 |
March | 180.00 | 01-MAR-00:10 | 177.86 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 90.16 | 23-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 177.86 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.04 | 08-APR-09:55 | 63.72 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 177.86 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.71 | 30-MAY-16:00 | 49.59 | 01-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 177.86 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.17 | 19-JUN-12:00 | 33.14 | 03-JUN-18:01 |
July | 180.00 | 01-JUL-00:10 | 177.86 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.01 | 10-JUL-15:10 | 19.20 | 01-JUL-18:00 |
August | 180.00 | 01-AUG-00:10 | 177.86 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.61 | 24-AUG-15:50 | 19.65 | 08-AUG-05:00 |
September | 180.00 | 01-SEP-00:10 | 177.86 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.00 | 01-SEP-15:10 | 36.29 | 24-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 177.86 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.86 | 04-OCT-15:10 | 64.11 | 09-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 177.86 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 87.83 | 24-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 177.86 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 102.20 | 31-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.20 | |||||
Maximum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 39.17 | 121.95 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 111.79 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 31.17 | 31-JAN-09:10 |
February | 0.00 | 01-FEB-00:10 | 111.79 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 35.04 | 05-FEB-24:00 |
March | 0.00 | 01-MAR-00:10 | 111.79 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 28.80 | 23-MAR-06:00 |
April | 0.00 | 01-APR-00:10 | 111.79 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 21.18 | 12-APR-06:10 |
May | 0.00 | 01-MAY-00:10 | 111.79 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.77 | 30-MAY-13:00 | 17.98 | 01-MAY-05:10 |
June | 0.00 | 01-JUN-00:10 | 111.79 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.19 | 19-JUN-12:00 | 11.93 | 03-JUN-03:00 |
July | 0.00 | 01-JUL-00:10 | 111.79 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.96 | 07-JUL-12:00 | 7.36 | 02-JUL-05:00 |
August | 0.00 | 01-AUG-00:10 | 111.79 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.92 | 24-AUG-15:00 | 10.43 | 08-AUG-05:00 |
September | 0.00 | 01-SEP-00:10 | 111.79 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.64 | 01-SEP-14:00 | 14.84 | 24-SEP-06:00 |
October | 0.00 | 01-OCT-00:10 | 111.79 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 22.98 | 29-OCT-07:00 |
November | 0.00 | 01-NOV-00:10 | 111.79 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 27.98 | 24-NOV-08:00 |
December | 0.00 | 01-DEC-00:10 | 111.79 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 29.15 | 22-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 0.00 | 111.79 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.36 | |||||
Maximum of Months | 0.00 | 111.79 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 8.19 | 35.04 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 111.82 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 33.14 | 02-JAN-05:00 |
February | 180.00 | 01-FEB-00:10 | 111.82 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 34.04 | 06-FEB-03:00 |
March | 180.00 | 01-MAR-00:10 | 111.82 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27-MAR-15:55 | 25.17 | 23-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 111.82 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.20 | 08-APR-09:55 | 17.79 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 111.82 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.06 | 30-MAY-16:00 | 13.84 | 01-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 111.82 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.93 | 19-JUN-12:00 | 7.17 | 02-JUN-21:20 |
July | 180.00 | 01-JUL-00:10 | 111.82 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.77 | 10-JUL-15:10 | 4.09 | 01-JUL-21:50 |
August | 180.00 | 01-AUG-00:10 | 111.82 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 24-AUG-15:10 | 5.48 | 08-AUG-05:00 |
September | 180.00 | 01-SEP-00:10 | 111.82 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.54 | 01-SEP-15:10 | 10.13 | 24-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 111.82 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.19 | 04-OCT-15:10 | 17.89 | 09-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 111.82 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 24.51 | 24-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 111.82 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 28.52 | 31-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.09 | |||||
Maximum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 10.93 | 34.04 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.88 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 118.73 | 02-JAN-05:00 |
February | 180.00 | 01-FEB-00:10 | 177.88 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 121.96 | 06-FEB-03:00 |
March | 180.00 | 01-MAR-00:10 | 177.88 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.23 | 27-MAR-16:00 | 90.17 | 23-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 177.88 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.04 | 08-APR-10:00 | 63.73 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 177.88 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.71 | 30-MAY-15:50 | 49.59 | 01-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 177.88 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.17 | 19-JUN-12:00 | 27.43 | 02-JUN-07:10 |
July | 180.00 | 01-JUL-00:10 | 177.88 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.02 | 10-JUL-15:10 | 8.95 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 177.88 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.62 | 24-AUG-15:10 | 19.65 | 08-AUG-05:00 |
September | 180.00 | 01-SEP-00:10 | 177.88 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.00 | 01-SEP-15:10 | 36.29 | 24-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 177.88 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.86 | 04-OCT-15:10 | 64.12 | 09-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 177.88 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 87.83 | 24-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 177.88 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 102.21 | 31-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.95 | |||||
Maximum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 39.17 | 121.96 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.86 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 118.72 | 02-JAN-05:00 |
February | 180.00 | 01-FEB-00:10 | 177.86 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 121.95 | 06-FEB-03:00 |
March | 180.00 | 01-MAR-00:10 | 177.86 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.20 | 27-MAR-15:55 | 90.16 | 23-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 177.86 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.04 | 08-APR-10:00 | 63.72 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 177.86 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.71 | 30-MAY-16:00 | 49.59 | 01-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 177.86 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.16 | 19-JUN-12:00 | 31.22 | 02-JUN-08:50 |
July | 180.00 | 01-JUL-00:10 | 177.86 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.02 | 10-JUL-15:10 | 15.98 | 11-JUL-08:00 |
August | 180.00 | 01-AUG-00:10 | 177.86 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.62 | 24-AUG-15:10 | 22.72 | 25-AUG-07:50 |
September | 180.00 | 01-SEP-00:10 | 177.86 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.00 | 01-SEP-15:10 | 36.29 | 24-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 177.86 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.86 | 04-OCT-15:08 | 64.11 | 09-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 177.86 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 87.83 | 24-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 177.86 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 102.20 | 31-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.98 | |||||
Maximum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 39.16 | 121.95 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2263.36 | 02-JAN-00:10 | 1867.32 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 143.10 | 02-JAN-05:00 |
February | 2263.36 | 01-FEB-00:10 | 1867.32 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 147.01 | 06-FEB-03:00 |
March | 2263.36 | 01-MAR-00:10 | 1867.32 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.10 | 27-MAR-16:00 | 108.58 | 23-MAR-06:00 |
April | 2263.36 | 01-APR-00:10 | 1867.32 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.07 | 07-APR-13:00 | 76.61 | 03-APR-06:00 |
May | 2263.36 | 01-MAY-00:10 | 1867.32 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.78 | 30-MAY-13:00 | 61.21 | 01-MAY-05:00 |
June | 2263.36 | 01-JUN-00:10 | 1867.32 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.33 | 19-JUN-12:00 | 37.36 | 03-JUN-03:00 |
July | 2263.36 | 01-JUL-00:10 | 1867.32 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.93 | 07-JUL-12:00 | 17.97 | 02-JUL-03:00 |
August | 2263.36 | 01-AUG-00:10 | 1867.32 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.35 | 24-AUG-16:00 | 31.20 | 08-AUG-05:00 |
September | 2263.36 | 01-SEP-00:10 | 1867.32 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.74 | 01-SEP-14:00 | 47.50 | 24-SEP-06:00 |
October | 2263.36 | 01-OCT-23:10 | 1867.32 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.94 | 25-OCT-10:55 | 80.49 | 09-OCT-04:00 |
November | 2263.36 | 01-NOV-00:10 | 1867.32 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 105.75 | 24-NOV-07:00 |
December | 2263.36 | 01-DEC-00:10 | 1867.32 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 123.13 | 31-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.97 | ||||
Maximum of Months | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.33 | 147.01 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.88 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 118.97 | 02-JAN-05:00 |
February | 180.00 | 01-FEB-00:10 | 177.88 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 122.19 | 06-FEB-03:00 |
March | 180.00 | 01-MAR-00:10 | 177.88 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.05 | 27-MAR-16:00 | 90.39 | 23-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 177.88 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.87 | 08-APR-09:55 | 63.94 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 177.88 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.52 | 30-MAY-16:00 | 49.80 | 01-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 177.88 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.00 | 19-JUN-12:00 | 25.23 | 03-JUN-03:00 |
July | 180.00 | 01-JUL-00:10 | 177.88 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.50 | 10-JUL-15:10 | 9.14 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 177.88 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.45 | 24-AUG-16:00 | 19.84 | 08-AUG-05:00 |
September | 180.00 | 01-SEP-00:10 | 177.88 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.80 | 01-SEP-15:10 | 36.49 | 24-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 177.88 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 04-OCT-15:10 | 64.33 | 09-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 177.88 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 88.06 | 24-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 177.88 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 102.44 | 31-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.14 | |||||
Maximum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 39.00 | 122.19 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.86 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 118.96 | 02-JAN-05:00 |
February | 180.00 | 01-FEB-00:10 | 177.86 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 122.18 | 06-FEB-03:00 |
March | 180.00 | 01-MAR-00:10 | 177.86 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 90.39 | 23-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 177.86 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.86 | 08-APR-09:55 | 63.94 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 177.86 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.50 | 30-MAY-16:00 | 49.79 | 01-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 177.86 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.00 | 19-JUN-12:00 | 35.79 | 03-JUN-18:01 |
July | 180.00 | 01-JUL-00:10 | 177.86 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.77 | 10-JUL-15:10 | 21.07 | 01-JUL-18:00 |
August | 180.00 | 01-AUG-00:10 | 177.86 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.44 | 24-AUG-16:00 | 19.84 | 08-AUG-05:00 |
September | 180.00 | 01-SEP-00:10 | 177.86 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.83 | 01-SEP-15:10 | 36.49 | 24-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 177.86 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.68 | 04-OCT-15:10 | 64.33 | 09-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 177.86 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 88.05 | 24-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 177.86 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 102.43 | 31-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.84 | |||||
Maximum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 39.00 | 122.18 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 111.82 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 60.87 | 02-JAN-05:00 |
February | 180.00 | 01-FEB-00:10 | 111.82 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 62.52 | 06-FEB-03:00 |
March | 180.00 | 01-MAR-00:10 | 111.82 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.56 | 27-MAR-16:00 | 46.25 | 23-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 111.82 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.61 | 08-APR-10:00 | 32.71 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 111.82 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.02 | 30-MAY-15:40 | 25.48 | 01-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 111.82 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.95 | 19-JUN-12:00 | 12.91 | 03-JUN-03:10 |
July | 180.00 | 01-JUL-00:10 | 111.82 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.83 | 10-JUL-15:10 | 4.68 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 111.82 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.16 | 24-AUG-16:00 | 10.15 | 08-AUG-05:00 |
September | 180.00 | 01-SEP-00:10 | 111.82 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.72 | 01-SEP-15:10 | 18.67 | 24-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 111.82 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.66 | 04-OCT-15:10 | 32.92 | 09-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 111.82 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 45.05 | 24-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 111.82 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 52.41 | 31-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.68 | |||||
Maximum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 19.95 | 62.52 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2988.03 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 311.09 | 02-JAN-05:00 |
February | 26988.77 | 01-FEB-00:10 | 2988.03 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 318.82 | 06-FEB-03:00 |
March | 26988.77 | 01-MAR-00:10 | 2988.03 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 244.79 | 23-MAR-04:10 |
April | 26988.77 | 01-APR-00:10 | 2988.03 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.66 | 07-APR-13:00 | 179.81 | 03-APR-06:00 |
May | 26988.77 | 01-MAY-00:10 | 2988.03 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.55 | 30-MAY-13:00 | 144.79 | 01-MAY-05:00 |
June | 26988.77 | 01-JUN-00:10 | 2988.03 | 01-JUN-19:19 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.45 | 19-JUN-12:00 | 84.07 | 03-JUN-03:10 |
July | 26988.77 | 01-JUL-00:10 | 2988.03 | 03-JUL-19:30 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.12 | 07-JUL-12:00 | 44.40 | 02-JUL-05:00 |
August | 26988.77 | 01-AUG-00:10 | 2988.03 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.64 | 24-AUG-15:40 | 70.93 | 08-AUG-05:00 |
September | 26988.77 | 01-SEP-00:10 | 2988.03 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.78 | 01-SEP-14:00 | 112.03 | 24-SEP-06:00 |
October | 26988.77 | 01-OCT-23:10 | 2988.03 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.36 | 25-OCT-10:55 | 180.92 | 09-OCT-06:00 |
November | 26988.77 | 01-NOV-00:10 | 2988.03 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 238.56 | 24-NOV-06:00 |
December | 26988.77 | 01-DEC-00:10 | 2988.03 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 274.56 | 31-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.40 | |||||
Maximum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 90.45 | 318.82 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2988.03 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 313.06 | 02-JAN-05:00 |
February | 26988.77 | 01-FEB-00:10 | 2988.03 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 320.77 | 06-FEB-03:00 |
March | 26988.77 | 01-MAR-00:10 | 2988.03 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 245.01 | 23-MAR-06:00 |
April | 26988.77 | 01-APR-00:10 | 2988.03 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.45 | 07-APR-13:00 | 179.82 | 03-APR-06:00 |
May | 26988.77 | 01-MAY-00:10 | 2988.03 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.55 | 30-MAY-13:00 | 144.79 | 01-MAY-05:00 |
June | 26988.77 | 01-JUN-00:10 | 2988.03 | 01-JUN-19:19 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.45 | 19-JUN-12:00 | 84.07 | 03-JUN-03:10 |
July | 26988.77 | 01-JUL-00:10 | 2988.03 | 03-JUL-19:30 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.12 | 07-JUL-12:00 | 44.40 | 02-JUL-05:00 |
August | 26988.77 | 01-AUG-00:10 | 2988.03 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.64 | 24-AUG-15:40 | 70.93 | 08-AUG-05:00 |
September | 26988.77 | 01-SEP-00:10 | 2988.03 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.78 | 01-SEP-14:00 | 112.03 | 24-SEP-06:00 |
October | 26988.77 | 01-OCT-23:10 | 2988.03 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.66 | 25-OCT-10:55 | 180.92 | 09-OCT-06:00 |
November | 26988.77 | 01-NOV-00:10 | 2988.03 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 239.22 | 24-NOV-07:00 |
December | 26988.77 | 01-DEC-00:10 | 2988.03 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 274.57 | 31-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.40 | |||||
Maximum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 90.45 | 320.77 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 1060.81 | 02-JAN-20:10 | 14912.86 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 278.30 | 02-JAN-07:00 |
February | 2401.70 | 01-FEB-00:10 | 1060.81 | 01-FEB-20:10 | 14912.86 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 284.06 | 06-FEB-07:00 |
March | 2401.70 | 01-MAR-00:10 | 1060.81 | 01-MAR-20:10 | 14912.86 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 219.30 | 23-MAR-06:00 |
April | 2401.70 | 01-APR-00:10 | 1060.81 | 03-APR-19:10 | 14912.86 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 17.26 | 07-APR-13:00 | 160.94 | 03-APR-06:00 |
May | 2401.70 | 01-MAY-00:10 | 1060.81 | 01-MAY-19:10 | 14912.86 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 39.05 | 30-MAY-13:00 | 128.23 | 01-MAY-05:10 |
June | 2401.70 | 01-JUN-00:10 | 1060.81 | 01-JUN-19:10 | 14912.86 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 81.05 | 19-JUN-12:00 | 75.13 | 03-JUN-05:00 |
July | 2401.70 | 01-JUL-00:10 | 1060.81 | 03-JUL-19:10 | 14912.86 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 63.75 | 07-JUL-12:00 | 39.74 | 02-JUL-05:00 |
August | 2401.70 | 01-AUG-00:10 | 1060.81 | 01-AUG-19:10 | 14912.86 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 63.31 | 24-AUG-15:50 | 63.50 | 08-AUG-05:00 |
September | 2401.70 | 01-SEP-00:10 | 1060.81 | 01-SEP-19:10 | 14912.86 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 45.52 | 01-SEP-14:00 | 100.26 | 24-SEP-06:00 |
October | 2401.70 | 01-OCT-23:10 | 1060.81 | 02-OCT-19:10 | 14912.86 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 6.06 | 04-OCT-13:00 | 161.93 | 09-OCT-06:00 |
November | 2401.70 | 01-NOV-00:10 | 1060.81 | 01-NOV-19:10 | 14912.86 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 214.12 | 24-NOV-07:00 |
December | 2401.70 | 01-DEC-00:10 | 1060.81 | 01-DEC-20:10 | 14912.86 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 245.78 | 31-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2401.70 | 1060.81 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 0.00 | 39.74 | ||||||
Maximum of Months | 2401.70 | 1060.81 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 81.05 | 284.06 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2395.44 | 02-JAN-00:10 | 1976.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 253.70 | 02-JAN-05:00 |
February | 2395.44 | 01-FEB-00:10 | 1976.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 260.61 | 06-FEB-03:00 |
March | 2395.44 | 01-MAR-00:10 | 1976.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.64 | 27-MAR-15:55 | 192.59 | 23-MAR-06:00 |
April | 2395.44 | 01-APR-00:10 | 1976.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.59 | 07-APR-13:00 | 136.01 | 03-APR-06:00 |
May | 2395.44 | 01-MAY-00:10 | 1976.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.29 | 30-MAY-13:00 | 106.12 | 01-MAY-05:00 |
June | 2395.44 | 01-JUN-00:10 | 1976.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.25 | 19-JUN-12:00 | 64.59 | 03-JUN-03:00 |
July | 2395.44 | 01-JUL-00:10 | 1976.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.31 | 07-JUL-12:00 | 30.71 | 02-JUL-03:00 |
August | 2395.44 | 01-AUG-00:10 | 1976.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.88 | 24-AUG-15:00 | 53.67 | 08-AUG-05:00 |
September | 2395.44 | 01-SEP-00:10 | 1976.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.48 | 01-SEP-14:00 | 82.62 | 30-SEP-01:00 |
October | 2395.44 | 01-OCT-23:10 | 1976.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.79 | 25-OCT-10:55 | 136.84 | 09-OCT-06:00 |
November | 2395.44 | 01-NOV-00:10 | 1976.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 187.59 | 24-NOV-07:00 |
December | 2395.44 | 01-DEC-00:10 | 1976.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 218.35 | 31-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.71 | ||||
Maximum of Months | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.25 | 260.61 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 15357.80 | 20-JAN-22:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 14580.63 | 01-FEB-21:00 | 8945.92 | 13190.31 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 13907.59 | 03-MAR-21:00 | 8945.92 | 13190.31 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 14725.19 | 08-APR-10:33 | 11501.89 | 10992.10 | 10646.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 14726.16 | 29-MAY-10:33 | 11501.89 | 13190.31 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16267.77 | 22-JUN-18:08 | 53675.50 | 70347.97 | 54753.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16351.43 | 11-JUL-18:05 | 53675.50 | 70347.97 | 54753.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 18029.17 | 24-AUG-18:23 | 35783.66 | 46898.65 | 36502.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 20442.02 | 13-SEP-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 22031.16 | 27-OCT-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 21719.52 | 03-NOV-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 20229.42 | 01-DEC-22:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 13907.59 | 8945.92 | 10992.10 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22031.16 | 53675.50 | 70347.97 | 54753.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2492.35 | 17-JAN-13:10 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.26 |
February | 2218.22 | 02-FEB-13:40 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.33 |
March | 3033.74 | 03-MAR-13:20 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
April | 3216.60 | 08-APR-12:30 | 389.84 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.13 |
May | 2502.14 | 30-MAY-12:50 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 30.75 | 0.00 |
June | 2993.12 | 01-JUN-14:30 | 1169.53 | 497.99 | 757.77 | 0.00 | 0.00 | 0.00 | 0.00 | 26.40 | 0.00 |
July | 3015.98 | 08-JUL-12:10 | 389.84 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 41.42 | 0.00 |
August | 3831.05 | 20-AUG-13:53 | 779.69 | 398.40 | 649.52 | 0.00 | 0.00 | 0.00 | 0.00 | 25.37 | 0.00 |
September | 3844.61 | 07-SEP-12:40 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 13.10 | 0.00 |
October | 4042.35 | 04-OCT-12:10 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 2.63 | 0.00 |
November | 3145.19 | 02-NOV-12:40 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.88 |
December | 3013.54 | 17-DEC-12:50 | 389.84 | 199.20 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2218.22 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4042.35 | 1169.53 | 497.99 | 757.77 | 0.00 | 0.00 | 0.00 | 0.00 | 41.42 | 100.33 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1190.36 | 19-JAN-21:00 | 1053.36 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.35 |
February | 1179.66 | 02-FEB-21:00 | 1053.36 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.40 |
March | 1305.74 | 03-MAR-21:00 | 1053.36 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.46 |
April | 1545.68 | 07-APR-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.52 |
May | 1793.74 | 31-MAY-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.05 |
June | 2020.41 | 19-JUN-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 9.85 | 0.00 |
July | 2047.63 | 07-JUL-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 3.25 | 0.00 |
August | 2103.83 | 16-AUG-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 5.45 | 0.00 |
September | 2024.92 | 01-SEP-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 5.42 | 0.00 |
October | 1777.07 | 05-OCT-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.56 |
November | 1344.53 | 03-NOV-20:00 | 1053.36 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.05 |
December | 1206.54 | 18-DEC-21:00 | 1053.36 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.32 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1179.66 | 1053.36 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2103.83 | 1203.84 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 9.85 | 54.40 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 813.12 | 19-JAN-21:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.98 |
February | 794.08 | 24-FEB-21:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.95 |
March | 927.88 | 28-MAR-10:33 | 190.94 | 570.15 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.51 |
April | 1123.76 | 08-APR-10:33 | 286.42 | 570.15 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 8.10 | 0.00 |
May | 1237.75 | 31-MAY-10:33 | 190.94 | 570.15 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 12.61 | 0.00 |
June | 1443.03 | 19-JUN-21:00 | 254.59 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 23.27 | 0.00 |
July | 1677.75 | 10-JUL-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 20.40 | 0.00 |
August | 1727.28 | 17-AUG-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 23.15 | 0.00 |
September | 1417.73 | 01-SEP-21:00 | 254.59 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 12.81 | 0.00 |
October | 1159.30 | 05-OCT-10:33 | 190.94 | 570.15 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.92 |
November | 1008.32 | 04-NOV-10:33 | 286.42 | 570.15 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.20 |
December | 819.23 | 19-DEC-21:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.22 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 794.08 | 190.94 | 570.15 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1727.28 | 286.42 | 684.18 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 23.27 | 105.95 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 450.31 | 19-JAN-21:00 | 171.36 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.06 |
February | 391.55 | 22-FEB-22:00 | 195.84 | 223.85 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.54 |
March | 539.26 | 28-MAR-10:33 | 146.88 | 209.86 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.27 |
April | 664.17 | 08-APR-10:33 | 220.32 | 209.86 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 4.89 | 0.00 |
May | 728.93 | 31-MAY-10:33 | 146.88 | 209.86 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 7.62 | 0.00 |
June | 771.22 | 22-JUN-18:08 | 1028.16 | 1343.12 | 1376.47 | 0.00 | 0.00 | 0.00 | 0.00 | 14.57 | 0.00 |
July | 786.88 | 08-JUL-10:33 | 220.32 | 209.86 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 18.90 | 0.00 |
August | 805.01 | 24-AUG-18:23 | 685.44 | 895.41 | 917.65 | 0.00 | 0.00 | 0.00 | 0.00 | 18.01 | 0.00 |
September | 754.25 | 03-SEP-10:33 | 220.32 | 251.83 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 5.51 | 0.00 |
October | 678.53 | 05-OCT-10:33 | 146.88 | 209.86 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.08 |
November | 587.84 | 04-NOV-10:33 | 220.32 | 209.86 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.02 |
December | 456.94 | 19-DEC-21:00 | 171.36 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 391.55 | 146.88 | 209.86 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 805.01 | 1028.16 | 1343.12 | 1376.47 | 0.00 | 0.00 | 0.00 | 0.00 | 18.90 | 56.54 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 36638.17 | 19-JAN-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 141.92 |
February | 36528.11 | 17-FEB-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 165.59 |
March | 37317.17 | 03-MAR-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 89.51 |
April | 38125.89 | 07-APR-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 15.23 |
May | 38432.35 | 30-MAY-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 26.86 |
June | 39060.39 | 22-JUN-19:25 | 1411.20 | 650.17 | 9145.60 | 79453.15 | 0.00 | 0.00 | 0.00 | 20.28 | 0.00 |
July | 38721.58 | 10-JUL-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 27.86 | 0.00 |
August | 38836.98 | 04-AUG-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 52.51 | 0.00 |
September | 39069.07 | 01-SEP-19:25 | 1411.20 | 650.17 | 9145.60 | 79453.15 | 0.00 | 0.00 | 0.00 | 16.90 | 0.00 |
October | 38095.97 | 04-OCT-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 34.23 |
November | 37405.36 | 03-NOV-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 76.73 |
December | 36662.70 | 19-DEC-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 108.92 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 36528.11 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 39069.07 | 1411.20 | 650.17 | 9145.60 | 79453.15 | 0.00 | 0.00 | 0.00 | 52.51 | 165.59 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10080.66 | 17-JAN-13:00 | 3415.20 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.20 |
February | 10022.53 | 20-FEB-13:00 | 5122.80 | 124.78 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.15 |
March | 11630.84 | 03-MAR-13:10 | 3415.20 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.35 |
April | 12265.14 | 08-APR-12:20 | 10245.60 | 207.96 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.58 |
May | 10611.27 | 29-MAY-10:33 | 15368.40 | 374.34 | 1219.29 | 0.00 | 0.00 | 0.00 | 0.00 | 45.56 | 0.00 |
June | 11746.76 | 19-JUN-21:10 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 54.36 | 0.00 |
July | 11621.43 | 10-JUL-21:10 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 36.04 | 0.00 |
August | 12605.55 | 19-AUG-11:40 | 10245.60 | 207.96 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 32.76 | 0.00 |
September | 14097.01 | 30-SEP-12:40 | 5122.80 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.03 |
October | 13848.99 | 04-OCT-12:00 | 3415.20 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 4.65 | 0.00 |
November | 12422.98 | 04-NOV-12:30 | 5122.80 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.69 |
December | 12381.77 | 17-DEC-11:00 | 8538.00 | 124.78 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.94 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10022.53 | 3415.20 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14097.01 | 15368.40 | 1134.35 | 1219.29 | 0.00 | 0.00 | 0.00 | 0.00 | 54.36 | 178.15 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 26531.63 | 19-JAN-21:00 | 35484.54 | 9504.80 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 690.64 |
February | 26813.25 | 19-FEB-11:33 | 45622.98 | 8174.13 | 12668.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 519.11 |
March | 28980.18 | 03-MAR-22:20 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 479.13 |
April | 34282.35 | 07-APR-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.99 |
May | 36426.76 | 31-MAY-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.30 |
June | 40018.74 | 19-JUN-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 155.24 | 0.00 |
July | 40518.19 | 10-JUL-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 102.90 | 0.00 |
August | 41586.16 | 04-AUG-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 245.70 | 0.00 |
September | 40686.00 | 01-SEP-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 85.52 | 0.00 |
October | 37681.23 | 05-OCT-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.77 |
November | 31379.25 | 03-NOV-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 388.75 |
December | 28377.32 | 17-DEC-11:33 | 45622.98 | 8174.13 | 12668.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 396.28 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 26531.63 | 35484.54 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 41586.16 | 45622.98 | 9504.80 | 12668.47 | 0.00 | 0.00 | 0.00 | 0.00 | 245.70 | 690.64 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3500.95 | 20-JAN-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.19 |
February | 3525.25 | 22-FEB-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.71 |
March | 3572.58 | 11-MAR-16:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.12 |
April | 3606.97 | 11-APR-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.21 |
May | 3637.70 | 27-MAY-18:01 | 819.00 | 1245.18 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.76 |
June | 3363.89 | 23-JUN-08:61 | 360.00 | 782.68 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 11.99 | 0.00 |
July | 3272.88 | 01-JUL-18:02 | 702.00 | 1067.29 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.69 |
August | 3273.55 | 13-AUG-08:62 | 324.00 | 597.68 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 12.11 | 0.00 |
September | 3581.72 | 28-SEP-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.95 |
October | 3557.06 | 28-OCT-15:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.64 |
November | 3353.70 | 02-NOV-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.24 |
December | 3480.75 | 02-DEC-16:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.21 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3272.88 | 324.00 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3637.70 | 970.20 | 1245.18 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 12.11 | 59.71 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2793.11 | 20-JAN-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.65 |
February | 3209.81 | 22-FEB-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.71 |
March | 3439.83 | 11-MAR-16:01 | 378.00 | 410.86 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.77 |
April | 3697.67 | 09-APR-18:11 | 1170.00 | 1778.61 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.73 |
May | 3784.68 | 02-MAY-18:21 | 1386.00 | 1582.97 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.65 |
June | 3470.79 | 10-JUN-08:51 | 540.00 | 996.02 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.36 |
July | 3556.19 | 03-JUL-18:51 | 1386.00 | 1582.97 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.77 | 0.00 |
August | 3407.87 | 23-AUG-08:51 | 360.00 | 782.59 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.70 |
September | 3411.53 | 03-SEP-08:51 | 540.00 | 996.02 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.59 |
October | 3423.05 | 26-OCT-15:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.80 |
November | 3108.48 | 04-NOV-15:01 | 378.00 | 410.86 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.31 |
December | 2116.85 | 17-DEC-16:01 | 378.00 | 410.86 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.46 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2116.85 | 360.00 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3784.68 | 1386.00 | 1778.61 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.77 | 56.71 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 145.12 | 31-JAN-15:20 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.74 |
February | 347.76 | 20-FEB-13:30 | 0.00 | 36.89 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.70 |
March | 410.14 | 15-MAR-13:05 | 0.00 | 62.60 | 61.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.85 |
April | 536.48 | 07-APR-12:30 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.48 |
May | 402.65 | 30-MAY-12:50 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 2.69 | 0.00 |
June | 420.01 | 19-JUN-13:20 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 6.68 | 0.00 |
July | 444.19 | 10-JUL-13:10 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 4.65 | 0.00 |
August | 567.08 | 30-AUG-12:50 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 | 0.00 |
September | 626.39 | 28-SEP-12:30 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.16 |
October | 666.10 | 04-OCT-12:00 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.98 |
November | 563.23 | 02-NOV-12:40 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.98 |
December | 397.06 | 17-DEC-13:30 | 0.00 | 36.89 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.84 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 145.12 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 666.10 | 0.00 | 62.60 | 61.92 | 0.00 | 0.00 | 0.00 | 0.00 | 6.68 | 26.74 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 906.89 | 22-JAN-09:02 | 270.00 | 313.10 | 799.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.01 |
February | 809.91 | 25-FEB-09:01 | 378.00 | 438.35 | 1119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.92 |
March | 1080.23 | 03-MAR-19:02 | 831.60 | 597.13 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.76 |
April | 1174.26 | 10-APR-20:41 | 1441.80 | 895.70 | 1602.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 |
May | 1236.22 | 27-MAY-21:51 | 1386.00 | 950.49 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.91 |
June | 1227.24 | 04-JUN-08:51 | 486.00 | 563.59 | 1439.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.13 | 0.00 |
July | 1143.51 | 03-JUL-18:51 | 1386.00 | 995.22 | 1187.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.70 | 0.00 |
August | 1121.68 | 28-AUG-21:51 | 1620.00 | 674.29 | 789.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.46 |
September | 1200.32 | 10-SEP-21:51 | 1247.40 | 855.44 | 789.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.71 |
October | 1157.97 | 06-OCT-18:01 | 970.20 | 696.66 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.94 |
November | 1083.19 | 02-NOV-18:01 | 970.20 | 696.66 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.18 |
December | 939.93 | 25-DEC-09:02 | 216.00 | 250.48 | 639.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.54 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 809.91 | 216.00 | 250.48 | 639.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1236.22 | 1620.00 | 995.22 | 1602.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.70 | 21.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2594.17 | 19-JAN-09:02 | 216.00 | 469.61 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.81 |
February | 3272.18 | 25-FEB-09:01 | 378.00 | 697.30 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.81 |
March | 3252.53 | 11-MAR-16:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.64 |
April | 3291.85 | 11-APR-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.81 |
May | 3329.86 | 27-MAY-18:01 | 819.00 | 1245.18 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.43 |
June | 3094.32 | 25-JUN-08:61 | 378.00 | 697.30 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 5.49 | 0.00 |
July | 3153.76 | 27-JUL-08:61 | 252.00 | 547.88 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 5.68 | 0.00 |
August | 3146.98 | 24-AUG-08:61 | 252.00 | 547.88 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 4.41 | 0.00 |
September | 3314.21 | 28-SEP-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.96 |
October | 3274.63 | 26-OCT-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.04 |
November | 3114.28 | 02-NOV-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.34 |
December | 3042.81 | 02-DEC-09:02 | 324.00 | 597.68 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.91 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2594.17 | 216.00 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3329.86 | 970.20 | 1245.18 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 5.68 | 82.81 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1654.11 | 19-JAN-09:02 | 216.00 | 469.55 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.02 |
February | 3026.22 | 25-FEB-09:01 | 378.00 | 697.22 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.34 |
March | 2933.25 | 23-MAR-08:62 | 216.00 | 469.55 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.24 |
April | 3453.81 | 08-APR-08:51 | 540.00 | 996.02 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.57 |
May | 3784.02 | 30-MAY-08:61 | 252.00 | 547.81 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 |
June | 3614.57 | 26-JUN-08:32 | 216.00 | 469.55 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.88 |
July | 3467.42 | 11-JUL-08:51 | 324.00 | 704.33 | 1019.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.35 |
August | 3592.18 | 30-AUG-08:51 | 360.00 | 782.59 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.99 |
September | 3475.51 | 03-SEP-08:51 | 540.00 | 996.02 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.09 |
October | 3238.26 | 15-OCT-08:51 | 486.00 | 896.42 | 1469.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.69 |
November | 2825.84 | 08-NOV-09:02 | 216.00 | 469.55 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.61 |
December | 2267.86 | 17-DEC-09:02 | 324.00 | 597.61 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.93 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1654.11 | 216.00 | 469.55 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.35 | |
Maximum of Months | 3784.02 | 540.00 | 996.02 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.34 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1581.74 | 19-JAN-19:08 | 7041.55 | 6639.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.14 |
February | 1754.94 | 19-FEB-11:33 | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.92 |
March | 1892.67 | 29-MAR-10:33 | 1508.90 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.32 |
April | 2297.17 | 08-APR-10:33 | 2263.36 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.44 | 0.00 |
May | 2530.82 | 31-MAY-10:33 | 1508.90 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.93 | 0.00 |
June | 2700.82 | 01-JUN-17:02 | 10059.36 | 9959.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.88 | 0.00 |
July | 2658.03 | 08-JUL-10:33 | 2263.36 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.04 | 0.00 |
August | 2809.83 | 24-AUG-18:23 | 7041.55 | 6639.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.59 | 0.00 |
September | 2655.58 | 04-SEP-10:33 | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.26 | 0.00 |
October | 2389.60 | 05-OCT-10:33 | 1508.90 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 |
November | 2046.35 | 04-NOV-10:33 | 2263.36 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.00 |
December | 1783.73 | 17-DEC-11:33 | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.92 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 1581.74 | 1508.90 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2809.83 | 10059.36 | 9959.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.04 | 60.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3651.16 | 20-JAN-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.27 |
February | 3677.93 | 22-FEB-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.80 |
March | 3739.30 | 11-MAR-16:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.30 |
April | 3767.21 | 11-APR-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.32 |
May | 3804.69 | 27-MAY-18:01 | 819.00 | 1245.18 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.94 |
June | 3459.67 | 23-JUN-08:61 | 360.00 | 782.68 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 11.86 | 0.00 |
July | 3402.84 | 01-JUL-18:02 | 702.00 | 1067.29 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.90 |
August | 3447.76 | 26-AUG-18:02 | 702.00 | 1067.29 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 3.89 | 0.00 |
September | 3742.03 | 28-SEP-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.08 |
October | 3706.95 | 28-OCT-15:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.69 |
November | 3447.81 | 02-NOV-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.68 |
December | 3641.60 | 02-DEC-16:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.41 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3402.84 | 360.00 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3804.69 | 970.20 | 1245.18 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 11.86 | 59.80 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2409.82 | 17-JAN-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.25 |
February | 2588.28 | 22-FEB-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.08 |
March | 3583.84 | 11-MAR-16:01 | 378.00 | 410.86 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.88 |
April | 3869.32 | 09-APR-18:11 | 1170.00 | 1778.61 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.81 |
May | 4055.86 | 02-MAY-18:21 | 1386.00 | 1582.97 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.19 |
June | 3735.00 | 04-JUN-21:51 | 1386.00 | 1511.82 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.10 |
July | 3691.54 | 03-JUL-18:51 | 1386.00 | 1582.97 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 | 0.00 |
August | 3521.34 | 30-AUG-08:51 | 360.00 | 782.59 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.53 |
September | 3528.58 | 03-SEP-08:51 | 540.00 | 996.02 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.58 |
October | 3559.02 | 26-OCT-15:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.84 |
November | 3143.08 | 04-NOV-15:01 | 378.00 | 410.86 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.43 |
December | 2043.67 | 17-DEC-16:01 | 378.00 | 410.86 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.72 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2043.67 | 360.00 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4055.86 | 1386.00 | 1778.61 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 | 56.08 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2002.78 | 31-JAN-16:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.07 |
February | 2002.53 | 22-FEB-16:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.97 |
March | 2003.87 | 22-MAR-15:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.95 |
April | 2018.02 | 11-APR-15:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.54 |
May | 2020.51 | 20-MAY-18:01 | 819.00 | 782.76 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.84 |
June | 1872.23 | 23-JUN-08:61 | 360.00 | 492.02 | 1109.66 | 0.00 | 0.00 | 0.00 | 0.00 | 5.96 | 0.00 |
July | 1863.47 | 19-JUL-18:02 | 831.60 | 597.13 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 5.31 | 0.00 |
August | 1859.65 | 03-AUG-18:02 | 831.60 | 597.13 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 0.00 |
September | 2033.40 | 10-SEP-18:01 | 819.00 | 782.76 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.74 |
October | 2012.85 | 26-OCT-15:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.28 |
November | 1980.88 | 02-NOV-18:01 | 970.20 | 696.66 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.22 |
December | 1993.15 | 21-DEC-16:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1859.65 | 360.00 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2033.40 | 970.20 | 782.76 | 1109.66 | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 42.07 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 17490.99 | 23-JAN-23:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.22 |
February | 16838.85 | 23-FEB-23:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.86 |
March | 19222.97 | 27-MAR-21:04 | 134943.84 | 9960.10 | 33739.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.79 |
April | 20678.38 | 07-APR-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.11 |
May | 22014.52 | 31-MAY-21:52 | 269887.68 | 19920.20 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.06 |
June | 23395.30 | 19-JUN-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 32.77 | 0.00 |
July | 23491.26 | 11-JUL-18:03 | 125947.58 | 9561.70 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 19.50 | 0.00 |
August | 23504.44 | 04-AUG-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 49.78 | 0.00 |
September | 22618.97 | 01-SEP-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 18.47 | 0.00 |
October | 20838.70 | 05-OCT-21:53 | 188921.38 | 13944.14 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.55 |
November | 18937.21 | 03-NOV-22:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.95 |
December | 17284.79 | 04-DEC-23:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 16838.85 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23504.44 | 269887.68 | 19920.20 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 49.78 | 151.86 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19540.94 | 23-JAN-23:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.22 |
February | 18838.40 | 23-FEB-23:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.86 |
March | 21140.24 | 27-MAR-21:04 | 134943.84 | 9960.10 | 33739.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.79 |
April | 22318.31 | 07-APR-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.11 |
May | 23260.91 | 31-MAY-21:52 | 269887.68 | 19920.20 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.06 |
June | 24647.70 | 19-JUN-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 32.74 | 0.00 |
July | 24945.59 | 11-JUL-18:03 | 125947.58 | 9561.70 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 19.50 | 0.00 |
August | 24713.49 | 04-AUG-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 49.76 | 0.00 |
September | 23853.01 | 01-SEP-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 18.46 | 0.00 |
October | 22213.90 | 05-OCT-21:53 | 188921.38 | 13944.14 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.55 |
November | 20732.15 | 03-NOV-22:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.95 |
December | 19296.23 | 04-DEC-23:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 18838.40 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24945.59 | 269887.68 | 19920.20 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 49.76 | 151.86 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 26771.56 | 17-JAN-11:50 | 533.71 | 294.67 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 106.57 |
February | 27393.20 | 19-FEB-11:50 | 800.57 | 353.60 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 115.76 |
March | 28348.20 | 29-MAR-10:33 | 1601.14 | 884.01 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 114.62 |
April | 30630.81 | 07-APR-17:01 | 9339.96 | 4950.44 | 104389.99 | 157449.82 | 0.00 | 0.00 | 0.00 | 6.00 | 0.00 |
May | 31243.56 | 29-MAY-10:33 | 2401.70 | 1060.81 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 21.94 | 0.00 |
June | 31760.52 | 01-JUN-18:05 | 11207.95 | 5657.64 | 89477.13 | 89971.33 | 0.00 | 0.00 | 0.00 | 23.14 | 0.00 |
July | 31445.95 | 09-JUL-10:40 | 2401.70 | 1060.81 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 35.47 | 0.00 |
August | 31465.65 | 30-AUG-18:08 | 11207.95 | 5657.64 | 89477.13 | 89971.33 | 0.00 | 0.00 | 0.00 | 22.05 | 0.00 |
September | 31235.55 | 04-SEP-10:37 | 2401.70 | 1060.81 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 9.79 | 0.00 |
October | 29950.39 | 04-OCT-10:33 | 1601.14 | 884.01 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 12.57 |
November | 28694.48 | 04-NOV-10:45 | 1601.14 | 589.34 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 48.51 |
December | 27265.59 | 17-DEC-11:50 | 800.57 | 353.60 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 84.47 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 26771.56 | 533.71 | 294.67 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31760.52 | 11207.95 | 5657.64 | 104389.99 | 157449.82 | 0.00 | 0.00 | 0.00 | 35.47 | 115.76 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3445.73 | 19-JAN-11:33 | 1596.96 | 1646.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.31 |
February | 3674.43 | 19-FEB-11:33 | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.53 |
March | 4012.73 | 03-MAR-11:33 | 1596.96 | 1646.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.52 |
April | 4919.87 | 08-APR-10:33 | 2395.44 | 1646.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.87 | 0.00 |
May | 5425.27 | 31-MAY-10:33 | 1596.96 | 1646.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.55 | 0.00 |
June | 6005.12 | 19-JUN-14:10 | 798.48 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.14 | 0.00 |
July | 6694.95 | 11-JUL-16:50 | 1330.80 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.36 | 0.00 |
August | 6676.81 | 16-AUG-12:50 | 532.32 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.08 | 0.00 |
September | 5963.70 | 01-SEP-14:10 | 798.48 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.97 | 0.00 |
October | 4949.54 | 05-OCT-10:33 | 1596.96 | 1646.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.46 |
November | 4166.73 | 04-NOV-10:45 | 1596.96 | 1097.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.51 |
December | 3742.37 | 17-DEC-11:33 | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.08 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 3445.73 | 532.32 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6694.95 | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.14 | 96.31 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.378697E+12 | 225190.25 | 20-JAN-07:19 | 0.589278E+12 | 531128.22 | 03-JAN-18:49 |
February | 0.343682E+12 | 218960.01 | 01-FEB-07:10 | 0.518468E+12 | 515447.69 | 06-FEB-19:10 |
March | 0.378900E+12 | 236318.82 | 27-MAR-18:10 | 0.507452E+12 | 540448.41 | 24-MAR-17:49 |
April | 0.371436E+12 | 271227.45 | 07-APR-18:00 | 0.488957E+12 | 530065.22 | 03-APR-17:00 |
May | 0.411102E+12 | 300200.89 | 29-MAY-19:19 | 0.416871E+12 | 444920.60 | 01-MAY-20:19 |
June | 0.530066E+12 | 379908.37 | 19-JUN-18:10 | 0.351385E+12 | 339019.54 | 01-JUN-17:30 |
July | 0.655370E+12 | 396467.32 | 20-JUL-20:00 | 0.353919E+12 | 324357.48 | 11-JUL-17:49 |
August | 0.613356E+12 | 413605.13 | 04-AUG-19:10 | 0.352490E+12 | 321964.81 | 22-AUG-17:19 |
September | 0.482356E+12 | 393324.53 | 07-SEP-19:00 | 0.354337E+12 | 316910.03 | 29-SEP-17:30 |
October | 0.420584E+12 | 298433.23 | 05-OCT-18:10 | 0.432224E+12 | 473556.05 | 28-OCT-18:49 |
November | 0.366647E+12 | 227040.24 | 02-NOV-18:10 | 0.518057E+12 | 510533.49 | 28-NOV-18:00 |
December | 0.381862E+12 | 225487.57 | 26-DEC-07:19 | 0.514862E+12 | 531992.43 | 26-DEC-18:00 |
Annual Sum or Average | 0.533406E+13 | 0.539830E+13 | ||||
Minimum of Months | 0.343682E+12 | 218960.01 | 0.351385E+12 | 316910.03 | ||
Maximum of Months | 0.655370E+12 | 413605.13 | 0.589278E+12 | 540448.41 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.671754E+11 | 0.200475E+11 | 0.140828E+12 | 0.691146E+11 | 0.407555E+11 | 0.347173E+10 | 0.00 | 0.835430E+09 | 0.00 | 0.00 | 0.232386E+11 | 0.804793E+10 | 0.00 |
February | 0.603942E+11 | 0.168124E+11 | 0.127191E+12 | 0.624260E+11 | 0.368978E+11 | 0.383285E+10 | 0.00 | 0.155408E+10 | 0.00 | 0.00 | 0.226410E+11 | 0.727240E+10 | 0.00 |
March | 0.665329E+11 | 0.168346E+11 | 0.140882E+12 | 0.691168E+11 | 0.406774E+11 | 0.635467E+10 | 0.00 | 0.556485E+10 | 0.00 | 0.00 | 0.196791E+11 | 0.804632E+10 | 0.00 |
April | 0.640800E+11 | 0.145100E+11 | 0.136245E+12 | 0.668843E+11 | 0.405216E+11 | 0.777478E+10 | 0.00 | 0.192000E+11 | 0.00 | 0.00 | 0.935461E+10 | 0.779747E+10 | 0.00 |
May | 0.657897E+11 | 0.134144E+11 | 0.140860E+12 | 0.691151E+11 | 0.443506E+11 | 0.908713E+10 | 0.00 | 0.521173E+11 | 0.00 | 0.00 | 0.302802E+10 | 0.804737E+10 | 0.00 |
June | 0.635197E+11 | 0.121484E+11 | 0.136336E+12 | 0.668864E+11 | 0.466258E+11 | 0.918945E+10 | 0.00 | 0.169557E+12 | 0.00 | 0.00 | 0.128322E+11 | 0.778868E+10 | 0.00 |
July | 0.657047E+11 | 0.129258E+11 | 0.140770E+12 | 0.691126E+11 | 0.509212E+11 | 0.100070E+11 | 0.00 | 0.268527E+12 | 0.00 | 0.00 | 0.240012E+11 | 0.805559E+10 | 0.00 |
August | 0.659929E+11 | 0.142731E+11 | 0.140892E+12 | 0.691165E+11 | 0.520447E+11 | 0.984974E+10 | 0.00 | 0.230623E+12 | 0.00 | 0.00 | 0.171574E+11 | 0.804711E+10 | 0.00 |
September | 0.642869E+11 | 0.155094E+11 | 0.136256E+12 | 0.668845E+11 | 0.461606E+11 | 0.903410E+10 | 0.00 | 0.123427E+12 | 0.00 | 0.00 | 0.783621E+10 | 0.779860E+10 | 0.00 |
October | 0.667474E+11 | 0.178784E+11 | 0.140818E+12 | 0.691143E+11 | 0.452512E+11 | 0.903434E+10 | 0.00 | 0.523892E+11 | 0.00 | 0.00 | 0.602450E+10 | 0.804604E+10 | 0.00 |
November | 0.648352E+11 | 0.189296E+11 | 0.136330E+12 | 0.668857E+11 | 0.403180E+11 | 0.639280E+10 | 0.00 | 0.617568E+10 | 0.00 | 0.00 | 0.139567E+11 | 0.778075E+10 | 0.00 |
December | 0.671636E+11 | 0.204399E+11 | 0.140770E+12 | 0.691135E+11 | 0.409245E+11 | 0.452698E+10 | 0.00 | 0.205812E+10 | 0.00 | 0.00 | 0.236249E+11 | 0.805628E+10 | 0.00 |
Annual Sum or Average | 0.782223E+12 | 0.193724E+12 | 0.165818E+13 | 0.813770E+12 | 0.525449E+12 | 0.885556E+11 | 0.00 | 0.932030E+12 | 0.00 | 0.00 | 0.183374E+12 | 0.947845E+11 | 0.00 |
Minimum of Months | 0.603942E+11 | 0.121484E+11 | 0.127191E+12 | 0.624260E+11 | 0.368978E+11 | 0.347173E+10 | 0.00 | 0.835430E+09 | 0.00 | 0.00 | 0.302802E+10 | 0.727240E+10 | 0.00 |
Maximum of Months | 0.671754E+11 | 0.204399E+11 | 0.140892E+12 | 0.691168E+11 | 0.520447E+11 | 0.100070E+11 | 0.00 | 0.268527E+12 | 0.00 | 0.00 | 0.240012E+11 | 0.805628E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.151918E+12 | 0.00 | 0.190338E+12 | 0.00 | 0.247022E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.156359E+12 | 0.00 | 0.224905E+12 | 0.00 | 0.00 |
March | 0.152024E+12 | 0.00 | 0.110706E+12 | 0.00 | 0.244723E+12 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.114682E+12 | 0.00 | 0.227318E+12 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.425867E+11 | 0.00 | 0.222306E+12 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 0.786899E+09 | 0.00 | 0.203485E+12 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 0.119262E+09 | 0.00 | 0.201980E+12 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 0.580061E+09 | 0.00 | 0.199871E+12 | 0.00 | 0.00 |
September | 0.146971E+12 | 0.00 | 0.961288E+10 | 0.00 | 0.197753E+12 | 0.00 | 0.00 |
October | 0.151903E+12 | 0.00 | 0.660697E+11 | 0.00 | 0.214251E+12 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.151392E+12 | 0.00 | 0.219573E+12 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.124194E+12 | 0.00 | 0.238848E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178884E+13 | 0.00 | 0.967427E+12 | 0.00 | 0.264203E+13 | 0.00 | 0.00 |
Minimum of Months | 0.137204E+12 | 0.00 | 0.119262E+09 | 0.00 | 0.197753E+12 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.190338E+12 | 0.00 | 0.247022E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 64632.59 | 02-JAN-20:10 | 12338.45 | 01-JAN-00:10 | 89171.45 | 02-JAN-07:10 | 49607.07 | 02-JAN-07:19 | 22867.98 | 02-JAN-19:10 | 4020.50 | 19-JAN-17:30 | 0.00 | 01-JAN-00:10 |
February | 64632.59 | 01-FEB-20:10 | 12338.45 | 01-FEB-00:10 | 89171.45 | 01-FEB-07:10 | 49607.07 | 01-FEB-07:19 | 23472.23 | 06-FEB-19:10 | 4102.38 | 06-FEB-10:50 | 0.00 | 01-FEB-00:10 |
March | 64632.59 | 01-MAR-20:10 | 12338.45 | 01-MAR-00:10 | 89171.45 | 01-MAR-07:10 | 49607.07 | 13-MAR-06:19 | 24337.70 | 27-MAR-21:10 | 4020.05 | 11-MAR-19:10 | 0.00 | 01-MAR-00:10 |
April | 64632.59 | 03-APR-19:10 | 12338.45 | 01-APR-00:10 | 89171.45 | 03-APR-06:10 | 49606.28 | 14-APR-06:19 | 28855.08 | 07-APR-21:00 | 4008.40 | 04-APR-08:20 | 0.00 | 01-APR-00:10 |
May | 64632.59 | 01-MAY-19:10 | 12338.45 | 01-MAY-00:10 | 89171.45 | 01-MAY-06:10 | 49606.28 | 04-MAY-06:19 | 32460.08 | 31-MAY-21:00 | 3978.54 | 01-MAY-06:10 | 0.00 | 01-MAY-00:10 |
June | 64632.59 | 01-JUN-19:19 | 12338.45 | 01-JUN-00:10 | 89171.45 | 01-JUN-06:10 | 49605.70 | 16-JUN-06:19 | 33106.26 | 19-JUN-21:10 | 4399.76 | 19-JUN-18:10 | 0.00 | 01-JUN-00:10 |
July | 64632.59 | 03-JUL-19:30 | 12338.45 | 01-JUL-00:10 | 89171.45 | 03-JUL-06:10 | 49606.17 | 24-JUL-06:19 | 33608.31 | 10-JUL-21:10 | 4603.53 | 20-JUL-18:10 | 0.00 | 01-JUL-00:10 |
August | 64632.59 | 01-AUG-19:10 | 12338.45 | 01-AUG-00:10 | 89171.45 | 01-AUG-06:10 | 49605.99 | 16-AUG-06:19 | 34998.06 | 18-AUG-21:10 | 4814.23 | 11-AUG-20:00 | 0.00 | 01-AUG-00:10 |
September | 64632.59 | 01-SEP-19:10 | 12338.45 | 01-SEP-00:10 | 89171.45 | 01-SEP-06:10 | 49606.78 | 27-SEP-06:19 | 35380.68 | 05-SEP-21:00 | 4696.97 | 07-SEP-19:00 | 0.00 | 01-SEP-00:10 |
October | 64632.59 | 02-OCT-19:10 | 12338.45 | 01-OCT-00:10 | 89171.45 | 02-OCT-06:10 | 49607.07 | 06-OCT-06:19 | 33090.13 | 05-OCT-21:00 | 4029.62 | 27-OCT-08:09 | 0.00 | 01-OCT-00:10 |
November | 64632.59 | 01-NOV-19:10 | 12338.45 | 01-NOV-00:10 | 89171.45 | 01-NOV-06:10 | 49607.07 | 01-NOV-06:19 | 26987.23 | 03-NOV-21:10 | 4048.10 | 27-NOV-07:10 | 0.00 | 01-NOV-00:10 |
December | 64632.59 | 01-DEC-20:10 | 12338.45 | 01-DEC-00:10 | 89171.45 | 01-DEC-07:10 | 49607.07 | 01-DEC-07:19 | 22011.20 | 04-DEC-21:10 | 4052.55 | 16-DEC-16:49 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 64632.59 | 12338.45 | 89171.45 | 49605.70 | 22011.20 | 3978.54 | 0.00 | |||||||
Maximum of Months | 64632.59 | 12338.45 | 89171.45 | 49607.07 | 35380.68 | 4814.23 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 4786.53 | 17-JAN-16:10 | 0.00 | 0.00 | 9938.94 | 01-JAN-00:10 | 4751.13 | 19-JAN-07:40 | 0.00 |
February | 7753.67 | 20-FEB-16:10 | 0.00 | 0.00 | 9938.94 | 01-FEB-00:20 | 4751.13 | 15-FEB-07:49 | 0.00 |
March | 44278.64 | 27-MAR-16:10 | 0.00 | 0.00 | 9938.94 | 01-MAR-00:20 | 4751.13 | 16-MAR-06:49 | 0.00 |
April | 86100.31 | 07-APR-15:09 | 0.00 | 0.00 | 9938.94 | 01-APR-00:10 | 4751.13 | 13-APR-06:49 | 0.00 |
May | 101396.45 | 31-MAY-15:20 | 0.00 | 0.00 | 9938.94 | 29-MAY-18:40 | 4751.13 | 16-MAY-06:40 | 0.00 |
June | 173321.28 | 19-JUN-18:10 | 0.00 | 0.00 | 9938.94 | 15-JUN-08:39 | 4751.12 | 23-JUN-06:00 | 0.00 |
July | 175787.62 | 20-JUL-20:00 | 0.00 | 0.00 | 9938.94 | 03-JUL-18:00 | 4751.13 | 28-JUL-06:00 | 0.00 |
August | 191431.37 | 04-AUG-18:30 | 0.00 | 0.00 | 9938.94 | 01-AUG-06:00 | 4751.13 | 31-AUG-06:00 | 0.00 |
September | 168931.68 | 07-SEP-19:00 | 0.00 | 0.00 | 9938.94 | 07-SEP-08:00 | 4751.13 | 15-SEP-06:19 | 0.00 |
October | 105191.13 | 03-OCT-15:09 | 0.00 | 0.00 | 9938.94 | 03-OCT-12:50 | 4751.13 | 26-OCT-18:49 | 0.00 |
November | 28033.22 | 03-NOV-15:09 | 0.00 | 0.00 | 9938.94 | 01-NOV-02:20 | 4751.13 | 10-NOV-19:40 | 0.00 |
December | 9612.89 | 18-DEC-10:00 | 0.00 | 0.00 | 9938.94 | 01-DEC-00:20 | 4751.13 | 21-DEC-07:19 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 4786.53 | 0.00 | 0.00 | 9938.94 | 4751.12 | 0.00 | |||
Maximum of Months | 191431.37 | 0.00 | 0.00 | 9938.94 | 4751.13 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 225190.25 | 20-JAN-07:19 | 36001.17 | 89171.45 | 12338.45 | 49607.07 | 15666.37 | 3494.05 | 0.00 | 1025.12 | 0.00 |
February | 218960.01 | 01-FEB-07:10 | 36001.17 | 89171.45 | 12338.45 | 49600.84 | 14926.60 | 396.04 | 0.00 | 0.00 | 0.00 |
March | 236318.82 | 27-MAR-18:10 | 57474.69 | 77573.37 | 12338.45 | 28158.62 | 19189.05 | 3392.01 | 0.00 | 31028.56 | 0.00 |
April | 271227.45 | 07-APR-18:00 | 57474.69 | 77573.37 | 12338.45 | 28169.74 | 21962.56 | 3558.09 | 0.00 | 62041.93 | 0.00 |
May | 300200.89 | 29-MAY-19:19 | 59807.00 | 84978.71 | 12338.45 | 10961.63 | 24398.84 | 3717.02 | 0.00 | 88494.90 | 0.00 |
June | 379908.37 | 19-JUN-18:10 | 53184.46 | 77573.37 | 0.00 | 28157.33 | 26165.45 | 4399.76 | 0.00 | 173321.28 | 0.00 |
July | 396467.32 | 20-JUL-20:00 | 57474.69 | 88218.55 | 12338.45 | 10998.34 | 30682.04 | 4518.05 | 0.00 | 175787.62 | 0.00 |
August | 413605.13 | 04-AUG-19:10 | 64632.59 | 86439.81 | 12338.45 | 10993.43 | 29588.50 | 4387.63 | 0.00 | 189455.27 | 0.00 |
September | 393324.53 | 07-SEP-19:00 | 64632.59 | 86439.81 | 12338.45 | 10999.77 | 28989.50 | 4696.97 | 0.00 | 168931.68 | 0.00 |
October | 298433.23 | 05-OCT-18:10 | 57474.69 | 77573.37 | 12338.45 | 28159.60 | 20797.75 | 3681.14 | 0.00 | 82820.16 | 0.00 |
November | 227040.24 | 02-NOV-18:10 | 57474.69 | 77573.37 | 12338.45 | 28159.60 | 22620.86 | 3402.87 | 0.00 | 16836.05 | 0.00 |
December | 225487.57 | 26-DEC-07:19 | 36001.17 | 89171.45 | 12338.45 | 49607.07 | 15723.69 | 3483.36 | 0.00 | 1251.01 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 218960.01 | 36001.17 | 77573.37 | 0.00 | 10961.63 | 14926.60 | 396.04 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 413605.13 | 64632.59 | 89171.45 | 12338.45 | 49607.07 | 30682.04 | 4696.97 | 0.00 | 189455.27 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 214962.93 | 02-JAN-09:09 | 0.00 | 255267.86 | 31-JAN-21:30 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 220144.77 | 06-FEB-07:10 | 0.00 | 255357.24 | 03-FEB-21:19 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 190385.66 | 24-MAR-17:49 | 0.00 | 254120.21 | 01-MAR-21:40 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 181886.49 | 03-APR-17:00 | 0.00 | 246636.57 | 03-APR-20:49 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 162610.60 | 01-MAY-06:19 | 0.00 | 235955.98 | 01-MAY-20:19 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 25445.74 | 03-JUN-02:00 | 0.00 | 223528.51 | 01-JUN-20:19 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 13316.78 | 11-JUL-17:49 | 0.00 | 213214.80 | 03-JUL-20:19 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 37021.96 | 20-AUG-13:30 | 0.00 | 209644.01 | 31-AUG-20:49 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 118587.55 | 24-SEP-05:00 | 0.00 | 215878.70 | 29-SEP-20:40 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 179576.51 | 27-OCT-08:20 | 0.00 | 228007.43 | 31-OCT-20:19 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 187743.85 | 18-NOV-12:50 | 0.00 | 240224.18 | 30-NOV-21:40 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 190805.88 | 14-DEC-11:50 | 0.00 | 250488.73 | 29-DEC-21:19 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 104248.32 | 0.00 | 13316.78 | 0.00 | 209644.01 | 0.00 | |||
Maximum of Months | 104248.32 | 0.00 | 220144.77 | 0.00 | 255357.24 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.65 | 0.50 | 24.65 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.50 | 24.65 | 0.50 | 24.65 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.65 | 0.50 | 24.65 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.00 | 20.46 | 2.00 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 |
February | 1.33 | 20.51 | 1.33 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.69 | 0.17 | 21.69 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.73 | 0.33 | 21.73 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.70 | 0.83 | 21.70 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.76 | 1.33 | 21.76 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 21.86 | 4.00 | 21.86 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.80 | 1.33 | 21.80 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.84 | 0.17 | 21.84 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.50 | 20.52 | 0.50 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
Annual Sum or Average | 3.83 | 20.48 | 3.83 | 20.48 | 8.17 | 21.17 | 8.17 | 21.39 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.00 | 20.52 | 2.00 | 20.52 | 4.00 | 21.86 | 4.00 | 21.86 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.17 | 20.46 | 4.17 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 |
February | 3.50 | 20.48 | 3.50 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.88 | 0.33 | 21.88 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.83 | 1.50 | 21.83 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 21.76 | 4.33 | 21.76 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 21.75 | 3.83 | 21.75 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 21.77 | 3.67 | 21.77 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.71 | 1.00 | 21.71 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.83 | 20.52 | 0.83 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
Annual Sum or Average | 8.50 | 20.47 | 8.50 | 20.47 | 14.67 | 21.07 | 14.67 | 21.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.17 | 20.52 | 4.17 | 20.52 | 4.33 | 21.88 | 4.33 | 21.88 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.33 | 20.27 | 1.33 | 20.27 | 0.00 | 20.27 | 0.00 | 20.27 |
February | 1.17 | 20.30 | 1.17 | 20.30 | 0.00 | 20.30 | 0.00 | 20.30 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 21.79 | 2.83 | 21.79 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 21.86 | 7.67 | 21.86 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 21.88 | 6.33 | 21.88 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 21.85 | 2.67 | 21.85 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 21.80 | 3.00 | 21.80 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.50 | 20.28 | 2.50 | 20.28 | 22.50 | 21.56 | 22.50 | 21.69 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.33 | 20.30 | 1.33 | 20.30 | 7.67 | 21.88 | 7.67 | 21.88 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.17 | 20.45 | 2.17 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 |
February | 1.50 | 20.51 | 1.50 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.67 | 0.17 | 21.67 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.77 | 0.17 | 21.77 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.74 | 0.50 | 21.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.83 | 20.52 | 0.83 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
Annual Sum or Average | 4.50 | 20.49 | 4.50 | 20.49 | 0.83 | 20.59 | 0.83 | 20.68 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.17 | 20.52 | 2.17 | 20.52 | 0.50 | 21.77 | 0.50 | 21.77 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.67 | 20.46 | 4.67 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 |
February | 3.50 | 20.49 | 3.50 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 |
March | 0.17 | 20.54 | 0.17 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 22.04 | 0.33 | 22.04 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 22.27 | 2.83 | 22.27 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 22.13 | 5.67 | 22.13 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 22.12 | 5.50 | 22.12 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 22.14 | 5.50 | 22.14 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 22.23 | 3.33 | 22.23 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.98 | 1.17 | 21.98 |
November | 0.67 | 20.55 | 0.67 | 20.55 | 0.00 | 20.55 | 0.00 | 20.55 |
December | 1.83 | 20.52 | 1.83 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
Annual Sum or Average | 10.83 | 20.49 | 10.83 | 20.49 | 24.33 | 21.37 | 24.33 | 21.64 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.46 | 0.00 | 20.46 |
Maximum of Months | 4.67 | 20.55 | 4.67 | 20.55 | 5.67 | 22.27 | 5.67 | 22.27 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.83 | 20.42 | 1.83 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 |
February | 0.83 | 20.48 | 0.83 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.81 | 0.17 | 21.81 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.90 | 0.33 | 21.90 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.76 | 1.50 | 21.76 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 21.78 | 3.00 | 21.78 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 21.87 | 5.17 | 21.87 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 21.80 | 2.00 | 21.80 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.80 | 0.33 | 21.80 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 20.49 | 0.33 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 |
Annual Sum or Average | 3.00 | 20.45 | 3.00 | 20.45 | 12.50 | 21.38 | 12.50 | 21.56 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.83 | 20.49 | 1.83 | 20.49 | 5.17 | 21.90 | 5.17 | 21.90 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.50 | 20.42 | 3.50 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 |
February | 2.50 | 20.42 | 2.50 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.87 | 0.67 | 21.87 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 21.87 | 2.83 | 21.87 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 21.83 | 5.83 | 21.83 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 21.79 | 5.83 | 21.79 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 21.82 | 5.17 | 21.82 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.74 | 1.50 | 21.74 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.83 | 20.51 | 0.83 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
Annual Sum or Average | 6.83 | 20.43 | 6.83 | 20.43 | 21.83 | 21.28 | 21.83 | 21.49 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.50 | 20.51 | 3.50 | 20.51 | 5.83 | 21.87 | 5.83 | 21.87 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 20.36 | 0.67 | 20.36 | 0.00 | 20.36 | 0.00 | 20.36 |
February | 0.17 | 20.49 | 0.17 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.70 | 0.17 | 21.70 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.84 | 0.17 | 21.84 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.67 | 0.17 | 21.67 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.68 | 0.33 | 21.68 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 21.75 | 3.33 | 21.75 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 21.75 | 2.00 | 21.75 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.76 | 1.50 | 21.76 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 20.50 | 0.33 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
Annual Sum or Average | 1.17 | 20.42 | 1.17 | 20.42 | 7.67 | 21.44 | 7.67 | 21.57 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 20.50 | 0.67 | 20.50 | 3.33 | 21.84 | 3.33 | 21.84 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.83 | 0.83 | 24.83 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.72 | 0.33 | 24.72 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 24.75 | 1.67 | 24.75 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 24.71 | 1.17 | 24.71 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 24.81 | 6.33 | 24.81 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.65 | 0.50 | 24.65 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 10.83 | 24.78 | 10.83 | 24.78 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 24.83 | 6.33 | 24.83 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 741.17 | 23.35 | 0.00 | 23.35 | 0.00 | 23.35 |
February | 672.00 | 22.96 | 0.00 | 22.96 | 0.00 | 22.96 |
March | 744.00 | 22.61 | 0.00 | 22.61 | 0.00 | 22.61 |
April | 720.00 | 22.41 | 0.00 | 22.41 | 0.00 | 22.41 |
May | 744.00 | 22.27 | 0.00 | 22.27 | 0.00 | 22.27 |
June | 720.00 | 22.68 | 0.00 | 22.68 | 0.00 | 22.68 |
July | 660.17 | 23.00 | 0.00 | 23.00 | 0.00 | 23.00 |
August | 319.50 | 23.18 | 119.50 | 23.37 | 0.00 | 23.37 |
September | 156.50 | 23.56 | 257.33 | 23.80 | 0.00 | 23.80 |
October | 275.67 | 23.87 | 207.50 | 23.92 | 0.00 | 23.92 |
November | 420.67 | 23.84 | 16.83 | 23.84 | 0.00 | 23.84 |
December | 714.17 | 23.73 | 0.00 | 23.73 | 0.00 | 23.73 |
Annual Sum or Average | 6887.83 | 23.00 | 601.17 | 23.08 | 0.00 | 23.08 |
Minimum of Months | 156.50 | 22.27 | 0.00 | 22.27 | 0.00 | 22.27 |
Maximum of Months | 744.00 | 23.87 | 257.33 | 23.92 | 0.00 | 23.92 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 734.67 | 21.13 | 352.67 | 21.09 | 352.67 | 21.07 |
February | 653.17 | 21.18 | 318.83 | 21.12 | 318.83 | 21.09 |
March | 703.17 | 21.24 | 105.83 | 21.23 | 99.50 | 21.20 |
April | 663.33 | 21.34 | 35.00 | 21.41 | 14.50 | 21.40 |
May | 676.50 | 21.59 | 21.00 | 21.65 | 0.00 | 21.65 |
June | 466.67 | 22.17 | 136.17 | 22.49 | 0.00 | 22.49 |
July | 249.50 | 22.44 | 320.83 | 23.10 | 0.00 | 23.10 |
August | 184.33 | 22.44 | 433.17 | 23.35 | 0.00 | 23.35 |
September | 437.33 | 21.98 | 202.50 | 22.55 | 0.00 | 22.55 |
October | 510.50 | 21.78 | 148.33 | 22.25 | 0.00 | 22.25 |
November | 682.67 | 21.23 | 107.33 | 21.25 | 93.83 | 21.22 |
December | 718.83 | 21.15 | 313.83 | 21.10 | 313.83 | 21.08 |
Annual Sum or Average | 6680.67 | 21.49 | 2495.50 | 21.74 | 1193.17 | 21.66 |
Minimum of Months | 184.33 | 21.13 | 21.00 | 21.09 | 0.00 | 21.07 |
Maximum of Months | 734.67 | 22.44 | 433.17 | 23.35 | 352.67 | 23.35 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.52 | 33.00 | 21.50 | 33.00 | 21.48 |
February | 672.00 | 21.62 | 31.83 | 21.59 | 31.83 | 21.57 |
March | 744.00 | 22.06 | 0.00 | 22.06 | 0.00 | 22.06 |
April | 690.83 | 22.35 | 1.83 | 22.36 | 0.00 | 22.36 |
May | 638.00 | 22.71 | 41.50 | 22.78 | 5.00 | 22.78 |
June | 279.83 | 23.04 | 286.83 | 23.44 | 24.33 | 23.45 |
July | 132.00 | 23.33 | 472.33 | 23.74 | 56.50 | 23.75 |
August | 63.00 | 23.23 | 494.50 | 23.81 | 9.83 | 23.81 |
September | 326.17 | 22.99 | 225.00 | 23.34 | 12.33 | 23.35 |
October | 522.17 | 22.95 | 105.83 | 23.10 | 1.33 | 23.10 |
November | 717.67 | 22.12 | 0.00 | 22.12 | 0.00 | 22.12 |
December | 744.00 | 21.75 | 2.33 | 21.75 | 2.33 | 21.75 |
Annual Sum or Average | 6273.67 | 22.22 | 1695.00 | 22.54 | 176.50 | 22.55 |
Minimum of Months | 63.00 | 21.52 | 0.00 | 21.50 | 0.00 | 21.48 |
Maximum of Months | 744.00 | 23.33 | 494.50 | 23.81 | 56.50 | 23.81 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.03 | 280.83 | 21.02 | 280.83 | 21.02 |
February | 672.00 | 21.02 | 312.33 | 21.02 | 312.33 | 21.01 |
March | 744.00 | 21.17 | 56.17 | 21.16 | 56.17 | 21.15 |
April | 720.00 | 21.60 | 5.67 | 21.60 | 5.67 | 21.60 |
May | 736.00 | 22.35 | 0.00 | 22.35 | 0.00 | 22.35 |
June | 494.67 | 23.11 | 32.33 | 23.16 | 0.00 | 23.16 |
July | 129.67 | 23.28 | 218.67 | 23.68 | 0.00 | 23.68 |
August | 177.00 | 23.41 | 210.67 | 23.69 | 0.00 | 23.69 |
September | 549.67 | 22.99 | 15.00 | 23.01 | 0.00 | 23.01 |
October | 742.50 | 22.47 | 0.00 | 22.47 | 0.00 | 22.47 |
November | 720.00 | 21.41 | 45.50 | 21.39 | 45.50 | 21.37 |
December | 744.00 | 21.05 | 96.00 | 21.04 | 96.00 | 21.04 |
Annual Sum or Average | 7173.50 | 21.82 | 1273.17 | 21.86 | 796.50 | 21.79 |
Minimum of Months | 129.67 | 21.02 | 0.00 | 21.02 | 0.00 | 21.01 |
Maximum of Months | 744.00 | 23.41 | 312.33 | 23.69 | 312.33 | 23.69 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.00 | 325.67 | 21.00 | 325.67 | 21.00 |
February | 672.00 | 21.00 | 364.50 | 21.00 | 364.50 | 21.00 |
March | 744.00 | 21.05 | 85.33 | 21.05 | 85.33 | 21.04 |
April | 720.00 | 21.39 | 9.33 | 21.39 | 9.33 | 21.38 |
May | 744.00 | 22.10 | 0.00 | 22.10 | 0.00 | 22.10 |
June | 628.67 | 22.98 | 0.00 | 22.98 | 0.00 | 22.98 |
July | 275.67 | 23.24 | 38.00 | 23.32 | 0.00 | 23.32 |
August | 341.50 | 23.31 | 87.17 | 23.42 | 0.00 | 23.42 |
September | 664.33 | 22.83 | 0.00 | 22.83 | 0.00 | 22.83 |
October | 744.00 | 22.18 | 0.00 | 22.18 | 0.00 | 22.18 |
November | 720.00 | 21.22 | 58.67 | 21.21 | 58.67 | 21.19 |
December | 744.00 | 21.00 | 159.17 | 21.00 | 159.17 | 21.00 |
Annual Sum or Average | 7742.17 | 21.78 | 1127.83 | 21.72 | 1002.67 | 21.65 |
Minimum of Months | 275.67 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
Maximum of Months | 744.00 | 23.31 | 364.50 | 23.42 | 364.50 | 23.42 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 283.50 | 22.59 | 413.33 | 23.18 | 134.17 | 23.31 |
February | 242.17 | 22.55 | 336.17 | 23.24 | 112.00 | 23.36 |
March | 260.17 | 22.87 | 494.33 | 23.24 | 156.33 | 23.37 |
April | 260.67 | 23.22 | 560.00 | 23.27 | 191.00 | 23.41 |
May | 297.67 | 23.57 | 647.83 | 23.31 | 254.33 | 23.45 |
June | 298.00 | 23.91 | 688.67 | 23.32 | 291.17 | 23.47 |
July | 314.83 | 23.96 | 737.33 | 23.29 | 314.83 | 23.45 |
August | 312.83 | 23.97 | 729.33 | 23.31 | 312.67 | 23.46 |
September | 295.00 | 23.84 | 670.17 | 23.34 | 279.67 | 23.48 |
October | 277.67 | 23.55 | 621.17 | 23.34 | 235.33 | 23.48 |
November | 248.50 | 22.98 | 506.67 | 23.27 | 159.00 | 23.40 |
December | 245.17 | 22.69 | 412.00 | 23.28 | 130.17 | 23.40 |
Annual Sum or Average | 3336.17 | 23.35 | 6817.00 | 23.29 | 2570.67 | 23.43 |
Minimum of Months | 242.17 | 22.55 | 336.17 | 23.18 | 112.00 | 23.31 |
Maximum of Months | 314.83 | 23.97 | 737.33 | 23.34 | 314.83 | 23.48 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 715.83 | 21.62 | 84.50 | 21.58 | 78.17 | 21.53 |
February | 628.00 | 21.79 | 48.17 | 21.79 | 36.00 | 21.75 |
March | 660.33 | 22.10 | 37.33 | 22.20 | 0.00 | 22.20 |
April | 543.17 | 22.15 | 84.17 | 22.36 | 0.00 | 22.36 |
May | 496.17 | 22.56 | 164.33 | 22.82 | 52.00 | 22.88 |
June | 320.00 | 23.36 | 510.33 | 23.51 | 219.33 | 23.58 |
July | 297.33 | 23.83 | 702.83 | 23.69 | 285.67 | 23.74 |
August | 229.33 | 23.87 | 709.17 | 23.80 | 217.50 | 23.83 |
September | 269.67 | 23.09 | 506.33 | 23.53 | 149.00 | 23.57 |
October | 341.67 | 23.01 | 392.50 | 23.45 | 92.83 | 23.49 |
November | 623.83 | 22.06 | 45.33 | 22.18 | 2.33 | 22.19 |
December | 699.50 | 21.82 | 33.83 | 21.87 | 11.17 | 21.86 |
Annual Sum or Average | 5824.83 | 22.34 | 3318.83 | 22.80 | 1144.00 | 22.89 |
Minimum of Months | 229.33 | 21.62 | 33.83 | 21.58 | 0.00 | 21.53 |
Maximum of Months | 715.83 | 23.87 | 709.17 | 23.80 | 285.67 | 23.83 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 22.04 | 7.00 | 22.03 | 7.00 | 22.02 |
February | 672.00 | 22.17 | 0.17 | 22.17 | 0.17 | 22.17 |
March | 734.33 | 22.52 | 0.00 | 22.52 | 0.00 | 22.52 |
April | 601.50 | 22.62 | 38.33 | 22.70 | 0.00 | 22.70 |
May | 504.00 | 22.88 | 125.50 | 23.07 | 43.17 | 23.12 |
June | 331.17 | 23.49 | 396.00 | 23.69 | 193.50 | 23.74 |
July | 267.17 | 23.91 | 580.67 | 23.83 | 251.67 | 23.86 |
August | 195.00 | 23.94 | 635.50 | 23.83 | 186.17 | 23.86 |
September | 259.83 | 23.40 | 401.33 | 23.66 | 132.17 | 23.71 |
October | 386.83 | 23.29 | 278.17 | 23.49 | 72.83 | 23.54 |
November | 673.17 | 22.57 | 8.83 | 22.58 | 2.00 | 22.59 |
December | 744.00 | 22.30 | 0.00 | 22.30 | 0.00 | 22.30 |
Annual Sum or Average | 6113.00 | 22.69 | 2471.50 | 23.01 | 888.67 | 23.09 |
Minimum of Months | 195.00 | 22.04 | 0.00 | 22.03 | 0.00 | 22.02 |
Maximum of Months | 744.00 | 23.94 | 635.50 | 23.83 | 251.67 | 23.86 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.84 | 477.50 | 20.76 | 477.50 | 20.73 |
February | 672.00 | 20.98 | 433.83 | 20.89 | 433.83 | 20.85 |
March | 743.83 | 21.25 | 122.67 | 21.17 | 122.67 | 21.12 |
April | 702.00 | 21.37 | 21.50 | 21.34 | 21.33 | 21.31 |
May | 703.17 | 21.53 | 2.17 | 21.54 | 0.50 | 21.54 |
June | 619.67 | 21.47 | 8.83 | 21.49 | 2.17 | 21.50 |
July | 610.33 | 21.40 | 18.33 | 21.45 | 1.67 | 21.46 |
August | 595.33 | 21.36 | 35.50 | 21.47 | 1.00 | 21.47 |
September | 640.17 | 21.49 | 12.00 | 21.52 | 2.50 | 21.53 |
October | 688.33 | 21.49 | 2.67 | 21.50 | 1.00 | 21.50 |
November | 720.00 | 21.18 | 168.83 | 21.10 | 168.83 | 21.05 |
December | 744.00 | 20.95 | 437.67 | 20.87 | 437.67 | 20.83 |
Annual Sum or Average | 8182.83 | 21.27 | 1741.50 | 21.19 | 1670.67 | 21.12 |
Minimum of Months | 595.33 | 20.84 | 2.17 | 20.76 | 0.50 | 20.73 |
Maximum of Months | 744.00 | 21.53 | 477.50 | 21.54 | 477.50 | 21.54 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.64 | 596.17 | 20.59 | 596.17 | 20.57 |
February | 672.00 | 20.70 | 574.67 | 20.66 | 574.67 | 20.64 |
March | 741.33 | 21.04 | 216.00 | 20.96 | 213.83 | 20.91 |
April | 689.33 | 21.34 | 38.17 | 21.36 | 26.33 | 21.33 |
May | 639.67 | 21.72 | 60.50 | 22.02 | 7.67 | 22.04 |
June | 531.00 | 22.18 | 166.33 | 22.82 | 89.00 | 23.02 |
July | 575.17 | 21.80 | 97.83 | 22.16 | 59.50 | 22.34 |
August | 563.50 | 21.65 | 75.50 | 21.95 | 18.17 | 22.00 |
September | 591.17 | 21.97 | 93.83 | 22.32 | 38.00 | 22.41 |
October | 680.33 | 21.65 | 42.83 | 21.77 | 20.50 | 21.81 |
November | 720.00 | 20.97 | 268.00 | 20.86 | 268.00 | 20.81 |
December | 744.00 | 20.70 | 628.67 | 20.67 | 628.67 | 20.65 |
Annual Sum or Average | 7891.50 | 21.31 | 2858.50 | 21.33 | 2540.50 | 21.25 |
Minimum of Months | 531.00 | 20.64 | 38.17 | 20.59 | 7.67 | 20.57 |
Maximum of Months | 744.00 | 22.18 | 628.67 | 22.82 | 628.67 | 23.02 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.93 | 335.17 | 20.87 | 335.17 | 20.83 |
February | 672.00 | 20.92 | 366.33 | 20.86 | 366.33 | 20.84 |
March | 744.00 | 21.17 | 59.33 | 21.14 | 59.33 | 21.12 |
April | 720.00 | 21.42 | 0.00 | 21.42 | 0.00 | 21.42 |
May | 733.00 | 21.83 | 7.17 | 21.85 | 2.83 | 21.85 |
June | 698.67 | 22.26 | 96.50 | 22.43 | 89.67 | 22.54 |
July | 727.83 | 22.04 | 66.67 | 22.19 | 62.00 | 22.30 |
August | 732.50 | 21.97 | 17.33 | 22.00 | 17.33 | 22.03 |
September | 707.17 | 22.08 | 36.67 | 22.15 | 35.67 | 22.21 |
October | 744.00 | 21.60 | 13.83 | 21.62 | 13.83 | 21.63 |
November | 720.00 | 21.17 | 68.17 | 21.13 | 68.17 | 21.10 |
December | 744.00 | 20.98 | 184.50 | 20.91 | 184.50 | 20.87 |
Annual Sum or Average | 8687.17 | 21.53 | 1251.67 | 21.50 | 1234.83 | 21.47 |
Minimum of Months | 672.00 | 20.92 | 0.00 | 20.86 | 0.00 | 20.83 |
Maximum of Months | 744.00 | 22.26 | 366.33 | 22.43 | 366.33 | 22.54 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.84 | 481.17 | 20.77 | 481.17 | 20.74 |
February | 672.00 | 21.00 | 412.33 | 20.91 | 412.33 | 20.88 |
March | 744.00 | 21.30 | 130.33 | 21.22 | 130.33 | 21.16 |
April | 707.50 | 21.44 | 21.83 | 21.41 | 21.83 | 21.38 |
May | 716.67 | 21.59 | 0.67 | 21.59 | 0.33 | 21.59 |
June | 614.33 | 21.46 | 4.17 | 21.47 | 2.33 | 21.48 |
July | 590.50 | 21.34 | 4.00 | 21.35 | 1.33 | 21.35 |
August | 574.67 | 21.29 | 2.33 | 21.30 | 0.50 | 21.30 |
September | 623.67 | 21.46 | 4.50 | 21.47 | 2.83 | 21.48 |
October | 690.50 | 21.53 | 1.00 | 21.53 | 0.83 | 21.53 |
November | 720.00 | 21.22 | 157.17 | 21.14 | 157.17 | 21.08 |
December | 744.00 | 20.95 | 435.50 | 20.87 | 435.50 | 20.83 |
Annual Sum or Average | 8141.83 | 21.28 | 1655.00 | 21.19 | 1646.50 | 21.12 |
Minimum of Months | 574.67 | 20.84 | 0.67 | 20.77 | 0.33 | 20.74 |
Maximum of Months | 744.00 | 21.59 | 481.17 | 21.59 | 481.17 | 21.59 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.64 | 594.00 | 20.59 | 594.00 | 20.57 |
February | 672.00 | 20.70 | 560.33 | 20.66 | 560.33 | 20.65 |
March | 744.00 | 21.08 | 197.83 | 21.01 | 197.83 | 20.96 |
April | 715.67 | 21.47 | 28.00 | 21.45 | 25.50 | 21.42 |
May | 675.00 | 21.87 | 35.83 | 22.02 | 9.50 | 22.06 |
June | 527.83 | 22.13 | 151.83 | 22.62 | 95.83 | 22.81 |
July | 547.83 | 21.79 | 102.00 | 22.23 | 62.83 | 22.44 |
August | 511.67 | 21.54 | 80.33 | 21.97 | 21.17 | 22.07 |
September | 613.17 | 22.07 | 79.33 | 22.34 | 40.67 | 22.44 |
October | 732.33 | 21.77 | 26.83 | 21.82 | 21.67 | 21.85 |
November | 720.00 | 21.00 | 233.50 | 20.89 | 233.50 | 20.83 |
December | 744.00 | 20.69 | 608.83 | 20.65 | 608.83 | 20.64 |
Annual Sum or Average | 7947.50 | 21.35 | 2698.67 | 21.33 | 2471.67 | 21.27 |
Minimum of Months | 511.67 | 20.64 | 26.83 | 20.59 | 9.50 | 20.57 |
Maximum of Months | 744.00 | 22.13 | 608.83 | 22.62 | 608.83 | 22.81 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.00 | 239.17 | 21.00 | 239.17 | 21.00 |
February | 672.00 | 21.01 | 249.00 | 21.01 | 249.00 | 21.00 |
March | 744.00 | 21.12 | 23.00 | 21.11 | 23.00 | 21.11 |
April | 720.00 | 21.51 | 0.83 | 21.51 | 0.83 | 21.51 |
May | 744.00 | 22.16 | 0.00 | 22.16 | 0.00 | 22.16 |
June | 689.50 | 23.04 | 0.00 | 23.04 | 0.00 | 23.04 |
July | 557.83 | 23.25 | 0.00 | 23.25 | 0.00 | 23.25 |
August | 396.33 | 23.33 | 12.67 | 23.35 | 0.00 | 23.35 |
September | 638.17 | 22.82 | 0.00 | 22.82 | 0.00 | 22.82 |
October | 744.00 | 22.34 | 0.00 | 22.34 | 0.00 | 22.34 |
November | 720.00 | 21.22 | 29.50 | 21.21 | 29.50 | 21.21 |
December | 744.00 | 21.01 | 88.67 | 21.01 | 88.67 | 21.01 |
Annual Sum or Average | 8113.83 | 21.89 | 642.83 | 21.83 | 630.17 | 21.78 |
Minimum of Months | 396.33 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
Maximum of Months | 744.00 | 23.33 | 249.00 | 23.35 | 249.00 | 23.35 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.74 | 593.17 | 20.68 | 593.17 | 20.66 |
February | 672.00 | 20.87 | 528.83 | 20.80 | 528.83 | 20.77 |
March | 741.00 | 21.16 | 219.17 | 21.06 | 219.17 | 20.99 |
April | 694.00 | 21.30 | 59.00 | 21.25 | 57.83 | 21.20 |
May | 684.50 | 21.47 | 12.67 | 21.49 | 6.50 | 21.49 |
June | 599.00 | 21.40 | 34.33 | 21.49 | 9.00 | 21.51 |
July | 591.50 | 21.34 | 51.83 | 21.50 | 5.00 | 21.51 |
August | 581.33 | 21.32 | 64.33 | 21.52 | 2.00 | 21.52 |
September | 626.50 | 21.44 | 35.50 | 21.51 | 13.83 | 21.52 |
October | 680.50 | 21.44 | 27.83 | 21.45 | 21.33 | 21.44 |
November | 719.17 | 21.08 | 267.00 | 20.98 | 267.00 | 20.92 |
December | 744.00 | 20.84 | 561.83 | 20.78 | 561.83 | 20.75 |
Annual Sum or Average | 8077.50 | 21.19 | 2455.50 | 21.12 | 2285.50 | 21.04 |
Minimum of Months | 581.33 | 20.74 | 12.67 | 20.68 | 2.00 | 20.66 |
Maximum of Months | 744.00 | 21.47 | 593.17 | 21.52 | 593.17 | 21.52 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.55 | 680.33 | 20.53 | 680.33 | 20.52 |
February | 672.00 | 20.61 | 627.33 | 20.59 | 627.33 | 20.59 |
March | 741.00 | 20.95 | 323.83 | 20.85 | 321.33 | 20.79 |
April | 680.33 | 21.27 | 96.83 | 21.29 | 77.00 | 21.23 |
May | 627.17 | 21.73 | 85.00 | 22.15 | 24.67 | 22.23 |
June | 517.33 | 22.27 | 201.33 | 23.00 | 109.00 | 23.25 |
July | 560.50 | 21.78 | 130.00 | 22.22 | 73.33 | 22.41 |
August | 545.33 | 21.58 | 102.17 | 21.96 | 23.17 | 22.02 |
September | 575.00 | 21.92 | 122.00 | 22.34 | 57.50 | 22.45 |
October | 671.67 | 21.56 | 113.67 | 21.69 | 84.33 | 21.68 |
November | 720.00 | 20.85 | 360.83 | 20.75 | 360.83 | 20.70 |
December | 744.00 | 20.60 | 696.67 | 20.58 | 696.67 | 20.57 |
Annual Sum or Average | 7798.33 | 21.25 | 3540.00 | 21.28 | 3135.50 | 21.21 |
Minimum of Months | 517.33 | 20.55 | 85.00 | 20.53 | 23.17 | 20.52 |
Maximum of Months | 744.00 | 22.27 | 696.67 | 23.00 | 696.67 | 23.25 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 737.83 | 21.11 | 335.17 | 21.00 | 335.17 | 20.94 |
February | 666.83 | 21.30 | 272.50 | 21.16 | 272.50 | 21.09 |
March | 716.83 | 21.32 | 89.67 | 21.27 | 89.67 | 21.23 |
April | 689.17 | 21.40 | 12.67 | 21.38 | 12.50 | 21.36 |
May | 705.50 | 21.54 | 0.67 | 21.54 | 0.67 | 21.54 |
June | 634.00 | 21.49 | 15.83 | 21.52 | 15.83 | 21.54 |
July | 626.67 | 21.44 | 8.33 | 21.46 | 8.33 | 21.48 |
August | 611.33 | 21.40 | 29.67 | 21.48 | 2.17 | 21.49 |
September | 621.17 | 21.44 | 32.50 | 21.52 | 7.17 | 21.53 |
October | 634.00 | 21.39 | 28.33 | 21.47 | 2.50 | 21.47 |
November | 699.33 | 21.39 | 53.67 | 21.36 | 53.67 | 21.33 |
December | 730.67 | 21.21 | 259.33 | 21.09 | 259.33 | 21.02 |
Annual Sum or Average | 8073.33 | 21.36 | 1138.33 | 21.32 | 1059.50 | 21.27 |
Minimum of Months | 611.33 | 21.11 | 0.67 | 21.00 | 0.67 | 20.94 |
Maximum of Months | 737.83 | 21.54 | 335.17 | 21.54 | 335.17 | 21.54 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 559.00 | 23.06 | 12.50 | 23.08 | 0.00 | 23.08 |
February | 537.33 | 23.11 | 0.00 | 23.11 | 0.00 | 23.11 |
March | 359.33 | 23.13 | 78.17 | 23.28 | 0.00 | 23.28 |
April | 162.33 | 23.14 | 263.83 | 23.65 | 0.00 | 23.65 |
May | 69.00 | 23.75 | 570.67 | 23.91 | 48.67 | 23.92 |
June | 189.33 | 24.00 | 706.33 | 23.96 | 189.33 | 23.97 |
July | 237.67 | 24.00 | 744.00 | 23.98 | 237.67 | 23.99 |
August | 183.17 | 24.00 | 741.67 | 23.97 | 183.17 | 23.98 |
September | 134.67 | 23.99 | 656.83 | 23.94 | 134.33 | 23.95 |
October | 193.00 | 23.58 | 414.83 | 23.79 | 83.67 | 23.81 |
November | 349.83 | 23.11 | 93.83 | 23.29 | 5.17 | 23.30 |
December | 498.83 | 23.10 | 3.33 | 23.10 | 0.00 | 23.10 |
Annual Sum or Average | 3473.50 | 23.33 | 4286.00 | 23.67 | 882.00 | 23.71 |
Minimum of Months | 69.00 | 23.06 | 0.00 | 23.08 | 0.00 | 23.08 |
Maximum of Months | 559.00 | 24.00 | 744.00 | 23.98 | 237.67 | 23.99 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 410.33 | 23.15 | 59.50 | 23.26 | 0.00 | 23.26 |
February | 409.17 | 23.23 | 14.67 | 23.25 | 0.00 | 23.25 |
March | 186.50 | 23.17 | 210.83 | 23.60 | 0.00 | 23.60 |
April | 69.50 | 23.26 | 409.83 | 23.86 | 0.00 | 23.86 |
May | 39.33 | 23.99 | 667.00 | 23.96 | 39.17 | 23.96 |
June | 170.33 | 24.00 | 714.00 | 23.98 | 170.33 | 23.99 |
July | 217.50 | 24.00 | 744.00 | 23.99 | 217.50 | 23.99 |
August | 167.33 | 24.00 | 744.00 | 23.99 | 167.33 | 23.99 |
September | 120.50 | 24.00 | 701.00 | 23.96 | 120.50 | 23.97 |
October | 109.17 | 23.76 | 472.50 | 23.90 | 69.67 | 23.91 |
November | 191.17 | 23.17 | 202.50 | 23.58 | 2.83 | 23.59 |
December | 328.00 | 23.13 | 45.17 | 23.24 | 0.00 | 23.24 |
Annual Sum or Average | 2418.83 | 23.45 | 4985.00 | 23.80 | 787.33 | 23.82 |
Minimum of Months | 39.33 | 23.13 | 14.67 | 23.24 | 0.00 | 23.24 |
Maximum of Months | 410.33 | 24.00 | 744.00 | 23.99 | 217.50 | 23.99 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 521.50 | 23.78 | 615.00 | 23.86 | 458.33 | 23.90 |
February | 479.67 | 23.75 | 539.50 | 23.86 | 414.33 | 23.89 |
March | 515.83 | 23.95 | 670.17 | 23.91 | 502.50 | 23.93 |
April | 509.17 | 23.99 | 685.67 | 23.92 | 509.17 | 23.94 |
May | 552.50 | 23.99 | 741.83 | 23.93 | 552.50 | 23.95 |
June | 563.17 | 24.00 | 720.00 | 23.97 | 563.17 | 23.98 |
July | 601.83 | 23.99 | 744.00 | 23.98 | 601.83 | 23.98 |
August | 597.17 | 24.01 | 744.00 | 23.99 | 597.17 | 24.00 |
September | 549.00 | 24.00 | 720.00 | 23.96 | 549.00 | 23.97 |
October | 535.83 | 23.99 | 722.83 | 23.93 | 535.83 | 23.95 |
November | 501.67 | 23.94 | 652.50 | 23.91 | 488.00 | 23.93 |
December | 504.50 | 23.89 | 623.67 | 23.91 | 475.33 | 23.93 |
Annual Sum or Average | 6431.83 | 23.94 | 8179.17 | 23.93 | 6247.17 | 23.95 |
Minimum of Months | 479.67 | 23.75 | 539.50 | 23.86 | 414.33 | 23.89 |
Maximum of Months | 601.83 | 24.01 | 744.00 | 23.99 | 601.83 | 24.00 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.01 | 266.83 | 21.01 | 266.83 | 21.00 |
February | 672.00 | 21.02 | 283.67 | 21.02 | 283.67 | 21.01 |
March | 744.00 | 21.15 | 24.50 | 21.15 | 24.50 | 21.14 |
April | 718.83 | 21.57 | 0.00 | 21.57 | 0.00 | 21.57 |
May | 706.33 | 22.23 | 10.67 | 22.26 | 0.00 | 22.26 |
June | 376.50 | 22.96 | 128.17 | 23.18 | 0.00 | 23.18 |
July | 46.00 | 23.05 | 443.50 | 23.76 | 0.00 | 23.76 |
August | 110.67 | 23.13 | 391.50 | 23.71 | 0.00 | 23.71 |
September | 507.00 | 22.68 | 81.00 | 22.84 | 0.00 | 22.84 |
October | 721.83 | 22.15 | 3.33 | 22.15 | 0.00 | 22.15 |
November | 720.00 | 21.17 | 38.00 | 21.16 | 38.00 | 21.15 |
December | 744.00 | 21.02 | 91.17 | 21.02 | 91.17 | 21.01 |
Annual Sum or Average | 6811.17 | 21.63 | 1762.33 | 21.85 | 704.17 | 21.79 |
Minimum of Months | 46.00 | 21.01 | 0.00 | 21.01 | 0.00 | 21.00 |
Maximum of Months | 744.00 | 23.13 | 443.50 | 23.76 | 283.67 | 23.76 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.35674 | 27.35738 | 0.09180 | 5.36677 |
February | 672.00000 | 22.96261 | 23.85668 | -0.0321 | 5.19980 |
March | 744.00000 | 22.61417 | 32.87842 | -0.0614 | 5.26562 |
April | 720.00000 | 22.41156 | 39.44177 | -0.0718 | 5.32227 |
May | 744.00000 | 22.26629 | 48.17438 | -1.1365 | 32.44219 |
June | 720.00000 | 22.67688 | 58.20711 | -0.9206 | 23.21816 |
July | 744.00000 | 23.07127 | 60.84726 | -0.7554 | 17.25922 |
August | 744.00000 | 23.48468 | 56.74725 | -0.6283 | 13.52635 |
September | 720.00000 | 23.78761 | 51.36146 | -0.5493 | 11.55181 |
October | 744.00000 | 23.89054 | 42.36162 | 0.34551 | 7.72967 |
November | 720.00000 | 23.88730 | 32.30884 | 0.27167 | 6.64793 |
December | 744.00000 | 23.73838 | 26.75381 | 0.18956 | 5.85080 |
Annual Sum or Average | 8760.00000 | 23.18065 | 41.79804 | -0.2729 | 11.66701 |
Minimum of Months | 672.00000 | 22.26629 | 23.85668 | -1.1365 | 5.19980 |
Maximum of Months | 744.00000 | 23.89054 | 60.84726 | 0.34551 | 32.44219 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.16129 | 29.05322 | -0.4939 | 10.91050 |
February | 672.00000 | 21.25800 | 24.47336 | -0.4673 | 10.65931 |
March | 744.00000 | 21.37896 | 33.75330 | -0.3299 | 8.51915 |
April | 720.00000 | 21.52216 | 40.05046 | -0.2258 | 7.61783 |
May | 744.00000 | 21.75534 | 48.43552 | -1.1614 | 35.04762 |
June | 720.00000 | 22.58033 | 57.61524 | -0.7645 | 18.85305 |
July | 744.00000 | 23.06245 | 60.23352 | -0.5514 | 12.50314 |
August | 744.00000 | 23.30227 | 56.38705 | -0.4671 | 11.10261 |
September | 720.00000 | 22.61365 | 53.77225 | -0.7660 | 20.70683 |
October | 744.00000 | 22.38455 | 44.76796 | 0.09424 | 7.76038 |
November | 720.00000 | 21.35827 | 35.74354 | -0.3250 | 8.47736 |
December | 744.00000 | 21.23995 | 28.97524 | -0.4436 | 10.13113 |
Annual Sum or Average | 8760.00000 | 21.97338 | 42.87802 | -0.4917 | 13.54335 |
Minimum of Months | 672.00000 | 21.16129 | 24.47336 | -1.1614 | 7.61783 |
Maximum of Months | 744.00000 | 23.30227 | 60.23352 | 0.09424 | 35.04762 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.51840 | 30.68913 | -0.3317 | 7.69600 |
February | 672.00000 | 21.62123 | 26.19434 | -0.3297 | 7.63797 |
March | 744.00000 | 22.05526 | 34.74458 | -0.1603 | 5.97029 |
April | 720.00000 | 22.40993 | 40.37913 | -0.0304 | 5.76116 |
May | 744.00000 | 22.84904 | 47.77728 | -0.8719 | 21.86614 |
June | 720.00000 | 23.42131 | 57.03382 | -0.5892 | 12.81576 |
July | 744.00000 | 23.62183 | 60.22677 | -0.4851 | 10.21117 |
August | 744.00000 | 23.71505 | 56.97937 | -0.4665 | 9.81415 |
September | 720.00000 | 23.38429 | 53.61682 | -0.6254 | 14.00315 |
October | 744.00000 | 23.15137 | 45.26165 | 0.20346 | 6.51753 |
November | 720.00000 | 22.12727 | 36.48000 | -0.1311 | 5.95978 |
December | 744.00000 | 21.75190 | 30.43245 | -0.2696 | 6.82541 |
Annual Sum or Average | 8760.00000 | 22.64172 | 43.41968 | -0.3407 | 9.60543 |
Minimum of Months | 672.00000 | 21.51840 | 26.19434 | -0.8719 | 5.76116 |
Maximum of Months | 744.00000 | 23.71505 | 60.22677 | 0.20346 | 21.86614 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.81313 | 24.34688 | 0.52573 | 13.66889 |
February | 672.00000 | 22.82255 | 20.30166 | 0.50414 | 13.19334 |
March | 744.00000 | 22.87655 | 28.73343 | 0.60437 | 15.51408 |
April | 720.00000 | 22.91202 | 34.74831 | 0.67496 | 17.37298 |
May | 744.00000 | 22.94956 | 42.80366 | 0.03987 | 10.54193 |
June | 720.00000 | 22.97852 | 53.66135 | 0.16007 | 10.78806 |
July | 744.00000 | 22.98572 | 57.53459 | 0.20578 | 10.85172 |
August | 744.00000 | 22.99181 | 54.62725 | 0.19842 | 10.91544 |
September | 720.00000 | 22.98958 | 50.07533 | 0.12837 | 10.63330 |
October | 744.00000 | 22.97365 | 41.08521 | 0.75733 | 19.82814 |
November | 720.00000 | 22.91597 | 30.49280 | 0.62743 | 16.04354 |
December | 744.00000 | 22.85723 | 24.31721 | 0.54852 | 14.01904 |
Annual Sum or Average | 8760.00000 | 22.92272 | 38.67034 | 0.41403 | 13.61662 |
Minimum of Months | 672.00000 | 22.81313 | 20.30166 | 0.03987 | 10.54193 |
Maximum of Months | 744.00000 | 22.99181 | 57.53459 | 0.75733 | 19.82814 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.69919 | 33.91469 | -0.2646 | 7.53820 |
February | 672.00000 | 21.91888 | 29.34374 | -0.2125 | 7.18742 |
March | 744.00000 | 22.27861 | 37.98735 | -0.0351 | 6.28327 |
April | 720.00000 | 22.49084 | 43.74656 | 0.07569 | 6.62920 |
May | 744.00000 | 22.84396 | 51.42049 | -0.7295 | 17.63979 |
June | 720.00000 | 23.33114 | 60.78666 | -0.4415 | 9.89372 |
July | 744.00000 | 23.57184 | 63.66218 | -0.3004 | 7.38026 |
August | 744.00000 | 23.73296 | 60.11677 | -0.2366 | 6.75384 |
September | 720.00000 | 23.43784 | 56.83370 | -0.4114 | 10.27895 |
October | 744.00000 | 23.40203 | 48.08214 | 0.40428 | 9.82726 |
November | 720.00000 | 22.27099 | 39.69076 | -0.0256 | 6.41881 |
December | 744.00000 | 21.93559 | 33.58949 | -0.1834 | 6.89582 |
Annual Sum or Average | 8760.00000 | 22.74806 | 46.69951 | -0.1965 | 8.57463 |
Minimum of Months | 672.00000 | 21.69919 | 29.34374 | -0.7295 | 6.28327 |
Maximum of Months | 744.00000 | 23.73296 | 63.66218 | 0.40428 | 17.63979 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.04161 | 32.91751 | -0.1790 | 6.25988 |
February | 672.00000 | 22.16895 | 28.52043 | -0.1688 | 6.11935 |
March | 744.00000 | 22.53712 | 36.96555 | -0.0113 | 5.53755 |
April | 720.00000 | 22.79594 | 42.57920 | 0.09991 | 5.97764 |
May | 744.00000 | 23.14157 | 50.00784 | -0.7185 | 16.74707 |
June | 720.00000 | 23.49918 | 59.46174 | -0.4983 | 10.76641 |
July | 744.00000 | 23.62413 | 62.67041 | -0.4143 | 8.91266 |
August | 744.00000 | 23.71461 | 59.44324 | -0.3947 | 8.48711 |
September | 720.00000 | 23.56164 | 55.81395 | -0.4988 | 10.82157 |
October | 744.00000 | 23.47405 | 47.40038 | 0.33026 | 7.85737 |
November | 720.00000 | 22.64699 | 38.53806 | 0.02914 | 5.73177 |
December | 744.00000 | 22.29536 | 32.61126 | -0.1094 | 5.77756 |
Annual Sum or Average | 8760.00000 | 22.96308 | 45.67907 | -0.2114 | 8.26635 |
Minimum of Months | 672.00000 | 22.04161 | 28.52043 | -0.7185 | 5.53755 |
Maximum of Months | 744.00000 | 23.71461 | 62.67041 | 0.33026 | 16.74707 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.84436 | 42.27887 | -0.5752 | 12.53886 |
February | 672.00000 | 20.97729 | 37.36810 | -0.5540 | 12.16800 |
March | 744.00000 | 21.24749 | 45.56517 | -0.3753 | 8.75420 |
April | 720.00000 | 21.41973 | 49.44698 | -0.2613 | 7.42624 |
May | 744.00000 | 21.63083 | 52.96431 | -1.2399 | 38.49266 |
June | 720.00000 | 21.72532 | 54.46686 | -1.1013 | 32.16572 |
July | 744.00000 | 21.74232 | 53.93725 | -1.0661 | 30.64820 |
August | 744.00000 | 21.74497 | 51.97145 | -1.0572 | 30.40178 |
September | 720.00000 | 21.69505 | 54.03936 | -1.1524 | 34.55530 |
October | 744.00000 | 21.63158 | 50.44830 | -0.1399 | 6.53777 |
November | 720.00000 | 21.18008 | 47.94453 | -0.3995 | 9.03431 |
December | 744.00000 | 20.95346 | 42.07670 | -0.5318 | 11.49156 |
Annual Sum or Average | 8760.00000 | 21.40168 | 48.60203 | -0.7055 | 19.56429 |
Minimum of Months | 672.00000 | 20.84436 | 37.36810 | -1.2399 | 6.53777 |
Maximum of Months | 744.00000 | 21.74497 | 54.46686 | -0.1399 | 38.49266 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.64317 | 42.74884 | -0.6428 | 14.17944 |
February | 672.00000 | 20.69772 | 37.94821 | -0.6498 | 14.38776 |
March | 744.00000 | 21.05122 | 46.08495 | -0.4467 | 9.78043 |
April | 720.00000 | 21.45877 | 49.70526 | -0.2719 | 7.79751 |
May | 744.00000 | 22.11581 | 52.38922 | -1.1135 | 34.42023 |
June | 720.00000 | 22.69292 | 54.18767 | -0.8207 | 23.82487 |
July | 744.00000 | 22.20318 | 54.80414 | -0.9328 | 26.12467 |
August | 744.00000 | 22.13819 | 52.92598 | -0.9615 | 26.87281 |
September | 720.00000 | 22.35249 | 54.85617 | -0.9879 | 28.65689 |
October | 744.00000 | 21.83844 | 52.11871 | -0.1278 | 6.98705 |
November | 720.00000 | 20.96506 | 48.64589 | -0.4741 | 10.26632 |
December | 744.00000 | 20.70159 | 42.68791 | -0.6145 | 13.26518 |
Annual Sum or Average | 8760.00000 | 21.57549 | 49.15329 | -0.6709 | 18.08151 |
Minimum of Months | 672.00000 | 20.64317 | 37.94821 | -1.1135 | 6.98705 |
Maximum of Months | 744.00000 | 22.69292 | 54.85617 | -0.1278 | 34.42023 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.92739 | 39.32546 | -0.5266 | 11.09386 |
February | 672.00000 | 20.91924 | 34.82212 | -0.5567 | 11.73189 |
March | 744.00000 | 21.16557 | 43.00880 | -0.4124 | 8.72651 |
April | 720.00000 | 21.42336 | 46.76859 | -0.2965 | 7.21356 |
May | 744.00000 | 21.86343 | 49.87801 | -1.2564 | 38.98662 |
June | 720.00000 | 22.31249 | 56.12852 | -1.0245 | 29.05585 |
July | 744.00000 | 22.08549 | 56.73531 | -1.0788 | 31.27914 |
August | 744.00000 | 21.99627 | 54.70279 | -1.1310 | 33.23433 |
September | 720.00000 | 22.10899 | 54.16681 | -1.1363 | 33.53633 |
October | 744.00000 | 21.59960 | 50.54809 | -0.2179 | 6.64862 |
November | 720.00000 | 21.16912 | 45.05641 | -0.3987 | 8.54585 |
December | 744.00000 | 20.98308 | 39.32315 | -0.5057 | 10.46137 |
Annual Sum or Average | 8760.00000 | 21.54905 | 47.61041 | -0.7130 | 19.26681 |
Minimum of Months | 672.00000 | 20.91924 | 34.82212 | -1.2564 | 6.64862 |
Maximum of Months | 744.00000 | 22.31249 | 56.73531 | -0.2179 | 38.98662 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.84023 | 42.25675 | -0.5740 | 12.44081 |
February | 672.00000 | 20.99871 | 37.30887 | -0.5455 | 11.89124 |
March | 744.00000 | 21.29677 | 45.45546 | -0.3688 | 8.69104 |
April | 720.00000 | 21.47375 | 48.97418 | -0.2493 | 7.37537 |
May | 744.00000 | 21.65725 | 52.54545 | -1.2280 | 37.97794 |
June | 720.00000 | 21.73458 | 54.58907 | -1.1077 | 32.41639 |
July | 744.00000 | 21.74837 | 53.77408 | -1.0669 | 30.69038 |
August | 744.00000 | 21.75213 | 51.90502 | -1.0554 | 30.32855 |
September | 720.00000 | 21.71026 | 53.84536 | -1.1457 | 34.26367 |
October | 744.00000 | 21.65940 | 50.38545 | -0.1365 | 6.51605 |
November | 720.00000 | 21.21597 | 47.62060 | -0.3846 | 8.83566 |
December | 744.00000 | 20.95342 | 42.06158 | -0.5277 | 11.36545 |
Annual Sum or Average | 8760.00000 | 21.42229 | 48.45321 | -0.7002 | 19.44659 |
Minimum of Months | 672.00000 | 20.84023 | 37.30887 | -1.2280 | 6.51605 |
Maximum of Months | 744.00000 | 21.75213 | 54.58907 | -0.1365 | 37.97794 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.63688 | 42.73409 | -0.6423 | 14.17454 |
February | 672.00000 | 20.70058 | 37.91084 | -0.6450 | 14.21732 |
March | 744.00000 | 21.07700 | 45.97845 | -0.4452 | 9.58989 |
April | 720.00000 | 21.49013 | 49.27140 | -0.2648 | 7.53546 |
May | 744.00000 | 22.08124 | 52.09229 | -1.1192 | 34.12576 |
June | 720.00000 | 22.57670 | 55.09295 | -0.8600 | 24.13577 |
July | 744.00000 | 22.25355 | 54.73169 | -0.9196 | 26.21157 |
August | 744.00000 | 22.22350 | 52.68306 | -0.9373 | 26.75130 |
September | 720.00000 | 22.34548 | 54.62276 | -0.9877 | 28.51717 |
October | 744.00000 | 21.80479 | 51.97562 | -0.1397 | 6.69942 |
November | 720.00000 | 20.99678 | 48.39322 | -0.4585 | 9.97238 |
December | 744.00000 | 20.69359 | 42.66108 | -0.6119 | 13.22908 |
Annual Sum or Average | 8760.00000 | 21.57747 | 49.07249 | -0.6698 | 17.96476 |
Minimum of Months | 672.00000 | 20.63688 | 37.91084 | -1.1192 | 6.69942 |
Maximum of Months | 744.00000 | 22.57670 | 55.09295 | -0.1397 | 34.12576 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.73730 | 43.41910 | -0.6341 | 14.11902 |
February | 672.00000 | 20.87256 | 38.22625 | -0.6134 | 13.74405 |
March | 744.00000 | 21.17137 | 46.75630 | -0.4119 | 9.55578 |
April | 720.00000 | 21.37568 | 50.71258 | -0.2802 | 7.89108 |
May | 744.00000 | 21.61772 | 54.11421 | -1.2428 | 38.86929 |
June | 720.00000 | 21.72131 | 55.47188 | -1.0930 | 32.00990 |
July | 744.00000 | 21.74330 | 54.67317 | -1.0523 | 30.27190 |
August | 744.00000 | 21.74444 | 52.77395 | -1.0459 | 30.18794 |
September | 720.00000 | 21.68272 | 55.41095 | -1.1558 | 34.92503 |
October | 744.00000 | 21.59679 | 51.95654 | -0.1572 | 6.84273 |
November | 720.00000 | 21.08045 | 49.33806 | -0.4460 | 10.01092 |
December | 744.00000 | 20.84425 | 43.17947 | -0.5889 | 12.91249 |
Annual Sum or Average | 8760.00000 | 21.35164 | 49.72985 | -0.7276 | 20.15199 |
Minimum of Months | 672.00000 | 20.73730 | 38.22625 | -1.2428 | 6.84273 |
Maximum of Months | 744.00000 | 21.74444 | 55.47188 | -0.1572 | 38.86929 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.55472 | 43.89903 | -0.6993 | 15.86547 |
February | 672.00000 | 20.61444 | 38.82528 | -0.7068 | 16.08534 |
March | 744.00000 | 20.96676 | 47.32678 | -0.4872 | 10.76323 |
April | 720.00000 | 21.43336 | 50.90559 | -0.2874 | 8.36135 |
May | 744.00000 | 22.16892 | 53.26704 | -1.0926 | 34.60749 |
June | 720.00000 | 22.76413 | 54.35277 | -0.7835 | 23.77075 |
July | 744.00000 | 22.20675 | 55.27282 | -0.9151 | 25.77369 |
August | 744.00000 | 22.12557 | 53.39464 | -0.9527 | 26.77208 |
September | 720.00000 | 22.36494 | 55.81614 | -0.9804 | 29.03229 |
October | 744.00000 | 21.79722 | 53.52065 | -0.1478 | 7.48916 |
November | 720.00000 | 20.85228 | 50.14985 | -0.5257 | 11.48329 |
December | 744.00000 | 20.59661 | 43.83634 | -0.6726 | 14.91970 |
Annual Sum or Average | 8760.00000 | 21.54126 | 50.10925 | -0.6879 | 18.77188 |
Minimum of Months | 672.00000 | 20.55472 | 38.82528 | -1.0926 | 7.48916 |
Maximum of Months | 744.00000 | 22.76413 | 55.81614 | -0.1478 | 34.60749 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.13257 | 42.69161 | -0.4707 | 10.75053 |
February | 672.00000 | 21.31102 | 38.06132 | -0.4260 | 10.16188 |
March | 744.00000 | 21.39524 | 45.85528 | -0.3201 | 8.29452 |
April | 720.00000 | 21.48351 | 49.26097 | -0.2501 | 7.43202 |
May | 744.00000 | 21.62816 | 53.16063 | -1.2756 | 40.27339 |
June | 720.00000 | 21.70837 | 56.47889 | -1.1552 | 34.58382 |
July | 744.00000 | 21.73942 | 55.13130 | -1.1098 | 32.59243 |
August | 744.00000 | 21.74104 | 52.85086 | -1.0950 | 32.19783 |
September | 720.00000 | 21.70111 | 54.08244 | -1.1584 | 35.09194 |
October | 744.00000 | 21.67371 | 50.05035 | -0.1106 | 6.64108 |
November | 720.00000 | 21.45019 | 47.33014 | -0.2987 | 7.92336 |
December | 744.00000 | 21.24383 | 42.43038 | -0.4181 | 9.88154 |
Annual Sum or Average | 8760.00000 | 21.51829 | 49.00705 | -0.6756 | 19.71243 |
Minimum of Months | 672.00000 | 21.13257 | 38.06132 | -1.2756 | 6.64108 |
Maximum of Months | 744.00000 | 21.74104 | 56.47889 | -0.1106 | 40.27339 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.28538 | 33.54721 | 0.13423 | 6.21445 |
February | 672.00000 | 23.28379 | 29.65129 | 0.10619 | 6.01828 |
March | 744.00000 | 23.54722 | 37.10575 | 0.25926 | 6.90914 |
April | 720.00000 | 23.71846 | 42.11127 | 0.36830 | 8.25335 |
May | 744.00000 | 23.87256 | 48.94319 | -0.3744 | 8.23575 |
June | 720.00000 | 23.95297 | 58.39111 | -0.2233 | 6.17283 |
July | 744.00000 | 23.98034 | 61.77594 | -0.1635 | 5.58056 |
August | 744.00000 | 23.96718 | 59.15342 | -0.1914 | 5.83958 |
September | 720.00000 | 23.90966 | 55.53718 | -0.2898 | 7.01982 |
October | 744.00000 | 23.78659 | 47.85963 | 0.44382 | 9.62072 |
November | 720.00000 | 23.53582 | 38.75975 | 0.26719 | 7.06533 |
December | 744.00000 | 23.39123 | 33.26035 | 0.16861 | 6.19706 |
Annual Sum or Average | 8760.00000 | 23.68822 | 45.60336 | 0.04169 | 6.93251 |
Minimum of Months | 672.00000 | 23.28379 | 29.65129 | -0.3744 | 5.58056 |
Maximum of Months | 744.00000 | 23.98034 | 61.77594 | 0.44382 | 9.62072 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.51398 | 32.45521 | 0.22911 | 6.72068 |
February | 672.00000 | 23.51480 | 28.64365 | 0.20115 | 6.41752 |
March | 744.00000 | 23.72650 | 36.00281 | 0.34129 | 7.77871 |
April | 720.00000 | 23.85194 | 41.09756 | 0.43764 | 9.29863 |
May | 744.00000 | 23.93894 | 48.10010 | -0.3020 | 7.11648 |
June | 720.00000 | 23.97987 | 57.79343 | -0.1730 | 5.73322 |
July | 744.00000 | 23.99093 | 61.27937 | -0.1219 | 5.32856 |
August | 744.00000 | 23.98410 | 58.64605 | -0.1483 | 5.52110 |
September | 720.00000 | 23.95526 | 54.84110 | -0.2313 | 6.31430 |
October | 744.00000 | 23.88143 | 46.97723 | 0.49938 | 10.62932 |
November | 720.00000 | 23.71547 | 37.66375 | 0.34915 | 7.94955 |
December | 744.00000 | 23.59696 | 32.16625 | 0.25774 | 6.79571 |
Annual Sum or Average | 8760.00000 | 23.80578 | 44.73516 | 0.11101 | 7.13745 |
Minimum of Months | 672.00000 | 23.51398 | 28.64365 | -0.3020 | 5.32856 |
Maximum of Months | 744.00000 | 23.99093 | 61.27937 | 0.49938 | 10.62932 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.67957 | 30.80684 | 0.88490 | 24.31727 |
February | 672.00000 | 23.66892 | 27.04432 | 0.86255 | 23.56020 |
March | 744.00000 | 23.75737 | 34.55779 | 0.98715 | 27.98234 |
April | 720.00000 | 23.81880 | 39.89084 | 1.08100 | 31.82249 |
May | 744.00000 | 23.88289 | 47.18600 | 0.63170 | 17.95771 |
June | 720.00000 | 23.94889 | 56.96128 | 0.77808 | 21.53450 |
July | 744.00000 | 23.96536 | 60.41307 | 0.84152 | 23.31997 |
August | 744.00000 | 23.97783 | 57.73661 | 0.83298 | 23.24515 |
September | 720.00000 | 23.92527 | 53.83714 | 0.71828 | 19.84136 |
October | 744.00000 | 23.85586 | 45.72374 | 1.15472 | 35.04528 |
November | 720.00000 | 23.76068 | 36.20300 | 0.99324 | 28.17953 |
December | 744.00000 | 23.71440 | 30.63305 | 0.90863 | 24.84695 |
Annual Sum or Average | 8760.00000 | 23.83060 | 43.51446 | 0.88975 | 25.14843 |
Minimum of Months | 672.00000 | 23.66892 | 27.04432 | 0.63170 | 17.95771 |
Maximum of Months | 744.00000 | 23.97783 | 60.41307 | 1.15472 | 35.04528 |
Report: OccupantComfortDataSummaryMonthly
For: STORAGE_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.00101 | 28.14891 | -0.5217 | 10.81643 |
February | 672.00000 | 21.00012 | 23.60316 | -0.5482 | 11.36439 |
March | 744.00000 | 21.05097 | 33.14505 | -0.4509 | 9.36584 |
April | 720.00000 | 21.39140 | 39.19307 | -0.3187 | 7.57889 |
May | 744.00000 | 22.10245 | 46.30860 | -1.1828 | 34.85974 |
June | 720.00000 | 23.04839 | 55.22860 | -0.7895 | 18.50459 |
July | 744.00000 | 23.46305 | 58.25914 | -0.6203 | 13.18342 |
August | 744.00000 | 23.50325 | 54.99896 | -0.6272 | 13.44156 |
September | 720.00000 | 22.88684 | 51.97045 | -0.8675 | 21.51449 |
October | 744.00000 | 22.18251 | 44.26335 | -0.0802 | 5.75288 |
November | 720.00000 | 21.22207 | 34.93063 | -0.3933 | 8.50697 |
December | 744.00000 | 21.00216 | 28.23188 | -0.5047 | 10.36682 |
Annual Sum or Average | 8760.00000 | 21.99433 | 41.62905 | -0.5755 | 13.78832 |
Minimum of Months | 672.00000 | 21.00012 | 23.60316 | -1.1828 | 5.75288 |
Maximum of Months | 744.00000 | 23.50325 | 58.25914 | -0.0802 | 34.85974 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.00477 | 31.40631 | -0.4995 | 10.30908 |
February | 672.00000 | 21.00797 | 26.86740 | -0.5185 | 10.67672 |
March | 744.00000 | 21.11588 | 36.27647 | -0.4218 | 8.82155 |
April | 720.00000 | 21.50785 | 42.18320 | -0.2851 | 7.10451 |
May | 744.00000 | 22.16212 | 49.40016 | -1.1669 | 34.11586 |
June | 720.00000 | 23.05746 | 58.24721 | -0.7901 | 18.36227 |
July | 744.00000 | 23.32204 | 61.45137 | -0.6730 | 14.58019 |
August | 744.00000 | 23.45384 | 58.16499 | -0.6475 | 13.89801 |
September | 720.00000 | 22.90610 | 55.08395 | -0.8641 | 21.49873 |
October | 744.00000 | 22.34414 | 47.14054 | -0.0381 | 5.50137 |
November | 720.00000 | 21.22206 | 38.13351 | -0.3872 | 8.37302 |
December | 744.00000 | 21.01148 | 31.44574 | -0.4897 | 10.04965 |
Annual Sum or Average | 8760.00000 | 22.01608 | 44.75500 | -0.5653 | 13.62918 |
Minimum of Months | 672.00000 | 21.00477 | 26.86740 | -1.1669 | 5.50137 |
Maximum of Months | 744.00000 | 23.45384 | 61.45137 | -0.0381 | 34.11586 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.00818 | 29.21094 | -0.5026 | 10.40933 |
February | 672.00000 | 21.02334 | 24.68273 | -0.5202 | 10.75038 |
March | 744.00000 | 21.15357 | 34.01111 | -0.4010 | 8.54765 |
April | 720.00000 | 21.56963 | 39.78985 | -0.2480 | 6.94731 |
May | 744.00000 | 22.30458 | 46.78436 | -1.0683 | 29.93943 |
June | 720.00000 | 23.26174 | 55.23538 | -0.6619 | 14.71999 |
July | 744.00000 | 23.64404 | 57.95699 | -0.4987 | 10.40652 |
August | 744.00000 | 23.66422 | 55.02440 | -0.5090 | 10.73285 |
September | 720.00000 | 22.95947 | 52.55567 | -0.7903 | 19.27733 |
October | 744.00000 | 22.18343 | 45.11505 | -0.0482 | 5.97084 |
November | 720.00000 | 21.16815 | 36.01329 | -0.3875 | 8.39392 |
December | 744.00000 | 21.01792 | 29.24566 | -0.4863 | 9.99030 |
Annual Sum or Average | 8760.00000 | 22.08679 | 42.23766 | -0.5100 | 12.18376 |
Minimum of Months | 672.00000 | 21.00818 | 24.68273 | -1.0683 | 5.97084 |
Maximum of Months | 744.00000 | 23.66422 | 57.95699 | -0.0482 | 29.93943 |
Report: OccupantComfortDataSummaryMonthly
For: MECH_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.02651 | 27.74969 | -0.5041 | 10.44822 |
February | 672.00000 | 21.02235 | 23.22021 | -0.5320 | 11.00155 |
March | 744.00000 | 21.16894 | 32.56521 | -0.4200 | 8.85620 |
April | 720.00000 | 21.60483 | 38.37391 | -0.2709 | 7.05249 |
May | 744.00000 | 22.36432 | 45.26152 | -1.1029 | 31.16741 |
June | 720.00000 | 23.28203 | 54.14360 | -0.7174 | 16.22788 |
July | 744.00000 | 23.64511 | 57.29456 | -0.5633 | 11.77590 |
August | 744.00000 | 23.68617 | 54.03820 | -0.5695 | 11.96950 |
September | 720.00000 | 23.14853 | 50.84522 | -0.7864 | 18.68121 |
October | 744.00000 | 22.47512 | 43.21415 | -0.0171 | 5.58649 |
November | 720.00000 | 21.41165 | 34.18801 | -0.3476 | 7.91091 |
December | 744.00000 | 21.04596 | 27.82091 | -0.4855 | 9.97722 |
Annual Sum or Average | 8760.00000 | 22.16387 | 40.83003 | -0.5263 | 12.56829 |
Minimum of Months | 672.00000 | 21.02235 | 23.22021 | -1.1029 | 5.58649 |
Maximum of Months | 744.00000 | 23.68617 | 57.29456 | -0.0171 | 31.16741 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.835430E+09 | 9766.54 | 24-JAN-19:02 | 197.32 | 0.394023E+10 | 0.00 | 0.477566E+10 | 1.25 | 4.72 | 03-JAN-21:50 | 0.00 | 0.00 |
February | 0.155408E+10 | 13550.17 | 20-FEB-09:03 | 241.83 | 0.732966E+10 | 0.00 | 0.888373E+10 | 1.70 | 4.72 | 01-FEB-09:02 | 0.00 | 0.00 |
March | 0.556485E+10 | 56772.73 | 27-MAR-15:01 | 479.99 | 0.258627E+11 | 0.00 | 0.314275E+11 | 3.04 | 4.72 | 01-MAR-03:40 | 0.00 | 0.00 |
April | 0.192000E+11 | 93877.67 | 07-APR-15:03 | 604.47 | 0.853801E+11 | 0.00 | 0.104580E+12 | 3.90 | 4.72 | 01-APR-02:40 | 0.00 | 0.00 |
May | 0.521173E+11 | 105891.35 | 31-MAY-15:03 | 737.08 | 0.226528E+12 | 0.00 | 0.278645E+12 | 4.48 | 4.72 | 01-MAY-00:50 | 0.00 | 0.00 |
June | 0.169557E+12 | 183344.09 | 19-JUN-18:03 | 720.00 | 0.705966E+12 | 0.00 | 0.875523E+12 | 4.24 | 4.70 | 03-JUN-03:05 | 0.00 | 0.00 |
July | 0.268527E+12 | 190244.94 | 20-JUL-18:03 | 744.00 | 0.107660E+13 | 0.00 | 0.134513E+13 | 4.03 | 4.50 | 01-JUL-21:55 | 0.00 | 0.00 |
August | 0.230623E+12 | 203719.72 | 11-AUG-21:51 | 744.00 | 0.908601E+12 | 0.00 | 0.113922E+13 | 4.02 | 4.62 | 08-AUG-05:00 | 0.00 | 0.00 |
September | 0.123427E+12 | 168931.68 | 07-SEP-20:00 | 720.00 | 0.519718E+12 | 0.00 | 0.643145E+12 | 4.33 | 4.72 | 11-SEP-05:10 | 0.00 | 0.00 |
October | 0.523892E+11 | 115827.11 | 03-OCT-15:03 | 722.76 | 0.232387E+12 | 0.00 | 0.284776E+12 | 4.45 | 4.72 | 01-OCT-01:00 | 0.00 | 0.00 |
November | 0.617568E+10 | 41957.60 | 04-NOV-15:03 | 471.63 | 0.288205E+11 | 0.00 | 0.349962E+11 | 3.08 | 4.72 | 01-NOV-00:20 | 0.00 | 0.00 |
December | 0.205812E+10 | 13251.59 | 20-DEC-09:02 | 310.62 | 0.970694E+10 | 0.00 | 0.117651E+11 | 1.97 | 4.72 | 01-DEC-01:20 | 0.00 | 0.00 |
Annual Sum or Average | 0.932030E+12 | 6693.70 | 0.383084E+13 | 0.00 | 0.476287E+13 | 3.38 | 0.00 | 0.00 | ||||
Minimum of Months | 0.835430E+09 | 9766.54 | 197.32 | 0.394023E+10 | 0.00 | 0.477566E+10 | 1.25 | 4.50 | 0.00 | 0.00 | ||
Maximum of Months | 0.268527E+12 | 203719.72 | 744.00 | 0.107660E+13 | 0.00 | 0.134513E+13 | 4.48 | 4.72 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.130064E+12 | 0.00 | 744.00 | 180921.21 | 02-JAN-09:04 | 0.00 | 38.22 | 60.00 | 0.50 | 0.00 | 0.10 | 0.39 | 02-JAN-09:04 |
February | 0.107890E+12 | 0.00 | 672.00 | 185828.75 | 06-FEB-09:02 | 0.00 | 39.78 | 60.00 | 0.47 | 0.00 | 0.10 | 0.40 | 06-FEB-09:02 |
March | 0.706048E+11 | 0.00 | 729.05 | 156626.58 | 11-MAR-19:03 | 0.00 | 38.94 | 59.36 | 0.27 | 0.00 | 0.06 | 0.34 | 11-MAR-19:03 |
April | 0.750359E+11 | 0.00 | 572.74 | 147593.66 | 02-APR-18:04 | 0.00 | 33.31 | 53.63 | 0.25 | 0.00 | 0.06 | 0.32 | 02-APR-18:04 |
May | 0.299086E+11 | 0.00 | 327.50 | 102921.98 | 01-MAY-06:20 | 0.00 | 28.70 | 42.83 | 0.09 | 0.00 | 0.02 | 0.22 | 01-MAY-06:20 |
June | 0.571983E+09 | 0.00 | 21.60 | 33861.52 | 06-JUN-15:06 | 0.00 | 33.49 | 34.42 | 0.00 | 0.00 | 0.00 | 0.07 | 06-JUN-15:06 |
July | 74281158.72 | 0.00 | 3.79 | 23908.15 | 14-JUL-08:07 | 0.00 | 39.20 | 39.31 | 0.00 | 0.00 | 0.00 | 0.05 | 14-JUL-08:07 |
August | 0.366123E+09 | 0.00 | 15.76 | 39732.26 | 24-AUG-19:00 | 0.00 | 33.65 | 34.25 | 0.00 | 0.00 | 0.00 | 0.09 | 24-AUG-19:00 |
September | 0.700926E+10 | 0.00 | 115.02 | 73826.71 | 24-SEP-06:00 | 0.00 | 31.07 | 36.04 | 0.02 | 0.00 | 0.01 | 0.16 | 24-SEP-06:00 |
October | 0.458077E+11 | 0.00 | 398.37 | 133080.09 | 27-OCT-18:04 | 0.00 | 31.05 | 46.34 | 0.14 | 0.00 | 0.04 | 0.29 | 27-OCT-18:04 |
November | 0.972909E+11 | 0.00 | 692.76 | 162487.64 | 16-NOV-16:02 | 0.00 | 35.97 | 58.80 | 0.36 | 0.00 | 0.08 | 0.35 | 16-NOV-16:02 |
December | 0.805723E+11 | 0.00 | 744.00 | 169568.87 | 04-DEC-16:02 | 0.00 | 40.27 | 60.00 | 0.34 | 0.00 | 0.06 | 0.37 | 04-DEC-16:02 |
Annual Sum or Average | 0.645195E+12 | 0.00 | 5036.58 | 0.00 | 35.29 | 48.69 | 0.20 | 0.00 | 0.04 | ||||
Minimum of Months | 74281158.72 | 0.00 | 3.79 | 23908.15 | 0.00 | 28.70 | 34.25 | 0.00 | 0.00 | 0.00 | 0.05 | ||
Maximum of Months | 0.130064E+12 | 0.00 | 744.00 | 185828.75 | 0.00 | 40.27 | 60.00 | 0.50 | 0.00 | 0.10 | 0.40 |
Report: DXReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 |
March | 0.272158E+09 | 0.00 | 15.00 | 0.236657E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19261.28 | 27-MAR-13:00 | 14888.95 | 27-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.216554E+10 | 0.00 | 99.83 | 0.212879E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20061.39 | 09-APR-10:00 | 17822.47 | 07-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.900257E+10 | 0.00 | 325.33 | 0.752894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31002.32 | 31-MAY-16:57 | 19442.15 | 30-MAY-13:00 | 0.00 | 0.00 | 0.00 |
June | 0.426109E+11 | 0.00 | 557.83 | 0.239468E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 46827.19 | 24-JUN-18:03 | 22015.28 | 19-JUN-12:20 | 0.00 | 0.00 | 0.00 |
July | 0.580827E+11 | 0.00 | 589.00 | 0.325850E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 47936.35 | 28-JUL-08:03 | 20981.36 | 07-JUL-12:20 | 0.00 | 0.00 | 0.00 |
August | 0.468423E+11 | 0.00 | 589.00 | 0.307391E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 42828.29 | 10-AUG-21:51 | 20975.18 | 24-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.289963E+11 | 0.00 | 496.50 | 0.191326E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 46314.94 | 14-SEP-08:03 | 19563.39 | 01-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.100098E+11 | 0.00 | 251.50 | 0.575803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30540.46 | 03-OCT-15:02 | 17220.62 | 04-OCT-12:15 | 0.00 | 0.00 | 0.00 |
November | 0.209514E+09 | 0.00 | 19.17 | 0.180116E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7316.39 | 10-NOV-08:00 | 6401.30 | 04-NOV-13:00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.198192E+12 | 0.00 | 2943.17 | 0.122236E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.580827E+11 | 0.00 | 589.00 | 0.325850E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 47936.35 | 22015.28 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 54740927.79 | 0.00 | 58.93 | 54740927.79 | 0.00 | 0.00 | 0.00 | 0.00 | 10741.93 | 03-JAN-19:10 | 10741.93 | 03-JAN-19:10 | 0.00 | 0.00 | 0.00 |
February | 66694393.81 | 0.00 | 53.64 | 66694393.81 | 0.00 | 0.00 | 0.00 | 0.00 | 9371.68 | 10-FEB-19:40 | 9371.68 | 10-FEB-19:40 | 0.00 | 0.00 | 0.00 |
March | 0.342005E+10 | 0.00 | 151.25 | 0.338865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 130872.94 | 27-MAR-16:00 | 130872.94 | 27-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.344920E+11 | 0.00 | 218.64 | 0.342317E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 214043.04 | 09-APR-10:50 | 208279.28 | 07-APR-17:01 | 0.00 | 0.00 | 0.00 |
May | 0.127231E+12 | 0.00 | 473.25 | 0.109458E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 299525.23 | 31-MAY-17:17 | 215687.16 | 29-MAY-12:25 | 0.00 | 0.00 | 0.00 |
June | 0.525177E+12 | 0.00 | 707.50 | 0.306567E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 503070.75 | 15-JUN-21:50 | 291504.97 | 22-JUN-18:30 | 0.00 | 0.00 | 0.00 |
July | 0.834222E+12 | 0.00 | 744.00 | 0.440636E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 557291.53 | 27-JUL-21:00 | 259754.77 | 11-JUL-18:08 | 0.00 | 0.00 | 0.00 |
August | 0.672424E+12 | 0.00 | 744.00 | 0.433192E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 587335.46 | 11-AUG-21:53 | 344171.59 | 24-AUG-18:20 | 0.00 | 0.00 | 0.00 |
September | 0.365735E+12 | 0.00 | 642.00 | 0.247697E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 547160.73 | 13-SEP-21:00 | 282156.11 | 01-SEP-19:20 | 0.00 | 0.00 | 0.00 |
October | 0.125858E+12 | 0.00 | 367.81 | 0.805302E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 288660.78 | 05-OCT-19:10 | 180186.64 | 25-OCT-10:33 | 0.00 | 0.00 | 0.00 |
November | 0.344095E+10 | 0.00 | 122.36 | 0.314063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65659.86 | 04-NOV-10:45 | 65659.86 | 04-NOV-10:45 | 0.00 | 0.00 | 0.00 |
December | 0.139726E+09 | 0.00 | 119.75 | 0.139726E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12967.07 | 29-DEC-19:20 | 12967.07 | 29-DEC-19:20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.269226E+13 | 0.00 | 4403.12 | 0.165910E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 54740927.79 | 0.00 | 53.64 | 54740927.79 | 0.00 | 0.00 | 0.00 | 0.00 | 9371.68 | 9371.68 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.834222E+12 | 0.00 | 744.00 | 0.440636E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 587335.46 | 344171.59 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 57954972.74 | 0.00 | 14.13 | 36758038.35 | 0.00 | 0.00 | 0.00 | 0.00 | 15686.18 | 20-JAN-16:01 | 15686.18 | 20-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.146236E+09 | 0.00 | 31.61 | 0.117006E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15683.77 | 17-FEB-16:01 | 15683.77 | 17-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.929969E+09 | 0.00 | 156.13 | 0.620808E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15848.06 | 27-MAR-15:01 | 15687.06 | 11-MAR-16:01 | 0.00 | 0.00 | 0.00 |
April | 0.233365E+10 | 0.00 | 326.27 | 0.139099E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15685.13 | 03-APR-15:01 | 15685.13 | 03-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.489671E+10 | 0.00 | 589.82 | 0.268489E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17065.34 | 19-MAY-15:01 | 15686.92 | 20-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.899425E+10 | 0.00 | 673.44 | 0.480938E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18282.10 | 27-JUN-08:62 | 14338.56 | 23-JUN-08:61 | 0.00 | 0.00 | 0.00 |
July | 0.109317E+11 | 0.00 | 713.43 | 0.619949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18307.59 | 28-JUL-08:61 | 14409.88 | 07-JUL-08:62 | 0.00 | 0.00 | 0.00 |
August | 0.115162E+11 | 0.00 | 715.63 | 0.714515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17932.15 | 06-AUG-08:61 | 14474.87 | 13-AUG-08:62 | 0.00 | 0.00 | 0.00 |
September | 0.713952E+10 | 0.00 | 648.69 | 0.382157E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19796.25 | 22-SEP-18:01 | 15682.75 | 28-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.475360E+10 | 0.00 | 560.93 | 0.249527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17221.67 | 24-OCT-08:62 | 15685.93 | 28-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.440737E+09 | 0.00 | 117.60 | 0.194355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15216.48 | 10-NOV-16:02 | 15118.17 | 02-NOV-18:01 | 0.00 | 0.00 | 0.00 |
December | 73535069.74 | 0.00 | 23.22 | 54459110.45 | 0.00 | 0.00 | 0.00 | 0.00 | 15655.43 | 02-DEC-16:01 | 15655.43 | 02-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.522141E+11 | 0.00 | 4570.90 | 0.295701E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 57954972.74 | 0.00 | 14.13 | 36758038.35 | 0.00 | 0.00 | 0.00 | 0.00 | 15216.48 | 14338.56 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.115162E+11 | 0.00 | 715.63 | 0.714515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19796.25 | 15687.06 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 8434436.35 | 0.00 | 2.12 | 5407460.49 | 0.00 | 0.00 | 0.00 | 0.00 | 12420.22 | 20-JAN-16:01 | 12420.22 | 20-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 28293066.84 | 0.00 | 8.13 | 22750529.96 | 0.00 | 0.00 | 0.00 | 0.00 | 14405.25 | 22-FEB-16:01 | 14405.25 | 22-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.385880E+09 | 0.00 | 73.48 | 0.255228E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15916.78 | 27-MAR-15:01 | 15250.03 | 11-MAR-16:01 | 0.00 | 0.00 | 0.00 |
April | 0.136765E+10 | 0.00 | 239.16 | 0.742944E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16307.64 | 27-APR-18:21 | 15895.08 | 09-APR-18:11 | 0.00 | 0.00 | 0.00 |
May | 0.336155E+10 | 0.00 | 445.66 | 0.170226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17510.77 | 31-MAY-21:51 | 16344.88 | 02-MAY-18:21 | 0.00 | 0.00 | 0.00 |
June | 0.643826E+10 | 0.00 | 459.17 | 0.362059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19475.28 | 25-JUN-07:51 | 15298.90 | 22-JUN-07:51 | 0.00 | 0.00 | 0.00 |
July | 0.940583E+10 | 0.00 | 590.04 | 0.552739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19776.16 | 23-JUL-08:21 | 15082.91 | 03-JUL-18:51 | 0.00 | 0.00 | 0.00 |
August | 0.943812E+10 | 0.00 | 593.83 | 0.582026E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19636.73 | 12-AUG-08:61 | 14490.40 | 23-AUG-08:51 | 0.00 | 0.00 | 0.00 |
September | 0.420569E+10 | 0.00 | 431.55 | 0.207338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18572.47 | 14-SEP-08:51 | 14516.06 | 03-SEP-08:51 | 0.00 | 0.00 | 0.00 |
October | 0.195775E+10 | 0.00 | 342.92 | 0.841869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17119.29 | 05-OCT-21:51 | 15248.83 | 28-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 87800472.23 | 0.00 | 38.03 | 43153090.80 | 0.00 | 0.00 | 0.00 | 0.00 | 15101.83 | 10-NOV-16:02 | 13939.73 | 04-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 5774268.90 | 0.00 | 1.30 | 4164321.67 | 0.00 | 0.00 | 0.00 | 0.00 | 9631.44 | 17-DEC-16:01 | 9631.44 | 17-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.366910E+11 | 0.00 | 3225.40 | 0.206594E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 5774268.90 | 0.00 | 1.30 | 4164321.67 | 0.00 | 0.00 | 0.00 | 0.00 | 9631.44 | 9631.44 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.943812E+10 | 0.00 | 593.83 | 0.582026E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19776.16 | 16344.88 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 29087784.87 | 0.00 | 1.83 | 29087784.87 | 0.00 | 0.00 | 0.00 | 0.00 | 5688.17 | 31-JAN-14:50 | 5688.17 | 31-JAN-14:50 | 0.00 | 0.00 | 0.00 |
February | 0.247367E+10 | 0.00 | 80.80 | 0.247367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27352.19 | 20-FEB-13:30 | 27352.19 | 20-FEB-13:30 | 0.00 | 0.00 | 0.00 |
March | 0.721664E+10 | 0.00 | 187.75 | 0.546446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32341.52 | 28-MAR-12:30 | 32226.40 | 15-MAR-13:05 | 0.00 | 0.00 | 0.00 |
April | 0.144535E+11 | 0.00 | 351.91 | 0.773157E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43697.87 | 07-APR-12:30 | 36132.55 | 07-APR-12:30 | 0.00 | 0.00 | 0.00 |
May | 0.247764E+11 | 0.00 | 599.74 | 0.937552E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32887.21 | 30-MAY-12:30 | 20921.98 | 30-MAY-12:50 | 0.00 | 0.00 | 0.00 |
June | 0.394729E+11 | 0.00 | 712.02 | 0.153252E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 35165.22 | 19-JUN-12:40 | 22799.43 | 19-JUN-13:20 | 0.00 | 0.00 | 0.00 |
July | 0.524059E+11 | 0.00 | 743.17 | 0.227802E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 36698.82 | 08-JUL-12:00 | 25245.74 | 10-JUL-13:10 | 0.00 | 0.00 | 0.00 |
August | 0.607843E+11 | 0.00 | 743.17 | 0.319404E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 45576.13 | 16-AUG-12:30 | 39982.72 | 30-AUG-12:50 | 0.00 | 0.00 | 0.00 |
September | 0.460589E+11 | 0.00 | 694.73 | 0.237979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 50462.89 | 28-SEP-12:30 | 48331.19 | 28-SEP-12:30 | 0.00 | 0.00 | 0.00 |
October | 0.449436E+11 | 0.00 | 666.30 | 0.305079E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 53103.73 | 04-OCT-11:10 | 49658.64 | 05-OCT-12:00 | 0.00 | 0.00 | 0.00 |
November | 0.105908E+11 | 0.00 | 237.29 | 0.733234E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44184.72 | 02-NOV-12:40 | 44184.72 | 02-NOV-12:40 | 0.00 | 0.00 | 0.00 |
December | 0.371234E+10 | 0.00 | 91.21 | 0.371234E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31204.56 | 17-DEC-13:30 | 31204.56 | 17-DEC-13:30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.306918E+12 | 0.00 | 5109.91 | 0.160470E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 29087784.87 | 0.00 | 1.83 | 29087784.87 | 0.00 | 0.00 | 0.00 | 0.00 | 5688.17 | 5688.17 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.607843E+11 | 0.00 | 743.17 | 0.319404E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 53103.73 | 49658.64 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.578204E+09 | 0.00 | 47.29 | 0.221455E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 79916.40 | 24-JAN-19:02 | 71902.62 | 22-JAN-09:02 | 0.00 | 0.00 | 0.00 |
February | 0.320595E+09 | 0.00 | 34.97 | 0.202940E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 61825.33 | 25-FEB-09:01 | 61825.33 | 25-FEB-09:01 | 0.00 | 0.00 | 0.00 |
March | 0.440538E+10 | 0.00 | 212.97 | 0.229528E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84826.39 | 27-MAR-15:01 | 84327.69 | 03-MAR-19:02 | 0.00 | 0.00 | 0.00 |
April | 0.154771E+11 | 0.00 | 380.24 | 0.836482E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 89103.62 | 10-APR-20:41 | 89103.62 | 10-APR-20:41 | 0.00 | 0.00 | 0.00 |
May | 0.324265E+11 | 0.00 | 443.36 | 0.192774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 98692.54 | 31-MAY-21:51 | 91473.64 | 27-MAY-21:51 | 0.00 | 0.00 | 0.00 |
June | 0.462180E+11 | 0.00 | 413.87 | 0.286362E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 113186.91 | 25-JUN-07:51 | 90921.27 | 02-JUN-21:41 | 0.00 | 0.00 | 0.00 |
July | 0.641569E+11 | 0.00 | 543.20 | 0.397457E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 115668.94 | 23-JUL-08:21 | 82871.38 | 03-JUL-18:51 | 0.00 | 0.00 | 0.00 |
August | 0.580814E+11 | 0.00 | 536.28 | 0.356936E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 113438.74 | 12-AUG-08:61 | 82755.86 | 17-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.341977E+11 | 0.00 | 383.21 | 0.196604E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 108054.09 | 14-SEP-08:51 | 90348.09 | 10-SEP-21:51 | 0.00 | 0.00 | 0.00 |
October | 0.191905E+11 | 0.00 | 387.66 | 0.104346E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 99049.42 | 05-OCT-21:51 | 89028.72 | 06-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.557406E+10 | 0.00 | 246.64 | 0.248006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 92027.98 | 10-NOV-09:13 | 83981.50 | 02-NOV-18:01 | 0.00 | 0.00 | 0.00 |
December | 0.560618E+09 | 0.00 | 53.30 | 0.364729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 75753.03 | 25-DEC-09:02 | 75753.03 | 25-DEC-09:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.281187E+12 | 0.00 | 3682.99 | 0.167377E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.320595E+09 | 0.00 | 34.97 | 0.202940E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 61825.33 | 61825.33 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.641569E+11 | 0.00 | 543.20 | 0.397457E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 115668.94 | 91473.64 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 95887284.39 | 0.00 | 19.07 | 59902839.12 | 0.00 | 0.00 | 0.00 | 0.00 | 11729.17 | 19-JAN-09:02 | 11729.17 | 19-JAN-09:02 | 0.00 | 0.00 | 0.00 |
February | 0.163637E+09 | 0.00 | 33.64 | 0.121909E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14445.96 | 25-FEB-09:01 | 14445.96 | 25-FEB-09:01 | 0.00 | 0.00 | 0.00 |
March | 0.797952E+09 | 0.00 | 158.49 | 0.506017E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14983.09 | 27-MAR-15:01 | 14450.03 | 11-MAR-16:01 | 0.00 | 0.00 | 0.00 |
April | 0.236917E+10 | 0.00 | 350.86 | 0.135223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14448.42 | 03-APR-15:01 | 14448.42 | 03-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.507178E+10 | 0.00 | 605.61 | 0.282903E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15617.81 | 19-MAY-15:01 | 14448.39 | 20-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.850089E+10 | 0.00 | 682.24 | 0.449807E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16924.46 | 18-JUN-08:61 | 13281.83 | 16-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.108164E+11 | 0.00 | 722.23 | 0.616650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16548.71 | 23-JUL-18:02 | 13371.83 | 27-JUL-08:61 | 0.00 | 0.00 | 0.00 |
August | 0.114265E+11 | 0.00 | 727.23 | 0.707128E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16486.47 | 06-AUG-08:61 | 13339.33 | 24-AUG-08:61 | 0.00 | 0.00 | 0.00 |
September | 0.720904E+10 | 0.00 | 660.65 | 0.390533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18301.64 | 22-SEP-18:01 | 14444.50 | 28-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.456827E+10 | 0.00 | 573.29 | 0.235030E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15894.83 | 05-OCT-18:02 | 14449.18 | 28-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.638564E+09 | 0.00 | 146.19 | 0.311318E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13909.91 | 11-NOV-09:01 | 13884.85 | 02-NOV-18:01 | 0.00 | 0.00 | 0.00 |
December | 0.181777E+09 | 0.00 | 36.22 | 0.109510E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13764.06 | 02-DEC-09:02 | 13764.06 | 02-DEC-09:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.518398E+11 | 0.00 | 4715.72 | 0.292814E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 95887284.39 | 0.00 | 19.07 | 59902839.12 | 0.00 | 0.00 | 0.00 | 0.00 | 11729.17 | 11729.17 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.114265E+11 | 0.00 | 727.23 | 0.707128E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18301.64 | 14450.03 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 8416216.06 | 0.00 | 4.89 | 2831399.10 | 0.00 | 0.00 | 0.00 | 0.00 | 7033.40 | 19-JAN-09:02 | 5349.43 | 19-JAN-09:02 | 0.00 | 0.00 | 0.00 |
February | 28520597.56 | 0.00 | 9.44 | 17252685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 13434.40 | 25-FEB-09:01 | 13434.40 | 25-FEB-09:01 | 0.00 | 0.00 | 0.00 |
March | 0.307861E+09 | 0.00 | 66.65 | 0.183478E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14176.06 | 27-MAR-15:01 | 13172.39 | 23-MAR-08:62 | 0.00 | 0.00 | 0.00 |
April | 0.147472E+10 | 0.00 | 265.22 | 0.791850E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14462.04 | 08-APR-08:51 | 14462.04 | 08-APR-08:51 | 0.00 | 0.00 | 0.00 |
May | 0.365228E+10 | 0.00 | 467.77 | 0.198081E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17847.51 | 31-MAY-08:32 | 16064.00 | 30-MAY-08:61 | 0.00 | 0.00 | 0.00 |
June | 0.613585E+10 | 0.00 | 469.87 | 0.335798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18499.94 | 20-JUN-08:62 | 15464.85 | 26-JUN-08:32 | 0.00 | 0.00 | 0.00 |
July | 0.921840E+10 | 0.00 | 598.32 | 0.534752E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18619.74 | 01-JUL-08:32 | 14809.77 | 17-JUL-07:32 | 0.00 | 0.00 | 0.00 |
August | 0.924265E+10 | 0.00 | 606.20 | 0.559061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18171.09 | 12-AUG-08:61 | 15017.43 | 10-AUG-08:32 | 0.00 | 0.00 | 0.00 |
September | 0.436277E+10 | 0.00 | 450.07 | 0.224071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18151.88 | 06-SEP-08:32 | 15013.20 | 04-SEP-08:32 | 0.00 | 0.00 | 0.00 |
October | 0.193117E+10 | 0.00 | 348.55 | 0.896180E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16494.35 | 04-OCT-08:51 | 14043.11 | 26-OCT-08:61 | 0.00 | 0.00 | 0.00 |
November | 0.186315E+09 | 0.00 | 54.87 | 80197936.58 | 0.00 | 0.00 | 0.00 | 0.00 | 13401.32 | 04-NOV-08:61 | 12708.10 | 08-NOV-09:02 | 0.00 | 0.00 | 0.00 |
December | 20071195.37 | 0.00 | 7.62 | 8792452.65 | 0.00 | 0.00 | 0.00 | 0.00 | 10294.54 | 17-DEC-09:02 | 10294.54 | 17-DEC-09:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.365690E+11 | 0.00 | 3349.47 | 0.204982E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 8416216.06 | 0.00 | 4.89 | 2831399.10 | 0.00 | 0.00 | 0.00 | 0.00 | 7033.40 | 5349.43 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.924265E+10 | 0.00 | 606.20 | 0.559061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18619.74 | 16064.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 13965455.42 | 0.00 | 10.79 | 8709236.01 | 0.00 | 0.00 | 0.00 | 0.00 | 4113.51 | 20-JAN-16:01 | 4113.51 | 20-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 36499203.31 | 0.00 | 27.06 | 28764599.26 | 0.00 | 0.00 | 0.00 | 0.00 | 4112.90 | 17-FEB-16:01 | 4112.90 | 17-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.235338E+09 | 0.00 | 126.75 | 0.160084E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4113.64 | 11-MAR-16:01 | 4113.64 | 11-MAR-16:01 | 0.00 | 0.00 | 0.00 |
April | 0.589561E+09 | 0.00 | 290.57 | 0.363269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4260.15 | 09-APR-08:61 | 4113.24 | 03-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.123823E+10 | 0.00 | 551.92 | 0.722596E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4508.12 | 19-MAY-15:01 | 4113.49 | 01-MAY-15:01 | 0.00 | 0.00 | 0.00 |
June | 0.230617E+10 | 0.00 | 671.61 | 0.125313E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4989.75 | 18-JUN-08:61 | 3706.66 | 23-JUN-08:61 | 0.00 | 0.00 | 0.00 |
July | 0.284720E+10 | 0.00 | 713.87 | 0.162900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4994.32 | 28-JUL-08:61 | 3752.68 | 31-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.296218E+10 | 0.00 | 715.28 | 0.183940E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4970.52 | 06-AUG-08:61 | 3787.68 | 26-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.175281E+10 | 0.00 | 625.99 | 0.952435E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5376.05 | 22-SEP-18:01 | 4111.94 | 28-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.109275E+10 | 0.00 | 491.66 | 0.587003E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4648.00 | 24-OCT-08:62 | 4113.63 | 06-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 84778257.78 | 0.00 | 82.61 | 39836643.41 | 0.00 | 0.00 | 0.00 | 0.00 | 4026.01 | 10-NOV-16:02 | 3912.26 | 02-NOV-18:01 | 0.00 | 0.00 | 0.00 |
December | 14905279.42 | 0.00 | 15.72 | 11716134.54 | 0.00 | 0.00 | 0.00 | 0.00 | 4112.86 | 02-DEC-16:01 | 4112.86 | 02-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.131744E+11 | 0.00 | 4323.84 | 0.759595E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 13965455.42 | 0.00 | 10.79 | 8709236.01 | 0.00 | 0.00 | 0.00 | 0.00 | 4026.01 | 3706.66 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.296218E+10 | 0.00 | 715.28 | 0.183940E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5376.05 | 4113.64 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 1454395.01 | 0.00 | 1.78 | 770636.45 | 0.00 | 0.00 | 0.00 | 0.00 | 2742.36 | 17-JAN-16:01 | 2742.36 | 17-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 4546371.53 | 0.00 | 6.19 | 3525048.60 | 0.00 | 0.00 | 0.00 | 0.00 | 2857.83 | 22-FEB-16:01 | 2857.83 | 22-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 90625579.44 | 0.00 | 63.43 | 59907370.66 | 0.00 | 0.00 | 0.00 | 0.00 | 4218.30 | 27-MAR-15:01 | 3990.78 | 11-MAR-16:01 | 0.00 | 0.00 | 0.00 |
April | 0.342900E+09 | 0.00 | 210.79 | 0.193540E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4289.39 | 27-APR-18:21 | 4184.15 | 10-APR-20:41 | 0.00 | 0.00 | 0.00 |
May | 0.874306E+09 | 0.00 | 423.67 | 0.471388E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4732.94 | 31-MAY-21:51 | 4391.62 | 02-MAY-18:21 | 0.00 | 0.00 | 0.00 |
June | 0.172993E+10 | 0.00 | 460.96 | 0.100250E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5287.43 | 25-JUN-07:51 | 4011.28 | 04-JUN-21:51 | 0.00 | 0.00 | 0.00 |
July | 0.249861E+10 | 0.00 | 592.06 | 0.149177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5373.79 | 23-JUL-08:21 | 3933.53 | 03-JUL-18:51 | 0.00 | 0.00 | 0.00 |
August | 0.246806E+10 | 0.00 | 595.14 | 0.154081E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5309.89 | 12-AUG-08:61 | 3793.97 | 28-AUG-21:51 | 0.00 | 0.00 | 0.00 |
September | 0.104724E+10 | 0.00 | 413.79 | 0.526135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5025.35 | 14-SEP-08:51 | 3774.41 | 03-SEP-08:51 | 0.00 | 0.00 | 0.00 |
October | 0.412142E+09 | 0.00 | 284.40 | 0.176167E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4594.72 | 05-OCT-21:51 | 3989.03 | 26-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 13334503.33 | 0.00 | 17.45 | 6738689.52 | 0.00 | 0.00 | 0.00 | 0.00 | 3698.62 | 04-NOV-15:01 | 3551.00 | 04-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 682761.12 | 0.00 | 0.89 | 353178.82 | 0.00 | 0.00 | 0.00 | 0.00 | 2325.71 | 17-DEC-16:01 | 2192.05 | 17-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.948384E+10 | 0.00 | 3070.55 | 0.547361E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 682761.12 | 0.00 | 0.89 | 353178.82 | 0.00 | 0.00 | 0.00 | 0.00 | 2325.71 | 2192.05 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.249861E+10 | 0.00 | 595.14 | 0.154081E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5373.79 | 4391.62 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.101517E+10 | 0.00 | 109.39 | 0.773157E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19451.24 | 10-JAN-16:01 | 19451.24 | 10-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.151036E+10 | 0.00 | 171.77 | 0.123978E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19451.72 | 22-FEB-16:01 | 19451.72 | 22-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.274054E+10 | 0.00 | 271.50 | 0.188983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19451.09 | 15-MAR-18:01 | 19451.09 | 15-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.393129E+10 | 0.00 | 381.61 | 0.233533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19444.29 | 11-APR-15:01 | 19444.29 | 11-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.621515E+10 | 0.00 | 594.22 | 0.323914E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21294.69 | 19-MAY-15:01 | 19445.03 | 27-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.108671E+11 | 0.00 | 660.07 | 0.537141E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24501.13 | 27-JUN-08:62 | 17814.17 | 15-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.143533E+11 | 0.00 | 710.98 | 0.800836E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24294.10 | 28-JUL-08:61 | 17935.97 | 07-JUL-08:62 | 0.00 | 0.00 | 0.00 |
August | 0.156212E+11 | 0.00 | 714.45 | 0.986923E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23610.05 | 06-AUG-08:61 | 17892.81 | 13-AUG-08:62 | 0.00 | 0.00 | 0.00 |
September | 0.114269E+11 | 0.00 | 653.84 | 0.672809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26176.50 | 22-SEP-18:01 | 19449.02 | 10-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.100360E+11 | 0.00 | 621.05 | 0.640330E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22280.06 | 05-OCT-18:02 | 19449.93 | 26-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.257825E+10 | 0.00 | 271.66 | 0.156580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20500.28 | 10-NOV-09:02 | 19448.29 | 02-NOV-18:01 | 0.00 | 0.00 | 0.00 |
December | 0.173129E+10 | 0.00 | 165.58 | 0.131313E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19451.44 | 15-DEC-16:01 | 19451.44 | 15-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.820265E+11 | 0.00 | 5326.13 | 0.487366E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.101517E+10 | 0.00 | 109.39 | 0.773157E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19444.29 | 17814.17 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.156212E+11 | 0.00 | 714.45 | 0.986923E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26176.50 | 19451.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 609.38 | 399.88 | 209.50 | 597.00 | 624.56 | 0.00 | 0.00 | 0.00 |
February | 806.45 | 535.99 | 270.46 | 806.05 | 618.90 | 0.00 | 0.00 | 0.00 |
March | 714.52 | 393.33 | 321.18 | 760.15 | 440.11 | 0.00 | 0.00 | 0.00 |
April | 568.74 | 230.10 | 338.64 | 639.57 | 310.26 | 0.00 | 0.00 | 0.00 |
May | 488.48 | 100.01 | 388.47 | 598.59 | 177.34 | 0.00 | 0.00 | 0.00 |
June | 461.24 | 71.07 | 390.17 | 650.98 | 84.68 | 0.00 | 0.00 | 0.00 |
July | 479.92 | 81.00 | 398.92 | 746.58 | 35.75 | 0.00 | 0.00 | 0.00 |
August | 642.81 | 237.13 | 405.68 | 986.36 | 63.61 | 0.00 | 0.00 | 0.00 |
September | 678.34 | 340.59 | 337.75 | 926.68 | 135.67 | 0.00 | 0.00 | 0.00 |
October | 958.61 | 601.13 | 357.48 | 1203.25 | 279.37 | 0.00 | 0.00 | 0.00 |
November | 663.77 | 398.18 | 265.59 | 709.37 | 432.80 | 0.00 | 0.00 | 0.00 |
December | 658.37 | 467.61 | 190.76 | 673.65 | 561.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 643.45 | 320.24 | 323.20 | 775.07 | 312.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 461.24 | 71.07 | 190.76 | 597.00 | 35.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 958.61 | 601.13 | 405.68 | 1203.25 | 624.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1715.97 | 1126.05 | 589.93 | 1659.82 | 1817.83 | 0.00 | 0.00 | 0.00 |
February | 2270.92 | 1509.32 | 761.60 | 2240.14 | 1806.70 | 0.00 | 0.00 | 0.00 |
March | 2012.03 | 1107.60 | 904.43 | 2111.33 | 1319.86 | 0.00 | 0.00 | 0.00 |
April | 1601.52 | 647.94 | 953.59 | 1768.83 | 949.96 | 0.00 | 0.00 | 0.00 |
May | 1375.52 | 281.62 | 1093.90 | 1641.50 | 566.30 | 0.00 | 0.00 | 0.00 |
June | 1298.82 | 200.12 | 1098.70 | 1802.31 | 277.96 | 0.00 | 0.00 | 0.00 |
July | 1351.43 | 228.09 | 1123.34 | 2078.60 | 122.84 | 0.00 | 0.00 | 0.00 |
August | 1810.11 | 667.74 | 1142.38 | 2757.46 | 198.48 | 0.00 | 0.00 | 0.00 |
September | 1910.16 | 959.07 | 951.10 | 2579.99 | 435.95 | 0.00 | 0.00 | 0.00 |
October | 2699.38 | 1692.74 | 1006.64 | 3354.11 | 861.15 | 0.00 | 0.00 | 0.00 |
November | 1869.14 | 1121.25 | 747.90 | 1964.82 | 1298.60 | 0.00 | 0.00 | 0.00 |
December | 1853.92 | 1316.75 | 537.17 | 1872.44 | 1652.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1811.90 | 901.78 | 910.12 | 2153.25 | 937.48 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1298.82 | 200.12 | 537.17 | 1641.50 | 122.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2699.38 | 1692.74 | 1142.38 | 3354.11 | 1817.83 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2229.15 | 1462.80 | 766.35 | 2189.91 | 2475.71 | 0.00 | 0.00 | 0.00 |
February | 2950.05 | 1960.69 | 989.36 | 2964.70 | 2441.26 | 0.00 | 0.00 | 0.00 |
March | 2613.75 | 1438.84 | 1174.91 | 2796.68 | 1787.28 | 0.00 | 0.00 | 0.00 |
April | 2080.47 | 841.71 | 1238.76 | 2341.87 | 1295.34 | 0.00 | 0.00 | 0.00 |
May | 1786.87 | 365.84 | 1421.04 | 2171.54 | 773.77 | 0.00 | 0.00 | 0.00 |
June | 1687.25 | 259.97 | 1427.28 | 2391.30 | 373.52 | 0.00 | 0.00 | 0.00 |
July | 1755.59 | 296.31 | 1459.28 | 2767.96 | 161.51 | 0.00 | 0.00 | 0.00 |
August | 2351.44 | 867.43 | 1484.02 | 3671.01 | 255.77 | 0.00 | 0.00 | 0.00 |
September | 2481.41 | 1245.88 | 1235.53 | 3418.90 | 579.70 | 0.00 | 0.00 | 0.00 |
October | 3506.65 | 2198.97 | 1307.68 | 4444.99 | 1140.79 | 0.00 | 0.00 | 0.00 |
November | 2428.12 | 1456.56 | 971.56 | 2592.30 | 1770.30 | 0.00 | 0.00 | 0.00 |
December | 2408.35 | 1710.53 | 697.81 | 2470.59 | 2251.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2353.77 | 1171.47 | 1182.30 | 2852.70 | 1268.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1687.25 | 259.97 | 697.81 | 2171.54 | 161.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3506.65 | 2198.97 | 1484.02 | 4444.99 | 2475.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 120.49 | 79.06 | 41.42 | 118.43 | 125.56 | 0.00 | 0.00 | 0.00 |
February | 159.45 | 105.97 | 53.48 | 159.86 | 124.70 | 0.00 | 0.00 | 0.00 |
March | 141.27 | 77.77 | 63.50 | 149.92 | 89.04 | 0.00 | 0.00 | 0.00 |
April | 112.45 | 45.49 | 66.96 | 125.82 | 62.19 | 0.00 | 0.00 | 0.00 |
May | 96.58 | 19.77 | 76.81 | 117.20 | 34.66 | 0.00 | 0.00 | 0.00 |
June | 91.20 | 14.05 | 77.14 | 130.91 | 13.25 | 0.00 | 0.00 | 0.00 |
July | 94.89 | 16.02 | 78.87 | 154.32 | 3.26 | 0.00 | 0.00 | 0.00 |
August | 127.10 | 46.88 | 80.21 | 202.80 | 7.80 | 0.00 | 0.00 | 0.00 |
September | 134.12 | 67.34 | 66.78 | 186.48 | 22.42 | 0.00 | 0.00 | 0.00 |
October | 189.53 | 118.85 | 70.68 | 240.21 | 51.83 | 0.00 | 0.00 | 0.00 |
November | 131.24 | 78.73 | 52.51 | 141.23 | 85.76 | 0.00 | 0.00 | 0.00 |
December | 130.17 | 92.45 | 37.72 | 134.20 | 112.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 127.22 | 63.32 | 63.90 | 155.18 | 60.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 91.20 | 14.05 | 37.72 | 117.20 | 3.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 189.53 | 118.85 | 80.21 | 240.21 | 125.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.55 | 36.76 | 52.79 | 52.47 | 254.17 | 0.00 | 0.00 | 0.00 |
February | 131.54 | 57.73 | 73.81 | 86.74 | 257.16 | 0.00 | 0.00 | 0.00 |
March | 195.39 | 90.55 | 104.84 | 172.96 | 166.09 | 0.00 | 0.00 | 0.00 |
April | 212.21 | 90.69 | 121.52 | 219.98 | 113.52 | 0.00 | 0.00 | 0.00 |
May | 247.91 | 94.24 | 153.67 | 298.48 | 62.68 | 0.00 | 0.00 | 0.00 |
June | 270.86 | 109.31 | 161.55 | 373.51 | 24.19 | 0.00 | 0.00 | 0.00 |
July | 253.41 | 95.23 | 158.18 | 383.39 | 6.02 | 0.00 | 0.00 | 0.00 |
August | 280.37 | 129.63 | 150.74 | 418.53 | 14.47 | 0.00 | 0.00 | 0.00 |
September | 199.48 | 87.09 | 112.39 | 262.57 | 41.98 | 0.00 | 0.00 | 0.00 |
October | 197.92 | 96.42 | 101.51 | 225.99 | 99.69 | 0.00 | 0.00 | 0.00 |
November | 93.21 | 27.23 | 65.98 | 61.93 | 170.97 | 0.00 | 0.00 | 0.00 |
December | 82.33 | 35.54 | 46.79 | 49.40 | 230.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 188.24 | 79.38 | 108.86 | 218.10 | 119.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 82.33 | 27.23 | 46.79 | 49.40 | 6.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 280.37 | 129.63 | 161.55 | 418.53 | 257.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.18 | 0.00 | 23.18 | 1.19 | 141.32 | 0.00 | 0.00 | 0.00 |
February | 31.72 | 0.00 | 31.72 | 2.73 | 144.71 | 0.00 | 0.00 | 0.00 |
March | 44.00 | 0.00 | 44.00 | 15.28 | 93.51 | 0.00 | 0.00 | 0.00 |
April | 52.95 | 0.22 | 52.73 | 34.35 | 61.91 | 0.00 | 0.00 | 0.00 |
May | 70.43 | 2.58 | 67.85 | 69.51 | 33.59 | 0.00 | 0.00 | 0.00 |
June | 74.30 | 3.95 | 70.35 | 96.51 | 15.17 | 0.00 | 0.00 | 0.00 |
July | 72.11 | 2.81 | 69.30 | 113.40 | 4.34 | 0.00 | 0.00 | 0.00 |
August | 63.77 | 0.85 | 62.92 | 99.79 | 8.67 | 0.00 | 0.00 | 0.00 |
September | 48.02 | 0.03 | 47.99 | 55.66 | 24.95 | 0.00 | 0.00 | 0.00 |
October | 41.52 | 0.00 | 41.52 | 32.27 | 55.19 | 0.00 | 0.00 | 0.00 |
November | 29.12 | 0.00 | 29.12 | 8.66 | 93.10 | 0.00 | 0.00 | 0.00 |
December | 20.22 | 0.00 | 20.22 | 0.82 | 127.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47.70 | 0.87 | 46.83 | 44.47 | 66.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.22 | 0.00 | 20.22 | 0.82 | 4.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.30 | 3.95 | 70.35 | 113.40 | 144.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.55 | 36.76 | 52.79 | 55.27 | 251.45 | 0.00 | 0.00 | 0.00 |
February | 131.54 | 57.73 | 73.81 | 90.87 | 253.05 | 0.00 | 0.00 | 0.00 |
March | 195.39 | 90.55 | 104.84 | 177.33 | 163.84 | 0.00 | 0.00 | 0.00 |
April | 212.21 | 90.69 | 121.52 | 221.70 | 113.23 | 0.00 | 0.00 | 0.00 |
May | 247.91 | 94.24 | 153.67 | 295.84 | 65.00 | 0.00 | 0.00 | 0.00 |
June | 270.86 | 109.31 | 161.55 | 366.89 | 29.04 | 0.00 | 0.00 | 0.00 |
July | 253.41 | 95.23 | 158.18 | 380.89 | 8.13 | 0.00 | 0.00 | 0.00 |
August | 280.37 | 129.63 | 150.74 | 418.20 | 16.46 | 0.00 | 0.00 | 0.00 |
September | 199.48 | 87.09 | 112.39 | 261.43 | 45.75 | 0.00 | 0.00 | 0.00 |
October | 197.92 | 96.42 | 101.51 | 228.92 | 100.14 | 0.00 | 0.00 | 0.00 |
November | 93.21 | 27.23 | 65.98 | 65.56 | 168.09 | 0.00 | 0.00 | 0.00 |
December | 82.33 | 35.54 | 46.79 | 52.66 | 227.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 188.24 | 79.38 | 108.86 | 218.89 | 119.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 82.33 | 27.23 | 46.79 | 52.66 | 8.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 280.37 | 129.63 | 161.55 | 418.20 | 253.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.37 | 63.24 | 33.13 | 92.87 | 104.25 | 0.00 | 0.00 | 0.00 |
February | 127.53 | 84.76 | 42.77 | 119.43 | 121.58 | 0.00 | 0.00 | 0.00 |
March | 113.00 | 62.20 | 50.79 | 111.00 | 95.64 | 0.00 | 0.00 | 0.00 |
April | 89.94 | 36.39 | 53.55 | 90.24 | 72.51 | 0.00 | 0.00 | 0.00 |
May | 77.25 | 15.82 | 61.43 | 80.63 | 46.48 | 0.00 | 0.00 | 0.00 |
June | 72.94 | 11.24 | 61.70 | 90.27 | 25.39 | 0.00 | 0.00 | 0.00 |
July | 75.90 | 12.81 | 63.09 | 106.82 | 14.49 | 0.00 | 0.00 | 0.00 |
August | 101.66 | 37.50 | 64.16 | 146.45 | 18.99 | 0.00 | 0.00 | 0.00 |
September | 107.27 | 53.86 | 53.41 | 136.63 | 36.64 | 0.00 | 0.00 | 0.00 |
October | 151.60 | 95.06 | 56.53 | 180.14 | 63.73 | 0.00 | 0.00 | 0.00 |
November | 104.97 | 62.97 | 42.00 | 102.78 | 94.16 | 0.00 | 0.00 | 0.00 |
December | 104.12 | 73.95 | 30.17 | 100.08 | 110.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 101.76 | 50.64 | 51.11 | 113.15 | 66.73 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 72.94 | 11.24 | 30.17 | 80.63 | 14.49 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 151.60 | 95.06 | 64.16 | 180.14 | 121.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 18.55 | 0.00 | 18.55 | 0.64 | 118.44 | 0.00 | 0.00 | 0.00 |
February | 25.38 | 0.00 | 25.38 | 1.91 | 120.11 | 0.00 | 0.00 | 0.00 |
March | 35.20 | 0.00 | 35.20 | 12.15 | 76.60 | 0.00 | 0.00 | 0.00 |
April | 42.37 | 0.17 | 42.19 | 28.50 | 50.08 | 0.00 | 0.00 | 0.00 |
May | 56.35 | 2.06 | 54.29 | 58.53 | 26.19 | 0.00 | 0.00 | 0.00 |
June | 59.45 | 3.16 | 56.28 | 81.73 | 10.59 | 0.00 | 0.00 | 0.00 |
July | 57.70 | 2.25 | 55.45 | 95.12 | 2.63 | 0.00 | 0.00 | 0.00 |
August | 51.02 | 0.68 | 50.35 | 84.61 | 5.75 | 0.00 | 0.00 | 0.00 |
September | 38.42 | 0.02 | 38.40 | 47.23 | 18.49 | 0.00 | 0.00 | 0.00 |
October | 33.22 | 0.00 | 33.22 | 27.41 | 42.94 | 0.00 | 0.00 | 0.00 |
November | 23.30 | 0.00 | 23.30 | 6.57 | 78.00 | 0.00 | 0.00 | 0.00 |
December | 16.18 | 0.00 | 16.18 | 0.48 | 107.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.17 | 0.70 | 37.47 | 37.32 | 54.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 16.18 | 0.00 | 16.18 | 0.48 | 2.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 59.45 | 3.16 | 56.28 | 95.12 | 120.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 90.17 | 36.03 | 54.15 | 51.09 | 249.93 | 0.00 | 0.00 | 0.00 |
February | 140.00 | 65.20 | 74.81 | 92.34 | 248.22 | 0.00 | 0.00 | 0.00 |
March | 179.79 | 76.41 | 103.38 | 153.70 | 166.91 | 0.00 | 0.00 | 0.00 |
April | 215.22 | 94.46 | 120.76 | 221.43 | 110.15 | 0.00 | 0.00 | 0.00 |
May | 259.83 | 103.55 | 156.29 | 313.71 | 60.74 | 0.00 | 0.00 | 0.00 |
June | 241.27 | 87.39 | 153.88 | 333.19 | 23.07 | 0.00 | 0.00 | 0.00 |
July | 242.01 | 87.13 | 154.88 | 368.80 | 5.70 | 0.00 | 0.00 | 0.00 |
August | 273.01 | 123.17 | 149.84 | 408.06 | 13.57 | 0.00 | 0.00 | 0.00 |
September | 204.23 | 92.00 | 112.22 | 268.03 | 40.26 | 0.00 | 0.00 | 0.00 |
October | 184.50 | 83.51 | 100.99 | 207.10 | 96.95 | 0.00 | 0.00 | 0.00 |
November | 114.27 | 43.91 | 70.36 | 88.68 | 166.54 | 0.00 | 0.00 | 0.00 |
December | 89.34 | 42.15 | 47.19 | 56.92 | 225.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 186.43 | 78.00 | 108.44 | 214.43 | 116.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 89.34 | 36.03 | 47.19 | 51.09 | 5.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 273.01 | 123.17 | 156.29 | 408.06 | 249.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 120.49 | 79.06 | 41.42 | 118.13 | 125.37 | 0.00 | 0.00 | 0.00 |
February | 159.45 | 105.97 | 53.48 | 159.12 | 124.40 | 0.00 | 0.00 | 0.00 |
March | 141.27 | 77.77 | 63.50 | 149.06 | 88.27 | 0.00 | 0.00 | 0.00 |
April | 112.45 | 45.49 | 66.96 | 124.86 | 61.76 | 0.00 | 0.00 | 0.00 |
May | 96.58 | 19.77 | 76.81 | 116.30 | 34.22 | 0.00 | 0.00 | 0.00 |
June | 91.20 | 14.05 | 77.14 | 130.93 | 12.80 | 0.00 | 0.00 | 0.00 |
July | 94.89 | 16.02 | 78.87 | 154.25 | 3.08 | 0.00 | 0.00 | 0.00 |
August | 127.10 | 46.88 | 80.21 | 202.57 | 7.53 | 0.00 | 0.00 | 0.00 |
September | 134.12 | 67.34 | 66.78 | 186.00 | 22.13 | 0.00 | 0.00 | 0.00 |
October | 189.53 | 118.85 | 70.68 | 239.72 | 51.31 | 0.00 | 0.00 | 0.00 |
November | 131.24 | 78.73 | 52.51 | 140.48 | 85.85 | 0.00 | 0.00 | 0.00 |
December | 130.17 | 92.45 | 37.72 | 133.80 | 111.92 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 127.22 | 63.32 | 63.90 | 154.66 | 60.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 91.20 | 14.05 | 37.72 | 116.30 | 3.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 189.53 | 118.85 | 80.21 | 239.72 | 125.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.18 | 0.00 | 23.18 | 1.04 | 141.28 | 0.00 | 0.00 | 0.00 |
February | 31.72 | 0.00 | 31.72 | 2.53 | 144.73 | 0.00 | 0.00 | 0.00 |
March | 44.00 | 0.00 | 44.00 | 14.58 | 92.75 | 0.00 | 0.00 | 0.00 |
April | 52.95 | 0.22 | 52.73 | 33.46 | 61.43 | 0.00 | 0.00 | 0.00 |
May | 70.43 | 2.58 | 67.85 | 68.78 | 32.91 | 0.00 | 0.00 | 0.00 |
June | 74.30 | 3.95 | 70.35 | 96.83 | 14.18 | 0.00 | 0.00 | 0.00 |
July | 72.11 | 2.81 | 69.30 | 112.93 | 4.08 | 0.00 | 0.00 | 0.00 |
August | 63.77 | 0.85 | 62.92 | 98.89 | 8.29 | 0.00 | 0.00 | 0.00 |
September | 48.02 | 0.03 | 47.99 | 54.84 | 24.20 | 0.00 | 0.00 | 0.00 |
October | 41.52 | 0.00 | 41.52 | 31.50 | 53.94 | 0.00 | 0.00 | 0.00 |
November | 29.12 | 0.00 | 29.12 | 8.14 | 93.34 | 0.00 | 0.00 | 0.00 |
December | 20.22 | 0.00 | 20.22 | 0.70 | 127.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47.70 | 0.87 | 46.83 | 43.97 | 66.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.22 | 0.00 | 20.22 | 0.70 | 4.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.30 | 3.95 | 70.35 | 112.93 | 144.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 90.17 | 36.03 | 54.15 | 52.70 | 245.95 | 0.00 | 0.00 | 0.00 |
February | 140.00 | 65.20 | 74.81 | 94.98 | 242.30 | 0.00 | 0.00 | 0.00 |
March | 179.79 | 76.41 | 103.38 | 157.59 | 163.85 | 0.00 | 0.00 | 0.00 |
April | 215.22 | 94.46 | 120.76 | 223.26 | 109.55 | 0.00 | 0.00 | 0.00 |
May | 259.83 | 103.55 | 156.29 | 311.77 | 62.78 | 0.00 | 0.00 | 0.00 |
June | 241.27 | 87.39 | 153.88 | 327.60 | 27.21 | 0.00 | 0.00 | 0.00 |
July | 242.01 | 87.13 | 154.88 | 365.51 | 7.70 | 0.00 | 0.00 | 0.00 |
August | 273.01 | 123.17 | 149.84 | 406.35 | 15.35 | 0.00 | 0.00 | 0.00 |
September | 204.23 | 92.00 | 112.22 | 266.56 | 43.41 | 0.00 | 0.00 | 0.00 |
October | 184.50 | 83.51 | 100.99 | 210.22 | 96.48 | 0.00 | 0.00 | 0.00 |
November | 114.27 | 43.91 | 70.36 | 91.73 | 163.00 | 0.00 | 0.00 | 0.00 |
December | 89.34 | 42.15 | 47.19 | 58.59 | 219.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 186.43 | 78.00 | 108.44 | 214.74 | 115.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 89.34 | 36.03 | 47.19 | 52.70 | 7.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 273.01 | 123.17 | 156.29 | 406.35 | 245.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 29.36 | 0.00 | 29.36 | 0.80 | 192.32 | 0.00 | 0.00 | 0.00 |
February | 40.17 | 0.00 | 40.17 | 2.70 | 195.62 | 0.00 | 0.00 | 0.00 |
March | 55.72 | 0.00 | 55.72 | 18.78 | 123.64 | 0.00 | 0.00 | 0.00 |
April | 67.06 | 0.28 | 66.78 | 45.13 | 81.96 | 0.00 | 0.00 | 0.00 |
May | 89.19 | 3.26 | 85.93 | 92.36 | 44.41 | 0.00 | 0.00 | 0.00 |
June | 94.09 | 5.00 | 89.09 | 126.46 | 20.71 | 0.00 | 0.00 | 0.00 |
July | 91.33 | 3.56 | 87.76 | 142.75 | 7.78 | 0.00 | 0.00 | 0.00 |
August | 80.76 | 1.07 | 79.69 | 124.41 | 14.04 | 0.00 | 0.00 | 0.00 |
September | 60.81 | 0.04 | 60.78 | 71.40 | 34.88 | 0.00 | 0.00 | 0.00 |
October | 52.59 | 0.00 | 52.59 | 40.74 | 75.39 | 0.00 | 0.00 | 0.00 |
November | 36.88 | 0.00 | 36.88 | 9.90 | 126.81 | 0.00 | 0.00 | 0.00 |
December | 25.61 | 0.00 | 25.61 | 0.63 | 174.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 60.41 | 1.11 | 59.31 | 56.70 | 90.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.61 | 0.00 | 25.61 | 0.63 | 7.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 94.09 | 5.00 | 89.09 | 142.75 | 195.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 10.82 | 0.00 | 10.82 | 0.29 | 70.90 | 0.00 | 0.00 | 0.00 |
February | 14.81 | 0.00 | 14.81 | 0.99 | 72.12 | 0.00 | 0.00 | 0.00 |
March | 20.54 | 0.00 | 20.54 | 6.92 | 45.58 | 0.00 | 0.00 | 0.00 |
April | 24.72 | 0.10 | 24.62 | 16.64 | 30.21 | 0.00 | 0.00 | 0.00 |
May | 32.88 | 1.20 | 31.68 | 34.05 | 16.37 | 0.00 | 0.00 | 0.00 |
June | 34.69 | 1.84 | 32.84 | 46.62 | 7.63 | 0.00 | 0.00 | 0.00 |
July | 33.67 | 1.31 | 32.35 | 52.62 | 2.87 | 0.00 | 0.00 | 0.00 |
August | 29.77 | 0.40 | 29.38 | 45.86 | 5.18 | 0.00 | 0.00 | 0.00 |
September | 22.42 | 0.01 | 22.41 | 26.32 | 12.86 | 0.00 | 0.00 | 0.00 |
October | 19.39 | 0.00 | 19.39 | 15.02 | 27.79 | 0.00 | 0.00 | 0.00 |
November | 13.60 | 0.00 | 13.60 | 3.65 | 46.75 | 0.00 | 0.00 | 0.00 |
December | 9.44 | 0.00 | 9.44 | 0.23 | 64.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 22.27 | 0.41 | 21.86 | 20.90 | 33.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 9.44 | 0.00 | 9.44 | 0.23 | 2.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 34.69 | 1.84 | 32.84 | 52.62 | 72.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.22 | 36.89 | 19.33 | 54.99 | 61.75 | 0.00 | 0.00 | 0.00 |
February | 74.40 | 49.45 | 24.95 | 74.61 | 60.72 | 0.00 | 0.00 | 0.00 |
March | 65.92 | 36.29 | 29.63 | 70.75 | 42.81 | 0.00 | 0.00 | 0.00 |
April | 52.47 | 21.23 | 31.24 | 59.69 | 30.23 | 0.00 | 0.00 | 0.00 |
May | 45.06 | 9.23 | 35.84 | 55.68 | 17.52 | 0.00 | 0.00 | 0.00 |
June | 42.55 | 6.56 | 36.00 | 61.13 | 8.08 | 0.00 | 0.00 | 0.00 |
July | 44.28 | 7.47 | 36.80 | 71.05 | 2.93 | 0.00 | 0.00 | 0.00 |
August | 59.30 | 21.88 | 37.43 | 93.78 | 5.32 | 0.00 | 0.00 | 0.00 |
September | 62.58 | 31.42 | 31.16 | 87.08 | 12.70 | 0.00 | 0.00 | 0.00 |
October | 88.44 | 55.46 | 32.98 | 112.90 | 26.30 | 0.00 | 0.00 | 0.00 |
November | 61.24 | 36.73 | 24.50 | 66.05 | 42.01 | 0.00 | 0.00 | 0.00 |
December | 60.74 | 43.14 | 17.60 | 62.58 | 54.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 59.36 | 29.54 | 29.82 | 72.55 | 30.28 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 42.55 | 6.56 | 17.60 | 54.99 | 2.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.44 | 55.46 | 37.43 | 112.90 | 61.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 152.59 | 100.13 | 52.46 | 149.24 | 167.61 | 0.00 | 0.00 | 0.00 |
February | 201.93 | 134.21 | 67.72 | 202.50 | 164.81 | 0.00 | 0.00 | 0.00 |
March | 178.91 | 98.49 | 80.42 | 192.04 | 116.19 | 0.00 | 0.00 | 0.00 |
April | 142.41 | 57.62 | 84.79 | 162.02 | 82.04 | 0.00 | 0.00 | 0.00 |
May | 122.31 | 25.04 | 97.27 | 151.13 | 47.54 | 0.00 | 0.00 | 0.00 |
June | 115.49 | 17.80 | 97.70 | 165.91 | 21.94 | 0.00 | 0.00 | 0.00 |
July | 120.17 | 20.28 | 99.89 | 192.84 | 7.96 | 0.00 | 0.00 | 0.00 |
August | 160.96 | 59.38 | 101.58 | 254.53 | 14.45 | 0.00 | 0.00 | 0.00 |
September | 169.85 | 85.28 | 84.57 | 236.36 | 34.47 | 0.00 | 0.00 | 0.00 |
October | 240.03 | 150.52 | 89.51 | 306.42 | 71.39 | 0.00 | 0.00 | 0.00 |
November | 166.21 | 99.70 | 66.50 | 179.27 | 114.03 | 0.00 | 0.00 | 0.00 |
December | 164.85 | 117.09 | 47.77 | 169.86 | 149.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 161.12 | 80.19 | 80.93 | 196.92 | 82.18 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 115.49 | 17.80 | 47.77 | 149.24 | 7.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 240.03 | 150.52 | 101.58 | 306.42 | 167.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 120.49 | 79.06 | 41.42 | 118.04 | 124.86 | 0.00 | 0.00 | 0.00 |
February | 159.45 | 105.97 | 53.48 | 159.22 | 124.18 | 0.00 | 0.00 | 0.00 |
March | 141.27 | 77.77 | 63.50 | 148.88 | 88.77 | 0.00 | 0.00 | 0.00 |
April | 112.45 | 45.49 | 66.96 | 124.68 | 61.88 | 0.00 | 0.00 | 0.00 |
May | 96.58 | 19.77 | 76.81 | 115.82 | 34.48 | 0.00 | 0.00 | 0.00 |
June | 91.20 | 14.05 | 77.14 | 129.69 | 12.95 | 0.00 | 0.00 | 0.00 |
July | 94.89 | 16.02 | 78.87 | 153.26 | 3.02 | 0.00 | 0.00 | 0.00 |
August | 127.10 | 46.88 | 80.21 | 201.62 | 7.42 | 0.00 | 0.00 | 0.00 |
September | 134.12 | 67.34 | 66.78 | 185.29 | 21.91 | 0.00 | 0.00 | 0.00 |
October | 189.53 | 118.85 | 70.68 | 238.82 | 51.14 | 0.00 | 0.00 | 0.00 |
November | 131.24 | 78.73 | 52.51 | 140.80 | 84.90 | 0.00 | 0.00 | 0.00 |
December | 130.17 | 92.45 | 37.72 | 133.90 | 111.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 127.22 | 63.32 | 63.90 | 154.23 | 60.20 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 91.20 | 14.05 | 37.72 | 115.82 | 3.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 189.53 | 118.85 | 80.21 | 238.82 | 124.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.55 | 36.76 | 52.79 | 52.33 | 252.87 | 0.00 | 0.00 | 0.00 |
February | 131.54 | 57.73 | 73.81 | 86.03 | 256.35 | 0.00 | 0.00 | 0.00 |
March | 195.39 | 90.55 | 104.84 | 171.38 | 165.28 | 0.00 | 0.00 | 0.00 |
April | 212.21 | 90.69 | 121.52 | 217.97 | 112.68 | 0.00 | 0.00 | 0.00 |
May | 247.91 | 94.24 | 153.67 | 295.69 | 62.17 | 0.00 | 0.00 | 0.00 |
June | 270.86 | 109.31 | 161.55 | 370.60 | 23.57 | 0.00 | 0.00 | 0.00 |
July | 253.41 | 95.23 | 158.18 | 381.02 | 5.58 | 0.00 | 0.00 | 0.00 |
August | 280.37 | 129.63 | 150.74 | 416.42 | 13.74 | 0.00 | 0.00 | 0.00 |
September | 199.48 | 87.09 | 112.39 | 260.87 | 40.96 | 0.00 | 0.00 | 0.00 |
October | 197.92 | 96.42 | 101.51 | 224.35 | 98.23 | 0.00 | 0.00 | 0.00 |
November | 93.21 | 27.23 | 65.98 | 61.70 | 169.30 | 0.00 | 0.00 | 0.00 |
December | 82.33 | 35.54 | 46.79 | 49.33 | 228.70 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 188.24 | 79.38 | 108.86 | 216.57 | 118.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 82.33 | 27.23 | 46.79 | 49.33 | 5.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 280.37 | 129.63 | 161.55 | 416.42 | 256.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.18 | 0.00 | 23.18 | 1.28 | 140.56 | 0.00 | 0.00 | 0.00 |
February | 31.72 | 0.00 | 31.72 | 2.80 | 144.32 | 0.00 | 0.00 | 0.00 |
March | 44.00 | 0.00 | 44.00 | 15.24 | 93.14 | 0.00 | 0.00 | 0.00 |
April | 52.95 | 0.22 | 52.73 | 33.95 | 61.66 | 0.00 | 0.00 | 0.00 |
May | 70.43 | 2.58 | 67.85 | 68.20 | 33.85 | 0.00 | 0.00 | 0.00 |
June | 74.30 | 3.95 | 70.35 | 95.24 | 15.60 | 0.00 | 0.00 | 0.00 |
July | 72.11 | 2.81 | 69.30 | 112.59 | 4.33 | 0.00 | 0.00 | 0.00 |
August | 63.77 | 0.85 | 62.92 | 99.39 | 8.45 | 0.00 | 0.00 | 0.00 |
September | 48.02 | 0.03 | 47.99 | 55.22 | 24.91 | 0.00 | 0.00 | 0.00 |
October | 41.52 | 0.00 | 41.52 | 32.27 | 54.58 | 0.00 | 0.00 | 0.00 |
November | 29.12 | 0.00 | 29.12 | 8.84 | 91.92 | 0.00 | 0.00 | 0.00 |
December | 20.22 | 0.00 | 20.22 | 0.90 | 126.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47.70 | 0.87 | 46.83 | 44.12 | 66.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.22 | 0.00 | 20.22 | 0.90 | 4.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.30 | 3.95 | 70.35 | 112.59 | 144.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.55 | 36.76 | 52.79 | 55.26 | 250.26 | 0.00 | 0.00 | 0.00 |
February | 131.54 | 57.73 | 73.81 | 90.40 | 252.39 | 0.00 | 0.00 | 0.00 |
March | 195.39 | 90.55 | 104.84 | 176.16 | 162.93 | 0.00 | 0.00 | 0.00 |
April | 212.21 | 90.69 | 121.52 | 219.67 | 112.59 | 0.00 | 0.00 | 0.00 |
May | 247.91 | 94.24 | 153.67 | 292.42 | 65.29 | 0.00 | 0.00 | 0.00 |
June | 270.86 | 109.31 | 161.55 | 363.13 | 29.76 | 0.00 | 0.00 | 0.00 |
July | 253.41 | 95.23 | 158.18 | 378.37 | 8.03 | 0.00 | 0.00 | 0.00 |
August | 280.37 | 129.63 | 150.74 | 416.19 | 15.99 | 0.00 | 0.00 | 0.00 |
September | 199.48 | 87.09 | 112.39 | 259.55 | 45.47 | 0.00 | 0.00 | 0.00 |
October | 197.92 | 96.42 | 101.51 | 227.67 | 98.86 | 0.00 | 0.00 | 0.00 |
November | 93.21 | 27.23 | 65.98 | 65.72 | 166.18 | 0.00 | 0.00 | 0.00 |
December | 82.33 | 35.54 | 46.79 | 52.87 | 225.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 188.24 | 79.38 | 108.86 | 217.37 | 118.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 82.33 | 27.23 | 46.79 | 52.87 | 8.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 280.37 | 129.63 | 161.55 | 416.19 | 252.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 176.70 | 115.95 | 60.75 | 167.56 | 190.20 | 0.00 | 0.00 | 0.00 |
February | 233.85 | 155.42 | 78.43 | 226.44 | 189.34 | 0.00 | 0.00 | 0.00 |
March | 207.19 | 114.06 | 93.13 | 214.59 | 133.78 | 0.00 | 0.00 | 0.00 |
April | 164.92 | 66.72 | 98.20 | 181.29 | 91.91 | 0.00 | 0.00 | 0.00 |
May | 141.64 | 29.00 | 112.65 | 171.03 | 49.80 | 0.00 | 0.00 | 0.00 |
June | 133.75 | 20.61 | 113.14 | 193.54 | 17.56 | 0.00 | 0.00 | 0.00 |
July | 139.17 | 23.49 | 115.68 | 228.45 | 3.71 | 0.00 | 0.00 | 0.00 |
August | 186.40 | 68.76 | 117.64 | 298.68 | 10.04 | 0.00 | 0.00 | 0.00 |
September | 196.70 | 98.76 | 97.94 | 271.68 | 31.86 | 0.00 | 0.00 | 0.00 |
October | 277.97 | 174.31 | 103.66 | 347.44 | 76.67 | 0.00 | 0.00 | 0.00 |
November | 192.48 | 115.46 | 77.02 | 201.02 | 130.87 | 0.00 | 0.00 | 0.00 |
December | 190.91 | 135.59 | 55.32 | 190.42 | 170.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 186.58 | 92.86 | 93.72 | 224.46 | 90.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 133.75 | 20.61 | 55.32 | 167.56 | 3.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 277.97 | 174.31 | 117.64 | 347.44 | 190.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 162.25 | 0.00 | 162.25 | 1.40 | 1187.47 | 0.00 | 0.00 | 0.00 |
February | 222.04 | 0.00 | 222.04 | 8.46 | 1200.75 | 0.00 | 0.00 | 0.00 |
March | 307.98 | 0.01 | 307.98 | 77.46 | 795.89 | 0.00 | 0.00 | 0.00 |
April | 370.63 | 1.53 | 369.11 | 205.59 | 537.31 | 0.00 | 0.00 | 0.00 |
May | 492.96 | 18.04 | 474.92 | 448.70 | 290.18 | 0.00 | 0.00 | 0.00 |
June | 520.06 | 27.66 | 492.40 | 655.92 | 135.65 | 0.00 | 0.00 | 0.00 |
July | 504.77 | 19.70 | 485.07 | 752.55 | 56.82 | 0.00 | 0.00 | 0.00 |
August | 446.39 | 5.93 | 440.46 | 660.13 | 87.70 | 0.00 | 0.00 | 0.00 |
September | 336.12 | 0.20 | 335.92 | 365.02 | 223.83 | 0.00 | 0.00 | 0.00 |
October | 290.65 | 0.00 | 290.65 | 198.99 | 465.50 | 0.00 | 0.00 | 0.00 |
November | 203.86 | 0.00 | 203.86 | 38.58 | 814.61 | 0.00 | 0.00 | 0.00 |
December | 141.53 | 0.00 | 141.53 | 1.40 | 1092.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 333.92 | 6.12 | 327.79 | 286.44 | 570.49 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 141.53 | 0.00 | 141.53 | 1.40 | 56.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 520.06 | 27.66 | 492.40 | 752.55 | 1200.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 162.25 | 0.00 | 162.25 | 0.82 | 1222.33 | 0.00 | 0.00 | 0.00 |
February | 222.04 | 0.00 | 222.04 | 6.80 | 1234.27 | 0.00 | 0.00 | 0.00 |
March | 307.98 | 0.01 | 307.98 | 70.45 | 820.30 | 0.00 | 0.00 | 0.00 |
April | 370.63 | 1.53 | 369.11 | 195.30 | 554.39 | 0.00 | 0.00 | 0.00 |
May | 492.96 | 18.04 | 474.92 | 436.59 | 299.00 | 0.00 | 0.00 | 0.00 |
June | 520.06 | 27.66 | 492.40 | 646.59 | 141.39 | 0.00 | 0.00 | 0.00 |
July | 504.77 | 19.70 | 485.07 | 744.34 | 61.04 | 0.00 | 0.00 | 0.00 |
August | 446.39 | 5.93 | 440.46 | 651.74 | 92.10 | 0.00 | 0.00 | 0.00 |
September | 336.12 | 0.20 | 335.92 | 356.63 | 232.55 | 0.00 | 0.00 | 0.00 |
October | 290.65 | 0.00 | 290.65 | 190.44 | 479.24 | 0.00 | 0.00 | 0.00 |
November | 203.86 | 0.00 | 203.86 | 34.33 | 841.80 | 0.00 | 0.00 | 0.00 |
December | 141.53 | 0.00 | 141.53 | 1.03 | 1125.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 333.92 | 6.12 | 327.79 | 279.82 | 588.39 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 141.53 | 0.00 | 141.53 | 0.82 | 61.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 520.06 | 27.66 | 492.40 | 744.34 | 1234.27 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.18 | 0.00 | 23.18 | 1.63 | 150.28 | 0.00 | 0.00 | 0.00 |
February | 31.72 | 0.00 | 31.72 | 3.24 | 152.86 | 0.00 | 0.00 | 0.00 |
March | 44.00 | 0.00 | 44.00 | 17.85 | 99.20 | 0.00 | 0.00 | 0.00 |
April | 52.95 | 0.22 | 52.73 | 43.25 | 67.47 | 0.00 | 0.00 | 0.00 |
May | 70.43 | 2.58 | 67.85 | 86.94 | 38.16 | 0.00 | 0.00 | 0.00 |
June | 74.30 | 3.95 | 70.35 | 120.83 | 18.20 | 0.00 | 0.00 | 0.00 |
July | 72.11 | 2.81 | 69.30 | 137.42 | 8.09 | 0.00 | 0.00 | 0.00 |
August | 63.77 | 0.85 | 62.92 | 122.26 | 11.70 | 0.00 | 0.00 | 0.00 |
September | 48.02 | 0.03 | 47.99 | 74.18 | 26.67 | 0.00 | 0.00 | 0.00 |
October | 41.52 | 0.00 | 41.52 | 42.43 | 55.77 | 0.00 | 0.00 | 0.00 |
November | 29.12 | 0.00 | 29.12 | 10.74 | 100.03 | 0.00 | 0.00 | 0.00 |
December | 20.22 | 0.00 | 20.22 | 1.19 | 135.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47.70 | 0.87 | 46.83 | 55.51 | 71.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.22 | 0.00 | 20.22 | 1.19 | 8.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.30 | 3.95 | 70.35 | 137.42 | 152.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 180.34 | 72.05 | 108.29 | 110.38 | 525.57 | 0.00 | 0.00 | 0.00 |
February | 279.99 | 130.38 | 149.60 | 196.98 | 513.51 | 0.00 | 0.00 | 0.00 |
March | 359.55 | 152.80 | 206.74 | 331.92 | 354.67 | 0.00 | 0.00 | 0.00 |
April | 430.41 | 188.91 | 241.50 | 485.89 | 243.36 | 0.00 | 0.00 | 0.00 |
May | 519.63 | 207.08 | 312.55 | 688.52 | 143.36 | 0.00 | 0.00 | 0.00 |
June | 482.51 | 174.77 | 307.74 | 743.11 | 68.37 | 0.00 | 0.00 | 0.00 |
July | 483.98 | 174.24 | 309.74 | 821.58 | 30.46 | 0.00 | 0.00 | 0.00 |
August | 545.99 | 246.33 | 299.66 | 899.91 | 43.77 | 0.00 | 0.00 | 0.00 |
September | 408.42 | 183.99 | 224.43 | 607.28 | 97.82 | 0.00 | 0.00 | 0.00 |
October | 368.98 | 167.02 | 201.96 | 466.96 | 202.17 | 0.00 | 0.00 | 0.00 |
November | 228.53 | 87.82 | 140.71 | 198.52 | 349.76 | 0.00 | 0.00 | 0.00 |
December | 178.67 | 84.30 | 94.36 | 123.30 | 469.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 372.84 | 155.98 | 216.86 | 474.74 | 252.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 178.67 | 72.05 | 94.36 | 110.38 | 30.46 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 545.99 | 246.33 | 312.55 | 899.91 | 525.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 120.49 | 79.06 | 41.42 | 121.58 | 132.69 | 0.00 | 0.00 | 0.00 |
February | 159.45 | 105.97 | 53.48 | 164.52 | 129.98 | 0.00 | 0.00 | 0.00 |
March | 141.27 | 77.77 | 63.50 | 157.20 | 94.15 | 0.00 | 0.00 | 0.00 |
April | 112.45 | 45.49 | 66.96 | 136.20 | 67.62 | 0.00 | 0.00 | 0.00 |
May | 96.58 | 19.77 | 76.81 | 132.85 | 39.90 | 0.00 | 0.00 | 0.00 |
June | 91.20 | 14.05 | 77.14 | 151.10 | 18.99 | 0.00 | 0.00 | 0.00 |
July | 94.89 | 16.02 | 78.87 | 176.41 | 8.26 | 0.00 | 0.00 | 0.00 |
August | 127.10 | 46.88 | 80.21 | 225.09 | 11.81 | 0.00 | 0.00 | 0.00 |
September | 134.12 | 67.34 | 66.78 | 205.19 | 26.44 | 0.00 | 0.00 | 0.00 |
October | 189.53 | 118.85 | 70.68 | 254.88 | 54.27 | 0.00 | 0.00 | 0.00 |
November | 131.24 | 78.73 | 52.51 | 147.41 | 90.98 | 0.00 | 0.00 | 0.00 |
December | 130.17 | 92.45 | 37.72 | 138.12 | 118.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 127.22 | 63.32 | 63.90 | 167.65 | 65.74 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 91.20 | 14.05 | 37.72 | 121.58 | 8.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 189.53 | 118.85 | 80.21 | 254.88 | 132.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 29.36 | 0.00 | 29.36 | 0.56 | 196.14 | 0.00 | 0.00 | 0.00 |
February | 40.17 | 0.00 | 40.17 | 2.22 | 199.74 | 0.00 | 0.00 | 0.00 |
March | 55.72 | 0.00 | 55.72 | 16.77 | 126.80 | 0.00 | 0.00 | 0.00 |
April | 67.06 | 0.28 | 66.78 | 42.02 | 84.13 | 0.00 | 0.00 | 0.00 |
May | 89.19 | 3.26 | 85.93 | 87.53 | 46.28 | 0.00 | 0.00 | 0.00 |
June | 94.09 | 5.00 | 89.09 | 121.03 | 22.59 | 0.00 | 0.00 | 0.00 |
July | 91.33 | 3.56 | 87.76 | 136.22 | 9.90 | 0.00 | 0.00 | 0.00 |
August | 80.76 | 1.07 | 79.69 | 118.82 | 15.58 | 0.00 | 0.00 | 0.00 |
September | 60.81 | 0.04 | 60.78 | 67.82 | 36.55 | 0.00 | 0.00 | 0.00 |
October | 52.59 | 0.00 | 52.59 | 38.45 | 75.83 | 0.00 | 0.00 | 0.00 |
November | 36.88 | 0.00 | 36.88 | 8.87 | 129.46 | 0.00 | 0.00 | 0.00 |
December | 25.61 | 0.00 | 25.61 | 0.47 | 178.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 60.41 | 1.11 | 59.31 | 53.75 | 92.84 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.61 | 0.00 | 25.61 | 0.47 | 9.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 94.09 | 5.00 | 89.09 | 136.22 | 199.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.26 | 0.00 | 26.26 | 0.50 | 175.48 | 0.00 | 0.00 | 0.00 |
February | 35.94 | 0.00 | 35.94 | 1.99 | 178.71 | 0.00 | 0.00 | 0.00 |
March | 49.86 | 0.00 | 49.85 | 15.01 | 113.45 | 0.00 | 0.00 | 0.00 |
April | 60.00 | 0.25 | 59.75 | 37.59 | 75.27 | 0.00 | 0.00 | 0.00 |
May | 79.80 | 2.92 | 76.88 | 78.31 | 41.41 | 0.00 | 0.00 | 0.00 |
June | 84.18 | 4.48 | 79.71 | 108.29 | 20.21 | 0.00 | 0.00 | 0.00 |
July | 81.71 | 3.19 | 78.52 | 121.88 | 8.85 | 0.00 | 0.00 | 0.00 |
August | 72.26 | 0.96 | 71.30 | 106.31 | 13.94 | 0.00 | 0.00 | 0.00 |
September | 54.41 | 0.03 | 54.38 | 60.68 | 32.70 | 0.00 | 0.00 | 0.00 |
October | 47.05 | 0.00 | 47.05 | 34.40 | 67.84 | 0.00 | 0.00 | 0.00 |
November | 33.00 | 0.00 | 33.00 | 7.94 | 115.82 | 0.00 | 0.00 | 0.00 |
December | 22.91 | 0.00 | 22.91 | 0.42 | 159.43 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.05 | 0.99 | 53.06 | 48.09 | 83.06 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.91 | 0.00 | 22.91 | 0.42 | 8.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 84.18 | 4.48 | 79.71 | 121.88 | 178.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 449.81 | 295.17 | 154.64 | 433.19 | 502.37 | 0.00 | 0.00 | 0.00 |
February | 595.27 | 395.63 | 199.64 | 588.01 | 493.30 | 0.00 | 0.00 | 0.00 |
March | 527.41 | 290.33 | 237.08 | 555.27 | 350.77 | 0.00 | 0.00 | 0.00 |
April | 419.81 | 169.84 | 249.96 | 465.30 | 248.92 | 0.00 | 0.00 | 0.00 |
May | 360.56 | 73.82 | 286.74 | 430.25 | 146.75 | 0.00 | 0.00 | 0.00 |
June | 340.46 | 52.46 | 288.00 | 471.87 | 70.94 | 0.00 | 0.00 | 0.00 |
July | 354.25 | 59.79 | 294.46 | 547.77 | 29.90 | 0.00 | 0.00 | 0.00 |
August | 474.49 | 175.03 | 299.45 | 731.32 | 47.41 | 0.00 | 0.00 | 0.00 |
September | 500.71 | 251.40 | 249.31 | 683.30 | 106.73 | 0.00 | 0.00 | 0.00 |
October | 707.59 | 443.72 | 263.87 | 891.82 | 211.83 | 0.00 | 0.00 | 0.00 |
November | 489.96 | 293.91 | 196.05 | 520.57 | 342.19 | 0.00 | 0.00 | 0.00 |
December | 485.97 | 345.16 | 140.81 | 493.62 | 447.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 474.95 | 236.38 | 238.57 | 567.88 | 248.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 340.46 | 52.46 | 140.81 | 430.25 | 29.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 707.59 | 443.72 | 299.45 | 891.82 | 502.37 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163216E+10 | 0.107105E+10 | 0.561115E+09 | 0.159900E+10 | 0.167283E+10 |
February | 0.195097E+10 | 0.129667E+10 | 0.654301E+09 | 0.194999E+10 | 0.149724E+10 |
March | 0.191376E+10 | 0.105350E+10 | 0.860258E+09 | 0.203597E+10 | 0.117880E+10 |
April | 0.147416E+10 | 0.596411E+09 | 0.877753E+09 | 0.165777E+10 | 0.804192E+09 |
May | 0.130833E+10 | 0.267862E+09 | 0.104047E+10 | 0.160325E+10 | 0.474979E+09 |
June | 0.119554E+10 | 0.184207E+09 | 0.101133E+10 | 0.168734E+10 | 0.219483E+09 |
July | 0.128543E+10 | 0.216954E+09 | 0.106847E+10 | 0.199965E+10 | 95747192.21 |
August | 0.172171E+10 | 0.635122E+09 | 0.108658E+10 | 0.264186E+10 | 0.170384E+09 |
September | 0.175826E+10 | 0.882798E+09 | 0.875461E+09 | 0.240196E+10 | 0.351658E+09 |
October | 0.256754E+10 | 0.161007E+10 | 0.957474E+09 | 0.322278E+10 | 0.748256E+09 |
November | 0.172050E+10 | 0.103208E+10 | 0.688421E+09 | 0.183869E+10 | 0.112182E+10 |
December | 0.176337E+10 | 0.125244E+10 | 0.510933E+09 | 0.180431E+10 | 0.150438E+10 |
Annual Sum or Average | 0.202917E+11 | 0.100992E+11 | 0.101926E+11 | 0.244426E+11 | 0.983977E+10 |
Minimum of Months | 0.119554E+10 | 0.184207E+09 | 0.510933E+09 | 0.159900E+10 | 95747192.21 |
Maximum of Months | 0.256754E+10 | 0.161007E+10 | 0.108658E+10 | 0.322278E+10 | 0.167283E+10 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.459606E+10 | 0.301600E+10 | 0.158006E+10 | 0.444565E+10 | 0.486887E+10 |
February | 0.549380E+10 | 0.365134E+10 | 0.184247E+10 | 0.541934E+10 | 0.437077E+10 |
March | 0.538903E+10 | 0.296660E+10 | 0.242243E+10 | 0.565500E+10 | 0.353511E+10 |
April | 0.415115E+10 | 0.167946E+10 | 0.247169E+10 | 0.458481E+10 | 0.246230E+10 |
May | 0.368418E+10 | 0.754282E+09 | 0.292990E+10 | 0.439660E+10 | 0.151679E+10 |
June | 0.336655E+10 | 0.518716E+09 | 0.284784E+10 | 0.467160E+10 | 0.720470E+09 |
July | 0.361968E+10 | 0.610929E+09 | 0.300875E+10 | 0.556732E+10 | 0.329009E+09 |
August | 0.484821E+10 | 0.178846E+10 | 0.305975E+10 | 0.738558E+10 | 0.531604E+09 |
September | 0.495114E+10 | 0.248590E+10 | 0.246524E+10 | 0.668734E+10 | 0.112998E+10 |
October | 0.723002E+10 | 0.453384E+10 | 0.269618E+10 | 0.898365E+10 | 0.230650E+10 |
November | 0.484482E+10 | 0.290627E+10 | 0.193855E+10 | 0.509282E+10 | 0.336598E+10 |
December | 0.496554E+10 | 0.352678E+10 | 0.143875E+10 | 0.501514E+10 | 0.442699E+10 |
Annual Sum or Average | 0.571402E+11 | 0.284386E+11 | 0.287016E+11 | 0.679048E+11 | 0.295644E+11 |
Minimum of Months | 0.336655E+10 | 0.518716E+09 | 0.143875E+10 | 0.439660E+10 | 0.329009E+09 |
Maximum of Months | 0.723002E+10 | 0.453384E+10 | 0.305975E+10 | 0.898365E+10 | 0.486887E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.597055E+10 | 0.391796E+10 | 0.205259E+10 | 0.586544E+10 | 0.663093E+10 |
February | 0.713676E+10 | 0.474329E+10 | 0.239347E+10 | 0.717219E+10 | 0.590589E+10 |
March | 0.700065E+10 | 0.385378E+10 | 0.314688E+10 | 0.749064E+10 | 0.478705E+10 |
April | 0.539258E+10 | 0.218171E+10 | 0.321087E+10 | 0.607013E+10 | 0.335753E+10 |
May | 0.478596E+10 | 0.979855E+09 | 0.380610E+10 | 0.581625E+10 | 0.207246E+10 |
June | 0.437334E+10 | 0.673841E+09 | 0.369950E+10 | 0.619824E+10 | 0.968160E+09 |
July | 0.470217E+10 | 0.793632E+09 | 0.390854E+10 | 0.741371E+10 | 0.432595E+09 |
August | 0.629810E+10 | 0.232331E+10 | 0.397479E+10 | 0.983244E+10 | 0.685046E+09 |
September | 0.643181E+10 | 0.322933E+10 | 0.320249E+10 | 0.886179E+10 | 0.150258E+10 |
October | 0.939221E+10 | 0.588972E+10 | 0.350250E+10 | 0.119055E+11 | 0.305548E+10 |
November | 0.629370E+10 | 0.377541E+10 | 0.251828E+10 | 0.671925E+10 | 0.458863E+10 |
December | 0.645052E+10 | 0.458149E+10 | 0.186902E+10 | 0.661722E+10 | 0.603085E+10 |
Annual Sum or Average | 0.742284E+11 | 0.369433E+11 | 0.372850E+11 | 0.899628E+11 | 0.400172E+11 |
Minimum of Months | 0.437334E+10 | 0.673841E+09 | 0.186902E+10 | 0.581625E+10 | 0.432595E+09 |
Maximum of Months | 0.939221E+10 | 0.588972E+10 | 0.397479E+10 | 0.119055E+11 | 0.663093E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.322707E+09 | 0.211765E+09 | 0.110943E+09 | 0.317201E+09 | 0.336299E+09 |
February | 0.385741E+09 | 0.256374E+09 | 0.129367E+09 | 0.386722E+09 | 0.301662E+09 |
March | 0.378385E+09 | 0.208296E+09 | 0.170089E+09 | 0.401540E+09 | 0.238488E+09 |
April | 0.291469E+09 | 0.117921E+09 | 0.173548E+09 | 0.326135E+09 | 0.161191E+09 |
May | 0.258682E+09 | 52960934.60 | 0.205721E+09 | 0.313906E+09 | 92821012.31 |
June | 0.236380E+09 | 36420939.70 | 0.199959E+09 | 0.339331E+09 | 34351910.30 |
July | 0.254153E+09 | 42895608.52 | 0.211258E+09 | 0.413318E+09 | 8730605.12 |
August | 0.340413E+09 | 0.125575E+09 | 0.214838E+09 | 0.543181E+09 | 20894051.28 |
September | 0.347639E+09 | 0.174544E+09 | 0.173095E+09 | 0.483368E+09 | 58119099.95 |
October | 0.507648E+09 | 0.318338E+09 | 0.189310E+09 | 0.643386E+09 | 0.138832E+09 |
November | 0.340174E+09 | 0.204060E+09 | 0.136113E+09 | 0.366078E+09 | 0.222278E+09 |
December | 0.348649E+09 | 0.247629E+09 | 0.101021E+09 | 0.359435E+09 | 0.300144E+09 |
Annual Sum or Average | 0.401204E+10 | 0.199678E+10 | 0.201526E+10 | 0.489360E+10 | 0.191381E+10 |
Minimum of Months | 0.236380E+09 | 36420939.70 | 0.101021E+09 | 0.313906E+09 | 8730605.12 |
Maximum of Months | 0.507648E+09 | 0.318338E+09 | 0.214838E+09 | 0.643386E+09 | 0.336299E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.239844E+09 | 98462657.35 | 0.141382E+09 | 0.140533E+09 | 0.680781E+09 |
February | 0.318223E+09 | 0.139658E+09 | 0.178565E+09 | 0.209831E+09 | 0.622127E+09 |
March | 0.523325E+09 | 0.242520E+09 | 0.280804E+09 | 0.463249E+09 | 0.444864E+09 |
April | 0.550044E+09 | 0.235058E+09 | 0.314986E+09 | 0.570195E+09 | 0.294234E+09 |
May | 0.663989E+09 | 0.252408E+09 | 0.411582E+09 | 0.799436E+09 | 0.167884E+09 |
June | 0.702057E+09 | 0.283331E+09 | 0.418726E+09 | 0.968146E+09 | 62689811.57 |
July | 0.678728E+09 | 0.255057E+09 | 0.423671E+09 | 0.102687E+10 | 16123469.57 |
August | 0.750935E+09 | 0.347199E+09 | 0.403736E+09 | 0.112098E+10 | 38757961.91 |
September | 0.517041E+09 | 0.225725E+09 | 0.291316E+09 | 0.680578E+09 | 0.108816E+09 |
October | 0.530121E+09 | 0.258241E+09 | 0.271880E+09 | 0.605285E+09 | 0.266997E+09 |
November | 0.241596E+09 | 70580626.93 | 0.171015E+09 | 0.160513E+09 | 0.443164E+09 |
December | 0.220511E+09 | 95188244.85 | 0.125323E+09 | 0.132314E+09 | 0.617085E+09 |
Annual Sum or Average | 0.593641E+10 | 0.250343E+10 | 0.343299E+10 | 0.687793E+10 | 0.376352E+10 |
Minimum of Months | 0.220511E+09 | 70580626.93 | 0.125323E+09 | 0.132314E+09 | 16123469.57 |
Maximum of Months | 0.750935E+09 | 0.347199E+09 | 0.423671E+09 | 0.112098E+10 | 0.680781E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62085473.63 | 0.00 | 62085473.63 | 3188464.18 | 0.378525E+09 |
February | 76739382.29 | 0.00 | 76739382.29 | 6606903.57 | 0.350073E+09 |
March | 0.117848E+09 | 2454.62 | 0.117846E+09 | 40930453.42 | 0.250454E+09 |
April | 0.137245E+09 | 565514.21 | 0.136680E+09 | 89038400.88 | 0.160461E+09 |
May | 0.188627E+09 | 6903211.21 | 0.181724E+09 | 0.186175E+09 | 89966859.27 |
June | 0.192578E+09 | 10242901.02 | 0.182335E+09 | 0.250163E+09 | 39320217.84 |
July | 0.193148E+09 | 7538040.63 | 0.185610E+09 | 0.303725E+09 | 11634935.51 |
August | 0.170807E+09 | 2269513.75 | 0.168538E+09 | 0.267266E+09 | 23212823.10 |
September | 0.124465E+09 | 72357.39 | 0.124392E+09 | 0.144283E+09 | 64659525.49 |
October | 0.111214E+09 | 0.00 | 0.111214E+09 | 86433042.51 | 0.147810E+09 |
November | 75489568.31 | 0.00 | 75489568.31 | 22434018.77 | 0.241317E+09 |
December | 54155055.53 | 0.00 | 54155055.53 | 2205494.88 | 0.341920E+09 |
Annual Sum or Average | 0.150440E+10 | 27593992.83 | 0.147681E+10 | 0.140245E+10 | 0.209936E+10 |
Minimum of Months | 54155055.53 | 0.00 | 54155055.53 | 2205494.88 | 11634935.51 |
Maximum of Months | 0.193148E+09 | 10242901.02 | 0.185610E+09 | 0.303725E+09 | 0.378525E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.239844E+09 | 98462657.35 | 0.141382E+09 | 0.148038E+09 | 0.673487E+09 |
February | 0.318223E+09 | 0.139658E+09 | 0.178565E+09 | 0.219829E+09 | 0.612186E+09 |
March | 0.523325E+09 | 0.242520E+09 | 0.280804E+09 | 0.474950E+09 | 0.438833E+09 |
April | 0.550044E+09 | 0.235058E+09 | 0.314986E+09 | 0.574647E+09 | 0.293497E+09 |
May | 0.663989E+09 | 0.252408E+09 | 0.411582E+09 | 0.792386E+09 | 0.174091E+09 |
June | 0.702057E+09 | 0.283331E+09 | 0.418726E+09 | 0.950980E+09 | 75282177.96 |
July | 0.678728E+09 | 0.255057E+09 | 0.423671E+09 | 0.102018E+10 | 21766318.22 |
August | 0.750935E+09 | 0.347199E+09 | 0.403736E+09 | 0.112011E+10 | 44088127.09 |
September | 0.517041E+09 | 0.225725E+09 | 0.291316E+09 | 0.677627E+09 | 0.118595E+09 |
October | 0.530121E+09 | 0.258241E+09 | 0.271880E+09 | 0.613152E+09 | 0.268225E+09 |
November | 0.241596E+09 | 70580626.93 | 0.171015E+09 | 0.169934E+09 | 0.435688E+09 |
December | 0.220511E+09 | 95188244.85 | 0.125323E+09 | 0.141034E+09 | 0.608026E+09 |
Annual Sum or Average | 0.593641E+10 | 0.250343E+10 | 0.343299E+10 | 0.690287E+10 | 0.376376E+10 |
Minimum of Months | 0.220511E+09 | 70580626.93 | 0.125323E+09 | 0.141034E+09 | 21766318.22 |
Maximum of Months | 0.750935E+09 | 0.347199E+09 | 0.423671E+09 | 0.112011E+10 | 0.673487E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.258114E+09 | 0.169378E+09 | 88736490.59 | 0.248736E+09 | 0.279232E+09 |
February | 0.308532E+09 | 0.205058E+09 | 0.103473E+09 | 0.288917E+09 | 0.294115E+09 |
March | 0.302648E+09 | 0.166604E+09 | 0.136044E+09 | 0.297308E+09 | 0.256164E+09 |
April | 0.233129E+09 | 94317873.29 | 0.138811E+09 | 0.233908E+09 | 0.187937E+09 |
May | 0.206904E+09 | 42360323.35 | 0.164544E+09 | 0.215948E+09 | 0.124498E+09 |
June | 0.189067E+09 | 29130958.40 | 0.159936E+09 | 0.233980E+09 | 65806204.26 |
July | 0.203282E+09 | 34309663.55 | 0.168973E+09 | 0.286107E+09 | 38819954.29 |
August | 0.272276E+09 | 0.100440E+09 | 0.171837E+09 | 0.392247E+09 | 50873819.56 |
September | 0.278056E+09 | 0.139608E+09 | 0.138449E+09 | 0.354148E+09 | 94983582.66 |
October | 0.406038E+09 | 0.254620E+09 | 0.151418E+09 | 0.482483E+09 | 0.170685E+09 |
November | 0.272085E+09 | 0.163216E+09 | 0.108869E+09 | 0.266398E+09 | 0.244065E+09 |
December | 0.278864E+09 | 0.198063E+09 | 80800618.01 | 0.268049E+09 | 0.297191E+09 |
Annual Sum or Average | 0.320900E+10 | 0.159710E+10 | 0.161189E+10 | 0.356823E+10 | 0.210437E+10 |
Minimum of Months | 0.189067E+09 | 29130958.40 | 80800618.01 | 0.215948E+09 | 38819954.29 |
Maximum of Months | 0.406038E+09 | 0.254620E+09 | 0.171837E+09 | 0.482483E+09 | 0.297191E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 49674962.73 | 0.00 | 49674962.73 | 1711418.60 | 0.317225E+09 |
February | 61399643.62 | 0.00 | 61399643.62 | 4608644.77 | 0.290580E+09 |
March | 94290864.36 | 1963.96 | 94288900.41 | 32542105.52 | 0.205165E+09 |
April | 0.109811E+09 | 452471.34 | 0.109358E+09 | 73859903.85 | 0.129812E+09 |
May | 0.150921E+09 | 5523301.01 | 0.145398E+09 | 0.156769E+09 | 70158725.58 |
June | 0.154082E+09 | 8195407.02 | 0.145887E+09 | 0.211844E+09 | 27459322.48 |
July | 0.154539E+09 | 6031231.87 | 0.148507E+09 | 0.254776E+09 | 7049234.19 |
August | 0.136664E+09 | 1815851.67 | 0.134848E+09 | 0.226615E+09 | 15407962.82 |
September | 99584946.32 | 57893.59 | 99527052.73 | 0.122424E+09 | 47922714.76 |
October | 88983113.67 | 0.00 | 88983113.67 | 73413932.84 | 0.114999E+09 |
November | 60399659.90 | 0.00 | 60399659.90 | 17017093.06 | 0.202187E+09 |
December | 43329787.27 | 0.00 | 43329787.27 | 1295952.97 | 0.287436E+09 |
Annual Sum or Average | 0.120368E+10 | 22078120.45 | 0.118160E+10 | 0.117688E+10 | 0.171540E+10 |
Minimum of Months | 43329787.27 | 0.00 | 43329787.27 | 1295952.97 | 7049234.19 |
Maximum of Months | 0.154539E+09 | 8195407.02 | 0.148507E+09 | 0.254776E+09 | 0.317225E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.241522E+09 | 96495417.54 | 0.145026E+09 | 0.136852E+09 | 0.669416E+09 |
February | 0.338694E+09 | 0.157722E+09 | 0.180972E+09 | 0.223377E+09 | 0.600482E+09 |
March | 0.481538E+09 | 0.204650E+09 | 0.276888E+09 | 0.411662E+09 | 0.447040E+09 |
April | 0.557847E+09 | 0.244845E+09 | 0.313002E+09 | 0.573940E+09 | 0.285516E+09 |
May | 0.695935E+09 | 0.277340E+09 | 0.418595E+09 | 0.840248E+09 | 0.162673E+09 |
June | 0.625383E+09 | 0.226521E+09 | 0.398862E+09 | 0.863624E+09 | 59788791.62 |
July | 0.648197E+09 | 0.233361E+09 | 0.414837E+09 | 0.987791E+09 | 15264223.13 |
August | 0.731240E+09 | 0.329905E+09 | 0.401335E+09 | 0.109296E+10 | 36341967.03 |
September | 0.529355E+09 | 0.238470E+09 | 0.290885E+09 | 0.694740E+09 | 0.104346E+09 |
October | 0.494167E+09 | 0.223686E+09 | 0.270480E+09 | 0.554694E+09 | 0.259682E+09 |
November | 0.296195E+09 | 0.113821E+09 | 0.182374E+09 | 0.229867E+09 | 0.431668E+09 |
December | 0.239288E+09 | 0.112907E+09 | 0.126381E+09 | 0.152461E+09 | 0.603098E+09 |
Annual Sum or Average | 0.587936E+10 | 0.245972E+10 | 0.341964E+10 | 0.676222E+10 | 0.367532E+10 |
Minimum of Months | 0.239288E+09 | 96495417.54 | 0.126381E+09 | 0.136852E+09 | 15264223.13 |
Maximum of Months | 0.731240E+09 | 0.329905E+09 | 0.418595E+09 | 0.109296E+10 | 0.669416E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.322707E+09 | 0.211765E+09 | 0.110943E+09 | 0.316402E+09 | 0.335803E+09 |
February | 0.385741E+09 | 0.256374E+09 | 0.129367E+09 | 0.384949E+09 | 0.300945E+09 |
March | 0.378385E+09 | 0.208296E+09 | 0.170089E+09 | 0.399253E+09 | 0.236416E+09 |
April | 0.291469E+09 | 0.117921E+09 | 0.173548E+09 | 0.323627E+09 | 0.160073E+09 |
May | 0.258682E+09 | 52960934.60 | 0.205721E+09 | 0.311504E+09 | 91642698.51 |
June | 0.236380E+09 | 36420939.70 | 0.199959E+09 | 0.339359E+09 | 33185243.02 |
July | 0.254153E+09 | 42895608.52 | 0.211258E+09 | 0.413151E+09 | 8256251.07 |
August | 0.340413E+09 | 0.125575E+09 | 0.214838E+09 | 0.542558E+09 | 20158042.75 |
September | 0.347639E+09 | 0.174544E+09 | 0.173095E+09 | 0.482121E+09 | 57356811.68 |
October | 0.507648E+09 | 0.318338E+09 | 0.189310E+09 | 0.642063E+09 | 0.137437E+09 |
November | 0.340174E+09 | 0.204060E+09 | 0.136113E+09 | 0.364132E+09 | 0.222531E+09 |
December | 0.348649E+09 | 0.247629E+09 | 0.101021E+09 | 0.358357E+09 | 0.299772E+09 |
Annual Sum or Average | 0.401204E+10 | 0.199678E+10 | 0.201526E+10 | 0.487748E+10 | 0.190358E+10 |
Minimum of Months | 0.236380E+09 | 36420939.70 | 0.101021E+09 | 0.311504E+09 | 8256251.07 |
Maximum of Months | 0.507648E+09 | 0.318338E+09 | 0.214838E+09 | 0.642063E+09 | 0.335803E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62085473.63 | 0.00 | 62085473.63 | 2775651.36 | 0.378409E+09 |
February | 76739382.29 | 0.00 | 76739382.29 | 6114973.67 | 0.350123E+09 |
March | 0.117848E+09 | 2454.62 | 0.117846E+09 | 39047356.09 | 0.248428E+09 |
April | 0.137245E+09 | 565514.21 | 0.136680E+09 | 86719828.11 | 0.159217E+09 |
May | 0.188627E+09 | 6903211.21 | 0.181724E+09 | 0.184221E+09 | 88135012.11 |
June | 0.192578E+09 | 10242901.02 | 0.182335E+09 | 0.250991E+09 | 36757076.83 |
July | 0.193148E+09 | 7538040.63 | 0.185610E+09 | 0.302461E+09 | 10928587.05 |
August | 0.170807E+09 | 2269513.75 | 0.168538E+09 | 0.264871E+09 | 22208671.90 |
September | 0.124465E+09 | 72357.39 | 0.124392E+09 | 0.142140E+09 | 62717631.52 |
October | 0.111214E+09 | 0.00 | 0.111214E+09 | 84357224.62 | 0.144469E+09 |
November | 75489568.31 | 0.00 | 75489568.31 | 21102746.83 | 0.241929E+09 |
December | 54155055.53 | 0.00 | 54155055.53 | 1879338.19 | 0.341867E+09 |
Annual Sum or Average | 0.150440E+10 | 27593992.83 | 0.147681E+10 | 0.138668E+10 | 0.208519E+10 |
Minimum of Months | 54155055.53 | 0.00 | 54155055.53 | 1879338.19 | 10928587.05 |
Maximum of Months | 0.193148E+09 | 10242901.02 | 0.185610E+09 | 0.302461E+09 | 0.378409E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.241522E+09 | 96495417.54 | 0.145026E+09 | 0.141158E+09 | 0.658744E+09 |
February | 0.338694E+09 | 0.157722E+09 | 0.180972E+09 | 0.229777E+09 | 0.586162E+09 |
March | 0.481538E+09 | 0.204650E+09 | 0.276888E+09 | 0.422085E+09 | 0.438853E+09 |
April | 0.557847E+09 | 0.244845E+09 | 0.313002E+09 | 0.578701E+09 | 0.283960E+09 |
May | 0.695935E+09 | 0.277340E+09 | 0.418595E+09 | 0.835037E+09 | 0.168157E+09 |
June | 0.625383E+09 | 0.226521E+09 | 0.398862E+09 | 0.849135E+09 | 70519514.61 |
July | 0.648197E+09 | 0.233361E+09 | 0.414837E+09 | 0.978987E+09 | 20625524.09 |
August | 0.731240E+09 | 0.329905E+09 | 0.401335E+09 | 0.108836E+10 | 41114473.11 |
September | 0.529355E+09 | 0.238470E+09 | 0.290885E+09 | 0.690935E+09 | 0.112515E+09 |
October | 0.494167E+09 | 0.223686E+09 | 0.270480E+09 | 0.563042E+09 | 0.258415E+09 |
November | 0.296195E+09 | 0.113821E+09 | 0.182374E+09 | 0.237769E+09 | 0.422508E+09 |
December | 0.239288E+09 | 0.112907E+09 | 0.126381E+09 | 0.156927E+09 | 0.589219E+09 |
Annual Sum or Average | 0.587936E+10 | 0.245972E+10 | 0.341964E+10 | 0.677192E+10 | 0.365079E+10 |
Minimum of Months | 0.239288E+09 | 96495417.54 | 0.126381E+09 | 0.141158E+09 | 20625524.09 |
Maximum of Months | 0.731240E+09 | 0.329905E+09 | 0.418595E+09 | 0.108836E+10 | 0.658744E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 78627334.97 | 0.00 | 78627334.97 | 2141099.33 | 0.515116E+09 |
February | 97185585.68 | 0.00 | 97185585.68 | 6524060.71 | 0.473254E+09 |
March | 0.149247E+09 | 3108.62 | 0.149244E+09 | 50307667.91 | 0.331151E+09 |
April | 0.173812E+09 | 716188.06 | 0.173096E+09 | 0.116986E+09 | 0.212446E+09 |
May | 0.238884E+09 | 8742481.42 | 0.230142E+09 | 0.247388E+09 | 0.118956E+09 |
June | 0.243887E+09 | 12971987.85 | 0.230915E+09 | 0.327783E+09 | 53668615.14 |
July | 0.244609E+09 | 9546452.84 | 0.235063E+09 | 0.382338E+09 | 20849383.76 |
August | 0.216317E+09 | 2874195.96 | 0.213443E+09 | 0.333231E+09 | 37601085.88 |
September | 0.157627E+09 | 91636.07 | 0.157535E+09 | 0.185070E+09 | 90418007.30 |
October | 0.140846E+09 | 0.00 | 0.140846E+09 | 0.109108E+09 | 0.201926E+09 |
November | 95602775.14 | 0.00 | 95602775.14 | 25653301.89 | 0.328697E+09 |
December | 68583960.84 | 0.00 | 68583960.84 | 1685671.53 | 0.466964E+09 |
Annual Sum or Average | 0.190523E+10 | 34946050.83 | 0.187028E+10 | 0.178822E+10 | 0.285105E+10 |
Minimum of Months | 68583960.84 | 0.00 | 68583960.84 | 1685671.53 | 20849383.76 |
Maximum of Months | 0.244609E+09 | 12971987.85 | 0.235063E+09 | 0.382338E+09 | 0.515116E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 28985291.37 | 0.00 | 28985291.37 | 789297.87 | 0.189893E+09 |
February | 35826631.02 | 0.00 | 35826631.02 | 2405038.92 | 0.174461E+09 |
March | 55018625.63 | 1145.97 | 55017479.66 | 18545489.47 | 0.122076E+09 |
April | 64074374.08 | 264016.58 | 63810357.50 | 43125819.27 | 78316483.01 |
May | 88062541.06 | 3222840.65 | 84839700.41 | 91197332.32 | 43851939.38 |
June | 89906978.19 | 4782011.85 | 85124966.34 | 0.120834E+09 | 19784473.78 |
July | 90173173.31 | 3519217.80 | 86653955.51 | 0.140946E+09 | 7685946.16 |
August | 79743320.60 | 1059547.64 | 78683772.95 | 0.122843E+09 | 13861317.19 |
September | 58107717.19 | 33780.85 | 58073936.34 | 68224572.75 | 33331821.41 |
October | 51921558.38 | 0.00 | 51921558.38 | 40221764.34 | 74438150.45 |
November | 35243141.51 | 0.00 | 35243141.51 | 9456869.30 | 0.121171E+09 |
December | 25282887.80 | 0.00 | 25282887.80 | 621408.33 | 0.172142E+09 |
Annual Sum or Average | 0.702346E+09 | 12882561.34 | 0.689464E+09 | 0.659210E+09 | 0.105101E+10 |
Minimum of Months | 25282887.80 | 0.00 | 25282887.80 | 621408.33 | 7685946.16 |
Maximum of Months | 90173173.31 | 4782011.85 | 86653955.51 | 0.140946E+09 | 0.189893E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.150574E+09 | 98808493.80 | 51765403.86 | 0.147274E+09 | 0.165401E+09 |
February | 0.179985E+09 | 0.119623E+09 | 60362290.71 | 0.180489E+09 | 0.146895E+09 |
March | 0.176553E+09 | 97190004.50 | 79362917.17 | 0.189508E+09 | 0.114653E+09 |
April | 0.135998E+09 | 55021364.60 | 80976996.46 | 0.154721E+09 | 78348583.00 |
May | 0.120700E+09 | 24711358.67 | 95988587.17 | 0.149137E+09 | 46913664.82 |
June | 0.110294E+09 | 16993863.70 | 93300242.89 | 0.158437E+09 | 20949054.65 |
July | 0.118587E+09 | 20014918.08 | 98572006.58 | 0.190296E+09 | 7857648.32 |
August | 0.158835E+09 | 58592560.64 | 0.100243E+09 | 0.251170E+09 | 14262282.13 |
September | 0.162207E+09 | 81441637.01 | 80765468.23 | 0.225722E+09 | 32922317.87 |
October | 0.236867E+09 | 0.148535E+09 | 88331451.67 | 0.302378E+09 | 70450456.39 |
November | 0.158724E+09 | 95213646.52 | 63509953.91 | 0.171196E+09 | 0.108895E+09 |
December | 0.162678E+09 | 0.115543E+09 | 47135925.66 | 0.167624E+09 | 0.147291E+09 |
Annual Sum or Average | 0.187200E+10 | 0.931688E+09 | 0.940314E+09 | 0.228795E+10 | 0.954839E+09 |
Minimum of Months | 0.110294E+09 | 16993863.70 | 47135925.66 | 0.147274E+09 | 7857648.32 |
Maximum of Months | 0.236867E+09 | 0.148535E+09 | 0.100243E+09 | 0.302378E+09 | 0.165401E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.408688E+09 | 0.268186E+09 | 0.140502E+09 | 0.399733E+09 | 0.448931E+09 |
February | 0.488517E+09 | 0.324681E+09 | 0.163836E+09 | 0.489884E+09 | 0.398702E+09 |
March | 0.479201E+09 | 0.263794E+09 | 0.215407E+09 | 0.514363E+09 | 0.311192E+09 |
April | 0.369127E+09 | 0.149339E+09 | 0.219788E+09 | 0.419944E+09 | 0.212654E+09 |
May | 0.327604E+09 | 67071682.02 | 0.260533E+09 | 0.404787E+09 | 0.127333E+09 |
June | 0.299361E+09 | 46124822.10 | 0.253236E+09 | 0.430029E+09 | 56860019.36 |
July | 0.321869E+09 | 54324581.63 | 0.267545E+09 | 0.516501E+09 | 21327264.79 |
August | 0.431112E+09 | 0.159032E+09 | 0.272079E+09 | 0.681726E+09 | 38710750.97 |
September | 0.440263E+09 | 0.221049E+09 | 0.219214E+09 | 0.612656E+09 | 89357904.82 |
October | 0.642904E+09 | 0.403155E+09 | 0.239750E+09 | 0.820717E+09 | 0.191217E+09 |
November | 0.430808E+09 | 0.258429E+09 | 0.172379E+09 | 0.464661E+09 | 0.295564E+09 |
December | 0.441543E+09 | 0.313606E+09 | 0.127937E+09 | 0.454966E+09 | 0.399778E+09 |
Annual Sum or Average | 0.508100E+10 | 0.252879E+10 | 0.255220E+10 | 0.620997E+10 | 0.259163E+10 |
Minimum of Months | 0.299361E+09 | 46124822.10 | 0.127937E+09 | 0.399733E+09 | 21327264.79 |
Maximum of Months | 0.642904E+09 | 0.403155E+09 | 0.272079E+09 | 0.820717E+09 | 0.448931E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.322707E+09 | 0.211765E+09 | 0.110943E+09 | 0.316169E+09 | 0.334414E+09 |
February | 0.385741E+09 | 0.256374E+09 | 0.129367E+09 | 0.385181E+09 | 0.300407E+09 |
March | 0.378385E+09 | 0.208296E+09 | 0.170089E+09 | 0.398753E+09 | 0.237754E+09 |
April | 0.291469E+09 | 0.117921E+09 | 0.173548E+09 | 0.323174E+09 | 0.160386E+09 |
May | 0.258682E+09 | 52960934.60 | 0.205721E+09 | 0.310215E+09 | 92343389.82 |
June | 0.236380E+09 | 36420939.70 | 0.199959E+09 | 0.336165E+09 | 33574942.02 |
July | 0.254153E+09 | 42895608.52 | 0.211258E+09 | 0.410490E+09 | 8100064.38 |
August | 0.340413E+09 | 0.125575E+09 | 0.214838E+09 | 0.540027E+09 | 19868659.40 |
September | 0.347639E+09 | 0.174544E+09 | 0.173095E+09 | 0.480267E+09 | 56795243.34 |
October | 0.507648E+09 | 0.318338E+09 | 0.189310E+09 | 0.639663E+09 | 0.136986E+09 |
November | 0.340174E+09 | 0.204060E+09 | 0.136113E+09 | 0.364944E+09 | 0.220050E+09 |
December | 0.348649E+09 | 0.247629E+09 | 0.101021E+09 | 0.358629E+09 | 0.297876E+09 |
Annual Sum or Average | 0.401204E+10 | 0.199678E+10 | 0.201526E+10 | 0.486368E+10 | 0.189856E+10 |
Minimum of Months | 0.236380E+09 | 36420939.70 | 0.101021E+09 | 0.310215E+09 | 8100064.38 |
Maximum of Months | 0.507648E+09 | 0.318338E+09 | 0.214838E+09 | 0.639663E+09 | 0.334414E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.239844E+09 | 98462657.35 | 0.141382E+09 | 0.140150E+09 | 0.677295E+09 |
February | 0.318223E+09 | 0.139658E+09 | 0.178565E+09 | 0.208133E+09 | 0.620159E+09 |
March | 0.523325E+09 | 0.242520E+09 | 0.280804E+09 | 0.459029E+09 | 0.442679E+09 |
April | 0.550044E+09 | 0.235058E+09 | 0.314986E+09 | 0.564984E+09 | 0.292068E+09 |
May | 0.663989E+09 | 0.252408E+09 | 0.411582E+09 | 0.791972E+09 | 0.166517E+09 |
June | 0.702057E+09 | 0.283331E+09 | 0.418726E+09 | 0.960599E+09 | 61102562.08 |
July | 0.678728E+09 | 0.255057E+09 | 0.423671E+09 | 0.102052E+10 | 14949439.11 |
August | 0.750935E+09 | 0.347199E+09 | 0.403736E+09 | 0.111534E+10 | 36813209.25 |
September | 0.517041E+09 | 0.225725E+09 | 0.291316E+09 | 0.676186E+09 | 0.106159E+09 |
October | 0.530121E+09 | 0.258241E+09 | 0.271880E+09 | 0.600896E+09 | 0.263090E+09 |
November | 0.241596E+09 | 70580626.93 | 0.171015E+09 | 0.159935E+09 | 0.438838E+09 |
December | 0.220511E+09 | 95188244.85 | 0.125323E+09 | 0.132138E+09 | 0.612554E+09 |
Annual Sum or Average | 0.593641E+10 | 0.250343E+10 | 0.343299E+10 | 0.682988E+10 | 0.373222E+10 |
Minimum of Months | 0.220511E+09 | 70580626.93 | 0.125323E+09 | 0.132138E+09 | 14949439.11 |
Maximum of Months | 0.750935E+09 | 0.347199E+09 | 0.423671E+09 | 0.111534E+10 | 0.677295E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62085473.63 | 0.00 | 62085473.63 | 3426193.08 | 0.376469E+09 |
February | 76739382.29 | 0.00 | 76739382.29 | 6780574.16 | 0.349137E+09 |
March | 0.117848E+09 | 2454.62 | 0.117846E+09 | 40814406.28 | 0.249474E+09 |
April | 0.137245E+09 | 565514.21 | 0.136680E+09 | 88000054.95 | 0.159813E+09 |
May | 0.188627E+09 | 6903211.21 | 0.181724E+09 | 0.182661E+09 | 90653524.09 |
June | 0.192578E+09 | 10242901.02 | 0.182335E+09 | 0.246862E+09 | 40428052.19 |
July | 0.193148E+09 | 7538040.63 | 0.185610E+09 | 0.301572E+09 | 11588010.68 |
August | 0.170807E+09 | 2269513.75 | 0.168538E+09 | 0.266195E+09 | 22640184.13 |
September | 0.124465E+09 | 72357.39 | 0.124392E+09 | 0.143141E+09 | 64579654.28 |
October | 0.111214E+09 | 0.00 | 0.111214E+09 | 86435544.10 | 0.146194E+09 |
November | 75489568.31 | 0.00 | 75489568.31 | 22912833.71 | 0.238254E+09 |
December | 54155055.53 | 0.00 | 54155055.53 | 2418249.63 | 0.338745E+09 |
Annual Sum or Average | 0.150440E+10 | 27593992.83 | 0.147681E+10 | 0.139122E+10 | 0.208798E+10 |
Minimum of Months | 54155055.53 | 0.00 | 54155055.53 | 2418249.63 | 11588010.68 |
Maximum of Months | 0.193148E+09 | 10242901.02 | 0.185610E+09 | 0.301572E+09 | 0.376469E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.239844E+09 | 98462657.35 | 0.141382E+09 | 0.148019E+09 | 0.670300E+09 |
February | 0.318223E+09 | 0.139658E+09 | 0.178565E+09 | 0.218705E+09 | 0.610583E+09 |
March | 0.523325E+09 | 0.242520E+09 | 0.280804E+09 | 0.471820E+09 | 0.436389E+09 |
April | 0.550044E+09 | 0.235058E+09 | 0.314986E+09 | 0.569379E+09 | 0.291839E+09 |
May | 0.663989E+09 | 0.252408E+09 | 0.411582E+09 | 0.783211E+09 | 0.174873E+09 |
June | 0.702057E+09 | 0.283331E+09 | 0.418726E+09 | 0.941226E+09 | 77143583.31 |
July | 0.678728E+09 | 0.255057E+09 | 0.423671E+09 | 0.101344E+10 | 21502278.53 |
August | 0.750935E+09 | 0.347199E+09 | 0.403736E+09 | 0.111472E+10 | 42832989.29 |
September | 0.517041E+09 | 0.225725E+09 | 0.291316E+09 | 0.672758E+09 | 0.117856E+09 |
October | 0.530121E+09 | 0.258241E+09 | 0.271880E+09 | 0.609794E+09 | 0.264788E+09 |
November | 0.241596E+09 | 70580626.93 | 0.171015E+09 | 0.170358E+09 | 0.430746E+09 |
December | 0.220511E+09 | 95188244.85 | 0.125323E+09 | 0.141612E+09 | 0.603509E+09 |
Annual Sum or Average | 0.593641E+10 | 0.250343E+10 | 0.343299E+10 | 0.685503E+10 | 0.374236E+10 |
Minimum of Months | 0.220511E+09 | 70580626.93 | 0.125323E+09 | 0.141612E+09 | 21502278.53 |
Maximum of Months | 0.750935E+09 | 0.347199E+09 | 0.423671E+09 | 0.111472E+10 | 0.670300E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.473281E+09 | 0.310573E+09 | 0.162708E+09 | 0.448794E+09 | 0.509421E+09 |
February | 0.565726E+09 | 0.375997E+09 | 0.189730E+09 | 0.547795E+09 | 0.458050E+09 |
March | 0.554938E+09 | 0.305486E+09 | 0.249452E+09 | 0.574745E+09 | 0.358306E+09 |
April | 0.427468E+09 | 0.172942E+09 | 0.254525E+09 | 0.469906E+09 | 0.238228E+09 |
May | 0.379382E+09 | 77672293.27 | 0.301710E+09 | 0.458089E+09 | 0.133385E+09 |
June | 0.346674E+09 | 53414803.41 | 0.293260E+09 | 0.501667E+09 | 45507684.92 |
July | 0.372740E+09 | 62910526.60 | 0.309830E+09 | 0.611867E+09 | 9934721.60 |
August | 0.499248E+09 | 0.184167E+09 | 0.315081E+09 | 0.799985E+09 | 26878280.93 |
September | 0.509846E+09 | 0.255986E+09 | 0.253861E+09 | 0.704200E+09 | 82575308.60 |
October | 0.744515E+09 | 0.466873E+09 | 0.277642E+09 | 0.930581E+09 | 0.205356E+09 |
November | 0.498897E+09 | 0.299274E+09 | 0.199623E+09 | 0.521032E+09 | 0.339206E+09 |
December | 0.511328E+09 | 0.363171E+09 | 0.148157E+09 | 0.510025E+09 | 0.456201E+09 |
Annual Sum or Average | 0.588404E+10 | 0.292847E+10 | 0.295558E+10 | 0.707869E+10 | 0.286305E+10 |
Minimum of Months | 0.346674E+09 | 53414803.41 | 0.148157E+09 | 0.448794E+09 | 9934721.60 |
Maximum of Months | 0.744515E+09 | 0.466873E+09 | 0.315081E+09 | 0.930581E+09 | 0.509421E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.434582E+09 | 0.00 | 0.434582E+09 | 3748008.28 | 0.318052E+10 |
February | 0.537155E+09 | 0.00 | 0.537155E+09 | 20457326.27 | 0.290486E+10 |
March | 0.824904E+09 | 17181.70 | 0.824887E+09 | 0.207478E+09 | 0.213172E+10 |
April | 0.960679E+09 | 3958449.54 | 0.956721E+09 | 0.532890E+09 | 0.139270E+10 |
May | 0.132034E+10 | 48320648.33 | 0.127202E+10 | 0.120179E+10 | 0.777208E+09 |
June | 0.134799E+10 | 71697591.63 | 0.127629E+10 | 0.170014E+10 | 0.351602E+09 |
July | 0.135198E+10 | 52764286.00 | 0.129922E+10 | 0.201563E+10 | 0.152192E+09 |
August | 0.119561E+10 | 15885994.55 | 0.117972E+10 | 0.176810E+10 | 0.234896E+09 |
September | 0.871220E+09 | 506482.57 | 0.870713E+09 | 0.946121E+09 | 0.580178E+09 |
October | 0.778470E+09 | 0.00 | 0.778470E+09 | 0.532962E+09 | 0.124681E+10 |
November | 0.528407E+09 | 0.00 | 0.528407E+09 | 99990078.64 | 0.211146E+10 |
December | 0.379071E+09 | 0.00 | 0.379071E+09 | 3743822.32 | 0.292681E+10 |
Annual Sum or Average | 0.105304E+11 | 0.193151E+09 | 0.103373E+11 | 0.903305E+10 | 0.179910E+11 |
Minimum of Months | 0.379071E+09 | 0.00 | 0.379071E+09 | 3743822.32 | 0.152192E+09 |
Maximum of Months | 0.135198E+10 | 71697591.63 | 0.129922E+10 | 0.201563E+10 | 0.318052E+10 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.434582E+09 | 0.00 | 0.434582E+09 | 2194742.90 | 0.327390E+10 |
February | 0.537155E+09 | 0.00 | 0.537155E+09 | 16452088.12 | 0.298594E+10 |
March | 0.824904E+09 | 17181.70 | 0.824887E+09 | 0.188686E+09 | 0.219710E+10 |
April | 0.960679E+09 | 3958449.54 | 0.956721E+09 | 0.506221E+09 | 0.143699E+10 |
May | 0.132034E+10 | 48320648.33 | 0.127202E+10 | 0.116936E+10 | 0.800854E+09 |
June | 0.134799E+10 | 71697591.63 | 0.127629E+10 | 0.167596E+10 | 0.366486E+09 |
July | 0.135198E+10 | 52764286.00 | 0.129922E+10 | 0.199364E+10 | 0.163485E+09 |
August | 0.119561E+10 | 15885994.55 | 0.117972E+10 | 0.174563E+10 | 0.246680E+09 |
September | 0.871220E+09 | 506482.57 | 0.870713E+09 | 0.924380E+09 | 0.602774E+09 |
October | 0.778470E+09 | 0.00 | 0.778470E+09 | 0.510085E+09 | 0.128359E+10 |
November | 0.528407E+09 | 0.00 | 0.528407E+09 | 88985251.86 | 0.218194E+10 |
December | 0.379071E+09 | 0.00 | 0.379071E+09 | 2749322.33 | 0.301583E+10 |
Annual Sum or Average | 0.105304E+11 | 0.193151E+09 | 0.103373E+11 | 0.882434E+10 | 0.185556E+11 |
Minimum of Months | 0.379071E+09 | 0.00 | 0.379071E+09 | 2194742.90 | 0.163485E+09 |
Maximum of Months | 0.135198E+10 | 71697591.63 | 0.129922E+10 | 0.199364E+10 | 0.327390E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62085473.63 | 0.00 | 62085473.63 | 4370272.45 | 0.402498E+09 |
February | 76739382.29 | 0.00 | 76739382.29 | 7849078.47 | 0.369796E+09 |
March | 0.117848E+09 | 2454.62 | 0.117846E+09 | 47803802.65 | 0.265704E+09 |
April | 0.137245E+09 | 565514.21 | 0.136680E+09 | 0.112112E+09 | 0.174876E+09 |
May | 0.188627E+09 | 6903211.21 | 0.181724E+09 | 0.232860E+09 | 0.102200E+09 |
June | 0.192578E+09 | 10242901.02 | 0.182335E+09 | 0.313191E+09 | 47181137.27 |
July | 0.193148E+09 | 7538040.63 | 0.185610E+09 | 0.368053E+09 | 21661244.04 |
August | 0.170807E+09 | 2269513.75 | 0.168538E+09 | 0.327465E+09 | 31334064.29 |
September | 0.124465E+09 | 72357.39 | 0.124392E+09 | 0.192281E+09 | 69134199.95 |
October | 0.111214E+09 | 0.00 | 0.111214E+09 | 0.113641E+09 | 0.149378E+09 |
November | 75489568.31 | 0.00 | 75489568.31 | 27843295.41 | 0.259284E+09 |
December | 54155055.53 | 0.00 | 54155055.53 | 3174703.29 | 0.363941E+09 |
Annual Sum or Average | 0.150440E+10 | 27593992.83 | 0.147681E+10 | 0.175064E+10 | 0.225699E+10 |
Minimum of Months | 54155055.53 | 0.00 | 54155055.53 | 3174703.29 | 21661244.04 |
Maximum of Months | 0.193148E+09 | 10242901.02 | 0.185610E+09 | 0.368053E+09 | 0.402498E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.483009E+09 | 0.192977E+09 | 0.290032E+09 | 0.295638E+09 | 0.140769E+10 |
February | 0.677341E+09 | 0.315422E+09 | 0.361918E+09 | 0.476535E+09 | 0.124229E+10 |
March | 0.963008E+09 | 0.409271E+09 | 0.553737E+09 | 0.889019E+09 | 0.949954E+09 |
April | 0.111562E+10 | 0.489656E+09 | 0.625960E+09 | 0.125943E+10 | 0.630785E+09 |
May | 0.139177E+10 | 0.554641E+09 | 0.837130E+09 | 0.184414E+10 | 0.383964E+09 |
June | 0.125068E+10 | 0.453010E+09 | 0.797667E+09 | 0.192614E+10 | 0.177223E+09 |
July | 0.129630E+10 | 0.466688E+09 | 0.829615E+09 | 0.220053E+10 | 81584738.45 |
August | 0.146238E+10 | 0.659763E+09 | 0.802613E+09 | 0.241031E+10 | 0.117235E+09 |
September | 0.105863E+10 | 0.476906E+09 | 0.581729E+09 | 0.157407E+10 | 0.253552E+09 |
October | 0.988263E+09 | 0.447341E+09 | 0.540922E+09 | 0.125070E+10 | 0.541487E+09 |
November | 0.592348E+09 | 0.227626E+09 | 0.364722E+09 | 0.514564E+09 | 0.906567E+09 |
December | 0.478542E+09 | 0.225798E+09 | 0.252744E+09 | 0.330249E+09 | 0.125757E+10 |
Annual Sum or Average | 0.117579E+11 | 0.491910E+10 | 0.683879E+10 | 0.149713E+11 | 0.794991E+10 |
Minimum of Months | 0.478542E+09 | 0.192977E+09 | 0.252744E+09 | 0.295638E+09 | 81584738.45 |
Maximum of Months | 0.146238E+10 | 0.659763E+09 | 0.837130E+09 | 0.241031E+10 | 0.140769E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.322707E+09 | 0.211765E+09 | 0.110943E+09 | 0.325630E+09 | 0.355391E+09 |
February | 0.385741E+09 | 0.256374E+09 | 0.129367E+09 | 0.398012E+09 | 0.314447E+09 |
March | 0.378385E+09 | 0.208296E+09 | 0.170089E+09 | 0.421052E+09 | 0.252172E+09 |
April | 0.291469E+09 | 0.117921E+09 | 0.173548E+09 | 0.353029E+09 | 0.175281E+09 |
May | 0.258682E+09 | 52960934.60 | 0.205721E+09 | 0.355826E+09 | 0.106858E+09 |
June | 0.236380E+09 | 36420939.70 | 0.199959E+09 | 0.391657E+09 | 49210056.22 |
July | 0.254153E+09 | 42895608.52 | 0.211258E+09 | 0.472509E+09 | 22131453.61 |
August | 0.340413E+09 | 0.125575E+09 | 0.214838E+09 | 0.602887E+09 | 31644797.37 |
September | 0.347639E+09 | 0.174544E+09 | 0.173095E+09 | 0.531843E+09 | 68544090.05 |
October | 0.507648E+09 | 0.318338E+09 | 0.189310E+09 | 0.682672E+09 | 0.145351E+09 |
November | 0.340174E+09 | 0.204060E+09 | 0.136113E+09 | 0.382080E+09 | 0.235827E+09 |
December | 0.348649E+09 | 0.247629E+09 | 0.101021E+09 | 0.369936E+09 | 0.316414E+09 |
Annual Sum or Average | 0.401204E+10 | 0.199678E+10 | 0.201526E+10 | 0.528713E+10 | 0.207327E+10 |
Minimum of Months | 0.236380E+09 | 36420939.70 | 0.101021E+09 | 0.325630E+09 | 22131453.61 |
Maximum of Months | 0.507648E+09 | 0.318338E+09 | 0.214838E+09 | 0.682672E+09 | 0.355391E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 78627334.97 | 0.00 | 78627334.97 | 1487390.47 | 0.525348E+09 |
February | 97185585.68 | 0.00 | 97185585.68 | 5382708.30 | 0.483212E+09 |
March | 0.149247E+09 | 3108.62 | 0.149244E+09 | 44930038.48 | 0.339613E+09 |
April | 0.173812E+09 | 716188.06 | 0.173096E+09 | 0.108905E+09 | 0.218056E+09 |
May | 0.238884E+09 | 8742481.42 | 0.230142E+09 | 0.234436E+09 | 0.123961E+09 |
June | 0.243887E+09 | 12971987.85 | 0.230915E+09 | 0.313714E+09 | 58541453.52 |
July | 0.244609E+09 | 9546452.84 | 0.235063E+09 | 0.364852E+09 | 26503611.53 |
August | 0.216317E+09 | 2874195.96 | 0.213443E+09 | 0.318247E+09 | 41739270.54 |
September | 0.157627E+09 | 91636.07 | 0.157535E+09 | 0.175801E+09 | 94747170.60 |
October | 0.140846E+09 | 0.00 | 0.140846E+09 | 0.102987E+09 | 0.203098E+09 |
November | 95602775.14 | 0.00 | 95602775.14 | 22988115.51 | 0.335552E+09 |
December | 68583960.84 | 0.00 | 68583960.84 | 1252059.21 | 0.477350E+09 |
Annual Sum or Average | 0.190523E+10 | 34946050.83 | 0.187028E+10 | 0.169498E+10 | 0.292772E+10 |
Minimum of Months | 68583960.84 | 0.00 | 68583960.84 | 1252059.21 | 26503611.53 |
Maximum of Months | 0.244609E+09 | 12971987.85 | 0.235063E+09 | 0.364852E+09 | 0.525348E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 70348174.52 | 0.00 | 70348174.52 | 1330773.89 | 0.470012E+09 |
February | 86952311.75 | 0.00 | 86952311.75 | 4815929.51 | 0.432332E+09 |
March | 0.133532E+09 | 2781.30 | 0.133529E+09 | 40199075.67 | 0.303853E+09 |
April | 0.155510E+09 | 640776.17 | 0.154870E+09 | 97437284.52 | 0.195096E+09 |
May | 0.213730E+09 | 7821931.26 | 0.205909E+09 | 0.209751E+09 | 0.110908E+09 |
June | 0.218207E+09 | 11606086.68 | 0.206601E+09 | 0.280681E+09 | 52377260.28 |
July | 0.218853E+09 | 8541247.52 | 0.210312E+09 | 0.326434E+09 | 23712881.66 |
August | 0.193539E+09 | 2571554.02 | 0.190968E+09 | 0.284737E+09 | 37344283.50 |
September | 0.141029E+09 | 81987.14 | 0.140947E+09 | 0.157290E+09 | 84770652.53 |
October | 0.126015E+09 | 0.00 | 0.126015E+09 | 92142730.12 | 0.181712E+09 |
November | 85536165.15 | 0.00 | 85536165.15 | 20567554.05 | 0.300216E+09 |
December | 61362329.63 | 0.00 | 61362329.63 | 1120222.12 | 0.427031E+09 |
Annual Sum or Average | 0.170462E+10 | 31266364.09 | 0.167335E+10 | 0.151651E+10 | 0.261937E+10 |
Minimum of Months | 61362329.63 | 0.00 | 61362329.63 | 1120222.12 | 23712881.66 |
Maximum of Months | 0.218853E+09 | 11606086.68 | 0.210312E+09 | 0.326434E+09 | 0.470012E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.120476E+10 | 0.790580E+09 | 0.414182E+09 | 0.116025E+10 | 0.134555E+10 |
February | 0.144009E+10 | 0.957120E+09 | 0.482967E+09 | 0.142251E+10 | 0.119340E+10 |
March | 0.141262E+10 | 0.777630E+09 | 0.634994E+09 | 0.148723E+10 | 0.939505E+09 |
April | 0.108814E+10 | 0.440233E+09 | 0.647908E+09 | 0.120605E+10 | 0.645192E+09 |
May | 0.965737E+09 | 0.197719E+09 | 0.768018E+09 | 0.115238E+10 | 0.393051E+09 |
June | 0.882478E+09 | 0.135970E+09 | 0.746508E+09 | 0.122308E+10 | 0.183872E+09 |
July | 0.948830E+09 | 0.160142E+09 | 0.788688E+09 | 0.146716E+10 | 80090063.93 |
August | 0.127086E+10 | 0.468807E+09 | 0.802056E+09 | 0.195876E+10 | 0.126979E+09 |
September | 0.129784E+10 | 0.651626E+09 | 0.646216E+09 | 0.177111E+10 | 0.276649E+09 |
October | 0.189520E+10 | 0.118845E+10 | 0.706752E+09 | 0.238864E+10 | 0.567355E+09 |
November | 0.126997E+10 | 0.761817E+09 | 0.508152E+09 | 0.134931E+10 | 0.886957E+09 |
December | 0.130161E+10 | 0.924471E+09 | 0.377141E+09 | 0.132210E+10 | 0.119960E+10 |
Annual Sum or Average | 0.149781E+11 | 0.745457E+10 | 0.752358E+10 | 0.179086E+11 | 0.783820E+10 |
Minimum of Months | 0.882478E+09 | 0.135970E+09 | 0.377141E+09 | 0.115238E+10 | 80090063.93 |
Maximum of Months | 0.189520E+10 | 0.118845E+10 | 0.802056E+09 | 0.238864E+10 | 0.134555E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 597.00 | 624.56 | 609.38 | 399.88 | 209.50 | 0.00 | 0.00 |
February | 806.05 | 618.90 | 806.45 | 535.99 | 270.46 | 0.00 | 0.00 |
March | 760.15 | 440.11 | 714.52 | 393.33 | 321.18 | 0.00 | 0.00 |
April | 639.57 | 310.26 | 568.74 | 230.10 | 338.64 | 0.00 | 0.00 |
May | 598.59 | 177.34 | 488.48 | 100.01 | 388.47 | 0.00 | 0.00 |
June | 650.98 | 84.68 | 461.24 | 71.07 | 390.17 | 0.00 | 0.00 |
July | 746.58 | 35.75 | 479.92 | 81.00 | 398.92 | 0.00 | 0.00 |
August | 986.36 | 63.61 | 642.81 | 237.13 | 405.68 | 0.00 | 0.00 |
September | 926.68 | 135.67 | 678.34 | 340.59 | 337.75 | 0.00 | 0.00 |
October | 1203.25 | 279.37 | 958.61 | 601.13 | 357.48 | 0.00 | 0.00 |
November | 709.37 | 432.80 | 663.77 | 398.18 | 265.59 | 0.00 | 0.00 |
December | 673.65 | 561.67 | 658.37 | 467.61 | 190.76 | 0.00 | 0.00 |
Annual Sum or Average | 775.07 | 312.02 | 643.45 | 320.24 | 323.20 | 0.00 | 0.00 |
Minimum of Months | 597.00 | 35.75 | 461.24 | 71.07 | 190.76 | 0.00 | 0.00 |
Maximum of Months | 1203.25 | 624.56 | 958.61 | 601.13 | 405.68 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1659.82 | 1817.83 | 1715.97 | 1126.05 | 589.93 | 0.00 | 0.00 |
February | 2240.14 | 1806.70 | 2270.92 | 1509.32 | 761.60 | 0.00 | 0.00 |
March | 2111.33 | 1319.86 | 2012.03 | 1107.60 | 904.43 | 0.00 | 0.00 |
April | 1768.83 | 949.96 | 1601.52 | 647.94 | 953.59 | 0.00 | 0.00 |
May | 1641.50 | 566.30 | 1375.52 | 281.62 | 1093.90 | 0.00 | 0.00 |
June | 1802.31 | 277.96 | 1298.82 | 200.12 | 1098.70 | 0.00 | 0.00 |
July | 2078.60 | 122.84 | 1351.43 | 228.09 | 1123.34 | 0.00 | 0.00 |
August | 2757.46 | 198.48 | 1810.11 | 667.74 | 1142.38 | 0.00 | 0.00 |
September | 2579.99 | 435.95 | 1910.16 | 959.07 | 951.10 | 0.00 | 0.00 |
October | 3354.11 | 861.15 | 2699.38 | 1692.74 | 1006.64 | 0.00 | 0.00 |
November | 1964.82 | 1298.60 | 1869.14 | 1121.25 | 747.90 | 0.00 | 0.00 |
December | 1872.44 | 1652.85 | 1853.92 | 1316.75 | 537.17 | 0.00 | 0.00 |
Annual Sum or Average | 2153.25 | 937.48 | 1811.90 | 901.78 | 910.12 | 0.00 | 0.00 |
Minimum of Months | 1641.50 | 122.84 | 1298.82 | 200.12 | 537.17 | 0.00 | 0.00 |
Maximum of Months | 3354.11 | 1817.83 | 2699.38 | 1692.74 | 1142.38 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2189.91 | 2475.71 | 2229.15 | 1462.80 | 766.35 | 0.00 | 0.00 |
February | 2964.70 | 2441.26 | 2950.05 | 1960.69 | 989.36 | 0.00 | 0.00 |
March | 2796.68 | 1787.28 | 2613.75 | 1438.84 | 1174.91 | 0.00 | 0.00 |
April | 2341.87 | 1295.34 | 2080.47 | 841.71 | 1238.76 | 0.00 | 0.00 |
May | 2171.54 | 773.77 | 1786.87 | 365.84 | 1421.04 | 0.00 | 0.00 |
June | 2391.30 | 373.52 | 1687.25 | 259.97 | 1427.28 | 0.00 | 0.00 |
July | 2767.96 | 161.51 | 1755.59 | 296.31 | 1459.28 | 0.00 | 0.00 |
August | 3671.01 | 255.77 | 2351.44 | 867.43 | 1484.02 | 0.00 | 0.00 |
September | 3418.90 | 579.70 | 2481.41 | 1245.88 | 1235.53 | 0.00 | 0.00 |
October | 4444.99 | 1140.79 | 3506.65 | 2198.97 | 1307.68 | 0.00 | 0.00 |
November | 2592.30 | 1770.30 | 2428.12 | 1456.56 | 971.56 | 0.00 | 0.00 |
December | 2470.59 | 2251.66 | 2408.35 | 1710.53 | 697.81 | 0.00 | 0.00 |
Annual Sum or Average | 2852.70 | 1268.94 | 2353.77 | 1171.47 | 1182.30 | 0.00 | 0.00 |
Minimum of Months | 2171.54 | 161.51 | 1687.25 | 259.97 | 697.81 | 0.00 | 0.00 |
Maximum of Months | 4444.99 | 2475.71 | 3506.65 | 2198.97 | 1484.02 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 158.06 | 366.89 | 210.03 | 115.83 | 94.21 | 0.00 | 0.00 |
February | 229.37 | 364.64 | 290.99 | 163.70 | 127.29 | 0.00 | 0.00 |
March | 317.59 | 249.85 | 336.66 | 168.32 | 168.34 | 0.00 | 0.00 |
April | 343.86 | 173.76 | 324.66 | 136.18 | 188.48 | 0.00 | 0.00 |
May | 414.61 | 96.27 | 344.49 | 114.01 | 230.47 | 0.00 | 0.00 |
June | 504.17 | 37.18 | 362.05 | 123.36 | 238.69 | 0.00 | 0.00 |
July | 537.69 | 9.26 | 348.30 | 111.24 | 237.06 | 0.00 | 0.00 |
August | 621.30 | 22.24 | 407.46 | 176.51 | 230.95 | 0.00 | 0.00 |
September | 448.67 | 64.02 | 333.60 | 154.42 | 179.17 | 0.00 | 0.00 |
October | 464.65 | 149.96 | 387.46 | 215.27 | 172.19 | 0.00 | 0.00 |
November | 197.06 | 250.63 | 224.45 | 105.96 | 118.49 | 0.00 | 0.00 |
December | 170.15 | 329.01 | 212.50 | 127.99 | 84.51 | 0.00 | 0.00 |
Annual Sum or Average | 368.33 | 175.08 | 315.46 | 142.70 | 172.76 | 0.00 | 0.00 |
Minimum of Months | 158.06 | 9.26 | 210.03 | 105.96 | 84.51 | 0.00 | 0.00 |
Maximum of Months | 621.30 | 366.89 | 407.46 | 215.27 | 238.69 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 50.91 | 387.23 | 112.73 | 36.76 | 75.97 | 0.00 | 0.00 |
February | 86.22 | 390.38 | 163.26 | 57.73 | 105.53 | 0.00 | 0.00 |
March | 187.25 | 251.99 | 239.39 | 90.55 | 148.84 | 0.00 | 0.00 |
April | 254.50 | 173.58 | 265.16 | 90.90 | 174.25 | 0.00 | 0.00 |
May | 364.42 | 97.65 | 318.33 | 96.82 | 221.51 | 0.00 | 0.00 |
June | 462.95 | 43.76 | 345.15 | 113.26 | 231.89 | 0.00 | 0.00 |
July | 494.19 | 12.37 | 325.52 | 98.04 | 227.48 | 0.00 | 0.00 |
August | 517.88 | 25.02 | 344.14 | 130.48 | 213.66 | 0.00 | 0.00 |
September | 316.62 | 70.22 | 247.49 | 87.11 | 160.38 | 0.00 | 0.00 |
October | 259.60 | 153.74 | 239.45 | 96.42 | 143.03 | 0.00 | 0.00 |
November | 71.71 | 258.68 | 122.33 | 27.23 | 95.10 | 0.00 | 0.00 |
December | 47.95 | 349.14 | 102.55 | 35.54 | 67.01 | 0.00 | 0.00 |
Annual Sum or Average | 260.75 | 183.31 | 235.95 | 80.26 | 155.69 | 0.00 | 0.00 |
Minimum of Months | 47.95 | 12.37 | 102.55 | 27.23 | 67.01 | 0.00 | 0.00 |
Maximum of Months | 517.88 | 390.38 | 345.15 | 130.48 | 231.89 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 92.87 | 104.25 | 96.37 | 63.24 | 33.13 | 0.00 | 0.00 |
February | 119.43 | 121.58 | 127.53 | 84.76 | 42.77 | 0.00 | 0.00 |
March | 111.00 | 95.64 | 113.00 | 62.20 | 50.79 | 0.00 | 0.00 |
April | 90.24 | 72.51 | 89.94 | 36.39 | 53.55 | 0.00 | 0.00 |
May | 80.63 | 46.48 | 77.25 | 15.82 | 61.43 | 0.00 | 0.00 |
June | 90.27 | 25.39 | 72.94 | 11.24 | 61.70 | 0.00 | 0.00 |
July | 106.82 | 14.49 | 75.90 | 12.81 | 63.09 | 0.00 | 0.00 |
August | 146.45 | 18.99 | 101.66 | 37.50 | 64.16 | 0.00 | 0.00 |
September | 136.63 | 36.64 | 107.27 | 53.86 | 53.41 | 0.00 | 0.00 |
October | 180.14 | 63.73 | 151.60 | 95.06 | 56.53 | 0.00 | 0.00 |
November | 102.78 | 94.16 | 104.97 | 62.97 | 42.00 | 0.00 | 0.00 |
December | 100.08 | 110.96 | 104.12 | 73.95 | 30.17 | 0.00 | 0.00 |
Annual Sum or Average | 113.15 | 66.73 | 101.76 | 50.64 | 51.11 | 0.00 | 0.00 |
Minimum of Months | 80.63 | 14.49 | 72.94 | 11.24 | 30.17 | 0.00 | 0.00 |
Maximum of Months | 180.14 | 121.58 | 151.60 | 95.06 | 64.16 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.64 | 118.44 | 18.55 | 0.00 | 18.55 | 0.00 | 0.00 |
February | 1.91 | 120.11 | 25.38 | 0.00 | 25.38 | 0.00 | 0.00 |
March | 12.15 | 76.60 | 35.20 | 0.00 | 35.20 | 0.00 | 0.00 |
April | 28.50 | 50.08 | 42.37 | 0.17 | 42.19 | 0.00 | 0.00 |
May | 58.53 | 26.19 | 56.35 | 2.06 | 54.29 | 0.00 | 0.00 |
June | 81.73 | 10.59 | 59.45 | 3.16 | 56.28 | 0.00 | 0.00 |
July | 95.12 | 2.63 | 57.70 | 2.25 | 55.45 | 0.00 | 0.00 |
August | 84.61 | 5.75 | 51.02 | 0.68 | 50.35 | 0.00 | 0.00 |
September | 47.23 | 18.49 | 38.42 | 0.02 | 38.40 | 0.00 | 0.00 |
October | 27.41 | 42.94 | 33.22 | 0.00 | 33.22 | 0.00 | 0.00 |
November | 6.57 | 78.00 | 23.30 | 0.00 | 23.30 | 0.00 | 0.00 |
December | 0.48 | 107.32 | 16.18 | 0.00 | 16.18 | 0.00 | 0.00 |
Annual Sum or Average | 37.32 | 54.40 | 38.17 | 0.70 | 37.47 | 0.00 | 0.00 |
Minimum of Months | 0.48 | 2.63 | 16.18 | 0.00 | 16.18 | 0.00 | 0.00 |
Maximum of Months | 95.12 | 120.11 | 59.45 | 3.16 | 56.28 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 158.42 | 364.50 | 210.66 | 115.09 | 95.57 | 0.00 | 0.00 |
February | 238.73 | 359.89 | 299.45 | 171.17 | 128.28 | 0.00 | 0.00 |
March | 299.25 | 251.66 | 321.06 | 154.18 | 166.88 | 0.00 | 0.00 |
April | 343.77 | 169.40 | 327.67 | 139.96 | 187.71 | 0.00 | 0.00 |
May | 428.58 | 93.51 | 356.41 | 123.32 | 233.09 | 0.00 | 0.00 |
June | 463.70 | 35.46 | 332.47 | 101.44 | 231.03 | 0.00 | 0.00 |
July | 523.00 | 8.73 | 336.90 | 103.14 | 233.76 | 0.00 | 0.00 |
August | 610.42 | 20.88 | 400.11 | 170.06 | 230.05 | 0.00 | 0.00 |
September | 453.39 | 61.74 | 338.35 | 159.34 | 179.00 | 0.00 | 0.00 |
October | 445.44 | 146.88 | 374.03 | 202.37 | 171.67 | 0.00 | 0.00 |
November | 225.20 | 248.42 | 245.51 | 122.64 | 122.87 | 0.00 | 0.00 |
December | 179.38 | 325.76 | 219.51 | 134.61 | 84.90 | 0.00 | 0.00 |
Annual Sum or Average | 365.05 | 172.87 | 313.65 | 141.31 | 172.34 | 0.00 | 0.00 |
Minimum of Months | 158.42 | 8.73 | 210.66 | 101.44 | 84.90 | 0.00 | 0.00 |
Maximum of Months | 610.42 | 364.50 | 400.11 | 202.37 | 233.76 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 46.32 | 379.81 | 113.35 | 36.03 | 77.33 | 0.00 | 0.00 |
February | 85.16 | 374.67 | 171.72 | 65.20 | 106.53 | 0.00 | 0.00 |
March | 167.87 | 252.31 | 223.79 | 76.41 | 147.38 | 0.00 | 0.00 |
April | 254.16 | 168.42 | 268.17 | 94.68 | 173.49 | 0.00 | 0.00 |
May | 379.69 | 94.83 | 330.26 | 106.12 | 224.13 | 0.00 | 0.00 |
June | 424.06 | 41.01 | 315.57 | 91.34 | 224.23 | 0.00 | 0.00 |
July | 478.39 | 11.74 | 314.12 | 89.94 | 224.18 | 0.00 | 0.00 |
August | 505.15 | 23.56 | 336.79 | 124.02 | 212.77 | 0.00 | 0.00 |
September | 320.48 | 66.68 | 252.25 | 92.03 | 160.22 | 0.00 | 0.00 |
October | 239.94 | 148.65 | 226.02 | 83.51 | 142.51 | 0.00 | 0.00 |
November | 95.38 | 251.85 | 143.40 | 43.91 | 99.48 | 0.00 | 0.00 |
December | 51.41 | 339.75 | 109.56 | 42.15 | 67.40 | 0.00 | 0.00 |
Annual Sum or Average | 255.17 | 178.35 | 234.14 | 78.87 | 155.27 | 0.00 | 0.00 |
Minimum of Months | 46.32 | 11.74 | 109.56 | 36.03 | 67.40 | 0.00 | 0.00 |
Maximum of Months | 505.15 | 379.81 | 336.79 | 124.02 | 224.23 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 181.47 | 468.73 | 248.98 | 137.02 | 111.96 | 0.00 | 0.00 |
February | 252.44 | 464.91 | 331.31 | 183.66 | 147.66 | 0.00 | 0.00 |
March | 284.12 | 323.83 | 321.09 | 134.78 | 186.32 | 0.00 | 0.00 |
April | 282.93 | 223.89 | 286.66 | 79.22 | 207.43 | 0.00 | 0.00 |
May | 331.51 | 124.13 | 289.45 | 38.74 | 250.71 | 0.00 | 0.00 |
June | 399.16 | 57.41 | 286.82 | 31.20 | 255.62 | 0.00 | 0.00 |
July | 459.04 | 21.33 | 289.44 | 32.63 | 256.81 | 0.00 | 0.00 |
August | 518.42 | 38.83 | 330.80 | 82.72 | 248.08 | 0.00 | 0.00 |
September | 420.90 | 94.64 | 315.67 | 116.75 | 198.92 | 0.00 | 0.00 |
October | 472.19 | 198.00 | 400.44 | 205.98 | 194.46 | 0.00 | 0.00 |
November | 248.20 | 318.95 | 277.92 | 136.44 | 141.49 | 0.00 | 0.00 |
December | 208.62 | 418.18 | 260.64 | 160.23 | 100.41 | 0.00 | 0.00 |
Annual Sum or Average | 338.96 | 228.08 | 303.16 | 111.25 | 191.92 | 0.00 | 0.00 |
Minimum of Months | 181.47 | 21.33 | 248.98 | 31.20 | 100.41 | 0.00 | 0.00 |
Maximum of Months | 518.42 | 468.73 | 400.44 | 205.98 | 256.81 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 157.64 | 365.00 | 210.03 | 115.83 | 94.21 | 0.00 | 0.00 |
February | 228.11 | 363.39 | 290.99 | 163.70 | 127.29 | 0.00 | 0.00 |
March | 314.97 | 248.75 | 336.66 | 168.32 | 168.34 | 0.00 | 0.00 |
April | 340.66 | 172.57 | 324.66 | 136.18 | 188.48 | 0.00 | 0.00 |
May | 410.38 | 95.52 | 344.49 | 114.01 | 230.47 | 0.00 | 0.00 |
June | 500.02 | 36.25 | 362.05 | 123.36 | 238.69 | 0.00 | 0.00 |
July | 534.26 | 8.59 | 348.30 | 111.24 | 237.06 | 0.00 | 0.00 |
August | 618.01 | 21.13 | 407.46 | 176.51 | 230.95 | 0.00 | 0.00 |
September | 445.77 | 62.48 | 333.60 | 154.42 | 179.17 | 0.00 | 0.00 |
October | 461.71 | 147.91 | 387.46 | 215.27 | 172.19 | 0.00 | 0.00 |
November | 196.56 | 248.26 | 224.45 | 105.96 | 118.49 | 0.00 | 0.00 |
December | 170.06 | 326.74 | 212.50 | 127.99 | 84.51 | 0.00 | 0.00 |
Annual Sum or Average | 365.91 | 173.66 | 315.46 | 142.70 | 172.76 | 0.00 | 0.00 |
Minimum of Months | 157.64 | 8.59 | 210.03 | 105.96 | 84.51 | 0.00 | 0.00 |
Maximum of Months | 618.01 | 365.00 | 407.46 | 215.27 | 238.69 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 51.14 | 385.42 | 112.73 | 36.76 | 75.97 | 0.00 | 0.00 |
February | 85.97 | 389.47 | 163.26 | 57.73 | 105.53 | 0.00 | 0.00 |
March | 185.98 | 250.65 | 239.39 | 90.55 | 148.84 | 0.00 | 0.00 |
April | 251.97 | 172.60 | 265.16 | 90.90 | 174.25 | 0.00 | 0.00 |
May | 359.67 | 98.19 | 318.33 | 96.82 | 221.51 | 0.00 | 0.00 |
June | 457.90 | 44.89 | 345.15 | 113.26 | 231.89 | 0.00 | 0.00 |
July | 490.87 | 12.26 | 325.52 | 98.04 | 227.48 | 0.00 | 0.00 |
August | 515.47 | 24.34 | 344.14 | 130.48 | 213.66 | 0.00 | 0.00 |
September | 314.21 | 69.82 | 247.49 | 87.11 | 160.38 | 0.00 | 0.00 |
October | 258.28 | 151.79 | 239.45 | 96.42 | 143.03 | 0.00 | 0.00 |
November | 72.15 | 255.68 | 122.33 | 27.23 | 95.10 | 0.00 | 0.00 |
December | 48.49 | 346.52 | 102.55 | 35.54 | 67.01 | 0.00 | 0.00 |
Annual Sum or Average | 258.91 | 182.30 | 235.95 | 80.26 | 155.69 | 0.00 | 0.00 |
Minimum of Months | 48.49 | 12.26 | 102.55 | 27.23 | 67.01 | 0.00 | 0.00 |
Maximum of Months | 515.47 | 389.47 | 345.15 | 130.48 | 231.89 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 167.56 | 190.20 | 176.70 | 115.95 | 60.75 | 0.00 | 0.00 |
February | 226.44 | 189.34 | 233.85 | 155.42 | 78.43 | 0.00 | 0.00 |
March | 214.59 | 133.78 | 207.19 | 114.06 | 93.13 | 0.00 | 0.00 |
April | 181.29 | 91.91 | 164.92 | 66.72 | 98.20 | 0.00 | 0.00 |
May | 171.03 | 49.80 | 141.64 | 29.00 | 112.65 | 0.00 | 0.00 |
June | 193.54 | 17.56 | 133.75 | 20.61 | 113.14 | 0.00 | 0.00 |
July | 228.45 | 3.71 | 139.17 | 23.49 | 115.68 | 0.00 | 0.00 |
August | 298.68 | 10.04 | 186.40 | 68.76 | 117.64 | 0.00 | 0.00 |
September | 271.68 | 31.86 | 196.70 | 98.76 | 97.94 | 0.00 | 0.00 |
October | 347.44 | 76.67 | 277.97 | 174.31 | 103.66 | 0.00 | 0.00 |
November | 201.02 | 130.87 | 192.48 | 115.46 | 77.02 | 0.00 | 0.00 |
December | 190.42 | 170.33 | 190.91 | 135.59 | 55.32 | 0.00 | 0.00 |
Annual Sum or Average | 224.46 | 90.79 | 186.58 | 92.86 | 93.72 | 0.00 | 0.00 |
Minimum of Months | 167.56 | 3.71 | 133.75 | 20.61 | 55.32 | 0.00 | 0.00 |
Maximum of Months | 347.44 | 190.20 | 277.97 | 174.31 | 117.64 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1.40 | 1187.47 | 162.25 | 0.00 | 162.25 | 0.00 | 0.00 |
February | 8.46 | 1200.75 | 222.04 | 0.00 | 222.04 | 0.00 | 0.00 |
March | 77.46 | 795.89 | 307.98 | 0.01 | 307.98 | 0.00 | 0.00 |
April | 205.59 | 537.31 | 370.63 | 1.53 | 369.11 | 0.00 | 0.00 |
May | 448.70 | 290.18 | 492.96 | 18.04 | 474.92 | 0.00 | 0.00 |
June | 655.92 | 135.65 | 520.06 | 27.66 | 492.40 | 0.00 | 0.00 |
July | 752.55 | 56.82 | 504.77 | 19.70 | 485.07 | 0.00 | 0.00 |
August | 660.13 | 87.70 | 446.39 | 5.93 | 440.46 | 0.00 | 0.00 |
September | 365.02 | 223.83 | 336.12 | 0.20 | 335.92 | 0.00 | 0.00 |
October | 198.99 | 465.50 | 290.65 | 0.00 | 290.65 | 0.00 | 0.00 |
November | 38.58 | 814.61 | 203.86 | 0.00 | 203.86 | 0.00 | 0.00 |
December | 1.40 | 1092.75 | 141.53 | 0.00 | 141.53 | 0.00 | 0.00 |
Annual Sum or Average | 286.44 | 570.49 | 333.92 | 6.12 | 327.79 | 0.00 | 0.00 |
Minimum of Months | 1.40 | 56.82 | 141.53 | 0.00 | 141.53 | 0.00 | 0.00 |
Maximum of Months | 752.55 | 1200.75 | 520.06 | 27.66 | 492.40 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.82 | 1222.33 | 162.25 | 0.00 | 162.25 | 0.00 | 0.00 |
February | 6.80 | 1234.27 | 222.04 | 0.00 | 222.04 | 0.00 | 0.00 |
March | 70.45 | 820.30 | 307.98 | 0.01 | 307.98 | 0.00 | 0.00 |
April | 195.30 | 554.39 | 370.63 | 1.53 | 369.11 | 0.00 | 0.00 |
May | 436.59 | 299.00 | 492.96 | 18.04 | 474.92 | 0.00 | 0.00 |
June | 646.59 | 141.39 | 520.06 | 27.66 | 492.40 | 0.00 | 0.00 |
July | 744.34 | 61.04 | 504.77 | 19.70 | 485.07 | 0.00 | 0.00 |
August | 651.74 | 92.10 | 446.39 | 5.93 | 440.46 | 0.00 | 0.00 |
September | 356.63 | 232.55 | 336.12 | 0.20 | 335.92 | 0.00 | 0.00 |
October | 190.44 | 479.24 | 290.65 | 0.00 | 290.65 | 0.00 | 0.00 |
November | 34.33 | 841.80 | 203.86 | 0.00 | 203.86 | 0.00 | 0.00 |
December | 1.03 | 1125.98 | 141.53 | 0.00 | 141.53 | 0.00 | 0.00 |
Annual Sum or Average | 279.82 | 588.39 | 333.92 | 6.12 | 327.79 | 0.00 | 0.00 |
Minimum of Months | 0.82 | 61.04 | 141.53 | 0.00 | 141.53 | 0.00 | 0.00 |
Maximum of Months | 744.34 | 1234.27 | 520.06 | 27.66 | 492.40 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 205.55 | 780.50 | 324.00 | 151.11 | 172.89 | 0.00 | 0.00 |
February | 330.42 | 762.03 | 471.16 | 236.36 | 234.80 | 0.00 | 0.00 |
March | 499.79 | 540.85 | 544.82 | 230.57 | 314.24 | 0.00 | 0.00 |
April | 660.98 | 374.08 | 595.81 | 234.62 | 361.18 | 0.00 | 0.00 |
May | 906.20 | 219.29 | 686.63 | 229.43 | 457.20 | 0.00 | 0.00 |
June | 1014.31 | 104.83 | 648.01 | 192.78 | 455.23 | 0.00 | 0.00 |
July | 1135.27 | 46.67 | 650.99 | 193.07 | 457.92 | 0.00 | 0.00 |
August | 1247.08 | 67.10 | 736.86 | 294.06 | 442.80 | 0.00 | 0.00 |
September | 885.66 | 149.95 | 590.56 | 251.36 | 339.20 | 0.00 | 0.00 |
October | 762.00 | 309.94 | 600.03 | 285.87 | 314.16 | 0.00 | 0.00 |
November | 346.52 | 530.62 | 388.89 | 166.55 | 222.35 | 0.00 | 0.00 |
December | 235.52 | 696.46 | 329.06 | 176.76 | 152.30 | 0.00 | 0.00 |
Annual Sum or Average | 688.24 | 379.74 | 547.77 | 220.18 | 327.59 | 0.00 | 0.00 |
Minimum of Months | 205.55 | 46.67 | 324.00 | 151.11 | 152.30 | 0.00 | 0.00 |
Maximum of Months | 1247.08 | 780.50 | 736.86 | 294.06 | 457.92 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 398.11 | 837.87 | 505.43 | 295.17 | 210.26 | 0.00 | 0.00 |
February | 548.87 | 828.40 | 671.39 | 395.63 | 275.75 | 0.00 | 0.00 |
March | 579.88 | 583.84 | 632.99 | 290.34 | 342.65 | 0.00 | 0.00 |
April | 544.01 | 407.41 | 546.86 | 170.37 | 376.49 | 0.00 | 0.00 |
May | 592.95 | 231.30 | 529.55 | 80.00 | 449.55 | 0.00 | 0.00 |
June | 699.26 | 111.81 | 518.74 | 61.94 | 456.80 | 0.00 | 0.00 |
July | 805.33 | 48.11 | 527.29 | 66.54 | 460.75 | 0.00 | 0.00 |
August | 956.13 | 76.62 | 627.51 | 177.07 | 450.44 | 0.00 | 0.00 |
September | 811.35 | 175.53 | 615.93 | 251.47 | 364.47 | 0.00 | 0.00 |
October | 960.27 | 351.09 | 807.22 | 443.72 | 363.51 | 0.00 | 0.00 |
November | 520.72 | 570.82 | 559.84 | 293.91 | 265.93 | 0.00 | 0.00 |
December | 456.94 | 747.97 | 534.48 | 345.16 | 189.32 | 0.00 | 0.00 |
Annual Sum or Average | 657.17 | 411.90 | 589.42 | 238.48 | 350.94 | 0.00 | 0.00 |
Minimum of Months | 398.11 | 48.11 | 505.43 | 61.94 | 189.32 | 0.00 | 0.00 |
Maximum of Months | 960.27 | 837.87 | 807.22 | 443.72 | 460.75 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.159900E+10 | 0.167283E+10 | 0.163216E+10 | 0.107105E+10 | 0.561115E+09 | 0.00 | 0.00 |
February | 0.194999E+10 | 0.149724E+10 | 0.195097E+10 | 0.129667E+10 | 0.654301E+09 | 0.00 | 0.00 |
March | 0.203597E+10 | 0.117880E+10 | 0.191376E+10 | 0.105350E+10 | 0.860258E+09 | 0.00 | 0.00 |
April | 0.165777E+10 | 0.804192E+09 | 0.147416E+10 | 0.596411E+09 | 0.877753E+09 | 0.00 | 0.00 |
May | 0.160325E+10 | 0.474979E+09 | 0.130833E+10 | 0.267862E+09 | 0.104047E+10 | 0.00 | 0.00 |
June | 0.168734E+10 | 0.219483E+09 | 0.119554E+10 | 0.184207E+09 | 0.101133E+10 | 0.00 | 0.00 |
July | 0.199965E+10 | 95747192.21 | 0.128543E+10 | 0.216954E+09 | 0.106847E+10 | 0.00 | 0.00 |
August | 0.264186E+10 | 0.170384E+09 | 0.172171E+10 | 0.635122E+09 | 0.108658E+10 | 0.00 | 0.00 |
September | 0.240196E+10 | 0.351658E+09 | 0.175826E+10 | 0.882798E+09 | 0.875461E+09 | 0.00 | 0.00 |
October | 0.322278E+10 | 0.748256E+09 | 0.256754E+10 | 0.161007E+10 | 0.957474E+09 | 0.00 | 0.00 |
November | 0.183869E+10 | 0.112182E+10 | 0.172050E+10 | 0.103208E+10 | 0.688421E+09 | 0.00 | 0.00 |
December | 0.180431E+10 | 0.150438E+10 | 0.176337E+10 | 0.125244E+10 | 0.510933E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.244426E+11 | 0.983977E+10 | 0.202917E+11 | 0.100992E+11 | 0.101926E+11 | 0.00 | 0.00 |
Minimum of Months | 0.159900E+10 | 95747192.21 | 0.119554E+10 | 0.184207E+09 | 0.510933E+09 | 0.00 | 0.00 |
Maximum of Months | 0.322278E+10 | 0.167283E+10 | 0.256754E+10 | 0.161007E+10 | 0.108658E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.444565E+10 | 0.486887E+10 | 0.459606E+10 | 0.301600E+10 | 0.158006E+10 | 0.00 | 0.00 |
February | 0.541934E+10 | 0.437077E+10 | 0.549380E+10 | 0.365134E+10 | 0.184247E+10 | 0.00 | 0.00 |
March | 0.565500E+10 | 0.353511E+10 | 0.538903E+10 | 0.296660E+10 | 0.242243E+10 | 0.00 | 0.00 |
April | 0.458481E+10 | 0.246230E+10 | 0.415115E+10 | 0.167946E+10 | 0.247169E+10 | 0.00 | 0.00 |
May | 0.439660E+10 | 0.151679E+10 | 0.368418E+10 | 0.754282E+09 | 0.292990E+10 | 0.00 | 0.00 |
June | 0.467160E+10 | 0.720470E+09 | 0.336655E+10 | 0.518716E+09 | 0.284784E+10 | 0.00 | 0.00 |
July | 0.556732E+10 | 0.329009E+09 | 0.361968E+10 | 0.610929E+09 | 0.300875E+10 | 0.00 | 0.00 |
August | 0.738558E+10 | 0.531604E+09 | 0.484821E+10 | 0.178846E+10 | 0.305975E+10 | 0.00 | 0.00 |
September | 0.668734E+10 | 0.112998E+10 | 0.495114E+10 | 0.248590E+10 | 0.246524E+10 | 0.00 | 0.00 |
October | 0.898365E+10 | 0.230650E+10 | 0.723002E+10 | 0.453384E+10 | 0.269618E+10 | 0.00 | 0.00 |
November | 0.509282E+10 | 0.336598E+10 | 0.484482E+10 | 0.290627E+10 | 0.193855E+10 | 0.00 | 0.00 |
December | 0.501514E+10 | 0.442699E+10 | 0.496554E+10 | 0.352678E+10 | 0.143875E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.679048E+11 | 0.295644E+11 | 0.571402E+11 | 0.284386E+11 | 0.287016E+11 | 0.00 | 0.00 |
Minimum of Months | 0.439660E+10 | 0.329009E+09 | 0.336655E+10 | 0.518716E+09 | 0.143875E+10 | 0.00 | 0.00 |
Maximum of Months | 0.898365E+10 | 0.486887E+10 | 0.723002E+10 | 0.453384E+10 | 0.305975E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.586544E+10 | 0.663093E+10 | 0.597055E+10 | 0.391796E+10 | 0.205259E+10 | 0.00 | 0.00 |
February | 0.717219E+10 | 0.590589E+10 | 0.713676E+10 | 0.474329E+10 | 0.239347E+10 | 0.00 | 0.00 |
March | 0.749064E+10 | 0.478705E+10 | 0.700065E+10 | 0.385378E+10 | 0.314688E+10 | 0.00 | 0.00 |
April | 0.607013E+10 | 0.335753E+10 | 0.539258E+10 | 0.218171E+10 | 0.321087E+10 | 0.00 | 0.00 |
May | 0.581625E+10 | 0.207246E+10 | 0.478596E+10 | 0.979855E+09 | 0.380610E+10 | 0.00 | 0.00 |
June | 0.619824E+10 | 0.968160E+09 | 0.437334E+10 | 0.673841E+09 | 0.369950E+10 | 0.00 | 0.00 |
July | 0.741371E+10 | 0.432595E+09 | 0.470217E+10 | 0.793632E+09 | 0.390854E+10 | 0.00 | 0.00 |
August | 0.983244E+10 | 0.685046E+09 | 0.629810E+10 | 0.232331E+10 | 0.397479E+10 | 0.00 | 0.00 |
September | 0.886179E+10 | 0.150258E+10 | 0.643181E+10 | 0.322933E+10 | 0.320249E+10 | 0.00 | 0.00 |
October | 0.119055E+11 | 0.305548E+10 | 0.939221E+10 | 0.588972E+10 | 0.350250E+10 | 0.00 | 0.00 |
November | 0.671925E+10 | 0.458863E+10 | 0.629370E+10 | 0.377541E+10 | 0.251828E+10 | 0.00 | 0.00 |
December | 0.661722E+10 | 0.603085E+10 | 0.645052E+10 | 0.458149E+10 | 0.186902E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.899628E+11 | 0.400172E+11 | 0.742284E+11 | 0.369433E+11 | 0.372850E+11 | 0.00 | 0.00 |
Minimum of Months | 0.581625E+10 | 0.432595E+09 | 0.437334E+10 | 0.673841E+09 | 0.186902E+10 | 0.00 | 0.00 |
Maximum of Months | 0.119055E+11 | 0.663093E+10 | 0.939221E+10 | 0.588972E+10 | 0.397479E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.423336E+09 | 0.982682E+09 | 0.562551E+09 | 0.310227E+09 | 0.252324E+09 | 0.00 | 0.00 |
February | 0.554893E+09 | 0.882129E+09 | 0.703964E+09 | 0.396032E+09 | 0.307932E+09 | 0.00 | 0.00 |
March | 0.850622E+09 | 0.669185E+09 | 0.901710E+09 | 0.450816E+09 | 0.450894E+09 | 0.00 | 0.00 |
April | 0.891283E+09 | 0.450377E+09 | 0.841513E+09 | 0.352979E+09 | 0.488534E+09 | 0.00 | 0.00 |
May | 0.111050E+10 | 0.257863E+09 | 0.922671E+09 | 0.305369E+09 | 0.617303E+09 | 0.00 | 0.00 |
June | 0.130681E+10 | 96375375.55 | 0.938438E+09 | 0.319752E+09 | 0.618686E+09 | 0.00 | 0.00 |
July | 0.144015E+10 | 24813480.69 | 0.932881E+09 | 0.297952E+09 | 0.634929E+09 | 0.00 | 0.00 |
August | 0.166409E+10 | 59576864.77 | 0.109135E+10 | 0.472774E+09 | 0.618575E+09 | 0.00 | 0.00 |
September | 0.116294E+10 | 0.165933E+09 | 0.864680E+09 | 0.400269E+09 | 0.464411E+09 | 0.00 | 0.00 |
October | 0.124451E+10 | 0.401664E+09 | 0.103777E+10 | 0.576578E+09 | 0.461191E+09 | 0.00 | 0.00 |
November | 0.510777E+09 | 0.649628E+09 | 0.581769E+09 | 0.274641E+09 | 0.307129E+09 | 0.00 | 0.00 |
December | 0.455735E+09 | 0.881215E+09 | 0.569161E+09 | 0.342817E+09 | 0.226344E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.116156E+11 | 0.552144E+10 | 0.994846E+10 | 0.450021E+10 | 0.544825E+10 | 0.00 | 0.00 |
Minimum of Months | 0.423336E+09 | 24813480.69 | 0.562551E+09 | 0.274641E+09 | 0.226344E+09 | 0.00 | 0.00 |
Maximum of Months | 0.166409E+10 | 0.982682E+09 | 0.109135E+10 | 0.576578E+09 | 0.634929E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.136359E+09 | 0.103714E+10 | 0.301930E+09 | 98462657.35 | 0.203467E+09 | 0.00 | 0.00 |
February | 0.208594E+09 | 0.944417E+09 | 0.394962E+09 | 0.139658E+09 | 0.255304E+09 | 0.00 | 0.00 |
March | 0.501519E+09 | 0.674927E+09 | 0.641173E+09 | 0.242523E+09 | 0.398650E+09 | 0.00 | 0.00 |
April | 0.659654E+09 | 0.449927E+09 | 0.687289E+09 | 0.235623E+09 | 0.451665E+09 | 0.00 | 0.00 |
May | 0.976055E+09 | 0.261553E+09 | 0.852616E+09 | 0.259311E+09 | 0.593305E+09 | 0.00 | 0.00 |
June | 0.119996E+10 | 0.113417E+09 | 0.894635E+09 | 0.293574E+09 | 0.601061E+09 | 0.00 | 0.00 |
July | 0.132364E+10 | 33141521.68 | 0.871875E+09 | 0.262595E+09 | 0.609281E+09 | 0.00 | 0.00 |
August | 0.138710E+10 | 67021495.22 | 0.921743E+09 | 0.349469E+09 | 0.572274E+09 | 0.00 | 0.00 |
September | 0.820670E+09 | 0.182015E+09 | 0.641506E+09 | 0.225797E+09 | 0.415709E+09 | 0.00 | 0.00 |
October | 0.695324E+09 | 0.411774E+09 | 0.641335E+09 | 0.258241E+09 | 0.383094E+09 | 0.00 | 0.00 |
November | 0.185860E+09 | 0.670497E+09 | 0.317085E+09 | 70580626.93 | 0.246505E+09 | 0.00 | 0.00 |
December | 0.128423E+09 | 0.935131E+09 | 0.274666E+09 | 95188244.85 | 0.179478E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.822316E+10 | 0.578096E+10 | 0.744082E+10 | 0.253102E+10 | 0.490979E+10 | 0.00 | 0.00 |
Minimum of Months | 0.128423E+09 | 33141521.68 | 0.274666E+09 | 70580626.93 | 0.179478E+09 | 0.00 | 0.00 |
Maximum of Months | 0.138710E+10 | 0.103714E+10 | 0.921743E+09 | 0.349469E+09 | 0.609281E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.248736E+09 | 0.279232E+09 | 0.258114E+09 | 0.169378E+09 | 88736490.59 | 0.00 | 0.00 |
February | 0.288917E+09 | 0.294115E+09 | 0.308532E+09 | 0.205058E+09 | 0.103473E+09 | 0.00 | 0.00 |
March | 0.297308E+09 | 0.256164E+09 | 0.302648E+09 | 0.166604E+09 | 0.136044E+09 | 0.00 | 0.00 |
April | 0.233908E+09 | 0.187937E+09 | 0.233129E+09 | 94317873.29 | 0.138811E+09 | 0.00 | 0.00 |
May | 0.215948E+09 | 0.124498E+09 | 0.206904E+09 | 42360323.35 | 0.164544E+09 | 0.00 | 0.00 |
June | 0.233980E+09 | 65806204.26 | 0.189067E+09 | 29130958.40 | 0.159936E+09 | 0.00 | 0.00 |
July | 0.286107E+09 | 38819954.29 | 0.203282E+09 | 34309663.55 | 0.168973E+09 | 0.00 | 0.00 |
August | 0.392247E+09 | 50873819.56 | 0.272276E+09 | 0.100440E+09 | 0.171837E+09 | 0.00 | 0.00 |
September | 0.354148E+09 | 94983582.66 | 0.278056E+09 | 0.139608E+09 | 0.138449E+09 | 0.00 | 0.00 |
October | 0.482483E+09 | 0.170685E+09 | 0.406038E+09 | 0.254620E+09 | 0.151418E+09 | 0.00 | 0.00 |
November | 0.266398E+09 | 0.244065E+09 | 0.272085E+09 | 0.163216E+09 | 0.108869E+09 | 0.00 | 0.00 |
December | 0.268049E+09 | 0.297191E+09 | 0.278864E+09 | 0.198063E+09 | 80800618.01 | 0.00 | 0.00 |
Annual Sum or Average | 0.356823E+10 | 0.210437E+10 | 0.320900E+10 | 0.159710E+10 | 0.161189E+10 | 0.00 | 0.00 |
Minimum of Months | 0.215948E+09 | 38819954.29 | 0.189067E+09 | 29130958.40 | 80800618.01 | 0.00 | 0.00 |
Maximum of Months | 0.482483E+09 | 0.297191E+09 | 0.406038E+09 | 0.254620E+09 | 0.171837E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 1711418.60 | 0.317225E+09 | 49674962.73 | 0.00 | 49674962.73 | 0.00 | 0.00 |
February | 4608644.77 | 0.290580E+09 | 61399643.62 | 0.00 | 61399643.62 | 0.00 | 0.00 |
March | 32542105.52 | 0.205165E+09 | 94290864.36 | 1963.96 | 94288900.41 | 0.00 | 0.00 |
April | 73859903.85 | 0.129812E+09 | 0.109811E+09 | 452471.34 | 0.109358E+09 | 0.00 | 0.00 |
May | 0.156769E+09 | 70158725.58 | 0.150921E+09 | 5523301.01 | 0.145398E+09 | 0.00 | 0.00 |
June | 0.211844E+09 | 27459322.48 | 0.154082E+09 | 8195407.02 | 0.145887E+09 | 0.00 | 0.00 |
July | 0.254776E+09 | 7049234.19 | 0.154539E+09 | 6031231.87 | 0.148507E+09 | 0.00 | 0.00 |
August | 0.226615E+09 | 15407962.82 | 0.136664E+09 | 1815851.67 | 0.134848E+09 | 0.00 | 0.00 |
September | 0.122424E+09 | 47922714.76 | 99584946.32 | 57893.59 | 99527052.73 | 0.00 | 0.00 |
October | 73413932.84 | 0.114999E+09 | 88983113.67 | 0.00 | 88983113.67 | 0.00 | 0.00 |
November | 17017093.06 | 0.202187E+09 | 60399659.90 | 0.00 | 60399659.90 | 0.00 | 0.00 |
December | 1295952.97 | 0.287436E+09 | 43329787.27 | 0.00 | 43329787.27 | 0.00 | 0.00 |
Annual Sum or Average | 0.117688E+10 | 0.171540E+10 | 0.120368E+10 | 22078120.45 | 0.118160E+10 | 0.00 | 0.00 |
Minimum of Months | 1295952.97 | 7049234.19 | 43329787.27 | 0.00 | 43329787.27 | 0.00 | 0.00 |
Maximum of Months | 0.254776E+09 | 0.317225E+09 | 0.154539E+09 | 8195407.02 | 0.148507E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.424323E+09 | 0.976289E+09 | 0.564229E+09 | 0.308260E+09 | 0.255969E+09 | 0.00 | 0.00 |
February | 0.577545E+09 | 0.870647E+09 | 0.724436E+09 | 0.414096E+09 | 0.310339E+09 | 0.00 | 0.00 |
March | 0.801507E+09 | 0.674048E+09 | 0.859923E+09 | 0.412946E+09 | 0.446977E+09 | 0.00 | 0.00 |
April | 0.891061E+09 | 0.439083E+09 | 0.849316E+09 | 0.362766E+09 | 0.486550E+09 | 0.00 | 0.00 |
May | 0.114790E+10 | 0.250461E+09 | 0.954617E+09 | 0.330301E+09 | 0.624316E+09 | 0.00 | 0.00 |
June | 0.120191E+10 | 91904610.37 | 0.861763E+09 | 0.262942E+09 | 0.598821E+09 | 0.00 | 0.00 |
July | 0.140079E+10 | 23371507.59 | 0.902351E+09 | 0.276256E+09 | 0.626094E+09 | 0.00 | 0.00 |
August | 0.163494E+10 | 55917100.03 | 0.107165E+10 | 0.455479E+09 | 0.616174E+09 | 0.00 | 0.00 |
September | 0.117518E+10 | 0.160018E+09 | 0.876994E+09 | 0.413014E+09 | 0.463980E+09 | 0.00 | 0.00 |
October | 0.119305E+10 | 0.393416E+09 | 0.100181E+10 | 0.542024E+09 | 0.459791E+09 | 0.00 | 0.00 |
November | 0.583706E+09 | 0.643906E+09 | 0.636369E+09 | 0.317881E+09 | 0.318487E+09 | 0.00 | 0.00 |
December | 0.480455E+09 | 0.872507E+09 | 0.587937E+09 | 0.360535E+09 | 0.227402E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.115124E+11 | 0.545157E+10 | 0.989140E+10 | 0.445650E+10 | 0.543490E+10 | 0.00 | 0.00 |
Minimum of Months | 0.424323E+09 | 23371507.59 | 0.564229E+09 | 0.262942E+09 | 0.227402E+09 | 0.00 | 0.00 |
Maximum of Months | 0.163494E+10 | 0.976289E+09 | 0.107165E+10 | 0.542024E+09 | 0.626094E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.124058E+09 | 0.101728E+10 | 0.303607E+09 | 96495417.54 | 0.207112E+09 | 0.00 | 0.00 |
February | 0.206011E+09 | 0.906404E+09 | 0.415434E+09 | 0.157722E+09 | 0.257711E+09 | 0.00 | 0.00 |
March | 0.449631E+09 | 0.675779E+09 | 0.599386E+09 | 0.204653E+09 | 0.394734E+09 | 0.00 | 0.00 |
April | 0.658779E+09 | 0.436535E+09 | 0.695092E+09 | 0.245411E+09 | 0.449682E+09 | 0.00 | 0.00 |
May | 0.101695E+10 | 0.253985E+09 | 0.884562E+09 | 0.284243E+09 | 0.600318E+09 | 0.00 | 0.00 |
June | 0.109915E+10 | 0.106305E+09 | 0.817960E+09 | 0.236764E+09 | 0.581196E+09 | 0.00 | 0.00 |
July | 0.128133E+10 | 31436817.17 | 0.841345E+09 | 0.240899E+09 | 0.600446E+09 | 0.00 | 0.00 |
August | 0.135300E+10 | 63093541.83 | 0.902047E+09 | 0.332174E+09 | 0.569873E+09 | 0.00 | 0.00 |
September | 0.830671E+09 | 0.172829E+09 | 0.653820E+09 | 0.238542E+09 | 0.415277E+09 | 0.00 | 0.00 |
October | 0.642649E+09 | 0.398133E+09 | 0.605381E+09 | 0.223686E+09 | 0.381695E+09 | 0.00 | 0.00 |
November | 0.247221E+09 | 0.652786E+09 | 0.371685E+09 | 0.113821E+09 | 0.257864E+09 | 0.00 | 0.00 |
December | 0.137696E+09 | 0.909975E+09 | 0.293443E+09 | 0.112907E+09 | 0.180536E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.804716E+10 | 0.562454E+10 | 0.738376E+10 | 0.248732E+10 | 0.489644E+10 | 0.00 | 0.00 |
Minimum of Months | 0.124058E+09 | 31436817.17 | 0.293443E+09 | 96495417.54 | 0.180536E+09 | 0.00 | 0.00 |
Maximum of Months | 0.135300E+10 | 0.101728E+10 | 0.902047E+09 | 0.332174E+09 | 0.600446E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.486054E+09 | 0.125546E+10 | 0.666875E+09 | 0.366995E+09 | 0.299880E+09 | 0.00 | 0.00 |
February | 0.610700E+09 | 0.112471E+10 | 0.801514E+09 | 0.444304E+09 | 0.357210E+09 | 0.00 | 0.00 |
March | 0.760992E+09 | 0.867340E+09 | 0.860019E+09 | 0.360988E+09 | 0.499031E+09 | 0.00 | 0.00 |
April | 0.733347E+09 | 0.580335E+09 | 0.743012E+09 | 0.205341E+09 | 0.537671E+09 | 0.00 | 0.00 |
May | 0.887928E+09 | 0.332473E+09 | 0.775251E+09 | 0.103748E+09 | 0.671502E+09 | 0.00 | 0.00 |
June | 0.103463E+10 | 0.148811E+09 | 0.743449E+09 | 80872685.50 | 0.662577E+09 | 0.00 | 0.00 |
July | 0.122950E+10 | 57138370.24 | 0.775239E+09 | 87405170.35 | 0.687834E+09 | 0.00 | 0.00 |
August | 0.138855E+10 | 0.104013E+09 | 0.886007E+09 | 0.221558E+09 | 0.664449E+09 | 0.00 | 0.00 |
September | 0.109096E+10 | 0.245319E+09 | 0.818205E+09 | 0.302616E+09 | 0.515588E+09 | 0.00 | 0.00 |
October | 0.126470E+10 | 0.530310E+09 | 0.107254E+10 | 0.551690E+09 | 0.520848E+09 | 0.00 | 0.00 |
November | 0.643347E+09 | 0.826707E+09 | 0.720378E+09 | 0.353643E+09 | 0.366735E+09 | 0.00 | 0.00 |
December | 0.558776E+09 | 0.112005E+10 | 0.698088E+09 | 0.429149E+09 | 0.268939E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.106895E+11 | 0.719267E+10 | 0.956058E+10 | 0.350831E+10 | 0.605227E+10 | 0.00 | 0.00 |
Minimum of Months | 0.486054E+09 | 57138370.24 | 0.666875E+09 | 80872685.50 | 0.268939E+09 | 0.00 | 0.00 |
Maximum of Months | 0.138855E+10 | 0.125546E+10 | 0.107254E+10 | 0.551690E+09 | 0.687834E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.422221E+09 | 0.977611E+09 | 0.562551E+09 | 0.310227E+09 | 0.252324E+09 | 0.00 | 0.00 |
February | 0.551854E+09 | 0.879107E+09 | 0.703964E+09 | 0.396032E+09 | 0.307932E+09 | 0.00 | 0.00 |
March | 0.843605E+09 | 0.666255E+09 | 0.901710E+09 | 0.450816E+09 | 0.450894E+09 | 0.00 | 0.00 |
April | 0.882994E+09 | 0.447290E+09 | 0.841513E+09 | 0.352979E+09 | 0.488534E+09 | 0.00 | 0.00 |
May | 0.109917E+10 | 0.255842E+09 | 0.922671E+09 | 0.305369E+09 | 0.617303E+09 | 0.00 | 0.00 |
June | 0.129605E+10 | 93963736.31 | 0.938438E+09 | 0.319752E+09 | 0.618686E+09 | 0.00 | 0.00 |
July | 0.143097E+10 | 23004006.53 | 0.932881E+09 | 0.297952E+09 | 0.634929E+09 | 0.00 | 0.00 |
August | 0.165528E+10 | 56594115.04 | 0.109135E+10 | 0.472774E+09 | 0.618575E+09 | 0.00 | 0.00 |
September | 0.115545E+10 | 0.161949E+09 | 0.864680E+09 | 0.400269E+09 | 0.464411E+09 | 0.00 | 0.00 |
October | 0.123664E+10 | 0.396154E+09 | 0.103777E+10 | 0.576578E+09 | 0.461191E+09 | 0.00 | 0.00 |
November | 0.509471E+09 | 0.643481E+09 | 0.581769E+09 | 0.274641E+09 | 0.307129E+09 | 0.00 | 0.00 |
December | 0.455488E+09 | 0.875151E+09 | 0.569161E+09 | 0.342817E+09 | 0.226344E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.115392E+11 | 0.547640E+10 | 0.994846E+10 | 0.450021E+10 | 0.544825E+10 | 0.00 | 0.00 |
Minimum of Months | 0.422221E+09 | 23004006.53 | 0.562551E+09 | 0.274641E+09 | 0.226344E+09 | 0.00 | 0.00 |
Maximum of Months | 0.165528E+10 | 0.977611E+09 | 0.109135E+10 | 0.576578E+09 | 0.634929E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.136980E+09 | 0.103230E+10 | 0.301930E+09 | 98462657.35 | 0.203467E+09 | 0.00 | 0.00 |
February | 0.207973E+09 | 0.942207E+09 | 0.394962E+09 | 0.139658E+09 | 0.255304E+09 | 0.00 | 0.00 |
March | 0.498122E+09 | 0.671351E+09 | 0.641173E+09 | 0.242523E+09 | 0.398650E+09 | 0.00 | 0.00 |
April | 0.653103E+09 | 0.447376E+09 | 0.687289E+09 | 0.235623E+09 | 0.451665E+09 | 0.00 | 0.00 |
May | 0.963327E+09 | 0.262983E+09 | 0.852616E+09 | 0.259311E+09 | 0.593305E+09 | 0.00 | 0.00 |
June | 0.118688E+10 | 0.116365E+09 | 0.894635E+09 | 0.293574E+09 | 0.601061E+09 | 0.00 | 0.00 |
July | 0.131476E+10 | 32838657.83 | 0.871875E+09 | 0.262595E+09 | 0.609281E+09 | 0.00 | 0.00 |
August | 0.138064E+10 | 65198366.67 | 0.921743E+09 | 0.349469E+09 | 0.572274E+09 | 0.00 | 0.00 |
September | 0.814435E+09 | 0.180972E+09 | 0.641506E+09 | 0.225797E+09 | 0.415709E+09 | 0.00 | 0.00 |
October | 0.691788E+09 | 0.406541E+09 | 0.641335E+09 | 0.258241E+09 | 0.383094E+09 | 0.00 | 0.00 |
November | 0.187007E+09 | 0.662735E+09 | 0.317085E+09 | 70580626.93 | 0.246505E+09 | 0.00 | 0.00 |
December | 0.129886E+09 | 0.928110E+09 | 0.274666E+09 | 95188244.85 | 0.179478E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.816490E+10 | 0.574898E+10 | 0.744082E+10 | 0.253102E+10 | 0.490979E+10 | 0.00 | 0.00 |
Minimum of Months | 0.129886E+09 | 32838657.83 | 0.274666E+09 | 70580626.93 | 0.179478E+09 | 0.00 | 0.00 |
Maximum of Months | 0.138064E+10 | 0.103230E+10 | 0.921743E+09 | 0.349469E+09 | 0.609281E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.448794E+09 | 0.509421E+09 | 0.473281E+09 | 0.310573E+09 | 0.162708E+09 | 0.00 | 0.00 |
February | 0.547795E+09 | 0.458050E+09 | 0.565726E+09 | 0.375997E+09 | 0.189730E+09 | 0.00 | 0.00 |
March | 0.574745E+09 | 0.358306E+09 | 0.554938E+09 | 0.305486E+09 | 0.249452E+09 | 0.00 | 0.00 |
April | 0.469906E+09 | 0.238228E+09 | 0.427468E+09 | 0.172942E+09 | 0.254525E+09 | 0.00 | 0.00 |
May | 0.458089E+09 | 0.133385E+09 | 0.379382E+09 | 77672293.27 | 0.301710E+09 | 0.00 | 0.00 |
June | 0.501667E+09 | 45507684.92 | 0.346674E+09 | 53414803.41 | 0.293260E+09 | 0.00 | 0.00 |
July | 0.611867E+09 | 9934721.60 | 0.372740E+09 | 62910526.60 | 0.309830E+09 | 0.00 | 0.00 |
August | 0.799985E+09 | 26878280.93 | 0.499248E+09 | 0.184167E+09 | 0.315081E+09 | 0.00 | 0.00 |
September | 0.704200E+09 | 82575308.60 | 0.509846E+09 | 0.255986E+09 | 0.253861E+09 | 0.00 | 0.00 |
October | 0.930581E+09 | 0.205356E+09 | 0.744515E+09 | 0.466873E+09 | 0.277642E+09 | 0.00 | 0.00 |
November | 0.521032E+09 | 0.339206E+09 | 0.498897E+09 | 0.299274E+09 | 0.199623E+09 | 0.00 | 0.00 |
December | 0.510025E+09 | 0.456201E+09 | 0.511328E+09 | 0.363171E+09 | 0.148157E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.707869E+10 | 0.286305E+10 | 0.588404E+10 | 0.292847E+10 | 0.295558E+10 | 0.00 | 0.00 |
Minimum of Months | 0.448794E+09 | 9934721.60 | 0.346674E+09 | 53414803.41 | 0.148157E+09 | 0.00 | 0.00 |
Maximum of Months | 0.930581E+09 | 0.509421E+09 | 0.744515E+09 | 0.466873E+09 | 0.315081E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 3748008.28 | 0.318052E+10 | 0.434582E+09 | 0.00 | 0.434582E+09 | 0.00 | 0.00 |
February | 20457326.27 | 0.290486E+10 | 0.537155E+09 | 0.00 | 0.537155E+09 | 0.00 | 0.00 |
March | 0.207478E+09 | 0.213172E+10 | 0.824904E+09 | 17181.70 | 0.824887E+09 | 0.00 | 0.00 |
April | 0.532890E+09 | 0.139270E+10 | 0.960679E+09 | 3958449.54 | 0.956721E+09 | 0.00 | 0.00 |
May | 0.120179E+10 | 0.777208E+09 | 0.132034E+10 | 48320648.33 | 0.127202E+10 | 0.00 | 0.00 |
June | 0.170014E+10 | 0.351602E+09 | 0.134799E+10 | 71697591.63 | 0.127629E+10 | 0.00 | 0.00 |
July | 0.201563E+10 | 0.152192E+09 | 0.135198E+10 | 52764286.00 | 0.129922E+10 | 0.00 | 0.00 |
August | 0.176810E+10 | 0.234896E+09 | 0.119561E+10 | 15885994.55 | 0.117972E+10 | 0.00 | 0.00 |
September | 0.946121E+09 | 0.580178E+09 | 0.871220E+09 | 506482.57 | 0.870713E+09 | 0.00 | 0.00 |
October | 0.532962E+09 | 0.124681E+10 | 0.778470E+09 | 0.00 | 0.778470E+09 | 0.00 | 0.00 |
November | 99990078.64 | 0.211146E+10 | 0.528407E+09 | 0.00 | 0.528407E+09 | 0.00 | 0.00 |
December | 3743822.32 | 0.292681E+10 | 0.379071E+09 | 0.00 | 0.379071E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.903305E+10 | 0.179910E+11 | 0.105304E+11 | 0.193151E+09 | 0.103373E+11 | 0.00 | 0.00 |
Minimum of Months | 3743822.32 | 0.152192E+09 | 0.379071E+09 | 0.00 | 0.379071E+09 | 0.00 | 0.00 |
Maximum of Months | 0.201563E+10 | 0.318052E+10 | 0.135198E+10 | 71697591.63 | 0.129922E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 2194742.90 | 0.327390E+10 | 0.434582E+09 | 0.00 | 0.434582E+09 | 0.00 | 0.00 |
February | 16452088.12 | 0.298594E+10 | 0.537155E+09 | 0.00 | 0.537155E+09 | 0.00 | 0.00 |
March | 0.188686E+09 | 0.219710E+10 | 0.824904E+09 | 17181.70 | 0.824887E+09 | 0.00 | 0.00 |
April | 0.506221E+09 | 0.143699E+10 | 0.960679E+09 | 3958449.54 | 0.956721E+09 | 0.00 | 0.00 |
May | 0.116936E+10 | 0.800854E+09 | 0.132034E+10 | 48320648.33 | 0.127202E+10 | 0.00 | 0.00 |
June | 0.167596E+10 | 0.366486E+09 | 0.134799E+10 | 71697591.63 | 0.127629E+10 | 0.00 | 0.00 |
July | 0.199364E+10 | 0.163485E+09 | 0.135198E+10 | 52764286.00 | 0.129922E+10 | 0.00 | 0.00 |
August | 0.174563E+10 | 0.246680E+09 | 0.119561E+10 | 15885994.55 | 0.117972E+10 | 0.00 | 0.00 |
September | 0.924380E+09 | 0.602774E+09 | 0.871220E+09 | 506482.57 | 0.870713E+09 | 0.00 | 0.00 |
October | 0.510085E+09 | 0.128359E+10 | 0.778470E+09 | 0.00 | 0.778470E+09 | 0.00 | 0.00 |
November | 88985251.86 | 0.218194E+10 | 0.528407E+09 | 0.00 | 0.528407E+09 | 0.00 | 0.00 |
December | 2749322.33 | 0.301583E+10 | 0.379071E+09 | 0.00 | 0.379071E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.882434E+10 | 0.185556E+11 | 0.105304E+11 | 0.193151E+09 | 0.103373E+11 | 0.00 | 0.00 |
Minimum of Months | 2194742.90 | 0.163485E+09 | 0.379071E+09 | 0.00 | 0.379071E+09 | 0.00 | 0.00 |
Maximum of Months | 0.199364E+10 | 0.327390E+10 | 0.135198E+10 | 71697591.63 | 0.129922E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.550542E+09 | 0.209048E+10 | 0.867802E+09 | 0.404742E+09 | 0.463060E+09 | 0.00 | 0.00 |
February | 0.799358E+09 | 0.184349E+10 | 0.113982E+10 | 0.571796E+09 | 0.568025E+09 | 0.00 | 0.00 |
March | 0.133865E+10 | 0.144861E+10 | 0.145924E+10 | 0.617570E+09 | 0.841672E+09 | 0.00 | 0.00 |
April | 0.171325E+10 | 0.969622E+09 | 0.154433E+10 | 0.608142E+09 | 0.936188E+09 | 0.00 | 0.00 |
May | 0.242715E+10 | 0.587350E+09 | 0.183908E+10 | 0.614505E+09 | 0.122457E+10 | 0.00 | 0.00 |
June | 0.262908E+10 | 0.271707E+09 | 0.167963E+10 | 0.499674E+09 | 0.117996E+10 | 0.00 | 0.00 |
July | 0.304071E+10 | 0.124991E+09 | 0.174360E+10 | 0.517122E+09 | 0.122648E+10 | 0.00 | 0.00 |
August | 0.334018E+10 | 0.179729E+09 | 0.197360E+10 | 0.787607E+09 | 0.118599E+10 | 0.00 | 0.00 |
September | 0.229562E+10 | 0.388658E+09 | 0.153074E+10 | 0.651522E+09 | 0.879216E+09 | 0.00 | 0.00 |
October | 0.204095E+10 | 0.830156E+09 | 0.160713E+10 | 0.765679E+09 | 0.841447E+09 | 0.00 | 0.00 |
November | 0.898186E+09 | 0.137538E+10 | 0.100801E+10 | 0.431686E+09 | 0.576325E+09 | 0.00 | 0.00 |
December | 0.630817E+09 | 0.186539E+10 | 0.881346E+09 | 0.473426E+09 | 0.407920E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.217045E+11 | 0.119756E+11 | 0.172743E+11 | 0.694347E+10 | 0.103309E+11 | 0.00 | 0.00 |
Minimum of Months | 0.550542E+09 | 0.124991E+09 | 0.867802E+09 | 0.404742E+09 | 0.407920E+09 | 0.00 | 0.00 |
Maximum of Months | 0.334018E+10 | 0.209048E+10 | 0.197360E+10 | 0.787607E+09 | 0.122648E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.106630E+10 | 0.224414E+10 | 0.135374E+10 | 0.790580E+09 | 0.563158E+09 | 0.00 | 0.00 |
February | 0.132783E+10 | 0.200407E+10 | 0.162422E+10 | 0.957120E+09 | 0.667105E+09 | 0.00 | 0.00 |
March | 0.155315E+10 | 0.156377E+10 | 0.169540E+10 | 0.777636E+09 | 0.917766E+09 | 0.00 | 0.00 |
April | 0.141006E+10 | 0.105602E+10 | 0.141746E+10 | 0.441590E+09 | 0.975874E+09 | 0.00 | 0.00 |
May | 0.158817E+10 | 0.619521E+09 | 0.141835E+10 | 0.214283E+09 | 0.120407E+10 | 0.00 | 0.00 |
June | 0.181248E+10 | 0.289801E+09 | 0.134457E+10 | 0.160548E+09 | 0.118402E+10 | 0.00 | 0.00 |
July | 0.215699E+10 | 0.128849E+09 | 0.141229E+10 | 0.178230E+09 | 0.123406E+10 | 0.00 | 0.00 |
August | 0.256090E+10 | 0.205215E+09 | 0.168072E+10 | 0.474253E+09 | 0.120647E+10 | 0.00 | 0.00 |
September | 0.210301E+10 | 0.454979E+09 | 0.159650E+10 | 0.651799E+09 | 0.944698E+09 | 0.00 | 0.00 |
October | 0.257197E+10 | 0.940372E+09 | 0.216206E+10 | 0.118845E+10 | 0.973613E+09 | 0.00 | 0.00 |
November | 0.134970E+10 | 0.147956E+10 | 0.145111E+10 | 0.761817E+09 | 0.689291E+09 | 0.00 | 0.00 |
December | 0.122387E+10 | 0.200337E+10 | 0.143156E+10 | 0.924471E+09 | 0.507087E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.207244E+11 | 0.129897E+11 | 0.185880E+11 | 0.752078E+10 | 0.110672E+11 | 0.00 | 0.00 |
Minimum of Months | 0.106630E+10 | 0.128849E+09 | 0.134457E+10 | 0.160548E+09 | 0.507087E+09 | 0.00 | 0.00 |
Maximum of Months | 0.257197E+10 | 0.224414E+10 | 0.216206E+10 | 0.118845E+10 | 0.123406E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 1.17 | -0.7 | -4.4 | 5.65 | -10.4 | 36.91 | 88.07 | 0.05 |
February | -0.2 | -2.6 | -7.5 | 5.07 | -13.4 | 46.98 | 136.68 | 0.04 |
March | 5.59 | 3.43 | 0.29 | 5.58 | -4.1 | 68.24 | 153.73 | 0.03 |
April | 10.94 | 8.00 | 4.75 | 4.99 | 0.53 | 82.64 | 161.98 | 0.05 |
May | 16.05 | 12.31 | 9.14 | 4.42 | 7.77 | 109.28 | 173.60 | 0.03 |
June | 21.71 | 18.08 | 15.84 | 4.92 | 13.23 | 112.36 | 186.51 | 0.01 |
July | 25.05 | 21.76 | 20.26 | 4.06 | 17.39 | 114.46 | 172.96 | 0.02 |
August | 24.79 | 19.84 | 17.14 | 4.19 | 14.42 | 95.56 | 226.16 | 0.00 |
September | 19.96 | 15.96 | 13.24 | 3.91 | 10.59 | 73.65 | 166.08 | 0.03 |
October | 14.02 | 11.03 | 7.95 | 4.86 | 2.64 | 61.34 | 179.75 | 0.00 |
November | 7.31 | 4.98 | 2.14 | 5.60 | -4.0 | 48.23 | 90.71 | 0.03 |
December | 3.33 | 0.91 | -2.8 | 5.64 | -8.5 | 30.23 | 98.59 | 0.04 |
Annual Sum or Average | 12.55 | 9.49 | 6.43 | 4.91 | 2.28 | 73.48 | 153.05 | 0.03 |
Minimum of Months | -0.2 | -2.6 | -7.5 | 3.91 | -13.4 | 30.23 | 88.07 | 0.00 |
Maximum of Months | 25.05 | 21.76 | 20.26 | 5.65 | 17.39 | 114.46 | 226.16 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.20 | 24-JAN-12:20 | 11.81 | 11.50 | 1.00 | 8.15 | 93.67 | 0.00 |
February | 10.00 | 20-FEB-11:00 | 4.36 | -3.3 | 2.60 | -3.9 | 151.50 | 540.00 |
March | 22.20 | 27-MAR-15:00 | 16.34 | 12.80 | 6.70 | 11.65 | 136.50 | 590.00 |
April | 26.70 | 07-APR-12:00 | 16.40 | 9.40 | 6.20 | 11.65 | 179.00 | 713.50 |
May | 30.00 | 30-MAY-12:00 | 18.00 | 10.60 | 5.20 | 17.39 | 233.50 | 730.00 |
June | 36.70 | 19-JUN-11:00 | 24.28 | 19.40 | 5.20 | 24.83 | 185.00 | 771.50 |
July | 33.90 | 07-JUL-11:00 | 23.31 | 18.90 | 3.60 | 23.82 | 331.00 | 570.00 |
August | 33.90 | 24-AUG-14:00 | 20.23 | 12.80 | 8.80 | 21.61 | 240.00 | 432.00 |
September | 31.10 | 01-SEP-13:00 | 17.34 | 8.30 | 4.60 | 18.46 | 182.00 | 662.00 |
October | 25.00 | 04-OCT-12:00 | 18.54 | 15.00 | 5.20 | 11.27 | 171.50 | 695.00 |
November | 17.80 | 04-NOV-12:20 | 12.57 | 8.50 | 3.60 | 6.15 | 182.50 | 595.67 |
December | 12.20 | 17-DEC-12:20 | 4.65 | -6.1 | 4.27 | -4.7 | 53.17 | 801.67 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.00 | 4.36 | -6.1 | 1.00 | -4.7 | 53.17 | 0.00 | |
Maximum of Months | 36.70 | 24.28 | 19.40 | 8.80 | 24.83 | 331.00 | 801.67 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -12.2 | 02-JAN-04:00 | -13.6 | -19.4 | 2.60 | -30.7 | 0.00 | 0.00 |
February | -13.9 | 06-FEB-02:00 | -15.3 | -22.8 | 7.20 | -34.1 | 0.00 | 0.00 |
March | -5.0 | 23-MAR-03:00 | -7.6 | -14.4 | 1.50 | -23.9 | 0.00 | 0.00 |
April | 2.20 | 01-APR-03:00 | 0.57 | -1.7 | 3.10 | -6.6 | 0.00 | 0.00 |
May | 6.10 | 01-MAY-04:00 | 4.33 | 2.20 | 3.60 | -9.7 | 25.50 | 0.00 |
June | 13.30 | 03-JUN-02:00 | 9.35 | 5.60 | 4.60 | -2.1 | 0.00 | 0.00 |
July | 18.30 | 02-JUL-02:00 | 17.54 | 17.20 | 0.00 | 5.33 | 0.00 | 0.00 |
August | 15.00 | 08-AUG-04:00 | 12.47 | 10.60 | 3.10 | 3.06 | 0.00 | 0.00 |
September | 10.00 | 24-SEP-05:00 | 8.56 | 7.20 | 2.60 | -3.4 | 18.50 | 158.50 |
October | 2.20 | 09-OCT-03:00 | 1.71 | 1.10 | 0.00 | -13.7 | 0.00 | 0.00 |
November | -4.4 | 24-NOV-05:00 | -6.2 | -10.0 | 1.50 | -19.7 | 0.00 | 0.00 |
December | -8.3 | 31-DEC-23:00 | -10.6 | -18.9 | 9.30 | -26.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -13.9 | -15.3 | -22.8 | 0.00 | -34.1 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 17.54 | 17.20 | 9.30 | 5.33 | 25.50 | 158.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.93 | 24-JAN-11:00 | 12.20 | 11.70 | 1.50 | 8.15 | 103.00 | 0.00 |
February | 6.67 | 28-FEB-09:00 | 7.20 | 6.10 | 4.10 | 2.01 | 101.50 | 0.00 |
March | 16.99 | 27-MAR-12:00 | 20.60 | 15.00 | 3.60 | 10.50 | 295.50 | 565.50 |
April | 17.70 | 09-APR-10:00 | 21.70 | 15.60 | 4.10 | 14.84 | 244.50 | 281.50 |
May | 20.43 | 31-MAY-12:00 | 26.10 | 17.80 | 4.10 | 17.03 | 214.00 | 772.00 |
June | 24.96 | 15-JUN-11:00 | 31.10 | 22.80 | 5.20 | 22.47 | 380.00 | 460.00 |
July | 26.10 | 08-JUL-11:00 | 32.20 | 23.90 | 5.20 | 22.47 | 354.00 | 501.50 |
August | 25.84 | 03-AUG-13:00 | 30.00 | 24.40 | 6.20 | 20.57 | 298.00 | 500.00 |
September | 23.57 | 07-SEP-13:00 | 27.20 | 22.20 | 6.20 | 15.02 | 148.00 | 730.50 |
October | 19.76 | 25-OCT-10:00 | 25.00 | 17.20 | 7.70 | 14.84 | 189.00 | 308.50 |
November | 16.10 | 10-NOV-07:00 | 16.10 | 16.10 | 8.20 | 12.98 | 71.50 | 0.00 |
December | 10.26 | 25-DEC-08:00 | 10.60 | 10.00 | 3.60 | 6.15 | 43.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.67 | 7.20 | 6.10 | 1.50 | 2.01 | 43.00 | 0.00 | |
Maximum of Months | 26.10 | 32.20 | 24.40 | 8.20 | 22.47 | 380.00 | 772.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.70 | 18-JAN-15:00 | 12.20 | 11.93 | 14.90 | 8.15 | 22.00 | 2.00 |
February | 6.10 | 28-FEB-10:20 | 7.03 | 6.58 | 3.43 | 1.87 | 109.83 | 0.00 |
March | 15.00 | 27-MAR-12:20 | 18.00 | 16.18 | 3.93 | 10.11 | 271.83 | 611.17 |
April | 15.60 | 09-APR-10:00 | 21.70 | 17.70 | 4.10 | 14.84 | 244.50 | 281.50 |
May | 18.00 | 18-MAY-09:00 | 18.00 | 18.00 | 4.60 | 15.39 | 265.50 | 12.00 |
June | 22.80 | 15-JUN-11:00 | 31.10 | 24.96 | 5.20 | 22.47 | 380.00 | 460.00 |
July | 24.40 | 09-JUL-07:00 | 27.20 | 25.17 | 2.10 | 15.39 | 195.00 | 504.00 |
August | 25.00 | 03-AUG-19:00 | 26.10 | 25.32 | 5.70 | 19.35 | 0.00 | 0.00 |
September | 22.20 | 07-SEP-13:00 | 27.20 | 23.57 | 6.20 | 15.02 | 148.00 | 730.50 |
October | 18.30 | 05-OCT-18:00 | 19.40 | 18.62 | 7.70 | 6.55 | 0.00 | 0.00 |
November | 16.10 | 10-NOV-07:00 | 16.10 | 16.10 | 8.20 | 12.98 | 71.50 | 0.00 |
December | 10.00 | 25-DEC-08:00 | 10.60 | 10.26 | 3.60 | 6.15 | 43.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 7.03 | 6.58 | 2.10 | 1.87 | 0.00 | 0.00 | |
Maximum of Months | 25.00 | 31.10 | 25.32 | 14.90 | 22.47 | 380.00 | 730.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 10.03 | 13.58 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 9.54 | 21.42 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 10.65 | 30.29 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 13.15 | 37.02 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 16.36 | 45.86 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 19.42 | 49.74 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 21.50 | 48.12 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 22.05 | 49.54 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 20.89 | 34.71 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 18.36 | 29.93 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 15.14 | 17.00 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 12.10 | 12.41 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 15.80 | 32.53 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 9.54 | 12.41 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 22.05 | 49.74 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH LAUNDRY G WATER HEATER
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.123935E+12 | -0.122162E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.177279E+10 | 82.17 | 0.00 | 0.00 |
February | 0.112702E+12 | -0.111090E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.161196E+10 | 82.17 | 0.00 | 0.00 |
March | 0.122902E+12 | -0.121107E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.179518E+10 | 82.17 | 0.00 | 0.00 |
April | 0.114857E+12 | -0.113114E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.174318E+10 | 82.17 | 0.00 | 0.00 |
May | 0.113251E+12 | -0.111445E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.180567E+10 | 82.17 | 0.00 | 0.00 |
June | 0.104567E+12 | -0.102832E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.173546E+10 | 82.17 | 0.00 | 0.00 |
July | 0.104513E+12 | -0.102732E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.178142E+10 | 82.17 | 0.00 | 0.00 |
August | 0.103577E+12 | -0.101808E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.176895E+10 | 82.17 | 0.00 | 0.00 |
September | 0.102121E+12 | -0.100418E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.170304E+10 | 82.17 | 0.00 | 0.00 |
October | 0.109811E+12 | -0.108054E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175671E+10 | 82.17 | 0.00 | 0.00 |
November | 0.111544E+12 | -0.109844E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.170014E+10 | 82.17 | 0.00 | 0.00 |
December | 0.120416E+12 | -0.118654E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.176129E+10 | 82.17 | 0.00 | 0.00 |
Annual Sum or Average | 0.134420E+13 | -0.132326E+13 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.209358E+11 | 82.17 | 0.00 | 0.00 |
Minimum of Months | 0.102121E+12 | -0.122162E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.180567E+10 | 82.17 | 0.00 | 0.00 |
Maximum of Months | 0.123935E+12 | -0.100418E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.161196E+10 | 82.17 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.804794E+10 | -0.788296E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164975235.8 | 82.17 | 0.00 | 0.00 |
February | 0.727240E+10 | -0.712336E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -149035961.0 | 82.17 | 0.00 | 0.00 |
March | 0.804631E+10 | -0.788155E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164755547.0 | 82.17 | 0.00 | 0.00 |
April | 0.779748E+10 | -0.763820E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -159276226.7 | 82.17 | 0.00 | 0.00 |
May | 0.804737E+10 | -0.788296E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164407912.7 | 82.17 | 0.00 | 0.00 |
June | 0.778869E+10 | -0.762976E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -158926405.2 | 82.17 | 0.00 | 0.00 |
July | 0.805558E+10 | -0.789140E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164181288.2 | 82.17 | 0.00 | 0.00 |
August | 0.804711E+10 | -0.788296E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164144382.7 | 82.17 | 0.00 | 0.00 |
September | 0.779860E+10 | -0.763961E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -158990696.7 | 82.17 | 0.00 | 0.00 |
October | 0.804604E+10 | -0.788155E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164481865.8 | 82.17 | 0.00 | 0.00 |
November | 0.778075E+10 | -0.762132E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -159433058.3 | 82.17 | 0.00 | 0.00 |
December | 0.805628E+10 | -0.789140E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164876721.1 | 82.17 | 0.00 | 0.00 |
Annual Sum or Average | 0.947845E+11 | -0.928470E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.193749E+10 | 82.17 | 0.00 | 0.00 |
Minimum of Months | 0.727240E+10 | -0.789140E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -164975235.8 | 82.17 | 0.00 | 0.00 |
Maximum of Months | 0.805628E+10 | -0.712336E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -149035961.0 | 82.17 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.745551E+11 | -0.730219E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.153322E+10 | 60.05 | 0.00 | 0.00 |
February | 0.680154E+11 | -0.666157E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.139971E+10 | 60.05 | 0.00 | 0.00 |
March | 0.737397E+11 | -0.721754E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.156425E+10 | 60.05 | 0.00 | 0.00 |
April | 0.678013E+11 | -0.662793E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.152198E+10 | 60.05 | 0.00 | 0.00 |
May | 0.653804E+11 | -0.638016E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.157879E+10 | 60.05 | 0.00 | 0.00 |
June | 0.589417E+11 | -0.574304E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.151128E+10 | 60.05 | 0.00 | 0.00 |
July | 0.577877E+11 | -0.562425E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.154518E+10 | 60.05 | 0.00 | 0.00 |
August | 0.570303E+11 | -0.555024E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.152789E+10 | 60.05 | 0.00 | 0.00 |
September | 0.567849E+11 | -0.553185E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.146634E+10 | 60.05 | 0.00 | 0.00 |
October | 0.623488E+11 | -0.608379E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.151092E+10 | 60.05 | 0.00 | 0.00 |
November | 0.648918E+11 | -0.634295E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.146232E+10 | 60.05 | 0.00 | 0.00 |
December | 0.715056E+11 | -0.699883E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.151727E+10 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.778783E+12 | -0.760643E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.181392E+11 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.567849E+11 | -0.730219E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.157879E+10 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.745551E+11 | -0.553185E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.139971E+10 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: LOBBY_FLR_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.87 | 0.86 | 01-JAN-07:49 | 5694.58 | 37.00 | 196.83 | 248.33 | 2718.13 | 33.79 | 187.50 | 189.50 |
February | 216.00 | 0.87 | 0.86 | 01-FEB-07:49 | 8334.64 | 37.62 | 208.33 | 259.83 | 1179.82 | 27.28 | 206.00 | 227.00 |
March | 275.00 | 0.87 | 0.86 | 01-MAR-06:00 | 4026.69 | 25.76 | 162.17 | 328.17 | 729.60 | 22.65 | 208.67 | 261.83 |
April | 261.17 | 0.87 | 0.86 | 01-APR-14:39 | 1431.16 | 20.47 | 81.00 | 345.00 | 583.09 | 22.20 | 202.83 | 280.17 |
May | 372.00 | 0.87 | 0.86 | 01-MAY-06:19 | 1294.96 | 20.18 | 114.83 | 396.83 | 514.01 | 21.90 | 242.83 | 318.33 |
June | 351.83 | 0.87 | 0.86 | 01-JUN-06:10 | 1228.03 | 20.09 | 86.83 | 387.33 | 495.41 | 21.83 | 248.67 | 320.50 |
July | 365.17 | 0.87 | 0.86 | 01-JUL-06:30 | 1369.18 | 20.25 | 118.50 | 396.33 | 542.04 | 21.98 | 266.33 | 324.33 |
August | 389.17 | 0.87 | 0.86 | 01-AUG-06:30 | 1466.15 | 20.53 | 150.33 | 375.17 | 593.16 | 22.25 | 307.50 | 324.00 |
September | 285.33 | 0.87 | 0.86 | 01-SEP-06:49 | 1631.60 | 20.64 | 94.17 | 328.33 | 658.47 | 22.41 | 235.83 | 275.33 |
October | 305.50 | 0.87 | 0.86 | 01-OCT-14:39 | 8052.62 | 35.71 | 283.00 | 309.83 | 1008.39 | 24.98 | 277.00 | 281.83 |
November | 240.83 | 0.87 | 0.86 | 01-NOV-06:00 | 5649.86 | 36.45 | 235.00 | 259.83 | 1499.51 | 29.91 | 223.33 | 229.33 |
December | 211.17 | 0.87 | 0.86 | 01-DEC-07:40 | 5289.17 | 37.98 | 208.00 | 248.17 | 4085.39 | 37.96 | 207.00 | 208.17 |
Annual Sum or Average | 3472.67 | 0.87 | 3399.41 | 26.35 | 1939.00 | 3883.17 | 1055.12 | 24.89 | 2813.50 | 3240.33 | ||
Minimum of Months | 199.50 | 0.87 | 0.86 | 1228.03 | 20.09 | 81.00 | 248.17 | 495.41 | 21.83 | 187.50 | 189.50 | |
Maximum of Months | 389.17 | 0.87 | 0.86 | 8334.64 | 37.98 | 283.00 | 396.83 | 4085.39 | 37.96 | 307.50 | 324.33 |
Report: DaylightingReportMonthly
For: CAFE_FLR_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.26 | 0.22 | 01-JAN-07:49 | 6123.40 | 37.06 | 197.00 | 260.17 | 3147.61 | 33.75 | 189.67 | 220.33 |
February | 216.00 | 0.25 | 0.22 | 01-FEB-07:40 | 8825.32 | 37.70 | 208.33 | 269.33 | 1670.07 | 26.97 | 194.50 | 246.33 |
March | 275.00 | 0.26 | 0.22 | 01-MAR-06:00 | 4427.71 | 25.90 | 154.50 | 337.00 | 1128.99 | 22.67 | 217.67 | 307.00 |
April | 261.17 | 0.26 | 0.22 | 01-APR-14:39 | 1741.13 | 20.78 | 87.00 | 357.83 | 892.29 | 22.36 | 238.67 | 319.83 |
May | 372.00 | 0.26 | 0.22 | 01-MAY-05:49 | 1517.86 | 20.78 | 151.67 | 411.83 | 736.12 | 22.30 | 272.50 | 371.17 |
June | 351.83 | 0.26 | 0.22 | 01-JUN-05:30 | 1441.17 | 20.70 | 150.67 | 404.50 | 707.84 | 22.25 | 280.33 | 361.17 |
July | 365.17 | 0.26 | 0.22 | 01-JUL-05:40 | 1596.16 | 20.84 | 166.83 | 413.67 | 768.20 | 22.39 | 294.33 | 366.50 |
August | 389.17 | 0.27 | 0.22 | 01-AUG-05:00 | 1752.43 | 20.92 | 180.67 | 384.50 | 878.61 | 22.48 | 320.67 | 357.67 |
September | 285.33 | 0.26 | 0.22 | 01-SEP-06:19 | 1989.65 | 20.83 | 105.00 | 340.00 | 1015.53 | 22.46 | 235.33 | 307.33 |
October | 305.50 | 0.25 | 0.22 | 01-OCT-14:39 | 8542.75 | 35.76 | 273.33 | 317.17 | 1496.97 | 24.83 | 283.33 | 299.67 |
November | 240.83 | 0.25 | 0.22 | 01-NOV-06:49 | 6049.70 | 36.52 | 235.00 | 267.83 | 1895.80 | 29.83 | 228.83 | 250.17 |
December | 211.17 | 0.26 | 0.22 | 01-DEC-07:30 | 5715.74 | 38.04 | 208.00 | 256.67 | 4510.05 | 37.97 | 204.67 | 233.17 |
Annual Sum or Average | 3472.67 | 0.26 | 3737.26 | 26.65 | 2118.00 | 4020.50 | 1391.88 | 25.02 | 2960.50 | 3640.33 | ||
Minimum of Months | 199.50 | 0.25 | 0.22 | 1441.17 | 20.70 | 87.00 | 256.67 | 707.84 | 22.25 | 189.67 | 220.33 | |
Maximum of Months | 389.17 | 0.27 | 0.22 | 8825.32 | 38.04 | 273.33 | 413.67 | 4510.05 | 37.97 | 320.67 | 371.17 |
Report: DaylightingReportMonthly
For: DINING_FLR_6_DAYLCTRL
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.67 | 0.60 | 01-JAN-09:20 | 430.17 | 15.16 | 0.00 | 231.50 | 207.49 | 18.56 | 0.00 | 114.67 |
February | 216.00 | 0.66 | 0.60 | 01-FEB-08:00 | 442.14 | 15.85 | 0.00 | 247.33 | 226.70 | 19.31 | 0.00 | 153.50 |
March | 275.00 | 0.63 | 0.60 | 01-MAR-07:30 | 606.22 | 17.20 | 0.00 | 325.50 | 292.38 | 20.44 | 26.00 | 241.00 |
April | 261.17 | 0.63 | 0.60 | 01-APR-14:39 | 667.96 | 17.80 | 0.00 | 355.67 | 322.14 | 21.02 | 82.50 | 300.00 |
May | 372.00 | 0.61 | 0.60 | 01-MAY-05:49 | 917.32 | 18.49 | 0.00 | 418.17 | 409.80 | 22.38 | 248.67 | 372.33 |
June | 351.83 | 0.61 | 0.60 | 01-JUN-05:10 | 1018.47 | 19.60 | 29.00 | 410.17 | 442.72 | 23.41 | 263.33 | 375.67 |
July | 365.17 | 0.61 | 0.60 | 01-JUL-04:00 | 1023.58 | 18.54 | 0.00 | 419.33 | 441.60 | 23.06 | 270.00 | 376.50 |
August | 389.17 | 0.62 | 0.60 | 01-AUG-05:49 | 811.38 | 18.24 | 0.00 | 387.67 | 375.42 | 21.46 | 221.83 | 355.67 |
September | 285.33 | 0.63 | 0.60 | 01-SEP-06:19 | 612.07 | 17.42 | 0.00 | 334.00 | 299.10 | 20.66 | 49.00 | 270.67 |
October | 305.50 | 0.64 | 0.60 | 01-OCT-14:39 | 553.63 | 16.97 | 0.00 | 302.17 | 283.71 | 20.33 | 0.00 | 245.17 |
November | 240.83 | 0.66 | 0.60 | 01-NOV-07:49 | 483.39 | 15.71 | 0.00 | 248.67 | 226.65 | 19.03 | 0.00 | 153.50 |
December | 211.17 | 0.70 | 0.60 | 01-DEC-09:30 | 340.64 | 14.26 | 0.00 | 219.33 | 171.24 | 17.82 | 0.00 | 70.17 |
Annual Sum or Average | 3472.67 | 0.64 | 703.70 | 17.40 | 29.00 | 3899.50 | 326.33 | 20.95 | 1161.33 | 3028.83 | ||
Minimum of Months | 199.50 | 0.61 | 0.60 | 340.64 | 14.26 | 0.00 | 219.33 | 171.24 | 17.82 | 0.00 | 70.17 | |
Maximum of Months | 389.17 | 0.70 | 0.60 | 1023.58 | 19.60 | 29.00 | 419.33 | 442.72 | 23.41 | 270.00 | 376.50 |
Report: DaylightingReportMonthly
For: BANQUET_FLR_6_DAYLCTRL
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.67 | 0.60 | 01-JAN-09:20 | 430.17 | 15.16 | 0.00 | 231.50 | 207.49 | 18.56 | 0.00 | 114.67 |
February | 216.00 | 0.66 | 0.60 | 01-FEB-08:00 | 442.14 | 15.85 | 0.00 | 247.33 | 226.70 | 19.31 | 0.00 | 153.50 |
March | 275.00 | 0.63 | 0.60 | 01-MAR-07:30 | 606.22 | 17.20 | 0.00 | 325.50 | 292.38 | 20.44 | 26.00 | 241.00 |
April | 261.17 | 0.63 | 0.60 | 01-APR-14:39 | 667.96 | 17.80 | 0.00 | 355.67 | 322.14 | 21.02 | 82.50 | 300.00 |
May | 372.00 | 0.61 | 0.60 | 01-MAY-05:49 | 917.32 | 18.49 | 0.00 | 418.17 | 409.80 | 22.38 | 248.67 | 372.33 |
June | 351.83 | 0.61 | 0.60 | 01-JUN-05:10 | 1018.47 | 19.60 | 29.00 | 410.17 | 442.72 | 23.41 | 263.33 | 375.67 |
July | 365.17 | 0.61 | 0.60 | 01-JUL-04:00 | 1023.58 | 18.54 | 0.00 | 419.33 | 441.60 | 23.06 | 270.00 | 376.50 |
August | 389.17 | 0.62 | 0.60 | 01-AUG-05:49 | 811.38 | 18.24 | 0.00 | 387.67 | 375.42 | 21.46 | 221.83 | 355.67 |
September | 285.33 | 0.63 | 0.60 | 01-SEP-06:19 | 612.07 | 17.42 | 0.00 | 334.00 | 299.10 | 20.66 | 49.00 | 270.67 |
October | 305.50 | 0.64 | 0.60 | 01-OCT-14:39 | 553.63 | 16.97 | 0.00 | 302.17 | 283.71 | 20.33 | 0.00 | 245.17 |
November | 240.83 | 0.66 | 0.60 | 01-NOV-07:49 | 483.39 | 15.71 | 0.00 | 248.67 | 226.65 | 19.03 | 0.00 | 153.50 |
December | 211.17 | 0.70 | 0.60 | 01-DEC-09:30 | 340.64 | 14.26 | 0.00 | 219.33 | 171.24 | 17.82 | 0.00 | 70.17 |
Annual Sum or Average | 3472.67 | 0.64 | 703.70 | 17.40 | 29.00 | 3899.50 | 326.33 | 20.95 | 1161.33 | 3028.83 | ||
Minimum of Months | 199.50 | 0.61 | 0.60 | 340.64 | 14.26 | 0.00 | 219.33 | 171.24 | 17.82 | 0.00 | 70.17 | |
Maximum of Months | 389.17 | 0.70 | 0.60 | 1023.58 | 19.60 | 29.00 | 419.33 | 442.72 | 23.41 | 270.00 | 376.50 |
Report: CoilReportMonthly
For: FLR_3_DOAS HEATING COIL
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.152463E+10 | 5816.73 | 14-JAN-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.172753E+10 | 6407.56 | 06-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.126669E+09 | 2711.17 | 17-MAR-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3493.52 | 0.28 | 08-APR-15:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 13988.00 | 0.29 | 29-MAY-03:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11513.28 | 0.28 | 01-JUN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 21603.60 | 26.11 | 04-JUL-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11270.98 | 4.24 | 09-AUG-04:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 14801.31 | 1.71 | 19-SEP-15:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 9145.81 | 0.29 | 05-OCT-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.137964E+09 | 1720.76 | 24-NOV-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.196715E+09 | 3443.42 | 31-DEC-24:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.371360E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 3493.52 | 0.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.172753E+10 | 6407.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.650983E+11 | 118937.55 | 20-JAN-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.525855E+11 | 121455.65 | 11-FEB-11:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.487206E+11 | 119082.83 | 24-MAR-17:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.677310E+11 | 117134.49 | 21-APR-18:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.293802E+11 | 110049.56 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.538997E+09 | 20773.58 | 01-JUN-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 36674158.58 | 11666.98 | 11-JUL-16:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.342336E+09 | 35019.31 | 20-AUG-13:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.690408E+10 | 73601.54 | 24-SEP-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.445963E+11 | 115393.59 | 18-OCT-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.744521E+11 | 114405.12 | 18-NOV-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.331898E+11 | 119554.11 | 14-DEC-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.423576E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 36674158.58 | 11666.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.744521E+11 | 121455.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.272391E+10 | 2409.67 | 02-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.204865E+10 | 2320.44 | 06-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.136286E+10 | 1613.81 | 17-MAR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.834849E+09 | 1425.81 | 21-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.214365E+09 | 877.31 | 04-MAY-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 27795407.34 | 553.48 | 24-SEP-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.110182E+09 | 767.63 | 29-OCT-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.130125E+10 | 1655.21 | 23-NOV-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.215154E+10 | 1823.23 | 12-DEC-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.107754E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.272391E+10 | 2409.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.104792E+09 | 503.86 | 02-JAN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 67377463.86 | 457.37 | 07-FEB-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 3445183.64 | 252.88 | 17-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 520872.05 | 87.51 | 21-APR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 3307964.08 | 180.03 | 26-NOV-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 35509184.50 | 373.27 | 12-DEC-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.214953E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.104792E+09 | 503.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.100771E+10 | 1086.90 | 02-JAN-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.950326E+09 | 1068.42 | 06-FEB-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.306702E+09 | 685.06 | 18-MAR-10:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 54720392.01 | 447.36 | 03-APR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.207551E+09 | 652.45 | 24-NOV-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.564092E+09 | 697.95 | 31-DEC-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.309110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.100771E+10 | 1086.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.991651E+09 | 788.82 | 02-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.915115E+09 | 800.75 | 06-FEB-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.403102E+09 | 526.84 | 17-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.114384E+09 | 376.23 | 21-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.288291E+09 | 482.22 | 24-NOV-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.684321E+09 | 589.01 | 31-DEC-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.339686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.991651E+09 | 800.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.288146E+09 | 2335.66 | 02-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.279978E+09 | 2335.66 | 06-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.173773E+09 | 1696.16 | 18-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 79586124.42 | 1346.19 | 22-APR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 20763601.52 | 804.55 | 01-MAY-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 408224.62 | 200.66 | 07-JUN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3492539.22 | 327.79 | 18-SEP-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 23370470.40 | 861.17 | 28-OCT-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.139318E+09 | 1744.38 | 24-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.229581E+09 | 1647.52 | 11-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.123842E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.288146E+09 | 2335.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.164678E+10 | 5354.70 | 08-JAN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.875781E+09 | 4656.68 | 27-FEB-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.501871E+09 | 3878.43 | 17-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.264109E+09 | 3590.67 | 21-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 48955783.79 | 2040.10 | 04-MAY-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 483672.90 | 741.54 | 26-SEP-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2902976.30 | 1328.27 | 31-OCT-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.371106E+09 | 3242.60 | 13-NOV-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.108199E+10 | 4718.73 | 12-DEC-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.479399E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.164678E+10 | 5354.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.808715E+09 | 8107.16 | 08-JAN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.336786E+09 | 5965.49 | 27-FEB-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17791564.57 | 3335.78 | 17-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2268165.84 | 864.78 | 21-APR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11107224.11 | 2128.81 | 26-NOV-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.267024E+09 | 5618.52 | 12-DEC-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.808715E+09 | 8107.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.810951E+10 | 8036.59 | 14-JAN-16:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.605777E+10 | 7041.78 | 06-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.221972E+10 | 5574.37 | 17-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.671539E+09 | 4246.49 | 21-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.281533E+10 | 5133.66 | 25-NOV-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.596848E+10 | 6516.09 | 12-DEC-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.258424E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.810951E+10 | 8036.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.483920E+10 | 4689.92 | 02-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.408048E+10 | 4636.64 | 06-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.164907E+10 | 2998.35 | 23-MAR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.500360E+09 | 1941.33 | 21-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 22706842.56 | 1149.96 | 29-OCT-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.169720E+10 | 3022.69 | 23-NOV-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.361201E+10 | 2997.92 | 31-DEC-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.164010E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.483920E+10 | 4689.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.439870E+10 | 6054.56 | 03-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.356650E+10 | 6053.87 | 28-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.166544E+10 | 6052.46 | 16-MAR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.718864E+09 | 5958.41 | 21-APR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 60041292.49 | 5090.80 | 03-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6903275.85 | 4140.86 | 11-JUN-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5380982.41 | 3571.21 | 24-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5805693.64 | 4384.14 | 08-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16223004.50 | 5117.12 | 23-SEP-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.132361E+09 | 5025.98 | 23-OCT-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.193242E+10 | 6046.19 | 25-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.346584E+10 | 6053.66 | 30-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.159745E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 5380982.41 | 3571.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.439870E+10 | 6054.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.525557E+10 | 6037.49 | 03-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.462123E+10 | 6036.79 | 28-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.216963E+10 | 6035.56 | 16-MAR-18:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.836347E+09 | 5949.40 | 21-APR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 61075572.32 | 5686.20 | 03-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3052153.24 | 3010.79 | 05-JUN-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 3291992.97 | 3537.58 | 18-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2985555.43 | 2929.02 | 25-AUG-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 12002671.43 | 5298.29 | 23-SEP-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.244831E+09 | 5039.80 | 26-OCT-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.253982E+10 | 6035.84 | 25-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.438454E+10 | 6036.57 | 30-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.201344E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 2985555.43 | 2929.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.525557E+10 | 6037.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.169096E+11 | 34742.71 | 02-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.166078E+11 | 34779.57 | 06-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.474692E+10 | 33736.20 | 16-MAR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.805264E+09 | 32915.56 | 03-APR-15:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 61211379.65 | 32941.62 | 03-MAY-15:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11444022.45 | 23542.28 | 06-JUN-15:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11026233.48 | 16594.81 | 14-JUL-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 20400089.43 | 21155.29 | 05-AUG-18:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 53434613.41 | 28624.20 | 24-SEP-15:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.272016E+09 | 32926.89 | 19-OCT-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.486391E+10 | 33961.85 | 24-NOV-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.117873E+11 | 34084.47 | 31-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.561503E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 11026233.48 | 16594.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.169096E+11 | 34779.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.437396E+10 | 5933.19 | 03-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.347801E+10 | 5932.47 | 28-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.176517E+10 | 5931.00 | 16-MAR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.731411E+09 | 5842.25 | 21-APR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 64317594.65 | 4985.27 | 19-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3780640.06 | 4349.51 | 08-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1478596.23 | 2058.03 | 18-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 626376.97 | 2725.61 | 07-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 12759315.42 | 4666.83 | 25-SEP-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.142529E+09 | 4306.54 | 22-OCT-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.182164E+10 | 5931.51 | 25-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.342797E+10 | 5932.21 | 30-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.158236E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 626376.97 | 2058.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.437396E+10 | 5933.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.520486E+10 | 5915.86 | 03-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.449313E+10 | 5915.12 | 28-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.227372E+10 | 5913.74 | 16-MAR-18:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.843554E+09 | 5833.09 | 21-APR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 67129673.53 | 5569.72 | 03-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2074473.38 | 3819.48 | 07-JUN-21:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1532434.79 | 2769.02 | 22-JUL-21:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 513512.68 | 1636.13 | 30-AUG-21:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 9138152.21 | 5066.42 | 25-SEP-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.261442E+09 | 5051.88 | 10-OCT-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.232887E+10 | 5914.13 | 25-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.426021E+10 | 5914.89 | 30-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.197462E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 513512.68 | 1636.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.520486E+10 | 5915.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.155551E+10 | 1789.88 | 24-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129025E+10 | 1789.33 | 28-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.649785E+09 | 1789.13 | 17-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.303009E+09 | 1789.47 | 21-APR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 35671249.58 | 1449.93 | 03-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1744319.67 | 1136.97 | 08-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1303115.14 | 876.79 | 18-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1590306.91 | 1042.07 | 29-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 7585774.16 | 1346.77 | 23-SEP-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 91527256.76 | 1212.05 | 23-OCT-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.747222E+09 | 1789.18 | 28-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.126760E+10 | 1789.30 | 11-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.595280E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1303115.14 | 876.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.155551E+10 | 1789.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.181318E+10 | 1783.15 | 24-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.160601E+10 | 1782.61 | 28-FEB-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.810260E+09 | 1782.45 | 08-MAR-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.342831E+09 | 1782.73 | 21-APR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 34953831.54 | 1506.18 | 03-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 632996.85 | 1001.84 | 07-JUN-21:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 809452.33 | 911.33 | 18-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 910314.74 | 830.30 | 01-AUG-06:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 7011462.77 | 1454.99 | 23-SEP-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.146813E+09 | 1729.87 | 29-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.951496E+09 | 1783.22 | 26-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.155326E+10 | 1782.56 | 11-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.726817E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 632996.85 | 830.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.181318E+10 | 1783.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.449400E+10 | 8507.84 | 25-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.322203E+10 | 8509.43 | 28-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.166211E+10 | 8494.39 | 16-MAR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.785447E+09 | 8360.97 | 21-APR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 66884250.57 | 7541.22 | 23-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 7354774.53 | 5254.72 | 01-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6058972.05 | 5076.27 | 11-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6074097.71 | 5270.84 | 08-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 12551676.95 | 6358.14 | 23-SEP-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 86894484.53 | 5713.83 | 06-OCT-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.145052E+10 | 8311.06 | 28-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.323964E+10 | 8509.14 | 30-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.150396E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 6058972.05 | 5076.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.449400E+10 | 8509.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.272158E+09 | 0.236657E+09 | 19261.28 | 27-MAR-13:00 | 12687.11 | 0.02 |
April | 0.00 | 0.00 | 0.216554E+10 | 0.212879E+10 | 20061.39 | 09-APR-10:00 | 13725.63 | 0.11 |
May | 0.00 | 0.00 | 0.900257E+10 | 0.752894E+10 | 31002.32 | 31-MAY-16:57 | 16337.36 | 0.33 |
June | 0.00 | 0.00 | 0.426109E+11 | 0.239468E+11 | 46827.19 | 24-JUN-18:03 | 16314.01 | 0.73 |
July | 0.00 | 0.00 | 0.580827E+11 | 0.325850E+11 | 47936.35 | 28-JUL-08:03 | 17975.05 | 0.79 |
August | 0.00 | 0.00 | 0.468423E+11 | 0.307391E+11 | 42828.29 | 10-AUG-21:51 | 17181.47 | 0.79 |
September | 0.00 | 0.00 | 0.289963E+11 | 0.191326E+11 | 46314.94 | 14-SEP-08:03 | 16585.28 | 0.65 |
October | 0.00 | 0.00 | 0.100098E+11 | 0.575803E+10 | 30540.46 | 03-OCT-15:02 | 16954.39 | 0.31 |
November | 0.00 | 0.00 | 0.209514E+09 | 0.180116E+09 | 7316.39 | 10-NOV-08:00 | 2644.07 | 0.01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.198192E+12 | 0.122236E+12 | 0.31 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.580827E+11 | 0.325850E+11 | 47936.35 | 17975.05 | 0.79 |
Report: CoilReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 54740927.79 | 54740927.79 | 10741.93 | 03-JAN-19:10 | 10741.93 | 0.02 |
February | 0.00 | 0.00 | 66694393.81 | 66694393.81 | 9371.68 | 10-FEB-19:40 | 9371.68 | 0.01 |
March | 0.00 | 0.00 | 0.342005E+10 | 0.338865E+10 | 130872.94 | 27-MAR-16:00 | 130872.94 | 0.08 |
April | 0.00 | 0.00 | 0.344920E+11 | 0.342317E+11 | 214043.04 | 09-APR-10:50 | 140601.39 | 0.21 |
May | 0.00 | 0.00 | 0.127231E+12 | 0.109458E+12 | 299525.23 | 31-MAY-17:17 | 162139.91 | 0.45 |
June | 0.00 | 0.00 | 0.525177E+12 | 0.306567E+12 | 503070.75 | 15-JUN-21:50 | 200447.93 | 0.92 |
July | 0.00 | 0.00 | 0.834222E+12 | 0.440636E+12 | 557291.53 | 27-JUL-21:00 | 211796.25 | 1.00 |
August | 0.00 | 0.00 | 0.672424E+12 | 0.433192E+12 | 587335.46 | 11-AUG-21:53 | 209337.81 | 0.98 |
September | 0.00 | 0.00 | 0.365735E+12 | 0.247697E+12 | 547160.73 | 13-SEP-21:00 | 215159.40 | 0.82 |
October | 0.00 | 0.00 | 0.125858E+12 | 0.805302E+11 | 288660.78 | 05-OCT-19:10 | 121281.97 | 0.43 |
November | 0.00 | 0.00 | 0.344095E+10 | 0.314063E+10 | 65659.86 | 04-NOV-10:45 | 65659.86 | 0.05 |
December | 0.00 | 0.00 | 0.139726E+09 | 0.139726E+09 | 12967.07 | 29-DEC-19:20 | 12967.07 | 0.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.269226E+13 | 0.165910E+13 | 0.42 | |||
Minimum of Months | 0.00 | 0.00 | 54740927.79 | 54740927.79 | 9371.68 | 9371.68 | 0.01 | |
Maximum of Months | 0.00 | 0.00 | 0.834222E+12 | 0.440636E+12 | 587335.46 | 215159.40 | 1.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 57954972.74 | 36758038.35 | 15686.18 | 20-JAN-16:01 | 15686.18 | 0.01 |
February | 0.00 | 0.00 | 0.146236E+09 | 0.117006E+09 | 15683.77 | 17-FEB-16:01 | 15683.77 | 0.02 |
March | 0.00 | 0.00 | 0.929969E+09 | 0.620808E+09 | 15848.06 | 27-MAR-15:01 | 13333.21 | 0.16 |
April | 0.00 | 0.00 | 0.233365E+10 | 0.139099E+10 | 15685.13 | 03-APR-15:01 | 15685.13 | 0.38 |
May | 0.00 | 0.00 | 0.489671E+10 | 0.268489E+10 | 17065.34 | 19-MAY-15:01 | 12159.63 | 0.75 |
June | 0.00 | 0.00 | 0.899425E+10 | 0.480938E+10 | 18282.10 | 27-JUN-08:62 | 11326.94 | 0.93 |
July | 0.00 | 0.00 | 0.109317E+11 | 0.619949E+10 | 18307.59 | 28-JUL-08:61 | 11277.13 | 0.96 |
August | 0.00 | 0.00 | 0.115162E+11 | 0.714515E+10 | 17932.15 | 06-AUG-08:61 | 11596.53 | 0.96 |
September | 0.00 | 0.00 | 0.713952E+10 | 0.382157E+10 | 19796.25 | 22-SEP-18:01 | 10058.60 | 0.89 |
October | 0.00 | 0.00 | 0.475360E+10 | 0.249527E+10 | 17221.67 | 24-OCT-08:62 | 11052.51 | 0.67 |
November | 0.00 | 0.00 | 0.440737E+09 | 0.194355E+09 | 15216.48 | 10-NOV-16:02 | 12862.39 | 0.15 |
December | 0.00 | 0.00 | 73535069.74 | 54459110.45 | 15655.43 | 02-DEC-16:01 | 15655.43 | 0.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.522141E+11 | 0.295701E+11 | 0.50 | |||
Minimum of Months | 0.00 | 0.00 | 57954972.74 | 36758038.35 | 15216.48 | 10058.60 | 0.01 | |
Maximum of Months | 0.00 | 0.00 | 0.115162E+11 | 0.714515E+10 | 19796.25 | 15686.18 | 0.96 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 8434436.35 | 5407460.49 | 12420.22 | 20-JAN-16:01 | 12420.22 | 0.00 |
February | 0.00 | 0.00 | 28293066.84 | 22750529.96 | 14405.25 | 22-FEB-16:01 | 14405.25 | 0.01 |
March | 0.00 | 0.00 | 0.385880E+09 | 0.255228E+09 | 15916.78 | 27-MAR-15:01 | 12501.13 | 0.08 |
April | 0.00 | 0.00 | 0.136765E+10 | 0.742944E+09 | 16307.64 | 27-APR-18:21 | 15173.75 | 0.28 |
May | 0.00 | 0.00 | 0.336155E+10 | 0.170226E+10 | 17510.77 | 31-MAY-21:51 | 13862.74 | 0.58 |
June | 0.00 | 0.00 | 0.643826E+10 | 0.362059E+10 | 19475.28 | 25-JUN-07:51 | 12453.29 | 0.64 |
July | 0.00 | 0.00 | 0.940583E+10 | 0.552739E+10 | 19776.16 | 23-JUL-08:21 | 11227.68 | 0.79 |
August | 0.00 | 0.00 | 0.943812E+10 | 0.582026E+10 | 19636.73 | 12-AUG-08:61 | 12536.59 | 0.80 |
September | 0.00 | 0.00 | 0.420569E+10 | 0.207338E+10 | 18572.47 | 14-SEP-08:51 | 10686.38 | 0.60 |
October | 0.00 | 0.00 | 0.195775E+10 | 0.841869E+09 | 17119.29 | 05-OCT-21:51 | 12068.65 | 0.40 |
November | 0.00 | 0.00 | 87800472.23 | 43153090.80 | 15101.83 | 10-NOV-16:02 | 11545.86 | 0.05 |
December | 0.00 | 0.00 | 5774268.90 | 4164321.67 | 9631.44 | 17-DEC-16:01 | 9631.44 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.366910E+11 | 0.206594E+11 | 0.36 | |||
Minimum of Months | 0.00 | 0.00 | 5774268.90 | 4164321.67 | 9631.44 | 9631.44 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.943812E+10 | 0.582026E+10 | 19776.16 | 15173.75 | 0.80 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 29087784.87 | 29087784.87 | 5688.17 | 31-JAN-14:50 | 5688.17 | 0.00 |
February | 0.00 | 0.00 | 0.247367E+10 | 0.247367E+10 | 27352.19 | 20-FEB-13:30 | 27352.19 | 0.00 |
March | 0.00 | 0.00 | 0.721664E+10 | 0.546446E+10 | 32341.52 | 28-MAR-12:30 | 19911.93 | 0.10 |
April | 0.00 | 0.00 | 0.144535E+11 | 0.773157E+10 | 43697.87 | 07-APR-12:30 | 36132.55 | 0.37 |
May | 0.00 | 0.00 | 0.247764E+11 | 0.937552E+10 | 32887.21 | 30-MAY-12:30 | 20793.66 | 0.79 |
June | 0.00 | 0.00 | 0.394729E+11 | 0.153252E+11 | 35165.22 | 19-JUN-12:40 | 22560.65 | 0.99 |
July | 0.00 | 0.00 | 0.524059E+11 | 0.227802E+11 | 36698.82 | 08-JUL-12:00 | 23827.64 | 1.00 |
August | 0.00 | 0.00 | 0.607843E+11 | 0.319404E+11 | 45576.13 | 16-AUG-12:30 | 36424.50 | 1.00 |
September | 0.00 | 0.00 | 0.460589E+11 | 0.237979E+11 | 50462.89 | 28-SEP-12:30 | 48331.19 | 0.96 |
October | 0.00 | 0.00 | 0.449436E+11 | 0.305079E+11 | 53103.73 | 04-OCT-11:10 | 48839.04 | 0.65 |
November | 0.00 | 0.00 | 0.105908E+11 | 0.733234E+10 | 44184.72 | 02-NOV-12:40 | 44184.72 | 0.19 |
December | 0.00 | 0.00 | 0.371234E+10 | 0.371234E+10 | 31204.56 | 17-DEC-13:30 | 31204.56 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.306918E+12 | 0.160470E+12 | 0.51 | |||
Minimum of Months | 0.00 | 0.00 | 29087784.87 | 29087784.87 | 5688.17 | 5688.17 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.607843E+11 | 0.319404E+11 | 53103.73 | 48839.04 | 1.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.578204E+09 | 0.221455E+09 | 79916.40 | 24-JAN-19:02 | 70463.80 | 0.05 |
February | 0.00 | 0.00 | 0.320595E+09 | 0.202940E+09 | 61825.33 | 25-FEB-09:01 | 61825.33 | 0.03 |
March | 0.00 | 0.00 | 0.440538E+10 | 0.229528E+10 | 84826.39 | 27-MAR-15:01 | 73109.06 | 0.22 |
April | 0.00 | 0.00 | 0.154771E+11 | 0.836482E+10 | 89103.62 | 10-APR-20:41 | 89103.62 | 0.44 |
May | 0.00 | 0.00 | 0.324265E+11 | 0.192774E+11 | 98692.54 | 31-MAY-21:51 | 77597.35 | 0.56 |
June | 0.00 | 0.00 | 0.462180E+11 | 0.286362E+11 | 113186.91 | 25-JUN-07:51 | 71551.75 | 0.57 |
July | 0.00 | 0.00 | 0.641569E+11 | 0.397457E+11 | 115668.94 | 23-JUL-08:21 | 61754.38 | 0.73 |
August | 0.00 | 0.00 | 0.580814E+11 | 0.356936E+11 | 113438.74 | 12-AUG-08:61 | 69408.03 | 0.72 |
September | 0.00 | 0.00 | 0.341977E+11 | 0.196604E+11 | 108054.09 | 14-SEP-08:51 | 60797.93 | 0.53 |
October | 0.00 | 0.00 | 0.191905E+11 | 0.104346E+11 | 99049.42 | 05-OCT-21:51 | 69335.95 | 0.37 |
November | 0.00 | 0.00 | 0.557406E+10 | 0.248006E+10 | 92027.98 | 10-NOV-09:13 | 63951.16 | 0.30 |
December | 0.00 | 0.00 | 0.560618E+09 | 0.364729E+09 | 75753.03 | 25-DEC-09:02 | 75753.03 | 0.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.281187E+12 | 0.167377E+12 | 0.38 | |||
Minimum of Months | 0.00 | 0.00 | 0.320595E+09 | 0.202940E+09 | 61825.33 | 60797.93 | 0.03 | |
Maximum of Months | 0.00 | 0.00 | 0.641569E+11 | 0.397457E+11 | 115668.94 | 89103.62 | 0.73 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 95887284.39 | 59902839.12 | 11729.17 | 19-JAN-09:02 | 11729.17 | 0.02 |
February | 0.00 | 0.00 | 0.163637E+09 | 0.121909E+09 | 14445.96 | 25-FEB-09:01 | 14445.96 | 0.02 |
March | 0.00 | 0.00 | 0.797952E+09 | 0.506017E+09 | 14983.09 | 27-MAR-15:01 | 11658.64 | 0.17 |
April | 0.00 | 0.00 | 0.236917E+10 | 0.135223E+10 | 14448.42 | 03-APR-15:01 | 14448.42 | 0.42 |
May | 0.00 | 0.00 | 0.507178E+10 | 0.282903E+10 | 15617.81 | 19-MAY-15:01 | 11391.07 | 0.77 |
June | 0.00 | 0.00 | 0.850089E+10 | 0.449807E+10 | 16924.46 | 18-JUN-08:61 | 10474.76 | 0.94 |
July | 0.00 | 0.00 | 0.108164E+11 | 0.616650E+10 | 16548.71 | 23-JUL-18:02 | 10710.15 | 0.97 |
August | 0.00 | 0.00 | 0.114265E+11 | 0.707128E+10 | 16486.47 | 06-AUG-08:61 | 10722.70 | 0.98 |
September | 0.00 | 0.00 | 0.720904E+10 | 0.390533E+10 | 18301.64 | 22-SEP-18:01 | 9229.42 | 0.91 |
October | 0.00 | 0.00 | 0.456827E+10 | 0.235030E+10 | 15894.83 | 05-OCT-18:02 | 11195.09 | 0.69 |
November | 0.00 | 0.00 | 0.638564E+09 | 0.311318E+09 | 13909.91 | 11-NOV-09:01 | 12685.39 | 0.19 |
December | 0.00 | 0.00 | 0.181777E+09 | 0.109510E+09 | 13764.06 | 02-DEC-09:02 | 13764.06 | 0.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.518398E+11 | 0.292814E+11 | 0.51 | |||
Minimum of Months | 0.00 | 0.00 | 95887284.39 | 59902839.12 | 11729.17 | 9229.42 | 0.02 | |
Maximum of Months | 0.00 | 0.00 | 0.114265E+11 | 0.707128E+10 | 18301.64 | 14448.42 | 0.98 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 8416216.06 | 2831399.10 | 7033.40 | 19-JAN-09:02 | 5349.43 | 0.01 |
February | 0.00 | 0.00 | 28520597.56 | 17252685.60 | 13434.40 | 25-FEB-09:01 | 13434.40 | 0.01 |
March | 0.00 | 0.00 | 0.307861E+09 | 0.183478E+09 | 14176.06 | 27-MAR-15:01 | 10656.37 | 0.07 |
April | 0.00 | 0.00 | 0.147472E+10 | 0.791850E+09 | 14462.04 | 08-APR-08:51 | 14462.04 | 0.32 |
May | 0.00 | 0.00 | 0.365228E+10 | 0.198081E+10 | 17847.51 | 31-MAY-08:32 | 15294.44 | 0.61 |
June | 0.00 | 0.00 | 0.613585E+10 | 0.335798E+10 | 18499.94 | 20-JUN-08:62 | 14766.57 | 0.65 |
July | 0.00 | 0.00 | 0.921840E+10 | 0.534752E+10 | 18619.74 | 01-JUL-08:32 | 14609.90 | 0.80 |
August | 0.00 | 0.00 | 0.924265E+10 | 0.559061E+10 | 18171.09 | 12-AUG-08:61 | 12234.55 | 0.81 |
September | 0.00 | 0.00 | 0.436277E+10 | 0.224071E+10 | 18151.88 | 06-SEP-08:32 | 14890.19 | 0.63 |
October | 0.00 | 0.00 | 0.193117E+10 | 0.896180E+09 | 16494.35 | 04-OCT-08:51 | 13001.84 | 0.42 |
November | 0.00 | 0.00 | 0.186315E+09 | 80197936.58 | 13401.32 | 04-NOV-08:61 | 12475.07 | 0.07 |
December | 0.00 | 0.00 | 20071195.37 | 8792452.65 | 10294.54 | 17-DEC-09:02 | 10294.54 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.365690E+11 | 0.204982E+11 | 0.37 | |||
Minimum of Months | 0.00 | 0.00 | 8416216.06 | 2831399.10 | 7033.40 | 5349.43 | 0.01 | |
Maximum of Months | 0.00 | 0.00 | 0.924265E+10 | 0.559061E+10 | 18619.74 | 15294.44 | 0.81 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 13965455.42 | 8709236.01 | 4113.51 | 20-JAN-16:01 | 4113.51 | 0.01 |
February | 0.00 | 0.00 | 36499203.31 | 28764599.26 | 4112.90 | 17-FEB-16:01 | 4112.90 | 0.02 |
March | 0.00 | 0.00 | 0.235338E+09 | 0.160084E+09 | 4113.64 | 11-MAR-16:01 | 4113.64 | 0.13 |
April | 0.00 | 0.00 | 0.589561E+09 | 0.363269E+09 | 4260.15 | 09-APR-08:61 | 3221.05 | 0.35 |
May | 0.00 | 0.00 | 0.123823E+10 | 0.722596E+09 | 4508.12 | 19-MAY-15:01 | 3177.83 | 0.70 |
June | 0.00 | 0.00 | 0.230617E+10 | 0.125313E+10 | 4989.75 | 18-JUN-08:61 | 2833.24 | 0.93 |
July | 0.00 | 0.00 | 0.284720E+10 | 0.162900E+10 | 4994.32 | 28-JUL-08:61 | 2794.71 | 0.96 |
August | 0.00 | 0.00 | 0.296218E+10 | 0.183940E+10 | 4970.52 | 06-AUG-08:61 | 2818.43 | 0.96 |
September | 0.00 | 0.00 | 0.175281E+10 | 0.952435E+09 | 5376.05 | 22-SEP-18:01 | 2476.59 | 0.86 |
October | 0.00 | 0.00 | 0.109275E+10 | 0.587003E+09 | 4648.00 | 24-OCT-08:62 | 2645.10 | 0.59 |
November | 0.00 | 0.00 | 84778257.78 | 39836643.41 | 4026.01 | 10-NOV-16:02 | 3276.04 | 0.11 |
December | 0.00 | 0.00 | 14905279.42 | 11716134.54 | 4112.86 | 02-DEC-16:01 | 4112.86 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.131744E+11 | 0.759595E+10 | 0.47 | |||
Minimum of Months | 0.00 | 0.00 | 13965455.42 | 8709236.01 | 4026.01 | 2476.59 | 0.01 | |
Maximum of Months | 0.00 | 0.00 | 0.296218E+10 | 0.183940E+10 | 5376.05 | 4113.64 | 0.96 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 1454395.01 | 770636.45 | 2742.36 | 17-JAN-16:01 | 2742.36 | 0.00 |
February | 0.00 | 0.00 | 4546371.53 | 3525048.60 | 2857.83 | 22-FEB-16:01 | 2857.83 | 0.00 |
March | 0.00 | 0.00 | 90625579.44 | 59907370.66 | 4218.30 | 27-MAR-15:01 | 3246.92 | 0.06 |
April | 0.00 | 0.00 | 0.342900E+09 | 0.193540E+09 | 4289.39 | 27-APR-18:21 | 4105.36 | 0.25 |
May | 0.00 | 0.00 | 0.874306E+09 | 0.471388E+09 | 4732.94 | 31-MAY-21:51 | 3704.12 | 0.55 |
June | 0.00 | 0.00 | 0.172993E+10 | 0.100250E+10 | 5287.43 | 25-JUN-07:51 | 3090.52 | 0.64 |
July | 0.00 | 0.00 | 0.249861E+10 | 0.149177E+10 | 5373.79 | 23-JUL-08:21 | 2726.49 | 0.80 |
August | 0.00 | 0.00 | 0.246806E+10 | 0.154081E+10 | 5309.89 | 12-AUG-08:61 | 3107.17 | 0.80 |
September | 0.00 | 0.00 | 0.104724E+10 | 0.526135E+09 | 5025.35 | 14-SEP-08:51 | 2644.21 | 0.57 |
October | 0.00 | 0.00 | 0.412142E+09 | 0.176167E+09 | 4594.72 | 05-OCT-21:51 | 3099.02 | 0.33 |
November | 0.00 | 0.00 | 13334503.33 | 6738689.52 | 3698.62 | 04-NOV-15:01 | 3551.00 | 0.02 |
December | 0.00 | 0.00 | 682761.12 | 353178.82 | 2325.71 | 17-DEC-16:01 | 2192.05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.948384E+10 | 0.547361E+10 | 0.34 | |||
Minimum of Months | 0.00 | 0.00 | 682761.12 | 353178.82 | 2325.71 | 2192.05 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.249861E+10 | 0.154081E+10 | 5373.79 | 4105.36 | 0.80 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.101517E+10 | 0.773157E+09 | 19451.24 | 10-JAN-16:01 | 19451.24 | 0.08 |
February | 0.00 | 0.00 | 0.151036E+10 | 0.123978E+10 | 19451.72 | 22-FEB-16:01 | 19451.72 | 0.10 |
March | 0.00 | 0.00 | 0.274054E+10 | 0.188983E+10 | 19451.09 | 15-MAR-18:01 | 19451.09 | 0.29 |
April | 0.00 | 0.00 | 0.393129E+10 | 0.233533E+10 | 19444.29 | 11-APR-15:01 | 19444.29 | 0.46 |
May | 0.00 | 0.00 | 0.621515E+10 | 0.323914E+10 | 21294.69 | 19-MAY-15:01 | 15248.09 | 0.76 |
June | 0.00 | 0.00 | 0.108671E+11 | 0.537141E+10 | 24501.13 | 27-JUN-08:62 | 12665.06 | 0.91 |
July | 0.00 | 0.00 | 0.143533E+11 | 0.800836E+10 | 24294.10 | 28-JUL-08:61 | 12799.62 | 0.96 |
August | 0.00 | 0.00 | 0.156212E+11 | 0.986923E+10 | 23610.05 | 06-AUG-08:61 | 13379.14 | 0.96 |
September | 0.00 | 0.00 | 0.114269E+11 | 0.672809E+10 | 26176.50 | 22-SEP-18:01 | 11242.42 | 0.89 |
October | 0.00 | 0.00 | 0.100360E+11 | 0.640330E+10 | 22280.06 | 05-OCT-18:02 | 14449.66 | 0.74 |
November | 0.00 | 0.00 | 0.257825E+10 | 0.156580E+10 | 20500.28 | 10-NOV-09:02 | 14071.61 | 0.35 |
December | 0.00 | 0.00 | 0.173129E+10 | 0.131313E+10 | 19451.44 | 15-DEC-16:01 | 19451.44 | 0.15 |
Annual Sum or Average | 0.00 | 0.00 | 0.820265E+11 | 0.487366E+11 | 0.56 | |||
Minimum of Months | 0.00 | 0.00 | 0.101517E+10 | 0.773157E+09 | 19444.29 | 11242.42 | 0.08 | |
Maximum of Months | 0.00 | 0.00 | 0.156212E+11 | 0.986923E+10 | 26176.50 | 19451.72 | 0.96 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 48560.20 | 180921.21 | 02-JAN-09:04 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 44597.36 | 185828.75 | 06-FEB-09:02 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 26360.80 | 156626.58 | 11-MAR-19:03 |
April | 0.00 | 0.00 | 01-APR-00:10 | 28949.02 | 147593.66 | 02-APR-18:04 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 11166.59 | 102921.98 | 01-MAY-06:20 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 220.67 | 33861.52 | 06-JUN-15:06 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 | 23908.15 | 14-JUL-08:07 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 136.70 | 39732.26 | 24-AUG-19:00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 2704.19 | 73826.71 | 24-SEP-06:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17102.64 | 133080.09 | 27-OCT-18:04 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 37535.08 | 162487.64 | 16-NOV-16:02 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 30082.23 | 169568.87 | 04-DEC-16:02 |
Annual Sum or Average | 0.00 | 20459.01 | ||||
Minimum of Months | 0.00 | 0.00 | 27.73 | 23908.15 | ||
Maximum of Months | 0.00 | 0.00 | 48560.20 | 185828.75 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 1471.11 | 46062.98 | 24-JAN-19:02 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 3029.79 | 63908.18 | 20-FEB-09:03 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 9656.02 | 246399.12 | 27-MAR-15:01 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 32939.85 | 379459.77 | 07-APR-15:03 | 0.00 | 0.00 | 01-APR-00:10 |
May | 84575.83 | 424012.45 | 31-MAY-15:03 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 272363.52 | 654035.43 | 23-JUN-21:52 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 401957.23 | 715440.00 | 24-JUL-21:52 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 339232.64 | 772852.38 | 11-AUG-21:51 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 200508.52 | 658687.52 | 07-SEP-20:00 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 86763.22 | 481376.37 | 03-OCT-15:03 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 11119.03 | 188747.58 | 04-NOV-15:03 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 3624.16 | 62499.93 | 20-DEC-09:02 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 121475.20 | 0.00 | ||||
Minimum of Months | 1471.11 | 46062.98 | 0.00 | 0.00 | ||
Maximum of Months | 401957.23 | 772852.38 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 27153.39 | 57316.47 | 31-JAN-07:20 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 27426.07 | 57394.64 | 09-FEB-07:15 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 26837.75 | 56950.67 | 01-MAR-07:30 |
April | 0.00 | 0.00 | 01-APR-00:10 | 25463.18 | 54540.10 | 03-APR-07:00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 23715.92 | 51383.54 | 01-MAY-06:20 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 22054.39 | 47941.60 | 01-JUN-18:02 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20897.65 | 44445.17 | 03-JUL-06:20 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 20621.82 | 44734.57 | 22-AUG-06:50 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21240.67 | 45448.23 | 29-SEP-06:15 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22610.95 | 49005.97 | 31-OCT-06:20 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 24365.37 | 52672.68 | 30-NOV-07:20 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 26022.28 | 55609.16 | 29-DEC-07:15 |
Annual Sum or Average | 0.00 | 24014.49 | ||||
Minimum of Months | 0.00 | 0.00 | 20621.82 | 44445.17 | ||
Maximum of Months | 0.00 | 0.00 | 27426.07 | 57394.64 |
Report: FanReportMonthly
For: FLR_3_DOAS FAN
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.271000E+10 | 0.69 | 1299.30 | 01-JAN-09:15 | 0.88 |
February | 0.244774E+10 | 0.70 | 1299.30 | 01-FEB-09:02 | 0.88 |
March | 0.271000E+10 | 0.69 | 1299.30 | 01-MAR-09:01 | 0.88 |
April | 0.262258E+10 | 0.69 | 1299.30 | 01-APR-08:62 | 0.88 |
May | 0.271000E+10 | 0.69 | 1299.30 | 01-MAY-15:01 | 0.88 |
June | 0.262258E+10 | 0.69 | 1299.30 | 01-JUN-08:51 | 0.87 |
July | 0.271000E+10 | 0.69 | 1299.30 | 01-JUL-08:51 | 0.87 |
August | 0.271000E+10 | 0.69 | 1299.30 | 01-AUG-06:51 | 0.87 |
September | 0.262258E+10 | 0.69 | 1299.30 | 01-SEP-08:61 | 0.87 |
October | 0.271000E+10 | 0.69 | 1299.30 | 01-OCT-08:62 | 0.87 |
November | 0.262258E+10 | 0.69 | 1299.30 | 01-NOV-08:62 | 0.88 |
December | 0.271000E+10 | 0.69 | 1299.30 | 01-DEC-16:02 | 0.88 |
Annual Sum or Average | 0.319080E+11 | 0.69 | |||
Minimum of Months | 0.244774E+10 | 0.69 | 1299.30 | 0.87 | |
Maximum of Months | 0.271000E+10 | 0.70 | 1299.30 | 0.88 |
Report: FanReportMonthly
For: VAV WITH REHEAT FAN
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.331993E+11 | 0.80 | 18141.53 | 23-JAN-21:10 | 0.99 |
February | 0.299769E+11 | 0.80 | 17784.95 | 23-FEB-21:10 | 0.98 |
March | 0.343334E+11 | 0.81 | 19913.59 | 03-MAR-22:10 | 1.05 |
April | 0.341317E+11 | 0.82 | 24740.85 | 07-APR-21:10 | 1.19 |
May | 0.366405E+11 | 0.84 | 25797.12 | 31-MAY-21:10 | 1.22 |
June | 0.374834E+11 | 0.86 | 26934.80 | 19-JUN-21:10 | 1.25 |
July | 0.399565E+11 | 0.88 | 27689.20 | 10-JUL-21:10 | 1.27 |
August | 0.408370E+11 | 0.89 | 29253.03 | 18-AUG-21:10 | 1.32 |
September | 0.375897E+11 | 0.86 | 30017.28 | 07-SEP-21:10 | 1.34 |
October | 0.374830E+11 | 0.85 | 28691.12 | 05-OCT-21:10 | 1.30 |
November | 0.339939E+11 | 0.82 | 23424.73 | 03-NOV-21:10 | 1.15 |
December | 0.338607E+11 | 0.81 | 19282.08 | 04-DEC-21:10 | 1.03 |
Annual Sum or Average | 0.429486E+12 | 0.84 | |||
Minimum of Months | 0.299769E+11 | 0.80 | 17784.95 | 0.98 | |
Maximum of Months | 0.408370E+11 | 0.89 | 30017.28 | 1.34 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205205E+09 | 0.27 | 76.61 | 01-JAN-00:05 | 0.27 |
February | 0.185347E+09 | 0.27 | 76.61 | 01-FEB-00:03 | 0.27 |
March | 0.205205E+09 | 0.27 | 76.61 | 01-MAR-00:03 | 0.27 |
April | 0.198586E+09 | 0.27 | 76.61 | 01-APR-00:10 | 0.27 |
May | 0.205205E+09 | 0.26 | 76.61 | 01-MAY-00:05 | 0.26 |
June | 0.198586E+09 | 0.26 | 76.61 | 01-JUN-00:05 | 0.26 |
July | 0.205205E+09 | 0.26 | 76.61 | 01-JUL-00:10 | 0.26 |
August | 0.205205E+09 | 0.26 | 76.61 | 01-AUG-00:05 | 0.26 |
September | 0.198586E+09 | 0.26 | 76.61 | 01-SEP-00:05 | 0.26 |
October | 0.205205E+09 | 0.26 | 76.61 | 01-OCT-00:10 | 0.26 |
November | 0.198586E+09 | 0.27 | 76.61 | 01-NOV-00:05 | 0.27 |
December | 0.205205E+09 | 0.27 | 76.61 | 01-DEC-00:03 | 0.27 |
Annual Sum or Average | 0.241613E+10 | 0.27 | |||
Minimum of Months | 0.185347E+09 | 0.26 | 76.61 | 0.26 | |
Maximum of Months | 0.205205E+09 | 0.27 | 76.61 | 0.27 |
Report: FanReportMonthly
For: LOBBY_FLR_1 EXHAUST FAN
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:05 | -0.0 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | -0.0 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | -0.0 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 EXHAUST FAN
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 EXHAUST FAN
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116283E+10 | 0.19 | 612.92 | 01-JAN-07:03 | 0.27 |
February | 0.105030E+10 | 0.19 | 612.92 | 01-FEB-07:05 | 0.27 |
March | 0.116283E+10 | 0.19 | 612.92 | 01-MAR-07:05 | 0.27 |
April | 0.112532E+10 | 0.19 | 612.92 | 01-APR-06:05 | 0.27 |
May | 0.116283E+10 | 0.19 | 612.92 | 01-MAY-06:05 | 0.27 |
June | 0.112532E+10 | 0.19 | 612.92 | 01-JUN-06:05 | 0.26 |
July | 0.116283E+10 | 0.19 | 612.92 | 01-JUL-06:05 | 0.26 |
August | 0.116283E+10 | 0.19 | 612.92 | 01-AUG-06:05 | 0.26 |
September | 0.112532E+10 | 0.19 | 612.92 | 01-SEP-06:05 | 0.26 |
October | 0.116283E+10 | 0.19 | 612.92 | 01-OCT-06:10 | 0.26 |
November | 0.112532E+10 | 0.19 | 612.92 | 01-NOV-06:05 | 0.27 |
December | 0.116283E+10 | 0.19 | 612.92 | 01-DEC-07:05 | 0.27 |
Annual Sum or Average | 0.136914E+11 | 0.19 | |||
Minimum of Months | 0.105030E+10 | 0.19 | 612.92 | 0.26 | |
Maximum of Months | 0.116283E+10 | 0.19 | 612.92 | 0.27 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.344118E+09 | 0.44 | 773.38 | 01-JAN-09:02 | 0.58 |
February | 0.291961E+09 | 0.44 | 773.38 | 01-FEB-09:02 | 0.57 |
March | 0.204330E+09 | 0.44 | 773.38 | 01-MAR-16:01 | 0.58 |
April | 0.188998E+09 | 0.46 | 773.38 | 01-APR-15:02 | 0.57 |
May | 0.241925E+09 | 0.49 | 773.38 | 01-MAY-15:01 | 0.58 |
June | 0.376537E+09 | 0.54 | 773.38 | 01-JUN-08:61 | 0.57 |
July | 0.446211E+09 | 0.55 | 773.38 | 01-JUL-08:61 | 0.57 |
August | 0.492147E+09 | 0.55 | 773.38 | 01-AUG-08:62 | 0.57 |
September | 0.311701E+09 | 0.52 | 773.38 | 01-SEP-08:61 | 0.57 |
October | 0.231746E+09 | 0.50 | 773.38 | 01-OCT-08:62 | 0.57 |
November | 0.196571E+09 | 0.42 | 773.38 | 01-NOV-15:01 | 0.57 |
December | 0.285427E+09 | 0.43 | 773.38 | 01-DEC-19:02 | 0.58 |
Annual Sum or Average | 0.361167E+10 | 0.48 | |||
Minimum of Months | 0.188998E+09 | 0.42 | 773.38 | 0.57 | |
Maximum of Months | 0.492147E+09 | 0.55 | 773.38 | 0.58 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.391366E+09 | 0.45 | 751.63 | 01-JAN-09:02 | 0.58 |
February | 0.354603E+09 | 0.46 | 751.63 | 01-FEB-09:02 | 0.57 |
March | 0.210516E+09 | 0.41 | 751.63 | 01-MAR-09:01 | 0.57 |
April | 0.151022E+09 | 0.41 | 751.63 | 01-APR-08:62 | 0.57 |
May | 0.167191E+09 | 0.38 | 751.63 | 01-MAY-15:01 | 0.58 |
June | 0.267734E+09 | 0.37 | 751.63 | 01-JUN-08:51 | 0.57 |
July | 0.389273E+09 | 0.45 | 751.63 | 01-JUL-08:51 | 0.57 |
August | 0.403628E+09 | 0.46 | 751.63 | 01-AUG-06:51 | 0.57 |
September | 0.182251E+09 | 0.35 | 751.63 | 01-SEP-08:61 | 0.57 |
October | 0.120236E+09 | 0.37 | 751.63 | 01-OCT-08:62 | 0.57 |
November | 0.216869E+09 | 0.40 | 751.63 | 01-NOV-08:62 | 0.57 |
December | 0.332626E+09 | 0.44 | 751.63 | 01-DEC-09:02 | 0.57 |
Annual Sum or Average | 0.318731E+10 | 0.41 | |||
Minimum of Months | 0.120236E+09 | 0.35 | 751.63 | 0.57 | |
Maximum of Months | 0.403628E+09 | 0.46 | 751.63 | 0.58 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 1585141.66 | 0.00 | 288.27 | 31-JAN-14:50 | 0.58 |
February | 0.104608E+09 | 0.07 | 922.53 | 20-FEB-13:30 | 0.58 |
March | 0.293952E+09 | 0.15 | 1085.99 | 03-MAR-13:30 | 0.57 |
April | 0.564306E+09 | 0.28 | 1354.43 | 07-APR-12:30 | 0.57 |
May | 0.962586E+09 | 0.46 | 1044.01 | 30-MAY-12:50 | 0.57 |
June | 0.138200E+10 | 0.57 | 1090.87 | 19-JUN-13:10 | 0.57 |
July | 0.173269E+10 | 0.57 | 1142.31 | 10-JUL-13:00 | 0.57 |
August | 0.200523E+10 | 0.57 | 1418.28 | 30-AUG-12:50 | 0.57 |
September | 0.158664E+10 | 0.55 | 1552.53 | 28-SEP-12:30 | 0.57 |
October | 0.157624E+10 | 0.51 | 2290.41 | 04-OCT-12:00 | 0.57 |
November | 0.419081E+09 | 0.19 | 1380.05 | 06-NOV-12:40 | 0.58 |
December | 0.146967E+09 | 0.07 | 1028.18 | 17-DEC-13:30 | 0.58 |
Annual Sum or Average | 0.107759E+11 | 0.33 | |||
Minimum of Months | 1585141.66 | 0.00 | 288.27 | 0.57 | |
Maximum of Months | 0.200523E+10 | 0.57 | 2290.41 | 0.58 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.143363E+10 | 0.41 | 4341.70 | 01-JAN-16:02 | 0.58 |
February | 0.136781E+10 | 0.41 | 4341.70 | 01-FEB-16:02 | 0.58 |
March | 0.755247E+09 | 0.40 | 4341.70 | 01-MAR-09:01 | 0.57 |
April | 0.846854E+09 | 0.38 | 4341.70 | 01-APR-08:62 | 0.57 |
May | 0.143506E+10 | 0.34 | 4341.70 | 01-MAY-08:62 | 0.57 |
June | 0.195969E+10 | 0.33 | 4341.70 | 01-JUN-08:51 | 0.57 |
July | 0.271803E+10 | 0.42 | 4341.70 | 01-JUL-08:51 | 0.57 |
August | 0.247515E+10 | 0.41 | 4341.70 | 01-AUG-06:51 | 0.57 |
September | 0.143443E+10 | 0.31 | 4341.70 | 01-SEP-08:61 | 0.57 |
October | 0.878190E+09 | 0.33 | 4341.70 | 01-OCT-08:62 | 0.57 |
November | 0.779719E+09 | 0.40 | 4341.70 | 01-NOV-08:62 | 0.57 |
December | 0.111241E+10 | 0.41 | 4341.70 | 01-DEC-16:02 | 0.58 |
Annual Sum or Average | 0.171962E+11 | 0.38 | |||
Minimum of Months | 0.755247E+09 | 0.31 | 4341.70 | 0.57 | |
Maximum of Months | 0.271803E+10 | 0.42 | 4341.70 | 0.58 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.323809E+09 | 0.43 | 711.72 | 01-JAN-16:02 | 0.58 |
February | 0.268553E+09 | 0.43 | 711.72 | 01-FEB-19:02 | 0.58 |
March | 0.194641E+09 | 0.44 | 711.72 | 01-MAR-09:01 | 0.57 |
April | 0.184121E+09 | 0.47 | 711.72 | 01-APR-15:02 | 0.57 |
May | 0.244970E+09 | 0.51 | 711.72 | 01-MAY-08:62 | 0.57 |
June | 0.349101E+09 | 0.54 | 711.72 | 01-JUN-08:61 | 0.57 |
July | 0.436510E+09 | 0.56 | 711.72 | 01-JUL-08:61 | 0.57 |
August | 0.479402E+09 | 0.56 | 711.72 | 01-AUG-08:62 | 0.57 |
September | 0.310186E+09 | 0.53 | 711.72 | 01-SEP-08:61 | 0.57 |
October | 0.221800E+09 | 0.51 | 711.72 | 01-OCT-08:62 | 0.57 |
November | 0.186776E+09 | 0.43 | 711.72 | 01-NOV-08:62 | 0.57 |
December | 0.270807E+09 | 0.43 | 711.72 | 01-DEC-16:02 | 0.58 |
Annual Sum or Average | 0.347068E+10 | 0.49 | |||
Minimum of Months | 0.184121E+09 | 0.43 | 711.72 | 0.57 | |
Maximum of Months | 0.479402E+09 | 0.56 | 711.72 | 0.58 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.370244E+09 | 0.46 | 692.56 | 01-JAN-09:02 | 0.58 |
February | 0.329059E+09 | 0.46 | 692.56 | 01-FEB-09:02 | 0.57 |
March | 0.201114E+09 | 0.41 | 692.56 | 01-MAR-09:01 | 0.57 |
April | 0.150582E+09 | 0.42 | 692.56 | 01-APR-15:02 | 0.57 |
May | 0.181516E+09 | 0.41 | 692.56 | 01-MAY-08:62 | 0.57 |
June | 0.259782E+09 | 0.37 | 692.56 | 01-JUN-08:51 | 0.57 |
July | 0.379553E+09 | 0.46 | 692.56 | 01-JUL-08:32 | 0.57 |
August | 0.389724E+09 | 0.47 | 692.56 | 01-AUG-06:51 | 0.57 |
September | 0.190440E+09 | 0.36 | 692.56 | 01-SEP-08:61 | 0.57 |
October | 0.118825E+09 | 0.37 | 692.56 | 01-OCT-08:62 | 0.57 |
November | 0.195294E+09 | 0.41 | 692.56 | 01-NOV-08:62 | 0.57 |
December | 0.308364E+09 | 0.44 | 692.56 | 01-DEC-16:02 | 0.58 |
Annual Sum or Average | 0.307450E+10 | 0.42 | |||
Minimum of Months | 0.118825E+09 | 0.36 | 692.56 | 0.57 | |
Maximum of Months | 0.389724E+09 | 0.47 | 692.56 | 0.58 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.110274E+09 | 0.46 | 202.89 | 01-JAN-09:02 | 0.58 |
February | 93902991.26 | 0.45 | 202.89 | 01-FEB-09:02 | 0.57 |
March | 63427043.95 | 0.44 | 202.89 | 01-MAR-16:01 | 0.58 |
April | 55514821.26 | 0.46 | 202.89 | 01-APR-08:62 | 0.57 |
May | 63795260.76 | 0.50 | 202.89 | 01-MAY-15:01 | 0.58 |
June | 97670591.25 | 0.54 | 202.89 | 01-JUN-08:61 | 0.57 |
July | 0.117745E+09 | 0.55 | 202.89 | 01-JUL-08:61 | 0.57 |
August | 0.129162E+09 | 0.55 | 202.89 | 01-AUG-08:62 | 0.57 |
September | 77998606.32 | 0.52 | 202.89 | 01-SEP-08:61 | 0.57 |
October | 58887521.89 | 0.49 | 202.89 | 02-OCT-15:01 | 0.57 |
November | 61271197.71 | 0.42 | 202.89 | 01-NOV-15:01 | 0.57 |
December | 89669594.33 | 0.45 | 202.89 | 01-DEC-09:02 | 0.57 |
Annual Sum or Average | 0.101932E+10 | 0.49 | |||
Minimum of Months | 55514821.26 | 0.42 | 202.89 | 0.57 | |
Maximum of Months | 0.129162E+09 | 0.55 | 202.89 | 0.58 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.128262E+09 | 0.49 | 196.78 | 01-JAN-09:02 | 0.58 |
February | 0.114753E+09 | 0.48 | 196.78 | 01-FEB-09:02 | 0.57 |
March | 65021463.02 | 0.42 | 196.78 | 01-MAR-09:01 | 0.57 |
April | 45496511.45 | 0.41 | 196.78 | 01-APR-08:62 | 0.57 |
May | 45469982.66 | 0.39 | 196.78 | 01-MAY-15:01 | 0.58 |
June | 72917916.24 | 0.37 | 196.78 | 01-JUN-08:51 | 0.57 |
July | 0.105112E+09 | 0.46 | 196.78 | 01-JUL-08:51 | 0.57 |
August | 0.107362E+09 | 0.46 | 196.78 | 01-AUG-06:51 | 0.57 |
September | 46111797.35 | 0.35 | 196.78 | 01-SEP-08:61 | 0.57 |
October | 32830915.10 | 0.37 | 196.78 | 02-OCT-15:01 | 0.57 |
November | 69379127.71 | 0.43 | 196.78 | 01-NOV-08:62 | 0.57 |
December | 0.103503E+09 | 0.47 | 196.78 | 01-DEC-09:02 | 0.57 |
Annual Sum or Average | 0.936220E+09 | 0.42 | |||
Minimum of Months | 32830915.10 | 0.35 | 196.78 | 0.57 | |
Maximum of Months | 0.128262E+09 | 0.49 | 196.78 | 0.58 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.374901E+09 | 0.45 | 954.69 | 01-JAN-16:02 | 0.58 |
February | 0.312291E+09 | 0.47 | 954.69 | 01-FEB-16:02 | 0.57 |
March | 0.277716E+09 | 0.47 | 954.69 | 01-MAR-09:01 | 0.57 |
April | 0.256450E+09 | 0.47 | 954.69 | 01-APR-15:02 | 0.57 |
May | 0.289552E+09 | 0.49 | 954.69 | 01-MAY-15:01 | 0.58 |
June | 0.430493E+09 | 0.53 | 954.69 | 01-JUN-08:61 | 0.57 |
July | 0.561582E+09 | 0.55 | 954.69 | 01-JUL-08:61 | 0.57 |
August | 0.647889E+09 | 0.55 | 954.69 | 01-AUG-08:62 | 0.57 |
September | 0.484741E+09 | 0.52 | 954.69 | 01-SEP-08:61 | 0.57 |
October | 0.451426E+09 | 0.52 | 954.69 | 01-OCT-08:62 | 0.57 |
November | 0.252645E+09 | 0.46 | 954.69 | 01-NOV-08:62 | 0.57 |
December | 0.335960E+09 | 0.46 | 954.69 | 01-DEC-16:02 | 0.57 |
Annual Sum or Average | 0.467565E+10 | 0.50 | |||
Minimum of Months | 0.252645E+09 | 0.45 | 954.69 | 0.57 | |
Maximum of Months | 0.647889E+09 | 0.55 | 954.69 | 0.58 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.103400E+10 | 0.930601E+09 | 846.19 | 02-JAN-09:04 | 761.57 | 761.57 | 32.22 | 1.56 |
February | 0.885666E+09 | 0.797099E+09 | 871.39 | 06-FEB-07:10 | 784.25 | 784.25 | 35.57 | 1.68 |
March | 0.600797E+09 | 0.540718E+09 | 804.89 | 11-MAR-19:03 | 724.40 | 724.40 | 32.98 | 1.39 |
April | 0.527456E+09 | 0.474710E+09 | 764.74 | 02-APR-18:04 | 688.26 | 688.26 | 31.73 | 1.25 |
May | 0.193458E+09 | 0.174112E+09 | 675.43 | 01-MAY-06:05 | 607.88 | 607.88 | 42.56 | 1.00 |
June | 4206236.88 | 3785613.19 | 250.66 | 01-JUN-18:07 | 225.59 | 225.59 | 39.35 | 0.28 |
July | 791434.56 | 712291.11 | 217.73 | 18-JUL-08:04 | 195.95 | 195.95 | 36.95 | 0.24 |
August | 3050640.63 | 2745576.56 | 278.98 | 24-AUG-19:00 | 251.08 | 251.08 | 30.22 | 0.32 |
September | 45104599.63 | 40594139.67 | 480.82 | 24-SEP-05:50 | 432.74 | 432.74 | 31.46 | 0.61 |
October | 0.305445E+09 | 0.274901E+09 | 802.07 | 31-OCT-08:07 | 721.87 | 721.87 | 38.48 | 1.37 |
November | 0.739372E+09 | 0.665435E+09 | 806.74 | 16-NOV-16:02 | 726.06 | 726.06 | 32.11 | 1.39 |
December | 0.761904E+09 | 0.685713E+09 | 818.37 | 04-DEC-16:02 | 736.53 | 736.53 | 31.81 | 1.44 |
Annual Sum or Average | 0.510125E+10 | 0.459113E+10 | ||||||
Minimum of Months | 791434.56 | 712291.11 | 217.73 | 195.95 | 195.95 | 30.22 | 0.24 | |
Maximum of Months | 0.103400E+10 | 0.930601E+09 | 871.39 | 784.25 | 784.25 | 42.56 | 1.68 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 585793.45 | 527214.10 | 29.33 | 19-JAN-09:02 | 26.40 | 26.40 | 6.72 | 2.76 |
February | 1653918.52 | 1488526.67 | 53.99 | 20-FEB-09:01 | 48.59 | 48.59 | 6.72 | 3.85 |
March | 9254220.11 | 8328798.10 | 155.01 | 27-MAR-15:01 | 139.51 | 139.51 | 6.72 | 6.57 |
April | 50270667.09 | 45243600.38 | 534.93 | 07-APR-15:13 | 481.44 | 481.44 | 6.72 | 11.65 |
May | 0.140813E+09 | 0.126732E+09 | 501.30 | 31-MAY-15:13 | 451.17 | 451.17 | 6.72 | 11.32 |
June | 0.636406E+09 | 0.572766E+09 | 1151.66 | 19-JUN-18:03 | 1036.49 | 1036.49 | 6.72 | 16.22 |
July | 0.117246E+10 | 0.105522E+10 | 1416.22 | 20-JUL-18:03 | 1274.60 | 1274.60 | 6.72 | 17.68 |
August | 0.101290E+10 | 0.911608E+09 | 1516.07 | 11-AUG-21:00 | 1364.46 | 1364.46 | 6.72 | 18.19 |
September | 0.440158E+09 | 0.396143E+09 | 1398.81 | 07-SEP-20:00 | 1258.93 | 1258.93 | 6.72 | 17.59 |
October | 0.143581E+09 | 0.129223E+09 | 597.64 | 05-OCT-15:03 | 537.87 | 537.87 | 6.72 | 12.23 |
November | 10779652.85 | 9701687.57 | 166.16 | 04-NOV-15:01 | 149.54 | 149.54 | 6.72 | 6.80 |
December | 2260309.57 | 2034278.61 | 53.91 | 17-DEC-09:02 | 48.52 | 48.52 | 6.72 | 3.85 |
Annual Sum or Average | 0.362113E+10 | 0.325901E+10 | ||||||
Minimum of Months | 585793.45 | 527214.10 | 29.33 | 26.40 | 26.40 | 6.72 | 2.76 | |
Maximum of Months | 0.117246E+10 | 0.105522E+10 | 1516.07 | 1364.46 | 1364.46 | 6.72 | 18.19 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.230883E+10 | 0.207795E+10 | 3250.25 | 01-JAN-09:02 | 2925.23 | 2925.23 | 6.73 | 28.75 |
February | 0.282964E+10 | 0.254667E+10 | 3250.25 | 01-FEB-09:02 | 2925.23 | 2925.23 | 6.78 | 28.75 |
March | 0.561631E+10 | 0.505468E+10 | 3250.25 | 01-MAR-00:03 | 2925.23 | 2925.23 | 6.72 | 28.75 |
April | 0.707288E+10 | 0.636559E+10 | 3250.25 | 01-APR-01:07 | 2925.23 | 2925.23 | 6.72 | 28.75 |
May | 0.862455E+10 | 0.776209E+10 | 3250.25 | 01-MAY-00:05 | 2925.23 | 2925.23 | 6.79 | 28.75 |
June | 0.842466E+10 | 0.758219E+10 | 3250.25 | 01-JUN-00:05 | 2925.23 | 2925.23 | 8.17 | 28.75 |
July | 0.870548E+10 | 0.783493E+10 | 3250.25 | 01-JUL-00:10 | 2925.23 | 2925.23 | 9.22 | 28.75 |
August | 0.870548E+10 | 0.783493E+10 | 3250.25 | 01-AUG-00:05 | 2925.23 | 2925.23 | 9.60 | 28.75 |
September | 0.842466E+10 | 0.758219E+10 | 3250.25 | 01-SEP-00:05 | 2925.23 | 2925.23 | 9.47 | 28.75 |
October | 0.845700E+10 | 0.761130E+10 | 3250.25 | 01-OCT-00:10 | 2925.23 | 2925.23 | 6.97 | 28.75 |
November | 0.551848E+10 | 0.496663E+10 | 3250.25 | 01-NOV-00:05 | 2925.23 | 2925.23 | 6.75 | 28.75 |
December | 0.363450E+10 | 0.327105E+10 | 3250.25 | 01-DEC-00:03 | 2925.23 | 2925.23 | 6.72 | 28.75 |
Annual Sum or Average | 0.783225E+11 | 0.704902E+11 | ||||||
Minimum of Months | 0.230883E+10 | 0.207795E+10 | 3250.25 | 2925.23 | 2925.23 | 6.72 | 28.75 | |
Maximum of Months | 0.870548E+10 | 0.783493E+10 | 3250.25 | 2925.23 | 2925.23 | 9.60 | 28.75 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:05 | 14.37 | 14.37 | 48.56 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:03 | 14.37 | 14.37 | 49.23 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:03 | 14.37 | 14.37 | 49.30 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 52.58 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:05 | 14.37 | 14.37 | 52.82 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:05 | 14.37 | 14.37 | 53.35 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 53.97 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:05 | 14.37 | 14.37 | 53.99 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:05 | 14.37 | 14.37 | 53.94 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:10 | 14.37 | 14.37 | 53.08 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:05 | 14.37 | 14.37 | 53.14 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:03 | 14.37 | 14.37 | 50.09 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 48.56 | 0.37 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 53.99 | 0.37 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 35.08 | 60.00 | 48560.20 | 180921.21 | 02-JAN-09:04 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 38.58 | 60.00 | 44597.36 | 185828.75 | 06-FEB-09:02 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 44.42 | 60.00 | 26360.80 | 156626.58 | 11-MAR-19:03 |
April | 0.00 | 0.00 | 01-APR-00:10 | 47.20 | 60.00 | 28949.02 | 147593.66 | 02-APR-18:04 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 31.14 | 60.00 | 11166.59 | 102921.98 | 01-MAY-06:20 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 36.49 | 36.49 | 220.67 | 33861.52 | 06-JUN-15:06 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 36.58 | 36.58 | 27.73 | 23908.15 | 14-JUL-08:07 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 43.95 | 43.95 | 136.70 | 39732.26 | 24-AUG-19:00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 32.24 | 32.24 | 2704.19 | 73826.71 | 24-SEP-06:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.10 | 60.00 | 17102.64 | 133080.09 | 27-OCT-18:04 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 31.85 | 60.00 | 37535.08 | 162487.64 | 16-NOV-16:02 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 46.69 | 60.00 | 30082.23 | 169568.87 | 04-DEC-16:02 |
Annual Sum or Average | 0.00 | 20459.01 | ||||||
Minimum of Months | 0.00 | 0.00 | 25.10 | 32.24 | 27.73 | 23908.15 | ||
Maximum of Months | 0.00 | 0.00 | 47.20 | 60.00 | 48560.20 | 185828.75 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 1471.11 | 46062.98 | 24-JAN-19:02 | 7.08 | 6.70 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 3029.79 | 63908.18 | 20-FEB-09:03 | 7.23 | 6.70 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 9656.02 | 246399.12 | 27-MAR-15:01 | 8.74 | 6.70 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 32939.85 | 379459.77 | 07-APR-15:03 | 9.85 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 84575.83 | 424012.45 | 31-MAY-15:03 | 10.22 | 6.70 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 272363.52 | 654035.43 | 23-JUN-21:52 | 12.13 | 6.70 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 401957.23 | 715440.00 | 24-JUL-21:52 | 12.64 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 339232.64 | 772852.38 | 11-AUG-21:51 | 13.12 | 6.70 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 200508.52 | 658687.52 | 07-SEP-20:00 | 12.17 | 6.70 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 86763.22 | 481376.37 | 03-OCT-15:03 | 10.70 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 11119.03 | 188747.58 | 04-NOV-15:03 | 8.27 | 6.70 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 3624.16 | 62499.93 | 20-DEC-09:02 | 7.22 | 6.70 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 121475.20 | 0.00 | ||||||
Minimum of Months | 1471.11 | 46062.98 | 7.08 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 401957.23 | 772852.38 | 13.12 | 6.70 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 48.56 | 60.05 | 27153.39 | 57316.47 | 31-JAN-07:20 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 49.23 | 60.05 | 27426.07 | 57394.64 | 09-FEB-07:15 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 49.30 | 60.05 | 26837.75 | 56950.67 | 01-MAR-07:30 |
April | 0.00 | 0.00 | 01-APR-00:10 | 52.58 | 60.05 | 25463.18 | 54540.10 | 03-APR-07:00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 52.82 | 60.05 | 23715.92 | 51383.54 | 01-MAY-06:20 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 53.35 | 60.05 | 22054.39 | 47941.60 | 01-JUN-18:02 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 53.97 | 60.05 | 20897.65 | 44445.17 | 03-JUL-06:20 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 53.99 | 60.05 | 20621.82 | 44734.57 | 22-AUG-06:50 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 53.94 | 60.05 | 21240.67 | 45448.23 | 29-SEP-06:15 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 53.08 | 60.05 | 22610.95 | 49005.97 | 31-OCT-06:20 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 53.14 | 60.05 | 24365.37 | 52672.68 | 30-NOV-07:20 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 50.09 | 60.05 | 26022.28 | 55609.16 | 29-DEC-07:15 |
Annual Sum or Average | 0.00 | 24014.49 | ||||||
Minimum of Months | 0.00 | 0.00 | 48.56 | 60.05 | 20621.82 | 44445.17 | ||
Maximum of Months | 0.00 | 0.00 | 53.99 | 60.05 | 27426.07 | 57394.64 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.152463E+10 | 0.00 | 0.00 | 0.271000E+10 | 0.00 | 0.00 |
February | 0.172753E+10 | 0.00 | 0.00 | 0.244774E+10 | 0.00 | 0.00 |
March | 0.126669E+09 | 0.00 | 0.272158E+09 | 0.271000E+10 | 0.00 | 0.00 |
April | 3493.52 | 0.00 | 0.216554E+10 | 0.262258E+10 | 0.00 | 0.00 |
May | 13988.00 | 0.00 | 0.900257E+10 | 0.271000E+10 | 0.00 | 0.00 |
June | 11513.28 | 0.00 | 0.426109E+11 | 0.262258E+10 | 0.00 | 0.00 |
July | 21603.60 | 0.00 | 0.580827E+11 | 0.271000E+10 | 0.00 | 0.00 |
August | 11270.98 | 0.00 | 0.468423E+11 | 0.271000E+10 | 0.00 | 0.00 |
September | 14801.31 | 0.00 | 0.289963E+11 | 0.262258E+10 | 0.00 | 0.00 |
October | 9145.81 | 0.00 | 0.100098E+11 | 0.271000E+10 | 0.00 | 0.00 |
November | 0.137964E+09 | 0.00 | 0.209514E+09 | 0.262258E+10 | 0.00 | 0.00 |
December | 0.196715E+09 | 0.00 | 0.00 | 0.271000E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.371360E+10 | 0.00 | 0.198192E+12 | 0.319080E+11 | 0.00 | 0.00 |
Minimum of Months | 3493.52 | 0.00 | 0.00 | 0.244774E+10 | 0.00 | 0.00 |
Maximum of Months | 0.172753E+10 | 0.00 | 0.580827E+11 | 0.271000E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.856187E+11 | 0.00 | 54740927.79 | 0.331993E+11 | 0.00 | 0.00 |
February | 0.681977E+11 | 0.00 | 66694393.81 | 0.299769E+11 | 0.00 | 0.00 |
March | 0.553589E+11 | 0.00 | 0.342005E+10 | 0.343334E+11 | 0.00 | 0.00 |
April | 0.702534E+11 | 0.00 | 0.344920E+11 | 0.341317E+11 | 0.00 | 0.00 |
May | 0.296643E+11 | 0.00 | 0.127231E+12 | 0.366405E+11 | 0.00 | 0.00 |
June | 0.539405E+09 | 0.00 | 0.525177E+12 | 0.374834E+11 | 0.00 | 0.00 |
July | 36674158.58 | 0.00 | 0.834222E+12 | 0.399565E+11 | 0.00 | 0.00 |
August | 0.342336E+09 | 0.00 | 0.672424E+12 | 0.408370E+11 | 0.00 | 0.00 |
September | 0.693585E+10 | 0.00 | 0.365735E+12 | 0.375897E+11 | 0.00 | 0.00 |
October | 0.447555E+11 | 0.00 | 0.125858E+12 | 0.374830E+11 | 0.00 | 0.00 |
November | 0.812865E+11 | 0.00 | 0.344095E+10 | 0.339939E+11 | 0.00 | 0.00 |
December | 0.477843E+11 | 0.00 | 0.139726E+09 | 0.338607E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.490774E+12 | 0.00 | 0.269226E+13 | 0.429486E+12 | 0.00 | 0.00 |
Minimum of Months | 36674158.58 | 0.00 | 54740927.79 | 0.299769E+11 | 0.00 | 0.00 |
Maximum of Months | 0.856187E+11 | 0.00 | 0.834222E+12 | 0.408370E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.271000E+10 | 0.00 | 0.152463E+10 | 0.541856E+11 | 26804.89 | 0.00 | 0.00 | 0.00 |
February | 0.244774E+10 | 0.00 | 0.172753E+10 | 0.528584E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.271000E+10 | 0.272158E+09 | 0.126669E+09 | 0.392352E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.262258E+10 | 0.216554E+10 | 3493.52 | 0.195641E+11 | 44581103.36 | 0.00 | 0.00 | 0.00 |
May | 0.271000E+10 | 0.900257E+10 | 13988.00 | 0.454910E+10 | 0.415226E+09 | 0.00 | 0.00 | 0.00 |
June | 0.262258E+10 | 0.426109E+11 | 11513.28 | 86609570.75 | 0.805790E+10 | 0.00 | 0.00 | 0.00 |
July | 0.271000E+10 | 0.580827E+11 | 21603.60 | 1699873.30 | 0.312410E+11 | 0.00 | 0.00 | 0.00 |
August | 0.271000E+10 | 0.468423E+11 | 11270.98 | 70889521.18 | 0.239262E+11 | 0.00 | 0.00 | 0.00 |
September | 0.262258E+10 | 0.289963E+11 | 14801.31 | 0.927037E+09 | 0.532300E+10 | 0.00 | 0.00 | 0.00 |
October | 0.271000E+10 | 0.100098E+11 | 9145.81 | 0.105793E+11 | 0.124408E+09 | 0.00 | 0.00 | 0.00 |
November | 0.262258E+10 | 0.209514E+09 | 0.137964E+09 | 0.315947E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.271000E+10 | 0.00 | 0.196715E+09 | 0.481933E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319080E+11 | 0.198192E+12 | 0.371360E+10 | 0.261846E+12 | 0.691323E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244774E+10 | 0.00 | 3493.52 | 1699873.30 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.271000E+10 | 0.580827E+11 | 0.172753E+10 | 0.541856E+11 | 0.312410E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.331993E+11 | 54740927.79 | 0.856187E+11 | 0.585088E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.299769E+11 | 66694393.81 | 0.681977E+11 | 0.589854E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.343334E+11 | 0.342005E+10 | 0.553589E+11 | 0.398635E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.341317E+11 | 0.344920E+11 | 0.702534E+11 | 0.133476E+12 | 0.193609E+09 | 0.00 | 0.00 | 0.00 |
May | 0.366405E+11 | 0.127231E+12 | 0.296643E+11 | 0.670803E+10 | 0.329519E+10 | 0.00 | 0.00 | 0.00 |
June | 0.374834E+11 | 0.525177E+12 | 0.539405E+09 | 0.00 | 0.561527E+11 | 0.00 | 0.00 | 0.00 |
July | 0.399565E+11 | 0.834222E+12 | 36674158.58 | 0.00 | 0.221367E+12 | 0.00 | 0.00 | 0.00 |
August | 0.408370E+11 | 0.672424E+12 | 0.342336E+09 | 0.00 | 0.177463E+12 | 0.00 | 0.00 | 0.00 |
September | 0.375897E+11 | 0.365735E+12 | 0.693585E+10 | 0.00 | 0.235325E+11 | 0.00 | 0.00 | 0.00 |
October | 0.374830E+11 | 0.125858E+12 | 0.447555E+11 | 0.587356E+11 | 0.601051E+09 | 0.00 | 0.00 | 0.00 |
November | 0.339939E+11 | 0.344095E+10 | 0.812865E+11 | 0.268411E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.338607E+11 | 0.139726E+09 | 0.477843E+11 | 0.523824E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.429486E+12 | 0.269226E+13 | 0.490774E+12 | 0.256473E+13 | 0.482605E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.299769E+11 | 54740927.79 | 36674158.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.408370E+11 | 0.834222E+12 | 0.856187E+11 | 0.589854E+12 | 0.221367E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.271000E+10 | 0.152463E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244774E+10 | 0.172753E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.271000E+10 | 0.126669E+09 | 0.272158E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.262258E+10 | 3493.52 | 0.216554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.271000E+10 | 13988.00 | 0.900257E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.262258E+10 | 11513.28 | 0.426109E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.271000E+10 | 21603.60 | 0.580827E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.271000E+10 | 11270.98 | 0.468423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.262258E+10 | 14801.31 | 0.289963E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.271000E+10 | 9145.81 | 0.100098E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.262258E+10 | 0.137964E+09 | 0.209514E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.271000E+10 | 0.196715E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319080E+11 | 0.371360E+10 | 0.198192E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244774E+10 | 3493.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.271000E+10 | 0.172753E+10 | 0.580827E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.331993E+11 | 0.856187E+11 | 54740927.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.299769E+11 | 0.681977E+11 | 66694393.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.343334E+11 | 0.553589E+11 | 0.342005E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.341317E+11 | 0.702534E+11 | 0.344920E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.366405E+11 | 0.296643E+11 | 0.127231E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.374834E+11 | 0.539405E+09 | 0.525177E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.399565E+11 | 36674158.58 | 0.834222E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.408370E+11 | 0.342336E+09 | 0.672424E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.375897E+11 | 0.693585E+10 | 0.365735E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.374830E+11 | 0.447555E+11 | 0.125858E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.339939E+11 | 0.812865E+11 | 0.344095E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.338607E+11 | 0.477843E+11 | 0.139726E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.429486E+12 | 0.490774E+12 | 0.269226E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.299769E+11 | 36674158.58 | 54740927.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.408370E+11 | 0.856187E+11 | 0.834222E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.389414E+11 | 0.00 | 0.00 | 7997602.22 | 0.00 | 0.00 | 0.127179E+11 | 0.00 | 0.99 |
February | 0.425747E+11 | 0.00 | 0.00 | 923925.97 | 0.00 | 0.00 | 0.346830E+10 | 0.00 | 0.99 |
March | 0.507090E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.98 |
April | 0.491145E+11 | 0.00 | 0.00 | 0.00 | 12710485.86 | 0.00 | 0.00 | 0.00 | 0.99 |
May | 0.396230E+11 | 0.00 | 0.00 | 0.00 | 0.267082E+09 | 0.00 | 0.00 | 0.00 | 0.99 |
June | 0.101734E+11 | 0.00 | 0.00 | 0.00 | 0.115248E+11 | 0.00 | 0.00 | 0.00 | 0.99 |
July | 0.524801E+09 | 0.327695E+10 | 0.00 | 68439.01 | 0.249498E+11 | 0.00 | 23385395.95 | 0.00 | 0.98 |
August | 0.135125E+10 | 0.664458E+10 | 0.00 | 8281654.56 | 0.106573E+11 | 0.00 | 0.492324E+10 | 0.00 | 0.99 |
September | 0.185653E+10 | 0.501023E+10 | 0.00 | 36694166.78 | 0.146313E+10 | 0.00 | 0.204961E+11 | 0.00 | 1.04 |
October | 0.161950E+10 | 0.343438E+09 | 0.00 | 67841766.30 | 0.133323E+09 | 0.00 | 0.453734E+11 | 0.00 | 1.09 |
November | 0.227332E+10 | 0.00 | 0.00 | 61368913.43 | 0.00 | 0.00 | 0.548100E+11 | 0.00 | 1.07 |
December | 0.143828E+11 | 0.00 | 0.00 | 34377761.47 | 0.00 | 0.00 | 0.364783E+11 | 0.00 | 1.03 |
Annual Sum or Average | 0.253144E+12 | 0.152752E+11 | 0.00 | 0.217554E+09 | 0.490081E+11 | 0.00 | 0.178291E+12 | 0.00 | 1.01 |
Minimum of Months | 0.524801E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.98 |
Maximum of Months | 0.507090E+11 | 0.664458E+10 | 0.00 | 67841766.30 | 0.249498E+11 | 0.00 | 0.548100E+11 | 0.00 | 1.09 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.456715E+10 | 0.00 | 0.00 | 154384.54 | 0.00 | 0.270175E+10 | 0.248424E+09 | 0.00 | 2.59 |
February | 0.434834E+10 | 0.00 | 0.00 | 246502.09 | 0.00 | 0.203380E+10 | 0.319022E+09 | 0.00 | 2.60 |
March | 0.645786E+10 | 0.00 | 0.00 | 615775.10 | 0.00 | 0.361406E+09 | 0.596722E+09 | 0.00 | 2.60 |
April | 0.678054E+10 | 2100199.68 | 0.00 | 525720.62 | 276135.66 | 21437139.55 | 0.347281E+09 | 0.00 | 2.61 |
May | 0.555034E+10 | 26833789.61 | 0.00 | 230411.85 | 13362432.91 | 0.00 | 0.214043E+09 | 0.00 | 2.62 |
June | 0.139466E+10 | 0.685805E+09 | 0.00 | 279209.28 | 0.999405E+09 | 0.00 | 85168377.81 | 0.00 | 2.62 |
July | 60224155.77 | 0.233738E+10 | 0.00 | 57379.44 | 0.185817E+10 | 0.00 | 19482136.67 | 0.00 | 2.63 |
August | 0.701275E+09 | 0.220632E+10 | 0.00 | 951643.47 | 0.509562E+09 | 0.00 | 0.207209E+09 | 0.00 | 2.80 |
September | 0.257091E+10 | 0.443935E+09 | 0.00 | 2351780.52 | 0.507858E+09 | 0.00 | 0.585958E+09 | 0.00 | 2.76 |
October | 0.499811E+10 | 91166119.33 | 0.00 | 3137647.35 | 3109764.76 | 0.00 | 0.140281E+10 | 0.00 | 2.78 |
November | 0.696243E+10 | 0.00 | 0.00 | 507159.75 | 0.00 | 0.297602E+09 | 0.428630E+09 | 0.00 | 2.61 |
December | 0.527448E+10 | 0.00 | 0.00 | 444161.38 | 0.00 | 0.149776E+10 | 0.408822E+09 | 0.00 | 2.61 |
Annual Sum or Average | 0.496663E+11 | 0.579354E+10 | 0.00 | 9501775.39 | 0.389174E+10 | 0.691375E+10 | 0.486357E+10 | 0.00 | 2.65 |
Minimum of Months | 60224155.77 | 0.00 | 0.00 | 57379.44 | 0.00 | 0.00 | 19482136.67 | 0.00 | 2.59 |
Maximum of Months | 0.696243E+10 | 0.233738E+10 | 0.00 | 3137647.35 | 0.185817E+10 | 0.270175E+10 | 0.140281E+10 | 0.00 | 2.80 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.474802E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.41 |
February | 0.423472E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.42 |
March | 0.455589E+10 | 0.00 | 0.00 | 23457.66 | 0.00 | 0.00 | 0.107861E+09 | 0.00 | 1.42 |
April | 0.410089E+10 | 0.00 | 0.00 | 277109.70 | 1169000.81 | 0.00 | 0.418578E+09 | 0.00 | 1.43 |
May | 0.284859E+10 | 3120005.71 | 0.00 | 701567.68 | 21460688.90 | 0.00 | 0.802610E+09 | 0.00 | 1.44 |
June | 0.324705E+09 | 0.553261E+09 | 0.00 | 1186964.64 | 0.536401E+09 | 0.00 | 0.625282E+09 | 0.00 | 1.47 |
July | 2896482.88 | 0.194444E+10 | 0.00 | 337850.24 | 0.773049E+09 | 0.00 | 49816991.03 | 0.00 | 1.48 |
August | 56822229.51 | 0.143321E+10 | 0.00 | 1742745.21 | 0.272706E+09 | 0.00 | 0.543136E+09 | 0.00 | 1.52 |
September | 0.990841E+09 | 0.379891E+09 | 0.00 | 1504367.57 | 0.213459E+09 | 0.00 | 0.100103E+10 | 0.00 | 1.47 |
October | 0.267606E+10 | 10037056.28 | 0.00 | 1208123.76 | 33500812.98 | 0.00 | 0.128626E+10 | 0.00 | 1.45 |
November | 0.463351E+10 | 0.00 | 0.00 | 67149.80 | 0.00 | 0.00 | 0.208858E+09 | 0.00 | 1.42 |
December | 0.451930E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.42 |
Annual Sum or Average | 0.336922E+11 | 0.432396E+10 | 0.00 | 7049336.26 | 0.185175E+10 | 0.00 | 0.504343E+10 | 0.00 | 1.45 |
Minimum of Months | 2896482.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.41 |
Maximum of Months | 0.474802E+10 | 0.194444E+10 | 0.00 | 1742745.21 | 0.773049E+09 | 0.00 | 0.128626E+10 | 0.00 | 1.52 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.326009E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.617769E+09 | 0.00 | 0.00 | 0.55 |
February | 0.271203E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.746598E+09 | 0.00 | 0.00 | 0.55 |
March | 0.380905E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.55 |
April | 0.368928E+10 | 0.00 | 0.00 | 0.00 | 954760.21 | 0.00 | 0.00 | 0.00 | 0.55 |
May | 0.296754E+10 | 1102.98 | 0.00 | 10025.75 | 20061009.87 | 0.00 | 8764353.69 | 0.00 | 0.55 |
June | 0.738182E+09 | 0.145894E+09 | 0.00 | 100670.08 | 0.723862E+09 | 0.00 | 27122859.89 | 0.00 | 0.55 |
July | 13123971.56 | 0.844214E+09 | 0.00 | 128145.38 | 0.132030E+10 | 0.00 | 28756126.39 | 0.00 | 0.56 |
August | 0.321875E+09 | 0.764940E+09 | 0.00 | 490548.19 | 0.578670E+09 | 0.00 | 0.150897E+09 | 0.00 | 0.56 |
September | 0.154574E+10 | 72201339.89 | 0.00 | 145025.86 | 0.392411E+09 | 0.00 | 57877575.83 | 0.00 | 0.55 |
October | 0.322003E+10 | 0.00 | 0.00 | 0.00 | 35436931.06 | 0.00 | 0.00 | 0.00 | 0.55 |
November | 0.395497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.55 |
December | 0.368359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7457975.05 | 0.00 | 0.00 | 0.55 |
Annual Sum or Average | 0.299155E+11 | 0.182725E+10 | 0.00 | 874415.26 | 0.307170E+10 | 0.137182E+10 | 0.273418E+09 | 0.00 | 0.55 |
Minimum of Months | 13123971.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.55 |
Maximum of Months | 0.395497E+10 | 0.844214E+09 | 0.00 | 490548.19 | 0.132030E+10 | 0.746598E+09 | 0.150897E+09 | 0.00 | 0.56 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.123199E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107965E+10 | 0.00 | 0.00 | 0.56 |
February | 0.106933E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.992402E+09 | 0.00 | 0.00 | 0.57 |
March | 0.219557E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75050653.13 | 0.00 | 0.00 | 0.56 |
April | 0.219923E+10 | 0.00 | 0.00 | 0.00 | 569144.25 | 0.00 | 0.00 | 0.00 | 0.57 |
May | 0.177422E+10 | 0.00 | 0.00 | 0.00 | 11959271.16 | 0.00 | 0.00 | 0.00 | 0.57 |
June | 0.451910E+09 | 11355728.02 | 0.00 | 4897.23 | 0.504695E+09 | 0.00 | 3622353.93 | 0.00 | 0.57 |
July | 17807096.87 | 0.160780E+09 | 0.00 | 15512.24 | 0.110337E+10 | 0.00 | 6726876.82 | 0.00 | 0.56 |
August | 0.262011E+09 | 0.247459E+09 | 0.00 | 44199.73 | 0.525381E+09 | 0.00 | 17421578.41 | 0.00 | 0.57 |
September | 0.954741E+09 | 2620457.82 | 0.00 | 4303.53 | 0.272847E+09 | 0.00 | 945197.85 | 0.00 | 0.57 |
October | 0.191950E+10 | 0.00 | 0.00 | 0.00 | 21124388.59 | 0.00 | 0.00 | 0.00 | 0.57 |
November | 0.222747E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130137E+09 | 0.00 | 0.00 | 0.57 |
December | 0.192569E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274589E+09 | 0.00 | 0.00 | 0.57 |
Annual Sum or Average | 0.162295E+11 | 0.422215E+09 | 0.00 | 68912.73 | 0.243994E+10 | 0.255183E+10 | 28716007.01 | 0.00 | 0.57 |
Minimum of Months | 17807096.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.56 |
Maximum of Months | 0.222747E+10 | 0.247459E+09 | 0.00 | 44199.73 | 0.110337E+10 | 0.107965E+10 | 17421578.41 | 0.00 | 0.57 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.415355E+09 | 0.00 | 0.00 | 90082664.84 | 0.00 | 0.00 | 0.771955E+11 | 0.00 | 23.01 |
February | 0.463473E+09 | 0.00 | 0.00 | 81369857.41 | 0.00 | 0.00 | 0.686566E+11 | 0.00 | 23.12 |
March | 0.213313E+09 | 0.00 | 0.00 | 92626404.24 | 0.00 | 0.00 | 0.764091E+11 | 0.00 | 23.17 |
April | 0.189456E+09 | 16685301.52 | 0.00 | 95059470.44 | 0.00 | 0.00 | 0.743116E+11 | 0.00 | 23.20 |
May | 0.155550E+09 | 0.362583E+09 | 0.00 | 0.109197E+09 | 8220316.93 | 0.00 | 0.598159E+11 | 0.00 | 23.38 |
June | 9924822.85 | 0.174546E+11 | 0.00 | 53924196.24 | 44008639.15 | 0.00 | 0.151924E+11 | 0.00 | 23.33 |
July | 0.00 | 0.427281E+11 | 0.00 | 6152915.82 | 66864585.92 | 0.00 | 0.765268E+09 | 0.00 | 22.93 |
August | 4699610.20 | 0.260865E+11 | 0.00 | 40559730.50 | 34938104.31 | 0.00 | 0.895322E+10 | 0.00 | 23.14 |
September | 31831836.07 | 0.956724E+10 | 0.00 | 77016854.07 | 2258655.28 | 0.00 | 0.318393E+11 | 0.00 | 23.37 |
October | 0.180938E+09 | 0.645253E+09 | 0.00 | 99990313.16 | 0.00 | 0.00 | 0.641940E+11 | 0.00 | 23.40 |
November | 0.274741E+09 | 0.00 | 0.00 | 89518195.36 | 0.00 | 0.00 | 0.791090E+11 | 0.00 | 23.20 |
December | 0.260576E+09 | 0.00 | 0.00 | 91110015.82 | 0.00 | 0.00 | 0.735270E+11 | 0.00 | 23.13 |
Annual Sum or Average | 0.219986E+10 | 0.968609E+11 | 0.00 | 0.926608E+09 | 0.156290E+09 | 0.00 | 0.629969E+12 | 0.00 | 23.20 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 6152915.82 | 0.00 | 0.00 | 0.765268E+09 | 0.00 | 22.93 |
Maximum of Months | 0.463473E+09 | 0.427281E+11 | 0.00 | 0.109197E+09 | 66864585.92 | 0.00 | 0.791090E+11 | 0.00 | 23.40 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.264601E+11 | 0.00 | 0.00 | 2057643.12 | 0.00 | 31411314.65 | 0.504406E+10 | 0.00 | 3.87 |
February | 0.212875E+11 | 0.00 | 0.00 | 3283418.68 | 0.00 | 0.00 | 0.685767E+10 | 0.00 | 3.89 |
March | 0.173846E+11 | 0.00 | 0.00 | 8107516.80 | 0.00 | 0.00 | 0.137308E+11 | 0.00 | 3.90 |
April | 0.146170E+11 | 9406718.70 | 0.00 | 10713833.41 | 0.00 | 0.00 | 0.153884E+11 | 0.00 | 3.91 |
May | 0.730417E+10 | 0.129848E+09 | 0.00 | 14339208.22 | 33319203.43 | 0.00 | 0.169021E+11 | 0.00 | 3.93 |
June | 0.844392E+09 | 0.552832E+10 | 0.00 | 12449226.88 | 0.162671E+10 | 0.00 | 0.541737E+10 | 0.00 | 3.98 |
July | 26272202.36 | 0.160385E+11 | 0.00 | 2151558.85 | 0.182401E+10 | 0.00 | 0.330517E+09 | 0.00 | 4.02 |
August | 0.264698E+09 | 0.107391E+11 | 0.00 | 13807567.07 | 0.641537E+09 | 0.00 | 0.374003E+10 | 0.00 | 4.22 |
September | 0.232726E+10 | 0.323063E+10 | 0.00 | 24794115.38 | 0.800144E+09 | 0.00 | 0.110306E+11 | 0.00 | 4.14 |
October | 0.451717E+10 | 0.357338E+09 | 0.00 | 31991452.19 | 2711511.04 | 0.00 | 0.224298E+11 | 0.00 | 4.14 |
November | 0.182130E+11 | 0.00 | 0.00 | 7846346.68 | 0.00 | 0.00 | 0.140547E+11 | 0.00 | 3.91 |
December | 0.220687E+11 | 0.00 | 0.00 | 4177131.18 | 0.00 | 0.00 | 0.811760E+10 | 0.00 | 3.91 |
Annual Sum or Average | 0.135315E+12 | 0.360331E+11 | 0.00 | 0.135719E+09 | 0.492843E+10 | 31411314.65 | 0.123044E+12 | 0.00 | 3.99 |
Minimum of Months | 26272202.36 | 0.00 | 0.00 | 2057643.12 | 0.00 | 0.00 | 0.330517E+09 | 0.00 | 3.87 |
Maximum of Months | 0.264601E+11 | 0.160385E+11 | 0.00 | 31991452.19 | 0.182401E+10 | 31411314.65 | 0.224298E+11 | 0.00 | 4.22 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.959529E+11 | 0.00 | 0.00 | 1132446.09 | 0.00 | 0.00 | 0.480801E+10 | 0.00 | 1.79 |
February | 0.849328E+11 | 0.00 | 0.00 | 1183678.66 | 0.00 | 0.00 | 0.493491E+10 | 0.00 | 1.80 |
March | 0.767625E+11 | 0.00 | 0.00 | 8624462.40 | 0.00 | 0.00 | 0.222219E+11 | 0.00 | 1.79 |
April | 0.600261E+11 | 4116889.80 | 0.00 | 22161099.20 | 20691565.75 | 0.00 | 0.360643E+11 | 0.00 | 1.80 |
May | 0.296380E+11 | 0.137153E+09 | 0.00 | 46674919.86 | 0.384202E+09 | 0.00 | 0.482394E+11 | 0.00 | 1.83 |
June | 0.351203E+10 | 0.140704E+11 | 0.00 | 44962255.05 | 0.931316E+10 | 0.00 | 0.170605E+11 | 0.00 | 1.88 |
July | 47635394.23 | 0.468024E+11 | 0.00 | 8215814.59 | 0.118999E+11 | 0.00 | 0.114877E+10 | 0.00 | 1.91 |
August | 0.820483E+09 | 0.319371E+11 | 0.00 | 44995291.28 | 0.446486E+10 | 0.00 | 0.126006E+11 | 0.00 | 1.96 |
September | 0.855997E+10 | 0.936660E+10 | 0.00 | 60910620.75 | 0.349109E+10 | 0.00 | 0.345940E+11 | 0.00 | 1.90 |
October | 0.249518E+11 | 0.745626E+09 | 0.00 | 64471553.69 | 0.178193E+09 | 0.00 | 0.602966E+11 | 0.00 | 1.85 |
November | 0.748483E+11 | 0.00 | 0.00 | 13168622.85 | 0.00 | 0.00 | 0.280186E+11 | 0.00 | 1.80 |
December | 0.851918E+11 | 0.00 | 0.00 | 2658553.70 | 0.00 | 0.00 | 0.107137E+11 | 0.00 | 1.80 |
Annual Sum or Average | 0.545244E+12 | 0.103063E+12 | 0.00 | 0.319159E+09 | 0.297521E+11 | 0.00 | 0.280701E+12 | 0.00 | 1.84 |
Minimum of Months | 47635394.23 | 0.00 | 0.00 | 1132446.09 | 0.00 | 0.00 | 0.114877E+10 | 0.00 | 1.79 |
Maximum of Months | 0.959529E+11 | 0.468024E+11 | 0.00 | 64471553.69 | 0.118999E+11 | 0.00 | 0.602966E+11 | 0.00 | 1.96 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 58033839.95 | 0.00 | 0.00 | 442801.25 | 0.00 | 0.145547E+10 | 52376099.96 | 0.00 | 0.35 |
February | 60491885.59 | 0.00 | 0.00 | 781438.34 | 0.00 | 0.127333E+10 | 98382055.88 | 0.00 | 0.35 |
March | 61403317.64 | 82834.06 | 0.00 | 3372736.06 | 9534.17 | 0.953088E+09 | 0.487154E+09 | 0.00 | 0.35 |
April | 49478101.03 | 1153980.07 | 0.00 | 7311267.09 | 0.00 | 0.509252E+09 | 0.760118E+09 | 0.00 | 0.35 |
May | 16762883.58 | 17222733.35 | 15371.32 | 13299521.16 | 841137.16 | 35483988.31 | 0.965856E+09 | 4838.03 | 0.35 |
June | 0.00 | 0.561589E+09 | 224957.92 | 6892186.81 | 281461.14 | 472363.70 | 0.204435E+09 | 14983.69 | 0.36 |
July | 0.00 | 0.112078E+10 | 1355145.65 | 282764.40 | 0.00 | 24114.19 | 1421707.44 | 32944.62 | 0.36 |
August | 0.00 | 0.777143E+09 | 830611.89 | 3705627.92 | 0.00 | 227673.47 | 68272234.49 | 13086.83 | 0.36 |
September | 4616843.56 | 0.279028E+09 | 333712.13 | 9176979.25 | 4030579.18 | 2450812.32 | 0.458831E+09 | 19046.61 | 0.35 |
October | 10658942.96 | 49786842.99 | 11173.68 | 9757662.32 | 48955.09 | 0.109776E+09 | 0.913687E+09 | 6913.46 | 0.35 |
November | 65878272.03 | 0.00 | 0.00 | 1779259.22 | 0.00 | 0.100308E+10 | 0.384029E+09 | 0.00 | 0.35 |
December | 61645860.96 | 0.00 | 0.00 | 545897.38 | 0.00 | 0.135735E+10 | 93608953.84 | 0.00 | 0.36 |
Annual Sum or Average | 0.388970E+09 | 0.280679E+10 | 2770972.59 | 57348141.21 | 5211666.73 | 0.670001E+10 | 0.448817E+10 | 91813.24 | 0.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 282764.40 | 0.00 | 24114.19 | 1421707.44 | 0.00 | 0.35 |
Maximum of Months | 65878272.03 | 0.112078E+10 | 1355145.65 | 13299521.16 | 4030579.18 | 0.145547E+10 | 0.965856E+09 | 32944.62 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 51953984.87 | 0.00 | 0.00 | 100132.80 | 0.00 | 0.150405E+10 | 10034943.13 | 0.00 | 0.35 |
February | 47365780.99 | 0.00 | 0.00 | 267462.99 | 0.00 | 0.135168E+10 | 33497549.48 | 0.00 | 0.35 |
March | 88896986.14 | 0.00 | 0.00 | 1849594.03 | 92357.41 | 0.114260E+10 | 0.271500E+09 | 0.00 | 0.35 |
April | 0.109238E+09 | 1148135.88 | 0.00 | 5139889.24 | 5708.99 | 0.582536E+09 | 0.629090E+09 | 0.00 | 0.35 |
May | 0.170424E+09 | 15280928.16 | 17356.77 | 9920564.58 | 2780906.22 | 38695539.31 | 0.812241E+09 | 2769.89 | 0.36 |
June | 89646199.11 | 0.451707E+09 | 297392.74 | 3788044.05 | 0.110029E+09 | 264503.71 | 0.118076E+09 | 10602.40 | 0.36 |
July | 1247499.86 | 0.959086E+09 | 1059969.10 | 52754.52 | 0.161868E+09 | 237.34 | 427891.77 | 24922.39 | 0.36 |
August | 27246650.65 | 0.717572E+09 | 899529.01 | 2460775.14 | 59410289.65 | 74076.87 | 42415573.28 | 14051.55 | 0.36 |
September | 0.151151E+09 | 0.211139E+09 | 345811.64 | 5013868.46 | 71882548.43 | 2211764.69 | 0.316644E+09 | 10620.79 | 0.36 |
October | 0.157086E+09 | 39863250.38 | 47942.58 | 5062719.34 | 9922667.83 | 0.206529E+09 | 0.675079E+09 | 14183.30 | 0.35 |
November | 94301333.41 | 0.00 | 0.00 | 744030.20 | 0.00 | 0.114913E+10 | 0.210423E+09 | 0.00 | 0.35 |
December | 59827830.85 | 0.00 | 0.00 | 82746.11 | 0.00 | 0.144620E+10 | 6866045.71 | 0.00 | 0.36 |
Annual Sum or Average | 0.104838E+10 | 0.239580E+10 | 2668001.83 | 34482581.48 | 0.415992E+09 | 0.742397E+10 | 0.312630E+10 | 77150.33 | 0.35 |
Minimum of Months | 1247499.86 | 0.00 | 0.00 | 52754.52 | 0.00 | 237.34 | 427891.77 | 0.00 | 0.35 |
Maximum of Months | 0.170424E+09 | 0.959086E+09 | 1059969.10 | 9920564.58 | 0.161868E+09 | 0.150405E+10 | 0.812241E+09 | 24922.39 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.965219E+09 | 0.00 | 0.00 | 5402.72 | 3720727.22 | 0.00 | 8937968.74 | 0.00 | 0.02 |
February | 0.888358E+09 | 0.00 | 0.00 | 514870.84 | 0.00 | 0.00 | 0.389086E+09 | 0.00 | 0.02 |
March | 0.788527E+09 | 0.00 | 0.00 | 1317917.73 | 0.00 | 0.00 | 0.700212E+09 | 0.00 | 0.02 |
April | 0.588878E+09 | 0.00 | 0.00 | 2083525.28 | 0.00 | 0.00 | 0.701033E+09 | 0.00 | 0.02 |
May | 0.197547E+09 | 30428881.62 | 0.00 | 2050318.90 | 0.00 | 0.00 | 0.811149E+09 | 0.00 | 0.02 |
June | 0.00 | 0.627008E+09 | 0.00 | 1339217.20 | 0.00 | 0.00 | 0.175601E+09 | 0.00 | 0.02 |
July | 0.00 | 0.112257E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
August | 0.00 | 0.800011E+09 | 0.00 | 1047172.29 | 0.00 | 0.00 | 12828471.95 | 0.00 | 0.02 |
September | 69394725.87 | 0.335197E+09 | 0.00 | 2694700.98 | 29143640.25 | 0.00 | 0.307105E+09 | 0.00 | 0.02 |
October | 79970950.29 | 0.160481E+09 | 0.00 | 3574609.10 | 0.00 | 0.00 | 0.855347E+09 | 0.00 | 0.02 |
November | 0.103342E+10 | 0.00 | 0.00 | 1016942.48 | 0.00 | 0.00 | 0.433032E+09 | 0.00 | 0.02 |
December | 0.105503E+10 | 0.00 | 0.00 | 542825.45 | 0.00 | 0.00 | 0.322136E+09 | 0.00 | 0.02 |
Annual Sum or Average | 0.566635E+10 | 0.307569E+10 | 0.00 | 16187502.96 | 32864367.47 | 0.00 | 0.471647E+10 | 0.00 | 0.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
Maximum of Months | 0.105503E+10 | 0.112257E+10 | 0.00 | 3574609.10 | 29143640.25 | 0.00 | 0.855347E+09 | 0.00 | 0.02 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.103872E+10 | 0.00 | 0.00 | 6147217.87 | 0.00 | 0.138946E+11 | 0.630431E+10 | 0.00 | 0.40 |
February | 0.994552E+09 | 0.00 | 0.00 | 4758058.14 | 0.00 | 0.136436E+11 | 0.479229E+10 | 0.00 | 0.40 |
March | 0.124931E+10 | 0.00 | 0.00 | 29179558.95 | 1252772.80 | 0.404061E+10 | 0.150932E+11 | 0.00 | 0.40 |
April | 0.156112E+10 | 14937909.84 | 20619.49 | 72001980.04 | 687448.12 | 0.166887E+09 | 0.161864E+11 | 5235.99 | 0.40 |
May | 0.263569E+10 | 0.200168E+09 | 291768.94 | 0.126793E+09 | 44805497.68 | 23120538.76 | 0.112031E+11 | 6174.58 | 0.40 |
June | 0.125168E+10 | 0.598299E+10 | 1434824.51 | 43481503.68 | 0.163932E+10 | 1165099.30 | 0.157627E+10 | 45705.44 | 0.41 |
July | 16921587.20 | 0.129931E+11 | 5478173.64 | 518491.43 | 0.222120E+10 | 0.00 | 6004406.58 | 36087.84 | 0.40 |
August | 0.375372E+09 | 0.962091E+10 | 7068285.46 | 24735859.59 | 0.923651E+09 | 632822.79 | 0.578569E+09 | 56287.35 | 0.40 |
September | 0.214049E+10 | 0.275108E+10 | 2267448.45 | 65902749.02 | 0.109046E+10 | 9929558.54 | 0.422704E+10 | 49972.24 | 0.40 |
October | 0.218245E+10 | 0.468907E+09 | 1720915.66 | 69060424.11 | 0.205430E+09 | 67068677.25 | 0.118394E+11 | 100643.89 | 0.40 |
November | 0.128464E+10 | 0.00 | 0.00 | 31749410.61 | 0.00 | 0.367968E+10 | 0.147347E+11 | 0.00 | 0.40 |
December | 0.105610E+10 | 0.00 | 0.00 | 7763542.03 | 0.00 | 0.111855E+11 | 0.827326E+10 | 0.00 | 0.40 |
Annual Sum or Average | 0.157871E+11 | 0.320321E+11 | 18282036.15 | 0.482092E+09 | 0.612681E+10 | 0.467129E+11 | 0.948145E+11 | 300107.33 | 0.40 |
Minimum of Months | 16921587.20 | 0.00 | 0.00 | 518491.43 | 0.00 | 0.00 | 6004406.58 | 0.00 | 0.40 |
Maximum of Months | 0.263569E+10 | 0.129931E+11 | 7068285.46 | 0.126793E+09 | 0.222120E+10 | 0.138946E+11 | 0.161864E+11 | 100643.89 | 0.41 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 60645797.38 | 0.00 | 0.00 | 450082.73 | 0.00 | 0.142703E+10 | 78196309.47 | 0.00 | 0.35 |
February | 63067035.01 | 0.00 | 0.00 | 872799.33 | 0.00 | 0.122919E+10 | 0.139851E+09 | 0.00 | 0.35 |
March | 56129750.53 | 0.00 | 0.00 | 3159763.77 | 92368.23 | 0.992908E+09 | 0.452820E+09 | 0.00 | 0.35 |
April | 38677749.34 | 1153980.07 | 0.00 | 7272583.02 | 0.00 | 0.499219E+09 | 0.780990E+09 | 0.00 | 0.35 |
May | 14782481.32 | 17741728.46 | 7619.47 | 13474147.71 | 333746.81 | 33420706.66 | 0.969725E+09 | 985.11 | 0.35 |
June | 0.00 | 0.561970E+09 | 133640.97 | 7227398.65 | 0.00 | 337781.04 | 0.204234E+09 | 6609.29 | 0.36 |
July | 0.00 | 0.112154E+10 | 618848.12 | 374000.22 | 0.00 | 0.00 | 1354585.80 | 7967.46 | 0.36 |
August | 0.00 | 0.777954E+09 | 31282.02 | 4214589.29 | 0.00 | 26425.88 | 67964520.71 | 1570.44 | 0.36 |
September | 4616843.56 | 0.279117E+09 | 250940.14 | 9701652.28 | 4030579.18 | 1497082.68 | 0.459260E+09 | 12293.12 | 0.35 |
October | 9778587.05 | 49786842.99 | 13677.49 | 9740683.67 | 48955.09 | 0.123004E+09 | 0.901356E+09 | 4409.64 | 0.35 |
November | 63411688.75 | 0.00 | 0.00 | 2507902.18 | 0.00 | 0.952245E+09 | 0.436605E+09 | 0.00 | 0.35 |
December | 66794294.28 | 0.00 | 0.00 | 867973.81 | 0.00 | 0.131859E+10 | 0.126908E+09 | 0.00 | 0.36 |
Annual Sum or Average | 0.377904E+09 | 0.280927E+10 | 1056008.21 | 59863576.67 | 4505649.31 | 0.657747E+10 | 0.461926E+10 | 33835.06 | 0.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 374000.22 | 0.00 | 0.00 | 1354585.80 | 0.00 | 0.35 |
Maximum of Months | 66794294.28 | 0.112154E+10 | 618848.12 | 13474147.71 | 4030579.18 | 0.142703E+10 | 0.969725E+09 | 12293.12 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 42871116.43 | 0.00 | 0.00 | 85905.73 | 0.00 | 0.149300E+10 | 30185555.34 | 0.00 | 0.35 |
February | 41618959.37 | 0.00 | 0.00 | 229661.36 | 0.00 | 0.134337E+10 | 47598782.93 | 0.00 | 0.35 |
March | 87858703.11 | 0.00 | 0.00 | 1523458.93 | 92357.41 | 0.113996E+10 | 0.275501E+09 | 0.00 | 0.35 |
April | 0.103633E+09 | 1153844.87 | 0.00 | 5196966.84 | 0.00 | 0.555597E+09 | 0.661577E+09 | 0.00 | 0.35 |
May | 0.159416E+09 | 15822087.34 | 1482.11 | 10407041.37 | 2257379.63 | 37467722.48 | 0.823991E+09 | 1011.96 | 0.36 |
June | 86913886.25 | 0.452532E+09 | 243415.63 | 4276068.80 | 0.109260E+09 | 181792.49 | 0.120403E+09 | 9460.11 | 0.36 |
July | 1214600.09 | 0.961410E+09 | 521318.27 | 63033.30 | 0.160096E+09 | 0.00 | 450750.10 | 11310.15 | 0.36 |
August | 25625029.55 | 0.719437E+09 | 7187.84 | 2581471.79 | 58450480.95 | 68046.05 | 43922528.55 | 1129.18 | 0.36 |
September | 0.147919E+09 | 0.209553E+09 | 222277.97 | 5916105.59 | 73596592.64 | 1433467.54 | 0.319752E+09 | 6417.02 | 0.36 |
October | 0.157597E+09 | 40067529.96 | 91401.71 | 5059099.25 | 9672969.10 | 0.205352E+09 | 0.675749E+09 | 16143.32 | 0.35 |
November | 94432445.12 | 0.00 | 0.00 | 1057313.52 | 0.00 | 0.106921E+10 | 0.289895E+09 | 0.00 | 0.35 |
December | 56819984.20 | 0.00 | 0.00 | 162043.97 | 0.00 | 0.141451E+10 | 41482080.45 | 0.00 | 0.36 |
Annual Sum or Average | 0.100592E+10 | 0.239998E+10 | 1087083.52 | 36558170.44 | 0.413425E+09 | 0.726015E+10 | 0.333051E+10 | 45471.74 | 0.35 |
Minimum of Months | 1214600.09 | 0.00 | 0.00 | 63033.30 | 0.00 | 0.00 | 450750.10 | 0.00 | 0.35 |
Maximum of Months | 0.159416E+09 | 0.961410E+09 | 521318.27 | 10407041.37 | 0.160096E+09 | 0.149300E+10 | 0.823991E+09 | 16143.32 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.290981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292619E+10 | 0.00 | 0.00 | 0.62 |
February | 0.267862E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177594E+10 | 0.00 | 0.00 | 0.62 |
March | 0.314561E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.62 |
April | 0.304670E+11 | 0.00 | 0.00 | 0.00 | 7884634.24 | 0.00 | 0.00 | 0.00 | 0.62 |
May | 0.245791E+11 | 0.00 | 0.00 | 0.00 | 0.165678E+09 | 0.00 | 0.00 | 0.00 | 0.63 |
June | 0.630828E+10 | 14530643.96 | 0.00 | 16.21 | 0.713458E+10 | 0.00 | 2509010.38 | 0.00 | 0.63 |
July | 0.312642E+09 | 0.456937E+09 | 0.00 | 51850.92 | 0.170528E+11 | 0.00 | 27401967.29 | 0.00 | 0.62 |
August | 0.358759E+10 | 0.130016E+10 | 0.00 | 495793.33 | 0.938050E+10 | 0.00 | 0.282215E+09 | 0.00 | 0.62 |
September | 0.132265E+11 | 0.151559E+09 | 0.00 | 39489.47 | 0.366462E+10 | 0.00 | 13099296.88 | 0.00 | 0.63 |
October | 0.265918E+11 | 0.00 | 0.00 | 0.00 | 0.292647E+09 | 0.00 | 0.00 | 0.00 | 0.63 |
November | 0.326610E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.62 |
December | 0.295460E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.935612E+09 | 0.00 | 0.00 | 0.62 |
Annual Sum or Average | 0.254620E+12 | 0.192319E+10 | 0.00 | 587149.92 | 0.376987E+11 | 0.563774E+10 | 0.325226E+09 | 0.00 | 0.62 |
Minimum of Months | 0.312642E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.62 |
Maximum of Months | 0.326610E+11 | 0.130016E+10 | 0.00 | 495793.33 | 0.170528E+11 | 0.292619E+10 | 0.282215E+09 | 0.00 | 0.63 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 12754832.38 | 0.00 | 0.00 | 97690.70 | 0.00 | 0.371385E+09 | 7344173.20 | 0.00 | 0.35 |
February | 13899921.80 | 0.00 | 0.00 | 181819.80 | 0.00 | 0.330229E+09 | 13934132.19 | 0.00 | 0.35 |
March | 14202415.91 | 12975.15 | 0.00 | 805741.80 | 10116.91 | 0.272628E+09 | 88618104.65 | 0.00 | 0.35 |
April | 12184767.32 | 288495.02 | 0.00 | 1789452.45 | 0.00 | 0.163448E+09 | 0.154117E+09 | 0.00 | 0.35 |
May | 3209047.63 | 4331461.88 | 3862.08 | 3261411.05 | 184505.74 | 27122439.97 | 0.224258E+09 | 1190.26 | 0.36 |
June | 0.00 | 0.140381E+09 | 49605.93 | 1679246.81 | 93071.64 | 97340.38 | 51173258.33 | 3706.54 | 0.36 |
July | 0.00 | 0.280266E+09 | 268341.57 | 66099.51 | 0.00 | 6028.55 | 360018.44 | 8511.06 | 0.36 |
August | 0.00 | 0.194313E+09 | 179134.81 | 875133.26 | 0.00 | 56918.37 | 17119332.35 | 4427.88 | 0.36 |
September | 1154210.89 | 69764174.47 | 75180.98 | 2170160.89 | 1007644.80 | 3552643.07 | 0.111892E+09 | 5781.93 | 0.35 |
October | 3688439.71 | 12446710.75 | 2969.07 | 2132107.51 | 12238.77 | 63151676.24 | 0.191998E+09 | 1552.71 | 0.35 |
November | 16584290.90 | 0.00 | 0.00 | 339697.53 | 0.00 | 0.280479E+09 | 66289111.89 | 0.00 | 0.36 |
December | 14059774.19 | 0.00 | 0.00 | 116444.71 | 0.00 | 0.352481E+09 | 11631864.18 | 0.00 | 0.36 |
Annual Sum or Average | 91737700.74 | 0.701804E+09 | 579094.44 | 13515006.01 | 1307577.86 | 0.186464E+10 | 0.938734E+09 | 25170.39 | 0.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 66099.51 | 0.00 | 6028.55 | 360018.44 | 0.00 | 0.35 |
Maximum of Months | 16584290.90 | 0.280266E+09 | 268341.57 | 3261411.05 | 1007644.80 | 0.371385E+09 | 0.224258E+09 | 8511.06 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 7686310.76 | 0.00 | 0.00 | 18126.97 | 0.00 | 0.381801E+09 | 2030018.27 | 0.00 | 0.35 |
February | 9066271.04 | 0.00 | 0.00 | 44937.71 | 0.00 | 0.341688E+09 | 7404128.28 | 0.00 | 0.35 |
March | 21900416.01 | 0.00 | 0.00 | 426226.95 | 23089.35 | 0.303423E+09 | 50461228.68 | 0.00 | 0.35 |
April | 26350060.35 | 288461.22 | 0.00 | 1265806.46 | 0.00 | 0.176675E+09 | 0.127210E+09 | 0.00 | 0.35 |
May | 41303093.23 | 3882719.58 | 4061.49 | 2487949.74 | 632739.02 | 28176870.68 | 0.185852E+09 | 970.17 | 0.36 |
June | 22411549.78 | 0.113023E+09 | 33560.26 | 978020.61 | 27452448.69 | 56167.73 | 29497903.56 | 2365.95 | 0.36 |
July | 311874.96 | 0.239816E+09 | 220552.48 | 11566.58 | 40467108.69 | 59.33 | 108594.99 | 6085.62 | 0.36 |
August | 6811662.66 | 0.179405E+09 | 211840.43 | 601040.79 | 14852572.41 | 18519.22 | 10618046.32 | 4638.50 | 0.36 |
September | 37438487.43 | 52791522.11 | 79434.04 | 1161386.50 | 17970637.11 | 2953752.67 | 77201373.18 | 2887.49 | 0.36 |
October | 39419982.98 | 10018490.22 | 11285.30 | 1030773.14 | 2428652.68 | 93125819.72 | 0.127363E+09 | 3582.82 | 0.35 |
November | 20928403.46 | 0.00 | 0.00 | 130484.35 | 0.00 | 0.316625E+09 | 25965911.01 | 0.00 | 0.35 |
December | 10696458.38 | 0.00 | 0.00 | 9818.11 | 0.00 | 0.366448E+09 | 1090592.05 | 0.00 | 0.36 |
Annual Sum or Average | 0.244325E+09 | 0.599225E+09 | 560734.01 | 8166137.92 | 0.103827E+09 | 0.201099E+10 | 0.644803E+09 | 20530.55 | 0.36 |
Minimum of Months | 311874.96 | 0.00 | 0.00 | 9818.11 | 0.00 | 59.33 | 108594.99 | 0.00 | 0.35 |
Maximum of Months | 41303093.23 | 0.239816E+09 | 220552.48 | 2487949.74 | 40467108.69 | 0.381801E+09 | 0.185852E+09 | 6085.62 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 68518949.21 | 0.00 | 0.00 | 2956133.63 | 0.00 | 0.196594E+10 | 0.478300E+09 | 0.00 | 0.40 |
February | 40403780.51 | 0.00 | 0.00 | 4264528.71 | 0.00 | 0.158638E+10 | 0.670495E+09 | 0.00 | 0.40 |
March | 46482239.19 | 148354.67 | 0.00 | 7636623.64 | 0.00 | 0.108652E+10 | 0.127660E+10 | 0.00 | 0.40 |
April | 51915848.87 | 1853433.17 | 0.00 | 11248196.21 | 0.00 | 0.592772E+09 | 0.147404E+10 | 0.00 | 0.40 |
May | 19978823.49 | 27661816.71 | 24942.17 | 17033463.69 | 1350969.17 | 27206931.04 | 0.159234E+10 | 7516.52 | 0.40 |
June | 0.00 | 0.899627E+09 | 248978.34 | 8289324.20 | 2929645.00 | 739469.58 | 0.331147E+09 | 12345.64 | 0.40 |
July | 0.00 | 0.180106E+10 | 1239563.49 | 394185.11 | 0.00 | 21879.77 | 2360255.74 | 42120.81 | 0.40 |
August | 0.00 | 0.124859E+10 | 928488.10 | 5112013.75 | 0.00 | 343126.25 | 0.110516E+09 | 20545.78 | 0.40 |
September | 7415215.57 | 0.448360E+09 | 352922.34 | 14565313.68 | 6473603.25 | 2541479.42 | 0.738508E+09 | 6718.82 | 0.40 |
October | 7873319.73 | 79970831.90 | 17919.65 | 18596829.51 | 78627.86 | 55579187.11 | 0.159455E+10 | 4059.14 | 0.40 |
November | 61212461.76 | 0.00 | 0.00 | 7376590.55 | 0.00 | 0.100520E+10 | 0.126275E+10 | 0.00 | 0.40 |
December | 62577681.18 | 0.00 | 0.00 | 4688298.05 | 0.00 | 0.165714E+10 | 0.705903E+09 | 0.00 | 0.40 |
Annual Sum or Average | 0.366378E+09 | 0.450728E+10 | 2812814.09 | 0.102162E+09 | 10832845.27 | 0.798039E+10 | 0.102375E+11 | 93306.72 | 0.40 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 394185.11 | 0.00 | 21879.77 | 2360255.74 | 0.00 | 0.40 |
Maximum of Months | 68518949.21 | 0.180106E+10 | 1239563.49 | 18596829.51 | 6473603.25 | 0.196594E+10 | 0.159455E+10 | 42120.81 | 0.40 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.101643E+11 | 0.00 | 0.00 | 37605289.09 | 0.00 | 0.00 | 0.367036E+11 | 0.00 | 4.28 |
February | 0.863360E+10 | 0.00 | 0.00 | 33803201.06 | 0.00 | 0.00 | 0.329526E+11 | 0.00 | 4.28 |
March | 0.376628E+10 | 0.00 | 0.00 | 51148536.89 | 0.00 | 0.00 | 0.443985E+11 | 0.00 | 4.46 |
April | 0.125201E+10 | 11602270.72 | 0.00 | 64534661.22 | 0.00 | 0.00 | 0.476429E+11 | 0.00 | 4.67 |
May | 0.179847E+09 | 0.252637E+09 | 0.00 | 87974875.07 | 251029.30 | 0.00 | 0.425161E+11 | 0.00 | 4.99 |
June | 389567.97 | 0.124551E+11 | 0.00 | 49844062.29 | 0.00 | 0.00 | 0.118973E+11 | 0.00 | 5.31 |
July | 0.00 | 0.319948E+11 | 0.00 | 5999645.27 | 0.00 | 0.00 | 0.674081E+09 | 0.00 | 5.37 |
August | 892699.43 | 0.192875E+11 | 0.00 | 36433150.68 | 0.00 | 0.00 | 0.754409E+10 | 0.00 | 5.37 |
September | 98726565.84 | 0.668057E+10 | 0.00 | 64404493.37 | 1454226.45 | 0.00 | 0.233659E+11 | 0.00 | 5.13 |
October | 0.679716E+09 | 0.415802E+09 | 0.00 | 71525109.06 | 9870591.95 | 0.00 | 0.431256E+11 | 0.00 | 4.81 |
November | 0.376438E+10 | 0.00 | 0.00 | 48884371.79 | 0.00 | 0.00 | 0.463502E+11 | 0.00 | 4.48 |
December | 0.703829E+10 | 0.00 | 0.00 | 41746976.40 | 0.00 | 0.00 | 0.380385E+11 | 0.00 | 4.34 |
Annual Sum or Average | 0.355785E+11 | 0.710980E+11 | 0.00 | 0.593904E+09 | 11575847.70 | 0.00 | 0.375209E+12 | 0.00 | 4.79 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 5999645.27 | 0.00 | 0.00 | 0.674081E+09 | 0.00 | 4.28 |
Maximum of Months | 0.101643E+11 | 0.319948E+11 | 0.00 | 87974875.07 | 9870591.95 | 0.00 | 0.476429E+11 | 0.00 | 5.37 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.485705E+10 | 0.00 | 0.00 | 51095442.80 | 0.00 | 0.00 | 0.458734E+11 | 0.00 | 4.63 |
February | 0.474416E+10 | 0.00 | 0.00 | 45990034.84 | 0.00 | 0.00 | 0.401832E+11 | 0.00 | 4.62 |
March | 0.128843E+10 | 0.00 | 0.00 | 66880232.65 | 0.00 | 0.00 | 0.511859E+11 | 0.00 | 4.86 |
April | 0.274749E+09 | 12565266.48 | 0.00 | 79633603.42 | 0.00 | 0.00 | 0.530104E+11 | 0.00 | 5.09 |
May | 4503674.69 | 0.272421E+09 | 0.00 | 0.101570E+09 | 0.00 | 0.00 | 0.463015E+11 | 0.00 | 5.41 |
June | 0.00 | 0.133199E+11 | 0.00 | 54831933.06 | 0.00 | 0.00 | 0.126954E+11 | 0.00 | 5.67 |
July | 0.00 | 0.340636E+11 | 0.00 | 6383363.10 | 0.00 | 0.00 | 0.709764E+09 | 0.00 | 5.71 |
August | 0.00 | 0.205051E+11 | 0.00 | 39781808.94 | 0.00 | 0.00 | 0.797892E+10 | 0.00 | 5.71 |
September | 3691808.48 | 0.713976E+10 | 0.00 | 72815666.22 | 0.00 | 0.00 | 0.252310E+11 | 0.00 | 5.50 |
October | 0.164995E+09 | 0.456403E+09 | 0.00 | 84951025.59 | 712970.87 | 0.00 | 0.472020E+11 | 0.00 | 5.20 |
November | 0.115544E+10 | 0.00 | 0.00 | 63593019.97 | 0.00 | 0.00 | 0.534031E+11 | 0.00 | 4.87 |
December | 0.212149E+10 | 0.00 | 0.00 | 56469698.07 | 0.00 | 0.00 | 0.468879E+11 | 0.00 | 4.71 |
Annual Sum or Average | 0.146145E+11 | 0.757697E+11 | 0.00 | 0.723996E+09 | 712970.87 | 0.00 | 0.430662E+12 | 0.00 | 5.17 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 6383363.10 | 0.00 | 0.00 | 0.709764E+09 | 0.00 | 4.62 |
Maximum of Months | 0.485705E+10 | 0.340636E+11 | 0.00 | 0.101570E+09 | 712970.87 | 0.00 | 0.534031E+11 | 0.00 | 5.71 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 2867343.92 | 0.00 | 0.00 | 0.110093E+09 | 0.00 | 0.00 | 0.699591E+11 | 0.00 | 20.59 |
February | 2885100.82 | 0.00 | 0.00 | 99947141.31 | 0.00 | 0.00 | 0.625357E+11 | 0.00 | 20.79 |
March | 0.00 | 0.00 | 0.00 | 0.116171E+09 | 0.00 | 0.00 | 0.707522E+11 | 0.00 | 21.33 |
April | 0.00 | 21707639.68 | 0.00 | 0.121409E+09 | 0.00 | 0.00 | 0.686857E+11 | 0.00 | 21.83 |
May | 0.00 | 0.455791E+09 | 0.00 | 0.140624E+09 | 0.00 | 0.00 | 0.539625E+11 | 0.00 | 22.41 |
June | 0.00 | 0.181492E+11 | 0.00 | 68122113.02 | 0.00 | 0.00 | 0.132567E+11 | 0.00 | 22.61 |
July | 0.00 | 0.428359E+11 | 0.00 | 6577538.91 | 0.00 | 0.00 | 0.642387E+09 | 0.00 | 22.48 |
August | 0.00 | 0.268773E+11 | 0.00 | 47751607.79 | 0.00 | 0.00 | 0.761522E+10 | 0.00 | 22.60 |
September | 0.00 | 0.950045E+10 | 0.00 | 99736219.90 | 0.00 | 0.00 | 0.286678E+11 | 0.00 | 22.50 |
October | 0.00 | 0.803725E+09 | 0.00 | 0.126671E+09 | 0.00 | 0.00 | 0.592260E+11 | 0.00 | 22.16 |
November | 0.00 | 0.00 | 0.00 | 0.110397E+09 | 0.00 | 0.00 | 0.729431E+11 | 0.00 | 21.32 |
December | 0.00 | 0.00 | 0.00 | 0.111421E+09 | 0.00 | 0.00 | 0.671136E+11 | 0.00 | 20.92 |
Annual Sum or Average | 5752444.74 | 0.986441E+11 | 0.00 | 0.115892E+10 | 0.00 | 0.00 | 0.575360E+12 | 0.00 | 21.80 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 6577538.91 | 0.00 | 0.00 | 0.642387E+09 | 0.00 | 20.59 |
Maximum of Months | 2885100.82 | 0.428359E+11 | 0.00 | 0.140624E+09 | 0.00 | 0.00 | 0.729431E+11 | 0.00 | 22.61 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.130139E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.303494E+10 | 0.00 | 0.00 | 1.17 |
February | 0.117611E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255273E+10 | 0.00 | 0.00 | 1.17 |
March | 0.157238E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 40261242.79 | 0.00 | 0.00 | 1.17 |
April | 0.152684E+11 | 0.00 | 0.00 | 0.00 | 3951351.68 | 0.00 | 0.00 | 0.00 | 1.18 |
May | 0.122522E+11 | 55895112.65 | 0.00 | 67516.12 | 28125248.28 | 0.00 | 65448477.11 | 0.00 | 1.19 |
June | 0.298183E+10 | 0.153602E+10 | 0.00 | 603219.54 | 0.206930E+10 | 0.00 | 0.180198E+09 | 0.00 | 1.19 |
July | 77116571.02 | 0.606810E+10 | 0.00 | 374544.33 | 0.292300E+10 | 0.00 | 93087019.27 | 0.00 | 1.20 |
August | 0.147162E+10 | 0.483265E+10 | 0.00 | 1380891.54 | 0.831989E+09 | 0.00 | 0.467890E+09 | 0.00 | 1.22 |
September | 0.637440E+10 | 0.625049E+09 | 0.00 | 685752.30 | 0.130729E+10 | 0.00 | 0.260244E+09 | 0.00 | 1.19 |
October | 0.133196E+11 | 19797885.84 | 0.00 | 1354.06 | 0.126861E+09 | 0.00 | 6788925.89 | 0.00 | 1.18 |
November | 0.162114E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156598E+09 | 0.00 | 0.00 | 1.17 |
December | 0.150625E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213170E+09 | 0.00 | 0.00 | 1.17 |
Annual Sum or Average | 0.123518E+12 | 0.131375E+11 | 0.00 | 3113277.89 | 0.729052E+10 | 0.599770E+10 | 0.107366E+10 | 0.00 | 1.18 |
Minimum of Months | 77116571.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 |
Maximum of Months | 0.162114E+11 | 0.606810E+10 | 0.00 | 1380891.54 | 0.292300E+10 | 0.303494E+10 | 0.467890E+09 | 0.00 | 1.22 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:21:32
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.136522E+12 | 0.930895E+10 | 0.271099E+12 | 0.107454E+13 | 0.798946E+11 |
February | 0.228319E+12 | 0.891899E+10 | 0.257525E+12 | 0.102672E+13 | 0.707033E+11 |
March | 0.412915E+12 | 0.757571E+10 | 0.221369E+12 | 0.891149E+12 | 0.863665E+11 |
April | 0.441397E+12 | 0.525156E+10 | 0.152599E+12 | 0.615878E+12 | 0.159144E+12 |
May | 0.570918E+12 | 0.350755E+10 | 0.959558E+11 | 0.392133E+12 | 0.308734E+12 |
June | 0.568184E+12 | -0.106182E+10 | -0.169768E+11 | -0.806081E+11 | 0.894035E+12 |
July | 0.540768E+12 | -0.464135E+10 | -0.116801E+12 | -0.523077E+12 | 0.136342E+13 |
August | 0.515996E+12 | -0.256755E+10 | -0.719987E+11 | -0.308727E+12 | 0.115768E+13 |
September | 0.353976E+12 | 0.892145E+09 | 0.309077E+11 | 0.117148E+12 | 0.663123E+12 |
October | 0.340092E+12 | 0.404712E+10 | 0.112207E+12 | 0.476130E+12 | 0.321379E+12 |
November | 0.163133E+12 | 0.654262E+10 | 0.193762E+12 | 0.783699E+12 | 0.103276E+12 |
December | 0.109488E+12 | 0.841109E+10 | 0.251229E+12 | 0.994295E+12 | 0.701308E+11 |