Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:24
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440
Simulation Timestamp: 2024-07-03 12:24:56
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:56
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 11919.83 | 1050.64 | 1050.64 |
Net Site Energy | 11919.83 | 1050.64 | 1050.64 |
Total Source Energy | 23259.98 | 2050.19 | 2050.19 |
Net Source Energy | 23259.98 | 2050.19 | 2050.19 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 2265.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 580.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 781.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 193.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1658.18 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 813.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 515.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 79.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 183.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 94.79 | 2901.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | 61.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 4963.46 | 6956.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 2265.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 580.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 781.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 193.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 872.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 14.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 8.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 21.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 789.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 2.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 515.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 79.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 183.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 94.79 | 2901.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5742.51 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.69 | |
Refrigeration | General | 7.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 20.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 34.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 2265.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 580.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 781.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 193.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 1658.18 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 813.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 515.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 79.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 183.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 94.79 | 2901.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | Unassigned | 61.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 85.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 112.05 | 455.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 239.48 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 437.49 | 613.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 85.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 112.05 | 455.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 239.48 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 437.49 | 613.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 4963.459 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 4963.459 | 100.00 |
Total On-Site and Utility Electric Sources | 4963.459 | 100.00 |
Total Electricity End Uses | 4963.459 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 223.76 | 4.68 |
Air to Air Heat Recovery for Heating | 4558.40 | 95.32 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 4782.15 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9857.19 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9857.19 | 100.00 |
Total Water End Uses | 9857.19 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 280.83 |
Time Setpoint Not Met During Occupied Cooling | 44.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 7993.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER1 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| FLR_3_DOAS COOLING COIL | VAV WITH REHEAT COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH LAUNDRY G WATER HEATER | SWH BOOSTER E WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |CoilReportMonthly
| FLR_3_DOAS HEATING COIL | VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | FLR_3_DOAS COOLING COIL | VAV WITH REHEAT COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |FanReportMonthly
| FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL_FANCOILFAN | ROOM_2_FLR_3 FAN COIL_FANCOILFAN | ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | ROOM_5_FLR_3 FAN COIL_FANCOILFAN | ROOM_6_FLR_3 FAN COIL_FANCOILFAN | ROOM_1_FLR_6 FAN COIL_FANCOILFAN | ROOM_2_FLR_6 FAN COIL_FANCOILFAN | ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| FLR_3_DOAS | VAV WITH REHEAT |AirLoopSystemComponentLoadsMonthly
| FLR_3_DOAS | VAV WITH REHEAT |AirLoopSystemComponentEnergyUseMonthly
| FLR_3_DOAS | VAV WITH REHEAT |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:56
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:24 |
RunPeriod | RUNPERIOD 1 |
Weather File | Rochester International Arpt MN USA TMY3 WMO#=726440 |
Latitude [deg] | 43.90 |
Longitude [deg] | -92.5 |
Elevation [m] | 398.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 8.8143 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.26 | 23.26 | 11.3140 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 11.3140 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 4.6285 | 61.93 | 5.3800 |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 5.7199 | 46.45 | 2.6900 |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 4.6285 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.50 | 65.50 | 10.0104 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.08 | 85.08 | 10.7639 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 8.2882 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 8.2882 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 7.1042 | 18.58 | 0.0000 |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.74 | 6.74 | 8.2882 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 10.0104 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 10.0104 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.37 | 26.37 | 11.4097 | 4.65 | 2934.4875 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.20 | 28.20 | 7.1042 | 18.58 | 0.0000 |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 8.5566 | 7.07 | 41.0709 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 8.5566 | 7.07 | 41.0709 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 1978.83 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 8.8143 | 18.58 | 5.3800 | |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 1.00 | RETAIL_1_FLR_1 | GENERAL | RETAIL_1_FLR_1 | 11.3140 | 6.19 | 10.7600 | |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 1.00 | RETAIL_2_FLR_1 | GENERAL | RETAIL_2_FLR_1 | 11.3140 | 6.19 | 10.7600 | |
MECH_FLR_1 | 164.24 | Yes | Yes | 1.00 | MECH_FLR_1 | GENERAL | MECH_FLR_1 | 4.6285 | 61.93 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 1.00 | STORAGE_FLR_1 | GENERAL | STORAGE_FLR_1 | 5.7199 | 46.45 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 1.00 | LAUNDRY_FLR_1 | GENERAL | LAUNDRY_FLR_1 | 4.6285 | 9.29 | 597.5300 | |
CAFE_FLR_1 | 188.86 | Yes | Yes | 1.00 | CAFE_FLR_1 | GENERAL | CAFE_FLR_1 | 10.0104 | 1.33 | 5.3800 | |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 1.00 | LOBBY_FLR_1 | GENERAL | LOBBY_FLR_1 | 10.7639 | 3.10 | 8.0700 | |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_1_FLR_3 | GENERAL | ROOM_1_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_2_FLR_3 | GENERAL | ROOM_2_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 76.00 | ROOM_3_MULT19_FLR_3 | GENERAL | ROOM_3_MULT19_FLR_3 | 8.2882 | 16.35 | 10.5200 | |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 76.00 | ROOM_4_MULT19_FLR_3 | GENERAL | ROOM_4_MULT19_FLR_3 | 8.2882 | 16.35 | 10.5200 | |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_5_FLR_3 | GENERAL | ROOM_5_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_6_FLR_3 | GENERAL | ROOM_6_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 4.00 | CORRIDOR_FLR_3 | GENERAL | CORRIDOR_FLR_3 | 7.1042 | 18.58 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_1_FLR_6 | GENERAL | ROOM_1_FLR_6 | 8.2882 | 26.01 | 6.7500 | |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_2_FLR_6 | GENERAL | ROOM_2_FLR_6 | 8.2882 | 26.01 | 6.7500 | |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 9.00 | ROOM_3_MULT9_FLR_6 | GENERAL | ROOM_3_MULT9_FLR_6 | 8.2882 | 16.35 | 10.5200 | |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1.00 | BANQUET_FLR_6 | GENERAL | BANQUET_FLR_6 | 10.0104 | 1.33 | 67.8200 | |
DINING_FLR_6 | 331.66 | Yes | Yes | 1.00 | DINING_FLR_6 | GENERAL | DINING_FLR_6 | 10.0104 | 1.33 | 67.8200 | |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 1.00 | KITCHEN_FLR_6 | GENERAL | KITCHEN_FLR_6 | 11.4097 | 4.65 | 2934.4875 | |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1.00 | CORRIDOR_FLR_6 | GENERAL | CORRIDOR_FLR_6 | 7.1042 | 18.58 | 0.0000 | |
Total | 11345.29 | 8.5566 | 3.54 | 41.0709 | |||||||
Conditioned Total | 11345.29 | 8.5566 | 3.54 | 41.0709 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 11345.29 | 11345.29 | 0.00 | 0.00 | 4.6520 | 8.82 | 37.1989 |
Total | 11345.29 | 11345.29 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:56
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 26-JUL-18:30 | 02-FEB-21:30 | - | - | - | - | - | - | - | - | - | - | 05-JAN-21:19 |
Heating | 0.00 | 731074.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 196657.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 53184.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 77573.37 | 75123.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 28166.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 25445.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 4705.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 4751.04 | 269426.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 2419.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 402842.58 | 1075624.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 731074.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 196657.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 53184.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 47590.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 37635.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1047.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 26968.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 150.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 25445.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 4705.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 4751.04 | 269426.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 228.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 1094.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1096.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:56
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 2456.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1838.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2475.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 613.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5251.45 | 1939.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2577.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1633.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 253.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 581.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 300.20 | 3145.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 194.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 15719.27 | 7540.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 216.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 162.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 218.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 54.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 462.88 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 227.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 144.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 22.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 51.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 26.46 | 277.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1385.53 | 664.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 216.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 162.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 218.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 54.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 462.88 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 227.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 144.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 22.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 51.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 26.46 | 277.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1385.53 | 664.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:56
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
BASEMENT VAV BOX COMPONENT | 2.57 | 0.586188 | 0.506000 | 1.30 | 1.00 | 0.500000 | 0.000650 | 0.000071 | 1.30 | 16.70 | 0.008000 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.398467 | 0.128263 | 0.506000 | 0.201624 | 0.506000 | 0.500000 | 0.002970 | 0.000041 | 0.201624 | 16.70 | 0.008000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.235836 | 0.250953 | 0.506000 | 0.119333 | 0.669207 | 0.500000 | 0.001518 | 0.000015 | 0.119333 | 16.70 | 0.008000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.185190 | 0.675811 | 0.506000 | 0.093706 | 1.00 | 0.500000 | 0.000564 | 0.000022 | 0.093706 | 16.70 | 0.008000 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.110662 | 0.652495 | 0.506000 | 0.055995 | 1.00 | 0.500000 | 0.000584 | 0.000016 | 0.066603 | 16.70 | 0.008000 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 3.41 | 0.017461 | 0.506000 | 1.72 | 0.506000 | 0.500000 | 0.021820 | 0.000099 | 1.72 | 16.70 | 0.008000 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.65 | 0.087043 | 0.506000 | 0.836593 | 0.506000 | 0.500000 | 0.004377 | 0.000118 | 0.836593 | 16.70 | 0.008000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 5.12 | 0.194568 | 0.506000 | 2.59 | 0.518848 | 0.500000 | 0.001958 | 0.000297 | 2.59 | 16.70 | 0.008000 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.62 | 0.731167 | 0.506000 | 0.821392 | 1.00 | 0.500000 | 0.000521 | 0.000146 | 0.821392 | 16.70 | 0.008000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.23 | 0.113390 | 0.506000 | 1.13 | 0.506000 | 0.500000 | 0.003360 | 0.000122 | 1.13 | 16.70 | 0.008000 |
DINING_FLR_6 VAV BOX COMPONENT | 2.34 | 0.108163 | 0.506000 | 1.18 | 0.506000 | 0.500000 | 0.003522 | 0.000126 | 1.18 | 16.70 | 0.008000 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.37 | 0.059787 | 0.506000 | 1.20 | 0.506000 | 0.500000 | 0.011462 | 0.000082 | 1.20 | 16.70 | 0.008000 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 0.797780 | 0.393641 | 0.506000 | 0.403677 | 1.00 | 0.500000 | 0.000968 | 0.000093 | 0.403677 | 16.70 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
BASEMENT VAV BOX REHEAT COIL | 8144.24 | 0.000071 | 172.00 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 4644.29 | 0.000041 | 119.49 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1756.94 | 0.000015 | 40.75 |
MECH_FLR_1 VAV BOX REHEAT COIL | 2503.38 | 0.000022 | 67.76 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 1817.34 | 0.000016 | 49.60 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 11362.85 | 0.000099 | 240.82 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 13522.25 | 0.000118 | 319.00 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 33993.08 | 0.000297 | 773.74 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | 8040.39 | 0.000070 | 229.74 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | 8060.73 | 0.000071 | 230.32 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 45677.70 | 0.000400 | 1305.14 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 46060.80 | 0.000403 | 1316.08 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | 7999.26 | 0.000070 | 228.56 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | 8019.61 | 0.000070 | 229.14 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 16739.82 | 0.000146 | 416.03 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | 2471.34 | 0.000022 | 70.61 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | 2478.91 | 0.000022 | 70.83 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 11788.13 | 0.000103 | 336.81 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 13932.12 | 0.000122 | 314.39 |
DINING_FLR_6 VAV BOX REHEAT COIL | 14376.36 | 0.000126 | 323.70 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 9373.98 | 0.000082 | 201.27 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 10678.24 | 0.000093 | 287.97 |
FLR_3_DOAS HEATING COIL | 30469.72 | 0.000267 | 443.51 |
VAV WITH REHEAT HEATING COIL | 340282.36 | 0.002977 | 4953.02 |
Design Size Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 0.061735 |
ROOM_2_FLR_3 DIRECT AIR | 0.061728 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 0.837072 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 0.837300 |
ROOM_5_FLR_3 DIRECT AIR | 0.061735 |
ROOM_6_FLR_3 DIRECT AIR | 0.061728 |
ROOM_1_FLR_6 DIRECT AIR | 0.015434 |
ROOM_2_FLR_6 DIRECT AIR | 0.015432 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 0.099154 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Hot Water Flow [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 1.24 | 0.000070 | 0.000382 |
ROOM_2_FLR_3 FAN COIL | 1.20 | 0.000071 | 0.000371 |
ROOM_3_MULT19_FLR_3 FAN COIL | 7.46 | 0.000400 | 0.002258 |
ROOM_4_MULT19_FLR_3 FAN COIL | 6.31 | 0.000403 | 0.002036 |
ROOM_5_FLR_3 FAN COIL | 1.13 | 0.000070 | 0.000349 |
ROOM_6_FLR_3 FAN COIL | 1.10 | 0.000070 | 0.000340 |
ROOM_1_FLR_6 FAN COIL | 0.322218 | 0.000022 | 0.000099 |
ROOM_2_FLR_6 FAN COIL | 0.311738 | 0.000022 | 0.000096 |
ROOM_3_MULT9_FLR_6 FAN COIL | 1.48 | 0.000103 | 0.000464 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COIL_FANCOILFAN | 1.24 |
ROOM_2_FLR_3 FAN COIL_FANCOILFAN | 1.20 |
ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | 7.46 |
ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | 6.31 |
ROOM_5_FLR_3 FAN COIL_FANCOILFAN | 1.13 |
ROOM_6_FLR_3 FAN COIL_FANCOILFAN | 1.10 |
ROOM_1_FLR_6 FAN COIL_FANCOILFAN | 0.322218 |
ROOM_2_FLR_6 FAN COIL_FANCOILFAN | 0.311738 |
ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN | 1.48 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Coil Load [W] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | 21.71 | 6.70 | 0.008615 | 12.80 | 0.008500 | 0.000382 | 1.24 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | 21.71 | 6.70 | 0.008618 | 12.80 | 0.008500 | 0.000371 | 1.20 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 21.71 | 6.70 | 0.008547 | 12.80 | 0.008500 | 0.002258 | 7.46 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 21.71 | 6.70 | 0.008787 | 12.80 | 0.008500 | 0.002036 | 6.31 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | 21.71 | 6.70 | 0.008627 | 12.80 | 0.008500 | 0.000349 | 1.13 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | 21.71 | 6.70 | 0.008631 | 12.80 | 0.008500 | 0.000340 | 1.10 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | 21.71 | 6.70 | 0.008611 | 12.80 | 0.008500 | 0.000099 | 0.322218 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | 21.71 | 6.70 | 0.008614 | 12.80 | 0.008500 | 0.000096 | 0.311738 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 21.71 | 6.70 | 0.008668 | 12.80 | 0.008500 | 0.000464 | 1.48 | |
FLR_3_DOAS COOLING COIL | 31.20 | 6.70 | 0.015365 | 11.90 | 0.008500 | 0.002511 | 2.05 | 87803.64 |
VAV WITH REHEAT COOLING COIL | 27.66 | 6.70 | 0.012568 | 10.90 | 0.008500 | 0.020684 | 22.91 | 723208.74 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
VAV WITH REHEAT | 11.66 | 11.66 | 23.04 | 11.66 | 22.91 | 22.91 | 0.300000 | 0.508880 | 22.91 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
VAV WITH REHEAT_OA_CONTROLLER | 22.91 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
FLR_3_DOAS OA HEAT RECOVERY | 2.05 |
VAV WITH REHEAT OA HEAT RECOVERY | 11.66 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS FAN | 2.05 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.002511 | 0.000190 |
FLR_3_DOAS_HEATC_CONTROLLER | 0.000267 | |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.020684 | 0.000023 |
VAV WITH REHEAT_HEATC_CONTROLLER | 0.002977 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT FAN | 22.91 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.029590 | 4831.14 | |
HEATSYS1 PUMP | 0.005723 | 1723.57 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.005723 | 0.686781 |
COOLSYS1 | 0.029590 | 3.55 |
SWHSYS1 | 0.000375 | 0.045004 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 654193.82 | 654193.82 | 0.005723 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.029590 | 3344.76 |
SWHSYS1 PUMP | 0.000375 | 47.91 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.029590 | 1034619.02 | 1035245.02 | 118.02 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000375 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:56
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:56
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:56
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 7.40 | -0.00 | -7.60 | -12.60 | -7.70 | 0.30 | 7.00 | 14.20 | 19.20 | 20.90 | 20.00 | 15.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Rochester International Arpt MN USA TMY3 WMO#=726440 | 43.90 | -92.50 | -6.00 | 398.00 | 96634 | 1.1486 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 6.38 | 33.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.58 | 23.26 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.72 | 65.50 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.80 | 85.08 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.70 | 6.74 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.96 | 26.37 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.27 | 28.20 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 8.814 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 14.194 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 11.314 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 22.074 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 11.314 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 22.074 | No |
4 | MECH_FLR_1 | 164.24 | 2.7 | 61.932 | 1.615E-002 | 4.628 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 10.008 | No |
5 | STORAGE_FLR_1 | 94.76 | 2.0 | 46.451 | 2.153E-002 | 5.720 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 8.410 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 4.628 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 602.158 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 10.010 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 15.390 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 10.764 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.834 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 8.288 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 18.808 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 8.288 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 18.808 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 21.0 | 18.581 | 5.382E-002 | 7.104 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.104 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 8.288 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 18.808 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 10.010 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 77.830 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 10.010 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 77.830 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 11.410 | 515.227 | 2419.260 | 0.000 | 0.000 | 0.000 | 2945.897 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 22.2 | 18.581 | 5.382E-002 | 7.104 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.104 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | STORAGE_FLR_1 PEOPLE | BLDG_OCC_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.0 | 2.153E-002 | 46.451 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | CORRIDOR_FLR_3 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 21.0 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 21 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
21 | CORRIDOR_FLR_6 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 22.2 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
22 | MECH_FLR_1 PEOPLE | BLDG_OCC_SCH | MECH_FLR_1 | 164.24 | 2.7 | 2.7 | 1.615E-002 | 61.932 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 3 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_BASEMENT | BASEMENT | 1978.83 | 106.5 | 17441.963 | 8.814 | 163.776 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 17441.963 |
2 | RETAIL_1_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_1_FLR_1 | 67.07 | 10.8 | 758.849 | 11.314 | 70.076 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 758.849 |
3 | RETAIL_2_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_2_FLR_1 | 77.67 | 12.5 | 878.750 | 11.314 | 70.076 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 878.750 |
4 | MECH_FLR_1_LIGHTS | LTG_SCH_MECHANIC | MECH_FLR_1 | 164.24 | 2.7 | 760.196 | 4.628 | 286.650 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 760.196 |
5 | STORAGE_FLR_1_LIGHTS | LTG_SCH_STORAGE | STORAGE_FLR_1 | 94.76 | 2.0 | 542.017 | 5.720 | 265.695 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 542.017 |
6 | LAUNDRY_FLR_1_LIGHTS | LTG_SCH_LAUNDRY | LAUNDRY_FLR_1 | 78.04 | 8.4 | 361.204 | 4.628 | 43.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 361.204 |
7 | CAFE_FLR_1_LIGHTS | LTG_SCH_DINING | CAFE_FLR_1 | 188.86 | 142.3 | 1890.589 | 10.010 | 13.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1890.589 |
8 | LOBBY_FLR_1_LIGHTS | LTG_SCH_LOBBY | LOBBY_FLR_1 | 1308.19 | 422.4 | 14081.185 | 10.764 | 33.333 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14081.185 |
9 | ROOM_1_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_3 | 39.02 | 1.5 | 323.422 | 8.288 | 215.615 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.422 |
10 | ROOM_2_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_3 | 39.02 | 1.5 | 323.384 | 8.288 | 215.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.384 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 203.259 | 8.288 | 135.506 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 203.259 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 203.314 | 8.288 | 135.543 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 203.314 |
13 | ROOM_5_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_5_FLR_3 | 39.02 | 1.5 | 323.422 | 8.288 | 215.615 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.422 |
14 | ROOM_6_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_6_FLR_3 | 39.02 | 1.5 | 323.384 | 8.288 | 215.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.384 |
15 | CORRIDOR_FLR_3_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2766.397 | 7.104 | 132.003 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2766.397 |
16 | ROOM_1_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_6 | 39.02 | 1.5 | 323.422 | 8.288 | 215.615 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.422 |
17 | ROOM_2_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_6 | 39.02 | 1.5 | 323.384 | 8.288 | 215.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.384 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 203.314 | 8.288 | 135.543 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 203.314 |
19 | BANQUET_FLR_6_LIGHTS | LTG_SCH_DINING | BANQUET_FLR_6 | 331.66 | 249.9 | 3320.034 | 10.010 | 13.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3320.034 |
20 | DINING_FLR_6_LIGHTS | LTG_SCH_DINING | DINING_FLR_6 | 331.66 | 249.9 | 3320.034 | 10.010 | 13.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3320.034 |
21 | KITCHEN_FLR_6_LIGHTS | LTG_SCH_KITCHEN | KITCHEN_FLR_6 | 103.30 | 22.2 | 1178.676 | 11.410 | 53.003 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1178.676 |
22 | CORRIDOR_FLR_6_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_6 | 412.12 | 22.2 | 2927.804 | 7.104 | 132.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2927.804 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 2.7 | 883.628 | 5.380 | 333.193 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 254.902 | 2.690 | 124.952 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 457.500 | 4.429 | 20.573 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 457.500 | 457.500 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 285.000 | 2.759 | 12.816 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 285.000 | 285.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 2.390 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
6 | RES_ROOF | 19 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
7 | NONRES_EXT_WALL_GRD | 21 | 3 | 9 | 0.167 | 0.6524 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | NONRES_EXT_WALL_MID | 22 | 3 | 9 | 0.167 | 0.8441 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | NONRES_EXT_WALL_TOP | 23 | 3 | 9 | 0.167 | 0.8569 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | RES_EXT_WALL_MID | 25 | 3 | 9 | 0.167 | 0.7799 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | RES_EXT_WALL_TOP | 26 | 3 | 9 | 0.167 | 0.7924 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | NONRES_FLOOR | 30 | 3 | 7 | 0.167 | 0.1901 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
13 | NONRES_FLOOR_CEILING | 33 | 3 | 7 | 0.167 | 0.1901 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
14 | BASEMENT_FLOOR | 36 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
15 | BASEMENT_WALL_NORTH_CFACTOR | 39 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | BASEMENT_WALL_EAST_CFACTOR | 40 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | BASEMENT_WALL_SOUTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
18 | BASEMENT_WALL_WEST_CFACTOR | 42 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4184 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
10 | RES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
11 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
12 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.365 |
14 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.017 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9996 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | RES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.115 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
25 | RES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 1.095 |
26 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
27 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.000 |
28 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
29 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
30 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
31 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
32 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.000 |
33 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
34 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
35 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
39 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
40 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
41 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
42 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 2.3900722 | 2.3900722 | 2.3900722 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
21 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
22 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
23 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
24 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
25 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
26 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
27 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
28 | 9 | -0.20756307E-14 | -0.33770914E-15 | -0.16263325E-09 | 0.36952592E-16 |
29 | 8 | 0.23685375E-07 | 0.88714462E-13 | 0.39655920E-03 | -0.26931086E-09 |
30 | 7 | -0.12800682E-01 | 0.45320291E-08 | -0.23890593E-01 | 0.14554843E-03 |
31 | 6 | 0.42054172 | 0.15673111E-05 | 0.48500809 | -0.49268323E-02 |
32 | 5 | -5.3387987 | 0.58223180E-04 | -4.5403777 | 0.65021910E-01 |
33 | 4 | 33.658449 | 0.47408857E-03 | 21.827556 | -0.43082749 |
34 | 3 | -112.62083 | 0.10289916E-02 | -56.389455 | 1.5353436 |
35 | 2 | 198.51314 | 0.57668395E-03 | 78.577213 | -2.9226634 |
36 | 1 | -171.67490 | 0.61354169E-04 | -55.459608 | 2.7545325 |
37 | 0 | 57.057407 | 0.34787598E-06 | 15.525360 | |
38 | 9 | -0.24257523E-14 | 0.33690592E-16 | -0.15372093E-09 | 0.39666009E-16 |
39 | 8 | 0.22436951E-07 | 0.11417013E-12 | 0.38367618E-03 | -0.25511586E-09 |
40 | 7 | -0.12417040E-01 | 0.58916776E-08 | -0.23338459E-01 | 0.14118628E-03 |
41 | 6 | 0.41011853 | 0.20479623E-05 | 0.47615013 | -0.48039676E-02 |
42 | 5 | -5.2370942 | 0.76414309E-04 | -4.4724296 | 0.63760808E-01 |
43 | 4 | 33.208666 | 0.62469949E-03 | 21.562156 | -0.42485549 |
44 | 3 | -111.66410 | 0.13607335E-02 | -55.864850 | 1.5215209 |
45 | 2 | 197.56520 | 0.76503996E-03 | 78.095736 | -2.9076095 |
46 | 1 | -171.32486 | 0.81633884E-04 | -55.318971 | 2.7483976 |
47 | 0 | 57.057407 | 0.46449959E-06 | 15.548073 | |
48 | 9 | -0.24053431E-14 | 0.30582108E-16 | -0.15312349E-09 | 0.40258954E-16 |
49 | 8 | 0.22353057E-07 | 0.11582316E-12 | 0.38280191E-03 | -0.25416195E-09 |
50 | 7 | -0.12390977E-01 | 0.59826426E-08 | -0.23300939E-01 | 0.14088992E-03 |
51 | 6 | 0.40941037 | 0.20803184E-05 | 0.47554760 | -0.47956200E-02 |
52 | 5 | -5.2301838 | 0.77645268E-04 | -4.4678046 | 0.63675121E-01 |
53 | 4 | 33.178102 | 0.63493787E-03 | 21.544084 | -0.42444968 |
54 | 3 | -111.59908 | 0.13833754E-02 | -55.829123 | 1.5205815 |
55 | 2 | 197.50076 | 0.77794062E-03 | 78.062960 | -2.9065863 |
56 | 1 | -171.30107 | 0.83027327E-04 | -55.309421 | 2.7479805 |
57 | 0 | 57.057407 | 0.47253235E-06 | 15.549635 | |
58 | 9 | -0.46044427E-14 | 0.27900089E-16 | -0.15673021E-09 | 0.84433218E-16 |
59 | 8 | 0.22857479E-07 | 0.10577188E-12 | 0.38804207E-03 | -0.25989740E-09 |
60 | 7 | -0.12547140E-01 | 0.54349272E-08 | -0.23525725E-01 | 0.14266556E-03 |
61 | 6 | 0.41365335 | 0.18858798E-05 | 0.47915629 | -0.48456347E-02 |
62 | 5 | -5.2715868 | 0.70260405E-04 | -4.4954992 | 0.64188504E-01 |
63 | 4 | 33.361217 | 0.57360532E-03 | 21.652286 | -0.42688098 |
64 | 3 | -111.98862 | 0.12479141E-02 | -56.043016 | 1.5262094 |
65 | 2 | 197.88677 | 0.70084509E-03 | 78.259217 | -2.9127162 |
66 | 1 | -171.44362 | 0.74708721E-04 | -55.366651 | 2.7504789 |
67 | 0 | 57.057407 | 0.42455547E-06 | 15.540314 | |
68 | 9 | -0.14490010E-14 | 0.30537737E-16 | -0.15613140E-09 | 0.37153042E-16 |
69 | 8 | 0.22775399E-07 | 0.10742354E-12 | 0.38719206E-03 | -0.25896410E-09 |
70 | 7 | -0.12521818E-01 | 0.55241817E-08 | -0.23489278E-01 | 0.14237764E-03 |
71 | 6 | 0.41296535 | 0.19175017E-05 | 0.47857136 | -0.48375248E-02 |
72 | 5 | -5.2648734 | 0.71459421E-04 | -4.4910111 | 0.64105260E-01 |
73 | 4 | 33.331527 | 0.58354868E-03 | 21.634754 | -0.42648676 |
74 | 3 | -111.92546 | 0.12698472E-02 | -56.008360 | 1.5252969 |
75 | 2 | 197.82418 | 0.71331385E-03 | 78.227414 | -2.9117223 |
76 | 1 | -171.42051 | 0.76052751E-04 | -55.357370 | 2.7500739 |
77 | 0 | 57.057407 | 0.43228786E-06 | 15.541820 | |
78 | 7 | -0.16359629E-14 | -0.14530353E-16 | -0.22331004E-13 | 0.54056000E-15 |
79 | 6 | 0.18262352E-10 | 0.22801053E-11 | 0.52333849E-09 | -0.18642118E-10 |
80 | 5 | -0.59540244E-07 | 0.11129510E-07 | -0.21928235E-05 | 0.17164558E-06 |
81 | 4 | 0.60861605E-04 | 0.41961443E-05 | 0.17683552E-02 | -0.28248824E-03 |
82 | 3 | -0.87523238E-02 | 0.14809838E-03 | -0.21562890 | 0.43346081E-01 |
83 | 2 | 0.12409989 | 0.64146884E-03 | 2.9009744 | -0.61915653 |
84 | 1 | -0.31397648 | 0.40472017E-03 | -7.1381115 | 1.5697592 |
85 | 0 | 0.19977219 | 0.56546383E-05 | 4.4522022 | |
86 | 7 | -0.22331004E-13 | -0.14530353E-16 | -0.16359629E-14 | 0.54056000E-15 |
87 | 6 | 0.52333849E-09 | 0.22801053E-11 | 0.18262352E-10 | -0.18642118E-10 |
88 | 5 | -0.21928235E-05 | 0.11129510E-07 | -0.59540244E-07 | 0.17164558E-06 |
89 | 4 | 0.17683552E-02 | 0.41961443E-05 | 0.60861605E-04 | -0.28248824E-03 |
90 | 3 | -0.21562890 | 0.14809838E-03 | -0.87523238E-02 | 0.43346081E-01 |
91 | 2 | 2.9009744 | 0.64146884E-03 | 0.12409989 | -0.61915653 |
92 | 1 | -7.1381115 | 0.40472017E-03 | -0.31397648 | 1.5697592 |
93 | 0 | 4.4522022 | 0.56546383E-05 | 0.19977219 | |
94 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
95 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
96 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
97 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
98 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
99 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
100 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
101 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
102 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
103 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
104 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
105 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
106 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
107 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
108 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
109 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 | |
110 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
111 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
112 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
113 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
114 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
115 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
116 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
117 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 | |
118 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
119 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
120 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
121 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
122 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
123 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
124 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
125 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 | |
126 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
127 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
128 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
129 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
130 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
131 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
132 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
133 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.361_SHGC_0.4 | 37 | 1 | VerySmooth | 2.051 | 2.051 | 1.000 | 0.401 | ||
2 | RESWINDOW_U_0.361_SHGC_0.4 | 38 | 1 | VerySmooth | 2.051 | 2.051 | 1.000 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 3.64640E-002 | 0.31435 | 0.48144 | 0.48144 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.11581 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 3.64640E-002 | 0.31435 | 0.48144 | 0.48144 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.11581 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | CAFE_FLR_1 | 1 | 0 |
2 | LOBBY_FLR_1 | 1 | 0 |
3 | BANQUET_FLR_6 | 1 | 0 |
4 | DINING_FLR_6 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | CAFE_FLR_1 | 0 | |
2 | LOBBY_FLR_1 | 0 | |
3 | BANQUET_FLR_6 | 0 | |
4 | DINING_FLR_6 | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH LAUNDRY G WATER HEATER | 1.1356 | 163316.0 | 11.511 | 0.4388 |
2 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.219 | 1.1187 |
3 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 2.2712 | 175842.6 | 5.775 | 0.3748 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 1.764E-002 | 2.631E-004 | 1.298E-004 | 0.239 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.811E-003 | 8.769E-005 | 2.388E-004 | 7.967E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 2.7 | 1.610E-002 | 9.800E-005 | 2.563E-004 | 8.904E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 9.287E-003 | 9.800E-005 | 2.127E-004 | 8.904E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 2.198E-002 | 2.816E-004 | 2.506E-004 | 0.256 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 3.900E-002 | 2.065E-004 | 1.137E-004 | 0.188 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 0.111 | 8.519E-005 | 1.629E-004 | 7.740E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 2.563E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 2.563E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 2.857E-003 | 1.165E-004 | 2.563E-004 | 0.138 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 2.858E-003 | 1.165E-004 | 2.563E-004 | 0.138 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 2.563E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 2.563E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 1.238E-002 | 3.180E-005 | 2.563E-004 | 3.755E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 1.297E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 1.297E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 5.239E-003 | 2.136E-004 | 1.165E-004 | 0.252 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 2.500E-002 | 7.539E-005 | 5.825E-005 | 8.904E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 2.500E-002 | 7.539E-005 | 5.825E-005 | 8.904E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 2.238E-002 | 2.167E-004 | 1.174E-004 | 0.256 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 2.191E-002 | 5.316E-005 | 4.403E-005 | 6.278E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1649 |
2 | Clear Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 8.6465E-002 |
3 | Clear Turbid Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1866 |
4 | Clear Turbid Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 9.8510E-002 |
5 | Intermediate Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1147 |
6 | Intermediate Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 4.5344E-002 |
7 | Overcast Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 4.6285E-002 |
8 | Overcast Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 1.5376E-002 |
9 | Clear Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1873 |
10 | Clear Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 0.1039 |
11 | Clear Turbid Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.2126 |
12 | Clear Turbid Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 0.1179 |
13 | Intermediate Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1269 |
14 | Intermediate Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 5.6629E-002 |
15 | Overcast Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 5.1970E-002 |
16 | Overcast Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 2.1022E-002 |
17 | Clear Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 4.0136E-002 |
18 | Clear Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 2.3165E-002 |
19 | Clear Turbid Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 3.0856E-002 |
20 | Clear Turbid Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.7487E-002 |
21 | Intermediate Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.9611E-002 |
22 | Intermediate Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.1840E-002 |
23 | Overcast Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 4.5560E-002 |
24 | Overcast Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.6155E-002 |
25 | Clear Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 4.0136E-002 |
26 | Clear Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 2.3165E-002 |
27 | Clear Turbid Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 3.0856E-002 |
28 | Clear Turbid Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.7487E-002 |
29 | Intermediate Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.9611E-002 |
30 | Intermediate Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.1840E-002 |
31 | Overcast Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 4.5560E-002 |
32 | Overcast Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.6155E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 33768.45223 | 33768.45223 | 2.57233 | 2.57233 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 26.48300 | 1.53564E-002 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
2 | BASEMENT | Heating | 1589.47544 | 1589.47544 | 7.14284E-002 | 0.85446 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -26.20000 | 3.61342E-004 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
3 | RETAIL_1_FLR_1 | Cooling | 5230.25082 | 5230.25082 | 0.39847 | 0.39847 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 30.84667 | 1.53644E-002 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 3629.44335 | 3629.44335 | 0.16309 | 0.16309 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 3095.56691 | 3095.56691 | 0.23584 | 0.23584 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 30.77600 | 1.53643E-002 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 1156.29732 | 1156.29732 | 5.19613E-002 | 9.17347E-002 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 2431.31499 | 2431.31499 | 0.18519 | 0.18519 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 30.77600 | 1.53643E-002 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 2031.81014 | 2031.81014 | 9.13046E-002 | 9.13046E-002 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 1452.84947 | 1452.84947 | 0.11066 | 0.11066 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 31.20000 | 1.53651E-002 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 1482.11653 | 1482.11653 | 6.66027E-002 | 6.66027E-002 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 44706.38879 | 44706.38879 | 3.40559 | 3.40559 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 31.20000 | 1.53651E-002 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 2691.67917 | 2691.67917 | 0.12095 | 0.12095 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 21683.82753 | 21683.82753 | 1.65335 | 1.65335 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 30.84667 | 1.53644E-002 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 9311.01380 | 9311.01380 | 0.41841 | 0.67639 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 67229.81829 | 67229.81829 | 5.12334 | 5.12334 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 30.93500 | 1.53646E-002 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 20944.03339 | 20944.03339 | 0.94118 | 1.89399 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 12064.84842 | 12064.84842 | 1.23845 | 1.23845 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 29.53933 | 1.53620E-002 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 8040.51697 | 8040.51697 | 0.36343 | 0.36343 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 11702.67830 | 11702.67830 | 1.20128 | 1.20128 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 29.53933 | 1.53620E-002 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 8060.86035 | 8060.86035 | 0.36435 | 0.36435 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 72674.76616 | 72674.76616 | 7.45956 | 7.45956 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 30.93500 | 1.53646E-002 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 45678.04825 | 45678.04825 | 2.06471 | 2.06471 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 61471.67647 | 61471.67647 | 6.31014 | 6.31014 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 27.06600 | 1.53574E-002 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 46061.15010 | 46061.15010 | 2.08203 | 2.08203 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 11005.02386 | 11005.02386 | 1.12966 | 1.12966 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 26.57133 | 1.53565E-002 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 7999.38278 | 7999.38278 | 0.36157 | 0.36157 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 10697.72450 | 10697.72450 | 1.09812 | 1.09812 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 25.67033 | 1.53549E-002 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 8019.73441 | 8019.73441 | 0.36249 | 0.36249 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 21310.47196 | 21310.47196 | 1.62330 | 1.62330 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 31.20000 | 1.53651E-002 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 12604.70788 | 12604.70788 | 0.56643 | 0.56643 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 3139.00542 | 3139.00542 | 0.32222 | 0.32222 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 29.71600 | 1.53623E-002 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 2471.37897 | 2471.37897 | 0.11171 | 0.11171 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 3036.91564 | 3036.91564 | 0.31174 | 0.31174 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 29.53933 | 1.53620E-002 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 2478.94696 | 2478.94696 | 0.11205 | 0.11205 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 14446.70253 | 14446.70253 | 1.48298 | 1.48298 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 31.02333 | 1.53648E-002 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 11788.26715 | 11788.26715 | 0.53284 | 0.53284 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 29222.24384 | 29222.24384 | 2.22880 | 2.22880 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 31.20000 | 1.53651E-002 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 8254.29908 | 8254.29908 | 0.37093 | 1.18780 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 30634.73299 | 30634.73299 | 2.33650 | 2.33650 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 31.20000 | 1.53651E-002 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
40 | DINING_FLR_6 | Heating | 8424.30589 | 8424.30589 | 0.37857 | 1.18780 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | -26.20000 | 3.61342E-004 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 31006.90845 | 31006.90845 | 2.36813 | 2.36813 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 26.87167 | 1.53571E-002 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 3349.83375 | 3349.83375 | 0.15052 | 0.36735 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | -26.20000 | 3.61342E-004 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
43 | CORRIDOR_FLR_6 | Cooling | 10473.17922 | 10473.17922 | 0.79778 | 0.79778 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 31.20000 | 1.53651E-002 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 8645.80716 | 8645.80716 | 0.38852 | 0.38852 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | -26.20000 | 3.61342E-004 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | FLR_3_DOAS | Cooling | Sensible | 43560.46 | 19.05438 | 2.05125 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | FLR_3_DOAS | Heating | Sensible | 101562.16 | 6.35519 | 2.05125 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 |
3 | VAV WITH REHEAT | Cooling | Sensible | 392791.42 | 22.90888 | 22.90888 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | VAV WITH REHEAT | Heating | Sensible | 379088.12 | 7.65642 | 7.65642 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.57233 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.58619 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50600 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.30160 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.49962E-004 |
8 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.12494E-005 |
9 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.30160 |
10 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8144.24330 |
13 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.12494E-005 |
14 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 171.99775 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.39847 |
16 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12826 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50600 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20162 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.50600 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.97047E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.06303E-005 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.20162 |
24 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 4644.29495 |
27 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.06303E-005 |
28 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 119.49192 |
29 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.23584 |
30 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25095 |
31 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50600 |
32 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.11933 |
33 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.66921 |
34 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.51822E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.53705E-005 |
37 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.11933 |
38 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1756.93822 |
41 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.53705E-005 |
42 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 40.74529 |
43 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.18519 |
44 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.67581 |
45 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50600 |
46 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 9.37060E-002 |
47 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.63767E-004 |
50 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.19006E-005 |
51 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 9.37060E-002 |
52 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2503.37848 |
55 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.19006E-005 |
56 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 67.76454 |
57 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.11066 |
58 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.65249 |
59 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50600 |
60 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 5.59951E-002 |
61 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.83913E-004 |
64 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.58989E-005 |
65 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 6.66027E-002 |
66 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1817.33634 |
69 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.58989E-005 |
70 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 49.59811 |
71 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.40559 |
72 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 1.74613E-002 |
73 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50600 |
74 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.72323 |
75 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.50600 |
76 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.18196E-002 |
78 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.94072E-005 |
79 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.72323 |
80 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11362.84954 |
83 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.94072E-005 |
84 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 240.81934 |
85 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.65335 |
86 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.70434E-002 |
87 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50600 |
88 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.83659 |
89 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.50600 |
90 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.37713E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.18299E-004 |
93 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.83659 |
94 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13522.24679 |
97 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.18299E-004 |
98 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 319.00240 |
99 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.12334 |
100 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19457 |
101 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50600 |
102 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.59241 |
103 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51885 |
104 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
105 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.95819E-003 |
106 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.97386E-004 |
107 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.59241 |
108 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
110 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 33993.07858 |
111 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.97386E-004 |
112 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 773.74387 |
113 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
114 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.23845 |
115 | Fan:OnOff | ROOM_1_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 1.23845 |
116 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 7.03408E-005 |
117 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.81865E-004 |
118 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.71043 |
119 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
120 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.61512E-003 |
121 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
122 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
123 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.81865E-004 |
124 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.23845 |
125 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 8040.39050 |
126 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.03408E-005 |
127 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 229.73757 |
128 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
129 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.20128 |
130 | Fan:OnOff | ROOM_2_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 1.20128 |
131 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 7.05188E-005 |
132 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.70732E-004 |
133 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.71042 |
134 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
135 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.61841E-003 |
136 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
137 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
138 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.70732E-004 |
139 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.20128 |
140 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 8060.73361 |
141 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.05188E-005 |
142 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 230.31875 |
143 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83707 |
144 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 7.45956 |
145 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 7.45956 |
146 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 3.99608E-004 |
147 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.25761E-003 |
148 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.71104 |
149 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
150 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.54667E-003 |
151 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
152 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
153 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.25761E-003 |
154 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 7.45956 |
155 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 45677.69616 |
156 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.99608E-004 |
157 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1305.13825 |
158 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83730 |
159 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 6.31014 |
160 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 6.31014 |
161 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.02960E-004 |
162 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.03636E-003 |
163 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.71011 |
164 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
165 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.78741E-003 |
166 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
167 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
168 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.03636E-003 |
169 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 6.31014 |
170 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 46060.79544 |
171 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.02960E-004 |
172 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1316.08306 |
173 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
174 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.12966 |
175 | Fan:OnOff | ROOM_5_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 1.12966 |
176 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 6.99810E-005 |
177 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.49428E-004 |
178 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.71040 |
179 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
180 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.62687E-003 |
181 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
182 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
183 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.49428E-004 |
184 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.12966 |
185 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 7999.25687 |
186 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.99810E-005 |
187 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 228.56243 |
188 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
189 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.09812 |
190 | Fan:OnOff | ROOM_6_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 1.09812 |
191 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 7.01590E-005 |
192 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.40018E-004 |
193 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.71040 |
194 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
195 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.63066E-003 |
196 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
197 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
198 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.40018E-004 |
199 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.09812 |
200 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 8019.60822 |
201 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.01590E-005 |
202 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 229.14384 |
203 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.62330 |
204 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.73117 |
205 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50600 |
206 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.82139 |
207 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.21085E-004 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.46447E-004 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.82139 |
212 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
213 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
214 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 16739.81636 |
215 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.46447E-004 |
216 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 416.03463 |
217 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54338E-002 |
218 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.32222 |
219 | Fan:OnOff | ROOM_1_FLR_6 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 0.32222 |
220 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.16204E-005 |
221 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 9.92332E-005 |
222 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.71044 |
223 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
224 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.61067E-003 |
225 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
226 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
227 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 9.92332E-005 |
228 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.32222 |
229 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 2471.34205 |
230 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.16204E-005 |
231 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 70.61164 |
232 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54319E-002 |
233 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.31174 |
234 | Fan:OnOff | ROOM_2_FLR_6 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 0.31174 |
235 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.16866E-005 |
236 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 9.60967E-005 |
237 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.71043 |
238 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
239 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.61416E-003 |
240 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
241 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
242 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 9.60967E-005 |
243 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.31174 |
244 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 2478.90994 |
245 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.16866E-005 |
246 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 70.82785 |
247 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 9.91540E-002 |
248 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.48298 |
249 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 1.48298 |
250 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.03128E-004 |
251 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.63778E-004 |
252 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.71022 |
253 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
254 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.66784E-003 |
255 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
256 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
257 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.63778E-004 |
258 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.48298 |
259 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 11788.12619 |
260 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.03128E-004 |
261 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 336.81159 |
262 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.22880 |
263 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11339 |
264 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50600 |
265 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.12777 |
266 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.50600 |
267 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
268 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.36010E-003 |
269 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.21884E-004 |
270 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.12777 |
271 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
272 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
273 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13932.12412 |
274 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.21884E-004 |
275 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 314.38776 |
276 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.33650 |
277 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10816 |
278 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50600 |
279 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.18227 |
280 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.50600 |
281 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
282 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.52245E-003 |
283 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.25771E-004 |
284 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.18227 |
285 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
286 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
287 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14376.36188 |
288 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.25771E-004 |
289 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 323.70149 |
290 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.36813 |
291 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 5.97875E-002 |
292 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50600 |
293 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.19827 |
294 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.50600 |
295 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
296 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.14619E-002 |
297 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.20076E-005 |
298 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.19827 |
299 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
300 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
301 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9373.97816 |
302 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.20076E-005 |
303 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 201.26866 |
304 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.79778 |
305 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.39364 |
306 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50600 |
307 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.40368 |
308 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
309 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
310 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 9.67887E-004 |
311 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.34179E-005 |
312 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.40368 |
313 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
314 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
315 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10678.23869 |
316 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.34179E-005 |
317 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 287.97343 |
318 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05132 |
319 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05132 |
320 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05132 |
321 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05132 |
322 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05132 |
323 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05132 |
324 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
325 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
326 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 11.65787 |
327 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 11.65787 |
328 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 23.03926 |
329 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 11.65787 |
330 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 22.90888 |
331 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 22.90888 |
332 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
333 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.50888 |
334 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05132 |
335 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 22.90888 |
336 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05132 |
337 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05125 |
338 | HeatExchanger:AirToAir:SensibleAndLatent | FLR_3_DOAS OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.05125 |
339 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 31.20000 |
340 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
341 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.89847 |
342 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.53651E-002 |
343 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
344 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Coil Load [W] | 87803.63747 |
345 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.51117E-003 |
346 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 2.05132 |
347 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Rated Capacity [W] | 30469.71807 |
348 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.66562E-004 |
349 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 443.50586 |
350 | Fan:ConstantVolume | FLR_3_DOAS FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05125 |
351 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.51117E-003 |
352 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.89629E-004 |
353 | Controller:WaterCoil | FLR_3_DOAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.66562E-004 |
354 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 22.90888 |
355 | HeatExchanger:AirToAir:SensibleAndLatent | VAV WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 11.66146 |
356 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 27.66074 |
357 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
358 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.90268 |
359 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.25675E-002 |
360 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
361 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 723208.74090 |
362 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.06837E-002 |
363 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 22.90888 |
364 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 340282.35843 |
365 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.97694E-003 |
366 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 4953.02318 |
367 | Fan:VariableVolume | VAV WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 22.90888 |
368 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.06837E-002 |
369 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 2.30225E-005 |
370 | Controller:WaterCoil | VAV WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.97694E-003 |
371 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 2.95900E-002 |
372 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 4831.13841 |
373 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 5.72317E-003 |
374 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.68678 |
375 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 5.72317E-003 |
376 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 1723.56835 |
377 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
378 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 654193.82093 |
379 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 654193.82000 |
380 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 5.72317E-003 |
381 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 2.95900E-002 |
382 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 3.55080 |
383 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 2.95900E-002 |
384 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 3344.76007 |
385 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 2.95900E-002 |
386 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1034619.01817 |
387 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1035245.02000 |
388 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 118.01793 |
389 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
390 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
391 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
392 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
393 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | 8186.00 |
2 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 4663.35 |
3 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1765.11 |
4 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | 2513.15 |
5 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | 1824.38 |
6 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 11420.93 |
7 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | 13584.18 |
8 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | 34153.79 |
9 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | 8660.26 |
10 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | 8682.17 |
11 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 49199.19 |
12 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 49611.79 |
13 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | 8615.96 |
14 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | 8637.88 |
15 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 16811.75 |
16 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | 2661.83 |
17 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | 2669.98 |
18 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 12696.73 |
19 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | 13998.53 |
20 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | 14445.02 |
21 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | 9421.37 |
22 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 10720.07 |
23 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | 18524.03 |
24 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | 206874.28 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | 20389.30 | 17212.69 | 3176.60 | 0.84 | 4924.82 | 49.95 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | 19789.29 | 16699.89 | 3089.40 | 0.84 | 4772.86 | 48.41 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 121235.53 | 103167.87 | 18067.67 | 0.85 | 30209.10 | 306.40 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 107174.78 | 88788.52 | 18386.26 | 0.83 | 24230.98 | 245.76 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | 18638.61 | 15713.72 | 2924.89 | 0.84 | 4478.50 | 45.42 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | 18130.82 | 15279.03 | 2851.78 | 0.84 | 4349.23 | 44.11 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | 5300.48 | 4476.95 | 823.53 | 0.84 | 1282.84 | 13.01 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | 5131.41 | 4332.42 | 798.99 | 0.84 | 1239.97 | 12.58 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 24654.31 | 20689.59 | 3964.72 | 0.84 | 5826.64 | 59.10 |
10 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | 64803.99 | 40877.16 | 23926.83 | 0.63 | 9107.44 | 92.37 |
11 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | 675684.54 | 436026.59 | 239657.95 | 0.65 | 104567.65 | 1060.58 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 4.09 | 13.95 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.354 | 0.336 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.354 | 0.336 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.354 | 0.336 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.354 | 0.336 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.652 | 0.594 | 22.63 | 45.89 | 22.63 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.361_SHGC_0.4 | N/A | 2.051 | No | 23.26 | 23.26 | 23.26 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.652 | 0.594 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.652 | 0.594 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.652 | 0.594 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.652 | 0.594 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 2.390 | 2.390 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.652 | 0.594 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.652 | 0.594 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.652 | 0.594 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.652 | 0.594 | 63.73 | 129.23 | 63.73 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.361_SHGC_0.4 | N/A | 2.051 | No | 65.50 | 65.50 | 65.50 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.652 | 0.594 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.652 | 0.594 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.652 | 0.594 | 82.79 | 167.88 | 82.79 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.361_SHGC_0.4 | N/A | 2.051 | No | 85.08 | 85.08 | 85.08 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.652 | 0.594 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.780 | 0.698 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.361_SHGC_0.4 | N/A | 2.051 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.780 | 0.698 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.361_SHGC_0.4 | N/A | 2.051 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.780 | 0.698 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.361_SHGC_0.4 | N/A | 2.051 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.780 | 0.698 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.361_SHGC_0.4 | N/A | 2.051 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.780 | 0.698 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.361_SHGC_0.4 | N/A | 2.051 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.780 | 0.698 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.361_SHGC_0.4 | N/A | 2.051 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.780 | 0.698 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.361_SHGC_0.4 | N/A | 2.051 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.780 | 0.698 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.361_SHGC_0.4 | N/A | 2.051 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.780 | 0.698 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.361_SHGC_0.4 | N/A | 2.051 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.780 | 0.698 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.361_SHGC_0.4 | N/A | 2.051 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.844 | 0.749 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.361_SHGC_0.4 | N/A | 2.051 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.844 | 0.749 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.361_SHGC_0.4 | N/A | 2.051 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.844 | 0.749 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.361_SHGC_0.4 | N/A | 2.051 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.844 | 0.749 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.361_SHGC_0.4 | N/A | 2.051 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.792 | 0.708 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.361_SHGC_0.4 | N/A | 2.051 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.792 | 0.708 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.361_SHGC_0.4 | N/A | 2.051 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.792 | 0.708 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.361_SHGC_0.4 | N/A | 2.051 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.792 | 0.708 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.361_SHGC_0.4 | N/A | 2.051 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.792 | 0.708 | 13.70 | 20.44 | 13.70 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.361_SHGC_0.4 | N/A | 2.051 | No | 6.74 | 6.74 | 6.74 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.857 | 0.759 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.361_SHGC_0.4 | N/A | 2.051 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.857 | 0.759 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.361_SHGC_0.4 | N/A | 2.051 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.857 | 0.759 | 16.77 | 21.37 | 16.77 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.361_SHGC_0.4 | N/A | 2.051 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.857 | 0.759 | 34.86 | 52.03 | 34.86 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.361_SHGC_0.4 | N/A | 2.051 | No | 17.17 | 17.17 | 17.17 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.857 | 0.759 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.361_SHGC_0.4 | N/A | 2.051 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.857 | 0.759 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.361_SHGC_0.4 | N/A | 2.051 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.857 | 0.759 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.361_SHGC_0.4 | N/A | 2.051 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.857 | 0.759 | 34.86 | 52.03 | 34.86 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.361_SHGC_0.4 | N/A | 2.051 | No | 17.17 | 17.17 | 17.17 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 1.8261180232E-002 | 2.2714549747E-002 | Pass | Pass | 4.4286664832E-003 | 1.2492577772E-002 | Pass | Pass |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.7756261312E-003 | 1.1996721842E-003 | Pass | Pass | 0.2863737977 | 0.8735487755 | Pass | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.7461980540E-002 | 2.4879687602E-002 | Pass | Pass | 1.6087907733E-002 | 4.4557960612E-002 | Pass | Pass |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.1565271859E-004 | 3.4419911256E-004 | Pass | Pass | 8.0933881086E-002 | 0.1495580160 | Pass | Pass |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.7124195389E-004 | 3.5861179597E-004 | Pass | Pass | 8.9228725924E-002 | 0.1874910213 | Pass | Pass |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 6.6189937367E-002 | 0.2008619520 | Pass | Pass | 1.9491202004E-002 | 5.3202639422E-002 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.1467311128E-002 | 3.7559241272E-002 | Pass | Pass | 4.6442343958E-002 | 0.1167874121 | Pass | Pass |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 3.0177285699E-002 | 4.8476995167E-002 | Pass | Pass | 1.4813878523E-002 | 3.8188730920E-002 | Pass | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.2456828178E-002 | 0.3035335602 | Pass | Pass | 8.2866332373E-002 | 0.2299766791 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.2615689256E-002 | 0.3083799682 | Pass | Pass | 8.1807716777E-002 | 0.2365066442 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 2.2023651144E-002 | 3.2446468921E-002 | Pass | Pass | 8.5325559939E-002 | 0.4371735564 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 2.8681389165E-002 | 9.6296057305E-002 | Pass | Pass | 0.7825994889 | 4.6316595116 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.2214495442E-002 | 0.2996208804 | Pass | Pass | 8.8617581418E-002 | 0.2465991825 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.2450971010E-002 | 0.3041173664 | Pass | Pass | 8.2461196776E-002 | 0.2340655889 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.5925101346E-004 | 3.5530755308E-004 | Pass | Pass | 0.3599510097 | 1.8374542134 | Pass | Pass |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.2629463093E-002 | 0.3268384317 | Pass | Pass | 0.1271381296 | 0.4855149776 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.2636051428E-002 | 0.3313478143 | Pass | Pass | 0.1625945395 | 0.6424532138 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 8.2880456272E-002 | 0.2678134174 | Pass | Pass | 0.2708810030 | 1.6740046753 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 4.1665669850E-002 | 7.7020643891E-002 | Pass | Pass | 1.1181139022E-002 | 3.2702192361E-002 | Pass | Pass |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 2.9873647692E-002 | 6.3641021345E-002 | Pass | Pass | 1.2880281695E-002 | 3.9141434214E-002 | Pass | Pass |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 2.6066946494E-002 | 7.8571803827E-002 | Pass | Pass | 2.1761171328E-002 | 4.2679003087E-002 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 8.0523952094E-004 | 5.8040072270E-004 | Pass | Pass | 0.3183231249 | 1.0193058400 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:56
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 4420.00 | 76.97 | 2165.08 | 8981.56 | 3821.91 | 19465.53 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:56
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | -26.20 | 0.00 | -26.20 | Wetbulb [C] | 5.70 | 310.00 |
ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 31.20 | 10.60 | 23.10 | Wetbulb [C] | 6.70 | 200.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 26.00 | 35 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 29.00 | 23 | |||
May | 0.00 | 0 | |||
Jun | 107.00 | 45 | |||
Jul | 72.00 | 29 | |||
Aug | 0.00 | 0 | |||
Sep | 20.00 | 11 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 4.00 | 8 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:56
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.340 | 0.354 | 211.13 | 211.13 | 0.00 | 90.00 | N |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.340 | 0.354 | 55.76 | 55.76 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.340 | 0.354 | 211.13 | 211.13 | 180.00 | 90.00 | S |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.340 | 0.354 | 55.76 | 55.76 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.594 | 0.652 | 45.89 | 22.63 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.594 | 0.652 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.594 | 0.652 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.594 | 0.652 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.594 | 0.652 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.594 | 0.652 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.594 | 0.652 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.594 | 0.652 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.594 | 0.652 | 129.23 | 63.73 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.594 | 0.652 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.594 | 0.652 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.594 | 0.652 | 167.88 | 82.79 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.594 | 0.652 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 104.06 | 69.72 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 847.14 | 567.58 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 847.37 | 567.71 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 104.06 | 69.72 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.698 | 0.780 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.749 | 0.844 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.749 | 0.844 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.749 | 0.844 | 26.02 | 17.43 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.749 | 0.844 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.708 | 0.792 | 13.94 | 9.34 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.708 | 0.792 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | RES_ROOF | 0.23 | 0.182 | 0.186 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | RES_EXT_WALL_TOP | 0.30 | 0.708 | 0.792 | 13.94 | 9.34 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.708 | 0.792 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | RES_ROOF | 0.23 | 0.182 | 0.186 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.708 | 0.792 | 183.96 | 123.26 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | RES_ROOF | 0.23 | 0.182 | 0.186 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.759 | 0.857 | 97.55 | 65.36 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.759 | 0.857 | 97.55 | 65.36 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.759 | 0.857 | 21.37 | 16.77 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.759 | 0.857 | 52.03 | 34.86 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.759 | 0.857 | 13.94 | 9.34 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.759 | 0.857 | 17.65 | 11.83 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.759 | 0.857 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.759 | 0.857 | 52.03 | 34.86 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 167.42 | 167.42 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_FLOOR | BASEMENT_FLOOR | 0.30 | 1.441 | 2.705 | 1978.83 | 1978.83 | 0.00 | 180.00 | |
BASEMENT_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 67.07 | 67.07 | 180.00 | 0.00 | |
BASEMENT_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 77.67 | 77.67 | 180.00 | 0.00 | |
BASEMENT_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 164.24 | 164.24 | 180.00 | 0.00 | |
BASEMENT_CEILING_4 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 94.76 | 94.76 | 180.00 | 0.00 | |
BASEMENT_CEILING_5 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 78.04 | 78.04 | 180.00 | 0.00 | |
BASEMENT_CEILING_6 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 188.86 | 188.86 | 180.00 | 0.00 | |
BASEMENT_CEILING_7 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 1088.56 | 1088.56 | 180.00 | 0.00 | |
BASEMENT_CEILING_8 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 219.63 | 219.63 | 90.00 | 0.00 | |
RETAIL_1_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_1_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
RETAIL_1_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 67.07 | 67.07 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
RETAIL_2_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_2_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 90.00 | 90.00 | E |
RETAIL_2_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 77.67 | 77.67 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 77.67 | 77.67 | 180.00 | 0.00 | |
MECH_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
MECH_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 180.00 | 90.00 | S |
MECH_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
MECH_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 164.24 | 164.24 | 0.00 | 180.00 | |
MECH_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 164.24 | 164.24 | 180.00 | 0.00 | |
STORAGE_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
STORAGE_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 180.00 | 90.00 | S |
STORAGE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
STORAGE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 94.76 | 94.76 | 0.00 | 180.00 | |
STORAGE_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 94.76 | 94.76 | 180.00 | 0.00 | |
LAUNDRY_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 180.00 | 90.00 | S |
LAUNDRY_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 270.00 | 90.00 | W |
LAUNDRY_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 78.04 | 78.04 | 0.00 | 180.00 | |
LAUNDRY_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 78.04 | 78.04 | 180.00 | 0.00 | |
CAFE_FLR_1_WALL_1_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_2_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
CAFE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 188.86 | 188.86 | 0.00 | 180.00 | |
LOBBY_FLR_1_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 90.00 | 90.00 | E |
LOBBY_FLR_1_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 1088.56 | 1088.56 | 180.00 | 180.00 | |
LOBBY_FLR_1_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 219.63 | 219.63 | 90.00 | 180.00 | |
LOBBY_FLR_1_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 1062.83 | 1062.83 | 270.00 | 0.00 | |
ROOM_1_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_1_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
ROOM_1_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_1_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_2_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
ROOM_2_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_2_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_2_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 156.07 | 156.07 | 180.00 | 0.00 | |
ROOM_3_MULT19_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.14 | 847.14 | 0.00 | 90.00 | N |
ROOM_3_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_3_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 1863.81 | 1863.81 | 0.00 | 180.00 | |
ROOM_3_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 1863.81 | 1863.81 | 180.00 | 0.00 | |
ROOM_4_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_4_MULT19_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.37 | 847.37 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_4_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 1864.32 | 1864.32 | 0.00 | 180.00 | |
ROOM_4_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 1864.32 | 1864.32 | 180.00 | 0.00 | |
ROOM_5_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
ROOM_5_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_5_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_6_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
ROOM_6_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_6_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 156.07 | 156.07 | 180.00 | 0.00 | |
CORRIDOR_FLR_3_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.28 | 847.28 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_4_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.27 | 847.27 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 297.29 | 297.29 | 180.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 963.06 | 963.06 | 270.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_3 | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 297.26 | 297.26 | 90.00 | 180.00 | |
CORRIDOR_FLR_3_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 297.29 | 297.29 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 963.06 | 963.06 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 297.26 | 297.26 | 90.00 | 0.00 | |
ROOM_1_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 0.00 | 90.00 | N |
ROOM_1_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_1_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_2_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_2_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 180.00 | 90.00 | S |
ROOM_2_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_3_MULT9_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.96 | 183.96 | 0.00 | 90.00 | N |
ROOM_3_MULT9_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 90.00 | 90.00 | E |
ROOM_3_MULT9_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 270.00 | 90.00 | W |
ROOM_3_MULT9_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 220.77 | 220.77 | 0.00 | 180.00 | |
BANQUET_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
BANQUET_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
BANQUET_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
BANQUET_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 331.66 | 331.66 | 0.00 | 180.00 | |
DINING_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
DINING_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
DINING_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
DINING_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 331.66 | 331.66 | 0.00 | 180.00 | |
KITCHEN_FLR_6_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 7.43 | 7.43 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 103.30 | 103.30 | 180.00 | 180.00 | |
CORRIDOR_FLR_6_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 104.98 | 104.98 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_1_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.95 | 183.95 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 11.15 | 11.15 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 40.88 | 40.88 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 412.12 | 412.12 | 180.00 | 180.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3957.66 | 0.00 | 90.00 | N | ||
RETAIL_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 134.14 | 0.00 | 90.00 | N | ||
RETAIL_2_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 155.34 | 0.00 | 90.00 | N | ||
MECH_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 328.49 | 0.00 | 90.00 | N | ||
STORAGE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 189.52 | 0.00 | 90.00 | N | ||
LAUNDRY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 156.08 | 0.00 | 90.00 | N | ||
CAFE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 377.72 | 0.00 | 90.00 | N | ||
LOBBY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 2616.37 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3727.63 | 0.00 | 90.00 | N | ||
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3728.64 | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3115.24 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.04 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.03 | 0.00 | 90.00 | N | ||
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 441.55 | 0.00 | 90.00 | N | ||
BANQUET_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
DINING_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 206.61 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 824.25 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.361_SHGC_0.4 | 23.26 | 0.00 | 0.00 | 23.26 | 23.26 | 2.051 | 0.401 | 0.442 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.361_SHGC_0.4 | 65.50 | 0.00 | 0.00 | 65.50 | 65.50 | 2.051 | 0.401 | 0.442 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.361_SHGC_0.4 | 85.08 | 0.00 | 0.00 | 85.08 | 85.08 | 2.051 | 0.401 | 0.442 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.361_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.051 | 0.401 | 0.442 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.361_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.051 | 0.401 | 0.442 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.361_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.051 | 0.401 | 0.442 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.361_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.051 | 0.401 | 0.442 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.361_SHGC_0.4 | 3.68 | 0.00 | 0.00 | 3.68 | 279.56 | 2.051 | 0.401 | 0.442 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.361_SHGC_0.4 | 3.68 | 0.00 | 0.00 | 3.68 | 279.65 | 2.051 | 0.401 | 0.442 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.361_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.051 | 0.401 | 0.442 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.361_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.051 | 0.401 | 0.442 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.361_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.051 | 0.401 | 0.442 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.361_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.051 | 0.401 | 0.442 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.361_SHGC_0.4 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.051 | 0.401 | 0.442 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.361_SHGC_0.4 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 2.051 | 0.401 | 0.442 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.361_SHGC_0.4 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 2.051 | 0.401 | 0.442 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.361_SHGC_0.4 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.051 | 0.401 | 0.442 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.361_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.051 | 0.401 | 0.442 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.361_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.051 | 0.401 | 0.442 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.361_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.051 | 0.401 | 0.442 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.361_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.051 | 0.401 | 0.442 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.361_SHGC_0.4 | 6.74 | 0.00 | 0.00 | 6.74 | 60.70 | 2.051 | 0.401 | 0.442 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.361_SHGC_0.4 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.051 | 0.401 | 0.442 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.361_SHGC_0.4 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.051 | 0.401 | 0.442 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.361_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.051 | 0.401 | 0.442 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.361_SHGC_0.4 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.051 | 0.401 | 0.442 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | |||||||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.361_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.051 | 0.401 | 0.442 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.361_SHGC_0.4 | 5.82 | 0.00 | 0.00 | 5.82 | 5.82 | 2.051 | 0.401 | 0.442 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.361_SHGC_0.4 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 2.051 | 0.401 | 0.442 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.361_SHGC_0.4 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.051 | 0.401 | 0.442 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 1213.79 | 2.051 | 0.401 | 0.442 | |||||||||||||||||
North Total or Average | 432.95 | 2.051 | 0.401 | 0.442 | |||||||||||||||||
Non-North Total or Average | 780.84 | 2.051 | 0.401 | 0.442 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 1.760 | 2.390 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:56
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:56
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 8.8143 | 1978.83 | 17441.96 | LightsWired | LTG_SCH_BASEMENT | 49.32 | 168.00 | 49.26 | 0.0000 | Y | 161.29 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | RETAIL_1_FLR_1 | GENERAL | 11.3140 | 67.07 | 758.85 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 7.31 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | RETAIL_2_FLR_1 | GENERAL | 11.3140 | 77.67 | 878.75 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 8.46 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | MECH_FLR_1 | GENERAL | 4.6285 | 164.24 | 760.20 | LightsWired | LTG_SCH_MECHANIC | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 8.37 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | STORAGE_FLR_1 | GENERAL | 5.7199 | 94.76 | 542.02 | LightsWired | LTG_SCH_STORAGE | 30.30 | 168.00 | 30.27 | 0.0000 | Y | 3.08 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | LAUNDRY_FLR_1 | GENERAL | 4.6285 | 78.04 | 361.20 | LightsWired | LTG_SCH_LAUNDRY | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 3.98 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | CAFE_FLR_1 | GENERAL | 10.0104 | 188.86 | 1890.59 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 39.39 | 0.0000 | Y | 13.98 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | LOBBY_FLR_1 | GENERAL | 10.7639 | 1308.19 | 14081.18 | LightsWired | LTG_SCH_LOBBY | 44.02 | 168.00 | 41.53 | 0.0000 | Y | 109.79 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | ROOM_1_FLR_3 | GENERAL | 8.2882 | 156.09 | 1293.69 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | ROOM_2_FLR_3 | GENERAL | 8.2882 | 156.07 | 1293.54 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | GENERAL | 8.2882 | 1863.81 | 15447.65 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 110.38 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | GENERAL | 8.2882 | 1864.32 | 15451.87 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 110.41 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | ROOM_5_FLR_3 | GENERAL | 8.2882 | 156.09 | 1293.69 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | ROOM_6_FLR_3 | GENERAL | 8.2882 | 156.07 | 1293.54 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | CORRIDOR_FLR_3 | GENERAL | 7.1042 | 1557.62 | 11065.59 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 91.33 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | ROOM_1_FLR_6 | GENERAL | 8.2882 | 39.02 | 323.42 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 2.31 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | ROOM_2_FLR_6 | GENERAL | 8.2882 | 39.02 | 323.38 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 2.31 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | GENERAL | 8.2882 | 220.77 | 1829.83 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 13.08 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | BANQUET_FLR_6 | GENERAL | 10.0104 | 331.66 | 3320.03 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 49.20 | 0.0000 | Y | 30.67 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | DINING_FLR_6 | GENERAL | 10.0104 | 331.66 | 3320.03 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 49.20 | 0.0000 | Y | 30.67 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | KITCHEN_FLR_6 | GENERAL | 11.4097 | 103.30 | 1178.68 | LightsWired | LTG_SCH_KITCHEN | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 12.97 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | CORRIDOR_FLR_6 | GENERAL | 7.1042 | 412.12 | 2927.80 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 24.17 |
Interior Lighting Total | 8.5566 | 11345.29 | 97077.49 | 455.77 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
LOBBY_FLR_1_DAYLREFPT1 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.07 | 14081.18 | 985.68 |
LOBBY_FLR_1_DAYLREFPT2 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.07 | 14081.18 | 985.68 |
CAFE_FLR_1_DAYLREFPT1 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1890.59 | 737.33 |
CAFE_FLR_1_DAYLREFPT2 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1890.59 | 737.33 |
DINING_FLR_6_DAYLREFPT1 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
DINING_FLR_6_DAYLREFPT2 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
BANQUET_FLR_6_DAYLREFPT1 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
BANQUET_FLR_6_DAYLREFPT2 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 12338.45 | AstronomicalClock | - | 83.63 | 83.63 | 193.69 | |
Exterior Lighting Total | 12338.45 | 193.69 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:56
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 654193.82 | 0.80 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 1035245.02 | 2.96 | 1035245.02 | 2.96 | 4.09 | 13.95 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 13352.22 | 20389.30 | 17212.69 | 3176.60 | 0.84 | - | 4924.82 | 49.95 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 12962.94 | 19789.29 | 16699.89 | 3089.40 | 0.84 | - | 4772.86 | 48.41 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 78939.23 | 121235.53 | 103167.87 | 18067.67 | 0.85 | - | 30209.10 | 306.40 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 71203.11 | 107174.78 | 88788.52 | 18386.26 | 0.83 | - | 24230.98 | 245.76 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 12218.04 | 18638.61 | 15713.72 | 2924.89 | 0.84 | - | 4478.50 | 45.42 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 11889.03 | 18130.82 | 15279.03 | 2851.78 | 0.84 | - | 4349.23 | 44.11 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3469.77 | 5300.48 | 4476.95 | 823.53 | 0.84 | - | 1282.84 | 13.01 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3360.10 | 5131.41 | 4332.42 | 798.99 | 0.84 | - | 1239.97 | 12.58 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 16216.38 | 24654.31 | 20689.59 | 3964.72 | 0.84 | - | 5826.64 | 59.10 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | 87803.64 | 64803.99 | 40877.16 | 23926.83 | 0.63 | - | 9107.44 | 92.37 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | 723208.74 | 675684.54 | 436026.59 | 239657.95 | 0.65 | - | 104567.65 | 1060.58 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 8144.24 | 8186.00 | - |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 4644.29 | 4663.35 | - |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1756.94 | 1765.11 | - |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2503.38 | 2513.15 | - |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1817.34 | 1824.38 | - |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 11362.85 | 11420.93 | - |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 13522.25 | 13584.18 | - |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 33993.08 | 34153.79 | - |
ROOM_1_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 8040.39 | 8660.26 | - |
ROOM_2_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 8060.73 | 8682.17 | - |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 45677.70 | 49199.19 | - |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 46060.80 | 49611.79 | - |
ROOM_5_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 7999.26 | 8615.96 | - |
ROOM_6_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 8019.61 | 8637.88 | - |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 16739.82 | 16811.75 | - |
ROOM_1_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 2471.34 | 2661.83 | - |
ROOM_2_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 2478.91 | 2669.98 | - |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 11788.13 | 12696.73 | - |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 13932.12 | 13998.53 | - |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 14376.36 | 14445.02 | - |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 9373.98 | 9421.37 | - |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 10678.24 | 10720.07 | - |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | 30469.72 | 18524.03 | - |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | 340282.36 | 206874.28 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 0.24 | 76.61 | 324.68 | 1.00 | 2.78 | General | ||
LOBBY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.24 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
ROOM_1_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 1.24 | 871.42 | 703.64 | 1.00 | 1.15 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 |
ROOM_2_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 1.20 | 845.26 | 703.64 | 1.00 | 1.15 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 |
ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 7.46 | 5248.82 | 703.64 | 1.00 | 0.95 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 |
ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 6.31 | 4440.05 | 703.64 | 1.00 | 0.96 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
ROOM_5_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 1.13 | 794.87 | 703.64 | 1.00 | 1.17 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 |
ROOM_6_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 1.10 | 772.68 | 703.64 | 1.00 | 1.17 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 |
ROOM_1_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 0.32 | 226.72 | 703.64 | 1.00 | 1.66 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
ROOM_2_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 0.31 | 219.35 | 703.64 | 1.00 | 1.69 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 |
ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 1.48 | 1043.48 | 703.64 | 1.00 | 1.11 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
BANQUET_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
DINING_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 1.89 | 612.92 | 324.68 | 1.00 | 1.48 | General | ||
FLR_3_DOAS FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.93 | 1070.05 | 1.00 | 1.30 | General | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 |
VAV WITH REHEAT FAN | Fan:VariableVolume | 0.62 | 1389.42 | 22.91 | 51330.52 | 2240.64 | 1.00 | 1.11 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.029590 | 4831.14 | 163269.44 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.005723 | 1723.57 | 301156.09 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.029590 | 3344.76 | 113036.94 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH LAUNDRY G WATER HEATER | WaterHeater:Mixed | 1.14 | 163316.00 | 0.80 | 11.51 | 0.44 |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.22 | 1.12 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.60 | 0.80 | 5.78 | 0.37 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:56
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 33768.45 | 33768.45 | 17.06 | 2.572 | 2.572 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 24.00 | 24.00 | 0.00921 | 26.48 | 0.01536 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 5230.25 | 5230.25 | 77.98 | 0.398 | 0.398 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 24.00 | 0.00903 | 30.85 | 0.01536 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 3095.57 | 3095.57 | 39.86 | 0.236 | 0.236 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 24.00 | 24.00 | 0.00946 | 30.78 | 0.01536 | 0.092 | 0.00 |
MECH_FLR_1 | 2431.31 | 2431.31 | 14.80 | 0.185 | 0.185 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 24.00 | 24.00 | 0.00888 | 30.78 | 0.01536 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1452.85 | 1452.85 | 15.33 | 0.111 | 0.111 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00895 | 31.20 | 0.01537 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 44706.39 | 44706.39 | 572.87 | 3.406 | 3.406 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00855 | 31.20 | 0.01537 | 0.000 | 0.00 |
CAFE_FLR_1 | 21683.83 | 21683.83 | 114.81 | 1.653 | 1.653 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 23.99 | 0.01001 | 30.85 | 0.01536 | 0.676 | 0.00 |
LOBBY_FLR_1 | 67229.82 | 67229.82 | 51.39 | 5.123 | 5.123 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 23.99 | 0.00995 | 30.93 | 0.01536 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 12064.85 | 12064.85 | 309.18 | 1.238 | 1.238 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 21.11 | 21.11 | 0.00862 | 29.54 | 0.01536 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 11702.68 | 11702.68 | 299.93 | 1.201 | 1.201 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 21.11 | 21.11 | 0.00862 | 29.54 | 0.01536 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 72674.77 | 72674.77 | 2963.43 | 7.460 | 7.460 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 21.11 | 21.11 | 0.00855 | 30.93 | 0.01536 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 61471.68 | 61471.68 | 2505.92 | 6.310 | 6.310 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 21.11 | 21.11 | 0.00879 | 27.07 | 0.01536 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 11005.02 | 11005.02 | 282.02 | 1.130 | 1.130 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 21.11 | 21.11 | 0.00863 | 26.57 | 0.01536 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 10697.72 | 10697.72 | 274.18 | 1.098 | 1.098 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 21.11 | 21.11 | 0.00863 | 25.67 | 0.01535 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 21310.47 | 21310.47 | 54.73 | 1.623 | 1.623 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 24.00 | 0.00944 | 31.20 | 0.01537 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 3139.01 | 3139.01 | 80.44 | 0.322 | 0.322 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 21.11 | 21.11 | 0.00861 | 29.72 | 0.01536 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 3036.92 | 3036.92 | 77.83 | 0.312 | 0.312 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 21.11 | 21.11 | 0.00861 | 29.54 | 0.01536 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 14446.70 | 14446.70 | 588.93 | 1.483 | 1.483 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 21.11 | 21.11 | 0.00867 | 31.02 | 0.01536 | 0.099 | 0.00 |
BANQUET_FLR_6 | 29222.24 | 29222.24 | 88.11 | 2.229 | 2.229 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 23.98 | 0.01044 | 31.20 | 0.01537 | 1.188 | 0.00 |
DINING_FLR_6 | 30634.73 | 30634.73 | 92.37 | 2.336 | 2.336 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 23.98 | 0.01036 | 31.20 | 0.01537 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 31006.91 | 31006.91 | 300.15 | 2.368 | 2.368 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 24.00 | 23.97 | 0.01000 | 26.87 | 0.01536 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 10473.18 | 10473.18 | 25.41 | 0.798 | 0.798 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 24.00 | 0.00902 | 31.20 | 0.01537 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 1589.48 | 1589.48 | 0.80 | 0.071 | 0.854 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00798 | -26.20 | 0.00036 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 3629.44 | 3629.44 | 54.11 | 0.163 | 0.163 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00776 | -26.20 | 0.00036 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 1156.30 | 1156.30 | 14.89 | 0.052 | 0.092 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00771 | -26.20 | 0.00036 | 0.092 | 0.00 |
MECH_FLR_1 | 2031.81 | 2031.81 | 12.37 | 0.091 | 0.091 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00762 | -26.20 | 0.00036 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1482.12 | 1482.12 | 15.64 | 0.067 | 0.067 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00770 | -26.20 | 0.00036 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 2691.68 | 2691.68 | 34.49 | 0.121 | 0.121 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00761 | -26.20 | 0.00036 | 0.000 | 0.00 |
CAFE_FLR_1 | 9311.01 | 9311.01 | 49.30 | 0.418 | 0.676 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00779 | -26.20 | 0.00036 | 0.676 | 0.00 |
LOBBY_FLR_1 | 20944.03 | 20944.03 | 16.01 | 0.941 | 1.894 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00774 | -26.20 | 0.00036 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 8040.52 | 8040.52 | 206.05 | 0.363 | 0.363 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00775 | -26.20 | 0.00036 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 8060.86 | 8060.86 | 206.60 | 0.364 | 0.364 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00775 | -26.20 | 0.00036 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 45678.05 | 45678.05 | 1862.60 | 2.065 | 2.065 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00777 | -26.20 | 0.00036 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 46061.15 | 46061.15 | 1877.71 | 2.082 | 2.082 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00777 | -26.20 | 0.00036 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 7999.38 | 7999.38 | 205.00 | 0.362 | 0.362 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00775 | -26.20 | 0.00036 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 8019.73 | 8019.73 | 205.54 | 0.362 | 0.362 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00775 | -26.20 | 0.00036 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 12604.71 | 12604.71 | 32.37 | 0.566 | 0.566 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00781 | -26.20 | 0.00036 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 2471.38 | 2471.38 | 63.33 | 0.112 | 0.112 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00780 | -26.20 | 0.00036 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2478.95 | 2478.95 | 63.53 | 0.112 | 0.112 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00780 | -26.20 | 0.00036 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 11788.27 | 11788.27 | 480.55 | 0.533 | 0.533 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00780 | -26.20 | 0.00036 | 0.099 | 0.00 |
BANQUET_FLR_6 | 8254.30 | 8254.30 | 24.89 | 0.371 | 1.188 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00785 | -26.20 | 0.00036 | 1.188 | 0.00 |
DINING_FLR_6 | 8424.31 | 8424.31 | 25.40 | 0.379 | 1.188 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 21.00 | 21.00 | 0.00785 | -26.20 | 0.00036 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 3349.83 | 3349.83 | 32.43 | 0.151 | 0.367 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 21.00 | 21.00 | 0.00732 | -26.20 | 0.00036 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 8645.81 | 8645.81 | 20.98 | 0.389 | 0.389 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | 21.00 | 21.00 | 0.00787 | -26.20 | 0.00036 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
FLR_3_DOAS | 19.05 | 2.05 | 6.36 | 2.05 | 2.0513 | 2.0513 | 2.0513 | 1.0000 | 0.3000 |
VAV WITH REHEAT | 22.91 | 22.91 | 7.66 | 7.66 | 22.9089 | 11.6579 | 22.9089 | 0.5089 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 8144.243 | 8144.243 | 1.301599 | 0.00007125 | 171.998 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 8144.24 | 8144.24 | 1.301599 | 16.70 | 12.75 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00797794 | 49.1947 | 1589.48 | 0.00 | 8189.81 | 8189.81 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 4644.295 | 4644.295 | 0.201624 | 0.00004063 | 119.492 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 4644.29 | 4644.29 | 0.201624 | 16.70 | 12.75 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00776251 | 47.8841 | 3629.44 | 0.00 | 4667.76 | 4667.76 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 1756.938 | 1756.938 | 0.119333 | 0.00001537 | 40.745 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 1756.94 | 1756.94 | 0.119333 | 16.70 | 12.75 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00771414 | 47.5884 | 1156.30 | 0.00 | 1766.34 | 1766.34 |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 2503.378 | 2503.378 | 0.093706 | 0.00002190 | 67.765 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 2503.38 | 2503.38 | 0.093706 | 16.70 | 12.75 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00762041 | 47.0172 | 2031.81 | 0.00 | 2515.82 | 2515.82 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 1817.336 | 1817.336 | 0.066603 | 0.00001590 | 49.598 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 1817.34 | 1817.34 | 0.066603 | 16.70 | 12.75 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00769662 | 47.4817 | 1482.12 | 0.00 | 1826.35 | 1826.35 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 11362.850 | 11362.850 | 1.723227 | 0.00009941 | 240.819 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 11362.85 | 11362.85 | 1.723227 | 16.70 | 12.75 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00760935 | 46.9508 | 2691.68 | 0.00 | 11426.35 | 11426.35 |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 13522.247 | 13522.247 | 0.836593 | 0.00011830 | 319.002 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 13522.25 | 13522.25 | 0.836593 | 16.70 | 12.75 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00779448 | 48.0786 | 9311.01 | 0.00 | 13594.22 | 13594.22 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 33993.079 | 33993.079 | 2.592411 | 0.00029739 | 773.744 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 33993.08 | 33993.08 | 2.592411 | 16.70 | 12.75 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00774082 | 47.7510 | 20944.03 | 0.00 | 34176.06 | 34176.06 |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 13352.217 | -999.000 | 1.238453 | 0.00038186 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | 7/21 17:10:00 | 13352.22 | 13007.78 | 1.238453 | 21.71 | 15.19 | 0.00861512 | 12.80 | 11.68 | 0.00850000 | 29.54 | 0.01536201 | 22.68 | 0.0000 | 21.11 | 0.00861512 | 52.7115 | 12064.85 | 0.00 | 13999.01 | 13999.01 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 8040.391 | 8040.391 | 0.363434 | 0.00007034 | 229.738 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 8040.39 | 8040.39 | 0.363434 | 21.11 | 14.21 | 0.00775288 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.11 | 0.00775288 | 47.5006 | 8040.52 | 0.00 | 8667.75 | 8667.75 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 12962.943 | -999.000 | 1.201277 | 0.00037073 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | 7/21 17:10:00 | 12962.94 | 12619.24 | 1.201277 | 21.71 | 15.20 | 0.00861841 | 12.80 | 11.68 | 0.00850000 | 29.54 | 0.01536201 | 22.68 | 0.0000 | 21.11 | 0.00861841 | 52.7314 | 11702.68 | 0.00 | 13590.49 | 13590.49 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 8060.734 | 8060.734 | 0.364353 | 0.00007052 | 230.319 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 8060.73 | 8060.73 | 0.364353 | 21.11 | 14.21 | 0.00775350 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.11 | 0.00775350 | 47.5044 | 8060.86 | 0.00 | 8689.68 | 8689.68 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 78939.233 | -999.000 | 7.459558 | 0.00225761 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | unknown | 7/21 13:30:00 | 78939.23 | 78100.92 | 7.459558 | 21.71 | 15.13 | 0.00854667 | 12.80 | 11.68 | 0.00850000 | 30.93 | 0.01536459 | 23.06 | 0.0000 | 21.11 | 0.00854667 | 52.2967 | 72674.77 | 0.00 | 82802.51 | 82802.51 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 45677.696 | 45677.696 | 2.064712 | 0.00039961 | 1305.138 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 45677.70 | 45677.70 | 2.064712 | 21.11 | 14.22 | 0.00776890 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.11 | 0.00776890 | 47.5966 | 45678.05 | 0.00 | 49241.98 | 49241.98 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 71203.108 | -999.000 | 6.310144 | 0.00203636 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | unknown | 7/21 19:00:00 | 71203.11 | 66787.57 | 6.310144 | 21.71 | 15.34 | 0.00878741 | 12.80 | 11.68 | 0.00850000 | 27.07 | 0.01535744 | 22.00 | 0.0000 | 21.11 | 0.00878741 | 53.7514 | 61471.68 | 0.00 | 74575.65 | 71904.58 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 46060.795 | 46060.795 | 2.082029 | 0.00040296 | 1316.083 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 46060.80 | 46060.80 | 2.082029 | 21.11 | 14.22 | 0.00777071 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.11 | 0.00777071 | 47.6076 | 46061.15 | 0.00 | 49654.98 | 49654.98 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 12218.036 | -999.000 | 1.129664 | 0.00034943 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | unknown | 7/21 09:40:00 | 12218.04 | 11871.60 | 1.129664 | 21.71 | 15.20 | 0.00862687 | 12.80 | 11.68 | 0.00850000 | 26.57 | 0.01535653 | 21.86 | 0.0000 | 21.11 | 0.00862687 | 52.7825 | 11005.02 | 0.00 | 12808.59 | 12808.59 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 7999.257 | 7999.257 | 0.361574 | 0.00006998 | 228.562 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 7999.26 | 7999.26 | 0.361574 | 21.11 | 14.21 | 0.00775165 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.11 | 0.00775165 | 47.4932 | 7999.38 | 0.00 | 8623.40 | 8623.40 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 11889.026 | -999.000 | 1.098120 | 0.00034002 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | unknown | 7/21 09:10:00 | 11889.03 | 11542.13 | 1.098120 | 21.71 | 15.21 | 0.00863066 | 12.80 | 11.68 | 0.00850000 | 25.67 | 0.01535487 | 21.60 | 0.0000 | 21.11 | 0.00863066 | 52.8054 | 10697.72 | 0.00 | 12463.28 | 12463.28 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 8019.608 | 8019.608 | 0.362494 | 0.00007016 | 229.144 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 8019.61 | 8019.61 | 0.362494 | 21.11 | 14.21 | 0.00775228 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.11 | 0.00775228 | 47.4970 | 8019.73 | 0.00 | 8645.34 | 8645.34 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 16739.816 | 16739.816 | 0.821392 | 0.00014645 | 416.035 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 16739.82 | 16739.82 | 0.821392 | 16.70 | 12.75 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00780687 | 48.1531 | 12604.71 | 0.00 | 16826.26 | 16826.26 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 3469.772 | -999.000 | 0.322218 | 0.00009923 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | 7/21 17:00:00 | 3469.77 | 3383.64 | 0.322218 | 21.71 | 15.19 | 0.00861067 | 12.80 | 11.68 | 0.00850000 | 29.72 | 0.01536233 | 22.73 | 0.0000 | 21.11 | 0.00861067 | 52.6847 | 3139.01 | 0.00 | 3637.99 | 3637.99 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 2471.342 | 2471.342 | 0.111707 | 0.00002162 | 70.612 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 2471.34 | 2471.34 | 0.111707 | 21.11 | 14.25 | 0.00779774 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.11 | 0.00779774 | 47.7720 | 2471.38 | 0.00 | 2664.17 | 2664.17 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 3360.102 | -999.000 | 0.311738 | 0.00009610 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | 7/21 17:10:00 | 3360.10 | 3274.12 | 0.311738 | 21.71 | 15.19 | 0.00861416 | 12.80 | 11.68 | 0.00850000 | 29.54 | 0.01536201 | 22.68 | 0.0000 | 21.11 | 0.00861416 | 52.7058 | 3036.92 | 0.00 | 3522.90 | 3522.90 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 2478.910 | 2478.910 | 0.112049 | 0.00002169 | 70.828 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 2478.91 | 2478.91 | 0.112049 | 21.11 | 14.25 | 0.00779835 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.11 | 0.00779835 | 47.7758 | 2478.95 | 0.00 | 2672.33 | 2672.33 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 16216.378 | -999.000 | 1.482977 | 0.00046378 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | unknown | 7/21 13:40:00 | 16216.38 | 15613.58 | 1.482977 | 21.71 | 15.24 | 0.00866784 | 12.80 | 11.68 | 0.00850000 | 31.02 | 0.01536476 | 23.08 | 0.0000 | 21.11 | 0.00866784 | 53.0302 | 14446.70 | 0.00 | 16996.46 | 16996.46 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 11788.126 | 11788.126 | 0.532838 | 0.00010313 | 336.812 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 11788.13 | 11788.13 | 0.532838 | 21.11 | 14.25 | 0.00780456 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.11 | 0.00780456 | 47.8130 | 11788.27 | 0.00 | 12707.93 | 12707.93 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 13932.124 | 13932.124 | 1.127773 | 0.00012188 | 314.388 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 13932.12 | 13932.12 | 1.127773 | 16.70 | 12.75 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00785021 | 48.4174 | 8254.30 | 0.00 | 14007.36 | 14007.36 |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 14376.362 | 14376.362 | 1.182267 | 0.00012577 | 323.701 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 14376.36 | 14376.36 | 1.182267 | 16.70 | 12.75 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00785318 | 48.4358 | 8424.31 | 0.00 | 14454.06 | 14454.06 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 9373.978 | 9373.978 | 1.198272 | 0.00008201 | 201.269 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 9373.98 | 9373.98 | 1.198272 | 16.70 | 12.75 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00732190 | 45.2024 | 3349.83 | 0.00 | 9426.15 | 9426.15 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 10678.239 | 10678.239 | 0.403677 | 0.00009342 | 287.973 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | 10678.24 | 10678.24 | 0.403677 | 16.70 | 12.75 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00787430 | 48.5640 | 8645.81 | 0.00 | 10731.35 | 10731.35 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 87803.637 | -999.000 | 2.051317 | 0.00251117 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 87803.64 | 47531.07 | 2.051317 | 31.20 | 23.13 | 0.01536508 | 11.90 | 11.31 | 0.00850000 | 31.20 | 0.01536508 | 23.13 | 99.9965 | 21.11 | 0.00865992 | 52.9812 | 185628.53 | 0.00 | 89691.54 | 48118.14 |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | FLR_3_DOAS | 30469.718 | 30469.718 | 0.615395 | 0.00026656 | 443.506 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 30469.72 | 30469.72 | 0.615395 | -26.20 | -26.20 | 0.00036134 | 16.70 | 12.75 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 333.3216 | 21.11 | 0.00777003 | 47.6035 | 140598.29 | 0.00 | 22379.93 | 22379.93 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 723208.741 | -999.000 | 22.908878 | 0.02068368 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 723208.74 | 450213.42 | 22.908878 | 27.66 | 20.25 | 0.01256753 | 10.90 | 10.89 | 0.00850000 | 31.20 | 0.01536508 | 23.13 | 50.9037 | 23.99 | 0.00962559 | 49.3569 | 300441.40 | 0.00 | 742715.66 | 449600.85 |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV WITH REHEAT | 340282.358 | 340282.358 | 6.872664 | 0.00297694 | 4953.023 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 340282.36 | 340282.36 | 6.872664 | -26.20 | -26.20 | 0.00036134 | 16.70 | 12.75 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 169.6789 | 21.00 | 0.00778233 | 47.9905 | 82874.77 | 0.00 | 249936.54 | 249936.54 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:24:56
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | Yes | Yes | No | 8144.243 | 8144.243 | 1.301599 | 0.00007125 | 171.998 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.72258911 | 54.44 | 82.22 | 27.78 | 667359.73 | 1.2204 | 1.244928 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 8144.24 | 8144.24 | 1.0000 | 1.49495881 | 1.301599 | 16.70 | 12.75 | 0.00800000 | 37036.7 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.07124213 | 60.00 | 32.22 | 27.78 | 0.000 | 8144.24 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00797794 | 21.00 | 0.00797794 | 49.1947 | 1589.48 | 0.00 | 8189.81 | 8189.81 | 1.49495881 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.97 | 15.21 | 0.00800000 | 42413.0 | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4644.295 | 4644.295 | 0.201624 | 0.00004063 | 119.492 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.72258911 | 54.44 | 82.22 | 27.78 | 667359.73 | 0.6959 | 0.709926 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 4644.29 | 4644.29 | 1.0000 | 0.23157653 | 0.201624 | 16.70 | 12.75 | 0.00800000 | 37036.7 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.04062617 | 60.00 | 32.22 | 27.78 | 0.000 | 4644.29 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00776251 | 21.00 | 0.00776251 | 47.8841 | 3629.44 | 0.00 | 4667.76 | 4667.76 | 0.23157653 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 36.37 | 20.08 | 0.00800000 | 57091.2 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1756.938 | 1756.938 | 0.119333 | 0.00001537 | 40.745 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.72258911 | 54.44 | 82.22 | 27.78 | 667359.73 | 0.2633 | 0.268565 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 1756.94 | 1756.94 | 1.0000 | 0.13706077 | 0.119333 | 16.70 | 12.75 | 0.00800000 | 37036.7 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.01536889 | 60.00 | 32.22 | 27.78 | 0.000 | 1756.94 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00771414 | 21.00 | 0.00771414 | 47.5884 | 1156.30 | 0.00 | 1766.34 | 1766.34 | 0.13706077 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 29.24 | 17.78 | 0.00800000 | 49822.0 | |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2503.378 | 2503.378 | 0.093706 | 0.00002190 | 67.765 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.72258911 | 54.44 | 82.22 | 27.78 | 667359.73 | 0.3751 | 0.382666 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 2503.38 | 2503.38 | 1.0000 | 0.10762657 | 0.093706 | 16.70 | 12.75 | 0.00800000 | 37036.7 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.02189841 | 60.00 | 32.22 | 27.78 | 0.000 | 2503.38 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00762041 | 21.00 | 0.00762041 | 47.0172 | 2031.81 | 0.00 | 2515.82 | 2515.82 | 0.10762657 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 39.52 | 21.04 | 0.00800000 | 60310.2 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1817.336 | 1817.336 | 0.066603 | 0.00001590 | 49.598 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.72258911 | 54.44 | 82.22 | 27.78 | 667359.73 | 0.2723 | 0.277798 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 1817.34 | 1817.34 | 1.0000 | 0.07649693 | 0.066603 | 16.70 | 12.75 | 0.00800000 | 37036.7 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.01589723 | 60.00 | 32.22 | 27.78 | 0.000 | 1817.34 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00769662 | 21.00 | 0.00769662 | 47.4817 | 1482.12 | 0.00 | 1826.35 | 1826.35 | 0.07649693 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 40.01 | 21.19 | 0.00800000 | 60809.5 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11362.850 | 11362.850 | 1.723227 | 0.00009941 | 240.819 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.72258911 | 54.44 | 82.22 | 27.78 | 667359.73 | 1.7027 | 1.736924 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 11362.85 | 11362.85 | 1.0000 | 1.97922195 | 1.723227 | 16.70 | 12.75 | 0.00800000 | 37036.7 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.09939702 | 60.00 | 32.22 | 27.78 | 0.000 | 11362.85 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00760935 | 21.00 | 0.00760935 | 46.9508 | 2691.68 | 0.00 | 11426.35 | 11426.35 | 1.97922195 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 22.26 | 15.32 | 0.00800000 | 42707.9 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13522.247 | 13522.247 | 0.836593 | 0.00011830 | 319.002 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.72258911 | 54.44 | 82.22 | 27.78 | 667359.73 | 2.0262 | 2.067009 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 13522.25 | 13522.25 | 1.0000 | 0.96087346 | 0.836593 | 16.70 | 12.75 | 0.00800000 | 37036.7 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.11828645 | 60.00 | 32.22 | 27.78 | 0.000 | 13522.25 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00779448 | 21.00 | 0.00779448 | 48.0786 | 9311.01 | 0.00 | 13594.22 | 13594.22 | 0.96087346 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 30.47 | 18.20 | 0.00800000 | 51082.5 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 33993.079 | 33993.079 | 2.592411 | 0.00029739 | 773.744 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.72258911 | 54.44 | 82.22 | 27.78 | 667359.73 | 5.0937 | 5.196178 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 33993.08 | 33993.08 | 1.0000 | 2.97752853 | 2.592411 | 16.70 | 12.75 | 0.00800000 | 37036.7 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.29735594 | 60.00 | 32.22 | 27.78 | 0.000 | 33993.08 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00774082 | 21.00 | 0.00774082 | 47.7510 | 20944.03 | 0.00 | 34176.06 | 34176.06 | 2.97752853 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 27.86 | 17.31 | 0.00800000 | 48412.7 | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13352.217 | -999.000 | 1.238453 | 0.00038186 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8551 | 1004.8586 | 1.1486 | ROOM_1_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.238453 | 1.42243188 | 4197.9300 | 999.8980 | 29.58695447 | 15.03 | 6.70 | 8.33 | 1034619.02 | 1.2905 | 1.290520 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | unknown | unknown | 7/21 17:10:00 | Sensible | 13352.22 | 13007.78 | 1.0000 | 1.42243188 | 1.238453 | 21.71 | 15.19 | 0.00861512 | 43709.1 | 12.80 | 11.68 | 0.00850000 | 34322.2 | 0.38182563 | 6.70 | 15.03 | 8.33 | 0.000 | 13352.22 | 29.54 | 0.01536201 | 22.68 | 0.00000000 | 0.0000 | 21.11 | 0.00861512 | 21.11 | 0.00861512 | 52.7115 | 12064.85 | 0.00 | 13999.01 | 13999.01 | 1.42243188 | 21.71 | 15.67 | 0.00861512 | 43709.1 | 12.07 | 11.91 | 0.00861512 | 33867.5 | |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8040.391 | 8040.391 | 0.363434 | 0.00007034 | 229.738 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ROOM_1_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.238453 | 1.42243188 | 4197.9300 | 999.8980 | 5.72258911 | 54.44 | 82.22 | 27.78 | 667359.73 | 1.2048 | 1.229053 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 8040.39 | 8040.39 | 1.0000 | 0.41742374 | 0.363434 | 21.11 | 14.21 | 0.00775288 | 40906.3 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.07033367 | 60.00 | 32.22 | 27.78 | 0.000 | 8040.39 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.11 | 0.00775288 | 21.11 | 0.00775288 | 47.5006 | 8040.52 | 0.00 | 8667.75 | 8667.75 | 0.41742374 | 16.60 | 12.91 | 0.00775288 | 36309.1 | 36.97 | 20.08 | 0.00775288 | 57073.9 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12962.943 | -999.000 | 1.201277 | 0.00037073 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8612 | 1004.8586 | 1.1486 | ROOM_2_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.201277 | 1.37973378 | 4197.9300 | 999.8980 | 29.58695447 | 15.03 | 6.70 | 8.33 | 1034619.02 | 1.2529 | 1.252896 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | unknown | unknown | 7/21 17:10:00 | Sensible | 12962.94 | 12619.24 | 1.0000 | 1.37973378 | 1.201277 | 21.71 | 15.20 | 0.00861841 | 43717.4 | 12.80 | 11.68 | 0.00850000 | 34322.2 | 0.37069380 | 6.70 | 15.03 | 8.33 | 0.000 | 12962.94 | 29.54 | 0.01536201 | 22.68 | 0.00000000 | 0.0000 | 21.11 | 0.00861841 | 21.11 | 0.00861841 | 52.7314 | 11702.68 | 0.00 | 13590.49 | 13590.49 | 1.37973378 | 21.71 | 15.67 | 0.00861841 | 43717.4 | 12.06 | 11.91 | 0.00861841 | 33867.4 | |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8060.734 | 8060.734 | 0.364353 | 0.00007052 | 230.319 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ROOM_2_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.201277 | 1.37973378 | 4197.9300 | 999.8980 | 5.72258911 | 54.44 | 82.22 | 27.78 | 667359.73 | 1.2079 | 1.232163 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 8060.73 | 8060.73 | 1.0000 | 0.41847987 | 0.364353 | 21.11 | 14.21 | 0.00775350 | 40907.9 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.07051162 | 60.00 | 32.22 | 27.78 | 0.000 | 8060.73 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.11 | 0.00775350 | 21.11 | 0.00775350 | 47.5044 | 8060.86 | 0.00 | 8689.68 | 8689.68 | 0.41847987 | 16.60 | 12.91 | 0.00775350 | 36310.7 | 36.97 | 20.08 | 0.00775350 | 57075.5 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 78939.233 | -999.000 | 7.459558 | 0.00225761 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7278 | 1004.8586 | 1.1486 | ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 7.459558 | 8.56771893 | 4197.9300 | 999.8980 | 29.58695447 | 15.03 | 6.70 | 8.33 | 1034619.02 | 7.6298 | 7.629645 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | unknown | unknown | unknown | 7/21 13:30:00 | Sensible | 78939.23 | 78100.92 | 1.0000 | 8.56771893 | 7.459558 | 21.71 | 15.13 | 0.00854667 | 43535.8 | 12.80 | 11.68 | 0.00850000 | 34322.2 | 2.25737961 | 6.70 | 15.03 | 8.33 | 0.000 | 78939.23 | 30.93 | 0.01536459 | 23.06 | 0.00000000 | 0.0000 | 21.11 | 0.00854667 | 21.11 | 0.00854667 | 52.2967 | 72674.77 | 0.00 | 82802.51 | 82802.51 | 8.56771893 | 21.71 | 15.61 | 0.00854667 | 43535.8 | 12.24 | 11.92 | 0.00854667 | 33871.3 | |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 45677.696 | 45677.696 | 2.064712 | 0.00039961 | 1305.138 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 7.459558 | 8.56771893 | 4197.9300 | 999.8980 | 5.72258911 | 54.44 | 82.22 | 27.78 | 667359.73 | 6.8445 | 6.982288 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 45677.70 | 45677.70 | 1.0000 | 2.37143692 | 2.064712 | 21.11 | 14.22 | 0.00776890 | 40947.3 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.39956765 | 60.00 | 32.22 | 27.78 | 0.000 | 45677.70 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.11 | 0.00776890 | 21.11 | 0.00776890 | 47.5966 | 45678.05 | 0.00 | 49241.98 | 49241.98 | 2.37143692 | 16.60 | 12.93 | 0.00776890 | 36349.6 | 36.97 | 20.10 | 0.00776890 | 57114.3 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 71203.108 | -999.000 | 6.310144 | 0.00203636 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1754 | 1004.8586 | 1.1486 | ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 6.310144 | 7.24755296 | 4197.9300 | 999.8980 | 29.58695447 | 15.03 | 6.70 | 8.33 | 1034619.02 | 6.8821 | 6.881932 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | unknown | unknown | unknown | 7/21 19:00:00 | Sensible | 71203.11 | 66787.57 | 1.0000 | 7.24755296 | 6.310144 | 21.71 | 15.34 | 0.00878741 | 44146.6 | 12.80 | 11.68 | 0.00850000 | 34322.2 | 2.03615411 | 6.70 | 15.03 | 8.33 | 0.000 | 71203.11 | 27.07 | 0.01535744 | 22.00 | 0.00000000 | 0.0000 | 21.11 | 0.00878741 | 21.11 | 0.00878741 | 53.7514 | 61471.68 | 0.00 | 74575.65 | 71904.58 | 7.24755296 | 21.71 | 15.82 | 0.00878741 | 44146.6 | 11.99 | 11.91 | 0.00864135 | 33856.9 | |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 46060.795 | 46060.795 | 2.082029 | 0.00040296 | 1316.083 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 6.310144 | 7.24755296 | 4197.9300 | 999.8980 | 5.72258911 | 54.44 | 82.22 | 27.78 | 667359.73 | 6.9019 | 7.040848 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 46060.80 | 46060.80 | 1.0000 | 2.39132619 | 2.082029 | 21.11 | 14.22 | 0.00777071 | 40951.9 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.40291883 | 60.00 | 32.22 | 27.78 | 0.000 | 46060.80 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.11 | 0.00777071 | 21.11 | 0.00777071 | 47.6076 | 46061.15 | 0.00 | 49654.98 | 49654.98 | 2.39132619 | 16.60 | 12.93 | 0.00777071 | 36354.2 | 36.97 | 20.10 | 0.00777071 | 57118.8 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12218.036 | -999.000 | 1.129664 | 0.00034943 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8769 | 1004.8586 | 1.1486 | ROOM_5_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.129664 | 1.29748198 | 4197.9300 | 999.8980 | 29.58695447 | 15.03 | 6.70 | 8.33 | 1034619.02 | 1.1809 | 1.180899 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | unknown | unknown | unknown | 7/21 09:40:00 | Sensible | 12218.04 | 11871.60 | 1.0000 | 1.29748198 | 1.129664 | 21.71 | 15.20 | 0.00862687 | 43738.9 | 12.80 | 11.68 | 0.00850000 | 34322.2 | 0.34939212 | 6.70 | 15.03 | 8.33 | 0.000 | 12218.04 | 26.57 | 0.01535653 | 21.86 | 0.00000000 | 0.0000 | 21.11 | 0.00862687 | 21.11 | 0.00862687 | 52.7825 | 11005.02 | 0.00 | 12808.59 | 12808.59 | 1.29748198 | 21.71 | 15.68 | 0.00862687 | 43738.9 | 12.04 | 11.91 | 0.00862687 | 33867.0 | |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7999.257 | 7999.257 | 0.361574 | 0.00006998 | 228.562 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ROOM_5_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.129664 | 1.29748198 | 4197.9300 | 999.8980 | 5.72258911 | 54.44 | 82.22 | 27.78 | 667359.73 | 1.1986 | 1.222766 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 7999.26 | 7999.26 | 1.0000 | 0.41528825 | 0.361574 | 21.11 | 14.21 | 0.00775165 | 40903.2 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.06997385 | 60.00 | 32.22 | 27.78 | 0.000 | 7999.26 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.11 | 0.00775165 | 21.11 | 0.00775165 | 47.4932 | 7999.38 | 0.00 | 8623.40 | 8623.40 | 0.41528825 | 16.60 | 12.91 | 0.00775165 | 36306.0 | 36.97 | 20.08 | 0.00775165 | 57070.8 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11889.026 | -999.000 | 1.098120 | 0.00034002 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8840 | 1004.8586 | 1.1486 | ROOM_6_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.098120 | 1.26125224 | 4197.9300 | 999.8980 | 29.58695447 | 15.03 | 6.70 | 8.33 | 1034619.02 | 1.1491 | 1.149100 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | unknown | unknown | unknown | 7/21 09:10:00 | Sensible | 11889.03 | 11542.13 | 1.0000 | 1.26125224 | 1.098120 | 21.71 | 15.21 | 0.00863066 | 43748.6 | 12.80 | 11.68 | 0.00850000 | 34322.2 | 0.33998359 | 6.70 | 15.03 | 8.33 | 0.000 | 11889.03 | 25.67 | 0.01535487 | 21.60 | 0.00000000 | 0.0000 | 21.11 | 0.00863066 | 21.11 | 0.00863066 | 52.8054 | 10697.72 | 0.00 | 12463.28 | 12463.28 | 1.26125224 | 21.71 | 15.68 | 0.00863066 | 43748.6 | 12.03 | 11.91 | 0.00863066 | 33866.9 | |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8019.608 | 8019.608 | 0.362494 | 0.00007016 | 229.144 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ROOM_6_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.098120 | 1.26125224 | 4197.9300 | 999.8980 | 5.72258911 | 54.44 | 82.22 | 27.78 | 667359.73 | 1.2017 | 1.225876 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 8019.61 | 8019.61 | 1.0000 | 0.41634481 | 0.362494 | 21.11 | 14.21 | 0.00775228 | 40904.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.07015187 | 60.00 | 32.22 | 27.78 | 0.000 | 8019.61 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.11 | 0.00775228 | 21.11 | 0.00775228 | 47.4970 | 8019.73 | 0.00 | 8645.34 | 8645.34 | 0.41634481 | 16.60 | 12.91 | 0.00775228 | 36307.6 | 36.97 | 20.08 | 0.00775228 | 57072.4 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 16739.816 | 16739.816 | 0.821392 | 0.00014645 | 416.035 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.72258911 | 54.44 | 82.22 | 27.78 | 667359.73 | 2.5084 | 2.558847 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 16739.82 | 16739.82 | 1.0000 | 0.94341410 | 0.821392 | 16.70 | 12.75 | 0.00800000 | 37036.7 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.14643228 | 60.00 | 32.22 | 27.78 | 0.000 | 16739.82 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00780687 | 21.00 | 0.00780687 | 48.1531 | 12604.71 | 0.00 | 16826.26 | 16826.26 | 0.94341410 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 34.09 | 19.37 | 0.00800000 | 54770.2 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3469.772 | -999.000 | 0.322218 | 0.00009923 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8468 | 1004.8586 | 1.1486 | ROOM_1_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.322218 | 0.37008502 | 4197.9300 | 999.8980 | 29.58695447 | 15.03 | 6.70 | 8.33 | 1034619.02 | 0.3354 | 0.335361 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | unknown | unknown | 7/21 17:00:00 | Sensible | 3469.77 | 3383.64 | 1.0000 | 0.37008502 | 0.322218 | 21.71 | 15.19 | 0.00861067 | 43697.8 | 12.80 | 11.68 | 0.00850000 | 34322.2 | 0.09922307 | 6.70 | 15.03 | 8.33 | 0.000 | 3469.77 | 29.72 | 0.01536233 | 22.73 | 0.00000000 | 0.0000 | 21.11 | 0.00861067 | 21.11 | 0.00861067 | 52.6847 | 3139.01 | 0.00 | 3637.99 | 3637.99 | 0.37008502 | 21.71 | 15.66 | 0.00861067 | 43697.8 | 12.08 | 11.91 | 0.00861067 | 33867.7 | |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2471.342 | 2471.342 | 0.111707 | 0.00002162 | 70.612 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ROOM_1_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.322218 | 0.37008502 | 4197.9300 | 999.8980 | 5.72258911 | 54.44 | 82.22 | 27.78 | 667359.73 | 0.3703 | 0.377769 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 2471.34 | 2471.34 | 1.0000 | 0.12830189 | 0.111707 | 21.11 | 14.25 | 0.00779774 | 41020.3 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.02161817 | 60.00 | 32.22 | 27.78 | 0.000 | 2471.34 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.11 | 0.00779774 | 21.11 | 0.00779774 | 47.7720 | 2471.38 | 0.00 | 2664.17 | 2664.17 | 0.12830189 | 16.60 | 12.95 | 0.00779774 | 36422.6 | 36.97 | 20.12 | 0.00779774 | 57187.5 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3360.102 | -999.000 | 0.311738 | 0.00009610 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8533 | 1004.8586 | 1.1486 | ROOM_2_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.311738 | 0.35804904 | 4197.9300 | 999.8980 | 29.58695447 | 15.03 | 6.70 | 8.33 | 1034619.02 | 0.3248 | 0.324761 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | unknown | unknown | 7/21 17:10:00 | Sensible | 3360.10 | 3274.12 | 1.0000 | 0.35804904 | 0.311738 | 21.71 | 15.19 | 0.00861416 | 43706.7 | 12.80 | 11.68 | 0.00850000 | 34322.2 | 0.09608690 | 6.70 | 15.03 | 8.33 | 0.000 | 3360.10 | 29.54 | 0.01536201 | 22.68 | 0.00000000 | 0.0000 | 21.11 | 0.00861416 | 21.11 | 0.00861416 | 52.7058 | 3036.92 | 0.00 | 3522.90 | 3522.90 | 0.35804904 | 21.71 | 15.67 | 0.00861416 | 43706.7 | 12.07 | 11.91 | 0.00861416 | 33867.5 | |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2478.910 | 2478.910 | 0.112049 | 0.00002169 | 70.828 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ROOM_2_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.311738 | 0.35804904 | 4197.9300 | 999.8980 | 5.72258911 | 54.44 | 82.22 | 27.78 | 667359.73 | 0.3715 | 0.378926 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 2478.91 | 2478.91 | 1.0000 | 0.12869478 | 0.112049 | 21.11 | 14.25 | 0.00779835 | 41021.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.02168437 | 60.00 | 32.22 | 27.78 | 0.000 | 2478.91 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.11 | 0.00779835 | 21.11 | 0.00779835 | 47.7758 | 2478.95 | 0.00 | 2672.33 | 2672.33 | 0.12869478 | 16.60 | 12.95 | 0.00779835 | 36424.2 | 36.97 | 20.12 | 0.00779835 | 57189.1 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 16216.378 | -999.000 | 1.482977 | 0.00046378 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9531 | 1004.8586 | 1.1486 | ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 1.482977 | 1.70328211 | 4197.9300 | 999.8980 | 29.58695447 | 15.03 | 6.70 | 8.33 | 1034619.02 | 1.5674 | 1.567347 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | unknown | unknown | unknown | 7/21 13:40:00 | Sensible | 16216.38 | 15613.58 | 1.0000 | 1.70328211 | 1.482977 | 21.71 | 15.24 | 0.00866784 | 43842.9 | 12.80 | 11.68 | 0.00850000 | 34322.2 | 0.46373039 | 6.70 | 15.03 | 8.33 | 0.000 | 16216.38 | 31.02 | 0.01536476 | 23.08 | 0.00000000 | 0.0000 | 21.11 | 0.00866784 | 21.11 | 0.00866784 | 53.0302 | 14446.70 | 0.00 | 16996.46 | 16996.46 | 1.70328211 | 21.71 | 15.71 | 0.00866784 | 43842.9 | 11.94 | 11.91 | 0.00866784 | 33864.2 | |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11788.126 | 11788.126 | 0.532838 | 0.00010313 | 336.812 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 1.482977 | 1.70328211 | 4197.9300 | 999.8980 | 5.72258911 | 54.44 | 82.22 | 27.78 | 667359.73 | 1.7664 | 1.801932 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 11788.13 | 11788.13 | 1.0000 | 0.61199456 | 0.532838 | 21.11 | 14.25 | 0.00780456 | 41037.7 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.10311715 | 60.00 | 32.22 | 27.78 | 0.000 | 11788.13 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.11 | 0.00780456 | 21.11 | 0.00780456 | 47.8130 | 11788.27 | 0.00 | 12707.93 | 12707.93 | 0.61199456 | 16.60 | 12.96 | 0.00780456 | 36439.9 | 36.97 | 20.12 | 0.00780456 | 57204.7 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13932.124 | 13932.124 | 1.127773 | 0.00012188 | 314.388 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.72258911 | 54.44 | 82.22 | 27.78 | 667359.73 | 2.0876 | 2.129663 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 13932.12 | 13932.12 | 1.0000 | 1.29531077 | 1.127773 | 16.70 | 12.75 | 0.00800000 | 37036.7 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.12187187 | 60.00 | 32.22 | 27.78 | 0.000 | 13932.12 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00785021 | 21.00 | 0.00785021 | 48.4174 | 8254.30 | 0.00 | 14007.36 | 14007.36 | 1.29531077 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 27.20 | 17.09 | 0.00800000 | 47748.6 | |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14376.362 | 14376.362 | 1.182267 | 0.00012577 | 323.701 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.72258911 | 54.44 | 82.22 | 27.78 | 667359.73 | 2.1542 | 2.197569 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | Sensible | 14376.36 | 14376.36 | 1.0000 | 1.35789924 | 1.182267 | 16.70 | 12.75 | 0.00800000 | 37036.7 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.12575786 | 60.00 | 32.22 | 27.78 | 0.000 | 14376.36 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00785318 | 21.00 | 0.00785318 | 48.4358 | 8424.31 | 0.00 | 14454.06 | 14454.06 | 1.35789924 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 27.04 | 17.03 | 0.00800000 | 47579.2 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9373.978 | 9373.978 | 1.198272 | 0.00008201 | 201.269 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.72258911 | 54.44 | 82.22 | 27.78 | 667359.73 | 1.4046 | 1.432905 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | Sensible | 9373.98 | 9373.98 | 1.0000 | 1.37628199 | 1.198272 | 16.70 | 12.75 | 0.00800000 | 37036.7 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.08199928 | 60.00 | 32.22 | 27.78 | 0.000 | 9373.98 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.70 | 0.00732190 | 21.00 | 0.00732190 | 45.2024 | 3349.83 | 0.00 | 9426.15 | 9426.15 | 1.37628199 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 23.32 | 15.71 | 0.00800000 | 43783.7 | |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10678.239 | 10678.239 | 0.403677 | 0.00009342 | 287.973 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.72258911 | 54.44 | 82.22 | 27.78 | 667359.73 | 1.6001 | 1.632274 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | Sensible | 10678.24 | 10678.24 | 1.0000 | 0.46364524 | 0.403677 | 16.70 | 12.75 | 0.00800000 | 37036.7 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.09340836 | 60.00 | 32.22 | 27.78 | 0.000 | 10678.24 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00787430 | 21.00 | 0.00787430 | 48.5640 | 8645.81 | 0.00 | 10731.35 | 10731.35 | 0.46364524 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 39.30 | 20.97 | 0.00800000 | 60080.3 | |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 87803.637 | -999.000 | 2.051317 | 0.00251117 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1033.4029 | 1004.8586 | 1.1486 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.35596953 | 4197.9300 | 999.8980 | 29.58695447 | 15.03 | 6.70 | 8.33 | 1034619.02 | 8.4866 | 8.486567 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | Sensible | 87803.64 | 47531.07 | 1.0000 | 2.35605237 | 2.051317 | 31.20 | 23.13 | 0.01536508 | 70669.3 | 11.90 | 11.31 | 0.00850000 | 33402.1 | 2.51091675 | 6.70 | 15.03 | 8.33 | 2195.006 | 85608.63 | 31.20 | 0.01536508 | 23.13 | 2.05124512 | 99.9965 | 21.11 | 0.00865978 | 21.11 | 0.00865992 | 52.9812 | 185628.53 | 0.00 | 89691.54 | 48118.14 | 2.35605237 | 31.20 | 23.70 | 0.01536508 | 70669.3 | 11.44 | 11.40 | 0.00836907 | 32600.8 | |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 30469.718 | 30469.718 | 0.615395 | 0.00026656 | 443.506 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.35596953 | 4197.9300 | 999.8980 | 5.72258911 | 54.44 | 82.22 | 27.78 | 667359.73 | 4.5657 | 4.657598 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 30469.72 | 30469.72 | 1.0000 | 0.70681571 | 0.615395 | -26.20 | -26.20 | 0.00036134 | -25440.7 | 16.70 | 12.75 | 0.00800000 | 37036.7 | 0.26653519 | 60.00 | 32.22 | 27.78 | 0.000 | 30469.72 | -26.20 | 0.00036134 | -26.20 | 2.05124512 | 333.3216 | 21.11 | 0.00776978 | 21.11 | 0.00777003 | 47.6035 | 140598.29 | 0.00 | 22379.93 | 22379.93 | 0.70681571 | 2.80 | -3.86 | 0.00036134 | 3719.1 | 34.29 | 12.71 | 0.00036134 | 35382.2 | |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 723208.741 | -999.000 | 22.908878 | 0.02068368 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1028.2024 | 1004.8586 | 1.1486 | VAV WITH REHEAT FAN | Fan:VariableVolume | 22.908878 | 26.31212587 | 4197.9300 | 999.8980 | 29.58695447 | 15.03 | 6.70 | 8.33 | 1034619.02 | 69.9010 | 69.900971 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | Sensible | 723208.74 | 450213.42 | 1.0000 | 26.31212587 | 22.908878 | 27.66 | 20.25 | 0.01256753 | 59871.5 | 10.90 | 10.89 | 0.00850000 | 32385.7 | 20.68156849 | 6.70 | 15.03 | 8.33 | 51330.518 | 671878.22 | 31.20 | 0.01536508 | 23.13 | 11.66146000 | 50.9037 | 23.99 | 0.00966509 | 23.99 | 0.00962559 | 49.3569 | 300441.40 | 0.00 | 742715.66 | 449600.85 | 26.31212587 | 27.66 | 20.79 | 0.01256753 | 59871.5 | 11.04 | 11.00 | 0.00814950 | 31644.3 | |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 340282.358 | 340282.358 | 6.872664 | 0.00297694 | 4953.023 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | VAV WITH REHEAT FAN | Fan:VariableVolume | 22.908878 | 26.31212587 | 4197.9300 | 999.8980 | 5.72258911 | 54.44 | 82.22 | 27.78 | 667359.73 | 50.9893 | 52.015526 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 340282.36 | 340282.36 | 1.0000 | 7.89363776 | 6.872664 | -26.20 | -26.20 | 0.00036134 | -25440.7 | 16.70 | 12.75 | 0.00800000 | 37036.7 | 2.97663484 | 60.00 | 32.22 | 27.78 | 0.000 | 340282.36 | -26.20 | 0.00036134 | -26.20 | 11.66146000 | 169.6789 | 20.96 | 0.00777691 | 21.00 | 0.00778233 | 47.9905 | 82874.77 | 0.00 | 249936.54 | 249936.54 | 7.89363776 | 2.80 | -3.86 | 0.00036134 | 3719.1 | 34.29 | 12.71 | 0.00036134 | 35382.2 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:56
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - | |||
VAV WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 22.91 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | VAV WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000610 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LAUNDRY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CAFE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001448 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_3 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
KITCHEN_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003556 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 856.67 | 7103.83 | 459.83 |
RETAIL_1_FLR_1 | 3401.33 | 7216.67 | 2355.33 |
RETAIL_2_FLR_1 | 2103.67 | 6969.50 | 1137.83 |
MECH_FLR_1 | 2260.50 | 7506.00 | 1869.83 |
STORAGE_FLR_1 | 2341.83 | 8105.67 | 2249.33 |
LAUNDRY_FLR_1 | 6863.00 | 3474.33 | 2651.50 |
CAFE_FLR_1 | 3634.50 | 6329.67 | 1876.17 |
LOBBY_FLR_1 | 2651.67 | 6308.17 | 1189.67 |
ROOM_1_FLR_3 | 2859.67 | 8240.67 | 2755.00 |
ROOM_2_FLR_3 | 3769.33 | 8021.83 | 3452.50 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 2364.83 | 8681.17 | 2341.17 |
ROOM_5_FLR_3 | 2745.33 | 8186.83 | 2709.83 |
ROOM_6_FLR_3 | 3603.67 | 7939.17 | 3348.33 |
CORRIDOR_FLR_3 | 2243.50 | 8244.50 | 2170.83 |
ROOM_1_FLR_6 | 3427.67 | 8163.17 | 3238.33 |
ROOM_2_FLR_6 | 4342.67 | 7993.67 | 4004.00 |
ROOM_3_MULT9_FLR_6 | 2266.83 | 8151.67 | 2199.33 |
BANQUET_FLR_6 | 3965.50 | 4266.33 | 1069.83 |
DINING_FLR_6 | 4430.00 | 3145.67 | 938.33 |
KITCHEN_FLR_6 | 8054.67 | 6305.83 | 5946.00 |
CORRIDOR_FLR_6 | 2883.67 | 7210.50 | 2019.00 |
Facility | 8754.83 | 8760.00 | 7993.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 170.67 | 0.00 | 170.67 | 0.00 |
RETAIL_1_FLR_1 | 172.83 | 0.00 | 172.83 | 0.00 |
RETAIL_2_FLR_1 | 184.83 | 0.00 | 184.83 | 0.00 |
MECH_FLR_1 | 236.33 | 0.00 | 236.33 | 0.00 |
STORAGE_FLR_1 | 260.00 | 0.00 | 260.00 | 0.00 |
LAUNDRY_FLR_1 | 140.83 | 0.00 | 140.83 | 0.00 |
CAFE_FLR_1 | 169.50 | 0.00 | 169.50 | 0.00 |
LOBBY_FLR_1 | 174.83 | 0.00 | 174.83 | 0.00 |
ROOM_1_FLR_3 | 37.50 | 3.83 | 37.50 | 3.83 |
ROOM_2_FLR_3 | 73.33 | 6.00 | 73.33 | 6.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 112.67 | 18.00 | 112.67 | 18.00 |
ROOM_5_FLR_3 | 51.67 | 0.00 | 51.67 | 0.00 |
ROOM_6_FLR_3 | 80.17 | 18.17 | 80.17 | 18.17 |
CORRIDOR_FLR_3 | 210.33 | 0.00 | 210.33 | 0.00 |
ROOM_1_FLR_6 | 46.67 | 7.33 | 46.67 | 7.33 |
ROOM_2_FLR_6 | 86.00 | 12.17 | 86.00 | 12.17 |
ROOM_3_MULT9_FLR_6 | 10.33 | 5.33 | 10.33 | 5.33 |
BANQUET_FLR_6 | 121.67 | 0.00 | 121.67 | 0.00 |
DINING_FLR_6 | 119.17 | 0.00 | 119.17 | 0.00 |
KITCHEN_FLR_6 | 94.33 | 0.00 | 94.33 | 0.00 |
CORRIDOR_FLR_6 | 213.33 | 0.00 | 213.33 | 0.00 |
Facility | 280.83 | 44.00 | 280.83 | 44.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:56
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.75 | 106.50 | 4826.41 | 1.015 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 2.815 | 0.063 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 1.441 | 0.021 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.528 | 0.024 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.544 | 0.024 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 23.924 | 0.068 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.50 | 142.30 | 748.35 | 4.173 | 0.050 | 0.000 | 0.000 |
LOBBY_FLR_1 | 244.92 | 422.44 | 5183.56 | 1.878 | 0.021 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.355 | 0.082 | 0.000 | 0.055 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.356 | 0.082 | 0.000 | 0.046 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.403 | 0.036 | 0.000 | 0.085 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.355 | 0.082 | 0.000 | 0.055 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.355 | 0.082 | 0.000 | 0.053 |
CORRIDOR_FLR_3 | 12.15 | 20.96 | 1186.91 | 0.632 | 0.010 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.355 | 0.082 | 0.000 | 0.067 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.356 | 0.082 | 0.000 | 0.052 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.403 | 0.067 | 0.000 | 0.106 |
BANQUET_FLR_6 | 144.89 | 249.90 | 1010.89 | 4.840 | 0.024 | 0.000 | 0.000 |
DINING_FLR_6 | 144.89 | 249.90 | 1010.89 | 5.235 | 0.024 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.89 | 22.24 | 314.87 | 22.519 | 0.068 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.86 | 22.18 | 1256.16 | 1.179 | 0.017 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.75 | 106.50 | 4826.41 | 0.875 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 2.468 | 0.001 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 1.333 | 0.000 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.498 | 0.000 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.514 | 0.000 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 18.574 | 0.001 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.50 | 142.30 | 748.35 | 3.824 | 0.001 | 0.000 | 0.000 |
LOBBY_FLR_1 | 244.92 | 422.44 | 5183.56 | 1.720 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
CORRIDOR_FLR_3 | 12.15 | 20.96 | 1186.91 | 0.596 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.000 | 0.001 | 0.000 | 0.000 |
BANQUET_FLR_6 | 144.89 | 249.90 | 1010.89 | 3.835 | 0.000 | 0.000 | 0.000 |
DINING_FLR_6 | 144.89 | 249.90 | 1010.89 | 4.020 | 0.000 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.89 | 22.24 | 314.87 | 12.856 | 0.001 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.86 | 22.18 | 1256.16 | 1.107 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:24:56
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | VAV WITH REHEAT | 61.75 | 106.50 | 4826.41 | 1978.83 | 0.0000 | 0.854 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 6.28 | 10.83 | 265.76 | 67.07 | 0.0000 | 0.079 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 7.27 | 12.54 | 307.76 | 77.67 | 0.0000 | 0.092 |
MECH_FLR_1 | VAV WITH REHEAT | 1.54 | 2.65 | 650.80 | 164.24 | 0.0000 | 0.000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 1.18 | 2.04 | 375.47 | 94.76 | 0.0000 | 0.058 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 4.87 | 8.40 | 309.22 | 78.04 | 0.0000 | 0.000 |
CAFE_FLR_1 | VAV WITH REHEAT | 82.50 | 142.30 | 748.35 | 188.86 | 0.0000 | 0.676 |
LOBBY_FLR_1 | VAV WITH REHEAT | 244.92 | 422.44 | 5183.56 | 1308.19 | 0.0000 | 1.894 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 1.50 | 74.75 | 24.52 | 0.0000 | 0.837 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.837 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 12.15 | 20.96 | 1186.91 | 389.40 | 0.0000 | 0.475 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.015 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.015 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.099 |
BANQUET_FLR_6 | VAV WITH REHEAT | 144.89 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
DINING_FLR_6 | VAV WITH REHEAT | 144.89 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 12.89 | 22.24 | 314.87 | 103.30 | 0.0000 | 0.367 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 12.86 | 22.18 | 1256.16 | 412.12 | 0.0000 | 0.126 |
Total Facility | 872.69 | 1604.23 | 35184.81 | 11345.29 | 0.0000 | 137.584 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 42144471.22 | 0.00 | 42144471.22 | 0.00 | 42144471.22 | 26946214.98 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_1_FLR_1 | 6464968.63 | 0.00 | 6464968.63 | 145101.77 | 6610070.40 | 2498216.28 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_2_FLR_1 | 3819394.45 | 0.00 | 3819394.45 | 56009.47 | 3875403.91 | 2892943.94 | 0.00 | 0.00 | 8760.00 | 0.00 |
MECH_FLR_1 | 2964246.80 | 0.00 | 2964246.80 | 132373.10 | 3096619.90 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
STORAGE_FLR_1 | 1765917.04 | 0.00 | 1765917.04 | 76371.99 | 1842289.03 | 1821682.01 | 8751.04 | 3.79 | 5.17 | 0.00 |
LAUNDRY_FLR_1 | 63671716.65 | 0.00 | 63671716.65 | 180748.71 | 63852465.36 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
CAFE_FLR_1 | 26875687.56 | 0.00 | 26875687.56 | 320755.67 | 27196443.23 | 21330615.53 | 0.00 | 0.00 | 8760.00 | 0.00 |
LOBBY_FLR_1 | 83654967.52 | 0.00 | 83654967.52 | 916472.22 | 84571439.73 | 59728886.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
ROOM_1_FLR_3 | 1460156.71 | 56729.39 | 1516886.11 | 84221.76 | 1601107.87 | 1946875.62 | 2190.00 | 6004.00 | 566.00 | 0.00 |
ROOM_2_FLR_3 | 1459985.63 | 46760.30 | 1506745.94 | 84215.33 | 1590961.27 | 1946647.51 | 2190.00 | 6110.73 | 459.28 | 0.00 |
ROOM_3_MULT19_FLR_3 | 1099911.97 | 0.00 | 1099911.97 | 23498.82 | 1123410.79 | 26397887.27 | 8395.00 | 365.00 | 0.00 | 365.00 |
ROOM_4_MULT19_FLR_3 | 19803829.30 | 54562.08 | 19858391.38 | 23505.24 | 19881896.62 | 26405105.73 | 2190.00 | 6014.07 | 555.93 | 0.00 |
ROOM_5_FLR_3 | 1460156.71 | 56823.53 | 1516980.25 | 84221.76 | 1601202.01 | 1946875.62 | 2190.00 | 6004.00 | 566.00 | 0.00 |
ROOM_6_FLR_3 | 1459985.63 | 53579.27 | 1513564.90 | 84215.33 | 1597780.24 | 1946647.51 | 2190.00 | 6009.64 | 560.36 | 0.00 |
CORRIDOR_FLR_3 | 25903125.43 | 0.00 | 25903125.43 | 101841.05 | 26004966.48 | 14972100.18 | 0.00 | 0.00 | 8760.00 | 0.00 |
ROOM_1_FLR_6 | 365039.18 | 68527.24 | 433566.41 | 84239.76 | 517806.17 | 486718.90 | 2043.85 | 6004.35 | 711.80 | 0.00 |
ROOM_2_FLR_6 | 364996.41 | 52706.28 | 417702.68 | 84233.33 | 501936.02 | 486661.88 | 2071.11 | 6138.67 | 550.22 | 0.00 |
ROOM_3_MULT9_FLR_6 | 2345190.31 | 68464.62 | 2413654.93 | 43100.01 | 2456754.94 | 3126920.42 | 2190.00 | 6003.00 | 567.00 | 0.00 |
BANQUET_FLR_6 | 41894502.75 | 0.00 | 41894502.75 | 205692.33 | 42100195.08 | 37458366.31 | 4135.89 | 219.22 | 4404.89 | 0.00 |
DINING_FLR_6 | 45310752.31 | 0.00 | 45310752.31 | 205692.33 | 45516444.64 | 37458366.31 | 0.00 | 3026.43 | 5733.57 | 0.00 |
KITCHEN_FLR_6 | 60733042.15 | 0.00 | 60733042.15 | 184142.32 | 60917184.47 | 11584760.86 | 0.00 | 0.00 | 8760.00 | 0.00 |
CORRIDOR_FLR_6 | 12789059.38 | 0.00 | 12789059.38 | 180228.23 | 12969287.61 | 3961413.96 | 0.00 | 0.00 | 8760.00 | 0.00 |
Total Facility | 0.21E+10 | 5739703.39 | 0.21E+10 | 8487130.57 | 0.21E+10 | 0.43E+10 | 8760.00 | 7690.09 | 8760.00 | 365.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 1.3364 | 0.0000 | 1.3364 | 0.0000 | 1.3364 | 0.8545 | 0.00 | 0.00 | 8760.00 |
RETAIL_1_FLR_1 | 0.2050 | 0.0000 | 0.2050 | 0.0046 | 0.2096 | 0.0792 | 0.00 | 0.00 | 8760.00 |
RETAIL_2_FLR_1 | 0.1211 | 0.0000 | 0.1211 | 0.0018 | 0.1229 | 0.0917 | 0.00 | 0.00 | 8760.00 |
MECH_FLR_1 | 0.0940 | 0.0000 | 0.0940 | 0.0042 | 0.0982 | 0.0000 | 0.00 | 0.00 | 8760.00 |
STORAGE_FLR_1 | 0.0560 | 0.0000 | 0.0560 | 0.0024 | 0.0584 | 0.0578 | 8751.04 | 3.79 | 5.17 |
LAUNDRY_FLR_1 | 2.0190 | 0.0000 | 2.0190 | 0.0057 | 2.0247 | 0.0000 | 0.00 | 0.00 | 8760.00 |
CAFE_FLR_1 | 0.8522 | 0.0000 | 0.8522 | 0.0102 | 0.8624 | 0.6764 | 0.00 | 0.00 | 8760.00 |
LOBBY_FLR_1 | 2.6527 | 0.0000 | 2.6527 | 0.0291 | 2.6817 | 1.8940 | 0.00 | 0.00 | 8760.00 |
ROOM_1_FLR_3 | 0.0463 | 0.0018 | 0.0481 | 0.0027 | 0.0508 | 0.0617 | 2190.00 | 6004.00 | 566.00 |
ROOM_2_FLR_3 | 0.0463 | 0.0015 | 0.0478 | 0.0027 | 0.0504 | 0.0617 | 2190.00 | 6110.73 | 459.28 |
ROOM_4_MULT19_FLR_3 | 0.6280 | 0.0017 | 0.6297 | 0.0007 | 0.6305 | 0.8373 | 2190.00 | 6014.07 | 555.93 |
ROOM_5_FLR_3 | 0.0463 | 0.0018 | 0.0481 | 0.0027 | 0.0508 | 0.0617 | 2190.00 | 6004.00 | 566.00 |
ROOM_6_FLR_3 | 0.0463 | 0.0017 | 0.0480 | 0.0027 | 0.0507 | 0.0617 | 2190.00 | 6009.64 | 560.36 |
CORRIDOR_FLR_3 | 0.8214 | 0.0000 | 0.8214 | 0.0032 | 0.8246 | 0.4748 | 0.00 | 0.00 | 8760.00 |
ROOM_1_FLR_6 | 0.0116 | 0.0022 | 0.0137 | 0.0027 | 0.0164 | 0.0154 | 2043.85 | 6004.35 | 711.80 |
ROOM_2_FLR_6 | 0.0116 | 0.0017 | 0.0132 | 0.0027 | 0.0159 | 0.0154 | 2071.11 | 6138.67 | 550.22 |
ROOM_3_MULT9_FLR_6 | 0.0744 | 0.0022 | 0.0765 | 0.0014 | 0.0779 | 0.0992 | 2190.00 | 6003.00 | 567.00 |
BANQUET_FLR_6 | 1.3285 | 0.0000 | 1.3285 | 0.0065 | 1.3350 | 1.1878 | 4135.89 | 219.22 | 4404.89 |
DINING_FLR_6 | 1.4368 | 0.0000 | 1.4368 | 0.0065 | 1.4433 | 1.1878 | 0.00 | 3026.43 | 5733.57 |
KITCHEN_FLR_6 | 1.9258 | 0.0000 | 1.9258 | 0.0058 | 1.9317 | 0.3674 | 0.00 | 0.00 | 8760.00 |
CORRIDOR_FLR_6 | 0.4055 | 0.0000 | 0.4055 | 0.0057 | 0.4113 | 0.1256 | 0.00 | 0.00 | 8760.00 |
Total Facility | 64.8779 | 0.1820 | 65.0599 | 0.2125 | 65.2724 | 73.9670 | 8760.00 | 7690.09 | 8760.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
FLR_3_DOAS | 39336975.27 | 458152.71 | 39795127.98 | 64690340.46 | 8755.50 | 1.17 | 3.33 | 0.00 |
VAV WITH REHEAT | 0.55E+09 | 0.00 | 0.55E+09 | 0.22E+09 | 0.00 | 0.00 | 8760.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
FLR_3_DOAS | 1.2474 | 0.0145 | 1.2619 | 2.0513 | 8755.50 | 1.17 | 3.33 |
VAV WITH REHEAT | 17.4850 | 0.0000 | 17.4850 | 6.9969 | 0.00 | 0.00 | 8760.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
FLR_3_DOAS | 0.00 | 0.00 | 0.00 | 0.00 | 6935.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
VAV WITH REHEAT | 0.00 | 0.00 | 3472.58 | 0.00 | 0.00 | 0.00 | 5287.42 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
FLR_3_DOAS | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.5756 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
VAV WITH REHEAT | 0.0000 | 0.0000 | 18.0447 | 0.0000 | 0.0000 | 0.0000 | 17.1208 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:56
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1333 |
Defaulted Fields | 1182 |
Fields with Defaults | 4000 |
Autosized Fields | 349 |
Autosizable Fields | 402 |
Autocalculated Fields | 280 |
Autocalculatable Fields | 539 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:24:56
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 4963.46 | 69686.77 | 27-MAY-04:40 | 402842.58 | 26-JUL-18:30 |
Electricity:Building | 2446.80 | 31063.18 | 17-JUN-05:00 | 151313.73 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 304.40 | 3493.55 | 02-JAN-02:10 | 22822.84 | 02-JAN-20:10 |
Electricity:SpaceType:GENERAL | 2439.71 | 30922.03 | 17-JUN-05:00 | 151072.40 | 02-JAN-20:10 |
InteriorLights:Electricity | 781.53 | 6720.06 | 17-JUN-05:00 | 64632.59 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 161.29 | 1465.65 | 02-JAN-02:10 | 13190.31 | 02-JAN-20:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 781.53 | 6720.06 | 17-JUN-05:00 | 64632.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 781.53 | 6720.06 | 17-JUN-05:00 | 64632.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 161.29 | 1465.65 | 02-JAN-02:10 | 13190.31 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 781.53 | 6720.06 | 17-JUN-05:00 | 64632.59 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 17.49 | 210.74 | 02-JAN-02:10 | 1283.20 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 7.31 | 66.40 | 02-JAN-02:10 | 597.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 7.31 | 66.40 | 02-JAN-02:10 | 597.59 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 20.26 | 244.03 | 02-JAN-02:10 | 1485.95 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 8.46 | 76.89 | 02-JAN-02:10 | 692.02 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 8.46 | 76.89 | 02-JAN-02:10 | 692.02 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 20.84 | 252.75 | 02-JAN-02:10 | 1523.62 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.37 | 76.02 | 02-JAN-02:10 | 684.18 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.37 | 76.02 | 02-JAN-02:10 | 684.18 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 6.68 | 78.96 | 02-JAN-02:10 | 493.99 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 3.08 | 27.98 | 02-JAN-02:10 | 251.84 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 3.08 | 27.98 | 02-JAN-02:10 | 251.84 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 71.91 | 998.82 | 02-JAN-02:10 | 4897.88 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 3.98 | 36.12 | 02-JAN-02:10 | 325.08 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 3.98 | 36.12 | 02-JAN-02:10 | 325.08 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 28.32 | 293.96 | 03-JUN-05:00 | 2666.80 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 13.98 | 83.19 | 01-JAN-13:10 | 1701.53 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 | 13.98 | 83.19 | 01-JAN-13:10 | 1701.53 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 258.79 | 3093.58 | 03-JUN-05:00 | 19534.01 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 109.79 | 982.16 | 03-JUN-05:00 | 9504.80 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 109.79 | 982.16 | 03-JUN-05:00 | 9504.80 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 19.72 | 257.38 | 01-JAN-02:10 | 1438.51 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 19.72 | 257.35 | 01-JAN-02:10 | 1438.34 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 305.38 | 4267.82 | 01-JAN-02:10 | 22404.45 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 110.39 | 934.58 | 01-JAN-02:10 | 8496.21 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 110.39 | 934.58 | 01-JAN-02:10 | 8496.21 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 305.47 | 4268.99 | 01-JAN-02:10 | 22410.58 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 110.42 | 934.84 | 01-JAN-02:10 | 8498.53 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 110.42 | 934.84 | 01-JAN-02:10 | 8498.53 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 19.72 | 257.38 | 01-JAN-02:10 | 1438.51 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 19.72 | 257.35 | 01-JAN-02:10 | 1438.34 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 4.93 | 64.34 | 01-JAN-02:10 | 359.63 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 2.31 | 19.57 | 01-JAN-02:10 | 177.88 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 2.31 | 19.57 | 01-JAN-02:10 | 177.88 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 4.93 | 64.34 | 01-JAN-02:10 | 359.59 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 2.31 | 19.56 | 01-JAN-02:10 | 177.86 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 2.31 | 19.56 | 01-JAN-02:10 | 177.86 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 36.17 | 505.54 | 01-JAN-02:10 | 2653.88 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 13.08 | 110.70 | 01-JAN-02:10 | 1006.40 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 13.08 | 110.70 | 01-JAN-02:10 | 1006.40 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 206.52 | 2448.50 | 17-JUN-05:00 | 9735.93 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 30.67 | 199.20 | 17-JUN-05:00 | 2988.03 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 30.67 | 199.20 | 17-JUN-05:00 | 2988.03 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 206.52 | 2448.50 | 17-JUN-05:00 | 9735.93 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 30.67 | 199.20 | 17-JUN-05:00 | 2988.03 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 | 30.67 | 199.20 | 17-JUN-05:00 | 2988.03 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 453.81 | 6249.79 | 02-JAN-02:10 | 18934.39 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 12.97 | 117.87 | 02-JAN-02:10 | 1060.81 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 12.97 | 117.87 | 02-JAN-02:10 | 1060.81 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1658.18 | 24201.97 | 02-JAN-02:10 | 89171.45 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 1658.18 | 24201.97 | 02-JAN-02:10 | 89171.45 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 433.74 | 5990.78 | 01-JAN-00:10 | 16487.34 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 410.33 | 5248.28 | 01-JAN-00:10 | 15744.84 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
Refrigeration:Electricity | 61.43 | 778.74 | 02-FEB-23:30 | 3263.91 | 12-SEP-06:20 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
Electricity:Plant | 809.70 | 2732.63 | 27-APR-01:30 | 215132.62 | 04-AUG-15:20 |
LowTempRefrigeration:Refrigeration:Electricity | 20.31 | 0.00 | 01-JAN-11:10 | 1894.53 | 29-JUL-10:50 |
MedTempRefrigeration:Refrigeration:Electricity | 34.03 | 511.54 | 02-FEB-06:00 | 1202.35 | 25-AUG-13:40 |
Fans:Electricity | 515.93 | 10598.75 | 05-JAN-08:10 | 36043.43 | 07-SEP-22:00 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 721.27 | 12424.38 | 14-NOV-15:00 | 44499.53 | 03-AUG-21:10 |
ExteriorEquipment:Electricity | 813.77 | 9999.82 | 02-JAN-02:20 | 49607.07 | 02-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 21.77 | 380.96 | 17-JUN-05:00 | 1291.59 | 02-JAN-21:10 |
ElectricityPurchased:Facility | 4963.46 | 69686.77 | 27-MAY-04:40 | 402842.58 | 26-JUL-18:30 |
ElectricityPurchased:Plant | 4963.46 | 69686.77 | 27-MAY-04:40 | 402842.58 | 26-JUL-18:30 |
Cogeneration:ElectricityPurchased | 4963.46 | 69686.77 | 27-MAY-04:40 | 402842.58 | 26-JUL-18:30 |
General:Cogeneration:ElectricityPurchased | 4963.46 | 69686.77 | 27-MAY-04:40 | 402842.58 | 26-JUL-18:30 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 4963.46 | 69686.77 | 27-MAY-04:40 | 402842.58 | 26-JUL-18:30 |
ElectricityNet:Plant | 4963.46 | 69686.77 | 27-MAY-04:40 | 402842.58 | 26-JUL-18:30 |
Cogeneration:ElectricityNet | 4963.46 | 69686.77 | 27-MAY-04:40 | 402842.58 | 26-JUL-18:30 |
General:Cogeneration:ElectricityNet | 4963.46 | 69686.77 | 27-MAY-04:40 | 402842.58 | 26-JUL-18:30 |
General:Fans:Electricity | 515.93 | 10598.75 | 05-JAN-08:10 | 36043.43 | 07-SEP-22:00 |
ExteriorLights:Electricity | 193.69 | 0.00 | 01-JAN-08:00 | 12338.45 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 193.69 | 0.00 | 01-JAN-08:00 | 12338.45 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 789.09 | 9600.00 | 01-JAN-00:10 | 48128.80 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 2.91 | 18.80 | 01-JAN-00:10 | 188.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 183.57 | 0.00 | 24-FEB-11:40 | 9938.94 | 06-JAN-10:40 |
General:HeatRecovery:Electricity | 183.57 | 0.00 | 24-FEB-11:40 | 9938.94 | 06-JAN-10:40 |
WaterSystems:Electricity | 94.79 | 1222.48 | 02-AUG-01:00 | 4772.05 | 02-FEB-07:10 |
Water Heater:WaterSystems:Electricity | 94.79 | 1222.48 | 02-AUG-01:00 | 4772.05 | 02-FEB-07:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 580.67 | 0.00 | 01-JAN-00:10 | 206703.84 | 04-AUG-15:20 |
General:Cooling:Electricity | 580.67 | 0.00 | 01-JAN-00:10 | 206703.84 | 04-AUG-15:20 |
Pumps:Electricity | 79.90 | 48.18 | 25-OCT-14:40 | 4999.18 | 30-JAN-16:30 |
General:Pumps:Electricity | 79.90 | 48.18 | 25-OCT-14:40 | 4999.18 | 30-JAN-16:30 |
WIRED_LTG_ELECTRICITY | 27.51 | 0.00 | 01-JAN-00:10 | 2275.07 | 02-JAN-20:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 6956.37 | 25767.43 | 19-AUG-02:20 | 1075624.60 | 02-FEB-21:30 |
NaturalGas:Building | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Laundry:InteriorEquipment:NaturalGas | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
NaturalGas:Plant | 5167.53 | 12405.53 | 19-AUG-02:20 | 1000500.84 | 02-FEB-21:30 |
WaterSystems:NaturalGas | 2901.70 | 12405.53 | 19-AUG-02:20 | 269507.31 | 21-FEB-21:20 |
Water Heater:WaterSystems:NaturalGas | 2901.70 | 12405.53 | 19-AUG-02:20 | 269507.31 | 21-FEB-21:20 |
Heating:NaturalGas | 2265.83 | 0.00 | 25-FEB-15:30 | 775417.27 | 02-FEB-06:00 |
Boiler:Heating:NaturalGas | 2265.83 | 0.00 | 25-FEB-15:30 | 775417.27 | 02-FEB-06:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 2368.80 | 0.00 | 01-JAN-00:10 | 690525.39 | 26-JUL-18:30 |
PlantLoopCoolingDemand:HVAC | 2368.80 | 0.00 | 01-JAN-00:10 | 690525.39 | 26-JUL-18:30 |
CoolingCoils:PlantLoopCoolingDemand | 2368.80 | 0.00 | 01-JAN-00:10 | 690525.39 | 26-JUL-18:30 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 9857.19 | 0.00 | 02-JAN-01:20 | 0.00 | 05-JAN-21:20 |
Water:Plant | 9857.19 | 0.00 | 02-JAN-01:20 | 0.00 | 05-JAN-21:20 |
WaterSystems:Water | 9857.19 | 0.00 | 02-JAN-01:20 | 0.00 | 05-JAN-21:20 |
Water Heater:WaterSystems:Water | 5742.51 | 0.00 | 19-JAN-02:10 | 0.00 | 02-JAN-19:20 |
MainsWater:Facility | 9857.19 | 0.00 | 02-JAN-01:20 | 0.00 | 05-JAN-21:20 |
MainsWater:Plant | 9857.19 | 0.00 | 02-JAN-01:20 | 0.00 | 05-JAN-21:20 |
WaterSystems:MainsWater | 9857.19 | 0.00 | 02-JAN-01:20 | 0.00 | 05-JAN-21:20 |
Water Heater:WaterSystems:MainsWater | 5742.51 | 0.00 | 19-JAN-02:10 | 0.00 | 02-JAN-19:20 |
WaterUse:WaterSystems:Water | 4114.69 | 0.00 | 02-JAN-01:20 | 0.00 | 05-JAN-07:40 |
WaterUse:WaterSystems:MainsWater | 4114.69 | 0.00 | 02-JAN-01:20 | 0.00 | 05-JAN-07:40 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 21748.99 | 152431.60 | 06-JUN-11:40 | 2948548.95 | 26-JUL-18:30 |
EnergyTransfer:Building | 4903.44 | 65667.56 | 06-FEB-11:10 | 342511.06 | 26-JUN-18:10 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 708.52 | 8676.83 | 05-FEB-04:00 | 36628.72 | 02-JUL-10:50 |
Refrigeration:EnergyTransfer | 181.03 | 1372.43 | 02-FEB-04:00 | 10373.23 | 12-SEP-06:20 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 90.52 | 686.22 | 02-FEB-04:00 | 5186.62 | 12-SEP-06:20 |
General:Refrigeration:EnergyTransfer | 90.52 | 686.22 | 02-FEB-04:00 | 5186.62 | 12-SEP-06:20 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 90.52 | 686.22 | 02-FEB-04:00 | 5186.62 | 12-SEP-06:20 |
EnergyTransfer:Plant | 8037.55 | 18007.73 | 10-APR-01:10 | 1618585.44 | 26-JUL-18:30 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 21.55 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 68.97 | 484.63 | 02-FEB-06:00 | 2557.05 | 25-AUG-13:40 |
EnergyTransfer:Zone:BASEMENT | 391.14 | 85.09 | 05-FEB-18:10 | 36285.49 | 26-NOV-06:40 |
Heating:EnergyTransfer | 309.21 | 0.00 | 12-JAN-14:10 | 113257.14 | 12-DEC-16:20 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.17 | 0.00 | 01-JAN-00:10 | 5532.48 | 04-FEB-11:30 |
General:Heating:EnergyTransfer | 309.21 | 0.00 | 12-JAN-14:10 | 113257.14 | 12-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.17 | 0.00 | 01-JAN-00:10 | 5532.48 | 04-FEB-11:30 |
Cooling:EnergyTransfer | 4503.72 | 14426.53 | 04-FEB-11:20 | 338889.28 | 26-JUN-18:10 |
Cooling:EnergyTransfer:Zone:BASEMENT | 390.97 | 0.00 | 04-FEB-11:20 | 36285.49 | 26-NOV-06:40 |
General:Cooling:EnergyTransfer | 4503.72 | 14426.53 | 04-FEB-11:20 | 338889.28 | 26-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 390.97 | 0.00 | 04-FEB-11:20 | 36285.49 | 26-NOV-06:40 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 38.64 | 0.02 | 22-APR-03:00 | 4596.05 | 07-SEP-13:00 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 3.64 | 0.00 | 01-JAN-10:20 | 2490.65 | 20-JAN-08:00 |
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 3.64 | 0.00 | 01-JAN-10:20 | 2490.65 | 20-JAN-08:00 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 35.00 | 0.00 | 01-JAN-00:10 | 4596.05 | 07-SEP-13:00 |
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 35.00 | 0.00 | 01-JAN-00:10 | 4596.05 | 07-SEP-13:00 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 31.67 | 0.01 | 26-NOV-12:30 | 2026.55 | 30-JUN-21:00 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.09 | 0.00 | 01-JAN-00:10 | 1128.91 | 04-FEB-11:30 |
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.09 | 0.00 | 01-JAN-00:10 | 1128.91 | 04-FEB-11:30 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 31.58 | 0.00 | 06-JAN-10:40 | 2026.55 | 30-JUN-21:00 |
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 31.58 | 0.00 | 06-JAN-10:40 | 2026.55 | 30-JUN-21:00 |
EnergyTransfer:Zone:MECH_FLR_1 | 20.30 | 0.00 | 01-FEB-20:20 | 1721.58 | 04-FEB-11:30 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 1.44 | 0.00 | 01-JAN-00:10 | 1721.58 | 04-FEB-11:30 |
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 | 1.44 | 0.00 | 01-JAN-00:10 | 1721.58 | 04-FEB-11:30 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 18.86 | 0.00 | 01-JAN-13:10 | 1562.87 | 30-JUN-20:00 |
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 18.86 | 0.00 | 01-JAN-13:10 | 1562.87 | 30-JUN-20:00 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 11.87 | 0.00 | 09-FEB-02:20 | 1161.92 | 04-FEB-11:30 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 2.16 | 0.00 | 01-JAN-20:10 | 1161.92 | 04-FEB-11:30 |
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 2.16 | 0.00 | 01-JAN-20:10 | 1161.92 | 04-FEB-11:30 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 9.70 | 0.00 | 01-JAN-00:10 | 706.73 | 30-JUN-10:40 |
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 9.70 | 0.00 | 01-JAN-00:10 | 706.73 | 30-JUN-10:40 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 590.07 | 4043.27 | 04-FEB-11:20 | 38807.15 | 26-JUN-20:00 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 376.69 | 04-FEB-11:20 |
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 376.69 | 04-FEB-11:20 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 590.07 | 3666.58 | 04-FEB-11:20 | 38807.15 | 26-JUN-20:00 |
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 590.07 | 3666.58 | 04-FEB-11:20 | 38807.15 | 26-JUN-20:00 |
EnergyTransfer:Zone:CAFE_FLR_1 | 216.70 | 1.63 | 19-JAN-14:30 | 15207.84 | 04-NOV-12:50 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.28 | 0.00 | 01-JAN-00:10 | 4975.45 | 20-JAN-08:00 |
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.28 | 0.00 | 01-JAN-00:10 | 4975.45 | 20-JAN-08:00 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 216.42 | 0.00 | 07-JAN-16:40 | 15207.84 | 04-NOV-12:50 |
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 216.42 | 0.00 | 07-JAN-16:40 | 15207.84 | 04-NOV-12:50 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 737.43 | 15.25 | 04-FEB-21:00 | 40762.87 | 07-SEP-21:10 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.36 | 0.00 | 01-JAN-00:10 | 16968.19 | 04-FEB-11:30 |
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.36 | 0.00 | 01-JAN-00:10 | 16968.19 | 04-FEB-11:30 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 737.08 | 0.00 | 06-JAN-10:50 | 40762.87 | 07-SEP-21:10 |
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 737.08 | 0.00 | 06-JAN-10:50 | 40762.87 | 07-SEP-21:10 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 71.25 | 0.00 | 01-JAN-08:10 | 11968.56 | 06-SEP-15:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 28.31 | 0.00 | 01-JAN-08:10 | 7687.82 | 09-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 28.31 | 0.00 | 01-JAN-08:10 | 7687.82 | 09-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 42.93 | 0.00 | 01-JAN-00:10 | 11968.56 | 06-SEP-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 42.93 | 0.00 | 01-JAN-00:10 | 11968.56 | 06-SEP-15:10 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 65.49 | 0.00 | 01-JAN-08:10 | 13465.86 | 16-JUN-17:00 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 34.19 | 0.00 | 01-JAN-08:10 | 7692.67 | 04-FEB-19:20 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 34.19 | 0.00 | 01-JAN-08:10 | 7692.67 | 04-FEB-19:20 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 31.30 | 0.00 | 01-JAN-00:10 | 13465.86 | 16-JUN-17:00 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 31.30 | 0.00 | 01-JAN-00:10 | 13465.86 | 16-JUN-17:00 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 253.98 | 0.00 | 01-JAN-07:20 | 54869.62 | 07-SEP-13:00 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 11.98 | 0.00 | 01-JAN-07:20 | 22538.12 | 19-JAN-05:00 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 11.98 | 0.00 | 01-JAN-07:20 | 22538.12 | 19-JAN-05:00 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 242.00 | 0.00 | 01-JAN-00:10 | 54869.62 | 07-SEP-13:00 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 242.00 | 0.00 | 01-JAN-00:10 | 54869.62 | 07-SEP-13:00 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 380.49 | 0.00 | 01-JAN-08:10 | 69598.84 | 25-JUN-18:20 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 97.36 | 0.00 | 01-JAN-08:10 | 42957.52 | 04-FEB-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 97.36 | 0.00 | 01-JAN-08:10 | 42957.52 | 04-FEB-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 283.13 | 0.00 | 01-JAN-00:10 | 69598.84 | 25-JUN-18:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 283.13 | 0.00 | 01-JAN-00:10 | 69598.84 | 25-JUN-18:20 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 70.43 | 0.00 | 01-JAN-08:10 | 11248.91 | 02-JUL-08:10 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 28.32 | 0.00 | 01-JAN-08:10 | 7524.23 | 09-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 28.32 | 0.00 | 01-JAN-08:10 | 7524.23 | 09-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 42.11 | 0.00 | 01-JAN-00:10 | 11248.91 | 02-JUL-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 42.11 | 0.00 | 01-JAN-00:10 | 11248.91 | 02-JUL-08:10 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 65.17 | 0.00 | 01-JAN-08:10 | 12700.68 | 09-JUN-09:00 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 34.21 | 0.00 | 01-JAN-08:10 | 7663.74 | 04-FEB-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 34.21 | 0.00 | 01-JAN-08:10 | 7663.74 | 04-FEB-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 30.95 | 0.00 | 01-JAN-00:10 | 12700.68 | 09-JUN-09:00 |
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 30.95 | 0.00 | 01-JAN-00:10 | 12700.68 | 09-JUN-09:00 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 167.43 | 0.19 | 29-JAN-14:10 | 10403.37 | 02-JUL-10:40 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 6.74 | 0.00 | 01-JAN-00:10 | 9064.62 | 04-FEB-11:30 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 6.74 | 0.00 | 01-JAN-00:10 | 9064.62 | 04-FEB-11:30 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 160.69 | 0.00 | 01-JAN-12:20 | 10403.37 | 02-JUL-10:40 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 160.69 | 0.00 | 01-JAN-12:20 | 10403.37 | 02-JUL-10:40 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 20.98 | 0.00 | 01-JAN-08:10 | 3238.74 | 04-AUG-15:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 10.41 | 0.00 | 01-JAN-08:10 | 2305.14 | 09-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 10.41 | 0.00 | 01-JAN-08:10 | 2305.14 | 09-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 10.56 | 0.00 | 01-JAN-00:10 | 3238.74 | 04-AUG-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 10.56 | 0.00 | 01-JAN-00:10 | 3238.74 | 04-AUG-15:10 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 20.12 | 0.00 | 01-JAN-08:10 | 3682.88 | 16-JUN-17:00 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 12.26 | 0.00 | 01-JAN-08:10 | 2351.46 | 02-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 12.26 | 0.00 | 01-JAN-08:10 | 2351.46 | 02-FEB-08:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 7.86 | 0.00 | 01-JAN-00:10 | 3682.88 | 16-JUN-17:00 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 7.86 | 0.00 | 01-JAN-00:10 | 3682.88 | 16-JUN-17:00 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 94.59 | 0.00 | 01-JAN-08:10 | 16713.33 | 06-SEP-15:10 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 29.67 | 0.00 | 01-JAN-08:10 | 10767.76 | 09-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 29.67 | 0.00 | 01-JAN-08:10 | 10767.76 | 09-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 64.92 | 0.00 | 01-JAN-00:10 | 16713.33 | 06-SEP-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 64.92 | 0.00 | 01-JAN-00:10 | 16713.33 | 06-SEP-15:10 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 413.00 | 20.42 | 04-FEB-13:30 | 23000.53 | 26-JUN-21:20 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.02 | 0.00 | 01-JAN-00:10 | 4200.58 | 04-FEB-11:30 |
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.02 | 0.00 | 01-JAN-00:10 | 4200.58 | 04-FEB-11:30 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 412.98 | 0.00 | 31-JAN-11:40 | 23000.53 | 26-JUN-21:20 |
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 412.98 | 0.00 | 31-JAN-11:40 | 23000.53 | 26-JUN-21:20 |
EnergyTransfer:Zone:DINING_FLR_6 | 452.91 | 35.26 | 04-FEB-12:20 | 24221.16 | 26-JUN-21:20 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.01 | 0.00 | 01-JAN-00:10 | 3760.87 | 04-FEB-11:30 |
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.01 | 0.00 | 01-JAN-00:10 | 3760.87 | 04-FEB-11:30 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 452.90 | 0.00 | 31-JAN-11:40 | 24221.16 | 26-JUN-21:20 |
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 452.90 | 0.00 | 31-JAN-11:40 | 24221.16 | 26-JUN-21:20 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 618.00 | 6693.55 | 05-FEB-04:00 | 31560.15 | 02-JUL-10:50 |
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 618.00 | 6693.55 | 05-FEB-04:00 | 31560.15 | 02-JUL-10:50 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 81.27 | 0.13 | 03-JAN-22:50 | 6818.49 | 04-FEB-11:30 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 7.57 | 0.00 | 01-JAN-00:10 | 6818.49 | 04-FEB-11:30 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 7.57 | 0.00 | 01-JAN-00:10 | 6818.49 | 04-FEB-11:30 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 73.71 | 0.00 | 01-JAN-02:00 | 6698.50 | 04-AUG-15:10 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 73.71 | 0.00 | 01-JAN-02:00 | 6698.50 | 04-AUG-15:10 |
PlantLoopHeatingDemand:Facility | 2522.00 | 10271.17 | 21-AUG-00:10 | 679756.05 | 02-FEB-07:10 |
PlantLoopHeatingDemand:Plant | 864.96 | 10271.17 | 21-AUG-00:10 | 64708.90 | 21-FEB-07:20 |
WaterSystems:PlantLoopHeatingDemand | 864.96 | 10271.17 | 21-AUG-00:10 | 64708.90 | 21-FEB-07:20 |
General:WaterSystems:PlantLoopHeatingDemand | 864.96 | 10271.17 | 21-AUG-00:10 | 64708.90 | 21-FEB-07:20 |
EnergyTransfer:HVAC | 8808.00 | 2522.95 | 08-NOV-18:40 | 1022266.44 | 26-JUL-18:30 |
HeatingCoils:EnergyTransfer | 1657.04 | 0.00 | 19-MAR-11:30 | 624262.54 | 02-FEB-06:00 |
PlantLoopHeatingDemand:HVAC | 1657.04 | 0.00 | 19-MAR-11:30 | 624262.54 | 02-FEB-06:00 |
HeatingCoils:PlantLoopHeatingDemand | 1657.04 | 0.00 | 19-MAR-11:30 | 624262.54 | 02-FEB-06:00 |
CoolingCoils:EnergyTransfer | 2368.80 | 0.00 | 01-JAN-00:10 | 690525.39 | 26-JUL-18:30 |
HeatRecoveryForHeating:EnergyTransfer | 4558.40 | 0.00 | 05-JAN-08:00 | 564017.16 | 08-DEC-21:20 |
HeatRecoveryForCooling:EnergyTransfer | 223.76 | 0.00 | 01-JAN-00:10 | 337775.98 | 26-JUL-19:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 864.96 | 10271.17 | 21-AUG-00:10 | 64708.90 | 21-FEB-07:20 |
WaterUse:WaterSystems:EnergyTransfer | 864.96 | 10271.17 | 21-AUG-00:10 | 64708.90 | 21-FEB-07:20 |
Boilers:EnergyTransfer | 1645.44 | 0.00 | 25-FEB-15:30 | 621924.34 | 02-FEB-06:00 |
Chillers:EnergyTransfer | 2427.99 | 0.00 | 01-JAN-00:10 | 692656.68 | 26-JUL-18:30 |
HeatRejection:EnergyTransfer | 3008.65 | 0.00 | 01-JAN-00:10 | 889314.30 | 26-JUL-18:30 |
General:HeatRejection:EnergyTransfer | 3008.65 | 0.00 | 01-JAN-00:10 | 889314.30 | 26-JUL-18:30 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:56
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.172 | -390.971 | 0.000 | 0.000 | 141.943 | 161.294 | 143.105 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -55.543 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 3.635 | -35.004 | 0.000 | 0.000 | 15.721 | 7.307 | 10.186 | 25.347 | 0.000 | 0.040 | 0.000 | 0.000 | -14.111 | 0.000 | -2.715 | -10.406 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.087 | -31.584 | 0.000 | 0.000 | 17.191 | 8.462 | 11.795 | 0.000 | 0.000 | 0.016 | 0.000 | 0.000 | 0.000 | 0.000 | -1.098 | -4.869 |
MECH_FLR_1 | 0.000 | 0.000 | 1.441 | -18.859 | 0.000 | 0.000 | 3.745 | 8.366 | 12.471 | 0.000 | 0.000 | 0.038 | 0.000 | 0.000 | 0.000 | 0.000 | -2.530 | -4.673 |
STORAGE_FLR_1 | 0.000 | 0.000 | 2.163 | -9.704 | 0.000 | 0.000 | 2.918 | 3.079 | 3.598 | 0.000 | 0.000 | 0.023 | 0.000 | 0.000 | 0.000 | 0.000 | -1.442 | -0.635 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.000 | -590.074 | 0.000 | 0.000 | 11.348 | 3.975 | 658.131 | 0.000 | 0.000 | 0.060 | 0.000 | 0.000 | 0.000 | 0.000 | -3.641 | -79.800 |
CAFE_FLR_1 | 0.000 | 0.000 | 0.283 | -216.418 | 0.000 | 0.000 | 195.687 | 13.979 | 14.341 | 70.486 | 0.000 | 0.085 | 0.000 | 0.000 | -41.411 | 0.000 | -6.276 | -30.756 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.357 | -737.083 | 0.000 | 0.000 | 566.627 | 109.788 | 148.998 | 93.072 | 0.000 | 0.257 | 0.000 | 0.000 | -56.203 | 0.000 | -18.314 | -107.500 |
ROOM_1_FLR_3 | 33.574 | -36.938 | 0.000 | -11.252 | 0.000 | 0.000 | 9.747 | 9.244 | 10.478 | 47.623 | 0.000 | 0.226 | 0.000 | 0.000 | -32.944 | 0.000 | -6.902 | -22.856 |
ROOM_2_FLR_3 | 39.763 | -25.116 | 0.000 | -11.757 | 0.000 | 0.000 | 9.613 | 9.243 | 10.477 | 33.514 | 0.000 | 0.144 | 0.000 | 0.000 | -34.968 | 0.000 | -7.220 | -23.693 |
ROOM_3_MULT19_FLR_3 | 11.977 | -229.482 | 0.006 | -12.516 | 0.000 | 0.000 | 0.000 | 110.385 | 194.997 | 287.124 | 0.000 | 0.129 | 0.002 | 0.000 | -199.069 | 0.000 | -37.788 | -125.765 |
ROOM_4_MULT19_FLR_3 | 153.947 | -183.551 | 0.000 | -156.140 | 0.000 | 0.000 | 183.752 | 110.415 | 195.050 | 84.704 | 0.000 | 1.080 | 0.000 | 0.000 | -198.309 | 0.000 | -49.937 | -141.011 |
ROOM_5_FLR_3 | 33.542 | -36.079 | 0.000 | -11.250 | 0.000 | 0.000 | 9.744 | 9.244 | 10.478 | 46.394 | 0.000 | 0.227 | 0.000 | 0.000 | -32.381 | 0.000 | -6.919 | -23.001 |
ROOM_6_FLR_3 | 39.784 | -24.842 | 0.000 | -11.682 | 0.000 | 0.000 | 9.646 | 9.243 | 10.477 | 32.101 | 0.000 | 0.145 | 0.000 | 0.000 | -34.145 | 0.000 | -7.312 | -23.415 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 6.735 | -160.692 | 0.000 | 0.000 | 119.587 | 91.336 | 0.000 | 42.307 | 0.000 | 0.119 | 0.000 | 0.000 | -42.263 | 0.000 | -7.738 | -49.391 |
ROOM_1_FLR_6 | 11.848 | -9.190 | 0.000 | -2.809 | 0.000 | 0.000 | 2.440 | 2.311 | 2.620 | 11.842 | 0.000 | 0.060 | 0.000 | 0.000 | -8.216 | 0.000 | -1.757 | -9.148 |
ROOM_2_FLR_6 | 13.745 | -6.394 | 0.000 | -2.944 | 0.000 | 0.000 | 2.403 | 2.311 | 2.619 | 8.329 | 0.000 | 0.036 | 0.000 | 0.000 | -8.742 | 0.000 | -1.828 | -9.536 |
ROOM_3_MULT9_FLR_6 | 37.048 | -54.104 | 0.000 | -18.193 | 0.000 | 0.000 | 21.857 | 13.076 | 23.098 | 65.379 | 0.000 | 0.387 | 0.000 | 0.000 | -38.172 | 0.000 | -9.031 | -41.343 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.023 | -412.982 | 0.000 | 0.000 | 320.656 | 30.666 | 175.857 | 8.702 | 0.000 | 0.047 | 0.000 | 0.000 | -25.749 | 0.000 | -4.309 | -92.911 |
DINING_FLR_6 | 0.000 | 0.000 | 0.014 | -452.901 | 0.000 | 0.000 | 319.055 | 30.666 | 175.857 | 8.513 | 0.000 | 0.046 | 0.000 | 0.000 | -26.349 | 0.000 | -4.340 | -50.561 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.000 | -617.988 | 0.000 | 0.000 | 28.673 | 12.972 | 550.372 | 21.712 | 0.000 | 0.041 | 25.109 | 0.000 | -17.000 | 0.000 | -3.892 | -0.002 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 7.567 | -73.707 | 0.000 | 0.000 | 31.705 | 24.166 | 0.000 | 20.853 | 0.000 | 0.044 | 11.654 | 0.000 | -18.857 | 0.000 | -3.425 | -0.001 |
Total Facility | 375.228 | -605.696 | 22.486 | -3986.509 | 0.000 | 0.000 | 2024.058 | 781.531 | 2365.005 | 908.001 | 0.000 | 3.250 | 36.765 | 0.000 | -828.889 | 0.000 | -188.415 | -906.816 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 26-NOV-07:07 | 0.00 | 0.00 | 0.00 | -36861.97 | 0.00 | 0.00 | 6163.62 | 5862.42 | 5069.75 | 0.00 | 0.00 | 0.00 | 19766.18 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 07-SEP-13:00 | 0.00 | 0.00 | 0.00 | -4594.66 | 0.00 | 0.00 | 150.61 | 166.00 | 252.59 | 5799.84 | 0.00 | 37.98 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1812.35 |
RETAIL_2_FLR_1 | 25-NOV-21:12 | 0.00 | 0.00 | 0.00 | -2051.65 | 0.00 | 0.00 | 722.57 | 538.23 | 668.57 | 0.00 | 0.00 | 0.00 | 226.51 | 0.00 | -0.00 | 0.00 | -104.24 | 0.00 |
MECH_FLR_1 | 30-JUN-19:53 | 0.00 | 0.00 | 0.00 | -1563.76 | 0.00 | 0.00 | 129.08 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -3.25 | -85.70 |
STORAGE_FLR_1 | 30-JUN-10:33 | 0.00 | 0.00 | 0.00 | -708.79 | 0.00 | 0.00 | 29.18 | 69.95 | 89.22 | 0.00 | 0.00 | 11.50 | 508.95 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 05-JAN-21:42 | 0.00 | 0.00 | 0.00 | -39796.90 | 0.00 | 0.00 | 501.48 | 288.96 | 41967.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -350.20 | -2611.17 |
CAFE_FLR_1 | 04-NOV-12:50 | 0.00 | 0.00 | 0.00 | -15206.72 | 0.00 | 0.00 | 2968.73 | 103.98 | 355.63 | 20144.06 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -120.32 | -8245.37 |
LOBBY_FLR_1 | 19-JAN-01:51 | 0.00 | 0.00 | 0.00 | -64018.14 | 0.00 | 0.00 | 31293.21 | 1584.13 | 2639.27 | 0.00 | 0.00 | 0.00 | 37202.86 | 0.00 | -7006.27 | 0.00 | -1695.06 | 0.00 |
ROOM_1_FLR_3 | 21-MAY-18:01 | 0.00 | -15974.82 | 0.00 | -546.89 | 0.00 | 0.00 | 283.22 | 711.53 | 484.65 | 6639.00 | 0.00 | 0.00 | 9004.87 | 0.00 | -0.00 | 0.00 | -601.55 | 0.00 |
ROOM_2_FLR_3 | 20-MAY-18:41 | 0.00 | -17667.05 | 0.00 | -646.57 | 0.00 | 0.00 | 244.02 | 711.45 | 484.60 | 2810.15 | 0.00 | 0.00 | 14195.12 | 0.00 | -0.00 | 0.00 | -131.72 | 0.00 |
ROOM_3_MULT19_FLR_3 | 07-SEP-13:00 | 0.00 | -54870.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2378.94 | 2352.88 | 69375.75 | 0.00 | 302.79 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -19539.81 |
ROOM_4_MULT19_FLR_3 | 06-MAY-19:31 | 0.00 | -86419.10 | 0.00 | -7298.34 | 0.00 | 0.00 | 5364.33 | 8498.53 | 12159.85 | 0.00 | 0.00 | 0.00 | 74232.11 | 0.00 | -5904.91 | 0.00 | -632.46 | 0.00 |
ROOM_5_FLR_3 | 26-APR-15:01 | 0.00 | -14386.03 | 0.00 | -485.51 | 0.00 | 0.00 | 235.28 | 199.23 | 200.18 | 2293.23 | 0.00 | 0.00 | 12094.60 | 0.00 | -0.00 | 0.00 | -150.98 | 0.00 |
ROOM_6_FLR_3 | 09-JUN-08:32 | 0.00 | -15302.95 | 0.00 | -1004.64 | 0.00 | 0.00 | 58.83 | 313.04 | 452.99 | 10026.96 | 0.00 | 0.00 | 5501.67 | 0.00 | -0.00 | 0.00 | -45.90 | 0.00 |
CORRIDOR_FLR_3 | 02-JUL-10:33 | 0.00 | 0.00 | 0.00 | -10428.18 | 0.00 | 0.00 | 1795.65 | 2489.76 | 0.00 | 5904.80 | 0.00 | 57.93 | 180.04 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 21-MAY-18:01 | 0.00 | -4160.17 | 0.00 | -136.94 | 0.00 | 0.00 | 70.80 | 177.88 | 121.16 | 1647.02 | 0.00 | 0.00 | 2445.29 | 0.00 | -0.00 | 0.00 | -165.06 | 0.00 |
ROOM_2_FLR_6 | 20-MAY-18:41 | 0.00 | -4642.82 | 0.00 | -165.55 | 0.00 | 0.00 | 59.99 | 177.86 | 121.15 | 680.91 | 0.00 | 0.00 | 3802.24 | 0.00 | -0.00 | 0.00 | -33.77 | 0.00 |
ROOM_3_MULT9_FLR_6 | 30-JAN-16:01 | 0.00 | -18759.11 | 0.00 | -2796.98 | 0.00 | 0.00 | 529.39 | 281.79 | 441.28 | 3347.32 | 0.00 | 0.00 | 17716.55 | 0.00 | -0.00 | 0.00 | -760.25 | 0.00 |
BANQUET_FLR_6 | 19-JAN-01:51 | 0.00 | 0.00 | 0.00 | -29472.35 | 0.00 | 0.00 | 17329.62 | 498.01 | 2249.30 | 0.00 | 0.00 | 0.00 | 12748.55 | 0.00 | -2961.76 | 0.00 | -391.37 | 0.00 |
DINING_FLR_6 | 19-JAN-01:51 | 0.00 | 0.00 | 0.00 | -31227.08 | 0.00 | 0.00 | 17065.62 | 498.01 | 2249.30 | 0.00 | 0.00 | 0.00 | 14808.26 | 0.00 | -3000.67 | 0.00 | -393.43 | 0.00 |
KITCHEN_FLR_6 | 29-JUL-10:40 | 0.00 | 0.00 | 0.00 | -31577.06 | 0.00 | 0.00 | 464.23 | 294.67 | 24259.91 | 4022.00 | 0.00 | 10.84 | 2525.41 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 04-AUG-15:03 | 0.00 | 0.00 | 0.00 | -6700.80 | 0.00 | 0.00 | 771.15 | 548.96 | 0.00 | 2621.38 | 0.00 | 58.86 | 2700.45 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 26-JUN-18:02 | 0.00 | -171195.29 | 0.00 | -200852.72 | 0.00 | 0.00 | 74887.91 | 52987.32 | 120482.43 | 63276.10 | 0.00 | 1667.52 | 58746.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 04-FEB-11:22 | 0.00 | 0.00 | 6129.34 | 0.00 | 0.00 | 0.00 | 3256.39 | 3664.03 | 3548.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -16598.59 |
RETAIL_1_FLR_1 | 20-JAN-07:52 | 0.00 | 0.00 | 2649.13 | 0.00 | 0.00 | 0.00 | 413.26 | 332.00 | 433.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1483.90 | 0.00 | -244.30 | -2099.21 |
RETAIL_2_FLR_1 | 04-FEB-11:22 | 0.00 | 0.00 | 1198.41 | 0.00 | 0.00 | 0.00 | 379.74 | 192.23 | 292.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -89.74 | -1973.15 |
MECH_FLR_1 | 04-FEB-11:22 | 0.00 | 0.00 | 1741.52 | 0.00 | 0.00 | 0.00 | 82.41 | 190.05 | 309.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -208.88 | -2114.37 |
STORAGE_FLR_1 | 04-FEB-11:22 | 0.00 | 0.00 | 1173.60 | 0.00 | 0.00 | 0.00 | 64.09 | 69.95 | 89.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -119.18 | -1277.69 |
LAUNDRY_FLR_1 | 04-FEB-11:11 | 0.00 | 0.00 | 3334.45 | 0.00 | 0.00 | 0.00 | 254.00 | 90.30 | 16320.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -298.20 | -19701.37 |
CAFE_FLR_1 | 20-JAN-07:52 | 0.00 | 0.00 | 5940.82 | 0.00 | 0.00 | 0.00 | 5143.35 | 822.41 | 609.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4323.31 | 0.00 | -557.65 | -7635.27 |
LOBBY_FLR_1 | 04-FEB-11:22 | 0.00 | 0.00 | 19116.71 | 0.00 | 0.00 | 0.00 | 12155.82 | 2270.59 | 3694.97 | 23941.37 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1522.01 | -59657.47 |
ROOM_1_FLR_3 | 02-FEB-08:03 | 7949.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.89 | 313.07 | 453.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4169.00 | 0.00 | -827.13 | -3947.34 |
ROOM_2_FLR_3 | 03-FEB-11:03 | 8665.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.06 | 199.20 | 126.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2546.66 | 0.00 | -697.44 | -5854.01 |
ROOM_3_MULT19_FLR_3 | 19-JAN-05:00 | 22537.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 934.58 | 3333.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -22478.05 | 0.00 | -3192.35 | -1135.15 |
ROOM_4_MULT19_FLR_3 | 03-FEB-11:01 | 47710.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2120.76 | 2379.59 | 2353.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -13524.74 | 0.00 | -3661.42 | -37378.65 |
ROOM_5_FLR_3 | 02-FEB-08:03 | 8215.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 229.07 | 313.07 | 453.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2674.09 | 0.00 | -827.00 | -5709.37 |
ROOM_6_FLR_3 | 03-FEB-18:02 | 8436.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 289.41 | 476.67 | 505.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4282.94 | 0.00 | -672.02 | -4753.11 |
CORRIDOR_FLR_3 | 04-FEB-11:22 | 0.00 | 0.00 | 9286.49 | 0.00 | 0.00 | 0.00 | 2393.30 | 2074.80 | 0.00 | 7325.50 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -689.55 | -20390.54 |
ROOM_1_FLR_6 | 03-FEB-08:03 | 2556.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.16 | 78.27 | 113.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -996.47 | 0.00 | -194.31 | -1614.48 |
ROOM_2_FLR_6 | 03-FEB-11:03 | 2522.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.79 | 49.80 | 31.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -653.21 | 0.00 | -174.69 | -1802.57 |
ROOM_3_MULT9_FLR_6 | 09-DEC-16:13 | 11033.56 | 533.98 | 0.00 | -533.98 | 0.00 | 0.00 | 340.42 | 332.11 | 487.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4019.56 | 0.00 | -622.90 | -7551.37 |
BANQUET_FLR_6 | 04-FEB-11:11 | 0.00 | 0.00 | 5586.24 | 0.00 | 0.00 | 0.00 | 7212.99 | 498.01 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1315.08 | 0.00 | -346.82 | -18383.24 |
DINING_FLR_6 | 04-FEB-11:11 | 0.00 | 0.00 | 5392.75 | 0.00 | 0.00 | 0.00 | 7166.67 | 498.01 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1338.78 | 0.00 | -348.77 | -18117.78 |
KITCHEN_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 04-FEB-11:22 | 0.00 | 0.00 | 6957.88 | 0.00 | 0.00 | 0.00 | 668.06 | 548.96 | 0.00 | 4256.88 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -292.87 | -12138.91 |
Total Facility | 12-DEC-16:13 | 33276.25 | 78146.78 | 11009.08 | -78146.78 | 0.00 | 0.00 | 60289.91 | 18000.67 | 73912.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -74974.48 | 0.00 | -12110.17 | -109403.85 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:56
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV WITH REHEAT | 23.0393 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 22.9089 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV WITH REHEAT | 11.6579 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 11.6579 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.6520 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.0400 | 0.000610 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.000000 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.000000 | 142.3000 | 0.003581 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.000000 | 422.4350 | 0.001448 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 83.8280 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003556 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.1800 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 | |
VAV WITH REHEAT | 0.00 | 0.001045 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.5723 | 2.5723 | 1.3016 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3985 | 0.3985 | 0.2016 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2358 | 0.2358 | 0.1193 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1852 | 0.1852 | 0.0937 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1107 | 0.1107 | 0.0560 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.4056 | 3.4056 | 1.7232 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6533 | 1.6533 | 0.8366 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.1233 | 5.1233 | 2.5924 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6233 | 1.6233 | 0.8214 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2288 | 2.2288 | 1.1278 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3365 | 2.3365 | 1.1823 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3681 | 2.3681 | 1.1983 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7978 | 0.7978 | 0.4037 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
VAV WITH REHEAT | 23.0393 | 22.9089 | 23.0393 | 11.6579 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3016 | 1.3016 | 1.3016 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2016 | 0.2016 | 0.2016 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1193 | 0.1193 | 0.1193 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0937 | 0.0937 | 0.0937 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0560 | 0.0560 | 0.0560 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7232 | 1.7232 | 1.7232 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8366 | 0.8366 | 0.8366 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.5924 | 2.5924 | 2.5924 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8214 | 0.8214 | 0.8214 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1278 | 1.1278 | 1.1278 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1823 | 1.1823 | 1.1823 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1983 | 1.1983 | 1.1983 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4037 | 0.4037 | 0.4037 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
VAV WITH REHEAT | 11.6579 | 11.6579 | 11.6579 | 11.6579 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:56
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 168.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 168.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 280.83 |
Number of hours cooling loads not met | 44.00 |
Number of hours not met | 324.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 2265.83 | 775417.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 580.67 | 206703.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 781.53 | 64632.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 193.69 | 12338.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 872.72 | 59188.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 14.43 | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 8.99 | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.20 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 21.77 | 1291.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 789.09 | 48128.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 2.91 | 188.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 515.93 | 36043.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 79.90 | 4999.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 183.57 | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 94.79 | 4772.05 | 2901.70 | 269507.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.09 | 2093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 20.31 | 1894.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 34.03 | 1202.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1719.61 | 4963.46 |
Natural Gas | 1788.84 | 6956.37 |
Additional | 0.00 | 0.00 |
Total | 3508.44 | 11919.83 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 68.89 |
Space Heating | 0.00 |
Space Cooling | 51.18 |
Fans (All) | 45.48 |
Service Water Heating | 8.36 |
Receptacle Equipment | 146.16 |
Miscellaneous (All) | 437.49 |
Subtotal | 437.49 |
Natural Gas [MJ/m2] | |
Space Heating | 199.72 |
Service Water Heating | 255.76 |
Miscellaneous (All) | 613.15 |
Subtotal | 613.15 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 6.56 |
Space Heating | 19.01 |
Space Cooling | 4.87 |
Fans (All) | 4.33 |
Service Water Heating | 25.14 |
Receptacle Equipment | 28.92 |
Miscellaneous | 11.18 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 486. | 5110. |
ELEVATOR_STANDBY_SCH | 7671. | 8760. |
LTG_SCH_KITCHEN | 3061. | 8760. |
LTG_SCH_DINING | 3061. | 8760. |
LTG_SCH_BASEMENT | 2572. | 8760. |
LTG_SCH_LOBBY | 2295. | 8760. |
LTG_SCH_STORAGE | 1580. | 8760. |
LTG_SCH_MECHANIC | 3061. | 8760. |
LTG_SCH_LAUNDRY | 3061. | 8760. |
LTG_SCH_GUESTROOM | 1980. | 8760. |
LTG_SCH_CORRIDOR | 2295. | 8760. |
LTG_SCH_RETAIL | 2678. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 1591. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3737. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 5740. | 6205. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 8760. | 8760. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 26.67 | 365 | 26.67 | 365 |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
HTGSETP_SCH | BASEMENT DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:56
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8682.83 | 77.17 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8588.67 | 171.33 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8716.67 | 43.33 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8645.83 | 114.17 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8588.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 171.33 | 0.00 | 0.00 | 0.00 |
Average | 8741.55 | 18.45 | 0.00 | 0.00 | 0.00 |
Sum | 192314.00 | 406.00 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4128.67 | 25.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4107.17 | 46.83 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108269.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 46.83 | 0.00 | 0.00 | 0.00 |
Average | 288883.77 | 3.28 | 0.00 | 0.00 | 0.00 |
Sum | 6355442.83 | 72.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8619.33 | 140.67 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8199.50 | 560.50 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8209.83 | 550.17 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8759.50 | 0.50 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8518.00 | 242.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8319.50 | 440.50 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8707.33 | 52.67 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8759.67 | 0.33 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8583.83 | 176.17 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8758.50 | 1.50 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8456.00 | 304.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8757.50 | 2.50 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8169.67 | 590.33 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8223.00 | 537.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8715.50 | 44.50 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8169.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 590.33 | 0.00 | 0.00 | 0.00 |
Average | 8594.39 | 165.61 | 0.00 | 0.00 | 0.00 |
Sum | 189076.67 | 3643.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 57646.67 | 1509.33 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 642318.83 | 68098.17 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 1923071.17 | 192357.83 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4042.33 | 111.67 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4136.33 | 17.67 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4118.67 | 35.33 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4001.17 | 152.83 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1125222.00 | 120493.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1134739.50 | 110975.50 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 107926.83 | 342.17 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 1923071.17 | 192357.83 | 0.00 | 0.00 | 0.00 |
Average | 266428.25 | 22458.80 | 0.00 | 0.00 | 0.00 |
Sum | 5861421.50 | 494093.50 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:56
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:56
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 1592.73 | 0.00 | 0.00 |
Sum | 0.00 | 35040.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 710417.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 2115429.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 2115429.00 | 0.00 | 0.00 |
Average | 0.00 | 241694.36 | 0.00 | 0.00 |
Sum | 0.00 | 5317276.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A
For: Environment
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Environment
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER
For: Environment
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.342535E+11 | 35047.67 | 19-JAN-01:51 | -23.9 | -24.0 | 0.727612E+10 | 4836.90 | 04-JAN-22:10 | -23.9 | -24.0 |
February | 0.275710E+11 | 31160.31 | 02-FEB-06:02 | -36.7 | -36.8 | 0.590259E+10 | 4624.49 | 28-FEB-22:10 | -14.5 | -15.2 |
March | 0.279733E+11 | 12855.39 | 19-MAR-10:33 | 13.87 | 10.01 | 0.712484E+10 | 4565.28 | 01-MAR-22:10 | 13.87 | 10.01 |
April | 0.260618E+11 | 13228.70 | 16-APR-10:33 | 23.33 | 18.86 | 0.660436E+10 | 4270.46 | 21-APR-21:10 | -0.1 | -0.4 |
May | 0.286802E+11 | 13800.02 | 29-MAY-10:33 | 24.63 | 18.66 | 0.700673E+10 | 4378.69 | 19-MAY-22:10 | 24.63 | 18.66 |
June | 0.305087E+11 | 14804.13 | 25-JUN-10:33 | 28.87 | 21.94 | 0.715968E+10 | 4626.26 | 15-JUN-22:10 | 28.87 | 21.94 |
July | 0.337545E+11 | 15598.80 | 23-JUL-10:33 | 20.40 | 14.64 | 0.772721E+10 | 4837.07 | 21-JUL-22:10 | 20.40 | 14.64 |
August | 0.363097E+11 | 18595.59 | 25-AUG-21:00 | 19.40 | 17.91 | 0.808289E+10 | 4837.09 | 30-AUG-22:10 | 16.28 | 15.50 |
September | 0.368850E+11 | 20645.29 | 13-SEP-20:55 | 13.90 | 11.61 | 0.791055E+10 | 4837.35 | 12-SEP-22:10 | 13.90 | 11.61 |
October | 0.381792E+11 | 21112.48 | 31-OCT-21:00 | -1.1 | -2.8 | 0.819565E+10 | 4837.05 | 22-OCT-23:19 | -1.1 | -2.8 |
November | 0.361987E+11 | 36862.02 | 26-NOV-07:07 | -28.3 | -28.5 | 0.783818E+10 | 4837.07 | 22-NOV-00:20 | -28.3 | -28.5 |
December | 0.345945E+11 | 18887.95 | 07-DEC-22:00 | -7.8 | -9.7 | 0.808950E+10 | 4837.07 | 08-DEC-00:20 | -6.8 | -8.6 |
Annual Sum or Average | 0.390970E+12 | 0.889183E+11 | ||||||||
Minimum of Months | 0.260618E+11 | 12855.39 | -36.7 | -36.8 | 0.590259E+10 | 4270.46 | -28.3 | -28.5 | ||
Maximum of Months | 0.381792E+11 | 36862.02 | 28.87 | 21.94 | 0.819565E+10 | 4837.35 | 28.87 | 21.94 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.639799E+09 | 2274.24 | 12-JAN-12:30 | 1.95 | 0.38 | 0.590876E+09 | 364.18 | 26-JAN-02:00 | -17.2 | -17.6 |
February | 0.103937E+10 | 3066.98 | 08-FEB-13:30 | 2.50 | 1.29 | 0.519513E+09 | 375.08 | 24-FEB-22:30 | 1.40 | 0.88 |
March | 0.187390E+10 | 2683.11 | 24-MAR-13:10 | 12.38 | 6.48 | 0.634978E+09 | 400.63 | 23-MAR-21:30 | 12.38 | 6.48 |
April | 0.276588E+10 | 3747.32 | 15-APR-13:30 | 28.85 | 20.45 | 0.632948E+09 | 456.24 | 18-APR-21:19 | 15.93 | 13.15 |
May | 0.399520E+10 | 2793.00 | 06-MAY-13:00 | 22.20 | 11.68 | 0.664370E+09 | 469.06 | 31-MAY-21:30 | 21.00 | 15.98 |
June | 0.446989E+10 | 3128.43 | 30-JUN-13:00 | 29.40 | 21.96 | 0.688781E+09 | 487.34 | 26-JUN-21:19 | 29.40 | 21.96 |
July | 0.501949E+10 | 3295.68 | 30-JUL-12:00 | 26.70 | 21.51 | 0.732051E+09 | 479.29 | 03-JUL-21:30 | 26.70 | 21.51 |
August | 0.506731E+10 | 3627.72 | 29-AUG-13:30 | 23.60 | 16.39 | 0.734329E+09 | 482.60 | 02-AUG-21:30 | 23.60 | 16.39 |
September | 0.445503E+10 | 4596.05 | 07-SEP-13:00 | 31.70 | 18.06 | 0.677413E+09 | 491.81 | 07-SEP-21:40 | 21.33 | 16.17 |
October | 0.331802E+10 | 4250.76 | 20-OCT-12:50 | 21.68 | 12.55 | 0.649623E+09 | 447.32 | 20-OCT-21:30 | 13.90 | 9.49 |
November | 0.156670E+10 | 4046.11 | 04-NOV-12:50 | 13.72 | 6.77 | 0.603460E+09 | 400.96 | 03-NOV-21:30 | 13.72 | 6.77 |
December | 0.792777E+09 | 3196.41 | 03-DEC-13:00 | 5.60 | 2.41 | 0.624753E+09 | 364.17 | 11-DEC-04:40 | -22.0 | -22.5 |
Annual Sum or Average | 0.350034E+11 | 0.775310E+10 | ||||||||
Minimum of Months | 0.639799E+09 | 2274.24 | 1.95 | 0.38 | 0.519513E+09 | 364.17 | -22.0 | -22.5 | ||
Maximum of Months | 0.506731E+10 | 4596.05 | 31.70 | 21.96 | 0.734329E+09 | 491.81 | 29.40 | 21.96 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.184385E+10 | 1779.69 | 05-JAN-21:23 | -23.6 | -23.9 | 0.717967E+09 | 516.06 | 13-JAN-23:10 | 0.82 | 0.04 |
February | 0.193637E+10 | 1606.15 | 02-FEB-06:00 | -36.7 | -36.8 | 0.645048E+09 | 531.96 | 24-FEB-22:40 | 1.13 | 0.61 |
March | 0.237591E+10 | 1251.07 | 24-MAR-20:00 | 3.90 | 2.01 | 0.810884E+09 | 556.58 | 24-MAR-21:30 | 1.70 | 0.37 |
April | 0.259267E+10 | 1701.62 | 18-APR-21:00 | 16.70 | 13.63 | 0.827428E+09 | 569.55 | 14-APR-21:30 | 16.70 | 13.63 |
May | 0.295174E+10 | 1826.98 | 31-MAY-20:55 | 22.20 | 17.24 | 0.899446E+09 | 569.55 | 12-MAY-22:10 | 22.20 | 17.24 |
June | 0.315328E+10 | 2026.55 | 30-JUN-21:00 | 22.20 | 17.11 | 0.901115E+09 | 569.55 | 20-JUN-22:10 | 22.20 | 17.11 |
July | 0.340332E+10 | 1994.16 | 03-JUL-21:00 | 24.40 | 22.86 | 0.945033E+09 | 569.55 | 13-JUL-22:10 | 18.40 | 16.95 |
August | 0.337826E+10 | 1943.08 | 02-AUG-21:00 | 24.40 | 21.64 | 0.949327E+09 | 569.55 | 07-AUG-22:10 | 14.82 | 11.79 |
September | 0.304483E+10 | 2024.62 | 07-SEP-21:00 | 22.80 | 16.44 | 0.890840E+09 | 569.57 | 12-SEP-22:10 | 15.68 | 14.97 |
October | 0.271940E+10 | 1482.53 | 20-OCT-21:00 | 13.90 | 9.43 | 0.868244E+09 | 569.51 | 11-OCT-21:00 | 13.90 | 9.43 |
November | 0.224576E+10 | 2051.70 | 25-NOV-21:12 | -23.7 | -24.1 | 0.776932E+09 | 565.28 | 03-NOV-21:30 | -23.7 | -24.1 |
December | 0.193820E+10 | 1091.39 | 05-DEC-21:00 | -6.7 | -9.2 | 0.760131E+09 | 510.72 | 05-DEC-22:30 | -7.0 | -9.4 |
Annual Sum or Average | 0.315836E+11 | 0.999239E+10 | ||||||||
Minimum of Months | 0.184385E+10 | 1091.39 | -36.7 | -36.8 | 0.645048E+09 | 510.72 | -23.7 | -24.1 | ||
Maximum of Months | 0.340332E+10 | 2051.70 | 24.40 | 22.86 | 0.949327E+09 | 569.57 | 22.20 | 17.24 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.232188E+09 | 722.82 | 13-JAN-21:00 | -0.6 | -1.3 | 0.148129E+09 | 93.74 | 13-JAN-22:10 | 2.02 | 0.71 |
February | 0.523406E+09 | 754.13 | 24-FEB-21:00 | 2.20 | 1.50 | 0.126228E+09 | 95.68 | 24-FEB-22:10 | 1.93 | 1.42 |
March | 0.113899E+10 | 853.20 | 20-MAR-10:33 | 9.43 | 6.43 | 0.156479E+09 | 101.73 | 24-MAR-21:10 | 2.43 | 0.93 |
April | 0.167149E+10 | 1086.87 | 16-APR-10:33 | 23.33 | 18.86 | 0.159071E+09 | 116.90 | 18-APR-21:10 | 16.32 | 13.39 |
May | 0.215881E+10 | 1127.03 | 31-MAY-10:33 | 27.93 | 19.39 | 0.179534E+09 | 120.45 | 31-MAY-21:19 | 21.40 | 16.40 |
June | 0.236070E+10 | 1563.76 | 30-JUN-19:53 | 23.30 | 18.22 | 0.185962E+09 | 120.45 | 28-JUN-21:30 | 23.30 | 18.22 |
July | 0.255213E+10 | 1494.54 | 03-JUL-21:00 | 24.40 | 22.86 | 0.197127E+09 | 120.45 | 27-JUL-21:19 | 20.73 | 17.79 |
August | 0.251250E+10 | 1534.75 | 04-AUG-20:00 | 18.90 | 18.12 | 0.197415E+09 | 120.45 | 11-AUG-21:19 | 18.33 | 16.08 |
September | 0.222898E+10 | 1326.14 | 11-SEP-21:00 | 19.40 | 17.91 | 0.181298E+09 | 120.46 | 12-SEP-22:10 | 15.68 | 14.97 |
October | 0.189257E+10 | 908.42 | 11-OCT-20:00 | 12.60 | 7.23 | 0.167403E+09 | 108.34 | 11-OCT-21:19 | 10.50 | 5.48 |
November | 0.116186E+10 | 906.07 | 04-NOV-10:33 | 10.20 | 5.24 | 0.152854E+09 | 106.72 | 03-NOV-21:10 | 10.20 | 5.24 |
December | 0.425670E+09 | 702.98 | 05-DEC-21:00 | -6.7 | -9.2 | 0.151885E+09 | 92.50 | 04-DEC-22:10 | -6.7 | -9.2 |
Annual Sum or Average | 0.188593E+11 | 0.200339E+10 | ||||||||
Minimum of Months | 0.232188E+09 | 702.98 | -6.7 | -9.2 | 0.126228E+09 | 92.50 | -6.7 | -9.2 | ||
Maximum of Months | 0.255213E+10 | 1563.76 | 27.93 | 22.86 | 0.197415E+09 | 120.46 | 23.30 | 18.22 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 19685927.30 | 369.64 | 13-JAN-22:00 | 2.20 | 0.77 | 0.113020E+09 | 68.57 | 18-JAN-05:00 | -9.4 | -9.8 |
February | 0.100072E+09 | 416.74 | 24-FEB-21:00 | 2.20 | 1.50 | 95906751.09 | 69.74 | 24-FEB-22:40 | 1.13 | 0.61 |
March | 0.441049E+09 | 492.97 | 20-MAR-10:33 | 9.43 | 6.43 | 0.118377E+09 | 73.88 | 28-MAR-22:10 | 8.80 | 7.21 |
April | 0.824842E+09 | 640.33 | 16-APR-10:33 | 23.33 | 18.86 | 0.119050E+09 | 86.04 | 18-APR-21:40 | 15.17 | 12.67 |
May | 0.123494E+10 | 664.76 | 31-MAY-10:33 | 27.93 | 19.39 | 0.133485E+09 | 89.23 | 31-MAY-21:40 | 20.60 | 15.57 |
June | 0.135048E+10 | 708.82 | 30-JUN-10:33 | 27.93 | 22.99 | 0.139295E+09 | 92.66 | 28-JUN-21:30 | 27.93 | 22.99 |
July | 0.146118E+10 | 703.48 | 02-JUL-10:33 | 27.77 | 21.90 | 0.147874E+09 | 92.66 | 03-JUL-21:19 | 24.03 | 22.77 |
August | 0.143889E+10 | 698.48 | 04-AUG-10:33 | 29.27 | 25.47 | 0.147635E+09 | 92.66 | 04-AUG-22:10 | 18.22 | 17.52 |
September | 0.126896E+10 | 686.54 | 09-SEP-10:33 | 25.53 | 16.73 | 0.134605E+09 | 91.21 | 11-SEP-21:40 | 19.40 | 17.91 |
October | 0.104996E+10 | 522.22 | 20-OCT-10:33 | 17.13 | 11.05 | 0.123250E+09 | 79.04 | 20-OCT-22:10 | 13.90 | 9.56 |
November | 0.469796E+09 | 518.75 | 04-NOV-10:33 | 10.20 | 5.24 | 0.115247E+09 | 77.62 | 08-NOV-23:10 | 14.40 | 12.79 |
December | 43874688.54 | 304.04 | 03-DEC-21:00 | -1.1 | -2.3 | 0.116690E+09 | 68.57 | 22-DEC-05:10 | -14.0 | -14.2 |
Annual Sum or Average | 0.970372E+10 | 0.150443E+10 | ||||||||
Minimum of Months | 19685927.30 | 304.04 | -1.1 | -2.3 | 95906751.09 | 68.57 | -14.0 | -14.2 | ||
Maximum of Months | 0.146118E+10 | 708.82 | 29.27 | 25.47 | 0.147874E+09 | 92.66 | 27.93 | 22.99 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.470500E+11 | 39792.68 | 05-JAN-21:42 | -23.8 | -24.1 | 0.531832E+09 | 381.59 | 13-JAN-22:10 | 2.02 | 0.71 |
February | 0.432356E+11 | 36982.67 | 24-FEB-21:00 | 2.20 | 1.50 | 0.471196E+09 | 381.59 | 06-FEB-22:10 | 2.20 | 1.50 |
March | 0.488412E+11 | 37414.01 | 28-MAR-20:00 | 11.70 | 8.27 | 0.590534E+09 | 381.61 | 15-MAR-21:10 | 11.70 | 8.27 |
April | 0.483628E+11 | 38319.16 | 18-APR-20:00 | 18.30 | 15.20 | 0.573527E+09 | 381.67 | 19-APR-21:10 | 7.62 | 3.96 |
May | 0.516511E+11 | 38625.06 | 31-MAY-20:00 | 24.40 | 17.91 | 0.596875E+09 | 381.69 | 30-MAY-21:19 | 24.40 | 17.91 |
June | 0.509356E+11 | 38807.15 | 26-JUN-20:00 | 26.70 | 21.52 | 0.579489E+09 | 381.69 | 27-JUN-21:10 | 23.62 | 18.90 |
July | 0.528392E+11 | 38650.47 | 03-JUL-20:00 | 26.70 | 23.80 | 0.598621E+09 | 381.70 | 28-JUL-21:19 | 19.40 | 17.20 |
August | 0.528884E+11 | 38697.38 | 03-AUG-20:00 | 25.00 | 23.44 | 0.600101E+09 | 381.72 | 04-AUG-21:19 | 18.30 | 17.83 |
September | 0.501291E+11 | 38659.61 | 07-SEP-20:00 | 23.90 | 17.04 | 0.577942E+09 | 381.73 | 22-SEP-21:10 | 9.13 | 6.07 |
October | 0.501397E+11 | 37840.34 | 20-OCT-20:00 | 15.00 | 9.90 | 0.594490E+09 | 381.70 | 03-OCT-21:10 | 15.00 | 9.90 |
November | 0.470682E+11 | 38969.89 | 25-NOV-21:23 | -23.9 | -24.3 | 0.562540E+09 | 381.66 | 03-NOV-21:10 | -23.9 | -24.3 |
December | 0.469302E+11 | 36381.18 | 01-DEC-21:00 | -5.0 | -5.8 | 0.583748E+09 | 381.61 | 01-DEC-22:10 | -3.8 | -4.6 |
Annual Sum or Average | 0.590071E+12 | 0.686089E+10 | ||||||||
Minimum of Months | 0.432356E+11 | 36381.18 | -23.9 | -24.3 | 0.471196E+09 | 381.59 | -23.9 | -24.3 | ||
Maximum of Months | 0.528884E+11 | 39792.68 | 26.70 | 23.80 | 0.600101E+09 | 381.73 | 24.40 | 18.90 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.120896E+11 | 9420.60 | 12-JAN-12:30 | 1.95 | 0.38 | 0.807911E+10 | 5964.46 | 13-JAN-22:40 | 1.47 | 0.51 |
February | 0.133976E+11 | 11851.00 | 08-FEB-13:30 | 2.50 | 1.29 | 0.738667E+10 | 6167.19 | 24-FEB-22:40 | 1.13 | 0.61 |
March | 0.162762E+11 | 10675.54 | 25-MAR-13:40 | 15.03 | 8.62 | 0.921899E+10 | 6421.56 | 23-MAR-21:40 | 15.03 | 8.62 |
April | 0.177826E+11 | 13907.80 | 15-APR-13:20 | 28.67 | 20.40 | 0.935519E+10 | 6462.66 | 14-APR-21:30 | 28.67 | 20.40 |
May | 0.204685E+11 | 11122.90 | 06-MAY-13:00 | 22.20 | 11.68 | 0.101323E+11 | 6462.71 | 30-MAY-22:10 | 18.90 | 16.33 |
June | 0.214162E+11 | 11465.37 | 26-JUN-21:10 | 25.40 | 21.26 | 0.101347E+11 | 6462.76 | 16-JUN-22:10 | 25.40 | 21.26 |
July | 0.230662E+11 | 12087.11 | 30-JUL-12:00 | 26.70 | 21.51 | 0.106149E+11 | 6462.76 | 18-JUL-22:10 | 26.70 | 21.51 |
August | 0.233221E+11 | 12623.29 | 29-AUG-15:03 | 23.80 | 16.28 | 0.106990E+11 | 6462.77 | 07-AUG-22:10 | 23.80 | 16.28 |
September | 0.217963E+11 | 15040.81 | 07-SEP-12:50 | 31.52 | 18.17 | 0.100153E+11 | 6462.81 | 12-SEP-21:30 | 14.75 | 13.54 |
October | 0.196270E+11 | 14997.40 | 20-OCT-12:50 | 21.68 | 12.55 | 0.982357E+10 | 6461.94 | 21-OCT-01:19 | 12.67 | 9.26 |
November | 0.149106E+11 | 15207.84 | 04-NOV-12:50 | 13.72 | 6.77 | 0.870171E+10 | 6412.07 | 03-NOV-21:40 | 13.72 | 6.77 |
December | 0.122629E+11 | 12828.18 | 03-DEC-13:00 | 5.60 | 2.41 | 0.862013E+10 | 5803.09 | 01-DEC-22:40 | 5.60 | 2.41 |
Annual Sum or Average | 0.216416E+12 | 0.112782E+12 | ||||||||
Minimum of Months | 0.120896E+11 | 9420.60 | 1.95 | 0.38 | 0.738667E+10 | 5803.09 | 1.13 | 0.51 | ||
Maximum of Months | 0.233221E+11 | 15207.84 | 31.52 | 21.51 | 0.106990E+11 | 6462.81 | 28.67 | 21.51 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.490557E+11 | 64021.25 | 19-JAN-01:51 | -23.9 | -24.0 | 0.254566E+11 | 18570.48 | 13-JAN-22:49 | -23.9 | -24.0 |
February | 0.481283E+11 | 39841.49 | 02-FEB-06:00 | -36.7 | -36.8 | 0.230340E+11 | 18967.31 | 24-FEB-22:49 | 0.87 | 0.34 |
March | 0.562710E+11 | 28241.91 | 24-MAR-21:10 | 2.43 | 0.93 | 0.289415E+11 | 19183.41 | 28-MAR-22:10 | 8.80 | 7.21 |
April | 0.596069E+11 | 36385.33 | 18-APR-21:10 | 16.32 | 13.39 | 0.290423E+11 | 19186.07 | 14-APR-21:30 | 16.32 | 13.39 |
May | 0.671993E+11 | 37603.10 | 31-MAY-21:10 | 21.80 | 16.82 | 0.313131E+11 | 19186.15 | 30-MAY-22:10 | 21.80 | 16.82 |
June | 0.706066E+11 | 40046.54 | 26-JUN-21:10 | 25.40 | 21.26 | 0.308289E+11 | 19186.23 | 20-JUN-22:10 | 25.40 | 21.26 |
July | 0.755442E+11 | 39123.77 | 03-JUL-21:10 | 24.22 | 22.81 | 0.320253E+11 | 19186.21 | 13-JUL-22:10 | 18.40 | 16.95 |
August | 0.756738E+11 | 39296.86 | 02-AUG-21:10 | 24.32 | 21.63 | 0.322324E+11 | 19186.23 | 07-AUG-22:10 | 14.82 | 11.79 |
September | 0.691512E+11 | 40762.87 | 07-SEP-21:10 | 22.43 | 16.38 | 0.307190E+11 | 19186.35 | 12-SEP-21:30 | 14.75 | 13.54 |
October | 0.630861E+11 | 34734.24 | 20-OCT-21:10 | 13.90 | 9.45 | 0.306670E+11 | 19185.13 | 21-OCT-01:19 | 12.67 | 9.26 |
November | 0.538875E+11 | 45541.67 | 25-NOV-21:12 | -23.7 | -24.1 | 0.276553E+11 | 19183.26 | 03-NOV-21:19 | -23.7 | -24.1 |
December | 0.488671E+11 | 26616.57 | 03-DEC-11:33 | 4.80 | 2.32 | 0.271836E+11 | 18367.52 | 05-DEC-22:49 | -6.8 | -9.2 |
Annual Sum or Average | 0.737078E+12 | 0.349099E+12 | ||||||||
Minimum of Months | 0.481283E+11 | 26616.57 | -36.7 | -36.8 | 0.230340E+11 | 18367.52 | -23.9 | -24.1 | ||
Maximum of Months | 0.756738E+11 | 64021.25 | 25.40 | 22.81 | 0.322324E+11 | 19186.35 | 25.40 | 21.26 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 7528664.52 | 2993.93 | 02-JAN-16:01 | -9.5 | -10.6 | 92815984.11 | 56.69 | 03-JAN-04:19 | -19.5 | -19.7 |
February | 53453943.08 | 3970.14 | 17-FEB-16:01 | -6.8 | -8.8 | 84050416.48 | 56.69 | 05-FEB-00:20 | -6.8 | -8.8 |
March | 0.182328E+09 | 4073.16 | 22-MAR-15:01 | 6.70 | 3.37 | 95576534.41 | 56.69 | 26-MAR-01:39 | 11.87 | 10.47 |
April | 0.734982E+09 | 4107.46 | 26-APR-15:01 | 10.10 | 3.34 | 93767268.37 | 56.69 | 18-APR-21:19 | 10.10 | 3.34 |
May | 0.125440E+10 | 4130.49 | 21-MAY-18:01 | 16.93 | 9.12 | 98609692.42 | 56.69 | 31-MAY-22:40 | 18.27 | 13.07 |
June | 0.196071E+10 | 3618.46 | 14-JUN-15:01 | 23.30 | 20.10 | 95672412.65 | 56.70 | 15-JUN-21:40 | 14.93 | 13.58 |
July | 0.240026E+10 | 3617.84 | 11-JUL-18:01 | 18.80 | 16.03 | 98990463.25 | 56.70 | 28-JUL-22:40 | 18.67 | 16.75 |
August | 0.216159E+10 | 3562.03 | 30-AUG-18:01 | 20.13 | 17.18 | 99031048.23 | 56.70 | 03-AUG-00:10 | 20.13 | 17.18 |
September | 0.145931E+10 | 4061.53 | 20-SEP-18:01 | 17.23 | 10.71 | 95162980.41 | 56.70 | 11-SEP-21:40 | 17.23 | 10.71 |
October | 0.412021E+09 | 3557.48 | 21-OCT-15:01 | 20.67 | 14.27 | 97050382.65 | 56.69 | 10-OCT-21:10 | 20.67 | 14.27 |
November | 95683117.85 | 4013.11 | 12-NOV-16:01 | 0.55 | -2.4 | 91571417.39 | 56.69 | 28-NOV-04:19 | -20.2 | -20.5 |
December | 10512556.59 | 3944.09 | 01-DEC-16:01 | -2.1 | -4.3 | 93293270.66 | 56.69 | 22-DEC-04:19 | -13.5 | -13.8 |
Annual Sum or Average | 0.107328E+11 | 0.113559E+10 | ||||||||
Minimum of Months | 7528664.52 | 2993.93 | -9.5 | -10.6 | 84050416.48 | 56.69 | -20.2 | -20.5 | ||
Maximum of Months | 0.240026E+10 | 4130.49 | 23.30 | 20.10 | 99031048.23 | 56.70 | 20.67 | 17.18 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 666792.66 | 575.59 | 13-JAN-16:03 | 3.62 | 1.75 | 92163509.83 | 56.69 | 24-JAN-04:19 | -17.9 | -18.6 |
February | 16007789.58 | 2785.27 | 25-FEB-16:01 | 5.50 | 2.74 | 82681489.58 | 56.69 | 28-FEB-04:19 | -16.3 | -16.8 |
March | 76582893.95 | 3789.01 | 21-MAR-18:01 | -2.7 | -5.5 | 94707707.63 | 56.99 | 23-MAR-18:10 | 13.53 | 8.78 |
April | 0.484713E+09 | 4100.65 | 29-APR-18:41 | 12.77 | 8.28 | 94910811.44 | 81.13 | 17-APR-18:10 | 12.77 | 8.28 |
May | 0.920368E+09 | 4578.40 | 20-MAY-18:41 | 13.68 | 7.74 | 0.103519E+09 | 77.27 | 30-MAY-21:40 | 19.27 | 16.63 |
June | 0.160974E+10 | 4079.36 | 16-JUN-16:32 | 24.23 | 16.73 | 0.103793E+09 | 93.84 | 08-JUN-18:10 | 24.23 | 16.73 |
July | 0.190168E+10 | 3981.05 | 23-JUL-21:51 | 13.90 | 11.92 | 0.109530E+09 | 92.66 | 24-JUL-18:10 | 21.98 | 17.37 |
August | 0.161259E+10 | 4049.14 | 11-AUG-18:11 | 23.70 | 17.82 | 0.108641E+09 | 89.96 | 16-AUG-18:10 | 21.83 | 15.21 |
September | 0.991878E+09 | 3751.27 | 12-SEP-21:11 | 14.47 | 13.10 | 99268781.79 | 82.47 | 12-SEP-18:10 | 14.47 | 13.10 |
October | 0.172413E+09 | 3699.11 | 10-OCT-16:51 | 14.30 | 11.87 | 96463253.35 | 59.27 | 20-OCT-20:10 | 14.82 | 9.83 |
November | 36749115.50 | 3436.56 | 03-NOV-15:01 | 15.92 | 9.56 | 90792591.74 | 56.69 | 28-NOV-04:19 | -20.2 | -20.5 |
December | 1462886.56 | 493.37 | 14-DEC-16:04 | 0.92 | -0.3 | 92461517.43 | 56.69 | 29-DEC-04:19 | -8.1 | -8.5 |
Annual Sum or Average | 0.782486E+10 | 0.116893E+10 | ||||||||
Minimum of Months | 666792.66 | 493.37 | -2.7 | -5.5 | 82681489.58 | 56.69 | -20.2 | -20.5 | ||
Maximum of Months | 0.190168E+10 | 4578.40 | 24.23 | 17.82 | 0.109530E+09 | 93.84 | 24.23 | 17.37 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 4154474.51 | 214.98 | 30-JAN-15:05 | -24.0 | -24.3 | 0.00 | 0.00 | 01-JAN-00:10 | -24.0 | -24.3 |
February | 10398351.92 | 252.83 | 02-FEB-15:05 | -28.9 | -29.2 | 0.00 | 0.00 | 01-FEB-00:10 | -28.9 | -29.2 |
March | 75324097.85 | 480.05 | 24-MAR-13:00 | 12.20 | 6.46 | 0.00 | 0.00 | 01-MAR-00:10 | 12.20 | 6.46 |
April | 0.200390E+09 | 627.33 | 15-APR-13:30 | 28.85 | 20.45 | 0.00 | 0.00 | 01-APR-00:10 | 28.85 | 20.45 |
May | 0.351898E+09 | 466.90 | 06-MAY-13:00 | 22.20 | 11.68 | 0.00 | 0.00 | 01-MAY-00:10 | 22.20 | 11.68 |
June | 0.473637E+09 | 473.39 | 26-JUN-12:50 | 31.02 | 21.46 | 0.00 | 0.00 | 01-JUN-00:10 | 31.02 | 21.46 |
July | 0.579967E+09 | 516.60 | 30-JUL-13:30 | 26.95 | 19.99 | 0.00 | 0.00 | 01-JUL-00:10 | 26.95 | 19.99 |
August | 0.598391E+09 | 586.56 | 29-AUG-13:30 | 23.60 | 16.39 | 0.00 | 0.00 | 01-AUG-00:10 | 23.60 | 16.39 |
September | 0.510286E+09 | 721.97 | 07-SEP-13:00 | 31.70 | 18.06 | 0.00 | 0.00 | 01-SEP-00:10 | 31.70 | 18.06 |
October | 0.286990E+09 | 720.77 | 20-OCT-12:40 | 21.57 | 12.49 | 0.00 | 0.00 | 01-OCT-00:10 | 21.57 | 12.49 |
November | 87235539.63 | 696.01 | 04-NOV-12:30 | 13.35 | 6.69 | 0.00 | 0.00 | 01-NOV-00:10 | 13.35 | 6.69 |
December | 5516074.86 | 138.99 | 07-DEC-15:20 | -3.9 | -7.6 | 0.00 | 0.00 | 01-DEC-00:10 | -3.9 | -7.6 |
Annual Sum or Average | 0.318419E+10 | 0.00 | ||||||||
Minimum of Months | 4154474.51 | 138.99 | -28.9 | -29.2 | 0.00 | 0.00 | -28.9 | -29.2 | ||
Maximum of Months | 0.598391E+09 | 721.97 | 31.70 | 21.46 | 0.00 | 0.00 | 31.70 | 21.46 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 4755799.35 | 384.50 | 01-JAN-09:02 | -3.2 | -3.4 | 92611067.08 | 56.69 | 09-JAN-00:20 | -4.6 | -5.3 |
February | 16068394.85 | 886.75 | 26-FEB-09:02 | -2.0 | -3.2 | 82838496.05 | 56.69 | 17-FEB-04:19 | -2.0 | -3.2 |
March | 98711535.11 | 1133.40 | 24-MAR-18:01 | 8.35 | 4.47 | 95563063.20 | 56.69 | 19-MAR-23:49 | 8.35 | 4.47 |
April | 0.252930E+09 | 1192.60 | 30-APR-18:01 | 15.22 | 9.05 | 94223095.54 | 72.56 | 14-APR-21:10 | 15.22 | 9.05 |
May | 0.503621E+09 | 1233.12 | 06-MAY-19:31 | 13.13 | 8.89 | 0.100601E+09 | 73.96 | 12-MAY-21:00 | 16.70 | 15.64 |
June | 0.682619E+09 | 1155.30 | 23-JUN-21:51 | 18.90 | 13.98 | 99936522.85 | 77.89 | 21-JUN-21:10 | 18.90 | 13.98 |
July | 0.724061E+09 | 1128.15 | 18-JUL-21:51 | 18.30 | 14.23 | 0.104855E+09 | 76.54 | 07-JUL-21:49 | 18.30 | 14.23 |
August | 0.650451E+09 | 1173.36 | 11-AUG-18:11 | 23.70 | 17.82 | 0.104373E+09 | 75.55 | 16-AUG-21:30 | 15.30 | 12.85 |
September | 0.472601E+09 | 1186.51 | 19-SEP-18:01 | 12.65 | 8.22 | 97192688.23 | 76.42 | 12-SEP-21:10 | 12.65 | 8.22 |
October | 0.219755E+09 | 1119.93 | 19-OCT-18:01 | 11.92 | 7.44 | 96590181.29 | 57.90 | 20-OCT-20:19 | 14.63 | 9.75 |
November | 93186642.13 | 1102.01 | 04-NOV-18:01 | 5.50 | 2.14 | 91980411.01 | 56.69 | 08-NOV-22:10 | 14.40 | 12.79 |
December | 6582004.28 | 484.41 | 03-DEC-09:02 | -1.5 | -1.7 | 93678062.93 | 56.69 | 26-DEC-04:19 | -3.9 | -4.4 |
Annual Sum or Average | 0.372534E+10 | 0.115444E+10 | ||||||||
Minimum of Months | 4755799.35 | 384.50 | -3.2 | -3.4 | 82838496.05 | 56.69 | -4.6 | -5.3 | ||
Maximum of Months | 0.724061E+09 | 1233.12 | 23.70 | 17.82 | 0.104855E+09 | 77.89 | 18.90 | 15.64 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 7023164.61 | 1103.50 | 12-JAN-16:01 | 2.62 | 1.03 | 92663964.32 | 56.69 | 24-JAN-04:19 | -17.9 | -18.6 |
February | 40005954.94 | 3395.94 | 21-FEB-09:02 | -4.8 | -6.3 | 83718011.74 | 56.69 | 28-FEB-04:19 | -16.3 | -16.8 |
March | 0.180435E+09 | 3697.13 | 22-MAR-15:01 | 6.70 | 3.37 | 95806368.95 | 56.69 | 14-MAR-03:20 | 6.70 | 3.37 |
April | 0.633833E+09 | 3717.97 | 26-APR-15:01 | 10.10 | 3.34 | 93850497.42 | 56.69 | 18-APR-21:40 | 10.10 | 3.34 |
May | 0.132487E+10 | 3712.35 | 06-MAY-18:01 | 16.83 | 10.29 | 98885340.34 | 56.70 | 30-MAY-21:40 | 19.27 | 16.63 |
June | 0.198980E+10 | 3398.50 | 25-JUN-08:61 | 24.27 | 20.61 | 95776744.36 | 56.70 | 16-JUN-21:40 | 24.27 | 20.61 |
July | 0.233691E+10 | 3436.59 | 17-JUL-08:61 | 22.57 | 20.41 | 99075316.31 | 56.70 | 31-JUL-21:19 | 19.27 | 18.36 |
August | 0.207804E+10 | 3444.11 | 01-AUG-08:61 | 23.07 | 20.95 | 99170108.29 | 56.70 | 08-AUG-21:40 | 16.30 | 13.31 |
September | 0.146510E+10 | 3709.38 | 20-SEP-18:01 | 17.23 | 10.71 | 95383106.75 | 56.70 | 11-SEP-21:00 | 17.23 | 10.71 |
October | 0.366030E+09 | 3289.92 | 21-OCT-15:01 | 20.67 | 14.27 | 97256929.97 | 56.69 | 02-OCT-04:19 | 20.67 | 14.27 |
November | 88361593.04 | 3308.58 | 12-NOV-09:02 | -5.3 | -6.6 | 91521525.51 | 56.69 | 28-NOV-04:19 | -20.2 | -20.5 |
December | 17418451.26 | 2505.83 | 03-DEC-09:02 | -1.5 | -1.7 | 93146366.15 | 56.69 | 29-DEC-04:19 | -8.1 | -8.5 |
Annual Sum or Average | 0.105278E+11 | 0.113625E+10 | ||||||||
Minimum of Months | 7023164.61 | 1103.50 | -5.3 | -6.6 | 83718011.74 | 56.69 | -20.2 | -20.5 | ||
Maximum of Months | 0.233691E+10 | 3717.97 | 24.27 | 20.95 | 99170108.29 | 56.70 | 24.27 | 20.61 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 681116.18 | 626.27 | 13-JAN-09:04 | -0.5 | -1.5 | 91971264.34 | 56.69 | 24-JAN-04:19 | -17.9 | -18.6 |
February | 10780401.61 | 2478.37 | 24-FEB-09:01 | 3.07 | 0.61 | 82176728.74 | 56.69 | 24-FEB-04:19 | 3.07 | 0.61 |
March | 75346241.86 | 3072.08 | 19-MAR-15:01 | 18.40 | 13.72 | 94805859.24 | 56.69 | 26-MAR-01:19 | 12.03 | 10.54 |
April | 0.407534E+09 | 3724.03 | 18-APR-08:51 | 22.80 | 18.62 | 94392408.92 | 73.97 | 18-APR-21:40 | 15.17 | 12.67 |
May | 0.102797E+10 | 3822.71 | 31-MAY-08:32 | 25.17 | 19.42 | 0.102239E+09 | 75.69 | 31-MAY-21:30 | 21.00 | 15.98 |
June | 0.164913E+10 | 4077.02 | 09-JUN-08:32 | 22.77 | 17.31 | 0.102260E+09 | 78.20 | 21-JUN-21:10 | 14.40 | 12.13 |
July | 0.183896E+10 | 4004.78 | 13-JUL-08:32 | 22.23 | 18.50 | 0.108080E+09 | 78.32 | 05-JUL-21:19 | 22.23 | 18.50 |
August | 0.155999E+10 | 3885.87 | 11-AUG-08:51 | 23.30 | 17.93 | 0.106765E+09 | 77.30 | 04-AUG-21:40 | 23.30 | 17.93 |
September | 0.100408E+10 | 3898.91 | 06-SEP-08:51 | 22.80 | 17.04 | 98601111.38 | 75.72 | 08-SEP-21:40 | 17.93 | 14.84 |
October | 0.138363E+09 | 3118.95 | 21-OCT-15:01 | 20.67 | 14.27 | 96232627.46 | 56.69 | 21-OCT-01:19 | 20.67 | 14.27 |
November | 24558542.12 | 2629.28 | 04-NOV-08:62 | 2.77 | 0.71 | 90703068.79 | 56.69 | 28-NOV-04:19 | -20.2 | -20.5 |
December | 1257470.85 | 724.81 | 05-DEC-09:03 | -6.6 | -8.5 | 92417731.40 | 56.69 | 26-DEC-04:19 | -3.9 | -4.4 |
Annual Sum or Average | 0.773865E+10 | 0.116065E+10 | ||||||||
Minimum of Months | 681116.18 | 626.27 | -6.6 | -8.5 | 82176728.74 | 56.69 | -20.2 | -20.5 | ||
Maximum of Months | 0.183896E+10 | 4077.02 | 25.17 | 19.42 | 0.108080E+09 | 78.32 | 23.30 | 18.50 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.863351E+09 | 1824.73 | 31-JAN-04:00 | -31.1 | -31.3 | 0.117460E+10 | 712.94 | 13-JAN-22:40 | -31.1 | -31.3 |
February | 0.158261E+10 | 2330.33 | 02-FEB-06:00 | -36.7 | -36.8 | 0.102507E+10 | 730.72 | 24-FEB-22:40 | 1.13 | 0.61 |
March | 0.252847E+10 | 1827.79 | 20-MAR-10:33 | 9.43 | 6.43 | 0.122109E+10 | 766.03 | 24-MAR-21:40 | 1.33 | 0.09 |
April | 0.352946E+10 | 2366.76 | 18-APR-10:33 | 26.33 | 20.75 | 0.123871E+10 | 890.44 | 18-APR-21:40 | 15.17 | 12.67 |
May | 0.457342E+10 | 2419.98 | 31-MAY-10:33 | 27.93 | 19.39 | 0.137917E+10 | 902.44 | 31-MAY-21:40 | 20.60 | 15.57 |
June | 0.497326E+10 | 2598.68 | 30-JUN-10:33 | 27.93 | 22.99 | 0.143459E+10 | 951.85 | 30-JUN-22:10 | 21.02 | 16.54 |
July | 0.540413E+10 | 2607.16 | 02-JUL-10:33 | 27.77 | 21.90 | 0.152739E+10 | 951.83 | 03-JUL-21:40 | 23.67 | 22.67 |
August | 0.529057E+10 | 2538.21 | 02-AUG-10:33 | 26.33 | 21.24 | 0.151835E+10 | 943.44 | 04-AUG-21:40 | 18.30 | 17.68 |
September | 0.468867E+10 | 2565.08 | 09-SEP-10:33 | 25.53 | 16.73 | 0.138880E+10 | 939.35 | 08-SEP-21:40 | 25.53 | 16.73 |
October | 0.376640E+10 | 1936.91 | 20-OCT-10:33 | 17.13 | 11.05 | 0.125243E+10 | 800.18 | 20-OCT-21:49 | 13.90 | 9.53 |
November | 0.208837E+10 | 1903.31 | 04-NOV-10:33 | 10.20 | 5.24 | 0.117345E+10 | 767.92 | 03-NOV-21:40 | 10.20 | 5.24 |
December | 0.883993E+09 | 1641.27 | 03-DEC-11:33 | 4.80 | 2.32 | 0.119889E+10 | 704.45 | 12-DEC-04:00 | -20.0 | -20.3 |
Annual Sum or Average | 0.401727E+11 | 0.155325E+11 | ||||||||
Minimum of Months | 0.863351E+09 | 1641.27 | -36.7 | -36.8 | 0.102507E+10 | 704.45 | -31.1 | -31.3 | ||
Maximum of Months | 0.540413E+10 | 2607.16 | 27.93 | 22.99 | 0.152739E+10 | 951.85 | 25.53 | 22.67 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 4486109.99 | 2768.47 | 12-JAN-16:01 | 2.62 | 1.03 | 92432661.72 | 56.69 | 27-JAN-04:19 | -15.0 | -15.4 |
February | 47749693.13 | 3955.57 | 17-FEB-16:01 | -6.8 | -8.8 | 83591262.18 | 56.69 | 24-FEB-04:19 | 0.20 | -1.4 |
March | 0.154809E+09 | 4210.85 | 22-MAR-15:01 | 6.70 | 3.37 | 95047081.50 | 56.69 | 14-MAR-03:20 | 6.70 | 3.37 |
April | 0.730678E+09 | 4272.92 | 26-APR-15:01 | 10.10 | 3.34 | 93448680.14 | 56.69 | 16-APR-04:10 | 10.10 | 3.34 |
May | 0.122330E+10 | 4297.16 | 21-MAY-18:01 | 16.93 | 9.12 | 98486679.71 | 56.70 | 30-MAY-21:00 | 18.90 | 16.37 |
June | 0.198814E+10 | 3725.78 | 17-JUN-18:02 | 23.72 | 19.22 | 95580147.12 | 56.70 | 26-JUN-23:40 | 23.50 | 20.12 |
July | 0.243138E+10 | 3726.51 | 21-JUL-18:01 | 20.00 | 15.79 | 98932698.17 | 56.70 | 02-JUL-23:40 | 20.00 | 15.79 |
August | 0.214237E+10 | 3767.67 | 25-AUG-15:01 | 22.30 | 19.56 | 98944370.93 | 56.70 | 03-AUG-21:00 | 22.30 | 19.56 |
September | 0.139401E+10 | 4213.95 | 20-SEP-18:01 | 17.23 | 10.71 | 94936995.68 | 56.70 | 12-SEP-21:10 | 17.23 | 10.71 |
October | 0.365393E+09 | 3607.78 | 21-OCT-15:01 | 20.67 | 14.27 | 96638818.76 | 56.69 | 10-OCT-21:19 | 20.67 | 14.27 |
November | 73494966.37 | 4160.25 | 12-NOV-16:01 | 0.55 | -2.4 | 91072462.83 | 56.69 | 01-NOV-04:19 | 0.55 | -2.4 |
December | 7565697.42 | 4076.13 | 01-DEC-16:01 | -2.1 | -4.3 | 92898552.38 | 56.69 | 29-DEC-04:19 | -8.1 | -8.5 |
Annual Sum or Average | 0.105634E+11 | 0.113201E+10 | ||||||||
Minimum of Months | 4486109.99 | 2768.47 | -6.8 | -8.8 | 83591262.18 | 56.69 | -15.0 | -15.4 | ||
Maximum of Months | 0.243138E+10 | 4297.16 | 23.72 | 19.56 | 98944370.93 | 56.70 | 23.50 | 20.12 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 244733.86 | 814.39 | 12-JAN-16:03 | 2.62 | 1.03 | 91801990.55 | 56.69 | 10-JAN-04:19 | 2.62 | 1.03 |
February | 11746734.06 | 2831.84 | 24-FEB-16:01 | 8.12 | 5.76 | 82236956.57 | 56.69 | 17-FEB-04:19 | 8.12 | 5.76 |
March | 56390698.00 | 3923.34 | 21-MAR-18:01 | -2.7 | -5.5 | 94204017.12 | 57.24 | 23-MAR-18:10 | 13.53 | 8.78 |
April | 0.477846E+09 | 4334.42 | 29-APR-18:41 | 12.77 | 8.28 | 94741675.91 | 88.03 | 17-APR-18:10 | 12.77 | 8.28 |
May | 0.899384E+09 | 4808.36 | 20-MAY-18:41 | 13.68 | 7.74 | 0.104037E+09 | 81.71 | 03-MAY-18:10 | 13.68 | 7.74 |
June | 0.167536E+10 | 4233.83 | 16-JUN-16:32 | 24.23 | 16.73 | 0.104662E+09 | 102.65 | 08-JUN-18:10 | 24.23 | 16.73 |
July | 0.198952E+10 | 4289.07 | 23-JUL-21:51 | 13.90 | 11.92 | 0.110262E+09 | 98.96 | 24-JUL-18:10 | 21.98 | 17.37 |
August | 0.163953E+10 | 4188.44 | 11-AUG-18:11 | 23.70 | 17.82 | 0.109387E+09 | 97.37 | 16-AUG-18:10 | 21.83 | 15.21 |
September | 0.945243E+09 | 4619.25 | 19-SEP-17:41 | 13.68 | 8.65 | 99284885.23 | 88.80 | 12-SEP-18:10 | 13.68 | 8.65 |
October | 0.135436E+09 | 3878.60 | 10-OCT-16:51 | 14.30 | 11.87 | 95969254.65 | 59.47 | 11-OCT-18:10 | 15.35 | 9.78 |
November | 24146915.96 | 3496.22 | 03-NOV-15:01 | 15.92 | 9.56 | 90340970.99 | 56.69 | 17-NOV-04:19 | 0.20 | -1.0 |
December | 492068.66 | 603.61 | 05-DEC-16:04 | -5.1 | -8.3 | 92263677.10 | 56.69 | 12-DEC-04:19 | -20.0 | -20.3 |
Annual Sum or Average | 0.785535E+10 | 0.116919E+10 | ||||||||
Minimum of Months | 244733.86 | 603.61 | -5.1 | -8.3 | 82236956.57 | 56.69 | -20.0 | -20.3 | ||
Maximum of Months | 0.198952E+10 | 4808.36 | 24.23 | 17.82 | 0.110262E+09 | 102.65 | 24.23 | 17.37 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 77855000.26 | 2395.19 | 30-JAN-16:01 | -24.5 | -24.9 | 94535599.61 | 56.69 | 27-JAN-00:20 | -24.5 | -24.9 |
February | 0.141776E+09 | 2305.45 | 01-FEB-16:02 | -26.2 | -26.5 | 86174369.96 | 56.69 | 05-FEB-00:20 | -17.0 | -17.6 |
March | 0.252880E+09 | 2241.79 | 21-MAR-15:01 | -0.1 | -3.9 | 96543176.90 | 56.69 | 19-MAR-23:30 | -0.1 | -3.9 |
April | 0.500314E+09 | 2239.81 | 26-APR-15:01 | 10.10 | 3.34 | 93890349.88 | 56.69 | 18-APR-21:00 | 10.10 | 3.34 |
May | 0.753581E+09 | 2187.18 | 21-MAY-18:01 | 16.93 | 9.12 | 98573296.34 | 56.69 | 30-MAY-21:00 | 18.90 | 16.37 |
June | 0.104721E+10 | 1960.12 | 03-JUN-15:01 | 14.40 | 10.99 | 95622696.43 | 56.69 | 13-JUN-22:30 | 24.15 | 20.49 |
July | 0.125604E+10 | 1952.03 | 07-JUL-18:01 | 22.62 | 17.11 | 98878138.67 | 56.69 | 31-JUL-21:49 | 19.07 | 18.00 |
August | 0.124694E+10 | 1966.40 | 11-AUG-18:02 | 24.35 | 17.82 | 98929096.36 | 56.69 | 18-AUG-21:00 | 15.60 | 13.62 |
September | 0.103067E+10 | 2207.42 | 20-SEP-18:01 | 17.23 | 10.71 | 95281693.61 | 56.69 | 08-SEP-23:40 | 17.23 | 10.71 |
October | 0.573646E+09 | 1945.21 | 02-OCT-15:01 | 18.02 | 14.64 | 97817777.97 | 56.69 | 20-OCT-22:10 | 13.90 | 9.56 |
November | 0.205463E+09 | 2194.75 | 21-NOV-16:01 | -7.0 | -8.7 | 92790929.93 | 56.69 | 02-NOV-21:10 | -7.0 | -8.7 |
December | 0.126909E+09 | 2212.22 | 05-DEC-16:01 | -5.1 | -8.3 | 94698393.61 | 56.69 | 19-DEC-04:19 | -3.1 | -3.8 |
Annual Sum or Average | 0.721327E+10 | 0.114374E+10 | ||||||||
Minimum of Months | 77855000.26 | 1945.21 | -26.2 | -26.5 | 86174369.96 | 56.69 | -24.5 | -24.9 | ||
Maximum of Months | 0.125604E+10 | 2395.19 | 24.35 | 17.82 | 98929096.36 | 56.69 | 24.15 | 20.49 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.277423E+11 | 29475.81 | 19-JAN-01:51 | -23.9 | -24.0 | 0.172787E+11 | 11347.88 | 17-JAN-00:20 | -23.9 | -24.0 |
February | 0.266800E+11 | 19323.08 | 02-FEB-06:00 | -36.7 | -36.8 | 0.154244E+11 | 11347.89 | 21-FEB-00:20 | -4.1 | -5.9 |
March | 0.313150E+11 | 18530.44 | 28-MAR-22:00 | 8.90 | 7.21 | 0.189906E+11 | 11347.88 | 07-MAR-00:20 | 8.90 | 7.21 |
April | 0.336042E+11 | 21122.21 | 18-APR-21:10 | 16.32 | 13.39 | 0.185099E+11 | 11348.92 | 14-APR-21:30 | 16.32 | 13.39 |
May | 0.388188E+11 | 22269.35 | 31-MAY-21:10 | 21.80 | 16.82 | 0.192957E+11 | 11349.11 | 31-MAY-21:19 | 21.40 | 16.40 |
June | 0.407816E+11 | 23000.53 | 26-JUN-21:20 | 25.20 | 21.20 | 0.187350E+11 | 11364.56 | 30-JUN-21:19 | 21.87 | 16.96 |
July | 0.430105E+11 | 22726.25 | 03-JUL-21:20 | 24.03 | 22.77 | 0.192975E+11 | 11358.71 | 27-JUL-21:19 | 20.73 | 17.79 |
August | 0.420888E+11 | 22568.52 | 03-AUG-21:20 | 24.23 | 23.04 | 0.193727E+11 | 11370.48 | 04-AUG-21:19 | 18.30 | 17.83 |
September | 0.375282E+11 | 22011.20 | 07-SEP-21:10 | 22.43 | 16.38 | 0.186396E+11 | 11349.25 | 12-SEP-21:30 | 14.75 | 13.54 |
October | 0.339478E+11 | 19273.72 | 20-OCT-22:00 | 13.90 | 9.54 | 0.191074E+11 | 11347.83 | 27-OCT-03:20 | 0.00 | -1.2 |
November | 0.298952E+11 | 24737.19 | 25-NOV-21:23 | -23.9 | -24.3 | 0.180185E+11 | 11347.89 | 13-NOV-00:20 | -23.9 | -24.3 |
December | 0.275660E+11 | 16062.25 | 04-DEC-23:00 | 2.20 | 0.30 | 0.183821E+11 | 11347.90 | 18-DEC-00:20 | -4.1 | -4.8 |
Annual Sum or Average | 0.412978E+12 | 0.221052E+12 | ||||||||
Minimum of Months | 0.266800E+11 | 16062.25 | -36.7 | -36.8 | 0.154244E+11 | 11347.83 | -23.9 | -24.3 | ||
Maximum of Months | 0.430105E+11 | 29475.81 | 25.20 | 23.04 | 0.193727E+11 | 11370.48 | 21.87 | 17.83 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.307767E+11 | 31230.89 | 19-JAN-01:51 | -23.9 | -24.0 | 0.176162E+11 | 11347.96 | 17-JAN-00:20 | -23.9 | -24.0 |
February | 0.296761E+11 | 20261.92 | 02-FEB-06:00 | -36.7 | -36.8 | 0.156410E+11 | 11347.96 | 13-FEB-00:20 | -6.7 | -7.2 |
March | 0.350334E+11 | 20460.10 | 28-MAR-21:10 | 9.82 | 7.62 | 0.191770E+11 | 11347.96 | 06-MAR-00:20 | 9.82 | 7.62 |
April | 0.372086E+11 | 22496.86 | 18-APR-21:10 | 16.32 | 13.39 | 0.186209E+11 | 11348.93 | 14-APR-21:30 | 16.32 | 13.39 |
May | 0.424225E+11 | 23573.11 | 31-MAY-21:20 | 21.40 | 16.40 | 0.193317E+11 | 11377.27 | 30-MAY-21:19 | 21.40 | 16.40 |
June | 0.438843E+11 | 24221.16 | 26-JUN-21:20 | 25.20 | 21.20 | 0.187523E+11 | 11378.49 | 23-JUN-21:19 | 25.20 | 21.20 |
July | 0.460317E+11 | 23930.88 | 03-JUL-21:20 | 24.03 | 22.77 | 0.193070E+11 | 11377.04 | 14-JUL-21:19 | 22.60 | 20.30 |
August | 0.451525E+11 | 23802.00 | 03-AUG-21:20 | 24.23 | 23.04 | 0.193862E+11 | 11383.58 | 04-AUG-21:19 | 18.30 | 17.83 |
September | 0.407516E+11 | 23249.59 | 07-SEP-21:20 | 22.07 | 16.32 | 0.186810E+11 | 11371.08 | 11-SEP-21:19 | 19.40 | 17.91 |
October | 0.377598E+11 | 21015.21 | 02-OCT-21:10 | 11.63 | 10.32 | 0.192230E+11 | 11347.88 | 27-OCT-03:20 | 0.00 | -1.2 |
November | 0.333415E+11 | 28068.09 | 25-NOV-21:23 | -23.9 | -24.3 | 0.182255E+11 | 11347.96 | 13-NOV-00:20 | -23.9 | -24.3 |
December | 0.308593E+11 | 18055.14 | 04-DEC-23:00 | 2.20 | 0.30 | 0.186911E+11 | 11347.98 | 26-DEC-00:20 | -6.5 | -7.2 |
Annual Sum or Average | 0.452898E+12 | 0.222653E+12 | ||||||||
Minimum of Months | 0.296761E+11 | 18055.14 | -36.7 | -36.8 | 0.156410E+11 | 11347.88 | -23.9 | -24.3 | ||
Maximum of Months | 0.460317E+11 | 31230.89 | 25.20 | 23.04 | 0.193862E+11 | 11383.58 | 25.20 | 21.20 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.457314E+11 | 27418.77 | 29-JAN-19:42 | -23.8 | -24.0 | 0.186729E+11 | 11319.71 | 07-JAN-18:19 | -23.8 | -24.0 |
February | 0.430232E+11 | 27558.49 | 24-FEB-11:33 | 5.93 | 2.90 | 0.168409E+11 | 11319.70 | 04-FEB-18:19 | 5.93 | 2.90 |
March | 0.500413E+11 | 28918.48 | 19-MAR-10:50 | 14.13 | 10.21 | 0.188217E+11 | 11319.62 | 04-MAR-18:19 | 14.13 | 10.21 |
April | 0.509960E+11 | 30814.17 | 15-APR-10:33 | 24.67 | 19.18 | 0.182273E+11 | 11319.67 | 15-APR-17:19 | 29.43 | 18.76 |
May | 0.558989E+11 | 31298.76 | 31-MAY-10:37 | 27.93 | 19.39 | 0.188537E+11 | 11319.67 | 06-MAY-17:19 | 27.93 | 19.39 |
June | 0.560883E+11 | 31528.78 | 11-JUN-10:40 | 29.67 | 22.05 | 0.182569E+11 | 11319.67 | 24-JUN-17:19 | 26.50 | 20.26 |
July | 0.586099E+11 | 31587.03 | 29-JUL-10:40 | 25.93 | 19.88 | 0.188625E+11 | 11319.68 | 08-JUL-17:19 | 25.93 | 19.88 |
August | 0.578852E+11 | 31279.08 | 01-AUG-10:33 | 26.83 | 21.26 | 0.188679E+11 | 11319.68 | 05-AUG-17:19 | 25.03 | 17.79 |
September | 0.539740E+11 | 31373.57 | 08-SEP-10:40 | 28.33 | 18.78 | 0.182447E+11 | 11319.68 | 09-SEP-17:19 | 26.27 | 16.30 |
October | 0.521124E+11 | 29099.70 | 01-OCT-10:33 | 16.07 | 11.42 | 0.188336E+11 | 11319.61 | 07-OCT-17:19 | 4.90 | 2.60 |
November | 0.473859E+11 | 28863.72 | 25-NOV-21:23 | -23.9 | -24.3 | 0.181888E+11 | 11319.68 | 25-NOV-18:19 | -23.9 | -24.3 |
December | 0.462581E+11 | 26861.17 | 03-DEC-11:33 | 4.80 | 2.32 | 0.187911E+11 | 11319.71 | 09-DEC-18:19 | -19.6 | -20.0 |
Annual Sum or Average | 0.618005E+12 | 0.221462E+12 | ||||||||
Minimum of Months | 0.430232E+11 | 26861.17 | -23.9 | -24.3 | 0.168409E+11 | 11319.61 | -23.9 | -24.3 | ||
Maximum of Months | 0.586099E+11 | 31587.03 | 29.67 | 22.05 | 0.188679E+11 | 11319.71 | 29.43 | 20.26 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.474429E+09 | 2823.92 | 13-JAN-11:35 | 3.33 | 1.18 | 0.122701E+10 | 745.66 | 27-JAN-05:19 | -16.5 | -16.9 |
February | 0.156314E+10 | 3433.00 | 24-FEB-11:33 | 5.93 | 2.90 | 0.105495E+10 | 757.79 | 24-FEB-22:30 | 1.40 | 0.88 |
March | 0.403017E+10 | 3721.06 | 20-MAR-10:33 | 9.43 | 6.43 | 0.128872E+10 | 809.49 | 19-MAR-23:19 | 9.43 | 6.43 |
April | 0.648051E+10 | 4839.94 | 18-APR-10:33 | 26.33 | 20.75 | 0.130995E+10 | 954.92 | 18-APR-21:30 | 15.55 | 12.91 |
May | 0.909467E+10 | 5115.48 | 31-MAY-10:33 | 27.93 | 19.39 | 0.146192E+10 | 1000.39 | 31-MAY-21:30 | 21.00 | 15.98 |
June | 0.101717E+11 | 6527.02 | 30-JUN-14:10 | 29.40 | 21.90 | 0.153158E+10 | 1007.40 | 28-JUN-21:19 | 29.40 | 21.90 |
July | 0.110115E+11 | 6282.57 | 05-JUL-14:10 | 27.30 | 19.85 | 0.162439E+10 | 1007.40 | 05-JUL-22:10 | 20.60 | 19.73 |
August | 0.105963E+11 | 6700.92 | 04-AUG-15:03 | 33.90 | 25.49 | 0.160937E+10 | 1007.40 | 04-AUG-22:10 | 18.22 | 17.52 |
September | 0.910004E+10 | 6614.47 | 07-SEP-13:30 | 31.95 | 18.23 | 0.144710E+10 | 1007.36 | 07-SEP-21:40 | 21.33 | 16.17 |
October | 0.693126E+10 | 3926.85 | 20-OCT-10:33 | 17.13 | 11.05 | 0.131573E+10 | 854.85 | 20-OCT-21:40 | 13.90 | 9.51 |
November | 0.340338E+10 | 3807.71 | 04-NOV-10:33 | 10.20 | 5.24 | 0.123606E+10 | 811.17 | 03-NOV-21:40 | 10.20 | 5.24 |
December | 0.849345E+09 | 3283.60 | 03-DEC-11:33 | 4.80 | 2.32 | 0.126895E+10 | 745.63 | 12-DEC-04:49 | -20.0 | -20.3 |
Annual Sum or Average | 0.737064E+11 | 0.163757E+11 | ||||||||
Minimum of Months | 0.474429E+09 | 2823.92 | 3.33 | 1.18 | 0.105495E+10 | 745.63 | -20.0 | -20.3 | ||
Maximum of Months | 0.110115E+11 | 6700.92 | 33.90 | 25.49 | 0.162439E+10 | 1007.40 | 29.40 | 21.90 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | -2.8 |
February | 0.172364E+09 | 6129.29 | 04-FEB-11:22 | -23.0 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 1.65 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -0.7 |
Annual Sum or Average | 0.172364E+09 | |||
Minimum of Months | 0.00 | 0.00 | -23.0 | |
Maximum of Months | 0.172364E+09 | 6129.29 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.130190E+10 | 2649.08 | 20-JAN-07:52 | -23.3 |
February | 0.484715E+09 | 2151.00 | 04-FEB-11:22 | -23.0 |
March | 0.226603E+09 | 846.87 | 06-MAR-05:00 | -15.6 |
April | 47881305.10 | 637.67 | 03-APR-06:10 | -7.1 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.15 |
September | 86990.71 | 44.83 | 30-SEP-06:20 | 0.60 |
October | 323568.32 | 76.96 | 23-OCT-06:10 | -3.0 |
November | 0.386901E+09 | 2509.39 | 26-NOV-08:51 | -23.3 |
December | 0.118671E+10 | 1870.90 | 10-DEC-06:00 | -22.8 |
Annual Sum or Average | 0.363512E+10 | |||
Minimum of Months | 0.00 | 0.00 | -23.3 | |
Maximum of Months | 0.130190E+10 | 2649.08 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 31362287.60 | 856.43 | 31-JAN-11:42 | -23.1 |
February | 52649143.04 | 1198.40 | 04-FEB-11:22 | -23.0 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 |
November | 3444565.27 | 695.49 | 26-NOV-08:51 | -23.3 |
December | 2308.31 | 3.85 | 12-DEC-15:00 | -15.6 |
Annual Sum or Average | 87458304.22 | |||
Minimum of Months | 0.00 | 0.00 | -23.3 | |
Maximum of Months | 52649143.04 | 1198.40 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.631416E+09 | 1387.71 | 31-JAN-11:42 | -23.1 |
February | 0.388731E+09 | 1741.51 | 04-FEB-11:22 | -23.0 |
March | 26546021.32 | 254.49 | 06-MAR-05:00 | -15.6 |
April | 271760.55 | 35.91 | 03-APR-11:50 | -3.9 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 |
November | 0.122204E+09 | 1190.95 | 26-NOV-08:51 | -23.3 |
December | 0.272094E+09 | 747.48 | 11-DEC-15:00 | -19.4 |
Annual Sum or Average | 0.144126E+10 | |||
Minimum of Months | 0.00 | 0.00 | -23.3 | |
Maximum of Months | 0.631416E+09 | 1741.51 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.861736E+09 | 964.76 | 31-JAN-11:42 | -23.1 |
February | 0.445240E+09 | 1173.59 | 04-FEB-11:22 | -23.0 |
March | 0.115100E+09 | 370.33 | 06-MAR-04:50 | -15.7 |
April | 10968201.36 | 176.84 | 03-APR-11:30 | -3.9 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 |
November | 0.203796E+09 | 848.65 | 26-NOV-08:51 | -23.3 |
December | 0.525725E+09 | 732.57 | 11-DEC-16:00 | -20.0 |
Annual Sum or Average | 0.216256E+10 | |||
Minimum of Months | 0.00 | 0.00 | -23.3 | |
Maximum of Months | 0.861736E+09 | 1173.59 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 73533.97 | 1225.57 | 31-JAN-11:31 | -23.3 |
February | 226012.74 | 3334.33 | 04-FEB-11:11 | -23.3 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 |
November | 35508.20 | 591.80 | 26-NOV-08:51 | -23.3 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -0.7 |
Annual Sum or Average | 335054.91 | |||
Minimum of Months | 0.00 | 0.00 | -23.3 | |
Maximum of Months | 226012.74 | 3334.33 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.111870E+09 | 5940.60 | 20-JAN-07:52 | -23.3 |
February | 3937326.84 | 4571.36 | 04-FEB-11:11 | -23.3 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 |
November | 24281160.50 | 5821.76 | 26-NOV-08:51 | -23.3 |
December | 0.142923E+09 | 2440.23 | 12-DEC-15:00 | -15.6 |
Annual Sum or Average | 0.283012E+09 | |||
Minimum of Months | 0.00 | 0.00 | -23.3 | |
Maximum of Months | 0.142923E+09 | 5940.60 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 80083906.46 | 12575.07 | 31-JAN-11:42 | -23.1 |
February | 0.269033E+09 | 19116.34 | 04-FEB-11:22 | -23.0 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 |
November | 8095812.86 | 11543.18 | 26-NOV-08:51 | -23.3 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -0.7 |
Annual Sum or Average | 0.357213E+09 | |||
Minimum of Months | 0.00 | 0.00 | -23.3 | |
Maximum of Months | 0.269033E+09 | 19116.34 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.203124E+10 | 1963.73 | 19-JAN-19:13 | -23.3 |
February | 0.128124E+10 | 1987.29 | 02-FEB-08:03 | -36.5 |
March | 0.681651E+09 | 1894.14 | 01-MAR-16:02 | -3.9 |
April | 0.246741E+09 | 1878.00 | 03-APR-08:62 | -5.9 |
May | 10252901.96 | 1157.21 | 09-MAY-08:03 | 12.07 |
June | 2592979.87 | 1167.72 | 03-JUN-08:03 | 8.68 |
July | 1429959.15 | 934.04 | 20-JUL-08:04 | 20.68 |
August | 1624630.26 | 893.10 | 22-AUG-08:04 | 22.07 |
September | 35691559.95 | 1442.04 | 29-SEP-08:62 | 5.05 |
October | 0.168958E+09 | 1809.12 | 26-OCT-08:62 | 1.28 |
November | 0.898332E+09 | 1947.96 | 26-NOV-16:13 | -13.9 |
December | 0.171882E+10 | 1984.52 | 09-DEC-16:13 | -19.1 |
Annual Sum or Average | 0.707857E+10 | |||
Minimum of Months | 1429959.15 | 893.10 | -36.5 | |
Maximum of Months | 0.203124E+10 | 1987.29 | 22.07 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.241391E+10 | 1971.24 | 20-JAN-09:13 | -21.5 |
February | 0.158944E+10 | 2166.33 | 03-FEB-11:03 | -29.2 |
March | 0.832031E+09 | 1899.42 | 05-MAR-09:01 | -8.9 |
April | 0.287187E+09 | 1871.71 | 03-APR-08:62 | -5.9 |
May | 12838114.29 | 1300.69 | 02-MAY-08:61 | 4.08 |
June | 2379801.47 | 1170.34 | 03-JUN-08:03 | 8.68 |
July | 600911.78 | 1032.06 | 12-JUL-08:53 | 20.00 |
August | 915544.26 | 1138.69 | 16-AUG-08:53 | 18.90 |
September | 45798465.55 | 1803.96 | 30-SEP-08:61 | 3.35 |
October | 0.266571E+09 | 1821.48 | 27-OCT-08:62 | 3.15 |
November | 0.108606E+10 | 1950.88 | 26-NOV-16:13 | -13.9 |
December | 0.200911E+10 | 1978.19 | 09-DEC-16:13 | -19.1 |
Annual Sum or Average | 0.854684E+10 | |||
Minimum of Months | 600911.78 | 1032.06 | -29.2 | |
Maximum of Months | 0.241391E+10 | 2166.33 | 20.00 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 88698039.67 | 296.55 | 19-JAN-05:00 | -27.2 |
February | 15312294.28 | 230.58 | 04-FEB-06:00 | -30.6 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 |
November | 1641976.96 | 116.73 | 28-NOV-05:00 | -21.7 |
December | 52000604.46 | 238.39 | 13-DEC-04:05 | -11.6 |
Annual Sum or Average | 0.157653E+09 | |||
Minimum of Months | 0.00 | 0.00 | -30.6 | |
Maximum of Months | 88698039.67 | 296.55 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.445054E+09 | 571.72 | 31-JAN-16:01 | -20.1 |
February | 0.269395E+09 | 627.77 | 03-FEB-11:01 | -29.2 |
March | 83880941.83 | 544.64 | 23-MAR-15:03 | 16.28 |
April | 11918280.46 | 529.43 | 29-APR-15:04 | 17.02 |
May | 612748.13 | 501.17 | 03-MAY-15:04 | 17.30 |
June | 167407.89 | 274.81 | 15-JUN-15:06 | 20.10 |
July | 111137.26 | 361.07 | 11-JUL-15:06 | 17.77 |
August | 250662.81 | 337.13 | 06-AUG-15:06 | 19.22 |
September | 737049.90 | 373.91 | 25-SEP-15:04 | 13.22 |
October | 2895141.20 | 474.76 | 29-OCT-15:03 | 14.82 |
November | 0.135006E+09 | 559.48 | 25-NOV-16:02 | -18.1 |
December | 0.331087E+09 | 558.18 | 09-DEC-16:13 | -19.1 |
Annual Sum or Average | 0.128111E+10 | |||
Minimum of Months | 111137.26 | 274.81 | -29.2 | |
Maximum of Months | 0.445054E+09 | 627.77 | 20.10 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.200649E+10 | 1913.13 | 19-JAN-16:02 | -22.9 |
February | 0.129162E+10 | 2053.74 | 02-FEB-08:03 | -36.5 |
March | 0.665152E+09 | 1851.20 | 01-MAR-16:02 | -3.9 |
April | 0.276453E+09 | 1826.75 | 03-APR-08:62 | -5.9 |
May | 8829436.10 | 1068.96 | 17-MAY-08:04 | 9.68 |
June | 2140854.44 | 1169.48 | 04-JUN-18:04 | 13.22 |
July | 710360.30 | 966.14 | 06-JUL-08:04 | 19.90 |
August | 1127114.77 | 914.79 | 06-AUG-08:04 | 12.80 |
September | 30604334.18 | 1340.08 | 30-SEP-18:03 | 5.92 |
October | 0.170221E+09 | 1756.78 | 26-OCT-08:62 | 1.28 |
November | 0.904121E+09 | 1898.56 | 26-NOV-16:13 | -13.9 |
December | 0.172338E+10 | 1934.30 | 09-DEC-16:13 | -19.1 |
Annual Sum or Average | 0.708085E+10 | |||
Minimum of Months | 710360.30 | 914.79 | -36.5 | |
Maximum of Months | 0.200649E+10 | 2053.74 | 19.90 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.239071E+10 | 1935.40 | 31-JAN-16:01 | -20.1 |
February | 0.160939E+10 | 2109.05 | 03-FEB-18:02 | -27.8 |
March | 0.809181E+09 | 1860.39 | 05-MAR-16:01 | -9.6 |
April | 0.323717E+09 | 1822.02 | 03-APR-08:62 | -5.9 |
May | 11181768.79 | 1107.46 | 11-MAY-15:04 | 16.70 |
June | 2314216.31 | 1156.95 | 04-JUN-18:04 | 13.22 |
July | 463494.76 | 712.51 | 22-JUL-21:34 | 14.27 |
August | 1002108.55 | 881.43 | 06-AUG-08:04 | 12.80 |
September | 37160076.44 | 1145.72 | 24-SEP-15:04 | 15.92 |
October | 0.260640E+09 | 1761.10 | 26-OCT-08:62 | 1.28 |
November | 0.108872E+10 | 1900.41 | 26-NOV-16:13 | -13.9 |
December | 0.201856E+10 | 1929.72 | 09-DEC-16:13 | -19.1 |
Annual Sum or Average | 0.855304E+10 | |||
Minimum of Months | 463494.76 | 712.51 | -27.8 | |
Maximum of Months | 0.239071E+10 | 2109.05 | 16.70 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.662021E+09 | 1842.32 | 31-JAN-11:42 | -23.1 |
February | 0.381943E+09 | 2321.61 | 04-FEB-11:22 | -23.0 |
March | 27141038.70 | 465.85 | 01-MAR-15:00 | -3.9 |
April | 2185997.98 | 198.60 | 03-APR-08:03 | -5.9 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 |
November | 0.150227E+09 | 1760.55 | 26-NOV-08:51 | -23.3 |
December | 0.460242E+09 | 1458.09 | 09-DEC-17:00 | -19.4 |
Annual Sum or Average | 0.168376E+10 | |||
Minimum of Months | 0.00 | 0.00 | -23.3 | |
Maximum of Months | 0.662021E+09 | 2321.61 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.282815E+10 | 2344.76 | 19-JAN-19:13 | -23.3 |
February | 0.180346E+10 | 2556.43 | 03-FEB-08:03 | -33.7 |
March | 0.106562E+10 | 2245.35 | 01-MAR-16:02 | -3.9 |
April | 0.438077E+09 | 2213.63 | 03-APR-08:62 | -5.9 |
May | 31661042.22 | 2117.50 | 02-MAY-08:61 | 4.08 |
June | 13712000.58 | 1239.81 | 04-JUN-08:03 | 11.38 |
July | 1689607.61 | 957.15 | 06-JUL-08:04 | 19.90 |
August | 1743050.05 | 1074.29 | 07-AUG-08:03 | 15.47 |
September | 89907261.24 | 2131.92 | 30-SEP-08:61 | 3.35 |
October | 0.360159E+09 | 2163.18 | 26-OCT-08:62 | 1.28 |
November | 0.134966E+10 | 2324.27 | 26-NOV-16:13 | -13.9 |
December | 0.242855E+10 | 2360.96 | 09-DEC-16:13 | -19.1 |
Annual Sum or Average | 0.104124E+11 | |||
Minimum of Months | 1689607.61 | 957.15 | -33.7 | |
Maximum of Months | 0.282815E+10 | 2556.43 | 19.90 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.327085E+10 | 2371.40 | 31-JAN-11:05 | -24.1 |
February | 0.217680E+10 | 2522.24 | 03-FEB-11:03 | -29.2 |
March | 0.126876E+10 | 2239.77 | 05-MAR-09:01 | -8.9 |
April | 0.496785E+09 | 2205.45 | 03-APR-08:62 | -5.9 |
May | 33880177.25 | 2117.55 | 02-MAY-08:61 | 4.08 |
June | 13819232.60 | 1233.16 | 04-JUN-08:03 | 11.38 |
July | 626331.93 | 982.90 | 12-JUL-08:53 | 20.00 |
August | 1106325.56 | 1245.32 | 08-AUG-08:53 | 20.00 |
September | 0.110020E+09 | 2157.01 | 30-SEP-08:61 | 3.35 |
October | 0.512823E+09 | 2173.25 | 23-OCT-08:62 | 0.70 |
November | 0.159332E+10 | 2321.20 | 26-NOV-16:13 | -13.9 |
December | 0.278358E+10 | 2351.33 | 09-DEC-16:13 | -19.1 |
Annual Sum or Average | 0.122624E+11 | |||
Minimum of Months | 626331.93 | 982.90 | -29.2 | |
Maximum of Months | 0.327085E+10 | 2522.24 | 20.00 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.967110E+09 | 1211.80 | 26-JAN-16:13 | -11.5 |
February | 0.540567E+09 | 1169.28 | 28-FEB-19:02 | -15.7 |
March | 0.316675E+09 | 1171.90 | 01-MAR-16:02 | -3.9 |
April | 0.141661E+09 | 1156.73 | 02-APR-15:02 | 0.60 |
May | 4933523.60 | 679.04 | 09-MAY-15:04 | 17.62 |
June | 1899019.32 | 680.13 | 06-JUN-15:04 | 16.28 |
July | 764347.00 | 564.22 | 10-JUL-15:04 | 18.30 |
August | 860982.40 | 481.55 | 06-AUG-08:04 | 12.80 |
September | 14420173.05 | 531.77 | 13-SEP-15:04 | 19.22 |
October | 52108970.02 | 1100.00 | 26-OCT-08:62 | 1.28 |
November | 0.406756E+09 | 1198.40 | 26-NOV-16:13 | -13.9 |
December | 0.848689E+09 | 1225.96 | 09-DEC-16:13 | -19.1 |
Annual Sum or Average | 0.329644E+10 | |||
Minimum of Months | 764347.00 | 481.55 | -19.1 | |
Maximum of Months | 0.967110E+09 | 1225.96 | 19.22 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 7086995.12 | 4373.25 | 31-JAN-11:31 | -23.3 |
February | 15832204.59 | 5586.14 | 04-FEB-11:11 | -23.3 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 |
November | 293397.72 | 2778.41 | 26-NOV-08:51 | -23.3 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -0.7 |
Annual Sum or Average | 23212597.43 | |||
Minimum of Months | 0.00 | 0.00 | -23.3 | |
Maximum of Months | 15832204.59 | 5586.14 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5138461.74 | 4208.49 | 31-JAN-11:31 | -23.3 |
February | 8995905.30 | 5392.65 | 04-FEB-11:11 | -23.3 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 |
November | 151548.72 | 2525.81 | 26-NOV-08:51 | -23.3 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -0.7 |
Annual Sum or Average | 14285915.76 | |||
Minimum of Months | 0.00 | 0.00 | -23.3 | |
Maximum of Months | 8995905.30 | 5392.65 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | -2.8 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -24.1 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 1.65 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -0.7 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -24.1 | |
Maximum of Months | 0.00 | 0.00 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.311640E+10 | 5621.17 | 31-JAN-11:42 | -23.1 |
February | 0.149560E+10 | 6957.82 | 04-FEB-11:22 | -23.0 |
March | 0.214744E+09 | 1739.35 | 06-MAR-07:05 | -12.7 |
April | 7130683.87 | 557.06 | 03-APR-06:05 | -7.1 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 |
November | 0.716084E+09 | 5506.51 | 26-NOV-08:51 | -23.3 |
December | 0.201749E+10 | 4090.30 | 10-DEC-06:00 | -22.8 |
Annual Sum or Average | 0.756745E+10 | |||
Minimum of Months | 0.00 | 0.00 | -23.3 | |
Maximum of Months | 0.311640E+10 | 6957.82 | 18.93 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.136942E+11 | 13190.31 | 02-JAN-20:10 | 0.121516E+11 | 9632.53 | 02-JAN-20:10 |
February | 0.123646E+11 | 13190.31 | 01-FEB-20:10 | 0.109726E+11 | 9632.53 | 01-FEB-20:10 |
March | 0.137364E+11 | 13190.31 | 01-MAR-20:10 | 0.121771E+11 | 9632.53 | 01-MAR-20:10 |
April | 0.132299E+11 | 13190.31 | 03-APR-19:10 | 0.117446E+11 | 9632.53 | 03-APR-19:10 |
May | 0.137180E+11 | 13190.31 | 01-MAY-19:10 | 0.121662E+11 | 9632.53 | 01-MAY-19:10 |
June | 0.132906E+11 | 13190.31 | 01-JUN-19:10 | 0.117829E+11 | 9632.53 | 01-JUN-19:10 |
July | 0.136573E+11 | 13190.31 | 03-JUL-19:10 | 0.121279E+11 | 9632.53 | 03-JUL-19:10 |
August | 0.137417E+11 | 13190.31 | 01-AUG-19:10 | 0.121808E+11 | 9632.53 | 01-AUG-19:10 |
September | 0.132352E+11 | 13190.31 | 01-SEP-19:10 | 0.117482E+11 | 9632.53 | 01-SEP-19:10 |
October | 0.136889E+11 | 13190.31 | 02-OCT-19:10 | 0.121479E+11 | 9632.53 | 02-OCT-19:10 |
November | 0.132800E+11 | 13190.31 | 01-NOV-19:10 | 0.117774E+11 | 9632.53 | 01-NOV-19:10 |
December | 0.136573E+11 | 13190.31 | 01-DEC-20:10 | 0.121279E+11 | 9632.53 | 01-DEC-20:10 |
Annual Sum or Average | 0.161294E+12 | 0.143105E+12 | ||||
Minimum of Months | 0.123646E+11 | 13190.31 | 0.109726E+11 | 9632.53 | ||
Maximum of Months | 0.137417E+11 | 13190.31 | 0.121808E+11 | 9632.53 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.620421E+09 | 597.59 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.560184E+09 | 597.59 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.622334E+09 | 597.59 | 01-MAR-20:10 | 0.866718E+09 | 685.60 | 01-MAR-20:10 |
April | 0.599386E+09 | 597.59 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.621497E+09 | 597.59 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.602135E+09 | 597.59 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.618748E+09 | 597.59 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.622573E+09 | 597.59 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.599625E+09 | 597.59 | 01-SEP-19:10 | 0.836191E+09 | 685.60 | 01-SEP-19:10 |
October | 0.620182E+09 | 597.59 | 02-OCT-19:10 | 0.864640E+09 | 685.60 | 02-OCT-19:10 |
November | 0.601657E+09 | 597.59 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.618748E+09 | 597.59 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.730749E+10 | 0.101856E+11 | ||||
Minimum of Months | 0.560184E+09 | 597.59 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.622573E+09 | 597.59 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.718450E+09 | 692.02 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.648695E+09 | 692.02 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.720665E+09 | 692.02 | 01-MAR-20:10 | 0.100366E+10 | 793.93 | 01-MAR-20:10 |
April | 0.694091E+09 | 692.02 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.719696E+09 | 692.02 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.697275E+09 | 692.02 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.716513E+09 | 692.02 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.720942E+09 | 692.02 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.694368E+09 | 692.02 | 01-SEP-19:10 | 0.968312E+09 | 793.93 | 01-SEP-19:10 |
October | 0.718174E+09 | 692.02 | 02-OCT-19:10 | 0.100126E+10 | 793.93 | 02-OCT-19:10 |
November | 0.696721E+09 | 692.02 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.716513E+09 | 692.02 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.846210E+10 | 0.117950E+11 | ||||
Minimum of Months | 0.648695E+09 | 692.02 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.720942E+09 | 692.02 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.710312E+09 | 684.18 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.641347E+09 | 684.18 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.712502E+09 | 684.18 | 01-MAR-20:10 | 0.106120E+10 | 839.45 | 01-MAR-20:10 |
April | 0.686229E+09 | 684.18 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.711544E+09 | 684.18 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.689376E+09 | 684.18 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.708397E+09 | 684.18 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.712775E+09 | 684.18 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.686503E+09 | 684.18 | 01-SEP-19:10 | 0.102382E+10 | 839.45 | 01-SEP-19:10 |
October | 0.710039E+09 | 684.18 | 02-OCT-19:10 | 0.105866E+10 | 839.45 | 02-OCT-19:10 |
November | 0.688829E+09 | 684.18 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.708397E+09 | 684.18 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.836625E+10 | 0.124712E+11 | ||||
Minimum of Months | 0.641347E+09 | 684.18 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.712775E+09 | 684.18 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.261454E+09 | 251.84 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.236069E+09 | 251.84 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.262260E+09 | 251.84 | 01-MAR-20:10 | 0.306128E+09 | 242.16 | 01-MAR-20:10 |
April | 0.252589E+09 | 251.84 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.261907E+09 | 251.84 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.253748E+09 | 251.84 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.260749E+09 | 251.84 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.262360E+09 | 251.84 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.252690E+09 | 251.84 | 01-SEP-19:10 | 0.295345E+09 | 242.16 | 01-SEP-19:10 |
October | 0.261353E+09 | 251.84 | 02-OCT-19:10 | 0.305393E+09 | 242.16 | 02-OCT-19:10 |
November | 0.253546E+09 | 251.84 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.260749E+09 | 251.84 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.307947E+10 | 0.359760E+10 | ||||
Minimum of Months | 0.236069E+09 | 251.84 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.262360E+09 | 251.84 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.337502E+09 | 325.08 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.304733E+09 | 325.08 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.338542E+09 | 325.08 | 01-MAR-20:10 | 0.578079E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.326059E+09 | 325.08 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.338087E+09 | 325.08 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.327554E+09 | 325.08 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.336592E+09 | 325.08 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.338672E+09 | 325.08 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.326189E+09 | 325.08 | 01-SEP-19:10 | 0.557718E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.337372E+09 | 325.08 | 02-OCT-19:10 | 0.576693E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.327294E+09 | 325.08 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.336592E+09 | 325.08 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.397519E+10 | 0.679355E+11 | ||||
Minimum of Months | 0.304733E+09 | 325.08 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.338672E+09 | 325.08 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.137273E+10 | 1701.53 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.118668E+10 | 1701.53 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.122017E+10 | 1701.53 | 01-MAR-20:10 | 0.122027E+10 | 965.27 | 01-MAR-20:10 |
April | 0.108820E+10 | 1701.53 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.100426E+10 | 1701.53 | 01-MAY-19:10 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.943052E+09 | 1701.53 | 01-JUN-19:10 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.976412E+09 | 1701.53 | 03-JUL-19:30 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.105647E+10 | 1701.53 | 01-AUG-19:30 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.114096E+10 | 1701.53 | 01-SEP-19:10 | 0.117729E+10 | 965.27 | 01-SEP-19:10 |
October | 0.128357E+10 | 1701.53 | 02-OCT-19:10 | 0.121734E+10 | 965.27 | 02-OCT-19:10 |
November | 0.130868E+10 | 1701.53 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.139780E+10 | 1701.53 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.139790E+11 | 0.143405E+11 | ||||
Minimum of Months | 0.943052E+09 | 1701.53 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.139780E+10 | 1701.53 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.949127E+10 | 9504.80 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.851521E+10 | 9504.80 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.937522E+10 | 9504.80 | 01-MAR-20:10 | 0.126786E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.895688E+10 | 9504.80 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.917716E+10 | 9504.80 | 01-MAY-19:10 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.885384E+10 | 9504.80 | 01-JUN-19:10 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.910218E+10 | 9504.80 | 03-JUL-19:30 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.923280E+10 | 9504.80 | 01-AUG-19:30 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.899930E+10 | 9504.80 | 01-SEP-19:10 | 0.122320E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.940012E+10 | 9504.80 | 02-OCT-19:10 | 0.126482E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.918179E+10 | 9504.80 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.950216E+10 | 9504.80 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.109788E+12 | 0.148998E+12 | ||||
Minimum of Months | 0.851521E+10 | 9504.80 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.950216E+10 | 9504.80 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196602E+09 | 177.88 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.177551E+09 | 177.88 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.195039E+09 | 177.88 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.190486E+09 | 177.88 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.195821E+09 | 177.88 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.188975E+09 | 177.88 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.197358E+09 | 177.88 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.195039E+09 | 177.88 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.190538E+09 | 177.88 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.196576E+09 | 177.88 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.189731E+09 | 177.88 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.197383E+09 | 177.88 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.231110E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.177551E+09 | 177.88 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.197383E+09 | 177.88 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196579E+09 | 177.86 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.177530E+09 | 177.86 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.195017E+09 | 177.86 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.190464E+09 | 177.86 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.195798E+09 | 177.86 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.188953E+09 | 177.86 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.197334E+09 | 177.86 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.195017E+09 | 177.86 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.190515E+09 | 177.86 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.196553E+09 | 177.86 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.189708E+09 | 177.86 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.197360E+09 | 177.86 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.231083E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.177530E+09 | 177.86 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.197360E+09 | 177.86 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123557E+09 | 111.79 | 01-JAN-19:10 | 0.217935E+09 | 232.19 | 01-JAN-08:09 |
February | 0.111584E+09 | 111.79 | 01-FEB-20:10 | 0.196843E+09 | 232.19 | 01-FEB-07:10 |
March | 0.122575E+09 | 111.79 | 01-MAR-20:10 | 0.217824E+09 | 232.19 | 01-MAR-07:10 |
April | 0.119713E+09 | 111.79 | 01-APR-18:10 | 0.210923E+09 | 232.19 | 01-APR-07:10 |
May | 0.123066E+09 | 111.79 | 01-MAY-19:10 | 0.217879E+09 | 232.19 | 01-MAY-06:10 |
June | 0.118764E+09 | 111.79 | 01-JUN-19:10 | 0.210812E+09 | 232.19 | 01-JUN-06:10 |
July | 0.124032E+09 | 111.79 | 01-JUL-18:10 | 0.217991E+09 | 232.19 | 01-JUL-07:10 |
August | 0.122575E+09 | 111.79 | 01-AUG-19:10 | 0.217824E+09 | 232.19 | 01-AUG-06:10 |
September | 0.119746E+09 | 111.79 | 01-SEP-19:10 | 0.210923E+09 | 232.19 | 01-SEP-06:10 |
October | 0.123541E+09 | 111.79 | 01-OCT-18:10 | 0.217935E+09 | 232.19 | 01-OCT-07:10 |
November | 0.119238E+09 | 111.79 | 01-NOV-19:10 | 0.210867E+09 | 232.19 | 01-NOV-06:10 |
December | 0.124048E+09 | 111.79 | 01-DEC-20:10 | 0.217991E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.145244E+10 | 0.256575E+10 | ||||
Minimum of Months | 0.111584E+09 | 111.79 | 0.196843E+09 | 232.19 | ||
Maximum of Months | 0.124048E+09 | 111.79 | 0.217991E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123591E+09 | 111.82 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 0.111614E+09 | 111.82 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 0.122608E+09 | 111.82 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 0.119746E+09 | 111.82 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 0.123099E+09 | 111.82 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 0.118796E+09 | 111.82 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 0.124066E+09 | 111.82 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 0.122608E+09 | 111.82 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 0.119778E+09 | 111.82 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 0.123574E+09 | 111.82 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 0.119271E+09 | 111.82 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 0.124082E+09 | 111.82 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.145283E+10 | 0.256645E+10 | ||||
Minimum of Months | 0.111614E+09 | 111.82 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 0.124082E+09 | 111.82 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196602E+09 | 177.88 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.177551E+09 | 177.88 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.195039E+09 | 177.88 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.190486E+09 | 177.88 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.195821E+09 | 177.88 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.188975E+09 | 177.88 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.197358E+09 | 177.88 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.195039E+09 | 177.88 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.190538E+09 | 177.88 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.196576E+09 | 177.88 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.189731E+09 | 177.88 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.197383E+09 | 177.88 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.231110E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.177551E+09 | 177.88 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.197383E+09 | 177.88 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196579E+09 | 177.86 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.177530E+09 | 177.86 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.195017E+09 | 177.86 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.190464E+09 | 177.86 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.195798E+09 | 177.86 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.188953E+09 | 177.86 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.197334E+09 | 177.86 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.195017E+09 | 177.86 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.190515E+09 | 177.86 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.196553E+09 | 177.86 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.189708E+09 | 177.86 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.197360E+09 | 177.86 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.231083E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.177530E+09 | 177.86 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.197360E+09 | 177.86 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.193865E+10 | 1867.32 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.175042E+10 | 1867.32 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.194462E+10 | 1867.32 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.187292E+10 | 1867.32 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.194201E+10 | 1867.32 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.188151E+10 | 1867.32 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.193342E+10 | 1867.32 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.194537E+10 | 1867.32 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.187367E+10 | 1867.32 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.193790E+10 | 1867.32 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.188002E+10 | 1867.32 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.193342E+10 | 1867.32 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.228339E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.175042E+10 | 1867.32 | 0.00 | 0.00 | |
Maximum of Months | 0.194537E+10 | 1867.32 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196602E+09 | 177.88 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.177551E+09 | 177.88 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.195039E+09 | 177.88 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.190486E+09 | 177.88 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.195821E+09 | 177.88 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.188975E+09 | 177.88 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.197358E+09 | 177.88 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.195039E+09 | 177.88 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.190538E+09 | 177.88 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.196576E+09 | 177.88 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.189731E+09 | 177.88 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.197383E+09 | 177.88 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.231110E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.177551E+09 | 177.88 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.197383E+09 | 177.88 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196579E+09 | 177.86 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.177530E+09 | 177.86 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.195017E+09 | 177.86 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.190464E+09 | 177.86 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.195798E+09 | 177.86 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.188953E+09 | 177.86 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.197334E+09 | 177.86 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.195017E+09 | 177.86 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.190515E+09 | 177.86 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.196553E+09 | 177.86 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.189708E+09 | 177.86 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.197360E+09 | 177.86 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.231083E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.177530E+09 | 177.86 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.197360E+09 | 177.86 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123591E+09 | 111.82 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 0.111614E+09 | 111.82 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 0.122608E+09 | 111.82 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 0.119746E+09 | 111.82 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 0.123099E+09 | 111.82 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 0.118796E+09 | 111.82 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 0.124066E+09 | 111.82 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 0.122608E+09 | 111.82 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 0.119778E+09 | 111.82 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 0.123574E+09 | 111.82 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 0.119271E+09 | 111.82 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 0.124082E+09 | 111.82 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.145283E+10 | 0.256645E+10 | ||||
Minimum of Months | 0.111614E+09 | 111.82 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 0.124082E+09 | 111.82 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.280253E+10 | 2988.03 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.248130E+10 | 2988.03 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.264408E+10 | 2988.03 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.245212E+10 | 2988.03 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.240571E+10 | 2988.03 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.228996E+10 | 2988.03 | 01-JUN-19:10 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.236708E+10 | 2988.03 | 03-JUL-19:30 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.246339E+10 | 2988.03 | 01-AUG-19:30 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.250707E+10 | 2988.03 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.271012E+10 | 2988.03 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.269615E+10 | 2988.03 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.284647E+10 | 2988.03 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.306660E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.228996E+10 | 2988.03 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.284647E+10 | 2988.03 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.280253E+10 | 2988.03 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.248130E+10 | 2988.03 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.264408E+10 | 2988.03 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.245212E+10 | 2988.03 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.240571E+10 | 2988.03 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.228996E+10 | 2988.03 | 01-JUN-19:10 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.236708E+10 | 2988.03 | 03-JUL-19:30 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.246339E+10 | 2988.03 | 01-AUG-19:30 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.250707E+10 | 2988.03 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.271012E+10 | 2988.03 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.269615E+10 | 2988.03 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.284647E+10 | 2988.03 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.306660E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.228996E+10 | 2988.03 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.284647E+10 | 2988.03 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.110133E+10 | 1060.81 | 02-JAN-20:10 | 0.368383E+11 | 16487.34 | 01-JAN-07:10 |
February | 0.994402E+09 | 1060.81 | 01-FEB-20:10 | 0.332733E+11 | 16487.34 | 01-FEB-07:10 |
March | 0.110473E+10 | 1060.81 | 01-MAR-20:10 | 0.368383E+11 | 16487.34 | 01-MAR-07:10 |
April | 0.106399E+10 | 1060.81 | 03-APR-19:10 | 0.356500E+11 | 16487.34 | 01-APR-06:10 |
May | 0.110324E+10 | 1060.81 | 01-MAY-19:10 | 0.368383E+11 | 16487.34 | 01-MAY-06:10 |
June | 0.106887E+10 | 1060.81 | 01-JUN-19:10 | 0.356500E+11 | 16487.34 | 01-JUN-06:10 |
July | 0.109836E+10 | 1060.81 | 03-JUL-19:10 | 0.368383E+11 | 16487.34 | 01-JUL-06:10 |
August | 0.110515E+10 | 1060.81 | 01-AUG-19:10 | 0.368383E+11 | 16487.34 | 01-AUG-06:10 |
September | 0.106442E+10 | 1060.81 | 01-SEP-19:10 | 0.356500E+11 | 16487.34 | 01-SEP-06:10 |
October | 0.110091E+10 | 1060.81 | 02-OCT-19:10 | 0.368383E+11 | 16487.34 | 01-OCT-06:10 |
November | 0.106802E+10 | 1060.81 | 01-NOV-19:10 | 0.356500E+11 | 16487.34 | 01-NOV-06:10 |
December | 0.109836E+10 | 1060.81 | 01-DEC-20:10 | 0.368383E+11 | 16487.34 | 01-DEC-07:10 |
Annual Sum or Average | 0.129718E+11 | 0.433742E+12 | ||||
Minimum of Months | 0.994402E+09 | 1060.81 | 0.332733E+11 | 16487.34 | ||
Maximum of Months | 0.110515E+10 | 1060.81 | 0.368383E+11 | 16487.34 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.205176E+10 | 1976.27 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.185255E+10 | 1976.27 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.205809E+10 | 1976.27 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.198220E+10 | 1976.27 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.205532E+10 | 1976.27 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.199129E+10 | 1976.27 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.204623E+10 | 1976.27 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.205888E+10 | 1976.27 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.198299E+10 | 1976.27 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.205097E+10 | 1976.27 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.198971E+10 | 1976.27 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.204623E+10 | 1976.27 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.241662E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.185255E+10 | 1976.27 | 0.00 | 0.00 | |
Maximum of Months | 0.205888E+10 | 1976.27 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.136942E+11 | 0.121516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.123646E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196682E+11 | 0.137364E+11 | 0.121771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.132299E+11 | 0.117446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.137180E+11 | 0.121662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.132906E+11 | 0.117829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.136573E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.137417E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189689E+11 | 0.132352E+11 | 0.117482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195854E+11 | 0.136889E+11 | 0.121479E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.132800E+11 | 0.117774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.136573E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230861E+12 | 0.161294E+12 | 0.143105E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.176991E+11 | 0.123646E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196682E+11 | 0.137417E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.620421E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.515789E+09 |
February | 0.179968E+10 | 0.560184E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.387464E+09 |
March | 0.199990E+10 | 0.622334E+09 | 0.866718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309310E+09 |
April | 0.192973E+10 | 0.599386E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1626368.67 | 0.207220E+09 |
May | 0.199475E+10 | 0.621497E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1785567.69 | 0.108811E+09 |
June | 0.193394E+10 | 0.602135E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11806273.85 | 55989030.44 |
July | 0.199054E+10 | 0.618748E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9548164.57 | 34741254.37 |
August | 0.199896E+10 | 0.622573E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9272180.96 | 46807408.90 |
September | 0.192879E+10 | 0.599625E+09 | 0.836191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5758293.31 | 0.100869E+09 |
October | 0.199148E+10 | 0.620182E+09 | 0.864640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204471E+09 |
November | 0.192552E+10 | 0.601657E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.305504E+09 |
December | 0.199054E+10 | 0.618748E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.438422E+09 |
Annual Sum or Average | 0.234744E+11 | 0.730749E+10 | 0.101856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 39796849.05 | 0.271540E+10 |
Minimum of Months | 0.179968E+10 | 0.560184E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34741254.37 |
Maximum of Months | 0.199990E+10 | 0.622573E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11806273.85 | 0.515789E+09 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.718450E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200660E+09 |
February | 0.208403E+10 | 0.648695E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151319E+09 |
March | 0.231589E+10 | 0.720665E+09 | 0.100366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122962E+09 |
April | 0.223463E+10 | 0.694091E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 712356.27 | 84749946.57 |
May | 0.230993E+10 | 0.719696E+09 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 760859.00 | 48871788.92 |
June | 0.223950E+10 | 0.697275E+09 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4536927.41 | 26737542.62 |
July | 0.230505E+10 | 0.716513E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3741768.42 | 18160115.14 |
August | 0.231480E+10 | 0.720942E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3718195.15 | 22904559.42 |
September | 0.223354E+10 | 0.694368E+09 | 0.968312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2462868.62 | 44433755.66 |
October | 0.230614E+10 | 0.718174E+09 | 0.100126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.72 | 84818959.03 |
November | 0.222975E+10 | 0.696721E+09 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122035E+09 |
December | 0.230505E+10 | 0.716513E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170699E+09 |
Annual Sum or Average | 0.271834E+11 | 0.846210E+10 | 0.117950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 15933062.59 | 0.109835E+10 |
Minimum of Months | 0.208403E+10 | 0.648695E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18160115.14 |
Maximum of Months | 0.231589E+10 | 0.720942E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4536927.41 | 0.200660E+09 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.487480E+09 | 0.710312E+09 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.472441E+09 |
February | 0.440737E+09 | 0.641347E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.351155E+09 |
March | 0.489771E+09 | 0.712502E+09 | 0.106120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280837E+09 |
April | 0.472586E+09 | 0.686229E+09 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1952646.66 | 0.190199E+09 |
May | 0.488511E+09 | 0.711544E+09 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2005618.03 | 0.109559E+09 |
June | 0.473617E+09 | 0.689376E+09 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10698373.13 | 61122640.20 |
July | 0.487480E+09 | 0.708397E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8712505.86 | 41914147.73 |
August | 0.489542E+09 | 0.712775E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8856441.55 | 52881932.42 |
September | 0.472357E+09 | 0.686503E+09 | 0.102382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6161967.47 | 0.101338E+09 |
October | 0.487709E+09 | 0.710039E+09 | 0.105866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26665.73 | 0.189842E+09 |
November | 0.471555E+09 | 0.688829E+09 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281062E+09 |
December | 0.487480E+09 | 0.708397E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.397652E+09 |
Annual Sum or Average | 0.574883E+10 | 0.836625E+10 | 0.124712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 38414218.43 | 0.253000E+10 |
Minimum of Months | 0.440737E+09 | 0.641347E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41914147.73 |
Maximum of Months | 0.489771E+09 | 0.712775E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10698373.13 | 0.472441E+09 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.374985E+09 | 0.261454E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.271880E+09 |
February | 0.339028E+09 | 0.236069E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201680E+09 |
March | 0.376747E+09 | 0.262260E+09 | 0.306128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161012E+09 |
April | 0.363528E+09 | 0.252589E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1163318.82 | 0.108088E+09 |
May | 0.375778E+09 | 0.261907E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1217006.94 | 60957861.03 |
June | 0.364321E+09 | 0.253748E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6423097.92 | 33714312.87 |
July | 0.374985E+09 | 0.260749E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5349176.28 | 22735364.58 |
August | 0.376571E+09 | 0.262360E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5416808.58 | 28841573.50 |
September | 0.363352E+09 | 0.252690E+09 | 0.295345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3706682.57 | 56206428.29 |
October | 0.375161E+09 | 0.261353E+09 | 0.305393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18783.39 | 0.106533E+09 |
November | 0.362735E+09 | 0.253546E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160923E+09 |
December | 0.374985E+09 | 0.260749E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229358E+09 |
Annual Sum or Average | 0.442217E+10 | 0.307947E+10 | 0.359760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23294874.49 | 0.144193E+10 |
Minimum of Months | 0.339028E+09 | 0.236069E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22735364.58 |
Maximum of Months | 0.376747E+09 | 0.262360E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6423097.92 | 0.271880E+09 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.337502E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.663333E+09 |
February | 0.139600E+10 | 0.304733E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.497563E+09 |
March | 0.155131E+10 | 0.338542E+09 | 0.578079E+10 | 0.502211E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.416356E+09 |
April | 0.149688E+10 | 0.326059E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 2578837.77 | 0.283952E+09 |
May | 0.154732E+10 | 0.338087E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 2661611.44 | 0.159882E+09 |
June | 0.150015E+10 | 0.327554E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 16366300.50 | 83870981.86 |
July | 0.154405E+10 | 0.336592E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 14706885.29 | 53602326.54 |
August | 0.155059E+10 | 0.338672E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 14395119.69 | 68604338.76 |
September | 0.149615E+10 | 0.326189E+09 | 0.557718E+10 | 0.484522E+11 | 0.00 | 0.00 | 0.00 | 9581667.11 | 0.142371E+09 |
October | 0.154478E+10 | 0.337372E+09 | 0.576693E+10 | 0.501006E+11 | 0.00 | 0.00 | 0.00 | 963.42 | 0.281646E+09 |
November | 0.149361E+10 | 0.327294E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.410911E+09 |
December | 0.154405E+10 | 0.336592E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.579144E+09 |
Annual Sum or Average | 0.182090E+11 | 0.397519E+10 | 0.679355E+11 | 0.590196E+12 | 0.00 | 0.00 | 0.00 | 60291385.22 | 0.364123E+10 |
Minimum of Months | 0.139600E+10 | 0.304733E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 53602326.54 |
Maximum of Months | 0.155131E+10 | 0.338672E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 16366300.50 | 0.663333E+09 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.137273E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114950E+10 |
February | 0.236489E+11 | 0.118668E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.872439E+09 |
March | 0.262800E+11 | 0.122017E+10 | 0.122027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.706901E+09 |
April | 0.253579E+11 | 0.108820E+10 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3490164.67 | 0.484206E+09 |
May | 0.262123E+11 | 0.100426E+10 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3664536.77 | 0.276247E+09 |
June | 0.254132E+11 | 0.943052E+09 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25103605.17 | 0.148493E+09 |
July | 0.261570E+11 | 0.976412E+09 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20471945.66 | 99199185.91 |
August | 0.262677E+11 | 0.105647E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19522087.94 | 0.126870E+09 |
September | 0.253456E+11 | 0.114096E+10 | 0.117729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12635282.79 | 0.250367E+09 |
October | 0.261693E+11 | 0.128357E+10 | 0.121734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.485509E+09 |
November | 0.253025E+11 | 0.130868E+10 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.695532E+09 |
December | 0.261570E+11 | 0.139780E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.980758E+09 |
Annual Sum or Average | 0.308468E+12 | 0.139790E+11 | 0.143405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 84887623.00 | 0.627602E+10 |
Minimum of Months | 0.236489E+11 | 0.943052E+09 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99199185.91 |
Maximum of Months | 0.262800E+11 | 0.139780E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25103605.17 | 0.114950E+10 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.949127E+10 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.331979E+10 |
February | 0.702046E+11 | 0.851521E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251560E+10 |
March | 0.780153E+11 | 0.937522E+10 | 0.126786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205811E+10 |
April | 0.752779E+11 | 0.895688E+10 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 11040525.43 | 0.141777E+10 |
May | 0.778146E+11 | 0.917716E+10 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 11890715.87 | 0.824699E+09 |
June | 0.754422E+11 | 0.885384E+10 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 74439639.34 | 0.448365E+09 |
July | 0.776503E+11 | 0.910218E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 61820864.90 | 0.301090E+09 |
August | 0.779788E+11 | 0.923280E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 59742534.67 | 0.379549E+09 |
September | 0.752414E+11 | 0.899930E+10 | 0.122320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 38393599.33 | 0.744597E+09 |
October | 0.776868E+11 | 0.940012E+10 | 0.126482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142794E+10 |
November | 0.751137E+11 | 0.918179E+10 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203800E+10 |
December | 0.776503E+11 | 0.950216E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283872E+10 |
Annual Sum or Average | 0.915726E+12 | 0.109788E+12 | 0.148998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257328E+09 | 0.183142E+11 |
Minimum of Months | 0.702046E+11 | 0.851521E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.301090E+09 |
Maximum of Months | 0.780153E+11 | 0.950216E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 74439639.34 | 0.331979E+10 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196602E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299683E+09 |
February | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229122E+09 |
March | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178013E+09 |
April | 0.293479E+09 | 0.190486E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1405004.25 | 0.118898E+09 |
May | 0.303504E+09 | 0.195821E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1540180.60 | 63197242.27 |
June | 0.293842E+09 | 0.188975E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9671718.53 | 30372426.13 |
July | 0.303141E+09 | 0.197358E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9060957.38 | 16287725.36 |
August | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8419429.25 | 22659722.01 |
September | 0.293479E+09 | 0.190538E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5167258.74 | 55431195.94 |
October | 0.303322E+09 | 0.196576E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9351.44 | 0.117303E+09 |
November | 0.293661E+09 | 0.189731E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175924E+09 |
December | 0.303141E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250768E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231110E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35273900.17 | 0.155766E+10 |
Minimum of Months | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16287725.36 |
Maximum of Months | 0.303685E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9671718.53 | 0.299683E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196579E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298460E+09 |
February | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227103E+09 |
March | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176223E+09 |
April | 0.293479E+09 | 0.190464E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1327044.24 | 0.119017E+09 |
May | 0.303504E+09 | 0.195798E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1388494.48 | 66363707.81 |
June | 0.293842E+09 | 0.188953E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8957150.40 | 34874086.20 |
July | 0.303141E+09 | 0.197334E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8130702.84 | 22407163.04 |
August | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7672355.28 | 28096875.38 |
September | 0.293479E+09 | 0.190515E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4841470.97 | 57629393.78 |
October | 0.303322E+09 | 0.196553E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2869.37 | 0.115778E+09 |
November | 0.293661E+09 | 0.189708E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174464E+09 |
December | 0.303141E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249099E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231083E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32320087.59 | 0.156951E+10 |
Minimum of Months | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22407163.04 |
Maximum of Months | 0.303685E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8957150.40 | 0.298460E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.123557E+09 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75060517.05 |
February | 0.00 | 0.111584E+09 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63577340.76 |
March | 0.00 | 0.122575E+09 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53900682.54 |
April | 0.00 | 0.119713E+09 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 77224.57 | 42451983.54 |
May | 0.00 | 0.123066E+09 | 0.217879E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 59428.05 | 28484168.82 |
June | 0.00 | 0.118764E+09 | 0.210812E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 650825.87 | 17103934.61 |
July | 0.00 | 0.124032E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 244766.62 | 13206824.11 |
August | 0.00 | 0.122575E+09 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 346163.63 | 15315580.57 |
September | 0.00 | 0.119746E+09 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 317294.44 | 25171642.63 |
October | 0.00 | 0.123541E+09 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44273339.30 |
November | 0.00 | 0.119238E+09 | 0.210867E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54578202.22 |
December | 0.00 | 0.124048E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64080252.85 |
Annual Sum or Average | 0.00 | 0.145244E+10 | 0.256575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1695703.18 | 0.497204E+09 |
Minimum of Months | 0.00 | 0.111584E+09 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13206824.11 |
Maximum of Months | 0.00 | 0.124048E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 650825.87 | 75060517.05 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.123591E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83593319.53 |
February | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63606281.19 |
March | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49618384.49 |
April | 0.293479E+09 | 0.119746E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 381773.44 | 33192251.17 |
May | 0.303504E+09 | 0.123099E+09 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 401833.93 | 17890916.50 |
June | 0.293842E+09 | 0.118796E+09 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2541042.10 | 9096733.13 |
July | 0.303141E+09 | 0.124066E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2323790.03 | 5447242.69 |
August | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2213886.97 | 7120708.82 |
September | 0.293479E+09 | 0.119778E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1402741.54 | 15724458.19 |
October | 0.303322E+09 | 0.123574E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5971.92 | 32445367.67 |
November | 0.293661E+09 | 0.119271E+09 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49201950.78 |
December | 0.303141E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70022635.38 |
Annual Sum or Average | 0.357224E+10 | 0.145283E+10 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9271039.93 | 0.436960E+09 |
Minimum of Months | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5447242.69 |
Maximum of Months | 0.303685E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2541042.10 | 83593319.53 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196602E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299521E+09 |
February | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228967E+09 |
March | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178659E+09 |
April | 0.293479E+09 | 0.190486E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1407388.17 | 0.119160E+09 |
May | 0.303504E+09 | 0.195821E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1541418.91 | 63614982.95 |
June | 0.293842E+09 | 0.188975E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9670561.10 | 30537119.68 |
July | 0.303141E+09 | 0.197358E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9072236.41 | 16413000.73 |
August | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8422159.33 | 22820944.63 |
September | 0.293479E+09 | 0.190538E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5177155.89 | 55771649.77 |
October | 0.303322E+09 | 0.196576E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9748.11 | 0.117741E+09 |
November | 0.293661E+09 | 0.189731E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175815E+09 |
December | 0.303141E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250489E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231110E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35300667.92 | 0.155951E+10 |
Minimum of Months | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16413000.73 |
Maximum of Months | 0.303685E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9670561.10 | 0.299521E+09 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196579E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298374E+09 |
February | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226799E+09 |
March | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176824E+09 |
April | 0.293479E+09 | 0.190464E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1326035.55 | 0.119039E+09 |
May | 0.303504E+09 | 0.195798E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1379530.96 | 65974812.39 |
June | 0.293842E+09 | 0.188953E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8908465.53 | 34600175.72 |
July | 0.303141E+09 | 0.197334E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8092685.26 | 22325583.34 |
August | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7651378.15 | 27584847.42 |
September | 0.293479E+09 | 0.190515E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4825473.97 | 57722207.71 |
October | 0.303322E+09 | 0.196553E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4035.61 | 0.115951E+09 |
November | 0.293661E+09 | 0.189708E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174337E+09 |
December | 0.303141E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248996E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231083E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32187605.03 | 0.156853E+10 |
Minimum of Months | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22325583.34 |
Maximum of Months | 0.303685E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8908465.53 | 0.298374E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.385223E+10 | 0.193865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364463E+09 |
February | 0.348285E+10 | 0.175042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273944E+09 |
March | 0.387034E+10 | 0.194462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215518E+09 |
April | 0.373454E+10 | 0.187292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1514745.21 | 0.145672E+09 |
May | 0.386038E+10 | 0.194201E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1585200.51 | 82276044.07 |
June | 0.374269E+10 | 0.188151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8363596.98 | 45427793.61 |
July | 0.385223E+10 | 0.193342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6718858.88 | 30913593.75 |
August | 0.386853E+10 | 0.194537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6926402.70 | 38702617.06 |
September | 0.373273E+10 | 0.187367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4657208.71 | 75537668.87 |
October | 0.385404E+10 | 0.193790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18047.29 | 0.141530E+09 |
November | 0.372639E+10 | 0.188002E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214271E+09 |
December | 0.385223E+10 | 0.193342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306316E+09 |
Annual Sum or Average | 0.454292E+11 | 0.228339E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29784060.29 | 0.193457E+10 |
Minimum of Months | 0.348285E+10 | 0.175042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30913593.75 |
Maximum of Months | 0.387034E+10 | 0.194537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8363596.98 | 0.364463E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196602E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299605E+09 |
February | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228903E+09 |
March | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177635E+09 |
April | 0.293479E+09 | 0.190486E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1380121.37 | 0.118856E+09 |
May | 0.303504E+09 | 0.195821E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1507282.02 | 63509360.44 |
June | 0.293842E+09 | 0.188975E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9518479.05 | 30569411.18 |
July | 0.303141E+09 | 0.197358E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8864950.58 | 16509861.64 |
August | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8253998.36 | 22882100.73 |
September | 0.293479E+09 | 0.190538E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5077272.41 | 55506479.60 |
October | 0.303322E+09 | 0.196576E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8633.08 | 0.117169E+09 |
November | 0.293661E+09 | 0.189731E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175612E+09 |
December | 0.303141E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250622E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231110E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34610736.88 | 0.155738E+10 |
Minimum of Months | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16509861.64 |
Maximum of Months | 0.303685E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9518479.05 | 0.299605E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196579E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298658E+09 |
February | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227037E+09 |
March | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175931E+09 |
April | 0.293479E+09 | 0.190464E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1306359.85 | 0.119037E+09 |
May | 0.303504E+09 | 0.195798E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1361044.10 | 67082763.61 |
June | 0.293842E+09 | 0.188953E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8823962.01 | 35536851.62 |
July | 0.303141E+09 | 0.197334E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7968991.30 | 23001589.75 |
August | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7535979.44 | 28699717.03 |
September | 0.293479E+09 | 0.190515E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4767667.55 | 57783928.01 |
October | 0.303322E+09 | 0.196553E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2752.79 | 0.115455E+09 |
November | 0.293661E+09 | 0.189708E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174263E+09 |
December | 0.303141E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249329E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231083E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31766757.06 | 0.157182E+10 |
Minimum of Months | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23001589.75 |
Maximum of Months | 0.303685E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8823962.01 | 0.298658E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.123591E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155397E+09 |
February | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119185E+09 |
March | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92245544.34 |
April | 0.293479E+09 | 0.119746E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 706830.88 | 61252081.71 |
May | 0.303504E+09 | 0.123099E+09 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 773095.00 | 32580103.24 |
June | 0.293842E+09 | 0.118796E+09 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4881548.26 | 15683867.71 |
July | 0.303141E+09 | 0.124066E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4551884.50 | 8419138.69 |
August | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4227546.85 | 11699386.61 |
September | 0.293479E+09 | 0.119778E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2597051.72 | 28673798.77 |
October | 0.303322E+09 | 0.123574E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3121.52 | 60857991.55 |
November | 0.293661E+09 | 0.119271E+09 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91331399.87 |
December | 0.303141E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129861E+09 |
Annual Sum or Average | 0.357224E+10 | 0.145283E+10 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17741078.73 | 0.807186E+09 |
Minimum of Months | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8419138.69 |
Maximum of Months | 0.303685E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4881548.26 | 0.155397E+09 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.280253E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.772220E+09 |
February | 0.415303E+11 | 0.248130E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.587735E+09 |
March | 0.461508E+11 | 0.264408E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.486481E+09 |
April | 0.445315E+11 | 0.245212E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2112614.38 | 0.337415E+09 |
May | 0.460320E+11 | 0.240571E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1983689.62 | 0.198649E+09 |
June | 0.446286E+11 | 0.228996E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 13792670.59 | 0.108396E+09 |
July | 0.459349E+11 | 0.236708E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 10383521.03 | 72875472.40 |
August | 0.461292E+11 | 0.246339E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 10616190.40 | 90347938.30 |
September | 0.445099E+11 | 0.250707E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 7733404.42 | 0.175336E+09 |
October | 0.459565E+11 | 0.271012E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.334913E+09 |
November | 0.444343E+11 | 0.269615E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.479363E+09 |
December | 0.459349E+11 | 0.284647E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.665262E+09 |
Annual Sum or Average | 0.541708E+12 | 0.306660E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 46622090.44 | 0.430899E+10 |
Minimum of Months | 0.415303E+11 | 0.228996E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72875472.40 |
Maximum of Months | 0.461508E+11 | 0.284647E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 13792670.59 | 0.772220E+09 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.280253E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.777697E+09 |
February | 0.415303E+11 | 0.248130E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.591615E+09 |
March | 0.461508E+11 | 0.264408E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.490373E+09 |
April | 0.445315E+11 | 0.245212E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2088785.62 | 0.339888E+09 |
May | 0.460320E+11 | 0.240571E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1966669.63 | 0.199679E+09 |
June | 0.446286E+11 | 0.228996E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 13765010.21 | 0.108864E+09 |
July | 0.459349E+11 | 0.236708E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 10335170.87 | 73102318.00 |
August | 0.461292E+11 | 0.246339E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 10515781.72 | 90645163.60 |
September | 0.445099E+11 | 0.250707E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 7657101.79 | 0.176353E+09 |
October | 0.459565E+11 | 0.271012E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.337606E+09 |
November | 0.444343E+11 | 0.269615E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.483324E+09 |
December | 0.459349E+11 | 0.284647E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.670730E+09 |
Annual Sum or Average | 0.541708E+12 | 0.306660E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 46328519.84 | 0.433987E+10 |
Minimum of Months | 0.415303E+11 | 0.228996E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73102318.00 |
Maximum of Months | 0.461508E+11 | 0.284647E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 13765010.21 | 0.777697E+09 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.110133E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.699448E+09 |
February | 0.369574E+10 | 0.994402E+09 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.529286E+09 |
March | 0.410691E+10 | 0.110473E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.439832E+09 |
April | 0.396281E+10 | 0.106399E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 1859526.43 | 0.303892E+09 |
May | 0.409635E+10 | 0.110324E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 1764069.06 | 0.177836E+09 |
June | 0.397146E+10 | 0.106887E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 12335900.31 | 96967797.59 |
July | 0.408770E+10 | 0.109836E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 9262989.45 | 65061274.90 |
August | 0.410499E+10 | 0.110515E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 9403992.80 | 80672858.37 |
September | 0.396089E+10 | 0.106442E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 6829465.80 | 0.157293E+09 |
October | 0.408962E+10 | 0.110091E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.301836E+09 |
November | 0.395417E+10 | 0.106802E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.434159E+09 |
December | 0.408770E+10 | 0.109836E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.605973E+09 |
Annual Sum or Average | 0.482060E+11 | 0.129718E+11 | 0.392709E+12 | 0.359593E+12 | 0.00 | 0.00 | 0.00 | 41455943.84 | 0.389226E+10 |
Minimum of Months | 0.369574E+10 | 0.994402E+09 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 65061274.90 |
Maximum of Months | 0.410691E+10 | 0.110515E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 12335900.31 | 0.699448E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.407704E+10 | 0.205176E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.643675E+09 |
February | 0.368610E+10 | 0.185255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.480168E+09 |
March | 0.409620E+10 | 0.205809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382459E+09 |
April | 0.395248E+10 | 0.198220E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2207374.44 | 0.259005E+09 |
May | 0.408566E+10 | 0.205532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2085815.09 | 0.147334E+09 |
June | 0.396110E+10 | 0.199129E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12702529.01 | 81793852.26 |
July | 0.407704E+10 | 0.204623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9646133.84 | 55356840.93 |
August | 0.409429E+10 | 0.205888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10187327.55 | 68772519.40 |
September | 0.395056E+10 | 0.198299E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7181197.79 | 0.131948E+09 |
October | 0.407896E+10 | 0.205097E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4664.80 | 0.251248E+09 |
November | 0.394385E+10 | 0.198971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.379786E+09 |
December | 0.407704E+10 | 0.204623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.543246E+09 |
Annual Sum or Average | 0.480803E+11 | 0.241662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44015042.51 | 0.342479E+10 |
Minimum of Months | 0.368610E+10 | 0.185255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55356840.93 |
Maximum of Months | 0.409620E+10 | 0.205888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12702529.01 | 0.643675E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 13190.31 | 02-JAN-20:10 | 9632.53 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 13190.31 | 01-FEB-20:10 | 9632.53 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 13190.31 | 01-MAR-20:10 | 9632.53 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 13190.31 | 03-APR-19:10 | 9632.53 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 13190.31 | 01-MAY-19:10 | 9632.53 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 13190.31 | 01-JUN-19:10 | 9632.53 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 13190.31 | 03-JUL-19:10 | 9632.53 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 13190.31 | 01-AUG-19:10 | 9632.53 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 13190.31 | 01-SEP-19:10 | 9632.53 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 01-OCT-23:10 | 13190.31 | 02-OCT-19:10 | 9632.53 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 13190.31 | 01-NOV-19:10 | 9632.53 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 13190.31 | 01-DEC-20:10 | 9632.53 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 11501.89 | 13190.31 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 13190.31 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 597.59 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 284.36 | 30-JAN-11:40 |
February | 1169.53 | 01-FEB-00:10 | 597.59 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 306.92 | 02-FEB-06:00 |
March | 1169.53 | 01-MAR-00:10 | 597.59 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 224.79 | 06-MAR-01:00 |
April | 1169.53 | 01-APR-00:10 | 597.59 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.11 | 15-APR-17:00 | 160.25 | 03-APR-06:00 |
May | 1169.53 | 01-MAY-00:10 | 597.59 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.50 | 31-MAY-13:00 | 113.02 | 03-MAY-03:00 |
June | 1169.53 | 01-JUN-00:10 | 597.59 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.12 | 11-JUN-15:00 | 88.00 | 01-JUN-05:00 |
July | 1169.53 | 01-JUL-00:10 | 597.59 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.48 | 26-JUL-18:00 | 61.16 | 24-JUL-03:00 |
August | 1169.53 | 01-AUG-00:10 | 597.59 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.89 | 04-AUG-15:00 | 68.68 | 07-AUG-06:00 |
September | 1169.53 | 01-SEP-00:10 | 597.59 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.37 | 07-SEP-14:00 | 122.56 | 30-SEP-01:00 |
October | 1169.53 | 01-OCT-23:10 | 597.59 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 136.82 | 23-OCT-06:00 |
November | 1169.53 | 01-NOV-00:10 | 597.59 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 271.41 | 26-NOV-07:00 |
December | 1169.53 | 01-DEC-00:10 | 597.59 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 262.44 | 09-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1169.53 | 597.59 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.16 | |||||
Maximum of Months | 1169.53 | 597.59 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 47.89 | 306.92 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 692.02 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 113.73 | 31-JAN-04:00 |
February | 1354.32 | 01-FEB-00:10 | 692.02 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 125.60 | 02-FEB-06:00 |
March | 1354.32 | 01-MAR-00:10 | 692.02 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 88.07 | 06-MAR-01:00 |
April | 1354.32 | 01-APR-00:10 | 692.02 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.85 | 15-APR-16:00 | 62.98 | 03-APR-06:00 |
May | 1354.32 | 01-MAY-00:10 | 692.02 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.04 | 31-MAY-13:00 | 47.21 | 03-MAY-03:00 |
June | 1354.32 | 01-JUN-00:10 | 692.02 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.56 | 11-JUN-15:00 | 38.59 | 01-JUN-05:00 |
July | 1354.32 | 01-JUL-00:10 | 692.02 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.44 | 26-JUL-15:00 | 27.96 | 24-JUL-05:00 |
August | 1354.32 | 01-AUG-00:10 | 692.02 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.95 | 04-AUG-15:00 | 31.51 | 07-AUG-06:00 |
September | 1354.32 | 01-SEP-00:10 | 692.02 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.37 | 06-SEP-14:00 | 50.66 | 30-SEP-01:00 |
October | 1354.32 | 01-OCT-23:10 | 692.02 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.15 | 20-OCT-15:00 | 56.02 | 23-OCT-06:00 |
November | 1354.32 | 01-NOV-00:10 | 692.02 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 111.09 | 26-NOV-07:00 |
December | 1354.32 | 01-DEC-00:10 | 692.02 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 103.00 | 08-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1354.32 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.96 | |||||
Maximum of Months | 1354.32 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 18.95 | 125.60 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 286.42 | 02-JAN-00:10 | 684.18 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 275.30 | 31-JAN-04:00 |
February | 286.42 | 01-FEB-00:10 | 684.18 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 304.96 | 02-FEB-06:10 |
March | 286.42 | 01-MAR-00:10 | 684.18 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 205.07 | 06-MAR-01:00 |
April | 286.42 | 01-APR-00:10 | 684.18 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.62 | 15-APR-16:50 | 146.19 | 03-APR-06:00 |
May | 286.42 | 01-MAY-00:10 | 684.18 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.00 | 31-MAY-13:00 | 105.73 | 03-MAY-03:00 |
June | 286.42 | 01-JUN-00:10 | 684.18 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.35 | 11-JUN-15:00 | 89.18 | 01-JUN-05:00 |
July | 286.42 | 01-JUL-00:10 | 684.18 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.70 | 26-JUL-16:00 | 64.11 | 23-JUL-04:00 |
August | 286.42 | 01-AUG-00:10 | 684.18 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.71 | 04-AUG-16:00 | 73.44 | 07-AUG-06:00 |
September | 286.42 | 01-SEP-00:10 | 684.18 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.39 | 06-SEP-14:00 | 115.50 | 30-SEP-01:00 |
October | 286.42 | 01-OCT-23:10 | 684.18 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.70 | 20-OCT-15:00 | 129.22 | 23-OCT-06:00 |
November | 286.42 | 01-NOV-00:10 | 684.18 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 269.83 | 26-NOV-07:00 |
December | 286.42 | 01-DEC-00:10 | 684.18 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 241.11 | 10-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 286.42 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.11 | |||||
Maximum of Months | 286.42 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 44.71 | 304.96 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 220.32 | 02-JAN-00:10 | 251.84 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 157.29 | 31-JAN-04:00 |
February | 220.32 | 01-FEB-00:10 | 251.84 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 173.91 | 02-FEB-06:00 |
March | 220.32 | 01-MAR-00:10 | 251.84 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 118.32 | 06-MAR-01:00 |
April | 220.32 | 01-APR-00:10 | 251.84 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.48 | 15-APR-17:00 | 84.34 | 03-APR-06:00 |
May | 220.32 | 01-MAY-00:10 | 251.84 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.09 | 31-MAY-13:00 | 59.95 | 03-MAY-03:00 |
June | 220.32 | 01-JUN-00:10 | 251.84 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.58 | 11-JUN-15:00 | 50.50 | 01-JUN-05:00 |
July | 220.32 | 01-JUL-00:10 | 251.84 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.30 | 26-JUL-16:00 | 35.89 | 23-JUL-04:00 |
August | 220.32 | 01-AUG-00:10 | 251.84 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.84 | 04-AUG-16:00 | 41.24 | 07-AUG-06:00 |
September | 220.32 | 01-SEP-00:10 | 251.84 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.44 | 06-SEP-14:00 | 65.15 | 30-SEP-01:00 |
October | 220.32 | 01-OCT-23:10 | 251.84 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.62 | 20-OCT-15:00 | 72.84 | 23-OCT-06:00 |
November | 220.32 | 01-NOV-00:10 | 251.84 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 154.18 | 26-NOV-07:00 |
December | 220.32 | 01-DEC-00:10 | 251.84 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 139.11 | 10-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 220.32 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.89 | |||||
Maximum of Months | 220.32 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 25.84 | 173.91 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 325.08 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 361.68 | 05-JAN-21:23 |
February | 907.20 | 01-FEB-00:10 | 325.08 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 377.92 | 02-FEB-21:00 |
March | 907.20 | 01-MAR-00:10 | 325.08 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 292.68 | 05-MAR-23:10 |
April | 907.20 | 01-APR-00:10 | 325.08 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 48.04 | 15-APR-17:00 | 220.75 | 03-APR-06:00 |
May | 907.20 | 01-MAY-00:10 | 325.08 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 44.30 | 31-MAY-13:00 | 154.95 | 03-MAY-05:10 |
June | 907.20 | 01-JUN-00:10 | 325.08 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 68.41 | 11-JUN-15:20 | 121.43 | 01-JUN-05:10 |
July | 907.20 | 01-JUL-00:10 | 325.08 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 47.66 | 02-JUL-16:00 | 90.26 | 24-JUL-05:10 |
August | 907.20 | 01-AUG-00:10 | 325.08 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 70.04 | 04-AUG-16:00 | 104.58 | 07-AUG-06:00 |
September | 907.20 | 01-SEP-00:10 | 325.08 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 58.30 | 07-SEP-13:50 | 165.11 | 29-SEP-23:00 |
October | 907.20 | 01-OCT-23:10 | 325.08 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 1.04 | 20-OCT-15:00 | 191.40 | 23-OCT-06:00 |
November | 907.20 | 01-NOV-00:10 | 325.08 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 356.41 | 25-NOV-21:10 |
December | 907.20 | 01-DEC-00:10 | 325.08 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 349.25 | 08-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 907.20 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 90.26 | ||||||
Maximum of Months | 907.20 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 70.04 | 377.92 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 1701.53 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 644.73 | 31-JAN-04:00 |
February | 15368.40 | 01-FEB-00:10 | 1701.53 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 706.82 | 02-FEB-06:00 |
March | 15368.40 | 01-MAR-00:10 | 1701.53 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 503.63 | 06-MAR-01:00 |
April | 15368.40 | 01-APR-00:10 | 1701.53 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.85 | 15-APR-17:00 | 359.79 | 03-APR-05:00 |
May | 15368.40 | 01-MAY-00:10 | 1701.53 | 01-MAY-19:10 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.21 | 31-MAY-13:00 | 271.80 | 03-MAY-03:00 |
June | 15368.40 | 01-JUN-00:10 | 1701.53 | 01-JUN-19:10 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 100.00 | 11-JUN-15:00 | 219.96 | 01-JUN-05:00 |
July | 15368.40 | 01-JUL-00:10 | 1701.53 | 03-JUL-19:30 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.67 | 26-JUL-18:00 | 160.29 | 24-JUL-03:00 |
August | 15368.40 | 01-AUG-00:10 | 1701.53 | 01-AUG-19:30 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.88 | 04-AUG-15:00 | 178.89 | 07-AUG-04:00 |
September | 15368.40 | 01-SEP-00:10 | 1701.53 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.26 | 07-SEP-14:00 | 289.26 | 30-SEP-01:00 |
October | 15368.40 | 01-OCT-23:10 | 1701.53 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 310.56 | 23-OCT-06:00 |
November | 15368.40 | 01-NOV-00:10 | 1701.53 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 612.81 | 26-NOV-07:00 |
December | 15368.40 | 01-DEC-00:10 | 1701.53 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 584.30 | 10-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 15368.40 | 1701.53 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.29 | |||||
Maximum of Months | 15368.40 | 1701.53 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 105.88 | 706.82 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 9504.80 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1873.72 | 31-JAN-04:00 |
February | 45622.98 | 01-FEB-00:10 | 9504.80 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 2066.34 | 02-FEB-06:00 |
March | 45622.98 | 01-MAR-00:10 | 9504.80 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 1470.09 | 06-MAR-01:00 |
April | 45622.98 | 01-APR-00:10 | 9504.80 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 206.51 | 15-APR-16:00 | 1060.73 | 03-APR-05:00 |
May | 45622.98 | 01-MAY-00:10 | 9504.80 | 01-MAY-19:10 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 210.39 | 31-MAY-13:00 | 796.07 | 03-MAY-03:00 |
June | 45622.98 | 01-JUN-00:10 | 9504.80 | 01-JUN-19:10 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 306.27 | 11-JUN-15:00 | 641.22 | 01-JUN-05:00 |
July | 45622.98 | 01-JUL-00:10 | 9504.80 | 03-JUL-19:30 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 203.42 | 26-JUL-15:00 | 470.13 | 24-JUL-05:00 |
August | 45622.98 | 01-AUG-00:10 | 9504.80 | 01-AUG-19:30 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 309.07 | 04-AUG-15:00 | 529.08 | 07-AUG-04:00 |
September | 45622.98 | 01-SEP-00:10 | 9504.80 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 257.43 | 06-SEP-14:00 | 855.33 | 30-SEP-01:00 |
October | 45622.98 | 01-OCT-23:10 | 9504.80 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 934.91 | 23-OCT-06:00 |
November | 45622.98 | 01-NOV-00:10 | 9504.80 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 1816.55 | 26-NOV-07:00 |
December | 45622.98 | 01-DEC-00:10 | 9504.80 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 1702.19 | 08-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 45622.98 | 9504.80 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 470.13 | |||||
Maximum of Months | 45622.98 | 9504.80 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 309.07 | 2066.34 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.88 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 187.25 | 31-JAN-04:00 |
February | 180.00 | 01-FEB-00:10 | 177.88 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 210.00 | 02-FEB-08:00 |
March | 180.00 | 01-MAR-00:10 | 177.88 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 131.00 | 06-MAR-01:00 |
April | 180.00 | 01-APR-00:10 | 177.88 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.08 | 15-APR-16:30 | 93.51 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 177.88 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.43 | 31-MAY-15:10 | 66.09 | 03-MAY-03:00 |
June | 180.00 | 01-JUN-00:10 | 177.88 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.96 | 11-JUN-15:10 | 50.37 | 03-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 177.88 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.43 | 26-JUL-15:10 | 34.46 | 23-JUL-04:00 |
August | 180.00 | 01-AUG-00:10 | 177.88 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.77 | 04-AUG-15:50 | 39.90 | 07-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 177.88 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.53 | 06-SEP-15:10 | 71.62 | 30-SEP-01:00 |
October | 180.00 | 01-OCT-00:10 | 177.88 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.28 | 20-OCT-15:10 | 79.91 | 23-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 177.88 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 178.02 | 26-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 177.88 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 153.94 | 10-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.46 | |||||
Maximum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 35.77 | 210.00 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.86 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 185.14 | 31-JAN-04:00 |
February | 180.00 | 01-FEB-00:10 | 177.86 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 207.65 | 02-FEB-08:00 |
March | 180.00 | 01-MAR-00:10 | 177.86 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 130.99 | 06-MAR-01:00 |
April | 180.00 | 01-APR-00:10 | 177.86 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.08 | 15-APR-15:10 | 93.50 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 177.86 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.43 | 31-MAY-15:10 | 66.09 | 03-MAY-03:00 |
June | 180.00 | 01-JUN-00:10 | 177.86 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.96 | 11-JUN-15:10 | 50.36 | 03-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 177.86 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.43 | 26-JUL-15:10 | 34.46 | 23-JUL-04:00 |
August | 180.00 | 01-AUG-00:10 | 177.86 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.78 | 04-AUG-15:10 | 39.90 | 07-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 177.86 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.05 | 06-SEP-15:10 | 71.62 | 30-SEP-01:00 |
October | 180.00 | 01-OCT-00:10 | 177.86 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.28 | 20-OCT-15:09 | 79.90 | 23-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 177.86 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 177.73 | 26-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 177.86 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 153.93 | 10-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.46 | |||||
Maximum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 35.78 | 207.65 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 111.79 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 47.10 | 31-JAN-04:00 |
February | 0.00 | 01-FEB-00:10 | 111.79 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 54.44 | 02-FEB-06:06 |
March | 0.00 | 01-MAR-00:10 | 111.79 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 33.43 | 06-MAR-01:00 |
April | 0.00 | 01-APR-00:10 | 111.79 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.60 | 15-APR-15:10 | 28.39 | 01-APR-05:00 |
May | 0.00 | 01-MAY-00:10 | 111.79 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.62 | 31-MAY-13:00 | 22.62 | 03-MAY-03:00 |
June | 0.00 | 01-JUN-00:10 | 111.79 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.18 | 11-JUN-15:00 | 18.79 | 01-JUN-05:00 |
July | 0.00 | 01-JUL-00:10 | 111.79 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.64 | 26-JUL-15:00 | 14.39 | 24-JUL-05:00 |
August | 0.00 | 01-AUG-00:10 | 111.79 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.63 | 04-AUG-15:00 | 15.95 | 07-AUG-06:00 |
September | 0.00 | 01-SEP-00:10 | 111.79 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.38 | 07-SEP-14:00 | 23.69 | 30-SEP-01:00 |
October | 0.00 | 01-OCT-00:10 | 111.79 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 26.22 | 23-OCT-06:00 |
November | 0.00 | 01-NOV-00:10 | 111.79 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 46.39 | 26-NOV-07:00 |
December | 0.00 | 01-DEC-00:10 | 111.79 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 42.47 | 08-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 0.00 | 111.79 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.39 | |||||
Maximum of Months | 0.00 | 111.79 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 5.63 | 54.44 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 111.82 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 50.86 | 31-JAN-04:00 |
February | 180.00 | 01-FEB-00:10 | 111.82 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 57.70 | 02-FEB-08:07 |
March | 180.00 | 01-MAR-00:10 | 111.82 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 36.56 | 06-MAR-01:00 |
April | 180.00 | 01-APR-00:10 | 111.82 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 15-APR-15:10 | 26.10 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 111.82 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.82 | 31-MAY-15:10 | 18.45 | 03-MAY-03:00 |
June | 180.00 | 01-JUN-00:10 | 111.82 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.48 | 11-JUN-15:10 | 14.06 | 03-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 111.82 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.10 | 26-JUL-15:10 | 9.62 | 23-JUL-04:00 |
August | 180.00 | 01-AUG-00:10 | 111.82 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.99 | 04-AUG-15:10 | 11.14 | 07-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 111.82 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 06-SEP-15:10 | 19.99 | 30-SEP-01:00 |
October | 180.00 | 01-OCT-00:10 | 111.82 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.47 | 20-OCT-15:07 | 22.30 | 23-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 111.82 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 49.11 | 26-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 111.82 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 42.96 | 10-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.62 | |||||
Maximum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 9.99 | 57.70 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.88 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 186.12 | 31-JAN-04:00 |
February | 180.00 | 01-FEB-00:10 | 177.88 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 209.54 | 02-FEB-08:00 |
March | 180.00 | 01-MAR-00:10 | 177.88 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 131.00 | 06-MAR-01:00 |
April | 180.00 | 01-APR-00:10 | 177.88 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.09 | 15-APR-15:10 | 93.51 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 177.88 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.43 | 31-MAY-15:08 | 66.09 | 03-MAY-03:00 |
June | 180.00 | 01-JUN-00:10 | 177.88 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.96 | 11-JUN-15:10 | 50.37 | 03-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 177.88 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.43 | 26-JUL-15:10 | 34.46 | 23-JUL-04:00 |
August | 180.00 | 01-AUG-00:10 | 177.88 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.79 | 04-AUG-15:08 | 39.90 | 07-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 177.88 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.05 | 06-SEP-15:10 | 71.62 | 30-SEP-01:00 |
October | 180.00 | 01-OCT-00:10 | 177.88 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.28 | 20-OCT-15:10 | 79.91 | 23-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 177.88 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 178.01 | 26-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 177.88 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 153.95 | 10-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.46 | |||||
Maximum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 35.79 | 209.54 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.86 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 183.77 | 31-JAN-04:00 |
February | 180.00 | 01-FEB-00:10 | 177.86 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 207.07 | 02-FEB-08:00 |
March | 180.00 | 01-MAR-00:10 | 177.86 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 130.99 | 06-MAR-01:00 |
April | 180.00 | 01-APR-00:10 | 177.86 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.08 | 15-APR-15:07 | 93.51 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 177.86 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.43 | 31-MAY-15:08 | 66.09 | 03-MAY-03:00 |
June | 180.00 | 01-JUN-00:10 | 177.86 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.96 | 11-JUN-15:08 | 50.36 | 03-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 177.86 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.43 | 26-JUL-15:08 | 34.46 | 23-JUL-04:00 |
August | 180.00 | 01-AUG-00:10 | 177.86 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.78 | 04-AUG-15:10 | 39.90 | 07-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 177.86 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.05 | 06-SEP-15:10 | 71.62 | 30-SEP-01:00 |
October | 180.00 | 01-OCT-00:10 | 177.86 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.28 | 20-OCT-15:07 | 79.90 | 23-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 177.86 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 177.03 | 26-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 177.86 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 153.93 | 10-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.46 | |||||
Maximum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 35.78 | 207.07 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2263.36 | 02-JAN-00:10 | 1867.32 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 216.12 | 31-JAN-04:00 |
February | 2263.36 | 01-FEB-00:10 | 1867.32 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 242.16 | 02-FEB-06:00 |
March | 2263.36 | 01-MAR-00:10 | 1867.32 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 157.95 | 06-MAR-01:00 |
April | 2263.36 | 01-APR-00:10 | 1867.32 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.81 | 15-APR-17:00 | 112.64 | 03-APR-06:00 |
May | 2263.36 | 01-MAY-00:10 | 1867.32 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.97 | 31-MAY-13:00 | 81.36 | 03-MAY-03:00 |
June | 2263.36 | 01-JUN-00:10 | 1867.32 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.18 | 11-JUN-15:00 | 67.37 | 01-JUN-05:00 |
July | 2263.36 | 01-JUL-00:10 | 1867.32 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.66 | 26-JUL-16:00 | 48.83 | 24-JUL-03:00 |
August | 2263.36 | 01-AUG-00:10 | 1867.32 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.41 | 04-AUG-16:00 | 55.37 | 07-AUG-04:00 |
September | 2263.36 | 01-SEP-00:10 | 1867.32 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.15 | 06-SEP-14:00 | 86.99 | 30-SEP-01:00 |
October | 2263.36 | 01-OCT-23:10 | 1867.32 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.11 | 20-OCT-15:00 | 96.58 | 23-OCT-06:00 |
November | 2263.36 | 01-NOV-00:10 | 1867.32 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 207.38 | 26-NOV-07:00 |
December | 2263.36 | 01-DEC-00:10 | 1867.32 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 185.69 | 10-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.83 | ||||
Maximum of Months | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.41 | 242.16 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.88 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 186.51 | 31-JAN-04:00 |
February | 180.00 | 01-FEB-00:10 | 177.88 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 208.77 | 02-FEB-08:00 |
March | 180.00 | 01-MAR-00:10 | 177.88 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 131.23 | 06-MAR-01:00 |
April | 180.00 | 01-APR-00:10 | 177.88 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.92 | 15-APR-16:50 | 93.73 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 177.88 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.27 | 31-MAY-15:10 | 66.30 | 03-MAY-03:00 |
June | 180.00 | 01-JUN-00:10 | 177.88 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.80 | 11-JUN-15:10 | 50.56 | 03-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 177.88 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.27 | 26-JUL-15:10 | 34.65 | 23-JUL-04:00 |
August | 180.00 | 01-AUG-00:10 | 177.88 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.61 | 04-AUG-16:00 | 40.10 | 07-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 177.88 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.17 | 06-SEP-15:10 | 71.83 | 30-SEP-01:00 |
October | 180.00 | 01-OCT-00:10 | 177.88 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.11 | 20-OCT-15:10 | 80.12 | 23-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 177.88 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 178.09 | 26-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 177.88 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 154.19 | 10-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.65 | |||||
Maximum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 35.61 | 208.77 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.86 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 184.00 | 31-JAN-04:00 |
February | 180.00 | 01-FEB-00:10 | 177.86 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 207.00 | 02-FEB-08:10 |
March | 180.00 | 01-MAR-00:10 | 177.86 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 131.22 | 06-MAR-01:00 |
April | 180.00 | 01-APR-00:10 | 177.86 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.92 | 15-APR-15:10 | 93.72 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 177.86 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.27 | 31-MAY-15:10 | 66.29 | 03-MAY-03:00 |
June | 180.00 | 01-JUN-00:10 | 177.86 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.79 | 11-JUN-15:10 | 50.56 | 03-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 177.86 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.26 | 26-JUL-15:10 | 34.65 | 23-JUL-04:00 |
August | 180.00 | 01-AUG-00:10 | 177.86 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.60 | 04-AUG-16:00 | 40.09 | 07-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 177.86 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.88 | 06-SEP-15:10 | 71.82 | 30-SEP-01:00 |
October | 180.00 | 01-OCT-00:10 | 177.86 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.11 | 20-OCT-15:07 | 80.11 | 23-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 177.86 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 176.89 | 26-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 177.86 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 154.18 | 10-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.65 | |||||
Maximum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 35.60 | 207.00 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 111.82 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 96.77 | 31-JAN-04:00 |
February | 180.00 | 01-FEB-00:10 | 111.82 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 109.53 | 02-FEB-08:00 |
March | 180.00 | 01-MAR-00:10 | 111.82 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 67.14 | 06-MAR-01:00 |
April | 180.00 | 01-APR-00:10 | 111.82 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.75 | 15-APR-15:10 | 47.96 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 111.82 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.42 | 31-MAY-15:10 | 33.92 | 03-MAY-03:00 |
June | 180.00 | 01-JUN-00:10 | 111.82 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.30 | 11-JUN-15:10 | 25.87 | 03-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 111.82 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.93 | 26-JUL-15:10 | 17.73 | 23-JUL-04:00 |
August | 180.00 | 01-AUG-00:10 | 111.82 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.22 | 04-AUG-15:50 | 20.52 | 07-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 111.82 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.73 | 06-SEP-15:10 | 36.75 | 30-SEP-01:00 |
October | 180.00 | 01-OCT-00:10 | 111.82 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.91 | 20-OCT-15:10 | 40.99 | 23-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 111.82 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 91.21 | 26-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 111.82 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 78.89 | 10-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.73 | |||||
Maximum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 18.22 | 109.53 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2988.03 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 429.25 | 31-JAN-04:00 |
February | 26988.77 | 01-FEB-00:10 | 2988.03 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 472.66 | 02-FEB-06:00 |
March | 26988.77 | 01-MAR-00:10 | 2988.03 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 343.02 | 06-MAR-01:00 |
April | 26988.77 | 01-APR-00:10 | 2988.03 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.86 | 15-APR-17:00 | 252.10 | 03-APR-06:00 |
May | 26988.77 | 01-MAY-00:10 | 2988.03 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.11 | 31-MAY-13:00 | 184.52 | 03-MAY-03:00 |
June | 26988.77 | 01-JUN-00:10 | 2988.03 | 01-JUN-19:10 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 63.26 | 11-JUN-15:00 | 145.41 | 03-JUN-04:00 |
July | 26988.77 | 01-JUL-00:10 | 2988.03 | 03-JUL-19:30 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.43 | 26-JUL-15:40 | 106.38 | 23-JUL-04:00 |
August | 26988.77 | 01-AUG-00:10 | 2988.03 | 01-AUG-19:30 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.20 | 04-AUG-15:00 | 119.78 | 07-AUG-06:00 |
September | 26988.77 | 01-SEP-00:10 | 2988.03 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.53 | 07-SEP-14:00 | 198.05 | 30-SEP-01:00 |
October | 26988.77 | 01-OCT-23:10 | 2988.03 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 218.64 | 23-OCT-06:00 |
November | 26988.77 | 01-NOV-00:10 | 2988.03 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 414.97 | 26-NOV-07:00 |
December | 26988.77 | 01-DEC-00:10 | 2988.03 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 398.28 | 08-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.38 | |||||
Maximum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 67.20 | 472.66 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2988.03 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 428.61 | 31-JAN-04:00 |
February | 26988.77 | 01-FEB-00:10 | 2988.03 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 471.22 | 02-FEB-06:00 |
March | 26988.77 | 01-MAR-00:10 | 2988.03 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 344.49 | 06-MAR-01:00 |
April | 26988.77 | 01-APR-00:10 | 2988.03 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.86 | 15-APR-16:50 | 252.10 | 03-APR-06:00 |
May | 26988.77 | 01-MAY-00:10 | 2988.03 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.11 | 31-MAY-13:00 | 184.53 | 03-MAY-03:00 |
June | 26988.77 | 01-JUN-00:10 | 2988.03 | 01-JUN-19:10 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 63.26 | 11-JUN-15:00 | 145.41 | 03-JUN-04:00 |
July | 26988.77 | 01-JUL-00:10 | 2988.03 | 03-JUL-19:30 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.43 | 26-JUL-15:40 | 106.38 | 23-JUL-04:00 |
August | 26988.77 | 01-AUG-00:10 | 2988.03 | 01-AUG-19:30 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.20 | 04-AUG-15:00 | 119.78 | 07-AUG-06:00 |
September | 26988.77 | 01-SEP-00:10 | 2988.03 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.53 | 07-SEP-14:00 | 198.05 | 30-SEP-01:00 |
October | 26988.77 | 01-OCT-23:10 | 2988.03 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 218.64 | 23-OCT-06:00 |
November | 26988.77 | 01-NOV-00:10 | 2988.03 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 415.28 | 26-NOV-07:00 |
December | 26988.77 | 01-DEC-00:10 | 2988.03 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 398.29 | 08-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.38 | |||||
Maximum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 67.20 | 471.22 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 1060.81 | 02-JAN-20:10 | 14912.86 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 368.23 | 05-JAN-21:17 |
February | 2401.70 | 01-FEB-00:10 | 1060.81 | 01-FEB-20:10 | 14912.86 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 385.10 | 02-FEB-21:00 |
March | 2401.70 | 01-MAR-00:10 | 1060.81 | 01-MAR-20:10 | 14912.86 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 299.20 | 06-MAR-00:03 |
April | 2401.70 | 01-APR-00:10 | 1060.81 | 03-APR-19:10 | 14912.86 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 36.66 | 15-APR-15:40 | 225.65 | 03-APR-06:00 |
May | 2401.70 | 01-MAY-00:10 | 1060.81 | 01-MAY-19:10 | 14912.86 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 36.86 | 31-MAY-13:00 | 159.18 | 03-MAY-05:10 |
June | 2401.70 | 01-JUN-00:10 | 1060.81 | 01-JUN-19:10 | 14912.86 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 56.69 | 11-JUN-15:00 | 129.51 | 01-JUN-05:00 |
July | 2401.70 | 01-JUL-00:10 | 1060.81 | 03-JUL-19:10 | 14912.86 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 37.17 | 26-JUL-15:40 | 95.13 | 24-JUL-05:00 |
August | 2401.70 | 01-AUG-00:10 | 1060.81 | 01-AUG-19:10 | 14912.86 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 60.22 | 04-AUG-15:00 | 107.21 | 07-AUG-06:00 |
September | 2401.70 | 01-SEP-00:10 | 1060.81 | 01-SEP-19:10 | 14912.86 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 50.66 | 07-SEP-14:00 | 170.52 | 30-SEP-01:00 |
October | 2401.70 | 01-OCT-23:10 | 1060.81 | 02-OCT-19:10 | 14912.86 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 195.70 | 23-OCT-06:00 |
November | 2401.70 | 01-NOV-00:10 | 1060.81 | 01-NOV-19:10 | 14912.86 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 363.84 | 25-NOV-21:07 |
December | 2401.70 | 01-DEC-00:10 | 1060.81 | 01-DEC-20:10 | 14912.86 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 356.58 | 09-DEC-08:04 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2401.70 | 1060.81 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 0.00 | 95.13 | ||||||
Maximum of Months | 2401.70 | 1060.81 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 60.22 | 385.10 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2395.44 | 02-JAN-00:10 | 1976.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 367.13 | 31-JAN-04:00 |
February | 2395.44 | 01-FEB-00:10 | 1976.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 405.56 | 02-FEB-06:00 |
March | 2395.44 | 01-MAR-00:10 | 1976.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 279.97 | 06-MAR-01:00 |
April | 2395.44 | 01-APR-00:10 | 1976.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.67 | 15-APR-17:00 | 199.76 | 03-APR-06:00 |
May | 2395.44 | 01-MAY-00:10 | 1976.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.01 | 31-MAY-13:00 | 141.41 | 03-MAY-03:00 |
June | 2395.44 | 01-JUN-00:10 | 1976.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.42 | 11-JUN-15:00 | 118.85 | 01-JUN-05:00 |
July | 2395.44 | 01-JUL-00:10 | 1976.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.28 | 26-JUL-15:00 | 84.66 | 24-JUL-03:00 |
August | 2395.44 | 01-AUG-00:10 | 1976.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.87 | 04-AUG-15:00 | 94.81 | 07-AUG-04:00 |
September | 2395.44 | 01-SEP-00:10 | 1976.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.52 | 07-SEP-14:00 | 152.91 | 30-SEP-01:00 |
October | 2395.44 | 01-OCT-23:10 | 1976.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.88 | 20-OCT-15:00 | 170.64 | 23-OCT-06:00 |
November | 2395.44 | 01-NOV-00:10 | 1976.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 357.58 | 26-NOV-07:00 |
December | 2395.44 | 01-DEC-00:10 | 1976.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 329.06 | 10-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.66 | ||||
Maximum of Months | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.87 | 405.56 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 35047.67 | 19-JAN-01:51 | 115018.92 | 21983.85 | 25348.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 31160.31 | 02-FEB-06:02 | 44729.58 | 29312.09 | 25348.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 12855.39 | 19-MAR-10:33 | 11501.89 | 13190.31 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 13228.70 | 16-APR-10:33 | 11501.89 | 13190.31 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 13800.02 | 29-MAY-10:33 | 11501.89 | 13190.31 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 14804.13 | 25-JUN-10:33 | 11501.89 | 13190.31 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 15598.80 | 23-JUL-10:33 | 11501.89 | 13190.31 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 18595.59 | 25-AUG-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 20645.29 | 13-SEP-20:55 | 20447.81 | 23449.32 | 18251.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 21112.48 | 31-OCT-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 36862.02 | 26-NOV-07:07 | 26837.75 | 17587.25 | 15209.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 18887.95 | 07-DEC-22:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 12855.39 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 36862.02 | 115018.92 | 29312.09 | 25348.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2274.24 | 12-JAN-12:30 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.18 |
February | 3066.98 | 08-FEB-13:30 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.64 |
March | 2683.11 | 24-MAR-13:10 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.25 |
April | 3747.32 | 15-APR-13:30 | 389.84 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 23.79 | 0.00 |
May | 2793.00 | 06-MAY-13:00 | 389.84 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.05 |
June | 3128.43 | 30-JUN-13:00 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 26.81 | 0.00 |
July | 3295.68 | 30-JUL-12:00 | 389.84 | 199.20 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 13.48 | 0.00 |
August | 3627.72 | 29-AUG-13:30 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.04 |
September | 4596.05 | 07-SEP-13:00 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 37.98 | 0.00 |
October | 4250.76 | 20-OCT-12:50 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.73 |
November | 4046.11 | 04-NOV-12:50 | 389.84 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.43 |
December | 3196.41 | 03-DEC-13:00 | 389.84 | 199.20 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.78 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2274.24 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4596.05 | 389.84 | 199.20 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 37.98 | 119.18 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1779.69 | 05-JAN-21:23 | 3611.52 | 1845.37 | 2256.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.11 |
February | 1606.15 | 02-FEB-06:00 | 1354.32 | 153.78 | 250.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.60 |
March | 1251.07 | 24-MAR-20:00 | 1053.36 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.73 |
April | 1701.62 | 18-APR-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.49 |
May | 1826.98 | 31-MAY-20:55 | 2407.68 | 1230.25 | 1504.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.51 |
June | 2026.55 | 30-JUN-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.54 |
July | 1994.16 | 03-JUL-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.77 | 0.00 |
August | 1943.08 | 02-AUG-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.77 | 0.00 |
September | 2024.62 | 07-SEP-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.36 |
October | 1482.53 | 20-OCT-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.17 |
November | 2051.70 | 25-NOV-21:12 | 5266.80 | 2691.17 | 3342.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.24 |
December | 1091.39 | 05-DEC-21:00 | 1053.36 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.76 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1091.39 | 1053.36 | 153.78 | 250.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2051.70 | 5266.80 | 2691.17 | 3342.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.77 | 125.60 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 722.82 | 13-JAN-21:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.74 |
February | 754.13 | 24-FEB-21:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.82 |
March | 853.20 | 20-MAR-10:33 | 190.94 | 570.15 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.65 |
April | 1086.87 | 16-APR-10:33 | 286.42 | 684.18 | 1060.35 | 0.00 | 0.00 | 0.00 | 0.00 | 2.29 | 0.00 |
May | 1127.03 | 31-MAY-10:33 | 190.94 | 570.15 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 22.21 | 0.00 |
June | 1563.76 | 30-JUN-19:53 | 1336.61 | 4105.06 | 5036.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.25 |
July | 1494.54 | 03-JUL-21:00 | 254.59 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 1.82 | 0.00 |
August | 1534.75 | 04-AUG-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.66 |
September | 1326.14 | 11-SEP-21:00 | 254.59 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.44 |
October | 908.42 | 11-OCT-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.27 |
November | 906.07 | 04-NOV-10:33 | 286.42 | 570.15 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.36 |
December | 702.98 | 05-DEC-21:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.49 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 702.98 | 190.94 | 570.15 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1563.76 | 1336.61 | 4105.06 | 5036.68 | 0.00 | 0.00 | 0.00 | 0.00 | 22.21 | 143.49 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 369.64 | 13-JAN-22:00 | 195.84 | 223.85 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.11 |
February | 416.74 | 24-FEB-21:00 | 171.36 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.80 |
March | 492.97 | 20-MAR-10:33 | 146.88 | 209.86 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.98 |
April | 640.33 | 16-APR-10:33 | 220.32 | 251.83 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 1.69 | 0.00 |
May | 664.76 | 31-MAY-10:33 | 146.88 | 209.86 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 13.16 | 0.00 |
June | 708.82 | 30-JUN-10:33 | 146.88 | 209.86 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 0.00 |
July | 703.48 | 02-JUL-10:33 | 220.32 | 251.83 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 11.25 | 0.00 |
August | 698.48 | 04-AUG-10:33 | 146.88 | 209.86 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 14.80 | 0.00 |
September | 686.54 | 09-SEP-10:33 | 220.32 | 209.86 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 6.11 | 0.00 |
October | 522.22 | 20-OCT-10:33 | 146.88 | 209.86 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.80 |
November | 518.75 | 04-NOV-10:33 | 220.32 | 209.86 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.11 |
December | 304.04 | 03-DEC-21:00 | 146.88 | 223.85 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.37 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 304.04 | 146.88 | 209.86 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 708.82 | 220.32 | 251.84 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 14.80 | 64.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 39792.68 | 05-JAN-21:42 | 4032.00 | 1444.82 | 21660.63 | 188178.52 | 0.00 | 0.00 | 0.00 | 0.00 | 350.20 |
February | 36982.67 | 24-FEB-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 147.14 |
March | 37414.01 | 28-MAR-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 79.87 |
April | 38319.16 | 18-APR-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 36.31 |
May | 38625.06 | 31-MAY-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 2.47 | 0.00 |
June | 38807.15 | 26-JUN-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 16.95 | 0.00 |
July | 38650.47 | 03-JUL-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 16.74 | 0.00 |
August | 38697.38 | 03-AUG-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 6.19 | 0.00 |
September | 38659.61 | 07-SEP-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.65 |
October | 37840.34 | 20-OCT-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 57.78 |
November | 38969.89 | 25-NOV-21:23 | 2822.40 | 1011.37 | 15403.12 | 133815.84 | 0.00 | 0.00 | 0.00 | 0.00 | 340.16 |
December | 36381.18 | 01-DEC-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 201.32 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 36381.18 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 39792.68 | 4032.00 | 1444.82 | 21660.63 | 188178.52 | 0.00 | 0.00 | 0.00 | 16.95 | 350.20 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9420.60 | 12-JAN-12:30 | 3415.20 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 263.47 |
February | 11851.00 | 08-FEB-13:30 | 3415.20 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 255.63 |
March | 10675.54 | 25-MAR-13:40 | 5122.80 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.76 |
April | 13907.80 | 15-APR-13:20 | 5122.80 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 50.64 | 0.00 |
May | 11122.90 | 06-MAY-13:00 | 5122.80 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.99 |
June | 11465.37 | 26-JUN-21:10 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 15.69 | 0.00 |
July | 12087.11 | 30-JUL-12:00 | 5122.80 | 124.78 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 29.81 | 0.00 |
August | 12623.29 | 29-AUG-15:03 | 51228.00 | 623.89 | 2133.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.26 |
September | 15040.81 | 07-SEP-12:50 | 3415.20 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 82.00 | 0.00 |
October | 14997.40 | 20-OCT-12:50 | 3415.20 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.92 |
November | 15207.84 | 04-NOV-12:50 | 5122.80 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.32 |
December | 12828.18 | 03-DEC-13:00 | 5122.80 | 124.78 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 218.34 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9420.60 | 3415.20 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15207.84 | 51228.00 | 1134.35 | 2133.76 | 0.00 | 0.00 | 0.00 | 0.00 | 82.00 | 263.47 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 64021.25 | 19-JAN-01:51 | 456229.80 | 15841.33 | 26392.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1695.06 |
February | 39841.49 | 02-FEB-06:00 | 45622.98 | 2112.18 | 3167.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2066.34 |
March | 28241.91 | 24-MAR-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 735.16 |
April | 36385.33 | 18-APR-21:10 | 91245.96 | 12673.07 | 14779.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 249.95 |
May | 37603.10 | 31-MAY-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.15 |
June | 40046.54 | 26-JUN-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 44.76 | 0.00 |
July | 39123.77 | 03-JUL-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 0.00 |
August | 39296.86 | 02-AUG-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 10.01 | 0.00 |
September | 40762.87 | 07-SEP-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.34 |
October | 34734.24 | 20-OCT-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 329.99 |
November | 45541.67 | 25-NOV-21:12 | 177422.70 | 36963.11 | 42228.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1717.42 |
December | 26616.57 | 03-DEC-11:33 | 45622.98 | 8174.13 | 12668.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 620.78 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 26616.57 | 45622.98 | 2112.18 | 3167.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 64021.25 | 456229.80 | 36963.11 | 42228.25 | 0.00 | 0.00 | 0.00 | 0.00 | 44.76 | 2066.34 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2993.93 | 02-JAN-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.54 |
February | 3970.14 | 17-FEB-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.87 |
March | 4073.16 | 22-MAR-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.80 |
April | 4107.46 | 26-APR-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.12 |
May | 4130.49 | 21-MAY-18:01 | 819.00 | 1245.18 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.47 |
June | 3618.46 | 14-JUN-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 2.56 | 0.00 |
July | 3617.84 | 11-JUL-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.72 |
August | 3562.03 | 30-AUG-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.25 |
September | 4061.53 | 20-SEP-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.05 |
October | 3557.48 | 21-OCT-15:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.54 |
November | 4013.11 | 12-NOV-16:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.53 |
December | 3944.09 | 01-DEC-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.79 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2993.93 | 378.00 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4130.49 | 970.20 | 1245.18 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 2.56 | 101.54 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 575.59 | 13-JAN-16:03 | 583.20 | 298.81 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.40 |
February | 2785.27 | 25-FEB-16:01 | 378.00 | 410.86 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.77 |
March | 3789.01 | 21-MAR-18:01 | 970.20 | 1108.08 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.92 |
April | 4100.65 | 29-APR-18:41 | 1053.00 | 1600.75 | 1090.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.46 |
May | 4578.40 | 20-MAY-18:41 | 1170.00 | 1778.61 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.93 |
June | 4079.36 | 16-JUN-16:32 | 583.20 | 298.81 | 758.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.63 |
July | 3981.05 | 23-JUL-21:51 | 1386.00 | 1511.82 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.73 |
August | 4049.14 | 11-AUG-18:11 | 1386.00 | 1582.97 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 |
September | 3751.27 | 12-SEP-21:11 | 1800.00 | 1191.67 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.28 |
October | 3699.11 | 10-OCT-16:51 | 972.00 | 498.01 | 1264.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.43 |
November | 3436.56 | 03-NOV-15:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.34 |
December | 493.37 | 14-DEC-16:04 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 493.37 | 378.00 | 298.81 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | |
Maximum of Months | 4578.40 | 1800.00 | 1778.61 | 1264.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 214.98 | 30-JAN-15:05 | 0.00 | 62.60 | 61.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.02 |
February | 252.83 | 02-FEB-15:05 | 0.00 | 62.60 | 61.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.33 |
March | 480.05 | 24-MAR-13:00 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.20 |
April | 627.33 | 15-APR-13:30 | 0.00 | 36.89 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 1.70 | 0.00 |
May | 466.90 | 06-MAY-13:00 | 0.00 | 36.89 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 |
June | 473.39 | 26-JUN-12:50 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 3.47 | 0.00 |
July | 516.60 | 30-JUL-13:30 | 0.00 | 36.89 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.19 | 0.00 |
August | 586.56 | 29-AUG-13:30 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.55 |
September | 721.97 | 07-SEP-13:00 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 3.98 | 0.00 |
October | 720.77 | 20-OCT-12:40 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.22 |
November | 696.01 | 04-NOV-12:30 | 0.00 | 36.89 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.47 |
December | 138.99 | 07-DEC-15:20 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.46 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 138.99 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 721.97 | 0.00 | 62.60 | 61.92 | 0.00 | 0.00 | 0.00 | 0.00 | 3.98 | 48.33 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 384.50 | 01-JAN-09:02 | 324.00 | 375.72 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.85 |
February | 886.75 | 26-FEB-09:02 | 324.00 | 375.72 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.67 |
March | 1133.40 | 24-MAR-18:01 | 970.20 | 696.66 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.56 |
April | 1192.60 | 30-APR-18:01 | 819.00 | 782.76 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.16 |
May | 1233.12 | 06-MAY-19:31 | 1170.00 | 1118.23 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.32 |
June | 1155.30 | 23-JUN-21:51 | 1800.00 | 749.21 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.77 |
July | 1128.15 | 18-JUL-21:51 | 1800.00 | 749.21 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 |
August | 1173.36 | 11-AUG-18:11 | 1386.00 | 995.22 | 1187.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 | 0.00 |
September | 1186.51 | 19-SEP-18:01 | 970.20 | 696.66 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.39 |
October | 1119.93 | 19-OCT-18:01 | 970.20 | 696.66 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.34 |
November | 1102.01 | 04-NOV-18:01 | 819.00 | 782.76 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.12 |
December | 484.41 | 03-DEC-09:02 | 324.00 | 375.72 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.17 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 384.50 | 324.00 | 375.72 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1233.12 | 1800.00 | 1118.23 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 | 21.85 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1103.50 | 12-JAN-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.94 |
February | 3395.94 | 21-FEB-09:02 | 216.00 | 469.61 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.95 |
March | 3697.13 | 22-MAR-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.52 |
April | 3717.97 | 26-APR-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.75 |
May | 3712.35 | 06-MAY-18:01 | 819.00 | 1245.18 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.07 |
June | 3398.50 | 25-JUN-08:61 | 378.00 | 697.30 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 4.26 | 0.00 |
July | 3436.59 | 17-JUL-08:61 | 252.00 | 547.88 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
August | 3444.11 | 01-AUG-08:61 | 252.00 | 547.88 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.95 | 0.00 |
September | 3709.38 | 20-SEP-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.97 |
October | 3289.92 | 21-OCT-15:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.77 |
November | 3308.58 | 12-NOV-09:02 | 324.00 | 597.68 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.78 |
December | 2505.83 | 03-DEC-09:02 | 324.00 | 597.68 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.34 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1103.50 | 216.00 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3717.97 | 970.20 | 1245.18 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 4.26 | 87.78 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 626.27 | 13-JAN-09:04 | 252.00 | 547.81 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.47 |
February | 2478.37 | 24-FEB-09:01 | 252.00 | 547.81 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.51 |
March | 3072.08 | 19-MAR-15:01 | 378.00 | 410.86 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.51 |
April | 3724.03 | 18-APR-08:51 | 360.00 | 782.59 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.38 |
May | 3822.71 | 31-MAY-08:32 | 216.00 | 469.55 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.68 |
June | 4077.02 | 09-JUN-08:32 | 216.00 | 469.55 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.47 |
July | 4004.78 | 13-JUL-08:32 | 216.00 | 469.55 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.96 |
August | 3885.87 | 11-AUG-08:51 | 360.00 | 782.59 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.80 |
September | 3898.91 | 06-SEP-08:51 | 360.00 | 782.59 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.37 |
October | 3118.95 | 21-OCT-15:01 | 378.00 | 410.86 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 |
November | 2629.28 | 04-NOV-08:62 | 324.00 | 597.61 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.01 |
December | 724.81 | 05-DEC-09:03 | 252.00 | 547.81 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 626.27 | 216.00 | 410.86 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | |
Maximum of Months | 4077.02 | 378.00 | 782.59 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1824.73 | 31-JAN-04:00 | 2263.36 | 207.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.12 |
February | 2330.33 | 02-FEB-06:00 | 2263.36 | 414.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 242.16 |
March | 1827.79 | 20-MAR-10:33 | 1508.90 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.09 |
April | 2366.76 | 18-APR-10:33 | 1508.90 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.40 | 0.00 |
May | 2419.98 | 31-MAY-10:33 | 1508.90 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.68 | 0.00 |
June | 2598.68 | 30-JUN-10:33 | 1508.90 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.21 | 0.00 |
July | 2607.16 | 02-JUL-10:33 | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.48 | 0.00 |
August | 2538.21 | 02-AUG-10:33 | 1508.90 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.54 | 0.00 |
September | 2565.08 | 09-SEP-10:33 | 2263.36 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 0.00 |
October | 1936.91 | 20-OCT-10:33 | 1508.90 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.20 |
November | 1903.31 | 04-NOV-10:33 | 2263.36 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.98 |
December | 1641.27 | 03-DEC-11:33 | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.80 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 1641.27 | 1508.90 | 207.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2607.16 | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.68 | 242.16 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2768.47 | 12-JAN-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.86 |
February | 3955.57 | 17-FEB-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.20 |
March | 4210.85 | 22-MAR-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.82 |
April | 4272.92 | 26-APR-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.34 |
May | 4297.16 | 21-MAY-18:01 | 819.00 | 1245.18 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.70 |
June | 3725.78 | 17-JUN-18:02 | 702.00 | 1067.29 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 3.59 | 0.00 |
July | 3726.51 | 21-JUL-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.14 |
August | 3767.67 | 25-AUG-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
September | 4213.95 | 20-SEP-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.19 |
October | 3607.78 | 21-OCT-15:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 |
November | 4160.25 | 12-NOV-16:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.65 |
December | 4076.13 | 01-DEC-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.77 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2768.47 | 378.00 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4297.16 | 970.20 | 1245.18 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 3.59 | 92.20 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 814.39 | 12-JAN-16:03 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.09 |
February | 2831.84 | 24-FEB-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.65 |
March | 3923.34 | 21-MAR-18:01 | 970.20 | 1108.08 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.10 |
April | 4334.42 | 29-APR-18:41 | 1053.00 | 1600.75 | 1090.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.58 |
May | 4808.36 | 20-MAY-18:41 | 1170.00 | 1778.61 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.77 |
June | 4233.83 | 16-JUN-16:32 | 583.20 | 298.81 | 758.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.30 |
July | 4289.07 | 23-JUL-21:51 | 1386.00 | 1511.82 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.05 |
August | 4188.44 | 11-AUG-18:11 | 1386.00 | 1582.97 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.55 |
September | 4619.25 | 19-SEP-17:41 | 777.60 | 953.34 | 1011.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.81 |
October | 3878.60 | 10-OCT-16:51 | 972.00 | 498.01 | 1264.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.46 |
November | 3496.22 | 03-NOV-15:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.40 |
December | 603.61 | 05-DEC-16:04 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.23 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 603.61 | 583.20 | 298.81 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.55 | |
Maximum of Months | 4808.36 | 1386.00 | 1778.61 | 1264.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.23 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2395.19 | 30-JAN-16:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.47 |
February | 2305.45 | 01-FEB-16:02 | 583.20 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.63 |
March | 2241.79 | 21-MAR-15:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.08 |
April | 2239.81 | 26-APR-15:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.79 |
May | 2187.18 | 21-MAY-18:01 | 819.00 | 782.76 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.18 |
June | 1960.12 | 03-JUN-15:01 | 378.00 | 258.31 | 379.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.57 |
July | 1952.03 | 07-JUL-18:01 | 970.20 | 696.66 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 0.00 |
August | 1966.40 | 11-AUG-18:02 | 831.60 | 597.13 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2.70 | 0.00 |
September | 2207.42 | 20-SEP-18:01 | 970.20 | 696.66 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.91 |
October | 1945.21 | 02-OCT-15:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.88 |
November | 2194.75 | 21-NOV-16:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.56 |
December | 2212.22 | 05-DEC-16:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.66 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1945.21 | 378.00 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2395.19 | 970.20 | 782.76 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 2.70 | 86.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 29475.81 | 19-JAN-01:51 | 269887.68 | 4980.05 | 22493.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 391.37 |
February | 19323.08 | 02-FEB-06:00 | 26988.77 | 664.01 | 2249.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 472.66 |
March | 18530.44 | 28-MAR-22:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.54 |
April | 21122.21 | 18-APR-21:10 | 53977.54 | 3984.04 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.82 |
May | 22269.35 | 31-MAY-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.48 |
June | 23000.53 | 26-JUN-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 7.90 | 0.00 |
July | 22726.25 | 03-JUL-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.49 |
August | 22568.52 | 03-AUG-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.92 | 0.00 |
September | 22011.20 | 07-SEP-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.01 |
October | 19273.72 | 20-OCT-22:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.78 |
November | 24737.19 | 25-NOV-21:23 | 83965.06 | 9296.09 | 26991.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 384.78 |
December | 16062.25 | 04-DEC-23:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.41 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 16062.25 | 26988.77 | 664.01 | 2249.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29475.81 | 269887.68 | 9296.09 | 26991.61 | 0.00 | 0.00 | 0.00 | 0.00 | 7.90 | 472.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 31230.89 | 19-JAN-01:51 | 269887.68 | 4980.05 | 22493.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 393.43 |
February | 20261.92 | 02-FEB-06:00 | 26988.77 | 664.01 | 2249.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 471.22 |
March | 20460.10 | 28-MAR-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.35 |
April | 22496.86 | 18-APR-21:10 | 53977.54 | 3984.04 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.82 |
May | 23573.11 | 31-MAY-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.38 |
June | 24221.16 | 26-JUN-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 7.88 | 0.00 |
July | 23930.88 | 03-JUL-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.51 |
August | 23802.00 | 03-AUG-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.89 | 0.00 |
September | 23249.59 | 07-SEP-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.70 |
October | 21015.21 | 02-OCT-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.55 |
November | 28068.09 | 25-NOV-21:23 | 83965.06 | 9296.09 | 26991.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 386.40 |
December | 18055.14 | 04-DEC-23:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.42 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 18055.14 | 26988.77 | 664.01 | 2249.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31230.89 | 269887.68 | 9296.09 | 26991.61 | 0.00 | 0.00 | 0.00 | 0.00 | 7.88 | 471.22 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 27418.77 | 29-JAN-19:42 | 6404.54 | 3300.29 | 59651.42 | 59980.88 | 0.00 | 0.00 | 0.00 | 0.00 | 350.62 |
February | 27558.49 | 24-FEB-11:33 | 1601.14 | 884.01 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 123.05 |
March | 28918.48 | 19-MAR-10:50 | 800.57 | 353.60 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 64.59 |
April | 30814.17 | 15-APR-10:33 | 2401.70 | 884.01 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 3.64 | 0.00 |
May | 31298.76 | 31-MAY-10:37 | 1601.14 | 884.01 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 23.98 | 0.00 |
June | 31528.78 | 11-JUN-10:40 | 2401.70 | 1060.81 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 34.07 | 0.00 |
July | 31587.03 | 29-JUL-10:40 | 2401.70 | 884.01 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 10.84 | 0.00 |
August | 31279.08 | 01-AUG-10:33 | 1601.14 | 884.01 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 17.42 | 0.00 |
September | 31373.57 | 08-SEP-10:40 | 1601.14 | 884.01 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 26.43 | 0.00 |
October | 29099.70 | 01-OCT-10:33 | 2401.70 | 1060.81 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 52.91 |
November | 28863.72 | 25-NOV-21:23 | 7471.97 | 3300.29 | 59651.42 | 44985.66 | 0.00 | 0.00 | 0.00 | 0.00 | 348.12 |
December | 26861.17 | 03-DEC-11:33 | 2401.70 | 1060.81 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 131.80 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 26861.17 | 800.57 | 353.60 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31587.03 | 7471.97 | 3300.29 | 59651.42 | 59980.88 | 0.00 | 0.00 | 0.00 | 34.07 | 350.62 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2823.92 | 13-JAN-11:35 | 1064.64 | 1097.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.39 |
February | 3433.00 | 24-FEB-11:33 | 1596.96 | 1646.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.66 |
March | 3721.06 | 20-MAR-10:33 | 1596.96 | 1646.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.44 |
April | 4839.94 | 18-APR-10:33 | 1596.96 | 1646.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.14 | 0.00 |
May | 5115.48 | 31-MAY-10:33 | 1596.96 | 1646.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.22 | 0.00 |
June | 6527.02 | 30-JUN-14:10 | 798.48 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.64 | 0.00 |
July | 6282.57 | 05-JUL-14:10 | 798.48 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.82 | 0.00 |
August | 6700.92 | 04-AUG-15:03 | 7984.80 | 3293.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.86 | 0.00 |
September | 6614.47 | 07-SEP-13:30 | 532.32 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.03 | 0.00 |
October | 3926.85 | 20-OCT-10:33 | 1596.96 | 1646.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.67 |
November | 3807.71 | 04-NOV-10:33 | 2395.44 | 1646.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.43 |
December | 3283.60 | 03-DEC-11:33 | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.60 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 2823.92 | 532.32 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6700.92 | 7984.80 | 3293.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.86 | 118.39 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.383036E+12 | 227920.45 | 20-JAN-07:10 | 0.102344E+13 | 1041321.32 | 30-JAN-21:00 |
February | 0.343427E+12 | 227472.55 | 03-FEB-07:30 | 0.804801E+12 | 1075624.60 | 02-FEB-21:30 |
March | 0.376756E+12 | 226443.63 | 24-MAR-18:30 | 0.609906E+12 | 561594.80 | 05-MAR-19:10 |
April | 0.379454E+12 | 308921.91 | 16-APR-18:49 | 0.505780E+12 | 563000.93 | 25-APR-17:40 |
May | 0.409201E+12 | 319575.15 | 31-MAY-18:10 | 0.467798E+12 | 525199.58 | 01-MAY-17:00 |
June | 0.474005E+12 | 367354.39 | 26-JUN-18:10 | 0.417294E+12 | 468349.32 | 01-JUN-17:00 |
July | 0.529719E+12 | 402842.58 | 26-JUL-18:30 | 0.385617E+12 | 339454.83 | 03-JUL-17:30 |
August | 0.511927E+12 | 379688.59 | 03-AUG-18:10 | 0.389677E+12 | 365234.11 | 06-AUG-20:00 |
September | 0.422434E+12 | 330500.99 | 07-SEP-18:40 | 0.429410E+12 | 520151.13 | 30-SEP-17:00 |
October | 0.383577E+12 | 232284.12 | 20-OCT-18:10 | 0.521740E+12 | 540427.56 | 18-OCT-17:19 |
November | 0.367498E+12 | 225826.68 | 02-NOV-06:49 | 0.626729E+12 | 959042.32 | 25-NOV-21:00 |
December | 0.382425E+12 | 224378.84 | 12-DEC-07:30 | 0.774176E+12 | 669069.69 | 11-DEC-19:19 |
Annual Sum or Average | 0.496346E+13 | 0.695637E+13 | ||||
Minimum of Months | 0.343427E+12 | 224378.84 | 0.385617E+12 | 339454.83 | ||
Maximum of Months | 0.529719E+12 | 402842.58 | 0.102344E+13 | 1075624.60 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.671532E+11 | 0.204621E+11 | 0.140828E+12 | 0.691146E+11 | 0.428775E+11 | 0.345787E+10 | 0.00 | 0.288390E+09 | 0.00 | 0.00 | 0.257713E+11 | 0.805023E+10 | 0.00 |
February | 0.604321E+11 | 0.170493E+11 | 0.127191E+12 | 0.624261E+11 | 0.375491E+11 | 0.321738E+10 | 0.00 | 0.616991E+09 | 0.00 | 0.00 | 0.231561E+11 | 0.727552E+10 | 0.00 |
March | 0.664655E+11 | 0.168938E+11 | 0.140882E+12 | 0.691168E+11 | 0.399860E+11 | 0.478502E+10 | 0.00 | 0.392172E+10 | 0.00 | 0.00 | 0.214741E+11 | 0.804631E+10 | 0.00 |
April | 0.639806E+11 | 0.143175E+11 | 0.136245E+12 | 0.668843E+11 | 0.400924E+11 | 0.635348E+10 | 0.00 | 0.223999E+11 | 0.00 | 0.00 | 0.163348E+11 | 0.779743E+10 | 0.00 |
May | 0.656312E+11 | 0.130220E+11 | 0.140860E+12 | 0.691149E+11 | 0.438506E+11 | 0.940909E+10 | 0.00 | 0.480087E+11 | 0.00 | 0.00 | 0.596095E+10 | 0.804728E+10 | 0.00 |
June | 0.633487E+11 | 0.117117E+11 | 0.136336E+12 | 0.668863E+11 | 0.461083E+11 | 0.928797E+10 | 0.00 | 0.119703E+12 | 0.00 | 0.00 | 0.766347E+10 | 0.778868E+10 | 0.00 |
July | 0.655135E+11 | 0.124816E+11 | 0.140770E+12 | 0.691124E+11 | 0.487208E+11 | 0.968265E+10 | 0.00 | 0.162240E+12 | 0.00 | 0.00 | 0.780550E+10 | 0.805557E+10 | 0.00 |
August | 0.658085E+11 | 0.140140E+11 | 0.140892E+12 | 0.691164E+11 | 0.485321E+11 | 0.964178E+10 | 0.00 | 0.142942E+12 | 0.00 | 0.00 | 0.757813E+10 | 0.804716E+10 | 0.00 |
September | 0.642023E+11 | 0.154428E+11 | 0.136256E+12 | 0.668845E+11 | 0.447032E+11 | 0.890460E+10 | 0.00 | 0.648273E+11 | 0.00 | 0.00 | 0.829465E+10 | 0.779861E+10 | 0.00 |
October | 0.667746E+11 | 0.180561E+11 | 0.140818E+12 | 0.691143E+11 | 0.418631E+11 | 0.761324E+10 | 0.00 | 0.120450E+11 | 0.00 | 0.00 | 0.140282E+11 | 0.804608E+10 | 0.00 |
November | 0.649238E+11 | 0.192850E+11 | 0.136330E+12 | 0.668858E+11 | 0.399323E+11 | 0.439169E+10 | 0.00 | 0.321870E+10 | 0.00 | 0.00 | 0.197473E+11 | 0.778108E+10 | 0.00 |
December | 0.672967E+11 | 0.209581E+11 | 0.140770E+12 | 0.691135E+11 | 0.417172E+11 | 0.315685E+10 | 0.00 | 0.457222E+09 | 0.00 | 0.00 | 0.257511E+11 | 0.805644E+10 | 0.00 |
Annual Sum or Average | 0.781531E+12 | 0.193694E+12 | 0.165818E+13 | 0.813770E+12 | 0.515933E+12 | 0.799016E+11 | 0.00 | 0.580668E+12 | 0.00 | 0.00 | 0.183566E+12 | 0.947904E+11 | 0.00 |
Minimum of Months | 0.604321E+11 | 0.117117E+11 | 0.127191E+12 | 0.624261E+11 | 0.375491E+11 | 0.315685E+10 | 0.00 | 0.288390E+09 | 0.00 | 0.00 | 0.596095E+10 | 0.727552E+10 | 0.00 |
Maximum of Months | 0.672967E+11 | 0.209581E+11 | 0.140892E+12 | 0.691168E+11 | 0.487208E+11 | 0.968265E+10 | 0.00 | 0.162240E+12 | 0.00 | 0.00 | 0.257713E+11 | 0.805644E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.151918E+12 | 0.00 | 0.607428E+12 | 0.00 | 0.264098E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.426933E+12 | 0.00 | 0.240664E+12 | 0.00 | 0.00 |
March | 0.152024E+12 | 0.00 | 0.192532E+12 | 0.00 | 0.265350E+12 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.106223E+12 | 0.00 | 0.252601E+12 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.648291E+11 | 0.00 | 0.250990E+12 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 0.400255E+11 | 0.00 | 0.230154E+12 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 0.638025E+10 | 0.00 | 0.227416E+12 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 0.148733E+11 | 0.00 | 0.222765E+12 | 0.00 | 0.00 |
September | 0.146971E+12 | 0.00 | 0.646889E+11 | 0.00 | 0.217750E+12 | 0.00 | 0.00 |
October | 0.151903E+12 | 0.00 | 0.136279E+12 | 0.00 | 0.233557E+12 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.241482E+12 | 0.00 | 0.238156E+12 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.364157E+12 | 0.00 | 0.258198E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178884E+13 | 0.00 | 0.226583E+13 | 0.00 | 0.290170E+13 | 0.00 | 0.00 |
Minimum of Months | 0.137204E+12 | 0.00 | 0.638025E+10 | 0.00 | 0.217750E+12 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.607428E+12 | 0.00 | 0.265350E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 64632.59 | 02-JAN-20:10 | 12338.45 | 01-JAN-00:10 | 89171.45 | 02-JAN-07:10 | 49607.07 | 02-JAN-07:19 | 25395.16 | 19-JAN-19:19 | 4999.18 | 30-JAN-16:30 | 0.00 | 01-JAN-00:10 |
February | 64632.59 | 01-FEB-20:10 | 12338.45 | 01-FEB-00:10 | 89171.45 | 01-FEB-07:10 | 49607.07 | 01-FEB-07:19 | 23461.02 | 05-FEB-19:10 | 4944.16 | 01-FEB-15:20 | 0.00 | 01-FEB-00:10 |
March | 64632.59 | 01-MAR-20:10 | 12338.45 | 01-MAR-00:10 | 89171.45 | 01-MAR-07:10 | 49607.07 | 13-MAR-06:19 | 22774.28 | 24-MAR-18:10 | 4325.05 | 05-MAR-17:49 | 0.00 | 01-MAR-00:10 |
April | 64632.59 | 03-APR-19:10 | 12338.45 | 01-APR-00:10 | 89171.45 | 03-APR-06:10 | 49606.97 | 14-APR-06:19 | 30378.13 | 18-APR-21:00 | 4221.84 | 08-APR-08:09 | 0.00 | 01-APR-00:10 |
May | 64632.59 | 01-MAY-19:10 | 12338.45 | 01-MAY-00:10 | 89171.45 | 01-MAY-06:10 | 49605.49 | 10-MAY-06:19 | 31721.62 | 31-MAY-21:00 | 4147.50 | 22-MAY-06:10 | 0.00 | 01-MAY-00:10 |
June | 64632.59 | 01-JUN-19:10 | 12338.45 | 01-JUN-00:10 | 89171.45 | 01-JUN-06:10 | 49605.88 | 13-JUN-06:19 | 33503.96 | 29-JUN-21:10 | 4335.52 | 26-JUN-18:19 | 0.00 | 01-JUN-00:10 |
July | 64632.59 | 03-JUL-19:30 | 12338.45 | 01-JUL-00:10 | 89171.45 | 03-JUL-06:10 | 49605.49 | 20-JUL-06:19 | 33029.73 | 27-JUL-21:00 | 4707.23 | 26-JUL-18:49 | 0.00 | 01-JUL-00:10 |
August | 64632.59 | 01-AUG-19:30 | 12338.45 | 01-AUG-00:10 | 89171.45 | 01-AUG-06:10 | 49605.70 | 23-AUG-06:19 | 34568.02 | 22-AUG-21:00 | 4557.06 | 03-AUG-21:00 | 0.00 | 01-AUG-00:10 |
September | 64632.59 | 01-SEP-19:10 | 12338.45 | 01-SEP-00:10 | 89171.45 | 01-SEP-06:10 | 49607.07 | 21-SEP-06:19 | 36043.43 | 07-SEP-21:00 | 4222.09 | 27-SEP-08:09 | 0.00 | 01-SEP-00:10 |
October | 64632.59 | 02-OCT-19:10 | 12338.45 | 01-OCT-00:10 | 89171.45 | 02-OCT-06:10 | 49607.07 | 02-OCT-06:19 | 30743.23 | 20-OCT-21:10 | 4258.32 | 05-OCT-08:09 | 0.00 | 01-OCT-00:10 |
November | 64632.59 | 01-NOV-19:10 | 12338.45 | 01-NOV-00:10 | 89171.45 | 01-NOV-06:10 | 49607.07 | 01-NOV-06:19 | 26190.98 | 03-NOV-21:10 | 4560.54 | 25-NOV-16:30 | 0.00 | 01-NOV-00:10 |
December | 64632.59 | 01-DEC-20:10 | 12338.45 | 01-DEC-00:10 | 89171.45 | 01-DEC-07:10 | 49607.07 | 01-DEC-07:19 | 26650.57 | 11-DEC-19:19 | 4465.18 | 10-DEC-10:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 64632.59 | 12338.45 | 89171.45 | 49605.49 | 22774.28 | 4147.50 | 0.00 | |||||||
Maximum of Months | 64632.59 | 12338.45 | 89171.45 | 49607.07 | 36043.43 | 4999.18 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 3674.32 | 12-JAN-16:10 | 0.00 | 0.00 | 9938.94 | 06-JAN-10:39 | 4764.18 | 31-JAN-07:10 | 0.00 |
February | 6933.42 | 24-FEB-16:10 | 0.00 | 0.00 | 9938.94 | 01-FEB-00:10 | 4772.05 | 02-FEB-07:10 | 0.00 |
March | 33539.87 | 25-MAR-15:09 | 0.00 | 0.00 | 9938.94 | 01-MAR-00:20 | 4751.12 | 07-MAR-07:49 | 0.00 |
April | 114931.43 | 18-APR-15:20 | 0.00 | 0.00 | 9938.94 | 01-APR-00:10 | 4751.12 | 20-APR-18:49 | 0.00 |
May | 113990.47 | 31-MAY-18:10 | 0.00 | 0.00 | 9938.94 | 01-MAY-00:00 | 4751.13 | 16-MAY-06:30 | 0.00 |
June | 170866.73 | 11-JUN-15:09 | 0.00 | 0.00 | 9938.94 | 11-JUN-08:00 | 4751.13 | 15-JUN-18:49 | 0.00 |
July | 196657.62 | 26-JUL-18:30 | 0.00 | 0.00 | 9938.94 | 03-JUL-08:00 | 4751.13 | 07-JUL-06:00 | 0.00 |
August | 206703.84 | 04-AUG-15:20 | 0.00 | 0.00 | 9938.94 | 05-AUG-08:00 | 4751.13 | 08-AUG-18:19 | 0.00 |
September | 136873.94 | 06-SEP-15:09 | 0.00 | 0.00 | 9938.94 | 07-SEP-08:00 | 4751.12 | 01-SEP-06:40 | 0.00 |
October | 71267.73 | 20-OCT-15:09 | 0.00 | 0.00 | 9938.94 | 01-OCT-00:10 | 4751.12 | 19-OCT-18:00 | 0.00 |
November | 25650.84 | 03-NOV-15:09 | 0.00 | 0.00 | 9938.94 | 01-NOV-00:10 | 4751.13 | 15-NOV-19:49 | 0.00 |
December | 3472.84 | 07-DEC-14:30 | 0.00 | 0.00 | 9938.94 | 01-DEC-00:20 | 4751.13 | 19-DEC-07:30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 3472.84 | 0.00 | 0.00 | 9938.94 | 4751.12 | 0.00 | |||
Maximum of Months | 206703.84 | 0.00 | 0.00 | 9938.94 | 4772.05 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 227920.45 | 20-JAN-07:10 | 36001.17 | 89171.45 | 12338.45 | 49600.84 | 21579.85 | 1744.68 | 0.00 | 0.00 | 0.00 |
February | 227472.55 | 03-FEB-07:30 | 36001.17 | 89171.45 | 12338.45 | 49607.07 | 21528.40 | 1731.60 | 0.00 | 0.00 | 0.00 |
March | 226443.63 | 24-MAR-18:30 | 57474.69 | 77573.37 | 12338.45 | 28169.20 | 21426.39 | 3414.44 | 0.00 | 9554.70 | 0.00 |
April | 308921.91 | 16-APR-18:49 | 54981.58 | 74651.16 | 12338.45 | 28110.46 | 22592.40 | 3840.30 | 0.00 | 96090.01 | 0.00 |
May | 319575.15 | 31-MAY-18:10 | 53184.46 | 77573.37 | 0.00 | 28157.23 | 25588.15 | 3974.62 | 0.00 | 113990.47 | 0.00 |
June | 367354.39 | 26-JUN-18:10 | 52987.32 | 77573.37 | 0.00 | 28157.23 | 26898.54 | 4334.93 | 0.00 | 160296.87 | 0.00 |
July | 402842.58 | 26-JUL-18:30 | 53184.46 | 77573.37 | 0.00 | 28166.69 | 25445.37 | 4705.62 | 0.00 | 196657.62 | 0.00 |
August | 379688.59 | 03-AUG-18:10 | 53184.46 | 77573.37 | 0.00 | 28157.33 | 24786.81 | 4443.63 | 0.00 | 174435.67 | 0.00 |
September | 330500.99 | 07-SEP-18:40 | 57474.69 | 77573.37 | 12338.45 | 28169.74 | 26808.26 | 3923.37 | 0.00 | 107105.96 | 0.00 |
October | 232284.12 | 20-OCT-18:10 | 57474.69 | 77573.37 | 12338.45 | 28159.60 | 21789.04 | 3453.38 | 0.00 | 24925.79 | 0.00 |
November | 225826.68 | 02-NOV-06:49 | 36001.17 | 89171.45 | 12338.45 | 49607.07 | 15698.12 | 3491.89 | 0.00 | 2977.43 | 0.00 |
December | 224378.84 | 12-DEC-07:30 | 36001.17 | 89171.45 | 12338.45 | 49607.07 | 18093.91 | 1287.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 224378.84 | 36001.17 | 74651.16 | 0.00 | 28110.46 | 15698.12 | 1287.23 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 402842.58 | 57474.69 | 89171.45 | 12338.45 | 49607.07 | 26898.54 | 4705.62 | 0.00 | 196657.62 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 735052.07 | 31-JAN-04:10 | 0.00 | 269342.93 | 31-JAN-21:30 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 775417.27 | 02-FEB-05:00 | 0.00 | 269507.31 | 21-FEB-21:19 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 233145.02 | 05-MAR-23:40 | 0.00 | 269465.06 | 01-MAR-21:40 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 197571.92 | 25-APR-17:40 | 0.00 | 267798.90 | 03-APR-20:49 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 187185.73 | 20-MAY-22:40 | 0.00 | 263827.54 | 01-MAY-20:19 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 185978.96 | 03-JUN-06:40 | 0.00 | 250577.53 | 01-JUN-20:19 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 89761.36 | 24-JUL-04:00 | 0.00 | 237836.91 | 03-JUL-20:49 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 152966.82 | 07-AUG-03:00 | 0.00 | 230824.87 | 01-AUG-20:49 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 196047.97 | 30-SEP-17:00 | 0.00 | 235602.32 | 28-SEP-20:40 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 202742.84 | 05-OCT-08:09 | 0.00 | 246699.17 | 31-OCT-20:19 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 704999.70 | 26-NOV-06:00 | 0.00 | 259671.12 | 29-NOV-21:30 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 345860.18 | 11-DEC-16:19 | 0.00 | 265736.14 | 29-DEC-21:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 104248.32 | 0.00 | 89761.36 | 0.00 | 230824.87 | 0.00 | |||
Maximum of Months | 104248.32 | 0.00 | 775417.27 | 0.00 | 269507.31 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 37.17 | 19.38 | 37.17 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 |
February | 133.50 | 16.91 | 133.50 | 16.91 | 0.00 | 16.91 | 0.00 | 16.91 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 170.67 | 17.44 | 170.67 | 17.44 | 0.00 | 17.44 | 0.00 | 17.44 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.50 | 19.38 | 133.50 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 77.17 | 16.62 | 77.17 | 16.62 | 0.00 | 16.62 | 0.00 | 16.62 |
February | 83.83 | 14.27 | 83.83 | 14.27 | 0.00 | 14.27 | 0.00 | 14.27 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11.83 | 17.17 | 11.83 | 17.17 | 0.00 | 17.17 | 0.00 | 17.17 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 172.83 | 15.52 | 172.83 | 15.52 | 0.00 | 15.52 | 0.00 | 15.52 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 83.83 | 17.17 | 83.83 | 17.17 | 0.00 | 17.17 | 0.00 | 17.17 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 81.83 | 18.12 | 81.83 | 18.12 | 0.00 | 18.12 | 0.00 | 18.12 |
February | 92.83 | 15.02 | 92.83 | 15.02 | 0.00 | 15.02 | 0.00 | 15.02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 10.17 | 18.98 | 10.17 | 18.98 | 0.00 | 18.98 | 0.00 | 18.98 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 184.83 | 16.61 | 184.83 | 16.61 | 0.00 | 16.61 | 0.00 | 16.61 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 92.83 | 18.98 | 92.83 | 18.98 | 0.00 | 18.98 | 0.00 | 18.98 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 89.00 | 19.08 | 89.00 | 19.08 | 0.00 | 19.08 | 0.00 | 19.08 |
February | 138.00 | 16.66 | 138.00 | 16.66 | 0.00 | 16.66 | 0.00 | 16.66 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 9.33 | 19.83 | 9.33 | 19.83 | 0.00 | 19.83 | 0.00 | 19.83 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 236.33 | 17.70 | 236.33 | 17.70 | 0.00 | 17.70 | 0.00 | 17.70 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 138.00 | 19.83 | 138.00 | 19.83 | 0.00 | 19.83 | 0.00 | 19.83 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 109.17 | 18.92 | 109.17 | 18.92 | 0.00 | 18.92 | 0.00 | 18.92 |
February | 139.17 | 16.22 | 139.17 | 16.22 | 0.00 | 16.22 | 0.00 | 16.22 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11.67 | 19.57 | 11.67 | 19.57 | 0.00 | 19.57 | 0.00 | 19.57 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 260.00 | 17.50 | 260.00 | 17.50 | 0.00 | 17.50 | 0.00 | 17.50 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 139.17 | 19.57 | 139.17 | 19.57 | 0.00 | 19.57 | 0.00 | 19.57 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 62.33 | 11.81 | 62.33 | 11.81 | 0.00 | 11.81 | 0.00 | 11.81 |
February | 70.67 | 8.60 | 70.67 | 8.60 | 0.00 | 8.60 | 0.00 | 8.60 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 7.83 | 13.29 | 7.83 | 13.29 | 0.00 | 13.29 | 0.00 | 13.29 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 140.83 | 10.28 | 140.83 | 10.28 | 0.00 | 10.28 | 0.00 | 10.28 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 70.67 | 13.29 | 70.67 | 13.29 | 0.00 | 13.29 | 0.00 | 13.29 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 74.83 | 17.33 | 74.83 | 17.33 | 0.00 | 17.33 | 0.00 | 17.33 |
February | 83.33 | 14.88 | 83.33 | 14.88 | 0.00 | 14.88 | 0.00 | 14.88 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11.33 | 17.92 | 11.33 | 17.92 | 0.00 | 17.92 | 0.00 | 17.92 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 169.50 | 16.17 | 169.50 | 16.17 | 0.00 | 16.17 | 0.00 | 16.17 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 83.33 | 17.92 | 83.33 | 17.92 | 0.00 | 17.92 | 0.00 | 17.92 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 75.17 | 18.09 | 75.17 | 18.09 | 0.00 | 18.09 | 0.00 | 18.09 |
February | 90.00 | 15.18 | 90.00 | 15.18 | 0.00 | 15.18 | 0.00 | 15.18 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 9.67 | 18.98 | 9.67 | 18.98 | 0.00 | 18.98 | 0.00 | 18.98 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 174.83 | 16.64 | 174.83 | 16.64 | 0.00 | 16.64 | 0.00 | 16.64 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 90.00 | 18.98 | 90.00 | 18.98 | 0.00 | 18.98 | 0.00 | 18.98 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.50 | 20.42 | 4.50 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 |
February | 30.50 | 19.90 | 30.50 | 19.90 | 0.00 | 19.90 | 0.00 | 19.90 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.77 | 0.17 | 21.77 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.70 | 0.67 | 21.70 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.68 | 0.83 | 21.68 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.72 | 1.00 | 21.72 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.81 | 1.17 | 21.81 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.33 | 20.51 | 0.33 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
December | 2.17 | 20.40 | 2.17 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 |
Annual Sum or Average | 37.50 | 20.00 | 37.50 | 20.00 | 3.83 | 20.08 | 3.83 | 20.16 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 30.50 | 20.51 | 30.50 | 20.51 | 1.17 | 21.81 | 1.17 | 21.81 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 16.83 | 20.25 | 16.83 | 20.25 | 0.00 | 20.25 | 0.00 | 20.25 |
February | 52.67 | 19.57 | 52.67 | 19.57 | 0.00 | 19.57 | 0.00 | 19.57 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.88 | 0.67 | 21.88 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 21.81 | 2.33 | 21.81 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 21.75 | 2.50 | 21.75 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.85 | 0.33 | 21.85 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.95 | 0.17 | 21.95 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.83 | 20.47 | 0.83 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
December | 3.00 | 20.38 | 3.00 | 20.38 | 0.00 | 20.38 | 0.00 | 20.38 |
Annual Sum or Average | 73.33 | 19.77 | 73.33 | 19.77 | 6.00 | 19.85 | 6.00 | 19.92 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 52.67 | 20.47 | 52.67 | 20.47 | 2.50 | 21.95 | 2.50 | 21.95 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 40.67 | 19.99 | 40.67 | 19.99 | 0.00 | 19.99 | 0.00 | 19.99 |
February | 64.67 | 18.96 | 64.67 | 18.96 | 0.00 | 18.96 | 0.00 | 18.96 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.85 | 0.17 | 21.85 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.79 | 1.33 | 21.79 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 21.81 | 4.83 | 21.81 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 21.82 | 5.67 | 21.82 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 21.76 | 5.00 | 21.76 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.72 | 1.00 | 21.72 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.50 | 20.30 | 1.50 | 20.30 | 0.00 | 20.30 | 0.00 | 20.30 |
December | 5.83 | 20.30 | 5.83 | 20.30 | 0.00 | 20.30 | 0.00 | 20.30 |
Annual Sum or Average | 112.67 | 19.42 | 112.67 | 19.42 | 18.00 | 19.60 | 18.00 | 19.75 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 64.67 | 20.30 | 64.67 | 20.30 | 5.67 | 21.85 | 5.67 | 21.85 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 9.67 | 20.39 | 9.67 | 20.39 | 0.00 | 20.39 | 0.00 | 20.39 |
February | 39.00 | 19.67 | 39.00 | 19.67 | 0.00 | 19.67 | 0.00 | 19.67 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.33 | 20.49 | 0.33 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 |
December | 2.67 | 20.40 | 2.67 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 |
Annual Sum or Average | 51.67 | 19.85 | 51.67 | 19.85 | 0.00 | 19.85 | 0.00 | 19.85 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 39.00 | 20.49 | 39.00 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 21.33 | 20.18 | 21.33 | 20.18 | 0.00 | 20.18 | 0.00 | 20.18 |
February | 55.00 | 19.24 | 55.00 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 22.12 | 0.33 | 22.12 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 22.07 | 1.50 | 22.07 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 22.34 | 4.50 | 22.34 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 22.35 | 6.50 | 22.35 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 22.13 | 3.83 | 22.13 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 22.23 | 1.50 | 22.23 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.83 | 20.44 | 0.83 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
December | 3.00 | 20.34 | 3.00 | 20.34 | 0.00 | 20.34 | 0.00 | 20.34 |
Annual Sum or Average | 80.17 | 19.55 | 80.17 | 19.55 | 18.17 | 19.82 | 18.17 | 20.05 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 55.00 | 20.44 | 55.00 | 20.44 | 6.50 | 22.35 | 6.50 | 22.35 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 82.17 | 19.35 | 82.17 | 19.35 | 0.00 | 19.35 | 0.00 | 19.35 |
February | 117.00 | 17.86 | 117.00 | 17.86 | 0.00 | 17.86 | 0.00 | 17.86 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11.17 | 19.77 | 11.17 | 19.77 | 0.00 | 19.77 | 0.00 | 19.77 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 210.33 | 18.55 | 210.33 | 18.55 | 0.00 | 18.55 | 0.00 | 18.55 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 117.00 | 19.77 | 117.00 | 19.77 | 0.00 | 19.77 | 0.00 | 19.77 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 10.67 | 20.37 | 10.67 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 |
February | 32.83 | 19.85 | 32.83 | 19.85 | 0.00 | 19.85 | 0.00 | 19.85 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.77 | 0.50 | 21.77 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.68 | 0.17 | 21.68 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.77 | 1.33 | 21.77 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 21.75 | 2.00 | 21.75 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.77 | 1.67 | 21.77 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.84 | 1.67 | 21.84 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.33 | 20.46 | 0.33 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 |
December | 2.83 | 20.35 | 2.83 | 20.35 | 0.00 | 20.35 | 0.00 | 20.35 |
Annual Sum or Average | 46.67 | 20.00 | 46.67 | 20.00 | 7.33 | 20.13 | 7.33 | 20.24 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 32.83 | 20.46 | 32.83 | 20.46 | 2.00 | 21.84 | 2.00 | 21.84 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 28.00 | 20.17 | 28.00 | 20.17 | 0.00 | 20.17 | 0.00 | 20.17 |
February | 53.33 | 19.40 | 53.33 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.81 | 0.33 | 21.81 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.97 | 1.00 | 21.97 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 21.85 | 3.67 | 21.85 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 21.78 | 4.50 | 21.78 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.77 | 1.83 | 21.77 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.76 | 0.83 | 21.76 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.00 | 20.43 | 1.00 | 20.43 | 0.00 | 20.43 | 0.00 | 20.43 |
December | 3.67 | 20.31 | 3.67 | 20.31 | 0.00 | 20.31 | 0.00 | 20.31 |
Annual Sum or Average | 86.00 | 19.70 | 86.00 | 19.70 | 12.17 | 19.84 | 12.17 | 19.96 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 53.33 | 20.43 | 53.33 | 20.43 | 4.50 | 21.97 | 4.50 | 21.97 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.67 | 20.41 | 1.67 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 |
February | 6.00 | 20.41 | 6.00 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.71 | 0.50 | 21.71 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.68 | 0.33 | 21.68 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.75 | 1.00 | 21.75 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 21.80 | 2.00 | 21.80 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.77 | 1.00 | 21.77 |
November | 0.17 | 20.49 | 0.17 | 20.49 | 0.50 | 21.29 | 0.50 | 21.49 |
December | 2.50 | 20.41 | 2.50 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 |
Annual Sum or Average | 10.33 | 20.41 | 10.33 | 20.41 | 5.33 | 20.69 | 5.33 | 20.87 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6.00 | 20.49 | 6.00 | 20.49 | 2.00 | 21.80 | 2.00 | 21.80 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 41.17 | 17.47 | 41.17 | 17.47 | 0.00 | 17.47 | 0.00 | 17.47 |
February | 78.33 | 15.25 | 78.33 | 15.25 | 0.00 | 15.25 | 0.00 | 15.25 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2.17 | 19.34 | 2.17 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 121.67 | 16.08 | 121.67 | 16.08 | 0.00 | 16.08 | 0.00 | 16.08 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 78.33 | 19.34 | 78.33 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 40.00 | 17.52 | 40.00 | 17.52 | 0.00 | 17.52 | 0.00 | 17.52 |
February | 77.50 | 15.23 | 77.50 | 15.23 | 0.00 | 15.23 | 0.00 | 15.23 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.67 | 19.25 | 1.67 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 119.17 | 16.06 | 119.17 | 16.06 | 0.00 | 16.06 | 0.00 | 16.06 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 77.50 | 19.25 | 77.50 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 37.83 | 14.16 | 37.83 | 14.16 | 0.00 | 14.16 | 0.00 | 14.16 |
February | 50.17 | 11.61 | 50.17 | 11.61 | 0.00 | 11.61 | 0.00 | 11.61 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6.33 | 14.60 | 6.33 | 14.60 | 0.00 | 14.60 | 0.00 | 14.60 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 94.33 | 12.83 | 94.33 | 12.83 | 0.00 | 12.83 | 0.00 | 12.83 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 50.17 | 14.60 | 50.17 | 14.60 | 0.00 | 14.60 | 0.00 | 14.60 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 89.83 | 18.47 | 89.83 | 18.47 | 0.00 | 18.47 | 0.00 | 18.47 |
February | 111.50 | 15.86 | 111.50 | 15.86 | 0.00 | 15.86 | 0.00 | 15.86 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 12.00 | 18.98 | 12.00 | 18.98 | 0.00 | 18.98 | 0.00 | 18.98 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 213.33 | 17.13 | 213.33 | 17.13 | 0.00 | 17.13 | 0.00 | 17.13 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 111.50 | 18.98 | 111.50 | 18.98 | 0.00 | 18.98 | 0.00 | 18.98 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 22.60 | 63.33 | 22.39 | 63.33 | 22.21 |
February | 672.00 | 21.40 | 140.67 | 20.66 | 140.67 | 20.13 |
March | 744.00 | 22.35 | 0.00 | 22.35 | 0.00 | 22.35 |
April | 720.00 | 21.95 | 0.00 | 21.95 | 0.00 | 21.95 |
May | 744.00 | 22.20 | 8.50 | 22.20 | 8.50 | 22.21 |
June | 719.67 | 22.73 | 45.83 | 22.73 | 45.83 | 22.74 |
July | 563.00 | 23.08 | 117.50 | 23.15 | 90.50 | 23.17 |
August | 254.67 | 23.47 | 321.17 | 23.69 | 95.83 | 23.70 |
September | 215.50 | 23.74 | 148.00 | 23.83 | 15.17 | 23.84 |
October | 448.33 | 23.86 | 0.00 | 23.86 | 0.00 | 23.86 |
November | 534.67 | 23.71 | 11.67 | 23.72 | 0.00 | 23.72 |
December | 744.00 | 23.74 | 0.00 | 23.74 | 0.00 | 23.74 |
Annual Sum or Average | 7103.83 | 22.75 | 856.67 | 22.71 | 459.83 | 22.62 |
Minimum of Months | 215.50 | 21.40 | 0.00 | 20.66 | 0.00 | 20.13 |
Maximum of Months | 744.00 | 23.86 | 321.17 | 23.86 | 140.67 | 23.86 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 735.00 | 20.61 | 618.33 | 20.54 | 618.33 | 20.51 |
February | 653.50 | 20.23 | 434.17 | 20.04 | 425.00 | 19.93 |
March | 711.50 | 21.20 | 282.83 | 21.18 | 271.67 | 21.14 |
April | 627.67 | 21.32 | 160.50 | 21.45 | 102.67 | 21.40 |
May | 654.00 | 21.52 | 51.83 | 21.68 | 0.00 | 21.68 |
June | 464.17 | 21.81 | 179.83 | 22.32 | 0.00 | 22.32 |
July | 391.17 | 22.09 | 247.50 | 22.67 | 0.00 | 22.67 |
August | 410.33 | 22.10 | 248.83 | 22.68 | 0.00 | 22.68 |
September | 491.00 | 21.66 | 172.17 | 22.20 | 4.00 | 22.20 |
October | 656.83 | 21.32 | 70.17 | 21.51 | 15.00 | 21.50 |
November | 694.83 | 21.06 | 341.00 | 21.03 | 327.50 | 20.99 |
December | 726.67 | 21.11 | 594.17 | 21.07 | 591.17 | 21.05 |
Annual Sum or Average | 7216.67 | 21.25 | 3401.33 | 21.34 | 2355.33 | 21.21 |
Minimum of Months | 391.17 | 20.23 | 51.83 | 20.04 | 0.00 | 19.93 |
Maximum of Months | 735.00 | 22.10 | 618.33 | 22.68 | 618.33 | 22.68 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.90 | 312.00 | 20.71 | 312.00 | 20.60 |
February | 672.00 | 20.67 | 158.50 | 20.06 | 158.50 | 19.64 |
March | 744.00 | 21.95 | 5.50 | 21.94 | 5.50 | 21.93 |
April | 648.00 | 22.35 | 33.50 | 22.42 | 5.17 | 22.43 |
May | 613.17 | 22.86 | 71.00 | 22.95 | 33.17 | 22.98 |
June | 381.33 | 23.10 | 286.33 | 23.43 | 104.83 | 23.48 |
July | 289.50 | 23.48 | 450.00 | 23.70 | 164.67 | 23.74 |
August | 260.83 | 23.46 | 412.17 | 23.69 | 138.33 | 23.71 |
September | 422.50 | 22.96 | 185.83 | 23.24 | 26.83 | 23.27 |
October | 730.17 | 22.65 | 0.00 | 22.65 | 0.00 | 22.65 |
November | 720.00 | 21.92 | 61.00 | 21.82 | 61.00 | 21.73 |
December | 744.00 | 21.43 | 127.83 | 21.37 | 127.83 | 21.32 |
Annual Sum or Average | 6969.50 | 22.09 | 2103.67 | 22.20 | 1137.83 | 22.12 |
Minimum of Months | 260.83 | 20.67 | 0.00 | 20.06 | 0.00 | 19.64 |
Maximum of Months | 744.00 | 23.48 | 450.00 | 23.70 | 312.00 | 23.74 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.76 | 588.00 | 20.73 | 588.00 | 20.72 |
February | 672.00 | 20.13 | 363.33 | 19.86 | 363.33 | 19.73 |
March | 744.00 | 21.21 | 201.67 | 21.17 | 201.67 | 21.14 |
April | 715.17 | 21.65 | 20.33 | 21.64 | 20.33 | 21.62 |
May | 733.83 | 22.51 | 1.50 | 22.51 | 0.00 | 22.51 |
June | 472.67 | 22.93 | 89.83 | 23.08 | 0.00 | 23.08 |
July | 273.50 | 23.21 | 169.67 | 23.47 | 0.00 | 23.47 |
August | 368.33 | 23.28 | 103.83 | 23.41 | 0.00 | 23.41 |
September | 574.50 | 22.78 | 25.83 | 22.83 | 0.00 | 22.83 |
October | 744.00 | 21.86 | 0.00 | 21.86 | 0.00 | 21.86 |
November | 720.00 | 21.34 | 185.00 | 21.26 | 185.00 | 21.21 |
December | 744.00 | 21.01 | 511.50 | 21.01 | 511.50 | 21.00 |
Annual Sum or Average | 7506.00 | 21.70 | 2260.50 | 21.57 | 1869.83 | 21.41 |
Minimum of Months | 273.50 | 20.13 | 0.00 | 19.86 | 0.00 | 19.73 |
Maximum of Months | 744.00 | 23.28 | 588.00 | 23.47 | 588.00 | 23.47 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.68 | 633.83 | 20.66 | 633.83 | 20.65 |
February | 672.00 | 20.01 | 412.83 | 19.77 | 412.83 | 19.67 |
March | 744.00 | 21.08 | 294.33 | 21.05 | 294.33 | 21.04 |
April | 720.00 | 21.44 | 60.00 | 21.40 | 60.00 | 21.37 |
May | 741.67 | 22.21 | 0.00 | 22.21 | 0.00 | 22.21 |
June | 568.67 | 22.76 | 42.33 | 22.83 | 0.00 | 22.83 |
July | 453.17 | 23.08 | 27.50 | 23.13 | 0.00 | 23.13 |
August | 594.00 | 23.12 | 22.50 | 23.15 | 0.00 | 23.15 |
September | 660.17 | 22.55 | 0.17 | 22.55 | 0.00 | 22.55 |
October | 744.00 | 21.46 | 0.00 | 21.46 | 0.00 | 21.46 |
November | 720.00 | 21.17 | 250.50 | 21.11 | 250.50 | 21.07 |
December | 744.00 | 21.00 | 597.83 | 21.00 | 597.83 | 21.00 |
Annual Sum or Average | 8105.67 | 21.62 | 2341.83 | 21.42 | 2249.33 | 21.27 |
Minimum of Months | 453.17 | 20.01 | 0.00 | 19.77 | 0.00 | 19.67 |
Maximum of Months | 744.00 | 23.12 | 633.83 | 23.15 | 633.83 | 23.15 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 362.83 | 20.32 | 396.00 | 21.02 | 175.17 | 20.67 |
February | 287.00 | 18.86 | 428.33 | 20.11 | 182.50 | 19.58 |
March | 249.33 | 22.89 | 503.00 | 23.32 | 150.00 | 23.44 |
April | 254.00 | 23.28 | 567.50 | 23.38 | 189.50 | 23.49 |
May | 293.83 | 23.76 | 672.17 | 23.44 | 269.50 | 23.56 |
June | 305.33 | 23.91 | 686.50 | 23.42 | 298.67 | 23.55 |
July | 330.67 | 23.96 | 735.17 | 23.41 | 330.67 | 23.54 |
August | 324.00 | 23.95 | 725.50 | 23.42 | 322.33 | 23.55 |
September | 293.67 | 23.73 | 653.17 | 23.43 | 266.83 | 23.55 |
October | 243.50 | 23.28 | 624.17 | 23.38 | 181.33 | 23.49 |
November | 259.50 | 22.62 | 488.67 | 23.10 | 165.33 | 23.15 |
December | 270.67 | 22.56 | 382.83 | 23.26 | 119.67 | 23.38 |
Annual Sum or Average | 3474.33 | 22.73 | 6863.00 | 22.97 | 2651.50 | 23.01 |
Minimum of Months | 243.50 | 18.86 | 382.83 | 20.11 | 119.67 | 19.58 |
Maximum of Months | 362.83 | 23.96 | 735.17 | 23.44 | 330.67 | 23.56 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 726.33 | 20.85 | 394.17 | 20.67 | 390.83 | 20.57 |
February | 638.33 | 20.71 | 211.33 | 20.25 | 192.83 | 19.90 |
March | 670.67 | 21.85 | 78.33 | 21.89 | 46.00 | 21.84 |
April | 549.00 | 22.09 | 139.83 | 22.42 | 24.83 | 22.44 |
May | 465.00 | 22.61 | 219.67 | 22.92 | 73.33 | 22.99 |
June | 353.17 | 23.03 | 486.83 | 23.37 | 176.83 | 23.45 |
July | 350.33 | 23.54 | 627.17 | 23.60 | 298.83 | 23.64 |
August | 289.83 | 23.52 | 624.00 | 23.62 | 239.00 | 23.65 |
September | 352.33 | 22.68 | 344.33 | 23.26 | 68.33 | 23.32 |
October | 559.83 | 22.31 | 106.50 | 22.57 | 0.00 | 22.57 |
November | 667.67 | 21.66 | 129.83 | 21.60 | 103.50 | 21.50 |
December | 707.17 | 21.41 | 272.50 | 21.33 | 261.83 | 21.26 |
Annual Sum or Average | 6329.67 | 21.95 | 3634.50 | 22.24 | 1876.17 | 22.18 |
Minimum of Months | 289.83 | 20.71 | 78.33 | 20.25 | 0.00 | 19.90 |
Maximum of Months | 726.33 | 23.54 | 627.17 | 23.62 | 390.83 | 23.65 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.28 | 183.67 | 20.99 | 183.67 | 20.79 |
February | 672.00 | 21.13 | 138.00 | 20.46 | 138.00 | 19.99 |
March | 721.50 | 22.40 | 0.00 | 22.40 | 0.00 | 22.40 |
April | 590.00 | 22.65 | 76.33 | 22.78 | 16.33 | 22.81 |
May | 439.17 | 23.03 | 217.17 | 23.29 | 70.00 | 23.35 |
June | 303.50 | 23.37 | 433.67 | 23.63 | 159.50 | 23.69 |
July | 306.67 | 23.82 | 590.67 | 23.80 | 274.67 | 23.83 |
August | 229.67 | 23.83 | 590.17 | 23.80 | 208.00 | 23.83 |
September | 299.50 | 23.14 | 322.83 | 23.52 | 58.67 | 23.56 |
October | 614.00 | 22.96 | 9.00 | 22.98 | 0.00 | 22.98 |
November | 644.17 | 22.21 | 38.83 | 22.15 | 29.50 | 22.07 |
December | 744.00 | 21.91 | 51.33 | 21.85 | 51.33 | 21.80 |
Annual Sum or Average | 6308.17 | 22.38 | 2651.67 | 22.59 | 1189.67 | 22.56 |
Minimum of Months | 229.67 | 21.13 | 0.00 | 20.46 | 0.00 | 19.99 |
Maximum of Months | 744.00 | 23.83 | 590.67 | 23.80 | 274.67 | 23.83 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.61 | 702.33 | 20.58 | 702.33 | 20.58 |
February | 672.00 | 20.74 | 498.83 | 20.65 | 498.83 | 20.61 |
March | 742.17 | 21.09 | 341.50 | 20.98 | 341.50 | 20.92 |
April | 690.00 | 21.25 | 117.33 | 21.18 | 110.17 | 21.11 |
May | 696.83 | 21.54 | 5.17 | 21.55 | 0.00 | 21.55 |
June | 622.33 | 21.43 | 24.17 | 21.50 | 2.17 | 21.50 |
July | 614.17 | 21.39 | 32.83 | 21.49 | 1.17 | 21.49 |
August | 617.83 | 21.39 | 26.17 | 21.47 | 4.17 | 21.48 |
September | 646.50 | 21.42 | 22.83 | 21.46 | 6.17 | 21.46 |
October | 734.50 | 21.38 | 27.67 | 21.36 | 27.67 | 21.34 |
November | 716.33 | 20.93 | 394.67 | 20.83 | 394.67 | 20.79 |
December | 744.00 | 20.71 | 666.17 | 20.67 | 666.17 | 20.66 |
Annual Sum or Average | 8240.67 | 21.14 | 2859.67 | 21.03 | 2755.00 | 20.95 |
Minimum of Months | 614.17 | 20.61 | 5.17 | 20.58 | 0.00 | 20.58 |
Maximum of Months | 744.00 | 21.54 | 702.33 | 21.55 | 702.33 | 21.55 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.47 | 740.83 | 20.47 | 740.83 | 20.47 |
February | 672.00 | 20.49 | 592.17 | 20.44 | 592.17 | 20.43 |
March | 744.00 | 20.88 | 424.17 | 20.78 | 424.17 | 20.73 |
April | 685.83 | 21.24 | 152.67 | 21.20 | 137.50 | 21.13 |
May | 658.67 | 21.76 | 67.67 | 22.07 | 19.67 | 22.15 |
June | 573.00 | 21.97 | 127.50 | 22.53 | 63.00 | 22.77 |
July | 556.67 | 22.20 | 171.17 | 22.83 | 94.17 | 23.10 |
August | 566.33 | 22.04 | 164.67 | 22.60 | 85.83 | 22.79 |
September | 619.50 | 21.60 | 45.50 | 21.80 | 13.50 | 21.82 |
October | 737.83 | 21.20 | 88.00 | 21.15 | 86.67 | 21.11 |
November | 720.00 | 20.77 | 457.67 | 20.68 | 457.67 | 20.65 |
December | 744.00 | 20.52 | 737.33 | 20.52 | 737.33 | 20.52 |
Annual Sum or Average | 8021.83 | 21.20 | 3769.33 | 21.20 | 3452.50 | 21.12 |
Minimum of Months | 556.67 | 20.47 | 45.50 | 20.44 | 13.50 | 20.43 |
Maximum of Months | 744.00 | 22.20 | 740.83 | 22.83 | 740.83 | 23.10 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.59 | 627.67 | 20.55 | 627.67 | 20.53 |
February | 672.00 | 20.60 | 405.00 | 20.47 | 405.00 | 20.42 |
March | 744.00 | 21.06 | 242.17 | 20.99 | 242.17 | 20.95 |
April | 720.00 | 21.35 | 22.83 | 21.32 | 22.83 | 21.30 |
May | 734.17 | 21.75 | 10.50 | 21.78 | 7.83 | 21.79 |
June | 697.50 | 21.98 | 43.50 | 22.08 | 35.50 | 22.15 |
July | 705.00 | 22.13 | 66.00 | 22.26 | 53.50 | 22.33 |
August | 736.50 | 22.12 | 69.50 | 22.22 | 69.00 | 22.30 |
September | 720.00 | 21.75 | 0.33 | 21.75 | 0.33 | 21.75 |
October | 744.00 | 21.27 | 0.00 | 21.27 | 0.00 | 21.27 |
November | 720.00 | 20.99 | 269.17 | 20.90 | 269.17 | 20.85 |
December | 744.00 | 20.73 | 608.17 | 20.69 | 608.17 | 20.67 |
Annual Sum or Average | 8681.17 | 21.36 | 2364.83 | 21.24 | 2341.17 | 21.15 |
Minimum of Months | 672.00 | 20.59 | 0.00 | 20.47 | 0.00 | 20.42 |
Maximum of Months | 744.00 | 22.13 | 627.67 | 22.26 | 627.67 | 22.33 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.59 | 693.00 | 20.57 | 693.00 | 20.56 |
February | 672.00 | 20.72 | 490.00 | 20.63 | 490.00 | 20.59 |
March | 744.00 | 21.17 | 304.33 | 21.06 | 304.33 | 20.99 |
April | 695.83 | 21.30 | 126.00 | 21.21 | 124.83 | 21.14 |
May | 689.17 | 21.57 | 0.83 | 21.58 | 0.00 | 21.58 |
June | 594.50 | 21.37 | 11.83 | 21.40 | 1.50 | 21.41 |
July | 591.67 | 21.34 | 13.33 | 21.38 | 0.83 | 21.38 |
August | 610.17 | 21.39 | 8.83 | 21.41 | 3.50 | 21.42 |
September | 638.00 | 21.44 | 5.67 | 21.45 | 0.33 | 21.45 |
October | 743.50 | 21.45 | 27.00 | 21.44 | 27.00 | 21.42 |
November | 720.00 | 20.93 | 399.67 | 20.83 | 399.67 | 20.78 |
December | 744.00 | 20.68 | 664.83 | 20.65 | 664.83 | 20.64 |
Annual Sum or Average | 8186.83 | 21.15 | 2745.33 | 21.02 | 2709.83 | 20.94 |
Minimum of Months | 591.67 | 20.59 | 0.83 | 20.57 | 0.00 | 20.56 |
Maximum of Months | 744.00 | 21.57 | 693.00 | 21.58 | 693.00 | 21.58 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.46 | 736.50 | 20.46 | 736.50 | 20.46 |
February | 672.00 | 20.45 | 599.50 | 20.41 | 599.50 | 20.40 |
March | 744.00 | 20.95 | 400.67 | 20.86 | 400.67 | 20.82 |
April | 695.50 | 21.29 | 155.00 | 21.20 | 150.33 | 21.12 |
May | 684.17 | 21.86 | 34.00 | 21.99 | 13.33 | 22.03 |
June | 530.00 | 21.82 | 110.17 | 22.34 | 46.67 | 22.54 |
July | 488.83 | 21.99 | 170.00 | 22.70 | 70.83 | 22.94 |
August | 537.83 | 21.94 | 123.17 | 22.37 | 73.00 | 22.54 |
September | 634.83 | 21.71 | 23.17 | 21.81 | 6.00 | 21.82 |
October | 744.00 | 21.24 | 63.67 | 21.22 | 63.67 | 21.20 |
November | 720.00 | 20.75 | 456.17 | 20.66 | 456.17 | 20.62 |
December | 744.00 | 20.51 | 731.67 | 20.51 | 731.67 | 20.50 |
Annual Sum or Average | 7939.17 | 21.19 | 3603.67 | 21.14 | 3348.33 | 21.06 |
Minimum of Months | 488.83 | 20.45 | 23.17 | 20.41 | 6.00 | 20.40 |
Maximum of Months | 744.00 | 21.99 | 736.50 | 22.70 | 736.50 | 22.94 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.81 | 579.83 | 20.79 | 579.83 | 20.78 |
February | 672.00 | 20.45 | 315.17 | 20.25 | 315.17 | 20.14 |
March | 744.00 | 21.11 | 150.50 | 21.09 | 150.50 | 21.08 |
April | 720.00 | 21.55 | 22.17 | 21.54 | 22.17 | 21.53 |
May | 744.00 | 22.28 | 21.83 | 22.29 | 21.83 | 22.29 |
June | 621.17 | 22.86 | 124.83 | 22.95 | 98.50 | 22.99 |
July | 514.67 | 23.21 | 191.83 | 23.28 | 156.50 | 23.30 |
August | 635.17 | 23.17 | 139.00 | 23.19 | 129.00 | 23.19 |
September | 641.50 | 22.58 | 20.33 | 22.60 | 19.33 | 22.62 |
October | 744.00 | 21.37 | 0.00 | 21.37 | 0.00 | 21.37 |
November | 720.00 | 21.10 | 189.00 | 21.06 | 189.00 | 21.04 |
December | 744.00 | 21.00 | 489.00 | 21.00 | 489.00 | 21.00 |
Annual Sum or Average | 8244.50 | 21.72 | 2243.50 | 21.63 | 2170.83 | 21.56 |
Minimum of Months | 514.67 | 20.45 | 0.00 | 20.25 | 0.00 | 20.14 |
Maximum of Months | 744.00 | 23.21 | 579.83 | 23.28 | 579.83 | 23.30 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.53 | 723.00 | 20.52 | 723.00 | 20.51 |
February | 671.50 | 20.64 | 568.67 | 20.58 | 568.67 | 20.55 |
March | 741.33 | 20.97 | 431.17 | 20.87 | 431.17 | 20.82 |
April | 684.33 | 21.17 | 198.50 | 21.08 | 188.50 | 21.00 |
May | 679.50 | 21.47 | 17.33 | 21.50 | 6.00 | 21.50 |
June | 604.67 | 21.36 | 47.50 | 21.49 | 6.50 | 21.50 |
July | 598.83 | 21.35 | 63.17 | 21.53 | 6.67 | 21.54 |
August | 606.83 | 21.35 | 53.17 | 21.49 | 13.33 | 21.50 |
September | 641.33 | 21.37 | 48.50 | 21.44 | 18.83 | 21.43 |
October | 730.83 | 21.29 | 126.67 | 21.23 | 125.67 | 21.19 |
November | 716.00 | 20.83 | 447.67 | 20.74 | 447.67 | 20.70 |
December | 744.00 | 20.63 | 702.33 | 20.61 | 702.33 | 20.60 |
Annual Sum or Average | 8163.17 | 21.06 | 3427.67 | 20.97 | 3238.33 | 20.89 |
Minimum of Months | 598.83 | 20.53 | 17.33 | 20.52 | 6.00 | 20.51 |
Maximum of Months | 744.00 | 21.47 | 723.00 | 21.53 | 723.00 | 21.54 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.43 | 743.00 | 20.43 | 743.00 | 20.43 |
February | 672.00 | 20.41 | 637.67 | 20.39 | 637.67 | 20.38 |
March | 744.00 | 20.78 | 502.67 | 20.69 | 502.67 | 20.65 |
April | 683.00 | 21.16 | 243.83 | 21.12 | 225.33 | 21.03 |
May | 648.83 | 21.80 | 81.17 | 22.16 | 37.17 | 22.30 |
June | 569.00 | 22.05 | 148.83 | 22.68 | 79.00 | 22.98 |
July | 555.33 | 22.29 | 201.50 | 22.97 | 117.00 | 23.27 |
August | 561.83 | 22.08 | 189.00 | 22.70 | 109.17 | 22.92 |
September | 615.00 | 21.55 | 83.00 | 21.77 | 43.83 | 21.80 |
October | 736.67 | 21.09 | 251.00 | 21.01 | 248.17 | 20.95 |
November | 720.00 | 20.68 | 518.00 | 20.61 | 518.00 | 20.58 |
December | 744.00 | 20.48 | 743.00 | 20.48 | 743.00 | 20.48 |
Annual Sum or Average | 7993.67 | 21.17 | 4342.67 | 21.18 | 4004.00 | 21.11 |
Minimum of Months | 555.33 | 20.41 | 81.17 | 20.39 | 37.17 | 20.38 |
Maximum of Months | 744.00 | 22.29 | 743.00 | 22.97 | 743.00 | 23.27 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 741.50 | 20.98 | 585.17 | 20.87 | 585.17 | 20.83 |
February | 657.00 | 21.09 | 369.83 | 20.97 | 369.83 | 20.91 |
March | 726.50 | 21.25 | 243.17 | 21.14 | 243.17 | 21.07 |
April | 672.33 | 21.24 | 113.50 | 21.18 | 106.67 | 21.11 |
May | 691.00 | 21.52 | 0.00 | 21.52 | 0.00 | 21.52 |
June | 635.00 | 21.46 | 8.00 | 21.47 | 7.50 | 21.48 |
July | 637.50 | 21.44 | 13.00 | 21.47 | 8.50 | 21.49 |
August | 635.33 | 21.43 | 27.17 | 21.48 | 15.67 | 21.49 |
September | 630.67 | 21.40 | 35.33 | 21.51 | 0.17 | 21.51 |
October | 685.33 | 21.39 | 10.17 | 21.40 | 5.00 | 21.39 |
November | 704.67 | 21.14 | 307.67 | 21.03 | 303.83 | 20.96 |
December | 734.83 | 20.97 | 553.83 | 20.85 | 553.83 | 20.80 |
Annual Sum or Average | 8151.67 | 21.27 | 2266.83 | 21.17 | 2199.33 | 21.10 |
Minimum of Months | 630.67 | 20.97 | 0.00 | 20.85 | 0.00 | 20.80 |
Maximum of Months | 741.50 | 21.52 | 585.17 | 21.52 | 585.17 | 21.52 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 709.83 | 22.35 | 106.17 | 21.96 | 106.17 | 21.66 |
February | 554.67 | 21.86 | 117.17 | 21.03 | 117.17 | 20.45 |
March | 478.17 | 23.29 | 53.50 | 23.36 | 0.00 | 23.36 |
April | 244.83 | 23.33 | 194.83 | 23.62 | 17.67 | 23.63 |
May | 101.33 | 23.85 | 564.67 | 23.94 | 81.83 | 23.94 |
June | 161.33 | 23.98 | 699.00 | 23.97 | 159.33 | 23.98 |
July | 274.67 | 24.00 | 744.00 | 23.98 | 274.67 | 23.98 |
August | 218.67 | 24.00 | 740.50 | 23.97 | 218.67 | 23.98 |
September | 116.67 | 23.67 | 508.67 | 23.92 | 66.00 | 23.92 |
October | 224.00 | 23.23 | 117.00 | 23.49 | 0.00 | 23.49 |
November | 466.17 | 23.05 | 106.50 | 23.12 | 14.83 | 23.05 |
December | 716.00 | 23.08 | 13.50 | 23.04 | 13.50 | 23.01 |
Annual Sum or Average | 4266.33 | 23.02 | 3965.50 | 23.31 | 1069.83 | 23.24 |
Minimum of Months | 101.33 | 21.86 | 13.50 | 21.03 | 0.00 | 20.45 |
Maximum of Months | 716.00 | 24.00 | 744.00 | 23.98 | 274.67 | 23.98 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 637.50 | 22.46 | 94.00 | 22.05 | 91.33 | 21.73 |
February | 435.17 | 21.61 | 106.83 | 20.66 | 104.50 | 20.01 |
March | 268.83 | 23.29 | 95.83 | 23.47 | 0.00 | 23.47 |
April | 111.83 | 23.35 | 290.17 | 23.80 | 14.00 | 23.81 |
May | 59.33 | 23.97 | 662.00 | 23.98 | 57.50 | 23.98 |
June | 141.83 | 24.00 | 713.50 | 23.99 | 141.83 | 23.99 |
July | 254.33 | 24.00 | 744.00 | 23.99 | 254.33 | 23.99 |
August | 202.33 | 24.00 | 743.33 | 23.99 | 202.33 | 23.99 |
September | 74.67 | 23.89 | 586.00 | 23.97 | 61.67 | 23.98 |
October | 88.00 | 23.31 | 234.00 | 23.79 | 0.00 | 23.79 |
November | 310.17 | 23.05 | 160.33 | 23.26 | 10.83 | 23.19 |
December | 561.67 | 23.17 | 0.00 | 23.17 | 0.00 | 23.17 |
Annual Sum or Average | 3145.67 | 23.01 | 4430.00 | 23.41 | 938.33 | 23.33 |
Minimum of Months | 59.33 | 21.61 | 0.00 | 20.66 | 0.00 | 20.01 |
Maximum of Months | 637.50 | 24.00 | 744.00 | 23.99 | 254.33 | 23.99 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 484.50 | 22.42 | 578.67 | 22.82 | 369.00 | 22.80 |
February | 473.50 | 21.98 | 555.50 | 22.28 | 412.50 | 22.23 |
March | 518.50 | 23.86 | 650.50 | 23.89 | 476.83 | 23.92 |
April | 502.17 | 23.98 | 674.83 | 23.94 | 498.00 | 23.95 |
May | 552.00 | 23.99 | 742.33 | 23.95 | 552.00 | 23.96 |
June | 567.67 | 23.99 | 720.00 | 23.97 | 567.67 | 23.98 |
July | 598.83 | 23.99 | 744.00 | 23.98 | 598.83 | 23.98 |
August | 590.17 | 23.99 | 744.00 | 23.97 | 590.17 | 23.98 |
September | 531.50 | 23.99 | 715.83 | 23.95 | 531.50 | 23.96 |
October | 508.67 | 23.99 | 711.50 | 23.93 | 508.67 | 23.95 |
November | 494.17 | 23.68 | 630.50 | 23.75 | 451.33 | 23.77 |
December | 484.17 | 23.64 | 587.00 | 23.82 | 389.50 | 23.86 |
Annual Sum or Average | 6305.83 | 23.66 | 8054.67 | 23.72 | 5946.00 | 23.73 |
Minimum of Months | 473.50 | 21.98 | 555.50 | 22.28 | 369.00 | 22.23 |
Maximum of Months | 598.83 | 23.99 | 744.00 | 23.98 | 598.83 | 23.98 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.69 | 616.17 | 20.66 | 616.17 | 20.65 |
February | 672.00 | 20.15 | 362.00 | 19.89 | 362.00 | 19.76 |
March | 744.00 | 21.11 | 210.83 | 21.09 | 210.83 | 21.07 |
April | 689.83 | 21.52 | 31.83 | 21.52 | 25.00 | 21.50 |
May | 702.17 | 22.29 | 24.00 | 22.34 | 0.00 | 22.34 |
June | 353.83 | 22.58 | 212.33 | 23.04 | 0.00 | 23.04 |
July | 212.00 | 22.91 | 332.83 | 23.47 | 0.00 | 23.47 |
August | 344.17 | 22.95 | 200.67 | 23.27 | 0.00 | 23.27 |
September | 540.50 | 22.23 | 88.00 | 22.46 | 0.00 | 22.46 |
October | 744.00 | 21.36 | 0.00 | 21.36 | 0.00 | 21.36 |
November | 720.00 | 21.07 | 237.17 | 21.03 | 237.17 | 21.00 |
December | 744.00 | 21.00 | 567.83 | 21.00 | 567.83 | 21.00 |
Annual Sum or Average | 7210.50 | 21.44 | 2883.67 | 21.47 | 2019.00 | 21.32 |
Minimum of Months | 212.00 | 20.15 | 0.00 | 19.89 | 0.00 | 19.76 |
Maximum of Months | 744.00 | 22.95 | 616.17 | 23.47 | 616.17 | 23.47 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.59831 | 17.74999 | -0.1521 | 6.82948 |
February | 672.00000 | 21.40440 | 21.91159 | -0.4165 | 15.10945 |
March | 744.00000 | 22.34814 | 27.87028 | -0.1665 | 5.74092 |
April | 720.00000 | 21.95063 | 35.94643 | -0.2170 | 6.20048 |
May | 744.00000 | 22.20241 | 48.71823 | -1.1634 | 33.72553 |
June | 720.00000 | 22.72572 | 55.97576 | -0.9246 | 23.35710 |
July | 744.00000 | 23.21597 | 58.98313 | -0.7237 | 16.27391 |
August | 744.00000 | 23.66681 | 55.90002 | -0.5748 | 12.11106 |
September | 720.00000 | 23.84663 | 42.90673 | -0.5918 | 12.55860 |
October | 744.00000 | 23.90016 | 30.76713 | 0.26067 | 6.48214 |
November | 720.00000 | 23.77490 | 26.95844 | 0.20196 | 6.23351 |
December | 744.00000 | 23.74076 | 20.30164 | 0.13954 | 5.50616 |
Annual Sum or Average | 8760.00000 | 22.95920 | 37.08534 | -0.3600 | 12.49397 |
Minimum of Months | 672.00000 | 21.40440 | 17.74999 | -1.1634 | 5.50616 |
Maximum of Months | 744.00000 | 23.90016 | 58.98313 | 0.26067 | 33.72553 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.64624 | 17.53996 | -0.7405 | 18.98225 |
February | 672.00000 | 20.33214 | 21.54111 | -0.7266 | 20.25051 |
March | 744.00000 | 21.31274 | 27.75329 | -0.4178 | 10.12227 |
April | 720.00000 | 21.61808 | 34.77898 | -0.2454 | 8.86326 |
May | 744.00000 | 21.75704 | 48.48564 | -1.1545 | 35.18639 |
June | 720.00000 | 22.37728 | 55.62995 | -0.8570 | 23.72443 |
July | 744.00000 | 22.70548 | 59.44829 | -0.6938 | 17.27023 |
August | 744.00000 | 22.71347 | 57.73946 | -0.7005 | 17.70859 |
September | 720.00000 | 22.29945 | 45.01401 | -0.9554 | 29.22463 |
October | 744.00000 | 21.61678 | 33.44173 | -0.2289 | 8.02942 |
November | 720.00000 | 21.15680 | 29.40749 | -0.4673 | 11.35611 |
December | 744.00000 | 21.17921 | 21.27131 | -0.5885 | 13.51825 |
Annual Sum or Average | 8760.00000 | 21.65126 | 37.76475 | -0.6476 | 17.82851 |
Minimum of Months | 672.00000 | 20.33214 | 17.53996 | -1.1545 | 8.02942 |
Maximum of Months | 744.00000 | 22.71347 | 59.44829 | -0.2289 | 35.18639 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.90314 | 19.79092 | -0.5621 | 13.15424 |
February | 672.00000 | 20.66712 | 23.45079 | -0.5784 | 17.18080 |
March | 744.00000 | 21.94709 | 29.20245 | -0.2310 | 6.84924 |
April | 720.00000 | 22.48597 | 35.68941 | -0.0459 | 6.19755 |
May | 744.00000 | 23.00709 | 47.70665 | -0.8240 | 20.12901 |
June | 720.00000 | 23.36687 | 55.00646 | -0.6320 | 14.36383 |
July | 744.00000 | 23.58531 | 58.78238 | -0.5208 | 11.07042 |
August | 744.00000 | 23.58948 | 57.18889 | -0.5317 | 11.25656 |
September | 720.00000 | 23.29467 | 45.11780 | -0.7270 | 17.56012 |
October | 744.00000 | 22.67574 | 34.07018 | -0.0082 | 5.39622 |
November | 720.00000 | 21.91545 | 30.48768 | -0.2328 | 7.42248 |
December | 744.00000 | 21.43017 | 23.43141 | -0.4109 | 8.88926 |
Annual Sum or Average | 8760.00000 | 22.41602 | 38.41376 | -0.4413 | 11.57938 |
Minimum of Months | 672.00000 | 20.66712 | 19.79092 | -0.8240 | 5.39622 |
Maximum of Months | 744.00000 | 23.58948 | 58.78238 | -0.0082 | 20.12901 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.77353 | 14.12405 | 0.20279 | 17.71729 |
February | 672.00000 | 21.29405 | 17.79564 | 0.13821 | 22.45218 |
March | 744.00000 | 23.01606 | 23.23891 | 0.59315 | 15.11561 |
April | 720.00000 | 23.06332 | 30.18881 | 0.67752 | 17.30667 |
May | 744.00000 | 23.11937 | 42.69341 | 0.09892 | 10.21375 |
June | 720.00000 | 23.11488 | 51.09602 | 0.18261 | 10.60191 |
July | 744.00000 | 23.13789 | 55.49294 | 0.22981 | 10.68565 |
August | 744.00000 | 23.13975 | 53.89225 | 0.21770 | 10.74242 |
September | 720.00000 | 23.13072 | 41.01792 | 0.09910 | 10.15615 |
October | 744.00000 | 23.11944 | 28.59712 | 0.68518 | 17.25479 |
November | 720.00000 | 22.87938 | 24.57093 | 0.56496 | 15.80896 |
December | 744.00000 | 22.92597 | 17.37897 | 0.49056 | 12.76288 |
Annual Sum or Average | 8760.00000 | 22.81938 | 33.43133 | 0.34975 | 14.17572 |
Minimum of Months | 672.00000 | 21.29405 | 14.12405 | 0.09892 | 10.15615 |
Maximum of Months | 744.00000 | 23.13975 | 55.49294 | 0.68518 | 22.45218 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.91990 | 22.56844 | -0.5690 | 14.51323 |
February | 672.00000 | 20.86360 | 26.10542 | -0.5029 | 16.46533 |
March | 744.00000 | 22.03452 | 32.14870 | -0.1580 | 7.29671 |
April | 720.00000 | 22.47426 | 38.75478 | 0.03344 | 7.62127 |
May | 744.00000 | 22.91517 | 51.09300 | -0.7007 | 16.98673 |
June | 720.00000 | 23.24221 | 58.45803 | -0.4951 | 12.09876 |
July | 744.00000 | 23.45988 | 62.27583 | -0.3687 | 8.79802 |
August | 744.00000 | 23.50850 | 60.53903 | -0.3596 | 8.70332 |
September | 720.00000 | 23.21126 | 48.30186 | -0.5704 | 15.36049 |
October | 744.00000 | 22.67260 | 37.15341 | 0.09337 | 6.72491 |
November | 720.00000 | 21.80814 | 33.65568 | -0.2215 | 8.49576 |
December | 744.00000 | 21.52867 | 26.31424 | -0.4006 | 9.93258 |
Annual Sum or Average | 8760.00000 | 22.39582 | 41.53681 | -0.3508 | 11.04093 |
Minimum of Months | 672.00000 | 20.86360 | 22.56844 | -0.7007 | 6.72491 |
Maximum of Months | 744.00000 | 23.50850 | 62.27583 | 0.09337 | 16.98673 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.28133 | 22.13577 | -0.4430 | 11.06746 |
February | 672.00000 | 21.13196 | 25.59049 | -0.4399 | 15.36022 |
March | 744.00000 | 22.44567 | 31.38032 | -0.0801 | 5.99911 |
April | 720.00000 | 22.84478 | 37.89293 | 0.07796 | 6.29312 |
May | 744.00000 | 23.29492 | 49.77847 | -0.6680 | 15.20233 |
June | 720.00000 | 23.49107 | 57.20158 | -0.5241 | 11.53917 |
July | 744.00000 | 23.62287 | 61.08508 | -0.4389 | 9.37420 |
August | 744.00000 | 23.65648 | 59.37807 | -0.4386 | 9.31589 |
September | 720.00000 | 23.52044 | 47.25980 | -0.5853 | 13.36423 |
October | 744.00000 | 23.11792 | 36.19316 | 0.14025 | 5.85764 |
November | 720.00000 | 22.37379 | 32.63688 | -0.0906 | 6.76751 |
December | 744.00000 | 21.90833 | 25.72967 | -0.2717 | 7.23680 |
Annual Sum or Average | 8760.00000 | 22.73356 | 40.60922 | -0.3128 | 9.73880 |
Minimum of Months | 672.00000 | 21.13196 | 22.13577 | -0.6680 | 5.85764 |
Maximum of Months | 744.00000 | 23.65648 | 61.08508 | 0.14025 | 15.36022 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.60539 | 31.38490 | -0.7596 | 17.82396 |
February | 672.00000 | 20.73718 | 34.83712 | -0.6595 | 15.48863 |
March | 744.00000 | 21.09056 | 40.48368 | -0.4794 | 10.85000 |
April | 720.00000 | 21.33782 | 44.62511 | -0.3119 | 8.53221 |
May | 744.00000 | 21.65182 | 51.60132 | -1.2421 | 38.70581 |
June | 720.00000 | 21.68547 | 52.94708 | -1.1415 | 34.12301 |
July | 744.00000 | 21.72763 | 53.23098 | -1.0825 | 31.45234 |
August | 744.00000 | 21.71935 | 53.59559 | -1.1060 | 32.49943 |
September | 720.00000 | 21.61241 | 49.33362 | -1.2500 | 39.43923 |
October | 744.00000 | 21.40390 | 45.39424 | -0.3134 | 7.90641 |
November | 720.00000 | 20.94212 | 42.34538 | -0.5343 | 12.12461 |
December | 744.00000 | 20.71335 | 35.25677 | -0.6965 | 15.97876 |
Annual Sum or Average | 8760.00000 | 21.27191 | 44.63657 | -0.7991 | 22.11499 |
Minimum of Months | 672.00000 | 20.60539 | 31.38490 | -1.2500 | 7.90641 |
Maximum of Months | 744.00000 | 21.72763 | 53.59559 | -0.3119 | 39.43923 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.47005 | 31.67294 | -0.8216 | 19.89334 |
February | 672.00000 | 20.48507 | 35.29932 | -0.7503 | 18.12794 |
March | 744.00000 | 20.88063 | 41.00867 | -0.5515 | 12.23312 |
April | 720.00000 | 21.37025 | 44.96516 | -0.3273 | 9.10472 |
May | 744.00000 | 22.06908 | 51.46926 | -1.1370 | 35.63669 |
June | 720.00000 | 22.36372 | 52.72788 | -0.9496 | 29.24838 |
July | 744.00000 | 22.61506 | 53.45695 | -0.8296 | 24.50613 |
August | 744.00000 | 22.49677 | 54.05118 | -0.8940 | 26.03269 |
September | 720.00000 | 21.94176 | 49.71492 | -1.1899 | 37.73276 |
October | 744.00000 | 21.22233 | 46.07127 | -0.3874 | 8.79888 |
November | 720.00000 | 20.76563 | 42.86475 | -0.5980 | 13.48426 |
December | 744.00000 | 20.52214 | 35.67440 | -0.7655 | 17.89303 |
Annual Sum or Average | 8760.00000 | 21.43940 | 44.96468 | -0.7670 | 21.06711 |
Minimum of Months | 672.00000 | 20.47005 | 31.67294 | -1.1899 | 8.79888 |
Maximum of Months | 744.00000 | 22.61506 | 54.05118 | -0.3273 | 37.73276 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.59283 | 28.46857 | -0.7058 | 16.16390 |
February | 672.00000 | 20.59748 | 31.99084 | -0.6667 | 15.66960 |
March | 744.00000 | 21.06098 | 37.93317 | -0.4837 | 10.19997 |
April | 720.00000 | 21.34650 | 42.63490 | -0.3512 | 8.16824 |
May | 744.00000 | 21.77864 | 49.67761 | -1.2901 | 40.68266 |
June | 720.00000 | 22.04788 | 53.45241 | -1.1388 | 33.90675 |
July | 744.00000 | 22.22621 | 55.99774 | -1.0561 | 30.18742 |
August | 744.00000 | 22.13870 | 55.63932 | -1.1007 | 31.95380 |
September | 720.00000 | 21.74851 | 48.57823 | -1.3137 | 41.80391 |
October | 744.00000 | 21.27307 | 42.90893 | -0.3728 | 8.05574 |
November | 720.00000 | 20.98718 | 39.27358 | -0.5020 | 10.84969 |
December | 744.00000 | 20.72633 | 32.62378 | -0.6410 | 14.02260 |
Annual Sum or Average | 8760.00000 | 21.38173 | 43.32778 | -0.8027 | 21.83522 |
Minimum of Months | 672.00000 | 20.59283 | 28.46857 | -1.3137 | 8.05574 |
Maximum of Months | 744.00000 | 22.22621 | 55.99774 | -0.3512 | 41.80391 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.58731 | 31.36497 | -0.7610 | 17.86158 |
February | 672.00000 | 20.72066 | 34.77417 | -0.6656 | 15.74034 |
March | 744.00000 | 21.16656 | 40.26245 | -0.4602 | 10.51268 |
April | 720.00000 | 21.36970 | 44.49729 | -0.3154 | 8.61733 |
May | 744.00000 | 21.70256 | 50.67592 | -1.2188 | 37.63952 |
June | 720.00000 | 21.70666 | 52.36384 | -1.1321 | 33.74909 |
July | 744.00000 | 21.74181 | 52.74372 | -1.0844 | 31.58838 |
August | 744.00000 | 21.73902 | 53.15537 | -1.1081 | 32.61305 |
September | 720.00000 | 21.65380 | 48.86956 | -1.2346 | 38.70487 |
October | 744.00000 | 21.45595 | 45.24767 | -0.3044 | 7.80435 |
November | 720.00000 | 20.92870 | 42.37569 | -0.5381 | 12.19938 |
December | 744.00000 | 20.68079 | 35.28704 | -0.7033 | 16.09971 |
Annual Sum or Average | 8760.00000 | 21.29106 | 44.34992 | -0.7948 | 21.96314 |
Minimum of Months | 672.00000 | 20.58731 | 31.36497 | -1.2346 | 7.80435 |
Maximum of Months | 744.00000 | 21.74181 | 53.15537 | -0.3044 | 38.70487 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.46089 | 31.62686 | -0.8224 | 19.96366 |
February | 672.00000 | 20.44941 | 35.26853 | -0.7608 | 18.53922 |
March | 744.00000 | 20.95113 | 40.76831 | -0.5338 | 11.74168 |
April | 720.00000 | 21.37114 | 44.88576 | -0.3381 | 9.02447 |
May | 744.00000 | 22.01985 | 50.72887 | -1.1429 | 34.81946 |
June | 720.00000 | 22.33458 | 52.42499 | -0.9534 | 28.76743 |
July | 744.00000 | 22.60925 | 53.23357 | -0.8355 | 24.60894 |
August | 744.00000 | 22.43470 | 53.90830 | -0.9191 | 26.15062 |
September | 720.00000 | 21.95399 | 49.14693 | -1.1839 | 36.99265 |
October | 744.00000 | 21.24095 | 45.95283 | -0.3865 | 8.51234 |
November | 720.00000 | 20.74962 | 42.89329 | -0.6033 | 13.60870 |
December | 744.00000 | 20.50982 | 35.67882 | -0.7694 | 18.05726 |
Annual Sum or Average | 8760.00000 | 21.42983 | 44.75856 | -0.7708 | 20.90512 |
Minimum of Months | 672.00000 | 20.44941 | 31.62686 | -1.1839 | 8.51234 |
Maximum of Months | 744.00000 | 22.60925 | 53.90830 | -0.3381 | 36.99265 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.52933 | 31.96767 | -0.8308 | 20.24273 |
February | 672.00000 | 20.64250 | 35.60331 | -0.7230 | 17.41965 |
March | 744.00000 | 20.98180 | 41.50671 | -0.5361 | 12.22291 |
April | 720.00000 | 21.27386 | 45.64563 | -0.3429 | 9.30253 |
May | 744.00000 | 21.63354 | 52.76979 | -1.2536 | 39.47490 |
June | 720.00000 | 21.67115 | 54.04392 | -1.1425 | 34.43620 |
July | 744.00000 | 21.72079 | 54.34266 | -1.0773 | 31.45974 |
August | 744.00000 | 21.70842 | 55.04262 | -1.1060 | 32.71211 |
September | 720.00000 | 21.57320 | 50.59466 | -1.2777 | 41.04614 |
October | 744.00000 | 21.32521 | 46.54096 | -0.3527 | 8.60365 |
November | 720.00000 | 20.83961 | 43.51872 | -0.5937 | 13.68506 |
December | 744.00000 | 20.62984 | 35.97297 | -0.7646 | 18.06967 |
Annual Sum or Average | 8760.00000 | 21.21403 | 45.68062 | -0.8342 | 23.25536 |
Minimum of Months | 672.00000 | 20.52933 | 31.96767 | -1.2777 | 8.60365 |
Maximum of Months | 744.00000 | 21.72079 | 55.04262 | -0.3429 | 41.04614 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.42583 | 32.22727 | -0.8871 | 22.31699 |
February | 672.00000 | 20.41046 | 36.06630 | -0.8119 | 20.21893 |
March | 744.00000 | 20.78122 | 42.05817 | -0.6086 | 13.74131 |
April | 720.00000 | 21.31392 | 45.93785 | -0.3577 | 10.01753 |
May | 744.00000 | 22.10101 | 52.29641 | -1.1304 | 36.31430 |
June | 720.00000 | 22.40697 | 53.28195 | -0.9286 | 29.91538 |
July | 744.00000 | 22.65055 | 53.86788 | -0.8061 | 24.89877 |
August | 744.00000 | 22.52965 | 54.79142 | -0.8766 | 26.38910 |
September | 720.00000 | 21.91077 | 50.79969 | -1.2140 | 39.49729 |
October | 744.00000 | 21.12076 | 47.32459 | -0.4342 | 9.76292 |
November | 720.00000 | 20.67568 | 44.04495 | -0.6566 | 15.15582 |
December | 744.00000 | 20.48171 | 36.36140 | -0.8262 | 19.96958 |
Annual Sum or Average | 8760.00000 | 21.40692 | 45.80419 | -0.7948 | 22.35313 |
Minimum of Months | 672.00000 | 20.41046 | 32.22727 | -1.2140 | 9.76292 |
Maximum of Months | 744.00000 | 22.65055 | 54.79142 | -0.3577 | 39.49729 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.98745 | 32.55870 | -0.6228 | 14.62153 |
February | 672.00000 | 21.14455 | 35.68451 | -0.5166 | 12.20693 |
March | 744.00000 | 21.29537 | 40.88354 | -0.4081 | 9.95346 |
April | 720.00000 | 21.37930 | 44.93665 | -0.3113 | 8.62730 |
May | 744.00000 | 21.65340 | 51.79975 | -1.2738 | 40.32877 |
June | 720.00000 | 21.67879 | 54.11635 | -1.1971 | 36.67625 |
July | 744.00000 | 21.70987 | 55.20590 | -1.1469 | 34.35331 |
August | 744.00000 | 21.70532 | 54.94496 | -1.1512 | 34.63478 |
September | 720.00000 | 21.64100 | 49.55998 | -1.2489 | 39.64668 |
October | 744.00000 | 21.53989 | 45.21915 | -0.2511 | 7.58302 |
November | 720.00000 | 21.19021 | 42.47113 | -0.4450 | 10.71916 |
December | 744.00000 | 20.99631 | 36.17261 | -0.5863 | 13.98285 |
Annual Sum or Average | 8760.00000 | 21.41162 | 45.34798 | -0.7649 | 22.00292 |
Minimum of Months | 672.00000 | 20.98745 | 32.55870 | -1.2738 | 7.58302 |
Maximum of Months | 744.00000 | 21.70987 | 55.20590 | -0.2511 | 40.32877 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.42985 | 23.96173 | -0.1792 | 9.03940 |
February | 672.00000 | 22.23344 | 26.89682 | -0.1798 | 14.05953 |
March | 744.00000 | 23.52575 | 32.03197 | 0.19427 | 6.44763 |
April | 720.00000 | 23.73092 | 37.89690 | 0.32797 | 7.84199 |
May | 744.00000 | 23.91356 | 48.87311 | -0.3698 | 8.21003 |
June | 720.00000 | 23.95588 | 56.23127 | -0.2519 | 6.56873 |
July | 744.00000 | 23.97651 | 60.28437 | -0.2011 | 5.90806 |
August | 744.00000 | 23.96649 | 58.90677 | -0.2301 | 6.20033 |
September | 720.00000 | 23.89297 | 47.35051 | -0.3886 | 8.74146 |
October | 744.00000 | 23.72592 | 36.60419 | 0.30968 | 7.29744 |
November | 720.00000 | 23.35721 | 33.37310 | 0.15583 | 6.94632 |
December | 744.00000 | 23.11474 | 27.28747 | 0.01063 | 6.06463 |
Annual Sum or Average | 8760.00000 | 23.49283 | 40.89069 | -0.0662 | 7.72826 |
Minimum of Months | 672.00000 | 22.23344 | 23.96173 | -0.3886 | 5.90806 |
Maximum of Months | 744.00000 | 23.97651 | 60.28437 | 0.32797 | 14.05953 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.68193 | 23.13447 | -0.0793 | 8.60242 |
February | 672.00000 | 22.43725 | 25.95229 | -0.0913 | 14.07524 |
March | 744.00000 | 23.71364 | 30.94295 | 0.28028 | 7.08846 |
April | 720.00000 | 23.85685 | 36.91367 | 0.39637 | 8.70582 |
May | 744.00000 | 23.96647 | 48.07509 | -0.3012 | 7.16226 |
June | 720.00000 | 23.98197 | 55.62402 | -0.1996 | 6.01587 |
July | 744.00000 | 23.99074 | 59.75128 | -0.1560 | 5.56056 |
August | 744.00000 | 23.98705 | 58.33764 | -0.1818 | 5.77008 |
September | 720.00000 | 23.95005 | 46.60737 | -0.3221 | 7.56746 |
October | 744.00000 | 23.85929 | 35.55866 | 0.38076 | 8.20666 |
November | 720.00000 | 23.55307 | 32.33765 | 0.24316 | 7.45420 |
December | 744.00000 | 23.36888 | 26.26655 | 0.11318 | 6.08124 |
Annual Sum or Average | 8760.00000 | 23.61948 | 40.04168 | 0.00743 | 7.64118 |
Minimum of Months | 672.00000 | 22.43725 | 23.13447 | -0.3221 | 5.56056 |
Maximum of Months | 744.00000 | 23.99074 | 59.75128 | 0.39637 | 14.07524 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.86207 | 22.44500 | 0.57719 | 21.77671 |
February | 672.00000 | 22.44397 | 26.09261 | 0.54351 | 26.69406 |
March | 744.00000 | 23.76059 | 29.41144 | 0.93051 | 25.86626 |
April | 720.00000 | 23.83662 | 35.66692 | 1.04594 | 30.40143 |
May | 744.00000 | 23.91553 | 47.08996 | 0.64468 | 18.38469 |
June | 720.00000 | 23.95280 | 54.72805 | 0.76647 | 21.53504 |
July | 744.00000 | 23.96850 | 58.83006 | 0.81973 | 22.92903 |
August | 744.00000 | 23.96089 | 57.38208 | 0.78435 | 21.84800 |
September | 720.00000 | 23.91895 | 45.56439 | 0.63185 | 17.95575 |
October | 744.00000 | 23.84004 | 34.23456 | 1.02596 | 29.27756 |
November | 720.00000 | 23.63830 | 30.90857 | 0.88898 | 25.63588 |
December | 744.00000 | 23.65508 | 24.52078 | 0.79068 | 21.06280 |
Annual Sum or Average | 8760.00000 | 23.65390 | 38.98072 | 0.78899 | 23.58568 |
Minimum of Months | 672.00000 | 22.44397 | 22.44500 | 0.54351 | 17.95575 |
Maximum of Months | 744.00000 | 23.96850 | 58.83006 | 1.04594 | 30.40143 |
Report: OccupantComfortDataSummaryMonthly
For: STORAGE_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.68214 | 16.83769 | -0.6983 | 16.17129 |
February | 672.00000 | 20.01031 | 21.06521 | -0.8045 | 22.29278 |
March | 744.00000 | 21.07528 | 27.13400 | -0.4965 | 10.34225 |
April | 720.00000 | 21.43543 | 34.23541 | -0.3449 | 8.44761 |
May | 744.00000 | 22.21396 | 46.23118 | -1.1505 | 33.47551 |
June | 720.00000 | 22.94521 | 53.18321 | -0.8469 | 21.12466 |
July | 744.00000 | 23.27147 | 56.92048 | -0.7061 | 15.73995 |
August | 744.00000 | 23.21289 | 55.41756 | -0.7377 | 16.66775 |
September | 720.00000 | 22.63313 | 43.39664 | -1.0182 | 28.32323 |
October | 744.00000 | 21.46446 | 32.74386 | -0.3368 | 7.59337 |
November | 720.00000 | 21.17453 | 28.38290 | -0.4660 | 10.17239 |
December | 744.00000 | 21.00016 | 20.53328 | -0.5899 | 12.35739 |
Annual Sum or Average | 8760.00000 | 21.77115 | 36.42775 | -0.6822 | 16.84660 |
Minimum of Months | 672.00000 | 20.01031 | 16.83769 | -1.1505 | 7.59337 |
Maximum of Months | 744.00000 | 23.27147 | 56.92048 | -0.3368 | 33.47551 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.80948 | 19.95961 | -0.6289 | 13.74361 |
February | 672.00000 | 20.45260 | 24.04730 | -0.6701 | 16.58273 |
March | 744.00000 | 21.11258 | 30.24423 | -0.4673 | 9.72862 |
April | 720.00000 | 21.55397 | 37.21346 | -0.3058 | 7.81118 |
May | 744.00000 | 22.27532 | 49.26902 | -1.1297 | 32.32520 |
June | 720.00000 | 22.97406 | 56.17547 | -0.8357 | 20.63111 |
July | 744.00000 | 23.33443 | 59.68402 | -0.6832 | 15.01031 |
August | 744.00000 | 23.22647 | 58.39448 | -0.7315 | 16.42141 |
September | 720.00000 | 22.68405 | 46.44146 | -0.9995 | 27.66082 |
October | 744.00000 | 21.36910 | 36.07113 | -0.3553 | 7.78539 |
November | 720.00000 | 21.09579 | 31.73819 | -0.4696 | 9.96420 |
December | 744.00000 | 21.00157 | 23.74396 | -0.5612 | 11.64421 |
Annual Sum or Average | 8760.00000 | 21.83262 | 39.50340 | -0.6530 | 15.76098 |
Minimum of Months | 672.00000 | 20.45260 | 19.95961 | -1.1297 | 7.78539 |
Maximum of Months | 744.00000 | 23.33443 | 59.68402 | -0.3058 | 32.32520 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.68883 | 17.81753 | -0.6935 | 16.15551 |
February | 672.00000 | 20.15313 | 21.96320 | -0.7614 | 20.72719 |
March | 744.00000 | 21.11254 | 28.12443 | -0.4688 | 9.85171 |
April | 720.00000 | 21.59809 | 34.88878 | -0.2810 | 7.95324 |
May | 744.00000 | 22.36252 | 46.79542 | -1.0538 | 29.45019 |
June | 720.00000 | 23.13134 | 53.34741 | -0.7273 | 17.70203 |
July | 744.00000 | 23.44854 | 56.97740 | -0.5866 | 12.76517 |
August | 744.00000 | 23.30932 | 55.81851 | -0.6488 | 14.38711 |
September | 720.00000 | 22.59047 | 44.30776 | -0.9852 | 27.98036 |
October | 744.00000 | 21.35802 | 33.92585 | -0.3428 | 7.74670 |
November | 720.00000 | 21.07141 | 29.63591 | -0.4807 | 10.38861 |
December | 744.00000 | 21.00337 | 21.60291 | -0.5869 | 12.30452 |
Annual Sum or Average | 8760.00000 | 21.82960 | 37.18709 | -0.6339 | 15.57144 |
Minimum of Months | 672.00000 | 20.15313 | 17.81753 | -1.0538 | 7.74670 |
Maximum of Months | 744.00000 | 23.44854 | 56.97740 | -0.2810 | 29.45019 |
Report: OccupantComfortDataSummaryMonthly
For: MECH_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.76355 | 16.45731 | -0.6620 | 14.91651 |
February | 672.00000 | 20.12994 | 20.66763 | -0.7642 | 20.89847 |
March | 744.00000 | 21.20985 | 26.52793 | -0.4570 | 9.65365 |
April | 720.00000 | 21.66671 | 33.41647 | -0.2904 | 7.80668 |
May | 744.00000 | 22.52704 | 45.05949 | -1.0544 | 29.16071 |
June | 720.00000 | 23.20086 | 52.04880 | -0.7679 | 18.32549 |
July | 744.00000 | 23.51645 | 55.74759 | -0.6299 | 13.57472 |
August | 744.00000 | 23.48548 | 54.18413 | -0.6527 | 14.16845 |
September | 720.00000 | 22.97084 | 42.23460 | -0.9131 | 24.02031 |
October | 744.00000 | 21.86119 | 31.66973 | -0.2499 | 6.52638 |
November | 720.00000 | 21.34262 | 27.69727 | -0.4186 | 9.44991 |
December | 744.00000 | 21.00849 | 20.15411 | -0.5688 | 11.83933 |
Annual Sum or Average | 8760.00000 | 21.98521 | 35.57374 | -0.6181 | 14.98154 |
Minimum of Months | 672.00000 | 20.12994 | 16.45731 | -1.0544 | 6.52638 |
Maximum of Months | 744.00000 | 23.51645 | 55.74759 | -0.2499 | 29.16071 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.288390E+09 | 5555.15 | 01-JAN-09:02 | 68.65 | 0.136017E+10 | 0.00 | 0.164856E+10 | 0.44 | 4.72 | 01-JAN-19:03 | 0.00 | 0.00 |
February | 0.616991E+09 | 13740.00 | 24-FEB-16:03 | 116.32 | 0.290998E+10 | 0.00 | 0.352697E+10 | 0.82 | 4.72 | 01-FEB-14:30 | 0.00 | 0.00 |
March | 0.392172E+10 | 52311.69 | 25-MAR-15:01 | 295.40 | 0.182484E+11 | 0.00 | 0.221701E+11 | 1.87 | 4.72 | 04-MAR-09:05 | 0.00 | 0.00 |
April | 0.223999E+11 | 125878.63 | 18-APR-15:03 | 462.41 | 0.954528E+11 | 0.00 | 0.117853E+12 | 2.96 | 4.72 | 01-APR-08:03 | 0.00 | 0.00 |
May | 0.480087E+11 | 124720.47 | 31-MAY-18:03 | 734.70 | 0.208886E+12 | 0.00 | 0.256895E+12 | 4.51 | 4.72 | 01-MAY-00:20 | 0.00 | 0.00 |
June | 0.119703E+12 | 179092.60 | 11-JUN-15:03 | 712.50 | 0.490562E+12 | 0.00 | 0.610265E+12 | 4.29 | 4.72 | 01-JUN-01:30 | 0.00 | 0.00 |
July | 0.162240E+12 | 213093.63 | 26-JUL-18:03 | 744.00 | 0.674749E+12 | 0.00 | 0.836989E+12 | 4.28 | 4.72 | 13-JUL-05:00 | 0.00 | 0.00 |
August | 0.142942E+12 | 211427.18 | 04-AUG-15:13 | 744.00 | 0.593500E+12 | 0.00 | 0.736441E+12 | 4.32 | 4.72 | 06-AUG-08:20 | 0.00 | 0.00 |
September | 0.648273E+11 | 148908.07 | 06-SEP-15:03 | 686.75 | 0.269589E+12 | 0.00 | 0.334417E+12 | 4.26 | 4.72 | 02-SEP-00:10 | 0.00 | 0.00 |
October | 0.120450E+11 | 87207.61 | 20-OCT-15:01 | 561.06 | 0.554717E+11 | 0.00 | 0.675166E+11 | 3.54 | 4.72 | 01-OCT-06:30 | 0.00 | 0.00 |
November | 0.321870E+10 | 38573.21 | 03-NOV-15:01 | 252.35 | 0.150999E+11 | 0.00 | 0.183186E+11 | 1.65 | 4.72 | 01-NOV-05:20 | 0.00 | 0.00 |
December | 0.457222E+09 | 9518.00 | 02-DEC-09:01 | 91.69 | 0.215645E+10 | 0.00 | 0.261367E+10 | 0.58 | 4.72 | 01-DEC-10:00 | 0.00 | 0.00 |
Annual Sum or Average | 0.580668E+12 | 5469.83 | 0.242799E+13 | 0.00 | 0.300865E+13 | 2.80 | 0.00 | 0.00 | ||||
Minimum of Months | 0.288390E+09 | 5555.15 | 68.65 | 0.136017E+10 | 0.00 | 0.164856E+10 | 0.44 | 4.72 | 0.00 | 0.00 | ||
Maximum of Months | 0.162240E+12 | 213093.63 | 744.00 | 0.674749E+12 | 0.00 | 0.836989E+12 | 4.51 | 4.72 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.468240E+12 | 0.00 | 744.00 | 590514.81 | 31-JAN-04:03 | 0.00 | 36.86 | 60.00 | 1.76 | 0.00 | 0.27 | 0.90 | 31-JAN-04:03 |
February | 0.323593E+12 | 0.00 | 671.33 | 621924.34 | 02-FEB-06:00 | 0.00 | 38.80 | 60.00 | 1.35 | 0.00 | 0.20 | 0.95 | 02-FEB-06:00 |
March | 0.128587E+12 | 0.00 | 718.20 | 212060.86 | 05-MAR-19:02 | 0.00 | 37.46 | 58.91 | 0.50 | 0.00 | 0.07 | 0.32 | 05-MAR-19:02 |
April | 0.693853E+11 | 0.00 | 589.85 | 172311.85 | 03-APR-08:62 | 0.00 | 36.23 | 54.18 | 0.27 | 0.00 | 0.04 | 0.26 | 03-APR-08:62 |
May | 0.462652E+11 | 0.00 | 380.99 | 139339.26 | 01-MAY-18:04 | 0.00 | 28.69 | 43.93 | 0.13 | 0.00 | 0.03 | 0.21 | 01-MAY-18:04 |
June | 0.278542E+11 | 0.00 | 185.26 | 128438.03 | 03-JUN-08:03 | 0.00 | 29.58 | 37.69 | 0.08 | 0.00 | 0.02 | 0.20 | 03-JUN-08:03 |
July | 0.507614E+10 | 0.00 | 57.01 | 71809.09 | 24-JUL-05:00 | 0.00 | 31.27 | 33.82 | 0.01 | 0.00 | 0.00 | 0.11 | 24-JUL-05:00 |
August | 0.116772E+11 | 0.00 | 104.29 | 99721.70 | 07-AUG-05:50 | 0.00 | 30.19 | 34.81 | 0.03 | 0.00 | 0.01 | 0.15 | 07-AUG-05:50 |
September | 0.438654E+11 | 0.00 | 335.51 | 133863.47 | 27-SEP-08:07 | 0.00 | 31.37 | 43.88 | 0.14 | 0.00 | 0.03 | 0.20 | 27-SEP-08:07 |
October | 0.867190E+11 | 0.00 | 664.54 | 154129.54 | 13-OCT-15:03 | 0.00 | 37.53 | 56.94 | 0.31 | 0.00 | 0.05 | 0.24 | 13-OCT-15:03 |
November | 0.168480E+12 | 0.00 | 712.36 | 567626.78 | 26-NOV-07:00 | 0.00 | 36.90 | 59.65 | 0.66 | 0.00 | 0.10 | 0.87 | 26-NOV-07:00 |
December | 0.265694E+12 | 0.00 | 744.00 | 290053.07 | 09-DEC-09:06 | 0.00 | 37.10 | 60.00 | 1.03 | 0.00 | 0.15 | 0.44 | 09-DEC-09:06 |
Annual Sum or Average | 0.164544E+13 | 0.00 | 5907.33 | 0.00 | 34.30 | 50.25 | 0.52 | 0.00 | 0.08 | ||||
Minimum of Months | 0.507614E+10 | 0.00 | 57.01 | 71809.09 | 0.00 | 28.69 | 33.82 | 0.01 | 0.00 | 0.00 | 0.11 | ||
Maximum of Months | 0.468240E+12 | 0.00 | 744.00 | 621924.34 | 0.00 | 38.80 | 60.00 | 1.76 | 0.00 | 0.27 | 0.95 |
Report: DXReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 |
March | 0.212226E+09 | 0.00 | 17.33 | 0.212226E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8515.76 | 19-MAR-16:00 | 8515.76 | 19-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.322158E+10 | 0.00 | 81.50 | 0.259043E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26462.51 | 18-APR-08:50 | 18719.58 | 15-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.743526E+10 | 0.00 | 247.83 | 0.563762E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29501.61 | 29-MAY-15:01 | 18656.86 | 31-MAY-13:00 | 0.00 | 0.00 | 0.00 |
June | 0.238818E+11 | 0.00 | 410.83 | 0.157026E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 40758.49 | 26-JUN-06:55 | 20103.12 | 11-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.360767E+11 | 0.00 | 538.67 | 0.207031E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 40259.68 | 17-JUL-18:50 | 18981.82 | 26-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.295340E+11 | 0.00 | 494.67 | 0.173761E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 42516.66 | 31-AUG-18:03 | 20399.35 | 04-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.108110E+11 | 0.00 | 280.33 | 0.934643E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29549.17 | 11-SEP-08:15 | 19478.96 | 06-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.651794E+09 | 0.00 | 41.00 | 0.651794E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15305.42 | 20-OCT-15:01 | 15305.42 | 20-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 24319535.87 | 0.00 | 7.00 | 24319535.87 | 0.00 | 0.00 | 0.00 | 0.00 | 2178.01 | 03-NOV-15:04 | 2178.01 | 03-NOV-15:04 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.111849E+12 | 0.00 | 2119.17 | 0.722446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.360767E+11 | 0.00 | 538.67 | 0.207031E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 42516.66 | 20399.35 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 827029.49 | 0.00 | 3.11 | 827029.49 | 0.00 | 0.00 | 0.00 | 0.00 | 265.97 | 17-JAN-23:50 | 265.97 | 17-JAN-23:50 | 0.00 | 0.00 | 0.00 |
February | 420853.21 | 0.00 | 4.11 | 420853.21 | 0.00 | 0.00 | 0.00 | 0.00 | 63.81 | 08-FEB-01:40 | 63.81 | 08-FEB-01:40 | 0.00 | 0.00 | 0.00 |
March | 0.296321E+10 | 0.00 | 27.17 | 0.296321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73077.36 | 19-MAR-16:20 | 73077.36 | 19-MAR-16:20 | 0.00 | 0.00 | 0.00 |
April | 0.461052E+11 | 0.00 | 121.17 | 0.386240E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 302330.66 | 18-APR-10:33 | 211147.86 | 15-APR-17:15 | 0.00 | 0.00 | 0.00 |
May | 0.107628E+12 | 0.00 | 360.17 | 0.875143E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 306217.52 | 30-MAY-19:20 | 218122.93 | 31-MAY-18:10 | 0.00 | 0.00 | 0.00 |
June | 0.328754E+12 | 0.00 | 540.95 | 0.224808E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 392941.16 | 26-JUN-18:10 | 248612.10 | 26-JUN-18:10 | 0.00 | 0.00 | 0.00 |
July | 0.477460E+12 | 0.00 | 691.33 | 0.285823E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 570571.76 | 03-JUL-21:30 | 242767.79 | 03-JUL-18:40 | 0.00 | 0.00 | 0.00 |
August | 0.413147E+12 | 0.00 | 645.06 | 0.251190E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 582009.16 | 03-AUG-22:00 | 240497.15 | 04-AUG-15:25 | 0.00 | 0.00 | 0.00 |
September | 0.151579E+12 | 0.00 | 380.92 | 0.138980E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 314331.36 | 11-SEP-19:20 | 241618.27 | 07-SEP-18:05 | 0.00 | 0.00 | 0.00 |
October | 0.104650E+11 | 0.00 | 70.50 | 0.104650E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 141932.70 | 20-OCT-15:04 | 141932.70 | 20-OCT-15:04 | 0.00 | 0.00 | 0.00 |
November | 0.480727E+09 | 0.00 | 13.67 | 0.480727E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23065.85 | 03-NOV-15:20 | 23065.85 | 03-NOV-15:20 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.153858E+13 | 0.00 | 2858.14 | 0.104085E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.477460E+12 | 0.00 | 691.33 | 0.285823E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 582009.16 | 248612.10 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 11947728.69 | 0.00 | 2.37 | 8174068.53 | 0.00 | 0.00 | 0.00 | 0.00 | 13422.09 | 02-JAN-16:01 | 13422.09 | 02-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.170058E+09 | 0.00 | 25.03 | 96829822.65 | 0.00 | 0.00 | 0.00 | 0.00 | 18090.78 | 17-FEB-16:01 | 18090.78 | 17-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.581102E+09 | 0.00 | 104.70 | 0.366809E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18215.66 | 10-MAR-16:01 | 18215.66 | 10-MAR-16:01 | 0.00 | 0.00 | 0.00 |
April | 0.281369E+10 | 0.00 | 298.61 | 0.179277E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18216.34 | 30-APR-18:01 | 18216.34 | 30-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.500199E+10 | 0.00 | 586.65 | 0.246007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18279.72 | 11-MAY-18:01 | 18215.16 | 06-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.839511E+10 | 0.00 | 622.26 | 0.452386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19501.32 | 25-JUN-08:61 | 16142.11 | 06-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.105912E+11 | 0.00 | 702.11 | 0.572579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19797.95 | 20-JUL-08:61 | 16146.62 | 11-JUL-18:01 | 0.00 | 0.00 | 0.00 |
August | 0.950185E+10 | 0.00 | 697.10 | 0.484468E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21009.84 | 31-AUG-08:61 | 15959.56 | 06-AUG-08:61 | 0.00 | 0.00 | 0.00 |
September | 0.588425E+10 | 0.00 | 525.95 | 0.326764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18216.22 | 20-SEP-18:01 | 18216.22 | 20-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.138207E+10 | 0.00 | 230.84 | 0.734365E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17004.13 | 02-OCT-15:01 | 16128.95 | 21-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.271021E+09 | 0.00 | 57.66 | 0.151522E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18210.83 | 12-NOV-16:01 | 18210.83 | 12-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 17058917.10 | 0.00 | 4.24 | 13209977.61 | 0.00 | 0.00 | 0.00 | 0.00 | 18031.89 | 01-DEC-16:01 | 18031.89 | 01-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.446213E+11 | 0.00 | 3857.53 | 0.239857E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 11947728.69 | 0.00 | 2.37 | 8174068.53 | 0.00 | 0.00 | 0.00 | 0.00 | 13422.09 | 13422.09 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.105912E+11 | 0.00 | 702.11 | 0.572579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21009.84 | 18216.34 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 445746.74 | 0.00 | 0.15 | 283257.82 | 0.00 | 0.00 | 0.00 | 0.00 | 1980.23 | 13-JAN-16:03 | 1423.11 | 02-JAN-16:04 | 0.00 | 0.00 | 0.00 |
February | 43381720.19 | 0.00 | 8.26 | 20906650.51 | 0.00 | 0.00 | 0.00 | 0.00 | 12761.82 | 25-FEB-16:01 | 12761.82 | 25-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.194071E+09 | 0.00 | 46.92 | 0.116886E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17268.82 | 21-MAR-18:01 | 17268.82 | 21-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.173919E+10 | 0.00 | 210.65 | 0.104927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18300.62 | 16-APR-21:51 | 18157.99 | 29-APR-18:41 | 0.00 | 0.00 | 0.00 |
May | 0.339015E+10 | 0.00 | 460.37 | 0.147853E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19853.16 | 20-MAY-18:41 | 19853.16 | 20-MAY-18:41 | 0.00 | 0.00 | 0.00 |
June | 0.662290E+10 | 0.00 | 481.08 | 0.363464E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22361.87 | 26-JUN-08:11 | 18121.64 | 16-JUN-16:32 | 0.00 | 0.00 | 0.00 |
July | 0.802168E+10 | 0.00 | 506.10 | 0.445769E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20777.55 | 02-JUL-08:51 | 17340.11 | 23-JUL-21:51 | 0.00 | 0.00 | 0.00 |
August | 0.670402E+10 | 0.00 | 505.67 | 0.331058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22520.95 | 03-AUG-07:51 | 17380.37 | 11-AUG-18:11 | 0.00 | 0.00 | 0.00 |
September | 0.376176E+10 | 0.00 | 390.23 | 0.186289E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18652.46 | 11-SEP-08:51 | 16415.91 | 12-SEP-21:11 | 0.00 | 0.00 | 0.00 |
October | 0.460256E+09 | 0.00 | 118.15 | 0.203769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17117.47 | 02-OCT-15:01 | 16207.50 | 10-OCT-16:51 | 0.00 | 0.00 | 0.00 |
November | 80292019.55 | 0.00 | 19.08 | 42452035.45 | 0.00 | 0.00 | 0.00 | 0.00 | 15574.59 | 03-NOV-15:01 | 15574.59 | 03-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 803480.63 | 0.00 | 0.25 | 386347.61 | 0.00 | 0.00 | 0.00 | 0.00 | 1656.07 | 14-DEC-16:04 | 1337.56 | 07-DEC-16:04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.310190E+11 | 0.00 | 2746.91 | 0.161783E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 445746.74 | 0.00 | 0.15 | 283257.82 | 0.00 | 0.00 | 0.00 | 0.00 | 1656.07 | 1337.56 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.802168E+10 | 0.00 | 506.10 | 0.445769E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22520.95 | 19853.16 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 |
February | 54434042.77 | 0.00 | 3.62 | 54434042.77 | 0.00 | 0.00 | 0.00 | 0.00 | 10930.25 | 25-FEB-16:04 | 10930.25 | 25-FEB-16:04 | 0.00 | 0.00 | 0.00 |
March | 0.506144E+10 | 0.00 | 138.41 | 0.451867E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37682.08 | 24-MAR-13:00 | 37682.08 | 24-MAR-13:00 | 0.00 | 0.00 | 0.00 |
April | 0.149769E+11 | 0.00 | 292.89 | 0.878031E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50880.70 | 15-APR-13:30 | 44929.05 | 15-APR-13:30 | 0.00 | 0.00 | 0.00 |
May | 0.272912E+11 | 0.00 | 608.97 | 0.111987E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 37433.33 | 06-MAY-12:50 | 26187.25 | 03-MAY-13:25 | 0.00 | 0.00 | 0.00 |
June | 0.379057E+11 | 0.00 | 652.46 | 0.147206E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 39501.82 | 26-JUN-12:30 | 26208.12 | 26-JUN-12:50 | 0.00 | 0.00 | 0.00 |
July | 0.470862E+11 | 0.00 | 734.01 | 0.187972E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 42419.00 | 30-JUL-13:30 | 30940.04 | 30-JUL-13:30 | 0.00 | 0.00 | 0.00 |
August | 0.482613E+11 | 0.00 | 740.44 | 0.206574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 47435.87 | 29-AUG-13:30 | 39436.54 | 29-AUG-13:30 | 0.00 | 0.00 | 0.00 |
September | 0.398317E+11 | 0.00 | 593.40 | 0.218532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 57393.47 | 07-SEP-13:00 | 54347.95 | 06-SEP-12:50 | 0.00 | 0.00 | 0.00 |
October | 0.214435E+11 | 0.00 | 423.57 | 0.177219E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 57532.43 | 20-OCT-12:40 | 50401.45 | 20-OCT-11:10 | 0.00 | 0.00 | 0.00 |
November | 0.605362E+10 | 0.00 | 141.50 | 0.448688E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55536.35 | 04-NOV-12:30 | 49821.51 | 04-NOV-11:20 | 0.00 | 0.00 | 0.00 |
December | 42033819.82 | 0.00 | 2.33 | 42033819.82 | 0.00 | 0.00 | 0.00 | 0.00 | 7934.53 | 07-DEC-14:40 | 7934.53 | 07-DEC-14:40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.248008E+12 | 0.00 | 4331.61 | 0.122831E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.482613E+11 | 0.00 | 740.44 | 0.218532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 57532.43 | 54347.95 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 17941576.86 | 0.00 | 1.51 | 12917953.14 | 0.00 | 0.00 | 0.00 | 0.00 | 25373.79 | 01-JAN-09:02 | 20097.48 | 01-JAN-09:02 | 0.00 | 0.00 | 0.00 |
February | 0.114159E+09 | 0.00 | 11.89 | 65960948.81 | 0.00 | 0.00 | 0.00 | 0.00 | 68949.84 | 26-FEB-09:02 | 68949.84 | 26-FEB-09:02 | 0.00 | 0.00 | 0.00 |
March | 0.318039E+10 | 0.00 | 133.44 | 0.149987E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 88506.06 | 24-MAR-18:01 | 88506.06 | 24-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.123480E+11 | 0.00 | 287.66 | 0.712377E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95314.96 | 16-APR-21:51 | 92510.94 | 30-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.321907E+11 | 0.00 | 453.37 | 0.179686E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 100914.47 | 11-MAY-21:42 | 93925.04 | 06-MAY-19:31 | 0.00 | 0.00 | 0.00 |
June | 0.480773E+11 | 0.00 | 469.44 | 0.290844E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 115938.54 | 26-JUN-08:11 | 86448.03 | 21-JUN-21:01 | 0.00 | 0.00 | 0.00 |
July | 0.521400E+11 | 0.00 | 454.19 | 0.308387E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 106548.10 | 02-JUL-08:51 | 84553.66 | 22-JUL-21:31 | 0.00 | 0.00 | 0.00 |
August | 0.462242E+11 | 0.00 | 443.56 | 0.261200E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 121119.09 | 03-AUG-07:51 | 85785.79 | 11-AUG-18:11 | 0.00 | 0.00 | 0.00 |
September | 0.288645E+11 | 0.00 | 435.62 | 0.160348E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 98405.85 | 11-SEP-21:51 | 92026.54 | 19-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.844338E+10 | 0.00 | 318.65 | 0.401789E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 88221.15 | 12-OCT-18:02 | 88221.15 | 12-OCT-18:02 | 0.00 | 0.00 | 0.00 |
November | 0.355329E+10 | 0.00 | 137.29 | 0.132574E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 86344.16 | 04-NOV-18:01 | 86344.16 | 04-NOV-18:01 | 0.00 | 0.00 | 0.00 |
December | 23804994.42 | 0.00 | 0.85 | 20536925.52 | 0.00 | 0.00 | 0.00 | 0.00 | 34566.71 | 03-DEC-09:02 | 33154.42 | 02-DEC-09:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.235178E+12 | 0.00 | 3147.45 | 0.134113E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 17941576.86 | 0.00 | 0.85 | 12917953.14 | 0.00 | 0.00 | 0.00 | 0.00 | 25373.79 | 20097.48 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.521400E+11 | 0.00 | 469.44 | 0.308387E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 121119.09 | 93925.04 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 7715977.07 | 0.00 | 3.41 | 2161835.99 | 0.00 | 0.00 | 0.00 | 0.00 | 4321.60 | 12-JAN-16:01 | 3240.49 | 12-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.113544E+09 | 0.00 | 22.47 | 64084499.16 | 0.00 | 0.00 | 0.00 | 0.00 | 15521.59 | 21-FEB-09:02 | 15521.59 | 21-FEB-09:02 | 0.00 | 0.00 | 0.00 |
March | 0.559293E+09 | 0.00 | 114.55 | 0.317923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16624.01 | 22-MAR-15:01 | 16624.01 | 22-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.241340E+10 | 0.00 | 302.68 | 0.138449E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16625.10 | 30-APR-18:01 | 16625.10 | 30-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.533991E+10 | 0.00 | 625.53 | 0.260079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16623.76 | 06-MAY-18:01 | 16623.76 | 06-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.856265E+10 | 0.00 | 646.57 | 0.469420E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17670.14 | 14-JUN-08:62 | 14713.30 | 07-JUN-08:61 | 0.00 | 0.00 | 0.00 |
July | 0.103696E+11 | 0.00 | 716.95 | 0.560609E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18102.24 | 20-JUL-08:61 | 14731.10 | 17-JUL-08:61 | 0.00 | 0.00 | 0.00 |
August | 0.918999E+10 | 0.00 | 712.95 | 0.464582E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19211.82 | 31-AUG-08:61 | 14707.15 | 20-AUG-08:62 | 0.00 | 0.00 | 0.00 |
September | 0.593432E+10 | 0.00 | 551.93 | 0.328332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16624.87 | 20-SEP-18:01 | 16624.87 | 20-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.118724E+10 | 0.00 | 248.13 | 0.540770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16163.87 | 02-OCT-15:01 | 14722.45 | 21-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.232705E+09 | 0.00 | 63.11 | 0.111950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15099.31 | 12-NOV-09:02 | 15099.31 | 12-NOV-09:02 | 0.00 | 0.00 | 0.00 |
December | 34725589.87 | 0.00 | 9.74 | 18581326.61 | 0.00 | 0.00 | 0.00 | 0.00 | 11586.01 | 03-DEC-09:02 | 11586.01 | 03-DEC-09:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.439451E+11 | 0.00 | 4018.03 | 0.232702E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 7715977.07 | 0.00 | 3.41 | 2161835.99 | 0.00 | 0.00 | 0.00 | 0.00 | 4321.60 | 3240.49 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.103696E+11 | 0.00 | 716.95 | 0.560609E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19211.82 | 16625.10 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 565753.21 | 0.00 | 0.15 | 191700.18 | 0.00 | 0.00 | 0.00 | 0.00 | 2193.21 | 13-JAN-09:04 | 932.07 | 13-JAN-09:04 | 0.00 | 0.00 | 0.00 |
February | 23131942.79 | 0.00 | 7.24 | 8794177.93 | 0.00 | 0.00 | 0.00 | 0.00 | 11228.88 | 24-FEB-09:01 | 11228.88 | 24-FEB-09:01 | 0.00 | 0.00 | 0.00 |
March | 0.179145E+09 | 0.00 | 47.71 | 99604231.03 | 0.00 | 0.00 | 0.00 | 0.00 | 13848.42 | 19-MAR-15:01 | 13848.42 | 19-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.143409E+10 | 0.00 | 197.48 | 0.784021E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17437.42 | 16-APR-08:51 | 16092.13 | 30-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.390703E+10 | 0.00 | 509.14 | 0.187883E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19792.38 | 31-MAY-08:32 | 16698.84 | 31-MAY-08:32 | 0.00 | 0.00 | 0.00 |
June | 0.682501E+10 | 0.00 | 509.59 | 0.380955E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21008.12 | 26-JUN-07:52 | 17861.39 | 09-JUN-08:32 | 0.00 | 0.00 | 0.00 |
July | 0.780333E+10 | 0.00 | 519.55 | 0.425612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20598.39 | 30-JUL-08:32 | 17551.91 | 13-JUL-08:32 | 0.00 | 0.00 | 0.00 |
August | 0.652620E+10 | 0.00 | 519.40 | 0.323889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20431.36 | 03-AUG-07:51 | 16424.54 | 11-AUG-08:51 | 0.00 | 0.00 | 0.00 |
September | 0.385115E+10 | 0.00 | 412.13 | 0.194904E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18132.62 | 11-SEP-08:51 | 16428.16 | 06-SEP-08:51 | 0.00 | 0.00 | 0.00 |
October | 0.320695E+09 | 0.00 | 94.93 | 0.127632E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15554.04 | 02-OCT-15:01 | 13912.29 | 21-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 32328038.73 | 0.00 | 12.12 | 13434812.83 | 0.00 | 0.00 | 0.00 | 0.00 | 12067.41 | 04-NOV-08:62 | 12067.41 | 04-NOV-08:62 | 0.00 | 0.00 | 0.00 |
December | 1331989.64 | 0.00 | 0.85 | 606534.45 | 0.00 | 0.00 | 0.00 | 0.00 | 2614.45 | 05-DEC-09:03 | 1558.37 | 25-DEC-09:05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.309040E+11 | 0.00 | 2830.28 | 0.161667E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 565753.21 | 0.00 | 0.15 | 191700.18 | 0.00 | 0.00 | 0.00 | 0.00 | 2193.21 | 932.07 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.780333E+10 | 0.00 | 519.55 | 0.425612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21008.12 | 17861.39 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 2090041.25 | 0.00 | 1.48 | 1321572.11 | 0.00 | 0.00 | 0.00 | 0.00 | 3202.27 | 12-JAN-16:01 | 3202.27 | 12-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 40855515.47 | 0.00 | 19.35 | 23688176.73 | 0.00 | 0.00 | 0.00 | 0.00 | 4541.91 | 17-FEB-16:01 | 4541.91 | 17-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.129635E+09 | 0.00 | 78.51 | 84377955.68 | 0.00 | 0.00 | 0.00 | 0.00 | 4738.78 | 23-MAR-18:01 | 4738.78 | 23-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.715218E+09 | 0.00 | 263.71 | 0.474447E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4738.43 | 25-APR-18:01 | 4738.43 | 25-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.123616E+10 | 0.00 | 525.86 | 0.649875E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4878.55 | 29-MAY-08:61 | 4737.71 | 06-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.213792E+10 | 0.00 | 595.78 | 0.120108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5247.12 | 25-JUN-08:61 | 4204.95 | 06-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.267999E+10 | 0.00 | 699.14 | 0.149985E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5361.98 | 20-JUL-08:61 | 4179.14 | 21-JUL-18:01 | 0.00 | 0.00 | 0.00 |
August | 0.235320E+10 | 0.00 | 692.43 | 0.123661E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5648.68 | 31-AUG-08:61 | 4207.46 | 25-AUG-15:01 | 0.00 | 0.00 | 0.00 |
September | 0.141528E+10 | 0.00 | 478.18 | 0.822468E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4901.68 | 11-SEP-08:61 | 4738.71 | 23-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.323031E+09 | 0.00 | 172.80 | 0.184678E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4414.95 | 02-OCT-15:01 | 4114.39 | 21-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 60895723.37 | 0.00 | 30.13 | 37861411.48 | 0.00 | 0.00 | 0.00 | 0.00 | 4737.30 | 12-NOV-16:01 | 4737.30 | 12-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 3107899.46 | 0.00 | 2.01 | 2603047.38 | 0.00 | 0.00 | 0.00 | 0.00 | 4675.77 | 01-DEC-16:01 | 4675.77 | 01-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.110974E+11 | 0.00 | 3559.38 | 0.621886E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2090041.25 | 0.00 | 1.48 | 1321572.11 | 0.00 | 0.00 | 0.00 | 0.00 | 3202.27 | 3202.27 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.267999E+10 | 0.00 | 699.14 | 0.149985E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5648.68 | 4738.78 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 100586.62 | 0.00 | 0.05 | 43732.57 | 0.00 | 0.00 | 0.00 | 0.00 | 746.44 | 12-JAN-16:03 | 385.70 | 12-JAN-16:03 | 0.00 | 0.00 | 0.00 |
February | 8134413.29 | 0.00 | 7.36 | 3423702.82 | 0.00 | 0.00 | 0.00 | 0.00 | 3268.46 | 25-FEB-16:01 | 3268.46 | 25-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 36855516.55 | 0.00 | 33.55 | 21981431.54 | 0.00 | 0.00 | 0.00 | 0.00 | 4483.38 | 21-MAR-18:01 | 4483.38 | 21-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.439618E+09 | 0.00 | 186.39 | 0.276787E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4844.30 | 16-APR-21:51 | 4810.09 | 29-APR-18:41 | 0.00 | 0.00 | 0.00 |
May | 0.841540E+09 | 0.00 | 410.70 | 0.395659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5207.71 | 20-MAY-18:41 | 5207.71 | 20-MAY-18:41 | 0.00 | 0.00 | 0.00 |
June | 0.173850E+10 | 0.00 | 459.64 | 0.993095E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5917.34 | 26-JUN-08:11 | 4714.04 | 16-JUN-16:32 | 0.00 | 0.00 | 0.00 |
July | 0.210236E+10 | 0.00 | 507.60 | 0.120360E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5458.72 | 02-JUL-08:51 | 4669.46 | 23-JUL-21:51 | 0.00 | 0.00 | 0.00 |
August | 0.170690E+10 | 0.00 | 506.65 | 0.866213E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6070.65 | 03-AUG-07:51 | 4499.37 | 11-AUG-18:11 | 0.00 | 0.00 | 0.00 |
September | 0.904371E+09 | 0.00 | 347.02 | 0.472903E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5305.65 | 19-SEP-17:41 | 5305.65 | 19-SEP-17:41 | 0.00 | 0.00 | 0.00 |
October | 94840134.93 | 0.00 | 74.71 | 42338627.50 | 0.00 | 0.00 | 0.00 | 0.00 | 4486.75 | 02-OCT-15:01 | 4257.62 | 10-OCT-16:51 | 0.00 | 0.00 | 0.00 |
November | 17226258.24 | 0.00 | 8.97 | 9252540.33 | 0.00 | 0.00 | 0.00 | 0.00 | 4112.44 | 03-NOV-15:01 | 3990.97 | 03-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 165478.25 | 0.00 | 0.10 | 109135.42 | 0.00 | 0.00 | 0.00 | 0.00 | 524.26 | 05-DEC-16:04 | 524.26 | 05-DEC-16:04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.789061E+10 | 0.00 | 2542.73 | 0.428541E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 100586.62 | 0.00 | 0.05 | 43732.57 | 0.00 | 0.00 | 0.00 | 0.00 | 524.26 | 385.70 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.210236E+10 | 0.00 | 507.60 | 0.120360E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6070.65 | 5305.65 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.576765E+09 | 0.00 | 64.45 | 0.474376E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21869.47 | 02-JAN-16:01 | 21869.47 | 02-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.107896E+10 | 0.00 | 105.36 | 0.734518E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21869.46 | 17-FEB-16:01 | 21869.46 | 17-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.194236E+10 | 0.00 | 218.15 | 0.126630E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21871.59 | 07-MAR-16:01 | 21871.59 | 07-MAR-16:01 | 0.00 | 0.00 | 0.00 |
April | 0.422791E+10 | 0.00 | 336.31 | 0.264945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21872.37 | 30-APR-18:01 | 21872.37 | 30-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.665083E+10 | 0.00 | 588.34 | 0.314308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22385.64 | 31-MAY-08:61 | 21763.29 | 21-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.997514E+10 | 0.00 | 621.73 | 0.508053E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24522.53 | 25-JUN-08:61 | 19454.18 | 03-JUN-15:01 | 0.00 | 0.00 | 0.00 |
July | 0.124323E+11 | 0.00 | 691.91 | 0.635888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25284.76 | 20-JUL-08:61 | 19059.35 | 21-JUL-18:01 | 0.00 | 0.00 | 0.00 |
August | 0.123410E+11 | 0.00 | 687.94 | 0.641505E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26512.13 | 31-AUG-08:61 | 19176.53 | 06-AUG-08:61 | 0.00 | 0.00 | 0.00 |
September | 0.927069E+10 | 0.00 | 563.12 | 0.565463E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22807.04 | 11-SEP-08:61 | 21867.47 | 20-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.460907E+10 | 0.00 | 397.75 | 0.290298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19835.09 | 09-OCT-15:02 | 19172.33 | 02-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.155914E+10 | 0.00 | 168.26 | 0.105320E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21864.47 | 21-NOV-16:01 | 21864.47 | 21-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.103979E+10 | 0.00 | 90.67 | 0.870245E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21869.53 | 25-DEC-16:01 | 21869.53 | 25-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.657039E+11 | 0.00 | 4533.96 | 0.366032E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.576765E+09 | 0.00 | 64.45 | 0.474376E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19835.09 | 19059.35 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.124323E+11 | 0.00 | 691.91 | 0.641505E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26512.13 | 21872.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 867.18 | 594.15 | 273.04 | 755.55 | 941.00 | 0.00 | 0.00 | 0.00 |
February | 934.82 | 634.23 | 300.59 | 854.73 | 742.80 | 0.00 | 0.00 | 0.00 |
March | 800.77 | 419.18 | 381.59 | 759.62 | 545.19 | 0.00 | 0.00 | 0.00 |
April | 713.90 | 327.18 | 386.72 | 762.18 | 393.79 | 0.00 | 0.00 | 0.00 |
May | 608.86 | 170.32 | 438.54 | 714.23 | 215.23 | 0.00 | 0.00 | 0.00 |
June | 581.22 | 116.07 | 465.15 | 753.97 | 137.27 | 0.00 | 0.00 | 0.00 |
July | 616.80 | 154.26 | 462.54 | 833.60 | 115.24 | 0.00 | 0.00 | 0.00 |
August | 683.50 | 236.70 | 446.81 | 928.21 | 142.39 | 0.00 | 0.00 | 0.00 |
September | 825.25 | 425.84 | 399.41 | 1039.58 | 254.23 | 0.00 | 0.00 | 0.00 |
October | 889.33 | 560.68 | 328.64 | 974.46 | 404.28 | 0.00 | 0.00 | 0.00 |
November | 665.62 | 416.74 | 248.88 | 615.40 | 608.19 | 0.00 | 0.00 | 0.00 |
December | 708.75 | 536.76 | 171.99 | 656.83 | 885.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 740.24 | 381.28 | 358.96 | 803.74 | 447.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 581.22 | 116.07 | 171.99 | 615.40 | 115.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 934.82 | 634.23 | 465.15 | 1039.58 | 941.00 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2441.93 | 1673.08 | 768.85 | 2109.95 | 2678.02 | 0.00 | 0.00 | 0.00 |
February | 2632.40 | 1785.95 | 846.45 | 2385.46 | 2142.31 | 0.00 | 0.00 | 0.00 |
March | 2254.92 | 1180.40 | 1074.52 | 2110.48 | 1595.28 | 0.00 | 0.00 | 0.00 |
April | 2010.29 | 921.31 | 1088.99 | 2119.88 | 1176.64 | 0.00 | 0.00 | 0.00 |
May | 1714.50 | 479.61 | 1234.89 | 1966.81 | 675.14 | 0.00 | 0.00 | 0.00 |
June | 1636.69 | 326.85 | 1309.83 | 2087.80 | 433.85 | 0.00 | 0.00 | 0.00 |
July | 1736.88 | 434.39 | 1302.49 | 2316.17 | 360.88 | 0.00 | 0.00 | 0.00 |
August | 1924.70 | 666.53 | 1258.17 | 2584.39 | 445.03 | 0.00 | 0.00 | 0.00 |
September | 2323.84 | 1199.13 | 1124.71 | 2897.16 | 776.56 | 0.00 | 0.00 | 0.00 |
October | 2504.29 | 1578.85 | 925.44 | 2710.84 | 1218.57 | 0.00 | 0.00 | 0.00 |
November | 1874.36 | 1173.52 | 700.84 | 1710.11 | 1769.51 | 0.00 | 0.00 | 0.00 |
December | 1995.80 | 1511.48 | 484.32 | 1832.75 | 2530.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2084.46 | 1073.66 | 1010.80 | 2235.11 | 1313.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1636.69 | 326.85 | 484.32 | 1710.11 | 360.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2632.40 | 1785.95 | 1309.83 | 2897.16 | 2678.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3172.21 | 2173.42 | 998.78 | 2777.63 | 3625.43 | 0.00 | 0.00 | 0.00 |
February | 3419.64 | 2320.05 | 1099.59 | 3152.21 | 2888.83 | 0.00 | 0.00 | 0.00 |
March | 2929.27 | 1533.40 | 1395.87 | 2786.30 | 2172.38 | 0.00 | 0.00 | 0.00 |
April | 2611.48 | 1196.83 | 1414.65 | 2805.60 | 1607.77 | 0.00 | 0.00 | 0.00 |
May | 2227.23 | 623.04 | 1604.19 | 2596.53 | 922.38 | 0.00 | 0.00 | 0.00 |
June | 2126.15 | 424.60 | 1701.55 | 2763.96 | 589.18 | 0.00 | 0.00 | 0.00 |
July | 2256.31 | 564.29 | 1692.01 | 3069.50 | 482.66 | 0.00 | 0.00 | 0.00 |
August | 2500.30 | 865.86 | 1634.44 | 3422.49 | 592.24 | 0.00 | 0.00 | 0.00 |
September | 3018.80 | 1557.74 | 1461.06 | 3824.89 | 1050.47 | 0.00 | 0.00 | 0.00 |
October | 3253.21 | 2051.01 | 1202.20 | 3571.36 | 1656.52 | 0.00 | 0.00 | 0.00 |
November | 2434.89 | 1524.47 | 910.43 | 2243.48 | 2422.24 | 0.00 | 0.00 | 0.00 |
December | 2592.66 | 1963.50 | 629.16 | 2415.52 | 3436.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2707.83 | 1394.74 | 1313.08 | 2951.29 | 1782.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 2126.15 | 424.60 | 629.16 | 2243.48 | 482.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3419.64 | 2320.05 | 1701.55 | 3824.89 | 3625.43 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 171.46 | 117.47 | 53.98 | 148.85 | 194.80 | 0.00 | 0.00 | 0.00 |
February | 184.83 | 125.40 | 59.43 | 167.21 | 155.92 | 0.00 | 0.00 | 0.00 |
March | 158.33 | 82.88 | 75.45 | 149.81 | 111.22 | 0.00 | 0.00 | 0.00 |
April | 141.15 | 64.69 | 76.46 | 150.64 | 79.54 | 0.00 | 0.00 | 0.00 |
May | 120.38 | 33.68 | 86.71 | 140.14 | 42.56 | 0.00 | 0.00 | 0.00 |
June | 114.92 | 22.95 | 91.97 | 150.89 | 24.71 | 0.00 | 0.00 | 0.00 |
July | 121.95 | 30.50 | 91.45 | 167.48 | 19.21 | 0.00 | 0.00 | 0.00 |
August | 135.14 | 46.80 | 88.34 | 186.02 | 24.30 | 0.00 | 0.00 | 0.00 |
September | 163.17 | 84.20 | 78.97 | 207.79 | 47.68 | 0.00 | 0.00 | 0.00 |
October | 175.84 | 110.86 | 64.98 | 193.51 | 80.32 | 0.00 | 0.00 | 0.00 |
November | 131.61 | 82.40 | 49.21 | 122.03 | 123.66 | 0.00 | 0.00 | 0.00 |
December | 140.13 | 106.13 | 34.01 | 130.71 | 179.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 146.36 | 75.39 | 70.97 | 159.54 | 90.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 114.92 | 22.95 | 34.01 | 122.03 | 19.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 184.83 | 125.40 | 91.97 | 207.79 | 194.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 109.56 | 44.55 | 65.01 | 45.97 | 412.90 | 0.00 | 0.00 | 0.00 |
February | 159.91 | 78.73 | 81.18 | 97.71 | 328.50 | 0.00 | 0.00 | 0.00 |
March | 190.84 | 70.98 | 119.86 | 137.81 | 214.74 | 0.00 | 0.00 | 0.00 |
April | 279.07 | 138.10 | 140.97 | 281.65 | 144.70 | 0.00 | 0.00 | 0.00 |
May | 279.64 | 111.96 | 167.68 | 317.19 | 77.14 | 0.00 | 0.00 | 0.00 |
June | 327.13 | 141.45 | 185.68 | 417.37 | 45.49 | 0.00 | 0.00 | 0.00 |
July | 351.36 | 166.70 | 184.67 | 462.40 | 35.60 | 0.00 | 0.00 | 0.00 |
August | 306.78 | 140.38 | 166.40 | 402.77 | 45.06 | 0.00 | 0.00 | 0.00 |
September | 248.93 | 117.96 | 130.98 | 296.73 | 88.60 | 0.00 | 0.00 | 0.00 |
October | 174.50 | 77.96 | 96.54 | 158.89 | 156.57 | 0.00 | 0.00 | 0.00 |
November | 104.11 | 38.66 | 65.46 | 61.12 | 252.70 | 0.00 | 0.00 | 0.00 |
December | 80.14 | 37.92 | 42.22 | 40.53 | 372.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 217.90 | 97.13 | 120.76 | 227.33 | 180.49 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 80.14 | 37.92 | 42.22 | 40.53 | 35.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 351.36 | 166.70 | 185.68 | 462.40 | 412.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.48 | 0.00 | 27.48 | 0.08 | 236.43 | 0.00 | 0.00 | 0.00 |
February | 34.84 | 0.00 | 34.84 | 1.55 | 189.41 | 0.00 | 0.00 | 0.00 |
March | 52.23 | 0.00 | 52.23 | 15.73 | 121.02 | 0.00 | 0.00 | 0.00 |
April | 60.53 | 0.49 | 60.04 | 33.43 | 79.46 | 0.00 | 0.00 | 0.00 |
May | 78.70 | 2.98 | 75.72 | 70.93 | 40.27 | 0.00 | 0.00 | 0.00 |
June | 92.10 | 8.54 | 83.56 | 108.51 | 24.76 | 0.00 | 0.00 | 0.00 |
July | 86.38 | 5.96 | 80.42 | 106.25 | 20.71 | 0.00 | 0.00 | 0.00 |
August | 72.38 | 1.47 | 70.91 | 88.21 | 25.65 | 0.00 | 0.00 | 0.00 |
September | 55.39 | 0.05 | 55.34 | 53.98 | 49.61 | 0.00 | 0.00 | 0.00 |
October | 41.13 | 0.00 | 41.13 | 19.53 | 85.82 | 0.00 | 0.00 | 0.00 |
November | 28.77 | 0.00 | 28.77 | 4.77 | 141.03 | 0.00 | 0.00 | 0.00 |
December | 18.66 | 0.00 | 18.66 | 0.02 | 207.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.15 | 1.63 | 52.52 | 42.16 | 101.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.66 | 0.00 | 18.66 | 0.02 | 20.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 92.10 | 8.54 | 83.56 | 108.51 | 236.43 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 109.56 | 44.55 | 65.01 | 48.08 | 409.87 | 0.00 | 0.00 | 0.00 |
February | 159.91 | 78.73 | 81.18 | 101.16 | 324.29 | 0.00 | 0.00 | 0.00 |
March | 190.84 | 70.98 | 119.86 | 141.89 | 212.37 | 0.00 | 0.00 | 0.00 |
April | 279.07 | 138.10 | 140.97 | 283.88 | 144.37 | 0.00 | 0.00 | 0.00 |
May | 279.64 | 111.96 | 167.68 | 315.38 | 78.84 | 0.00 | 0.00 | 0.00 |
June | 327.13 | 141.45 | 185.68 | 413.16 | 48.51 | 0.00 | 0.00 | 0.00 |
July | 351.36 | 166.70 | 184.67 | 457.70 | 40.17 | 0.00 | 0.00 | 0.00 |
August | 306.78 | 140.38 | 166.40 | 399.94 | 49.54 | 0.00 | 0.00 | 0.00 |
September | 248.93 | 117.96 | 130.98 | 297.90 | 90.32 | 0.00 | 0.00 | 0.00 |
October | 174.50 | 77.96 | 96.54 | 163.49 | 154.45 | 0.00 | 0.00 | 0.00 |
November | 104.11 | 38.66 | 65.46 | 63.94 | 250.18 | 0.00 | 0.00 | 0.00 |
December | 80.14 | 37.92 | 42.22 | 42.99 | 369.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 217.90 | 97.13 | 120.76 | 228.09 | 180.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 80.14 | 37.92 | 42.22 | 42.99 | 40.17 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 351.36 | 166.70 | 185.68 | 457.70 | 409.87 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 137.14 | 93.96 | 43.18 | 121.50 | 141.05 | 0.00 | 0.00 | 0.00 |
February | 147.84 | 100.30 | 47.54 | 132.35 | 127.97 | 0.00 | 0.00 | 0.00 |
March | 126.64 | 66.29 | 60.35 | 114.08 | 98.96 | 0.00 | 0.00 | 0.00 |
April | 112.90 | 51.74 | 61.16 | 112.34 | 84.80 | 0.00 | 0.00 | 0.00 |
May | 96.29 | 26.93 | 69.35 | 99.61 | 52.28 | 0.00 | 0.00 | 0.00 |
June | 91.92 | 18.36 | 73.56 | 107.38 | 35.34 | 0.00 | 0.00 | 0.00 |
July | 97.54 | 24.40 | 73.15 | 120.78 | 29.57 | 0.00 | 0.00 | 0.00 |
August | 108.09 | 37.43 | 70.66 | 136.28 | 35.54 | 0.00 | 0.00 | 0.00 |
September | 130.51 | 67.34 | 63.16 | 154.89 | 58.16 | 0.00 | 0.00 | 0.00 |
October | 140.64 | 88.67 | 51.97 | 142.89 | 88.00 | 0.00 | 0.00 | 0.00 |
November | 105.26 | 65.90 | 39.36 | 91.24 | 113.91 | 0.00 | 0.00 | 0.00 |
December | 112.08 | 84.88 | 27.20 | 105.02 | 134.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 117.06 | 60.30 | 56.77 | 119.80 | 83.06 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 91.92 | 18.36 | 27.20 | 91.24 | 29.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 147.84 | 100.30 | 73.56 | 154.89 | 141.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 21.99 | 0.00 | 21.99 | 0.04 | 195.24 | 0.00 | 0.00 | 0.00 |
February | 27.88 | 0.00 | 27.88 | 1.01 | 155.95 | 0.00 | 0.00 | 0.00 |
March | 41.79 | 0.00 | 41.79 | 12.21 | 99.58 | 0.00 | 0.00 | 0.00 |
April | 48.43 | 0.39 | 48.04 | 28.17 | 64.22 | 0.00 | 0.00 | 0.00 |
May | 62.97 | 2.39 | 60.58 | 59.92 | 31.53 | 0.00 | 0.00 | 0.00 |
June | 73.69 | 6.83 | 66.86 | 91.05 | 18.63 | 0.00 | 0.00 | 0.00 |
July | 69.12 | 4.77 | 64.35 | 89.82 | 14.69 | 0.00 | 0.00 | 0.00 |
August | 57.91 | 1.17 | 56.74 | 74.84 | 18.74 | 0.00 | 0.00 | 0.00 |
September | 44.32 | 0.04 | 44.28 | 45.51 | 38.62 | 0.00 | 0.00 | 0.00 |
October | 32.91 | 0.00 | 32.91 | 15.54 | 70.00 | 0.00 | 0.00 | 0.00 |
November | 23.02 | 0.00 | 23.02 | 3.51 | 117.27 | 0.00 | 0.00 | 0.00 |
December | 14.93 | 0.00 | 14.93 | 0.00 | 172.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 43.33 | 1.30 | 42.02 | 35.34 | 82.74 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.93 | 0.00 | 14.93 | 0.00 | 14.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 73.69 | 6.83 | 66.86 | 91.05 | 195.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 109.65 | 44.94 | 64.72 | 42.65 | 405.85 | 0.00 | 0.00 | 0.00 |
February | 146.01 | 64.26 | 81.74 | 76.95 | 321.48 | 0.00 | 0.00 | 0.00 |
March | 198.30 | 78.68 | 119.63 | 143.75 | 209.27 | 0.00 | 0.00 | 0.00 |
April | 242.03 | 105.49 | 136.55 | 229.16 | 141.39 | 0.00 | 0.00 | 0.00 |
May | 305.81 | 133.75 | 172.06 | 346.84 | 72.89 | 0.00 | 0.00 | 0.00 |
June | 336.08 | 146.41 | 189.67 | 427.69 | 43.07 | 0.00 | 0.00 | 0.00 |
July | 339.77 | 156.84 | 182.93 | 443.47 | 33.33 | 0.00 | 0.00 | 0.00 |
August | 286.45 | 123.45 | 163.00 | 372.63 | 42.14 | 0.00 | 0.00 | 0.00 |
September | 256.63 | 121.72 | 134.92 | 305.31 | 86.32 | 0.00 | 0.00 | 0.00 |
October | 162.51 | 67.64 | 94.87 | 138.95 | 151.48 | 0.00 | 0.00 | 0.00 |
November | 96.13 | 31.20 | 64.93 | 47.31 | 247.60 | 0.00 | 0.00 | 0.00 |
December | 74.19 | 31.76 | 42.42 | 29.39 | 366.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 213.13 | 92.31 | 120.82 | 217.77 | 176.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 74.19 | 31.20 | 42.42 | 29.39 | 33.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 339.77 | 156.84 | 189.67 | 443.47 | 405.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 171.46 | 117.47 | 53.98 | 148.61 | 194.60 | 0.00 | 0.00 | 0.00 |
February | 184.83 | 125.40 | 59.43 | 166.88 | 155.31 | 0.00 | 0.00 | 0.00 |
March | 158.33 | 82.88 | 75.45 | 148.68 | 110.92 | 0.00 | 0.00 | 0.00 |
April | 141.15 | 64.69 | 76.46 | 150.17 | 78.64 | 0.00 | 0.00 | 0.00 |
May | 120.38 | 33.68 | 86.71 | 139.02 | 42.35 | 0.00 | 0.00 | 0.00 |
June | 114.92 | 22.95 | 91.97 | 150.07 | 24.32 | 0.00 | 0.00 | 0.00 |
July | 121.95 | 30.50 | 91.45 | 166.94 | 18.63 | 0.00 | 0.00 | 0.00 |
August | 135.14 | 46.80 | 88.34 | 185.70 | 23.82 | 0.00 | 0.00 | 0.00 |
September | 163.17 | 84.20 | 78.97 | 206.93 | 47.31 | 0.00 | 0.00 | 0.00 |
October | 175.84 | 110.86 | 64.98 | 192.88 | 79.95 | 0.00 | 0.00 | 0.00 |
November | 131.61 | 82.40 | 49.21 | 121.91 | 123.38 | 0.00 | 0.00 | 0.00 |
December | 140.13 | 106.13 | 34.01 | 130.69 | 179.65 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 146.36 | 75.39 | 70.97 | 159.00 | 89.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 114.92 | 22.95 | 34.01 | 121.91 | 18.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 184.83 | 125.40 | 91.97 | 206.93 | 194.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.48 | 0.00 | 27.48 | 0.07 | 236.40 | 0.00 | 0.00 | 0.00 |
February | 34.84 | 0.00 | 34.84 | 1.35 | 188.92 | 0.00 | 0.00 | 0.00 |
March | 52.23 | 0.00 | 52.23 | 15.11 | 121.19 | 0.00 | 0.00 | 0.00 |
April | 60.53 | 0.49 | 60.04 | 33.10 | 78.45 | 0.00 | 0.00 | 0.00 |
May | 78.70 | 2.98 | 75.72 | 70.10 | 39.76 | 0.00 | 0.00 | 0.00 |
June | 92.10 | 8.54 | 83.56 | 107.68 | 24.06 | 0.00 | 0.00 | 0.00 |
July | 86.38 | 5.96 | 80.42 | 105.34 | 19.63 | 0.00 | 0.00 | 0.00 |
August | 72.38 | 1.47 | 70.91 | 87.80 | 24.53 | 0.00 | 0.00 | 0.00 |
September | 55.39 | 0.05 | 55.34 | 52.92 | 48.88 | 0.00 | 0.00 | 0.00 |
October | 41.13 | 0.00 | 41.13 | 18.93 | 85.24 | 0.00 | 0.00 | 0.00 |
November | 28.77 | 0.00 | 28.77 | 4.65 | 140.76 | 0.00 | 0.00 | 0.00 |
December | 18.66 | 0.00 | 18.66 | 0.01 | 207.92 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.15 | 1.63 | 52.52 | 41.66 | 100.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.66 | 0.00 | 18.66 | 0.01 | 19.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 92.10 | 8.54 | 83.56 | 107.68 | 236.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 109.65 | 44.94 | 64.72 | 43.74 | 401.71 | 0.00 | 0.00 | 0.00 |
February | 146.01 | 64.26 | 81.74 | 79.13 | 315.83 | 0.00 | 0.00 | 0.00 |
March | 198.30 | 78.68 | 119.63 | 147.22 | 206.20 | 0.00 | 0.00 | 0.00 |
April | 242.03 | 105.49 | 136.55 | 231.47 | 140.53 | 0.00 | 0.00 | 0.00 |
May | 305.81 | 133.75 | 172.06 | 346.14 | 74.25 | 0.00 | 0.00 | 0.00 |
June | 336.08 | 146.41 | 189.67 | 423.61 | 45.60 | 0.00 | 0.00 | 0.00 |
July | 339.77 | 156.84 | 182.93 | 438.04 | 37.02 | 0.00 | 0.00 | 0.00 |
August | 286.45 | 123.45 | 163.00 | 369.95 | 45.68 | 0.00 | 0.00 | 0.00 |
September | 256.63 | 121.72 | 134.92 | 306.23 | 87.40 | 0.00 | 0.00 | 0.00 |
October | 162.51 | 67.64 | 94.87 | 143.45 | 148.71 | 0.00 | 0.00 | 0.00 |
November | 96.13 | 31.20 | 64.93 | 49.13 | 244.02 | 0.00 | 0.00 | 0.00 |
December | 74.19 | 31.76 | 42.42 | 30.18 | 361.65 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 213.13 | 92.31 | 120.82 | 218.11 | 175.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 74.19 | 31.20 | 42.42 | 30.18 | 37.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 339.77 | 156.84 | 189.67 | 438.04 | 401.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.81 | 0.00 | 34.81 | 0.03 | 316.44 | 0.00 | 0.00 | 0.00 |
February | 44.13 | 0.00 | 44.13 | 1.31 | 250.09 | 0.00 | 0.00 | 0.00 |
March | 66.14 | 0.00 | 66.14 | 18.73 | 161.23 | 0.00 | 0.00 | 0.00 |
April | 76.66 | 0.62 | 76.04 | 43.76 | 105.30 | 0.00 | 0.00 | 0.00 |
May | 99.67 | 3.78 | 95.89 | 93.54 | 54.00 | 0.00 | 0.00 | 0.00 |
June | 116.63 | 10.81 | 105.82 | 140.38 | 34.42 | 0.00 | 0.00 | 0.00 |
July | 109.40 | 7.55 | 101.85 | 137.19 | 28.76 | 0.00 | 0.00 | 0.00 |
August | 91.66 | 1.86 | 89.81 | 113.64 | 35.75 | 0.00 | 0.00 | 0.00 |
September | 70.14 | 0.06 | 70.08 | 68.50 | 68.43 | 0.00 | 0.00 | 0.00 |
October | 52.09 | 0.00 | 52.09 | 23.99 | 114.11 | 0.00 | 0.00 | 0.00 |
November | 36.43 | 0.00 | 36.43 | 5.35 | 190.33 | 0.00 | 0.00 | 0.00 |
December | 23.63 | 0.00 | 23.63 | 0.00 | 280.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 68.58 | 2.06 | 66.51 | 54.18 | 136.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 23.63 | 0.00 | 23.63 | 0.00 | 28.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 116.63 | 10.81 | 105.82 | 140.38 | 316.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 12.83 | 0.00 | 12.83 | 0.01 | 116.65 | 0.00 | 0.00 | 0.00 |
February | 16.27 | 0.00 | 16.27 | 0.48 | 92.20 | 0.00 | 0.00 | 0.00 |
March | 24.38 | 0.00 | 24.38 | 6.91 | 59.44 | 0.00 | 0.00 | 0.00 |
April | 28.26 | 0.23 | 28.03 | 16.13 | 38.82 | 0.00 | 0.00 | 0.00 |
May | 36.74 | 1.39 | 35.35 | 34.48 | 19.91 | 0.00 | 0.00 | 0.00 |
June | 43.00 | 3.98 | 39.01 | 51.75 | 12.69 | 0.00 | 0.00 | 0.00 |
July | 40.33 | 2.78 | 37.55 | 50.57 | 10.60 | 0.00 | 0.00 | 0.00 |
August | 33.79 | 0.68 | 33.11 | 41.89 | 13.18 | 0.00 | 0.00 | 0.00 |
September | 25.86 | 0.02 | 25.83 | 25.25 | 25.23 | 0.00 | 0.00 | 0.00 |
October | 19.20 | 0.00 | 19.20 | 8.84 | 42.07 | 0.00 | 0.00 | 0.00 |
November | 13.43 | 0.00 | 13.43 | 1.97 | 70.16 | 0.00 | 0.00 | 0.00 |
December | 8.71 | 0.00 | 8.71 | 0.00 | 103.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 25.28 | 0.76 | 24.52 | 19.97 | 50.18 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 8.71 | 0.00 | 8.71 | 0.00 | 10.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 43.00 | 3.98 | 39.01 | 51.75 | 116.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.00 | 54.81 | 25.19 | 68.69 | 94.61 | 0.00 | 0.00 | 0.00 |
February | 86.24 | 58.51 | 27.73 | 78.17 | 74.58 | 0.00 | 0.00 | 0.00 |
March | 73.87 | 38.67 | 35.20 | 70.14 | 53.84 | 0.00 | 0.00 | 0.00 |
April | 65.86 | 30.18 | 35.68 | 71.31 | 38.71 | 0.00 | 0.00 | 0.00 |
May | 56.17 | 15.71 | 40.46 | 66.38 | 21.50 | 0.00 | 0.00 | 0.00 |
June | 53.62 | 10.71 | 42.91 | 70.53 | 13.62 | 0.00 | 0.00 | 0.00 |
July | 56.90 | 14.23 | 42.67 | 78.03 | 11.22 | 0.00 | 0.00 | 0.00 |
August | 63.06 | 21.84 | 41.22 | 86.91 | 13.84 | 0.00 | 0.00 | 0.00 |
September | 76.13 | 39.29 | 36.85 | 97.27 | 24.78 | 0.00 | 0.00 | 0.00 |
October | 82.04 | 51.73 | 30.32 | 91.26 | 38.79 | 0.00 | 0.00 | 0.00 |
November | 61.41 | 38.45 | 22.96 | 56.74 | 60.44 | 0.00 | 0.00 | 0.00 |
December | 65.39 | 49.52 | 15.87 | 60.64 | 88.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 68.29 | 35.17 | 33.12 | 74.65 | 44.37 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 53.62 | 10.71 | 15.87 | 56.74 | 11.22 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 86.24 | 58.51 | 42.91 | 97.27 | 94.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 217.14 | 148.77 | 68.37 | 186.43 | 256.79 | 0.00 | 0.00 | 0.00 |
February | 234.08 | 158.81 | 75.27 | 212.18 | 202.41 | 0.00 | 0.00 | 0.00 |
March | 200.51 | 104.96 | 95.55 | 190.36 | 146.12 | 0.00 | 0.00 | 0.00 |
April | 178.76 | 81.92 | 96.83 | 193.54 | 105.06 | 0.00 | 0.00 | 0.00 |
May | 152.46 | 42.65 | 109.81 | 180.17 | 58.36 | 0.00 | 0.00 | 0.00 |
June | 145.54 | 29.06 | 116.47 | 191.42 | 36.96 | 0.00 | 0.00 | 0.00 |
July | 154.45 | 38.63 | 115.82 | 211.80 | 30.44 | 0.00 | 0.00 | 0.00 |
August | 171.15 | 59.27 | 111.88 | 235.88 | 37.57 | 0.00 | 0.00 | 0.00 |
September | 206.64 | 106.63 | 100.01 | 264.01 | 67.25 | 0.00 | 0.00 | 0.00 |
October | 222.68 | 140.39 | 82.29 | 247.70 | 105.28 | 0.00 | 0.00 | 0.00 |
November | 166.67 | 104.35 | 62.32 | 154.01 | 164.05 | 0.00 | 0.00 | 0.00 |
December | 177.47 | 134.40 | 43.07 | 164.58 | 239.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 185.35 | 95.47 | 89.88 | 202.62 | 120.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 145.54 | 29.06 | 43.07 | 154.01 | 30.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 234.08 | 158.81 | 116.47 | 264.01 | 256.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 171.46 | 117.47 | 53.98 | 148.20 | 195.04 | 0.00 | 0.00 | 0.00 |
February | 184.83 | 125.40 | 59.43 | 166.39 | 156.01 | 0.00 | 0.00 | 0.00 |
March | 158.33 | 82.88 | 75.45 | 149.24 | 111.06 | 0.00 | 0.00 | 0.00 |
April | 141.15 | 64.69 | 76.46 | 149.72 | 79.23 | 0.00 | 0.00 | 0.00 |
May | 120.38 | 33.68 | 86.71 | 138.96 | 42.35 | 0.00 | 0.00 | 0.00 |
June | 114.92 | 22.95 | 91.97 | 149.89 | 24.32 | 0.00 | 0.00 | 0.00 |
July | 121.95 | 30.50 | 91.45 | 166.42 | 18.80 | 0.00 | 0.00 | 0.00 |
August | 135.14 | 46.80 | 88.34 | 184.88 | 23.93 | 0.00 | 0.00 | 0.00 |
September | 163.17 | 84.20 | 78.97 | 206.95 | 47.02 | 0.00 | 0.00 | 0.00 |
October | 175.84 | 110.86 | 64.98 | 192.79 | 79.89 | 0.00 | 0.00 | 0.00 |
November | 131.61 | 82.40 | 49.21 | 121.75 | 123.36 | 0.00 | 0.00 | 0.00 |
December | 140.13 | 106.13 | 34.01 | 130.44 | 179.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 146.36 | 75.39 | 70.97 | 158.76 | 89.76 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 114.92 | 22.95 | 34.01 | 121.75 | 18.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 184.83 | 125.40 | 91.97 | 206.95 | 195.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 109.56 | 44.55 | 65.01 | 45.68 | 414.03 | 0.00 | 0.00 | 0.00 |
February | 159.91 | 78.73 | 81.18 | 96.89 | 329.49 | 0.00 | 0.00 | 0.00 |
March | 190.84 | 70.98 | 119.86 | 137.11 | 214.43 | 0.00 | 0.00 | 0.00 |
April | 279.07 | 138.10 | 140.97 | 279.76 | 144.04 | 0.00 | 0.00 | 0.00 |
May | 279.64 | 111.96 | 167.68 | 314.89 | 76.64 | 0.00 | 0.00 | 0.00 |
June | 327.13 | 141.45 | 185.68 | 415.08 | 44.74 | 0.00 | 0.00 | 0.00 |
July | 351.36 | 166.70 | 184.67 | 459.94 | 34.79 | 0.00 | 0.00 | 0.00 |
August | 306.78 | 140.38 | 166.40 | 400.53 | 44.33 | 0.00 | 0.00 | 0.00 |
September | 248.93 | 117.96 | 130.98 | 295.56 | 87.35 | 0.00 | 0.00 | 0.00 |
October | 174.50 | 77.96 | 96.54 | 158.08 | 155.62 | 0.00 | 0.00 | 0.00 |
November | 104.11 | 38.66 | 65.46 | 61.21 | 251.95 | 0.00 | 0.00 | 0.00 |
December | 80.14 | 37.92 | 42.22 | 40.52 | 372.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 217.90 | 97.13 | 120.76 | 226.08 | 180.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 80.14 | 37.92 | 42.22 | 40.52 | 34.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 351.36 | 166.70 | 185.68 | 459.94 | 414.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.48 | 0.00 | 27.48 | 0.10 | 237.10 | 0.00 | 0.00 | 0.00 |
February | 34.84 | 0.00 | 34.84 | 1.59 | 189.81 | 0.00 | 0.00 | 0.00 |
March | 52.23 | 0.00 | 52.23 | 15.90 | 120.81 | 0.00 | 0.00 | 0.00 |
April | 60.53 | 0.49 | 60.04 | 33.19 | 79.32 | 0.00 | 0.00 | 0.00 |
May | 78.70 | 2.98 | 75.72 | 69.89 | 40.43 | 0.00 | 0.00 | 0.00 |
June | 92.10 | 8.54 | 83.56 | 107.43 | 24.87 | 0.00 | 0.00 | 0.00 |
July | 86.38 | 5.96 | 80.42 | 105.31 | 20.88 | 0.00 | 0.00 | 0.00 |
August | 72.38 | 1.47 | 70.91 | 87.54 | 25.91 | 0.00 | 0.00 | 0.00 |
September | 55.39 | 0.05 | 55.34 | 53.96 | 49.20 | 0.00 | 0.00 | 0.00 |
October | 41.13 | 0.00 | 41.13 | 19.84 | 85.16 | 0.00 | 0.00 | 0.00 |
November | 28.77 | 0.00 | 28.77 | 4.95 | 140.43 | 0.00 | 0.00 | 0.00 |
December | 18.66 | 0.00 | 18.66 | 0.02 | 208.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.15 | 1.63 | 52.52 | 41.88 | 101.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.66 | 0.00 | 18.66 | 0.02 | 20.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 92.10 | 8.54 | 83.56 | 107.43 | 237.10 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 109.56 | 44.55 | 65.01 | 47.65 | 411.02 | 0.00 | 0.00 | 0.00 |
February | 159.91 | 78.73 | 81.18 | 100.45 | 325.24 | 0.00 | 0.00 | 0.00 |
March | 190.84 | 70.98 | 119.86 | 141.44 | 212.08 | 0.00 | 0.00 | 0.00 |
April | 279.07 | 138.10 | 140.97 | 282.12 | 143.83 | 0.00 | 0.00 | 0.00 |
May | 279.64 | 111.96 | 167.68 | 312.57 | 78.93 | 0.00 | 0.00 | 0.00 |
June | 327.13 | 141.45 | 185.68 | 410.27 | 48.61 | 0.00 | 0.00 | 0.00 |
July | 351.36 | 166.70 | 184.67 | 454.80 | 40.39 | 0.00 | 0.00 | 0.00 |
August | 306.78 | 140.38 | 166.40 | 397.39 | 49.86 | 0.00 | 0.00 | 0.00 |
September | 248.93 | 117.96 | 130.98 | 296.83 | 89.48 | 0.00 | 0.00 | 0.00 |
October | 174.50 | 77.96 | 96.54 | 163.25 | 153.32 | 0.00 | 0.00 | 0.00 |
November | 104.11 | 38.66 | 65.46 | 64.17 | 249.46 | 0.00 | 0.00 | 0.00 |
December | 80.14 | 37.92 | 42.22 | 42.95 | 369.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 217.90 | 97.13 | 120.76 | 226.78 | 180.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 80.14 | 37.92 | 42.22 | 42.95 | 40.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 351.36 | 166.70 | 185.68 | 454.80 | 411.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 251.46 | 172.29 | 79.17 | 209.71 | 293.92 | 0.00 | 0.00 | 0.00 |
February | 271.07 | 183.91 | 87.16 | 236.54 | 236.43 | 0.00 | 0.00 | 0.00 |
March | 232.20 | 121.55 | 110.65 | 213.44 | 167.23 | 0.00 | 0.00 | 0.00 |
April | 207.01 | 94.87 | 112.14 | 218.35 | 117.35 | 0.00 | 0.00 | 0.00 |
May | 176.55 | 49.39 | 127.16 | 204.48 | 61.65 | 0.00 | 0.00 | 0.00 |
June | 168.54 | 33.66 | 134.88 | 222.39 | 34.66 | 0.00 | 0.00 | 0.00 |
July | 178.86 | 44.73 | 134.13 | 247.31 | 25.91 | 0.00 | 0.00 | 0.00 |
August | 198.20 | 68.64 | 129.56 | 273.14 | 33.89 | 0.00 | 0.00 | 0.00 |
September | 239.30 | 123.48 | 115.82 | 302.44 | 69.34 | 0.00 | 0.00 | 0.00 |
October | 257.88 | 162.58 | 95.30 | 278.11 | 120.70 | 0.00 | 0.00 | 0.00 |
November | 193.01 | 120.84 | 72.17 | 173.33 | 187.13 | 0.00 | 0.00 | 0.00 |
December | 205.52 | 155.65 | 49.87 | 185.40 | 271.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 214.65 | 110.56 | 104.09 | 230.35 | 134.49 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 168.54 | 33.66 | 49.87 | 173.33 | 25.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 271.07 | 183.91 | 134.88 | 302.44 | 293.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 192.37 | 0.00 | 192.37 | 0.00 | 1826.80 | 0.00 | 0.00 | 0.00 |
February | 243.89 | 0.00 | 243.89 | 3.71 | 1463.07 | 0.00 | 0.00 | 0.00 |
March | 365.57 | 0.00 | 365.56 | 79.52 | 996.47 | 0.00 | 0.00 | 0.00 |
April | 423.69 | 3.43 | 420.26 | 207.74 | 665.52 | 0.00 | 0.00 | 0.00 |
May | 550.88 | 20.87 | 530.01 | 462.44 | 337.55 | 0.00 | 0.00 | 0.00 |
June | 644.65 | 59.75 | 584.90 | 736.00 | 211.84 | 0.00 | 0.00 | 0.00 |
July | 604.66 | 41.71 | 562.95 | 728.33 | 169.98 | 0.00 | 0.00 | 0.00 |
August | 506.63 | 10.26 | 496.37 | 598.71 | 212.61 | 0.00 | 0.00 | 0.00 |
September | 387.70 | 0.36 | 387.34 | 352.98 | 413.91 | 0.00 | 0.00 | 0.00 |
October | 287.89 | 0.00 | 287.89 | 102.22 | 720.41 | 0.00 | 0.00 | 0.00 |
November | 201.38 | 0.00 | 201.38 | 19.99 | 1157.43 | 0.00 | 0.00 | 0.00 |
December | 130.63 | 0.00 | 130.63 | 0.00 | 1658.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 379.04 | 11.41 | 367.63 | 275.93 | 816.49 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 130.63 | 0.00 | 130.63 | 0.00 | 169.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 644.65 | 59.75 | 584.90 | 736.00 | 1826.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 192.37 | 0.00 | 192.37 | 0.00 | 1861.87 | 0.00 | 0.00 | 0.00 |
February | 243.89 | 0.00 | 243.89 | 2.80 | 1494.16 | 0.00 | 0.00 | 0.00 |
March | 365.57 | 0.00 | 365.56 | 72.76 | 1021.67 | 0.00 | 0.00 | 0.00 |
April | 423.69 | 3.43 | 420.26 | 199.50 | 683.46 | 0.00 | 0.00 | 0.00 |
May | 550.88 | 20.87 | 530.01 | 451.19 | 345.72 | 0.00 | 0.00 | 0.00 |
June | 644.65 | 59.75 | 584.90 | 726.93 | 217.87 | 0.00 | 0.00 | 0.00 |
July | 604.66 | 41.71 | 562.95 | 720.16 | 175.01 | 0.00 | 0.00 | 0.00 |
August | 506.63 | 10.26 | 496.37 | 590.61 | 218.61 | 0.00 | 0.00 | 0.00 |
September | 387.70 | 0.36 | 387.34 | 344.88 | 424.27 | 0.00 | 0.00 | 0.00 |
October | 287.89 | 0.00 | 287.89 | 93.96 | 739.16 | 0.00 | 0.00 | 0.00 |
November | 201.38 | 0.00 | 201.38 | 17.37 | 1186.58 | 0.00 | 0.00 | 0.00 |
December | 130.63 | 0.00 | 130.63 | 0.00 | 1694.80 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 379.04 | 11.41 | 367.63 | 269.94 | 835.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 130.63 | 0.00 | 130.63 | 0.00 | 175.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 644.65 | 59.75 | 584.90 | 726.93 | 1861.87 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.48 | 0.00 | 27.48 | 0.11 | 235.64 | 0.00 | 0.00 | 0.00 |
February | 34.84 | 0.00 | 34.84 | 1.73 | 185.15 | 0.00 | 0.00 | 0.00 |
March | 52.23 | 0.00 | 52.23 | 18.37 | 126.06 | 0.00 | 0.00 | 0.00 |
April | 60.53 | 0.49 | 60.04 | 42.77 | 82.83 | 0.00 | 0.00 | 0.00 |
May | 78.70 | 2.98 | 75.72 | 90.49 | 44.41 | 0.00 | 0.00 | 0.00 |
June | 92.10 | 8.54 | 83.56 | 133.08 | 28.44 | 0.00 | 0.00 | 0.00 |
July | 86.38 | 5.96 | 80.42 | 133.19 | 22.73 | 0.00 | 0.00 | 0.00 |
August | 72.38 | 1.47 | 70.91 | 112.82 | 27.70 | 0.00 | 0.00 | 0.00 |
September | 55.39 | 0.05 | 55.34 | 70.48 | 51.16 | 0.00 | 0.00 | 0.00 |
October | 41.13 | 0.00 | 41.13 | 25.38 | 88.12 | 0.00 | 0.00 | 0.00 |
November | 28.77 | 0.00 | 28.77 | 6.82 | 144.16 | 0.00 | 0.00 | 0.00 |
December | 18.66 | 0.00 | 18.66 | 0.03 | 213.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.15 | 1.63 | 52.52 | 53.25 | 103.76 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.66 | 0.00 | 18.66 | 0.03 | 22.73 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 92.10 | 8.54 | 83.56 | 133.19 | 235.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 219.29 | 89.86 | 129.42 | 94.10 | 805.37 | 0.00 | 0.00 | 0.00 |
February | 291.99 | 128.52 | 163.48 | 168.64 | 622.09 | 0.00 | 0.00 | 0.00 |
March | 396.58 | 157.34 | 239.23 | 312.75 | 433.39 | 0.00 | 0.00 | 0.00 |
April | 484.03 | 210.96 | 273.07 | 502.93 | 300.31 | 0.00 | 0.00 | 0.00 |
May | 611.58 | 267.49 | 344.09 | 767.74 | 164.96 | 0.00 | 0.00 | 0.00 |
June | 672.10 | 292.79 | 379.31 | 940.85 | 106.62 | 0.00 | 0.00 | 0.00 |
July | 679.49 | 313.66 | 365.83 | 979.92 | 85.10 | 0.00 | 0.00 | 0.00 |
August | 572.86 | 246.88 | 325.98 | 833.40 | 103.44 | 0.00 | 0.00 | 0.00 |
September | 513.23 | 243.41 | 269.81 | 682.77 | 185.89 | 0.00 | 0.00 | 0.00 |
October | 325.01 | 135.28 | 189.73 | 318.27 | 311.15 | 0.00 | 0.00 | 0.00 |
November | 192.24 | 62.39 | 129.85 | 109.48 | 504.28 | 0.00 | 0.00 | 0.00 |
December | 148.36 | 63.52 | 84.84 | 63.18 | 742.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 426.22 | 184.60 | 241.62 | 482.88 | 362.61 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 148.36 | 62.39 | 84.84 | 63.18 | 85.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 679.49 | 313.66 | 379.31 | 979.92 | 805.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 171.46 | 117.47 | 53.98 | 152.52 | 193.76 | 0.00 | 0.00 | 0.00 |
February | 184.83 | 125.40 | 59.43 | 174.31 | 152.79 | 0.00 | 0.00 | 0.00 |
March | 158.33 | 82.88 | 75.45 | 156.56 | 115.46 | 0.00 | 0.00 | 0.00 |
April | 141.15 | 64.69 | 76.46 | 162.21 | 82.69 | 0.00 | 0.00 | 0.00 |
May | 120.38 | 33.68 | 86.71 | 158.65 | 46.92 | 0.00 | 0.00 | 0.00 |
June | 114.92 | 22.95 | 91.97 | 172.84 | 29.90 | 0.00 | 0.00 | 0.00 |
July | 121.95 | 30.50 | 91.45 | 191.71 | 23.51 | 0.00 | 0.00 | 0.00 |
August | 135.14 | 46.80 | 88.34 | 208.79 | 28.60 | 0.00 | 0.00 | 0.00 |
September | 163.17 | 84.20 | 78.97 | 226.03 | 50.59 | 0.00 | 0.00 | 0.00 |
October | 175.84 | 110.86 | 64.98 | 205.35 | 83.30 | 0.00 | 0.00 | 0.00 |
November | 131.61 | 82.40 | 49.21 | 127.39 | 126.72 | 0.00 | 0.00 | 0.00 |
December | 140.13 | 106.13 | 34.01 | 133.85 | 183.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 146.36 | 75.39 | 70.97 | 172.51 | 92.85 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 114.92 | 22.95 | 34.01 | 127.39 | 23.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 184.83 | 125.40 | 91.97 | 226.03 | 193.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.81 | 0.00 | 34.81 | 0.01 | 319.19 | 0.00 | 0.00 | 0.00 |
February | 44.13 | 0.00 | 44.13 | 1.00 | 250.61 | 0.00 | 0.00 | 0.00 |
March | 66.14 | 0.00 | 66.14 | 17.24 | 164.32 | 0.00 | 0.00 | 0.00 |
April | 76.66 | 0.62 | 76.04 | 41.00 | 107.61 | 0.00 | 0.00 | 0.00 |
May | 99.67 | 3.78 | 95.89 | 89.32 | 55.61 | 0.00 | 0.00 | 0.00 |
June | 116.63 | 10.81 | 105.82 | 135.48 | 36.04 | 0.00 | 0.00 | 0.00 |
July | 109.40 | 7.55 | 101.85 | 132.69 | 30.10 | 0.00 | 0.00 | 0.00 |
August | 91.66 | 1.86 | 89.81 | 109.57 | 37.22 | 0.00 | 0.00 | 0.00 |
September | 70.14 | 0.06 | 70.08 | 65.92 | 69.10 | 0.00 | 0.00 | 0.00 |
October | 52.09 | 0.00 | 52.09 | 21.91 | 116.26 | 0.00 | 0.00 | 0.00 |
November | 36.43 | 0.00 | 36.43 | 4.77 | 193.44 | 0.00 | 0.00 | 0.00 |
December | 23.63 | 0.00 | 23.63 | 0.00 | 284.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 68.58 | 2.06 | 66.51 | 51.88 | 138.18 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 23.63 | 0.00 | 23.63 | 0.00 | 30.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 116.63 | 10.81 | 105.82 | 135.48 | 319.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 31.14 | 0.00 | 31.14 | 0.01 | 285.57 | 0.00 | 0.00 | 0.00 |
February | 39.48 | 0.00 | 39.48 | 0.90 | 224.22 | 0.00 | 0.00 | 0.00 |
March | 59.18 | 0.00 | 59.18 | 15.43 | 147.02 | 0.00 | 0.00 | 0.00 |
April | 68.58 | 0.55 | 68.03 | 36.68 | 96.28 | 0.00 | 0.00 | 0.00 |
May | 89.17 | 3.38 | 85.80 | 79.91 | 49.75 | 0.00 | 0.00 | 0.00 |
June | 104.35 | 9.67 | 94.68 | 121.22 | 32.25 | 0.00 | 0.00 | 0.00 |
July | 97.88 | 6.75 | 91.13 | 118.72 | 26.93 | 0.00 | 0.00 | 0.00 |
August | 82.01 | 1.66 | 80.35 | 98.03 | 33.30 | 0.00 | 0.00 | 0.00 |
September | 62.76 | 0.06 | 62.70 | 58.98 | 61.83 | 0.00 | 0.00 | 0.00 |
October | 46.60 | 0.00 | 46.60 | 19.61 | 104.02 | 0.00 | 0.00 | 0.00 |
November | 32.60 | 0.00 | 32.60 | 4.27 | 173.07 | 0.00 | 0.00 | 0.00 |
December | 21.15 | 0.00 | 21.15 | 0.00 | 254.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 61.36 | 1.85 | 59.51 | 46.42 | 123.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 21.15 | 0.00 | 21.15 | 0.00 | 26.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 104.35 | 9.67 | 94.68 | 121.22 | 285.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 640.10 | 438.56 | 201.54 | 543.69 | 761.65 | 0.00 | 0.00 | 0.00 |
February | 690.03 | 468.15 | 221.88 | 620.20 | 596.86 | 0.00 | 0.00 | 0.00 |
March | 591.08 | 309.42 | 281.67 | 551.47 | 437.95 | 0.00 | 0.00 | 0.00 |
April | 526.96 | 241.50 | 285.46 | 559.58 | 316.38 | 0.00 | 0.00 | 0.00 |
May | 449.42 | 125.72 | 323.70 | 517.43 | 177.48 | 0.00 | 0.00 | 0.00 |
June | 429.03 | 85.68 | 343.35 | 549.22 | 114.38 | 0.00 | 0.00 | 0.00 |
July | 455.29 | 113.87 | 341.42 | 609.97 | 94.17 | 0.00 | 0.00 | 0.00 |
August | 504.52 | 174.72 | 329.81 | 681.34 | 115.63 | 0.00 | 0.00 | 0.00 |
September | 609.15 | 314.33 | 294.82 | 767.76 | 200.50 | 0.00 | 0.00 | 0.00 |
October | 656.45 | 413.86 | 242.59 | 719.14 | 315.79 | 0.00 | 0.00 | 0.00 |
November | 491.32 | 307.61 | 183.71 | 446.94 | 491.18 | 0.00 | 0.00 | 0.00 |
December | 523.16 | 396.20 | 126.96 | 479.61 | 713.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 546.40 | 281.44 | 264.96 | 586.99 | 360.22 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 429.03 | 85.68 | 126.96 | 446.94 | 94.17 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 690.03 | 468.15 | 343.35 | 767.76 | 761.65 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.232266E+10 | 0.159136E+10 | 0.731301E+09 | 0.202367E+10 | 0.252037E+10 |
February | 0.226152E+10 | 0.153433E+10 | 0.727194E+09 | 0.206776E+10 | 0.179698E+10 |
March | 0.214479E+10 | 0.112274E+10 | 0.102204E+10 | 0.203456E+10 | 0.146022E+10 |
April | 0.185043E+10 | 0.848040E+09 | 0.100239E+10 | 0.197558E+10 | 0.102070E+10 |
May | 0.163076E+10 | 0.456187E+09 | 0.117457E+10 | 0.191299E+10 | 0.576470E+09 |
June | 0.150653E+10 | 0.300860E+09 | 0.120567E+10 | 0.195430E+10 | 0.355814E+09 |
July | 0.165205E+10 | 0.413171E+09 | 0.123888E+10 | 0.223271E+10 | 0.308649E+09 |
August | 0.183070E+10 | 0.633976E+09 | 0.119672E+10 | 0.248612E+10 | 0.381390E+09 |
September | 0.213904E+10 | 0.110377E+10 | 0.103527E+10 | 0.269460E+10 | 0.658955E+09 |
October | 0.238198E+10 | 0.150174E+10 | 0.880239E+09 | 0.261000E+10 | 0.108284E+10 |
November | 0.172530E+10 | 0.108019E+10 | 0.645105E+09 | 0.159511E+10 | 0.157643E+10 |
December | 0.189833E+10 | 0.143766E+10 | 0.460667E+09 | 0.175926E+10 | 0.237266E+10 |
Annual Sum or Average | 0.233441E+11 | 0.120240E+11 | 0.113200E+11 | 0.253467E+11 | 0.141115E+11 |
Minimum of Months | 0.150653E+10 | 0.300860E+09 | 0.460667E+09 | 0.159511E+10 | 0.308649E+09 |
Maximum of Months | 0.238198E+10 | 0.159136E+10 | 0.123888E+10 | 0.269460E+10 | 0.252037E+10 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.654047E+10 | 0.448117E+10 | 0.205930E+10 | 0.565129E+10 | 0.717282E+10 |
February | 0.636831E+10 | 0.432057E+10 | 0.204773E+10 | 0.577090E+10 | 0.518267E+10 |
March | 0.603958E+10 | 0.316157E+10 | 0.287800E+10 | 0.565271E+10 | 0.427280E+10 |
April | 0.521068E+10 | 0.238803E+10 | 0.282265E+10 | 0.549472E+10 | 0.304986E+10 |
May | 0.459212E+10 | 0.128459E+10 | 0.330752E+10 | 0.526791E+10 | 0.180830E+10 |
June | 0.424230E+10 | 0.847203E+09 | 0.339509E+10 | 0.541157E+10 | 0.112453E+10 |
July | 0.465206E+10 | 0.116346E+10 | 0.348860E+10 | 0.620364E+10 | 0.966592E+09 |
August | 0.515513E+10 | 0.178524E+10 | 0.336989E+10 | 0.692202E+10 | 0.119196E+10 |
September | 0.602340E+10 | 0.310816E+10 | 0.291524E+10 | 0.750945E+10 | 0.201285E+10 |
October | 0.670748E+10 | 0.422879E+10 | 0.247870E+10 | 0.726071E+10 | 0.326381E+10 |
November | 0.485833E+10 | 0.304176E+10 | 0.181657E+10 | 0.443260E+10 | 0.458657E+10 |
December | 0.534556E+10 | 0.404835E+10 | 0.129721E+10 | 0.490884E+10 | 0.677777E+10 |
Annual Sum or Average | 0.657354E+11 | 0.338589E+11 | 0.318765E+11 | 0.704864E+11 | 0.414105E+11 |
Minimum of Months | 0.424230E+10 | 0.847203E+09 | 0.129721E+10 | 0.443260E+10 | 0.966592E+09 |
Maximum of Months | 0.670748E+10 | 0.448117E+10 | 0.348860E+10 | 0.750945E+10 | 0.717282E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.849644E+10 | 0.582130E+10 | 0.267514E+10 | 0.743961E+10 | 0.971036E+10 |
February | 0.827279E+10 | 0.561267E+10 | 0.266012E+10 | 0.762582E+10 | 0.698866E+10 |
March | 0.784575E+10 | 0.410706E+10 | 0.373869E+10 | 0.746283E+10 | 0.581849E+10 |
April | 0.676897E+10 | 0.310218E+10 | 0.366678E+10 | 0.727211E+10 | 0.416733E+10 |
May | 0.596542E+10 | 0.166876E+10 | 0.429666E+10 | 0.695454E+10 | 0.247051E+10 |
June | 0.551098E+10 | 0.110057E+10 | 0.441042E+10 | 0.716419E+10 | 0.152715E+10 |
July | 0.604329E+10 | 0.151140E+10 | 0.453188E+10 | 0.822136E+10 | 0.129275E+10 |
August | 0.669681E+10 | 0.231912E+10 | 0.437768E+10 | 0.916680E+10 | 0.158625E+10 |
September | 0.782473E+10 | 0.403767E+10 | 0.378706E+10 | 0.991412E+10 | 0.272281E+10 |
October | 0.871340E+10 | 0.549344E+10 | 0.321997E+10 | 0.956554E+10 | 0.443682E+10 |
November | 0.631125E+10 | 0.395142E+10 | 0.235983E+10 | 0.581510E+10 | 0.627844E+10 |
December | 0.694419E+10 | 0.525904E+10 | 0.168515E+10 | 0.646974E+10 | 0.920356E+10 |
Annual Sum or Average | 0.853940E+11 | 0.439846E+11 | 0.414094E+11 | 0.930718E+11 | 0.562031E+11 |
Minimum of Months | 0.551098E+10 | 0.110057E+10 | 0.168515E+10 | 0.581510E+10 | 0.129275E+10 |
Maximum of Months | 0.871340E+10 | 0.582130E+10 | 0.453188E+10 | 0.991412E+10 | 0.971036E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.459231E+09 | 0.314640E+09 | 0.144591E+09 | 0.398676E+09 | 0.521766E+09 |
February | 0.447143E+09 | 0.303364E+09 | 0.143780E+09 | 0.404503E+09 | 0.377202E+09 |
March | 0.424062E+09 | 0.221986E+09 | 0.202077E+09 | 0.401240E+09 | 0.297879E+09 |
April | 0.365863E+09 | 0.167672E+09 | 0.198191E+09 | 0.390459E+09 | 0.206166E+09 |
May | 0.322432E+09 | 90196010.26 | 0.232236E+09 | 0.375356E+09 | 0.114004E+09 |
June | 0.297870E+09 | 59485281.17 | 0.238384E+09 | 0.391095E+09 | 64052322.02 |
July | 0.326641E+09 | 81690964.68 | 0.244950E+09 | 0.448576E+09 | 51465184.18 |
August | 0.361963E+09 | 0.125348E+09 | 0.236615E+09 | 0.498235E+09 | 65093040.26 |
September | 0.422927E+09 | 0.218235E+09 | 0.204691E+09 | 0.538590E+09 | 0.123597E+09 |
October | 0.470959E+09 | 0.296919E+09 | 0.174040E+09 | 0.518287E+09 | 0.215142E+09 |
November | 0.341122E+09 | 0.213573E+09 | 0.127549E+09 | 0.316292E+09 | 0.320518E+09 |
December | 0.375332E+09 | 0.284250E+09 | 91082307.95 | 0.350084E+09 | 0.481807E+09 |
Annual Sum or Average | 0.461554E+10 | 0.237736E+10 | 0.223819E+10 | 0.503139E+10 | 0.283869E+10 |
Minimum of Months | 0.297870E+09 | 59485281.17 | 91082307.95 | 0.316292E+09 | 51465184.18 |
Maximum of Months | 0.470959E+09 | 0.314640E+09 | 0.244950E+09 | 0.538590E+09 | 0.521766E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.293454E+09 | 0.119331E+09 | 0.174123E+09 | 0.123136E+09 | 0.110592E+10 |
February | 0.386849E+09 | 0.190456E+09 | 0.196393E+09 | 0.236389E+09 | 0.794711E+09 |
March | 0.511133E+09 | 0.190106E+09 | 0.321027E+09 | 0.369114E+09 | 0.575151E+09 |
April | 0.723359E+09 | 0.357960E+09 | 0.365400E+09 | 0.730048E+09 | 0.375074E+09 |
May | 0.748978E+09 | 0.299877E+09 | 0.449101E+09 | 0.849555E+09 | 0.206606E+09 |
June | 0.847924E+09 | 0.366641E+09 | 0.481284E+09 | 0.108183E+10 | 0.117904E+09 |
July | 0.941093E+09 | 0.446478E+09 | 0.494615E+09 | 0.123850E+10 | 95338708.23 |
August | 0.821685E+09 | 0.375996E+09 | 0.445689E+09 | 0.107877E+10 | 0.120686E+09 |
September | 0.645234E+09 | 0.305745E+09 | 0.339489E+09 | 0.769124E+09 | 0.229647E+09 |
October | 0.467379E+09 | 0.208801E+09 | 0.258579E+09 | 0.425567E+09 | 0.419357E+09 |
November | 0.269862E+09 | 0.100201E+09 | 0.169661E+09 | 0.158428E+09 | 0.654995E+09 |
December | 0.214648E+09 | 0.101573E+09 | 0.113075E+09 | 0.108565E+09 | 0.996695E+09 |
Annual Sum or Average | 0.687160E+10 | 0.306316E+10 | 0.380844E+10 | 0.716902E+10 | 0.569208E+10 |
Minimum of Months | 0.214648E+09 | 0.100201E+09 | 0.113075E+09 | 0.108565E+09 | 95338708.23 |
Maximum of Months | 0.941093E+09 | 0.446478E+09 | 0.494615E+09 | 0.123850E+10 | 0.110592E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 73609583.96 | 0.00 | 73609583.96 | 225061.32 | 0.633247E+09 |
February | 84291399.13 | 0.00 | 84291399.13 | 3739259.77 | 0.458232E+09 |
March | 0.139881E+09 | 1242.15 | 0.139880E+09 | 42130255.43 | 0.324142E+09 |
April | 0.156892E+09 | 1268909.30 | 0.155623E+09 | 86655852.67 | 0.205958E+09 |
May | 0.210790E+09 | 7985446.72 | 0.202805E+09 | 0.189982E+09 | 0.107865E+09 |
June | 0.238713E+09 | 22124525.26 | 0.216589E+09 | 0.281256E+09 | 64175764.52 |
July | 0.231367E+09 | 15959484.86 | 0.215408E+09 | 0.284573E+09 | 55468565.91 |
August | 0.193858E+09 | 3925624.94 | 0.189933E+09 | 0.236274E+09 | 68688535.35 |
September | 0.143564E+09 | 131474.19 | 0.143433E+09 | 0.139928E+09 | 0.128580E+09 |
October | 0.110157E+09 | 0.00 | 0.110157E+09 | 52303409.11 | 0.229853E+09 |
November | 74570442.74 | 0.00 | 74570442.74 | 12354665.79 | 0.365538E+09 |
December | 49983277.18 | 0.00 | 49983277.18 | 43072.85 | 0.556912E+09 |
Annual Sum or Average | 0.170768E+10 | 51396707.43 | 0.165628E+10 | 0.132946E+10 | 0.319866E+10 |
Minimum of Months | 49983277.18 | 0.00 | 49983277.18 | 43072.85 | 55468565.91 |
Maximum of Months | 0.238713E+09 | 22124525.26 | 0.216589E+09 | 0.284573E+09 | 0.633247E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.293454E+09 | 0.119331E+09 | 0.174123E+09 | 0.128785E+09 | 0.109778E+10 |
February | 0.386849E+09 | 0.190456E+09 | 0.196393E+09 | 0.244737E+09 | 0.784519E+09 |
March | 0.511133E+09 | 0.190106E+09 | 0.321027E+09 | 0.380030E+09 | 0.568801E+09 |
April | 0.723359E+09 | 0.357960E+09 | 0.365400E+09 | 0.735810E+09 | 0.374199E+09 |
May | 0.748978E+09 | 0.299877E+09 | 0.449101E+09 | 0.844709E+09 | 0.211173E+09 |
June | 0.847924E+09 | 0.366641E+09 | 0.481284E+09 | 0.107090E+10 | 0.125728E+09 |
July | 0.941093E+09 | 0.446478E+09 | 0.494615E+09 | 0.122591E+10 | 0.107586E+09 |
August | 0.821685E+09 | 0.375996E+09 | 0.445689E+09 | 0.107119E+10 | 0.132696E+09 |
September | 0.645234E+09 | 0.305745E+09 | 0.339489E+09 | 0.772155E+09 | 0.234114E+09 |
October | 0.467379E+09 | 0.208801E+09 | 0.258579E+09 | 0.437884E+09 | 0.413687E+09 |
November | 0.269862E+09 | 0.100201E+09 | 0.169661E+09 | 0.165728E+09 | 0.648477E+09 |
December | 0.214648E+09 | 0.101573E+09 | 0.113075E+09 | 0.115156E+09 | 0.988518E+09 |
Annual Sum or Average | 0.687160E+10 | 0.306316E+10 | 0.380844E+10 | 0.719300E+10 | 0.568728E+10 |
Minimum of Months | 0.214648E+09 | 0.100201E+09 | 0.113075E+09 | 0.115156E+09 | 0.107586E+09 |
Maximum of Months | 0.941093E+09 | 0.446478E+09 | 0.494615E+09 | 0.122591E+10 | 0.109778E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.367312E+09 | 0.251662E+09 | 0.115650E+09 | 0.325416E+09 | 0.377786E+09 |
February | 0.357643E+09 | 0.242643E+09 | 0.115001E+09 | 0.320187E+09 | 0.309589E+09 |
March | 0.339182E+09 | 0.177553E+09 | 0.161629E+09 | 0.305559E+09 | 0.265044E+09 |
April | 0.292632E+09 | 0.134111E+09 | 0.158521E+09 | 0.291185E+09 | 0.219800E+09 |
May | 0.257894E+09 | 72142461.01 | 0.185752E+09 | 0.266783E+09 | 0.140040E+09 |
June | 0.238248E+09 | 47578762.80 | 0.190670E+09 | 0.278342E+09 | 91600724.52 |
July | 0.261261E+09 | 65339777.42 | 0.195921E+09 | 0.323498E+09 | 79188430.72 |
August | 0.289513E+09 | 0.100258E+09 | 0.189254E+09 | 0.365020E+09 | 95177892.60 |
September | 0.338274E+09 | 0.174553E+09 | 0.163721E+09 | 0.401469E+09 | 0.150762E+09 |
October | 0.376692E+09 | 0.237488E+09 | 0.139204E+09 | 0.382725E+09 | 0.235702E+09 |
November | 0.272843E+09 | 0.170824E+09 | 0.102019E+09 | 0.236495E+09 | 0.295265E+09 |
December | 0.300206E+09 | 0.227355E+09 | 72851358.19 | 0.281273E+09 | 0.359371E+09 |
Annual Sum or Average | 0.369170E+10 | 0.190151E+10 | 0.179019E+10 | 0.377795E+10 | 0.261933E+10 |
Minimum of Months | 0.238248E+09 | 47578762.80 | 72851358.19 | 0.236495E+09 | 79188430.72 |
Maximum of Months | 0.376692E+09 | 0.251662E+09 | 0.195921E+09 | 0.401469E+09 | 0.377786E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 58895473.06 | 0.00 | 58895473.06 | 102477.33 | 0.522928E+09 |
February | 67442057.94 | 0.00 | 67442057.94 | 2442675.57 | 0.377269E+09 |
March | 0.111920E+09 | 993.85 | 0.111919E+09 | 32715597.57 | 0.266711E+09 |
April | 0.125530E+09 | 1015262.00 | 0.124515E+09 | 73022590.63 | 0.166454E+09 |
May | 0.168655E+09 | 6389204.19 | 0.162265E+09 | 0.160488E+09 | 84438700.93 |
June | 0.190996E+09 | 17701966.40 | 0.173294E+09 | 0.236009E+09 | 48300559.38 |
July | 0.185118E+09 | 12769280.31 | 0.172349E+09 | 0.240568E+09 | 39348600.76 |
August | 0.155107E+09 | 3140916.24 | 0.151966E+09 | 0.200462E+09 | 50194576.84 |
September | 0.114867E+09 | 105193.30 | 0.114761E+09 | 0.117970E+09 | 0.100106E+09 |
October | 88137585.25 | 0.00 | 88137585.25 | 41626693.50 | 0.187495E+09 |
November | 59664261.98 | 0.00 | 59664261.98 | 9107478.45 | 0.303965E+09 |
December | 39991922.20 | 0.00 | 39991922.20 | 8438.42 | 0.462118E+09 |
Annual Sum or Average | 0.136632E+10 | 41122816.28 | 0.132520E+10 | 0.111452E+10 | 0.260933E+10 |
Minimum of Months | 39991922.20 | 0.00 | 39991922.20 | 8438.42 | 39348600.76 |
Maximum of Months | 0.190996E+09 | 17701966.40 | 0.173294E+09 | 0.240568E+09 | 0.522928E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.293690E+09 | 0.120355E+09 | 0.173335E+09 | 0.114246E+09 | 0.108704E+10 |
February | 0.353221E+09 | 0.155464E+09 | 0.197757E+09 | 0.186169E+09 | 0.777725E+09 |
March | 0.531135E+09 | 0.210730E+09 | 0.320405E+09 | 0.385021E+09 | 0.560500E+09 |
April | 0.627343E+09 | 0.273418E+09 | 0.353925E+09 | 0.593984E+09 | 0.366494E+09 |
May | 0.819085E+09 | 0.358244E+09 | 0.460841E+09 | 0.928981E+09 | 0.195240E+09 |
June | 0.871108E+09 | 0.379482E+09 | 0.491626E+09 | 0.110858E+10 | 0.111645E+09 |
July | 0.910034E+09 | 0.420082E+09 | 0.489951E+09 | 0.118778E+10 | 89270087.09 |
August | 0.767225E+09 | 0.330645E+09 | 0.436581E+09 | 0.998052E+09 | 0.112858E+09 |
September | 0.665190E+09 | 0.315486E+09 | 0.349704E+09 | 0.791367E+09 | 0.223747E+09 |
October | 0.435280E+09 | 0.181178E+09 | 0.254102E+09 | 0.372164E+09 | 0.405737E+09 |
November | 0.249166E+09 | 80867192.16 | 0.168299E+09 | 0.122621E+09 | 0.641769E+09 |
December | 0.198698E+09 | 85074026.75 | 0.113624E+09 | 78710652.75 | 0.980574E+09 |
Annual Sum or Average | 0.672118E+10 | 0.291103E+10 | 0.381015E+10 | 0.686768E+10 | 0.555260E+10 |
Minimum of Months | 0.198698E+09 | 80867192.16 | 0.113624E+09 | 78710652.75 | 89270087.09 |
Maximum of Months | 0.910034E+09 | 0.420082E+09 | 0.491626E+09 | 0.118778E+10 | 0.108704E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.459231E+09 | 0.314640E+09 | 0.144591E+09 | 0.398028E+09 | 0.521224E+09 |
February | 0.447143E+09 | 0.303364E+09 | 0.143780E+09 | 0.403716E+09 | 0.375724E+09 |
March | 0.424062E+09 | 0.221986E+09 | 0.202077E+09 | 0.398234E+09 | 0.297092E+09 |
April | 0.365863E+09 | 0.167672E+09 | 0.198191E+09 | 0.389236E+09 | 0.203824E+09 |
May | 0.322432E+09 | 90196010.26 | 0.232236E+09 | 0.372349E+09 | 0.113426E+09 |
June | 0.297870E+09 | 59485281.17 | 0.238384E+09 | 0.388977E+09 | 63042937.79 |
July | 0.326641E+09 | 81690964.68 | 0.244950E+09 | 0.447144E+09 | 49894508.40 |
August | 0.361963E+09 | 0.125348E+09 | 0.236615E+09 | 0.497386E+09 | 63809954.14 |
September | 0.422927E+09 | 0.218235E+09 | 0.204691E+09 | 0.536363E+09 | 0.122629E+09 |
October | 0.470959E+09 | 0.296919E+09 | 0.174040E+09 | 0.516603E+09 | 0.214133E+09 |
November | 0.341122E+09 | 0.213573E+09 | 0.127549E+09 | 0.316001E+09 | 0.319794E+09 |
December | 0.375332E+09 | 0.284250E+09 | 91082307.95 | 0.350044E+09 | 0.481183E+09 |
Annual Sum or Average | 0.461554E+10 | 0.237736E+10 | 0.223819E+10 | 0.501408E+10 | 0.282578E+10 |
Minimum of Months | 0.297870E+09 | 59485281.17 | 91082307.95 | 0.316001E+09 | 49894508.40 |
Maximum of Months | 0.470959E+09 | 0.314640E+09 | 0.244950E+09 | 0.536363E+09 | 0.521224E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 73609583.96 | 0.00 | 73609583.96 | 178286.90 | 0.633167E+09 |
February | 84291399.13 | 0.00 | 84291399.13 | 3269721.26 | 0.457034E+09 |
March | 0.139881E+09 | 1242.15 | 0.139880E+09 | 40458557.83 | 0.324586E+09 |
April | 0.156892E+09 | 1268909.30 | 0.155623E+09 | 85793703.53 | 0.203333E+09 |
May | 0.210790E+09 | 7985446.72 | 0.202805E+09 | 0.187768E+09 | 0.106502E+09 |
June | 0.238713E+09 | 22124525.26 | 0.216589E+09 | 0.279100E+09 | 62352570.80 |
July | 0.231367E+09 | 15959484.86 | 0.215408E+09 | 0.282150E+09 | 52571311.46 |
August | 0.193858E+09 | 3925624.94 | 0.189933E+09 | 0.235167E+09 | 65696111.05 |
September | 0.143564E+09 | 131474.19 | 0.143433E+09 | 0.137170E+09 | 0.126705E+09 |
October | 0.110157E+09 | 0.00 | 0.110157E+09 | 50702866.60 | 0.228301E+09 |
November | 74570442.74 | 0.00 | 74570442.74 | 12042955.55 | 0.364852E+09 |
December | 49983277.18 | 0.00 | 49983277.18 | 25599.41 | 0.556880E+09 |
Annual Sum or Average | 0.170768E+10 | 51396707.43 | 0.165628E+10 | 0.131383E+10 | 0.318198E+10 |
Minimum of Months | 49983277.18 | 0.00 | 49983277.18 | 25599.41 | 52571311.46 |
Maximum of Months | 0.238713E+09 | 22124525.26 | 0.216589E+09 | 0.282150E+09 | 0.633167E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.293690E+09 | 0.120355E+09 | 0.173335E+09 | 0.117150E+09 | 0.107594E+10 |
February | 0.353221E+09 | 0.155464E+09 | 0.197757E+09 | 0.191421E+09 | 0.764068E+09 |
March | 0.531135E+09 | 0.210730E+09 | 0.320405E+09 | 0.394327E+09 | 0.552296E+09 |
April | 0.627343E+09 | 0.273418E+09 | 0.353925E+09 | 0.599968E+09 | 0.364260E+09 |
May | 0.819085E+09 | 0.358244E+09 | 0.460841E+09 | 0.927106E+09 | 0.198864E+09 |
June | 0.871108E+09 | 0.379482E+09 | 0.491626E+09 | 0.109801E+10 | 0.118188E+09 |
July | 0.910034E+09 | 0.420082E+09 | 0.489951E+09 | 0.117325E+10 | 99160091.74 |
August | 0.767225E+09 | 0.330645E+09 | 0.436581E+09 | 0.990878E+09 | 0.122347E+09 |
September | 0.665190E+09 | 0.315486E+09 | 0.349704E+09 | 0.793744E+09 | 0.226532E+09 |
October | 0.435280E+09 | 0.181178E+09 | 0.254102E+09 | 0.384223E+09 | 0.398314E+09 |
November | 0.249166E+09 | 80867192.16 | 0.168299E+09 | 0.127353E+09 | 0.632491E+09 |
December | 0.198698E+09 | 85074026.75 | 0.113624E+09 | 80831994.35 | 0.968649E+09 |
Annual Sum or Average | 0.672118E+10 | 0.291103E+10 | 0.381015E+10 | 0.687826E+10 | 0.552111E+10 |
Minimum of Months | 0.198698E+09 | 80867192.16 | 0.113624E+09 | 80831994.35 | 99160091.74 |
Maximum of Months | 0.910034E+09 | 0.420082E+09 | 0.491626E+09 | 0.117325E+10 | 0.107594E+10 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93221893.58 | 0.00 | 93221893.58 | 77511.07 | 0.847543E+09 |
February | 0.106750E+09 | 0.00 | 0.106750E+09 | 3157926.82 | 0.605029E+09 |
March | 0.177150E+09 | 1573.11 | 0.177149E+09 | 50173680.31 | 0.431837E+09 |
April | 0.198693E+09 | 1606993.56 | 0.197086E+09 | 0.113422E+09 | 0.272939E+09 |
May | 0.266953E+09 | 10113064.41 | 0.256839E+09 | 0.250536E+09 | 0.144628E+09 |
June | 0.302315E+09 | 28019315.27 | 0.274296E+09 | 0.363857E+09 | 89215804.26 |
July | 0.293012E+09 | 20211680.59 | 0.272800E+09 | 0.367449E+09 | 77031921.50 |
August | 0.245510E+09 | 4971556.29 | 0.240538E+09 | 0.304364E+09 | 95749259.32 |
September | 0.181815E+09 | 166503.77 | 0.181648E+09 | 0.177554E+09 | 0.177377E+09 |
October | 0.139507E+09 | 0.00 | 0.139507E+09 | 64251710.06 | 0.305631E+09 |
November | 94438760.59 | 0.00 | 94438760.59 | 13865248.78 | 0.493329E+09 |
December | 63300666.78 | 0.00 | 63300666.78 | 0.00 | 0.752017E+09 |
Annual Sum or Average | 0.216267E+10 | 65090687.00 | 0.209758E+10 | 0.170871E+10 | 0.429233E+10 |
Minimum of Months | 63300666.78 | 0.00 | 63300666.78 | 0.00 | 77031921.50 |
Maximum of Months | 0.302315E+09 | 28019315.27 | 0.274296E+09 | 0.367449E+09 | 0.847543E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 34365449.99 | 0.00 | 34365449.99 | 28573.79 | 0.312440E+09 |
February | 39352373.77 | 0.00 | 39352373.77 | 1164142.59 | 0.223039E+09 |
March | 65304963.22 | 579.91 | 65304383.30 | 18496096.09 | 0.159193E+09 |
April | 73246539.20 | 592404.37 | 72654134.83 | 41811906.69 | 0.100617E+09 |
May | 98409767.03 | 3728094.29 | 94681672.73 | 92357782.98 | 53315819.42 |
June | 0.111446E+09 | 10329079.80 | 0.101117E+09 | 0.134133E+09 | 32888639.59 |
July | 0.108016E+09 | 7450862.37 | 0.100566E+09 | 0.135457E+09 | 28397155.91 |
August | 90504969.44 | 1832721.51 | 88672247.94 | 0.112201E+09 | 35297141.65 |
September | 67024524.33 | 61380.18 | 66963144.15 | 65453934.26 | 65388510.58 |
October | 51428193.38 | 0.00 | 51428193.38 | 23685840.78 | 0.112668E+09 |
November | 34814037.56 | 0.00 | 34814037.56 | 5111304.81 | 0.181861E+09 |
December | 23335246.85 | 0.00 | 23335246.85 | 0.00 | 0.277224E+09 |
Annual Sum or Average | 0.797248E+09 | 23995122.42 | 0.773253E+09 | 0.629901E+09 | 0.158233E+10 |
Minimum of Months | 23335246.85 | 0.00 | 23335246.85 | 0.00 | 28397155.91 |
Maximum of Months | 0.111446E+09 | 10329079.80 | 0.101117E+09 | 0.135457E+09 | 0.312440E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214275E+09 | 0.146810E+09 | 67465805.62 | 0.183974E+09 | 0.253407E+09 |
February | 0.208635E+09 | 0.141548E+09 | 67086999.07 | 0.189116E+09 | 0.180414E+09 |
March | 0.197866E+09 | 0.103578E+09 | 94288199.77 | 0.187853E+09 | 0.144193E+09 |
April | 0.170710E+09 | 78235132.85 | 92474964.41 | 0.184823E+09 | 0.100327E+09 |
May | 0.150445E+09 | 42085094.92 | 0.108360E+09 | 0.177796E+09 | 57592882.92 |
June | 0.138985E+09 | 27755592.49 | 0.111229E+09 | 0.182804E+09 | 35299129.29 |
July | 0.152409E+09 | 38116674.93 | 0.114293E+09 | 0.209002E+09 | 30041912.47 |
August | 0.168890E+09 | 58486891.36 | 0.110404E+09 | 0.232768E+09 | 37076203.29 |
September | 0.197336E+09 | 0.101828E+09 | 95508225.40 | 0.252123E+09 | 64222236.60 |
October | 0.219747E+09 | 0.138541E+09 | 81206153.04 | 0.244431E+09 | 0.103887E+09 |
November | 0.159166E+09 | 99652319.79 | 59513840.21 | 0.147072E+09 | 0.156661E+09 |
December | 0.175129E+09 | 0.132630E+09 | 42498637.86 | 0.162414E+09 | 0.236059E+09 |
Annual Sum or Average | 0.215359E+10 | 0.110927E+10 | 0.104433E+10 | 0.235418E+10 | 0.139918E+10 |
Minimum of Months | 0.138985E+09 | 27755592.49 | 42498637.86 | 0.147072E+09 | 30041912.47 |
Maximum of Months | 0.219747E+09 | 0.146810E+09 | 0.114293E+09 | 0.252123E+09 | 0.253407E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.581588E+09 | 0.398472E+09 | 0.183116E+09 | 0.499344E+09 | 0.687799E+09 |
February | 0.566279E+09 | 0.384191E+09 | 0.182088E+09 | 0.513298E+09 | 0.489680E+09 |
March | 0.537048E+09 | 0.281131E+09 | 0.255917E+09 | 0.509872E+09 | 0.391369E+09 |
April | 0.463342E+09 | 0.212346E+09 | 0.250996E+09 | 0.501647E+09 | 0.272308E+09 |
May | 0.408340E+09 | 0.114228E+09 | 0.294112E+09 | 0.482574E+09 | 0.156319E+09 |
June | 0.377233E+09 | 75334355.29 | 0.301899E+09 | 0.496169E+09 | 95809057.18 |
July | 0.413670E+09 | 0.103456E+09 | 0.310214E+09 | 0.567273E+09 | 81539895.39 |
August | 0.458403E+09 | 0.158745E+09 | 0.299658E+09 | 0.631781E+09 | 0.100632E+09 |
September | 0.535610E+09 | 0.276381E+09 | 0.259229E+09 | 0.684314E+09 | 0.174312E+09 |
October | 0.596439E+09 | 0.376029E+09 | 0.220410E+09 | 0.663435E+09 | 0.281970E+09 |
November | 0.432010E+09 | 0.270477E+09 | 0.161533E+09 | 0.399184E+09 | 0.425210E+09 |
December | 0.475335E+09 | 0.359985E+09 | 0.115350E+09 | 0.440824E+09 | 0.640712E+09 |
Annual Sum or Average | 0.584530E+10 | 0.301077E+10 | 0.283452E+10 | 0.638972E+10 | 0.379766E+10 |
Minimum of Months | 0.377233E+09 | 75334355.29 | 0.115350E+09 | 0.399184E+09 | 81539895.39 |
Maximum of Months | 0.596439E+09 | 0.398472E+09 | 0.310214E+09 | 0.684314E+09 | 0.687799E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.459231E+09 | 0.314640E+09 | 0.144591E+09 | 0.396947E+09 | 0.522393E+09 |
February | 0.447143E+09 | 0.303364E+09 | 0.143780E+09 | 0.402527E+09 | 0.377408E+09 |
March | 0.424062E+09 | 0.221986E+09 | 0.202077E+09 | 0.399732E+09 | 0.297450E+09 |
April | 0.365863E+09 | 0.167672E+09 | 0.198191E+09 | 0.388072E+09 | 0.205356E+09 |
May | 0.322432E+09 | 90196010.26 | 0.232236E+09 | 0.372188E+09 | 0.113419E+09 |
June | 0.297870E+09 | 59485281.17 | 0.238384E+09 | 0.388517E+09 | 63044211.36 |
July | 0.326641E+09 | 81690964.68 | 0.244950E+09 | 0.445746E+09 | 50350744.97 |
August | 0.361963E+09 | 0.125348E+09 | 0.236615E+09 | 0.495172E+09 | 64101498.93 |
September | 0.422927E+09 | 0.218235E+09 | 0.204691E+09 | 0.536405E+09 | 0.121870E+09 |
October | 0.470959E+09 | 0.296919E+09 | 0.174040E+09 | 0.516365E+09 | 0.213983E+09 |
November | 0.341122E+09 | 0.213573E+09 | 0.127549E+09 | 0.315574E+09 | 0.319754E+09 |
December | 0.375332E+09 | 0.284250E+09 | 91082307.95 | 0.349378E+09 | 0.481640E+09 |
Annual Sum or Average | 0.461554E+10 | 0.237736E+10 | 0.223819E+10 | 0.500662E+10 | 0.283077E+10 |
Minimum of Months | 0.297870E+09 | 59485281.17 | 91082307.95 | 0.315574E+09 | 50350744.97 |
Maximum of Months | 0.470959E+09 | 0.314640E+09 | 0.244950E+09 | 0.536405E+09 | 0.522393E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.293454E+09 | 0.119331E+09 | 0.174123E+09 | 0.122354E+09 | 0.110893E+10 |
February | 0.386849E+09 | 0.190456E+09 | 0.196393E+09 | 0.234394E+09 | 0.797106E+09 |
March | 0.511133E+09 | 0.190106E+09 | 0.321027E+09 | 0.367234E+09 | 0.574340E+09 |
April | 0.723359E+09 | 0.357960E+09 | 0.365400E+09 | 0.725147E+09 | 0.373358E+09 |
May | 0.748978E+09 | 0.299877E+09 | 0.449101E+09 | 0.843402E+09 | 0.205265E+09 |
June | 0.847924E+09 | 0.366641E+09 | 0.481284E+09 | 0.107589E+10 | 0.115966E+09 |
July | 0.941093E+09 | 0.446478E+09 | 0.494615E+09 | 0.123191E+10 | 93193183.61 |
August | 0.821685E+09 | 0.375996E+09 | 0.445689E+09 | 0.107279E+10 | 0.118722E+09 |
September | 0.645234E+09 | 0.305745E+09 | 0.339489E+09 | 0.766086E+09 | 0.226413E+09 |
October | 0.467379E+09 | 0.208801E+09 | 0.258579E+09 | 0.423407E+09 | 0.416813E+09 |
November | 0.269862E+09 | 0.100201E+09 | 0.169661E+09 | 0.158644E+09 | 0.653042E+09 |
December | 0.214648E+09 | 0.101573E+09 | 0.113075E+09 | 0.108522E+09 | 0.997229E+09 |
Annual Sum or Average | 0.687160E+10 | 0.306316E+10 | 0.380844E+10 | 0.712978E+10 | 0.568038E+10 |
Minimum of Months | 0.214648E+09 | 0.100201E+09 | 0.113075E+09 | 0.108522E+09 | 93193183.61 |
Maximum of Months | 0.941093E+09 | 0.446478E+09 | 0.494615E+09 | 0.123191E+10 | 0.110893E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 73609583.96 | 0.00 | 73609583.96 | 254639.21 | 0.635038E+09 |
February | 84291399.13 | 0.00 | 84291399.13 | 3841973.13 | 0.459192E+09 |
March | 0.139881E+09 | 1242.15 | 0.139880E+09 | 42573968.59 | 0.323578E+09 |
April | 0.156892E+09 | 1268909.30 | 0.155623E+09 | 86022603.47 | 0.205607E+09 |
May | 0.210790E+09 | 7985446.72 | 0.202805E+09 | 0.187198E+09 | 0.108296E+09 |
June | 0.238713E+09 | 22124525.26 | 0.216589E+09 | 0.278457E+09 | 64468316.34 |
July | 0.231367E+09 | 15959484.86 | 0.215408E+09 | 0.282055E+09 | 55929954.95 |
August | 0.193858E+09 | 3925624.94 | 0.189933E+09 | 0.234460E+09 | 69384052.48 |
September | 0.143564E+09 | 131474.19 | 0.143433E+09 | 0.139877E+09 | 0.127515E+09 |
October | 0.110157E+09 | 0.00 | 0.110157E+09 | 53151760.34 | 0.228090E+09 |
November | 74570442.74 | 0.00 | 74570442.74 | 12830679.39 | 0.363987E+09 |
December | 49983277.18 | 0.00 | 49983277.18 | 57075.87 | 0.557285E+09 |
Annual Sum or Average | 0.170768E+10 | 51396707.43 | 0.165628E+10 | 0.132078E+10 | 0.319837E+10 |
Minimum of Months | 49983277.18 | 0.00 | 49983277.18 | 57075.87 | 55929954.95 |
Maximum of Months | 0.238713E+09 | 22124525.26 | 0.216589E+09 | 0.282055E+09 | 0.635038E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.293454E+09 | 0.119331E+09 | 0.174123E+09 | 0.127630E+09 | 0.110086E+10 |
February | 0.386849E+09 | 0.190456E+09 | 0.196393E+09 | 0.243007E+09 | 0.786822E+09 |
March | 0.511133E+09 | 0.190106E+09 | 0.321027E+09 | 0.378831E+09 | 0.568029E+09 |
April | 0.723359E+09 | 0.357960E+09 | 0.365400E+09 | 0.731266E+09 | 0.372797E+09 |
May | 0.748978E+09 | 0.299877E+09 | 0.449101E+09 | 0.837181E+09 | 0.211418E+09 |
June | 0.847924E+09 | 0.366641E+09 | 0.481284E+09 | 0.106341E+10 | 0.125991E+09 |
July | 0.941093E+09 | 0.446478E+09 | 0.494615E+09 | 0.121814E+10 | 0.108182E+09 |
August | 0.821685E+09 | 0.375996E+09 | 0.445689E+09 | 0.106437E+10 | 0.133557E+09 |
September | 0.645234E+09 | 0.305745E+09 | 0.339489E+09 | 0.769374E+09 | 0.231923E+09 |
October | 0.467379E+09 | 0.208801E+09 | 0.258579E+09 | 0.437243E+09 | 0.410643E+09 |
November | 0.269862E+09 | 0.100201E+09 | 0.169661E+09 | 0.166324E+09 | 0.646600E+09 |
December | 0.214648E+09 | 0.101573E+09 | 0.113075E+09 | 0.115039E+09 | 0.989718E+09 |
Annual Sum or Average | 0.687160E+10 | 0.306316E+10 | 0.380844E+10 | 0.715182E+10 | 0.568654E+10 |
Minimum of Months | 0.214648E+09 | 0.100201E+09 | 0.113075E+09 | 0.115039E+09 | 0.108182E+09 |
Maximum of Months | 0.941093E+09 | 0.446478E+09 | 0.494615E+09 | 0.121814E+10 | 0.110086E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.673507E+09 | 0.461450E+09 | 0.212057E+09 | 0.561690E+09 | 0.787227E+09 |
February | 0.655778E+09 | 0.444912E+09 | 0.210867E+09 | 0.572242E+09 | 0.571979E+09 |
March | 0.621928E+09 | 0.325563E+09 | 0.296365E+09 | 0.571690E+09 | 0.447900E+09 |
April | 0.536573E+09 | 0.245907E+09 | 0.290666E+09 | 0.565968E+09 | 0.304178E+09 |
May | 0.472877E+09 | 0.132281E+09 | 0.340596E+09 | 0.547683E+09 | 0.165130E+09 |
June | 0.436855E+09 | 87240873.66 | 0.349614E+09 | 0.576438E+09 | 89843278.94 |
July | 0.479050E+09 | 0.119808E+09 | 0.359242E+09 | 0.662393E+09 | 69408586.14 |
August | 0.530853E+09 | 0.183835E+09 | 0.347018E+09 | 0.731580E+09 | 90776813.42 |
September | 0.620262E+09 | 0.320063E+09 | 0.300200E+09 | 0.783926E+09 | 0.179719E+09 |
October | 0.690706E+09 | 0.435460E+09 | 0.255246E+09 | 0.744894E+09 | 0.323291E+09 |
November | 0.500288E+09 | 0.313225E+09 | 0.187063E+09 | 0.449262E+09 | 0.485050E+09 |
December | 0.550461E+09 | 0.416880E+09 | 0.133581E+09 | 0.496583E+09 | 0.726885E+09 |
Annual Sum or Average | 0.676914E+10 | 0.348662E+10 | 0.328251E+10 | 0.726435E+10 | 0.424139E+10 |
Minimum of Months | 0.436855E+09 | 87240873.66 | 0.133581E+09 | 0.449262E+09 | 69408586.14 |
Maximum of Months | 0.690706E+09 | 0.461450E+09 | 0.359242E+09 | 0.783926E+09 | 0.787227E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.515248E+09 | 0.00 | 0.515248E+09 | 9186.53 | 0.489291E+10 |
February | 0.590017E+09 | 0.00 | 0.590017E+09 | 8972960.28 | 0.353946E+10 |
March | 0.979129E+09 | 8694.74 | 0.979121E+09 | 0.212985E+09 | 0.266895E+10 |
April | 0.109820E+10 | 8882028.68 | 0.108932E+10 | 0.538464E+09 | 0.172503E+10 |
May | 0.147548E+10 | 55896009.98 | 0.141958E+10 | 0.123860E+10 | 0.904088E+09 |
June | 0.167093E+10 | 0.154866E+09 | 0.151606E+10 | 0.190770E+10 | 0.549102E+09 |
July | 0.161951E+10 | 0.111712E+09 | 0.150780E+10 | 0.195077E+10 | 0.455265E+09 |
August | 0.135696E+10 | 27478333.85 | 0.132948E+10 | 0.160359E+10 | 0.569462E+09 |
September | 0.100491E+10 | 920284.50 | 0.100399E+10 | 0.914923E+09 | 0.107286E+10 |
October | 0.771072E+09 | 0.00 | 0.771072E+09 | 0.273773E+09 | 0.192955E+10 |
November | 0.521973E+09 | 0.00 | 0.521973E+09 | 51815400.38 | 0.300005E+10 |
December | 0.349870E+09 | 0.00 | 0.349870E+09 | 0.00 | 0.444208E+10 |
Annual Sum or Average | 0.119533E+11 | 0.359763E+09 | 0.115935E+11 | 0.870160E+10 | 0.257488E+11 |
Minimum of Months | 0.349870E+09 | 0.00 | 0.349870E+09 | 0.00 | 0.455265E+09 |
Maximum of Months | 0.167093E+10 | 0.154866E+09 | 0.151606E+10 | 0.195077E+10 | 0.489291E+10 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.515248E+09 | 0.00 | 0.515248E+09 | 0.00 | 0.498683E+10 |
February | 0.590017E+09 | 0.00 | 0.590017E+09 | 6784937.98 | 0.361467E+10 |
March | 0.979129E+09 | 8694.74 | 0.979121E+09 | 0.194877E+09 | 0.273644E+10 |
April | 0.109820E+10 | 8882028.68 | 0.108932E+10 | 0.517101E+09 | 0.177154E+10 |
May | 0.147548E+10 | 55896009.98 | 0.141958E+10 | 0.120846E+10 | 0.925975E+09 |
June | 0.167093E+10 | 0.154866E+09 | 0.151606E+10 | 0.188419E+10 | 0.564709E+09 |
July | 0.161951E+10 | 0.111712E+09 | 0.150780E+10 | 0.192888E+10 | 0.468756E+09 |
August | 0.135696E+10 | 27478333.85 | 0.132948E+10 | 0.158188E+10 | 0.585516E+09 |
September | 0.100491E+10 | 920284.50 | 0.100399E+10 | 0.893934E+09 | 0.109970E+10 |
October | 0.771072E+09 | 0.00 | 0.771072E+09 | 0.251650E+09 | 0.197975E+10 |
November | 0.521973E+09 | 0.00 | 0.521973E+09 | 45022338.88 | 0.307561E+10 |
December | 0.349870E+09 | 0.00 | 0.349870E+09 | 0.00 | 0.453935E+10 |
Annual Sum or Average | 0.119533E+11 | 0.359763E+09 | 0.115935E+11 | 0.851278E+10 | 0.263489E+11 |
Minimum of Months | 0.349870E+09 | 0.00 | 0.349870E+09 | 0.00 | 0.468756E+09 |
Maximum of Months | 0.167093E+10 | 0.154866E+09 | 0.151606E+10 | 0.192888E+10 | 0.498683E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 73609583.96 | 0.00 | 73609583.96 | 292007.43 | 0.631151E+09 |
February | 84291399.13 | 0.00 | 84291399.13 | 4190415.99 | 0.447904E+09 |
March | 0.139881E+09 | 1242.15 | 0.139880E+09 | 49198028.79 | 0.337650E+09 |
April | 0.156892E+09 | 1268909.30 | 0.155623E+09 | 0.110871E+09 | 0.214698E+09 |
May | 0.210790E+09 | 7985446.72 | 0.202805E+09 | 0.242356E+09 | 0.118956E+09 |
June | 0.238713E+09 | 22124525.26 | 0.216589E+09 | 0.344931E+09 | 73706939.24 |
July | 0.231367E+09 | 15959484.86 | 0.215408E+09 | 0.356748E+09 | 60887522.20 |
August | 0.193858E+09 | 3925624.94 | 0.189933E+09 | 0.302165E+09 | 74181427.75 |
September | 0.143564E+09 | 131474.19 | 0.143433E+09 | 0.182672E+09 | 0.132618E+09 |
October | 0.110157E+09 | 0.00 | 0.110157E+09 | 67973231.14 | 0.236012E+09 |
November | 74570442.74 | 0.00 | 74570442.74 | 17679579.37 | 0.373654E+09 |
December | 49983277.18 | 0.00 | 49983277.18 | 85965.10 | 0.570741E+09 |
Annual Sum or Average | 0.170768E+10 | 51396707.43 | 0.165628E+10 | 0.167916E+10 | 0.327216E+10 |
Minimum of Months | 49983277.18 | 0.00 | 49983277.18 | 85965.10 | 60887522.20 |
Maximum of Months | 0.238713E+09 | 22124525.26 | 0.216589E+09 | 0.356748E+09 | 0.631151E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.587339E+09 | 0.240693E+09 | 0.346645E+09 | 0.252032E+09 | 0.215711E+10 |
February | 0.706392E+09 | 0.310906E+09 | 0.395485E+09 | 0.407974E+09 | 0.150496E+10 |
March | 0.106219E+10 | 0.421431E+09 | 0.640764E+09 | 0.837663E+09 | 0.116079E+10 |
April | 0.125460E+10 | 0.546798E+09 | 0.707799E+09 | 0.130360E+10 | 0.778402E+09 |
May | 0.163805E+10 | 0.716437E+09 | 0.921616E+09 | 0.205631E+10 | 0.441828E+09 |
June | 0.174209E+10 | 0.758910E+09 | 0.983183E+09 | 0.243868E+10 | 0.276355E+09 |
July | 0.181994E+10 | 0.840105E+09 | 0.979833E+09 | 0.262462E+10 | 0.227930E+09 |
August | 0.153434E+10 | 0.661242E+09 | 0.873100E+09 | 0.223217E+10 | 0.277041E+09 |
September | 0.133028E+10 | 0.630927E+09 | 0.699358E+09 | 0.176975E+10 | 0.481816E+09 |
October | 0.870498E+09 | 0.362331E+09 | 0.508168E+09 | 0.852448E+09 | 0.833391E+09 |
November | 0.498298E+09 | 0.161723E+09 | 0.336575E+09 | 0.283770E+09 | 0.130710E+10 |
December | 0.397368E+09 | 0.170136E+09 | 0.227232E+09 | 0.169209E+09 | 0.198840E+10 |
Annual Sum or Average | 0.134414E+11 | 0.582164E+10 | 0.761976E+10 | 0.152282E+11 | 0.114351E+11 |
Minimum of Months | 0.397368E+09 | 0.161723E+09 | 0.227232E+09 | 0.169209E+09 | 0.227930E+09 |
Maximum of Months | 0.181994E+10 | 0.840105E+09 | 0.983183E+09 | 0.262462E+10 | 0.215711E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.459231E+09 | 0.314640E+09 | 0.144591E+09 | 0.408515E+09 | 0.518976E+09 |
February | 0.447143E+09 | 0.303364E+09 | 0.143780E+09 | 0.421699E+09 | 0.369622E+09 |
March | 0.424062E+09 | 0.221986E+09 | 0.202077E+09 | 0.419339E+09 | 0.309250E+09 |
April | 0.365863E+09 | 0.167672E+09 | 0.198191E+09 | 0.420436E+09 | 0.214330E+09 |
May | 0.322432E+09 | 90196010.26 | 0.232236E+09 | 0.424936E+09 | 0.125674E+09 |
June | 0.297870E+09 | 59485281.17 | 0.238384E+09 | 0.447989E+09 | 77494473.62 |
July | 0.326641E+09 | 81690964.68 | 0.244950E+09 | 0.513488E+09 | 62969208.84 |
August | 0.361963E+09 | 0.125348E+09 | 0.236615E+09 | 0.559236E+09 | 76590041.81 |
September | 0.422927E+09 | 0.218235E+09 | 0.204691E+09 | 0.585881E+09 | 0.131139E+09 |
October | 0.470959E+09 | 0.296919E+09 | 0.174040E+09 | 0.550011E+09 | 0.223122E+09 |
November | 0.341122E+09 | 0.213573E+09 | 0.127549E+09 | 0.330204E+09 | 0.328449E+09 |
December | 0.375332E+09 | 0.284250E+09 | 91082307.95 | 0.358495E+09 | 0.490449E+09 |
Annual Sum or Average | 0.461554E+10 | 0.237736E+10 | 0.223819E+10 | 0.544023E+10 | 0.292807E+10 |
Minimum of Months | 0.297870E+09 | 59485281.17 | 91082307.95 | 0.330204E+09 | 62969208.84 |
Maximum of Months | 0.470959E+09 | 0.314640E+09 | 0.244950E+09 | 0.585881E+09 | 0.518976E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93221893.58 | 0.00 | 93221893.58 | 29990.33 | 0.854920E+09 |
February | 0.106750E+09 | 0.00 | 0.106750E+09 | 2426888.37 | 0.606283E+09 |
March | 0.177150E+09 | 1573.11 | 0.177149E+09 | 46178523.83 | 0.440109E+09 |
April | 0.198693E+09 | 1606993.56 | 0.197086E+09 | 0.106271E+09 | 0.278930E+09 |
May | 0.266953E+09 | 10113064.41 | 0.256839E+09 | 0.239225E+09 | 0.148940E+09 |
June | 0.302315E+09 | 28019315.27 | 0.274296E+09 | 0.351167E+09 | 93420129.34 |
July | 0.293012E+09 | 20211680.59 | 0.272800E+09 | 0.355389E+09 | 80612913.59 |
August | 0.245510E+09 | 4971556.29 | 0.240538E+09 | 0.293479E+09 | 99689019.60 |
September | 0.181815E+09 | 166503.77 | 0.181648E+09 | 0.170871E+09 | 0.179118E+09 |
October | 0.139507E+09 | 0.00 | 0.139507E+09 | 58693286.34 | 0.311403E+09 |
November | 94438760.59 | 0.00 | 94438760.59 | 12374978.28 | 0.501403E+09 |
December | 63300666.78 | 0.00 | 63300666.78 | 0.00 | 0.762722E+09 |
Annual Sum or Average | 0.216267E+10 | 65090687.00 | 0.209758E+10 | 0.163611E+10 | 0.435755E+10 |
Minimum of Months | 63300666.78 | 0.00 | 63300666.78 | 0.00 | 80612913.59 |
Maximum of Months | 0.302315E+09 | 28019315.27 | 0.274296E+09 | 0.355389E+09 | 0.854920E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 83405981.40 | 0.00 | 83405981.40 | 26832.46 | 0.764861E+09 |
February | 95509395.51 | 0.00 | 95509395.51 | 2171346.22 | 0.542444E+09 |
March | 0.158497E+09 | 1407.47 | 0.158496E+09 | 41316100.24 | 0.393767E+09 |
April | 0.177772E+09 | 1437783.23 | 0.176334E+09 | 95081353.85 | 0.249559E+09 |
May | 0.238843E+09 | 9048197.05 | 0.229795E+09 | 0.214035E+09 | 0.133257E+09 |
June | 0.270483E+09 | 25068987.53 | 0.245414E+09 | 0.314190E+09 | 83583343.69 |
July | 0.262159E+09 | 18083467.21 | 0.244076E+09 | 0.317968E+09 | 72124679.23 |
August | 0.219658E+09 | 4448070.25 | 0.215210E+09 | 0.262577E+09 | 89192143.56 |
September | 0.162671E+09 | 148971.55 | 0.162522E+09 | 0.152879E+09 | 0.160258E+09 |
October | 0.124818E+09 | 0.00 | 0.124818E+09 | 52513105.68 | 0.278613E+09 |
November | 84494716.93 | 0.00 | 84494716.93 | 11071939.96 | 0.448596E+09 |
December | 56635346.41 | 0.00 | 56635346.41 | 0.00 | 0.682370E+09 |
Annual Sum or Average | 0.193495E+10 | 58236884.29 | 0.187671E+10 | 0.146383E+10 | 0.389863E+10 |
Minimum of Months | 56635346.41 | 0.00 | 56635346.41 | 0.00 | 72124679.23 |
Maximum of Months | 0.270483E+09 | 25068987.53 | 0.245414E+09 | 0.317968E+09 | 0.764861E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.171445E+10 | 0.117464E+10 | 0.539803E+09 | 0.145621E+10 | 0.204001E+10 |
February | 0.166932E+10 | 0.113255E+10 | 0.536772E+09 | 0.150039E+10 | 0.144394E+10 |
March | 0.158315E+10 | 0.828739E+09 | 0.754413E+09 | 0.147705E+10 | 0.117300E+10 |
April | 0.136587E+10 | 0.625970E+09 | 0.739905E+09 | 0.145043E+10 | 0.820057E+09 |
May | 0.120373E+10 | 0.336729E+09 | 0.867005E+09 | 0.138589E+10 | 0.475374E+09 |
June | 0.111204E+10 | 0.222076E+09 | 0.889960E+09 | 0.142359E+10 | 0.296472E+09 |
July | 0.121945E+10 | 0.304977E+09 | 0.914471E+09 | 0.163375E+10 | 0.252216E+09 |
August | 0.135132E+10 | 0.467962E+09 | 0.883354E+09 | 0.182489E+10 | 0.309701E+09 |
September | 0.157891E+10 | 0.814737E+09 | 0.764174E+09 | 0.199003E+10 | 0.519702E+09 |
October | 0.175823E+10 | 0.110849E+10 | 0.649742E+09 | 0.192614E+10 | 0.845824E+09 |
November | 0.127351E+10 | 0.797332E+09 | 0.476178E+09 | 0.115846E+10 | 0.127313E+10 |
December | 0.140123E+10 | 0.106119E+10 | 0.340037E+09 | 0.128460E+10 | 0.191049E+10 |
Annual Sum or Average | 0.172312E+11 | 0.887539E+10 | 0.835581E+10 | 0.185114E+11 | 0.113599E+11 |
Minimum of Months | 0.111204E+10 | 0.222076E+09 | 0.340037E+09 | 0.115846E+10 | 0.252216E+09 |
Maximum of Months | 0.175823E+10 | 0.117464E+10 | 0.914471E+09 | 0.199003E+10 | 0.204001E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 755.55 | 941.00 | 867.18 | 594.15 | 273.04 | 0.00 | 0.00 |
February | 854.73 | 742.80 | 934.82 | 634.23 | 300.59 | 0.00 | 0.00 |
March | 759.62 | 545.19 | 800.77 | 419.18 | 381.59 | 0.00 | 0.00 |
April | 762.18 | 393.79 | 713.90 | 327.18 | 386.72 | 0.00 | 0.00 |
May | 714.23 | 215.23 | 608.86 | 170.32 | 438.54 | 0.00 | 0.00 |
June | 753.97 | 137.27 | 581.22 | 116.07 | 465.15 | 0.00 | 0.00 |
July | 833.60 | 115.24 | 616.80 | 154.26 | 462.54 | 0.00 | 0.00 |
August | 928.21 | 142.39 | 683.50 | 236.70 | 446.81 | 0.00 | 0.00 |
September | 1039.58 | 254.23 | 825.25 | 425.84 | 399.41 | 0.00 | 0.00 |
October | 974.46 | 404.28 | 889.33 | 560.68 | 328.64 | 0.00 | 0.00 |
November | 615.40 | 608.19 | 665.62 | 416.74 | 248.88 | 0.00 | 0.00 |
December | 656.83 | 885.85 | 708.75 | 536.76 | 171.99 | 0.00 | 0.00 |
Annual Sum or Average | 803.74 | 447.47 | 740.24 | 381.28 | 358.96 | 0.00 | 0.00 |
Minimum of Months | 615.40 | 115.24 | 581.22 | 116.07 | 171.99 | 0.00 | 0.00 |
Maximum of Months | 1039.58 | 941.00 | 934.82 | 634.23 | 465.15 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2109.95 | 2678.02 | 2441.93 | 1673.08 | 768.85 | 0.00 | 0.00 |
February | 2385.46 | 2142.31 | 2632.40 | 1785.95 | 846.45 | 0.00 | 0.00 |
March | 2110.48 | 1595.28 | 2254.92 | 1180.40 | 1074.52 | 0.00 | 0.00 |
April | 2119.88 | 1176.64 | 2010.29 | 921.31 | 1088.99 | 0.00 | 0.00 |
May | 1966.81 | 675.14 | 1714.50 | 479.61 | 1234.89 | 0.00 | 0.00 |
June | 2087.80 | 433.85 | 1636.69 | 326.85 | 1309.83 | 0.00 | 0.00 |
July | 2316.17 | 360.88 | 1736.88 | 434.39 | 1302.49 | 0.00 | 0.00 |
August | 2584.39 | 445.03 | 1924.70 | 666.53 | 1258.17 | 0.00 | 0.00 |
September | 2897.16 | 776.56 | 2323.84 | 1199.13 | 1124.71 | 0.00 | 0.00 |
October | 2710.84 | 1218.57 | 2504.29 | 1578.85 | 925.44 | 0.00 | 0.00 |
November | 1710.11 | 1769.51 | 1874.36 | 1173.52 | 700.84 | 0.00 | 0.00 |
December | 1832.75 | 2530.53 | 1995.80 | 1511.48 | 484.32 | 0.00 | 0.00 |
Annual Sum or Average | 2235.11 | 1313.12 | 2084.46 | 1073.66 | 1010.80 | 0.00 | 0.00 |
Minimum of Months | 1710.11 | 360.88 | 1636.69 | 326.85 | 484.32 | 0.00 | 0.00 |
Maximum of Months | 2897.16 | 2678.02 | 2632.40 | 1785.95 | 1309.83 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2777.63 | 3625.43 | 3172.21 | 2173.42 | 998.78 | 0.00 | 0.00 |
February | 3152.21 | 2888.83 | 3419.64 | 2320.05 | 1099.59 | 0.00 | 0.00 |
March | 2786.30 | 2172.38 | 2929.27 | 1533.40 | 1395.87 | 0.00 | 0.00 |
April | 2805.60 | 1607.77 | 2611.48 | 1196.83 | 1414.65 | 0.00 | 0.00 |
May | 2596.53 | 922.38 | 2227.23 | 623.04 | 1604.19 | 0.00 | 0.00 |
June | 2763.96 | 589.18 | 2126.15 | 424.60 | 1701.55 | 0.00 | 0.00 |
July | 3069.50 | 482.66 | 2256.31 | 564.29 | 1692.01 | 0.00 | 0.00 |
August | 3422.49 | 592.24 | 2500.30 | 865.86 | 1634.44 | 0.00 | 0.00 |
September | 3824.89 | 1050.47 | 3018.80 | 1557.74 | 1461.06 | 0.00 | 0.00 |
October | 3571.36 | 1656.52 | 3253.21 | 2051.01 | 1202.20 | 0.00 | 0.00 |
November | 2243.48 | 2422.24 | 2434.89 | 1524.47 | 910.43 | 0.00 | 0.00 |
December | 2415.52 | 3436.22 | 2592.66 | 1963.50 | 629.16 | 0.00 | 0.00 |
Annual Sum or Average | 2951.29 | 1782.19 | 2707.83 | 1394.74 | 1313.08 | 0.00 | 0.00 |
Minimum of Months | 2243.48 | 482.66 | 2126.15 | 424.60 | 629.16 | 0.00 | 0.00 |
Maximum of Months | 3824.89 | 3625.43 | 3419.64 | 2320.05 | 1701.55 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 160.89 | 573.77 | 281.02 | 162.03 | 118.99 | 0.00 | 0.00 |
February | 238.84 | 458.35 | 344.74 | 204.13 | 140.61 | 0.00 | 0.00 |
March | 279.61 | 317.94 | 349.16 | 153.86 | 195.30 | 0.00 | 0.00 |
April | 429.17 | 221.12 | 420.22 | 202.79 | 217.43 | 0.00 | 0.00 |
May | 456.36 | 118.73 | 400.02 | 145.64 | 254.38 | 0.00 | 0.00 |
June | 567.98 | 69.92 | 442.05 | 164.40 | 277.65 | 0.00 | 0.00 |
July | 629.76 | 54.69 | 473.32 | 197.20 | 276.12 | 0.00 | 0.00 |
August | 588.57 | 69.14 | 441.92 | 187.18 | 254.74 | 0.00 | 0.00 |
September | 503.27 | 135.03 | 412.10 | 202.15 | 209.95 | 0.00 | 0.00 |
October | 348.12 | 232.62 | 350.34 | 188.81 | 161.52 | 0.00 | 0.00 |
November | 170.68 | 363.89 | 235.72 | 121.05 | 114.66 | 0.00 | 0.00 |
December | 148.85 | 529.62 | 220.27 | 144.05 | 76.22 | 0.00 | 0.00 |
Annual Sum or Average | 377.53 | 261.16 | 364.25 | 172.52 | 191.74 | 0.00 | 0.00 |
Minimum of Months | 148.85 | 54.69 | 220.27 | 121.05 | 76.22 | 0.00 | 0.00 |
Maximum of Months | 629.76 | 573.77 | 473.32 | 204.13 | 277.65 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 36.17 | 634.29 | 137.05 | 44.55 | 92.49 | 0.00 | 0.00 |
February | 89.26 | 500.25 | 194.75 | 78.73 | 116.02 | 0.00 | 0.00 |
March | 151.60 | 327.37 | 243.06 | 70.98 | 172.08 | 0.00 | 0.00 |
April | 314.78 | 221.30 | 339.60 | 138.59 | 201.01 | 0.00 | 0.00 |
May | 385.04 | 117.85 | 358.34 | 114.94 | 243.39 | 0.00 | 0.00 |
June | 520.33 | 71.93 | 419.23 | 149.99 | 269.24 | 0.00 | 0.00 |
July | 563.21 | 60.13 | 437.75 | 172.65 | 265.09 | 0.00 | 0.00 |
August | 487.60 | 74.63 | 379.16 | 141.85 | 237.31 | 0.00 | 0.00 |
September | 350.71 | 138.76 | 304.32 | 118.01 | 186.31 | 0.00 | 0.00 |
October | 180.27 | 237.52 | 215.63 | 77.96 | 137.67 | 0.00 | 0.00 |
November | 63.50 | 386.01 | 132.88 | 38.66 | 94.23 | 0.00 | 0.00 |
December | 34.63 | 568.61 | 98.80 | 37.92 | 60.88 | 0.00 | 0.00 |
Annual Sum or Average | 265.68 | 277.21 | 272.05 | 98.76 | 173.29 | 0.00 | 0.00 |
Minimum of Months | 34.63 | 60.13 | 98.80 | 37.92 | 60.88 | 0.00 | 0.00 |
Maximum of Months | 563.21 | 634.29 | 437.75 | 172.65 | 269.24 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 121.50 | 141.05 | 137.14 | 93.96 | 43.18 | 0.00 | 0.00 |
February | 132.35 | 127.97 | 147.84 | 100.30 | 47.54 | 0.00 | 0.00 |
March | 114.08 | 98.96 | 126.64 | 66.29 | 60.35 | 0.00 | 0.00 |
April | 112.34 | 84.80 | 112.90 | 51.74 | 61.16 | 0.00 | 0.00 |
May | 99.61 | 52.28 | 96.29 | 26.93 | 69.35 | 0.00 | 0.00 |
June | 107.38 | 35.34 | 91.92 | 18.36 | 73.56 | 0.00 | 0.00 |
July | 120.78 | 29.57 | 97.54 | 24.40 | 73.15 | 0.00 | 0.00 |
August | 136.28 | 35.54 | 108.09 | 37.43 | 70.66 | 0.00 | 0.00 |
September | 154.89 | 58.16 | 130.51 | 67.34 | 63.16 | 0.00 | 0.00 |
October | 142.89 | 88.00 | 140.64 | 88.67 | 51.97 | 0.00 | 0.00 |
November | 91.24 | 113.91 | 105.26 | 65.90 | 39.36 | 0.00 | 0.00 |
December | 105.02 | 134.17 | 112.08 | 84.88 | 27.20 | 0.00 | 0.00 |
Annual Sum or Average | 119.80 | 83.06 | 117.06 | 60.30 | 56.77 | 0.00 | 0.00 |
Minimum of Months | 91.24 | 29.57 | 91.92 | 18.36 | 27.20 | 0.00 | 0.00 |
Maximum of Months | 154.89 | 141.05 | 147.84 | 100.30 | 73.56 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.04 | 195.24 | 21.99 | 0.00 | 21.99 | 0.00 | 0.00 |
February | 1.01 | 155.95 | 27.88 | 0.00 | 27.88 | 0.00 | 0.00 |
March | 12.21 | 99.58 | 41.79 | 0.00 | 41.79 | 0.00 | 0.00 |
April | 28.17 | 64.22 | 48.43 | 0.39 | 48.04 | 0.00 | 0.00 |
May | 59.92 | 31.53 | 62.97 | 2.39 | 60.58 | 0.00 | 0.00 |
June | 91.05 | 18.63 | 73.69 | 6.83 | 66.86 | 0.00 | 0.00 |
July | 89.82 | 14.69 | 69.12 | 4.77 | 64.35 | 0.00 | 0.00 |
August | 74.84 | 18.74 | 57.91 | 1.17 | 56.74 | 0.00 | 0.00 |
September | 45.51 | 38.62 | 44.32 | 0.04 | 44.28 | 0.00 | 0.00 |
October | 15.54 | 70.00 | 32.91 | 0.00 | 32.91 | 0.00 | 0.00 |
November | 3.51 | 117.27 | 23.02 | 0.00 | 23.02 | 0.00 | 0.00 |
December | 0.00 | 172.53 | 14.93 | 0.00 | 14.93 | 0.00 | 0.00 |
Annual Sum or Average | 35.34 | 82.74 | 43.33 | 1.30 | 42.02 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 14.69 | 14.93 | 0.00 | 14.93 | 0.00 | 0.00 |
Maximum of Months | 91.05 | 195.24 | 73.69 | 6.83 | 66.86 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 161.54 | 570.74 | 281.11 | 162.41 | 118.70 | 0.00 | 0.00 |
February | 218.43 | 451.39 | 330.84 | 189.66 | 141.18 | 0.00 | 0.00 |
March | 285.61 | 313.37 | 356.63 | 161.56 | 195.07 | 0.00 | 0.00 |
April | 375.99 | 216.69 | 383.18 | 170.17 | 213.01 | 0.00 | 0.00 |
May | 483.10 | 112.48 | 426.19 | 167.43 | 258.77 | 0.00 | 0.00 |
June | 576.55 | 66.18 | 450.99 | 169.35 | 281.64 | 0.00 | 0.00 |
July | 609.63 | 51.18 | 461.72 | 187.34 | 274.38 | 0.00 | 0.00 |
August | 557.16 | 64.79 | 421.59 | 170.25 | 251.34 | 0.00 | 0.00 |
September | 510.74 | 132.13 | 419.80 | 205.91 | 213.89 | 0.00 | 0.00 |
October | 328.76 | 228.37 | 338.35 | 178.50 | 159.85 | 0.00 | 0.00 |
November | 157.94 | 359.70 | 227.73 | 113.60 | 114.14 | 0.00 | 0.00 |
December | 138.37 | 524.05 | 214.32 | 137.89 | 76.43 | 0.00 | 0.00 |
Annual Sum or Average | 367.79 | 256.70 | 359.49 | 167.69 | 191.79 | 0.00 | 0.00 |
Minimum of Months | 138.37 | 51.18 | 214.32 | 113.60 | 76.43 | 0.00 | 0.00 |
Maximum of Months | 609.63 | 570.74 | 461.72 | 205.91 | 281.64 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 29.08 | 623.38 | 137.13 | 44.94 | 92.20 | 0.00 | 0.00 |
February | 66.17 | 490.44 | 180.85 | 64.26 | 116.59 | 0.00 | 0.00 |
March | 154.64 | 319.70 | 250.53 | 78.68 | 171.85 | 0.00 | 0.00 |
April | 261.53 | 215.94 | 302.56 | 105.97 | 196.58 | 0.00 | 0.00 |
May | 415.03 | 112.79 | 384.51 | 136.73 | 247.78 | 0.00 | 0.00 |
June | 530.72 | 69.09 | 428.17 | 154.94 | 273.23 | 0.00 | 0.00 |
July | 543.07 | 56.34 | 426.15 | 162.80 | 263.35 | 0.00 | 0.00 |
August | 457.28 | 69.73 | 358.83 | 124.91 | 233.91 | 0.00 | 0.00 |
September | 357.20 | 134.33 | 312.02 | 121.77 | 190.25 | 0.00 | 0.00 |
October | 157.95 | 229.52 | 203.64 | 67.64 | 136.00 | 0.00 | 0.00 |
November | 47.16 | 378.15 | 124.90 | 31.20 | 93.70 | 0.00 | 0.00 |
December | 21.45 | 560.83 | 92.85 | 31.76 | 61.08 | 0.00 | 0.00 |
Annual Sum or Average | 254.48 | 270.68 | 267.28 | 93.94 | 173.34 | 0.00 | 0.00 |
Minimum of Months | 21.45 | 56.34 | 92.85 | 31.20 | 61.08 | 0.00 | 0.00 |
Maximum of Months | 543.07 | 623.38 | 428.17 | 162.80 | 273.23 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 196.36 | 725.69 | 344.78 | 203.58 | 141.19 | 0.00 | 0.00 |
February | 246.29 | 573.43 | 380.71 | 217.32 | 163.39 | 0.00 | 0.00 |
March | 275.37 | 409.85 | 364.91 | 143.63 | 221.27 | 0.00 | 0.00 |
April | 323.57 | 286.72 | 349.53 | 112.96 | 236.58 | 0.00 | 0.00 |
May | 372.47 | 151.66 | 345.04 | 63.53 | 281.51 | 0.00 | 0.00 |
June | 451.79 | 95.41 | 358.79 | 54.57 | 304.22 | 0.00 | 0.00 |
July | 476.22 | 79.65 | 361.08 | 63.19 | 297.89 | 0.00 | 0.00 |
August | 477.50 | 99.53 | 359.66 | 83.65 | 276.01 | 0.00 | 0.00 |
September | 454.29 | 184.94 | 378.78 | 146.00 | 232.77 | 0.00 | 0.00 |
October | 365.14 | 293.59 | 376.02 | 192.12 | 183.90 | 0.00 | 0.00 |
November | 195.19 | 462.10 | 277.94 | 142.80 | 135.15 | 0.00 | 0.00 |
December | 184.52 | 670.92 | 275.20 | 183.92 | 91.28 | 0.00 | 0.00 |
Annual Sum or Average | 335.39 | 335.04 | 347.50 | 133.47 | 214.03 | 0.00 | 0.00 |
Minimum of Months | 184.52 | 79.65 | 275.20 | 54.57 | 91.28 | 0.00 | 0.00 |
Maximum of Months | 477.50 | 725.69 | 380.71 | 217.32 | 304.22 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 159.84 | 575.03 | 281.02 | 162.03 | 118.99 | 0.00 | 0.00 |
February | 237.01 | 459.23 | 344.74 | 204.13 | 140.61 | 0.00 | 0.00 |
March | 278.37 | 317.51 | 349.16 | 153.86 | 195.30 | 0.00 | 0.00 |
April | 426.30 | 220.08 | 420.22 | 202.79 | 217.43 | 0.00 | 0.00 |
May | 452.84 | 117.97 | 400.02 | 145.64 | 254.38 | 0.00 | 0.00 |
June | 564.67 | 68.76 | 442.05 | 164.40 | 277.65 | 0.00 | 0.00 |
July | 626.23 | 53.46 | 473.32 | 197.20 | 276.12 | 0.00 | 0.00 |
August | 585.17 | 68.02 | 441.92 | 187.18 | 254.74 | 0.00 | 0.00 |
September | 501.27 | 133.13 | 412.10 | 202.15 | 209.95 | 0.00 | 0.00 |
October | 346.71 | 231.36 | 350.34 | 188.81 | 161.52 | 0.00 | 0.00 |
November | 170.57 | 362.93 | 235.72 | 121.05 | 114.66 | 0.00 | 0.00 |
December | 148.74 | 529.93 | 220.27 | 144.05 | 76.22 | 0.00 | 0.00 |
Annual Sum or Average | 375.50 | 260.54 | 364.25 | 172.52 | 191.74 | 0.00 | 0.00 |
Minimum of Months | 148.74 | 53.46 | 220.27 | 121.05 | 76.22 | 0.00 | 0.00 |
Maximum of Months | 626.23 | 575.03 | 473.32 | 204.13 | 277.65 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 35.86 | 636.22 | 137.05 | 44.55 | 92.49 | 0.00 | 0.00 |
February | 88.66 | 501.67 | 194.75 | 78.73 | 116.02 | 0.00 | 0.00 |
March | 151.35 | 326.90 | 243.06 | 70.98 | 172.08 | 0.00 | 0.00 |
April | 312.69 | 220.53 | 339.60 | 138.59 | 201.01 | 0.00 | 0.00 |
May | 381.17 | 118.08 | 358.34 | 114.94 | 243.39 | 0.00 | 0.00 |
June | 516.38 | 72.17 | 419.23 | 149.99 | 269.24 | 0.00 | 0.00 |
July | 559.39 | 60.55 | 437.75 | 172.65 | 265.09 | 0.00 | 0.00 |
August | 484.34 | 75.19 | 379.16 | 141.85 | 237.31 | 0.00 | 0.00 |
September | 349.56 | 137.44 | 304.32 | 118.01 | 186.31 | 0.00 | 0.00 |
October | 180.33 | 235.71 | 215.63 | 77.96 | 137.67 | 0.00 | 0.00 |
November | 64.04 | 384.81 | 132.88 | 38.66 | 94.23 | 0.00 | 0.00 |
December | 34.74 | 569.35 | 98.80 | 37.92 | 60.88 | 0.00 | 0.00 |
Annual Sum or Average | 264.12 | 277.20 | 272.05 | 98.76 | 173.29 | 0.00 | 0.00 |
Minimum of Months | 34.74 | 60.55 | 98.80 | 37.92 | 60.88 | 0.00 | 0.00 |
Maximum of Months | 559.39 | 636.22 | 437.75 | 172.65 | 269.24 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 209.71 | 293.92 | 251.46 | 172.29 | 79.17 | 0.00 | 0.00 |
February | 236.54 | 236.43 | 271.07 | 183.91 | 87.16 | 0.00 | 0.00 |
March | 213.44 | 167.23 | 232.20 | 121.55 | 110.65 | 0.00 | 0.00 |
April | 218.35 | 117.35 | 207.01 | 94.87 | 112.14 | 0.00 | 0.00 |
May | 204.48 | 61.65 | 176.55 | 49.39 | 127.16 | 0.00 | 0.00 |
June | 222.39 | 34.66 | 168.54 | 33.66 | 134.88 | 0.00 | 0.00 |
July | 247.31 | 25.91 | 178.86 | 44.73 | 134.13 | 0.00 | 0.00 |
August | 273.14 | 33.89 | 198.20 | 68.64 | 129.56 | 0.00 | 0.00 |
September | 302.44 | 69.34 | 239.30 | 123.48 | 115.82 | 0.00 | 0.00 |
October | 278.11 | 120.70 | 257.88 | 162.58 | 95.30 | 0.00 | 0.00 |
November | 173.33 | 187.13 | 193.01 | 120.84 | 72.17 | 0.00 | 0.00 |
December | 185.40 | 271.39 | 205.52 | 155.65 | 49.87 | 0.00 | 0.00 |
Annual Sum or Average | 230.35 | 134.49 | 214.65 | 110.56 | 104.09 | 0.00 | 0.00 |
Minimum of Months | 173.33 | 25.91 | 168.54 | 33.66 | 49.87 | 0.00 | 0.00 |
Maximum of Months | 302.44 | 293.92 | 271.07 | 183.91 | 134.88 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 1826.80 | 192.37 | 0.00 | 192.37 | 0.00 | 0.00 |
February | 3.71 | 1463.07 | 243.89 | 0.00 | 243.89 | 0.00 | 0.00 |
March | 79.52 | 996.47 | 365.57 | 0.00 | 365.56 | 0.00 | 0.00 |
April | 207.74 | 665.52 | 423.69 | 3.43 | 420.26 | 0.00 | 0.00 |
May | 462.44 | 337.55 | 550.88 | 20.87 | 530.01 | 0.00 | 0.00 |
June | 736.00 | 211.84 | 644.65 | 59.75 | 584.90 | 0.00 | 0.00 |
July | 728.33 | 169.98 | 604.66 | 41.71 | 562.95 | 0.00 | 0.00 |
August | 598.71 | 212.61 | 506.63 | 10.26 | 496.37 | 0.00 | 0.00 |
September | 352.98 | 413.91 | 387.70 | 0.36 | 387.34 | 0.00 | 0.00 |
October | 102.22 | 720.41 | 287.89 | 0.00 | 287.89 | 0.00 | 0.00 |
November | 19.99 | 1157.43 | 201.38 | 0.00 | 201.38 | 0.00 | 0.00 |
December | 0.00 | 1658.48 | 130.63 | 0.00 | 130.63 | 0.00 | 0.00 |
Annual Sum or Average | 275.93 | 816.49 | 379.04 | 11.41 | 367.63 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 169.98 | 130.63 | 0.00 | 130.63 | 0.00 | 0.00 |
Maximum of Months | 736.00 | 1826.80 | 644.65 | 59.75 | 584.90 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 1861.87 | 192.37 | 0.00 | 192.37 | 0.00 | 0.00 |
February | 2.80 | 1494.16 | 243.89 | 0.00 | 243.89 | 0.00 | 0.00 |
March | 72.76 | 1021.67 | 365.57 | 0.00 | 365.56 | 0.00 | 0.00 |
April | 199.50 | 683.46 | 423.69 | 3.43 | 420.26 | 0.00 | 0.00 |
May | 451.19 | 345.72 | 550.88 | 20.87 | 530.01 | 0.00 | 0.00 |
June | 726.93 | 217.87 | 644.65 | 59.75 | 584.90 | 0.00 | 0.00 |
July | 720.16 | 175.01 | 604.66 | 41.71 | 562.95 | 0.00 | 0.00 |
August | 590.61 | 218.61 | 506.63 | 10.26 | 496.37 | 0.00 | 0.00 |
September | 344.88 | 424.27 | 387.70 | 0.36 | 387.34 | 0.00 | 0.00 |
October | 93.96 | 739.16 | 287.89 | 0.00 | 287.89 | 0.00 | 0.00 |
November | 17.37 | 1186.58 | 201.38 | 0.00 | 201.38 | 0.00 | 0.00 |
December | 0.00 | 1694.80 | 130.63 | 0.00 | 130.63 | 0.00 | 0.00 |
Annual Sum or Average | 269.94 | 835.52 | 379.04 | 11.41 | 367.63 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 175.01 | 130.63 | 0.00 | 130.63 | 0.00 | 0.00 |
Maximum of Months | 726.93 | 1861.87 | 644.65 | 59.75 | 584.90 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 175.73 | 1163.79 | 418.23 | 207.34 | 210.89 | 0.00 | 0.00 |
February | 287.65 | 902.98 | 511.67 | 253.91 | 257.75 | 0.00 | 0.00 |
March | 471.66 | 658.90 | 607.13 | 240.22 | 366.91 | 0.00 | 0.00 |
April | 702.54 | 460.46 | 685.71 | 276.13 | 409.57 | 0.00 | 0.00 |
May | 1013.60 | 253.02 | 810.66 | 304.14 | 506.52 | 0.00 | 0.00 |
June | 1245.19 | 163.39 | 879.12 | 324.27 | 554.84 | 0.00 | 0.00 |
July | 1303.99 | 130.50 | 887.82 | 350.12 | 537.71 | 0.00 | 0.00 |
August | 1153.90 | 158.62 | 780.38 | 295.14 | 485.23 | 0.00 | 0.00 |
September | 976.86 | 285.23 | 731.78 | 327.66 | 404.12 | 0.00 | 0.00 |
October | 542.72 | 476.30 | 541.97 | 246.14 | 295.84 | 0.00 | 0.00 |
November | 216.54 | 748.00 | 352.62 | 144.79 | 207.83 | 0.00 | 0.00 |
December | 145.22 | 1086.76 | 307.15 | 169.65 | 137.51 | 0.00 | 0.00 |
Annual Sum or Average | 688.49 | 539.07 | 626.73 | 261.62 | 365.11 | 0.00 | 0.00 |
Minimum of Months | 145.22 | 130.50 | 307.15 | 144.79 | 137.51 | 0.00 | 0.00 |
Maximum of Months | 1303.99 | 1163.79 | 887.82 | 350.12 | 554.84 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 457.28 | 1279.98 | 706.05 | 438.56 | 267.48 | 0.00 | 0.00 |
February | 555.24 | 1004.84 | 773.64 | 468.15 | 305.49 | 0.00 | 0.00 |
March | 567.26 | 732.41 | 716.40 | 309.42 | 406.98 | 0.00 | 0.00 |
April | 635.28 | 518.29 | 672.20 | 242.68 | 429.52 | 0.00 | 0.00 |
May | 682.98 | 279.16 | 638.27 | 132.87 | 505.39 | 0.00 | 0.00 |
June | 801.29 | 178.04 | 650.01 | 106.16 | 543.85 | 0.00 | 0.00 |
July | 858.58 | 148.39 | 662.57 | 128.16 | 534.40 | 0.00 | 0.00 |
August | 887.47 | 184.68 | 678.20 | 178.23 | 499.96 | 0.00 | 0.00 |
September | 891.49 | 330.27 | 742.05 | 314.45 | 427.60 | 0.00 | 0.00 |
October | 750.14 | 525.56 | 755.14 | 413.86 | 341.27 | 0.00 | 0.00 |
November | 421.41 | 823.12 | 560.36 | 307.61 | 252.74 | 0.00 | 0.00 |
December | 419.48 | 1192.70 | 567.94 | 396.20 | 171.73 | 0.00 | 0.00 |
Annual Sum or Average | 661.23 | 597.96 | 676.33 | 285.35 | 390.98 | 0.00 | 0.00 |
Minimum of Months | 419.48 | 148.39 | 560.36 | 106.16 | 171.73 | 0.00 | 0.00 |
Maximum of Months | 891.49 | 1279.98 | 773.64 | 468.15 | 543.85 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.202367E+10 | 0.252037E+10 | 0.232266E+10 | 0.159136E+10 | 0.731301E+09 | 0.00 | 0.00 |
February | 0.206776E+10 | 0.179698E+10 | 0.226152E+10 | 0.153433E+10 | 0.727194E+09 | 0.00 | 0.00 |
March | 0.203456E+10 | 0.146022E+10 | 0.214479E+10 | 0.112274E+10 | 0.102204E+10 | 0.00 | 0.00 |
April | 0.197558E+10 | 0.102070E+10 | 0.185043E+10 | 0.848040E+09 | 0.100239E+10 | 0.00 | 0.00 |
May | 0.191299E+10 | 0.576470E+09 | 0.163076E+10 | 0.456187E+09 | 0.117457E+10 | 0.00 | 0.00 |
June | 0.195430E+10 | 0.355814E+09 | 0.150653E+10 | 0.300860E+09 | 0.120567E+10 | 0.00 | 0.00 |
July | 0.223271E+10 | 0.308649E+09 | 0.165205E+10 | 0.413171E+09 | 0.123888E+10 | 0.00 | 0.00 |
August | 0.248612E+10 | 0.381390E+09 | 0.183070E+10 | 0.633976E+09 | 0.119672E+10 | 0.00 | 0.00 |
September | 0.269460E+10 | 0.658955E+09 | 0.213904E+10 | 0.110377E+10 | 0.103527E+10 | 0.00 | 0.00 |
October | 0.261000E+10 | 0.108284E+10 | 0.238198E+10 | 0.150174E+10 | 0.880239E+09 | 0.00 | 0.00 |
November | 0.159511E+10 | 0.157643E+10 | 0.172530E+10 | 0.108019E+10 | 0.645105E+09 | 0.00 | 0.00 |
December | 0.175926E+10 | 0.237266E+10 | 0.189833E+10 | 0.143766E+10 | 0.460667E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.253467E+11 | 0.141115E+11 | 0.233441E+11 | 0.120240E+11 | 0.113200E+11 | 0.00 | 0.00 |
Minimum of Months | 0.159511E+10 | 0.308649E+09 | 0.150653E+10 | 0.300860E+09 | 0.460667E+09 | 0.00 | 0.00 |
Maximum of Months | 0.269460E+10 | 0.252037E+10 | 0.238198E+10 | 0.159136E+10 | 0.123888E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.565129E+10 | 0.717282E+10 | 0.654047E+10 | 0.448117E+10 | 0.205930E+10 | 0.00 | 0.00 |
February | 0.577090E+10 | 0.518267E+10 | 0.636831E+10 | 0.432057E+10 | 0.204773E+10 | 0.00 | 0.00 |
March | 0.565271E+10 | 0.427280E+10 | 0.603958E+10 | 0.316157E+10 | 0.287800E+10 | 0.00 | 0.00 |
April | 0.549472E+10 | 0.304986E+10 | 0.521068E+10 | 0.238803E+10 | 0.282265E+10 | 0.00 | 0.00 |
May | 0.526791E+10 | 0.180830E+10 | 0.459212E+10 | 0.128459E+10 | 0.330752E+10 | 0.00 | 0.00 |
June | 0.541157E+10 | 0.112453E+10 | 0.424230E+10 | 0.847203E+09 | 0.339509E+10 | 0.00 | 0.00 |
July | 0.620364E+10 | 0.966592E+09 | 0.465206E+10 | 0.116346E+10 | 0.348860E+10 | 0.00 | 0.00 |
August | 0.692202E+10 | 0.119196E+10 | 0.515513E+10 | 0.178524E+10 | 0.336989E+10 | 0.00 | 0.00 |
September | 0.750945E+10 | 0.201285E+10 | 0.602340E+10 | 0.310816E+10 | 0.291524E+10 | 0.00 | 0.00 |
October | 0.726071E+10 | 0.326381E+10 | 0.670748E+10 | 0.422879E+10 | 0.247870E+10 | 0.00 | 0.00 |
November | 0.443260E+10 | 0.458657E+10 | 0.485833E+10 | 0.304176E+10 | 0.181657E+10 | 0.00 | 0.00 |
December | 0.490884E+10 | 0.677777E+10 | 0.534556E+10 | 0.404835E+10 | 0.129721E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.704864E+11 | 0.414105E+11 | 0.657354E+11 | 0.338589E+11 | 0.318765E+11 | 0.00 | 0.00 |
Minimum of Months | 0.443260E+10 | 0.966592E+09 | 0.424230E+10 | 0.847203E+09 | 0.129721E+10 | 0.00 | 0.00 |
Maximum of Months | 0.750945E+10 | 0.717282E+10 | 0.670748E+10 | 0.448117E+10 | 0.348860E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.743961E+10 | 0.971036E+10 | 0.849644E+10 | 0.582130E+10 | 0.267514E+10 | 0.00 | 0.00 |
February | 0.762582E+10 | 0.698866E+10 | 0.827279E+10 | 0.561267E+10 | 0.266012E+10 | 0.00 | 0.00 |
March | 0.746283E+10 | 0.581849E+10 | 0.784575E+10 | 0.410706E+10 | 0.373869E+10 | 0.00 | 0.00 |
April | 0.727211E+10 | 0.416733E+10 | 0.676897E+10 | 0.310218E+10 | 0.366678E+10 | 0.00 | 0.00 |
May | 0.695454E+10 | 0.247051E+10 | 0.596542E+10 | 0.166876E+10 | 0.429666E+10 | 0.00 | 0.00 |
June | 0.716419E+10 | 0.152715E+10 | 0.551098E+10 | 0.110057E+10 | 0.441042E+10 | 0.00 | 0.00 |
July | 0.822136E+10 | 0.129275E+10 | 0.604329E+10 | 0.151140E+10 | 0.453188E+10 | 0.00 | 0.00 |
August | 0.916680E+10 | 0.158625E+10 | 0.669681E+10 | 0.231912E+10 | 0.437768E+10 | 0.00 | 0.00 |
September | 0.991412E+10 | 0.272281E+10 | 0.782473E+10 | 0.403767E+10 | 0.378706E+10 | 0.00 | 0.00 |
October | 0.956554E+10 | 0.443682E+10 | 0.871340E+10 | 0.549344E+10 | 0.321997E+10 | 0.00 | 0.00 |
November | 0.581510E+10 | 0.627844E+10 | 0.631125E+10 | 0.395142E+10 | 0.235983E+10 | 0.00 | 0.00 |
December | 0.646974E+10 | 0.920356E+10 | 0.694419E+10 | 0.525904E+10 | 0.168515E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.930718E+11 | 0.562031E+11 | 0.853940E+11 | 0.439846E+11 | 0.414094E+11 | 0.00 | 0.00 |
Minimum of Months | 0.581510E+10 | 0.129275E+10 | 0.551098E+10 | 0.110057E+10 | 0.168515E+10 | 0.00 | 0.00 |
Maximum of Months | 0.991412E+10 | 0.971036E+10 | 0.871340E+10 | 0.582130E+10 | 0.453188E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.430925E+09 | 0.153680E+10 | 0.752685E+09 | 0.433971E+09 | 0.318714E+09 | 0.00 | 0.00 |
February | 0.577808E+09 | 0.110883E+10 | 0.833992E+09 | 0.493819E+09 | 0.340173E+09 | 0.00 | 0.00 |
March | 0.748901E+09 | 0.851577E+09 | 0.935195E+09 | 0.412091E+09 | 0.523104E+09 | 0.00 | 0.00 |
April | 0.111242E+10 | 0.573154E+09 | 0.108922E+10 | 0.525632E+09 | 0.563590E+09 | 0.00 | 0.00 |
May | 0.122231E+10 | 0.318014E+09 | 0.107141E+10 | 0.390073E+09 | 0.681337E+09 | 0.00 | 0.00 |
June | 0.147220E+10 | 0.181233E+09 | 0.114579E+10 | 0.426126E+09 | 0.719668E+09 | 0.00 | 0.00 |
July | 0.168675E+10 | 0.146482E+09 | 0.126773E+10 | 0.528169E+09 | 0.739565E+09 | 0.00 | 0.00 |
August | 0.157642E+10 | 0.185196E+09 | 0.118365E+10 | 0.501344E+09 | 0.682304E+09 | 0.00 | 0.00 |
September | 0.130447E+10 | 0.349998E+09 | 0.106816E+10 | 0.523980E+09 | 0.544180E+09 | 0.00 | 0.00 |
October | 0.932400E+09 | 0.623044E+09 | 0.938338E+09 | 0.505720E+09 | 0.432618E+09 | 0.00 | 0.00 |
November | 0.442400E+09 | 0.943192E+09 | 0.610984E+09 | 0.313774E+09 | 0.297210E+09 | 0.00 | 0.00 |
December | 0.398669E+09 | 0.141852E+10 | 0.589980E+09 | 0.385823E+09 | 0.204157E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.119057E+11 | 0.823604E+10 | 0.114871E+11 | 0.544052E+10 | 0.604662E+10 | 0.00 | 0.00 |
Minimum of Months | 0.398669E+09 | 0.146482E+09 | 0.589980E+09 | 0.313774E+09 | 0.204157E+09 | 0.00 | 0.00 |
Maximum of Months | 0.168675E+10 | 0.153680E+10 | 0.126773E+10 | 0.528169E+09 | 0.739565E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 96869911.74 | 0.169889E+10 | 0.367064E+09 | 0.119331E+09 | 0.247732E+09 | 0.00 | 0.00 |
February | 0.215928E+09 | 0.121020E+10 | 0.471140E+09 | 0.190456E+09 | 0.280685E+09 | 0.00 | 0.00 |
March | 0.406057E+09 | 0.876840E+09 | 0.651014E+09 | 0.190107E+09 | 0.460907E+09 | 0.00 | 0.00 |
April | 0.815915E+09 | 0.573607E+09 | 0.880251E+09 | 0.359229E+09 | 0.521022E+09 | 0.00 | 0.00 |
May | 0.103130E+10 | 0.315648E+09 | 0.959768E+09 | 0.307862E+09 | 0.651906E+09 | 0.00 | 0.00 |
June | 0.134870E+10 | 0.186451E+09 | 0.108664E+10 | 0.388765E+09 | 0.697872E+09 | 0.00 | 0.00 |
July | 0.150849E+10 | 0.161060E+09 | 0.117246E+10 | 0.462437E+09 | 0.710023E+09 | 0.00 | 0.00 |
August | 0.130599E+10 | 0.199902E+09 | 0.101554E+10 | 0.379922E+09 | 0.635622E+09 | 0.00 | 0.00 |
September | 0.909043E+09 | 0.359655E+09 | 0.788798E+09 | 0.305877E+09 | 0.482922E+09 | 0.00 | 0.00 |
October | 0.482822E+09 | 0.636175E+09 | 0.577537E+09 | 0.208801E+09 | 0.368736E+09 | 0.00 | 0.00 |
November | 0.164600E+09 | 0.100053E+10 | 0.344432E+09 | 0.100201E+09 | 0.244232E+09 | 0.00 | 0.00 |
December | 92746019.90 | 0.152298E+10 | 0.264631E+09 | 0.101573E+09 | 0.163058E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.837846E+10 | 0.874194E+10 | 0.857928E+10 | 0.311456E+10 | 0.546472E+10 | 0.00 | 0.00 |
Minimum of Months | 92746019.90 | 0.161060E+09 | 0.264631E+09 | 0.100201E+09 | 0.163058E+09 | 0.00 | 0.00 |
Maximum of Months | 0.150849E+10 | 0.169889E+10 | 0.117246E+10 | 0.462437E+09 | 0.710023E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.325416E+09 | 0.377786E+09 | 0.367312E+09 | 0.251662E+09 | 0.115650E+09 | 0.00 | 0.00 |
February | 0.320187E+09 | 0.309589E+09 | 0.357643E+09 | 0.242643E+09 | 0.115001E+09 | 0.00 | 0.00 |
March | 0.305559E+09 | 0.265044E+09 | 0.339182E+09 | 0.177553E+09 | 0.161629E+09 | 0.00 | 0.00 |
April | 0.291185E+09 | 0.219800E+09 | 0.292632E+09 | 0.134111E+09 | 0.158521E+09 | 0.00 | 0.00 |
May | 0.266783E+09 | 0.140040E+09 | 0.257894E+09 | 72142461.01 | 0.185752E+09 | 0.00 | 0.00 |
June | 0.278342E+09 | 91600724.52 | 0.238248E+09 | 47578762.80 | 0.190670E+09 | 0.00 | 0.00 |
July | 0.323498E+09 | 79188430.72 | 0.261261E+09 | 65339777.42 | 0.195921E+09 | 0.00 | 0.00 |
August | 0.365020E+09 | 95177892.60 | 0.289513E+09 | 0.100258E+09 | 0.189254E+09 | 0.00 | 0.00 |
September | 0.401469E+09 | 0.150762E+09 | 0.338274E+09 | 0.174553E+09 | 0.163721E+09 | 0.00 | 0.00 |
October | 0.382725E+09 | 0.235702E+09 | 0.376692E+09 | 0.237488E+09 | 0.139204E+09 | 0.00 | 0.00 |
November | 0.236495E+09 | 0.295265E+09 | 0.272843E+09 | 0.170824E+09 | 0.102019E+09 | 0.00 | 0.00 |
December | 0.281273E+09 | 0.359371E+09 | 0.300206E+09 | 0.227355E+09 | 72851358.19 | 0.00 | 0.00 |
Annual Sum or Average | 0.377795E+10 | 0.261933E+10 | 0.369170E+10 | 0.190151E+10 | 0.179019E+10 | 0.00 | 0.00 |
Minimum of Months | 0.236495E+09 | 79188430.72 | 0.238248E+09 | 47578762.80 | 72851358.19 | 0.00 | 0.00 |
Maximum of Months | 0.401469E+09 | 0.377786E+09 | 0.376692E+09 | 0.251662E+09 | 0.195921E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 102477.33 | 0.522928E+09 | 58895473.06 | 0.00 | 58895473.06 | 0.00 | 0.00 |
February | 2442675.57 | 0.377269E+09 | 67442057.94 | 0.00 | 67442057.94 | 0.00 | 0.00 |
March | 32715597.57 | 0.266711E+09 | 0.111920E+09 | 993.85 | 0.111919E+09 | 0.00 | 0.00 |
April | 73022590.63 | 0.166454E+09 | 0.125530E+09 | 1015262.00 | 0.124515E+09 | 0.00 | 0.00 |
May | 0.160488E+09 | 84438700.93 | 0.168655E+09 | 6389204.19 | 0.162265E+09 | 0.00 | 0.00 |
June | 0.236009E+09 | 48300559.38 | 0.190996E+09 | 17701966.40 | 0.173294E+09 | 0.00 | 0.00 |
July | 0.240568E+09 | 39348600.76 | 0.185118E+09 | 12769280.31 | 0.172349E+09 | 0.00 | 0.00 |
August | 0.200462E+09 | 50194576.84 | 0.155107E+09 | 3140916.24 | 0.151966E+09 | 0.00 | 0.00 |
September | 0.117970E+09 | 0.100106E+09 | 0.114867E+09 | 105193.30 | 0.114761E+09 | 0.00 | 0.00 |
October | 41626693.50 | 0.187495E+09 | 88137585.25 | 0.00 | 88137585.25 | 0.00 | 0.00 |
November | 9107478.45 | 0.303965E+09 | 59664261.98 | 0.00 | 59664261.98 | 0.00 | 0.00 |
December | 8438.42 | 0.462118E+09 | 39991922.20 | 0.00 | 39991922.20 | 0.00 | 0.00 |
Annual Sum or Average | 0.111452E+10 | 0.260933E+10 | 0.136632E+10 | 41122816.28 | 0.132520E+10 | 0.00 | 0.00 |
Minimum of Months | 8438.42 | 39348600.76 | 39991922.20 | 0.00 | 39991922.20 | 0.00 | 0.00 |
Maximum of Months | 0.240568E+09 | 0.522928E+09 | 0.190996E+09 | 17701966.40 | 0.173294E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.432679E+09 | 0.152867E+10 | 0.752922E+09 | 0.434995E+09 | 0.317926E+09 | 0.00 | 0.00 |
February | 0.528426E+09 | 0.109199E+10 | 0.800364E+09 | 0.458828E+09 | 0.341536E+09 | 0.00 | 0.00 |
March | 0.764989E+09 | 0.839326E+09 | 0.955197E+09 | 0.432716E+09 | 0.522482E+09 | 0.00 | 0.00 |
April | 0.974575E+09 | 0.561673E+09 | 0.993206E+09 | 0.441090E+09 | 0.552115E+09 | 0.00 | 0.00 |
May | 0.129394E+10 | 0.301273E+09 | 0.114152E+10 | 0.448440E+09 | 0.693077E+09 | 0.00 | 0.00 |
June | 0.149441E+10 | 0.171538E+09 | 0.116898E+10 | 0.438967E+09 | 0.730011E+09 | 0.00 | 0.00 |
July | 0.163284E+10 | 0.137081E+09 | 0.123667E+10 | 0.501773E+09 | 0.734901E+09 | 0.00 | 0.00 |
August | 0.149230E+10 | 0.173534E+09 | 0.112919E+10 | 0.455993E+09 | 0.673196E+09 | 0.00 | 0.00 |
September | 0.132383E+10 | 0.342472E+09 | 0.108812E+10 | 0.533721E+09 | 0.554395E+09 | 0.00 | 0.00 |
October | 0.880556E+09 | 0.611659E+09 | 0.906239E+09 | 0.478097E+09 | 0.428141E+09 | 0.00 | 0.00 |
November | 0.409393E+09 | 0.932334E+09 | 0.590289E+09 | 0.294440E+09 | 0.295848E+09 | 0.00 | 0.00 |
December | 0.370602E+09 | 0.140360E+10 | 0.574030E+09 | 0.369324E+09 | 0.204706E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.115985E+11 | 0.809515E+10 | 0.113367E+11 | 0.528838E+10 | 0.604834E+10 | 0.00 | 0.00 |
Minimum of Months | 0.370602E+09 | 0.137081E+09 | 0.574030E+09 | 0.294440E+09 | 0.204706E+09 | 0.00 | 0.00 |
Maximum of Months | 0.163284E+10 | 0.152867E+10 | 0.123667E+10 | 0.533721E+09 | 0.734901E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 77878773.24 | 0.166966E+10 | 0.367300E+09 | 0.120355E+09 | 0.246945E+09 | 0.00 | 0.00 |
February | 0.160073E+09 | 0.118648E+10 | 0.437512E+09 | 0.155464E+09 | 0.282048E+09 | 0.00 | 0.00 |
March | 0.414198E+09 | 0.856295E+09 | 0.671016E+09 | 0.210732E+09 | 0.460285E+09 | 0.00 | 0.00 |
April | 0.677877E+09 | 0.559708E+09 | 0.784234E+09 | 0.274687E+09 | 0.509547E+09 | 0.00 | 0.00 |
May | 0.111160E+10 | 0.302096E+09 | 0.102988E+10 | 0.366229E+09 | 0.663646E+09 | 0.00 | 0.00 |
June | 0.137564E+10 | 0.179070E+09 | 0.110982E+10 | 0.401606E+09 | 0.708215E+09 | 0.00 | 0.00 |
July | 0.145457E+10 | 0.150898E+09 | 0.114140E+10 | 0.436042E+09 | 0.705359E+09 | 0.00 | 0.00 |
August | 0.122478E+10 | 0.186777E+09 | 0.961084E+09 | 0.334570E+09 | 0.626514E+09 | 0.00 | 0.00 |
September | 0.925862E+09 | 0.348185E+09 | 0.808754E+09 | 0.315617E+09 | 0.493136E+09 | 0.00 | 0.00 |
October | 0.423046E+09 | 0.614734E+09 | 0.545437E+09 | 0.181178E+09 | 0.364259E+09 | 0.00 | 0.00 |
November | 0.122230E+09 | 0.980176E+09 | 0.323737E+09 | 80867192.16 | 0.242870E+09 | 0.00 | 0.00 |
December | 57449993.46 | 0.150212E+10 | 0.248681E+09 | 85074026.75 | 0.163607E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.802521E+10 | 0.853621E+10 | 0.842885E+10 | 0.296242E+10 | 0.546643E+10 | 0.00 | 0.00 |
Minimum of Months | 57449993.46 | 0.150898E+09 | 0.248681E+09 | 80867192.16 | 0.163607E+09 | 0.00 | 0.00 |
Maximum of Months | 0.145457E+10 | 0.166966E+10 | 0.114140E+10 | 0.436042E+09 | 0.708215E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.525935E+09 | 0.194370E+10 | 0.923450E+09 | 0.545281E+09 | 0.378169E+09 | 0.00 | 0.00 |
February | 0.595825E+09 | 0.138725E+10 | 0.921016E+09 | 0.525739E+09 | 0.395277E+09 | 0.00 | 0.00 |
March | 0.737541E+09 | 0.109774E+10 | 0.977369E+09 | 0.384711E+09 | 0.592659E+09 | 0.00 | 0.00 |
April | 0.838698E+09 | 0.743186E+09 | 0.905992E+09 | 0.292781E+09 | 0.613211E+09 | 0.00 | 0.00 |
May | 0.997620E+09 | 0.406213E+09 | 0.924147E+09 | 0.170154E+09 | 0.753993E+09 | 0.00 | 0.00 |
June | 0.117104E+10 | 0.247294E+09 | 0.929979E+09 | 0.141438E+09 | 0.788541E+09 | 0.00 | 0.00 |
July | 0.127551E+10 | 0.213335E+09 | 0.967108E+09 | 0.169236E+09 | 0.797872E+09 | 0.00 | 0.00 |
August | 0.127893E+10 | 0.266570E+09 | 0.963308E+09 | 0.224037E+09 | 0.739271E+09 | 0.00 | 0.00 |
September | 0.117752E+10 | 0.479377E+09 | 0.981785E+09 | 0.378437E+09 | 0.603349E+09 | 0.00 | 0.00 |
October | 0.977999E+09 | 0.786351E+09 | 0.100712E+10 | 0.514570E+09 | 0.492552E+09 | 0.00 | 0.00 |
November | 0.505939E+09 | 0.119777E+10 | 0.720428E+09 | 0.370129E+09 | 0.350299E+09 | 0.00 | 0.00 |
December | 0.494208E+09 | 0.179698E+10 | 0.737099E+09 | 0.492615E+09 | 0.244485E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.105768E+11 | 0.105658E+11 | 0.109588E+11 | 0.420913E+10 | 0.674968E+10 | 0.00 | 0.00 |
Minimum of Months | 0.494208E+09 | 0.213335E+09 | 0.720428E+09 | 0.141438E+09 | 0.244485E+09 | 0.00 | 0.00 |
Maximum of Months | 0.127893E+10 | 0.194370E+10 | 0.100712E+10 | 0.545281E+09 | 0.797872E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.428129E+09 | 0.154015E+10 | 0.752685E+09 | 0.433971E+09 | 0.318714E+09 | 0.00 | 0.00 |
February | 0.573379E+09 | 0.111097E+10 | 0.833992E+09 | 0.493819E+09 | 0.340173E+09 | 0.00 | 0.00 |
March | 0.745588E+09 | 0.850411E+09 | 0.935195E+09 | 0.412091E+09 | 0.523104E+09 | 0.00 | 0.00 |
April | 0.110496E+10 | 0.570457E+09 | 0.108922E+10 | 0.525632E+09 | 0.563590E+09 | 0.00 | 0.00 |
May | 0.121288E+10 | 0.315970E+09 | 0.107141E+10 | 0.390073E+09 | 0.681337E+09 | 0.00 | 0.00 |
June | 0.146364E+10 | 0.178236E+09 | 0.114579E+10 | 0.426126E+09 | 0.719668E+09 | 0.00 | 0.00 |
July | 0.167730E+10 | 0.143193E+09 | 0.126773E+10 | 0.528169E+09 | 0.739565E+09 | 0.00 | 0.00 |
August | 0.156733E+10 | 0.182189E+09 | 0.118365E+10 | 0.501344E+09 | 0.682304E+09 | 0.00 | 0.00 |
September | 0.129929E+10 | 0.345080E+09 | 0.106816E+10 | 0.523980E+09 | 0.544180E+09 | 0.00 | 0.00 |
October | 0.928641E+09 | 0.619666E+09 | 0.938338E+09 | 0.505720E+09 | 0.432618E+09 | 0.00 | 0.00 |
November | 0.442129E+09 | 0.940708E+09 | 0.610984E+09 | 0.313774E+09 | 0.297210E+09 | 0.00 | 0.00 |
December | 0.398388E+09 | 0.141936E+10 | 0.589980E+09 | 0.385823E+09 | 0.204157E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.118416E+11 | 0.821639E+10 | 0.114871E+11 | 0.544052E+10 | 0.604662E+10 | 0.00 | 0.00 |
Minimum of Months | 0.398388E+09 | 0.143193E+09 | 0.589980E+09 | 0.313774E+09 | 0.204157E+09 | 0.00 | 0.00 |
Maximum of Months | 0.167730E+10 | 0.154015E+10 | 0.126773E+10 | 0.528169E+09 | 0.739565E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 96034394.82 | 0.170405E+10 | 0.367064E+09 | 0.119331E+09 | 0.247732E+09 | 0.00 | 0.00 |
February | 0.214474E+09 | 0.121364E+10 | 0.471140E+09 | 0.190456E+09 | 0.280685E+09 | 0.00 | 0.00 |
March | 0.405378E+09 | 0.875579E+09 | 0.651014E+09 | 0.190107E+09 | 0.460907E+09 | 0.00 | 0.00 |
April | 0.810502E+09 | 0.571618E+09 | 0.880251E+09 | 0.359229E+09 | 0.521022E+09 | 0.00 | 0.00 |
May | 0.102092E+10 | 0.316257E+09 | 0.959768E+09 | 0.307862E+09 | 0.651906E+09 | 0.00 | 0.00 |
June | 0.133847E+10 | 0.187057E+09 | 0.108664E+10 | 0.388765E+09 | 0.697872E+09 | 0.00 | 0.00 |
July | 0.149827E+10 | 0.162182E+09 | 0.117246E+10 | 0.462437E+09 | 0.710023E+09 | 0.00 | 0.00 |
August | 0.129727E+10 | 0.201379E+09 | 0.101554E+10 | 0.379922E+09 | 0.635622E+09 | 0.00 | 0.00 |
September | 0.906069E+09 | 0.356256E+09 | 0.788798E+09 | 0.305877E+09 | 0.482922E+09 | 0.00 | 0.00 |
October | 0.482994E+09 | 0.631331E+09 | 0.577537E+09 | 0.208801E+09 | 0.368736E+09 | 0.00 | 0.00 |
November | 0.165986E+09 | 0.997417E+09 | 0.344432E+09 | 0.100201E+09 | 0.244232E+09 | 0.00 | 0.00 |
December | 93044300.59 | 0.152495E+10 | 0.264631E+09 | 0.101573E+09 | 0.163058E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.832940E+10 | 0.874172E+10 | 0.857928E+10 | 0.311456E+10 | 0.546472E+10 | 0.00 | 0.00 |
Minimum of Months | 93044300.59 | 0.162182E+09 | 0.264631E+09 | 0.100201E+09 | 0.163058E+09 | 0.00 | 0.00 |
Maximum of Months | 0.149827E+10 | 0.170405E+10 | 0.117246E+10 | 0.462437E+09 | 0.710023E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.561690E+09 | 0.787227E+09 | 0.673507E+09 | 0.461450E+09 | 0.212057E+09 | 0.00 | 0.00 |
February | 0.572242E+09 | 0.571979E+09 | 0.655778E+09 | 0.444912E+09 | 0.210867E+09 | 0.00 | 0.00 |
March | 0.571690E+09 | 0.447900E+09 | 0.621928E+09 | 0.325563E+09 | 0.296365E+09 | 0.00 | 0.00 |
April | 0.565968E+09 | 0.304178E+09 | 0.536573E+09 | 0.245907E+09 | 0.290666E+09 | 0.00 | 0.00 |
May | 0.547683E+09 | 0.165130E+09 | 0.472877E+09 | 0.132281E+09 | 0.340596E+09 | 0.00 | 0.00 |
June | 0.576438E+09 | 89843278.94 | 0.436855E+09 | 87240873.66 | 0.349614E+09 | 0.00 | 0.00 |
July | 0.662393E+09 | 69408586.14 | 0.479050E+09 | 0.119808E+09 | 0.359242E+09 | 0.00 | 0.00 |
August | 0.731580E+09 | 90776813.42 | 0.530853E+09 | 0.183835E+09 | 0.347018E+09 | 0.00 | 0.00 |
September | 0.783926E+09 | 0.179719E+09 | 0.620262E+09 | 0.320063E+09 | 0.300200E+09 | 0.00 | 0.00 |
October | 0.744894E+09 | 0.323291E+09 | 0.690706E+09 | 0.435460E+09 | 0.255246E+09 | 0.00 | 0.00 |
November | 0.449262E+09 | 0.485050E+09 | 0.500288E+09 | 0.313225E+09 | 0.187063E+09 | 0.00 | 0.00 |
December | 0.496583E+09 | 0.726885E+09 | 0.550461E+09 | 0.416880E+09 | 0.133581E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.726435E+10 | 0.424139E+10 | 0.676914E+10 | 0.348662E+10 | 0.328251E+10 | 0.00 | 0.00 |
Minimum of Months | 0.449262E+09 | 69408586.14 | 0.436855E+09 | 87240873.66 | 0.133581E+09 | 0.00 | 0.00 |
Maximum of Months | 0.783926E+09 | 0.787227E+09 | 0.690706E+09 | 0.461450E+09 | 0.359242E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 9186.53 | 0.489291E+10 | 0.515248E+09 | 0.00 | 0.515248E+09 | 0.00 | 0.00 |
February | 8972960.28 | 0.353946E+10 | 0.590017E+09 | 0.00 | 0.590017E+09 | 0.00 | 0.00 |
March | 0.212985E+09 | 0.266895E+10 | 0.979129E+09 | 8694.74 | 0.979121E+09 | 0.00 | 0.00 |
April | 0.538464E+09 | 0.172503E+10 | 0.109820E+10 | 8882028.68 | 0.108932E+10 | 0.00 | 0.00 |
May | 0.123860E+10 | 0.904088E+09 | 0.147548E+10 | 55896009.98 | 0.141958E+10 | 0.00 | 0.00 |
June | 0.190770E+10 | 0.549102E+09 | 0.167093E+10 | 0.154866E+09 | 0.151606E+10 | 0.00 | 0.00 |
July | 0.195077E+10 | 0.455265E+09 | 0.161951E+10 | 0.111712E+09 | 0.150780E+10 | 0.00 | 0.00 |
August | 0.160359E+10 | 0.569462E+09 | 0.135696E+10 | 27478333.85 | 0.132948E+10 | 0.00 | 0.00 |
September | 0.914923E+09 | 0.107286E+10 | 0.100491E+10 | 920284.50 | 0.100399E+10 | 0.00 | 0.00 |
October | 0.273773E+09 | 0.192955E+10 | 0.771072E+09 | 0.00 | 0.771072E+09 | 0.00 | 0.00 |
November | 51815400.38 | 0.300005E+10 | 0.521973E+09 | 0.00 | 0.521973E+09 | 0.00 | 0.00 |
December | 0.00 | 0.444208E+10 | 0.349870E+09 | 0.00 | 0.349870E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.870160E+10 | 0.257488E+11 | 0.119533E+11 | 0.359763E+09 | 0.115935E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.455265E+09 | 0.349870E+09 | 0.00 | 0.349870E+09 | 0.00 | 0.00 |
Maximum of Months | 0.195077E+10 | 0.489291E+10 | 0.167093E+10 | 0.154866E+09 | 0.151606E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.498683E+10 | 0.515248E+09 | 0.00 | 0.515248E+09 | 0.00 | 0.00 |
February | 6784937.98 | 0.361467E+10 | 0.590017E+09 | 0.00 | 0.590017E+09 | 0.00 | 0.00 |
March | 0.194877E+09 | 0.273644E+10 | 0.979129E+09 | 8694.74 | 0.979121E+09 | 0.00 | 0.00 |
April | 0.517101E+09 | 0.177154E+10 | 0.109820E+10 | 8882028.68 | 0.108932E+10 | 0.00 | 0.00 |
May | 0.120846E+10 | 0.925975E+09 | 0.147548E+10 | 55896009.98 | 0.141958E+10 | 0.00 | 0.00 |
June | 0.188419E+10 | 0.564709E+09 | 0.167093E+10 | 0.154866E+09 | 0.151606E+10 | 0.00 | 0.00 |
July | 0.192888E+10 | 0.468756E+09 | 0.161951E+10 | 0.111712E+09 | 0.150780E+10 | 0.00 | 0.00 |
August | 0.158188E+10 | 0.585516E+09 | 0.135696E+10 | 27478333.85 | 0.132948E+10 | 0.00 | 0.00 |
September | 0.893934E+09 | 0.109970E+10 | 0.100491E+10 | 920284.50 | 0.100399E+10 | 0.00 | 0.00 |
October | 0.251650E+09 | 0.197975E+10 | 0.771072E+09 | 0.00 | 0.771072E+09 | 0.00 | 0.00 |
November | 45022338.88 | 0.307561E+10 | 0.521973E+09 | 0.00 | 0.521973E+09 | 0.00 | 0.00 |
December | 0.00 | 0.453935E+10 | 0.349870E+09 | 0.00 | 0.349870E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.851278E+10 | 0.263489E+11 | 0.119533E+11 | 0.359763E+09 | 0.115935E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.468756E+09 | 0.349870E+09 | 0.00 | 0.349870E+09 | 0.00 | 0.00 |
Maximum of Months | 0.192888E+10 | 0.498683E+10 | 0.167093E+10 | 0.154866E+09 | 0.151606E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.470685E+09 | 0.311708E+10 | 0.112018E+10 | 0.555333E+09 | 0.564846E+09 | 0.00 | 0.00 |
February | 0.695872E+09 | 0.218449E+10 | 0.123783E+10 | 0.614270E+09 | 0.623556E+09 | 0.00 | 0.00 |
March | 0.126330E+10 | 0.176479E+10 | 0.162614E+10 | 0.643418E+09 | 0.982721E+09 | 0.00 | 0.00 |
April | 0.182099E+10 | 0.119352E+10 | 0.177735E+10 | 0.715739E+09 | 0.106161E+10 | 0.00 | 0.00 |
May | 0.271483E+10 | 0.677687E+09 | 0.217128E+10 | 0.814618E+09 | 0.135666E+10 | 0.00 | 0.00 |
June | 0.322754E+10 | 0.423498E+09 | 0.227868E+10 | 0.840520E+09 | 0.143816E+10 | 0.00 | 0.00 |
July | 0.349260E+10 | 0.349530E+09 | 0.237795E+10 | 0.937755E+09 | 0.144019E+10 | 0.00 | 0.00 |
August | 0.309062E+10 | 0.424860E+09 | 0.209016E+10 | 0.790516E+09 | 0.129965E+10 | 0.00 | 0.00 |
September | 0.253203E+10 | 0.739308E+09 | 0.189678E+10 | 0.849293E+09 | 0.104748E+10 | 0.00 | 0.00 |
October | 0.145363E+10 | 0.127572E+10 | 0.145161E+10 | 0.659250E+09 | 0.792365E+09 | 0.00 | 0.00 |
November | 0.561267E+09 | 0.193882E+10 | 0.913990E+09 | 0.375296E+09 | 0.538694E+09 | 0.00 | 0.00 |
December | 0.388966E+09 | 0.291077E+10 | 0.822683E+09 | 0.454386E+09 | 0.368297E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.217123E+11 | 0.170001E+11 | 0.197646E+11 | 0.825039E+10 | 0.115142E+11 | 0.00 | 0.00 |
Minimum of Months | 0.388966E+09 | 0.349530E+09 | 0.822683E+09 | 0.375296E+09 | 0.368297E+09 | 0.00 | 0.00 |
Maximum of Months | 0.349260E+10 | 0.311708E+10 | 0.237795E+10 | 0.937755E+09 | 0.144019E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.122479E+10 | 0.342831E+10 | 0.189108E+10 | 0.117464E+10 | 0.716431E+09 | 0.00 | 0.00 |
February | 0.134324E+10 | 0.243092E+10 | 0.187158E+10 | 0.113255E+10 | 0.739031E+09 | 0.00 | 0.00 |
March | 0.151935E+10 | 0.196168E+10 | 0.191880E+10 | 0.828742E+09 | 0.109006E+10 | 0.00 | 0.00 |
April | 0.164665E+10 | 0.134341E+10 | 0.174234E+10 | 0.629015E+09 | 0.111332E+10 | 0.00 | 0.00 |
May | 0.182928E+10 | 0.747701E+09 | 0.170953E+10 | 0.355890E+09 | 0.135364E+10 | 0.00 | 0.00 |
June | 0.207694E+10 | 0.461474E+09 | 0.168483E+10 | 0.275165E+09 | 0.140967E+10 | 0.00 | 0.00 |
July | 0.229961E+10 | 0.397451E+09 | 0.177462E+10 | 0.343272E+09 | 0.143135E+10 | 0.00 | 0.00 |
August | 0.237700E+10 | 0.494635E+09 | 0.181648E+10 | 0.477381E+09 | 0.133910E+10 | 0.00 | 0.00 |
September | 0.231075E+10 | 0.856053E+09 | 0.192340E+10 | 0.815052E+09 | 0.110834E+10 | 0.00 | 0.00 |
October | 0.200917E+10 | 0.140767E+10 | 0.202255E+10 | 0.110849E+10 | 0.914067E+09 | 0.00 | 0.00 |
November | 0.109231E+10 | 0.213353E+10 | 0.145244E+10 | 0.797332E+09 | 0.655112E+09 | 0.00 | 0.00 |
December | 0.112354E+10 | 0.319452E+10 | 0.152116E+10 | 0.106119E+10 | 0.459973E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.208526E+11 | 0.188573E+11 | 0.213288E+11 | 0.899872E+10 | 0.123301E+11 | 0.00 | 0.00 |
Minimum of Months | 0.109231E+10 | 0.397451E+09 | 0.145244E+10 | 0.275165E+09 | 0.459973E+09 | 0.00 | 0.00 |
Maximum of Months | 0.237700E+10 | 0.342831E+10 | 0.202255E+10 | 0.117464E+10 | 0.143135E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -12.6 | -13.1 | -15.2 | 6.10 | -26.1 | 37.55 | 107.22 | 0.02 |
February | -7.7 | -8.6 | -10.9 | 6.39 | -21.3 | 45.57 | 135.04 | 0.00 |
March | 0.33 | -1.4 | -4.2 | 6.99 | -10.6 | 74.69 | 127.11 | 0.00 |
April | 7.02 | 4.40 | 1.63 | 6.38 | -3.6 | 77.59 | 184.47 | 0.02 |
May | 14.19 | 11.30 | 8.94 | 5.14 | 4.70 | 102.33 | 182.89 | 0.00 |
June | 19.16 | 15.71 | 13.79 | 4.87 | 8.84 | 110.26 | 213.51 | 0.04 |
July | 20.92 | 17.87 | 16.31 | 4.22 | 9.95 | 102.99 | 231.93 | 0.03 |
August | 20.05 | 17.00 | 15.28 | 4.97 | 11.01 | 95.97 | 190.14 | 0.00 |
September | 15.39 | 11.24 | 8.10 | 4.97 | 3.18 | 72.67 | 177.74 | 0.01 |
October | 7.43 | 4.69 | 1.56 | 5.55 | -3.9 | 55.50 | 131.91 | 0.00 |
November | -0.0 | -1.5 | -3.9 | 6.30 | -10.9 | 41.35 | 79.05 | 0.00 |
December | -7.6 | -8.4 | -10.6 | 6.09 | -20.0 | 22.97 | 92.59 | 0.00 |
Annual Sum or Average | 6.46 | 4.16 | 1.81 | 5.66 | -4.8 | 70.09 | 154.52 | 0.01 |
Minimum of Months | -12.6 | -13.1 | -15.2 | 4.22 | -26.1 | 22.97 | 79.05 | 0.00 |
Maximum of Months | 20.92 | 17.87 | 16.31 | 6.99 | 11.01 | 110.26 | 231.93 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 6.10 | 17-JAN-23:19 | 3.74 | 0.93 | 10.63 | -0.4 | 0.00 | 0.00 |
February | 8.30 | 24-FEB-14:00 | 5.62 | 2.80 | 5.20 | -7.3 | 71.00 | 794.50 |
March | 18.90 | 19-MAR-15:00 | 13.93 | 10.60 | 8.80 | 7.95 | 139.50 | 237.50 |
April | 30.00 | 15-APR-15:20 | 19.12 | 13.53 | 12.70 | 15.70 | 115.83 | 790.83 |
May | 30.00 | 31-MAY-12:00 | 19.70 | 14.40 | 6.20 | 19.52 | 251.00 | 580.50 |
June | 33.30 | 11-JUN-14:00 | 24.81 | 21.70 | 10.30 | 24.50 | 281.00 | 458.50 |
July | 30.00 | 26-JUL-15:20 | 25.67 | 24.23 | 5.13 | 20.98 | 260.33 | 436.00 |
August | 33.90 | 04-AUG-14:00 | 25.31 | 22.20 | 4.60 | 23.82 | 194.50 | 612.00 |
September | 32.20 | 06-SEP-13:00 | 21.19 | 16.10 | 6.20 | 18.28 | 135.00 | 769.00 |
October | 23.30 | 20-OCT-14:00 | 13.36 | 5.60 | 7.20 | 7.35 | 55.00 | 745.50 |
November | 16.10 | 03-NOV-13:00 | 10.47 | 5.60 | 6.70 | 0.51 | 82.00 | 691.00 |
December | 7.20 | 02-DEC-13:00 | 3.94 | 0.00 | 7.70 | -3.9 | 75.00 | 301.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 3.74 | 0.00 | 4.60 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 33.90 | 25.67 | 24.23 | 12.70 | 24.50 | 281.00 | 794.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -31.1 | 31-JAN-03:00 | -31.3 | -34.4 | 4.60 | -46.7 | 0.00 | 0.00 |
February | -36.7 | 02-FEB-05:00 | -36.8 | -40.2 | 3.10 | -59.6 | 0.00 | 0.00 |
March | -17.2 | 06-MAR-00:00 | -17.6 | -20.0 | 5.20 | -36.8 | 0.00 | 0.00 |
April | -7.2 | 03-APR-05:19 | -8.0 | -9.8 | 7.37 | -15.9 | 0.00 | 0.00 |
May | 0.60 | 03-MAY-02:00 | -0.1 | -1.1 | 1.50 | -15.5 | 0.00 | 0.00 |
June | 5.00 | 01-JUN-04:00 | 5.00 | 5.00 | 3.10 | -7.8 | 30.50 | 132.50 |
July | 10.00 | 23-JUL-03:00 | 9.66 | 9.40 | 2.60 | -4.3 | 0.00 | 0.00 |
August | 8.30 | 07-AUG-03:00 | 7.41 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
September | -1.1 | 30-SEP-00:00 | -2.4 | -4.4 | 4.10 | -17.8 | 0.00 | 0.00 |
October | -3.3 | 23-OCT-05:00 | -4.2 | -6.1 | 3.60 | -19.1 | 0.00 | 0.00 |
November | -28.9 | 26-NOV-06:00 | -29.0 | -30.6 | 1.50 | -50.2 | 0.00 | 0.00 |
December | -22.8 | 09-DEC-00:20 | -23.0 | -25.0 | 13.40 | -37.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -36.7 | -36.8 | -40.2 | 1.50 | -59.6 | 0.00 | 0.00 | |
Maximum of Months | 10.00 | 9.66 | 9.40 | 13.40 | -3.2 | 30.50 | 132.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.60 | 18-JAN-00:00 | 5.60 | 5.60 | 7.70 | 0.30 | 0.00 | 0.00 |
February | 5.88 | 24-FEB-15:00 | 8.30 | 3.30 | 5.70 | -7.3 | 54.50 | 665.50 |
March | 13.93 | 19-MAR-15:00 | 18.90 | 10.60 | 8.80 | 7.95 | 139.50 | 237.50 |
April | 20.94 | 18-APR-11:00 | 27.80 | 17.80 | 13.90 | 17.57 | 334.00 | 447.00 |
May | 19.93 | 29-MAY-13:00 | 23.30 | 18.30 | 6.20 | 20.75 | 379.00 | 52.00 |
June | 24.81 | 11-JUN-14:00 | 33.30 | 21.70 | 10.30 | 24.50 | 281.00 | 458.50 |
July | 26.15 | 26-JUL-18:00 | 27.80 | 25.60 | 3.10 | 19.35 | 33.50 | 51.00 |
August | 26.64 | 04-AUG-12:00 | 31.70 | 25.00 | 4.60 | 25.66 | 235.00 | 593.50 |
September | 21.19 | 06-SEP-13:00 | 32.20 | 16.10 | 6.20 | 18.28 | 135.00 | 769.00 |
October | 14.84 | 02-OCT-14:00 | 18.30 | 12.80 | 3.60 | 12.41 | 202.00 | 164.00 |
November | 13.04 | 09-NOV-04:00 | 15.00 | 11.70 | 10.30 | 10.88 | 0.00 | 0.00 |
December | 3.94 | 02-DEC-13:00 | 7.20 | 0.00 | 7.70 | -3.9 | 75.00 | 301.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 3.94 | 5.60 | 0.00 | 3.10 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 26.64 | 33.30 | 25.60 | 13.90 | 25.66 | 379.00 | 769.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.60 | 18-JAN-00:00 | 5.60 | 5.60 | 7.70 | 0.30 | 0.00 | 0.00 |
February | 3.30 | 24-FEB-15:00 | 8.30 | 5.88 | 5.70 | -7.3 | 54.50 | 665.50 |
March | 11.10 | 26-MAR-05:00 | 13.30 | 12.04 | 8.20 | 9.13 | 0.00 | 0.00 |
April | 18.30 | 18-APR-09:00 | 25.60 | 20.52 | 14.40 | 15.57 | 196.00 | 741.50 |
May | 18.30 | 29-MAY-13:00 | 23.30 | 19.93 | 6.20 | 20.75 | 379.00 | 52.00 |
June | 22.20 | 13-JUN-11:00 | 26.70 | 23.35 | 8.80 | 16.85 | 273.50 | 600.50 |
July | 25.60 | 26-JUL-18:00 | 27.80 | 26.15 | 3.10 | 19.35 | 33.50 | 51.00 |
August | 25.00 | 04-AUG-12:00 | 31.70 | 26.64 | 4.60 | 25.66 | 235.00 | 593.50 |
September | 18.30 | 12-SEP-02:00 | 18.90 | 18.46 | 5.70 | 14.28 | 0.00 | 0.00 |
October | 12.80 | 02-OCT-13:00 | 17.40 | 14.50 | 3.40 | 11.65 | 249.50 | 141.50 |
November | 11.70 | 08-NOV-10:00 | 13.90 | 12.62 | 7.20 | 9.91 | 158.00 | 0.50 |
December | 0.00 | 02-DEC-11:00 | 5.00 | 2.79 | 7.20 | -8.3 | 115.50 | 562.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 5.00 | 2.79 | 3.10 | -8.3 | 0.00 | 0.00 | |
Maximum of Months | 25.60 | 31.70 | 26.64 | 14.40 | 25.66 | 379.00 | 741.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 4.29 | 14.52 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 3.18 | 19.75 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 3.75 | 28.43 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 5.88 | 38.20 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 9.06 | 44.89 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 12.40 | 51.07 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 15.02 | 51.61 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 16.22 | 43.31 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 15.63 | 34.41 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.44 | 22.83 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 10.25 | 13.98 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 6.92 | 10.24 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 9.71 | 31.16 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 3.18 | 10.24 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 16.22 | 51.61 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH LAUNDRY G WATER HEATER
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.129252E+12 | -0.127479E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.177305E+10 | 81.42 | 0.00 | 0.00 |
February | 0.116908E+12 | -0.115283E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.162599E+10 | 81.13 | 0.00 | 0.00 |
March | 0.129334E+12 | -0.127557E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.177622E+10 | 81.28 | 0.00 | 0.00 |
April | 0.124871E+12 | -0.123124E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.174690E+10 | 81.84 | 0.00 | 0.00 |
May | 0.125616E+12 | -0.123809E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.180760E+10 | 82.17 | 0.00 | 0.00 |
June | 0.116062E+12 | -0.114328E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.173404E+10 | 82.17 | 0.00 | 0.00 |
July | 0.115482E+12 | -0.113705E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.177706E+10 | 82.17 | 0.00 | 0.00 |
August | 0.113446E+12 | -0.111682E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.176345E+10 | 82.17 | 0.00 | 0.00 |
September | 0.110741E+12 | -0.109040E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.170131E+10 | 82.17 | 0.00 | 0.00 |
October | 0.118136E+12 | -0.116380E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175642E+10 | 82.17 | 0.00 | 0.00 |
November | 0.119555E+12 | -0.117852E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.170341E+10 | 82.17 | 0.00 | 0.00 |
December | 0.128394E+12 | -0.126637E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175714E+10 | 82.03 | 0.00 | 0.00 |
Annual Sum or Average | 0.144780E+13 | -0.142687E+13 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.209226E+11 | 81.91 | 0.00 | 0.00 |
Minimum of Months | 0.110741E+12 | -0.127557E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.180760E+10 | 81.13 | 0.00 | 0.00 |
Maximum of Months | 0.129334E+12 | -0.109040E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.162599E+10 | 82.17 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.805024E+10 | -0.788296E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -167277411.4 | 82.17 | 0.00 | 0.00 |
February | 0.727552E+10 | -0.712336E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -152157440.6 | 82.17 | 0.00 | 0.00 |
March | 0.804630E+10 | -0.788155E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164747052.6 | 82.17 | 0.00 | 0.00 |
April | 0.779743E+10 | -0.763820E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -159228053.4 | 82.17 | 0.00 | 0.00 |
May | 0.804728E+10 | -0.788296E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164317048.5 | 82.17 | 0.00 | 0.00 |
June | 0.778868E+10 | -0.762976E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -158917617.9 | 82.17 | 0.00 | 0.00 |
July | 0.805557E+10 | -0.789140E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164171691.8 | 82.17 | 0.00 | 0.00 |
August | 0.804715E+10 | -0.788296E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164192836.3 | 82.17 | 0.00 | 0.00 |
September | 0.779861E+10 | -0.763961E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -159007431.7 | 82.17 | 0.00 | 0.00 |
October | 0.804608E+10 | -0.788155E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164525190.5 | 82.17 | 0.00 | 0.00 |
November | 0.778109E+10 | -0.762132E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -159765649.9 | 82.17 | 0.00 | 0.00 |
December | 0.805645E+10 | -0.789140E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -165043997.2 | 82.17 | 0.00 | 0.00 |
Annual Sum or Average | 0.947904E+11 | -0.928470E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.194335E+10 | 82.17 | 0.00 | 0.00 |
Minimum of Months | 0.727552E+10 | -0.789140E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -167277411.4 | 82.17 | 0.00 | 0.00 |
Maximum of Months | 0.805645E+10 | -0.712336E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -152157440.6 | 82.17 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.829712E+11 | -0.814063E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.156490E+10 | 60.05 | 0.00 | 0.00 |
February | 0.764669E+11 | -0.750083E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.145855E+10 | 60.05 | 0.00 | 0.00 |
March | 0.838574E+11 | -0.822821E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.157536E+10 | 60.05 | 0.00 | 0.00 |
April | 0.780978E+11 | -0.765572E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.154061E+10 | 60.05 | 0.00 | 0.00 |
May | 0.760616E+11 | -0.744802E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.158146E+10 | 60.05 | 0.00 | 0.00 |
June | 0.688741E+11 | -0.673648E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.150931E+10 | 60.05 | 0.00 | 0.00 |
July | 0.672552E+11 | -0.657161E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.153914E+10 | 60.05 | 0.00 | 0.00 |
August | 0.655559E+11 | -0.640356E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.152027E+10 | 60.05 | 0.00 | 0.00 |
September | 0.642294E+11 | -0.627655E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.146395E+10 | 60.05 | 0.00 | 0.00 |
October | 0.695357E+11 | -0.680252E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.151052E+10 | 60.05 | 0.00 | 0.00 |
November | 0.718095E+11 | -0.703427E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.146685E+10 | 60.05 | 0.00 | 0.00 |
December | 0.790817E+11 | -0.775646E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.151717E+10 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.883797E+12 | -0.865549E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.182481E+11 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.642294E+11 | -0.822821E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.158146E+10 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.838574E+11 | -0.627655E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.145855E+10 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: LOBBY_FLR_1_DAYLCTRL
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.87 | 0.86 | 01-JAN-09:39 | 6560.51 | 38.07 | 207.17 | 251.67 | 4405.62 | 37.54 | 209.33 | 220.00 |
February | 226.83 | 0.87 | 0.86 | 01-FEB-07:00 | 7949.11 | 37.88 | 221.67 | 259.00 | 1683.07 | 29.13 | 211.17 | 234.83 |
March | 334.33 | 0.87 | 0.86 | 01-MAR-08:09 | 4433.43 | 26.24 | 208.67 | 332.00 | 763.38 | 22.41 | 241.33 | 286.17 |
April | 285.17 | 0.87 | 0.86 | 01-APR-07:30 | 1638.54 | 20.98 | 132.67 | 352.50 | 668.04 | 22.69 | 227.00 | 286.33 |
May | 428.67 | 0.87 | 0.86 | 01-MAY-06:49 | 1347.95 | 20.09 | 100.83 | 402.17 | 527.62 | 21.79 | 286.50 | 336.17 |
June | 400.67 | 0.87 | 0.86 | 01-JUN-06:10 | 1372.97 | 20.47 | 156.50 | 403.67 | 549.99 | 22.18 | 290.00 | 338.50 |
July | 414.00 | 0.87 | 0.86 | 01-JUL-06:10 | 1411.89 | 20.81 | 180.67 | 413.67 | 569.66 | 22.51 | 315.50 | 350.00 |
August | 410.83 | 0.87 | 0.86 | 01-AUG-06:40 | 1583.16 | 20.54 | 156.83 | 384.17 | 620.94 | 22.24 | 311.00 | 333.00 |
September | 326.50 | 0.87 | 0.86 | 01-SEP-06:40 | 2683.09 | 23.20 | 196.00 | 337.50 | 737.60 | 22.83 | 252.50 | 294.83 |
October | 325.17 | 0.87 | 0.86 | 01-OCT-07:10 | 6894.32 | 33.84 | 296.83 | 310.67 | 935.80 | 23.82 | 248.67 | 280.50 |
November | 254.83 | 0.87 | 0.86 | 01-NOV-07:49 | 4689.54 | 33.36 | 239.67 | 253.83 | 2253.42 | 30.81 | 229.83 | 223.83 |
December | 186.17 | 0.87 | 0.86 | 01-DEC-08:09 | 5688.36 | 38.18 | 180.50 | 227.50 | 5052.28 | 39.16 | 180.83 | 176.33 |
Annual Sum or Average | 3807.33 | 0.87 | 3386.20 | 26.15 | 2278.00 | 3928.33 | 1252.44 | 25.12 | 3003.67 | 3360.50 | ||
Minimum of Months | 186.17 | 0.87 | 0.86 | 1347.95 | 20.09 | 100.83 | 227.50 | 527.62 | 21.79 | 180.83 | 176.33 | |
Maximum of Months | 428.67 | 0.87 | 0.86 | 7949.11 | 38.18 | 296.83 | 413.67 | 5052.28 | 39.16 | 315.50 | 350.00 |
Report: DaylightingReportMonthly
For: CAFE_FLR_1_DAYLCTRL
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.24 | 0.22 | 01-JAN-09:39 | 7089.00 | 38.16 | 207.17 | 259.67 | 4933.36 | 37.53 | 204.67 | 238.50 |
February | 226.83 | 0.25 | 0.22 | 01-FEB-07:49 | 8469.40 | 37.94 | 222.00 | 266.17 | 2199.12 | 28.86 | 206.67 | 249.83 |
March | 334.33 | 0.25 | 0.22 | 01-MAR-07:40 | 4812.25 | 26.46 | 211.00 | 341.67 | 1138.84 | 22.54 | 245.83 | 314.00 |
April | 285.17 | 0.26 | 0.22 | 01-APR-06:00 | 2003.95 | 21.18 | 131.17 | 362.67 | 1032.39 | 22.75 | 238.83 | 332.33 |
May | 428.67 | 0.26 | 0.22 | 01-MAY-06:40 | 1589.32 | 20.64 | 161.00 | 416.67 | 768.17 | 22.16 | 312.33 | 379.33 |
June | 400.67 | 0.26 | 0.22 | 01-JUN-05:30 | 1613.23 | 21.00 | 198.33 | 416.17 | 789.43 | 22.53 | 316.00 | 383.00 |
July | 414.00 | 0.25 | 0.22 | 01-JUL-05:49 | 1668.88 | 21.28 | 222.67 | 426.00 | 825.79 | 22.81 | 336.17 | 392.50 |
August | 410.83 | 0.26 | 0.22 | 01-AUG-05:00 | 1866.75 | 20.97 | 203.17 | 396.00 | 903.52 | 22.50 | 327.00 | 368.00 |
September | 326.50 | 0.25 | 0.22 | 01-SEP-06:19 | 3066.31 | 23.36 | 186.67 | 346.33 | 1119.45 | 22.90 | 271.33 | 320.33 |
October | 325.17 | 0.25 | 0.22 | 01-OCT-06:49 | 7307.74 | 34.00 | 298.50 | 317.00 | 1349.44 | 23.84 | 243.17 | 299.83 |
November | 254.83 | 0.25 | 0.22 | 01-NOV-07:40 | 5046.66 | 33.47 | 241.33 | 262.00 | 2610.83 | 30.86 | 229.67 | 241.67 |
December | 186.17 | 0.25 | 0.22 | 01-DEC-07:00 | 6180.94 | 38.27 | 180.50 | 238.67 | 5540.93 | 39.23 | 180.83 | 210.67 |
Annual Sum or Average | 3807.33 | 0.25 | 3734.73 | 26.45 | 2463.50 | 4049.00 | 1599.64 | 25.27 | 3112.50 | 3730.00 | ||
Minimum of Months | 186.17 | 0.24 | 0.22 | 1589.32 | 20.64 | 131.17 | 238.67 | 768.17 | 22.16 | 180.83 | 210.67 | |
Maximum of Months | 428.67 | 0.26 | 0.22 | 8469.40 | 38.27 | 298.50 | 426.00 | 5540.93 | 39.23 | 336.17 | 392.50 |
Report: DaylightingReportMonthly
For: DINING_FLR_6_DAYLCTRL
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.66 | 0.60 | 01-JAN-10:09 | 471.36 | 15.70 | 0.00 | 234.00 | 229.93 | 19.17 | 0.50 | 138.50 |
February | 226.83 | 0.66 | 0.60 | 01-FEB-09:30 | 483.84 | 15.93 | 0.00 | 245.67 | 238.13 | 19.35 | 0.50 | 164.00 |
March | 334.33 | 0.63 | 0.60 | 01-MAR-08:20 | 679.86 | 17.19 | 0.00 | 332.17 | 304.73 | 20.39 | 33.83 | 270.33 |
April | 285.17 | 0.62 | 0.60 | 01-APR-07:19 | 772.63 | 18.34 | 0.00 | 362.33 | 367.82 | 21.54 | 143.00 | 305.17 |
May | 428.67 | 0.62 | 0.60 | 01-MAY-06:40 | 912.49 | 18.41 | 4.17 | 423.00 | 398.77 | 22.41 | 236.50 | 387.33 |
June | 400.67 | 0.61 | 0.60 | 01-JUN-04:00 | 1107.44 | 21.39 | 67.17 | 424.50 | 513.48 | 24.46 | 307.17 | 398.50 |
July | 414.00 | 0.61 | 0.60 | 01-JUL-05:40 | 1035.02 | 20.95 | 54.17 | 432.33 | 479.48 | 23.61 | 308.33 | 406.17 |
August | 410.83 | 0.62 | 0.60 | 01-AUG-05:00 | 851.20 | 18.49 | 4.50 | 398.33 | 386.76 | 21.86 | 234.17 | 370.17 |
September | 326.50 | 0.62 | 0.60 | 01-SEP-06:19 | 683.00 | 17.87 | 0.00 | 340.50 | 328.29 | 21.06 | 102.83 | 293.83 |
October | 325.17 | 0.64 | 0.60 | 01-OCT-07:40 | 553.68 | 16.40 | 0.00 | 299.50 | 255.68 | 19.70 | 0.17 | 227.67 |
November | 254.83 | 0.66 | 0.60 | 01-NOV-08:30 | 485.11 | 15.48 | 0.00 | 240.50 | 214.82 | 18.78 | 0.00 | 144.67 |
December | 186.17 | 0.70 | 0.60 | 02-DEC-09:39 | 334.27 | 14.29 | 0.00 | 203.83 | 169.56 | 17.89 | 0.00 | 50.17 |
Annual Sum or Average | 3807.33 | 0.63 | 751.26 | 17.98 | 130.00 | 3936.67 | 346.89 | 21.28 | 1367.00 | 3156.50 | ||
Minimum of Months | 186.17 | 0.61 | 0.60 | 334.27 | 14.29 | 0.00 | 203.83 | 169.56 | 17.89 | 0.00 | 50.17 | |
Maximum of Months | 428.67 | 0.70 | 0.60 | 1107.44 | 21.39 | 67.17 | 432.33 | 513.48 | 24.46 | 308.33 | 406.17 |
Report: DaylightingReportMonthly
For: BANQUET_FLR_6_DAYLCTRL
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.66 | 0.60 | 01-JAN-10:09 | 471.36 | 15.70 | 0.00 | 234.00 | 229.93 | 19.17 | 0.50 | 138.50 |
February | 226.83 | 0.66 | 0.60 | 01-FEB-09:30 | 483.84 | 15.93 | 0.00 | 245.67 | 238.13 | 19.35 | 0.50 | 164.00 |
March | 334.33 | 0.63 | 0.60 | 01-MAR-08:20 | 679.86 | 17.19 | 0.00 | 332.17 | 304.73 | 20.39 | 33.83 | 270.33 |
April | 285.17 | 0.62 | 0.60 | 01-APR-07:19 | 772.63 | 18.34 | 0.00 | 362.33 | 367.82 | 21.54 | 143.00 | 305.17 |
May | 428.67 | 0.62 | 0.60 | 01-MAY-06:40 | 912.49 | 18.41 | 4.17 | 423.00 | 398.77 | 22.41 | 236.50 | 387.33 |
June | 400.67 | 0.61 | 0.60 | 01-JUN-04:00 | 1107.44 | 21.39 | 67.17 | 424.50 | 513.48 | 24.46 | 307.17 | 398.50 |
July | 414.00 | 0.61 | 0.60 | 01-JUL-05:40 | 1035.02 | 20.95 | 54.17 | 432.33 | 479.48 | 23.61 | 308.33 | 406.17 |
August | 410.83 | 0.62 | 0.60 | 01-AUG-05:00 | 851.20 | 18.49 | 4.50 | 398.33 | 386.76 | 21.86 | 234.17 | 370.17 |
September | 326.50 | 0.62 | 0.60 | 01-SEP-06:19 | 683.00 | 17.87 | 0.00 | 340.50 | 328.29 | 21.06 | 102.83 | 293.83 |
October | 325.17 | 0.64 | 0.60 | 01-OCT-07:40 | 553.68 | 16.40 | 0.00 | 299.50 | 255.68 | 19.70 | 0.17 | 227.67 |
November | 254.83 | 0.66 | 0.60 | 01-NOV-08:30 | 485.11 | 15.48 | 0.00 | 240.50 | 214.82 | 18.78 | 0.00 | 144.67 |
December | 186.17 | 0.70 | 0.60 | 02-DEC-09:39 | 334.27 | 14.29 | 0.00 | 203.83 | 169.56 | 17.89 | 0.00 | 50.17 |
Annual Sum or Average | 3807.33 | 0.63 | 751.26 | 17.98 | 130.00 | 3936.67 | 346.89 | 21.28 | 1367.00 | 3156.50 | ||
Minimum of Months | 186.17 | 0.61 | 0.60 | 334.27 | 14.29 | 0.00 | 203.83 | 169.56 | 17.89 | 0.00 | 50.17 | |
Maximum of Months | 428.67 | 0.70 | 0.60 | 1107.44 | 21.39 | 67.17 | 432.33 | 513.48 | 24.46 | 308.33 | 406.17 |
Report: CoilReportMonthly
For: FLR_3_DOAS HEATING COIL
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.163225E+11 | 31980.12 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.110961E+11 | 33531.07 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.230999E+10 | 6989.26 | 06-MAR-01:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.435202E+09 | 3874.35 | 03-APR-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 10075.16 | 0.27 | 12-MAY-20:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 13542.62 | 0.27 | 18-JUN-22:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 14162.12 | 0.27 | 09-JUL-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 14422.16 | 0.27 | 15-AUG-18:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 299025.44 | 190.24 | 30-SEP-01:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 21426625.45 | 1122.77 | 23-OCT-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.383360E+10 | 31354.11 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.690334E+10 | 11618.06 | 09-DEC-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.409225E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 10075.16 | 0.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.163225E+11 | 33531.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.277285E+12 | 331877.40 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.184471E+12 | 347743.39 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.834848E+11 | 123316.03 | 31-MAR-10:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.531709E+11 | 126156.47 | 25-APR-17:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.457324E+11 | 116568.25 | 20-MAY-22:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.276447E+11 | 118755.51 | 03-JUN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.507541E+10 | 72299.18 | 24-JUL-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.116869E+11 | 100156.38 | 07-AUG-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.420044E+11 | 121684.35 | 30-SEP-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.768058E+11 | 126029.35 | 18-OCT-17:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.103376E+12 | 325463.69 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.146054E+12 | 164290.63 | 08-DEC-20:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.105679E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.507541E+10 | 72299.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.277285E+12 | 347743.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.186181E+10 | 7460.90 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.344382E+10 | 7869.48 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 40073868.79 | 7263.42 | 26-NOV-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.534570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.344382E+10 | 7869.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.502691E+10 | 4303.48 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.363528E+10 | 4546.74 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.204530E+10 | 2110.59 | 06-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.119134E+10 | 1901.68 | 03-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.187012E+09 | 1031.39 | 02-MAY-07:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.108882E+09 | 907.77 | 05-JUN-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1462181.29 | 308.07 | 10-JUL-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.261544E+09 | 1310.89 | 30-SEP-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.769297E+09 | 1343.40 | 23-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.247925E+10 | 4206.99 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.393374E+10 | 3042.91 | 09-DEC-18:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.196400E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.502691E+10 | 4546.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.868873E+09 | 1618.47 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.696644E+09 | 1708.48 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 40408322.91 | 461.11 | 01-MAR-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8141942.04 | 352.23 | 03-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.167442E+09 | 1582.69 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.244354E+09 | 749.56 | 12-DEC-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.202586E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.868873E+09 | 1708.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.246173E+10 | 2326.25 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.174796E+10 | 2458.75 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.567002E+09 | 852.21 | 01-MAR-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.123450E+09 | 684.61 | 03-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.688117E+09 | 2273.75 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.143506E+10 | 1332.39 | 11-DEC-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.702331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.246173E+10 | 2458.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.206014E+10 | 1537.70 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.145127E+10 | 1624.62 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.654037E+09 | 721.18 | 06-MAR-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.219421E+09 | 552.36 | 03-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 212801.10 | 109.34 | 02-MAY-10:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 124478.79 | 36.31 | 30-SEP-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11719467.64 | 144.83 | 27-OCT-10:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.737927E+09 | 1503.23 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.142948E+10 | 1082.19 | 11-DEC-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.656433E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.206014E+10 | 1624.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.306600E+10 | 10411.69 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.324917E+10 | 10982.20 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 87057106.41 | 1465.90 | 06-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 24489392.48 | 1094.98 | 03-APR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 41780.63 | 69.63 | 02-MAY-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1148511.75 | 394.55 | 30-SEP-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 7211075.82 | 456.66 | 28-OCT-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.497315E+09 | 10184.47 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.200406E+09 | 2141.37 | 11-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.713284E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.324917E+10 | 10982.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.687813E+10 | 12469.05 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.526618E+10 | 13164.42 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.991089E+09 | 4887.43 | 01-MAR-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.611047E+09 | 4285.56 | 03-APR-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1898414.05 | 1027.02 | 25-MAY-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 20953059.57 | 2004.39 | 05-JUN-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 52031.63 | 86.72 | 10-JUL-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 34731591.88 | 2127.67 | 27-SEP-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 83880125.70 | 2315.22 | 26-OCT-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.197357E+10 | 12192.74 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.352412E+10 | 7670.20 | 12-DEC-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.193857E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.687813E+10 | 13164.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.123815E+11 | 31279.37 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.116376E+11 | 33013.72 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.340447E+09 | 6954.65 | 01-MAR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 65831289.62 | 4778.85 | 03-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.219057E+10 | 30589.70 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.246314E+10 | 13618.29 | 12-DEC-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.290791E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.123815E+11 | 33013.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.173927E+11 | 15481.66 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124454E+11 | 16352.15 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.447664E+10 | 7009.40 | 01-MAR-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.135646E+10 | 6046.37 | 03-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 7937135.17 | 1617.09 | 30-SEP-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.277078E+09 | 2870.18 | 27-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.678644E+10 | 15136.14 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.122145E+11 | 10945.81 | 12-DEC-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.549571E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.173927E+11 | 16352.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.114320E+11 | 9920.64 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.806856E+10 | 10485.39 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.329777E+10 | 4265.13 | 06-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.117658E+10 | 3088.66 | 03-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6088057.12 | 659.09 | 02-MAY-07:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 81342729.61 | 1808.77 | 30-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.589783E+09 | 2059.68 | 27-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.442497E+10 | 9696.83 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.800421E+10 | 6612.64 | 10-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.370813E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.114320E+11 | 10485.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.367329E+10 | 12813.33 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.401643E+10 | 13522.79 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.507978E+09 | 12531.16 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 12651277.42 | 868.62 | 11-DEC-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.821036E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.401643E+10 | 13522.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.369451E+10 | 13220.17 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.407592E+10 | 13951.90 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.502086E+09 | 12929.14 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.827252E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.407592E+10 | 13951.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.231005E+10 | 8596.10 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.255878E+10 | 9068.15 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.328624E+09 | 8408.15 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.519746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.255878E+10 | 9068.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.857915E+10 | 7828.07 | 18-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.569245E+10 | 7827.90 | 27-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.311745E+10 | 7827.60 | 02-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.125765E+10 | 7827.82 | 02-APR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 87044955.63 | 4681.64 | 09-MAY-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 37396891.32 | 4747.24 | 03-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6882507.26 | 4038.48 | 20-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7791849.00 | 3884.31 | 22-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.236928E+09 | 6105.44 | 29-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.101629E+10 | 7661.30 | 26-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.399642E+10 | 7827.65 | 17-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.715158E+10 | 7828.31 | 14-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.311870E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 6882507.26 | 3884.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.857915E+10 | 7828.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.999630E+10 | 7791.47 | 18-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.686675E+10 | 7811.97 | 02-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.374415E+10 | 7791.01 | 02-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.144704E+10 | 7791.23 | 02-APR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 99658542.44 | 5444.95 | 02-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 37511757.64 | 4763.85 | 03-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 3300861.42 | 4392.87 | 12-JUL-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 4720003.44 | 4767.90 | 16-AUG-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.294731E+09 | 7567.88 | 29-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.147848E+10 | 7687.32 | 27-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.475239E+10 | 7791.08 | 17-NOV-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.827300E+10 | 7791.74 | 14-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.369980E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 3300861.42 | 4392.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.999630E+10 | 7811.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.623810E+10 | 21273.41 | 19-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.107469E+10 | 16452.84 | 04-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.113581E+09 | 8180.71 | 28-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.363868E+10 | 17022.64 | 13-DEC-04:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.110650E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.623810E+10 | 21273.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.451561E+11 | 43656.89 | 18-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.311390E+11 | 44528.85 | 03-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.118409E+11 | 43160.33 | 01-MAR-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.316372E+10 | 42217.82 | 03-APR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 95456802.99 | 39264.77 | 03-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 27833109.61 | 27085.20 | 15-JUN-15:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16505385.28 | 31282.36 | 11-JUL-15:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 37479494.29 | 30116.95 | 06-AUG-15:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.256670E+09 | 31189.42 | 25-SEP-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.199972E+10 | 37259.09 | 29-OCT-15:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.161741E+11 | 43654.56 | 27-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.332119E+11 | 43656.93 | 08-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.143119E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 16505385.28 | 27085.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.451561E+11 | 44528.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.849926E+10 | 7638.66 | 16-JAN-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.575265E+10 | 7638.60 | 27-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.305675E+10 | 7638.18 | 02-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.139279E+10 | 7638.41 | 02-APR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 74537488.45 | 4400.71 | 11-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 29107041.29 | 4794.81 | 04-JUN-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 3698524.95 | 4151.06 | 06-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5767001.49 | 3875.96 | 23-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.213941E+09 | 5244.54 | 30-SEP-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.102863E+10 | 7435.06 | 26-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.402430E+10 | 7638.22 | 17-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.718489E+10 | 7638.55 | 31-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.312663E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 3698524.95 | 3875.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.849926E+10 | 7638.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.993847E+10 | 7603.21 | 16-JAN-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.696293E+10 | 7717.23 | 03-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.366468E+10 | 7602.70 | 02-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.160812E+10 | 7602.93 | 02-APR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 87613730.47 | 4601.28 | 11-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 30847274.71 | 4749.97 | 04-JUN-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 2473435.04 | 3047.72 | 22-JUL-21:34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5207523.74 | 3692.66 | 06-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.258691E+09 | 4740.10 | 24-SEP-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.146895E+10 | 7438.90 | 26-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.478099E+10 | 7602.78 | 17-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.833669E+10 | 7603.13 | 31-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.371457E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 2473435.04 | 3047.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.993847E+10 | 7717.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.289802E+10 | 2315.69 | 18-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.192661E+10 | 2316.06 | 23-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.115977E+10 | 2315.53 | 03-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.510536E+09 | 2315.72 | 02-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 59245351.35 | 2237.89 | 02-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 27592212.93 | 1260.56 | 04-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1991552.53 | 1031.23 | 06-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2289826.19 | 1095.08 | 07-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.126748E+09 | 2262.93 | 29-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.458464E+09 | 2305.18 | 26-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.144222E+10 | 2315.85 | 20-NOV-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.246946E+10 | 2315.78 | 14-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.110829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1991552.53 | 1031.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.289802E+10 | 2316.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.331278E+10 | 2302.10 | 13-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.228047E+10 | 2332.66 | 02-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.136332E+10 | 2302.24 | 12-MAR-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.572209E+09 | 2302.11 | 02-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 59286269.73 | 2233.14 | 02-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 28068251.00 | 1256.36 | 04-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 841684.57 | 1054.61 | 12-JUL-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1377318.71 | 1305.54 | 08-AUG-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.148775E+09 | 2272.58 | 29-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.621118E+09 | 2302.22 | 27-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.168066E+10 | 2302.64 | 15-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.280797E+10 | 2302.17 | 14-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.128769E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 841684.57 | 1054.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.331278E+10 | 2332.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.972715E+10 | 10947.45 | 18-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.595454E+10 | 10945.71 | 11-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.346712E+10 | 10946.51 | 02-MAR-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.170174E+10 | 10947.27 | 02-APR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.120441E+09 | 6517.06 | 09-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 51666979.96 | 6450.33 | 06-JUN-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 9278445.30 | 5569.42 | 28-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 12791217.16 | 4863.76 | 12-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.243374E+09 | 5314.79 | 13-SEP-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.824794E+09 | 10584.47 | 26-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.430191E+10 | 10947.04 | 23-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.825507E+10 | 10947.68 | 31-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.346699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 9278445.30 | 4863.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.972715E+10 | 10947.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.212226E+09 | 0.212226E+09 | 8515.76 | 19-MAR-16:00 | 8515.76 | 0.01 |
April | 0.00 | 0.00 | 0.322158E+10 | 0.259043E+10 | 26462.51 | 18-APR-08:50 | 14831.26 | 0.10 |
May | 0.00 | 0.00 | 0.743526E+10 | 0.563762E+10 | 29501.61 | 29-MAY-15:01 | 14685.64 | 0.29 |
June | 0.00 | 0.00 | 0.238818E+11 | 0.157026E+11 | 40758.49 | 26-JUN-06:55 | 16463.34 | 0.57 |
July | 0.00 | 0.00 | 0.360767E+11 | 0.207031E+11 | 40259.68 | 17-JUL-18:50 | 16006.69 | 0.72 |
August | 0.00 | 0.00 | 0.295340E+11 | 0.173761E+11 | 42516.66 | 31-AUG-18:03 | 16363.09 | 0.66 |
September | 0.00 | 0.00 | 0.108110E+11 | 0.934643E+10 | 29549.17 | 11-SEP-08:15 | 15611.99 | 0.35 |
October | 0.00 | 0.00 | 0.651794E+09 | 0.651794E+09 | 15305.42 | 20-OCT-15:01 | 15305.42 | 0.03 |
November | 0.00 | 0.00 | 24319535.87 | 24319535.87 | 2178.01 | 03-NOV-15:04 | 2178.01 | 0.01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.111849E+12 | 0.722446E+11 | 0.23 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.360767E+11 | 0.207031E+11 | 42516.66 | 16463.34 | 0.72 |
Report: CoilReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 827029.49 | 827029.49 | 265.97 | 17-JAN-23:50 | 265.97 | 0.00 |
February | 0.00 | 0.00 | 420853.21 | 420853.21 | 63.81 | 08-FEB-01:40 | 63.81 | 0.00 |
March | 0.00 | 0.00 | 0.296321E+10 | 0.296321E+10 | 73077.36 | 19-MAR-16:20 | 73077.36 | 0.02 |
April | 0.00 | 0.00 | 0.461052E+11 | 0.386240E+11 | 302330.66 | 18-APR-10:33 | 184258.89 | 0.14 |
May | 0.00 | 0.00 | 0.107628E+12 | 0.875143E+11 | 306217.52 | 30-MAY-19:20 | 195866.30 | 0.40 |
June | 0.00 | 0.00 | 0.328754E+12 | 0.224808E+12 | 392941.16 | 26-JUN-18:10 | 248612.10 | 0.75 |
July | 0.00 | 0.00 | 0.477460E+12 | 0.285823E+12 | 570571.76 | 03-JUL-21:30 | 207150.07 | 0.93 |
August | 0.00 | 0.00 | 0.413147E+12 | 0.251190E+12 | 582009.16 | 03-AUG-22:00 | 208530.62 | 0.86 |
September | 0.00 | 0.00 | 0.151579E+12 | 0.138980E+12 | 314331.36 | 11-SEP-19:20 | 195590.17 | 0.46 |
October | 0.00 | 0.00 | 0.104650E+11 | 0.104650E+11 | 141932.70 | 20-OCT-15:04 | 141932.70 | 0.05 |
November | 0.00 | 0.00 | 0.480727E+09 | 0.480727E+09 | 23065.85 | 03-NOV-15:20 | 23065.85 | 0.01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.153858E+13 | 0.104085E+13 | 0.30 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.477460E+12 | 0.285823E+12 | 582009.16 | 248612.10 | 0.93 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 11947728.69 | 8174068.53 | 13422.09 | 02-JAN-16:01 | 13422.09 | 0.00 |
February | 0.00 | 0.00 | 0.170058E+09 | 96829822.65 | 18090.78 | 17-FEB-16:01 | 18090.78 | 0.03 |
March | 0.00 | 0.00 | 0.581102E+09 | 0.366809E+09 | 18215.66 | 10-MAR-16:01 | 18215.66 | 0.11 |
April | 0.00 | 0.00 | 0.281369E+10 | 0.179277E+10 | 18216.34 | 30-APR-18:01 | 18216.34 | 0.34 |
May | 0.00 | 0.00 | 0.500199E+10 | 0.246007E+10 | 18279.72 | 11-MAY-18:01 | 14215.30 | 0.77 |
June | 0.00 | 0.00 | 0.839511E+10 | 0.452386E+10 | 19501.32 | 25-JUN-08:61 | 13404.22 | 0.86 |
July | 0.00 | 0.00 | 0.105912E+11 | 0.572579E+10 | 19797.95 | 20-JUL-08:61 | 13149.67 | 0.94 |
August | 0.00 | 0.00 | 0.950185E+10 | 0.484468E+10 | 21009.84 | 31-AUG-08:61 | 12124.86 | 0.94 |
September | 0.00 | 0.00 | 0.588425E+10 | 0.326764E+10 | 18216.22 | 20-SEP-18:01 | 18216.22 | 0.71 |
October | 0.00 | 0.00 | 0.138207E+10 | 0.734365E+09 | 17004.13 | 02-OCT-15:01 | 15338.86 | 0.30 |
November | 0.00 | 0.00 | 0.271021E+09 | 0.151522E+09 | 18210.83 | 12-NOV-16:01 | 18210.83 | 0.07 |
December | 0.00 | 0.00 | 17058917.10 | 13209977.61 | 18031.89 | 01-DEC-16:01 | 18031.89 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.446213E+11 | 0.239857E+11 | 0.43 | |||
Minimum of Months | 0.00 | 0.00 | 11947728.69 | 8174068.53 | 13422.09 | 12124.86 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.105912E+11 | 0.572579E+10 | 21009.84 | 18216.34 | 0.94 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 445746.74 | 283257.82 | 1980.23 | 13-JAN-16:03 | 761.25 | 0.00 |
February | 0.00 | 0.00 | 43381720.19 | 20906650.51 | 12761.82 | 25-FEB-16:01 | 12761.82 | 0.01 |
March | 0.00 | 0.00 | 0.194071E+09 | 0.116886E+09 | 17268.82 | 21-MAR-18:01 | 17268.82 | 0.05 |
April | 0.00 | 0.00 | 0.173919E+10 | 0.104927E+10 | 18300.62 | 16-APR-21:51 | 14566.52 | 0.24 |
May | 0.00 | 0.00 | 0.339015E+10 | 0.147853E+10 | 19853.16 | 20-MAY-18:41 | 19853.16 | 0.61 |
June | 0.00 | 0.00 | 0.662290E+10 | 0.363464E+10 | 22361.87 | 26-JUN-08:11 | 13090.51 | 0.67 |
July | 0.00 | 0.00 | 0.802168E+10 | 0.445769E+10 | 20777.55 | 02-JUL-08:51 | 13743.90 | 0.68 |
August | 0.00 | 0.00 | 0.670402E+10 | 0.331058E+10 | 22520.95 | 03-AUG-07:51 | 12638.48 | 0.68 |
September | 0.00 | 0.00 | 0.376176E+10 | 0.186289E+10 | 18652.46 | 11-SEP-08:51 | 13937.02 | 0.54 |
October | 0.00 | 0.00 | 0.460256E+09 | 0.203769E+09 | 17117.47 | 02-OCT-15:01 | 14413.29 | 0.15 |
November | 0.00 | 0.00 | 80292019.55 | 42452035.45 | 15574.59 | 03-NOV-15:01 | 15574.59 | 0.03 |
December | 0.00 | 0.00 | 803480.63 | 386347.61 | 1656.07 | 14-DEC-16:04 | 541.40 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.310190E+11 | 0.161783E+11 | 0.31 | |||
Minimum of Months | 0.00 | 0.00 | 445746.74 | 283257.82 | 1656.07 | 541.40 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.802168E+10 | 0.445769E+10 | 22520.95 | 19853.16 | 0.68 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 54434042.77 | 54434042.77 | 10930.25 | 25-FEB-16:04 | 10930.25 | 0.00 |
March | 0.00 | 0.00 | 0.506144E+10 | 0.451867E+10 | 37682.08 | 24-MAR-13:00 | 37682.08 | 0.05 |
April | 0.00 | 0.00 | 0.149769E+11 | 0.878031E+10 | 50880.70 | 15-APR-13:30 | 44929.05 | 0.28 |
May | 0.00 | 0.00 | 0.272912E+11 | 0.111987E+11 | 37433.33 | 06-MAY-12:50 | 25355.92 | 0.73 |
June | 0.00 | 0.00 | 0.379057E+11 | 0.147206E+11 | 39501.82 | 26-JUN-12:30 | 25962.15 | 0.91 |
July | 0.00 | 0.00 | 0.470862E+11 | 0.187972E+11 | 42419.00 | 30-JUL-13:30 | 30940.04 | 0.99 |
August | 0.00 | 0.00 | 0.482613E+11 | 0.206574E+11 | 47435.87 | 29-AUG-13:30 | 39436.54 | 1.00 |
September | 0.00 | 0.00 | 0.398317E+11 | 0.218532E+11 | 57393.47 | 07-SEP-13:00 | 41814.07 | 0.76 |
October | 0.00 | 0.00 | 0.214435E+11 | 0.177219E+11 | 57532.43 | 20-OCT-12:40 | 45737.96 | 0.23 |
November | 0.00 | 0.00 | 0.605362E+10 | 0.448688E+10 | 55536.35 | 04-NOV-12:30 | 42312.76 | 0.12 |
December | 0.00 | 0.00 | 42033819.82 | 42033819.82 | 7934.53 | 07-DEC-14:40 | 7934.53 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.248008E+12 | 0.122831E+12 | 0.42 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.482613E+11 | 0.218532E+11 | 57532.43 | 45737.96 | 1.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 17941576.86 | 12917953.14 | 25373.79 | 01-JAN-09:02 | 20097.48 | 0.00 |
February | 0.00 | 0.00 | 0.114159E+09 | 65960948.81 | 68949.84 | 26-FEB-09:02 | 68949.84 | 0.01 |
March | 0.00 | 0.00 | 0.318039E+10 | 0.149987E+10 | 88506.06 | 24-MAR-18:01 | 88506.06 | 0.15 |
April | 0.00 | 0.00 | 0.123480E+11 | 0.712377E+10 | 95314.96 | 16-APR-21:51 | 74657.29 | 0.31 |
May | 0.00 | 0.00 | 0.321907E+11 | 0.179686E+11 | 100914.47 | 11-MAY-21:42 | 70497.14 | 0.58 |
June | 0.00 | 0.00 | 0.480773E+11 | 0.290844E+11 | 115938.54 | 26-JUN-08:11 | 66222.68 | 0.65 |
July | 0.00 | 0.00 | 0.521400E+11 | 0.308387E+11 | 106548.10 | 02-JUL-08:51 | 71447.68 | 0.61 |
August | 0.00 | 0.00 | 0.462242E+11 | 0.261200E+11 | 121119.09 | 03-AUG-07:51 | 61062.27 | 0.60 |
September | 0.00 | 0.00 | 0.288645E+11 | 0.160348E+11 | 98405.85 | 11-SEP-21:51 | 74188.54 | 0.58 |
October | 0.00 | 0.00 | 0.844338E+10 | 0.401789E+10 | 88221.15 | 12-OCT-18:02 | 88221.15 | 0.36 |
November | 0.00 | 0.00 | 0.355329E+10 | 0.132574E+10 | 86344.16 | 04-NOV-18:01 | 86344.16 | 0.17 |
December | 0.00 | 0.00 | 23804994.42 | 20536925.52 | 34566.71 | 03-DEC-09:02 | 25424.19 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.235178E+12 | 0.134113E+12 | 0.34 | |||
Minimum of Months | 0.00 | 0.00 | 17941576.86 | 12917953.14 | 25373.79 | 20097.48 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.521400E+11 | 0.308387E+11 | 121119.09 | 88506.06 | 0.65 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 7715977.07 | 2161835.99 | 4321.60 | 12-JAN-16:01 | 3240.49 | 0.00 |
February | 0.00 | 0.00 | 0.113544E+09 | 64084499.16 | 15521.59 | 21-FEB-09:02 | 15521.59 | 0.03 |
March | 0.00 | 0.00 | 0.559293E+09 | 0.317923E+09 | 16624.01 | 22-MAR-15:01 | 16624.01 | 0.12 |
April | 0.00 | 0.00 | 0.241340E+10 | 0.138449E+10 | 16625.10 | 30-APR-18:01 | 16625.10 | 0.35 |
May | 0.00 | 0.00 | 0.533991E+10 | 0.260079E+10 | 16623.76 | 06-MAY-18:01 | 16623.76 | 0.82 |
June | 0.00 | 0.00 | 0.856265E+10 | 0.469420E+10 | 17670.14 | 14-JUN-08:62 | 12045.18 | 0.90 |
July | 0.00 | 0.00 | 0.103696E+11 | 0.560609E+10 | 18102.24 | 20-JUL-08:61 | 12006.21 | 0.96 |
August | 0.00 | 0.00 | 0.918999E+10 | 0.464582E+10 | 19211.82 | 31-AUG-08:61 | 10839.68 | 0.96 |
September | 0.00 | 0.00 | 0.593432E+10 | 0.328332E+10 | 16624.87 | 20-SEP-18:01 | 16624.87 | 0.75 |
October | 0.00 | 0.00 | 0.118724E+10 | 0.540770E+09 | 16163.87 | 02-OCT-15:01 | 13530.00 | 0.33 |
November | 0.00 | 0.00 | 0.232705E+09 | 0.111950E+09 | 15099.31 | 12-NOV-09:02 | 15099.31 | 0.08 |
December | 0.00 | 0.00 | 34725589.87 | 18581326.61 | 11586.01 | 03-DEC-09:02 | 11586.01 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.439451E+11 | 0.232702E+11 | 0.44 | |||
Minimum of Months | 0.00 | 0.00 | 7715977.07 | 2161835.99 | 4321.60 | 3240.49 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.103696E+11 | 0.560609E+10 | 19211.82 | 16625.10 | 0.96 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 565753.21 | 191700.18 | 2193.21 | 13-JAN-09:04 | 932.07 | 0.00 |
February | 0.00 | 0.00 | 23131942.79 | 8794177.93 | 11228.88 | 24-FEB-09:01 | 11228.88 | 0.01 |
March | 0.00 | 0.00 | 0.179145E+09 | 99604231.03 | 13848.42 | 19-MAR-15:01 | 13848.42 | 0.05 |
April | 0.00 | 0.00 | 0.143409E+10 | 0.784021E+09 | 17437.42 | 16-APR-08:51 | 14739.43 | 0.24 |
May | 0.00 | 0.00 | 0.390703E+10 | 0.187883E+10 | 19792.38 | 31-MAY-08:32 | 16698.84 | 0.67 |
June | 0.00 | 0.00 | 0.682501E+10 | 0.380955E+10 | 21008.12 | 26-JUN-07:52 | 15688.99 | 0.71 |
July | 0.00 | 0.00 | 0.780333E+10 | 0.425612E+10 | 20598.39 | 30-JUL-08:32 | 16025.30 | 0.70 |
August | 0.00 | 0.00 | 0.652620E+10 | 0.323889E+10 | 20431.36 | 03-AUG-07:51 | 13199.17 | 0.70 |
September | 0.00 | 0.00 | 0.385115E+10 | 0.194904E+10 | 18132.62 | 11-SEP-08:51 | 15113.16 | 0.57 |
October | 0.00 | 0.00 | 0.320695E+09 | 0.127632E+09 | 15554.04 | 02-OCT-15:01 | 12799.53 | 0.13 |
November | 0.00 | 0.00 | 32328038.73 | 13434812.83 | 12067.41 | 04-NOV-08:62 | 12067.41 | 0.02 |
December | 0.00 | 0.00 | 1331989.64 | 606534.45 | 2614.45 | 05-DEC-09:03 | 1337.80 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.309040E+11 | 0.161667E+11 | 0.32 | |||
Minimum of Months | 0.00 | 0.00 | 565753.21 | 191700.18 | 2193.21 | 932.07 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.780333E+10 | 0.425612E+10 | 21008.12 | 16698.84 | 0.71 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 2090041.25 | 1321572.11 | 3202.27 | 12-JAN-16:01 | 3202.27 | 0.00 |
February | 0.00 | 0.00 | 40855515.47 | 23688176.73 | 4541.91 | 17-FEB-16:01 | 4541.91 | 0.02 |
March | 0.00 | 0.00 | 0.129635E+09 | 84377955.68 | 4738.78 | 23-MAR-18:01 | 4738.78 | 0.08 |
April | 0.00 | 0.00 | 0.715218E+09 | 0.474447E+09 | 4738.43 | 25-APR-18:01 | 4738.43 | 0.30 |
May | 0.00 | 0.00 | 0.123616E+10 | 0.649875E+09 | 4878.55 | 29-MAY-08:61 | 3639.06 | 0.69 |
June | 0.00 | 0.00 | 0.213792E+10 | 0.120108E+10 | 5247.12 | 25-JUN-08:61 | 3340.78 | 0.83 |
July | 0.00 | 0.00 | 0.267999E+10 | 0.149985E+10 | 5361.98 | 20-JUL-08:61 | 3148.04 | 0.94 |
August | 0.00 | 0.00 | 0.235320E+10 | 0.123661E+10 | 5648.68 | 31-AUG-08:61 | 2873.96 | 0.93 |
September | 0.00 | 0.00 | 0.141528E+10 | 0.822468E+09 | 4901.68 | 11-SEP-08:61 | 3596.93 | 0.65 |
October | 0.00 | 0.00 | 0.323031E+09 | 0.184678E+09 | 4414.95 | 02-OCT-15:01 | 3993.85 | 0.23 |
November | 0.00 | 0.00 | 60895723.37 | 37861411.48 | 4737.30 | 12-NOV-16:01 | 4737.30 | 0.04 |
December | 0.00 | 0.00 | 3107899.46 | 2603047.38 | 4675.77 | 01-DEC-16:01 | 4675.77 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.110974E+11 | 0.621886E+10 | 0.39 | |||
Minimum of Months | 0.00 | 0.00 | 2090041.25 | 1321572.11 | 3202.27 | 2873.96 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.267999E+10 | 0.149985E+10 | 5648.68 | 4738.78 | 0.94 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 100586.62 | 43732.57 | 746.44 | 12-JAN-16:03 | 385.70 | 0.00 |
February | 0.00 | 0.00 | 8134413.29 | 3423702.82 | 3268.46 | 25-FEB-16:01 | 3268.46 | 0.01 |
March | 0.00 | 0.00 | 36855516.55 | 21981431.54 | 4483.38 | 21-MAR-18:01 | 4483.38 | 0.04 |
April | 0.00 | 0.00 | 0.439618E+09 | 0.276787E+09 | 4844.30 | 16-APR-21:51 | 3734.51 | 0.21 |
May | 0.00 | 0.00 | 0.841540E+09 | 0.395659E+09 | 5207.71 | 20-MAY-18:41 | 5207.71 | 0.55 |
June | 0.00 | 0.00 | 0.173850E+10 | 0.993095E+09 | 5917.34 | 26-JUN-08:11 | 3298.59 | 0.64 |
July | 0.00 | 0.00 | 0.210236E+10 | 0.120360E+10 | 5458.72 | 02-JUL-08:51 | 3522.57 | 0.68 |
August | 0.00 | 0.00 | 0.170690E+10 | 0.866213E+09 | 6070.65 | 03-AUG-07:51 | 3031.63 | 0.68 |
September | 0.00 | 0.00 | 0.904371E+09 | 0.472903E+09 | 5305.65 | 19-SEP-17:41 | 5305.65 | 0.48 |
October | 0.00 | 0.00 | 94840134.93 | 42338627.50 | 4486.75 | 02-OCT-15:01 | 3701.95 | 0.10 |
November | 0.00 | 0.00 | 17226258.24 | 9252540.33 | 4112.44 | 03-NOV-15:01 | 3990.97 | 0.01 |
December | 0.00 | 0.00 | 165478.25 | 109135.42 | 524.26 | 05-DEC-16:04 | 524.26 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.789061E+10 | 0.428541E+10 | 0.28 | |||
Minimum of Months | 0.00 | 0.00 | 100586.62 | 43732.57 | 524.26 | 385.70 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.210236E+10 | 0.120360E+10 | 6070.65 | 5305.65 | 0.68 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.576765E+09 | 0.474376E+09 | 21869.47 | 02-JAN-16:01 | 21869.47 | 0.03 |
February | 0.00 | 0.00 | 0.107896E+10 | 0.734518E+09 | 21869.46 | 17-FEB-16:01 | 21869.46 | 0.11 |
March | 0.00 | 0.00 | 0.194236E+10 | 0.126630E+10 | 21871.59 | 07-MAR-16:01 | 21871.59 | 0.21 |
April | 0.00 | 0.00 | 0.422791E+10 | 0.264945E+10 | 21872.37 | 30-APR-18:01 | 21872.37 | 0.39 |
May | 0.00 | 0.00 | 0.665083E+10 | 0.314308E+10 | 22385.64 | 31-MAY-08:61 | 17047.13 | 0.77 |
June | 0.00 | 0.00 | 0.997514E+10 | 0.508053E+10 | 24522.53 | 25-JUN-08:61 | 15376.19 | 0.86 |
July | 0.00 | 0.00 | 0.124323E+11 | 0.635888E+10 | 25284.76 | 20-JUL-08:61 | 14080.57 | 0.93 |
August | 0.00 | 0.00 | 0.123410E+11 | 0.641505E+10 | 26512.13 | 31-AUG-08:61 | 12889.24 | 0.92 |
September | 0.00 | 0.00 | 0.927069E+10 | 0.565463E+10 | 22807.04 | 11-SEP-08:61 | 16730.82 | 0.77 |
October | 0.00 | 0.00 | 0.460907E+10 | 0.290298E+10 | 19835.09 | 09-OCT-15:02 | 17738.22 | 0.53 |
November | 0.00 | 0.00 | 0.155914E+10 | 0.105320E+10 | 21864.47 | 21-NOV-16:01 | 21864.47 | 0.19 |
December | 0.00 | 0.00 | 0.103979E+10 | 0.870245E+09 | 21869.53 | 25-DEC-16:01 | 21869.53 | 0.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.657039E+11 | 0.366032E+11 | 0.48 | |||
Minimum of Months | 0.00 | 0.00 | 0.576765E+09 | 0.474376E+09 | 19835.09 | 12889.24 | 0.03 | |
Maximum of Months | 0.00 | 0.00 | 0.124323E+11 | 0.641505E+10 | 26512.13 | 21872.37 | 0.93 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 174820.76 | 590514.81 | 31-JAN-04:03 |
February | 0.01 | 19.05 | 25-FEB-16:00 | 133760.33 | 621924.34 | 02-FEB-06:00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 48008.78 | 212060.86 | 05-MAR-19:02 |
April | 0.00 | 0.00 | 01-APR-00:10 | 26769.03 | 172311.85 | 03-APR-08:62 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 17273.45 | 139339.26 | 01-MAY-18:04 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 10746.21 | 128438.03 | 03-JUN-08:03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1895.22 | 71809.09 | 24-JUL-05:00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 4359.78 | 99721.70 | 07-AUG-05:50 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16923.37 | 133863.47 | 27-SEP-08:07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 32377.18 | 154129.54 | 13-OCT-15:03 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 65000.14 | 567626.78 | 26-NOV-07:00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 99198.82 | 290053.07 | 09-DEC-09:06 |
Annual Sum or Average | 0.00 | 52176.45 | ||||
Minimum of Months | 0.00 | 0.00 | 1895.22 | 71809.09 | ||
Maximum of Months | 0.01 | 19.05 | 174820.76 | 621924.34 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 507.83 | 26200.37 | 01-JAN-09:02 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 1202.87 | 64803.49 | 24-FEB-16:03 | 0.00 | 0.00 | 01-FEB-00:01 |
March | 6813.18 | 230884.34 | 25-MAR-15:01 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 36825.93 | 481008.12 | 16-APR-18:03 | 0.00 | 0.00 | 01-APR-00:10 |
May | 77989.22 | 490446.13 | 30-MAY-18:03 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 189260.10 | 600119.99 | 26-JUN-18:03 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 251922.52 | 734219.44 | 26-JUL-18:03 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 221587.34 | 701309.26 | 21-AUG-21:51 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 104008.23 | 510926.68 | 06-SEP-15:03 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 20710.75 | 369957.27 | 20-OCT-15:01 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 5825.58 | 176454.57 | 03-NOV-15:01 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 805.13 | 44890.78 | 02-DEC-09:01 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 76990.93 | 0.00 | ||||
Minimum of Months | 507.83 | 26200.37 | 0.00 | 0.00 | ||
Maximum of Months | 251922.52 | 734219.44 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 30280.17 | 64225.72 | 31-JAN-07:50 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 30891.29 | 64647.10 | 21-FEB-07:40 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 30606.81 | 64549.17 | 01-MAR-07:30 |
April | 0.00 | 0.00 | 01-APR-00:10 | 29423.48 | 62712.76 | 03-APR-07:00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 27697.25 | 59738.18 | 01-MAY-06:20 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25881.35 | 55776.74 | 01-JUN-06:40 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 24429.58 | 52098.89 | 03-JUL-06:30 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23803.14 | 50020.72 | 01-AUG-06:45 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 24109.57 | 51198.73 | 29-SEP-06:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25290.43 | 54506.66 | 31-OCT-06:20 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27028.68 | 58339.91 | 30-NOV-07:30 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 28847.49 | 61750.50 | 29-DEC-07:50 |
Annual Sum or Average | 0.00 | 27336.57 | ||||
Minimum of Months | 0.00 | 0.00 | 23803.14 | 50020.72 | ||
Maximum of Months | 0.00 | 0.00 | 30891.29 | 64647.10 |
Report: FanReportMonthly
For: FLR_3_DOAS FAN
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.271000E+10 | 0.73 | 1299.30 | 01-JAN-16:05 | 0.92 |
February | 0.244774E+10 | 0.73 | 1299.30 | 05-FEB-07:50 | 0.92 |
March | 0.271000E+10 | 0.73 | 1299.30 | 03-MAR-16:15 | 0.92 |
April | 0.262258E+10 | 0.73 | 1299.30 | 01-APR-08:03 | 0.92 |
May | 0.271000E+10 | 0.72 | 1299.30 | 05-MAY-18:40 | 0.92 |
June | 0.262258E+10 | 0.72 | 1299.30 | 08-JUN-22:30 | 0.91 |
July | 0.271000E+10 | 0.72 | 1299.30 | 01-JUL-16:50 | 0.91 |
August | 0.271000E+10 | 0.72 | 1299.30 | 01-AUG-15:17 | 0.91 |
September | 0.262258E+10 | 0.72 | 1299.30 | 07-SEP-16:50 | 0.91 |
October | 0.271000E+10 | 0.73 | 1299.30 | 30-OCT-16:11 | 0.92 |
November | 0.262258E+10 | 0.73 | 1299.30 | 01-NOV-08:62 | 0.92 |
December | 0.271000E+10 | 0.73 | 1299.30 | 21-DEC-16:10 | 0.92 |
Annual Sum or Average | 0.319080E+11 | 0.73 | |||
Minimum of Months | 0.244774E+10 | 0.72 | 1299.30 | 0.91 | |
Maximum of Months | 0.271000E+10 | 0.73 | 1299.30 | 0.92 |
Report: FanReportMonthly
For: VAV WITH REHEAT FAN
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.306280E+11 | 0.78 | 17181.11 | 13-JAN-19:20 | 0.98 |
February | 0.282968E+11 | 0.79 | 17652.92 | 24-FEB-22:10 | 1.00 |
March | 0.330550E+11 | 0.81 | 19536.01 | 28-MAR-21:10 | 1.05 |
April | 0.333951E+11 | 0.83 | 25563.74 | 18-APR-21:10 | 1.23 |
May | 0.361592E+11 | 0.85 | 26688.65 | 31-MAY-21:10 | 1.26 |
June | 0.369565E+11 | 0.87 | 28271.61 | 30-JUN-21:10 | 1.31 |
July | 0.387275E+11 | 0.88 | 27694.78 | 27-JUL-21:10 | 1.29 |
August | 0.390156E+11 | 0.88 | 29414.03 | 22-AUG-21:10 | 1.34 |
September | 0.365582E+11 | 0.87 | 31600.90 | 08-SEP-21:10 | 1.40 |
October | 0.352611E+11 | 0.84 | 26781.40 | 20-OCT-21:10 | 1.28 |
November | 0.323792E+11 | 0.82 | 23003.73 | 03-NOV-21:10 | 1.17 |
December | 0.318388E+11 | 0.80 | 18460.40 | 04-DEC-21:10 | 1.02 |
Annual Sum or Average | 0.412271E+12 | 0.84 | |||
Minimum of Months | 0.282968E+11 | 0.78 | 17181.11 | 0.98 | |
Maximum of Months | 0.390156E+11 | 0.88 | 31600.90 | 1.40 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205205E+09 | 0.28 | 76.61 | 01-JAN-00:10 | 0.28 |
February | 0.185347E+09 | 0.28 | 76.61 | 01-FEB-00:01 | 0.28 |
March | 0.205205E+09 | 0.28 | 76.61 | 01-MAR-00:03 | 0.28 |
April | 0.198586E+09 | 0.28 | 76.61 | 01-APR-00:10 | 0.28 |
May | 0.205205E+09 | 0.28 | 76.61 | 01-MAY-00:05 | 0.28 |
June | 0.198586E+09 | 0.28 | 76.61 | 01-JUN-00:05 | 0.28 |
July | 0.205205E+09 | 0.28 | 76.61 | 01-JUL-00:10 | 0.28 |
August | 0.205205E+09 | 0.28 | 76.61 | 01-AUG-00:05 | 0.28 |
September | 0.198586E+09 | 0.28 | 76.61 | 01-SEP-00:05 | 0.28 |
October | 0.205205E+09 | 0.28 | 76.61 | 01-OCT-00:10 | 0.28 |
November | 0.198586E+09 | 0.28 | 76.61 | 01-NOV-00:05 | 0.28 |
December | 0.205205E+09 | 0.28 | 76.61 | 01-DEC-00:03 | 0.28 |
Annual Sum or Average | 0.241613E+10 | 0.28 | |||
Minimum of Months | 0.185347E+09 | 0.28 | 76.61 | 0.28 | |
Maximum of Months | 0.205205E+09 | 0.28 | 76.61 | 0.28 |
Report: FanReportMonthly
For: LOBBY_FLR_1 EXHAUST FAN
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:05 | -0.0 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:05 | -0.0 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 EXHAUST FAN
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 EXHAUST FAN
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116283E+10 | 0.20 | 612.92 | 01-JAN-07:05 | 0.28 |
February | 0.105030E+10 | 0.20 | 612.92 | 01-FEB-07:03 | 0.28 |
March | 0.116283E+10 | 0.20 | 612.92 | 01-MAR-07:05 | 0.28 |
April | 0.112532E+10 | 0.20 | 612.92 | 01-APR-06:05 | 0.28 |
May | 0.116283E+10 | 0.20 | 612.92 | 01-MAY-06:05 | 0.28 |
June | 0.112532E+10 | 0.20 | 612.92 | 01-JUN-06:05 | 0.28 |
July | 0.116283E+10 | 0.20 | 612.92 | 01-JUL-06:05 | 0.28 |
August | 0.116283E+10 | 0.20 | 612.92 | 01-AUG-06:05 | 0.28 |
September | 0.112532E+10 | 0.20 | 612.92 | 01-SEP-06:05 | 0.28 |
October | 0.116283E+10 | 0.20 | 612.92 | 01-OCT-06:10 | 0.28 |
November | 0.112532E+10 | 0.20 | 612.92 | 01-NOV-06:05 | 0.28 |
December | 0.116283E+10 | 0.20 | 612.92 | 01-DEC-07:05 | 0.28 |
Annual Sum or Average | 0.136914E+11 | 0.20 | |||
Minimum of Months | 0.105030E+10 | 0.20 | 612.92 | 0.28 | |
Maximum of Months | 0.116283E+10 | 0.20 | 612.92 | 0.28 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.685643E+09 | 0.52 | 871.42 | 01-JAN-09:02 | 0.60 |
February | 0.491767E+09 | 0.49 | 871.42 | 01-FEB-03:50 | 0.61 |
March | 0.269840E+09 | 0.46 | 871.42 | 01-MAR-09:02 | 0.60 |
April | 0.242175E+09 | 0.49 | 871.42 | 01-APR-08:62 | 0.60 |
May | 0.237326E+09 | 0.52 | 871.42 | 01-MAY-15:01 | 0.60 |
June | 0.363165E+09 | 0.55 | 871.42 | 01-JUN-08:61 | 0.60 |
July | 0.440916E+09 | 0.57 | 871.42 | 01-JUL-08:61 | 0.60 |
August | 0.395852E+09 | 0.56 | 871.42 | 01-AUG-08:61 | 0.60 |
September | 0.291480E+09 | 0.53 | 871.42 | 01-SEP-08:62 | 0.60 |
October | 0.174900E+09 | 0.46 | 871.42 | 01-OCT-15:01 | 0.60 |
November | 0.321919E+09 | 0.47 | 871.42 | 03-NOV-15:01 | 0.60 |
December | 0.527166E+09 | 0.51 | 871.42 | 01-DEC-09:01 | 0.60 |
Annual Sum or Average | 0.444215E+10 | 0.51 | |||
Minimum of Months | 0.174900E+09 | 0.46 | 871.42 | 0.60 | |
Maximum of Months | 0.685643E+09 | 0.57 | 871.42 | 0.61 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.813486E+09 | 0.57 | 845.26 | 01-JAN-09:02 | 0.60 |
February | 0.559110E+09 | 0.51 | 845.26 | 01-FEB-00:55 | 0.61 |
March | 0.285035E+09 | 0.45 | 845.26 | 01-MAR-09:02 | 0.60 |
April | 0.204053E+09 | 0.44 | 845.26 | 01-APR-08:62 | 0.60 |
May | 0.164737E+09 | 0.42 | 845.26 | 01-MAY-15:01 | 0.60 |
June | 0.285582E+09 | 0.43 | 845.26 | 01-JUN-08:61 | 0.60 |
July | 0.332235E+09 | 0.41 | 845.26 | 01-JUL-08:51 | 0.60 |
August | 0.276759E+09 | 0.41 | 845.26 | 01-AUG-08:51 | 0.60 |
September | 0.198520E+09 | 0.42 | 845.26 | 01-SEP-08:51 | 0.60 |
October | 0.163940E+09 | 0.42 | 845.26 | 01-OCT-15:01 | 0.60 |
November | 0.364574E+09 | 0.48 | 845.26 | 03-NOV-15:01 | 0.60 |
December | 0.584767E+09 | 0.55 | 845.26 | 01-DEC-09:01 | 0.60 |
Annual Sum or Average | 0.423280E+10 | 0.46 | |||
Minimum of Months | 0.163940E+09 | 0.41 | 845.26 | 0.60 | |
Maximum of Months | 0.813486E+09 | 0.57 | 845.26 | 0.61 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.500876E+09 | 0.17 | 1264.73 | 19-JAN-05:00 | 0.61 |
February | 91776025.55 | 0.04 | 1071.57 | 04-FEB-06:00 | 0.61 |
March | 0.198222E+09 | 0.11 | 1198.45 | 24-MAR-13:00 | 0.60 |
April | 0.544974E+09 | 0.24 | 1579.91 | 15-APR-13:30 | 0.60 |
May | 0.100122E+10 | 0.49 | 1199.48 | 06-MAY-13:00 | 0.60 |
June | 0.129522E+10 | 0.54 | 1220.36 | 26-JUN-12:50 | 0.60 |
July | 0.157415E+10 | 0.59 | 1320.58 | 30-JUL-13:30 | 0.60 |
August | 0.162042E+10 | 0.60 | 1482.98 | 29-AUG-13:30 | 0.60 |
September | 0.139176E+10 | 0.50 | 2525.31 | 07-SEP-12:50 | 0.60 |
October | 0.792473E+09 | 0.34 | 2755.57 | 20-OCT-12:30 | 0.60 |
November | 0.249472E+09 | 0.12 | 2639.36 | 04-NOV-12:30 | 0.60 |
December | 0.312729E+09 | 0.12 | 1095.13 | 13-DEC-04:05 | 0.61 |
Annual Sum or Average | 0.957330E+10 | 0.33 | |||
Minimum of Months | 91776025.55 | 0.04 | 1071.57 | 0.60 | |
Maximum of Months | 0.162042E+10 | 0.60 | 2755.57 | 0.61 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.355702E+10 | 0.48 | 4440.05 | 01-JAN-16:02 | 0.60 |
February | 0.262213E+10 | 0.46 | 4440.05 | 01-FEB-00:01 | 0.61 |
March | 0.108188E+10 | 0.42 | 4440.05 | 01-MAR-09:02 | 0.60 |
April | 0.888341E+09 | 0.40 | 4440.05 | 01-APR-08:62 | 0.60 |
May | 0.137906E+10 | 0.37 | 4440.05 | 01-MAY-08:61 | 0.60 |
June | 0.202752E+10 | 0.39 | 4440.05 | 01-JUN-08:61 | 0.60 |
July | 0.213877E+10 | 0.37 | 4440.05 | 01-JUL-08:51 | 0.60 |
August | 0.184927E+10 | 0.36 | 4440.05 | 01-AUG-08:51 | 0.60 |
September | 0.127601E+10 | 0.38 | 4440.05 | 01-SEP-08:51 | 0.60 |
October | 0.677824E+09 | 0.41 | 4440.05 | 01-OCT-08:61 | 0.60 |
November | 0.141866E+10 | 0.43 | 4440.05 | 01-NOV-15:01 | 0.60 |
December | 0.236912E+10 | 0.45 | 4440.05 | 01-DEC-09:01 | 0.60 |
Annual Sum or Average | 0.212856E+11 | 0.41 | |||
Minimum of Months | 0.677824E+09 | 0.36 | 4440.05 | 0.60 | |
Maximum of Months | 0.355702E+10 | 0.48 | 4440.05 | 0.61 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.661921E+09 | 0.52 | 794.87 | 01-JAN-09:02 | 0.60 |
February | 0.464033E+09 | 0.49 | 794.87 | 01-FEB-02:15 | 0.61 |
March | 0.249624E+09 | 0.46 | 794.87 | 01-MAR-09:02 | 0.60 |
April | 0.223617E+09 | 0.50 | 794.87 | 01-APR-08:62 | 0.60 |
May | 0.243645E+09 | 0.54 | 794.87 | 01-MAY-08:61 | 0.60 |
June | 0.360481E+09 | 0.56 | 794.87 | 01-JUN-08:61 | 0.60 |
July | 0.419038E+09 | 0.58 | 794.87 | 01-JUL-08:61 | 0.60 |
August | 0.370371E+09 | 0.58 | 794.87 | 01-AUG-08:61 | 0.60 |
September | 0.282069E+09 | 0.54 | 794.87 | 01-SEP-08:62 | 0.60 |
October | 0.159703E+09 | 0.48 | 794.87 | 01-OCT-08:61 | 0.60 |
November | 0.307468E+09 | 0.47 | 794.87 | 03-NOV-15:01 | 0.60 |
December | 0.499647E+09 | 0.51 | 794.87 | 01-DEC-09:01 | 0.60 |
Annual Sum or Average | 0.424162E+10 | 0.52 | |||
Minimum of Months | 0.159703E+09 | 0.46 | 794.87 | 0.60 | |
Maximum of Months | 0.661921E+09 | 0.58 | 794.87 | 0.61 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.775460E+09 | 0.57 | 772.68 | 01-JAN-09:02 | 0.60 |
February | 0.539922E+09 | 0.51 | 772.68 | 01-FEB-00:01 | 0.61 |
March | 0.262199E+09 | 0.44 | 772.68 | 01-MAR-09:02 | 0.60 |
April | 0.192640E+09 | 0.44 | 772.68 | 01-APR-08:62 | 0.60 |
May | 0.184060E+09 | 0.45 | 772.68 | 01-MAY-08:61 | 0.60 |
June | 0.293149E+09 | 0.45 | 772.68 | 01-JUN-08:61 | 0.60 |
July | 0.319765E+09 | 0.42 | 772.68 | 01-JUL-08:32 | 0.60 |
August | 0.265992E+09 | 0.42 | 772.68 | 01-AUG-08:32 | 0.60 |
September | 0.194547E+09 | 0.44 | 772.68 | 01-SEP-08:51 | 0.60 |
October | 0.147413E+09 | 0.41 | 772.68 | 01-OCT-08:61 | 0.60 |
November | 0.348299E+09 | 0.48 | 772.68 | 04-NOV-08:62 | 0.60 |
December | 0.558640E+09 | 0.56 | 772.68 | 01-DEC-09:01 | 0.60 |
Annual Sum or Average | 0.408209E+10 | 0.47 | |||
Minimum of Months | 0.147413E+09 | 0.41 | 772.68 | 0.60 | |
Maximum of Months | 0.775460E+09 | 0.57 | 772.68 | 0.61 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.217604E+09 | 0.55 | 226.72 | 01-JAN-09:02 | 0.60 |
February | 0.145539E+09 | 0.52 | 226.72 | 01-FEB-02:40 | 0.61 |
March | 83122711.43 | 0.47 | 226.72 | 01-MAR-09:02 | 0.60 |
April | 71927220.94 | 0.50 | 226.72 | 01-APR-08:62 | 0.60 |
May | 62727278.44 | 0.52 | 226.72 | 01-MAY-15:01 | 0.60 |
June | 95517701.43 | 0.54 | 226.72 | 01-JUN-08:61 | 0.60 |
July | 0.113723E+09 | 0.56 | 226.72 | 01-JUL-08:61 | 0.60 |
August | 99685296.30 | 0.56 | 226.72 | 01-AUG-08:61 | 0.60 |
September | 76538829.84 | 0.52 | 226.72 | 01-SEP-15:01 | 0.60 |
October | 54778690.99 | 0.46 | 226.72 | 01-OCT-15:01 | 0.60 |
November | 0.104510E+09 | 0.49 | 226.72 | 03-NOV-15:01 | 0.60 |
December | 0.162166E+09 | 0.53 | 226.72 | 01-DEC-09:01 | 0.60 |
Annual Sum or Average | 0.128784E+10 | 0.52 | |||
Minimum of Months | 54778690.99 | 0.46 | 226.72 | 0.60 | |
Maximum of Months | 0.217604E+09 | 0.56 | 226.72 | 0.61 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.246824E+09 | 0.58 | 219.35 | 01-JAN-09:02 | 0.60 |
February | 0.164772E+09 | 0.55 | 219.35 | 01-FEB-00:01 | 0.61 |
March | 89736037.90 | 0.48 | 219.35 | 01-MAR-09:02 | 0.60 |
April | 61387972.08 | 0.44 | 219.35 | 01-APR-08:62 | 0.60 |
May | 44096327.53 | 0.42 | 219.35 | 01-MAY-15:01 | 0.60 |
June | 78097362.17 | 0.43 | 219.35 | 01-JUN-08:61 | 0.60 |
July | 89008375.04 | 0.41 | 219.35 | 01-JUL-08:51 | 0.60 |
August | 71091619.61 | 0.41 | 219.35 | 01-AUG-08:51 | 0.59 |
September | 53347868.98 | 0.42 | 219.35 | 01-SEP-08:51 | 0.60 |
October | 52906427.48 | 0.42 | 219.35 | 01-OCT-15:01 | 0.60 |
November | 0.116051E+09 | 0.50 | 219.35 | 01-NOV-08:62 | 0.60 |
December | 0.183038E+09 | 0.57 | 219.35 | 01-DEC-09:01 | 0.60 |
Annual Sum or Average | 0.125036E+10 | 0.47 | |||
Minimum of Months | 44096327.53 | 0.41 | 219.35 | 0.59 | |
Maximum of Months | 0.246824E+09 | 0.58 | 219.35 | 0.61 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.712613E+09 | 0.50 | 1043.48 | 01-JAN-09:02 | 0.60 |
February | 0.489835E+09 | 0.48 | 1043.48 | 01-FEB-09:02 | 0.61 |
March | 0.333268E+09 | 0.49 | 1043.48 | 01-MAR-09:02 | 0.60 |
April | 0.321708E+09 | 0.50 | 1043.48 | 01-APR-15:02 | 0.60 |
May | 0.296561E+09 | 0.52 | 1043.48 | 01-MAY-08:61 | 0.60 |
June | 0.406610E+09 | 0.54 | 1043.48 | 01-JUN-08:61 | 0.60 |
July | 0.487707E+09 | 0.56 | 1043.48 | 01-JUL-08:61 | 0.60 |
August | 0.488991E+09 | 0.56 | 1043.48 | 01-AUG-08:61 | 0.60 |
September | 0.434202E+09 | 0.54 | 1043.48 | 01-SEP-08:62 | 0.60 |
October | 0.300055E+09 | 0.50 | 1043.48 | 01-OCT-08:61 | 0.60 |
November | 0.375691E+09 | 0.48 | 1043.48 | 01-NOV-15:01 | 0.60 |
December | 0.603126E+09 | 0.52 | 1043.48 | 01-DEC-09:01 | 0.60 |
Annual Sum or Average | 0.525037E+10 | 0.52 | |||
Minimum of Months | 0.296561E+09 | 0.48 | 1043.48 | 0.60 | |
Maximum of Months | 0.712613E+09 | 0.56 | 1043.48 | 0.61 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.250273E+10 | 0.225246E+10 | 1743.68 | 19-JAN-04:40 | 1569.31 | 1569.31 | 35.17 | 5.59 |
February | 0.170039E+10 | 0.153035E+10 | 1728.13 | 04-FEB-06:00 | 1555.32 | 1555.32 | 34.28 | 5.55 |
March | 0.109394E+10 | 0.984543E+09 | 1094.57 | 05-MAR-19:02 | 985.11 | 985.11 | 32.02 | 1.81 |
April | 0.599246E+09 | 0.539322E+09 | 945.10 | 03-APR-08:62 | 850.59 | 850.59 | 30.47 | 1.40 |
May | 0.313822E+09 | 0.282440E+09 | 821.08 | 01-MAY-18:04 | 738.97 | 738.97 | 30.41 | 1.13 |
June | 0.186054E+09 | 0.167449E+09 | 791.50 | 03-JUN-08:03 | 712.35 | 712.35 | 31.25 | 1.07 |
July | 33339757.20 | 30005781.48 | 470.75 | 24-JUL-05:00 | 423.67 | 423.67 | 28.97 | 0.55 |
August | 76473635.27 | 68826271.74 | 644.02 | 07-AUG-05:50 | 579.62 | 579.62 | 30.59 | 0.81 |
September | 0.315417E+09 | 0.283876E+09 | 952.52 | 28-SEP-08:04 | 857.27 | 857.27 | 41.11 | 1.41 |
October | 0.707084E+09 | 0.636375E+09 | 913.99 | 03-OCT-08:05 | 822.59 | 822.59 | 32.98 | 1.32 |
November | 0.122410E+10 | 0.110169E+10 | 1644.46 | 26-NOV-06:50 | 1480.02 | 1480.02 | 34.48 | 5.30 |
December | 0.192425E+10 | 0.173183E+10 | 1292.82 | 09-DEC-09:04 | 1163.54 | 1163.54 | 35.22 | 2.79 |
Annual Sum or Average | 0.106768E+11 | 0.960916E+10 | ||||||
Minimum of Months | 33339757.20 | 30005781.48 | 470.75 | 423.67 | 423.67 | 28.97 | 0.55 | |
Maximum of Months | 0.250273E+10 | 0.225246E+10 | 1743.68 | 1569.31 | 1569.31 | 41.11 | 5.59 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 148901.87 | 134011.68 | 11.74 | 01-JAN-09:02 | 10.56 | 10.56 | 6.72 | 1.61 |
February | 469267.71 | 422340.94 | 34.11 | 25-FEB-09:02 | 30.69 | 30.69 | 6.72 | 3.04 |
March | 5763146.87 | 5186832.19 | 159.57 | 25-MAR-15:01 | 143.61 | 143.61 | 6.72 | 6.77 |
April | 62099839.52 | 55889855.57 | 603.29 | 16-APR-18:03 | 542.96 | 542.96 | 6.72 | 12.48 |
May | 0.120348E+09 | 0.108313E+09 | 644.25 | 31-MAY-18:03 | 579.82 | 579.82 | 6.72 | 12.85 |
June | 0.398429E+09 | 0.358586E+09 | 999.45 | 26-JUN-18:03 | 899.50 | 899.50 | 6.72 | 15.53 |
July | 0.562389E+09 | 0.506150E+09 | 1411.33 | 26-JUL-18:02 | 1270.20 | 1270.20 | 6.72 | 17.96 |
August | 0.478384E+09 | 0.430546E+09 | 1187.10 | 03-AUG-18:02 | 1068.39 | 1068.39 | 6.72 | 16.70 |
September | 0.195755E+09 | 0.176179E+09 | 692.66 | 06-SEP-18:02 | 623.40 | 623.40 | 6.72 | 13.26 |
October | 22028199.62 | 19825379.66 | 312.85 | 20-OCT-15:01 | 281.57 | 281.57 | 6.72 | 9.29 |
November | 4855142.10 | 4369627.89 | 145.12 | 05-NOV-15:01 | 130.61 | 130.61 | 6.72 | 6.46 |
December | 280204.18 | 252183.77 | 27.27 | 02-DEC-09:01 | 24.54 | 24.54 | 6.72 | 2.68 |
Annual Sum or Average | 0.185095E+10 | 0.166585E+10 | ||||||
Minimum of Months | 148901.87 | 134011.68 | 11.74 | 10.56 | 10.56 | 6.72 | 1.61 | |
Maximum of Months | 0.562389E+09 | 0.506150E+09 | 1411.33 | 1270.20 | 1270.20 | 6.72 | 17.96 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.826677E+09 | 0.744009E+09 | 3344.76 | 01-JAN-09:02 | 3010.28 | 3010.28 | 6.91 | 29.59 |
February | 0.140062E+10 | 0.126056E+10 | 3344.76 | 01-FEB-12:50 | 3010.28 | 3010.28 | 6.73 | 29.59 |
March | 0.355701E+10 | 0.320131E+10 | 3344.76 | 01-MAR-09:05 | 3010.28 | 3010.28 | 6.78 | 29.59 |
April | 0.556796E+10 | 0.501116E+10 | 3344.76 | 01-APR-08:62 | 3010.28 | 3010.28 | 6.95 | 29.59 |
May | 0.884660E+10 | 0.796194E+10 | 3344.76 | 01-MAY-00:05 | 3010.28 | 3010.28 | 6.79 | 29.59 |
June | 0.857931E+10 | 0.772138E+10 | 3344.76 | 01-JUN-00:05 | 3010.28 | 3010.28 | 7.14 | 29.59 |
July | 0.895861E+10 | 0.806274E+10 | 3344.76 | 01-JUL-00:10 | 3010.28 | 3010.28 | 7.92 | 29.59 |
August | 0.895861E+10 | 0.806274E+10 | 3344.76 | 01-AUG-00:05 | 3010.28 | 3010.28 | 8.54 | 29.59 |
September | 0.826925E+10 | 0.744233E+10 | 3344.76 | 01-SEP-00:05 | 3010.28 | 3010.28 | 7.56 | 29.59 |
October | 0.675581E+10 | 0.608023E+10 | 3344.76 | 01-OCT-06:20 | 3010.28 | 3010.28 | 6.74 | 29.59 |
November | 0.303856E+10 | 0.273470E+10 | 3344.76 | 01-NOV-05:03 | 3010.28 | 3010.28 | 6.74 | 29.59 |
December | 0.110400E+10 | 0.993600E+09 | 3344.76 | 01-DEC-09:03 | 3010.28 | 3010.28 | 6.75 | 29.59 |
Annual Sum or Average | 0.658630E+11 | 0.592767E+11 | ||||||
Minimum of Months | 0.826677E+09 | 0.744009E+09 | 3344.76 | 3010.28 | 3010.28 | 6.73 | 29.59 | |
Maximum of Months | 0.895861E+10 | 0.806274E+10 | 3344.76 | 3010.28 | 3010.28 | 8.54 | 29.59 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:10 | 14.37 | 14.37 | 47.70 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:01 | 14.37 | 14.37 | 47.24 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:03 | 14.37 | 14.37 | 47.87 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 51.48 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:05 | 14.37 | 14.37 | 51.64 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:05 | 14.37 | 14.37 | 52.20 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 52.92 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:05 | 14.37 | 14.37 | 53.01 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:05 | 14.37 | 14.37 | 53.06 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:10 | 14.37 | 14.37 | 52.20 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:05 | 14.37 | 14.37 | 52.37 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:03 | 14.37 | 14.37 | 49.02 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 47.24 | 0.37 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 53.06 | 0.37 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 42.21 | 60.00 | 174820.76 | 590514.81 | 31-JAN-04:03 |
February | 0.01 | 19.05 | 25-FEB-16:00 | 60.03 | 60.03 | 133760.33 | 621924.34 | 02-FEB-06:00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 36.89 | 60.00 | 48008.78 | 212060.86 | 05-MAR-19:02 |
April | 0.00 | 0.00 | 01-APR-00:10 | 49.41 | 60.00 | 26769.03 | 172311.85 | 03-APR-08:62 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.78 | 60.00 | 17273.45 | 139339.26 | 01-MAY-18:04 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 28.11 | 60.00 | 10746.21 | 128438.03 | 03-JUN-08:03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 37.08 | 37.08 | 1895.22 | 71809.09 | 24-JUL-05:00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 30.89 | 30.89 | 4359.78 | 99721.70 | 07-AUG-05:50 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 28.97 | 28.97 | 16923.37 | 133863.47 | 27-SEP-08:07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 52.20 | 60.00 | 32377.18 | 154129.54 | 13-OCT-15:03 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 51.03 | 60.00 | 65000.14 | 567626.78 | 26-NOV-07:00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 41.71 | 60.00 | 99198.82 | 290053.07 | 09-DEC-09:06 |
Annual Sum or Average | 0.00 | 52176.45 | ||||||
Minimum of Months | 0.00 | 0.00 | 28.11 | 28.97 | 1895.22 | 71809.09 | ||
Maximum of Months | 0.01 | 19.05 | 60.03 | 60.03 | 174820.76 | 621924.34 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 507.83 | 26200.37 | 01-JAN-09:02 | 6.91 | 6.70 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 1202.87 | 64803.49 | 24-FEB-16:03 | 7.22 | 6.70 | 0.00 | 0.00 | 01-FEB-00:01 |
March | 6813.18 | 230884.34 | 25-MAR-15:01 | 8.56 | 6.70 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 36825.93 | 481008.12 | 16-APR-18:03 | 10.58 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 77989.22 | 490446.13 | 30-MAY-18:03 | 10.66 | 6.70 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 189260.10 | 600119.99 | 26-JUN-18:03 | 11.54 | 6.70 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 251922.52 | 734219.44 | 26-JUL-18:03 | 12.63 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 221587.34 | 701309.26 | 21-AUG-21:51 | 12.36 | 6.70 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 104008.23 | 510926.68 | 06-SEP-15:03 | 10.82 | 6.70 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 20710.75 | 369957.27 | 20-OCT-15:01 | 9.68 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 5825.58 | 176454.57 | 03-NOV-15:01 | 8.12 | 6.70 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 805.13 | 44890.78 | 02-DEC-09:01 | 7.06 | 6.70 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 76990.93 | 0.00 | ||||||
Minimum of Months | 507.83 | 26200.37 | 6.91 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 251922.52 | 734219.44 | 12.63 | 6.70 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 47.70 | 60.05 | 30280.17 | 64225.72 | 31-JAN-07:50 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 47.24 | 60.05 | 30891.29 | 64647.10 | 21-FEB-07:40 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 47.87 | 60.05 | 30606.81 | 64549.17 | 01-MAR-07:30 |
April | 0.00 | 0.00 | 01-APR-00:10 | 51.48 | 60.05 | 29423.48 | 62712.76 | 03-APR-07:00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 51.64 | 60.05 | 27697.25 | 59738.18 | 01-MAY-06:20 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 52.20 | 60.05 | 25881.35 | 55776.74 | 01-JUN-06:40 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 52.92 | 60.05 | 24429.58 | 52098.89 | 03-JUL-06:30 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 53.01 | 60.05 | 23803.14 | 50020.72 | 01-AUG-06:45 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 53.06 | 60.05 | 24109.57 | 51198.73 | 29-SEP-06:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 52.20 | 60.05 | 25290.43 | 54506.66 | 31-OCT-06:20 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 52.37 | 60.05 | 27028.68 | 58339.91 | 30-NOV-07:30 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 49.02 | 60.05 | 28847.49 | 61750.50 | 29-DEC-07:50 |
Annual Sum or Average | 0.00 | 27336.57 | ||||||
Minimum of Months | 0.00 | 0.00 | 47.24 | 60.05 | 23803.14 | 50020.72 | ||
Maximum of Months | 0.00 | 0.00 | 53.06 | 60.05 | 30891.29 | 64647.10 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.163225E+11 | 0.00 | 0.00 | 0.271000E+10 | 0.00 | 0.00 |
February | 0.110961E+11 | 0.00 | 0.00 | 0.244774E+10 | 0.00 | 0.00 |
March | 0.230999E+10 | 0.00 | 0.212226E+09 | 0.271000E+10 | 0.00 | 0.00 |
April | 0.435202E+09 | 0.00 | 0.322158E+10 | 0.262258E+10 | 0.00 | 0.00 |
May | 10075.16 | 0.00 | 0.743526E+10 | 0.271000E+10 | 0.00 | 0.00 |
June | 13542.62 | 0.00 | 0.238818E+11 | 0.262258E+10 | 0.00 | 0.00 |
July | 14162.12 | 0.00 | 0.360767E+11 | 0.271000E+10 | 0.00 | 0.00 |
August | 14422.16 | 0.00 | 0.295340E+11 | 0.271000E+10 | 0.00 | 0.00 |
September | 299025.44 | 0.00 | 0.108110E+11 | 0.262258E+10 | 0.00 | 0.00 |
October | 21426625.45 | 0.00 | 0.651794E+09 | 0.271000E+10 | 0.00 | 0.00 |
November | 0.383360E+10 | 0.00 | 24319535.87 | 0.262258E+10 | 0.00 | 0.00 |
December | 0.690334E+10 | 0.00 | 0.00 | 0.271000E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.409225E+11 | 0.00 | 0.111849E+12 | 0.319080E+11 | 0.00 | 0.00 |
Minimum of Months | 10075.16 | 0.00 | 0.00 | 0.244774E+10 | 0.00 | 0.00 |
Maximum of Months | 0.163225E+11 | 0.00 | 0.360767E+11 | 0.271000E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.350393E+12 | 0.00 | 827029.49 | 0.306280E+11 | 0.00 | 0.00 |
February | 0.246764E+12 | 0.00 | 420853.21 | 0.282968E+11 | 0.00 | 0.00 |
March | 0.959845E+11 | 0.00 | 0.296321E+10 | 0.330550E+11 | 0.00 | 0.00 |
April | 0.579477E+11 | 0.00 | 0.461052E+11 | 0.333951E+11 | 0.00 | 0.00 |
May | 0.459277E+11 | 0.00 | 0.107628E+12 | 0.361592E+11 | 0.00 | 0.00 |
June | 0.277745E+11 | 0.00 | 0.328754E+12 | 0.369565E+11 | 0.00 | 0.00 |
July | 0.507692E+10 | 0.00 | 0.477460E+12 | 0.387275E+11 | 0.00 | 0.00 |
August | 0.116869E+11 | 0.00 | 0.413147E+12 | 0.390156E+11 | 0.00 | 0.00 |
September | 0.423912E+11 | 0.00 | 0.151579E+12 | 0.365582E+11 | 0.00 | 0.00 |
October | 0.785447E+11 | 0.00 | 0.104650E+11 | 0.352611E+11 | 0.00 | 0.00 |
November | 0.124700E+12 | 0.00 | 0.480727E+09 | 0.323792E+11 | 0.00 | 0.00 |
December | 0.179516E+12 | 0.00 | 0.00 | 0.318388E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.126671E+13 | 0.00 | 0.153858E+13 | 0.412271E+12 | 0.00 | 0.00 |
Minimum of Months | 0.507692E+10 | 0.00 | 0.00 | 0.282968E+11 | 0.00 | 0.00 |
Maximum of Months | 0.350393E+12 | 0.00 | 0.477460E+12 | 0.390156E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.271000E+10 | 0.00 | 0.163225E+11 | 0.702666E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244774E+10 | 0.00 | 0.110961E+11 | 0.525898E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.271000E+10 | 0.212226E+09 | 0.230999E+10 | 0.539284E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.262258E+10 | 0.322158E+10 | 0.435202E+09 | 0.333203E+11 | 0.750791E+09 | 0.00 | 0.00 | 0.00 |
May | 0.271000E+10 | 0.743526E+10 | 10075.16 | 0.105232E+11 | 0.680266E+09 | 0.00 | 0.00 | 0.00 |
June | 0.262258E+10 | 0.238818E+11 | 13542.62 | 0.341800E+10 | 0.671019E+10 | 0.00 | 0.00 | 0.00 |
July | 0.271000E+10 | 0.360767E+11 | 14162.12 | 0.460418E+09 | 0.809428E+10 | 0.00 | 0.00 | 0.00 |
August | 0.271000E+10 | 0.295340E+11 | 14422.16 | 0.114661E+10 | 0.711921E+10 | 0.00 | 0.00 | 0.00 |
September | 0.262258E+10 | 0.108110E+11 | 299025.44 | 0.112153E+11 | 0.168508E+10 | 0.00 | 0.00 | 0.00 |
October | 0.271000E+10 | 0.651794E+09 | 21426625.45 | 0.323555E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.262258E+10 | 24319535.87 | 0.383360E+10 | 0.491203E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.271000E+10 | 0.00 | 0.690334E+10 | 0.740954E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319080E+11 | 0.111849E+12 | 0.409225E+11 | 0.392440E+12 | 0.250398E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244774E+10 | 0.00 | 10075.16 | 0.460418E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.271000E+10 | 0.360767E+11 | 0.163225E+11 | 0.740954E+11 | 0.809428E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.306280E+11 | 827029.49 | 0.350393E+12 | 0.808795E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.282968E+11 | 420853.21 | 0.246764E+12 | 0.604203E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.330550E+11 | 0.296321E+10 | 0.959845E+11 | 0.588884E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.333951E+11 | 0.461052E+11 | 0.579477E+11 | 0.341624E+12 | 0.625405E+10 | 0.00 | 0.00 | 0.00 |
May | 0.361592E+11 | 0.107628E+12 | 0.459277E+11 | 0.615828E+11 | 0.470540E+10 | 0.00 | 0.00 | 0.00 |
June | 0.369565E+11 | 0.328754E+12 | 0.277745E+11 | 0.884624E+10 | 0.558497E+11 | 0.00 | 0.00 | 0.00 |
July | 0.387275E+11 | 0.477460E+12 | 0.507692E+10 | 0.724740E+09 | 0.655165E+11 | 0.00 | 0.00 | 0.00 |
August | 0.390156E+11 | 0.413147E+12 | 0.116869E+11 | 0.134750E+10 | 0.569139E+11 | 0.00 | 0.00 | 0.00 |
September | 0.365582E+11 | 0.151579E+12 | 0.423912E+11 | 0.760416E+11 | 0.947889E+10 | 0.00 | 0.00 | 0.00 |
October | 0.352611E+11 | 0.104650E+11 | 0.785447E+11 | 0.283203E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.323792E+11 | 0.480727E+09 | 0.124700E+12 | 0.538190E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.318388E+11 | 0.00 | 0.179516E+12 | 0.852515E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.412271E+12 | 0.153858E+13 | 0.126671E+13 | 0.416596E+13 | 0.198718E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.282968E+11 | 0.00 | 0.507692E+10 | 0.724740E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.390156E+11 | 0.477460E+12 | 0.350393E+12 | 0.852515E+12 | 0.655165E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.271000E+10 | 0.163225E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244774E+10 | 0.110961E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.271000E+10 | 0.230999E+10 | 0.212226E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.262258E+10 | 0.435202E+09 | 0.322158E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.271000E+10 | 10075.16 | 0.743526E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.262258E+10 | 13542.62 | 0.238818E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.271000E+10 | 14162.12 | 0.360767E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.271000E+10 | 14422.16 | 0.295340E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.262258E+10 | 299025.44 | 0.108110E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.271000E+10 | 21426625.45 | 0.651794E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.262258E+10 | 0.383360E+10 | 24319535.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.271000E+10 | 0.690334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319080E+11 | 0.409225E+11 | 0.111849E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244774E+10 | 10075.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.271000E+10 | 0.163225E+11 | 0.360767E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.306280E+11 | 0.350393E+12 | 827029.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.282968E+11 | 0.246764E+12 | 420853.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.330550E+11 | 0.959845E+11 | 0.296321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.333951E+11 | 0.579477E+11 | 0.461052E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.361592E+11 | 0.459277E+11 | 0.107628E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.369565E+11 | 0.277745E+11 | 0.328754E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.387275E+11 | 0.507692E+10 | 0.477460E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.390156E+11 | 0.116869E+11 | 0.413147E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.365582E+11 | 0.423912E+11 | 0.151579E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.352611E+11 | 0.785447E+11 | 0.104650E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.323792E+11 | 0.124700E+12 | 0.480727E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.318388E+11 | 0.179516E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.412271E+12 | 0.126671E+13 | 0.153858E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.282968E+11 | 0.507692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.390156E+11 | 0.350393E+12 | 0.477460E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.602439E+11 | 0.00 | 0.00 | 2300266.25 | 0.00 | 0.979953E+10 | 0.597239E+10 | 0.00 | 0.98 |
February | 0.367773E+11 | 0.00 | 0.00 | 2882.98 | 0.00 | 0.258704E+11 | 0.128830E+09 | 0.00 | 0.98 |
March | 0.515337E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.99 |
April | 0.447227E+11 | 0.00 | 0.00 | 0.00 | 0.481230E+09 | 0.00 | 0.00 | 0.00 | 0.98 |
May | 0.416586E+11 | 0.00 | 0.00 | 0.00 | 0.583016E+09 | 0.00 | 0.00 | 0.00 | 0.99 |
June | 0.245503E+11 | 0.00 | 0.00 | 7513.24 | 0.542495E+10 | 0.00 | 0.135921E+09 | 0.00 | 0.99 |
July | 0.121251E+11 | 0.154707E+10 | 0.00 | 3129379.80 | 0.725527E+10 | 0.00 | 0.258829E+10 | 0.00 | 0.99 |
August | 0.265376E+10 | 0.316028E+10 | 0.00 | 27868588.51 | 0.486123E+10 | 0.00 | 0.181261E+11 | 0.00 | 1.02 |
September | 0.202873E+10 | 0.296061E+09 | 0.00 | 56152744.06 | 0.229048E+09 | 0.00 | 0.384739E+11 | 0.00 | 1.07 |
October | 0.230922E+10 | 0.00 | 0.00 | 62338101.21 | 0.00 | 0.00 | 0.554345E+11 | 0.00 | 1.09 |
November | 0.104621E+11 | 0.00 | 0.00 | 50737556.88 | 0.00 | 0.00 | 0.472344E+11 | 0.00 | 1.07 |
December | 0.180999E+11 | 0.00 | 0.00 | 33406911.47 | 0.00 | 0.00 | 0.417817E+11 | 0.00 | 1.02 |
Annual Sum or Average | 0.307165E+12 | 0.500341E+10 | 0.00 | 0.235944E+09 | 0.188347E+11 | 0.356699E+11 | 0.209876E+12 | 0.00 | 1.02 |
Minimum of Months | 0.202873E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.98 |
Maximum of Months | 0.602439E+11 | 0.316028E+10 | 0.00 | 62338101.21 | 0.725527E+10 | 0.258704E+11 | 0.554345E+11 | 0.00 | 1.09 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.234558E+10 | 0.00 | 0.00 | 112477.00 | 0.00 | 0.925278E+10 | 0.177684E+09 | 0.00 | 2.74 |
February | 0.323782E+10 | 0.00 | 0.00 | 330718.42 | 0.00 | 0.623203E+10 | 0.286142E+09 | 0.00 | 2.76 |
March | 0.546931E+10 | 0.00 | 0.00 | 468280.50 | 0.00 | 0.207413E+10 | 0.456072E+09 | 0.00 | 2.78 |
April | 0.568830E+10 | 88257092.62 | 0.00 | 747032.43 | 5664849.36 | 0.653091E+09 | 0.609660E+09 | 0.00 | 2.80 |
May | 0.617665E+10 | 56993207.40 | 0.00 | 463483.15 | 35753165.01 | 0.00 | 0.278684E+09 | 0.00 | 2.79 |
June | 0.361201E+10 | 0.613794E+09 | 0.00 | 398034.99 | 0.267573E+09 | 0.00 | 0.211885E+09 | 0.00 | 2.82 |
July | 0.209802E+10 | 0.930349E+09 | 0.00 | 543841.20 | 0.486657E+09 | 0.00 | 0.183207E+09 | 0.00 | 2.85 |
August | 0.270057E+10 | 0.816138E+09 | 0.00 | 1331444.37 | 0.475863E+09 | 0.00 | 0.434694E+09 | 0.00 | 2.89 |
September | 0.509887E+10 | 0.105525E+09 | 0.00 | 2517868.76 | 3999359.19 | 7271999.66 | 0.712143E+09 | 0.00 | 2.95 |
October | 0.711441E+10 | 0.00 | 0.00 | 1760979.89 | 0.00 | 26015796.78 | 0.117509E+10 | 0.00 | 2.85 |
November | 0.502821E+10 | 0.00 | 0.00 | 595863.02 | 0.00 | 0.293424E+10 | 0.420438E+09 | 0.00 | 2.79 |
December | 0.269811E+10 | 0.00 | 0.00 | 326690.49 | 0.00 | 0.586798E+10 | 0.350908E+09 | 0.00 | 2.75 |
Annual Sum or Average | 0.512678E+11 | 0.261106E+10 | 0.00 | 9596714.21 | 0.127551E+10 | 0.270476E+11 | 0.529660E+10 | 0.00 | 2.82 |
Minimum of Months | 0.209802E+10 | 0.00 | 0.00 | 112477.00 | 0.00 | 0.00 | 0.177684E+09 | 0.00 | 2.74 |
Maximum of Months | 0.711441E+10 | 0.930349E+09 | 0.00 | 2517868.76 | 0.486657E+09 | 0.925278E+10 | 0.117509E+10 | 0.00 | 2.95 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.492689E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204255E+10 | 0.00 | 0.00 | 1.40 |
February | 0.354511E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221037E+10 | 0.00 | 0.00 | 1.41 |
March | 0.459273E+10 | 0.00 | 0.00 | 34071.62 | 0.00 | 0.00 | 0.131941E+09 | 0.00 | 1.42 |
April | 0.353994E+10 | 17998658.63 | 0.00 | 515602.68 | 26356714.26 | 0.00 | 0.575326E+09 | 0.00 | 1.43 |
May | 0.267329E+10 | 9162045.75 | 0.00 | 887157.16 | 44670846.47 | 0.00 | 0.115938E+10 | 0.00 | 1.43 |
June | 0.118103E+10 | 0.303122E+09 | 0.00 | 1742026.31 | 0.215199E+09 | 0.00 | 0.112161E+10 | 0.00 | 1.48 |
July | 0.310036E+09 | 0.598723E+09 | 0.00 | 2109134.91 | 0.269830E+09 | 0.00 | 0.107893E+10 | 0.00 | 1.50 |
August | 0.295892E+09 | 0.479318E+09 | 0.00 | 2736498.31 | 0.286628E+09 | 0.00 | 0.164319E+10 | 0.00 | 1.50 |
September | 0.189663E+10 | 36034903.28 | 0.00 | 2252744.55 | 12468123.93 | 0.00 | 0.159185E+10 | 0.00 | 1.47 |
October | 0.414830E+10 | 0.00 | 0.00 | 313139.12 | 0.00 | 0.00 | 0.664995E+09 | 0.00 | 1.42 |
November | 0.444345E+10 | 0.00 | 0.00 | 67209.09 | 0.00 | 0.286015E+09 | 0.189973E+09 | 0.00 | 1.41 |
December | 0.526417E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1415482.60 | 0.00 | 0.00 | 1.40 |
Annual Sum or Average | 0.368175E+11 | 0.144436E+10 | 0.00 | 10657583.76 | 0.855152E+09 | 0.454035E+10 | 0.815719E+10 | 0.00 | 1.44 |
Minimum of Months | 0.295892E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.40 |
Maximum of Months | 0.526417E+10 | 0.598723E+09 | 0.00 | 2736498.31 | 0.286628E+09 | 0.221037E+10 | 0.164319E+10 | 0.00 | 1.50 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.130535E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.416738E+10 | 0.00 | 0.00 | 0.52 |
February | 0.205858E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246089E+10 | 0.00 | 0.00 | 0.52 |
March | 0.333662E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.373447E+09 | 0.00 | 0.00 | 0.53 |
April | 0.320362E+10 | 0.00 | 0.00 | 0.00 | 34645173.85 | 16096637.09 | 0.00 | 0.00 | 0.52 |
May | 0.298855E+10 | 416840.58 | 0.00 | 27663.17 | 41556221.21 | 0.00 | 10558627.91 | 0.00 | 0.53 |
June | 0.166932E+10 | 0.103174E+09 | 0.00 | 220812.51 | 0.293792E+09 | 0.00 | 0.111004E+09 | 0.00 | 0.54 |
July | 0.891240E+09 | 0.214791E+09 | 0.00 | 392179.07 | 0.435679E+09 | 0.00 | 0.171881E+09 | 0.00 | 0.54 |
August | 0.118945E+10 | 0.194933E+09 | 0.00 | 431868.68 | 0.382641E+09 | 0.00 | 0.266927E+09 | 0.00 | 0.54 |
September | 0.254873E+10 | 2198667.83 | 0.00 | 301280.75 | 35272733.02 | 0.00 | 0.140363E+09 | 0.00 | 0.53 |
October | 0.377735E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
November | 0.298550E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.877524E+09 | 0.00 | 0.00 | 0.52 |
December | 0.228067E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185412E+10 | 0.00 | 0.00 | 0.52 |
Annual Sum or Average | 0.282350E+11 | 0.515514E+09 | 0.00 | 1373804.18 | 0.122359E+10 | 0.974946E+10 | 0.700733E+09 | 0.00 | 0.53 |
Minimum of Months | 0.891240E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
Maximum of Months | 0.377735E+10 | 0.214791E+09 | 0.00 | 431868.68 | 0.435679E+09 | 0.416738E+10 | 0.266927E+09 | 0.00 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.168248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310205E+10 | 0.00 | 0.00 | 0.54 |
February | 0.608699E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209196E+10 | 0.00 | 0.00 | 0.54 |
March | 0.141260E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.804389E+09 | 0.00 | 0.00 | 0.54 |
April | 0.179425E+10 | 0.00 | 0.00 | 0.00 | 20702634.00 | 0.129732E+09 | 0.00 | 0.00 | 0.54 |
May | 0.179216E+10 | 0.00 | 0.00 | 0.00 | 25081500.24 | 0.00 | 0.00 | 0.00 | 0.55 |
June | 0.104958E+10 | 21575806.09 | 0.00 | 49298.49 | 0.211995E+09 | 0.00 | 12543888.23 | 0.00 | 0.55 |
July | 0.622368E+09 | 45764767.20 | 0.00 | 12202.29 | 0.333079E+09 | 0.00 | 10726277.35 | 0.00 | 0.55 |
August | 0.859354E+09 | 36877609.85 | 0.00 | 14700.86 | 0.301718E+09 | 0.00 | 8050688.60 | 0.00 | 0.55 |
September | 0.159759E+10 | 127631.04 | 0.00 | 4974.50 | 22182147.78 | 0.00 | 6595703.48 | 0.00 | 0.55 |
October | 0.225720E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 |
November | 0.145613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.852271E+09 | 0.00 | 0.00 | 0.54 |
December | 0.405814E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206498E+10 | 0.00 | 0.00 | 0.54 |
Annual Sum or Average | 0.140240E+11 | 0.104346E+09 | 0.00 | 81176.14 | 0.914759E+09 | 0.904538E+10 | 37916557.67 | 0.00 | 0.54 |
Minimum of Months | 0.168248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 |
Maximum of Months | 0.225720E+10 | 45764767.20 | 0.00 | 49298.49 | 0.333079E+09 | 0.310205E+10 | 12543888.23 | 0.00 | 0.55 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.352328E+10 | 0.00 | 0.00 | 84109325.38 | 0.00 | 0.206192E+11 | 0.893215E+11 | 0.00 | 23.24 |
February | 0.115574E+10 | 0.00 | 0.00 | 75055624.54 | 0.00 | 0.233068E+11 | 0.682933E+11 | 0.00 | 23.30 |
March | 0.231113E+09 | 0.00 | 0.00 | 95554909.59 | 0.00 | 0.00 | 0.804114E+11 | 0.00 | 24.10 |
April | 0.132607E+09 | 0.671713E+09 | 0.00 | 94177291.29 | 588756.09 | 0.00 | 0.697405E+11 | 0.00 | 23.98 |
May | 60180394.05 | 0.842312E+09 | 0.00 | 0.108954E+09 | 4306607.37 | 0.00 | 0.654200E+11 | 0.00 | 24.16 |
June | 23759086.09 | 0.823571E+10 | 0.00 | 81926850.64 | 2098160.73 | 0.00 | 0.380391E+11 | 0.00 | 24.16 |
July | 19161421.91 | 0.143307E+11 | 0.00 | 68905920.22 | 4410462.89 | 0.00 | 0.219305E+11 | 0.00 | 24.07 |
August | 12937273.22 | 0.124246E+11 | 0.00 | 84533315.78 | 681874.85 | 0.00 | 0.310741E+11 | 0.00 | 24.27 |
September | 86727497.12 | 0.746512E+09 | 0.00 | 0.107025E+09 | 0.00 | 0.00 | 0.586688E+11 | 0.00 | 24.15 |
October | 0.159692E+09 | 0.00 | 0.00 | 97135017.49 | 0.00 | 0.00 | 0.817904E+11 | 0.00 | 24.07 |
November | 0.969676E+09 | 0.00 | 0.00 | 90572044.07 | 0.00 | 0.252366E+10 | 0.796578E+11 | 0.00 | 23.90 |
December | 0.409201E+09 | 0.00 | 0.00 | 94630090.67 | 0.00 | 0.00 | 0.887468E+11 | 0.00 | 23.62 |
Annual Sum or Average | 0.678407E+10 | 0.372515E+11 | 0.00 | 0.108258E+10 | 12085861.93 | 0.464496E+11 | 0.773094E+12 | 0.00 | 23.92 |
Minimum of Months | 12937273.22 | 0.00 | 0.00 | 68905920.22 | 0.00 | 0.00 | 0.219305E+11 | 0.00 | 23.24 |
Maximum of Months | 0.352328E+10 | 0.143307E+11 | 0.00 | 0.108954E+09 | 4410462.89 | 0.233068E+11 | 0.893215E+11 | 0.00 | 24.27 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.327482E+11 | 0.00 | 0.00 | 1007567.20 | 0.00 | 0.139571E+11 | 0.216027E+10 | 0.00 | 4.05 |
February | 0.224269E+11 | 0.00 | 0.00 | 2857625.28 | 0.00 | 0.134706E+11 | 0.457459E+10 | 0.00 | 4.09 |
March | 0.222743E+11 | 0.00 | 0.00 | 6126304.05 | 0.00 | 0.00 | 0.109423E+11 | 0.00 | 4.11 |
April | 0.144760E+11 | 0.352200E+09 | 0.00 | 12073454.25 | 10222782.20 | 0.00 | 0.144022E+11 | 0.00 | 4.14 |
May | 0.842312E+10 | 0.322982E+09 | 0.00 | 15487563.03 | 55570036.47 | 0.00 | 0.184141E+11 | 0.00 | 4.14 |
June | 0.450228E+10 | 0.317253E+10 | 0.00 | 16597897.90 | 0.439854E+09 | 0.00 | 0.114809E+11 | 0.00 | 4.21 |
July | 0.126475E+10 | 0.513241E+10 | 0.00 | 17010009.97 | 0.755983E+09 | 0.00 | 0.832161E+10 | 0.00 | 4.26 |
August | 0.143935E+10 | 0.466359E+10 | 0.00 | 23995518.95 | 0.729193E+09 | 0.00 | 0.118102E+11 | 0.00 | 4.31 |
September | 0.669069E+10 | 0.401346E+09 | 0.00 | 27154796.63 | 4391035.87 | 0.00 | 0.177281E+11 | 0.00 | 4.36 |
October | 0.131470E+11 | 0.00 | 0.00 | 16826127.38 | 0.00 | 0.00 | 0.213360E+11 | 0.00 | 4.21 |
November | 0.231650E+11 | 0.00 | 0.00 | 5870847.20 | 0.00 | 0.219545E+10 | 0.941731E+10 | 0.00 | 4.12 |
December | 0.310273E+11 | 0.00 | 0.00 | 2381868.24 | 0.00 | 0.225515E+10 | 0.373577E+10 | 0.00 | 4.06 |
Annual Sum or Average | 0.181585E+12 | 0.140451E+11 | 0.00 | 0.147390E+09 | 0.199521E+10 | 0.318782E+11 | 0.134323E+12 | 0.00 | 4.17 |
Minimum of Months | 0.126475E+10 | 0.00 | 0.00 | 1007567.20 | 0.00 | 0.00 | 0.216027E+10 | 0.00 | 4.05 |
Maximum of Months | 0.327482E+11 | 0.513241E+10 | 0.00 | 27154796.63 | 0.755983E+09 | 0.139571E+11 | 0.213360E+11 | 0.00 | 4.36 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.111831E+12 | 0.00 | 0.00 | 392810.70 | 0.00 | 0.382832E+11 | 0.129102E+10 | 0.00 | 1.82 |
February | 0.762117E+11 | 0.00 | 0.00 | 1422390.62 | 0.00 | 0.434351E+11 | 0.538442E+10 | 0.00 | 1.82 |
March | 0.811137E+11 | 0.00 | 0.00 | 9413368.40 | 0.00 | 0.00 | 0.215554E+11 | 0.00 | 1.84 |
April | 0.552559E+11 | 0.718389E+09 | 0.00 | 27852634.02 | 0.243563E+09 | 0.00 | 0.346032E+11 | 0.00 | 1.85 |
May | 0.299275E+11 | 0.459970E+09 | 0.00 | 54337756.57 | 0.707103E+09 | 0.00 | 0.542577E+11 | 0.00 | 1.87 |
June | 0.145299E+11 | 0.838787E+10 | 0.00 | 60248981.35 | 0.286803E+10 | 0.00 | 0.366278E+11 | 0.00 | 1.95 |
July | 0.363143E+10 | 0.145605E+11 | 0.00 | 63171670.19 | 0.420168E+10 | 0.00 | 0.277175E+11 | 0.00 | 1.98 |
August | 0.384649E+10 | 0.125335E+11 | 0.00 | 80245938.00 | 0.426259E+10 | 0.00 | 0.401120E+11 | 0.00 | 1.99 |
September | 0.225551E+11 | 0.935194E+09 | 0.00 | 79337328.99 | 0.115710E+09 | 0.00 | 0.548635E+11 | 0.00 | 1.93 |
October | 0.520033E+11 | 0.00 | 0.00 | 34045803.55 | 0.00 | 0.00 | 0.530947E+11 | 0.00 | 1.84 |
November | 0.784825E+11 | 0.00 | 0.00 | 13204267.78 | 0.00 | 0.485382E+10 | 0.236319E+11 | 0.00 | 1.83 |
December | 0.111034E+12 | 0.00 | 0.00 | 641695.46 | 0.00 | 0.00 | 0.335579E+10 | 0.00 | 1.81 |
Annual Sum or Average | 0.640422E+12 | 0.375955E+11 | 0.00 | 0.424315E+09 | 0.123987E+11 | 0.865721E+11 | 0.356495E+12 | 0.00 | 1.88 |
Minimum of Months | 0.363143E+10 | 0.00 | 0.00 | 392810.70 | 0.00 | 0.00 | 0.129102E+10 | 0.00 | 1.81 |
Maximum of Months | 0.111831E+12 | 0.145605E+11 | 0.00 | 80245938.00 | 0.426259E+10 | 0.434351E+11 | 0.548635E+11 | 0.00 | 1.99 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 51653776.83 | 0.00 | 0.00 | 120844.40 | 0.00 | 0.252278E+10 | 6909874.29 | 0.00 | 0.35 |
February | 47328224.99 | 0.00 | 0.00 | 663244.68 | 0.00 | 0.208138E+10 | 68295620.02 | 0.00 | 0.35 |
March | 66205035.88 | 0.00 | 0.00 | 2255897.78 | 0.00 | 0.117839E+10 | 0.312933E+09 | 0.00 | 0.36 |
April | 49473876.88 | 24959990.83 | 0.00 | 6079991.11 | 0.00 | 0.633324E+09 | 0.610454E+09 | 0.00 | 0.35 |
May | 18728104.46 | 31187770.01 | 25861.71 | 11770255.01 | 0.00 | 62908258.17 | 0.913594E+09 | 3153.83 | 0.36 |
June | 10882507.99 | 0.319227E+09 | 96490.52 | 8391736.82 | 0.00 | 20159876.85 | 0.444759E+09 | 11478.18 | 0.36 |
July | 1628014.14 | 0.528707E+09 | 215231.17 | 6385460.55 | 0.00 | 394572.37 | 0.198555E+09 | 29878.99 | 0.36 |
August | 0.00 | 0.375166E+09 | 347276.17 | 8402392.25 | 0.00 | 507358.77 | 0.333087E+09 | 27061.71 | 0.36 |
September | 19669327.23 | 62853359.77 | 26872.70 | 9294979.43 | 0.00 | 0.156999E+09 | 0.704989E+09 | 6102.57 | 0.36 |
October | 56102712.04 | 0.00 | 0.00 | 4749078.68 | 0.00 | 0.678106E+09 | 0.703741E+09 | 0.00 | 0.35 |
November | 60124486.43 | 0.00 | 0.00 | 1078605.39 | 0.00 | 0.132969E+10 | 0.245460E+09 | 0.00 | 0.35 |
December | 44897846.58 | 0.00 | 0.00 | 181469.86 | 0.00 | 0.171519E+10 | 11044576.81 | 0.00 | 0.35 |
Annual Sum or Average | 0.426694E+09 | 0.134210E+10 | 711732.26 | 59373955.97 | 0.00 | 0.103798E+11 | 0.455382E+10 | 77675.28 | 0.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 120844.40 | 0.00 | 394572.37 | 6909874.29 | 0.00 | 0.35 |
Maximum of Months | 66205035.88 | 0.528707E+09 | 347276.17 | 11770255.01 | 0.00 | 0.252278E+10 | 0.913594E+09 | 29878.99 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 4928397.71 | 0.00 | 0.00 | 8059.74 | 0.00 | 0.257492E+10 | 1308500.02 | 0.00 | 0.35 |
February | 24856631.00 | 0.00 | 0.00 | 265994.99 | 0.00 | 0.214382E+10 | 28468046.99 | 0.00 | 0.35 |
March | 78154548.76 | 0.00 | 0.00 | 1163242.55 | 0.00 | 0.127548E+10 | 0.204801E+09 | 0.00 | 0.36 |
April | 0.104239E+09 | 22978693.12 | 8369.91 | 4133972.83 | 1964179.03 | 0.726360E+09 | 0.464447E+09 | 5824.34 | 0.36 |
May | 0.153234E+09 | 23992631.83 | 24947.20 | 8855977.81 | 7191431.31 | 74306558.11 | 0.770486E+09 | 4117.71 | 0.36 |
June | 90942078.46 | 0.282376E+09 | 219518.42 | 5914380.31 | 36688381.19 | 23131727.38 | 0.364148E+09 | 13813.97 | 0.36 |
July | 81063446.23 | 0.438519E+09 | 220421.87 | 4521450.22 | 90129546.85 | 245020.81 | 0.121109E+09 | 20660.95 | 0.36 |
August | 0.110765E+09 | 0.314541E+09 | 396031.63 | 5688063.83 | 60535881.83 | 450517.01 | 0.225054E+09 | 23226.38 | 0.36 |
September | 0.132654E+09 | 56873576.83 | 36614.81 | 5919811.18 | 5962533.57 | 0.197723E+09 | 0.554552E+09 | 6241.77 | 0.36 |
October | 0.107376E+09 | 0.00 | 0.00 | 2429622.88 | 0.00 | 0.904722E+09 | 0.428002E+09 | 0.00 | 0.35 |
November | 55230086.48 | 0.00 | 0.00 | 523426.55 | 0.00 | 0.143252E+10 | 0.147890E+09 | 0.00 | 0.35 |
December | 14311477.08 | 0.00 | 0.00 | 12637.04 | 0.00 | 0.175584E+10 | 940311.92 | 0.00 | 0.35 |
Annual Sum or Average | 0.957754E+09 | 0.113928E+10 | 905903.85 | 39436639.92 | 0.202472E+09 | 0.111095E+11 | 0.331120E+10 | 73885.13 | 0.36 |
Minimum of Months | 4928397.71 | 0.00 | 0.00 | 8059.74 | 0.00 | 245020.81 | 940311.92 | 0.00 | 0.35 |
Maximum of Months | 0.153234E+09 | 0.438519E+09 | 396031.63 | 8855977.81 | 90129546.85 | 0.257492E+10 | 0.770486E+09 | 23226.38 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.999228E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187256E+09 | 0.00 | 0.00 | 0.02 |
February | 0.132673E+10 | 0.00 | 0.00 | 46352.93 | 0.00 | 0.00 | 64932390.84 | 0.00 | 0.02 |
March | 0.726669E+09 | 0.00 | 0.00 | 1186175.42 | 0.00 | 0.00 | 0.431993E+09 | 0.00 | 0.02 |
April | 0.476722E+09 | 55192028.55 | 0.00 | 1635756.90 | 0.00 | 0.00 | 0.673704E+09 | 0.00 | 0.02 |
May | 62642834.13 | 0.118397E+09 | 0.00 | 2004509.62 | 0.00 | 0.00 | 0.783956E+09 | 0.00 | 0.02 |
June | 0.145819E+09 | 0.417537E+09 | 0.00 | 1194907.04 | 0.00 | 0.00 | 0.238356E+09 | 0.00 | 0.02 |
July | 0.00 | 0.688856E+09 | 0.00 | 582228.03 | 0.00 | 0.00 | 74835811.94 | 0.00 | 0.02 |
August | 0.00 | 0.581292E+09 | 0.00 | 898733.62 | 0.00 | 0.00 | 78474261.07 | 0.00 | 0.02 |
September | 0.218433E+09 | 89148771.65 | 0.00 | 2398892.95 | 0.00 | 0.00 | 0.572053E+09 | 0.00 | 0.02 |
October | 0.414527E+09 | 0.00 | 0.00 | 3699911.76 | 0.00 | 0.00 | 0.100165E+10 | 0.00 | 0.02 |
November | 0.963926E+09 | 0.00 | 0.00 | 933609.69 | 0.00 | 0.00 | 0.290979E+09 | 0.00 | 0.02 |
December | 0.792605E+09 | 0.00 | 0.00 | 7863.70 | 0.00 | 0.174042E+09 | 16530133.96 | 0.00 | 0.02 |
Annual Sum or Average | 0.612730E+10 | 0.195042E+10 | 0.00 | 14588941.67 | 0.00 | 0.361298E+09 | 0.422746E+10 | 0.00 | 0.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
Maximum of Months | 0.132673E+10 | 0.688856E+09 | 0.00 | 3699911.76 | 0.00 | 0.187256E+09 | 0.100165E+10 | 0.00 | 0.02 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.707601E+09 | 0.00 | 0.00 | 495609.03 | 0.00 | 0.337711E+11 | 0.532707E+09 | 0.00 | 0.40 |
February | 0.803394E+09 | 0.00 | 0.00 | 2274825.90 | 0.00 | 0.262412E+11 | 0.275968E+10 | 0.00 | 0.40 |
March | 0.126932E+10 | 0.00 | 0.00 | 18441958.80 | 0.00 | 0.106432E+11 | 0.922399E+10 | 0.00 | 0.40 |
April | 0.153165E+10 | 0.282635E+09 | 321022.29 | 46667061.27 | 55541509.55 | 0.271596E+10 | 0.133283E+11 | 30479.68 | 0.40 |
May | 0.227677E+10 | 0.260011E+09 | 397748.83 | 0.114147E+09 | 0.162969E+09 | 20670011.57 | 0.112462E+11 | 9903.91 | 0.40 |
June | 0.128600E+10 | 0.380509E+10 | 1094839.87 | 76470381.51 | 0.524865E+09 | 9015216.72 | 0.519554E+10 | 31891.96 | 0.40 |
July | 0.112400E+10 | 0.587322E+10 | 1382325.04 | 54441061.89 | 0.129942E+10 | 2079509.12 | 0.162647E+10 | 47724.59 | 0.41 |
August | 0.156464E+10 | 0.410213E+10 | 4541681.15 | 67481549.84 | 0.986577E+09 | 2637170.28 | 0.300368E+10 | 136502.83 | 0.41 |
September | 0.190002E+10 | 0.726982E+09 | 2497174.24 | 78161606.55 | 0.123349E+09 | 51067272.78 | 0.100546E+11 | 86652.54 | 0.40 |
October | 0.145650E+10 | 0.00 | 0.00 | 43779026.32 | 0.00 | 0.994694E+09 | 0.170721E+11 | 0.00 | 0.40 |
November | 0.105888E+10 | 0.00 | 0.00 | 16655315.99 | 0.00 | 0.129408E+11 | 0.817722E+10 | 0.00 | 0.40 |
December | 0.958335E+09 | 0.00 | 0.00 | 635591.96 | 0.00 | 0.223373E+11 | 0.727710E+09 | 0.00 | 0.40 |
Annual Sum or Average | 0.159371E+11 | 0.150501E+11 | 10234791.42 | 0.519651E+09 | 0.315272E+10 | 0.109730E+12 | 0.829481E+11 | 343155.50 | 0.40 |
Minimum of Months | 0.707601E+09 | 0.00 | 0.00 | 495609.03 | 0.00 | 2079509.12 | 0.532707E+09 | 0.00 | 0.40 |
Maximum of Months | 0.227677E+10 | 0.587322E+10 | 4541681.15 | 0.114147E+09 | 0.129942E+10 | 0.337711E+11 | 0.170721E+11 | 136502.83 | 0.41 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 42029229.29 | 0.00 | 0.00 | 44119.33 | 0.00 | 0.252461E+10 | 14779521.71 | 0.00 | 0.35 |
February | 40237652.93 | 0.00 | 0.00 | 514891.47 | 0.00 | 0.208053E+10 | 76382429.14 | 0.00 | 0.35 |
March | 59277232.66 | 0.00 | 0.00 | 2053288.59 | 0.00 | 0.114737E+10 | 0.351082E+09 | 0.00 | 0.36 |
April | 31204955.42 | 24959592.87 | 0.00 | 5204124.52 | 0.00 | 0.667638E+09 | 0.595285E+09 | 397.96 | 0.35 |
May | 11057972.30 | 31207547.97 | 7673.29 | 12041996.89 | 0.00 | 52657942.19 | 0.931243E+09 | 1564.29 | 0.36 |
June | 6857554.70 | 0.319298E+09 | 34094.46 | 8837138.47 | 0.00 | 11622839.64 | 0.456876E+09 | 3269.02 | 0.36 |
July | 1628014.14 | 0.528681E+09 | 259164.18 | 6783043.44 | 0.00 | 255456.53 | 0.198296E+09 | 11598.36 | 0.36 |
August | 0.00 | 0.375244E+09 | 284805.69 | 8111746.47 | 0.00 | 461709.06 | 0.333423E+09 | 12155.53 | 0.36 |
September | 15645920.06 | 62876632.82 | 9222.24 | 9415887.95 | 0.00 | 0.153676E+09 | 0.712214E+09 | 479.97 | 0.36 |
October | 45894308.18 | 0.00 | 0.00 | 4193432.25 | 0.00 | 0.686166E+09 | 0.706445E+09 | 0.00 | 0.35 |
November | 60124486.43 | 0.00 | 0.00 | 945680.80 | 0.00 | 0.132135E+10 | 0.253928E+09 | 0.00 | 0.35 |
December | 44033710.47 | 0.00 | 0.00 | 155593.27 | 0.00 | 0.168524E+10 | 41890241.79 | 0.00 | 0.35 |
Annual Sum or Average | 0.357991E+09 | 0.134227E+10 | 594959.86 | 58300943.46 | 0.00 | 0.103316E+11 | 0.467185E+10 | 29465.13 | 0.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 44119.33 | 0.00 | 255456.53 | 14779521.71 | 0.00 | 0.35 |
Maximum of Months | 60124486.43 | 0.528681E+09 | 284805.69 | 12041996.89 | 0.00 | 0.252461E+10 | 0.931243E+09 | 12155.53 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 4398527.02 | 0.00 | 0.00 | 8908.88 | 0.00 | 0.257586E+10 | 892037.99 | 0.00 | 0.35 |
February | 25875148.93 | 0.00 | 0.00 | 127066.14 | 0.00 | 0.214814E+10 | 23272949.35 | 0.00 | 0.35 |
March | 81995125.58 | 0.00 | 0.00 | 875223.68 | 0.00 | 0.126640E+10 | 0.210322E+09 | 0.00 | 0.36 |
April | 98272401.80 | 23194766.37 | 27467.95 | 3325923.48 | 1731327.42 | 0.740929E+09 | 0.456652E+09 | 3504.66 | 0.36 |
May | 0.135852E+09 | 24413248.69 | 34673.93 | 9358933.98 | 6762011.12 | 65880143.19 | 0.795791E+09 | 3194.30 | 0.36 |
June | 84906732.84 | 0.284215E+09 | 175561.46 | 6118805.50 | 34893352.61 | 14136414.54 | 0.378975E+09 | 14297.38 | 0.36 |
July | 79471147.96 | 0.442786E+09 | 193658.85 | 4512565.98 | 85901928.37 | 279228.19 | 0.122675E+09 | 7848.89 | 0.36 |
August | 0.110091E+09 | 0.316622E+09 | 404898.01 | 5191095.34 | 58454387.10 | 687319.71 | 0.225987E+09 | 15404.60 | 0.36 |
September | 0.123057E+09 | 57323582.68 | 42264.68 | 6013517.10 | 5510460.91 | 0.178828E+09 | 0.582950E+09 | 2658.71 | 0.36 |
October | 0.107376E+09 | 0.00 | 0.00 | 1621303.77 | 0.00 | 0.910141E+09 | 0.423391E+09 | 0.00 | 0.35 |
November | 52133874.46 | 0.00 | 0.00 | 250692.92 | 0.00 | 0.143153E+10 | 0.152242E+09 | 0.00 | 0.35 |
December | 4951344.45 | 0.00 | 0.00 | 18532.63 | 0.00 | 0.176163E+10 | 4510139.29 | 0.00 | 0.35 |
Annual Sum or Average | 0.908381E+09 | 0.114855E+10 | 878524.88 | 37422569.40 | 0.193253E+09 | 0.110944E+11 | 0.337766E+10 | 46908.55 | 0.36 |
Minimum of Months | 4398527.02 | 0.00 | 0.00 | 8908.88 | 0.00 | 279228.19 | 892037.99 | 0.00 | 0.35 |
Maximum of Months | 0.135852E+09 | 0.442786E+09 | 404898.01 | 9358933.98 | 85901928.37 | 0.257586E+10 | 0.795791E+09 | 15404.60 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.154911E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.324808E+11 | 0.00 | 0.00 | 0.63 |
February | 0.199749E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196411E+11 | 0.00 | 0.00 | 0.63 |
March | 0.306072E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191387E+10 | 0.00 | 0.00 | 0.63 |
April | 0.279293E+11 | 0.00 | 0.00 | 0.00 | 0.303687E+09 | 0.293567E+09 | 0.00 | 0.00 | 0.63 |
May | 0.262892E+11 | 0.00 | 0.00 | 0.00 | 0.367920E+09 | 0.00 | 0.00 | 0.00 | 0.63 |
June | 0.153977E+11 | 0.453433E+09 | 0.00 | 551097.90 | 0.297088E+10 | 0.00 | 0.182565E+09 | 0.00 | 0.64 |
July | 0.899258E+10 | 0.887326E+09 | 0.00 | 269040.75 | 0.466760E+10 | 0.00 | 0.294186E+09 | 0.00 | 0.64 |
August | 0.125954E+11 | 0.499812E+09 | 0.00 | 104145.34 | 0.446705E+10 | 0.00 | 0.128522E+09 | 0.00 | 0.64 |
September | 0.233396E+11 | 5237497.22 | 0.00 | 117076.83 | 0.322024E+09 | 0.00 | 0.192150E+09 | 0.00 | 0.64 |
October | 0.331108E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.63 |
November | 0.267677E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.709410E+10 | 0.00 | 0.00 | 0.63 |
December | 0.218979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143461E+11 | 0.00 | 0.00 | 0.63 |
Annual Sum or Average | 0.262393E+12 | 0.184581E+10 | 0.00 | 1041360.81 | 0.130992E+11 | 0.757696E+11 | 0.797423E+09 | 0.00 | 0.63 |
Minimum of Months | 0.899258E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.63 |
Maximum of Months | 0.331108E+11 | 0.887326E+09 | 0.00 | 551097.90 | 0.466760E+10 | 0.324808E+11 | 0.294186E+09 | 0.00 | 0.64 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 5025880.30 | 0.00 | 0.00 | 22150.67 | 0.00 | 0.639089E+09 | 1228997.55 | 0.00 | 0.35 |
February | 8212420.72 | 0.00 | 0.00 | 148749.09 | 0.00 | 0.529710E+09 | 11345962.67 | 0.00 | 0.35 |
March | 16303546.23 | 0.00 | 0.00 | 496477.23 | 0.00 | 0.321341E+09 | 51804120.07 | 0.00 | 0.36 |
April | 11074585.58 | 6239997.71 | 0.00 | 1483106.62 | 0.00 | 0.192438E+09 | 0.119837E+09 | 0.00 | 0.35 |
May | 4131656.17 | 7803215.94 | 228.41 | 2806822.33 | 0.00 | 44525434.38 | 0.200286E+09 | 752.04 | 0.36 |
June | 2601810.14 | 79806857.85 | 23828.19 | 1997025.28 | 0.00 | 22655484.06 | 93794031.58 | 3163.99 | 0.36 |
July | 407003.54 | 0.132189E+09 | 40932.26 | 1481365.22 | 0.00 | 96152.60 | 49756146.03 | 8246.41 | 0.36 |
August | 0.00 | 93792370.82 | 86578.81 | 1937428.37 | 0.00 | 120514.55 | 83441240.68 | 6170.94 | 0.36 |
September | 5579428.08 | 15713339.94 | 6538.42 | 2102240.15 | 0.00 | 76003247.32 | 0.139053E+09 | 1705.39 | 0.36 |
October | 16154877.65 | 0.00 | 0.00 | 1087820.51 | 0.00 | 0.229999E+09 | 0.113433E+09 | 0.00 | 0.35 |
November | 12806227.81 | 0.00 | 0.00 | 220206.72 | 0.00 | 0.363874E+09 | 32187208.31 | 0.00 | 0.36 |
December | 9243271.09 | 0.00 | 0.00 | 35906.33 | 0.00 | 0.432069E+09 | 1480471.67 | 0.00 | 0.35 |
Annual Sum or Average | 91540707.31 | 0.335545E+09 | 158106.09 | 13819298.51 | 0.00 | 0.285192E+10 | 0.897647E+09 | 20038.77 | 0.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 22150.67 | 0.00 | 96152.60 | 1228997.55 | 0.00 | 0.35 |
Maximum of Months | 16303546.23 | 0.132189E+09 | 86578.81 | 2806822.33 | 0.00 | 0.639089E+09 | 0.200286E+09 | 8246.41 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 476800.00 | 0.00 | 0.00 | 1254.06 | 0.00 | 0.644783E+09 | 29387.73 | 0.00 | 0.35 |
February | 3430104.42 | 0.00 | 0.00 | 46757.47 | 0.00 | 0.540357E+09 | 5519544.65 | 0.00 | 0.35 |
March | 14922158.86 | 0.00 | 0.00 | 235212.07 | 0.00 | 0.347522E+09 | 27219680.98 | 0.00 | 0.36 |
April | 25033601.48 | 5742494.94 | 4416.35 | 1000234.21 | 491044.76 | 0.204385E+09 | 94375565.40 | 1310.55 | 0.36 |
May | 36347962.27 | 6034340.51 | 5475.69 | 2154333.49 | 1762658.63 | 41089703.45 | 0.172129E+09 | 807.17 | 0.36 |
June | 21881254.74 | 70586167.79 | 63179.66 | 1474661.56 | 9172077.39 | 23149695.41 | 74528556.77 | 3071.49 | 0.36 |
July | 19714778.64 | 0.109629E+09 | 56771.76 | 1138025.25 | 22532386.71 | 51667.29 | 30830134.03 | 4437.26 | 0.36 |
August | 27446218.63 | 78629582.61 | 102377.87 | 1389936.20 | 15133970.46 | 119661.37 | 56533349.91 | 8189.62 | 0.36 |
September | 33099503.65 | 14219426.76 | 6099.32 | 1312786.03 | 1490633.39 | 82521006.18 | 0.105779E+09 | 3582.27 | 0.36 |
October | 26948410.60 | 0.00 | 0.00 | 512471.50 | 0.00 | 0.261970E+09 | 71201117.15 | 0.00 | 0.35 |
November | 11756615.06 | 0.00 | 0.00 | 102287.31 | 0.00 | 0.385203E+09 | 11978334.14 | 0.00 | 0.35 |
December | 959189.66 | 0.00 | 0.00 | 2167.39 | 0.00 | 0.441737E+09 | 79012.83 | 0.00 | 0.35 |
Annual Sum or Average | 0.222017E+09 | 0.284841E+09 | 238320.65 | 9370126.53 | 50582771.34 | 0.297289E+10 | 0.650202E+09 | 21398.37 | 0.36 |
Minimum of Months | 476800.00 | 0.00 | 0.00 | 1254.06 | 0.00 | 51667.29 | 29387.73 | 0.00 | 0.35 |
Maximum of Months | 36347962.27 | 0.109629E+09 | 102377.87 | 2154333.49 | 22532386.71 | 0.644783E+09 | 0.172129E+09 | 8189.62 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 76610559.93 | 0.00 | 0.00 | 1505313.15 | 0.00 | 0.377537E+10 | 0.292665E+09 | 0.00 | 0.40 |
February | 0.126534E+09 | 0.00 | 0.00 | 2817130.82 | 0.00 | 0.298100E+10 | 0.419379E+09 | 0.00 | 0.40 |
March | 48012870.64 | 0.00 | 0.00 | 5320925.66 | 0.00 | 0.162522E+10 | 0.826638E+09 | 0.00 | 0.40 |
April | 46303943.08 | 40088798.77 | 0.00 | 8510335.90 | 0.00 | 0.912540E+09 | 0.111953E+10 | 0.00 | 0.40 |
May | 21840846.94 | 50126635.17 | 7448.74 | 15136724.59 | 0.00 | 88223120.09 | 0.149217E+10 | 3892.61 | 0.40 |
June | 11537296.86 | 0.512062E+09 | 148217.18 | 9819139.60 | 666429.92 | 21440814.80 | 0.734877E+09 | 15396.49 | 0.40 |
July | 2614789.88 | 0.849231E+09 | 305265.67 | 7106573.33 | 0.00 | 761927.06 | 0.321924E+09 | 24826.09 | 0.40 |
August | 0.00 | 0.602882E+09 | 270400.42 | 10154959.39 | 0.00 | 3021445.71 | 0.536112E+09 | 11056.92 | 0.40 |
September | 22440886.54 | 0.100966E+09 | 33261.78 | 14161252.71 | 0.00 | 0.180598E+09 | 0.121378E+10 | 4117.59 | 0.40 |
October | 44650080.15 | 0.00 | 0.00 | 11824978.34 | 0.00 | 0.633739E+09 | 0.162694E+10 | 0.00 | 0.40 |
November | 58847262.63 | 0.00 | 0.00 | 4215912.69 | 0.00 | 0.176975E+10 | 0.795373E+09 | 0.00 | 0.40 |
December | 34000879.28 | 0.00 | 0.00 | 2191089.04 | 0.00 | 0.253593E+10 | 0.272824E+09 | 0.00 | 0.40 |
Annual Sum or Average | 0.493394E+09 | 0.215536E+10 | 764593.80 | 92764335.22 | 666429.92 | 0.145276E+11 | 0.965220E+10 | 59289.69 | 0.40 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 1505313.15 | 0.00 | 761927.06 | 0.272824E+09 | 0.00 | 0.40 |
Maximum of Months | 0.126534E+09 | 0.849231E+09 | 305265.67 | 15136724.59 | 666429.92 | 0.377537E+10 | 0.162694E+10 | 24826.09 | 0.40 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.275107E+11 | 0.00 | 0.00 | 22601147.32 | 0.00 | 0.883155E+10 | 0.305841E+11 | 0.00 | 4.16 |
February | 0.118333E+11 | 0.00 | 0.00 | 27965541.12 | 0.00 | 0.170577E+11 | 0.273926E+11 | 0.00 | 4.27 |
March | 0.572125E+10 | 0.00 | 0.00 | 48214929.10 | 0.00 | 0.00 | 0.433476E+11 | 0.00 | 4.51 |
April | 0.145532E+10 | 0.451553E+09 | 0.00 | 61239561.55 | 2878583.77 | 0.00 | 0.439150E+11 | 0.00 | 4.78 |
May | 0.145083E+09 | 0.571058E+09 | 0.00 | 85005877.60 | 0.00 | 0.00 | 0.463945E+11 | 0.00 | 5.17 |
June | 14038833.00 | 0.589076E+10 | 0.00 | 70652960.94 | 0.00 | 0.00 | 0.289034E+11 | 0.00 | 5.50 |
July | 0.00 | 0.100371E+11 | 0.00 | 61884449.14 | 0.00 | 0.00 | 0.181298E+11 | 0.00 | 5.58 |
August | 7033248.32 | 0.876622E+10 | 0.00 | 71133107.46 | 332734.78 | 0.00 | 0.249136E+11 | 0.00 | 5.51 |
September | 0.228586E+09 | 0.504896E+09 | 0.00 | 81155397.49 | 170741.89 | 0.00 | 0.409689E+11 | 0.00 | 5.16 |
October | 0.125604E+10 | 0.00 | 0.00 | 60991824.74 | 0.00 | 0.00 | 0.512574E+11 | 0.00 | 4.71 |
November | 0.982304E+10 | 0.00 | 0.00 | 42467086.17 | 0.00 | 0.459759E+09 | 0.403713E+11 | 0.00 | 4.47 |
December | 0.164883E+11 | 0.00 | 0.00 | 31052119.34 | 0.00 | 0.00 | 0.348663E+11 | 0.00 | 4.20 |
Annual Sum or Average | 0.744827E+11 | 0.262216E+11 | 0.00 | 0.664364E+09 | 3382060.44 | 0.263491E+11 | 0.431045E+12 | 0.00 | 4.84 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 22601147.32 | 0.00 | 0.00 | 0.181298E+11 | 0.00 | 4.16 |
Maximum of Months | 0.275107E+11 | 0.100371E+11 | 0.00 | 85005877.60 | 2878583.77 | 0.170577E+11 | 0.512574E+11 | 0.00 | 5.58 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.250253E+11 | 0.00 | 0.00 | 31617943.25 | 0.00 | 0.894532E+10 | 0.372301E+11 | 0.00 | 4.45 |
February | 0.785821E+10 | 0.00 | 0.00 | 38481356.89 | 0.00 | 0.175673E+11 | 0.349314E+11 | 0.00 | 4.62 |
March | 0.191089E+10 | 0.00 | 0.00 | 63066603.73 | 0.00 | 0.00 | 0.518152E+11 | 0.00 | 4.93 |
April | 0.347454E+09 | 0.494996E+09 | 0.00 | 74913588.16 | 0.00 | 0.00 | 0.492561E+11 | 0.00 | 5.23 |
May | 5692387.15 | 0.621674E+09 | 0.00 | 96921266.30 | 0.00 | 0.00 | 0.505512E+11 | 0.00 | 5.63 |
June | 0.00 | 0.633080E+10 | 0.00 | 78257948.01 | 0.00 | 0.00 | 0.311010E+11 | 0.00 | 5.91 |
July | 0.00 | 0.107524E+11 | 0.00 | 67384134.71 | 0.00 | 0.00 | 0.193031E+11 | 0.00 | 5.96 |
August | 0.00 | 0.940910E+10 | 0.00 | 78156433.30 | 0.00 | 0.00 | 0.265392E+11 | 0.00 | 5.90 |
September | 6973223.23 | 0.544376E+09 | 0.00 | 92226921.55 | 0.00 | 0.00 | 0.445608E+11 | 0.00 | 5.58 |
October | 0.328534E+09 | 0.00 | 0.00 | 75639642.66 | 0.00 | 0.00 | 0.572754E+11 | 0.00 | 5.17 |
November | 0.647366E+10 | 0.00 | 0.00 | 55679095.86 | 0.00 | 0.404029E+09 | 0.481783E+11 | 0.00 | 4.87 |
December | 0.103640E+11 | 0.00 | 0.00 | 42805316.97 | 0.00 | 0.00 | 0.451036E+11 | 0.00 | 4.55 |
Annual Sum or Average | 0.523207E+11 | 0.281534E+11 | 0.00 | 0.795150E+09 | 0.00 | 0.269167E+11 | 0.495846E+12 | 0.00 | 5.24 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 31617943.25 | 0.00 | 0.00 | 0.193031E+11 | 0.00 | 4.45 |
Maximum of Months | 0.250253E+11 | 0.107524E+11 | 0.00 | 96921266.30 | 0.00 | 0.175673E+11 | 0.572754E+11 | 0.00 | 5.96 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.467089E+10 | 0.00 | 0.00 | 99276041.64 | 0.00 | 0.891009E+10 | 0.815363E+11 | 0.00 | 19.98 |
February | 0.479445E+10 | 0.00 | 0.00 | 88682142.27 | 0.00 | 0.118110E+11 | 0.617240E+11 | 0.00 | 20.58 |
March | 0.00 | 0.00 | 0.00 | 0.114460E+09 | 0.00 | 0.00 | 0.748343E+11 | 0.00 | 22.30 |
April | 0.00 | 0.874451E+09 | 0.00 | 0.114335E+09 | 0.00 | 0.00 | 0.658619E+11 | 0.00 | 22.81 |
May | 0.00 | 0.105910E+10 | 0.00 | 0.134392E+09 | 0.00 | 0.00 | 0.607258E+11 | 0.00 | 23.61 |
June | 0.00 | 0.957176E+10 | 0.00 | 0.100675E+09 | 0.00 | 0.00 | 0.347374E+11 | 0.00 | 23.92 |
July | 0.00 | 0.152261E+11 | 0.00 | 83817643.72 | 0.00 | 0.00 | 0.193232E+11 | 0.00 | 24.03 |
August | 0.00 | 0.136189E+11 | 0.00 | 98825849.04 | 0.00 | 0.00 | 0.269175E+11 | 0.00 | 23.95 |
September | 0.00 | 0.937422E+09 | 0.00 | 0.129439E+09 | 0.00 | 0.00 | 0.540288E+11 | 0.00 | 23.48 |
October | 0.00 | 0.00 | 0.00 | 0.118030E+09 | 0.00 | 0.00 | 0.778195E+11 | 0.00 | 22.74 |
November | 0.704957E+09 | 0.00 | 0.00 | 0.106806E+09 | 0.00 | 0.147668E+10 | 0.732636E+11 | 0.00 | 21.76 |
December | 26649795.30 | 0.00 | 0.00 | 0.109581E+09 | 0.00 | 0.00 | 0.794703E+11 | 0.00 | 20.93 |
Annual Sum or Average | 0.101969E+11 | 0.412878E+11 | 0.00 | 0.129832E+10 | 0.00 | 0.221978E+11 | 0.710242E+12 | 0.00 | 22.52 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 83817643.72 | 0.00 | 0.00 | 0.193232E+11 | 0.00 | 19.98 |
Maximum of Months | 0.479445E+10 | 0.152261E+11 | 0.00 | 0.134392E+09 | 0.00 | 0.118110E+11 | 0.815363E+11 | 0.00 | 24.03 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.337223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202038E+11 | 0.00 | 0.00 | 1.16 |
February | 0.771243E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117570E+11 | 0.00 | 0.00 | 1.16 |
March | 0.132539E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272871E+10 | 0.00 | 0.00 | 1.17 |
April | 0.135985E+11 | 62614390.44 | 0.00 | 29864.66 | 86633797.15 | 0.221875E+09 | 49827052.73 | 0.00 | 1.17 |
May | 0.128472E+11 | 77031349.48 | 0.00 | 89675.02 | 0.105006E+09 | 0.00 | 72673759.83 | 0.00 | 1.18 |
June | 0.710838E+10 | 0.141495E+10 | 0.00 | 1047643.11 | 0.377332E+09 | 0.00 | 0.549008E+09 | 0.00 | 1.21 |
July | 0.389657E+10 | 0.219551E+10 | 0.00 | 1402284.27 | 0.659784E+09 | 0.00 | 0.667511E+09 | 0.00 | 1.21 |
August | 0.559630E+10 | 0.166719E+10 | 0.00 | 1518467.32 | 0.851672E+09 | 0.00 | 0.656168E+09 | 0.00 | 1.20 |
September | 0.111402E+11 | 0.149558E+09 | 0.00 | 1381859.71 | 23644178.91 | 0.00 | 0.424595E+09 | 0.00 | 1.19 |
October | 0.162725E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 |
November | 0.114901E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.515142E+10 | 0.00 | 0.00 | 1.17 |
December | 0.637251E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114398E+11 | 0.00 | 0.00 | 1.16 |
Annual Sum or Average | 0.112661E+12 | 0.556686E+10 | 0.00 | 5469794.08 | 0.210407E+10 | 0.515026E+11 | 0.241978E+10 | 0.00 | 1.18 |
Minimum of Months | 0.337223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.16 |
Maximum of Months | 0.162725E+11 | 0.219551E+10 | 0.00 | 1518467.32 | 0.851672E+09 | 0.202038E+11 | 0.667511E+09 | 0.00 | 1.21 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:24:56
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.219356E+12 | 0.139820E+11 | 0.387739E+12 | 0.151824E+13 | 0.156600E+12 |
February | 0.245466E+12 | 0.108031E+11 | 0.302359E+12 | 0.119674E+13 | 0.120260E+12 |
March | 0.410957E+12 | 0.934939E+10 | 0.265490E+12 | 0.109841E+13 | 0.100879E+12 |
April | 0.482111E+12 | 0.657825E+10 | 0.185196E+12 | 0.780787E+12 | 0.169532E+12 |
May | 0.550290E+12 | 0.395215E+10 | 0.107156E+12 | 0.474989E+12 | 0.292518E+12 |
June | 0.573795E+12 | 0.945340E+09 | 0.276752E+11 | 0.141121E+12 | 0.640377E+12 |
July | 0.556944E+12 | -456373568.2 | -0.107694E+11 | -0.205324E+11 | 0.857906E+12 |
August | 0.502907E+12 | 0.211558E+09 | 0.565372E+10 | 0.606161E+11 | 0.758390E+12 |
September | 0.346703E+12 | 0.354262E+10 | 0.971886E+11 | 0.443110E+12 | 0.371792E+12 |
October | 0.257500E+12 | 0.664221E+10 | 0.188646E+12 | 0.818980E+12 | 0.131722E+12 |
November | 0.159398E+12 | 0.904106E+10 | 0.260894E+12 | 0.106564E+13 | 0.105646E+12 |
December | 0.114576E+12 | 0.123822E+11 | 0.347850E+12 | 0.140317E+13 | 0.116272E+12 |
Annual Sum or Average | 0.442000E+13 | 0.769735E+11 | 0.216508E+13 | 0.898127E+13 | 0.382189E+13 |