Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904
Simulation Timestamp: 2024-07-03 12:21:51
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:51
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 10038.27 | 884.80 | 884.80 |
Net Site Energy | 10038.27 | 884.80 | 884.80 |
Total Source Energy | 21021.05 | 1852.84 | 1852.84 |
Net Source Energy | 21021.05 | 1852.84 | 1852.84 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 902.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 664.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 783.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 193.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1658.18 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 813.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 520.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 75.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 94.78 | 2478.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | 62.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 4867.77 | 5170.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 902.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 664.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 783.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 193.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 872.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 14.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 8.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 21.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 789.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 2.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 520.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 75.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 94.78 | 2478.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5742.51 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.69 | |
Refrigeration | General | 7.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 20.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 34.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 902.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 664.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 783.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 193.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 1658.18 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 813.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 520.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 75.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 94.78 | 2478.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | Unassigned | 62.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 86.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 119.54 | 298.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 223.38 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 429.06 | 455.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 86.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 119.54 | 298.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 223.38 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 429.06 | 455.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 4867.769 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 4867.769 | 100.00 |
Total On-Site and Utility Electric Sources | 4867.769 | 100.00 |
Total Electricity End Uses | 4867.769 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9857.19 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9857.19 | 100.00 |
Total Water End Uses | 9857.19 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 56.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 7296.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER1 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| FLR_3_DOAS COOLING COIL | VAV WITH REHEAT COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH LAUNDRY G WATER HEATER | SWH BOOSTER E WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |CoilReportMonthly
| FLR_3_DOAS HEATING COIL | VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | FLR_3_DOAS COOLING COIL | VAV WITH REHEAT COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |FanReportMonthly
| FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL_FANCOILFAN | ROOM_2_FLR_3 FAN COIL_FANCOILFAN | ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | ROOM_5_FLR_3 FAN COIL_FANCOILFAN | ROOM_6_FLR_3 FAN COIL_FANCOILFAN | ROOM_1_FLR_6 FAN COIL_FANCOILFAN | ROOM_2_FLR_6 FAN COIL_FANCOILFAN | ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| FLR_3_DOAS | VAV WITH REHEAT |AirLoopSystemComponentLoadsMonthly
| FLR_3_DOAS | VAV WITH REHEAT |AirLoopSystemComponentEnergyUseMonthly
| FLR_3_DOAS | VAV WITH REHEAT |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:51
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21 |
RunPeriod | RUNPERIOD 1 |
Weather File | San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 |
Latitude [deg] | 32.58 |
Longitude [deg] | -117.0 |
Elevation [m] | 159.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 8.8143 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.26 | 23.26 | 11.3140 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 11.3140 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 4.6285 | 61.93 | 5.3800 |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 5.7199 | 46.45 | 2.6900 |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 4.6285 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.50 | 65.50 | 10.0104 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.08 | 85.08 | 10.7639 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 8.2882 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 8.2882 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 7.1042 | 18.58 | 0.0000 |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.74 | 6.74 | 8.2882 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 10.0104 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 10.0104 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.37 | 26.37 | 11.4097 | 4.65 | 2934.4875 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.20 | 28.20 | 7.1042 | 18.58 | 0.0000 |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 8.5566 | 7.07 | 41.0709 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 8.5566 | 7.07 | 41.0709 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 1978.83 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 8.8143 | 18.58 | 5.3800 | |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 1.00 | RETAIL_1_FLR_1 | GENERAL | RETAIL_1_FLR_1 | 11.3140 | 6.19 | 10.7600 | |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 1.00 | RETAIL_2_FLR_1 | GENERAL | RETAIL_2_FLR_1 | 11.3140 | 6.19 | 10.7600 | |
MECH_FLR_1 | 164.24 | Yes | Yes | 1.00 | MECH_FLR_1 | GENERAL | MECH_FLR_1 | 4.6285 | 61.93 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 1.00 | STORAGE_FLR_1 | GENERAL | STORAGE_FLR_1 | 5.7199 | 46.45 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 1.00 | LAUNDRY_FLR_1 | GENERAL | LAUNDRY_FLR_1 | 4.6285 | 9.29 | 597.5300 | |
CAFE_FLR_1 | 188.86 | Yes | Yes | 1.00 | CAFE_FLR_1 | GENERAL | CAFE_FLR_1 | 10.0104 | 1.33 | 5.3800 | |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 1.00 | LOBBY_FLR_1 | GENERAL | LOBBY_FLR_1 | 10.7639 | 3.10 | 8.0700 | |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_1_FLR_3 | GENERAL | ROOM_1_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_2_FLR_3 | GENERAL | ROOM_2_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 76.00 | ROOM_3_MULT19_FLR_3 | GENERAL | ROOM_3_MULT19_FLR_3 | 8.2882 | 16.35 | 10.5200 | |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 76.00 | ROOM_4_MULT19_FLR_3 | GENERAL | ROOM_4_MULT19_FLR_3 | 8.2882 | 16.35 | 10.5200 | |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_5_FLR_3 | GENERAL | ROOM_5_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_6_FLR_3 | GENERAL | ROOM_6_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 4.00 | CORRIDOR_FLR_3 | GENERAL | CORRIDOR_FLR_3 | 7.1042 | 18.58 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_1_FLR_6 | GENERAL | ROOM_1_FLR_6 | 8.2882 | 26.01 | 6.7500 | |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_2_FLR_6 | GENERAL | ROOM_2_FLR_6 | 8.2882 | 26.01 | 6.7500 | |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 9.00 | ROOM_3_MULT9_FLR_6 | GENERAL | ROOM_3_MULT9_FLR_6 | 8.2882 | 16.35 | 10.5200 | |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1.00 | BANQUET_FLR_6 | GENERAL | BANQUET_FLR_6 | 10.0104 | 1.33 | 67.8200 | |
DINING_FLR_6 | 331.66 | Yes | Yes | 1.00 | DINING_FLR_6 | GENERAL | DINING_FLR_6 | 10.0104 | 1.33 | 67.8200 | |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 1.00 | KITCHEN_FLR_6 | GENERAL | KITCHEN_FLR_6 | 11.4097 | 4.65 | 2934.4875 | |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1.00 | CORRIDOR_FLR_6 | GENERAL | CORRIDOR_FLR_6 | 7.1042 | 18.58 | 0.0000 | |
Total | 11345.29 | 8.5566 | 3.54 | 41.0709 | |||||||
Conditioned Total | 11345.29 | 8.5566 | 3.54 | 41.0709 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 11345.29 | 11345.29 | 0.00 | 0.00 | 4.6520 | 8.82 | 37.1989 |
Total | 11345.29 | 11345.29 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:51
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 29-SEP-18:00 | 29-MAR-17:00 | - | - | - | - | - | - | - | - | - | - | 05-MAY-20:30 |
Heating | 0.00 | 141315.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 114713.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 57474.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 12338.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 77573.37 | 104248.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 28169.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 26461.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2841.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 4751.09 | 220447.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1814.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 326139.69 | 466011.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 141315.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 114713.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 57474.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 12338.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 47590.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 29272.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1050.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 26968.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 150.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 26461.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 2841.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 4751.09 | 220447.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 228.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 527.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1058.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:51
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 978.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2105.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2480.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 614.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5251.45 | 1939.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2577.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1648.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 240.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 300.18 | 2687.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 197.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 15416.22 | 5604.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 185.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 218.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 54.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 462.88 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 227.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 145.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 21.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 26.46 | 236.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1358.82 | 494.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 185.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 218.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 54.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 462.88 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 227.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 145.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 21.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 26.46 | 236.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1358.82 | 494.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:51
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
BASEMENT VAV BOX COMPONENT | 2.44 | 0.619015 | 0.547000 | 1.33 | 1.00 | 0.500000 | 0.000615 | 0.000060 | 1.33 | 16.70 | 0.008000 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.312360 | 0.163620 | 0.547000 | 0.170861 | 0.547000 | 0.500000 | 0.002329 | 0.000022 | 0.170861 | 16.70 | 0.008000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.227768 | 0.259842 | 0.547000 | 0.124589 | 0.692911 | 0.500000 | 0.001466 | 0.000011 | 0.124589 | 16.70 | 0.008000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.181082 | 0.691141 | 0.547000 | 0.099052 | 1.00 | 0.500000 | 0.000551 | 0.000013 | 0.099052 | 16.70 | 0.008000 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.106271 | 0.679459 | 0.547000 | 0.058130 | 1.00 | 0.500000 | 0.000561 | 0.000008 | 0.058130 | 16.70 | 0.008000 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 3.30 | 0.018040 | 0.547000 | 1.80 | 0.547000 | 0.500000 | 0.021120 | 0.000093 | 1.80 | 16.70 | 0.008000 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.38 | 0.104135 | 0.547000 | 0.755944 | 0.547000 | 0.500000 | 0.003659 | 0.000072 | 0.755944 | 16.70 | 0.008000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 4.66 | 0.213759 | 0.547000 | 2.55 | 0.570024 | 0.500000 | 0.001782 | 0.000203 | 2.55 | 16.70 | 0.008000 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.42 | 0.833401 | 0.547000 | 0.779022 | 1.00 | 0.500000 | 0.000457 | 0.000088 | 0.779022 | 16.70 | 0.008000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.12 | 0.119240 | 0.547000 | 1.16 | 0.547000 | 0.500000 | 0.003195 | 0.000087 | 1.16 | 16.70 | 0.008000 |
DINING_FLR_6 VAV BOX COMPONENT | 2.22 | 0.113706 | 0.547000 | 1.22 | 0.547000 | 0.500000 | 0.003351 | 0.000090 | 1.22 | 16.70 | 0.008000 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.22 | 0.063646 | 0.547000 | 1.22 | 0.547000 | 0.500000 | 0.010767 | 0.000059 | 1.22 | 16.70 | 0.008000 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 0.704597 | 0.445700 | 0.547000 | 0.385415 | 1.00 | 0.500000 | 0.000855 | 0.000054 | 0.385415 | 16.70 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
BASEMENT VAV BOX REHEAT COIL | 6904.49 | 0.000060 | 143.98 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 2567.64 | 0.000022 | 59.46 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1207.82 | 0.000011 | 26.38 |
MECH_FLR_1 VAV BOX REHEAT COIL | 1513.84 | 0.000013 | 35.16 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 971.37 | 0.000008 | 22.94 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 10644.59 | 0.000093 | 223.59 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 8207.96 | 0.000072 | 181.52 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 23179.43 | 0.000203 | 503.11 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | 3704.30 | 0.000032 | 105.84 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | 3704.51 | 0.000032 | 105.85 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 21626.49 | 0.000189 | 617.91 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 21641.02 | 0.000189 | 618.32 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | 3703.47 | 0.000032 | 105.82 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | 3703.68 | 0.000032 | 105.82 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 10059.28 | 0.000088 | 227.50 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | 1153.43 | 0.000010 | 32.96 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | 1152.99 | 0.000010 | 32.94 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 5585.51 | 0.000049 | 159.59 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 9904.56 | 0.000087 | 213.76 |
DINING_FLR_6 VAV BOX REHEAT COIL | 10253.90 | 0.000090 | 221.04 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 6758.61 | 0.000059 | 141.47 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 6157.45 | 0.000054 | 144.16 |
FLR_3_DOAS HEATING COIL | 9427.25 | 0.000082 | 168.97 |
VAV WITH REHEAT HEATING COIL | 97345.61 | 0.000852 | 1744.76 |
Design Size Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 0.061735 |
ROOM_2_FLR_3 DIRECT AIR | 0.061728 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 0.837072 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 0.837300 |
ROOM_5_FLR_3 DIRECT AIR | 0.061735 |
ROOM_6_FLR_3 DIRECT AIR | 0.061728 |
ROOM_1_FLR_6 DIRECT AIR | 0.015434 |
ROOM_2_FLR_6 DIRECT AIR | 0.015432 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 0.099154 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Hot Water Flow [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 0.978062 | 0.000032 | 0.000306 |
ROOM_2_FLR_3 FAN COIL | 0.941639 | 0.000032 | 0.000295 |
ROOM_3_MULT19_FLR_3 FAN COIL | 6.11 | 0.000189 | 0.001874 |
ROOM_4_MULT19_FLR_3 FAN COIL | 5.74 | 0.000189 | 0.001881 |
ROOM_5_FLR_3 FAN COIL | 0.869152 | 0.000032 | 0.000273 |
ROOM_6_FLR_3 FAN COIL | 0.836813 | 0.000032 | 0.000263 |
ROOM_1_FLR_6 FAN COIL | 0.253311 | 0.000010 | 0.000079 |
ROOM_2_FLR_6 FAN COIL | 0.243315 | 0.000010 | 0.000076 |
ROOM_3_MULT9_FLR_6 FAN COIL | 1.19 | 0.000049 | 0.000379 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COIL_FANCOILFAN | 0.978062 |
ROOM_2_FLR_3 FAN COIL_FANCOILFAN | 0.941639 |
ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | 6.11 |
ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | 5.74 |
ROOM_5_FLR_3 FAN COIL_FANCOILFAN | 0.869152 |
ROOM_6_FLR_3 FAN COIL_FANCOILFAN | 0.836813 |
ROOM_1_FLR_6 FAN COIL_FANCOILFAN | 0.253311 |
ROOM_2_FLR_6 FAN COIL_FANCOILFAN | 0.243315 |
ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN | 1.19 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Coil Load [W] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008574 | 12.80 | 0.008500 | 0.000306 | 0.978062 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008576 | 12.80 | 0.008500 | 0.000295 | 0.941639 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008498 | 12.80 | 0.008498 | 0.001874 | 6.11 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008746 | 12.80 | 0.008500 | 0.001881 | 5.74 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008583 | 12.80 | 0.008500 | 0.000273 | 0.869152 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008586 | 12.80 | 0.008500 | 0.000263 | 0.836813 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008571 | 12.80 | 0.008500 | 0.000079 | 0.253311 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008574 | 12.80 | 0.008500 | 0.000076 | 0.243315 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008639 | 12.80 | 0.008500 | 0.000379 | 1.19 | |
FLR_3_DOAS COOLING COIL | 31.30 | 6.70 | 0.008233 | 11.91 | 0.008233 | 0.001371 | 2.05 | 47946.25 |
VAV WITH REHEAT COOLING COIL | 28.02 | 6.70 | 0.008891 | 10.94 | 0.008500 | 0.013188 | 21.18 | 461117.25 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
VAV WITH REHEAT | 11.65 | 11.65 | 21.30 | 11.65 | 21.18 | 21.18 | 0.300000 | 0.550063 | 21.18 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
VAV WITH REHEAT_OA_CONTROLLER | 21.18 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS FAN | 2.05 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.001371 | 0.000347 |
FLR_3_DOAS_HEATC_CONTROLLER | 0.000082 | |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.013188 | 0.000036 |
VAV WITH REHEAT_HEATC_CONTROLLER | 0.000852 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT FAN | 21.18 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.019985 | 3263.02 | |
HEATSYS1 PUMP | 0.002372 | 714.20 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.002372 | 0.284582 |
COOLSYS1 | 0.019985 | 2.40 |
SWHSYS1 | 0.000375 | 0.045004 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 271079.21 | 271079.21 | 0.002372 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.019985 | 2259.10 |
SWHSYS1 PUMP | 0.000375 | 47.91 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.019985 | 698796.70 | 699394.26 | 79.73 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000375 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:51
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:51
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:51
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.80 | 14.30 | 13.60 | 13.20 | 13.30 | 12.60 | 15.30 | 15.60 | 17.70 | 19.40 | 19.70 | 18.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 | 32.58 | -116.98 | -8.00 | 159.00 | 99429 | 1.1818 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 16.00 | 7.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.58 | 23.26 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.72 | 65.50 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.80 | 85.08 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.70 | 6.74 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.96 | 26.37 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.27 | 28.20 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 8.814 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 14.194 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 11.314 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 22.074 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 11.314 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 22.074 | No |
4 | MECH_FLR_1 | 164.24 | 2.7 | 61.932 | 1.615E-002 | 4.628 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 10.008 | No |
5 | STORAGE_FLR_1 | 94.76 | 2.0 | 46.451 | 2.153E-002 | 5.720 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 8.410 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 4.628 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 602.158 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 10.010 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 15.390 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 10.764 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.834 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 8.288 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 18.808 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 8.288 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 18.808 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 21.0 | 18.581 | 5.382E-002 | 7.104 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.104 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 8.288 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 18.808 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 10.010 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 77.830 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 10.010 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 77.830 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 11.410 | 515.227 | 2419.260 | 0.000 | 0.000 | 0.000 | 2945.897 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 22.2 | 18.581 | 5.382E-002 | 7.104 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.104 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | STORAGE_FLR_1 PEOPLE | BLDG_OCC_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.0 | 2.153E-002 | 46.451 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | CORRIDOR_FLR_3 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 21.0 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 21 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
21 | CORRIDOR_FLR_6 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 22.2 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
22 | MECH_FLR_1 PEOPLE | BLDG_OCC_SCH | MECH_FLR_1 | 164.24 | 2.7 | 2.7 | 1.615E-002 | 61.932 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 3 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_BASEMENT | BASEMENT | 1978.83 | 106.5 | 17441.963 | 8.814 | 163.776 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 17441.963 |
2 | RETAIL_1_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_1_FLR_1 | 67.07 | 10.8 | 758.849 | 11.314 | 70.076 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 758.849 |
3 | RETAIL_2_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_2_FLR_1 | 77.67 | 12.5 | 878.750 | 11.314 | 70.076 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 878.750 |
4 | MECH_FLR_1_LIGHTS | LTG_SCH_MECHANIC | MECH_FLR_1 | 164.24 | 2.7 | 760.196 | 4.628 | 286.650 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 760.196 |
5 | STORAGE_FLR_1_LIGHTS | LTG_SCH_STORAGE | STORAGE_FLR_1 | 94.76 | 2.0 | 542.017 | 5.720 | 265.695 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 542.017 |
6 | LAUNDRY_FLR_1_LIGHTS | LTG_SCH_LAUNDRY | LAUNDRY_FLR_1 | 78.04 | 8.4 | 361.204 | 4.628 | 43.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 361.204 |
7 | CAFE_FLR_1_LIGHTS | LTG_SCH_DINING | CAFE_FLR_1 | 188.86 | 142.3 | 1890.589 | 10.010 | 13.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1890.589 |
8 | LOBBY_FLR_1_LIGHTS | LTG_SCH_LOBBY | LOBBY_FLR_1 | 1308.19 | 422.4 | 14081.185 | 10.764 | 33.333 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14081.185 |
9 | ROOM_1_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_3 | 39.02 | 1.5 | 323.422 | 8.288 | 215.615 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.422 |
10 | ROOM_2_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_3 | 39.02 | 1.5 | 323.384 | 8.288 | 215.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.384 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 203.259 | 8.288 | 135.506 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 203.259 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 203.314 | 8.288 | 135.543 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 203.314 |
13 | ROOM_5_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_5_FLR_3 | 39.02 | 1.5 | 323.422 | 8.288 | 215.615 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.422 |
14 | ROOM_6_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_6_FLR_3 | 39.02 | 1.5 | 323.384 | 8.288 | 215.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.384 |
15 | CORRIDOR_FLR_3_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2766.397 | 7.104 | 132.003 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2766.397 |
16 | ROOM_1_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_6 | 39.02 | 1.5 | 323.422 | 8.288 | 215.615 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.422 |
17 | ROOM_2_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_6 | 39.02 | 1.5 | 323.384 | 8.288 | 215.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.384 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 203.314 | 8.288 | 135.543 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 203.314 |
19 | BANQUET_FLR_6_LIGHTS | LTG_SCH_DINING | BANQUET_FLR_6 | 331.66 | 249.9 | 3320.034 | 10.010 | 13.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3320.034 |
20 | DINING_FLR_6_LIGHTS | LTG_SCH_DINING | DINING_FLR_6 | 331.66 | 249.9 | 3320.034 | 10.010 | 13.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3320.034 |
21 | KITCHEN_FLR_6_LIGHTS | LTG_SCH_KITCHEN | KITCHEN_FLR_6 | 103.30 | 22.2 | 1178.676 | 11.410 | 53.003 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1178.676 |
22 | CORRIDOR_FLR_6_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_6 | 412.12 | 22.2 | 2927.804 | 7.104 | 132.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2927.804 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 2.7 | 883.628 | 5.380 | 333.193 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 254.902 | 2.690 | 124.952 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 457.500 | 4.429 | 20.573 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 457.500 | 457.500 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 285.000 | 2.759 | 12.816 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 285.000 | 285.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 2.390 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
6 | RES_ROOF | 19 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
7 | NONRES_EXT_WALL_GRD | 21 | 3 | 9 | 0.167 | 0.9589 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | NONRES_EXT_WALL_MID | 22 | 3 | 9 | 0.167 | 1.167 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | NONRES_EXT_WALL_TOP | 23 | 3 | 9 | 0.167 | 1.181 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | RES_EXT_WALL_MID | 25 | 3 | 9 | 0.167 | 1.021 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | RES_EXT_WALL_TOP | 26 | 3 | 9 | 0.167 | 1.034 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | NONRES_FLOOR | 30 | 3 | 7 | 0.167 | 0.3181 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
13 | NONRES_FLOOR_CEILING | 33 | 3 | 7 | 0.167 | 0.3181 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
14 | BASEMENT_FLOOR | 36 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
15 | BASEMENT_WALL_NORTH_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | BASEMENT_WALL_EAST_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | BASEMENT_WALL_SOUTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
18 | BASEMENT_WALL_WEST_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4184 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
10 | RES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
11 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
12 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8756 |
14 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6894 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6793 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | RES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8120 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
25 | RES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7993 |
26 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
27 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.883 |
28 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
29 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
30 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
31 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
32 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.883 |
33 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
34 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
35 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
39 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
40 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
41 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
42 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 2.3900722 | 2.3900722 | 2.3900722 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
21 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
22 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
23 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
24 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
25 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
26 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
27 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
28 | 9 | -0.56372661E-17 | 0.35603042E-16 | -0.14834456E-09 | -0.22354951E-17 |
29 | 8 | 0.21681598E-07 | 0.12895413E-12 | 0.37576420E-03 | -0.24652724E-09 |
30 | 7 | -0.12181032E-01 | 0.67087143E-08 | -0.22998674E-01 | 0.13850277E-03 |
31 | 6 | 0.40370585 | 0.23395349E-05 | 0.47069069 | -0.47283774E-02 |
32 | 5 | -5.1745154 | 0.87537405E-04 | -4.4305073 | 0.62984858E-01 |
33 | 4 | 32.931872 | 0.71743813E-03 | 21.398312 | -0.42118042 |
34 | 3 | -111.07522 | 0.15662534E-02 | -55.540939 | 1.5130129 |
35 | 2 | 196.98158 | 0.88235367E-03 | 77.798628 | -2.8983416 |
36 | 1 | -171.10930 | 0.94326468E-04 | -55.232514 | 2.7446195 |
37 | 0 | 57.057407 | 0.53780718E-06 | 15.562302 | |
38 | 9 | 0.13788181E-14 | 0.42316407E-16 | -0.13850765E-09 | -0.36591458E-17 |
39 | 8 | 0.20295421E-07 | 0.15509090E-12 | 0.36099725E-03 | -0.23076592E-09 |
40 | 7 | -0.11739701E-01 | 0.81955471E-08 | -0.22363010E-01 | 0.13348467E-03 |
41 | 6 | 0.39171309 | 0.28760220E-05 | 0.46045976 | -0.45870120E-02 |
42 | 5 | -5.0574682 | 0.10819265E-03 | -4.3518524 | 0.61533536E-01 |
43 | 4 | 32.414067 | 0.89103805E-03 | 21.090697 | -0.41430552 |
44 | 3 | -109.97331 | 0.19536482E-02 | -54.932704 | 1.4970936 |
45 | 2 | 195.88922 | 0.11048200E-02 | 77.241099 | -2.8809953 |
46 | 1 | -170.70571 | 0.11852782E-03 | -55.070977 | 2.7375462 |
47 | 0 | 57.057407 | 0.67841551E-06 | 15.589460 | |
48 | 9 | 0.13857471E-14 | 0.43057560E-16 | -0.13784678E-09 | -0.68945926E-17 |
49 | 8 | 0.20202246E-07 | 0.15680163E-12 | 0.35999259E-03 | -0.22970649E-09 |
50 | 7 | -0.11709634E-01 | 0.82948599E-08 | -0.22319691E-01 | 0.13314280E-03 |
51 | 6 | 0.39089600 | 0.29121450E-05 | 0.45976168 | -0.45773805E-02 |
52 | 5 | -5.0494928 | 0.10959277E-03 | -4.3464810 | 0.61434646E-01 |
53 | 4 | 32.378781 | 0.90287364E-03 | 21.069680 | -0.41383702 |
54 | 3 | -109.89821 | 0.19801908E-02 | -54.891143 | 1.4960086 |
55 | 2 | 195.81476 | 0.11201274E-02 | 77.203021 | -2.8798128 |
56 | 1 | -170.67819 | 0.12019965E-03 | -55.059979 | 2.7370639 |
57 | 0 | 57.057407 | 0.68811227E-06 | 15.591337 | |
58 | 9 | 0.14302076E-15 | 0.35792568E-16 | -0.14541430E-09 | -0.27421543E-17 |
59 | 8 | 0.21269444E-07 | 0.13686051E-12 | 0.37140784E-03 | -0.24184090E-09 |
60 | 7 | -0.12050952E-01 | 0.71525680E-08 | -0.22811354E-01 | 0.13702371E-03 |
61 | 6 | 0.40017121 | 0.24988627E-05 | 0.46767819 | -0.46867126E-02 |
62 | 5 | -5.1400200 | 0.93645327E-04 | -4.4073602 | 0.62557131E-01 |
63 | 4 | 32.779281 | 0.76858103E-03 | 21.307814 | -0.41915444 |
64 | 3 | -110.75053 | 0.16800125E-02 | -55.362013 | 1.5083221 |
65 | 2 | 196.65975 | 0.94749847E-03 | 77.634567 | -2.8932310 |
66 | 1 | -170.99041 | 0.10139533E-03 | -55.184883 | 2.7425359 |
67 | 0 | 57.057407 | 0.57877233E-06 | 15.570231 | |
68 | 9 | 0.33566835E-16 | 0.35384250E-16 | -0.14478218E-09 | -0.87565041E-18 |
69 | 8 | 0.21180494E-07 | 0.13854999E-12 | 0.37046393E-03 | -0.24082951E-09 |
70 | 7 | -0.12022754E-01 | 0.72481687E-08 | -0.22770744E-01 | 0.13670309E-03 |
71 | 6 | 0.39940498 | 0.25332696E-05 | 0.46702484 | -0.46776806E-02 |
72 | 5 | -5.1325420 | 0.94967185E-04 | -4.4023386 | 0.62464408E-01 |
73 | 4 | 32.746200 | 0.77967008E-03 | 21.288178 | -0.41871522 |
74 | 3 | -110.68014 | 0.17047184E-02 | -55.323188 | 1.5073051 |
75 | 2 | 196.58997 | 0.96166638E-03 | 77.598974 | -2.8921229 |
76 | 1 | -170.96463 | 0.10293464E-03 | -55.174560 | 2.7420841 |
77 | 0 | 57.057407 | 0.58770932E-06 | 15.571958 | |
78 | 7 | -0.11407965E-14 | 0.23474115E-16 | -0.22119674E-13 | 0.51962024E-15 |
79 | 6 | 0.16676876E-10 | 0.39440661E-11 | 0.52102403E-09 | -0.18553030E-10 |
80 | 5 | -0.80001662E-07 | 0.19215958E-07 | -0.21848785E-05 | 0.17095694E-06 |
81 | 4 | 0.10228101E-03 | 0.72538432E-05 | 0.17630655E-02 | -0.28160064E-03 |
82 | 3 | -0.15120274E-01 | 0.25611913E-03 | -0.21515117 | 0.43248511E-01 |
83 | 2 | 0.21482172 | 0.11124906E-02 | 2.8969963 | -0.61829830 |
84 | 1 | -0.54366453 | 0.69706713E-03 | -7.1337069 | 1.5687761 |
85 | 0 | 0.34594624 | 0.12518961E-04 | 4.4521846 | |
86 | 7 | -0.22119674E-13 | 0.23474115E-16 | -0.11407965E-14 | 0.51962024E-15 |
87 | 6 | 0.52102403E-09 | 0.39440661E-11 | 0.16676876E-10 | -0.18553030E-10 |
88 | 5 | -0.21848785E-05 | 0.19215958E-07 | -0.80001662E-07 | 0.17095694E-06 |
89 | 4 | 0.17630655E-02 | 0.72538432E-05 | 0.10228101E-03 | -0.28160064E-03 |
90 | 3 | -0.21515117 | 0.25611913E-03 | -0.15120274E-01 | 0.43248511E-01 |
91 | 2 | 2.8969963 | 0.11124906E-02 | 0.21482172 | -0.61829830 |
92 | 1 | -7.1337069 | 0.69706713E-03 | -0.54366453 | 1.5687761 |
93 | 0 | 4.4521846 | 0.12518961E-04 | 0.34594624 | |
94 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
95 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
96 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
97 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
98 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
99 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
100 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
101 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
102 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
103 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
104 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
105 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
106 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
107 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
108 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
109 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
110 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
111 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
112 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
113 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
114 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
115 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
116 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
117 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
118 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
119 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
120 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
121 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
122 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
123 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
124 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
125 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
126 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
127 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
128 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
129 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
130 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
131 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
132 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
133 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.45_SHGC_0.25 | 37 | 1 | VerySmooth | 2.557 | 2.557 | 1.000 | 0.251 | ||
2 | RESWINDOW_U_0.487_SHGC_0.25 | 38 | 1 | VerySmooth | 2.769 | 2.769 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 2.66719E-002 | 0.16139 | 0.61727 | 0.61727 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.12129 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 2.17016E-002 | 0.16139 | 0.61276 | 0.61276 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.11379 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | CAFE_FLR_1 | 1 | 0 |
2 | LOBBY_FLR_1 | 1 | 0 |
3 | BANQUET_FLR_6 | 1 | 0 |
4 | DINING_FLR_6 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | CAFE_FLR_1 | 0 | |
2 | LOBBY_FLR_1 | 0 | |
3 | BANQUET_FLR_6 | 0 | |
4 | DINING_FLR_6 | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH LAUNDRY G WATER HEATER | 1.1356 | 163316.0 | 11.511 | 0.4388 |
2 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.219 | 1.1187 |
3 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 2.2712 | 175842.6 | 5.775 | 0.3748 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 1.764E-002 | 2.631E-004 | 1.298E-004 | 0.239 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.811E-003 | 8.769E-005 | 2.388E-004 | 7.967E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 2.7 | 1.610E-002 | 9.800E-005 | 2.563E-004 | 8.904E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 9.287E-003 | 9.800E-005 | 2.127E-004 | 8.904E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 2.198E-002 | 2.816E-004 | 2.506E-004 | 0.256 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 3.900E-002 | 2.065E-004 | 1.137E-004 | 0.188 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 0.111 | 8.519E-005 | 1.629E-004 | 7.740E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 2.563E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 2.563E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 2.857E-003 | 1.165E-004 | 2.563E-004 | 0.138 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 2.858E-003 | 1.165E-004 | 2.563E-004 | 0.138 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 2.563E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 2.563E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 1.238E-002 | 3.180E-005 | 2.563E-004 | 3.755E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 1.297E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 1.297E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 5.239E-003 | 2.136E-004 | 1.165E-004 | 0.252 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 2.500E-002 | 7.539E-005 | 5.825E-005 | 8.904E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 2.500E-002 | 7.539E-005 | 5.825E-005 | 8.904E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 2.238E-002 | 2.167E-004 | 1.174E-004 | 0.256 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 2.191E-002 | 5.316E-005 | 4.403E-005 | 6.278E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 9.5713E-002 |
2 | Clear Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 4.3008E-002 |
3 | Clear Turbid Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1063 |
4 | Clear Turbid Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 4.6946E-002 |
5 | Intermediate Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 7.2253E-002 |
6 | Intermediate Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 2.6856E-002 |
7 | Overcast Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 2.9162E-002 |
8 | Overcast Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 9.6591E-003 |
9 | Clear Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1081 |
10 | Clear Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 5.2611E-002 |
11 | Clear Turbid Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1204 |
12 | Clear Turbid Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 5.7369E-002 |
13 | Intermediate Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 7.9985E-002 |
14 | Intermediate Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 3.3898E-002 |
15 | Overcast Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 3.2764E-002 |
16 | Overcast Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 1.3236E-002 |
17 | Clear Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.3289E-002 |
18 | Clear Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.3312E-002 |
19 | Clear Turbid Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 1.7943E-002 |
20 | Clear Turbid Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.0055E-002 |
21 | Intermediate Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 1.7164E-002 |
22 | Intermediate Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 6.8561E-003 |
23 | Overcast Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.8719E-002 |
24 | Overcast Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.0154E-002 |
25 | Clear Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.3289E-002 |
26 | Clear Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.3312E-002 |
27 | Clear Turbid Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 1.7943E-002 |
28 | Clear Turbid Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.0055E-002 |
29 | Intermediate Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 1.7164E-002 |
30 | Intermediate Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 6.8561E-003 |
31 | Overcast Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.8719E-002 |
32 | Overcast Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.0154E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 32902.69748 | 32902.69748 | 2.43592 | 2.43592 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:20:00 | 27.50267 | 8.22747E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 0.85446 | 00:10:00 | 3.80000 | 5.05843E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 | |
3 | RETAIL_1_FLR_1 | Cooling | 4218.75745 | 4218.75745 | 0.31236 | 0.31236 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | 30.92917 | 8.23290E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 1682.57937 | 1682.57937 | 7.34860E-002 | 7.92179E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 3076.20060 | 3076.20060 | 0.22777 | 0.22777 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 30.05400 | 8.23151E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 562.46518 | 562.46518 | 2.45656E-002 | 9.17347E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 2446.19663 | 2446.19663 | 0.18108 | 0.18108 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:30:00 | 28.49650 | 8.22904E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 1000.82488 | 1000.82488 | 4.37109E-002 | 4.37109E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 1435.57375 | 1435.57375 | 0.10627 | 0.10627 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 31.21100 | 8.23335E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 670.28289 | 670.28289 | 2.92745E-002 | 5.77652E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 44525.31933 | 44525.31933 | 3.29633 | 3.29633 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 31.30000 | 8.23349E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 1306.23105 | 1306.23105 | 5.70491E-002 | 5.70491E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 18649.47260 | 18649.47260 | 1.38198 | 1.38198 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | 30.92917 | 8.23290E-003 | 188.86188 | 142.30000 | 0.67638 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 4292.00006 | 4292.00006 | 0.18745 | 0.67638 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 188.86188 | 142.30000 | 0.67638 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 62965.29312 | 62965.29312 | 4.66338 | 4.66338 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 31.07750 | 8.23314E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 9965.93524 | 9965.93524 | 0.43526 | 1.89399 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 9804.14433 | 9804.14433 | 0.97806 | 0.97806 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 30.52867 | 8.23226E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 3704.30699 | 3704.30699 | 0.16273 | 0.16273 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 9439.03834 | 9439.03834 | 0.94164 | 0.94164 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 30.41000 | 8.23207E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 3704.51086 | 3704.51086 | 0.16274 | 0.16274 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 61224.75970 | 61224.75970 | 6.10751 | 6.10751 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 31.07750 | 8.23314E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 21626.50983 | 21626.50983 | 0.95008 | 0.95008 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 57499.59948 | 57499.59948 | 5.73636 | 5.73636 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 31.30000 | 8.23349E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 21641.03659 | 21641.03659 | 0.95072 | 0.95072 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 8712.42120 | 8712.42120 | 0.86915 | 0.86915 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:30:00 | 27.16150 | 8.22694E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 3703.47754 | 3703.47754 | 0.16270 | 0.16270 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 8388.25058 | 8388.25058 | 0.83681 | 0.83681 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | 26.65717 | 8.22614E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 3703.68139 | 3703.68139 | 0.16271 | 0.16271 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 19237.22982 | 19237.22982 | 1.42417 | 1.42417 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 31.30000 | 8.23349E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 6023.58091 | 6023.58091 | 0.26308 | 0.47476 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 2539.20075 | 2539.20075 | 0.25331 | 0.25331 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 30.52867 | 8.23226E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 1153.43294 | 1153.43294 | 5.06717E-002 | 5.06717E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 2438.99931 | 2438.99931 | 0.24331 | 0.24331 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 30.41000 | 8.23207E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 1152.98951 | 1152.98951 | 5.06522E-002 | 5.06522E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 11922.45204 | 11922.45204 | 1.18942 | 1.18942 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 31.07750 | 8.23314E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 5585.51508 | 5585.51508 | 0.24538 | 0.24538 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 28592.97589 | 28592.97589 | 2.11944 | 2.11944 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 31.30000 | 8.23349E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 3898.48204 | 3898.48204 | 0.17027 | 1.18780 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 20:00:00 | 3.80000 | 5.05843E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 29985.09931 | 29985.09931 | 2.22260 | 2.22260 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 31.30000 | 8.23349E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
40 | DINING_FLR_6 | Heating | 3955.38943 | 3955.38943 | 0.17275 | 1.18780 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:20:00 | 3.80000 | 5.05843E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 29969.63864 | 29969.63864 | 2.22457 | 2.22457 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 30.49900 | 8.23222E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 75.88517 | 75.88517 | 3.31510E-003 | 0.36735 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 3.80000 | 5.05843E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
43 | CORRIDOR_FLR_6 | Cooling | 9517.54181 | 9517.54181 | 0.70460 | 0.70460 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 31.22583 | 8.23338E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 4160.65325 | 4160.65325 | 0.18172 | 0.18172 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:30:00 | 3.80000 | 5.05843E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | FLR_3_DOAS | Cooling | Sensible | 45064.07 | 16.39778 | 2.05125 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
2 | FLR_3_DOAS | Heating | Sensible | 31423.05 | 2.89839 | 2.05125 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
3 | VAV WITH REHEAT | Cooling | Sensible | 382603.23 | 21.18187 | 21.18187 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | VAV WITH REHEAT | Heating | Sensible | 109582.88 | 7.15339 | 7.15339 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:30:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.43592 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.61901 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.54700 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.33245 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.15494E-004 |
8 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.04035E-005 |
9 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.33245 |
10 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6904.49014 |
13 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.04035E-005 |
14 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 143.98124 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.31236 |
16 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16362 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.54700 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17086 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.54700 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.32857E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.24628E-005 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.17086 |
24 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2567.63677 |
27 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.24628E-005 |
28 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 59.46405 |
29 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.22777 |
30 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25984 |
31 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.54700 |
32 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.12459 |
33 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.69291 |
34 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.46628E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.05665E-005 |
37 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.12459 |
38 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1207.82117 |
41 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.05665E-005 |
42 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 26.38422 |
43 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.18108 |
44 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.69114 |
45 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.54700 |
46 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 9.90519E-002 |
47 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.51262E-004 |
50 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.32438E-005 |
51 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 9.90519E-002 |
52 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1513.84388 |
55 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.32438E-005 |
56 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 35.16164 |
57 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.10627 |
58 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.67946 |
59 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.54700 |
60 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 5.81300E-002 |
61 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.60740E-004 |
64 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.49800E-006 |
65 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.81300E-002 |
66 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 971.37371 |
69 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.49800E-006 |
70 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 22.93683 |
71 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.29633 |
72 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 1.80401E-002 |
73 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.54700 |
74 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.80310 |
75 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.54700 |
76 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.11197E-002 |
78 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.31235E-005 |
79 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.80310 |
80 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10644.59252 |
83 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.31235E-005 |
84 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 223.58928 |
85 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.38198 |
86 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10414 |
87 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.54700 |
88 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.75594 |
89 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.54700 |
90 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.65871E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.18069E-005 |
93 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.75594 |
94 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8207.96423 |
97 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.18069E-005 |
98 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 181.51987 |
99 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 4.66338 |
100 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21376 |
101 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.54700 |
102 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.55087 |
103 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.57002 |
104 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
105 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.78238E-003 |
106 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.02784E-004 |
107 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.55087 |
108 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
110 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 23179.42724 |
111 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.02784E-004 |
112 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 503.10621 |
113 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
114 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.97806 |
115 | Fan:OnOff | ROOM_1_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 0.97806 |
116 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 3.24068E-005 |
117 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.06252E-004 |
118 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69392 |
119 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
120 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.57357E-003 |
121 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
122 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
123 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.06252E-004 |
124 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.97806 |
125 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 3704.30165 |
126 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.24068E-005 |
127 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 105.83922 |
128 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
129 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.94164 |
130 | Fan:OnOff | ROOM_2_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 0.94164 |
131 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 3.24086E-005 |
132 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.95071E-004 |
133 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69392 |
134 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
135 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.57634E-003 |
136 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
137 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
138 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.95071E-004 |
139 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.94164 |
140 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 3704.50551 |
141 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.24086E-005 |
142 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 105.84504 |
143 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83707 |
144 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 6.10751 |
145 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 6.10751 |
146 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.89198E-004 |
147 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.87389E-003 |
148 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69437 |
149 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
150 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.49776E-003 |
151 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
152 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.49776E-003 |
153 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.87389E-003 |
154 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 6.10751 |
155 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 21626.49471 |
156 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.89198E-004 |
157 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 617.90663 |
158 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83730 |
159 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 5.73636 |
160 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 5.73636 |
161 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.89325E-004 |
162 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.88085E-003 |
163 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69346 |
164 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
165 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.74561E-003 |
166 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
167 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
168 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.88085E-003 |
169 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.73636 |
170 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 21641.02147 |
171 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.89325E-004 |
172 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 618.32166 |
173 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
174 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.86915 |
175 | Fan:OnOff | ROOM_5_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 0.86915 |
176 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 3.23996E-005 |
177 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.72831E-004 |
178 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69391 |
179 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
180 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.58270E-003 |
181 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
182 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
183 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.72831E-004 |
184 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.86915 |
185 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 3703.47219 |
186 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.23996E-005 |
187 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 105.81552 |
188 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
189 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.83681 |
190 | Fan:OnOff | ROOM_6_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 0.83681 |
191 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 3.24014E-005 |
192 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.62907E-004 |
193 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69390 |
194 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
195 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.58586E-003 |
196 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
197 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
198 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.62907E-004 |
199 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.83681 |
200 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 3703.67604 |
201 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.24014E-005 |
202 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 105.82135 |
203 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.42417 |
204 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.83340 |
205 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.54700 |
206 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.77902 |
207 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.57163E-004 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.80030E-005 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.77902 |
212 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
213 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
214 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10059.28379 |
215 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.80030E-005 |
216 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 227.50053 |
217 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54338E-002 |
218 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.25331 |
219 | Fan:OnOff | ROOM_1_FLR_6 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 0.25331 |
220 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.00907E-005 |
221 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 7.92632E-005 |
222 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69393 |
223 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
224 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.57110E-003 |
225 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
226 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
227 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 7.92632E-005 |
228 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.25331 |
229 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1153.43135 |
230 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.00907E-005 |
231 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 32.95515 |
232 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54319E-002 |
233 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.24331 |
234 | Fan:OnOff | ROOM_2_FLR_6 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 0.24331 |
235 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.00868E-005 |
236 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 7.61948E-005 |
237 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69392 |
238 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
239 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.57394E-003 |
240 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
241 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
242 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 7.61948E-005 |
243 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.24331 |
244 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1152.98792 |
245 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.00868E-005 |
246 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 32.94248 |
247 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 9.91540E-002 |
248 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.18942 |
249 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 1.18942 |
250 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.88645E-005 |
251 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.79096E-004 |
252 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69363 |
253 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
254 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.63892E-003 |
255 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
256 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
257 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.79096E-004 |
258 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.18942 |
259 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 5585.50894 |
260 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.88645E-005 |
261 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 159.58524 |
262 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.11944 |
263 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11924 |
264 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.54700 |
265 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.15933 |
266 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.54700 |
267 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
268 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.19523E-003 |
269 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.66494E-005 |
270 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.15933 |
271 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
272 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
273 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9904.55954 |
274 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.66494E-005 |
275 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 213.75667 |
276 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.22260 |
277 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11371 |
278 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.54700 |
279 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.21576 |
280 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.54700 |
281 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
282 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.35074E-003 |
283 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.97056E-005 |
284 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.21576 |
285 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
286 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
287 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10253.89673 |
288 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.97056E-005 |
289 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 221.04413 |
290 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.22457 |
291 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 6.36456E-002 |
292 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.54700 |
293 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.21684 |
294 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.54700 |
295 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
296 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.07671E-002 |
297 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.91273E-005 |
298 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.21684 |
299 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
300 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
301 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6758.61114 |
302 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.91273E-005 |
303 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 141.46612 |
304 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.70460 |
305 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.44570 |
306 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.54700 |
307 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.38541 |
308 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
309 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
310 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 8.54835E-004 |
311 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.38680E-005 |
312 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.38541 |
313 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
314 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
315 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6157.44652 |
316 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.38680E-005 |
317 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 144.16031 |
318 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05132 |
319 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05132 |
320 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05132 |
321 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05132 |
322 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05132 |
323 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05132 |
324 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
325 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
326 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 11.65136 |
327 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 11.65136 |
328 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 21.30047 |
329 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 11.65136 |
330 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 21.18187 |
331 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 21.18187 |
332 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
333 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.55006 |
334 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05132 |
335 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 21.18187 |
336 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05132 |
337 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05125 |
338 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 31.30000 |
339 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
340 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.91243 |
341 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.23349E-003 |
342 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.23349E-003 |
343 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Coil Load [W] | 47946.24805 |
344 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.37126E-003 |
345 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 2.05132 |
346 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Rated Capacity [W] | 9427.24706 |
347 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.24737E-005 |
348 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 168.96790 |
349 | Fan:ConstantVolume | FLR_3_DOAS FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05125 |
350 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.37126E-003 |
351 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 3.47266E-004 |
352 | Controller:WaterCoil | FLR_3_DOAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 8.24737E-005 |
353 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 21.18187 |
354 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 28.01518 |
355 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
356 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.94368 |
357 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.89053E-003 |
358 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
359 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 461117.24515 |
360 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.31879E-002 |
361 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 21.18187 |
362 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 97345.61167 |
363 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.51622E-004 |
364 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1744.76005 |
365 | Fan:VariableVolume | VAV WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 21.18187 |
366 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.31879E-002 |
367 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 3.61081E-005 |
368 | Controller:WaterCoil | VAV WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 8.51622E-004 |
369 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 1.99855E-002 |
370 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 3263.02098 |
371 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 2.37152E-003 |
372 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.28458 |
373 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 2.37152E-003 |
374 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 714.19742 |
375 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
376 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 271079.20588 |
377 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 271079.21000 |
378 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 2.37152E-003 |
379 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 1.99855E-002 |
380 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 2.39826 |
381 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 1.99855E-002 |
382 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 2259.09948 |
383 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 1.99855E-002 |
384 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 698796.69689 |
385 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 699394.26000 |
386 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 79.73095 |
387 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
388 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
389 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
390 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
391 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | 6940.20 |
2 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 2579.49 |
3 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1213.81 |
4 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | 1520.81 |
5 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | 975.78 |
6 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 10699.28 |
7 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | 8247.63 |
8 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | 23295.07 |
9 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | 3989.58 |
10 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | 3989.80 |
11 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 23291.92 |
12 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 23307.56 |
13 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | 3988.69 |
14 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | 3988.91 |
15 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 10106.81 |
16 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | 1242.25 |
17 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | 1241.77 |
18 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 6015.58 |
19 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | 9954.22 |
20 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | 10305.36 |
21 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | 6793.45 |
22 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 6185.59 |
23 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | 7911.32 |
24 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | 81692.19 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | 15966.31 | 13745.90 | 2220.41 | 0.86 | 3235.93 | 32.82 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | 15379.68 | 13236.70 | 2142.98 | 0.86 | 3114.53 | 31.59 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 98327.12 | 85377.27 | 12949.85 | 0.87 | 20385.07 | 206.76 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 96630.89 | 81659.65 | 14971.24 | 0.85 | 18745.16 | 190.12 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | 14212.60 | 12223.44 | 1989.15 | 0.86 | 2872.91 | 29.14 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | 13691.86 | 11771.38 | 1920.48 | 0.86 | 2765.14 | 28.05 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | 4133.24 | 3559.44 | 573.80 | 0.86 | 838.30 | 8.50 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | 3972.25 | 3419.69 | 552.56 | 0.86 | 804.98 | 8.16 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 19654.86 | 16798.67 | 2856.19 | 0.85 | 3914.85 | 39.71 |
10 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | 51303.12 | 35829.51 | 15473.61 | 0.70 | 7298.17 | 74.02 |
11 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | 526994.00 | 369834.86 | 157159.13 | 0.70 | 81964.46 | 831.33 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 4.09 | 13.95 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.940 | 0.824 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 22.63 | 45.89 | 22.63 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 23.26 | 23.26 | 23.26 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 2.390 | 2.390 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 63.73 | 129.23 | 63.73 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 65.50 | 65.50 | 65.50 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 82.79 | 167.88 | 82.79 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 85.08 | 85.08 | 85.08 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.167 | 0.994 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.167 | 0.994 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.167 | 0.994 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.167 | 0.994 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.034 | 0.896 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.034 | 0.896 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.034 | 0.896 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.034 | 0.896 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.034 | 0.896 | 13.70 | 20.44 | 13.70 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 6.74 | 6.74 | 6.74 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 16.77 | 21.37 | 16.77 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 34.86 | 52.03 | 34.86 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 17.17 | 17.17 | 17.17 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 34.86 | 52.03 | 34.86 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 17.17 | 17.17 | 17.17 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 2.1524618771E-002 | 2.2478803277E-002 | Pass | Pass | 8.8072284782E-003 | 1.8743785847E-002 | Pass | Pass |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.1406676064E-002 | 4.8179984240E-002 | Pass | Pass | 4.1231077116E-002 | 5.1189906769E-002 | Pass | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 3.2397223257E-002 | 3.0109176735E-002 | Pass | Pass | 1.0580351007E-002 | 2.1523934612E-002 | Pass | Pass |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.4146102827E-002 | 1.4141506055E-002 | Pass | Pass | 1.3412105433E-002 | 2.8019856193E-002 | Pass | Pass |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 5.7013892567E-003 | 8.7915192689E-003 | Pass | Pass | 1.5471318766E-002 | 2.4094391522E-002 | Pass | Pass |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 9.5334337534E-002 | 0.2285272878 | Pass | Pass | 1.9678442991E-002 | 4.9397896868E-002 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 7.3398419037E-002 | 7.7871581439E-002 | Pass | Pass | 1.4862963151E-002 | 2.4450665847E-002 | Pass | Pass |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.6291185835E-002 | 4.4317012408E-002 | Pass | Pass | 1.0593494479E-002 | 2.0422393693E-002 | Pass | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 3.6482474648E-002 | 0.1096074918 | Pass | Pass | 0.3602964626 | 1.0870287748 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 2.1991052299E-002 | 4.8911735693E-002 | Pass | Pass | 0.2728631308 | 1.7401080748 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.0212379993E-002 | 6.4153802777E-002 | Pass | Pass | 0.2552684594 | 1.8096340210 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 5.0981869462E-002 | 0.1502847602 | Pass | Pass | 0.2432158522 | 1.0820105097 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 5.2875061117E-002 | 0.2000539311 | Pass | Pass | 0.6759221493 | 3.8335816061 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 3.8441327788E-002 | 0.1676594035 | Pass | Pass | 0.3306127618 | 1.0063370982 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 6.5942903021E-003 | 1.0095049774E-002 | Pass | Pass | 1.9054565049E-002 | 3.1817014708E-002 | Pass | Pass |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 3.4875875723E-002 | 7.8140155925E-002 | Pass | Pass | 0.2176887800 | 0.7451261291 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 3.7533047364E-002 | 0.1012068992 | Pass | Pass | 0.1458467658 | 0.6096772121 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 7.9990790571E-002 | 0.2410266724 | Pass | Pass | 0.2167175798 | 0.5224651680 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 4.1443793852E-002 | 7.2372223782E-002 | Pass | Pass | 1.3062576154E-002 | 3.5278577844E-002 | Pass | Pass |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 3.1581463035E-002 | 6.1737117813E-002 | Pass | Pass | 1.3796962788E-002 | 3.6647373806E-002 | Pass | Pass |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 3.1286014319E-002 | 9.7163700724E-002 | Pass | Pass | 2.1106511863E-002 | 3.9424087504E-002 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 1.0772594172E-002 | 1.4738655670E-002 | Pass | Pass | 1.6173074083E-002 | 2.0726433822E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:51
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3549.09 | 37.84 | 1069.27 | 4336.09 | 4076.46 | 13068.75 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:51
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00 | 3.80 | Wetbulb [C] | 3.00 | 120.00 |
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 31.30 | 8.90 | 18.40 | Wetbulb [C] | 4.10 | 280.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 2.00 | 2 | |||
Feb | 59.00 | 53 | |||
Mar | 58.58 | 43 | |||
Apr | 46.42 | 14 | |||
May | 18.00 | 12 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 3.00 | 6 | |||
Oct | 0.00 | 0 | |||
Nov | 18.00 | 12 | |||
Dec | 4.00 | 4 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:51
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 211.13 | 211.13 | 0.00 | 90.00 | N |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 55.76 | 55.76 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 211.13 | 211.13 | 180.00 | 90.00 | S |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 55.76 | 55.76 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 45.89 | 22.63 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 129.23 | 63.73 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 167.88 | 82.79 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 104.06 | 69.72 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 847.14 | 567.58 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 847.37 | 567.71 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 104.06 | 69.72 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 26.02 | 17.43 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 13.94 | 9.34 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | RES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 13.94 | 9.34 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 183.96 | 123.26 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 97.55 | 65.36 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 97.55 | 65.36 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 21.37 | 16.77 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 52.03 | 34.86 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 13.94 | 9.34 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 17.65 | 11.83 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 52.03 | 34.86 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 167.42 | 167.42 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_FLOOR | BASEMENT_FLOOR | 0.30 | 1.441 | 2.705 | 1978.83 | 1978.83 | 0.00 | 180.00 | |
BASEMENT_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 67.07 | 67.07 | 180.00 | 0.00 | |
BASEMENT_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 77.67 | 77.67 | 180.00 | 0.00 | |
BASEMENT_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 164.24 | 164.24 | 180.00 | 0.00 | |
BASEMENT_CEILING_4 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 94.76 | 94.76 | 180.00 | 0.00 | |
BASEMENT_CEILING_5 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 78.04 | 78.04 | 180.00 | 0.00 | |
BASEMENT_CEILING_6 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 188.86 | 188.86 | 180.00 | 0.00 | |
BASEMENT_CEILING_7 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 1088.56 | 1088.56 | 180.00 | 0.00 | |
BASEMENT_CEILING_8 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 219.63 | 219.63 | 90.00 | 0.00 | |
RETAIL_1_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_1_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
RETAIL_1_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 67.07 | 67.07 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
RETAIL_2_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_2_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 90.00 | 90.00 | E |
RETAIL_2_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 77.67 | 77.67 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 77.67 | 77.67 | 180.00 | 0.00 | |
MECH_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
MECH_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 180.00 | 90.00 | S |
MECH_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
MECH_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 164.24 | 164.24 | 0.00 | 180.00 | |
MECH_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 164.24 | 164.24 | 180.00 | 0.00 | |
STORAGE_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
STORAGE_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 180.00 | 90.00 | S |
STORAGE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
STORAGE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 94.76 | 94.76 | 0.00 | 180.00 | |
STORAGE_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 94.76 | 94.76 | 180.00 | 0.00 | |
LAUNDRY_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 180.00 | 90.00 | S |
LAUNDRY_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 270.00 | 90.00 | W |
LAUNDRY_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 78.04 | 78.04 | 0.00 | 180.00 | |
LAUNDRY_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 78.04 | 78.04 | 180.00 | 0.00 | |
CAFE_FLR_1_WALL_1_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_2_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
CAFE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 188.86 | 188.86 | 0.00 | 180.00 | |
LOBBY_FLR_1_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 90.00 | 90.00 | E |
LOBBY_FLR_1_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 1088.56 | 1088.56 | 180.00 | 180.00 | |
LOBBY_FLR_1_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 219.63 | 219.63 | 90.00 | 180.00 | |
LOBBY_FLR_1_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 1062.83 | 1062.83 | 270.00 | 0.00 | |
ROOM_1_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_1_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
ROOM_1_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_1_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_2_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
ROOM_2_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_2_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_2_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 156.07 | 156.07 | 180.00 | 0.00 | |
ROOM_3_MULT19_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.14 | 847.14 | 0.00 | 90.00 | N |
ROOM_3_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_3_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 1863.81 | 1863.81 | 0.00 | 180.00 | |
ROOM_3_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 1863.81 | 1863.81 | 180.00 | 0.00 | |
ROOM_4_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_4_MULT19_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.37 | 847.37 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_4_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 1864.32 | 1864.32 | 0.00 | 180.00 | |
ROOM_4_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 1864.32 | 1864.32 | 180.00 | 0.00 | |
ROOM_5_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
ROOM_5_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_5_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_6_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
ROOM_6_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_6_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 156.07 | 156.07 | 180.00 | 0.00 | |
CORRIDOR_FLR_3_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.28 | 847.28 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_4_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.27 | 847.27 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 297.29 | 297.29 | 180.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 963.06 | 963.06 | 270.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_3 | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 297.26 | 297.26 | 90.00 | 180.00 | |
CORRIDOR_FLR_3_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 297.29 | 297.29 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 963.06 | 963.06 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 297.26 | 297.26 | 90.00 | 0.00 | |
ROOM_1_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 0.00 | 90.00 | N |
ROOM_1_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_1_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_2_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_2_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 180.00 | 90.00 | S |
ROOM_2_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_3_MULT9_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.96 | 183.96 | 0.00 | 90.00 | N |
ROOM_3_MULT9_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 90.00 | 90.00 | E |
ROOM_3_MULT9_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 270.00 | 90.00 | W |
ROOM_3_MULT9_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 220.77 | 220.77 | 0.00 | 180.00 | |
BANQUET_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
BANQUET_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
BANQUET_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
BANQUET_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 331.66 | 331.66 | 0.00 | 180.00 | |
DINING_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
DINING_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
DINING_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
DINING_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 331.66 | 331.66 | 0.00 | 180.00 | |
KITCHEN_FLR_6_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 7.43 | 7.43 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 103.30 | 103.30 | 180.00 | 180.00 | |
CORRIDOR_FLR_6_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 104.98 | 104.98 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_1_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.95 | 183.95 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 11.15 | 11.15 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 40.88 | 40.88 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 412.12 | 412.12 | 180.00 | 180.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3957.66 | 0.00 | 90.00 | N | ||
RETAIL_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 134.14 | 0.00 | 90.00 | N | ||
RETAIL_2_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 155.34 | 0.00 | 90.00 | N | ||
MECH_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 328.49 | 0.00 | 90.00 | N | ||
STORAGE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 189.52 | 0.00 | 90.00 | N | ||
LAUNDRY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 156.08 | 0.00 | 90.00 | N | ||
CAFE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 377.72 | 0.00 | 90.00 | N | ||
LOBBY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 2616.37 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3727.63 | 0.00 | 90.00 | N | ||
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3728.64 | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3115.24 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.04 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.03 | 0.00 | 90.00 | N | ||
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 441.55 | 0.00 | 90.00 | N | ||
BANQUET_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
DINING_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 206.61 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 824.25 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 23.26 | 0.00 | 0.00 | 23.26 | 23.26 | 2.557 | 0.251 | 0.276 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 65.50 | 0.00 | 0.00 | 65.50 | 65.50 | 2.557 | 0.251 | 0.276 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 85.08 | 0.00 | 0.00 | 85.08 | 85.08 | 2.557 | 0.251 | 0.276 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.769 | 0.251 | 0.276 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.769 | 0.251 | 0.276 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.769 | 0.251 | 0.276 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.769 | 0.251 | 0.276 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 3.68 | 0.00 | 0.00 | 3.68 | 279.56 | 2.769 | 0.251 | 0.276 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 3.68 | 0.00 | 0.00 | 3.68 | 279.65 | 2.769 | 0.251 | 0.276 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.769 | 0.251 | 0.276 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.769 | 0.251 | 0.276 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.769 | 0.251 | 0.276 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.769 | 0.251 | 0.276 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.557 | 0.251 | 0.276 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 2.557 | 0.251 | 0.276 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 2.557 | 0.251 | 0.276 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.557 | 0.251 | 0.276 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.769 | 0.251 | 0.276 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.769 | 0.251 | 0.276 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.769 | 0.251 | 0.276 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.769 | 0.251 | 0.276 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 6.74 | 0.00 | 0.00 | 6.74 | 60.70 | 2.769 | 0.251 | 0.276 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.557 | 0.251 | 0.276 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.557 | 0.251 | 0.276 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.557 | 0.251 | 0.276 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.557 | 0.251 | 0.276 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | |||||||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.557 | 0.251 | 0.276 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 5.82 | 0.00 | 0.00 | 5.82 | 5.82 | 2.557 | 0.251 | 0.276 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 2.557 | 0.251 | 0.276 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.557 | 0.251 | 0.276 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 1213.79 | 2.707 | 0.251 | 0.276 | |||||||||||||||||
North Total or Average | 432.95 | 2.714 | 0.251 | 0.276 | |||||||||||||||||
Non-North Total or Average | 780.84 | 2.702 | 0.251 | 0.276 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 1.760 | 2.390 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:51
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:51
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 8.8143 | 1978.83 | 17441.96 | LightsWired | LTG_SCH_BASEMENT | 49.32 | 168.00 | 49.26 | 0.0000 | Y | 161.29 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | RETAIL_1_FLR_1 | GENERAL | 11.3140 | 67.07 | 758.85 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 7.31 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | RETAIL_2_FLR_1 | GENERAL | 11.3140 | 77.67 | 878.75 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 8.46 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | MECH_FLR_1 | GENERAL | 4.6285 | 164.24 | 760.20 | LightsWired | LTG_SCH_MECHANIC | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 8.37 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | STORAGE_FLR_1 | GENERAL | 5.7199 | 94.76 | 542.02 | LightsWired | LTG_SCH_STORAGE | 30.30 | 168.00 | 30.27 | 0.0000 | Y | 3.08 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | LAUNDRY_FLR_1 | GENERAL | 4.6285 | 78.04 | 361.20 | LightsWired | LTG_SCH_LAUNDRY | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 3.98 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | CAFE_FLR_1 | GENERAL | 10.0104 | 188.86 | 1890.59 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 40.42 | 0.0000 | Y | 14.34 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | LOBBY_FLR_1 | GENERAL | 10.7639 | 1308.19 | 14081.18 | LightsWired | LTG_SCH_LOBBY | 44.02 | 168.00 | 41.67 | 0.0000 | Y | 110.15 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | ROOM_1_FLR_3 | GENERAL | 8.2882 | 156.09 | 1293.69 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | ROOM_2_FLR_3 | GENERAL | 8.2882 | 156.07 | 1293.54 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | GENERAL | 8.2882 | 1863.81 | 15447.65 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 110.38 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | GENERAL | 8.2882 | 1864.32 | 15451.87 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 110.41 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | ROOM_5_FLR_3 | GENERAL | 8.2882 | 156.09 | 1293.69 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | ROOM_6_FLR_3 | GENERAL | 8.2882 | 156.07 | 1293.54 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | CORRIDOR_FLR_3 | GENERAL | 7.1042 | 1557.62 | 11065.59 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 91.33 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | ROOM_1_FLR_6 | GENERAL | 8.2882 | 39.02 | 323.42 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 2.31 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | ROOM_2_FLR_6 | GENERAL | 8.2882 | 39.02 | 323.38 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 2.31 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | GENERAL | 8.2882 | 220.77 | 1829.83 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 13.08 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | BANQUET_FLR_6 | GENERAL | 10.0104 | 331.66 | 3320.03 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 50.05 | 0.0000 | Y | 31.19 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | DINING_FLR_6 | GENERAL | 10.0104 | 331.66 | 3320.03 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 50.05 | 0.0000 | Y | 31.19 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | KITCHEN_FLR_6 | GENERAL | 11.4097 | 103.30 | 1178.68 | LightsWired | LTG_SCH_KITCHEN | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 12.97 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | CORRIDOR_FLR_6 | GENERAL | 7.1042 | 412.12 | 2927.80 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 24.17 |
Interior Lighting Total | 8.5566 | 11345.29 | 97077.49 | 457.56 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
LOBBY_FLR_1_DAYLREFPT1 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.07 | 14081.18 | 985.68 |
LOBBY_FLR_1_DAYLREFPT2 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.07 | 14081.18 | 985.68 |
CAFE_FLR_1_DAYLREFPT1 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1890.59 | 737.33 |
CAFE_FLR_1_DAYLREFPT2 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1890.59 | 737.33 |
DINING_FLR_6_DAYLREFPT1 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
DINING_FLR_6_DAYLREFPT2 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
BANQUET_FLR_6_DAYLREFPT1 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
BANQUET_FLR_6_DAYLREFPT2 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 12338.45 | AstronomicalClock | - | 83.75 | 83.75 | 193.98 | |
Exterior Lighting Total | 12338.45 | 193.98 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:51
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 271079.21 | 0.80 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 699394.26 | 2.96 | 699394.26 | 2.96 | 4.09 | 13.95 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 10708.37 | 15966.31 | 13745.90 | 2220.41 | 0.86 | - | 3235.93 | 32.82 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 10317.41 | 15379.68 | 13236.70 | 2142.98 | 0.86 | - | 3114.53 | 31.59 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 65521.98 | 98327.12 | 85377.27 | 12949.85 | 0.87 | - | 20385.07 | 206.76 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 65765.34 | 96630.89 | 81659.65 | 14971.24 | 0.85 | - | 18745.16 | 190.12 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 9539.76 | 14212.60 | 12223.44 | 1989.15 | 0.86 | - | 2872.91 | 29.14 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 9192.76 | 13691.86 | 11771.38 | 1920.48 | 0.86 | - | 2765.14 | 28.05 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 2771.50 | 4133.24 | 3559.44 | 573.80 | 0.86 | - | 838.30 | 8.50 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 2664.21 | 3972.25 | 3419.69 | 552.56 | 0.86 | - | 804.98 | 8.16 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 13255.40 | 19654.86 | 16798.67 | 2856.19 | 0.85 | - | 3914.85 | 39.71 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | 47946.25 | 51303.12 | 35829.51 | 15473.61 | 0.70 | - | 7298.17 | 74.02 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | 461117.25 | 526994.00 | 369834.86 | 157159.13 | 0.70 | - | 81964.46 | 831.33 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 6904.49 | 6940.20 | - |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2567.64 | 2579.49 | - |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1207.82 | 1213.81 | - |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1513.84 | 1520.81 | - |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 971.37 | 975.78 | - |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 10644.59 | 10699.28 | - |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 8207.96 | 8247.63 | - |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 23179.43 | 23295.07 | - |
ROOM_1_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 3704.30 | 3989.58 | - |
ROOM_2_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 3704.51 | 3989.80 | - |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 21626.49 | 23291.92 | - |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 21641.02 | 23307.56 | - |
ROOM_5_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 3703.47 | 3988.69 | - |
ROOM_6_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 3703.68 | 3988.91 | - |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 10059.28 | 10106.81 | - |
ROOM_1_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 1153.43 | 1242.25 | - |
ROOM_2_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 1152.99 | 1241.77 | - |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 5585.51 | 6015.58 | - |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 9904.56 | 9954.22 | - |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 10253.90 | 10305.36 | - |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 6758.61 | 6793.45 | - |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 6157.45 | 6185.59 | - |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | 9427.25 | 7911.32 | - |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | 97345.61 | 81692.19 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 0.24 | 76.61 | 324.68 | 1.00 | 2.78 | General | ||
LOBBY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.24 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
ROOM_1_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 0.98 | 688.20 | 703.64 | 1.00 | 1.20 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 |
ROOM_2_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 0.94 | 662.57 | 703.64 | 1.00 | 1.21 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 |
ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 6.11 | 4297.47 | 703.64 | 1.00 | 0.96 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 |
ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 5.74 | 4036.31 | 703.64 | 1.00 | 0.96 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 |
ROOM_5_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 0.87 | 611.57 | 703.64 | 1.00 | 1.23 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:30:00 |
ROOM_6_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 0.84 | 588.81 | 703.64 | 1.00 | 1.24 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 |
ROOM_1_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 0.25 | 178.24 | 703.64 | 1.00 | 1.84 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 |
ROOM_2_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 0.24 | 171.21 | 703.64 | 1.00 | 1.87 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 |
ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 1.19 | 836.92 | 703.64 | 1.00 | 1.16 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 |
BANQUET_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
DINING_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 1.89 | 612.92 | 324.68 | 1.00 | 1.48 | General | ||
FLR_3_DOAS FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.93 | 1070.05 | 1.00 | 1.30 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
VAV WITH REHEAT FAN | Fan:VariableVolume | 0.62 | 1389.42 | 21.18 | 47460.92 | 2240.64 | 1.00 | 1.11 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.019985 | 3263.02 | 163269.44 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.002372 | 714.20 | 301156.09 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.019985 | 2259.10 | 113036.94 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH LAUNDRY G WATER HEATER | WaterHeater:Mixed | 1.14 | 163316.00 | 0.80 | 11.51 | 0.44 |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.22 | 1.12 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.60 | 0.80 | 5.78 | 0.37 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:51
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 32902.70 | 32902.70 | 16.63 | 2.436 | 2.436 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:20:00 | 24.00 | 24.00 | 0.00923 | 27.50 | 0.00823 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 4218.76 | 4218.76 | 62.90 | 0.312 | 0.312 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | 24.00 | 24.00 | 0.00907 | 30.93 | 0.00823 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 3076.20 | 3076.20 | 39.61 | 0.228 | 0.228 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 24.00 | 24.00 | 0.00942 | 30.05 | 0.00823 | 0.092 | 0.00 |
MECH_FLR_1 | 2446.20 | 2446.20 | 14.89 | 0.181 | 0.181 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:30:00 | 24.00 | 24.00 | 0.00874 | 28.50 | 0.00823 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1435.57 | 1435.57 | 15.15 | 0.106 | 0.106 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 24.00 | 24.00 | 0.00881 | 31.21 | 0.00823 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 44525.32 | 44525.32 | 570.55 | 3.296 | 3.296 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 24.00 | 24.00 | 0.00854 | 31.30 | 0.00823 | 0.000 | 0.00 |
CAFE_FLR_1 | 18649.47 | 18649.47 | 98.75 | 1.382 | 1.382 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | 24.00 | 23.99 | 0.01021 | 30.93 | 0.00823 | 0.676 | 0.00 |
LOBBY_FLR_1 | 62965.29 | 62965.29 | 48.13 | 4.663 | 4.663 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 24.00 | 23.99 | 0.01001 | 31.08 | 0.00823 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 9804.14 | 9804.14 | 251.25 | 0.978 | 0.978 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 21.11 | 21.11 | 0.00857 | 30.53 | 0.00823 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 9439.04 | 9439.04 | 241.92 | 0.942 | 0.942 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 21.11 | 21.11 | 0.00858 | 30.41 | 0.00823 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 61224.76 | 61224.76 | 2496.54 | 6.108 | 6.108 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 21.11 | 21.11 | 0.00850 | 31.08 | 0.00823 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 57499.60 | 57499.60 | 2344.00 | 5.736 | 5.736 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 21.11 | 21.11 | 0.00875 | 31.30 | 0.00823 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 8712.42 | 8712.42 | 223.27 | 0.869 | 0.869 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:30:00 | 21.11 | 21.11 | 0.00858 | 27.16 | 0.00823 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 8388.25 | 8388.25 | 214.99 | 0.837 | 0.837 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | 21.11 | 21.11 | 0.00859 | 26.66 | 0.00823 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 19237.23 | 19237.23 | 49.40 | 1.424 | 1.424 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 24.00 | 24.00 | 0.00948 | 31.30 | 0.00823 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 2539.20 | 2539.20 | 65.07 | 0.253 | 0.253 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 21.11 | 21.11 | 0.00857 | 30.53 | 0.00823 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2439.00 | 2439.00 | 62.51 | 0.243 | 0.243 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 21.11 | 21.11 | 0.00857 | 30.41 | 0.00823 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 11922.45 | 11922.45 | 486.02 | 1.189 | 1.189 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 21.11 | 21.11 | 0.00864 | 31.08 | 0.00823 | 0.099 | 0.00 |
BANQUET_FLR_6 | 28592.98 | 28592.98 | 86.21 | 2.119 | 2.119 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 24.00 | 23.98 | 0.01047 | 31.30 | 0.00823 | 1.188 | 0.00 |
DINING_FLR_6 | 29985.10 | 29985.10 | 90.41 | 2.223 | 2.223 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 24.00 | 23.98 | 0.01038 | 31.30 | 0.00823 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 29969.64 | 29969.64 | 290.11 | 2.225 | 2.225 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 24.00 | 23.97 | 0.01012 | 30.50 | 0.00823 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 9517.54 | 9517.54 | 23.09 | 0.705 | 0.705 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 24.00 | 24.00 | 0.00902 | 31.23 | 0.00823 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 0.854 | 00:10:00 | 21.00 | 21.47 | 0.00506 | 3.80 | 0.00506 | 0.854 | 0.00 | |
RETAIL_1_FLR_1 | 1682.58 | 1682.58 | 25.09 | 0.073 | 0.079 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00783 | 3.80 | 0.00506 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 562.47 | 562.47 | 7.24 | 0.025 | 0.092 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00780 | 3.80 | 0.00506 | 0.092 | 0.00 |
MECH_FLR_1 | 1000.82 | 1000.82 | 6.09 | 0.044 | 0.044 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00774 | 3.80 | 0.00506 | 0.000 | 0.00 |
STORAGE_FLR_1 | 670.28 | 670.28 | 7.07 | 0.029 | 0.058 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00777 | 3.80 | 0.00506 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 1306.23 | 1306.23 | 16.74 | 0.057 | 0.057 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00773 | 3.80 | 0.00506 | 0.000 | 0.00 |
CAFE_FLR_1 | 4292.00 | 4292.00 | 22.73 | 0.187 | 0.676 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00785 | 3.80 | 0.00506 | 0.676 | 0.00 |
LOBBY_FLR_1 | 9965.94 | 9965.94 | 7.62 | 0.435 | 1.894 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00781 | 3.80 | 0.00506 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 3704.31 | 3704.31 | 94.93 | 0.163 | 0.163 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00782 | 3.80 | 0.00506 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 3704.51 | 3704.51 | 94.94 | 0.163 | 0.163 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00782 | 3.80 | 0.00506 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 21626.51 | 21626.51 | 881.86 | 0.950 | 0.950 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00783 | 3.80 | 0.00506 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 21641.04 | 21641.04 | 882.21 | 0.951 | 0.951 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00783 | 3.80 | 0.00506 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 3703.48 | 3703.48 | 94.91 | 0.163 | 0.163 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00782 | 3.80 | 0.00506 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 3703.68 | 3703.68 | 94.92 | 0.163 | 0.163 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00782 | 3.80 | 0.00506 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 6023.58 | 6023.58 | 15.47 | 0.263 | 0.475 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00786 | 3.80 | 0.00506 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 1153.43 | 1153.43 | 29.56 | 0.051 | 0.051 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00785 | 3.80 | 0.00506 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 1152.99 | 1152.99 | 29.55 | 0.051 | 0.051 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00785 | 3.80 | 0.00506 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 5585.52 | 5585.52 | 227.70 | 0.245 | 0.245 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00786 | 3.80 | 0.00506 | 0.099 | 0.00 |
BANQUET_FLR_6 | 3898.48 | 3898.48 | 11.75 | 0.170 | 1.188 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 20:00:00 | 21.00 | 21.00 | 0.00789 | 3.80 | 0.00506 | 1.188 | 0.00 |
DINING_FLR_6 | 3955.39 | 3955.39 | 11.93 | 0.173 | 1.188 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:20:00 | 21.00 | 21.00 | 0.00789 | 3.80 | 0.00506 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 75.89 | 75.89 | 0.73 | 0.003 | 0.367 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 21.00 | 21.29 | 0.00369 | 3.80 | 0.00506 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 4160.65 | 4160.65 | 10.10 | 0.182 | 0.182 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:30:00 | 21.00 | 21.00 | 0.00791 | 3.80 | 0.00506 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
FLR_3_DOAS | 16.40 | 2.05 | 2.90 | 2.05 | 2.0513 | 2.0513 | 2.0513 | 1.0000 | 0.3000 |
VAV WITH REHEAT | 21.18 | 21.18 | 7.15 | 7.15 | 21.1819 | 11.6514 | 21.1819 | 0.5501 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 6904.490 | 6904.490 | 1.332446 | 0.00006040 | 143.981 | 12/21 00:10:00 | 12/21 00:10:00 | 6904.49 | 6904.49 | 1.332446 | 16.70 | 13.02 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00800000 | 50.7558 | 0.00 | 0.00 | 6943.30 | 6943.30 | ||
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 2567.637 | 2567.637 | 0.170861 | 0.00002246 | 59.464 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 2567.64 | 2567.64 | 0.170861 | 16.70 | 13.02 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00782559 | 49.6635 | 1682.58 | 0.00 | 2581.38 | 2581.38 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 1207.821 | 1207.821 | 0.124589 | 0.00001057 | 26.384 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1207.82 | 1207.82 | 0.124589 | 16.70 | 13.02 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00780032 | 49.5048 | 562.47 | 0.00 | 1214.51 | 1214.51 |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 1513.844 | 1513.844 | 0.099052 | 0.00001324 | 35.162 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1513.84 | 1513.84 | 0.099052 | 16.70 | 13.02 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00774048 | 49.1297 | 1000.82 | 0.00 | 1521.94 | 1521.94 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 971.374 | 971.374 | 0.058130 | 0.00000850 | 22.937 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 971.37 | 971.37 | 0.058130 | 16.70 | 13.02 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00777372 | 49.3381 | 670.28 | 0.00 | 976.54 | 976.54 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 10644.593 | 10644.593 | 1.803095 | 0.00009312 | 223.589 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 10644.59 | 10644.59 | 1.803095 | 16.70 | 13.02 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00772981 | 49.0631 | 1306.23 | 0.00 | 10704.26 | 10704.26 |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 8207.964 | 8207.964 | 0.755944 | 0.00007181 | 181.520 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 8207.96 | 8207.96 | 0.755944 | 16.70 | 13.02 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00784765 | 49.8016 | 4292.00 | 0.00 | 8252.64 | 8252.64 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 23179.427 | 23179.427 | 2.550867 | 0.00020278 | 503.106 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 23179.43 | 23179.43 | 2.550867 | 16.70 | 13.02 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00781464 | 49.5946 | 9965.94 | 0.00 | 23308.02 | 23308.02 |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 10708.369 | -999.000 | 0.978062 | 0.00030625 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | unknown | 8/21 16:20:00 | 10708.37 | 10522.64 | 0.978062 | 21.69 | 15.44 | 0.00857357 | 12.80 | 11.93 | 0.00850000 | 30.53 | 0.00823226 | 18.20 | 0.0000 | 21.11 | 0.00857357 | 53.9772 | 9804.14 | 0.00 | 10912.59 | 10912.59 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 3704.302 | 3704.302 | 0.162734 | 0.00003241 | 105.839 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3704.30 | 3704.30 | 0.162734 | 21.11 | 14.54 | 0.00781767 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.11 | 0.00781767 | 49.2768 | 3704.31 | 0.00 | 3993.36 | 3993.36 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 10317.415 | -999.000 | 0.941639 | 0.00029507 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | unknown | 8/21 16:30:00 | 10317.41 | 10131.86 | 0.941639 | 21.69 | 15.44 | 0.00857634 | 12.80 | 11.93 | 0.00850000 | 30.41 | 0.00823207 | 18.16 | 0.0000 | 21.11 | 0.00857634 | 53.9944 | 9439.04 | 0.00 | 10514.05 | 10514.05 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 3704.506 | 3704.506 | 0.162743 | 0.00003241 | 105.845 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3704.51 | 3704.51 | 0.162743 | 21.11 | 14.54 | 0.00781770 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.11 | 0.00781770 | 49.2769 | 3704.51 | 0.00 | 3993.58 | 3993.58 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 65521.977 | -999.000 | 6.107512 | 0.00187389 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | unknown | 8/21 13:30:00 | 65521.98 | 65521.98 | 6.107512 | 21.69 | 15.37 | 0.00849776 | 12.80 | 11.93 | 0.00849776 | 31.08 | 0.00823314 | 18.38 | 0.0000 | 21.11 | 0.00849776 | 53.5051 | 61224.76 | 0.00 | 66783.29 | 66783.29 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 21626.495 | 21626.495 | 0.950083 | 0.00018920 | 617.907 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21626.49 | 21626.49 | 0.950083 | 21.11 | 14.56 | 0.00783349 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.11 | 0.00783349 | 49.3749 | 21626.51 | 0.00 | 23314.11 | 23314.11 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 65765.342 | -999.000 | 5.736356 | 0.00188085 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | unknown | 8/21 14:50:00 | 65765.34 | 62105.82 | 5.736356 | 21.69 | 15.59 | 0.00874561 | 12.80 | 11.93 | 0.00850000 | 31.30 | 0.00823349 | 18.45 | 0.0000 | 21.11 | 0.00874561 | 55.0462 | 57499.60 | 0.00 | 66993.87 | 65738.85 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 21641.021 | 21641.021 | 0.950722 | 0.00018933 | 618.322 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21641.02 | 21641.02 | 0.950722 | 21.11 | 14.56 | 0.00783356 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.11 | 0.00783356 | 49.3753 | 21641.04 | 0.00 | 23329.77 | 23329.77 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 9539.759 | -999.000 | 0.869152 | 0.00027283 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:30:00 | unknown | 8/21 09:30:00 | 9539.76 | 9354.18 | 0.869152 | 21.69 | 15.44 | 0.00858270 | 12.80 | 11.93 | 0.00850000 | 27.16 | 0.00822694 | 17.07 | 0.0000 | 21.11 | 0.00858270 | 54.0339 | 8712.42 | 0.00 | 9721.31 | 9721.31 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 3703.472 | 3703.472 | 0.162698 | 0.00003240 | 105.816 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3703.47 | 3703.47 | 0.162698 | 21.11 | 14.54 | 0.00781764 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.11 | 0.00781764 | 49.2765 | 3703.48 | 0.00 | 3992.46 | 3992.46 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 9192.763 | -999.000 | 0.836813 | 0.00026291 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | unknown | 8/21 09:10:00 | 9192.76 | 9007.22 | 0.836813 | 21.69 | 15.45 | 0.00858586 | 12.80 | 11.93 | 0.00850000 | 26.66 | 0.00822614 | 16.89 | 0.0000 | 21.11 | 0.00858586 | 54.0535 | 8388.25 | 0.00 | 9367.59 | 9367.59 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 3703.676 | 3703.676 | 0.162707 | 0.00003240 | 105.821 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3703.68 | 3703.68 | 0.162707 | 21.11 | 14.54 | 0.00781766 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.11 | 0.00781766 | 49.2767 | 3703.68 | 0.00 | 3992.68 | 3992.68 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 10059.284 | 10059.284 | 0.779022 | 0.00008800 | 227.501 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 10059.28 | 10059.28 | 0.779022 | 16.70 | 13.02 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00786143 | 49.8877 | 6023.58 | 0.00 | 10113.56 | 10113.56 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 2771.503 | -999.000 | 0.253311 | 0.00007926 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | unknown | 8/21 16:20:00 | 2771.50 | 2725.03 | 0.253311 | 21.69 | 15.43 | 0.00857110 | 12.80 | 11.93 | 0.00850000 | 30.53 | 0.00823226 | 18.20 | 0.0000 | 21.11 | 0.00857110 | 53.9618 | 2539.20 | 0.00 | 2824.39 | 2824.39 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 1153.431 | 1153.431 | 0.050672 | 0.00001009 | 32.955 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1153.43 | 1153.43 | 0.050672 | 21.11 | 14.57 | 0.00785177 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.11 | 0.00785177 | 49.4890 | 1153.43 | 0.00 | 1243.44 | 1243.44 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 2664.214 | -999.000 | 0.243315 | 0.00007619 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | unknown | 8/21 16:30:00 | 2664.21 | 2617.78 | 0.243315 | 21.69 | 15.44 | 0.00857394 | 12.80 | 11.93 | 0.00850000 | 30.41 | 0.00823207 | 18.16 | 0.0000 | 21.11 | 0.00857394 | 53.9795 | 2439.00 | 0.00 | 2715.02 | 2715.02 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 1152.988 | 1152.988 | 0.050652 | 0.00001009 | 32.942 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1152.99 | 1152.99 | 0.050652 | 21.11 | 14.57 | 0.00785173 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.11 | 0.00785173 | 49.4887 | 1152.99 | 0.00 | 1242.96 | 1242.96 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 13255.404 | -999.000 | 1.189416 | 0.00037910 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | unknown | 8/21 13:30:00 | 13255.40 | 12827.87 | 1.189416 | 21.69 | 15.49 | 0.00863892 | 12.80 | 11.93 | 0.00850000 | 31.08 | 0.00823314 | 18.38 | 0.0000 | 21.11 | 0.00863892 | 54.3837 | 11922.45 | 0.00 | 13506.61 | 13506.61 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 5585.509 | 5585.509 | 0.245379 | 0.00004886 | 159.585 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 5585.51 | 5585.51 | 0.245379 | 21.11 | 14.58 | 0.00785870 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.11 | 0.00785870 | 49.5320 | 5585.52 | 0.00 | 6021.37 | 6021.37 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 9904.560 | 9904.560 | 1.159334 | 0.00008665 | 213.757 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 20:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 20:00:00 | 9904.56 | 9904.56 | 1.159334 | 16.70 | 13.02 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00789078 | 50.0720 | 3898.48 | 0.00 | 9959.60 | 9959.60 |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 10253.897 | 10253.897 | 1.215761 | 0.00008971 | 221.044 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:20:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:20:00 | 10253.90 | 10253.90 | 1.215761 | 16.70 | 13.02 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00789213 | 50.0802 | 3955.39 | 0.00 | 10310.89 | 10310.89 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 6758.611 | 6758.611 | 1.216841 | 0.00005913 | 141.466 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 6758.61 | 6758.61 | 1.216841 | 16.70 | 13.02 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.29 | 0.00369468 | 23.1809 | 75.89 | 0.00 | 6796.55 | 6796.55 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 6157.447 | 6157.447 | 0.385415 | 0.00005387 | 144.160 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:30:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:30:00 | 6157.45 | 6157.45 | 0.385415 | 16.70 | 13.02 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00790963 | 50.1898 | 4160.65 | 0.00 | 6190.29 | 6190.29 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 47946.248 | -999.000 | 2.051317 | 0.00137126 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 47946.25 | 47946.25 | 2.051317 | 31.30 | 18.45 | 0.00823349 | 11.91 | 11.29 | 0.00823349 | 31.30 | 0.00823349 | 18.45 | 99.9965 | 21.11 | 0.00861907 | 54.2595 | 164372.54 | 0.00 | 48578.76 | 48578.76 |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | FLR_3_DOAS | 9427.247 | 9427.247 | 0.615395 | 0.00008247 | 168.968 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 9427.25 | 9427.25 | 0.615395 | 3.80 | 3.80 | 0.00505843 | 16.70 | 13.02 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 333.3216 | 21.11 | 0.00783363 | 49.3758 | 65975.46 | 0.00 | 9576.38 | 9576.38 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 461117.245 | -999.000 | 21.181871 | 0.01318789 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 461117.25 | 435635.08 | 21.181871 | 28.02 | 17.89 | 0.00889053 | 10.94 | 10.94 | 0.00850000 | 31.30 | 0.00823349 | 18.45 | 55.0540 | 23.99 | 0.00966027 | 50.9644 | 285836.33 | 0.00 | 467517.86 | 425623.95 |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV WITH REHEAT | 97345.612 | 97345.612 | 6.354561 | 0.00085162 | 1744.760 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:30:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:30:00 | 97345.61 | 97345.61 | 6.354561 | 3.80 | 3.80 | 0.00505843 | 16.70 | 13.02 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 183.5132 | 21.37 | 0.00635988 | 39.5452 | 37450.68 | 0.00 | 98885.53 | 98885.53 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:51
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | Yes | Yes | No | 6904.490 | 6904.490 | 1.332446 | 0.00006040 | 143.981 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.37127723 | 54.44 | 82.22 | 27.78 | 276534.78 | 2.4968 | 2.547038 | 12/21 00:10:00 | unknown | unknown | 12/21 00:10:00 | Sensible | 6904.49 | 6904.49 | 1.0000 | 1.57465639 | 1.332446 | 16.70 | 13.02 | 0.00800000 | 37036.7 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.06039733 | 60.00 | 32.22 | 27.78 | 0.000 | 6904.49 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 50.7558 | 0.00 | 0.00 | 6943.30 | 6943.30 | 1.57465639 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 20.92 | 14.82 | 0.00800000 | 41344.1 | |||
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2567.637 | 2567.637 | 0.170861 | 0.00002246 | 59.464 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.37127723 | 54.44 | 82.22 | 27.78 | 276534.78 | 0.9285 | 0.947191 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 2567.64 | 2567.64 | 1.0000 | 0.20191982 | 0.170861 | 16.70 | 13.02 | 0.00800000 | 37036.7 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.02246052 | 60.00 | 32.22 | 27.78 | 0.000 | 2567.64 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.00 | 0.00782559 | 21.00 | 0.00782559 | 49.6635 | 1682.58 | 0.00 | 2581.38 | 2581.38 | 0.20191982 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 29.14 | 17.75 | 0.00800000 | 49718.9 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1207.821 | 1207.821 | 0.124589 | 0.00001057 | 26.384 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.37127723 | 54.44 | 82.22 | 27.78 | 276534.78 | 0.4368 | 0.445560 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1207.82 | 1207.82 | 1.0000 | 0.14723700 | 0.124589 | 16.70 | 13.02 | 0.00800000 | 37036.7 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.01056547 | 60.00 | 32.22 | 27.78 | 0.000 | 1207.82 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.00 | 0.00780032 | 21.00 | 0.00780032 | 49.5048 | 562.47 | 0.00 | 1214.51 | 1214.51 | 0.14723700 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 24.69 | 16.20 | 0.00800000 | 45183.4 | |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1513.844 | 1513.844 | 0.099052 | 0.00001324 | 35.162 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.37127723 | 54.44 | 82.22 | 27.78 | 276534.78 | 0.5474 | 0.558451 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1513.84 | 1513.84 | 1.0000 | 0.11705745 | 0.099052 | 16.70 | 13.02 | 0.00800000 | 37036.7 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.01324242 | 60.00 | 32.22 | 27.78 | 0.000 | 1513.84 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.00 | 0.00774048 | 21.00 | 0.00774048 | 49.1297 | 1000.82 | 0.00 | 1521.94 | 1521.94 | 0.11705745 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 29.35 | 17.82 | 0.00800000 | 49936.4 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 971.374 | 971.374 | 0.058130 | 0.00000850 | 22.937 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.37127723 | 54.44 | 82.22 | 27.78 | 276534.78 | 0.3513 | 0.358336 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 971.37 | 971.37 | 1.0000 | 0.06869685 | 0.058130 | 16.70 | 13.02 | 0.00800000 | 37036.7 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.00849713 | 60.00 | 32.22 | 27.78 | 0.000 | 971.37 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.00 | 0.00777372 | 21.00 | 0.00777372 | 49.3381 | 670.28 | 0.00 | 976.54 | 976.54 | 0.06869685 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 30.54 | 18.22 | 0.00800000 | 51150.0 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10644.593 | 10644.593 | 1.803095 | 0.00009312 | 223.589 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.37127723 | 54.44 | 82.22 | 27.78 | 276534.78 | 3.8493 | 3.926746 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 10644.59 | 10644.59 | 1.0000 | 2.13085945 | 1.803095 | 16.70 | 13.02 | 0.00800000 | 37036.7 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.09311404 | 60.00 | 32.22 | 27.78 | 0.000 | 10644.59 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.00 | 0.00772981 | 21.00 | 0.00772981 | 49.0631 | 1306.23 | 0.00 | 10704.26 | 10704.26 | 2.13085945 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.53 | 15.05 | 0.00800000 | 41958.2 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8207.964 | 8207.964 | 0.755944 | 0.00007181 | 181.520 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.37127723 | 54.44 | 82.22 | 27.78 | 276534.78 | 2.9681 | 3.027884 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 8207.96 | 8207.96 | 1.0000 | 0.89335848 | 0.755944 | 16.70 | 13.02 | 0.00800000 | 37036.7 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.07179953 | 60.00 | 32.22 | 27.78 | 0.000 | 8207.96 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.00 | 0.00784765 | 21.00 | 0.00784765 | 49.8016 | 4292.00 | 0.00 | 8252.64 | 8252.64 | 0.89335848 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 25.66 | 16.55 | 0.00800000 | 46172.5 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 23179.427 | 23179.427 | 2.550867 | 0.00020278 | 503.106 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.37127723 | 54.44 | 82.22 | 27.78 | 276534.78 | 8.3821 | 8.550795 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 23179.43 | 23179.43 | 1.0000 | 3.01455960 | 2.550867 | 16.70 | 13.02 | 0.00800000 | 37036.7 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.20276306 | 60.00 | 32.22 | 27.78 | 0.000 | 23179.43 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.00 | 0.00781464 | 21.00 | 0.00781464 | 49.5946 | 9965.94 | 0.00 | 23308.02 | 23308.02 | 3.01455960 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 24.18 | 16.02 | 0.00800000 | 44666.5 | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10708.369 | -999.000 | 0.978062 | 0.00030625 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7778 | 1004.8586 | 1.1818 | ROOM_1_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.978062 | 1.15585281 | 4197.9300 | 999.8980 | 19.98345835 | 15.03 | 6.70 | 8.33 | 698796.70 | 1.5324 | 1.532373 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | unknown | unknown | unknown | 8/21 16:20:00 | Sensible | 10708.37 | 10522.64 | 1.0000 | 1.15585281 | 0.978062 | 21.69 | 15.44 | 0.00857357 | 43586.7 | 12.80 | 11.93 | 0.00850000 | 34322.2 | 0.30622105 | 6.70 | 15.03 | 8.33 | 0.000 | 10708.37 | 30.53 | 0.00823226 | 18.20 | 0.00000000 | 0.0000 | 21.11 | 0.00857357 | 21.11 | 0.00857357 | 53.9772 | 9804.14 | 0.00 | 10912.59 | 10912.59 | 1.15585281 | 21.69 | 15.62 | 0.00857357 | 43586.7 | 12.44 | 12.03 | 0.00857357 | 34145.5 | |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3704.302 | 3704.302 | 0.162734 | 0.00003241 | 105.839 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | ROOM_1_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.978062 | 1.15585281 | 4197.9300 | 999.8980 | 2.37127723 | 54.44 | 82.22 | 27.78 | 276534.78 | 1.3395 | 1.366502 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 3704.30 | 3704.30 | 1.0000 | 0.19231616 | 0.162734 | 21.11 | 14.54 | 0.00781767 | 41071.3 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.03240354 | 60.00 | 32.22 | 27.78 | 0.000 | 3704.30 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.11 | 0.00781767 | 21.11 | 0.00781767 | 49.2768 | 3704.31 | 0.00 | 3993.36 | 3993.36 | 0.19231616 | 16.60 | 12.97 | 0.00781767 | 36473.1 | 36.97 | 20.13 | 0.00781767 | 57237.7 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10317.415 | -999.000 | 0.941639 | 0.00029507 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7830 | 1004.8586 | 1.1818 | ROOM_2_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.941639 | 1.11280927 | 4197.9300 | 999.8980 | 19.98345835 | 15.03 | 6.70 | 8.33 | 698796.70 | 1.4765 | 1.476427 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | unknown | unknown | unknown | 8/21 16:30:00 | Sensible | 10317.41 | 10131.86 | 1.0000 | 1.11280927 | 0.941639 | 21.69 | 15.44 | 0.00857634 | 43593.7 | 12.80 | 11.93 | 0.00850000 | 34322.2 | 0.29504115 | 6.70 | 15.03 | 8.33 | 0.000 | 10317.41 | 30.41 | 0.00823207 | 18.16 | 0.00000000 | 0.0000 | 21.11 | 0.00857634 | 21.11 | 0.00857634 | 53.9944 | 9439.04 | 0.00 | 10514.05 | 10514.05 | 1.11280927 | 21.69 | 15.63 | 0.00857634 | 43593.7 | 12.44 | 12.03 | 0.00857634 | 34145.5 | |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3704.506 | 3704.506 | 0.162743 | 0.00003241 | 105.845 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | ROOM_2_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.941639 | 1.11280927 | 4197.9300 | 999.8980 | 2.37127723 | 54.44 | 82.22 | 27.78 | 276534.78 | 1.3396 | 1.366577 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 3704.51 | 3704.51 | 1.0000 | 0.19232674 | 0.162743 | 21.11 | 14.54 | 0.00781770 | 41071.4 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.03240532 | 60.00 | 32.22 | 27.78 | 0.000 | 3704.51 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.11 | 0.00781770 | 21.11 | 0.00781770 | 49.2769 | 3704.51 | 0.00 | 3993.58 | 3993.58 | 0.19232674 | 16.60 | 12.97 | 0.00781770 | 36473.2 | 36.97 | 20.13 | 0.00781770 | 57237.7 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 65521.977 | -999.000 | 6.107512 | 0.00187389 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6369 | 1004.8586 | 1.1818 | ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 6.107512 | 7.21772684 | 4197.9300 | 999.8980 | 19.98345835 | 15.03 | 6.70 | 8.33 | 698796.70 | 9.3764 | 9.376225 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | unknown | unknown | unknown | 8/21 13:30:00 | Sensible | 65521.98 | 65521.98 | 1.0000 | 7.21772684 | 6.107512 | 21.69 | 15.37 | 0.00849776 | 43394.5 | 12.80 | 11.93 | 0.00849776 | 34316.5 | 1.87369409 | 6.70 | 15.03 | 8.33 | 0.000 | 65521.98 | 31.08 | 0.00823314 | 18.38 | 0.00000000 | 0.0000 | 21.11 | 0.00849776 | 21.11 | 0.00849776 | 53.5051 | 61224.76 | 0.00 | 66783.29 | 66783.29 | 7.21772684 | 21.69 | 15.56 | 0.00849776 | 43394.5 | 12.63 | 12.03 | 0.00849776 | 34141.8 | |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 21626.495 | 21626.495 | 0.950083 | 0.00018920 | 617.907 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 6.107512 | 7.21772684 | 4197.9300 | 999.8980 | 2.37127723 | 54.44 | 82.22 | 27.78 | 276534.78 | 7.8205 | 7.977925 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 21626.49 | 21626.49 | 1.0000 | 1.12278825 | 0.950083 | 21.11 | 14.56 | 0.00783349 | 41111.6 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.18917871 | 60.00 | 32.22 | 27.78 | 0.000 | 21626.49 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.11 | 0.00783349 | 21.11 | 0.00783349 | 49.3749 | 21626.51 | 0.00 | 23314.11 | 23314.11 | 1.12278825 | 16.60 | 12.99 | 0.00783349 | 36513.2 | 36.97 | 20.14 | 0.00783349 | 57277.6 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 65765.342 | -999.000 | 5.736356 | 0.00188085 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0976 | 1004.8586 | 1.1818 | ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 5.736356 | 6.77910321 | 4197.9300 | 999.8980 | 19.98345835 | 15.03 | 6.70 | 8.33 | 698796.70 | 9.4112 | 9.411051 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | unknown | unknown | unknown | 8/21 14:50:00 | Sensible | 65765.34 | 62105.82 | 1.0000 | 6.77910321 | 5.736356 | 21.69 | 15.59 | 0.00874561 | 44023.4 | 12.80 | 11.93 | 0.00850000 | 34322.2 | 1.88065347 | 6.70 | 15.03 | 8.33 | 0.000 | 65765.34 | 31.30 | 0.00823349 | 18.45 | 0.00000000 | 0.0000 | 21.11 | 0.00874561 | 21.11 | 0.00874561 | 55.0462 | 57499.60 | 0.00 | 66993.87 | 65738.85 | 6.77910321 | 21.69 | 15.77 | 0.00874561 | 44023.4 | 12.20 | 12.02 | 0.00867225 | 34141.0 | |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 21641.021 | 21641.021 | 0.950722 | 0.00018933 | 618.322 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 5.736356 | 6.77910321 | 4197.9300 | 999.8980 | 2.37127723 | 54.44 | 82.22 | 27.78 | 276534.78 | 7.8258 | 7.983283 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 21641.02 | 21641.02 | 1.0000 | 1.12354244 | 0.950722 | 21.11 | 14.56 | 0.00783356 | 41111.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.18930578 | 60.00 | 32.22 | 27.78 | 0.000 | 21641.02 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.11 | 0.00783356 | 21.11 | 0.00783356 | 49.3753 | 21641.04 | 0.00 | 23329.77 | 23329.77 | 1.12354244 | 16.60 | 12.99 | 0.00783356 | 36513.3 | 36.97 | 20.14 | 0.00783356 | 57277.8 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9539.759 | -999.000 | 0.869152 | 0.00027283 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7948 | 1004.8586 | 1.1818 | ROOM_5_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.869152 | 1.02714535 | 4197.9300 | 999.8980 | 19.98345835 | 15.03 | 6.70 | 8.33 | 698796.70 | 1.3652 | 1.365144 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:30:00 | unknown | unknown | unknown | 8/21 09:30:00 | Sensible | 9539.76 | 9354.18 | 1.0000 | 1.02714535 | 0.869152 | 21.69 | 15.44 | 0.00858270 | 43609.8 | 12.80 | 11.93 | 0.00850000 | 34322.2 | 0.27280296 | 6.70 | 15.03 | 8.33 | 0.000 | 9539.76 | 27.16 | 0.00822694 | 17.07 | 0.00000000 | 0.0000 | 21.11 | 0.00858270 | 21.11 | 0.00858270 | 54.0339 | 8712.42 | 0.00 | 9721.31 | 9721.31 | 1.02714535 | 21.69 | 15.63 | 0.00858270 | 43609.8 | 12.42 | 12.03 | 0.00858270 | 34145.4 | |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3703.472 | 3703.472 | 0.162698 | 0.00003240 | 105.816 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | ROOM_5_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.869152 | 1.02714535 | 4197.9300 | 999.8980 | 2.37127723 | 54.44 | 82.22 | 27.78 | 276534.78 | 1.3392 | 1.366196 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 3703.47 | 3703.47 | 1.0000 | 0.19227310 | 0.162698 | 21.11 | 14.54 | 0.00781764 | 41071.2 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.03239629 | 60.00 | 32.22 | 27.78 | 0.000 | 3703.47 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.11 | 0.00781764 | 21.11 | 0.00781764 | 49.2765 | 3703.48 | 0.00 | 3992.46 | 3992.46 | 0.19227310 | 16.60 | 12.97 | 0.00781764 | 36473.0 | 36.97 | 20.13 | 0.00781764 | 57237.6 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9192.763 | -999.000 | 0.836813 | 0.00026291 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8007 | 1004.8586 | 1.1818 | ROOM_6_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.836813 | 0.98892766 | 4197.9300 | 999.8980 | 19.98345835 | 15.03 | 6.70 | 8.33 | 698796.70 | 1.3155 | 1.315489 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | unknown | unknown | unknown | 8/21 09:10:00 | Sensible | 9192.76 | 9007.22 | 1.0000 | 0.98892766 | 0.836813 | 21.69 | 15.45 | 0.00858586 | 43617.9 | 12.80 | 11.93 | 0.00850000 | 34322.2 | 0.26288014 | 6.70 | 15.03 | 8.33 | 0.000 | 9192.76 | 26.66 | 0.00822614 | 16.89 | 0.00000000 | 0.0000 | 21.11 | 0.00858586 | 21.11 | 0.00858586 | 54.0535 | 8388.25 | 0.00 | 9367.59 | 9367.59 | 0.98892766 | 21.69 | 15.63 | 0.00858586 | 43617.9 | 12.41 | 12.03 | 0.00858586 | 34145.4 | |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3703.676 | 3703.676 | 0.162707 | 0.00003240 | 105.821 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | ROOM_6_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.836813 | 0.98892766 | 4197.9300 | 999.8980 | 2.37127723 | 54.44 | 82.22 | 27.78 | 276534.78 | 1.3393 | 1.366271 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 3703.68 | 3703.68 | 1.0000 | 0.19228368 | 0.162707 | 21.11 | 14.54 | 0.00781766 | 41071.3 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.03239807 | 60.00 | 32.22 | 27.78 | 0.000 | 3703.68 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.11 | 0.00781766 | 21.11 | 0.00781766 | 49.2767 | 3703.68 | 0.00 | 3992.68 | 3992.68 | 0.19228368 | 16.60 | 12.97 | 0.00781766 | 36473.1 | 36.97 | 20.13 | 0.00781766 | 57237.6 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10059.284 | 10059.284 | 0.779022 | 0.00008800 | 227.501 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.37127723 | 54.44 | 82.22 | 27.78 | 276534.78 | 3.6376 | 3.710828 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 10059.28 | 10059.28 | 1.0000 | 0.92063107 | 0.779022 | 16.70 | 13.02 | 0.00800000 | 37036.7 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.08799403 | 60.00 | 32.22 | 27.78 | 0.000 | 10059.28 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.00 | 0.00786143 | 21.00 | 0.00786143 | 49.8877 | 6023.58 | 0.00 | 10113.56 | 10113.56 | 0.92063107 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 27.37 | 17.15 | 0.00800000 | 47920.2 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2771.503 | -999.000 | 0.253311 | 0.00007926 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7732 | 1004.8586 | 1.1818 | ROOM_1_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.253311 | 0.29935722 | 4197.9300 | 999.8980 | 19.98345835 | 15.03 | 6.70 | 8.33 | 698796.70 | 0.3966 | 0.396603 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | unknown | unknown | unknown | 8/21 16:20:00 | Sensible | 2771.50 | 2725.03 | 1.0000 | 0.29935722 | 0.253311 | 21.69 | 15.43 | 0.00857110 | 43580.4 | 12.80 | 11.93 | 0.00850000 | 34322.2 | 0.07925508 | 6.70 | 15.03 | 8.33 | 0.000 | 2771.50 | 30.53 | 0.00823226 | 18.20 | 0.00000000 | 0.0000 | 21.11 | 0.00857110 | 21.11 | 0.00857110 | 53.9618 | 2539.20 | 0.00 | 2824.39 | 2824.39 | 0.29935722 | 21.69 | 15.62 | 0.00857110 | 43580.4 | 12.45 | 12.03 | 0.00857110 | 34145.5 | |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1153.431 | 1153.431 | 0.050672 | 0.00001009 | 32.955 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | ROOM_1_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.253311 | 0.29935722 | 4197.9300 | 999.8980 | 2.37127723 | 54.44 | 82.22 | 27.78 | 276534.78 | 0.4171 | 0.425496 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1153.43 | 1153.43 | 1.0000 | 0.05988268 | 0.050672 | 21.11 | 14.57 | 0.00785177 | 41157.9 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.01008969 | 60.00 | 32.22 | 27.78 | 0.000 | 1153.43 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.11 | 0.00785177 | 21.11 | 0.00785177 | 49.4890 | 1153.43 | 0.00 | 1243.44 | 1243.44 | 0.05988268 | 16.60 | 13.01 | 0.00785177 | 36559.5 | 36.97 | 20.16 | 0.00785177 | 57324.0 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2664.214 | -999.000 | 0.243315 | 0.00007619 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7785 | 1004.8586 | 1.1818 | ROOM_2_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.243315 | 0.28754414 | 4197.9300 | 999.8980 | 19.98345835 | 15.03 | 6.70 | 8.33 | 698796.70 | 0.3813 | 0.381250 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | unknown | unknown | unknown | 8/21 16:30:00 | Sensible | 2664.21 | 2617.78 | 1.0000 | 0.28754414 | 0.243315 | 21.69 | 15.44 | 0.00857394 | 43587.6 | 12.80 | 11.93 | 0.00850000 | 34322.2 | 0.07618700 | 6.70 | 15.03 | 8.33 | 0.000 | 2664.21 | 30.41 | 0.00823207 | 18.16 | 0.00000000 | 0.0000 | 21.11 | 0.00857394 | 21.11 | 0.00857394 | 53.9795 | 2439.00 | 0.00 | 2715.02 | 2715.02 | 0.28754414 | 21.69 | 15.62 | 0.00857394 | 43587.6 | 12.44 | 12.03 | 0.00857394 | 34145.5 | |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1152.988 | 1152.988 | 0.050652 | 0.00001009 | 32.942 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | ROOM_2_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.243315 | 0.28754414 | 4197.9300 | 999.8980 | 2.37127723 | 54.44 | 82.22 | 27.78 | 276534.78 | 0.4169 | 0.425332 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1152.99 | 1152.99 | 1.0000 | 0.05985965 | 0.050652 | 21.11 | 14.57 | 0.00785173 | 41157.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.01008581 | 60.00 | 32.22 | 27.78 | 0.000 | 1152.99 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.11 | 0.00785173 | 21.11 | 0.00785173 | 49.4887 | 1152.99 | 0.00 | 1242.96 | 1242.96 | 0.05985965 | 16.60 | 13.01 | 0.00785173 | 36559.3 | 36.97 | 20.16 | 0.00785173 | 57323.9 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13255.404 | -999.000 | 1.189416 | 0.00037910 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8993 | 1004.8586 | 1.1818 | ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 1.189416 | 1.40562664 | 4197.9300 | 999.8980 | 19.98345835 | 15.03 | 6.70 | 8.33 | 698796.70 | 1.8969 | 1.896855 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | unknown | unknown | unknown | 8/21 13:30:00 | Sensible | 13255.40 | 12827.87 | 1.0000 | 1.40562664 | 1.189416 | 21.69 | 15.49 | 0.00863892 | 43752.4 | 12.80 | 11.93 | 0.00850000 | 34322.2 | 0.37905713 | 6.70 | 15.03 | 8.33 | 0.000 | 13255.40 | 31.08 | 0.00823314 | 18.38 | 0.00000000 | 0.0000 | 21.11 | 0.00863892 | 21.11 | 0.00863892 | 54.3837 | 11922.45 | 0.00 | 13506.61 | 13506.61 | 1.40562664 | 21.69 | 15.68 | 0.00863892 | 43752.4 | 12.28 | 12.02 | 0.00863892 | 34143.5 | |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5585.509 | 5585.509 | 0.245379 | 0.00004886 | 159.585 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 1.189416 | 1.40562664 | 4197.9300 | 999.8980 | 2.37127723 | 54.44 | 82.22 | 27.78 | 276534.78 | 2.0198 | 2.060471 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 5585.51 | 5585.51 | 1.0000 | 0.28998331 | 0.245379 | 21.11 | 14.58 | 0.00785870 | 41175.6 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.04885948 | 60.00 | 32.22 | 27.78 | 0.000 | 5585.51 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.11 | 0.00785870 | 21.11 | 0.00785870 | 49.5320 | 5585.52 | 0.00 | 6021.37 | 6021.37 | 0.28998331 | 16.60 | 13.01 | 0.00785870 | 36577.0 | 36.97 | 20.16 | 0.00785870 | 57341.5 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9904.560 | 9904.560 | 1.159334 | 0.00008665 | 213.757 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.37127723 | 54.44 | 82.22 | 27.78 | 276534.78 | 3.5817 | 3.653751 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 20:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 20:00:00 | Sensible | 9904.56 | 9904.56 | 1.0000 | 1.37007663 | 1.159334 | 16.70 | 13.02 | 0.00800000 | 37036.7 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.08664057 | 60.00 | 32.22 | 27.78 | 0.000 | 9904.56 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.00 | 0.00789078 | 21.00 | 0.00789078 | 50.0720 | 3898.48 | 0.00 | 9959.60 | 9959.60 | 1.37007663 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 23.73 | 15.86 | 0.00800000 | 44204.1 | |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10253.897 | 10253.897 | 1.215761 | 0.00008971 | 221.044 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.37127723 | 54.44 | 82.22 | 27.78 | 276534.78 | 3.7080 | 3.782620 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:20:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:20:00 | Sensible | 10253.90 | 10253.90 | 1.0000 | 1.43676022 | 1.215761 | 16.70 | 13.02 | 0.00800000 | 37036.7 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.08969641 | 60.00 | 32.22 | 27.78 | 0.000 | 10253.90 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.00 | 0.00789213 | 21.00 | 0.00789213 | 50.0802 | 3955.39 | 0.00 | 10310.89 | 10310.89 | 1.43676022 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 23.64 | 15.82 | 0.00800000 | 44111.2 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6758.611 | 6758.611 | 1.216841 | 0.00005913 | 141.466 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.37127723 | 54.44 | 82.22 | 27.78 | 276534.78 | 2.4440 | 2.493224 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 6758.61 | 6758.61 | 1.0000 | 1.43803719 | 1.216841 | 16.70 | 13.02 | 0.00800000 | 37036.7 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.05912125 | 60.00 | 32.22 | 27.78 | 0.000 | 6758.61 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 17.95 | 0.00369468 | 21.29 | 0.00369468 | 23.1809 | 75.89 | 0.00 | 6796.55 | 6796.55 | 1.43803719 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.23 | 14.94 | 0.00800000 | 41661.0 | |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6157.447 | 6157.447 | 0.385415 | 0.00005387 | 144.160 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.37127723 | 54.44 | 82.22 | 27.78 | 276534.78 | 2.2266 | 2.271457 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:30:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:30:00 | Sensible | 6157.45 | 6157.45 | 1.0000 | 0.45547500 | 0.385415 | 16.70 | 13.02 | 0.00800000 | 37036.7 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.05386253 | 60.00 | 32.22 | 27.78 | 0.000 | 6157.45 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.00 | 0.00790963 | 21.00 | 0.00790963 | 50.1898 | 4160.65 | 0.00 | 6190.29 | 6190.29 | 0.45547500 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 29.93 | 18.01 | 0.00800000 | 50525.6 | |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 47946.248 | -999.000 | 2.051317 | 0.00137126 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.1456 | 1004.8586 | 1.1818 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.42411771 | 4197.9300 | 999.8980 | 19.98345835 | 15.03 | 6.70 | 8.33 | 698796.70 | 6.8613 | 6.861259 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | Sensible | 47946.25 | 47946.25 | 1.0000 | 2.42420295 | 2.051317 | 31.30 | 18.45 | 0.00823349 | 52522.0 | 11.91 | 11.29 | 0.00823349 | 32743.9 | 1.37111674 | 6.70 | 15.03 | 8.33 | 2195.006 | 45751.24 | 31.30 | 0.00823349 | 18.45 | 2.05124512 | 99.9965 | 21.11 | 0.00861483 | 21.11 | 0.00861907 | 54.2595 | 164372.54 | 0.00 | 48578.76 | 48578.76 | 2.42420295 | 31.30 | 18.65 | 0.00823349 | 52522.0 | 11.66 | 11.35 | 0.00823349 | 32483.0 | |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 9427.247 | 9427.247 | 0.615395 | 0.00008247 | 168.968 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.42411771 | 4197.9300 | 999.8980 | 2.37127723 | 54.44 | 82.22 | 27.78 | 276534.78 | 3.4091 | 3.477673 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 9427.25 | 9427.25 | 1.0000 | 0.72726088 | 0.615395 | 3.80 | 3.80 | 0.00505843 | 16505.0 | 16.70 | 13.02 | 0.00800000 | 37036.7 | 0.08246526 | 60.00 | 32.22 | 27.78 | 0.000 | 9427.25 | 3.80 | 0.00505843 | 3.80 | 2.05124512 | 333.3216 | 21.11 | 0.00783273 | 21.11 | 0.00783363 | 49.3758 | 65975.46 | 0.00 | 9576.38 | 9576.38 | 0.72726088 | 2.80 | 2.80 | 0.00505843 | 15490.7 | 15.78 | 9.78 | 0.00505843 | 28658.4 | |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 461117.245 | -999.000 | 21.181871 | 0.01318789 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.3670 | 1004.8586 | 1.1818 | VAV WITH REHEAT FAN | Fan:VariableVolume | 21.181871 | 25.03228324 | 4197.9300 | 999.8980 | 19.98345835 | 15.03 | 6.70 | 8.33 | 698796.70 | 65.9873 | 65.987325 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | Sensible | 461117.25 | 435635.08 | 1.0000 | 25.03228324 | 21.181871 | 28.02 | 17.89 | 0.00889053 | 50848.5 | 10.94 | 10.94 | 0.00850000 | 32427.6 | 13.18654954 | 6.70 | 15.03 | 8.33 | 47460.918 | 413656.33 | 31.30 | 0.00823349 | 18.45 | 11.66146000 | 55.0540 | 23.99 | 0.00969588 | 23.99 | 0.00966027 | 50.9644 | 285836.33 | 0.00 | 467517.86 | 425623.95 | 25.03228324 | 28.02 | 18.10 | 0.00889053 | 50848.5 | 11.37 | 11.22 | 0.00822695 | 32171.9 | |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 97345.612 | 97345.612 | 6.354561 | 0.00085162 | 1744.760 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | VAV WITH REHEAT FAN | Fan:VariableVolume | 21.181871 | 25.03228324 | 4197.9300 | 999.8980 | 2.37127723 | 54.44 | 82.22 | 27.78 | 276534.78 | 35.2019 | 35.910394 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:30:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:30:00 | Sensible | 97345.61 | 97345.61 | 1.0000 | 7.50968497 | 6.354561 | 3.80 | 3.80 | 0.00505843 | 16505.0 | 16.70 | 13.02 | 0.00800000 | 37036.7 | 0.85153500 | 60.00 | 32.22 | 27.78 | 0.000 | 97345.61 | 3.80 | 0.00505843 | 3.80 | 11.66146000 | 183.5132 | 18.35 | 0.00730273 | 21.37 | 0.00635988 | 39.5452 | 37450.68 | 0.00 | 98885.53 | 98885.53 | 7.50968497 | 2.80 | 2.80 | 0.00505843 | 15490.7 | 15.78 | 9.78 | 0.00505843 | 28658.4 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:51
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - | |||
VAV WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 21.18 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | VAV WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000610 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LAUNDRY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CAFE_FLR_1 | VAV WITH REHEAT_DCV | 0.003540 | 0.000914 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001448 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_3 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
KITCHEN_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003556 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 67.33 | 8098.00 | 0.00 |
RETAIL_1_FLR_1 | 839.00 | 7312.83 | 15.17 |
RETAIL_2_FLR_1 | 1107.00 | 6846.17 | 282.00 |
MECH_FLR_1 | 0.00 | 8624.83 | 0.00 |
STORAGE_FLR_1 | 1.33 | 8758.83 | 1.33 |
LAUNDRY_FLR_1 | 7483.33 | 3482.83 | 2887.83 |
CAFE_FLR_1 | 3310.67 | 5071.33 | 1163.17 |
LOBBY_FLR_1 | 2266.17 | 5626.17 | 897.17 |
ROOM_1_FLR_3 | 41.17 | 8283.17 | 40.00 |
ROOM_2_FLR_3 | 859.00 | 7737.17 | 275.33 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 103.33 | 8712.50 | 99.00 |
ROOM_5_FLR_3 | 50.00 | 8634.50 | 50.00 |
ROOM_6_FLR_3 | 514.67 | 8232.50 | 272.67 |
CORRIDOR_FLR_3 | 172.50 | 8758.33 | 172.50 |
ROOM_1_FLR_6 | 205.17 | 8128.50 | 198.50 |
ROOM_2_FLR_6 | 1223.00 | 7645.33 | 639.67 |
ROOM_3_MULT9_FLR_6 | 22.67 | 8159.17 | 12.33 |
BANQUET_FLR_6 | 6185.33 | 1862.17 | 893.50 |
DINING_FLR_6 | 7077.83 | 1129.33 | 791.50 |
KITCHEN_FLR_6 | 8459.83 | 6538.00 | 6401.83 |
CORRIDOR_FLR_6 | 15.83 | 8500.83 | 5.83 |
Facility | 8671.50 | 8760.00 | 7296.17 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 2.83 | 0.00 | 2.83 |
ROOM_2_FLR_3 | 0.00 | 6.83 | 0.00 | 6.83 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 17.83 | 0.00 | 17.83 |
ROOM_5_FLR_3 | 0.00 | 1.67 | 0.00 | 1.67 |
ROOM_6_FLR_3 | 0.00 | 27.50 | 0.00 | 27.50 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 4.67 | 0.00 | 4.67 |
ROOM_2_FLR_6 | 0.00 | 16.33 | 0.00 | 16.33 |
ROOM_3_MULT9_FLR_6 | 0.00 | 7.33 | 0.00 | 7.33 |
BANQUET_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 56.00 | 0.00 | 56.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:51
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.74 | 106.50 | 4826.41 | 1.015 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 2.405 | 0.061 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 1.494 | 0.020 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.557 | 0.023 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.567 | 0.023 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 24.138 | 0.065 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.49 | 142.30 | 748.35 | 3.791 | 0.048 | 0.000 | 0.000 |
LOBBY_FLR_1 | 244.88 | 422.44 | 5183.56 | 1.833 | 0.020 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.356 | 0.079 | 0.000 | 0.093 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.356 | 0.079 | 0.000 | 0.095 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.404 | 0.035 | 0.000 | 0.157 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.356 | 0.079 | 0.000 | 0.093 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.356 | 0.079 | 0.000 | 0.101 |
CORRIDOR_FLR_3 | 12.15 | 20.96 | 1186.91 | 0.601 | 0.010 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.356 | 0.079 | 0.000 | 0.104 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.356 | 0.079 | 0.000 | 0.097 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.404 | 0.064 | 0.000 | 0.166 |
BANQUET_FLR_6 | 144.86 | 249.90 | 1010.89 | 4.909 | 0.023 | 0.000 | 0.000 |
DINING_FLR_6 | 144.86 | 249.90 | 1010.89 | 5.297 | 0.023 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.89 | 22.24 | 314.87 | 22.320 | 0.066 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.86 | 22.18 | 1256.16 | 1.123 | 0.016 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.74 | 106.50 | 4826.41 | 0.990 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 2.295 | 0.001 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 1.448 | 0.000 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.543 | 0.000 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.552 | 0.000 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 20.779 | 0.001 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.49 | 142.30 | 748.35 | 3.618 | 0.001 | 0.000 | 0.000 |
LOBBY_FLR_1 | 244.88 | 422.44 | 5183.56 | 1.764 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
CORRIDOR_FLR_3 | 12.15 | 20.96 | 1186.91 | 0.586 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.000 | 0.001 | 0.000 | 0.000 |
BANQUET_FLR_6 | 144.86 | 249.90 | 1010.89 | 4.114 | 0.000 | 0.000 | 0.000 |
DINING_FLR_6 | 144.86 | 249.90 | 1010.89 | 4.320 | 0.000 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.89 | 22.24 | 314.87 | 13.846 | 0.001 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.86 | 22.18 | 1256.16 | 1.095 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:51
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | VAV WITH REHEAT | 61.74 | 106.50 | 4826.41 | 1978.83 | 0.0000 | 0.854 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 6.28 | 10.83 | 265.76 | 67.07 | 0.0000 | 0.079 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 7.27 | 12.54 | 307.76 | 77.67 | 0.0000 | 0.092 |
MECH_FLR_1 | VAV WITH REHEAT | 1.54 | 2.65 | 650.80 | 164.24 | 0.0000 | 0.000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 1.18 | 2.04 | 375.47 | 94.76 | 0.0000 | 0.058 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 4.87 | 8.40 | 309.22 | 78.04 | 0.0000 | 0.000 |
CAFE_FLR_1 | VAV WITH REHEAT | 82.49 | 142.30 | 748.35 | 188.86 | 0.0000 | 0.173 |
LOBBY_FLR_1 | VAV WITH REHEAT | 244.88 | 422.44 | 5183.56 | 1308.19 | 0.0000 | 1.894 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 1.50 | 74.75 | 24.52 | 0.0000 | 0.837 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.837 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 12.15 | 20.96 | 1186.91 | 389.40 | 0.0000 | 0.475 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.015 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.015 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.099 |
BANQUET_FLR_6 | VAV WITH REHEAT | 144.86 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
DINING_FLR_6 | VAV WITH REHEAT | 144.86 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 12.89 | 22.24 | 314.87 | 103.30 | 0.0000 | 0.367 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 12.86 | 22.18 | 1256.16 | 412.12 | 0.0000 | 0.126 |
Total Facility | 872.55 | 1604.23 | 35184.81 | 11345.29 | 0.0000 | 137.081 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 42043451.99 | 0.00 | 42043451.99 | 0.00 | 42043451.99 | 26946214.98 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_1_FLR_1 | 5503108.42 | 0.00 | 5503108.42 | 139545.61 | 5642654.03 | 2498216.28 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_2_FLR_1 | 3945053.09 | 0.00 | 3945053.09 | 53864.78 | 3998917.88 | 2892943.94 | 0.00 | 0.00 | 8760.00 | 0.00 |
MECH_FLR_1 | 3121400.88 | 0.00 | 3121400.88 | 127304.34 | 3248705.23 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
STORAGE_FLR_1 | 1831828.56 | 0.00 | 1831828.56 | 73447.59 | 1905276.15 | 1821682.01 | 25.33 | 8734.67 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 64123756.07 | 0.00 | 64123756.07 | 173827.58 | 64297583.65 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
CAFE_FLR_1 | 24303963.84 | 0.00 | 24303963.84 | 308473.47 | 24612437.31 | 14544917.54 | 0.00 | 0.00 | 8760.00 | 0.00 |
LOBBY_FLR_1 | 81361980.28 | 0.00 | 81361980.28 | 881379.17 | 82243359.45 | 59728886.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
ROOM_1_FLR_3 | 1460156.71 | 95273.53 | 1555430.24 | 80996.32 | 1636426.56 | 1946875.62 | 2190.00 | 5347.50 | 1222.50 | 0.00 |
ROOM_2_FLR_3 | 1459985.63 | 96490.54 | 1556476.18 | 80990.14 | 1637466.32 | 1946647.51 | 2190.00 | 5439.46 | 1130.54 | 0.00 |
ROOM_3_MULT19_FLR_3 | 1099911.97 | 0.00 | 1099911.97 | 22598.88 | 1122510.85 | 26397887.27 | 8395.00 | 365.00 | 0.00 | 365.00 |
ROOM_4_MULT19_FLR_3 | 19803829.30 | 100817.07 | 19904646.36 | 22605.06 | 19927251.42 | 26405105.73 | 2190.00 | 5360.28 | 1209.72 | 0.00 |
ROOM_5_FLR_3 | 1460156.71 | 95446.02 | 1555602.74 | 80996.32 | 1636599.06 | 1946875.62 | 2190.00 | 5347.50 | 1222.50 | 0.00 |
ROOM_6_FLR_3 | 1459985.63 | 103391.06 | 1563376.70 | 80990.14 | 1644366.84 | 1946647.51 | 2190.00 | 5347.50 | 1222.50 | 0.00 |
CORRIDOR_FLR_3 | 24548990.16 | 0.00 | 24548990.16 | 97940.85 | 24646931.01 | 14972100.18 | 0.00 | 0.00 | 8760.00 | 0.00 |
ROOM_1_FLR_6 | 365039.18 | 107145.54 | 472184.72 | 81012.99 | 553197.70 | 486718.90 | 1886.87 | 5357.11 | 1516.02 | 0.00 |
ROOM_2_FLR_6 | 364996.41 | 98531.53 | 463527.94 | 81006.80 | 544534.74 | 486661.88 | 1944.29 | 5524.49 | 1291.23 | 0.00 |
ROOM_3_MULT9_FLR_6 | 2345190.31 | 106999.30 | 2452189.61 | 41449.08 | 2493638.69 | 3126920.42 | 2190.00 | 5347.50 | 1222.50 | 0.00 |
BANQUET_FLR_6 | 42390036.42 | 0.00 | 42390036.42 | 197813.35 | 42587849.77 | 37458366.31 | 3752.91 | 255.45 | 4751.63 | 0.00 |
DINING_FLR_6 | 45740267.16 | 0.00 | 45740267.16 | 197813.35 | 45938080.51 | 37458366.31 | 0.00 | 0.00 | 8760.00 | 0.00 |
KITCHEN_FLR_6 | 60076188.73 | 0.00 | 60076188.73 | 177088.81 | 60253277.55 | 11584760.86 | 0.00 | 0.00 | 8760.00 | 0.00 |
CORRIDOR_FLR_6 | 12146765.25 | 0.00 | 12146765.25 | 173324.65 | 12320089.90 | 3961413.96 | 0.00 | 0.00 | 8760.00 | 0.00 |
Total Facility | 0.21E+10 | 10393172.37 | 0.21E+10 | 8162099.07 | 0.21E+10 | 0.43E+10 | 8760.00 | 8759.17 | 8760.00 | 365.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 1.3332 | 0.0000 | 1.3332 | 0.0000 | 1.3332 | 0.8545 | 0.00 | 0.00 | 8760.00 |
RETAIL_1_FLR_1 | 0.1745 | 0.0000 | 0.1745 | 0.0044 | 0.1789 | 0.0792 | 0.00 | 0.00 | 8760.00 |
RETAIL_2_FLR_1 | 0.1251 | 0.0000 | 0.1251 | 0.0017 | 0.1268 | 0.0917 | 0.00 | 0.00 | 8760.00 |
MECH_FLR_1 | 0.0990 | 0.0000 | 0.0990 | 0.0040 | 0.1030 | 0.0000 | 0.00 | 0.00 | 8760.00 |
STORAGE_FLR_1 | 0.0581 | 0.0000 | 0.0581 | 0.0023 | 0.0604 | 0.0578 | 25.33 | 8734.67 | 0.00 |
LAUNDRY_FLR_1 | 2.0334 | 0.0000 | 2.0334 | 0.0055 | 2.0389 | 0.0000 | 0.00 | 0.00 | 8760.00 |
CAFE_FLR_1 | 0.7707 | 0.0000 | 0.7707 | 0.0098 | 0.7805 | 0.4612 | 0.00 | 0.00 | 8760.00 |
LOBBY_FLR_1 | 2.5800 | 0.0000 | 2.5800 | 0.0279 | 2.6079 | 1.8940 | 0.00 | 0.00 | 8760.00 |
ROOM_1_FLR_3 | 0.0463 | 0.0030 | 0.0493 | 0.0026 | 0.0519 | 0.0617 | 2190.00 | 5347.50 | 1222.50 |
ROOM_2_FLR_3 | 0.0463 | 0.0031 | 0.0494 | 0.0026 | 0.0519 | 0.0617 | 2190.00 | 5439.46 | 1130.54 |
ROOM_4_MULT19_FLR_3 | 0.6280 | 0.0032 | 0.6312 | 0.0007 | 0.6319 | 0.8373 | 2190.00 | 5360.28 | 1209.72 |
ROOM_5_FLR_3 | 0.0463 | 0.0030 | 0.0493 | 0.0026 | 0.0519 | 0.0617 | 2190.00 | 5347.50 | 1222.50 |
ROOM_6_FLR_3 | 0.0463 | 0.0033 | 0.0496 | 0.0026 | 0.0521 | 0.0617 | 2190.00 | 5347.50 | 1222.50 |
CORRIDOR_FLR_3 | 0.7784 | 0.0000 | 0.7784 | 0.0031 | 0.7815 | 0.4748 | 0.00 | 0.00 | 8760.00 |
ROOM_1_FLR_6 | 0.0116 | 0.0034 | 0.0150 | 0.0026 | 0.0175 | 0.0154 | 1886.87 | 5357.11 | 1516.02 |
ROOM_2_FLR_6 | 0.0116 | 0.0031 | 0.0147 | 0.0026 | 0.0173 | 0.0154 | 1944.29 | 5524.49 | 1291.23 |
ROOM_3_MULT9_FLR_6 | 0.0744 | 0.0034 | 0.0778 | 0.0013 | 0.0791 | 0.0992 | 2190.00 | 5347.50 | 1222.50 |
BANQUET_FLR_6 | 1.3442 | 0.0000 | 1.3442 | 0.0063 | 1.3505 | 1.1878 | 3752.91 | 255.45 | 4751.63 |
DINING_FLR_6 | 1.4504 | 0.0000 | 1.4504 | 0.0063 | 1.4567 | 1.1878 | 0.00 | 0.00 | 8760.00 |
KITCHEN_FLR_6 | 1.9050 | 0.0000 | 1.9050 | 0.0056 | 1.9106 | 0.3674 | 0.00 | 0.00 | 8760.00 |
CORRIDOR_FLR_6 | 0.3852 | 0.0000 | 0.3852 | 0.0055 | 0.3907 | 0.1256 | 0.00 | 0.00 | 8760.00 |
Total Facility | 64.5317 | 0.3296 | 64.8613 | 0.2044 | 65.0657 | 73.7518 | 8760.00 | 8759.17 | 8760.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
FLR_3_DOAS | 41645591.30 | 804094.58 | 42449685.88 | 64690340.46 | 8758.83 | 1.17 | 0.00 | 0.00 |
VAV WITH REHEAT | 0.57E+09 | 0.00 | 0.57E+09 | 0.21E+09 | 0.00 | 0.00 | 8760.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
FLR_3_DOAS | 1.3206 | 0.0255 | 1.3461 | 2.0513 | 8758.83 | 1.17 | 0.00 |
VAV WITH REHEAT | 18.2076 | 0.0000 | 18.2076 | 6.7817 | 0.00 | 0.00 | 8760.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
FLR_3_DOAS | 0.00 | 0.00 | 0.00 | 0.00 | 6935.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
VAV WITH REHEAT | 0.00 | 0.00 | 7631.82 | 0.00 | 0.00 | 0.00 | 1128.18 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
FLR_3_DOAS | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.6681 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
VAV WITH REHEAT | 0.0000 | 0.0000 | 18.2966 | 0.0000 | 0.0000 | 0.0000 | 17.6214 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:51
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1329 |
Defaulted Fields | 1181 |
Fields with Defaults | 3960 |
Autosized Fields | 347 |
Autosizable Fields | 400 |
Autocalculated Fields | 280 |
Autocalculatable Fields | 539 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:21:51
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 4867.77 | 63071.83 | 13-MAY-05:00 | 326139.69 | 29-SEP-19:00 |
Electricity:Building | 2448.58 | 31319.00 | 03-JUN-05:00 | 151313.73 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 304.40 | 3493.55 | 02-JAN-02:10 | 22822.84 | 02-JAN-20:10 |
Electricity:SpaceType:GENERAL | 2441.49 | 31177.85 | 03-JUN-05:00 | 151072.40 | 02-JAN-20:10 |
InteriorLights:Electricity | 783.31 | 6975.88 | 03-JUN-05:00 | 64632.59 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 161.29 | 1465.65 | 02-JAN-02:10 | 13190.31 | 02-JAN-20:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 783.31 | 6975.88 | 03-JUN-05:00 | 64632.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 783.31 | 6975.88 | 03-JUN-05:00 | 64632.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 161.29 | 1465.65 | 02-JAN-02:10 | 13190.31 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 783.31 | 6975.88 | 03-JUN-05:00 | 64632.59 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 17.49 | 210.74 | 02-JAN-02:10 | 1283.20 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 7.31 | 66.40 | 02-JAN-02:10 | 597.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 7.31 | 66.40 | 02-JAN-02:10 | 597.59 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 20.26 | 244.03 | 02-JAN-02:10 | 1485.95 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 8.46 | 76.89 | 02-JAN-02:10 | 692.02 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 8.46 | 76.89 | 02-JAN-02:10 | 692.02 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 20.84 | 252.75 | 02-JAN-02:10 | 1523.62 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.37 | 76.02 | 02-JAN-02:10 | 684.18 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.37 | 76.02 | 02-JAN-02:10 | 684.18 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 6.68 | 78.96 | 02-JAN-02:10 | 493.99 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 3.08 | 27.98 | 02-JAN-02:10 | 251.84 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 3.08 | 27.98 | 02-JAN-02:10 | 251.84 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 71.91 | 998.82 | 02-JAN-02:10 | 4897.88 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 3.98 | 36.12 | 02-JAN-02:10 | 325.08 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 3.98 | 36.12 | 02-JAN-02:10 | 325.08 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 28.68 | 367.70 | 13-MAY-05:00 | 2666.80 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 14.34 | 83.19 | 01-JAN-13:10 | 1701.53 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 | 14.34 | 83.19 | 01-JAN-13:10 | 1701.53 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 259.15 | 3142.86 | 03-JUN-05:00 | 19534.01 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 110.15 | 1031.45 | 03-JUN-05:00 | 9504.80 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 110.15 | 1031.45 | 03-JUN-05:00 | 9504.80 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 19.72 | 257.38 | 01-JAN-02:10 | 1438.51 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 19.72 | 257.35 | 01-JAN-02:10 | 1438.34 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 305.38 | 4267.82 | 01-JAN-02:10 | 22404.45 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 110.39 | 934.58 | 01-JAN-02:10 | 8496.21 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 110.39 | 934.58 | 01-JAN-02:10 | 8496.21 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 305.47 | 4268.99 | 01-JAN-02:10 | 22410.58 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 110.42 | 934.84 | 01-JAN-02:10 | 8498.53 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 110.42 | 934.84 | 01-JAN-02:10 | 8498.53 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 19.72 | 257.38 | 01-JAN-02:10 | 1438.51 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 19.72 | 257.35 | 01-JAN-02:10 | 1438.34 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 4.93 | 64.34 | 01-JAN-02:10 | 359.63 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 2.31 | 19.57 | 01-JAN-02:10 | 177.88 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 2.31 | 19.57 | 01-JAN-02:10 | 177.88 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 4.93 | 64.34 | 01-JAN-02:10 | 359.59 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 2.31 | 19.56 | 01-JAN-02:10 | 177.86 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 2.31 | 19.56 | 01-JAN-02:10 | 177.86 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 36.17 | 505.54 | 01-JAN-02:10 | 2653.88 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 13.08 | 110.70 | 01-JAN-02:10 | 1006.40 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 13.08 | 110.70 | 01-JAN-02:10 | 1006.40 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 207.05 | 2514.90 | 27-MAY-05:00 | 9735.93 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 31.19 | 265.60 | 27-MAY-05:00 | 2988.03 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 31.19 | 265.60 | 27-MAY-05:00 | 2988.03 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 207.05 | 2514.90 | 27-MAY-05:00 | 9735.93 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 31.19 | 265.60 | 27-MAY-05:00 | 2988.03 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 | 31.19 | 265.60 | 27-MAY-05:00 | 2988.03 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 453.81 | 6249.79 | 02-JAN-02:10 | 18934.39 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 12.97 | 117.87 | 02-JAN-02:10 | 1060.81 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 12.97 | 117.87 | 02-JAN-02:10 | 1060.81 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1658.18 | 24201.97 | 02-JAN-02:10 | 89171.45 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 1658.18 | 24201.97 | 02-JAN-02:10 | 89171.45 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 433.74 | 5990.78 | 01-JAN-00:10 | 16487.34 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 410.33 | 5248.28 | 01-JAN-00:10 | 15744.84 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
Refrigeration:Electricity | 62.32 | 1114.62 | 03-FEB-23:30 | 3263.16 | 14-JUL-06:20 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
Electricity:Plant | 890.78 | 3080.87 | 02-JAN-03:00 | 164478.81 | 16-OCT-10:50 |
LowTempRefrigeration:Refrigeration:Electricity | 20.47 | 0.00 | 01-JAN-11:10 | 1893.15 | 30-SEP-10:50 |
MedTempRefrigeration:Refrigeration:Electricity | 34.75 | 928.84 | 07-JAN-02:30 | 1203.27 | 11-FEB-14:10 |
Fans:Electricity | 520.65 | 12170.16 | 30-MAR-07:10 | 34789.12 | 16-OCT-22:00 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 542.42 | 12769.01 | 29-JAN-03:00 | 35622.63 | 16-OCT-22:00 |
ExteriorEquipment:Electricity | 813.77 | 9999.82 | 02-JAN-02:20 | 49607.07 | 18-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 21.77 | 381.01 | 27-MAY-05:00 | 1291.59 | 02-JAN-21:10 |
ElectricityPurchased:Facility | 4867.77 | 63071.83 | 13-MAY-05:00 | 326139.69 | 29-SEP-19:00 |
ElectricityPurchased:Plant | 4867.77 | 63071.83 | 13-MAY-05:00 | 326139.69 | 29-SEP-19:00 |
Cogeneration:ElectricityPurchased | 4867.77 | 63071.83 | 13-MAY-05:00 | 326139.69 | 29-SEP-19:00 |
General:Cogeneration:ElectricityPurchased | 4867.77 | 63071.83 | 13-MAY-05:00 | 326139.69 | 29-SEP-19:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 4867.77 | 63071.83 | 13-MAY-05:00 | 326139.69 | 29-SEP-19:00 |
ElectricityNet:Plant | 4867.77 | 63071.83 | 13-MAY-05:00 | 326139.69 | 29-SEP-19:00 |
Cogeneration:ElectricityNet | 4867.77 | 63071.83 | 13-MAY-05:00 | 326139.69 | 29-SEP-19:00 |
General:Cogeneration:ElectricityNet | 4867.77 | 63071.83 | 13-MAY-05:00 | 326139.69 | 29-SEP-19:00 |
General:Fans:Electricity | 520.65 | 12170.16 | 30-MAR-07:10 | 34789.12 | 16-OCT-22:00 |
ExteriorLights:Electricity | 193.98 | 0.00 | 01-JAN-07:00 | 12338.45 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 193.98 | 0.00 | 01-JAN-07:00 | 12338.45 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 789.09 | 9600.00 | 01-JAN-00:10 | 48128.80 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 2.91 | 18.80 | 01-JAN-00:10 | 188.00 | 01-JAN-07:10 |
WaterSystems:Electricity | 94.78 | 1222.49 | 15-JUL-00:10 | 4752.55 | 09-JAN-07:10 |
Water Heater:WaterSystems:Electricity | 94.78 | 1222.49 | 15-JUL-00:10 | 4752.55 | 09-JAN-07:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 664.89 | 0.00 | 01-JAN-00:30 | 156617.73 | 16-OCT-11:10 |
General:Cooling:Electricity | 664.89 | 0.00 | 01-JAN-00:30 | 156617.73 | 16-OCT-11:10 |
Pumps:Electricity | 75.88 | 61.88 | 27-MAR-13:40 | 4250.92 | 29-SEP-15:20 |
General:Pumps:Electricity | 75.88 | 61.88 | 27-MAR-13:40 | 4250.92 | 29-SEP-15:20 |
WIRED_LTG_ELECTRICITY | 27.57 | 0.00 | 01-JAN-00:10 | 2275.07 | 02-JAN-20:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 5170.50 | 23626.99 | 04-AUG-02:40 | 466011.65 | 29-MAR-18:00 |
NaturalGas:Building | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Laundry:InteriorEquipment:NaturalGas | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
NaturalGas:Plant | 3381.66 | 10265.09 | 04-AUG-02:40 | 378847.74 | 28-DEC-21:40 |
WaterSystems:NaturalGas | 2478.95 | 10265.09 | 04-AUG-02:40 | 226542.04 | 06-FEB-21:40 |
Water Heater:WaterSystems:NaturalGas | 2478.95 | 10265.09 | 04-AUG-02:40 | 226542.04 | 06-FEB-21:40 |
Heating:NaturalGas | 902.72 | 0.00 | 02-JAN-11:10 | 191268.39 | 08-JAN-07:00 |
Boiler:Heating:NaturalGas | 902.72 | 0.00 | 02-JAN-11:10 | 191268.39 | 08-JAN-07:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 2816.68 | 0.00 | 01-JAN-00:10 | 502818.30 | 18-AUG-15:20 |
PlantLoopCoolingDemand:HVAC | 2816.68 | 0.00 | 01-JAN-00:10 | 502818.30 | 18-AUG-15:20 |
CoolingCoils:PlantLoopCoolingDemand | 2816.68 | 0.00 | 01-JAN-00:10 | 502818.30 | 18-AUG-15:20 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 05-MAY-20:30 |
Water:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 05-MAY-20:30 |
WaterSystems:Water | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 05-MAY-20:30 |
Water Heater:WaterSystems:Water | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:10 |
MainsWater:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 05-MAY-20:30 |
MainsWater:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 05-MAY-20:30 |
WaterSystems:MainsWater | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 05-MAY-20:30 |
Water Heater:WaterSystems:MainsWater | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:10 |
WaterUse:WaterSystems:Water | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 05-JAN-07:10 |
WaterUse:WaterSystems:MainsWater | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 05-JAN-07:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 16285.77 | 128335.22 | 27-MAR-13:40 | 1929063.16 | 18-AUG-15:20 |
EnergyTransfer:Building | 5105.28 | 93984.84 | 29-MAR-12:00 | 299571.61 | 16-OCT-18:10 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 734.22 | 11871.22 | 07-JAN-03:00 | 35322.44 | 30-SEP-10:50 |
Refrigeration:EnergyTransfer | 185.64 | 3947.76 | 07-JAN-02:30 | 10368.69 | 14-JUL-06:20 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 92.82 | 1973.88 | 07-JAN-02:30 | 5184.35 | 14-JUL-06:20 |
General:Refrigeration:EnergyTransfer | 92.82 | 1973.88 | 07-JAN-02:30 | 5184.35 | 14-JUL-06:20 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 92.82 | 1973.88 | 07-JAN-02:30 | 5184.35 | 14-JUL-06:20 |
EnergyTransfer:Plant | 7787.20 | 20688.02 | 27-MAR-13:40 | 1164129.08 | 18-AUG-15:20 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 21.67 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 71.15 | 1736.53 | 07-JAN-02:30 | 2559.81 | 11-FEB-14:10 |
EnergyTransfer:Zone:BASEMENT | 397.71 | 9955.39 | 31-MAR-14:00 | 22096.14 | 08-JAN-07:00 |
Heating:EnergyTransfer | 6.63 | 0.00 | 01-JAN-08:10 | 12730.16 | 28-MAR-08:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 6.63 | 0.00 | 01-JAN-08:10 | 12730.16 | 28-MAR-08:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 5005.82 | 91249.37 | 29-MAR-12:00 | 296025.88 | 16-OCT-18:10 |
Cooling:EnergyTransfer:Zone:BASEMENT | 397.71 | 9955.39 | 31-MAR-14:00 | 22096.14 | 08-JAN-07:00 |
General:Cooling:EnergyTransfer | 5005.82 | 91249.37 | 29-MAR-12:00 | 296025.88 | 16-OCT-18:10 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 397.71 | 9955.39 | 31-MAR-14:00 | 22096.14 | 08-JAN-07:00 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 45.48 | 5.79 | 30-MAR-06:10 | 4013.08 | 16-OCT-12:20 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 3.59 | 30-MAR-06:10 |
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 3.59 | 30-MAR-06:10 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 45.48 | 2.20 | 30-MAR-06:10 | 4013.08 | 16-OCT-12:20 |
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 45.48 | 2.20 | 30-MAR-06:10 | 4013.08 | 16-OCT-12:20 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 37.47 | 786.84 | 29-MAR-12:10 | 1981.03 | 16-OCT-20:10 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 37.47 | 786.84 | 29-MAR-12:10 | 1981.03 | 16-OCT-20:10 |
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 37.47 | 786.84 | 29-MAR-12:10 | 1981.03 | 16-OCT-20:10 |
EnergyTransfer:Zone:MECH_FLR_1 | 27.56 | 414.79 | 30-MAR-10:00 | 1322.24 | 28-JAN-07:00 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 27.56 | 414.79 | 30-MAR-10:00 | 1322.24 | 28-JAN-07:00 |
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 27.56 | 414.79 | 30-MAR-10:00 | 1322.24 | 28-JAN-07:00 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 15.57 | 133.71 | 30-MAR-04:00 | 722.59 | 27-JAN-05:00 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 15.57 | 133.71 | 30-MAR-04:00 | 722.59 | 27-JAN-05:00 |
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 15.57 | 133.71 | 30-MAR-04:00 | 722.59 | 27-JAN-05:00 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 606.94 | 10058.91 | 09-JAN-05:00 | 38380.00 | 29-SEP-20:00 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 606.94 | 10058.91 | 09-JAN-05:00 | 38380.00 | 29-SEP-20:00 |
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 606.94 | 10058.91 | 09-JAN-05:00 | 38380.00 | 29-SEP-20:00 |
EnergyTransfer:Zone:CAFE_FLR_1 | 235.51 | 2454.41 | 29-MAR-12:10 | 14055.17 | 19-NOV-11:00 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 235.51 | 2454.41 | 29-MAR-12:10 | 14055.17 | 19-NOV-11:00 |
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 235.51 | 2454.41 | 29-MAR-12:10 | 14055.17 | 19-NOV-11:00 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 799.96 | 16745.69 | 29-MAR-11:40 | 38779.30 | 16-OCT-21:10 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 799.96 | 16745.69 | 29-MAR-11:40 | 38779.30 | 16-OCT-21:10 |
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 799.96 | 16745.69 | 29-MAR-11:40 | 38779.30 | 16-OCT-21:10 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 53.42 | 0.00 | 01-JAN-08:10 | 9821.08 | 30-SEP-15:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 0.65 | 0.00 | 01-JAN-07:50 | 1560.68 | 29-MAR-04:10 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 0.65 | 0.00 | 01-JAN-07:50 | 1560.68 | 29-MAR-04:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 52.77 | 0.00 | 01-JAN-00:10 | 9821.08 | 30-SEP-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 52.77 | 0.00 | 01-JAN-00:10 | 9821.08 | 30-SEP-15:10 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 33.47 | 0.00 | 01-JAN-08:10 | 9282.99 | 30-SEP-15:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 1.28 | 0.00 | 01-JAN-08:10 | 1665.98 | 30-MAR-08:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 1.28 | 0.00 | 01-JAN-08:10 | 1665.98 | 30-MAR-08:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 32.20 | 0.00 | 01-JAN-00:10 | 9282.99 | 30-SEP-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 32.20 | 0.00 | 01-JAN-00:10 | 9282.99 | 30-SEP-15:10 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 321.35 | 0.00 | 01-JAN-00:10 | 48790.83 | 16-OCT-12:20 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 321.35 | 0.00 | 01-JAN-00:10 | 48790.83 | 16-OCT-12:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 321.35 | 0.00 | 01-JAN-00:10 | 48790.83 | 16-OCT-12:20 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 362.92 | 0.00 | 01-JAN-08:10 | 63059.17 | 22-JUN-20:30 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 0.62 | 0.00 | 01-JAN-00:10 | 6339.37 | 03-JAN-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 0.62 | 0.00 | 01-JAN-00:10 | 6339.37 | 03-JAN-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 362.30 | 0.00 | 01-JAN-08:10 | 63059.17 | 22-JUN-20:30 |
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 362.30 | 0.00 | 01-JAN-08:10 | 63059.17 | 22-JUN-20:30 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 49.74 | 0.00 | 01-JAN-08:10 | 9425.59 | 15-OCT-08:10 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 0.73 | 0.00 | 01-JAN-07:10 | 1782.17 | 30-MAR-04:00 |
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 0.73 | 0.00 | 01-JAN-07:10 | 1782.17 | 30-MAR-04:00 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 49.01 | 0.00 | 01-JAN-00:10 | 9425.59 | 15-OCT-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 49.01 | 0.00 | 01-JAN-00:10 | 9425.59 | 15-OCT-08:10 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 32.10 | 0.00 | 01-JAN-08:10 | 9812.90 | 17-OCT-08:40 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 1.42 | 0.00 | 01-JAN-07:20 | 1867.66 | 30-MAR-04:00 |
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 1.42 | 0.00 | 01-JAN-07:20 | 1867.66 | 30-MAR-04:00 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 30.68 | 0.00 | 01-JAN-00:10 | 9812.90 | 17-OCT-08:40 |
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 30.68 | 0.00 | 01-JAN-00:10 | 9812.90 | 17-OCT-08:40 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 210.89 | 2802.59 | 29-MAR-12:00 | 10386.74 | 28-JAN-07:00 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 210.89 | 2802.59 | 29-MAR-12:00 | 10386.74 | 28-JAN-07:00 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 210.89 | 2802.59 | 29-MAR-12:00 | 10386.74 | 28-JAN-07:00 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 12.83 | 0.00 | 01-JAN-08:10 | 2610.30 | 30-SEP-15:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 0.55 | 0.00 | 01-JAN-08:10 | 599.40 | 29-MAR-08:10 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 0.55 | 0.00 | 01-JAN-08:10 | 599.40 | 29-MAR-08:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 12.28 | 0.00 | 01-JAN-00:10 | 2610.30 | 30-SEP-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 12.28 | 0.00 | 01-JAN-00:10 | 2610.30 | 30-SEP-15:10 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 8.44 | 0.00 | 01-JAN-08:10 | 2454.70 | 17-AUG-15:20 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 0.95 | 0.00 | 01-JAN-08:10 | 646.27 | 30-MAR-08:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 0.95 | 0.00 | 01-JAN-08:10 | 646.27 | 30-MAR-08:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 7.49 | 0.00 | 01-JAN-00:10 | 2454.70 | 17-AUG-15:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 7.49 | 0.00 | 01-JAN-00:10 | 2454.70 | 17-AUG-15:20 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 84.58 | 0.00 | 01-JAN-08:10 | 13532.73 | 31-OCT-15:10 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 0.43 | 0.00 | 01-JAN-00:10 | 2252.40 | 30-MAR-04:00 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 0.43 | 0.00 | 01-JAN-00:10 | 2252.40 | 30-MAR-04:00 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 84.15 | 0.00 | 01-JAN-00:30 | 13532.73 | 31-OCT-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 84.15 | 0.00 | 01-JAN-00:30 | 13532.73 | 31-OCT-15:10 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 445.90 | 9411.46 | 29-MAR-11:40 | 21449.45 | 29-SEP-21:10 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 445.90 | 9411.46 | 29-MAR-11:40 | 21449.45 | 29-SEP-21:10 |
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 445.90 | 9411.46 | 29-MAR-11:40 | 21449.45 | 29-SEP-21:10 |
EnergyTransfer:Zone:DINING_FLR_6 | 485.76 | 10428.89 | 29-MAR-11:40 | 22812.48 | 29-SEP-21:10 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 485.76 | 10428.89 | 29-MAR-11:40 | 22812.48 | 29-SEP-21:10 |
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 485.76 | 10428.89 | 29-MAR-11:40 | 22812.48 | 29-SEP-21:10 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 641.40 | 9800.57 | 07-JAN-03:10 | 30305.06 | 30-SEP-10:50 |
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 641.40 | 9800.57 | 07-JAN-03:10 | 30305.06 | 30-SEP-10:50 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 103.43 | 626.51 | 30-MAR-06:10 | 5183.82 | 30-SEP-13:40 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 103.43 | 626.51 | 30-MAR-06:10 | 5183.82 | 30-SEP-13:40 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 103.43 | 626.51 | 30-MAR-06:10 | 5183.82 | 30-SEP-13:40 |
PlantLoopHeatingDemand:Facility | 1276.05 | 9088.53 | 04-AUG-01:00 | 178546.26 | 08-JAN-07:00 |
PlantLoopHeatingDemand:Plant | 699.43 | 9088.53 | 04-AUG-01:00 | 48539.47 | 02-FEB-07:10 |
WaterSystems:PlantLoopHeatingDemand | 699.43 | 9088.53 | 04-AUG-01:00 | 48539.47 | 02-FEB-07:10 |
General:WaterSystems:PlantLoopHeatingDemand | 699.43 | 9088.53 | 04-AUG-01:00 | 48539.47 | 02-FEB-07:10 |
EnergyTransfer:HVAC | 3393.30 | 228.60 | 27-MAR-11:50 | 502818.30 | 18-AUG-15:20 |
HeatingCoils:EnergyTransfer | 576.62 | 0.00 | 02-JAN-11:10 | 151503.07 | 08-JAN-07:00 |
PlantLoopHeatingDemand:HVAC | 576.62 | 0.00 | 02-JAN-11:10 | 151503.07 | 08-JAN-07:00 |
HeatingCoils:PlantLoopHeatingDemand | 576.62 | 0.00 | 02-JAN-11:10 | 151503.07 | 08-JAN-07:00 |
CoolingCoils:EnergyTransfer | 2816.68 | 0.00 | 01-JAN-00:10 | 502818.30 | 18-AUG-15:20 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 699.43 | 9088.53 | 04-AUG-01:00 | 48539.47 | 02-FEB-07:10 |
WaterUse:WaterSystems:EnergyTransfer | 699.43 | 9088.53 | 04-AUG-01:00 | 48539.47 | 02-FEB-07:10 |
Boilers:EnergyTransfer | 572.87 | 0.00 | 02-JAN-11:10 | 150697.24 | 08-JAN-07:00 |
Chillers:EnergyTransfer | 2878.59 | 0.00 | 01-JAN-00:30 | 504857.75 | 18-AUG-15:20 |
HeatRejection:EnergyTransfer | 3543.48 | 0.00 | 01-JAN-00:30 | 642206.78 | 18-AUG-15:20 |
General:HeatRejection:EnergyTransfer | 3543.48 | 0.00 | 01-JAN-00:30 | 642206.78 | 18-AUG-15:20 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:51
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -397.710 | 0.000 | 0.000 | 142.425 | 161.294 | 143.105 | 0.000 | 0.000 | 0.000 | 0.002 | 0.000 | 0.000 | 0.000 | 0.000 | -49.114 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 0.000 | -45.483 | 0.000 | 0.000 | 15.377 | 7.307 | 10.186 | 21.133 | 0.000 | 0.020 | 0.791 | 0.000 | -8.270 | 0.000 | -1.060 | -0.000 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.000 | -37.473 | 0.000 | 0.000 | 16.680 | 8.462 | 11.795 | 0.000 | 0.000 | 0.009 | 0.992 | 0.000 | 0.000 | 0.000 | -0.464 | -0.000 |
MECH_FLR_1 | 0.000 | 0.000 | 0.000 | -27.559 | 0.000 | 0.000 | 3.659 | 8.366 | 12.471 | 0.000 | 0.000 | 0.023 | 4.057 | 0.000 | 0.000 | 0.000 | -1.018 | -0.000 |
STORAGE_FLR_1 | 0.000 | 0.000 | 0.000 | -15.571 | 0.000 | 0.000 | 2.857 | 3.079 | 3.598 | 0.000 | 0.000 | 0.014 | 6.589 | 0.000 | 0.000 | 0.000 | -0.567 | 0.000 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.000 | -606.944 | 0.000 | 0.000 | 11.372 | 3.975 | 658.131 | 0.000 | 0.000 | 0.037 | 0.000 | 0.000 | 0.000 | 0.000 | -1.480 | -65.092 |
CAFE_FLR_1 | 0.000 | 0.000 | 0.000 | -235.512 | 0.000 | 0.000 | 187.611 | 14.344 | 14.341 | 58.393 | 0.000 | 0.046 | 0.000 | 0.000 | -25.714 | 0.000 | -2.706 | -10.803 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.000 | -799.961 | 0.000 | 0.000 | 550.958 | 110.149 | 148.998 | 77.575 | 0.000 | 0.142 | 0.000 | 0.000 | -34.397 | 0.000 | -7.872 | -45.592 |
ROOM_1_FLR_3 | 1.901 | -42.579 | 0.000 | -11.437 | 0.000 | 0.000 | 9.652 | 9.244 | 10.478 | 43.594 | 0.000 | 0.103 | 1.984 | 0.000 | -18.996 | 0.000 | -3.945 | -0.001 |
ROOM_2_FLR_3 | 3.161 | -21.738 | 0.000 | -12.341 | 0.000 | 0.000 | 9.433 | 9.243 | 10.477 | 30.902 | 0.000 | 0.066 | 0.000 | 0.000 | -19.762 | 0.000 | -4.901 | -4.541 |
ROOM_3_MULT19_FLR_3 | 0.000 | -304.672 | 0.000 | -16.679 | 0.000 | 0.000 | 0.000 | 110.385 | 194.997 | 221.772 | 0.000 | 0.064 | 0.023 | 0.000 | -162.123 | 0.000 | -22.217 | -21.526 |
ROOM_4_MULT19_FLR_3 | 5.402 | -205.679 | 0.000 | -161.378 | 0.000 | 0.000 | 181.595 | 110.415 | 195.050 | 66.147 | 0.000 | 0.545 | 0.001 | 0.000 | -104.438 | 0.000 | -52.410 | -35.249 |
ROOM_5_FLR_3 | 2.073 | -38.916 | 0.000 | -11.439 | 0.000 | 0.000 | 9.646 | 9.244 | 10.478 | 40.476 | 0.000 | 0.102 | 0.833 | 0.000 | -18.536 | 0.000 | -3.962 | -0.000 |
ROOM_6_FLR_3 | 3.380 | -20.481 | 0.000 | -12.156 | 0.000 | 0.000 | 9.498 | 9.243 | 10.477 | 27.617 | 0.000 | 0.065 | 0.000 | 0.000 | -18.802 | 0.000 | -4.791 | -4.051 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 0.000 | -210.891 | 0.000 | 0.000 | 117.195 | 91.336 | 0.000 | 36.638 | 0.000 | 0.074 | 0.000 | 0.000 | -23.316 | 0.000 | -3.058 | -7.978 |
ROOM_1_FLR_6 | 1.125 | -9.990 | 0.000 | -2.860 | 0.000 | 0.000 | 2.415 | 2.311 | 2.620 | 10.761 | 0.000 | 0.026 | 0.000 | 0.000 | -4.687 | 0.000 | -1.034 | -0.686 |
ROOM_2_FLR_6 | 1.692 | -5.131 | 0.000 | -3.097 | 0.000 | 0.000 | 2.355 | 2.311 | 2.619 | 7.603 | 0.000 | 0.016 | 0.000 | 0.000 | -4.896 | 0.000 | -1.237 | -2.236 |
ROOM_3_MULT9_FLR_6 | 1.599 | -66.931 | 0.000 | -18.390 | 0.000 | 0.000 | 21.705 | 13.076 | 23.098 | 54.610 | 0.000 | 0.169 | 0.002 | 0.000 | -21.937 | 0.000 | -6.731 | -0.268 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.000 | -445.898 | 0.000 | 0.000 | 316.312 | 31.195 | 175.857 | 6.151 | 0.000 | 0.021 | 0.000 | 0.000 | -14.214 | 0.000 | -1.917 | -67.506 |
DINING_FLR_6 | 0.000 | 0.000 | 0.000 | -485.765 | 0.000 | 0.000 | 315.268 | 31.195 | 175.857 | 5.831 | 0.000 | 0.019 | 0.000 | 0.000 | -14.677 | 0.000 | -1.938 | -25.791 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.000 | -641.388 | 0.000 | 0.000 | 28.413 | 12.972 | 550.372 | 18.652 | 0.000 | 0.016 | 42.911 | 0.000 | -10.227 | 0.000 | -1.721 | 0.000 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 0.000 | -103.429 | 0.000 | 0.000 | 31.143 | 24.166 | 0.000 | 17.742 | 0.000 | 0.024 | 42.233 | 0.000 | -10.522 | 0.000 | -1.358 | 0.000 |
Total Facility | 20.332 | -716.118 | 0.000 | -4303.358 | 0.000 | 0.000 | 1985.568 | 783.315 | 2365.005 | 745.596 | 0.000 | 1.602 | 100.419 | 0.000 | -515.512 | 0.000 | -126.385 | -340.436 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 08-JAN-07:00 | 0.00 | 0.00 | 0.00 | -22092.80 | 0.00 | 0.00 | 5811.90 | 4396.77 | 4055.80 | 0.00 | 0.00 | 0.00 | 7828.32 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 16-OCT-12:20 | 0.00 | 0.00 | 0.00 | -4013.00 | 0.00 | 0.00 | 150.60 | 166.00 | 252.59 | 4697.51 | 0.00 | 56.73 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1310.43 |
RETAIL_2_FLR_1 | 16-OCT-20:10 | 0.00 | 0.00 | 0.00 | -1980.60 | 0.00 | 0.00 | 697.63 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -7.08 | -77.21 |
MECH_FLR_1 | 28-JAN-07:00 | 0.00 | 0.00 | 0.00 | -1322.05 | 0.00 | 0.00 | 151.90 | 228.06 | 353.45 | 0.00 | 0.00 | 0.00 | 681.35 | 0.00 | -0.00 | 0.00 | -92.71 | 0.00 |
STORAGE_FLR_1 | 27-JAN-04:55 | 0.00 | 0.00 | 0.00 | -723.71 | 0.00 | 0.00 | 149.35 | 27.98 | 50.98 | 0.00 | 0.00 | 0.00 | 546.21 | 0.00 | -0.00 | 0.00 | -50.81 | 0.00 |
LAUNDRY_FLR_1 | 29-SEP-20:00 | 0.00 | 0.00 | 0.00 | -38379.97 | 0.00 | 0.00 | 408.86 | 325.08 | 44299.38 | 0.00 | 0.00 | 6.40 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -6659.75 |
CAFE_FLR_1 | 19-NOV-11:00 | 0.00 | 0.00 | 0.00 | -14060.48 | 0.00 | 0.00 | 4947.83 | 124.78 | 406.43 | 13663.13 | 0.00 | 22.79 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5104.49 |
LOBBY_FLR_1 | 16-OCT-21:10 | 0.00 | 0.00 | 0.00 | -38770.12 | 0.00 | 0.00 | 26440.96 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 374.35 | 0.00 | -1582.72 | 0.00 | -188.94 | 0.00 |
ROOM_1_FLR_3 | 14-OCT-08:61 | 0.00 | -12542.93 | 0.00 | -728.66 | 0.00 | 0.00 | 130.71 | 398.46 | 653.23 | 2466.85 | 0.00 | 59.20 | 9563.14 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 14-OCT-08:61 | 0.00 | -12504.69 | 0.00 | -769.57 | 0.00 | 0.00 | 125.46 | 398.41 | 653.15 | 1226.87 | 0.00 | 52.62 | 10817.75 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 16-OCT-12:20 | 0.00 | -48791.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2378.94 | 2352.88 | 55563.17 | 0.00 | 531.69 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -12035.63 |
ROOM_4_MULT19_FLR_3 | 14-OCT-08:61 | 0.00 | -78682.06 | 0.00 | -10587.34 | 0.00 | 0.00 | 2408.47 | 4759.18 | 12159.85 | 6684.88 | 0.00 | 268.35 | 62988.67 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 14-OCT-08:61 | 0.00 | -11362.15 | 0.00 | -743.36 | 0.00 | 0.00 | 130.71 | 398.46 | 653.23 | 7039.29 | 0.00 | 56.83 | 3826.99 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 17-OCT-08:21 | 0.00 | -12633.17 | 0.00 | -926.21 | 0.00 | 0.00 | 71.66 | 313.04 | 452.99 | 6544.11 | 0.00 | 25.63 | 6151.94 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 28-JAN-07:00 | 0.00 | 0.00 | 0.00 | -10384.95 | 0.00 | 0.00 | 4812.51 | 2489.76 | 0.00 | 0.00 | 0.00 | 0.00 | 5211.61 | 0.00 | -1843.42 | 0.00 | -285.51 | 0.00 |
ROOM_1_FLR_6 | 26-OCT-15:01 | 0.00 | -3244.86 | 0.00 | -182.11 | 0.00 | 0.00 | 58.82 | 49.81 | 50.05 | 1591.70 | 0.00 | 0.00 | 1679.04 | 0.00 | -0.00 | 0.00 | -2.43 | 0.00 |
ROOM_2_FLR_6 | 14-OCT-08:61 | 0.00 | -3143.32 | 0.00 | -184.55 | 0.00 | 0.00 | 32.24 | 99.60 | 163.29 | 317.48 | 0.00 | 14.24 | 2701.02 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 14-OCT-08:61 | 0.00 | -15520.15 | 0.00 | -1185.10 | 0.00 | 0.00 | 294.11 | 563.59 | 1439.98 | 5466.68 | 0.00 | 65.61 | 8875.29 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 29-SEP-21:10 | 0.00 | 0.00 | 0.00 | -21449.74 | 0.00 | 0.00 | 15644.30 | 1992.02 | 6747.90 | 0.00 | 0.00 | 3.54 | 0.00 | 0.00 | -214.81 | 0.00 | 0.00 | -2723.21 |
DINING_FLR_6 | 29-SEP-21:10 | 0.00 | 0.00 | 0.00 | -22812.92 | 0.00 | 0.00 | 15644.19 | 1992.02 | 6747.90 | 0.00 | 0.00 | 3.54 | 0.00 | 0.00 | -230.92 | 0.00 | 0.00 | -1343.81 |
KITCHEN_FLR_6 | 30-SEP-10:50 | 0.00 | 0.00 | 0.00 | -30341.04 | 0.00 | 0.00 | 460.90 | 294.67 | 24259.91 | 2355.32 | 0.00 | 42.23 | 2928.02 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 30-SEP-13:40 | 0.00 | 0.00 | 0.00 | -5184.16 | 0.00 | 0.00 | 462.68 | 548.96 | 0.00 | 2835.62 | 0.00 | 49.26 | 1287.64 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 15-OCT-08:61 | 0.00 | -176299.36 | 0.00 | -156590.81 | 0.00 | 0.00 | 50316.26 | 24800.21 | 89868.82 | 97827.30 | 0.00 | 1709.04 | 68368.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 30-MAR-06:07 | 0.00 | 0.00 | 5.52 | 0.00 | 0.00 | 0.00 | 357.99 | 332.00 | 433.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -695.28 | 0.00 | -85.36 | -347.88 |
RETAIL_2_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 21-MAR-18:04 | 4230.03 | 414.75 | 0.00 | -414.75 | 0.00 | 0.00 | 335.50 | 633.26 | 484.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1148.66 | 0.00 | -91.03 | -4443.75 |
ROOM_2_FLR_3 | 24-NOV-16:03 | 4212.92 | 418.39 | 0.00 | -418.39 | 0.00 | 0.00 | 253.07 | 199.20 | 200.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -288.82 | 0.00 | -521.20 | -4055.33 |
ROOM_3_MULT19_FLR_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 18-FEB-16:04 | 21716.38 | 5698.50 | 0.00 | -5698.50 | 0.00 | 0.00 | 2615.43 | 2804.51 | 4118.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -204.85 | 0.00 | -10271.28 | -20778.86 |
ROOM_5_FLR_3 | 16-NOV-16:04 | 4123.59 | 415.94 | 0.00 | -415.94 | 0.00 | 0.00 | 235.28 | 199.23 | 200.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -59.75 | 0.00 | -577.35 | -4121.18 |
ROOM_6_FLR_3 | 18-APR-15:04 | 4008.28 | 429.94 | 0.00 | -429.94 | 0.00 | 0.00 | 238.16 | 199.20 | 200.16 | 777.86 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -671.02 | -4752.64 |
CORRIDOR_FLR_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 16-JUN-15:04 | 1238.29 | 120.03 | 0.00 | -120.03 | 0.00 | 0.00 | 58.82 | 49.81 | 50.05 | 191.11 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -109.50 | -1478.58 |
ROOM_2_FLR_6 | 13-MAY-15:04 | 1222.33 | 110.77 | 0.00 | -110.77 | 0.00 | 0.00 | 32.68 | 58.69 | 55.31 | 910.27 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -201.59 | -2077.69 |
ROOM_3_MULT9_FLR_6 | 17-APR-15:04 | 5894.43 | 762.08 | 0.00 | -762.08 | 0.00 | 0.00 | 529.39 | 281.79 | 441.28 | 1387.41 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -2185.70 | -6348.61 |
BANQUET_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 20-MAR-15:04 | -70353.78 | 123314.08 | 0.00 | -123314.08 | 0.00 | 0.00 | 56840.82 | 16709.04 | 73912.59 | 4268.19 | 0.00 | 0.00 | 0.00 | 0.00 | -1299.74 | 0.00 | -18308.56 | -61768.56 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:51
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV WITH REHEAT | 21.3005 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 21.1819 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV WITH REHEAT | 11.6514 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 11.6514 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.6520 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.0400 | 0.000610 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.000000 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.003540 | 142.3000 | 0.000914 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.000000 | 422.4350 | 0.001448 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 83.8280 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003556 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.1800 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 | |
VAV WITH REHEAT | 0.00 | 0.000970 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.4359 | 2.4359 | 1.3324 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3124 | 0.3124 | 0.1709 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2278 | 0.2278 | 0.1246 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1811 | 0.1811 | 0.0991 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1063 | 0.1063 | 0.0581 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.2963 | 3.2963 | 1.8031 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3820 | 1.3820 | 0.7559 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.6634 | 4.6634 | 2.5509 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4242 | 1.4242 | 0.7790 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1194 | 2.1194 | 1.1593 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2226 | 2.2226 | 1.2158 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2246 | 2.2246 | 1.2168 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7046 | 0.7046 | 0.3854 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
VAV WITH REHEAT | 21.3005 | 21.1819 | 21.3005 | 11.6514 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3324 | 1.3324 | 1.3324 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1709 | 0.1709 | 0.1709 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1246 | 0.1246 | 0.1246 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0991 | 0.0991 | 0.0991 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0581 | 0.0581 | 0.0581 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8031 | 1.8031 | 1.8031 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7559 | 0.7559 | 0.7559 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.5509 | 2.5509 | 2.5509 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7790 | 0.7790 | 0.7790 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1593 | 1.1593 | 1.1593 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2158 | 1.2158 | 1.2158 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2168 | 1.2168 | 1.2168 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3854 | 0.3854 | 0.3854 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
VAV WITH REHEAT | 11.6514 | 11.6514 | 11.6514 | 11.6514 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:51
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 168.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 168.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 56.00 |
Number of hours not met | 56.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 902.72 | 191268.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 664.89 | 156617.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 783.31 | 64632.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 193.98 | 12338.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 872.72 | 59188.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 14.43 | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 8.99 | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.20 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 21.77 | 1291.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 789.09 | 48128.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 2.91 | 188.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 520.65 | 34789.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 75.88 | 4250.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 94.78 | 4752.55 | 2478.95 | 226542.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.09 | 2093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 20.47 | 1893.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 34.75 | 1203.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1720.50 | 4867.77 |
Natural Gas | 1788.84 | 5170.50 |
Additional | 0.00 | 0.00 |
Total | 3509.34 | 10038.27 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 69.04 |
Space Heating | 0.00 |
Space Cooling | 58.60 |
Fans (All) | 45.89 |
Service Water Heating | 8.35 |
Receptacle Equipment | 146.16 |
Miscellaneous (All) | 429.06 |
Subtotal | 429.06 |
Natural Gas [MJ/m2] | |
Space Heating | 79.57 |
Service Water Heating | 218.50 |
Miscellaneous (All) | 455.74 |
Subtotal | 455.74 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 7.80 |
Space Heating | 8.99 |
Space Cooling | 6.62 |
Fans (All) | 5.19 |
Service Water Heating | 25.64 |
Receptacle Equipment | 34.34 |
Miscellaneous | 11.42 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 486. | 5110. |
ELEVATOR_STANDBY_SCH | 7671. | 8760. |
LTG_SCH_KITCHEN | 3061. | 8760. |
LTG_SCH_DINING | 3061. | 8760. |
LTG_SCH_BASEMENT | 2572. | 8760. |
LTG_SCH_LOBBY | 2295. | 8760. |
LTG_SCH_STORAGE | 1580. | 8760. |
LTG_SCH_MECHANIC | 3061. | 8760. |
LTG_SCH_LAUNDRY | 3061. | 8760. |
LTG_SCH_GUESTROOM | 1980. | 8760. |
LTG_SCH_CORRIDOR | 2295. | 8760. |
LTG_SCH_RETAIL | 2678. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 1591. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3737. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 5740. | 6205. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 8760. | 8760. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 26.67 | 365 | 26.67 | 365 |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
HTGSETP_SCH | BASEMENT DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:51
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8711.50 | 48.50 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 7161.33 | 1598.67 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8752.67 | 7.33 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8650.50 | 109.50 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 7161.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 1598.67 | 0.00 | 0.00 | 0.00 |
Average | 8679.82 | 80.18 | 0.00 | 0.00 | 0.00 |
Sum | 190956.00 | 1764.00 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4149.67 | 4.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4133.67 | 20.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108269.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 20.33 | 0.00 | 0.00 | 0.00 |
Average | 288885.92 | 1.12 | 0.00 | 0.00 | 0.00 |
Sum | 6355490.33 | 24.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 7859.83 | 900.17 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 7954.50 | 805.50 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8483.33 | 276.67 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 5875.33 | 2884.67 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8752.17 | 7.83 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8627.00 | 133.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8341.67 | 418.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 7889.83 | 870.17 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 7987.33 | 772.67 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8697.67 | 62.33 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 5875.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 2884.67 | 0.00 | 0.00 | 0.00 |
Average | 8435.85 | 324.15 | 0.00 | 0.00 | 0.00 |
Sum | 185588.67 | 7131.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 599671.67 | 110745.33 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 1826386.67 | 289042.33 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4026.83 | 127.17 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4153.00 | 1.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4142.67 | 11.33 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 3949.50 | 204.50 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1065164.33 | 180550.67 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1084041.83 | 161673.17 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 107667.67 | 601.33 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 1826386.67 | 289042.33 | 0.00 | 0.00 | 0.00 |
Average | 255116.28 | 33770.77 | 0.00 | 0.00 | 0.00 |
Sum | 5612558.17 | 742956.83 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:51
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:51
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 1592.73 | 0.00 | 0.00 |
Sum | 0.00 | 35040.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 710417.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 2115429.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 2115429.00 | 0.00 | 0.00 |
Average | 0.00 | 241694.36 | 0.00 | 0.00 |
Sum | 0.00 | 5317276.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C
For: Environment
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Environment
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO
For: Environment
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.355749E+11 | 22096.14 | 08-JAN-07:00 | 1.00 | -0.3 | 0.765983E+10 | 4837.05 | 24-JAN-23:10 | 14.33 | 10.84 |
February | 0.294135E+11 | 17115.76 | 04-FEB-05:55 | 5.00 | 0.22 | 0.668199E+10 | 4780.99 | 01-FEB-22:19 | 5.00 | 0.22 |
March | 0.322013E+11 | 17505.81 | 08-MAR-02:00 | 4.00 | 3.53 | 0.719939E+10 | 4522.44 | 24-MAR-22:10 | 13.00 | 11.29 |
April | 0.305997E+11 | 14895.94 | 30-APR-10:33 | 25.67 | 16.97 | 0.698024E+10 | 4505.14 | 14-APR-21:19 | 25.67 | 16.97 |
May | 0.316693E+11 | 14628.35 | 28-MAY-10:33 | 21.00 | 15.43 | 0.723236E+10 | 4506.75 | 12-MAY-21:10 | 21.00 | 15.43 |
June | 0.305724E+11 | 14788.29 | 25-JUN-10:33 | 23.00 | 17.26 | 0.695046E+10 | 4458.95 | 09-JUN-21:19 | 23.00 | 17.26 |
July | 0.334402E+11 | 15672.76 | 23-JUL-10:33 | 25.67 | 20.39 | 0.739748E+10 | 4623.01 | 28-JUL-22:10 | 18.00 | 17.35 |
August | 0.339315E+11 | 15659.67 | 13-AUG-10:33 | 24.00 | 19.90 | 0.751105E+10 | 4651.09 | 11-AUG-22:10 | 24.00 | 19.90 |
September | 0.337839E+11 | 16160.27 | 30-SEP-10:33 | 30.57 | 17.23 | 0.747475E+10 | 4808.76 | 28-SEP-22:10 | 30.57 | 17.23 |
October | 0.361322E+11 | 16934.47 | 20-OCT-21:00 | 16.00 | 13.03 | 0.791319E+10 | 4837.09 | 18-OCT-21:30 | 16.00 | 13.03 |
November | 0.348943E+11 | 17164.12 | 22-NOV-22:00 | 11.00 | 2.60 | 0.768014E+10 | 4837.05 | 09-NOV-23:10 | 11.00 | 2.60 |
December | 0.354960E+11 | 18090.57 | 03-DEC-01:00 | 5.00 | 5.00 | 0.775594E+10 | 4837.04 | 06-DEC-22:19 | 15.00 | 9.64 |
Annual Sum or Average | 0.397709E+12 | 0.884368E+11 | ||||||||
Minimum of Months | 0.294135E+11 | 14628.35 | 1.00 | -0.3 | 0.668199E+10 | 4458.95 | 5.00 | 0.22 | ||
Maximum of Months | 0.361322E+11 | 22096.14 | 30.57 | 20.39 | 0.791319E+10 | 4837.09 | 30.57 | 19.90 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.385175E+10 | 3252.13 | 14-JAN-12:40 | 25.33 | 11.70 | 0.675250E+09 | 441.78 | 18-JAN-22:30 | 16.50 | 13.26 |
February | 0.317629E+10 | 2915.66 | 02-FEB-12:40 | 19.33 | 12.36 | 0.603184E+09 | 442.79 | 01-FEB-22:30 | 19.33 | 12.36 |
March | 0.317285E+10 | 2533.58 | 11-MAR-13:00 | 24.00 | 13.82 | 0.655903E+09 | 440.07 | 23-MAR-21:30 | 13.50 | 12.93 |
April | 0.350930E+10 | 2013.49 | 08-APR-10:33 | 21.67 | 16.37 | 0.650673E+09 | 439.94 | 26-APR-22:10 | 16.00 | 15.29 |
May | 0.339958E+10 | 1951.60 | 04-MAY-10:33 | 22.00 | 15.73 | 0.653653E+09 | 441.66 | 04-MAY-21:30 | 17.00 | 15.07 |
June | 0.354652E+10 | 1872.57 | 25-JUN-10:33 | 23.00 | 17.26 | 0.651714E+09 | 437.75 | 28-JUN-21:40 | 17.00 | 16.37 |
July | 0.397279E+10 | 2049.32 | 30-JUL-10:33 | 24.67 | 20.10 | 0.700676E+09 | 452.70 | 31-JUL-21:40 | 18.80 | 17.92 |
August | 0.417505E+10 | 2128.66 | 27-AUG-10:33 | 23.33 | 18.72 | 0.725548E+09 | 460.45 | 18-AUG-21:40 | 23.33 | 18.72 |
September | 0.407982E+10 | 3414.99 | 30-SEP-13:10 | 32.00 | 16.98 | 0.699370E+09 | 491.81 | 29-SEP-21:30 | 32.00 | 16.98 |
October | 0.453674E+10 | 4013.08 | 16-OCT-12:20 | 35.37 | 17.35 | 0.729241E+09 | 491.84 | 16-OCT-22:10 | 20.17 | 11.06 |
November | 0.396974E+10 | 3608.33 | 19-NOV-12:30 | 26.50 | 15.22 | 0.668270E+09 | 446.95 | 20-NOV-22:30 | 14.00 | 12.84 |
December | 0.409264E+10 | 3443.73 | 19-DEC-12:50 | 25.83 | 11.54 | 0.684308E+09 | 458.82 | 05-DEC-22:30 | 25.83 | 11.54 |
Annual Sum or Average | 0.454831E+11 | 0.809779E+10 | ||||||||
Minimum of Months | 0.317285E+10 | 1872.57 | 19.33 | 11.54 | 0.603184E+09 | 437.75 | 13.50 | 11.06 | ||
Maximum of Months | 0.453674E+10 | 4013.08 | 35.37 | 20.10 | 0.729241E+09 | 491.84 | 32.00 | 18.72 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.309922E+10 | 1699.75 | 28-JAN-07:00 | 3.00 | 2.55 | 0.856629E+09 | 569.55 | 18-JAN-23:10 | 3.00 | 2.55 |
February | 0.271737E+10 | 1571.06 | 04-FEB-05:55 | 5.00 | 0.22 | 0.783620E+09 | 569.51 | 02-FEB-23:10 | 5.00 | 0.22 |
March | 0.299558E+10 | 1584.46 | 08-MAR-02:00 | 4.00 | 3.53 | 0.851019E+09 | 569.51 | 23-MAR-21:10 | 13.83 | 13.26 |
April | 0.300460E+10 | 1523.18 | 27-APR-21:00 | 14.00 | 12.84 | 0.857834E+09 | 569.55 | 26-APR-22:10 | 14.00 | 12.84 |
May | 0.307336E+10 | 1526.23 | 03-MAY-21:00 | 16.00 | 14.77 | 0.882273E+09 | 569.55 | 04-MAY-22:10 | 16.83 | 15.02 |
June | 0.308882E+10 | 1573.99 | 30-JUN-21:00 | 16.00 | 14.76 | 0.872658E+09 | 569.55 | 19-JUN-22:10 | 16.00 | 14.76 |
July | 0.334740E+10 | 1672.24 | 31-JUL-21:00 | 19.00 | 17.66 | 0.918458E+09 | 569.55 | 21-JUL-22:10 | 19.00 | 17.66 |
August | 0.341070E+10 | 1738.65 | 18-AUG-21:00 | 19.00 | 17.66 | 0.930560E+09 | 569.55 | 10-AUG-22:10 | 19.00 | 17.66 |
September | 0.323176E+10 | 1926.60 | 29-SEP-21:00 | 24.60 | 13.50 | 0.891979E+09 | 569.55 | 13-SEP-22:10 | 24.60 | 13.50 |
October | 0.334860E+10 | 1981.03 | 16-OCT-20:10 | 20.50 | 12.73 | 0.922004E+09 | 569.55 | 18-OCT-21:30 | 14.50 | 14.21 |
November | 0.303104E+10 | 1558.66 | 29-NOV-23:00 | 7.00 | 4.66 | 0.863289E+09 | 569.54 | 10-NOV-22:30 | 7.00 | 4.66 |
December | 0.312474E+10 | 1558.75 | 03-DEC-01:00 | 5.00 | 5.00 | 0.873384E+09 | 569.54 | 05-DEC-23:10 | 17.33 | 9.21 |
Annual Sum or Average | 0.374732E+11 | 0.105037E+11 | ||||||||
Minimum of Months | 0.271737E+10 | 1523.18 | 3.00 | 0.22 | 0.783620E+09 | 569.51 | 3.00 | 0.22 | ||
Maximum of Months | 0.341070E+10 | 1981.03 | 24.60 | 17.66 | 0.930560E+09 | 569.55 | 24.60 | 17.66 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.218270E+10 | 1322.24 | 28-JAN-07:00 | 3.00 | 2.55 | 0.166617E+09 | 110.60 | 19-JAN-22:19 | 3.00 | 2.55 |
February | 0.195003E+10 | 1183.71 | 04-FEB-05:55 | 5.00 | 0.22 | 0.152685E+09 | 109.20 | 03-FEB-22:10 | 5.00 | 0.22 |
March | 0.212408E+10 | 1126.41 | 08-MAR-01:20 | 4.67 | 3.90 | 0.166259E+09 | 108.59 | 24-MAR-21:19 | 13.00 | 11.68 |
April | 0.218060E+10 | 1108.41 | 30-APR-10:33 | 25.67 | 16.97 | 0.168107E+09 | 111.38 | 27-APR-21:19 | 25.67 | 16.97 |
May | 0.230838E+10 | 1124.20 | 04-MAY-10:33 | 22.00 | 15.73 | 0.177017E+09 | 113.66 | 04-MAY-21:19 | 17.00 | 15.07 |
June | 0.236594E+10 | 1168.36 | 25-JUN-10:33 | 23.00 | 17.26 | 0.177765E+09 | 116.16 | 30-JUN-21:19 | 16.03 | 15.21 |
July | 0.256629E+10 | 1217.55 | 23-JUL-10:33 | 25.67 | 20.39 | 0.188172E+09 | 117.65 | 19-JUL-22:10 | 25.67 | 20.39 |
August | 0.256402E+10 | 1208.98 | 19-AUG-10:33 | 24.67 | 20.11 | 0.188760E+09 | 117.71 | 18-AUG-21:19 | 24.67 | 20.11 |
September | 0.239334E+10 | 1236.64 | 30-SEP-10:33 | 30.57 | 17.23 | 0.178789E+09 | 118.49 | 29-SEP-22:10 | 30.57 | 17.23 |
October | 0.249756E+10 | 1229.55 | 17-OCT-10:33 | 31.00 | 16.57 | 0.186495E+09 | 120.45 | 16-OCT-22:10 | 31.00 | 16.57 |
November | 0.219200E+10 | 1126.39 | 29-NOV-23:00 | 7.00 | 4.66 | 0.169149E+09 | 110.99 | 01-NOV-21:10 | 7.00 | 4.66 |
December | 0.223357E+10 | 1187.86 | 03-DEC-01:00 | 5.00 | 5.00 | 0.169772E+09 | 110.53 | 05-DEC-22:19 | 17.33 | 9.44 |
Annual Sum or Average | 0.275585E+11 | 0.208959E+10 | ||||||||
Minimum of Months | 0.195003E+10 | 1108.41 | 3.00 | 0.22 | 0.152685E+09 | 108.59 | 3.00 | 0.22 | ||
Maximum of Months | 0.256629E+10 | 1322.24 | 31.00 | 20.39 | 0.188760E+09 | 120.45 | 31.00 | 20.39 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.120725E+10 | 723.67 | 27-JAN-04:55 | 4.00 | 3.53 | 0.124984E+09 | 81.54 | 18-JAN-23:10 | 4.00 | 3.53 |
February | 0.110105E+10 | 678.17 | 04-FEB-05:55 | 5.00 | 0.22 | 0.114092E+09 | 80.29 | 03-FEB-23:10 | 5.00 | 0.22 |
March | 0.117011E+10 | 607.69 | 19-MAR-10:33 | 19.33 | 15.06 | 0.124584E+09 | 80.07 | 24-MAR-22:10 | 13.00 | 11.29 |
April | 0.123553E+10 | 642.74 | 30-APR-10:33 | 25.67 | 16.97 | 0.125880E+09 | 82.15 | 27-APR-22:10 | 25.67 | 16.97 |
May | 0.130803E+10 | 651.95 | 04-MAY-10:33 | 22.00 | 15.73 | 0.132374E+09 | 84.07 | 04-MAY-22:10 | 16.83 | 15.02 |
June | 0.134554E+10 | 675.65 | 25-JUN-10:33 | 23.00 | 17.26 | 0.133193E+09 | 85.59 | 30-JUN-22:10 | 16.13 | 16.03 |
July | 0.146210E+10 | 705.58 | 23-JUL-10:33 | 25.67 | 20.39 | 0.141072E+09 | 86.98 | 19-JUL-22:10 | 25.67 | 20.39 |
August | 0.146040E+10 | 699.80 | 19-AUG-10:33 | 24.67 | 20.11 | 0.141492E+09 | 86.93 | 18-AUG-22:10 | 24.67 | 20.11 |
September | 0.136178E+10 | 720.98 | 30-SEP-10:33 | 30.57 | 17.23 | 0.134021E+09 | 88.21 | 29-SEP-22:10 | 30.57 | 17.23 |
October | 0.141971E+10 | 719.17 | 16-OCT-10:33 | 36.33 | 17.49 | 0.139659E+09 | 89.50 | 16-OCT-22:10 | 20.17 | 11.06 |
November | 0.124044E+10 | 639.91 | 19-NOV-11:33 | 26.00 | 15.32 | 0.126426E+09 | 81.81 | 01-NOV-22:10 | 26.00 | 15.32 |
December | 0.125929E+10 | 673.32 | 03-DEC-01:00 | 5.00 | 5.00 | 0.126930E+09 | 81.98 | 05-DEC-23:10 | 17.33 | 9.21 |
Annual Sum or Average | 0.155712E+11 | 0.156471E+10 | ||||||||
Minimum of Months | 0.110105E+10 | 607.69 | 4.00 | 0.22 | 0.114092E+09 | 80.07 | 4.00 | 0.22 | ||
Maximum of Months | 0.146210E+10 | 723.67 | 36.33 | 20.39 | 0.141492E+09 | 89.50 | 30.57 | 20.39 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.507758E+11 | 37557.13 | 24-JAN-21:00 | 17.00 | 11.91 | 0.571364E+09 | 381.75 | 24-JAN-22:10 | 16.50 | 11.73 |
February | 0.457270E+11 | 37484.34 | 03-FEB-21:00 | 13.00 | 7.33 | 0.522783E+09 | 381.69 | 21-FEB-22:10 | 10.67 | 10.13 |
March | 0.507536E+11 | 37673.09 | 23-MAR-20:00 | 14.00 | 13.42 | 0.575077E+09 | 381.68 | 23-MAR-21:10 | 13.83 | 13.26 |
April | 0.497539E+11 | 37921.70 | 26-APR-20:00 | 17.00 | 15.07 | 0.563385E+09 | 381.71 | 05-APR-21:10 | 17.00 | 15.07 |
May | 0.515083E+11 | 37942.09 | 04-MAY-20:00 | 17.00 | 15.07 | 0.582819E+09 | 381.70 | 02-MAY-21:10 | 17.00 | 15.07 |
June | 0.504254E+11 | 37958.08 | 30-JUN-20:00 | 16.00 | 15.39 | 0.565594E+09 | 381.73 | 23-JUN-21:10 | 16.00 | 15.39 |
July | 0.524960E+11 | 38179.60 | 19-JUL-20:00 | 19.00 | 18.34 | 0.583978E+09 | 381.67 | 14-JUL-21:19 | 19.00 | 18.34 |
August | 0.527845E+11 | 38141.66 | 18-AUG-20:00 | 19.00 | 17.66 | 0.585450E+09 | 381.68 | 04-AUG-21:19 | 19.00 | 17.66 |
September | 0.503756E+11 | 38380.00 | 29-SEP-20:00 | 25.00 | 13.58 | 0.564926E+09 | 381.70 | 29-SEP-21:10 | 24.58 | 13.52 |
October | 0.520754E+11 | 38262.23 | 16-OCT-20:00 | 21.00 | 13.07 | 0.584693E+09 | 381.75 | 31-OCT-21:10 | 16.88 | 14.87 |
November | 0.494828E+11 | 37486.70 | 28-NOV-21:00 | 13.00 | 6.31 | 0.562570E+09 | 381.74 | 06-NOV-22:10 | 13.00 | 6.31 |
December | 0.507863E+11 | 37691.77 | 05-DEC-21:00 | 16.00 | 9.09 | 0.574311E+09 | 381.73 | 21-DEC-22:10 | 10.67 | 10.67 |
Annual Sum or Average | 0.606945E+12 | 0.683695E+10 | ||||||||
Minimum of Months | 0.457270E+11 | 37484.34 | 13.00 | 6.31 | 0.522783E+09 | 381.67 | 10.67 | 6.31 | ||
Maximum of Months | 0.527845E+11 | 38380.00 | 25.00 | 18.34 | 0.585450E+09 | 381.75 | 24.58 | 18.34 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.206944E+11 | 12721.45 | 14-JAN-12:40 | 25.33 | 11.70 | 0.101117E+11 | 6462.52 | 18-JAN-23:10 | 15.67 | 12.73 |
February | 0.174842E+11 | 10948.50 | 20-FEB-11:00 | 16.00 | 9.07 | 0.914832E+10 | 6462.02 | 02-FEB-00:20 | 16.00 | 9.07 |
March | 0.186764E+11 | 10509.78 | 11-MAR-12:50 | 24.00 | 13.82 | 0.986089E+10 | 6461.97 | 23-MAR-23:19 | 12.00 | 12.00 |
April | 0.184837E+11 | 9195.35 | 08-APR-10:33 | 21.67 | 16.37 | 0.984000E+10 | 6462.68 | 25-APR-21:30 | 14.50 | 13.91 |
May | 0.183035E+11 | 8849.59 | 04-MAY-21:20 | 17.00 | 15.07 | 0.996253E+10 | 6462.64 | 03-MAY-22:10 | 17.00 | 15.07 |
June | 0.182546E+11 | 8628.66 | 25-JUN-10:33 | 23.00 | 17.26 | 0.983734E+10 | 6462.74 | 19-JUN-22:10 | 23.00 | 17.26 |
July | 0.197416E+11 | 9217.26 | 30-JUL-10:33 | 24.67 | 20.10 | 0.103204E+11 | 6462.75 | 07-JUL-21:30 | 24.67 | 20.10 |
August | 0.205305E+11 | 9554.66 | 27-AUG-10:33 | 23.33 | 18.72 | 0.105634E+11 | 6462.72 | 01-AUG-22:10 | 23.33 | 18.72 |
September | 0.201059E+11 | 12058.51 | 30-SEP-12:00 | 32.00 | 17.11 | 0.102348E+11 | 6462.61 | 12-SEP-22:10 | 32.00 | 17.11 |
October | 0.219136E+11 | 13677.65 | 15-OCT-12:00 | 32.00 | 16.89 | 0.106311E+11 | 6462.63 | 16-OCT-22:10 | 20.17 | 11.06 |
November | 0.201227E+11 | 14055.17 | 19-NOV-11:00 | 26.00 | 15.07 | 0.100863E+11 | 6462.38 | 10-NOV-22:30 | 26.00 | 15.07 |
December | 0.211996E+11 | 12574.26 | 16-DEC-13:00 | 26.00 | 13.31 | 0.102608E+11 | 6462.67 | 01-DEC-00:00 | 26.00 | 13.31 |
Annual Sum or Average | 0.235511E+12 | 0.120857E+12 | ||||||||
Minimum of Months | 0.174842E+11 | 8628.66 | 16.00 | 9.07 | 0.914832E+10 | 6461.97 | 12.00 | 9.07 | ||
Maximum of Months | 0.219136E+11 | 14055.17 | 32.00 | 20.10 | 0.106311E+11 | 6462.75 | 32.00 | 20.10 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.674593E+11 | 37648.63 | 09-JAN-05:55 | 2.00 | -0.2 | 0.302088E+11 | 19185.87 | 18-JAN-23:10 | 15.67 | 12.73 |
February | 0.589207E+11 | 33715.83 | 04-FEB-05:55 | 5.00 | 0.22 | 0.275890E+11 | 19185.32 | 02-FEB-00:20 | 5.00 | 0.22 |
March | 0.646625E+11 | 33763.26 | 08-MAR-02:00 | 4.00 | 3.53 | 0.299287E+11 | 19185.16 | 23-MAR-23:19 | 12.00 | 12.00 |
April | 0.637598E+11 | 31533.75 | 26-APR-21:52 | 16.00 | 15.39 | 0.297638E+11 | 19186.10 | 26-APR-22:10 | 16.00 | 15.29 |
May | 0.652371E+11 | 32428.36 | 04-MAY-21:53 | 17.00 | 15.07 | 0.306690E+11 | 19186.00 | 04-MAY-22:10 | 16.83 | 15.02 |
June | 0.651560E+11 | 32339.04 | 30-JUN-21:52 | 16.10 | 16.10 | 0.301529E+11 | 19186.22 | 19-JUN-22:10 | 16.10 | 16.10 |
July | 0.697984E+11 | 33679.59 | 19-JUL-21:52 | 18.00 | 17.35 | 0.313874E+11 | 19186.17 | 21-JUL-22:10 | 17.00 | 15.73 |
August | 0.711249E+11 | 34316.62 | 18-AUG-21:10 | 19.00 | 17.66 | 0.317324E+11 | 19186.17 | 10-AUG-22:10 | 19.00 | 17.66 |
September | 0.682054E+11 | 38050.84 | 29-SEP-21:10 | 24.58 | 13.52 | 0.306186E+11 | 19186.01 | 13-SEP-22:10 | 24.58 | 13.52 |
October | 0.719018E+11 | 38779.30 | 16-OCT-21:10 | 18.33 | 11.06 | 0.317764E+11 | 19186.08 | 18-OCT-21:30 | 14.50 | 14.21 |
November | 0.657188E+11 | 33022.84 | 20-NOV-22:10 | 14.00 | 12.84 | 0.302187E+11 | 19185.68 | 10-NOV-22:30 | 14.00 | 12.84 |
December | 0.680138E+11 | 34111.01 | 05-DEC-22:10 | 17.17 | 9.45 | 0.307232E+11 | 19187.91 | 01-DEC-01:10 | 17.17 | 9.45 |
Annual Sum or Average | 0.799959E+12 | 0.364769E+12 | ||||||||
Minimum of Months | 0.589207E+11 | 31533.75 | 2.00 | -0.2 | 0.275890E+11 | 19185.16 | 5.00 | 0.22 | ||
Maximum of Months | 0.719018E+11 | 38779.30 | 24.58 | 17.66 | 0.317764E+11 | 19187.91 | 24.58 | 17.66 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.646413E+09 | 3272.60 | 14-JAN-16:01 | 23.00 | 12.42 | 98078426.74 | 56.69 | 20-JAN-23:10 | 13.83 | 13.83 |
February | 0.572346E+09 | 3284.55 | 03-FEB-16:01 | 20.50 | 10.05 | 88309482.39 | 56.69 | 14-FEB-22:10 | 13.00 | 12.44 |
March | 0.597901E+09 | 2881.82 | 05-MAR-16:01 | 14.67 | 11.36 | 97804519.11 | 56.69 | 23-MAR-23:10 | 12.00 | 12.00 |
April | 0.106876E+10 | 3051.25 | 01-APR-18:02 | 17.83 | 8.84 | 95349529.13 | 56.69 | 27-APR-21:10 | 14.00 | 12.84 |
May | 0.102426E+10 | 2995.73 | 24-MAY-08:62 | 18.00 | 8.80 | 98498660.77 | 56.69 | 03-MAY-21:19 | 18.00 | 8.80 |
June | 0.130628E+10 | 2969.15 | 28-JUN-18:01 | 18.67 | 16.49 | 95553544.38 | 56.70 | 30-JUN-21:40 | 16.07 | 15.66 |
July | 0.172840E+10 | 2977.48 | 27-JUL-18:01 | 20.67 | 17.73 | 98881915.11 | 56.70 | 26-JUL-21:49 | 20.67 | 17.73 |
August | 0.177263E+10 | 2961.18 | 17-AUG-18:02 | 20.77 | 18.28 | 99001095.32 | 56.69 | 02-AUG-21:00 | 20.77 | 18.28 |
September | 0.146929E+10 | 2920.29 | 24-SEP-15:01 | 18.83 | 17.02 | 95607089.61 | 56.69 | 24-SEP-23:49 | 17.00 | 16.37 |
October | 0.145192E+10 | 3317.95 | 14-OCT-08:61 | 27.67 | 13.01 | 98706513.28 | 56.69 | 17-OCT-22:40 | 16.67 | 12.78 |
November | 0.822565E+09 | 3245.74 | 27-NOV-16:01 | 19.67 | 7.55 | 95209454.84 | 56.69 | 10-NOV-23:19 | 19.67 | 7.55 |
December | 0.731815E+09 | 3283.86 | 19-DEC-16:01 | 20.67 | 8.11 | 98179659.47 | 56.69 | 07-DEC-22:40 | 20.67 | 8.11 |
Annual Sum or Average | 0.131926E+11 | 0.115918E+10 | ||||||||
Minimum of Months | 0.572346E+09 | 2881.82 | 14.67 | 7.55 | 88309482.39 | 56.69 | 12.00 | 7.55 | ||
Maximum of Months | 0.177263E+10 | 3317.95 | 27.67 | 18.28 | 99001095.32 | 56.70 | 20.77 | 18.28 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.237544E+09 | 3136.29 | 15-JAN-16:01 | 21.83 | 10.39 | 97557230.90 | 64.99 | 18-JAN-22:40 | 16.33 | 13.19 |
February | 0.270341E+09 | 3145.55 | 03-FEB-16:01 | 20.50 | 10.05 | 88010108.37 | 56.69 | 01-FEB-22:10 | 20.50 | 10.05 |
March | 0.337619E+09 | 2849.82 | 24-MAR-15:01 | 18.00 | 15.36 | 98104676.97 | 57.64 | 22-MAR-18:10 | 18.00 | 15.36 |
April | 0.705468E+09 | 3120.74 | 19-APR-18:01 | 14.00 | 12.24 | 98778775.68 | 75.26 | 26-APR-21:49 | 16.00 | 15.39 |
May | 0.781233E+09 | 3048.38 | 24-MAY-08:51 | 18.00 | 9.64 | 0.103049E+09 | 75.54 | 03-MAY-21:40 | 18.00 | 9.64 |
June | 0.937144E+09 | 2898.64 | 22-JUN-20:11 | 15.00 | 13.18 | 0.105489E+09 | 79.26 | 30-JUN-18:10 | 18.83 | 16.43 |
July | 0.123602E+10 | 2806.27 | 09-JUL-21:51 | 17.00 | 14.51 | 0.112134E+09 | 79.28 | 07-JUL-21:10 | 17.00 | 14.51 |
August | 0.117363E+10 | 2783.67 | 05-AUG-15:01 | 22.67 | 18.32 | 0.111235E+09 | 78.25 | 09-AUG-21:40 | 18.00 | 17.36 |
September | 0.917562E+09 | 2859.97 | 18-SEP-15:01 | 19.83 | 15.05 | 0.102389E+09 | 74.12 | 13-SEP-21:40 | 19.83 | 15.05 |
October | 0.832438E+09 | 3318.62 | 14-OCT-08:61 | 27.67 | 13.01 | 0.104214E+09 | 75.48 | 16-OCT-21:40 | 19.33 | 11.10 |
November | 0.364814E+09 | 3110.18 | 27-NOV-16:01 | 19.67 | 7.55 | 95283408.28 | 66.64 | 10-NOV-22:10 | 19.67 | 7.55 |
December | 0.255575E+09 | 3145.30 | 19-DEC-16:01 | 20.67 | 8.11 | 97677375.15 | 65.54 | 05-DEC-22:40 | 20.67 | 8.11 |
Annual Sum or Average | 0.804938E+10 | 0.121392E+10 | ||||||||
Minimum of Months | 0.237544E+09 | 2783.67 | 14.00 | 7.55 | 88010108.37 | 56.69 | 16.00 | 7.55 | ||
Maximum of Months | 0.123602E+10 | 3318.62 | 27.67 | 18.32 | 0.112134E+09 | 79.28 | 20.67 | 17.36 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.454813E+09 | 576.52 | 14-JAN-12:40 | 25.33 | 11.70 | 0.00 | 0.00 | 01-JAN-00:10 | 25.33 | 11.70 |
February | 0.295019E+09 | 506.55 | 02-FEB-12:30 | 19.50 | 11.91 | 0.00 | 0.00 | 01-FEB-00:10 | 19.50 | 11.91 |
March | 0.226104E+09 | 429.68 | 11-MAR-13:10 | 24.00 | 13.64 | 0.00 | 0.00 | 01-MAR-00:10 | 24.00 | 13.64 |
April | 0.252643E+09 | 302.19 | 08-APR-12:50 | 22.17 | 16.56 | 0.00 | 0.00 | 01-APR-00:10 | 22.17 | 16.56 |
May | 0.161547E+09 | 256.16 | 03-MAY-15:03 | 21.83 | 15.33 | 0.00 | 0.00 | 01-MAY-00:10 | 21.83 | 15.33 |
June | 0.202146E+09 | 222.64 | 30-JUN-15:06 | 22.95 | 17.86 | 0.00 | 0.00 | 01-JUN-00:10 | 22.95 | 17.86 |
July | 0.295540E+09 | 265.41 | 19-JUL-15:03 | 26.67 | 20.20 | 0.00 | 0.00 | 01-JUL-00:10 | 26.67 | 20.20 |
August | 0.386626E+09 | 286.55 | 30-AUG-13:00 | 24.00 | 18.12 | 0.00 | 0.00 | 01-AUG-00:10 | 24.00 | 18.12 |
September | 0.432429E+09 | 533.06 | 30-SEP-13:05 | 32.00 | 16.98 | 0.00 | 0.00 | 01-SEP-00:10 | 32.00 | 16.98 |
October | 0.552652E+09 | 641.98 | 16-OCT-12:20 | 35.37 | 17.35 | 0.00 | 0.00 | 01-OCT-00:10 | 35.37 | 17.35 |
November | 0.460905E+09 | 609.24 | 19-NOV-09:58 | 26.00 | 13.89 | 0.00 | 0.00 | 01-NOV-00:10 | 26.00 | 13.89 |
December | 0.507920E+09 | 588.24 | 19-DEC-13:00 | 26.00 | 11.60 | 0.00 | 0.00 | 01-DEC-00:10 | 26.00 | 11.60 |
Annual Sum or Average | 0.422834E+10 | 0.00 | ||||||||
Minimum of Months | 0.161547E+09 | 222.64 | 19.50 | 11.60 | 0.00 | 0.00 | 19.50 | 11.60 | ||
Maximum of Months | 0.552652E+09 | 641.98 | 35.37 | 20.20 | 0.00 | 0.00 | 35.37 | 20.20 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.273544E+09 | 1093.77 | 15-JAN-16:01 | 21.83 | 10.39 | 97513967.47 | 69.04 | 18-JAN-22:00 | 16.00 | 13.03 |
February | 0.279405E+09 | 1060.00 | 03-FEB-16:01 | 20.50 | 10.05 | 87778747.49 | 58.62 | 13-FEB-21:19 | 14.67 | 14.08 |
March | 0.321117E+09 | 973.56 | 04-MAR-09:01 | 14.00 | 12.23 | 97460101.69 | 57.30 | 30-MAR-23:10 | 8.00 | 6.97 |
April | 0.397008E+09 | 1050.39 | 02-APR-08:51 | 19.00 | 9.47 | 95739379.29 | 71.65 | 25-APR-21:10 | 14.83 | 14.24 |
May | 0.455758E+09 | 1055.46 | 24-MAY-08:51 | 18.00 | 9.64 | 99932383.92 | 72.10 | 04-MAY-21:00 | 18.00 | 9.64 |
June | 0.482380E+09 | 1025.16 | 22-JUN-20:11 | 15.00 | 13.18 | 0.100319E+09 | 74.73 | 30-JUN-21:00 | 16.10 | 16.10 |
July | 0.555836E+09 | 1038.95 | 04-JUL-08:51 | 22.00 | 15.83 | 0.105886E+09 | 76.09 | 07-JUL-21:10 | 15.17 | 13.86 |
August | 0.523107E+09 | 1006.39 | 22-AUG-15:01 | 20.83 | 15.93 | 0.105396E+09 | 74.09 | 07-AUG-21:00 | 20.83 | 15.93 |
September | 0.442949E+09 | 1007.96 | 01-SEP-15:01 | 20.67 | 15.86 | 98907749.15 | 71.87 | 22-SEP-21:00 | 17.00 | 16.37 |
October | 0.451291E+09 | 1174.61 | 14-OCT-08:61 | 27.67 | 13.01 | 0.102177E+09 | 74.34 | 04-OCT-21:30 | 27.67 | 13.01 |
November | 0.309758E+09 | 1080.05 | 19-NOV-09:41 | 25.67 | 13.67 | 94446866.53 | 68.62 | 10-NOV-22:10 | 25.67 | 13.67 |
December | 0.274947E+09 | 1089.33 | 05-DEC-16:01 | 22.67 | 12.42 | 97274320.44 | 69.07 | 06-DEC-22:10 | 14.50 | 9.28 |
Annual Sum or Average | 0.476710E+10 | 0.118283E+10 | ||||||||
Minimum of Months | 0.273544E+09 | 973.56 | 14.00 | 9.47 | 87778747.49 | 57.30 | 8.00 | 6.97 | ||
Maximum of Months | 0.555836E+09 | 1174.61 | 27.67 | 15.93 | 0.105886E+09 | 76.09 | 27.67 | 16.37 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.675210E+09 | 2934.84 | 14-JAN-16:01 | 23.00 | 12.42 | 98367448.45 | 56.69 | 20-JAN-23:19 | 13.67 | 13.67 |
February | 0.537357E+09 | 2930.11 | 03-FEB-16:01 | 20.50 | 10.05 | 88398294.37 | 56.69 | 17-FEB-22:10 | 13.67 | 12.71 |
March | 0.586536E+09 | 2599.48 | 24-MAR-15:01 | 18.00 | 15.36 | 97990910.33 | 56.69 | 23-MAR-22:49 | 18.00 | 15.36 |
April | 0.979101E+09 | 2896.14 | 02-APR-08:62 | 17.33 | 8.66 | 95480633.88 | 56.69 | 27-APR-01:00 | 16.00 | 15.39 |
May | 0.898461E+09 | 2904.35 | 24-MAY-08:62 | 18.00 | 8.80 | 98582775.30 | 56.69 | 03-MAY-00:00 | 18.00 | 8.80 |
June | 0.112855E+10 | 2675.65 | 26-JUN-15:01 | 22.00 | 17.98 | 95596961.87 | 56.69 | 16-JUN-21:00 | 22.00 | 17.98 |
July | 0.158023E+10 | 2720.74 | 19-JUL-08:61 | 22.67 | 18.97 | 99033703.92 | 56.69 | 28-JUL-21:19 | 18.00 | 17.35 |
August | 0.168479E+10 | 2725.10 | 14-AUG-08:61 | 23.33 | 19.67 | 99142509.54 | 56.69 | 09-AUG-21:10 | 23.33 | 19.67 |
September | 0.128935E+10 | 2651.35 | 04-SEP-15:01 | 20.83 | 16.01 | 95529778.95 | 56.69 | 30-SEP-23:30 | 18.30 | 17.65 |
October | 0.138936E+10 | 3026.42 | 14-OCT-08:61 | 27.67 | 13.01 | 98769580.50 | 56.69 | 18-OCT-21:19 | 14.67 | 14.28 |
November | 0.773081E+09 | 2952.51 | 27-NOV-09:01 | 21.17 | 8.41 | 95336920.42 | 56.69 | 10-NOV-22:49 | 21.17 | 8.41 |
December | 0.730582E+09 | 2972.27 | 05-DEC-09:01 | 24.33 | 12.02 | 98395945.11 | 56.69 | 07-DEC-22:49 | 12.13 | 12.12 |
Annual Sum or Average | 0.122526E+11 | 0.116063E+10 | ||||||||
Minimum of Months | 0.537357E+09 | 2599.48 | 17.33 | 8.41 | 88398294.37 | 56.69 | 12.13 | 8.41 | ||
Maximum of Months | 0.168479E+10 | 3026.42 | 27.67 | 19.67 | 99142509.54 | 56.69 | 23.33 | 19.67 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.272845E+09 | 2798.62 | 14-JAN-16:01 | 23.00 | 12.42 | 97640604.55 | 64.10 | 24-JAN-22:40 | 15.00 | 11.13 |
February | 0.259120E+09 | 2863.66 | 03-FEB-09:51 | 21.00 | 8.28 | 87801579.12 | 56.69 | 17-FEB-22:19 | 13.33 | 12.58 |
March | 0.346560E+09 | 2767.83 | 23-MAR-08:51 | 19.00 | 14.76 | 97910969.74 | 56.69 | 23-MAR-22:19 | 12.67 | 12.30 |
April | 0.678736E+09 | 3108.15 | 02-APR-08:51 | 19.00 | 9.47 | 97418692.34 | 71.19 | 26-APR-21:49 | 16.00 | 15.39 |
May | 0.718395E+09 | 3191.52 | 24-MAY-08:51 | 18.00 | 9.64 | 0.101514E+09 | 72.41 | 04-MAY-21:40 | 18.00 | 9.64 |
June | 0.860008E+09 | 2986.79 | 23-JUN-08:51 | 21.00 | 15.42 | 0.101989E+09 | 73.23 | 30-JUN-21:49 | 16.08 | 15.88 |
July | 0.116818E+10 | 2957.70 | 04-JUL-08:51 | 22.00 | 15.83 | 0.108616E+09 | 75.05 | 19-JUL-21:49 | 18.00 | 17.46 |
August | 0.114698E+10 | 2885.16 | 22-AUG-08:51 | 19.00 | 14.76 | 0.108455E+09 | 74.82 | 18-AUG-21:30 | 19.00 | 14.76 |
September | 0.807890E+09 | 2912.60 | 12-SEP-08:51 | 21.00 | 15.98 | 0.100371E+09 | 70.75 | 13-SEP-21:40 | 17.00 | 16.37 |
October | 0.794544E+09 | 3389.84 | 17-OCT-08:21 | 27.50 | 13.36 | 0.103426E+09 | 73.79 | 16-OCT-21:40 | 27.50 | 13.36 |
November | 0.348482E+09 | 2825.52 | 28-NOV-09:51 | 21.00 | 8.49 | 94943222.44 | 63.37 | 10-NOV-22:10 | 21.00 | 8.49 |
December | 0.268435E+09 | 3049.44 | 05-DEC-09:41 | 25.67 | 12.88 | 97704138.42 | 65.45 | 05-DEC-22:40 | 17.67 | 9.41 |
Annual Sum or Average | 0.767018E+10 | 0.119779E+10 | ||||||||
Minimum of Months | 0.259120E+09 | 2767.83 | 18.00 | 8.28 | 87801579.12 | 56.69 | 12.67 | 8.49 | ||
Maximum of Months | 0.116818E+10 | 3389.84 | 27.50 | 15.98 | 0.108616E+09 | 75.05 | 27.50 | 17.46 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.424356E+10 | 2596.68 | 28-JAN-07:00 | 3.00 | 2.55 | 0.129828E+10 | 829.93 | 20-JAN-23:10 | 3.00 | 2.55 |
February | 0.374851E+10 | 2317.31 | 04-FEB-05:55 | 5.00 | 0.22 | 0.118412E+10 | 827.83 | 03-FEB-23:10 | 5.00 | 0.22 |
March | 0.408207E+10 | 2255.54 | 08-MAR-01:30 | 4.50 | 3.81 | 0.128941E+10 | 825.18 | 24-MAR-21:49 | 13.00 | 11.39 |
April | 0.417921E+10 | 2161.93 | 30-APR-10:33 | 25.67 | 16.97 | 0.130062E+10 | 838.54 | 27-APR-21:49 | 25.67 | 16.97 |
May | 0.435470E+10 | 2168.59 | 04-MAY-10:33 | 22.00 | 15.73 | 0.135459E+10 | 857.94 | 04-MAY-22:10 | 16.83 | 15.02 |
June | 0.442937E+10 | 2231.77 | 25-JUN-10:33 | 23.00 | 17.26 | 0.135192E+10 | 871.17 | 30-JUN-22:10 | 16.13 | 16.03 |
July | 0.484589E+10 | 2325.59 | 23-JUL-10:33 | 25.67 | 20.39 | 0.143801E+10 | 882.44 | 28-JUL-22:10 | 18.00 | 17.35 |
August | 0.490837E+10 | 2343.00 | 19-AUG-10:33 | 24.67 | 20.11 | 0.145721E+10 | 891.79 | 18-AUG-22:10 | 24.67 | 20.11 |
September | 0.456943E+10 | 2397.46 | 30-SEP-10:33 | 30.57 | 17.23 | 0.137797E+10 | 894.04 | 29-SEP-22:10 | 30.57 | 17.23 |
October | 0.478766E+10 | 2413.39 | 17-OCT-10:33 | 31.00 | 16.57 | 0.144044E+10 | 917.97 | 17-OCT-21:49 | 18.00 | 14.47 |
November | 0.422028E+10 | 2173.64 | 19-NOV-11:33 | 26.00 | 15.32 | 0.131112E+10 | 856.61 | 01-NOV-00:10 | 26.00 | 15.32 |
December | 0.435370E+10 | 2304.75 | 03-DEC-01:00 | 5.00 | 5.00 | 0.132677E+10 | 841.34 | 05-DEC-23:10 | 17.33 | 9.21 |
Annual Sum or Average | 0.527227E+11 | 0.161305E+11 | ||||||||
Minimum of Months | 0.374851E+10 | 2161.93 | 3.00 | 0.22 | 0.118412E+10 | 825.18 | 3.00 | 0.22 | ||
Maximum of Months | 0.490837E+10 | 2596.68 | 31.00 | 20.39 | 0.145721E+10 | 917.97 | 30.57 | 20.11 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.533632E+09 | 3387.17 | 14-JAN-16:01 | 23.00 | 12.42 | 97809750.23 | 56.69 | 05-JAN-22:00 | 23.00 | 12.42 |
February | 0.465590E+09 | 3393.45 | 03-FEB-16:01 | 20.50 | 10.05 | 88029638.77 | 56.69 | 21-FEB-00:20 | 10.33 | 8.38 |
March | 0.527450E+09 | 3008.17 | 05-MAR-16:01 | 14.67 | 11.36 | 97581772.66 | 56.69 | 23-MAR-21:00 | 13.00 | 12.44 |
April | 0.101641E+10 | 3177.96 | 01-APR-18:02 | 17.83 | 8.84 | 95275088.51 | 56.70 | 07-APR-02:39 | 13.00 | 11.87 |
May | 0.958281E+09 | 3064.29 | 24-MAY-08:62 | 18.00 | 8.80 | 98424975.32 | 56.69 | 29-MAY-04:40 | 13.00 | 11.68 |
June | 0.128355E+10 | 3060.42 | 28-JUN-18:01 | 18.67 | 16.49 | 95506879.14 | 56.70 | 17-JUN-04:30 | 18.67 | 16.49 |
July | 0.174204E+10 | 3072.92 | 27-JUL-18:01 | 20.67 | 17.73 | 98851378.05 | 56.69 | 31-JUL-21:19 | 18.90 | 17.79 |
August | 0.176314E+10 | 3044.75 | 14-AUG-18:02 | 21.83 | 18.58 | 98952852.88 | 56.70 | 17-AUG-21:19 | 19.00 | 17.66 |
September | 0.139957E+10 | 2997.62 | 04-SEP-18:01 | 16.83 | 14.45 | 95530820.87 | 56.70 | 03-SEP-03:09 | 16.83 | 14.45 |
October | 0.132344E+10 | 3427.03 | 26-OCT-15:01 | 22.67 | 12.63 | 98576973.44 | 56.70 | 17-OCT-21:40 | 22.67 | 12.63 |
November | 0.669668E+09 | 3350.65 | 30-NOV-16:01 | 17.83 | 11.31 | 94964536.52 | 56.69 | 02-NOV-21:49 | 17.83 | 11.31 |
December | 0.595385E+09 | 3397.19 | 19-DEC-16:01 | 20.67 | 8.11 | 97876085.79 | 56.69 | 07-DEC-22:30 | 20.67 | 8.11 |
Annual Sum or Average | 0.122782E+11 | 0.115738E+10 | ||||||||
Minimum of Months | 0.465590E+09 | 2997.62 | 14.67 | 8.11 | 88029638.77 | 56.69 | 10.33 | 8.11 | ||
Maximum of Months | 0.176314E+10 | 3427.03 | 23.00 | 18.58 | 98952852.88 | 56.70 | 23.00 | 17.79 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.153878E+09 | 3231.94 | 15-JAN-16:01 | 21.83 | 10.39 | 97025150.16 | 63.30 | 18-JAN-22:30 | 16.50 | 13.26 |
February | 0.183171E+09 | 3237.06 | 03-FEB-16:01 | 20.50 | 10.05 | 87623581.93 | 56.69 | 02-FEB-00:20 | 20.50 | 10.05 |
March | 0.266672E+09 | 3016.92 | 19-MAR-18:11 | 13.67 | 12.71 | 97983151.60 | 60.18 | 22-MAR-18:10 | 15.50 | 14.39 |
April | 0.647286E+09 | 3319.00 | 23-APR-18:11 | 14.67 | 13.07 | 99323795.03 | 78.91 | 26-APR-18:10 | 18.67 | 15.37 |
May | 0.730968E+09 | 3200.97 | 19-MAY-18:51 | 13.00 | 11.87 | 0.103605E+09 | 77.49 | 03-MAY-21:40 | 13.00 | 11.87 |
June | 0.962111E+09 | 3079.60 | 04-JUN-19:31 | 15.00 | 13.18 | 0.106964E+09 | 84.19 | 30-JUN-18:10 | 18.83 | 16.43 |
July | 0.131783E+10 | 2955.52 | 08-JUL-21:11 | 15.00 | 13.80 | 0.113882E+09 | 83.15 | 25-JUL-18:10 | 20.67 | 18.14 |
August | 0.122149E+10 | 2863.12 | 21-AUG-20:11 | 15.00 | 13.80 | 0.112532E+09 | 81.43 | 03-AUG-18:10 | 15.00 | 13.80 |
September | 0.876043E+09 | 2938.83 | 18-SEP-15:01 | 19.83 | 15.05 | 0.102582E+09 | 74.66 | 13-SEP-21:40 | 19.83 | 15.05 |
October | 0.734300E+09 | 3327.92 | 14-OCT-08:61 | 27.67 | 13.01 | 0.103696E+09 | 74.86 | 16-OCT-21:40 | 19.33 | 11.10 |
November | 0.236236E+09 | 3197.71 | 27-NOV-16:01 | 19.67 | 7.55 | 94755635.41 | 64.26 | 10-NOV-22:10 | 19.67 | 7.55 |
December | 0.158525E+09 | 3240.45 | 19-DEC-16:01 | 20.67 | 8.11 | 97023985.32 | 63.51 | 05-DEC-22:40 | 20.67 | 8.11 |
Annual Sum or Average | 0.748851E+10 | 0.121700E+10 | ||||||||
Minimum of Months | 0.153878E+09 | 2863.12 | 13.00 | 7.55 | 87623581.93 | 56.69 | 13.00 | 7.55 | ||
Maximum of Months | 0.131783E+10 | 3327.92 | 27.67 | 15.05 | 0.113882E+09 | 84.19 | 20.67 | 18.14 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.908432E+09 | 1820.47 | 04-JAN-16:01 | 17.67 | 9.41 | 98763466.01 | 57.39 | 12-JAN-04:49 | 8.00 | 8.00 |
February | 0.624954E+09 | 1841.27 | 03-FEB-16:01 | 20.50 | 10.05 | 88787675.76 | 57.32 | 22-FEB-03:00 | 9.00 | 7.42 |
March | 0.545025E+09 | 1611.92 | 24-MAR-18:01 | 13.00 | 11.87 | 98168269.85 | 57.40 | 02-MAR-01:00 | 13.00 | 11.87 |
April | 0.632726E+09 | 1728.66 | 01-APR-18:02 | 17.83 | 8.84 | 95289884.03 | 56.69 | 11-APR-21:10 | 13.83 | 13.83 |
May | 0.458429E+09 | 1638.74 | 24-MAY-08:62 | 18.00 | 8.80 | 98138609.10 | 56.69 | 25-MAY-22:10 | 15.00 | 13.80 |
June | 0.543410E+09 | 1629.28 | 30-JUN-15:01 | 22.95 | 17.86 | 95182258.15 | 56.69 | 30-JUN-23:49 | 16.38 | 15.77 |
July | 0.757712E+09 | 1659.73 | 15-JUL-15:01 | 21.83 | 18.03 | 98689708.16 | 56.69 | 31-JUL-21:10 | 18.95 | 17.72 |
August | 0.916260E+09 | 1640.88 | 02-AUG-15:01 | 22.83 | 18.38 | 98888387.60 | 56.69 | 21-AUG-21:10 | 15.17 | 13.86 |
September | 0.929876E+09 | 1641.45 | 21-SEP-15:02 | 27.67 | 19.86 | 95446450.32 | 56.69 | 06-SEP-21:30 | 27.67 | 19.86 |
October | 0.113498E+10 | 1856.17 | 14-OCT-08:61 | 27.67 | 13.01 | 98771321.46 | 56.69 | 10-OCT-21:49 | 27.67 | 13.01 |
November | 0.912763E+09 | 1827.23 | 27-NOV-09:01 | 21.17 | 8.41 | 95659596.93 | 57.41 | 06-NOV-03:30 | 21.17 | 8.41 |
December | 0.985510E+09 | 1851.23 | 29-DEC-16:01 | 21.17 | 10.21 | 98815914.91 | 57.40 | 15-DEC-02:09 | 21.17 | 10.21 |
Annual Sum or Average | 0.935008E+10 | 0.116060E+10 | ||||||||
Minimum of Months | 0.458429E+09 | 1611.92 | 13.00 | 8.41 | 88787675.76 | 56.69 | 8.00 | 7.42 | ||
Maximum of Months | 0.113498E+10 | 1856.17 | 27.67 | 19.86 | 98888387.60 | 57.41 | 27.67 | 19.86 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.355712E+11 | 19647.80 | 18-JAN-22:10 | 16.83 | 13.41 | 0.188185E+11 | 11348.62 | 18-JAN-23:10 | 15.67 | 12.73 |
February | 0.321441E+11 | 19111.67 | 01-FEB-23:00 | 13.00 | 11.29 | 0.172122E+11 | 11347.79 | 08-FEB-00:20 | 12.67 | 6.27 |
March | 0.359872E+11 | 19465.74 | 24-MAR-22:00 | 13.00 | 11.29 | 0.190364E+11 | 11347.72 | 13-MAR-23:19 | 13.00 | 11.29 |
April | 0.364236E+11 | 20358.60 | 26-APR-21:52 | 16.00 | 15.39 | 0.185876E+11 | 11348.97 | 26-APR-22:10 | 16.00 | 15.29 |
May | 0.381436E+11 | 20743.09 | 04-MAY-21:53 | 17.00 | 15.07 | 0.192356E+11 | 11348.92 | 03-MAY-22:10 | 17.00 | 15.07 |
June | 0.385394E+11 | 20975.44 | 27-JUN-21:52 | 17.00 | 16.37 | 0.186854E+11 | 11349.13 | 19-JUN-22:10 | 17.00 | 16.37 |
July | 0.408888E+11 | 21159.84 | 19-JUL-21:52 | 18.00 | 17.35 | 0.192556E+11 | 11349.09 | 05-JUL-22:10 | 18.00 | 17.35 |
August | 0.407672E+11 | 21020.01 | 18-AUG-21:52 | 19.00 | 17.66 | 0.193272E+11 | 11349.09 | 01-AUG-22:10 | 19.00 | 17.66 |
September | 0.380449E+11 | 21449.45 | 29-SEP-21:10 | 24.58 | 13.52 | 0.186218E+11 | 11348.82 | 12-SEP-22:10 | 24.58 | 13.52 |
October | 0.389751E+11 | 21198.14 | 16-OCT-21:52 | 20.00 | 11.09 | 0.192112E+11 | 11348.91 | 16-OCT-22:10 | 20.17 | 11.06 |
November | 0.349167E+11 | 19323.51 | 10-NOV-23:00 | 15.00 | 13.80 | 0.184636E+11 | 11348.33 | 10-NOV-22:30 | 15.00 | 13.80 |
December | 0.354964E+11 | 19757.85 | 05-DEC-22:54 | 18.00 | 9.37 | 0.189405E+11 | 11348.89 | 01-DEC-00:49 | 18.00 | 9.37 |
Annual Sum or Average | 0.445898E+12 | 0.225396E+12 | ||||||||
Minimum of Months | 0.321441E+11 | 19111.67 | 13.00 | 9.37 | 0.172122E+11 | 11347.72 | 12.67 | 6.27 | ||
Maximum of Months | 0.408888E+11 | 21449.45 | 24.58 | 17.66 | 0.193272E+11 | 11349.13 | 24.58 | 17.66 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.389576E+11 | 21302.18 | 18-JAN-22:10 | 16.83 | 13.41 | 0.189853E+11 | 11348.63 | 18-JAN-23:10 | 15.67 | 12.73 |
February | 0.353262E+11 | 20804.15 | 01-FEB-22:10 | 13.00 | 11.77 | 0.173332E+11 | 11347.81 | 08-FEB-00:20 | 12.67 | 6.27 |
March | 0.395304E+11 | 21050.45 | 24-MAR-21:10 | 13.00 | 11.77 | 0.191925E+11 | 11347.73 | 13-MAR-23:19 | 13.00 | 11.77 |
April | 0.398389E+11 | 21881.63 | 26-APR-21:52 | 16.00 | 15.39 | 0.186615E+11 | 11348.97 | 26-APR-22:10 | 16.00 | 15.29 |
May | 0.417096E+11 | 22189.92 | 04-MAY-21:10 | 17.00 | 15.07 | 0.193012E+11 | 11348.93 | 03-MAY-22:10 | 17.00 | 15.07 |
June | 0.418763E+11 | 22393.34 | 27-JUN-21:52 | 17.00 | 16.37 | 0.187283E+11 | 11349.13 | 19-JUN-22:10 | 17.00 | 16.37 |
July | 0.441565E+11 | 22546.55 | 19-JUL-21:52 | 18.00 | 17.35 | 0.192873E+11 | 11349.09 | 05-JUL-22:10 | 18.00 | 17.35 |
August | 0.439404E+11 | 22361.93 | 18-AUG-21:52 | 19.00 | 17.66 | 0.193613E+11 | 11349.09 | 01-AUG-22:10 | 19.00 | 17.66 |
September | 0.412090E+11 | 22812.48 | 29-SEP-21:10 | 24.58 | 13.52 | 0.186675E+11 | 11348.83 | 12-SEP-22:10 | 24.58 | 13.52 |
October | 0.421477E+11 | 22581.11 | 04-OCT-21:53 | 21.00 | 18.98 | 0.192633E+11 | 11348.91 | 16-OCT-22:10 | 20.17 | 11.06 |
November | 0.382016E+11 | 20999.41 | 10-NOV-22:14 | 15.00 | 13.80 | 0.185687E+11 | 11348.35 | 10-NOV-22:30 | 15.00 | 13.80 |
December | 0.388701E+11 | 21335.55 | 05-DEC-22:54 | 18.00 | 9.37 | 0.190898E+11 | 11349.14 | 01-DEC-00:49 | 18.00 | 9.37 |
Annual Sum or Average | 0.485764E+12 | 0.226440E+12 | ||||||||
Minimum of Months | 0.353262E+11 | 20804.15 | 13.00 | 9.37 | 0.173332E+11 | 11347.73 | 12.67 | 6.27 | ||
Maximum of Months | 0.441565E+11 | 22812.48 | 24.58 | 18.98 | 0.193613E+11 | 11349.14 | 24.58 | 17.66 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.529315E+11 | 28436.32 | 20-JAN-11:45 | 21.83 | 15.77 | 0.187909E+11 | 11319.59 | 07-JAN-18:19 | 21.83 | 15.77 |
February | 0.476570E+11 | 28308.96 | 01-FEB-11:45 | 25.50 | 14.48 | 0.169999E+11 | 11319.69 | 25-FEB-18:19 | 11.00 | 9.85 |
March | 0.530951E+11 | 29168.99 | 19-MAR-10:33 | 19.33 | 15.06 | 0.188086E+11 | 11319.62 | 25-MAR-17:19 | 11.00 | 10.47 |
April | 0.528509E+11 | 29567.87 | 30-APR-10:33 | 25.67 | 16.97 | 0.182308E+11 | 11319.57 | 08-APR-17:19 | 25.67 | 16.97 |
May | 0.545725E+11 | 29272.52 | 04-MAY-10:33 | 22.00 | 15.73 | 0.188399E+11 | 11319.62 | 20-MAY-17:19 | 17.00 | 12.68 |
June | 0.538218E+11 | 29639.28 | 25-JUN-10:33 | 23.00 | 17.26 | 0.182438E+11 | 11319.62 | 17-JUN-17:19 | 23.00 | 17.26 |
July | 0.565616E+11 | 30075.30 | 23-JUL-10:33 | 25.67 | 20.39 | 0.188505E+11 | 11319.65 | 08-JUL-17:19 | 25.67 | 20.39 |
August | 0.566548E+11 | 29952.91 | 19-AUG-10:33 | 24.67 | 20.11 | 0.188581E+11 | 11319.65 | 12-AUG-17:19 | 24.67 | 20.11 |
September | 0.537295E+11 | 30329.55 | 30-SEP-10:50 | 30.78 | 17.57 | 0.182406E+11 | 11319.61 | 30-SEP-17:19 | 25.00 | 17.45 |
October | 0.551196E+11 | 30194.87 | 15-OCT-10:40 | 31.67 | 16.43 | 0.188447E+11 | 11319.60 | 14-OCT-17:19 | 31.67 | 16.43 |
November | 0.515325E+11 | 29053.34 | 19-NOV-11:45 | 26.00 | 15.39 | 0.182151E+11 | 11319.57 | 25-NOV-18:19 | 13.00 | 11.13 |
December | 0.528753E+11 | 28349.42 | 05-DEC-11:45 | 23.17 | 12.83 | 0.188002E+11 | 11319.58 | 02-DEC-18:19 | 23.17 | 12.83 |
Annual Sum or Average | 0.641402E+12 | 0.221723E+12 | ||||||||
Minimum of Months | 0.476570E+11 | 28308.96 | 19.33 | 12.83 | 0.169999E+11 | 11319.57 | 11.00 | 9.85 | ||
Maximum of Months | 0.566548E+11 | 30329.55 | 31.67 | 20.39 | 0.188581E+11 | 11319.69 | 31.67 | 20.39 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.794350E+10 | 4371.84 | 06-JAN-23:00 | 5.00 | 2.03 | 0.135511E+10 | 875.80 | 18-JAN-22:40 | 16.33 | 13.19 |
February | 0.721228E+10 | 4236.69 | 04-FEB-05:55 | 5.00 | 0.22 | 0.122676E+10 | 856.85 | 01-FEB-22:40 | 5.00 | 0.22 |
March | 0.780084E+10 | 4270.05 | 11-MAR-11:33 | 24.00 | 13.82 | 0.135573E+10 | 875.07 | 24-MAR-21:40 | 13.00 | 11.48 |
April | 0.837496E+10 | 4453.11 | 30-APR-10:33 | 25.67 | 16.97 | 0.137771E+10 | 898.63 | 27-APR-21:40 | 25.67 | 16.97 |
May | 0.866361E+10 | 4525.64 | 04-MAY-10:33 | 22.00 | 15.73 | 0.142734E+10 | 920.38 | 04-MAY-21:40 | 17.00 | 15.07 |
June | 0.891940E+10 | 4589.88 | 30-JUN-10:33 | 23.33 | 17.95 | 0.143751E+10 | 926.87 | 27-JUN-21:40 | 23.33 | 17.95 |
July | 0.977731E+10 | 4822.62 | 30-JUL-10:33 | 24.67 | 20.10 | 0.153148E+10 | 942.78 | 31-JUL-21:40 | 18.80 | 17.92 |
August | 0.988214E+10 | 4803.76 | 19-AUG-10:33 | 24.67 | 20.11 | 0.154945E+10 | 947.59 | 18-AUG-21:40 | 24.67 | 20.11 |
September | 0.911093E+10 | 5183.82 | 30-SEP-13:40 | 32.00 | 17.36 | 0.145389E+10 | 971.82 | 29-SEP-21:40 | 32.00 | 17.36 |
October | 0.943475E+10 | 5051.30 | 16-OCT-13:10 | 33.75 | 16.65 | 0.150746E+10 | 977.57 | 16-OCT-21:40 | 19.33 | 11.10 |
November | 0.812308E+10 | 4535.76 | 19-NOV-11:33 | 26.00 | 15.32 | 0.134915E+10 | 889.61 | 01-NOV-00:10 | 26.00 | 15.32 |
December | 0.818550E+10 | 4367.77 | 19-DEC-11:33 | 25.00 | 11.16 | 0.136568E+10 | 886.37 | 05-DEC-22:40 | 25.00 | 11.16 |
Annual Sum or Average | 0.103428E+12 | 0.169373E+11 | ||||||||
Minimum of Months | 0.721228E+10 | 4236.69 | 5.00 | 0.22 | 0.122676E+10 | 856.85 | 5.00 | 0.22 | ||
Maximum of Months | 0.988214E+10 | 5183.82 | 33.75 | 20.11 | 0.154945E+10 | 977.57 | 32.00 | 20.11 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 13.23 |
March | 2152.03 | 5.52 | 30-MAR-06:07 | 5.58 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 10.63 |
Annual Sum or Average | 2152.03 | |||
Minimum of Months | 0.00 | 0.00 | 5.58 | |
Maximum of Months | 2152.03 | 5.52 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 40070037.40 | 1044.95 | 29-JAN-16:04 | 13.83 |
February | 22079190.87 | 1049.49 | 02-FEB-19:04 | 13.83 |
March | 51021703.53 | 1057.47 | 21-MAR-18:04 | 13.83 |
April | 8000471.32 | 1050.21 | 06-APR-18:04 | 13.00 |
May | 4662004.03 | 1048.29 | 08-MAY-18:04 | 14.83 |
June | 1895497.01 | 1050.25 | 16-JUN-15:04 | 17.17 |
July | 1579132.67 | 1012.84 | 04-JUL-08:04 | 19.50 |
August | 1390064.43 | 798.55 | 03-AUG-08:04 | 21.17 |
September | 2222034.28 | 1022.98 | 22-SEP-18:04 | 18.00 |
October | 2758301.50 | 1057.47 | 23-OCT-15:04 | 17.00 |
November | 5715566.76 | 1041.04 | 04-NOV-18:04 | 12.00 |
December | 22152304.96 | 1040.87 | 11-DEC-16:04 | 13.83 |
Annual Sum or Average | 0.163546E+09 | |||
Minimum of Months | 1390064.43 | 798.55 | 12.00 | |
Maximum of Months | 51021703.53 | 1057.47 | 21.17 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.104270E+09 | 1037.69 | 22-JAN-16:04 | 14.67 |
February | 38619993.02 | 1027.47 | 09-FEB-19:03 | 11.92 |
March | 69433575.56 | 1021.42 | 18-MAR-15:04 | 16.83 |
April | 8749827.96 | 1044.01 | 06-APR-18:04 | 13.00 |
May | 3936717.41 | 1037.69 | 11-MAY-15:04 | 17.00 |
June | 1123548.69 | 984.76 | 02-JUN-08:53 | 19.00 |
July | 325906.75 | 557.91 | 10-JUL-08:54 | 21.00 |
August | 193351.46 | 427.12 | 22-AUG-21:55 | 16.30 |
September | 1451948.63 | 999.41 | 02-SEP-08:54 | 18.00 |
October | 1771736.07 | 1043.29 | 23-OCT-15:04 | 17.00 |
November | 20174244.62 | 1053.24 | 24-NOV-16:03 | 15.83 |
December | 69166131.70 | 1043.00 | 26-DEC-19:03 | 12.00 |
Annual Sum or Average | 0.319217E+09 | |||
Minimum of Months | 193351.46 | 427.12 | 11.92 | |
Maximum of Months | 0.104270E+09 | 1053.24 | 21.00 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1346050.98 | 279.76 | 08-JAN-16:03 | 13.67 |
February | 1215398.14 | 285.75 | 18-FEB-16:04 | 15.83 |
March | 1171638.11 | 284.32 | 20-MAR-15:04 | 15.67 |
April | 489949.40 | 282.16 | 18-APR-15:04 | 16.00 |
May | 513230.04 | 271.40 | 09-MAY-15:06 | 16.17 |
June | 157014.69 | 262.08 | 06-JUN-15:06 | 17.83 |
July | 47773.90 | 134.33 | 09-JUL-21:57 | 17.00 |
August | 51280.21 | 191.94 | 22-AUG-08:54 | 19.00 |
September | 311864.35 | 263.54 | 19-SEP-08:54 | 17.00 |
October | 496459.09 | 252.93 | 11-OCT-15:06 | 18.58 |
November | 1168097.99 | 281.40 | 20-NOV-16:04 | 15.67 |
December | 1243094.03 | 277.46 | 10-DEC-16:04 | 14.00 |
Annual Sum or Average | 8211850.94 | |||
Minimum of Months | 47773.90 | 134.33 | 13.67 | |
Maximum of Months | 1346050.98 | 285.75 | 19.00 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 40797328.24 | 1016.97 | 29-JAN-16:04 | 13.83 |
February | 27055147.63 | 1020.92 | 18-FEB-16:04 | 15.83 |
March | 60091411.08 | 1015.62 | 17-MAR-15:04 | 16.00 |
April | 7004485.63 | 1025.70 | 18-APR-15:04 | 16.00 |
May | 5812448.37 | 1010.25 | 12-MAY-15:04 | 15.83 |
June | 1775491.23 | 959.60 | 08-JUN-15:04 | 18.00 |
July | 248339.44 | 855.55 | 09-JUL-18:04 | 17.83 |
August | 268879.21 | 725.15 | 08-AUG-08:05 | 19.13 |
September | 1838648.66 | 886.83 | 21-SEP-18:04 | 19.00 |
October | 1893126.81 | 1009.35 | 23-OCT-15:04 | 17.00 |
November | 8279042.40 | 1030.97 | 16-NOV-16:04 | 15.67 |
December | 26548073.10 | 1020.39 | 11-DEC-16:04 | 13.83 |
Annual Sum or Average | 0.181612E+09 | |||
Minimum of Months | 248339.44 | 725.15 | 13.83 | |
Maximum of Months | 60091411.08 | 1030.97 | 19.13 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.100203E+09 | 996.81 | 06-JAN-16:03 | 16.67 |
February | 49765319.90 | 980.85 | 24-FEB-16:03 | 14.00 |
March | 82352669.78 | 978.43 | 17-MAR-15:04 | 16.00 |
April | 7852427.45 | 1002.14 | 18-APR-15:04 | 16.00 |
May | 4576495.27 | 992.53 | 12-MAY-15:04 | 15.83 |
June | 959594.32 | 861.32 | 11-JUN-15:05 | 18.00 |
July | 224198.46 | 457.80 | 27-JUL-06:15 | 15.33 |
August | 142152.02 | 484.78 | 21-AUG-20:14 | 15.00 |
September | 1005371.50 | 671.88 | 27-SEP-21:54 | 16.70 |
October | 1508910.48 | 991.49 | 23-OCT-15:04 | 17.00 |
November | 28830920.56 | 997.24 | 01-NOV-15:04 | 16.97 |
December | 78042655.72 | 992.62 | 17-DEC-19:03 | 13.17 |
Annual Sum or Average | 0.355464E+09 | |||
Minimum of Months | 142152.02 | 457.80 | 13.17 | |
Maximum of Months | 0.100203E+09 | 1002.14 | 18.00 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.127277E+09 | 1222.92 | 16-JAN-16:04 | 18.00 |
February | 89515289.09 | 1171.31 | 17-FEB-16:04 | 17.00 |
March | 0.138154E+09 | 1223.47 | 17-MAR-15:04 | 16.00 |
April | 19827250.38 | 1159.08 | 17-APR-15:04 | 17.33 |
May | 15860671.82 | 1232.95 | 11-MAY-15:04 | 17.00 |
June | 2071664.09 | 1238.47 | 16-JUN-15:04 | 17.17 |
July | 1328261.02 | 995.13 | 04-JUL-08:04 | 19.50 |
August | 1142059.29 | 861.16 | 22-AUG-18:04 | 17.00 |
September | 2199755.95 | 1021.14 | 22-SEP-18:04 | 18.00 |
October | 6685676.51 | 1235.63 | 23-OCT-15:04 | 17.00 |
November | 44829888.42 | 1073.30 | 09-NOV-16:04 | 17.83 |
December | 0.103215E+09 | 1150.20 | 27-DEC-09:03 | 15.67 |
Annual Sum or Average | 0.552106E+09 | |||
Minimum of Months | 1142059.29 | 861.16 | 15.67 | |
Maximum of Months | 0.138154E+09 | 1238.47 | 19.50 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.258824E+09 | 1164.80 | 26-JAN-16:04 | 15.67 |
February | 0.146007E+09 | 1121.21 | 09-FEB-09:01 | 11.90 |
March | 0.178183E+09 | 1146.78 | 30-MAR-08:62 | 9.50 |
April | 21409018.16 | 1192.41 | 14-APR-15:04 | 17.67 |
May | 12544488.74 | 1222.54 | 13-MAY-15:04 | 16.17 |
June | 1007630.25 | 1041.56 | 08-JUN-15:04 | 18.00 |
July | 177550.32 | 546.70 | 06-JUL-08:54 | 20.00 |
August | 293262.13 | 551.54 | 22-AUG-21:55 | 16.30 |
September | 1699373.16 | 939.74 | 12-SEP-08:53 | 21.00 |
October | 8583311.97 | 1217.88 | 23-OCT-15:04 | 17.00 |
November | 0.101893E+09 | 1203.27 | 17-NOV-16:04 | 15.67 |
December | 0.221677E+09 | 1219.54 | 27-DEC-19:03 | 14.17 |
Annual Sum or Average | 0.952299E+09 | |||
Minimum of Months | 177550.32 | 546.70 | 9.50 | |
Maximum of Months | 0.258824E+09 | 1222.54 | 21.00 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 4116938.69 | 382.79 | 25-JAN-16:05 | 15.00 |
February | 4929778.38 | 482.32 | 25-FEB-09:04 | 11.17 |
March | 22455153.54 | 647.64 | 16-MAR-15:05 | 15.83 |
April | 3328071.36 | 655.03 | 17-APR-15:04 | 17.33 |
May | 3994141.47 | 650.64 | 13-MAY-15:04 | 16.17 |
June | 1624471.00 | 630.74 | 17-JUN-18:04 | 17.83 |
July | 865439.86 | 632.26 | 04-JUL-18:04 | 17.83 |
August | 431028.18 | 476.18 | 22-AUG-18:04 | 17.00 |
September | 974683.87 | 538.30 | 22-SEP-18:04 | 18.00 |
October | 869838.25 | 626.37 | 23-OCT-15:04 | 17.00 |
November | 732571.32 | 651.32 | 24-NOV-16:04 | 15.83 |
December | 3046601.59 | 612.48 | 06-DEC-09:04 | 20.17 |
Annual Sum or Average | 47368717.50 | |||
Minimum of Months | 431028.18 | 382.79 | 11.17 | |
Maximum of Months | 22455153.54 | 655.03 | 20.17 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.136942E+11 | 13190.31 | 02-JAN-20:10 | 0.121516E+11 | 9632.53 | 02-JAN-20:10 |
February | 0.123646E+11 | 13190.31 | 01-FEB-20:10 | 0.109726E+11 | 9632.53 | 01-FEB-20:10 |
March | 0.137364E+11 | 13190.31 | 01-MAR-20:10 | 0.121771E+11 | 9632.53 | 01-MAR-20:10 |
April | 0.132299E+11 | 13190.31 | 03-APR-19:10 | 0.117446E+11 | 9632.53 | 03-APR-19:10 |
May | 0.137180E+11 | 13190.31 | 01-MAY-19:10 | 0.121662E+11 | 9632.53 | 01-MAY-19:10 |
June | 0.132906E+11 | 13190.31 | 01-JUN-19:10 | 0.117829E+11 | 9632.53 | 01-JUN-19:10 |
July | 0.136573E+11 | 13190.31 | 03-JUL-19:10 | 0.121279E+11 | 9632.53 | 03-JUL-19:10 |
August | 0.137417E+11 | 13190.31 | 01-AUG-19:10 | 0.121808E+11 | 9632.53 | 01-AUG-19:10 |
September | 0.132352E+11 | 13190.31 | 01-SEP-19:10 | 0.117482E+11 | 9632.53 | 01-SEP-19:10 |
October | 0.136889E+11 | 13190.31 | 02-OCT-19:10 | 0.121479E+11 | 9632.53 | 02-OCT-19:10 |
November | 0.132800E+11 | 13190.31 | 01-NOV-19:10 | 0.117774E+11 | 9632.53 | 01-NOV-19:10 |
December | 0.136573E+11 | 13190.31 | 01-DEC-20:10 | 0.121279E+11 | 9632.53 | 01-DEC-20:10 |
Annual Sum or Average | 0.161294E+12 | 0.143105E+12 | ||||
Minimum of Months | 0.123646E+11 | 13190.31 | 0.109726E+11 | 9632.53 | ||
Maximum of Months | 0.137417E+11 | 13190.31 | 0.121808E+11 | 9632.53 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.620421E+09 | 597.59 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.560184E+09 | 597.59 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.622334E+09 | 597.59 | 01-MAR-20:10 | 0.866718E+09 | 685.60 | 01-MAR-20:10 |
April | 0.599386E+09 | 597.59 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.621497E+09 | 597.59 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.602135E+09 | 597.59 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.618748E+09 | 597.59 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.622573E+09 | 597.59 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.599625E+09 | 597.59 | 01-SEP-19:10 | 0.836191E+09 | 685.60 | 01-SEP-19:10 |
October | 0.620182E+09 | 597.59 | 02-OCT-19:10 | 0.864640E+09 | 685.60 | 02-OCT-19:10 |
November | 0.601657E+09 | 597.59 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.618748E+09 | 597.59 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.730749E+10 | 0.101856E+11 | ||||
Minimum of Months | 0.560184E+09 | 597.59 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.622573E+09 | 597.59 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.718450E+09 | 692.02 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.648695E+09 | 692.02 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.720665E+09 | 692.02 | 01-MAR-20:10 | 0.100366E+10 | 793.93 | 01-MAR-20:10 |
April | 0.694091E+09 | 692.02 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.719696E+09 | 692.02 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.697275E+09 | 692.02 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.716513E+09 | 692.02 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.720942E+09 | 692.02 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.694368E+09 | 692.02 | 01-SEP-19:10 | 0.968312E+09 | 793.93 | 01-SEP-19:10 |
October | 0.718174E+09 | 692.02 | 02-OCT-19:10 | 0.100126E+10 | 793.93 | 02-OCT-19:10 |
November | 0.696721E+09 | 692.02 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.716513E+09 | 692.02 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.846210E+10 | 0.117950E+11 | ||||
Minimum of Months | 0.648695E+09 | 692.02 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.720942E+09 | 692.02 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.710312E+09 | 684.18 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.641347E+09 | 684.18 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.712502E+09 | 684.18 | 01-MAR-20:10 | 0.106120E+10 | 839.45 | 01-MAR-20:10 |
April | 0.686229E+09 | 684.18 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.711544E+09 | 684.18 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.689376E+09 | 684.18 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.708397E+09 | 684.18 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.712775E+09 | 684.18 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.686503E+09 | 684.18 | 01-SEP-19:10 | 0.102382E+10 | 839.45 | 01-SEP-19:10 |
October | 0.710039E+09 | 684.18 | 02-OCT-19:10 | 0.105866E+10 | 839.45 | 02-OCT-19:10 |
November | 0.688829E+09 | 684.18 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.708397E+09 | 684.18 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.836625E+10 | 0.124712E+11 | ||||
Minimum of Months | 0.641347E+09 | 684.18 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.712775E+09 | 684.18 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.261454E+09 | 251.84 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.236069E+09 | 251.84 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.262260E+09 | 251.84 | 01-MAR-20:10 | 0.306128E+09 | 242.16 | 01-MAR-20:10 |
April | 0.252589E+09 | 251.84 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.261907E+09 | 251.84 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.253748E+09 | 251.84 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.260749E+09 | 251.84 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.262360E+09 | 251.84 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.252690E+09 | 251.84 | 01-SEP-19:10 | 0.295345E+09 | 242.16 | 01-SEP-19:10 |
October | 0.261353E+09 | 251.84 | 02-OCT-19:10 | 0.305393E+09 | 242.16 | 02-OCT-19:10 |
November | 0.253546E+09 | 251.84 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.260749E+09 | 251.84 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.307947E+10 | 0.359760E+10 | ||||
Minimum of Months | 0.236069E+09 | 251.84 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.262360E+09 | 251.84 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.337502E+09 | 325.08 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.304733E+09 | 325.08 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.338542E+09 | 325.08 | 01-MAR-20:10 | 0.578079E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.326059E+09 | 325.08 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.338087E+09 | 325.08 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.327554E+09 | 325.08 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.336592E+09 | 325.08 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.338672E+09 | 325.08 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.326189E+09 | 325.08 | 01-SEP-19:10 | 0.557718E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.337372E+09 | 325.08 | 02-OCT-19:10 | 0.576693E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.327294E+09 | 325.08 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.336592E+09 | 325.08 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.397519E+10 | 0.679355E+11 | ||||
Minimum of Months | 0.304733E+09 | 325.08 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.338672E+09 | 325.08 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.130497E+10 | 1701.53 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.114673E+10 | 1701.53 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.125376E+10 | 1701.53 | 01-MAR-20:10 | 0.122027E+10 | 965.27 | 01-MAR-20:10 |
April | 0.113983E+10 | 1701.53 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.112129E+10 | 1701.53 | 01-MAY-19:10 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.107741E+10 | 1701.53 | 01-JUN-19:10 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.111560E+10 | 1701.53 | 03-JUL-19:10 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.115503E+10 | 1701.53 | 01-AUG-19:10 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.120189E+10 | 1701.53 | 01-SEP-19:10 | 0.117729E+10 | 965.27 | 01-SEP-19:10 |
October | 0.128074E+10 | 1701.53 | 02-OCT-19:10 | 0.121734E+10 | 965.27 | 02-OCT-19:10 |
November | 0.124997E+10 | 1701.53 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.129666E+10 | 1701.53 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.143439E+11 | 0.143405E+11 | ||||
Minimum of Months | 0.107741E+10 | 1701.53 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.130497E+10 | 1701.53 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.941787E+10 | 9504.80 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.847556E+10 | 9504.80 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.940788E+10 | 9504.80 | 01-MAR-20:10 | 0.126786E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.900527E+10 | 9504.80 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.929404E+10 | 9504.80 | 01-MAY-19:10 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.899654E+10 | 9504.80 | 01-JUN-19:10 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.924755E+10 | 9504.80 | 03-JUL-19:10 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.933252E+10 | 9504.80 | 01-AUG-19:10 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.906632E+10 | 9504.80 | 01-SEP-19:10 | 0.122320E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.940530E+10 | 9504.80 | 02-OCT-19:10 | 0.126482E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.911494E+10 | 9504.80 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.938557E+10 | 9504.80 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.110149E+12 | 0.148998E+12 | ||||
Minimum of Months | 0.847556E+10 | 9504.80 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.941787E+10 | 9504.80 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196602E+09 | 177.88 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.177551E+09 | 177.88 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.195039E+09 | 177.88 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.190486E+09 | 177.88 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.195821E+09 | 177.88 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.188975E+09 | 177.88 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.197358E+09 | 177.88 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.195039E+09 | 177.88 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.190538E+09 | 177.88 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.196576E+09 | 177.88 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.189731E+09 | 177.88 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.197383E+09 | 177.88 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.231110E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.177551E+09 | 177.88 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.197383E+09 | 177.88 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196579E+09 | 177.86 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.177530E+09 | 177.86 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.195017E+09 | 177.86 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.190464E+09 | 177.86 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.195798E+09 | 177.86 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.188953E+09 | 177.86 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.197334E+09 | 177.86 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.195017E+09 | 177.86 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.190515E+09 | 177.86 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.196553E+09 | 177.86 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.189708E+09 | 177.86 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.197360E+09 | 177.86 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.231083E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.177530E+09 | 177.86 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.197360E+09 | 177.86 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123557E+09 | 111.79 | 01-JAN-19:10 | 0.217935E+09 | 232.19 | 01-JAN-08:09 |
February | 0.111584E+09 | 111.79 | 01-FEB-20:10 | 0.196843E+09 | 232.19 | 01-FEB-07:10 |
March | 0.122575E+09 | 111.79 | 01-MAR-20:10 | 0.217824E+09 | 232.19 | 01-MAR-07:10 |
April | 0.119713E+09 | 111.79 | 01-APR-18:10 | 0.210923E+09 | 232.19 | 01-APR-07:10 |
May | 0.123066E+09 | 111.79 | 01-MAY-19:10 | 0.217879E+09 | 232.19 | 01-MAY-06:10 |
June | 0.118764E+09 | 111.79 | 01-JUN-19:10 | 0.210812E+09 | 232.19 | 01-JUN-06:10 |
July | 0.124032E+09 | 111.79 | 01-JUL-18:10 | 0.217991E+09 | 232.19 | 01-JUL-07:10 |
August | 0.122575E+09 | 111.79 | 01-AUG-19:10 | 0.217824E+09 | 232.19 | 01-AUG-06:10 |
September | 0.119746E+09 | 111.79 | 01-SEP-19:10 | 0.210923E+09 | 232.19 | 01-SEP-06:10 |
October | 0.123541E+09 | 111.79 | 01-OCT-18:10 | 0.217935E+09 | 232.19 | 01-OCT-07:10 |
November | 0.119238E+09 | 111.79 | 01-NOV-19:10 | 0.210867E+09 | 232.19 | 01-NOV-06:10 |
December | 0.124048E+09 | 111.79 | 01-DEC-20:10 | 0.217991E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.145244E+10 | 0.256575E+10 | ||||
Minimum of Months | 0.111584E+09 | 111.79 | 0.196843E+09 | 232.19 | ||
Maximum of Months | 0.124048E+09 | 111.79 | 0.217991E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123591E+09 | 111.82 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 0.111614E+09 | 111.82 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 0.122608E+09 | 111.82 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 0.119746E+09 | 111.82 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 0.123099E+09 | 111.82 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 0.118796E+09 | 111.82 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 0.124066E+09 | 111.82 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 0.122608E+09 | 111.82 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 0.119778E+09 | 111.82 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 0.123574E+09 | 111.82 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 0.119271E+09 | 111.82 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 0.124082E+09 | 111.82 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.145283E+10 | 0.256645E+10 | ||||
Minimum of Months | 0.111614E+09 | 111.82 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 0.124082E+09 | 111.82 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196602E+09 | 177.88 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.177551E+09 | 177.88 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.195039E+09 | 177.88 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.190486E+09 | 177.88 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.195821E+09 | 177.88 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.188975E+09 | 177.88 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.197358E+09 | 177.88 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.195039E+09 | 177.88 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.190538E+09 | 177.88 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.196576E+09 | 177.88 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.189731E+09 | 177.88 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.197383E+09 | 177.88 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.231110E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.177551E+09 | 177.88 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.197383E+09 | 177.88 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196579E+09 | 177.86 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.177530E+09 | 177.86 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.195017E+09 | 177.86 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.190464E+09 | 177.86 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.195798E+09 | 177.86 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.188953E+09 | 177.86 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.197334E+09 | 177.86 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.195017E+09 | 177.86 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.190515E+09 | 177.86 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.196553E+09 | 177.86 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.189708E+09 | 177.86 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.197360E+09 | 177.86 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.231083E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.177530E+09 | 177.86 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.197360E+09 | 177.86 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.193865E+10 | 1867.32 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.175042E+10 | 1867.32 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.194462E+10 | 1867.32 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.187292E+10 | 1867.32 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.194201E+10 | 1867.32 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.188151E+10 | 1867.32 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.193342E+10 | 1867.32 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.194537E+10 | 1867.32 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.187367E+10 | 1867.32 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.193790E+10 | 1867.32 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.188002E+10 | 1867.32 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.193342E+10 | 1867.32 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.228339E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.175042E+10 | 1867.32 | 0.00 | 0.00 | |
Maximum of Months | 0.194537E+10 | 1867.32 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196602E+09 | 177.88 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.177551E+09 | 177.88 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.195039E+09 | 177.88 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.190486E+09 | 177.88 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.195821E+09 | 177.88 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.188975E+09 | 177.88 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.197358E+09 | 177.88 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.195039E+09 | 177.88 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.190538E+09 | 177.88 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.196576E+09 | 177.88 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.189731E+09 | 177.88 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.197383E+09 | 177.88 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.231110E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.177551E+09 | 177.88 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.197383E+09 | 177.88 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196579E+09 | 177.86 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.177530E+09 | 177.86 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.195017E+09 | 177.86 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.190464E+09 | 177.86 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.195798E+09 | 177.86 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.188953E+09 | 177.86 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.197334E+09 | 177.86 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.195017E+09 | 177.86 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.190515E+09 | 177.86 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.196553E+09 | 177.86 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.189708E+09 | 177.86 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.197360E+09 | 177.86 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.231083E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.177530E+09 | 177.86 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.197360E+09 | 177.86 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123591E+09 | 111.82 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 0.111614E+09 | 111.82 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 0.122608E+09 | 111.82 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 0.119746E+09 | 111.82 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 0.123099E+09 | 111.82 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 0.118796E+09 | 111.82 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 0.124066E+09 | 111.82 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 0.122608E+09 | 111.82 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 0.119778E+09 | 111.82 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 0.123574E+09 | 111.82 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 0.119271E+09 | 111.82 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 0.124082E+09 | 111.82 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.145283E+10 | 0.256645E+10 | ||||
Minimum of Months | 0.111614E+09 | 111.82 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 0.124082E+09 | 111.82 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.278781E+10 | 2988.03 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.246232E+10 | 2988.03 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.268528E+10 | 2988.03 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.249776E+10 | 2988.03 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.250863E+10 | 2988.03 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.240793E+10 | 2988.03 | 01-JUN-19:10 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.248899E+10 | 2988.03 | 03-JUL-19:10 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.255593E+10 | 2988.03 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.257519E+10 | 2988.03 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.275378E+10 | 2988.03 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.268255E+10 | 2988.03 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.278872E+10 | 2988.03 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.311949E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.240793E+10 | 2988.03 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.278872E+10 | 2988.03 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.278781E+10 | 2988.03 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.246232E+10 | 2988.03 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.268528E+10 | 2988.03 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.249776E+10 | 2988.03 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.250863E+10 | 2988.03 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.240793E+10 | 2988.03 | 01-JUN-19:10 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.248899E+10 | 2988.03 | 03-JUL-19:10 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.255593E+10 | 2988.03 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.257519E+10 | 2988.03 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.275378E+10 | 2988.03 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.268255E+10 | 2988.03 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.278872E+10 | 2988.03 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.311949E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.240793E+10 | 2988.03 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.278872E+10 | 2988.03 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.110133E+10 | 1060.81 | 02-JAN-20:10 | 0.368383E+11 | 16487.34 | 01-JAN-07:10 |
February | 0.994402E+09 | 1060.81 | 01-FEB-20:10 | 0.332733E+11 | 16487.34 | 01-FEB-07:10 |
March | 0.110473E+10 | 1060.81 | 01-MAR-20:10 | 0.368383E+11 | 16487.34 | 01-MAR-07:10 |
April | 0.106399E+10 | 1060.81 | 03-APR-19:10 | 0.356500E+11 | 16487.34 | 01-APR-06:10 |
May | 0.110324E+10 | 1060.81 | 01-MAY-19:10 | 0.368383E+11 | 16487.34 | 01-MAY-06:10 |
June | 0.106887E+10 | 1060.81 | 01-JUN-19:10 | 0.356500E+11 | 16487.34 | 01-JUN-06:10 |
July | 0.109836E+10 | 1060.81 | 03-JUL-19:10 | 0.368383E+11 | 16487.34 | 01-JUL-06:10 |
August | 0.110515E+10 | 1060.81 | 01-AUG-19:10 | 0.368383E+11 | 16487.34 | 01-AUG-06:10 |
September | 0.106442E+10 | 1060.81 | 01-SEP-19:10 | 0.356500E+11 | 16487.34 | 01-SEP-06:10 |
October | 0.110091E+10 | 1060.81 | 02-OCT-19:10 | 0.368383E+11 | 16487.34 | 01-OCT-06:10 |
November | 0.106802E+10 | 1060.81 | 01-NOV-19:10 | 0.356500E+11 | 16487.34 | 01-NOV-06:10 |
December | 0.109836E+10 | 1060.81 | 01-DEC-20:10 | 0.368383E+11 | 16487.34 | 01-DEC-07:10 |
Annual Sum or Average | 0.129718E+11 | 0.433742E+12 | ||||
Minimum of Months | 0.994402E+09 | 1060.81 | 0.332733E+11 | 16487.34 | ||
Maximum of Months | 0.110515E+10 | 1060.81 | 0.368383E+11 | 16487.34 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.205176E+10 | 1976.27 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.185255E+10 | 1976.27 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.205809E+10 | 1976.27 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.198220E+10 | 1976.27 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.205532E+10 | 1976.27 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.199129E+10 | 1976.27 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.204623E+10 | 1976.27 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.205888E+10 | 1976.27 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.198299E+10 | 1976.27 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.205097E+10 | 1976.27 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.198971E+10 | 1976.27 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.204623E+10 | 1976.27 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.241662E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.185255E+10 | 1976.27 | 0.00 | 0.00 | |
Maximum of Months | 0.205888E+10 | 1976.27 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.136942E+11 | 0.121516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.123646E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196682E+11 | 0.137364E+11 | 0.121771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.132299E+11 | 0.117446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.137180E+11 | 0.121662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.132906E+11 | 0.117829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.136573E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.137417E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189689E+11 | 0.132352E+11 | 0.117482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195854E+11 | 0.136889E+11 | 0.121479E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.132800E+11 | 0.117774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.136573E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230861E+12 | 0.161294E+12 | 0.143105E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.176991E+11 | 0.123646E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196682E+11 | 0.137417E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.620421E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 456622.88 | 0.130395E+09 |
February | 0.179968E+10 | 0.560184E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 31909.05 | 0.112714E+09 |
March | 0.199990E+10 | 0.622334E+09 | 0.866718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130604E+09 |
April | 0.192973E+10 | 0.599386E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 546556.49 | 92394060.51 |
May | 0.199475E+10 | 0.621497E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 52315.74 | 85970077.40 |
June | 0.193394E+10 | 0.602135E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1315370.96 | 57944632.22 |
July | 0.199054E+10 | 0.618748E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4176060.31 | 43685344.18 |
August | 0.199896E+10 | 0.622573E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3425069.34 | 44720494.00 |
September | 0.192879E+10 | 0.599625E+09 | 0.836191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3613908.84 | 60649729.00 |
October | 0.199148E+10 | 0.620182E+09 | 0.864640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6269620.24 | 62938900.08 |
November | 0.192552E+10 | 0.601657E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 280925.48 | 0.112207E+09 |
December | 0.199054E+10 | 0.618748E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 177357.57 | 0.126273E+09 |
Annual Sum or Average | 0.234744E+11 | 0.730749E+10 | 0.101856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 20345716.90 | 0.106050E+10 |
Minimum of Months | 0.179968E+10 | 0.560184E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43685344.18 |
Maximum of Months | 0.199990E+10 | 0.622573E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6269620.24 | 0.130604E+09 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.718450E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 349016.33 | 53208866.84 |
February | 0.208403E+10 | 0.648695E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 43693.05 | 47416609.89 |
March | 0.231589E+10 | 0.720665E+09 | 0.100366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61843.23 | 54947676.99 |
April | 0.223463E+10 | 0.694091E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 342678.74 | 41046433.10 |
May | 0.230993E+10 | 0.719696E+09 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41780.09 | 40260217.84 |
June | 0.223950E+10 | 0.697275E+09 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 328266.57 | 28768218.87 |
July | 0.230505E+10 | 0.716513E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1461066.17 | 22378969.65 |
August | 0.231480E+10 | 0.720942E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1610846.12 | 21791284.21 |
September | 0.223354E+10 | 0.694368E+09 | 0.968312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1449883.47 | 27100199.60 |
October | 0.230614E+10 | 0.718174E+09 | 0.100126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2889219.67 | 28089159.99 |
November | 0.222975E+10 | 0.696721E+09 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 233792.68 | 47127636.62 |
December | 0.230505E+10 | 0.716513E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 268815.66 | 52014753.18 |
Annual Sum or Average | 0.271834E+11 | 0.846210E+10 | 0.117950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 9080901.79 | 0.464150E+09 |
Minimum of Months | 0.208403E+10 | 0.648695E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41780.09 | 21791284.21 |
Maximum of Months | 0.231589E+10 | 0.720942E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2889219.67 | 54947676.99 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.487480E+09 | 0.710312E+09 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1149103.45 | 0.116019E+09 |
February | 0.440737E+09 | 0.641347E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 166588.89 | 0.103601E+09 |
March | 0.489771E+09 | 0.712502E+09 | 0.106120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 317300.37 | 0.121110E+09 |
April | 0.472586E+09 | 0.686229E+09 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1094949.89 | 89050494.13 |
May | 0.488511E+09 | 0.711544E+09 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 121281.68 | 89841430.37 |
June | 0.473617E+09 | 0.689376E+09 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 622329.60 | 64621337.69 |
July | 0.487480E+09 | 0.708397E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3170130.22 | 49851890.25 |
August | 0.489542E+09 | 0.712775E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3818117.20 | 47348309.10 |
September | 0.472357E+09 | 0.686503E+09 | 0.102382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3678537.85 | 58640181.19 |
October | 0.487709E+09 | 0.710039E+09 | 0.105866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7240176.31 | 61943971.86 |
November | 0.471555E+09 | 0.688829E+09 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 832016.74 | 0.102899E+09 |
December | 0.487480E+09 | 0.708397E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1101334.91 | 0.113194E+09 |
Annual Sum or Average | 0.574883E+10 | 0.836625E+10 | 0.124712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 23311867.12 | 0.101812E+10 |
Minimum of Months | 0.440737E+09 | 0.641347E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 121281.68 | 47348309.10 |
Maximum of Months | 0.489771E+09 | 0.712775E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7240176.31 | 0.121110E+09 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.374985E+09 | 0.261454E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 686797.64 | 65319874.30 |
February | 0.339028E+09 | 0.236069E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 104475.23 | 58026455.03 |
March | 0.376747E+09 | 0.262260E+09 | 0.306128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 194956.55 | 68184518.63 |
April | 0.363528E+09 | 0.252589E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 663255.85 | 49693433.16 |
May | 0.375778E+09 | 0.261907E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 86477.26 | 49965854.57 |
June | 0.364321E+09 | 0.253748E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 437541.43 | 35645141.47 |
July | 0.374985E+09 | 0.260749E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2002427.88 | 27190298.98 |
August | 0.376571E+09 | 0.262360E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2411963.92 | 25769644.18 |
September | 0.363352E+09 | 0.252690E+09 | 0.295345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2200554.02 | 32209066.83 |
October | 0.375161E+09 | 0.261353E+09 | 0.305393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4287131.35 | 34013639.44 |
November | 0.362735E+09 | 0.253546E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 502084.52 | 57517943.16 |
December | 0.374985E+09 | 0.260749E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 668440.16 | 63441436.93 |
Annual Sum or Average | 0.442217E+10 | 0.307947E+10 | 0.359760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14246105.80 | 0.566977E+09 |
Minimum of Months | 0.339028E+09 | 0.236069E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 86477.26 | 25769644.18 |
Maximum of Months | 0.376747E+09 | 0.262360E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4287131.35 | 68184518.63 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.337502E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 1198675.34 | 0.173909E+09 |
February | 0.139600E+10 | 0.304733E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 169195.27 | 0.155199E+09 |
March | 0.155131E+10 | 0.338542E+09 | 0.578079E+10 | 0.502211E+11 | 0.00 | 0.00 | 0.00 | 218072.11 | 0.182504E+09 |
April | 0.149688E+10 | 0.326059E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 1201371.84 | 0.132133E+09 |
May | 0.154732E+10 | 0.338087E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 187961.97 | 0.130824E+09 |
June | 0.150015E+10 | 0.327554E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 1443660.76 | 90708095.18 |
July | 0.154405E+10 | 0.336592E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 6265179.55 | 67023513.63 |
August | 0.155059E+10 | 0.338672E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 7462755.43 | 64006819.97 |
September | 0.149615E+10 | 0.326189E+09 | 0.557718E+10 | 0.484522E+11 | 0.00 | 0.00 | 0.00 | 5741672.61 | 81236499.17 |
October | 0.154478E+10 | 0.337372E+09 | 0.576693E+10 | 0.501006E+11 | 0.00 | 0.00 | 0.00 | 11080148.87 | 84732404.21 |
November | 0.149361E+10 | 0.327294E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 985550.43 | 0.149953E+09 |
December | 0.154405E+10 | 0.336592E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 1033553.58 | 0.167364E+09 |
Annual Sum or Average | 0.182090E+11 | 0.397519E+10 | 0.679355E+11 | 0.590196E+12 | 0.00 | 0.00 | 0.00 | 36987797.75 | 0.147959E+10 |
Minimum of Months | 0.139600E+10 | 0.304733E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 169195.27 | 64006819.97 |
Maximum of Months | 0.155131E+10 | 0.338672E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 11080148.87 | 0.182504E+09 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.130497E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 904652.31 | 0.320192E+09 |
February | 0.236489E+11 | 0.114673E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68835.78 | 0.280511E+09 |
March | 0.262800E+11 | 0.125376E+10 | 0.122027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.321243E+09 |
April | 0.253579E+11 | 0.113983E+10 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1098081.89 | 0.237110E+09 |
May | 0.262123E+11 | 0.112129E+10 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 157874.30 | 0.225737E+09 |
June | 0.254132E+11 | 0.107741E+10 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2802965.86 | 0.159660E+09 |
July | 0.261570E+11 | 0.111560E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9534737.59 | 0.123058E+09 |
August | 0.262677E+11 | 0.115503E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8380553.79 | 0.122600E+09 |
September | 0.253456E+11 | 0.120189E+10 | 0.117729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7689721.73 | 0.158366E+09 |
October | 0.261693E+11 | 0.128074E+10 | 0.121734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13879969.42 | 0.164554E+09 |
November | 0.253025E+11 | 0.124997E+10 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 621791.48 | 0.281005E+09 |
December | 0.261570E+11 | 0.129666E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 392471.36 | 0.311576E+09 |
Annual Sum or Average | 0.308468E+12 | 0.143439E+11 | 0.143405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 45531655.52 | 0.270561E+10 |
Minimum of Months | 0.236489E+11 | 0.107741E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122600E+09 |
Maximum of Months | 0.262800E+11 | 0.130497E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13879969.42 | 0.321243E+09 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.941787E+10 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4254819.30 | 0.909171E+09 |
February | 0.702046E+11 | 0.847556E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 498523.45 | 0.808499E+09 |
March | 0.780153E+11 | 0.940788E+10 | 0.126786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 614936.02 | 0.932707E+09 |
April | 0.752779E+11 | 0.900527E+10 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4785480.87 | 0.692209E+09 |
May | 0.778146E+11 | 0.929404E+10 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 687921.74 | 0.680903E+09 |
June | 0.754422E+11 | 0.899654E+10 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5698830.99 | 0.487020E+09 |
July | 0.776503E+11 | 0.924755E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 25021937.79 | 0.374631E+09 |
August | 0.779788E+11 | 0.933252E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 27046363.99 | 0.363497E+09 |
September | 0.752414E+11 | 0.906632E+10 | 0.122320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 23285947.84 | 0.456201E+09 |
October | 0.776868E+11 | 0.940530E+10 | 0.126482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 44607288.56 | 0.476545E+09 |
November | 0.751137E+11 | 0.911494E+10 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2642461.98 | 0.802353E+09 |
December | 0.776503E+11 | 0.938557E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2714135.67 | 0.888052E+09 |
Annual Sum or Average | 0.915726E+12 | 0.110149E+12 | 0.148998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141859E+09 | 0.787179E+10 |
Minimum of Months | 0.702046E+11 | 0.847556E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 498523.45 | 0.363497E+09 |
Maximum of Months | 0.780153E+11 | 0.941787E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 44607288.56 | 0.932707E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196602E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 483588.43 | 71871104.38 |
February | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 85145.19 | 62956333.72 |
March | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 80929.00 | 75132039.89 |
April | 0.293479E+09 | 0.190486E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 440911.07 | 52219050.28 |
May | 0.303504E+09 | 0.195821E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41113.08 | 51129372.52 |
June | 0.293842E+09 | 0.188975E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 549822.90 | 33011265.68 |
July | 0.303141E+09 | 0.197358E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2553513.23 | 21747343.41 |
August | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3007055.64 | 20326848.62 |
September | 0.293479E+09 | 0.190538E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2888375.57 | 29112591.71 |
October | 0.303322E+09 | 0.196576E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5054910.11 | 29878402.56 |
November | 0.293661E+09 | 0.189731E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 379862.95 | 60195000.46 |
December | 0.303141E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 420923.81 | 68644891.24 |
Annual Sum or Average | 0.357224E+10 | 0.231110E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15986150.98 | 0.576224E+09 |
Minimum of Months | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41113.08 | 20326848.62 |
Maximum of Months | 0.303685E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5054910.11 | 75132039.89 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196579E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 561819.29 | 70642957.85 |
February | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 98509.90 | 62244402.17 |
March | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 102406.46 | 74959268.58 |
April | 0.293479E+09 | 0.190464E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 396896.01 | 54714150.38 |
May | 0.303504E+09 | 0.195798E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 28265.64 | 54719793.47 |
June | 0.293842E+09 | 0.188953E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 367744.83 | 40097269.37 |
July | 0.303141E+09 | 0.197334E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2121001.87 | 30788730.68 |
August | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2458428.38 | 28456306.10 |
September | 0.293479E+09 | 0.190515E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2776368.24 | 34028279.34 |
October | 0.303322E+09 | 0.196553E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4852244.97 | 33543624.95 |
November | 0.293661E+09 | 0.189708E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 441266.74 | 59860783.59 |
December | 0.303141E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 552446.41 | 67618145.40 |
Annual Sum or Average | 0.357224E+10 | 0.231083E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14757398.75 | 0.611674E+09 |
Minimum of Months | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 28265.64 | 28456306.10 |
Maximum of Months | 0.303685E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4852244.97 | 74959268.58 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.123557E+09 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31649454.91 |
February | 0.00 | 0.111584E+09 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28058552.13 |
March | 0.00 | 0.122575E+09 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32348739.41 |
April | 0.00 | 0.119713E+09 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 263.49 | 25532765.42 |
May | 0.00 | 0.123066E+09 | 0.217879E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25626830.70 |
June | 0.00 | 0.118764E+09 | 0.210812E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20077475.88 |
July | 0.00 | 0.124032E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19981.07 | 16697791.56 |
August | 0.00 | 0.122575E+09 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13567.91 | 16171071.79 |
September | 0.00 | 0.119746E+09 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 296030.18 | 18631719.21 |
October | 0.00 | 0.123541E+09 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 507387.01 | 18829407.53 |
November | 0.00 | 0.119238E+09 | 0.210867E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 202.80 | 27967906.96 |
December | 0.00 | 0.124048E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30739510.41 |
Annual Sum or Average | 0.00 | 0.145244E+10 | 0.256575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 837432.46 | 0.292331E+09 |
Minimum of Months | 0.00 | 0.111584E+09 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16171071.79 |
Maximum of Months | 0.00 | 0.124048E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 507387.01 | 32348739.41 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.123591E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 196540.27 | 19645921.12 |
February | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 36448.40 | 17266284.59 |
March | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 42557.95 | 20748984.39 |
April | 0.293479E+09 | 0.119746E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 145699.28 | 14509597.38 |
May | 0.303504E+09 | 0.123099E+09 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14912.74 | 14503646.02 |
June | 0.293842E+09 | 0.118796E+09 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 128445.78 | 10141029.11 |
July | 0.303141E+09 | 0.124066E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 648711.06 | 7403302.25 |
August | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 774441.90 | 6838450.28 |
September | 0.293479E+09 | 0.119778E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 803481.10 | 8694453.15 |
October | 0.303322E+09 | 0.123574E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1447735.47 | 8920848.30 |
November | 0.293661E+09 | 0.119271E+09 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 170166.38 | 16395371.51 |
December | 0.303141E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 210777.43 | 18703555.99 |
Annual Sum or Average | 0.357224E+10 | 0.145283E+10 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4619917.76 | 0.163771E+09 |
Minimum of Months | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14912.74 | 6838450.28 |
Maximum of Months | 0.303685E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1447735.47 | 20748984.39 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196602E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 470604.10 | 72230560.37 |
February | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 83253.31 | 63083789.82 |
March | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 77098.21 | 75476126.40 |
April | 0.293479E+09 | 0.190486E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 423760.89 | 52498419.78 |
May | 0.303504E+09 | 0.195821E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40223.67 | 51392676.31 |
June | 0.293842E+09 | 0.188975E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 513531.32 | 33108893.82 |
July | 0.303141E+09 | 0.197358E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2511276.80 | 21916875.60 |
August | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2942826.80 | 20461167.90 |
September | 0.293479E+09 | 0.190538E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2876650.18 | 29110415.63 |
October | 0.303322E+09 | 0.196576E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5047201.05 | 29993108.86 |
November | 0.293661E+09 | 0.189731E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 373865.29 | 60375390.52 |
December | 0.303141E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 415311.67 | 68896632.66 |
Annual Sum or Average | 0.357224E+10 | 0.231110E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15775603.28 | 0.578544E+09 |
Minimum of Months | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40223.67 | 20461167.90 |
Maximum of Months | 0.303685E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5047201.05 | 75476126.40 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196579E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 528100.39 | 70743579.42 |
February | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 73952.96 | 62110181.71 |
March | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 77477.60 | 75042749.79 |
April | 0.293479E+09 | 0.190464E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 324099.18 | 54048003.92 |
May | 0.303504E+09 | 0.195798E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 27166.38 | 54021933.34 |
June | 0.293842E+09 | 0.188953E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 329432.45 | 38217539.39 |
July | 0.303141E+09 | 0.197334E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2053752.21 | 29137349.85 |
August | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2347162.79 | 27294072.26 |
September | 0.293479E+09 | 0.190515E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2726585.78 | 32865799.75 |
October | 0.303322E+09 | 0.196553E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4693409.55 | 33183922.53 |
November | 0.293661E+09 | 0.189708E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 413684.11 | 59527496.79 |
December | 0.303141E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 483828.08 | 67623130.02 |
Annual Sum or Average | 0.357224E+10 | 0.231083E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14078651.48 | 0.603816E+09 |
Minimum of Months | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 27166.38 | 27294072.26 |
Maximum of Months | 0.303685E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4693409.55 | 75042749.79 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.385223E+10 | 0.193865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 871781.25 | 88706680.96 |
February | 0.348285E+10 | 0.175042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124604.31 | 78657352.78 |
March | 0.387034E+10 | 0.194462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188082.20 | 91984987.44 |
April | 0.373454E+10 | 0.187292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 814662.84 | 67098328.11 |
May | 0.386038E+10 | 0.194201E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109000.60 | 66534755.81 |
June | 0.374269E+10 | 0.188151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 664611.72 | 46706664.65 |
July | 0.385223E+10 | 0.193342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2765576.90 | 35869021.02 |
August | 0.386853E+10 | 0.194537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3071344.59 | 34800314.26 |
September | 0.373273E+10 | 0.187367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2916524.40 | 43373488.71 |
October | 0.385404E+10 | 0.193790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5550197.45 | 46026505.69 |
November | 0.372639E+10 | 0.188002E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 589807.58 | 78001564.73 |
December | 0.385223E+10 | 0.193342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 733988.29 | 86701475.77 |
Annual Sum or Average | 0.454292E+11 | 0.228339E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18400182.15 | 0.764461E+09 |
Minimum of Months | 0.348285E+10 | 0.175042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109000.60 | 34800314.26 |
Maximum of Months | 0.387034E+10 | 0.194537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5550197.45 | 91984987.44 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196602E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 461416.87 | 72059402.46 |
February | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 82273.22 | 63054761.59 |
March | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 74535.41 | 75323156.44 |
April | 0.293479E+09 | 0.190486E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 414302.46 | 52606423.94 |
May | 0.303504E+09 | 0.195821E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35994.91 | 51566389.53 |
June | 0.293842E+09 | 0.188975E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 500088.48 | 33413153.52 |
July | 0.303141E+09 | 0.197358E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2439617.74 | 22113031.73 |
August | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2875427.25 | 20649740.18 |
September | 0.293479E+09 | 0.190538E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2840931.13 | 29457737.63 |
October | 0.303322E+09 | 0.196576E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4965663.89 | 30133621.95 |
November | 0.293661E+09 | 0.189731E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 365950.93 | 60400055.55 |
December | 0.303141E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 403853.44 | 68796095.42 |
Annual Sum or Average | 0.357224E+10 | 0.231110E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15460055.71 | 0.579574E+09 |
Minimum of Months | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35994.91 | 20649740.18 |
Maximum of Months | 0.303685E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4965663.89 | 75323156.44 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196579E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 555896.54 | 70521539.28 |
February | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 102915.73 | 62187957.72 |
March | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 90081.03 | 75228311.67 |
April | 0.293479E+09 | 0.190464E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 360310.14 | 55574908.24 |
May | 0.303504E+09 | 0.195798E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 24638.60 | 55585165.31 |
June | 0.293842E+09 | 0.188953E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 330489.16 | 41393462.44 |
July | 0.303141E+09 | 0.197334E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2026531.66 | 32201205.82 |
August | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2345776.70 | 29553328.28 |
September | 0.293479E+09 | 0.190515E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2742977.52 | 34534142.34 |
October | 0.303322E+09 | 0.196553E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4809789.92 | 33502342.28 |
November | 0.293661E+09 | 0.189708E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 448017.24 | 59750403.98 |
December | 0.303141E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 574536.75 | 67366827.91 |
Annual Sum or Average | 0.357224E+10 | 0.231083E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14411960.98 | 0.617400E+09 |
Minimum of Months | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 24638.60 | 29553328.28 |
Maximum of Months | 0.303685E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4809789.92 | 75228311.67 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.123591E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 219953.61 | 37434635.74 |
February | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40491.04 | 32772530.66 |
March | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35952.51 | 38986156.98 |
April | 0.293479E+09 | 0.119746E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 209188.02 | 26974667.95 |
May | 0.303504E+09 | 0.123099E+09 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18606.63 | 26270557.93 |
June | 0.293842E+09 | 0.118796E+09 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 263875.64 | 16927746.69 |
July | 0.303141E+09 | 0.124066E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1261063.46 | 11223436.88 |
August | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1468236.51 | 10522023.20 |
September | 0.293479E+09 | 0.119778E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1449975.87 | 15061596.34 |
October | 0.303322E+09 | 0.123574E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2521286.89 | 15539753.29 |
November | 0.293661E+09 | 0.119271E+09 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 177076.68 | 31322019.54 |
December | 0.303141E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 199732.99 | 35757297.26 |
Annual Sum or Average | 0.357224E+10 | 0.145283E+10 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7865439.85 | 0.298792E+09 |
Minimum of Months | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18606.63 | 10522023.20 |
Maximum of Months | 0.303685E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2521286.89 | 38986156.98 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.278781E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 600521.39 | 0.216947E+09 |
February | 0.415303E+11 | 0.246232E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 91375.58 | 0.194689E+09 |
March | 0.461508E+11 | 0.268528E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 26201.31 | 0.228496E+09 |
April | 0.445315E+11 | 0.249776E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 413226.73 | 0.170855E+09 |
May | 0.460320E+11 | 0.250863E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 13299.06 | 0.171040E+09 |
June | 0.446286E+11 | 0.240793E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 131438.50 | 0.123891E+09 |
July | 0.459349E+11 | 0.248899E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2281153.14 | 94653980.46 |
August | 0.461292E+11 | 0.255593E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2689743.09 | 90075115.16 |
September | 0.445099E+11 | 0.257519E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4523372.72 | 0.111988E+09 |
October | 0.459565E+11 | 0.275378E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 9092669.76 | 0.114477E+09 |
November | 0.444343E+11 | 0.268255E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 522244.43 | 0.189385E+09 |
December | 0.459349E+11 | 0.278872E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 545702.24 | 0.210098E+09 |
Annual Sum or Average | 0.541708E+12 | 0.311949E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 20930947.96 | 0.191660E+10 |
Minimum of Months | 0.415303E+11 | 0.240793E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 13299.06 | 90075115.16 |
Maximum of Months | 0.461508E+11 | 0.278872E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 9092669.76 | 0.228496E+09 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.278781E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 455757.88 | 0.219851E+09 |
February | 0.415303E+11 | 0.246232E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 69979.39 | 0.197156E+09 |
March | 0.461508E+11 | 0.268528E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4085.57 | 0.231488E+09 |
April | 0.445315E+11 | 0.249776E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 346375.21 | 0.172573E+09 |
May | 0.460320E+11 | 0.250863E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2938.90 | 0.172700E+09 |
June | 0.446286E+11 | 0.240793E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 64776.01 | 0.125006E+09 |
July | 0.459349E+11 | 0.248899E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2039748.45 | 95302837.13 |
August | 0.461292E+11 | 0.255593E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2372923.44 | 90712574.00 |
September | 0.445099E+11 | 0.257519E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4450419.64 | 0.113107E+09 |
October | 0.459565E+11 | 0.275378E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 8788080.13 | 0.115483E+09 |
November | 0.444343E+11 | 0.268255E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 444435.02 | 0.191554E+09 |
December | 0.459349E+11 | 0.278872E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 402839.38 | 0.212774E+09 |
Annual Sum or Average | 0.541708E+12 | 0.311949E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 19442359.05 | 0.193771E+10 |
Minimum of Months | 0.415303E+11 | 0.240793E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2938.90 | 90712574.00 |
Maximum of Months | 0.461508E+11 | 0.278872E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 8788080.13 | 0.231488E+09 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.110133E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 271280.49 | 0.195209E+09 |
February | 0.369574E+10 | 0.994402E+09 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 35974.29 | 0.175673E+09 |
March | 0.410691E+10 | 0.110473E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205423E+09 |
April | 0.396281E+10 | 0.106399E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 273325.49 | 0.153418E+09 |
May | 0.409635E+10 | 0.110324E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153318E+09 |
June | 0.397146E+10 | 0.106887E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 19537.04 | 0.110984E+09 |
July | 0.408770E+10 | 0.109836E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 1683660.33 | 84384461.58 |
August | 0.410499E+10 | 0.110515E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 1906274.16 | 80442412.97 |
September | 0.396089E+10 | 0.106442E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 3958266.59 | 0.100703E+09 |
October | 0.408962E+10 | 0.110091E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 7500555.02 | 0.102486E+09 |
November | 0.395417E+10 | 0.106802E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 335260.86 | 0.170396E+09 |
December | 0.408770E+10 | 0.109836E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 202863.52 | 0.188484E+09 |
Annual Sum or Average | 0.482060E+11 | 0.129718E+11 | 0.392709E+12 | 0.359593E+12 | 0.00 | 0.00 | 0.00 | 16186997.80 | 0.172092E+10 |
Minimum of Months | 0.369574E+10 | 0.994402E+09 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 80442412.97 |
Maximum of Months | 0.410691E+10 | 0.110515E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 7500555.02 | 0.205423E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.407704E+10 | 0.205176E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1134040.76 | 0.156824E+09 |
February | 0.368610E+10 | 0.185255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166041.71 | 0.138076E+09 |
March | 0.409620E+10 | 0.205809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162981.54 | 0.163895E+09 |
April | 0.395248E+10 | 0.198220E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 820502.72 | 0.120851E+09 |
May | 0.408566E+10 | 0.205532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43011.97 | 0.119368E+09 |
June | 0.396110E+10 | 0.199129E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 434773.59 | 85150446.39 |
July | 0.407704E+10 | 0.204623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3259928.79 | 65575831.60 |
August | 0.409429E+10 | 0.205888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3535599.26 | 63151966.71 |
September | 0.395056E+10 | 0.198299E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4535677.03 | 78035636.77 |
October | 0.407896E+10 | 0.205097E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8649267.47 | 80681672.54 |
November | 0.394385E+10 | 0.198971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 786376.05 | 0.135672E+09 |
December | 0.407704E+10 | 0.204623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 920493.08 | 0.150932E+09 |
Annual Sum or Average | 0.480803E+11 | 0.241662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24448693.98 | 0.135821E+10 |
Minimum of Months | 0.368610E+10 | 0.185255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43011.97 | 63151966.71 |
Maximum of Months | 0.409620E+10 | 0.205888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8649267.47 | 0.163895E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 13190.31 | 02-JAN-20:10 | 9632.53 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 13190.31 | 01-FEB-20:10 | 9632.53 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 13190.31 | 01-MAR-20:10 | 9632.53 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 13190.31 | 03-APR-19:10 | 9632.53 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 13190.31 | 01-MAY-19:10 | 9632.53 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 13190.31 | 01-JUN-19:10 | 9632.53 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 13190.31 | 03-JUL-19:10 | 9632.53 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 13190.31 | 01-AUG-19:10 | 9632.53 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 13190.31 | 01-SEP-19:10 | 9632.53 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 01-OCT-23:10 | 13190.31 | 02-OCT-19:10 | 9632.53 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 13190.31 | 01-NOV-19:10 | 9632.53 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 13190.31 | 01-DEC-20:10 | 9632.53 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 11501.89 | 13190.31 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 13190.31 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 597.59 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.59 | 17-JAN-11:55 | 110.85 | 08-JAN-07:00 |
February | 1169.53 | 01-FEB-00:10 | 597.59 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.28 | 01-FEB-12:00 | 88.64 | 04-FEB-05:55 |
March | 1169.53 | 01-MAR-00:10 | 597.59 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 94.87 | 08-MAR-04:00 |
April | 1169.53 | 01-APR-00:10 | 597.59 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.69 | 30-APR-10:55 | 76.90 | 01-APR-06:00 |
May | 1169.53 | 01-MAY-00:10 | 597.59 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.20 | 03-MAY-12:00 | 71.56 | 15-MAY-02:00 |
June | 1169.53 | 01-JUN-00:10 | 597.59 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.50 | 29-JUN-10:55 | 54.53 | 13-JUN-04:30 |
July | 1169.53 | 01-JUL-00:10 | 597.59 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.90 | 19-JUL-10:55 | 46.45 | 06-JUL-01:00 |
August | 1169.53 | 01-AUG-00:10 | 597.59 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.31 | 14-AUG-10:55 | 42.33 | 28-AUG-03:00 |
September | 1169.53 | 01-SEP-00:10 | 597.59 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.71 | 29-SEP-11:00 | 56.31 | 20-SEP-03:00 |
October | 1169.53 | 01-OCT-23:10 | 597.59 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.60 | 16-OCT-11:00 | 68.36 | 30-OCT-03:00 |
November | 1169.53 | 01-NOV-00:10 | 597.59 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.39 | 19-NOV-13:00 | 82.98 | 29-NOV-23:00 |
December | 1169.53 | 01-DEC-00:10 | 597.59 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.36 | 16-DEC-13:00 | 88.86 | 22-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1169.53 | 597.59 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.33 | |||||
Maximum of Months | 1169.53 | 597.59 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 64.60 | 110.85 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 692.02 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.28 | 13-JAN-14:00 | 43.57 | 08-JAN-07:00 |
February | 1354.32 | 01-FEB-00:10 | 692.02 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.13 | 01-FEB-11:55 | 37.22 | 04-FEB-05:55 |
March | 1354.32 | 01-MAR-00:10 | 692.02 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.47 | 11-MAR-11:50 | 37.71 | 08-MAR-02:00 |
April | 1354.32 | 01-APR-00:10 | 692.02 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.93 | 26-APR-13:00 | 30.91 | 01-APR-06:00 |
May | 1354.32 | 01-MAY-00:10 | 692.02 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.16 | 03-MAY-12:00 | 31.29 | 19-MAY-05:00 |
June | 1354.32 | 01-JUN-00:10 | 692.02 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 29-JUN-10:55 | 25.13 | 13-JUN-05:00 |
July | 1354.32 | 01-JUL-00:10 | 692.02 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.04 | 19-JUL-10:55 | 21.82 | 06-JUL-01:00 |
August | 1354.32 | 01-AUG-00:10 | 692.02 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.97 | 14-AUG-10:55 | 19.61 | 28-AUG-06:00 |
September | 1354.32 | 01-SEP-00:10 | 692.02 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.35 | 29-SEP-10:55 | 25.64 | 20-SEP-03:00 |
October | 1354.32 | 01-OCT-23:10 | 692.02 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.66 | 16-OCT-10:55 | 30.04 | 27-OCT-04:30 |
November | 1354.32 | 01-NOV-00:10 | 692.02 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.68 | 19-NOV-13:00 | 35.56 | 29-NOV-23:00 |
December | 1354.32 | 01-DEC-00:10 | 692.02 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.92 | 16-DEC-13:00 | 36.86 | 03-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1354.32 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 3.16 | 19.61 | |||||
Maximum of Months | 1354.32 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 26.66 | 43.57 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 286.42 | 02-JAN-00:10 | 684.18 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.86 | 13-JAN-14:00 | 102.99 | 08-JAN-07:00 |
February | 286.42 | 01-FEB-00:10 | 684.18 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.96 | 01-FEB-11:55 | 85.26 | 04-FEB-05:55 |
March | 286.42 | 01-MAR-00:10 | 684.18 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.80 | 11-MAR-11:55 | 86.54 | 08-MAR-04:00 |
April | 286.42 | 01-APR-00:10 | 684.18 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.40 | 26-APR-13:00 | 70.14 | 01-APR-06:00 |
May | 286.42 | 01-MAY-00:10 | 684.18 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.71 | 03-MAY-12:00 | 71.38 | 27-MAY-03:00 |
June | 286.42 | 01-JUN-00:10 | 684.18 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.23 | 29-JUN-10:55 | 56.92 | 13-JUN-04:40 |
July | 286.42 | 01-JUL-00:10 | 684.18 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.40 | 19-JUL-10:55 | 49.13 | 06-JUL-01:00 |
August | 286.42 | 01-AUG-00:10 | 684.18 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.97 | 14-AUG-10:55 | 43.74 | 28-AUG-06:50 |
September | 286.42 | 01-SEP-00:10 | 684.18 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.47 | 29-SEP-10:55 | 56.93 | 20-SEP-03:00 |
October | 286.42 | 01-OCT-23:10 | 684.18 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 63.09 | 16-OCT-10:55 | 67.77 | 12-OCT-06:00 |
November | 286.42 | 01-NOV-00:10 | 684.18 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.55 | 19-NOV-13:00 | 79.37 | 29-NOV-23:00 |
December | 286.42 | 01-DEC-00:10 | 684.18 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.95 | 16-DEC-13:00 | 84.97 | 03-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 286.42 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 7.71 | 43.74 | |||||
Maximum of Months | 286.42 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 63.09 | 102.99 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 220.32 | 02-JAN-00:10 | 251.84 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.58 | 13-JAN-14:00 | 59.42 | 08-JAN-07:00 |
February | 220.32 | 01-FEB-00:10 | 251.84 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.09 | 01-FEB-11:55 | 48.49 | 04-FEB-05:55 |
March | 220.32 | 01-MAR-00:10 | 251.84 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.86 | 11-MAR-11:50 | 49.93 | 08-MAR-04:00 |
April | 220.32 | 01-APR-00:10 | 251.84 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.08 | 26-APR-13:00 | 40.47 | 01-APR-06:00 |
May | 220.32 | 01-MAY-00:10 | 251.84 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.71 | 03-MAY-12:00 | 40.37 | 27-MAY-03:00 |
June | 220.32 | 01-JUN-00:10 | 251.84 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 29-JUN-10:55 | 32.15 | 13-JUN-05:00 |
July | 220.32 | 01-JUL-00:10 | 251.84 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.36 | 19-JUL-10:55 | 27.55 | 06-JUL-01:00 |
August | 220.32 | 01-AUG-00:10 | 251.84 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.66 | 14-AUG-10:55 | 24.32 | 28-AUG-07:00 |
September | 220.32 | 01-SEP-00:10 | 251.84 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.87 | 29-SEP-10:55 | 32.16 | 20-SEP-03:00 |
October | 220.32 | 01-OCT-23:10 | 251.84 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.41 | 16-OCT-10:55 | 38.21 | 27-OCT-04:05 |
November | 220.32 | 01-NOV-00:10 | 251.84 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.52 | 19-NOV-13:00 | 44.48 | 29-NOV-23:00 |
December | 220.32 | 01-DEC-00:10 | 251.84 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.11 | 16-DEC-13:00 | 48.02 | 03-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 220.32 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 4.71 | 24.32 | |||||
Maximum of Months | 220.32 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 36.41 | 59.42 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 325.08 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 30.52 | 14-JAN-11:50 | 135.36 | 08-JAN-07:00 |
February | 907.20 | 01-FEB-00:10 | 325.08 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 27.37 | 01-FEB-11:55 | 116.36 | 06-FEB-23:00 |
March | 907.20 | 01-MAR-00:10 | 325.08 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 17.95 | 11-MAR-11:50 | 124.94 | 29-MAR-22:00 |
April | 907.20 | 01-APR-00:10 | 325.08 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 29.77 | 26-APR-13:00 | 102.04 | 15-APR-22:00 |
May | 907.20 | 01-MAY-00:10 | 325.08 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 12.75 | 04-MAY-12:00 | 99.60 | 15-MAY-05:08 |
June | 907.20 | 01-JUN-00:10 | 325.08 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 23.66 | 29-JUN-10:50 | 84.12 | 13-JUN-05:10 |
July | 907.20 | 01-JUL-00:10 | 325.08 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 42.72 | 19-JUL-10:50 | 65.37 | 08-JUL-24:00 |
August | 907.20 | 01-AUG-00:10 | 325.08 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 42.78 | 14-AUG-10:50 | 66.51 | 28-AUG-07:00 |
September | 907.20 | 01-SEP-00:10 | 325.08 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 91.74 | 29-SEP-10:50 | 80.65 | 20-SEP-06:00 |
October | 907.20 | 01-OCT-23:10 | 325.08 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 96.26 | 16-OCT-10:50 | 101.94 | 12-OCT-06:00 |
November | 907.20 | 01-NOV-00:10 | 325.08 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 29.69 | 19-NOV-13:10 | 116.82 | 23-NOV-22:00 |
December | 907.20 | 01-DEC-00:10 | 325.08 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 26.05 | 16-DEC-13:00 | 123.85 | 12-DEC-22:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 907.20 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 12.75 | 65.37 | ||||||
Maximum of Months | 907.20 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 96.26 | 135.36 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 1701.53 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.13 | 17-JAN-11:55 | 249.58 | 08-JAN-07:00 |
February | 15368.40 | 01-FEB-00:10 | 1701.53 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.74 | 01-FEB-12:00 | 212.50 | 04-FEB-05:55 |
March | 15368.40 | 01-MAR-00:10 | 1701.53 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 213.71 | 08-MAR-02:00 |
April | 15368.40 | 01-APR-00:10 | 1701.53 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.71 | 26-APR-13:00 | 174.94 | 04-APR-04:05 |
May | 15368.40 | 01-MAY-00:10 | 1701.53 | 01-MAY-19:10 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.14 | 03-MAY-12:00 | 179.30 | 19-MAY-05:00 |
June | 15368.40 | 01-JUN-00:10 | 1701.53 | 01-JUN-19:10 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.85 | 29-JUN-10:55 | 148.35 | 13-JUN-05:00 |
July | 15368.40 | 01-JUL-00:10 | 1701.53 | 03-JUL-19:10 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.17 | 19-JUL-10:55 | 126.32 | 06-JUL-01:00 |
August | 15368.40 | 01-AUG-00:10 | 1701.53 | 01-AUG-19:10 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 62.15 | 14-AUG-10:55 | 116.57 | 28-AUG-03:00 |
September | 15368.40 | 01-SEP-00:10 | 1701.53 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.00 | 29-SEP-10:55 | 150.74 | 20-SEP-03:00 |
October | 15368.40 | 01-OCT-23:10 | 1701.53 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 142.81 | 16-OCT-10:55 | 177.49 | 30-OCT-03:00 |
November | 15368.40 | 01-NOV-00:10 | 1701.53 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.02 | 19-NOV-13:00 | 202.32 | 29-NOV-23:00 |
December | 15368.40 | 01-DEC-00:10 | 1701.53 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.91 | 16-DEC-13:00 | 209.24 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 15368.40 | 1701.53 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.57 | |||||
Maximum of Months | 15368.40 | 1701.53 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 142.81 | 249.58 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 9504.80 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.46 | 13-JAN-14:00 | 712.96 | 08-JAN-07:00 |
February | 45622.98 | 01-FEB-00:10 | 9504.80 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.65 | 01-FEB-11:55 | 626.09 | 04-FEB-05:55 |
March | 45622.98 | 01-MAR-00:10 | 9504.80 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.74 | 11-MAR-11:50 | 631.70 | 08-MAR-02:00 |
April | 45622.98 | 01-APR-00:10 | 9504.80 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.64 | 26-APR-13:00 | 524.73 | 01-APR-06:00 |
May | 45622.98 | 01-MAY-00:10 | 9504.80 | 01-MAY-19:10 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.34 | 03-MAY-12:00 | 529.91 | 19-MAY-05:00 |
June | 45622.98 | 01-JUN-00:10 | 9504.80 | 01-JUN-19:10 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 92.23 | 29-JUN-10:55 | 435.84 | 13-JUN-05:00 |
July | 45622.98 | 01-JUL-00:10 | 9504.80 | 03-JUL-19:10 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 184.95 | 19-JUL-10:55 | 370.33 | 06-JUL-01:00 |
August | 45622.98 | 01-AUG-00:10 | 9504.80 | 01-AUG-19:10 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 182.13 | 14-AUG-10:55 | 336.15 | 28-AUG-05:00 |
September | 45622.98 | 01-SEP-00:10 | 9504.80 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 410.03 | 29-SEP-10:55 | 437.01 | 20-SEP-03:00 |
October | 45622.98 | 01-OCT-23:10 | 9504.80 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 429.33 | 16-OCT-10:55 | 511.52 | 27-OCT-04:30 |
November | 45622.98 | 01-NOV-00:10 | 9504.80 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 106.92 | 19-NOV-13:00 | 590.05 | 29-NOV-23:00 |
December | 45622.98 | 01-DEC-00:10 | 9504.80 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.84 | 16-DEC-13:00 | 613.32 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 45622.98 | 9504.80 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 41.74 | 336.15 | |||||
Maximum of Months | 45622.98 | 9504.80 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 429.33 | 712.96 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.88 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.55 | 14-JAN-11:00 | 66.02 | 08-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 177.88 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.56 | 01-FEB-09:51 | 51.94 | 04-FEB-05:55 |
March | 180.00 | 01-MAR-00:10 | 177.88 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.56 | 11-MAR-11:00 | 55.55 | 08-MAR-02:00 |
April | 180.00 | 01-APR-00:10 | 177.88 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.57 | 30-APR-10:00 | 45.11 | 01-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 177.88 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.59 | 03-MAY-10:00 | 42.01 | 15-MAY-02:00 |
June | 180.00 | 01-JUN-00:10 | 177.88 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.56 | 30-JUN-10:00 | 32.13 | 13-JUN-04:10 |
July | 180.00 | 01-JUL-00:10 | 177.88 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.41 | 19-JUL-10:00 | 25.46 | 06-JUL-01:00 |
August | 180.00 | 01-AUG-00:10 | 177.88 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.42 | 15-AUG-10:00 | 24.61 | 28-AUG-07:20 |
September | 180.00 | 01-SEP-00:10 | 177.88 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.11 | 29-SEP-10:00 | 31.90 | 20-SEP-03:10 |
October | 180.00 | 01-OCT-00:10 | 177.88 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.19 | 16-OCT-10:00 | 38.63 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 177.88 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.52 | 19-NOV-09:55 | 45.32 | 24-NOV-00:55 |
December | 180.00 | 01-DEC-00:10 | 177.88 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.54 | 05-DEC-10:00 | 52.06 | 22-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 5.59 | 24.61 | |||||
Maximum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 40.19 | 66.02 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.86 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.55 | 14-JAN-11:00 | 66.02 | 08-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 177.86 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.99 | 01-FEB-11:55 | 51.93 | 04-FEB-05:55 |
March | 180.00 | 01-MAR-00:10 | 177.86 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.56 | 11-MAR-11:00 | 55.55 | 08-MAR-04:00 |
April | 180.00 | 01-APR-00:10 | 177.86 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.57 | 30-APR-10:00 | 45.11 | 01-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 177.86 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.59 | 03-MAY-10:00 | 42.01 | 15-MAY-02:00 |
June | 180.00 | 01-JUN-00:10 | 177.86 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.56 | 30-JUN-10:00 | 32.12 | 13-JUN-04:10 |
July | 180.00 | 01-JUL-00:10 | 177.86 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.41 | 19-JUL-10:00 | 29.65 | 07-JUL-21:00 |
August | 180.00 | 01-AUG-00:10 | 177.86 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.42 | 15-AUG-10:00 | 28.79 | 26-AUG-18:00 |
September | 180.00 | 01-SEP-00:10 | 177.86 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.11 | 29-SEP-10:00 | 31.90 | 20-SEP-03:10 |
October | 180.00 | 01-OCT-00:10 | 177.86 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.38 | 16-OCT-10:01 | 38.63 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 177.86 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.52 | 19-NOV-09:58 | 45.32 | 24-NOV-00:55 |
December | 180.00 | 01-DEC-00:10 | 177.86 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.54 | 05-DEC-10:00 | 52.06 | 22-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 5.59 | 28.79 | |||||
Maximum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 40.38 | 66.02 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 111.79 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 22.81 | 08-JAN-07:00 |
February | 0.00 | 01-FEB-00:10 | 111.79 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 19.09 | 04-FEB-05:55 |
March | 0.00 | 01-MAR-00:10 | 111.79 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 19.88 | 08-MAR-02:00 |
April | 0.00 | 01-APR-00:10 | 111.79 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.24 | 26-APR-13:00 | 15.75 | 01-APR-06:00 |
May | 0.00 | 01-MAY-00:10 | 111.79 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 15.90 | 15-MAY-02:00 |
June | 0.00 | 01-JUN-00:10 | 111.79 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 13.31 | 13-JUN-04:20 |
July | 0.00 | 01-JUL-00:10 | 111.79 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.07 | 19-JUL-12:00 | 11.87 | 06-JUL-01:00 |
August | 0.00 | 01-AUG-00:10 | 111.79 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.07 | 18-AUG-12:00 | 11.02 | 24-AUG-02:00 |
September | 0.00 | 01-SEP-00:10 | 111.79 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.49 | 29-SEP-11:00 | 13.66 | 20-SEP-03:00 |
October | 0.00 | 01-OCT-00:10 | 111.79 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.28 | 16-OCT-10:55 | 15.69 | 12-OCT-06:00 |
November | 0.00 | 01-NOV-00:10 | 111.79 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.24 | 19-NOV-13:00 | 17.61 | 24-NOV-01:00 |
December | 0.00 | 01-DEC-00:10 | 111.79 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 19.52 | 22-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 0.00 | 111.79 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.02 | |||||
Maximum of Months | 0.00 | 111.79 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 8.28 | 22.81 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 111.82 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4.06 | 14-JAN-11:00 | 18.42 | 08-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 111.82 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.09 | 01-FEB-11:55 | 14.49 | 04-FEB-05:55 |
March | 180.00 | 01-MAR-00:10 | 111.82 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.39 | 11-MAR-11:00 | 15.50 | 08-MAR-02:00 |
April | 180.00 | 01-APR-00:10 | 111.82 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.87 | 26-APR-13:00 | 12.59 | 01-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 111.82 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.56 | 03-MAY-10:00 | 11.78 | 14-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 111.82 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.39 | 30-JUN-10:00 | 8.97 | 13-JUN-04:10 |
July | 180.00 | 01-JUL-00:10 | 111.82 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.86 | 19-JUL-10:00 | 7.89 | 07-JUL-21:00 |
August | 180.00 | 01-AUG-00:10 | 111.82 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.86 | 15-AUG-10:00 | 7.49 | 21-AUG-20:10 |
September | 180.00 | 01-SEP-00:10 | 111.82 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.20 | 29-SEP-10:00 | 8.90 | 20-SEP-03:10 |
October | 180.00 | 01-OCT-00:10 | 111.82 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.35 | 16-OCT-10:01 | 10.78 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 111.82 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.05 | 19-NOV-09:58 | 12.65 | 24-NOV-01:00 |
December | 180.00 | 01-DEC-00:10 | 111.82 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.06 | 05-DEC-10:00 | 14.53 | 22-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 1.56 | 7.49 | |||||
Maximum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 11.35 | 18.42 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.88 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.55 | 14-JAN-11:00 | 66.02 | 08-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 177.88 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.56 | 01-FEB-10:00 | 51.94 | 04-FEB-05:55 |
March | 180.00 | 01-MAR-00:10 | 177.88 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.56 | 11-MAR-11:00 | 55.55 | 08-MAR-04:00 |
April | 180.00 | 01-APR-00:10 | 177.88 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.57 | 30-APR-10:00 | 45.11 | 01-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 177.88 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.58 | 03-MAY-10:00 | 42.01 | 15-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 177.88 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.56 | 26-JUN-10:00 | 32.13 | 13-JUN-04:10 |
July | 180.00 | 01-JUL-00:10 | 177.88 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.41 | 19-JUL-10:00 | 25.46 | 06-JUL-01:00 |
August | 180.00 | 01-AUG-00:10 | 177.88 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.42 | 15-AUG-10:00 | 26.94 | 28-AUG-07:20 |
September | 180.00 | 01-SEP-00:10 | 177.88 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.11 | 29-SEP-10:00 | 31.90 | 20-SEP-03:10 |
October | 180.00 | 01-OCT-00:10 | 177.88 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.19 | 16-OCT-10:00 | 38.63 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 177.88 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.52 | 19-NOV-10:00 | 45.32 | 24-NOV-00:55 |
December | 180.00 | 01-DEC-00:10 | 177.88 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.54 | 05-DEC-10:00 | 52.06 | 22-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 5.58 | 25.46 | |||||
Maximum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 40.19 | 66.02 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.86 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.55 | 14-JAN-11:00 | 66.01 | 08-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 177.86 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.56 | 01-FEB-10:00 | 51.93 | 04-FEB-05:55 |
March | 180.00 | 01-MAR-00:10 | 177.86 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.56 | 11-MAR-11:00 | 55.55 | 08-MAR-02:00 |
April | 180.00 | 01-APR-00:10 | 177.86 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.56 | 30-APR-10:00 | 45.11 | 01-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 177.86 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.58 | 03-MAY-10:00 | 42.01 | 15-MAY-02:00 |
June | 180.00 | 01-JUN-00:10 | 177.86 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.56 | 30-JUN-10:00 | 32.12 | 13-JUN-04:10 |
July | 180.00 | 01-JUL-00:10 | 177.86 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.41 | 19-JUL-10:00 | 26.90 | 07-JUL-21:00 |
August | 180.00 | 01-AUG-00:10 | 177.86 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.42 | 15-AUG-10:00 | 29.10 | 26-AUG-08:00 |
September | 180.00 | 01-SEP-00:10 | 177.86 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.11 | 29-SEP-10:00 | 31.90 | 20-SEP-03:10 |
October | 180.00 | 01-OCT-00:10 | 177.86 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.19 | 16-OCT-10:00 | 38.63 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 177.86 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.51 | 19-NOV-10:00 | 45.32 | 24-NOV-00:55 |
December | 180.00 | 01-DEC-00:10 | 177.86 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.53 | 05-DEC-10:00 | 52.06 | 22-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 5.58 | 26.90 | |||||
Maximum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 40.19 | 66.01 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2263.36 | 02-JAN-00:10 | 1867.32 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.22 | 13-JAN-14:00 | 79.40 | 08-JAN-07:00 |
February | 2263.36 | 01-FEB-00:10 | 1867.32 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.38 | 01-FEB-11:55 | 65.52 | 04-FEB-05:55 |
March | 2263.36 | 01-MAR-00:10 | 1867.32 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.94 | 11-MAR-11:50 | 66.74 | 08-MAR-02:00 |
April | 2263.36 | 01-APR-00:10 | 1867.32 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.29 | 26-APR-13:00 | 54.13 | 01-APR-06:00 |
May | 2263.36 | 01-MAY-00:10 | 1867.32 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.08 | 03-MAY-12:00 | 53.92 | 27-MAY-03:00 |
June | 2263.36 | 01-JUN-00:10 | 1867.32 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.47 | 29-JUN-10:55 | 42.57 | 13-JUN-05:00 |
July | 2263.36 | 01-JUL-00:10 | 1867.32 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.70 | 19-JUL-10:55 | 36.92 | 06-JUL-01:00 |
August | 2263.36 | 01-AUG-00:10 | 1867.32 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.41 | 14-AUG-10:55 | 33.04 | 24-AUG-02:00 |
September | 2263.36 | 01-SEP-00:10 | 1867.32 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.30 | 29-SEP-10:55 | 43.35 | 20-SEP-03:00 |
October | 2263.36 | 01-OCT-23:10 | 1867.32 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.40 | 16-OCT-10:55 | 51.68 | 30-OCT-03:00 |
November | 2263.36 | 01-NOV-00:10 | 1867.32 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.95 | 19-NOV-13:00 | 59.58 | 29-NOV-23:00 |
December | 2263.36 | 01-DEC-00:10 | 1867.32 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.84 | 16-DEC-13:00 | 64.97 | 03-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.08 | 33.04 | ||||
Maximum of Months | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.40 | 79.40 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.88 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.38 | 14-JAN-11:00 | 66.23 | 08-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 177.88 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.38 | 01-FEB-09:51 | 52.14 | 04-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 177.88 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.39 | 11-MAR-11:00 | 55.76 | 08-MAR-04:00 |
April | 180.00 | 01-APR-00:10 | 177.88 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.39 | 30-APR-10:00 | 45.31 | 01-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 177.88 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.41 | 03-MAY-10:00 | 42.21 | 15-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 177.88 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.39 | 26-JUN-10:00 | 32.32 | 13-JUN-04:10 |
July | 180.00 | 01-JUL-00:10 | 177.88 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.24 | 19-JUL-10:00 | 25.65 | 06-JUL-01:00 |
August | 180.00 | 01-AUG-00:10 | 177.88 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.24 | 15-AUG-10:00 | 24.02 | 28-AUG-07:20 |
September | 180.00 | 01-SEP-00:10 | 177.88 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.95 | 29-SEP-10:00 | 32.10 | 20-SEP-03:10 |
October | 180.00 | 01-OCT-00:10 | 177.88 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.03 | 16-OCT-10:00 | 38.83 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 177.88 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.34 | 19-NOV-09:53 | 45.52 | 24-NOV-00:55 |
December | 180.00 | 01-DEC-00:10 | 177.88 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.37 | 05-DEC-09:55 | 52.26 | 22-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 5.41 | 24.02 | |||||
Maximum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 40.03 | 66.23 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.86 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.38 | 14-JAN-11:00 | 66.22 | 08-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 177.86 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.04 | 01-FEB-11:55 | 52.13 | 04-FEB-05:55 |
March | 180.00 | 01-MAR-00:10 | 177.86 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.39 | 11-MAR-11:00 | 55.75 | 08-MAR-04:00 |
April | 180.00 | 01-APR-00:10 | 177.86 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.39 | 30-APR-10:00 | 45.31 | 01-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 177.86 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.41 | 03-MAY-10:00 | 42.20 | 15-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 177.86 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.39 | 30-JUN-10:00 | 33.13 | 02-JUN-20:00 |
July | 180.00 | 01-JUL-00:10 | 177.86 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.24 | 19-JUL-10:00 | 31.63 | 10-JUL-18:01 |
August | 180.00 | 01-AUG-00:10 | 177.86 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.24 | 15-AUG-10:00 | 30.76 | 26-AUG-18:00 |
September | 180.00 | 01-SEP-00:10 | 177.86 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.95 | 29-SEP-10:00 | 32.09 | 20-SEP-03:10 |
October | 180.00 | 01-OCT-00:10 | 177.86 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.18 | 16-OCT-10:01 | 38.82 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 177.86 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.34 | 19-NOV-10:00 | 45.52 | 24-NOV-00:55 |
December | 180.00 | 01-DEC-00:10 | 177.86 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.37 | 05-DEC-10:00 | 52.26 | 22-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 5.41 | 30.76 | |||||
Maximum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 40.18 | 66.22 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 111.82 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7.36 | 14-JAN-11:00 | 33.88 | 08-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 111.82 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.29 | 01-FEB-09:51 | 26.68 | 04-FEB-05:55 |
March | 180.00 | 01-MAR-00:10 | 111.82 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.29 | 11-MAR-11:00 | 28.53 | 08-MAR-02:00 |
April | 180.00 | 01-APR-00:10 | 111.82 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 30-APR-10:00 | 23.18 | 01-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 111.82 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.77 | 03-MAY-10:00 | 21.59 | 15-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 111.82 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.29 | 30-JUN-10:00 | 16.54 | 13-JUN-04:10 |
July | 180.00 | 01-JUL-00:10 | 111.82 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.82 | 19-JUL-10:00 | 13.12 | 06-JUL-01:00 |
August | 180.00 | 01-AUG-00:10 | 111.82 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.82 | 15-AUG-10:00 | 12.56 | 28-AUG-07:20 |
September | 180.00 | 01-SEP-00:10 | 111.82 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.44 | 29-SEP-10:00 | 16.42 | 20-SEP-03:10 |
October | 180.00 | 01-OCT-00:10 | 111.82 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.48 | 16-OCT-10:00 | 19.86 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 111.82 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.97 | 19-NOV-10:30 | 23.39 | 30-NOV-02:30 |
December | 180.00 | 01-DEC-00:10 | 111.82 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.35 | 05-DEC-10:00 | 26.74 | 22-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 2.77 | 12.56 | |||||
Maximum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 20.48 | 33.88 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2988.03 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.96 | 13-JAN-14:00 | 163.18 | 08-JAN-07:00 |
February | 26988.77 | 01-FEB-00:10 | 2988.03 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.20 | 01-FEB-11:55 | 145.33 | 04-FEB-05:55 |
March | 26988.77 | 01-MAR-00:10 | 2988.03 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 11-MAR-11:50 | 149.41 | 08-MAR-02:00 |
April | 26988.77 | 01-APR-00:10 | 2988.03 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.11 | 26-APR-13:00 | 130.28 | 01-APR-06:00 |
May | 26988.77 | 01-MAY-00:10 | 2988.03 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.20 | 03-MAY-12:00 | 125.54 | 15-MAY-02:00 |
June | 26988.77 | 01-JUN-00:10 | 2988.03 | 01-JUN-19:10 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.23 | 29-JUN-10:55 | 101.21 | 13-JUN-04:10 |
July | 26988.77 | 01-JUL-00:10 | 2988.03 | 03-JUL-19:10 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.77 | 19-JUL-10:55 | 84.60 | 06-JUL-01:00 |
August | 26988.77 | 01-AUG-00:10 | 2988.03 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.22 | 14-AUG-10:55 | 76.64 | 31-AUG-04:00 |
September | 26988.77 | 01-SEP-00:10 | 2988.03 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.79 | 29-SEP-10:50 | 100.51 | 20-SEP-03:10 |
October | 26988.77 | 01-OCT-23:10 | 2988.03 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.69 | 16-OCT-10:55 | 117.18 | 30-OCT-04:00 |
November | 26988.77 | 01-NOV-00:10 | 2988.03 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.37 | 19-NOV-13:00 | 133.69 | 23-NOV-22:00 |
December | 26988.77 | 01-DEC-00:10 | 2988.03 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.46 | 19-DEC-13:00 | 143.37 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 3.20 | 76.64 | |||||
Maximum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 95.69 | 163.18 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2988.03 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.52 | 13-JAN-14:00 | 164.17 | 08-JAN-07:00 |
February | 26988.77 | 01-FEB-00:10 | 2988.03 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.98 | 01-FEB-11:55 | 146.14 | 04-FEB-05:55 |
March | 26988.77 | 01-MAR-00:10 | 2988.03 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.75 | 11-MAR-11:50 | 150.84 | 08-MAR-02:00 |
April | 26988.77 | 01-APR-00:10 | 2988.03 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.17 | 26-APR-13:00 | 131.92 | 01-APR-06:00 |
May | 26988.77 | 01-MAY-00:10 | 2988.03 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.39 | 03-MAY-12:00 | 125.54 | 15-MAY-05:00 |
June | 26988.77 | 01-JUN-00:10 | 2988.03 | 01-JUN-19:10 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.57 | 29-JUN-10:55 | 101.21 | 13-JUN-04:10 |
July | 26988.77 | 01-JUL-00:10 | 2988.03 | 03-JUL-19:10 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.16 | 19-JUL-10:55 | 84.60 | 06-JUL-01:00 |
August | 26988.77 | 01-AUG-00:10 | 2988.03 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.64 | 14-AUG-10:55 | 76.65 | 31-AUG-04:00 |
September | 26988.77 | 01-SEP-00:10 | 2988.03 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.33 | 29-SEP-10:50 | 100.51 | 20-SEP-03:10 |
October | 26988.77 | 01-OCT-23:10 | 2988.03 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.53 | 16-OCT-10:55 | 117.18 | 30-OCT-04:00 |
November | 26988.77 | 01-NOV-00:10 | 2988.03 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.76 | 19-NOV-13:00 | 133.72 | 24-NOV-01:00 |
December | 26988.77 | 01-DEC-00:10 | 2988.03 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.62 | 19-DEC-13:00 | 144.62 | 22-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 1.39 | 76.65 | |||||
Maximum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 94.53 | 164.17 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 1060.81 | 02-JAN-20:10 | 14912.86 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 12.53 | 14-JAN-11:00 | 144.76 | 03-JAN-07:10 |
February | 2401.70 | 01-FEB-00:10 | 1060.81 | 01-FEB-20:10 | 14912.86 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 12.45 | 01-FEB-11:55 | 121.89 | 09-FEB-07:00 |
March | 2401.70 | 01-MAR-00:10 | 1060.81 | 01-MAR-20:10 | 14912.86 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 131.56 | 29-MAR-22:50 |
April | 2401.70 | 01-APR-00:10 | 1060.81 | 03-APR-19:10 | 14912.86 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 18.92 | 26-APR-13:00 | 119.08 | 01-APR-06:00 |
May | 2401.70 | 01-MAY-00:10 | 1060.81 | 01-MAY-19:10 | 14912.86 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 111.95 | 19-MAY-05:00 |
June | 2401.70 | 01-JUN-00:10 | 1060.81 | 01-JUN-19:10 | 14912.86 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 5.95 | 29-JUN-10:55 | 90.61 | 13-JUN-04:10 |
July | 2401.70 | 01-JUL-00:10 | 1060.81 | 03-JUL-19:10 | 14912.86 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 25.38 | 19-JUL-12:00 | 72.04 | 06-JUL-01:00 |
August | 2401.70 | 01-AUG-00:10 | 1060.81 | 01-AUG-19:10 | 14912.86 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 25.44 | 18-AUG-12:00 | 68.40 | 28-AUG-06:10 |
September | 2401.70 | 01-SEP-00:10 | 1060.81 | 01-SEP-19:10 | 14912.86 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 75.18 | 29-SEP-11:20 | 86.16 | 20-SEP-03:30 |
October | 2401.70 | 01-OCT-23:10 | 1060.81 | 02-OCT-19:10 | 14912.86 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 81.37 | 16-OCT-11:00 | 104.78 | 12-OCT-06:00 |
November | 2401.70 | 01-NOV-00:10 | 1060.81 | 01-NOV-19:10 | 14912.86 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 18.95 | 19-NOV-13:00 | 119.64 | 23-NOV-22:00 |
December | 2401.70 | 01-DEC-00:10 | 1060.81 | 01-DEC-20:10 | 14912.86 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 12.57 | 16-DEC-13:00 | 134.53 | 22-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2401.70 | 1060.81 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 0.00 | 68.40 | ||||||
Maximum of Months | 2401.70 | 1060.81 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 81.37 | 144.76 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2395.44 | 02-JAN-00:10 | 1976.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.25 | 14-JAN-11:00 | 140.60 | 08-JAN-07:00 |
February | 2395.44 | 01-FEB-00:10 | 1976.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.61 | 01-FEB-11:55 | 111.23 | 04-FEB-05:55 |
March | 2395.44 | 01-MAR-00:10 | 1976.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.70 | 11-MAR-11:00 | 118.53 | 08-MAR-04:00 |
April | 2395.44 | 01-APR-00:10 | 1976.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.08 | 26-APR-13:00 | 96.19 | 01-APR-06:00 |
May | 2395.44 | 01-MAY-00:10 | 1976.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.97 | 03-MAY-12:00 | 92.78 | 27-MAY-03:00 |
June | 2395.44 | 01-JUN-00:10 | 1976.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.15 | 29-JUN-10:55 | 73.63 | 13-JUN-04:05 |
July | 2395.44 | 01-JUL-00:10 | 1976.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.44 | 19-JUL-10:55 | 64.07 | 06-JUL-01:00 |
August | 2395.44 | 01-AUG-00:10 | 1976.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.16 | 14-AUG-10:55 | 57.47 | 28-AUG-03:00 |
September | 2395.44 | 01-SEP-00:10 | 1976.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.34 | 29-SEP-10:55 | 74.05 | 20-SEP-03:00 |
October | 2395.44 | 01-OCT-23:10 | 1976.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.13 | 16-OCT-10:55 | 88.30 | 30-OCT-03:00 |
November | 2395.44 | 01-NOV-00:10 | 1976.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.86 | 19-NOV-13:00 | 103.24 | 29-NOV-23:00 |
December | 2395.44 | 01-DEC-00:10 | 1976.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.27 | 16-DEC-13:00 | 111.08 | 22-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.97 | 57.47 | ||||
Maximum of Months | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.13 | 140.60 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 22096.14 | 08-JAN-07:00 | 8945.92 | 4396.77 | 4055.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17115.76 | 04-FEB-05:55 | 23003.78 | 2931.30 | 4055.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17505.81 | 08-MAR-02:00 | 11501.89 | 2198.39 | 2534.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 14895.94 | 30-APR-10:33 | 11501.89 | 13190.31 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 14628.35 | 28-MAY-10:33 | 11501.89 | 13190.31 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 14788.29 | 25-JUN-10:33 | 11501.89 | 13190.31 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 15672.76 | 23-JUL-10:33 | 11501.89 | 13190.31 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 15659.67 | 13-AUG-10:33 | 11501.89 | 13190.31 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16160.27 | 30-SEP-10:33 | 11501.89 | 10992.10 | 10646.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16934.47 | 20-OCT-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17164.12 | 22-NOV-22:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 18090.57 | 03-DEC-01:00 | 8945.92 | 4396.77 | 4055.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 14628.35 | 8945.92 | 2198.39 | 2534.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22096.14 | 23003.78 | 13190.31 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3252.13 | 14-JAN-12:40 | 389.84 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 6.88 | 0.00 |
February | 2915.66 | 02-FEB-12:40 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.59 |
March | 2533.58 | 11-MAR-13:00 | 389.84 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
April | 2013.49 | 08-APR-10:33 | 1169.53 | 497.99 | 757.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.34 |
May | 1951.60 | 04-MAY-10:33 | 779.69 | 497.99 | 757.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.96 |
June | 1872.57 | 25-JUN-10:33 | 1169.53 | 597.59 | 866.03 | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 0.00 |
July | 2049.32 | 30-JUL-10:33 | 1169.53 | 597.59 | 866.03 | 0.00 | 0.00 | 0.00 | 0.00 | 9.72 | 0.00 |
August | 2128.66 | 27-AUG-10:33 | 1169.53 | 597.59 | 866.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 | 0.00 |
September | 3414.99 | 30-SEP-13:10 | 779.69 | 332.00 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 40.17 | 0.00 |
October | 4013.08 | 16-OCT-12:20 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 56.73 | 0.00 |
November | 3608.33 | 19-NOV-12:30 | 389.84 | 199.20 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 12.85 | 0.00 |
December | 3443.73 | 19-DEC-12:50 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 9.45 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1872.57 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4013.08 | 1169.53 | 597.59 | 866.03 | 0.00 | 0.00 | 0.00 | 0.00 | 56.73 | 24.59 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1699.75 | 28-JAN-07:00 | 1053.36 | 230.67 | 334.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.75 |
February | 1571.06 | 04-FEB-05:55 | 2708.64 | 153.78 | 334.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.22 |
March | 1584.46 | 08-MAR-02:00 | 1354.32 | 115.34 | 208.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.71 |
April | 1523.18 | 27-APR-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.73 |
May | 1526.23 | 03-MAY-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.52 |
June | 1573.99 | 30-JUN-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.44 |
July | 1672.24 | 31-JUL-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.18 |
August | 1738.65 | 18-AUG-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.19 |
September | 1926.60 | 29-SEP-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 1.19 | 0.00 |
October | 1981.03 | 16-OCT-20:10 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.08 |
November | 1558.66 | 29-NOV-23:00 | 1354.32 | 461.34 | 585.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.56 |
December | 1558.75 | 03-DEC-01:00 | 1053.36 | 230.67 | 334.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.86 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1523.18 | 1053.36 | 115.34 | 208.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1981.03 | 2708.64 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 1.19 | 39.75 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1322.24 | 28-JAN-07:00 | 222.77 | 228.06 | 353.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.71 |
February | 1183.71 | 04-FEB-05:55 | 572.83 | 152.04 | 353.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.26 |
March | 1126.41 | 08-MAR-01:20 | 286.42 | 114.03 | 220.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.01 |
April | 1108.41 | 30-APR-10:33 | 286.42 | 684.18 | 1060.35 | 0.00 | 0.00 | 0.00 | 0.00 | 16.01 | 0.00 |
May | 1124.20 | 04-MAY-10:33 | 190.94 | 570.15 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.44 |
June | 1168.36 | 25-JUN-10:33 | 286.42 | 684.18 | 1060.35 | 0.00 | 0.00 | 0.00 | 0.00 | 1.25 | 0.00 |
July | 1217.55 | 23-JUL-10:33 | 286.42 | 684.18 | 1060.35 | 0.00 | 0.00 | 0.00 | 0.00 | 12.72 | 0.00 |
August | 1208.98 | 19-AUG-10:33 | 286.42 | 570.15 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 8.14 | 0.00 |
September | 1236.64 | 30-SEP-10:33 | 286.42 | 570.15 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 34.02 | 0.00 |
October | 1229.55 | 17-OCT-10:33 | 190.94 | 570.15 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 35.95 | 0.00 |
November | 1126.39 | 29-NOV-23:00 | 286.42 | 456.12 | 618.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.37 |
December | 1187.86 | 03-DEC-01:00 | 222.77 | 228.06 | 353.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.97 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1108.41 | 190.94 | 114.03 | 220.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1322.24 | 572.83 | 684.18 | 1060.35 | 0.00 | 0.00 | 0.00 | 0.00 | 35.95 | 92.71 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 723.67 | 27-JAN-04:55 | 440.64 | 55.97 | 101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.81 |
February | 678.17 | 04-FEB-05:55 | 440.64 | 55.97 | 101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.49 |
March | 607.69 | 19-MAR-10:33 | 220.32 | 251.83 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.87 |
April | 642.74 | 30-APR-10:33 | 220.32 | 251.83 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 9.54 | 0.00 |
May | 651.95 | 04-MAY-10:33 | 146.88 | 209.86 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.10 |
June | 675.65 | 25-JUN-10:33 | 220.32 | 251.83 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 1.12 | 0.00 |
July | 705.58 | 23-JUL-10:33 | 220.32 | 251.83 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 7.69 | 0.00 |
August | 699.80 | 19-AUG-10:33 | 220.32 | 209.86 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 5.07 | 0.00 |
September | 720.98 | 30-SEP-10:33 | 220.32 | 209.86 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 19.81 | 0.00 |
October | 719.17 | 16-OCT-10:33 | 146.88 | 209.86 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 34.60 | 0.00 |
November | 639.91 | 19-NOV-11:33 | 220.32 | 251.83 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 9.92 | 0.00 |
December | 673.32 | 03-DEC-01:00 | 171.36 | 83.94 | 101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 607.69 | 146.88 | 55.97 | 101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 723.67 | 440.64 | 251.83 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 34.60 | 50.81 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 37557.13 | 24-JAN-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 46.50 |
February | 37484.34 | 03-FEB-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 73.97 |
March | 37673.09 | 23-MAR-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 66.83 |
April | 37921.70 | 26-APR-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 46.31 |
May | 37942.09 | 04-MAY-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 46.36 |
June | 37958.08 | 30-JUN-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 53.06 |
July | 38179.60 | 19-JUL-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 32.85 |
August | 38141.66 | 18-AUG-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 32.88 |
September | 38380.00 | 29-SEP-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 6.40 | 0.00 |
October | 38262.23 | 16-OCT-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 19.55 |
November | 37486.70 | 28-NOV-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 74.10 |
December | 37691.77 | 05-DEC-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 53.31 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 37484.34 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 38380.00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 6.40 | 74.10 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12721.45 | 14-JAN-12:40 | 5122.80 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 15.23 | 0.00 |
February | 10948.50 | 20-FEB-11:00 | 8538.00 | 124.78 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.99 |
March | 10509.78 | 11-MAR-12:50 | 5122.80 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
April | 9195.35 | 08-APR-10:33 | 15368.40 | 311.95 | 1066.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.52 |
May | 8849.59 | 04-MAY-21:20 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.18 |
June | 8628.66 | 25-JUN-10:33 | 15368.40 | 374.34 | 1219.29 | 0.00 | 0.00 | 0.00 | 0.00 | 6.87 | 0.00 |
July | 9217.26 | 30-JUL-10:33 | 15368.40 | 374.34 | 1219.29 | 0.00 | 0.00 | 0.00 | 0.00 | 19.76 | 0.00 |
August | 9554.66 | 27-AUG-10:33 | 15368.40 | 374.34 | 1219.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.62 |
September | 12058.51 | 30-SEP-12:00 | 5122.80 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 88.92 | 0.00 |
October | 13677.65 | 15-OCT-12:00 | 5122.80 | 124.78 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 89.34 | 0.00 |
November | 14055.17 | 19-NOV-11:00 | 8538.00 | 124.78 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 22.79 | 0.00 |
December | 12574.26 | 16-DEC-13:00 | 5122.80 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 22.91 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8628.66 | 5122.80 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14055.17 | 15368.40 | 1134.35 | 1219.29 | 0.00 | 0.00 | 0.00 | 0.00 | 89.34 | 93.99 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 37648.63 | 09-JAN-05:55 | 91245.96 | 4224.36 | 6334.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 690.92 |
February | 33715.83 | 04-FEB-05:55 | 91245.96 | 2112.18 | 4222.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 626.09 |
March | 33763.26 | 08-MAR-02:00 | 45622.98 | 1584.13 | 2639.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 631.70 |
April | 31533.75 | 26-APR-21:52 | 364983.84 | 50692.26 | 59119.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 269.59 |
May | 32428.36 | 04-MAY-21:53 | 319360.86 | 44355.73 | 51729.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.04 |
June | 32339.04 | 30-JUN-21:52 | 410606.82 | 57028.80 | 66509.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 265.64 |
July | 33679.59 | 19-JUL-21:52 | 364983.84 | 50692.26 | 59119.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.49 |
August | 34316.62 | 18-AUG-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.64 |
September | 38050.84 | 29-SEP-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 18.97 | 0.00 |
October | 38779.30 | 16-OCT-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.94 |
November | 33022.84 | 20-NOV-22:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 339.42 |
December | 34111.01 | 05-DEC-22:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 229.90 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 31533.75 | 45622.98 | 1584.13 | 2639.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 38779.30 | 410606.82 | 57028.80 | 66509.49 | 0.00 | 0.00 | 0.00 | 0.00 | 18.97 | 690.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3272.60 | 14-JAN-16:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 1.40 | 0.00 |
February | 3284.55 | 03-FEB-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.42 |
March | 2881.82 | 05-MAR-16:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.49 |
April | 3051.25 | 01-APR-18:02 | 702.00 | 1067.29 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.16 |
May | 2995.73 | 24-MAY-08:62 | 216.00 | 469.61 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.86 |
June | 2969.15 | 28-JUN-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.23 |
July | 2977.48 | 27-JUL-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.16 |
August | 2961.18 | 17-AUG-18:02 | 831.60 | 949.89 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.46 |
September | 2920.29 | 24-SEP-15:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.32 |
October | 3317.95 | 14-OCT-08:61 | 540.00 | 996.14 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 14.80 | 0.00 |
November | 3245.74 | 27-NOV-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.72 |
December | 3283.86 | 19-DEC-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.89 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2881.82 | 216.00 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3317.95 | 970.20 | 1108.21 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 14.80 | 24.49 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3136.29 | 15-JAN-16:01 | 378.00 | 410.86 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.92 |
February | 3145.55 | 03-FEB-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.18 |
March | 2849.82 | 24-MAR-15:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.25 |
April | 3120.74 | 19-APR-18:01 | 1386.00 | 1582.97 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.10 |
May | 3048.38 | 24-MAY-08:51 | 360.00 | 782.59 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.59 |
June | 2898.64 | 22-JUN-20:11 | 1602.00 | 1582.97 | 1817.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.09 |
July | 2806.27 | 09-JUL-21:51 | 1247.40 | 1360.64 | 805.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.36 |
August | 2783.67 | 05-AUG-15:01 | 378.00 | 410.86 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.08 | 0.00 |
September | 2859.97 | 18-SEP-15:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.68 |
October | 3318.62 | 14-OCT-08:61 | 540.00 | 996.02 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 13.16 | 0.00 |
November | 3110.18 | 27-NOV-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 |
December | 3145.30 | 19-DEC-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.65 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2783.67 | 360.00 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3318.62 | 1602.00 | 1582.97 | 1817.24 | 0.00 | 0.00 | 0.00 | 0.00 | 13.16 | 32.10 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 576.52 | 14-JAN-12:40 | 0.00 | 36.89 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.16 |
February | 506.55 | 02-FEB-12:30 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.14 |
March | 429.68 | 11-MAR-13:10 | 0.00 | 36.89 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.28 |
April | 302.19 | 08-APR-12:50 | 0.00 | 36.89 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.85 |
May | 256.16 | 03-MAY-15:03 | 0.00 | 219.11 | 343.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.14 |
June | 222.64 | 30-JUN-15:06 | 0.00 | 219.11 | 343.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 |
July | 265.41 | 19-JUL-15:03 | 0.00 | 187.81 | 294.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
August | 286.55 | 30-AUG-13:00 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.28 |
September | 533.06 | 30-SEP-13:05 | 0.00 | 73.78 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 4.30 | 0.00 |
October | 641.98 | 16-OCT-12:20 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 0.00 |
November | 609.24 | 19-NOV-09:58 | 0.00 | 250.41 | 639.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
December | 588.24 | 19-DEC-13:00 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 222.64 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 641.98 | 0.00 | 250.41 | 639.82 | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 6.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1093.77 | 15-JAN-16:01 | 378.00 | 258.31 | 379.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.48 |
February | 1060.00 | 03-FEB-16:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.30 |
March | 973.56 | 04-MAR-09:01 | 378.00 | 438.35 | 1119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.37 |
April | 1050.39 | 02-APR-08:51 | 540.00 | 626.21 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.52 |
May | 1055.46 | 24-MAY-08:51 | 360.00 | 492.02 | 1109.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.52 |
June | 1025.16 | 22-JUN-20:11 | 1602.00 | 995.22 | 1780.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.46 |
July | 1038.95 | 04-JUL-08:51 | 540.00 | 626.21 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.91 |
August | 1006.39 | 22-AUG-15:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.74 |
September | 1007.96 | 01-SEP-15:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.87 |
October | 1174.61 | 14-OCT-08:61 | 540.00 | 626.21 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 3.53 | 0.00 |
November | 1080.05 | 19-NOV-09:41 | 486.00 | 563.59 | 1439.98 | 0.00 | 0.00 | 0.00 | 0.00 | 2.93 | 0.00 |
December | 1089.33 | 05-DEC-16:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 973.56 | 360.00 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1174.61 | 1602.00 | 995.22 | 1780.62 | 0.00 | 0.00 | 0.00 | 0.00 | 3.53 | 7.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2934.84 | 14-JAN-16:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 1.35 | 0.00 |
February | 2930.11 | 03-FEB-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.31 |
March | 2599.48 | 24-MAR-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.21 |
April | 2896.14 | 02-APR-08:62 | 324.00 | 597.68 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.04 |
May | 2904.35 | 24-MAY-08:62 | 216.00 | 469.61 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.99 |
June | 2675.65 | 26-JUN-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.99 |
July | 2720.74 | 19-JUL-08:61 | 252.00 | 547.88 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 |
August | 2725.10 | 14-AUG-08:61 | 252.00 | 547.88 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 1.57 | 0.00 |
September | 2651.35 | 04-SEP-15:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.47 |
October | 3026.42 | 14-OCT-08:61 | 540.00 | 996.14 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 14.21 | 0.00 |
November | 2952.51 | 27-NOV-09:01 | 252.00 | 547.88 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.49 |
December | 2972.27 | 05-DEC-09:01 | 252.00 | 547.88 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 4.95 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2599.48 | 216.00 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3026.42 | 680.40 | 996.14 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 14.21 | 16.04 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2798.62 | 14-JAN-16:01 | 378.00 | 410.86 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 0.00 |
February | 2863.66 | 03-FEB-09:51 | 252.00 | 547.81 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.31 |
March | 2767.83 | 23-MAR-08:51 | 324.00 | 704.33 | 1019.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.85 |
April | 3108.15 | 02-APR-08:51 | 540.00 | 996.02 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.28 |
May | 3191.52 | 24-MAY-08:51 | 360.00 | 782.59 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.91 |
June | 2986.79 | 23-JUN-08:51 | 360.00 | 782.59 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.34 |
July | 2957.70 | 04-JUL-08:51 | 540.00 | 996.02 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.31 |
August | 2885.16 | 22-AUG-08:51 | 360.00 | 782.59 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.67 |
September | 2912.60 | 12-SEP-08:51 | 360.00 | 782.59 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.85 |
October | 3389.84 | 17-OCT-08:21 | 360.00 | 782.59 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 6.41 | 0.00 |
November | 2825.52 | 28-NOV-09:51 | 252.00 | 547.81 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.74 |
December | 3049.44 | 05-DEC-09:41 | 324.00 | 704.33 | 1019.23 | 0.00 | 0.00 | 0.00 | 0.00 | 6.16 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2767.83 | 252.00 | 410.86 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3389.84 | 540.00 | 996.02 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 6.41 | 19.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2596.68 | 28-JAN-07:00 | 1760.39 | 622.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.38 |
February | 2317.31 | 04-FEB-05:55 | 4526.71 | 414.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.52 |
March | 2255.54 | 08-MAR-01:30 | 2263.36 | 311.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.75 |
April | 2161.93 | 30-APR-10:33 | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.47 | 0.00 |
May | 2168.59 | 04-MAY-10:33 | 1508.90 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.36 |
June | 2231.77 | 25-JUN-10:33 | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.86 | 0.00 |
July | 2325.59 | 23-JUL-10:33 | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.72 | 0.00 |
August | 2343.00 | 19-AUG-10:33 | 2263.36 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.66 | 0.00 |
September | 2397.46 | 30-SEP-10:33 | 2263.36 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.57 | 0.00 |
October | 2413.39 | 17-OCT-10:33 | 1508.90 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.60 | 0.00 |
November | 2173.64 | 19-NOV-11:33 | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.65 | 0.00 |
December | 2304.75 | 03-DEC-01:00 | 1760.39 | 622.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.97 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 2161.93 | 1508.90 | 311.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2596.68 | 4526.71 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.60 | 71.38 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3387.17 | 14-JAN-16:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 1.18 | 0.00 |
February | 3393.45 | 03-FEB-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.59 |
March | 3008.17 | 05-MAR-16:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.59 |
April | 3177.96 | 01-APR-18:02 | 702.00 | 1067.29 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.70 |
May | 3064.29 | 24-MAY-08:62 | 216.00 | 469.61 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.62 |
June | 3060.42 | 28-JUN-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.42 |
July | 3072.92 | 27-JUL-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.34 |
August | 3044.75 | 14-AUG-18:02 | 831.60 | 949.89 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.45 |
September | 2997.62 | 04-SEP-18:01 | 819.00 | 1245.18 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.53 |
October | 3427.03 | 26-OCT-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.20 |
November | 3350.65 | 30-NOV-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.65 |
December | 3397.19 | 19-DEC-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2997.62 | 216.00 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3427.03 | 970.20 | 1245.18 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 1.18 | 24.59 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3231.94 | 15-JAN-16:01 | 378.00 | 410.86 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.07 |
February | 3237.06 | 03-FEB-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.29 |
March | 3016.92 | 19-MAR-18:11 | 1170.00 | 1778.61 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.26 |
April | 3319.00 | 23-APR-18:11 | 1170.00 | 1778.61 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.21 |
May | 3200.97 | 19-MAY-18:51 | 1386.00 | 1582.97 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.74 |
June | 3079.60 | 04-JUN-19:31 | 1053.00 | 1600.75 | 1469.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.81 |
July | 2955.52 | 08-JUL-21:11 | 1247.40 | 1360.64 | 805.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.61 |
August | 2863.12 | 21-AUG-20:11 | 1441.80 | 1424.67 | 1635.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.26 |
September | 2938.83 | 18-SEP-15:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.85 |
October | 3327.92 | 14-OCT-08:61 | 540.00 | 996.02 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 14.24 | 0.00 |
November | 3197.71 | 27-NOV-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.58 |
December | 3240.45 | 19-DEC-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.79 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2863.12 | 378.00 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3327.92 | 1441.80 | 1778.61 | 1635.51 | 0.00 | 0.00 | 0.00 | 0.00 | 14.24 | 34.74 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1820.47 | 04-JAN-16:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.10 |
February | 1841.27 | 03-FEB-16:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.61 |
March | 1611.92 | 24-MAR-18:01 | 970.20 | 696.66 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.43 |
April | 1728.66 | 01-APR-18:02 | 702.00 | 670.94 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.84 |
May | 1638.74 | 24-MAY-08:62 | 216.00 | 295.21 | 665.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.40 |
June | 1629.28 | 30-JUN-15:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 | 0.00 |
July | 1659.73 | 15-JUL-15:01 | 378.00 | 258.31 | 379.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.39 |
August | 1640.88 | 02-AUG-15:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.09 | 0.00 |
September | 1641.45 | 21-SEP-15:02 | 583.20 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 7.57 | 0.00 |
October | 1856.17 | 14-OCT-08:61 | 540.00 | 626.21 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 7.29 | 0.00 |
November | 1827.23 | 27-NOV-09:01 | 252.00 | 344.41 | 776.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.44 |
December | 1851.23 | 29-DEC-16:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.61 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1611.92 | 216.00 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1856.17 | 970.20 | 696.66 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 7.57 | 15.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19647.80 | 18-JAN-22:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.07 |
February | 19111.67 | 01-FEB-23:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.56 |
March | 19465.74 | 24-MAR-22:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.48 |
April | 20358.60 | 26-APR-21:52 | 215910.14 | 15936.16 | 53983.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.27 |
May | 20743.09 | 04-MAY-21:53 | 188921.38 | 13944.14 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.51 |
June | 20975.44 | 27-JUN-21:52 | 242898.91 | 17928.18 | 60731.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.43 |
July | 21159.84 | 19-JUL-21:52 | 215910.14 | 15936.16 | 53983.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.76 |
August | 21020.01 | 18-AUG-21:52 | 242898.91 | 17928.18 | 60731.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.17 |
September | 21449.45 | 29-SEP-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 3.54 | 0.00 |
October | 21198.14 | 16-OCT-21:52 | 215910.14 | 15936.16 | 53983.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.53 |
November | 19323.51 | 10-NOV-23:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.15 |
December | 19757.85 | 05-DEC-22:54 | 134943.84 | 9960.10 | 33739.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.98 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 19111.67 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21449.45 | 242898.91 | 17928.18 | 60731.12 | 0.00 | 0.00 | 0.00 | 0.00 | 3.54 | 84.56 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 21302.18 | 18-JAN-22:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.08 |
February | 20804.15 | 01-FEB-22:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.58 |
March | 21050.45 | 24-MAR-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.56 |
April | 21881.63 | 26-APR-21:52 | 215910.14 | 15936.16 | 53983.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.27 |
May | 22189.92 | 04-MAY-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.49 |
June | 22393.34 | 27-JUN-21:52 | 242898.91 | 17928.18 | 60731.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.43 |
July | 22546.55 | 19-JUL-21:52 | 215910.14 | 15936.16 | 53983.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.76 |
August | 22361.93 | 18-AUG-21:52 | 242898.91 | 17928.18 | 60731.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.17 |
September | 22812.48 | 29-SEP-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 3.54 | 0.00 |
October | 22581.11 | 04-OCT-21:53 | 188921.38 | 13944.14 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.03 |
November | 20999.41 | 10-NOV-22:14 | 134943.84 | 9960.10 | 33739.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.18 |
December | 21335.55 | 05-DEC-22:54 | 134943.84 | 9960.10 | 33739.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.98 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 20804.15 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22812.48 | 242898.91 | 17928.18 | 60731.12 | 0.00 | 0.00 | 0.00 | 0.00 | 3.54 | 84.58 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 28436.32 | 20-JAN-11:45 | 1067.42 | 589.34 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 15.06 |
February | 28308.96 | 01-FEB-11:45 | 1067.42 | 589.34 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 9.20 | 0.00 |
March | 29168.99 | 19-MAR-10:33 | 2401.70 | 1060.81 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 31.89 |
April | 29567.87 | 30-APR-10:33 | 2401.70 | 1060.81 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 10.30 | 0.00 |
May | 29272.52 | 04-MAY-10:33 | 1601.14 | 884.01 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 13.90 |
June | 29639.28 | 25-JUN-10:33 | 2401.70 | 1060.81 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 7.21 |
July | 30075.30 | 23-JUL-10:33 | 2401.70 | 1060.81 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 10.34 | 0.00 |
August | 29952.91 | 19-AUG-10:33 | 2401.70 | 884.01 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 3.78 | 0.00 |
September | 30329.55 | 30-SEP-10:50 | 1601.14 | 589.34 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 42.23 | 0.00 |
October | 30194.87 | 15-OCT-10:40 | 2401.70 | 1060.81 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 48.09 | 0.00 |
November | 29053.34 | 19-NOV-11:45 | 1601.14 | 707.21 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 12.47 | 0.00 |
December | 28349.42 | 05-DEC-11:45 | 1067.42 | 589.34 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 6.14 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 28308.96 | 1067.42 | 589.34 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30329.55 | 2401.70 | 1060.81 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 48.09 | 31.89 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4371.84 | 06-JAN-23:00 | 2395.44 | 1317.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.36 |
February | 4236.69 | 04-FEB-05:55 | 4790.88 | 439.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.23 |
March | 4270.05 | 11-MAR-11:33 | 2395.44 | 1646.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.14 | 0.00 |
April | 4453.11 | 30-APR-10:33 | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.23 | 0.00 |
May | 4525.64 | 04-MAY-10:33 | 1596.96 | 1646.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.07 |
June | 4589.88 | 30-JUN-10:33 | 1596.96 | 1646.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.93 | 0.00 |
July | 4822.62 | 30-JUL-10:33 | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.68 | 0.00 |
August | 4803.76 | 19-AUG-10:33 | 2395.44 | 1646.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.04 | 0.00 |
September | 5183.82 | 30-SEP-13:40 | 798.48 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.26 | 0.00 |
October | 5051.30 | 16-OCT-13:10 | 1064.64 | 1097.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.10 | 0.00 |
November | 4535.76 | 19-NOV-11:33 | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.75 | 0.00 |
December | 4367.77 | 19-DEC-11:33 | 1596.96 | 1646.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 4236.69 | 798.48 | 439.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5183.82 | 4790.88 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.10 | 113.36 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.386654E+12 | 239249.29 | 17-JAN-19:10 | 0.524019E+12 | 454222.14 | 06-JAN-20:10 |
February | 0.341240E+12 | 230736.48 | 13-FEB-19:19 | 0.460233E+12 | 451405.32 | 21-FEB-20:00 |
March | 0.374264E+12 | 229395.86 | 23-MAR-19:19 | 0.536957E+12 | 466011.65 | 29-MAR-17:00 |
April | 0.379523E+12 | 243477.11 | 26-APR-18:30 | 0.431268E+12 | 414910.19 | 15-APR-21:40 |
May | 0.389580E+12 | 239539.83 | 04-MAY-18:00 | 0.429458E+12 | 389520.03 | 10-MAY-20:10 |
June | 0.401498E+12 | 272709.29 | 29-JUN-18:10 | 0.358578E+12 | 352876.78 | 12-JUN-20:00 |
July | 0.466116E+12 | 318795.82 | 18-JUL-18:10 | 0.355757E+12 | 313419.54 | 03-JUL-17:30 |
August | 0.480548E+12 | 286948.89 | 14-AUG-18:40 | 0.355346E+12 | 312992.63 | 31-AUG-17:30 |
September | 0.427235E+12 | 326139.69 | 29-SEP-18:00 | 0.350838E+12 | 315315.54 | 28-SEP-17:40 |
October | 0.452170E+12 | 297624.61 | 15-OCT-08:00 | 0.388123E+12 | 352415.91 | 11-OCT-20:00 |
November | 0.378102E+12 | 241594.23 | 19-NOV-08:00 | 0.459749E+12 | 442950.30 | 04-NOV-19:49 |
December | 0.390839E+12 | 242912.53 | 05-DEC-19:10 | 0.520174E+12 | 457924.29 | 21-DEC-19:40 |
Annual Sum or Average | 0.486777E+13 | 0.517050E+13 | ||||
Minimum of Months | 0.341240E+12 | 229395.86 | 0.350838E+12 | 312992.63 | ||
Maximum of Months | 0.480548E+12 | 326139.69 | 0.536957E+12 | 466011.65 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.669826E+11 | 0.191147E+11 | 0.140828E+12 | 0.691145E+11 | 0.425874E+11 | 0.619939E+10 | 0.00 | 0.285484E+11 | 0.00 | 0.00 | 0.00 | 0.804801E+10 | 0.00 |
February | 0.603145E+11 | 0.163386E+11 | 0.127191E+12 | 0.624260E+11 | 0.384810E+11 | 0.569569E+10 | 0.00 | 0.187722E+11 | 0.00 | 0.00 | 0.00 | 0.727211E+10 | 0.00 |
March | 0.666141E+11 | 0.167457E+11 | 0.140882E+12 | 0.691169E+11 | 0.421256E+11 | 0.608629E+10 | 0.00 | 0.193802E+11 | 0.00 | 0.00 | 0.00 | 0.804648E+10 | 0.00 |
April | 0.641719E+11 | 0.148876E+11 | 0.136245E+12 | 0.668844E+11 | 0.421943E+11 | 0.631093E+10 | 0.00 | 0.359052E+11 | 0.00 | 0.00 | 0.00 | 0.779739E+10 | 0.00 |
May | 0.660709E+11 | 0.142139E+11 | 0.140860E+12 | 0.691152E+11 | 0.436105E+11 | 0.652102E+10 | 0.00 | 0.358357E+11 | 0.00 | 0.00 | 0.00 | 0.804744E+10 | 0.00 |
June | 0.638617E+11 | 0.131775E+11 | 0.136336E+12 | 0.668866E+11 | 0.433256E+11 | 0.619775E+10 | 0.00 | 0.587505E+11 | 0.00 | 0.00 | 0.00 | 0.778883E+10 | 0.00 |
July | 0.660419E+11 | 0.138734E+11 | 0.140770E+12 | 0.691128E+11 | 0.459592E+11 | 0.661406E+10 | 0.00 | 0.110353E+12 | 0.00 | 0.00 | 0.00 | 0.805572E+10 | 0.00 |
August | 0.661918E+11 | 0.148580E+11 | 0.140892E+12 | 0.691167E+11 | 0.463683E+11 | 0.668550E+10 | 0.00 | 0.123023E+12 | 0.00 | 0.00 | 0.00 | 0.804726E+10 | 0.00 |
September | 0.644665E+11 | 0.156427E+11 | 0.136256E+12 | 0.668847E+11 | 0.441227E+11 | 0.630091E+10 | 0.00 | 0.805852E+11 | 0.00 | 0.00 | 0.00 | 0.779867E+10 | 0.00 |
October | 0.668642E+11 | 0.175305E+11 | 0.140818E+12 | 0.691144E+11 | 0.464365E+11 | 0.662709E+10 | 0.00 | 0.914382E+11 | 0.00 | 0.00 | 0.00 | 0.804595E+10 | 0.00 |
November | 0.647710E+11 | 0.181597E+11 | 0.136330E+12 | 0.668856E+11 | 0.423624E+11 | 0.628937E+10 | 0.00 | 0.304435E+11 | 0.00 | 0.00 | 0.00 | 0.778066E+10 | 0.00 |
December | 0.669635E+11 | 0.194405E+11 | 0.140770E+12 | 0.691133E+11 | 0.430788E+11 | 0.635332E+10 | 0.00 | 0.318501E+11 | 0.00 | 0.00 | 0.00 | 0.805635E+10 | 0.00 |
Annual Sum or Average | 0.783315E+12 | 0.193983E+12 | 0.165818E+13 | 0.813771E+12 | 0.520652E+12 | 0.758813E+11 | 0.00 | 0.664886E+12 | 0.00 | 0.00 | 0.00 | 0.947849E+11 | 0.00 |
Minimum of Months | 0.603145E+11 | 0.131775E+11 | 0.127191E+12 | 0.624260E+11 | 0.384810E+11 | 0.569569E+10 | 0.00 | 0.187722E+11 | 0.00 | 0.00 | 0.00 | 0.727211E+10 | 0.00 |
Maximum of Months | 0.669826E+11 | 0.194405E+11 | 0.140892E+12 | 0.691169E+11 | 0.464365E+11 | 0.668550E+10 | 0.00 | 0.123023E+12 | 0.00 | 0.00 | 0.00 | 0.805635E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.151918E+12 | 0.00 | 0.154119E+12 | 0.00 | 0.217982E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.125931E+12 | 0.00 | 0.197098E+12 | 0.00 | 0.00 |
March | 0.152024E+12 | 0.00 | 0.168419E+12 | 0.00 | 0.216515E+12 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.780922E+11 | 0.00 | 0.206220E+12 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.684318E+11 | 0.00 | 0.209048E+12 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 0.126494E+11 | 0.00 | 0.198815E+12 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 0.829945E+09 | 0.00 | 0.203106E+12 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 0.370378E+09 | 0.00 | 0.202937E+12 | 0.00 | 0.00 |
September | 0.146971E+12 | 0.00 | 0.575534E+10 | 0.00 | 0.198112E+12 | 0.00 | 0.00 |
October | 0.151903E+12 | 0.00 | 0.281449E+11 | 0.00 | 0.208075E+12 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.107375E+12 | 0.00 | 0.205283E+12 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.152599E+12 | 0.00 | 0.215755E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178884E+13 | 0.00 | 0.902716E+12 | 0.00 | 0.247895E+13 | 0.00 | 0.00 |
Minimum of Months | 0.137204E+12 | 0.00 | 0.370378E+09 | 0.00 | 0.197098E+12 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.168419E+12 | 0.00 | 0.217982E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 64632.59 | 02-JAN-20:10 | 12338.45 | 01-JAN-00:10 | 89171.45 | 02-JAN-07:10 | 49607.07 | 18-JAN-07:19 | 27942.11 | 18-JAN-22:00 | 2843.35 | 09-JAN-07:19 | 0.00 | 01-JAN-00:10 |
February | 64632.59 | 01-FEB-20:10 | 12338.45 | 01-FEB-00:10 | 89171.45 | 01-FEB-07:10 | 49606.67 | 10-FEB-07:19 | 26838.33 | 01-FEB-22:10 | 2837.37 | 03-FEB-21:00 | 0.00 | 01-FEB-00:10 |
March | 64632.59 | 01-MAR-20:10 | 12338.45 | 01-MAR-00:10 | 89171.45 | 01-MAR-07:10 | 49607.07 | 13-MAR-06:19 | 26845.15 | 23-MAR-21:10 | 2846.73 | 29-MAR-08:09 | 0.00 | 01-MAR-00:10 |
April | 64632.59 | 03-APR-19:10 | 12338.45 | 01-APR-00:10 | 89171.45 | 03-APR-06:10 | 49606.67 | 05-APR-06:19 | 28887.19 | 26-APR-21:00 | 2827.10 | 01-APR-06:19 | 0.00 | 01-APR-00:10 |
May | 64632.59 | 01-MAY-19:10 | 12338.45 | 01-MAY-00:10 | 89171.45 | 01-MAY-06:10 | 49606.28 | 09-MAY-06:19 | 29133.51 | 04-MAY-21:00 | 2826.25 | 14-MAY-04:49 | 0.00 | 01-MAY-00:10 |
June | 64632.59 | 01-JUN-19:10 | 12338.45 | 01-JUN-00:10 | 89171.45 | 01-JUN-06:10 | 49606.28 | 16-JUN-06:19 | 29547.06 | 27-JUN-21:00 | 2824.86 | 29-JUN-18:10 | 0.00 | 01-JUN-00:10 |
July | 64632.59 | 03-JUL-19:10 | 12338.45 | 01-JUL-00:10 | 89171.45 | 03-JUL-06:10 | 49606.28 | 12-JUL-06:19 | 31053.94 | 19-JUL-21:00 | 3320.25 | 18-JUL-18:10 | 0.00 | 01-JUL-00:10 |
August | 64632.59 | 01-AUG-19:10 | 12338.45 | 01-AUG-00:10 | 89171.45 | 01-AUG-06:10 | 49606.67 | 21-AUG-06:19 | 30939.24 | 18-AUG-21:00 | 3329.52 | 14-AUG-10:50 | 0.00 | 01-AUG-00:10 |
September | 64632.59 | 01-SEP-19:10 | 12338.45 | 01-SEP-00:10 | 89171.45 | 01-SEP-06:10 | 49607.07 | 18-SEP-06:19 | 32155.42 | 29-SEP-21:10 | 4250.92 | 29-SEP-15:20 | 0.00 | 01-SEP-00:10 |
October | 64632.59 | 02-OCT-19:10 | 12338.45 | 01-OCT-00:10 | 89171.45 | 02-OCT-06:10 | 49607.07 | 05-OCT-06:19 | 34789.12 | 16-OCT-21:00 | 3687.31 | 17-OCT-10:50 | 0.00 | 01-OCT-00:10 |
November | 64632.59 | 01-NOV-19:10 | 12338.45 | 01-NOV-00:10 | 89171.45 | 01-NOV-06:10 | 49607.07 | 01-NOV-06:19 | 28203.46 | 28-NOV-22:10 | 3110.49 | 19-NOV-10:00 | 0.00 | 01-NOV-00:10 |
December | 64632.59 | 01-DEC-20:10 | 12338.45 | 01-DEC-00:10 | 89171.45 | 01-DEC-07:10 | 49607.07 | 08-DEC-07:19 | 29557.67 | 05-DEC-22:00 | 2841.31 | 19-DEC-21:19 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 64632.59 | 12338.45 | 89171.45 | 49606.28 | 26838.33 | 2824.86 | 0.00 | |||||||
Maximum of Months | 64632.59 | 12338.45 | 89171.45 | 49607.07 | 34789.12 | 4250.92 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 68516.21 | 14-JAN-10:00 | 0.00 | 0.00 | 0.00 | 4752.55 | 09-JAN-07:10 | 0.00 |
February | 60514.85 | 01-FEB-11:50 | 0.00 | 0.00 | 0.00 | 4751.13 | 07-FEB-07:49 | 0.00 |
March | 68473.05 | 23-MAR-15:09 | 0.00 | 0.00 | 0.00 | 4751.57 | 30-MAR-06:10 | 0.00 |
April | 68010.09 | 26-APR-10:50 | 0.00 | 0.00 | 0.00 | 4751.13 | 03-APR-18:00 | 0.00 |
May | 58494.97 | 04-MAY-15:09 | 0.00 | 0.00 | 0.00 | 4751.13 | 04-MAY-18:00 | 0.00 |
June | 82648.21 | 29-JUN-18:10 | 0.00 | 0.00 | 0.00 | 4751.13 | 09-JUN-18:40 | 0.00 |
July | 129646.22 | 19-JUL-15:20 | 0.00 | 0.00 | 0.00 | 4751.13 | 28-JUL-06:40 | 0.00 |
August | 137929.44 | 18-AUG-15:09 | 0.00 | 0.00 | 0.00 | 4751.13 | 08-AUG-06:40 | 0.00 |
September | 151238.10 | 29-SEP-15:09 | 0.00 | 0.00 | 0.00 | 4751.13 | 25-SEP-18:00 | 0.00 |
October | 156617.73 | 16-OCT-11:09 | 0.00 | 0.00 | 0.00 | 4751.12 | 11-OCT-18:30 | 0.00 |
November | 81184.49 | 19-NOV-09:00 | 0.00 | 0.00 | 0.00 | 4751.13 | 30-NOV-07:40 | 0.00 |
December | 72534.18 | 05-DEC-09:50 | 0.00 | 0.00 | 0.00 | 4751.13 | 20-DEC-07:49 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 58494.97 | 0.00 | 0.00 | 0.00 | 4751.12 | 0.00 | ||
Maximum of Months | 156617.73 | 0.00 | 0.00 | 0.00 | 4752.55 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 239249.29 | 17-JAN-19:10 | 57474.69 | 77573.37 | 12338.45 | 28159.60 | 19940.15 | 2427.34 | 0.00 | 34731.29 | 0.00 |
February | 230736.48 | 13-FEB-19:19 | 57474.69 | 77573.37 | 12338.45 | 28169.74 | 20800.82 | 2407.46 | 0.00 | 24804.11 | 0.00 |
March | 229395.86 | 23-MAR-19:19 | 64632.59 | 86439.81 | 12338.45 | 10999.77 | 24151.24 | 2400.40 | 0.00 | 22051.37 | 0.00 |
April | 243477.11 | 26-APR-18:30 | 57474.69 | 77573.37 | 12338.45 | 28169.74 | 20169.42 | 2454.74 | 0.00 | 38123.93 | 0.00 |
May | 239539.83 | 04-MAY-18:00 | 57474.69 | 77573.37 | 12338.45 | 28169.74 | 20535.26 | 2422.58 | 0.00 | 33857.44 | 0.00 |
June | 272709.29 | 29-JUN-18:10 | 54326.11 | 77573.37 | 0.00 | 28157.54 | 20009.25 | 2824.86 | 0.00 | 82648.21 | 0.00 |
July | 318795.82 | 18-JUL-18:10 | 54719.87 | 77573.37 | 0.00 | 28157.54 | 24643.19 | 3320.25 | 0.00 | 123776.00 | 0.00 |
August | 286948.89 | 14-AUG-18:40 | 57474.69 | 77573.37 | 12338.45 | 28169.74 | 20568.31 | 2823.49 | 0.00 | 80832.58 | 0.00 |
September | 326139.69 | 29-SEP-18:00 | 57474.69 | 77573.37 | 12338.45 | 28169.74 | 26461.96 | 2841.89 | 0.00 | 114713.80 | 0.00 |
October | 297624.61 | 15-OCT-08:00 | 24800.21 | 70367.69 | 0.00 | 27993.71 | 23013.76 | 2805.26 | 0.00 | 142464.33 | 0.00 |
November | 241594.23 | 19-NOV-08:00 | 29109.14 | 86249.25 | 0.00 | 49532.81 | 16932.78 | 2445.09 | 0.00 | 51549.44 | 0.00 |
December | 242912.53 | 05-DEC-19:10 | 57474.69 | 77573.37 | 12338.45 | 28159.60 | 20769.66 | 2411.39 | 0.00 | 37627.04 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 229395.86 | 24800.21 | 70367.69 | 0.00 | 10999.77 | 16932.78 | 2400.40 | 0.00 | 22051.37 | 0.00 | |
Maximum of Months | 326139.69 | 64632.59 | 86439.81 | 12338.45 | 49532.81 | 26461.96 | 3320.25 | 0.00 | 142464.33 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 191268.39 | 08-JAN-06:00 | 0.00 | 226539.50 | 31-JAN-21:40 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 152604.69 | 04-FEB-04:30 | 0.00 | 226542.04 | 06-FEB-21:40 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 179579.26 | 30-MAR-02:00 | 0.00 | 225277.90 | 01-MAR-21:49 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 151070.81 | 20-APR-03:00 | 0.00 | 222389.31 | 05-APR-20:30 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 153663.66 | 27-MAY-04:40 | 0.00 | 218078.36 | 01-MAY-20:19 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 105674.71 | 13-JUN-03:00 | 0.00 | 214899.15 | 01-JUN-20:00 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 45866.78 | 06-JUL-00:00 | 0.00 | 211843.78 | 03-JUL-20:49 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 16224.00 | 28-AUG-03:00 | 0.00 | 211771.51 | 31-AUG-20:40 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 101162.77 | 20-SEP-02:00 | 0.00 | 213931.15 | 28-SEP-20:00 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 149600.77 | 28-OCT-04:00 | 0.00 | 217246.80 | 31-OCT-20:19 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 154115.14 | 04-NOV-19:49 | 0.00 | 222320.19 | 30-NOV-21:19 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 155958.60 | 21-DEC-19:40 | 0.00 | 224932.90 | 29-DEC-21:49 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 104248.32 | 0.00 | 16224.00 | 0.00 | 211771.51 | 0.00 | |||
Maximum of Months | 104248.32 | 0.00 | 191268.39 | 0.00 | 226542.04 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.93 | 0.67 | 21.93 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 21.93 | 2.17 | 21.93 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 2.83 | 21.93 | 2.83 | 21.93 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 21.93 | 2.17 | 21.93 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.78 | 0.50 | 21.78 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.93 | 0.50 | 21.93 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.73 | 1.17 | 21.73 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.72 | 1.83 | 21.72 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.69 | 1.50 | 21.69 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.82 | 0.50 | 21.82 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.82 | 0.83 | 21.82 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 6.83 | 21.75 | 6.83 | 21.75 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.93 | 1.83 | 21.93 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.68 | 0.17 | 21.68 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.74 | 0.67 | 21.74 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 21.82 | 3.17 | 21.82 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 21.84 | 5.67 | 21.84 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 21.79 | 4.67 | 21.79 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.76 | 1.33 | 21.76 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 21.79 | 2.17 | 21.79 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 17.83 | 21.81 | 17.83 | 21.81 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 21.84 | 5.67 | 21.84 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.73 | 0.67 | 21.73 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.74 | 0.83 | 21.74 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.73 | 0.17 | 21.73 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.67 | 21.74 | 1.67 | 21.74 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.74 | 0.83 | 21.74 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.82 | 0.50 | 21.82 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 22.01 | 1.50 | 22.01 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 21.92 | 2.50 | 21.92 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 22.09 | 4.00 | 22.09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 22.21 | 7.00 | 22.21 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 22.24 | 7.00 | 22.24 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 22.00 | 3.17 | 22.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.97 | 1.67 | 21.97 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 22.03 | 0.17 | 22.03 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 27.50 | 22.12 | 27.50 | 22.12 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 22.24 | 7.00 | 22.24 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.68 | 0.17 | 21.68 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.71 | 0.50 | 21.71 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.96 | 1.00 | 21.96 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 22.00 | 3.00 | 22.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 4.67 | 21.95 | 4.67 | 21.95 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 22.00 | 3.00 | 22.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.84 | 0.83 | 21.84 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.84 | 1.50 | 21.84 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 21.79 | 2.83 | 21.79 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 21.75 | 6.00 | 21.75 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 21.74 | 3.50 | 21.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.91 | 0.67 | 21.91 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.89 | 1.00 | 21.89 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 16.33 | 21.78 | 16.33 | 21.78 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 21.91 | 6.00 | 21.91 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.72 | 0.50 | 21.72 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.94 | 0.67 | 21.94 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 21.96 | 4.83 | 21.96 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.77 | 0.50 | 21.77 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.80 | 0.83 | 21.80 |
Annual Sum or Average | 0.00 | 0.00 | 7.33 | 21.91 | 7.33 | 21.91 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 21.96 | 4.83 | 21.96 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 682.33 | 23.10 | 5.17 | 23.10 | 0.00 | 23.10 |
February | 668.83 | 22.77 | 0.00 | 22.77 | 0.00 | 22.77 |
March | 744.00 | 22.47 | 0.00 | 22.47 | 0.00 | 22.47 |
April | 720.00 | 22.50 | 0.00 | 22.50 | 0.00 | 22.50 |
May | 744.00 | 22.52 | 0.00 | 22.52 | 0.00 | 22.52 |
June | 720.00 | 22.43 | 0.00 | 22.43 | 0.00 | 22.43 |
July | 744.00 | 22.77 | 0.00 | 22.77 | 0.00 | 22.77 |
August | 733.17 | 22.87 | 0.00 | 22.87 | 0.00 | 22.87 |
September | 576.33 | 23.10 | 6.33 | 23.11 | 0.00 | 23.11 |
October | 510.83 | 23.35 | 38.67 | 23.39 | 0.00 | 23.39 |
November | 556.00 | 23.43 | 15.17 | 23.45 | 0.00 | 23.45 |
December | 698.50 | 23.24 | 2.00 | 23.25 | 0.00 | 23.25 |
Annual Sum or Average | 8098.00 | 22.85 | 67.33 | 22.86 | 0.00 | 22.86 |
Minimum of Months | 510.83 | 22.43 | 0.00 | 22.43 | 0.00 | 22.43 |
Maximum of Months | 744.00 | 23.43 | 38.67 | 23.45 | 0.00 | 23.45 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 591.50 | 21.67 | 93.33 | 21.96 | 6.50 | 21.95 |
February | 567.00 | 21.56 | 59.17 | 21.77 | 2.50 | 21.77 |
March | 669.00 | 21.42 | 51.83 | 21.57 | 5.50 | 21.56 |
April | 649.83 | 21.73 | 23.83 | 21.79 | 0.00 | 21.79 |
May | 735.50 | 21.50 | 0.00 | 21.50 | 0.00 | 21.50 |
June | 720.00 | 21.76 | 0.00 | 21.76 | 0.00 | 21.76 |
July | 693.00 | 22.15 | 7.83 | 22.16 | 0.00 | 22.16 |
August | 550.50 | 22.33 | 103.83 | 22.51 | 0.00 | 22.51 |
September | 501.00 | 22.19 | 156.33 | 22.55 | 0.00 | 22.55 |
October | 500.00 | 22.22 | 160.50 | 22.62 | 0.00 | 22.62 |
November | 561.33 | 21.89 | 96.00 | 22.18 | 0.67 | 22.18 |
December | 574.17 | 21.77 | 86.33 | 22.06 | 0.00 | 22.06 |
Annual Sum or Average | 7312.83 | 21.83 | 839.00 | 22.03 | 15.17 | 22.02 |
Minimum of Months | 500.00 | 21.42 | 0.00 | 21.50 | 0.00 | 21.50 |
Maximum of Months | 735.50 | 22.33 | 160.50 | 22.62 | 6.50 | 22.62 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 709.33 | 22.54 | 7.50 | 22.56 | 0.00 | 22.56 |
February | 638.17 | 22.62 | 2.00 | 22.62 | 0.00 | 22.62 |
March | 712.83 | 22.38 | 6.83 | 22.40 | 0.00 | 22.40 |
April | 599.50 | 22.69 | 40.33 | 22.76 | 1.50 | 22.76 |
May | 646.17 | 22.66 | 23.83 | 22.71 | 0.00 | 22.71 |
June | 514.17 | 22.74 | 95.17 | 22.91 | 19.00 | 22.92 |
July | 414.83 | 22.94 | 251.50 | 23.25 | 86.00 | 23.28 |
August | 395.67 | 23.07 | 324.00 | 23.38 | 111.83 | 23.41 |
September | 369.00 | 22.95 | 197.17 | 23.24 | 33.67 | 23.25 |
October | 487.50 | 23.09 | 138.00 | 23.25 | 30.00 | 23.26 |
November | 640.17 | 22.90 | 17.67 | 22.93 | 0.00 | 22.93 |
December | 718.83 | 22.76 | 3.00 | 22.77 | 0.00 | 22.77 |
Annual Sum or Average | 6846.17 | 22.74 | 1107.00 | 22.89 | 282.00 | 22.91 |
Minimum of Months | 369.00 | 22.38 | 2.00 | 22.40 | 0.00 | 22.40 |
Maximum of Months | 718.83 | 23.09 | 324.00 | 23.38 | 111.83 | 23.41 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.84 | 0.00 | 21.84 | 0.00 | 21.84 |
February | 672.00 | 21.96 | 0.00 | 21.96 | 0.00 | 21.96 |
March | 744.00 | 21.76 | 0.00 | 21.76 | 0.00 | 21.76 |
April | 720.00 | 22.20 | 0.00 | 22.20 | 0.00 | 22.20 |
May | 744.00 | 22.39 | 0.00 | 22.39 | 0.00 | 22.39 |
June | 716.00 | 22.73 | 0.00 | 22.73 | 0.00 | 22.73 |
July | 706.00 | 22.99 | 0.00 | 22.99 | 0.00 | 22.99 |
August | 707.33 | 22.98 | 0.00 | 22.98 | 0.00 | 22.98 |
September | 714.67 | 22.82 | 0.00 | 22.82 | 0.00 | 22.82 |
October | 692.83 | 22.89 | 0.00 | 22.89 | 0.00 | 22.89 |
November | 720.00 | 22.31 | 0.00 | 22.31 | 0.00 | 22.31 |
December | 744.00 | 22.02 | 0.00 | 22.02 | 0.00 | 22.02 |
Annual Sum or Average | 8624.83 | 22.40 | 0.00 | 22.40 | 0.00 | 22.40 |
Minimum of Months | 672.00 | 21.76 | 0.00 | 21.76 | 0.00 | 21.76 |
Maximum of Months | 744.00 | 22.99 | 0.00 | 22.99 | 0.00 | 22.99 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.62 | 1.33 | 21.62 | 1.33 | 21.62 |
February | 672.00 | 21.70 | 0.00 | 21.70 | 0.00 | 21.70 |
March | 744.00 | 21.54 | 0.00 | 21.54 | 0.00 | 21.54 |
April | 720.00 | 21.97 | 0.00 | 21.97 | 0.00 | 21.97 |
May | 744.00 | 22.14 | 0.00 | 22.14 | 0.00 | 22.14 |
June | 720.00 | 22.50 | 0.00 | 22.50 | 0.00 | 22.50 |
July | 744.00 | 22.79 | 0.00 | 22.79 | 0.00 | 22.79 |
August | 744.00 | 22.78 | 0.00 | 22.78 | 0.00 | 22.78 |
September | 718.83 | 22.59 | 0.00 | 22.59 | 0.00 | 22.59 |
October | 744.00 | 22.69 | 0.00 | 22.69 | 0.00 | 22.69 |
November | 720.00 | 22.05 | 0.00 | 22.05 | 0.00 | 22.05 |
December | 744.00 | 21.77 | 0.00 | 21.77 | 0.00 | 21.77 |
Annual Sum or Average | 8758.83 | 22.18 | 1.33 | 22.18 | 1.33 | 22.18 |
Minimum of Months | 672.00 | 21.54 | 0.00 | 21.54 | 0.00 | 21.54 |
Maximum of Months | 744.00 | 22.79 | 1.33 | 22.79 | 1.33 | 22.79 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 292.33 | 22.96 | 559.67 | 23.11 | 194.33 | 23.27 |
February | 254.50 | 23.16 | 542.33 | 23.16 | 181.83 | 23.31 |
March | 306.33 | 23.12 | 595.67 | 23.12 | 219.17 | 23.29 |
April | 293.83 | 23.55 | 623.67 | 23.23 | 250.33 | 23.39 |
May | 305.67 | 23.54 | 649.00 | 23.23 | 259.00 | 23.39 |
June | 296.00 | 23.80 | 656.00 | 23.26 | 278.00 | 23.42 |
July | 297.33 | 23.96 | 703.17 | 23.26 | 296.50 | 23.42 |
August | 300.00 | 23.97 | 706.33 | 23.25 | 299.33 | 23.41 |
September | 290.17 | 23.85 | 661.83 | 23.27 | 278.00 | 23.43 |
October | 280.67 | 23.59 | 651.00 | 23.25 | 242.17 | 23.40 |
November | 285.67 | 23.25 | 581.17 | 23.22 | 213.33 | 23.37 |
December | 280.33 | 22.90 | 553.50 | 23.12 | 175.83 | 23.27 |
Annual Sum or Average | 3482.83 | 23.48 | 7483.33 | 23.21 | 2887.83 | 23.37 |
Minimum of Months | 254.50 | 22.90 | 542.33 | 23.11 | 175.83 | 23.27 |
Maximum of Months | 306.33 | 23.97 | 706.33 | 23.27 | 299.33 | 23.43 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 398.00 | 22.59 | 221.83 | 23.05 | 16.00 | 23.07 |
February | 399.50 | 22.52 | 166.67 | 22.89 | 13.17 | 22.90 |
March | 508.33 | 22.25 | 131.33 | 22.54 | 3.00 | 22.55 |
April | 398.33 | 22.61 | 197.50 | 22.93 | 35.33 | 22.98 |
May | 622.50 | 22.48 | 75.83 | 22.62 | 40.17 | 22.68 |
June | 567.50 | 22.64 | 183.67 | 22.91 | 139.83 | 23.04 |
July | 527.83 | 23.08 | 365.50 | 23.30 | 284.00 | 23.40 |
August | 397.00 | 23.53 | 541.17 | 23.55 | 315.83 | 23.62 |
September | 302.33 | 23.38 | 525.67 | 23.56 | 205.67 | 23.62 |
October | 256.83 | 23.11 | 428.33 | 23.57 | 86.83 | 23.61 |
November | 307.00 | 22.94 | 272.67 | 23.36 | 23.33 | 23.36 |
December | 386.17 | 22.78 | 200.50 | 23.17 | 0.00 | 23.17 |
Annual Sum or Average | 5071.33 | 22.78 | 3310.67 | 23.15 | 1163.17 | 23.23 |
Minimum of Months | 256.83 | 22.25 | 75.83 | 22.54 | 0.00 | 22.55 |
Maximum of Months | 622.50 | 23.53 | 541.17 | 23.57 | 315.83 | 23.62 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 553.17 | 22.80 | 66.83 | 22.92 | 7.33 | 22.93 |
February | 510.67 | 22.86 | 52.67 | 22.96 | 6.17 | 22.96 |
March | 591.17 | 22.58 | 49.83 | 22.68 | 0.00 | 22.68 |
April | 455.33 | 22.73 | 146.33 | 23.01 | 13.33 | 23.03 |
May | 493.83 | 22.69 | 117.50 | 22.92 | 20.67 | 22.95 |
June | 424.50 | 22.84 | 270.67 | 23.23 | 94.83 | 23.31 |
July | 497.33 | 23.19 | 385.50 | 23.48 | 224.50 | 23.56 |
August | 482.67 | 23.42 | 411.00 | 23.62 | 283.00 | 23.69 |
September | 323.33 | 23.36 | 353.33 | 23.62 | 167.17 | 23.68 |
October | 279.33 | 23.27 | 264.33 | 23.56 | 62.00 | 23.60 |
November | 429.50 | 23.13 | 112.50 | 23.28 | 18.17 | 23.29 |
December | 585.33 | 23.08 | 35.67 | 23.12 | 0.00 | 23.12 |
Annual Sum or Average | 5626.17 | 22.97 | 2266.17 | 23.22 | 897.17 | 23.29 |
Minimum of Months | 279.33 | 22.58 | 35.67 | 22.68 | 0.00 | 22.68 |
Maximum of Months | 591.17 | 23.42 | 411.00 | 23.62 | 283.00 | 23.69 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 730.50 | 21.56 | 9.83 | 21.56 | 9.83 | 21.55 |
February | 656.00 | 21.49 | 5.83 | 21.48 | 5.83 | 21.48 |
March | 726.33 | 21.46 | 8.83 | 21.45 | 8.83 | 21.44 |
April | 682.33 | 21.56 | 0.00 | 21.56 | 0.00 | 21.56 |
May | 724.50 | 21.58 | 0.00 | 21.58 | 0.00 | 21.58 |
June | 675.17 | 21.56 | 0.00 | 21.56 | 0.00 | 21.56 |
July | 662.67 | 21.51 | 0.00 | 21.51 | 0.00 | 21.51 |
August | 653.67 | 21.49 | 0.00 | 21.49 | 0.00 | 21.49 |
September | 653.67 | 21.53 | 0.67 | 21.53 | 0.00 | 21.53 |
October | 693.50 | 21.56 | 0.50 | 21.57 | 0.00 | 21.57 |
November | 690.50 | 21.57 | 7.17 | 21.56 | 7.17 | 21.56 |
December | 734.33 | 21.59 | 8.33 | 21.59 | 8.33 | 21.58 |
Annual Sum or Average | 8283.17 | 21.54 | 41.17 | 21.54 | 40.00 | 21.53 |
Minimum of Months | 653.67 | 21.46 | 0.00 | 21.45 | 0.00 | 21.44 |
Maximum of Months | 734.33 | 21.59 | 9.83 | 21.59 | 9.83 | 21.58 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.44 | 43.00 | 21.42 | 43.00 | 21.40 |
February | 672.00 | 21.43 | 14.00 | 21.43 | 14.00 | 21.42 |
March | 730.67 | 21.44 | 17.83 | 21.46 | 10.17 | 21.44 |
April | 630.83 | 21.65 | 45.67 | 21.86 | 0.00 | 21.86 |
May | 646.33 | 21.73 | 54.17 | 21.97 | 0.00 | 21.97 |
June | 546.83 | 21.95 | 122.17 | 22.54 | 8.33 | 22.57 |
July | 509.67 | 22.10 | 199.33 | 22.92 | 48.00 | 23.03 |
August | 518.00 | 22.05 | 191.00 | 22.78 | 53.00 | 22.86 |
September | 583.50 | 21.94 | 76.33 | 22.22 | 14.33 | 22.24 |
October | 691.83 | 22.04 | 39.00 | 22.13 | 28.00 | 22.17 |
November | 719.50 | 21.59 | 16.83 | 21.58 | 16.83 | 21.57 |
December | 744.00 | 21.48 | 39.67 | 21.46 | 39.67 | 21.44 |
Annual Sum or Average | 7737.17 | 21.71 | 859.00 | 21.96 | 275.33 | 21.99 |
Minimum of Months | 509.67 | 21.43 | 14.00 | 21.42 | 0.00 | 21.40 |
Maximum of Months | 744.00 | 22.10 | 199.33 | 22.92 | 53.00 | 23.03 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.39 | 5.33 | 21.39 | 5.33 | 21.39 |
February | 672.00 | 21.38 | 8.00 | 21.38 | 8.00 | 21.37 |
March | 744.00 | 21.40 | 0.00 | 21.40 | 0.00 | 21.40 |
April | 720.00 | 21.61 | 0.00 | 21.61 | 0.00 | 21.61 |
May | 744.00 | 21.73 | 0.00 | 21.73 | 0.00 | 21.73 |
June | 711.17 | 22.07 | 1.33 | 22.08 | 0.00 | 22.08 |
July | 720.17 | 22.27 | 21.33 | 22.31 | 18.50 | 22.34 |
August | 731.17 | 22.22 | 20.67 | 22.25 | 20.50 | 22.28 |
September | 720.00 | 21.95 | 4.67 | 21.96 | 4.67 | 21.96 |
October | 742.00 | 21.92 | 16.33 | 21.95 | 16.33 | 21.98 |
November | 720.00 | 21.43 | 11.67 | 21.42 | 11.67 | 21.42 |
December | 744.00 | 21.38 | 14.00 | 21.37 | 14.00 | 21.37 |
Annual Sum or Average | 8712.50 | 21.73 | 103.33 | 21.74 | 99.00 | 21.75 |
Minimum of Months | 672.00 | 21.38 | 0.00 | 21.37 | 0.00 | 21.37 |
Maximum of Months | 744.00 | 22.27 | 21.33 | 22.31 | 20.50 | 22.34 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.64 | 13.33 | 21.63 | 13.33 | 21.62 |
February | 672.00 | 21.55 | 7.17 | 21.54 | 7.17 | 21.54 |
March | 744.00 | 21.55 | 8.83 | 21.54 | 8.83 | 21.53 |
April | 719.17 | 21.68 | 0.00 | 21.68 | 0.00 | 21.68 |
May | 743.83 | 21.66 | 0.00 | 21.66 | 0.00 | 21.66 |
June | 716.67 | 21.68 | 0.00 | 21.68 | 0.00 | 21.68 |
July | 722.17 | 21.69 | 0.00 | 21.69 | 0.00 | 21.69 |
August | 693.00 | 21.62 | 0.00 | 21.62 | 0.00 | 21.62 |
September | 699.33 | 21.65 | 0.00 | 21.65 | 0.00 | 21.65 |
October | 716.33 | 21.64 | 0.00 | 21.64 | 0.00 | 21.64 |
November | 720.00 | 21.66 | 7.83 | 21.66 | 7.83 | 21.65 |
December | 744.00 | 21.65 | 12.83 | 21.64 | 12.83 | 21.63 |
Annual Sum or Average | 8634.50 | 21.64 | 50.00 | 21.63 | 50.00 | 21.63 |
Minimum of Months | 672.00 | 21.55 | 0.00 | 21.54 | 0.00 | 21.53 |
Maximum of Months | 744.00 | 21.69 | 13.33 | 21.69 | 13.33 | 21.69 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 743.33 | 21.45 | 34.17 | 21.44 | 34.17 | 21.43 |
February | 672.00 | 21.42 | 13.33 | 21.41 | 13.33 | 21.41 |
March | 741.83 | 21.49 | 11.00 | 21.48 | 10.33 | 21.47 |
April | 705.00 | 21.84 | 8.67 | 21.87 | 0.00 | 21.87 |
May | 720.33 | 21.90 | 10.50 | 21.94 | 0.00 | 21.94 |
June | 635.33 | 22.09 | 50.33 | 22.28 | 3.00 | 22.29 |
July | 561.33 | 22.24 | 134.17 | 22.68 | 48.17 | 22.80 |
August | 574.83 | 22.29 | 127.83 | 22.69 | 60.00 | 22.84 |
September | 685.33 | 22.08 | 30.83 | 22.17 | 14.17 | 22.20 |
October | 730.83 | 22.09 | 30.83 | 22.15 | 26.67 | 22.19 |
November | 718.83 | 21.54 | 23.00 | 21.53 | 22.83 | 21.52 |
December | 743.50 | 21.48 | 40.00 | 21.47 | 40.00 | 21.45 |
Annual Sum or Average | 8232.50 | 21.81 | 514.67 | 21.92 | 272.67 | 21.94 |
Minimum of Months | 561.33 | 21.42 | 8.67 | 21.41 | 0.00 | 21.41 |
Maximum of Months | 743.50 | 22.29 | 134.17 | 22.69 | 60.00 | 22.84 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.74 | 0.00 | 21.74 | 0.00 | 21.74 |
February | 672.00 | 21.80 | 0.00 | 21.80 | 0.00 | 21.80 |
March | 744.00 | 21.61 | 0.00 | 21.61 | 0.00 | 21.61 |
April | 720.00 | 22.02 | 0.00 | 22.02 | 0.00 | 22.02 |
May | 744.00 | 22.09 | 0.00 | 22.09 | 0.00 | 22.09 |
June | 720.00 | 22.36 | 10.33 | 22.37 | 10.33 | 22.37 |
July | 744.00 | 22.70 | 53.50 | 22.71 | 53.50 | 22.71 |
August | 744.00 | 22.79 | 70.00 | 22.80 | 70.00 | 22.80 |
September | 720.00 | 22.60 | 17.83 | 22.60 | 17.83 | 22.60 |
October | 742.33 | 22.73 | 20.83 | 22.74 | 20.83 | 22.74 |
November | 720.00 | 22.15 | 0.00 | 22.15 | 0.00 | 22.15 |
December | 744.00 | 21.95 | 0.00 | 21.95 | 0.00 | 21.95 |
Annual Sum or Average | 8758.33 | 22.21 | 172.50 | 22.23 | 172.50 | 22.24 |
Minimum of Months | 672.00 | 21.61 | 0.00 | 21.61 | 0.00 | 21.61 |
Maximum of Months | 744.00 | 22.79 | 70.00 | 22.80 | 70.00 | 22.80 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 722.67 | 21.51 | 46.00 | 21.48 | 46.00 | 21.46 |
February | 651.67 | 21.43 | 27.50 | 21.42 | 27.50 | 21.41 |
March | 715.83 | 21.39 | 28.17 | 21.37 | 28.17 | 21.35 |
April | 667.83 | 21.51 | 2.50 | 21.51 | 2.50 | 21.50 |
May | 705.17 | 21.53 | 0.67 | 21.53 | 0.67 | 21.53 |
June | 655.00 | 21.50 | 0.33 | 21.50 | 0.33 | 21.50 |
July | 643.17 | 21.45 | 1.00 | 21.45 | 1.00 | 21.46 |
August | 636.50 | 21.43 | 3.00 | 21.44 | 3.00 | 21.45 |
September | 636.50 | 21.47 | 6.67 | 21.48 | 3.67 | 21.48 |
October | 682.33 | 21.52 | 4.33 | 21.53 | 0.67 | 21.53 |
November | 682.17 | 21.51 | 34.33 | 21.49 | 34.33 | 21.47 |
December | 729.67 | 21.54 | 50.67 | 21.51 | 50.67 | 21.49 |
Annual Sum or Average | 8128.50 | 21.48 | 205.17 | 21.48 | 198.50 | 21.47 |
Minimum of Months | 636.50 | 21.39 | 0.33 | 21.37 | 0.33 | 21.35 |
Maximum of Months | 729.67 | 21.54 | 50.67 | 21.53 | 50.67 | 21.53 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.37 | 101.17 | 21.32 | 101.17 | 21.29 |
February | 671.67 | 21.36 | 43.33 | 21.35 | 43.33 | 21.33 |
March | 724.17 | 21.38 | 45.33 | 21.40 | 35.33 | 21.37 |
April | 605.67 | 21.59 | 63.83 | 21.89 | 5.00 | 21.90 |
May | 617.50 | 21.65 | 72.17 | 22.00 | 0.33 | 22.00 |
June | 541.00 | 22.07 | 137.00 | 22.79 | 32.83 | 22.96 |
July | 519.83 | 22.34 | 213.83 | 23.22 | 88.33 | 23.45 |
August | 524.33 | 22.18 | 214.33 | 22.99 | 93.17 | 23.15 |
September | 552.67 | 21.83 | 107.00 | 22.21 | 31.83 | 22.24 |
October | 681.67 | 21.94 | 52.17 | 22.06 | 35.50 | 22.12 |
November | 718.83 | 21.51 | 59.17 | 21.48 | 59.17 | 21.45 |
December | 744.00 | 21.38 | 113.67 | 21.33 | 113.67 | 21.29 |
Annual Sum or Average | 7645.33 | 21.68 | 1223.00 | 21.98 | 639.67 | 22.02 |
Minimum of Months | 519.83 | 21.36 | 43.33 | 21.32 | 0.33 | 21.29 |
Maximum of Months | 744.00 | 22.34 | 214.33 | 23.22 | 113.67 | 23.45 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 658.00 | 21.48 | 0.50 | 21.48 | 0.50 | 21.48 |
February | 627.67 | 21.49 | 1.67 | 21.49 | 1.67 | 21.49 |
March | 701.00 | 21.47 | 7.50 | 21.46 | 7.50 | 21.45 |
April | 694.83 | 21.59 | 0.00 | 21.59 | 0.00 | 21.59 |
May | 744.00 | 21.59 | 0.00 | 21.59 | 0.00 | 21.59 |
June | 720.00 | 21.62 | 0.00 | 21.62 | 0.00 | 21.62 |
July | 740.00 | 21.67 | 0.17 | 21.67 | 0.17 | 21.67 |
August | 686.33 | 21.56 | 1.00 | 21.56 | 1.00 | 21.56 |
September | 632.17 | 21.45 | 1.67 | 21.46 | 0.00 | 21.46 |
October | 649.83 | 21.46 | 6.67 | 21.48 | 0.33 | 21.48 |
November | 646.17 | 21.52 | 2.83 | 21.53 | 1.00 | 21.53 |
December | 659.17 | 21.50 | 0.67 | 21.50 | 0.17 | 21.50 |
Annual Sum or Average | 8159.17 | 21.54 | 22.67 | 21.54 | 12.33 | 21.54 |
Minimum of Months | 627.67 | 21.45 | 0.00 | 21.46 | 0.00 | 21.45 |
Maximum of Months | 744.00 | 21.67 | 7.50 | 21.67 | 7.50 | 21.67 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 256.67 | 23.10 | 270.83 | 23.54 | 12.00 | 23.55 |
February | 157.67 | 23.29 | 308.50 | 23.72 | 10.83 | 23.73 |
March | 139.67 | 22.99 | 403.17 | 23.67 | 1.00 | 23.67 |
April | 25.33 | 23.58 | 591.00 | 23.89 | 12.33 | 23.89 |
May | 20.33 | 23.78 | 646.33 | 23.91 | 15.83 | 23.91 |
June | 90.17 | 23.99 | 702.83 | 23.91 | 89.83 | 23.92 |
July | 215.67 | 24.00 | 744.00 | 23.93 | 215.67 | 23.94 |
August | 279.67 | 24.00 | 743.83 | 23.93 | 279.67 | 23.94 |
September | 172.83 | 24.00 | 705.67 | 23.90 | 172.83 | 23.92 |
October | 91.83 | 23.76 | 544.17 | 23.88 | 63.67 | 23.89 |
November | 146.67 | 23.43 | 337.67 | 23.78 | 19.83 | 23.78 |
December | 265.67 | 23.26 | 187.33 | 23.55 | 0.00 | 23.55 |
Annual Sum or Average | 1862.17 | 23.57 | 6185.33 | 23.83 | 893.50 | 23.85 |
Minimum of Months | 20.33 | 22.99 | 187.33 | 23.54 | 0.00 | 23.55 |
Maximum of Months | 279.67 | 24.00 | 744.00 | 23.93 | 279.67 | 23.94 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 129.67 | 23.12 | 393.00 | 23.74 | 4.83 | 23.74 |
February | 33.33 | 23.45 | 446.50 | 23.89 | 6.50 | 23.89 |
March | 45.50 | 22.99 | 559.50 | 23.84 | 0.00 | 23.84 |
April | 11.00 | 24.00 | 666.33 | 23.93 | 11.00 | 23.93 |
May | 8.83 | 24.00 | 718.33 | 23.94 | 8.83 | 23.94 |
June | 73.33 | 24.00 | 717.33 | 23.95 | 73.33 | 23.95 |
July | 200.33 | 24.00 | 744.00 | 23.97 | 200.33 | 23.97 |
August | 264.50 | 24.00 | 744.00 | 23.96 | 264.50 | 23.97 |
September | 149.83 | 24.00 | 717.67 | 23.94 | 149.83 | 23.95 |
October | 61.00 | 23.96 | 607.83 | 23.94 | 58.00 | 23.94 |
November | 56.00 | 23.60 | 465.33 | 23.89 | 14.33 | 23.89 |
December | 96.00 | 23.29 | 298.00 | 23.78 | 0.00 | 23.78 |
Annual Sum or Average | 1129.33 | 23.76 | 7077.83 | 23.91 | 791.50 | 23.92 |
Minimum of Months | 8.83 | 22.99 | 298.00 | 23.74 | 0.00 | 23.74 |
Maximum of Months | 264.50 | 24.00 | 744.00 | 23.97 | 264.50 | 23.97 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 565.83 | 23.77 | 663.67 | 23.82 | 517.83 | 23.87 |
February | 482.67 | 23.95 | 640.33 | 23.89 | 473.17 | 23.92 |
March | 559.83 | 23.84 | 691.83 | 23.85 | 528.17 | 23.89 |
April | 525.17 | 23.99 | 714.17 | 23.92 | 524.83 | 23.94 |
May | 546.17 | 23.99 | 740.50 | 23.92 | 546.17 | 23.94 |
June | 547.17 | 23.99 | 720.00 | 23.94 | 547.17 | 23.95 |
July | 574.67 | 23.99 | 744.00 | 23.95 | 574.67 | 23.96 |
August | 577.17 | 23.99 | 744.00 | 23.95 | 577.17 | 23.96 |
September | 546.67 | 23.99 | 720.00 | 23.94 | 546.67 | 23.95 |
October | 544.17 | 23.99 | 741.00 | 23.93 | 544.17 | 23.95 |
November | 517.00 | 23.95 | 683.50 | 23.90 | 508.50 | 23.93 |
December | 551.50 | 23.82 | 656.83 | 23.86 | 513.33 | 23.90 |
Annual Sum or Average | 6538.00 | 23.94 | 8459.83 | 23.91 | 6401.83 | 23.93 |
Minimum of Months | 482.67 | 23.77 | 640.33 | 23.82 | 473.17 | 23.87 |
Maximum of Months | 577.17 | 23.99 | 744.00 | 23.95 | 577.17 | 23.96 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.70 | 4.17 | 21.70 | 4.17 | 21.69 |
February | 672.00 | 21.68 | 0.00 | 21.68 | 0.00 | 21.68 |
March | 744.00 | 21.62 | 0.00 | 21.62 | 0.00 | 21.62 |
April | 720.00 | 22.12 | 0.00 | 22.12 | 0.00 | 22.12 |
May | 744.00 | 22.13 | 0.00 | 22.13 | 0.00 | 22.13 |
June | 712.83 | 22.49 | 0.00 | 22.49 | 0.00 | 22.49 |
July | 688.67 | 22.82 | 0.00 | 22.82 | 0.00 | 22.82 |
August | 628.50 | 22.86 | 2.83 | 22.86 | 0.00 | 22.86 |
September | 691.50 | 22.62 | 0.00 | 22.62 | 0.00 | 22.62 |
October | 691.33 | 22.63 | 7.17 | 22.64 | 0.00 | 22.64 |
November | 720.00 | 21.97 | 0.00 | 21.97 | 0.00 | 21.97 |
December | 744.00 | 21.78 | 1.67 | 21.78 | 1.67 | 21.78 |
Annual Sum or Average | 8500.83 | 22.19 | 15.83 | 22.19 | 5.83 | 22.19 |
Minimum of Months | 628.50 | 21.62 | 0.00 | 21.62 | 0.00 | 21.62 |
Maximum of Months | 744.00 | 22.86 | 7.17 | 22.86 | 4.17 | 22.86 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.15491 | 38.74822 | 0.12435 | 5.68534 |
February | 672.00000 | 22.77136 | 42.37446 | 0.04280 | 5.23839 |
March | 744.00000 | 22.46717 | 46.67266 | -0.0060 | 5.20689 |
April | 720.00000 | 22.49897 | 51.38987 | 0.02881 | 5.21527 |
May | 744.00000 | 22.52321 | 50.96943 | -1.0262 | 27.43020 |
June | 720.00000 | 22.43137 | 58.19007 | -1.0126 | 26.83470 |
July | 744.00000 | 22.76950 | 60.67321 | -0.8707 | 21.21828 |
August | 744.00000 | 22.87860 | 61.17290 | -0.8274 | 19.64719 |
September | 720.00000 | 23.20434 | 56.76139 | -0.7360 | 16.67028 |
October | 744.00000 | 23.47175 | 45.73714 | 0.25054 | 6.54808 |
November | 720.00000 | 23.52292 | 39.72025 | 0.22262 | 6.28169 |
December | 744.00000 | 23.27936 | 33.59897 | 0.12024 | 5.59700 |
Annual Sum or Average | 8760.00000 | 22.91563 | 48.85775 | -0.3096 | 12.67960 |
Minimum of Months | 672.00000 | 22.43137 | 33.59897 | -1.0262 | 5.20689 |
Maximum of Months | 744.00000 | 23.52292 | 61.17290 | 0.25054 | 27.43020 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.12303 | 40.08848 | -0.0396 | 7.10290 |
February | 672.00000 | 21.91029 | 43.58635 | -0.0860 | 6.83697 |
March | 744.00000 | 21.64048 | 47.86631 | -0.1404 | 6.91368 |
April | 720.00000 | 21.88159 | 52.22235 | -0.0319 | 6.03818 |
May | 744.00000 | 21.52164 | 52.85978 | -1.2487 | 38.24933 |
June | 720.00000 | 21.75640 | 59.51028 | -1.1094 | 31.43276 |
July | 744.00000 | 22.20296 | 61.85012 | -0.9196 | 23.33639 |
August | 744.00000 | 22.56358 | 61.54859 | -0.7838 | 18.81691 |
September | 720.00000 | 22.60277 | 57.87842 | -0.7912 | 20.10182 |
October | 744.00000 | 22.71179 | 46.87886 | 0.17971 | 7.14795 |
November | 720.00000 | 22.31975 | 41.46804 | 0.02907 | 6.77477 |
December | 744.00000 | 22.25725 | 34.66204 | -0.0311 | 7.03641 |
Annual Sum or Average | 8760.00000 | 22.12588 | 50.05800 | -0.4164 | 15.03719 |
Minimum of Months | 672.00000 | 21.52164 | 34.66204 | -1.2487 | 6.03818 |
Maximum of Months | 744.00000 | 22.71179 | 61.85012 | 0.17971 | 38.24933 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.59684 | 40.77651 | 0.03347 | 5.64352 |
February | 672.00000 | 22.67467 | 43.57821 | 0.06499 | 5.46826 |
March | 744.00000 | 22.43561 | 47.64978 | 0.03181 | 5.60345 |
April | 720.00000 | 22.85246 | 51.32675 | 0.16365 | 6.04044 |
May | 744.00000 | 22.79198 | 51.16153 | -0.8687 | 21.59572 |
June | 720.00000 | 22.99186 | 57.39193 | -0.7516 | 17.54205 |
July | 744.00000 | 23.23750 | 60.12953 | -0.6376 | 14.03315 |
August | 744.00000 | 23.33582 | 60.64126 | -0.5958 | 12.88496 |
September | 720.00000 | 23.28325 | 57.46682 | -0.6382 | 14.00548 |
October | 744.00000 | 23.31031 | 47.05138 | 0.26207 | 6.83098 |
November | 720.00000 | 22.99522 | 41.79946 | 0.13951 | 5.77503 |
December | 744.00000 | 22.79569 | 35.47085 | 0.04839 | 5.39881 |
Annual Sum or Average | 8760.00000 | 22.94299 | 49.55902 | -0.2310 | 10.09783 |
Minimum of Months | 672.00000 | 22.43561 | 35.47085 | -0.8687 | 5.39881 |
Maximum of Months | 744.00000 | 23.33582 | 60.64126 | 0.26207 | 21.59572 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.71600 | 35.99753 | 0.64801 | 17.08442 |
February | 672.00000 | 22.80920 | 38.58874 | 0.68394 | 17.79399 |
March | 744.00000 | 22.72386 | 42.44459 | 0.68900 | 18.10503 |
April | 720.00000 | 22.82908 | 46.94304 | 0.76055 | 19.99248 |
May | 744.00000 | 22.84141 | 46.47995 | 0.02095 | 10.77816 |
June | 720.00000 | 22.84636 | 53.34170 | 0.08548 | 10.83945 |
July | 744.00000 | 22.85498 | 56.85309 | 0.12745 | 10.75759 |
August | 744.00000 | 22.84797 | 57.70447 | 0.13593 | 10.92396 |
September | 720.00000 | 22.85513 | 54.28427 | 0.09638 | 10.74544 |
October | 744.00000 | 22.87394 | 43.59350 | 0.76555 | 20.15076 |
November | 720.00000 | 22.86081 | 37.44848 | 0.70027 | 18.26476 |
December | 744.00000 | 22.76042 | 30.86341 | 0.62707 | 16.29739 |
Annual Sum or Average | 8760.00000 | 22.81801 | 45.40560 | 0.44346 | 15.12469 |
Minimum of Months | 672.00000 | 22.71600 | 30.86341 | 0.02095 | 10.74544 |
Maximum of Months | 744.00000 | 22.87394 | 57.70447 | 0.76555 | 20.15076 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.11872 | 43.94172 | 0.26832 | 7.75161 |
February | 672.00000 | 22.99521 | 47.13510 | 0.23576 | 7.19091 |
March | 744.00000 | 22.65575 | 51.27230 | 0.16618 | 6.85431 |
April | 720.00000 | 22.94914 | 55.30389 | 0.27684 | 7.18275 |
May | 744.00000 | 22.64140 | 55.73853 | -0.8211 | 20.09960 |
June | 720.00000 | 22.79247 | 62.22002 | -0.7098 | 16.45841 |
July | 744.00000 | 23.03581 | 64.94319 | -0.5818 | 12.72986 |
August | 744.00000 | 23.29311 | 64.89988 | -0.4720 | 10.14242 |
September | 720.00000 | 23.41069 | 61.16086 | -0.4498 | 10.08301 |
October | 744.00000 | 23.51656 | 50.57902 | 0.43673 | 9.67749 |
November | 720.00000 | 23.38258 | 45.13979 | 0.34586 | 8.24338 |
December | 744.00000 | 23.26576 | 38.84979 | 0.27833 | 7.58369 |
Annual Sum or Average | 8760.00000 | 23.08836 | 53.45610 | -0.0876 | 10.35721 |
Minimum of Months | 672.00000 | 22.64140 | 38.84979 | -0.8211 | 6.85431 |
Maximum of Months | 744.00000 | 23.51656 | 64.94319 | 0.43673 | 20.09960 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.03344 | 43.07578 | 0.17751 | 6.26896 |
February | 672.00000 | 23.07399 | 45.86554 | 0.19774 | 6.21823 |
March | 744.00000 | 22.80759 | 49.91618 | 0.15561 | 6.13868 |
April | 720.00000 | 23.09515 | 53.85040 | 0.25827 | 6.86622 |
May | 744.00000 | 23.03493 | 53.67454 | -0.7441 | 17.49402 |
June | 720.00000 | 23.17408 | 59.95943 | -0.6436 | 14.52321 |
July | 744.00000 | 23.31843 | 62.90435 | -0.5612 | 12.29053 |
August | 744.00000 | 23.40488 | 63.40254 | -0.5220 | 11.26687 |
September | 720.00000 | 23.43551 | 60.00450 | -0.5356 | 11.50725 |
October | 744.00000 | 23.52912 | 49.47205 | 0.35956 | 8.03591 |
November | 720.00000 | 23.36291 | 44.16192 | 0.26893 | 6.85715 |
December | 744.00000 | 23.21890 | 37.91920 | 0.19074 | 6.08058 |
Annual Sum or Average | 8760.00000 | 23.20786 | 52.04062 | -0.1186 | 9.48375 |
Minimum of Months | 672.00000 | 22.80759 | 37.91920 | -0.7441 | 6.08058 |
Maximum of Months | 744.00000 | 23.52912 | 63.40254 | 0.35956 | 17.49402 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.59691 | 47.37376 | -0.2196 | 6.95255 |
February | 672.00000 | 21.53082 | 50.35391 | -0.2192 | 6.78525 |
March | 744.00000 | 21.50603 | 53.62481 | -0.2118 | 6.77544 |
April | 720.00000 | 21.64895 | 54.37376 | -0.1231 | 6.21168 |
May | 744.00000 | 21.62857 | 54.68293 | -1.2573 | 39.14311 |
June | 720.00000 | 21.66604 | 56.60893 | -1.1923 | 36.04226 |
July | 744.00000 | 21.70778 | 56.26545 | -1.1389 | 33.65791 |
August | 744.00000 | 21.71089 | 56.38976 | -1.1326 | 33.43018 |
September | 720.00000 | 21.69219 | 56.06391 | -1.1655 | 34.98091 |
October | 744.00000 | 21.68396 | 49.86661 | -0.1092 | 6.18661 |
November | 720.00000 | 21.63749 | 47.61246 | -0.1838 | 6.67529 |
December | 744.00000 | 21.61697 | 42.27219 | -0.2344 | 7.12721 |
Annual Sum or Average | 8760.00000 | 21.63613 | 52.12171 | -0.6014 | 18.73631 |
Minimum of Months | 672.00000 | 21.50603 | 42.27219 | -1.2573 | 6.18661 |
Maximum of Months | 744.00000 | 21.71089 | 56.60893 | -0.1092 | 39.14311 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.44073 | 49.09266 | -0.2968 | 7.51986 |
February | 672.00000 | 21.43441 | 51.71587 | -0.2691 | 7.09636 |
March | 744.00000 | 21.48342 | 54.80716 | -0.2365 | 7.00825 |
April | 720.00000 | 21.96755 | 54.77917 | -0.0712 | 6.69187 |
May | 744.00000 | 22.06541 | 53.90451 | -1.1367 | 34.68558 |
June | 720.00000 | 22.57982 | 55.30060 | -0.9270 | 27.51727 |
July | 744.00000 | 22.86373 | 55.52593 | -0.7998 | 23.31549 |
August | 744.00000 | 22.77102 | 56.79652 | -0.8307 | 23.82647 |
September | 720.00000 | 22.32566 | 57.28089 | -1.0020 | 28.72361 |
October | 744.00000 | 22.15600 | 50.95498 | -0.0358 | 6.29273 |
November | 720.00000 | 21.58836 | 49.58489 | -0.2306 | 6.87781 |
December | 744.00000 | 21.47792 | 43.48640 | -0.3145 | 7.67495 |
Annual Sum or Average | 8760.00000 | 22.01647 | 52.76171 | -0.5141 | 15.65216 |
Minimum of Months | 672.00000 | 21.43441 | 43.48640 | -1.1367 | 6.29273 |
Maximum of Months | 744.00000 | 22.86373 | 57.28089 | -0.0358 | 34.68558 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.39164 | 45.15239 | -0.3231 | 7.48848 |
February | 672.00000 | 21.37824 | 47.97005 | -0.3033 | 7.12463 |
March | 744.00000 | 21.40119 | 51.30867 | -0.2759 | 6.82168 |
April | 720.00000 | 21.60888 | 53.44656 | -0.1974 | 6.19904 |
May | 744.00000 | 21.72759 | 52.39812 | -1.3004 | 40.77490 |
June | 720.00000 | 22.09400 | 55.69813 | -1.1387 | 33.35532 |
July | 744.00000 | 22.31749 | 57.89536 | -1.0393 | 29.19715 |
August | 744.00000 | 22.24773 | 59.21869 | -1.0638 | 30.11589 |
September | 720.00000 | 21.94891 | 57.68135 | -1.1875 | 35.39321 |
October | 744.00000 | 21.92092 | 49.18670 | -0.1359 | 6.12038 |
November | 720.00000 | 21.42642 | 46.33158 | -0.2978 | 7.13528 |
December | 744.00000 | 21.37868 | 39.87727 | -0.3567 | 7.86656 |
Annual Sum or Average | 8760.00000 | 21.73940 | 51.35354 | -0.6369 | 18.19702 |
Minimum of Months | 672.00000 | 21.37824 | 39.87727 | -1.3004 | 6.12038 |
Maximum of Months | 744.00000 | 22.31749 | 59.21869 | -0.1359 | 40.77490 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.64126 | 47.07011 | -0.2075 | 6.80956 |
February | 672.00000 | 21.54800 | 50.36358 | -0.2191 | 6.75065 |
March | 744.00000 | 21.54777 | 53.20624 | -0.2053 | 6.72232 |
April | 720.00000 | 21.68600 | 54.14167 | -0.1212 | 6.19673 |
May | 744.00000 | 21.66069 | 54.44875 | -1.2613 | 39.31051 |
June | 720.00000 | 21.68302 | 56.90863 | -1.2038 | 36.55423 |
July | 744.00000 | 21.73369 | 56.30510 | -1.1433 | 33.87977 |
August | 744.00000 | 21.73519 | 56.25846 | -1.1322 | 33.42941 |
September | 720.00000 | 21.69345 | 56.81096 | -1.1810 | 35.65450 |
October | 744.00000 | 21.69874 | 50.05213 | -0.1088 | 6.14741 |
November | 720.00000 | 21.66059 | 47.73576 | -0.1827 | 6.59447 |
December | 744.00000 | 21.64773 | 42.19646 | -0.2279 | 7.00332 |
Annual Sum or Average | 8760.00000 | 21.66206 | 52.11985 | -0.6018 | 18.82572 |
Minimum of Months | 672.00000 | 21.54777 | 42.19646 | -1.2613 | 6.14741 |
Maximum of Months | 744.00000 | 21.73519 | 56.90863 | -0.1088 | 39.31051 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.45672 | 48.66416 | -0.2908 | 7.32923 |
February | 672.00000 | 21.41980 | 51.68282 | -0.2771 | 7.02457 |
March | 744.00000 | 21.49652 | 54.41624 | -0.2365 | 6.85249 |
April | 720.00000 | 21.89341 | 54.87424 | -0.0928 | 6.21459 |
May | 744.00000 | 21.98125 | 54.31374 | -1.1730 | 35.51603 |
June | 720.00000 | 22.34843 | 56.80708 | -1.0058 | 28.81861 |
July | 744.00000 | 22.67053 | 56.82778 | -0.8632 | 24.01390 |
August | 744.00000 | 22.64257 | 57.73960 | -0.8706 | 24.18531 |
September | 720.00000 | 22.18581 | 58.75076 | -1.0580 | 30.43003 |
October | 744.00000 | 22.13188 | 51.27200 | -0.0442 | 6.08171 |
November | 720.00000 | 21.55010 | 49.62749 | -0.2443 | 6.78657 |
December | 744.00000 | 21.48686 | 43.51989 | -0.3121 | 7.48905 |
Annual Sum or Average | 8760.00000 | 21.94231 | 53.20072 | -0.5405 | 15.94433 |
Minimum of Months | 672.00000 | 21.41980 | 43.51989 | -1.1730 | 6.08171 |
Maximum of Months | 744.00000 | 22.67053 | 58.75076 | -0.0442 | 35.51603 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.56068 | 48.63493 | -0.2453 | 7.36329 |
February | 672.00000 | 21.48290 | 51.85062 | -0.2465 | 7.18675 |
March | 744.00000 | 21.46824 | 55.15244 | -0.2319 | 7.14434 |
April | 720.00000 | 21.63973 | 55.89896 | -0.1257 | 6.39358 |
May | 744.00000 | 21.62118 | 56.14351 | -1.2652 | 39.75062 |
June | 720.00000 | 21.66249 | 58.00311 | -1.1901 | 36.14103 |
July | 744.00000 | 21.70647 | 57.36414 | -1.1321 | 33.55384 |
August | 744.00000 | 21.70664 | 57.71526 | -1.1285 | 33.44855 |
September | 720.00000 | 21.68163 | 57.94464 | -1.1692 | 35.35348 |
October | 744.00000 | 21.66601 | 51.29499 | -0.1197 | 6.38750 |
November | 720.00000 | 21.60353 | 49.12107 | -0.2075 | 7.01798 |
December | 744.00000 | 21.57582 | 43.39215 | -0.2644 | 7.59062 |
Annual Sum or Average | 8760.00000 | 21.61534 | 53.53828 | -0.6128 | 19.01592 |
Minimum of Months | 672.00000 | 21.46824 | 43.39215 | -1.2652 | 6.38750 |
Maximum of Months | 744.00000 | 21.70664 | 58.00311 | -0.1197 | 39.75062 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.36524 | 50.49484 | -0.3353 | 8.11686 |
February | 672.00000 | 21.36474 | 53.36585 | -0.3036 | 7.62956 |
March | 744.00000 | 21.45584 | 56.37889 | -0.2556 | 7.43105 |
April | 720.00000 | 22.01892 | 55.93095 | -0.0607 | 7.12997 |
May | 744.00000 | 22.10961 | 54.92778 | -1.1256 | 34.97544 |
June | 720.00000 | 22.68678 | 55.65763 | -0.8868 | 27.54647 |
July | 744.00000 | 22.98744 | 55.25445 | -0.7501 | 23.25735 |
August | 744.00000 | 22.85889 | 56.82083 | -0.7953 | 23.85911 |
September | 720.00000 | 22.33360 | 58.56738 | -0.9976 | 29.11758 |
October | 744.00000 | 22.09621 | 52.32946 | -0.0542 | 6.52283 |
November | 720.00000 | 21.51242 | 51.32743 | -0.2665 | 7.37180 |
December | 744.00000 | 21.38338 | 44.72917 | -0.3608 | 8.41395 |
Annual Sum or Average | 8760.00000 | 22.01841 | 53.80204 | -0.5174 | 15.99583 |
Minimum of Months | 672.00000 | 21.36474 | 44.72917 | -1.1256 | 6.52283 |
Maximum of Months | 744.00000 | 22.98744 | 58.56738 | -0.0542 | 34.97544 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.69642 | 46.00182 | -0.1567 | 6.78833 |
February | 672.00000 | 21.61624 | 49.28015 | -0.1857 | 6.75252 |
March | 744.00000 | 21.57378 | 52.44049 | -0.1982 | 6.84157 |
April | 720.00000 | 21.65484 | 54.55710 | -0.1444 | 6.39852 |
May | 744.00000 | 21.59447 | 56.16460 | -1.3230 | 42.36766 |
June | 720.00000 | 21.61928 | 59.59306 | -1.2671 | 39.54167 |
July | 744.00000 | 21.68177 | 59.68844 | -1.2102 | 36.92989 |
August | 744.00000 | 21.69705 | 58.56849 | -1.1841 | 35.82118 |
September | 720.00000 | 21.68009 | 56.42903 | -1.1938 | 36.45172 |
October | 744.00000 | 21.69975 | 49.62502 | -0.1019 | 6.36067 |
November | 720.00000 | 21.70774 | 46.27695 | -0.1448 | 6.66756 |
December | 744.00000 | 21.70802 | 41.33106 | -0.1717 | 6.97056 |
Annual Sum or Average | 8760.00000 | 21.66110 | 52.50396 | -0.6094 | 19.90502 |
Minimum of Months | 672.00000 | 21.57378 | 41.33106 | -1.3230 | 6.36067 |
Maximum of Months | 744.00000 | 21.70802 | 59.68844 | -0.1019 | 42.36766 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.57505 | 43.58572 | 0.33751 | 7.89443 |
February | 672.00000 | 23.69079 | 45.70248 | 0.38221 | 8.34966 |
March | 744.00000 | 23.64702 | 49.37276 | 0.40002 | 8.67373 |
April | 720.00000 | 23.81761 | 52.87452 | 0.48813 | 10.15942 |
May | 744.00000 | 23.84115 | 52.31346 | -0.3838 | 8.26561 |
June | 720.00000 | 23.88368 | 58.29462 | -0.2999 | 7.01601 |
July | 744.00000 | 23.91568 | 61.35082 | -0.2490 | 6.36133 |
August | 744.00000 | 23.90076 | 62.20300 | -0.2519 | 6.40092 |
September | 720.00000 | 23.86701 | 59.32709 | -0.3062 | 7.11653 |
October | 744.00000 | 23.84928 | 49.46476 | 0.48914 | 10.28709 |
November | 720.00000 | 23.73555 | 44.51965 | 0.39201 | 8.53817 |
December | 744.00000 | 23.64461 | 38.64604 | 0.32058 | 7.47386 |
Annual Sum or Average | 8760.00000 | 23.78092 | 51.49364 | 0.10812 | 8.04044 |
Minimum of Months | 672.00000 | 23.57505 | 38.64604 | -0.3838 | 6.36133 |
Maximum of Months | 744.00000 | 23.91568 | 62.20300 | 0.48914 | 10.28709 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.72430 | 42.59859 | 0.40762 | 8.88398 |
February | 672.00000 | 23.82654 | 44.67391 | 0.45008 | 9.46197 |
March | 744.00000 | 23.79497 | 48.30998 | 0.47103 | 9.87543 |
April | 720.00000 | 23.90932 | 51.93407 | 0.54411 | 11.32326 |
May | 744.00000 | 23.92435 | 51.39997 | -0.3049 | 7.05288 |
June | 720.00000 | 23.94492 | 57.47933 | -0.2314 | 6.19890 |
July | 744.00000 | 23.96066 | 60.62561 | -0.1892 | 5.78340 |
August | 744.00000 | 23.94905 | 61.47847 | -0.1921 | 5.81025 |
September | 720.00000 | 23.92904 | 58.52062 | -0.2396 | 6.30340 |
October | 744.00000 | 23.91538 | 48.70152 | 0.53506 | 11.23327 |
November | 720.00000 | 23.85040 | 43.57295 | 0.45305 | 9.55964 |
December | 744.00000 | 23.78321 | 37.68932 | 0.38782 | 8.40408 |
Annual Sum or Average | 8760.00000 | 23.87606 | 50.60544 | 0.17250 | 8.31461 |
Minimum of Months | 672.00000 | 23.72430 | 37.68932 | -0.3049 | 5.78340 |
Maximum of Months | 744.00000 | 23.96066 | 61.47847 | 0.54411 | 11.32326 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.65061 | 41.21549 | 1.04144 | 31.19664 |
February | 672.00000 | 23.78146 | 43.32618 | 1.08362 | 32.16790 |
March | 744.00000 | 23.70126 | 46.86036 | 1.09361 | 33.10374 |
April | 720.00000 | 23.85291 | 50.77485 | 1.18769 | 36.49960 |
May | 744.00000 | 23.85591 | 50.38620 | 0.60430 | 17.33908 |
June | 720.00000 | 23.89545 | 56.52984 | 0.68833 | 19.11577 |
July | 744.00000 | 23.91754 | 59.67061 | 0.74629 | 20.59472 |
August | 744.00000 | 23.91954 | 60.39953 | 0.75203 | 20.71707 |
September | 720.00000 | 23.89992 | 57.34976 | 0.69263 | 19.14184 |
October | 744.00000 | 23.88824 | 47.73652 | 1.18804 | 36.40737 |
November | 720.00000 | 23.79651 | 42.32903 | 1.09151 | 32.48869 |
December | 744.00000 | 23.68910 | 36.43494 | 1.01837 | 29.96426 |
Annual Sum or Average | 8760.00000 | 23.82058 | 49.44233 | 0.93127 | 27.36188 |
Minimum of Months | 672.00000 | 23.65061 | 36.43494 | 0.60430 | 17.33908 |
Maximum of Months | 744.00000 | 23.91954 | 60.39953 | 1.18804 | 36.49960 |
Report: OccupantComfortDataSummaryMonthly
For: STORAGE_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.62250 | 39.68839 | -0.2513 | 6.86875 |
February | 672.00000 | 21.70208 | 42.65449 | -0.2150 | 6.13256 |
March | 744.00000 | 21.53563 | 46.78791 | -0.2318 | 6.43540 |
April | 720.00000 | 21.96911 | 50.62649 | -0.0987 | 5.45210 |
May | 744.00000 | 22.13654 | 49.82393 | -1.1511 | 33.05263 |
June | 720.00000 | 22.50090 | 55.77181 | -0.9840 | 25.59939 |
July | 744.00000 | 22.79147 | 58.61236 | -0.8615 | 20.74779 |
August | 744.00000 | 22.77788 | 59.59162 | -0.8605 | 20.69554 |
September | 720.00000 | 22.59527 | 56.57639 | -0.9451 | 24.01676 |
October | 744.00000 | 22.69077 | 45.50122 | 0.05477 | 5.41698 |
November | 720.00000 | 22.05247 | 40.72052 | -0.1381 | 5.64090 |
December | 744.00000 | 21.77353 | 34.05953 | -0.2476 | 6.57445 |
Annual Sum or Average | 8760.00000 | 22.18183 | 48.38684 | -0.4959 | 13.93568 |
Minimum of Months | 672.00000 | 21.53563 | 34.05953 | -1.1511 | 5.41698 |
Maximum of Months | 744.00000 | 22.79147 | 59.59162 | 0.05477 | 33.05263 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.74147 | 42.85953 | -0.2188 | 6.40453 |
February | 672.00000 | 21.80111 | 45.87057 | -0.1886 | 5.87204 |
March | 744.00000 | 21.60511 | 49.98391 | -0.2115 | 6.20568 |
April | 720.00000 | 22.01938 | 53.88869 | -0.0840 | 5.37822 |
May | 744.00000 | 22.08528 | 53.37595 | -1.1739 | 34.15692 |
June | 720.00000 | 22.36432 | 59.62078 | -1.0354 | 27.80099 |
July | 744.00000 | 22.70001 | 62.25122 | -0.8974 | 22.08311 |
August | 744.00000 | 22.79424 | 62.84957 | -0.8598 | 20.65703 |
September | 720.00000 | 22.59873 | 59.96476 | -0.9487 | 24.14081 |
October | 744.00000 | 22.73215 | 48.84501 | 0.06804 | 5.40096 |
November | 720.00000 | 22.15138 | 43.96845 | -0.1111 | 5.44964 |
December | 744.00000 | 21.95385 | 37.18295 | -0.2013 | 6.04995 |
Annual Sum or Average | 8760.00000 | 22.21485 | 51.74095 | -0.4904 | 14.18414 |
Minimum of Months | 672.00000 | 21.60511 | 37.18295 | -1.1739 | 5.37822 |
Maximum of Months | 744.00000 | 22.79424 | 62.84957 | 0.06804 | 34.15692 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.69899 | 40.62921 | -0.2098 | 6.48145 |
February | 672.00000 | 21.67788 | 43.76412 | -0.1964 | 6.13304 |
March | 744.00000 | 21.61950 | 47.63275 | -0.1880 | 6.20022 |
April | 720.00000 | 22.12179 | 51.26600 | -0.0336 | 5.41395 |
May | 744.00000 | 22.12842 | 50.88964 | -1.1162 | 31.64688 |
June | 720.00000 | 22.49697 | 56.84367 | -0.9432 | 24.15374 |
July | 744.00000 | 22.85602 | 59.34093 | -0.7946 | 18.50471 |
August | 744.00000 | 22.93537 | 59.96050 | -0.7620 | 17.42553 |
September | 720.00000 | 22.65430 | 57.41890 | -0.8824 | 21.83438 |
October | 744.00000 | 22.70008 | 46.51344 | 0.08846 | 5.71375 |
November | 720.00000 | 21.97317 | 41.94534 | -0.1307 | 5.73364 |
December | 744.00000 | 21.77984 | 35.19474 | -0.2219 | 6.40837 |
Annual Sum or Average | 8760.00000 | 22.22365 | 49.30030 | -0.4507 | 13.01261 |
Minimum of Months | 672.00000 | 21.61950 | 35.19474 | -1.1162 | 5.41395 |
Maximum of Months | 744.00000 | 22.93537 | 59.96050 | 0.08846 | 31.64688 |
Report: OccupantComfortDataSummaryMonthly
For: MECH_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.83720 | 38.80415 | -0.2049 | 6.51007 |
February | 672.00000 | 21.95755 | 41.65573 | -0.1603 | 5.73055 |
March | 744.00000 | 21.75904 | 45.80860 | -0.1832 | 6.07641 |
April | 720.00000 | 22.20318 | 49.56462 | -0.0486 | 5.34874 |
May | 744.00000 | 22.38587 | 48.73540 | -1.0744 | 29.58712 |
June | 720.00000 | 22.73757 | 54.63499 | -0.9107 | 22.73690 |
July | 744.00000 | 23.02572 | 57.44781 | -0.7886 | 18.25918 |
August | 744.00000 | 23.01398 | 58.40791 | -0.7870 | 18.19118 |
September | 720.00000 | 22.83095 | 55.42861 | -0.8722 | 21.26466 |
October | 744.00000 | 22.93628 | 44.47128 | 0.10790 | 5.63101 |
November | 720.00000 | 22.30689 | 39.74842 | -0.0836 | 5.42051 |
December | 744.00000 | 22.02223 | 33.18419 | -0.1943 | 6.12729 |
Annual Sum or Average | 8760.00000 | 22.42071 | 47.34329 | -0.4351 | 12.61761 |
Minimum of Months | 672.00000 | 21.75904 | 33.18419 | -1.0744 | 5.34874 |
Maximum of Months | 744.00000 | 23.02572 | 58.40791 | 0.10790 | 29.58712 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.285484E+11 | 79200.93 | 15-JAN-09:52 | 665.32 | 0.126536E+12 | 0.00 | 0.155084E+12 | 4.11 | 4.72 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.187722E+11 | 75108.30 | 01-FEB-09:51 | 621.78 | 0.850174E+11 | 0.00 | 0.103790E+12 | 4.29 | 4.72 | 01-FEB-06:20 | 0.00 | 0.00 |
March | 0.193802E+11 | 79977.75 | 23-MAR-15:03 | 649.28 | 0.871493E+11 | 0.00 | 0.106529E+12 | 4.05 | 4.72 | 01-MAR-06:13 | 0.00 | 0.00 |
April | 0.359052E+11 | 76066.94 | 11-APR-15:03 | 711.90 | 0.158547E+12 | 0.00 | 0.194453E+12 | 4.52 | 4.72 | 01-APR-00:20 | 0.00 | 0.00 |
May | 0.358357E+11 | 72045.15 | 04-MAY-15:03 | 742.76 | 0.159503E+12 | 0.00 | 0.195339E+12 | 4.55 | 4.72 | 01-MAY-23:03 | 0.00 | 0.00 |
June | 0.587505E+11 | 91088.44 | 28-JUN-15:03 | 720.00 | 0.257147E+12 | 0.00 | 0.315898E+12 | 4.47 | 4.72 | 01-JUN-01:30 | 0.00 | 0.00 |
July | 0.110353E+12 | 143215.80 | 19-JUL-15:03 | 744.00 | 0.474103E+12 | 0.00 | 0.584457E+12 | 4.38 | 4.71 | 06-JUL-01:00 | 0.00 | 0.00 |
August | 0.123023E+12 | 149131.70 | 18-AUG-15:03 | 744.00 | 0.528604E+12 | 0.00 | 0.651627E+12 | 4.38 | 4.68 | 25-AUG-21:54 | 0.00 | 0.00 |
September | 0.805852E+11 | 158580.33 | 29-SEP-15:03 | 720.00 | 0.344113E+12 | 0.00 | 0.424698E+12 | 4.42 | 4.72 | 03-SEP-01:15 | 0.00 | 0.00 |
October | 0.914382E+11 | 161155.32 | 14-OCT-15:01 | 744.00 | 0.382069E+12 | 0.00 | 0.473508E+12 | 4.39 | 4.72 | 07-OCT-23:50 | 0.00 | 0.00 |
November | 0.304435E+11 | 99142.86 | 19-NOV-09:41 | 698.07 | 0.135511E+12 | 0.00 | 0.165955E+12 | 4.46 | 4.72 | 01-NOV-03:05 | 0.00 | 0.00 |
December | 0.318501E+11 | 92409.70 | 05-DEC-09:41 | 685.11 | 0.140292E+12 | 0.00 | 0.172142E+12 | 4.23 | 4.72 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.664886E+12 | 8446.22 | 0.287859E+13 | 0.00 | 0.354348E+13 | 4.35 | 0.00 | 0.00 | ||||
Minimum of Months | 0.187722E+11 | 72045.15 | 621.78 | 0.850174E+11 | 0.00 | 0.103790E+12 | 4.05 | 4.68 | 0.00 | 0.00 | ||
Maximum of Months | 0.123023E+12 | 161155.32 | 744.00 | 0.528604E+12 | 0.00 | 0.651627E+12 | 4.55 | 4.72 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.102416E+12 | 0.00 | 528.26 | 150697.24 | 08-JAN-07:00 | 0.00 | 34.27 | 53.01 | 0.38 | 0.00 | 0.14 | 0.56 | 08-JAN-07:00 |
February | 0.787413E+11 | 0.00 | 520.72 | 111145.59 | 05-FEB-06:00 | 0.00 | 32.76 | 53.47 | 0.31 | 0.00 | 0.12 | 0.41 | 05-FEB-06:00 |
March | 0.109070E+12 | 0.00 | 579.91 | 140963.49 | 30-MAR-03:00 | 0.00 | 32.08 | 53.51 | 0.39 | 0.00 | 0.15 | 0.52 | 30-MAR-03:00 |
April | 0.473046E+11 | 0.00 | 396.09 | 104882.63 | 01-APR-05:00 | 0.00 | 29.10 | 45.99 | 0.15 | 0.00 | 0.07 | 0.39 | 01-APR-05:00 |
May | 0.413527E+11 | 0.00 | 361.91 | 94183.95 | 27-MAY-03:00 | 0.00 | 28.66 | 43.52 | 0.13 | 0.00 | 0.06 | 0.35 | 27-MAY-03:00 |
June | 0.760673E+10 | 0.00 | 150.68 | 63484.44 | 13-JUN-04:00 | 0.00 | 28.21 | 35.11 | 0.02 | 0.00 | 0.01 | 0.23 | 13-JUN-04:00 |
July | 0.502207E+09 | 0.00 | 36.94 | 27554.62 | 06-JUL-01:00 | 0.00 | 31.66 | 33.14 | 0.00 | 0.00 | 0.00 | 0.10 | 06-JUL-01:00 |
August | 0.224273E+09 | 0.00 | 27.13 | 23836.50 | 28-AUG-08:54 | 0.00 | 37.32 | 38.24 | 0.00 | 0.00 | 0.00 | 0.09 | 28-AUG-08:54 |
September | 0.347492E+10 | 0.00 | 81.09 | 60773.87 | 20-SEP-03:00 | 0.00 | 32.51 | 35.96 | 0.01 | 0.00 | 0.00 | 0.22 | 20-SEP-03:00 |
October | 0.169191E+11 | 0.00 | 161.48 | 89873.17 | 28-OCT-05:00 | 0.00 | 32.51 | 38.83 | 0.05 | 0.00 | 0.02 | 0.33 | 28-OCT-05:00 |
November | 0.661532E+11 | 0.00 | 449.38 | 102055.67 | 24-NOV-04:00 | 0.00 | 32.06 | 49.47 | 0.24 | 0.00 | 0.09 | 0.38 | 24-NOV-04:00 |
December | 0.991097E+11 | 0.00 | 510.17 | 116502.45 | 23-DEC-06:00 | 0.00 | 34.78 | 52.59 | 0.37 | 0.00 | 0.14 | 0.43 | 23-DEC-06:00 |
Annual Sum or Average | 0.572874E+12 | 0.00 | 3803.77 | 0.00 | 32.17 | 44.36 | 0.17 | 0.00 | 0.07 | ||||
Minimum of Months | 0.224273E+09 | 0.00 | 27.13 | 23836.50 | 0.00 | 28.21 | 33.14 | 0.00 | 0.00 | 0.00 | 0.09 | ||
Maximum of Months | 0.109070E+12 | 0.00 | 579.91 | 150697.24 | 0.00 | 37.32 | 53.51 | 0.39 | 0.00 | 0.15 | 0.56 |
Report: DXReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.352394E+10 | 0.00 | 171.17 | 0.349904E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20570.98 | 13-JAN-14:00 | 20570.98 | 13-JAN-14:00 | 0.00 | 0.00 | 0.00 |
February | 0.189616E+10 | 0.00 | 130.67 | 0.184036E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17583.23 | 01-FEB-09:53 | 17583.23 | 01-FEB-09:53 | 0.00 | 0.00 | 0.00 |
March | 0.213914E+10 | 0.00 | 109.83 | 0.197595E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22012.17 | 22-MAR-13:00 | 17622.52 | 11-MAR-11:00 | 0.00 | 0.00 | 0.00 |
April | 0.536108E+10 | 0.00 | 211.67 | 0.504766E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22090.96 | 26-APR-13:00 | 22090.96 | 26-APR-13:00 | 0.00 | 0.00 | 0.00 |
May | 0.568444E+10 | 0.00 | 273.33 | 0.557746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18829.64 | 04-MAY-13:00 | 17662.38 | 03-MAY-12:50 | 0.00 | 0.00 | 0.00 |
June | 0.127679E+11 | 0.00 | 460.00 | 0.101514E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 30817.80 | 29-JUN-12:15 | 17826.82 | 29-JUN-12:15 | 0.00 | 0.00 | 0.00 |
July | 0.285718E+11 | 0.00 | 581.00 | 0.167816E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 40153.36 | 31-JUL-12:50 | 23766.73 | 31-JUL-12:30 | 0.00 | 0.00 | 0.00 |
August | 0.326065E+11 | 0.00 | 582.67 | 0.176854E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 38729.91 | 14-AUG-10:00 | 22286.10 | 18-AUG-12:20 | 0.00 | 0.00 | 0.00 |
September | 0.185738E+11 | 0.00 | 518.17 | 0.130116E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 39619.58 | 22-SEP-12:15 | 35123.90 | 29-SEP-13:00 | 0.00 | 0.00 | 0.00 |
October | 0.206208E+11 | 0.00 | 461.00 | 0.151880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 38860.24 | 01-OCT-12:10 | 34150.37 | 16-OCT-12:20 | 0.00 | 0.00 | 0.00 |
November | 0.354751E+10 | 0.00 | 209.17 | 0.347968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21516.80 | 19-NOV-13:05 | 21516.80 | 19-NOV-13:05 | 0.00 | 0.00 | 0.00 |
December | 0.428641E+10 | 0.00 | 177.33 | 0.428428E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20480.92 | 05-DEC-09:55 | 20480.92 | 05-DEC-09:55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.139579E+12 | 0.00 | 3886.00 | 0.985224E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.189616E+10 | 0.00 | 109.83 | 0.184036E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17583.23 | 17583.23 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.326065E+11 | 0.00 | 582.67 | 0.176854E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 40153.36 | 35123.90 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.580356E+11 | 0.00 | 286.14 | 0.578582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 209507.34 | 14-JAN-11:45 | 209507.34 | 14-JAN-11:45 | 0.00 | 0.00 | 0.00 |
February | 0.325376E+11 | 0.00 | 233.58 | 0.317867E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 197645.24 | 01-FEB-11:45 | 197645.24 | 01-FEB-11:45 | 0.00 | 0.00 | 0.00 |
March | 0.360422E+11 | 0.00 | 212.67 | 0.353849E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 182548.43 | 23-MAR-10:45 | 176939.84 | 11-MAR-11:45 | 0.00 | 0.00 | 0.00 |
April | 0.856442E+11 | 0.00 | 357.56 | 0.841340E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 248801.82 | 26-APR-10:45 | 208737.88 | 30-APR-10:45 | 0.00 | 0.00 | 0.00 |
May | 0.916843E+11 | 0.00 | 436.17 | 0.907220E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 160265.73 | 18-MAY-10:45 | 157876.76 | 04-MAY-12:00 | 0.00 | 0.00 | 0.00 |
June | 0.168981E+12 | 0.00 | 613.67 | 0.147634E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 311545.41 | 29-JUN-10:45 | 192253.53 | 29-JUN-10:45 | 0.00 | 0.00 | 0.00 |
July | 0.344845E+12 | 0.00 | 735.17 | 0.225519E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 379846.46 | 31-JUL-10:45 | 241704.35 | 19-JUL-10:45 | 0.00 | 0.00 | 0.00 |
August | 0.388248E+12 | 0.00 | 736.67 | 0.235368E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 407055.93 | 14-AUG-10:45 | 241645.37 | 14-AUG-10:45 | 0.00 | 0.00 | 0.00 |
September | 0.229551E+12 | 0.00 | 674.83 | 0.177330E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 373451.97 | 22-SEP-12:00 | 363907.17 | 29-SEP-10:50 | 0.00 | 0.00 | 0.00 |
October | 0.260147E+12 | 0.00 | 618.00 | 0.209800E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 383393.45 | 16-OCT-10:45 | 383393.45 | 16-OCT-10:45 | 0.00 | 0.00 | 0.00 |
November | 0.605792E+11 | 0.00 | 343.08 | 0.598840E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 214444.18 | 19-NOV-11:45 | 214444.18 | 19-NOV-11:45 | 0.00 | 0.00 | 0.00 |
December | 0.668534E+11 | 0.00 | 297.46 | 0.668534E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 193632.86 | 19-DEC-11:45 | 193632.86 | 19-DEC-11:45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.182315E+13 | 0.00 | 5544.99 | 0.142227E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.325376E+11 | 0.00 | 212.67 | 0.317867E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 160265.73 | 157876.76 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.388248E+12 | 0.00 | 736.67 | 0.235368E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 407055.93 | 383393.45 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.217582E+10 | 0.00 | 435.80 | 0.109536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14065.88 | 21-JAN-09:02 | 14046.92 | 15-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.194204E+10 | 0.00 | 365.23 | 0.103107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14877.07 | 13-FEB-16:02 | 14041.95 | 06-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.211089E+10 | 0.00 | 381.84 | 0.957685E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14078.98 | 17-MAR-15:01 | 12633.42 | 05-MAR-16:01 | 0.00 | 0.00 | 0.00 |
April | 0.416899E+10 | 0.00 | 570.04 | 0.200237E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13979.96 | 08-APR-08:61 | 13646.88 | 01-APR-18:02 | 0.00 | 0.00 | 0.00 |
May | 0.391154E+10 | 0.00 | 579.68 | 0.178067E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14181.44 | 06-MAY-08:62 | 13407.16 | 24-MAY-08:62 | 0.00 | 0.00 | 0.00 |
June | 0.547476E+10 | 0.00 | 618.30 | 0.251281E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14344.78 | 16-JUN-15:01 | 12764.03 | 28-JUN-18:01 | 0.00 | 0.00 | 0.00 |
July | 0.761582E+10 | 0.00 | 681.60 | 0.370226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14677.75 | 30-JUL-08:61 | 12713.74 | 02-JUL-18:01 | 0.00 | 0.00 | 0.00 |
August | 0.786608E+10 | 0.00 | 690.17 | 0.386137E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14919.63 | 18-AUG-08:61 | 12784.20 | 17-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.624545E+10 | 0.00 | 650.22 | 0.296698E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14690.72 | 23-SEP-08:62 | 12731.47 | 24-SEP-15:01 | 0.00 | 0.00 | 0.00 |
October | 0.568310E+10 | 0.00 | 649.50 | 0.330525E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14855.68 | 01-OCT-08:61 | 14046.40 | 25-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.292420E+10 | 0.00 | 513.31 | 0.151173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14694.74 | 12-NOV-09:02 | 14041.50 | 30-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.243721E+10 | 0.00 | 458.66 | 0.164179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14045.90 | 25-DEC-16:01 | 14045.90 | 25-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.525559E+11 | 0.00 | 6594.36 | 0.263693E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.194204E+10 | 0.00 | 365.23 | 0.957685E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13979.96 | 12633.42 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.786608E+10 | 0.00 | 690.17 | 0.386137E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14919.63 | 14046.92 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.521995E+09 | 0.00 | 190.04 | 0.228927E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13786.68 | 20-JAN-19:01 | 13527.29 | 15-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.698535E+09 | 0.00 | 202.77 | 0.299410E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14158.78 | 13-FEB-16:02 | 13522.47 | 06-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.982138E+09 | 0.00 | 254.16 | 0.364959E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13823.06 | 22-MAR-18:51 | 12264.45 | 24-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.245637E+10 | 0.00 | 428.17 | 0.950917E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14728.05 | 26-APR-21:51 | 13295.78 | 19-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.271019E+10 | 0.00 | 446.30 | 0.108959E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14282.87 | 03-MAY-21:51 | 13002.61 | 24-MAY-08:51 | 0.00 | 0.00 | 0.00 |
June | 0.354110E+10 | 0.00 | 401.63 | 0.155581E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15246.55 | 28-JUN-21:51 | 12428.91 | 04-JUN-19:31 | 0.00 | 0.00 | 0.00 |
July | 0.496058E+10 | 0.00 | 418.65 | 0.247115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15402.26 | 27-JUL-21:51 | 12011.66 | 08-JUL-21:11 | 0.00 | 0.00 | 0.00 |
August | 0.468699E+10 | 0.00 | 413.60 | 0.224037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15277.88 | 16-AUG-21:51 | 11905.25 | 05-AUG-15:01 | 0.00 | 0.00 | 0.00 |
September | 0.344084E+10 | 0.00 | 403.80 | 0.144153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14835.65 | 30-SEP-21:51 | 12195.59 | 18-SEP-15:01 | 0.00 | 0.00 | 0.00 |
October | 0.270654E+10 | 0.00 | 397.78 | 0.143225E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15243.46 | 01-OCT-08:51 | 13999.46 | 14-OCT-08:61 | 0.00 | 0.00 | 0.00 |
November | 0.942833E+09 | 0.00 | 299.71 | 0.380427E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14148.95 | 12-NOV-09:02 | 13521.86 | 30-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.548646E+09 | 0.00 | 204.03 | 0.337562E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13652.50 | 09-DEC-16:01 | 13526.32 | 30-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.281968E+11 | 0.00 | 4060.62 | 0.127929E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.521995E+09 | 0.00 | 190.04 | 0.228927E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13652.50 | 11905.25 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.496058E+10 | 0.00 | 446.30 | 0.247115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15402.26 | 13999.46 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.349880E+11 | 0.00 | 586.14 | 0.222311E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 45911.75 | 14-JAN-12:40 | 44584.32 | 14-JAN-13:30 | 0.00 | 0.00 | 0.00 |
February | 0.224363E+11 | 0.00 | 447.90 | 0.135836E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 41052.07 | 02-FEB-12:30 | 35743.23 | 02-FEB-12:30 | 0.00 | 0.00 | 0.00 |
March | 0.169593E+11 | 0.00 | 437.03 | 0.664649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33759.25 | 11-MAR-13:10 | 26269.95 | 11-MAR-13:00 | 0.00 | 0.00 | 0.00 |
April | 0.192376E+11 | 0.00 | 536.01 | 0.631212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25503.97 | 08-APR-12:40 | 13496.46 | 08-APR-12:50 | 0.00 | 0.00 | 0.00 |
May | 0.116634E+11 | 0.00 | 486.00 | 0.266746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22143.80 | 03-MAY-15:03 | 9960.59 | 03-MAY-15:03 | 0.00 | 0.00 | 0.00 |
June | 0.153682E+11 | 0.00 | 559.20 | 0.361980E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20191.17 | 30-JUN-15:06 | 7754.73 | 30-JUN-15:06 | 0.00 | 0.00 | 0.00 |
July | 0.235361E+11 | 0.00 | 686.54 | 0.664315E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24176.11 | 19-JUL-15:03 | 10746.75 | 19-JUL-15:03 | 0.00 | 0.00 | 0.00 |
August | 0.312057E+11 | 0.00 | 736.38 | 0.105790E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 24264.48 | 30-AUG-12:40 | 12224.75 | 30-AUG-13:00 | 0.00 | 0.00 | 0.00 |
September | 0.343521E+11 | 0.00 | 704.95 | 0.144281E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 42176.75 | 30-SEP-13:10 | 39301.51 | 30-SEP-13:05 | 0.00 | 0.00 | 0.00 |
October | 0.431468E+11 | 0.00 | 697.63 | 0.252556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 51201.35 | 16-OCT-12:20 | 44345.51 | 31-OCT-14:00 | 0.00 | 0.00 | 0.00 |
November | 0.356447E+11 | 0.00 | 605.65 | 0.227021E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 48465.61 | 19-NOV-09:53 | 44332.12 | 19-NOV-10:50 | 0.00 | 0.00 | 0.00 |
December | 0.389257E+11 | 0.00 | 606.77 | 0.288208E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 46123.66 | 19-DEC-13:00 | 46123.66 | 19-DEC-13:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.327464E+12 | 0.00 | 7090.20 | 0.163489E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.116634E+11 | 0.00 | 437.03 | 0.266746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20191.17 | 7754.73 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.431468E+11 | 0.00 | 736.38 | 0.288208E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 51201.35 | 46123.66 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.112394E+11 | 0.00 | 326.28 | 0.556612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84417.85 | 20-JAN-19:01 | 81522.86 | 16-JAN-09:02 | 0.00 | 0.00 | 0.00 |
February | 0.127748E+11 | 0.00 | 385.89 | 0.582245E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 82887.72 | 13-FEB-21:12 | 80336.20 | 04-FEB-19:02 | 0.00 | 0.00 | 0.00 |
March | 0.158503E+11 | 0.00 | 400.95 | 0.683492E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81831.23 | 22-MAR-18:51 | 74431.68 | 04-MAR-09:01 | 0.00 | 0.00 | 0.00 |
April | 0.232985E+11 | 0.00 | 412.83 | 0.113024E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 89070.55 | 26-APR-21:51 | 79596.67 | 01-APR-21:52 | 0.00 | 0.00 | 0.00 |
May | 0.274870E+11 | 0.00 | 410.02 | 0.145838E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 86991.28 | 04-MAY-21:51 | 78749.58 | 24-MAY-08:51 | 0.00 | 0.00 | 0.00 |
June | 0.309735E+11 | 0.00 | 348.42 | 0.172939E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 92204.57 | 28-JUN-21:51 | 75993.05 | 22-JUN-20:11 | 0.00 | 0.00 | 0.00 |
July | 0.370193E+11 | 0.00 | 361.98 | 0.213356E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 93941.08 | 19-JUL-21:51 | 74878.64 | 04-JUL-08:51 | 0.00 | 0.00 | 0.00 |
August | 0.342596E+11 | 0.00 | 349.54 | 0.188249E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 92936.58 | 16-AUG-21:51 | 73916.54 | 22-AUG-15:01 | 0.00 | 0.00 | 0.00 |
September | 0.272320E+11 | 0.00 | 329.62 | 0.140358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 92429.37 | 22-SEP-21:52 | 74458.91 | 02-SEP-15:01 | 0.00 | 0.00 | 0.00 |
October | 0.244003E+11 | 0.00 | 355.43 | 0.152848E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 91980.68 | 01-OCT-08:51 | 85611.40 | 14-OCT-08:61 | 0.00 | 0.00 | 0.00 |
November | 0.145310E+11 | 0.00 | 391.80 | 0.720263E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84739.39 | 09-NOV-22:53 | 80721.84 | 28-NOV-19:01 | 0.00 | 0.00 | 0.00 |
December | 0.104317E+11 | 0.00 | 338.68 | 0.624003E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81079.44 | 19-DEC-19:01 | 81079.44 | 19-DEC-19:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.269497E+12 | 0.00 | 4411.44 | 0.144327E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.104317E+11 | 0.00 | 326.28 | 0.556612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81079.44 | 73916.54 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.370193E+11 | 0.00 | 412.83 | 0.213356E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 93941.08 | 85611.40 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.231069E+10 | 0.00 | 456.13 | 0.129191E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12491.48 | 15-JAN-16:01 | 12491.48 | 15-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.182485E+10 | 0.00 | 348.72 | 0.102593E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12872.66 | 13-FEB-16:02 | 12489.20 | 05-FEB-09:01 | 0.00 | 0.00 | 0.00 |
March | 0.208244E+10 | 0.00 | 382.51 | 0.958866E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12345.24 | 15-MAR-15:01 | 11292.19 | 19-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.380804E+10 | 0.00 | 582.97 | 0.182211E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12488.46 | 02-APR-08:62 | 12488.46 | 02-APR-08:62 | 0.00 | 0.00 | 0.00 |
May | 0.338270E+10 | 0.00 | 574.61 | 0.153054E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12733.83 | 06-MAY-08:62 | 12484.25 | 24-MAY-08:62 | 0.00 | 0.00 | 0.00 |
June | 0.468018E+10 | 0.00 | 630.11 | 0.209351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12843.80 | 28-JUN-08:62 | 11361.38 | 05-JUN-15:01 | 0.00 | 0.00 | 0.00 |
July | 0.698008E+10 | 0.00 | 706.04 | 0.335747E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12480.99 | 13-JUL-18:01 | 11370.12 | 16-JUL-08:61 | 0.00 | 0.00 | 0.00 |
August | 0.751455E+10 | 0.00 | 710.03 | 0.368507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12774.71 | 08-AUG-08:62 | 11361.48 | 14-AUG-08:61 | 0.00 | 0.00 | 0.00 |
September | 0.542190E+10 | 0.00 | 654.26 | 0.251212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13146.25 | 23-SEP-08:62 | 11338.22 | 23-SEP-15:01 | 0.00 | 0.00 | 0.00 |
October | 0.540079E+10 | 0.00 | 654.46 | 0.319977E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13245.24 | 01-OCT-08:61 | 12490.76 | 25-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.272858E+10 | 0.00 | 514.71 | 0.153145E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13097.02 | 12-NOV-09:02 | 12487.06 | 30-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.244847E+10 | 0.00 | 468.76 | 0.176044E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12492.10 | 31-DEC-09:01 | 12492.10 | 31-DEC-09:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.485833E+11 | 0.00 | 6683.30 | 0.247692E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.182485E+10 | 0.00 | 348.72 | 0.958866E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12345.24 | 11292.19 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.751455E+10 | 0.00 | 710.03 | 0.368507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13245.24 | 12492.10 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.663480E+09 | 0.00 | 182.92 | 0.339008E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12316.20 | 20-JAN-19:01 | 11948.88 | 14-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.691428E+09 | 0.00 | 176.39 | 0.350155E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12281.95 | 14-FEB-09:02 | 12151.15 | 03-FEB-09:51 | 0.00 | 0.00 | 0.00 |
March | 0.103991E+10 | 0.00 | 248.83 | 0.447134E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11948.53 | 22-MAR-18:51 | 11523.67 | 23-MAR-08:51 | 0.00 | 0.00 | 0.00 |
April | 0.236595E+10 | 0.00 | 435.00 | 0.109464E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12915.78 | 02-APR-08:51 | 12915.78 | 02-APR-08:51 | 0.00 | 0.00 | 0.00 |
May | 0.244546E+10 | 0.00 | 449.24 | 0.109221E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13280.02 | 24-MAY-08:51 | 13280.02 | 24-MAY-08:51 | 0.00 | 0.00 | 0.00 |
June | 0.317484E+10 | 0.00 | 417.81 | 0.142490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13827.31 | 30-JUN-08:51 | 12248.35 | 23-JUN-08:51 | 0.00 | 0.00 | 0.00 |
July | 0.466603E+10 | 0.00 | 433.56 | 0.228889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14256.45 | 30-JUL-08:51 | 12105.73 | 10-JUL-08:51 | 0.00 | 0.00 | 0.00 |
August | 0.458466E+10 | 0.00 | 433.90 | 0.221183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14441.91 | 18-AUG-08:51 | 11941.13 | 22-AUG-08:51 | 0.00 | 0.00 | 0.00 |
September | 0.289995E+10 | 0.00 | 416.96 | 0.128076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14044.57 | 10-SEP-08:51 | 11945.97 | 12-SEP-08:51 | 0.00 | 0.00 | 0.00 |
October | 0.253603E+10 | 0.00 | 407.62 | 0.145230E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13924.00 | 17-OCT-08:21 | 13924.00 | 17-OCT-08:21 | 0.00 | 0.00 | 0.00 |
November | 0.902726E+09 | 0.00 | 245.96 | 0.435849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12597.05 | 12-NOV-09:02 | 12007.04 | 28-NOV-09:51 | 0.00 | 0.00 | 0.00 |
December | 0.583149E+09 | 0.00 | 185.81 | 0.382934E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12691.91 | 05-DEC-09:41 | 12691.91 | 05-DEC-09:41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.265536E+11 | 0.00 | 4034.01 | 0.128006E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.583149E+09 | 0.00 | 176.39 | 0.339008E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11948.53 | 11523.67 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.466603E+10 | 0.00 | 449.24 | 0.228889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14441.91 | 13924.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.456990E+09 | 0.00 | 345.60 | 0.243220E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3869.35 | 21-JAN-09:02 | 3637.31 | 15-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.414317E+09 | 0.00 | 263.12 | 0.230542E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3874.95 | 13-FEB-16:02 | 3636.22 | 06-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.487631E+09 | 0.00 | 291.79 | 0.240857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3704.74 | 24-MAR-08:61 | 3309.44 | 05-MAR-16:01 | 0.00 | 0.00 | 0.00 |
April | 0.100095E+10 | 0.00 | 509.43 | 0.513319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3749.09 | 08-APR-08:61 | 3566.51 | 01-APR-18:02 | 0.00 | 0.00 | 0.00 |
May | 0.919590E+09 | 0.00 | 512.87 | 0.443929E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3906.32 | 06-MAY-08:62 | 3445.50 | 24-MAY-08:62 | 0.00 | 0.00 | 0.00 |
June | 0.133862E+10 | 0.00 | 605.90 | 0.644247E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3839.35 | 28-JUN-08:62 | 3299.84 | 01-JUN-18:01 | 0.00 | 0.00 | 0.00 |
July | 0.191430E+10 | 0.00 | 688.99 | 0.957401E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3937.62 | 30-JUL-08:61 | 3285.13 | 03-JUL-18:01 | 0.00 | 0.00 | 0.00 |
August | 0.195070E+10 | 0.00 | 689.28 | 0.978414E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4077.06 | 06-AUG-08:61 | 3312.25 | 21-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.147110E+10 | 0.00 | 642.60 | 0.715491E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3964.62 | 23-SEP-08:62 | 3310.11 | 04-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.128912E+10 | 0.00 | 590.61 | 0.759074E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4008.58 | 01-OCT-08:61 | 3637.22 | 25-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.601801E+09 | 0.00 | 403.21 | 0.319591E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3793.52 | 11-NOV-16:01 | 3636.07 | 30-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.503022E+09 | 0.00 | 363.96 | 0.351616E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3663.19 | 08-DEC-16:01 | 3637.33 | 25-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.123481E+11 | 0.00 | 5907.37 | 0.639770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.414317E+09 | 0.00 | 263.12 | 0.230542E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3663.19 | 3285.13 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.195070E+10 | 0.00 | 689.28 | 0.978414E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4077.06 | 3637.33 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 84301365.31 | 0.00 | 98.18 | 42469656.99 | 0.00 | 0.00 | 0.00 | 0.00 | 3603.71 | 21-JAN-09:02 | 3494.74 | 15-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.123064E+09 | 0.00 | 125.55 | 56183407.41 | 0.00 | 0.00 | 0.00 | 0.00 | 3676.11 | 13-FEB-16:02 | 3493.67 | 06-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.207399E+09 | 0.00 | 172.73 | 84172204.53 | 0.00 | 0.00 | 0.00 | 0.00 | 3635.98 | 22-MAR-18:51 | 3224.55 | 19-MAR-18:11 | 0.00 | 0.00 | 0.00 |
April | 0.571078E+09 | 0.00 | 370.22 | 0.237022E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3910.07 | 26-APR-21:51 | 3538.01 | 23-APR-18:11 | 0.00 | 0.00 | 0.00 |
May | 0.634359E+09 | 0.00 | 409.56 | 0.271321E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3786.08 | 03-MAY-21:51 | 3414.00 | 19-MAY-18:51 | 0.00 | 0.00 | 0.00 |
June | 0.913856E+09 | 0.00 | 403.46 | 0.415953E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4050.07 | 28-JUN-21:51 | 3306.57 | 04-JUN-19:31 | 0.00 | 0.00 | 0.00 |
July | 0.133429E+10 | 0.00 | 423.33 | 0.682477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4080.47 | 27-JUL-21:51 | 3167.36 | 08-JUL-21:11 | 0.00 | 0.00 | 0.00 |
August | 0.122716E+10 | 0.00 | 419.09 | 0.596903E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4047.79 | 16-AUG-21:51 | 3075.31 | 21-AUG-20:11 | 0.00 | 0.00 | 0.00 |
September | 0.809247E+09 | 0.00 | 410.87 | 0.338812E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3897.61 | 07-SEP-21:51 | 3164.52 | 21-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.582619E+09 | 0.00 | 344.49 | 0.315290E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4009.82 | 01-OCT-08:51 | 3528.97 | 14-OCT-08:61 | 0.00 | 0.00 | 0.00 |
November | 0.142848E+09 | 0.00 | 176.12 | 61383988.53 | 0.00 | 0.00 | 0.00 | 0.00 | 3637.56 | 11-NOV-16:01 | 3493.55 | 30-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 77968184.67 | 0.00 | 98.90 | 54217173.59 | 0.00 | 0.00 | 0.00 | 0.00 | 3562.77 | 09-DEC-16:01 | 3494.61 | 30-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.670819E+10 | 0.00 | 3452.52 | 0.315620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 77968184.67 | 0.00 | 98.18 | 42469656.99 | 0.00 | 0.00 | 0.00 | 0.00 | 3562.77 | 3075.31 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.133429E+10 | 0.00 | 423.33 | 0.682477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4080.47 | 3538.01 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.764340E+10 | 0.00 | 584.43 | 0.536691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17169.90 | 14-JAN-19:01 | 17169.90 | 14-JAN-19:01 | 0.00 | 0.00 | 0.00 |
February | 0.510830E+10 | 0.00 | 470.44 | 0.336316E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17984.72 | 13-FEB-16:02 | 17169.64 | 06-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.447999E+10 | 0.00 | 454.04 | 0.236354E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17394.28 | 20-MAR-15:01 | 15583.40 | 24-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.540427E+10 | 0.00 | 572.13 | 0.248549E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17237.19 | 22-APR-15:01 | 16896.83 | 01-APR-18:02 | 0.00 | 0.00 | 0.00 |
May | 0.351121E+10 | 0.00 | 511.30 | 0.132494E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17475.51 | 06-MAY-08:62 | 16048.13 | 24-MAY-08:62 | 0.00 | 0.00 | 0.00 |
June | 0.465700E+10 | 0.00 | 578.96 | 0.169646E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17886.05 | 16-JUN-15:01 | 15640.34 | 12-JUN-15:01 | 0.00 | 0.00 | 0.00 |
July | 0.724628E+10 | 0.00 | 659.51 | 0.293536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18601.18 | 30-JUL-08:61 | 15621.99 | 15-JUL-15:01 | 0.00 | 0.00 | 0.00 |
August | 0.904042E+10 | 0.00 | 679.22 | 0.399167E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18773.94 | 20-AUG-08:61 | 15414.02 | 19-AUG-18:01 | 0.00 | 0.00 | 0.00 |
September | 0.883538E+10 | 0.00 | 644.77 | 0.442872E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18246.26 | 22-SEP-08:61 | 15523.09 | 21-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.101221E+11 | 0.00 | 664.89 | 0.681537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18719.82 | 01-OCT-08:61 | 17170.23 | 25-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.782689E+10 | 0.00 | 613.09 | 0.534141E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17751.56 | 11-NOV-16:01 | 17167.29 | 30-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.817131E+10 | 0.00 | 596.07 | 0.651216E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17183.17 | 08-DEC-16:01 | 17171.09 | 05-DEC-19:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.820465E+11 | 0.00 | 7028.86 | 0.466252E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.351121E+10 | 0.00 | 454.04 | 0.132494E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17169.90 | 15414.02 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.101221E+11 | 0.00 | 679.22 | 0.681537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18773.94 | 17171.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 691.88 | 507.95 | 183.94 | 1016.06 | 360.43 | 0.00 | 0.00 | 0.00 |
February | 546.53 | 338.18 | 208.36 | 766.59 | 325.66 | 0.00 | 0.00 | 0.00 |
March | 435.89 | 212.33 | 223.56 | 608.67 | 335.19 | 0.00 | 0.00 | 0.00 |
April | 364.49 | 140.88 | 223.62 | 543.76 | 270.89 | 0.00 | 0.00 | 0.00 |
May | 256.82 | 31.10 | 225.72 | 330.29 | 237.25 | 0.00 | 0.00 | 0.00 |
June | 225.30 | 13.21 | 212.09 | 294.99 | 177.77 | 0.00 | 0.00 | 0.00 |
July | 237.61 | 25.41 | 212.20 | 350.95 | 156.85 | 0.00 | 0.00 | 0.00 |
August | 305.17 | 94.83 | 210.34 | 499.35 | 169.75 | 0.00 | 0.00 | 0.00 |
September | 419.06 | 208.19 | 210.87 | 675.52 | 203.11 | 0.00 | 0.00 | 0.00 |
October | 548.73 | 368.52 | 180.22 | 884.37 | 225.50 | 0.00 | 0.00 | 0.00 |
November | 666.54 | 472.26 | 194.28 | 981.22 | 326.07 | 0.00 | 0.00 | 0.00 |
December | 740.41 | 564.21 | 176.20 | 1092.89 | 362.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 452.81 | 247.78 | 205.03 | 670.11 | 262.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 225.30 | 13.21 | 176.20 | 294.99 | 156.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 740.41 | 564.21 | 225.72 | 1092.89 | 362.23 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1948.30 | 1430.34 | 517.96 | 2821.82 | 1101.73 | 0.00 | 0.00 | 0.00 |
February | 1539.00 | 952.28 | 586.71 | 2118.07 | 1013.97 | 0.00 | 0.00 | 0.00 |
March | 1227.43 | 597.91 | 629.52 | 1675.39 | 1033.92 | 0.00 | 0.00 | 0.00 |
April | 1026.39 | 396.71 | 629.69 | 1494.92 | 849.01 | 0.00 | 0.00 | 0.00 |
May | 723.18 | 87.58 | 635.60 | 888.77 | 751.15 | 0.00 | 0.00 | 0.00 |
June | 634.43 | 37.21 | 597.22 | 792.26 | 572.02 | 0.00 | 0.00 | 0.00 |
July | 669.08 | 71.55 | 597.53 | 959.18 | 496.83 | 0.00 | 0.00 | 0.00 |
August | 859.34 | 267.03 | 592.31 | 1383.61 | 531.54 | 0.00 | 0.00 | 0.00 |
September | 1180.05 | 586.24 | 593.81 | 1876.55 | 634.94 | 0.00 | 0.00 | 0.00 |
October | 1545.20 | 1037.72 | 507.48 | 2459.42 | 698.59 | 0.00 | 0.00 | 0.00 |
November | 1876.94 | 1329.86 | 547.08 | 2721.72 | 1006.88 | 0.00 | 0.00 | 0.00 |
December | 2084.94 | 1588.78 | 496.16 | 3036.85 | 1106.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1275.09 | 697.73 | 577.36 | 1851.63 | 815.38 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 634.43 | 37.21 | 496.16 | 792.26 | 496.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2084.94 | 1588.78 | 635.60 | 3036.85 | 1106.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2530.95 | 1858.09 | 672.86 | 3757.36 | 1452.67 | 0.00 | 0.00 | 0.00 |
February | 1999.24 | 1237.07 | 762.17 | 2816.39 | 1356.61 | 0.00 | 0.00 | 0.00 |
March | 1594.50 | 776.72 | 817.79 | 2227.13 | 1393.12 | 0.00 | 0.00 | 0.00 |
April | 1333.34 | 515.34 | 818.00 | 1990.85 | 1141.24 | 0.00 | 0.00 | 0.00 |
May | 939.45 | 113.77 | 825.68 | 1164.68 | 1032.70 | 0.00 | 0.00 | 0.00 |
June | 824.17 | 48.34 | 775.83 | 1034.75 | 788.40 | 0.00 | 0.00 | 0.00 |
July | 869.17 | 92.94 | 776.23 | 1266.53 | 678.72 | 0.00 | 0.00 | 0.00 |
August | 1116.33 | 346.89 | 769.44 | 1844.60 | 710.09 | 0.00 | 0.00 | 0.00 |
September | 1532.95 | 761.56 | 771.39 | 2502.63 | 841.59 | 0.00 | 0.00 | 0.00 |
October | 2007.30 | 1348.05 | 659.24 | 3269.04 | 919.73 | 0.00 | 0.00 | 0.00 |
November | 2438.25 | 1727.56 | 710.69 | 3619.17 | 1330.65 | 0.00 | 0.00 | 0.00 |
December | 2708.45 | 2063.92 | 644.54 | 4037.76 | 1460.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1656.41 | 906.39 | 750.02 | 2459.89 | 1090.73 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 824.17 | 48.34 | 644.54 | 1034.75 | 678.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2708.45 | 2063.92 | 825.68 | 4037.76 | 1460.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 136.80 | 100.43 | 36.37 | 203.61 | 73.29 | 0.00 | 0.00 | 0.00 |
February | 108.06 | 66.86 | 41.20 | 151.38 | 67.31 | 0.00 | 0.00 | 0.00 |
March | 86.18 | 41.98 | 44.20 | 119.08 | 71.28 | 0.00 | 0.00 | 0.00 |
April | 72.07 | 27.85 | 44.21 | 106.10 | 56.60 | 0.00 | 0.00 | 0.00 |
May | 50.78 | 6.15 | 44.63 | 61.68 | 51.06 | 0.00 | 0.00 | 0.00 |
June | 44.55 | 2.61 | 41.93 | 55.69 | 36.80 | 0.00 | 0.00 | 0.00 |
July | 46.98 | 5.02 | 41.96 | 68.93 | 30.47 | 0.00 | 0.00 | 0.00 |
August | 60.34 | 18.75 | 41.59 | 100.26 | 31.63 | 0.00 | 0.00 | 0.00 |
September | 82.86 | 41.16 | 41.69 | 135.69 | 38.16 | 0.00 | 0.00 | 0.00 |
October | 108.49 | 72.86 | 35.63 | 178.63 | 41.71 | 0.00 | 0.00 | 0.00 |
November | 131.79 | 93.37 | 38.41 | 196.27 | 65.17 | 0.00 | 0.00 | 0.00 |
December | 146.39 | 111.55 | 34.84 | 219.13 | 72.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.53 | 48.99 | 40.54 | 132.99 | 52.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 44.55 | 2.61 | 34.84 | 55.69 | 30.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 146.39 | 111.55 | 44.63 | 219.13 | 73.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 99.13 | 49.99 | 49.14 | 123.71 | 148.50 | 0.00 | 0.00 | 0.00 |
February | 118.40 | 54.72 | 63.67 | 141.67 | 132.14 | 0.00 | 0.00 | 0.00 |
March | 135.41 | 59.84 | 75.57 | 166.83 | 134.65 | 0.00 | 0.00 | 0.00 |
April | 186.62 | 97.02 | 89.60 | 263.15 | 102.11 | 0.00 | 0.00 | 0.00 |
May | 183.33 | 84.55 | 98.78 | 252.85 | 90.54 | 0.00 | 0.00 | 0.00 |
June | 194.16 | 96.95 | 97.21 | 286.20 | 64.48 | 0.00 | 0.00 | 0.00 |
July | 205.59 | 109.90 | 95.69 | 321.83 | 53.54 | 0.00 | 0.00 | 0.00 |
August | 192.92 | 104.46 | 88.46 | 304.34 | 56.63 | 0.00 | 0.00 | 0.00 |
September | 165.33 | 88.43 | 76.90 | 250.54 | 69.26 | 0.00 | 0.00 | 0.00 |
October | 127.00 | 69.58 | 57.41 | 197.85 | 81.20 | 0.00 | 0.00 | 0.00 |
November | 114.28 | 59.82 | 54.46 | 147.89 | 129.98 | 0.00 | 0.00 | 0.00 |
December | 100.52 | 53.75 | 46.77 | 127.81 | 148.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 152.02 | 77.52 | 74.51 | 215.76 | 100.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 99.13 | 49.99 | 46.77 | 123.71 | 53.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 205.59 | 109.90 | 98.78 | 321.83 | 148.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.68 | 0.00 | 20.68 | 14.35 | 79.69 | 0.00 | 0.00 | 0.00 |
February | 25.96 | 0.00 | 25.96 | 16.15 | 71.90 | 0.00 | 0.00 | 0.00 |
March | 31.81 | 0.00 | 31.81 | 23.52 | 74.09 | 0.00 | 0.00 | 0.00 |
April | 36.84 | 0.30 | 36.55 | 32.39 | 56.34 | 0.00 | 0.00 | 0.00 |
May | 44.32 | 2.31 | 42.01 | 40.99 | 48.37 | 0.00 | 0.00 | 0.00 |
June | 46.98 | 4.64 | 42.34 | 51.99 | 36.64 | 0.00 | 0.00 | 0.00 |
July | 44.50 | 3.78 | 40.73 | 55.01 | 32.55 | 0.00 | 0.00 | 0.00 |
August | 37.00 | 0.82 | 36.18 | 44.73 | 34.62 | 0.00 | 0.00 | 0.00 |
September | 31.23 | 0.01 | 31.23 | 35.41 | 41.34 | 0.00 | 0.00 | 0.00 |
October | 24.77 | 0.00 | 24.77 | 32.22 | 46.51 | 0.00 | 0.00 | 0.00 |
November | 22.43 | 0.00 | 22.43 | 16.44 | 70.90 | 0.00 | 0.00 | 0.00 |
December | 19.25 | 0.00 | 19.25 | 13.00 | 79.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.17 | 0.99 | 31.18 | 31.44 | 55.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 19.25 | 0.00 | 19.25 | 13.00 | 32.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 46.98 | 4.64 | 42.34 | 55.01 | 79.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 99.13 | 49.99 | 49.14 | 129.67 | 144.95 | 0.00 | 0.00 | 0.00 |
February | 118.40 | 54.72 | 63.67 | 145.94 | 129.76 | 0.00 | 0.00 | 0.00 |
March | 135.41 | 59.84 | 75.57 | 169.62 | 133.33 | 0.00 | 0.00 | 0.00 |
April | 186.62 | 97.02 | 89.60 | 262.11 | 103.38 | 0.00 | 0.00 | 0.00 |
May | 183.33 | 84.55 | 98.78 | 249.05 | 93.09 | 0.00 | 0.00 | 0.00 |
June | 194.16 | 96.95 | 97.21 | 278.19 | 70.43 | 0.00 | 0.00 | 0.00 |
July | 205.59 | 109.90 | 95.69 | 312.77 | 61.49 | 0.00 | 0.00 | 0.00 |
August | 192.92 | 104.46 | 88.46 | 297.99 | 64.32 | 0.00 | 0.00 | 0.00 |
September | 165.33 | 88.43 | 76.90 | 248.69 | 73.53 | 0.00 | 0.00 | 0.00 |
October | 127.00 | 69.58 | 57.41 | 198.96 | 84.26 | 0.00 | 0.00 | 0.00 |
November | 114.28 | 59.82 | 54.46 | 152.82 | 127.69 | 0.00 | 0.00 | 0.00 |
December | 100.52 | 53.75 | 46.77 | 133.83 | 144.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 152.02 | 77.52 | 74.51 | 215.31 | 102.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 99.13 | 49.99 | 46.77 | 129.67 | 61.49 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 205.59 | 109.90 | 98.78 | 312.77 | 144.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 109.42 | 80.33 | 29.09 | 148.30 | 87.20 | 0.00 | 0.00 | 0.00 |
February | 86.43 | 53.48 | 32.95 | 107.04 | 83.05 | 0.00 | 0.00 | 0.00 |
March | 68.93 | 33.58 | 35.35 | 81.83 | 85.13 | 0.00 | 0.00 | 0.00 |
April | 57.64 | 22.28 | 35.36 | 71.92 | 70.67 | 0.00 | 0.00 | 0.00 |
May | 40.61 | 4.92 | 35.70 | 36.17 | 64.92 | 0.00 | 0.00 | 0.00 |
June | 35.63 | 2.09 | 33.54 | 30.85 | 51.31 | 0.00 | 0.00 | 0.00 |
July | 37.58 | 4.02 | 33.56 | 41.28 | 44.78 | 0.00 | 0.00 | 0.00 |
August | 48.26 | 15.00 | 33.26 | 66.54 | 47.02 | 0.00 | 0.00 | 0.00 |
September | 66.27 | 32.92 | 33.35 | 95.28 | 54.27 | 0.00 | 0.00 | 0.00 |
October | 86.78 | 58.28 | 28.50 | 128.73 | 58.02 | 0.00 | 0.00 | 0.00 |
November | 105.41 | 74.68 | 30.72 | 142.45 | 79.65 | 0.00 | 0.00 | 0.00 |
December | 117.09 | 89.23 | 27.86 | 160.44 | 86.71 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 71.61 | 39.18 | 32.42 | 92.53 | 67.64 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 35.63 | 2.09 | 27.86 | 30.85 | 44.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 117.09 | 89.23 | 35.70 | 160.44 | 87.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.54 | 0.00 | 16.54 | 11.83 | 64.41 | 0.00 | 0.00 | 0.00 |
February | 20.77 | 0.00 | 20.77 | 13.50 | 57.81 | 0.00 | 0.00 | 0.00 |
March | 25.45 | 0.00 | 25.45 | 19.70 | 59.44 | 0.00 | 0.00 | 0.00 |
April | 29.48 | 0.24 | 29.24 | 29.03 | 43.17 | 0.00 | 0.00 | 0.00 |
May | 35.46 | 1.85 | 33.61 | 36.33 | 37.46 | 0.00 | 0.00 | 0.00 |
June | 37.59 | 3.71 | 33.88 | 46.11 | 27.47 | 0.00 | 0.00 | 0.00 |
July | 35.61 | 3.02 | 32.58 | 49.09 | 23.54 | 0.00 | 0.00 | 0.00 |
August | 29.60 | 0.66 | 28.95 | 40.28 | 24.69 | 0.00 | 0.00 | 0.00 |
September | 24.99 | 0.00 | 24.98 | 31.42 | 30.28 | 0.00 | 0.00 | 0.00 |
October | 19.82 | 0.00 | 19.82 | 27.82 | 35.29 | 0.00 | 0.00 | 0.00 |
November | 17.95 | 0.00 | 17.95 | 14.12 | 56.02 | 0.00 | 0.00 | 0.00 |
December | 15.40 | 0.00 | 15.40 | 10.92 | 64.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 25.74 | 0.79 | 24.95 | 27.60 | 43.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 15.40 | 0.00 | 15.40 | 10.92 | 23.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 37.59 | 3.71 | 33.88 | 49.09 | 64.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 104.03 | 55.59 | 48.45 | 125.74 | 140.81 | 0.00 | 0.00 | 0.00 |
February | 109.78 | 50.23 | 59.54 | 123.25 | 126.47 | 0.00 | 0.00 | 0.00 |
March | 133.98 | 59.84 | 74.14 | 160.12 | 128.58 | 0.00 | 0.00 | 0.00 |
April | 170.78 | 85.69 | 85.09 | 235.76 | 97.93 | 0.00 | 0.00 | 0.00 |
May | 160.86 | 67.04 | 93.82 | 216.34 | 87.74 | 0.00 | 0.00 | 0.00 |
June | 160.04 | 69.48 | 90.57 | 233.00 | 63.91 | 0.00 | 0.00 | 0.00 |
July | 181.24 | 90.04 | 91.20 | 284.30 | 53.56 | 0.00 | 0.00 | 0.00 |
August | 179.13 | 95.20 | 83.93 | 283.40 | 55.35 | 0.00 | 0.00 | 0.00 |
September | 130.78 | 60.15 | 70.63 | 194.86 | 67.78 | 0.00 | 0.00 | 0.00 |
October | 115.26 | 59.16 | 56.10 | 175.83 | 77.25 | 0.00 | 0.00 | 0.00 |
November | 104.83 | 53.07 | 51.76 | 127.94 | 124.71 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 56.17 | 44.61 | 121.29 | 140.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 137.81 | 66.94 | 70.87 | 190.62 | 96.91 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 100.77 | 50.23 | 44.61 | 121.29 | 53.56 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 181.24 | 95.20 | 93.82 | 284.30 | 140.81 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 136.80 | 100.43 | 36.37 | 202.74 | 73.08 | 0.00 | 0.00 | 0.00 |
February | 108.06 | 66.86 | 41.20 | 150.91 | 66.71 | 0.00 | 0.00 | 0.00 |
March | 86.18 | 41.98 | 44.20 | 118.22 | 70.74 | 0.00 | 0.00 | 0.00 |
April | 72.07 | 27.85 | 44.21 | 105.23 | 55.64 | 0.00 | 0.00 | 0.00 |
May | 50.78 | 6.15 | 44.63 | 61.11 | 50.06 | 0.00 | 0.00 | 0.00 |
June | 44.55 | 2.61 | 41.93 | 55.36 | 35.69 | 0.00 | 0.00 | 0.00 |
July | 46.98 | 5.02 | 41.96 | 68.31 | 29.44 | 0.00 | 0.00 | 0.00 |
August | 60.34 | 18.75 | 41.59 | 99.54 | 30.72 | 0.00 | 0.00 | 0.00 |
September | 82.86 | 41.16 | 41.69 | 135.64 | 37.00 | 0.00 | 0.00 | 0.00 |
October | 108.49 | 72.86 | 35.63 | 178.26 | 41.12 | 0.00 | 0.00 | 0.00 |
November | 131.79 | 93.37 | 38.41 | 195.83 | 64.56 | 0.00 | 0.00 | 0.00 |
December | 146.39 | 111.55 | 34.84 | 218.46 | 72.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.53 | 48.99 | 40.54 | 132.42 | 52.20 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 44.55 | 2.61 | 34.84 | 55.36 | 29.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 146.39 | 111.55 | 44.63 | 218.46 | 73.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.68 | 0.00 | 20.68 | 13.53 | 79.26 | 0.00 | 0.00 | 0.00 |
February | 25.96 | 0.00 | 25.96 | 15.55 | 70.87 | 0.00 | 0.00 | 0.00 |
March | 31.81 | 0.00 | 31.81 | 22.67 | 73.30 | 0.00 | 0.00 | 0.00 |
April | 36.84 | 0.30 | 36.55 | 31.77 | 54.64 | 0.00 | 0.00 | 0.00 |
May | 44.32 | 2.31 | 42.01 | 41.03 | 46.95 | 0.00 | 0.00 | 0.00 |
June | 46.98 | 4.64 | 42.34 | 52.88 | 34.60 | 0.00 | 0.00 | 0.00 |
July | 44.50 | 3.78 | 40.73 | 55.19 | 30.38 | 0.00 | 0.00 | 0.00 |
August | 37.00 | 0.82 | 36.18 | 44.10 | 32.43 | 0.00 | 0.00 | 0.00 |
September | 31.23 | 0.01 | 31.23 | 35.35 | 38.88 | 0.00 | 0.00 | 0.00 |
October | 24.77 | 0.00 | 24.77 | 31.50 | 45.21 | 0.00 | 0.00 | 0.00 |
November | 22.43 | 0.00 | 22.43 | 15.86 | 69.63 | 0.00 | 0.00 | 0.00 |
December | 19.25 | 0.00 | 19.25 | 12.18 | 79.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.17 | 0.99 | 31.18 | 31.06 | 54.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 19.25 | 0.00 | 19.25 | 12.18 | 30.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 46.98 | 4.64 | 42.34 | 55.19 | 79.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 104.03 | 55.59 | 48.45 | 131.07 | 136.25 | 0.00 | 0.00 | 0.00 |
February | 109.78 | 50.23 | 59.54 | 127.40 | 123.35 | 0.00 | 0.00 | 0.00 |
March | 133.98 | 59.84 | 74.14 | 163.16 | 126.90 | 0.00 | 0.00 | 0.00 |
April | 170.78 | 85.69 | 85.09 | 236.36 | 98.56 | 0.00 | 0.00 | 0.00 |
May | 160.86 | 67.04 | 93.82 | 214.22 | 89.75 | 0.00 | 0.00 | 0.00 |
June | 160.04 | 69.48 | 90.57 | 227.86 | 68.57 | 0.00 | 0.00 | 0.00 |
July | 181.24 | 90.04 | 91.20 | 277.28 | 59.98 | 0.00 | 0.00 | 0.00 |
August | 179.13 | 95.20 | 83.93 | 277.78 | 61.27 | 0.00 | 0.00 | 0.00 |
September | 130.78 | 60.15 | 70.63 | 194.15 | 70.59 | 0.00 | 0.00 | 0.00 |
October | 115.26 | 59.16 | 56.10 | 176.92 | 79.52 | 0.00 | 0.00 | 0.00 |
November | 104.83 | 53.07 | 51.76 | 132.53 | 121.04 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 56.17 | 44.61 | 126.55 | 135.97 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 137.81 | 66.94 | 70.87 | 190.88 | 97.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 100.77 | 50.23 | 44.61 | 126.55 | 59.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 181.24 | 95.20 | 93.82 | 277.78 | 136.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.19 | 0.00 | 26.19 | 18.10 | 100.96 | 0.00 | 0.00 | 0.00 |
February | 32.87 | 0.00 | 32.87 | 21.22 | 91.24 | 0.00 | 0.00 | 0.00 |
March | 40.29 | 0.00 | 40.29 | 32.09 | 91.65 | 0.00 | 0.00 | 0.00 |
April | 46.66 | 0.38 | 46.28 | 46.38 | 68.88 | 0.00 | 0.00 | 0.00 |
May | 56.13 | 2.93 | 53.20 | 58.99 | 59.66 | 0.00 | 0.00 | 0.00 |
June | 59.50 | 5.88 | 53.62 | 74.92 | 44.00 | 0.00 | 0.00 | 0.00 |
July | 56.36 | 4.78 | 51.58 | 78.26 | 38.61 | 0.00 | 0.00 | 0.00 |
August | 46.86 | 1.04 | 45.82 | 62.76 | 41.61 | 0.00 | 0.00 | 0.00 |
September | 39.55 | 0.01 | 39.55 | 48.32 | 51.14 | 0.00 | 0.00 | 0.00 |
October | 31.37 | 0.00 | 31.37 | 41.27 | 60.22 | 0.00 | 0.00 | 0.00 |
November | 28.41 | 0.00 | 28.41 | 20.74 | 91.48 | 0.00 | 0.00 | 0.00 |
December | 24.38 | 0.00 | 24.38 | 15.87 | 102.65 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.75 | 1.26 | 39.49 | 43.38 | 70.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.38 | 0.00 | 24.38 | 15.87 | 38.61 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 59.50 | 5.88 | 53.62 | 78.26 | 102.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 9.65 | 0.00 | 9.65 | 6.67 | 37.22 | 0.00 | 0.00 | 0.00 |
February | 12.12 | 0.00 | 12.12 | 7.82 | 33.63 | 0.00 | 0.00 | 0.00 |
March | 14.85 | 0.00 | 14.85 | 11.83 | 33.79 | 0.00 | 0.00 | 0.00 |
April | 17.20 | 0.14 | 17.06 | 17.10 | 25.39 | 0.00 | 0.00 | 0.00 |
May | 20.69 | 1.08 | 19.61 | 21.75 | 21.99 | 0.00 | 0.00 | 0.00 |
June | 21.93 | 2.17 | 19.77 | 27.62 | 16.22 | 0.00 | 0.00 | 0.00 |
July | 20.78 | 1.76 | 19.01 | 28.85 | 14.23 | 0.00 | 0.00 | 0.00 |
August | 17.27 | 0.38 | 16.89 | 23.14 | 15.34 | 0.00 | 0.00 | 0.00 |
September | 14.58 | 0.00 | 14.58 | 17.81 | 18.85 | 0.00 | 0.00 | 0.00 |
October | 11.57 | 0.00 | 11.57 | 15.22 | 22.20 | 0.00 | 0.00 | 0.00 |
November | 10.47 | 0.00 | 10.47 | 7.65 | 33.72 | 0.00 | 0.00 | 0.00 |
December | 8.99 | 0.00 | 8.99 | 5.85 | 37.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 15.02 | 0.46 | 14.56 | 15.99 | 25.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 8.99 | 0.00 | 8.99 | 5.85 | 14.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 21.93 | 2.17 | 19.77 | 28.85 | 37.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.83 | 46.86 | 16.97 | 96.42 | 33.59 | 0.00 | 0.00 | 0.00 |
February | 50.42 | 31.20 | 19.22 | 72.03 | 31.16 | 0.00 | 0.00 | 0.00 |
March | 40.21 | 19.59 | 20.62 | 57.15 | 32.41 | 0.00 | 0.00 | 0.00 |
April | 33.63 | 13.00 | 20.63 | 51.30 | 25.99 | 0.00 | 0.00 | 0.00 |
May | 23.69 | 2.87 | 20.82 | 30.38 | 23.75 | 0.00 | 0.00 | 0.00 |
June | 20.79 | 1.22 | 19.57 | 27.30 | 17.66 | 0.00 | 0.00 | 0.00 |
July | 21.92 | 2.34 | 19.58 | 33.11 | 15.21 | 0.00 | 0.00 | 0.00 |
August | 28.15 | 8.75 | 19.41 | 47.49 | 15.98 | 0.00 | 0.00 | 0.00 |
September | 38.66 | 19.21 | 19.45 | 64.16 | 18.75 | 0.00 | 0.00 | 0.00 |
October | 50.62 | 34.00 | 16.63 | 83.55 | 20.89 | 0.00 | 0.00 | 0.00 |
November | 61.49 | 43.57 | 17.92 | 92.67 | 30.63 | 0.00 | 0.00 | 0.00 |
December | 68.31 | 52.05 | 16.25 | 103.41 | 33.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 41.77 | 22.86 | 18.92 | 63.23 | 24.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.79 | 1.22 | 16.25 | 27.30 | 15.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 68.31 | 52.05 | 20.82 | 103.41 | 33.82 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 173.25 | 127.19 | 46.06 | 261.72 | 91.17 | 0.00 | 0.00 | 0.00 |
February | 136.85 | 84.68 | 52.17 | 195.52 | 84.57 | 0.00 | 0.00 | 0.00 |
March | 109.15 | 53.17 | 55.98 | 155.13 | 87.96 | 0.00 | 0.00 | 0.00 |
April | 91.27 | 35.28 | 55.99 | 139.25 | 70.54 | 0.00 | 0.00 | 0.00 |
May | 64.31 | 7.79 | 56.52 | 82.47 | 64.45 | 0.00 | 0.00 | 0.00 |
June | 56.42 | 3.31 | 53.11 | 74.11 | 47.94 | 0.00 | 0.00 | 0.00 |
July | 59.50 | 6.36 | 53.13 | 89.86 | 41.29 | 0.00 | 0.00 | 0.00 |
August | 76.41 | 23.74 | 52.67 | 128.90 | 43.37 | 0.00 | 0.00 | 0.00 |
September | 104.93 | 52.13 | 52.80 | 174.16 | 50.88 | 0.00 | 0.00 | 0.00 |
October | 137.40 | 92.28 | 45.13 | 226.78 | 56.71 | 0.00 | 0.00 | 0.00 |
November | 166.90 | 118.25 | 48.65 | 251.52 | 83.14 | 0.00 | 0.00 | 0.00 |
December | 185.40 | 141.28 | 44.12 | 280.69 | 91.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 113.38 | 62.04 | 51.34 | 171.61 | 67.73 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 56.42 | 3.31 | 44.12 | 74.11 | 41.29 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 185.40 | 141.28 | 56.52 | 280.69 | 91.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 136.80 | 100.43 | 36.37 | 202.50 | 72.44 | 0.00 | 0.00 | 0.00 |
February | 108.06 | 66.86 | 41.20 | 149.98 | 66.44 | 0.00 | 0.00 | 0.00 |
March | 86.18 | 41.98 | 44.20 | 117.78 | 70.80 | 0.00 | 0.00 | 0.00 |
April | 72.07 | 27.85 | 44.21 | 104.47 | 56.23 | 0.00 | 0.00 | 0.00 |
May | 50.78 | 6.15 | 44.63 | 60.32 | 50.78 | 0.00 | 0.00 | 0.00 |
June | 44.55 | 2.61 | 41.93 | 54.46 | 36.57 | 0.00 | 0.00 | 0.00 |
July | 46.98 | 5.02 | 41.96 | 67.70 | 30.21 | 0.00 | 0.00 | 0.00 |
August | 60.34 | 18.75 | 41.59 | 98.85 | 31.30 | 0.00 | 0.00 | 0.00 |
September | 82.86 | 41.16 | 41.69 | 134.16 | 37.64 | 0.00 | 0.00 | 0.00 |
October | 108.49 | 72.86 | 35.63 | 177.29 | 40.93 | 0.00 | 0.00 | 0.00 |
November | 131.79 | 93.37 | 38.41 | 194.91 | 64.24 | 0.00 | 0.00 | 0.00 |
December | 146.39 | 111.55 | 34.84 | 217.92 | 71.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.53 | 48.99 | 40.54 | 131.65 | 52.38 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 44.55 | 2.61 | 34.84 | 54.46 | 30.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 146.39 | 111.55 | 44.63 | 217.92 | 72.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 99.13 | 49.99 | 49.14 | 122.14 | 146.23 | 0.00 | 0.00 | 0.00 |
February | 118.40 | 54.72 | 63.67 | 139.76 | 129.98 | 0.00 | 0.00 | 0.00 |
March | 135.41 | 59.84 | 75.57 | 164.12 | 133.28 | 0.00 | 0.00 | 0.00 |
April | 186.62 | 97.02 | 89.60 | 258.83 | 101.17 | 0.00 | 0.00 | 0.00 |
May | 183.33 | 84.55 | 98.78 | 248.44 | 89.75 | 0.00 | 0.00 | 0.00 |
June | 194.16 | 96.95 | 97.21 | 281.40 | 63.86 | 0.00 | 0.00 | 0.00 |
July | 205.59 | 109.90 | 95.69 | 317.32 | 52.87 | 0.00 | 0.00 | 0.00 |
August | 192.92 | 104.46 | 88.46 | 300.14 | 55.88 | 0.00 | 0.00 | 0.00 |
September | 165.33 | 88.43 | 76.90 | 247.01 | 68.16 | 0.00 | 0.00 | 0.00 |
October | 127.00 | 69.58 | 57.41 | 195.80 | 79.45 | 0.00 | 0.00 | 0.00 |
November | 114.28 | 59.82 | 54.46 | 146.15 | 127.65 | 0.00 | 0.00 | 0.00 |
December | 100.52 | 53.75 | 46.77 | 126.58 | 145.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 152.02 | 77.52 | 74.51 | 212.67 | 99.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 99.13 | 49.99 | 46.77 | 122.14 | 52.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 205.59 | 109.90 | 98.78 | 317.32 | 146.23 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.68 | 0.00 | 20.68 | 14.63 | 78.20 | 0.00 | 0.00 | 0.00 |
February | 25.96 | 0.00 | 25.96 | 16.32 | 70.61 | 0.00 | 0.00 | 0.00 |
March | 31.81 | 0.00 | 31.81 | 23.17 | 73.48 | 0.00 | 0.00 | 0.00 |
April | 36.84 | 0.30 | 36.55 | 31.34 | 56.50 | 0.00 | 0.00 | 0.00 |
May | 44.32 | 2.31 | 42.01 | 39.60 | 48.52 | 0.00 | 0.00 | 0.00 |
June | 46.98 | 4.64 | 42.34 | 50.02 | 37.40 | 0.00 | 0.00 | 0.00 |
July | 44.50 | 3.78 | 40.73 | 53.17 | 33.52 | 0.00 | 0.00 | 0.00 |
August | 37.00 | 0.82 | 36.18 | 43.49 | 35.50 | 0.00 | 0.00 | 0.00 |
September | 31.23 | 0.01 | 31.23 | 34.73 | 41.37 | 0.00 | 0.00 | 0.00 |
October | 24.77 | 0.00 | 24.77 | 32.26 | 45.62 | 0.00 | 0.00 | 0.00 |
November | 22.43 | 0.00 | 22.43 | 16.77 | 69.40 | 0.00 | 0.00 | 0.00 |
December | 19.25 | 0.00 | 19.25 | 13.53 | 78.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.17 | 0.99 | 31.18 | 30.84 | 55.61 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 19.25 | 0.00 | 19.25 | 13.53 | 33.52 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 46.98 | 4.64 | 42.34 | 53.17 | 78.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 99.13 | 49.99 | 49.14 | 128.99 | 142.09 | 0.00 | 0.00 | 0.00 |
February | 118.40 | 54.72 | 63.67 | 144.67 | 127.27 | 0.00 | 0.00 | 0.00 |
March | 135.41 | 59.84 | 75.57 | 167.07 | 132.02 | 0.00 | 0.00 | 0.00 |
April | 186.62 | 97.02 | 89.60 | 257.25 | 103.20 | 0.00 | 0.00 | 0.00 |
May | 183.33 | 84.55 | 98.78 | 243.91 | 93.13 | 0.00 | 0.00 | 0.00 |
June | 194.16 | 96.95 | 97.21 | 272.06 | 71.59 | 0.00 | 0.00 | 0.00 |
July | 205.59 | 109.90 | 95.69 | 306.83 | 63.01 | 0.00 | 0.00 | 0.00 |
August | 192.92 | 104.46 | 88.46 | 292.80 | 65.50 | 0.00 | 0.00 | 0.00 |
September | 165.33 | 88.43 | 76.90 | 244.89 | 73.20 | 0.00 | 0.00 | 0.00 |
October | 127.00 | 69.58 | 57.41 | 197.30 | 82.53 | 0.00 | 0.00 | 0.00 |
November | 114.28 | 59.82 | 54.46 | 151.95 | 124.81 | 0.00 | 0.00 | 0.00 |
December | 100.52 | 53.75 | 46.77 | 133.67 | 141.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 152.02 | 77.52 | 74.51 | 212.12 | 101.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 99.13 | 49.99 | 46.77 | 128.99 | 63.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 205.59 | 109.90 | 98.78 | 306.83 | 142.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 200.63 | 147.29 | 53.34 | 292.00 | 110.76 | 0.00 | 0.00 | 0.00 |
February | 158.48 | 98.06 | 60.42 | 216.35 | 100.79 | 0.00 | 0.00 | 0.00 |
March | 126.40 | 61.57 | 64.83 | 170.40 | 105.92 | 0.00 | 0.00 | 0.00 |
April | 105.69 | 40.85 | 64.84 | 153.66 | 81.40 | 0.00 | 0.00 | 0.00 |
May | 74.47 | 9.02 | 65.45 | 90.69 | 72.41 | 0.00 | 0.00 | 0.00 |
June | 65.33 | 3.83 | 61.50 | 83.42 | 50.82 | 0.00 | 0.00 | 0.00 |
July | 68.90 | 7.37 | 61.53 | 103.25 | 41.19 | 0.00 | 0.00 | 0.00 |
August | 88.49 | 27.50 | 60.99 | 147.52 | 43.43 | 0.00 | 0.00 | 0.00 |
September | 121.52 | 60.37 | 61.15 | 197.19 | 54.02 | 0.00 | 0.00 | 0.00 |
October | 159.12 | 106.86 | 52.26 | 258.57 | 60.71 | 0.00 | 0.00 | 0.00 |
November | 193.28 | 136.94 | 56.34 | 281.93 | 97.55 | 0.00 | 0.00 | 0.00 |
December | 214.70 | 163.60 | 51.09 | 314.50 | 109.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 131.30 | 71.85 | 59.45 | 192.41 | 77.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 65.33 | 3.83 | 51.09 | 83.42 | 41.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 214.70 | 163.60 | 65.45 | 314.50 | 110.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 144.74 | 0.00 | 144.74 | 72.84 | 642.56 | 0.00 | 0.00 | 0.00 |
February | 181.69 | 0.00 | 181.69 | 83.48 | 597.54 | 0.00 | 0.00 | 0.00 |
March | 222.66 | 0.00 | 222.66 | 131.81 | 601.08 | 0.00 | 0.00 | 0.00 |
April | 257.88 | 2.08 | 255.81 | 199.88 | 450.07 | 0.00 | 0.00 | 0.00 |
May | 310.23 | 16.18 | 294.05 | 255.52 | 388.10 | 0.00 | 0.00 | 0.00 |
June | 328.85 | 32.49 | 296.36 | 343.64 | 288.93 | 0.00 | 0.00 | 0.00 |
July | 311.50 | 26.43 | 285.07 | 372.58 | 248.32 | 0.00 | 0.00 | 0.00 |
August | 258.99 | 5.75 | 253.24 | 297.48 | 267.70 | 0.00 | 0.00 | 0.00 |
September | 218.62 | 0.04 | 218.58 | 225.31 | 330.52 | 0.00 | 0.00 | 0.00 |
October | 173.40 | 0.00 | 173.40 | 198.01 | 380.72 | 0.00 | 0.00 | 0.00 |
November | 157.00 | 0.00 | 157.00 | 87.27 | 577.36 | 0.00 | 0.00 | 0.00 |
December | 134.74 | 0.00 | 134.74 | 64.28 | 645.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 225.21 | 6.95 | 218.26 | 195.03 | 450.73 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 134.74 | 0.00 | 134.74 | 64.28 | 248.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 328.85 | 32.49 | 296.36 | 372.58 | 645.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 144.74 | 0.00 | 144.74 | 65.29 | 664.25 | 0.00 | 0.00 | 0.00 |
February | 181.69 | 0.00 | 181.69 | 74.84 | 618.63 | 0.00 | 0.00 | 0.00 |
March | 222.66 | 0.00 | 222.66 | 121.10 | 620.93 | 0.00 | 0.00 | 0.00 |
April | 257.88 | 2.08 | 255.81 | 187.91 | 463.45 | 0.00 | 0.00 | 0.00 |
May | 310.23 | 16.18 | 294.05 | 241.52 | 399.01 | 0.00 | 0.00 | 0.00 |
June | 328.85 | 32.49 | 296.36 | 330.64 | 297.93 | 0.00 | 0.00 | 0.00 |
July | 311.50 | 26.43 | 285.07 | 361.02 | 256.20 | 0.00 | 0.00 | 0.00 |
August | 258.99 | 5.75 | 253.24 | 286.93 | 276.60 | 0.00 | 0.00 | 0.00 |
September | 218.62 | 0.04 | 218.58 | 215.53 | 341.91 | 0.00 | 0.00 | 0.00 |
October | 173.40 | 0.00 | 173.40 | 189.32 | 393.25 | 0.00 | 0.00 | 0.00 |
November | 157.00 | 0.00 | 157.00 | 79.17 | 595.77 | 0.00 | 0.00 | 0.00 |
December | 134.74 | 0.00 | 134.74 | 57.27 | 666.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 225.21 | 6.95 | 218.26 | 184.90 | 465.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 134.74 | 0.00 | 134.74 | 57.27 | 256.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 328.85 | 32.49 | 296.36 | 361.02 | 666.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.68 | 0.00 | 20.68 | 16.86 | 81.22 | 0.00 | 0.00 | 0.00 |
February | 25.96 | 0.00 | 25.96 | 18.58 | 77.53 | 0.00 | 0.00 | 0.00 |
March | 31.81 | 0.00 | 31.81 | 27.11 | 78.75 | 0.00 | 0.00 | 0.00 |
April | 36.84 | 0.30 | 36.55 | 40.60 | 60.00 | 0.00 | 0.00 | 0.00 |
May | 44.32 | 2.31 | 42.01 | 51.58 | 53.43 | 0.00 | 0.00 | 0.00 |
June | 46.98 | 4.64 | 42.34 | 66.25 | 40.17 | 0.00 | 0.00 | 0.00 |
July | 44.50 | 3.78 | 40.73 | 71.26 | 34.62 | 0.00 | 0.00 | 0.00 |
August | 37.00 | 0.82 | 36.18 | 58.84 | 36.57 | 0.00 | 0.00 | 0.00 |
September | 31.23 | 0.01 | 31.23 | 45.34 | 42.20 | 0.00 | 0.00 | 0.00 |
October | 24.77 | 0.00 | 24.77 | 39.83 | 48.13 | 0.00 | 0.00 | 0.00 |
November | 22.43 | 0.00 | 22.43 | 19.84 | 72.99 | 0.00 | 0.00 | 0.00 |
December | 19.25 | 0.00 | 19.25 | 15.57 | 81.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.17 | 0.99 | 31.18 | 39.44 | 58.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 19.25 | 0.00 | 19.25 | 15.57 | 34.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 46.98 | 4.64 | 42.34 | 71.26 | 81.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 208.05 | 111.16 | 96.89 | 279.99 | 284.51 | 0.00 | 0.00 | 0.00 |
February | 219.54 | 100.46 | 119.08 | 268.39 | 274.81 | 0.00 | 0.00 | 0.00 |
March | 267.94 | 119.67 | 148.26 | 345.85 | 277.73 | 0.00 | 0.00 | 0.00 |
April | 341.54 | 171.37 | 170.17 | 507.65 | 218.55 | 0.00 | 0.00 | 0.00 |
May | 321.70 | 134.06 | 187.64 | 466.11 | 202.03 | 0.00 | 0.00 | 0.00 |
June | 320.07 | 138.95 | 181.12 | 503.61 | 155.40 | 0.00 | 0.00 | 0.00 |
July | 362.45 | 180.07 | 182.38 | 612.79 | 133.70 | 0.00 | 0.00 | 0.00 |
August | 358.23 | 190.39 | 167.84 | 610.64 | 137.83 | 0.00 | 0.00 | 0.00 |
September | 261.54 | 120.30 | 141.24 | 428.29 | 156.00 | 0.00 | 0.00 | 0.00 |
October | 230.50 | 118.31 | 112.19 | 388.01 | 172.91 | 0.00 | 0.00 | 0.00 |
November | 209.64 | 106.13 | 103.51 | 283.19 | 258.08 | 0.00 | 0.00 | 0.00 |
December | 201.53 | 112.32 | 89.21 | 270.02 | 284.71 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 275.60 | 133.87 | 141.73 | 414.72 | 212.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 201.53 | 100.46 | 89.21 | 268.39 | 133.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 362.45 | 190.39 | 187.64 | 612.79 | 284.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 136.80 | 100.43 | 36.37 | 212.15 | 74.90 | 0.00 | 0.00 | 0.00 |
February | 108.06 | 66.86 | 41.20 | 157.93 | 73.36 | 0.00 | 0.00 | 0.00 |
March | 86.18 | 41.98 | 44.20 | 125.49 | 76.44 | 0.00 | 0.00 | 0.00 |
April | 72.07 | 27.85 | 44.21 | 114.79 | 61.28 | 0.00 | 0.00 | 0.00 |
May | 50.78 | 6.15 | 44.63 | 69.68 | 56.92 | 0.00 | 0.00 | 0.00 |
June | 44.55 | 2.61 | 41.93 | 65.55 | 42.90 | 0.00 | 0.00 | 0.00 |
July | 46.98 | 5.02 | 41.96 | 80.47 | 36.31 | 0.00 | 0.00 | 0.00 |
August | 60.34 | 18.75 | 41.59 | 111.53 | 37.59 | 0.00 | 0.00 | 0.00 |
September | 82.86 | 41.16 | 41.69 | 146.09 | 42.20 | 0.00 | 0.00 | 0.00 |
October | 108.49 | 72.86 | 35.63 | 188.34 | 46.36 | 0.00 | 0.00 | 0.00 |
November | 131.79 | 93.37 | 38.41 | 204.80 | 68.00 | 0.00 | 0.00 | 0.00 |
December | 146.39 | 111.55 | 34.84 | 227.62 | 74.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.53 | 48.99 | 40.54 | 142.01 | 57.49 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 44.55 | 2.61 | 34.84 | 65.55 | 36.31 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 146.39 | 111.55 | 44.63 | 227.62 | 76.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.19 | 0.00 | 26.19 | 16.02 | 102.36 | 0.00 | 0.00 | 0.00 |
February | 32.87 | 0.00 | 32.87 | 19.13 | 92.15 | 0.00 | 0.00 | 0.00 |
March | 40.29 | 0.00 | 40.29 | 29.07 | 93.54 | 0.00 | 0.00 | 0.00 |
April | 46.66 | 0.38 | 46.28 | 42.14 | 70.80 | 0.00 | 0.00 | 0.00 |
May | 56.13 | 2.93 | 53.20 | 54.65 | 61.05 | 0.00 | 0.00 | 0.00 |
June | 59.50 | 5.88 | 53.62 | 69.67 | 45.73 | 0.00 | 0.00 | 0.00 |
July | 56.36 | 4.78 | 51.58 | 72.99 | 40.31 | 0.00 | 0.00 | 0.00 |
August | 46.86 | 1.04 | 45.82 | 57.99 | 43.60 | 0.00 | 0.00 | 0.00 |
September | 39.55 | 0.01 | 39.55 | 44.60 | 52.87 | 0.00 | 0.00 | 0.00 |
October | 31.37 | 0.00 | 31.37 | 38.50 | 61.48 | 0.00 | 0.00 | 0.00 |
November | 28.41 | 0.00 | 28.41 | 18.92 | 91.70 | 0.00 | 0.00 | 0.00 |
December | 24.38 | 0.00 | 24.38 | 14.23 | 102.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.75 | 1.26 | 39.49 | 39.95 | 71.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.38 | 0.00 | 24.38 | 14.23 | 40.31 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 59.50 | 5.88 | 53.62 | 72.99 | 102.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.43 | 0.00 | 23.43 | 14.33 | 91.57 | 0.00 | 0.00 | 0.00 |
February | 29.41 | 0.00 | 29.41 | 17.11 | 82.45 | 0.00 | 0.00 | 0.00 |
March | 36.04 | 0.00 | 36.04 | 26.01 | 83.69 | 0.00 | 0.00 | 0.00 |
April | 41.74 | 0.34 | 41.41 | 37.71 | 63.34 | 0.00 | 0.00 | 0.00 |
May | 50.22 | 2.62 | 47.60 | 48.90 | 54.63 | 0.00 | 0.00 | 0.00 |
June | 53.23 | 5.26 | 47.97 | 62.34 | 40.92 | 0.00 | 0.00 | 0.00 |
July | 50.42 | 4.28 | 46.15 | 65.30 | 36.06 | 0.00 | 0.00 | 0.00 |
August | 41.92 | 0.93 | 40.99 | 51.88 | 39.01 | 0.00 | 0.00 | 0.00 |
September | 35.39 | 0.01 | 35.38 | 39.90 | 47.31 | 0.00 | 0.00 | 0.00 |
October | 28.07 | 0.00 | 28.07 | 34.44 | 55.01 | 0.00 | 0.00 | 0.00 |
November | 25.41 | 0.00 | 25.41 | 16.92 | 82.05 | 0.00 | 0.00 | 0.00 |
December | 21.81 | 0.00 | 21.81 | 12.73 | 91.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 36.46 | 1.13 | 35.33 | 35.74 | 63.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 21.81 | 0.00 | 21.81 | 12.73 | 36.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 53.23 | 5.26 | 47.97 | 65.30 | 91.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 510.71 | 374.93 | 135.77 | 760.05 | 272.38 | 0.00 | 0.00 | 0.00 |
February | 403.42 | 249.62 | 153.80 | 564.78 | 252.20 | 0.00 | 0.00 | 0.00 |
March | 321.75 | 156.73 | 165.02 | 444.59 | 265.36 | 0.00 | 0.00 | 0.00 |
April | 269.05 | 103.99 | 165.06 | 395.69 | 214.50 | 0.00 | 0.00 | 0.00 |
May | 189.57 | 22.96 | 166.61 | 229.79 | 195.62 | 0.00 | 0.00 | 0.00 |
June | 166.31 | 9.75 | 156.55 | 204.06 | 147.95 | 0.00 | 0.00 | 0.00 |
July | 175.39 | 18.75 | 156.63 | 249.90 | 128.13 | 0.00 | 0.00 | 0.00 |
August | 225.26 | 70.00 | 155.26 | 364.61 | 134.64 | 0.00 | 0.00 | 0.00 |
September | 309.33 | 153.67 | 155.66 | 499.40 | 155.39 | 0.00 | 0.00 | 0.00 |
October | 405.04 | 272.02 | 133.03 | 655.90 | 171.12 | 0.00 | 0.00 | 0.00 |
November | 492.00 | 348.59 | 143.41 | 730.72 | 245.93 | 0.00 | 0.00 | 0.00 |
December | 546.52 | 416.47 | 130.06 | 816.98 | 270.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 334.24 | 182.90 | 151.34 | 492.84 | 204.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 166.31 | 9.75 | 130.06 | 204.06 | 128.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 546.52 | 416.47 | 166.61 | 816.98 | 272.38 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.185314E+10 | 0.136048E+10 | 0.492663E+09 | 0.272142E+10 | 0.965380E+09 |
February | 0.132217E+10 | 0.818116E+09 | 0.504052E+09 | 0.185454E+10 | 0.787826E+09 |
March | 0.116748E+10 | 0.568705E+09 | 0.598776E+09 | 0.163027E+10 | 0.897761E+09 |
April | 0.944769E+09 | 0.365158E+09 | 0.579611E+09 | 0.140942E+10 | 0.702136E+09 |
May | 0.687861E+09 | 83301651.90 | 0.604559E+09 | 0.884637E+09 | 0.635446E+09 |
June | 0.583982E+09 | 34251187.10 | 0.549731E+09 | 0.764614E+09 | 0.460786E+09 |
July | 0.636401E+09 | 68053370.08 | 0.568348E+09 | 0.939993E+09 | 0.420117E+09 |
August | 0.817369E+09 | 0.253989E+09 | 0.563379E+09 | 0.133747E+10 | 0.454655E+09 |
September | 0.108621E+10 | 0.539619E+09 | 0.546586E+09 | 0.175094E+10 | 0.526449E+09 |
October | 0.146973E+10 | 0.987033E+09 | 0.482692E+09 | 0.236870E+10 | 0.603975E+09 |
November | 0.172768E+10 | 0.122410E+10 | 0.503575E+09 | 0.254333E+10 | 0.845186E+09 |
December | 0.198311E+10 | 0.151118E+10 | 0.471925E+09 | 0.292720E+10 | 0.970190E+09 |
Annual Sum or Average | 0.142799E+11 | 0.781399E+10 | 0.646590E+10 | 0.211325E+11 | 0.826991E+10 |
Minimum of Months | 0.583982E+09 | 34251187.10 | 0.471925E+09 | 0.764614E+09 | 0.420117E+09 |
Maximum of Months | 0.198311E+10 | 0.151118E+10 | 0.604559E+09 | 0.292720E+10 | 0.970190E+09 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.521833E+10 | 0.383102E+10 | 0.138731E+10 | 0.755795E+10 | 0.295088E+10 |
February | 0.372314E+10 | 0.230376E+10 | 0.141938E+10 | 0.512403E+10 | 0.245299E+10 |
March | 0.328755E+10 | 0.160144E+10 | 0.168611E+10 | 0.448738E+10 | 0.276925E+10 |
April | 0.266041E+10 | 0.102826E+10 | 0.163215E+10 | 0.387483E+10 | 0.220063E+10 |
May | 0.193697E+10 | 0.234572E+09 | 0.170240E+10 | 0.238048E+10 | 0.201187E+10 |
June | 0.164445E+10 | 96449084.55 | 0.154801E+10 | 0.205353E+10 | 0.148268E+10 |
July | 0.179206E+10 | 0.191634E+09 | 0.160043E+10 | 0.256907E+10 | 0.133070E+10 |
August | 0.230166E+10 | 0.715217E+09 | 0.158644E+10 | 0.370587E+10 | 0.142369E+10 |
September | 0.305868E+10 | 0.151953E+10 | 0.153915E+10 | 0.486402E+10 | 0.164575E+10 |
October | 0.413865E+10 | 0.277942E+10 | 0.135923E+10 | 0.658732E+10 | 0.187109E+10 |
November | 0.486503E+10 | 0.344700E+10 | 0.141803E+10 | 0.705471E+10 | 0.260984E+10 |
December | 0.558430E+10 | 0.425539E+10 | 0.132891E+10 | 0.813390E+10 | 0.296432E+10 |
Annual Sum or Average | 0.402112E+11 | 0.220037E+11 | 0.182075E+11 | 0.583931E+11 | 0.257137E+11 |
Minimum of Months | 0.164445E+10 | 96449084.55 | 0.132891E+10 | 0.205353E+10 | 0.133070E+10 |
Maximum of Months | 0.558430E+10 | 0.425539E+10 | 0.170240E+10 | 0.813390E+10 | 0.296432E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.677891E+10 | 0.497672E+10 | 0.180219E+10 | 0.100637E+11 | 0.389083E+10 |
February | 0.483657E+10 | 0.299272E+10 | 0.184385E+10 | 0.681340E+10 | 0.328191E+10 |
March | 0.427071E+10 | 0.208036E+10 | 0.219036E+10 | 0.596514E+10 | 0.373133E+10 |
April | 0.345602E+10 | 0.133577E+10 | 0.212025E+10 | 0.516028E+10 | 0.295811E+10 |
May | 0.251623E+10 | 0.304722E+09 | 0.221151E+10 | 0.311948E+10 | 0.276599E+10 |
June | 0.213624E+10 | 0.125293E+09 | 0.201095E+10 | 0.268208E+10 | 0.204353E+10 |
July | 0.232799E+10 | 0.248943E+09 | 0.207905E+10 | 0.339229E+10 | 0.181788E+10 |
August | 0.298998E+10 | 0.929108E+09 | 0.206087E+10 | 0.494059E+10 | 0.190190E+10 |
September | 0.397340E+10 | 0.197396E+10 | 0.199944E+10 | 0.648682E+10 | 0.218141E+10 |
October | 0.537634E+10 | 0.361063E+10 | 0.176572E+10 | 0.875579E+10 | 0.246341E+10 |
November | 0.631995E+10 | 0.447785E+10 | 0.184211E+10 | 0.938089E+10 | 0.344904E+10 |
December | 0.725432E+10 | 0.552799E+10 | 0.172633E+10 | 0.108147E+11 | 0.391195E+10 |
Annual Sum or Average | 0.522367E+11 | 0.285840E+11 | 0.236526E+11 | 0.775752E+11 | 0.343973E+11 |
Minimum of Months | 0.213624E+10 | 0.125293E+09 | 0.172633E+10 | 0.268208E+10 | 0.181788E+10 |
Maximum of Months | 0.725432E+10 | 0.552799E+10 | 0.221151E+10 | 0.108147E+11 | 0.391195E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.366399E+09 | 0.268990E+09 | 97408702.42 | 0.545357E+09 | 0.196305E+09 |
February | 0.261416E+09 | 0.161756E+09 | 99660556.79 | 0.366207E+09 | 0.162839E+09 |
March | 0.230832E+09 | 0.112443E+09 | 0.118389E+09 | 0.318947E+09 | 0.190923E+09 |
April | 0.186798E+09 | 72197917.93 | 0.114600E+09 | 0.275014E+09 | 0.146708E+09 |
May | 0.136003E+09 | 16470167.27 | 0.119533E+09 | 0.165206E+09 | 0.136768E+09 |
June | 0.115465E+09 | 6772047.95 | 0.108693E+09 | 0.144338E+09 | 95391844.44 |
July | 0.125829E+09 | 13455320.07 | 0.112374E+09 | 0.184628E+09 | 81615406.28 |
August | 0.161609E+09 | 50218052.04 | 0.111391E+09 | 0.268530E+09 | 84705542.82 |
September | 0.214763E+09 | 0.106692E+09 | 0.108071E+09 | 0.351713E+09 | 98921845.44 |
October | 0.290591E+09 | 0.195153E+09 | 95437466.31 | 0.478455E+09 | 0.111726E+09 |
November | 0.341593E+09 | 0.242027E+09 | 99566205.17 | 0.508722E+09 | 0.168910E+09 |
December | 0.392095E+09 | 0.298787E+09 | 93308334.56 | 0.586910E+09 | 0.195394E+09 |
Annual Sum or Average | 0.282339E+10 | 0.154496E+10 | 0.127843E+10 | 0.419403E+10 | 0.167021E+10 |
Minimum of Months | 0.115465E+09 | 6772047.95 | 93308334.56 | 0.144338E+09 | 81615406.28 |
Maximum of Months | 0.392095E+09 | 0.298787E+09 | 0.119533E+09 | 0.586910E+09 | 0.196305E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.265521E+09 | 0.133901E+09 | 0.131620E+09 | 0.331356E+09 | 0.397738E+09 |
February | 0.286426E+09 | 0.132386E+09 | 0.154039E+09 | 0.342726E+09 | 0.319678E+09 |
March | 0.362688E+09 | 0.160278E+09 | 0.202410E+09 | 0.446844E+09 | 0.360634E+09 |
April | 0.483730E+09 | 0.251482E+09 | 0.232247E+09 | 0.682078E+09 | 0.264658E+09 |
May | 0.491022E+09 | 0.226458E+09 | 0.264564E+09 | 0.677233E+09 | 0.242505E+09 |
June | 0.503264E+09 | 0.251292E+09 | 0.251972E+09 | 0.741824E+09 | 0.167139E+09 |
July | 0.550654E+09 | 0.294353E+09 | 0.256300E+09 | 0.861980E+09 | 0.143413E+09 |
August | 0.516705E+09 | 0.279782E+09 | 0.236923E+09 | 0.815155E+09 | 0.151682E+09 |
September | 0.428535E+09 | 0.229221E+09 | 0.199314E+09 | 0.649391E+09 | 0.179518E+09 |
October | 0.340146E+09 | 0.186368E+09 | 0.153778E+09 | 0.529930E+09 | 0.217473E+09 |
November | 0.296219E+09 | 0.155051E+09 | 0.141168E+09 | 0.383320E+09 | 0.336904E+09 |
December | 0.269240E+09 | 0.143959E+09 | 0.125281E+09 | 0.342335E+09 | 0.397149E+09 |
Annual Sum or Average | 0.479415E+10 | 0.244453E+10 | 0.234962E+10 | 0.680417E+10 | 0.317849E+10 |
Minimum of Months | 0.265521E+09 | 0.132386E+09 | 0.125281E+09 | 0.331356E+09 | 0.143413E+09 |
Maximum of Months | 0.550654E+09 | 0.294353E+09 | 0.264564E+09 | 0.861980E+09 | 0.397738E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 55383852.68 | 0.00 | 55383852.68 | 38422400.49 | 0.213434E+09 |
February | 62793579.01 | 0.00 | 62793579.01 | 39072199.83 | 0.173930E+09 |
March | 85200912.64 | 780.17 | 85200132.47 | 62993049.19 | 0.198444E+09 |
April | 95493362.34 | 768414.00 | 94724948.34 | 83943784.65 | 0.146023E+09 |
May | 0.118708E+09 | 6190456.55 | 0.112517E+09 | 0.109796E+09 | 0.129563E+09 |
June | 0.121773E+09 | 12029988.47 | 0.109743E+09 | 0.134751E+09 | 94970094.88 |
July | 0.119193E+09 | 10114061.15 | 0.109079E+09 | 0.147344E+09 | 87191355.49 |
August | 99102290.78 | 2201816.78 | 96900474.00 | 0.119814E+09 | 92735754.53 |
September | 80955510.48 | 16100.43 | 80939410.05 | 91787747.89 | 0.107145E+09 |
October | 66349884.71 | 0.00 | 66349884.71 | 86285095.17 | 0.124565E+09 |
November | 58137116.95 | 0.00 | 58137116.95 | 42603411.76 | 0.183775E+09 |
December | 51557659.69 | 0.00 | 51557659.69 | 34828688.74 | 0.214014E+09 |
Annual Sum or Average | 0.101465E+10 | 31321617.54 | 0.983326E+09 | 0.991642E+09 | 0.176579E+10 |
Minimum of Months | 51557659.69 | 0.00 | 51557659.69 | 34828688.74 | 87191355.49 |
Maximum of Months | 0.121773E+09 | 12029988.47 | 0.112517E+09 | 0.147344E+09 | 0.214014E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.265521E+09 | 0.133901E+09 | 0.131620E+09 | 0.347301E+09 | 0.388247E+09 |
February | 0.286426E+09 | 0.132386E+09 | 0.154039E+09 | 0.353056E+09 | 0.313910E+09 |
March | 0.362688E+09 | 0.160278E+09 | 0.202410E+09 | 0.454300E+09 | 0.357120E+09 |
April | 0.483730E+09 | 0.251482E+09 | 0.232247E+09 | 0.679392E+09 | 0.267953E+09 |
May | 0.491022E+09 | 0.226458E+09 | 0.264564E+09 | 0.667068E+09 | 0.249340E+09 |
June | 0.503264E+09 | 0.251292E+09 | 0.251972E+09 | 0.721061E+09 | 0.182553E+09 |
July | 0.550654E+09 | 0.294353E+09 | 0.256300E+09 | 0.837714E+09 | 0.164704E+09 |
August | 0.516705E+09 | 0.279782E+09 | 0.236923E+09 | 0.798140E+09 | 0.172265E+09 |
September | 0.428535E+09 | 0.229221E+09 | 0.199314E+09 | 0.644594E+09 | 0.190579E+09 |
October | 0.340146E+09 | 0.186368E+09 | 0.153778E+09 | 0.532899E+09 | 0.225684E+09 |
November | 0.296219E+09 | 0.155051E+09 | 0.141168E+09 | 0.396101E+09 | 0.330984E+09 |
December | 0.269240E+09 | 0.143959E+09 | 0.125281E+09 | 0.358454E+09 | 0.387532E+09 |
Annual Sum or Average | 0.479415E+10 | 0.244453E+10 | 0.234962E+10 | 0.679008E+10 | 0.323087E+10 |
Minimum of Months | 0.265521E+09 | 0.132386E+09 | 0.125281E+09 | 0.347301E+09 | 0.164704E+09 |
Maximum of Months | 0.550654E+09 | 0.294353E+09 | 0.264564E+09 | 0.837714E+09 | 0.388247E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.293061E+09 | 0.215149E+09 | 77911467.45 | 0.397197E+09 | 0.233546E+09 |
February | 0.209091E+09 | 0.129379E+09 | 79712592.74 | 0.258946E+09 | 0.200917E+09 |
March | 0.184629E+09 | 89936327.87 | 94692605.60 | 0.219183E+09 | 0.228011E+09 |
April | 0.149409E+09 | 57746850.06 | 91662135.38 | 0.186412E+09 | 0.183170E+09 |
May | 0.108781E+09 | 13173513.96 | 95607483.13 | 96865478.16 | 0.173892E+09 |
June | 92353413.13 | 5416561.15 | 86936851.98 | 79972363.84 | 0.133001E+09 |
July | 0.100643E+09 | 10762115.76 | 89881160.52 | 0.110551E+09 | 0.119937E+09 |
August | 0.129262E+09 | 40166453.60 | 89095338.36 | 0.178222E+09 | 0.125935E+09 |
September | 0.171776E+09 | 85336561.19 | 86439337.30 | 0.246958E+09 | 0.140662E+09 |
October | 0.232427E+09 | 0.156092E+09 | 76334792.12 | 0.344782E+09 | 0.155414E+09 |
November | 0.273220E+09 | 0.193583E+09 | 79637126.46 | 0.369242E+09 | 0.206458E+09 |
December | 0.313614E+09 | 0.238982E+09 | 74631825.39 | 0.429724E+09 | 0.232254E+09 |
Annual Sum or Average | 0.225827E+10 | 0.123572E+10 | 0.102254E+10 | 0.291805E+10 | 0.213320E+10 |
Minimum of Months | 92353413.13 | 5416561.15 | 74631825.39 | 79972363.84 | 0.119937E+09 |
Maximum of Months | 0.313614E+09 | 0.238982E+09 | 95607483.13 | 0.429724E+09 | 0.233546E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 44312955.30 | 0.00 | 44312955.30 | 31686574.94 | 0.172506E+09 |
February | 50241522.13 | 0.00 | 50241522.13 | 32658707.69 | 0.139861E+09 |
March | 68169765.21 | 624.22 | 68169140.99 | 52753290.28 | 0.159213E+09 |
April | 76404816.42 | 614812.68 | 75790003.74 | 75246460.74 | 0.111898E+09 |
May | 94978755.02 | 4953021.70 | 90025733.32 | 97299494.08 | 0.100323E+09 |
June | 97431324.50 | 9625266.49 | 87806058.00 | 0.119513E+09 | 71204884.02 |
July | 95367114.15 | 8092321.46 | 87274792.68 | 0.131486E+09 | 63044846.23 |
August | 79292341.88 | 1761686.91 | 77530654.97 | 0.107885E+09 | 66141105.79 |
September | 64772993.27 | 12882.05 | 64760111.22 | 81447027.67 | 78490635.24 |
October | 53086943.81 | 0.00 | 53086943.81 | 74525464.13 | 94533971.54 |
November | 46515858.69 | 0.00 | 46515858.69 | 36598498.63 | 0.145208E+09 |
December | 41251595.16 | 0.00 | 41251595.16 | 29253268.86 | 0.171756E+09 |
Annual Sum or Average | 0.811826E+09 | 25060615.52 | 0.786765E+09 | 0.870354E+09 | 0.137418E+10 |
Minimum of Months | 41251595.16 | 0.00 | 41251595.16 | 29253268.86 | 63044846.23 |
Maximum of Months | 97431324.50 | 9625266.49 | 90025733.32 | 0.131486E+09 | 0.172506E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.278642E+09 | 0.148882E+09 | 0.129760E+09 | 0.336791E+09 | 0.377151E+09 |
February | 0.265576E+09 | 0.121526E+09 | 0.144050E+09 | 0.298165E+09 | 0.305963E+09 |
March | 0.358848E+09 | 0.160278E+09 | 0.198570E+09 | 0.428854E+09 | 0.344389E+09 |
April | 0.442664E+09 | 0.222110E+09 | 0.220555E+09 | 0.611084E+09 | 0.253825E+09 |
May | 0.430846E+09 | 0.179547E+09 | 0.251299E+09 | 0.579454E+09 | 0.234991E+09 |
June | 0.414835E+09 | 0.180091E+09 | 0.234745E+09 | 0.603934E+09 | 0.165642E+09 |
July | 0.485425E+09 | 0.241161E+09 | 0.244264E+09 | 0.761481E+09 | 0.143449E+09 |
August | 0.479775E+09 | 0.254984E+09 | 0.224791E+09 | 0.759052E+09 | 0.148255E+09 |
September | 0.338985E+09 | 0.155919E+09 | 0.183066E+09 | 0.505084E+09 | 0.175685E+09 |
October | 0.308711E+09 | 0.158449E+09 | 0.150261E+09 | 0.470946E+09 | 0.206911E+09 |
November | 0.271708E+09 | 0.137555E+09 | 0.134153E+09 | 0.331618E+09 | 0.323236E+09 |
December | 0.269909E+09 | 0.150433E+09 | 0.119475E+09 | 0.324875E+09 | 0.376787E+09 |
Annual Sum or Average | 0.434593E+10 | 0.211093E+10 | 0.223499E+10 | 0.601134E+10 | 0.305628E+10 |
Minimum of Months | 0.265576E+09 | 0.121526E+09 | 0.119475E+09 | 0.298165E+09 | 0.143449E+09 |
Maximum of Months | 0.485425E+09 | 0.254984E+09 | 0.251299E+09 | 0.761481E+09 | 0.377151E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.366399E+09 | 0.268990E+09 | 97408702.42 | 0.543029E+09 | 0.195733E+09 |
February | 0.261416E+09 | 0.161756E+09 | 99660556.79 | 0.365090E+09 | 0.161374E+09 |
March | 0.230832E+09 | 0.112443E+09 | 0.118389E+09 | 0.316650E+09 | 0.189465E+09 |
April | 0.186798E+09 | 72197917.93 | 0.114600E+09 | 0.272767E+09 | 0.144210E+09 |
May | 0.136003E+09 | 16470167.27 | 0.119533E+09 | 0.163672E+09 | 0.134088E+09 |
June | 0.115465E+09 | 6772047.95 | 0.108693E+09 | 0.143505E+09 | 92499172.55 |
July | 0.125829E+09 | 13455320.07 | 0.112374E+09 | 0.182948E+09 | 78843483.44 |
August | 0.161609E+09 | 50218052.04 | 0.111391E+09 | 0.266604E+09 | 82277994.70 |
September | 0.214763E+09 | 0.106692E+09 | 0.108071E+09 | 0.351571E+09 | 95899773.61 |
October | 0.290591E+09 | 0.195153E+09 | 95437466.31 | 0.477450E+09 | 0.110134E+09 |
November | 0.341593E+09 | 0.242027E+09 | 99566205.17 | 0.507600E+09 | 0.167335E+09 |
December | 0.392095E+09 | 0.298787E+09 | 93308334.56 | 0.585112E+09 | 0.194311E+09 |
Annual Sum or Average | 0.282339E+10 | 0.154496E+10 | 0.127843E+10 | 0.417600E+10 | 0.164617E+10 |
Minimum of Months | 0.115465E+09 | 6772047.95 | 93308334.56 | 0.143505E+09 | 78843483.44 |
Maximum of Months | 0.392095E+09 | 0.298787E+09 | 0.119533E+09 | 0.585112E+09 | 0.195733E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 55383852.68 | 0.00 | 55383852.68 | 36246238.83 | 0.212278E+09 |
February | 62793579.01 | 0.00 | 62793579.01 | 37613177.58 | 0.171447E+09 |
March | 85200912.64 | 780.17 | 85200132.47 | 60730825.07 | 0.196328E+09 |
April | 95493362.34 | 768414.00 | 94724948.34 | 82347636.16 | 0.141621E+09 |
May | 0.118708E+09 | 6190456.55 | 0.112517E+09 | 0.109894E+09 | 0.125761E+09 |
June | 0.121773E+09 | 12029988.47 | 0.109743E+09 | 0.137071E+09 | 89672083.13 |
July | 0.119193E+09 | 10114061.15 | 0.109079E+09 | 0.147821E+09 | 81377257.06 |
August | 99102290.78 | 2201816.78 | 96900474.00 | 0.118116E+09 | 86870438.56 |
September | 80955510.48 | 16100.43 | 80939410.05 | 91636922.89 | 0.100780E+09 |
October | 66349884.71 | 0.00 | 66349884.71 | 84365758.26 | 0.121088E+09 |
November | 58137116.95 | 0.00 | 58137116.95 | 41115565.58 | 0.180490E+09 |
December | 51557659.69 | 0.00 | 51557659.69 | 32621349.57 | 0.211997E+09 |
Annual Sum or Average | 0.101465E+10 | 31321617.54 | 0.983326E+09 | 0.979579E+09 | 0.171971E+10 |
Minimum of Months | 51557659.69 | 0.00 | 51557659.69 | 32621349.57 | 81377257.06 |
Maximum of Months | 0.121773E+09 | 12029988.47 | 0.112517E+09 | 0.147821E+09 | 0.212278E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.278642E+09 | 0.148882E+09 | 0.129760E+09 | 0.351064E+09 | 0.364920E+09 |
February | 0.265576E+09 | 0.121526E+09 | 0.144050E+09 | 0.308212E+09 | 0.298407E+09 |
March | 0.358848E+09 | 0.160278E+09 | 0.198570E+09 | 0.436996E+09 | 0.339901E+09 |
April | 0.442664E+09 | 0.222110E+09 | 0.220555E+09 | 0.612633E+09 | 0.255462E+09 |
May | 0.430846E+09 | 0.179547E+09 | 0.251299E+09 | 0.573764E+09 | 0.240400E+09 |
June | 0.414835E+09 | 0.180091E+09 | 0.234745E+09 | 0.590624E+09 | 0.177742E+09 |
July | 0.485425E+09 | 0.241161E+09 | 0.244264E+09 | 0.742664E+09 | 0.160639E+09 |
August | 0.479775E+09 | 0.254984E+09 | 0.224791E+09 | 0.743994E+09 | 0.164116E+09 |
September | 0.338985E+09 | 0.155919E+09 | 0.183066E+09 | 0.503226E+09 | 0.182981E+09 |
October | 0.308711E+09 | 0.158449E+09 | 0.150261E+09 | 0.473875E+09 | 0.212993E+09 |
November | 0.271708E+09 | 0.137555E+09 | 0.134153E+09 | 0.343506E+09 | 0.313733E+09 |
December | 0.269909E+09 | 0.150433E+09 | 0.119475E+09 | 0.338952E+09 | 0.364189E+09 |
Annual Sum or Average | 0.434593E+10 | 0.211093E+10 | 0.223499E+10 | 0.601951E+10 | 0.307548E+10 |
Minimum of Months | 0.265576E+09 | 0.121526E+09 | 0.119475E+09 | 0.308212E+09 | 0.160639E+09 |
Maximum of Months | 0.485425E+09 | 0.254984E+09 | 0.251299E+09 | 0.743994E+09 | 0.364920E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 70140154.89 | 0.00 | 70140154.89 | 48475840.69 | 0.270402E+09 |
February | 79524105.76 | 0.00 | 79524105.76 | 51324386.21 | 0.220728E+09 |
March | 0.107902E+09 | 988.04 | 0.107901E+09 | 85958868.73 | 0.245478E+09 |
April | 0.120936E+09 | 973147.84 | 0.119963E+09 | 0.120216E+09 | 0.178533E+09 |
May | 0.150336E+09 | 7839822.62 | 0.142496E+09 | 0.157998E+09 | 0.159785E+09 |
June | 0.154218E+09 | 15235221.35 | 0.138983E+09 | 0.194186E+09 | 0.114040E+09 |
July | 0.150951E+09 | 12808820.29 | 0.138142E+09 | 0.209610E+09 | 0.103420E+09 |
August | 0.125507E+09 | 2788462.02 | 0.122718E+09 | 0.168090E+09 | 0.111446E+09 |
September | 0.102525E+09 | 20390.18 | 0.102505E+09 | 0.125258E+09 | 0.132563E+09 |
October | 84027942.54 | 0.00 | 84027942.54 | 0.110547E+09 | 0.161296E+09 |
November | 73626990.37 | 0.00 | 73626990.37 | 53767912.57 | 0.237128E+09 |
December | 65294522.88 | 0.00 | 65294522.88 | 42515156.73 | 0.274934E+09 |
Annual Sum or Average | 0.128499E+10 | 39666852.34 | 0.124532E+10 | 0.136795E+10 | 0.220975E+10 |
Minimum of Months | 65294522.88 | 0.00 | 65294522.88 | 42515156.73 | 0.103420E+09 |
Maximum of Months | 0.154218E+09 | 15235221.35 | 0.142496E+09 | 0.209610E+09 | 0.274934E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 25856565.37 | 0.00 | 25856565.37 | 17870202.11 | 99681391.10 |
February | 29315878.22 | 0.00 | 29315878.22 | 18920293.93 | 81369585.30 |
March | 39776990.23 | 364.23 | 39776626.00 | 31687998.29 | 90493271.29 |
April | 44582134.43 | 358742.59 | 44223391.84 | 44316734.82 | 65814697.45 |
May | 55420009.14 | 2890083.24 | 52529925.90 | 58244779.75 | 58903449.98 |
June | 56851080.99 | 5616333.43 | 51234747.56 | 71584835.35 | 42039828.44 |
July | 55646616.31 | 4721861.53 | 50924754.78 | 77271047.37 | 38124715.41 |
August | 46267002.67 | 1027942.56 | 45239060.11 | 61965102.21 | 41083672.15 |
September | 37794977.19 | 7516.66 | 37787460.52 | 46175120.50 | 48868082.42 |
October | 30976178.94 | 0.00 | 30976178.94 | 40752191.94 | 59460200.47 |
November | 27141957.31 | 0.00 | 27141957.31 | 19821078.93 | 87415099.96 |
December | 24070264.77 | 0.00 | 24070264.77 | 15672847.19 | 0.101352E+09 |
Annual Sum or Average | 0.473700E+09 | 14622844.25 | 0.459077E+09 | 0.504282E+09 | 0.814606E+09 |
Minimum of Months | 24070264.77 | 0.00 | 24070264.77 | 15672847.19 | 38124715.41 |
Maximum of Months | 56851080.99 | 5616333.43 | 52529925.90 | 77271047.37 | 0.101352E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.170960E+09 | 0.125510E+09 | 45450508.02 | 0.258263E+09 | 89971567.32 |
February | 0.121976E+09 | 75474510.52 | 46501214.20 | 0.174266E+09 | 75375102.37 |
March | 0.107705E+09 | 52465342.08 | 55239968.79 | 0.153082E+09 | 86798167.04 |
April | 87159368.36 | 33687257.57 | 53472110.79 | 0.132980E+09 | 67367612.15 |
May | 63458586.31 | 7684913.68 | 55773672.63 | 81380718.02 | 63602511.08 |
June | 53875375.24 | 3159810.28 | 50715564.96 | 70772448.17 | 45786200.87 |
July | 58711357.72 | 6278198.12 | 52433159.60 | 88671594.36 | 40747546.42 |
August | 75406282.36 | 23431540.72 | 51974741.64 | 0.127196E+09 | 42793541.33 |
September | 0.100207E+09 | 49782017.80 | 50425334.32 | 0.166314E+09 | 48589230.92 |
October | 0.135589E+09 | 91057819.93 | 44530737.20 | 0.223784E+09 | 55962286.00 |
November | 0.159386E+09 | 0.112929E+09 | 46457190.11 | 0.240195E+09 | 79394351.18 |
December | 0.182950E+09 | 0.139413E+09 | 43537292.90 | 0.276986E+09 | 90581005.15 |
Annual Sum or Average | 0.131738E+10 | 0.720873E+09 | 0.596511E+09 | 0.199389E+10 | 0.786969E+09 |
Minimum of Months | 53875375.24 | 3159810.28 | 43537292.90 | 70772448.17 | 40747546.42 |
Maximum of Months | 0.182950E+09 | 0.139413E+09 | 55773672.63 | 0.276986E+09 | 90581005.15 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.464021E+09 | 0.340659E+09 | 0.123362E+09 | 0.700978E+09 | 0.244201E+09 |
February | 0.331067E+09 | 0.204853E+09 | 0.126214E+09 | 0.472993E+09 | 0.204583E+09 |
March | 0.292334E+09 | 0.142402E+09 | 0.149933E+09 | 0.415496E+09 | 0.235588E+09 |
April | 0.236568E+09 | 91434107.63 | 0.145134E+09 | 0.360934E+09 | 0.182850E+09 |
May | 0.172240E+09 | 20858427.64 | 0.151381E+09 | 0.220884E+09 | 0.172630E+09 |
June | 0.146229E+09 | 8576371.43 | 0.137652E+09 | 0.192091E+09 | 0.124273E+09 |
July | 0.159355E+09 | 17040313.89 | 0.142314E+09 | 0.240673E+09 | 0.110597E+09 |
August | 0.204668E+09 | 63597994.32 | 0.141070E+09 | 0.345235E+09 | 0.116150E+09 |
September | 0.271983E+09 | 0.135119E+09 | 0.136865E+09 | 0.451410E+09 | 0.131881E+09 |
October | 0.368015E+09 | 0.247150E+09 | 0.120866E+09 | 0.607397E+09 | 0.151893E+09 |
November | 0.432606E+09 | 0.306511E+09 | 0.126094E+09 | 0.651938E+09 | 0.215493E+09 |
December | 0.496564E+09 | 0.378395E+09 | 0.118169E+09 | 0.751797E+09 | 0.245855E+09 |
Annual Sum or Average | 0.357565E+10 | 0.195660E+10 | 0.161905E+10 | 0.541183E+10 | 0.213600E+10 |
Minimum of Months | 0.146229E+09 | 8576371.43 | 0.118169E+09 | 0.192091E+09 | 0.110597E+09 |
Maximum of Months | 0.496564E+09 | 0.378395E+09 | 0.151381E+09 | 0.751797E+09 | 0.245855E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.366399E+09 | 0.268990E+09 | 97408702.42 | 0.542386E+09 | 0.194015E+09 |
February | 0.261416E+09 | 0.161756E+09 | 99660556.79 | 0.362826E+09 | 0.160720E+09 |
March | 0.230832E+09 | 0.112443E+09 | 0.118389E+09 | 0.315470E+09 | 0.189643E+09 |
April | 0.186798E+09 | 72197917.93 | 0.114600E+09 | 0.270798E+09 | 0.145741E+09 |
May | 0.136003E+09 | 16470167.27 | 0.119533E+09 | 0.161566E+09 | 0.136019E+09 |
June | 0.115465E+09 | 6772047.95 | 0.108693E+09 | 0.141166E+09 | 94791978.36 |
July | 0.125829E+09 | 13455320.07 | 0.112374E+09 | 0.181332E+09 | 80923366.83 |
August | 0.161609E+09 | 50218052.04 | 0.111391E+09 | 0.264750E+09 | 83821348.31 |
September | 0.214763E+09 | 0.106692E+09 | 0.108071E+09 | 0.347750E+09 | 97563405.35 |
October | 0.290591E+09 | 0.195153E+09 | 95437466.31 | 0.474853E+09 | 0.109626E+09 |
November | 0.341593E+09 | 0.242027E+09 | 99566205.17 | 0.505207E+09 | 0.166506E+09 |
December | 0.392095E+09 | 0.298787E+09 | 93308334.56 | 0.583685E+09 | 0.192519E+09 |
Annual Sum or Average | 0.282339E+10 | 0.154496E+10 | 0.127843E+10 | 0.415179E+10 | 0.165189E+10 |
Minimum of Months | 0.115465E+09 | 6772047.95 | 93308334.56 | 0.141166E+09 | 80923366.83 |
Maximum of Months | 0.392095E+09 | 0.298787E+09 | 0.119533E+09 | 0.583685E+09 | 0.194015E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.265521E+09 | 0.133901E+09 | 0.131620E+09 | 0.327150E+09 | 0.391669E+09 |
February | 0.286426E+09 | 0.132386E+09 | 0.154039E+09 | 0.338106E+09 | 0.314459E+09 |
March | 0.362688E+09 | 0.160278E+09 | 0.202410E+09 | 0.439577E+09 | 0.356986E+09 |
April | 0.483730E+09 | 0.251482E+09 | 0.232247E+09 | 0.670891E+09 | 0.262225E+09 |
May | 0.491022E+09 | 0.226458E+09 | 0.264564E+09 | 0.665431E+09 | 0.240391E+09 |
June | 0.503264E+09 | 0.251292E+09 | 0.251972E+09 | 0.729399E+09 | 0.165523E+09 |
July | 0.550654E+09 | 0.294353E+09 | 0.256300E+09 | 0.849912E+09 | 0.141613E+09 |
August | 0.516705E+09 | 0.279782E+09 | 0.236923E+09 | 0.803898E+09 | 0.149662E+09 |
September | 0.428535E+09 | 0.229221E+09 | 0.199314E+09 | 0.640247E+09 | 0.176679E+09 |
October | 0.340146E+09 | 0.186368E+09 | 0.153778E+09 | 0.524428E+09 | 0.212810E+09 |
November | 0.296219E+09 | 0.155051E+09 | 0.141168E+09 | 0.378815E+09 | 0.330872E+09 |
December | 0.269240E+09 | 0.143959E+09 | 0.125281E+09 | 0.339019E+09 | 0.389831E+09 |
Annual Sum or Average | 0.479415E+10 | 0.244453E+10 | 0.234962E+10 | 0.670687E+10 | 0.313272E+10 |
Minimum of Months | 0.265521E+09 | 0.132386E+09 | 0.125281E+09 | 0.327150E+09 | 0.141613E+09 |
Maximum of Months | 0.550654E+09 | 0.294353E+09 | 0.264564E+09 | 0.849912E+09 | 0.391669E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 55383852.68 | 0.00 | 55383852.68 | 39197142.67 | 0.209440E+09 |
February | 62793579.01 | 0.00 | 62793579.01 | 39477708.15 | 0.170824E+09 |
March | 85200912.64 | 780.17 | 85200132.47 | 62055421.75 | 0.196819E+09 |
April | 95493362.34 | 768414.00 | 94724948.34 | 81232317.52 | 0.146452E+09 |
May | 0.118708E+09 | 6190456.55 | 0.112517E+09 | 0.106056E+09 | 0.129963E+09 |
June | 0.121773E+09 | 12029988.47 | 0.109743E+09 | 0.129652E+09 | 96941646.34 |
July | 0.119193E+09 | 10114061.15 | 0.109079E+09 | 0.142408E+09 | 89791439.73 |
August | 99102290.78 | 2201816.78 | 96900474.00 | 0.116494E+09 | 95086251.97 |
September | 80955510.48 | 16100.43 | 80939410.05 | 90028307.27 | 0.107236E+09 |
October | 66349884.71 | 0.00 | 66349884.71 | 86403839.10 | 0.122201E+09 |
November | 58137116.95 | 0.00 | 58137116.95 | 43478712.08 | 0.179893E+09 |
December | 51557659.69 | 0.00 | 51557659.69 | 36226830.80 | 0.209069E+09 |
Annual Sum or Average | 0.101465E+10 | 31321617.54 | 0.983326E+09 | 0.972710E+09 | 0.175372E+10 |
Minimum of Months | 51557659.69 | 0.00 | 51557659.69 | 36226830.80 | 89791439.73 |
Maximum of Months | 0.121773E+09 | 12029988.47 | 0.112517E+09 | 0.142408E+09 | 0.209440E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.265521E+09 | 0.133901E+09 | 0.131620E+09 | 0.345479E+09 | 0.380570E+09 |
February | 0.286426E+09 | 0.132386E+09 | 0.154039E+09 | 0.349981E+09 | 0.307885E+09 |
March | 0.362688E+09 | 0.160278E+09 | 0.202410E+09 | 0.447467E+09 | 0.353592E+09 |
April | 0.483730E+09 | 0.251482E+09 | 0.232247E+09 | 0.666803E+09 | 0.267485E+09 |
May | 0.491022E+09 | 0.226458E+09 | 0.264564E+09 | 0.653277E+09 | 0.249444E+09 |
June | 0.503264E+09 | 0.251292E+09 | 0.251972E+09 | 0.705169E+09 | 0.185550E+09 |
July | 0.550654E+09 | 0.294353E+09 | 0.256300E+09 | 0.821809E+09 | 0.168764E+09 |
August | 0.516705E+09 | 0.279782E+09 | 0.236923E+09 | 0.784242E+09 | 0.175428E+09 |
September | 0.428535E+09 | 0.229221E+09 | 0.199314E+09 | 0.634757E+09 | 0.189746E+09 |
October | 0.340146E+09 | 0.186368E+09 | 0.153778E+09 | 0.528457E+09 | 0.221054E+09 |
November | 0.296219E+09 | 0.155051E+09 | 0.141168E+09 | 0.393857E+09 | 0.323501E+09 |
December | 0.269240E+09 | 0.143959E+09 | 0.125281E+09 | 0.358014E+09 | 0.378241E+09 |
Annual Sum or Average | 0.479415E+10 | 0.244453E+10 | 0.234962E+10 | 0.668931E+10 | 0.320126E+10 |
Minimum of Months | 0.265521E+09 | 0.132386E+09 | 0.125281E+09 | 0.345479E+09 | 0.168764E+09 |
Maximum of Months | 0.550654E+09 | 0.294353E+09 | 0.264564E+09 | 0.821809E+09 | 0.380570E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.537359E+09 | 0.394500E+09 | 0.142859E+09 | 0.782103E+09 | 0.296664E+09 |
February | 0.383392E+09 | 0.237230E+09 | 0.146162E+09 | 0.523393E+09 | 0.243836E+09 |
March | 0.338537E+09 | 0.164908E+09 | 0.173629E+09 | 0.456411E+09 | 0.283687E+09 |
April | 0.273958E+09 | 0.105885E+09 | 0.168073E+09 | 0.398288E+09 | 0.211001E+09 |
May | 0.199462E+09 | 24155080.95 | 0.175307E+09 | 0.242915E+09 | 0.193931E+09 |
June | 0.169340E+09 | 9931858.23 | 0.159408E+09 | 0.216223E+09 | 0.131714E+09 |
July | 0.184540E+09 | 19733518.19 | 0.164807E+09 | 0.276549E+09 | 0.110322E+09 |
August | 0.237016E+09 | 73649592.75 | 0.163366E+09 | 0.395121E+09 | 0.116320E+09 |
September | 0.314970E+09 | 0.156474E+09 | 0.158496E+09 | 0.511124E+09 | 0.140031E+09 |
October | 0.426179E+09 | 0.286211E+09 | 0.139968E+09 | 0.692546E+09 | 0.162618E+09 |
November | 0.500979E+09 | 0.354955E+09 | 0.146023E+09 | 0.730762E+09 | 0.252845E+09 |
December | 0.575045E+09 | 0.438199E+09 | 0.136846E+09 | 0.842359E+09 | 0.294459E+09 |
Annual Sum or Average | 0.414078E+10 | 0.226583E+10 | 0.187494E+10 | 0.606779E+10 | 0.243743E+10 |
Minimum of Months | 0.169340E+09 | 9931858.23 | 0.136846E+09 | 0.216223E+09 | 0.110322E+09 |
Maximum of Months | 0.575045E+09 | 0.438199E+09 | 0.175307E+09 | 0.842359E+09 | 0.296664E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.387672E+09 | 0.00 | 0.387672E+09 | 0.195093E+09 | 0.172104E+10 |
February | 0.439538E+09 | 0.00 | 0.439538E+09 | 0.201945E+09 | 0.144557E+10 |
March | 0.596384E+09 | 5460.98 | 0.596378E+09 | 0.353029E+09 | 0.160994E+10 |
April | 0.668428E+09 | 5378694.26 | 0.663050E+09 | 0.518092E+09 | 0.116659E+10 |
May | 0.830922E+09 | 43331554.67 | 0.787591E+09 | 0.684379E+09 | 0.103947E+10 |
June | 0.852379E+09 | 84206730.00 | 0.768172E+09 | 0.890702E+09 | 0.748895E+09 |
July | 0.834320E+09 | 70795746.72 | 0.763524E+09 | 0.997916E+09 | 0.665106E+09 |
August | 0.693690E+09 | 15412133.73 | 0.678278E+09 | 0.796773E+09 | 0.717001E+09 |
September | 0.566667E+09 | 112698.72 | 0.566554E+09 | 0.583992E+09 | 0.856711E+09 |
October | 0.464432E+09 | 0.00 | 0.464432E+09 | 0.530344E+09 | 0.101972E+10 |
November | 0.406944E+09 | 0.00 | 0.406944E+09 | 0.226195E+09 | 0.149651E+10 |
December | 0.360890E+09 | 0.00 | 0.360890E+09 | 0.172162E+09 | 0.172772E+10 |
Annual Sum or Average | 0.710227E+10 | 0.219243E+09 | 0.688302E+10 | 0.615062E+10 | 0.142143E+11 |
Minimum of Months | 0.360890E+09 | 0.00 | 0.360890E+09 | 0.172162E+09 | 0.665106E+09 |
Maximum of Months | 0.852379E+09 | 84206730.00 | 0.787591E+09 | 0.997916E+09 | 0.172772E+10 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.387672E+09 | 0.00 | 0.387672E+09 | 0.174883E+09 | 0.177913E+10 |
February | 0.439538E+09 | 0.00 | 0.439538E+09 | 0.181055E+09 | 0.149660E+10 |
March | 0.596384E+09 | 5460.98 | 0.596378E+09 | 0.324352E+09 | 0.166310E+10 |
April | 0.668428E+09 | 5378694.26 | 0.663050E+09 | 0.487066E+09 | 0.120127E+10 |
May | 0.830922E+09 | 43331554.67 | 0.787591E+09 | 0.646885E+09 | 0.106872E+10 |
June | 0.852379E+09 | 84206730.00 | 0.768172E+09 | 0.857032E+09 | 0.772225E+09 |
July | 0.834320E+09 | 70795746.72 | 0.763524E+09 | 0.966948E+09 | 0.686198E+09 |
August | 0.693690E+09 | 15412133.73 | 0.678278E+09 | 0.768502E+09 | 0.740858E+09 |
September | 0.566667E+09 | 112698.72 | 0.566554E+09 | 0.558646E+09 | 0.886221E+09 |
October | 0.464432E+09 | 0.00 | 0.464432E+09 | 0.507066E+09 | 0.105329E+10 |
November | 0.406944E+09 | 0.00 | 0.406944E+09 | 0.205209E+09 | 0.154424E+10 |
December | 0.360890E+09 | 0.00 | 0.360890E+09 | 0.153389E+09 | 0.178504E+10 |
Annual Sum or Average | 0.710227E+10 | 0.219243E+09 | 0.688302E+10 | 0.583103E+10 | 0.146769E+11 |
Minimum of Months | 0.360890E+09 | 0.00 | 0.360890E+09 | 0.153389E+09 | 0.686198E+09 |
Maximum of Months | 0.852379E+09 | 84206730.00 | 0.787591E+09 | 0.966948E+09 | 0.178504E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 55383852.68 | 0.00 | 55383852.68 | 45168875.35 | 0.217551E+09 |
February | 62793579.01 | 0.00 | 62793579.01 | 44936884.57 | 0.187557E+09 |
March | 85200912.64 | 780.17 | 85200132.47 | 72611637.93 | 0.210929E+09 |
April | 95493362.34 | 768414.00 | 94724948.34 | 0.105236E+09 | 0.155519E+09 |
May | 0.118708E+09 | 6190456.55 | 0.112517E+09 | 0.138154E+09 | 0.143112E+09 |
June | 0.121773E+09 | 12029988.47 | 0.109743E+09 | 0.171731E+09 | 0.104109E+09 |
July | 0.119193E+09 | 10114061.15 | 0.109079E+09 | 0.190863E+09 | 92721957.90 |
August | 99102290.78 | 2201816.78 | 96900474.00 | 0.157599E+09 | 97946510.86 |
September | 80955510.48 | 16100.43 | 80939410.05 | 0.117515E+09 | 0.109370E+09 |
October | 66349884.71 | 0.00 | 66349884.71 | 0.106679E+09 | 0.128922E+09 |
November | 58137116.95 | 0.00 | 58137116.95 | 51414582.13 | 0.189184E+09 |
December | 51557659.69 | 0.00 | 51557659.69 | 41714736.56 | 0.218147E+09 |
Annual Sum or Average | 0.101465E+10 | 31321617.54 | 0.983326E+09 | 0.124362E+10 | 0.185507E+10 |
Minimum of Months | 51557659.69 | 0.00 | 51557659.69 | 41714736.56 | 92721957.90 |
Maximum of Months | 0.121773E+09 | 12029988.47 | 0.112517E+09 | 0.190863E+09 | 0.218147E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.557245E+09 | 0.297743E+09 | 0.259502E+09 | 0.749922E+09 | 0.762029E+09 |
February | 0.531115E+09 | 0.243035E+09 | 0.288080E+09 | 0.649298E+09 | 0.664826E+09 |
March | 0.717645E+09 | 0.320532E+09 | 0.397113E+09 | 0.926336E+09 | 0.743870E+09 |
April | 0.885266E+09 | 0.444188E+09 | 0.441078E+09 | 0.131584E+10 | 0.566487E+09 |
May | 0.861631E+09 | 0.359068E+09 | 0.502562E+09 | 0.124843E+10 | 0.541126E+09 |
June | 0.829612E+09 | 0.360156E+09 | 0.469456E+09 | 0.130535E+10 | 0.402793E+09 |
July | 0.970781E+09 | 0.482287E+09 | 0.488494E+09 | 0.164129E+10 | 0.358098E+09 |
August | 0.959482E+09 | 0.509932E+09 | 0.449550E+09 | 0.163553E+10 | 0.369152E+09 |
September | 0.677922E+09 | 0.311816E+09 | 0.366105E+09 | 0.111013E+10 | 0.404352E+09 |
October | 0.617378E+09 | 0.316876E+09 | 0.300501E+09 | 0.103924E+10 | 0.463130E+09 |
November | 0.543378E+09 | 0.275091E+09 | 0.268287E+09 | 0.734035E+09 | 0.668938E+09 |
December | 0.539779E+09 | 0.300845E+09 | 0.238934E+09 | 0.723231E+09 | 0.762555E+09 |
Annual Sum or Average | 0.869123E+10 | 0.422157E+10 | 0.446966E+10 | 0.130786E+11 | 0.670736E+10 |
Minimum of Months | 0.531115E+09 | 0.243035E+09 | 0.238934E+09 | 0.649298E+09 | 0.358098E+09 |
Maximum of Months | 0.970781E+09 | 0.509932E+09 | 0.502562E+09 | 0.164129E+10 | 0.762555E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.366399E+09 | 0.268990E+09 | 97408702.42 | 0.568230E+09 | 0.200601E+09 |
February | 0.261416E+09 | 0.161756E+09 | 99660556.79 | 0.382072E+09 | 0.177468E+09 |
March | 0.230832E+09 | 0.112443E+09 | 0.118389E+09 | 0.336117E+09 | 0.204740E+09 |
April | 0.186798E+09 | 72197917.93 | 0.114600E+09 | 0.297543E+09 | 0.158825E+09 |
May | 0.136003E+09 | 16470167.27 | 0.119533E+09 | 0.186639E+09 | 0.152444E+09 |
June | 0.115465E+09 | 6772047.95 | 0.108693E+09 | 0.169899E+09 | 0.111197E+09 |
July | 0.125829E+09 | 13455320.07 | 0.112374E+09 | 0.215526E+09 | 97241350.65 |
August | 0.161609E+09 | 50218052.04 | 0.111391E+09 | 0.298718E+09 | 0.100683E+09 |
September | 0.214763E+09 | 0.106692E+09 | 0.108071E+09 | 0.378656E+09 | 0.109383E+09 |
October | 0.290591E+09 | 0.195153E+09 | 95437466.31 | 0.504461E+09 | 0.124169E+09 |
November | 0.341593E+09 | 0.242027E+09 | 99566205.17 | 0.530851E+09 | 0.176244E+09 |
December | 0.392095E+09 | 0.298787E+09 | 93308334.56 | 0.609649E+09 | 0.199909E+09 |
Annual Sum or Average | 0.282339E+10 | 0.154496E+10 | 0.127843E+10 | 0.447836E+10 | 0.181290E+10 |
Minimum of Months | 0.115465E+09 | 6772047.95 | 93308334.56 | 0.169899E+09 | 97241350.65 |
Maximum of Months | 0.392095E+09 | 0.298787E+09 | 0.119533E+09 | 0.609649E+09 | 0.204740E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 70140154.89 | 0.00 | 70140154.89 | 42906869.95 | 0.274160E+09 |
February | 79524105.76 | 0.00 | 79524105.76 | 46271646.60 | 0.222932E+09 |
March | 0.107902E+09 | 988.04 | 0.107901E+09 | 77855812.46 | 0.250542E+09 |
April | 0.120936E+09 | 973147.84 | 0.119963E+09 | 0.109237E+09 | 0.183502E+09 |
May | 0.150336E+09 | 7839822.62 | 0.142496E+09 | 0.146375E+09 | 0.163528E+09 |
June | 0.154218E+09 | 15235221.35 | 0.138983E+09 | 0.180592E+09 | 0.118537E+09 |
July | 0.150951E+09 | 12808820.29 | 0.138142E+09 | 0.195485E+09 | 0.107961E+09 |
August | 0.125507E+09 | 2788462.02 | 0.122718E+09 | 0.155316E+09 | 0.116772E+09 |
September | 0.102525E+09 | 20390.18 | 0.102505E+09 | 0.115591E+09 | 0.137047E+09 |
October | 84027942.54 | 0.00 | 84027942.54 | 0.103105E+09 | 0.164673E+09 |
November | 73626990.37 | 0.00 | 73626990.37 | 49030835.91 | 0.237698E+09 |
December | 65294522.88 | 0.00 | 65294522.88 | 38122350.99 | 0.275185E+09 |
Annual Sum or Average | 0.128499E+10 | 39666852.34 | 0.124532E+10 | 0.125989E+10 | 0.225254E+10 |
Minimum of Months | 65294522.88 | 0.00 | 65294522.88 | 38122350.99 | 0.107961E+09 |
Maximum of Months | 0.154218E+09 | 15235221.35 | 0.142496E+09 | 0.195485E+09 | 0.275185E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62754662.34 | 0.00 | 62754662.34 | 38388939.12 | 0.245269E+09 |
February | 71150518.74 | 0.00 | 71150518.74 | 41399417.53 | 0.199459E+09 |
March | 96539952.45 | 884.00 | 96539068.45 | 69657890.40 | 0.224161E+09 |
April | 0.108202E+09 | 870679.06 | 0.107332E+09 | 97734885.20 | 0.164180E+09 |
May | 0.134506E+09 | 7014319.00 | 0.127492E+09 | 0.130962E+09 | 0.146309E+09 |
June | 0.137979E+09 | 13631010.27 | 0.124348E+09 | 0.161577E+09 | 0.106055E+09 |
July | 0.135056E+09 | 11460100.04 | 0.123596E+09 | 0.174901E+09 | 96592830.58 |
August | 0.112291E+09 | 2494847.54 | 0.109797E+09 | 0.138962E+09 | 0.104476E+09 |
September | 91729547.13 | 18243.17 | 91711303.96 | 0.103419E+09 | 0.122616E+09 |
October | 75180118.57 | 0.00 | 75180118.57 | 92248472.72 | 0.147333E+09 |
November | 65874347.26 | 0.00 | 65874347.26 | 43868074.67 | 0.212667E+09 |
December | 58419257.03 | 0.00 | 58419257.03 | 34108211.88 | 0.246175E+09 |
Annual Sum or Average | 0.114968E+10 | 35490083.08 | 0.111419E+10 | 0.112723E+10 | 0.201529E+10 |
Minimum of Months | 58419257.03 | 0.00 | 58419257.03 | 34108211.88 | 96592830.58 |
Maximum of Months | 0.137979E+09 | 13631010.27 | 0.127492E+09 | 0.174901E+09 | 0.246175E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.136788E+10 | 0.100422E+10 | 0.363656E+09 | 0.203571E+10 | 0.729542E+09 |
February | 0.975944E+09 | 0.603882E+09 | 0.372063E+09 | 0.136632E+10 | 0.610132E+09 |
March | 0.861765E+09 | 0.419782E+09 | 0.441983E+09 | 0.119078E+10 | 0.710730E+09 |
April | 0.697374E+09 | 0.269536E+09 | 0.427838E+09 | 0.102564E+10 | 0.555975E+09 |
May | 0.507741E+09 | 61488042.30 | 0.446253E+09 | 0.615465E+09 | 0.523954E+09 |
June | 0.431064E+09 | 25282072.96 | 0.405782E+09 | 0.528915E+09 | 0.383478E+09 |
July | 0.469758E+09 | 50232719.31 | 0.419525E+09 | 0.669325E+09 | 0.343185E+09 |
August | 0.603336E+09 | 0.187479E+09 | 0.415857E+09 | 0.976568E+09 | 0.360622E+09 |
September | 0.801773E+09 | 0.398313E+09 | 0.403460E+09 | 0.129445E+10 | 0.402767E+09 |
October | 0.108486E+10 | 0.728566E+09 | 0.356297E+09 | 0.175677E+10 | 0.458319E+09 |
November | 0.127527E+10 | 0.903557E+09 | 0.371710E+09 | 0.189402E+10 | 0.637461E+09 |
December | 0.146381E+10 | 0.111546E+10 | 0.348348E+09 | 0.218820E+10 | 0.725729E+09 |
Annual Sum or Average | 0.105406E+11 | 0.576780E+10 | 0.477277E+10 | 0.155422E+11 | 0.644189E+10 |
Minimum of Months | 0.431064E+09 | 25282072.96 | 0.348348E+09 | 0.528915E+09 | 0.343185E+09 |
Maximum of Months | 0.146381E+10 | 0.111546E+10 | 0.446253E+09 | 0.218820E+10 | 0.729542E+09 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1016.06 | 360.43 | 691.88 | 507.95 | 183.94 | 0.00 | 0.00 |
February | 766.59 | 325.66 | 546.53 | 338.18 | 208.36 | 0.00 | 0.00 |
March | 608.67 | 335.19 | 435.89 | 212.33 | 223.56 | 0.00 | 0.00 |
April | 543.76 | 270.89 | 364.49 | 140.88 | 223.62 | 0.00 | 0.00 |
May | 330.29 | 237.25 | 256.82 | 31.10 | 225.72 | 0.00 | 0.00 |
June | 294.99 | 177.77 | 225.30 | 13.21 | 212.09 | 0.00 | 0.00 |
July | 350.95 | 156.85 | 237.61 | 25.41 | 212.20 | 0.00 | 0.00 |
August | 499.35 | 169.75 | 305.17 | 94.83 | 210.34 | 0.00 | 0.00 |
September | 675.52 | 203.11 | 419.06 | 208.19 | 210.87 | 0.00 | 0.00 |
October | 884.37 | 225.50 | 548.73 | 368.52 | 180.22 | 0.00 | 0.00 |
November | 981.22 | 326.07 | 666.54 | 472.26 | 194.28 | 0.00 | 0.00 |
December | 1092.89 | 362.23 | 740.41 | 564.21 | 176.20 | 0.00 | 0.00 |
Annual Sum or Average | 670.11 | 262.24 | 452.81 | 247.78 | 205.03 | 0.00 | 0.00 |
Minimum of Months | 294.99 | 156.85 | 225.30 | 13.21 | 176.20 | 0.00 | 0.00 |
Maximum of Months | 1092.89 | 362.23 | 740.41 | 564.21 | 225.72 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2821.82 | 1101.73 | 1948.30 | 1430.34 | 517.96 | 0.00 | 0.00 |
February | 2118.07 | 1013.97 | 1539.00 | 952.28 | 586.71 | 0.00 | 0.00 |
March | 1675.39 | 1033.92 | 1227.43 | 597.91 | 629.52 | 0.00 | 0.00 |
April | 1494.92 | 849.01 | 1026.39 | 396.71 | 629.69 | 0.00 | 0.00 |
May | 888.77 | 751.15 | 723.18 | 87.58 | 635.60 | 0.00 | 0.00 |
June | 792.26 | 572.02 | 634.43 | 37.21 | 597.22 | 0.00 | 0.00 |
July | 959.18 | 496.83 | 669.08 | 71.55 | 597.53 | 0.00 | 0.00 |
August | 1383.61 | 531.54 | 859.34 | 267.03 | 592.31 | 0.00 | 0.00 |
September | 1876.55 | 634.94 | 1180.05 | 586.24 | 593.81 | 0.00 | 0.00 |
October | 2459.42 | 698.59 | 1545.20 | 1037.72 | 507.48 | 0.00 | 0.00 |
November | 2721.72 | 1006.88 | 1876.94 | 1329.86 | 547.08 | 0.00 | 0.00 |
December | 3036.85 | 1106.75 | 2084.94 | 1588.78 | 496.16 | 0.00 | 0.00 |
Annual Sum or Average | 1851.63 | 815.38 | 1275.09 | 697.73 | 577.36 | 0.00 | 0.00 |
Minimum of Months | 792.26 | 496.83 | 634.43 | 37.21 | 496.16 | 0.00 | 0.00 |
Maximum of Months | 3036.85 | 1106.75 | 2084.94 | 1588.78 | 635.60 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3757.36 | 1452.67 | 2530.95 | 1858.09 | 672.86 | 0.00 | 0.00 |
February | 2816.39 | 1356.61 | 1999.24 | 1237.07 | 762.17 | 0.00 | 0.00 |
March | 2227.13 | 1393.12 | 1594.50 | 776.72 | 817.79 | 0.00 | 0.00 |
April | 1990.85 | 1141.24 | 1333.34 | 515.34 | 818.00 | 0.00 | 0.00 |
May | 1164.68 | 1032.70 | 939.45 | 113.77 | 825.68 | 0.00 | 0.00 |
June | 1034.75 | 788.40 | 824.17 | 48.34 | 775.83 | 0.00 | 0.00 |
July | 1266.53 | 678.72 | 869.17 | 92.94 | 776.23 | 0.00 | 0.00 |
August | 1844.60 | 710.09 | 1116.33 | 346.89 | 769.44 | 0.00 | 0.00 |
September | 2502.63 | 841.59 | 1532.95 | 761.56 | 771.39 | 0.00 | 0.00 |
October | 3269.04 | 919.73 | 2007.30 | 1348.05 | 659.24 | 0.00 | 0.00 |
November | 3619.17 | 1330.65 | 2438.25 | 1727.56 | 710.69 | 0.00 | 0.00 |
December | 4037.76 | 1460.55 | 2708.45 | 2063.92 | 644.54 | 0.00 | 0.00 |
Annual Sum or Average | 2459.89 | 1090.73 | 1656.41 | 906.39 | 750.02 | 0.00 | 0.00 |
Minimum of Months | 1034.75 | 678.72 | 824.17 | 48.34 | 644.54 | 0.00 | 0.00 |
Maximum of Months | 4037.76 | 1460.55 | 2708.45 | 2063.92 | 825.68 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 320.45 | 214.91 | 235.93 | 150.42 | 85.51 | 0.00 | 0.00 |
February | 289.30 | 195.71 | 226.46 | 121.59 | 104.87 | 0.00 | 0.00 |
March | 283.31 | 203.32 | 221.59 | 101.82 | 119.77 | 0.00 | 0.00 |
April | 367.19 | 156.65 | 258.69 | 124.88 | 133.81 | 0.00 | 0.00 |
May | 312.37 | 139.44 | 234.10 | 90.70 | 143.41 | 0.00 | 0.00 |
June | 339.72 | 99.12 | 238.71 | 99.56 | 139.15 | 0.00 | 0.00 |
July | 389.11 | 82.37 | 252.57 | 114.92 | 137.65 | 0.00 | 0.00 |
August | 403.41 | 87.06 | 253.25 | 123.21 | 130.05 | 0.00 | 0.00 |
September | 384.96 | 106.16 | 248.19 | 129.60 | 118.59 | 0.00 | 0.00 |
October | 374.80 | 121.22 | 235.49 | 142.44 | 93.05 | 0.00 | 0.00 |
November | 339.31 | 190.31 | 246.07 | 153.19 | 92.88 | 0.00 | 0.00 |
December | 339.22 | 213.51 | 246.91 | 165.30 | 81.61 | 0.00 | 0.00 |
Annual Sum or Average | 345.59 | 150.59 | 241.55 | 126.51 | 115.04 | 0.00 | 0.00 |
Minimum of Months | 283.31 | 82.37 | 221.59 | 90.70 | 81.61 | 0.00 | 0.00 |
Maximum of Months | 403.41 | 214.91 | 258.69 | 165.30 | 143.41 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 141.80 | 222.43 | 119.81 | 49.99 | 69.82 | 0.00 | 0.00 |
February | 159.72 | 199.28 | 144.35 | 54.72 | 89.63 | 0.00 | 0.00 |
March | 190.59 | 204.88 | 167.22 | 59.84 | 107.38 | 0.00 | 0.00 |
April | 292.84 | 158.06 | 223.47 | 97.32 | 126.15 | 0.00 | 0.00 |
May | 288.77 | 140.18 | 227.65 | 86.86 | 140.79 | 0.00 | 0.00 |
June | 328.93 | 105.82 | 241.14 | 101.59 | 139.55 | 0.00 | 0.00 |
July | 366.83 | 93.10 | 250.09 | 113.68 | 136.42 | 0.00 | 0.00 |
August | 341.80 | 98.01 | 229.92 | 105.28 | 124.64 | 0.00 | 0.00 |
September | 282.18 | 112.95 | 196.56 | 88.44 | 108.12 | 0.00 | 0.00 |
October | 229.86 | 129.45 | 151.77 | 69.58 | 82.19 | 0.00 | 0.00 |
November | 166.69 | 196.03 | 136.71 | 59.82 | 76.89 | 0.00 | 0.00 |
December | 144.37 | 222.13 | 119.77 | 53.75 | 66.02 | 0.00 | 0.00 |
Annual Sum or Average | 244.97 | 156.66 | 184.20 | 78.51 | 105.69 | 0.00 | 0.00 |
Minimum of Months | 141.80 | 93.10 | 119.77 | 49.99 | 66.02 | 0.00 | 0.00 |
Maximum of Months | 366.83 | 222.43 | 250.09 | 113.68 | 140.79 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 148.30 | 87.20 | 109.42 | 80.33 | 29.09 | 0.00 | 0.00 |
February | 107.04 | 83.05 | 86.43 | 53.48 | 32.95 | 0.00 | 0.00 |
March | 81.83 | 85.13 | 68.93 | 33.58 | 35.35 | 0.00 | 0.00 |
April | 71.92 | 70.67 | 57.64 | 22.28 | 35.36 | 0.00 | 0.00 |
May | 36.17 | 64.92 | 40.61 | 4.92 | 35.70 | 0.00 | 0.00 |
June | 30.85 | 51.31 | 35.63 | 2.09 | 33.54 | 0.00 | 0.00 |
July | 41.28 | 44.78 | 37.58 | 4.02 | 33.56 | 0.00 | 0.00 |
August | 66.54 | 47.02 | 48.26 | 15.00 | 33.26 | 0.00 | 0.00 |
September | 95.28 | 54.27 | 66.27 | 32.92 | 33.35 | 0.00 | 0.00 |
October | 128.73 | 58.02 | 86.78 | 58.28 | 28.50 | 0.00 | 0.00 |
November | 142.45 | 79.65 | 105.41 | 74.68 | 30.72 | 0.00 | 0.00 |
December | 160.44 | 86.71 | 117.09 | 89.23 | 27.86 | 0.00 | 0.00 |
Annual Sum or Average | 92.53 | 67.64 | 71.61 | 39.18 | 32.42 | 0.00 | 0.00 |
Minimum of Months | 30.85 | 44.78 | 35.63 | 2.09 | 27.86 | 0.00 | 0.00 |
Maximum of Months | 160.44 | 87.20 | 117.09 | 89.23 | 35.70 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 11.83 | 64.41 | 16.54 | 0.00 | 16.54 | 0.00 | 0.00 |
February | 13.50 | 57.81 | 20.77 | 0.00 | 20.77 | 0.00 | 0.00 |
March | 19.70 | 59.44 | 25.45 | 0.00 | 25.45 | 0.00 | 0.00 |
April | 29.03 | 43.17 | 29.48 | 0.24 | 29.24 | 0.00 | 0.00 |
May | 36.33 | 37.46 | 35.46 | 1.85 | 33.61 | 0.00 | 0.00 |
June | 46.11 | 27.47 | 37.59 | 3.71 | 33.88 | 0.00 | 0.00 |
July | 49.09 | 23.54 | 35.61 | 3.02 | 32.58 | 0.00 | 0.00 |
August | 40.28 | 24.69 | 29.60 | 0.66 | 28.95 | 0.00 | 0.00 |
September | 31.42 | 30.28 | 24.99 | 0.00 | 24.98 | 0.00 | 0.00 |
October | 27.82 | 35.29 | 19.82 | 0.00 | 19.82 | 0.00 | 0.00 |
November | 14.12 | 56.02 | 17.95 | 0.00 | 17.95 | 0.00 | 0.00 |
December | 10.92 | 64.13 | 15.40 | 0.00 | 15.40 | 0.00 | 0.00 |
Annual Sum or Average | 27.60 | 43.57 | 25.74 | 0.79 | 24.95 | 0.00 | 0.00 |
Minimum of Months | 10.92 | 23.54 | 15.40 | 0.00 | 15.40 | 0.00 | 0.00 |
Maximum of Months | 49.09 | 64.41 | 37.59 | 3.71 | 33.88 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 324.93 | 210.33 | 240.83 | 156.02 | 84.82 | 0.00 | 0.00 |
February | 271.52 | 190.54 | 217.84 | 117.10 | 100.74 | 0.00 | 0.00 |
March | 275.21 | 196.19 | 220.16 | 101.82 | 118.34 | 0.00 | 0.00 |
April | 338.43 | 151.00 | 242.85 | 113.54 | 129.30 | 0.00 | 0.00 |
May | 274.79 | 135.14 | 211.64 | 73.18 | 138.45 | 0.00 | 0.00 |
June | 287.05 | 98.28 | 204.59 | 72.09 | 132.50 | 0.00 | 0.00 |
July | 352.01 | 82.39 | 228.22 | 95.06 | 133.15 | 0.00 | 0.00 |
August | 382.02 | 85.15 | 239.47 | 113.95 | 125.52 | 0.00 | 0.00 |
September | 329.75 | 104.03 | 213.64 | 101.32 | 112.32 | 0.00 | 0.00 |
October | 352.89 | 117.17 | 223.75 | 132.02 | 91.73 | 0.00 | 0.00 |
November | 320.68 | 186.17 | 236.61 | 146.44 | 90.17 | 0.00 | 0.00 |
December | 336.14 | 209.61 | 247.16 | 167.72 | 79.44 | 0.00 | 0.00 |
Annual Sum or Average | 320.87 | 146.95 | 227.34 | 115.93 | 111.41 | 0.00 | 0.00 |
Minimum of Months | 271.52 | 82.39 | 204.59 | 72.09 | 79.44 | 0.00 | 0.00 |
Maximum of Months | 382.02 | 210.33 | 247.16 | 167.72 | 138.45 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 138.85 | 209.75 | 124.71 | 55.59 | 69.12 | 0.00 | 0.00 |
February | 138.75 | 190.02 | 135.73 | 50.23 | 85.50 | 0.00 | 0.00 |
March | 180.99 | 195.37 | 165.79 | 59.84 | 105.95 | 0.00 | 0.00 |
April | 265.85 | 150.92 | 207.62 | 85.99 | 121.64 | 0.00 | 0.00 |
May | 253.91 | 135.37 | 205.18 | 69.35 | 135.83 | 0.00 | 0.00 |
June | 278.98 | 101.40 | 207.02 | 74.12 | 132.90 | 0.00 | 0.00 |
July | 331.07 | 88.96 | 225.74 | 93.82 | 131.92 | 0.00 | 0.00 |
August | 321.19 | 93.02 | 216.13 | 96.02 | 120.11 | 0.00 | 0.00 |
September | 228.56 | 108.54 | 162.01 | 60.16 | 101.85 | 0.00 | 0.00 |
October | 205.91 | 122.22 | 140.03 | 59.16 | 80.87 | 0.00 | 0.00 |
November | 143.89 | 186.17 | 127.26 | 53.07 | 74.19 | 0.00 | 0.00 |
December | 132.82 | 209.22 | 120.02 | 56.17 | 63.86 | 0.00 | 0.00 |
Annual Sum or Average | 218.93 | 149.05 | 169.98 | 67.93 | 102.05 | 0.00 | 0.00 |
Minimum of Months | 132.82 | 88.96 | 120.02 | 50.23 | 63.86 | 0.00 | 0.00 |
Maximum of Months | 331.07 | 209.75 | 225.74 | 96.02 | 135.83 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 373.52 | 253.55 | 272.92 | 174.05 | 98.87 | 0.00 | 0.00 |
February | 291.48 | 235.49 | 232.26 | 115.88 | 116.38 | 0.00 | 0.00 |
March | 254.34 | 243.94 | 204.49 | 72.76 | 131.74 | 0.00 | 0.00 |
April | 253.72 | 190.49 | 188.75 | 48.79 | 139.97 | 0.00 | 0.00 |
May | 191.57 | 167.83 | 164.82 | 14.66 | 150.16 | 0.00 | 0.00 |
June | 201.01 | 122.88 | 158.63 | 12.57 | 146.06 | 0.00 | 0.00 |
July | 227.93 | 107.21 | 158.55 | 15.25 | 143.30 | 0.00 | 0.00 |
August | 261.60 | 115.62 | 168.70 | 33.92 | 134.78 | 0.00 | 0.00 |
September | 304.33 | 139.50 | 197.73 | 71.35 | 126.38 | 0.00 | 0.00 |
October | 364.32 | 157.53 | 230.96 | 126.27 | 104.69 | 0.00 | 0.00 |
November | 365.37 | 231.77 | 267.27 | 161.82 | 105.45 | 0.00 | 0.00 |
December | 395.08 | 255.35 | 287.07 | 193.33 | 93.74 | 0.00 | 0.00 |
Annual Sum or Average | 290.45 | 184.84 | 210.92 | 86.62 | 124.30 | 0.00 | 0.00 |
Minimum of Months | 191.57 | 107.21 | 158.55 | 12.57 | 93.74 | 0.00 | 0.00 |
Maximum of Months | 395.08 | 255.35 | 287.07 | 193.33 | 150.16 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 318.12 | 212.14 | 235.93 | 150.42 | 85.51 | 0.00 | 0.00 |
February | 286.19 | 192.87 | 226.46 | 121.59 | 104.87 | 0.00 | 0.00 |
March | 279.33 | 201.51 | 221.59 | 101.82 | 119.77 | 0.00 | 0.00 |
April | 361.16 | 155.25 | 258.69 | 124.88 | 133.81 | 0.00 | 0.00 |
May | 306.53 | 138.30 | 234.10 | 90.70 | 143.41 | 0.00 | 0.00 |
June | 333.59 | 98.16 | 238.71 | 99.56 | 139.15 | 0.00 | 0.00 |
July | 383.27 | 81.34 | 252.57 | 114.92 | 137.65 | 0.00 | 0.00 |
August | 397.73 | 85.92 | 253.25 | 123.21 | 130.05 | 0.00 | 0.00 |
September | 379.86 | 104.50 | 248.19 | 129.60 | 118.59 | 0.00 | 0.00 |
October | 371.52 | 118.82 | 235.49 | 142.44 | 93.05 | 0.00 | 0.00 |
November | 336.48 | 187.32 | 246.07 | 153.19 | 92.88 | 0.00 | 0.00 |
December | 337.21 | 210.13 | 246.91 | 165.30 | 81.61 | 0.00 | 0.00 |
Annual Sum or Average | 341.24 | 148.63 | 241.55 | 126.51 | 115.04 | 0.00 | 0.00 |
Minimum of Months | 279.33 | 81.34 | 221.59 | 90.70 | 81.61 | 0.00 | 0.00 |
Maximum of Months | 397.73 | 212.14 | 258.69 | 165.30 | 143.41 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 141.39 | 218.05 | 119.81 | 49.99 | 69.82 | 0.00 | 0.00 |
February | 158.56 | 195.45 | 144.35 | 54.72 | 89.63 | 0.00 | 0.00 |
March | 187.56 | 202.83 | 167.22 | 59.84 | 107.38 | 0.00 | 0.00 |
April | 286.70 | 157.80 | 223.47 | 97.32 | 126.15 | 0.00 | 0.00 |
May | 282.16 | 140.31 | 227.65 | 86.86 | 140.79 | 0.00 | 0.00 |
June | 320.73 | 107.64 | 241.14 | 101.59 | 139.55 | 0.00 | 0.00 |
July | 358.96 | 95.50 | 250.09 | 113.68 | 136.42 | 0.00 | 0.00 |
August | 335.19 | 99.89 | 229.92 | 105.28 | 124.64 | 0.00 | 0.00 |
September | 277.52 | 112.47 | 196.56 | 88.44 | 108.12 | 0.00 | 0.00 |
October | 228.20 | 126.79 | 151.77 | 69.58 | 82.19 | 0.00 | 0.00 |
November | 166.12 | 191.60 | 136.71 | 59.82 | 76.89 | 0.00 | 0.00 |
December | 144.74 | 216.83 | 119.77 | 53.75 | 66.02 | 0.00 | 0.00 |
Annual Sum or Average | 241.08 | 155.24 | 184.20 | 78.51 | 105.69 | 0.00 | 0.00 |
Minimum of Months | 141.39 | 95.50 | 119.77 | 49.99 | 66.02 | 0.00 | 0.00 |
Maximum of Months | 358.96 | 218.05 | 250.09 | 113.68 | 140.79 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 292.00 | 110.76 | 200.63 | 147.29 | 53.34 | 0.00 | 0.00 |
February | 216.35 | 100.79 | 158.48 | 98.06 | 60.42 | 0.00 | 0.00 |
March | 170.40 | 105.92 | 126.40 | 61.57 | 64.83 | 0.00 | 0.00 |
April | 153.66 | 81.40 | 105.69 | 40.85 | 64.84 | 0.00 | 0.00 |
May | 90.69 | 72.41 | 74.47 | 9.02 | 65.45 | 0.00 | 0.00 |
June | 83.42 | 50.82 | 65.33 | 3.83 | 61.50 | 0.00 | 0.00 |
July | 103.25 | 41.19 | 68.90 | 7.37 | 61.53 | 0.00 | 0.00 |
August | 147.52 | 43.43 | 88.49 | 27.50 | 60.99 | 0.00 | 0.00 |
September | 197.19 | 54.02 | 121.52 | 60.37 | 61.15 | 0.00 | 0.00 |
October | 258.57 | 60.71 | 159.12 | 106.86 | 52.26 | 0.00 | 0.00 |
November | 281.93 | 97.55 | 193.28 | 136.94 | 56.34 | 0.00 | 0.00 |
December | 314.50 | 109.94 | 214.70 | 163.60 | 51.09 | 0.00 | 0.00 |
Annual Sum or Average | 192.41 | 77.29 | 131.30 | 71.85 | 59.45 | 0.00 | 0.00 |
Minimum of Months | 83.42 | 41.19 | 65.33 | 3.83 | 51.09 | 0.00 | 0.00 |
Maximum of Months | 314.50 | 110.76 | 214.70 | 163.60 | 65.45 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 72.84 | 642.56 | 144.74 | 0.00 | 144.74 | 0.00 | 0.00 |
February | 83.48 | 597.54 | 181.69 | 0.00 | 181.69 | 0.00 | 0.00 |
March | 131.81 | 601.08 | 222.66 | 0.00 | 222.66 | 0.00 | 0.00 |
April | 199.88 | 450.07 | 257.88 | 2.08 | 255.81 | 0.00 | 0.00 |
May | 255.52 | 388.10 | 310.23 | 16.18 | 294.05 | 0.00 | 0.00 |
June | 343.64 | 288.93 | 328.85 | 32.49 | 296.36 | 0.00 | 0.00 |
July | 372.58 | 248.32 | 311.50 | 26.43 | 285.07 | 0.00 | 0.00 |
August | 297.48 | 267.70 | 258.99 | 5.75 | 253.24 | 0.00 | 0.00 |
September | 225.31 | 330.52 | 218.62 | 0.04 | 218.58 | 0.00 | 0.00 |
October | 198.01 | 380.72 | 173.40 | 0.00 | 173.40 | 0.00 | 0.00 |
November | 87.27 | 577.36 | 157.00 | 0.00 | 157.00 | 0.00 | 0.00 |
December | 64.28 | 645.06 | 134.74 | 0.00 | 134.74 | 0.00 | 0.00 |
Annual Sum or Average | 195.03 | 450.73 | 225.21 | 6.95 | 218.26 | 0.00 | 0.00 |
Minimum of Months | 64.28 | 248.32 | 134.74 | 0.00 | 134.74 | 0.00 | 0.00 |
Maximum of Months | 372.58 | 645.06 | 328.85 | 32.49 | 296.36 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 65.29 | 664.25 | 144.74 | 0.00 | 144.74 | 0.00 | 0.00 |
February | 74.84 | 618.63 | 181.69 | 0.00 | 181.69 | 0.00 | 0.00 |
March | 121.10 | 620.93 | 222.66 | 0.00 | 222.66 | 0.00 | 0.00 |
April | 187.91 | 463.45 | 257.88 | 2.08 | 255.81 | 0.00 | 0.00 |
May | 241.52 | 399.01 | 310.23 | 16.18 | 294.05 | 0.00 | 0.00 |
June | 330.64 | 297.93 | 328.85 | 32.49 | 296.36 | 0.00 | 0.00 |
July | 361.02 | 256.20 | 311.50 | 26.43 | 285.07 | 0.00 | 0.00 |
August | 286.93 | 276.60 | 258.99 | 5.75 | 253.24 | 0.00 | 0.00 |
September | 215.53 | 341.91 | 218.62 | 0.04 | 218.58 | 0.00 | 0.00 |
October | 189.32 | 393.25 | 173.40 | 0.00 | 173.40 | 0.00 | 0.00 |
November | 79.17 | 595.77 | 157.00 | 0.00 | 157.00 | 0.00 | 0.00 |
December | 57.27 | 666.46 | 134.74 | 0.00 | 134.74 | 0.00 | 0.00 |
Annual Sum or Average | 184.90 | 465.40 | 225.21 | 6.95 | 218.26 | 0.00 | 0.00 |
Minimum of Months | 57.27 | 256.20 | 134.74 | 0.00 | 134.74 | 0.00 | 0.00 |
Maximum of Months | 361.02 | 666.46 | 328.85 | 32.49 | 296.36 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 500.01 | 431.64 | 365.53 | 211.59 | 153.93 | 0.00 | 0.00 |
February | 438.79 | 419.59 | 353.56 | 167.32 | 186.23 | 0.00 | 0.00 |
March | 491.57 | 426.04 | 385.93 | 161.65 | 224.28 | 0.00 | 0.00 |
April | 658.87 | 335.65 | 450.45 | 199.52 | 250.93 | 0.00 | 0.00 |
May | 583.86 | 308.86 | 416.79 | 142.52 | 274.27 | 0.00 | 0.00 |
June | 632.64 | 235.70 | 411.59 | 146.20 | 265.39 | 0.00 | 0.00 |
July | 762.64 | 202.75 | 453.93 | 188.87 | 265.06 | 0.00 | 0.00 |
August | 779.76 | 210.74 | 455.57 | 209.96 | 245.61 | 0.00 | 0.00 |
September | 618.52 | 239.21 | 375.63 | 161.47 | 214.16 | 0.00 | 0.00 |
October | 613.23 | 264.45 | 363.77 | 191.17 | 172.60 | 0.00 | 0.00 |
November | 500.43 | 391.66 | 363.85 | 199.51 | 164.35 | 0.00 | 0.00 |
December | 503.81 | 431.39 | 367.17 | 223.88 | 143.29 | 0.00 | 0.00 |
Annual Sum or Average | 591.46 | 324.29 | 397.30 | 183.85 | 213.45 | 0.00 | 0.00 |
Minimum of Months | 438.79 | 202.75 | 353.56 | 142.52 | 143.29 | 0.00 | 0.00 |
Maximum of Months | 779.76 | 431.64 | 455.57 | 223.88 | 274.27 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 776.00 | 451.91 | 560.32 | 374.93 | 185.39 | 0.00 | 0.00 |
February | 593.13 | 418.91 | 465.70 | 249.62 | 216.08 | 0.00 | 0.00 |
March | 496.67 | 439.59 | 398.08 | 156.73 | 241.35 | 0.00 | 0.00 |
April | 475.04 | 348.13 | 357.45 | 104.70 | 252.75 | 0.00 | 0.00 |
May | 329.74 | 307.71 | 295.92 | 28.50 | 267.41 | 0.00 | 0.00 |
June | 330.54 | 229.07 | 279.04 | 20.89 | 258.15 | 0.00 | 0.00 |
July | 384.00 | 200.32 | 282.17 | 27.82 | 254.35 | 0.00 | 0.00 |
August | 473.29 | 216.05 | 314.04 | 71.97 | 242.07 | 0.00 | 0.00 |
September | 583.67 | 255.34 | 384.27 | 153.68 | 230.58 | 0.00 | 0.00 |
October | 724.97 | 283.74 | 464.48 | 272.02 | 192.47 | 0.00 | 0.00 |
November | 755.60 | 408.73 | 545.82 | 348.59 | 197.23 | 0.00 | 0.00 |
December | 827.93 | 449.59 | 592.71 | 416.47 | 176.25 | 0.00 | 0.00 |
Annual Sum or Average | 562.58 | 333.65 | 411.44 | 185.28 | 226.16 | 0.00 | 0.00 |
Minimum of Months | 329.74 | 200.32 | 279.04 | 20.89 | 176.25 | 0.00 | 0.00 |
Maximum of Months | 827.93 | 451.91 | 592.71 | 416.47 | 267.41 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.272142E+10 | 0.965380E+09 | 0.185314E+10 | 0.136048E+10 | 0.492663E+09 | 0.00 | 0.00 |
February | 0.185454E+10 | 0.787826E+09 | 0.132217E+10 | 0.818116E+09 | 0.504052E+09 | 0.00 | 0.00 |
March | 0.163027E+10 | 0.897761E+09 | 0.116748E+10 | 0.568705E+09 | 0.598776E+09 | 0.00 | 0.00 |
April | 0.140942E+10 | 0.702136E+09 | 0.944769E+09 | 0.365158E+09 | 0.579611E+09 | 0.00 | 0.00 |
May | 0.884637E+09 | 0.635446E+09 | 0.687861E+09 | 83301651.90 | 0.604559E+09 | 0.00 | 0.00 |
June | 0.764614E+09 | 0.460786E+09 | 0.583982E+09 | 34251187.10 | 0.549731E+09 | 0.00 | 0.00 |
July | 0.939993E+09 | 0.420117E+09 | 0.636401E+09 | 68053370.08 | 0.568348E+09 | 0.00 | 0.00 |
August | 0.133747E+10 | 0.454655E+09 | 0.817369E+09 | 0.253989E+09 | 0.563379E+09 | 0.00 | 0.00 |
September | 0.175094E+10 | 0.526449E+09 | 0.108621E+10 | 0.539619E+09 | 0.546586E+09 | 0.00 | 0.00 |
October | 0.236870E+10 | 0.603975E+09 | 0.146973E+10 | 0.987033E+09 | 0.482692E+09 | 0.00 | 0.00 |
November | 0.254333E+10 | 0.845186E+09 | 0.172768E+10 | 0.122410E+10 | 0.503575E+09 | 0.00 | 0.00 |
December | 0.292720E+10 | 0.970190E+09 | 0.198311E+10 | 0.151118E+10 | 0.471925E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.211325E+11 | 0.826991E+10 | 0.142799E+11 | 0.781399E+10 | 0.646590E+10 | 0.00 | 0.00 |
Minimum of Months | 0.764614E+09 | 0.420117E+09 | 0.583982E+09 | 34251187.10 | 0.471925E+09 | 0.00 | 0.00 |
Maximum of Months | 0.292720E+10 | 0.970190E+09 | 0.198311E+10 | 0.151118E+10 | 0.604559E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.755795E+10 | 0.295088E+10 | 0.521833E+10 | 0.383102E+10 | 0.138731E+10 | 0.00 | 0.00 |
February | 0.512403E+10 | 0.245299E+10 | 0.372314E+10 | 0.230376E+10 | 0.141938E+10 | 0.00 | 0.00 |
March | 0.448738E+10 | 0.276925E+10 | 0.328755E+10 | 0.160144E+10 | 0.168611E+10 | 0.00 | 0.00 |
April | 0.387483E+10 | 0.220063E+10 | 0.266041E+10 | 0.102826E+10 | 0.163215E+10 | 0.00 | 0.00 |
May | 0.238048E+10 | 0.201187E+10 | 0.193697E+10 | 0.234572E+09 | 0.170240E+10 | 0.00 | 0.00 |
June | 0.205353E+10 | 0.148268E+10 | 0.164445E+10 | 96449084.55 | 0.154801E+10 | 0.00 | 0.00 |
July | 0.256907E+10 | 0.133070E+10 | 0.179206E+10 | 0.191634E+09 | 0.160043E+10 | 0.00 | 0.00 |
August | 0.370587E+10 | 0.142369E+10 | 0.230166E+10 | 0.715217E+09 | 0.158644E+10 | 0.00 | 0.00 |
September | 0.486402E+10 | 0.164575E+10 | 0.305868E+10 | 0.151953E+10 | 0.153915E+10 | 0.00 | 0.00 |
October | 0.658732E+10 | 0.187109E+10 | 0.413865E+10 | 0.277942E+10 | 0.135923E+10 | 0.00 | 0.00 |
November | 0.705471E+10 | 0.260984E+10 | 0.486503E+10 | 0.344700E+10 | 0.141803E+10 | 0.00 | 0.00 |
December | 0.813390E+10 | 0.296432E+10 | 0.558430E+10 | 0.425539E+10 | 0.132891E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.583931E+11 | 0.257137E+11 | 0.402112E+11 | 0.220037E+11 | 0.182075E+11 | 0.00 | 0.00 |
Minimum of Months | 0.205353E+10 | 0.133070E+10 | 0.164445E+10 | 96449084.55 | 0.132891E+10 | 0.00 | 0.00 |
Maximum of Months | 0.813390E+10 | 0.296432E+10 | 0.558430E+10 | 0.425539E+10 | 0.170240E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.100637E+11 | 0.389083E+10 | 0.677891E+10 | 0.497672E+10 | 0.180219E+10 | 0.00 | 0.00 |
February | 0.681340E+10 | 0.328191E+10 | 0.483657E+10 | 0.299272E+10 | 0.184385E+10 | 0.00 | 0.00 |
March | 0.596514E+10 | 0.373133E+10 | 0.427071E+10 | 0.208036E+10 | 0.219036E+10 | 0.00 | 0.00 |
April | 0.516028E+10 | 0.295811E+10 | 0.345602E+10 | 0.133577E+10 | 0.212025E+10 | 0.00 | 0.00 |
May | 0.311948E+10 | 0.276599E+10 | 0.251623E+10 | 0.304722E+09 | 0.221151E+10 | 0.00 | 0.00 |
June | 0.268208E+10 | 0.204353E+10 | 0.213624E+10 | 0.125293E+09 | 0.201095E+10 | 0.00 | 0.00 |
July | 0.339229E+10 | 0.181788E+10 | 0.232799E+10 | 0.248943E+09 | 0.207905E+10 | 0.00 | 0.00 |
August | 0.494059E+10 | 0.190190E+10 | 0.298998E+10 | 0.929108E+09 | 0.206087E+10 | 0.00 | 0.00 |
September | 0.648682E+10 | 0.218141E+10 | 0.397340E+10 | 0.197396E+10 | 0.199944E+10 | 0.00 | 0.00 |
October | 0.875579E+10 | 0.246341E+10 | 0.537634E+10 | 0.361063E+10 | 0.176572E+10 | 0.00 | 0.00 |
November | 0.938089E+10 | 0.344904E+10 | 0.631995E+10 | 0.447785E+10 | 0.184211E+10 | 0.00 | 0.00 |
December | 0.108147E+11 | 0.391195E+10 | 0.725432E+10 | 0.552799E+10 | 0.172633E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.775752E+11 | 0.343973E+11 | 0.522367E+11 | 0.285840E+11 | 0.236526E+11 | 0.00 | 0.00 |
Minimum of Months | 0.268208E+10 | 0.181788E+10 | 0.213624E+10 | 0.125293E+09 | 0.172633E+10 | 0.00 | 0.00 |
Maximum of Months | 0.108147E+11 | 0.391195E+10 | 0.725432E+10 | 0.552799E+10 | 0.221151E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.858281E+09 | 0.575610E+09 | 0.631920E+09 | 0.402891E+09 | 0.229029E+09 | 0.00 | 0.00 |
February | 0.699879E+09 | 0.473463E+09 | 0.547842E+09 | 0.294142E+09 | 0.253700E+09 | 0.00 | 0.00 |
March | 0.758817E+09 | 0.544583E+09 | 0.593520E+09 | 0.272721E+09 | 0.320799E+09 | 0.00 | 0.00 |
April | 0.951757E+09 | 0.406032E+09 | 0.670528E+09 | 0.323680E+09 | 0.346848E+09 | 0.00 | 0.00 |
May | 0.836653E+09 | 0.373488E+09 | 0.627025E+09 | 0.242928E+09 | 0.384097E+09 | 0.00 | 0.00 |
June | 0.880557E+09 | 0.256925E+09 | 0.618729E+09 | 0.258064E+09 | 0.360665E+09 | 0.00 | 0.00 |
July | 0.104219E+10 | 0.220611E+09 | 0.676483E+09 | 0.307809E+09 | 0.368674E+09 | 0.00 | 0.00 |
August | 0.108049E+10 | 0.233187E+09 | 0.678314E+09 | 0.330001E+09 | 0.348314E+09 | 0.00 | 0.00 |
September | 0.997827E+09 | 0.275163E+09 | 0.643298E+09 | 0.335913E+09 | 0.307385E+09 | 0.00 | 0.00 |
October | 0.100388E+10 | 0.324689E+09 | 0.630737E+09 | 0.381522E+09 | 0.249215E+09 | 0.00 | 0.00 |
November | 0.879502E+09 | 0.493274E+09 | 0.637811E+09 | 0.397077E+09 | 0.240734E+09 | 0.00 | 0.00 |
December | 0.908563E+09 | 0.571861E+09 | 0.661336E+09 | 0.442746E+09 | 0.218589E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.108984E+11 | 0.474889E+10 | 0.761754E+10 | 0.398949E+10 | 0.362805E+10 | 0.00 | 0.00 |
Minimum of Months | 0.699879E+09 | 0.220611E+09 | 0.547842E+09 | 0.242928E+09 | 0.218589E+09 | 0.00 | 0.00 |
Maximum of Months | 0.108049E+10 | 0.575610E+09 | 0.678314E+09 | 0.442746E+09 | 0.384097E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.379792E+09 | 0.595749E+09 | 0.320905E+09 | 0.133901E+09 | 0.187004E+09 | 0.00 | 0.00 |
February | 0.386384E+09 | 0.482095E+09 | 0.349219E+09 | 0.132386E+09 | 0.216833E+09 | 0.00 | 0.00 |
March | 0.510470E+09 | 0.548742E+09 | 0.447889E+09 | 0.160279E+09 | 0.287610E+09 | 0.00 | 0.00 |
April | 0.759054E+09 | 0.409694E+09 | 0.579223E+09 | 0.252251E+09 | 0.326972E+09 | 0.00 | 0.00 |
May | 0.773433E+09 | 0.375471E+09 | 0.609729E+09 | 0.232648E+09 | 0.377081E+09 | 0.00 | 0.00 |
June | 0.852577E+09 | 0.274288E+09 | 0.625037E+09 | 0.263322E+09 | 0.361715E+09 | 0.00 | 0.00 |
July | 0.982516E+09 | 0.249354E+09 | 0.669847E+09 | 0.304467E+09 | 0.365379E+09 | 0.00 | 0.00 |
August | 0.915466E+09 | 0.262513E+09 | 0.615807E+09 | 0.281984E+09 | 0.333823E+09 | 0.00 | 0.00 |
September | 0.731415E+09 | 0.292757E+09 | 0.509491E+09 | 0.229238E+09 | 0.280253E+09 | 0.00 | 0.00 |
October | 0.615657E+09 | 0.346723E+09 | 0.406496E+09 | 0.186368E+09 | 0.220128E+09 | 0.00 | 0.00 |
November | 0.432052E+09 | 0.508106E+09 | 0.354356E+09 | 0.155051E+09 | 0.199305E+09 | 0.00 | 0.00 |
December | 0.386677E+09 | 0.594940E+09 | 0.320798E+09 | 0.143959E+09 | 0.176839E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.772549E+10 | 0.494043E+10 | 0.580880E+10 | 0.247585E+10 | 0.333294E+10 | 0.00 | 0.00 |
Minimum of Months | 0.379792E+09 | 0.249354E+09 | 0.320798E+09 | 0.132386E+09 | 0.176839E+09 | 0.00 | 0.00 |
Maximum of Months | 0.982516E+09 | 0.595749E+09 | 0.669847E+09 | 0.304467E+09 | 0.377081E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.397197E+09 | 0.233546E+09 | 0.293061E+09 | 0.215149E+09 | 77911467.45 | 0.00 | 0.00 |
February | 0.258946E+09 | 0.200917E+09 | 0.209091E+09 | 0.129379E+09 | 79712592.74 | 0.00 | 0.00 |
March | 0.219183E+09 | 0.228011E+09 | 0.184629E+09 | 89936327.87 | 94692605.60 | 0.00 | 0.00 |
April | 0.186412E+09 | 0.183170E+09 | 0.149409E+09 | 57746850.06 | 91662135.38 | 0.00 | 0.00 |
May | 96865478.16 | 0.173892E+09 | 0.108781E+09 | 13173513.96 | 95607483.13 | 0.00 | 0.00 |
June | 79972363.84 | 0.133001E+09 | 92353413.13 | 5416561.15 | 86936851.98 | 0.00 | 0.00 |
July | 0.110551E+09 | 0.119937E+09 | 0.100643E+09 | 10762115.76 | 89881160.52 | 0.00 | 0.00 |
August | 0.178222E+09 | 0.125935E+09 | 0.129262E+09 | 40166453.60 | 89095338.36 | 0.00 | 0.00 |
September | 0.246958E+09 | 0.140662E+09 | 0.171776E+09 | 85336561.19 | 86439337.30 | 0.00 | 0.00 |
October | 0.344782E+09 | 0.155414E+09 | 0.232427E+09 | 0.156092E+09 | 76334792.12 | 0.00 | 0.00 |
November | 0.369242E+09 | 0.206458E+09 | 0.273220E+09 | 0.193583E+09 | 79637126.46 | 0.00 | 0.00 |
December | 0.429724E+09 | 0.232254E+09 | 0.313614E+09 | 0.238982E+09 | 74631825.39 | 0.00 | 0.00 |
Annual Sum or Average | 0.291805E+10 | 0.213320E+10 | 0.225827E+10 | 0.123572E+10 | 0.102254E+10 | 0.00 | 0.00 |
Minimum of Months | 79972363.84 | 0.119937E+09 | 92353413.13 | 5416561.15 | 74631825.39 | 0.00 | 0.00 |
Maximum of Months | 0.429724E+09 | 0.233546E+09 | 0.313614E+09 | 0.238982E+09 | 95607483.13 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 31686574.94 | 0.172506E+09 | 44312955.30 | 0.00 | 44312955.30 | 0.00 | 0.00 |
February | 32658707.69 | 0.139861E+09 | 50241522.13 | 0.00 | 50241522.13 | 0.00 | 0.00 |
March | 52753290.28 | 0.159213E+09 | 68169765.21 | 624.22 | 68169140.99 | 0.00 | 0.00 |
April | 75246460.74 | 0.111898E+09 | 76404816.42 | 614812.68 | 75790003.74 | 0.00 | 0.00 |
May | 97299494.08 | 0.100323E+09 | 94978755.02 | 4953021.70 | 90025733.32 | 0.00 | 0.00 |
June | 0.119513E+09 | 71204884.02 | 97431324.50 | 9625266.49 | 87806058.00 | 0.00 | 0.00 |
July | 0.131486E+09 | 63044846.23 | 95367114.15 | 8092321.46 | 87274792.68 | 0.00 | 0.00 |
August | 0.107885E+09 | 66141105.79 | 79292341.88 | 1761686.91 | 77530654.97 | 0.00 | 0.00 |
September | 81447027.67 | 78490635.24 | 64772993.27 | 12882.05 | 64760111.22 | 0.00 | 0.00 |
October | 74525464.13 | 94533971.54 | 53086943.81 | 0.00 | 53086943.81 | 0.00 | 0.00 |
November | 36598498.63 | 0.145208E+09 | 46515858.69 | 0.00 | 46515858.69 | 0.00 | 0.00 |
December | 29253268.86 | 0.171756E+09 | 41251595.16 | 0.00 | 41251595.16 | 0.00 | 0.00 |
Annual Sum or Average | 0.870354E+09 | 0.137418E+10 | 0.811826E+09 | 25060615.52 | 0.786765E+09 | 0.00 | 0.00 |
Minimum of Months | 29253268.86 | 63044846.23 | 41251595.16 | 0.00 | 41251595.16 | 0.00 | 0.00 |
Maximum of Months | 0.131486E+09 | 0.172506E+09 | 97431324.50 | 9625266.49 | 90025733.32 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.870285E+09 | 0.563350E+09 | 0.645041E+09 | 0.417872E+09 | 0.227169E+09 | 0.00 | 0.00 |
February | 0.656863E+09 | 0.460945E+09 | 0.526993E+09 | 0.283282E+09 | 0.243711E+09 | 0.00 | 0.00 |
March | 0.737132E+09 | 0.525483E+09 | 0.589680E+09 | 0.272720E+09 | 0.316960E+09 | 0.00 | 0.00 |
April | 0.877209E+09 | 0.391393E+09 | 0.629463E+09 | 0.294307E+09 | 0.335155E+09 | 0.00 | 0.00 |
May | 0.735995E+09 | 0.361947E+09 | 0.566849E+09 | 0.196017E+09 | 0.370832E+09 | 0.00 | 0.00 |
June | 0.744046E+09 | 0.254748E+09 | 0.530300E+09 | 0.186863E+09 | 0.343438E+09 | 0.00 | 0.00 |
July | 0.942822E+09 | 0.220685E+09 | 0.611254E+09 | 0.254616E+09 | 0.356638E+09 | 0.00 | 0.00 |
August | 0.102319E+10 | 0.228068E+09 | 0.641384E+09 | 0.305202E+09 | 0.336182E+09 | 0.00 | 0.00 |
September | 0.854723E+09 | 0.269653E+09 | 0.553748E+09 | 0.262611E+09 | 0.291136E+09 | 0.00 | 0.00 |
October | 0.945177E+09 | 0.313826E+09 | 0.599302E+09 | 0.353603E+09 | 0.245699E+09 | 0.00 | 0.00 |
November | 0.831193E+09 | 0.482546E+09 | 0.613301E+09 | 0.379582E+09 | 0.233719E+09 | 0.00 | 0.00 |
December | 0.900312E+09 | 0.561423E+09 | 0.662004E+09 | 0.449220E+09 | 0.212784E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.101189E+11 | 0.463407E+10 | 0.716932E+10 | 0.365590E+10 | 0.351342E+10 | 0.00 | 0.00 |
Minimum of Months | 0.656863E+09 | 0.220685E+09 | 0.526993E+09 | 0.186863E+09 | 0.212784E+09 | 0.00 | 0.00 |
Maximum of Months | 0.102319E+10 | 0.563350E+09 | 0.662004E+09 | 0.449220E+09 | 0.370832E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.371898E+09 | 0.561786E+09 | 0.334026E+09 | 0.148882E+09 | 0.185144E+09 | 0.00 | 0.00 |
February | 0.335668E+09 | 0.459698E+09 | 0.328370E+09 | 0.121526E+09 | 0.206844E+09 | 0.00 | 0.00 |
March | 0.484771E+09 | 0.523274E+09 | 0.444049E+09 | 0.160278E+09 | 0.283771E+09 | 0.00 | 0.00 |
April | 0.689077E+09 | 0.391179E+09 | 0.538158E+09 | 0.222878E+09 | 0.315280E+09 | 0.00 | 0.00 |
May | 0.680082E+09 | 0.362585E+09 | 0.549554E+09 | 0.185737E+09 | 0.363816E+09 | 0.00 | 0.00 |
June | 0.723107E+09 | 0.262826E+09 | 0.536608E+09 | 0.192121E+09 | 0.344488E+09 | 0.00 | 0.00 |
July | 0.886741E+09 | 0.238273E+09 | 0.604618E+09 | 0.251275E+09 | 0.353343E+09 | 0.00 | 0.00 |
August | 0.860279E+09 | 0.249155E+09 | 0.578877E+09 | 0.257186E+09 | 0.321691E+09 | 0.00 | 0.00 |
September | 0.592426E+09 | 0.281324E+09 | 0.419941E+09 | 0.155935E+09 | 0.264005E+09 | 0.00 | 0.00 |
October | 0.551510E+09 | 0.327350E+09 | 0.375061E+09 | 0.158449E+09 | 0.216611E+09 | 0.00 | 0.00 |
November | 0.372959E+09 | 0.482560E+09 | 0.329845E+09 | 0.137555E+09 | 0.192290E+09 | 0.00 | 0.00 |
December | 0.355753E+09 | 0.560367E+09 | 0.321466E+09 | 0.150433E+09 | 0.171033E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.690427E+10 | 0.470038E+10 | 0.536057E+10 | 0.214226E+10 | 0.321832E+10 | 0.00 | 0.00 |
Minimum of Months | 0.335668E+09 | 0.238273E+09 | 0.321466E+09 | 0.121526E+09 | 0.171033E+09 | 0.00 | 0.00 |
Maximum of Months | 0.886741E+09 | 0.561786E+09 | 0.604618E+09 | 0.257186E+09 | 0.363816E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.100044E+10 | 0.679106E+09 | 0.730978E+09 | 0.466169E+09 | 0.264809E+09 | 0.00 | 0.00 |
February | 0.705149E+09 | 0.569702E+09 | 0.561883E+09 | 0.280328E+09 | 0.281555E+09 | 0.00 | 0.00 |
March | 0.681237E+09 | 0.653370E+09 | 0.547718E+09 | 0.194868E+09 | 0.352850E+09 | 0.00 | 0.00 |
April | 0.657641E+09 | 0.493760E+09 | 0.489246E+09 | 0.126453E+09 | 0.362793E+09 | 0.00 | 0.00 |
May | 0.513094E+09 | 0.449508E+09 | 0.441454E+09 | 39273247.18 | 0.402181E+09 | 0.00 | 0.00 |
June | 0.521009E+09 | 0.318515E+09 | 0.411173E+09 | 32587736.49 | 0.378585E+09 | 0.00 | 0.00 |
July | 0.610500E+09 | 0.287163E+09 | 0.424663E+09 | 40849193.83 | 0.383814E+09 | 0.00 | 0.00 |
August | 0.700680E+09 | 0.309668E+09 | 0.451848E+09 | 90845939.63 | 0.361002E+09 | 0.00 | 0.00 |
September | 0.788828E+09 | 0.361572E+09 | 0.512511E+09 | 0.184929E+09 | 0.327582E+09 | 0.00 | 0.00 |
October | 0.975807E+09 | 0.421938E+09 | 0.618608E+09 | 0.338207E+09 | 0.280400E+09 | 0.00 | 0.00 |
November | 0.947029E+09 | 0.600737E+09 | 0.692760E+09 | 0.419440E+09 | 0.273320E+09 | 0.00 | 0.00 |
December | 0.105817E+10 | 0.683922E+09 | 0.768878E+09 | 0.517807E+09 | 0.251071E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.915958E+10 | 0.582896E+10 | 0.665172E+10 | 0.273176E+10 | 0.391996E+10 | 0.00 | 0.00 |
Minimum of Months | 0.513094E+09 | 0.287163E+09 | 0.411173E+09 | 32587736.49 | 0.251071E+09 | 0.00 | 0.00 |
Maximum of Months | 0.105817E+10 | 0.683922E+09 | 0.768878E+09 | 0.517807E+09 | 0.402181E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.852055E+09 | 0.568202E+09 | 0.631920E+09 | 0.402891E+09 | 0.229029E+09 | 0.00 | 0.00 |
February | 0.692352E+09 | 0.466599E+09 | 0.547842E+09 | 0.294142E+09 | 0.253700E+09 | 0.00 | 0.00 |
March | 0.748145E+09 | 0.539727E+09 | 0.593520E+09 | 0.272721E+09 | 0.320799E+09 | 0.00 | 0.00 |
April | 0.936138E+09 | 0.402415E+09 | 0.670528E+09 | 0.323680E+09 | 0.346848E+09 | 0.00 | 0.00 |
May | 0.821014E+09 | 0.370427E+09 | 0.627025E+09 | 0.242928E+09 | 0.384097E+09 | 0.00 | 0.00 |
June | 0.864668E+09 | 0.254419E+09 | 0.618729E+09 | 0.258064E+09 | 0.360665E+09 | 0.00 | 0.00 |
July | 0.102656E+10 | 0.217854E+09 | 0.676483E+09 | 0.307809E+09 | 0.368674E+09 | 0.00 | 0.00 |
August | 0.106529E+10 | 0.230128E+09 | 0.678314E+09 | 0.330001E+09 | 0.348314E+09 | 0.00 | 0.00 |
September | 0.984610E+09 | 0.270856E+09 | 0.643298E+09 | 0.335913E+09 | 0.307385E+09 | 0.00 | 0.00 |
October | 0.995092E+09 | 0.318247E+09 | 0.630737E+09 | 0.381522E+09 | 0.249215E+09 | 0.00 | 0.00 |
November | 0.872167E+09 | 0.485523E+09 | 0.637811E+09 | 0.397077E+09 | 0.240734E+09 | 0.00 | 0.00 |
December | 0.903177E+09 | 0.562823E+09 | 0.661336E+09 | 0.442746E+09 | 0.218589E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.107613E+11 | 0.468722E+10 | 0.761754E+10 | 0.398949E+10 | 0.362805E+10 | 0.00 | 0.00 |
Minimum of Months | 0.692352E+09 | 0.217854E+09 | 0.547842E+09 | 0.242928E+09 | 0.218589E+09 | 0.00 | 0.00 |
Maximum of Months | 0.106529E+10 | 0.568202E+09 | 0.678314E+09 | 0.442746E+09 | 0.384097E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.378704E+09 | 0.584038E+09 | 0.320905E+09 | 0.133901E+09 | 0.187004E+09 | 0.00 | 0.00 |
February | 0.383583E+09 | 0.472834E+09 | 0.349219E+09 | 0.132386E+09 | 0.216833E+09 | 0.00 | 0.00 |
March | 0.502366E+09 | 0.543255E+09 | 0.447889E+09 | 0.160279E+09 | 0.287610E+09 | 0.00 | 0.00 |
April | 0.743119E+09 | 0.409020E+09 | 0.579223E+09 | 0.252251E+09 | 0.326972E+09 | 0.00 | 0.00 |
May | 0.755746E+09 | 0.375820E+09 | 0.609729E+09 | 0.232648E+09 | 0.377081E+09 | 0.00 | 0.00 |
June | 0.831323E+09 | 0.278994E+09 | 0.625037E+09 | 0.263322E+09 | 0.361715E+09 | 0.00 | 0.00 |
July | 0.961436E+09 | 0.255775E+09 | 0.669847E+09 | 0.304467E+09 | 0.365379E+09 | 0.00 | 0.00 |
August | 0.897761E+09 | 0.267540E+09 | 0.615807E+09 | 0.281984E+09 | 0.333823E+09 | 0.00 | 0.00 |
September | 0.719327E+09 | 0.291524E+09 | 0.509491E+09 | 0.229238E+09 | 0.280253E+09 | 0.00 | 0.00 |
October | 0.611202E+09 | 0.339596E+09 | 0.406496E+09 | 0.186368E+09 | 0.220128E+09 | 0.00 | 0.00 |
November | 0.430574E+09 | 0.496632E+09 | 0.354356E+09 | 0.155051E+09 | 0.199305E+09 | 0.00 | 0.00 |
December | 0.387684E+09 | 0.580753E+09 | 0.320798E+09 | 0.143959E+09 | 0.176839E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.760283E+10 | 0.489578E+10 | 0.580880E+10 | 0.247585E+10 | 0.333294E+10 | 0.00 | 0.00 |
Minimum of Months | 0.378704E+09 | 0.255775E+09 | 0.320798E+09 | 0.132386E+09 | 0.176839E+09 | 0.00 | 0.00 |
Maximum of Months | 0.961436E+09 | 0.584038E+09 | 0.669847E+09 | 0.304467E+09 | 0.377081E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.782103E+09 | 0.296664E+09 | 0.537359E+09 | 0.394500E+09 | 0.142859E+09 | 0.00 | 0.00 |
February | 0.523393E+09 | 0.243836E+09 | 0.383392E+09 | 0.237230E+09 | 0.146162E+09 | 0.00 | 0.00 |
March | 0.456411E+09 | 0.283687E+09 | 0.338537E+09 | 0.164908E+09 | 0.173629E+09 | 0.00 | 0.00 |
April | 0.398288E+09 | 0.211001E+09 | 0.273958E+09 | 0.105885E+09 | 0.168073E+09 | 0.00 | 0.00 |
May | 0.242915E+09 | 0.193931E+09 | 0.199462E+09 | 24155080.95 | 0.175307E+09 | 0.00 | 0.00 |
June | 0.216223E+09 | 0.131714E+09 | 0.169340E+09 | 9931858.23 | 0.159408E+09 | 0.00 | 0.00 |
July | 0.276549E+09 | 0.110322E+09 | 0.184540E+09 | 19733518.19 | 0.164807E+09 | 0.00 | 0.00 |
August | 0.395121E+09 | 0.116320E+09 | 0.237016E+09 | 73649592.75 | 0.163366E+09 | 0.00 | 0.00 |
September | 0.511124E+09 | 0.140031E+09 | 0.314970E+09 | 0.156474E+09 | 0.158496E+09 | 0.00 | 0.00 |
October | 0.692546E+09 | 0.162618E+09 | 0.426179E+09 | 0.286211E+09 | 0.139968E+09 | 0.00 | 0.00 |
November | 0.730762E+09 | 0.252845E+09 | 0.500979E+09 | 0.354955E+09 | 0.146023E+09 | 0.00 | 0.00 |
December | 0.842359E+09 | 0.294459E+09 | 0.575045E+09 | 0.438199E+09 | 0.136846E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.606779E+10 | 0.243743E+10 | 0.414078E+10 | 0.226583E+10 | 0.187494E+10 | 0.00 | 0.00 |
Minimum of Months | 0.216223E+09 | 0.110322E+09 | 0.169340E+09 | 9931858.23 | 0.136846E+09 | 0.00 | 0.00 |
Maximum of Months | 0.842359E+09 | 0.296664E+09 | 0.575045E+09 | 0.438199E+09 | 0.175307E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.195093E+09 | 0.172104E+10 | 0.387672E+09 | 0.00 | 0.387672E+09 | 0.00 | 0.00 |
February | 0.201945E+09 | 0.144557E+10 | 0.439538E+09 | 0.00 | 0.439538E+09 | 0.00 | 0.00 |
March | 0.353029E+09 | 0.160994E+10 | 0.596384E+09 | 5460.98 | 0.596378E+09 | 0.00 | 0.00 |
April | 0.518092E+09 | 0.116659E+10 | 0.668428E+09 | 5378694.26 | 0.663050E+09 | 0.00 | 0.00 |
May | 0.684379E+09 | 0.103947E+10 | 0.830922E+09 | 43331554.67 | 0.787591E+09 | 0.00 | 0.00 |
June | 0.890702E+09 | 0.748895E+09 | 0.852379E+09 | 84206730.00 | 0.768172E+09 | 0.00 | 0.00 |
July | 0.997916E+09 | 0.665106E+09 | 0.834320E+09 | 70795746.72 | 0.763524E+09 | 0.00 | 0.00 |
August | 0.796773E+09 | 0.717001E+09 | 0.693690E+09 | 15412133.73 | 0.678278E+09 | 0.00 | 0.00 |
September | 0.583992E+09 | 0.856711E+09 | 0.566667E+09 | 112698.72 | 0.566554E+09 | 0.00 | 0.00 |
October | 0.530344E+09 | 0.101972E+10 | 0.464432E+09 | 0.00 | 0.464432E+09 | 0.00 | 0.00 |
November | 0.226195E+09 | 0.149651E+10 | 0.406944E+09 | 0.00 | 0.406944E+09 | 0.00 | 0.00 |
December | 0.172162E+09 | 0.172772E+10 | 0.360890E+09 | 0.00 | 0.360890E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.615062E+10 | 0.142143E+11 | 0.710227E+10 | 0.219243E+09 | 0.688302E+10 | 0.00 | 0.00 |
Minimum of Months | 0.172162E+09 | 0.665106E+09 | 0.360890E+09 | 0.00 | 0.360890E+09 | 0.00 | 0.00 |
Maximum of Months | 0.997916E+09 | 0.172772E+10 | 0.852379E+09 | 84206730.00 | 0.787591E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.174883E+09 | 0.177913E+10 | 0.387672E+09 | 0.00 | 0.387672E+09 | 0.00 | 0.00 |
February | 0.181055E+09 | 0.149660E+10 | 0.439538E+09 | 0.00 | 0.439538E+09 | 0.00 | 0.00 |
March | 0.324352E+09 | 0.166310E+10 | 0.596384E+09 | 5460.98 | 0.596378E+09 | 0.00 | 0.00 |
April | 0.487066E+09 | 0.120127E+10 | 0.668428E+09 | 5378694.26 | 0.663050E+09 | 0.00 | 0.00 |
May | 0.646885E+09 | 0.106872E+10 | 0.830922E+09 | 43331554.67 | 0.787591E+09 | 0.00 | 0.00 |
June | 0.857032E+09 | 0.772225E+09 | 0.852379E+09 | 84206730.00 | 0.768172E+09 | 0.00 | 0.00 |
July | 0.966948E+09 | 0.686198E+09 | 0.834320E+09 | 70795746.72 | 0.763524E+09 | 0.00 | 0.00 |
August | 0.768502E+09 | 0.740858E+09 | 0.693690E+09 | 15412133.73 | 0.678278E+09 | 0.00 | 0.00 |
September | 0.558646E+09 | 0.886221E+09 | 0.566667E+09 | 112698.72 | 0.566554E+09 | 0.00 | 0.00 |
October | 0.507066E+09 | 0.105329E+10 | 0.464432E+09 | 0.00 | 0.464432E+09 | 0.00 | 0.00 |
November | 0.205209E+09 | 0.154424E+10 | 0.406944E+09 | 0.00 | 0.406944E+09 | 0.00 | 0.00 |
December | 0.153389E+09 | 0.178504E+10 | 0.360890E+09 | 0.00 | 0.360890E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.583103E+10 | 0.146769E+11 | 0.710227E+10 | 0.219243E+09 | 0.688302E+10 | 0.00 | 0.00 |
Minimum of Months | 0.153389E+09 | 0.686198E+09 | 0.360890E+09 | 0.00 | 0.360890E+09 | 0.00 | 0.00 |
Maximum of Months | 0.966948E+09 | 0.178504E+10 | 0.852379E+09 | 84206730.00 | 0.787591E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.133923E+10 | 0.115609E+10 | 0.979027E+09 | 0.566733E+09 | 0.412294E+09 | 0.00 | 0.00 |
February | 0.106152E+10 | 0.101507E+10 | 0.855325E+09 | 0.404791E+09 | 0.450534E+09 | 0.00 | 0.00 |
March | 0.131662E+10 | 0.114109E+10 | 0.103368E+10 | 0.432976E+09 | 0.600702E+09 | 0.00 | 0.00 |
April | 0.170779E+10 | 0.869998E+09 | 0.116756E+10 | 0.517154E+09 | 0.650404E+09 | 0.00 | 0.00 |
May | 0.156380E+10 | 0.827261E+09 | 0.111634E+10 | 0.381729E+09 | 0.734613E+09 | 0.00 | 0.00 |
June | 0.163980E+10 | 0.610923E+09 | 0.106685E+10 | 0.378958E+09 | 0.687892E+09 | 0.00 | 0.00 |
July | 0.204266E+10 | 0.543043E+09 | 0.121580E+10 | 0.505857E+09 | 0.709947E+09 | 0.00 | 0.00 |
August | 0.208851E+10 | 0.564447E+09 | 0.122019E+10 | 0.562352E+09 | 0.657842E+09 | 0.00 | 0.00 |
September | 0.160322E+10 | 0.620024E+09 | 0.973640E+09 | 0.418524E+09 | 0.555116E+09 | 0.00 | 0.00 |
October | 0.164247E+10 | 0.708309E+09 | 0.974319E+09 | 0.512030E+09 | 0.462289E+09 | 0.00 | 0.00 |
November | 0.129711E+10 | 0.101518E+10 | 0.943108E+09 | 0.517117E+09 | 0.425991E+09 | 0.00 | 0.00 |
December | 0.134941E+10 | 0.115543E+10 | 0.983432E+09 | 0.599632E+09 | 0.383800E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.186521E+11 | 0.102269E+11 | 0.125293E+11 | 0.579785E+10 | 0.673142E+10 | 0.00 | 0.00 |
Minimum of Months | 0.106152E+10 | 0.543043E+09 | 0.855325E+09 | 0.378958E+09 | 0.383800E+09 | 0.00 | 0.00 |
Maximum of Months | 0.208851E+10 | 0.115609E+10 | 0.122019E+10 | 0.599632E+09 | 0.734613E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.207844E+10 | 0.121040E+10 | 0.150077E+10 | 0.100422E+10 | 0.496551E+09 | 0.00 | 0.00 |
February | 0.143489E+10 | 0.101343E+10 | 0.112662E+10 | 0.603882E+09 | 0.522737E+09 | 0.00 | 0.00 |
March | 0.133027E+10 | 0.117741E+10 | 0.106621E+10 | 0.419784E+09 | 0.646422E+09 | 0.00 | 0.00 |
April | 0.123130E+10 | 0.902347E+09 | 0.926512E+09 | 0.271380E+09 | 0.655132E+09 | 0.00 | 0.00 |
May | 0.883177E+09 | 0.824168E+09 | 0.792583E+09 | 76342183.92 | 0.716240E+09 | 0.00 | 0.00 |
June | 0.856764E+09 | 0.593750E+09 | 0.723261E+09 | 54148304.57 | 0.669113E+09 | 0.00 | 0.00 |
July | 0.102850E+10 | 0.536524E+09 | 0.755764E+09 | 74501639.64 | 0.681262E+09 | 0.00 | 0.00 |
August | 0.126766E+10 | 0.578681E+09 | 0.841134E+09 | 0.192762E+09 | 0.648372E+09 | 0.00 | 0.00 |
September | 0.151287E+10 | 0.661840E+09 | 0.996027E+09 | 0.398351E+09 | 0.597676E+09 | 0.00 | 0.00 |
October | 0.194177E+10 | 0.759974E+09 | 0.124407E+10 | 0.728566E+09 | 0.515505E+09 | 0.00 | 0.00 |
November | 0.195851E+10 | 0.105943E+10 | 0.141477E+10 | 0.903557E+09 | 0.511212E+09 | 0.00 | 0.00 |
December | 0.221752E+10 | 0.120418E+10 | 0.158752E+10 | 0.111546E+10 | 0.472062E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.177417E+11 | 0.105221E+11 | 0.129752E+11 | 0.584296E+10 | 0.713228E+10 | 0.00 | 0.00 |
Minimum of Months | 0.856764E+09 | 0.536524E+09 | 0.723261E+09 | 54148304.57 | 0.472062E+09 | 0.00 | 0.00 |
Maximum of Months | 0.221752E+10 | 0.121040E+10 | 0.158752E+10 | 0.111546E+10 | 0.716240E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.22 | 9.61 | 5.99 | 2.23 | 0.81 | 45.19 | 208.20 | 0.00 |
February | 13.28 | 10.20 | 7.03 | 3.12 | 2.96 | 66.07 | 175.60 | 0.04 |
March | 12.64 | 10.61 | 8.97 | 2.93 | 3.55 | 84.90 | 179.28 | 0.03 |
April | 15.30 | 12.62 | 10.61 | 2.62 | 4.76 | 81.20 | 282.81 | 0.02 |
May | 15.56 | 12.65 | 10.56 | 2.92 | 6.17 | 105.80 | 234.18 | 0.01 |
June | 17.67 | 14.80 | 13.02 | 2.53 | 9.03 | 98.05 | 261.27 | 0.00 |
July | 19.43 | 16.76 | 15.28 | 2.35 | 9.62 | 86.54 | 312.15 | 0.00 |
August | 19.66 | 17.23 | 15.95 | 2.55 | 9.62 | 74.58 | 307.55 | 0.00 |
September | 18.47 | 15.50 | 13.65 | 2.19 | 8.99 | 70.75 | 240.05 | 0.00 |
October | 18.77 | 13.72 | 9.60 | 2.71 | 7.74 | 53.88 | 216.36 | 0.00 |
November | 14.32 | 10.43 | 6.22 | 2.47 | 2.41 | 50.75 | 207.87 | 0.01 |
December | 13.59 | 8.82 | 3.19 | 2.50 | 0.05 | 39.49 | 221.83 | 0.00 |
Annual Sum or Average | 16.01 | 12.76 | 10.02 | 2.59 | 5.49 | 71.44 | 237.65 | 0.01 |
Minimum of Months | 12.64 | 8.82 | 3.19 | 2.19 | 0.05 | 39.49 | 175.60 | 0.00 |
Maximum of Months | 19.66 | 17.23 | 15.95 | 3.12 | 9.62 | 105.80 | 312.15 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 26.00 | 13-JAN-13:00 | 15.46 | 8.00 | 3.10 | 11.84 | 120.00 | 725.00 |
February | 26.00 | 01-FEB-11:00 | 14.67 | 6.00 | 4.10 | 10.11 | 166.00 | 715.50 |
March | 24.00 | 11-MAR-10:00 | 13.82 | 6.00 | 2.60 | 8.15 | 120.00 | 907.00 |
April | 27.00 | 26-APR-12:00 | 17.13 | 11.00 | 4.10 | 12.22 | 159.00 | 884.00 |
May | 24.00 | 03-MAY-11:00 | 15.05 | 9.00 | 4.10 | 12.98 | 187.00 | 842.50 |
June | 25.00 | 29-JUN-10:00 | 19.59 | 17.00 | 4.60 | 11.65 | 177.50 | 829.00 |
July | 28.00 | 19-JUL-10:00 | 20.49 | 17.00 | 3.60 | 14.65 | 173.00 | 813.00 |
August | 28.00 | 14-AUG-10:00 | 21.19 | 18.00 | 3.60 | 14.84 | 148.00 | 840.00 |
September | 36.00 | 29-SEP-10:00 | 17.91 | 5.00 | 3.60 | 19.35 | 159.50 | 790.00 |
October | 37.00 | 16-OCT-10:00 | 17.87 | 4.00 | 5.70 | 20.05 | 122.00 | 871.50 |
November | 27.00 | 19-NOV-12:00 | 14.96 | 6.00 | 4.10 | 11.07 | 128.50 | 796.00 |
December | 26.00 | 05-DEC-09:00 | 13.09 | 1.00 | 3.60 | 8.94 | 75.50 | 857.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 24.00 | 13.09 | 1.00 | 2.60 | 8.15 | 75.50 | 715.50 | |
Maximum of Months | 37.00 | 21.19 | 18.00 | 5.70 | 20.05 | 187.00 | 907.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.00 | 08-JAN-06:00 | -0.3 | -2.0 | 3.10 | -15.5 | 11.50 | 193.50 |
February | 5.00 | 04-FEB-05:00 | 0.22 | -8.0 | 4.10 | -10.9 | 0.00 | 0.00 |
March | 4.00 | 07-MAR-04:00 | 3.53 | 3.00 | 0.00 | -11.4 | 0.00 | 0.00 |
April | 7.00 | 01-APR-05:00 | 4.33 | 1.00 | 4.10 | -9.0 | 23.50 | 211.00 |
May | 8.00 | 14-MAY-03:00 | 7.45 | 7.00 | 1.50 | -6.6 | 0.00 | 0.00 |
June | 11.00 | 13-JUN-03:00 | 9.85 | 9.00 | 2.10 | -3.4 | 0.00 | 0.00 |
July | 13.00 | 06-JUL-00:00 | 13.00 | 13.00 | 0.00 | -0.6 | 0.00 | 0.00 |
August | 14.00 | 24-AUG-01:00 | 14.00 | 14.00 | 0.00 | 0.51 | 0.00 | 0.00 |
September | 11.00 | 20-SEP-02:00 | 9.85 | 9.00 | 1.50 | -3.4 | 0.00 | 0.00 |
October | 9.00 | 12-OCT-04:00 | 6.56 | 4.00 | 3.10 | -6.4 | 0.00 | 0.00 |
November | 7.00 | 05-NOV-01:00 | 5.54 | 4.00 | 3.10 | -8.3 | 0.00 | 0.00 |
December | 5.00 | 03-DEC-00:00 | 5.00 | 5.00 | 2.10 | -0.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.00 | -0.3 | -8.0 | 0.00 | -15.5 | 0.00 | 0.00 | |
Maximum of Months | 14.00 | 14.00 | 14.00 | 4.10 | 0.51 | 23.50 | 211.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 17.04 | 17-JAN-11:00 | 24.00 | 13.00 | 3.10 | 12.79 | 223.50 | 9.00 |
February | 16.80 | 11-FEB-13:00 | 18.00 | 16.20 | 1.10 | 15.02 | 241.00 | 12.50 |
March | 17.41 | 22-MAR-12:00 | 22.00 | 15.00 | 3.10 | 8.35 | 145.50 | 876.00 |
April | 18.33 | 26-APR-10:00 | 26.00 | 14.00 | 4.10 | 12.03 | 141.50 | 915.50 |
May | 16.69 | 05-MAY-14:00 | 18.00 | 16.00 | 5.10 | 8.74 | 303.50 | 269.00 |
June | 19.59 | 29-JUN-10:00 | 25.00 | 17.00 | 4.60 | 11.65 | 177.50 | 829.00 |
July | 21.19 | 19-JUL-11:00 | 28.00 | 18.00 | 4.60 | 14.84 | 182.50 | 808.00 |
August | 21.20 | 18-AUG-11:00 | 28.00 | 18.00 | 3.60 | 17.21 | 244.00 | 667.50 |
September | 21.85 | 22-SEP-11:00 | 26.00 | 20.00 | 2.60 | 20.05 | 284.00 | 21.00 |
October | 21.09 | 01-OCT-11:00 | 26.00 | 19.00 | 3.60 | 13.16 | 102.00 | 899.50 |
November | 16.52 | 10-NOV-12:00 | 21.00 | 14.00 | 5.10 | 7.15 | 131.00 | 808.50 |
December | 15.64 | 07-DEC-12:00 | 20.00 | 13.00 | 5.10 | 5.94 | 89.00 | 868.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.64 | 18.00 | 13.00 | 1.10 | 5.94 | 89.00 | 9.00 | |
Maximum of Months | 21.85 | 28.00 | 20.00 | 5.10 | 20.05 | 303.50 | 915.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.00 | 17-JAN-12:00 | 22.00 | 16.85 | 2.10 | 11.65 | 241.50 | 67.50 |
February | 16.20 | 11-FEB-13:00 | 18.00 | 16.80 | 1.10 | 15.02 | 241.00 | 12.50 |
March | 15.00 | 23-MAR-15:20 | 21.67 | 17.34 | 3.77 | 8.02 | 112.00 | 809.83 |
April | 15.00 | 26-APR-21:19 | 16.00 | 15.39 | 2.23 | 6.15 | 0.00 | 0.00 |
May | 16.00 | 05-MAY-14:00 | 18.00 | 16.69 | 5.10 | 8.74 | 303.50 | 269.00 |
June | 17.00 | 28-JUN-08:00 | 19.00 | 17.66 | 1.50 | 16.12 | 285.00 | 428.50 |
July | 18.00 | 18-JUL-10:00 | 26.00 | 20.47 | 4.60 | 12.79 | 169.00 | 819.00 |
August | 18.10 | 14-AUG-09:00 | 26.90 | 20.93 | 3.40 | 13.73 | 139.00 | 817.00 |
September | 20.00 | 22-SEP-09:00 | 22.00 | 20.55 | 1.50 | 16.30 | 296.00 | 18.00 |
October | 19.00 | 01-OCT-07:10 | 19.17 | 19.06 | 0.25 | 16.82 | 53.33 | 0.00 |
November | 15.00 | 10-NOV-17:19 | 16.67 | 15.62 | 2.77 | 3.34 | 0.00 | 0.00 |
December | 13.00 | 07-DEC-12:00 | 20.00 | 15.64 | 5.10 | 5.94 | 89.00 | 868.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.00 | 16.00 | 15.39 | 0.25 | 3.34 | 0.00 | 0.00 | |
Maximum of Months | 20.00 | 26.90 | 20.93 | 5.10 | 16.82 | 303.50 | 868.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 17.43 | 27.46 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 17.38 | 30.87 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 17.83 | 38.09 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 18.69 | 55.75 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 19.73 | 55.13 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 20.65 | 58.21 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 21.22 | 63.49 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 21.28 | 59.02 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 20.81 | 46.26 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 19.94 | 34.64 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 18.91 | 29.25 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 17.99 | 26.27 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 19.33 | 43.77 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 17.38 | 26.27 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 21.28 | 63.49 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH LAUNDRY G WATER HEATER
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.111412E+12 | -0.109633E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.177888E+10 | 82.17 | 0.00 | 0.00 |
February | 0.100712E+12 | -0.990946E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.161716E+10 | 82.17 | 0.00 | 0.00 |
March | 0.110744E+12 | -0.108944E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.179961E+10 | 82.17 | 0.00 | 0.00 |
April | 0.105762E+12 | -0.104022E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.174063E+10 | 82.17 | 0.00 | 0.00 |
May | 0.107539E+12 | -0.105741E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.179792E+10 | 82.17 | 0.00 | 0.00 |
June | 0.102553E+12 | -0.100811E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.174260E+10 | 82.17 | 0.00 | 0.00 |
July | 0.104996E+12 | -0.103206E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.179049E+10 | 82.17 | 0.00 | 0.00 |
August | 0.104893E+12 | -0.103106E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.178721E+10 | 82.17 | 0.00 | 0.00 |
September | 0.102270E+12 | -0.100550E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.172007E+10 | 82.17 | 0.00 | 0.00 |
October | 0.107145E+12 | -0.105375E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.176934E+10 | 82.17 | 0.00 | 0.00 |
November | 0.105380E+12 | -0.103669E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.171076E+10 | 82.17 | 0.00 | 0.00 |
December | 0.110455E+12 | -0.108679E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.177512E+10 | 82.17 | 0.00 | 0.00 |
Annual Sum or Average | 0.127386E+13 | -0.125283E+13 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.210298E+11 | 82.17 | 0.00 | 0.00 |
Minimum of Months | 0.100712E+12 | -0.109633E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.179961E+10 | 82.17 | 0.00 | 0.00 |
Maximum of Months | 0.111412E+12 | -0.990946E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.161716E+10 | 82.17 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.804802E+10 | -0.788296E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -165061401.7 | 82.17 | 0.00 | 0.00 |
February | 0.727211E+10 | -0.712336E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -148749255.8 | 82.17 | 0.00 | 0.00 |
March | 0.804647E+10 | -0.788155E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164915056.0 | 82.17 | 0.00 | 0.00 |
April | 0.779738E+10 | -0.763820E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -159184352.9 | 82.17 | 0.00 | 0.00 |
May | 0.804744E+10 | -0.788296E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164481543.5 | 82.17 | 0.00 | 0.00 |
June | 0.778883E+10 | -0.762976E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -159071255.9 | 82.17 | 0.00 | 0.00 |
July | 0.805571E+10 | -0.789140E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164312252.1 | 82.17 | 0.00 | 0.00 |
August | 0.804727E+10 | -0.788296E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164306516.0 | 82.17 | 0.00 | 0.00 |
September | 0.779867E+10 | -0.763961E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -159058929.9 | 82.17 | 0.00 | 0.00 |
October | 0.804595E+10 | -0.788155E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164392302.3 | 82.17 | 0.00 | 0.00 |
November | 0.778066E+10 | -0.762132E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -159336383.5 | 82.17 | 0.00 | 0.00 |
December | 0.805635E+10 | -0.789140E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164946598.5 | 82.17 | 0.00 | 0.00 |
Annual Sum or Average | 0.947849E+11 | -0.928470E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.193782E+10 | 82.17 | 0.00 | 0.00 |
Minimum of Months | 0.727211E+10 | -0.789140E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -165061401.7 | 82.17 | 0.00 | 0.00 |
Maximum of Months | 0.805635E+10 | -0.712336E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -148749255.8 | 82.17 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.637463E+11 | -0.622046E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.154166E+10 | 60.05 | 0.00 | 0.00 |
February | 0.576644E+11 | -0.562575E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.140693E+10 | 60.05 | 0.00 | 0.00 |
March | 0.632352E+11 | -0.616648E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.157039E+10 | 60.05 | 0.00 | 0.00 |
April | 0.599449E+11 | -0.584264E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.151845E+10 | 60.05 | 0.00 | 0.00 |
May | 0.604411E+11 | -0.588730E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.156805E+10 | 60.05 | 0.00 | 0.00 |
June | 0.572052E+11 | -0.556840E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.152118E+10 | 60.05 | 0.00 | 0.00 |
July | 0.582097E+11 | -0.566520E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.155776E+10 | 60.05 | 0.00 | 0.00 |
August | 0.581771E+11 | -0.566239E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.155321E+10 | 60.05 | 0.00 | 0.00 |
September | 0.569226E+11 | -0.554326E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.148996E+10 | 60.05 | 0.00 | 0.00 |
October | 0.600528E+11 | -0.585243E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.152844E+10 | 60.05 | 0.00 | 0.00 |
November | 0.595757E+11 | -0.580986E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.147705E+10 | 60.05 | 0.00 | 0.00 |
December | 0.629138E+11 | -0.613773E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.153645E+10 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.718089E+12 | -0.699819E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.182695E+11 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.569226E+11 | -0.622046E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.157039E+10 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.637463E+11 | -0.554326E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.140693E+10 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: LOBBY_FLR_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.87 | 0.86 | 01-JAN-07:30 | 7052.51 | 37.52 | 285.00 | 281.50 | 1015.00 | 27.16 | 209.67 | 265.00 |
February | 279.67 | 0.87 | 0.86 | 01-FEB-07:30 | 4904.28 | 32.25 | 218.50 | 277.00 | 670.04 | 23.86 | 187.83 | 247.67 |
March | 338.17 | 0.87 | 0.86 | 01-MAR-07:40 | 1285.36 | 20.03 | 18.83 | 322.67 | 479.18 | 21.29 | 186.67 | 268.33 |
April | 358.33 | 0.87 | 0.86 | 01-APR-07:19 | 884.18 | 19.54 | 0.00 | 335.17 | 373.14 | 21.29 | 213.17 | 274.67 |
May | 393.83 | 0.88 | 0.86 | 01-MAY-06:00 | 803.15 | 19.04 | 0.00 | 367.83 | 327.24 | 20.77 | 162.33 | 280.33 |
June | 381.00 | 0.88 | 0.86 | 01-JUN-07:10 | 694.69 | 18.85 | 0.00 | 360.33 | 292.55 | 20.60 | 125.00 | 260.50 |
July | 408.67 | 0.88 | 0.86 | 01-JUL-07:00 | 684.44 | 18.97 | 0.00 | 369.83 | 298.69 | 20.73 | 173.83 | 280.00 |
August | 390.67 | 0.88 | 0.86 | 01-AUG-07:40 | 744.35 | 19.22 | 0.00 | 356.00 | 324.31 | 20.97 | 187.33 | 283.00 |
September | 328.83 | 0.87 | 0.86 | 01-SEP-07:10 | 999.70 | 19.53 | 0.33 | 311.00 | 416.32 | 21.30 | 182.17 | 261.17 |
October | 296.17 | 0.87 | 0.86 | 01-OCT-09:39 | 3383.21 | 27.32 | 136.83 | 307.33 | 492.85 | 21.81 | 127.33 | 256.83 |
November | 300.00 | 0.87 | 0.86 | 01-NOV-06:49 | 6865.72 | 37.35 | 295.17 | 281.67 | 889.85 | 26.74 | 225.17 | 269.50 |
December | 297.00 | 0.87 | 0.86 | 01-DEC-07:19 | 6902.00 | 37.93 | 289.17 | 282.17 | 1244.45 | 28.71 | 200.50 | 267.83 |
Annual Sum or Average | 4065.67 | 0.87 | 2652.36 | 24.77 | 1243.83 | 3852.50 | 538.51 | 22.67 | 2181.00 | 3214.83 | ||
Minimum of Months | 279.67 | 0.87 | 0.86 | 684.44 | 18.85 | 0.00 | 277.00 | 292.55 | 20.60 | 125.00 | 247.67 | |
Maximum of Months | 408.67 | 0.88 | 0.86 | 7052.51 | 37.93 | 295.17 | 369.83 | 1244.45 | 28.71 | 225.17 | 283.00 |
Report: DaylightingReportMonthly
For: CAFE_FLR_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.25 | 0.22 | 01-JAN-07:19 | 7460.67 | 37.60 | 285.00 | 288.33 | 1425.15 | 26.86 | 184.67 | 276.00 |
February | 279.67 | 0.25 | 0.22 | 01-FEB-07:19 | 5228.42 | 32.34 | 219.00 | 283.17 | 993.76 | 23.90 | 182.17 | 266.00 |
March | 338.17 | 0.28 | 0.22 | 01-MAR-07:10 | 1535.43 | 20.47 | 44.50 | 331.67 | 728.33 | 21.58 | 206.00 | 303.83 |
April | 358.33 | 0.26 | 0.22 | 01-APR-06:40 | 1086.01 | 20.10 | 41.67 | 348.00 | 574.49 | 21.65 | 229.33 | 317.83 |
May | 393.83 | 0.27 | 0.22 | 01-MAY-06:30 | 945.90 | 19.84 | 7.17 | 381.33 | 469.50 | 21.36 | 251.33 | 346.17 |
June | 381.00 | 0.28 | 0.22 | 01-JUN-06:40 | 823.20 | 19.70 | 0.17 | 372.50 | 420.64 | 21.22 | 248.50 | 336.50 |
July | 408.67 | 0.28 | 0.22 | 01-JUL-06:10 | 820.23 | 19.76 | 0.67 | 380.33 | 434.09 | 21.30 | 305.33 | 350.50 |
August | 390.67 | 0.28 | 0.22 | 01-AUG-07:10 | 913.02 | 19.87 | 14.50 | 368.50 | 492.57 | 21.42 | 254.50 | 339.67 |
September | 328.83 | 0.27 | 0.22 | 01-SEP-06:49 | 1240.89 | 19.96 | 38.67 | 324.17 | 656.95 | 21.56 | 193.33 | 295.50 |
October | 296.17 | 0.26 | 0.22 | 01-OCT-09:39 | 3714.16 | 27.35 | 138.50 | 318.17 | 821.62 | 21.74 | 123.67 | 286.50 |
November | 300.00 | 0.26 | 0.22 | 01-NOV-06:40 | 7249.89 | 37.41 | 295.17 | 286.17 | 1271.19 | 26.49 | 203.33 | 277.67 |
December | 297.00 | 0.26 | 0.22 | 01-DEC-07:10 | 7326.86 | 38.01 | 289.33 | 287.83 | 1668.60 | 28.35 | 178.67 | 277.67 |
Annual Sum or Average | 4065.67 | 0.27 | 2901.42 | 25.22 | 1374.33 | 3970.17 | 786.93 | 22.90 | 2560.83 | 3673.83 | ||
Minimum of Months | 279.67 | 0.25 | 0.22 | 820.23 | 19.70 | 0.17 | 283.17 | 420.64 | 21.22 | 123.67 | 266.00 | |
Maximum of Months | 408.67 | 0.28 | 0.22 | 7460.67 | 38.01 | 295.17 | 381.33 | 1668.60 | 28.35 | 305.33 | 350.50 |
Report: DaylightingReportMonthly
For: DINING_FLR_6_DAYLCTRL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.70 | 0.60 | 01-JAN-09:20 | 331.49 | 14.72 | 0.00 | 246.50 | 171.60 | 18.27 | 0.00 | 65.83 |
February | 279.67 | 0.67 | 0.60 | 01-FEB-10:30 | 414.60 | 15.58 | 0.00 | 259.17 | 198.91 | 18.90 | 0.00 | 130.50 |
March | 338.17 | 0.65 | 0.60 | 01-MAR-10:30 | 496.51 | 16.13 | 0.00 | 317.67 | 228.10 | 19.33 | 0.00 | 229.67 |
April | 358.33 | 0.63 | 0.60 | 01-APR-07:00 | 523.15 | 17.06 | 0.00 | 346.17 | 256.09 | 20.31 | 33.67 | 297.67 |
May | 393.83 | 0.62 | 0.60 | 01-MAY-06:40 | 703.49 | 18.00 | 12.50 | 389.50 | 316.66 | 21.20 | 95.33 | 355.00 |
June | 381.00 | 0.62 | 0.60 | 01-JUN-06:40 | 745.03 | 20.01 | 58.83 | 383.67 | 344.66 | 22.41 | 133.83 | 348.17 |
July | 408.67 | 0.62 | 0.60 | 01-JUL-05:49 | 677.39 | 19.27 | 44.83 | 391.83 | 298.57 | 20.88 | 117.33 | 362.17 |
August | 390.67 | 0.63 | 0.60 | 01-AUG-07:19 | 536.69 | 17.14 | 0.00 | 372.67 | 257.97 | 20.42 | 59.50 | 331.17 |
September | 328.83 | 0.64 | 0.60 | 01-SEP-06:00 | 460.90 | 16.42 | 0.00 | 314.83 | 228.79 | 19.69 | 1.67 | 235.33 |
October | 296.17 | 0.69 | 0.60 | 01-OCT-09:39 | 343.47 | 15.07 | 0.00 | 273.00 | 174.39 | 18.51 | 0.00 | 96.83 |
November | 300.00 | 0.70 | 0.60 | 01-NOV-08:30 | 340.01 | 14.51 | 0.00 | 252.50 | 173.32 | 17.96 | 0.00 | 81.00 |
December | 297.00 | 0.71 | 0.60 | 01-DEC-09:30 | 298.98 | 14.19 | 0.00 | 239.67 | 159.19 | 17.81 | 0.00 | 46.17 |
Annual Sum or Average | 4065.67 | 0.65 | 506.69 | 16.71 | 116.17 | 3787.17 | 241.01 | 19.80 | 441.33 | 2579.50 | ||
Minimum of Months | 279.67 | 0.62 | 0.60 | 298.98 | 14.19 | 0.00 | 239.67 | 159.19 | 17.81 | 0.00 | 46.17 | |
Maximum of Months | 408.67 | 0.71 | 0.60 | 745.03 | 20.01 | 58.83 | 391.83 | 344.66 | 22.41 | 133.83 | 362.17 |
Report: DaylightingReportMonthly
For: BANQUET_FLR_6_DAYLCTRL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.70 | 0.60 | 01-JAN-09:20 | 331.49 | 14.72 | 0.00 | 246.50 | 171.60 | 18.27 | 0.00 | 65.83 |
February | 279.67 | 0.67 | 0.60 | 01-FEB-10:30 | 414.60 | 15.58 | 0.00 | 259.17 | 198.91 | 18.90 | 0.00 | 130.50 |
March | 338.17 | 0.65 | 0.60 | 01-MAR-10:30 | 496.51 | 16.13 | 0.00 | 317.67 | 228.10 | 19.33 | 0.00 | 229.67 |
April | 358.33 | 0.63 | 0.60 | 01-APR-07:00 | 523.15 | 17.06 | 0.00 | 346.17 | 256.09 | 20.31 | 33.67 | 297.67 |
May | 393.83 | 0.62 | 0.60 | 01-MAY-06:40 | 703.49 | 18.00 | 12.50 | 389.50 | 316.66 | 21.20 | 95.33 | 355.00 |
June | 381.00 | 0.62 | 0.60 | 01-JUN-06:40 | 745.03 | 20.01 | 58.83 | 383.67 | 344.66 | 22.41 | 133.83 | 348.17 |
July | 408.67 | 0.62 | 0.60 | 01-JUL-05:49 | 677.39 | 19.27 | 44.83 | 391.83 | 298.57 | 20.88 | 117.33 | 362.17 |
August | 390.67 | 0.63 | 0.60 | 01-AUG-07:19 | 536.69 | 17.14 | 0.00 | 372.67 | 257.97 | 20.42 | 59.67 | 331.17 |
September | 328.83 | 0.64 | 0.60 | 01-SEP-06:00 | 460.90 | 16.42 | 0.00 | 314.83 | 228.79 | 19.69 | 1.67 | 235.33 |
October | 296.17 | 0.69 | 0.60 | 01-OCT-09:39 | 343.47 | 15.07 | 0.00 | 273.00 | 174.39 | 18.51 | 0.00 | 96.83 |
November | 300.00 | 0.70 | 0.60 | 01-NOV-08:30 | 340.01 | 14.51 | 0.00 | 252.50 | 173.32 | 17.96 | 0.00 | 81.00 |
December | 297.00 | 0.71 | 0.60 | 01-DEC-09:30 | 298.98 | 14.19 | 0.00 | 239.67 | 159.19 | 17.81 | 0.00 | 46.17 |
Annual Sum or Average | 4065.67 | 0.65 | 506.69 | 16.71 | 116.17 | 3787.17 | 241.01 | 19.80 | 441.50 | 2579.50 | ||
Minimum of Months | 279.67 | 0.62 | 0.60 | 298.98 | 14.19 | 0.00 | 239.67 | 159.19 | 17.81 | 0.00 | 46.17 | |
Maximum of Months | 408.67 | 0.71 | 0.60 | 745.03 | 20.01 | 58.83 | 391.83 | 344.66 | 22.41 | 133.83 | 362.17 |
Report: CoilReportMonthly
For: FLR_3_DOAS HEATING COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.796627E+10 | 8943.46 | 08-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.641498E+10 | 8391.78 | 05-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.857742E+10 | 8532.16 | 07-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.405566E+10 | 8113.59 | 01-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.360689E+10 | 7975.38 | 19-MAY-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.639403E+09 | 5275.70 | 13-JUN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 37027035.96 | 2369.00 | 06-JUL-01:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17469671.82 | 904.60 | 24-AUG-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.319034E+09 | 5276.32 | 20-SEP-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.143387E+10 | 7833.53 | 28-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.564075E+10 | 8114.43 | 05-NOV-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.800628E+10 | 8394.05 | 03-DEC-01:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.467151E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 17469671.82 | 904.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.857742E+10 | 8943.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.876339E+11 | 90052.39 | 08-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.697356E+11 | 85883.31 | 03-FEB-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.944809E+11 | 85927.47 | 07-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.427837E+11 | 83270.33 | 15-APR-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.373482E+11 | 81128.49 | 19-MAY-05:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.689025E+10 | 57136.42 | 13-JUN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.411132E+09 | 25218.19 | 06-JUL-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.172226E+09 | 9689.23 | 31-AUG-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.305474E+10 | 55155.88 | 20-SEP-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.153624E+11 | 81015.52 | 29-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.592536E+11 | 85603.52 | 29-NOV-22:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.870412E+11 | 85991.60 | 19-DEC-21:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.504168E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.172226E+09 | 9689.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.944809E+11 | 90052.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.332628E+09 | 1925.02 | 08-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.256413E+09 | 1129.11 | 05-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.514578E+09 | 1836.34 | 30-MAR-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 83252708.09 | 1213.96 | 01-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.106887E+09 | 893.07 | 14-MAY-04:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11106353.56 | 249.91 | 08-JUN-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 106830.47 | 242.12 | 18-SEP-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6256419.62 | 291.09 | 25-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 51364596.35 | 766.63 | 05-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.205293E+09 | 1357.22 | 13-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.156789E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.514578E+09 | 1925.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 2968718.60 | 403.09 | 08-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 4693067.47 | 298.62 | 29-MAR-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 7661786.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4693067.47 | 403.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 38238505.42 | 717.78 | 09-JAN-05:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 41517258.91 | 724.64 | 30-MAR-03:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 706517.37 | 236.18 | 01-APR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 80462281.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 41517258.91 | 724.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 56035842.14 | 634.33 | 08-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 254521.67 | 64.41 | 28-FEB-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 59004038.53 | 548.89 | 30-MAR-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2187562.75 | 199.31 | 01-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5168509.81 | 161.73 | 24-DEC-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.122650E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 59004038.53 | 634.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.117002E+10 | 7951.53 | 08-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.304044E+09 | 7457.30 | 04-FEB-05:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.908492E+09 | 7587.25 | 07-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 91978727.01 | 3762.06 | 01-APR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 90052412.34 | 2742.38 | 27-MAY-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 30594977.86 | 760.88 | 12-JUN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 14665353.11 | 426.91 | 10-JUL-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 10543687.64 | 368.89 | 28-AUG-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 25182253.84 | 596.76 | 19-SEP-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 30754415.34 | 1330.44 | 28-OCT-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.227589E+09 | 4979.53 | 08-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.731222E+09 | 7462.77 | 23-DEC-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.363514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 10543687.64 | 368.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.117002E+10 | 7951.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 78573337.99 | 4212.33 | 08-JAN-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 43059475.14 | 1646.03 | 28-FEB-11:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145118E+09 | 4035.65 | 29-MAR-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 272494.63 | 571.82 | 22-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3263241.67 | 1443.00 | 09-MAY-10:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 264433.19 | 529.03 | 08-JUN-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 374094.61 | 785.80 | 18-SEP-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 549999.19 | 1307.59 | 13-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.271475E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.145118E+09 | 4212.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 11832122.83 | 4669.87 | 08-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 18366855.67 | 4941.61 | 29-MAR-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 30198978.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18366855.67 | 4941.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.271411E+09 | 6124.03 | 03-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4167777.25 | 1616.62 | 28-FEB-11:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.334887E+09 | 5250.44 | 30-MAR-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 10065173.73 | 2300.44 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 163292.22 | 433.22 | 15-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.620695E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.334887E+09 | 6124.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.529134E+09 | 4618.28 | 08-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 64628781.39 | 1414.50 | 05-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.455145E+09 | 3614.76 | 30-MAR-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 18177942.24 | 1666.09 | 01-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1736212.89 | 479.86 | 14-MAY-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 8364322.69 | 807.85 | 05-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.207896E+09 | 2315.54 | 13-DEC-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.128508E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.529134E+09 | 4618.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.139376E+09 | 4970.20 | 09-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 267470.62 | 293.68 | 05-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 98148498.19 | 4321.90 | 30-MAR-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 19288841.59 | 2519.96 | 24-DEC-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.257081E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.139376E+09 | 4970.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.403588E+09 | 3762.08 | 29-JAN-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.260197E+09 | 3763.24 | 16-FEB-19:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.450385E+09 | 3842.99 | 29-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 62793628.56 | 3760.22 | 19-APR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 46330906.75 | 3765.73 | 12-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 8775161.79 | 3757.83 | 24-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6988001.47 | 3755.40 | 04-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6530290.29 | 3236.58 | 03-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 10112038.45 | 3758.63 | 21-SEP-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16478989.40 | 3759.68 | 23-OCT-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.108715E+09 | 3759.49 | 09-NOV-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.287276E+09 | 3763.06 | 08-DEC-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.166817E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 6530290.29 | 3236.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.450385E+09 | 3842.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.792308E+09 | 3827.50 | 03-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.414265E+09 | 3804.93 | 25-FEB-16:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.585084E+09 | 3842.51 | 30-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 71099421.82 | 3745.39 | 02-APR-08:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 38434517.05 | 3745.12 | 28-MAY-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5468887.77 | 3745.08 | 02-JUN-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 2089366.46 | 2632.29 | 10-JUL-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1389645.57 | 1940.07 | 22-AUG-21:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 7102440.71 | 3745.32 | 03-SEP-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16823142.57 | 3744.68 | 27-OCT-08:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.251666E+09 | 3744.44 | 04-NOV-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.617337E+09 | 3825.12 | 13-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.280307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1389645.57 | 1940.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.792308E+09 | 3842.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.166232E+10 | 22023.04 | 26-JAN-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.354240E+09 | 22026.94 | 22-FEB-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.943655E+09 | 22027.33 | 01-MAR-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.108097E+09 | 22020.34 | 03-APR-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 64395207.48 | 22016.61 | 09-MAY-15:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 24283152.53 | 21973.13 | 06-JUN-15:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 12450733.23 | 16944.56 | 17-JUL-15:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 13589214.53 | 19389.06 | 22-AUG-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 44081214.98 | 22019.00 | 20-SEP-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 69231492.28 | 22016.37 | 13-OCT-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.271159E+09 | 22029.99 | 14-NOV-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.100157E+10 | 22022.39 | 15-DEC-16:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.456907E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 12450733.23 | 16944.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.166232E+10 | 22029.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.400723E+09 | 3697.07 | 18-JAN-19:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.309642E+09 | 3700.09 | 23-FEB-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.494672E+09 | 3745.06 | 28-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 73065065.45 | 3700.65 | 22-APR-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 67284504.29 | 3700.96 | 12-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 10148980.32 | 3598.23 | 08-JUN-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1315665.72 | 3423.00 | 09-JUL-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1310712.36 | 3021.69 | 08-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 8188071.61 | 3429.56 | 23-SEP-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17240045.74 | 3695.39 | 25-OCT-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.139458E+09 | 3697.80 | 02-NOV-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.316793E+09 | 3701.36 | 13-DEC-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.183984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1310712.36 | 3021.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.494672E+09 | 3745.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.759192E+09 | 3726.46 | 02-JAN-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.492474E+09 | 3737.89 | 25-FEB-16:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.643972E+09 | 3754.08 | 29-MAR-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 88205913.90 | 3678.00 | 15-APR-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 57747716.65 | 3679.46 | 12-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5258685.87 | 3352.89 | 11-JUN-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1335794.67 | 2069.04 | 27-JUL-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 926384.18 | 2181.67 | 21-AUG-20:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5951711.75 | 2774.94 | 27-SEP-21:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 23752432.18 | 3677.40 | 24-OCT-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.310932E+09 | 3681.15 | 04-NOV-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.643170E+09 | 3741.55 | 12-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.303292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 926384.18 | 2069.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.759192E+09 | 3754.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.216012E+09 | 1139.12 | 16-JAN-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.166374E+09 | 1172.62 | 25-FEB-16:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.226449E+09 | 1179.79 | 29-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 44529303.98 | 1087.23 | 17-APR-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 39613829.90 | 1140.37 | 08-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6060574.29 | 1139.03 | 08-JUN-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1573008.66 | 999.22 | 04-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1502505.53 | 857.98 | 22-AUG-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3431970.52 | 1013.43 | 22-SEP-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 20870046.93 | 1139.53 | 23-OCT-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 98520027.45 | 1010.52 | 09-NOV-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.184605E+09 | 1063.39 | 27-DEC-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.100954E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1502505.53 | 857.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.226449E+09 | 1179.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.382846E+09 | 1175.03 | 03-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.241353E+09 | 1169.81 | 25-FEB-16:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.282888E+09 | 1177.22 | 30-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 47547650.23 | 1121.35 | 14-APR-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 29085379.70 | 1132.40 | 24-MAY-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2850358.57 | 1025.67 | 08-JUN-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 297639.40 | 642.29 | 06-JUL-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 435667.28 | 614.72 | 22-AUG-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2596142.73 | 978.24 | 12-SEP-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 25199955.61 | 1131.89 | 23-OCT-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.182382E+09 | 1111.47 | 17-NOV-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.337000E+09 | 1173.86 | 13-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.153448E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 297639.40 | 614.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.382846E+09 | 1177.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.217440E+09 | 3835.17 | 25-JAN-16:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.197682E+09 | 4442.33 | 25-FEB-09:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.502887E+09 | 5484.79 | 16-MAR-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 91510462.41 | 5493.34 | 17-APR-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.135894E+09 | 5501.15 | 12-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 26099486.93 | 5493.63 | 22-JUN-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 10568714.50 | 5486.34 | 04-JUL-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5680952.44 | 4475.46 | 22-AUG-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11845472.42 | 5043.87 | 22-SEP-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 18035621.22 | 5314.23 | 23-OCT-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 44952791.81 | 5490.90 | 24-NOV-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.138287E+09 | 5488.49 | 06-DEC-09:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.140088E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 5680952.44 | 3835.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.502887E+09 | 5501.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.352394E+10 | 0.349904E+10 | 20570.98 | 13-JAN-14:00 | 20570.98 | 0.16 |
February | 0.00 | 0.00 | 0.189616E+10 | 0.184036E+10 | 17583.23 | 01-FEB-09:53 | 17583.23 | 0.14 |
March | 0.00 | 0.00 | 0.213914E+10 | 0.197595E+10 | 22012.17 | 22-MAR-13:00 | 14832.69 | 0.12 |
April | 0.00 | 0.00 | 0.536108E+10 | 0.504766E+10 | 22090.96 | 26-APR-13:00 | 22090.96 | 0.27 |
May | 0.00 | 0.00 | 0.568444E+10 | 0.557746E+10 | 18829.64 | 04-MAY-13:00 | 16265.15 | 0.35 |
June | 0.00 | 0.00 | 0.127679E+11 | 0.101514E+11 | 30817.80 | 29-JUN-12:15 | 17826.82 | 0.64 |
July | 0.00 | 0.00 | 0.285718E+11 | 0.167816E+11 | 40153.36 | 31-JUL-12:50 | 23766.73 | 0.78 |
August | 0.00 | 0.00 | 0.326065E+11 | 0.176854E+11 | 38729.91 | 14-AUG-10:00 | 22142.75 | 0.78 |
September | 0.00 | 0.00 | 0.185738E+11 | 0.130116E+11 | 39619.58 | 22-SEP-12:15 | 19372.88 | 0.69 |
October | 0.00 | 0.00 | 0.206208E+11 | 0.151880E+11 | 38860.24 | 01-OCT-12:10 | 20585.66 | 0.46 |
November | 0.00 | 0.00 | 0.354751E+10 | 0.347968E+10 | 21516.80 | 19-NOV-13:05 | 21516.80 | 0.19 |
December | 0.00 | 0.00 | 0.428641E+10 | 0.428428E+10 | 20480.92 | 05-DEC-09:55 | 20480.92 | 0.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.139579E+12 | 0.985224E+11 | 0.39 | |||
Minimum of Months | 0.00 | 0.00 | 0.189616E+10 | 0.184036E+10 | 17583.23 | 14832.69 | 0.06 | |
Maximum of Months | 0.00 | 0.00 | 0.326065E+11 | 0.176854E+11 | 40153.36 | 23766.73 | 0.78 |
Report: CoilReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.580356E+11 | 0.578582E+11 | 209507.34 | 14-JAN-11:45 | 209507.34 | 0.26 |
February | 0.00 | 0.00 | 0.325376E+11 | 0.317867E+11 | 197645.24 | 01-FEB-11:45 | 197645.24 | 0.24 |
March | 0.00 | 0.00 | 0.360422E+11 | 0.353849E+11 | 182548.43 | 23-MAR-10:45 | 147380.26 | 0.24 |
April | 0.00 | 0.00 | 0.856442E+11 | 0.841340E+11 | 248801.82 | 26-APR-10:45 | 205354.12 | 0.47 |
May | 0.00 | 0.00 | 0.916843E+11 | 0.907220E+11 | 160265.73 | 18-MAY-10:45 | 143422.59 | 0.56 |
June | 0.00 | 0.00 | 0.168981E+12 | 0.147634E+12 | 311545.41 | 29-JUN-10:45 | 192253.53 | 0.85 |
July | 0.00 | 0.00 | 0.344845E+12 | 0.225519E+12 | 379846.46 | 31-JUL-10:45 | 224861.20 | 0.99 |
August | 0.00 | 0.00 | 0.388248E+12 | 0.235368E+12 | 407055.93 | 14-AUG-10:45 | 241645.37 | 0.99 |
September | 0.00 | 0.00 | 0.229551E+12 | 0.177330E+12 | 373451.97 | 22-SEP-12:00 | 185697.53 | 0.90 |
October | 0.00 | 0.00 | 0.260147E+12 | 0.209800E+12 | 383393.45 | 16-OCT-10:45 | 383393.45 | 0.61 |
November | 0.00 | 0.00 | 0.605792E+11 | 0.598840E+11 | 214444.18 | 19-NOV-11:45 | 214444.18 | 0.32 |
December | 0.00 | 0.00 | 0.668534E+11 | 0.668534E+11 | 193632.86 | 19-DEC-11:45 | 193632.86 | 0.12 |
Annual Sum or Average | 0.00 | 0.00 | 0.182315E+13 | 0.142227E+13 | 0.55 | |||
Minimum of Months | 0.00 | 0.00 | 0.325376E+11 | 0.317867E+11 | 160265.73 | 143422.59 | 0.12 | |
Maximum of Months | 0.00 | 0.00 | 0.388248E+12 | 0.235368E+12 | 407055.93 | 383393.45 | 0.99 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.217582E+10 | 0.109536E+10 | 14065.88 | 21-JAN-09:02 | 11622.72 | 0.48 |
February | 0.00 | 0.00 | 0.194204E+10 | 0.103107E+10 | 14877.07 | 13-FEB-16:02 | 10432.39 | 0.46 |
March | 0.00 | 0.00 | 0.211089E+10 | 0.957685E+09 | 14078.98 | 17-MAR-15:01 | 11444.70 | 0.51 |
April | 0.00 | 0.00 | 0.416899E+10 | 0.200237E+10 | 13979.96 | 08-APR-08:61 | 11443.67 | 0.78 |
May | 0.00 | 0.00 | 0.391154E+10 | 0.178067E+10 | 14181.44 | 06-MAY-08:62 | 10700.47 | 0.77 |
June | 0.00 | 0.00 | 0.547476E+10 | 0.251281E+10 | 14344.78 | 16-JUN-15:01 | 11415.87 | 0.86 |
July | 0.00 | 0.00 | 0.761582E+10 | 0.370226E+10 | 14677.75 | 30-JUL-08:61 | 11155.09 | 0.92 |
August | 0.00 | 0.00 | 0.786608E+10 | 0.386137E+10 | 14919.63 | 18-AUG-08:61 | 10949.75 | 0.93 |
September | 0.00 | 0.00 | 0.624545E+10 | 0.296698E+10 | 14690.72 | 23-SEP-08:62 | 10361.66 | 0.90 |
October | 0.00 | 0.00 | 0.568310E+10 | 0.330525E+10 | 14855.68 | 01-OCT-08:61 | 11014.84 | 0.75 |
November | 0.00 | 0.00 | 0.292420E+10 | 0.151173E+10 | 14694.74 | 12-NOV-09:02 | 9717.97 | 0.58 |
December | 0.00 | 0.00 | 0.243721E+10 | 0.164179E+10 | 14045.90 | 25-DEC-16:01 | 14045.90 | 0.36 |
Annual Sum or Average | 0.00 | 0.00 | 0.525559E+11 | 0.263693E+11 | 0.69 | |||
Minimum of Months | 0.00 | 0.00 | 0.194204E+10 | 0.957685E+09 | 13979.96 | 9717.97 | 0.36 | |
Maximum of Months | 0.00 | 0.00 | 0.786608E+10 | 0.386137E+10 | 14919.63 | 14045.90 | 0.93 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.521995E+09 | 0.228927E+09 | 13786.68 | 20-JAN-19:01 | 10126.30 | 0.22 |
February | 0.00 | 0.00 | 0.698535E+09 | 0.299410E+09 | 14158.78 | 13-FEB-16:02 | 9779.89 | 0.27 |
March | 0.00 | 0.00 | 0.982138E+09 | 0.364959E+09 | 13823.06 | 22-MAR-18:51 | 10915.33 | 0.34 |
April | 0.00 | 0.00 | 0.245637E+10 | 0.950917E+09 | 14728.05 | 26-APR-21:51 | 11020.69 | 0.59 |
May | 0.00 | 0.00 | 0.271019E+10 | 0.108959E+10 | 14282.87 | 03-MAY-21:51 | 11403.74 | 0.60 |
June | 0.00 | 0.00 | 0.354110E+10 | 0.155581E+10 | 15246.55 | 28-JUN-21:51 | 11180.75 | 0.56 |
July | 0.00 | 0.00 | 0.496058E+10 | 0.247115E+10 | 15402.26 | 27-JUL-21:51 | 11095.00 | 0.56 |
August | 0.00 | 0.00 | 0.468699E+10 | 0.224037E+10 | 15277.88 | 16-AUG-21:51 | 11015.99 | 0.56 |
September | 0.00 | 0.00 | 0.344084E+10 | 0.144153E+10 | 14835.65 | 30-SEP-21:51 | 10947.98 | 0.56 |
October | 0.00 | 0.00 | 0.270654E+10 | 0.143225E+10 | 15243.46 | 01-OCT-08:51 | 9959.38 | 0.45 |
November | 0.00 | 0.00 | 0.942833E+09 | 0.380427E+09 | 14148.95 | 12-NOV-09:02 | 9257.71 | 0.35 |
December | 0.00 | 0.00 | 0.548646E+09 | 0.337562E+09 | 13652.50 | 09-DEC-16:01 | 11103.18 | 0.17 |
Annual Sum or Average | 0.00 | 0.00 | 0.281968E+11 | 0.127929E+11 | 0.44 | |||
Minimum of Months | 0.00 | 0.00 | 0.521995E+09 | 0.228927E+09 | 13652.50 | 9257.71 | 0.17 | |
Maximum of Months | 0.00 | 0.00 | 0.496058E+10 | 0.247115E+10 | 15402.26 | 11403.74 | 0.60 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.349880E+11 | 0.222311E+11 | 45911.75 | 14-JAN-12:40 | 33927.53 | 0.67 |
February | 0.00 | 0.00 | 0.224363E+11 | 0.135836E+11 | 41052.07 | 02-FEB-12:30 | 35743.23 | 0.55 |
March | 0.00 | 0.00 | 0.169593E+11 | 0.664649E+10 | 33759.25 | 11-MAR-13:10 | 26269.68 | 0.59 |
April | 0.00 | 0.00 | 0.192376E+11 | 0.631212E+10 | 25503.97 | 08-APR-12:40 | 13491.03 | 0.73 |
May | 0.00 | 0.00 | 0.116634E+11 | 0.266746E+10 | 22143.80 | 03-MAY-15:03 | 9960.59 | 0.65 |
June | 0.00 | 0.00 | 0.153682E+11 | 0.361980E+10 | 20191.17 | 30-JUN-15:06 | 7754.73 | 0.78 |
July | 0.00 | 0.00 | 0.235361E+11 | 0.664315E+10 | 24176.11 | 19-JUL-15:03 | 10746.75 | 0.92 |
August | 0.00 | 0.00 | 0.312057E+11 | 0.105790E+11 | 24264.48 | 30-AUG-12:40 | 12151.52 | 0.99 |
September | 0.00 | 0.00 | 0.343521E+11 | 0.144281E+11 | 42176.75 | 30-SEP-13:10 | 39301.46 | 0.98 |
October | 0.00 | 0.00 | 0.431468E+11 | 0.252556E+11 | 51201.35 | 16-OCT-12:20 | 43514.48 | 0.87 |
November | 0.00 | 0.00 | 0.356447E+11 | 0.227021E+11 | 48465.61 | 19-NOV-09:53 | 36991.93 | 0.67 |
December | 0.00 | 0.00 | 0.389257E+11 | 0.288208E+11 | 46123.66 | 19-DEC-13:00 | 46123.66 | 0.55 |
Annual Sum or Average | 0.00 | 0.00 | 0.327464E+12 | 0.163489E+12 | 0.75 | |||
Minimum of Months | 0.00 | 0.00 | 0.116634E+11 | 0.266746E+10 | 20191.17 | 7754.73 | 0.55 | |
Maximum of Months | 0.00 | 0.00 | 0.431468E+11 | 0.288208E+11 | 51201.35 | 46123.66 | 0.99 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.112394E+11 | 0.556612E+10 | 84417.85 | 20-JAN-19:01 | 66207.78 | 0.36 |
February | 0.00 | 0.00 | 0.127748E+11 | 0.582245E+10 | 82887.72 | 13-FEB-21:12 | 64989.48 | 0.50 |
March | 0.00 | 0.00 | 0.158503E+11 | 0.683492E+10 | 81831.23 | 22-MAR-18:51 | 65945.40 | 0.54 |
April | 0.00 | 0.00 | 0.232985E+11 | 0.113024E+11 | 89070.55 | 26-APR-21:51 | 66509.65 | 0.56 |
May | 0.00 | 0.00 | 0.274870E+11 | 0.145838E+11 | 86991.28 | 04-MAY-21:51 | 68976.69 | 0.55 |
June | 0.00 | 0.00 | 0.309735E+11 | 0.172939E+11 | 92204.57 | 28-JUN-21:51 | 67441.92 | 0.48 |
July | 0.00 | 0.00 | 0.370193E+11 | 0.213356E+11 | 93941.08 | 19-JUL-21:51 | 65976.27 | 0.49 |
August | 0.00 | 0.00 | 0.342596E+11 | 0.188249E+11 | 92936.58 | 16-AUG-21:51 | 66540.85 | 0.47 |
September | 0.00 | 0.00 | 0.272320E+11 | 0.140358E+11 | 92429.37 | 22-SEP-21:52 | 64588.19 | 0.46 |
October | 0.00 | 0.00 | 0.244003E+11 | 0.152848E+11 | 91980.68 | 01-OCT-08:51 | 62546.65 | 0.37 |
November | 0.00 | 0.00 | 0.145310E+11 | 0.720263E+10 | 84739.39 | 09-NOV-22:53 | 63237.43 | 0.45 |
December | 0.00 | 0.00 | 0.104317E+11 | 0.624003E+10 | 81079.44 | 19-DEC-19:01 | 81079.44 | 0.30 |
Annual Sum or Average | 0.00 | 0.00 | 0.269497E+12 | 0.144327E+12 | 0.46 | |||
Minimum of Months | 0.00 | 0.00 | 0.104317E+11 | 0.556612E+10 | 81079.44 | 62546.65 | 0.30 | |
Maximum of Months | 0.00 | 0.00 | 0.370193E+11 | 0.213356E+11 | 93941.08 | 81079.44 | 0.56 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.231069E+10 | 0.129191E+10 | 12491.48 | 15-JAN-16:01 | 12491.48 | 0.50 |
February | 0.00 | 0.00 | 0.182485E+10 | 0.102593E+10 | 12872.66 | 13-FEB-16:02 | 8682.85 | 0.43 |
March | 0.00 | 0.00 | 0.208244E+10 | 0.958866E+09 | 12345.24 | 15-MAR-15:01 | 10491.95 | 0.51 |
April | 0.00 | 0.00 | 0.380804E+10 | 0.182211E+10 | 12488.46 | 02-APR-08:62 | 12488.46 | 0.79 |
May | 0.00 | 0.00 | 0.338270E+10 | 0.153054E+10 | 12733.83 | 06-MAY-08:62 | 9832.25 | 0.77 |
June | 0.00 | 0.00 | 0.468018E+10 | 0.209351E+10 | 12843.80 | 28-JUN-08:62 | 9512.53 | 0.88 |
July | 0.00 | 0.00 | 0.698008E+10 | 0.335747E+10 | 12480.99 | 13-JUL-18:01 | 10388.35 | 0.95 |
August | 0.00 | 0.00 | 0.751455E+10 | 0.368507E+10 | 12774.71 | 08-AUG-08:62 | 9887.54 | 0.95 |
September | 0.00 | 0.00 | 0.542190E+10 | 0.251212E+10 | 13146.25 | 23-SEP-08:62 | 9223.99 | 0.91 |
October | 0.00 | 0.00 | 0.540079E+10 | 0.319977E+10 | 13245.24 | 01-OCT-08:61 | 9779.57 | 0.75 |
November | 0.00 | 0.00 | 0.272858E+10 | 0.153145E+10 | 13097.02 | 12-NOV-09:02 | 8606.59 | 0.58 |
December | 0.00 | 0.00 | 0.244847E+10 | 0.176044E+10 | 12492.10 | 31-DEC-09:01 | 12492.10 | 0.36 |
Annual Sum or Average | 0.00 | 0.00 | 0.485833E+11 | 0.247692E+11 | 0.70 | |||
Minimum of Months | 0.00 | 0.00 | 0.182485E+10 | 0.958866E+09 | 12345.24 | 8606.59 | 0.36 | |
Maximum of Months | 0.00 | 0.00 | 0.751455E+10 | 0.368507E+10 | 13245.24 | 12492.10 | 0.95 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.663480E+09 | 0.339008E+09 | 12316.20 | 20-JAN-19:01 | 9123.89 | 0.21 |
February | 0.00 | 0.00 | 0.691428E+09 | 0.350155E+09 | 12281.95 | 14-FEB-09:02 | 9745.09 | 0.23 |
March | 0.00 | 0.00 | 0.103991E+10 | 0.447134E+09 | 11948.53 | 22-MAR-18:51 | 9202.53 | 0.33 |
April | 0.00 | 0.00 | 0.236595E+10 | 0.109464E+10 | 12915.78 | 02-APR-08:51 | 12915.78 | 0.60 |
May | 0.00 | 0.00 | 0.244546E+10 | 0.109221E+10 | 13280.02 | 24-MAY-08:51 | 13280.02 | 0.60 |
June | 0.00 | 0.00 | 0.317484E+10 | 0.142490E+10 | 13827.31 | 30-JUN-08:51 | 11448.04 | 0.58 |
July | 0.00 | 0.00 | 0.466603E+10 | 0.228889E+10 | 14256.45 | 30-JUL-08:51 | 11079.71 | 0.58 |
August | 0.00 | 0.00 | 0.458466E+10 | 0.221183E+10 | 14441.91 | 18-AUG-08:51 | 11038.16 | 0.58 |
September | 0.00 | 0.00 | 0.289995E+10 | 0.128076E+10 | 14044.57 | 10-SEP-08:51 | 11294.25 | 0.58 |
October | 0.00 | 0.00 | 0.253603E+10 | 0.145230E+10 | 13924.00 | 17-OCT-08:21 | 13924.00 | 0.46 |
November | 0.00 | 0.00 | 0.902726E+09 | 0.435849E+09 | 12597.05 | 12-NOV-09:02 | 8175.06 | 0.30 |
December | 0.00 | 0.00 | 0.583149E+09 | 0.382934E+09 | 12691.91 | 05-DEC-09:41 | 12691.91 | 0.16 |
Annual Sum or Average | 0.00 | 0.00 | 0.265536E+11 | 0.128006E+11 | 0.43 | |||
Minimum of Months | 0.00 | 0.00 | 0.583149E+09 | 0.339008E+09 | 11948.53 | 8175.06 | 0.16 | |
Maximum of Months | 0.00 | 0.00 | 0.466603E+10 | 0.228889E+10 | 14441.91 | 13924.00 | 0.60 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.456990E+09 | 0.243220E+09 | 3869.35 | 21-JAN-09:02 | 2671.17 | 0.38 |
February | 0.00 | 0.00 | 0.414317E+09 | 0.230542E+09 | 3874.95 | 13-FEB-16:02 | 2622.05 | 0.33 |
March | 0.00 | 0.00 | 0.487631E+09 | 0.240857E+09 | 3704.74 | 24-MAR-08:61 | 2621.30 | 0.39 |
April | 0.00 | 0.00 | 0.100095E+10 | 0.513319E+09 | 3749.09 | 08-APR-08:61 | 2733.30 | 0.70 |
May | 0.00 | 0.00 | 0.919590E+09 | 0.443929E+09 | 3906.32 | 06-MAY-08:62 | 2437.47 | 0.68 |
June | 0.00 | 0.00 | 0.133862E+10 | 0.644247E+09 | 3839.35 | 28-JUN-08:62 | 2577.87 | 0.84 |
July | 0.00 | 0.00 | 0.191430E+10 | 0.957401E+09 | 3937.62 | 30-JUL-08:61 | 2777.41 | 0.93 |
August | 0.00 | 0.00 | 0.195070E+10 | 0.978414E+09 | 4077.06 | 06-AUG-08:61 | 2652.39 | 0.93 |
September | 0.00 | 0.00 | 0.147110E+10 | 0.715491E+09 | 3964.62 | 23-SEP-08:62 | 2444.97 | 0.89 |
October | 0.00 | 0.00 | 0.128912E+10 | 0.759074E+09 | 4008.58 | 01-OCT-08:61 | 2720.11 | 0.68 |
November | 0.00 | 0.00 | 0.601801E+09 | 0.319591E+09 | 3793.52 | 11-NOV-16:01 | 2666.73 | 0.46 |
December | 0.00 | 0.00 | 0.503022E+09 | 0.351616E+09 | 3663.19 | 08-DEC-16:01 | 2811.27 | 0.28 |
Annual Sum or Average | 0.00 | 0.00 | 0.123481E+11 | 0.639770E+10 | 0.63 | |||
Minimum of Months | 0.00 | 0.00 | 0.414317E+09 | 0.230542E+09 | 3663.19 | 2437.47 | 0.28 | |
Maximum of Months | 0.00 | 0.00 | 0.195070E+10 | 0.978414E+09 | 4077.06 | 2811.27 | 0.93 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 84301365.31 | 42469656.99 | 3603.71 | 21-JAN-09:02 | 2302.85 | 0.11 |
February | 0.00 | 0.00 | 0.123064E+09 | 56183407.41 | 3676.11 | 13-FEB-16:02 | 2437.93 | 0.17 |
March | 0.00 | 0.00 | 0.207399E+09 | 84172204.53 | 3635.98 | 22-MAR-18:51 | 2898.42 | 0.23 |
April | 0.00 | 0.00 | 0.571078E+09 | 0.237022E+09 | 3910.07 | 26-APR-21:51 | 2853.74 | 0.51 |
May | 0.00 | 0.00 | 0.634359E+09 | 0.271321E+09 | 3786.08 | 03-MAY-21:51 | 2946.89 | 0.55 |
June | 0.00 | 0.00 | 0.913856E+09 | 0.415953E+09 | 4050.07 | 28-JUN-21:51 | 2909.04 | 0.56 |
July | 0.00 | 0.00 | 0.133429E+10 | 0.682477E+09 | 4080.47 | 27-JUL-21:51 | 2883.15 | 0.57 |
August | 0.00 | 0.00 | 0.122716E+10 | 0.596903E+09 | 4047.79 | 16-AUG-21:51 | 2840.53 | 0.56 |
September | 0.00 | 0.00 | 0.809247E+09 | 0.338812E+09 | 3897.61 | 07-SEP-21:51 | 2633.55 | 0.57 |
October | 0.00 | 0.00 | 0.582619E+09 | 0.315290E+09 | 4009.82 | 01-OCT-08:51 | 2454.07 | 0.40 |
November | 0.00 | 0.00 | 0.142848E+09 | 61383988.53 | 3637.56 | 11-NOV-16:01 | 2433.21 | 0.21 |
December | 0.00 | 0.00 | 77968184.67 | 54217173.59 | 3562.77 | 09-DEC-16:01 | 2776.83 | 0.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.670819E+10 | 0.315620E+10 | 0.38 | |||
Minimum of Months | 0.00 | 0.00 | 77968184.67 | 42469656.99 | 3562.77 | 2302.85 | 0.07 | |
Maximum of Months | 0.00 | 0.00 | 0.133429E+10 | 0.682477E+09 | 4080.47 | 2946.89 | 0.57 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.764340E+10 | 0.536691E+10 | 17169.90 | 14-JAN-19:01 | 17169.90 | 0.65 |
February | 0.00 | 0.00 | 0.510830E+10 | 0.336316E+10 | 17984.72 | 13-FEB-16:02 | 12889.44 | 0.59 |
March | 0.00 | 0.00 | 0.447999E+10 | 0.236354E+10 | 17394.28 | 20-MAR-15:01 | 14164.57 | 0.61 |
April | 0.00 | 0.00 | 0.540427E+10 | 0.248549E+10 | 17237.19 | 22-APR-15:01 | 14298.99 | 0.78 |
May | 0.00 | 0.00 | 0.351121E+10 | 0.132494E+10 | 17475.51 | 06-MAY-08:62 | 13124.57 | 0.68 |
June | 0.00 | 0.00 | 0.465700E+10 | 0.169646E+10 | 17886.05 | 16-JUN-15:01 | 13454.68 | 0.80 |
July | 0.00 | 0.00 | 0.724628E+10 | 0.293536E+10 | 18601.18 | 30-JUL-08:61 | 13226.89 | 0.89 |
August | 0.00 | 0.00 | 0.904042E+10 | 0.399167E+10 | 18773.94 | 20-AUG-08:61 | 13096.50 | 0.91 |
September | 0.00 | 0.00 | 0.883538E+10 | 0.442872E+10 | 18246.26 | 22-SEP-08:61 | 13117.29 | 0.90 |
October | 0.00 | 0.00 | 0.101221E+11 | 0.681537E+10 | 18719.82 | 01-OCT-08:61 | 13135.47 | 0.76 |
November | 0.00 | 0.00 | 0.782689E+10 | 0.534141E+10 | 17751.56 | 11-NOV-16:01 | 13900.03 | 0.70 |
December | 0.00 | 0.00 | 0.817131E+10 | 0.651216E+10 | 17183.17 | 08-DEC-16:01 | 14338.52 | 0.50 |
Annual Sum or Average | 0.00 | 0.00 | 0.820465E+11 | 0.466252E+11 | 0.73 | |||
Minimum of Months | 0.00 | 0.00 | 0.351121E+10 | 0.132494E+10 | 17169.90 | 12889.44 | 0.50 | |
Maximum of Months | 0.00 | 0.00 | 0.101221E+11 | 0.681537E+10 | 18773.94 | 17169.90 | 0.91 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 38237.63 | 150697.24 | 08-JAN-07:00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 32548.50 | 111145.59 | 05-FEB-06:00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 40722.04 | 140963.49 | 30-MAR-03:00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 18250.22 | 104882.63 | 01-APR-05:00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15439.33 | 94183.95 | 27-MAY-03:00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 2934.71 | 63484.44 | 13-JUN-04:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 187.52 | 27554.62 | 06-JUL-01:00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 83.75 | 23836.50 | 28-AUG-08:54 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 1340.65 | 60773.87 | 20-SEP-03:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 6316.87 | 89873.17 | 28-OCT-05:00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 25522.07 | 102055.67 | 24-NOV-04:00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 37003.31 | 116502.45 | 23-DEC-06:00 |
Annual Sum or Average | 0.00 | 18165.73 | ||||
Minimum of Months | 0.00 | 0.00 | 83.75 | 23836.50 | ||
Maximum of Months | 0.00 | 0.00 | 40722.04 | 150697.24 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 47243.03 | 326643.74 | 14-JAN-16:01 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 35142.78 | 310180.32 | 01-FEB-09:51 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 32537.81 | 340012.91 | 23-MAR-15:03 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 61168.01 | 319966.15 | 11-APR-15:03 | 0.00 | 0.00 | 01-APR-00:10 |
May | 59551.69 | 308587.99 | 04-MAY-15:03 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 99208.11 | 375137.58 | 28-JUN-15:03 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 177009.90 | 528273.67 | 18-JUL-18:03 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 197358.11 | 537186.92 | 18-AUG-15:03 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 132759.61 | 500420.95 | 29-SEP-15:03 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 142648.37 | 507460.83 | 14-OCT-15:01 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 52280.52 | 384936.01 | 19-NOV-09:41 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 52378.99 | 362291.50 | 05-DEC-09:41 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 91279.59 | 0.00 | ||||
Minimum of Months | 32537.81 | 308587.99 | 0.00 | 0.00 | ||
Maximum of Months | 197358.11 | 537186.92 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 23120.51 | 48443.70 | 31-JAN-07:15 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 23150.48 | 48445.21 | 02-FEB-07:50 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 22919.27 | 48206.02 | 01-MAR-07:40 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22438.01 | 47336.42 | 03-APR-06:20 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 21878.40 | 46290.89 | 01-MAY-07:00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 21381.45 | 45108.45 | 01-JUN-06:20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21050.28 | 44195.19 | 03-JUL-06:50 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 21039.85 | 44108.96 | 31-AUG-06:20 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21284.59 | 44854.19 | 29-SEP-06:50 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 21748.39 | 46034.05 | 31-OCT-06:30 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 22311.73 | 47180.38 | 30-NOV-07:30 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 22812.07 | 48035.37 | 29-DEC-07:30 |
Annual Sum or Average | 0.00 | 22088.55 | ||||
Minimum of Months | 0.00 | 0.00 | 21039.85 | 44108.96 | ||
Maximum of Months | 0.00 | 0.00 | 23150.48 | 48445.21 |
Report: FanReportMonthly
For: FLR_3_DOAS FAN
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.271000E+10 | 0.71 | 1299.30 | 01-JAN-00:25 | 0.89 |
February | 0.244774E+10 | 0.70 | 1299.30 | 01-FEB-00:07 | 0.89 |
March | 0.271000E+10 | 0.70 | 1299.30 | 03-MAR-09:04 | 0.89 |
April | 0.262258E+10 | 0.70 | 1299.30 | 01-APR-01:10 | 0.89 |
May | 0.271000E+10 | 0.70 | 1299.30 | 01-MAY-00:30 | 0.88 |
June | 0.262258E+10 | 0.70 | 1299.30 | 01-JUN-01:05 | 0.89 |
July | 0.271000E+10 | 0.70 | 1299.30 | 01-JUL-00:50 | 0.88 |
August | 0.271000E+10 | 0.70 | 1299.30 | 01-AUG-00:50 | 0.89 |
September | 0.262258E+10 | 0.70 | 1299.30 | 29-SEP-16:00 | 0.89 |
October | 0.271000E+10 | 0.70 | 1299.30 | 13-OCT-15:09 | 0.89 |
November | 0.262258E+10 | 0.70 | 1299.30 | 01-NOV-00:10 | 0.89 |
December | 0.271000E+10 | 0.71 | 1299.30 | 01-DEC-00:30 | 0.89 |
Annual Sum or Average | 0.319080E+11 | 0.70 | |||
Minimum of Months | 0.244774E+10 | 0.70 | 1299.30 | 0.88 | |
Maximum of Months | 0.271000E+10 | 0.71 | 1299.30 | 0.89 |
Report: FanReportMonthly
For: VAV WITH REHEAT FAN
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.354911E+11 | 0.86 | 23882.68 | 18-JAN-22:10 | 1.21 |
February | 0.325105E+11 | 0.86 | 23151.48 | 01-FEB-22:10 | 1.19 |
March | 0.356248E+11 | 0.86 | 23067.16 | 24-MAR-21:10 | 1.18 |
April | 0.356106E+11 | 0.87 | 23563.97 | 26-APR-21:10 | 1.19 |
May | 0.370521E+11 | 0.87 | 24315.44 | 04-MAY-21:10 | 1.22 |
June | 0.365613E+11 | 0.88 | 24028.79 | 28-JUN-21:10 | 1.21 |
July | 0.381737E+11 | 0.88 | 24762.98 | 31-JUL-21:10 | 1.23 |
August | 0.384129E+11 | 0.89 | 25171.80 | 18-AUG-21:10 | 1.24 |
September | 0.367056E+11 | 0.88 | 27199.75 | 29-SEP-21:20 | 1.32 |
October | 0.384540E+11 | 0.89 | 28258.03 | 16-OCT-21:10 | 1.35 |
November | 0.355170E+11 | 0.87 | 24568.31 | 28-NOV-22:10 | 1.24 |
December | 0.359194E+11 | 0.86 | 25677.96 | 05-DEC-22:10 | 1.27 |
Annual Sum or Average | 0.436033E+12 | 0.87 | |||
Minimum of Months | 0.325105E+11 | 0.86 | 23067.16 | 1.18 | |
Maximum of Months | 0.384540E+11 | 0.89 | 28258.03 | 1.35 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205205E+09 | 0.27 | 76.61 | 01-JAN-00:10 | 0.27 |
February | 0.185347E+09 | 0.27 | 76.61 | 01-FEB-00:03 | 0.27 |
March | 0.205205E+09 | 0.27 | 76.61 | 01-MAR-00:03 | 0.27 |
April | 0.198586E+09 | 0.27 | 76.61 | 01-APR-00:10 | 0.27 |
May | 0.205205E+09 | 0.27 | 76.61 | 01-MAY-00:05 | 0.27 |
June | 0.198586E+09 | 0.27 | 76.61 | 01-JUN-00:05 | 0.27 |
July | 0.205205E+09 | 0.27 | 76.61 | 01-JUL-00:10 | 0.27 |
August | 0.205205E+09 | 0.27 | 76.61 | 01-AUG-00:05 | 0.27 |
September | 0.198586E+09 | 0.27 | 76.61 | 01-SEP-00:05 | 0.27 |
October | 0.205205E+09 | 0.27 | 76.61 | 01-OCT-00:10 | 0.27 |
November | 0.198586E+09 | 0.27 | 76.61 | 01-NOV-00:05 | 0.27 |
December | 0.205205E+09 | 0.27 | 76.61 | 01-DEC-00:03 | 0.27 |
Annual Sum or Average | 0.241613E+10 | 0.27 | |||
Minimum of Months | 0.185347E+09 | 0.27 | 76.61 | 0.27 | |
Maximum of Months | 0.205205E+09 | 0.27 | 76.61 | 0.27 |
Report: FanReportMonthly
For: LOBBY_FLR_1 EXHAUST FAN
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:10 | -0.0 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | -0.0 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | -0.0 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | -0.0 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 EXHAUST FAN
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 EXHAUST FAN
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116283E+10 | 0.19 | 612.92 | 01-JAN-07:03 | 0.27 |
February | 0.105030E+10 | 0.19 | 612.92 | 01-FEB-07:05 | 0.27 |
March | 0.116283E+10 | 0.19 | 612.92 | 01-MAR-07:03 | 0.27 |
April | 0.112532E+10 | 0.19 | 612.92 | 01-APR-06:10 | 0.27 |
May | 0.116283E+10 | 0.19 | 612.92 | 01-MAY-06:05 | 0.27 |
June | 0.112532E+10 | 0.19 | 612.92 | 01-JUN-06:05 | 0.27 |
July | 0.116283E+10 | 0.19 | 612.92 | 01-JUL-06:05 | 0.27 |
August | 0.116283E+10 | 0.19 | 612.92 | 01-AUG-06:05 | 0.27 |
September | 0.112532E+10 | 0.19 | 612.92 | 01-SEP-06:05 | 0.27 |
October | 0.116283E+10 | 0.19 | 612.92 | 01-OCT-06:10 | 0.27 |
November | 0.112532E+10 | 0.19 | 612.92 | 01-NOV-06:05 | 0.27 |
December | 0.116283E+10 | 0.19 | 612.92 | 01-DEC-07:05 | 0.27 |
Annual Sum or Average | 0.136914E+11 | 0.19 | |||
Minimum of Months | 0.105030E+10 | 0.19 | 612.92 | 0.27 | |
Maximum of Months | 0.116283E+10 | 0.19 | 612.92 | 0.27 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.157367E+09 | 0.50 | 688.20 | 01-JAN-09:01 | 0.58 |
February | 0.131806E+09 | 0.48 | 688.20 | 01-FEB-09:01 | 0.59 |
March | 0.156304E+09 | 0.47 | 688.20 | 01-MAR-09:01 | 0.58 |
April | 0.197497E+09 | 0.50 | 688.20 | 01-APR-15:01 | 0.58 |
May | 0.184748E+09 | 0.48 | 688.20 | 01-MAY-08:62 | 0.58 |
June | 0.235303E+09 | 0.50 | 688.20 | 01-JUN-15:01 | 0.58 |
July | 0.315738E+09 | 0.53 | 688.20 | 01-JUL-08:61 | 0.58 |
August | 0.322017E+09 | 0.54 | 688.20 | 01-AUG-08:62 | 0.58 |
September | 0.264765E+09 | 0.53 | 688.20 | 01-SEP-08:62 | 0.58 |
October | 0.260161E+09 | 0.52 | 688.20 | 01-OCT-08:61 | 0.58 |
November | 0.154458E+09 | 0.50 | 688.20 | 01-NOV-08:62 | 0.58 |
December | 0.161036E+09 | 0.50 | 688.20 | 01-DEC-09:01 | 0.58 |
Annual Sum or Average | 0.254120E+10 | 0.50 | |||
Minimum of Months | 0.131806E+09 | 0.47 | 688.20 | 0.58 | |
Maximum of Months | 0.322017E+09 | 0.54 | 688.20 | 0.59 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.119796E+09 | 0.39 | 662.57 | 02-JAN-16:02 | 0.58 |
February | 93998958.23 | 0.41 | 662.57 | 01-FEB-09:51 | 0.59 |
March | 0.118240E+09 | 0.41 | 662.57 | 01-MAR-16:01 | 0.58 |
April | 0.117755E+09 | 0.39 | 662.57 | 01-APR-15:01 | 0.58 |
May | 0.125304E+09 | 0.37 | 662.57 | 01-MAY-08:51 | 0.58 |
June | 0.142668E+09 | 0.33 | 662.57 | 01-JUN-08:51 | 0.58 |
July | 0.194589E+09 | 0.33 | 662.57 | 01-JUL-08:51 | 0.58 |
August | 0.182375E+09 | 0.32 | 662.57 | 01-AUG-08:51 | 0.58 |
September | 0.140983E+09 | 0.33 | 662.57 | 01-SEP-08:51 | 0.58 |
October | 0.127855E+09 | 0.33 | 662.57 | 01-OCT-08:51 | 0.58 |
November | 86019252.55 | 0.39 | 662.57 | 01-NOV-08:62 | 0.58 |
December | 0.108815E+09 | 0.39 | 662.57 | 02-DEC-16:01 | 0.58 |
Annual Sum or Average | 0.155840E+10 | 0.37 | |||
Minimum of Months | 86019252.55 | 0.32 | 662.57 | 0.58 | |
Maximum of Months | 0.194589E+09 | 0.41 | 662.57 | 0.59 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.123996E+10 | 0.46 | 2095.97 | 14-JAN-12:40 | 0.58 |
February | 0.805500E+09 | 0.39 | 1274.49 | 02-FEB-12:30 | 0.58 |
March | 0.630567E+09 | 0.34 | 1103.63 | 11-MAR-13:00 | 0.58 |
April | 0.716345E+09 | 0.43 | 805.27 | 08-APR-12:40 | 0.58 |
May | 0.474029E+09 | 0.38 | 700.38 | 03-MAY-15:03 | 0.58 |
June | 0.588571E+09 | 0.45 | 626.72 | 30-JUN-15:06 | 0.58 |
July | 0.849672E+09 | 0.54 | 729.38 | 19-JUL-15:03 | 0.58 |
August | 0.109037E+10 | 0.58 | 768.91 | 30-AUG-13:00 | 0.58 |
September | 0.119300E+10 | 0.57 | 1331.97 | 30-SEP-13:10 | 0.58 |
October | 0.154127E+10 | 0.55 | 2410.51 | 16-OCT-12:20 | 0.59 |
November | 0.124937E+10 | 0.49 | 2164.86 | 19-NOV-09:53 | 0.58 |
December | 0.136105E+10 | 0.48 | 2059.44 | 16-DEC-13:00 | 0.58 |
Annual Sum or Average | 0.117397E+11 | 0.47 | |||
Minimum of Months | 0.474029E+09 | 0.34 | 626.72 | 0.58 | |
Maximum of Months | 0.154127E+10 | 0.58 | 2410.51 | 0.59 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.767017E+09 | 0.37 | 4036.31 | 01-JAN-09:01 | 0.58 |
February | 0.702272E+09 | 0.38 | 4036.31 | 01-FEB-09:51 | 0.59 |
March | 0.911741E+09 | 0.39 | 4036.31 | 01-MAR-09:01 | 0.59 |
April | 0.987070E+09 | 0.34 | 4036.31 | 01-APR-08:62 | 0.59 |
May | 0.116607E+10 | 0.32 | 4036.31 | 01-MAY-08:51 | 0.58 |
June | 0.123005E+10 | 0.28 | 4036.31 | 01-JUN-08:51 | 0.58 |
July | 0.146114E+10 | 0.28 | 4036.31 | 01-JUL-08:51 | 0.58 |
August | 0.131773E+10 | 0.27 | 4036.31 | 01-AUG-08:51 | 0.58 |
September | 0.106801E+10 | 0.27 | 4036.31 | 01-SEP-08:51 | 0.58 |
October | 0.105962E+10 | 0.28 | 4036.31 | 01-OCT-08:51 | 0.58 |
November | 0.746771E+09 | 0.35 | 4036.31 | 01-NOV-08:62 | 0.58 |
December | 0.700719E+09 | 0.36 | 4036.31 | 01-DEC-09:01 | 0.58 |
Annual Sum or Average | 0.121182E+11 | 0.33 | |||
Minimum of Months | 0.700719E+09 | 0.27 | 4036.31 | 0.58 | |
Maximum of Months | 0.146114E+10 | 0.39 | 4036.31 | 0.59 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.157228E+09 | 0.50 | 611.57 | 01-JAN-09:01 | 0.58 |
February | 0.128913E+09 | 0.49 | 611.57 | 01-FEB-09:01 | 0.59 |
March | 0.152095E+09 | 0.47 | 611.57 | 01-MAR-09:01 | 0.58 |
April | 0.178079E+09 | 0.52 | 611.57 | 01-APR-08:62 | 0.58 |
May | 0.159367E+09 | 0.50 | 611.57 | 01-MAY-08:62 | 0.58 |
June | 0.195949E+09 | 0.52 | 611.57 | 01-JUN-08:62 | 0.58 |
July | 0.280984E+09 | 0.55 | 611.57 | 01-JUL-08:61 | 0.58 |
August | 0.301025E+09 | 0.56 | 611.57 | 01-AUG-08:62 | 0.58 |
September | 0.226944E+09 | 0.53 | 611.57 | 01-SEP-08:62 | 0.58 |
October | 0.244537E+09 | 0.53 | 611.57 | 01-OCT-08:61 | 0.58 |
November | 0.149789E+09 | 0.51 | 611.57 | 01-NOV-08:62 | 0.58 |
December | 0.160334E+09 | 0.51 | 611.57 | 01-DEC-09:01 | 0.58 |
Annual Sum or Average | 0.233524E+10 | 0.52 | |||
Minimum of Months | 0.128913E+09 | 0.47 | 611.57 | 0.58 | |
Maximum of Months | 0.301025E+09 | 0.56 | 611.57 | 0.59 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.112333E+09 | 0.38 | 588.81 | 01-JAN-09:01 | 0.58 |
February | 94591220.97 | 0.39 | 588.81 | 01-FEB-09:51 | 0.59 |
March | 0.118114E+09 | 0.41 | 588.81 | 01-MAR-09:01 | 0.58 |
April | 0.117349E+09 | 0.41 | 588.81 | 01-APR-08:62 | 0.58 |
May | 0.117608E+09 | 0.39 | 588.81 | 01-MAY-08:51 | 0.58 |
June | 0.134744E+09 | 0.34 | 588.81 | 01-JUN-08:51 | 0.58 |
July | 0.191674E+09 | 0.34 | 588.81 | 01-JUL-08:51 | 0.58 |
August | 0.187340E+09 | 0.34 | 588.81 | 01-AUG-08:51 | 0.58 |
September | 0.124025E+09 | 0.34 | 588.81 | 01-SEP-08:51 | 0.58 |
October | 0.120529E+09 | 0.34 | 588.81 | 01-OCT-08:51 | 0.58 |
November | 84711182.77 | 0.36 | 588.81 | 01-NOV-08:62 | 0.58 |
December | 0.103174E+09 | 0.37 | 588.81 | 01-DEC-09:01 | 0.58 |
Annual Sum or Average | 0.150619E+10 | 0.37 | |||
Minimum of Months | 84711182.77 | 0.34 | 588.81 | 0.58 | |
Maximum of Months | 0.191674E+09 | 0.41 | 588.81 | 0.59 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 44486950.34 | 0.49 | 178.24 | 02-JAN-16:02 | 0.58 |
February | 38827315.87 | 0.47 | 178.24 | 01-FEB-09:01 | 0.59 |
March | 46202384.33 | 0.47 | 178.24 | 01-MAR-16:01 | 0.58 |
April | 51150076.53 | 0.51 | 178.24 | 01-APR-15:01 | 0.58 |
May | 47375271.30 | 0.49 | 178.24 | 01-MAY-08:62 | 0.58 |
June | 58719081.51 | 0.51 | 178.24 | 01-JUN-15:01 | 0.58 |
July | 80241158.11 | 0.54 | 178.24 | 01-JUL-08:61 | 0.58 |
August | 80875189.07 | 0.54 | 178.24 | 01-AUG-08:62 | 0.58 |
September | 63671529.67 | 0.53 | 178.24 | 01-SEP-08:62 | 0.58 |
October | 62686433.81 | 0.52 | 178.24 | 01-OCT-08:61 | 0.58 |
November | 40117295.74 | 0.50 | 178.24 | 01-NOV-08:62 | 0.58 |
December | 45009934.83 | 0.50 | 178.24 | 01-DEC-09:01 | 0.58 |
Annual Sum or Average | 0.659363E+09 | 0.51 | |||
Minimum of Months | 38827315.87 | 0.47 | 178.24 | 0.58 | |
Maximum of Months | 80875189.07 | 0.54 | 178.24 | 0.59 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 40564904.41 | 0.39 | 171.21 | 01-JAN-09:01 | 0.58 |
February | 31829624.81 | 0.40 | 171.21 | 01-FEB-16:01 | 0.58 |
March | 37846120.39 | 0.41 | 171.21 | 01-MAR-09:01 | 0.58 |
April | 30605738.81 | 0.40 | 171.21 | 01-APR-15:01 | 0.58 |
May | 31621217.57 | 0.38 | 171.21 | 01-MAY-08:51 | 0.58 |
June | 37252952.27 | 0.34 | 171.21 | 01-JUN-08:51 | 0.58 |
July | 52717335.77 | 0.33 | 171.21 | 01-JUL-08:51 | 0.58 |
August | 48124078.03 | 0.33 | 171.21 | 01-AUG-08:51 | 0.58 |
September | 33702582.18 | 0.34 | 171.21 | 01-SEP-08:51 | 0.58 |
October | 30775022.75 | 0.33 | 171.21 | 01-OCT-08:51 | 0.58 |
November | 27838184.78 | 0.39 | 171.21 | 01-NOV-15:01 | 0.58 |
December | 37513178.63 | 0.39 | 171.21 | 02-DEC-16:01 | 0.58 |
Annual Sum or Average | 0.440391E+09 | 0.37 | |||
Minimum of Months | 27838184.78 | 0.33 | 171.21 | 0.58 | |
Maximum of Months | 52717335.77 | 0.41 | 171.21 | 0.58 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.379537E+09 | 0.53 | 836.92 | 01-JAN-09:01 | 0.58 |
February | 0.259405E+09 | 0.51 | 836.92 | 01-FEB-09:01 | 0.59 |
March | 0.251597E+09 | 0.49 | 836.92 | 01-MAR-09:01 | 0.58 |
April | 0.241354E+09 | 0.51 | 836.92 | 01-APR-08:62 | 0.58 |
May | 0.174270E+09 | 0.47 | 836.92 | 01-MAY-08:62 | 0.58 |
June | 0.194573E+09 | 0.48 | 836.92 | 01-JUN-15:01 | 0.58 |
July | 0.280730E+09 | 0.52 | 836.92 | 01-JUL-08:61 | 0.58 |
August | 0.347418E+09 | 0.53 | 836.92 | 01-AUG-08:62 | 0.58 |
September | 0.355463E+09 | 0.52 | 836.92 | 01-SEP-08:62 | 0.58 |
October | 0.457036E+09 | 0.53 | 836.92 | 01-OCT-08:61 | 0.58 |
November | 0.359820E+09 | 0.54 | 836.92 | 01-NOV-08:62 | 0.58 |
December | 0.403704E+09 | 0.54 | 836.92 | 01-DEC-09:01 | 0.58 |
Annual Sum or Average | 0.370491E+10 | 0.51 | |||
Minimum of Months | 0.174270E+09 | 0.47 | 836.92 | 0.58 | |
Maximum of Months | 0.457036E+09 | 0.54 | 836.92 | 0.59 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.576838E+09 | 0.519154E+09 | 570.24 | 08-JAN-06:50 | 513.22 | 513.22 | 36.11 | 1.50 |
February | 0.475672E+09 | 0.428105E+09 | 541.31 | 04-FEB-05:55 | 487.18 | 487.18 | 38.06 | 1.20 |
March | 0.628164E+09 | 0.565347E+09 | 567.76 | 30-MAR-03:00 | 510.98 | 510.98 | 37.14 | 1.47 |
April | 0.294213E+09 | 0.264791E+09 | 535.96 | 01-APR-05:00 | 482.36 | 482.36 | 38.27 | 1.15 |
May | 0.255315E+09 | 0.229783E+09 | 517.89 | 14-MAY-04:50 | 466.10 | 466.10 | 38.15 | 1.03 |
June | 48179997.96 | 43361998.16 | 393.12 | 13-JUN-04:00 | 353.81 | 353.81 | 33.88 | 0.58 |
July | 3335232.25 | 3001709.02 | 172.49 | 06-JUL-03:00 | 155.24 | 155.24 | 27.07 | 0.20 |
August | 1623737.07 | 1461363.36 | 157.21 | 22-AUG-08:54 | 141.49 | 141.49 | 40.21 | 0.18 |
September | 22254348.78 | 20028913.90 | 378.90 | 20-SEP-04:00 | 341.01 | 341.01 | 33.48 | 0.55 |
October | 0.105576E+09 | 95018573.75 | 510.04 | 12-OCT-05:00 | 459.04 | 459.04 | 38.26 | 0.99 |
November | 0.398354E+09 | 0.358519E+09 | 531.55 | 24-NOV-04:00 | 478.39 | 478.39 | 38.23 | 1.12 |
December | 0.571813E+09 | 0.514632E+09 | 547.49 | 23-DEC-06:00 | 492.74 | 492.74 | 37.78 | 1.25 |
Annual Sum or Average | 0.338134E+10 | 0.304320E+10 | ||||||
Minimum of Months | 1623737.07 | 1461363.36 | 157.21 | 141.49 | 141.49 | 27.07 | 0.18 | |
Maximum of Months | 0.628164E+09 | 0.565347E+09 | 570.24 | 513.22 | 513.22 | 40.21 | 1.50 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 83356837.53 | 75021153.78 | 549.19 | 24-JAN-09:51 | 494.27 | 494.27 | 6.72 | 9.60 |
February | 47355015.35 | 42619513.81 | 297.48 | 01-FEB-09:51 | 267.74 | 267.74 | 6.72 | 7.33 |
March | 49398075.20 | 44458267.68 | 450.19 | 23-MAR-15:03 | 405.17 | 405.17 | 6.72 | 8.81 |
April | 0.102815E+09 | 92533183.51 | 441.55 | 13-APR-08:51 | 397.40 | 397.40 | 6.72 | 8.73 |
May | 96713677.13 | 87042309.42 | 440.30 | 18-MAY-15:03 | 396.27 | 396.27 | 6.72 | 8.72 |
June | 0.169811E+09 | 0.152830E+09 | 559.36 | 29-JUN-18:03 | 503.43 | 503.43 | 6.72 | 9.68 |
July | 0.431642E+09 | 0.388478E+09 | 1164.43 | 18-JUL-18:03 | 1047.99 | 1047.99 | 6.72 | 13.18 |
August | 0.504794E+09 | 0.454315E+09 | 1048.09 | 18-AUG-15:13 | 943.28 | 943.28 | 6.72 | 12.62 |
September | 0.298900E+09 | 0.269010E+09 | 1993.50 | 29-SEP-15:13 | 1794.15 | 1794.15 | 6.72 | 16.40 |
October | 0.342429E+09 | 0.308186E+09 | 1387.17 | 17-OCT-10:50 | 1248.45 | 1248.45 | 6.72 | 14.16 |
November | 89615711.31 | 80654140.18 | 803.48 | 19-NOV-11:00 | 723.13 | 723.13 | 6.72 | 11.29 |
December | 81349562.58 | 73214606.33 | 444.95 | 16-DEC-16:01 | 400.45 | 400.45 | 6.72 | 8.76 |
Annual Sum or Average | 0.229818E+10 | 0.206836E+10 | ||||||
Minimum of Months | 47355015.35 | 42619513.81 | 297.48 | 267.74 | 267.74 | 6.72 | 7.33 | |
Maximum of Months | 0.504794E+09 | 0.454315E+09 | 1993.50 | 1794.15 | 1794.15 | 6.72 | 16.40 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.541088E+10 | 0.486979E+10 | 2259.10 | 01-JAN-00:10 | 2033.19 | 2033.19 | 6.72 | 19.98 |
February | 0.505677E+10 | 0.455109E+10 | 2259.10 | 01-FEB-00:03 | 2033.19 | 2033.19 | 6.84 | 19.98 |
March | 0.528042E+10 | 0.475238E+10 | 2259.10 | 01-MAR-06:13 | 2033.19 | 2033.19 | 6.72 | 19.98 |
April | 0.578973E+10 | 0.521076E+10 | 2259.10 | 01-APR-00:20 | 2033.19 | 2033.19 | 6.72 | 19.98 |
May | 0.604067E+10 | 0.543661E+10 | 2259.10 | 01-MAY-00:05 | 2033.19 | 2033.19 | 7.27 | 19.98 |
June | 0.585559E+10 | 0.527003E+10 | 2259.10 | 01-JUN-00:05 | 2033.19 | 2033.19 | 6.96 | 19.98 |
July | 0.605077E+10 | 0.544569E+10 | 2259.10 | 01-JUL-00:10 | 2033.19 | 2033.19 | 8.02 | 19.98 |
August | 0.605077E+10 | 0.544569E+10 | 2259.10 | 01-AUG-00:05 | 2033.19 | 2033.19 | 8.86 | 19.98 |
September | 0.585559E+10 | 0.527003E+10 | 2259.10 | 01-SEP-00:05 | 2033.19 | 2033.19 | 7.52 | 19.98 |
October | 0.605077E+10 | 0.544569E+10 | 2259.10 | 01-OCT-00:10 | 2033.19 | 2033.19 | 9.01 | 19.98 |
November | 0.567723E+10 | 0.510951E+10 | 2259.10 | 01-NOV-00:05 | 2033.19 | 2033.19 | 7.15 | 19.98 |
December | 0.557184E+10 | 0.501466E+10 | 2259.10 | 01-DEC-00:03 | 2033.19 | 2033.19 | 6.89 | 19.98 |
Annual Sum or Average | 0.686910E+11 | 0.618219E+11 | ||||||
Minimum of Months | 0.505677E+10 | 0.455109E+10 | 2259.10 | 2033.19 | 2033.19 | 6.72 | 19.98 | |
Maximum of Months | 0.605077E+10 | 0.544569E+10 | 2259.10 | 2033.19 | 2033.19 | 9.01 | 19.98 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:10 | 14.37 | 14.37 | 50.47 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:03 | 14.37 | 14.37 | 50.90 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:03 | 14.37 | 14.37 | 50.95 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 53.59 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:05 | 14.37 | 14.37 | 53.53 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:05 | 14.37 | 14.37 | 53.70 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 54.02 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:05 | 14.37 | 14.37 | 53.88 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:05 | 14.37 | 14.37 | 53.84 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:10 | 14.37 | 14.37 | 53.19 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:05 | 14.37 | 14.37 | 53.57 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:03 | 14.37 | 14.37 | 51.14 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 50.47 | 0.37 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 54.02 | 0.37 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 38.33 | 60.00 | 38237.63 | 150697.24 | 08-JAN-07:00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 28.31 | 60.00 | 32548.50 | 111145.59 | 05-FEB-06:00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 37.96 | 60.00 | 40722.04 | 140963.49 | 30-MAR-03:00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 37.83 | 60.00 | 18250.22 | 104882.63 | 01-APR-05:00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.04 | 30.04 | 15439.33 | 94183.95 | 27-MAY-03:00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 26.89 | 60.00 | 2934.71 | 63484.44 | 13-JUN-04:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.02 | 26.02 | 187.52 | 27554.62 | 06-JUL-01:00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 36.84 | 36.84 | 83.75 | 23836.50 | 28-AUG-08:54 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 27.45 | 27.45 | 1340.65 | 60773.87 | 20-SEP-03:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 38.68 | 38.68 | 6316.87 | 89873.17 | 28-OCT-05:00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 28.96 | 28.96 | 25522.07 | 102055.67 | 24-NOV-04:00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 34.23 | 60.00 | 37003.31 | 116502.45 | 23-DEC-06:00 |
Annual Sum or Average | 0.00 | 18165.73 | ||||||
Minimum of Months | 0.00 | 0.00 | 26.02 | 26.02 | 83.75 | 23836.50 | ||
Maximum of Months | 0.00 | 0.00 | 38.68 | 60.00 | 40722.04 | 150697.24 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 47243.03 | 326643.74 | 14-JAN-16:01 | 10.60 | 6.70 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 35142.78 | 310180.32 | 01-FEB-09:51 | 10.40 | 6.70 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 32537.81 | 340012.91 | 23-MAR-15:03 | 10.76 | 6.70 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 61168.01 | 319966.15 | 11-APR-15:03 | 10.52 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 59551.69 | 308587.99 | 04-MAY-15:03 | 10.39 | 6.70 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 99208.11 | 375137.58 | 28-JUN-15:03 | 11.18 | 6.70 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 177009.90 | 528273.67 | 18-JUL-18:03 | 13.01 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 197358.11 | 537186.92 | 18-AUG-15:03 | 13.12 | 6.70 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 132759.61 | 500420.95 | 29-SEP-15:03 | 12.68 | 6.70 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 142648.37 | 507460.83 | 14-OCT-15:01 | 12.76 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 52280.52 | 384936.01 | 19-NOV-09:41 | 11.30 | 6.70 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 52378.99 | 362291.50 | 05-DEC-09:41 | 11.03 | 6.70 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 91279.59 | 0.00 | ||||||
Minimum of Months | 32537.81 | 308587.99 | 10.39 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 197358.11 | 537186.92 | 13.12 | 6.70 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 50.47 | 60.05 | 23120.51 | 48443.70 | 31-JAN-07:15 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 50.90 | 60.05 | 23150.48 | 48445.21 | 02-FEB-07:50 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 50.95 | 60.05 | 22919.27 | 48206.02 | 01-MAR-07:40 |
April | 0.00 | 0.00 | 01-APR-00:10 | 53.59 | 60.05 | 22438.01 | 47336.42 | 03-APR-06:20 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 53.53 | 60.05 | 21878.40 | 46290.89 | 01-MAY-07:00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 53.70 | 60.05 | 21381.45 | 45108.45 | 01-JUN-06:20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 54.02 | 60.05 | 21050.28 | 44195.19 | 03-JUL-06:50 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 53.88 | 60.05 | 21039.85 | 44108.96 | 31-AUG-06:20 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 53.84 | 60.05 | 21284.59 | 44854.19 | 29-SEP-06:50 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 53.19 | 60.05 | 21748.39 | 46034.05 | 31-OCT-06:30 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 53.57 | 60.05 | 22311.73 | 47180.38 | 30-NOV-07:30 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 51.14 | 60.05 | 22812.07 | 48035.37 | 29-DEC-07:30 |
Annual Sum or Average | 0.00 | 22088.55 | ||||||
Minimum of Months | 0.00 | 0.00 | 50.47 | 60.05 | 21039.85 | 44108.96 | ||
Maximum of Months | 0.00 | 0.00 | 54.02 | 60.05 | 23150.48 | 48445.21 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.796627E+10 | 0.00 | 0.352394E+10 | 0.271000E+10 | 0.00 | 0.00 |
February | 0.641498E+10 | 0.00 | 0.189616E+10 | 0.244774E+10 | 0.00 | 0.00 |
March | 0.857742E+10 | 0.00 | 0.213914E+10 | 0.271000E+10 | 0.00 | 0.00 |
April | 0.405566E+10 | 0.00 | 0.536108E+10 | 0.262258E+10 | 0.00 | 0.00 |
May | 0.360689E+10 | 0.00 | 0.568444E+10 | 0.271000E+10 | 0.00 | 0.00 |
June | 0.639403E+09 | 0.00 | 0.127679E+11 | 0.262258E+10 | 0.00 | 0.00 |
July | 37027035.96 | 0.00 | 0.285718E+11 | 0.271000E+10 | 0.00 | 0.00 |
August | 17469671.82 | 0.00 | 0.326065E+11 | 0.271000E+10 | 0.00 | 0.00 |
September | 0.319034E+09 | 0.00 | 0.185738E+11 | 0.262258E+10 | 0.00 | 0.00 |
October | 0.143387E+10 | 0.00 | 0.206208E+11 | 0.271000E+10 | 0.00 | 0.00 |
November | 0.564075E+10 | 0.00 | 0.354751E+10 | 0.262258E+10 | 0.00 | 0.00 |
December | 0.800628E+10 | 0.00 | 0.428641E+10 | 0.271000E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.467151E+11 | 0.00 | 0.139579E+12 | 0.319080E+11 | 0.00 | 0.00 |
Minimum of Months | 17469671.82 | 0.00 | 0.189616E+10 | 0.244774E+10 | 0.00 | 0.00 |
Maximum of Months | 0.857742E+10 | 0.00 | 0.326065E+11 | 0.271000E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.902641E+11 | 0.00 | 0.580356E+11 | 0.354911E+11 | 0.00 | 0.00 |
February | 0.704084E+11 | 0.00 | 0.325376E+11 | 0.325105E+11 | 0.00 | 0.00 |
March | 0.970608E+11 | 0.00 | 0.360422E+11 | 0.356248E+11 | 0.00 | 0.00 |
April | 0.429903E+11 | 0.00 | 0.856442E+11 | 0.356106E+11 | 0.00 | 0.00 |
May | 0.375501E+11 | 0.00 | 0.916843E+11 | 0.370521E+11 | 0.00 | 0.00 |
June | 0.693222E+10 | 0.00 | 0.168981E+12 | 0.365613E+11 | 0.00 | 0.00 |
July | 0.425797E+09 | 0.00 | 0.344845E+12 | 0.381737E+11 | 0.00 | 0.00 |
August | 0.182770E+09 | 0.00 | 0.388248E+12 | 0.384129E+11 | 0.00 | 0.00 |
September | 0.308041E+10 | 0.00 | 0.229551E+12 | 0.367056E+11 | 0.00 | 0.00 |
October | 0.153994E+11 | 0.00 | 0.260147E+12 | 0.384540E+11 | 0.00 | 0.00 |
November | 0.595409E+11 | 0.00 | 0.605792E+11 | 0.355170E+11 | 0.00 | 0.00 |
December | 0.882108E+11 | 0.00 | 0.668534E+11 | 0.359194E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.512046E+12 | 0.00 | 0.182315E+13 | 0.436033E+12 | 0.00 | 0.00 |
Minimum of Months | 0.182770E+09 | 0.00 | 0.325376E+11 | 0.325105E+11 | 0.00 | 0.00 |
Maximum of Months | 0.970608E+11 | 0.00 | 0.388248E+12 | 0.384540E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.271000E+10 | 0.352394E+10 | 0.796627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244774E+10 | 0.189616E+10 | 0.641498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.271000E+10 | 0.213914E+10 | 0.857742E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.262258E+10 | 0.536108E+10 | 0.405566E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.271000E+10 | 0.568444E+10 | 0.360689E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.262258E+10 | 0.127679E+11 | 0.639403E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.271000E+10 | 0.285718E+11 | 37027035.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.271000E+10 | 0.326065E+11 | 17469671.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.262258E+10 | 0.185738E+11 | 0.319034E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.271000E+10 | 0.206208E+11 | 0.143387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.262258E+10 | 0.354751E+10 | 0.564075E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.271000E+10 | 0.428641E+10 | 0.800628E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319080E+11 | 0.139579E+12 | 0.467151E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244774E+10 | 0.189616E+10 | 17469671.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.271000E+10 | 0.326065E+11 | 0.857742E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.354911E+11 | 0.580356E+11 | 0.902641E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.325105E+11 | 0.325376E+11 | 0.704084E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.356248E+11 | 0.360422E+11 | 0.970608E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.356106E+11 | 0.856442E+11 | 0.429903E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.370521E+11 | 0.916843E+11 | 0.375501E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.365613E+11 | 0.168981E+12 | 0.693222E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.381737E+11 | 0.344845E+12 | 0.425797E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.384129E+11 | 0.388248E+12 | 0.182770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.367056E+11 | 0.229551E+12 | 0.308041E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.384540E+11 | 0.260147E+12 | 0.153994E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.355170E+11 | 0.605792E+11 | 0.595409E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.359194E+11 | 0.668534E+11 | 0.882108E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.436033E+12 | 0.182315E+13 | 0.512046E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.325105E+11 | 0.325376E+11 | 0.182770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.384540E+11 | 0.388248E+12 | 0.970608E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.271000E+10 | 0.796627E+10 | 0.352394E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244774E+10 | 0.641498E+10 | 0.189616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.271000E+10 | 0.857742E+10 | 0.213914E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.262258E+10 | 0.405566E+10 | 0.536108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.271000E+10 | 0.360689E+10 | 0.568444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.262258E+10 | 0.639403E+09 | 0.127679E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.271000E+10 | 37027035.96 | 0.285718E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.271000E+10 | 17469671.82 | 0.326065E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.262258E+10 | 0.319034E+09 | 0.185738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.271000E+10 | 0.143387E+10 | 0.206208E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.262258E+10 | 0.564075E+10 | 0.354751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.271000E+10 | 0.800628E+10 | 0.428641E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319080E+11 | 0.467151E+11 | 0.139579E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244774E+10 | 17469671.82 | 0.189616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.271000E+10 | 0.857742E+10 | 0.326065E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.354911E+11 | 0.902641E+11 | 0.580356E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.325105E+11 | 0.704084E+11 | 0.325376E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.356248E+11 | 0.970608E+11 | 0.360422E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.356106E+11 | 0.429903E+11 | 0.856442E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.370521E+11 | 0.375501E+11 | 0.916843E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.365613E+11 | 0.693222E+10 | 0.168981E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.381737E+11 | 0.425797E+09 | 0.344845E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.384129E+11 | 0.182770E+09 | 0.388248E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.367056E+11 | 0.308041E+10 | 0.229551E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.384540E+11 | 0.153994E+11 | 0.260147E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.355170E+11 | 0.595409E+11 | 0.605792E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.359194E+11 | 0.882108E+11 | 0.668534E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.436033E+12 | 0.512046E+12 | 0.182315E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.325105E+11 | 0.182770E+09 | 0.325376E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.384540E+11 | 0.970608E+11 | 0.388248E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.424151E+11 | 0.00 | 0.00 | 5211415.17 | 77329012.66 | 0.00 | 0.111469E+11 | 0.00 | 1.01 |
February | 0.468116E+11 | 0.00 | 0.00 | 401592.59 | 14151252.45 | 0.00 | 0.117716E+10 | 0.00 | 1.01 |
March | 0.550261E+11 | 0.00 | 0.00 | 0.00 | 131877.72 | 0.00 | 0.00 | 0.00 | 1.01 |
April | 0.431474E+11 | 0.00 | 0.00 | 0.00 | 79350020.58 | 0.00 | 0.00 | 0.00 | 1.01 |
May | 0.433853E+11 | 0.00 | 0.00 | 0.00 | 11321854.45 | 0.00 | 0.00 | 0.00 | 1.01 |
June | 0.320859E+11 | 0.00 | 0.00 | 0.00 | 0.560409E+09 | 0.00 | 0.00 | 0.00 | 1.01 |
July | 0.204172E+11 | 0.00 | 0.00 | 18233.70 | 0.463608E+10 | 0.00 | 0.207027E+09 | 0.00 | 1.02 |
August | 0.162287E+11 | 0.00 | 0.00 | 267209.70 | 0.557649E+10 | 0.00 | 0.127796E+10 | 0.00 | 1.02 |
September | 0.225707E+11 | 67557174.02 | 0.00 | 3876105.98 | 0.169303E+10 | 0.00 | 0.539683E+10 | 0.00 | 1.02 |
October | 0.994291E+10 | 0.109765E+09 | 0.00 | 14855047.78 | 0.300042E+10 | 0.00 | 0.198541E+11 | 0.00 | 1.02 |
November | 0.193809E+11 | 377609.55 | 0.00 | 15520753.49 | 51157449.62 | 0.00 | 0.294700E+11 | 0.00 | 1.02 |
December | 0.375439E+11 | 0.00 | 0.00 | 7223668.94 | 27407126.79 | 0.00 | 0.149707E+11 | 0.00 | 1.01 |
Annual Sum or Average | 0.388956E+12 | 0.177700E+09 | 0.00 | 47374027.34 | 0.157273E+11 | 0.00 | 0.835008E+11 | 0.00 | 1.01 |
Minimum of Months | 0.994291E+10 | 0.00 | 0.00 | 0.00 | 131877.72 | 0.00 | 0.00 | 0.00 | 1.01 |
Maximum of Months | 0.550261E+11 | 0.109765E+09 | 0.00 | 15520753.49 | 0.557649E+10 | 0.00 | 0.294700E+11 | 0.00 | 1.02 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.611178E+10 | 14489237.56 | 0.00 | 2321322.99 | 370698.93 | 1360984.56 | 0.863105E+09 | 0.00 | 2.43 |
February | 0.564697E+10 | 2459157.62 | 0.00 | 1512805.14 | 0.00 | 0.00 | 0.554428E+09 | 0.00 | 2.40 |
March | 0.678967E+10 | 0.00 | 0.00 | 649531.45 | 16910.82 | 27035354.27 | 0.241779E+09 | 0.00 | 2.36 |
April | 0.539443E+10 | 4852595.72 | 0.00 | 209792.30 | 5322539.82 | 0.00 | 0.138203E+09 | 0.00 | 2.35 |
May | 0.555994E+10 | 529264.48 | 0.00 | 6030.41 | 922548.68 | 0.00 | 3390891.88 | 0.00 | 2.35 |
June | 0.411441E+10 | 0.00 | 0.00 | 0.00 | 71861783.94 | 0.00 | 0.00 | 0.00 | 2.36 |
July | 0.264100E+10 | 0.101325E+09 | 0.00 | 2328.39 | 0.493165E+09 | 0.00 | 3667079.41 | 0.00 | 2.36 |
August | 0.215892E+10 | 0.352342E+09 | 0.00 | 85126.43 | 0.362737E+09 | 0.00 | 85925295.51 | 0.00 | 2.37 |
September | 0.317506E+10 | 0.186639E+09 | 0.00 | 987827.48 | 82165656.83 | 0.00 | 0.415743E+09 | 0.00 | 2.41 |
October | 0.314276E+10 | 0.442803E+09 | 0.00 | 2015868.46 | 96825995.96 | 0.00 | 0.679323E+09 | 0.00 | 2.53 |
November | 0.551186E+10 | 10778224.81 | 0.00 | 2466926.27 | 0.00 | 0.00 | 0.792071E+09 | 0.00 | 2.46 |
December | 0.594536E+10 | 5606673.06 | 0.00 | 3271746.87 | 0.00 | 0.00 | 0.902066E+09 | 0.00 | 2.49 |
Annual Sum or Average | 0.561922E+11 | 0.112182E+10 | 0.00 | 13529306.21 | 0.111339E+10 | 28396338.84 | 0.467970E+10 | 0.00 | 2.41 |
Minimum of Months | 0.215892E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.35 |
Maximum of Months | 0.678967E+10 | 0.442803E+09 | 0.00 | 3271746.87 | 0.493165E+09 | 27035354.27 | 0.902066E+09 | 0.00 | 2.53 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.429933E+10 | 0.00 | 0.00 | 288939.92 | 7230588.42 | 0.00 | 0.707498E+09 | 0.00 | 1.48 |
February | 0.374543E+10 | 0.00 | 0.00 | 312083.21 | 1323201.71 | 0.00 | 0.744060E+09 | 0.00 | 1.48 |
March | 0.461263E+10 | 0.00 | 0.00 | 204039.75 | 12331.12 | 0.00 | 0.533816E+09 | 0.00 | 1.48 |
April | 0.299005E+10 | 0.00 | 0.00 | 587296.87 | 7419561.17 | 0.00 | 0.104988E+10 | 0.00 | 1.49 |
May | 0.314917E+10 | 0.00 | 0.00 | 491898.19 | 1058641.08 | 0.00 | 0.910292E+09 | 0.00 | 1.49 |
June | 0.186770E+10 | 98470.93 | 0.00 | 1004174.36 | 52302099.03 | 0.00 | 0.114146E+10 | 0.00 | 1.50 |
July | 0.645880E+09 | 13460852.44 | 0.00 | 1839844.22 | 0.420101E+09 | 0.00 | 0.129956E+10 | 0.00 | 1.51 |
August | 0.354289E+09 | 9860263.66 | 0.00 | 2275816.98 | 0.511571E+09 | 0.00 | 0.131334E+10 | 0.00 | 1.52 |
September | 0.105707E+10 | 38910611.52 | 0.00 | 1689824.61 | 0.125916E+09 | 0.00 | 0.159020E+10 | 0.00 | 1.51 |
October | 0.125308E+10 | 85963842.86 | 0.00 | 1889340.72 | 0.205082E+09 | 0.00 | 0.155862E+10 | 0.00 | 1.51 |
November | 0.329008E+10 | 35308.08 | 0.00 | 640848.58 | 4783437.03 | 0.00 | 0.123433E+10 | 0.00 | 1.48 |
December | 0.395665E+10 | 0.00 | 0.00 | 441114.00 | 2562681.80 | 0.00 | 0.951456E+09 | 0.00 | 1.48 |
Annual Sum or Average | 0.312213E+11 | 0.148329E+09 | 0.00 | 11665221.42 | 0.133936E+10 | 0.00 | 0.130345E+11 | 0.00 | 1.49 |
Minimum of Months | 0.354289E+09 | 0.00 | 0.00 | 204039.75 | 12331.12 | 0.00 | 0.533816E+09 | 0.00 | 1.48 |
Maximum of Months | 0.461263E+10 | 85963842.86 | 0.00 | 2275816.98 | 0.511571E+09 | 0.00 | 0.159020E+10 | 0.00 | 1.52 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.398030E+10 | 0.00 | 0.00 | 0.00 | 5748515.90 | 0.00 | 0.00 | 0.00 | 0.55 |
February | 0.356744E+10 | 0.00 | 0.00 | 0.00 | 1051981.62 | 0.00 | 0.00 | 0.00 | 0.56 |
March | 0.409055E+10 | 0.00 | 0.00 | 0.00 | 9803.58 | 0.00 | 0.00 | 0.00 | 0.56 |
April | 0.320751E+10 | 0.00 | 0.00 | 0.00 | 5898754.42 | 0.00 | 0.00 | 0.00 | 0.56 |
May | 0.322519E+10 | 0.00 | 0.00 | 0.00 | 841648.67 | 0.00 | 0.00 | 0.00 | 0.56 |
June | 0.238522E+10 | 0.00 | 0.00 | 0.00 | 41659888.86 | 0.00 | 0.00 | 0.00 | 0.56 |
July | 0.152754E+10 | 93730.21 | 0.00 | 2194.98 | 0.344545E+09 | 0.00 | 5634559.87 | 0.00 | 0.56 |
August | 0.129827E+10 | 0.00 | 0.00 | 2597.86 | 0.414548E+09 | 0.00 | 3162456.43 | 0.00 | 0.56 |
September | 0.207406E+10 | 59010.87 | 0.00 | 14864.81 | 0.130820E+09 | 0.00 | 5279283.87 | 0.00 | 0.56 |
October | 0.215321E+10 | 3150838.71 | 0.00 | 56620.51 | 0.227931E+09 | 0.00 | 45341739.67 | 0.00 | 0.56 |
November | 0.359370E+10 | 0.00 | 0.00 | 0.00 | 3831034.40 | 0.00 | 0.00 | 0.00 | 0.56 |
December | 0.390037E+10 | 0.00 | 0.00 | 0.00 | 2037402.25 | 0.00 | 0.00 | 0.00 | 0.55 |
Annual Sum or Average | 0.350034E+11 | 3303579.80 | 0.00 | 76278.16 | 0.117892E+10 | 0.00 | 59418039.85 | 0.00 | 0.56 |
Minimum of Months | 0.129827E+10 | 0.00 | 0.00 | 0.00 | 9803.58 | 0.00 | 0.00 | 0.00 | 0.55 |
Maximum of Months | 0.409055E+10 | 3150838.71 | 0.00 | 56620.51 | 0.414548E+09 | 0.00 | 45341739.67 | 0.00 | 0.56 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.233590E+10 | 0.00 | 0.00 | 0.00 | 3373599.23 | 0.00 | 0.00 | 0.00 | 0.56 |
February | 0.209360E+10 | 0.00 | 0.00 | 0.00 | 617370.54 | 0.00 | 0.00 | 0.00 | 0.56 |
March | 0.240060E+10 | 0.00 | 0.00 | 0.00 | 5753.37 | 0.00 | 0.00 | 0.00 | 0.56 |
April | 0.188237E+10 | 0.00 | 0.00 | 0.00 | 3461768.86 | 0.00 | 0.00 | 0.00 | 0.57 |
May | 0.189275E+10 | 0.00 | 0.00 | 0.00 | 493933.62 | 0.00 | 0.00 | 0.00 | 0.57 |
June | 0.139980E+10 | 0.00 | 0.00 | 0.00 | 24448704.89 | 0.00 | 0.00 | 0.00 | 0.57 |
July | 0.899766E+09 | 0.00 | 0.00 | 0.00 | 0.202256E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
August | 0.763765E+09 | 0.00 | 0.00 | 0.00 | 0.243283E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
September | 0.122030E+10 | 0.00 | 0.00 | 0.00 | 76808190.93 | 0.00 | 0.00 | 0.00 | 0.57 |
October | 0.129018E+10 | 0.00 | 0.00 | 0.00 | 0.135614E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
November | 0.210902E+10 | 0.00 | 0.00 | 0.00 | 2248297.63 | 0.00 | 0.00 | 0.00 | 0.56 |
December | 0.228899E+10 | 0.00 | 0.00 | 0.00 | 1195678.81 | 0.00 | 0.00 | 0.00 | 0.56 |
Annual Sum or Average | 0.205770E+11 | 0.00 | 0.00 | 0.00 | 0.693806E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
Minimum of Months | 0.763765E+09 | 0.00 | 0.00 | 0.00 | 5753.37 | 0.00 | 0.00 | 0.00 | 0.56 |
Maximum of Months | 0.240060E+10 | 0.00 | 0.00 | 0.00 | 0.243283E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.435995E+09 | 0.104643E+09 | 0.00 | 98125524.88 | 0.00 | 0.00 | 0.817724E+11 | 0.00 | 23.82 |
February | 0.304375E+09 | 19149784.20 | 0.00 | 87404582.16 | 0.00 | 0.00 | 0.738924E+11 | 0.00 | 24.10 |
March | 0.318079E+09 | 178459.82 | 0.00 | 95907845.30 | 0.00 | 0.00 | 0.844899E+11 | 0.00 | 24.04 |
April | 0.190968E+09 | 0.107378E+09 | 0.00 | 0.104523E+09 | 0.00 | 0.00 | 0.669647E+11 | 0.00 | 24.13 |
May | 0.213120E+09 | 15320980.97 | 0.00 | 0.113430E+09 | 0.00 | 0.00 | 0.673641E+11 | 0.00 | 24.18 |
June | 62396765.84 | 0.765794E+09 | 0.00 | 0.113945E+09 | 293877.60 | 0.00 | 0.501360E+11 | 0.00 | 24.26 |
July | 61661345.69 | 0.641646E+10 | 0.00 | 96963300.94 | 49035471.20 | 0.00 | 0.315644E+11 | 0.00 | 24.19 |
August | 7939157.72 | 0.754872E+10 | 0.00 | 89964368.19 | 0.126646E+09 | 0.00 | 0.272179E+11 | 0.00 | 24.34 |
September | 66977823.86 | 0.243951E+10 | 0.00 | 99632655.23 | 0.00 | 0.00 | 0.433505E+11 | 0.00 | 24.31 |
October | 81450288.73 | 0.430731E+10 | 0.00 | 92858376.67 | 43769438.76 | 0.00 | 0.460119E+11 | 0.00 | 24.25 |
November | 0.230793E+09 | 69738368.80 | 0.00 | 97504472.52 | 0.00 | 0.00 | 0.748859E+11 | 0.00 | 24.13 |
December | 0.297258E+09 | 37403151.17 | 0.00 | 98689578.69 | 0.00 | 0.00 | 0.807718E+11 | 0.00 | 23.91 |
Annual Sum or Average | 0.227101E+10 | 0.218316E+11 | 0.00 | 0.118895E+10 | 0.219745E+09 | 0.00 | 0.728422E+12 | 0.00 | 24.14 |
Minimum of Months | 7939157.72 | 178459.82 | 0.00 | 87404582.16 | 0.00 | 0.00 | 0.272179E+11 | 0.00 | 23.82 |
Maximum of Months | 0.435995E+09 | 0.754872E+10 | 0.00 | 0.113945E+09 | 0.126646E+09 | 0.00 | 0.844899E+11 | 0.00 | 24.34 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.790195E+10 | 57233139.54 | 0.00 | 23167677.99 | 1174245.29 | 0.00 | 0.229127E+11 | 0.00 | 3.81 |
February | 0.786110E+10 | 9517311.61 | 0.00 | 17869841.93 | 0.00 | 0.00 | 0.195907E+11 | 0.00 | 3.77 |
March | 0.133677E+11 | 74818.91 | 0.00 | 12364556.84 | 0.00 | 0.00 | 0.178752E+11 | 0.00 | 3.72 |
April | 0.663271E+10 | 33370419.74 | 0.00 | 13221602.94 | 11647664.46 | 0.00 | 0.178703E+11 | 0.00 | 3.72 |
May | 0.893239E+10 | 2341636.90 | 0.00 | 9798154.76 | 4081653.14 | 0.00 | 0.156936E+11 | 0.00 | 3.71 |
June | 0.540724E+10 | 21727245.29 | 0.00 | 12873799.37 | 0.296212E+09 | 0.00 | 0.128038E+11 | 0.00 | 3.72 |
July | 0.224005E+10 | 0.140500E+10 | 0.00 | 16552113.30 | 0.122521E+10 | 0.00 | 0.949640E+10 | 0.00 | 3.74 |
August | 0.107886E+10 | 0.215063E+10 | 0.00 | 19875237.73 | 0.101312E+10 | 0.00 | 0.900767E+10 | 0.00 | 3.78 |
September | 0.222437E+10 | 0.841653E+09 | 0.00 | 22856656.13 | 0.244024E+09 | 0.00 | 0.138935E+11 | 0.00 | 3.82 |
October | 0.200320E+10 | 0.186873E+10 | 0.00 | 27966694.95 | 0.203217E+09 | 0.00 | 0.153928E+11 | 0.00 | 3.96 |
November | 0.389540E+10 | 41394909.41 | 0.00 | 26952139.87 | 0.00 | 0.00 | 0.240417E+11 | 0.00 | 3.85 |
December | 0.668453E+10 | 21043835.08 | 0.00 | 28464596.17 | 0.00 | 0.00 | 0.236454E+11 | 0.00 | 3.88 |
Annual Sum or Average | 0.682295E+11 | 0.645272E+10 | 0.00 | 0.231963E+09 | 0.299869E+10 | 0.00 | 0.202224E+12 | 0.00 | 3.79 |
Minimum of Months | 0.107886E+10 | 74818.91 | 0.00 | 9798154.76 | 0.00 | 0.00 | 0.900767E+10 | 0.00 | 3.71 |
Maximum of Months | 0.133677E+11 | 0.215063E+10 | 0.00 | 28464596.17 | 0.122521E+10 | 0.00 | 0.240417E+11 | 0.00 | 3.96 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.529333E+11 | 55654215.62 | 0.00 | 30549406.65 | 92386283.87 | 0.00 | 0.500044E+11 | 0.00 | 1.81 |
February | 0.409166E+11 | 0.00 | 0.00 | 28940449.86 | 27091493.97 | 0.00 | 0.514279E+11 | 0.00 | 1.82 |
March | 0.608887E+11 | 0.00 | 0.00 | 22227233.91 | 252469.85 | 0.00 | 0.446598E+11 | 0.00 | 1.81 |
April | 0.326151E+11 | 0.00 | 0.00 | 36412889.80 | 0.151910E+09 | 0.00 | 0.504459E+11 | 0.00 | 1.82 |
May | 0.314572E+11 | 0.00 | 0.00 | 36888703.86 | 21674827.21 | 0.00 | 0.519676E+11 | 0.00 | 1.82 |
June | 0.177718E+11 | 2016113.23 | 0.00 | 53284927.18 | 0.107084E+10 | 0.00 | 0.442761E+11 | 0.00 | 1.83 |
July | 0.673328E+10 | 0.420032E+09 | 0.00 | 69187931.09 | 0.845601E+10 | 0.00 | 0.335225E+11 | 0.00 | 1.85 |
August | 0.396000E+10 | 0.630368E+09 | 0.00 | 74673125.46 | 0.100454E+11 | 0.00 | 0.307661E+11 | 0.00 | 1.86 |
September | 0.117025E+11 | 0.139152E+10 | 0.00 | 65350815.39 | 0.200184E+10 | 0.00 | 0.432388E+11 | 0.00 | 1.86 |
October | 0.960263E+10 | 0.363643E+10 | 0.00 | 72478644.44 | 0.233226E+10 | 0.00 | 0.494586E+11 | 0.00 | 1.88 |
November | 0.272176E+11 | 91518055.42 | 0.00 | 47710618.02 | 7200495.42 | 0.00 | 0.664805E+11 | 0.00 | 1.82 |
December | 0.417537E+11 | 31050267.32 | 0.00 | 38307366.85 | 21418587.51 | 0.00 | 0.594892E+11 | 0.00 | 1.81 |
Annual Sum or Average | 0.337552E+12 | 0.625859E+10 | 0.00 | 0.576012E+09 | 0.242283E+11 | 0.00 | 0.575737E+12 | 0.00 | 1.83 |
Minimum of Months | 0.396000E+10 | 0.00 | 0.00 | 22227233.91 | 252469.85 | 0.00 | 0.307661E+11 | 0.00 | 1.81 |
Maximum of Months | 0.608887E+11 | 0.363643E+10 | 0.00 | 74673125.46 | 0.100454E+11 | 0.00 | 0.664805E+11 | 0.00 | 1.88 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 9591654.22 | 2456508.33 | 3556.49 | 6986971.29 | 840180.78 | 0.530767E+09 | 0.130006E+10 | 4954.08 | 0.35 |
February | 24063881.23 | 1584546.67 | 0.00 | 6545839.88 | 0.00 | 0.302183E+09 | 0.126258E+10 | 0.00 | 0.36 |
March | 39518817.52 | 2800218.40 | 0.00 | 6777053.31 | 0.00 | 0.546120E+09 | 0.124583E+10 | 0.00 | 0.36 |
April | 15054800.99 | 7068947.88 | 0.00 | 12280831.46 | 0.00 | 54899032.40 | 0.117280E+10 | 0.00 | 0.36 |
May | 24805437.99 | 2668049.47 | 0.00 | 12938664.73 | 128353.55 | 41074850.72 | 0.119255E+10 | 0.00 | 0.36 |
June | 8590317.60 | 43562559.20 | 0.00 | 13237647.03 | 269791.07 | 1809905.83 | 0.708219E+09 | 0.00 | 0.36 |
July | 0.00 | 0.260843E+09 | 11489.29 | 11119439.28 | 0.00 | 734990.24 | 0.318254E+09 | 4045.12 | 0.36 |
August | 0.00 | 0.339108E+09 | 37639.85 | 8644328.64 | 0.00 | 619817.72 | 0.239678E+09 | 10147.02 | 0.36 |
September | 1614375.76 | 0.102920E+09 | 11844.14 | 11457406.58 | 3772446.33 | 2024934.77 | 0.539535E+09 | 3008.27 | 0.36 |
October | 3640093.80 | 0.192002E+09 | 92960.40 | 9674335.30 | 0.00 | 2074122.84 | 0.851036E+09 | 11830.52 | 0.36 |
November | 9486146.28 | 2651826.20 | 0.00 | 8671088.32 | 259950.12 | 0.119738E+09 | 0.141927E+10 | 0.00 | 0.35 |
December | 11562969.57 | 4585814.36 | 13774.18 | 7731632.14 | 0.00 | 0.361598E+09 | 0.143108E+10 | 1556.21 | 0.35 |
Annual Sum or Average | 0.147928E+09 | 0.962252E+09 | 171264.34 | 0.116065E+09 | 5270721.84 | 0.196364E+10 | 0.116809E+11 | 35541.20 | 0.36 |
Minimum of Months | 0.00 | 1584546.67 | 0.00 | 6545839.88 | 0.00 | 619817.72 | 0.239678E+09 | 0.00 | 0.35 |
Maximum of Months | 39518817.52 | 0.339108E+09 | 92960.40 | 13237647.03 | 3772446.33 | 0.546120E+09 | 0.143108E+10 | 11830.52 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.124475E+09 | 1133750.22 | 18608.27 | 2886919.09 | 2144626.69 | 0.940539E+09 | 0.779287E+09 | 7827.24 | 0.35 |
February | 0.108547E+09 | 573111.79 | 0.00 | 3447968.55 | 1011249.23 | 0.535949E+09 | 0.947240E+09 | 0.00 | 0.36 |
March | 0.105449E+09 | 577507.21 | 0.00 | 4151072.51 | 2222383.10 | 0.722696E+09 | 0.100573E+10 | 0.00 | 0.36 |
April | 0.158887E+09 | 4556869.23 | 0.00 | 8430598.41 | 2511250.42 | 64318553.07 | 0.102325E+10 | 0.00 | 0.36 |
May | 0.225721E+09 | 2557072.55 | 0.00 | 10243709.36 | 239002.82 | 36766340.02 | 0.998484E+09 | 0.00 | 0.36 |
June | 0.298115E+09 | 35014997.32 | 40946.54 | 9222237.10 | 8763044.05 | 1178028.08 | 0.423255E+09 | 8226.76 | 0.36 |
July | 0.214009E+09 | 0.218276E+09 | 104666.89 | 6894913.19 | 42440084.20 | 163601.26 | 0.109003E+09 | 7581.71 | 0.36 |
August | 0.170586E+09 | 0.280136E+09 | 85310.52 | 4583710.34 | 58888909.47 | 238253.98 | 73504770.17 | 5233.37 | 0.36 |
September | 0.230850E+09 | 88141571.69 | 129911.55 | 6662138.95 | 18413609.04 | 1099199.21 | 0.315955E+09 | 9921.47 | 0.36 |
October | 0.235642E+09 | 0.156445E+09 | 203694.77 | 4987718.89 | 35419413.15 | 1774586.74 | 0.623919E+09 | 16076.81 | 0.36 |
November | 0.163288E+09 | 2249011.22 | 12599.17 | 4060891.17 | 646920.31 | 0.344462E+09 | 0.104517E+10 | 2904.46 | 0.35 |
December | 0.139483E+09 | 3332610.65 | 43850.04 | 2987080.50 | 1211330.33 | 0.830593E+09 | 0.838699E+09 | 12814.64 | 0.35 |
Annual Sum or Average | 0.217505E+10 | 0.792994E+09 | 639587.75 | 68558958.05 | 0.173912E+09 | 0.347978E+10 | 0.818349E+10 | 70586.45 | 0.36 |
Minimum of Months | 0.105449E+09 | 573111.79 | 0.00 | 2886919.09 | 239002.82 | 163601.26 | 73504770.17 | 0.00 | 0.35 |
Maximum of Months | 0.298115E+09 | 0.280136E+09 | 203694.77 | 10243709.36 | 58888909.47 | 0.940539E+09 | 0.104517E+10 | 16076.81 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 98915629.49 | 999740.93 | 0.00 | 4362673.07 | 0.00 | 0.00 | 0.102176E+10 | 0.00 | 0.02 |
February | 0.395865E+09 | 0.00 | 0.00 | 2614381.62 | 0.00 | 0.00 | 0.759550E+09 | 0.00 | 0.02 |
March | 0.588558E+09 | 7500674.86 | 0.00 | 1904939.19 | 0.00 | 0.00 | 0.630637E+09 | 0.00 | 0.02 |
April | 0.146785E+09 | 288357.43 | 0.00 | 2125214.88 | 0.00 | 0.00 | 0.661888E+09 | 0.00 | 0.02 |
May | 0.665821E+09 | 0.00 | 0.00 | 450823.00 | 0.00 | 0.00 | 0.308045E+09 | 0.00 | 0.02 |
June | 0.373810E+09 | 22078718.67 | 0.00 | 232574.53 | 559329.18 | 0.00 | 0.175283E+09 | 0.00 | 0.02 |
July | 33178457.94 | 0.358784E+09 | 0.00 | 194304.03 | 1459769.80 | 0.00 | 0.102205E+09 | 0.00 | 0.02 |
August | 0.00 | 0.537111E+09 | 0.00 | 245474.02 | 0.00 | 0.00 | 22671334.64 | 0.00 | 0.02 |
September | 0.00 | 0.188751E+09 | 0.00 | 1562519.44 | 0.00 | 0.00 | 0.152150E+09 | 0.00 | 0.02 |
October | 30206293.52 | 0.203162E+09 | 0.00 | 2699714.19 | 0.00 | 0.00 | 0.335983E+09 | 0.00 | 0.02 |
November | 20821618.73 | 0.00 | 0.00 | 4000202.47 | 0.00 | 0.00 | 0.983225E+09 | 0.00 | 0.02 |
December | 79848721.30 | 0.00 | 0.00 | 4600362.55 | 0.00 | 0.00 | 0.108581E+10 | 0.00 | 0.02 |
Annual Sum or Average | 0.243381E+10 | 0.131868E+10 | 0.00 | 24993183.00 | 2019098.99 | 0.00 | 0.623921E+10 | 0.00 | 0.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 194304.03 | 0.00 | 0.00 | 22671334.64 | 0.00 | 0.02 |
Maximum of Months | 0.665821E+09 | 0.537111E+09 | 0.00 | 4600362.55 | 1459769.80 | 0.00 | 0.108581E+10 | 0.00 | 0.02 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.169040E+10 | 13143072.24 | 398344.02 | 57459603.32 | 31264661.54 | 0.170403E+09 | 0.231377E+11 | 21720.04 | 0.40 |
February | 0.147386E+10 | 6520141.59 | 219789.79 | 59635694.86 | 14750901.50 | 0.106450E+09 | 0.199978E+11 | 73.89 | 0.40 |
March | 0.144288E+10 | 7498231.41 | 325994.03 | 70370122.69 | 30145293.53 | 0.130247E+09 | 0.232883E+11 | 9313.45 | 0.40 |
April | 0.218164E+10 | 41322919.61 | 406025.49 | 96989169.40 | 54114236.45 | 29759682.53 | 0.147133E+11 | 31621.32 | 0.40 |
May | 0.314797E+10 | 13146931.69 | 185042.15 | 0.122506E+09 | 24594922.73 | 22815901.73 | 0.139500E+11 | 188.51 | 0.40 |
June | 0.412098E+10 | 0.329784E+09 | 322402.29 | 0.116010E+09 | 0.264381E+09 | 6946563.31 | 0.568209E+10 | 3211.85 | 0.41 |
July | 0.291110E+10 | 0.243877E+10 | 962755.86 | 84140149.90 | 0.109823E+10 | 1935335.39 | 0.148003E+10 | 10823.87 | 0.41 |
August | 0.231390E+10 | 0.309819E+10 | 1098360.07 | 56290633.13 | 0.150060E+10 | 1498946.33 | 0.100467E+10 | 7214.56 | 0.41 |
September | 0.316652E+10 | 0.947085E+09 | 477600.70 | 76132538.67 | 0.499651E+09 | 10794717.56 | 0.426892E+10 | 39844.45 | 0.41 |
October | 0.321215E+10 | 0.178261E+10 | 2722200.46 | 66592059.02 | 0.820091E+09 | 16543232.46 | 0.845586E+10 | 91937.26 | 0.40 |
November | 0.222891E+10 | 20409340.38 | 328556.57 | 64915816.13 | 18726834.08 | 73160193.39 | 0.187525E+11 | 27140.32 | 0.40 |
December | 0.189152E+10 | 42917681.54 | 596896.60 | 56111729.77 | 18814858.99 | 0.113066E+09 | 0.225148E+11 | 75018.68 | 0.40 |
Annual Sum or Average | 0.297818E+11 | 0.874140E+10 | 8043968.03 | 0.927153E+09 | 0.437537E+10 | 0.683621E+09 | 0.157246E+12 | 318108.19 | 0.40 |
Minimum of Months | 0.144288E+10 | 6520141.59 | 185042.15 | 56111729.77 | 14750901.50 | 1498946.33 | 0.100467E+10 | 73.89 | 0.40 |
Maximum of Months | 0.412098E+10 | 0.309819E+10 | 2722200.46 | 0.122506E+09 | 0.150060E+10 | 0.170403E+09 | 0.232883E+11 | 91937.26 | 0.41 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 11529572.38 | 2465863.57 | 22488.69 | 8202199.97 | 811455.21 | 0.530918E+09 | 0.129675E+10 | 5392.20 | 0.35 |
February | 26853816.66 | 1584546.67 | 0.00 | 6484868.24 | 0.00 | 0.362865E+09 | 0.119917E+10 | 0.00 | 0.36 |
March | 41770004.17 | 2800218.40 | 0.00 | 6993555.19 | 0.00 | 0.580528E+09 | 0.120895E+10 | 0.00 | 0.36 |
April | 10502231.78 | 7068947.88 | 0.00 | 11351498.66 | 0.00 | 52314195.23 | 0.118086E+10 | 0.00 | 0.36 |
May | 19993925.02 | 2796403.01 | 0.00 | 11779307.31 | 0.00 | 72426616.29 | 0.116716E+10 | 0.00 | 0.36 |
June | 8020855.80 | 43832350.27 | 0.00 | 11947212.11 | 0.00 | 2120914.30 | 0.709768E+09 | 0.00 | 0.36 |
July | 0.00 | 0.260859E+09 | 0.00 | 10531218.20 | 0.00 | 399692.28 | 0.319178E+09 | 0.00 | 0.36 |
August | 0.00 | 0.339155E+09 | 0.00 | 8631362.68 | 0.00 | 313159.96 | 0.239998E+09 | 0.00 | 0.36 |
September | 1614375.76 | 0.102913E+09 | 0.00 | 10273612.42 | 3794706.14 | 1639565.76 | 0.541104E+09 | 0.00 | 0.36 |
October | 3599895.74 | 0.190813E+09 | 0.00 | 9929719.91 | 1291946.58 | 2359011.73 | 0.850536E+09 | 1584.45 | 0.36 |
November | 10517212.05 | 2555814.01 | 0.00 | 8930673.30 | 355962.31 | 0.168295E+09 | 0.136942E+10 | 0.00 | 0.35 |
December | 14103352.34 | 4585814.36 | 11429.07 | 8441005.55 | 0.00 | 0.443315E+09 | 0.134611E+10 | 3901.32 | 0.35 |
Annual Sum or Average | 0.148505E+09 | 0.961431E+09 | 33917.75 | 0.113496E+09 | 6254070.23 | 0.221749E+10 | 0.114290E+11 | 10877.98 | 0.36 |
Minimum of Months | 0.00 | 1584546.67 | 0.00 | 6484868.24 | 0.00 | 313159.96 | 0.239998E+09 | 0.00 | 0.35 |
Maximum of Months | 41770004.17 | 0.339155E+09 | 22488.69 | 11947212.11 | 3794706.14 | 0.580528E+09 | 0.136942E+10 | 5392.20 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.124924E+09 | 981227.37 | 26909.07 | 3492906.06 | 2292274.75 | 0.855386E+09 | 0.863385E+09 | 4401.22 | 0.35 |
February | 0.108656E+09 | 558309.58 | 10840.65 | 3368159.24 | 1011249.23 | 0.636986E+09 | 0.846174E+09 | 3961.56 | 0.36 |
March | 0.105353E+09 | 970247.70 | 0.00 | 4409130.45 | 1829642.61 | 0.734250E+09 | 0.994016E+09 | 0.00 | 0.36 |
April | 0.154688E+09 | 6415163.95 | 0.00 | 8219788.74 | 652955.70 | 81017297.15 | 0.101096E+10 | 0.00 | 0.36 |
May | 0.221933E+09 | 2729197.05 | 0.00 | 9842282.65 | 66878.33 | 68583515.98 | 0.970856E+09 | 0.00 | 0.36 |
June | 0.297198E+09 | 35248892.81 | 0.00 | 7991311.92 | 8578321.87 | 1263334.50 | 0.425318E+09 | 0.00 | 0.36 |
July | 0.212559E+09 | 0.220435E+09 | 0.00 | 5936187.50 | 40393512.58 | 315596.08 | 0.111259E+09 | 0.00 | 0.36 |
August | 0.170352E+09 | 0.283939E+09 | 0.00 | 3999454.39 | 55176334.34 | 311762.48 | 74249647.37 | 0.00 | 0.36 |
September | 0.231145E+09 | 87224193.10 | 60087.81 | 5748976.82 | 19407571.73 | 1029168.02 | 0.316644E+09 | 3161.11 | 0.36 |
October | 0.235494E+09 | 0.157795E+09 | 195847.00 | 5317805.51 | 34086874.99 | 3116871.12 | 0.622395E+09 | 6569.04 | 0.36 |
November | 0.164358E+09 | 2047470.64 | 16491.12 | 4262840.25 | 842642.39 | 0.447501E+09 | 0.940858E+09 | 4831.01 | 0.35 |
December | 0.139337E+09 | 3238163.21 | 32998.85 | 3302286.12 | 1324025.37 | 0.825965E+09 | 0.843158E+09 | 5418.23 | 0.35 |
Annual Sum or Average | 0.216600E+10 | 0.801582E+09 | 343174.49 | 65891129.64 | 0.165662E+09 | 0.365573E+10 | 0.801927E+10 | 28342.18 | 0.36 |
Minimum of Months | 0.105353E+09 | 558309.58 | 0.00 | 3302286.12 | 66878.33 | 311762.48 | 74249647.37 | 0.00 | 0.35 |
Maximum of Months | 0.297198E+09 | 0.283939E+09 | 195847.00 | 9842282.65 | 55176334.34 | 0.855386E+09 | 0.101096E+10 | 6569.04 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.313042E+11 | 0.00 | 0.00 | 0.00 | 45210810.70 | 0.00 | 0.00 | 0.00 | 0.60 |
February | 0.280571E+11 | 0.00 | 0.00 | 0.00 | 8273603.57 | 0.00 | 0.00 | 0.00 | 0.60 |
March | 0.321713E+11 | 0.00 | 0.00 | 0.00 | 77103.00 | 0.00 | 0.00 | 0.00 | 0.60 |
April | 0.252264E+11 | 0.00 | 0.00 | 0.00 | 46392403.52 | 0.00 | 0.00 | 0.00 | 0.60 |
May | 0.253654E+11 | 0.00 | 0.00 | 0.00 | 6619381.27 | 0.00 | 0.00 | 0.00 | 0.60 |
June | 0.187592E+11 | 0.00 | 0.00 | 0.00 | 0.327646E+09 | 0.00 | 0.00 | 0.00 | 0.60 |
July | 0.120581E+11 | 0.00 | 0.00 | 0.00 | 0.271051E+10 | 0.00 | 0.00 | 0.00 | 0.60 |
August | 0.102355E+11 | 0.00 | 0.00 | 0.00 | 0.326033E+10 | 0.00 | 0.00 | 0.00 | 0.61 |
September | 0.163536E+11 | 0.00 | 0.00 | 0.00 | 0.102933E+10 | 0.00 | 0.00 | 0.00 | 0.61 |
October | 0.172901E+11 | 0.00 | 0.00 | 0.00 | 0.181741E+10 | 0.00 | 0.00 | 0.00 | 0.60 |
November | 0.282637E+11 | 0.00 | 0.00 | 0.00 | 30130241.22 | 0.00 | 0.00 | 0.00 | 0.60 |
December | 0.306755E+11 | 0.00 | 0.00 | 0.00 | 16023719.67 | 0.00 | 0.00 | 0.00 | 0.60 |
Annual Sum or Average | 0.275760E+12 | 0.00 | 0.00 | 0.00 | 0.929795E+10 | 0.00 | 0.00 | 0.00 | 0.60 |
Minimum of Months | 0.102355E+11 | 0.00 | 0.00 | 0.00 | 77103.00 | 0.00 | 0.00 | 0.00 | 0.60 |
Maximum of Months | 0.321713E+11 | 0.00 | 0.00 | 0.00 | 0.326033E+10 | 0.00 | 0.00 | 0.00 | 0.61 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 2274430.40 | 614127.08 | 910.13 | 1409536.69 | 210045.19 | 0.234090E+09 | 0.224077E+09 | 1217.51 | 0.35 |
February | 6419419.29 | 396136.67 | 0.00 | 1344374.75 | 0.00 | 0.185138E+09 | 0.205941E+09 | 0.00 | 0.36 |
March | 9507167.67 | 700054.60 | 0.00 | 1499115.66 | 0.00 | 0.224163E+09 | 0.224392E+09 | 0.00 | 0.36 |
April | 3157560.90 | 1767236.97 | 0.00 | 2913800.06 | 0.00 | 50199331.23 | 0.257487E+09 | 0.00 | 0.36 |
May | 5065714.70 | 699100.75 | 0.00 | 3078648.07 | 0.00 | 41176489.32 | 0.268520E+09 | 0.00 | 0.36 |
June | 2033204.63 | 10955517.60 | 0.00 | 3168700.46 | 2569.97 | 3052126.28 | 0.174710E+09 | 0.00 | 0.36 |
July | 0.00 | 65210832.33 | 3208.24 | 2690495.52 | 0.00 | 195384.33 | 79641329.89 | 675.37 | 0.36 |
August | 0.00 | 84776914.66 | 10016.25 | 2033706.36 | 0.00 | 171453.33 | 60030402.58 | 1930.46 | 0.36 |
September | 403593.94 | 26163686.42 | 2941.42 | 2617807.49 | 509443.98 | 468455.64 | 0.135168E+09 | 807.21 | 0.36 |
October | 1419230.48 | 48000557.17 | 23137.63 | 2056620.79 | 0.00 | 24621695.53 | 0.188509E+09 | 3060.10 | 0.36 |
November | 3147613.88 | 662956.55 | 0.00 | 1739113.85 | 64987.53 | 0.129119E+09 | 0.255284E+09 | 0.00 | 0.35 |
December | 3172363.64 | 1146453.59 | 3466.65 | 1543510.50 | 0.00 | 0.219870E+09 | 0.228407E+09 | 365.95 | 0.35 |
Annual Sum or Average | 36600299.53 | 0.241094E+09 | 43680.33 | 26095430.21 | 787046.67 | 0.111227E+10 | 0.230217E+10 | 8056.59 | 0.36 |
Minimum of Months | 0.00 | 396136.67 | 0.00 | 1344374.75 | 0.00 | 171453.33 | 60030402.58 | 0.00 | 0.35 |
Maximum of Months | 9507167.67 | 84776914.66 | 23137.63 | 3168700.46 | 509443.98 | 0.234090E+09 | 0.268520E+09 | 3060.10 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 31113296.66 | 312214.00 | 4842.23 | 503884.64 | 507380.23 | 0.334559E+09 | 95620493.06 | 1766.65 | 0.35 |
February | 27379694.61 | 143277.95 | 0.00 | 636220.76 | 252812.31 | 0.252952E+09 | 0.117828E+09 | 0.00 | 0.36 |
March | 26334544.78 | 144376.80 | 0.00 | 865372.96 | 555595.77 | 0.266302E+09 | 0.166006E+09 | 0.00 | 0.36 |
April | 39239260.94 | 1488329.42 | 0.00 | 1995391.87 | 278700.50 | 51680062.89 | 0.220806E+09 | 0.00 | 0.36 |
May | 54967813.61 | 682299.26 | 0.00 | 2510386.73 | 16719.58 | 29737457.63 | 0.230588E+09 | 0.00 | 0.36 |
June | 74357964.49 | 8801266.44 | 666.19 | 2345906.36 | 2154268.74 | 679767.67 | 0.105559E+09 | 602.29 | 0.36 |
July | 53502277.86 | 54576755.87 | 19064.08 | 1799293.41 | 10610021.05 | 28284.24 | 27187684.96 | 1234.07 | 0.36 |
August | 42646586.84 | 70039295.86 | 16267.97 | 1147013.30 | 14722227.37 | 67548.38 | 18367121.95 | 1135.92 | 0.36 |
September | 57493504.92 | 22329831.98 | 31537.52 | 1522842.85 | 4309560.31 | 289501.83 | 79335893.42 | 2823.63 | 0.36 |
October | 58959692.29 | 39209565.91 | 28838.19 | 968823.02 | 8779131.44 | 34259367.35 | 0.122393E+09 | 3592.31 | 0.36 |
November | 40928715.66 | 562252.81 | 2911.49 | 684458.48 | 161730.08 | 0.204791E+09 | 0.142840E+09 | 964.42 | 0.35 |
December | 34853017.11 | 825976.10 | 6583.68 | 500627.58 | 315387.27 | 0.314651E+09 | 0.102936E+09 | 2204.36 | 0.35 |
Annual Sum or Average | 0.541776E+09 | 0.199115E+09 | 110711.35 | 15480221.95 | 42663534.64 | 0.149000E+10 | 0.142947E+10 | 14323.66 | 0.36 |
Minimum of Months | 26334544.78 | 143277.95 | 0.00 | 500627.58 | 16719.58 | 28284.24 | 18367121.95 | 0.00 | 0.35 |
Maximum of Months | 74357964.49 | 70039295.86 | 31537.52 | 2510386.73 | 14722227.37 | 0.334559E+09 | 0.230588E+09 | 3592.31 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 8116256.74 | 5294886.00 | 12965.18 | 19603184.68 | 0.00 | 0.250074E+09 | 0.268936E+10 | 703.82 | 0.40 |
February | 26960571.36 | 2544975.80 | 0.00 | 14195938.30 | 0.00 | 0.165451E+09 | 0.235575E+10 | 0.00 | 0.40 |
March | 48240602.87 | 4497493.31 | 0.00 | 12732792.96 | 0.00 | 0.565855E+09 | 0.232562E+10 | 0.00 | 0.40 |
April | 10834717.43 | 11353595.08 | 0.00 | 15708694.72 | 0.00 | 80256768.69 | 0.190893E+10 | 0.00 | 0.40 |
May | 28628177.29 | 4491365.34 | 0.00 | 13162667.24 | 0.00 | 0.124162E+09 | 0.187601E+10 | 0.00 | 0.40 |
June | 13754760.01 | 70102652.47 | 0.00 | 12978022.98 | 297464.32 | 4435628.14 | 0.114428E+10 | 0.00 | 0.40 |
July | 0.00 | 0.418971E+09 | 0.00 | 11412578.85 | 0.00 | 1817212.91 | 0.516965E+09 | 0.00 | 0.40 |
August | 0.00 | 0.544725E+09 | 0.00 | 10232112.12 | 0.00 | 1092770.60 | 0.388507E+09 | 0.00 | 0.41 |
September | 2592884.96 | 0.166842E+09 | 0.00 | 15142953.53 | 4543619.46 | 3160236.71 | 0.869911E+09 | 0.00 | 0.41 |
October | 1788220.56 | 0.308264E+09 | 20251.50 | 16208384.00 | 257828.61 | 5580026.67 | 0.136801E+10 | 5018.29 | 0.40 |
November | 1970336.62 | 4676668.98 | 0.00 | 19591519.23 | 0.00 | 2990454.49 | 0.247644E+10 | 0.00 | 0.40 |
December | 9322027.33 | 7390001.35 | 0.00 | 20634924.05 | 0.00 | 95653748.57 | 0.278464E+10 | 0.00 | 0.40 |
Annual Sum or Average | 0.152209E+09 | 0.154915E+10 | 33216.69 | 0.181604E+09 | 5098912.39 | 0.130053E+10 | 0.207044E+11 | 5722.11 | 0.40 |
Minimum of Months | 0.00 | 2544975.80 | 0.00 | 10232112.12 | 0.00 | 1092770.60 | 0.388507E+09 | 0.00 | 0.40 |
Maximum of Months | 48240602.87 | 0.544725E+09 | 20251.50 | 20634924.05 | 4543619.46 | 0.565855E+09 | 0.278464E+10 | 5018.29 | 0.41 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.223845E+10 | 66355984.56 | 0.00 | 58177871.82 | 926423.05 | 0.00 | 0.491917E+11 | 0.00 | 4.59 |
February | 0.982248E+09 | 11523001.18 | 0.00 | 56598933.88 | 789716.94 | 0.00 | 0.465888E+11 | 0.00 | 4.71 |
March | 0.158428E+10 | 0.00 | 0.00 | 62794074.93 | 114744.14 | 0.00 | 0.522594E+11 | 0.00 | 4.68 |
April | 0.301217E+09 | 67740756.94 | 0.00 | 77737016.53 | 1321400.35 | 0.00 | 0.449127E+11 | 0.00 | 4.89 |
May | 0.186941E+09 | 9630981.65 | 0.00 | 85487267.79 | 219934.58 | 0.00 | 0.459142E+11 | 0.00 | 4.96 |
June | 49130763.50 | 0.495959E+09 | 0.00 | 91132350.11 | 196288.69 | 0.00 | 0.356844E+11 | 0.00 | 5.13 |
July | 4654141.19 | 0.419904E+10 | 0.00 | 82872748.13 | 9638780.25 | 0.00 | 0.238334E+11 | 0.00 | 5.21 |
August | 28636216.76 | 0.494159E+10 | 0.00 | 72316059.14 | 37957110.11 | 0.00 | 0.204813E+11 | 0.00 | 5.21 |
September | 0.130614E+09 | 0.159571E+10 | 0.00 | 78292517.44 | 16082918.32 | 0.00 | 0.305203E+11 | 0.00 | 5.09 |
October | 0.123953E+09 | 0.278951E+10 | 0.00 | 71170851.71 | 20707963.67 | 0.00 | 0.320896E+11 | 0.00 | 5.05 |
November | 0.651214E+09 | 45479324.32 | 0.00 | 63935725.38 | 51565.93 | 0.00 | 0.481604E+11 | 0.00 | 4.76 |
December | 0.110244E+10 | 21613401.76 | 0.00 | 60563245.37 | 2232984.12 | 0.00 | 0.498803E+11 | 0.00 | 4.62 |
Annual Sum or Average | 0.738378E+10 | 0.142442E+11 | 0.00 | 0.861079E+09 | 90239830.14 | 0.00 | 0.479516E+12 | 0.00 | 4.91 |
Minimum of Months | 4654141.19 | 0.00 | 0.00 | 56598933.88 | 51565.93 | 0.00 | 0.204813E+11 | 0.00 | 4.59 |
Maximum of Months | 0.223845E+10 | 0.494159E+10 | 0.00 | 91132350.11 | 37957110.11 | 0.00 | 0.522594E+11 | 0.00 | 5.21 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.109719E+10 | 70818377.19 | 0.00 | 74034765.80 | 0.00 | 0.00 | 0.545365E+11 | 0.00 | 4.95 |
February | 0.162554E+09 | 12903402.37 | 0.00 | 71246362.17 | 8593.35 | 0.00 | 0.515550E+11 | 0.00 | 5.11 |
March | 0.414296E+09 | 120328.90 | 0.00 | 79145742.97 | 0.00 | 0.00 | 0.579962E+11 | 0.00 | 5.06 |
April | 5061627.90 | 72853733.38 | 0.00 | 93149252.45 | 0.00 | 0.00 | 0.491566E+11 | 0.00 | 5.30 |
May | 2359719.33 | 10408319.76 | 0.00 | 0.101639E+09 | 0.00 | 0.00 | 0.501210E+11 | 0.00 | 5.37 |
June | 0.00 | 0.526175E+09 | 0.00 | 0.104956E+09 | 0.00 | 0.00 | 0.386339E+11 | 0.00 | 5.54 |
July | 0.00 | 0.452538E+10 | 0.00 | 92562799.33 | 0.00 | 0.00 | 0.255951E+11 | 0.00 | 5.60 |
August | 0.00 | 0.532356E+10 | 0.00 | 80023597.17 | 0.00 | 0.00 | 0.219689E+11 | 0.00 | 5.58 |
September | 2148153.83 | 0.172057E+10 | 0.00 | 89850214.71 | 0.00 | 0.00 | 0.330464E+11 | 0.00 | 5.48 |
October | 20760031.36 | 0.299608E+10 | 0.00 | 81308990.54 | 1669419.04 | 0.00 | 0.347127E+11 | 0.00 | 5.43 |
November | 95614798.54 | 48219914.34 | 0.00 | 79188188.69 | 0.00 | 0.00 | 0.528898E+11 | 0.00 | 5.14 |
December | 0.317963E+09 | 24589962.94 | 0.00 | 76746276.95 | 417060.65 | 0.00 | 0.549177E+11 | 0.00 | 4.98 |
Annual Sum or Average | 0.211795E+10 | 0.153317E+11 | 0.00 | 0.102385E+10 | 2095073.05 | 0.00 | 0.525130E+12 | 0.00 | 5.30 |
Minimum of Months | 0.00 | 120328.90 | 0.00 | 71246362.17 | 0.00 | 0.00 | 0.219689E+11 | 0.00 | 4.95 |
Maximum of Months | 0.109719E+10 | 0.532356E+10 | 0.00 | 0.104956E+09 | 1669419.04 | 0.00 | 0.579962E+11 | 0.00 | 5.60 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.128536E+09 | 0.00 | 0.125926E+09 | 0.00 | 0.00 | 0.697667E+11 | 0.00 | 21.69 |
February | 0.00 | 23589400.13 | 0.00 | 0.113289E+09 | 0.00 | 0.00 | 0.644422E+11 | 0.00 | 22.01 |
March | 17988514.34 | 219986.89 | 0.00 | 0.124888E+09 | 0.00 | 0.00 | 0.728999E+11 | 0.00 | 21.90 |
April | 0.00 | 0.132304E+09 | 0.00 | 0.138578E+09 | 0.00 | 0.00 | 0.578176E+11 | 0.00 | 22.41 |
May | 0.00 | 18853229.10 | 0.00 | 0.146816E+09 | 0.00 | 0.00 | 0.581578E+11 | 0.00 | 22.43 |
June | 0.00 | 0.934010E+09 | 0.00 | 0.143370E+09 | 0.00 | 0.00 | 0.426656E+11 | 0.00 | 22.64 |
July | 0.00 | 0.772838E+10 | 0.00 | 0.115488E+09 | 0.00 | 0.00 | 0.263041E+11 | 0.00 | 22.76 |
August | 0.00 | 0.929686E+10 | 0.00 | 96376145.27 | 0.00 | 0.00 | 0.220056E+11 | 0.00 | 22.80 |
September | 0.00 | 0.290405E+10 | 0.00 | 0.125187E+09 | 0.00 | 0.00 | 0.370316E+11 | 0.00 | 22.68 |
October | 0.00 | 0.512048E+10 | 0.00 | 0.111867E+09 | 0.00 | 0.00 | 0.385972E+11 | 0.00 | 22.52 |
November | 4383145.51 | 85664555.22 | 0.00 | 0.125054E+09 | 0.00 | 0.00 | 0.647077E+11 | 0.00 | 22.15 |
December | 8921803.90 | 45621893.39 | 0.00 | 0.127052E+09 | 0.00 | 0.00 | 0.688947E+11 | 0.00 | 21.82 |
Annual Sum or Average | 31293463.75 | 0.264186E+11 | 0.00 | 0.149389E+10 | 0.00 | 0.00 | 0.623291E+12 | 0.00 | 22.32 |
Minimum of Months | 0.00 | 219986.89 | 0.00 | 96376145.27 | 0.00 | 0.00 | 0.220056E+11 | 0.00 | 21.69 |
Maximum of Months | 17988514.34 | 0.929686E+10 | 0.00 | 0.146816E+09 | 0.00 | 0.00 | 0.728999E+11 | 0.00 | 22.80 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.154875E+11 | 0.00 | 0.00 | 0.00 | 22367693.73 | 0.00 | 0.00 | 0.00 | 1.11 |
February | 0.138810E+11 | 0.00 | 0.00 | 0.00 | 4093300.43 | 0.00 | 0.00 | 0.00 | 1.12 |
March | 0.159165E+11 | 0.00 | 0.00 | 0.00 | 38146.10 | 0.00 | 0.00 | 0.00 | 1.12 |
April | 0.124806E+11 | 0.00 | 0.00 | 0.00 | 22952277.51 | 0.00 | 0.00 | 0.00 | 1.12 |
May | 0.125493E+11 | 0.00 | 0.00 | 0.00 | 3274886.93 | 0.00 | 0.00 | 0.00 | 1.12 |
June | 0.928097E+10 | 0.00 | 0.00 | 0.00 | 0.162100E+09 | 0.00 | 0.00 | 0.00 | 1.13 |
July | 0.596564E+10 | 26828706.04 | 0.00 | 0.00 | 0.131417E+10 | 0.00 | 0.00 | 0.00 | 1.13 |
August | 0.506383E+10 | 0.134727E+09 | 0.00 | 384.89 | 0.147829E+10 | 0.00 | 95750.14 | 0.00 | 1.13 |
September | 0.807072E+10 | 0.172589E+09 | 0.00 | 30495.21 | 0.342627E+09 | 0.00 | 20089513.88 | 0.00 | 1.13 |
October | 0.844365E+10 | 0.364757E+09 | 0.00 | 59457.16 | 0.538663E+09 | 0.00 | 0.110438E+09 | 0.00 | 1.13 |
November | 0.139832E+11 | 0.00 | 0.00 | 0.00 | 14906700.35 | 0.00 | 0.00 | 0.00 | 1.12 |
December | 0.151765E+11 | 0.00 | 0.00 | 0.00 | 7927609.53 | 0.00 | 0.00 | 0.00 | 1.11 |
Annual Sum or Average | 0.136299E+12 | 0.698902E+09 | 0.00 | 90337.26 | 0.391142E+10 | 0.00 | 0.130623E+09 | 0.00 | 1.12 |
Minimum of Months | 0.506383E+10 | 0.00 | 0.00 | 0.00 | 38146.10 | 0.00 | 0.00 | 0.00 | 1.11 |
Maximum of Months | 0.159165E+11 | 0.364757E+09 | 0.00 | 59457.16 | 0.147829E+10 | 0.00 | 0.110438E+09 | 0.00 | 1.13 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.160043E+12 | 0.433629E+10 | 0.124845E+12 | 0.505820E+12 | 0.222773E+12 |
February | 0.209135E+12 | 0.385413E+10 | 0.115929E+12 | 0.457796E+12 | 0.165091E+12 |
March | 0.298193E+12 | 0.435765E+10 | 0.132145E+12 | 0.522121E+12 | 0.181512E+12 |
April | 0.387434E+12 | 0.357011E+10 | 0.102098E+12 | 0.412668E+12 | 0.241922E+12 |
May | 0.415826E+12 | 0.382282E+10 | 0.103352E+12 | 0.417584E+12 | 0.239918E+12 |
June | 0.410269E+12 | 0.289451E+10 | 0.757646E+11 | 0.300525E+12 | 0.339133E+12 |
July | 0.434648E+12 | 0.121288E+10 | 0.357631E+11 | 0.147059E+12 | 0.604429E+12 |
August | 0.394824E+12 | 0.792095E+09 | 0.254933E+11 | 0.107892E+12 | 0.671329E+12 |
September | 0.310478E+12 | 0.227027E+10 | 0.613739E+11 | 0.245468E+12 | 0.444261E+12 |
October | 0.211444E+12 | 0.239624E+10 | 0.587486E+11 | 0.256195E+12 | 0.501902E+12 |
November | 0.176530E+12 | 0.398221E+10 | 0.112008E+12 | 0.463420E+12 | 0.222643E+12 |
December | 0.140259E+12 | 0.435126E+10 | 0.121752E+12 | 0.499380E+12 | 0.241520E+12 |
Annual Sum or Average | 0.354909E+13 | 0.378405E+11 | 0.106927E+13 | 0.433593E+13 | 0.407643E+13 |
Minimum of Months | 0.140259E+12 | 0.792095E+09 | 0.254933E+11 | 0.107892E+12 | 0.165091E+12 |
Maximum of Months | 0.434648E+12 | 0.435765E+10 | 0.132145E+12 | 0.522121E+12 | 0.671329E+12 |