Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21

Tabular Output Report in Format: HTML

Building: HotelLarge

Environment: RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904

Simulation Timestamp: 2024-07-03 12:21:51


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:51

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 10038.27 884.80 884.80
Net Site Energy 10038.27 884.80 884.80
Total Source Energy 21021.05 1852.84 1852.84
Net Source Energy 21021.05 1852.84 1852.84


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 11345.29
Net Conditioned Building Area 11345.29
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 902.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 664.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 783.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 193.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1658.18 1788.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 813.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 520.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 75.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 94.78 2478.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9857.19
Refrigeration 62.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 4867.77 5170.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9857.19
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 902.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 664.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 783.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 193.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 872.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Cooking 762.04 1198.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInFreezer 14.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInRefrigerator 8.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Laundry 0.00 590.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 21.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 789.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 2.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 520.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 75.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 94.78 2478.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5742.51
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4114.69
Refrigeration General 7.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  LowTempRefrigeration 20.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MedTempRefrigeration 34.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 0.00 902.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 664.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 783.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 193.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 1658.18 1788.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 813.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 520.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 75.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 94.78 2478.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9857.19
Refrigeration Unassigned 62.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 86.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 119.54 298.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87
Other 223.38 157.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 429.06 455.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 86.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 119.54 298.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87
Other 223.38 157.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 429.06 455.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 4867.769 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 4867.769 100.00
     
Total On-Site and Utility Electric Sources 4867.769 100.00
Total Electricity End Uses 4867.769 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 9857.19 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 9857.19 100.00
Total Water End Uses 9857.19 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 0.00
Time Setpoint Not Met During Occupied Cooling 56.00
Time Not Comfortable Based on Simple ASHRAE 55-2004 7296.17


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

ZoneCoolingSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

ZoneHeatingSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

ZoneElectricSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

SpaceGainsMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

PeakSpaceGainsMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

SpaceGainComponentsAtCoolingPeakMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

ComfortReportSimple55Monthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

OccupantComfortDataSummaryMonthly

| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |

ChillerReportMonthly

| COOLSYS1 CHILLER1 |

BoilerReportMonthly

| HEATSYS1 BOILER |

DXReportMonthly

| FLR_3_DOAS COOLING COIL | VAV WITH REHEAT COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |

WindowReportMonthly

| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |

WindowEnergyReportMonthly

| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |

WindowZoneSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

WindowEnergyZoneSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWH LAUNDRY G WATER HEATER | SWH BOOSTER E WATER HEATER | SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |

CoilReportMonthly

| FLR_3_DOAS HEATING COIL | VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | FLR_3_DOAS COOLING COIL | VAV WITH REHEAT COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |

PlantLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1 | SWHSYS1 |

FanReportMonthly

| FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL_FANCOILFAN | ROOM_2_FLR_3 FAN COIL_FANCOILFAN | ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | ROOM_5_FLR_3 FAN COIL_FANCOILFAN | ROOM_6_FLR_3 FAN COIL_FANCOILFAN | ROOM_1_FLR_6 FAN COIL_FANCOILFAN | ROOM_2_FLR_6 FAN COIL_FANCOILFAN | ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN |

PumpReportMonthly

| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |

CondLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1 | SWHSYS1 |

ZoneTemperatureOscillationReportMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

AirLoopSystemEnergyAndWaterUseMonthly

| FLR_3_DOAS | VAV WITH REHEAT |

AirLoopSystemComponentLoadsMonthly

| FLR_3_DOAS | VAV WITH REHEAT |

AirLoopSystemComponentEnergyUseMonthly

| FLR_3_DOAS | VAV WITH REHEAT |

MechanicalVentilationLoadsMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:51

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21
RunPeriod RUNPERIOD 1
Weather File San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904
Latitude [deg] 32.58
Longitude [deg] -117.0
Elevation [m] 159.00
Time Zone -8.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 4559.59 1873.43 406.47 1873.22 406.47
Above Ground Wall Area [m2] 4025.82 1662.30 350.71 1662.10 350.71
Window Opening Area [m2] 1213.79 432.95 85.85 609.15 85.85
Gross Window-Wall Ratio [%] 26.62 23.11 21.12 32.52 21.12
Above Ground Window-Wall Ratio [%] 30.15 26.05 24.48 36.65 24.48


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 4559.59 1873.43 406.47 1873.22 406.47
Above Ground Wall Area [m2] 4025.82 1662.30 350.71 1662.10 350.71
Window Opening Area [m2] 1213.79 432.95 85.85 609.15 85.85
Gross Window-Wall Ratio [%] 26.62 23.11 21.12 32.52 21.12
Above Ground Window-Wall Ratio [%] 30.15 26.05 24.48 36.65 24.48


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 1978.84
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
BASEMENT 1978.83 Yes Yes 4826.41 1.00 0.00 533.77 0.00 0.00 8.8143 18.58 5.3800
RETAIL_1_FLR_1 67.07 Yes Yes 265.76 1.00 68.84 0.00 23.26 23.26 11.3140 6.19 10.7600
RETAIL_2_FLR_1 77.67 Yes Yes 307.76 1.00 26.57 0.00 0.00 0.00 11.3140 6.19 10.7600
MECH_FLR_1 164.24 Yes Yes 650.80 1.00 62.80 0.00 0.00 0.00 4.6285 61.93 5.3800
STORAGE_FLR_1 94.76 Yes Yes 375.47 1.00 36.23 0.00 0.00 0.00 5.7199 46.45 2.6900
LAUNDRY_FLR_1 78.04 Yes Yes 309.22 1.00 85.75 0.00 0.00 0.00 4.6285 9.29 597.5300
CAFE_FLR_1 188.86 Yes Yes 748.35 1.00 152.17 0.00 65.50 65.50 10.0104 1.33 5.3800
LOBBY_FLR_1 1308.19 Yes Yes 5183.56 1.00 434.79 0.00 85.08 85.08 10.7639 3.10 8.0700
ROOM_1_FLR_3 39.02 Yes Yes 118.94 4.00 39.95 0.00 13.18 13.18 8.2882 26.01 6.7500
ROOM_2_FLR_3 39.02 Yes Yes 118.93 4.00 39.95 0.00 13.18 13.18 8.2882 26.01 6.7500
ROOM_3_MULT19_FLR_3 24.52 Yes Yes 74.75 76.00 11.15 0.00 3.68 3.68 8.2882 16.35 10.5200
ROOM_4_MULT19_FLR_3 24.53 Yes Yes 74.77 76.00 11.15 0.00 3.68 3.68 8.2882 16.35 10.5200
ROOM_5_FLR_3 39.02 Yes Yes 118.94 4.00 39.95 0.00 13.18 13.18 8.2882 26.01 6.7500
ROOM_6_FLR_3 39.02 Yes Yes 118.93 4.00 39.95 0.00 13.18 13.18 8.2882 26.01 6.7500
CORRIDOR_FLR_3 389.40 Yes Yes 1186.91 4.00 48.31 0.00 15.94 15.94 7.1042 18.58 0.0000
ROOM_1_FLR_6 39.02 Yes Yes 118.94 1.00 39.95 0.00 13.18 13.18 8.2882 26.01 6.7500
ROOM_2_FLR_6 39.02 Yes Yes 118.93 1.00 39.95 0.00 13.18 13.18 8.2882 26.01 6.7500
ROOM_3_MULT9_FLR_6 24.53 Yes Yes 74.77 9.00 20.44 0.00 6.74 6.74 8.2882 16.35 10.5200
BANQUET_FLR_6 331.66 Yes Yes 1010.89 1.00 97.55 0.00 32.19 32.19 10.0104 1.33 67.8200
DINING_FLR_6 331.66 Yes Yes 1010.89 1.00 97.55 0.00 32.19 32.19 10.0104 1.33 67.8200
KITCHEN_FLR_6 103.30 Yes Yes 314.87 1.00 87.33 0.00 26.37 26.37 11.4097 4.65 2934.4875
CORRIDOR_FLR_6 412.12 Yes Yes 1256.16 1.00 85.47 0.00 28.20 28.20 7.1042 18.58 0.0000
Total 11345.29     35184.81   4025.82 533.77 1213.79 1213.79 8.5566 7.07 41.0709
Conditioned Total 11345.29     35184.81   4025.82 533.77 1213.79 1213.79 8.5566 7.07 41.0709
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 0.00     0.00   0.00 0.00 0.00 0.00      


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
BASEMENT 1978.83 Yes Yes 1.00 BASEMENT GENERAL BASEMENT 8.8143 18.58 5.3800  
RETAIL_1_FLR_1 67.07 Yes Yes 1.00 RETAIL_1_FLR_1 GENERAL RETAIL_1_FLR_1 11.3140 6.19 10.7600  
RETAIL_2_FLR_1 77.67 Yes Yes 1.00 RETAIL_2_FLR_1 GENERAL RETAIL_2_FLR_1 11.3140 6.19 10.7600  
MECH_FLR_1 164.24 Yes Yes 1.00 MECH_FLR_1 GENERAL MECH_FLR_1 4.6285 61.93 5.3800  
STORAGE_FLR_1 94.76 Yes Yes 1.00 STORAGE_FLR_1 GENERAL STORAGE_FLR_1 5.7199 46.45 2.6900  
LAUNDRY_FLR_1 78.04 Yes Yes 1.00 LAUNDRY_FLR_1 GENERAL LAUNDRY_FLR_1 4.6285 9.29 597.5300  
CAFE_FLR_1 188.86 Yes Yes 1.00 CAFE_FLR_1 GENERAL CAFE_FLR_1 10.0104 1.33 5.3800  
LOBBY_FLR_1 1308.19 Yes Yes 1.00 LOBBY_FLR_1 GENERAL LOBBY_FLR_1 10.7639 3.10 8.0700  
ROOM_1_FLR_3 39.02 Yes Yes 4.00 ROOM_1_FLR_3 GENERAL ROOM_1_FLR_3 8.2882 26.01 6.7500  
ROOM_2_FLR_3 39.02 Yes Yes 4.00 ROOM_2_FLR_3 GENERAL ROOM_2_FLR_3 8.2882 26.01 6.7500  
ROOM_3_MULT19_FLR_3 24.52 Yes Yes 76.00 ROOM_3_MULT19_FLR_3 GENERAL ROOM_3_MULT19_FLR_3 8.2882 16.35 10.5200  
ROOM_4_MULT19_FLR_3 24.53 Yes Yes 76.00 ROOM_4_MULT19_FLR_3 GENERAL ROOM_4_MULT19_FLR_3 8.2882 16.35 10.5200  
ROOM_5_FLR_3 39.02 Yes Yes 4.00 ROOM_5_FLR_3 GENERAL ROOM_5_FLR_3 8.2882 26.01 6.7500  
ROOM_6_FLR_3 39.02 Yes Yes 4.00 ROOM_6_FLR_3 GENERAL ROOM_6_FLR_3 8.2882 26.01 6.7500  
CORRIDOR_FLR_3 389.40 Yes Yes 4.00 CORRIDOR_FLR_3 GENERAL CORRIDOR_FLR_3 7.1042 18.58 0.0000  
ROOM_1_FLR_6 39.02 Yes Yes 1.00 ROOM_1_FLR_6 GENERAL ROOM_1_FLR_6 8.2882 26.01 6.7500  
ROOM_2_FLR_6 39.02 Yes Yes 1.00 ROOM_2_FLR_6 GENERAL ROOM_2_FLR_6 8.2882 26.01 6.7500  
ROOM_3_MULT9_FLR_6 24.53 Yes Yes 9.00 ROOM_3_MULT9_FLR_6 GENERAL ROOM_3_MULT9_FLR_6 8.2882 16.35 10.5200  
BANQUET_FLR_6 331.66 Yes Yes 1.00 BANQUET_FLR_6 GENERAL BANQUET_FLR_6 10.0104 1.33 67.8200  
DINING_FLR_6 331.66 Yes Yes 1.00 DINING_FLR_6 GENERAL DINING_FLR_6 10.0104 1.33 67.8200  
KITCHEN_FLR_6 103.30 Yes Yes 1.00 KITCHEN_FLR_6 GENERAL KITCHEN_FLR_6 11.4097 4.65 2934.4875  
CORRIDOR_FLR_6 412.12 Yes Yes 1.00 CORRIDOR_FLR_6 GENERAL CORRIDOR_FLR_6 7.1042 18.58 0.0000  
Total 11345.29             8.5566 3.54 41.0709  
Conditioned Total 11345.29             8.5566 3.54 41.0709  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 0.00             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 11345.29 11345.29 0.00 0.00 4.6520 8.82 37.1989
Total 11345.29 11345.29 0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:51

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 29-SEP-18:00 29-MAR-17:00 - - - - - - - - - - 05-MAY-20:30
Heating 0.00 141315.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 114713.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 57474.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 12338.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 77573.37 104248.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 28169.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 26461.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 2841.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 4751.09 220447.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 1814.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 326139.69 466011.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 141315.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 114713.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 57474.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 12338.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 47590.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Cooking 29240.64 74976.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInFreezer 457.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInRefrigerator 285.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Laundry 0.00 29272.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 1050.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 26968.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 150.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 26461.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 2841.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 4751.09 220447.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 228.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  LowTempRefrigeration 527.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MedTempRefrigeration 1058.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:51

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 978.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 2105.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 2480.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 614.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 5251.45 1939.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 2577.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 1648.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 240.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 300.18 2687.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 197.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 15416.22 5604.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 86.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 185.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 218.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 54.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 462.88 170.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 227.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 145.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 21.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 26.46 236.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 17.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1358.82 494.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 86.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 185.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 218.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 54.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 462.88 170.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 227.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 145.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 21.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 26.46 236.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 17.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1358.82 494.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:51

AirTerminal:SingleDuct:VAV:Reheat

Design Size Maximum Air Flow Rate [m3/s] Design Size Constant Minimum Air Flow Fraction User-Specified Constant Minimum Air Flow Fraction Design Size Minimum Air Flow Rate [m3/s] Design Size Maximum Flow Fraction during Reheat [] User-Specified Maximum Flow Fraction during Reheat [] Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] Design Size Maximum Reheat Water Flow Rate [m3/s] Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] Design Size Reheat Coil Sizing Inlet Air Temperature [C] Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir]
BASEMENT VAV BOX COMPONENT 2.44 0.619015 0.547000 1.33 1.00 0.500000 0.000615 0.000060 1.33 16.70 0.008000
RETAIL_1_FLR_1 VAV BOX COMPONENT 0.312360 0.163620 0.547000 0.170861 0.547000 0.500000 0.002329 0.000022 0.170861 16.70 0.008000
RETAIL_2_FLR_1 VAV BOX COMPONENT 0.227768 0.259842 0.547000 0.124589 0.692911 0.500000 0.001466 0.000011 0.124589 16.70 0.008000
MECH_FLR_1 VAV BOX COMPONENT 0.181082 0.691141 0.547000 0.099052 1.00 0.500000 0.000551 0.000013 0.099052 16.70 0.008000
STORAGE_FLR_1 VAV BOX COMPONENT 0.106271 0.679459 0.547000 0.058130 1.00 0.500000 0.000561 0.000008 0.058130 16.70 0.008000
LAUNDRY_FLR_1 VAV BOX COMPONENT 3.30 0.018040 0.547000 1.80 0.547000 0.500000 0.021120 0.000093 1.80 16.70 0.008000
CAFE_FLR_1 VAV BOX COMPONENT 1.38 0.104135 0.547000 0.755944 0.547000 0.500000 0.003659 0.000072 0.755944 16.70 0.008000
LOBBY_FLR_1 VAV BOX COMPONENT 4.66 0.213759 0.547000 2.55 0.570024 0.500000 0.001782 0.000203 2.55 16.70 0.008000
CORRIDOR_FLR_3 VAV BOX COMPONENT 1.42 0.833401 0.547000 0.779022 1.00 0.500000 0.000457 0.000088 0.779022 16.70 0.008000
BANQUET_FLR_6 VAV BOX COMPONENT 2.12 0.119240 0.547000 1.16 0.547000 0.500000 0.003195 0.000087 1.16 16.70 0.008000
DINING_FLR_6 VAV BOX COMPONENT 2.22 0.113706 0.547000 1.22 0.547000 0.500000 0.003351 0.000090 1.22 16.70 0.008000
KITCHEN_FLR_6 VAV BOX COMPONENT 2.22 0.063646 0.547000 1.22 0.547000 0.500000 0.010767 0.000059 1.22 16.70 0.008000
CORRIDOR_FLR_6 VAV BOX COMPONENT 0.704597 0.445700 0.547000 0.385415 1.00 0.500000 0.000855 0.000054 0.385415 16.70 0.008000
User-Specified values were used. Design Size values were used if no User-Specified values were provided. Design Size values may be derived from alternate User-Specified values.

Coil:Heating:Water

Design Size Rated Capacity [W] Design Size Maximum Water Flow Rate [m3/s] Design Size U-Factor Times Area Value [W/K]
BASEMENT VAV BOX REHEAT COIL 6904.49 0.000060 143.98
RETAIL_1_FLR_1 VAV BOX REHEAT COIL 2567.64 0.000022 59.46
RETAIL_2_FLR_1 VAV BOX REHEAT COIL 1207.82 0.000011 26.38
MECH_FLR_1 VAV BOX REHEAT COIL 1513.84 0.000013 35.16
STORAGE_FLR_1 VAV BOX REHEAT COIL 971.37 0.000008 22.94
LAUNDRY_FLR_1 VAV BOX REHEAT COIL 10644.59 0.000093 223.59
CAFE_FLR_1 VAV BOX REHEAT COIL 8207.96 0.000072 181.52
LOBBY_FLR_1 VAV BOX REHEAT COIL 23179.43 0.000203 503.11
ROOM_1_FLR_3 FAN COIL HEATING COIL 3704.30 0.000032 105.84
ROOM_2_FLR_3 FAN COIL HEATING COIL 3704.51 0.000032 105.85
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL 21626.49 0.000189 617.91
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL 21641.02 0.000189 618.32
ROOM_5_FLR_3 FAN COIL HEATING COIL 3703.47 0.000032 105.82
ROOM_6_FLR_3 FAN COIL HEATING COIL 3703.68 0.000032 105.82
CORRIDOR_FLR_3 VAV BOX REHEAT COIL 10059.28 0.000088 227.50
ROOM_1_FLR_6 FAN COIL HEATING COIL 1153.43 0.000010 32.96
ROOM_2_FLR_6 FAN COIL HEATING COIL 1152.99 0.000010 32.94
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL 5585.51 0.000049 159.59
BANQUET_FLR_6 VAV BOX REHEAT COIL 9904.56 0.000087 213.76
DINING_FLR_6 VAV BOX REHEAT COIL 10253.90 0.000090 221.04
KITCHEN_FLR_6 VAV BOX REHEAT COIL 6758.61 0.000059 141.47
CORRIDOR_FLR_6 VAV BOX REHEAT COIL 6157.45 0.000054 144.16
FLR_3_DOAS HEATING COIL 9427.25 0.000082 168.97
VAV WITH REHEAT HEATING COIL 97345.61 0.000852 1744.76
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
ROOM_1_FLR_3 DIRECT AIR 0.061735
ROOM_2_FLR_3 DIRECT AIR 0.061728
ROOM_3_MULT19_FLR_3 DIRECT AIR 0.837072
ROOM_4_MULT19_FLR_3 DIRECT AIR 0.837300
ROOM_5_FLR_3 DIRECT AIR 0.061735
ROOM_6_FLR_3 DIRECT AIR 0.061728
ROOM_1_FLR_6 DIRECT AIR 0.015434
ROOM_2_FLR_6 DIRECT AIR 0.015432
ROOM_3_MULT9_FLR_6 DIRECT AIR 0.099154
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

ZoneHVAC:FourPipeFanCoil

Design Size Maximum Supply Air Flow Rate [m3/s] Design Size Maximum Hot Water Flow [m3/s] Design Size Maximum Cold Water Flow [m3/s]
ROOM_1_FLR_3 FAN COIL 0.978062 0.000032 0.000306
ROOM_2_FLR_3 FAN COIL 0.941639 0.000032 0.000295
ROOM_3_MULT19_FLR_3 FAN COIL 6.11 0.000189 0.001874
ROOM_4_MULT19_FLR_3 FAN COIL 5.74 0.000189 0.001881
ROOM_5_FLR_3 FAN COIL 0.869152 0.000032 0.000273
ROOM_6_FLR_3 FAN COIL 0.836813 0.000032 0.000263
ROOM_1_FLR_6 FAN COIL 0.253311 0.000010 0.000079
ROOM_2_FLR_6 FAN COIL 0.243315 0.000010 0.000076
ROOM_3_MULT9_FLR_6 FAN COIL 1.19 0.000049 0.000379
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [m3/s]
ROOM_1_FLR_3 FAN COIL_FANCOILFAN 0.978062
ROOM_2_FLR_3 FAN COIL_FANCOILFAN 0.941639
ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN 6.11
ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN 5.74
ROOM_5_FLR_3 FAN COIL_FANCOILFAN 0.869152
ROOM_6_FLR_3 FAN COIL_FANCOILFAN 0.836813
ROOM_1_FLR_6 FAN COIL_FANCOILFAN 0.253311
ROOM_2_FLR_6 FAN COIL_FANCOILFAN 0.243315
ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN 1.19
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:Water

Design Size Design Inlet Air Temperature [C] Design Size Design Inlet Water Temperature [C] Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Outlet Air Temperature [C] Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Water Flow Rate [m3/s] Design Size Design Air Flow Rate [m3/s] Design Size Design Coil Load [W]
ROOM_1_FLR_3 FAN COIL COOLING COIL 21.69 6.70 0.008574 12.80 0.008500 0.000306 0.978062  
ROOM_2_FLR_3 FAN COIL COOLING COIL 21.69 6.70 0.008576 12.80 0.008500 0.000295 0.941639  
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL 21.69 6.70 0.008498 12.80 0.008498 0.001874 6.11  
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL 21.69 6.70 0.008746 12.80 0.008500 0.001881 5.74  
ROOM_5_FLR_3 FAN COIL COOLING COIL 21.69 6.70 0.008583 12.80 0.008500 0.000273 0.869152  
ROOM_6_FLR_3 FAN COIL COOLING COIL 21.69 6.70 0.008586 12.80 0.008500 0.000263 0.836813  
ROOM_1_FLR_6 FAN COIL COOLING COIL 21.69 6.70 0.008571 12.80 0.008500 0.000079 0.253311  
ROOM_2_FLR_6 FAN COIL COOLING COIL 21.69 6.70 0.008574 12.80 0.008500 0.000076 0.243315  
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL 21.69 6.70 0.008639 12.80 0.008500 0.000379 1.19  
FLR_3_DOAS COOLING COIL 31.30 6.70 0.008233 11.91 0.008233 0.001371 2.05 47946.25
VAV WITH REHEAT COOLING COIL 28.02 6.70 0.008891 10.94 0.008500 0.013188 21.18 461117.25
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
FLR_3_DOAS 2.05 2.05 2.05 2.05 2.05 2.05 0.300000 1.00 2.05
VAV WITH REHEAT 11.65 11.65 21.30 11.65 21.18 21.18 0.300000 0.550063 21.18
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
FLR_3_DOAS_OA_CONTROLLER 2.05 2.05
VAV WITH REHEAT_OA_CONTROLLER 21.18  
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ConstantVolume

User-Specified Maximum Flow Rate [m3/s]
FLR_3_DOAS FAN 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:WaterCoil

Maximum Actuated Flow [m3/s] Controller Convergence Tolerance
FLR_3_DOAS_COOLC_CONTROLLER 0.001371 0.000347
FLR_3_DOAS_HEATC_CONTROLLER 0.000082  
VAV WITH REHEAT_COOLC_CONTROLLER 0.013188 0.000036
VAV WITH REHEAT_HEATC_CONTROLLER 0.000852  
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:VariableVolume

Design Size Maximum Flow Rate [m3/s]
VAV WITH REHEAT FAN 21.18
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W] Design Minimum Flow Rate [m3/s]
COOLSYS1 PUMP SECONDARY 0.019985 3263.02  
HEATSYS1 PUMP 0.002372 714.20 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
HEATSYS1 0.002372 0.284582
COOLSYS1 0.019985 2.40
SWHSYS1 0.000375 0.045004
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Boiler:HotWater

Design Size Nominal Capacity [W] User-Specified Nominal Capacity [W] Design Size Design Water Flow Rate [m3/s]
HEATSYS1 BOILER 271079.21 271079.21 0.002372
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
COOLSYS1 PUMP 0.019985 2259.10
SWHSYS1 PUMP 0.000375 47.91
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Chiller:Electric:EIR

Design Size Reference Chilled Water Flow Rate [m3/s] Design Size Reference Capacity [W] User-Specified Reference Capacity [W] Design Size Reference Condenser Fluid Flow Rate [m3/s]
COOLSYS1 CHILLER1 0.019985 698796.70 699394.26 79.73
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SWHSYS1 WATER HEATER 0.000375
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:51

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
RETAIL_1_FLR_1_CEILING ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH |
CAFE_FLR_1_CEILING ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH |
LOBBY_FLR_1_CEILING_2 ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
RETAIL_1_FLR_1_WALL_SOUTH RETAIL_1_FLR_1_WALL_SOUTH_WINDOW |
RETAIL_2_FLR_1_WALL_WEST RETAIL_2_FLR_1_WALL_WEST_DOOR |
STORAGE_FLR_1_WALL_NORTH STORAGE_FLR_1_WALL_NORTH_ROLLDOOR |
LAUNDRY_FLR_1_WALL_EAST LAUNDRY_FLR_1_WALL_EAST_DOOR |
CAFE_FLR_1_WALL_EAST CAFE_FLR_1_WALL_EAST_DOOR |
CAFE_FLR_1_WALL_SOUTH CAFE_FLR_1_WALL_SOUTH_WINDOW |
LOBBY_FLR_1_WALL_1_NORTH LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 |
LOBBY_FLR_1_WALL_1_SOUTH LOBBY_FLR_1_WALL_SOUTH_WINDOW |
ROOM_1_FLR_3_WALL_SOUTH ROOM_1_FLR_3_WALL_SOUTH_WINDOW |
ROOM_1_FLR_3_WALL_WEST ROOM_1_FLR_3_WALL_WEST_WINDOW |
ROOM_2_FLR_3_WALL_NORTH ROOM_2_FLR_3_WALL_NORTH_WINDOW |
ROOM_2_FLR_3_WALL_WEST ROOM_2_FLR_3_WALL_WEST_WINDOW |
ROOM_3_MULT19_FLR_3_WALL_SOUTH ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW |
ROOM_4_MULT19_FLR_3_WALL_NORTH ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW |
ROOM_5_FLR_3_WALL_EAST ROOM_5_FLR_3_WALL_EAST_WINDOW |
ROOM_5_FLR_3_WALL_SOUTH ROOM_5_FLR_3_WALL_SOUTH_WINDOW |
ROOM_6_FLR_3_WALL_NORTH ROOM_6_FLR_3_WALL_NORTH_WINDOW |
ROOM_6_FLR_3_WALL_EAST ROOM_6_FLR_3_WALL_EAST_WINDOW |
CORRIDOR_FLR_3_WALL_1_NORTH CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW |
CORRIDOR_FLR_3_WALL_2_NORTH CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW |
CORRIDOR_FLR_3_WALL_1_SOUTH CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW |
CORRIDOR_FLR_3_WALL_2_SOUTH CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW |
ROOM_1_FLR_6_WALL_SOUTH ROOM_1_FLR_6_WALL_SOUTH_WINDOW |
ROOM_1_FLR_6_WALL_WEST ROOM_1_FLR_6_WALL_WEST_WINDOW |
ROOM_2_FLR_6_WALL_NORTH ROOM_2_FLR_6_WALL_NORTH_WINDOW |
ROOM_2_FLR_6_WALL_WEST ROOM_2_FLR_6_WALL_WEST_WINDOW |
ROOM_3_MULT9_FLR_6_WALL_SOUTH ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW |
BANQUET_FLR_6_WALL_NORTH BANQUET_FLR_6_WALL_NORTH_WINDOW |
DINING_FLR_6_WALL_NORTH DINING_FLR_6_WALL_NORTH_WINDOW |
KITCHEN_FLR_6_WALL_NORTH KITCHEN_FLR_6_WALL_NORTH_WINDOW |
KITCHEN_FLR_6_WALL_EAST KITCHEN_FLR_6_WALL_EAST_WINDOW |
KITCHEN_FLR_6_WALL_1_SOUTH KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW |
CORRIDOR_FLR_6_WALL_1_NORTH CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW |
CORRIDOR_FLR_6_WALL_2_NORTH CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW |
CORRIDOR_FLR_6_WALL_2_SOUTH CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:51

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:51

Version

Version ID
1 22.1


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.80 14.30 13.60 13.20 13.30 12.60 15.30 15.60 17.70 19.40 19.70 18.50


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 32.58 -116.98 -8.00 159.00 99429 1.1818


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 16.00 7.10 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 HotelLarge 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 DOE-2


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 22 235 36


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 BASEMENT 0.0 0.00 0.00 0.00 41.45 11.51 -1.22 1 1 1 0.00 86.56 0.00 22.86 -2.44 0.00 2.44 4826.41 TARP DOE-2 1978.83 0.00 0.00 0.00 13 0 0 Yes
2 RETAIL_1_FLR_1 0.0 0.00 0.00 0.00 5.79 2.90 1.98 1 1 1 0.00 11.58 0.00 5.79 0.00 3.96 3.96 265.76 TARP DOE-2 67.07 68.84 45.58 23.26 6 1 0 Yes
3 RETAIL_2_FLR_1 0.0 0.00 0.00 0.00 5.79 9.14 1.98 1 1 1 0.00 11.58 5.79 12.50 0.00 3.96 3.96 307.76 TARP DOE-2 77.67 26.57 24.62 0.00 6 1 0 Yes
4 MECH_FLR_1 0.0 0.00 0.00 0.00 61.87 17.68 1.98 1 1 1 53.95 69.80 12.50 22.86 0.00 3.96 3.96 650.80 TARP DOE-2 164.24 62.80 62.80 0.00 6 0 0 Yes
5 STORAGE_FLR_1 0.0 0.00 0.00 0.00 74.37 17.68 1.98 1 1 1 69.80 78.94 12.50 22.86 0.00 3.96 3.96 375.47 TARP DOE-2 94.76 36.23 28.80 0.00 6 1 0 Yes
6 LAUNDRY_FLR_1 0.0 0.00 0.00 0.00 84.28 14.33 1.98 1 1 1 81.99 86.56 5.79 22.86 0.00 3.96 3.96 309.22 TARP DOE-2 78.04 85.75 83.80 0.00 6 1 0 Yes
7 CAFE_FLR_1 0.0 0.00 0.00 0.00 70.26 2.90 1.98 1 1 1 53.95 86.56 0.00 5.79 0.00 3.96 3.96 748.35 TARP DOE-2 188.86 152.17 84.72 65.50 7 2 0 Yes
8 LOBBY_FLR_1 0.0 0.00 0.00 0.00 38.29 12.45 1.98 1 1 1 0.00 81.99 0.00 22.86 0.00 3.96 3.96 5183.56 TARP DOE-2 1308.19 434.79 345.80 85.08 18 3 0 Yes
9 ROOM_1_FLR_3 0.0 0.00 0.00 0.00 2.29 10.06 8.53 1 4 1 0.00 4.57 5.79 14.33 7.01 10.06 3.05 118.94 TARP DOE-2 39.02 39.95 26.77 13.18 6 2 0 Yes
10 ROOM_2_FLR_3 0.0 0.00 0.00 0.00 2.29 18.59 8.53 1 4 1 0.00 4.57 14.33 22.86 7.01 10.06 3.05 118.93 TARP DOE-2 39.02 39.95 26.76 13.18 6 2 0 Yes
11 ROOM_3_MULT19_FLR_3 0.0 0.00 0.00 0.00 8.53 9.14 8.53 1 76 1 6.71 10.36 5.79 12.50 7.01 10.06 3.05 74.75 TARP DOE-2 24.52 11.15 7.47 3.68 6 1 0 Yes
12 ROOM_4_MULT19_FLR_3 0.0 0.00 0.00 0.00 12.19 19.51 8.53 1 76 1 10.36 14.02 16.15 22.86 7.01 10.06 3.05 74.77 TARP DOE-2 24.53 11.15 7.47 3.68 6 1 0 Yes
13 ROOM_5_FLR_3 0.0 0.00 0.00 0.00 84.28 10.06 8.53 1 4 1 81.99 86.56 5.79 14.33 7.01 10.06 3.05 118.94 TARP DOE-2 39.02 39.95 26.77 13.18 6 2 0 Yes
14 ROOM_6_FLR_3 0.0 0.00 0.00 0.00 84.28 18.59 8.53 1 4 1 81.99 86.56 14.33 22.86 7.01 10.06 3.05 118.93 TARP DOE-2 39.02 39.95 26.76 13.18 6 2 0 Yes
15 CORRIDOR_FLR_3 0.0 0.00 0.00 0.00 43.28 14.33 8.53 1 4 1 4.57 81.99 5.79 22.86 7.01 10.06 3.05 1186.91 TARP DOE-2 389.40 48.31 32.37 15.94 20 4 0 Yes
16 ROOM_1_FLR_6 0.0 0.00 0.00 0.00 2.29 10.06 17.68 1 1 1 0.00 4.57 5.79 14.33 16.15 19.20 3.05 118.94 TARP DOE-2 39.02 39.95 26.77 13.18 6 2 0 Yes
17 ROOM_2_FLR_6 0.0 0.00 0.00 0.00 2.29 18.59 17.68 1 1 1 0.00 4.57 14.33 22.86 16.15 19.20 3.05 118.93 TARP DOE-2 39.02 39.95 26.76 13.18 6 2 0 Yes
18 ROOM_3_MULT9_FLR_6 0.0 0.00 0.00 0.00 7.93 7.62 17.68 1 9 1 4.57 11.28 5.79 9.45 16.15 19.20 3.05 74.77 TARP DOE-2 24.53 20.44 13.70 6.74 6 1 0 Yes
19 BANQUET_FLR_6 0.0 0.00 0.00 0.00 26.37 17.68 17.68 1 1 1 10.36 42.37 12.50 22.86 16.15 19.20 3.05 1010.89 TARP DOE-2 331.66 97.55 65.36 32.19 6 1 0 Yes
20 DINING_FLR_6 0.0 0.00 0.00 0.00 63.55 17.68 17.68 1 1 1 47.55 79.55 12.50 22.86 16.15 19.20 3.05 1010.89 TARP DOE-2 331.66 97.55 65.36 32.19 6 1 0 Yes
21 KITCHEN_FLR_6 0.0 0.00 0.00 0.00 82.99 14.11 17.68 1 1 1 79.55 86.56 5.79 22.86 16.15 19.20 3.05 314.87 TARP DOE-2 103.30 87.33 60.96 26.37 8 3 0 Yes
22 CORRIDOR_FLR_6 0.0 0.00 0.00 0.00 41.51 13.35 17.68 1 1 1 4.57 81.99 5.79 22.86 16.15 19.20 3.05 1256.16 TARP DOE-2 412.12 85.47 57.27 28.20 15 3 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 BASEMENT 1978.83 106.5 18.581 5.382E-002 8.814 5.380 0.000 0.000 0.000 0.000 14.194 No
2 RETAIL_1_FLR_1 67.07 10.8 6.194 0.161 11.314 10.760 0.000 0.000 0.000 0.000 22.074 No
3 RETAIL_2_FLR_1 77.67 12.5 6.194 0.161 11.314 10.760 0.000 0.000 0.000 0.000 22.074 No
4 MECH_FLR_1 164.24 2.7 61.932 1.615E-002 4.628 5.380 0.000 0.000 0.000 0.000 10.008 No
5 STORAGE_FLR_1 94.76 2.0 46.451 2.153E-002 5.720 2.690 0.000 0.000 0.000 0.000 8.410 No
6 LAUNDRY_FLR_1 78.04 8.4 9.290 0.108 4.628 61.680 535.850 0.000 0.000 0.000 602.158 No
7 CAFE_FLR_1 188.86 142.3 1.327 0.753 10.010 5.380 0.000 0.000 0.000 0.000 15.390 No
8 LOBBY_FLR_1 1308.19 422.4 3.097 0.323 10.764 8.070 0.000 0.000 0.000 0.000 18.834 No
9 ROOM_1_FLR_3 39.02 1.5 26.015 3.844E-002 8.288 6.750 0.000 0.000 0.000 0.000 15.038 No
10 ROOM_2_FLR_3 39.02 1.5 26.012 3.844E-002 8.288 6.750 0.000 0.000 0.000 0.000 15.038 No
11 ROOM_3_MULT19_FLR_3 24.52 1.5 16.349 6.116E-002 8.288 10.520 0.000 0.000 0.000 0.000 18.808 No
12 ROOM_4_MULT19_FLR_3 24.53 1.5 16.354 6.115E-002 8.288 10.520 0.000 0.000 0.000 0.000 18.808 No
13 ROOM_5_FLR_3 39.02 1.5 26.015 3.844E-002 8.288 6.750 0.000 0.000 0.000 0.000 15.038 No
14 ROOM_6_FLR_3 39.02 1.5 26.012 3.844E-002 8.288 6.750 0.000 0.000 0.000 0.000 15.038 No
15 CORRIDOR_FLR_3 389.40 21.0 18.581 5.382E-002 7.104 0.000 0.000 0.000 0.000 0.000 7.104 No
16 ROOM_1_FLR_6 39.02 1.5 26.015 3.844E-002 8.288 6.750 0.000 0.000 0.000 0.000 15.038 No
17 ROOM_2_FLR_6 39.02 1.5 26.012 3.844E-002 8.288 6.750 0.000 0.000 0.000 0.000 15.038 No
18 ROOM_3_MULT9_FLR_6 24.53 1.5 16.354 6.115E-002 8.288 10.520 0.000 0.000 0.000 0.000 18.808 No
19 BANQUET_FLR_6 331.66 249.9 1.327 0.753 10.010 67.820 0.000 0.000 0.000 0.000 77.830 No
20 DINING_FLR_6 331.66 249.9 1.327 0.753 10.010 67.820 0.000 0.000 0.000 0.000 77.830 No
21 KITCHEN_FLR_6 103.30 22.2 4.645 0.215 11.410 515.227 2419.260 0.000 0.000 0.000 2945.897 No
22 CORRIDOR_FLR_6 412.12 22.2 18.581 5.382E-002 7.104 0.000 0.000 0.000 0.000 0.000 7.104 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People MRT Calculation Type Work Efficiency Clothing Insulation Calculation Method Clothing Insulation Calculation Method Schedule Clothing Air Velocity Fanger Calculation Pierce Calculation KSU Calculation Cooling Effect Calculation Ankle Draft Calculation
1 BASEMENT PEOPLE BLDG_OCC_SCH BASEMENT 1978.83 106.5 106.5 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 106 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
2 RETAIL_1_FLR_1 PEOPLE BLDG_OCC_SCH RETAIL_1_FLR_1 67.07 10.8 10.8 0.161 6.194 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
3 RETAIL_2_FLR_1 PEOPLE BLDG_OCC_SCH RETAIL_2_FLR_1 77.67 12.5 12.5 0.161 6.194 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 13 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
4 LAUNDRY_FLR_1 PEOPLE BLDG_OCC_SCH LAUNDRY_FLR_1 78.04 8.4 8.4 0.108 9.290 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 8 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
5 CAFE_FLR_1 PEOPLE BLDG_OCC_SCH CAFE_FLR_1 188.86 142.3 142.3 0.753 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 142 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
6 LOBBY_FLR_1 PEOPLE BLDG_OCC_SCH LOBBY_FLR_1 1308.19 422.4 422.4 0.323 3.097 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 422 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
7 ROOM_1_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_1_FLR_3 39.02 1.5 1.5 3.844E-002 26.015 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
8 ROOM_2_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_2_FLR_3 39.02 1.5 1.5 3.844E-002 26.012 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
9 ROOM_3_MULT19_FLR_3 PEOPLE ALWAYS_OFF ROOM_3_MULT19_FLR_3 24.52 1.5 1.5 6.116E-002 16.349 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
10 ROOM_4_MULT19_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_4_MULT19_FLR_3 24.53 1.5 1.5 6.115E-002 16.354 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
11 ROOM_5_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_5_FLR_3 39.02 1.5 1.5 3.844E-002 26.015 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
12 ROOM_6_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_6_FLR_3 39.02 1.5 1.5 3.844E-002 26.012 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
13 ROOM_1_FLR_6 PEOPLE GUESTROOM_OCC_SCH ROOM_1_FLR_6 39.02 1.5 1.5 3.844E-002 26.015 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
14 ROOM_2_FLR_6 PEOPLE GUESTROOM_OCC_SCH ROOM_2_FLR_6 39.02 1.5 1.5 3.844E-002 26.012 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
15 ROOM_3_MULT9_FLR_6 PEOPLE GUESTROOM_OCC_SCH ROOM_3_MULT9_FLR_6 24.53 1.5 1.5 6.115E-002 16.354 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
16 BANQUET_FLR_6 PEOPLE BLDG_OCC_SCH BANQUET_FLR_6 331.66 249.9 249.9 0.753 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 250 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
17 DINING_FLR_6 PEOPLE BLDG_OCC_SCH DINING_FLR_6 331.66 249.9 249.9 0.753 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 250 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
18 KITCHEN_FLR_6 PEOPLE BLDG_OCC_SCH KITCHEN_FLR_6 103.30 22.2 22.2 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 22 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
19 STORAGE_FLR_1 PEOPLE BLDG_OCC_SCH STORAGE_FLR_1 94.76 2.0 2.0 2.153E-002 46.451 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
20 CORRIDOR_FLR_3 PEOPLE BLDG_OCC_SCH CORRIDOR_FLR_3 389.40 21.0 21.0 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 21 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
21 CORRIDOR_FLR_6 PEOPLE BLDG_OCC_SCH CORRIDOR_FLR_6 412.12 22.2 22.2 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 22 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
22 MECH_FLR_1 PEOPLE BLDG_OCC_SCH MECH_FLR_1 164.24 2.7 2.7 1.615E-002 61.932 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 3 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 BASEMENT_LIGHTS LTG_SCH_BASEMENT BASEMENT 1978.83 106.5 17441.963 8.814 163.776 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 17441.963
2 RETAIL_1_FLR_1_LIGHTS LTG_SCH_RETAIL RETAIL_1_FLR_1 67.07 10.8 758.849 11.314 70.076 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 758.849
3 RETAIL_2_FLR_1_LIGHTS LTG_SCH_RETAIL RETAIL_2_FLR_1 77.67 12.5 878.750 11.314 70.076 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 878.750
4 MECH_FLR_1_LIGHTS LTG_SCH_MECHANIC MECH_FLR_1 164.24 2.7 760.196 4.628 286.650 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 760.196
5 STORAGE_FLR_1_LIGHTS LTG_SCH_STORAGE STORAGE_FLR_1 94.76 2.0 542.017 5.720 265.695 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 542.017
6 LAUNDRY_FLR_1_LIGHTS LTG_SCH_LAUNDRY LAUNDRY_FLR_1 78.04 8.4 361.204 4.628 43.000 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 361.204
7 CAFE_FLR_1_LIGHTS LTG_SCH_DINING CAFE_FLR_1 188.86 142.3 1890.589 10.010 13.286 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1890.589
8 LOBBY_FLR_1_LIGHTS LTG_SCH_LOBBY LOBBY_FLR_1 1308.19 422.4 14081.185 10.764 33.333 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 14081.185
9 ROOM_1_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_1_FLR_3 39.02 1.5 323.422 8.288 215.615 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 323.422
10 ROOM_2_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_2_FLR_3 39.02 1.5 323.384 8.288 215.590 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 323.384
11 ROOM_3_MULT19_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_3_MULT19_FLR_3 24.52 1.5 203.259 8.288 135.506 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 203.259
12 ROOM_4_MULT19_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_4_MULT19_FLR_3 24.53 1.5 203.314 8.288 135.543 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 203.314
13 ROOM_5_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_5_FLR_3 39.02 1.5 323.422 8.288 215.615 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 323.422
14 ROOM_6_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_6_FLR_3 39.02 1.5 323.384 8.288 215.590 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 323.384
15 CORRIDOR_FLR_3_LIGHTS LTG_SCH_CORRIDOR CORRIDOR_FLR_3 389.40 21.0 2766.397 7.104 132.003 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2766.397
16 ROOM_1_FLR_6_LIGHTS LTG_SCH_GUESTROOM ROOM_1_FLR_6 39.02 1.5 323.422 8.288 215.615 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 323.422
17 ROOM_2_FLR_6_LIGHTS LTG_SCH_GUESTROOM ROOM_2_FLR_6 39.02 1.5 323.384 8.288 215.590 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 323.384
18 ROOM_3_MULT9_FLR_6_LIGHTS LTG_SCH_GUESTROOM ROOM_3_MULT9_FLR_6 24.53 1.5 203.314 8.288 135.543 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 203.314
19 BANQUET_FLR_6_LIGHTS LTG_SCH_DINING BANQUET_FLR_6 331.66 249.9 3320.034 10.010 13.286 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3320.034
20 DINING_FLR_6_LIGHTS LTG_SCH_DINING DINING_FLR_6 331.66 249.9 3320.034 10.010 13.286 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3320.034
21 KITCHEN_FLR_6_LIGHTS LTG_SCH_KITCHEN KITCHEN_FLR_6 103.30 22.2 1178.676 11.410 53.003 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1178.676
22 CORRIDOR_FLR_6_LIGHTS LTG_SCH_CORRIDOR CORRIDOR_FLR_6 412.12 22.2 2927.804 7.104 132.002 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2927.804


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 BASEMENT_MISCPLUG_EQUIP BASEMENT_EQUIP_SCH BASEMENT 1978.83 106.5 10646.106 5.380 99.964 0.000 0.500 0.000 0.500 MiscPlug 0.000 10646.106
2 RETAIL_1_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH RETAIL_1_FLR_1 67.07 10.8 721.688 10.760 66.644 0.000 0.500 0.000 0.500 MiscPlug 0.000 721.688
3 RETAIL_2_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH RETAIL_2_FLR_1 77.67 12.5 835.717 10.760 66.644 0.000 0.500 0.000 0.500 MiscPlug 0.000 835.717
4 MECH_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH MECH_FLR_1 164.24 2.7 883.628 5.380 333.193 0.000 0.500 0.000 0.500 MiscPlug 0.000 883.628
5 STORAGE_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH STORAGE_FLR_1 94.76 2.0 254.902 2.690 124.952 0.000 0.500 0.000 0.500 MiscPlug 0.000 254.902
6 LAUNDRY_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH LAUNDRY_FLR_1 78.04 8.4 4813.474 61.680 573.033 0.000 0.500 0.000 0.500 MiscPlug 0.000 4813.474
7 CAFE_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH CAFE_FLR_1 188.86 142.3 1016.077 5.380 7.140 0.000 0.500 0.000 0.500 MiscPlug 0.000 1016.077
8 LOBBY_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH LOBBY_FLR_1 1308.19 422.4 10557.062 8.070 24.991 0.000 0.500 0.000 0.500 MiscPlug 0.000 10557.062
9 ROOM_1_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_1_FLR_3 39.02 1.5 263.399 6.750 175.599 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.399
10 ROOM_2_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_2_FLR_3 39.02 1.5 263.368 6.750 175.579 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.368
11 ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_3_MULT19_FLR_3 24.52 1.5 257.991 10.520 171.994 0.000 0.500 0.000 0.500 MiscPlug 0.000 257.991
12 ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_4_MULT19_FLR_3 24.53 1.5 258.061 10.520 172.041 0.000 0.500 0.000 0.500 MiscPlug 0.000 258.061
13 ROOM_5_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_5_FLR_3 39.02 1.5 263.399 6.750 175.599 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.399
14 ROOM_6_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_6_FLR_3 39.02 1.5 263.368 6.750 175.579 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.368
15 ROOM_1_FLR_6_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_1_FLR_6 39.02 1.5 263.399 6.750 175.599 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.399
16 ROOM_2_FLR_6_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_2_FLR_6 39.02 1.5 263.368 6.750 175.579 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.368
17 ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_3_MULT9_FLR_6 24.53 1.5 258.061 10.520 172.041 0.000 0.500 0.000 0.500 MiscPlug 0.000 258.061
18 BANQUET_FLR_6_MISCPLUG_EQUIP KITCHEN_ELEC_EQUIP_SCH BANQUET_FLR_6 331.66 249.9 22493.008 67.820 90.009 0.000 0.500 0.000 0.500 Cooking 0.000 6747.903
19 DINING_FLR_6_MISCPLUG_EQUIP KITCHEN_ELEC_EQUIP_SCH DINING_FLR_6 331.66 249.9 22493.008 67.820 90.009 0.000 0.500 0.000 0.500 Cooking 0.000 6747.903
20 KITCHEN_FLR_6_MISCELEC_EQUIP KITCHEN_ELEC_EQUIP_SCH KITCHEN_FLR_6 103.30 22.2 52482.799 508.040 2360.050 0.200 0.500 0.100 0.200 Cooking 0.000 15744.840
21 KITCHEN_FLR_6_REACH-IN-FREEZER ALWAYS_ON KITCHEN_FLR_6 103.30 22.2 457.500 4.429 20.573 0.000 0.250 0.000 0.750 ReachInFreezer 457.500 457.500
22 KITCHEN_FLR_6_REACH-IN-REFRIGERATOR ALWAYS_ON KITCHEN_FLR_6 103.30 22.2 285.000 2.759 12.816 0.000 0.250 0.000 0.750 ReachInRefrigerator 285.000 285.000


GasEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 LAUNDRY_FLR_1_MISCGAS_EQUIP BLDG_EQUIP_SCH LAUNDRY_FLR_1 78.04 8.4 41817.449 535.850 4978.268 0.000 0.500 0.000 0.500 Laundry 0.000 41817.449
2 KITCHEN_FLR_6_MISCGAS_EQUIP KITCHEN_GAS_EQUIP_SCH KITCHEN_FLR_6 103.30 22.2 249920.353 2419.260 11238.437 0.100 0.200 0.700 0.000 Cooking 0.000 74976.106


Construction CTF

Construction Name Index #Layers #CTFs Time Step {hours} ThermalConductance {w/m2-K} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 SWINGING DOOR_CON 1 1 1 0.167 3.065 0.900 0.900 0.700 0.700 MediumRough
2 OVERHEAD DOOR_CON 2 1 1 0.167 2.390 0.900 0.900 0.700 0.700 MediumRough
3 INTERIORFURNISHINGS 3 1 9 0.167 0.8000 0.900 0.900 0.700 0.700 MediumSmooth
4 INT_WALL 8 2 4 0.167 6.299 0.900 0.900 0.700 0.700 Smooth
5 NONRES_ROOF 18 3 3 0.167 0.2284 0.750 0.900 0.450 0.700 Rough
6 RES_ROOF 19 3 3 0.167 0.2284 0.750 0.900 0.450 0.700 Rough
7 NONRES_EXT_WALL_GRD 21 3 9 0.167 0.9589 0.900 0.900 0.700 0.700 MediumRough
8 NONRES_EXT_WALL_MID 22 3 9 0.167 1.167 0.900 0.900 0.700 0.700 MediumRough
9 NONRES_EXT_WALL_TOP 23 3 9 0.167 1.181 0.900 0.900 0.700 0.700 MediumRough
10 RES_EXT_WALL_MID 25 3 9 0.167 1.021 0.900 0.900 0.700 0.700 MediumRough
11 RES_EXT_WALL_TOP 26 3 9 0.167 1.034 0.900 0.900 0.700 0.700 MediumRough
12 NONRES_FLOOR 30 3 7 0.167 0.3181 0.900 0.900 0.700 0.700 MediumSmooth
13 NONRES_FLOOR_CEILING 33 3 7 0.167 0.3181 0.900 0.900 0.700 0.700 VeryRough
14 BASEMENT_FLOOR 36 2 7 0.333 2.705 0.900 0.900 0.700 0.700 MediumRough
15 BASEMENT_WALL_NORTH_CFACTOR 39 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
16 BASEMENT_WALL_EAST_CFACTOR 40 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
17 BASEMENT_WALL_SOUTH_CFACTOR 41 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
18 BASEMENT_WALL_WEST_CFACTOR 42 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough


Material CTF Summary

Material Name Thickness {m} Conductivity {w/m-K} Density {kg/m3} Specific Heat {J/kg-K} ThermalResistance {m2-K/w}
1 OPAQUE DOOR PANEL_CON 0.0000 0.000 0.000 0.000 0.3263
2 OVERHEAD DOOR_CON PANEL 0.0000 0.000 0.000 0.000 0.4184
3 STD WOOD 6INCH 0.1500 0.120 540.000 1210.000 1.250
4 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
5 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
6 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
7 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 4.319
8 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
9 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
10 RES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 4.319
11 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
12 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
13 NONRES_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 0.8756
14 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
15 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
16 NONRES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 0.6894
17 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
18 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
19 NONRES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.6793
20 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
21 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
22 RES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 0.8120
23 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
24 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
25 RES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.7993
26 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
27 NONRES_FLOOR_INSULATION 0.0000 0.000 0.000 0.000 2.883
28 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
29 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
30 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
31 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
32 NONRES_FLOOR_INSULATION 0.0000 0.000 0.000 0.000 2.883
33 M10 200MM CONCRETE BLOCK BASEMENT WALL 0.2032 1.326 1842.000 912.000 0.1532
34 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
35 ~FC_Insulation_1 0.0000 0.000 0.000 0.000 0.9868
36 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
37 ~FC_Insulation_2 0.0000 0.000 0.000 0.000 0.9868
38 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
39 ~FC_Insulation_3 0.0000 0.000 0.000 0.000 0.9868
40 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
41 ~FC_Insulation_4 0.0000 0.000 0.000 0.000 0.9868
42 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01


CTF

Time Outside Cross Inside Flux (except final one)
1 1 0.0000000 0.0000000 -0.0000000 -0.0000000
2 0 3.0649134 3.0649134 3.0649134  
3 1 0.0000000 0.0000000 -0.0000000 -0.0000000
4 0 2.3900722 2.3900722 2.3900722  
5 9 -0.27580628E-02 0.97439125E-12 -0.27580628E-02 0.28516790E-03
6 8 0.73590997E-01 0.21837543E-08 0.73590997E-01 -0.77836043E-02
7 7 -0.82599318 0.23162835E-06 -0.82599318 0.89703933E-01
8 6 5.1113916 0.48671053E-05 5.1113916 -0.57224845
9 5 -19.214933 0.30163627E-04 -19.214933 2.2266322
10 4 45.557404 0.63181060E-04 45.557404 -5.4853312
11 3 -68.275533 0.44785456E-04 -68.275533 8.5710568
12 2 62.555368 0.93952058E-05 62.555368 -8.2111738
13 1 -31.904423 0.39200004E-06 -31.904423 4.3886678
14 0 6.9260389 0.77047546E-09 6.9260389  
15 4 0.68458728E-09 0.26079551E-09 0.68458728E-09 -0.34507121E-18
16 3 -0.72180374E-03 0.24295686E-03 -0.72180374E-03 0.69691454E-09
17 2 0.83054762 0.27682775 0.83054762 -0.35168967E-03
18 1 -12.650482 3.3590720 -12.650482 0.19281313
19 0 16.907513 1.4507143 16.907513  
20 3 -0.62451068E-06 0.10350887E-08 -0.38276125E-05 0.11995084E-16
21 2 0.77976586 0.13989883E-02 1.0579789 -0.73382352E-06
22 1 -21.958702 0.93426804E-01 -6.3215779 0.20283230
23 0 21.361010 0.87247630E-01 5.4456762  
24 3 -0.62451068E-06 0.10350887E-08 -0.38276125E-05 0.11995084E-16
25 2 0.77976586 0.13989883E-02 1.0579789 -0.73382352E-06
26 1 -21.958702 0.93426804E-01 -6.3215779 0.20283230
27 0 21.361010 0.87247630E-01 5.4456762  
28 9 -0.56372661E-17 0.35603042E-16 -0.14834456E-09 -0.22354951E-17
29 8 0.21681598E-07 0.12895413E-12 0.37576420E-03 -0.24652724E-09
30 7 -0.12181032E-01 0.67087143E-08 -0.22998674E-01 0.13850277E-03
31 6 0.40370585 0.23395349E-05 0.47069069 -0.47283774E-02
32 5 -5.1745154 0.87537405E-04 -4.4305073 0.62984858E-01
33 4 32.931872 0.71743813E-03 21.398312 -0.42118042
34 3 -111.07522 0.15662534E-02 -55.540939 1.5130129
35 2 196.98158 0.88235367E-03 77.798628 -2.8983416
36 1 -171.10930 0.94326468E-04 -55.232514 2.7446195
37 0 57.057407 0.53780718E-06 15.562302  
38 9 0.13788181E-14 0.42316407E-16 -0.13850765E-09 -0.36591458E-17
39 8 0.20295421E-07 0.15509090E-12 0.36099725E-03 -0.23076592E-09
40 7 -0.11739701E-01 0.81955471E-08 -0.22363010E-01 0.13348467E-03
41 6 0.39171309 0.28760220E-05 0.46045976 -0.45870120E-02
42 5 -5.0574682 0.10819265E-03 -4.3518524 0.61533536E-01
43 4 32.414067 0.89103805E-03 21.090697 -0.41430552
44 3 -109.97331 0.19536482E-02 -54.932704 1.4970936
45 2 195.88922 0.11048200E-02 77.241099 -2.8809953
46 1 -170.70571 0.11852782E-03 -55.070977 2.7375462
47 0 57.057407 0.67841551E-06 15.589460  
48 9 0.13857471E-14 0.43057560E-16 -0.13784678E-09 -0.68945926E-17
49 8 0.20202246E-07 0.15680163E-12 0.35999259E-03 -0.22970649E-09
50 7 -0.11709634E-01 0.82948599E-08 -0.22319691E-01 0.13314280E-03
51 6 0.39089600 0.29121450E-05 0.45976168 -0.45773805E-02
52 5 -5.0494928 0.10959277E-03 -4.3464810 0.61434646E-01
53 4 32.378781 0.90287364E-03 21.069680 -0.41383702
54 3 -109.89821 0.19801908E-02 -54.891143 1.4960086
55 2 195.81476 0.11201274E-02 77.203021 -2.8798128
56 1 -170.67819 0.12019965E-03 -55.059979 2.7370639
57 0 57.057407 0.68811227E-06 15.591337  
58 9 0.14302076E-15 0.35792568E-16 -0.14541430E-09 -0.27421543E-17
59 8 0.21269444E-07 0.13686051E-12 0.37140784E-03 -0.24184090E-09
60 7 -0.12050952E-01 0.71525680E-08 -0.22811354E-01 0.13702371E-03
61 6 0.40017121 0.24988627E-05 0.46767819 -0.46867126E-02
62 5 -5.1400200 0.93645327E-04 -4.4073602 0.62557131E-01
63 4 32.779281 0.76858103E-03 21.307814 -0.41915444
64 3 -110.75053 0.16800125E-02 -55.362013 1.5083221
65 2 196.65975 0.94749847E-03 77.634567 -2.8932310
66 1 -170.99041 0.10139533E-03 -55.184883 2.7425359
67 0 57.057407 0.57877233E-06 15.570231  
68 9 0.33566835E-16 0.35384250E-16 -0.14478218E-09 -0.87565041E-18
69 8 0.21180494E-07 0.13854999E-12 0.37046393E-03 -0.24082951E-09
70 7 -0.12022754E-01 0.72481687E-08 -0.22770744E-01 0.13670309E-03
71 6 0.39940498 0.25332696E-05 0.46702484 -0.46776806E-02
72 5 -5.1325420 0.94967185E-04 -4.4023386 0.62464408E-01
73 4 32.746200 0.77967008E-03 21.288178 -0.41871522
74 3 -110.68014 0.17047184E-02 -55.323188 1.5073051
75 2 196.58997 0.96166638E-03 77.598974 -2.8921229
76 1 -170.96463 0.10293464E-03 -55.174560 2.7420841
77 0 57.057407 0.58770932E-06 15.571958  
78 7 -0.11407965E-14 0.23474115E-16 -0.22119674E-13 0.51962024E-15
79 6 0.16676876E-10 0.39440661E-11 0.52102403E-09 -0.18553030E-10
80 5 -0.80001662E-07 0.19215958E-07 -0.21848785E-05 0.17095694E-06
81 4 0.10228101E-03 0.72538432E-05 0.17630655E-02 -0.28160064E-03
82 3 -0.15120274E-01 0.25611913E-03 -0.21515117 0.43248511E-01
83 2 0.21482172 0.11124906E-02 2.8969963 -0.61829830
84 1 -0.54366453 0.69706713E-03 -7.1337069 1.5687761
85 0 0.34594624 0.12518961E-04 4.4521846  
86 7 -0.22119674E-13 0.23474115E-16 -0.11407965E-14 0.51962024E-15
87 6 0.52102403E-09 0.39440661E-11 0.16676876E-10 -0.18553030E-10
88 5 -0.21848785E-05 0.19215958E-07 -0.80001662E-07 0.17095694E-06
89 4 0.17630655E-02 0.72538432E-05 0.10228101E-03 -0.28160064E-03
90 3 -0.21515117 0.25611913E-03 -0.15120274E-01 0.43248511E-01
91 2 2.8969963 0.11124906E-02 0.21482172 -0.61829830
92 1 -7.1337069 0.69706713E-03 -0.54366453 1.5687761
93 0 4.4521846 0.12518961E-04 0.34594624  
94 7 -0.52459208E-15 -0.63961428E-15 -0.12292524E-09 -0.35846135E-17
95 6 0.39860198E-02 0.96339020E-07 0.40499006E-03 -0.70890431E-04
96 5 -0.20832379 0.49172556E-04 -0.20585669E-01 0.38489246E-02
97 4 3.5198270 0.18993977E-02 0.34924834 -0.69168259E-01
98 3 -23.366787 0.13311857E-01 -2.4329538 0.50524779
99 2 64.890127 0.19943872E-01 7.3672511 -1.5911358
100 1 -76.040094 0.56792084E-02 -9.5568013 2.1361271
101 0 31.242244 0.96490710E-04 4.3344156  
102 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
103 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
104 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
105 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
106 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
107 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
108 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
109 0 1.0055995 0.48413807E-04 60.838472  
110 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
111 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
112 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
113 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
114 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
115 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
116 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
117 0 1.0055995 0.48413807E-04 60.838472  
118 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
119 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
120 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
121 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
122 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
123 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
124 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
125 0 1.0055995 0.48413807E-04 60.838472  
126 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
127 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
128 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
129 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
130 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
131 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
132 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
133 0 1.0055995 0.48413807E-04 60.838472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {W/m2-K} Conductance (Before Adjusted) {W/m2-K} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 NONRESWINDOW_U_0.45_SHGC_0.25 37 1 VerySmooth 2.557 2.557 1.000 0.251    
2 RESWINDOW_U_0.487_SHGC_0.25 38 1 VerySmooth 2.769 2.769 1.000 0.251    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {m} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLAZING LAYER SpectralAverage   2.66719E-002 0.16139 0.61727 0.61727 0.27500 0.15630 0.22588 0.00000 0.84000 0.84000 0.12129 1.00000 No
2 RESIDENTIAL WINDOW GLAZING LAYER SpectralAverage   2.17016E-002 0.16139 0.61276 0.61276 0.27500 0.15630 0.22588 0.00000 0.84000 0.84000 0.11379 1.00000 No


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 7 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Enclosure/Window Adjacency Daylighting Counts

Enclosure Name Number of Exterior Windows Number of Exterior Windows in Adjacent Enclosures
1 CAFE_FLR_1 1 0
2 LOBBY_FLR_1 1 0
3 BANQUET_FLR_6 1 0
4 DINING_FLR_6 1 0


Enclosure/Window Adjacency Daylighting Matrix

Enclosure Name Number of Adjacent Enclosures with Windows Adjacent Enclosure Names - 1st 100 (max)
1 CAFE_FLR_1 0  
2 LOBBY_FLR_1 0  
3 BANQUET_FLR_6 0  
4 DINING_FLR_6 0  


#Refrigeration Compressor Racks

Number of Refrigeration Compressor Racks
1 2


Refrigeration Compressor Rack

Compressor Rack Name # Refrigerated Cases Connected # WalkIn Coolers Connected Heat Rejection Location Condenser Type COP
1 RACK1 1 0 Zone Air-Cooled 1.500
2 RACK2 1 0 Zone Air-Cooled 3.000


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWH LAUNDRY G WATER HEATER 1.1356 163316.0 11.511 0.4388
2 WaterHeater:Mixed SWH BOOSTER E WATER HEATER 2.2712E-002 8000.0 1.219 1.1187
3 WaterHeater:Mixed SWHSYS1 WATER HEATER 2.2712 175842.6 5.775 0.3748


Surface Convection Parameters

Surface Name Outside Model Assignment Outside Area [m2] Outside Perimeter [m] Outside Height [m] Inside Model Assignment Inside Height [m] Inside Perimeter Envelope [m] Inside Hydraulic Diameter [m] Window Wall Ratio Window Location Near Radiant {Yes/No} Has Active HVAC {Yes/No}
1 BASEMENT_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
2 BASEMENT_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
3 BASEMENT_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
4 BASEMENT_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
5 BASEMENT_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
6 BASEMENT_CEILING_1 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
7 BASEMENT_CEILING_2 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
8 BASEMENT_CEILING_3 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
9 BASEMENT_CEILING_4 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
10 BASEMENT_CEILING_5 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
11 BASEMENT_CEILING_6 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
12 BASEMENT_CEILING_7 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
13 BASEMENT_CEILING_8 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
14 BASEMENT_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
15 RETAIL_1_FLR_1_WALL_SOUTH 0 506.51 211.91 19.20 0 3.96 17.37 7.72 0.34 4 No No
16 RETAIL_1_FLR_1_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.96 17.37 7.72 0.34 1 No No
17 RETAIL_1_FLR_1_WALL_WEST 0 194.63 84.12 19.20 0 3.96 17.37 7.72 0.34 3 No No
18 RETAIL_1_FLR_1_WALL_NORTH 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
19 RETAIL_1_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
20 RETAIL_1_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
21 RETAIL_1_FLR_1_CEILING 0 1782.60 293.11 15.24 0 3.96 17.37 7.72 0.34 0 No No
22 RETAIL_1_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
23 RETAIL_2_FLR_1_WALL_WEST 0 194.63 84.12 19.20 0 3.96 6.71 8.49 0.00 0 No No
24 RETAIL_2_FLR_1_WALL_WEST_DOOR 0 194.63 84.12 19.20 0 3.96 6.71 8.49 0.00 0 No No
25 RETAIL_2_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
26 RETAIL_2_FLR_1_WALL_NORTH 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
27 RETAIL_2_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
28 RETAIL_2_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
29 RETAIL_2_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
30 RETAIL_2_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
31 MECH_FLR_1_WALL_NORTH 0 670.01 217.46 19.20 0 3.96 15.85 12.53 0.00 0 No No
32 MECH_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
33 MECH_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
34 MECH_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
35 MECH_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
36 MECH_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
37 MECH_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
38 STORAGE_FLR_1_WALL_NORTH 0 670.01 217.46 19.20 0 3.96 9.14 9.72 0.00 0 No No
39 STORAGE_FLR_1_WALL_NORTH_ROLLDOOR 0 670.01 217.46 19.20 0 3.96 9.14 9.72 0.00 0 No No
40 STORAGE_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
41 STORAGE_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
42 STORAGE_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
43 STORAGE_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
44 STORAGE_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
45 STORAGE_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
46 LAUNDRY_FLR_1_WALL_NORTH 0 670.01 217.46 19.20 0 3.96 21.64 7.21 0.00 0 No No
47 LAUNDRY_FLR_1_WALL_EAST 0 194.63 217.46 19.20 0 3.96 21.64 7.21 0.00 0 No No
48 LAUNDRY_FLR_1_WALL_EAST_DOOR 0 194.63 217.46 19.20 0 3.96 21.64 7.21 0.00 0 No No
49 LAUNDRY_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
50 LAUNDRY_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
51 LAUNDRY_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
52 LAUNDRY_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
53 LAUNDRY_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
54 CAFE_FLR_1_WALL_EAST 0 194.63 217.46 19.20 0 3.96 38.40 9.84 0.43 3 No No
55 CAFE_FLR_1_WALL_EAST_DOOR 0 194.63 217.46 19.20 0 3.96 38.40 9.84 0.43 0 No No
56 CAFE_FLR_1_WALL_SOUTH 0 506.51 211.91 19.20 0 3.96 38.40 9.84 0.43 4 No No
57 CAFE_FLR_1_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.96 38.40 9.84 0.43 1 No No
58 CAFE_FLR_1_WALL_1_NORTH 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
59 CAFE_FLR_1_WALL_2_NORTH 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
60 CAFE_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
61 CAFE_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
62 CAFE_FLR_1_CEILING 0 1782.60 293.11 15.24 0 3.96 38.40 9.84 0.43 0 No No
63 CAFE_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
64 LOBBY_FLR_1_WALL_1_NORTH 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 3 No No
65 LOBBY_FLR_1_WALL_1_NORTH_DOOR1 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 0 No No
66 LOBBY_FLR_1_WALL_1_NORTH_DOOR2 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 0 No No
67 LOBBY_FLR_1_WALL_2_NORTH 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 4 No No
68 LOBBY_FLR_1_WALL_1_SOUTH 0 506.51 211.91 19.20 0 3.96 109.73 24.95 0.20 4 No No
69 LOBBY_FLR_1_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.96 109.73 24.95 0.20 1 No No
70 LOBBY_FLR_1_WALL_1_WEST 0 194.63 84.12 19.20 0 3.96 109.73 24.95 0.20 3 No No
71 LOBBY_FLR_1_WALL_2_SOUTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
72 LOBBY_FLR_1_WALL_3_SOUTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
73 LOBBY_FLR_1_WALL_2_WEST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
74 LOBBY_FLR_1_WALL_3_WEST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
75 LOBBY_FLR_1_WALL_4_WEST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
76 LOBBY_FLR_1_WALL_3_NORTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
77 LOBBY_FLR_1_WALL_4_NORTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
78 LOBBY_FLR_1_WALL_1_EAST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
79 LOBBY_FLR_1_WALL_2_EAST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
80 LOBBY_FLR_1_WALL_3_EAST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
81 LOBBY_FLR_1_FLOOR_1 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
82 LOBBY_FLR_1_FLOOR_2 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
83 LOBBY_FLR_1_CEILING_1 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
84 LOBBY_FLR_1_CEILING_2 0 1782.60 293.11 15.24 0 3.96 109.73 24.95 0.20 0 No No
85 LOBBY_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
86 ROOM_1_FLR_3_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 3 No No
87 ROOM_1_FLR_3_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 2 No No
88 ROOM_1_FLR_3_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
89 ROOM_1_FLR_3_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
90 ROOM_1_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
91 ROOM_1_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
92 ROOM_1_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
93 ROOM_1_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
94 ROOM_1_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
95 ROOM_2_FLR_3_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
96 ROOM_2_FLR_3_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
97 ROOM_2_FLR_3_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
98 ROOM_2_FLR_3_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
99 ROOM_2_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
100 ROOM_2_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
101 ROOM_2_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
102 ROOM_2_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
103 ROOM_2_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
104 ROOM_3_MULT19_FLR_3_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 3.66 4.73 0.33 3 No No
105 ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 3.66 4.73 0.33 2 No No
106 ROOM_3_MULT19_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
107 ROOM_3_MULT19_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
108 ROOM_3_MULT19_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
109 ROOM_3_MULT19_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
110 ROOM_3_MULT19_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
111 ROOM_3_MULT19_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
112 ROOM_4_MULT19_FLR_3_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 3.66 4.73 0.33 3 No No
113 ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 3.66 4.73 0.33 2 No No
114 ROOM_4_MULT19_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
115 ROOM_4_MULT19_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
116 ROOM_4_MULT19_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
117 ROOM_4_MULT19_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
118 ROOM_4_MULT19_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
119 ROOM_4_MULT19_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
120 ROOM_5_FLR_3_WALL_EAST 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
121 ROOM_5_FLR_3_WALL_EAST_WINDOW 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
122 ROOM_5_FLR_3_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 3 No No
123 ROOM_5_FLR_3_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 2 No No
124 ROOM_5_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
125 ROOM_5_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
126 ROOM_5_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
127 ROOM_5_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
128 ROOM_5_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
129 ROOM_6_FLR_3_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
130 ROOM_6_FLR_3_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
131 ROOM_6_FLR_3_WALL_EAST 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
132 ROOM_6_FLR_3_WALL_EAST_WINDOW 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
133 ROOM_6_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
134 ROOM_6_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
135 ROOM_6_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
136 ROOM_6_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
137 ROOM_6_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
138 CORRIDOR_FLR_3_WALL_1_NORTH 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 3 No No
139 CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 2 No No
140 CORRIDOR_FLR_3_WALL_2_NORTH 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 3 No No
141 CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 2 No No
142 CORRIDOR_FLR_3_WALL_1_SOUTH 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 3 No No
143 CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 2 No No
144 CORRIDOR_FLR_3_WALL_2_SOUTH 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 3 No No
145 CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 2 No No
146 CORRIDOR_FLR_3_WALL_3_NORTH 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
147 CORRIDOR_FLR_3_WALL_1_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
148 CORRIDOR_FLR_3_WALL_2_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
149 CORRIDOR_FLR_3_WALL_3_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
150 CORRIDOR_FLR_3_WALL_4_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
151 CORRIDOR_FLR_3_WALL_3_SOUTH 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
152 CORRIDOR_FLR_3_WALL_1_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
153 CORRIDOR_FLR_3_WALL_2_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
154 CORRIDOR_FLR_3_WALL_3_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
155 CORRIDOR_FLR_3_WALL_4_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
156 CORRIDOR_FLR_3_FLOOR_1 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
157 CORRIDOR_FLR_3_FLOOR_2 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
158 CORRIDOR_FLR_3_FLOOR_3 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
159 CORRIDOR_FLR_3_CEILING_1 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
160 CORRIDOR_FLR_3_CEILING_2 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
161 CORRIDOR_FLR_3_CEILING_3 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
162 CORRIDOR_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
163 ROOM_1_FLR_6_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 3 No No
164 ROOM_1_FLR_6_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 2 No No
165 ROOM_1_FLR_6_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
166 ROOM_1_FLR_6_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
167 ROOM_1_FLR_6_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
168 ROOM_1_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
169 ROOM_1_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
170 ROOM_1_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 13.11 5.95 0.33 0 No No
171 ROOM_1_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
172 ROOM_2_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
173 ROOM_2_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
174 ROOM_2_FLR_6_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
175 ROOM_2_FLR_6_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
176 ROOM_2_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
177 ROOM_2_FLR_6_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
178 ROOM_2_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
179 ROOM_2_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 13.11 5.95 0.33 0 No No
180 ROOM_2_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
181 ROOM_3_MULT9_FLR_6_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 6.71 4.73 0.33 3 No No
182 ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 6.71 4.73 0.33 2 No No
183 ROOM_3_MULT9_FLR_6_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
184 ROOM_3_MULT9_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
185 ROOM_3_MULT9_FLR_6_WALL_WEST 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
186 ROOM_3_MULT9_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
187 ROOM_3_MULT9_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 6.71 4.73 0.33 0 No No
188 ROOM_3_MULT9_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
189 BANQUET_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 3 No No
190 BANQUET_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 2 No No
191 BANQUET_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
192 BANQUET_FLR_6_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
193 BANQUET_FLR_6_WALL_WEST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
194 BANQUET_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
195 BANQUET_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 32.00 15.66 0.33 0 No No
196 BANQUET_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
197 DINING_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 3 No No
198 DINING_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 2 No No
199 DINING_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
200 DINING_FLR_6_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
201 DINING_FLR_6_WALL_WEST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
202 DINING_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
203 DINING_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 32.00 15.66 0.33 0 No No
204 DINING_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
205 KITCHEN_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 28.65 8.58 0.30 3 No No
206 KITCHEN_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 28.65 8.58 0.30 2 No No
207 KITCHEN_FLR_6_WALL_EAST 0 194.63 217.46 19.20 0 3.05 28.65 8.58 0.30 3 No No
208 KITCHEN_FLR_6_WALL_EAST_WINDOW 0 194.63 217.46 19.20 0 3.05 28.65 8.58 0.30 2 No No
209 KITCHEN_FLR_6_WALL_1_SOUTH 0 506.51 211.91 19.20 0 3.05 28.65 8.58 0.30 3 No No
210 KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 28.65 8.58 0.30 2 No No
211 KITCHEN_FLR_6_WALL_2_SOUTH 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
212 KITCHEN_FLR_6_WALL_1_WEST 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
213 KITCHEN_FLR_6_WALL_2_WEST 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
214 KITCHEN_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
215 KITCHEN_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 28.65 8.58 0.30 0 No No
216 KITCHEN_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
217 CORRIDOR_FLR_6_WALL_1_NORTH 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 3 No No
218 CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 2 No No
219 CORRIDOR_FLR_6_WALL_2_NORTH 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 3 No No
220 CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 2 No No
221 CORRIDOR_FLR_6_WALL_2_SOUTH 0 506.51 211.91 19.20 0 3.05 28.04 8.72 0.33 3 No No
222 CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 28.04 8.72 0.33 2 No No
223 CORRIDOR_FLR_6_WALL_3_NORTH 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
224 CORRIDOR_FLR_6_WALL_4_NORTH 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
225 CORRIDOR_FLR_6_WALL_1_SOUTH 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
226 CORRIDOR_FLR_6_WALL_1_WEST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
227 CORRIDOR_FLR_6_WALL_2_WEST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
228 CORRIDOR_FLR_6_WALL_3_WEST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
229 CORRIDOR_FLR_6_WALL_1_EAST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
230 CORRIDOR_FLR_6_WALL_2_EAST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
231 CORRIDOR_FLR_6_WALL_3_EAST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
232 CORRIDOR_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
233 CORRIDOR_FLR_6_CEILING_1 0 1782.60 293.11 15.24 0 3.05 28.04 8.72 0.33 0 No No
234 CORRIDOR_FLR_6_CEILING_2 0 1782.60 293.11 15.24 0 3.05 28.04 8.72 0.33 0 No No
235 CORRIDOR_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 RETAIL_1_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH RETAIL_1_FLR_1 67.07 10.8 1.764E-002 2.631E-004 1.298E-004 0.239 1.000 0.000 0.000 0.000
2 RETAIL_2_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH RETAIL_2_FLR_1 77.67 12.5 6.811E-003 8.769E-005 2.388E-004 7.967E-002 1.000 0.000 0.000 0.000
3 MECH_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH MECH_FLR_1 164.24 2.7 1.610E-002 9.800E-005 2.563E-004 8.904E-002 1.000 0.000 0.000 0.000
4 STORAGE_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH STORAGE_FLR_1 94.76 2.0 9.287E-003 9.800E-005 2.127E-004 8.904E-002 1.000 0.000 0.000 0.000
5 LAUNDRY_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH LAUNDRY_FLR_1 78.04 8.4 2.198E-002 2.816E-004 2.506E-004 0.256 1.000 0.000 0.000 0.000
6 CAFE_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH CAFE_FLR_1 188.86 142.3 3.900E-002 2.065E-004 1.137E-004 0.188 1.000 0.000 0.000 0.000
7 LOBBY_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH LOBBY_FLR_1 1308.19 422.4 0.111 8.519E-005 1.629E-004 7.740E-002 1.000 0.000 0.000 0.000
8 ROOM_1_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_1_FLR_3 39.02 1.5 1.024E-002 2.624E-004 2.563E-004 0.310 1.000 0.000 0.000 0.000
9 ROOM_2_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_2_FLR_3 39.02 1.5 1.024E-002 2.624E-004 2.563E-004 0.310 1.000 0.000 0.000 0.000
10 ROOM_3_MULT19_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_3_MULT19_FLR_3 24.52 1.5 2.857E-003 1.165E-004 2.563E-004 0.138 1.000 0.000 0.000 0.000
11 ROOM_4_MULT19_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_4_MULT19_FLR_3 24.53 1.5 2.858E-003 1.165E-004 2.563E-004 0.138 1.000 0.000 0.000 0.000
12 ROOM_5_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_5_FLR_3 39.02 1.5 1.024E-002 2.624E-004 2.563E-004 0.310 1.000 0.000 0.000 0.000
13 ROOM_6_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_6_FLR_3 39.02 1.5 1.024E-002 2.624E-004 2.563E-004 0.310 1.000 0.000 0.000 0.000
14 CORRIDOR_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH CORRIDOR_FLR_3 389.40 21.0 1.238E-002 3.180E-005 2.563E-004 3.755E-002 1.000 0.000 0.000 0.000
15 ROOM_1_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_1_FLR_6 39.02 1.5 1.024E-002 2.624E-004 1.297E-004 0.310 1.000 0.000 0.000 0.000
16 ROOM_2_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_2_FLR_6 39.02 1.5 1.024E-002 2.624E-004 1.297E-004 0.310 1.000 0.000 0.000 0.000
17 ROOM_3_MULT9_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_3_MULT9_FLR_6 24.53 1.5 5.239E-003 2.136E-004 1.165E-004 0.252 1.000 0.000 0.000 0.000
18 BANQUET_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH BANQUET_FLR_6 331.66 249.9 2.500E-002 7.539E-005 5.825E-005 8.904E-002 1.000 0.000 0.000 0.000
19 DINING_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH DINING_FLR_6 331.66 249.9 2.500E-002 7.539E-005 5.825E-005 8.904E-002 1.000 0.000 0.000 0.000
20 KITCHEN_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH KITCHEN_FLR_6 103.30 22.2 2.238E-002 2.167E-004 1.174E-004 0.256 1.000 0.000 0.000 0.000
21 CORRIDOR_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH CORRIDOR_FLR_6 412.12 22.2 2.191E-002 5.316E-005 4.403E-005 6.278E-002 1.000 0.000 0.000 0.000


ZoneVentilation Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/person Area {m3/s-person} ACH - Air Changes per Hour Fan Type {Exhaust;Intake;Natural} Fan Pressure Rise {Pa} Fan Efficiency {} Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2} Minimum Indoor Temperature{C}/Schedule Maximum Indoor Temperature{C}/Schedule Delta Temperature{C}/Schedule Minimum Outdoor Temperature{C}/Schedule Maximum Outdoor Temperature{C}/Schedule Maximum WindSpeed{m/s}
1 ROOM_1_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_1_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
2 ROOM_2_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_2_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
3 ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_3_MULT19_FLR_3 24.52 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
4 ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_4_MULT19_FLR_3 24.53 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
5 ROOM_5_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_5_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
6 ROOM_6_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_6_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
7 ROOM_1_FLR_6 SLIDING DOOR VENTILATION Constant-0.0 ROOM_1_FLR_6 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
8 ROOM_2_FLR_6 SLIDING DOOR VENTILATION Constant-0.0 ROOM_2_FLR_6 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
9 ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION Constant-0.0 ROOM_3_MULT9_FLR_6 24.53 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 BASEMENT Mixing/Well-Stirred
2 RETAIL_1_FLR_1 Mixing/Well-Stirred
3 RETAIL_2_FLR_1 Mixing/Well-Stirred
4 MECH_FLR_1 Mixing/Well-Stirred
5 STORAGE_FLR_1 Mixing/Well-Stirred
6 LAUNDRY_FLR_1 Mixing/Well-Stirred
7 CAFE_FLR_1 Mixing/Well-Stirred
8 LOBBY_FLR_1 Mixing/Well-Stirred
9 ROOM_1_FLR_3 Mixing/Well-Stirred
10 ROOM_2_FLR_3 Mixing/Well-Stirred
11 ROOM_3_MULT19_FLR_3 Mixing/Well-Stirred
12 ROOM_4_MULT19_FLR_3 Mixing/Well-Stirred
13 ROOM_5_FLR_3 Mixing/Well-Stirred
14 ROOM_6_FLR_3 Mixing/Well-Stirred
15 CORRIDOR_FLR_3 Mixing/Well-Stirred
16 ROOM_1_FLR_6 Mixing/Well-Stirred
17 ROOM_2_FLR_6 Mixing/Well-Stirred
18 ROOM_3_MULT9_FLR_6 Mixing/Well-Stirred
19 BANQUET_FLR_6 Mixing/Well-Stirred
20 DINING_FLR_6 Mixing/Well-Stirred
21 KITCHEN_FLR_6 Mixing/Well-Stirred
22 CORRIDOR_FLR_6 Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Sky Daylight Factors

Sky Type MonthAndDay Daylighting Control Name Enclosure Name Window Name Reference Point Daylight Factor
1 Clear Sky 12/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 9.5713E-002
2 Clear Sky 12/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 4.3008E-002
3 Clear Turbid Sky 12/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 0.1063
4 Clear Turbid Sky 12/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 4.6946E-002
5 Intermediate Sky 12/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 7.2253E-002
6 Intermediate Sky 12/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 2.6856E-002
7 Overcast Sky 12/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 2.9162E-002
8 Overcast Sky 12/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 9.6591E-003
9 Clear Sky 12/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 0.1081
10 Clear Sky 12/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 5.2611E-002
11 Clear Turbid Sky 12/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 0.1204
12 Clear Turbid Sky 12/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 5.7369E-002
13 Intermediate Sky 12/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 7.9985E-002
14 Intermediate Sky 12/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 3.3898E-002
15 Overcast Sky 12/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 3.2764E-002
16 Overcast Sky 12/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 1.3236E-002
17 Clear Sky 12/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 2.3289E-002
18 Clear Sky 12/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 1.3312E-002
19 Clear Turbid Sky 12/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 1.7943E-002
20 Clear Turbid Sky 12/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 1.0055E-002
21 Intermediate Sky 12/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 1.7164E-002
22 Intermediate Sky 12/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 6.8561E-003
23 Overcast Sky 12/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 2.8719E-002
24 Overcast Sky 12/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 1.0154E-002
25 Clear Sky 12/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 2.3289E-002
26 Clear Sky 12/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 1.3312E-002
27 Clear Turbid Sky 12/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 1.7943E-002
28 Clear Turbid Sky 12/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 1.0055E-002
29 Intermediate Sky 12/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 1.7164E-002
30 Intermediate Sky 12/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 6.8561E-003
31 Overcast Sky 12/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 2.8719E-002
32 Overcast Sky 12/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 1.0154E-002


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 BASEMENT Cooling 32902.69748 32902.69748 2.43592 2.43592 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 19:20:00 27.50267 8.22747E-003 1978.83018 106.49900 0.85446 0.00000
2 BASEMENT Heating 0.00000 0.00000 0.00000 0.85446   00:10:00 3.80000 5.05843E-003 1978.83018 106.49900 0.85446 0.00000
3 RETAIL_1_FLR_1 Cooling 4218.75745 4218.75745 0.31236 0.31236 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:10:00 30.92917 8.23290E-003 67.07136 10.82900 7.92179E-002 0.00000
4 RETAIL_1_FLR_1 Heating 1682.57937 1682.57937 7.34860E-002 7.92179E-002 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3.80000 5.05843E-003 67.07136 10.82900 7.92179E-002 0.00000
5 RETAIL_2_FLR_1 Cooling 3076.20060 3076.20060 0.22777 0.22777 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 30.05400 8.23151E-003 77.66889 12.54000 9.17347E-002 0.00000
6 RETAIL_2_FLR_1 Heating 562.46518 562.46518 2.45656E-002 9.17347E-002 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3.80000 5.05843E-003 77.66889 12.54000 9.17347E-002 0.00000
7 MECH_FLR_1 Cooling 2446.19663 2446.19663 0.18108 0.18108 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:30:00 28.49650 8.22904E-003 164.24319 2.65200 0.00000 0.00000
8 MECH_FLR_1 Heating 1000.82488 1000.82488 4.37109E-002 4.37109E-002 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3.80000 5.05843E-003 164.24319 2.65200 0.00000 0.00000
9 STORAGE_FLR_1 Cooling 1435.57375 1435.57375 0.10627 0.10627 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:10:00 31.21100 8.23335E-003 94.75927 2.04000 5.77652E-002 0.00000
10 STORAGE_FLR_1 Heating 670.28289 670.28289 2.92745E-002 5.77652E-002 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3.80000 5.05843E-003 94.75927 2.04000 5.77652E-002 0.00000
11 LAUNDRY_FLR_1 Cooling 44525.31933 44525.31933 3.29633 3.29633 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:40:00 31.30000 8.23349E-003 78.03947 8.40000 0.00000 0.00000
12 LAUNDRY_FLR_1 Heating 1306.23105 1306.23105 5.70491E-002 5.70491E-002 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3.80000 5.05843E-003 78.03947 8.40000 0.00000 0.00000
13 CAFE_FLR_1 Cooling 18649.47260 18649.47260 1.38198 1.38198 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:10:00 30.92917 8.23290E-003 188.86188 142.30000 0.67638 0.00000
14 CAFE_FLR_1 Heating 4292.00006 4292.00006 0.18745 0.67638 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3.80000 5.05843E-003 188.86188 142.30000 0.67638 0.00000
15 LOBBY_FLR_1 Cooling 62965.29312 62965.29312 4.66338 4.66338 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 31.07750 8.23314E-003 1308.18612 422.43500 1.89399 0.00000
16 LOBBY_FLR_1 Heating 9965.93524 9965.93524 0.43526 1.89399 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3.80000 5.05843E-003 1308.18612 422.43500 1.89399 0.00000
17 ROOM_1_FLR_3 Cooling 9804.14433 9804.14433 0.97806 0.97806 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:20:00 30.52867 8.23226E-003 39.02202 1.50000 6.17350E-002 0.00000
18 ROOM_1_FLR_3 Heating 3704.30699 3704.30699 0.16273 0.16273 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3.80000 5.05843E-003 39.02202 1.50000 6.17350E-002 0.00000
19 ROOM_2_FLR_3 Cooling 9439.03834 9439.03834 0.94164 0.94164 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00 30.41000 8.23207E-003 39.01745 1.50000 6.17278E-002 0.00000
20 ROOM_2_FLR_3 Heating 3704.51086 3704.51086 0.16274 0.16274 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3.80000 5.05843E-003 39.01745 1.50000 6.17278E-002 0.00000
21 ROOM_3_MULT19_FLR_3 Cooling 61224.75970 61224.75970 6.10751 6.10751 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 31.07750 8.23314E-003 24.52384 1.50000 0.83707 0.00000
22 ROOM_3_MULT19_FLR_3 Heating 21626.50983 21626.50983 0.95008 0.95008 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3.80000 5.05843E-003 24.52384 1.50000 0.83707 0.00000
23 ROOM_4_MULT19_FLR_3 Cooling 57499.59948 57499.59948 5.73636 5.73636 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:50:00 31.30000 8.23349E-003 24.53055 1.50000 0.83730 0.00000
24 ROOM_4_MULT19_FLR_3 Heating 21641.03659 21641.03659 0.95072 0.95072 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3.80000 5.05843E-003 24.53055 1.50000 0.83730 0.00000
25 ROOM_5_FLR_3 Cooling 8712.42120 8712.42120 0.86915 0.86915 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:30:00 27.16150 8.22694E-003 39.02202 1.50000 6.17350E-002 0.00000
26 ROOM_5_FLR_3 Heating 3703.47754 3703.47754 0.16270 0.16270 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3.80000 5.05843E-003 39.02202 1.50000 6.17350E-002 0.00000
27 ROOM_6_FLR_3 Cooling 8388.25058 8388.25058 0.83681 0.83681 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:10:00 26.65717 8.22614E-003 39.01745 1.50000 6.17278E-002 0.00000
28 ROOM_6_FLR_3 Heating 3703.68139 3703.68139 0.16271 0.16271 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3.80000 5.05843E-003 39.01745 1.50000 6.17278E-002 0.00000
29 CORRIDOR_FLR_3 Cooling 19237.22982 19237.22982 1.42417 1.42417 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:10:00 31.30000 8.23349E-003 389.40468 20.95700 0.47476 0.00000
30 CORRIDOR_FLR_3 Heating 6023.58091 6023.58091 0.26308 0.47476 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3.80000 5.05843E-003 389.40468 20.95700 0.47476 0.00000
31 ROOM_1_FLR_6 Cooling 2539.20075 2539.20075 0.25331 0.25331 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:20:00 30.52867 8.23226E-003 39.02202 1.50000 1.54338E-002 0.00000
32 ROOM_1_FLR_6 Heating 1153.43294 1153.43294 5.06717E-002 5.06717E-002 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3.80000 5.05843E-003 39.02202 1.50000 1.54338E-002 0.00000
33 ROOM_2_FLR_6 Cooling 2438.99931 2438.99931 0.24331 0.24331 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00 30.41000 8.23207E-003 39.01745 1.50000 1.54319E-002 0.00000
34 ROOM_2_FLR_6 Heating 1152.98951 1152.98951 5.06522E-002 5.06522E-002 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3.80000 5.05843E-003 39.01745 1.50000 1.54319E-002 0.00000
35 ROOM_3_MULT9_FLR_6 Cooling 11922.45204 11922.45204 1.18942 1.18942 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 31.07750 8.23314E-003 24.53055 1.50000 9.91540E-002 0.00000
36 ROOM_3_MULT9_FLR_6 Heating 5585.51508 5585.51508 0.24538 0.24538 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3.80000 5.05843E-003 24.53055 1.50000 9.91540E-002 0.00000
37 BANQUET_FLR_6 Cooling 28592.97589 28592.97589 2.11944 2.11944 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:20:00 31.30000 8.23349E-003 331.65745 249.89600 1.18780 0.00000
38 BANQUET_FLR_6 Heating 3898.48204 3898.48204 0.17027 1.18780 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 20:00:00 3.80000 5.05843E-003 331.65745 249.89600 1.18780 0.00000
39 DINING_FLR_6 Cooling 29985.09931 29985.09931 2.22260 2.22260 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:10:00 31.30000 8.23349E-003 331.65745 249.89600 1.18780 0.00000
40 DINING_FLR_6 Heating 3955.38943 3955.38943 0.17275 1.18780 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 04:20:00 3.80000 5.05843E-003 331.65745 249.89600 1.18780 0.00000
41 KITCHEN_FLR_6 Cooling 29969.63864 29969.63864 2.22457 2.22457 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 12:30:00 30.49900 8.23222E-003 103.30446 22.23800 0.36735 0.00000
42 KITCHEN_FLR_6 Heating 75.88517 75.88517 3.31510E-003 0.36735 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 3.80000 5.05843E-003 103.30446 22.23800 0.36735 0.00000
43 CORRIDOR_FLR_6 Cooling 9517.54181 9517.54181 0.70460 0.70460 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:50:00 31.22583 8.23338E-003 412.12471 22.18000 0.12562 0.00000
44 CORRIDOR_FLR_6 Heating 4160.65325 4160.65325 0.18172 0.18172 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 04:30:00 3.80000 5.05843E-003 412.12471 22.18000 0.12562 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 FLR_3_DOAS Cooling Sensible 45064.07 16.39778 2.05125 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 00:00:00
2 FLR_3_DOAS Heating Sensible 31423.05 2.89839 2.05125 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00
3 VAV WITH REHEAT Cooling Sensible 382603.23 21.18187 21.18187 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 00:00:00
4 VAV WITH REHEAT Heating Sensible 109582.88 7.15339 7.15339 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 04:30:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.43592
2 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.61901
3 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.54700
4 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.33245
5 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
6 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
7 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 6.15494E-004
8 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 6.04035E-005
9 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.33245
10 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
11 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
12 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size Rated Capacity [W] 6904.49014
13 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 6.04035E-005
14 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 143.98124
15 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.31236
16 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.16362
17 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.54700
18 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.17086
19 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.54700
20 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
21 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.32857E-003
22 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.24628E-005
23 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.17086
24 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
25 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
26 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 2567.63677
27 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.24628E-005
28 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 59.46405
29 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.22777
30 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.25984
31 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.54700
32 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.12459
33 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.69291
34 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
35 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.46628E-003
36 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.05665E-005
37 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.12459
38 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
39 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
40 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1207.82117
41 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.05665E-005
42 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 26.38422
43 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.18108
44 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.69114
45 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.54700
46 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 9.90519E-002
47 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
48 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
49 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 5.51262E-004
50 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.32438E-005
51 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 9.90519E-002
52 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
53 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
54 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1513.84388
55 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.32438E-005
56 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 35.16164
57 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.10627
58 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.67946
59 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.54700
60 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 5.81300E-002
61 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
62 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
63 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 5.60740E-004
64 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 8.49800E-006
65 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 5.81300E-002
66 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
67 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
68 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 971.37371
69 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 8.49800E-006
70 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 22.93683
71 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 3.29633
72 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 1.80401E-002
73 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.54700
74 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.80310
75 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.54700
76 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
77 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.11197E-002
78 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.31235E-005
79 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.80310
80 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
81 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
82 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 10644.59252
83 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.31235E-005
84 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 223.58928
85 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.38198
86 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.10414
87 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.54700
88 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.75594
89 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.54700
90 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
91 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.65871E-003
92 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 7.18069E-005
93 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.75594
94 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
95 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
96 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 8207.96423
97 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 7.18069E-005
98 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 181.51987
99 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 4.66338
100 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.21376
101 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.54700
102 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.55087
103 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.57002
104 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
105 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.78238E-003
106 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.02784E-004
107 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.55087
108 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
109 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
110 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 23179.42724
111 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.02784E-004
112 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 503.10621
113 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_1_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17350E-002
114 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.97806
115 Fan:OnOff ROOM_1_FLR_3 FAN COIL_FANCOILFAN Design Size Maximum Flow Rate [m3/s] 0.97806
116 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 3.24068E-005
117 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 3.06252E-004
118 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69392
119 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
120 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.57357E-003
121 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
122 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
123 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 3.06252E-004
124 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.97806
125 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 3704.30165
126 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 3.24068E-005
127 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 105.83922
128 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_2_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17278E-002
129 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.94164
130 Fan:OnOff ROOM_2_FLR_3 FAN COIL_FANCOILFAN Design Size Maximum Flow Rate [m3/s] 0.94164
131 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 3.24086E-005
132 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 2.95071E-004
133 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69392
134 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
135 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.57634E-003
136 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
137 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
138 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 2.95071E-004
139 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.94164
140 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 3704.50551
141 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 3.24086E-005
142 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 105.84504
143 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_3_MULT19_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.83707
144 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT19_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 6.10751
145 Fan:OnOff ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN Design Size Maximum Flow Rate [m3/s] 6.10751
146 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT19_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 1.89198E-004
147 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT19_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 1.87389E-003
148 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69437
149 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
150 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.49776E-003
151 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
152 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.49776E-003
153 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.87389E-003
154 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 6.10751
155 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 21626.49471
156 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.89198E-004
157 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 617.90663
158 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_4_MULT19_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.83730
159 ZoneHVAC:FourPipeFanCoil ROOM_4_MULT19_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 5.73636
160 Fan:OnOff ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN Design Size Maximum Flow Rate [m3/s] 5.73636
161 ZoneHVAC:FourPipeFanCoil ROOM_4_MULT19_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 1.89325E-004
162 ZoneHVAC:FourPipeFanCoil ROOM_4_MULT19_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 1.88085E-003
163 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69346
164 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
165 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.74561E-003
166 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
167 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
168 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.88085E-003
169 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 5.73636
170 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 21641.02147
171 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.89325E-004
172 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 618.32166
173 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_5_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17350E-002
174 ZoneHVAC:FourPipeFanCoil ROOM_5_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.86915
175 Fan:OnOff ROOM_5_FLR_3 FAN COIL_FANCOILFAN Design Size Maximum Flow Rate [m3/s] 0.86915
176 ZoneHVAC:FourPipeFanCoil ROOM_5_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 3.23996E-005
177 ZoneHVAC:FourPipeFanCoil ROOM_5_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 2.72831E-004
178 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69391
179 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
180 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.58270E-003
181 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
182 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
183 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 2.72831E-004
184 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.86915
185 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 3703.47219
186 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 3.23996E-005
187 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 105.81552
188 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_6_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17278E-002
189 ZoneHVAC:FourPipeFanCoil ROOM_6_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.83681
190 Fan:OnOff ROOM_6_FLR_3 FAN COIL_FANCOILFAN Design Size Maximum Flow Rate [m3/s] 0.83681
191 ZoneHVAC:FourPipeFanCoil ROOM_6_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 3.24014E-005
192 ZoneHVAC:FourPipeFanCoil ROOM_6_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 2.62907E-004
193 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69390
194 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
195 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.58586E-003
196 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
197 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
198 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 2.62907E-004
199 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.83681
200 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 3703.67604
201 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 3.24014E-005
202 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 105.82135
203 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.42417
204 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.83340
205 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.54700
206 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.77902
207 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
208 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
209 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 4.57163E-004
210 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 8.80030E-005
211 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.77902
212 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
213 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
214 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 10059.28379
215 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 8.80030E-005
216 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 227.50053
217 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_1_FLR_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 1.54338E-002
218 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_6 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.25331
219 Fan:OnOff ROOM_1_FLR_6 FAN COIL_FANCOILFAN Design Size Maximum Flow Rate [m3/s] 0.25331
220 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_6 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 1.00907E-005
221 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_6 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 7.92632E-005
222 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69393
223 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
224 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.57110E-003
225 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
226 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
227 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 7.92632E-005
228 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.25331
229 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL Design Size Rated Capacity [W] 1153.43135
230 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.00907E-005
231 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 32.95515
232 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_2_FLR_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 1.54319E-002
233 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_6 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.24331
234 Fan:OnOff ROOM_2_FLR_6 FAN COIL_FANCOILFAN Design Size Maximum Flow Rate [m3/s] 0.24331
235 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_6 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 1.00868E-005
236 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_6 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 7.61948E-005
237 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69392
238 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
239 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.57394E-003
240 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
241 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
242 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 7.61948E-005
243 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.24331
244 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL Design Size Rated Capacity [W] 1152.98792
245 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.00868E-005
246 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 32.94248
247 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_3_MULT9_FLR_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 9.91540E-002
248 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT9_FLR_6 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.18942
249 Fan:OnOff ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN Design Size Maximum Flow Rate [m3/s] 1.18942
250 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT9_FLR_6 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 4.88645E-005
251 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT9_FLR_6 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 3.79096E-004
252 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69363
253 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
254 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.63892E-003
255 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
256 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
257 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 3.79096E-004
258 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.18942
259 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Design Size Rated Capacity [W] 5585.50894
260 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 4.88645E-005
261 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 159.58524
262 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.11944
263 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.11924
264 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.54700
265 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.15933
266 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.54700
267 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
268 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.19523E-003
269 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 8.66494E-005
270 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.15933
271 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
272 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
273 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 9904.55954
274 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 8.66494E-005
275 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 213.75667
276 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.22260
277 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.11371
278 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.54700
279 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.21576
280 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.54700
281 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
282 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.35074E-003
283 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 8.97056E-005
284 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.21576
285 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
286 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
287 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 10253.89673
288 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 8.97056E-005
289 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 221.04413
290 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.22457
291 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 6.36456E-002
292 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.54700
293 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.21684
294 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.54700
295 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
296 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.07671E-002
297 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 5.91273E-005
298 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.21684
299 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
300 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
301 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 6758.61114
302 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 5.91273E-005
303 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 141.46612
304 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.70460
305 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.44570
306 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.54700
307 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.38541
308 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
309 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
310 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 8.54835E-004
311 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 5.38680E-005
312 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.38541
313 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
314 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
315 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 6157.44652
316 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 5.38680E-005
317 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 144.16031
318 AirLoopHVAC FLR_3_DOAS Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 2.05132
319 AirLoopHVAC FLR_3_DOAS Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 2.05132
320 AirLoopHVAC FLR_3_DOAS Sum of Air Terminal Maximum Flow Rates [m3/s] 2.05132
321 AirLoopHVAC FLR_3_DOAS Adjusted Heating Design Air Flow Rate [m3/s] 2.05132
322 AirLoopHVAC FLR_3_DOAS Adjusted Cooling Design Air Flow Rate [m3/s] 2.05132
323 AirLoopHVAC FLR_3_DOAS Adjusted Main Design Air Flow Rate [m3/s] 2.05132
324 AirLoopHVAC FLR_3_DOAS User Heating Air Flow Ratio [] 0.30000
325 AirLoopHVAC FLR_3_DOAS Calculated Heating Air Flow Ratio [] 1.00000
326 AirLoopHVAC VAV WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 11.65136
327 AirLoopHVAC VAV WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 11.65136
328 AirLoopHVAC VAV WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 21.30047
329 AirLoopHVAC VAV WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 11.65136
330 AirLoopHVAC VAV WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 21.18187
331 AirLoopHVAC VAV WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 21.18187
332 AirLoopHVAC VAV WITH REHEAT User Heating Air Flow Ratio [] 0.30000
333 AirLoopHVAC VAV WITH REHEAT Calculated Heating Air Flow Ratio [] 0.55006
334 AirLoopHVAC FLR_3_DOAS Design Supply Air Flow Rate [m3/s] 2.05132
335 AirLoopHVAC VAV WITH REHEAT Design Supply Air Flow Rate [m3/s] 21.18187
336 Controller:OutdoorAir FLR_3_DOAS_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 2.05132
337 Controller:OutdoorAir FLR_3_DOAS_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 2.05125
338 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Inlet Air Temperature [C] 31.30000
339 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
340 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Outlet Air Temperature [C] 11.91243
341 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.23349E-003
342 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.23349E-003
343 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Coil Load [W] 47946.24805
344 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.37126E-003
345 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Air Flow Rate [m3/s] 2.05132
346 Coil:Heating:Water FLR_3_DOAS HEATING COIL Design Size Rated Capacity [W] 9427.24706
347 Coil:Heating:Water FLR_3_DOAS HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 8.24737E-005
348 Coil:Heating:Water FLR_3_DOAS HEATING COIL Design Size U-Factor Times Area Value [W/K] 168.96790
349 Fan:ConstantVolume FLR_3_DOAS FAN User-Specified Maximum Flow Rate [m3/s] 2.05125
350 Controller:WaterCoil FLR_3_DOAS_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 1.37126E-003
351 Controller:WaterCoil FLR_3_DOAS_COOLC_CONTROLLER Controller Convergence Tolerance 3.47266E-004
352 Controller:WaterCoil FLR_3_DOAS_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 8.24737E-005
353 Controller:OutdoorAir VAV WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 21.18187
354 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 28.01518
355 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
356 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 10.94368
357 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.89053E-003
358 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
359 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 461117.24515
360 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.31879E-002
361 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 21.18187
362 Coil:Heating:Water VAV WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 97345.61167
363 Coil:Heating:Water VAV WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 8.51622E-004
364 Coil:Heating:Water VAV WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 1744.76005
365 Fan:VariableVolume VAV WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 21.18187
366 Controller:WaterCoil VAV WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 1.31879E-002
367 Controller:WaterCoil VAV WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 3.61081E-005
368 Controller:WaterCoil VAV WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 8.51622E-004
369 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Flow Rate [m3/s] 1.99855E-002
370 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Power Consumption [W] 3263.02098
371 PlantLoop HEATSYS1 Maximum Loop Flow Rate [m3/s] 2.37152E-003
372 PlantLoop HEATSYS1 Plant Loop Volume [m3] 0.28458
373 Pump:VariableSpeed HEATSYS1 PUMP Design Flow Rate [m3/s] 2.37152E-003
374 Pump:VariableSpeed HEATSYS1 PUMP Design Power Consumption [W] 714.19742
375 Pump:VariableSpeed HEATSYS1 PUMP Design Minimum Flow Rate [m3/s] 0.00000
376 Boiler:HotWater HEATSYS1 BOILER Design Size Nominal Capacity [W] 271079.20588
377 Boiler:HotWater HEATSYS1 BOILER User-Specified Nominal Capacity [W] 271079.21000
378 Boiler:HotWater HEATSYS1 BOILER Design Size Design Water Flow Rate [m3/s] 2.37152E-003
379 PlantLoop COOLSYS1 Maximum Loop Flow Rate [m3/s] 1.99855E-002
380 PlantLoop COOLSYS1 Plant Loop Volume [m3] 2.39826
381 Pump:ConstantSpeed COOLSYS1 PUMP Design Flow Rate [m3/s] 1.99855E-002
382 Pump:ConstantSpeed COOLSYS1 PUMP Design Power Consumption [W] 2259.09948
383 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Chilled Water Flow Rate [m3/s] 1.99855E-002
384 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Capacity [W] 698796.69689
385 Chiller:Electric:EIR COOLSYS1 CHILLER1 User-Specified Reference Capacity [W] 699394.26000
386 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Condenser Fluid Flow Rate [m3/s] 79.73095
387 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 3.75036E-004
388 PlantLoop SWHSYS1 Plant Loop Volume [m3] 4.50044E-002
389 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 3.75036E-004
390 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 47.90688
391 WaterHeater:Mixed SWHSYS1 WATER HEATER Use Side Design Flow Rate [m3/s] 3.75036E-004


Water Heating Coil Capacity Information

Component Type Name Nominal Total Capacity {W}
1 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL 6940.20
2 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL 2579.49
3 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL 1213.81
4 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL 1520.81
5 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL 975.78
6 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL 10699.28
7 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL 8247.63
8 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL 23295.07
9 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL 3989.58
10 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL 3989.80
11 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL 23291.92
12 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL 23307.56
13 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL 3988.69
14 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL 3988.91
15 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL 10106.81
16 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL 1242.25
17 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL 1241.77
18 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL 6015.58
19 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL 9954.22
20 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL 10305.36
21 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL 6793.45
22 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL 6185.59
23 Coil:Heating:Water FLR_3_DOAS HEATING COIL 7911.32
24 Coil:Heating:Water VAV WITH REHEAT HEATING COIL 81692.19


Water Cooling Coil Capacity Information

Component Type Name Nominal Total Capacity {W} Nominal Sensible Capacity {W} Nominal Latent Capacity {W} Nominal Sensible Heat Ratio Nominal Coil UA Value {W/C} Nominal Coil Surface Area {m2}
1 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL 15966.31 13745.90 2220.41 0.86 3235.93 32.82
2 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL 15379.68 13236.70 2142.98 0.86 3114.53 31.59
3 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL 98327.12 85377.27 12949.85 0.87 20385.07 206.76
4 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL 96630.89 81659.65 14971.24 0.85 18745.16 190.12
5 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL 14212.60 12223.44 1989.15 0.86 2872.91 29.14
6 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL 13691.86 11771.38 1920.48 0.86 2765.14 28.05
7 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL 4133.24 3559.44 573.80 0.86 838.30 8.50
8 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL 3972.25 3419.69 552.56 0.86 804.98 8.16
9 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL 19654.86 16798.67 2856.19 0.85 3914.85 39.71
10 Coil:Cooling:Water FLR_3_DOAS COOLING COIL 51303.12 35829.51 15473.61 0.70 7298.17 74.02
11 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL 526994.00 369834.86 157159.13 0.70 81964.46 831.33


Chiller Standard Rating Information

Component Type Component Name IPLV in SI Units {W/W} IPLV in IP Units {Btu/W-h}
1 Chiller:Electric:EIR COOLSYS1 CHILLER1 4.09 13.95


Zone Surfaces

Zone Name # Surfaces
1 BASEMENT 14
2 RETAIL_1_FLR_1 8
3 RETAIL_2_FLR_1 8
4 MECH_FLR_1 7
5 STORAGE_FLR_1 8
6 LAUNDRY_FLR_1 8
7 CAFE_FLR_1 10
8 LOBBY_FLR_1 22
9 ROOM_1_FLR_3 9
10 ROOM_2_FLR_3 9
11 ROOM_3_MULT19_FLR_3 8
12 ROOM_4_MULT19_FLR_3 8
13 ROOM_5_FLR_3 9
14 ROOM_6_FLR_3 9
15 CORRIDOR_FLR_3 25
16 ROOM_1_FLR_6 9
17 ROOM_2_FLR_6 9
18 ROOM_3_MULT9_FLR_6 8
19 BANQUET_FLR_6 8
20 DINING_FLR_6 8
21 KITCHEN_FLR_6 12
22 CORRIDOR_FLR_6 19


HeatTransfer Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Construction Nominal U (w/o film coefs) {W/m2-K} Nominal U (with film coefs) {W/m2-K} Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m} ExtBoundCondition ExtConvCoeffCalc IntConvCoeffCalc SunExposure WindExposure ViewFactorToGround ViewFactorToSky ViewFactorToGround-IR ViewFactorToSky-IR #Sides
1 BASEMENT_WALL_NORTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_NORTH_CFACTOR 0.940 0.824   211.13 211.13 211.13 0.00 90.00 86.56 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
2 BASEMENT_WALL_EAST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_EAST_CFACTOR 0.940 0.824   55.76 55.76 55.76 90.00 90.00 22.86 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
3 BASEMENT_WALL_SOUTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_SOUTH_CFACTOR 0.940 0.824   211.13 211.13 211.13 180.00 90.00 86.56 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
4 BASEMENT_WALL_WEST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_WEST_CFACTOR 0.940 0.824   55.76 55.76 55.76 270.00 90.00 22.86 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
5 BASEMENT_FLOOR Floor   CTF - ConductionTransferFunction BASEMENT_FLOOR 2.705 1.632   1978.83 1978.83 1978.83 0.00 180.00 86.56 22.86 0.00 BASEMENT_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
6 BASEMENT_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.318 0.300   67.07 67.07 67.07 180.00 0.00 11.58 5.79 0.00 RETAIL_1_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
7 BASEMENT_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.318 0.300   77.67 77.67 77.67 180.00 0.00 11.58 6.71 0.00 RETAIL_2_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
8 BASEMENT_CEILING_3 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.318 0.300   164.24 164.24 164.24 180.00 0.00 15.85 10.36 0.00 MECH_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
9 BASEMENT_CEILING_4 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.318 0.300   94.76 94.76 94.76 180.00 0.00 9.14 10.36 0.00 STORAGE_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
10 BASEMENT_CEILING_5 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.318 0.300   78.04 78.04 78.04 180.00 0.00 4.57 17.07 0.00 LAUNDRY_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
11 BASEMENT_CEILING_6 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.318 0.300   188.86 188.86 188.86 180.00 0.00 32.61 5.79 0.00 CAFE_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
12 BASEMENT_CEILING_7 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.318 0.300   1088.56 1088.56 1088.56 180.00 0.00 32.99 32.99 0.00 LOBBY_FLR_1_FLOOR_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
13 BASEMENT_CEILING_8 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.318 0.300   219.63 219.63 219.63 90.00 0.00 14.82 14.82 0.00 LOBBY_FLR_1_FLOOR_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
14 BASEMENT_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   3957.66 3957.66 3957.66 0.00 90.00 3957.66 1.00 0.00 BASEMENT_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
15 RETAIL_1_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.959 0.839   22.63 45.89 22.63 180.00 90.00 11.58 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
16 RETAIL_1_FLR_1_WALL_SOUTH_WINDOW Window RETAIL_1_FLR_1_WALL_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.45_SHGC_0.25 N/A 2.557 No 23.26 23.26 23.26 180.00 90.00 10.92 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
17 RETAIL_1_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.959 0.839   22.95 22.95 22.95 270.00 90.00 5.79 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
18 RETAIL_1_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 0.00 90.00 11.58 3.96 0.00 RETAIL_2_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
19 RETAIL_1_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 90.00 90.00 5.79 3.96 0.00 LOBBY_FLR_1_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
20 RETAIL_1_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.318 0.295   67.07 67.07 67.07 0.00 180.00 11.58 5.79 0.00 BASEMENT_CEILING_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
21 RETAIL_1_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   67.07 67.07 67.07 180.00 0.00 11.58 5.79 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 7.62E-002 0.92 4
22 RETAIL_1_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   134.14 134.14 134.14 0.00 90.00 134.14 1.00 0.00 RETAIL_1_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
23 RETAIL_2_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.959 0.839   24.62 26.57 24.62 270.00 90.00 6.71 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
24 RETAIL_2_FLR_1_WALL_WEST_DOOR Door RETAIL_2_FLR_1_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
25 RETAIL_2_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 180.00 90.00 11.58 3.96 0.00 RETAIL_1_FLR_1_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
26 RETAIL_2_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 0.00 90.00 11.58 3.96 0.00 LOBBY_FLR_1_WALL_2_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
27 RETAIL_2_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.57 26.57 26.57 90.00 90.00 6.71 3.96 0.00 LOBBY_FLR_1_WALL_3_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
28 RETAIL_2_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.318 0.295   77.67 77.67 77.67 0.00 180.00 11.58 6.71 0.00 BASEMENT_CEILING_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
29 RETAIL_2_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.318 0.300   77.67 77.67 77.67 180.00 0.00 11.58 6.71 0.00 RETAIL_2_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
30 RETAIL_2_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   155.34 155.34 155.34 0.00 90.00 155.34 1.00 0.00 RETAIL_2_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
31 MECH_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.959 0.839   62.80 62.80 62.80 0.00 90.00 15.85 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
32 MECH_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 90.00 90.00 10.36 3.96 0.00 STORAGE_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
33 MECH_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   62.80 62.80 62.80 180.00 90.00 15.85 3.96 0.00 LOBBY_FLR_1_WALL_3_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
34 MECH_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 LOBBY_FLR_1_WALL_1_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
35 MECH_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.318 0.295   164.24 164.24 164.24 0.00 180.00 15.85 10.36 0.00 BASEMENT_CEILING_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
36 MECH_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.318 0.300   164.24 164.24 164.24 180.00 0.00 15.85 10.36 0.00 MECH_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
37 MECH_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   328.49 328.49 328.49 0.00 90.00 328.49 1.00 0.00 MECH_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
38 STORAGE_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.959 0.839   28.80 36.23 28.80 0.00 90.00 9.14 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
39 STORAGE_FLR_1_WALL_NORTH_ROLLDOOR Door STORAGE_FLR_1_WALL_NORTH CTF - ConductionTransferFunction OVERHEAD DOOR_CON 2.390 2.390   7.43 7.43 7.43 0.00 90.00 3.05 2.44 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
40 STORAGE_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 90.00 90.00 10.36 3.96 0.00 LOBBY_FLR_1_WALL_4_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
41 STORAGE_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.23 36.23 36.23 180.00 90.00 9.14 3.96 0.00 LOBBY_FLR_1_WALL_4_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
42 STORAGE_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 MECH_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
43 STORAGE_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.318 0.295   94.76 94.76 94.76 0.00 180.00 9.14 10.36 0.00 BASEMENT_CEILING_4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
44 STORAGE_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.318 0.300   94.76 94.76 94.76 180.00 0.00 9.14 10.36 0.00 STORAGE_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
45 STORAGE_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   189.52 189.52 189.52 0.00 90.00 189.52 1.00 0.00 STORAGE_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
46 LAUNDRY_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.959 0.839   18.12 18.12 18.12 0.00 90.00 4.57 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
47 LAUNDRY_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.959 0.839   65.68 67.63 65.68 90.00 90.00 17.07 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
48 LAUNDRY_FLR_1_WALL_EAST_DOOR Door LAUNDRY_FLR_1_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
49 LAUNDRY_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.12 18.12 18.12 180.00 90.00 4.57 3.96 0.00 CAFE_FLR_1_WALL_2_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
50 LAUNDRY_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   67.63 67.63 67.63 270.00 90.00 17.07 3.96 0.00 LOBBY_FLR_1_WALL_3_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
51 LAUNDRY_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.318 0.295   78.04 78.04 78.04 0.00 180.00 4.57 17.07 0.00 BASEMENT_CEILING_5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
52 LAUNDRY_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.318 0.300   78.04 78.04 78.04 180.00 0.00 4.57 17.07 0.00 LAUNDRY_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
53 LAUNDRY_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   156.08 156.08 156.08 0.00 90.00 156.08 1.00 0.00 LAUNDRY_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
54 CAFE_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.959 0.839   21.00 22.95 21.00 90.00 90.00 5.79 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
55 CAFE_FLR_1_WALL_EAST_DOOR Door CAFE_FLR_1_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
56 CAFE_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.959 0.839   63.73 129.23 63.73 180.00 90.00 32.61 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
57 CAFE_FLR_1_WALL_SOUTH_WINDOW Window CAFE_FLR_1_WALL_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.45_SHGC_0.25 N/A 2.557 No 65.50 65.50 65.50 180.00 90.00 30.75 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
58 CAFE_FLR_1_WALL_1_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.11 111.11 111.11 0.00 90.00 28.04 3.96 0.00 LOBBY_FLR_1_WALL_3_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
59 CAFE_FLR_1_WALL_2_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.12 18.12 18.12 0.00 90.00 4.57 3.96 0.00 LAUNDRY_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
60 CAFE_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 270.00 90.00 5.79 3.96 0.00 LOBBY_FLR_1_WALL_2_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
61 CAFE_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.318 0.295   188.86 188.86 188.86 0.00 180.00 32.61 5.79 0.00 BASEMENT_CEILING_6 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
62 CAFE_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   188.86 188.86 188.86 180.00 0.00 32.61 5.79 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 3.86E-002 0.96 4
63 CAFE_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   377.72 377.72 377.72 0.00 90.00 377.72 1.00 0.00 CAFE_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
64 LOBBY_FLR_1_WALL_1_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.959 0.839   209.87 213.77 209.87 0.00 90.00 53.95 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
65 LOBBY_FLR_1_WALL_1_NORTH_DOOR1 Door LOBBY_FLR_1_WALL_1_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
66 LOBBY_FLR_1_WALL_1_NORTH_DOOR2 Door LOBBY_FLR_1_WALL_1_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
67 LOBBY_FLR_1_WALL_2_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.959 0.839   12.08 12.08 12.08 0.00 90.00 3.05 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
68 LOBBY_FLR_1_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.959 0.839   82.79 167.88 82.79 180.00 90.00 42.37 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
69 LOBBY_FLR_1_WALL_SOUTH_WINDOW Window LOBBY_FLR_1_WALL_1_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.45_SHGC_0.25 N/A 2.557 No 85.08 85.08 85.08 180.00 90.00 39.95 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
70 LOBBY_FLR_1_WALL_1_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.959 0.839   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
71 LOBBY_FLR_1_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 180.00 90.00 11.58 3.96 0.00 RETAIL_2_FLR_1_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
72 LOBBY_FLR_1_WALL_3_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.11 111.11 111.11 180.00 90.00 28.04 3.96 0.00 CAFE_FLR_1_WALL_1_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
73 LOBBY_FLR_1_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 270.00 90.00 5.79 3.96 0.00 RETAIL_1_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
74 LOBBY_FLR_1_WALL_3_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.57 26.57 26.57 270.00 90.00 6.71 3.96 0.00 RETAIL_2_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
75 LOBBY_FLR_1_WALL_4_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 STORAGE_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
76 LOBBY_FLR_1_WALL_3_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   62.80 62.80 62.80 0.00 90.00 15.85 3.96 0.00 MECH_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
77 LOBBY_FLR_1_WALL_4_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.23 36.23 36.23 0.00 90.00 9.14 3.96 0.00 STORAGE_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
78 LOBBY_FLR_1_WALL_1_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 90.00 90.00 10.36 3.96 0.00 MECH_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
79 LOBBY_FLR_1_WALL_2_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 90.00 90.00 5.79 3.96 0.00 CAFE_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
80 LOBBY_FLR_1_WALL_3_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   67.63 67.63 67.63 90.00 90.00 17.07 3.96 0.00 LAUNDRY_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
81 LOBBY_FLR_1_FLOOR_1 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.318 0.295   1088.56 1088.56 1088.56 180.00 180.00 32.99 32.99 0.00 BASEMENT_CEILING_7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
82 LOBBY_FLR_1_FLOOR_2 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.318 0.295   219.63 219.63 219.63 90.00 180.00 14.82 14.82 0.00 BASEMENT_CEILING_8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
83 LOBBY_FLR_1_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.318 0.300   1062.83 1062.83 1062.83 270.00 0.00 32.60 32.60 0.00 LOBBY_FLR_1_CEILING_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 10
84 LOBBY_FLR_1_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   245.35 245.35 245.35 180.00 0.00 42.37 5.79 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 4.22E-003 1.00 4
85 LOBBY_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   2616.37 2616.37 2616.37 0.00 90.00 2616.37 1.00 0.00 LOBBY_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
86 ROOM_1_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.021 0.886   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
87 ROOM_1_FLR_3_WALL_SOUTH_WINDOW Window ROOM_1_FLR_3_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.487_SHGC_0.25 N/A 2.769 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
88 ROOM_1_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.021 0.886   17.43 26.01 17.43 270.00 90.00 8.54 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
89 ROOM_1_FLR_3_WALL_WEST_WINDOW Window ROOM_1_FLR_3_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.487_SHGC_0.25 N/A 2.769 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
90 ROOM_1_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ROOM_2_FLR_3_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
91 ROOM_1_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.54 3.05 0.00 CORRIDOR_FLR_3_WALL_3_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
92 ROOM_1_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.318 0.295   39.02 39.02 39.02 0.00 180.00 4.57 8.54 0.00 ROOM_1_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
93 ROOM_1_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.318 0.300   39.02 39.02 39.02 180.00 0.00 4.57 8.54 0.00 ROOM_1_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
94 ROOM_1_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 ROOM_1_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
95 ROOM_2_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.021 0.886   9.34 13.94 9.34 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
96 ROOM_2_FLR_3_WALL_NORTH_WINDOW Window ROOM_2_FLR_3_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.487_SHGC_0.25 N/A 2.769 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
97 ROOM_2_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.021 0.886   17.43 26.01 17.43 270.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
98 ROOM_2_FLR_3_WALL_WEST_WINDOW Window ROOM_2_FLR_3_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.487_SHGC_0.25 N/A 2.769 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
99 ROOM_2_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.53 3.05 0.00 CORRIDOR_FLR_3_WALL_4_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
100 ROOM_2_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ROOM_1_FLR_3_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
101 ROOM_2_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.318 0.295   39.02 39.02 39.02 0.00 180.00 4.57 8.53 0.00 ROOM_2_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
102 ROOM_2_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.318 0.300   39.02 39.02 39.02 180.00 0.00 4.57 8.53 0.00 ROOM_2_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
103 ROOM_2_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.03 78.03 78.03 0.00 90.00 78.03 1.00 0.00 ROOM_2_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
104 ROOM_3_MULT19_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.021 0.886   7.47 11.15 7.47 180.00 90.00 3.66 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
105 ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW Window ROOM_3_MULT19_FLR_3_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.487_SHGC_0.25 N/A 2.769 No 3.68 3.68 3.68 180.00 90.00 3.02 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
106 ROOM_3_MULT19_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 0.00 90.00 3.66 3.05 0.00 ROOM_3_MULT19_FLR_3_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
107 ROOM_3_MULT19_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 ROOM_3_MULT19_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
108 ROOM_3_MULT19_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 ROOM_3_MULT19_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
109 ROOM_3_MULT19_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.318 0.295   24.52 24.52 24.52 0.00 180.00 3.66 6.71 0.00 ROOM_3_MULT19_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
110 ROOM_3_MULT19_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.318 0.300   24.52 24.52 24.52 180.00 0.00 3.66 6.71 0.00 ROOM_3_MULT19_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
111 ROOM_3_MULT19_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   49.05 49.05 49.05 0.00 90.00 49.05 1.00 0.00 ROOM_3_MULT19_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
112 ROOM_4_MULT19_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.021 0.886   7.47 11.15 7.47 0.00 90.00 3.66 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
113 ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW Window ROOM_4_MULT19_FLR_3_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.487_SHGC_0.25 N/A 2.769 No 3.68 3.68 3.68 0.00 90.00 3.02 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
114 ROOM_4_MULT19_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 ROOM_4_MULT19_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
115 ROOM_4_MULT19_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 180.00 90.00 3.66 3.05 0.00 ROOM_4_MULT19_FLR_3_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
116 ROOM_4_MULT19_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 ROOM_4_MULT19_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
117 ROOM_4_MULT19_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.318 0.295   24.53 24.53 24.53 0.00 180.00 3.66 6.71 0.00 ROOM_4_MULT19_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
118 ROOM_4_MULT19_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.318 0.300   24.53 24.53 24.53 180.00 0.00 3.66 6.71 0.00 ROOM_4_MULT19_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
119 ROOM_4_MULT19_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   49.06 49.06 49.06 0.00 90.00 49.06 1.00 0.00 ROOM_4_MULT19_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
120 ROOM_5_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.021 0.886   17.43 26.01 17.43 90.00 90.00 8.54 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
121 ROOM_5_FLR_3_WALL_EAST_WINDOW Window ROOM_5_FLR_3_WALL_EAST Window5 Detailed Fenestration RESWINDOW_U_0.487_SHGC_0.25 N/A 2.769 No 8.58 8.58 8.58 90.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
122 ROOM_5_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.021 0.886   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
123 ROOM_5_FLR_3_WALL_SOUTH_WINDOW Window ROOM_5_FLR_3_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.487_SHGC_0.25 N/A 2.769 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
124 ROOM_5_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ROOM_6_FLR_3_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
125 ROOM_5_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.54 3.05 0.00 CORRIDOR_FLR_3_WALL_3_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
126 ROOM_5_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.318 0.295   39.02 39.02 39.02 0.00 180.00 4.57 8.54 0.00 ROOM_5_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
127 ROOM_5_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.318 0.300   39.02 39.02 39.02 180.00 0.00 4.57 8.54 0.00 ROOM_5_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
128 ROOM_5_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 ROOM_5_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
129 ROOM_6_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.021 0.886   9.34 13.94 9.34 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
130 ROOM_6_FLR_3_WALL_NORTH_WINDOW Window ROOM_6_FLR_3_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.487_SHGC_0.25 N/A 2.769 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
131 ROOM_6_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.021 0.886   17.43 26.01 17.43 90.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
132 ROOM_6_FLR_3_WALL_EAST_WINDOW Window ROOM_6_FLR_3_WALL_EAST Window5 Detailed Fenestration RESWINDOW_U_0.487_SHGC_0.25 N/A 2.769 No 8.58 8.58 8.58 90.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
133 ROOM_6_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ROOM_5_FLR_3_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
134 ROOM_6_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.53 3.05 0.00 CORRIDOR_FLR_3_WALL_4_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
135 ROOM_6_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.318 0.295   39.02 39.02 39.02 0.00 180.00 4.57 8.53 0.00 ROOM_6_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
136 ROOM_6_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.318 0.300   39.02 39.02 39.02 180.00 0.00 4.57 8.53 0.00 ROOM_6_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
137 ROOM_6_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.03 78.03 78.03 0.00 90.00 78.03 1.00 0.00 ROOM_6_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
138 CORRIDOR_FLR_3_WALL_1_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.167 0.994   11.83 17.65 11.83 0.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
139 CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW Window CORRIDOR_FLR_3_WALL_1_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.45_SHGC_0.25 N/A 2.557 No 5.82 5.82 5.82 0.00 90.00 4.78 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
140 CORRIDOR_FLR_3_WALL_2_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.167 0.994   4.35 6.50 4.35 0.00 90.00 2.13 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
141 CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW Window CORRIDOR_FLR_3_WALL_2_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.45_SHGC_0.25 N/A 2.557 No 2.15 2.15 2.15 0.00 90.00 1.76 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
142 CORRIDOR_FLR_3_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.167 0.994   4.36 6.50 4.36 180.00 90.00 2.13 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
143 CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW Window CORRIDOR_FLR_3_WALL_1_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.45_SHGC_0.25 N/A 2.557 No 2.15 2.15 2.15 180.00 90.00 1.76 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
144 CORRIDOR_FLR_3_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.167 0.994   11.83 17.65 11.83 180.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
145 CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW Window CORRIDOR_FLR_3_WALL_2_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.45_SHGC_0.25 N/A 2.557 No 5.82 5.82 5.82 180.00 90.00 4.78 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
146 CORRIDOR_FLR_3_WALL_3_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   211.82 211.82 211.82 0.00 90.00 69.50 3.05 0.00 CORRIDOR_FLR_3_WALL_3_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
147 CORRIDOR_FLR_3_WALL_1_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_1_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
148 CORRIDOR_FLR_3_WALL_2_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_2_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
149 CORRIDOR_FLR_3_WALL_3_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.54 3.05 0.00 ROOM_5_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
150 CORRIDOR_FLR_3_WALL_4_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.53 3.05 0.00 ROOM_6_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
151 CORRIDOR_FLR_3_WALL_3_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   211.82 211.82 211.82 180.00 90.00 69.49 3.05 0.00 CORRIDOR_FLR_3_WALL_3_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
152 CORRIDOR_FLR_3_WALL_1_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_1_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
153 CORRIDOR_FLR_3_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
154 CORRIDOR_FLR_3_WALL_3_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.54 3.05 0.00 ROOM_1_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
155 CORRIDOR_FLR_3_WALL_4_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.53 3.05 0.00 ROOM_2_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
156 CORRIDOR_FLR_3_FLOOR_1 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.318 0.295   74.32 74.32 74.32 180.00 180.00 8.62 8.62 0.00 CORRIDOR_FLR_3_FLOOR_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
157 CORRIDOR_FLR_3_FLOOR_2 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.318 0.295   240.77 240.77 240.77 270.00 180.00 3.66 65.84 0.00 CORRIDOR_FLR_3_FLOOR_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
158 CORRIDOR_FLR_3_FLOOR_3 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.318 0.295   74.32 74.32 74.32 90.00 180.00 8.62 8.62 0.00 CORRIDOR_FLR_3_FLOOR_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
159 CORRIDOR_FLR_3_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.318 0.300   74.32 74.32 74.32 90.00 0.00 8.62 8.62 0.00 CORRIDOR_FLR_3_CEILING_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
160 CORRIDOR_FLR_3_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.318 0.300   240.77 240.77 240.77 90.00 0.00 3.66 65.84 0.00 CORRIDOR_FLR_3_CEILING_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
161 CORRIDOR_FLR_3_CEILING_3 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.318 0.300   74.32 74.32 74.32 90.00 0.00 8.62 8.62 0.00 CORRIDOR_FLR_3_CEILING_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
162 CORRIDOR_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   778.81 778.81 778.81 0.00 90.00 778.81 1.00 0.00 CORRIDOR_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
163 ROOM_1_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.034 0.896   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
164 ROOM_1_FLR_6_WALL_SOUTH_WINDOW Window ROOM_1_FLR_6_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.487_SHGC_0.25 N/A 2.769 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
165 ROOM_1_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.034 0.896   17.43 26.01 17.43 270.00 90.00 8.54 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
166 ROOM_1_FLR_6_WALL_WEST_WINDOW Window ROOM_1_FLR_6_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.487_SHGC_0.25 N/A 2.769 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
167 ROOM_1_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ROOM_2_FLR_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
168 ROOM_1_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.54 3.05 0.00 ROOM_1_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
169 ROOM_1_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.318 0.295   39.02 39.02 39.02 0.00 180.00 4.57 8.54 0.00 ROOM_1_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
170 ROOM_1_FLR_6_CEILING Roof   CTF - ConductionTransferFunction RES_ROOF 0.228 0.219   39.02 39.02 39.02 180.00 0.00 4.57 8.54 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
171 ROOM_1_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 ROOM_1_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
172 ROOM_2_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.034 0.896   9.34 13.94 9.34 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
173 ROOM_2_FLR_6_WALL_NORTH_WINDOW Window ROOM_2_FLR_6_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.487_SHGC_0.25 N/A 2.769 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
174 ROOM_2_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.034 0.896   17.43 26.01 17.43 270.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
175 ROOM_2_FLR_6_WALL_WEST_WINDOW Window ROOM_2_FLR_6_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.487_SHGC_0.25 N/A 2.769 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
176 ROOM_2_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.53 3.05 0.00 ROOM_2_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
177 ROOM_2_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ROOM_1_FLR_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
178 ROOM_2_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.318 0.295   39.02 39.02 39.02 0.00 180.00 4.57 8.53 0.00 ROOM_2_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
179 ROOM_2_FLR_6_CEILING Roof   CTF - ConductionTransferFunction RES_ROOF 0.228 0.219   39.02 39.02 39.02 180.00 0.00 4.57 8.53 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
180 ROOM_2_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.03 78.03 78.03 0.00 90.00 78.03 1.00 0.00 ROOM_2_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
181 ROOM_3_MULT9_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.034 0.896   13.70 20.44 13.70 180.00 90.00 6.71 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
182 ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW Window ROOM_3_MULT9_FLR_6_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.487_SHGC_0.25 N/A 2.769 No 6.74 6.74 6.74 180.00 90.00 5.53 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
183 ROOM_3_MULT9_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 0.00 90.00 6.71 3.05 0.00 ROOM_3_MULT9_FLR_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
184 ROOM_3_MULT9_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 90.00 90.00 3.66 3.05 0.00 ROOM_3_MULT9_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
185 ROOM_3_MULT9_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 270.00 90.00 3.66 3.05 0.00 ROOM_3_MULT9_FLR_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
186 ROOM_3_MULT9_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.318 0.295   24.53 24.53 24.53 0.00 180.00 6.71 3.66 0.00 ROOM_3_MULT9_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
187 ROOM_3_MULT9_FLR_6_CEILING Roof   CTF - ConductionTransferFunction RES_ROOF 0.228 0.219   24.53 24.53 24.53 180.00 0.00 6.71 3.66 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
188 ROOM_3_MULT9_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   49.06 49.06 49.06 0.00 90.00 49.06 1.00 0.00 ROOM_3_MULT9_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
189 BANQUET_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.181 1.004   65.36 97.55 65.36 0.00 90.00 32.00 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
190 BANQUET_FLR_6_WALL_NORTH_WINDOW Window BANQUET_FLR_6_WALL_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.45_SHGC_0.25 N/A 2.557 No 32.19 32.19 32.19 0.00 90.00 26.40 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
191 BANQUET_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 CORRIDOR_FLR_6_WALL_3_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
192 BANQUET_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   97.55 97.55 97.55 180.00 90.00 32.00 3.05 0.00 CORRIDOR_FLR_6_WALL_3_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
193 BANQUET_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 CORRIDOR_FLR_6_WALL_1_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
194 BANQUET_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.318 0.295   331.66 331.66 331.66 0.00 180.00 32.00 10.36 0.00 BANQUET_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
195 BANQUET_FLR_6_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   331.66 331.66 331.66 180.00 0.00 32.00 10.36 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
196 BANQUET_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   663.31 663.31 663.31 0.00 90.00 663.31 1.00 0.00 BANQUET_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
197 DINING_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.181 1.004   65.36 97.55 65.36 0.00 90.00 32.00 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
198 DINING_FLR_6_WALL_NORTH_WINDOW Window DINING_FLR_6_WALL_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.45_SHGC_0.25 N/A 2.557 No 32.19 32.19 32.19 0.00 90.00 26.40 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
199 DINING_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 KITCHEN_FLR_6_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
200 DINING_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   97.55 97.55 97.55 180.00 90.00 32.00 3.05 0.00 DINING_FLR_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
201 DINING_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 CORRIDOR_FLR_6_WALL_2_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
202 DINING_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.318 0.295   331.66 331.66 331.66 0.00 180.00 32.00 10.36 0.00 DINING_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
203 DINING_FLR_6_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   331.66 331.66 331.66 180.00 0.00 32.00 10.36 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
204 DINING_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   663.31 663.31 663.31 0.00 90.00 663.31 1.00 0.00 DINING_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
205 KITCHEN_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.181 1.004   16.77 21.37 16.77 0.00 90.00 7.01 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
206 KITCHEN_FLR_6_WALL_NORTH_WINDOW Window KITCHEN_FLR_6_WALL_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.45_SHGC_0.25 N/A 2.557 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
207 KITCHEN_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.181 1.004   34.86 52.03 34.86 90.00 90.00 17.07 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
208 KITCHEN_FLR_6_WALL_EAST_WINDOW Window KITCHEN_FLR_6_WALL_EAST Window5 Detailed Fenestration NONRESWINDOW_U_0.45_SHGC_0.25 N/A 2.557 No 17.17 17.17 17.17 90.00 90.00 14.08 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
209 KITCHEN_FLR_6_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.181 1.004   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
210 KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW Window KITCHEN_FLR_6_WALL_1_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.45_SHGC_0.25 N/A 2.557 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
211 KITCHEN_FLR_6_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 180.00 90.00 2.44 3.05 0.00 KITCHEN_FLR_6_WALL_2_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
212 KITCHEN_FLR_6_WALL_1_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_6_WALL_3_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
213 KITCHEN_FLR_6_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 DINING_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
214 KITCHEN_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.318 0.295   103.30 103.30 103.30 180.00 180.00 10.16 10.16 0.00 KITCHEN_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
215 KITCHEN_FLR_6_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   103.30 103.30 103.30 270.00 0.00 10.16 10.16 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 6
216 KITCHEN_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   206.61 206.61 206.61 0.00 90.00 206.61 1.00 0.00 KITCHEN_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
217 CORRIDOR_FLR_6_WALL_1_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.181 1.004   11.83 17.65 11.83 0.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
218 CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW Window CORRIDOR_FLR_6_WALL_1_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.45_SHGC_0.25 N/A 2.557 No 5.82 5.82 5.82 0.00 90.00 4.78 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
219 CORRIDOR_FLR_6_WALL_2_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.181 1.004   10.58 15.79 10.58 0.00 90.00 5.18 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
220 CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW Window CORRIDOR_FLR_6_WALL_2_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.45_SHGC_0.25 N/A 2.557 No 5.21 5.21 5.21 0.00 90.00 4.27 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
221 CORRIDOR_FLR_6_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.181 1.004   34.86 52.03 34.86 180.00 90.00 17.07 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
222 CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW Window CORRIDOR_FLR_6_WALL_2_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.45_SHGC_0.25 N/A 2.557 No 17.17 17.17 17.17 180.00 90.00 14.08 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
223 CORRIDOR_FLR_6_WALL_3_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   97.55 97.55 97.55 0.00 90.00 32.00 3.05 0.00 BANQUET_FLR_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
224 CORRIDOR_FLR_6_WALL_4_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   104.98 104.98 104.98 0.00 90.00 34.44 3.05 0.00 CORRIDOR_FLR_6_WALL_4_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
225 CORRIDOR_FLR_6_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   183.95 183.95 183.95 180.00 90.00 60.35 3.05 0.00 CORRIDOR_FLR_6_WALL_1_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
226 CORRIDOR_FLR_6_WALL_1_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 270.00 90.00 3.66 3.05 0.00 CORRIDOR_FLR_6_WALL_1_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
227 CORRIDOR_FLR_6_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   40.88 40.88 40.88 270.00 90.00 13.41 3.05 0.00 CORRIDOR_FLR_6_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
228 CORRIDOR_FLR_6_WALL_3_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 BANQUET_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
229 CORRIDOR_FLR_6_WALL_1_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 BANQUET_FLR_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
230 CORRIDOR_FLR_6_WALL_2_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 DINING_FLR_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
231 CORRIDOR_FLR_6_WALL_3_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 KITCHEN_FLR_6_WALL_1_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
232 CORRIDOR_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.318 0.295   412.12 412.12 412.12 180.00 180.00 20.30 20.30 0.00 CORRIDOR_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 12
233 CORRIDOR_FLR_6_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   244.71 244.71 244.71 90.00 0.00 15.64 15.64 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 8
234 CORRIDOR_FLR_6_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   167.42 167.42 167.42 270.00 0.00 12.94 12.94 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 6
235 CORRIDOR_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   824.25 824.25 824.25 0.00 90.00 824.25 1.00 0.00 CORRIDOR_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 BASEMENT RunPeriod: RUNPERIOD 1 2.1524618771E-002 2.2478803277E-002 Pass Pass 8.8072284782E-003 1.8743785847E-002 Pass Pass
2 RETAIL_1_FLR_1 RunPeriod: RUNPERIOD 1 2.1406676064E-002 4.8179984240E-002 Pass Pass 4.1231077116E-002 5.1189906769E-002 Pass Pass
3 RETAIL_2_FLR_1 RunPeriod: RUNPERIOD 1 3.2397223257E-002 3.0109176735E-002 Pass Pass 1.0580351007E-002 2.1523934612E-002 Pass Pass
4 MECH_FLR_1 RunPeriod: RUNPERIOD 1 1.4146102827E-002 1.4141506055E-002 Pass Pass 1.3412105433E-002 2.8019856193E-002 Pass Pass
5 STORAGE_FLR_1 RunPeriod: RUNPERIOD 1 5.7013892567E-003 8.7915192689E-003 Pass Pass 1.5471318766E-002 2.4094391522E-002 Pass Pass
6 LAUNDRY_FLR_1 RunPeriod: RUNPERIOD 1 9.5334337534E-002 0.2285272878 Pass Pass 1.9678442991E-002 4.9397896868E-002 Pass Pass
7 CAFE_FLR_1 RunPeriod: RUNPERIOD 1 7.3398419037E-002 7.7871581439E-002 Pass Pass 1.4862963151E-002 2.4450665847E-002 Pass Pass
8 LOBBY_FLR_1 RunPeriod: RUNPERIOD 1 4.6291185835E-002 4.4317012408E-002 Pass Pass 1.0593494479E-002 2.0422393693E-002 Pass Pass
9 ROOM_1_FLR_3 RunPeriod: RUNPERIOD 1 3.6482474648E-002 0.1096074918 Pass Pass 0.3602964626 1.0870287748 Pass Pass
10 ROOM_2_FLR_3 RunPeriod: RUNPERIOD 1 2.1991052299E-002 4.8911735693E-002 Pass Pass 0.2728631308 1.7401080748 Pass Pass
11 ROOM_3_MULT19_FLR_3 RunPeriod: RUNPERIOD 1 4.0212379993E-002 6.4153802777E-002 Pass Pass 0.2552684594 1.8096340210 Pass Pass
12 ROOM_4_MULT19_FLR_3 RunPeriod: RUNPERIOD 1 5.0981869462E-002 0.1502847602 Pass Pass 0.2432158522 1.0820105097 Pass Pass
13 ROOM_5_FLR_3 RunPeriod: RUNPERIOD 1 5.2875061117E-002 0.2000539311 Pass Pass 0.6759221493 3.8335816061 Pass Pass
14 ROOM_6_FLR_3 RunPeriod: RUNPERIOD 1 3.8441327788E-002 0.1676594035 Pass Pass 0.3306127618 1.0063370982 Pass Pass
15 CORRIDOR_FLR_3 RunPeriod: RUNPERIOD 1 6.5942903021E-003 1.0095049774E-002 Pass Pass 1.9054565049E-002 3.1817014708E-002 Pass Pass
16 ROOM_1_FLR_6 RunPeriod: RUNPERIOD 1 3.4875875723E-002 7.8140155925E-002 Pass Pass 0.2176887800 0.7451261291 Pass Pass
17 ROOM_2_FLR_6 RunPeriod: RUNPERIOD 1 3.7533047364E-002 0.1012068992 Pass Pass 0.1458467658 0.6096772121 Pass Pass
18 ROOM_3_MULT9_FLR_6 RunPeriod: RUNPERIOD 1 7.9990790571E-002 0.2410266724 Pass Pass 0.2167175798 0.5224651680 Pass Pass
19 BANQUET_FLR_6 RunPeriod: RUNPERIOD 1 4.1443793852E-002 7.2372223782E-002 Pass Pass 1.3062576154E-002 3.5278577844E-002 Pass Pass
20 DINING_FLR_6 RunPeriod: RUNPERIOD 1 3.1581463035E-002 6.1737117813E-002 Pass Pass 1.3796962788E-002 3.6647373806E-002 Pass Pass
21 KITCHEN_FLR_6 RunPeriod: RUNPERIOD 1 3.1286014319E-002 9.7163700724E-002 Pass Pass 2.1106511863E-002 3.9424087504E-002 Pass Pass
22 CORRIDOR_FLR_6 RunPeriod: RUNPERIOD 1 1.0772594172E-002 1.4738655670E-002 Pass Pass 1.6173074083E-002 2.0726433822E-002 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:51

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 3549.09 37.84 1069.27 4336.09 4076.46 13068.75



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:51

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 3.80 0.00 3.80 Wetbulb [C] 3.00 120.00
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 31.30 8.90 18.40 Wetbulb [C] 4.10 280.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 2.00 2      
Feb 59.00 53      
Mar 58.58 43      
Apr 46.42 14      
May 18.00 12      
Jun 0.00 0      
Jul 0.00 0      
Aug 0.00 0      
Sep 3.00 6      
Oct 0.00 0      
Nov 18.00 12      
Dec 4.00 4      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:51

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_NORTH BASEMENT_WALL_NORTH_CFACTOR 1.00 0.845 0.940 211.13 211.13 0.00 90.00 N
BASEMENT_WALL_EAST BASEMENT_WALL_EAST_CFACTOR 1.00 0.845 0.940 55.76 55.76 90.00 90.00 E
BASEMENT_WALL_SOUTH BASEMENT_WALL_SOUTH_CFACTOR 1.00 0.845 0.940 211.13 211.13 180.00 90.00 S
BASEMENT_WALL_WEST BASEMENT_WALL_WEST_CFACTOR 1.00 0.845 0.940 55.76 55.76 270.00 90.00 W
RETAIL_1_FLR_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.839 0.959 45.89 22.63 180.00 90.00 S
RETAIL_1_FLR_1_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.839 0.959 22.95 22.95 270.00 90.00 W
RETAIL_1_FLR_1_CEILING NONRES_ROOF 0.55 0.221 0.228 67.07 67.07 180.00 0.00  
RETAIL_2_FLR_1_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.839 0.959 26.57 24.62 270.00 90.00 W
MECH_FLR_1_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.839 0.959 62.80 62.80 0.00 90.00 N
STORAGE_FLR_1_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.839 0.959 36.23 28.80 0.00 90.00 N
LAUNDRY_FLR_1_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.839 0.959 18.12 18.12 0.00 90.00 N
LAUNDRY_FLR_1_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.839 0.959 67.63 65.68 90.00 90.00 E
CAFE_FLR_1_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.839 0.959 22.95 21.00 90.00 90.00 E
CAFE_FLR_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.839 0.959 129.23 63.73 180.00 90.00 S
CAFE_FLR_1_CEILING NONRES_ROOF 0.55 0.221 0.228 188.86 188.86 180.00 0.00  
LOBBY_FLR_1_WALL_1_NORTH NONRES_EXT_WALL_GRD 0.30 0.839 0.959 213.77 209.87 0.00 90.00 N
LOBBY_FLR_1_WALL_2_NORTH NONRES_EXT_WALL_GRD 0.30 0.839 0.959 12.08 12.08 0.00 90.00 N
LOBBY_FLR_1_WALL_1_SOUTH NONRES_EXT_WALL_GRD 0.30 0.839 0.959 167.88 82.79 180.00 90.00 S
LOBBY_FLR_1_WALL_1_WEST NONRES_EXT_WALL_GRD 0.30 0.839 0.959 41.06 41.06 270.00 90.00 W
LOBBY_FLR_1_CEILING_2 NONRES_ROOF 0.55 0.221 0.228 245.35 245.35 180.00 0.00  
ROOM_1_FLR_3_WALL_SOUTH RES_EXT_WALL_MID 0.30 0.886 1.021 55.74 37.35 180.00 90.00 S
ROOM_1_FLR_3_WALL_WEST RES_EXT_WALL_MID 0.30 0.886 1.021 104.06 69.72 270.00 90.00 W
ROOM_2_FLR_3_WALL_NORTH RES_EXT_WALL_MID 0.30 0.886 1.021 55.74 37.35 0.00 90.00 N
ROOM_2_FLR_3_WALL_WEST RES_EXT_WALL_MID 0.30 0.886 1.021 104.05 69.71 270.00 90.00 W
ROOM_3_MULT19_FLR_3_WALL_SOUTH RES_EXT_WALL_MID 0.30 0.886 1.021 847.14 567.58 180.00 90.00 S
ROOM_4_MULT19_FLR_3_WALL_NORTH RES_EXT_WALL_MID 0.30 0.886 1.021 847.37 567.71 0.00 90.00 N
ROOM_5_FLR_3_WALL_EAST RES_EXT_WALL_MID 0.30 0.886 1.021 104.06 69.72 90.00 90.00 E
ROOM_5_FLR_3_WALL_SOUTH RES_EXT_WALL_MID 0.30 0.886 1.021 55.74 37.35 180.00 90.00 S
ROOM_6_FLR_3_WALL_NORTH RES_EXT_WALL_MID 0.30 0.886 1.021 55.74 37.35 0.00 90.00 N
ROOM_6_FLR_3_WALL_EAST RES_EXT_WALL_MID 0.30 0.886 1.021 104.05 69.71 90.00 90.00 E
CORRIDOR_FLR_3_WALL_1_NORTH NONRES_EXT_WALL_MID 0.30 0.994 1.167 70.60 47.31 0.00 90.00 N
CORRIDOR_FLR_3_WALL_2_NORTH NONRES_EXT_WALL_MID 0.30 0.994 1.167 26.01 17.42 0.00 90.00 N
CORRIDOR_FLR_3_WALL_1_SOUTH NONRES_EXT_WALL_MID 0.30 0.994 1.167 26.02 17.43 180.00 90.00 S
CORRIDOR_FLR_3_WALL_2_SOUTH NONRES_EXT_WALL_MID 0.30 0.994 1.167 70.60 47.31 180.00 90.00 S
ROOM_1_FLR_6_WALL_SOUTH RES_EXT_WALL_TOP 0.30 0.896 1.034 13.94 9.34 180.00 90.00 S
ROOM_1_FLR_6_WALL_WEST RES_EXT_WALL_TOP 0.30 0.896 1.034 26.01 17.43 270.00 90.00 W
ROOM_1_FLR_6_CEILING RES_ROOF 0.55 0.221 0.228 39.02 39.02 180.00 0.00  
ROOM_2_FLR_6_WALL_NORTH RES_EXT_WALL_TOP 0.30 0.896 1.034 13.94 9.34 0.00 90.00 N
ROOM_2_FLR_6_WALL_WEST RES_EXT_WALL_TOP 0.30 0.896 1.034 26.01 17.43 270.00 90.00 W
ROOM_2_FLR_6_CEILING RES_ROOF 0.55 0.221 0.228 39.02 39.02 180.00 0.00  
ROOM_3_MULT9_FLR_6_WALL_SOUTH RES_EXT_WALL_TOP 0.30 0.896 1.034 183.96 123.26 180.00 90.00 S
ROOM_3_MULT9_FLR_6_CEILING RES_ROOF 0.55 0.221 0.228 220.77 220.77 180.00 0.00  
BANQUET_FLR_6_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.004 1.181 97.55 65.36 0.00 90.00 N
BANQUET_FLR_6_CEILING NONRES_ROOF 0.55 0.221 0.228 331.66 331.66 180.00 0.00  
DINING_FLR_6_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.004 1.181 97.55 65.36 0.00 90.00 N
DINING_FLR_6_CEILING NONRES_ROOF 0.55 0.221 0.228 331.66 331.66 180.00 0.00  
KITCHEN_FLR_6_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.004 1.181 21.37 16.77 0.00 90.00 N
KITCHEN_FLR_6_WALL_EAST NONRES_EXT_WALL_TOP 0.30 1.004 1.181 52.03 34.86 90.00 90.00 E
KITCHEN_FLR_6_WALL_1_SOUTH NONRES_EXT_WALL_TOP 0.30 1.004 1.181 13.94 9.34 180.00 90.00 S
KITCHEN_FLR_6_CEILING NONRES_ROOF 0.55 0.221 0.228 103.30 103.30 270.00 0.00  
CORRIDOR_FLR_6_WALL_1_NORTH NONRES_EXT_WALL_TOP 0.30 1.004 1.181 17.65 11.83 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_NORTH NONRES_EXT_WALL_TOP 0.30 1.004 1.181 15.79 10.58 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_SOUTH NONRES_EXT_WALL_TOP 0.30 1.004 1.181 52.03 34.86 180.00 90.00 S
CORRIDOR_FLR_6_CEILING_1 NONRES_ROOF 0.55 0.221 0.228 244.71 244.71 90.00 0.00  
CORRIDOR_FLR_6_CEILING_2 NONRES_ROOF 0.55 0.221 0.228 167.42 167.42 270.00 0.00  


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_FLOOR BASEMENT_FLOOR 0.30 1.441 2.705 1978.83 1978.83 0.00 180.00  
BASEMENT_CEILING_1 NONRES_FLOOR_CEILING 0.30 0.293 0.318 67.07 67.07 180.00 0.00  
BASEMENT_CEILING_2 NONRES_FLOOR_CEILING 0.30 0.293 0.318 77.67 77.67 180.00 0.00  
BASEMENT_CEILING_3 NONRES_FLOOR_CEILING 0.30 0.293 0.318 164.24 164.24 180.00 0.00  
BASEMENT_CEILING_4 NONRES_FLOOR_CEILING 0.30 0.293 0.318 94.76 94.76 180.00 0.00  
BASEMENT_CEILING_5 NONRES_FLOOR_CEILING 0.30 0.293 0.318 78.04 78.04 180.00 0.00  
BASEMENT_CEILING_6 NONRES_FLOOR_CEILING 0.30 0.293 0.318 188.86 188.86 180.00 0.00  
BASEMENT_CEILING_7 NONRES_FLOOR_CEILING 0.30 0.293 0.318 1088.56 1088.56 180.00 0.00  
BASEMENT_CEILING_8 NONRES_FLOOR_CEILING 0.30 0.293 0.318 219.63 219.63 90.00 0.00  
RETAIL_1_FLR_1_WALL_NORTH INT_WALL 0.30 2.511 6.299 45.89 45.89 0.00 90.00 N
RETAIL_1_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 22.95 22.95 90.00 90.00 E
RETAIL_1_FLR_1_FLOOR NONRES_FLOOR 0.30 0.293 0.318 67.07 67.07 0.00 180.00  
RETAIL_2_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 45.89 45.89 180.00 90.00 S
RETAIL_2_FLR_1_WALL_NORTH INT_WALL 0.30 2.511 6.299 45.89 45.89 0.00 90.00 N
RETAIL_2_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 26.57 26.57 90.00 90.00 E
RETAIL_2_FLR_1_FLOOR NONRES_FLOOR 0.30 0.293 0.318 77.67 77.67 0.00 180.00  
RETAIL_2_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.298 0.318 77.67 77.67 180.00 0.00  
MECH_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 41.06 41.06 90.00 90.00 E
MECH_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 62.80 62.80 180.00 90.00 S
MECH_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 41.06 41.06 270.00 90.00 W
MECH_FLR_1_FLOOR NONRES_FLOOR 0.30 0.293 0.318 164.24 164.24 0.00 180.00  
MECH_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.298 0.318 164.24 164.24 180.00 0.00  
STORAGE_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 41.06 41.06 90.00 90.00 E
STORAGE_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 36.23 36.23 180.00 90.00 S
STORAGE_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 41.06 41.06 270.00 90.00 W
STORAGE_FLR_1_FLOOR NONRES_FLOOR 0.30 0.293 0.318 94.76 94.76 0.00 180.00  
STORAGE_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.298 0.318 94.76 94.76 180.00 0.00  
LAUNDRY_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 18.12 18.12 180.00 90.00 S
LAUNDRY_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 67.63 67.63 270.00 90.00 W
LAUNDRY_FLR_1_FLOOR NONRES_FLOOR 0.30 0.293 0.318 78.04 78.04 0.00 180.00  
LAUNDRY_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.298 0.318 78.04 78.04 180.00 0.00  
CAFE_FLR_1_WALL_1_NORTH INT_WALL 0.30 2.511 6.299 111.11 111.11 0.00 90.00 N
CAFE_FLR_1_WALL_2_NORTH INT_WALL 0.30 2.511 6.299 18.12 18.12 0.00 90.00 N
CAFE_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 22.95 22.95 270.00 90.00 W
CAFE_FLR_1_FLOOR NONRES_FLOOR 0.30 0.293 0.318 188.86 188.86 0.00 180.00  
LOBBY_FLR_1_WALL_2_SOUTH INT_WALL 0.30 2.511 6.299 45.89 45.89 180.00 90.00 S
LOBBY_FLR_1_WALL_3_SOUTH INT_WALL 0.30 2.511 6.299 111.11 111.11 180.00 90.00 S
LOBBY_FLR_1_WALL_2_WEST INT_WALL 0.30 2.511 6.299 22.95 22.95 270.00 90.00 W
LOBBY_FLR_1_WALL_3_WEST INT_WALL 0.30 2.511 6.299 26.57 26.57 270.00 90.00 W
LOBBY_FLR_1_WALL_4_WEST INT_WALL 0.30 2.511 6.299 41.06 41.06 270.00 90.00 W
LOBBY_FLR_1_WALL_3_NORTH INT_WALL 0.30 2.511 6.299 62.80 62.80 0.00 90.00 N
LOBBY_FLR_1_WALL_4_NORTH INT_WALL 0.30 2.511 6.299 36.23 36.23 0.00 90.00 N
LOBBY_FLR_1_WALL_1_EAST INT_WALL 0.30 2.511 6.299 41.06 41.06 90.00 90.00 E
LOBBY_FLR_1_WALL_2_EAST INT_WALL 0.30 2.511 6.299 22.95 22.95 90.00 90.00 E
LOBBY_FLR_1_WALL_3_EAST INT_WALL 0.30 2.511 6.299 67.63 67.63 90.00 90.00 E
LOBBY_FLR_1_FLOOR_1 NONRES_FLOOR 0.30 0.293 0.318 1088.56 1088.56 180.00 180.00  
LOBBY_FLR_1_FLOOR_2 NONRES_FLOOR 0.30 0.293 0.318 219.63 219.63 90.00 180.00  
LOBBY_FLR_1_CEILING_1 NONRES_FLOOR_CEILING 0.30 0.298 0.318 1062.83 1062.83 270.00 0.00  
ROOM_1_FLR_3_WALL_NORTH INT_WALL 0.30 2.511 6.299 55.74 55.74 0.00 90.00 N
ROOM_1_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 104.06 104.06 90.00 90.00 E
ROOM_1_FLR_3_FLOOR NONRES_FLOOR 0.30 0.288 0.318 156.09 156.09 0.00 180.00  
ROOM_1_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.298 0.318 156.09 156.09 180.00 0.00  
ROOM_2_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 104.05 104.05 90.00 90.00 E
ROOM_2_FLR_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 55.74 55.74 180.00 90.00 S
ROOM_2_FLR_3_FLOOR NONRES_FLOOR 0.30 0.288 0.318 156.07 156.07 0.00 180.00  
ROOM_2_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.298 0.318 156.07 156.07 180.00 0.00  
ROOM_3_MULT19_FLR_3_WALL_NORTH INT_WALL 0.30 2.511 6.299 847.14 847.14 0.00 90.00 N
ROOM_3_MULT19_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 90.00 90.00 E
ROOM_3_MULT19_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 270.00 90.00 W
ROOM_3_MULT19_FLR_3_FLOOR NONRES_FLOOR 0.30 0.288 0.318 1863.81 1863.81 0.00 180.00  
ROOM_3_MULT19_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.298 0.318 1863.81 1863.81 180.00 0.00  
ROOM_4_MULT19_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 90.00 90.00 E
ROOM_4_MULT19_FLR_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 847.37 847.37 180.00 90.00 S
ROOM_4_MULT19_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 270.00 90.00 W
ROOM_4_MULT19_FLR_3_FLOOR NONRES_FLOOR 0.30 0.288 0.318 1864.32 1864.32 0.00 180.00  
ROOM_4_MULT19_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.298 0.318 1864.32 1864.32 180.00 0.00  
ROOM_5_FLR_3_WALL_NORTH INT_WALL 0.30 2.511 6.299 55.74 55.74 0.00 90.00 N
ROOM_5_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 104.06 104.06 270.00 90.00 W
ROOM_5_FLR_3_FLOOR NONRES_FLOOR 0.30 0.288 0.318 156.09 156.09 0.00 180.00  
ROOM_5_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.298 0.318 156.09 156.09 180.00 0.00  
ROOM_6_FLR_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 55.74 55.74 180.00 90.00 S
ROOM_6_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 104.05 104.05 270.00 90.00 W
ROOM_6_FLR_3_FLOOR NONRES_FLOOR 0.30 0.288 0.318 156.07 156.07 0.00 180.00  
ROOM_6_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.298 0.318 156.07 156.07 180.00 0.00  
CORRIDOR_FLR_3_WALL_3_NORTH INT_WALL 0.30 2.511 6.299 847.28 847.28 0.00 90.00 N
CORRIDOR_FLR_3_WALL_1_EAST INT_WALL 0.30 2.511 6.299 81.76 81.76 90.00 90.00 E
CORRIDOR_FLR_3_WALL_2_EAST INT_WALL 0.30 2.511 6.299 81.76 81.76 90.00 90.00 E
CORRIDOR_FLR_3_WALL_3_EAST INT_WALL 0.30 2.511 6.299 104.06 104.06 90.00 90.00 E
CORRIDOR_FLR_3_WALL_4_EAST INT_WALL 0.30 2.511 6.299 104.05 104.05 90.00 90.00 E
CORRIDOR_FLR_3_WALL_3_SOUTH INT_WALL 0.30 2.511 6.299 847.27 847.27 180.00 90.00 S
CORRIDOR_FLR_3_WALL_1_WEST INT_WALL 0.30 2.511 6.299 81.76 81.76 270.00 90.00 W
CORRIDOR_FLR_3_WALL_2_WEST INT_WALL 0.30 2.511 6.299 81.76 81.76 270.00 90.00 W
CORRIDOR_FLR_3_WALL_3_WEST INT_WALL 0.30 2.511 6.299 104.06 104.06 270.00 90.00 W
CORRIDOR_FLR_3_WALL_4_WEST INT_WALL 0.30 2.511 6.299 104.05 104.05 270.00 90.00 W
CORRIDOR_FLR_3_FLOOR_1 NONRES_FLOOR 0.30 0.288 0.318 297.29 297.29 180.00 180.00  
CORRIDOR_FLR_3_FLOOR_2 NONRES_FLOOR 0.30 0.288 0.318 963.06 963.06 270.00 180.00  
CORRIDOR_FLR_3_FLOOR_3 NONRES_FLOOR 0.30 0.288 0.318 297.26 297.26 90.00 180.00  
CORRIDOR_FLR_3_CEILING_1 NONRES_FLOOR_CEILING 0.30 0.298 0.318 297.29 297.29 90.00 0.00  
CORRIDOR_FLR_3_CEILING_2 NONRES_FLOOR_CEILING 0.30 0.298 0.318 963.06 963.06 90.00 0.00  
CORRIDOR_FLR_3_CEILING_3 NONRES_FLOOR_CEILING 0.30 0.298 0.318 297.26 297.26 90.00 0.00  
ROOM_1_FLR_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 13.94 13.94 0.00 90.00 N
ROOM_1_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 26.01 26.01 90.00 90.00 E
ROOM_1_FLR_6_FLOOR NONRES_FLOOR 0.30 0.288 0.318 39.02 39.02 0.00 180.00  
ROOM_2_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 26.01 26.01 90.00 90.00 E
ROOM_2_FLR_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 13.94 13.94 180.00 90.00 S
ROOM_2_FLR_6_FLOOR NONRES_FLOOR 0.30 0.288 0.318 39.02 39.02 0.00 180.00  
ROOM_3_MULT9_FLR_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 183.96 183.96 0.00 90.00 N
ROOM_3_MULT9_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 100.35 100.35 90.00 90.00 E
ROOM_3_MULT9_FLR_6_WALL_WEST INT_WALL 0.30 2.511 6.299 100.35 100.35 270.00 90.00 W
ROOM_3_MULT9_FLR_6_FLOOR NONRES_FLOOR 0.30 0.288 0.318 220.77 220.77 0.00 180.00  
BANQUET_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
BANQUET_FLR_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 97.55 97.55 180.00 90.00 S
BANQUET_FLR_6_WALL_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
BANQUET_FLR_6_FLOOR NONRES_FLOOR 0.30 0.288 0.318 331.66 331.66 0.00 180.00  
DINING_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
DINING_FLR_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 97.55 97.55 180.00 90.00 S
DINING_FLR_6_WALL_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
DINING_FLR_6_FLOOR NONRES_FLOOR 0.30 0.288 0.318 331.66 331.66 0.00 180.00  
KITCHEN_FLR_6_WALL_2_SOUTH INT_WALL 0.30 2.511 6.299 7.43 7.43 180.00 90.00 S
KITCHEN_FLR_6_WALL_1_WEST INT_WALL 0.30 2.511 6.299 20.44 20.44 270.00 90.00 W
KITCHEN_FLR_6_WALL_2_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
KITCHEN_FLR_6_FLOOR NONRES_FLOOR 0.30 0.288 0.318 103.30 103.30 180.00 180.00  
CORRIDOR_FLR_6_WALL_3_NORTH INT_WALL 0.30 2.511 6.299 97.55 97.55 0.00 90.00 N
CORRIDOR_FLR_6_WALL_4_NORTH INT_WALL 0.30 2.511 6.299 104.98 104.98 0.00 90.00 N
CORRIDOR_FLR_6_WALL_1_SOUTH INT_WALL 0.30 2.511 6.299 183.95 183.95 180.00 90.00 S
CORRIDOR_FLR_6_WALL_1_WEST INT_WALL 0.30 2.511 6.299 11.15 11.15 270.00 90.00 W
CORRIDOR_FLR_6_WALL_2_WEST INT_WALL 0.30 2.511 6.299 40.88 40.88 270.00 90.00 W
CORRIDOR_FLR_6_WALL_3_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
CORRIDOR_FLR_6_WALL_1_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
CORRIDOR_FLR_6_WALL_2_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
CORRIDOR_FLR_6_WALL_3_EAST INT_WALL 0.30 2.511 6.299 20.44 20.44 90.00 90.00 E
CORRIDOR_FLR_6_FLOOR NONRES_FLOOR 0.30 0.288 0.318 412.12 412.12 180.00 180.00  
BASEMENT_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3957.66   0.00 90.00 N
RETAIL_1_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 134.14   0.00 90.00 N
RETAIL_2_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 155.34   0.00 90.00 N
MECH_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 328.49   0.00 90.00 N
STORAGE_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 189.52   0.00 90.00 N
LAUNDRY_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 156.08   0.00 90.00 N
CAFE_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 377.72   0.00 90.00 N
LOBBY_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 2616.37   0.00 90.00 N
ROOM_1_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.18   0.00 90.00 N
ROOM_2_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.14   0.00 90.00 N
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3727.63   0.00 90.00 N
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3728.64   0.00 90.00 N
ROOM_5_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.18   0.00 90.00 N
ROOM_6_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.14   0.00 90.00 N
CORRIDOR_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3115.24   0.00 90.00 N
ROOM_1_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 78.04   0.00 90.00 N
ROOM_2_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 78.03   0.00 90.00 N
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 441.55   0.00 90.00 N
BANQUET_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 663.31   0.00 90.00 N
DINING_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 663.31   0.00 90.00 N
KITCHEN_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 206.61   0.00 90.00 N
CORRIDOR_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 824.25   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.45_SHGC_0.25   23.26 0.00 0.00 23.26 23.26 2.557 0.251 0.276             No RETAIL_1_FLR_1_WALL_SOUTH 180.00 90.00 S
CAFE_FLR_1_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.45_SHGC_0.25   65.50 0.00 0.00 65.50 65.50 2.557 0.251 0.276             No CAFE_FLR_1_WALL_SOUTH 180.00 90.00 S
LOBBY_FLR_1_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.45_SHGC_0.25   85.08 0.00 0.00 85.08 85.08 2.557 0.251 0.276             No LOBBY_FLR_1_WALL_1_SOUTH 180.00 90.00 S
ROOM_1_FLR_3_WALL_SOUTH_WINDOW RESWINDOW_U_0.487_SHGC_0.25   4.60 0.00 0.00 4.60 18.40 2.769 0.251 0.276             No ROOM_1_FLR_3_WALL_SOUTH 180.00 90.00 S
ROOM_1_FLR_3_WALL_WEST_WINDOW RESWINDOW_U_0.487_SHGC_0.25   8.58 0.00 0.00 8.58 34.34 2.769 0.251 0.276             No ROOM_1_FLR_3_WALL_WEST 270.00 90.00 W
ROOM_2_FLR_3_WALL_NORTH_WINDOW RESWINDOW_U_0.487_SHGC_0.25   4.60 0.00 0.00 4.60 18.40 2.769 0.251 0.276             No ROOM_2_FLR_3_WALL_NORTH 0.00 90.00 N
ROOM_2_FLR_3_WALL_WEST_WINDOW RESWINDOW_U_0.487_SHGC_0.25   8.58 0.00 0.00 8.58 34.34 2.769 0.251 0.276             No ROOM_2_FLR_3_WALL_WEST 270.00 90.00 W
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW RESWINDOW_U_0.487_SHGC_0.25   3.68 0.00 0.00 3.68 279.56 2.769 0.251 0.276             No ROOM_3_MULT19_FLR_3_WALL_SOUTH 180.00 90.00 S
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW RESWINDOW_U_0.487_SHGC_0.25   3.68 0.00 0.00 3.68 279.65 2.769 0.251 0.276             No ROOM_4_MULT19_FLR_3_WALL_NORTH 0.00 90.00 N
ROOM_5_FLR_3_WALL_EAST_WINDOW RESWINDOW_U_0.487_SHGC_0.25   8.58 0.00 0.00 8.58 34.34 2.769 0.251 0.276             No ROOM_5_FLR_3_WALL_EAST 90.00 90.00 E
ROOM_5_FLR_3_WALL_SOUTH_WINDOW RESWINDOW_U_0.487_SHGC_0.25   4.60 0.00 0.00 4.60 18.40 2.769 0.251 0.276             No ROOM_5_FLR_3_WALL_SOUTH 180.00 90.00 S
ROOM_6_FLR_3_WALL_NORTH_WINDOW RESWINDOW_U_0.487_SHGC_0.25   4.60 0.00 0.00 4.60 18.40 2.769 0.251 0.276             No ROOM_6_FLR_3_WALL_NORTH 0.00 90.00 N
ROOM_6_FLR_3_WALL_EAST_WINDOW RESWINDOW_U_0.487_SHGC_0.25   8.58 0.00 0.00 8.58 34.34 2.769 0.251 0.276             No ROOM_6_FLR_3_WALL_EAST 90.00 90.00 E
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW NONRESWINDOW_U_0.45_SHGC_0.25   5.82 0.00 0.00 5.82 23.30 2.557 0.251 0.276             No CORRIDOR_FLR_3_WALL_1_NORTH 0.00 90.00 N
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW NONRESWINDOW_U_0.45_SHGC_0.25   2.15 0.00 0.00 2.15 8.59 2.557 0.251 0.276             No CORRIDOR_FLR_3_WALL_2_NORTH 0.00 90.00 N
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW NONRESWINDOW_U_0.45_SHGC_0.25   2.15 0.00 0.00 2.15 8.58 2.557 0.251 0.276             No CORRIDOR_FLR_3_WALL_1_SOUTH 180.00 90.00 S
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW NONRESWINDOW_U_0.45_SHGC_0.25   5.82 0.00 0.00 5.82 23.30 2.557 0.251 0.276             No CORRIDOR_FLR_3_WALL_2_SOUTH 180.00 90.00 S
ROOM_1_FLR_6_WALL_SOUTH_WINDOW RESWINDOW_U_0.487_SHGC_0.25   4.60 0.00 0.00 4.60 4.60 2.769 0.251 0.276             No ROOM_1_FLR_6_WALL_SOUTH 180.00 90.00 S
ROOM_1_FLR_6_WALL_WEST_WINDOW RESWINDOW_U_0.487_SHGC_0.25   8.58 0.00 0.00 8.58 8.58 2.769 0.251 0.276             No ROOM_1_FLR_6_WALL_WEST 270.00 90.00 W
ROOM_2_FLR_6_WALL_NORTH_WINDOW RESWINDOW_U_0.487_SHGC_0.25   4.60 0.00 0.00 4.60 4.60 2.769 0.251 0.276             No ROOM_2_FLR_6_WALL_NORTH 0.00 90.00 N
ROOM_2_FLR_6_WALL_WEST_WINDOW RESWINDOW_U_0.487_SHGC_0.25   8.58 0.00 0.00 8.58 8.58 2.769 0.251 0.276             No ROOM_2_FLR_6_WALL_WEST 270.00 90.00 W
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW RESWINDOW_U_0.487_SHGC_0.25   6.74 0.00 0.00 6.74 60.70 2.769 0.251 0.276             No ROOM_3_MULT9_FLR_6_WALL_SOUTH 180.00 90.00 S
BANQUET_FLR_6_WALL_NORTH_WINDOW NONRESWINDOW_U_0.45_SHGC_0.25   32.19 0.00 0.00 32.19 32.19 2.557 0.251 0.276             No BANQUET_FLR_6_WALL_NORTH 0.00 90.00 N
DINING_FLR_6_WALL_NORTH_WINDOW NONRESWINDOW_U_0.45_SHGC_0.25   32.19 0.00 0.00 32.19 32.19 2.557 0.251 0.276             No DINING_FLR_6_WALL_NORTH 0.00 90.00 N
KITCHEN_FLR_6_WALL_NORTH_WINDOW NONRESWINDOW_U_0.45_SHGC_0.25   4.60 0.00 0.00 4.60 4.60 2.557 0.251 0.276             No KITCHEN_FLR_6_WALL_NORTH 0.00 90.00 N
KITCHEN_FLR_6_WALL_EAST_WINDOW NONRESWINDOW_U_0.45_SHGC_0.25   17.17 0.00 0.00 17.17 17.17 2.557 0.251 0.276             No KITCHEN_FLR_6_WALL_EAST 90.00 90.00 E
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW NONRESWINDOW_U_0.45_SHGC_0.25   4.60 0.00 0.00 4.60 4.60 2.557 0.251 0.276             No KITCHEN_FLR_6_WALL_1_SOUTH 180.00 90.00 S
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW NONRESWINDOW_U_0.45_SHGC_0.25   5.82 0.00 0.00 5.82 5.82 2.557 0.251 0.276             No CORRIDOR_FLR_6_WALL_1_NORTH 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW NONRESWINDOW_U_0.45_SHGC_0.25   5.21 0.00 0.00 5.21 5.21 2.557 0.251 0.276             No CORRIDOR_FLR_6_WALL_2_NORTH 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW NONRESWINDOW_U_0.45_SHGC_0.25   17.17 0.00 0.00 17.17 17.17 2.557 0.251 0.276             No CORRIDOR_FLR_6_WALL_2_SOUTH 180.00 90.00 S
Total or Average             1213.79 2.707 0.251 0.276                      
North Total or Average             432.95 2.714 0.251 0.276                      
Non-North Total or Average             780.84 2.702 0.251 0.276                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
RETAIL_2_FLR_1_WALL_WEST_DOOR SWINGING DOOR_CON 2.101 3.065 1.95 RETAIL_2_FLR_1_WALL_WEST
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR OVERHEAD DOOR_CON 1.760 2.390 7.43 STORAGE_FLR_1_WALL_NORTH
LAUNDRY_FLR_1_WALL_EAST_DOOR SWINGING DOOR_CON 2.101 3.065 1.95 LAUNDRY_FLR_1_WALL_EAST
CAFE_FLR_1_WALL_EAST_DOOR SWINGING DOOR_CON 2.101 3.065 1.95 CAFE_FLR_1_WALL_EAST
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 SWINGING DOOR_CON 2.101 3.065 1.95 LOBBY_FLR_1_WALL_1_NORTH
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 SWINGING DOOR_CON 2.101 3.065 1.95 LOBBY_FLR_1_WALL_1_NORTH


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:51

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
CAFE_FLR_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
LOBBY_FLR_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
ROOM_1_FLR_3_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
ROOM_1_FLR_3_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_2_FLR_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
ROOM_5_FLR_3_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
ROOM_6_FLR_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
ROOM_1_FLR_6_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
ROOM_1_FLR_6_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_2_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
BANQUET_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
DINING_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:51

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
BASEMENT_LIGHTS BASEMENT BASEMENT GENERAL 8.8143 1978.83 17441.96 LightsWired LTG_SCH_BASEMENT 49.32 168.00 49.26 0.0000 Y 161.29
RETAIL_1_FLR_1_LIGHTS RETAIL_1_FLR_1 RETAIL_1_FLR_1 GENERAL 11.3140 67.07 758.85 LightsWired LTG_SCH_RETAIL 51.36 168.00 51.30 0.0000 Y 7.31
RETAIL_2_FLR_1_LIGHTS RETAIL_2_FLR_1 RETAIL_2_FLR_1 GENERAL 11.3140 77.67 878.75 LightsWired LTG_SCH_RETAIL 51.36 168.00 51.30 0.0000 Y 8.46
MECH_FLR_1_LIGHTS MECH_FLR_1 MECH_FLR_1 GENERAL 4.6285 164.24 760.20 LightsWired LTG_SCH_MECHANIC 58.69 168.00 58.63 0.0000 Y 8.37
STORAGE_FLR_1_LIGHTS STORAGE_FLR_1 STORAGE_FLR_1 GENERAL 5.7199 94.76 542.02 LightsWired LTG_SCH_STORAGE 30.30 168.00 30.27 0.0000 Y 3.08
LAUNDRY_FLR_1_LIGHTS LAUNDRY_FLR_1 LAUNDRY_FLR_1 GENERAL 4.6285 78.04 361.20 LightsWired LTG_SCH_LAUNDRY 58.69 168.00 58.63 0.0000 Y 3.98
CAFE_FLR_1_LIGHTS CAFE_FLR_1 CAFE_FLR_1 GENERAL 10.0104 188.86 1890.59 LightsWired LTG_SCH_DINING 58.69 168.00 40.42 0.0000 Y 14.34
LOBBY_FLR_1_LIGHTS LOBBY_FLR_1 LOBBY_FLR_1 GENERAL 10.7639 1308.19 14081.18 LightsWired LTG_SCH_LOBBY 44.02 168.00 41.67 0.0000 Y 110.15
ROOM_1_FLR_3_LIGHTS ROOM_1_FLR_3 ROOM_1_FLR_3 GENERAL 8.2882 156.09 1293.69 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 9.24
ROOM_2_FLR_3_LIGHTS ROOM_2_FLR_3 ROOM_2_FLR_3 GENERAL 8.2882 156.07 1293.54 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 9.24
ROOM_3_MULT19_FLR_3_LIGHTS ROOM_3_MULT19_FLR_3 ROOM_3_MULT19_FLR_3 GENERAL 8.2882 1863.81 15447.65 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 110.38
ROOM_4_MULT19_FLR_3_LIGHTS ROOM_4_MULT19_FLR_3 ROOM_4_MULT19_FLR_3 GENERAL 8.2882 1864.32 15451.87 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 110.41
ROOM_5_FLR_3_LIGHTS ROOM_5_FLR_3 ROOM_5_FLR_3 GENERAL 8.2882 156.09 1293.69 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 9.24
ROOM_6_FLR_3_LIGHTS ROOM_6_FLR_3 ROOM_6_FLR_3 GENERAL 8.2882 156.07 1293.54 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 9.24
CORRIDOR_FLR_3_LIGHTS CORRIDOR_FLR_3 CORRIDOR_FLR_3 GENERAL 7.1042 1557.62 11065.59 LightsWired LTG_SCH_CORRIDOR 44.02 168.00 43.97 0.0000 Y 91.33
ROOM_1_FLR_6_LIGHTS ROOM_1_FLR_6 ROOM_1_FLR_6 GENERAL 8.2882 39.02 323.42 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 2.31
ROOM_2_FLR_6_LIGHTS ROOM_2_FLR_6 ROOM_2_FLR_6 GENERAL 8.2882 39.02 323.38 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 2.31
ROOM_3_MULT9_FLR_6_LIGHTS ROOM_3_MULT9_FLR_6 ROOM_3_MULT9_FLR_6 GENERAL 8.2882 220.77 1829.83 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 13.08
BANQUET_FLR_6_LIGHTS BANQUET_FLR_6 BANQUET_FLR_6 GENERAL 10.0104 331.66 3320.03 LightsWired LTG_SCH_DINING 58.69 168.00 50.05 0.0000 Y 31.19
DINING_FLR_6_LIGHTS DINING_FLR_6 DINING_FLR_6 GENERAL 10.0104 331.66 3320.03 LightsWired LTG_SCH_DINING 58.69 168.00 50.05 0.0000 Y 31.19
KITCHEN_FLR_6_LIGHTS KITCHEN_FLR_6 KITCHEN_FLR_6 GENERAL 11.4097 103.30 1178.68 LightsWired LTG_SCH_KITCHEN 58.69 168.00 58.63 0.0000 Y 12.97
CORRIDOR_FLR_6_LIGHTS CORRIDOR_FLR_6 CORRIDOR_FLR_6 GENERAL 7.1042 412.12 2927.80 LightsWired LTG_SCH_CORRIDOR 44.02 168.00 43.97 0.0000 Y 24.17
Interior Lighting Total       8.5566 11345.29 97077.49               457.56


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
LOBBY_FLR_1_DAYLREFPT1 LOBBY_FLR_1 LOBBY_FLR_1_DAYLCTRL SplitFlux Stepped 0.07 14081.18 985.68
LOBBY_FLR_1_DAYLREFPT2 LOBBY_FLR_1 LOBBY_FLR_1_DAYLCTRL SplitFlux Stepped 0.07 14081.18 985.68
CAFE_FLR_1_DAYLREFPT1 CAFE_FLR_1 CAFE_FLR_1_DAYLCTRL SplitFlux Stepped 0.39 1890.59 737.33
CAFE_FLR_1_DAYLREFPT2 CAFE_FLR_1 CAFE_FLR_1_DAYLCTRL SplitFlux Stepped 0.39 1890.59 737.33
DINING_FLR_6_DAYLREFPT1 DINING_FLR_6 DINING_FLR_6_DAYLCTRL SplitFlux Stepped 0.20 3320.03 664.01
DINING_FLR_6_DAYLREFPT2 DINING_FLR_6 DINING_FLR_6_DAYLCTRL SplitFlux Stepped 0.20 3320.03 664.01
BANQUET_FLR_6_DAYLREFPT1 BANQUET_FLR_6 BANQUET_FLR_6_DAYLCTRL SplitFlux Stepped 0.20 3320.03 664.01
BANQUET_FLR_6_DAYLREFPT2 BANQUET_FLR_6 BANQUET_FLR_6_DAYLCTRL SplitFlux Stepped 0.20 3320.03 664.01


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR FACADE LIGHTING 12338.45 AstronomicalClock -   83.75 83.75 193.98
Exterior Lighting Total 12338.45           193.98



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:51

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
HEATSYS1 BOILER Boiler:HotWater 271079.21 0.80        
COOLSYS1 CHILLER1 Chiller:Electric:EIR 699394.26 2.96 699394.26 2.96 4.09 13.95


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
ROOM_1_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 10708.37 15966.31 13745.90 2220.41 0.86 - 3235.93 32.82
ROOM_2_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 10317.41 15379.68 13236.70 2142.98 0.86 - 3114.53 31.59
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 65521.98 98327.12 85377.27 12949.85 0.87 - 20385.07 206.76
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 65765.34 96630.89 81659.65 14971.24 0.85 - 18745.16 190.12
ROOM_5_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 9539.76 14212.60 12223.44 1989.15 0.86 - 2872.91 29.14
ROOM_6_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 9192.76 13691.86 11771.38 1920.48 0.86 - 2765.14 28.05
ROOM_1_FLR_6 FAN COIL COOLING COIL Coil:Cooling:Water 2771.50 4133.24 3559.44 573.80 0.86 - 838.30 8.50
ROOM_2_FLR_6 FAN COIL COOLING COIL Coil:Cooling:Water 2664.21 3972.25 3419.69 552.56 0.86 - 804.98 8.16
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Coil:Cooling:Water 13255.40 19654.86 16798.67 2856.19 0.85 - 3914.85 39.71
FLR_3_DOAS COOLING COIL Coil:Cooling:Water 47946.25 51303.12 35829.51 15473.61 0.70 - 7298.17 74.02
VAV WITH REHEAT COOLING COIL Coil:Cooling:Water 461117.25 526994.00 369834.86 157159.13 0.70 - 81964.46 831.33
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
None              


DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
None                  


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
BASEMENT VAV BOX REHEAT COIL Coil:Heating:Water 6904.49 6940.20 -
RETAIL_1_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 2567.64 2579.49 -
RETAIL_2_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 1207.82 1213.81 -
MECH_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 1513.84 1520.81 -
STORAGE_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 971.37 975.78 -
LAUNDRY_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 10644.59 10699.28 -
CAFE_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 8207.96 8247.63 -
LOBBY_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 23179.43 23295.07 -
ROOM_1_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 3704.30 3989.58 -
ROOM_2_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 3704.51 3989.80 -
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 21626.49 23291.92 -
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 21641.02 23307.56 -
ROOM_5_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 3703.47 3988.69 -
ROOM_6_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 3703.68 3988.91 -
CORRIDOR_FLR_3 VAV BOX REHEAT COIL Coil:Heating:Water 10059.28 10106.81 -
ROOM_1_FLR_6 FAN COIL HEATING COIL Coil:Heating:Water 1153.43 1242.25 -
ROOM_2_FLR_6 FAN COIL HEATING COIL Coil:Heating:Water 1152.99 1241.77 -
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Coil:Heating:Water 5585.51 6015.58 -
BANQUET_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 9904.56 9954.22 -
DINING_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 10253.90 10305.36 -
KITCHEN_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 6758.61 6793.45 -
CORRIDOR_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 6157.45 6185.59 -
FLR_3_DOAS HEATING COIL Coil:Heating:Water 9427.25 7911.32 -
VAV WITH REHEAT HEATING COIL Coil:Heating:Water 97345.61 81692.19 -
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
LAUNDRY_FLR_1 EXHAUST FAN Fan:ZoneExhaust 0.39 125.00 0.24 76.61 324.68 1.00 2.78 General    
LOBBY_FLR_1 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.24 0.00 0.00 1.00 0.00 General    
ROOM_1_FLR_3 FAN COIL_FANCOILFAN Fan:OnOff 0.39 270.90 0.98 688.20 703.64 1.00 1.20 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:20:00
ROOM_2_FLR_3 FAN COIL_FANCOILFAN Fan:OnOff 0.39 270.90 0.94 662.57 703.64 1.00 1.21 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00
ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN Fan:OnOff 0.39 270.90 6.11 4297.47 703.64 1.00 0.96 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00
ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN Fan:OnOff 0.39 270.90 5.74 4036.31 703.64 1.00 0.96 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:50:00
ROOM_5_FLR_3 FAN COIL_FANCOILFAN Fan:OnOff 0.39 270.90 0.87 611.57 703.64 1.00 1.23 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:30:00
ROOM_6_FLR_3 FAN COIL_FANCOILFAN Fan:OnOff 0.39 270.90 0.84 588.81 703.64 1.00 1.24 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:10:00
ROOM_1_FLR_6 FAN COIL_FANCOILFAN Fan:OnOff 0.39 270.90 0.25 178.24 703.64 1.00 1.84 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:20:00
ROOM_2_FLR_6 FAN COIL_FANCOILFAN Fan:OnOff 0.39 270.90 0.24 171.21 703.64 1.00 1.87 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00
ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN Fan:OnOff 0.39 270.90 1.19 836.92 703.64 1.00 1.16 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00
BANQUET_FLR_6 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.87 0.00 0.00 1.00 0.00 General    
DINING_FLR_6 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.87 0.00 0.00 1.00 0.00 General    
KITCHEN_FLR_6 EXHAUST FAN Fan:ZoneExhaust 0.39 125.00 1.89 612.92 324.68 1.00 1.48 General    
FLR_3_DOAS FAN Fan:ConstantVolume 0.58 622.50 2.05 2194.93 1070.05 1.00 1.30 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00
VAV WITH REHEAT FAN Fan:VariableVolume 0.62 1389.42 21.18 47460.92 2240.64 1.00 1.11 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:40:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
COOLSYS1 PUMP SECONDARY Pump:VariableSpeed Intermittent 105797.75 0.019985 3263.02 163269.44 0.90 General
HEATSYS1 PUMP Pump:VariableSpeed Intermittent 180705.70 0.002372 714.20 301156.09 0.90 General
COOLSYS1 PUMP Pump:ConstantSpeed Intermittent 73247.35 0.019985 2259.10 113036.94 0.90 General
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 29891.00 0.000375 47.91 127739.32 0.30 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWH LAUNDRY G WATER HEATER WaterHeater:Mixed 1.14 163316.00 0.80 11.51 0.44
SWH BOOSTER E WATER HEATER WaterHeater:Mixed 0.02 8000.00 1.00 1.22 1.12
SWHSYS1 WATER HEATER WaterHeater:Mixed 2.27 175842.60 0.80 5.78 0.37



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:51

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 32902.70 32902.70 16.63 2.436 2.436 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 19:20:00 24.00 24.00 0.00923 27.50 0.00823 0.854 0.00
RETAIL_1_FLR_1 4218.76 4218.76 62.90 0.312 0.312 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:10:00 24.00 24.00 0.00907 30.93 0.00823 0.079 0.00
RETAIL_2_FLR_1 3076.20 3076.20 39.61 0.228 0.228 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 24.00 24.00 0.00942 30.05 0.00823 0.092 0.00
MECH_FLR_1 2446.20 2446.20 14.89 0.181 0.181 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:30:00 24.00 24.00 0.00874 28.50 0.00823 0.000 0.00
STORAGE_FLR_1 1435.57 1435.57 15.15 0.106 0.106 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:10:00 24.00 24.00 0.00881 31.21 0.00823 0.058 0.00
LAUNDRY_FLR_1 44525.32 44525.32 570.55 3.296 3.296 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:40:00 24.00 24.00 0.00854 31.30 0.00823 0.000 0.00
CAFE_FLR_1 18649.47 18649.47 98.75 1.382 1.382 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:10:00 24.00 23.99 0.01021 30.93 0.00823 0.676 0.00
LOBBY_FLR_1 62965.29 62965.29 48.13 4.663 4.663 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 24.00 23.99 0.01001 31.08 0.00823 1.894 0.00
ROOM_1_FLR_3 9804.14 9804.14 251.25 0.978 0.978 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:20:00 21.11 21.11 0.00857 30.53 0.00823 0.062 0.00
ROOM_2_FLR_3 9439.04 9439.04 241.92 0.942 0.942 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00 21.11 21.11 0.00858 30.41 0.00823 0.062 0.00
ROOM_3_MULT19_FLR_3 61224.76 61224.76 2496.54 6.108 6.108 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 21.11 21.11 0.00850 31.08 0.00823 0.837 0.00
ROOM_4_MULT19_FLR_3 57499.60 57499.60 2344.00 5.736 5.736 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:50:00 21.11 21.11 0.00875 31.30 0.00823 0.837 0.00
ROOM_5_FLR_3 8712.42 8712.42 223.27 0.869 0.869 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:30:00 21.11 21.11 0.00858 27.16 0.00823 0.062 0.00
ROOM_6_FLR_3 8388.25 8388.25 214.99 0.837 0.837 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:10:00 21.11 21.11 0.00859 26.66 0.00823 0.062 0.00
CORRIDOR_FLR_3 19237.23 19237.23 49.40 1.424 1.424 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:10:00 24.00 24.00 0.00948 31.30 0.00823 0.475 0.00
ROOM_1_FLR_6 2539.20 2539.20 65.07 0.253 0.253 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:20:00 21.11 21.11 0.00857 30.53 0.00823 0.015 0.00
ROOM_2_FLR_6 2439.00 2439.00 62.51 0.243 0.243 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00 21.11 21.11 0.00857 30.41 0.00823 0.015 0.00
ROOM_3_MULT9_FLR_6 11922.45 11922.45 486.02 1.189 1.189 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 21.11 21.11 0.00864 31.08 0.00823 0.099 0.00
BANQUET_FLR_6 28592.98 28592.98 86.21 2.119 2.119 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:20:00 24.00 23.98 0.01047 31.30 0.00823 1.188 0.00
DINING_FLR_6 29985.10 29985.10 90.41 2.223 2.223 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:10:00 24.00 23.98 0.01038 31.30 0.00823 1.188 0.00
KITCHEN_FLR_6 29969.64 29969.64 290.11 2.225 2.225 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 12:30:00 24.00 23.97 0.01012 30.50 0.00823 0.367 0.00
CORRIDOR_FLR_6 9517.54 9517.54 23.09 0.705 0.705 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:50:00 24.00 24.00 0.00902 31.23 0.00823 0.126 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 0.00 0.00 0.00 0.000 0.854   00:10:00 21.00 21.47 0.00506 3.80 0.00506 0.854 0.00
RETAIL_1_FLR_1 1682.58 1682.58 25.09 0.073 0.079 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00783 3.80 0.00506 0.079 0.00
RETAIL_2_FLR_1 562.47 562.47 7.24 0.025 0.092 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00780 3.80 0.00506 0.092 0.00
MECH_FLR_1 1000.82 1000.82 6.09 0.044 0.044 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00774 3.80 0.00506 0.000 0.00
STORAGE_FLR_1 670.28 670.28 7.07 0.029 0.058 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00777 3.80 0.00506 0.058 0.00
LAUNDRY_FLR_1 1306.23 1306.23 16.74 0.057 0.057 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00773 3.80 0.00506 0.000 0.00
CAFE_FLR_1 4292.00 4292.00 22.73 0.187 0.676 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00785 3.80 0.00506 0.676 0.00
LOBBY_FLR_1 9965.94 9965.94 7.62 0.435 1.894 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00781 3.80 0.00506 1.894 0.00
ROOM_1_FLR_3 3704.31 3704.31 94.93 0.163 0.163 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00782 3.80 0.00506 0.062 0.00
ROOM_2_FLR_3 3704.51 3704.51 94.94 0.163 0.163 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00782 3.80 0.00506 0.062 0.00
ROOM_3_MULT19_FLR_3 21626.51 21626.51 881.86 0.950 0.950 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00783 3.80 0.00506 0.837 0.00
ROOM_4_MULT19_FLR_3 21641.04 21641.04 882.21 0.951 0.951 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00783 3.80 0.00506 0.837 0.00
ROOM_5_FLR_3 3703.48 3703.48 94.91 0.163 0.163 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00782 3.80 0.00506 0.062 0.00
ROOM_6_FLR_3 3703.68 3703.68 94.92 0.163 0.163 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00782 3.80 0.00506 0.062 0.00
CORRIDOR_FLR_3 6023.58 6023.58 15.47 0.263 0.475 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00786 3.80 0.00506 0.475 0.00
ROOM_1_FLR_6 1153.43 1153.43 29.56 0.051 0.051 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00785 3.80 0.00506 0.015 0.00
ROOM_2_FLR_6 1152.99 1152.99 29.55 0.051 0.051 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00785 3.80 0.00506 0.015 0.00
ROOM_3_MULT9_FLR_6 5585.52 5585.52 227.70 0.245 0.245 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00786 3.80 0.00506 0.099 0.00
BANQUET_FLR_6 3898.48 3898.48 11.75 0.170 1.188 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 20:00:00 21.00 21.00 0.00789 3.80 0.00506 1.188 0.00
DINING_FLR_6 3955.39 3955.39 11.93 0.173 1.188 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 04:20:00 21.00 21.00 0.00789 3.80 0.00506 1.188 0.00
KITCHEN_FLR_6 75.89 75.89 0.73 0.003 0.367 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 21.00 21.29 0.00369 3.80 0.00506 0.367 0.00
CORRIDOR_FLR_6 4160.65 4160.65 10.10 0.182 0.182 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 04:30:00 21.00 21.00 0.00791 3.80 0.00506 0.126 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
FLR_3_DOAS 16.40 2.05 2.90 2.05 2.0513 2.0513 2.0513 1.0000 0.3000
VAV WITH REHEAT 21.18 21.18 7.15 7.15 21.1819 11.6514 21.1819 0.5501 0.3000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
BASEMENT VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT BASEMENT VAV BOX 6904.490 6904.490 1.332446 0.00006040 143.981   12/21 00:10:00   12/21 00:10:00 6904.49 6904.49 1.332446 16.70 13.02 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00800000 50.7558 0.00 0.00 6943.30 6943.30
RETAIL_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_1_FLR_1 VAV BOX 2567.637 2567.637 0.170861 0.00002246 59.464 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 2567.64 2567.64 0.170861 16.70 13.02 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00782559 49.6635 1682.58 0.00 2581.38 2581.38
RETAIL_2_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_2_FLR_1 VAV BOX 1207.821 1207.821 0.124589 0.00001057 26.384 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 1207.82 1207.82 0.124589 16.70 13.02 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00780032 49.5048 562.47 0.00 1214.51 1214.51
MECH_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT MECH_FLR_1 VAV BOX 1513.844 1513.844 0.099052 0.00001324 35.162 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 1513.84 1513.84 0.099052 16.70 13.02 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00774048 49.1297 1000.82 0.00 1521.94 1521.94
STORAGE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT STORAGE_FLR_1 VAV BOX 971.374 971.374 0.058130 0.00000850 22.937 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 971.37 971.37 0.058130 16.70 13.02 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00777372 49.3381 670.28 0.00 976.54 976.54
LAUNDRY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 10644.593 10644.593 1.803095 0.00009312 223.589 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 10644.59 10644.59 1.803095 16.70 13.02 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00772981 49.0631 1306.23 0.00 10704.26 10704.26
CAFE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CAFE_FLR_1 VAV BOX 8207.964 8207.964 0.755944 0.00007181 181.520 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 8207.96 8207.96 0.755944 16.70 13.02 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00784765 49.8016 4292.00 0.00 8252.64 8252.64
LOBBY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 23179.427 23179.427 2.550867 0.00020278 503.106 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 23179.43 23179.43 2.550867 16.70 13.02 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00781464 49.5946 9965.94 0.00 23308.02 23308.02
ROOM_1_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL 10708.369 -999.000 0.978062 0.00030625 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:20:00 unknown 8/21 16:20:00 10708.37 10522.64 0.978062 21.69 15.44 0.00857357 12.80 11.93 0.00850000 30.53 0.00823226 18.20 0.0000 21.11 0.00857357 53.9772 9804.14 0.00 10912.59 10912.59
ROOM_1_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL 3704.302 3704.302 0.162734 0.00003241 105.839 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3704.30 3704.30 0.162734 21.11 14.54 0.00781767 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.11 0.00781767 49.2768 3704.31 0.00 3993.36 3993.36
ROOM_2_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL 10317.415 -999.000 0.941639 0.00029507 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00 unknown 8/21 16:30:00 10317.41 10131.86 0.941639 21.69 15.44 0.00857634 12.80 11.93 0.00850000 30.41 0.00823207 18.16 0.0000 21.11 0.00857634 53.9944 9439.04 0.00 10514.05 10514.05
ROOM_2_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL 3704.506 3704.506 0.162743 0.00003241 105.845 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3704.51 3704.51 0.162743 21.11 14.54 0.00781770 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.11 0.00781770 49.2769 3704.51 0.00 3993.58 3993.58
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL 65521.977 -999.000 6.107512 0.00187389 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 unknown 8/21 13:30:00 65521.98 65521.98 6.107512 21.69 15.37 0.00849776 12.80 11.93 0.00849776 31.08 0.00823314 18.38 0.0000 21.11 0.00849776 53.5051 61224.76 0.00 66783.29 66783.29
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL 21626.495 21626.495 0.950083 0.00018920 617.907 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21626.49 21626.49 0.950083 21.11 14.56 0.00783349 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.11 0.00783349 49.3749 21626.51 0.00 23314.11 23314.11
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL 65765.342 -999.000 5.736356 0.00188085 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:50:00 unknown 8/21 14:50:00 65765.34 62105.82 5.736356 21.69 15.59 0.00874561 12.80 11.93 0.00850000 31.30 0.00823349 18.45 0.0000 21.11 0.00874561 55.0462 57499.60 0.00 66993.87 65738.85
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL 21641.021 21641.021 0.950722 0.00018933 618.322 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21641.02 21641.02 0.950722 21.11 14.56 0.00783356 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.11 0.00783356 49.3753 21641.04 0.00 23329.77 23329.77
ROOM_5_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL 9539.759 -999.000 0.869152 0.00027283 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:30:00 unknown 8/21 09:30:00 9539.76 9354.18 0.869152 21.69 15.44 0.00858270 12.80 11.93 0.00850000 27.16 0.00822694 17.07 0.0000 21.11 0.00858270 54.0339 8712.42 0.00 9721.31 9721.31
ROOM_5_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL 3703.472 3703.472 0.162698 0.00003240 105.816 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3703.47 3703.47 0.162698 21.11 14.54 0.00781764 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.11 0.00781764 49.2765 3703.48 0.00 3992.46 3992.46
ROOM_6_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL 9192.763 -999.000 0.836813 0.00026291 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:10:00 unknown 8/21 09:10:00 9192.76 9007.22 0.836813 21.69 15.45 0.00858586 12.80 11.93 0.00850000 26.66 0.00822614 16.89 0.0000 21.11 0.00858586 54.0535 8388.25 0.00 9367.59 9367.59
ROOM_6_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL 3703.676 3703.676 0.162707 0.00003240 105.821 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3703.68 3703.68 0.162707 21.11 14.54 0.00781766 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.11 0.00781766 49.2767 3703.68 0.00 3992.68 3992.68
CORRIDOR_FLR_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_3 VAV BOX 10059.284 10059.284 0.779022 0.00008800 227.501 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 10059.28 10059.28 0.779022 16.70 13.02 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00786143 49.8877 6023.58 0.00 10113.56 10113.56
ROOM_1_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL 2771.503 -999.000 0.253311 0.00007926 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:20:00 unknown 8/21 16:20:00 2771.50 2725.03 0.253311 21.69 15.43 0.00857110 12.80 11.93 0.00850000 30.53 0.00823226 18.20 0.0000 21.11 0.00857110 53.9618 2539.20 0.00 2824.39 2824.39
ROOM_1_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL 1153.431 1153.431 0.050672 0.00001009 32.955 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 1153.43 1153.43 0.050672 21.11 14.57 0.00785177 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.11 0.00785177 49.4890 1153.43 0.00 1243.44 1243.44
ROOM_2_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL 2664.214 -999.000 0.243315 0.00007619 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00 unknown 8/21 16:30:00 2664.21 2617.78 0.243315 21.69 15.44 0.00857394 12.80 11.93 0.00850000 30.41 0.00823207 18.16 0.0000 21.11 0.00857394 53.9795 2439.00 0.00 2715.02 2715.02
ROOM_2_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL 1152.988 1152.988 0.050652 0.00001009 32.942 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 1152.99 1152.99 0.050652 21.11 14.57 0.00785173 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.11 0.00785173 49.4887 1152.99 0.00 1242.96 1242.96
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL 13255.404 -999.000 1.189416 0.00037910 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 unknown 8/21 13:30:00 13255.40 12827.87 1.189416 21.69 15.49 0.00863892 12.80 11.93 0.00850000 31.08 0.00823314 18.38 0.0000 21.11 0.00863892 54.3837 11922.45 0.00 13506.61 13506.61
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL 5585.509 5585.509 0.245379 0.00004886 159.585 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 5585.51 5585.51 0.245379 21.11 14.58 0.00785870 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.11 0.00785870 49.5320 5585.52 0.00 6021.37 6021.37
BANQUET_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 9904.560 9904.560 1.159334 0.00008665 213.757 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 20:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 20:00:00 9904.56 9904.56 1.159334 16.70 13.02 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00789078 50.0720 3898.48 0.00 9959.60 9959.60
DINING_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 10253.897 10253.897 1.215761 0.00008971 221.044 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 04:20:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 04:20:00 10253.90 10253.90 1.215761 16.70 13.02 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00789213 50.0802 3955.39 0.00 10310.89 10310.89
KITCHEN_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 6758.611 6758.611 1.216841 0.00005913 141.466 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 6758.61 6758.61 1.216841 16.70 13.02 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.29 0.00369468 23.1809 75.89 0.00 6796.55 6796.55
CORRIDOR_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_6 VAV BOX 6157.447 6157.447 0.385415 0.00005387 144.160 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 04:30:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 04:30:00 6157.45 6157.45 0.385415 16.70 13.02 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00790963 50.1898 4160.65 0.00 6190.29 6190.29
FLR_3_DOAS COOLING COIL Coil:Cooling:Water AirLoopHVAC FLR_3_DOAS 47946.248 -999.000 2.051317 0.00137126 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:40:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:40:00 47946.25 47946.25 2.051317 31.30 18.45 0.00823349 11.91 11.29 0.00823349 31.30 0.00823349 18.45 99.9965 21.11 0.00861907 54.2595 164372.54 0.00 48578.76 48578.76
FLR_3_DOAS HEATING COIL Coil:Heating:Water AirLoopHVAC FLR_3_DOAS 9427.247 9427.247 0.615395 0.00008247 168.968 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 9427.25 9427.25 0.615395 3.80 3.80 0.00505843 16.70 13.02 0.00800000 3.80 0.00505843 3.80 333.3216 21.11 0.00783363 49.3758 65975.46 0.00 9576.38 9576.38
VAV WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV WITH REHEAT 461117.245 -999.000 21.181871 0.01318789 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:40:00 461117.25 435635.08 21.181871 28.02 17.89 0.00889053 10.94 10.94 0.00850000 31.30 0.00823349 18.45 55.0540 23.99 0.00966027 50.9644 285836.33 0.00 467517.86 425623.95
VAV WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV WITH REHEAT 97345.612 97345.612 6.354561 0.00085162 1744.760 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 04:30:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 04:30:00 97345.61 97345.61 6.354561 3.80 3.80 0.00505843 16.70 13.02 0.00800000 3.80 0.00505843 3.80 183.5132 21.37 0.00635988 39.5452 37450.68 0.00 98885.53 98885.53



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2024-07-03 12:21:51

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
BASEMENT VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT BASEMENT VAV BOX BASEMENT N/A N/A N/A Yes Yes Yes No 6904.490 6904.490 1.332446 0.00006040 143.981 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.37127723 54.44 82.22 27.78 276534.78 2.4968 2.547038   12/21 00:10:00 unknown unknown   12/21 00:10:00 Sensible 6904.49 6904.49 1.0000 1.57465639 1.332446 16.70 13.02 0.00800000 37036.7 40.00 20.96 0.00800000 60796.0 0.06039733 60.00 32.22 27.78 0.000 6904.49 3.80 0.00505843 3.80 0.00000000 0.0000 21.00 0.00800000 21.00 0.00800000 50.7558 0.00 0.00 6943.30 6943.30 1.57465639 16.60 13.15 0.00800000 36934.7 20.92 14.82 0.00800000 41344.1
RETAIL_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_1_FLR_1 VAV BOX RETAIL_1_FLR_1 N/A N/A N/A Yes Yes Yes No 2567.637 2567.637 0.170861 0.00002246 59.464 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.37127723 54.44 82.22 27.78 276534.78 0.9285 0.947191 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 2567.64 2567.64 1.0000 0.20191982 0.170861 16.70 13.02 0.00800000 37036.7 40.00 20.96 0.00800000 60796.0 0.02246052 60.00 32.22 27.78 0.000 2567.64 3.80 0.00505843 3.80 0.00000000 0.0000 21.00 0.00782559 21.00 0.00782559 49.6635 1682.58 0.00 2581.38 2581.38 0.20191982 16.60 13.15 0.00800000 36934.7 29.14 17.75 0.00800000 49718.9
RETAIL_2_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_2_FLR_1 VAV BOX RETAIL_2_FLR_1 N/A N/A N/A Yes Yes Yes No 1207.821 1207.821 0.124589 0.00001057 26.384 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.37127723 54.44 82.22 27.78 276534.78 0.4368 0.445560 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 1207.82 1207.82 1.0000 0.14723700 0.124589 16.70 13.02 0.00800000 37036.7 40.00 20.96 0.00800000 60796.0 0.01056547 60.00 32.22 27.78 0.000 1207.82 3.80 0.00505843 3.80 0.00000000 0.0000 21.00 0.00780032 21.00 0.00780032 49.5048 562.47 0.00 1214.51 1214.51 0.14723700 16.60 13.15 0.00800000 36934.7 24.69 16.20 0.00800000 45183.4
MECH_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT MECH_FLR_1 VAV BOX MECH_FLR_1 N/A N/A N/A Yes Yes Yes No 1513.844 1513.844 0.099052 0.00001324 35.162 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.37127723 54.44 82.22 27.78 276534.78 0.5474 0.558451 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 1513.84 1513.84 1.0000 0.11705745 0.099052 16.70 13.02 0.00800000 37036.7 40.00 20.96 0.00800000 60796.0 0.01324242 60.00 32.22 27.78 0.000 1513.84 3.80 0.00505843 3.80 0.00000000 0.0000 21.00 0.00774048 21.00 0.00774048 49.1297 1000.82 0.00 1521.94 1521.94 0.11705745 16.60 13.15 0.00800000 36934.7 29.35 17.82 0.00800000 49936.4
STORAGE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT STORAGE_FLR_1 VAV BOX STORAGE_FLR_1 N/A N/A N/A Yes Yes Yes No 971.374 971.374 0.058130 0.00000850 22.937 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.37127723 54.44 82.22 27.78 276534.78 0.3513 0.358336 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 971.37 971.37 1.0000 0.06869685 0.058130 16.70 13.02 0.00800000 37036.7 40.00 20.96 0.00800000 60796.0 0.00849713 60.00 32.22 27.78 0.000 971.37 3.80 0.00505843 3.80 0.00000000 0.0000 21.00 0.00777372 21.00 0.00777372 49.3381 670.28 0.00 976.54 976.54 0.06869685 16.60 13.15 0.00800000 36934.7 30.54 18.22 0.00800000 51150.0
LAUNDRY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown LAUNDRY_FLR_1 N/A N/A N/A Yes Yes Yes No 10644.593 10644.593 1.803095 0.00009312 223.589 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.37127723 54.44 82.22 27.78 276534.78 3.8493 3.926746 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 10644.59 10644.59 1.0000 2.13085945 1.803095 16.70 13.02 0.00800000 37036.7 40.00 20.96 0.00800000 60796.0 0.09311404 60.00 32.22 27.78 0.000 10644.59 3.80 0.00505843 3.80 0.00000000 0.0000 21.00 0.00772981 21.00 0.00772981 49.0631 1306.23 0.00 10704.26 10704.26 2.13085945 16.60 13.15 0.00800000 36934.7 21.53 15.05 0.00800000 41958.2
CAFE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CAFE_FLR_1 VAV BOX CAFE_FLR_1 N/A N/A N/A Yes Yes Yes No 8207.964 8207.964 0.755944 0.00007181 181.520 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.37127723 54.44 82.22 27.78 276534.78 2.9681 3.027884 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 8207.96 8207.96 1.0000 0.89335848 0.755944 16.70 13.02 0.00800000 37036.7 40.00 20.96 0.00800000 60796.0 0.07179953 60.00 32.22 27.78 0.000 8207.96 3.80 0.00505843 3.80 0.00000000 0.0000 21.00 0.00784765 21.00 0.00784765 49.8016 4292.00 0.00 8252.64 8252.64 0.89335848 16.60 13.15 0.00800000 36934.7 25.66 16.55 0.00800000 46172.5
LOBBY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown LOBBY_FLR_1 N/A N/A N/A Yes Yes Yes No 23179.427 23179.427 2.550867 0.00020278 503.106 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.37127723 54.44 82.22 27.78 276534.78 8.3821 8.550795 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 23179.43 23179.43 1.0000 3.01455960 2.550867 16.70 13.02 0.00800000 37036.7 40.00 20.96 0.00800000 60796.0 0.20276306 60.00 32.22 27.78 0.000 23179.43 3.80 0.00505843 3.80 0.00000000 0.0000 21.00 0.00781464 21.00 0.00781464 49.5946 9965.94 0.00 23308.02 23308.02 3.01455960 16.60 13.15 0.00800000 36934.7 24.18 16.02 0.00800000 44666.5
ROOM_1_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL ROOM_1_FLR_3 N/A N/A N/A Yes Yes Yes No 10708.369 -999.000 0.978062 0.00030625 -999.000 -999.0000 1.00000 1.00000 1020.7778 1004.8586 1.1818 ROOM_1_FLR_3 FAN COIL_FANCOILFAN Fan:OnOff 0.978062 1.15585281   4197.9300 999.8980 19.98345835 15.03 6.70 8.33 698796.70 1.5324 1.532373 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:20:00 unknown unknown unknown 8/21 16:20:00 Sensible 10708.37 10522.64 1.0000 1.15585281 0.978062 21.69 15.44 0.00857357 43586.7 12.80 11.93 0.00850000 34322.2 0.30622105 6.70 15.03 8.33 0.000 10708.37 30.53 0.00823226 18.20 0.00000000 0.0000 21.11 0.00857357 21.11 0.00857357 53.9772 9804.14 0.00 10912.59 10912.59 1.15585281 21.69 15.62 0.00857357 43586.7 12.44 12.03 0.00857357 34145.5
ROOM_1_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL ROOM_1_FLR_3 N/A N/A N/A Yes Yes Yes No 3704.302 3704.302 0.162734 0.00003241 105.839 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 ROOM_1_FLR_3 FAN COIL_FANCOILFAN Fan:OnOff 0.978062 1.15585281   4197.9300 999.8980 2.37127723 54.44 82.22 27.78 276534.78 1.3395 1.366502 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 3704.30 3704.30 1.0000 0.19231616 0.162734 21.11 14.54 0.00781767 41071.3 40.00 20.96 0.00800000 60796.0 0.03240354 60.00 32.22 27.78 0.000 3704.30 3.80 0.00505843 3.80 0.00000000 0.0000 21.11 0.00781767 21.11 0.00781767 49.2768 3704.31 0.00 3993.36 3993.36 0.19231616 16.60 12.97 0.00781767 36473.1 36.97 20.13 0.00781767 57237.7
ROOM_2_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL ROOM_2_FLR_3 N/A N/A N/A Yes Yes Yes No 10317.415 -999.000 0.941639 0.00029507 -999.000 -999.0000 1.00000 1.00000 1020.7830 1004.8586 1.1818 ROOM_2_FLR_3 FAN COIL_FANCOILFAN Fan:OnOff 0.941639 1.11280927   4197.9300 999.8980 19.98345835 15.03 6.70 8.33 698796.70 1.4765 1.476427 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00 unknown unknown unknown 8/21 16:30:00 Sensible 10317.41 10131.86 1.0000 1.11280927 0.941639 21.69 15.44 0.00857634 43593.7 12.80 11.93 0.00850000 34322.2 0.29504115 6.70 15.03 8.33 0.000 10317.41 30.41 0.00823207 18.16 0.00000000 0.0000 21.11 0.00857634 21.11 0.00857634 53.9944 9439.04 0.00 10514.05 10514.05 1.11280927 21.69 15.63 0.00857634 43593.7 12.44 12.03 0.00857634 34145.5
ROOM_2_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL ROOM_2_FLR_3 N/A N/A N/A Yes Yes Yes No 3704.506 3704.506 0.162743 0.00003241 105.845 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 ROOM_2_FLR_3 FAN COIL_FANCOILFAN Fan:OnOff 0.941639 1.11280927   4197.9300 999.8980 2.37127723 54.44 82.22 27.78 276534.78 1.3396 1.366577 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 3704.51 3704.51 1.0000 0.19232674 0.162743 21.11 14.54 0.00781770 41071.4 40.00 20.96 0.00800000 60796.0 0.03240532 60.00 32.22 27.78 0.000 3704.51 3.80 0.00505843 3.80 0.00000000 0.0000 21.11 0.00781770 21.11 0.00781770 49.2769 3704.51 0.00 3993.58 3993.58 0.19232674 16.60 12.97 0.00781770 36473.2 36.97 20.13 0.00781770 57237.7
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL ROOM_3_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 65521.977 -999.000 6.107512 0.00187389 -999.000 -999.0000 1.00000 1.00000 1020.6369 1004.8586 1.1818 ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN Fan:OnOff 6.107512 7.21772684   4197.9300 999.8980 19.98345835 15.03 6.70 8.33 698796.70 9.3764 9.376225 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 unknown unknown unknown 8/21 13:30:00 Sensible 65521.98 65521.98 1.0000 7.21772684 6.107512 21.69 15.37 0.00849776 43394.5 12.80 11.93 0.00849776 34316.5 1.87369409 6.70 15.03 8.33 0.000 65521.98 31.08 0.00823314 18.38 0.00000000 0.0000 21.11 0.00849776 21.11 0.00849776 53.5051 61224.76 0.00 66783.29 66783.29 7.21772684 21.69 15.56 0.00849776 43394.5 12.63 12.03 0.00849776 34141.8
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL ROOM_3_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 21626.495 21626.495 0.950083 0.00018920 617.907 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN Fan:OnOff 6.107512 7.21772684   4197.9300 999.8980 2.37127723 54.44 82.22 27.78 276534.78 7.8205 7.977925 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 21626.49 21626.49 1.0000 1.12278825 0.950083 21.11 14.56 0.00783349 41111.6 40.00 20.96 0.00800000 60796.0 0.18917871 60.00 32.22 27.78 0.000 21626.49 3.80 0.00505843 3.80 0.00000000 0.0000 21.11 0.00783349 21.11 0.00783349 49.3749 21626.51 0.00 23314.11 23314.11 1.12278825 16.60 12.99 0.00783349 36513.2 36.97 20.14 0.00783349 57277.6
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL ROOM_4_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 65765.342 -999.000 5.736356 0.00188085 -999.000 -999.0000 1.00000 1.00000 1021.0976 1004.8586 1.1818 ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN Fan:OnOff 5.736356 6.77910321   4197.9300 999.8980 19.98345835 15.03 6.70 8.33 698796.70 9.4112 9.411051 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:50:00 unknown unknown unknown 8/21 14:50:00 Sensible 65765.34 62105.82 1.0000 6.77910321 5.736356 21.69 15.59 0.00874561 44023.4 12.80 11.93 0.00850000 34322.2 1.88065347 6.70 15.03 8.33 0.000 65765.34 31.30 0.00823349 18.45 0.00000000 0.0000 21.11 0.00874561 21.11 0.00874561 55.0462 57499.60 0.00 66993.87 65738.85 6.77910321 21.69 15.77 0.00874561 44023.4 12.20 12.02 0.00867225 34141.0
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL ROOM_4_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 21641.021 21641.021 0.950722 0.00018933 618.322 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN Fan:OnOff 5.736356 6.77910321   4197.9300 999.8980 2.37127723 54.44 82.22 27.78 276534.78 7.8258 7.983283 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 21641.02 21641.02 1.0000 1.12354244 0.950722 21.11 14.56 0.00783356 41111.8 40.00 20.96 0.00800000 60796.0 0.18930578 60.00 32.22 27.78 0.000 21641.02 3.80 0.00505843 3.80 0.00000000 0.0000 21.11 0.00783356 21.11 0.00783356 49.3753 21641.04 0.00 23329.77 23329.77 1.12354244 16.60 12.99 0.00783356 36513.3 36.97 20.14 0.00783356 57277.8
ROOM_5_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL ROOM_5_FLR_3 N/A N/A N/A Yes Yes Yes No 9539.759 -999.000 0.869152 0.00027283 -999.000 -999.0000 1.00000 1.00000 1020.7948 1004.8586 1.1818 ROOM_5_FLR_3 FAN COIL_FANCOILFAN Fan:OnOff 0.869152 1.02714535   4197.9300 999.8980 19.98345835 15.03 6.70 8.33 698796.70 1.3652 1.365144 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:30:00 unknown unknown unknown 8/21 09:30:00 Sensible 9539.76 9354.18 1.0000 1.02714535 0.869152 21.69 15.44 0.00858270 43609.8 12.80 11.93 0.00850000 34322.2 0.27280296 6.70 15.03 8.33 0.000 9539.76 27.16 0.00822694 17.07 0.00000000 0.0000 21.11 0.00858270 21.11 0.00858270 54.0339 8712.42 0.00 9721.31 9721.31 1.02714535 21.69 15.63 0.00858270 43609.8 12.42 12.03 0.00858270 34145.4
ROOM_5_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL ROOM_5_FLR_3 N/A N/A N/A Yes Yes Yes No 3703.472 3703.472 0.162698 0.00003240 105.816 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 ROOM_5_FLR_3 FAN COIL_FANCOILFAN Fan:OnOff 0.869152 1.02714535   4197.9300 999.8980 2.37127723 54.44 82.22 27.78 276534.78 1.3392 1.366196 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 3703.47 3703.47 1.0000 0.19227310 0.162698 21.11 14.54 0.00781764 41071.2 40.00 20.96 0.00800000 60796.0 0.03239629 60.00 32.22 27.78 0.000 3703.47 3.80 0.00505843 3.80 0.00000000 0.0000 21.11 0.00781764 21.11 0.00781764 49.2765 3703.48 0.00 3992.46 3992.46 0.19227310 16.60 12.97 0.00781764 36473.0 36.97 20.13 0.00781764 57237.6
ROOM_6_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL ROOM_6_FLR_3 N/A N/A N/A Yes Yes Yes No 9192.763 -999.000 0.836813 0.00026291 -999.000 -999.0000 1.00000 1.00000 1020.8007 1004.8586 1.1818 ROOM_6_FLR_3 FAN COIL_FANCOILFAN Fan:OnOff 0.836813 0.98892766   4197.9300 999.8980 19.98345835 15.03 6.70 8.33 698796.70 1.3155 1.315489 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:10:00 unknown unknown unknown 8/21 09:10:00 Sensible 9192.76 9007.22 1.0000 0.98892766 0.836813 21.69 15.45 0.00858586 43617.9 12.80 11.93 0.00850000 34322.2 0.26288014 6.70 15.03 8.33 0.000 9192.76 26.66 0.00822614 16.89 0.00000000 0.0000 21.11 0.00858586 21.11 0.00858586 54.0535 8388.25 0.00 9367.59 9367.59 0.98892766 21.69 15.63 0.00858586 43617.9 12.41 12.03 0.00858586 34145.4
ROOM_6_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL ROOM_6_FLR_3 N/A N/A N/A Yes Yes Yes No 3703.676 3703.676 0.162707 0.00003240 105.821 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 ROOM_6_FLR_3 FAN COIL_FANCOILFAN Fan:OnOff 0.836813 0.98892766   4197.9300 999.8980 2.37127723 54.44 82.22 27.78 276534.78 1.3393 1.366271 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 3703.68 3703.68 1.0000 0.19228368 0.162707 21.11 14.54 0.00781766 41071.3 40.00 20.96 0.00800000 60796.0 0.03239807 60.00 32.22 27.78 0.000 3703.68 3.80 0.00505843 3.80 0.00000000 0.0000 21.11 0.00781766 21.11 0.00781766 49.2767 3703.68 0.00 3992.68 3992.68 0.19228368 16.60 12.97 0.00781766 36473.1 36.97 20.13 0.00781766 57237.6
CORRIDOR_FLR_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_3 VAV BOX CORRIDOR_FLR_3 N/A N/A N/A Yes Yes Yes No 10059.284 10059.284 0.779022 0.00008800 227.501 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.37127723 54.44 82.22 27.78 276534.78 3.6376 3.710828 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 10059.28 10059.28 1.0000 0.92063107 0.779022 16.70 13.02 0.00800000 37036.7 40.00 20.96 0.00800000 60796.0 0.08799403 60.00 32.22 27.78 0.000 10059.28 3.80 0.00505843 3.80 0.00000000 0.0000 21.00 0.00786143 21.00 0.00786143 49.8877 6023.58 0.00 10113.56 10113.56 0.92063107 16.60 13.15 0.00800000 36934.7 27.37 17.15 0.00800000 47920.2
ROOM_1_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL ROOM_1_FLR_6 N/A N/A N/A Yes Yes Yes No 2771.503 -999.000 0.253311 0.00007926 -999.000 -999.0000 1.00000 1.00000 1020.7732 1004.8586 1.1818 ROOM_1_FLR_6 FAN COIL_FANCOILFAN Fan:OnOff 0.253311 0.29935722   4197.9300 999.8980 19.98345835 15.03 6.70 8.33 698796.70 0.3966 0.396603 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:20:00 unknown unknown unknown 8/21 16:20:00 Sensible 2771.50 2725.03 1.0000 0.29935722 0.253311 21.69 15.43 0.00857110 43580.4 12.80 11.93 0.00850000 34322.2 0.07925508 6.70 15.03 8.33 0.000 2771.50 30.53 0.00823226 18.20 0.00000000 0.0000 21.11 0.00857110 21.11 0.00857110 53.9618 2539.20 0.00 2824.39 2824.39 0.29935722 21.69 15.62 0.00857110 43580.4 12.45 12.03 0.00857110 34145.5
ROOM_1_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL ROOM_1_FLR_6 N/A N/A N/A Yes Yes Yes No 1153.431 1153.431 0.050672 0.00001009 32.955 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 ROOM_1_FLR_6 FAN COIL_FANCOILFAN Fan:OnOff 0.253311 0.29935722   4197.9300 999.8980 2.37127723 54.44 82.22 27.78 276534.78 0.4171 0.425496 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 1153.43 1153.43 1.0000 0.05988268 0.050672 21.11 14.57 0.00785177 41157.9 40.00 20.96 0.00800000 60796.0 0.01008969 60.00 32.22 27.78 0.000 1153.43 3.80 0.00505843 3.80 0.00000000 0.0000 21.11 0.00785177 21.11 0.00785177 49.4890 1153.43 0.00 1243.44 1243.44 0.05988268 16.60 13.01 0.00785177 36559.5 36.97 20.16 0.00785177 57324.0
ROOM_2_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL ROOM_2_FLR_6 N/A N/A N/A Yes Yes Yes No 2664.214 -999.000 0.243315 0.00007619 -999.000 -999.0000 1.00000 1.00000 1020.7785 1004.8586 1.1818 ROOM_2_FLR_6 FAN COIL_FANCOILFAN Fan:OnOff 0.243315 0.28754414   4197.9300 999.8980 19.98345835 15.03 6.70 8.33 698796.70 0.3813 0.381250 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00 unknown unknown unknown 8/21 16:30:00 Sensible 2664.21 2617.78 1.0000 0.28754414 0.243315 21.69 15.44 0.00857394 43587.6 12.80 11.93 0.00850000 34322.2 0.07618700 6.70 15.03 8.33 0.000 2664.21 30.41 0.00823207 18.16 0.00000000 0.0000 21.11 0.00857394 21.11 0.00857394 53.9795 2439.00 0.00 2715.02 2715.02 0.28754414 21.69 15.62 0.00857394 43587.6 12.44 12.03 0.00857394 34145.5
ROOM_2_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL ROOM_2_FLR_6 N/A N/A N/A Yes Yes Yes No 1152.988 1152.988 0.050652 0.00001009 32.942 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 ROOM_2_FLR_6 FAN COIL_FANCOILFAN Fan:OnOff 0.243315 0.28754414   4197.9300 999.8980 2.37127723 54.44 82.22 27.78 276534.78 0.4169 0.425332 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 1152.99 1152.99 1.0000 0.05985965 0.050652 21.11 14.57 0.00785173 41157.8 40.00 20.96 0.00800000 60796.0 0.01008581 60.00 32.22 27.78 0.000 1152.99 3.80 0.00505843 3.80 0.00000000 0.0000 21.11 0.00785173 21.11 0.00785173 49.4887 1152.99 0.00 1242.96 1242.96 0.05985965 16.60 13.01 0.00785173 36559.3 36.97 20.16 0.00785173 57323.9
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL ROOM_3_MULT9_FLR_6 N/A N/A N/A Yes Yes Yes No 13255.404 -999.000 1.189416 0.00037910 -999.000 -999.0000 1.00000 1.00000 1020.8993 1004.8586 1.1818 ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN Fan:OnOff 1.189416 1.40562664   4197.9300 999.8980 19.98345835 15.03 6.70 8.33 698796.70 1.8969 1.896855 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 unknown unknown unknown 8/21 13:30:00 Sensible 13255.40 12827.87 1.0000 1.40562664 1.189416 21.69 15.49 0.00863892 43752.4 12.80 11.93 0.00850000 34322.2 0.37905713 6.70 15.03 8.33 0.000 13255.40 31.08 0.00823314 18.38 0.00000000 0.0000 21.11 0.00863892 21.11 0.00863892 54.3837 11922.45 0.00 13506.61 13506.61 1.40562664 21.69 15.68 0.00863892 43752.4 12.28 12.02 0.00863892 34143.5
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL ROOM_3_MULT9_FLR_6 N/A N/A N/A Yes Yes Yes No 5585.509 5585.509 0.245379 0.00004886 159.585 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN Fan:OnOff 1.189416 1.40562664   4197.9300 999.8980 2.37127723 54.44 82.22 27.78 276534.78 2.0198 2.060471 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 5585.51 5585.51 1.0000 0.28998331 0.245379 21.11 14.58 0.00785870 41175.6 40.00 20.96 0.00800000 60796.0 0.04885948 60.00 32.22 27.78 0.000 5585.51 3.80 0.00505843 3.80 0.00000000 0.0000 21.11 0.00785870 21.11 0.00785870 49.5320 5585.52 0.00 6021.37 6021.37 0.28998331 16.60 13.01 0.00785870 36577.0 36.97 20.16 0.00785870 57341.5
BANQUET_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown BANQUET_FLR_6 N/A N/A N/A Yes Yes Yes No 9904.560 9904.560 1.159334 0.00008665 213.757 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.37127723 54.44 82.22 27.78 276534.78 3.5817 3.653751 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 20:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 20:00:00 Sensible 9904.56 9904.56 1.0000 1.37007663 1.159334 16.70 13.02 0.00800000 37036.7 40.00 20.96 0.00800000 60796.0 0.08664057 60.00 32.22 27.78 0.000 9904.56 3.80 0.00505843 3.80 0.00000000 0.0000 21.00 0.00789078 21.00 0.00789078 50.0720 3898.48 0.00 9959.60 9959.60 1.37007663 16.60 13.15 0.00800000 36934.7 23.73 15.86 0.00800000 44204.1
DINING_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown DINING_FLR_6 N/A N/A N/A Yes Yes Yes No 10253.897 10253.897 1.215761 0.00008971 221.044 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.37127723 54.44 82.22 27.78 276534.78 3.7080 3.782620 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 04:20:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 04:20:00 Sensible 10253.90 10253.90 1.0000 1.43676022 1.215761 16.70 13.02 0.00800000 37036.7 40.00 20.96 0.00800000 60796.0 0.08969641 60.00 32.22 27.78 0.000 10253.90 3.80 0.00505843 3.80 0.00000000 0.0000 21.00 0.00789213 21.00 0.00789213 50.0802 3955.39 0.00 10310.89 10310.89 1.43676022 16.60 13.15 0.00800000 36934.7 23.64 15.82 0.00800000 44111.2
KITCHEN_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown KITCHEN_FLR_6 N/A N/A N/A Yes Yes Yes No 6758.611 6758.611 1.216841 0.00005913 141.466 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.37127723 54.44 82.22 27.78 276534.78 2.4440 2.493224 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 6758.61 6758.61 1.0000 1.43803719 1.216841 16.70 13.02 0.00800000 37036.7 40.00 20.96 0.00800000 60796.0 0.05912125 60.00 32.22 27.78 0.000 6758.61 3.80 0.00505843 3.80 0.00000000 0.0000 17.95 0.00369468 21.29 0.00369468 23.1809 75.89 0.00 6796.55 6796.55 1.43803719 16.60 13.15 0.00800000 36934.7 21.23 14.94 0.00800000 41661.0
CORRIDOR_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_6 VAV BOX CORRIDOR_FLR_6 N/A N/A N/A Yes Yes Yes No 6157.447 6157.447 0.385415 0.00005387 144.160 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.37127723 54.44 82.22 27.78 276534.78 2.2266 2.271457 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 04:30:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 04:30:00 Sensible 6157.45 6157.45 1.0000 0.45547500 0.385415 16.70 13.02 0.00800000 37036.7 40.00 20.96 0.00800000 60796.0 0.05386253 60.00 32.22 27.78 0.000 6157.45 3.80 0.00505843 3.80 0.00000000 0.0000 21.00 0.00790963 21.00 0.00790963 50.1898 4160.65 0.00 6190.29 6190.29 0.45547500 16.60 13.15 0.00800000 36934.7 29.93 18.01 0.00800000 50525.6
FLR_3_DOAS COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC FLR_3_DOAS ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 47946.248 -999.000 2.051317 0.00137126 -999.000 -999.0000 1.00000 1.00000 1020.1456 1004.8586 1.1818 FLR_3_DOAS FAN Fan:ConstantVolume 2.051245 2.42411771   4197.9300 999.8980 19.98345835 15.03 6.70 8.33 698796.70 6.8613 6.861259 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:40:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:40:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:40:00 Sensible 47946.25 47946.25 1.0000 2.42420295 2.051317 31.30 18.45 0.00823349 52522.0 11.91 11.29 0.00823349 32743.9 1.37111674 6.70 15.03 8.33 2195.006 45751.24 31.30 0.00823349 18.45 2.05124512 99.9965 21.11 0.00861483 21.11 0.00861907 54.2595 164372.54 0.00 48578.76 48578.76 2.42420295 31.30 18.65 0.00823349 52522.0 11.66 11.35 0.00823349 32483.0
FLR_3_DOAS HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC FLR_3_DOAS ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 9427.247 9427.247 0.615395 0.00008247 168.968 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 FLR_3_DOAS FAN Fan:ConstantVolume 2.051245 2.42411771   4197.9300 999.8980 2.37127723 54.44 82.22 27.78 276534.78 3.4091 3.477673 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 9427.25 9427.25 1.0000 0.72726088 0.615395 3.80 3.80 0.00505843 16505.0 16.70 13.02 0.00800000 37036.7 0.08246526 60.00 32.22 27.78 0.000 9427.25 3.80 0.00505843 3.80 2.05124512 333.3216 21.11 0.00783273 21.11 0.00783363 49.3758 65975.46 0.00 9576.38 9576.38 0.72726088 2.80 2.80 0.00505843 15490.7 15.78 9.78 0.00505843 28658.4
VAV WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV WITH REHEAT BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 461117.245 -999.000 21.181871 0.01318789 -999.000 -999.0000 1.00000 1.00000 1021.3670 1004.8586 1.1818 VAV WITH REHEAT FAN Fan:VariableVolume 21.181871 25.03228324   4197.9300 999.8980 19.98345835 15.03 6.70 8.33 698796.70 65.9873 65.987325 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:40:00 Sensible 461117.25 435635.08 1.0000 25.03228324 21.181871 28.02 17.89 0.00889053 50848.5 10.94 10.94 0.00850000 32427.6 13.18654954 6.70 15.03 8.33 47460.918 413656.33 31.30 0.00823349 18.45 11.66146000 55.0540 23.99 0.00969588 23.99 0.00966027 50.9644 285836.33 0.00 467517.86 425623.95 25.03228324 28.02 18.10 0.00889053 50848.5 11.37 11.22 0.00822695 32171.9
VAV WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV WITH REHEAT BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 97345.612 97345.612 6.354561 0.00085162 1744.760 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 VAV WITH REHEAT FAN Fan:VariableVolume 21.181871 25.03228324   4197.9300 999.8980 2.37127723 54.44 82.22 27.78 276534.78 35.2019 35.910394 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 04:30:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 04:30:00 Sensible 97345.61 97345.61 1.0000 7.50968497 6.354561 3.80 3.80 0.00505843 16505.0 16.70 13.02 0.00800000 37036.7 0.85153500 60.00 32.22 27.78 0.000 97345.61 3.80 0.00505843 3.80 11.66146000 183.5132 18.35 0.00730273 21.37 0.00635988 39.5452 37450.68 0.00 98885.53 98885.53 7.50968497 2.80 2.80 0.00505843 15490.7 15.78 9.78 0.00505843 28658.4



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:51

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
FLR_3_DOAS_OA_CONTROLLER DifferentialDryBulb 2.05 2.05 -      
VAV WITH REHEAT_OA_CONTROLLER DifferentialDryBulb 0.00 21.18 -      


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
BASEMENT VAV WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
RETAIL_1_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.001181 0.000000 0.000000 Flow/Area   1.00 1.00  
RETAIL_2_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.001181 0.000000 0.000000 Flow/Area   1.00 1.00  
MECH_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.000000 0.000000 0.000000 Flow/Area   1.00 1.00  
STORAGE_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.000610 0.000000 0.000000 Flow/Area   1.00 1.00  
LAUNDRY_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.000000 0.000000 0.000000 Flow/Area   1.00 1.00  
CAFE_FLR_1 VAV WITH REHEAT_DCV 0.003540 0.000914 0.000000 0.000000 Sum   1.00 1.00  
LOBBY_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.001448 0.000000 0.000000 Flow/Area   1.00 1.00  
CORRIDOR_FLR_3 VAV WITH REHEAT_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  
BANQUET_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.003581 0.000000 0.000000 Flow/Area   1.00 1.00  
DINING_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.003581 0.000000 0.000000 Flow/Area   1.00 1.00  
KITCHEN_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.003556 0.000000 0.000000 Flow/Area   1.00 1.00  
CORRIDOR_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
BASEMENT 67.33 8098.00 0.00
RETAIL_1_FLR_1 839.00 7312.83 15.17
RETAIL_2_FLR_1 1107.00 6846.17 282.00
MECH_FLR_1 0.00 8624.83 0.00
STORAGE_FLR_1 1.33 8758.83 1.33
LAUNDRY_FLR_1 7483.33 3482.83 2887.83
CAFE_FLR_1 3310.67 5071.33 1163.17
LOBBY_FLR_1 2266.17 5626.17 897.17
ROOM_1_FLR_3 41.17 8283.17 40.00
ROOM_2_FLR_3 859.00 7737.17 275.33
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 103.33 8712.50 99.00
ROOM_5_FLR_3 50.00 8634.50 50.00
ROOM_6_FLR_3 514.67 8232.50 272.67
CORRIDOR_FLR_3 172.50 8758.33 172.50
ROOM_1_FLR_6 205.17 8128.50 198.50
ROOM_2_FLR_6 1223.00 7645.33 639.67
ROOM_3_MULT9_FLR_6 22.67 8159.17 12.33
BANQUET_FLR_6 6185.33 1862.17 893.50
DINING_FLR_6 7077.83 1129.33 791.50
KITCHEN_FLR_6 8459.83 6538.00 6401.83
CORRIDOR_FLR_6 15.83 8500.83 5.83
Facility 8671.50 8760.00 7296.17
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
BASEMENT 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 0.00 0.00 0.00 0.00
MECH_FLR_1 0.00 0.00 0.00 0.00
STORAGE_FLR_1 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 0.00 0.00 0.00 0.00
CAFE_FLR_1 0.00 0.00 0.00 0.00
LOBBY_FLR_1 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 0.00 2.83 0.00 2.83
ROOM_2_FLR_3 0.00 6.83 0.00 6.83
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 0.00 17.83 0.00 17.83
ROOM_5_FLR_3 0.00 1.67 0.00 1.67
ROOM_6_FLR_3 0.00 27.50 0.00 27.50
CORRIDOR_FLR_3 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 0.00 4.67 0.00 4.67
ROOM_2_FLR_6 0.00 16.33 0.00 16.33
ROOM_3_MULT9_FLR_6 0.00 7.33 0.00 7.33
BANQUET_FLR_6 0.00 0.00 0.00 0.00
DINING_FLR_6 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 0.00 0.00 0.00 0.00
Facility 0.00 56.00 0.00 56.00
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:51

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 61.74 106.50 4826.41 1.015 0.000 0.000 0.000
RETAIL_1_FLR_1 6.28 10.83 265.76 2.405 0.061 0.000 0.000
RETAIL_2_FLR_1 7.27 12.54 307.76 1.494 0.020 0.000 0.000
MECH_FLR_1 1.54 2.65 650.80 0.557 0.023 0.000 0.000
STORAGE_FLR_1 1.18 2.04 375.47 0.567 0.023 0.000 0.000
LAUNDRY_FLR_1 4.87 8.40 309.22 24.138 0.065 0.000 0.000
CAFE_FLR_1 82.49 142.30 748.35 3.791 0.048 0.000 0.000
LOBBY_FLR_1 244.88 422.44 5183.56 1.833 0.020 0.000 0.000
ROOM_1_FLR_3 0.95 1.50 118.94 0.356 0.079 0.000 0.093
ROOM_2_FLR_3 0.95 1.50 118.93 0.356 0.079 0.000 0.095
ROOM_3_MULT19_FLR_3   1.50 74.75        
ROOM_4_MULT19_FLR_3 0.95 1.50 74.77 0.404 0.035 0.000 0.157
ROOM_5_FLR_3 0.95 1.50 118.94 0.356 0.079 0.000 0.093
ROOM_6_FLR_3 0.95 1.50 118.93 0.356 0.079 0.000 0.101
CORRIDOR_FLR_3 12.15 20.96 1186.91 0.601 0.010 0.000 0.000
ROOM_1_FLR_6 0.95 1.50 118.94 0.356 0.079 0.000 0.104
ROOM_2_FLR_6 0.95 1.50 118.93 0.356 0.079 0.000 0.097
ROOM_3_MULT9_FLR_6 0.95 1.50 74.77 0.404 0.064 0.000 0.166
BANQUET_FLR_6 144.86 249.90 1010.89 4.909 0.023 0.000 0.000
DINING_FLR_6 144.86 249.90 1010.89 5.297 0.023 0.000 0.000
KITCHEN_FLR_6 12.89 22.24 314.87 22.320 0.066 0.000 0.000
CORRIDOR_FLR_6 12.86 22.18 1256.16 1.123 0.016 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 61.74 106.50 4826.41 0.990 0.000 0.000 0.000
RETAIL_1_FLR_1 6.28 10.83 265.76 2.295 0.001 0.000 0.000
RETAIL_2_FLR_1 7.27 12.54 307.76 1.448 0.000 0.000 0.000
MECH_FLR_1 1.54 2.65 650.80 0.543 0.000 0.000 0.000
STORAGE_FLR_1 1.18 2.04 375.47 0.552 0.000 0.000 0.000
LAUNDRY_FLR_1 4.87 8.40 309.22 20.779 0.001 0.000 0.000
CAFE_FLR_1 82.49 142.30 748.35 3.618 0.001 0.000 0.000
LOBBY_FLR_1 244.88 422.44 5183.56 1.764 0.000 0.000 0.000
ROOM_1_FLR_3 0.95 1.50 118.94 0.000 0.001 0.000 0.000
ROOM_2_FLR_3 0.95 1.50 118.93 0.000 0.001 0.000 0.000
ROOM_3_MULT19_FLR_3   1.50 74.75        
ROOM_4_MULT19_FLR_3 0.95 1.50 74.77 0.000 0.001 0.000 0.000
ROOM_5_FLR_3 0.95 1.50 118.94 0.000 0.001 0.000 0.000
ROOM_6_FLR_3 0.95 1.50 118.93 0.000 0.001 0.000 0.000
CORRIDOR_FLR_3 12.15 20.96 1186.91 0.586 0.000 0.000 0.000
ROOM_1_FLR_6 0.95 1.50 118.94 0.000 0.001 0.000 0.000
ROOM_2_FLR_6 0.95 1.50 118.93 0.000 0.001 0.000 0.000
ROOM_3_MULT9_FLR_6 0.95 1.50 74.77 0.000 0.001 0.000 0.000
BANQUET_FLR_6 144.86 249.90 1010.89 4.114 0.000 0.000 0.000
DINING_FLR_6 144.86 249.90 1010.89 4.320 0.000 0.000 0.000
KITCHEN_FLR_6 12.89 22.24 314.87 13.846 0.001 0.000 0.000
CORRIDOR_FLR_6 12.86 22.18 1256.16 1.095 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2024-07-03 12:21:51

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
BASEMENT VAV WITH REHEAT 61.74 106.50 4826.41 1978.83 0.0000 0.854
RETAIL_1_FLR_1 VAV WITH REHEAT 6.28 10.83 265.76 67.07 0.0000 0.079
RETAIL_2_FLR_1 VAV WITH REHEAT 7.27 12.54 307.76 77.67 0.0000 0.092
MECH_FLR_1 VAV WITH REHEAT 1.54 2.65 650.80 164.24 0.0000 0.000
STORAGE_FLR_1 VAV WITH REHEAT 1.18 2.04 375.47 94.76 0.0000 0.058
LAUNDRY_FLR_1 VAV WITH REHEAT 4.87 8.40 309.22 78.04 0.0000 0.000
CAFE_FLR_1 VAV WITH REHEAT 82.49 142.30 748.35 188.86 0.0000 0.173
LOBBY_FLR_1 VAV WITH REHEAT 244.88 422.44 5183.56 1308.19 0.0000 1.894
ROOM_1_FLR_3 FLR_3_DOAS 0.95 1.50 118.94 39.02 0.0000 0.062
ROOM_2_FLR_3 FLR_3_DOAS 0.95 1.50 118.93 39.02 0.0000 0.062
ROOM_3_MULT19_FLR_3 FLR_3_DOAS   1.50 74.75 24.52 0.0000 0.837
ROOM_4_MULT19_FLR_3 FLR_3_DOAS 0.95 1.50 74.77 24.53 0.0000 0.837
ROOM_5_FLR_3 FLR_3_DOAS 0.95 1.50 118.94 39.02 0.0000 0.062
ROOM_6_FLR_3 FLR_3_DOAS 0.95 1.50 118.93 39.02 0.0000 0.062
CORRIDOR_FLR_3 VAV WITH REHEAT 12.15 20.96 1186.91 389.40 0.0000 0.475
ROOM_1_FLR_6 FLR_3_DOAS 0.95 1.50 118.94 39.02 0.0000 0.015
ROOM_2_FLR_6 FLR_3_DOAS 0.95 1.50 118.93 39.02 0.0000 0.015
ROOM_3_MULT9_FLR_6 FLR_3_DOAS 0.95 1.50 74.77 24.53 0.0000 0.099
BANQUET_FLR_6 VAV WITH REHEAT 144.86 249.90 1010.89 331.66 0.0000 1.188
DINING_FLR_6 VAV WITH REHEAT 144.86 249.90 1010.89 331.66 0.0000 1.188
KITCHEN_FLR_6 VAV WITH REHEAT 12.89 22.24 314.87 103.30 0.0000 0.367
CORRIDOR_FLR_6 VAV WITH REHEAT 12.86 22.18 1256.16 412.12 0.0000 0.126
Total Facility   872.55 1604.23 35184.81 11345.29 0.0000 137.081


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
BASEMENT 42043451.99 0.00 42043451.99 0.00 42043451.99 26946214.98 0.00 0.00 8760.00 0.00
RETAIL_1_FLR_1 5503108.42 0.00 5503108.42 139545.61 5642654.03 2498216.28 0.00 0.00 8760.00 0.00
RETAIL_2_FLR_1 3945053.09 0.00 3945053.09 53864.78 3998917.88 2892943.94 0.00 0.00 8760.00 0.00
MECH_FLR_1 3121400.88 0.00 3121400.88 127304.34 3248705.23 0.00 0.00 0.00 8760.00 0.00
STORAGE_FLR_1 1831828.56 0.00 1831828.56 73447.59 1905276.15 1821682.01 25.33 8734.67 0.00 0.00
LAUNDRY_FLR_1 64123756.07 0.00 64123756.07 173827.58 64297583.65 0.00 0.00 0.00 8760.00 0.00
CAFE_FLR_1 24303963.84 0.00 24303963.84 308473.47 24612437.31 14544917.54 0.00 0.00 8760.00 0.00
LOBBY_FLR_1 81361980.28 0.00 81361980.28 881379.17 82243359.45 59728886.00 0.00 0.00 8760.00 0.00
ROOM_1_FLR_3 1460156.71 95273.53 1555430.24 80996.32 1636426.56 1946875.62 2190.00 5347.50 1222.50 0.00
ROOM_2_FLR_3 1459985.63 96490.54 1556476.18 80990.14 1637466.32 1946647.51 2190.00 5439.46 1130.54 0.00
ROOM_3_MULT19_FLR_3 1099911.97 0.00 1099911.97 22598.88 1122510.85 26397887.27 8395.00 365.00 0.00 365.00
ROOM_4_MULT19_FLR_3 19803829.30 100817.07 19904646.36 22605.06 19927251.42 26405105.73 2190.00 5360.28 1209.72 0.00
ROOM_5_FLR_3 1460156.71 95446.02 1555602.74 80996.32 1636599.06 1946875.62 2190.00 5347.50 1222.50 0.00
ROOM_6_FLR_3 1459985.63 103391.06 1563376.70 80990.14 1644366.84 1946647.51 2190.00 5347.50 1222.50 0.00
CORRIDOR_FLR_3 24548990.16 0.00 24548990.16 97940.85 24646931.01 14972100.18 0.00 0.00 8760.00 0.00
ROOM_1_FLR_6 365039.18 107145.54 472184.72 81012.99 553197.70 486718.90 1886.87 5357.11 1516.02 0.00
ROOM_2_FLR_6 364996.41 98531.53 463527.94 81006.80 544534.74 486661.88 1944.29 5524.49 1291.23 0.00
ROOM_3_MULT9_FLR_6 2345190.31 106999.30 2452189.61 41449.08 2493638.69 3126920.42 2190.00 5347.50 1222.50 0.00
BANQUET_FLR_6 42390036.42 0.00 42390036.42 197813.35 42587849.77 37458366.31 3752.91 255.45 4751.63 0.00
DINING_FLR_6 45740267.16 0.00 45740267.16 197813.35 45938080.51 37458366.31 0.00 0.00 8760.00 0.00
KITCHEN_FLR_6 60076188.73 0.00 60076188.73 177088.81 60253277.55 11584760.86 0.00 0.00 8760.00 0.00
CORRIDOR_FLR_6 12146765.25 0.00 12146765.25 173324.65 12320089.90 3961413.96 0.00 0.00 8760.00 0.00
Total Facility 0.21E+10 10393172.37 0.21E+10 8162099.07 0.21E+10 0.43E+10 8760.00 8759.17 8760.00 365.00


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
BASEMENT 1.3332 0.0000 1.3332 0.0000 1.3332 0.8545 0.00 0.00 8760.00
RETAIL_1_FLR_1 0.1745 0.0000 0.1745 0.0044 0.1789 0.0792 0.00 0.00 8760.00
RETAIL_2_FLR_1 0.1251 0.0000 0.1251 0.0017 0.1268 0.0917 0.00 0.00 8760.00
MECH_FLR_1 0.0990 0.0000 0.0990 0.0040 0.1030 0.0000 0.00 0.00 8760.00
STORAGE_FLR_1 0.0581 0.0000 0.0581 0.0023 0.0604 0.0578 25.33 8734.67 0.00
LAUNDRY_FLR_1 2.0334 0.0000 2.0334 0.0055 2.0389 0.0000 0.00 0.00 8760.00
CAFE_FLR_1 0.7707 0.0000 0.7707 0.0098 0.7805 0.4612 0.00 0.00 8760.00
LOBBY_FLR_1 2.5800 0.0000 2.5800 0.0279 2.6079 1.8940 0.00 0.00 8760.00
ROOM_1_FLR_3 0.0463 0.0030 0.0493 0.0026 0.0519 0.0617 2190.00 5347.50 1222.50
ROOM_2_FLR_3 0.0463 0.0031 0.0494 0.0026 0.0519 0.0617 2190.00 5439.46 1130.54
ROOM_4_MULT19_FLR_3 0.6280 0.0032 0.6312 0.0007 0.6319 0.8373 2190.00 5360.28 1209.72
ROOM_5_FLR_3 0.0463 0.0030 0.0493 0.0026 0.0519 0.0617 2190.00 5347.50 1222.50
ROOM_6_FLR_3 0.0463 0.0033 0.0496 0.0026 0.0521 0.0617 2190.00 5347.50 1222.50
CORRIDOR_FLR_3 0.7784 0.0000 0.7784 0.0031 0.7815 0.4748 0.00 0.00 8760.00
ROOM_1_FLR_6 0.0116 0.0034 0.0150 0.0026 0.0175 0.0154 1886.87 5357.11 1516.02
ROOM_2_FLR_6 0.0116 0.0031 0.0147 0.0026 0.0173 0.0154 1944.29 5524.49 1291.23
ROOM_3_MULT9_FLR_6 0.0744 0.0034 0.0778 0.0013 0.0791 0.0992 2190.00 5347.50 1222.50
BANQUET_FLR_6 1.3442 0.0000 1.3442 0.0063 1.3505 1.1878 3752.91 255.45 4751.63
DINING_FLR_6 1.4504 0.0000 1.4504 0.0063 1.4567 1.1878 0.00 0.00 8760.00
KITCHEN_FLR_6 1.9050 0.0000 1.9050 0.0056 1.9106 0.3674 0.00 0.00 8760.00
CORRIDOR_FLR_6 0.3852 0.0000 0.3852 0.0055 0.3907 0.1256 0.00 0.00 8760.00
Total Facility 64.5317 0.3296 64.8613 0.2044 65.0657 73.7518 8760.00 8759.17 8760.00


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
FLR_3_DOAS 41645591.30 804094.58 42449685.88 64690340.46 8758.83 1.17 0.00 0.00
VAV WITH REHEAT 0.57E+09 0.00 0.57E+09 0.21E+09 0.00 0.00 8760.00 0.00


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
FLR_3_DOAS 1.3206 0.0255 1.3461 2.0513 8758.83 1.17 0.00
VAV WITH REHEAT 18.2076 0.0000 18.2076 6.7817 0.00 0.00 8760.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
FLR_3_DOAS 0.00 0.00 0.00 0.00 6935.00 0.00 0.00 0.00 0.00 0.00
VAV WITH REHEAT 0.00 0.00 7631.82 0.00 0.00 0.00 1128.18 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
FLR_3_DOAS 0.0000 0.0000 0.0000 0.0000 1.6681 0.0000 0.0000 0.0000 0.0000 0.0000
VAV WITH REHEAT 0.0000 0.0000 18.2966 0.0000 0.0000 0.0000 17.6214 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:51

Surfaces by Class

Total Outdoors
Wall 119 44
Floor 25 0
Roof 33 11
Internal Mass 22 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 30 30
Door 6 6
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 2
Conditioned Zones 22
Unconditioned Zones 0
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 1329
Defaulted Fields 1181
Fields with Defaults 3960
Autosized Fields 347
Autosizable Fields 400
Autocalculated Fields 280
Autocalculatable Fields 539



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2024-07-03 12:21:51

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 4867.77 63071.83 13-MAY-05:00 326139.69 29-SEP-19:00
Electricity:Building 2448.58 31319.00 03-JUN-05:00 151313.73 02-JAN-20:10
Electricity:Zone:BASEMENT 304.40 3493.55 02-JAN-02:10 22822.84 02-JAN-20:10
Electricity:SpaceType:GENERAL 2441.49 31177.85 03-JUN-05:00 151072.40 02-JAN-20:10
InteriorLights:Electricity 783.31 6975.88 03-JUN-05:00 64632.59 02-JAN-20:10
InteriorLights:Electricity:Zone:BASEMENT 161.29 1465.65 02-JAN-02:10 13190.31 02-JAN-20:10
InteriorLights:Electricity:SpaceType:GENERAL 783.31 6975.88 03-JUN-05:00 64632.59 02-JAN-20:10
LightsWired:InteriorLights:Electricity 783.31 6975.88 03-JUN-05:00 64632.59 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:BASEMENT 161.29 1465.65 02-JAN-02:10 13190.31 02-JAN-20:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 783.31 6975.88 03-JUN-05:00 64632.59 02-JAN-20:10
Electricity:Zone:RETAIL_1_FLR_1 17.49 210.74 02-JAN-02:10 1283.20 02-JAN-20:10
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 7.31 66.40 02-JAN-02:10 597.59 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 7.31 66.40 02-JAN-02:10 597.59 02-JAN-20:10
Electricity:Zone:RETAIL_2_FLR_1 20.26 244.03 02-JAN-02:10 1485.95 02-JAN-20:10
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 8.46 76.89 02-JAN-02:10 692.02 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 8.46 76.89 02-JAN-02:10 692.02 02-JAN-20:10
Electricity:Zone:MECH_FLR_1 20.84 252.75 02-JAN-02:10 1523.62 02-JAN-20:10
InteriorLights:Electricity:Zone:MECH_FLR_1 8.37 76.02 02-JAN-02:10 684.18 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 8.37 76.02 02-JAN-02:10 684.18 02-JAN-20:10
Electricity:Zone:STORAGE_FLR_1 6.68 78.96 02-JAN-02:10 493.99 02-JAN-20:10
InteriorLights:Electricity:Zone:STORAGE_FLR_1 3.08 27.98 02-JAN-02:10 251.84 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 3.08 27.98 02-JAN-02:10 251.84 02-JAN-20:10
Electricity:Zone:LAUNDRY_FLR_1 71.91 998.82 02-JAN-02:10 4897.88 02-JAN-20:10
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 3.98 36.12 02-JAN-02:10 325.08 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 3.98 36.12 02-JAN-02:10 325.08 02-JAN-20:10
Electricity:Zone:CAFE_FLR_1 28.68 367.70 13-MAY-05:00 2666.80 02-JAN-20:10
InteriorLights:Electricity:Zone:CAFE_FLR_1 14.34 83.19 01-JAN-13:10 1701.53 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 14.34 83.19 01-JAN-13:10 1701.53 02-JAN-20:10
Electricity:Zone:LOBBY_FLR_1 259.15 3142.86 03-JUN-05:00 19534.01 02-JAN-20:10
InteriorLights:Electricity:Zone:LOBBY_FLR_1 110.15 1031.45 03-JUN-05:00 9504.80 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 110.15 1031.45 03-JUN-05:00 9504.80 02-JAN-20:10
Electricity:Zone:ROOM_1_FLR_3 19.72 257.38 01-JAN-02:10 1438.51 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 9.24 78.27 01-JAN-02:10 711.53 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 9.24 78.27 01-JAN-02:10 711.53 01-JAN-19:10
Electricity:Zone:ROOM_2_FLR_3 19.72 257.35 01-JAN-02:10 1438.34 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 9.24 78.26 01-JAN-02:10 711.45 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 9.24 78.26 01-JAN-02:10 711.45 01-JAN-19:10
Electricity:Zone:ROOM_3_MULT19_FLR_3 305.38 4267.82 01-JAN-02:10 22404.45 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 110.39 934.58 01-JAN-02:10 8496.21 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 110.39 934.58 01-JAN-02:10 8496.21 01-JAN-19:10
Electricity:Zone:ROOM_4_MULT19_FLR_3 305.47 4268.99 01-JAN-02:10 22410.58 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 110.42 934.84 01-JAN-02:10 8498.53 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 110.42 934.84 01-JAN-02:10 8498.53 01-JAN-19:10
Electricity:Zone:ROOM_5_FLR_3 19.72 257.38 01-JAN-02:10 1438.51 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 9.24 78.27 01-JAN-02:10 711.53 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 9.24 78.27 01-JAN-02:10 711.53 01-JAN-19:10
Electricity:Zone:ROOM_6_FLR_3 19.72 257.35 01-JAN-02:10 1438.34 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 9.24 78.26 01-JAN-02:10 711.45 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 9.24 78.26 01-JAN-02:10 711.45 01-JAN-19:10
Electricity:Zone:CORRIDOR_FLR_3 91.34 829.92 02-JAN-02:10 7469.27 02-JAN-20:10
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 91.34 829.92 02-JAN-02:10 7469.27 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 91.34 829.92 02-JAN-02:10 7469.27 02-JAN-20:10
Electricity:Zone:ROOM_1_FLR_6 4.93 64.34 01-JAN-02:10 359.63 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 2.31 19.57 01-JAN-02:10 177.88 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 2.31 19.57 01-JAN-02:10 177.88 01-JAN-19:10
Electricity:Zone:ROOM_2_FLR_6 4.93 64.34 01-JAN-02:10 359.59 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 2.31 19.56 01-JAN-02:10 177.86 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 2.31 19.56 01-JAN-02:10 177.86 01-JAN-19:10
Electricity:Zone:ROOM_3_MULT9_FLR_6 36.17 505.54 01-JAN-02:10 2653.88 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 13.08 110.70 01-JAN-02:10 1006.40 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 13.08 110.70 01-JAN-02:10 1006.40 01-JAN-19:10
Electricity:Zone:BANQUET_FLR_6 207.05 2514.90 27-MAY-05:00 9735.93 02-JAN-20:10
InteriorLights:Electricity:Zone:BANQUET_FLR_6 31.19 265.60 27-MAY-05:00 2988.03 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 31.19 265.60 27-MAY-05:00 2988.03 02-JAN-20:10
Electricity:Zone:DINING_FLR_6 207.05 2514.90 27-MAY-05:00 9735.93 02-JAN-20:10
InteriorLights:Electricity:Zone:DINING_FLR_6 31.19 265.60 27-MAY-05:00 2988.03 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 31.19 265.60 27-MAY-05:00 2988.03 02-JAN-20:10
Electricity:Zone:KITCHEN_FLR_6 453.81 6249.79 02-JAN-02:10 18934.39 01-JAN-11:10
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 12.97 117.87 02-JAN-02:10 1060.81 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 12.97 117.87 02-JAN-02:10 1060.81 02-JAN-20:10
Electricity:Zone:CORRIDOR_FLR_6 24.17 219.59 02-JAN-02:10 1976.27 02-JAN-20:10
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 24.17 219.59 02-JAN-02:10 1976.27 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 24.17 219.59 02-JAN-02:10 1976.27 02-JAN-20:10
InteriorEquipment:Electricity 1658.18 24201.97 02-JAN-02:10 89171.45 02-JAN-07:10
InteriorEquipment:Electricity:Zone:BASEMENT 143.11 2027.90 02-JAN-02:10 9632.53 02-JAN-20:10
InteriorEquipment:Electricity:SpaceType:GENERAL 1658.18 24201.97 02-JAN-02:10 89171.45 02-JAN-07:10
MiscPlug:InteriorEquipment:Electricity 872.72 13712.59 02-JAN-02:10 59188.31 02-JAN-07:10
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT 143.11 2027.90 02-JAN-02:10 9632.53 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 872.72 13712.59 02-JAN-02:10 59188.31 02-JAN-07:10
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 10.19 144.34 02-JAN-02:10 685.60 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 10.19 144.34 02-JAN-02:10 685.60 02-JAN-20:10
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 11.79 167.14 02-JAN-02:10 793.93 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 11.79 167.14 02-JAN-02:10 793.93 02-JAN-20:10
InteriorEquipment:Electricity:Zone:MECH_FLR_1 12.47 176.73 02-JAN-02:10 839.45 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 12.47 176.73 02-JAN-02:10 839.45 02-JAN-20:10
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 3.60 50.98 02-JAN-02:10 242.16 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 3.60 50.98 02-JAN-02:10 242.16 02-JAN-20:10
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 67.94 962.69 02-JAN-02:10 4572.80 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 67.94 962.69 02-JAN-02:10 4572.80 02-JAN-20:10
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 14.34 203.22 02-JAN-02:10 965.27 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 14.34 203.22 02-JAN-02:10 965.27 02-JAN-20:10
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 149.00 2111.41 02-JAN-02:10 10029.21 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 149.00 2111.41 02-JAN-02:10 10029.21 02-JAN-20:10
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 10.48 126.43 02-JAN-10:10 948.23 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 10.48 126.43 02-JAN-10:10 948.23 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 10.48 126.42 02-JAN-10:10 948.12 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 10.48 126.42 02-JAN-10:10 948.12 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 195.00 2352.88 02-JAN-10:10 17646.57 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 195.00 2352.88 02-JAN-10:10 17646.57 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 195.05 2353.52 02-JAN-10:10 17651.40 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 195.05 2353.52 02-JAN-10:10 17651.40 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 10.48 126.43 02-JAN-10:10 948.23 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 10.48 126.43 02-JAN-10:10 948.23 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 10.48 126.42 02-JAN-10:10 948.12 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 10.48 126.42 02-JAN-10:10 948.12 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 2.62 31.61 02-JAN-10:10 237.06 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 2.62 31.61 02-JAN-10:10 237.06 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 2.62 31.60 02-JAN-10:10 237.03 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 2.62 31.60 02-JAN-10:10 237.03 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 23.10 278.71 02-JAN-10:10 2090.30 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 23.10 278.71 02-JAN-10:10 2090.30 01-JAN-08:10
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
Cooking:InteriorEquipment:Electricity 762.04 9746.88 01-JAN-00:10 29240.64 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL 762.04 9746.88 01-JAN-00:10 29240.64 01-JAN-07:10
InteriorEquipment:Electricity:Zone:DINING_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 433.74 5990.78 01-JAN-00:10 16487.34 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 410.33 5248.28 01-JAN-00:10 15744.84 01-JAN-07:10
ReachInFreezer:InteriorEquipment:Electricity 14.43 457.50 01-JAN-00:10 457.50 01-JAN-00:10
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 14.43 457.50 01-JAN-00:10 457.50 01-JAN-00:10
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL 14.43 457.50 01-JAN-00:10 457.50 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity 8.99 285.00 01-JAN-00:10 285.00 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 8.99 285.00 01-JAN-00:10 285.00 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL 8.99 285.00 01-JAN-00:10 285.00 01-JAN-00:10
Refrigeration:Electricity 62.32 1114.62 03-FEB-23:30 3263.16 14-JUL-06:20
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 7.09 88.82 02-JAN-11:30 2093.44 01-JAN-11:10
General:Refrigeration:Electricity 7.09 88.82 02-JAN-11:30 2093.44 01-JAN-11:10
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 7.09 88.82 02-JAN-11:30 2093.44 01-JAN-11:10
Electricity:Plant 890.78 3080.87 02-JAN-03:00 164478.81 16-OCT-10:50
LowTempRefrigeration:Refrigeration:Electricity 20.47 0.00 01-JAN-11:10 1893.15 30-SEP-10:50
MedTempRefrigeration:Refrigeration:Electricity 34.75 928.84 07-JAN-02:30 1203.27 11-FEB-14:10
Fans:Electricity 520.65 12170.16 30-MAR-07:10 34789.12 16-OCT-22:00
Fans:Electricity:Zone:ROOM_1_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_2_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_5_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_6_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_1_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_2_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Electricity:HVAC 542.42 12769.01 29-JAN-03:00 35622.63 16-OCT-22:00
ExteriorEquipment:Electricity 813.77 9999.82 02-JAN-02:20 49607.07 18-JAN-07:20
Transformer:ExteriorEquipment:Electricity 21.77 381.01 27-MAY-05:00 1291.59 02-JAN-21:10
ElectricityPurchased:Facility 4867.77 63071.83 13-MAY-05:00 326139.69 29-SEP-19:00
ElectricityPurchased:Plant 4867.77 63071.83 13-MAY-05:00 326139.69 29-SEP-19:00
Cogeneration:ElectricityPurchased 4867.77 63071.83 13-MAY-05:00 326139.69 29-SEP-19:00
General:Cogeneration:ElectricityPurchased 4867.77 63071.83 13-MAY-05:00 326139.69 29-SEP-19:00
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 4867.77 63071.83 13-MAY-05:00 326139.69 29-SEP-19:00
ElectricityNet:Plant 4867.77 63071.83 13-MAY-05:00 326139.69 29-SEP-19:00
Cogeneration:ElectricityNet 4867.77 63071.83 13-MAY-05:00 326139.69 29-SEP-19:00
General:Cogeneration:ElectricityNet 4867.77 63071.83 13-MAY-05:00 326139.69 29-SEP-19:00
General:Fans:Electricity 520.65 12170.16 30-MAR-07:10 34789.12 16-OCT-22:00
ExteriorLights:Electricity 193.98 0.00 01-JAN-07:00 12338.45 01-JAN-00:10
General:ExteriorLights:Electricity 193.98 0.00 01-JAN-07:00 12338.45 01-JAN-00:10
ElevatorLift:ExteriorEquipment:Electricity 789.09 9600.00 01-JAN-00:10 48128.80 01-JAN-07:10
ElevatorLightsFan:ExteriorEquipment:Electricity 2.91 18.80 01-JAN-00:10 188.00 01-JAN-07:10
WaterSystems:Electricity 94.78 1222.49 15-JUL-00:10 4752.55 09-JAN-07:10
Water Heater:WaterSystems:Electricity 94.78 1222.49 15-JUL-00:10 4752.55 09-JAN-07:10
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:Electricity 664.89 0.00 01-JAN-00:30 156617.73 16-OCT-11:10
General:Cooling:Electricity 664.89 0.00 01-JAN-00:30 156617.73 16-OCT-11:10
Pumps:Electricity 75.88 61.88 27-MAR-13:40 4250.92 29-SEP-15:20
General:Pumps:Electricity 75.88 61.88 27-MAR-13:40 4250.92 29-SEP-15:20
WIRED_LTG_ELECTRICITY 27.57 0.00 01-JAN-00:10 2275.07 02-JAN-20:20


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 5170.50 23626.99 04-AUG-02:40 466011.65 29-MAR-18:00
NaturalGas:Building 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
NaturalGas:Zone:LAUNDRY_FLR_1 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
NaturalGas:SpaceType:GENERAL 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
InteriorEquipment:NaturalGas 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
InteriorEquipment:NaturalGas:SpaceType:GENERAL 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
Laundry:InteriorEquipment:NaturalGas 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
NaturalGas:Zone:KITCHEN_FLR_6 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
Cooking:InteriorEquipment:NaturalGas 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
NaturalGas:Plant 3381.66 10265.09 04-AUG-02:40 378847.74 28-DEC-21:40
WaterSystems:NaturalGas 2478.95 10265.09 04-AUG-02:40 226542.04 06-FEB-21:40
Water Heater:WaterSystems:NaturalGas 2478.95 10265.09 04-AUG-02:40 226542.04 06-FEB-21:40
Heating:NaturalGas 902.72 0.00 02-JAN-11:10 191268.39 08-JAN-07:00
Boiler:Heating:NaturalGas 902.72 0.00 02-JAN-11:10 191268.39 08-JAN-07:00


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
PlantLoopCoolingDemand:Facility 2816.68 0.00 01-JAN-00:10 502818.30 18-AUG-15:20
PlantLoopCoolingDemand:HVAC 2816.68 0.00 01-JAN-00:10 502818.30 18-AUG-15:20
CoolingCoils:PlantLoopCoolingDemand 2816.68 0.00 01-JAN-00:10 502818.30 18-AUG-15:20


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 9857.19 0.00 02-JAN-01:10 0.00 05-MAY-20:30
Water:Plant 9857.19 0.00 02-JAN-01:10 0.00 05-MAY-20:30
WaterSystems:Water 9857.19 0.00 02-JAN-01:10 0.00 05-MAY-20:30
Water Heater:WaterSystems:Water 5742.51 0.00 02-JAN-01:10 0.00 02-JAN-19:10
MainsWater:Facility 9857.19 0.00 02-JAN-01:10 0.00 05-MAY-20:30
MainsWater:Plant 9857.19 0.00 02-JAN-01:10 0.00 05-MAY-20:30
WaterSystems:MainsWater 9857.19 0.00 02-JAN-01:10 0.00 05-MAY-20:30
Water Heater:WaterSystems:MainsWater 5742.51 0.00 02-JAN-01:10 0.00 02-JAN-19:10
WaterUse:WaterSystems:Water 4114.69 0.00 02-JAN-01:10 0.00 05-JAN-07:10
WaterUse:WaterSystems:MainsWater 4114.69 0.00 02-JAN-01:10 0.00 05-JAN-07:10


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 16285.77 128335.22 27-MAR-13:40 1929063.16 18-AUG-15:20
EnergyTransfer:Building 5105.28 93984.84 29-MAR-12:00 299571.61 16-OCT-18:10
EnergyTransfer:Zone:KITCHEN_FLR_6 734.22 11871.22 07-JAN-03:00 35322.44 30-SEP-10:50
Refrigeration:EnergyTransfer 185.64 3947.76 07-JAN-02:30 10368.69 14-JUL-06:20
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 92.82 1973.88 07-JAN-02:30 5184.35 14-JUL-06:20
General:Refrigeration:EnergyTransfer 92.82 1973.88 07-JAN-02:30 5184.35 14-JUL-06:20
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 92.82 1973.88 07-JAN-02:30 5184.35 14-JUL-06:20
EnergyTransfer:Plant 7787.20 20688.02 27-MAR-13:40 1164129.08 18-AUG-15:20
LowTempRefrigeration:Refrigeration:EnergyTransfer 21.67 0.00 01-JAN-11:10 2686.44 01-JAN-11:40
MedTempRefrigeration:Refrigeration:EnergyTransfer 71.15 1736.53 07-JAN-02:30 2559.81 11-FEB-14:10
EnergyTransfer:Zone:BASEMENT 397.71 9955.39 31-MAR-14:00 22096.14 08-JAN-07:00
Heating:EnergyTransfer 6.63 0.00 01-JAN-08:10 12730.16 28-MAR-08:10
Heating:EnergyTransfer:Zone:BASEMENT 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer 6.63 0.00 01-JAN-08:10 12730.16 28-MAR-08:10
General:Heating:EnergyTransfer:Zone:BASEMENT 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer 5005.82 91249.37 29-MAR-12:00 296025.88 16-OCT-18:10
Cooling:EnergyTransfer:Zone:BASEMENT 397.71 9955.39 31-MAR-14:00 22096.14 08-JAN-07:00
General:Cooling:EnergyTransfer 5005.82 91249.37 29-MAR-12:00 296025.88 16-OCT-18:10
General:Cooling:EnergyTransfer:Zone:BASEMENT 397.71 9955.39 31-MAR-14:00 22096.14 08-JAN-07:00
EnergyTransfer:Zone:RETAIL_1_FLR_1 45.48 5.79 30-MAR-06:10 4013.08 16-OCT-12:20
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 0.00 0.00 01-JAN-00:10 3.59 30-MAR-06:10
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 0.00 0.00 01-JAN-00:10 3.59 30-MAR-06:10
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 45.48 2.20 30-MAR-06:10 4013.08 16-OCT-12:20
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 45.48 2.20 30-MAR-06:10 4013.08 16-OCT-12:20
EnergyTransfer:Zone:RETAIL_2_FLR_1 37.47 786.84 29-MAR-12:10 1981.03 16-OCT-20:10
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 37.47 786.84 29-MAR-12:10 1981.03 16-OCT-20:10
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 37.47 786.84 29-MAR-12:10 1981.03 16-OCT-20:10
EnergyTransfer:Zone:MECH_FLR_1 27.56 414.79 30-MAR-10:00 1322.24 28-JAN-07:00
Heating:EnergyTransfer:Zone:MECH_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:MECH_FLR_1 27.56 414.79 30-MAR-10:00 1322.24 28-JAN-07:00
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 27.56 414.79 30-MAR-10:00 1322.24 28-JAN-07:00
EnergyTransfer:Zone:STORAGE_FLR_1 15.57 133.71 30-MAR-04:00 722.59 27-JAN-05:00
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 15.57 133.71 30-MAR-04:00 722.59 27-JAN-05:00
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 15.57 133.71 30-MAR-04:00 722.59 27-JAN-05:00
EnergyTransfer:Zone:LAUNDRY_FLR_1 606.94 10058.91 09-JAN-05:00 38380.00 29-SEP-20:00
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 606.94 10058.91 09-JAN-05:00 38380.00 29-SEP-20:00
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 606.94 10058.91 09-JAN-05:00 38380.00 29-SEP-20:00
EnergyTransfer:Zone:CAFE_FLR_1 235.51 2454.41 29-MAR-12:10 14055.17 19-NOV-11:00
Heating:EnergyTransfer:Zone:CAFE_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 235.51 2454.41 29-MAR-12:10 14055.17 19-NOV-11:00
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 235.51 2454.41 29-MAR-12:10 14055.17 19-NOV-11:00
EnergyTransfer:Zone:LOBBY_FLR_1 799.96 16745.69 29-MAR-11:40 38779.30 16-OCT-21:10
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 799.96 16745.69 29-MAR-11:40 38779.30 16-OCT-21:10
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 799.96 16745.69 29-MAR-11:40 38779.30 16-OCT-21:10
EnergyTransfer:Zone:ROOM_1_FLR_3 53.42 0.00 01-JAN-08:10 9821.08 30-SEP-15:10
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 0.65 0.00 01-JAN-07:50 1560.68 29-MAR-04:10
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 0.65 0.00 01-JAN-07:50 1560.68 29-MAR-04:10
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 52.77 0.00 01-JAN-00:10 9821.08 30-SEP-15:10
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 52.77 0.00 01-JAN-00:10 9821.08 30-SEP-15:10
EnergyTransfer:Zone:ROOM_2_FLR_3 33.47 0.00 01-JAN-08:10 9282.99 30-SEP-15:10
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 1.28 0.00 01-JAN-08:10 1665.98 30-MAR-08:10
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 1.28 0.00 01-JAN-08:10 1665.98 30-MAR-08:10
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 32.20 0.00 01-JAN-00:10 9282.99 30-SEP-15:10
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 32.20 0.00 01-JAN-00:10 9282.99 30-SEP-15:10
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 321.35 0.00 01-JAN-00:10 48790.83 16-OCT-12:20
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 321.35 0.00 01-JAN-00:10 48790.83 16-OCT-12:20
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 321.35 0.00 01-JAN-00:10 48790.83 16-OCT-12:20
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 362.92 0.00 01-JAN-08:10 63059.17 22-JUN-20:30
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 0.62 0.00 01-JAN-00:10 6339.37 03-JAN-16:10
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 0.62 0.00 01-JAN-00:10 6339.37 03-JAN-16:10
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 362.30 0.00 01-JAN-08:10 63059.17 22-JUN-20:30
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 362.30 0.00 01-JAN-08:10 63059.17 22-JUN-20:30
EnergyTransfer:Zone:ROOM_5_FLR_3 49.74 0.00 01-JAN-08:10 9425.59 15-OCT-08:10
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 0.73 0.00 01-JAN-07:10 1782.17 30-MAR-04:00
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 0.73 0.00 01-JAN-07:10 1782.17 30-MAR-04:00
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 49.01 0.00 01-JAN-00:10 9425.59 15-OCT-08:10
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 49.01 0.00 01-JAN-00:10 9425.59 15-OCT-08:10
EnergyTransfer:Zone:ROOM_6_FLR_3 32.10 0.00 01-JAN-08:10 9812.90 17-OCT-08:40
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 1.42 0.00 01-JAN-07:20 1867.66 30-MAR-04:00
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 1.42 0.00 01-JAN-07:20 1867.66 30-MAR-04:00
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 30.68 0.00 01-JAN-00:10 9812.90 17-OCT-08:40
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 30.68 0.00 01-JAN-00:10 9812.90 17-OCT-08:40
EnergyTransfer:Zone:CORRIDOR_FLR_3 210.89 2802.59 29-MAR-12:00 10386.74 28-JAN-07:00
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 210.89 2802.59 29-MAR-12:00 10386.74 28-JAN-07:00
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 210.89 2802.59 29-MAR-12:00 10386.74 28-JAN-07:00
EnergyTransfer:Zone:ROOM_1_FLR_6 12.83 0.00 01-JAN-08:10 2610.30 30-SEP-15:10
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 0.55 0.00 01-JAN-08:10 599.40 29-MAR-08:10
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 0.55 0.00 01-JAN-08:10 599.40 29-MAR-08:10
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 12.28 0.00 01-JAN-00:10 2610.30 30-SEP-15:10
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 12.28 0.00 01-JAN-00:10 2610.30 30-SEP-15:10
EnergyTransfer:Zone:ROOM_2_FLR_6 8.44 0.00 01-JAN-08:10 2454.70 17-AUG-15:20
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 0.95 0.00 01-JAN-08:10 646.27 30-MAR-08:10
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 0.95 0.00 01-JAN-08:10 646.27 30-MAR-08:10
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 7.49 0.00 01-JAN-00:10 2454.70 17-AUG-15:20
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 7.49 0.00 01-JAN-00:10 2454.70 17-AUG-15:20
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 84.58 0.00 01-JAN-08:10 13532.73 31-OCT-15:10
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 0.43 0.00 01-JAN-00:10 2252.40 30-MAR-04:00
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 0.43 0.00 01-JAN-00:10 2252.40 30-MAR-04:00
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 84.15 0.00 01-JAN-00:30 13532.73 31-OCT-15:10
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 84.15 0.00 01-JAN-00:30 13532.73 31-OCT-15:10
EnergyTransfer:Zone:BANQUET_FLR_6 445.90 9411.46 29-MAR-11:40 21449.45 29-SEP-21:10
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 445.90 9411.46 29-MAR-11:40 21449.45 29-SEP-21:10
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 445.90 9411.46 29-MAR-11:40 21449.45 29-SEP-21:10
EnergyTransfer:Zone:DINING_FLR_6 485.76 10428.89 29-MAR-11:40 22812.48 29-SEP-21:10
Heating:EnergyTransfer:Zone:DINING_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:DINING_FLR_6 485.76 10428.89 29-MAR-11:40 22812.48 29-SEP-21:10
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 485.76 10428.89 29-MAR-11:40 22812.48 29-SEP-21:10
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 641.40 9800.57 07-JAN-03:10 30305.06 30-SEP-10:50
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 641.40 9800.57 07-JAN-03:10 30305.06 30-SEP-10:50
EnergyTransfer:Zone:CORRIDOR_FLR_6 103.43 626.51 30-MAR-06:10 5183.82 30-SEP-13:40
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 103.43 626.51 30-MAR-06:10 5183.82 30-SEP-13:40
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 103.43 626.51 30-MAR-06:10 5183.82 30-SEP-13:40
PlantLoopHeatingDemand:Facility 1276.05 9088.53 04-AUG-01:00 178546.26 08-JAN-07:00
PlantLoopHeatingDemand:Plant 699.43 9088.53 04-AUG-01:00 48539.47 02-FEB-07:10
WaterSystems:PlantLoopHeatingDemand 699.43 9088.53 04-AUG-01:00 48539.47 02-FEB-07:10
General:WaterSystems:PlantLoopHeatingDemand 699.43 9088.53 04-AUG-01:00 48539.47 02-FEB-07:10
EnergyTransfer:HVAC 3393.30 228.60 27-MAR-11:50 502818.30 18-AUG-15:20
HeatingCoils:EnergyTransfer 576.62 0.00 02-JAN-11:10 151503.07 08-JAN-07:00
PlantLoopHeatingDemand:HVAC 576.62 0.00 02-JAN-11:10 151503.07 08-JAN-07:00
HeatingCoils:PlantLoopHeatingDemand 576.62 0.00 02-JAN-11:10 151503.07 08-JAN-07:00
CoolingCoils:EnergyTransfer 2816.68 0.00 01-JAN-00:10 502818.30 18-AUG-15:20
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
WaterSystems:EnergyTransfer 699.43 9088.53 04-AUG-01:00 48539.47 02-FEB-07:10
WaterUse:WaterSystems:EnergyTransfer 699.43 9088.53 04-AUG-01:00 48539.47 02-FEB-07:10
Boilers:EnergyTransfer 572.87 0.00 02-JAN-11:10 150697.24 08-JAN-07:00
Chillers:EnergyTransfer 2878.59 0.00 01-JAN-00:30 504857.75 18-AUG-15:20
HeatRejection:EnergyTransfer 3543.48 0.00 01-JAN-00:30 642206.78 18-AUG-15:20
General:HeatRejection:EnergyTransfer 3543.48 0.00 01-JAN-00:30 642206.78 18-AUG-15:20



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:51

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
BASEMENT 0.000 0.000 0.000 -397.710 0.000 0.000 142.425 161.294 143.105 0.000 0.000 0.000 0.002 0.000 0.000 0.000 0.000 -49.114
RETAIL_1_FLR_1 0.000 0.000 0.000 -45.483 0.000 0.000 15.377 7.307 10.186 21.133 0.000 0.020 0.791 0.000 -8.270 0.000 -1.060 -0.000
RETAIL_2_FLR_1 0.000 0.000 0.000 -37.473 0.000 0.000 16.680 8.462 11.795 0.000 0.000 0.009 0.992 0.000 0.000 0.000 -0.464 -0.000
MECH_FLR_1 0.000 0.000 0.000 -27.559 0.000 0.000 3.659 8.366 12.471 0.000 0.000 0.023 4.057 0.000 0.000 0.000 -1.018 -0.000
STORAGE_FLR_1 0.000 0.000 0.000 -15.571 0.000 0.000 2.857 3.079 3.598 0.000 0.000 0.014 6.589 0.000 0.000 0.000 -0.567 0.000
LAUNDRY_FLR_1 0.000 0.000 0.000 -606.944 0.000 0.000 11.372 3.975 658.131 0.000 0.000 0.037 0.000 0.000 0.000 0.000 -1.480 -65.092
CAFE_FLR_1 0.000 0.000 0.000 -235.512 0.000 0.000 187.611 14.344 14.341 58.393 0.000 0.046 0.000 0.000 -25.714 0.000 -2.706 -10.803
LOBBY_FLR_1 0.000 0.000 0.000 -799.961 0.000 0.000 550.958 110.149 148.998 77.575 0.000 0.142 0.000 0.000 -34.397 0.000 -7.872 -45.592
ROOM_1_FLR_3 1.901 -42.579 0.000 -11.437 0.000 0.000 9.652 9.244 10.478 43.594 0.000 0.103 1.984 0.000 -18.996 0.000 -3.945 -0.001
ROOM_2_FLR_3 3.161 -21.738 0.000 -12.341 0.000 0.000 9.433 9.243 10.477 30.902 0.000 0.066 0.000 0.000 -19.762 0.000 -4.901 -4.541
ROOM_3_MULT19_FLR_3 0.000 -304.672 0.000 -16.679 0.000 0.000 0.000 110.385 194.997 221.772 0.000 0.064 0.023 0.000 -162.123 0.000 -22.217 -21.526
ROOM_4_MULT19_FLR_3 5.402 -205.679 0.000 -161.378 0.000 0.000 181.595 110.415 195.050 66.147 0.000 0.545 0.001 0.000 -104.438 0.000 -52.410 -35.249
ROOM_5_FLR_3 2.073 -38.916 0.000 -11.439 0.000 0.000 9.646 9.244 10.478 40.476 0.000 0.102 0.833 0.000 -18.536 0.000 -3.962 -0.000
ROOM_6_FLR_3 3.380 -20.481 0.000 -12.156 0.000 0.000 9.498 9.243 10.477 27.617 0.000 0.065 0.000 0.000 -18.802 0.000 -4.791 -4.051
CORRIDOR_FLR_3 0.000 0.000 0.000 -210.891 0.000 0.000 117.195 91.336 0.000 36.638 0.000 0.074 0.000 0.000 -23.316 0.000 -3.058 -7.978
ROOM_1_FLR_6 1.125 -9.990 0.000 -2.860 0.000 0.000 2.415 2.311 2.620 10.761 0.000 0.026 0.000 0.000 -4.687 0.000 -1.034 -0.686
ROOM_2_FLR_6 1.692 -5.131 0.000 -3.097 0.000 0.000 2.355 2.311 2.619 7.603 0.000 0.016 0.000 0.000 -4.896 0.000 -1.237 -2.236
ROOM_3_MULT9_FLR_6 1.599 -66.931 0.000 -18.390 0.000 0.000 21.705 13.076 23.098 54.610 0.000 0.169 0.002 0.000 -21.937 0.000 -6.731 -0.268
BANQUET_FLR_6 0.000 0.000 0.000 -445.898 0.000 0.000 316.312 31.195 175.857 6.151 0.000 0.021 0.000 0.000 -14.214 0.000 -1.917 -67.506
DINING_FLR_6 0.000 0.000 0.000 -485.765 0.000 0.000 315.268 31.195 175.857 5.831 0.000 0.019 0.000 0.000 -14.677 0.000 -1.938 -25.791
KITCHEN_FLR_6 0.000 0.000 0.000 -641.388 0.000 0.000 28.413 12.972 550.372 18.652 0.000 0.016 42.911 0.000 -10.227 0.000 -1.721 0.000
CORRIDOR_FLR_6 0.000 0.000 0.000 -103.429 0.000 0.000 31.143 24.166 0.000 17.742 0.000 0.024 42.233 0.000 -10.522 0.000 -1.358 0.000
Total Facility 20.332 -716.118 0.000 -4303.358 0.000 0.000 1985.568 783.315 2365.005 745.596 0.000 1.602 100.419 0.000 -515.512 0.000 -126.385 -340.436


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 08-JAN-07:00 0.00 0.00 0.00 -22092.80 0.00 0.00 5811.90 4396.77 4055.80 0.00 0.00 0.00 7828.32 0.00 -0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 16-OCT-12:20 0.00 0.00 0.00 -4013.00 0.00 0.00 150.60 166.00 252.59 4697.51 0.00 56.73 0.00 0.00 -0.00 0.00 0.00 -1310.43
RETAIL_2_FLR_1 16-OCT-20:10 0.00 0.00 0.00 -1980.60 0.00 0.00 697.63 615.12 752.15 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -7.08 -77.21
MECH_FLR_1 28-JAN-07:00 0.00 0.00 0.00 -1322.05 0.00 0.00 151.90 228.06 353.45 0.00 0.00 0.00 681.35 0.00 -0.00 0.00 -92.71 0.00
STORAGE_FLR_1 27-JAN-04:55 0.00 0.00 0.00 -723.71 0.00 0.00 149.35 27.98 50.98 0.00 0.00 0.00 546.21 0.00 -0.00 0.00 -50.81 0.00
LAUNDRY_FLR_1 29-SEP-20:00 0.00 0.00 0.00 -38379.97 0.00 0.00 408.86 325.08 44299.38 0.00 0.00 6.40 0.00 0.00 -0.00 0.00 0.00 -6659.75
CAFE_FLR_1 19-NOV-11:00 0.00 0.00 0.00 -14060.48 0.00 0.00 4947.83 124.78 406.43 13663.13 0.00 22.79 0.00 0.00 -0.00 0.00 0.00 -5104.49
LOBBY_FLR_1 16-OCT-21:10 0.00 0.00 0.00 -38770.12 0.00 0.00 26440.96 6336.53 7389.94 0.00 0.00 0.00 374.35 0.00 -1582.72 0.00 -188.94 0.00
ROOM_1_FLR_3 14-OCT-08:61 0.00 -12542.93 0.00 -728.66 0.00 0.00 130.71 398.46 653.23 2466.85 0.00 59.20 9563.14 0.00 -0.00 0.00 0.00 0.00
ROOM_2_FLR_3 14-OCT-08:61 0.00 -12504.69 0.00 -769.57 0.00 0.00 125.46 398.41 653.15 1226.87 0.00 52.62 10817.75 0.00 -0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 16-OCT-12:20 0.00 -48791.04 0.00 0.00 0.00 0.00 0.00 2378.94 2352.88 55563.17 0.00 531.69 0.00 0.00 -0.00 0.00 0.00 -12035.63
ROOM_4_MULT19_FLR_3 14-OCT-08:61 0.00 -78682.06 0.00 -10587.34 0.00 0.00 2408.47 4759.18 12159.85 6684.88 0.00 268.35 62988.67 0.00 -0.00 0.00 0.00 0.00
ROOM_5_FLR_3 14-OCT-08:61 0.00 -11362.15 0.00 -743.36 0.00 0.00 130.71 398.46 653.23 7039.29 0.00 56.83 3826.99 0.00 -0.00 0.00 0.00 0.00
ROOM_6_FLR_3 17-OCT-08:21 0.00 -12633.17 0.00 -926.21 0.00 0.00 71.66 313.04 452.99 6544.11 0.00 25.63 6151.94 0.00 -0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 28-JAN-07:00 0.00 0.00 0.00 -10384.95 0.00 0.00 4812.51 2489.76 0.00 0.00 0.00 0.00 5211.61 0.00 -1843.42 0.00 -285.51 0.00
ROOM_1_FLR_6 26-OCT-15:01 0.00 -3244.86 0.00 -182.11 0.00 0.00 58.82 49.81 50.05 1591.70 0.00 0.00 1679.04 0.00 -0.00 0.00 -2.43 0.00
ROOM_2_FLR_6 14-OCT-08:61 0.00 -3143.32 0.00 -184.55 0.00 0.00 32.24 99.60 163.29 317.48 0.00 14.24 2701.02 0.00 -0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 14-OCT-08:61 0.00 -15520.15 0.00 -1185.10 0.00 0.00 294.11 563.59 1439.98 5466.68 0.00 65.61 8875.29 0.00 -0.00 0.00 0.00 0.00
BANQUET_FLR_6 29-SEP-21:10 0.00 0.00 0.00 -21449.74 0.00 0.00 15644.30 1992.02 6747.90 0.00 0.00 3.54 0.00 0.00 -214.81 0.00 0.00 -2723.21
DINING_FLR_6 29-SEP-21:10 0.00 0.00 0.00 -22812.92 0.00 0.00 15644.19 1992.02 6747.90 0.00 0.00 3.54 0.00 0.00 -230.92 0.00 0.00 -1343.81
KITCHEN_FLR_6 30-SEP-10:50 0.00 0.00 0.00 -30341.04 0.00 0.00 460.90 294.67 24259.91 2355.32 0.00 42.23 2928.02 0.00 -0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 30-SEP-13:40 0.00 0.00 0.00 -5184.16 0.00 0.00 462.68 548.96 0.00 2835.62 0.00 49.26 1287.64 0.00 -0.00 0.00 0.00 0.00
Total Facility 15-OCT-08:61 0.00 -176299.36 0.00 -156590.81 0.00 0.00 50316.26 24800.21 89868.82 97827.30 0.00 1709.04 68368.55 0.00 0.00 0.00 0.00 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 30-MAR-06:07 0.00 0.00 5.52 0.00 0.00 0.00 357.99 332.00 433.01 0.00 0.00 0.00 0.00 0.00 -695.28 0.00 -85.36 -347.88
RETAIL_2_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MECH_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 21-MAR-18:04 4230.03 414.75 0.00 -414.75 0.00 0.00 335.50 633.26 484.65 0.00 0.00 0.00 0.00 0.00 -1148.66 0.00 -91.03 -4443.75
ROOM_2_FLR_3 24-NOV-16:03 4212.92 418.39 0.00 -418.39 0.00 0.00 253.07 199.20 200.16 0.00 0.00 0.00 0.00 0.00 -288.82 0.00 -521.20 -4055.33
ROOM_3_MULT19_FLR_3 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 18-FEB-16:04 21716.38 5698.50 0.00 -5698.50 0.00 0.00 2615.43 2804.51 4118.66 0.00 0.00 0.00 0.00 0.00 -204.85 0.00 -10271.28 -20778.86
ROOM_5_FLR_3 16-NOV-16:04 4123.59 415.94 0.00 -415.94 0.00 0.00 235.28 199.23 200.18 0.00 0.00 0.00 0.00 0.00 -59.75 0.00 -577.35 -4121.18
ROOM_6_FLR_3 18-APR-15:04 4008.28 429.94 0.00 -429.94 0.00 0.00 238.16 199.20 200.16 777.86 0.00 0.00 0.00 0.00 -0.00 0.00 -671.02 -4752.64
CORRIDOR_FLR_3 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 16-JUN-15:04 1238.29 120.03 0.00 -120.03 0.00 0.00 58.82 49.81 50.05 191.11 0.00 0.00 0.00 0.00 -0.00 0.00 -109.50 -1478.58
ROOM_2_FLR_6 13-MAY-15:04 1222.33 110.77 0.00 -110.77 0.00 0.00 32.68 58.69 55.31 910.27 0.00 0.00 0.00 0.00 -0.00 0.00 -201.59 -2077.69
ROOM_3_MULT9_FLR_6 17-APR-15:04 5894.43 762.08 0.00 -762.08 0.00 0.00 529.39 281.79 441.28 1387.41 0.00 0.00 0.00 0.00 -0.00 0.00 -2185.70 -6348.61
BANQUET_FLR_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
DINING_FLR_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 20-MAR-15:04 -70353.78 123314.08 0.00 -123314.08 0.00 0.00 56840.82 16709.04 73912.59 4268.19 0.00 0.00 0.00 0.00 -1299.74 0.00 -18308.56 -61768.56



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:51

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
FLR_3_DOAS 2.0513 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.0513 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV WITH REHEAT 21.3005 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 21.1819 0.0000 1.0000 Not calculated 0.0000 0.0000    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
FLR_3_DOAS 2.0513 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.0513 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV WITH REHEAT 11.6514 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 11.6514 0.0000 1.0000 Not calculated 0.0000 0.0000    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
BASEMENT VAV WITH REHEAT 0.000000 106.4990 0.000432 1978.83 0.0000 1.0000 0.0000 1.000 0.0000
RETAIL_1_FLR_1 VAV WITH REHEAT 0.000000 10.8290 0.001181 67.07 0.0000 1.0000 0.0000 1.000 0.0000
RETAIL_2_FLR_1 VAV WITH REHEAT 0.000000 12.5400 0.001181 77.67 0.0000 1.0000 0.0000 1.000 0.0000
MECH_FLR_1 VAV WITH REHEAT 0.000000 2.6520 0.000000 164.24 0.0000 1.0000 0.0000 1.000 0.0000
STORAGE_FLR_1 VAV WITH REHEAT 0.000000 2.0400 0.000610 94.76 0.0000 1.0000 0.0000 1.000 0.0000
LAUNDRY_FLR_1 VAV WITH REHEAT 0.000000 8.4000 0.000000 78.04 0.0000 1.0000 0.0000 1.000 0.0000
CAFE_FLR_1 VAV WITH REHEAT 0.003540 142.3000 0.000914 188.86 0.0000 1.0000 0.0000 1.000 0.0000
LOBBY_FLR_1 VAV WITH REHEAT 0.000000 422.4350 0.001448 1308.19 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_1_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.09 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_2_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.07 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_3_MULT19_FLR_3 FLR_3_DOAS 0.000000 114.0000 0.000449 1863.81 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_4_MULT19_FLR_3 FLR_3_DOAS 0.000000 114.0000 0.000449 1864.32 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_5_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.09 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_6_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.07 0.0000 1.0000 0.0000 1.000 0.0000
CORRIDOR_FLR_3 VAV WITH REHEAT 0.000000 83.8280 0.000305 1557.62 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_1_FLR_6 FLR_3_DOAS 0.000000 1.5000 0.000396 39.02 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_2_FLR_6 FLR_3_DOAS 0.000000 1.5000 0.000396 39.02 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_3_MULT9_FLR_6 FLR_3_DOAS 0.000000 13.5000 0.000449 220.77 0.0000 1.0000 0.0000 1.000 0.0000
BANQUET_FLR_6 VAV WITH REHEAT 0.000000 249.8960 0.003581 331.66 0.0000 1.0000 0.0000 1.000 0.0000
DINING_FLR_6 VAV WITH REHEAT 0.000000 249.8960 0.003581 331.66 0.0000 1.0000 0.0000 1.000 0.0000
KITCHEN_FLR_6 VAV WITH REHEAT 0.000000 22.2380 0.003556 103.30 0.0000 1.0000 0.0000 1.000 0.0000
CORRIDOR_FLR_6 VAV WITH REHEAT 0.000000 22.1800 0.000305 412.12 0.0000 1.0000 0.0000 1.000 0.0000


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
FLR_3_DOAS   0.00 0.000441 4651.2638 0.0000 0.0000 0.0000
VAV WITH REHEAT   0.00 0.000970 6694.0231 0.0000 0.0000 0.0000


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.4359 2.4359 1.3324 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_1_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3124 0.3124 0.1709 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_2_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2278 0.2278 0.1246 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
MECH_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1811 0.1811 0.0991 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
STORAGE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1063 0.1063 0.0581 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LAUNDRY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 3.2963 3.2963 1.8031 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CAFE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.3820 1.3820 0.7559 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LOBBY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 4.6634 4.6634 2.5509 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8371 0.8371 0.8371 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_4_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8373 0.8373 0.8373 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_5_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_6_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_3 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.4242 1.4242 0.7790 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT9_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0992 0.0992 0.0992 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
BANQUET_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.1194 2.1194 1.1593 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DINING_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.2226 2.2226 1.2158 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
KITCHEN_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.2246 2.2246 1.2168 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7046 0.7046 0.3854 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
FLR_3_DOAS 2.0513 2.0513 2.0513 2.0513 0.0000 1.0000
VAV WITH REHEAT 21.3005 21.1819 21.3005 11.6514 0.0000 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.3324 1.3324 1.3324 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_1_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1709 0.1709 0.1709 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_2_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1246 0.1246 0.1246 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
MECH_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0991 0.0991 0.0991 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
STORAGE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0581 0.0581 0.0581 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LAUNDRY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.8031 1.8031 1.8031 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CAFE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7559 0.7559 0.7559 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LOBBY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.5509 2.5509 2.5509 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8371 0.8371 0.8371 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_4_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8373 0.8373 0.8373 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_5_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_6_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_3 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7790 0.7790 0.7790 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT9_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0992 0.0992 0.0992 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
BANQUET_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1593 1.1593 1.1593 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DINING_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.2158 1.2158 1.2158 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
KITCHEN_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.2168 1.2168 1.2168 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3854 0.3854 0.3854 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
FLR_3_DOAS 2.0513 2.0513 2.0513 2.0513 0.0000 1.0000
VAV WITH REHEAT 11.6514 11.6514 11.6514 11.6514 0.0000 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:51

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904
Total gross floor area [m2] 11345.29
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
BASEMENT 1978.83 1978.83 0.00 168.00
RETAIL_1_FLR_1 67.07 67.07 0.00 168.00
RETAIL_2_FLR_1 77.67 77.67 0.00 168.00
MECH_FLR_1 164.24 164.24 0.00 168.00
STORAGE_FLR_1 94.76 94.76 0.00 168.00
LAUNDRY_FLR_1 78.04 78.04 0.00 168.00
CAFE_FLR_1 188.86 188.86 0.00 168.00
LOBBY_FLR_1 1308.19 1308.19 0.00 168.00
ROOM_1_FLR_3 39.02 39.02 0.00 168.00
ROOM_2_FLR_3 39.02 39.02 0.00 168.00
ROOM_3_MULT19_FLR_3 24.52 24.52 0.00 0.00
ROOM_4_MULT19_FLR_3 24.53 24.53 0.00 168.00
ROOM_5_FLR_3 39.02 39.02 0.00 168.00
ROOM_6_FLR_3 39.02 39.02 0.00 168.00
CORRIDOR_FLR_3 389.40 389.40 0.00 168.00
ROOM_1_FLR_6 39.02 39.02 0.00 168.00
ROOM_2_FLR_6 39.02 39.02 0.00 168.00
ROOM_3_MULT9_FLR_6 24.53 24.53 0.00 168.00
BANQUET_FLR_6 331.66 331.66 0.00 168.00
DINING_FLR_6 331.66 331.66 0.00 168.00
KITCHEN_FLR_6 103.30 103.30 0.00 168.00
CORRIDOR_FLR_6 412.12 412.12 0.00 168.00
Totals 11345.29 11345.29 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 0.00
Number of hours cooling loads not met 56.00
Number of hours not met 56.00


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler 0.00 0.00 902.72 191268.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 664.89 156617.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 783.31 64632.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 193.98 12338.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 872.72 59188.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- Cooking 762.04 29240.64 1198.64 74976.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ReachInFreezer 14.43 457.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ReachInRefrigerator 8.99 285.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- Laundry 0.00 0.00 590.20 39726.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Transformer 21.77 1291.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLift 789.09 48128.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLightsFan 2.91 188.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 520.65 34789.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 75.88 4250.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 94.78 4752.55 2478.95 226542.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- General 7.09 2093.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- LowTempRefrigeration 20.47 1893.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- MedTempRefrigeration 34.75 1203.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 1720.50 4867.77
Natural Gas 1788.84 5170.50
Additional 0.00 0.00
Total 3509.34 10038.27


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 69.04
Space Heating 0.00
Space Cooling 58.60
Fans (All) 45.89
Service Water Heating 8.35
Receptacle Equipment 146.16
Miscellaneous (All) 429.06
Subtotal 429.06


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 79.57
Service Water Heating 218.50
Miscellaneous (All) 455.74
Subtotal 455.74


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 7.80
Space Heating 8.99
Space Cooling 6.62
Fans (All) 5.19
Service Water Heating 25.64
Receptacle Equipment 34.34
Miscellaneous 11.42


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
ELEVATOR_RUNNING_SCH 486. 5110.
ELEVATOR_STANDBY_SCH 7671. 8760.
LTG_SCH_KITCHEN 3061. 8760.
LTG_SCH_DINING 3061. 8760.
LTG_SCH_BASEMENT 2572. 8760.
LTG_SCH_LOBBY 2295. 8760.
LTG_SCH_STORAGE 1580. 8760.
LTG_SCH_MECHANIC 3061. 8760.
LTG_SCH_LAUNDRY 3061. 8760.
LTG_SCH_GUESTROOM 1980. 8760.
LTG_SCH_CORRIDOR 2295. 8760.
LTG_SCH_RETAIL 2678. 8760.
WALKIN_OCC_LGHT_SCH_2 1591. 8760.
EXTERIOR_LTG_SCH 4380. 4380.
BASEMENT_EQUIP_SCH 3737. 8760.
BLDG_EQUIP_SCH 3924. 8760.
GUESTROOM_EQP_SCH_BASE 3239. 8760.
GUESTROOM_EQP_SCH_ADVA 2762. 8760.
LOBBY_EQP_SCH 3292. 8760.
OFFICE_EQP_SCH 4941. 8760.
EMPLOYEELOUNGE_EQP_SCH 4044. 8760.
LAUNDRYROOM_EQP_ELEC_SCH 2920. 2920.
LAUNDRYROOM_EQP_GAS_SCH 2920. 2920.
MEETINGROOM_EQP_SCH 1336. 4745.
EXERCISEROOM_EQP_SCH 3832. 5840.
KITCHEN_ELEC_EQUIP_SCH 2172. 8760.
KITCHEN_GAS_EQUIP_SCH 1332. 8760.
KITCHEN_EXHAUST_SCH 6205. 6205.
ELEV_LIGHT_FAN_SCH_24_7 8760. 8760.
ELEV_LIGHT_FAN_SCH_ADD_DF 2154. 8760.
BLDG_OCC_SCH 5026. 8760.
GUESTROOM_OCC_SCH 5515. 8760.
LOBBY_OCC_SCH 2304. 8760.
OFFICE_OCC_SCH 3954. 8760.
EMPLOYEELOUNGE_OCC_SCH 948. 5475.
MEETINGROOM_OCC_SCH 1168. 4745.
LAUNDRYROOM_OCC_SCH 427. 2920.
EXERCISEROOM_OCC_SCH 5292. 5840.
INFIL_SCH 8760. 8760.
INFIL_HALF_ON_SCH 4380. 8760.
INFIL_QUARTER_ON_SCH 2190. 8760.
LAUNDRY_SWH_SCH 2555. 2555.
BLDG_SWH_SCH 3301. 8760.
GUESTROOM_SWH_SCH 2899. 8760.
LAUNDRYROOM_SWH_SCH 2920. 2920.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
ALWAYS_ON 8760. 8760.
ALWAYS_OFF 0. 0.
FAN_SCH 8760. 8760.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
OCC_GUESTROOM_VENT_CTRL_30MIN 6570. 6570.
OCC_GUESTROOM_VENT_CTRL_20MIN 6327. 6327.
VAC_GUESTROOM_VENTILATION_SCHEDULE 365. 365.
MINOA_MOTORIZEDDAMPER_SCHED 8760. 8760.
MINOA_SCHED 8760. 8760.
WORK_EFF_SCH 0. 0.
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED 2774. 8760.
FLR_3_DOAS_OAMINOAFRACSCHEDULE 8760. 8760.
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE 5740. 6205.
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE 8760. 8760.
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH 3285. 3285.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
VACGUESTROOM_HTGSP_SCH VACGUESTROOM THERMOSTAT DUAL SP CONTROL January 15.56 365 15.56 365
VACGUESTROOM_CLGSP_SCH VACGUESTROOM THERMOSTAT DUAL SP CONTROL July 26.67 365 26.67 365
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL January 21.11 365 21.11 365
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL July 23.33 365 21.11 365
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL January 21.11 365 21.11 365
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL July 23.33 365 21.11 365
HTGSETP_SCH BASEMENT DUAL SP CONTROL January 21.00 365 21.00 365
CLGSETP_SCH BASEMENT DUAL SP CONTROL July 24.00 365 24.00 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:51

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 8760.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 8760.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 8760.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8760.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 8760.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 8760.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 8711.50 48.50 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 7161.33 1598.67 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 8752.67 7.33 0.00 0.00 0.00
CORRIDOR_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 8760.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 8650.50 109.50 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 8760.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 8760.00 0.00 0.00 0.00 0.00
DINING_FLR_6 8760.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 8760.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 8760.00 0.00 0.00 0.00 0.00
Min 7161.33 0.00 0.00 0.00 0.00
Max 8760.00 1598.67 0.00 0.00 0.00
Average 8679.82 80.18 0.00 0.00 0.00
Sum 190956.00 1764.00 0.00 0.00 0.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 529331.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 50179.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 59156.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8977.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 5588.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 37203.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 710417.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 2115429.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 4149.67 4.33 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 4154.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 100358.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 4133.67 20.33 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 4154.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 1245715.00 0.00 0.00 0.00 0.00
DINING_FLR_6 1245715.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 108269.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 105946.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 2115429.00 20.33 0.00 0.00 0.00
Average 288885.92 1.12 0.00 0.00 0.00
Sum 6355490.33 24.67 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 8760.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 8760.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 8760.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8760.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 8760.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 7859.83 900.17 0.00 0.00 0.00
LOBBY_FLR_1 7954.50 805.50 0.00 0.00 0.00
ROOM_1_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 8483.33 276.67 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 5875.33 2884.67 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 8752.17 7.83 0.00 0.00 0.00
ROOM_5_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 8627.00 133.00 0.00 0.00 0.00
CORRIDOR_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 8760.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 8341.67 418.33 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 8760.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 7889.83 870.17 0.00 0.00 0.00
DINING_FLR_6 7987.33 772.67 0.00 0.00 0.00
KITCHEN_FLR_6 8697.67 62.33 0.00 0.00 0.00
CORRIDOR_FLR_6 8760.00 0.00 0.00 0.00 0.00
Min 5875.33 0.00 0.00 0.00 0.00
Max 8760.00 2884.67 0.00 0.00 0.00
Average 8435.85 324.15 0.00 0.00 0.00
Sum 185588.67 7131.33 0.00 0.00 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 529331.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 50179.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 59156.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8977.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 5588.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 37203.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 599671.67 110745.33 0.00 0.00 0.00
LOBBY_FLR_1 1826386.67 289042.33 0.00 0.00 0.00
ROOM_1_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 4026.83 127.17 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 4153.00 1.00 0.00 0.00 0.00
ROOM_5_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 4142.67 11.33 0.00 0.00 0.00
CORRIDOR_FLR_3 100358.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 3949.50 204.50 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 4154.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 1065164.33 180550.67 0.00 0.00 0.00
DINING_FLR_6 1084041.83 161673.17 0.00 0.00 0.00
KITCHEN_FLR_6 107667.67 601.33 0.00 0.00 0.00
CORRIDOR_FLR_6 105946.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 1826386.67 289042.33 0.00 0.00 0.00
Average 255116.28 33770.77 0.00 0.00 0.00
Sum 5612558.17 742956.83 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:51

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:51

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 0.00 0.00 0.00 0.00
MECH_FLR_1 0.00 0.00 0.00 0.00
STORAGE_FLR_1 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 0.00 0.00 0.00 0.00
CAFE_FLR_1 0.00 8760.00 0.00 0.00
LOBBY_FLR_1 0.00 8760.00 0.00 0.00
ROOM_1_FLR_3 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 0.00 0.00 0.00 0.00
BANQUET_FLR_6 0.00 8760.00 0.00 0.00
DINING_FLR_6 0.00 8760.00 0.00 0.00
KITCHEN_FLR_6 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 8760.00 0.00 0.00
Average 0.00 1592.73 0.00 0.00
Sum 0.00 35040.00 0.00 0.00


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 0.00 0.00 0.00 0.00
MECH_FLR_1 0.00 0.00 0.00 0.00
STORAGE_FLR_1 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 0.00 0.00 0.00 0.00
CAFE_FLR_1 0.00 710417.00 0.00 0.00
LOBBY_FLR_1 0.00 2115429.00 0.00 0.00
ROOM_1_FLR_3 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 0.00 0.00 0.00 0.00
BANQUET_FLR_6 0.00 1245715.00 0.00 0.00
DINING_FLR_6 0.00 1245715.00 0.00 0.00
KITCHEN_FLR_6 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 2115429.00 0.00 0.00
Average 0.00 241694.36 0.00 0.00
Sum 0.00 5317276.00 0.00 0.00



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C

For: Environment

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.221
February 13.282
March 12.638
April 15.303
May 15.556
June 17.667
July 19.435
August 19.664
September 18.470
October 18.770
November 14.323
December 13.589
   
Annual Sum or Average 16.011
Minimum of Months 12.638
Maximum of Months 19.664



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.221
February 13.282
March 12.638
April 15.303
May 15.556
June 17.667
July 19.435
August 19.664
September 18.470
October 18.770
November 14.323
December 13.589
   
Annual Sum or Average 16.011
Minimum of Months 12.638
Maximum of Months 19.664



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

For: Environment

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.221
February 13.282
March 12.638
April 15.303
May 15.556
June 17.667
July 19.435
August 19.664
September 18.470
October 18.770
November 14.323
December 13.589
   
Annual Sum or Average 16.011
Minimum of Months 12.638
Maximum of Months 19.664



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016

For: Environment

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.221
February 13.282
March 12.638
April 15.303
May 15.556
June 17.667
July 19.435
August 19.664
September 18.470
October 18.770
November 14.323
December 13.589
   
Annual Sum or Average 16.011
Minimum of Months 12.638
Maximum of Months 19.664



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE

For: Environment

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.221
February 13.282
March 12.638
April 15.303
May 15.556
June 17.667
July 19.435
August 19.664
September 18.470
October 18.770
November 14.323
December 13.589
   
Annual Sum or Average 16.011
Minimum of Months 12.638
Maximum of Months 19.664



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO

For: Environment

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.221
February 13.282
March 12.638
April 15.303
May 15.556
June 17.667
July 19.435
August 19.664
September 18.470
October 18.770
November 14.323
December 13.589
   
Annual Sum or Average 16.011
Minimum of Months 12.638
Maximum of Months 19.664



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.221
February 13.282
March 12.638
April 15.303
May 15.556
June 17.667
July 19.435
August 19.664
September 18.470
October 18.770
November 14.323
December 13.589
   
Annual Sum or Average 16.011
Minimum of Months 12.638
Maximum of Months 19.664



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED

For: Environment

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.221
February 13.282
March 12.638
April 15.303
May 15.556
June 17.667
July 19.435
August 19.664
September 18.470
October 18.770
November 14.323
December 13.589
   
Annual Sum or Average 16.011
Minimum of Months 12.638
Maximum of Months 19.664



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.221
February 13.282
March 12.638
April 15.303
May 15.556
June 17.667
July 19.435
August 19.664
September 18.470
October 18.770
November 14.323
December 13.589
   
Annual Sum or Average 16.011
Minimum of Months 12.638
Maximum of Months 19.664



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BASEMENT

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.355749E+11 22096.14 08-JAN-07:00 1.00 -0.3 0.765983E+10 4837.05 24-JAN-23:10 14.33 10.84
February 0.294135E+11 17115.76 04-FEB-05:55 5.00 0.22 0.668199E+10 4780.99 01-FEB-22:19 5.00 0.22
March 0.322013E+11 17505.81 08-MAR-02:00 4.00 3.53 0.719939E+10 4522.44 24-MAR-22:10 13.00 11.29
April 0.305997E+11 14895.94 30-APR-10:33 25.67 16.97 0.698024E+10 4505.14 14-APR-21:19 25.67 16.97
May 0.316693E+11 14628.35 28-MAY-10:33 21.00 15.43 0.723236E+10 4506.75 12-MAY-21:10 21.00 15.43
June 0.305724E+11 14788.29 25-JUN-10:33 23.00 17.26 0.695046E+10 4458.95 09-JUN-21:19 23.00 17.26
July 0.334402E+11 15672.76 23-JUL-10:33 25.67 20.39 0.739748E+10 4623.01 28-JUL-22:10 18.00 17.35
August 0.339315E+11 15659.67 13-AUG-10:33 24.00 19.90 0.751105E+10 4651.09 11-AUG-22:10 24.00 19.90
September 0.337839E+11 16160.27 30-SEP-10:33 30.57 17.23 0.747475E+10 4808.76 28-SEP-22:10 30.57 17.23
October 0.361322E+11 16934.47 20-OCT-21:00 16.00 13.03 0.791319E+10 4837.09 18-OCT-21:30 16.00 13.03
November 0.348943E+11 17164.12 22-NOV-22:00 11.00 2.60 0.768014E+10 4837.05 09-NOV-23:10 11.00 2.60
December 0.354960E+11 18090.57 03-DEC-01:00 5.00 5.00 0.775594E+10 4837.04 06-DEC-22:19 15.00 9.64
                     
Annual Sum or Average 0.397709E+12         0.884368E+11        
Minimum of Months 0.294135E+11 14628.35   1.00 -0.3 0.668199E+10 4458.95   5.00 0.22
Maximum of Months 0.361322E+11 22096.14   30.57 20.39 0.791319E+10 4837.09   30.57 19.90



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.385175E+10 3252.13 14-JAN-12:40 25.33 11.70 0.675250E+09 441.78 18-JAN-22:30 16.50 13.26
February 0.317629E+10 2915.66 02-FEB-12:40 19.33 12.36 0.603184E+09 442.79 01-FEB-22:30 19.33 12.36
March 0.317285E+10 2533.58 11-MAR-13:00 24.00 13.82 0.655903E+09 440.07 23-MAR-21:30 13.50 12.93
April 0.350930E+10 2013.49 08-APR-10:33 21.67 16.37 0.650673E+09 439.94 26-APR-22:10 16.00 15.29
May 0.339958E+10 1951.60 04-MAY-10:33 22.00 15.73 0.653653E+09 441.66 04-MAY-21:30 17.00 15.07
June 0.354652E+10 1872.57 25-JUN-10:33 23.00 17.26 0.651714E+09 437.75 28-JUN-21:40 17.00 16.37
July 0.397279E+10 2049.32 30-JUL-10:33 24.67 20.10 0.700676E+09 452.70 31-JUL-21:40 18.80 17.92
August 0.417505E+10 2128.66 27-AUG-10:33 23.33 18.72 0.725548E+09 460.45 18-AUG-21:40 23.33 18.72
September 0.407982E+10 3414.99 30-SEP-13:10 32.00 16.98 0.699370E+09 491.81 29-SEP-21:30 32.00 16.98
October 0.453674E+10 4013.08 16-OCT-12:20 35.37 17.35 0.729241E+09 491.84 16-OCT-22:10 20.17 11.06
November 0.396974E+10 3608.33 19-NOV-12:30 26.50 15.22 0.668270E+09 446.95 20-NOV-22:30 14.00 12.84
December 0.409264E+10 3443.73 19-DEC-12:50 25.83 11.54 0.684308E+09 458.82 05-DEC-22:30 25.83 11.54
                     
Annual Sum or Average 0.454831E+11         0.809779E+10        
Minimum of Months 0.317285E+10 1872.57   19.33 11.54 0.603184E+09 437.75   13.50 11.06
Maximum of Months 0.453674E+10 4013.08   35.37 20.10 0.729241E+09 491.84   32.00 18.72



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.309922E+10 1699.75 28-JAN-07:00 3.00 2.55 0.856629E+09 569.55 18-JAN-23:10 3.00 2.55
February 0.271737E+10 1571.06 04-FEB-05:55 5.00 0.22 0.783620E+09 569.51 02-FEB-23:10 5.00 0.22
March 0.299558E+10 1584.46 08-MAR-02:00 4.00 3.53 0.851019E+09 569.51 23-MAR-21:10 13.83 13.26
April 0.300460E+10 1523.18 27-APR-21:00 14.00 12.84 0.857834E+09 569.55 26-APR-22:10 14.00 12.84
May 0.307336E+10 1526.23 03-MAY-21:00 16.00 14.77 0.882273E+09 569.55 04-MAY-22:10 16.83 15.02
June 0.308882E+10 1573.99 30-JUN-21:00 16.00 14.76 0.872658E+09 569.55 19-JUN-22:10 16.00 14.76
July 0.334740E+10 1672.24 31-JUL-21:00 19.00 17.66 0.918458E+09 569.55 21-JUL-22:10 19.00 17.66
August 0.341070E+10 1738.65 18-AUG-21:00 19.00 17.66 0.930560E+09 569.55 10-AUG-22:10 19.00 17.66
September 0.323176E+10 1926.60 29-SEP-21:00 24.60 13.50 0.891979E+09 569.55 13-SEP-22:10 24.60 13.50
October 0.334860E+10 1981.03 16-OCT-20:10 20.50 12.73 0.922004E+09 569.55 18-OCT-21:30 14.50 14.21
November 0.303104E+10 1558.66 29-NOV-23:00 7.00 4.66 0.863289E+09 569.54 10-NOV-22:30 7.00 4.66
December 0.312474E+10 1558.75 03-DEC-01:00 5.00 5.00 0.873384E+09 569.54 05-DEC-23:10 17.33 9.21
                     
Annual Sum or Average 0.374732E+11         0.105037E+11        
Minimum of Months 0.271737E+10 1523.18   3.00 0.22 0.783620E+09 569.51   3.00 0.22
Maximum of Months 0.341070E+10 1981.03   24.60 17.66 0.930560E+09 569.55   24.60 17.66



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: MECH_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.218270E+10 1322.24 28-JAN-07:00 3.00 2.55 0.166617E+09 110.60 19-JAN-22:19 3.00 2.55
February 0.195003E+10 1183.71 04-FEB-05:55 5.00 0.22 0.152685E+09 109.20 03-FEB-22:10 5.00 0.22
March 0.212408E+10 1126.41 08-MAR-01:20 4.67 3.90 0.166259E+09 108.59 24-MAR-21:19 13.00 11.68
April 0.218060E+10 1108.41 30-APR-10:33 25.67 16.97 0.168107E+09 111.38 27-APR-21:19 25.67 16.97
May 0.230838E+10 1124.20 04-MAY-10:33 22.00 15.73 0.177017E+09 113.66 04-MAY-21:19 17.00 15.07
June 0.236594E+10 1168.36 25-JUN-10:33 23.00 17.26 0.177765E+09 116.16 30-JUN-21:19 16.03 15.21
July 0.256629E+10 1217.55 23-JUL-10:33 25.67 20.39 0.188172E+09 117.65 19-JUL-22:10 25.67 20.39
August 0.256402E+10 1208.98 19-AUG-10:33 24.67 20.11 0.188760E+09 117.71 18-AUG-21:19 24.67 20.11
September 0.239334E+10 1236.64 30-SEP-10:33 30.57 17.23 0.178789E+09 118.49 29-SEP-22:10 30.57 17.23
October 0.249756E+10 1229.55 17-OCT-10:33 31.00 16.57 0.186495E+09 120.45 16-OCT-22:10 31.00 16.57
November 0.219200E+10 1126.39 29-NOV-23:00 7.00 4.66 0.169149E+09 110.99 01-NOV-21:10 7.00 4.66
December 0.223357E+10 1187.86 03-DEC-01:00 5.00 5.00 0.169772E+09 110.53 05-DEC-22:19 17.33 9.44
                     
Annual Sum or Average 0.275585E+11         0.208959E+10        
Minimum of Months 0.195003E+10 1108.41   3.00 0.22 0.152685E+09 108.59   3.00 0.22
Maximum of Months 0.256629E+10 1322.24   31.00 20.39 0.188760E+09 120.45   31.00 20.39



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.120725E+10 723.67 27-JAN-04:55 4.00 3.53 0.124984E+09 81.54 18-JAN-23:10 4.00 3.53
February 0.110105E+10 678.17 04-FEB-05:55 5.00 0.22 0.114092E+09 80.29 03-FEB-23:10 5.00 0.22
March 0.117011E+10 607.69 19-MAR-10:33 19.33 15.06 0.124584E+09 80.07 24-MAR-22:10 13.00 11.29
April 0.123553E+10 642.74 30-APR-10:33 25.67 16.97 0.125880E+09 82.15 27-APR-22:10 25.67 16.97
May 0.130803E+10 651.95 04-MAY-10:33 22.00 15.73 0.132374E+09 84.07 04-MAY-22:10 16.83 15.02
June 0.134554E+10 675.65 25-JUN-10:33 23.00 17.26 0.133193E+09 85.59 30-JUN-22:10 16.13 16.03
July 0.146210E+10 705.58 23-JUL-10:33 25.67 20.39 0.141072E+09 86.98 19-JUL-22:10 25.67 20.39
August 0.146040E+10 699.80 19-AUG-10:33 24.67 20.11 0.141492E+09 86.93 18-AUG-22:10 24.67 20.11
September 0.136178E+10 720.98 30-SEP-10:33 30.57 17.23 0.134021E+09 88.21 29-SEP-22:10 30.57 17.23
October 0.141971E+10 719.17 16-OCT-10:33 36.33 17.49 0.139659E+09 89.50 16-OCT-22:10 20.17 11.06
November 0.124044E+10 639.91 19-NOV-11:33 26.00 15.32 0.126426E+09 81.81 01-NOV-22:10 26.00 15.32
December 0.125929E+10 673.32 03-DEC-01:00 5.00 5.00 0.126930E+09 81.98 05-DEC-23:10 17.33 9.21
                     
Annual Sum or Average 0.155712E+11         0.156471E+10        
Minimum of Months 0.110105E+10 607.69   4.00 0.22 0.114092E+09 80.07   4.00 0.22
Maximum of Months 0.146210E+10 723.67   36.33 20.39 0.141492E+09 89.50   30.57 20.39



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.507758E+11 37557.13 24-JAN-21:00 17.00 11.91 0.571364E+09 381.75 24-JAN-22:10 16.50 11.73
February 0.457270E+11 37484.34 03-FEB-21:00 13.00 7.33 0.522783E+09 381.69 21-FEB-22:10 10.67 10.13
March 0.507536E+11 37673.09 23-MAR-20:00 14.00 13.42 0.575077E+09 381.68 23-MAR-21:10 13.83 13.26
April 0.497539E+11 37921.70 26-APR-20:00 17.00 15.07 0.563385E+09 381.71 05-APR-21:10 17.00 15.07
May 0.515083E+11 37942.09 04-MAY-20:00 17.00 15.07 0.582819E+09 381.70 02-MAY-21:10 17.00 15.07
June 0.504254E+11 37958.08 30-JUN-20:00 16.00 15.39 0.565594E+09 381.73 23-JUN-21:10 16.00 15.39
July 0.524960E+11 38179.60 19-JUL-20:00 19.00 18.34 0.583978E+09 381.67 14-JUL-21:19 19.00 18.34
August 0.527845E+11 38141.66 18-AUG-20:00 19.00 17.66 0.585450E+09 381.68 04-AUG-21:19 19.00 17.66
September 0.503756E+11 38380.00 29-SEP-20:00 25.00 13.58 0.564926E+09 381.70 29-SEP-21:10 24.58 13.52
October 0.520754E+11 38262.23 16-OCT-20:00 21.00 13.07 0.584693E+09 381.75 31-OCT-21:10 16.88 14.87
November 0.494828E+11 37486.70 28-NOV-21:00 13.00 6.31 0.562570E+09 381.74 06-NOV-22:10 13.00 6.31
December 0.507863E+11 37691.77 05-DEC-21:00 16.00 9.09 0.574311E+09 381.73 21-DEC-22:10 10.67 10.67
                     
Annual Sum or Average 0.606945E+12         0.683695E+10        
Minimum of Months 0.457270E+11 37484.34   13.00 6.31 0.522783E+09 381.67   10.67 6.31
Maximum of Months 0.527845E+11 38380.00   25.00 18.34 0.585450E+09 381.75   24.58 18.34



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.206944E+11 12721.45 14-JAN-12:40 25.33 11.70 0.101117E+11 6462.52 18-JAN-23:10 15.67 12.73
February 0.174842E+11 10948.50 20-FEB-11:00 16.00 9.07 0.914832E+10 6462.02 02-FEB-00:20 16.00 9.07
March 0.186764E+11 10509.78 11-MAR-12:50 24.00 13.82 0.986089E+10 6461.97 23-MAR-23:19 12.00 12.00
April 0.184837E+11 9195.35 08-APR-10:33 21.67 16.37 0.984000E+10 6462.68 25-APR-21:30 14.50 13.91
May 0.183035E+11 8849.59 04-MAY-21:20 17.00 15.07 0.996253E+10 6462.64 03-MAY-22:10 17.00 15.07
June 0.182546E+11 8628.66 25-JUN-10:33 23.00 17.26 0.983734E+10 6462.74 19-JUN-22:10 23.00 17.26
July 0.197416E+11 9217.26 30-JUL-10:33 24.67 20.10 0.103204E+11 6462.75 07-JUL-21:30 24.67 20.10
August 0.205305E+11 9554.66 27-AUG-10:33 23.33 18.72 0.105634E+11 6462.72 01-AUG-22:10 23.33 18.72
September 0.201059E+11 12058.51 30-SEP-12:00 32.00 17.11 0.102348E+11 6462.61 12-SEP-22:10 32.00 17.11
October 0.219136E+11 13677.65 15-OCT-12:00 32.00 16.89 0.106311E+11 6462.63 16-OCT-22:10 20.17 11.06
November 0.201227E+11 14055.17 19-NOV-11:00 26.00 15.07 0.100863E+11 6462.38 10-NOV-22:30 26.00 15.07
December 0.211996E+11 12574.26 16-DEC-13:00 26.00 13.31 0.102608E+11 6462.67 01-DEC-00:00 26.00 13.31
                     
Annual Sum or Average 0.235511E+12         0.120857E+12        
Minimum of Months 0.174842E+11 8628.66   16.00 9.07 0.914832E+10 6461.97   12.00 9.07
Maximum of Months 0.219136E+11 14055.17   32.00 20.10 0.106311E+11 6462.75   32.00 20.10



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.674593E+11 37648.63 09-JAN-05:55 2.00 -0.2 0.302088E+11 19185.87 18-JAN-23:10 15.67 12.73
February 0.589207E+11 33715.83 04-FEB-05:55 5.00 0.22 0.275890E+11 19185.32 02-FEB-00:20 5.00 0.22
March 0.646625E+11 33763.26 08-MAR-02:00 4.00 3.53 0.299287E+11 19185.16 23-MAR-23:19 12.00 12.00
April 0.637598E+11 31533.75 26-APR-21:52 16.00 15.39 0.297638E+11 19186.10 26-APR-22:10 16.00 15.29
May 0.652371E+11 32428.36 04-MAY-21:53 17.00 15.07 0.306690E+11 19186.00 04-MAY-22:10 16.83 15.02
June 0.651560E+11 32339.04 30-JUN-21:52 16.10 16.10 0.301529E+11 19186.22 19-JUN-22:10 16.10 16.10
July 0.697984E+11 33679.59 19-JUL-21:52 18.00 17.35 0.313874E+11 19186.17 21-JUL-22:10 17.00 15.73
August 0.711249E+11 34316.62 18-AUG-21:10 19.00 17.66 0.317324E+11 19186.17 10-AUG-22:10 19.00 17.66
September 0.682054E+11 38050.84 29-SEP-21:10 24.58 13.52 0.306186E+11 19186.01 13-SEP-22:10 24.58 13.52
October 0.719018E+11 38779.30 16-OCT-21:10 18.33 11.06 0.317764E+11 19186.08 18-OCT-21:30 14.50 14.21
November 0.657188E+11 33022.84 20-NOV-22:10 14.00 12.84 0.302187E+11 19185.68 10-NOV-22:30 14.00 12.84
December 0.680138E+11 34111.01 05-DEC-22:10 17.17 9.45 0.307232E+11 19187.91 01-DEC-01:10 17.17 9.45
                     
Annual Sum or Average 0.799959E+12         0.364769E+12        
Minimum of Months 0.589207E+11 31533.75   2.00 -0.2 0.275890E+11 19185.16   5.00 0.22
Maximum of Months 0.719018E+11 38779.30   24.58 17.66 0.317764E+11 19187.91   24.58 17.66



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.646413E+09 3272.60 14-JAN-16:01 23.00 12.42 98078426.74 56.69 20-JAN-23:10 13.83 13.83
February 0.572346E+09 3284.55 03-FEB-16:01 20.50 10.05 88309482.39 56.69 14-FEB-22:10 13.00 12.44
March 0.597901E+09 2881.82 05-MAR-16:01 14.67 11.36 97804519.11 56.69 23-MAR-23:10 12.00 12.00
April 0.106876E+10 3051.25 01-APR-18:02 17.83 8.84 95349529.13 56.69 27-APR-21:10 14.00 12.84
May 0.102426E+10 2995.73 24-MAY-08:62 18.00 8.80 98498660.77 56.69 03-MAY-21:19 18.00 8.80
June 0.130628E+10 2969.15 28-JUN-18:01 18.67 16.49 95553544.38 56.70 30-JUN-21:40 16.07 15.66
July 0.172840E+10 2977.48 27-JUL-18:01 20.67 17.73 98881915.11 56.70 26-JUL-21:49 20.67 17.73
August 0.177263E+10 2961.18 17-AUG-18:02 20.77 18.28 99001095.32 56.69 02-AUG-21:00 20.77 18.28
September 0.146929E+10 2920.29 24-SEP-15:01 18.83 17.02 95607089.61 56.69 24-SEP-23:49 17.00 16.37
October 0.145192E+10 3317.95 14-OCT-08:61 27.67 13.01 98706513.28 56.69 17-OCT-22:40 16.67 12.78
November 0.822565E+09 3245.74 27-NOV-16:01 19.67 7.55 95209454.84 56.69 10-NOV-23:19 19.67 7.55
December 0.731815E+09 3283.86 19-DEC-16:01 20.67 8.11 98179659.47 56.69 07-DEC-22:40 20.67 8.11
                     
Annual Sum or Average 0.131926E+11         0.115918E+10        
Minimum of Months 0.572346E+09 2881.82   14.67 7.55 88309482.39 56.69   12.00 7.55
Maximum of Months 0.177263E+10 3317.95   27.67 18.28 99001095.32 56.70   20.77 18.28



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.237544E+09 3136.29 15-JAN-16:01 21.83 10.39 97557230.90 64.99 18-JAN-22:40 16.33 13.19
February 0.270341E+09 3145.55 03-FEB-16:01 20.50 10.05 88010108.37 56.69 01-FEB-22:10 20.50 10.05
March 0.337619E+09 2849.82 24-MAR-15:01 18.00 15.36 98104676.97 57.64 22-MAR-18:10 18.00 15.36
April 0.705468E+09 3120.74 19-APR-18:01 14.00 12.24 98778775.68 75.26 26-APR-21:49 16.00 15.39
May 0.781233E+09 3048.38 24-MAY-08:51 18.00 9.64 0.103049E+09 75.54 03-MAY-21:40 18.00 9.64
June 0.937144E+09 2898.64 22-JUN-20:11 15.00 13.18 0.105489E+09 79.26 30-JUN-18:10 18.83 16.43
July 0.123602E+10 2806.27 09-JUL-21:51 17.00 14.51 0.112134E+09 79.28 07-JUL-21:10 17.00 14.51
August 0.117363E+10 2783.67 05-AUG-15:01 22.67 18.32 0.111235E+09 78.25 09-AUG-21:40 18.00 17.36
September 0.917562E+09 2859.97 18-SEP-15:01 19.83 15.05 0.102389E+09 74.12 13-SEP-21:40 19.83 15.05
October 0.832438E+09 3318.62 14-OCT-08:61 27.67 13.01 0.104214E+09 75.48 16-OCT-21:40 19.33 11.10
November 0.364814E+09 3110.18 27-NOV-16:01 19.67 7.55 95283408.28 66.64 10-NOV-22:10 19.67 7.55
December 0.255575E+09 3145.30 19-DEC-16:01 20.67 8.11 97677375.15 65.54 05-DEC-22:40 20.67 8.11
                     
Annual Sum or Average 0.804938E+10         0.121392E+10        
Minimum of Months 0.237544E+09 2783.67   14.00 7.55 88010108.37 56.69   16.00 7.55
Maximum of Months 0.123602E+10 3318.62   27.67 18.32 0.112134E+09 79.28   20.67 17.36



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.454813E+09 576.52 14-JAN-12:40 25.33 11.70 0.00 0.00 01-JAN-00:10 25.33 11.70
February 0.295019E+09 506.55 02-FEB-12:30 19.50 11.91 0.00 0.00 01-FEB-00:10 19.50 11.91
March 0.226104E+09 429.68 11-MAR-13:10 24.00 13.64 0.00 0.00 01-MAR-00:10 24.00 13.64
April 0.252643E+09 302.19 08-APR-12:50 22.17 16.56 0.00 0.00 01-APR-00:10 22.17 16.56
May 0.161547E+09 256.16 03-MAY-15:03 21.83 15.33 0.00 0.00 01-MAY-00:10 21.83 15.33
June 0.202146E+09 222.64 30-JUN-15:06 22.95 17.86 0.00 0.00 01-JUN-00:10 22.95 17.86
July 0.295540E+09 265.41 19-JUL-15:03 26.67 20.20 0.00 0.00 01-JUL-00:10 26.67 20.20
August 0.386626E+09 286.55 30-AUG-13:00 24.00 18.12 0.00 0.00 01-AUG-00:10 24.00 18.12
September 0.432429E+09 533.06 30-SEP-13:05 32.00 16.98 0.00 0.00 01-SEP-00:10 32.00 16.98
October 0.552652E+09 641.98 16-OCT-12:20 35.37 17.35 0.00 0.00 01-OCT-00:10 35.37 17.35
November 0.460905E+09 609.24 19-NOV-09:58 26.00 13.89 0.00 0.00 01-NOV-00:10 26.00 13.89
December 0.507920E+09 588.24 19-DEC-13:00 26.00 11.60 0.00 0.00 01-DEC-00:10 26.00 11.60
                     
Annual Sum or Average 0.422834E+10         0.00        
Minimum of Months 0.161547E+09 222.64   19.50 11.60 0.00 0.00   19.50 11.60
Maximum of Months 0.552652E+09 641.98   35.37 20.20 0.00 0.00   35.37 20.20



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.273544E+09 1093.77 15-JAN-16:01 21.83 10.39 97513967.47 69.04 18-JAN-22:00 16.00 13.03
February 0.279405E+09 1060.00 03-FEB-16:01 20.50 10.05 87778747.49 58.62 13-FEB-21:19 14.67 14.08
March 0.321117E+09 973.56 04-MAR-09:01 14.00 12.23 97460101.69 57.30 30-MAR-23:10 8.00 6.97
April 0.397008E+09 1050.39 02-APR-08:51 19.00 9.47 95739379.29 71.65 25-APR-21:10 14.83 14.24
May 0.455758E+09 1055.46 24-MAY-08:51 18.00 9.64 99932383.92 72.10 04-MAY-21:00 18.00 9.64
June 0.482380E+09 1025.16 22-JUN-20:11 15.00 13.18 0.100319E+09 74.73 30-JUN-21:00 16.10 16.10
July 0.555836E+09 1038.95 04-JUL-08:51 22.00 15.83 0.105886E+09 76.09 07-JUL-21:10 15.17 13.86
August 0.523107E+09 1006.39 22-AUG-15:01 20.83 15.93 0.105396E+09 74.09 07-AUG-21:00 20.83 15.93
September 0.442949E+09 1007.96 01-SEP-15:01 20.67 15.86 98907749.15 71.87 22-SEP-21:00 17.00 16.37
October 0.451291E+09 1174.61 14-OCT-08:61 27.67 13.01 0.102177E+09 74.34 04-OCT-21:30 27.67 13.01
November 0.309758E+09 1080.05 19-NOV-09:41 25.67 13.67 94446866.53 68.62 10-NOV-22:10 25.67 13.67
December 0.274947E+09 1089.33 05-DEC-16:01 22.67 12.42 97274320.44 69.07 06-DEC-22:10 14.50 9.28
                     
Annual Sum or Average 0.476710E+10         0.118283E+10        
Minimum of Months 0.273544E+09 973.56   14.00 9.47 87778747.49 57.30   8.00 6.97
Maximum of Months 0.555836E+09 1174.61   27.67 15.93 0.105886E+09 76.09   27.67 16.37



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.675210E+09 2934.84 14-JAN-16:01 23.00 12.42 98367448.45 56.69 20-JAN-23:19 13.67 13.67
February 0.537357E+09 2930.11 03-FEB-16:01 20.50 10.05 88398294.37 56.69 17-FEB-22:10 13.67 12.71
March 0.586536E+09 2599.48 24-MAR-15:01 18.00 15.36 97990910.33 56.69 23-MAR-22:49 18.00 15.36
April 0.979101E+09 2896.14 02-APR-08:62 17.33 8.66 95480633.88 56.69 27-APR-01:00 16.00 15.39
May 0.898461E+09 2904.35 24-MAY-08:62 18.00 8.80 98582775.30 56.69 03-MAY-00:00 18.00 8.80
June 0.112855E+10 2675.65 26-JUN-15:01 22.00 17.98 95596961.87 56.69 16-JUN-21:00 22.00 17.98
July 0.158023E+10 2720.74 19-JUL-08:61 22.67 18.97 99033703.92 56.69 28-JUL-21:19 18.00 17.35
August 0.168479E+10 2725.10 14-AUG-08:61 23.33 19.67 99142509.54 56.69 09-AUG-21:10 23.33 19.67
September 0.128935E+10 2651.35 04-SEP-15:01 20.83 16.01 95529778.95 56.69 30-SEP-23:30 18.30 17.65
October 0.138936E+10 3026.42 14-OCT-08:61 27.67 13.01 98769580.50 56.69 18-OCT-21:19 14.67 14.28
November 0.773081E+09 2952.51 27-NOV-09:01 21.17 8.41 95336920.42 56.69 10-NOV-22:49 21.17 8.41
December 0.730582E+09 2972.27 05-DEC-09:01 24.33 12.02 98395945.11 56.69 07-DEC-22:49 12.13 12.12
                     
Annual Sum or Average 0.122526E+11         0.116063E+10        
Minimum of Months 0.537357E+09 2599.48   17.33 8.41 88398294.37 56.69   12.13 8.41
Maximum of Months 0.168479E+10 3026.42   27.67 19.67 99142509.54 56.69   23.33 19.67



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.272845E+09 2798.62 14-JAN-16:01 23.00 12.42 97640604.55 64.10 24-JAN-22:40 15.00 11.13
February 0.259120E+09 2863.66 03-FEB-09:51 21.00 8.28 87801579.12 56.69 17-FEB-22:19 13.33 12.58
March 0.346560E+09 2767.83 23-MAR-08:51 19.00 14.76 97910969.74 56.69 23-MAR-22:19 12.67 12.30
April 0.678736E+09 3108.15 02-APR-08:51 19.00 9.47 97418692.34 71.19 26-APR-21:49 16.00 15.39
May 0.718395E+09 3191.52 24-MAY-08:51 18.00 9.64 0.101514E+09 72.41 04-MAY-21:40 18.00 9.64
June 0.860008E+09 2986.79 23-JUN-08:51 21.00 15.42 0.101989E+09 73.23 30-JUN-21:49 16.08 15.88
July 0.116818E+10 2957.70 04-JUL-08:51 22.00 15.83 0.108616E+09 75.05 19-JUL-21:49 18.00 17.46
August 0.114698E+10 2885.16 22-AUG-08:51 19.00 14.76 0.108455E+09 74.82 18-AUG-21:30 19.00 14.76
September 0.807890E+09 2912.60 12-SEP-08:51 21.00 15.98 0.100371E+09 70.75 13-SEP-21:40 17.00 16.37
October 0.794544E+09 3389.84 17-OCT-08:21 27.50 13.36 0.103426E+09 73.79 16-OCT-21:40 27.50 13.36
November 0.348482E+09 2825.52 28-NOV-09:51 21.00 8.49 94943222.44 63.37 10-NOV-22:10 21.00 8.49
December 0.268435E+09 3049.44 05-DEC-09:41 25.67 12.88 97704138.42 65.45 05-DEC-22:40 17.67 9.41
                     
Annual Sum or Average 0.767018E+10         0.119779E+10        
Minimum of Months 0.259120E+09 2767.83   18.00 8.28 87801579.12 56.69   12.67 8.49
Maximum of Months 0.116818E+10 3389.84   27.50 15.98 0.108616E+09 75.05   27.50 17.46



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.424356E+10 2596.68 28-JAN-07:00 3.00 2.55 0.129828E+10 829.93 20-JAN-23:10 3.00 2.55
February 0.374851E+10 2317.31 04-FEB-05:55 5.00 0.22 0.118412E+10 827.83 03-FEB-23:10 5.00 0.22
March 0.408207E+10 2255.54 08-MAR-01:30 4.50 3.81 0.128941E+10 825.18 24-MAR-21:49 13.00 11.39
April 0.417921E+10 2161.93 30-APR-10:33 25.67 16.97 0.130062E+10 838.54 27-APR-21:49 25.67 16.97
May 0.435470E+10 2168.59 04-MAY-10:33 22.00 15.73 0.135459E+10 857.94 04-MAY-22:10 16.83 15.02
June 0.442937E+10 2231.77 25-JUN-10:33 23.00 17.26 0.135192E+10 871.17 30-JUN-22:10 16.13 16.03
July 0.484589E+10 2325.59 23-JUL-10:33 25.67 20.39 0.143801E+10 882.44 28-JUL-22:10 18.00 17.35
August 0.490837E+10 2343.00 19-AUG-10:33 24.67 20.11 0.145721E+10 891.79 18-AUG-22:10 24.67 20.11
September 0.456943E+10 2397.46 30-SEP-10:33 30.57 17.23 0.137797E+10 894.04 29-SEP-22:10 30.57 17.23
October 0.478766E+10 2413.39 17-OCT-10:33 31.00 16.57 0.144044E+10 917.97 17-OCT-21:49 18.00 14.47
November 0.422028E+10 2173.64 19-NOV-11:33 26.00 15.32 0.131112E+10 856.61 01-NOV-00:10 26.00 15.32
December 0.435370E+10 2304.75 03-DEC-01:00 5.00 5.00 0.132677E+10 841.34 05-DEC-23:10 17.33 9.21
                     
Annual Sum or Average 0.527227E+11         0.161305E+11        
Minimum of Months 0.374851E+10 2161.93   3.00 0.22 0.118412E+10 825.18   3.00 0.22
Maximum of Months 0.490837E+10 2596.68   31.00 20.39 0.145721E+10 917.97   30.57 20.11



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.533632E+09 3387.17 14-JAN-16:01 23.00 12.42 97809750.23 56.69 05-JAN-22:00 23.00 12.42
February 0.465590E+09 3393.45 03-FEB-16:01 20.50 10.05 88029638.77 56.69 21-FEB-00:20 10.33 8.38
March 0.527450E+09 3008.17 05-MAR-16:01 14.67 11.36 97581772.66 56.69 23-MAR-21:00 13.00 12.44
April 0.101641E+10 3177.96 01-APR-18:02 17.83 8.84 95275088.51 56.70 07-APR-02:39 13.00 11.87
May 0.958281E+09 3064.29 24-MAY-08:62 18.00 8.80 98424975.32 56.69 29-MAY-04:40 13.00 11.68
June 0.128355E+10 3060.42 28-JUN-18:01 18.67 16.49 95506879.14 56.70 17-JUN-04:30 18.67 16.49
July 0.174204E+10 3072.92 27-JUL-18:01 20.67 17.73 98851378.05 56.69 31-JUL-21:19 18.90 17.79
August 0.176314E+10 3044.75 14-AUG-18:02 21.83 18.58 98952852.88 56.70 17-AUG-21:19 19.00 17.66
September 0.139957E+10 2997.62 04-SEP-18:01 16.83 14.45 95530820.87 56.70 03-SEP-03:09 16.83 14.45
October 0.132344E+10 3427.03 26-OCT-15:01 22.67 12.63 98576973.44 56.70 17-OCT-21:40 22.67 12.63
November 0.669668E+09 3350.65 30-NOV-16:01 17.83 11.31 94964536.52 56.69 02-NOV-21:49 17.83 11.31
December 0.595385E+09 3397.19 19-DEC-16:01 20.67 8.11 97876085.79 56.69 07-DEC-22:30 20.67 8.11
                     
Annual Sum or Average 0.122782E+11         0.115738E+10        
Minimum of Months 0.465590E+09 2997.62   14.67 8.11 88029638.77 56.69   10.33 8.11
Maximum of Months 0.176314E+10 3427.03   23.00 18.58 98952852.88 56.70   23.00 17.79



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.153878E+09 3231.94 15-JAN-16:01 21.83 10.39 97025150.16 63.30 18-JAN-22:30 16.50 13.26
February 0.183171E+09 3237.06 03-FEB-16:01 20.50 10.05 87623581.93 56.69 02-FEB-00:20 20.50 10.05
March 0.266672E+09 3016.92 19-MAR-18:11 13.67 12.71 97983151.60 60.18 22-MAR-18:10 15.50 14.39
April 0.647286E+09 3319.00 23-APR-18:11 14.67 13.07 99323795.03 78.91 26-APR-18:10 18.67 15.37
May 0.730968E+09 3200.97 19-MAY-18:51 13.00 11.87 0.103605E+09 77.49 03-MAY-21:40 13.00 11.87
June 0.962111E+09 3079.60 04-JUN-19:31 15.00 13.18 0.106964E+09 84.19 30-JUN-18:10 18.83 16.43
July 0.131783E+10 2955.52 08-JUL-21:11 15.00 13.80 0.113882E+09 83.15 25-JUL-18:10 20.67 18.14
August 0.122149E+10 2863.12 21-AUG-20:11 15.00 13.80 0.112532E+09 81.43 03-AUG-18:10 15.00 13.80
September 0.876043E+09 2938.83 18-SEP-15:01 19.83 15.05 0.102582E+09 74.66 13-SEP-21:40 19.83 15.05
October 0.734300E+09 3327.92 14-OCT-08:61 27.67 13.01 0.103696E+09 74.86 16-OCT-21:40 19.33 11.10
November 0.236236E+09 3197.71 27-NOV-16:01 19.67 7.55 94755635.41 64.26 10-NOV-22:10 19.67 7.55
December 0.158525E+09 3240.45 19-DEC-16:01 20.67 8.11 97023985.32 63.51 05-DEC-22:40 20.67 8.11
                     
Annual Sum or Average 0.748851E+10         0.121700E+10        
Minimum of Months 0.153878E+09 2863.12   13.00 7.55 87623581.93 56.69   13.00 7.55
Maximum of Months 0.131783E+10 3327.92   27.67 15.05 0.113882E+09 84.19   20.67 18.14



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.908432E+09 1820.47 04-JAN-16:01 17.67 9.41 98763466.01 57.39 12-JAN-04:49 8.00 8.00
February 0.624954E+09 1841.27 03-FEB-16:01 20.50 10.05 88787675.76 57.32 22-FEB-03:00 9.00 7.42
March 0.545025E+09 1611.92 24-MAR-18:01 13.00 11.87 98168269.85 57.40 02-MAR-01:00 13.00 11.87
April 0.632726E+09 1728.66 01-APR-18:02 17.83 8.84 95289884.03 56.69 11-APR-21:10 13.83 13.83
May 0.458429E+09 1638.74 24-MAY-08:62 18.00 8.80 98138609.10 56.69 25-MAY-22:10 15.00 13.80
June 0.543410E+09 1629.28 30-JUN-15:01 22.95 17.86 95182258.15 56.69 30-JUN-23:49 16.38 15.77
July 0.757712E+09 1659.73 15-JUL-15:01 21.83 18.03 98689708.16 56.69 31-JUL-21:10 18.95 17.72
August 0.916260E+09 1640.88 02-AUG-15:01 22.83 18.38 98888387.60 56.69 21-AUG-21:10 15.17 13.86
September 0.929876E+09 1641.45 21-SEP-15:02 27.67 19.86 95446450.32 56.69 06-SEP-21:30 27.67 19.86
October 0.113498E+10 1856.17 14-OCT-08:61 27.67 13.01 98771321.46 56.69 10-OCT-21:49 27.67 13.01
November 0.912763E+09 1827.23 27-NOV-09:01 21.17 8.41 95659596.93 57.41 06-NOV-03:30 21.17 8.41
December 0.985510E+09 1851.23 29-DEC-16:01 21.17 10.21 98815914.91 57.40 15-DEC-02:09 21.17 10.21
                     
Annual Sum or Average 0.935008E+10         0.116060E+10        
Minimum of Months 0.458429E+09 1611.92   13.00 8.41 88787675.76 56.69   8.00 7.42
Maximum of Months 0.113498E+10 1856.17   27.67 19.86 98888387.60 57.41   27.67 19.86



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.355712E+11 19647.80 18-JAN-22:10 16.83 13.41 0.188185E+11 11348.62 18-JAN-23:10 15.67 12.73
February 0.321441E+11 19111.67 01-FEB-23:00 13.00 11.29 0.172122E+11 11347.79 08-FEB-00:20 12.67 6.27
March 0.359872E+11 19465.74 24-MAR-22:00 13.00 11.29 0.190364E+11 11347.72 13-MAR-23:19 13.00 11.29
April 0.364236E+11 20358.60 26-APR-21:52 16.00 15.39 0.185876E+11 11348.97 26-APR-22:10 16.00 15.29
May 0.381436E+11 20743.09 04-MAY-21:53 17.00 15.07 0.192356E+11 11348.92 03-MAY-22:10 17.00 15.07
June 0.385394E+11 20975.44 27-JUN-21:52 17.00 16.37 0.186854E+11 11349.13 19-JUN-22:10 17.00 16.37
July 0.408888E+11 21159.84 19-JUL-21:52 18.00 17.35 0.192556E+11 11349.09 05-JUL-22:10 18.00 17.35
August 0.407672E+11 21020.01 18-AUG-21:52 19.00 17.66 0.193272E+11 11349.09 01-AUG-22:10 19.00 17.66
September 0.380449E+11 21449.45 29-SEP-21:10 24.58 13.52 0.186218E+11 11348.82 12-SEP-22:10 24.58 13.52
October 0.389751E+11 21198.14 16-OCT-21:52 20.00 11.09 0.192112E+11 11348.91 16-OCT-22:10 20.17 11.06
November 0.349167E+11 19323.51 10-NOV-23:00 15.00 13.80 0.184636E+11 11348.33 10-NOV-22:30 15.00 13.80
December 0.354964E+11 19757.85 05-DEC-22:54 18.00 9.37 0.189405E+11 11348.89 01-DEC-00:49 18.00 9.37
                     
Annual Sum or Average 0.445898E+12         0.225396E+12        
Minimum of Months 0.321441E+11 19111.67   13.00 9.37 0.172122E+11 11347.72   12.67 6.27
Maximum of Months 0.408888E+11 21449.45   24.58 17.66 0.193272E+11 11349.13   24.58 17.66



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DINING_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.389576E+11 21302.18 18-JAN-22:10 16.83 13.41 0.189853E+11 11348.63 18-JAN-23:10 15.67 12.73
February 0.353262E+11 20804.15 01-FEB-22:10 13.00 11.77 0.173332E+11 11347.81 08-FEB-00:20 12.67 6.27
March 0.395304E+11 21050.45 24-MAR-21:10 13.00 11.77 0.191925E+11 11347.73 13-MAR-23:19 13.00 11.77
April 0.398389E+11 21881.63 26-APR-21:52 16.00 15.39 0.186615E+11 11348.97 26-APR-22:10 16.00 15.29
May 0.417096E+11 22189.92 04-MAY-21:10 17.00 15.07 0.193012E+11 11348.93 03-MAY-22:10 17.00 15.07
June 0.418763E+11 22393.34 27-JUN-21:52 17.00 16.37 0.187283E+11 11349.13 19-JUN-22:10 17.00 16.37
July 0.441565E+11 22546.55 19-JUL-21:52 18.00 17.35 0.192873E+11 11349.09 05-JUL-22:10 18.00 17.35
August 0.439404E+11 22361.93 18-AUG-21:52 19.00 17.66 0.193613E+11 11349.09 01-AUG-22:10 19.00 17.66
September 0.412090E+11 22812.48 29-SEP-21:10 24.58 13.52 0.186675E+11 11348.83 12-SEP-22:10 24.58 13.52
October 0.421477E+11 22581.11 04-OCT-21:53 21.00 18.98 0.192633E+11 11348.91 16-OCT-22:10 20.17 11.06
November 0.382016E+11 20999.41 10-NOV-22:14 15.00 13.80 0.185687E+11 11348.35 10-NOV-22:30 15.00 13.80
December 0.388701E+11 21335.55 05-DEC-22:54 18.00 9.37 0.190898E+11 11349.14 01-DEC-00:49 18.00 9.37
                     
Annual Sum or Average 0.485764E+12         0.226440E+12        
Minimum of Months 0.353262E+11 20804.15   13.00 9.37 0.173332E+11 11347.73   12.67 6.27
Maximum of Months 0.441565E+11 22812.48   24.58 18.98 0.193613E+11 11349.14   24.58 17.66



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.529315E+11 28436.32 20-JAN-11:45 21.83 15.77 0.187909E+11 11319.59 07-JAN-18:19 21.83 15.77
February 0.476570E+11 28308.96 01-FEB-11:45 25.50 14.48 0.169999E+11 11319.69 25-FEB-18:19 11.00 9.85
March 0.530951E+11 29168.99 19-MAR-10:33 19.33 15.06 0.188086E+11 11319.62 25-MAR-17:19 11.00 10.47
April 0.528509E+11 29567.87 30-APR-10:33 25.67 16.97 0.182308E+11 11319.57 08-APR-17:19 25.67 16.97
May 0.545725E+11 29272.52 04-MAY-10:33 22.00 15.73 0.188399E+11 11319.62 20-MAY-17:19 17.00 12.68
June 0.538218E+11 29639.28 25-JUN-10:33 23.00 17.26 0.182438E+11 11319.62 17-JUN-17:19 23.00 17.26
July 0.565616E+11 30075.30 23-JUL-10:33 25.67 20.39 0.188505E+11 11319.65 08-JUL-17:19 25.67 20.39
August 0.566548E+11 29952.91 19-AUG-10:33 24.67 20.11 0.188581E+11 11319.65 12-AUG-17:19 24.67 20.11
September 0.537295E+11 30329.55 30-SEP-10:50 30.78 17.57 0.182406E+11 11319.61 30-SEP-17:19 25.00 17.45
October 0.551196E+11 30194.87 15-OCT-10:40 31.67 16.43 0.188447E+11 11319.60 14-OCT-17:19 31.67 16.43
November 0.515325E+11 29053.34 19-NOV-11:45 26.00 15.39 0.182151E+11 11319.57 25-NOV-18:19 13.00 11.13
December 0.528753E+11 28349.42 05-DEC-11:45 23.17 12.83 0.188002E+11 11319.58 02-DEC-18:19 23.17 12.83
                     
Annual Sum or Average 0.641402E+12         0.221723E+12        
Minimum of Months 0.476570E+11 28308.96   19.33 12.83 0.169999E+11 11319.57   11.00 9.85
Maximum of Months 0.566548E+11 30329.55   31.67 20.39 0.188581E+11 11319.69   31.67 20.39



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.794350E+10 4371.84 06-JAN-23:00 5.00 2.03 0.135511E+10 875.80 18-JAN-22:40 16.33 13.19
February 0.721228E+10 4236.69 04-FEB-05:55 5.00 0.22 0.122676E+10 856.85 01-FEB-22:40 5.00 0.22
March 0.780084E+10 4270.05 11-MAR-11:33 24.00 13.82 0.135573E+10 875.07 24-MAR-21:40 13.00 11.48
April 0.837496E+10 4453.11 30-APR-10:33 25.67 16.97 0.137771E+10 898.63 27-APR-21:40 25.67 16.97
May 0.866361E+10 4525.64 04-MAY-10:33 22.00 15.73 0.142734E+10 920.38 04-MAY-21:40 17.00 15.07
June 0.891940E+10 4589.88 30-JUN-10:33 23.33 17.95 0.143751E+10 926.87 27-JUN-21:40 23.33 17.95
July 0.977731E+10 4822.62 30-JUL-10:33 24.67 20.10 0.153148E+10 942.78 31-JUL-21:40 18.80 17.92
August 0.988214E+10 4803.76 19-AUG-10:33 24.67 20.11 0.154945E+10 947.59 18-AUG-21:40 24.67 20.11
September 0.911093E+10 5183.82 30-SEP-13:40 32.00 17.36 0.145389E+10 971.82 29-SEP-21:40 32.00 17.36
October 0.943475E+10 5051.30 16-OCT-13:10 33.75 16.65 0.150746E+10 977.57 16-OCT-21:40 19.33 11.10
November 0.812308E+10 4535.76 19-NOV-11:33 26.00 15.32 0.134915E+10 889.61 01-NOV-00:10 26.00 15.32
December 0.818550E+10 4367.77 19-DEC-11:33 25.00 11.16 0.136568E+10 886.37 05-DEC-22:40 25.00 11.16
                     
Annual Sum or Average 0.103428E+12         0.169373E+11        
Minimum of Months 0.721228E+10 4236.69   5.00 0.22 0.122676E+10 856.85   5.00 0.22
Maximum of Months 0.988214E+10 5183.82   33.75 20.11 0.154945E+10 977.57   32.00 20.11



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BASEMENT

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 8.83
February 0.00 0.00 01-FEB-00:03 13.23
March 0.00 0.00 01-MAR-00:03 7.63
April 0.00 0.00 01-APR-00:10 9.63
May 0.00 0.00 01-MAY-00:05 15.20
June 0.00 0.00 01-JUN-00:05 13.07
July 0.00 0.00 01-JUL-00:10 16.43
August 0.00 0.00 01-AUG-00:05 18.07
September 0.00 0.00 01-SEP-00:05 16.07
October 0.00 0.00 01-OCT-00:10 18.42
November 0.00 0.00 01-NOV-00:05 14.77
December 0.00 0.00 01-DEC-00:03 10.63
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.63
Maximum of Months 0.00 0.00   18.42



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 8.83
February 0.00 0.00 01-FEB-00:03 13.23
March 2152.03 5.52 30-MAR-06:07 5.58
April 0.00 0.00 01-APR-00:10 9.63
May 0.00 0.00 01-MAY-00:05 15.20
June 0.00 0.00 01-JUN-00:05 13.07
July 0.00 0.00 01-JUL-00:10 16.43
August 0.00 0.00 01-AUG-00:05 18.07
September 0.00 0.00 01-SEP-00:05 16.07
October 0.00 0.00 01-OCT-00:10 18.42
November 0.00 0.00 01-NOV-00:05 14.77
December 0.00 0.00 01-DEC-00:03 10.63
         
Annual Sum or Average 2152.03      
Minimum of Months 0.00 0.00   5.58
Maximum of Months 2152.03 5.52   18.42



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 8.83
February 0.00 0.00 01-FEB-00:03 13.23
March 0.00 0.00 01-MAR-00:03 7.63
April 0.00 0.00 01-APR-00:10 9.63
May 0.00 0.00 01-MAY-00:05 15.20
June 0.00 0.00 01-JUN-00:05 13.07
July 0.00 0.00 01-JUL-00:10 16.43
August 0.00 0.00 01-AUG-00:05 18.07
September 0.00 0.00 01-SEP-00:05 16.07
October 0.00 0.00 01-OCT-00:10 18.42
November 0.00 0.00 01-NOV-00:05 14.77
December 0.00 0.00 01-DEC-00:03 10.63
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.63
Maximum of Months 0.00 0.00   18.42



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: MECH_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 8.83
February 0.00 0.00 01-FEB-00:03 13.23
March 0.00 0.00 01-MAR-00:03 7.63
April 0.00 0.00 01-APR-00:10 9.63
May 0.00 0.00 01-MAY-00:05 15.20
June 0.00 0.00 01-JUN-00:05 13.07
July 0.00 0.00 01-JUL-00:10 16.43
August 0.00 0.00 01-AUG-00:05 18.07
September 0.00 0.00 01-SEP-00:05 16.07
October 0.00 0.00 01-OCT-00:10 18.42
November 0.00 0.00 01-NOV-00:05 14.77
December 0.00 0.00 01-DEC-00:03 10.63
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.63
Maximum of Months 0.00 0.00   18.42



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 8.83
February 0.00 0.00 01-FEB-00:03 13.23
March 0.00 0.00 01-MAR-00:03 7.63
April 0.00 0.00 01-APR-00:10 9.63
May 0.00 0.00 01-MAY-00:05 15.20
June 0.00 0.00 01-JUN-00:05 13.07
July 0.00 0.00 01-JUL-00:10 16.43
August 0.00 0.00 01-AUG-00:05 18.07
September 0.00 0.00 01-SEP-00:05 16.07
October 0.00 0.00 01-OCT-00:10 18.42
November 0.00 0.00 01-NOV-00:05 14.77
December 0.00 0.00 01-DEC-00:03 10.63
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.63
Maximum of Months 0.00 0.00   18.42



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 8.83
February 0.00 0.00 01-FEB-00:03 13.23
March 0.00 0.00 01-MAR-00:03 7.63
April 0.00 0.00 01-APR-00:10 9.63
May 0.00 0.00 01-MAY-00:05 15.20
June 0.00 0.00 01-JUN-00:05 13.07
July 0.00 0.00 01-JUL-00:10 16.43
August 0.00 0.00 01-AUG-00:05 18.07
September 0.00 0.00 01-SEP-00:05 16.07
October 0.00 0.00 01-OCT-00:10 18.42
November 0.00 0.00 01-NOV-00:05 14.77
December 0.00 0.00 01-DEC-00:03 10.63
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.63
Maximum of Months 0.00 0.00   18.42



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 8.83
February 0.00 0.00 01-FEB-00:03 13.23
March 0.00 0.00 01-MAR-00:03 7.63
April 0.00 0.00 01-APR-00:10 9.63
May 0.00 0.00 01-MAY-00:05 15.20
June 0.00 0.00 01-JUN-00:05 13.07
July 0.00 0.00 01-JUL-00:10 16.43
August 0.00 0.00 01-AUG-00:05 18.07
September 0.00 0.00 01-SEP-00:05 16.07
October 0.00 0.00 01-OCT-00:10 18.42
November 0.00 0.00 01-NOV-00:05 14.77
December 0.00 0.00 01-DEC-00:03 10.63
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.63
Maximum of Months 0.00 0.00   18.42



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 8.83
February 0.00 0.00 01-FEB-00:03 13.23
March 0.00 0.00 01-MAR-00:03 7.63
April 0.00 0.00 01-APR-00:10 9.63
May 0.00 0.00 01-MAY-00:05 15.20
June 0.00 0.00 01-JUN-00:05 13.07
July 0.00 0.00 01-JUL-00:10 16.43
August 0.00 0.00 01-AUG-00:05 18.07
September 0.00 0.00 01-SEP-00:05 16.07
October 0.00 0.00 01-OCT-00:10 18.42
November 0.00 0.00 01-NOV-00:05 14.77
December 0.00 0.00 01-DEC-00:03 10.63
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.63
Maximum of Months 0.00 0.00   18.42



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 40070037.40 1044.95 29-JAN-16:04 13.83
February 22079190.87 1049.49 02-FEB-19:04 13.83
March 51021703.53 1057.47 21-MAR-18:04 13.83
April 8000471.32 1050.21 06-APR-18:04 13.00
May 4662004.03 1048.29 08-MAY-18:04 14.83
June 1895497.01 1050.25 16-JUN-15:04 17.17
July 1579132.67 1012.84 04-JUL-08:04 19.50
August 1390064.43 798.55 03-AUG-08:04 21.17
September 2222034.28 1022.98 22-SEP-18:04 18.00
October 2758301.50 1057.47 23-OCT-15:04 17.00
November 5715566.76 1041.04 04-NOV-18:04 12.00
December 22152304.96 1040.87 11-DEC-16:04 13.83
         
Annual Sum or Average 0.163546E+09      
Minimum of Months 1390064.43 798.55   12.00
Maximum of Months 51021703.53 1057.47   21.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.104270E+09 1037.69 22-JAN-16:04 14.67
February 38619993.02 1027.47 09-FEB-19:03 11.92
March 69433575.56 1021.42 18-MAR-15:04 16.83
April 8749827.96 1044.01 06-APR-18:04 13.00
May 3936717.41 1037.69 11-MAY-15:04 17.00
June 1123548.69 984.76 02-JUN-08:53 19.00
July 325906.75 557.91 10-JUL-08:54 21.00
August 193351.46 427.12 22-AUG-21:55 16.30
September 1451948.63 999.41 02-SEP-08:54 18.00
October 1771736.07 1043.29 23-OCT-15:04 17.00
November 20174244.62 1053.24 24-NOV-16:03 15.83
December 69166131.70 1043.00 26-DEC-19:03 12.00
         
Annual Sum or Average 0.319217E+09      
Minimum of Months 193351.46 427.12   11.92
Maximum of Months 0.104270E+09 1053.24   21.00



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 8.83
February 0.00 0.00 01-FEB-00:03 13.23
March 0.00 0.00 01-MAR-00:03 7.63
April 0.00 0.00 01-APR-00:10 9.63
May 0.00 0.00 01-MAY-00:05 15.20
June 0.00 0.00 01-JUN-00:05 13.07
July 0.00 0.00 01-JUL-00:10 16.43
August 0.00 0.00 01-AUG-00:05 18.07
September 0.00 0.00 01-SEP-00:05 16.07
October 0.00 0.00 01-OCT-00:10 18.42
November 0.00 0.00 01-NOV-00:05 14.77
December 0.00 0.00 01-DEC-00:03 10.63
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.63
Maximum of Months 0.00 0.00   18.42



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 1346050.98 279.76 08-JAN-16:03 13.67
February 1215398.14 285.75 18-FEB-16:04 15.83
March 1171638.11 284.32 20-MAR-15:04 15.67
April 489949.40 282.16 18-APR-15:04 16.00
May 513230.04 271.40 09-MAY-15:06 16.17
June 157014.69 262.08 06-JUN-15:06 17.83
July 47773.90 134.33 09-JUL-21:57 17.00
August 51280.21 191.94 22-AUG-08:54 19.00
September 311864.35 263.54 19-SEP-08:54 17.00
October 496459.09 252.93 11-OCT-15:06 18.58
November 1168097.99 281.40 20-NOV-16:04 15.67
December 1243094.03 277.46 10-DEC-16:04 14.00
         
Annual Sum or Average 8211850.94      
Minimum of Months 47773.90 134.33   13.67
Maximum of Months 1346050.98 285.75   19.00



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 40797328.24 1016.97 29-JAN-16:04 13.83
February 27055147.63 1020.92 18-FEB-16:04 15.83
March 60091411.08 1015.62 17-MAR-15:04 16.00
April 7004485.63 1025.70 18-APR-15:04 16.00
May 5812448.37 1010.25 12-MAY-15:04 15.83
June 1775491.23 959.60 08-JUN-15:04 18.00
July 248339.44 855.55 09-JUL-18:04 17.83
August 268879.21 725.15 08-AUG-08:05 19.13
September 1838648.66 886.83 21-SEP-18:04 19.00
October 1893126.81 1009.35 23-OCT-15:04 17.00
November 8279042.40 1030.97 16-NOV-16:04 15.67
December 26548073.10 1020.39 11-DEC-16:04 13.83
         
Annual Sum or Average 0.181612E+09      
Minimum of Months 248339.44 725.15   13.83
Maximum of Months 60091411.08 1030.97   19.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.100203E+09 996.81 06-JAN-16:03 16.67
February 49765319.90 980.85 24-FEB-16:03 14.00
March 82352669.78 978.43 17-MAR-15:04 16.00
April 7852427.45 1002.14 18-APR-15:04 16.00
May 4576495.27 992.53 12-MAY-15:04 15.83
June 959594.32 861.32 11-JUN-15:05 18.00
July 224198.46 457.80 27-JUL-06:15 15.33
August 142152.02 484.78 21-AUG-20:14 15.00
September 1005371.50 671.88 27-SEP-21:54 16.70
October 1508910.48 991.49 23-OCT-15:04 17.00
November 28830920.56 997.24 01-NOV-15:04 16.97
December 78042655.72 992.62 17-DEC-19:03 13.17
         
Annual Sum or Average 0.355464E+09      
Minimum of Months 142152.02 457.80   13.17
Maximum of Months 0.100203E+09 1002.14   18.00



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 8.83
February 0.00 0.00 01-FEB-00:03 13.23
March 0.00 0.00 01-MAR-00:03 7.63
April 0.00 0.00 01-APR-00:10 9.63
May 0.00 0.00 01-MAY-00:05 15.20
June 0.00 0.00 01-JUN-00:05 13.07
July 0.00 0.00 01-JUL-00:10 16.43
August 0.00 0.00 01-AUG-00:05 18.07
September 0.00 0.00 01-SEP-00:05 16.07
October 0.00 0.00 01-OCT-00:10 18.42
November 0.00 0.00 01-NOV-00:05 14.77
December 0.00 0.00 01-DEC-00:03 10.63
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.63
Maximum of Months 0.00 0.00   18.42



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.127277E+09 1222.92 16-JAN-16:04 18.00
February 89515289.09 1171.31 17-FEB-16:04 17.00
March 0.138154E+09 1223.47 17-MAR-15:04 16.00
April 19827250.38 1159.08 17-APR-15:04 17.33
May 15860671.82 1232.95 11-MAY-15:04 17.00
June 2071664.09 1238.47 16-JUN-15:04 17.17
July 1328261.02 995.13 04-JUL-08:04 19.50
August 1142059.29 861.16 22-AUG-18:04 17.00
September 2199755.95 1021.14 22-SEP-18:04 18.00
October 6685676.51 1235.63 23-OCT-15:04 17.00
November 44829888.42 1073.30 09-NOV-16:04 17.83
December 0.103215E+09 1150.20 27-DEC-09:03 15.67
         
Annual Sum or Average 0.552106E+09      
Minimum of Months 1142059.29 861.16   15.67
Maximum of Months 0.138154E+09 1238.47   19.50



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.258824E+09 1164.80 26-JAN-16:04 15.67
February 0.146007E+09 1121.21 09-FEB-09:01 11.90
March 0.178183E+09 1146.78 30-MAR-08:62 9.50
April 21409018.16 1192.41 14-APR-15:04 17.67
May 12544488.74 1222.54 13-MAY-15:04 16.17
June 1007630.25 1041.56 08-JUN-15:04 18.00
July 177550.32 546.70 06-JUL-08:54 20.00
August 293262.13 551.54 22-AUG-21:55 16.30
September 1699373.16 939.74 12-SEP-08:53 21.00
October 8583311.97 1217.88 23-OCT-15:04 17.00
November 0.101893E+09 1203.27 17-NOV-16:04 15.67
December 0.221677E+09 1219.54 27-DEC-19:03 14.17
         
Annual Sum or Average 0.952299E+09      
Minimum of Months 177550.32 546.70   9.50
Maximum of Months 0.258824E+09 1222.54   21.00



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 4116938.69 382.79 25-JAN-16:05 15.00
February 4929778.38 482.32 25-FEB-09:04 11.17
March 22455153.54 647.64 16-MAR-15:05 15.83
April 3328071.36 655.03 17-APR-15:04 17.33
May 3994141.47 650.64 13-MAY-15:04 16.17
June 1624471.00 630.74 17-JUN-18:04 17.83
July 865439.86 632.26 04-JUL-18:04 17.83
August 431028.18 476.18 22-AUG-18:04 17.00
September 974683.87 538.30 22-SEP-18:04 18.00
October 869838.25 626.37 23-OCT-15:04 17.00
November 732571.32 651.32 24-NOV-16:04 15.83
December 3046601.59 612.48 06-DEC-09:04 20.17
         
Annual Sum or Average 47368717.50      
Minimum of Months 431028.18 382.79   11.17
Maximum of Months 22455153.54 655.03   20.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 8.83
February 0.00 0.00 01-FEB-00:03 13.23
March 0.00 0.00 01-MAR-00:03 7.63
April 0.00 0.00 01-APR-00:10 9.63
May 0.00 0.00 01-MAY-00:05 15.20
June 0.00 0.00 01-JUN-00:05 13.07
July 0.00 0.00 01-JUL-00:10 16.43
August 0.00 0.00 01-AUG-00:05 18.07
September 0.00 0.00 01-SEP-00:05 16.07
October 0.00 0.00 01-OCT-00:10 18.42
November 0.00 0.00 01-NOV-00:05 14.77
December 0.00 0.00 01-DEC-00:03 10.63
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.63
Maximum of Months 0.00 0.00   18.42



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DINING_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 8.83
February 0.00 0.00 01-FEB-00:03 13.23
March 0.00 0.00 01-MAR-00:03 7.63
April 0.00 0.00 01-APR-00:10 9.63
May 0.00 0.00 01-MAY-00:05 15.20
June 0.00 0.00 01-JUN-00:05 13.07
July 0.00 0.00 01-JUL-00:10 16.43
August 0.00 0.00 01-AUG-00:05 18.07
September 0.00 0.00 01-SEP-00:05 16.07
October 0.00 0.00 01-OCT-00:10 18.42
November 0.00 0.00 01-NOV-00:05 14.77
December 0.00 0.00 01-DEC-00:03 10.63
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.63
Maximum of Months 0.00 0.00   18.42



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 8.83
February 0.00 0.00 01-FEB-00:03 13.23
March 0.00 0.00 01-MAR-00:03 7.63
April 0.00 0.00 01-APR-00:10 9.63
May 0.00 0.00 01-MAY-00:05 15.20
June 0.00 0.00 01-JUN-00:05 13.07
July 0.00 0.00 01-JUL-00:10 16.43
August 0.00 0.00 01-AUG-00:05 18.07
September 0.00 0.00 01-SEP-00:05 16.07
October 0.00 0.00 01-OCT-00:10 18.42
November 0.00 0.00 01-NOV-00:05 14.77
December 0.00 0.00 01-DEC-00:03 10.63
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.63
Maximum of Months 0.00 0.00   18.42



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 8.83
February 0.00 0.00 01-FEB-00:03 13.23
March 0.00 0.00 01-MAR-00:03 7.63
April 0.00 0.00 01-APR-00:10 9.63
May 0.00 0.00 01-MAY-00:05 15.20
June 0.00 0.00 01-JUN-00:05 13.07
July 0.00 0.00 01-JUL-00:10 16.43
August 0.00 0.00 01-AUG-00:05 18.07
September 0.00 0.00 01-SEP-00:05 16.07
October 0.00 0.00 01-OCT-00:10 18.42
November 0.00 0.00 01-NOV-00:05 14.77
December 0.00 0.00 01-DEC-00:03 10.63
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.63
Maximum of Months 0.00 0.00   18.42



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BASEMENT

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.136942E+11 13190.31 02-JAN-20:10 0.121516E+11 9632.53 02-JAN-20:10
February 0.123646E+11 13190.31 01-FEB-20:10 0.109726E+11 9632.53 01-FEB-20:10
March 0.137364E+11 13190.31 01-MAR-20:10 0.121771E+11 9632.53 01-MAR-20:10
April 0.132299E+11 13190.31 03-APR-19:10 0.117446E+11 9632.53 03-APR-19:10
May 0.137180E+11 13190.31 01-MAY-19:10 0.121662E+11 9632.53 01-MAY-19:10
June 0.132906E+11 13190.31 01-JUN-19:10 0.117829E+11 9632.53 01-JUN-19:10
July 0.136573E+11 13190.31 03-JUL-19:10 0.121279E+11 9632.53 03-JUL-19:10
August 0.137417E+11 13190.31 01-AUG-19:10 0.121808E+11 9632.53 01-AUG-19:10
September 0.132352E+11 13190.31 01-SEP-19:10 0.117482E+11 9632.53 01-SEP-19:10
October 0.136889E+11 13190.31 02-OCT-19:10 0.121479E+11 9632.53 02-OCT-19:10
November 0.132800E+11 13190.31 01-NOV-19:10 0.117774E+11 9632.53 01-NOV-19:10
December 0.136573E+11 13190.31 01-DEC-20:10 0.121279E+11 9632.53 01-DEC-20:10
             
Annual Sum or Average 0.161294E+12     0.143105E+12    
Minimum of Months 0.123646E+11 13190.31   0.109726E+11 9632.53  
Maximum of Months 0.137417E+11 13190.31   0.121808E+11 9632.53  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.620421E+09 597.59 02-JAN-20:10 0.864900E+09 685.60 02-JAN-20:10
February 0.560184E+09 597.59 01-FEB-20:10 0.780982E+09 685.60 01-FEB-20:10
March 0.622334E+09 597.59 01-MAR-20:10 0.866718E+09 685.60 01-MAR-20:10
April 0.599386E+09 597.59 03-APR-19:10 0.835931E+09 685.60 03-APR-19:10
May 0.621497E+09 597.59 01-MAY-19:10 0.865939E+09 685.60 01-MAY-19:10
June 0.602135E+09 597.59 01-JUN-19:10 0.838659E+09 685.60 01-JUN-19:10
July 0.618748E+09 597.59 03-JUL-19:10 0.863211E+09 685.60 03-JUL-19:10
August 0.622573E+09 597.59 01-AUG-19:10 0.866978E+09 685.60 01-AUG-19:10
September 0.599625E+09 597.59 01-SEP-19:10 0.836191E+09 685.60 01-SEP-19:10
October 0.620182E+09 597.59 02-OCT-19:10 0.864640E+09 685.60 02-OCT-19:10
November 0.601657E+09 597.59 01-NOV-19:10 0.838269E+09 685.60 01-NOV-19:10
December 0.618748E+09 597.59 01-DEC-20:10 0.863211E+09 685.60 01-DEC-20:10
             
Annual Sum or Average 0.730749E+10     0.101856E+11    
Minimum of Months 0.560184E+09 597.59   0.780982E+09 685.60  
Maximum of Months 0.622573E+09 597.59   0.866978E+09 685.60  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.718450E+09 692.02 02-JAN-20:10 0.100156E+10 793.93 02-JAN-20:10
February 0.648695E+09 692.02 01-FEB-20:10 0.904380E+09 793.93 01-FEB-20:10
March 0.720665E+09 692.02 01-MAR-20:10 0.100366E+10 793.93 01-MAR-20:10
April 0.694091E+09 692.02 03-APR-19:10 0.968011E+09 793.93 03-APR-19:10
May 0.719696E+09 692.02 01-MAY-19:10 0.100276E+10 793.93 01-MAY-19:10
June 0.697275E+09 692.02 01-JUN-19:10 0.971170E+09 793.93 01-JUN-19:10
July 0.716513E+09 692.02 03-JUL-19:10 0.999601E+09 793.93 03-JUL-19:10
August 0.720942E+09 692.02 01-AUG-19:10 0.100396E+10 793.93 01-AUG-19:10
September 0.694368E+09 692.02 01-SEP-19:10 0.968312E+09 793.93 01-SEP-19:10
October 0.718174E+09 692.02 02-OCT-19:10 0.100126E+10 793.93 02-OCT-19:10
November 0.696721E+09 692.02 01-NOV-19:10 0.970719E+09 793.93 01-NOV-19:10
December 0.716513E+09 692.02 01-DEC-20:10 0.999601E+09 793.93 01-DEC-20:10
             
Annual Sum or Average 0.846210E+10     0.117950E+11    
Minimum of Months 0.648695E+09 692.02   0.904380E+09 793.93  
Maximum of Months 0.720942E+09 692.02   0.100396E+10 793.93  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: MECH_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.710312E+09 684.18 02-JAN-20:10 0.105898E+10 839.45 02-JAN-20:10
February 0.641347E+09 684.18 01-FEB-20:10 0.956227E+09 839.45 01-FEB-20:10
March 0.712502E+09 684.18 01-MAR-20:10 0.106120E+10 839.45 01-MAR-20:10
April 0.686229E+09 684.18 03-APR-19:10 0.102351E+10 839.45 03-APR-19:10
May 0.711544E+09 684.18 01-MAY-19:10 0.106025E+10 839.45 01-MAY-19:10
June 0.689376E+09 684.18 01-JUN-19:10 0.102685E+10 839.45 01-JUN-19:10
July 0.708397E+09 684.18 03-JUL-19:10 0.105691E+10 839.45 03-JUL-19:10
August 0.712775E+09 684.18 01-AUG-19:10 0.106152E+10 839.45 01-AUG-19:10
September 0.686503E+09 684.18 01-SEP-19:10 0.102382E+10 839.45 01-SEP-19:10
October 0.710039E+09 684.18 02-OCT-19:10 0.105866E+10 839.45 02-OCT-19:10
November 0.688829E+09 684.18 01-NOV-19:10 0.102637E+10 839.45 01-NOV-19:10
December 0.708397E+09 684.18 01-DEC-20:10 0.105691E+10 839.45 01-DEC-20:10
             
Annual Sum or Average 0.836625E+10     0.124712E+11    
Minimum of Months 0.641347E+09 684.18   0.956227E+09 839.45  
Maximum of Months 0.712775E+09 684.18   0.106152E+10 839.45  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.261454E+09 251.84 02-JAN-20:10 0.305485E+09 242.16 02-JAN-20:10
February 0.236069E+09 251.84 01-FEB-20:10 0.275845E+09 242.16 01-FEB-20:10
March 0.262260E+09 251.84 01-MAR-20:10 0.306128E+09 242.16 01-MAR-20:10
April 0.252589E+09 251.84 03-APR-19:10 0.295253E+09 242.16 03-APR-19:10
May 0.261907E+09 251.84 01-MAY-19:10 0.305852E+09 242.16 01-MAY-19:10
June 0.253748E+09 251.84 01-JUN-19:10 0.296217E+09 242.16 01-JUN-19:10
July 0.260749E+09 251.84 03-JUL-19:10 0.304889E+09 242.16 03-JUL-19:10
August 0.262360E+09 251.84 01-AUG-19:10 0.306219E+09 242.16 01-AUG-19:10
September 0.252690E+09 251.84 01-SEP-19:10 0.295345E+09 242.16 01-SEP-19:10
October 0.261353E+09 251.84 02-OCT-19:10 0.305393E+09 242.16 02-OCT-19:10
November 0.253546E+09 251.84 01-NOV-19:10 0.296079E+09 242.16 01-NOV-19:10
December 0.260749E+09 251.84 01-DEC-20:10 0.304889E+09 242.16 01-DEC-20:10
             
Annual Sum or Average 0.307947E+10     0.359760E+10    
Minimum of Months 0.236069E+09 251.84   0.275845E+09 242.16  
Maximum of Months 0.262360E+09 251.84   0.306219E+09 242.16  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.337502E+09 325.08 02-JAN-20:10 0.576866E+10 4572.80 02-JAN-20:10
February 0.304733E+09 325.08 01-FEB-20:10 0.520895E+10 4572.80 01-FEB-20:10
March 0.338542E+09 325.08 01-MAR-20:10 0.578079E+10 4572.80 01-MAR-20:10
April 0.326059E+09 325.08 03-APR-19:10 0.557545E+10 4572.80 03-APR-19:10
May 0.338087E+09 325.08 01-MAY-19:10 0.577559E+10 4572.80 01-MAY-19:10
June 0.327554E+09 325.08 01-JUN-19:10 0.559364E+10 4572.80 01-JUN-19:10
July 0.336592E+09 325.08 03-JUL-19:10 0.575740E+10 4572.80 03-JUL-19:10
August 0.338672E+09 325.08 01-AUG-19:10 0.578252E+10 4572.80 01-AUG-19:10
September 0.326189E+09 325.08 01-SEP-19:10 0.557718E+10 4572.80 01-SEP-19:10
October 0.337372E+09 325.08 02-OCT-19:10 0.576693E+10 4572.80 02-OCT-19:10
November 0.327294E+09 325.08 01-NOV-19:10 0.559104E+10 4572.80 01-NOV-19:10
December 0.336592E+09 325.08 01-DEC-20:10 0.575740E+10 4572.80 01-DEC-20:10
             
Annual Sum or Average 0.397519E+10     0.679355E+11    
Minimum of Months 0.304733E+09 325.08   0.520895E+10 4572.80  
Maximum of Months 0.338672E+09 325.08   0.578252E+10 4572.80  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.130497E+10 1701.53 02-JAN-20:10 0.121771E+10 965.27 02-JAN-20:10
February 0.114673E+10 1701.53 01-FEB-20:10 0.109956E+10 965.27 01-FEB-20:10
March 0.125376E+10 1701.53 01-MAR-20:10 0.122027E+10 965.27 01-MAR-20:10
April 0.113983E+10 1701.53 03-APR-19:10 0.117692E+10 965.27 03-APR-19:10
May 0.112129E+10 1701.53 01-MAY-19:10 0.121917E+10 965.27 01-MAY-19:10
June 0.107741E+10 1701.53 01-JUN-19:10 0.118076E+10 965.27 01-JUN-19:10
July 0.111560E+10 1701.53 03-JUL-19:10 0.121533E+10 965.27 03-JUL-19:10
August 0.115503E+10 1701.53 01-AUG-19:10 0.122063E+10 965.27 01-AUG-19:10
September 0.120189E+10 1701.53 01-SEP-19:10 0.117729E+10 965.27 01-SEP-19:10
October 0.128074E+10 1701.53 02-OCT-19:10 0.121734E+10 965.27 02-OCT-19:10
November 0.124997E+10 1701.53 01-NOV-19:10 0.118021E+10 965.27 01-NOV-19:10
December 0.129666E+10 1701.53 01-DEC-20:10 0.121533E+10 965.27 01-DEC-20:10
             
Annual Sum or Average 0.143439E+11     0.143405E+11    
Minimum of Months 0.107741E+10 1701.53   0.109956E+10 965.27  
Maximum of Months 0.130497E+10 1701.53   0.122063E+10 965.27  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.941787E+10 9504.80 02-JAN-20:10 0.126520E+11 10029.21 02-JAN-20:10
February 0.847556E+10 9504.80 01-FEB-20:10 0.114244E+11 10029.21 01-FEB-20:10
March 0.940788E+10 9504.80 01-MAR-20:10 0.126786E+11 10029.21 01-MAR-20:10
April 0.900527E+10 9504.80 03-APR-19:10 0.122282E+11 10029.21 03-APR-19:10
May 0.929404E+10 9504.80 01-MAY-19:10 0.126672E+11 10029.21 01-MAY-19:10
June 0.899654E+10 9504.80 01-JUN-19:10 0.122682E+11 10029.21 01-JUN-19:10
July 0.924755E+10 9504.80 03-JUL-19:10 0.126273E+11 10029.21 03-JUL-19:10
August 0.933252E+10 9504.80 01-AUG-19:10 0.126824E+11 10029.21 01-AUG-19:10
September 0.906632E+10 9504.80 01-SEP-19:10 0.122320E+11 10029.21 01-SEP-19:10
October 0.940530E+10 9504.80 02-OCT-19:10 0.126482E+11 10029.21 02-OCT-19:10
November 0.911494E+10 9504.80 01-NOV-19:10 0.122624E+11 10029.21 01-NOV-19:10
December 0.938557E+10 9504.80 01-DEC-20:10 0.126273E+11 10029.21 01-DEC-20:10
             
Annual Sum or Average 0.110149E+12     0.148998E+12    
Minimum of Months 0.847556E+10 9504.80   0.114244E+11 10029.21  
Maximum of Months 0.941787E+10 9504.80   0.126824E+11 10029.21  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.196602E+09 177.88 01-JAN-19:10 0.222503E+09 237.06 01-JAN-08:09
February 0.177551E+09 177.88 01-FEB-20:10 0.200969E+09 237.06 01-FEB-07:10
March 0.195039E+09 177.88 01-MAR-20:10 0.222390E+09 237.06 01-MAR-07:10
April 0.190486E+09 177.88 01-APR-18:10 0.215344E+09 237.06 01-APR-07:10
May 0.195821E+09 177.88 01-MAY-19:10 0.222446E+09 237.06 01-MAY-06:10
June 0.188975E+09 177.88 01-JUN-19:10 0.215230E+09 237.06 01-JUN-06:10
July 0.197358E+09 177.88 01-JUL-18:10 0.222560E+09 237.06 01-JUL-07:10
August 0.195039E+09 177.88 01-AUG-19:10 0.222390E+09 237.06 01-AUG-06:10
September 0.190538E+09 177.88 01-SEP-19:10 0.215344E+09 237.06 01-SEP-06:10
October 0.196576E+09 177.88 01-OCT-18:10 0.222503E+09 237.06 01-OCT-07:10
November 0.189731E+09 177.88 01-NOV-19:10 0.215287E+09 237.06 01-NOV-06:10
December 0.197383E+09 177.88 01-DEC-20:10 0.222560E+09 237.06 01-DEC-07:10
             
Annual Sum or Average 0.231110E+10     0.261953E+10    
Minimum of Months 0.177551E+09 177.88   0.200969E+09 237.06  
Maximum of Months 0.197383E+09 177.88   0.222560E+09 237.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.196579E+09 177.86 01-JAN-19:10 0.222477E+09 237.03 01-JAN-08:09
February 0.177530E+09 177.86 01-FEB-20:10 0.200945E+09 237.03 01-FEB-07:10
March 0.195017E+09 177.86 01-MAR-20:10 0.222364E+09 237.03 01-MAR-07:10
April 0.190464E+09 177.86 01-APR-18:10 0.215319E+09 237.03 01-APR-07:10
May 0.195798E+09 177.86 01-MAY-19:10 0.222420E+09 237.03 01-MAY-06:10
June 0.188953E+09 177.86 01-JUN-19:10 0.215205E+09 237.03 01-JUN-06:10
July 0.197334E+09 177.86 01-JUL-18:10 0.222534E+09 237.03 01-JUL-07:10
August 0.195017E+09 177.86 01-AUG-19:10 0.222364E+09 237.03 01-AUG-06:10
September 0.190515E+09 177.86 01-SEP-19:10 0.215319E+09 237.03 01-SEP-06:10
October 0.196553E+09 177.86 01-OCT-18:10 0.222477E+09 237.03 01-OCT-07:10
November 0.189708E+09 177.86 01-NOV-19:10 0.215262E+09 237.03 01-NOV-06:10
December 0.197360E+09 177.86 01-DEC-20:10 0.222534E+09 237.03 01-DEC-07:10
             
Annual Sum or Average 0.231083E+10     0.261922E+10    
Minimum of Months 0.177530E+09 177.86   0.200945E+09 237.03  
Maximum of Months 0.197360E+09 177.86   0.222534E+09 237.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.123557E+09 111.79 01-JAN-19:10 0.217935E+09 232.19 01-JAN-08:09
February 0.111584E+09 111.79 01-FEB-20:10 0.196843E+09 232.19 01-FEB-07:10
March 0.122575E+09 111.79 01-MAR-20:10 0.217824E+09 232.19 01-MAR-07:10
April 0.119713E+09 111.79 01-APR-18:10 0.210923E+09 232.19 01-APR-07:10
May 0.123066E+09 111.79 01-MAY-19:10 0.217879E+09 232.19 01-MAY-06:10
June 0.118764E+09 111.79 01-JUN-19:10 0.210812E+09 232.19 01-JUN-06:10
July 0.124032E+09 111.79 01-JUL-18:10 0.217991E+09 232.19 01-JUL-07:10
August 0.122575E+09 111.79 01-AUG-19:10 0.217824E+09 232.19 01-AUG-06:10
September 0.119746E+09 111.79 01-SEP-19:10 0.210923E+09 232.19 01-SEP-06:10
October 0.123541E+09 111.79 01-OCT-18:10 0.217935E+09 232.19 01-OCT-07:10
November 0.119238E+09 111.79 01-NOV-19:10 0.210867E+09 232.19 01-NOV-06:10
December 0.124048E+09 111.79 01-DEC-20:10 0.217991E+09 232.19 01-DEC-07:10
             
Annual Sum or Average 0.145244E+10     0.256575E+10    
Minimum of Months 0.111584E+09 111.79   0.196843E+09 232.19  
Maximum of Months 0.124048E+09 111.79   0.217991E+09 232.19  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.123591E+09 111.82 01-JAN-19:10 0.217995E+09 232.26 01-JAN-08:09
February 0.111614E+09 111.82 01-FEB-20:10 0.196897E+09 232.26 01-FEB-07:10
March 0.122608E+09 111.82 01-MAR-20:10 0.217883E+09 232.26 01-MAR-07:10
April 0.119746E+09 111.82 01-APR-18:10 0.210981E+09 232.26 01-APR-07:10
May 0.123099E+09 111.82 01-MAY-19:10 0.217939E+09 232.26 01-MAY-06:10
June 0.118796E+09 111.82 01-JUN-19:10 0.210869E+09 232.26 01-JUN-06:10
July 0.124066E+09 111.82 01-JUL-18:10 0.218051E+09 232.26 01-JUL-07:10
August 0.122608E+09 111.82 01-AUG-19:10 0.217883E+09 232.26 01-AUG-06:10
September 0.119778E+09 111.82 01-SEP-19:10 0.210981E+09 232.26 01-SEP-06:10
October 0.123574E+09 111.82 01-OCT-18:10 0.217995E+09 232.26 01-OCT-07:10
November 0.119271E+09 111.82 01-NOV-19:10 0.210925E+09 232.26 01-NOV-06:10
December 0.124082E+09 111.82 01-DEC-20:10 0.218051E+09 232.26 01-DEC-07:10
             
Annual Sum or Average 0.145283E+10     0.256645E+10    
Minimum of Months 0.111614E+09 111.82   0.196897E+09 232.26  
Maximum of Months 0.124082E+09 111.82   0.218051E+09 232.26  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.196602E+09 177.88 01-JAN-19:10 0.222503E+09 237.06 01-JAN-08:09
February 0.177551E+09 177.88 01-FEB-20:10 0.200969E+09 237.06 01-FEB-07:10
March 0.195039E+09 177.88 01-MAR-20:10 0.222390E+09 237.06 01-MAR-07:10
April 0.190486E+09 177.88 01-APR-18:10 0.215344E+09 237.06 01-APR-07:10
May 0.195821E+09 177.88 01-MAY-19:10 0.222446E+09 237.06 01-MAY-06:10
June 0.188975E+09 177.88 01-JUN-19:10 0.215230E+09 237.06 01-JUN-06:10
July 0.197358E+09 177.88 01-JUL-18:10 0.222560E+09 237.06 01-JUL-07:10
August 0.195039E+09 177.88 01-AUG-19:10 0.222390E+09 237.06 01-AUG-06:10
September 0.190538E+09 177.88 01-SEP-19:10 0.215344E+09 237.06 01-SEP-06:10
October 0.196576E+09 177.88 01-OCT-18:10 0.222503E+09 237.06 01-OCT-07:10
November 0.189731E+09 177.88 01-NOV-19:10 0.215287E+09 237.06 01-NOV-06:10
December 0.197383E+09 177.88 01-DEC-20:10 0.222560E+09 237.06 01-DEC-07:10
             
Annual Sum or Average 0.231110E+10     0.261953E+10    
Minimum of Months 0.177551E+09 177.88   0.200969E+09 237.06  
Maximum of Months 0.197383E+09 177.88   0.222560E+09 237.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.196579E+09 177.86 01-JAN-19:10 0.222477E+09 237.03 01-JAN-08:09
February 0.177530E+09 177.86 01-FEB-20:10 0.200945E+09 237.03 01-FEB-07:10
March 0.195017E+09 177.86 01-MAR-20:10 0.222364E+09 237.03 01-MAR-07:10
April 0.190464E+09 177.86 01-APR-18:10 0.215319E+09 237.03 01-APR-07:10
May 0.195798E+09 177.86 01-MAY-19:10 0.222420E+09 237.03 01-MAY-06:10
June 0.188953E+09 177.86 01-JUN-19:10 0.215205E+09 237.03 01-JUN-06:10
July 0.197334E+09 177.86 01-JUL-18:10 0.222534E+09 237.03 01-JUL-07:10
August 0.195017E+09 177.86 01-AUG-19:10 0.222364E+09 237.03 01-AUG-06:10
September 0.190515E+09 177.86 01-SEP-19:10 0.215319E+09 237.03 01-SEP-06:10
October 0.196553E+09 177.86 01-OCT-18:10 0.222477E+09 237.03 01-OCT-07:10
November 0.189708E+09 177.86 01-NOV-19:10 0.215262E+09 237.03 01-NOV-06:10
December 0.197360E+09 177.86 01-DEC-20:10 0.222534E+09 237.03 01-DEC-07:10
             
Annual Sum or Average 0.231083E+10     0.261922E+10    
Minimum of Months 0.177530E+09 177.86   0.200945E+09 237.03  
Maximum of Months 0.197360E+09 177.86   0.222534E+09 237.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY []
January 0.193865E+10 1867.32 02-JAN-20:10 0.00 0.00
February 0.175042E+10 1867.32 01-FEB-20:10 0.00 0.00
March 0.194462E+10 1867.32 01-MAR-20:10 0.00 0.00
April 0.187292E+10 1867.32 03-APR-19:10 0.00 0.00
May 0.194201E+10 1867.32 01-MAY-19:10 0.00 0.00
June 0.188151E+10 1867.32 01-JUN-19:10 0.00 0.00
July 0.193342E+10 1867.32 03-JUL-19:10 0.00 0.00
August 0.194537E+10 1867.32 01-AUG-19:10 0.00 0.00
September 0.187367E+10 1867.32 01-SEP-19:10 0.00 0.00
October 0.193790E+10 1867.32 02-OCT-19:10 0.00 0.00
November 0.188002E+10 1867.32 01-NOV-19:10 0.00 0.00
December 0.193342E+10 1867.32 01-DEC-20:10 0.00 0.00
           
Annual Sum or Average 0.228339E+11     0.00 0.00
Minimum of Months 0.175042E+10 1867.32   0.00 0.00
Maximum of Months 0.194537E+10 1867.32   0.00 0.00



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.196602E+09 177.88 01-JAN-19:10 0.222503E+09 237.06 01-JAN-08:09
February 0.177551E+09 177.88 01-FEB-20:10 0.200969E+09 237.06 01-FEB-07:10
March 0.195039E+09 177.88 01-MAR-20:10 0.222390E+09 237.06 01-MAR-07:10
April 0.190486E+09 177.88 01-APR-18:10 0.215344E+09 237.06 01-APR-07:10
May 0.195821E+09 177.88 01-MAY-19:10 0.222446E+09 237.06 01-MAY-06:10
June 0.188975E+09 177.88 01-JUN-19:10 0.215230E+09 237.06 01-JUN-06:10
July 0.197358E+09 177.88 01-JUL-18:10 0.222560E+09 237.06 01-JUL-07:10
August 0.195039E+09 177.88 01-AUG-19:10 0.222390E+09 237.06 01-AUG-06:10
September 0.190538E+09 177.88 01-SEP-19:10 0.215344E+09 237.06 01-SEP-06:10
October 0.196576E+09 177.88 01-OCT-18:10 0.222503E+09 237.06 01-OCT-07:10
November 0.189731E+09 177.88 01-NOV-19:10 0.215287E+09 237.06 01-NOV-06:10
December 0.197383E+09 177.88 01-DEC-20:10 0.222560E+09 237.06 01-DEC-07:10
             
Annual Sum or Average 0.231110E+10     0.261953E+10    
Minimum of Months 0.177551E+09 177.88   0.200969E+09 237.06  
Maximum of Months 0.197383E+09 177.88   0.222560E+09 237.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.196579E+09 177.86 01-JAN-19:10 0.222477E+09 237.03 01-JAN-08:09
February 0.177530E+09 177.86 01-FEB-20:10 0.200945E+09 237.03 01-FEB-07:10
March 0.195017E+09 177.86 01-MAR-20:10 0.222364E+09 237.03 01-MAR-07:10
April 0.190464E+09 177.86 01-APR-18:10 0.215319E+09 237.03 01-APR-07:10
May 0.195798E+09 177.86 01-MAY-19:10 0.222420E+09 237.03 01-MAY-06:10
June 0.188953E+09 177.86 01-JUN-19:10 0.215205E+09 237.03 01-JUN-06:10
July 0.197334E+09 177.86 01-JUL-18:10 0.222534E+09 237.03 01-JUL-07:10
August 0.195017E+09 177.86 01-AUG-19:10 0.222364E+09 237.03 01-AUG-06:10
September 0.190515E+09 177.86 01-SEP-19:10 0.215319E+09 237.03 01-SEP-06:10
October 0.196553E+09 177.86 01-OCT-18:10 0.222477E+09 237.03 01-OCT-07:10
November 0.189708E+09 177.86 01-NOV-19:10 0.215262E+09 237.03 01-NOV-06:10
December 0.197360E+09 177.86 01-DEC-20:10 0.222534E+09 237.03 01-DEC-07:10
             
Annual Sum or Average 0.231083E+10     0.261922E+10    
Minimum of Months 0.177530E+09 177.86   0.200945E+09 237.03  
Maximum of Months 0.197360E+09 177.86   0.222534E+09 237.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.123591E+09 111.82 01-JAN-19:10 0.217995E+09 232.26 01-JAN-08:09
February 0.111614E+09 111.82 01-FEB-20:10 0.196897E+09 232.26 01-FEB-07:10
March 0.122608E+09 111.82 01-MAR-20:10 0.217883E+09 232.26 01-MAR-07:10
April 0.119746E+09 111.82 01-APR-18:10 0.210981E+09 232.26 01-APR-07:10
May 0.123099E+09 111.82 01-MAY-19:10 0.217939E+09 232.26 01-MAY-06:10
June 0.118796E+09 111.82 01-JUN-19:10 0.210869E+09 232.26 01-JUN-06:10
July 0.124066E+09 111.82 01-JUL-18:10 0.218051E+09 232.26 01-JUL-07:10
August 0.122608E+09 111.82 01-AUG-19:10 0.217883E+09 232.26 01-AUG-06:10
September 0.119778E+09 111.82 01-SEP-19:10 0.210981E+09 232.26 01-SEP-06:10
October 0.123574E+09 111.82 01-OCT-18:10 0.217995E+09 232.26 01-OCT-07:10
November 0.119271E+09 111.82 01-NOV-19:10 0.210925E+09 232.26 01-NOV-06:10
December 0.124082E+09 111.82 01-DEC-20:10 0.218051E+09 232.26 01-DEC-07:10
             
Annual Sum or Average 0.145283E+10     0.256645E+10    
Minimum of Months 0.111614E+09 111.82   0.196897E+09 232.26  
Maximum of Months 0.124082E+09 111.82   0.218051E+09 232.26  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.278781E+10 2988.03 02-JAN-20:10 0.149358E+11 6747.90 01-JAN-07:10
February 0.246232E+10 2988.03 01-FEB-20:10 0.134904E+11 6747.90 01-FEB-07:10
March 0.268528E+10 2988.03 01-MAR-20:10 0.149358E+11 6747.90 01-MAR-07:10
April 0.249776E+10 2988.03 03-APR-19:10 0.144540E+11 6747.90 01-APR-06:10
May 0.250863E+10 2988.03 01-MAY-19:10 0.149358E+11 6747.90 01-MAY-06:10
June 0.240793E+10 2988.03 01-JUN-19:10 0.144540E+11 6747.90 01-JUN-06:10
July 0.248899E+10 2988.03 03-JUL-19:10 0.149358E+11 6747.90 01-JUL-06:10
August 0.255593E+10 2988.03 01-AUG-19:10 0.149358E+11 6747.90 01-AUG-06:10
September 0.257519E+10 2988.03 01-SEP-19:10 0.144540E+11 6747.90 01-SEP-06:10
October 0.275378E+10 2988.03 02-OCT-19:10 0.149358E+11 6747.90 01-OCT-06:10
November 0.268255E+10 2988.03 01-NOV-19:10 0.144540E+11 6747.90 01-NOV-06:10
December 0.278872E+10 2988.03 01-DEC-20:10 0.149358E+11 6747.90 01-DEC-07:10
             
Annual Sum or Average 0.311949E+11     0.175857E+12    
Minimum of Months 0.240793E+10 2988.03   0.134904E+11 6747.90  
Maximum of Months 0.278872E+10 2988.03   0.149358E+11 6747.90  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DINING_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.278781E+10 2988.03 02-JAN-20:10 0.149358E+11 6747.90 01-JAN-07:10
February 0.246232E+10 2988.03 01-FEB-20:10 0.134904E+11 6747.90 01-FEB-07:10
March 0.268528E+10 2988.03 01-MAR-20:10 0.149358E+11 6747.90 01-MAR-07:10
April 0.249776E+10 2988.03 03-APR-19:10 0.144540E+11 6747.90 01-APR-06:10
May 0.250863E+10 2988.03 01-MAY-19:10 0.149358E+11 6747.90 01-MAY-06:10
June 0.240793E+10 2988.03 01-JUN-19:10 0.144540E+11 6747.90 01-JUN-06:10
July 0.248899E+10 2988.03 03-JUL-19:10 0.149358E+11 6747.90 01-JUL-06:10
August 0.255593E+10 2988.03 01-AUG-19:10 0.149358E+11 6747.90 01-AUG-06:10
September 0.257519E+10 2988.03 01-SEP-19:10 0.144540E+11 6747.90 01-SEP-06:10
October 0.275378E+10 2988.03 02-OCT-19:10 0.149358E+11 6747.90 01-OCT-06:10
November 0.268255E+10 2988.03 01-NOV-19:10 0.144540E+11 6747.90 01-NOV-06:10
December 0.278872E+10 2988.03 01-DEC-20:10 0.149358E+11 6747.90 01-DEC-07:10
             
Annual Sum or Average 0.311949E+11     0.175857E+12    
Minimum of Months 0.240793E+10 2988.03   0.134904E+11 6747.90  
Maximum of Months 0.278872E+10 2988.03   0.149358E+11 6747.90  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.110133E+10 1060.81 02-JAN-20:10 0.368383E+11 16487.34 01-JAN-07:10
February 0.994402E+09 1060.81 01-FEB-20:10 0.332733E+11 16487.34 01-FEB-07:10
March 0.110473E+10 1060.81 01-MAR-20:10 0.368383E+11 16487.34 01-MAR-07:10
April 0.106399E+10 1060.81 03-APR-19:10 0.356500E+11 16487.34 01-APR-06:10
May 0.110324E+10 1060.81 01-MAY-19:10 0.368383E+11 16487.34 01-MAY-06:10
June 0.106887E+10 1060.81 01-JUN-19:10 0.356500E+11 16487.34 01-JUN-06:10
July 0.109836E+10 1060.81 03-JUL-19:10 0.368383E+11 16487.34 01-JUL-06:10
August 0.110515E+10 1060.81 01-AUG-19:10 0.368383E+11 16487.34 01-AUG-06:10
September 0.106442E+10 1060.81 01-SEP-19:10 0.356500E+11 16487.34 01-SEP-06:10
October 0.110091E+10 1060.81 02-OCT-19:10 0.368383E+11 16487.34 01-OCT-06:10
November 0.106802E+10 1060.81 01-NOV-19:10 0.356500E+11 16487.34 01-NOV-06:10
December 0.109836E+10 1060.81 01-DEC-20:10 0.368383E+11 16487.34 01-DEC-07:10
             
Annual Sum or Average 0.129718E+11     0.433742E+12    
Minimum of Months 0.994402E+09 1060.81   0.332733E+11 16487.34  
Maximum of Months 0.110515E+10 1060.81   0.368383E+11 16487.34  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY []
January 0.205176E+10 1976.27 02-JAN-20:10 0.00 0.00
February 0.185255E+10 1976.27 01-FEB-20:10 0.00 0.00
March 0.205809E+10 1976.27 01-MAR-20:10 0.00 0.00
April 0.198220E+10 1976.27 03-APR-19:10 0.00 0.00
May 0.205532E+10 1976.27 01-MAY-19:10 0.00 0.00
June 0.199129E+10 1976.27 01-JUN-19:10 0.00 0.00
July 0.204623E+10 1976.27 03-JUL-19:10 0.00 0.00
August 0.205888E+10 1976.27 01-AUG-19:10 0.00 0.00
September 0.198299E+10 1976.27 01-SEP-19:10 0.00 0.00
October 0.205097E+10 1976.27 02-OCT-19:10 0.00 0.00
November 0.198971E+10 1976.27 01-NOV-19:10 0.00 0.00
December 0.204623E+10 1976.27 01-DEC-20:10 0.00 0.00
           
Annual Sum or Average 0.241662E+11     0.00 0.00
Minimum of Months 0.185255E+10 1976.27   0.00 0.00
Maximum of Months 0.205888E+10 1976.27   0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: BASEMENT

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.195762E+11 0.136942E+11 0.121516E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.176991E+11 0.123646E+11 0.109726E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.196682E+11 0.137364E+11 0.121771E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.189781E+11 0.132299E+11 0.117446E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.196176E+11 0.137180E+11 0.121662E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.190195E+11 0.132906E+11 0.117829E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.195762E+11 0.136573E+11 0.121279E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.196590E+11 0.137417E+11 0.121808E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.189689E+11 0.132352E+11 0.117482E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.195854E+11 0.136889E+11 0.121479E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.189367E+11 0.132800E+11 0.117774E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.195762E+11 0.136573E+11 0.121279E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.230861E+12 0.161294E+12 0.143105E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.176991E+11 0.123646E+11 0.109726E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.196682E+11 0.137417E+11 0.121808E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: RETAIL_1_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.199054E+10 0.620421E+09 0.864900E+09 0.00 0.00 0.00 0.00 456622.88 0.130395E+09
February 0.179968E+10 0.560184E+09 0.780982E+09 0.00 0.00 0.00 0.00 31909.05 0.112714E+09
March 0.199990E+10 0.622334E+09 0.866718E+09 0.00 0.00 0.00 0.00 0.00 0.130604E+09
April 0.192973E+10 0.599386E+09 0.835931E+09 0.00 0.00 0.00 0.00 546556.49 92394060.51
May 0.199475E+10 0.621497E+09 0.865939E+09 0.00 0.00 0.00 0.00 52315.74 85970077.40
June 0.193394E+10 0.602135E+09 0.838659E+09 0.00 0.00 0.00 0.00 1315370.96 57944632.22
July 0.199054E+10 0.618748E+09 0.863211E+09 0.00 0.00 0.00 0.00 4176060.31 43685344.18
August 0.199896E+10 0.622573E+09 0.866978E+09 0.00 0.00 0.00 0.00 3425069.34 44720494.00
September 0.192879E+10 0.599625E+09 0.836191E+09 0.00 0.00 0.00 0.00 3613908.84 60649729.00
October 0.199148E+10 0.620182E+09 0.864640E+09 0.00 0.00 0.00 0.00 6269620.24 62938900.08
November 0.192552E+10 0.601657E+09 0.838269E+09 0.00 0.00 0.00 0.00 280925.48 0.112207E+09
December 0.199054E+10 0.618748E+09 0.863211E+09 0.00 0.00 0.00 0.00 177357.57 0.126273E+09
                   
Annual Sum or Average 0.234744E+11 0.730749E+10 0.101856E+11 0.00 0.00 0.00 0.00 20345716.90 0.106050E+10
Minimum of Months 0.179968E+10 0.560184E+09 0.780982E+09 0.00 0.00 0.00 0.00 0.00 43685344.18
Maximum of Months 0.199990E+10 0.622573E+09 0.866978E+09 0.00 0.00 0.00 0.00 6269620.24 0.130604E+09



Table of Contents

Report: SpaceGainsMonthly

For: RETAIL_2_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.230505E+10 0.718450E+09 0.100156E+10 0.00 0.00 0.00 0.00 349016.33 53208866.84
February 0.208403E+10 0.648695E+09 0.904380E+09 0.00 0.00 0.00 0.00 43693.05 47416609.89
March 0.231589E+10 0.720665E+09 0.100366E+10 0.00 0.00 0.00 0.00 61843.23 54947676.99
April 0.223463E+10 0.694091E+09 0.968011E+09 0.00 0.00 0.00 0.00 342678.74 41046433.10
May 0.230993E+10 0.719696E+09 0.100276E+10 0.00 0.00 0.00 0.00 41780.09 40260217.84
June 0.223950E+10 0.697275E+09 0.971170E+09 0.00 0.00 0.00 0.00 328266.57 28768218.87
July 0.230505E+10 0.716513E+09 0.999601E+09 0.00 0.00 0.00 0.00 1461066.17 22378969.65
August 0.231480E+10 0.720942E+09 0.100396E+10 0.00 0.00 0.00 0.00 1610846.12 21791284.21
September 0.223354E+10 0.694368E+09 0.968312E+09 0.00 0.00 0.00 0.00 1449883.47 27100199.60
October 0.230614E+10 0.718174E+09 0.100126E+10 0.00 0.00 0.00 0.00 2889219.67 28089159.99
November 0.222975E+10 0.696721E+09 0.970719E+09 0.00 0.00 0.00 0.00 233792.68 47127636.62
December 0.230505E+10 0.716513E+09 0.999601E+09 0.00 0.00 0.00 0.00 268815.66 52014753.18
                   
Annual Sum or Average 0.271834E+11 0.846210E+10 0.117950E+11 0.00 0.00 0.00 0.00 9080901.79 0.464150E+09
Minimum of Months 0.208403E+10 0.648695E+09 0.904380E+09 0.00 0.00 0.00 0.00 41780.09 21791284.21
Maximum of Months 0.231589E+10 0.720942E+09 0.100396E+10 0.00 0.00 0.00 0.00 2889219.67 54947676.99



Table of Contents

Report: SpaceGainsMonthly

For: MECH_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.487480E+09 0.710312E+09 0.105898E+10 0.00 0.00 0.00 0.00 1149103.45 0.116019E+09
February 0.440737E+09 0.641347E+09 0.956227E+09 0.00 0.00 0.00 0.00 166588.89 0.103601E+09
March 0.489771E+09 0.712502E+09 0.106120E+10 0.00 0.00 0.00 0.00 317300.37 0.121110E+09
April 0.472586E+09 0.686229E+09 0.102351E+10 0.00 0.00 0.00 0.00 1094949.89 89050494.13
May 0.488511E+09 0.711544E+09 0.106025E+10 0.00 0.00 0.00 0.00 121281.68 89841430.37
June 0.473617E+09 0.689376E+09 0.102685E+10 0.00 0.00 0.00 0.00 622329.60 64621337.69
July 0.487480E+09 0.708397E+09 0.105691E+10 0.00 0.00 0.00 0.00 3170130.22 49851890.25
August 0.489542E+09 0.712775E+09 0.106152E+10 0.00 0.00 0.00 0.00 3818117.20 47348309.10
September 0.472357E+09 0.686503E+09 0.102382E+10 0.00 0.00 0.00 0.00 3678537.85 58640181.19
October 0.487709E+09 0.710039E+09 0.105866E+10 0.00 0.00 0.00 0.00 7240176.31 61943971.86
November 0.471555E+09 0.688829E+09 0.102637E+10 0.00 0.00 0.00 0.00 832016.74 0.102899E+09
December 0.487480E+09 0.708397E+09 0.105691E+10 0.00 0.00 0.00 0.00 1101334.91 0.113194E+09
                   
Annual Sum or Average 0.574883E+10 0.836625E+10 0.124712E+11 0.00 0.00 0.00 0.00 23311867.12 0.101812E+10
Minimum of Months 0.440737E+09 0.641347E+09 0.956227E+09 0.00 0.00 0.00 0.00 121281.68 47348309.10
Maximum of Months 0.489771E+09 0.712775E+09 0.106152E+10 0.00 0.00 0.00 0.00 7240176.31 0.121110E+09



Table of Contents

Report: SpaceGainsMonthly

For: STORAGE_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.374985E+09 0.261454E+09 0.305485E+09 0.00 0.00 0.00 0.00 686797.64 65319874.30
February 0.339028E+09 0.236069E+09 0.275845E+09 0.00 0.00 0.00 0.00 104475.23 58026455.03
March 0.376747E+09 0.262260E+09 0.306128E+09 0.00 0.00 0.00 0.00 194956.55 68184518.63
April 0.363528E+09 0.252589E+09 0.295253E+09 0.00 0.00 0.00 0.00 663255.85 49693433.16
May 0.375778E+09 0.261907E+09 0.305852E+09 0.00 0.00 0.00 0.00 86477.26 49965854.57
June 0.364321E+09 0.253748E+09 0.296217E+09 0.00 0.00 0.00 0.00 437541.43 35645141.47
July 0.374985E+09 0.260749E+09 0.304889E+09 0.00 0.00 0.00 0.00 2002427.88 27190298.98
August 0.376571E+09 0.262360E+09 0.306219E+09 0.00 0.00 0.00 0.00 2411963.92 25769644.18
September 0.363352E+09 0.252690E+09 0.295345E+09 0.00 0.00 0.00 0.00 2200554.02 32209066.83
October 0.375161E+09 0.261353E+09 0.305393E+09 0.00 0.00 0.00 0.00 4287131.35 34013639.44
November 0.362735E+09 0.253546E+09 0.296079E+09 0.00 0.00 0.00 0.00 502084.52 57517943.16
December 0.374985E+09 0.260749E+09 0.304889E+09 0.00 0.00 0.00 0.00 668440.16 63441436.93
                   
Annual Sum or Average 0.442217E+10 0.307947E+10 0.359760E+10 0.00 0.00 0.00 0.00 14246105.80 0.566977E+09
Minimum of Months 0.339028E+09 0.236069E+09 0.275845E+09 0.00 0.00 0.00 0.00 86477.26 25769644.18
Maximum of Months 0.376747E+09 0.262360E+09 0.306219E+09 0.00 0.00 0.00 0.00 4287131.35 68184518.63



Table of Contents

Report: SpaceGainsMonthly

For: LAUNDRY_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.154405E+10 0.337502E+09 0.576866E+10 0.501157E+11 0.00 0.00 0.00 1198675.34 0.173909E+09
February 0.139600E+10 0.304733E+09 0.520895E+10 0.452532E+11 0.00 0.00 0.00 169195.27 0.155199E+09
March 0.155131E+10 0.338542E+09 0.578079E+10 0.502211E+11 0.00 0.00 0.00 218072.11 0.182504E+09
April 0.149688E+10 0.326059E+09 0.557545E+10 0.484372E+11 0.00 0.00 0.00 1201371.84 0.132133E+09
May 0.154732E+10 0.338087E+09 0.577559E+10 0.501759E+11 0.00 0.00 0.00 187961.97 0.130824E+09
June 0.150015E+10 0.327554E+09 0.559364E+10 0.485952E+11 0.00 0.00 0.00 1443660.76 90708095.18
July 0.154405E+10 0.336592E+09 0.575740E+10 0.500179E+11 0.00 0.00 0.00 6265179.55 67023513.63
August 0.155059E+10 0.338672E+09 0.578252E+10 0.502361E+11 0.00 0.00 0.00 7462755.43 64006819.97
September 0.149615E+10 0.326189E+09 0.557718E+10 0.484522E+11 0.00 0.00 0.00 5741672.61 81236499.17
October 0.154478E+10 0.337372E+09 0.576693E+10 0.501006E+11 0.00 0.00 0.00 11080148.87 84732404.21
November 0.149361E+10 0.327294E+09 0.559104E+10 0.485726E+11 0.00 0.00 0.00 985550.43 0.149953E+09
December 0.154405E+10 0.336592E+09 0.575740E+10 0.500179E+11 0.00 0.00 0.00 1033553.58 0.167364E+09
                   
Annual Sum or Average 0.182090E+11 0.397519E+10 0.679355E+11 0.590196E+12 0.00 0.00 0.00 36987797.75 0.147959E+10
Minimum of Months 0.139600E+10 0.304733E+09 0.520895E+10 0.452532E+11 0.00 0.00 0.00 169195.27 64006819.97
Maximum of Months 0.155131E+10 0.338672E+09 0.578252E+10 0.502361E+11 0.00 0.00 0.00 11080148.87 0.182504E+09



Table of Contents

Report: SpaceGainsMonthly

For: CAFE_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.261570E+11 0.130497E+10 0.121771E+10 0.00 0.00 0.00 0.00 904652.31 0.320192E+09
February 0.236489E+11 0.114673E+10 0.109956E+10 0.00 0.00 0.00 0.00 68835.78 0.280511E+09
March 0.262800E+11 0.125376E+10 0.122027E+10 0.00 0.00 0.00 0.00 0.00 0.321243E+09
April 0.253579E+11 0.113983E+10 0.117692E+10 0.00 0.00 0.00 0.00 1098081.89 0.237110E+09
May 0.262123E+11 0.112129E+10 0.121917E+10 0.00 0.00 0.00 0.00 157874.30 0.225737E+09
June 0.254132E+11 0.107741E+10 0.118076E+10 0.00 0.00 0.00 0.00 2802965.86 0.159660E+09
July 0.261570E+11 0.111560E+10 0.121533E+10 0.00 0.00 0.00 0.00 9534737.59 0.123058E+09
August 0.262677E+11 0.115503E+10 0.122063E+10 0.00 0.00 0.00 0.00 8380553.79 0.122600E+09
September 0.253456E+11 0.120189E+10 0.117729E+10 0.00 0.00 0.00 0.00 7689721.73 0.158366E+09
October 0.261693E+11 0.128074E+10 0.121734E+10 0.00 0.00 0.00 0.00 13879969.42 0.164554E+09
November 0.253025E+11 0.124997E+10 0.118021E+10 0.00 0.00 0.00 0.00 621791.48 0.281005E+09
December 0.261570E+11 0.129666E+10 0.121533E+10 0.00 0.00 0.00 0.00 392471.36 0.311576E+09
                   
Annual Sum or Average 0.308468E+12 0.143439E+11 0.143405E+11 0.00 0.00 0.00 0.00 45531655.52 0.270561E+10
Minimum of Months 0.236489E+11 0.107741E+10 0.109956E+10 0.00 0.00 0.00 0.00 0.00 0.122600E+09
Maximum of Months 0.262800E+11 0.130497E+10 0.122063E+10 0.00 0.00 0.00 0.00 13879969.42 0.321243E+09



Table of Contents

Report: SpaceGainsMonthly

For: LOBBY_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.776503E+11 0.941787E+10 0.126520E+11 0.00 0.00 0.00 0.00 4254819.30 0.909171E+09
February 0.702046E+11 0.847556E+10 0.114244E+11 0.00 0.00 0.00 0.00 498523.45 0.808499E+09
March 0.780153E+11 0.940788E+10 0.126786E+11 0.00 0.00 0.00 0.00 614936.02 0.932707E+09
April 0.752779E+11 0.900527E+10 0.122282E+11 0.00 0.00 0.00 0.00 4785480.87 0.692209E+09
May 0.778146E+11 0.929404E+10 0.126672E+11 0.00 0.00 0.00 0.00 687921.74 0.680903E+09
June 0.754422E+11 0.899654E+10 0.122682E+11 0.00 0.00 0.00 0.00 5698830.99 0.487020E+09
July 0.776503E+11 0.924755E+10 0.126273E+11 0.00 0.00 0.00 0.00 25021937.79 0.374631E+09
August 0.779788E+11 0.933252E+10 0.126824E+11 0.00 0.00 0.00 0.00 27046363.99 0.363497E+09
September 0.752414E+11 0.906632E+10 0.122320E+11 0.00 0.00 0.00 0.00 23285947.84 0.456201E+09
October 0.776868E+11 0.940530E+10 0.126482E+11 0.00 0.00 0.00 0.00 44607288.56 0.476545E+09
November 0.751137E+11 0.911494E+10 0.122624E+11 0.00 0.00 0.00 0.00 2642461.98 0.802353E+09
December 0.776503E+11 0.938557E+10 0.126273E+11 0.00 0.00 0.00 0.00 2714135.67 0.888052E+09
                   
Annual Sum or Average 0.915726E+12 0.110149E+12 0.148998E+12 0.00 0.00 0.00 0.00 0.141859E+09 0.787179E+10
Minimum of Months 0.702046E+11 0.847556E+10 0.114244E+11 0.00 0.00 0.00 0.00 498523.45 0.363497E+09
Maximum of Months 0.780153E+11 0.941787E+10 0.126824E+11 0.00 0.00 0.00 0.00 44607288.56 0.932707E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_1_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.196602E+09 0.222503E+09 0.00 0.00 0.00 0.00 483588.43 71871104.38
February 0.273974E+09 0.177551E+09 0.200969E+09 0.00 0.00 0.00 0.00 85145.19 62956333.72
March 0.303685E+09 0.195039E+09 0.222390E+09 0.00 0.00 0.00 0.00 80929.00 75132039.89
April 0.293479E+09 0.190486E+09 0.215344E+09 0.00 0.00 0.00 0.00 440911.07 52219050.28
May 0.303504E+09 0.195821E+09 0.222446E+09 0.00 0.00 0.00 0.00 41113.08 51129372.52
June 0.293842E+09 0.188975E+09 0.215230E+09 0.00 0.00 0.00 0.00 549822.90 33011265.68
July 0.303141E+09 0.197358E+09 0.222560E+09 0.00 0.00 0.00 0.00 2553513.23 21747343.41
August 0.303685E+09 0.195039E+09 0.222390E+09 0.00 0.00 0.00 0.00 3007055.64 20326848.62
September 0.293479E+09 0.190538E+09 0.215344E+09 0.00 0.00 0.00 0.00 2888375.57 29112591.71
October 0.303322E+09 0.196576E+09 0.222503E+09 0.00 0.00 0.00 0.00 5054910.11 29878402.56
November 0.293661E+09 0.189731E+09 0.215287E+09 0.00 0.00 0.00 0.00 379862.95 60195000.46
December 0.303141E+09 0.197383E+09 0.222560E+09 0.00 0.00 0.00 0.00 420923.81 68644891.24
                   
Annual Sum or Average 0.357224E+10 0.231110E+10 0.261953E+10 0.00 0.00 0.00 0.00 15986150.98 0.576224E+09
Minimum of Months 0.273974E+09 0.177551E+09 0.200969E+09 0.00 0.00 0.00 0.00 41113.08 20326848.62
Maximum of Months 0.303685E+09 0.197383E+09 0.222560E+09 0.00 0.00 0.00 0.00 5054910.11 75132039.89



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_2_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.196579E+09 0.222477E+09 0.00 0.00 0.00 0.00 561819.29 70642957.85
February 0.273974E+09 0.177530E+09 0.200945E+09 0.00 0.00 0.00 0.00 98509.90 62244402.17
March 0.303685E+09 0.195017E+09 0.222364E+09 0.00 0.00 0.00 0.00 102406.46 74959268.58
April 0.293479E+09 0.190464E+09 0.215319E+09 0.00 0.00 0.00 0.00 396896.01 54714150.38
May 0.303504E+09 0.195798E+09 0.222420E+09 0.00 0.00 0.00 0.00 28265.64 54719793.47
June 0.293842E+09 0.188953E+09 0.215205E+09 0.00 0.00 0.00 0.00 367744.83 40097269.37
July 0.303141E+09 0.197334E+09 0.222534E+09 0.00 0.00 0.00 0.00 2121001.87 30788730.68
August 0.303685E+09 0.195017E+09 0.222364E+09 0.00 0.00 0.00 0.00 2458428.38 28456306.10
September 0.293479E+09 0.190515E+09 0.215319E+09 0.00 0.00 0.00 0.00 2776368.24 34028279.34
October 0.303322E+09 0.196553E+09 0.222477E+09 0.00 0.00 0.00 0.00 4852244.97 33543624.95
November 0.293661E+09 0.189708E+09 0.215262E+09 0.00 0.00 0.00 0.00 441266.74 59860783.59
December 0.303141E+09 0.197360E+09 0.222534E+09 0.00 0.00 0.00 0.00 552446.41 67618145.40
                   
Annual Sum or Average 0.357224E+10 0.231083E+10 0.261922E+10 0.00 0.00 0.00 0.00 14757398.75 0.611674E+09
Minimum of Months 0.273974E+09 0.177530E+09 0.200945E+09 0.00 0.00 0.00 0.00 28265.64 28456306.10
Maximum of Months 0.303685E+09 0.197360E+09 0.222534E+09 0.00 0.00 0.00 0.00 4852244.97 74959268.58



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.123557E+09 0.217935E+09 0.00 0.00 0.00 0.00 0.00 31649454.91
February 0.00 0.111584E+09 0.196843E+09 0.00 0.00 0.00 0.00 0.00 28058552.13
March 0.00 0.122575E+09 0.217824E+09 0.00 0.00 0.00 0.00 0.00 32348739.41
April 0.00 0.119713E+09 0.210923E+09 0.00 0.00 0.00 0.00 263.49 25532765.42
May 0.00 0.123066E+09 0.217879E+09 0.00 0.00 0.00 0.00 0.00 25626830.70
June 0.00 0.118764E+09 0.210812E+09 0.00 0.00 0.00 0.00 0.00 20077475.88
July 0.00 0.124032E+09 0.217991E+09 0.00 0.00 0.00 0.00 19981.07 16697791.56
August 0.00 0.122575E+09 0.217824E+09 0.00 0.00 0.00 0.00 13567.91 16171071.79
September 0.00 0.119746E+09 0.210923E+09 0.00 0.00 0.00 0.00 296030.18 18631719.21
October 0.00 0.123541E+09 0.217935E+09 0.00 0.00 0.00 0.00 507387.01 18829407.53
November 0.00 0.119238E+09 0.210867E+09 0.00 0.00 0.00 0.00 202.80 27967906.96
December 0.00 0.124048E+09 0.217991E+09 0.00 0.00 0.00 0.00 0.00 30739510.41
                   
Annual Sum or Average 0.00 0.145244E+10 0.256575E+10 0.00 0.00 0.00 0.00 837432.46 0.292331E+09
Minimum of Months 0.00 0.111584E+09 0.196843E+09 0.00 0.00 0.00 0.00 0.00 16171071.79
Maximum of Months 0.00 0.124048E+09 0.217991E+09 0.00 0.00 0.00 0.00 507387.01 32348739.41



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.123591E+09 0.217995E+09 0.00 0.00 0.00 0.00 196540.27 19645921.12
February 0.273974E+09 0.111614E+09 0.196897E+09 0.00 0.00 0.00 0.00 36448.40 17266284.59
March 0.303685E+09 0.122608E+09 0.217883E+09 0.00 0.00 0.00 0.00 42557.95 20748984.39
April 0.293479E+09 0.119746E+09 0.210981E+09 0.00 0.00 0.00 0.00 145699.28 14509597.38
May 0.303504E+09 0.123099E+09 0.217939E+09 0.00 0.00 0.00 0.00 14912.74 14503646.02
June 0.293842E+09 0.118796E+09 0.210869E+09 0.00 0.00 0.00 0.00 128445.78 10141029.11
July 0.303141E+09 0.124066E+09 0.218051E+09 0.00 0.00 0.00 0.00 648711.06 7403302.25
August 0.303685E+09 0.122608E+09 0.217883E+09 0.00 0.00 0.00 0.00 774441.90 6838450.28
September 0.293479E+09 0.119778E+09 0.210981E+09 0.00 0.00 0.00 0.00 803481.10 8694453.15
October 0.303322E+09 0.123574E+09 0.217995E+09 0.00 0.00 0.00 0.00 1447735.47 8920848.30
November 0.293661E+09 0.119271E+09 0.210925E+09 0.00 0.00 0.00 0.00 170166.38 16395371.51
December 0.303141E+09 0.124082E+09 0.218051E+09 0.00 0.00 0.00 0.00 210777.43 18703555.99
                   
Annual Sum or Average 0.357224E+10 0.145283E+10 0.256645E+10 0.00 0.00 0.00 0.00 4619917.76 0.163771E+09
Minimum of Months 0.273974E+09 0.111614E+09 0.196897E+09 0.00 0.00 0.00 0.00 14912.74 6838450.28
Maximum of Months 0.303685E+09 0.124082E+09 0.218051E+09 0.00 0.00 0.00 0.00 1447735.47 20748984.39



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_5_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.196602E+09 0.222503E+09 0.00 0.00 0.00 0.00 470604.10 72230560.37
February 0.273974E+09 0.177551E+09 0.200969E+09 0.00 0.00 0.00 0.00 83253.31 63083789.82
March 0.303685E+09 0.195039E+09 0.222390E+09 0.00 0.00 0.00 0.00 77098.21 75476126.40
April 0.293479E+09 0.190486E+09 0.215344E+09 0.00 0.00 0.00 0.00 423760.89 52498419.78
May 0.303504E+09 0.195821E+09 0.222446E+09 0.00 0.00 0.00 0.00 40223.67 51392676.31
June 0.293842E+09 0.188975E+09 0.215230E+09 0.00 0.00 0.00 0.00 513531.32 33108893.82
July 0.303141E+09 0.197358E+09 0.222560E+09 0.00 0.00 0.00 0.00 2511276.80 21916875.60
August 0.303685E+09 0.195039E+09 0.222390E+09 0.00 0.00 0.00 0.00 2942826.80 20461167.90
September 0.293479E+09 0.190538E+09 0.215344E+09 0.00 0.00 0.00 0.00 2876650.18 29110415.63
October 0.303322E+09 0.196576E+09 0.222503E+09 0.00 0.00 0.00 0.00 5047201.05 29993108.86
November 0.293661E+09 0.189731E+09 0.215287E+09 0.00 0.00 0.00 0.00 373865.29 60375390.52
December 0.303141E+09 0.197383E+09 0.222560E+09 0.00 0.00 0.00 0.00 415311.67 68896632.66
                   
Annual Sum or Average 0.357224E+10 0.231110E+10 0.261953E+10 0.00 0.00 0.00 0.00 15775603.28 0.578544E+09
Minimum of Months 0.273974E+09 0.177551E+09 0.200969E+09 0.00 0.00 0.00 0.00 40223.67 20461167.90
Maximum of Months 0.303685E+09 0.197383E+09 0.222560E+09 0.00 0.00 0.00 0.00 5047201.05 75476126.40



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_6_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.196579E+09 0.222477E+09 0.00 0.00 0.00 0.00 528100.39 70743579.42
February 0.273974E+09 0.177530E+09 0.200945E+09 0.00 0.00 0.00 0.00 73952.96 62110181.71
March 0.303685E+09 0.195017E+09 0.222364E+09 0.00 0.00 0.00 0.00 77477.60 75042749.79
April 0.293479E+09 0.190464E+09 0.215319E+09 0.00 0.00 0.00 0.00 324099.18 54048003.92
May 0.303504E+09 0.195798E+09 0.222420E+09 0.00 0.00 0.00 0.00 27166.38 54021933.34
June 0.293842E+09 0.188953E+09 0.215205E+09 0.00 0.00 0.00 0.00 329432.45 38217539.39
July 0.303141E+09 0.197334E+09 0.222534E+09 0.00 0.00 0.00 0.00 2053752.21 29137349.85
August 0.303685E+09 0.195017E+09 0.222364E+09 0.00 0.00 0.00 0.00 2347162.79 27294072.26
September 0.293479E+09 0.190515E+09 0.215319E+09 0.00 0.00 0.00 0.00 2726585.78 32865799.75
October 0.303322E+09 0.196553E+09 0.222477E+09 0.00 0.00 0.00 0.00 4693409.55 33183922.53
November 0.293661E+09 0.189708E+09 0.215262E+09 0.00 0.00 0.00 0.00 413684.11 59527496.79
December 0.303141E+09 0.197360E+09 0.222534E+09 0.00 0.00 0.00 0.00 483828.08 67623130.02
                   
Annual Sum or Average 0.357224E+10 0.231083E+10 0.261922E+10 0.00 0.00 0.00 0.00 14078651.48 0.603816E+09
Minimum of Months 0.273974E+09 0.177530E+09 0.200945E+09 0.00 0.00 0.00 0.00 27166.38 27294072.26
Maximum of Months 0.303685E+09 0.197360E+09 0.222534E+09 0.00 0.00 0.00 0.00 4693409.55 75042749.79



Table of Contents

Report: SpaceGainsMonthly

For: CORRIDOR_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.385223E+10 0.193865E+10 0.00 0.00 0.00 0.00 0.00 871781.25 88706680.96
February 0.348285E+10 0.175042E+10 0.00 0.00 0.00 0.00 0.00 124604.31 78657352.78
March 0.387034E+10 0.194462E+10 0.00 0.00 0.00 0.00 0.00 188082.20 91984987.44
April 0.373454E+10 0.187292E+10 0.00 0.00 0.00 0.00 0.00 814662.84 67098328.11
May 0.386038E+10 0.194201E+10 0.00 0.00 0.00 0.00 0.00 109000.60 66534755.81
June 0.374269E+10 0.188151E+10 0.00 0.00 0.00 0.00 0.00 664611.72 46706664.65
July 0.385223E+10 0.193342E+10 0.00 0.00 0.00 0.00 0.00 2765576.90 35869021.02
August 0.386853E+10 0.194537E+10 0.00 0.00 0.00 0.00 0.00 3071344.59 34800314.26
September 0.373273E+10 0.187367E+10 0.00 0.00 0.00 0.00 0.00 2916524.40 43373488.71
October 0.385404E+10 0.193790E+10 0.00 0.00 0.00 0.00 0.00 5550197.45 46026505.69
November 0.372639E+10 0.188002E+10 0.00 0.00 0.00 0.00 0.00 589807.58 78001564.73
December 0.385223E+10 0.193342E+10 0.00 0.00 0.00 0.00 0.00 733988.29 86701475.77
                   
Annual Sum or Average 0.454292E+11 0.228339E+11 0.00 0.00 0.00 0.00 0.00 18400182.15 0.764461E+09
Minimum of Months 0.348285E+10 0.175042E+10 0.00 0.00 0.00 0.00 0.00 109000.60 34800314.26
Maximum of Months 0.387034E+10 0.194537E+10 0.00 0.00 0.00 0.00 0.00 5550197.45 91984987.44



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_1_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.196602E+09 0.222503E+09 0.00 0.00 0.00 0.00 461416.87 72059402.46
February 0.273974E+09 0.177551E+09 0.200969E+09 0.00 0.00 0.00 0.00 82273.22 63054761.59
March 0.303685E+09 0.195039E+09 0.222390E+09 0.00 0.00 0.00 0.00 74535.41 75323156.44
April 0.293479E+09 0.190486E+09 0.215344E+09 0.00 0.00 0.00 0.00 414302.46 52606423.94
May 0.303504E+09 0.195821E+09 0.222446E+09 0.00 0.00 0.00 0.00 35994.91 51566389.53
June 0.293842E+09 0.188975E+09 0.215230E+09 0.00 0.00 0.00 0.00 500088.48 33413153.52
July 0.303141E+09 0.197358E+09 0.222560E+09 0.00 0.00 0.00 0.00 2439617.74 22113031.73
August 0.303685E+09 0.195039E+09 0.222390E+09 0.00 0.00 0.00 0.00 2875427.25 20649740.18
September 0.293479E+09 0.190538E+09 0.215344E+09 0.00 0.00 0.00 0.00 2840931.13 29457737.63
October 0.303322E+09 0.196576E+09 0.222503E+09 0.00 0.00 0.00 0.00 4965663.89 30133621.95
November 0.293661E+09 0.189731E+09 0.215287E+09 0.00 0.00 0.00 0.00 365950.93 60400055.55
December 0.303141E+09 0.197383E+09 0.222560E+09 0.00 0.00 0.00 0.00 403853.44 68796095.42
                   
Annual Sum or Average 0.357224E+10 0.231110E+10 0.261953E+10 0.00 0.00 0.00 0.00 15460055.71 0.579574E+09
Minimum of Months 0.273974E+09 0.177551E+09 0.200969E+09 0.00 0.00 0.00 0.00 35994.91 20649740.18
Maximum of Months 0.303685E+09 0.197383E+09 0.222560E+09 0.00 0.00 0.00 0.00 4965663.89 75323156.44



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_2_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.196579E+09 0.222477E+09 0.00 0.00 0.00 0.00 555896.54 70521539.28
February 0.273974E+09 0.177530E+09 0.200945E+09 0.00 0.00 0.00 0.00 102915.73 62187957.72
March 0.303685E+09 0.195017E+09 0.222364E+09 0.00 0.00 0.00 0.00 90081.03 75228311.67
April 0.293479E+09 0.190464E+09 0.215319E+09 0.00 0.00 0.00 0.00 360310.14 55574908.24
May 0.303504E+09 0.195798E+09 0.222420E+09 0.00 0.00 0.00 0.00 24638.60 55585165.31
June 0.293842E+09 0.188953E+09 0.215205E+09 0.00 0.00 0.00 0.00 330489.16 41393462.44
July 0.303141E+09 0.197334E+09 0.222534E+09 0.00 0.00 0.00 0.00 2026531.66 32201205.82
August 0.303685E+09 0.195017E+09 0.222364E+09 0.00 0.00 0.00 0.00 2345776.70 29553328.28
September 0.293479E+09 0.190515E+09 0.215319E+09 0.00 0.00 0.00 0.00 2742977.52 34534142.34
October 0.303322E+09 0.196553E+09 0.222477E+09 0.00 0.00 0.00 0.00 4809789.92 33502342.28
November 0.293661E+09 0.189708E+09 0.215262E+09 0.00 0.00 0.00 0.00 448017.24 59750403.98
December 0.303141E+09 0.197360E+09 0.222534E+09 0.00 0.00 0.00 0.00 574536.75 67366827.91
                   
Annual Sum or Average 0.357224E+10 0.231083E+10 0.261922E+10 0.00 0.00 0.00 0.00 14411960.98 0.617400E+09
Minimum of Months 0.273974E+09 0.177530E+09 0.200945E+09 0.00 0.00 0.00 0.00 24638.60 29553328.28
Maximum of Months 0.303685E+09 0.197360E+09 0.222534E+09 0.00 0.00 0.00 0.00 4809789.92 75228311.67



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.123591E+09 0.217995E+09 0.00 0.00 0.00 0.00 219953.61 37434635.74
February 0.273974E+09 0.111614E+09 0.196897E+09 0.00 0.00 0.00 0.00 40491.04 32772530.66
March 0.303685E+09 0.122608E+09 0.217883E+09 0.00 0.00 0.00 0.00 35952.51 38986156.98
April 0.293479E+09 0.119746E+09 0.210981E+09 0.00 0.00 0.00 0.00 209188.02 26974667.95
May 0.303504E+09 0.123099E+09 0.217939E+09 0.00 0.00 0.00 0.00 18606.63 26270557.93
June 0.293842E+09 0.118796E+09 0.210869E+09 0.00 0.00 0.00 0.00 263875.64 16927746.69
July 0.303141E+09 0.124066E+09 0.218051E+09 0.00 0.00 0.00 0.00 1261063.46 11223436.88
August 0.303685E+09 0.122608E+09 0.217883E+09 0.00 0.00 0.00 0.00 1468236.51 10522023.20
September 0.293479E+09 0.119778E+09 0.210981E+09 0.00 0.00 0.00 0.00 1449975.87 15061596.34
October 0.303322E+09 0.123574E+09 0.217995E+09 0.00 0.00 0.00 0.00 2521286.89 15539753.29
November 0.293661E+09 0.119271E+09 0.210925E+09 0.00 0.00 0.00 0.00 177076.68 31322019.54
December 0.303141E+09 0.124082E+09 0.218051E+09 0.00 0.00 0.00 0.00 199732.99 35757297.26
                   
Annual Sum or Average 0.357224E+10 0.145283E+10 0.256645E+10 0.00 0.00 0.00 0.00 7865439.85 0.298792E+09
Minimum of Months 0.273974E+09 0.111614E+09 0.196897E+09 0.00 0.00 0.00 0.00 18606.63 10522023.20
Maximum of Months 0.303685E+09 0.124082E+09 0.218051E+09 0.00 0.00 0.00 0.00 2521286.89 38986156.98



Table of Contents

Report: SpaceGainsMonthly

For: BANQUET_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.459349E+11 0.278781E+10 0.149358E+11 0.00 0.00 0.00 0.00 600521.39 0.216947E+09
February 0.415303E+11 0.246232E+10 0.134904E+11 0.00 0.00 0.00 0.00 91375.58 0.194689E+09
March 0.461508E+11 0.268528E+10 0.149358E+11 0.00 0.00 0.00 0.00 26201.31 0.228496E+09
April 0.445315E+11 0.249776E+10 0.144540E+11 0.00 0.00 0.00 0.00 413226.73 0.170855E+09
May 0.460320E+11 0.250863E+10 0.149358E+11 0.00 0.00 0.00 0.00 13299.06 0.171040E+09
June 0.446286E+11 0.240793E+10 0.144540E+11 0.00 0.00 0.00 0.00 131438.50 0.123891E+09
July 0.459349E+11 0.248899E+10 0.149358E+11 0.00 0.00 0.00 0.00 2281153.14 94653980.46
August 0.461292E+11 0.255593E+10 0.149358E+11 0.00 0.00 0.00 0.00 2689743.09 90075115.16
September 0.445099E+11 0.257519E+10 0.144540E+11 0.00 0.00 0.00 0.00 4523372.72 0.111988E+09
October 0.459565E+11 0.275378E+10 0.149358E+11 0.00 0.00 0.00 0.00 9092669.76 0.114477E+09
November 0.444343E+11 0.268255E+10 0.144540E+11 0.00 0.00 0.00 0.00 522244.43 0.189385E+09
December 0.459349E+11 0.278872E+10 0.149358E+11 0.00 0.00 0.00 0.00 545702.24 0.210098E+09
                   
Annual Sum or Average 0.541708E+12 0.311949E+11 0.175857E+12 0.00 0.00 0.00 0.00 20930947.96 0.191660E+10
Minimum of Months 0.415303E+11 0.240793E+10 0.134904E+11 0.00 0.00 0.00 0.00 13299.06 90075115.16
Maximum of Months 0.461508E+11 0.278872E+10 0.149358E+11 0.00 0.00 0.00 0.00 9092669.76 0.228496E+09



Table of Contents

Report: SpaceGainsMonthly

For: DINING_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.459349E+11 0.278781E+10 0.149358E+11 0.00 0.00 0.00 0.00 455757.88 0.219851E+09
February 0.415303E+11 0.246232E+10 0.134904E+11 0.00 0.00 0.00 0.00 69979.39 0.197156E+09
March 0.461508E+11 0.268528E+10 0.149358E+11 0.00 0.00 0.00 0.00 4085.57 0.231488E+09
April 0.445315E+11 0.249776E+10 0.144540E+11 0.00 0.00 0.00 0.00 346375.21 0.172573E+09
May 0.460320E+11 0.250863E+10 0.149358E+11 0.00 0.00 0.00 0.00 2938.90 0.172700E+09
June 0.446286E+11 0.240793E+10 0.144540E+11 0.00 0.00 0.00 0.00 64776.01 0.125006E+09
July 0.459349E+11 0.248899E+10 0.149358E+11 0.00 0.00 0.00 0.00 2039748.45 95302837.13
August 0.461292E+11 0.255593E+10 0.149358E+11 0.00 0.00 0.00 0.00 2372923.44 90712574.00
September 0.445099E+11 0.257519E+10 0.144540E+11 0.00 0.00 0.00 0.00 4450419.64 0.113107E+09
October 0.459565E+11 0.275378E+10 0.149358E+11 0.00 0.00 0.00 0.00 8788080.13 0.115483E+09
November 0.444343E+11 0.268255E+10 0.144540E+11 0.00 0.00 0.00 0.00 444435.02 0.191554E+09
December 0.459349E+11 0.278872E+10 0.149358E+11 0.00 0.00 0.00 0.00 402839.38 0.212774E+09
                   
Annual Sum or Average 0.541708E+12 0.311949E+11 0.175857E+12 0.00 0.00 0.00 0.00 19442359.05 0.193771E+10
Minimum of Months 0.415303E+11 0.240793E+10 0.134904E+11 0.00 0.00 0.00 0.00 2938.90 90712574.00
Maximum of Months 0.461508E+11 0.278872E+10 0.149358E+11 0.00 0.00 0.00 0.00 8788080.13 0.231488E+09



Table of Contents

Report: SpaceGainsMonthly

For: KITCHEN_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.408770E+10 0.110133E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 271280.49 0.195209E+09
February 0.369574E+10 0.994402E+09 0.301256E+11 0.275852E+11 0.00 0.00 0.00 35974.29 0.175673E+09
March 0.410691E+10 0.110473E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 0.00 0.205423E+09
April 0.396281E+10 0.106399E+10 0.322775E+11 0.295556E+11 0.00 0.00 0.00 273325.49 0.153418E+09
May 0.409635E+10 0.110324E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 0.00 0.153318E+09
June 0.397146E+10 0.106887E+10 0.322775E+11 0.295556E+11 0.00 0.00 0.00 19537.04 0.110984E+09
July 0.408770E+10 0.109836E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 1683660.33 84384461.58
August 0.410499E+10 0.110515E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 1906274.16 80442412.97
September 0.396089E+10 0.106442E+10 0.322775E+11 0.295556E+11 0.00 0.00 0.00 3958266.59 0.100703E+09
October 0.408962E+10 0.110091E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 7500555.02 0.102486E+09
November 0.395417E+10 0.106802E+10 0.322775E+11 0.295556E+11 0.00 0.00 0.00 335260.86 0.170396E+09
December 0.408770E+10 0.109836E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 202863.52 0.188484E+09
                   
Annual Sum or Average 0.482060E+11 0.129718E+11 0.392709E+12 0.359593E+12 0.00 0.00 0.00 16186997.80 0.172092E+10
Minimum of Months 0.369574E+10 0.994402E+09 0.301256E+11 0.275852E+11 0.00 0.00 0.00 0.00 80442412.97
Maximum of Months 0.410691E+10 0.110515E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 7500555.02 0.205423E+09



Table of Contents

Report: SpaceGainsMonthly

For: CORRIDOR_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.407704E+10 0.205176E+10 0.00 0.00 0.00 0.00 0.00 1134040.76 0.156824E+09
February 0.368610E+10 0.185255E+10 0.00 0.00 0.00 0.00 0.00 166041.71 0.138076E+09
March 0.409620E+10 0.205809E+10 0.00 0.00 0.00 0.00 0.00 162981.54 0.163895E+09
April 0.395248E+10 0.198220E+10 0.00 0.00 0.00 0.00 0.00 820502.72 0.120851E+09
May 0.408566E+10 0.205532E+10 0.00 0.00 0.00 0.00 0.00 43011.97 0.119368E+09
June 0.396110E+10 0.199129E+10 0.00 0.00 0.00 0.00 0.00 434773.59 85150446.39
July 0.407704E+10 0.204623E+10 0.00 0.00 0.00 0.00 0.00 3259928.79 65575831.60
August 0.409429E+10 0.205888E+10 0.00 0.00 0.00 0.00 0.00 3535599.26 63151966.71
September 0.395056E+10 0.198299E+10 0.00 0.00 0.00 0.00 0.00 4535677.03 78035636.77
October 0.407896E+10 0.205097E+10 0.00 0.00 0.00 0.00 0.00 8649267.47 80681672.54
November 0.394385E+10 0.198971E+10 0.00 0.00 0.00 0.00 0.00 786376.05 0.135672E+09
December 0.407704E+10 0.204623E+10 0.00 0.00 0.00 0.00 0.00 920493.08 0.150932E+09
                   
Annual Sum or Average 0.480803E+11 0.241662E+11 0.00 0.00 0.00 0.00 0.00 24448693.98 0.135821E+10
Minimum of Months 0.368610E+10 0.185255E+10 0.00 0.00 0.00 0.00 0.00 43011.97 63151966.71
Maximum of Months 0.409620E+10 0.205888E+10 0.00 0.00 0.00 0.00 0.00 8649267.47 0.163895E+09



Table of Contents

Report: PeakSpaceGainsMonthly

For: BASEMENT

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 11501.89 02-JAN-00:10 13190.31 02-JAN-20:10 9632.53 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 0.00
February 11501.89 01-FEB-00:10 13190.31 01-FEB-20:10 9632.53 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 0.00
March 11501.89 01-MAR-00:10 13190.31 01-MAR-20:10 9632.53 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 0.00
April 11501.89 01-APR-00:10 13190.31 03-APR-19:10 9632.53 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 0.00
May 11501.89 01-MAY-00:10 13190.31 01-MAY-19:10 9632.53 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 0.00
June 11501.89 01-JUN-00:10 13190.31 01-JUN-19:10 9632.53 01-JUN-19:10 0.00 0.00 0.00 0.00 0.00 0.00
July 11501.89 01-JUL-00:10 13190.31 03-JUL-19:10 9632.53 03-JUL-19:10 0.00 0.00 0.00 0.00 0.00 0.00
August 11501.89 01-AUG-00:10 13190.31 01-AUG-19:10 9632.53 01-AUG-19:10 0.00 0.00 0.00 0.00 0.00 0.00
September 11501.89 01-SEP-00:10 13190.31 01-SEP-19:10 9632.53 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 0.00
October 11501.89 01-OCT-23:10 13190.31 02-OCT-19:10 9632.53 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 0.00
November 11501.89 01-NOV-00:10 13190.31 01-NOV-19:10 9632.53 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 0.00
December 11501.89 01-DEC-00:10 13190.31 01-DEC-20:10 9632.53 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 11501.89   13190.31   9632.53   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 11501.89   13190.31   9632.53   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: RETAIL_1_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1169.53 02-JAN-00:10 597.59 02-JAN-20:10 685.60 02-JAN-20:10 0.00 0.00 0.00 0.00 13.59 17-JAN-11:55 110.85 08-JAN-07:00
February 1169.53 01-FEB-00:10 597.59 01-FEB-20:10 685.60 01-FEB-20:10 0.00 0.00 0.00 0.00 10.28 01-FEB-12:00 88.64 04-FEB-05:55
March 1169.53 01-MAR-00:10 597.59 01-MAR-20:10 685.60 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 94.87 08-MAR-04:00
April 1169.53 01-APR-00:10 597.59 03-APR-19:10 685.60 03-APR-19:10 0.00 0.00 0.00 0.00 18.69 30-APR-10:55 76.90 01-APR-06:00
May 1169.53 01-MAY-00:10 597.59 01-MAY-19:10 685.60 01-MAY-19:10 0.00 0.00 0.00 0.00 5.20 03-MAY-12:00 71.56 15-MAY-02:00
June 1169.53 01-JUN-00:10 597.59 01-JUN-19:10 685.60 01-JUN-19:10 0.00 0.00 0.00 0.00 15.50 29-JUN-10:55 54.53 13-JUN-04:30
July 1169.53 01-JUL-00:10 597.59 03-JUL-19:10 685.60 03-JUL-19:10 0.00 0.00 0.00 0.00 28.90 19-JUL-10:55 46.45 06-JUL-01:00
August 1169.53 01-AUG-00:10 597.59 01-AUG-19:10 685.60 01-AUG-19:10 0.00 0.00 0.00 0.00 26.31 14-AUG-10:55 42.33 28-AUG-03:00
September 1169.53 01-SEP-00:10 597.59 01-SEP-19:10 685.60 01-SEP-19:10 0.00 0.00 0.00 0.00 59.71 29-SEP-11:00 56.31 20-SEP-03:00
October 1169.53 01-OCT-23:10 597.59 02-OCT-19:10 685.60 02-OCT-19:10 0.00 0.00 0.00 0.00 64.60 16-OCT-11:00 68.36 30-OCT-03:00
November 1169.53 01-NOV-00:10 597.59 01-NOV-19:10 685.60 01-NOV-19:10 0.00 0.00 0.00 0.00 15.39 19-NOV-13:00 82.98 29-NOV-23:00
December 1169.53 01-DEC-00:10 597.59 01-DEC-20:10 685.60 01-DEC-20:10 0.00 0.00 0.00 0.00 10.36 16-DEC-13:00 88.86 22-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1169.53   597.59   685.60   0.00 0.00 0.00 0.00 0.00   42.33  
Maximum of Months 1169.53   597.59   685.60   0.00 0.00 0.00 0.00 64.60   110.85  



Table of Contents

Report: PeakSpaceGainsMonthly

For: RETAIL_2_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1354.32 02-JAN-00:10 692.02 02-JAN-20:10 793.93 02-JAN-20:10 0.00 0.00 0.00 0.00 7.28 13-JAN-14:00 43.57 08-JAN-07:00
February 1354.32 01-FEB-00:10 692.02 01-FEB-20:10 793.93 01-FEB-20:10 0.00 0.00 0.00 0.00 7.13 01-FEB-11:55 37.22 04-FEB-05:55
March 1354.32 01-MAR-00:10 692.02 01-MAR-20:10 793.93 01-MAR-20:10 0.00 0.00 0.00 0.00 3.47 11-MAR-11:50 37.71 08-MAR-02:00
April 1354.32 01-APR-00:10 692.02 03-APR-19:10 793.93 03-APR-19:10 0.00 0.00 0.00 0.00 8.93 26-APR-13:00 30.91 01-APR-06:00
May 1354.32 01-MAY-00:10 692.02 01-MAY-19:10 793.93 01-MAY-19:10 0.00 0.00 0.00 0.00 3.16 03-MAY-12:00 31.29 19-MAY-05:00
June 1354.32 01-JUN-00:10 692.02 01-JUN-19:10 793.93 01-JUN-19:10 0.00 0.00 0.00 0.00 5.33 29-JUN-10:55 25.13 13-JUN-05:00
July 1354.32 01-JUL-00:10 692.02 03-JUL-19:10 793.93 03-JUL-19:10 0.00 0.00 0.00 0.00 11.04 19-JUL-10:55 21.82 06-JUL-01:00
August 1354.32 01-AUG-00:10 692.02 01-AUG-19:10 793.93 01-AUG-19:10 0.00 0.00 0.00 0.00 10.97 14-AUG-10:55 19.61 28-AUG-06:00
September 1354.32 01-SEP-00:10 692.02 01-SEP-19:10 793.93 01-SEP-19:10 0.00 0.00 0.00 0.00 25.35 29-SEP-10:55 25.64 20-SEP-03:00
October 1354.32 01-OCT-23:10 692.02 02-OCT-19:10 793.93 02-OCT-19:10 0.00 0.00 0.00 0.00 26.66 16-OCT-10:55 30.04 27-OCT-04:30
November 1354.32 01-NOV-00:10 692.02 01-NOV-19:10 793.93 01-NOV-19:10 0.00 0.00 0.00 0.00 7.68 19-NOV-13:00 35.56 29-NOV-23:00
December 1354.32 01-DEC-00:10 692.02 01-DEC-20:10 793.93 01-DEC-20:10 0.00 0.00 0.00 0.00 6.92 16-DEC-13:00 36.86 03-DEC-01:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1354.32   692.02   793.93   0.00 0.00 0.00 0.00 3.16   19.61  
Maximum of Months 1354.32   692.02   793.93   0.00 0.00 0.00 0.00 26.66   43.57  



Table of Contents

Report: PeakSpaceGainsMonthly

For: MECH_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 286.42 02-JAN-00:10 684.18 02-JAN-20:10 839.45 02-JAN-20:10 0.00 0.00 0.00 0.00 21.86 13-JAN-14:00 102.99 08-JAN-07:00
February 286.42 01-FEB-00:10 684.18 01-FEB-20:10 839.45 01-FEB-20:10 0.00 0.00 0.00 0.00 18.96 01-FEB-11:55 85.26 04-FEB-05:55
March 286.42 01-MAR-00:10 684.18 01-MAR-20:10 839.45 01-MAR-20:10 0.00 0.00 0.00 0.00 11.80 11-MAR-11:55 86.54 08-MAR-04:00
April 286.42 01-APR-00:10 684.18 03-APR-19:10 839.45 03-APR-19:10 0.00 0.00 0.00 0.00 22.40 26-APR-13:00 70.14 01-APR-06:00
May 286.42 01-MAY-00:10 684.18 01-MAY-19:10 839.45 01-MAY-19:10 0.00 0.00 0.00 0.00 7.71 03-MAY-12:00 71.38 27-MAY-03:00
June 286.42 01-JUN-00:10 684.18 01-JUN-19:10 839.45 01-JUN-19:10 0.00 0.00 0.00 0.00 11.23 29-JUN-10:55 56.92 13-JUN-04:40
July 286.42 01-JUL-00:10 684.18 03-JUL-19:10 839.45 03-JUL-19:10 0.00 0.00 0.00 0.00 24.40 19-JUL-10:55 49.13 06-JUL-01:00
August 286.42 01-AUG-00:10 684.18 01-AUG-19:10 839.45 01-AUG-19:10 0.00 0.00 0.00 0.00 24.97 14-AUG-10:55 43.74 28-AUG-06:50
September 286.42 01-SEP-00:10 684.18 01-SEP-19:10 839.45 01-SEP-19:10 0.00 0.00 0.00 0.00 60.47 29-SEP-10:55 56.93 20-SEP-03:00
October 286.42 01-OCT-23:10 684.18 02-OCT-19:10 839.45 02-OCT-19:10 0.00 0.00 0.00 0.00 63.09 16-OCT-10:55 67.77 12-OCT-06:00
November 286.42 01-NOV-00:10 684.18 01-NOV-19:10 839.45 01-NOV-19:10 0.00 0.00 0.00 0.00 21.55 19-NOV-13:00 79.37 29-NOV-23:00
December 286.42 01-DEC-00:10 684.18 01-DEC-20:10 839.45 01-DEC-20:10 0.00 0.00 0.00 0.00 20.95 16-DEC-13:00 84.97 03-DEC-01:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 286.42   684.18   839.45   0.00 0.00 0.00 0.00 7.71   43.74  
Maximum of Months 286.42   684.18   839.45   0.00 0.00 0.00 0.00 63.09   102.99  



Table of Contents

Report: PeakSpaceGainsMonthly

For: STORAGE_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 220.32 02-JAN-00:10 251.84 02-JAN-20:10 242.16 02-JAN-20:10 0.00 0.00 0.00 0.00 12.58 13-JAN-14:00 59.42 08-JAN-07:00
February 220.32 01-FEB-00:10 251.84 01-FEB-20:10 242.16 01-FEB-20:10 0.00 0.00 0.00 0.00 11.09 01-FEB-11:55 48.49 04-FEB-05:55
March 220.32 01-MAR-00:10 251.84 01-MAR-20:10 242.16 01-MAR-20:10 0.00 0.00 0.00 0.00 6.86 11-MAR-11:50 49.93 08-MAR-04:00
April 220.32 01-APR-00:10 251.84 03-APR-19:10 242.16 03-APR-19:10 0.00 0.00 0.00 0.00 13.08 26-APR-13:00 40.47 01-APR-06:00
May 220.32 01-MAY-00:10 251.84 01-MAY-19:10 242.16 01-MAY-19:10 0.00 0.00 0.00 0.00 4.71 03-MAY-12:00 40.37 27-MAY-03:00
June 220.32 01-JUN-00:10 251.84 01-JUN-19:10 242.16 01-JUN-19:10 0.00 0.00 0.00 0.00 6.83 29-JUN-10:55 32.15 13-JUN-05:00
July 220.32 01-JUL-00:10 251.84 03-JUL-19:10 242.16 03-JUL-19:10 0.00 0.00 0.00 0.00 14.36 19-JUL-10:55 27.55 06-JUL-01:00
August 220.32 01-AUG-00:10 251.84 01-AUG-19:10 242.16 01-AUG-19:10 0.00 0.00 0.00 0.00 14.66 14-AUG-10:55 24.32 28-AUG-07:00
September 220.32 01-SEP-00:10 251.84 01-SEP-19:10 242.16 01-SEP-19:10 0.00 0.00 0.00 0.00 34.87 29-SEP-10:55 32.16 20-SEP-03:00
October 220.32 01-OCT-23:10 251.84 02-OCT-19:10 242.16 02-OCT-19:10 0.00 0.00 0.00 0.00 36.41 16-OCT-10:55 38.21 27-OCT-04:05
November 220.32 01-NOV-00:10 251.84 01-NOV-19:10 242.16 01-NOV-19:10 0.00 0.00 0.00 0.00 12.52 19-NOV-13:00 44.48 29-NOV-23:00
December 220.32 01-DEC-00:10 251.84 01-DEC-20:10 242.16 01-DEC-20:10 0.00 0.00 0.00 0.00 12.11 16-DEC-13:00 48.02 03-DEC-01:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 220.32   251.84   242.16   0.00 0.00 0.00 0.00 4.71   24.32  
Maximum of Months 220.32   251.84   242.16   0.00 0.00 0.00 0.00 36.41   59.42  



Table of Contents

Report: PeakSpaceGainsMonthly

For: LAUNDRY_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 907.20 02-JAN-00:10 325.08 02-JAN-20:10 4572.80 02-JAN-20:10 39726.58 02-JAN-20:10 0.00 0.00 0.00 30.52 14-JAN-11:50 135.36 08-JAN-07:00
February 907.20 01-FEB-00:10 325.08 01-FEB-20:10 4572.80 01-FEB-20:10 39726.58 01-FEB-20:10 0.00 0.00 0.00 27.37 01-FEB-11:55 116.36 06-FEB-23:00
March 907.20 01-MAR-00:10 325.08 01-MAR-20:10 4572.80 01-MAR-20:10 39726.58 01-MAR-20:10 0.00 0.00 0.00 17.95 11-MAR-11:50 124.94 29-MAR-22:00
April 907.20 01-APR-00:10 325.08 03-APR-19:10 4572.80 03-APR-19:10 39726.58 03-APR-19:10 0.00 0.00 0.00 29.77 26-APR-13:00 102.04 15-APR-22:00
May 907.20 01-MAY-00:10 325.08 01-MAY-19:10 4572.80 01-MAY-19:10 39726.58 01-MAY-19:10 0.00 0.00 0.00 12.75 04-MAY-12:00 99.60 15-MAY-05:08
June 907.20 01-JUN-00:10 325.08 01-JUN-19:10 4572.80 01-JUN-19:10 39726.58 01-JUN-19:10 0.00 0.00 0.00 23.66 29-JUN-10:50 84.12 13-JUN-05:10
July 907.20 01-JUL-00:10 325.08 03-JUL-19:10 4572.80 03-JUL-19:10 39726.58 03-JUL-19:10 0.00 0.00 0.00 42.72 19-JUL-10:50 65.37 08-JUL-24:00
August 907.20 01-AUG-00:10 325.08 01-AUG-19:10 4572.80 01-AUG-19:10 39726.58 01-AUG-19:10 0.00 0.00 0.00 42.78 14-AUG-10:50 66.51 28-AUG-07:00
September 907.20 01-SEP-00:10 325.08 01-SEP-19:10 4572.80 01-SEP-19:10 39726.58 01-SEP-19:10 0.00 0.00 0.00 91.74 29-SEP-10:50 80.65 20-SEP-06:00
October 907.20 01-OCT-23:10 325.08 02-OCT-19:10 4572.80 02-OCT-19:10 39726.58 02-OCT-19:10 0.00 0.00 0.00 96.26 16-OCT-10:50 101.94 12-OCT-06:00
November 907.20 01-NOV-00:10 325.08 01-NOV-19:10 4572.80 01-NOV-19:10 39726.58 01-NOV-19:10 0.00 0.00 0.00 29.69 19-NOV-13:10 116.82 23-NOV-22:00
December 907.20 01-DEC-00:10 325.08 01-DEC-20:10 4572.80 01-DEC-20:10 39726.58 01-DEC-20:10 0.00 0.00 0.00 26.05 16-DEC-13:00 123.85 12-DEC-22:00
                               
Annual Sum or Average                 0.00 0.00 0.00        
Minimum of Months 907.20   325.08   4572.80   39726.58   0.00 0.00 0.00 12.75   65.37  
Maximum of Months 907.20   325.08   4572.80   39726.58   0.00 0.00 0.00 96.26   135.36  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CAFE_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 15368.40 02-JAN-00:10 1701.53 02-JAN-20:10 965.27 02-JAN-20:10 0.00 0.00 0.00 0.00 28.13 17-JAN-11:55 249.58 08-JAN-07:00
February 15368.40 01-FEB-00:10 1701.53 01-FEB-20:10 965.27 01-FEB-20:10 0.00 0.00 0.00 0.00 22.74 01-FEB-12:00 212.50 04-FEB-05:55
March 15368.40 01-MAR-00:10 1701.53 01-MAR-20:10 965.27 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 213.71 08-MAR-02:00
April 15368.40 01-APR-00:10 1701.53 03-APR-19:10 965.27 03-APR-19:10 0.00 0.00 0.00 0.00 43.71 26-APR-13:00 174.94 04-APR-04:05
May 15368.40 01-MAY-00:10 1701.53 01-MAY-19:10 965.27 01-MAY-19:10 0.00 0.00 0.00 0.00 14.14 03-MAY-12:00 179.30 19-MAY-05:00
June 15368.40 01-JUN-00:10 1701.53 01-JUN-19:10 965.27 01-JUN-19:10 0.00 0.00 0.00 0.00 36.85 29-JUN-10:55 148.35 13-JUN-05:00
July 15368.40 01-JUL-00:10 1701.53 03-JUL-19:10 965.27 03-JUL-19:10 0.00 0.00 0.00 0.00 67.17 19-JUL-10:55 126.32 06-JUL-01:00
August 15368.40 01-AUG-00:10 1701.53 01-AUG-19:10 965.27 01-AUG-19:10 0.00 0.00 0.00 0.00 62.15 14-AUG-10:55 116.57 28-AUG-03:00
September 15368.40 01-SEP-00:10 1701.53 01-SEP-19:10 965.27 01-SEP-19:10 0.00 0.00 0.00 0.00 132.00 29-SEP-10:55 150.74 20-SEP-03:00
October 15368.40 01-OCT-23:10 1701.53 02-OCT-19:10 965.27 02-OCT-19:10 0.00 0.00 0.00 0.00 142.81 16-OCT-10:55 177.49 30-OCT-03:00
November 15368.40 01-NOV-00:10 1701.53 01-NOV-19:10 965.27 01-NOV-19:10 0.00 0.00 0.00 0.00 34.02 19-NOV-13:00 202.32 29-NOV-23:00
December 15368.40 01-DEC-00:10 1701.53 01-DEC-20:10 965.27 01-DEC-20:10 0.00 0.00 0.00 0.00 22.91 16-DEC-13:00 209.24 23-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 15368.40   1701.53   965.27   0.00 0.00 0.00 0.00 0.00   116.57  
Maximum of Months 15368.40   1701.53   965.27   0.00 0.00 0.00 0.00 142.81   249.58  



Table of Contents

Report: PeakSpaceGainsMonthly

For: LOBBY_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 45622.98 02-JAN-00:10 9504.80 02-JAN-20:10 10029.21 02-JAN-20:10 0.00 0.00 0.00 0.00 102.46 13-JAN-14:00 712.96 08-JAN-07:00
February 45622.98 01-FEB-00:10 9504.80 01-FEB-20:10 10029.21 01-FEB-20:10 0.00 0.00 0.00 0.00 102.65 01-FEB-11:55 626.09 04-FEB-05:55
March 45622.98 01-MAR-00:10 9504.80 01-MAR-20:10 10029.21 01-MAR-20:10 0.00 0.00 0.00 0.00 41.74 11-MAR-11:50 631.70 08-MAR-02:00
April 45622.98 01-APR-00:10 9504.80 03-APR-19:10 10029.21 03-APR-19:10 0.00 0.00 0.00 0.00 144.64 26-APR-13:00 524.73 01-APR-06:00
May 45622.98 01-MAY-00:10 9504.80 01-MAY-19:10 10029.21 01-MAY-19:10 0.00 0.00 0.00 0.00 50.34 03-MAY-12:00 529.91 19-MAY-05:00
June 45622.98 01-JUN-00:10 9504.80 01-JUN-19:10 10029.21 01-JUN-19:10 0.00 0.00 0.00 0.00 92.23 29-JUN-10:55 435.84 13-JUN-05:00
July 45622.98 01-JUL-00:10 9504.80 03-JUL-19:10 10029.21 03-JUL-19:10 0.00 0.00 0.00 0.00 184.95 19-JUL-10:55 370.33 06-JUL-01:00
August 45622.98 01-AUG-00:10 9504.80 01-AUG-19:10 10029.21 01-AUG-19:10 0.00 0.00 0.00 0.00 182.13 14-AUG-10:55 336.15 28-AUG-05:00
September 45622.98 01-SEP-00:10 9504.80 01-SEP-19:10 10029.21 01-SEP-19:10 0.00 0.00 0.00 0.00 410.03 29-SEP-10:55 437.01 20-SEP-03:00
October 45622.98 01-OCT-23:10 9504.80 02-OCT-19:10 10029.21 02-OCT-19:10 0.00 0.00 0.00 0.00 429.33 16-OCT-10:55 511.52 27-OCT-04:30
November 45622.98 01-NOV-00:10 9504.80 01-NOV-19:10 10029.21 01-NOV-19:10 0.00 0.00 0.00 0.00 106.92 19-NOV-13:00 590.05 29-NOV-23:00
December 45622.98 01-DEC-00:10 9504.80 01-DEC-20:10 10029.21 01-DEC-20:10 0.00 0.00 0.00 0.00 89.84 16-DEC-13:00 613.32 23-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 45622.98   9504.80   10029.21   0.00 0.00 0.00 0.00 41.74   336.15  
Maximum of Months 45622.98   9504.80   10029.21   0.00 0.00 0.00 0.00 429.33   712.96  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_1_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 177.88 01-JAN-19:10 237.06 01-JAN-08:09 0.00 0.00 0.00 0.00 14.55 14-JAN-11:00 66.02 08-JAN-07:00
February 180.00 01-FEB-00:10 177.88 01-FEB-20:10 237.06 01-FEB-07:10 0.00 0.00 0.00 0.00 8.56 01-FEB-09:51 51.94 04-FEB-05:55
March 180.00 01-MAR-00:10 177.88 01-MAR-20:10 237.06 01-MAR-07:10 0.00 0.00 0.00 0.00 8.56 11-MAR-11:00 55.55 08-MAR-02:00
April 180.00 01-APR-00:10 177.88 01-APR-18:10 237.06 01-APR-07:10 0.00 0.00 0.00 0.00 11.57 30-APR-10:00 45.11 01-APR-06:00
May 180.00 01-MAY-00:10 177.88 01-MAY-19:10 237.06 01-MAY-06:10 0.00 0.00 0.00 0.00 5.59 03-MAY-10:00 42.01 15-MAY-02:00
June 180.00 01-JUN-00:10 177.88 01-JUN-19:10 237.06 01-JUN-06:10 0.00 0.00 0.00 0.00 8.56 30-JUN-10:00 32.13 13-JUN-04:10
July 180.00 01-JUL-00:10 177.88 01-JUL-18:10 237.06 01-JUL-07:10 0.00 0.00 0.00 0.00 17.41 19-JUL-10:00 25.46 06-JUL-01:00
August 180.00 01-AUG-00:10 177.88 01-AUG-19:10 237.06 01-AUG-06:10 0.00 0.00 0.00 0.00 17.42 15-AUG-10:00 24.61 28-AUG-07:20
September 180.00 01-SEP-00:10 177.88 01-SEP-19:10 237.06 01-SEP-06:10 0.00 0.00 0.00 0.00 40.11 29-SEP-10:00 31.90 20-SEP-03:10
October 180.00 01-OCT-00:10 177.88 01-OCT-18:10 237.06 01-OCT-07:10 0.00 0.00 0.00 0.00 40.19 16-OCT-10:00 38.63 30-OCT-04:00
November 180.00 01-NOV-00:10 177.88 01-NOV-19:10 237.06 01-NOV-06:10 0.00 0.00 0.00 0.00 14.52 19-NOV-09:55 45.32 24-NOV-00:55
December 180.00 01-DEC-00:10 177.88 01-DEC-20:10 237.06 01-DEC-07:10 0.00 0.00 0.00 0.00 14.54 05-DEC-10:00 52.06 22-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   177.88   237.06   0.00 0.00 0.00 0.00 5.59   24.61  
Maximum of Months 180.00   177.88   237.06   0.00 0.00 0.00 0.00 40.19   66.02  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_2_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 177.86 01-JAN-19:10 237.03 01-JAN-08:09 0.00 0.00 0.00 0.00 14.55 14-JAN-11:00 66.02 08-JAN-07:00
February 180.00 01-FEB-00:10 177.86 01-FEB-20:10 237.03 01-FEB-07:10 0.00 0.00 0.00 0.00 9.99 01-FEB-11:55 51.93 04-FEB-05:55
March 180.00 01-MAR-00:10 177.86 01-MAR-20:10 237.03 01-MAR-07:10 0.00 0.00 0.00 0.00 8.56 11-MAR-11:00 55.55 08-MAR-04:00
April 180.00 01-APR-00:10 177.86 01-APR-18:10 237.03 01-APR-07:10 0.00 0.00 0.00 0.00 11.57 30-APR-10:00 45.11 01-APR-06:00
May 180.00 01-MAY-00:10 177.86 01-MAY-19:10 237.03 01-MAY-06:10 0.00 0.00 0.00 0.00 5.59 03-MAY-10:00 42.01 15-MAY-02:00
June 180.00 01-JUN-00:10 177.86 01-JUN-19:10 237.03 01-JUN-06:10 0.00 0.00 0.00 0.00 8.56 30-JUN-10:00 32.12 13-JUN-04:10
July 180.00 01-JUL-00:10 177.86 01-JUL-18:10 237.03 01-JUL-07:10 0.00 0.00 0.00 0.00 17.41 19-JUL-10:00 29.65 07-JUL-21:00
August 180.00 01-AUG-00:10 177.86 01-AUG-19:10 237.03 01-AUG-06:10 0.00 0.00 0.00 0.00 17.42 15-AUG-10:00 28.79 26-AUG-18:00
September 180.00 01-SEP-00:10 177.86 01-SEP-19:10 237.03 01-SEP-06:10 0.00 0.00 0.00 0.00 40.11 29-SEP-10:00 31.90 20-SEP-03:10
October 180.00 01-OCT-00:10 177.86 01-OCT-18:10 237.03 01-OCT-07:10 0.00 0.00 0.00 0.00 40.38 16-OCT-10:01 38.63 30-OCT-04:00
November 180.00 01-NOV-00:10 177.86 01-NOV-19:10 237.03 01-NOV-06:10 0.00 0.00 0.00 0.00 14.52 19-NOV-09:58 45.32 24-NOV-00:55
December 180.00 01-DEC-00:10 177.86 01-DEC-20:10 237.03 01-DEC-07:10 0.00 0.00 0.00 0.00 14.54 05-DEC-10:00 52.06 22-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   177.86   237.03   0.00 0.00 0.00 0.00 5.59   28.79  
Maximum of Months 180.00   177.86   237.03   0.00 0.00 0.00 0.00 40.38   66.02  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 01-JAN-00:10 111.79 01-JAN-19:10 232.19 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 22.81 08-JAN-07:00
February 0.00 01-FEB-00:10 111.79 01-FEB-20:10 232.19 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 19.09 04-FEB-05:55
March 0.00 01-MAR-00:10 111.79 01-MAR-20:10 232.19 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 19.88 08-MAR-02:00
April 0.00 01-APR-00:10 111.79 01-APR-18:10 232.19 01-APR-07:10 0.00 0.00 0.00 0.00 0.24 26-APR-13:00 15.75 01-APR-06:00
May 0.00 01-MAY-00:10 111.79 01-MAY-19:10 232.19 01-MAY-06:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:05 15.90 15-MAY-02:00
June 0.00 01-JUN-00:10 111.79 01-JUN-19:10 232.19 01-JUN-06:10 0.00 0.00 0.00 0.00 0.00 01-JUN-00:05 13.31 13-JUN-04:20
July 0.00 01-JUL-00:10 111.79 01-JUL-18:10 232.19 01-JUL-07:10 0.00 0.00 0.00 0.00 1.07 19-JUL-12:00 11.87 06-JUL-01:00
August 0.00 01-AUG-00:10 111.79 01-AUG-19:10 232.19 01-AUG-06:10 0.00 0.00 0.00 0.00 1.07 18-AUG-12:00 11.02 24-AUG-02:00
September 0.00 01-SEP-00:10 111.79 01-SEP-19:10 232.19 01-SEP-06:10 0.00 0.00 0.00 0.00 7.49 29-SEP-11:00 13.66 20-SEP-03:00
October 0.00 01-OCT-00:10 111.79 01-OCT-18:10 232.19 01-OCT-07:10 0.00 0.00 0.00 0.00 8.28 16-OCT-10:55 15.69 12-OCT-06:00
November 0.00 01-NOV-00:10 111.79 01-NOV-19:10 232.19 01-NOV-06:10 0.00 0.00 0.00 0.00 0.24 19-NOV-13:00 17.61 24-NOV-01:00
December 0.00 01-DEC-00:10 111.79 01-DEC-20:10 232.19 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 19.52 22-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 0.00   111.79   232.19   0.00 0.00 0.00 0.00 0.00   11.02  
Maximum of Months 0.00   111.79   232.19   0.00 0.00 0.00 0.00 8.28   22.81  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 111.82 01-JAN-19:10 232.26 01-JAN-08:09 0.00 0.00 0.00 0.00 4.06 14-JAN-11:00 18.42 08-JAN-07:00
February 180.00 01-FEB-00:10 111.82 01-FEB-20:10 232.26 01-FEB-07:10 0.00 0.00 0.00 0.00 3.09 01-FEB-11:55 14.49 04-FEB-05:55
March 180.00 01-MAR-00:10 111.82 01-MAR-20:10 232.26 01-MAR-07:10 0.00 0.00 0.00 0.00 2.39 11-MAR-11:00 15.50 08-MAR-02:00
April 180.00 01-APR-00:10 111.82 01-APR-18:10 232.26 01-APR-07:10 0.00 0.00 0.00 0.00 3.87 26-APR-13:00 12.59 01-APR-06:00
May 180.00 01-MAY-00:10 111.82 01-MAY-19:10 232.26 01-MAY-06:10 0.00 0.00 0.00 0.00 1.56 03-MAY-10:00 11.78 14-MAY-05:00
June 180.00 01-JUN-00:10 111.82 01-JUN-19:10 232.26 01-JUN-06:10 0.00 0.00 0.00 0.00 2.39 30-JUN-10:00 8.97 13-JUN-04:10
July 180.00 01-JUL-00:10 111.82 01-JUL-18:10 232.26 01-JUL-07:10 0.00 0.00 0.00 0.00 4.86 19-JUL-10:00 7.89 07-JUL-21:00
August 180.00 01-AUG-00:10 111.82 01-AUG-19:10 232.26 01-AUG-06:10 0.00 0.00 0.00 0.00 4.86 15-AUG-10:00 7.49 21-AUG-20:10
September 180.00 01-SEP-00:10 111.82 01-SEP-19:10 232.26 01-SEP-06:10 0.00 0.00 0.00 0.00 11.20 29-SEP-10:00 8.90 20-SEP-03:10
October 180.00 01-OCT-00:10 111.82 01-OCT-18:10 232.26 01-OCT-07:10 0.00 0.00 0.00 0.00 11.35 16-OCT-10:01 10.78 30-OCT-04:00
November 180.00 01-NOV-00:10 111.82 01-NOV-19:10 232.26 01-NOV-06:10 0.00 0.00 0.00 0.00 4.05 19-NOV-09:58 12.65 24-NOV-01:00
December 180.00 01-DEC-00:10 111.82 01-DEC-20:10 232.26 01-DEC-07:10 0.00 0.00 0.00 0.00 4.06 05-DEC-10:00 14.53 22-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   111.82   232.26   0.00 0.00 0.00 0.00 1.56   7.49  
Maximum of Months 180.00   111.82   232.26   0.00 0.00 0.00 0.00 11.35   18.42  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_5_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 177.88 01-JAN-19:10 237.06 01-JAN-08:09 0.00 0.00 0.00 0.00 14.55 14-JAN-11:00 66.02 08-JAN-07:00
February 180.00 01-FEB-00:10 177.88 01-FEB-20:10 237.06 01-FEB-07:10 0.00 0.00 0.00 0.00 8.56 01-FEB-10:00 51.94 04-FEB-05:55
March 180.00 01-MAR-00:10 177.88 01-MAR-20:10 237.06 01-MAR-07:10 0.00 0.00 0.00 0.00 8.56 11-MAR-11:00 55.55 08-MAR-04:00
April 180.00 01-APR-00:10 177.88 01-APR-18:10 237.06 01-APR-07:10 0.00 0.00 0.00 0.00 11.57 30-APR-10:00 45.11 01-APR-06:00
May 180.00 01-MAY-00:10 177.88 01-MAY-19:10 237.06 01-MAY-06:10 0.00 0.00 0.00 0.00 5.58 03-MAY-10:00 42.01 15-MAY-05:00
June 180.00 01-JUN-00:10 177.88 01-JUN-19:10 237.06 01-JUN-06:10 0.00 0.00 0.00 0.00 8.56 26-JUN-10:00 32.13 13-JUN-04:10
July 180.00 01-JUL-00:10 177.88 01-JUL-18:10 237.06 01-JUL-07:10 0.00 0.00 0.00 0.00 17.41 19-JUL-10:00 25.46 06-JUL-01:00
August 180.00 01-AUG-00:10 177.88 01-AUG-19:10 237.06 01-AUG-06:10 0.00 0.00 0.00 0.00 17.42 15-AUG-10:00 26.94 28-AUG-07:20
September 180.00 01-SEP-00:10 177.88 01-SEP-19:10 237.06 01-SEP-06:10 0.00 0.00 0.00 0.00 40.11 29-SEP-10:00 31.90 20-SEP-03:10
October 180.00 01-OCT-00:10 177.88 01-OCT-18:10 237.06 01-OCT-07:10 0.00 0.00 0.00 0.00 40.19 16-OCT-10:00 38.63 30-OCT-04:00
November 180.00 01-NOV-00:10 177.88 01-NOV-19:10 237.06 01-NOV-06:10 0.00 0.00 0.00 0.00 14.52 19-NOV-10:00 45.32 24-NOV-00:55
December 180.00 01-DEC-00:10 177.88 01-DEC-20:10 237.06 01-DEC-07:10 0.00 0.00 0.00 0.00 14.54 05-DEC-10:00 52.06 22-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   177.88   237.06   0.00 0.00 0.00 0.00 5.58   25.46  
Maximum of Months 180.00   177.88   237.06   0.00 0.00 0.00 0.00 40.19   66.02  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_6_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 177.86 01-JAN-19:10 237.03 01-JAN-08:09 0.00 0.00 0.00 0.00 14.55 14-JAN-11:00 66.01 08-JAN-07:00
February 180.00 01-FEB-00:10 177.86 01-FEB-20:10 237.03 01-FEB-07:10 0.00 0.00 0.00 0.00 8.56 01-FEB-10:00 51.93 04-FEB-05:55
March 180.00 01-MAR-00:10 177.86 01-MAR-20:10 237.03 01-MAR-07:10 0.00 0.00 0.00 0.00 8.56 11-MAR-11:00 55.55 08-MAR-02:00
April 180.00 01-APR-00:10 177.86 01-APR-18:10 237.03 01-APR-07:10 0.00 0.00 0.00 0.00 11.56 30-APR-10:00 45.11 01-APR-06:00
May 180.00 01-MAY-00:10 177.86 01-MAY-19:10 237.03 01-MAY-06:10 0.00 0.00 0.00 0.00 5.58 03-MAY-10:00 42.01 15-MAY-02:00
June 180.00 01-JUN-00:10 177.86 01-JUN-19:10 237.03 01-JUN-06:10 0.00 0.00 0.00 0.00 8.56 30-JUN-10:00 32.12 13-JUN-04:10
July 180.00 01-JUL-00:10 177.86 01-JUL-18:10 237.03 01-JUL-07:10 0.00 0.00 0.00 0.00 17.41 19-JUL-10:00 26.90 07-JUL-21:00
August 180.00 01-AUG-00:10 177.86 01-AUG-19:10 237.03 01-AUG-06:10 0.00 0.00 0.00 0.00 17.42 15-AUG-10:00 29.10 26-AUG-08:00
September 180.00 01-SEP-00:10 177.86 01-SEP-19:10 237.03 01-SEP-06:10 0.00 0.00 0.00 0.00 40.11 29-SEP-10:00 31.90 20-SEP-03:10
October 180.00 01-OCT-00:10 177.86 01-OCT-18:10 237.03 01-OCT-07:10 0.00 0.00 0.00 0.00 40.19 16-OCT-10:00 38.63 30-OCT-04:00
November 180.00 01-NOV-00:10 177.86 01-NOV-19:10 237.03 01-NOV-06:10 0.00 0.00 0.00 0.00 14.51 19-NOV-10:00 45.32 24-NOV-00:55
December 180.00 01-DEC-00:10 177.86 01-DEC-20:10 237.03 01-DEC-07:10 0.00 0.00 0.00 0.00 14.53 05-DEC-10:00 52.06 22-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   177.86   237.03   0.00 0.00 0.00 0.00 5.58   26.90  
Maximum of Months 180.00   177.86   237.03   0.00 0.00 0.00 0.00 40.19   66.01  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORRIDOR_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2263.36 02-JAN-00:10 1867.32 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 15.22 13-JAN-14:00 79.40 08-JAN-07:00
February 2263.36 01-FEB-00:10 1867.32 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 14.38 01-FEB-11:55 65.52 04-FEB-05:55
March 2263.36 01-MAR-00:10 1867.32 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 7.94 11-MAR-11:50 66.74 08-MAR-02:00
April 2263.36 01-APR-00:10 1867.32 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 17.29 26-APR-13:00 54.13 01-APR-06:00
May 2263.36 01-MAY-00:10 1867.32 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 6.08 03-MAY-12:00 53.92 27-MAY-03:00
June 2263.36 01-JUN-00:10 1867.32 01-JUN-19:10 0.00 0.00 0.00 0.00 0.00 9.47 29-JUN-10:55 42.57 13-JUN-05:00
July 2263.36 01-JUL-00:10 1867.32 03-JUL-19:10 0.00 0.00 0.00 0.00 0.00 19.70 19-JUL-10:55 36.92 06-JUL-01:00
August 2263.36 01-AUG-00:10 1867.32 01-AUG-19:10 0.00 0.00 0.00 0.00 0.00 19.41 14-AUG-10:55 33.04 24-AUG-02:00
September 2263.36 01-SEP-00:10 1867.32 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 46.30 29-SEP-10:55 43.35 20-SEP-03:00
October 2263.36 01-OCT-23:10 1867.32 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 48.40 16-OCT-10:55 51.68 30-OCT-03:00
November 2263.36 01-NOV-00:10 1867.32 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 15.95 19-NOV-13:00 59.58 29-NOV-23:00
December 2263.36 01-DEC-00:10 1867.32 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 14.84 16-DEC-13:00 64.97 03-DEC-01:00
                           
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00        
Minimum of Months 2263.36   1867.32   0.00 0.00 0.00 0.00 0.00 6.08   33.04  
Maximum of Months 2263.36   1867.32   0.00 0.00 0.00 0.00 0.00 48.40   79.40  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_1_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 177.88 01-JAN-19:10 237.06 01-JAN-08:09 0.00 0.00 0.00 0.00 14.38 14-JAN-11:00 66.23 08-JAN-07:00
February 180.00 01-FEB-00:10 177.88 01-FEB-20:10 237.06 01-FEB-07:10 0.00 0.00 0.00 0.00 8.38 01-FEB-09:51 52.14 04-FEB-06:00
March 180.00 01-MAR-00:10 177.88 01-MAR-20:10 237.06 01-MAR-07:10 0.00 0.00 0.00 0.00 8.39 11-MAR-11:00 55.76 08-MAR-04:00
April 180.00 01-APR-00:10 177.88 01-APR-18:10 237.06 01-APR-07:10 0.00 0.00 0.00 0.00 11.39 30-APR-10:00 45.31 01-APR-06:00
May 180.00 01-MAY-00:10 177.88 01-MAY-19:10 237.06 01-MAY-06:10 0.00 0.00 0.00 0.00 5.41 03-MAY-10:00 42.21 15-MAY-05:00
June 180.00 01-JUN-00:10 177.88 01-JUN-19:10 237.06 01-JUN-06:10 0.00 0.00 0.00 0.00 8.39 26-JUN-10:00 32.32 13-JUN-04:10
July 180.00 01-JUL-00:10 177.88 01-JUL-18:10 237.06 01-JUL-07:10 0.00 0.00 0.00 0.00 17.24 19-JUL-10:00 25.65 06-JUL-01:00
August 180.00 01-AUG-00:10 177.88 01-AUG-19:10 237.06 01-AUG-06:10 0.00 0.00 0.00 0.00 17.24 15-AUG-10:00 24.02 28-AUG-07:20
September 180.00 01-SEP-00:10 177.88 01-SEP-19:10 237.06 01-SEP-06:10 0.00 0.00 0.00 0.00 39.95 29-SEP-10:00 32.10 20-SEP-03:10
October 180.00 01-OCT-00:10 177.88 01-OCT-18:10 237.06 01-OCT-07:10 0.00 0.00 0.00 0.00 40.03 16-OCT-10:00 38.83 30-OCT-04:00
November 180.00 01-NOV-00:10 177.88 01-NOV-19:10 237.06 01-NOV-06:10 0.00 0.00 0.00 0.00 14.34 19-NOV-09:53 45.52 24-NOV-00:55
December 180.00 01-DEC-00:10 177.88 01-DEC-20:10 237.06 01-DEC-07:10 0.00 0.00 0.00 0.00 14.37 05-DEC-09:55 52.26 22-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   177.88   237.06   0.00 0.00 0.00 0.00 5.41   24.02  
Maximum of Months 180.00   177.88   237.06   0.00 0.00 0.00 0.00 40.03   66.23  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_2_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 177.86 01-JAN-19:10 237.03 01-JAN-08:09 0.00 0.00 0.00 0.00 14.38 14-JAN-11:00 66.22 08-JAN-07:00
February 180.00 01-FEB-00:10 177.86 01-FEB-20:10 237.03 01-FEB-07:10 0.00 0.00 0.00 0.00 10.04 01-FEB-11:55 52.13 04-FEB-05:55
March 180.00 01-MAR-00:10 177.86 01-MAR-20:10 237.03 01-MAR-07:10 0.00 0.00 0.00 0.00 8.39 11-MAR-11:00 55.75 08-MAR-04:00
April 180.00 01-APR-00:10 177.86 01-APR-18:10 237.03 01-APR-07:10 0.00 0.00 0.00 0.00 11.39 30-APR-10:00 45.31 01-APR-06:00
May 180.00 01-MAY-00:10 177.86 01-MAY-19:10 237.03 01-MAY-06:10 0.00 0.00 0.00 0.00 5.41 03-MAY-10:00 42.20 15-MAY-05:00
June 180.00 01-JUN-00:10 177.86 01-JUN-19:10 237.03 01-JUN-06:10 0.00 0.00 0.00 0.00 8.39 30-JUN-10:00 33.13 02-JUN-20:00
July 180.00 01-JUL-00:10 177.86 01-JUL-18:10 237.03 01-JUL-07:10 0.00 0.00 0.00 0.00 17.24 19-JUL-10:00 31.63 10-JUL-18:01
August 180.00 01-AUG-00:10 177.86 01-AUG-19:10 237.03 01-AUG-06:10 0.00 0.00 0.00 0.00 17.24 15-AUG-10:00 30.76 26-AUG-18:00
September 180.00 01-SEP-00:10 177.86 01-SEP-19:10 237.03 01-SEP-06:10 0.00 0.00 0.00 0.00 39.95 29-SEP-10:00 32.09 20-SEP-03:10
October 180.00 01-OCT-00:10 177.86 01-OCT-18:10 237.03 01-OCT-07:10 0.00 0.00 0.00 0.00 40.18 16-OCT-10:01 38.82 30-OCT-04:00
November 180.00 01-NOV-00:10 177.86 01-NOV-19:10 237.03 01-NOV-06:10 0.00 0.00 0.00 0.00 14.34 19-NOV-10:00 45.52 24-NOV-00:55
December 180.00 01-DEC-00:10 177.86 01-DEC-20:10 237.03 01-DEC-07:10 0.00 0.00 0.00 0.00 14.37 05-DEC-10:00 52.26 22-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   177.86   237.03   0.00 0.00 0.00 0.00 5.41   30.76  
Maximum of Months 180.00   177.86   237.03   0.00 0.00 0.00 0.00 40.18   66.22  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 111.82 01-JAN-19:10 232.26 01-JAN-08:09 0.00 0.00 0.00 0.00 7.36 14-JAN-11:00 33.88 08-JAN-07:00
February 180.00 01-FEB-00:10 111.82 01-FEB-20:10 232.26 01-FEB-07:10 0.00 0.00 0.00 0.00 4.29 01-FEB-09:51 26.68 04-FEB-05:55
March 180.00 01-MAR-00:10 111.82 01-MAR-20:10 232.26 01-MAR-07:10 0.00 0.00 0.00 0.00 4.29 11-MAR-11:00 28.53 08-MAR-02:00
April 180.00 01-APR-00:10 111.82 01-APR-18:10 232.26 01-APR-07:10 0.00 0.00 0.00 0.00 5.83 30-APR-10:00 23.18 01-APR-06:00
May 180.00 01-MAY-00:10 111.82 01-MAY-19:10 232.26 01-MAY-06:10 0.00 0.00 0.00 0.00 2.77 03-MAY-10:00 21.59 15-MAY-05:00
June 180.00 01-JUN-00:10 111.82 01-JUN-19:10 232.26 01-JUN-06:10 0.00 0.00 0.00 0.00 4.29 30-JUN-10:00 16.54 13-JUN-04:10
July 180.00 01-JUL-00:10 111.82 01-JUL-18:10 232.26 01-JUL-07:10 0.00 0.00 0.00 0.00 8.82 19-JUL-10:00 13.12 06-JUL-01:00
August 180.00 01-AUG-00:10 111.82 01-AUG-19:10 232.26 01-AUG-06:10 0.00 0.00 0.00 0.00 8.82 15-AUG-10:00 12.56 28-AUG-07:20
September 180.00 01-SEP-00:10 111.82 01-SEP-19:10 232.26 01-SEP-06:10 0.00 0.00 0.00 0.00 20.44 29-SEP-10:00 16.42 20-SEP-03:10
October 180.00 01-OCT-00:10 111.82 01-OCT-18:10 232.26 01-OCT-07:10 0.00 0.00 0.00 0.00 20.48 16-OCT-10:00 19.86 30-OCT-04:00
November 180.00 01-NOV-00:10 111.82 01-NOV-19:10 232.26 01-NOV-06:10 0.00 0.00 0.00 0.00 6.97 19-NOV-10:30 23.39 30-NOV-02:30
December 180.00 01-DEC-00:10 111.82 01-DEC-20:10 232.26 01-DEC-07:10 0.00 0.00 0.00 0.00 7.35 05-DEC-10:00 26.74 22-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   111.82   232.26   0.00 0.00 0.00 0.00 2.77   12.56  
Maximum of Months 180.00   111.82   232.26   0.00 0.00 0.00 0.00 20.48   33.88  



Table of Contents

Report: PeakSpaceGainsMonthly

For: BANQUET_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 26988.77 02-JAN-00:10 2988.03 02-JAN-20:10 6747.90 01-JAN-07:10 0.00 0.00 0.00 0.00 20.96 13-JAN-14:00 163.18 08-JAN-07:00
February 26988.77 01-FEB-00:10 2988.03 01-FEB-20:10 6747.90 01-FEB-07:10 0.00 0.00 0.00 0.00 22.20 01-FEB-11:55 145.33 04-FEB-05:55
March 26988.77 01-MAR-00:10 2988.03 01-MAR-20:10 6747.90 01-MAR-07:10 0.00 0.00 0.00 0.00 4.83 11-MAR-11:50 149.41 08-MAR-02:00
April 26988.77 01-APR-00:10 2988.03 03-APR-19:10 6747.90 01-APR-06:10 0.00 0.00 0.00 0.00 24.11 26-APR-13:00 130.28 01-APR-06:00
May 26988.77 01-MAY-00:10 2988.03 01-MAY-19:10 6747.90 01-MAY-06:10 0.00 0.00 0.00 0.00 3.20 03-MAY-12:00 125.54 15-MAY-02:00
June 26988.77 01-JUN-00:10 2988.03 01-JUN-19:10 6747.90 01-JUN-06:10 0.00 0.00 0.00 0.00 12.23 29-JUN-10:55 101.21 13-JUN-04:10
July 26988.77 01-JUL-00:10 2988.03 03-JUL-19:10 6747.90 01-JUL-06:10 0.00 0.00 0.00 0.00 33.77 19-JUL-10:55 84.60 06-JUL-01:00
August 26988.77 01-AUG-00:10 2988.03 01-AUG-19:10 6747.90 01-AUG-06:10 0.00 0.00 0.00 0.00 34.22 14-AUG-10:55 76.64 31-AUG-04:00
September 26988.77 01-SEP-00:10 2988.03 01-SEP-19:10 6747.90 01-SEP-06:10 0.00 0.00 0.00 0.00 88.79 29-SEP-10:50 100.51 20-SEP-03:10
October 26988.77 01-OCT-23:10 2988.03 02-OCT-19:10 6747.90 01-OCT-06:10 0.00 0.00 0.00 0.00 95.69 16-OCT-10:55 117.18 30-OCT-04:00
November 26988.77 01-NOV-00:10 2988.03 01-NOV-19:10 6747.90 01-NOV-06:10 0.00 0.00 0.00 0.00 23.37 19-NOV-13:00 133.69 23-NOV-22:00
December 26988.77 01-DEC-00:10 2988.03 01-DEC-20:10 6747.90 01-DEC-07:10 0.00 0.00 0.00 0.00 19.46 19-DEC-13:00 143.37 23-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 26988.77   2988.03   6747.90   0.00 0.00 0.00 0.00 3.20   76.64  
Maximum of Months 26988.77   2988.03   6747.90   0.00 0.00 0.00 0.00 95.69   163.18  



Table of Contents

Report: PeakSpaceGainsMonthly

For: DINING_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 26988.77 02-JAN-00:10 2988.03 02-JAN-20:10 6747.90 01-JAN-07:10 0.00 0.00 0.00 0.00 18.52 13-JAN-14:00 164.17 08-JAN-07:00
February 26988.77 01-FEB-00:10 2988.03 01-FEB-20:10 6747.90 01-FEB-07:10 0.00 0.00 0.00 0.00 19.98 01-FEB-11:55 146.14 04-FEB-05:55
March 26988.77 01-MAR-00:10 2988.03 01-MAR-20:10 6747.90 01-MAR-07:10 0.00 0.00 0.00 0.00 2.75 11-MAR-11:50 150.84 08-MAR-02:00
April 26988.77 01-APR-00:10 2988.03 03-APR-19:10 6747.90 01-APR-06:10 0.00 0.00 0.00 0.00 22.17 26-APR-13:00 131.92 01-APR-06:00
May 26988.77 01-MAY-00:10 2988.03 01-MAY-19:10 6747.90 01-MAY-06:10 0.00 0.00 0.00 0.00 1.39 03-MAY-12:00 125.54 15-MAY-05:00
June 26988.77 01-JUN-00:10 2988.03 01-JUN-19:10 6747.90 01-JUN-06:10 0.00 0.00 0.00 0.00 10.57 29-JUN-10:55 101.21 13-JUN-04:10
July 26988.77 01-JUL-00:10 2988.03 03-JUL-19:10 6747.90 01-JUL-06:10 0.00 0.00 0.00 0.00 32.16 19-JUL-10:55 84.60 06-JUL-01:00
August 26988.77 01-AUG-00:10 2988.03 01-AUG-19:10 6747.90 01-AUG-06:10 0.00 0.00 0.00 0.00 32.64 14-AUG-10:55 76.65 31-AUG-04:00
September 26988.77 01-SEP-00:10 2988.03 01-SEP-19:10 6747.90 01-SEP-06:10 0.00 0.00 0.00 0.00 87.33 29-SEP-10:50 100.51 20-SEP-03:10
October 26988.77 01-OCT-23:10 2988.03 02-OCT-19:10 6747.90 01-OCT-06:10 0.00 0.00 0.00 0.00 94.53 16-OCT-10:55 117.18 30-OCT-04:00
November 26988.77 01-NOV-00:10 2988.03 01-NOV-19:10 6747.90 01-NOV-06:10 0.00 0.00 0.00 0.00 21.76 19-NOV-13:00 133.72 24-NOV-01:00
December 26988.77 01-DEC-00:10 2988.03 01-DEC-20:10 6747.90 01-DEC-07:10 0.00 0.00 0.00 0.00 17.62 19-DEC-13:00 144.62 22-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 26988.77   2988.03   6747.90   0.00 0.00 0.00 0.00 1.39   76.65  
Maximum of Months 26988.77   2988.03   6747.90   0.00 0.00 0.00 0.00 94.53   164.17  



Table of Contents

Report: PeakSpaceGainsMonthly

For: KITCHEN_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2401.70 02-JAN-00:10 1060.81 02-JAN-20:10 14912.86 01-JAN-07:10 22492.83 01-JAN-16:10 0.00 0.00 0.00 12.53 14-JAN-11:00 144.76 03-JAN-07:10
February 2401.70 01-FEB-00:10 1060.81 01-FEB-20:10 14912.86 01-FEB-07:10 22492.83 01-FEB-16:10 0.00 0.00 0.00 12.45 01-FEB-11:55 121.89 09-FEB-07:00
March 2401.70 01-MAR-00:10 1060.81 01-MAR-20:10 14912.86 01-MAR-07:10 22492.83 01-MAR-16:10 0.00 0.00 0.00 0.00 01-MAR-00:03 131.56 29-MAR-22:50
April 2401.70 01-APR-00:10 1060.81 03-APR-19:10 14912.86 01-APR-06:10 22492.83 01-APR-15:09 0.00 0.00 0.00 18.92 26-APR-13:00 119.08 01-APR-06:00
May 2401.70 01-MAY-00:10 1060.81 01-MAY-19:10 14912.86 01-MAY-06:10 22492.83 01-MAY-15:09 0.00 0.00 0.00 0.00 01-MAY-00:05 111.95 19-MAY-05:00
June 2401.70 01-JUN-00:10 1060.81 01-JUN-19:10 14912.86 01-JUN-06:10 22492.83 01-JUN-15:09 0.00 0.00 0.00 5.95 29-JUN-10:55 90.61 13-JUN-04:10
July 2401.70 01-JUL-00:10 1060.81 03-JUL-19:10 14912.86 01-JUL-06:10 22492.83 01-JUL-15:09 0.00 0.00 0.00 25.38 19-JUL-12:00 72.04 06-JUL-01:00
August 2401.70 01-AUG-00:10 1060.81 01-AUG-19:10 14912.86 01-AUG-06:10 22492.83 01-AUG-15:09 0.00 0.00 0.00 25.44 18-AUG-12:00 68.40 28-AUG-06:10
September 2401.70 01-SEP-00:10 1060.81 01-SEP-19:10 14912.86 01-SEP-06:10 22492.83 01-SEP-15:09 0.00 0.00 0.00 75.18 29-SEP-11:20 86.16 20-SEP-03:30
October 2401.70 01-OCT-23:10 1060.81 02-OCT-19:10 14912.86 01-OCT-06:10 22492.83 01-OCT-15:09 0.00 0.00 0.00 81.37 16-OCT-11:00 104.78 12-OCT-06:00
November 2401.70 01-NOV-00:10 1060.81 01-NOV-19:10 14912.86 01-NOV-06:10 22492.83 01-NOV-15:09 0.00 0.00 0.00 18.95 19-NOV-13:00 119.64 23-NOV-22:00
December 2401.70 01-DEC-00:10 1060.81 01-DEC-20:10 14912.86 01-DEC-07:10 22492.83 01-DEC-16:10 0.00 0.00 0.00 12.57 16-DEC-13:00 134.53 22-DEC-07:00
                               
Annual Sum or Average                 0.00 0.00 0.00        
Minimum of Months 2401.70   1060.81   14912.86   22492.83   0.00 0.00 0.00 0.00   68.40  
Maximum of Months 2401.70   1060.81   14912.86   22492.83   0.00 0.00 0.00 81.37   144.76  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORRIDOR_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2395.44 02-JAN-00:10 1976.27 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 23.25 14-JAN-11:00 140.60 08-JAN-07:00
February 2395.44 01-FEB-00:10 1976.27 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 22.61 01-FEB-11:55 111.23 04-FEB-05:55
March 2395.44 01-MAR-00:10 1976.27 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 9.70 11-MAR-11:00 118.53 08-MAR-04:00
April 2395.44 01-APR-00:10 1976.27 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 25.08 26-APR-13:00 96.19 01-APR-06:00
May 2395.44 01-MAY-00:10 1976.27 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 5.97 03-MAY-12:00 92.78 27-MAY-03:00
June 2395.44 01-JUN-00:10 1976.27 01-JUN-19:10 0.00 0.00 0.00 0.00 0.00 13.15 29-JUN-10:55 73.63 13-JUN-04:05
July 2395.44 01-JUL-00:10 1976.27 03-JUL-19:10 0.00 0.00 0.00 0.00 0.00 31.44 19-JUL-10:55 64.07 06-JUL-01:00
August 2395.44 01-AUG-00:10 1976.27 01-AUG-19:10 0.00 0.00 0.00 0.00 0.00 31.16 14-AUG-10:55 57.47 28-AUG-03:00
September 2395.44 01-SEP-00:10 1976.27 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 77.34 29-SEP-10:55 74.05 20-SEP-03:00
October 2395.44 01-OCT-23:10 1976.27 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 81.13 16-OCT-10:55 88.30 30-OCT-03:00
November 2395.44 01-NOV-00:10 1976.27 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 23.86 19-NOV-13:00 103.24 29-NOV-23:00
December 2395.44 01-DEC-00:10 1976.27 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 22.27 16-DEC-13:00 111.08 22-DEC-07:00
                           
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00        
Minimum of Months 2395.44   1976.27   0.00 0.00 0.00 0.00 0.00 5.97   57.47  
Maximum of Months 2395.44   1976.27   0.00 0.00 0.00 0.00 0.00 81.13   140.60  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BASEMENT

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 22096.14 08-JAN-07:00 8945.92 4396.77 4055.80 0.00 0.00 0.00 0.00 0.00 0.00
February 17115.76 04-FEB-05:55 23003.78 2931.30 4055.80 0.00 0.00 0.00 0.00 0.00 0.00
March 17505.81 08-MAR-02:00 11501.89 2198.39 2534.88 0.00 0.00 0.00 0.00 0.00 0.00
April 14895.94 30-APR-10:33 11501.89 13190.31 12167.41 0.00 0.00 0.00 0.00 0.00 0.00
May 14628.35 28-MAY-10:33 11501.89 13190.31 12167.41 0.00 0.00 0.00 0.00 0.00 0.00
June 14788.29 25-JUN-10:33 11501.89 13190.31 12167.41 0.00 0.00 0.00 0.00 0.00 0.00
July 15672.76 23-JUL-10:33 11501.89 13190.31 12167.41 0.00 0.00 0.00 0.00 0.00 0.00
August 15659.67 13-AUG-10:33 11501.89 13190.31 12167.41 0.00 0.00 0.00 0.00 0.00 0.00
September 16160.27 30-SEP-10:33 11501.89 10992.10 10646.48 0.00 0.00 0.00 0.00 0.00 0.00
October 16934.47 20-OCT-21:00 10223.90 11724.66 9125.55 0.00 0.00 0.00 0.00 0.00 0.00
November 17164.12 22-NOV-22:00 10223.90 11724.66 9125.55 0.00 0.00 0.00 0.00 0.00 0.00
December 18090.57 03-DEC-01:00 8945.92 4396.77 4055.80 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 14628.35   8945.92 2198.39 2534.88 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 22096.14   23003.78 13190.31 12167.41 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: RETAIL_1_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3252.13 14-JAN-12:40 389.84 166.00 252.59 0.00 0.00 0.00 0.00 6.88 0.00
February 2915.66 02-FEB-12:40 259.90 166.00 252.59 0.00 0.00 0.00 0.00 0.00 24.59
March 2533.58 11-MAR-13:00 389.84 166.00 252.59 0.00 0.00 0.00 0.00 0.00 0.01
April 2013.49 08-APR-10:33 1169.53 497.99 757.77 0.00 0.00 0.00 0.00 0.00 6.34
May 1951.60 04-MAY-10:33 779.69 497.99 757.77 0.00 0.00 0.00 0.00 0.00 2.96
June 1872.57 25-JUN-10:33 1169.53 597.59 866.03 0.00 0.00 0.00 0.00 5.00 0.00
July 2049.32 30-JUL-10:33 1169.53 597.59 866.03 0.00 0.00 0.00 0.00 9.72 0.00
August 2128.66 27-AUG-10:33 1169.53 597.59 866.03 0.00 0.00 0.00 0.00 0.42 0.00
September 3414.99 30-SEP-13:10 779.69 332.00 505.18 0.00 0.00 0.00 0.00 40.17 0.00
October 4013.08 16-OCT-12:20 259.90 166.00 252.59 0.00 0.00 0.00 0.00 56.73 0.00
November 3608.33 19-NOV-12:30 389.84 199.20 288.68 0.00 0.00 0.00 0.00 12.85 0.00
December 3443.73 19-DEC-12:50 259.90 166.00 252.59 0.00 0.00 0.00 0.00 9.45 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1872.57   259.90 166.00 252.59 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4013.08   1169.53 597.59 866.03 0.00 0.00 0.00 0.00 56.73 24.59



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: RETAIL_2_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1699.75 28-JAN-07:00 1053.36 230.67 334.29 0.00 0.00 0.00 0.00 0.00 39.75
February 1571.06 04-FEB-05:55 2708.64 153.78 334.29 0.00 0.00 0.00 0.00 0.00 37.22
March 1584.46 08-MAR-02:00 1354.32 115.34 208.93 0.00 0.00 0.00 0.00 0.00 37.71
April 1523.18 27-APR-21:00 1203.84 615.12 752.15 0.00 0.00 0.00 0.00 0.00 20.73
May 1526.23 03-MAY-21:00 1203.84 615.12 752.15 0.00 0.00 0.00 0.00 0.00 16.52
June 1573.99 30-JUN-21:00 1203.84 615.12 752.15 0.00 0.00 0.00 0.00 0.00 16.44
July 1672.24 31-JUL-21:00 1203.84 615.12 752.15 0.00 0.00 0.00 0.00 0.00 10.18
August 1738.65 18-AUG-21:00 1203.84 615.12 752.15 0.00 0.00 0.00 0.00 0.00 10.19
September 1926.60 29-SEP-21:00 1203.84 615.12 752.15 0.00 0.00 0.00 0.00 1.19 0.00
October 1981.03 16-OCT-20:10 1203.84 615.12 752.15 0.00 0.00 0.00 0.00 0.00 7.08
November 1558.66 29-NOV-23:00 1354.32 461.34 585.00 0.00 0.00 0.00 0.00 0.00 35.56
December 1558.75 03-DEC-01:00 1053.36 230.67 334.29 0.00 0.00 0.00 0.00 0.00 36.86
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1523.18   1053.36 115.34 208.93 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1981.03   2708.64 615.12 752.15 0.00 0.00 0.00 0.00 1.19 39.75



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: MECH_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1322.24 28-JAN-07:00 222.77 228.06 353.45 0.00 0.00 0.00 0.00 0.00 92.71
February 1183.71 04-FEB-05:55 572.83 152.04 353.45 0.00 0.00 0.00 0.00 0.00 85.26
March 1126.41 08-MAR-01:20 286.42 114.03 220.91 0.00 0.00 0.00 0.00 0.00 83.01
April 1108.41 30-APR-10:33 286.42 684.18 1060.35 0.00 0.00 0.00 0.00 16.01 0.00
May 1124.20 04-MAY-10:33 190.94 570.15 927.81 0.00 0.00 0.00 0.00 0.00 2.44
June 1168.36 25-JUN-10:33 286.42 684.18 1060.35 0.00 0.00 0.00 0.00 1.25 0.00
July 1217.55 23-JUL-10:33 286.42 684.18 1060.35 0.00 0.00 0.00 0.00 12.72 0.00
August 1208.98 19-AUG-10:33 286.42 570.15 927.81 0.00 0.00 0.00 0.00 8.14 0.00
September 1236.64 30-SEP-10:33 286.42 570.15 927.81 0.00 0.00 0.00 0.00 34.02 0.00
October 1229.55 17-OCT-10:33 190.94 570.15 927.81 0.00 0.00 0.00 0.00 35.95 0.00
November 1126.39 29-NOV-23:00 286.42 456.12 618.54 0.00 0.00 0.00 0.00 0.00 79.37
December 1187.86 03-DEC-01:00 222.77 228.06 353.45 0.00 0.00 0.00 0.00 0.00 84.97
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1108.41   190.94 114.03 220.91 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1322.24   572.83 684.18 1060.35 0.00 0.00 0.00 0.00 35.95 92.71



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: STORAGE_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 723.67 27-JAN-04:55 440.64 55.97 101.96 0.00 0.00 0.00 0.00 0.00 50.81
February 678.17 04-FEB-05:55 440.64 55.97 101.96 0.00 0.00 0.00 0.00 0.00 48.49
March 607.69 19-MAR-10:33 220.32 251.83 305.88 0.00 0.00 0.00 0.00 0.00 6.87
April 642.74 30-APR-10:33 220.32 251.83 305.88 0.00 0.00 0.00 0.00 9.54 0.00
May 651.95 04-MAY-10:33 146.88 209.86 267.65 0.00 0.00 0.00 0.00 0.00 1.10
June 675.65 25-JUN-10:33 220.32 251.83 305.88 0.00 0.00 0.00 0.00 1.12 0.00
July 705.58 23-JUL-10:33 220.32 251.83 305.88 0.00 0.00 0.00 0.00 7.69 0.00
August 699.80 19-AUG-10:33 220.32 209.86 267.65 0.00 0.00 0.00 0.00 5.07 0.00
September 720.98 30-SEP-10:33 220.32 209.86 267.65 0.00 0.00 0.00 0.00 19.81 0.00
October 719.17 16-OCT-10:33 146.88 209.86 267.65 0.00 0.00 0.00 0.00 34.60 0.00
November 639.91 19-NOV-11:33 220.32 251.83 305.88 0.00 0.00 0.00 0.00 9.92 0.00
December 673.32 03-DEC-01:00 171.36 83.94 101.96 0.00 0.00 0.00 0.00 0.00 48.02
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 607.69   146.88 55.97 101.96 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 723.67   440.64 251.83 305.88 0.00 0.00 0.00 0.00 34.60 50.81



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: LAUNDRY_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 37557.13 24-JAN-21:00 705.60 325.08 4572.80 39726.58 0.00 0.00 0.00 0.00 46.50
February 37484.34 03-FEB-21:00 705.60 325.08 4572.80 39726.58 0.00 0.00 0.00 0.00 73.97
March 37673.09 23-MAR-20:00 705.60 325.08 4572.80 39726.58 0.00 0.00 0.00 0.00 66.83
April 37921.70 26-APR-20:00 705.60 325.08 4572.80 39726.58 0.00 0.00 0.00 0.00 46.31
May 37942.09 04-MAY-20:00 705.60 325.08 4572.80 39726.58 0.00 0.00 0.00 0.00 46.36
June 37958.08 30-JUN-20:00 705.60 325.08 4572.80 39726.58 0.00 0.00 0.00 0.00 53.06
July 38179.60 19-JUL-20:00 705.60 325.08 4572.80 39726.58 0.00 0.00 0.00 0.00 32.85
August 38141.66 18-AUG-20:00 705.60 325.08 4572.80 39726.58 0.00 0.00 0.00 0.00 32.88
September 38380.00 29-SEP-20:00 705.60 325.08 4572.80 39726.58 0.00 0.00 0.00 6.40 0.00
October 38262.23 16-OCT-20:00 705.60 325.08 4572.80 39726.58 0.00 0.00 0.00 0.00 19.55
November 37486.70 28-NOV-21:00 705.60 325.08 4572.80 39726.58 0.00 0.00 0.00 0.00 74.10
December 37691.77 05-DEC-21:00 705.60 325.08 4572.80 39726.58 0.00 0.00 0.00 0.00 53.31
                       
Annual Sum or Average             0.00 0.00 0.00    
Minimum of Months 37484.34   705.60 325.08 4572.80 39726.58 0.00 0.00 0.00 0.00 0.00
Maximum of Months 38380.00   705.60 325.08 4572.80 39726.58 0.00 0.00 0.00 6.40 74.10



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CAFE_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 12721.45 14-JAN-12:40 5122.80 103.98 355.63 0.00 0.00 0.00 0.00 15.23 0.00
February 10948.50 20-FEB-11:00 8538.00 124.78 406.43 0.00 0.00 0.00 0.00 0.00 93.99
March 10509.78 11-MAR-12:50 5122.80 103.98 355.63 0.00 0.00 0.00 0.00 0.00 0.02
April 9195.35 08-APR-10:33 15368.40 311.95 1066.88 0.00 0.00 0.00 0.00 0.00 17.52
May 8849.59 04-MAY-21:20 15368.40 1134.35 711.25 0.00 0.00 0.00 0.00 0.00 82.18
June 8628.66 25-JUN-10:33 15368.40 374.34 1219.29 0.00 0.00 0.00 0.00 6.87 0.00
July 9217.26 30-JUL-10:33 15368.40 374.34 1219.29 0.00 0.00 0.00 0.00 19.76 0.00
August 9554.66 27-AUG-10:33 15368.40 374.34 1219.29 0.00 0.00 0.00 0.00 0.00 0.62
September 12058.51 30-SEP-12:00 5122.80 103.98 355.63 0.00 0.00 0.00 0.00 88.92 0.00
October 13677.65 15-OCT-12:00 5122.80 124.78 406.43 0.00 0.00 0.00 0.00 89.34 0.00
November 14055.17 19-NOV-11:00 8538.00 124.78 406.43 0.00 0.00 0.00 0.00 22.79 0.00
December 12574.26 16-DEC-13:00 5122.80 103.98 355.63 0.00 0.00 0.00 0.00 22.91 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 8628.66   5122.80 103.98 355.63 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 14055.17   15368.40 1134.35 1219.29 0.00 0.00 0.00 0.00 89.34 93.99



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: LOBBY_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 37648.63 09-JAN-05:55 91245.96 4224.36 6334.24 0.00 0.00 0.00 0.00 0.00 690.92
February 33715.83 04-FEB-05:55 91245.96 2112.18 4222.82 0.00 0.00 0.00 0.00 0.00 626.09
March 33763.26 08-MAR-02:00 45622.98 1584.13 2639.27 0.00 0.00 0.00 0.00 0.00 631.70
April 31533.75 26-APR-21:52 364983.84 50692.26 59119.55 0.00 0.00 0.00 0.00 0.00 269.59
May 32428.36 04-MAY-21:53 319360.86 44355.73 51729.60 0.00 0.00 0.00 0.00 0.00 235.04
June 32339.04 30-JUN-21:52 410606.82 57028.80 66509.49 0.00 0.00 0.00 0.00 0.00 265.64
July 33679.59 19-JUL-21:52 364983.84 50692.26 59119.55 0.00 0.00 0.00 0.00 0.00 200.49
August 34316.62 18-AUG-21:10 45622.98 6336.53 7389.94 0.00 0.00 0.00 0.00 0.00 166.64
September 38050.84 29-SEP-21:10 45622.98 6336.53 7389.94 0.00 0.00 0.00 0.00 18.97 0.00
October 38779.30 16-OCT-21:10 45622.98 6336.53 7389.94 0.00 0.00 0.00 0.00 0.00 188.94
November 33022.84 20-NOV-22:10 45622.98 6336.53 7389.94 0.00 0.00 0.00 0.00 0.00 339.42
December 34111.01 05-DEC-22:10 45622.98 6336.53 7389.94 0.00 0.00 0.00 0.00 0.00 229.90
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 31533.75   45622.98 1584.13 2639.27 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 38779.30   410606.82 57028.80 66509.49 0.00 0.00 0.00 0.00 18.97 690.92



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_1_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3272.60 14-JAN-16:01 378.00 410.91 387.20 0.00 0.00 0.00 0.00 1.40 0.00
February 3284.55 03-FEB-16:01 680.40 348.65 350.32 0.00 0.00 0.00 0.00 0.00 6.42
March 2881.82 05-MAR-16:01 378.00 410.91 387.20 0.00 0.00 0.00 0.00 0.00 24.49
April 3051.25 01-APR-18:02 702.00 1067.29 726.98 0.00 0.00 0.00 0.00 0.00 12.16
May 2995.73 24-MAY-08:62 216.00 469.61 679.57 0.00 0.00 0.00 0.00 0.00 10.86
June 2969.15 28-JUN-18:01 970.20 1108.21 848.14 0.00 0.00 0.00 0.00 0.00 12.23
July 2977.48 27-JUL-18:01 970.20 1108.21 848.14 0.00 0.00 0.00 0.00 0.00 6.16
August 2961.18 17-AUG-18:02 831.60 949.89 726.98 0.00 0.00 0.00 0.00 0.00 5.46
September 2920.29 24-SEP-15:01 378.00 410.91 387.20 0.00 0.00 0.00 0.00 0.00 11.32
October 3317.95 14-OCT-08:61 540.00 996.14 1633.07 0.00 0.00 0.00 0.00 14.80 0.00
November 3245.74 27-NOV-16:01 680.40 348.65 350.32 0.00 0.00 0.00 0.00 0.00 8.72
December 3283.86 19-DEC-16:01 680.40 348.65 350.32 0.00 0.00 0.00 0.00 0.00 5.89
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2881.82   216.00 348.65 350.32 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3317.95   970.20 1108.21 1633.07 0.00 0.00 0.00 0.00 14.80 24.49



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_2_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3136.29 15-JAN-16:01 378.00 410.86 387.15 0.00 0.00 0.00 0.00 0.00 1.92
February 3145.55 03-FEB-16:01 680.40 348.61 350.28 0.00 0.00 0.00 0.00 0.00 6.18
March 2849.82 24-MAR-15:01 680.40 348.61 350.28 0.00 0.00 0.00 0.00 0.00 14.25
April 3120.74 19-APR-18:01 1386.00 1582.97 1211.49 0.00 0.00 0.00 0.00 0.00 32.10
May 3048.38 24-MAY-08:51 360.00 782.59 1132.48 0.00 0.00 0.00 0.00 0.00 12.59
June 2898.64 22-JUN-20:11 1602.00 1582.97 1817.24 0.00 0.00 0.00 0.00 0.00 28.09
July 2806.27 09-JUL-21:51 1247.40 1360.64 805.91 0.00 0.00 0.00 0.00 0.00 20.36
August 2783.67 05-AUG-15:01 378.00 410.86 387.15 0.00 0.00 0.00 0.00 0.08 0.00
September 2859.97 18-SEP-15:01 680.40 348.61 350.28 0.00 0.00 0.00 0.00 0.00 8.68
October 3318.62 14-OCT-08:61 540.00 996.02 1632.88 0.00 0.00 0.00 0.00 13.16 0.00
November 3110.18 27-NOV-16:01 680.40 348.61 350.28 0.00 0.00 0.00 0.00 0.00 8.50
December 3145.30 19-DEC-16:01 680.40 348.61 350.28 0.00 0.00 0.00 0.00 0.00 5.65
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2783.67   360.00 348.61 350.28 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3318.62   1602.00 1582.97 1817.24 0.00 0.00 0.00 0.00 13.16 32.10



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 576.52 14-JAN-12:40 0.00 36.89 33.54 0.00 0.00 0.00 0.00 0.00 1.16
February 506.55 02-FEB-12:30 0.00 31.30 30.96 0.00 0.00 0.00 0.00 0.00 6.14
March 429.68 11-MAR-13:10 0.00 36.89 33.54 0.00 0.00 0.00 0.00 0.00 2.28
April 302.19 08-APR-12:50 0.00 36.89 33.54 0.00 0.00 0.00 0.00 0.00 3.85
May 256.16 03-MAY-15:03 0.00 219.11 343.13 0.00 0.00 0.00 0.00 0.00 4.14
June 222.64 30-JUN-15:06 0.00 219.11 343.13 0.00 0.00 0.00 0.00 0.00 3.17
July 265.41 19-JUL-15:03 0.00 187.81 294.11 0.00 0.00 0.00 0.00 0.00 0.04
August 286.55 30-AUG-13:00 0.00 31.30 30.96 0.00 0.00 0.00 0.00 0.00 2.28
September 533.06 30-SEP-13:05 0.00 73.78 67.08 0.00 0.00 0.00 0.00 4.30 0.00
October 641.98 16-OCT-12:20 0.00 31.30 30.96 0.00 0.00 0.00 0.00 7.00 0.00
November 609.24 19-NOV-09:58 0.00 250.41 639.82 0.00 0.00 0.00 0.00 0.00 0.60
December 588.24 19-DEC-13:00 0.00 31.30 30.96 0.00 0.00 0.00 0.00 0.00 0.60
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 222.64   0.00 31.30 30.96 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 641.98   0.00 250.41 639.82 0.00 0.00 0.00 0.00 7.00 6.14



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1093.77 15-JAN-16:01 378.00 258.31 379.35 0.00 0.00 0.00 0.00 0.00 0.48
February 1060.00 03-FEB-16:01 680.40 219.17 343.22 0.00 0.00 0.00 0.00 0.00 1.30
March 973.56 04-MAR-09:01 378.00 438.35 1119.99 0.00 0.00 0.00 0.00 0.00 7.37
April 1050.39 02-APR-08:51 540.00 626.21 1599.98 0.00 0.00 0.00 0.00 0.00 2.52
May 1055.46 24-MAY-08:51 360.00 492.02 1109.66 0.00 0.00 0.00 0.00 0.00 3.52
June 1025.16 22-JUN-20:11 1602.00 995.22 1780.62 0.00 0.00 0.00 0.00 0.00 7.46
July 1038.95 04-JUL-08:51 540.00 626.21 1599.98 0.00 0.00 0.00 0.00 0.00 0.91
August 1006.39 22-AUG-15:01 680.40 219.17 343.22 0.00 0.00 0.00 0.00 0.00 1.74
September 1007.96 01-SEP-15:01 680.40 219.17 343.22 0.00 0.00 0.00 0.00 0.00 1.87
October 1174.61 14-OCT-08:61 540.00 626.21 1599.98 0.00 0.00 0.00 0.00 3.53 0.00
November 1080.05 19-NOV-09:41 486.00 563.59 1439.98 0.00 0.00 0.00 0.00 2.93 0.00
December 1089.33 05-DEC-16:01 680.40 219.17 343.22 0.00 0.00 0.00 0.00 0.28 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 973.56   360.00 219.17 343.22 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1174.61   1602.00 995.22 1780.62 0.00 0.00 0.00 0.00 3.53 7.46



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_5_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2934.84 14-JAN-16:01 378.00 410.91 387.20 0.00 0.00 0.00 0.00 1.35 0.00
February 2930.11 03-FEB-16:01 680.40 348.65 350.32 0.00 0.00 0.00 0.00 0.00 6.31
March 2599.48 24-MAR-15:01 680.40 348.65 350.32 0.00 0.00 0.00 0.00 0.00 14.21
April 2896.14 02-APR-08:62 324.00 597.68 979.84 0.00 0.00 0.00 0.00 0.00 16.04
May 2904.35 24-MAY-08:62 216.00 469.61 679.57 0.00 0.00 0.00 0.00 0.00 13.99
June 2675.65 26-JUN-15:01 680.40 348.65 350.32 0.00 0.00 0.00 0.00 0.00 1.99
July 2720.74 19-JUL-08:61 252.00 547.88 792.83 0.00 0.00 0.00 0.00 0.00 0.42
August 2725.10 14-AUG-08:61 252.00 547.88 792.83 0.00 0.00 0.00 0.00 1.57 0.00
September 2651.35 04-SEP-15:01 378.00 410.91 387.20 0.00 0.00 0.00 0.00 0.00 5.47
October 3026.42 14-OCT-08:61 540.00 996.14 1633.07 0.00 0.00 0.00 0.00 14.21 0.00
November 2952.51 27-NOV-09:01 252.00 547.88 792.83 0.00 0.00 0.00 0.00 0.00 4.49
December 2972.27 05-DEC-09:01 252.00 547.88 792.83 0.00 0.00 0.00 0.00 4.95 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2599.48   216.00 348.65 350.32 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3026.42   680.40 996.14 1633.07 0.00 0.00 0.00 0.00 14.21 16.04



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_6_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2798.62 14-JAN-16:01 378.00 410.86 387.15 0.00 0.00 0.00 0.00 1.83 0.00
February 2863.66 03-FEB-09:51 252.00 547.81 792.74 0.00 0.00 0.00 0.00 0.00 5.31
March 2767.83 23-MAR-08:51 324.00 704.33 1019.23 0.00 0.00 0.00 0.00 0.00 15.85
April 3108.15 02-APR-08:51 540.00 996.02 1632.88 0.00 0.00 0.00 0.00 0.00 15.28
May 3191.52 24-MAY-08:51 360.00 782.59 1132.48 0.00 0.00 0.00 0.00 0.00 19.91
June 2986.79 23-JUN-08:51 360.00 782.59 1132.48 0.00 0.00 0.00 0.00 0.00 12.34
July 2957.70 04-JUL-08:51 540.00 996.02 1632.88 0.00 0.00 0.00 0.00 0.00 10.31
August 2885.16 22-AUG-08:51 360.00 782.59 1132.48 0.00 0.00 0.00 0.00 0.00 16.67
September 2912.60 12-SEP-08:51 360.00 782.59 1132.48 0.00 0.00 0.00 0.00 0.00 11.85
October 3389.84 17-OCT-08:21 360.00 782.59 1132.48 0.00 0.00 0.00 0.00 6.41 0.00
November 2825.52 28-NOV-09:51 252.00 547.81 792.74 0.00 0.00 0.00 0.00 0.00 4.74
December 3049.44 05-DEC-09:41 324.00 704.33 1019.23 0.00 0.00 0.00 0.00 6.16 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2767.83   252.00 410.86 387.15 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3389.84   540.00 996.02 1632.88 0.00 0.00 0.00 0.00 6.41 19.91



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORRIDOR_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2596.68 28-JAN-07:00 1760.39 622.44 0.00 0.00 0.00 0.00 0.00 0.00 71.38
February 2317.31 04-FEB-05:55 4526.71 414.96 0.00 0.00 0.00 0.00 0.00 0.00 65.52
March 2255.54 08-MAR-01:30 2263.36 311.22 0.00 0.00 0.00 0.00 0.00 0.00 64.75
April 2161.93 30-APR-10:33 2263.36 1867.32 0.00 0.00 0.00 0.00 0.00 12.47 0.00
May 2168.59 04-MAY-10:33 1508.90 1556.10 0.00 0.00 0.00 0.00 0.00 0.00 1.36
June 2231.77 25-JUN-10:33 2263.36 1867.32 0.00 0.00 0.00 0.00 0.00 1.86 0.00
July 2325.59 23-JUL-10:33 2263.36 1867.32 0.00 0.00 0.00 0.00 0.00 10.72 0.00
August 2343.00 19-AUG-10:33 2263.36 1556.10 0.00 0.00 0.00 0.00 0.00 6.66 0.00
September 2397.46 30-SEP-10:33 2263.36 1556.10 0.00 0.00 0.00 0.00 0.00 26.57 0.00
October 2413.39 17-OCT-10:33 1508.90 1556.10 0.00 0.00 0.00 0.00 0.00 27.60 0.00
November 2173.64 19-NOV-11:33 2263.36 1867.32 0.00 0.00 0.00 0.00 0.00 12.65 0.00
December 2304.75 03-DEC-01:00 1760.39 622.44 0.00 0.00 0.00 0.00 0.00 0.00 64.97
                       
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00    
Minimum of Months 2161.93   1508.90 311.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2596.68   4526.71 1867.32 0.00 0.00 0.00 0.00 0.00 27.60 71.38



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_1_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3387.17 14-JAN-16:01 378.00 410.91 387.20 0.00 0.00 0.00 0.00 1.18 0.00
February 3393.45 03-FEB-16:01 680.40 348.65 350.32 0.00 0.00 0.00 0.00 0.00 6.59
March 3008.17 05-MAR-16:01 378.00 410.91 387.20 0.00 0.00 0.00 0.00 0.00 24.59
April 3177.96 01-APR-18:02 702.00 1067.29 726.98 0.00 0.00 0.00 0.00 0.00 12.70
May 3064.29 24-MAY-08:62 216.00 469.61 679.57 0.00 0.00 0.00 0.00 0.00 10.62
June 3060.42 28-JUN-18:01 970.20 1108.21 848.14 0.00 0.00 0.00 0.00 0.00 12.42
July 3072.92 27-JUL-18:01 970.20 1108.21 848.14 0.00 0.00 0.00 0.00 0.00 6.34
August 3044.75 14-AUG-18:02 831.60 949.89 726.98 0.00 0.00 0.00 0.00 0.00 2.45
September 2997.62 04-SEP-18:01 819.00 1245.18 848.14 0.00 0.00 0.00 0.00 0.00 17.53
October 3427.03 26-OCT-15:01 680.40 348.65 350.32 0.00 0.00 0.00 0.00 0.00 0.20
November 3350.65 30-NOV-16:01 680.40 348.65 350.32 0.00 0.00 0.00 0.00 0.00 14.65
December 3397.19 19-DEC-16:01 680.40 348.65 350.32 0.00 0.00 0.00 0.00 0.00 6.09
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2997.62   216.00 348.65 350.32 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3427.03   970.20 1245.18 848.14 0.00 0.00 0.00 0.00 1.18 24.59



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_2_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3231.94 15-JAN-16:01 378.00 410.86 387.15 0.00 0.00 0.00 0.00 0.00 2.07
February 3237.06 03-FEB-16:01 680.40 348.61 350.28 0.00 0.00 0.00 0.00 0.00 6.29
March 3016.92 19-MAR-18:11 1170.00 1778.61 1211.49 0.00 0.00 0.00 0.00 0.00 32.26
April 3319.00 23-APR-18:11 1170.00 1778.61 1211.49 0.00 0.00 0.00 0.00 0.00 31.21
May 3200.97 19-MAY-18:51 1386.00 1582.97 1211.49 0.00 0.00 0.00 0.00 0.00 34.74
June 3079.60 04-JUN-19:31 1053.00 1600.75 1469.59 0.00 0.00 0.00 0.00 0.00 27.81
July 2955.52 08-JUL-21:11 1247.40 1360.64 805.91 0.00 0.00 0.00 0.00 0.00 28.61
August 2863.12 21-AUG-20:11 1441.80 1424.67 1635.51 0.00 0.00 0.00 0.00 0.00 27.26
September 2938.83 18-SEP-15:01 680.40 348.61 350.28 0.00 0.00 0.00 0.00 0.00 8.85
October 3327.92 14-OCT-08:61 540.00 996.02 1632.88 0.00 0.00 0.00 0.00 14.24 0.00
November 3197.71 27-NOV-16:01 680.40 348.61 350.28 0.00 0.00 0.00 0.00 0.00 8.58
December 3240.45 19-DEC-16:01 680.40 348.61 350.28 0.00 0.00 0.00 0.00 0.00 5.79
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2863.12   378.00 348.61 350.28 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3327.92   1441.80 1778.61 1635.51 0.00 0.00 0.00 0.00 14.24 34.74



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1820.47 04-JAN-16:01 680.40 219.17 343.22 0.00 0.00 0.00 0.00 0.00 8.10
February 1841.27 03-FEB-16:01 680.40 219.17 343.22 0.00 0.00 0.00 0.00 0.00 3.61
March 1611.92 24-MAR-18:01 970.20 696.66 830.96 0.00 0.00 0.00 0.00 0.00 15.43
April 1728.66 01-APR-18:02 702.00 670.94 712.25 0.00 0.00 0.00 0.00 0.00 6.84
May 1638.74 24-MAY-08:62 216.00 295.21 665.80 0.00 0.00 0.00 0.00 0.00 5.40
June 1629.28 30-JUN-15:01 680.40 219.17 343.22 0.00 0.00 0.00 0.00 0.30 0.00
July 1659.73 15-JUL-15:01 378.00 258.31 379.35 0.00 0.00 0.00 0.00 0.00 1.39
August 1640.88 02-AUG-15:01 680.40 219.17 343.22 0.00 0.00 0.00 0.00 0.09 0.00
September 1641.45 21-SEP-15:02 583.20 187.86 294.19 0.00 0.00 0.00 0.00 7.57 0.00
October 1856.17 14-OCT-08:61 540.00 626.21 1599.98 0.00 0.00 0.00 0.00 7.29 0.00
November 1827.23 27-NOV-09:01 252.00 344.41 776.76 0.00 0.00 0.00 0.00 0.00 2.44
December 1851.23 29-DEC-16:01 680.40 219.17 343.22 0.00 0.00 0.00 0.00 0.00 2.61
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1611.92   216.00 187.86 294.19 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1856.17   970.20 696.66 1599.98 0.00 0.00 0.00 0.00 7.57 15.43



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BANQUET_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 19647.80 18-JAN-22:10 26988.77 1992.02 6747.90 0.00 0.00 0.00 0.00 0.00 55.07
February 19111.67 01-FEB-23:00 26988.77 1992.02 6747.90 0.00 0.00 0.00 0.00 0.00 84.56
March 19465.74 24-MAR-22:00 26988.77 1992.02 6747.90 0.00 0.00 0.00 0.00 0.00 84.48
April 20358.60 26-APR-21:52 215910.14 15936.16 53983.22 0.00 0.00 0.00 0.00 0.00 61.27
May 20743.09 04-MAY-21:53 188921.38 13944.14 47235.32 0.00 0.00 0.00 0.00 0.00 53.51
June 20975.44 27-JUN-21:52 242898.91 17928.18 60731.12 0.00 0.00 0.00 0.00 0.00 53.43
July 21159.84 19-JUL-21:52 215910.14 15936.16 53983.22 0.00 0.00 0.00 0.00 0.00 45.76
August 21020.01 18-AUG-21:52 242898.91 17928.18 60731.12 0.00 0.00 0.00 0.00 0.00 38.17
September 21449.45 29-SEP-21:10 26988.77 1992.02 6747.90 0.00 0.00 0.00 0.00 3.54 0.00
October 21198.14 16-OCT-21:52 215910.14 15936.16 53983.22 0.00 0.00 0.00 0.00 0.00 30.53
November 19323.51 10-NOV-23:00 26988.77 1992.02 6747.90 0.00 0.00 0.00 0.00 0.00 69.15
December 19757.85 05-DEC-22:54 134943.84 9960.10 33739.51 0.00 0.00 0.00 0.00 0.00 45.98
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 19111.67   26988.77 1992.02 6747.90 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 21449.45   242898.91 17928.18 60731.12 0.00 0.00 0.00 0.00 3.54 84.56



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DINING_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 21302.18 18-JAN-22:10 26988.77 1992.02 6747.90 0.00 0.00 0.00 0.00 0.00 55.08
February 20804.15 01-FEB-22:10 26988.77 1992.02 6747.90 0.00 0.00 0.00 0.00 0.00 84.58
March 21050.45 24-MAR-21:10 26988.77 1992.02 6747.90 0.00 0.00 0.00 0.00 0.00 84.56
April 21881.63 26-APR-21:52 215910.14 15936.16 53983.22 0.00 0.00 0.00 0.00 0.00 61.27
May 22189.92 04-MAY-21:10 26988.77 1992.02 6747.90 0.00 0.00 0.00 0.00 0.00 53.49
June 22393.34 27-JUN-21:52 242898.91 17928.18 60731.12 0.00 0.00 0.00 0.00 0.00 53.43
July 22546.55 19-JUL-21:52 215910.14 15936.16 53983.22 0.00 0.00 0.00 0.00 0.00 45.76
August 22361.93 18-AUG-21:52 242898.91 17928.18 60731.12 0.00 0.00 0.00 0.00 0.00 38.17
September 22812.48 29-SEP-21:10 26988.77 1992.02 6747.90 0.00 0.00 0.00 0.00 3.54 0.00
October 22581.11 04-OCT-21:53 188921.38 13944.14 47235.32 0.00 0.00 0.00 0.00 0.00 23.03
November 20999.41 10-NOV-22:14 134943.84 9960.10 33739.51 0.00 0.00 0.00 0.00 0.00 69.18
December 21335.55 05-DEC-22:54 134943.84 9960.10 33739.51 0.00 0.00 0.00 0.00 0.00 45.98
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 20804.15   26988.77 1992.02 6747.90 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 22812.48   242898.91 17928.18 60731.12 0.00 0.00 0.00 0.00 3.54 84.58



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: KITCHEN_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 28436.32 20-JAN-11:45 1067.42 589.34 29825.71 37488.05 0.00 0.00 0.00 0.00 15.06
February 28308.96 01-FEB-11:45 1067.42 589.34 29825.71 37488.05 0.00 0.00 0.00 9.20 0.00
March 29168.99 19-MAR-10:33 2401.70 1060.81 44738.57 56232.08 0.00 0.00 0.00 0.00 31.89
April 29567.87 30-APR-10:33 2401.70 1060.81 44738.57 56232.08 0.00 0.00 0.00 10.30 0.00
May 29272.52 04-MAY-10:33 1601.14 884.01 44738.57 56232.08 0.00 0.00 0.00 0.00 13.90
June 29639.28 25-JUN-10:33 2401.70 1060.81 44738.57 56232.08 0.00 0.00 0.00 0.00 7.21
July 30075.30 23-JUL-10:33 2401.70 1060.81 44738.57 56232.08 0.00 0.00 0.00 10.34 0.00
August 29952.91 19-AUG-10:33 2401.70 884.01 44738.57 56232.08 0.00 0.00 0.00 3.78 0.00
September 30329.55 30-SEP-10:50 1601.14 589.34 29825.71 37488.05 0.00 0.00 0.00 42.23 0.00
October 30194.87 15-OCT-10:40 2401.70 1060.81 44738.57 56232.08 0.00 0.00 0.00 48.09 0.00
November 29053.34 19-NOV-11:45 1601.14 707.21 29825.71 37488.05 0.00 0.00 0.00 12.47 0.00
December 28349.42 05-DEC-11:45 1067.42 589.34 29825.71 37488.05 0.00 0.00 0.00 0.00 6.14
                       
Annual Sum or Average             0.00 0.00 0.00    
Minimum of Months 28308.96   1067.42 589.34 29825.71 37488.05 0.00 0.00 0.00 0.00 0.00
Maximum of Months 30329.55   2401.70 1060.81 44738.57 56232.08 0.00 0.00 0.00 48.09 31.89



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORRIDOR_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 4371.84 06-JAN-23:00 2395.44 1317.51 0.00 0.00 0.00 0.00 0.00 0.00 113.36
February 4236.69 04-FEB-05:55 4790.88 439.17 0.00 0.00 0.00 0.00 0.00 0.00 111.23
March 4270.05 11-MAR-11:33 2395.44 1646.89 0.00 0.00 0.00 0.00 0.00 9.14 0.00
April 4453.11 30-APR-10:33 2395.44 1976.27 0.00 0.00 0.00 0.00 0.00 19.23 0.00
May 4525.64 04-MAY-10:33 1596.96 1646.89 0.00 0.00 0.00 0.00 0.00 0.00 6.07
June 4589.88 30-JUN-10:33 1596.96 1646.89 0.00 0.00 0.00 0.00 0.00 1.93 0.00
July 4822.62 30-JUL-10:33 2395.44 1976.27 0.00 0.00 0.00 0.00 0.00 8.68 0.00
August 4803.76 19-AUG-10:33 2395.44 1646.89 0.00 0.00 0.00 0.00 0.00 9.04 0.00
September 5183.82 30-SEP-13:40 798.48 548.96 0.00 0.00 0.00 0.00 0.00 49.26 0.00
October 5051.30 16-OCT-13:10 1064.64 1097.93 0.00 0.00 0.00 0.00 0.00 60.10 0.00
November 4535.76 19-NOV-11:33 2395.44 1976.27 0.00 0.00 0.00 0.00 0.00 18.75 0.00
December 4367.77 19-DEC-11:33 1596.96 1646.89 0.00 0.00 0.00 0.00 0.00 13.17 0.00
                       
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00    
Minimum of Months 4236.69   798.48 439.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5183.82   4790.88 1976.27 0.00 0.00 0.00 0.00 0.00 60.10 113.36



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.386654E+12 239249.29 17-JAN-19:10 0.524019E+12 454222.14 06-JAN-20:10
February 0.341240E+12 230736.48 13-FEB-19:19 0.460233E+12 451405.32 21-FEB-20:00
March 0.374264E+12 229395.86 23-MAR-19:19 0.536957E+12 466011.65 29-MAR-17:00
April 0.379523E+12 243477.11 26-APR-18:30 0.431268E+12 414910.19 15-APR-21:40
May 0.389580E+12 239539.83 04-MAY-18:00 0.429458E+12 389520.03 10-MAY-20:10
June 0.401498E+12 272709.29 29-JUN-18:10 0.358578E+12 352876.78 12-JUN-20:00
July 0.466116E+12 318795.82 18-JUL-18:10 0.355757E+12 313419.54 03-JUL-17:30
August 0.480548E+12 286948.89 14-AUG-18:40 0.355346E+12 312992.63 31-AUG-17:30
September 0.427235E+12 326139.69 29-SEP-18:00 0.350838E+12 315315.54 28-SEP-17:40
October 0.452170E+12 297624.61 15-OCT-08:00 0.388123E+12 352415.91 11-OCT-20:00
November 0.378102E+12 241594.23 19-NOV-08:00 0.459749E+12 442950.30 04-NOV-19:49
December 0.390839E+12 242912.53 05-DEC-19:10 0.520174E+12 457924.29 21-DEC-19:40
             
Annual Sum or Average 0.486777E+13     0.517050E+13    
Minimum of Months 0.341240E+12 229395.86   0.350838E+12 312992.63  
Maximum of Months 0.480548E+12 326139.69   0.536957E+12 466011.65  



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [J] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY [J] COGENERATION:ELECTRICITY []
January 0.669826E+11 0.191147E+11 0.140828E+12 0.691145E+11 0.425874E+11 0.619939E+10 0.00 0.285484E+11 0.00 0.00 0.00 0.804801E+10 0.00
February 0.603145E+11 0.163386E+11 0.127191E+12 0.624260E+11 0.384810E+11 0.569569E+10 0.00 0.187722E+11 0.00 0.00 0.00 0.727211E+10 0.00
March 0.666141E+11 0.167457E+11 0.140882E+12 0.691169E+11 0.421256E+11 0.608629E+10 0.00 0.193802E+11 0.00 0.00 0.00 0.804648E+10 0.00
April 0.641719E+11 0.148876E+11 0.136245E+12 0.668844E+11 0.421943E+11 0.631093E+10 0.00 0.359052E+11 0.00 0.00 0.00 0.779739E+10 0.00
May 0.660709E+11 0.142139E+11 0.140860E+12 0.691152E+11 0.436105E+11 0.652102E+10 0.00 0.358357E+11 0.00 0.00 0.00 0.804744E+10 0.00
June 0.638617E+11 0.131775E+11 0.136336E+12 0.668866E+11 0.433256E+11 0.619775E+10 0.00 0.587505E+11 0.00 0.00 0.00 0.778883E+10 0.00
July 0.660419E+11 0.138734E+11 0.140770E+12 0.691128E+11 0.459592E+11 0.661406E+10 0.00 0.110353E+12 0.00 0.00 0.00 0.805572E+10 0.00
August 0.661918E+11 0.148580E+11 0.140892E+12 0.691167E+11 0.463683E+11 0.668550E+10 0.00 0.123023E+12 0.00 0.00 0.00 0.804726E+10 0.00
September 0.644665E+11 0.156427E+11 0.136256E+12 0.668847E+11 0.441227E+11 0.630091E+10 0.00 0.805852E+11 0.00 0.00 0.00 0.779867E+10 0.00
October 0.668642E+11 0.175305E+11 0.140818E+12 0.691144E+11 0.464365E+11 0.662709E+10 0.00 0.914382E+11 0.00 0.00 0.00 0.804595E+10 0.00
November 0.647710E+11 0.181597E+11 0.136330E+12 0.668856E+11 0.423624E+11 0.628937E+10 0.00 0.304435E+11 0.00 0.00 0.00 0.778066E+10 0.00
December 0.669635E+11 0.194405E+11 0.140770E+12 0.691133E+11 0.430788E+11 0.635332E+10 0.00 0.318501E+11 0.00 0.00 0.00 0.805635E+10 0.00
                           
Annual Sum or Average 0.783315E+12 0.193983E+12 0.165818E+13 0.813771E+12 0.520652E+12 0.758813E+11 0.00 0.664886E+12 0.00 0.00 0.00 0.947849E+11 0.00
Minimum of Months 0.603145E+11 0.131775E+11 0.127191E+12 0.624260E+11 0.384810E+11 0.569569E+10 0.00 0.187722E+11 0.00 0.00 0.00 0.727211E+10 0.00
Maximum of Months 0.669826E+11 0.194405E+11 0.140892E+12 0.691169E+11 0.464365E+11 0.668550E+10 0.00 0.123023E+12 0.00 0.00 0.00 0.805635E+10 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [J] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [J] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.151918E+12 0.00 0.154119E+12 0.00 0.217982E+12 0.00 0.00
February 0.137204E+12 0.00 0.125931E+12 0.00 0.197098E+12 0.00 0.00
March 0.152024E+12 0.00 0.168419E+12 0.00 0.216515E+12 0.00 0.00
April 0.146956E+12 0.00 0.780922E+11 0.00 0.206220E+12 0.00 0.00
May 0.151978E+12 0.00 0.684318E+11 0.00 0.209048E+12 0.00 0.00
June 0.147114E+12 0.00 0.126494E+11 0.00 0.198815E+12 0.00 0.00
July 0.151820E+12 0.00 0.829945E+09 0.00 0.203106E+12 0.00 0.00
August 0.152039E+12 0.00 0.370378E+09 0.00 0.202937E+12 0.00 0.00
September 0.146971E+12 0.00 0.575534E+10 0.00 0.198112E+12 0.00 0.00
October 0.151903E+12 0.00 0.281449E+11 0.00 0.208075E+12 0.00 0.00
November 0.147091E+12 0.00 0.107375E+12 0.00 0.205283E+12 0.00 0.00
December 0.151820E+12 0.00 0.152599E+12 0.00 0.215755E+12 0.00 0.00
               
Annual Sum or Average 0.178884E+13 0.00 0.902716E+12 0.00 0.247895E+13 0.00 0.00
Minimum of Months 0.137204E+12 0.00 0.370378E+09 0.00 0.197098E+12 0.00 0.00
Maximum of Months 0.152039E+12 0.00 0.168419E+12 0.00 0.217982E+12 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 64632.59 02-JAN-20:10 12338.45 01-JAN-00:10 89171.45 02-JAN-07:10 49607.07 18-JAN-07:19 27942.11 18-JAN-22:00 2843.35 09-JAN-07:19 0.00 01-JAN-00:10
February 64632.59 01-FEB-20:10 12338.45 01-FEB-00:10 89171.45 01-FEB-07:10 49606.67 10-FEB-07:19 26838.33 01-FEB-22:10 2837.37 03-FEB-21:00 0.00 01-FEB-00:10
March 64632.59 01-MAR-20:10 12338.45 01-MAR-00:10 89171.45 01-MAR-07:10 49607.07 13-MAR-06:19 26845.15 23-MAR-21:10 2846.73 29-MAR-08:09 0.00 01-MAR-00:10
April 64632.59 03-APR-19:10 12338.45 01-APR-00:10 89171.45 03-APR-06:10 49606.67 05-APR-06:19 28887.19 26-APR-21:00 2827.10 01-APR-06:19 0.00 01-APR-00:10
May 64632.59 01-MAY-19:10 12338.45 01-MAY-00:10 89171.45 01-MAY-06:10 49606.28 09-MAY-06:19 29133.51 04-MAY-21:00 2826.25 14-MAY-04:49 0.00 01-MAY-00:10
June 64632.59 01-JUN-19:10 12338.45 01-JUN-00:10 89171.45 01-JUN-06:10 49606.28 16-JUN-06:19 29547.06 27-JUN-21:00 2824.86 29-JUN-18:10 0.00 01-JUN-00:10
July 64632.59 03-JUL-19:10 12338.45 01-JUL-00:10 89171.45 03-JUL-06:10 49606.28 12-JUL-06:19 31053.94 19-JUL-21:00 3320.25 18-JUL-18:10 0.00 01-JUL-00:10
August 64632.59 01-AUG-19:10 12338.45 01-AUG-00:10 89171.45 01-AUG-06:10 49606.67 21-AUG-06:19 30939.24 18-AUG-21:00 3329.52 14-AUG-10:50 0.00 01-AUG-00:10
September 64632.59 01-SEP-19:10 12338.45 01-SEP-00:10 89171.45 01-SEP-06:10 49607.07 18-SEP-06:19 32155.42 29-SEP-21:10 4250.92 29-SEP-15:20 0.00 01-SEP-00:10
October 64632.59 02-OCT-19:10 12338.45 01-OCT-00:10 89171.45 02-OCT-06:10 49607.07 05-OCT-06:19 34789.12 16-OCT-21:00 3687.31 17-OCT-10:50 0.00 01-OCT-00:10
November 64632.59 01-NOV-19:10 12338.45 01-NOV-00:10 89171.45 01-NOV-06:10 49607.07 01-NOV-06:19 28203.46 28-NOV-22:10 3110.49 19-NOV-10:00 0.00 01-NOV-00:10
December 64632.59 01-DEC-20:10 12338.45 01-DEC-00:10 89171.45 01-DEC-07:10 49607.07 08-DEC-07:19 29557.67 05-DEC-22:00 2841.31 19-DEC-21:19 0.00 01-DEC-00:10
                             
Annual Sum or Average                            
Minimum of Months 64632.59   12338.45   89171.45   49606.28   26838.33   2824.86   0.00  
Maximum of Months 64632.59   12338.45   89171.45   49607.07   34789.12   4250.92   0.00  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY {Maximum} [W] WATERSYSTEMS:ELECTRICITY {TIMESTAMP} COGENERATION:ELECTRICITY []
January 68516.21 14-JAN-10:00 0.00 0.00 0.00 4752.55 09-JAN-07:10 0.00
February 60514.85 01-FEB-11:50 0.00 0.00 0.00 4751.13 07-FEB-07:49 0.00
March 68473.05 23-MAR-15:09 0.00 0.00 0.00 4751.57 30-MAR-06:10 0.00
April 68010.09 26-APR-10:50 0.00 0.00 0.00 4751.13 03-APR-18:00 0.00
May 58494.97 04-MAY-15:09 0.00 0.00 0.00 4751.13 04-MAY-18:00 0.00
June 82648.21 29-JUN-18:10 0.00 0.00 0.00 4751.13 09-JUN-18:40 0.00
July 129646.22 19-JUL-15:20 0.00 0.00 0.00 4751.13 28-JUL-06:40 0.00
August 137929.44 18-AUG-15:09 0.00 0.00 0.00 4751.13 08-AUG-06:40 0.00
September 151238.10 29-SEP-15:09 0.00 0.00 0.00 4751.13 25-SEP-18:00 0.00
October 156617.73 16-OCT-11:09 0.00 0.00 0.00 4751.12 11-OCT-18:30 0.00
November 81184.49 19-NOV-09:00 0.00 0.00 0.00 4751.13 30-NOV-07:40 0.00
December 72534.18 05-DEC-09:50 0.00 0.00 0.00 4751.13 20-DEC-07:49 0.00
                 
Annual Sum or Average     0.00 0.00 0.00     0.00
Minimum of Months 58494.97   0.00 0.00 0.00 4751.12   0.00
Maximum of Months 156617.73   0.00 0.00 0.00 4752.55   0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY []
January 239249.29 17-JAN-19:10 57474.69 77573.37 12338.45 28159.60 19940.15 2427.34 0.00 34731.29 0.00
February 230736.48 13-FEB-19:19 57474.69 77573.37 12338.45 28169.74 20800.82 2407.46 0.00 24804.11 0.00
March 229395.86 23-MAR-19:19 64632.59 86439.81 12338.45 10999.77 24151.24 2400.40 0.00 22051.37 0.00
April 243477.11 26-APR-18:30 57474.69 77573.37 12338.45 28169.74 20169.42 2454.74 0.00 38123.93 0.00
May 239539.83 04-MAY-18:00 57474.69 77573.37 12338.45 28169.74 20535.26 2422.58 0.00 33857.44 0.00
June 272709.29 29-JUN-18:10 54326.11 77573.37 0.00 28157.54 20009.25 2824.86 0.00 82648.21 0.00
July 318795.82 18-JUL-18:10 54719.87 77573.37 0.00 28157.54 24643.19 3320.25 0.00 123776.00 0.00
August 286948.89 14-AUG-18:40 57474.69 77573.37 12338.45 28169.74 20568.31 2823.49 0.00 80832.58 0.00
September 326139.69 29-SEP-18:00 57474.69 77573.37 12338.45 28169.74 26461.96 2841.89 0.00 114713.80 0.00
October 297624.61 15-OCT-08:00 24800.21 70367.69 0.00 27993.71 23013.76 2805.26 0.00 142464.33 0.00
November 241594.23 19-NOV-08:00 29109.14 86249.25 0.00 49532.81 16932.78 2445.09 0.00 51549.44 0.00
December 242912.53 05-DEC-19:10 57474.69 77573.37 12338.45 28159.60 20769.66 2411.39 0.00 37627.04 0.00
                       
Annual Sum or Average                     0.00
Minimum of Months 229395.86   24800.21 70367.69 0.00 10999.77 16932.78 2400.40 0.00 22051.37 0.00
Maximum of Months 326139.69   64632.59 86439.81 12338.45 49532.81 26461.96 3320.25 0.00 142464.33 0.00



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS {Maximum} [W] INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS {Maximum} [W] WATERSYSTEMS:NATURALGAS {TIMESTAMP} COGENERATION:NATURALGAS []
January 104248.32 02-JAN-18:10 0.00 191268.39 08-JAN-06:00 0.00 226539.50 31-JAN-21:40 0.00
February 104248.32 01-FEB-18:10 0.00 152604.69 04-FEB-04:30 0.00 226542.04 06-FEB-21:40 0.00
March 104248.32 01-MAR-18:10 0.00 179579.26 30-MAR-02:00 0.00 225277.90 01-MAR-21:49 0.00
April 104248.32 01-APR-17:10 0.00 151070.81 20-APR-03:00 0.00 222389.31 05-APR-20:30 0.00
May 104248.32 01-MAY-17:10 0.00 153663.66 27-MAY-04:40 0.00 218078.36 01-MAY-20:19 0.00
June 104248.32 01-JUN-17:10 0.00 105674.71 13-JUN-03:00 0.00 214899.15 01-JUN-20:00 0.00
July 104248.32 01-JUL-17:10 0.00 45866.78 06-JUL-00:00 0.00 211843.78 03-JUL-20:49 0.00
August 104248.32 01-AUG-17:10 0.00 16224.00 28-AUG-03:00 0.00 211771.51 31-AUG-20:40 0.00
September 104248.32 01-SEP-17:10 0.00 101162.77 20-SEP-02:00 0.00 213931.15 28-SEP-20:00 0.00
October 104248.32 02-OCT-17:10 0.00 149600.77 28-OCT-04:00 0.00 217246.80 31-OCT-20:19 0.00
November 104248.32 01-NOV-17:10 0.00 154115.14 04-NOV-19:49 0.00 222320.19 30-NOV-21:19 0.00
December 104248.32 01-DEC-18:10 0.00 155958.60 21-DEC-19:40 0.00 224932.90 29-DEC-21:49 0.00
                   
Annual Sum or Average     0.00     0.00     0.00
Minimum of Months 104248.32   0.00 16224.00   0.00 211771.51   0.00
Maximum of Months 104248.32   0.00 191268.39   0.00 226542.04   0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BASEMENT

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: RETAIL_1_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: RETAIL_2_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: MECH_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: STORAGE_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: LAUNDRY_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CAFE_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: LOBBY_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_1_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.67 21.93 0.67 21.93
October 0.00 0.00 0.00 0.00 2.17 21.93 2.17 21.93
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   2.83 21.93 2.83 21.93
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 2.17 21.93 2.17 21.93



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_2_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.50 21.78 0.50 21.78
May 0.00 0.00 0.00 0.00 0.50 21.93 0.50 21.93
June 0.00 0.00 0.00 0.00 1.17 21.73 1.17 21.73
July 0.00 0.00 0.00 0.00 1.83 21.72 1.83 21.72
August 0.00 0.00 0.00 0.00 1.50 21.69 1.50 21.69
September 0.00 0.00 0.00 0.00 0.50 21.82 0.50 21.82
October 0.00 0.00 0.00 0.00 0.83 21.82 0.83 21.82
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   6.83 21.75 6.83 21.75
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 1.83 21.93 1.83 21.93



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.17 21.68 0.17 21.68
May 0.00 0.00 0.00 0.00 0.67 21.74 0.67 21.74
June 0.00 0.00 0.00 0.00 3.17 21.82 3.17 21.82
July 0.00 0.00 0.00 0.00 5.67 21.84 5.67 21.84
August 0.00 0.00 0.00 0.00 4.67 21.79 4.67 21.79
September 0.00 0.00 0.00 0.00 1.33 21.76 1.33 21.76
October 0.00 0.00 0.00 0.00 2.17 21.79 2.17 21.79
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   17.83 21.81 17.83 21.81
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 5.67 21.84 5.67 21.84



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_5_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.67 21.73 0.67 21.73
October 0.00 0.00 0.00 0.00 0.83 21.74 0.83 21.74
November 0.00 0.00 0.00 0.00 0.17 21.73 0.17 21.73
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   1.67 21.74 1.67 21.74
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.83 21.74 0.83 21.74



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_6_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.50 21.82 0.50 21.82
April 0.00 0.00 0.00 0.00 1.50 22.01 1.50 22.01
May 0.00 0.00 0.00 0.00 2.50 21.92 2.50 21.92
June 0.00 0.00 0.00 0.00 4.00 22.09 4.00 22.09
July 0.00 0.00 0.00 0.00 7.00 22.21 7.00 22.21
August 0.00 0.00 0.00 0.00 7.00 22.24 7.00 22.24
September 0.00 0.00 0.00 0.00 3.17 22.00 3.17 22.00
October 0.00 0.00 0.00 0.00 1.67 21.97 1.67 21.97
November 0.00 0.00 0.00 0.00 0.17 22.03 0.17 22.03
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   27.50 22.12 27.50 22.12
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 7.00 22.24 7.00 22.24



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORRIDOR_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_1_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.17 21.68 0.17 21.68
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.50 21.71 0.50 21.71
September 0.00 0.00 0.00 0.00 1.00 21.96 1.00 21.96
October 0.00 0.00 0.00 0.00 3.00 22.00 3.00 22.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   4.67 21.95 4.67 21.95
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 3.00 22.00 3.00 22.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_2_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.83 21.84 0.83 21.84
May 0.00 0.00 0.00 0.00 1.50 21.84 1.50 21.84
June 0.00 0.00 0.00 0.00 2.83 21.79 2.83 21.79
July 0.00 0.00 0.00 0.00 6.00 21.75 6.00 21.75
August 0.00 0.00 0.00 0.00 3.50 21.74 3.50 21.74
September 0.00 0.00 0.00 0.00 0.67 21.91 0.67 21.91
October 0.00 0.00 0.00 0.00 1.00 21.89 1.00 21.89
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   16.33 21.78 16.33 21.78
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 6.00 21.91 6.00 21.91



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.50 21.72 0.50 21.72
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.67 21.94 0.67 21.94
October 0.00 0.00 0.00 0.00 4.83 21.96 4.83 21.96
November 0.00 0.00 0.00 0.00 0.50 21.77 0.50 21.77
December 0.00 0.00 0.00 0.00 0.83 21.80 0.83 21.80
                 
Annual Sum or Average 0.00   0.00   7.33 21.91 7.33 21.91
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 4.83 21.96 4.83 21.96



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BANQUET_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DINING_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: KITCHEN_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORRIDOR_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: BASEMENT

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 682.33 23.10 5.17 23.10 0.00 23.10
February 668.83 22.77 0.00 22.77 0.00 22.77
March 744.00 22.47 0.00 22.47 0.00 22.47
April 720.00 22.50 0.00 22.50 0.00 22.50
May 744.00 22.52 0.00 22.52 0.00 22.52
June 720.00 22.43 0.00 22.43 0.00 22.43
July 744.00 22.77 0.00 22.77 0.00 22.77
August 733.17 22.87 0.00 22.87 0.00 22.87
September 576.33 23.10 6.33 23.11 0.00 23.11
October 510.83 23.35 38.67 23.39 0.00 23.39
November 556.00 23.43 15.17 23.45 0.00 23.45
December 698.50 23.24 2.00 23.25 0.00 23.25
             
Annual Sum or Average 8098.00 22.85 67.33 22.86 0.00 22.86
Minimum of Months 510.83 22.43 0.00 22.43 0.00 22.43
Maximum of Months 744.00 23.43 38.67 23.45 0.00 23.45



Table of Contents

Report: ComfortReportSimple55Monthly

For: RETAIL_1_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 591.50 21.67 93.33 21.96 6.50 21.95
February 567.00 21.56 59.17 21.77 2.50 21.77
March 669.00 21.42 51.83 21.57 5.50 21.56
April 649.83 21.73 23.83 21.79 0.00 21.79
May 735.50 21.50 0.00 21.50 0.00 21.50
June 720.00 21.76 0.00 21.76 0.00 21.76
July 693.00 22.15 7.83 22.16 0.00 22.16
August 550.50 22.33 103.83 22.51 0.00 22.51
September 501.00 22.19 156.33 22.55 0.00 22.55
October 500.00 22.22 160.50 22.62 0.00 22.62
November 561.33 21.89 96.00 22.18 0.67 22.18
December 574.17 21.77 86.33 22.06 0.00 22.06
             
Annual Sum or Average 7312.83 21.83 839.00 22.03 15.17 22.02
Minimum of Months 500.00 21.42 0.00 21.50 0.00 21.50
Maximum of Months 735.50 22.33 160.50 22.62 6.50 22.62



Table of Contents

Report: ComfortReportSimple55Monthly

For: RETAIL_2_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 709.33 22.54 7.50 22.56 0.00 22.56
February 638.17 22.62 2.00 22.62 0.00 22.62
March 712.83 22.38 6.83 22.40 0.00 22.40
April 599.50 22.69 40.33 22.76 1.50 22.76
May 646.17 22.66 23.83 22.71 0.00 22.71
June 514.17 22.74 95.17 22.91 19.00 22.92
July 414.83 22.94 251.50 23.25 86.00 23.28
August 395.67 23.07 324.00 23.38 111.83 23.41
September 369.00 22.95 197.17 23.24 33.67 23.25
October 487.50 23.09 138.00 23.25 30.00 23.26
November 640.17 22.90 17.67 22.93 0.00 22.93
December 718.83 22.76 3.00 22.77 0.00 22.77
             
Annual Sum or Average 6846.17 22.74 1107.00 22.89 282.00 22.91
Minimum of Months 369.00 22.38 2.00 22.40 0.00 22.40
Maximum of Months 718.83 23.09 324.00 23.38 111.83 23.41



Table of Contents

Report: ComfortReportSimple55Monthly

For: MECH_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.84 0.00 21.84 0.00 21.84
February 672.00 21.96 0.00 21.96 0.00 21.96
March 744.00 21.76 0.00 21.76 0.00 21.76
April 720.00 22.20 0.00 22.20 0.00 22.20
May 744.00 22.39 0.00 22.39 0.00 22.39
June 716.00 22.73 0.00 22.73 0.00 22.73
July 706.00 22.99 0.00 22.99 0.00 22.99
August 707.33 22.98 0.00 22.98 0.00 22.98
September 714.67 22.82 0.00 22.82 0.00 22.82
October 692.83 22.89 0.00 22.89 0.00 22.89
November 720.00 22.31 0.00 22.31 0.00 22.31
December 744.00 22.02 0.00 22.02 0.00 22.02
             
Annual Sum or Average 8624.83 22.40 0.00 22.40 0.00 22.40
Minimum of Months 672.00 21.76 0.00 21.76 0.00 21.76
Maximum of Months 744.00 22.99 0.00 22.99 0.00 22.99



Table of Contents

Report: ComfortReportSimple55Monthly

For: STORAGE_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.62 1.33 21.62 1.33 21.62
February 672.00 21.70 0.00 21.70 0.00 21.70
March 744.00 21.54 0.00 21.54 0.00 21.54
April 720.00 21.97 0.00 21.97 0.00 21.97
May 744.00 22.14 0.00 22.14 0.00 22.14
June 720.00 22.50 0.00 22.50 0.00 22.50
July 744.00 22.79 0.00 22.79 0.00 22.79
August 744.00 22.78 0.00 22.78 0.00 22.78
September 718.83 22.59 0.00 22.59 0.00 22.59
October 744.00 22.69 0.00 22.69 0.00 22.69
November 720.00 22.05 0.00 22.05 0.00 22.05
December 744.00 21.77 0.00 21.77 0.00 21.77
             
Annual Sum or Average 8758.83 22.18 1.33 22.18 1.33 22.18
Minimum of Months 672.00 21.54 0.00 21.54 0.00 21.54
Maximum of Months 744.00 22.79 1.33 22.79 1.33 22.79



Table of Contents

Report: ComfortReportSimple55Monthly

For: LAUNDRY_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 292.33 22.96 559.67 23.11 194.33 23.27
February 254.50 23.16 542.33 23.16 181.83 23.31
March 306.33 23.12 595.67 23.12 219.17 23.29
April 293.83 23.55 623.67 23.23 250.33 23.39
May 305.67 23.54 649.00 23.23 259.00 23.39
June 296.00 23.80 656.00 23.26 278.00 23.42
July 297.33 23.96 703.17 23.26 296.50 23.42
August 300.00 23.97 706.33 23.25 299.33 23.41
September 290.17 23.85 661.83 23.27 278.00 23.43
October 280.67 23.59 651.00 23.25 242.17 23.40
November 285.67 23.25 581.17 23.22 213.33 23.37
December 280.33 22.90 553.50 23.12 175.83 23.27
             
Annual Sum or Average 3482.83 23.48 7483.33 23.21 2887.83 23.37
Minimum of Months 254.50 22.90 542.33 23.11 175.83 23.27
Maximum of Months 306.33 23.97 706.33 23.27 299.33 23.43



Table of Contents

Report: ComfortReportSimple55Monthly

For: CAFE_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 398.00 22.59 221.83 23.05 16.00 23.07
February 399.50 22.52 166.67 22.89 13.17 22.90
March 508.33 22.25 131.33 22.54 3.00 22.55
April 398.33 22.61 197.50 22.93 35.33 22.98
May 622.50 22.48 75.83 22.62 40.17 22.68
June 567.50 22.64 183.67 22.91 139.83 23.04
July 527.83 23.08 365.50 23.30 284.00 23.40
August 397.00 23.53 541.17 23.55 315.83 23.62
September 302.33 23.38 525.67 23.56 205.67 23.62
October 256.83 23.11 428.33 23.57 86.83 23.61
November 307.00 22.94 272.67 23.36 23.33 23.36
December 386.17 22.78 200.50 23.17 0.00 23.17
             
Annual Sum or Average 5071.33 22.78 3310.67 23.15 1163.17 23.23
Minimum of Months 256.83 22.25 75.83 22.54 0.00 22.55
Maximum of Months 622.50 23.53 541.17 23.57 315.83 23.62



Table of Contents

Report: ComfortReportSimple55Monthly

For: LOBBY_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 553.17 22.80 66.83 22.92 7.33 22.93
February 510.67 22.86 52.67 22.96 6.17 22.96
March 591.17 22.58 49.83 22.68 0.00 22.68
April 455.33 22.73 146.33 23.01 13.33 23.03
May 493.83 22.69 117.50 22.92 20.67 22.95
June 424.50 22.84 270.67 23.23 94.83 23.31
July 497.33 23.19 385.50 23.48 224.50 23.56
August 482.67 23.42 411.00 23.62 283.00 23.69
September 323.33 23.36 353.33 23.62 167.17 23.68
October 279.33 23.27 264.33 23.56 62.00 23.60
November 429.50 23.13 112.50 23.28 18.17 23.29
December 585.33 23.08 35.67 23.12 0.00 23.12
             
Annual Sum or Average 5626.17 22.97 2266.17 23.22 897.17 23.29
Minimum of Months 279.33 22.58 35.67 22.68 0.00 22.68
Maximum of Months 591.17 23.42 411.00 23.62 283.00 23.69



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_1_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 730.50 21.56 9.83 21.56 9.83 21.55
February 656.00 21.49 5.83 21.48 5.83 21.48
March 726.33 21.46 8.83 21.45 8.83 21.44
April 682.33 21.56 0.00 21.56 0.00 21.56
May 724.50 21.58 0.00 21.58 0.00 21.58
June 675.17 21.56 0.00 21.56 0.00 21.56
July 662.67 21.51 0.00 21.51 0.00 21.51
August 653.67 21.49 0.00 21.49 0.00 21.49
September 653.67 21.53 0.67 21.53 0.00 21.53
October 693.50 21.56 0.50 21.57 0.00 21.57
November 690.50 21.57 7.17 21.56 7.17 21.56
December 734.33 21.59 8.33 21.59 8.33 21.58
             
Annual Sum or Average 8283.17 21.54 41.17 21.54 40.00 21.53
Minimum of Months 653.67 21.46 0.00 21.45 0.00 21.44
Maximum of Months 734.33 21.59 9.83 21.59 9.83 21.58



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_2_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.44 43.00 21.42 43.00 21.40
February 672.00 21.43 14.00 21.43 14.00 21.42
March 730.67 21.44 17.83 21.46 10.17 21.44
April 630.83 21.65 45.67 21.86 0.00 21.86
May 646.33 21.73 54.17 21.97 0.00 21.97
June 546.83 21.95 122.17 22.54 8.33 22.57
July 509.67 22.10 199.33 22.92 48.00 23.03
August 518.00 22.05 191.00 22.78 53.00 22.86
September 583.50 21.94 76.33 22.22 14.33 22.24
October 691.83 22.04 39.00 22.13 28.00 22.17
November 719.50 21.59 16.83 21.58 16.83 21.57
December 744.00 21.48 39.67 21.46 39.67 21.44
             
Annual Sum or Average 7737.17 21.71 859.00 21.96 275.33 21.99
Minimum of Months 509.67 21.43 14.00 21.42 0.00 21.40
Maximum of Months 744.00 22.10 199.33 22.92 53.00 23.03



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.39 5.33 21.39 5.33 21.39
February 672.00 21.38 8.00 21.38 8.00 21.37
March 744.00 21.40 0.00 21.40 0.00 21.40
April 720.00 21.61 0.00 21.61 0.00 21.61
May 744.00 21.73 0.00 21.73 0.00 21.73
June 711.17 22.07 1.33 22.08 0.00 22.08
July 720.17 22.27 21.33 22.31 18.50 22.34
August 731.17 22.22 20.67 22.25 20.50 22.28
September 720.00 21.95 4.67 21.96 4.67 21.96
October 742.00 21.92 16.33 21.95 16.33 21.98
November 720.00 21.43 11.67 21.42 11.67 21.42
December 744.00 21.38 14.00 21.37 14.00 21.37
             
Annual Sum or Average 8712.50 21.73 103.33 21.74 99.00 21.75
Minimum of Months 672.00 21.38 0.00 21.37 0.00 21.37
Maximum of Months 744.00 22.27 21.33 22.31 20.50 22.34



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_5_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.64 13.33 21.63 13.33 21.62
February 672.00 21.55 7.17 21.54 7.17 21.54
March 744.00 21.55 8.83 21.54 8.83 21.53
April 719.17 21.68 0.00 21.68 0.00 21.68
May 743.83 21.66 0.00 21.66 0.00 21.66
June 716.67 21.68 0.00 21.68 0.00 21.68
July 722.17 21.69 0.00 21.69 0.00 21.69
August 693.00 21.62 0.00 21.62 0.00 21.62
September 699.33 21.65 0.00 21.65 0.00 21.65
October 716.33 21.64 0.00 21.64 0.00 21.64
November 720.00 21.66 7.83 21.66 7.83 21.65
December 744.00 21.65 12.83 21.64 12.83 21.63
             
Annual Sum or Average 8634.50 21.64 50.00 21.63 50.00 21.63
Minimum of Months 672.00 21.55 0.00 21.54 0.00 21.53
Maximum of Months 744.00 21.69 13.33 21.69 13.33 21.69



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_6_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 743.33 21.45 34.17 21.44 34.17 21.43
February 672.00 21.42 13.33 21.41 13.33 21.41
March 741.83 21.49 11.00 21.48 10.33 21.47
April 705.00 21.84 8.67 21.87 0.00 21.87
May 720.33 21.90 10.50 21.94 0.00 21.94
June 635.33 22.09 50.33 22.28 3.00 22.29
July 561.33 22.24 134.17 22.68 48.17 22.80
August 574.83 22.29 127.83 22.69 60.00 22.84
September 685.33 22.08 30.83 22.17 14.17 22.20
October 730.83 22.09 30.83 22.15 26.67 22.19
November 718.83 21.54 23.00 21.53 22.83 21.52
December 743.50 21.48 40.00 21.47 40.00 21.45
             
Annual Sum or Average 8232.50 21.81 514.67 21.92 272.67 21.94
Minimum of Months 561.33 21.42 8.67 21.41 0.00 21.41
Maximum of Months 743.50 22.29 134.17 22.69 60.00 22.84



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORRIDOR_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.74 0.00 21.74 0.00 21.74
February 672.00 21.80 0.00 21.80 0.00 21.80
March 744.00 21.61 0.00 21.61 0.00 21.61
April 720.00 22.02 0.00 22.02 0.00 22.02
May 744.00 22.09 0.00 22.09 0.00 22.09
June 720.00 22.36 10.33 22.37 10.33 22.37
July 744.00 22.70 53.50 22.71 53.50 22.71
August 744.00 22.79 70.00 22.80 70.00 22.80
September 720.00 22.60 17.83 22.60 17.83 22.60
October 742.33 22.73 20.83 22.74 20.83 22.74
November 720.00 22.15 0.00 22.15 0.00 22.15
December 744.00 21.95 0.00 21.95 0.00 21.95
             
Annual Sum or Average 8758.33 22.21 172.50 22.23 172.50 22.24
Minimum of Months 672.00 21.61 0.00 21.61 0.00 21.61
Maximum of Months 744.00 22.79 70.00 22.80 70.00 22.80



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_1_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 722.67 21.51 46.00 21.48 46.00 21.46
February 651.67 21.43 27.50 21.42 27.50 21.41
March 715.83 21.39 28.17 21.37 28.17 21.35
April 667.83 21.51 2.50 21.51 2.50 21.50
May 705.17 21.53 0.67 21.53 0.67 21.53
June 655.00 21.50 0.33 21.50 0.33 21.50
July 643.17 21.45 1.00 21.45 1.00 21.46
August 636.50 21.43 3.00 21.44 3.00 21.45
September 636.50 21.47 6.67 21.48 3.67 21.48
October 682.33 21.52 4.33 21.53 0.67 21.53
November 682.17 21.51 34.33 21.49 34.33 21.47
December 729.67 21.54 50.67 21.51 50.67 21.49
             
Annual Sum or Average 8128.50 21.48 205.17 21.48 198.50 21.47
Minimum of Months 636.50 21.39 0.33 21.37 0.33 21.35
Maximum of Months 729.67 21.54 50.67 21.53 50.67 21.53



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_2_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.37 101.17 21.32 101.17 21.29
February 671.67 21.36 43.33 21.35 43.33 21.33
March 724.17 21.38 45.33 21.40 35.33 21.37
April 605.67 21.59 63.83 21.89 5.00 21.90
May 617.50 21.65 72.17 22.00 0.33 22.00
June 541.00 22.07 137.00 22.79 32.83 22.96
July 519.83 22.34 213.83 23.22 88.33 23.45
August 524.33 22.18 214.33 22.99 93.17 23.15
September 552.67 21.83 107.00 22.21 31.83 22.24
October 681.67 21.94 52.17 22.06 35.50 22.12
November 718.83 21.51 59.17 21.48 59.17 21.45
December 744.00 21.38 113.67 21.33 113.67 21.29
             
Annual Sum or Average 7645.33 21.68 1223.00 21.98 639.67 22.02
Minimum of Months 519.83 21.36 43.33 21.32 0.33 21.29
Maximum of Months 744.00 22.34 214.33 23.22 113.67 23.45



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 658.00 21.48 0.50 21.48 0.50 21.48
February 627.67 21.49 1.67 21.49 1.67 21.49
March 701.00 21.47 7.50 21.46 7.50 21.45
April 694.83 21.59 0.00 21.59 0.00 21.59
May 744.00 21.59 0.00 21.59 0.00 21.59
June 720.00 21.62 0.00 21.62 0.00 21.62
July 740.00 21.67 0.17 21.67 0.17 21.67
August 686.33 21.56 1.00 21.56 1.00 21.56
September 632.17 21.45 1.67 21.46 0.00 21.46
October 649.83 21.46 6.67 21.48 0.33 21.48
November 646.17 21.52 2.83 21.53 1.00 21.53
December 659.17 21.50 0.67 21.50 0.17 21.50
             
Annual Sum or Average 8159.17 21.54 22.67 21.54 12.33 21.54
Minimum of Months 627.67 21.45 0.00 21.46 0.00 21.45
Maximum of Months 744.00 21.67 7.50 21.67 7.50 21.67



Table of Contents

Report: ComfortReportSimple55Monthly

For: BANQUET_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 256.67 23.10 270.83 23.54 12.00 23.55
February 157.67 23.29 308.50 23.72 10.83 23.73
March 139.67 22.99 403.17 23.67 1.00 23.67
April 25.33 23.58 591.00 23.89 12.33 23.89
May 20.33 23.78 646.33 23.91 15.83 23.91
June 90.17 23.99 702.83 23.91 89.83 23.92
July 215.67 24.00 744.00 23.93 215.67 23.94
August 279.67 24.00 743.83 23.93 279.67 23.94
September 172.83 24.00 705.67 23.90 172.83 23.92
October 91.83 23.76 544.17 23.88 63.67 23.89
November 146.67 23.43 337.67 23.78 19.83 23.78
December 265.67 23.26 187.33 23.55 0.00 23.55
             
Annual Sum or Average 1862.17 23.57 6185.33 23.83 893.50 23.85
Minimum of Months 20.33 22.99 187.33 23.54 0.00 23.55
Maximum of Months 279.67 24.00 744.00 23.93 279.67 23.94



Table of Contents

Report: ComfortReportSimple55Monthly

For: DINING_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 129.67 23.12 393.00 23.74 4.83 23.74
February 33.33 23.45 446.50 23.89 6.50 23.89
March 45.50 22.99 559.50 23.84 0.00 23.84
April 11.00 24.00 666.33 23.93 11.00 23.93
May 8.83 24.00 718.33 23.94 8.83 23.94
June 73.33 24.00 717.33 23.95 73.33 23.95
July 200.33 24.00 744.00 23.97 200.33 23.97
August 264.50 24.00 744.00 23.96 264.50 23.97
September 149.83 24.00 717.67 23.94 149.83 23.95
October 61.00 23.96 607.83 23.94 58.00 23.94
November 56.00 23.60 465.33 23.89 14.33 23.89
December 96.00 23.29 298.00 23.78 0.00 23.78
             
Annual Sum or Average 1129.33 23.76 7077.83 23.91 791.50 23.92
Minimum of Months 8.83 22.99 298.00 23.74 0.00 23.74
Maximum of Months 264.50 24.00 744.00 23.97 264.50 23.97



Table of Contents

Report: ComfortReportSimple55Monthly

For: KITCHEN_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 565.83 23.77 663.67 23.82 517.83 23.87
February 482.67 23.95 640.33 23.89 473.17 23.92
March 559.83 23.84 691.83 23.85 528.17 23.89
April 525.17 23.99 714.17 23.92 524.83 23.94
May 546.17 23.99 740.50 23.92 546.17 23.94
June 547.17 23.99 720.00 23.94 547.17 23.95
July 574.67 23.99 744.00 23.95 574.67 23.96
August 577.17 23.99 744.00 23.95 577.17 23.96
September 546.67 23.99 720.00 23.94 546.67 23.95
October 544.17 23.99 741.00 23.93 544.17 23.95
November 517.00 23.95 683.50 23.90 508.50 23.93
December 551.50 23.82 656.83 23.86 513.33 23.90
             
Annual Sum or Average 6538.00 23.94 8459.83 23.91 6401.83 23.93
Minimum of Months 482.67 23.77 640.33 23.82 473.17 23.87
Maximum of Months 577.17 23.99 744.00 23.95 577.17 23.96



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORRIDOR_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.70 4.17 21.70 4.17 21.69
February 672.00 21.68 0.00 21.68 0.00 21.68
March 744.00 21.62 0.00 21.62 0.00 21.62
April 720.00 22.12 0.00 22.12 0.00 22.12
May 744.00 22.13 0.00 22.13 0.00 22.13
June 712.83 22.49 0.00 22.49 0.00 22.49
July 688.67 22.82 0.00 22.82 0.00 22.82
August 628.50 22.86 2.83 22.86 0.00 22.86
September 691.50 22.62 0.00 22.62 0.00 22.62
October 691.33 22.63 7.17 22.64 0.00 22.64
November 720.00 21.97 0.00 21.97 0.00 21.97
December 744.00 21.78 1.67 21.78 1.67 21.78
             
Annual Sum or Average 8500.83 22.19 15.83 22.19 5.83 22.19
Minimum of Months 628.50 21.62 0.00 21.62 0.00 21.62
Maximum of Months 744.00 22.86 7.17 22.86 4.17 22.86



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BASEMENT PEOPLE

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.15491 38.74822 0.12435 5.68534
February 672.00000 22.77136 42.37446 0.04280 5.23839
March 744.00000 22.46717 46.67266 -0.0060 5.20689
April 720.00000 22.49897 51.38987 0.02881 5.21527
May 744.00000 22.52321 50.96943 -1.0262 27.43020
June 720.00000 22.43137 58.19007 -1.0126 26.83470
July 744.00000 22.76950 60.67321 -0.8707 21.21828
August 744.00000 22.87860 61.17290 -0.8274 19.64719
September 720.00000 23.20434 56.76139 -0.7360 16.67028
October 744.00000 23.47175 45.73714 0.25054 6.54808
November 720.00000 23.52292 39.72025 0.22262 6.28169
December 744.00000 23.27936 33.59897 0.12024 5.59700
           
Annual Sum or Average 8760.00000 22.91563 48.85775 -0.3096 12.67960
Minimum of Months 672.00000 22.43137 33.59897 -1.0262 5.20689
Maximum of Months 744.00000 23.52292 61.17290 0.25054 27.43020



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: RETAIL_1_FLR_1 PEOPLE

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 22.12303 40.08848 -0.0396 7.10290
February 672.00000 21.91029 43.58635 -0.0860 6.83697
March 744.00000 21.64048 47.86631 -0.1404 6.91368
April 720.00000 21.88159 52.22235 -0.0319 6.03818
May 744.00000 21.52164 52.85978 -1.2487 38.24933
June 720.00000 21.75640 59.51028 -1.1094 31.43276
July 744.00000 22.20296 61.85012 -0.9196 23.33639
August 744.00000 22.56358 61.54859 -0.7838 18.81691
September 720.00000 22.60277 57.87842 -0.7912 20.10182
October 744.00000 22.71179 46.87886 0.17971 7.14795
November 720.00000 22.31975 41.46804 0.02907 6.77477
December 744.00000 22.25725 34.66204 -0.0311 7.03641
           
Annual Sum or Average 8760.00000 22.12588 50.05800 -0.4164 15.03719
Minimum of Months 672.00000 21.52164 34.66204 -1.2487 6.03818
Maximum of Months 744.00000 22.71179 61.85012 0.17971 38.24933



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: RETAIL_2_FLR_1 PEOPLE

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 22.59684 40.77651 0.03347 5.64352
February 672.00000 22.67467 43.57821 0.06499 5.46826
March 744.00000 22.43561 47.64978 0.03181 5.60345
April 720.00000 22.85246 51.32675 0.16365 6.04044
May 744.00000 22.79198 51.16153 -0.8687 21.59572
June 720.00000 22.99186 57.39193 -0.7516 17.54205
July 744.00000 23.23750 60.12953 -0.6376 14.03315
August 744.00000 23.33582 60.64126 -0.5958 12.88496
September 720.00000 23.28325 57.46682 -0.6382 14.00548
October 744.00000 23.31031 47.05138 0.26207 6.83098
November 720.00000 22.99522 41.79946 0.13951 5.77503
December 744.00000 22.79569 35.47085 0.04839 5.39881
           
Annual Sum or Average 8760.00000 22.94299 49.55902 -0.2310 10.09783
Minimum of Months 672.00000 22.43561 35.47085 -0.8687 5.39881
Maximum of Months 744.00000 23.33582 60.64126 0.26207 21.59572



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: LAUNDRY_FLR_1 PEOPLE

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 22.71600 35.99753 0.64801 17.08442
February 672.00000 22.80920 38.58874 0.68394 17.79399
March 744.00000 22.72386 42.44459 0.68900 18.10503
April 720.00000 22.82908 46.94304 0.76055 19.99248
May 744.00000 22.84141 46.47995 0.02095 10.77816
June 720.00000 22.84636 53.34170 0.08548 10.83945
July 744.00000 22.85498 56.85309 0.12745 10.75759
August 744.00000 22.84797 57.70447 0.13593 10.92396
September 720.00000 22.85513 54.28427 0.09638 10.74544
October 744.00000 22.87394 43.59350 0.76555 20.15076
November 720.00000 22.86081 37.44848 0.70027 18.26476
December 744.00000 22.76042 30.86341 0.62707 16.29739
           
Annual Sum or Average 8760.00000 22.81801 45.40560 0.44346 15.12469
Minimum of Months 672.00000 22.71600 30.86341 0.02095 10.74544
Maximum of Months 744.00000 22.87394 57.70447 0.76555 20.15076



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CAFE_FLR_1 PEOPLE

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.11872 43.94172 0.26832 7.75161
February 672.00000 22.99521 47.13510 0.23576 7.19091
March 744.00000 22.65575 51.27230 0.16618 6.85431
April 720.00000 22.94914 55.30389 0.27684 7.18275
May 744.00000 22.64140 55.73853 -0.8211 20.09960
June 720.00000 22.79247 62.22002 -0.7098 16.45841
July 744.00000 23.03581 64.94319 -0.5818 12.72986
August 744.00000 23.29311 64.89988 -0.4720 10.14242
September 720.00000 23.41069 61.16086 -0.4498 10.08301
October 744.00000 23.51656 50.57902 0.43673 9.67749
November 720.00000 23.38258 45.13979 0.34586 8.24338
December 744.00000 23.26576 38.84979 0.27833 7.58369
           
Annual Sum or Average 8760.00000 23.08836 53.45610 -0.0876 10.35721
Minimum of Months 672.00000 22.64140 38.84979 -0.8211 6.85431
Maximum of Months 744.00000 23.51656 64.94319 0.43673 20.09960



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: LOBBY_FLR_1 PEOPLE

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.03344 43.07578 0.17751 6.26896
February 672.00000 23.07399 45.86554 0.19774 6.21823
March 744.00000 22.80759 49.91618 0.15561 6.13868
April 720.00000 23.09515 53.85040 0.25827 6.86622
May 744.00000 23.03493 53.67454 -0.7441 17.49402
June 720.00000 23.17408 59.95943 -0.6436 14.52321
July 744.00000 23.31843 62.90435 -0.5612 12.29053
August 744.00000 23.40488 63.40254 -0.5220 11.26687
September 720.00000 23.43551 60.00450 -0.5356 11.50725
October 744.00000 23.52912 49.47205 0.35956 8.03591
November 720.00000 23.36291 44.16192 0.26893 6.85715
December 744.00000 23.21890 37.91920 0.19074 6.08058
           
Annual Sum or Average 8760.00000 23.20786 52.04062 -0.1186 9.48375
Minimum of Months 672.00000 22.80759 37.91920 -0.7441 6.08058
Maximum of Months 744.00000 23.52912 63.40254 0.35956 17.49402



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_1_FLR_3 PEOPLE

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.59691 47.37376 -0.2196 6.95255
February 672.00000 21.53082 50.35391 -0.2192 6.78525
March 744.00000 21.50603 53.62481 -0.2118 6.77544
April 720.00000 21.64895 54.37376 -0.1231 6.21168
May 744.00000 21.62857 54.68293 -1.2573 39.14311
June 720.00000 21.66604 56.60893 -1.1923 36.04226
July 744.00000 21.70778 56.26545 -1.1389 33.65791
August 744.00000 21.71089 56.38976 -1.1326 33.43018
September 720.00000 21.69219 56.06391 -1.1655 34.98091
October 744.00000 21.68396 49.86661 -0.1092 6.18661
November 720.00000 21.63749 47.61246 -0.1838 6.67529
December 744.00000 21.61697 42.27219 -0.2344 7.12721
           
Annual Sum or Average 8760.00000 21.63613 52.12171 -0.6014 18.73631
Minimum of Months 672.00000 21.50603 42.27219 -1.2573 6.18661
Maximum of Months 744.00000 21.71089 56.60893 -0.1092 39.14311



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_2_FLR_3 PEOPLE

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.44073 49.09266 -0.2968 7.51986
February 672.00000 21.43441 51.71587 -0.2691 7.09636
March 744.00000 21.48342 54.80716 -0.2365 7.00825
April 720.00000 21.96755 54.77917 -0.0712 6.69187
May 744.00000 22.06541 53.90451 -1.1367 34.68558
June 720.00000 22.57982 55.30060 -0.9270 27.51727
July 744.00000 22.86373 55.52593 -0.7998 23.31549
August 744.00000 22.77102 56.79652 -0.8307 23.82647
September 720.00000 22.32566 57.28089 -1.0020 28.72361
October 744.00000 22.15600 50.95498 -0.0358 6.29273
November 720.00000 21.58836 49.58489 -0.2306 6.87781
December 744.00000 21.47792 43.48640 -0.3145 7.67495
           
Annual Sum or Average 8760.00000 22.01647 52.76171 -0.5141 15.65216
Minimum of Months 672.00000 21.43441 43.48640 -1.1367 6.29273
Maximum of Months 744.00000 22.86373 57.28089 -0.0358 34.68558



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_3_MULT19_FLR_3 PEOPLE

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 0.00000 0.00000 0.00000 0.00000 0.00000
February 0.00000 0.00000 0.00000 0.00000 0.00000
March 0.00000 0.00000 0.00000 0.00000 0.00000
April 0.00000 0.00000 0.00000 0.00000 0.00000
May 0.00000 0.00000 0.00000 0.00000 0.00000
June 0.00000 0.00000 0.00000 0.00000 0.00000
July 0.00000 0.00000 0.00000 0.00000 0.00000
August 0.00000 0.00000 0.00000 0.00000 0.00000
September 0.00000 0.00000 0.00000 0.00000 0.00000
October 0.00000 0.00000 0.00000 0.00000 0.00000
November 0.00000 0.00000 0.00000 0.00000 0.00000
December 0.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 0.00000        
Minimum of Months 0.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 0.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_4_MULT19_FLR_3 PEOPLE

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.39164 45.15239 -0.3231 7.48848
February 672.00000 21.37824 47.97005 -0.3033 7.12463
March 744.00000 21.40119 51.30867 -0.2759 6.82168
April 720.00000 21.60888 53.44656 -0.1974 6.19904
May 744.00000 21.72759 52.39812 -1.3004 40.77490
June 720.00000 22.09400 55.69813 -1.1387 33.35532
July 744.00000 22.31749 57.89536 -1.0393 29.19715
August 744.00000 22.24773 59.21869 -1.0638 30.11589
September 720.00000 21.94891 57.68135 -1.1875 35.39321
October 744.00000 21.92092 49.18670 -0.1359 6.12038
November 720.00000 21.42642 46.33158 -0.2978 7.13528
December 744.00000 21.37868 39.87727 -0.3567 7.86656
           
Annual Sum or Average 8760.00000 21.73940 51.35354 -0.6369 18.19702
Minimum of Months 672.00000 21.37824 39.87727 -1.3004 6.12038
Maximum of Months 744.00000 22.31749 59.21869 -0.1359 40.77490



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_5_FLR_3 PEOPLE

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.64126 47.07011 -0.2075 6.80956
February 672.00000 21.54800 50.36358 -0.2191 6.75065
March 744.00000 21.54777 53.20624 -0.2053 6.72232
April 720.00000 21.68600 54.14167 -0.1212 6.19673
May 744.00000 21.66069 54.44875 -1.2613 39.31051
June 720.00000 21.68302 56.90863 -1.2038 36.55423
July 744.00000 21.73369 56.30510 -1.1433 33.87977
August 744.00000 21.73519 56.25846 -1.1322 33.42941
September 720.00000 21.69345 56.81096 -1.1810 35.65450
October 744.00000 21.69874 50.05213 -0.1088 6.14741
November 720.00000 21.66059 47.73576 -0.1827 6.59447
December 744.00000 21.64773 42.19646 -0.2279 7.00332
           
Annual Sum or Average 8760.00000 21.66206 52.11985 -0.6018 18.82572
Minimum of Months 672.00000 21.54777 42.19646 -1.2613 6.14741
Maximum of Months 744.00000 21.73519 56.90863 -0.1088 39.31051



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_6_FLR_3 PEOPLE

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.45672 48.66416 -0.2908 7.32923
February 672.00000 21.41980 51.68282 -0.2771 7.02457
March 744.00000 21.49652 54.41624 -0.2365 6.85249
April 720.00000 21.89341 54.87424 -0.0928 6.21459
May 744.00000 21.98125 54.31374 -1.1730 35.51603
June 720.00000 22.34843 56.80708 -1.0058 28.81861
July 744.00000 22.67053 56.82778 -0.8632 24.01390
August 744.00000 22.64257 57.73960 -0.8706 24.18531
September 720.00000 22.18581 58.75076 -1.0580 30.43003
October 744.00000 22.13188 51.27200 -0.0442 6.08171
November 720.00000 21.55010 49.62749 -0.2443 6.78657
December 744.00000 21.48686 43.51989 -0.3121 7.48905
           
Annual Sum or Average 8760.00000 21.94231 53.20072 -0.5405 15.94433
Minimum of Months 672.00000 21.41980 43.51989 -1.1730 6.08171
Maximum of Months 744.00000 22.67053 58.75076 -0.0442 35.51603



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_1_FLR_6 PEOPLE

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.56068 48.63493 -0.2453 7.36329
February 672.00000 21.48290 51.85062 -0.2465 7.18675
March 744.00000 21.46824 55.15244 -0.2319 7.14434
April 720.00000 21.63973 55.89896 -0.1257 6.39358
May 744.00000 21.62118 56.14351 -1.2652 39.75062
June 720.00000 21.66249 58.00311 -1.1901 36.14103
July 744.00000 21.70647 57.36414 -1.1321 33.55384
August 744.00000 21.70664 57.71526 -1.1285 33.44855
September 720.00000 21.68163 57.94464 -1.1692 35.35348
October 744.00000 21.66601 51.29499 -0.1197 6.38750
November 720.00000 21.60353 49.12107 -0.2075 7.01798
December 744.00000 21.57582 43.39215 -0.2644 7.59062
           
Annual Sum or Average 8760.00000 21.61534 53.53828 -0.6128 19.01592
Minimum of Months 672.00000 21.46824 43.39215 -1.2652 6.38750
Maximum of Months 744.00000 21.70664 58.00311 -0.1197 39.75062



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_2_FLR_6 PEOPLE

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.36524 50.49484 -0.3353 8.11686
February 672.00000 21.36474 53.36585 -0.3036 7.62956
March 744.00000 21.45584 56.37889 -0.2556 7.43105
April 720.00000 22.01892 55.93095 -0.0607 7.12997
May 744.00000 22.10961 54.92778 -1.1256 34.97544
June 720.00000 22.68678 55.65763 -0.8868 27.54647
July 744.00000 22.98744 55.25445 -0.7501 23.25735
August 744.00000 22.85889 56.82083 -0.7953 23.85911
September 720.00000 22.33360 58.56738 -0.9976 29.11758
October 744.00000 22.09621 52.32946 -0.0542 6.52283
November 720.00000 21.51242 51.32743 -0.2665 7.37180
December 744.00000 21.38338 44.72917 -0.3608 8.41395
           
Annual Sum or Average 8760.00000 22.01841 53.80204 -0.5174 15.99583
Minimum of Months 672.00000 21.36474 44.72917 -1.1256 6.52283
Maximum of Months 744.00000 22.98744 58.56738 -0.0542 34.97544



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_3_MULT9_FLR_6 PEOPLE

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.69642 46.00182 -0.1567 6.78833
February 672.00000 21.61624 49.28015 -0.1857 6.75252
March 744.00000 21.57378 52.44049 -0.1982 6.84157
April 720.00000 21.65484 54.55710 -0.1444 6.39852
May 744.00000 21.59447 56.16460 -1.3230 42.36766
June 720.00000 21.61928 59.59306 -1.2671 39.54167
July 744.00000 21.68177 59.68844 -1.2102 36.92989
August 744.00000 21.69705 58.56849 -1.1841 35.82118
September 720.00000 21.68009 56.42903 -1.1938 36.45172
October 744.00000 21.69975 49.62502 -0.1019 6.36067
November 720.00000 21.70774 46.27695 -0.1448 6.66756
December 744.00000 21.70802 41.33106 -0.1717 6.97056
           
Annual Sum or Average 8760.00000 21.66110 52.50396 -0.6094 19.90502
Minimum of Months 672.00000 21.57378 41.33106 -1.3230 6.36067
Maximum of Months 744.00000 21.70802 59.68844 -0.1019 42.36766



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BANQUET_FLR_6 PEOPLE

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.57505 43.58572 0.33751 7.89443
February 672.00000 23.69079 45.70248 0.38221 8.34966
March 744.00000 23.64702 49.37276 0.40002 8.67373
April 720.00000 23.81761 52.87452 0.48813 10.15942
May 744.00000 23.84115 52.31346 -0.3838 8.26561
June 720.00000 23.88368 58.29462 -0.2999 7.01601
July 744.00000 23.91568 61.35082 -0.2490 6.36133
August 744.00000 23.90076 62.20300 -0.2519 6.40092
September 720.00000 23.86701 59.32709 -0.3062 7.11653
October 744.00000 23.84928 49.46476 0.48914 10.28709
November 720.00000 23.73555 44.51965 0.39201 8.53817
December 744.00000 23.64461 38.64604 0.32058 7.47386
           
Annual Sum or Average 8760.00000 23.78092 51.49364 0.10812 8.04044
Minimum of Months 672.00000 23.57505 38.64604 -0.3838 6.36133
Maximum of Months 744.00000 23.91568 62.20300 0.48914 10.28709



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DINING_FLR_6 PEOPLE

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.72430 42.59859 0.40762 8.88398
February 672.00000 23.82654 44.67391 0.45008 9.46197
March 744.00000 23.79497 48.30998 0.47103 9.87543
April 720.00000 23.90932 51.93407 0.54411 11.32326
May 744.00000 23.92435 51.39997 -0.3049 7.05288
June 720.00000 23.94492 57.47933 -0.2314 6.19890
July 744.00000 23.96066 60.62561 -0.1892 5.78340
August 744.00000 23.94905 61.47847 -0.1921 5.81025
September 720.00000 23.92904 58.52062 -0.2396 6.30340
October 744.00000 23.91538 48.70152 0.53506 11.23327
November 720.00000 23.85040 43.57295 0.45305 9.55964
December 744.00000 23.78321 37.68932 0.38782 8.40408
           
Annual Sum or Average 8760.00000 23.87606 50.60544 0.17250 8.31461
Minimum of Months 672.00000 23.72430 37.68932 -0.3049 5.78340
Maximum of Months 744.00000 23.96066 61.47847 0.54411 11.32326



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: KITCHEN_FLR_6 PEOPLE

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.65061 41.21549 1.04144 31.19664
February 672.00000 23.78146 43.32618 1.08362 32.16790
March 744.00000 23.70126 46.86036 1.09361 33.10374
April 720.00000 23.85291 50.77485 1.18769 36.49960
May 744.00000 23.85591 50.38620 0.60430 17.33908
June 720.00000 23.89545 56.52984 0.68833 19.11577
July 744.00000 23.91754 59.67061 0.74629 20.59472
August 744.00000 23.91954 60.39953 0.75203 20.71707
September 720.00000 23.89992 57.34976 0.69263 19.14184
October 744.00000 23.88824 47.73652 1.18804 36.40737
November 720.00000 23.79651 42.32903 1.09151 32.48869
December 744.00000 23.68910 36.43494 1.01837 29.96426
           
Annual Sum or Average 8760.00000 23.82058 49.44233 0.93127 27.36188
Minimum of Months 672.00000 23.65061 36.43494 0.60430 17.33908
Maximum of Months 744.00000 23.91954 60.39953 1.18804 36.49960



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: STORAGE_FLR_1 PEOPLE

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.62250 39.68839 -0.2513 6.86875
February 672.00000 21.70208 42.65449 -0.2150 6.13256
March 744.00000 21.53563 46.78791 -0.2318 6.43540
April 720.00000 21.96911 50.62649 -0.0987 5.45210
May 744.00000 22.13654 49.82393 -1.1511 33.05263
June 720.00000 22.50090 55.77181 -0.9840 25.59939
July 744.00000 22.79147 58.61236 -0.8615 20.74779
August 744.00000 22.77788 59.59162 -0.8605 20.69554
September 720.00000 22.59527 56.57639 -0.9451 24.01676
October 744.00000 22.69077 45.50122 0.05477 5.41698
November 720.00000 22.05247 40.72052 -0.1381 5.64090
December 744.00000 21.77353 34.05953 -0.2476 6.57445
           
Annual Sum or Average 8760.00000 22.18183 48.38684 -0.4959 13.93568
Minimum of Months 672.00000 21.53563 34.05953 -1.1511 5.41698
Maximum of Months 744.00000 22.79147 59.59162 0.05477 33.05263



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORRIDOR_FLR_3 PEOPLE

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.74147 42.85953 -0.2188 6.40453
February 672.00000 21.80111 45.87057 -0.1886 5.87204
March 744.00000 21.60511 49.98391 -0.2115 6.20568
April 720.00000 22.01938 53.88869 -0.0840 5.37822
May 744.00000 22.08528 53.37595 -1.1739 34.15692
June 720.00000 22.36432 59.62078 -1.0354 27.80099
July 744.00000 22.70001 62.25122 -0.8974 22.08311
August 744.00000 22.79424 62.84957 -0.8598 20.65703
September 720.00000 22.59873 59.96476 -0.9487 24.14081
October 744.00000 22.73215 48.84501 0.06804 5.40096
November 720.00000 22.15138 43.96845 -0.1111 5.44964
December 744.00000 21.95385 37.18295 -0.2013 6.04995
           
Annual Sum or Average 8760.00000 22.21485 51.74095 -0.4904 14.18414
Minimum of Months 672.00000 21.60511 37.18295 -1.1739 5.37822
Maximum of Months 744.00000 22.79424 62.84957 0.06804 34.15692



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORRIDOR_FLR_6 PEOPLE

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.69899 40.62921 -0.2098 6.48145
February 672.00000 21.67788 43.76412 -0.1964 6.13304
March 744.00000 21.61950 47.63275 -0.1880 6.20022
April 720.00000 22.12179 51.26600 -0.0336 5.41395
May 744.00000 22.12842 50.88964 -1.1162 31.64688
June 720.00000 22.49697 56.84367 -0.9432 24.15374
July 744.00000 22.85602 59.34093 -0.7946 18.50471
August 744.00000 22.93537 59.96050 -0.7620 17.42553
September 720.00000 22.65430 57.41890 -0.8824 21.83438
October 744.00000 22.70008 46.51344 0.08846 5.71375
November 720.00000 21.97317 41.94534 -0.1307 5.73364
December 744.00000 21.77984 35.19474 -0.2219 6.40837
           
Annual Sum or Average 8760.00000 22.22365 49.30030 -0.4507 13.01261
Minimum of Months 672.00000 21.61950 35.19474 -1.1162 5.41395
Maximum of Months 744.00000 22.93537 59.96050 0.08846 31.64688



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: MECH_FLR_1 PEOPLE

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.83720 38.80415 -0.2049 6.51007
February 672.00000 21.95755 41.65573 -0.1603 5.73055
March 744.00000 21.75904 45.80860 -0.1832 6.07641
April 720.00000 22.20318 49.56462 -0.0486 5.34874
May 744.00000 22.38587 48.73540 -1.0744 29.58712
June 720.00000 22.73757 54.63499 -0.9107 22.73690
July 744.00000 23.02572 57.44781 -0.7886 18.25918
August 744.00000 23.01398 58.40791 -0.7870 18.19118
September 720.00000 22.83095 55.42861 -0.8722 21.26466
October 744.00000 22.93628 44.47128 0.10790 5.63101
November 720.00000 22.30689 39.74842 -0.0836 5.42051
December 744.00000 22.02223 33.18419 -0.1943 6.12729
           
Annual Sum or Average 8760.00000 22.42071 47.34329 -0.4351 12.61761
Minimum of Months 672.00000 21.75904 33.18419 -1.0744 5.34874
Maximum of Months 744.00000 23.02572 58.40791 0.10790 29.58712



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.285484E+11 79200.93 15-JAN-09:52 665.32 0.126536E+12 0.00 0.155084E+12 4.11 4.72 01-JAN-00:10 0.00 0.00
February 0.187722E+11 75108.30 01-FEB-09:51 621.78 0.850174E+11 0.00 0.103790E+12 4.29 4.72 01-FEB-06:20 0.00 0.00
March 0.193802E+11 79977.75 23-MAR-15:03 649.28 0.871493E+11 0.00 0.106529E+12 4.05 4.72 01-MAR-06:13 0.00 0.00
April 0.359052E+11 76066.94 11-APR-15:03 711.90 0.158547E+12 0.00 0.194453E+12 4.52 4.72 01-APR-00:20 0.00 0.00
May 0.358357E+11 72045.15 04-MAY-15:03 742.76 0.159503E+12 0.00 0.195339E+12 4.55 4.72 01-MAY-23:03 0.00 0.00
June 0.587505E+11 91088.44 28-JUN-15:03 720.00 0.257147E+12 0.00 0.315898E+12 4.47 4.72 01-JUN-01:30 0.00 0.00
July 0.110353E+12 143215.80 19-JUL-15:03 744.00 0.474103E+12 0.00 0.584457E+12 4.38 4.71 06-JUL-01:00 0.00 0.00
August 0.123023E+12 149131.70 18-AUG-15:03 744.00 0.528604E+12 0.00 0.651627E+12 4.38 4.68 25-AUG-21:54 0.00 0.00
September 0.805852E+11 158580.33 29-SEP-15:03 720.00 0.344113E+12 0.00 0.424698E+12 4.42 4.72 03-SEP-01:15 0.00 0.00
October 0.914382E+11 161155.32 14-OCT-15:01 744.00 0.382069E+12 0.00 0.473508E+12 4.39 4.72 07-OCT-23:50 0.00 0.00
November 0.304435E+11 99142.86 19-NOV-09:41 698.07 0.135511E+12 0.00 0.165955E+12 4.46 4.72 01-NOV-03:05 0.00 0.00
December 0.318501E+11 92409.70 05-DEC-09:41 685.11 0.140292E+12 0.00 0.172142E+12 4.23 4.72 01-DEC-00:03 0.00 0.00
                         
Annual Sum or Average 0.664886E+12     8446.22 0.287859E+13 0.00 0.354348E+13 4.35     0.00 0.00
Minimum of Months 0.187722E+11 72045.15   621.78 0.850174E+11 0.00 0.103790E+12 4.05 4.68   0.00 0.00
Maximum of Months 0.123023E+12 161155.32   744.00 0.528604E+12 0.00 0.651627E+12 4.55 4.72   0.00 0.00



Table of Contents

Report: BoilerReportMonthly

For: HEATSYS1 BOILER

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO {Maximum} [] BOILER PART LOAD RATIO {TIMESTAMP}
January 0.102416E+12 0.00 528.26 150697.24 08-JAN-07:00 0.00 34.27 53.01 0.38 0.00 0.14 0.56 08-JAN-07:00
February 0.787413E+11 0.00 520.72 111145.59 05-FEB-06:00 0.00 32.76 53.47 0.31 0.00 0.12 0.41 05-FEB-06:00
March 0.109070E+12 0.00 579.91 140963.49 30-MAR-03:00 0.00 32.08 53.51 0.39 0.00 0.15 0.52 30-MAR-03:00
April 0.473046E+11 0.00 396.09 104882.63 01-APR-05:00 0.00 29.10 45.99 0.15 0.00 0.07 0.39 01-APR-05:00
May 0.413527E+11 0.00 361.91 94183.95 27-MAY-03:00 0.00 28.66 43.52 0.13 0.00 0.06 0.35 27-MAY-03:00
June 0.760673E+10 0.00 150.68 63484.44 13-JUN-04:00 0.00 28.21 35.11 0.02 0.00 0.01 0.23 13-JUN-04:00
July 0.502207E+09 0.00 36.94 27554.62 06-JUL-01:00 0.00 31.66 33.14 0.00 0.00 0.00 0.10 06-JUL-01:00
August 0.224273E+09 0.00 27.13 23836.50 28-AUG-08:54 0.00 37.32 38.24 0.00 0.00 0.00 0.09 28-AUG-08:54
September 0.347492E+10 0.00 81.09 60773.87 20-SEP-03:00 0.00 32.51 35.96 0.01 0.00 0.00 0.22 20-SEP-03:00
October 0.169191E+11 0.00 161.48 89873.17 28-OCT-05:00 0.00 32.51 38.83 0.05 0.00 0.02 0.33 28-OCT-05:00
November 0.661532E+11 0.00 449.38 102055.67 24-NOV-04:00 0.00 32.06 49.47 0.24 0.00 0.09 0.38 24-NOV-04:00
December 0.991097E+11 0.00 510.17 116502.45 23-DEC-06:00 0.00 34.78 52.59 0.37 0.00 0.14 0.43 23-DEC-06:00
                           
Annual Sum or Average 0.572874E+12 0.00 3803.77     0.00 32.17 44.36 0.17 0.00 0.07    
Minimum of Months 0.224273E+09 0.00 27.13 23836.50   0.00 28.21 33.14 0.00 0.00 0.00 0.09  
Maximum of Months 0.109070E+12 0.00 579.91 150697.24   0.00 37.32 53.51 0.39 0.00 0.15 0.56  



Table of Contents

Report: DXReportMonthly

For: FLR_3_DOAS COOLING COIL

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.352394E+10 0.00 171.17 0.349904E+10 0.00 0.00 0.00 0.00 20570.98 13-JAN-14:00 20570.98 13-JAN-14:00 0.00 0.00 0.00
February 0.189616E+10 0.00 130.67 0.184036E+10 0.00 0.00 0.00 0.00 17583.23 01-FEB-09:53 17583.23 01-FEB-09:53 0.00 0.00 0.00
March 0.213914E+10 0.00 109.83 0.197595E+10 0.00 0.00 0.00 0.00 22012.17 22-MAR-13:00 17622.52 11-MAR-11:00 0.00 0.00 0.00
April 0.536108E+10 0.00 211.67 0.504766E+10 0.00 0.00 0.00 0.00 22090.96 26-APR-13:00 22090.96 26-APR-13:00 0.00 0.00 0.00
May 0.568444E+10 0.00 273.33 0.557746E+10 0.00 0.00 0.00 0.00 18829.64 04-MAY-13:00 17662.38 03-MAY-12:50 0.00 0.00 0.00
June 0.127679E+11 0.00 460.00 0.101514E+11 0.00 0.00 0.00 0.00 30817.80 29-JUN-12:15 17826.82 29-JUN-12:15 0.00 0.00 0.00
July 0.285718E+11 0.00 581.00 0.167816E+11 0.00 0.00 0.00 0.00 40153.36 31-JUL-12:50 23766.73 31-JUL-12:30 0.00 0.00 0.00
August 0.326065E+11 0.00 582.67 0.176854E+11 0.00 0.00 0.00 0.00 38729.91 14-AUG-10:00 22286.10 18-AUG-12:20 0.00 0.00 0.00
September 0.185738E+11 0.00 518.17 0.130116E+11 0.00 0.00 0.00 0.00 39619.58 22-SEP-12:15 35123.90 29-SEP-13:00 0.00 0.00 0.00
October 0.206208E+11 0.00 461.00 0.151880E+11 0.00 0.00 0.00 0.00 38860.24 01-OCT-12:10 34150.37 16-OCT-12:20 0.00 0.00 0.00
November 0.354751E+10 0.00 209.17 0.347968E+10 0.00 0.00 0.00 0.00 21516.80 19-NOV-13:05 21516.80 19-NOV-13:05 0.00 0.00 0.00
December 0.428641E+10 0.00 177.33 0.428428E+10 0.00 0.00 0.00 0.00 20480.92 05-DEC-09:55 20480.92 05-DEC-09:55 0.00 0.00 0.00
                               
Annual Sum or Average 0.139579E+12 0.00 3886.00 0.985224E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.189616E+10 0.00 109.83 0.184036E+10 0.00 0.00 0.00 0.00 17583.23   17583.23   0.00 0.00 0.00
Maximum of Months 0.326065E+11 0.00 582.67 0.176854E+11 0.00 0.00 0.00 0.00 40153.36   35123.90   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV WITH REHEAT COOLING COIL

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.580356E+11 0.00 286.14 0.578582E+11 0.00 0.00 0.00 0.00 209507.34 14-JAN-11:45 209507.34 14-JAN-11:45 0.00 0.00 0.00
February 0.325376E+11 0.00 233.58 0.317867E+11 0.00 0.00 0.00 0.00 197645.24 01-FEB-11:45 197645.24 01-FEB-11:45 0.00 0.00 0.00
March 0.360422E+11 0.00 212.67 0.353849E+11 0.00 0.00 0.00 0.00 182548.43 23-MAR-10:45 176939.84 11-MAR-11:45 0.00 0.00 0.00
April 0.856442E+11 0.00 357.56 0.841340E+11 0.00 0.00 0.00 0.00 248801.82 26-APR-10:45 208737.88 30-APR-10:45 0.00 0.00 0.00
May 0.916843E+11 0.00 436.17 0.907220E+11 0.00 0.00 0.00 0.00 160265.73 18-MAY-10:45 157876.76 04-MAY-12:00 0.00 0.00 0.00
June 0.168981E+12 0.00 613.67 0.147634E+12 0.00 0.00 0.00 0.00 311545.41 29-JUN-10:45 192253.53 29-JUN-10:45 0.00 0.00 0.00
July 0.344845E+12 0.00 735.17 0.225519E+12 0.00 0.00 0.00 0.00 379846.46 31-JUL-10:45 241704.35 19-JUL-10:45 0.00 0.00 0.00
August 0.388248E+12 0.00 736.67 0.235368E+12 0.00 0.00 0.00 0.00 407055.93 14-AUG-10:45 241645.37 14-AUG-10:45 0.00 0.00 0.00
September 0.229551E+12 0.00 674.83 0.177330E+12 0.00 0.00 0.00 0.00 373451.97 22-SEP-12:00 363907.17 29-SEP-10:50 0.00 0.00 0.00
October 0.260147E+12 0.00 618.00 0.209800E+12 0.00 0.00 0.00 0.00 383393.45 16-OCT-10:45 383393.45 16-OCT-10:45 0.00 0.00 0.00
November 0.605792E+11 0.00 343.08 0.598840E+11 0.00 0.00 0.00 0.00 214444.18 19-NOV-11:45 214444.18 19-NOV-11:45 0.00 0.00 0.00
December 0.668534E+11 0.00 297.46 0.668534E+11 0.00 0.00 0.00 0.00 193632.86 19-DEC-11:45 193632.86 19-DEC-11:45 0.00 0.00 0.00
                               
Annual Sum or Average 0.182315E+13 0.00 5544.99 0.142227E+13 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.325376E+11 0.00 212.67 0.317867E+11 0.00 0.00 0.00 0.00 160265.73   157876.76   0.00 0.00 0.00
Maximum of Months 0.388248E+12 0.00 736.67 0.235368E+12 0.00 0.00 0.00 0.00 407055.93   383393.45   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_1_FLR_3 FAN COIL COOLING COIL

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.217582E+10 0.00 435.80 0.109536E+10 0.00 0.00 0.00 0.00 14065.88 21-JAN-09:02 14046.92 15-JAN-16:01 0.00 0.00 0.00
February 0.194204E+10 0.00 365.23 0.103107E+10 0.00 0.00 0.00 0.00 14877.07 13-FEB-16:02 14041.95 06-FEB-16:01 0.00 0.00 0.00
March 0.211089E+10 0.00 381.84 0.957685E+09 0.00 0.00 0.00 0.00 14078.98 17-MAR-15:01 12633.42 05-MAR-16:01 0.00 0.00 0.00
April 0.416899E+10 0.00 570.04 0.200237E+10 0.00 0.00 0.00 0.00 13979.96 08-APR-08:61 13646.88 01-APR-18:02 0.00 0.00 0.00
May 0.391154E+10 0.00 579.68 0.178067E+10 0.00 0.00 0.00 0.00 14181.44 06-MAY-08:62 13407.16 24-MAY-08:62 0.00 0.00 0.00
June 0.547476E+10 0.00 618.30 0.251281E+10 0.00 0.00 0.00 0.00 14344.78 16-JUN-15:01 12764.03 28-JUN-18:01 0.00 0.00 0.00
July 0.761582E+10 0.00 681.60 0.370226E+10 0.00 0.00 0.00 0.00 14677.75 30-JUL-08:61 12713.74 02-JUL-18:01 0.00 0.00 0.00
August 0.786608E+10 0.00 690.17 0.386137E+10 0.00 0.00 0.00 0.00 14919.63 18-AUG-08:61 12784.20 17-AUG-18:02 0.00 0.00 0.00
September 0.624545E+10 0.00 650.22 0.296698E+10 0.00 0.00 0.00 0.00 14690.72 23-SEP-08:62 12731.47 24-SEP-15:01 0.00 0.00 0.00
October 0.568310E+10 0.00 649.50 0.330525E+10 0.00 0.00 0.00 0.00 14855.68 01-OCT-08:61 14046.40 25-OCT-18:01 0.00 0.00 0.00
November 0.292420E+10 0.00 513.31 0.151173E+10 0.00 0.00 0.00 0.00 14694.74 12-NOV-09:02 14041.50 30-NOV-16:01 0.00 0.00 0.00
December 0.243721E+10 0.00 458.66 0.164179E+10 0.00 0.00 0.00 0.00 14045.90 25-DEC-16:01 14045.90 25-DEC-16:01 0.00 0.00 0.00
                               
Annual Sum or Average 0.525559E+11 0.00 6594.36 0.263693E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.194204E+10 0.00 365.23 0.957685E+09 0.00 0.00 0.00 0.00 13979.96   12633.42   0.00 0.00 0.00
Maximum of Months 0.786608E+10 0.00 690.17 0.386137E+10 0.00 0.00 0.00 0.00 14919.63   14046.92   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_2_FLR_3 FAN COIL COOLING COIL

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.521995E+09 0.00 190.04 0.228927E+09 0.00 0.00 0.00 0.00 13786.68 20-JAN-19:01 13527.29 15-JAN-16:01 0.00 0.00 0.00
February 0.698535E+09 0.00 202.77 0.299410E+09 0.00 0.00 0.00 0.00 14158.78 13-FEB-16:02 13522.47 06-FEB-16:01 0.00 0.00 0.00
March 0.982138E+09 0.00 254.16 0.364959E+09 0.00 0.00 0.00 0.00 13823.06 22-MAR-18:51 12264.45 24-MAR-15:01 0.00 0.00 0.00
April 0.245637E+10 0.00 428.17 0.950917E+09 0.00 0.00 0.00 0.00 14728.05 26-APR-21:51 13295.78 19-APR-18:01 0.00 0.00 0.00
May 0.271019E+10 0.00 446.30 0.108959E+10 0.00 0.00 0.00 0.00 14282.87 03-MAY-21:51 13002.61 24-MAY-08:51 0.00 0.00 0.00
June 0.354110E+10 0.00 401.63 0.155581E+10 0.00 0.00 0.00 0.00 15246.55 28-JUN-21:51 12428.91 04-JUN-19:31 0.00 0.00 0.00
July 0.496058E+10 0.00 418.65 0.247115E+10 0.00 0.00 0.00 0.00 15402.26 27-JUL-21:51 12011.66 08-JUL-21:11 0.00 0.00 0.00
August 0.468699E+10 0.00 413.60 0.224037E+10 0.00 0.00 0.00 0.00 15277.88 16-AUG-21:51 11905.25 05-AUG-15:01 0.00 0.00 0.00
September 0.344084E+10 0.00 403.80 0.144153E+10 0.00 0.00 0.00 0.00 14835.65 30-SEP-21:51 12195.59 18-SEP-15:01 0.00 0.00 0.00
October 0.270654E+10 0.00 397.78 0.143225E+10 0.00 0.00 0.00 0.00 15243.46 01-OCT-08:51 13999.46 14-OCT-08:61 0.00 0.00 0.00
November 0.942833E+09 0.00 299.71 0.380427E+09 0.00 0.00 0.00 0.00 14148.95 12-NOV-09:02 13521.86 30-NOV-16:01 0.00 0.00 0.00
December 0.548646E+09 0.00 204.03 0.337562E+09 0.00 0.00 0.00 0.00 13652.50 09-DEC-16:01 13526.32 30-DEC-16:01 0.00 0.00 0.00
                               
Annual Sum or Average 0.281968E+11 0.00 4060.62 0.127929E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.521995E+09 0.00 190.04 0.228927E+09 0.00 0.00 0.00 0.00 13652.50   11905.25   0.00 0.00 0.00
Maximum of Months 0.496058E+10 0.00 446.30 0.247115E+10 0.00 0.00 0.00 0.00 15402.26   13999.46   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.349880E+11 0.00 586.14 0.222311E+11 0.00 0.00 0.00 0.00 45911.75 14-JAN-12:40 44584.32 14-JAN-13:30 0.00 0.00 0.00
February 0.224363E+11 0.00 447.90 0.135836E+11 0.00 0.00 0.00 0.00 41052.07 02-FEB-12:30 35743.23 02-FEB-12:30 0.00 0.00 0.00
March 0.169593E+11 0.00 437.03 0.664649E+10 0.00 0.00 0.00 0.00 33759.25 11-MAR-13:10 26269.95 11-MAR-13:00 0.00 0.00 0.00
April 0.192376E+11 0.00 536.01 0.631212E+10 0.00 0.00 0.00 0.00 25503.97 08-APR-12:40 13496.46 08-APR-12:50 0.00 0.00 0.00
May 0.116634E+11 0.00 486.00 0.266746E+10 0.00 0.00 0.00 0.00 22143.80 03-MAY-15:03 9960.59 03-MAY-15:03 0.00 0.00 0.00
June 0.153682E+11 0.00 559.20 0.361980E+10 0.00 0.00 0.00 0.00 20191.17 30-JUN-15:06 7754.73 30-JUN-15:06 0.00 0.00 0.00
July 0.235361E+11 0.00 686.54 0.664315E+10 0.00 0.00 0.00 0.00 24176.11 19-JUL-15:03 10746.75 19-JUL-15:03 0.00 0.00 0.00
August 0.312057E+11 0.00 736.38 0.105790E+11 0.00 0.00 0.00 0.00 24264.48 30-AUG-12:40 12224.75 30-AUG-13:00 0.00 0.00 0.00
September 0.343521E+11 0.00 704.95 0.144281E+11 0.00 0.00 0.00 0.00 42176.75 30-SEP-13:10 39301.51 30-SEP-13:05 0.00 0.00 0.00
October 0.431468E+11 0.00 697.63 0.252556E+11 0.00 0.00 0.00 0.00 51201.35 16-OCT-12:20 44345.51 31-OCT-14:00 0.00 0.00 0.00
November 0.356447E+11 0.00 605.65 0.227021E+11 0.00 0.00 0.00 0.00 48465.61 19-NOV-09:53 44332.12 19-NOV-10:50 0.00 0.00 0.00
December 0.389257E+11 0.00 606.77 0.288208E+11 0.00 0.00 0.00 0.00 46123.66 19-DEC-13:00 46123.66 19-DEC-13:00 0.00 0.00 0.00
                               
Annual Sum or Average 0.327464E+12 0.00 7090.20 0.163489E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.116634E+11 0.00 437.03 0.266746E+10 0.00 0.00 0.00 0.00 20191.17   7754.73   0.00 0.00 0.00
Maximum of Months 0.431468E+11 0.00 736.38 0.288208E+11 0.00 0.00 0.00 0.00 51201.35   46123.66   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.112394E+11 0.00 326.28 0.556612E+10 0.00 0.00 0.00 0.00 84417.85 20-JAN-19:01 81522.86 16-JAN-09:02 0.00 0.00 0.00
February 0.127748E+11 0.00 385.89 0.582245E+10 0.00 0.00 0.00 0.00 82887.72 13-FEB-21:12 80336.20 04-FEB-19:02 0.00 0.00 0.00
March 0.158503E+11 0.00 400.95 0.683492E+10 0.00 0.00 0.00 0.00 81831.23 22-MAR-18:51 74431.68 04-MAR-09:01 0.00 0.00 0.00
April 0.232985E+11 0.00 412.83 0.113024E+11 0.00 0.00 0.00 0.00 89070.55 26-APR-21:51 79596.67 01-APR-21:52 0.00 0.00 0.00
May 0.274870E+11 0.00 410.02 0.145838E+11 0.00 0.00 0.00 0.00 86991.28 04-MAY-21:51 78749.58 24-MAY-08:51 0.00 0.00 0.00
June 0.309735E+11 0.00 348.42 0.172939E+11 0.00 0.00 0.00 0.00 92204.57 28-JUN-21:51 75993.05 22-JUN-20:11 0.00 0.00 0.00
July 0.370193E+11 0.00 361.98 0.213356E+11 0.00 0.00 0.00 0.00 93941.08 19-JUL-21:51 74878.64 04-JUL-08:51 0.00 0.00 0.00
August 0.342596E+11 0.00 349.54 0.188249E+11 0.00 0.00 0.00 0.00 92936.58 16-AUG-21:51 73916.54 22-AUG-15:01 0.00 0.00 0.00
September 0.272320E+11 0.00 329.62 0.140358E+11 0.00 0.00 0.00 0.00 92429.37 22-SEP-21:52 74458.91 02-SEP-15:01 0.00 0.00 0.00
October 0.244003E+11 0.00 355.43 0.152848E+11 0.00 0.00 0.00 0.00 91980.68 01-OCT-08:51 85611.40 14-OCT-08:61 0.00 0.00 0.00
November 0.145310E+11 0.00 391.80 0.720263E+10 0.00 0.00 0.00 0.00 84739.39 09-NOV-22:53 80721.84 28-NOV-19:01 0.00 0.00 0.00
December 0.104317E+11 0.00 338.68 0.624003E+10 0.00 0.00 0.00 0.00 81079.44 19-DEC-19:01 81079.44 19-DEC-19:01 0.00 0.00 0.00
                               
Annual Sum or Average 0.269497E+12 0.00 4411.44 0.144327E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.104317E+11 0.00 326.28 0.556612E+10 0.00 0.00 0.00 0.00 81079.44   73916.54   0.00 0.00 0.00
Maximum of Months 0.370193E+11 0.00 412.83 0.213356E+11 0.00 0.00 0.00 0.00 93941.08   85611.40   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_5_FLR_3 FAN COIL COOLING COIL

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.231069E+10 0.00 456.13 0.129191E+10 0.00 0.00 0.00 0.00 12491.48 15-JAN-16:01 12491.48 15-JAN-16:01 0.00 0.00 0.00
February 0.182485E+10 0.00 348.72 0.102593E+10 0.00 0.00 0.00 0.00 12872.66 13-FEB-16:02 12489.20 05-FEB-09:01 0.00 0.00 0.00
March 0.208244E+10 0.00 382.51 0.958866E+09 0.00 0.00 0.00 0.00 12345.24 15-MAR-15:01 11292.19 19-MAR-18:01 0.00 0.00 0.00
April 0.380804E+10 0.00 582.97 0.182211E+10 0.00 0.00 0.00 0.00 12488.46 02-APR-08:62 12488.46 02-APR-08:62 0.00 0.00 0.00
May 0.338270E+10 0.00 574.61 0.153054E+10 0.00 0.00 0.00 0.00 12733.83 06-MAY-08:62 12484.25 24-MAY-08:62 0.00 0.00 0.00
June 0.468018E+10 0.00 630.11 0.209351E+10 0.00 0.00 0.00 0.00 12843.80 28-JUN-08:62 11361.38 05-JUN-15:01 0.00 0.00 0.00
July 0.698008E+10 0.00 706.04 0.335747E+10 0.00 0.00 0.00 0.00 12480.99 13-JUL-18:01 11370.12 16-JUL-08:61 0.00 0.00 0.00
August 0.751455E+10 0.00 710.03 0.368507E+10 0.00 0.00 0.00 0.00 12774.71 08-AUG-08:62 11361.48 14-AUG-08:61 0.00 0.00 0.00
September 0.542190E+10 0.00 654.26 0.251212E+10 0.00 0.00 0.00 0.00 13146.25 23-SEP-08:62 11338.22 23-SEP-15:01 0.00 0.00 0.00
October 0.540079E+10 0.00 654.46 0.319977E+10 0.00 0.00 0.00 0.00 13245.24 01-OCT-08:61 12490.76 25-OCT-18:01 0.00 0.00 0.00
November 0.272858E+10 0.00 514.71 0.153145E+10 0.00 0.00 0.00 0.00 13097.02 12-NOV-09:02 12487.06 30-NOV-16:01 0.00 0.00 0.00
December 0.244847E+10 0.00 468.76 0.176044E+10 0.00 0.00 0.00 0.00 12492.10 31-DEC-09:01 12492.10 31-DEC-09:01 0.00 0.00 0.00
                               
Annual Sum or Average 0.485833E+11 0.00 6683.30 0.247692E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.182485E+10 0.00 348.72 0.958866E+09 0.00 0.00 0.00 0.00 12345.24   11292.19   0.00 0.00 0.00
Maximum of Months 0.751455E+10 0.00 710.03 0.368507E+10 0.00 0.00 0.00 0.00 13245.24   12492.10   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_6_FLR_3 FAN COIL COOLING COIL

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.663480E+09 0.00 182.92 0.339008E+09 0.00 0.00 0.00 0.00 12316.20 20-JAN-19:01 11948.88 14-JAN-16:01 0.00 0.00 0.00
February 0.691428E+09 0.00 176.39 0.350155E+09 0.00 0.00 0.00 0.00 12281.95 14-FEB-09:02 12151.15 03-FEB-09:51 0.00 0.00 0.00
March 0.103991E+10 0.00 248.83 0.447134E+09 0.00 0.00 0.00 0.00 11948.53 22-MAR-18:51 11523.67 23-MAR-08:51 0.00 0.00 0.00
April 0.236595E+10 0.00 435.00 0.109464E+10 0.00 0.00 0.00 0.00 12915.78 02-APR-08:51 12915.78 02-APR-08:51 0.00 0.00 0.00
May 0.244546E+10 0.00 449.24 0.109221E+10 0.00 0.00 0.00 0.00 13280.02 24-MAY-08:51 13280.02 24-MAY-08:51 0.00 0.00 0.00
June 0.317484E+10 0.00 417.81 0.142490E+10 0.00 0.00 0.00 0.00 13827.31 30-JUN-08:51 12248.35 23-JUN-08:51 0.00 0.00 0.00
July 0.466603E+10 0.00 433.56 0.228889E+10 0.00 0.00 0.00 0.00 14256.45 30-JUL-08:51 12105.73 10-JUL-08:51 0.00 0.00 0.00
August 0.458466E+10 0.00 433.90 0.221183E+10 0.00 0.00 0.00 0.00 14441.91 18-AUG-08:51 11941.13 22-AUG-08:51 0.00 0.00 0.00
September 0.289995E+10 0.00 416.96 0.128076E+10 0.00 0.00 0.00 0.00 14044.57 10-SEP-08:51 11945.97 12-SEP-08:51 0.00 0.00 0.00
October 0.253603E+10 0.00 407.62 0.145230E+10 0.00 0.00 0.00 0.00 13924.00 17-OCT-08:21 13924.00 17-OCT-08:21 0.00 0.00 0.00
November 0.902726E+09 0.00 245.96 0.435849E+09 0.00 0.00 0.00 0.00 12597.05 12-NOV-09:02 12007.04 28-NOV-09:51 0.00 0.00 0.00
December 0.583149E+09 0.00 185.81 0.382934E+09 0.00 0.00 0.00 0.00 12691.91 05-DEC-09:41 12691.91 05-DEC-09:41 0.00 0.00 0.00
                               
Annual Sum or Average 0.265536E+11 0.00 4034.01 0.128006E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.583149E+09 0.00 176.39 0.339008E+09 0.00 0.00 0.00 0.00 11948.53   11523.67   0.00 0.00 0.00
Maximum of Months 0.466603E+10 0.00 449.24 0.228889E+10 0.00 0.00 0.00 0.00 14441.91   13924.00   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_1_FLR_6 FAN COIL COOLING COIL

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.456990E+09 0.00 345.60 0.243220E+09 0.00 0.00 0.00 0.00 3869.35 21-JAN-09:02 3637.31 15-JAN-16:01 0.00 0.00 0.00
February 0.414317E+09 0.00 263.12 0.230542E+09 0.00 0.00 0.00 0.00 3874.95 13-FEB-16:02 3636.22 06-FEB-16:01 0.00 0.00 0.00
March 0.487631E+09 0.00 291.79 0.240857E+09 0.00 0.00 0.00 0.00 3704.74 24-MAR-08:61 3309.44 05-MAR-16:01 0.00 0.00 0.00
April 0.100095E+10 0.00 509.43 0.513319E+09 0.00 0.00 0.00 0.00 3749.09 08-APR-08:61 3566.51 01-APR-18:02 0.00 0.00 0.00
May 0.919590E+09 0.00 512.87 0.443929E+09 0.00 0.00 0.00 0.00 3906.32 06-MAY-08:62 3445.50 24-MAY-08:62 0.00 0.00 0.00
June 0.133862E+10 0.00 605.90 0.644247E+09 0.00 0.00 0.00 0.00 3839.35 28-JUN-08:62 3299.84 01-JUN-18:01 0.00 0.00 0.00
July 0.191430E+10 0.00 688.99 0.957401E+09 0.00 0.00 0.00 0.00 3937.62 30-JUL-08:61 3285.13 03-JUL-18:01 0.00 0.00 0.00
August 0.195070E+10 0.00 689.28 0.978414E+09 0.00 0.00 0.00 0.00 4077.06 06-AUG-08:61 3312.25 21-AUG-18:02 0.00 0.00 0.00
September 0.147110E+10 0.00 642.60 0.715491E+09 0.00 0.00 0.00 0.00 3964.62 23-SEP-08:62 3310.11 04-SEP-18:01 0.00 0.00 0.00
October 0.128912E+10 0.00 590.61 0.759074E+09 0.00 0.00 0.00 0.00 4008.58 01-OCT-08:61 3637.22 25-OCT-18:01 0.00 0.00 0.00
November 0.601801E+09 0.00 403.21 0.319591E+09 0.00 0.00 0.00 0.00 3793.52 11-NOV-16:01 3636.07 30-NOV-16:01 0.00 0.00 0.00
December 0.503022E+09 0.00 363.96 0.351616E+09 0.00 0.00 0.00 0.00 3663.19 08-DEC-16:01 3637.33 25-DEC-16:01 0.00 0.00 0.00
                               
Annual Sum or Average 0.123481E+11 0.00 5907.37 0.639770E+10 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.414317E+09 0.00 263.12 0.230542E+09 0.00 0.00 0.00 0.00 3663.19   3285.13   0.00 0.00 0.00
Maximum of Months 0.195070E+10 0.00 689.28 0.978414E+09 0.00 0.00 0.00 0.00 4077.06   3637.33   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_2_FLR_6 FAN COIL COOLING COIL

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 84301365.31 0.00 98.18 42469656.99 0.00 0.00 0.00 0.00 3603.71 21-JAN-09:02 3494.74 15-JAN-16:01 0.00 0.00 0.00
February 0.123064E+09 0.00 125.55 56183407.41 0.00 0.00 0.00 0.00 3676.11 13-FEB-16:02 3493.67 06-FEB-16:01 0.00 0.00 0.00
March 0.207399E+09 0.00 172.73 84172204.53 0.00 0.00 0.00 0.00 3635.98 22-MAR-18:51 3224.55 19-MAR-18:11 0.00 0.00 0.00
April 0.571078E+09 0.00 370.22 0.237022E+09 0.00 0.00 0.00 0.00 3910.07 26-APR-21:51 3538.01 23-APR-18:11 0.00 0.00 0.00
May 0.634359E+09 0.00 409.56 0.271321E+09 0.00 0.00 0.00 0.00 3786.08 03-MAY-21:51 3414.00 19-MAY-18:51 0.00 0.00 0.00
June 0.913856E+09 0.00 403.46 0.415953E+09 0.00 0.00 0.00 0.00 4050.07 28-JUN-21:51 3306.57 04-JUN-19:31 0.00 0.00 0.00
July 0.133429E+10 0.00 423.33 0.682477E+09 0.00 0.00 0.00 0.00 4080.47 27-JUL-21:51 3167.36 08-JUL-21:11 0.00 0.00 0.00
August 0.122716E+10 0.00 419.09 0.596903E+09 0.00 0.00 0.00 0.00 4047.79 16-AUG-21:51 3075.31 21-AUG-20:11 0.00 0.00 0.00
September 0.809247E+09 0.00 410.87 0.338812E+09 0.00 0.00 0.00 0.00 3897.61 07-SEP-21:51 3164.52 21-SEP-15:02 0.00 0.00 0.00
October 0.582619E+09 0.00 344.49 0.315290E+09 0.00 0.00 0.00 0.00 4009.82 01-OCT-08:51 3528.97 14-OCT-08:61 0.00 0.00 0.00
November 0.142848E+09 0.00 176.12 61383988.53 0.00 0.00 0.00 0.00 3637.56 11-NOV-16:01 3493.55 30-NOV-16:01 0.00 0.00 0.00
December 77968184.67 0.00 98.90 54217173.59 0.00 0.00 0.00 0.00 3562.77 09-DEC-16:01 3494.61 30-DEC-16:01 0.00 0.00 0.00
                               
Annual Sum or Average 0.670819E+10 0.00 3452.52 0.315620E+10 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 77968184.67 0.00 98.18 42469656.99 0.00 0.00 0.00 0.00 3562.77   3075.31   0.00 0.00 0.00
Maximum of Months 0.133429E+10 0.00 423.33 0.682477E+09 0.00 0.00 0.00 0.00 4080.47   3538.01   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.764340E+10 0.00 584.43 0.536691E+10 0.00 0.00 0.00 0.00 17169.90 14-JAN-19:01 17169.90 14-JAN-19:01 0.00 0.00 0.00
February 0.510830E+10 0.00 470.44 0.336316E+10 0.00 0.00 0.00 0.00 17984.72 13-FEB-16:02 17169.64 06-FEB-16:01 0.00 0.00 0.00
March 0.447999E+10 0.00 454.04 0.236354E+10 0.00 0.00 0.00 0.00 17394.28 20-MAR-15:01 15583.40 24-MAR-18:01 0.00 0.00 0.00
April 0.540427E+10 0.00 572.13 0.248549E+10 0.00 0.00 0.00 0.00 17237.19 22-APR-15:01 16896.83 01-APR-18:02 0.00 0.00 0.00
May 0.351121E+10 0.00 511.30 0.132494E+10 0.00 0.00 0.00 0.00 17475.51 06-MAY-08:62 16048.13 24-MAY-08:62 0.00 0.00 0.00
June 0.465700E+10 0.00 578.96 0.169646E+10 0.00 0.00 0.00 0.00 17886.05 16-JUN-15:01 15640.34 12-JUN-15:01 0.00 0.00 0.00
July 0.724628E+10 0.00 659.51 0.293536E+10 0.00 0.00 0.00 0.00 18601.18 30-JUL-08:61 15621.99 15-JUL-15:01 0.00 0.00 0.00
August 0.904042E+10 0.00 679.22 0.399167E+10 0.00 0.00 0.00 0.00 18773.94 20-AUG-08:61 15414.02 19-AUG-18:01 0.00 0.00 0.00
September 0.883538E+10 0.00 644.77 0.442872E+10 0.00 0.00 0.00 0.00 18246.26 22-SEP-08:61 15523.09 21-SEP-15:02 0.00 0.00 0.00
October 0.101221E+11 0.00 664.89 0.681537E+10 0.00 0.00 0.00 0.00 18719.82 01-OCT-08:61 17170.23 25-OCT-18:01 0.00 0.00 0.00
November 0.782689E+10 0.00 613.09 0.534141E+10 0.00 0.00 0.00 0.00 17751.56 11-NOV-16:01 17167.29 30-NOV-16:01 0.00 0.00 0.00
December 0.817131E+10 0.00 596.07 0.651216E+10 0.00 0.00 0.00 0.00 17183.17 08-DEC-16:01 17171.09 05-DEC-19:01 0.00 0.00 0.00
                               
Annual Sum or Average 0.820465E+11 0.00 7028.86 0.466252E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.351121E+10 0.00 454.04 0.132494E+10 0.00 0.00 0.00 0.00 17169.90   15414.02   0.00 0.00 0.00
Maximum of Months 0.101221E+11 0.00 679.22 0.681537E+10 0.00 0.00 0.00 0.00 18773.94   17171.09   0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 691.88 507.95 183.94 1016.06 360.43 0.00 0.00 0.00
February 546.53 338.18 208.36 766.59 325.66 0.00 0.00 0.00
March 435.89 212.33 223.56 608.67 335.19 0.00 0.00 0.00
April 364.49 140.88 223.62 543.76 270.89 0.00 0.00 0.00
May 256.82 31.10 225.72 330.29 237.25 0.00 0.00 0.00
June 225.30 13.21 212.09 294.99 177.77 0.00 0.00 0.00
July 237.61 25.41 212.20 350.95 156.85 0.00 0.00 0.00
August 305.17 94.83 210.34 499.35 169.75 0.00 0.00 0.00
September 419.06 208.19 210.87 675.52 203.11 0.00 0.00 0.00
October 548.73 368.52 180.22 884.37 225.50 0.00 0.00 0.00
November 666.54 472.26 194.28 981.22 326.07 0.00 0.00 0.00
December 740.41 564.21 176.20 1092.89 362.23 0.00 0.00 0.00
                 
Annual Sum or Average 452.81 247.78 205.03 670.11 262.24 0.00 0.00 0.00
Minimum of Months 225.30 13.21 176.20 294.99 156.85 0.00 0.00 0.00
Maximum of Months 740.41 564.21 225.72 1092.89 362.23 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CAFE_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1948.30 1430.34 517.96 2821.82 1101.73 0.00 0.00 0.00
February 1539.00 952.28 586.71 2118.07 1013.97 0.00 0.00 0.00
March 1227.43 597.91 629.52 1675.39 1033.92 0.00 0.00 0.00
April 1026.39 396.71 629.69 1494.92 849.01 0.00 0.00 0.00
May 723.18 87.58 635.60 888.77 751.15 0.00 0.00 0.00
June 634.43 37.21 597.22 792.26 572.02 0.00 0.00 0.00
July 669.08 71.55 597.53 959.18 496.83 0.00 0.00 0.00
August 859.34 267.03 592.31 1383.61 531.54 0.00 0.00 0.00
September 1180.05 586.24 593.81 1876.55 634.94 0.00 0.00 0.00
October 1545.20 1037.72 507.48 2459.42 698.59 0.00 0.00 0.00
November 1876.94 1329.86 547.08 2721.72 1006.88 0.00 0.00 0.00
December 2084.94 1588.78 496.16 3036.85 1106.75 0.00 0.00 0.00
                 
Annual Sum or Average 1275.09 697.73 577.36 1851.63 815.38 0.00 0.00 0.00
Minimum of Months 634.43 37.21 496.16 792.26 496.83 0.00 0.00 0.00
Maximum of Months 2084.94 1588.78 635.60 3036.85 1106.75 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: LOBBY_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 2530.95 1858.09 672.86 3757.36 1452.67 0.00 0.00 0.00
February 1999.24 1237.07 762.17 2816.39 1356.61 0.00 0.00 0.00
March 1594.50 776.72 817.79 2227.13 1393.12 0.00 0.00 0.00
April 1333.34 515.34 818.00 1990.85 1141.24 0.00 0.00 0.00
May 939.45 113.77 825.68 1164.68 1032.70 0.00 0.00 0.00
June 824.17 48.34 775.83 1034.75 788.40 0.00 0.00 0.00
July 869.17 92.94 776.23 1266.53 678.72 0.00 0.00 0.00
August 1116.33 346.89 769.44 1844.60 710.09 0.00 0.00 0.00
September 1532.95 761.56 771.39 2502.63 841.59 0.00 0.00 0.00
October 2007.30 1348.05 659.24 3269.04 919.73 0.00 0.00 0.00
November 2438.25 1727.56 710.69 3619.17 1330.65 0.00 0.00 0.00
December 2708.45 2063.92 644.54 4037.76 1460.55 0.00 0.00 0.00
                 
Annual Sum or Average 1656.41 906.39 750.02 2459.89 1090.73 0.00 0.00 0.00
Minimum of Months 824.17 48.34 644.54 1034.75 678.72 0.00 0.00 0.00
Maximum of Months 2708.45 2063.92 825.68 4037.76 1460.55 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 136.80 100.43 36.37 203.61 73.29 0.00 0.00 0.00
February 108.06 66.86 41.20 151.38 67.31 0.00 0.00 0.00
March 86.18 41.98 44.20 119.08 71.28 0.00 0.00 0.00
April 72.07 27.85 44.21 106.10 56.60 0.00 0.00 0.00
May 50.78 6.15 44.63 61.68 51.06 0.00 0.00 0.00
June 44.55 2.61 41.93 55.69 36.80 0.00 0.00 0.00
July 46.98 5.02 41.96 68.93 30.47 0.00 0.00 0.00
August 60.34 18.75 41.59 100.26 31.63 0.00 0.00 0.00
September 82.86 41.16 41.69 135.69 38.16 0.00 0.00 0.00
October 108.49 72.86 35.63 178.63 41.71 0.00 0.00 0.00
November 131.79 93.37 38.41 196.27 65.17 0.00 0.00 0.00
December 146.39 111.55 34.84 219.13 72.95 0.00 0.00 0.00
                 
Annual Sum or Average 89.53 48.99 40.54 132.99 52.96 0.00 0.00 0.00
Minimum of Months 44.55 2.61 34.84 55.69 30.47 0.00 0.00 0.00
Maximum of Months 146.39 111.55 44.63 219.13 73.29 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_3_WALL_WEST_WINDOW

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 99.13 49.99 49.14 123.71 148.50 0.00 0.00 0.00
February 118.40 54.72 63.67 141.67 132.14 0.00 0.00 0.00
March 135.41 59.84 75.57 166.83 134.65 0.00 0.00 0.00
April 186.62 97.02 89.60 263.15 102.11 0.00 0.00 0.00
May 183.33 84.55 98.78 252.85 90.54 0.00 0.00 0.00
June 194.16 96.95 97.21 286.20 64.48 0.00 0.00 0.00
July 205.59 109.90 95.69 321.83 53.54 0.00 0.00 0.00
August 192.92 104.46 88.46 304.34 56.63 0.00 0.00 0.00
September 165.33 88.43 76.90 250.54 69.26 0.00 0.00 0.00
October 127.00 69.58 57.41 197.85 81.20 0.00 0.00 0.00
November 114.28 59.82 54.46 147.89 129.98 0.00 0.00 0.00
December 100.52 53.75 46.77 127.81 148.28 0.00 0.00 0.00
                 
Annual Sum or Average 152.02 77.52 74.51 215.76 100.79 0.00 0.00 0.00
Minimum of Months 99.13 49.99 46.77 123.71 53.54 0.00 0.00 0.00
Maximum of Months 205.59 109.90 98.78 321.83 148.50 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 20.68 0.00 20.68 14.35 79.69 0.00 0.00 0.00
February 25.96 0.00 25.96 16.15 71.90 0.00 0.00 0.00
March 31.81 0.00 31.81 23.52 74.09 0.00 0.00 0.00
April 36.84 0.30 36.55 32.39 56.34 0.00 0.00 0.00
May 44.32 2.31 42.01 40.99 48.37 0.00 0.00 0.00
June 46.98 4.64 42.34 51.99 36.64 0.00 0.00 0.00
July 44.50 3.78 40.73 55.01 32.55 0.00 0.00 0.00
August 37.00 0.82 36.18 44.73 34.62 0.00 0.00 0.00
September 31.23 0.01 31.23 35.41 41.34 0.00 0.00 0.00
October 24.77 0.00 24.77 32.22 46.51 0.00 0.00 0.00
November 22.43 0.00 22.43 16.44 70.90 0.00 0.00 0.00
December 19.25 0.00 19.25 13.00 79.90 0.00 0.00 0.00
                 
Annual Sum or Average 32.17 0.99 31.18 31.44 55.99 0.00 0.00 0.00
Minimum of Months 19.25 0.00 19.25 13.00 32.55 0.00 0.00 0.00
Maximum of Months 46.98 4.64 42.34 55.01 79.90 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_3_WALL_WEST_WINDOW

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 99.13 49.99 49.14 129.67 144.95 0.00 0.00 0.00
February 118.40 54.72 63.67 145.94 129.76 0.00 0.00 0.00
March 135.41 59.84 75.57 169.62 133.33 0.00 0.00 0.00
April 186.62 97.02 89.60 262.11 103.38 0.00 0.00 0.00
May 183.33 84.55 98.78 249.05 93.09 0.00 0.00 0.00
June 194.16 96.95 97.21 278.19 70.43 0.00 0.00 0.00
July 205.59 109.90 95.69 312.77 61.49 0.00 0.00 0.00
August 192.92 104.46 88.46 297.99 64.32 0.00 0.00 0.00
September 165.33 88.43 76.90 248.69 73.53 0.00 0.00 0.00
October 127.00 69.58 57.41 198.96 84.26 0.00 0.00 0.00
November 114.28 59.82 54.46 152.82 127.69 0.00 0.00 0.00
December 100.52 53.75 46.77 133.83 144.69 0.00 0.00 0.00
                 
Annual Sum or Average 152.02 77.52 74.51 215.31 102.45 0.00 0.00 0.00
Minimum of Months 99.13 49.99 46.77 129.67 61.49 0.00 0.00 0.00
Maximum of Months 205.59 109.90 98.78 312.77 144.95 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 109.42 80.33 29.09 148.30 87.20 0.00 0.00 0.00
February 86.43 53.48 32.95 107.04 83.05 0.00 0.00 0.00
March 68.93 33.58 35.35 81.83 85.13 0.00 0.00 0.00
April 57.64 22.28 35.36 71.92 70.67 0.00 0.00 0.00
May 40.61 4.92 35.70 36.17 64.92 0.00 0.00 0.00
June 35.63 2.09 33.54 30.85 51.31 0.00 0.00 0.00
July 37.58 4.02 33.56 41.28 44.78 0.00 0.00 0.00
August 48.26 15.00 33.26 66.54 47.02 0.00 0.00 0.00
September 66.27 32.92 33.35 95.28 54.27 0.00 0.00 0.00
October 86.78 58.28 28.50 128.73 58.02 0.00 0.00 0.00
November 105.41 74.68 30.72 142.45 79.65 0.00 0.00 0.00
December 117.09 89.23 27.86 160.44 86.71 0.00 0.00 0.00
                 
Annual Sum or Average 71.61 39.18 32.42 92.53 67.64 0.00 0.00 0.00
Minimum of Months 35.63 2.09 27.86 30.85 44.78 0.00 0.00 0.00
Maximum of Months 117.09 89.23 35.70 160.44 87.20 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 16.54 0.00 16.54 11.83 64.41 0.00 0.00 0.00
February 20.77 0.00 20.77 13.50 57.81 0.00 0.00 0.00
March 25.45 0.00 25.45 19.70 59.44 0.00 0.00 0.00
April 29.48 0.24 29.24 29.03 43.17 0.00 0.00 0.00
May 35.46 1.85 33.61 36.33 37.46 0.00 0.00 0.00
June 37.59 3.71 33.88 46.11 27.47 0.00 0.00 0.00
July 35.61 3.02 32.58 49.09 23.54 0.00 0.00 0.00
August 29.60 0.66 28.95 40.28 24.69 0.00 0.00 0.00
September 24.99 0.00 24.98 31.42 30.28 0.00 0.00 0.00
October 19.82 0.00 19.82 27.82 35.29 0.00 0.00 0.00
November 17.95 0.00 17.95 14.12 56.02 0.00 0.00 0.00
December 15.40 0.00 15.40 10.92 64.13 0.00 0.00 0.00
                 
Annual Sum or Average 25.74 0.79 24.95 27.60 43.57 0.00 0.00 0.00
Minimum of Months 15.40 0.00 15.40 10.92 23.54 0.00 0.00 0.00
Maximum of Months 37.59 3.71 33.88 49.09 64.41 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_5_FLR_3_WALL_EAST_WINDOW

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 104.03 55.59 48.45 125.74 140.81 0.00 0.00 0.00
February 109.78 50.23 59.54 123.25 126.47 0.00 0.00 0.00
March 133.98 59.84 74.14 160.12 128.58 0.00 0.00 0.00
April 170.78 85.69 85.09 235.76 97.93 0.00 0.00 0.00
May 160.86 67.04 93.82 216.34 87.74 0.00 0.00 0.00
June 160.04 69.48 90.57 233.00 63.91 0.00 0.00 0.00
July 181.24 90.04 91.20 284.30 53.56 0.00 0.00 0.00
August 179.13 95.20 83.93 283.40 55.35 0.00 0.00 0.00
September 130.78 60.15 70.63 194.86 67.78 0.00 0.00 0.00
October 115.26 59.16 56.10 175.83 77.25 0.00 0.00 0.00
November 104.83 53.07 51.76 127.94 124.71 0.00 0.00 0.00
December 100.77 56.17 44.61 121.29 140.68 0.00 0.00 0.00
                 
Annual Sum or Average 137.81 66.94 70.87 190.62 96.91 0.00 0.00 0.00
Minimum of Months 100.77 50.23 44.61 121.29 53.56 0.00 0.00 0.00
Maximum of Months 181.24 95.20 93.82 284.30 140.81 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 136.80 100.43 36.37 202.74 73.08 0.00 0.00 0.00
February 108.06 66.86 41.20 150.91 66.71 0.00 0.00 0.00
March 86.18 41.98 44.20 118.22 70.74 0.00 0.00 0.00
April 72.07 27.85 44.21 105.23 55.64 0.00 0.00 0.00
May 50.78 6.15 44.63 61.11 50.06 0.00 0.00 0.00
June 44.55 2.61 41.93 55.36 35.69 0.00 0.00 0.00
July 46.98 5.02 41.96 68.31 29.44 0.00 0.00 0.00
August 60.34 18.75 41.59 99.54 30.72 0.00 0.00 0.00
September 82.86 41.16 41.69 135.64 37.00 0.00 0.00 0.00
October 108.49 72.86 35.63 178.26 41.12 0.00 0.00 0.00
November 131.79 93.37 38.41 195.83 64.56 0.00 0.00 0.00
December 146.39 111.55 34.84 218.46 72.55 0.00 0.00 0.00
                 
Annual Sum or Average 89.53 48.99 40.54 132.42 52.20 0.00 0.00 0.00
Minimum of Months 44.55 2.61 34.84 55.36 29.44 0.00 0.00 0.00
Maximum of Months 146.39 111.55 44.63 218.46 73.08 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_6_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 20.68 0.00 20.68 13.53 79.26 0.00 0.00 0.00
February 25.96 0.00 25.96 15.55 70.87 0.00 0.00 0.00
March 31.81 0.00 31.81 22.67 73.30 0.00 0.00 0.00
April 36.84 0.30 36.55 31.77 54.64 0.00 0.00 0.00
May 44.32 2.31 42.01 41.03 46.95 0.00 0.00 0.00
June 46.98 4.64 42.34 52.88 34.60 0.00 0.00 0.00
July 44.50 3.78 40.73 55.19 30.38 0.00 0.00 0.00
August 37.00 0.82 36.18 44.10 32.43 0.00 0.00 0.00
September 31.23 0.01 31.23 35.35 38.88 0.00 0.00 0.00
October 24.77 0.00 24.77 31.50 45.21 0.00 0.00 0.00
November 22.43 0.00 22.43 15.86 69.63 0.00 0.00 0.00
December 19.25 0.00 19.25 12.18 79.15 0.00 0.00 0.00
                 
Annual Sum or Average 32.17 0.99 31.18 31.06 54.53 0.00 0.00 0.00
Minimum of Months 19.25 0.00 19.25 12.18 30.38 0.00 0.00 0.00
Maximum of Months 46.98 4.64 42.34 55.19 79.26 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_6_FLR_3_WALL_EAST_WINDOW

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 104.03 55.59 48.45 131.07 136.25 0.00 0.00 0.00
February 109.78 50.23 59.54 127.40 123.35 0.00 0.00 0.00
March 133.98 59.84 74.14 163.16 126.90 0.00 0.00 0.00
April 170.78 85.69 85.09 236.36 98.56 0.00 0.00 0.00
May 160.86 67.04 93.82 214.22 89.75 0.00 0.00 0.00
June 160.04 69.48 90.57 227.86 68.57 0.00 0.00 0.00
July 181.24 90.04 91.20 277.28 59.98 0.00 0.00 0.00
August 179.13 95.20 83.93 277.78 61.27 0.00 0.00 0.00
September 130.78 60.15 70.63 194.15 70.59 0.00 0.00 0.00
October 115.26 59.16 56.10 176.92 79.52 0.00 0.00 0.00
November 104.83 53.07 51.76 132.53 121.04 0.00 0.00 0.00
December 100.77 56.17 44.61 126.55 135.97 0.00 0.00 0.00
                 
Annual Sum or Average 137.81 66.94 70.87 190.88 97.52 0.00 0.00 0.00
Minimum of Months 100.77 50.23 44.61 126.55 59.98 0.00 0.00 0.00
Maximum of Months 181.24 95.20 93.82 277.78 136.25 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 26.19 0.00 26.19 18.10 100.96 0.00 0.00 0.00
February 32.87 0.00 32.87 21.22 91.24 0.00 0.00 0.00
March 40.29 0.00 40.29 32.09 91.65 0.00 0.00 0.00
April 46.66 0.38 46.28 46.38 68.88 0.00 0.00 0.00
May 56.13 2.93 53.20 58.99 59.66 0.00 0.00 0.00
June 59.50 5.88 53.62 74.92 44.00 0.00 0.00 0.00
July 56.36 4.78 51.58 78.26 38.61 0.00 0.00 0.00
August 46.86 1.04 45.82 62.76 41.61 0.00 0.00 0.00
September 39.55 0.01 39.55 48.32 51.14 0.00 0.00 0.00
October 31.37 0.00 31.37 41.27 60.22 0.00 0.00 0.00
November 28.41 0.00 28.41 20.74 91.48 0.00 0.00 0.00
December 24.38 0.00 24.38 15.87 102.65 0.00 0.00 0.00
                 
Annual Sum or Average 40.75 1.26 39.49 43.38 70.07 0.00 0.00 0.00
Minimum of Months 24.38 0.00 24.38 15.87 38.61 0.00 0.00 0.00
Maximum of Months 59.50 5.88 53.62 78.26 102.65 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 9.65 0.00 9.65 6.67 37.22 0.00 0.00 0.00
February 12.12 0.00 12.12 7.82 33.63 0.00 0.00 0.00
March 14.85 0.00 14.85 11.83 33.79 0.00 0.00 0.00
April 17.20 0.14 17.06 17.10 25.39 0.00 0.00 0.00
May 20.69 1.08 19.61 21.75 21.99 0.00 0.00 0.00
June 21.93 2.17 19.77 27.62 16.22 0.00 0.00 0.00
July 20.78 1.76 19.01 28.85 14.23 0.00 0.00 0.00
August 17.27 0.38 16.89 23.14 15.34 0.00 0.00 0.00
September 14.58 0.00 14.58 17.81 18.85 0.00 0.00 0.00
October 11.57 0.00 11.57 15.22 22.20 0.00 0.00 0.00
November 10.47 0.00 10.47 7.65 33.72 0.00 0.00 0.00
December 8.99 0.00 8.99 5.85 37.84 0.00 0.00 0.00
                 
Annual Sum or Average 15.02 0.46 14.56 15.99 25.83 0.00 0.00 0.00
Minimum of Months 8.99 0.00 8.99 5.85 14.23 0.00 0.00 0.00
Maximum of Months 21.93 2.17 19.77 28.85 37.84 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 63.83 46.86 16.97 96.42 33.59 0.00 0.00 0.00
February 50.42 31.20 19.22 72.03 31.16 0.00 0.00 0.00
March 40.21 19.59 20.62 57.15 32.41 0.00 0.00 0.00
April 33.63 13.00 20.63 51.30 25.99 0.00 0.00 0.00
May 23.69 2.87 20.82 30.38 23.75 0.00 0.00 0.00
June 20.79 1.22 19.57 27.30 17.66 0.00 0.00 0.00
July 21.92 2.34 19.58 33.11 15.21 0.00 0.00 0.00
August 28.15 8.75 19.41 47.49 15.98 0.00 0.00 0.00
September 38.66 19.21 19.45 64.16 18.75 0.00 0.00 0.00
October 50.62 34.00 16.63 83.55 20.89 0.00 0.00 0.00
November 61.49 43.57 17.92 92.67 30.63 0.00 0.00 0.00
December 68.31 52.05 16.25 103.41 33.82 0.00 0.00 0.00
                 
Annual Sum or Average 41.77 22.86 18.92 63.23 24.95 0.00 0.00 0.00
Minimum of Months 20.79 1.22 16.25 27.30 15.21 0.00 0.00 0.00
Maximum of Months 68.31 52.05 20.82 103.41 33.82 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 173.25 127.19 46.06 261.72 91.17 0.00 0.00 0.00
February 136.85 84.68 52.17 195.52 84.57 0.00 0.00 0.00
March 109.15 53.17 55.98 155.13 87.96 0.00 0.00 0.00
April 91.27 35.28 55.99 139.25 70.54 0.00 0.00 0.00
May 64.31 7.79 56.52 82.47 64.45 0.00 0.00 0.00
June 56.42 3.31 53.11 74.11 47.94 0.00 0.00 0.00
July 59.50 6.36 53.13 89.86 41.29 0.00 0.00 0.00
August 76.41 23.74 52.67 128.90 43.37 0.00 0.00 0.00
September 104.93 52.13 52.80 174.16 50.88 0.00 0.00 0.00
October 137.40 92.28 45.13 226.78 56.71 0.00 0.00 0.00
November 166.90 118.25 48.65 251.52 83.14 0.00 0.00 0.00
December 185.40 141.28 44.12 280.69 91.79 0.00 0.00 0.00
                 
Annual Sum or Average 113.38 62.04 51.34 171.61 67.73 0.00 0.00 0.00
Minimum of Months 56.42 3.31 44.12 74.11 41.29 0.00 0.00 0.00
Maximum of Months 185.40 141.28 56.52 280.69 91.79 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 136.80 100.43 36.37 202.50 72.44 0.00 0.00 0.00
February 108.06 66.86 41.20 149.98 66.44 0.00 0.00 0.00
March 86.18 41.98 44.20 117.78 70.80 0.00 0.00 0.00
April 72.07 27.85 44.21 104.47 56.23 0.00 0.00 0.00
May 50.78 6.15 44.63 60.32 50.78 0.00 0.00 0.00
June 44.55 2.61 41.93 54.46 36.57 0.00 0.00 0.00
July 46.98 5.02 41.96 67.70 30.21 0.00 0.00 0.00
August 60.34 18.75 41.59 98.85 31.30 0.00 0.00 0.00
September 82.86 41.16 41.69 134.16 37.64 0.00 0.00 0.00
October 108.49 72.86 35.63 177.29 40.93 0.00 0.00 0.00
November 131.79 93.37 38.41 194.91 64.24 0.00 0.00 0.00
December 146.39 111.55 34.84 217.92 71.88 0.00 0.00 0.00
                 
Annual Sum or Average 89.53 48.99 40.54 131.65 52.38 0.00 0.00 0.00
Minimum of Months 44.55 2.61 34.84 54.46 30.21 0.00 0.00 0.00
Maximum of Months 146.39 111.55 44.63 217.92 72.44 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_6_WALL_WEST_WINDOW

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 99.13 49.99 49.14 122.14 146.23 0.00 0.00 0.00
February 118.40 54.72 63.67 139.76 129.98 0.00 0.00 0.00
March 135.41 59.84 75.57 164.12 133.28 0.00 0.00 0.00
April 186.62 97.02 89.60 258.83 101.17 0.00 0.00 0.00
May 183.33 84.55 98.78 248.44 89.75 0.00 0.00 0.00
June 194.16 96.95 97.21 281.40 63.86 0.00 0.00 0.00
July 205.59 109.90 95.69 317.32 52.87 0.00 0.00 0.00
August 192.92 104.46 88.46 300.14 55.88 0.00 0.00 0.00
September 165.33 88.43 76.90 247.01 68.16 0.00 0.00 0.00
October 127.00 69.58 57.41 195.80 79.45 0.00 0.00 0.00
November 114.28 59.82 54.46 146.15 127.65 0.00 0.00 0.00
December 100.52 53.75 46.77 126.58 145.55 0.00 0.00 0.00
                 
Annual Sum or Average 152.02 77.52 74.51 212.67 99.34 0.00 0.00 0.00
Minimum of Months 99.13 49.99 46.77 122.14 52.87 0.00 0.00 0.00
Maximum of Months 205.59 109.90 98.78 317.32 146.23 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 20.68 0.00 20.68 14.63 78.20 0.00 0.00 0.00
February 25.96 0.00 25.96 16.32 70.61 0.00 0.00 0.00
March 31.81 0.00 31.81 23.17 73.48 0.00 0.00 0.00
April 36.84 0.30 36.55 31.34 56.50 0.00 0.00 0.00
May 44.32 2.31 42.01 39.60 48.52 0.00 0.00 0.00
June 46.98 4.64 42.34 50.02 37.40 0.00 0.00 0.00
July 44.50 3.78 40.73 53.17 33.52 0.00 0.00 0.00
August 37.00 0.82 36.18 43.49 35.50 0.00 0.00 0.00
September 31.23 0.01 31.23 34.73 41.37 0.00 0.00 0.00
October 24.77 0.00 24.77 32.26 45.62 0.00 0.00 0.00
November 22.43 0.00 22.43 16.77 69.40 0.00 0.00 0.00
December 19.25 0.00 19.25 13.53 78.06 0.00 0.00 0.00
                 
Annual Sum or Average 32.17 0.99 31.18 30.84 55.61 0.00 0.00 0.00
Minimum of Months 19.25 0.00 19.25 13.53 33.52 0.00 0.00 0.00
Maximum of Months 46.98 4.64 42.34 53.17 78.20 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_6_WALL_WEST_WINDOW

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 99.13 49.99 49.14 128.99 142.09 0.00 0.00 0.00
February 118.40 54.72 63.67 144.67 127.27 0.00 0.00 0.00
March 135.41 59.84 75.57 167.07 132.02 0.00 0.00 0.00
April 186.62 97.02 89.60 257.25 103.20 0.00 0.00 0.00
May 183.33 84.55 98.78 243.91 93.13 0.00 0.00 0.00
June 194.16 96.95 97.21 272.06 71.59 0.00 0.00 0.00
July 205.59 109.90 95.69 306.83 63.01 0.00 0.00 0.00
August 192.92 104.46 88.46 292.80 65.50 0.00 0.00 0.00
September 165.33 88.43 76.90 244.89 73.20 0.00 0.00 0.00
October 127.00 69.58 57.41 197.30 82.53 0.00 0.00 0.00
November 114.28 59.82 54.46 151.95 124.81 0.00 0.00 0.00
December 100.52 53.75 46.77 133.67 141.22 0.00 0.00 0.00
                 
Annual Sum or Average 152.02 77.52 74.51 212.12 101.51 0.00 0.00 0.00
Minimum of Months 99.13 49.99 46.77 128.99 63.01 0.00 0.00 0.00
Maximum of Months 205.59 109.90 98.78 306.83 142.09 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 200.63 147.29 53.34 292.00 110.76 0.00 0.00 0.00
February 158.48 98.06 60.42 216.35 100.79 0.00 0.00 0.00
March 126.40 61.57 64.83 170.40 105.92 0.00 0.00 0.00
April 105.69 40.85 64.84 153.66 81.40 0.00 0.00 0.00
May 74.47 9.02 65.45 90.69 72.41 0.00 0.00 0.00
June 65.33 3.83 61.50 83.42 50.82 0.00 0.00 0.00
July 68.90 7.37 61.53 103.25 41.19 0.00 0.00 0.00
August 88.49 27.50 60.99 147.52 43.43 0.00 0.00 0.00
September 121.52 60.37 61.15 197.19 54.02 0.00 0.00 0.00
October 159.12 106.86 52.26 258.57 60.71 0.00 0.00 0.00
November 193.28 136.94 56.34 281.93 97.55 0.00 0.00 0.00
December 214.70 163.60 51.09 314.50 109.94 0.00 0.00 0.00
                 
Annual Sum or Average 131.30 71.85 59.45 192.41 77.29 0.00 0.00 0.00
Minimum of Months 65.33 3.83 51.09 83.42 41.19 0.00 0.00 0.00
Maximum of Months 214.70 163.60 65.45 314.50 110.76 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: BANQUET_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 144.74 0.00 144.74 72.84 642.56 0.00 0.00 0.00
February 181.69 0.00 181.69 83.48 597.54 0.00 0.00 0.00
March 222.66 0.00 222.66 131.81 601.08 0.00 0.00 0.00
April 257.88 2.08 255.81 199.88 450.07 0.00 0.00 0.00
May 310.23 16.18 294.05 255.52 388.10 0.00 0.00 0.00
June 328.85 32.49 296.36 343.64 288.93 0.00 0.00 0.00
July 311.50 26.43 285.07 372.58 248.32 0.00 0.00 0.00
August 258.99 5.75 253.24 297.48 267.70 0.00 0.00 0.00
September 218.62 0.04 218.58 225.31 330.52 0.00 0.00 0.00
October 173.40 0.00 173.40 198.01 380.72 0.00 0.00 0.00
November 157.00 0.00 157.00 87.27 577.36 0.00 0.00 0.00
December 134.74 0.00 134.74 64.28 645.06 0.00 0.00 0.00
                 
Annual Sum or Average 225.21 6.95 218.26 195.03 450.73 0.00 0.00 0.00
Minimum of Months 134.74 0.00 134.74 64.28 248.32 0.00 0.00 0.00
Maximum of Months 328.85 32.49 296.36 372.58 645.06 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: DINING_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 144.74 0.00 144.74 65.29 664.25 0.00 0.00 0.00
February 181.69 0.00 181.69 74.84 618.63 0.00 0.00 0.00
March 222.66 0.00 222.66 121.10 620.93 0.00 0.00 0.00
April 257.88 2.08 255.81 187.91 463.45 0.00 0.00 0.00
May 310.23 16.18 294.05 241.52 399.01 0.00 0.00 0.00
June 328.85 32.49 296.36 330.64 297.93 0.00 0.00 0.00
July 311.50 26.43 285.07 361.02 256.20 0.00 0.00 0.00
August 258.99 5.75 253.24 286.93 276.60 0.00 0.00 0.00
September 218.62 0.04 218.58 215.53 341.91 0.00 0.00 0.00
October 173.40 0.00 173.40 189.32 393.25 0.00 0.00 0.00
November 157.00 0.00 157.00 79.17 595.77 0.00 0.00 0.00
December 134.74 0.00 134.74 57.27 666.46 0.00 0.00 0.00
                 
Annual Sum or Average 225.21 6.95 218.26 184.90 465.40 0.00 0.00 0.00
Minimum of Months 134.74 0.00 134.74 57.27 256.20 0.00 0.00 0.00
Maximum of Months 328.85 32.49 296.36 361.02 666.46 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 20.68 0.00 20.68 16.86 81.22 0.00 0.00 0.00
February 25.96 0.00 25.96 18.58 77.53 0.00 0.00 0.00
March 31.81 0.00 31.81 27.11 78.75 0.00 0.00 0.00
April 36.84 0.30 36.55 40.60 60.00 0.00 0.00 0.00
May 44.32 2.31 42.01 51.58 53.43 0.00 0.00 0.00
June 46.98 4.64 42.34 66.25 40.17 0.00 0.00 0.00
July 44.50 3.78 40.73 71.26 34.62 0.00 0.00 0.00
August 37.00 0.82 36.18 58.84 36.57 0.00 0.00 0.00
September 31.23 0.01 31.23 45.34 42.20 0.00 0.00 0.00
October 24.77 0.00 24.77 39.83 48.13 0.00 0.00 0.00
November 22.43 0.00 22.43 19.84 72.99 0.00 0.00 0.00
December 19.25 0.00 19.25 15.57 81.45 0.00 0.00 0.00
                 
Annual Sum or Average 32.17 0.99 31.18 39.44 58.82 0.00 0.00 0.00
Minimum of Months 19.25 0.00 19.25 15.57 34.62 0.00 0.00 0.00
Maximum of Months 46.98 4.64 42.34 71.26 81.45 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_FLR_6_WALL_EAST_WINDOW

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 208.05 111.16 96.89 279.99 284.51 0.00 0.00 0.00
February 219.54 100.46 119.08 268.39 274.81 0.00 0.00 0.00
March 267.94 119.67 148.26 345.85 277.73 0.00 0.00 0.00
April 341.54 171.37 170.17 507.65 218.55 0.00 0.00 0.00
May 321.70 134.06 187.64 466.11 202.03 0.00 0.00 0.00
June 320.07 138.95 181.12 503.61 155.40 0.00 0.00 0.00
July 362.45 180.07 182.38 612.79 133.70 0.00 0.00 0.00
August 358.23 190.39 167.84 610.64 137.83 0.00 0.00 0.00
September 261.54 120.30 141.24 428.29 156.00 0.00 0.00 0.00
October 230.50 118.31 112.19 388.01 172.91 0.00 0.00 0.00
November 209.64 106.13 103.51 283.19 258.08 0.00 0.00 0.00
December 201.53 112.32 89.21 270.02 284.71 0.00 0.00 0.00
                 
Annual Sum or Average 275.60 133.87 141.73 414.72 212.69 0.00 0.00 0.00
Minimum of Months 201.53 100.46 89.21 268.39 133.70 0.00 0.00 0.00
Maximum of Months 362.45 190.39 187.64 612.79 284.71 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 136.80 100.43 36.37 212.15 74.90 0.00 0.00 0.00
February 108.06 66.86 41.20 157.93 73.36 0.00 0.00 0.00
March 86.18 41.98 44.20 125.49 76.44 0.00 0.00 0.00
April 72.07 27.85 44.21 114.79 61.28 0.00 0.00 0.00
May 50.78 6.15 44.63 69.68 56.92 0.00 0.00 0.00
June 44.55 2.61 41.93 65.55 42.90 0.00 0.00 0.00
July 46.98 5.02 41.96 80.47 36.31 0.00 0.00 0.00
August 60.34 18.75 41.59 111.53 37.59 0.00 0.00 0.00
September 82.86 41.16 41.69 146.09 42.20 0.00 0.00 0.00
October 108.49 72.86 35.63 188.34 46.36 0.00 0.00 0.00
November 131.79 93.37 38.41 204.80 68.00 0.00 0.00 0.00
December 146.39 111.55 34.84 227.62 74.64 0.00 0.00 0.00
                 
Annual Sum or Average 89.53 48.99 40.54 142.01 57.49 0.00 0.00 0.00
Minimum of Months 44.55 2.61 34.84 65.55 36.31 0.00 0.00 0.00
Maximum of Months 146.39 111.55 44.63 227.62 76.44 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 26.19 0.00 26.19 16.02 102.36 0.00 0.00 0.00
February 32.87 0.00 32.87 19.13 92.15 0.00 0.00 0.00
March 40.29 0.00 40.29 29.07 93.54 0.00 0.00 0.00
April 46.66 0.38 46.28 42.14 70.80 0.00 0.00 0.00
May 56.13 2.93 53.20 54.65 61.05 0.00 0.00 0.00
June 59.50 5.88 53.62 69.67 45.73 0.00 0.00 0.00
July 56.36 4.78 51.58 72.99 40.31 0.00 0.00 0.00
August 46.86 1.04 45.82 57.99 43.60 0.00 0.00 0.00
September 39.55 0.01 39.55 44.60 52.87 0.00 0.00 0.00
October 31.37 0.00 31.37 38.50 61.48 0.00 0.00 0.00
November 28.41 0.00 28.41 18.92 91.70 0.00 0.00 0.00
December 24.38 0.00 24.38 14.23 102.74 0.00 0.00 0.00
                 
Annual Sum or Average 40.75 1.26 39.49 39.95 71.43 0.00 0.00 0.00
Minimum of Months 24.38 0.00 24.38 14.23 40.31 0.00 0.00 0.00
Maximum of Months 59.50 5.88 53.62 72.99 102.74 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 23.43 0.00 23.43 14.33 91.57 0.00 0.00 0.00
February 29.41 0.00 29.41 17.11 82.45 0.00 0.00 0.00
March 36.04 0.00 36.04 26.01 83.69 0.00 0.00 0.00
April 41.74 0.34 41.41 37.71 63.34 0.00 0.00 0.00
May 50.22 2.62 47.60 48.90 54.63 0.00 0.00 0.00
June 53.23 5.26 47.97 62.34 40.92 0.00 0.00 0.00
July 50.42 4.28 46.15 65.30 36.06 0.00 0.00 0.00
August 41.92 0.93 40.99 51.88 39.01 0.00 0.00 0.00
September 35.39 0.01 35.38 39.90 47.31 0.00 0.00 0.00
October 28.07 0.00 28.07 34.44 55.01 0.00 0.00 0.00
November 25.41 0.00 25.41 16.92 82.05 0.00 0.00 0.00
December 21.81 0.00 21.81 12.73 91.91 0.00 0.00 0.00
                 
Annual Sum or Average 36.46 1.13 35.33 35.74 63.90 0.00 0.00 0.00
Minimum of Months 21.81 0.00 21.81 12.73 36.06 0.00 0.00 0.00
Maximum of Months 53.23 5.26 47.97 65.30 91.91 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 510.71 374.93 135.77 760.05 272.38 0.00 0.00 0.00
February 403.42 249.62 153.80 564.78 252.20 0.00 0.00 0.00
March 321.75 156.73 165.02 444.59 265.36 0.00 0.00 0.00
April 269.05 103.99 165.06 395.69 214.50 0.00 0.00 0.00
May 189.57 22.96 166.61 229.79 195.62 0.00 0.00 0.00
June 166.31 9.75 156.55 204.06 147.95 0.00 0.00 0.00
July 175.39 18.75 156.63 249.90 128.13 0.00 0.00 0.00
August 225.26 70.00 155.26 364.61 134.64 0.00 0.00 0.00
September 309.33 153.67 155.66 499.40 155.39 0.00 0.00 0.00
October 405.04 272.02 133.03 655.90 171.12 0.00 0.00 0.00
November 492.00 348.59 143.41 730.72 245.93 0.00 0.00 0.00
December 546.52 416.47 130.06 816.98 270.96 0.00 0.00 0.00
                 
Annual Sum or Average 334.24 182.90 151.34 492.84 204.27 0.00 0.00 0.00
Minimum of Months 166.31 9.75 130.06 204.06 128.13 0.00 0.00 0.00
Maximum of Months 546.52 416.47 166.61 816.98 272.38 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.185314E+10 0.136048E+10 0.492663E+09 0.272142E+10 0.965380E+09
February 0.132217E+10 0.818116E+09 0.504052E+09 0.185454E+10 0.787826E+09
March 0.116748E+10 0.568705E+09 0.598776E+09 0.163027E+10 0.897761E+09
April 0.944769E+09 0.365158E+09 0.579611E+09 0.140942E+10 0.702136E+09
May 0.687861E+09 83301651.90 0.604559E+09 0.884637E+09 0.635446E+09
June 0.583982E+09 34251187.10 0.549731E+09 0.764614E+09 0.460786E+09
July 0.636401E+09 68053370.08 0.568348E+09 0.939993E+09 0.420117E+09
August 0.817369E+09 0.253989E+09 0.563379E+09 0.133747E+10 0.454655E+09
September 0.108621E+10 0.539619E+09 0.546586E+09 0.175094E+10 0.526449E+09
October 0.146973E+10 0.987033E+09 0.482692E+09 0.236870E+10 0.603975E+09
November 0.172768E+10 0.122410E+10 0.503575E+09 0.254333E+10 0.845186E+09
December 0.198311E+10 0.151118E+10 0.471925E+09 0.292720E+10 0.970190E+09
           
Annual Sum or Average 0.142799E+11 0.781399E+10 0.646590E+10 0.211325E+11 0.826991E+10
Minimum of Months 0.583982E+09 34251187.10 0.471925E+09 0.764614E+09 0.420117E+09
Maximum of Months 0.198311E+10 0.151118E+10 0.604559E+09 0.292720E+10 0.970190E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CAFE_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.521833E+10 0.383102E+10 0.138731E+10 0.755795E+10 0.295088E+10
February 0.372314E+10 0.230376E+10 0.141938E+10 0.512403E+10 0.245299E+10
March 0.328755E+10 0.160144E+10 0.168611E+10 0.448738E+10 0.276925E+10
April 0.266041E+10 0.102826E+10 0.163215E+10 0.387483E+10 0.220063E+10
May 0.193697E+10 0.234572E+09 0.170240E+10 0.238048E+10 0.201187E+10
June 0.164445E+10 96449084.55 0.154801E+10 0.205353E+10 0.148268E+10
July 0.179206E+10 0.191634E+09 0.160043E+10 0.256907E+10 0.133070E+10
August 0.230166E+10 0.715217E+09 0.158644E+10 0.370587E+10 0.142369E+10
September 0.305868E+10 0.151953E+10 0.153915E+10 0.486402E+10 0.164575E+10
October 0.413865E+10 0.277942E+10 0.135923E+10 0.658732E+10 0.187109E+10
November 0.486503E+10 0.344700E+10 0.141803E+10 0.705471E+10 0.260984E+10
December 0.558430E+10 0.425539E+10 0.132891E+10 0.813390E+10 0.296432E+10
           
Annual Sum or Average 0.402112E+11 0.220037E+11 0.182075E+11 0.583931E+11 0.257137E+11
Minimum of Months 0.164445E+10 96449084.55 0.132891E+10 0.205353E+10 0.133070E+10
Maximum of Months 0.558430E+10 0.425539E+10 0.170240E+10 0.813390E+10 0.296432E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: LOBBY_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.677891E+10 0.497672E+10 0.180219E+10 0.100637E+11 0.389083E+10
February 0.483657E+10 0.299272E+10 0.184385E+10 0.681340E+10 0.328191E+10
March 0.427071E+10 0.208036E+10 0.219036E+10 0.596514E+10 0.373133E+10
April 0.345602E+10 0.133577E+10 0.212025E+10 0.516028E+10 0.295811E+10
May 0.251623E+10 0.304722E+09 0.221151E+10 0.311948E+10 0.276599E+10
June 0.213624E+10 0.125293E+09 0.201095E+10 0.268208E+10 0.204353E+10
July 0.232799E+10 0.248943E+09 0.207905E+10 0.339229E+10 0.181788E+10
August 0.298998E+10 0.929108E+09 0.206087E+10 0.494059E+10 0.190190E+10
September 0.397340E+10 0.197396E+10 0.199944E+10 0.648682E+10 0.218141E+10
October 0.537634E+10 0.361063E+10 0.176572E+10 0.875579E+10 0.246341E+10
November 0.631995E+10 0.447785E+10 0.184211E+10 0.938089E+10 0.344904E+10
December 0.725432E+10 0.552799E+10 0.172633E+10 0.108147E+11 0.391195E+10
           
Annual Sum or Average 0.522367E+11 0.285840E+11 0.236526E+11 0.775752E+11 0.343973E+11
Minimum of Months 0.213624E+10 0.125293E+09 0.172633E+10 0.268208E+10 0.181788E+10
Maximum of Months 0.725432E+10 0.552799E+10 0.221151E+10 0.108147E+11 0.391195E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.366399E+09 0.268990E+09 97408702.42 0.545357E+09 0.196305E+09
February 0.261416E+09 0.161756E+09 99660556.79 0.366207E+09 0.162839E+09
March 0.230832E+09 0.112443E+09 0.118389E+09 0.318947E+09 0.190923E+09
April 0.186798E+09 72197917.93 0.114600E+09 0.275014E+09 0.146708E+09
May 0.136003E+09 16470167.27 0.119533E+09 0.165206E+09 0.136768E+09
June 0.115465E+09 6772047.95 0.108693E+09 0.144338E+09 95391844.44
July 0.125829E+09 13455320.07 0.112374E+09 0.184628E+09 81615406.28
August 0.161609E+09 50218052.04 0.111391E+09 0.268530E+09 84705542.82
September 0.214763E+09 0.106692E+09 0.108071E+09 0.351713E+09 98921845.44
October 0.290591E+09 0.195153E+09 95437466.31 0.478455E+09 0.111726E+09
November 0.341593E+09 0.242027E+09 99566205.17 0.508722E+09 0.168910E+09
December 0.392095E+09 0.298787E+09 93308334.56 0.586910E+09 0.195394E+09
           
Annual Sum or Average 0.282339E+10 0.154496E+10 0.127843E+10 0.419403E+10 0.167021E+10
Minimum of Months 0.115465E+09 6772047.95 93308334.56 0.144338E+09 81615406.28
Maximum of Months 0.392095E+09 0.298787E+09 0.119533E+09 0.586910E+09 0.196305E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_3_WALL_WEST_WINDOW

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.265521E+09 0.133901E+09 0.131620E+09 0.331356E+09 0.397738E+09
February 0.286426E+09 0.132386E+09 0.154039E+09 0.342726E+09 0.319678E+09
March 0.362688E+09 0.160278E+09 0.202410E+09 0.446844E+09 0.360634E+09
April 0.483730E+09 0.251482E+09 0.232247E+09 0.682078E+09 0.264658E+09
May 0.491022E+09 0.226458E+09 0.264564E+09 0.677233E+09 0.242505E+09
June 0.503264E+09 0.251292E+09 0.251972E+09 0.741824E+09 0.167139E+09
July 0.550654E+09 0.294353E+09 0.256300E+09 0.861980E+09 0.143413E+09
August 0.516705E+09 0.279782E+09 0.236923E+09 0.815155E+09 0.151682E+09
September 0.428535E+09 0.229221E+09 0.199314E+09 0.649391E+09 0.179518E+09
October 0.340146E+09 0.186368E+09 0.153778E+09 0.529930E+09 0.217473E+09
November 0.296219E+09 0.155051E+09 0.141168E+09 0.383320E+09 0.336904E+09
December 0.269240E+09 0.143959E+09 0.125281E+09 0.342335E+09 0.397149E+09
           
Annual Sum or Average 0.479415E+10 0.244453E+10 0.234962E+10 0.680417E+10 0.317849E+10
Minimum of Months 0.265521E+09 0.132386E+09 0.125281E+09 0.331356E+09 0.143413E+09
Maximum of Months 0.550654E+09 0.294353E+09 0.264564E+09 0.861980E+09 0.397738E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 55383852.68 0.00 55383852.68 38422400.49 0.213434E+09
February 62793579.01 0.00 62793579.01 39072199.83 0.173930E+09
March 85200912.64 780.17 85200132.47 62993049.19 0.198444E+09
April 95493362.34 768414.00 94724948.34 83943784.65 0.146023E+09
May 0.118708E+09 6190456.55 0.112517E+09 0.109796E+09 0.129563E+09
June 0.121773E+09 12029988.47 0.109743E+09 0.134751E+09 94970094.88
July 0.119193E+09 10114061.15 0.109079E+09 0.147344E+09 87191355.49
August 99102290.78 2201816.78 96900474.00 0.119814E+09 92735754.53
September 80955510.48 16100.43 80939410.05 91787747.89 0.107145E+09
October 66349884.71 0.00 66349884.71 86285095.17 0.124565E+09
November 58137116.95 0.00 58137116.95 42603411.76 0.183775E+09
December 51557659.69 0.00 51557659.69 34828688.74 0.214014E+09
           
Annual Sum or Average 0.101465E+10 31321617.54 0.983326E+09 0.991642E+09 0.176579E+10
Minimum of Months 51557659.69 0.00 51557659.69 34828688.74 87191355.49
Maximum of Months 0.121773E+09 12029988.47 0.112517E+09 0.147344E+09 0.214014E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_3_WALL_WEST_WINDOW

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.265521E+09 0.133901E+09 0.131620E+09 0.347301E+09 0.388247E+09
February 0.286426E+09 0.132386E+09 0.154039E+09 0.353056E+09 0.313910E+09
March 0.362688E+09 0.160278E+09 0.202410E+09 0.454300E+09 0.357120E+09
April 0.483730E+09 0.251482E+09 0.232247E+09 0.679392E+09 0.267953E+09
May 0.491022E+09 0.226458E+09 0.264564E+09 0.667068E+09 0.249340E+09
June 0.503264E+09 0.251292E+09 0.251972E+09 0.721061E+09 0.182553E+09
July 0.550654E+09 0.294353E+09 0.256300E+09 0.837714E+09 0.164704E+09
August 0.516705E+09 0.279782E+09 0.236923E+09 0.798140E+09 0.172265E+09
September 0.428535E+09 0.229221E+09 0.199314E+09 0.644594E+09 0.190579E+09
October 0.340146E+09 0.186368E+09 0.153778E+09 0.532899E+09 0.225684E+09
November 0.296219E+09 0.155051E+09 0.141168E+09 0.396101E+09 0.330984E+09
December 0.269240E+09 0.143959E+09 0.125281E+09 0.358454E+09 0.387532E+09
           
Annual Sum or Average 0.479415E+10 0.244453E+10 0.234962E+10 0.679008E+10 0.323087E+10
Minimum of Months 0.265521E+09 0.132386E+09 0.125281E+09 0.347301E+09 0.164704E+09
Maximum of Months 0.550654E+09 0.294353E+09 0.264564E+09 0.837714E+09 0.388247E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.293061E+09 0.215149E+09 77911467.45 0.397197E+09 0.233546E+09
February 0.209091E+09 0.129379E+09 79712592.74 0.258946E+09 0.200917E+09
March 0.184629E+09 89936327.87 94692605.60 0.219183E+09 0.228011E+09
April 0.149409E+09 57746850.06 91662135.38 0.186412E+09 0.183170E+09
May 0.108781E+09 13173513.96 95607483.13 96865478.16 0.173892E+09
June 92353413.13 5416561.15 86936851.98 79972363.84 0.133001E+09
July 0.100643E+09 10762115.76 89881160.52 0.110551E+09 0.119937E+09
August 0.129262E+09 40166453.60 89095338.36 0.178222E+09 0.125935E+09
September 0.171776E+09 85336561.19 86439337.30 0.246958E+09 0.140662E+09
October 0.232427E+09 0.156092E+09 76334792.12 0.344782E+09 0.155414E+09
November 0.273220E+09 0.193583E+09 79637126.46 0.369242E+09 0.206458E+09
December 0.313614E+09 0.238982E+09 74631825.39 0.429724E+09 0.232254E+09
           
Annual Sum or Average 0.225827E+10 0.123572E+10 0.102254E+10 0.291805E+10 0.213320E+10
Minimum of Months 92353413.13 5416561.15 74631825.39 79972363.84 0.119937E+09
Maximum of Months 0.313614E+09 0.238982E+09 95607483.13 0.429724E+09 0.233546E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 44312955.30 0.00 44312955.30 31686574.94 0.172506E+09
February 50241522.13 0.00 50241522.13 32658707.69 0.139861E+09
March 68169765.21 624.22 68169140.99 52753290.28 0.159213E+09
April 76404816.42 614812.68 75790003.74 75246460.74 0.111898E+09
May 94978755.02 4953021.70 90025733.32 97299494.08 0.100323E+09
June 97431324.50 9625266.49 87806058.00 0.119513E+09 71204884.02
July 95367114.15 8092321.46 87274792.68 0.131486E+09 63044846.23
August 79292341.88 1761686.91 77530654.97 0.107885E+09 66141105.79
September 64772993.27 12882.05 64760111.22 81447027.67 78490635.24
October 53086943.81 0.00 53086943.81 74525464.13 94533971.54
November 46515858.69 0.00 46515858.69 36598498.63 0.145208E+09
December 41251595.16 0.00 41251595.16 29253268.86 0.171756E+09
           
Annual Sum or Average 0.811826E+09 25060615.52 0.786765E+09 0.870354E+09 0.137418E+10
Minimum of Months 41251595.16 0.00 41251595.16 29253268.86 63044846.23
Maximum of Months 97431324.50 9625266.49 90025733.32 0.131486E+09 0.172506E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_5_FLR_3_WALL_EAST_WINDOW

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.278642E+09 0.148882E+09 0.129760E+09 0.336791E+09 0.377151E+09
February 0.265576E+09 0.121526E+09 0.144050E+09 0.298165E+09 0.305963E+09
March 0.358848E+09 0.160278E+09 0.198570E+09 0.428854E+09 0.344389E+09
April 0.442664E+09 0.222110E+09 0.220555E+09 0.611084E+09 0.253825E+09
May 0.430846E+09 0.179547E+09 0.251299E+09 0.579454E+09 0.234991E+09
June 0.414835E+09 0.180091E+09 0.234745E+09 0.603934E+09 0.165642E+09
July 0.485425E+09 0.241161E+09 0.244264E+09 0.761481E+09 0.143449E+09
August 0.479775E+09 0.254984E+09 0.224791E+09 0.759052E+09 0.148255E+09
September 0.338985E+09 0.155919E+09 0.183066E+09 0.505084E+09 0.175685E+09
October 0.308711E+09 0.158449E+09 0.150261E+09 0.470946E+09 0.206911E+09
November 0.271708E+09 0.137555E+09 0.134153E+09 0.331618E+09 0.323236E+09
December 0.269909E+09 0.150433E+09 0.119475E+09 0.324875E+09 0.376787E+09
           
Annual Sum or Average 0.434593E+10 0.211093E+10 0.223499E+10 0.601134E+10 0.305628E+10
Minimum of Months 0.265576E+09 0.121526E+09 0.119475E+09 0.298165E+09 0.143449E+09
Maximum of Months 0.485425E+09 0.254984E+09 0.251299E+09 0.761481E+09 0.377151E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.366399E+09 0.268990E+09 97408702.42 0.543029E+09 0.195733E+09
February 0.261416E+09 0.161756E+09 99660556.79 0.365090E+09 0.161374E+09
March 0.230832E+09 0.112443E+09 0.118389E+09 0.316650E+09 0.189465E+09
April 0.186798E+09 72197917.93 0.114600E+09 0.272767E+09 0.144210E+09
May 0.136003E+09 16470167.27 0.119533E+09 0.163672E+09 0.134088E+09
June 0.115465E+09 6772047.95 0.108693E+09 0.143505E+09 92499172.55
July 0.125829E+09 13455320.07 0.112374E+09 0.182948E+09 78843483.44
August 0.161609E+09 50218052.04 0.111391E+09 0.266604E+09 82277994.70
September 0.214763E+09 0.106692E+09 0.108071E+09 0.351571E+09 95899773.61
October 0.290591E+09 0.195153E+09 95437466.31 0.477450E+09 0.110134E+09
November 0.341593E+09 0.242027E+09 99566205.17 0.507600E+09 0.167335E+09
December 0.392095E+09 0.298787E+09 93308334.56 0.585112E+09 0.194311E+09
           
Annual Sum or Average 0.282339E+10 0.154496E+10 0.127843E+10 0.417600E+10 0.164617E+10
Minimum of Months 0.115465E+09 6772047.95 93308334.56 0.143505E+09 78843483.44
Maximum of Months 0.392095E+09 0.298787E+09 0.119533E+09 0.585112E+09 0.195733E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_6_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 55383852.68 0.00 55383852.68 36246238.83 0.212278E+09
February 62793579.01 0.00 62793579.01 37613177.58 0.171447E+09
March 85200912.64 780.17 85200132.47 60730825.07 0.196328E+09
April 95493362.34 768414.00 94724948.34 82347636.16 0.141621E+09
May 0.118708E+09 6190456.55 0.112517E+09 0.109894E+09 0.125761E+09
June 0.121773E+09 12029988.47 0.109743E+09 0.137071E+09 89672083.13
July 0.119193E+09 10114061.15 0.109079E+09 0.147821E+09 81377257.06
August 99102290.78 2201816.78 96900474.00 0.118116E+09 86870438.56
September 80955510.48 16100.43 80939410.05 91636922.89 0.100780E+09
October 66349884.71 0.00 66349884.71 84365758.26 0.121088E+09
November 58137116.95 0.00 58137116.95 41115565.58 0.180490E+09
December 51557659.69 0.00 51557659.69 32621349.57 0.211997E+09
           
Annual Sum or Average 0.101465E+10 31321617.54 0.983326E+09 0.979579E+09 0.171971E+10
Minimum of Months 51557659.69 0.00 51557659.69 32621349.57 81377257.06
Maximum of Months 0.121773E+09 12029988.47 0.112517E+09 0.147821E+09 0.212278E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_6_FLR_3_WALL_EAST_WINDOW

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.278642E+09 0.148882E+09 0.129760E+09 0.351064E+09 0.364920E+09
February 0.265576E+09 0.121526E+09 0.144050E+09 0.308212E+09 0.298407E+09
March 0.358848E+09 0.160278E+09 0.198570E+09 0.436996E+09 0.339901E+09
April 0.442664E+09 0.222110E+09 0.220555E+09 0.612633E+09 0.255462E+09
May 0.430846E+09 0.179547E+09 0.251299E+09 0.573764E+09 0.240400E+09
June 0.414835E+09 0.180091E+09 0.234745E+09 0.590624E+09 0.177742E+09
July 0.485425E+09 0.241161E+09 0.244264E+09 0.742664E+09 0.160639E+09
August 0.479775E+09 0.254984E+09 0.224791E+09 0.743994E+09 0.164116E+09
September 0.338985E+09 0.155919E+09 0.183066E+09 0.503226E+09 0.182981E+09
October 0.308711E+09 0.158449E+09 0.150261E+09 0.473875E+09 0.212993E+09
November 0.271708E+09 0.137555E+09 0.134153E+09 0.343506E+09 0.313733E+09
December 0.269909E+09 0.150433E+09 0.119475E+09 0.338952E+09 0.364189E+09
           
Annual Sum or Average 0.434593E+10 0.211093E+10 0.223499E+10 0.601951E+10 0.307548E+10
Minimum of Months 0.265576E+09 0.121526E+09 0.119475E+09 0.308212E+09 0.160639E+09
Maximum of Months 0.485425E+09 0.254984E+09 0.251299E+09 0.743994E+09 0.364920E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 70140154.89 0.00 70140154.89 48475840.69 0.270402E+09
February 79524105.76 0.00 79524105.76 51324386.21 0.220728E+09
March 0.107902E+09 988.04 0.107901E+09 85958868.73 0.245478E+09
April 0.120936E+09 973147.84 0.119963E+09 0.120216E+09 0.178533E+09
May 0.150336E+09 7839822.62 0.142496E+09 0.157998E+09 0.159785E+09
June 0.154218E+09 15235221.35 0.138983E+09 0.194186E+09 0.114040E+09
July 0.150951E+09 12808820.29 0.138142E+09 0.209610E+09 0.103420E+09
August 0.125507E+09 2788462.02 0.122718E+09 0.168090E+09 0.111446E+09
September 0.102525E+09 20390.18 0.102505E+09 0.125258E+09 0.132563E+09
October 84027942.54 0.00 84027942.54 0.110547E+09 0.161296E+09
November 73626990.37 0.00 73626990.37 53767912.57 0.237128E+09
December 65294522.88 0.00 65294522.88 42515156.73 0.274934E+09
           
Annual Sum or Average 0.128499E+10 39666852.34 0.124532E+10 0.136795E+10 0.220975E+10
Minimum of Months 65294522.88 0.00 65294522.88 42515156.73 0.103420E+09
Maximum of Months 0.154218E+09 15235221.35 0.142496E+09 0.209610E+09 0.274934E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 25856565.37 0.00 25856565.37 17870202.11 99681391.10
February 29315878.22 0.00 29315878.22 18920293.93 81369585.30
March 39776990.23 364.23 39776626.00 31687998.29 90493271.29
April 44582134.43 358742.59 44223391.84 44316734.82 65814697.45
May 55420009.14 2890083.24 52529925.90 58244779.75 58903449.98
June 56851080.99 5616333.43 51234747.56 71584835.35 42039828.44
July 55646616.31 4721861.53 50924754.78 77271047.37 38124715.41
August 46267002.67 1027942.56 45239060.11 61965102.21 41083672.15
September 37794977.19 7516.66 37787460.52 46175120.50 48868082.42
October 30976178.94 0.00 30976178.94 40752191.94 59460200.47
November 27141957.31 0.00 27141957.31 19821078.93 87415099.96
December 24070264.77 0.00 24070264.77 15672847.19 0.101352E+09
           
Annual Sum or Average 0.473700E+09 14622844.25 0.459077E+09 0.504282E+09 0.814606E+09
Minimum of Months 24070264.77 0.00 24070264.77 15672847.19 38124715.41
Maximum of Months 56851080.99 5616333.43 52529925.90 77271047.37 0.101352E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.170960E+09 0.125510E+09 45450508.02 0.258263E+09 89971567.32
February 0.121976E+09 75474510.52 46501214.20 0.174266E+09 75375102.37
March 0.107705E+09 52465342.08 55239968.79 0.153082E+09 86798167.04
April 87159368.36 33687257.57 53472110.79 0.132980E+09 67367612.15
May 63458586.31 7684913.68 55773672.63 81380718.02 63602511.08
June 53875375.24 3159810.28 50715564.96 70772448.17 45786200.87
July 58711357.72 6278198.12 52433159.60 88671594.36 40747546.42
August 75406282.36 23431540.72 51974741.64 0.127196E+09 42793541.33
September 0.100207E+09 49782017.80 50425334.32 0.166314E+09 48589230.92
October 0.135589E+09 91057819.93 44530737.20 0.223784E+09 55962286.00
November 0.159386E+09 0.112929E+09 46457190.11 0.240195E+09 79394351.18
December 0.182950E+09 0.139413E+09 43537292.90 0.276986E+09 90581005.15
           
Annual Sum or Average 0.131738E+10 0.720873E+09 0.596511E+09 0.199389E+10 0.786969E+09
Minimum of Months 53875375.24 3159810.28 43537292.90 70772448.17 40747546.42
Maximum of Months 0.182950E+09 0.139413E+09 55773672.63 0.276986E+09 90581005.15



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.464021E+09 0.340659E+09 0.123362E+09 0.700978E+09 0.244201E+09
February 0.331067E+09 0.204853E+09 0.126214E+09 0.472993E+09 0.204583E+09
March 0.292334E+09 0.142402E+09 0.149933E+09 0.415496E+09 0.235588E+09
April 0.236568E+09 91434107.63 0.145134E+09 0.360934E+09 0.182850E+09
May 0.172240E+09 20858427.64 0.151381E+09 0.220884E+09 0.172630E+09
June 0.146229E+09 8576371.43 0.137652E+09 0.192091E+09 0.124273E+09
July 0.159355E+09 17040313.89 0.142314E+09 0.240673E+09 0.110597E+09
August 0.204668E+09 63597994.32 0.141070E+09 0.345235E+09 0.116150E+09
September 0.271983E+09 0.135119E+09 0.136865E+09 0.451410E+09 0.131881E+09
October 0.368015E+09 0.247150E+09 0.120866E+09 0.607397E+09 0.151893E+09
November 0.432606E+09 0.306511E+09 0.126094E+09 0.651938E+09 0.215493E+09
December 0.496564E+09 0.378395E+09 0.118169E+09 0.751797E+09 0.245855E+09
           
Annual Sum or Average 0.357565E+10 0.195660E+10 0.161905E+10 0.541183E+10 0.213600E+10
Minimum of Months 0.146229E+09 8576371.43 0.118169E+09 0.192091E+09 0.110597E+09
Maximum of Months 0.496564E+09 0.378395E+09 0.151381E+09 0.751797E+09 0.245855E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.366399E+09 0.268990E+09 97408702.42 0.542386E+09 0.194015E+09
February 0.261416E+09 0.161756E+09 99660556.79 0.362826E+09 0.160720E+09
March 0.230832E+09 0.112443E+09 0.118389E+09 0.315470E+09 0.189643E+09
April 0.186798E+09 72197917.93 0.114600E+09 0.270798E+09 0.145741E+09
May 0.136003E+09 16470167.27 0.119533E+09 0.161566E+09 0.136019E+09
June 0.115465E+09 6772047.95 0.108693E+09 0.141166E+09 94791978.36
July 0.125829E+09 13455320.07 0.112374E+09 0.181332E+09 80923366.83
August 0.161609E+09 50218052.04 0.111391E+09 0.264750E+09 83821348.31
September 0.214763E+09 0.106692E+09 0.108071E+09 0.347750E+09 97563405.35
October 0.290591E+09 0.195153E+09 95437466.31 0.474853E+09 0.109626E+09
November 0.341593E+09 0.242027E+09 99566205.17 0.505207E+09 0.166506E+09
December 0.392095E+09 0.298787E+09 93308334.56 0.583685E+09 0.192519E+09
           
Annual Sum or Average 0.282339E+10 0.154496E+10 0.127843E+10 0.415179E+10 0.165189E+10
Minimum of Months 0.115465E+09 6772047.95 93308334.56 0.141166E+09 80923366.83
Maximum of Months 0.392095E+09 0.298787E+09 0.119533E+09 0.583685E+09 0.194015E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_6_WALL_WEST_WINDOW

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.265521E+09 0.133901E+09 0.131620E+09 0.327150E+09 0.391669E+09
February 0.286426E+09 0.132386E+09 0.154039E+09 0.338106E+09 0.314459E+09
March 0.362688E+09 0.160278E+09 0.202410E+09 0.439577E+09 0.356986E+09
April 0.483730E+09 0.251482E+09 0.232247E+09 0.670891E+09 0.262225E+09
May 0.491022E+09 0.226458E+09 0.264564E+09 0.665431E+09 0.240391E+09
June 0.503264E+09 0.251292E+09 0.251972E+09 0.729399E+09 0.165523E+09
July 0.550654E+09 0.294353E+09 0.256300E+09 0.849912E+09 0.141613E+09
August 0.516705E+09 0.279782E+09 0.236923E+09 0.803898E+09 0.149662E+09
September 0.428535E+09 0.229221E+09 0.199314E+09 0.640247E+09 0.176679E+09
October 0.340146E+09 0.186368E+09 0.153778E+09 0.524428E+09 0.212810E+09
November 0.296219E+09 0.155051E+09 0.141168E+09 0.378815E+09 0.330872E+09
December 0.269240E+09 0.143959E+09 0.125281E+09 0.339019E+09 0.389831E+09
           
Annual Sum or Average 0.479415E+10 0.244453E+10 0.234962E+10 0.670687E+10 0.313272E+10
Minimum of Months 0.265521E+09 0.132386E+09 0.125281E+09 0.327150E+09 0.141613E+09
Maximum of Months 0.550654E+09 0.294353E+09 0.264564E+09 0.849912E+09 0.391669E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 55383852.68 0.00 55383852.68 39197142.67 0.209440E+09
February 62793579.01 0.00 62793579.01 39477708.15 0.170824E+09
March 85200912.64 780.17 85200132.47 62055421.75 0.196819E+09
April 95493362.34 768414.00 94724948.34 81232317.52 0.146452E+09
May 0.118708E+09 6190456.55 0.112517E+09 0.106056E+09 0.129963E+09
June 0.121773E+09 12029988.47 0.109743E+09 0.129652E+09 96941646.34
July 0.119193E+09 10114061.15 0.109079E+09 0.142408E+09 89791439.73
August 99102290.78 2201816.78 96900474.00 0.116494E+09 95086251.97
September 80955510.48 16100.43 80939410.05 90028307.27 0.107236E+09
October 66349884.71 0.00 66349884.71 86403839.10 0.122201E+09
November 58137116.95 0.00 58137116.95 43478712.08 0.179893E+09
December 51557659.69 0.00 51557659.69 36226830.80 0.209069E+09
           
Annual Sum or Average 0.101465E+10 31321617.54 0.983326E+09 0.972710E+09 0.175372E+10
Minimum of Months 51557659.69 0.00 51557659.69 36226830.80 89791439.73
Maximum of Months 0.121773E+09 12029988.47 0.112517E+09 0.142408E+09 0.209440E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_6_WALL_WEST_WINDOW

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.265521E+09 0.133901E+09 0.131620E+09 0.345479E+09 0.380570E+09
February 0.286426E+09 0.132386E+09 0.154039E+09 0.349981E+09 0.307885E+09
March 0.362688E+09 0.160278E+09 0.202410E+09 0.447467E+09 0.353592E+09
April 0.483730E+09 0.251482E+09 0.232247E+09 0.666803E+09 0.267485E+09
May 0.491022E+09 0.226458E+09 0.264564E+09 0.653277E+09 0.249444E+09
June 0.503264E+09 0.251292E+09 0.251972E+09 0.705169E+09 0.185550E+09
July 0.550654E+09 0.294353E+09 0.256300E+09 0.821809E+09 0.168764E+09
August 0.516705E+09 0.279782E+09 0.236923E+09 0.784242E+09 0.175428E+09
September 0.428535E+09 0.229221E+09 0.199314E+09 0.634757E+09 0.189746E+09
October 0.340146E+09 0.186368E+09 0.153778E+09 0.528457E+09 0.221054E+09
November 0.296219E+09 0.155051E+09 0.141168E+09 0.393857E+09 0.323501E+09
December 0.269240E+09 0.143959E+09 0.125281E+09 0.358014E+09 0.378241E+09
           
Annual Sum or Average 0.479415E+10 0.244453E+10 0.234962E+10 0.668931E+10 0.320126E+10
Minimum of Months 0.265521E+09 0.132386E+09 0.125281E+09 0.345479E+09 0.168764E+09
Maximum of Months 0.550654E+09 0.294353E+09 0.264564E+09 0.821809E+09 0.380570E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.537359E+09 0.394500E+09 0.142859E+09 0.782103E+09 0.296664E+09
February 0.383392E+09 0.237230E+09 0.146162E+09 0.523393E+09 0.243836E+09
March 0.338537E+09 0.164908E+09 0.173629E+09 0.456411E+09 0.283687E+09
April 0.273958E+09 0.105885E+09 0.168073E+09 0.398288E+09 0.211001E+09
May 0.199462E+09 24155080.95 0.175307E+09 0.242915E+09 0.193931E+09
June 0.169340E+09 9931858.23 0.159408E+09 0.216223E+09 0.131714E+09
July 0.184540E+09 19733518.19 0.164807E+09 0.276549E+09 0.110322E+09
August 0.237016E+09 73649592.75 0.163366E+09 0.395121E+09 0.116320E+09
September 0.314970E+09 0.156474E+09 0.158496E+09 0.511124E+09 0.140031E+09
October 0.426179E+09 0.286211E+09 0.139968E+09 0.692546E+09 0.162618E+09
November 0.500979E+09 0.354955E+09 0.146023E+09 0.730762E+09 0.252845E+09
December 0.575045E+09 0.438199E+09 0.136846E+09 0.842359E+09 0.294459E+09
           
Annual Sum or Average 0.414078E+10 0.226583E+10 0.187494E+10 0.606779E+10 0.243743E+10
Minimum of Months 0.169340E+09 9931858.23 0.136846E+09 0.216223E+09 0.110322E+09
Maximum of Months 0.575045E+09 0.438199E+09 0.175307E+09 0.842359E+09 0.296664E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: BANQUET_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.387672E+09 0.00 0.387672E+09 0.195093E+09 0.172104E+10
February 0.439538E+09 0.00 0.439538E+09 0.201945E+09 0.144557E+10
March 0.596384E+09 5460.98 0.596378E+09 0.353029E+09 0.160994E+10
April 0.668428E+09 5378694.26 0.663050E+09 0.518092E+09 0.116659E+10
May 0.830922E+09 43331554.67 0.787591E+09 0.684379E+09 0.103947E+10
June 0.852379E+09 84206730.00 0.768172E+09 0.890702E+09 0.748895E+09
July 0.834320E+09 70795746.72 0.763524E+09 0.997916E+09 0.665106E+09
August 0.693690E+09 15412133.73 0.678278E+09 0.796773E+09 0.717001E+09
September 0.566667E+09 112698.72 0.566554E+09 0.583992E+09 0.856711E+09
October 0.464432E+09 0.00 0.464432E+09 0.530344E+09 0.101972E+10
November 0.406944E+09 0.00 0.406944E+09 0.226195E+09 0.149651E+10
December 0.360890E+09 0.00 0.360890E+09 0.172162E+09 0.172772E+10
           
Annual Sum or Average 0.710227E+10 0.219243E+09 0.688302E+10 0.615062E+10 0.142143E+11
Minimum of Months 0.360890E+09 0.00 0.360890E+09 0.172162E+09 0.665106E+09
Maximum of Months 0.852379E+09 84206730.00 0.787591E+09 0.997916E+09 0.172772E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: DINING_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.387672E+09 0.00 0.387672E+09 0.174883E+09 0.177913E+10
February 0.439538E+09 0.00 0.439538E+09 0.181055E+09 0.149660E+10
March 0.596384E+09 5460.98 0.596378E+09 0.324352E+09 0.166310E+10
April 0.668428E+09 5378694.26 0.663050E+09 0.487066E+09 0.120127E+10
May 0.830922E+09 43331554.67 0.787591E+09 0.646885E+09 0.106872E+10
June 0.852379E+09 84206730.00 0.768172E+09 0.857032E+09 0.772225E+09
July 0.834320E+09 70795746.72 0.763524E+09 0.966948E+09 0.686198E+09
August 0.693690E+09 15412133.73 0.678278E+09 0.768502E+09 0.740858E+09
September 0.566667E+09 112698.72 0.566554E+09 0.558646E+09 0.886221E+09
October 0.464432E+09 0.00 0.464432E+09 0.507066E+09 0.105329E+10
November 0.406944E+09 0.00 0.406944E+09 0.205209E+09 0.154424E+10
December 0.360890E+09 0.00 0.360890E+09 0.153389E+09 0.178504E+10
           
Annual Sum or Average 0.710227E+10 0.219243E+09 0.688302E+10 0.583103E+10 0.146769E+11
Minimum of Months 0.360890E+09 0.00 0.360890E+09 0.153389E+09 0.686198E+09
Maximum of Months 0.852379E+09 84206730.00 0.787591E+09 0.966948E+09 0.178504E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 55383852.68 0.00 55383852.68 45168875.35 0.217551E+09
February 62793579.01 0.00 62793579.01 44936884.57 0.187557E+09
March 85200912.64 780.17 85200132.47 72611637.93 0.210929E+09
April 95493362.34 768414.00 94724948.34 0.105236E+09 0.155519E+09
May 0.118708E+09 6190456.55 0.112517E+09 0.138154E+09 0.143112E+09
June 0.121773E+09 12029988.47 0.109743E+09 0.171731E+09 0.104109E+09
July 0.119193E+09 10114061.15 0.109079E+09 0.190863E+09 92721957.90
August 99102290.78 2201816.78 96900474.00 0.157599E+09 97946510.86
September 80955510.48 16100.43 80939410.05 0.117515E+09 0.109370E+09
October 66349884.71 0.00 66349884.71 0.106679E+09 0.128922E+09
November 58137116.95 0.00 58137116.95 51414582.13 0.189184E+09
December 51557659.69 0.00 51557659.69 41714736.56 0.218147E+09
           
Annual Sum or Average 0.101465E+10 31321617.54 0.983326E+09 0.124362E+10 0.185507E+10
Minimum of Months 51557659.69 0.00 51557659.69 41714736.56 92721957.90
Maximum of Months 0.121773E+09 12029988.47 0.112517E+09 0.190863E+09 0.218147E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_FLR_6_WALL_EAST_WINDOW

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.557245E+09 0.297743E+09 0.259502E+09 0.749922E+09 0.762029E+09
February 0.531115E+09 0.243035E+09 0.288080E+09 0.649298E+09 0.664826E+09
March 0.717645E+09 0.320532E+09 0.397113E+09 0.926336E+09 0.743870E+09
April 0.885266E+09 0.444188E+09 0.441078E+09 0.131584E+10 0.566487E+09
May 0.861631E+09 0.359068E+09 0.502562E+09 0.124843E+10 0.541126E+09
June 0.829612E+09 0.360156E+09 0.469456E+09 0.130535E+10 0.402793E+09
July 0.970781E+09 0.482287E+09 0.488494E+09 0.164129E+10 0.358098E+09
August 0.959482E+09 0.509932E+09 0.449550E+09 0.163553E+10 0.369152E+09
September 0.677922E+09 0.311816E+09 0.366105E+09 0.111013E+10 0.404352E+09
October 0.617378E+09 0.316876E+09 0.300501E+09 0.103924E+10 0.463130E+09
November 0.543378E+09 0.275091E+09 0.268287E+09 0.734035E+09 0.668938E+09
December 0.539779E+09 0.300845E+09 0.238934E+09 0.723231E+09 0.762555E+09
           
Annual Sum or Average 0.869123E+10 0.422157E+10 0.446966E+10 0.130786E+11 0.670736E+10
Minimum of Months 0.531115E+09 0.243035E+09 0.238934E+09 0.649298E+09 0.358098E+09
Maximum of Months 0.970781E+09 0.509932E+09 0.502562E+09 0.164129E+10 0.762555E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.366399E+09 0.268990E+09 97408702.42 0.568230E+09 0.200601E+09
February 0.261416E+09 0.161756E+09 99660556.79 0.382072E+09 0.177468E+09
March 0.230832E+09 0.112443E+09 0.118389E+09 0.336117E+09 0.204740E+09
April 0.186798E+09 72197917.93 0.114600E+09 0.297543E+09 0.158825E+09
May 0.136003E+09 16470167.27 0.119533E+09 0.186639E+09 0.152444E+09
June 0.115465E+09 6772047.95 0.108693E+09 0.169899E+09 0.111197E+09
July 0.125829E+09 13455320.07 0.112374E+09 0.215526E+09 97241350.65
August 0.161609E+09 50218052.04 0.111391E+09 0.298718E+09 0.100683E+09
September 0.214763E+09 0.106692E+09 0.108071E+09 0.378656E+09 0.109383E+09
October 0.290591E+09 0.195153E+09 95437466.31 0.504461E+09 0.124169E+09
November 0.341593E+09 0.242027E+09 99566205.17 0.530851E+09 0.176244E+09
December 0.392095E+09 0.298787E+09 93308334.56 0.609649E+09 0.199909E+09
           
Annual Sum or Average 0.282339E+10 0.154496E+10 0.127843E+10 0.447836E+10 0.181290E+10
Minimum of Months 0.115465E+09 6772047.95 93308334.56 0.169899E+09 97241350.65
Maximum of Months 0.392095E+09 0.298787E+09 0.119533E+09 0.609649E+09 0.204740E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 70140154.89 0.00 70140154.89 42906869.95 0.274160E+09
February 79524105.76 0.00 79524105.76 46271646.60 0.222932E+09
March 0.107902E+09 988.04 0.107901E+09 77855812.46 0.250542E+09
April 0.120936E+09 973147.84 0.119963E+09 0.109237E+09 0.183502E+09
May 0.150336E+09 7839822.62 0.142496E+09 0.146375E+09 0.163528E+09
June 0.154218E+09 15235221.35 0.138983E+09 0.180592E+09 0.118537E+09
July 0.150951E+09 12808820.29 0.138142E+09 0.195485E+09 0.107961E+09
August 0.125507E+09 2788462.02 0.122718E+09 0.155316E+09 0.116772E+09
September 0.102525E+09 20390.18 0.102505E+09 0.115591E+09 0.137047E+09
October 84027942.54 0.00 84027942.54 0.103105E+09 0.164673E+09
November 73626990.37 0.00 73626990.37 49030835.91 0.237698E+09
December 65294522.88 0.00 65294522.88 38122350.99 0.275185E+09
           
Annual Sum or Average 0.128499E+10 39666852.34 0.124532E+10 0.125989E+10 0.225254E+10
Minimum of Months 65294522.88 0.00 65294522.88 38122350.99 0.107961E+09
Maximum of Months 0.154218E+09 15235221.35 0.142496E+09 0.195485E+09 0.275185E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 62754662.34 0.00 62754662.34 38388939.12 0.245269E+09
February 71150518.74 0.00 71150518.74 41399417.53 0.199459E+09
March 96539952.45 884.00 96539068.45 69657890.40 0.224161E+09
April 0.108202E+09 870679.06 0.107332E+09 97734885.20 0.164180E+09
May 0.134506E+09 7014319.00 0.127492E+09 0.130962E+09 0.146309E+09
June 0.137979E+09 13631010.27 0.124348E+09 0.161577E+09 0.106055E+09
July 0.135056E+09 11460100.04 0.123596E+09 0.174901E+09 96592830.58
August 0.112291E+09 2494847.54 0.109797E+09 0.138962E+09 0.104476E+09
September 91729547.13 18243.17 91711303.96 0.103419E+09 0.122616E+09
October 75180118.57 0.00 75180118.57 92248472.72 0.147333E+09
November 65874347.26 0.00 65874347.26 43868074.67 0.212667E+09
December 58419257.03 0.00 58419257.03 34108211.88 0.246175E+09
           
Annual Sum or Average 0.114968E+10 35490083.08 0.111419E+10 0.112723E+10 0.201529E+10
Minimum of Months 58419257.03 0.00 58419257.03 34108211.88 96592830.58
Maximum of Months 0.137979E+09 13631010.27 0.127492E+09 0.174901E+09 0.246175E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.136788E+10 0.100422E+10 0.363656E+09 0.203571E+10 0.729542E+09
February 0.975944E+09 0.603882E+09 0.372063E+09 0.136632E+10 0.610132E+09
March 0.861765E+09 0.419782E+09 0.441983E+09 0.119078E+10 0.710730E+09
April 0.697374E+09 0.269536E+09 0.427838E+09 0.102564E+10 0.555975E+09
May 0.507741E+09 61488042.30 0.446253E+09 0.615465E+09 0.523954E+09
June 0.431064E+09 25282072.96 0.405782E+09 0.528915E+09 0.383478E+09
July 0.469758E+09 50232719.31 0.419525E+09 0.669325E+09 0.343185E+09
August 0.603336E+09 0.187479E+09 0.415857E+09 0.976568E+09 0.360622E+09
September 0.801773E+09 0.398313E+09 0.403460E+09 0.129445E+10 0.402767E+09
October 0.108486E+10 0.728566E+09 0.356297E+09 0.175677E+10 0.458319E+09
November 0.127527E+10 0.903557E+09 0.371710E+09 0.189402E+10 0.637461E+09
December 0.146381E+10 0.111546E+10 0.348348E+09 0.218820E+10 0.725729E+09
           
Annual Sum or Average 0.105406E+11 0.576780E+10 0.477277E+10 0.155422E+11 0.644189E+10
Minimum of Months 0.431064E+09 25282072.96 0.348348E+09 0.528915E+09 0.343185E+09
Maximum of Months 0.146381E+10 0.111546E+10 0.446253E+09 0.218820E+10 0.729542E+09



Table of Contents

Report: WindowZoneSummaryMonthly

For: BASEMENT

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1016.06 360.43 691.88 507.95 183.94 0.00 0.00
February 766.59 325.66 546.53 338.18 208.36 0.00 0.00
March 608.67 335.19 435.89 212.33 223.56 0.00 0.00
April 543.76 270.89 364.49 140.88 223.62 0.00 0.00
May 330.29 237.25 256.82 31.10 225.72 0.00 0.00
June 294.99 177.77 225.30 13.21 212.09 0.00 0.00
July 350.95 156.85 237.61 25.41 212.20 0.00 0.00
August 499.35 169.75 305.17 94.83 210.34 0.00 0.00
September 675.52 203.11 419.06 208.19 210.87 0.00 0.00
October 884.37 225.50 548.73 368.52 180.22 0.00 0.00
November 981.22 326.07 666.54 472.26 194.28 0.00 0.00
December 1092.89 362.23 740.41 564.21 176.20 0.00 0.00
               
Annual Sum or Average 670.11 262.24 452.81 247.78 205.03 0.00 0.00
Minimum of Months 294.99 156.85 225.30 13.21 176.20 0.00 0.00
Maximum of Months 1092.89 362.23 740.41 564.21 225.72 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: MECH_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 2821.82 1101.73 1948.30 1430.34 517.96 0.00 0.00
February 2118.07 1013.97 1539.00 952.28 586.71 0.00 0.00
March 1675.39 1033.92 1227.43 597.91 629.52 0.00 0.00
April 1494.92 849.01 1026.39 396.71 629.69 0.00 0.00
May 888.77 751.15 723.18 87.58 635.60 0.00 0.00
June 792.26 572.02 634.43 37.21 597.22 0.00 0.00
July 959.18 496.83 669.08 71.55 597.53 0.00 0.00
August 1383.61 531.54 859.34 267.03 592.31 0.00 0.00
September 1876.55 634.94 1180.05 586.24 593.81 0.00 0.00
October 2459.42 698.59 1545.20 1037.72 507.48 0.00 0.00
November 2721.72 1006.88 1876.94 1329.86 547.08 0.00 0.00
December 3036.85 1106.75 2084.94 1588.78 496.16 0.00 0.00
               
Annual Sum or Average 1851.63 815.38 1275.09 697.73 577.36 0.00 0.00
Minimum of Months 792.26 496.83 634.43 37.21 496.16 0.00 0.00
Maximum of Months 3036.85 1106.75 2084.94 1588.78 635.60 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 3757.36 1452.67 2530.95 1858.09 672.86 0.00 0.00
February 2816.39 1356.61 1999.24 1237.07 762.17 0.00 0.00
March 2227.13 1393.12 1594.50 776.72 817.79 0.00 0.00
April 1990.85 1141.24 1333.34 515.34 818.00 0.00 0.00
May 1164.68 1032.70 939.45 113.77 825.68 0.00 0.00
June 1034.75 788.40 824.17 48.34 775.83 0.00 0.00
July 1266.53 678.72 869.17 92.94 776.23 0.00 0.00
August 1844.60 710.09 1116.33 346.89 769.44 0.00 0.00
September 2502.63 841.59 1532.95 761.56 771.39 0.00 0.00
October 3269.04 919.73 2007.30 1348.05 659.24 0.00 0.00
November 3619.17 1330.65 2438.25 1727.56 710.69 0.00 0.00
December 4037.76 1460.55 2708.45 2063.92 644.54 0.00 0.00
               
Annual Sum or Average 2459.89 1090.73 1656.41 906.39 750.02 0.00 0.00
Minimum of Months 1034.75 678.72 824.17 48.34 644.54 0.00 0.00
Maximum of Months 4037.76 1460.55 2708.45 2063.92 825.68 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 320.45 214.91 235.93 150.42 85.51 0.00 0.00
February 289.30 195.71 226.46 121.59 104.87 0.00 0.00
March 283.31 203.32 221.59 101.82 119.77 0.00 0.00
April 367.19 156.65 258.69 124.88 133.81 0.00 0.00
May 312.37 139.44 234.10 90.70 143.41 0.00 0.00
June 339.72 99.12 238.71 99.56 139.15 0.00 0.00
July 389.11 82.37 252.57 114.92 137.65 0.00 0.00
August 403.41 87.06 253.25 123.21 130.05 0.00 0.00
September 384.96 106.16 248.19 129.60 118.59 0.00 0.00
October 374.80 121.22 235.49 142.44 93.05 0.00 0.00
November 339.31 190.31 246.07 153.19 92.88 0.00 0.00
December 339.22 213.51 246.91 165.30 81.61 0.00 0.00
               
Annual Sum or Average 345.59 150.59 241.55 126.51 115.04 0.00 0.00
Minimum of Months 283.31 82.37 221.59 90.70 81.61 0.00 0.00
Maximum of Months 403.41 214.91 258.69 165.30 143.41 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 141.80 222.43 119.81 49.99 69.82 0.00 0.00
February 159.72 199.28 144.35 54.72 89.63 0.00 0.00
March 190.59 204.88 167.22 59.84 107.38 0.00 0.00
April 292.84 158.06 223.47 97.32 126.15 0.00 0.00
May 288.77 140.18 227.65 86.86 140.79 0.00 0.00
June 328.93 105.82 241.14 101.59 139.55 0.00 0.00
July 366.83 93.10 250.09 113.68 136.42 0.00 0.00
August 341.80 98.01 229.92 105.28 124.64 0.00 0.00
September 282.18 112.95 196.56 88.44 108.12 0.00 0.00
October 229.86 129.45 151.77 69.58 82.19 0.00 0.00
November 166.69 196.03 136.71 59.82 76.89 0.00 0.00
December 144.37 222.13 119.77 53.75 66.02 0.00 0.00
               
Annual Sum or Average 244.97 156.66 184.20 78.51 105.69 0.00 0.00
Minimum of Months 141.80 93.10 119.77 49.99 66.02 0.00 0.00
Maximum of Months 366.83 222.43 250.09 113.68 140.79 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 148.30 87.20 109.42 80.33 29.09 0.00 0.00
February 107.04 83.05 86.43 53.48 32.95 0.00 0.00
March 81.83 85.13 68.93 33.58 35.35 0.00 0.00
April 71.92 70.67 57.64 22.28 35.36 0.00 0.00
May 36.17 64.92 40.61 4.92 35.70 0.00 0.00
June 30.85 51.31 35.63 2.09 33.54 0.00 0.00
July 41.28 44.78 37.58 4.02 33.56 0.00 0.00
August 66.54 47.02 48.26 15.00 33.26 0.00 0.00
September 95.28 54.27 66.27 32.92 33.35 0.00 0.00
October 128.73 58.02 86.78 58.28 28.50 0.00 0.00
November 142.45 79.65 105.41 74.68 30.72 0.00 0.00
December 160.44 86.71 117.09 89.23 27.86 0.00 0.00
               
Annual Sum or Average 92.53 67.64 71.61 39.18 32.42 0.00 0.00
Minimum of Months 30.85 44.78 35.63 2.09 27.86 0.00 0.00
Maximum of Months 160.44 87.20 117.09 89.23 35.70 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 11.83 64.41 16.54 0.00 16.54 0.00 0.00
February 13.50 57.81 20.77 0.00 20.77 0.00 0.00
March 19.70 59.44 25.45 0.00 25.45 0.00 0.00
April 29.03 43.17 29.48 0.24 29.24 0.00 0.00
May 36.33 37.46 35.46 1.85 33.61 0.00 0.00
June 46.11 27.47 37.59 3.71 33.88 0.00 0.00
July 49.09 23.54 35.61 3.02 32.58 0.00 0.00
August 40.28 24.69 29.60 0.66 28.95 0.00 0.00
September 31.42 30.28 24.99 0.00 24.98 0.00 0.00
October 27.82 35.29 19.82 0.00 19.82 0.00 0.00
November 14.12 56.02 17.95 0.00 17.95 0.00 0.00
December 10.92 64.13 15.40 0.00 15.40 0.00 0.00
               
Annual Sum or Average 27.60 43.57 25.74 0.79 24.95 0.00 0.00
Minimum of Months 10.92 23.54 15.40 0.00 15.40 0.00 0.00
Maximum of Months 49.09 64.41 37.59 3.71 33.88 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 324.93 210.33 240.83 156.02 84.82 0.00 0.00
February 271.52 190.54 217.84 117.10 100.74 0.00 0.00
March 275.21 196.19 220.16 101.82 118.34 0.00 0.00
April 338.43 151.00 242.85 113.54 129.30 0.00 0.00
May 274.79 135.14 211.64 73.18 138.45 0.00 0.00
June 287.05 98.28 204.59 72.09 132.50 0.00 0.00
July 352.01 82.39 228.22 95.06 133.15 0.00 0.00
August 382.02 85.15 239.47 113.95 125.52 0.00 0.00
September 329.75 104.03 213.64 101.32 112.32 0.00 0.00
October 352.89 117.17 223.75 132.02 91.73 0.00 0.00
November 320.68 186.17 236.61 146.44 90.17 0.00 0.00
December 336.14 209.61 247.16 167.72 79.44 0.00 0.00
               
Annual Sum or Average 320.87 146.95 227.34 115.93 111.41 0.00 0.00
Minimum of Months 271.52 82.39 204.59 72.09 79.44 0.00 0.00
Maximum of Months 382.02 210.33 247.16 167.72 138.45 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 138.85 209.75 124.71 55.59 69.12 0.00 0.00
February 138.75 190.02 135.73 50.23 85.50 0.00 0.00
March 180.99 195.37 165.79 59.84 105.95 0.00 0.00
April 265.85 150.92 207.62 85.99 121.64 0.00 0.00
May 253.91 135.37 205.18 69.35 135.83 0.00 0.00
June 278.98 101.40 207.02 74.12 132.90 0.00 0.00
July 331.07 88.96 225.74 93.82 131.92 0.00 0.00
August 321.19 93.02 216.13 96.02 120.11 0.00 0.00
September 228.56 108.54 162.01 60.16 101.85 0.00 0.00
October 205.91 122.22 140.03 59.16 80.87 0.00 0.00
November 143.89 186.17 127.26 53.07 74.19 0.00 0.00
December 132.82 209.22 120.02 56.17 63.86 0.00 0.00
               
Annual Sum or Average 218.93 149.05 169.98 67.93 102.05 0.00 0.00
Minimum of Months 132.82 88.96 120.02 50.23 63.86 0.00 0.00
Maximum of Months 331.07 209.75 225.74 96.02 135.83 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 373.52 253.55 272.92 174.05 98.87 0.00 0.00
February 291.48 235.49 232.26 115.88 116.38 0.00 0.00
March 254.34 243.94 204.49 72.76 131.74 0.00 0.00
April 253.72 190.49 188.75 48.79 139.97 0.00 0.00
May 191.57 167.83 164.82 14.66 150.16 0.00 0.00
June 201.01 122.88 158.63 12.57 146.06 0.00 0.00
July 227.93 107.21 158.55 15.25 143.30 0.00 0.00
August 261.60 115.62 168.70 33.92 134.78 0.00 0.00
September 304.33 139.50 197.73 71.35 126.38 0.00 0.00
October 364.32 157.53 230.96 126.27 104.69 0.00 0.00
November 365.37 231.77 267.27 161.82 105.45 0.00 0.00
December 395.08 255.35 287.07 193.33 93.74 0.00 0.00
               
Annual Sum or Average 290.45 184.84 210.92 86.62 124.30 0.00 0.00
Minimum of Months 191.57 107.21 158.55 12.57 93.74 0.00 0.00
Maximum of Months 395.08 255.35 287.07 193.33 150.16 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 318.12 212.14 235.93 150.42 85.51 0.00 0.00
February 286.19 192.87 226.46 121.59 104.87 0.00 0.00
March 279.33 201.51 221.59 101.82 119.77 0.00 0.00
April 361.16 155.25 258.69 124.88 133.81 0.00 0.00
May 306.53 138.30 234.10 90.70 143.41 0.00 0.00
June 333.59 98.16 238.71 99.56 139.15 0.00 0.00
July 383.27 81.34 252.57 114.92 137.65 0.00 0.00
August 397.73 85.92 253.25 123.21 130.05 0.00 0.00
September 379.86 104.50 248.19 129.60 118.59 0.00 0.00
October 371.52 118.82 235.49 142.44 93.05 0.00 0.00
November 336.48 187.32 246.07 153.19 92.88 0.00 0.00
December 337.21 210.13 246.91 165.30 81.61 0.00 0.00
               
Annual Sum or Average 341.24 148.63 241.55 126.51 115.04 0.00 0.00
Minimum of Months 279.33 81.34 221.59 90.70 81.61 0.00 0.00
Maximum of Months 397.73 212.14 258.69 165.30 143.41 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 141.39 218.05 119.81 49.99 69.82 0.00 0.00
February 158.56 195.45 144.35 54.72 89.63 0.00 0.00
March 187.56 202.83 167.22 59.84 107.38 0.00 0.00
April 286.70 157.80 223.47 97.32 126.15 0.00 0.00
May 282.16 140.31 227.65 86.86 140.79 0.00 0.00
June 320.73 107.64 241.14 101.59 139.55 0.00 0.00
July 358.96 95.50 250.09 113.68 136.42 0.00 0.00
August 335.19 99.89 229.92 105.28 124.64 0.00 0.00
September 277.52 112.47 196.56 88.44 108.12 0.00 0.00
October 228.20 126.79 151.77 69.58 82.19 0.00 0.00
November 166.12 191.60 136.71 59.82 76.89 0.00 0.00
December 144.74 216.83 119.77 53.75 66.02 0.00 0.00
               
Annual Sum or Average 241.08 155.24 184.20 78.51 105.69 0.00 0.00
Minimum of Months 141.39 95.50 119.77 49.99 66.02 0.00 0.00
Maximum of Months 358.96 218.05 250.09 113.68 140.79 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 292.00 110.76 200.63 147.29 53.34 0.00 0.00
February 216.35 100.79 158.48 98.06 60.42 0.00 0.00
March 170.40 105.92 126.40 61.57 64.83 0.00 0.00
April 153.66 81.40 105.69 40.85 64.84 0.00 0.00
May 90.69 72.41 74.47 9.02 65.45 0.00 0.00
June 83.42 50.82 65.33 3.83 61.50 0.00 0.00
July 103.25 41.19 68.90 7.37 61.53 0.00 0.00
August 147.52 43.43 88.49 27.50 60.99 0.00 0.00
September 197.19 54.02 121.52 60.37 61.15 0.00 0.00
October 258.57 60.71 159.12 106.86 52.26 0.00 0.00
November 281.93 97.55 193.28 136.94 56.34 0.00 0.00
December 314.50 109.94 214.70 163.60 51.09 0.00 0.00
               
Annual Sum or Average 192.41 77.29 131.30 71.85 59.45 0.00 0.00
Minimum of Months 83.42 41.19 65.33 3.83 51.09 0.00 0.00
Maximum of Months 314.50 110.76 214.70 163.60 65.45 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 72.84 642.56 144.74 0.00 144.74 0.00 0.00
February 83.48 597.54 181.69 0.00 181.69 0.00 0.00
March 131.81 601.08 222.66 0.00 222.66 0.00 0.00
April 199.88 450.07 257.88 2.08 255.81 0.00 0.00
May 255.52 388.10 310.23 16.18 294.05 0.00 0.00
June 343.64 288.93 328.85 32.49 296.36 0.00 0.00
July 372.58 248.32 311.50 26.43 285.07 0.00 0.00
August 297.48 267.70 258.99 5.75 253.24 0.00 0.00
September 225.31 330.52 218.62 0.04 218.58 0.00 0.00
October 198.01 380.72 173.40 0.00 173.40 0.00 0.00
November 87.27 577.36 157.00 0.00 157.00 0.00 0.00
December 64.28 645.06 134.74 0.00 134.74 0.00 0.00
               
Annual Sum or Average 195.03 450.73 225.21 6.95 218.26 0.00 0.00
Minimum of Months 64.28 248.32 134.74 0.00 134.74 0.00 0.00
Maximum of Months 372.58 645.06 328.85 32.49 296.36 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DINING_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 65.29 664.25 144.74 0.00 144.74 0.00 0.00
February 74.84 618.63 181.69 0.00 181.69 0.00 0.00
March 121.10 620.93 222.66 0.00 222.66 0.00 0.00
April 187.91 463.45 257.88 2.08 255.81 0.00 0.00
May 241.52 399.01 310.23 16.18 294.05 0.00 0.00
June 330.64 297.93 328.85 32.49 296.36 0.00 0.00
July 361.02 256.20 311.50 26.43 285.07 0.00 0.00
August 286.93 276.60 258.99 5.75 253.24 0.00 0.00
September 215.53 341.91 218.62 0.04 218.58 0.00 0.00
October 189.32 393.25 173.40 0.00 173.40 0.00 0.00
November 79.17 595.77 157.00 0.00 157.00 0.00 0.00
December 57.27 666.46 134.74 0.00 134.74 0.00 0.00
               
Annual Sum or Average 184.90 465.40 225.21 6.95 218.26 0.00 0.00
Minimum of Months 57.27 256.20 134.74 0.00 134.74 0.00 0.00
Maximum of Months 361.02 666.46 328.85 32.49 296.36 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 500.01 431.64 365.53 211.59 153.93 0.00 0.00
February 438.79 419.59 353.56 167.32 186.23 0.00 0.00
March 491.57 426.04 385.93 161.65 224.28 0.00 0.00
April 658.87 335.65 450.45 199.52 250.93 0.00 0.00
May 583.86 308.86 416.79 142.52 274.27 0.00 0.00
June 632.64 235.70 411.59 146.20 265.39 0.00 0.00
July 762.64 202.75 453.93 188.87 265.06 0.00 0.00
August 779.76 210.74 455.57 209.96 245.61 0.00 0.00
September 618.52 239.21 375.63 161.47 214.16 0.00 0.00
October 613.23 264.45 363.77 191.17 172.60 0.00 0.00
November 500.43 391.66 363.85 199.51 164.35 0.00 0.00
December 503.81 431.39 367.17 223.88 143.29 0.00 0.00
               
Annual Sum or Average 591.46 324.29 397.30 183.85 213.45 0.00 0.00
Minimum of Months 438.79 202.75 353.56 142.52 143.29 0.00 0.00
Maximum of Months 779.76 431.64 455.57 223.88 274.27 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 776.00 451.91 560.32 374.93 185.39 0.00 0.00
February 593.13 418.91 465.70 249.62 216.08 0.00 0.00
March 496.67 439.59 398.08 156.73 241.35 0.00 0.00
April 475.04 348.13 357.45 104.70 252.75 0.00 0.00
May 329.74 307.71 295.92 28.50 267.41 0.00 0.00
June 330.54 229.07 279.04 20.89 258.15 0.00 0.00
July 384.00 200.32 282.17 27.82 254.35 0.00 0.00
August 473.29 216.05 314.04 71.97 242.07 0.00 0.00
September 583.67 255.34 384.27 153.68 230.58 0.00 0.00
October 724.97 283.74 464.48 272.02 192.47 0.00 0.00
November 755.60 408.73 545.82 348.59 197.23 0.00 0.00
December 827.93 449.59 592.71 416.47 176.25 0.00 0.00
               
Annual Sum or Average 562.58 333.65 411.44 185.28 226.16 0.00 0.00
Minimum of Months 329.74 200.32 279.04 20.89 176.25 0.00 0.00
Maximum of Months 827.93 451.91 592.71 416.47 267.41 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BASEMENT

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.272142E+10 0.965380E+09 0.185314E+10 0.136048E+10 0.492663E+09 0.00 0.00
February 0.185454E+10 0.787826E+09 0.132217E+10 0.818116E+09 0.504052E+09 0.00 0.00
March 0.163027E+10 0.897761E+09 0.116748E+10 0.568705E+09 0.598776E+09 0.00 0.00
April 0.140942E+10 0.702136E+09 0.944769E+09 0.365158E+09 0.579611E+09 0.00 0.00
May 0.884637E+09 0.635446E+09 0.687861E+09 83301651.90 0.604559E+09 0.00 0.00
June 0.764614E+09 0.460786E+09 0.583982E+09 34251187.10 0.549731E+09 0.00 0.00
July 0.939993E+09 0.420117E+09 0.636401E+09 68053370.08 0.568348E+09 0.00 0.00
August 0.133747E+10 0.454655E+09 0.817369E+09 0.253989E+09 0.563379E+09 0.00 0.00
September 0.175094E+10 0.526449E+09 0.108621E+10 0.539619E+09 0.546586E+09 0.00 0.00
October 0.236870E+10 0.603975E+09 0.146973E+10 0.987033E+09 0.482692E+09 0.00 0.00
November 0.254333E+10 0.845186E+09 0.172768E+10 0.122410E+10 0.503575E+09 0.00 0.00
December 0.292720E+10 0.970190E+09 0.198311E+10 0.151118E+10 0.471925E+09 0.00 0.00
               
Annual Sum or Average 0.211325E+11 0.826991E+10 0.142799E+11 0.781399E+10 0.646590E+10 0.00 0.00
Minimum of Months 0.764614E+09 0.420117E+09 0.583982E+09 34251187.10 0.471925E+09 0.00 0.00
Maximum of Months 0.292720E+10 0.970190E+09 0.198311E+10 0.151118E+10 0.604559E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: MECH_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.755795E+10 0.295088E+10 0.521833E+10 0.383102E+10 0.138731E+10 0.00 0.00
February 0.512403E+10 0.245299E+10 0.372314E+10 0.230376E+10 0.141938E+10 0.00 0.00
March 0.448738E+10 0.276925E+10 0.328755E+10 0.160144E+10 0.168611E+10 0.00 0.00
April 0.387483E+10 0.220063E+10 0.266041E+10 0.102826E+10 0.163215E+10 0.00 0.00
May 0.238048E+10 0.201187E+10 0.193697E+10 0.234572E+09 0.170240E+10 0.00 0.00
June 0.205353E+10 0.148268E+10 0.164445E+10 96449084.55 0.154801E+10 0.00 0.00
July 0.256907E+10 0.133070E+10 0.179206E+10 0.191634E+09 0.160043E+10 0.00 0.00
August 0.370587E+10 0.142369E+10 0.230166E+10 0.715217E+09 0.158644E+10 0.00 0.00
September 0.486402E+10 0.164575E+10 0.305868E+10 0.151953E+10 0.153915E+10 0.00 0.00
October 0.658732E+10 0.187109E+10 0.413865E+10 0.277942E+10 0.135923E+10 0.00 0.00
November 0.705471E+10 0.260984E+10 0.486503E+10 0.344700E+10 0.141803E+10 0.00 0.00
December 0.813390E+10 0.296432E+10 0.558430E+10 0.425539E+10 0.132891E+10 0.00 0.00
               
Annual Sum or Average 0.583931E+11 0.257137E+11 0.402112E+11 0.220037E+11 0.182075E+11 0.00 0.00
Minimum of Months 0.205353E+10 0.133070E+10 0.164445E+10 96449084.55 0.132891E+10 0.00 0.00
Maximum of Months 0.813390E+10 0.296432E+10 0.558430E+10 0.425539E+10 0.170240E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.100637E+11 0.389083E+10 0.677891E+10 0.497672E+10 0.180219E+10 0.00 0.00
February 0.681340E+10 0.328191E+10 0.483657E+10 0.299272E+10 0.184385E+10 0.00 0.00
March 0.596514E+10 0.373133E+10 0.427071E+10 0.208036E+10 0.219036E+10 0.00 0.00
April 0.516028E+10 0.295811E+10 0.345602E+10 0.133577E+10 0.212025E+10 0.00 0.00
May 0.311948E+10 0.276599E+10 0.251623E+10 0.304722E+09 0.221151E+10 0.00 0.00
June 0.268208E+10 0.204353E+10 0.213624E+10 0.125293E+09 0.201095E+10 0.00 0.00
July 0.339229E+10 0.181788E+10 0.232799E+10 0.248943E+09 0.207905E+10 0.00 0.00
August 0.494059E+10 0.190190E+10 0.298998E+10 0.929108E+09 0.206087E+10 0.00 0.00
September 0.648682E+10 0.218141E+10 0.397340E+10 0.197396E+10 0.199944E+10 0.00 0.00
October 0.875579E+10 0.246341E+10 0.537634E+10 0.361063E+10 0.176572E+10 0.00 0.00
November 0.938089E+10 0.344904E+10 0.631995E+10 0.447785E+10 0.184211E+10 0.00 0.00
December 0.108147E+11 0.391195E+10 0.725432E+10 0.552799E+10 0.172633E+10 0.00 0.00
               
Annual Sum or Average 0.775752E+11 0.343973E+11 0.522367E+11 0.285840E+11 0.236526E+11 0.00 0.00
Minimum of Months 0.268208E+10 0.181788E+10 0.213624E+10 0.125293E+09 0.172633E+10 0.00 0.00
Maximum of Months 0.108147E+11 0.391195E+10 0.725432E+10 0.552799E+10 0.221151E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.858281E+09 0.575610E+09 0.631920E+09 0.402891E+09 0.229029E+09 0.00 0.00
February 0.699879E+09 0.473463E+09 0.547842E+09 0.294142E+09 0.253700E+09 0.00 0.00
March 0.758817E+09 0.544583E+09 0.593520E+09 0.272721E+09 0.320799E+09 0.00 0.00
April 0.951757E+09 0.406032E+09 0.670528E+09 0.323680E+09 0.346848E+09 0.00 0.00
May 0.836653E+09 0.373488E+09 0.627025E+09 0.242928E+09 0.384097E+09 0.00 0.00
June 0.880557E+09 0.256925E+09 0.618729E+09 0.258064E+09 0.360665E+09 0.00 0.00
July 0.104219E+10 0.220611E+09 0.676483E+09 0.307809E+09 0.368674E+09 0.00 0.00
August 0.108049E+10 0.233187E+09 0.678314E+09 0.330001E+09 0.348314E+09 0.00 0.00
September 0.997827E+09 0.275163E+09 0.643298E+09 0.335913E+09 0.307385E+09 0.00 0.00
October 0.100388E+10 0.324689E+09 0.630737E+09 0.381522E+09 0.249215E+09 0.00 0.00
November 0.879502E+09 0.493274E+09 0.637811E+09 0.397077E+09 0.240734E+09 0.00 0.00
December 0.908563E+09 0.571861E+09 0.661336E+09 0.442746E+09 0.218589E+09 0.00 0.00
               
Annual Sum or Average 0.108984E+11 0.474889E+10 0.761754E+10 0.398949E+10 0.362805E+10 0.00 0.00
Minimum of Months 0.699879E+09 0.220611E+09 0.547842E+09 0.242928E+09 0.218589E+09 0.00 0.00
Maximum of Months 0.108049E+10 0.575610E+09 0.678314E+09 0.442746E+09 0.384097E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.379792E+09 0.595749E+09 0.320905E+09 0.133901E+09 0.187004E+09 0.00 0.00
February 0.386384E+09 0.482095E+09 0.349219E+09 0.132386E+09 0.216833E+09 0.00 0.00
March 0.510470E+09 0.548742E+09 0.447889E+09 0.160279E+09 0.287610E+09 0.00 0.00
April 0.759054E+09 0.409694E+09 0.579223E+09 0.252251E+09 0.326972E+09 0.00 0.00
May 0.773433E+09 0.375471E+09 0.609729E+09 0.232648E+09 0.377081E+09 0.00 0.00
June 0.852577E+09 0.274288E+09 0.625037E+09 0.263322E+09 0.361715E+09 0.00 0.00
July 0.982516E+09 0.249354E+09 0.669847E+09 0.304467E+09 0.365379E+09 0.00 0.00
August 0.915466E+09 0.262513E+09 0.615807E+09 0.281984E+09 0.333823E+09 0.00 0.00
September 0.731415E+09 0.292757E+09 0.509491E+09 0.229238E+09 0.280253E+09 0.00 0.00
October 0.615657E+09 0.346723E+09 0.406496E+09 0.186368E+09 0.220128E+09 0.00 0.00
November 0.432052E+09 0.508106E+09 0.354356E+09 0.155051E+09 0.199305E+09 0.00 0.00
December 0.386677E+09 0.594940E+09 0.320798E+09 0.143959E+09 0.176839E+09 0.00 0.00
               
Annual Sum or Average 0.772549E+10 0.494043E+10 0.580880E+10 0.247585E+10 0.333294E+10 0.00 0.00
Minimum of Months 0.379792E+09 0.249354E+09 0.320798E+09 0.132386E+09 0.176839E+09 0.00 0.00
Maximum of Months 0.982516E+09 0.595749E+09 0.669847E+09 0.304467E+09 0.377081E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.397197E+09 0.233546E+09 0.293061E+09 0.215149E+09 77911467.45 0.00 0.00
February 0.258946E+09 0.200917E+09 0.209091E+09 0.129379E+09 79712592.74 0.00 0.00
March 0.219183E+09 0.228011E+09 0.184629E+09 89936327.87 94692605.60 0.00 0.00
April 0.186412E+09 0.183170E+09 0.149409E+09 57746850.06 91662135.38 0.00 0.00
May 96865478.16 0.173892E+09 0.108781E+09 13173513.96 95607483.13 0.00 0.00
June 79972363.84 0.133001E+09 92353413.13 5416561.15 86936851.98 0.00 0.00
July 0.110551E+09 0.119937E+09 0.100643E+09 10762115.76 89881160.52 0.00 0.00
August 0.178222E+09 0.125935E+09 0.129262E+09 40166453.60 89095338.36 0.00 0.00
September 0.246958E+09 0.140662E+09 0.171776E+09 85336561.19 86439337.30 0.00 0.00
October 0.344782E+09 0.155414E+09 0.232427E+09 0.156092E+09 76334792.12 0.00 0.00
November 0.369242E+09 0.206458E+09 0.273220E+09 0.193583E+09 79637126.46 0.00 0.00
December 0.429724E+09 0.232254E+09 0.313614E+09 0.238982E+09 74631825.39 0.00 0.00
               
Annual Sum or Average 0.291805E+10 0.213320E+10 0.225827E+10 0.123572E+10 0.102254E+10 0.00 0.00
Minimum of Months 79972363.84 0.119937E+09 92353413.13 5416561.15 74631825.39 0.00 0.00
Maximum of Months 0.429724E+09 0.233546E+09 0.313614E+09 0.238982E+09 95607483.13 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 31686574.94 0.172506E+09 44312955.30 0.00 44312955.30 0.00 0.00
February 32658707.69 0.139861E+09 50241522.13 0.00 50241522.13 0.00 0.00
March 52753290.28 0.159213E+09 68169765.21 624.22 68169140.99 0.00 0.00
April 75246460.74 0.111898E+09 76404816.42 614812.68 75790003.74 0.00 0.00
May 97299494.08 0.100323E+09 94978755.02 4953021.70 90025733.32 0.00 0.00
June 0.119513E+09 71204884.02 97431324.50 9625266.49 87806058.00 0.00 0.00
July 0.131486E+09 63044846.23 95367114.15 8092321.46 87274792.68 0.00 0.00
August 0.107885E+09 66141105.79 79292341.88 1761686.91 77530654.97 0.00 0.00
September 81447027.67 78490635.24 64772993.27 12882.05 64760111.22 0.00 0.00
October 74525464.13 94533971.54 53086943.81 0.00 53086943.81 0.00 0.00
November 36598498.63 0.145208E+09 46515858.69 0.00 46515858.69 0.00 0.00
December 29253268.86 0.171756E+09 41251595.16 0.00 41251595.16 0.00 0.00
               
Annual Sum or Average 0.870354E+09 0.137418E+10 0.811826E+09 25060615.52 0.786765E+09 0.00 0.00
Minimum of Months 29253268.86 63044846.23 41251595.16 0.00 41251595.16 0.00 0.00
Maximum of Months 0.131486E+09 0.172506E+09 97431324.50 9625266.49 90025733.32 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.870285E+09 0.563350E+09 0.645041E+09 0.417872E+09 0.227169E+09 0.00 0.00
February 0.656863E+09 0.460945E+09 0.526993E+09 0.283282E+09 0.243711E+09 0.00 0.00
March 0.737132E+09 0.525483E+09 0.589680E+09 0.272720E+09 0.316960E+09 0.00 0.00
April 0.877209E+09 0.391393E+09 0.629463E+09 0.294307E+09 0.335155E+09 0.00 0.00
May 0.735995E+09 0.361947E+09 0.566849E+09 0.196017E+09 0.370832E+09 0.00 0.00
June 0.744046E+09 0.254748E+09 0.530300E+09 0.186863E+09 0.343438E+09 0.00 0.00
July 0.942822E+09 0.220685E+09 0.611254E+09 0.254616E+09 0.356638E+09 0.00 0.00
August 0.102319E+10 0.228068E+09 0.641384E+09 0.305202E+09 0.336182E+09 0.00 0.00
September 0.854723E+09 0.269653E+09 0.553748E+09 0.262611E+09 0.291136E+09 0.00 0.00
October 0.945177E+09 0.313826E+09 0.599302E+09 0.353603E+09 0.245699E+09 0.00 0.00
November 0.831193E+09 0.482546E+09 0.613301E+09 0.379582E+09 0.233719E+09 0.00 0.00
December 0.900312E+09 0.561423E+09 0.662004E+09 0.449220E+09 0.212784E+09 0.00 0.00
               
Annual Sum or Average 0.101189E+11 0.463407E+10 0.716932E+10 0.365590E+10 0.351342E+10 0.00 0.00
Minimum of Months 0.656863E+09 0.220685E+09 0.526993E+09 0.186863E+09 0.212784E+09 0.00 0.00
Maximum of Months 0.102319E+10 0.563350E+09 0.662004E+09 0.449220E+09 0.370832E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.371898E+09 0.561786E+09 0.334026E+09 0.148882E+09 0.185144E+09 0.00 0.00
February 0.335668E+09 0.459698E+09 0.328370E+09 0.121526E+09 0.206844E+09 0.00 0.00
March 0.484771E+09 0.523274E+09 0.444049E+09 0.160278E+09 0.283771E+09 0.00 0.00
April 0.689077E+09 0.391179E+09 0.538158E+09 0.222878E+09 0.315280E+09 0.00 0.00
May 0.680082E+09 0.362585E+09 0.549554E+09 0.185737E+09 0.363816E+09 0.00 0.00
June 0.723107E+09 0.262826E+09 0.536608E+09 0.192121E+09 0.344488E+09 0.00 0.00
July 0.886741E+09 0.238273E+09 0.604618E+09 0.251275E+09 0.353343E+09 0.00 0.00
August 0.860279E+09 0.249155E+09 0.578877E+09 0.257186E+09 0.321691E+09 0.00 0.00
September 0.592426E+09 0.281324E+09 0.419941E+09 0.155935E+09 0.264005E+09 0.00 0.00
October 0.551510E+09 0.327350E+09 0.375061E+09 0.158449E+09 0.216611E+09 0.00 0.00
November 0.372959E+09 0.482560E+09 0.329845E+09 0.137555E+09 0.192290E+09 0.00 0.00
December 0.355753E+09 0.560367E+09 0.321466E+09 0.150433E+09 0.171033E+09 0.00 0.00
               
Annual Sum or Average 0.690427E+10 0.470038E+10 0.536057E+10 0.214226E+10 0.321832E+10 0.00 0.00
Minimum of Months 0.335668E+09 0.238273E+09 0.321466E+09 0.121526E+09 0.171033E+09 0.00 0.00
Maximum of Months 0.886741E+09 0.561786E+09 0.604618E+09 0.257186E+09 0.363816E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.100044E+10 0.679106E+09 0.730978E+09 0.466169E+09 0.264809E+09 0.00 0.00
February 0.705149E+09 0.569702E+09 0.561883E+09 0.280328E+09 0.281555E+09 0.00 0.00
March 0.681237E+09 0.653370E+09 0.547718E+09 0.194868E+09 0.352850E+09 0.00 0.00
April 0.657641E+09 0.493760E+09 0.489246E+09 0.126453E+09 0.362793E+09 0.00 0.00
May 0.513094E+09 0.449508E+09 0.441454E+09 39273247.18 0.402181E+09 0.00 0.00
June 0.521009E+09 0.318515E+09 0.411173E+09 32587736.49 0.378585E+09 0.00 0.00
July 0.610500E+09 0.287163E+09 0.424663E+09 40849193.83 0.383814E+09 0.00 0.00
August 0.700680E+09 0.309668E+09 0.451848E+09 90845939.63 0.361002E+09 0.00 0.00
September 0.788828E+09 0.361572E+09 0.512511E+09 0.184929E+09 0.327582E+09 0.00 0.00
October 0.975807E+09 0.421938E+09 0.618608E+09 0.338207E+09 0.280400E+09 0.00 0.00
November 0.947029E+09 0.600737E+09 0.692760E+09 0.419440E+09 0.273320E+09 0.00 0.00
December 0.105817E+10 0.683922E+09 0.768878E+09 0.517807E+09 0.251071E+09 0.00 0.00
               
Annual Sum or Average 0.915958E+10 0.582896E+10 0.665172E+10 0.273176E+10 0.391996E+10 0.00 0.00
Minimum of Months 0.513094E+09 0.287163E+09 0.411173E+09 32587736.49 0.251071E+09 0.00 0.00
Maximum of Months 0.105817E+10 0.683922E+09 0.768878E+09 0.517807E+09 0.402181E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.852055E+09 0.568202E+09 0.631920E+09 0.402891E+09 0.229029E+09 0.00 0.00
February 0.692352E+09 0.466599E+09 0.547842E+09 0.294142E+09 0.253700E+09 0.00 0.00
March 0.748145E+09 0.539727E+09 0.593520E+09 0.272721E+09 0.320799E+09 0.00 0.00
April 0.936138E+09 0.402415E+09 0.670528E+09 0.323680E+09 0.346848E+09 0.00 0.00
May 0.821014E+09 0.370427E+09 0.627025E+09 0.242928E+09 0.384097E+09 0.00 0.00
June 0.864668E+09 0.254419E+09 0.618729E+09 0.258064E+09 0.360665E+09 0.00 0.00
July 0.102656E+10 0.217854E+09 0.676483E+09 0.307809E+09 0.368674E+09 0.00 0.00
August 0.106529E+10 0.230128E+09 0.678314E+09 0.330001E+09 0.348314E+09 0.00 0.00
September 0.984610E+09 0.270856E+09 0.643298E+09 0.335913E+09 0.307385E+09 0.00 0.00
October 0.995092E+09 0.318247E+09 0.630737E+09 0.381522E+09 0.249215E+09 0.00 0.00
November 0.872167E+09 0.485523E+09 0.637811E+09 0.397077E+09 0.240734E+09 0.00 0.00
December 0.903177E+09 0.562823E+09 0.661336E+09 0.442746E+09 0.218589E+09 0.00 0.00
               
Annual Sum or Average 0.107613E+11 0.468722E+10 0.761754E+10 0.398949E+10 0.362805E+10 0.00 0.00
Minimum of Months 0.692352E+09 0.217854E+09 0.547842E+09 0.242928E+09 0.218589E+09 0.00 0.00
Maximum of Months 0.106529E+10 0.568202E+09 0.678314E+09 0.442746E+09 0.384097E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.378704E+09 0.584038E+09 0.320905E+09 0.133901E+09 0.187004E+09 0.00 0.00
February 0.383583E+09 0.472834E+09 0.349219E+09 0.132386E+09 0.216833E+09 0.00 0.00
March 0.502366E+09 0.543255E+09 0.447889E+09 0.160279E+09 0.287610E+09 0.00 0.00
April 0.743119E+09 0.409020E+09 0.579223E+09 0.252251E+09 0.326972E+09 0.00 0.00
May 0.755746E+09 0.375820E+09 0.609729E+09 0.232648E+09 0.377081E+09 0.00 0.00
June 0.831323E+09 0.278994E+09 0.625037E+09 0.263322E+09 0.361715E+09 0.00 0.00
July 0.961436E+09 0.255775E+09 0.669847E+09 0.304467E+09 0.365379E+09 0.00 0.00
August 0.897761E+09 0.267540E+09 0.615807E+09 0.281984E+09 0.333823E+09 0.00 0.00
September 0.719327E+09 0.291524E+09 0.509491E+09 0.229238E+09 0.280253E+09 0.00 0.00
October 0.611202E+09 0.339596E+09 0.406496E+09 0.186368E+09 0.220128E+09 0.00 0.00
November 0.430574E+09 0.496632E+09 0.354356E+09 0.155051E+09 0.199305E+09 0.00 0.00
December 0.387684E+09 0.580753E+09 0.320798E+09 0.143959E+09 0.176839E+09 0.00 0.00
               
Annual Sum or Average 0.760283E+10 0.489578E+10 0.580880E+10 0.247585E+10 0.333294E+10 0.00 0.00
Minimum of Months 0.378704E+09 0.255775E+09 0.320798E+09 0.132386E+09 0.176839E+09 0.00 0.00
Maximum of Months 0.961436E+09 0.584038E+09 0.669847E+09 0.304467E+09 0.377081E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.782103E+09 0.296664E+09 0.537359E+09 0.394500E+09 0.142859E+09 0.00 0.00
February 0.523393E+09 0.243836E+09 0.383392E+09 0.237230E+09 0.146162E+09 0.00 0.00
March 0.456411E+09 0.283687E+09 0.338537E+09 0.164908E+09 0.173629E+09 0.00 0.00
April 0.398288E+09 0.211001E+09 0.273958E+09 0.105885E+09 0.168073E+09 0.00 0.00
May 0.242915E+09 0.193931E+09 0.199462E+09 24155080.95 0.175307E+09 0.00 0.00
June 0.216223E+09 0.131714E+09 0.169340E+09 9931858.23 0.159408E+09 0.00 0.00
July 0.276549E+09 0.110322E+09 0.184540E+09 19733518.19 0.164807E+09 0.00 0.00
August 0.395121E+09 0.116320E+09 0.237016E+09 73649592.75 0.163366E+09 0.00 0.00
September 0.511124E+09 0.140031E+09 0.314970E+09 0.156474E+09 0.158496E+09 0.00 0.00
October 0.692546E+09 0.162618E+09 0.426179E+09 0.286211E+09 0.139968E+09 0.00 0.00
November 0.730762E+09 0.252845E+09 0.500979E+09 0.354955E+09 0.146023E+09 0.00 0.00
December 0.842359E+09 0.294459E+09 0.575045E+09 0.438199E+09 0.136846E+09 0.00 0.00
               
Annual Sum or Average 0.606779E+10 0.243743E+10 0.414078E+10 0.226583E+10 0.187494E+10 0.00 0.00
Minimum of Months 0.216223E+09 0.110322E+09 0.169340E+09 9931858.23 0.136846E+09 0.00 0.00
Maximum of Months 0.842359E+09 0.296664E+09 0.575045E+09 0.438199E+09 0.175307E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.195093E+09 0.172104E+10 0.387672E+09 0.00 0.387672E+09 0.00 0.00
February 0.201945E+09 0.144557E+10 0.439538E+09 0.00 0.439538E+09 0.00 0.00
March 0.353029E+09 0.160994E+10 0.596384E+09 5460.98 0.596378E+09 0.00 0.00
April 0.518092E+09 0.116659E+10 0.668428E+09 5378694.26 0.663050E+09 0.00 0.00
May 0.684379E+09 0.103947E+10 0.830922E+09 43331554.67 0.787591E+09 0.00 0.00
June 0.890702E+09 0.748895E+09 0.852379E+09 84206730.00 0.768172E+09 0.00 0.00
July 0.997916E+09 0.665106E+09 0.834320E+09 70795746.72 0.763524E+09 0.00 0.00
August 0.796773E+09 0.717001E+09 0.693690E+09 15412133.73 0.678278E+09 0.00 0.00
September 0.583992E+09 0.856711E+09 0.566667E+09 112698.72 0.566554E+09 0.00 0.00
October 0.530344E+09 0.101972E+10 0.464432E+09 0.00 0.464432E+09 0.00 0.00
November 0.226195E+09 0.149651E+10 0.406944E+09 0.00 0.406944E+09 0.00 0.00
December 0.172162E+09 0.172772E+10 0.360890E+09 0.00 0.360890E+09 0.00 0.00
               
Annual Sum or Average 0.615062E+10 0.142143E+11 0.710227E+10 0.219243E+09 0.688302E+10 0.00 0.00
Minimum of Months 0.172162E+09 0.665106E+09 0.360890E+09 0.00 0.360890E+09 0.00 0.00
Maximum of Months 0.997916E+09 0.172772E+10 0.852379E+09 84206730.00 0.787591E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DINING_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.174883E+09 0.177913E+10 0.387672E+09 0.00 0.387672E+09 0.00 0.00
February 0.181055E+09 0.149660E+10 0.439538E+09 0.00 0.439538E+09 0.00 0.00
March 0.324352E+09 0.166310E+10 0.596384E+09 5460.98 0.596378E+09 0.00 0.00
April 0.487066E+09 0.120127E+10 0.668428E+09 5378694.26 0.663050E+09 0.00 0.00
May 0.646885E+09 0.106872E+10 0.830922E+09 43331554.67 0.787591E+09 0.00 0.00
June 0.857032E+09 0.772225E+09 0.852379E+09 84206730.00 0.768172E+09 0.00 0.00
July 0.966948E+09 0.686198E+09 0.834320E+09 70795746.72 0.763524E+09 0.00 0.00
August 0.768502E+09 0.740858E+09 0.693690E+09 15412133.73 0.678278E+09 0.00 0.00
September 0.558646E+09 0.886221E+09 0.566667E+09 112698.72 0.566554E+09 0.00 0.00
October 0.507066E+09 0.105329E+10 0.464432E+09 0.00 0.464432E+09 0.00 0.00
November 0.205209E+09 0.154424E+10 0.406944E+09 0.00 0.406944E+09 0.00 0.00
December 0.153389E+09 0.178504E+10 0.360890E+09 0.00 0.360890E+09 0.00 0.00
               
Annual Sum or Average 0.583103E+10 0.146769E+11 0.710227E+10 0.219243E+09 0.688302E+10 0.00 0.00
Minimum of Months 0.153389E+09 0.686198E+09 0.360890E+09 0.00 0.360890E+09 0.00 0.00
Maximum of Months 0.966948E+09 0.178504E+10 0.852379E+09 84206730.00 0.787591E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.133923E+10 0.115609E+10 0.979027E+09 0.566733E+09 0.412294E+09 0.00 0.00
February 0.106152E+10 0.101507E+10 0.855325E+09 0.404791E+09 0.450534E+09 0.00 0.00
March 0.131662E+10 0.114109E+10 0.103368E+10 0.432976E+09 0.600702E+09 0.00 0.00
April 0.170779E+10 0.869998E+09 0.116756E+10 0.517154E+09 0.650404E+09 0.00 0.00
May 0.156380E+10 0.827261E+09 0.111634E+10 0.381729E+09 0.734613E+09 0.00 0.00
June 0.163980E+10 0.610923E+09 0.106685E+10 0.378958E+09 0.687892E+09 0.00 0.00
July 0.204266E+10 0.543043E+09 0.121580E+10 0.505857E+09 0.709947E+09 0.00 0.00
August 0.208851E+10 0.564447E+09 0.122019E+10 0.562352E+09 0.657842E+09 0.00 0.00
September 0.160322E+10 0.620024E+09 0.973640E+09 0.418524E+09 0.555116E+09 0.00 0.00
October 0.164247E+10 0.708309E+09 0.974319E+09 0.512030E+09 0.462289E+09 0.00 0.00
November 0.129711E+10 0.101518E+10 0.943108E+09 0.517117E+09 0.425991E+09 0.00 0.00
December 0.134941E+10 0.115543E+10 0.983432E+09 0.599632E+09 0.383800E+09 0.00 0.00
               
Annual Sum or Average 0.186521E+11 0.102269E+11 0.125293E+11 0.579785E+10 0.673142E+10 0.00 0.00
Minimum of Months 0.106152E+10 0.543043E+09 0.855325E+09 0.378958E+09 0.383800E+09 0.00 0.00
Maximum of Months 0.208851E+10 0.115609E+10 0.122019E+10 0.599632E+09 0.734613E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.207844E+10 0.121040E+10 0.150077E+10 0.100422E+10 0.496551E+09 0.00 0.00
February 0.143489E+10 0.101343E+10 0.112662E+10 0.603882E+09 0.522737E+09 0.00 0.00
March 0.133027E+10 0.117741E+10 0.106621E+10 0.419784E+09 0.646422E+09 0.00 0.00
April 0.123130E+10 0.902347E+09 0.926512E+09 0.271380E+09 0.655132E+09 0.00 0.00
May 0.883177E+09 0.824168E+09 0.792583E+09 76342183.92 0.716240E+09 0.00 0.00
June 0.856764E+09 0.593750E+09 0.723261E+09 54148304.57 0.669113E+09 0.00 0.00
July 0.102850E+10 0.536524E+09 0.755764E+09 74501639.64 0.681262E+09 0.00 0.00
August 0.126766E+10 0.578681E+09 0.841134E+09 0.192762E+09 0.648372E+09 0.00 0.00
September 0.151287E+10 0.661840E+09 0.996027E+09 0.398351E+09 0.597676E+09 0.00 0.00
October 0.194177E+10 0.759974E+09 0.124407E+10 0.728566E+09 0.515505E+09 0.00 0.00
November 0.195851E+10 0.105943E+10 0.141477E+10 0.903557E+09 0.511212E+09 0.00 0.00
December 0.221752E+10 0.120418E+10 0.158752E+10 0.111546E+10 0.472062E+09 0.00 0.00
               
Annual Sum or Average 0.177417E+11 0.105221E+11 0.129752E+11 0.584296E+10 0.713228E+10 0.00 0.00
Minimum of Months 0.856764E+09 0.536524E+09 0.723261E+09 54148304.57 0.472062E+09 0.00 0.00
Maximum of Months 0.221752E+10 0.121040E+10 0.158752E+10 0.111546E+10 0.716240E+09 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January 13.22 9.61 5.99 2.23 0.81 45.19 208.20 0.00
February 13.28 10.20 7.03 3.12 2.96 66.07 175.60 0.04
March 12.64 10.61 8.97 2.93 3.55 84.90 179.28 0.03
April 15.30 12.62 10.61 2.62 4.76 81.20 282.81 0.02
May 15.56 12.65 10.56 2.92 6.17 105.80 234.18 0.01
June 17.67 14.80 13.02 2.53 9.03 98.05 261.27 0.00
July 19.43 16.76 15.28 2.35 9.62 86.54 312.15 0.00
August 19.66 17.23 15.95 2.55 9.62 74.58 307.55 0.00
September 18.47 15.50 13.65 2.19 8.99 70.75 240.05 0.00
October 18.77 13.72 9.60 2.71 7.74 53.88 216.36 0.00
November 14.32 10.43 6.22 2.47 2.41 50.75 207.87 0.01
December 13.59 8.82 3.19 2.50 0.05 39.49 221.83 0.00
                 
Annual Sum or Average 16.01 12.76 10.02 2.59 5.49 71.44 237.65 0.01
Minimum of Months 12.64 8.82 3.19 2.19 0.05 39.49 175.60 0.00
Maximum of Months 19.66 17.23 15.95 3.12 9.62 105.80 312.15 0.04



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 26.00 13-JAN-13:00 15.46 8.00 3.10 11.84 120.00 725.00
February 26.00 01-FEB-11:00 14.67 6.00 4.10 10.11 166.00 715.50
March 24.00 11-MAR-10:00 13.82 6.00 2.60 8.15 120.00 907.00
April 27.00 26-APR-12:00 17.13 11.00 4.10 12.22 159.00 884.00
May 24.00 03-MAY-11:00 15.05 9.00 4.10 12.98 187.00 842.50
June 25.00 29-JUN-10:00 19.59 17.00 4.60 11.65 177.50 829.00
July 28.00 19-JUL-10:00 20.49 17.00 3.60 14.65 173.00 813.00
August 28.00 14-AUG-10:00 21.19 18.00 3.60 14.84 148.00 840.00
September 36.00 29-SEP-10:00 17.91 5.00 3.60 19.35 159.50 790.00
October 37.00 16-OCT-10:00 17.87 4.00 5.70 20.05 122.00 871.50
November 27.00 19-NOV-12:00 14.96 6.00 4.10 11.07 128.50 796.00
December 26.00 05-DEC-09:00 13.09 1.00 3.60 8.94 75.50 857.00
                 
Annual Sum or Average                
Minimum of Months 24.00   13.09 1.00 2.60 8.15 75.50 715.50
Maximum of Months 37.00   21.19 18.00 5.70 20.05 187.00 907.00



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 1.00 08-JAN-06:00 -0.3 -2.0 3.10 -15.5 11.50 193.50
February 5.00 04-FEB-05:00 0.22 -8.0 4.10 -10.9 0.00 0.00
March 4.00 07-MAR-04:00 3.53 3.00 0.00 -11.4 0.00 0.00
April 7.00 01-APR-05:00 4.33 1.00 4.10 -9.0 23.50 211.00
May 8.00 14-MAY-03:00 7.45 7.00 1.50 -6.6 0.00 0.00
June 11.00 13-JUN-03:00 9.85 9.00 2.10 -3.4 0.00 0.00
July 13.00 06-JUL-00:00 13.00 13.00 0.00 -0.6 0.00 0.00
August 14.00 24-AUG-01:00 14.00 14.00 0.00 0.51 0.00 0.00
September 11.00 20-SEP-02:00 9.85 9.00 1.50 -3.4 0.00 0.00
October 9.00 12-OCT-04:00 6.56 4.00 3.10 -6.4 0.00 0.00
November 7.00 05-NOV-01:00 5.54 4.00 3.10 -8.3 0.00 0.00
December 5.00 03-DEC-00:00 5.00 5.00 2.10 -0.4 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months 1.00   -0.3 -8.0 0.00 -15.5 0.00 0.00
Maximum of Months 14.00   14.00 14.00 4.10 0.51 23.50 211.00



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 17.04 17-JAN-11:00 24.00 13.00 3.10 12.79 223.50 9.00
February 16.80 11-FEB-13:00 18.00 16.20 1.10 15.02 241.00 12.50
March 17.41 22-MAR-12:00 22.00 15.00 3.10 8.35 145.50 876.00
April 18.33 26-APR-10:00 26.00 14.00 4.10 12.03 141.50 915.50
May 16.69 05-MAY-14:00 18.00 16.00 5.10 8.74 303.50 269.00
June 19.59 29-JUN-10:00 25.00 17.00 4.60 11.65 177.50 829.00
July 21.19 19-JUL-11:00 28.00 18.00 4.60 14.84 182.50 808.00
August 21.20 18-AUG-11:00 28.00 18.00 3.60 17.21 244.00 667.50
September 21.85 22-SEP-11:00 26.00 20.00 2.60 20.05 284.00 21.00
October 21.09 01-OCT-11:00 26.00 19.00 3.60 13.16 102.00 899.50
November 16.52 10-NOV-12:00 21.00 14.00 5.10 7.15 131.00 808.50
December 15.64 07-DEC-12:00 20.00 13.00 5.10 5.94 89.00 868.50
                 
Annual Sum or Average                
Minimum of Months 15.64   18.00 13.00 1.10 5.94 89.00 9.00
Maximum of Months 21.85   28.00 20.00 5.10 20.05 303.50 915.50



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 14.00 17-JAN-12:00 22.00 16.85 2.10 11.65 241.50 67.50
February 16.20 11-FEB-13:00 18.00 16.80 1.10 15.02 241.00 12.50
March 15.00 23-MAR-15:20 21.67 17.34 3.77 8.02 112.00 809.83
April 15.00 26-APR-21:19 16.00 15.39 2.23 6.15 0.00 0.00
May 16.00 05-MAY-14:00 18.00 16.69 5.10 8.74 303.50 269.00
June 17.00 28-JUN-08:00 19.00 17.66 1.50 16.12 285.00 428.50
July 18.00 18-JUL-10:00 26.00 20.47 4.60 12.79 169.00 819.00
August 18.10 14-AUG-09:00 26.90 20.93 3.40 13.73 139.00 817.00
September 20.00 22-SEP-09:00 22.00 20.55 1.50 16.30 296.00 18.00
October 19.00 01-OCT-07:10 19.17 19.06 0.25 16.82 53.33 0.00
November 15.00 10-NOV-17:19 16.67 15.62 2.77 3.34 0.00 0.00
December 13.00 07-DEC-12:00 20.00 15.64 5.10 5.94 89.00 868.50
                 
Annual Sum or Average                
Minimum of Months 13.00   16.00 15.39 0.25 3.34 0.00 0.00
Maximum of Months 20.00   26.90 20.93 5.10 16.82 303.50 868.50



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 17.43 27.46 0.00
February 18.00 13.00 16.00 17.38 30.87 0.00
March 18.00 13.00 16.00 17.83 38.09 0.00
April 18.00 13.00 16.00 18.69 55.75 0.00
May 18.00 13.00 16.00 19.73 55.13 0.00
June 18.00 13.00 16.00 20.65 58.21 0.00
July 18.00 13.00 16.00 21.22 63.49 0.00
August 18.00 13.00 16.00 21.28 59.02 0.00
September 18.00 13.00 16.00 20.81 46.26 0.00
October 18.00 13.00 16.00 19.94 34.64 0.00
November 18.00 13.00 16.00 18.91 29.25 0.00
December 18.00 13.00 16.00 17.99 26.27 0.00
             
Annual Sum or Average 18.00 13.00 16.00 19.33 43.77 0.00
Minimum of Months 18.00 13.00 16.00 17.38 26.27 0.00
Maximum of Months 18.00 13.00 16.00 21.28 63.49 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWH LAUNDRY G WATER HEATER

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.111412E+12 -0.109633E+12 0.00 0.00 744.00 0.00 -0.177888E+10 82.17 0.00 0.00
February 0.100712E+12 -0.990946E+11 0.00 0.00 672.00 0.00 -0.161716E+10 82.17 0.00 0.00
March 0.110744E+12 -0.108944E+12 0.00 0.00 744.00 0.00 -0.179961E+10 82.17 0.00 0.00
April 0.105762E+12 -0.104022E+12 0.00 0.00 720.00 0.00 -0.174063E+10 82.17 0.00 0.00
May 0.107539E+12 -0.105741E+12 0.00 0.00 744.00 0.00 -0.179792E+10 82.17 0.00 0.00
June 0.102553E+12 -0.100811E+12 0.00 0.00 720.00 0.00 -0.174260E+10 82.17 0.00 0.00
July 0.104996E+12 -0.103206E+12 0.00 0.00 744.00 0.00 -0.179049E+10 82.17 0.00 0.00
August 0.104893E+12 -0.103106E+12 0.00 0.00 744.00 0.00 -0.178721E+10 82.17 0.00 0.00
September 0.102270E+12 -0.100550E+12 0.00 0.00 720.00 0.00 -0.172007E+10 82.17 0.00 0.00
October 0.107145E+12 -0.105375E+12 0.00 0.00 744.00 0.00 -0.176934E+10 82.17 0.00 0.00
November 0.105380E+12 -0.103669E+12 0.00 0.00 720.00 0.00 -0.171076E+10 82.17 0.00 0.00
December 0.110455E+12 -0.108679E+12 0.00 0.00 744.00 0.00 -0.177512E+10 82.17 0.00 0.00
                     
Annual Sum or Average 0.127386E+13 -0.125283E+13 0.00 0.00 8760.00 0.00 -0.210298E+11 82.17 0.00 0.00
Minimum of Months 0.100712E+12 -0.109633E+12 0.00 0.00 672.00 0.00 -0.179961E+10 82.17 0.00 0.00
Maximum of Months 0.111412E+12 -0.990946E+11 0.00 0.00 744.00 0.00 -0.161716E+10 82.17 0.00 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWH BOOSTER E WATER HEATER

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.804802E+10 -0.788296E+10 0.00 0.00 744.00 0.00 -165061401.7 82.17 0.00 0.00
February 0.727211E+10 -0.712336E+10 0.00 0.00 672.00 0.00 -148749255.8 82.17 0.00 0.00
March 0.804647E+10 -0.788155E+10 0.00 0.00 744.00 0.00 -164915056.0 82.17 0.00 0.00
April 0.779738E+10 -0.763820E+10 0.00 0.00 720.00 0.00 -159184352.9 82.17 0.00 0.00
May 0.804744E+10 -0.788296E+10 0.00 0.00 744.00 0.00 -164481543.5 82.17 0.00 0.00
June 0.778883E+10 -0.762976E+10 0.00 0.00 720.00 0.00 -159071255.9 82.17 0.00 0.00
July 0.805571E+10 -0.789140E+10 0.00 0.00 744.00 0.00 -164312252.1 82.17 0.00 0.00
August 0.804727E+10 -0.788296E+10 0.00 0.00 744.00 0.00 -164306516.0 82.17 0.00 0.00
September 0.779867E+10 -0.763961E+10 0.00 0.00 720.00 0.00 -159058929.9 82.17 0.00 0.00
October 0.804595E+10 -0.788155E+10 0.00 0.00 744.00 0.00 -164392302.3 82.17 0.00 0.00
November 0.778066E+10 -0.762132E+10 0.00 0.00 720.00 0.00 -159336383.5 82.17 0.00 0.00
December 0.805635E+10 -0.789140E+10 0.00 0.00 744.00 0.00 -164946598.5 82.17 0.00 0.00
                     
Annual Sum or Average 0.947849E+11 -0.928470E+11 0.00 0.00 8760.00 0.00 -0.193782E+10 82.17 0.00 0.00
Minimum of Months 0.727211E+10 -0.789140E+10 0.00 0.00 672.00 0.00 -165061401.7 82.17 0.00 0.00
Maximum of Months 0.805635E+10 -0.712336E+10 0.00 0.00 744.00 0.00 -148749255.8 82.17 0.00 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.637463E+11 -0.622046E+11 0.00 0.00 744.00 0.00 -0.154166E+10 60.05 0.00 0.00
February 0.576644E+11 -0.562575E+11 0.00 0.00 672.00 0.00 -0.140693E+10 60.05 0.00 0.00
March 0.632352E+11 -0.616648E+11 0.00 0.00 744.00 0.00 -0.157039E+10 60.05 0.00 0.00
April 0.599449E+11 -0.584264E+11 0.00 0.00 720.00 0.00 -0.151845E+10 60.05 0.00 0.00
May 0.604411E+11 -0.588730E+11 0.00 0.00 744.00 0.00 -0.156805E+10 60.05 0.00 0.00
June 0.572052E+11 -0.556840E+11 0.00 0.00 720.00 0.00 -0.152118E+10 60.05 0.00 0.00
July 0.582097E+11 -0.566520E+11 0.00 0.00 744.00 0.00 -0.155776E+10 60.05 0.00 0.00
August 0.581771E+11 -0.566239E+11 0.00 0.00 744.00 0.00 -0.155321E+10 60.05 0.00 0.00
September 0.569226E+11 -0.554326E+11 0.00 0.00 720.00 0.00 -0.148996E+10 60.05 0.00 0.00
October 0.600528E+11 -0.585243E+11 0.00 0.00 744.00 0.00 -0.152844E+10 60.05 0.00 0.00
November 0.595757E+11 -0.580986E+11 0.00 0.00 720.00 0.00 -0.147705E+10 60.05 0.00 0.00
December 0.629138E+11 -0.613773E+11 0.00 0.00 744.00 0.00 -0.153645E+10 60.05 0.00 0.00
                     
Annual Sum or Average 0.718089E+12 -0.699819E+12 0.00 0.00 8760.00 0.00 -0.182695E+11 60.05 0.00 0.00
Minimum of Months 0.569226E+11 -0.622046E+11 0.00 0.00 672.00 0.00 -0.157039E+10 60.05 0.00 0.00
Maximum of Months 0.637463E+11 -0.554326E+11 0.00 0.00 744.00 0.00 -0.140693E+10 60.05 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: LOBBY_FLR_1_DAYLCTRL

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 293.33 0.87 0.86 01-JAN-07:30 7052.51 37.52 285.00 281.50 1015.00 27.16 209.67 265.00
February 279.67 0.87 0.86 01-FEB-07:30 4904.28 32.25 218.50 277.00 670.04 23.86 187.83 247.67
March 338.17 0.87 0.86 01-MAR-07:40 1285.36 20.03 18.83 322.67 479.18 21.29 186.67 268.33
April 358.33 0.87 0.86 01-APR-07:19 884.18 19.54 0.00 335.17 373.14 21.29 213.17 274.67
May 393.83 0.88 0.86 01-MAY-06:00 803.15 19.04 0.00 367.83 327.24 20.77 162.33 280.33
June 381.00 0.88 0.86 01-JUN-07:10 694.69 18.85 0.00 360.33 292.55 20.60 125.00 260.50
July 408.67 0.88 0.86 01-JUL-07:00 684.44 18.97 0.00 369.83 298.69 20.73 173.83 280.00
August 390.67 0.88 0.86 01-AUG-07:40 744.35 19.22 0.00 356.00 324.31 20.97 187.33 283.00
September 328.83 0.87 0.86 01-SEP-07:10 999.70 19.53 0.33 311.00 416.32 21.30 182.17 261.17
October 296.17 0.87 0.86 01-OCT-09:39 3383.21 27.32 136.83 307.33 492.85 21.81 127.33 256.83
November 300.00 0.87 0.86 01-NOV-06:49 6865.72 37.35 295.17 281.67 889.85 26.74 225.17 269.50
December 297.00 0.87 0.86 01-DEC-07:19 6902.00 37.93 289.17 282.17 1244.45 28.71 200.50 267.83
                         
Annual Sum or Average 4065.67 0.87     2652.36 24.77 1243.83 3852.50 538.51 22.67 2181.00 3214.83
Minimum of Months 279.67 0.87 0.86   684.44 18.85 0.00 277.00 292.55 20.60 125.00 247.67
Maximum of Months 408.67 0.88 0.86   7052.51 37.93 295.17 369.83 1244.45 28.71 225.17 283.00



Table of Contents

Report: DaylightingReportMonthly

For: CAFE_FLR_1_DAYLCTRL

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 293.33 0.25 0.22 01-JAN-07:19 7460.67 37.60 285.00 288.33 1425.15 26.86 184.67 276.00
February 279.67 0.25 0.22 01-FEB-07:19 5228.42 32.34 219.00 283.17 993.76 23.90 182.17 266.00
March 338.17 0.28 0.22 01-MAR-07:10 1535.43 20.47 44.50 331.67 728.33 21.58 206.00 303.83
April 358.33 0.26 0.22 01-APR-06:40 1086.01 20.10 41.67 348.00 574.49 21.65 229.33 317.83
May 393.83 0.27 0.22 01-MAY-06:30 945.90 19.84 7.17 381.33 469.50 21.36 251.33 346.17
June 381.00 0.28 0.22 01-JUN-06:40 823.20 19.70 0.17 372.50 420.64 21.22 248.50 336.50
July 408.67 0.28 0.22 01-JUL-06:10 820.23 19.76 0.67 380.33 434.09 21.30 305.33 350.50
August 390.67 0.28 0.22 01-AUG-07:10 913.02 19.87 14.50 368.50 492.57 21.42 254.50 339.67
September 328.83 0.27 0.22 01-SEP-06:49 1240.89 19.96 38.67 324.17 656.95 21.56 193.33 295.50
October 296.17 0.26 0.22 01-OCT-09:39 3714.16 27.35 138.50 318.17 821.62 21.74 123.67 286.50
November 300.00 0.26 0.22 01-NOV-06:40 7249.89 37.41 295.17 286.17 1271.19 26.49 203.33 277.67
December 297.00 0.26 0.22 01-DEC-07:10 7326.86 38.01 289.33 287.83 1668.60 28.35 178.67 277.67
                         
Annual Sum or Average 4065.67 0.27     2901.42 25.22 1374.33 3970.17 786.93 22.90 2560.83 3673.83
Minimum of Months 279.67 0.25 0.22   820.23 19.70 0.17 283.17 420.64 21.22 123.67 266.00
Maximum of Months 408.67 0.28 0.22   7460.67 38.01 295.17 381.33 1668.60 28.35 305.33 350.50



Table of Contents

Report: DaylightingReportMonthly

For: DINING_FLR_6_DAYLCTRL

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 293.33 0.70 0.60 01-JAN-09:20 331.49 14.72 0.00 246.50 171.60 18.27 0.00 65.83
February 279.67 0.67 0.60 01-FEB-10:30 414.60 15.58 0.00 259.17 198.91 18.90 0.00 130.50
March 338.17 0.65 0.60 01-MAR-10:30 496.51 16.13 0.00 317.67 228.10 19.33 0.00 229.67
April 358.33 0.63 0.60 01-APR-07:00 523.15 17.06 0.00 346.17 256.09 20.31 33.67 297.67
May 393.83 0.62 0.60 01-MAY-06:40 703.49 18.00 12.50 389.50 316.66 21.20 95.33 355.00
June 381.00 0.62 0.60 01-JUN-06:40 745.03 20.01 58.83 383.67 344.66 22.41 133.83 348.17
July 408.67 0.62 0.60 01-JUL-05:49 677.39 19.27 44.83 391.83 298.57 20.88 117.33 362.17
August 390.67 0.63 0.60 01-AUG-07:19 536.69 17.14 0.00 372.67 257.97 20.42 59.50 331.17
September 328.83 0.64 0.60 01-SEP-06:00 460.90 16.42 0.00 314.83 228.79 19.69 1.67 235.33
October 296.17 0.69 0.60 01-OCT-09:39 343.47 15.07 0.00 273.00 174.39 18.51 0.00 96.83
November 300.00 0.70 0.60 01-NOV-08:30 340.01 14.51 0.00 252.50 173.32 17.96 0.00 81.00
December 297.00 0.71 0.60 01-DEC-09:30 298.98 14.19 0.00 239.67 159.19 17.81 0.00 46.17
                         
Annual Sum or Average 4065.67 0.65     506.69 16.71 116.17 3787.17 241.01 19.80 441.33 2579.50
Minimum of Months 279.67 0.62 0.60   298.98 14.19 0.00 239.67 159.19 17.81 0.00 46.17
Maximum of Months 408.67 0.71 0.60   745.03 20.01 58.83 391.83 344.66 22.41 133.83 362.17



Table of Contents

Report: DaylightingReportMonthly

For: BANQUET_FLR_6_DAYLCTRL

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 293.33 0.70 0.60 01-JAN-09:20 331.49 14.72 0.00 246.50 171.60 18.27 0.00 65.83
February 279.67 0.67 0.60 01-FEB-10:30 414.60 15.58 0.00 259.17 198.91 18.90 0.00 130.50
March 338.17 0.65 0.60 01-MAR-10:30 496.51 16.13 0.00 317.67 228.10 19.33 0.00 229.67
April 358.33 0.63 0.60 01-APR-07:00 523.15 17.06 0.00 346.17 256.09 20.31 33.67 297.67
May 393.83 0.62 0.60 01-MAY-06:40 703.49 18.00 12.50 389.50 316.66 21.20 95.33 355.00
June 381.00 0.62 0.60 01-JUN-06:40 745.03 20.01 58.83 383.67 344.66 22.41 133.83 348.17
July 408.67 0.62 0.60 01-JUL-05:49 677.39 19.27 44.83 391.83 298.57 20.88 117.33 362.17
August 390.67 0.63 0.60 01-AUG-07:19 536.69 17.14 0.00 372.67 257.97 20.42 59.67 331.17
September 328.83 0.64 0.60 01-SEP-06:00 460.90 16.42 0.00 314.83 228.79 19.69 1.67 235.33
October 296.17 0.69 0.60 01-OCT-09:39 343.47 15.07 0.00 273.00 174.39 18.51 0.00 96.83
November 300.00 0.70 0.60 01-NOV-08:30 340.01 14.51 0.00 252.50 173.32 17.96 0.00 81.00
December 297.00 0.71 0.60 01-DEC-09:30 298.98 14.19 0.00 239.67 159.19 17.81 0.00 46.17
                         
Annual Sum or Average 4065.67 0.65     506.69 16.71 116.17 3787.17 241.01 19.80 441.50 2579.50
Minimum of Months 279.67 0.62 0.60   298.98 14.19 0.00 239.67 159.19 17.81 0.00 46.17
Maximum of Months 408.67 0.71 0.60   745.03 20.01 58.83 391.83 344.66 22.41 133.83 362.17



Table of Contents

Report: CoilReportMonthly

For: FLR_3_DOAS HEATING COIL

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.796627E+10 8943.46 08-JAN-07:00 0.00 0.00 0.00 0.00 0.00
February 0.641498E+10 8391.78 05-FEB-06:00 0.00 0.00 0.00 0.00 0.00
March 0.857742E+10 8532.16 07-MAR-05:00 0.00 0.00 0.00 0.00 0.00
April 0.405566E+10 8113.59 01-APR-06:00 0.00 0.00 0.00 0.00 0.00
May 0.360689E+10 7975.38 19-MAY-05:00 0.00 0.00 0.00 0.00 0.00
June 0.639403E+09 5275.70 13-JUN-04:00 0.00 0.00 0.00 0.00 0.00
July 37027035.96 2369.00 06-JUL-01:00 0.00 0.00 0.00 0.00 0.00
August 17469671.82 904.60 24-AUG-02:00 0.00 0.00 0.00 0.00 0.00
September 0.319034E+09 5276.32 20-SEP-03:00 0.00 0.00 0.00 0.00 0.00
October 0.143387E+10 7833.53 28-OCT-04:00 0.00 0.00 0.00 0.00 0.00
November 0.564075E+10 8114.43 05-NOV-02:00 0.00 0.00 0.00 0.00 0.00
December 0.800628E+10 8394.05 03-DEC-01:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.467151E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 17469671.82 904.60   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.857742E+10 8943.46   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV WITH REHEAT HEATING COIL

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.876339E+11 90052.39 08-JAN-07:00 0.00 0.00 0.00 0.00 0.00
February 0.697356E+11 85883.31 03-FEB-22:00 0.00 0.00 0.00 0.00 0.00
March 0.944809E+11 85927.47 07-MAR-05:00 0.00 0.00 0.00 0.00 0.00
April 0.427837E+11 83270.33 15-APR-22:00 0.00 0.00 0.00 0.00 0.00
May 0.373482E+11 81128.49 19-MAY-05:17 0.00 0.00 0.00 0.00 0.00
June 0.689025E+10 57136.42 13-JUN-05:00 0.00 0.00 0.00 0.00 0.00
July 0.411132E+09 25218.19 06-JUL-03:00 0.00 0.00 0.00 0.00 0.00
August 0.172226E+09 9689.23 31-AUG-04:00 0.00 0.00 0.00 0.00 0.00
September 0.305474E+10 55155.88 20-SEP-03:00 0.00 0.00 0.00 0.00 0.00
October 0.153624E+11 81015.52 29-OCT-06:10 0.00 0.00 0.00 0.00 0.00
November 0.592536E+11 85603.52 29-NOV-22:20 0.00 0.00 0.00 0.00 0.00
December 0.870412E+11 85991.60 19-DEC-21:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.504168E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.172226E+09 9689.23   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.944809E+11 90052.39   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: BASEMENT VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.332628E+09 1925.02 08-JAN-07:00 0.00 0.00 0.00 0.00 0.00
February 0.256413E+09 1129.11 05-FEB-06:00 0.00 0.00 0.00 0.00 0.00
March 0.514578E+09 1836.34 30-MAR-03:00 0.00 0.00 0.00 0.00 0.00
April 83252708.09 1213.96 01-APR-06:00 0.00 0.00 0.00 0.00 0.00
May 0.106887E+09 893.07 14-MAY-04:40 0.00 0.00 0.00 0.00 0.00
June 11106353.56 249.91 08-JUN-10:50 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 106830.47 242.12 18-SEP-10:40 0.00 0.00 0.00 0.00 0.00
October 6256419.62 291.09 25-OCT-06:10 0.00 0.00 0.00 0.00 0.00
November 51364596.35 766.63 05-NOV-05:00 0.00 0.00 0.00 0.00 0.00
December 0.205293E+09 1357.22 13-DEC-06:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.156789E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.514578E+09 1925.02   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 2968718.60 403.09 08-JAN-07:00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 4693067.47 298.62 29-MAR-11:00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 7661786.07     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 4693067.47 403.09   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: MECH_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 38238505.42 717.78 09-JAN-05:55 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 41517258.91 724.64 30-MAR-03:10 0.00 0.00 0.00 0.00 0.00
April 706517.37 236.18 01-APR-10:40 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 80462281.70     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 41517258.91 724.64   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: STORAGE_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 56035842.14 634.33 08-JAN-07:00 0.00 0.00 0.00 0.00 0.00
February 254521.67 64.41 28-FEB-11:50 0.00 0.00 0.00 0.00 0.00
March 59004038.53 548.89 30-MAR-03:00 0.00 0.00 0.00 0.00 0.00
April 2187562.75 199.31 01-APR-06:00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 5168509.81 161.73 24-DEC-04:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.122650E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 59004038.53 634.33   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.117002E+10 7951.53 08-JAN-07:00 0.00 0.00 0.00 0.00 0.00
February 0.304044E+09 7457.30 04-FEB-05:55 0.00 0.00 0.00 0.00 0.00
March 0.908492E+09 7587.25 07-MAR-05:00 0.00 0.00 0.00 0.00 0.00
April 91978727.01 3762.06 01-APR-05:00 0.00 0.00 0.00 0.00 0.00
May 90052412.34 2742.38 27-MAY-03:00 0.00 0.00 0.00 0.00 0.00
June 30594977.86 760.88 12-JUN-04:00 0.00 0.00 0.00 0.00 0.00
July 14665353.11 426.91 10-JUL-04:00 0.00 0.00 0.00 0.00 0.00
August 10543687.64 368.89 28-AUG-04:00 0.00 0.00 0.00 0.00 0.00
September 25182253.84 596.76 19-SEP-04:00 0.00 0.00 0.00 0.00 0.00
October 30754415.34 1330.44 28-OCT-05:00 0.00 0.00 0.00 0.00 0.00
November 0.227589E+09 4979.53 08-NOV-05:00 0.00 0.00 0.00 0.00 0.00
December 0.731222E+09 7462.77 23-DEC-04:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.363514E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 10543687.64 368.89   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.117002E+10 7951.53   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CAFE_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 78573337.99 4212.33 08-JAN-06:50 0.00 0.00 0.00 0.00 0.00
February 43059475.14 1646.03 28-FEB-11:37 0.00 0.00 0.00 0.00 0.00
March 0.145118E+09 4035.65 29-MAR-11:00 0.00 0.00 0.00 0.00 0.00
April 272494.63 571.82 22-APR-10:50 0.00 0.00 0.00 0.00 0.00
May 3263241.67 1443.00 09-MAY-10:37 0.00 0.00 0.00 0.00 0.00
June 264433.19 529.03 08-JUN-10:50 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 374094.61 785.80 18-SEP-10:40 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 549999.19 1307.59 13-DEC-07:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.271475E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.145118E+09 4212.33   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: LOBBY_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 11832122.83 4669.87 08-JAN-07:00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 18366855.67 4941.61 29-MAR-11:00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 30198978.49     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 18366855.67 4941.61   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.271411E+09 6124.03 03-JAN-07:10 0.00 0.00 0.00 0.00 0.00
February 4167777.25 1616.62 28-FEB-11:33 0.00 0.00 0.00 0.00 0.00
March 0.334887E+09 5250.44 30-MAR-06:07 0.00 0.00 0.00 0.00 0.00
April 10065173.73 2300.44 01-APR-06:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 163292.22 433.22 15-DEC-07:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.620695E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.334887E+09 6124.03   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.529134E+09 4618.28 08-JAN-07:00 0.00 0.00 0.00 0.00 0.00
February 64628781.39 1414.50 05-FEB-06:00 0.00 0.00 0.00 0.00 0.00
March 0.455145E+09 3614.76 30-MAR-03:00 0.00 0.00 0.00 0.00 0.00
April 18177942.24 1666.09 01-APR-06:00 0.00 0.00 0.00 0.00 0.00
May 1736212.89 479.86 14-MAY-04:50 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 8364322.69 807.85 05-NOV-05:00 0.00 0.00 0.00 0.00 0.00
December 0.207896E+09 2315.54 13-DEC-06:07 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.128508E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.529134E+09 4618.28   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: BANQUET_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: DINING_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: KITCHEN_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.139376E+09 4970.20 09-JAN-06:00 0.00 0.00 0.00 0.00 0.00
February 267470.62 293.68 05-FEB-06:00 0.00 0.00 0.00 0.00 0.00
March 98148498.19 4321.90 30-MAR-03:00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 19288841.59 2519.96 24-DEC-04:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.257081E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.139376E+09 4970.20   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_3 FAN COIL HEATING COIL

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.403588E+09 3762.08 29-JAN-16:04 0.00 0.00 0.00 0.00 0.00
February 0.260197E+09 3763.24 16-FEB-19:04 0.00 0.00 0.00 0.00 0.00
March 0.450385E+09 3842.99 29-MAR-08:62 0.00 0.00 0.00 0.00 0.00
April 62793628.56 3760.22 19-APR-08:03 0.00 0.00 0.00 0.00 0.00
May 46330906.75 3765.73 12-MAY-15:04 0.00 0.00 0.00 0.00 0.00
June 8775161.79 3757.83 24-JUN-08:04 0.00 0.00 0.00 0.00 0.00
July 6988001.47 3755.40 04-JUL-08:04 0.00 0.00 0.00 0.00 0.00
August 6530290.29 3236.58 03-AUG-08:04 0.00 0.00 0.00 0.00 0.00
September 10112038.45 3758.63 21-SEP-18:04 0.00 0.00 0.00 0.00 0.00
October 16478989.40 3759.68 23-OCT-15:04 0.00 0.00 0.00 0.00 0.00
November 0.108715E+09 3759.49 09-NOV-16:04 0.00 0.00 0.00 0.00 0.00
December 0.287276E+09 3763.06 08-DEC-16:04 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.166817E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 6530290.29 3236.58   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.450385E+09 3842.99   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_3 FAN COIL HEATING COIL

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.792308E+09 3827.50 03-JAN-09:01 0.00 0.00 0.00 0.00 0.00
February 0.414265E+09 3804.93 25-FEB-16:03 0.00 0.00 0.00 0.00 0.00
March 0.585084E+09 3842.51 30-MAR-08:62 0.00 0.00 0.00 0.00 0.00
April 71099421.82 3745.39 02-APR-08:52 0.00 0.00 0.00 0.00 0.00
May 38434517.05 3745.12 28-MAY-08:53 0.00 0.00 0.00 0.00 0.00
June 5468887.77 3745.08 02-JUN-08:53 0.00 0.00 0.00 0.00 0.00
July 2089366.46 2632.29 10-JUL-08:54 0.00 0.00 0.00 0.00 0.00
August 1389645.57 1940.07 22-AUG-21:55 0.00 0.00 0.00 0.00 0.00
September 7102440.71 3745.32 03-SEP-08:53 0.00 0.00 0.00 0.00 0.00
October 16823142.57 3744.68 27-OCT-08:52 0.00 0.00 0.00 0.00 0.00
November 0.251666E+09 3744.44 04-NOV-18:04 0.00 0.00 0.00 0.00 0.00
December 0.617337E+09 3825.12 13-DEC-09:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.280307E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 1389645.57 1940.07   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.792308E+09 3842.51   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.166232E+10 22023.04 26-JAN-16:04 0.00 0.00 0.00 0.00 0.00
February 0.354240E+09 22026.94 22-FEB-16:04 0.00 0.00 0.00 0.00 0.00
March 0.943655E+09 22027.33 01-MAR-16:04 0.00 0.00 0.00 0.00 0.00
April 0.108097E+09 22020.34 03-APR-08:53 0.00 0.00 0.00 0.00 0.00
May 64395207.48 22016.61 09-MAY-15:06 0.00 0.00 0.00 0.00 0.00
June 24283152.53 21973.13 06-JUN-15:06 0.00 0.00 0.00 0.00 0.00
July 12450733.23 16944.56 17-JUL-15:07 0.00 0.00 0.00 0.00 0.00
August 13589214.53 19389.06 22-AUG-08:54 0.00 0.00 0.00 0.00 0.00
September 44081214.98 22019.00 20-SEP-08:53 0.00 0.00 0.00 0.00 0.00
October 69231492.28 22016.37 13-OCT-08:53 0.00 0.00 0.00 0.00 0.00
November 0.271159E+09 22029.99 14-NOV-16:04 0.00 0.00 0.00 0.00 0.00
December 0.100157E+10 22022.39 15-DEC-16:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.456907E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 12450733.23 16944.56   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.166232E+10 22029.99   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_5_FLR_3 FAN COIL HEATING COIL

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.400723E+09 3697.07 18-JAN-19:04 0.00 0.00 0.00 0.00 0.00
February 0.309642E+09 3700.09 23-FEB-16:04 0.00 0.00 0.00 0.00 0.00
March 0.494672E+09 3745.06 28-MAR-08:62 0.00 0.00 0.00 0.00 0.00
April 73065065.45 3700.65 22-APR-15:04 0.00 0.00 0.00 0.00 0.00
May 67284504.29 3700.96 12-MAY-15:04 0.00 0.00 0.00 0.00 0.00
June 10148980.32 3598.23 08-JUN-15:04 0.00 0.00 0.00 0.00 0.00
July 1315665.72 3423.00 09-JUL-18:04 0.00 0.00 0.00 0.00 0.00
August 1310712.36 3021.69 08-AUG-08:05 0.00 0.00 0.00 0.00 0.00
September 8188071.61 3429.56 23-SEP-18:04 0.00 0.00 0.00 0.00 0.00
October 17240045.74 3695.39 25-OCT-18:04 0.00 0.00 0.00 0.00 0.00
November 0.139458E+09 3697.80 02-NOV-15:04 0.00 0.00 0.00 0.00 0.00
December 0.316793E+09 3701.36 13-DEC-16:04 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.183984E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 1310712.36 3021.69   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.494672E+09 3745.06   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_6_FLR_3 FAN COIL HEATING COIL

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.759192E+09 3726.46 02-JAN-19:02 0.00 0.00 0.00 0.00 0.00
February 0.492474E+09 3737.89 25-FEB-16:03 0.00 0.00 0.00 0.00 0.00
March 0.643972E+09 3754.08 29-MAR-18:03 0.00 0.00 0.00 0.00 0.00
April 88205913.90 3678.00 15-APR-15:04 0.00 0.00 0.00 0.00 0.00
May 57747716.65 3679.46 12-MAY-15:04 0.00 0.00 0.00 0.00 0.00
June 5258685.87 3352.89 11-JUN-15:05 0.00 0.00 0.00 0.00 0.00
July 1335794.67 2069.04 27-JUL-06:15 0.00 0.00 0.00 0.00 0.00
August 926384.18 2181.67 21-AUG-20:14 0.00 0.00 0.00 0.00 0.00
September 5951711.75 2774.94 27-SEP-21:54 0.00 0.00 0.00 0.00 0.00
October 23752432.18 3677.40 24-OCT-15:04 0.00 0.00 0.00 0.00 0.00
November 0.310932E+09 3681.15 04-NOV-15:04 0.00 0.00 0.00 0.00 0.00
December 0.643170E+09 3741.55 12-DEC-16:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.303292E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 926384.18 2069.04   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.759192E+09 3754.08   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_6 FAN COIL HEATING COIL

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.216012E+09 1139.12 16-JAN-16:04 0.00 0.00 0.00 0.00 0.00
February 0.166374E+09 1172.62 25-FEB-16:03 0.00 0.00 0.00 0.00 0.00
March 0.226449E+09 1179.79 29-MAR-08:62 0.00 0.00 0.00 0.00 0.00
April 44529303.98 1087.23 17-APR-15:04 0.00 0.00 0.00 0.00 0.00
May 39613829.90 1140.37 08-MAY-15:04 0.00 0.00 0.00 0.00 0.00
June 6060574.29 1139.03 08-JUN-15:04 0.00 0.00 0.00 0.00 0.00
July 1573008.66 999.22 04-JUL-08:04 0.00 0.00 0.00 0.00 0.00
August 1502505.53 857.98 22-AUG-18:04 0.00 0.00 0.00 0.00 0.00
September 3431970.52 1013.43 22-SEP-18:04 0.00 0.00 0.00 0.00 0.00
October 20870046.93 1139.53 23-OCT-15:04 0.00 0.00 0.00 0.00 0.00
November 98520027.45 1010.52 09-NOV-16:04 0.00 0.00 0.00 0.00 0.00
December 0.184605E+09 1063.39 27-DEC-09:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.100954E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 1502505.53 857.98   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.226449E+09 1179.79   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_6 FAN COIL HEATING COIL

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.382846E+09 1175.03 03-JAN-09:01 0.00 0.00 0.00 0.00 0.00
February 0.241353E+09 1169.81 25-FEB-16:03 0.00 0.00 0.00 0.00 0.00
March 0.282888E+09 1177.22 30-MAR-08:62 0.00 0.00 0.00 0.00 0.00
April 47547650.23 1121.35 14-APR-15:04 0.00 0.00 0.00 0.00 0.00
May 29085379.70 1132.40 24-MAY-08:53 0.00 0.00 0.00 0.00 0.00
June 2850358.57 1025.67 08-JUN-15:04 0.00 0.00 0.00 0.00 0.00
July 297639.40 642.29 06-JUL-08:54 0.00 0.00 0.00 0.00 0.00
August 435667.28 614.72 22-AUG-08:53 0.00 0.00 0.00 0.00 0.00
September 2596142.73 978.24 12-SEP-08:53 0.00 0.00 0.00 0.00 0.00
October 25199955.61 1131.89 23-OCT-15:04 0.00 0.00 0.00 0.00 0.00
November 0.182382E+09 1111.47 17-NOV-16:04 0.00 0.00 0.00 0.00 0.00
December 0.337000E+09 1173.86 13-DEC-09:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.153448E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 297639.40 614.72   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.382846E+09 1177.22   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.217440E+09 3835.17 25-JAN-16:05 0.00 0.00 0.00 0.00 0.00
February 0.197682E+09 4442.33 25-FEB-09:04 0.00 0.00 0.00 0.00 0.00
March 0.502887E+09 5484.79 16-MAR-15:05 0.00 0.00 0.00 0.00 0.00
April 91510462.41 5493.34 17-APR-15:04 0.00 0.00 0.00 0.00 0.00
May 0.135894E+09 5501.15 12-MAY-15:04 0.00 0.00 0.00 0.00 0.00
June 26099486.93 5493.63 22-JUN-18:04 0.00 0.00 0.00 0.00 0.00
July 10568714.50 5486.34 04-JUL-18:04 0.00 0.00 0.00 0.00 0.00
August 5680952.44 4475.46 22-AUG-18:04 0.00 0.00 0.00 0.00 0.00
September 11845472.42 5043.87 22-SEP-18:04 0.00 0.00 0.00 0.00 0.00
October 18035621.22 5314.23 23-OCT-15:04 0.00 0.00 0.00 0.00 0.00
November 44952791.81 5490.90 24-NOV-16:04 0.00 0.00 0.00 0.00 0.00
December 0.138287E+09 5488.49 06-DEC-09:04 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.140088E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 5680952.44 3835.17   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.502887E+09 5501.15   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLR_3_DOAS COOLING COIL

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.352394E+10 0.349904E+10 20570.98 13-JAN-14:00 20570.98 0.16
February 0.00 0.00 0.189616E+10 0.184036E+10 17583.23 01-FEB-09:53 17583.23 0.14
March 0.00 0.00 0.213914E+10 0.197595E+10 22012.17 22-MAR-13:00 14832.69 0.12
April 0.00 0.00 0.536108E+10 0.504766E+10 22090.96 26-APR-13:00 22090.96 0.27
May 0.00 0.00 0.568444E+10 0.557746E+10 18829.64 04-MAY-13:00 16265.15 0.35
June 0.00 0.00 0.127679E+11 0.101514E+11 30817.80 29-JUN-12:15 17826.82 0.64
July 0.00 0.00 0.285718E+11 0.167816E+11 40153.36 31-JUL-12:50 23766.73 0.78
August 0.00 0.00 0.326065E+11 0.176854E+11 38729.91 14-AUG-10:00 22142.75 0.78
September 0.00 0.00 0.185738E+11 0.130116E+11 39619.58 22-SEP-12:15 19372.88 0.69
October 0.00 0.00 0.206208E+11 0.151880E+11 38860.24 01-OCT-12:10 20585.66 0.46
November 0.00 0.00 0.354751E+10 0.347968E+10 21516.80 19-NOV-13:05 21516.80 0.19
December 0.00 0.00 0.428641E+10 0.428428E+10 20480.92 05-DEC-09:55 20480.92 0.06
                 
Annual Sum or Average 0.00 0.00 0.139579E+12 0.985224E+11       0.39
Minimum of Months 0.00 0.00 0.189616E+10 0.184036E+10 17583.23   14832.69 0.06
Maximum of Months 0.00 0.00 0.326065E+11 0.176854E+11 40153.36   23766.73 0.78



Table of Contents

Report: CoilReportMonthly

For: VAV WITH REHEAT COOLING COIL

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.580356E+11 0.578582E+11 209507.34 14-JAN-11:45 209507.34 0.26
February 0.00 0.00 0.325376E+11 0.317867E+11 197645.24 01-FEB-11:45 197645.24 0.24
March 0.00 0.00 0.360422E+11 0.353849E+11 182548.43 23-MAR-10:45 147380.26 0.24
April 0.00 0.00 0.856442E+11 0.841340E+11 248801.82 26-APR-10:45 205354.12 0.47
May 0.00 0.00 0.916843E+11 0.907220E+11 160265.73 18-MAY-10:45 143422.59 0.56
June 0.00 0.00 0.168981E+12 0.147634E+12 311545.41 29-JUN-10:45 192253.53 0.85
July 0.00 0.00 0.344845E+12 0.225519E+12 379846.46 31-JUL-10:45 224861.20 0.99
August 0.00 0.00 0.388248E+12 0.235368E+12 407055.93 14-AUG-10:45 241645.37 0.99
September 0.00 0.00 0.229551E+12 0.177330E+12 373451.97 22-SEP-12:00 185697.53 0.90
October 0.00 0.00 0.260147E+12 0.209800E+12 383393.45 16-OCT-10:45 383393.45 0.61
November 0.00 0.00 0.605792E+11 0.598840E+11 214444.18 19-NOV-11:45 214444.18 0.32
December 0.00 0.00 0.668534E+11 0.668534E+11 193632.86 19-DEC-11:45 193632.86 0.12
                 
Annual Sum or Average 0.00 0.00 0.182315E+13 0.142227E+13       0.55
Minimum of Months 0.00 0.00 0.325376E+11 0.317867E+11 160265.73   143422.59 0.12
Maximum of Months 0.00 0.00 0.388248E+12 0.235368E+12 407055.93   383393.45 0.99



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_3 FAN COIL COOLING COIL

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.217582E+10 0.109536E+10 14065.88 21-JAN-09:02 11622.72 0.48
February 0.00 0.00 0.194204E+10 0.103107E+10 14877.07 13-FEB-16:02 10432.39 0.46
March 0.00 0.00 0.211089E+10 0.957685E+09 14078.98 17-MAR-15:01 11444.70 0.51
April 0.00 0.00 0.416899E+10 0.200237E+10 13979.96 08-APR-08:61 11443.67 0.78
May 0.00 0.00 0.391154E+10 0.178067E+10 14181.44 06-MAY-08:62 10700.47 0.77
June 0.00 0.00 0.547476E+10 0.251281E+10 14344.78 16-JUN-15:01 11415.87 0.86
July 0.00 0.00 0.761582E+10 0.370226E+10 14677.75 30-JUL-08:61 11155.09 0.92
August 0.00 0.00 0.786608E+10 0.386137E+10 14919.63 18-AUG-08:61 10949.75 0.93
September 0.00 0.00 0.624545E+10 0.296698E+10 14690.72 23-SEP-08:62 10361.66 0.90
October 0.00 0.00 0.568310E+10 0.330525E+10 14855.68 01-OCT-08:61 11014.84 0.75
November 0.00 0.00 0.292420E+10 0.151173E+10 14694.74 12-NOV-09:02 9717.97 0.58
December 0.00 0.00 0.243721E+10 0.164179E+10 14045.90 25-DEC-16:01 14045.90 0.36
                 
Annual Sum or Average 0.00 0.00 0.525559E+11 0.263693E+11       0.69
Minimum of Months 0.00 0.00 0.194204E+10 0.957685E+09 13979.96   9717.97 0.36
Maximum of Months 0.00 0.00 0.786608E+10 0.386137E+10 14919.63   14045.90 0.93



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_3 FAN COIL COOLING COIL

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.521995E+09 0.228927E+09 13786.68 20-JAN-19:01 10126.30 0.22
February 0.00 0.00 0.698535E+09 0.299410E+09 14158.78 13-FEB-16:02 9779.89 0.27
March 0.00 0.00 0.982138E+09 0.364959E+09 13823.06 22-MAR-18:51 10915.33 0.34
April 0.00 0.00 0.245637E+10 0.950917E+09 14728.05 26-APR-21:51 11020.69 0.59
May 0.00 0.00 0.271019E+10 0.108959E+10 14282.87 03-MAY-21:51 11403.74 0.60
June 0.00 0.00 0.354110E+10 0.155581E+10 15246.55 28-JUN-21:51 11180.75 0.56
July 0.00 0.00 0.496058E+10 0.247115E+10 15402.26 27-JUL-21:51 11095.00 0.56
August 0.00 0.00 0.468699E+10 0.224037E+10 15277.88 16-AUG-21:51 11015.99 0.56
September 0.00 0.00 0.344084E+10 0.144153E+10 14835.65 30-SEP-21:51 10947.98 0.56
October 0.00 0.00 0.270654E+10 0.143225E+10 15243.46 01-OCT-08:51 9959.38 0.45
November 0.00 0.00 0.942833E+09 0.380427E+09 14148.95 12-NOV-09:02 9257.71 0.35
December 0.00 0.00 0.548646E+09 0.337562E+09 13652.50 09-DEC-16:01 11103.18 0.17
                 
Annual Sum or Average 0.00 0.00 0.281968E+11 0.127929E+11       0.44
Minimum of Months 0.00 0.00 0.521995E+09 0.228927E+09 13652.50   9257.71 0.17
Maximum of Months 0.00 0.00 0.496058E+10 0.247115E+10 15402.26   11403.74 0.60



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.349880E+11 0.222311E+11 45911.75 14-JAN-12:40 33927.53 0.67
February 0.00 0.00 0.224363E+11 0.135836E+11 41052.07 02-FEB-12:30 35743.23 0.55
March 0.00 0.00 0.169593E+11 0.664649E+10 33759.25 11-MAR-13:10 26269.68 0.59
April 0.00 0.00 0.192376E+11 0.631212E+10 25503.97 08-APR-12:40 13491.03 0.73
May 0.00 0.00 0.116634E+11 0.266746E+10 22143.80 03-MAY-15:03 9960.59 0.65
June 0.00 0.00 0.153682E+11 0.361980E+10 20191.17 30-JUN-15:06 7754.73 0.78
July 0.00 0.00 0.235361E+11 0.664315E+10 24176.11 19-JUL-15:03 10746.75 0.92
August 0.00 0.00 0.312057E+11 0.105790E+11 24264.48 30-AUG-12:40 12151.52 0.99
September 0.00 0.00 0.343521E+11 0.144281E+11 42176.75 30-SEP-13:10 39301.46 0.98
October 0.00 0.00 0.431468E+11 0.252556E+11 51201.35 16-OCT-12:20 43514.48 0.87
November 0.00 0.00 0.356447E+11 0.227021E+11 48465.61 19-NOV-09:53 36991.93 0.67
December 0.00 0.00 0.389257E+11 0.288208E+11 46123.66 19-DEC-13:00 46123.66 0.55
                 
Annual Sum or Average 0.00 0.00 0.327464E+12 0.163489E+12       0.75
Minimum of Months 0.00 0.00 0.116634E+11 0.266746E+10 20191.17   7754.73 0.55
Maximum of Months 0.00 0.00 0.431468E+11 0.288208E+11 51201.35   46123.66 0.99



Table of Contents

Report: CoilReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.112394E+11 0.556612E+10 84417.85 20-JAN-19:01 66207.78 0.36
February 0.00 0.00 0.127748E+11 0.582245E+10 82887.72 13-FEB-21:12 64989.48 0.50
March 0.00 0.00 0.158503E+11 0.683492E+10 81831.23 22-MAR-18:51 65945.40 0.54
April 0.00 0.00 0.232985E+11 0.113024E+11 89070.55 26-APR-21:51 66509.65 0.56
May 0.00 0.00 0.274870E+11 0.145838E+11 86991.28 04-MAY-21:51 68976.69 0.55
June 0.00 0.00 0.309735E+11 0.172939E+11 92204.57 28-JUN-21:51 67441.92 0.48
July 0.00 0.00 0.370193E+11 0.213356E+11 93941.08 19-JUL-21:51 65976.27 0.49
August 0.00 0.00 0.342596E+11 0.188249E+11 92936.58 16-AUG-21:51 66540.85 0.47
September 0.00 0.00 0.272320E+11 0.140358E+11 92429.37 22-SEP-21:52 64588.19 0.46
October 0.00 0.00 0.244003E+11 0.152848E+11 91980.68 01-OCT-08:51 62546.65 0.37
November 0.00 0.00 0.145310E+11 0.720263E+10 84739.39 09-NOV-22:53 63237.43 0.45
December 0.00 0.00 0.104317E+11 0.624003E+10 81079.44 19-DEC-19:01 81079.44 0.30
                 
Annual Sum or Average 0.00 0.00 0.269497E+12 0.144327E+12       0.46
Minimum of Months 0.00 0.00 0.104317E+11 0.556612E+10 81079.44   62546.65 0.30
Maximum of Months 0.00 0.00 0.370193E+11 0.213356E+11 93941.08   81079.44 0.56



Table of Contents

Report: CoilReportMonthly

For: ROOM_5_FLR_3 FAN COIL COOLING COIL

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.231069E+10 0.129191E+10 12491.48 15-JAN-16:01 12491.48 0.50
February 0.00 0.00 0.182485E+10 0.102593E+10 12872.66 13-FEB-16:02 8682.85 0.43
March 0.00 0.00 0.208244E+10 0.958866E+09 12345.24 15-MAR-15:01 10491.95 0.51
April 0.00 0.00 0.380804E+10 0.182211E+10 12488.46 02-APR-08:62 12488.46 0.79
May 0.00 0.00 0.338270E+10 0.153054E+10 12733.83 06-MAY-08:62 9832.25 0.77
June 0.00 0.00 0.468018E+10 0.209351E+10 12843.80 28-JUN-08:62 9512.53 0.88
July 0.00 0.00 0.698008E+10 0.335747E+10 12480.99 13-JUL-18:01 10388.35 0.95
August 0.00 0.00 0.751455E+10 0.368507E+10 12774.71 08-AUG-08:62 9887.54 0.95
September 0.00 0.00 0.542190E+10 0.251212E+10 13146.25 23-SEP-08:62 9223.99 0.91
October 0.00 0.00 0.540079E+10 0.319977E+10 13245.24 01-OCT-08:61 9779.57 0.75
November 0.00 0.00 0.272858E+10 0.153145E+10 13097.02 12-NOV-09:02 8606.59 0.58
December 0.00 0.00 0.244847E+10 0.176044E+10 12492.10 31-DEC-09:01 12492.10 0.36
                 
Annual Sum or Average 0.00 0.00 0.485833E+11 0.247692E+11       0.70
Minimum of Months 0.00 0.00 0.182485E+10 0.958866E+09 12345.24   8606.59 0.36
Maximum of Months 0.00 0.00 0.751455E+10 0.368507E+10 13245.24   12492.10 0.95



Table of Contents

Report: CoilReportMonthly

For: ROOM_6_FLR_3 FAN COIL COOLING COIL

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.663480E+09 0.339008E+09 12316.20 20-JAN-19:01 9123.89 0.21
February 0.00 0.00 0.691428E+09 0.350155E+09 12281.95 14-FEB-09:02 9745.09 0.23
March 0.00 0.00 0.103991E+10 0.447134E+09 11948.53 22-MAR-18:51 9202.53 0.33
April 0.00 0.00 0.236595E+10 0.109464E+10 12915.78 02-APR-08:51 12915.78 0.60
May 0.00 0.00 0.244546E+10 0.109221E+10 13280.02 24-MAY-08:51 13280.02 0.60
June 0.00 0.00 0.317484E+10 0.142490E+10 13827.31 30-JUN-08:51 11448.04 0.58
July 0.00 0.00 0.466603E+10 0.228889E+10 14256.45 30-JUL-08:51 11079.71 0.58
August 0.00 0.00 0.458466E+10 0.221183E+10 14441.91 18-AUG-08:51 11038.16 0.58
September 0.00 0.00 0.289995E+10 0.128076E+10 14044.57 10-SEP-08:51 11294.25 0.58
October 0.00 0.00 0.253603E+10 0.145230E+10 13924.00 17-OCT-08:21 13924.00 0.46
November 0.00 0.00 0.902726E+09 0.435849E+09 12597.05 12-NOV-09:02 8175.06 0.30
December 0.00 0.00 0.583149E+09 0.382934E+09 12691.91 05-DEC-09:41 12691.91 0.16
                 
Annual Sum or Average 0.00 0.00 0.265536E+11 0.128006E+11       0.43
Minimum of Months 0.00 0.00 0.583149E+09 0.339008E+09 11948.53   8175.06 0.16
Maximum of Months 0.00 0.00 0.466603E+10 0.228889E+10 14441.91   13924.00 0.60



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_6 FAN COIL COOLING COIL

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.456990E+09 0.243220E+09 3869.35 21-JAN-09:02 2671.17 0.38
February 0.00 0.00 0.414317E+09 0.230542E+09 3874.95 13-FEB-16:02 2622.05 0.33
March 0.00 0.00 0.487631E+09 0.240857E+09 3704.74 24-MAR-08:61 2621.30 0.39
April 0.00 0.00 0.100095E+10 0.513319E+09 3749.09 08-APR-08:61 2733.30 0.70
May 0.00 0.00 0.919590E+09 0.443929E+09 3906.32 06-MAY-08:62 2437.47 0.68
June 0.00 0.00 0.133862E+10 0.644247E+09 3839.35 28-JUN-08:62 2577.87 0.84
July 0.00 0.00 0.191430E+10 0.957401E+09 3937.62 30-JUL-08:61 2777.41 0.93
August 0.00 0.00 0.195070E+10 0.978414E+09 4077.06 06-AUG-08:61 2652.39 0.93
September 0.00 0.00 0.147110E+10 0.715491E+09 3964.62 23-SEP-08:62 2444.97 0.89
October 0.00 0.00 0.128912E+10 0.759074E+09 4008.58 01-OCT-08:61 2720.11 0.68
November 0.00 0.00 0.601801E+09 0.319591E+09 3793.52 11-NOV-16:01 2666.73 0.46
December 0.00 0.00 0.503022E+09 0.351616E+09 3663.19 08-DEC-16:01 2811.27 0.28
                 
Annual Sum or Average 0.00 0.00 0.123481E+11 0.639770E+10       0.63
Minimum of Months 0.00 0.00 0.414317E+09 0.230542E+09 3663.19   2437.47 0.28
Maximum of Months 0.00 0.00 0.195070E+10 0.978414E+09 4077.06   2811.27 0.93



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_6 FAN COIL COOLING COIL

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 84301365.31 42469656.99 3603.71 21-JAN-09:02 2302.85 0.11
February 0.00 0.00 0.123064E+09 56183407.41 3676.11 13-FEB-16:02 2437.93 0.17
March 0.00 0.00 0.207399E+09 84172204.53 3635.98 22-MAR-18:51 2898.42 0.23
April 0.00 0.00 0.571078E+09 0.237022E+09 3910.07 26-APR-21:51 2853.74 0.51
May 0.00 0.00 0.634359E+09 0.271321E+09 3786.08 03-MAY-21:51 2946.89 0.55
June 0.00 0.00 0.913856E+09 0.415953E+09 4050.07 28-JUN-21:51 2909.04 0.56
July 0.00 0.00 0.133429E+10 0.682477E+09 4080.47 27-JUL-21:51 2883.15 0.57
August 0.00 0.00 0.122716E+10 0.596903E+09 4047.79 16-AUG-21:51 2840.53 0.56
September 0.00 0.00 0.809247E+09 0.338812E+09 3897.61 07-SEP-21:51 2633.55 0.57
October 0.00 0.00 0.582619E+09 0.315290E+09 4009.82 01-OCT-08:51 2454.07 0.40
November 0.00 0.00 0.142848E+09 61383988.53 3637.56 11-NOV-16:01 2433.21 0.21
December 0.00 0.00 77968184.67 54217173.59 3562.77 09-DEC-16:01 2776.83 0.07
                 
Annual Sum or Average 0.00 0.00 0.670819E+10 0.315620E+10       0.38
Minimum of Months 0.00 0.00 77968184.67 42469656.99 3562.77   2302.85 0.07
Maximum of Months 0.00 0.00 0.133429E+10 0.682477E+09 4080.47   2946.89 0.57



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.764340E+10 0.536691E+10 17169.90 14-JAN-19:01 17169.90 0.65
February 0.00 0.00 0.510830E+10 0.336316E+10 17984.72 13-FEB-16:02 12889.44 0.59
March 0.00 0.00 0.447999E+10 0.236354E+10 17394.28 20-MAR-15:01 14164.57 0.61
April 0.00 0.00 0.540427E+10 0.248549E+10 17237.19 22-APR-15:01 14298.99 0.78
May 0.00 0.00 0.351121E+10 0.132494E+10 17475.51 06-MAY-08:62 13124.57 0.68
June 0.00 0.00 0.465700E+10 0.169646E+10 17886.05 16-JUN-15:01 13454.68 0.80
July 0.00 0.00 0.724628E+10 0.293536E+10 18601.18 30-JUL-08:61 13226.89 0.89
August 0.00 0.00 0.904042E+10 0.399167E+10 18773.94 20-AUG-08:61 13096.50 0.91
September 0.00 0.00 0.883538E+10 0.442872E+10 18246.26 22-SEP-08:61 13117.29 0.90
October 0.00 0.00 0.101221E+11 0.681537E+10 18719.82 01-OCT-08:61 13135.47 0.76
November 0.00 0.00 0.782689E+10 0.534141E+10 17751.56 11-NOV-16:01 13900.03 0.70
December 0.00 0.00 0.817131E+10 0.651216E+10 17183.17 08-DEC-16:01 14338.52 0.50
                 
Annual Sum or Average 0.00 0.00 0.820465E+11 0.466252E+11       0.73
Minimum of Months 0.00 0.00 0.351121E+10 0.132494E+10 17169.90   12889.44 0.50
Maximum of Months 0.00 0.00 0.101221E+11 0.681537E+10 18773.94   17169.90 0.91



Table of Contents

Report: PlantLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 38237.63 150697.24 08-JAN-07:00
February 0.00 0.00 01-FEB-00:03 32548.50 111145.59 05-FEB-06:00
March 0.00 0.00 01-MAR-00:03 40722.04 140963.49 30-MAR-03:00
April 0.00 0.00 01-APR-00:10 18250.22 104882.63 01-APR-05:00
May 0.00 0.00 01-MAY-00:05 15439.33 94183.95 27-MAY-03:00
June 0.00 0.00 01-JUN-00:05 2934.71 63484.44 13-JUN-04:00
July 0.00 0.00 01-JUL-00:10 187.52 27554.62 06-JUL-01:00
August 0.00 0.00 01-AUG-00:05 83.75 23836.50 28-AUG-08:54
September 0.00 0.00 01-SEP-00:05 1340.65 60773.87 20-SEP-03:00
October 0.00 0.00 01-OCT-00:10 6316.87 89873.17 28-OCT-05:00
November 0.00 0.00 01-NOV-00:05 25522.07 102055.67 24-NOV-04:00
December 0.00 0.00 01-DEC-00:03 37003.31 116502.45 23-DEC-06:00
             
Annual Sum or Average 0.00     18165.73    
Minimum of Months 0.00 0.00   83.75 23836.50  
Maximum of Months 0.00 0.00   40722.04 150697.24  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 47243.03 326643.74 14-JAN-16:01 0.00 0.00 01-JAN-00:10
February 35142.78 310180.32 01-FEB-09:51 0.00 0.00 01-FEB-00:03
March 32537.81 340012.91 23-MAR-15:03 0.00 0.00 01-MAR-00:03
April 61168.01 319966.15 11-APR-15:03 0.00 0.00 01-APR-00:10
May 59551.69 308587.99 04-MAY-15:03 0.00 0.00 01-MAY-00:05
June 99208.11 375137.58 28-JUN-15:03 0.00 0.00 01-JUN-00:05
July 177009.90 528273.67 18-JUL-18:03 0.00 0.00 01-JUL-00:10
August 197358.11 537186.92 18-AUG-15:03 0.00 0.00 01-AUG-00:05
September 132759.61 500420.95 29-SEP-15:03 0.00 0.00 01-SEP-00:05
October 142648.37 507460.83 14-OCT-15:01 0.00 0.00 01-OCT-00:10
November 52280.52 384936.01 19-NOV-09:41 0.00 0.00 01-NOV-00:05
December 52378.99 362291.50 05-DEC-09:41 0.00 0.00 01-DEC-00:03
             
Annual Sum or Average 91279.59     0.00    
Minimum of Months 32537.81 308587.99   0.00 0.00  
Maximum of Months 197358.11 537186.92   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 23120.51 48443.70 31-JAN-07:15
February 0.00 0.00 01-FEB-00:03 23150.48 48445.21 02-FEB-07:50
March 0.00 0.00 01-MAR-00:03 22919.27 48206.02 01-MAR-07:40
April 0.00 0.00 01-APR-00:10 22438.01 47336.42 03-APR-06:20
May 0.00 0.00 01-MAY-00:05 21878.40 46290.89 01-MAY-07:00
June 0.00 0.00 01-JUN-00:05 21381.45 45108.45 01-JUN-06:20
July 0.00 0.00 01-JUL-00:10 21050.28 44195.19 03-JUL-06:50
August 0.00 0.00 01-AUG-00:05 21039.85 44108.96 31-AUG-06:20
September 0.00 0.00 01-SEP-00:05 21284.59 44854.19 29-SEP-06:50
October 0.00 0.00 01-OCT-00:10 21748.39 46034.05 31-OCT-06:30
November 0.00 0.00 01-NOV-00:05 22311.73 47180.38 30-NOV-07:30
December 0.00 0.00 01-DEC-00:03 22812.07 48035.37 29-DEC-07:30
             
Annual Sum or Average 0.00     22088.55    
Minimum of Months 0.00 0.00   21039.85 44108.96  
Maximum of Months 0.00 0.00   23150.48 48445.21  



Table of Contents

Report: FanReportMonthly

For: FLR_3_DOAS FAN

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.271000E+10 0.71 1299.30 01-JAN-00:25 0.89
February 0.244774E+10 0.70 1299.30 01-FEB-00:07 0.89
March 0.271000E+10 0.70 1299.30 03-MAR-09:04 0.89
April 0.262258E+10 0.70 1299.30 01-APR-01:10 0.89
May 0.271000E+10 0.70 1299.30 01-MAY-00:30 0.88
June 0.262258E+10 0.70 1299.30 01-JUN-01:05 0.89
July 0.271000E+10 0.70 1299.30 01-JUL-00:50 0.88
August 0.271000E+10 0.70 1299.30 01-AUG-00:50 0.89
September 0.262258E+10 0.70 1299.30 29-SEP-16:00 0.89
October 0.271000E+10 0.70 1299.30 13-OCT-15:09 0.89
November 0.262258E+10 0.70 1299.30 01-NOV-00:10 0.89
December 0.271000E+10 0.71 1299.30 01-DEC-00:30 0.89
           
Annual Sum or Average 0.319080E+11 0.70      
Minimum of Months 0.244774E+10 0.70 1299.30   0.88
Maximum of Months 0.271000E+10 0.71 1299.30   0.89



Table of Contents

Report: FanReportMonthly

For: VAV WITH REHEAT FAN

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.354911E+11 0.86 23882.68 18-JAN-22:10 1.21
February 0.325105E+11 0.86 23151.48 01-FEB-22:10 1.19
March 0.356248E+11 0.86 23067.16 24-MAR-21:10 1.18
April 0.356106E+11 0.87 23563.97 26-APR-21:10 1.19
May 0.370521E+11 0.87 24315.44 04-MAY-21:10 1.22
June 0.365613E+11 0.88 24028.79 28-JUN-21:10 1.21
July 0.381737E+11 0.88 24762.98 31-JUL-21:10 1.23
August 0.384129E+11 0.89 25171.80 18-AUG-21:10 1.24
September 0.367056E+11 0.88 27199.75 29-SEP-21:20 1.32
October 0.384540E+11 0.89 28258.03 16-OCT-21:10 1.35
November 0.355170E+11 0.87 24568.31 28-NOV-22:10 1.24
December 0.359194E+11 0.86 25677.96 05-DEC-22:10 1.27
           
Annual Sum or Average 0.436033E+12 0.87      
Minimum of Months 0.325105E+11 0.86 23067.16   1.18
Maximum of Months 0.384540E+11 0.89 28258.03   1.35



Table of Contents

Report: FanReportMonthly

For: LAUNDRY_FLR_1 EXHAUST FAN

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.205205E+09 0.27 76.61 01-JAN-00:10 0.27
February 0.185347E+09 0.27 76.61 01-FEB-00:03 0.27
March 0.205205E+09 0.27 76.61 01-MAR-00:03 0.27
April 0.198586E+09 0.27 76.61 01-APR-00:10 0.27
May 0.205205E+09 0.27 76.61 01-MAY-00:05 0.27
June 0.198586E+09 0.27 76.61 01-JUN-00:05 0.27
July 0.205205E+09 0.27 76.61 01-JUL-00:10 0.27
August 0.205205E+09 0.27 76.61 01-AUG-00:05 0.27
September 0.198586E+09 0.27 76.61 01-SEP-00:05 0.27
October 0.205205E+09 0.27 76.61 01-OCT-00:10 0.27
November 0.198586E+09 0.27 76.61 01-NOV-00:05 0.27
December 0.205205E+09 0.27 76.61 01-DEC-00:03 0.27
           
Annual Sum or Average 0.241613E+10 0.27      
Minimum of Months 0.185347E+09 0.27 76.61   0.27
Maximum of Months 0.205205E+09 0.27 76.61   0.27



Table of Contents

Report: FanReportMonthly

For: LOBBY_FLR_1 EXHAUST FAN

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 -0.0 0.00 01-JAN-00:10 -0.0
February 0.00 0.00 0.00 01-FEB-00:03 -0.0
March 0.00 -0.0 0.00 01-MAR-00:03 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00
May 0.00 -0.0 0.00 01-MAY-00:05 0.00
June 0.00 -0.0 0.00 01-JUN-00:05 0.00
July 0.00 -0.0 0.00 01-JUL-00:10 0.00
August 0.00 0.00 0.00 01-AUG-00:05 -0.0
September 0.00 -0.0 0.00 01-SEP-00:05 0.00
October 0.00 0.00 0.00 01-OCT-00:10 -0.0
November 0.00 -0.0 0.00 01-NOV-00:05 0.00
December 0.00 0.00 0.00 01-DEC-00:03 0.00
           
Annual Sum or Average 0.00 -0.0      
Minimum of Months 0.00 -0.0 0.00   -0.0
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: BANQUET_FLR_6 EXHAUST FAN

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 -0.0 0.00 01-JAN-00:10 0.00
February 0.00 0.00 0.00 01-FEB-00:03 0.00
March 0.00 0.00 0.00 01-MAR-00:03 0.00
April 0.00 -0.0 0.00 01-APR-00:10 0.00
May 0.00 -0.0 0.00 01-MAY-00:05 0.00
June 0.00 0.00 0.00 01-JUN-00:05 0.00
July 0.00 -0.0 0.00 01-JUL-00:10 0.00
August 0.00 0.00 0.00 01-AUG-00:05 0.00
September 0.00 0.00 0.00 01-SEP-00:05 0.00
October 0.00 -0.0 0.00 01-OCT-00:10 0.00
November 0.00 0.00 0.00 01-NOV-00:05 0.00
December 0.00 0.00 0.00 01-DEC-00:03 0.00
           
Annual Sum or Average 0.00 0.00      
Minimum of Months 0.00 -0.0 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: DINING_FLR_6 EXHAUST FAN

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 -0.0 0.00 01-JAN-00:10 0.00
February 0.00 -0.0 0.00 01-FEB-00:03 0.00
March 0.00 -0.0 0.00 01-MAR-00:03 0.00
April 0.00 -0.0 0.00 01-APR-00:10 0.00
May 0.00 0.00 0.00 01-MAY-00:05 0.00
June 0.00 -0.0 0.00 01-JUN-00:05 0.00
July 0.00 -0.0 0.00 01-JUL-00:10 0.00
August 0.00 0.00 0.00 01-AUG-00:05 0.00
September 0.00 0.00 0.00 01-SEP-00:05 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00
November 0.00 -0.0 0.00 01-NOV-00:05 0.00
December 0.00 -0.0 0.00 01-DEC-00:03 0.00
           
Annual Sum or Average 0.00 -0.0      
Minimum of Months 0.00 -0.0 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: KITCHEN_FLR_6 EXHAUST FAN

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.116283E+10 0.19 612.92 01-JAN-07:03 0.27
February 0.105030E+10 0.19 612.92 01-FEB-07:05 0.27
March 0.116283E+10 0.19 612.92 01-MAR-07:03 0.27
April 0.112532E+10 0.19 612.92 01-APR-06:10 0.27
May 0.116283E+10 0.19 612.92 01-MAY-06:05 0.27
June 0.112532E+10 0.19 612.92 01-JUN-06:05 0.27
July 0.116283E+10 0.19 612.92 01-JUL-06:05 0.27
August 0.116283E+10 0.19 612.92 01-AUG-06:05 0.27
September 0.112532E+10 0.19 612.92 01-SEP-06:05 0.27
October 0.116283E+10 0.19 612.92 01-OCT-06:10 0.27
November 0.112532E+10 0.19 612.92 01-NOV-06:05 0.27
December 0.116283E+10 0.19 612.92 01-DEC-07:05 0.27
           
Annual Sum or Average 0.136914E+11 0.19      
Minimum of Months 0.105030E+10 0.19 612.92   0.27
Maximum of Months 0.116283E+10 0.19 612.92   0.27



Table of Contents

Report: FanReportMonthly

For: ROOM_1_FLR_3 FAN COIL_FANCOILFAN

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.157367E+09 0.50 688.20 01-JAN-09:01 0.58
February 0.131806E+09 0.48 688.20 01-FEB-09:01 0.59
March 0.156304E+09 0.47 688.20 01-MAR-09:01 0.58
April 0.197497E+09 0.50 688.20 01-APR-15:01 0.58
May 0.184748E+09 0.48 688.20 01-MAY-08:62 0.58
June 0.235303E+09 0.50 688.20 01-JUN-15:01 0.58
July 0.315738E+09 0.53 688.20 01-JUL-08:61 0.58
August 0.322017E+09 0.54 688.20 01-AUG-08:62 0.58
September 0.264765E+09 0.53 688.20 01-SEP-08:62 0.58
October 0.260161E+09 0.52 688.20 01-OCT-08:61 0.58
November 0.154458E+09 0.50 688.20 01-NOV-08:62 0.58
December 0.161036E+09 0.50 688.20 01-DEC-09:01 0.58
           
Annual Sum or Average 0.254120E+10 0.50      
Minimum of Months 0.131806E+09 0.47 688.20   0.58
Maximum of Months 0.322017E+09 0.54 688.20   0.59



Table of Contents

Report: FanReportMonthly

For: ROOM_2_FLR_3 FAN COIL_FANCOILFAN

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.119796E+09 0.39 662.57 02-JAN-16:02 0.58
February 93998958.23 0.41 662.57 01-FEB-09:51 0.59
March 0.118240E+09 0.41 662.57 01-MAR-16:01 0.58
April 0.117755E+09 0.39 662.57 01-APR-15:01 0.58
May 0.125304E+09 0.37 662.57 01-MAY-08:51 0.58
June 0.142668E+09 0.33 662.57 01-JUN-08:51 0.58
July 0.194589E+09 0.33 662.57 01-JUL-08:51 0.58
August 0.182375E+09 0.32 662.57 01-AUG-08:51 0.58
September 0.140983E+09 0.33 662.57 01-SEP-08:51 0.58
October 0.127855E+09 0.33 662.57 01-OCT-08:51 0.58
November 86019252.55 0.39 662.57 01-NOV-08:62 0.58
December 0.108815E+09 0.39 662.57 02-DEC-16:01 0.58
           
Annual Sum or Average 0.155840E+10 0.37      
Minimum of Months 86019252.55 0.32 662.57   0.58
Maximum of Months 0.194589E+09 0.41 662.57   0.59



Table of Contents

Report: FanReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.123996E+10 0.46 2095.97 14-JAN-12:40 0.58
February 0.805500E+09 0.39 1274.49 02-FEB-12:30 0.58
March 0.630567E+09 0.34 1103.63 11-MAR-13:00 0.58
April 0.716345E+09 0.43 805.27 08-APR-12:40 0.58
May 0.474029E+09 0.38 700.38 03-MAY-15:03 0.58
June 0.588571E+09 0.45 626.72 30-JUN-15:06 0.58
July 0.849672E+09 0.54 729.38 19-JUL-15:03 0.58
August 0.109037E+10 0.58 768.91 30-AUG-13:00 0.58
September 0.119300E+10 0.57 1331.97 30-SEP-13:10 0.58
October 0.154127E+10 0.55 2410.51 16-OCT-12:20 0.59
November 0.124937E+10 0.49 2164.86 19-NOV-09:53 0.58
December 0.136105E+10 0.48 2059.44 16-DEC-13:00 0.58
           
Annual Sum or Average 0.117397E+11 0.47      
Minimum of Months 0.474029E+09 0.34 626.72   0.58
Maximum of Months 0.154127E+10 0.58 2410.51   0.59



Table of Contents

Report: FanReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.767017E+09 0.37 4036.31 01-JAN-09:01 0.58
February 0.702272E+09 0.38 4036.31 01-FEB-09:51 0.59
March 0.911741E+09 0.39 4036.31 01-MAR-09:01 0.59
April 0.987070E+09 0.34 4036.31 01-APR-08:62 0.59
May 0.116607E+10 0.32 4036.31 01-MAY-08:51 0.58
June 0.123005E+10 0.28 4036.31 01-JUN-08:51 0.58
July 0.146114E+10 0.28 4036.31 01-JUL-08:51 0.58
August 0.131773E+10 0.27 4036.31 01-AUG-08:51 0.58
September 0.106801E+10 0.27 4036.31 01-SEP-08:51 0.58
October 0.105962E+10 0.28 4036.31 01-OCT-08:51 0.58
November 0.746771E+09 0.35 4036.31 01-NOV-08:62 0.58
December 0.700719E+09 0.36 4036.31 01-DEC-09:01 0.58
           
Annual Sum or Average 0.121182E+11 0.33      
Minimum of Months 0.700719E+09 0.27 4036.31   0.58
Maximum of Months 0.146114E+10 0.39 4036.31   0.59



Table of Contents

Report: FanReportMonthly

For: ROOM_5_FLR_3 FAN COIL_FANCOILFAN

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.157228E+09 0.50 611.57 01-JAN-09:01 0.58
February 0.128913E+09 0.49 611.57 01-FEB-09:01 0.59
March 0.152095E+09 0.47 611.57 01-MAR-09:01 0.58
April 0.178079E+09 0.52 611.57 01-APR-08:62 0.58
May 0.159367E+09 0.50 611.57 01-MAY-08:62 0.58
June 0.195949E+09 0.52 611.57 01-JUN-08:62 0.58
July 0.280984E+09 0.55 611.57 01-JUL-08:61 0.58
August 0.301025E+09 0.56 611.57 01-AUG-08:62 0.58
September 0.226944E+09 0.53 611.57 01-SEP-08:62 0.58
October 0.244537E+09 0.53 611.57 01-OCT-08:61 0.58
November 0.149789E+09 0.51 611.57 01-NOV-08:62 0.58
December 0.160334E+09 0.51 611.57 01-DEC-09:01 0.58
           
Annual Sum or Average 0.233524E+10 0.52      
Minimum of Months 0.128913E+09 0.47 611.57   0.58
Maximum of Months 0.301025E+09 0.56 611.57   0.59



Table of Contents

Report: FanReportMonthly

For: ROOM_6_FLR_3 FAN COIL_FANCOILFAN

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.112333E+09 0.38 588.81 01-JAN-09:01 0.58
February 94591220.97 0.39 588.81 01-FEB-09:51 0.59
March 0.118114E+09 0.41 588.81 01-MAR-09:01 0.58
April 0.117349E+09 0.41 588.81 01-APR-08:62 0.58
May 0.117608E+09 0.39 588.81 01-MAY-08:51 0.58
June 0.134744E+09 0.34 588.81 01-JUN-08:51 0.58
July 0.191674E+09 0.34 588.81 01-JUL-08:51 0.58
August 0.187340E+09 0.34 588.81 01-AUG-08:51 0.58
September 0.124025E+09 0.34 588.81 01-SEP-08:51 0.58
October 0.120529E+09 0.34 588.81 01-OCT-08:51 0.58
November 84711182.77 0.36 588.81 01-NOV-08:62 0.58
December 0.103174E+09 0.37 588.81 01-DEC-09:01 0.58
           
Annual Sum or Average 0.150619E+10 0.37      
Minimum of Months 84711182.77 0.34 588.81   0.58
Maximum of Months 0.191674E+09 0.41 588.81   0.59



Table of Contents

Report: FanReportMonthly

For: ROOM_1_FLR_6 FAN COIL_FANCOILFAN

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 44486950.34 0.49 178.24 02-JAN-16:02 0.58
February 38827315.87 0.47 178.24 01-FEB-09:01 0.59
March 46202384.33 0.47 178.24 01-MAR-16:01 0.58
April 51150076.53 0.51 178.24 01-APR-15:01 0.58
May 47375271.30 0.49 178.24 01-MAY-08:62 0.58
June 58719081.51 0.51 178.24 01-JUN-15:01 0.58
July 80241158.11 0.54 178.24 01-JUL-08:61 0.58
August 80875189.07 0.54 178.24 01-AUG-08:62 0.58
September 63671529.67 0.53 178.24 01-SEP-08:62 0.58
October 62686433.81 0.52 178.24 01-OCT-08:61 0.58
November 40117295.74 0.50 178.24 01-NOV-08:62 0.58
December 45009934.83 0.50 178.24 01-DEC-09:01 0.58
           
Annual Sum or Average 0.659363E+09 0.51      
Minimum of Months 38827315.87 0.47 178.24   0.58
Maximum of Months 80875189.07 0.54 178.24   0.59



Table of Contents

Report: FanReportMonthly

For: ROOM_2_FLR_6 FAN COIL_FANCOILFAN

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 40564904.41 0.39 171.21 01-JAN-09:01 0.58
February 31829624.81 0.40 171.21 01-FEB-16:01 0.58
March 37846120.39 0.41 171.21 01-MAR-09:01 0.58
April 30605738.81 0.40 171.21 01-APR-15:01 0.58
May 31621217.57 0.38 171.21 01-MAY-08:51 0.58
June 37252952.27 0.34 171.21 01-JUN-08:51 0.58
July 52717335.77 0.33 171.21 01-JUL-08:51 0.58
August 48124078.03 0.33 171.21 01-AUG-08:51 0.58
September 33702582.18 0.34 171.21 01-SEP-08:51 0.58
October 30775022.75 0.33 171.21 01-OCT-08:51 0.58
November 27838184.78 0.39 171.21 01-NOV-15:01 0.58
December 37513178.63 0.39 171.21 02-DEC-16:01 0.58
           
Annual Sum or Average 0.440391E+09 0.37      
Minimum of Months 27838184.78 0.33 171.21   0.58
Maximum of Months 52717335.77 0.41 171.21   0.58



Table of Contents

Report: FanReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.379537E+09 0.53 836.92 01-JAN-09:01 0.58
February 0.259405E+09 0.51 836.92 01-FEB-09:01 0.59
March 0.251597E+09 0.49 836.92 01-MAR-09:01 0.58
April 0.241354E+09 0.51 836.92 01-APR-08:62 0.58
May 0.174270E+09 0.47 836.92 01-MAY-08:62 0.58
June 0.194573E+09 0.48 836.92 01-JUN-15:01 0.58
July 0.280730E+09 0.52 836.92 01-JUL-08:61 0.58
August 0.347418E+09 0.53 836.92 01-AUG-08:62 0.58
September 0.355463E+09 0.52 836.92 01-SEP-08:62 0.58
October 0.457036E+09 0.53 836.92 01-OCT-08:61 0.58
November 0.359820E+09 0.54 836.92 01-NOV-08:62 0.58
December 0.403704E+09 0.54 836.92 01-DEC-09:01 0.58
           
Annual Sum or Average 0.370491E+10 0.51      
Minimum of Months 0.174270E+09 0.47 836.92   0.58
Maximum of Months 0.457036E+09 0.54 836.92   0.59



Table of Contents

Report: PumpReportMonthly

For: HEATSYS1 PUMP

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.576838E+09 0.519154E+09 570.24 08-JAN-06:50 513.22 513.22 36.11 1.50
February 0.475672E+09 0.428105E+09 541.31 04-FEB-05:55 487.18 487.18 38.06 1.20
March 0.628164E+09 0.565347E+09 567.76 30-MAR-03:00 510.98 510.98 37.14 1.47
April 0.294213E+09 0.264791E+09 535.96 01-APR-05:00 482.36 482.36 38.27 1.15
May 0.255315E+09 0.229783E+09 517.89 14-MAY-04:50 466.10 466.10 38.15 1.03
June 48179997.96 43361998.16 393.12 13-JUN-04:00 353.81 353.81 33.88 0.58
July 3335232.25 3001709.02 172.49 06-JUL-03:00 155.24 155.24 27.07 0.20
August 1623737.07 1461363.36 157.21 22-AUG-08:54 141.49 141.49 40.21 0.18
September 22254348.78 20028913.90 378.90 20-SEP-04:00 341.01 341.01 33.48 0.55
October 0.105576E+09 95018573.75 510.04 12-OCT-05:00 459.04 459.04 38.26 0.99
November 0.398354E+09 0.358519E+09 531.55 24-NOV-04:00 478.39 478.39 38.23 1.12
December 0.571813E+09 0.514632E+09 547.49 23-DEC-06:00 492.74 492.74 37.78 1.25
                 
Annual Sum or Average 0.338134E+10 0.304320E+10            
Minimum of Months 1623737.07 1461363.36 157.21   141.49 141.49 27.07 0.18
Maximum of Months 0.628164E+09 0.565347E+09 570.24   513.22 513.22 40.21 1.50



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP SECONDARY

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 83356837.53 75021153.78 549.19 24-JAN-09:51 494.27 494.27 6.72 9.60
February 47355015.35 42619513.81 297.48 01-FEB-09:51 267.74 267.74 6.72 7.33
March 49398075.20 44458267.68 450.19 23-MAR-15:03 405.17 405.17 6.72 8.81
April 0.102815E+09 92533183.51 441.55 13-APR-08:51 397.40 397.40 6.72 8.73
May 96713677.13 87042309.42 440.30 18-MAY-15:03 396.27 396.27 6.72 8.72
June 0.169811E+09 0.152830E+09 559.36 29-JUN-18:03 503.43 503.43 6.72 9.68
July 0.431642E+09 0.388478E+09 1164.43 18-JUL-18:03 1047.99 1047.99 6.72 13.18
August 0.504794E+09 0.454315E+09 1048.09 18-AUG-15:13 943.28 943.28 6.72 12.62
September 0.298900E+09 0.269010E+09 1993.50 29-SEP-15:13 1794.15 1794.15 6.72 16.40
October 0.342429E+09 0.308186E+09 1387.17 17-OCT-10:50 1248.45 1248.45 6.72 14.16
November 89615711.31 80654140.18 803.48 19-NOV-11:00 723.13 723.13 6.72 11.29
December 81349562.58 73214606.33 444.95 16-DEC-16:01 400.45 400.45 6.72 8.76
                 
Annual Sum or Average 0.229818E+10 0.206836E+10            
Minimum of Months 47355015.35 42619513.81 297.48   267.74 267.74 6.72 7.33
Maximum of Months 0.504794E+09 0.454315E+09 1993.50   1794.15 1794.15 6.72 16.40



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.541088E+10 0.486979E+10 2259.10 01-JAN-00:10 2033.19 2033.19 6.72 19.98
February 0.505677E+10 0.455109E+10 2259.10 01-FEB-00:03 2033.19 2033.19 6.84 19.98
March 0.528042E+10 0.475238E+10 2259.10 01-MAR-06:13 2033.19 2033.19 6.72 19.98
April 0.578973E+10 0.521076E+10 2259.10 01-APR-00:20 2033.19 2033.19 6.72 19.98
May 0.604067E+10 0.543661E+10 2259.10 01-MAY-00:05 2033.19 2033.19 7.27 19.98
June 0.585559E+10 0.527003E+10 2259.10 01-JUN-00:05 2033.19 2033.19 6.96 19.98
July 0.605077E+10 0.544569E+10 2259.10 01-JUL-00:10 2033.19 2033.19 8.02 19.98
August 0.605077E+10 0.544569E+10 2259.10 01-AUG-00:05 2033.19 2033.19 8.86 19.98
September 0.585559E+10 0.527003E+10 2259.10 01-SEP-00:05 2033.19 2033.19 7.52 19.98
October 0.605077E+10 0.544569E+10 2259.10 01-OCT-00:10 2033.19 2033.19 9.01 19.98
November 0.567723E+10 0.510951E+10 2259.10 01-NOV-00:05 2033.19 2033.19 7.15 19.98
December 0.557184E+10 0.501466E+10 2259.10 01-DEC-00:03 2033.19 2033.19 6.89 19.98
                 
Annual Sum or Average 0.686910E+11 0.618219E+11            
Minimum of Months 0.505677E+10 0.455109E+10 2259.10   2033.19 2033.19 6.72 19.98
Maximum of Months 0.605077E+10 0.544569E+10 2259.10   2033.19 2033.19 9.01 19.98



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.128314E+09 38494137.67 47.91 01-JAN-00:10 14.37 14.37 50.47 0.37
February 0.115896E+09 34768898.54 47.91 01-FEB-00:03 14.37 14.37 50.90 0.37
March 0.128314E+09 38494137.67 47.91 01-MAR-00:03 14.37 14.37 50.95 0.37
April 0.124175E+09 37252391.29 47.91 01-APR-00:10 14.37 14.37 53.59 0.37
May 0.128314E+09 38494137.67 47.91 01-MAY-00:05 14.37 14.37 53.53 0.37
June 0.124175E+09 37252391.29 47.91 01-JUN-00:05 14.37 14.37 53.70 0.37
July 0.128314E+09 38494137.67 47.91 01-JUL-00:10 14.37 14.37 54.02 0.37
August 0.128314E+09 38494137.67 47.91 01-AUG-00:05 14.37 14.37 53.88 0.37
September 0.124175E+09 37252391.29 47.91 01-SEP-00:05 14.37 14.37 53.84 0.37
October 0.128314E+09 38494137.67 47.91 01-OCT-00:10 14.37 14.37 53.19 0.37
November 0.124175E+09 37252391.29 47.91 01-NOV-00:05 14.37 14.37 53.57 0.37
December 0.128314E+09 38494137.67 47.91 01-DEC-00:03 14.37 14.37 51.14 0.37
                 
Annual Sum or Average 0.151079E+10 0.453237E+09            
Minimum of Months 0.115896E+09 34768898.54 47.91   14.37 14.37 50.47 0.37
Maximum of Months 0.128314E+09 38494137.67 47.91   14.37 14.37 54.02 0.37



Table of Contents

Report: CondLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 38.33 60.00 38237.63 150697.24 08-JAN-07:00
February 0.00 0.00 01-FEB-00:03 28.31 60.00 32548.50 111145.59 05-FEB-06:00
March 0.00 0.00 01-MAR-00:03 37.96 60.00 40722.04 140963.49 30-MAR-03:00
April 0.00 0.00 01-APR-00:10 37.83 60.00 18250.22 104882.63 01-APR-05:00
May 0.00 0.00 01-MAY-00:05 30.04 30.04 15439.33 94183.95 27-MAY-03:00
June 0.00 0.00 01-JUN-00:05 26.89 60.00 2934.71 63484.44 13-JUN-04:00
July 0.00 0.00 01-JUL-00:10 26.02 26.02 187.52 27554.62 06-JUL-01:00
August 0.00 0.00 01-AUG-00:05 36.84 36.84 83.75 23836.50 28-AUG-08:54
September 0.00 0.00 01-SEP-00:05 27.45 27.45 1340.65 60773.87 20-SEP-03:00
October 0.00 0.00 01-OCT-00:10 38.68 38.68 6316.87 89873.17 28-OCT-05:00
November 0.00 0.00 01-NOV-00:05 28.96 28.96 25522.07 102055.67 24-NOV-04:00
December 0.00 0.00 01-DEC-00:03 34.23 60.00 37003.31 116502.45 23-DEC-06:00
                 
Annual Sum or Average 0.00         18165.73    
Minimum of Months 0.00 0.00   26.02 26.02 83.75 23836.50  
Maximum of Months 0.00 0.00   38.68 60.00 40722.04 150697.24  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 47243.03 326643.74 14-JAN-16:01 10.60 6.70 0.00 0.00 01-JAN-00:10
February 35142.78 310180.32 01-FEB-09:51 10.40 6.70 0.00 0.00 01-FEB-00:03
March 32537.81 340012.91 23-MAR-15:03 10.76 6.70 0.00 0.00 01-MAR-00:03
April 61168.01 319966.15 11-APR-15:03 10.52 6.70 0.00 0.00 01-APR-00:10
May 59551.69 308587.99 04-MAY-15:03 10.39 6.70 0.00 0.00 01-MAY-00:05
June 99208.11 375137.58 28-JUN-15:03 11.18 6.70 0.00 0.00 01-JUN-00:05
July 177009.90 528273.67 18-JUL-18:03 13.01 6.70 0.00 0.00 01-JUL-00:10
August 197358.11 537186.92 18-AUG-15:03 13.12 6.70 0.00 0.00 01-AUG-00:05
September 132759.61 500420.95 29-SEP-15:03 12.68 6.70 0.00 0.00 01-SEP-00:05
October 142648.37 507460.83 14-OCT-15:01 12.76 6.70 0.00 0.00 01-OCT-00:10
November 52280.52 384936.01 19-NOV-09:41 11.30 6.70 0.00 0.00 01-NOV-00:05
December 52378.99 362291.50 05-DEC-09:41 11.03 6.70 0.00 0.00 01-DEC-00:03
                 
Annual Sum or Average 91279.59         0.00    
Minimum of Months 32537.81 308587.99   10.39 6.70 0.00 0.00  
Maximum of Months 197358.11 537186.92   13.12 6.70 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 50.47 60.05 23120.51 48443.70 31-JAN-07:15
February 0.00 0.00 01-FEB-00:03 50.90 60.05 23150.48 48445.21 02-FEB-07:50
March 0.00 0.00 01-MAR-00:03 50.95 60.05 22919.27 48206.02 01-MAR-07:40
April 0.00 0.00 01-APR-00:10 53.59 60.05 22438.01 47336.42 03-APR-06:20
May 0.00 0.00 01-MAY-00:05 53.53 60.05 21878.40 46290.89 01-MAY-07:00
June 0.00 0.00 01-JUN-00:05 53.70 60.05 21381.45 45108.45 01-JUN-06:20
July 0.00 0.00 01-JUL-00:10 54.02 60.05 21050.28 44195.19 03-JUL-06:50
August 0.00 0.00 01-AUG-00:05 53.88 60.05 21039.85 44108.96 31-AUG-06:20
September 0.00 0.00 01-SEP-00:05 53.84 60.05 21284.59 44854.19 29-SEP-06:50
October 0.00 0.00 01-OCT-00:10 53.19 60.05 21748.39 46034.05 31-OCT-06:30
November 0.00 0.00 01-NOV-00:05 53.57 60.05 22311.73 47180.38 30-NOV-07:30
December 0.00 0.00 01-DEC-00:03 51.14 60.05 22812.07 48035.37 29-DEC-07:30
                 
Annual Sum or Average 0.00         22088.55    
Minimum of Months 0.00 0.00   50.47 60.05 21039.85 44108.96  
Maximum of Months 0.00 0.00   54.02 60.05 23150.48 48445.21  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BASEMENT

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: RETAIL_1_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: RETAIL_2_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: MECH_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: STORAGE_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: LAUNDRY_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CAFE_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: LOBBY_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_1_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_2_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_5_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_6_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORRIDOR_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_1_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_2_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BANQUET_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DINING_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: KITCHEN_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORRIDOR_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: FLR_3_DOAS

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.796627E+10 0.00 0.352394E+10 0.271000E+10 0.00 0.00
February 0.641498E+10 0.00 0.189616E+10 0.244774E+10 0.00 0.00
March 0.857742E+10 0.00 0.213914E+10 0.271000E+10 0.00 0.00
April 0.405566E+10 0.00 0.536108E+10 0.262258E+10 0.00 0.00
May 0.360689E+10 0.00 0.568444E+10 0.271000E+10 0.00 0.00
June 0.639403E+09 0.00 0.127679E+11 0.262258E+10 0.00 0.00
July 37027035.96 0.00 0.285718E+11 0.271000E+10 0.00 0.00
August 17469671.82 0.00 0.326065E+11 0.271000E+10 0.00 0.00
September 0.319034E+09 0.00 0.185738E+11 0.262258E+10 0.00 0.00
October 0.143387E+10 0.00 0.206208E+11 0.271000E+10 0.00 0.00
November 0.564075E+10 0.00 0.354751E+10 0.262258E+10 0.00 0.00
December 0.800628E+10 0.00 0.428641E+10 0.271000E+10 0.00 0.00
             
Annual Sum or Average 0.467151E+11 0.00 0.139579E+12 0.319080E+11 0.00 0.00
Minimum of Months 17469671.82 0.00 0.189616E+10 0.244774E+10 0.00 0.00
Maximum of Months 0.857742E+10 0.00 0.326065E+11 0.271000E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV WITH REHEAT

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.902641E+11 0.00 0.580356E+11 0.354911E+11 0.00 0.00
February 0.704084E+11 0.00 0.325376E+11 0.325105E+11 0.00 0.00
March 0.970608E+11 0.00 0.360422E+11 0.356248E+11 0.00 0.00
April 0.429903E+11 0.00 0.856442E+11 0.356106E+11 0.00 0.00
May 0.375501E+11 0.00 0.916843E+11 0.370521E+11 0.00 0.00
June 0.693222E+10 0.00 0.168981E+12 0.365613E+11 0.00 0.00
July 0.425797E+09 0.00 0.344845E+12 0.381737E+11 0.00 0.00
August 0.182770E+09 0.00 0.388248E+12 0.384129E+11 0.00 0.00
September 0.308041E+10 0.00 0.229551E+12 0.367056E+11 0.00 0.00
October 0.153994E+11 0.00 0.260147E+12 0.384540E+11 0.00 0.00
November 0.595409E+11 0.00 0.605792E+11 0.355170E+11 0.00 0.00
December 0.882108E+11 0.00 0.668534E+11 0.359194E+11 0.00 0.00
             
Annual Sum or Average 0.512046E+12 0.00 0.182315E+13 0.436033E+12 0.00 0.00
Minimum of Months 0.182770E+09 0.00 0.325376E+11 0.325105E+11 0.00 0.00
Maximum of Months 0.970608E+11 0.00 0.388248E+12 0.384540E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: FLR_3_DOAS

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.271000E+10 0.352394E+10 0.796627E+10 0.00 0.00 0.00 0.00 0.00
February 0.244774E+10 0.189616E+10 0.641498E+10 0.00 0.00 0.00 0.00 0.00
March 0.271000E+10 0.213914E+10 0.857742E+10 0.00 0.00 0.00 0.00 0.00
April 0.262258E+10 0.536108E+10 0.405566E+10 0.00 0.00 0.00 0.00 0.00
May 0.271000E+10 0.568444E+10 0.360689E+10 0.00 0.00 0.00 0.00 0.00
June 0.262258E+10 0.127679E+11 0.639403E+09 0.00 0.00 0.00 0.00 0.00
July 0.271000E+10 0.285718E+11 37027035.96 0.00 0.00 0.00 0.00 0.00
August 0.271000E+10 0.326065E+11 17469671.82 0.00 0.00 0.00 0.00 0.00
September 0.262258E+10 0.185738E+11 0.319034E+09 0.00 0.00 0.00 0.00 0.00
October 0.271000E+10 0.206208E+11 0.143387E+10 0.00 0.00 0.00 0.00 0.00
November 0.262258E+10 0.354751E+10 0.564075E+10 0.00 0.00 0.00 0.00 0.00
December 0.271000E+10 0.428641E+10 0.800628E+10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.319080E+11 0.139579E+12 0.467151E+11 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.244774E+10 0.189616E+10 17469671.82 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.271000E+10 0.326065E+11 0.857742E+10 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV WITH REHEAT

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.354911E+11 0.580356E+11 0.902641E+11 0.00 0.00 0.00 0.00 0.00
February 0.325105E+11 0.325376E+11 0.704084E+11 0.00 0.00 0.00 0.00 0.00
March 0.356248E+11 0.360422E+11 0.970608E+11 0.00 0.00 0.00 0.00 0.00
April 0.356106E+11 0.856442E+11 0.429903E+11 0.00 0.00 0.00 0.00 0.00
May 0.370521E+11 0.916843E+11 0.375501E+11 0.00 0.00 0.00 0.00 0.00
June 0.365613E+11 0.168981E+12 0.693222E+10 0.00 0.00 0.00 0.00 0.00
July 0.381737E+11 0.344845E+12 0.425797E+09 0.00 0.00 0.00 0.00 0.00
August 0.384129E+11 0.388248E+12 0.182770E+09 0.00 0.00 0.00 0.00 0.00
September 0.367056E+11 0.229551E+12 0.308041E+10 0.00 0.00 0.00 0.00 0.00
October 0.384540E+11 0.260147E+12 0.153994E+11 0.00 0.00 0.00 0.00 0.00
November 0.355170E+11 0.605792E+11 0.595409E+11 0.00 0.00 0.00 0.00 0.00
December 0.359194E+11 0.668534E+11 0.882108E+11 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.436033E+12 0.182315E+13 0.512046E+12 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.325105E+11 0.325376E+11 0.182770E+09 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.384540E+11 0.388248E+12 0.970608E+11 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: FLR_3_DOAS

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.271000E+10 0.796627E+10 0.352394E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.244774E+10 0.641498E+10 0.189616E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.271000E+10 0.857742E+10 0.213914E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.262258E+10 0.405566E+10 0.536108E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.271000E+10 0.360689E+10 0.568444E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.262258E+10 0.639403E+09 0.127679E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.271000E+10 37027035.96 0.285718E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.271000E+10 17469671.82 0.326065E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.262258E+10 0.319034E+09 0.185738E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.271000E+10 0.143387E+10 0.206208E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.262258E+10 0.564075E+10 0.354751E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.271000E+10 0.800628E+10 0.428641E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.319080E+11 0.467151E+11 0.139579E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.244774E+10 17469671.82 0.189616E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.271000E+10 0.857742E+10 0.326065E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV WITH REHEAT

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.354911E+11 0.902641E+11 0.580356E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.325105E+11 0.704084E+11 0.325376E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.356248E+11 0.970608E+11 0.360422E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.356106E+11 0.429903E+11 0.856442E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.370521E+11 0.375501E+11 0.916843E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.365613E+11 0.693222E+10 0.168981E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.381737E+11 0.425797E+09 0.344845E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.384129E+11 0.182770E+09 0.388248E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.367056E+11 0.308041E+10 0.229551E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.384540E+11 0.153994E+11 0.260147E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.355170E+11 0.595409E+11 0.605792E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.359194E+11 0.882108E+11 0.668534E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.436033E+12 0.512046E+12 0.182315E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.325105E+11 0.182770E+09 0.325376E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.384540E+11 0.970608E+11 0.388248E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BASEMENT

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.424151E+11 0.00 0.00 5211415.17 77329012.66 0.00 0.111469E+11 0.00 1.01
February 0.468116E+11 0.00 0.00 401592.59 14151252.45 0.00 0.117716E+10 0.00 1.01
March 0.550261E+11 0.00 0.00 0.00 131877.72 0.00 0.00 0.00 1.01
April 0.431474E+11 0.00 0.00 0.00 79350020.58 0.00 0.00 0.00 1.01
May 0.433853E+11 0.00 0.00 0.00 11321854.45 0.00 0.00 0.00 1.01
June 0.320859E+11 0.00 0.00 0.00 0.560409E+09 0.00 0.00 0.00 1.01
July 0.204172E+11 0.00 0.00 18233.70 0.463608E+10 0.00 0.207027E+09 0.00 1.02
August 0.162287E+11 0.00 0.00 267209.70 0.557649E+10 0.00 0.127796E+10 0.00 1.02
September 0.225707E+11 67557174.02 0.00 3876105.98 0.169303E+10 0.00 0.539683E+10 0.00 1.02
October 0.994291E+10 0.109765E+09 0.00 14855047.78 0.300042E+10 0.00 0.198541E+11 0.00 1.02
November 0.193809E+11 377609.55 0.00 15520753.49 51157449.62 0.00 0.294700E+11 0.00 1.02
December 0.375439E+11 0.00 0.00 7223668.94 27407126.79 0.00 0.149707E+11 0.00 1.01
                   
Annual Sum or Average 0.388956E+12 0.177700E+09 0.00 47374027.34 0.157273E+11 0.00 0.835008E+11 0.00 1.01
Minimum of Months 0.994291E+10 0.00 0.00 0.00 131877.72 0.00 0.00 0.00 1.01
Maximum of Months 0.550261E+11 0.109765E+09 0.00 15520753.49 0.557649E+10 0.00 0.294700E+11 0.00 1.02



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: RETAIL_1_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.611178E+10 14489237.56 0.00 2321322.99 370698.93 1360984.56 0.863105E+09 0.00 2.43
February 0.564697E+10 2459157.62 0.00 1512805.14 0.00 0.00 0.554428E+09 0.00 2.40
March 0.678967E+10 0.00 0.00 649531.45 16910.82 27035354.27 0.241779E+09 0.00 2.36
April 0.539443E+10 4852595.72 0.00 209792.30 5322539.82 0.00 0.138203E+09 0.00 2.35
May 0.555994E+10 529264.48 0.00 6030.41 922548.68 0.00 3390891.88 0.00 2.35
June 0.411441E+10 0.00 0.00 0.00 71861783.94 0.00 0.00 0.00 2.36
July 0.264100E+10 0.101325E+09 0.00 2328.39 0.493165E+09 0.00 3667079.41 0.00 2.36
August 0.215892E+10 0.352342E+09 0.00 85126.43 0.362737E+09 0.00 85925295.51 0.00 2.37
September 0.317506E+10 0.186639E+09 0.00 987827.48 82165656.83 0.00 0.415743E+09 0.00 2.41
October 0.314276E+10 0.442803E+09 0.00 2015868.46 96825995.96 0.00 0.679323E+09 0.00 2.53
November 0.551186E+10 10778224.81 0.00 2466926.27 0.00 0.00 0.792071E+09 0.00 2.46
December 0.594536E+10 5606673.06 0.00 3271746.87 0.00 0.00 0.902066E+09 0.00 2.49
                   
Annual Sum or Average 0.561922E+11 0.112182E+10 0.00 13529306.21 0.111339E+10 28396338.84 0.467970E+10 0.00 2.41
Minimum of Months 0.215892E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2.35
Maximum of Months 0.678967E+10 0.442803E+09 0.00 3271746.87 0.493165E+09 27035354.27 0.902066E+09 0.00 2.53



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: RETAIL_2_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.429933E+10 0.00 0.00 288939.92 7230588.42 0.00 0.707498E+09 0.00 1.48
February 0.374543E+10 0.00 0.00 312083.21 1323201.71 0.00 0.744060E+09 0.00 1.48
March 0.461263E+10 0.00 0.00 204039.75 12331.12 0.00 0.533816E+09 0.00 1.48
April 0.299005E+10 0.00 0.00 587296.87 7419561.17 0.00 0.104988E+10 0.00 1.49
May 0.314917E+10 0.00 0.00 491898.19 1058641.08 0.00 0.910292E+09 0.00 1.49
June 0.186770E+10 98470.93 0.00 1004174.36 52302099.03 0.00 0.114146E+10 0.00 1.50
July 0.645880E+09 13460852.44 0.00 1839844.22 0.420101E+09 0.00 0.129956E+10 0.00 1.51
August 0.354289E+09 9860263.66 0.00 2275816.98 0.511571E+09 0.00 0.131334E+10 0.00 1.52
September 0.105707E+10 38910611.52 0.00 1689824.61 0.125916E+09 0.00 0.159020E+10 0.00 1.51
October 0.125308E+10 85963842.86 0.00 1889340.72 0.205082E+09 0.00 0.155862E+10 0.00 1.51
November 0.329008E+10 35308.08 0.00 640848.58 4783437.03 0.00 0.123433E+10 0.00 1.48
December 0.395665E+10 0.00 0.00 441114.00 2562681.80 0.00 0.951456E+09 0.00 1.48
                   
Annual Sum or Average 0.312213E+11 0.148329E+09 0.00 11665221.42 0.133936E+10 0.00 0.130345E+11 0.00 1.49
Minimum of Months 0.354289E+09 0.00 0.00 204039.75 12331.12 0.00 0.533816E+09 0.00 1.48
Maximum of Months 0.461263E+10 85963842.86 0.00 2275816.98 0.511571E+09 0.00 0.159020E+10 0.00 1.52



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: MECH_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.398030E+10 0.00 0.00 0.00 5748515.90 0.00 0.00 0.00 0.55
February 0.356744E+10 0.00 0.00 0.00 1051981.62 0.00 0.00 0.00 0.56
March 0.409055E+10 0.00 0.00 0.00 9803.58 0.00 0.00 0.00 0.56
April 0.320751E+10 0.00 0.00 0.00 5898754.42 0.00 0.00 0.00 0.56
May 0.322519E+10 0.00 0.00 0.00 841648.67 0.00 0.00 0.00 0.56
June 0.238522E+10 0.00 0.00 0.00 41659888.86 0.00 0.00 0.00 0.56
July 0.152754E+10 93730.21 0.00 2194.98 0.344545E+09 0.00 5634559.87 0.00 0.56
August 0.129827E+10 0.00 0.00 2597.86 0.414548E+09 0.00 3162456.43 0.00 0.56
September 0.207406E+10 59010.87 0.00 14864.81 0.130820E+09 0.00 5279283.87 0.00 0.56
October 0.215321E+10 3150838.71 0.00 56620.51 0.227931E+09 0.00 45341739.67 0.00 0.56
November 0.359370E+10 0.00 0.00 0.00 3831034.40 0.00 0.00 0.00 0.56
December 0.390037E+10 0.00 0.00 0.00 2037402.25 0.00 0.00 0.00 0.55
                   
Annual Sum or Average 0.350034E+11 3303579.80 0.00 76278.16 0.117892E+10 0.00 59418039.85 0.00 0.56
Minimum of Months 0.129827E+10 0.00 0.00 0.00 9803.58 0.00 0.00 0.00 0.55
Maximum of Months 0.409055E+10 3150838.71 0.00 56620.51 0.414548E+09 0.00 45341739.67 0.00 0.56



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: STORAGE_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.233590E+10 0.00 0.00 0.00 3373599.23 0.00 0.00 0.00 0.56
February 0.209360E+10 0.00 0.00 0.00 617370.54 0.00 0.00 0.00 0.56
March 0.240060E+10 0.00 0.00 0.00 5753.37 0.00 0.00 0.00 0.56
April 0.188237E+10 0.00 0.00 0.00 3461768.86 0.00 0.00 0.00 0.57
May 0.189275E+10 0.00 0.00 0.00 493933.62 0.00 0.00 0.00 0.57
June 0.139980E+10 0.00 0.00 0.00 24448704.89 0.00 0.00 0.00 0.57
July 0.899766E+09 0.00 0.00 0.00 0.202256E+09 0.00 0.00 0.00 0.57
August 0.763765E+09 0.00 0.00 0.00 0.243283E+09 0.00 0.00 0.00 0.57
September 0.122030E+10 0.00 0.00 0.00 76808190.93 0.00 0.00 0.00 0.57
October 0.129018E+10 0.00 0.00 0.00 0.135614E+09 0.00 0.00 0.00 0.57
November 0.210902E+10 0.00 0.00 0.00 2248297.63 0.00 0.00 0.00 0.56
December 0.228899E+10 0.00 0.00 0.00 1195678.81 0.00 0.00 0.00 0.56
                   
Annual Sum or Average 0.205770E+11 0.00 0.00 0.00 0.693806E+09 0.00 0.00 0.00 0.57
Minimum of Months 0.763765E+09 0.00 0.00 0.00 5753.37 0.00 0.00 0.00 0.56
Maximum of Months 0.240060E+10 0.00 0.00 0.00 0.243283E+09 0.00 0.00 0.00 0.57



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: LAUNDRY_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.435995E+09 0.104643E+09 0.00 98125524.88 0.00 0.00 0.817724E+11 0.00 23.82
February 0.304375E+09 19149784.20 0.00 87404582.16 0.00 0.00 0.738924E+11 0.00 24.10
March 0.318079E+09 178459.82 0.00 95907845.30 0.00 0.00 0.844899E+11 0.00 24.04
April 0.190968E+09 0.107378E+09 0.00 0.104523E+09 0.00 0.00 0.669647E+11 0.00 24.13
May 0.213120E+09 15320980.97 0.00 0.113430E+09 0.00 0.00 0.673641E+11 0.00 24.18
June 62396765.84 0.765794E+09 0.00 0.113945E+09 293877.60 0.00 0.501360E+11 0.00 24.26
July 61661345.69 0.641646E+10 0.00 96963300.94 49035471.20 0.00 0.315644E+11 0.00 24.19
August 7939157.72 0.754872E+10 0.00 89964368.19 0.126646E+09 0.00 0.272179E+11 0.00 24.34
September 66977823.86 0.243951E+10 0.00 99632655.23 0.00 0.00 0.433505E+11 0.00 24.31
October 81450288.73 0.430731E+10 0.00 92858376.67 43769438.76 0.00 0.460119E+11 0.00 24.25
November 0.230793E+09 69738368.80 0.00 97504472.52 0.00 0.00 0.748859E+11 0.00 24.13
December 0.297258E+09 37403151.17 0.00 98689578.69 0.00 0.00 0.807718E+11 0.00 23.91
                   
Annual Sum or Average 0.227101E+10 0.218316E+11 0.00 0.118895E+10 0.219745E+09 0.00 0.728422E+12 0.00 24.14
Minimum of Months 7939157.72 178459.82 0.00 87404582.16 0.00 0.00 0.272179E+11 0.00 23.82
Maximum of Months 0.435995E+09 0.754872E+10 0.00 0.113945E+09 0.126646E+09 0.00 0.844899E+11 0.00 24.34



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CAFE_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.790195E+10 57233139.54 0.00 23167677.99 1174245.29 0.00 0.229127E+11 0.00 3.81
February 0.786110E+10 9517311.61 0.00 17869841.93 0.00 0.00 0.195907E+11 0.00 3.77
March 0.133677E+11 74818.91 0.00 12364556.84 0.00 0.00 0.178752E+11 0.00 3.72
April 0.663271E+10 33370419.74 0.00 13221602.94 11647664.46 0.00 0.178703E+11 0.00 3.72
May 0.893239E+10 2341636.90 0.00 9798154.76 4081653.14 0.00 0.156936E+11 0.00 3.71
June 0.540724E+10 21727245.29 0.00 12873799.37 0.296212E+09 0.00 0.128038E+11 0.00 3.72
July 0.224005E+10 0.140500E+10 0.00 16552113.30 0.122521E+10 0.00 0.949640E+10 0.00 3.74
August 0.107886E+10 0.215063E+10 0.00 19875237.73 0.101312E+10 0.00 0.900767E+10 0.00 3.78
September 0.222437E+10 0.841653E+09 0.00 22856656.13 0.244024E+09 0.00 0.138935E+11 0.00 3.82
October 0.200320E+10 0.186873E+10 0.00 27966694.95 0.203217E+09 0.00 0.153928E+11 0.00 3.96
November 0.389540E+10 41394909.41 0.00 26952139.87 0.00 0.00 0.240417E+11 0.00 3.85
December 0.668453E+10 21043835.08 0.00 28464596.17 0.00 0.00 0.236454E+11 0.00 3.88
                   
Annual Sum or Average 0.682295E+11 0.645272E+10 0.00 0.231963E+09 0.299869E+10 0.00 0.202224E+12 0.00 3.79
Minimum of Months 0.107886E+10 74818.91 0.00 9798154.76 0.00 0.00 0.900767E+10 0.00 3.71
Maximum of Months 0.133677E+11 0.215063E+10 0.00 28464596.17 0.122521E+10 0.00 0.240417E+11 0.00 3.96



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: LOBBY_FLR_1

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.529333E+11 55654215.62 0.00 30549406.65 92386283.87 0.00 0.500044E+11 0.00 1.81
February 0.409166E+11 0.00 0.00 28940449.86 27091493.97 0.00 0.514279E+11 0.00 1.82
March 0.608887E+11 0.00 0.00 22227233.91 252469.85 0.00 0.446598E+11 0.00 1.81
April 0.326151E+11 0.00 0.00 36412889.80 0.151910E+09 0.00 0.504459E+11 0.00 1.82
May 0.314572E+11 0.00 0.00 36888703.86 21674827.21 0.00 0.519676E+11 0.00 1.82
June 0.177718E+11 2016113.23 0.00 53284927.18 0.107084E+10 0.00 0.442761E+11 0.00 1.83
July 0.673328E+10 0.420032E+09 0.00 69187931.09 0.845601E+10 0.00 0.335225E+11 0.00 1.85
August 0.396000E+10 0.630368E+09 0.00 74673125.46 0.100454E+11 0.00 0.307661E+11 0.00 1.86
September 0.117025E+11 0.139152E+10 0.00 65350815.39 0.200184E+10 0.00 0.432388E+11 0.00 1.86
October 0.960263E+10 0.363643E+10 0.00 72478644.44 0.233226E+10 0.00 0.494586E+11 0.00 1.88
November 0.272176E+11 91518055.42 0.00 47710618.02 7200495.42 0.00 0.664805E+11 0.00 1.82
December 0.417537E+11 31050267.32 0.00 38307366.85 21418587.51 0.00 0.594892E+11 0.00 1.81
                   
Annual Sum or Average 0.337552E+12 0.625859E+10 0.00 0.576012E+09 0.242283E+11 0.00 0.575737E+12 0.00 1.83
Minimum of Months 0.396000E+10 0.00 0.00 22227233.91 252469.85 0.00 0.307661E+11 0.00 1.81
Maximum of Months 0.608887E+11 0.363643E+10 0.00 74673125.46 0.100454E+11 0.00 0.664805E+11 0.00 1.88



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_1_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 9591654.22 2456508.33 3556.49 6986971.29 840180.78 0.530767E+09 0.130006E+10 4954.08 0.35
February 24063881.23 1584546.67 0.00 6545839.88 0.00 0.302183E+09 0.126258E+10 0.00 0.36
March 39518817.52 2800218.40 0.00 6777053.31 0.00 0.546120E+09 0.124583E+10 0.00 0.36
April 15054800.99 7068947.88 0.00 12280831.46 0.00 54899032.40 0.117280E+10 0.00 0.36
May 24805437.99 2668049.47 0.00 12938664.73 128353.55 41074850.72 0.119255E+10 0.00 0.36
June 8590317.60 43562559.20 0.00 13237647.03 269791.07 1809905.83 0.708219E+09 0.00 0.36
July 0.00 0.260843E+09 11489.29 11119439.28 0.00 734990.24 0.318254E+09 4045.12 0.36
August 0.00 0.339108E+09 37639.85 8644328.64 0.00 619817.72 0.239678E+09 10147.02 0.36
September 1614375.76 0.102920E+09 11844.14 11457406.58 3772446.33 2024934.77 0.539535E+09 3008.27 0.36
October 3640093.80 0.192002E+09 92960.40 9674335.30 0.00 2074122.84 0.851036E+09 11830.52 0.36
November 9486146.28 2651826.20 0.00 8671088.32 259950.12 0.119738E+09 0.141927E+10 0.00 0.35
December 11562969.57 4585814.36 13774.18 7731632.14 0.00 0.361598E+09 0.143108E+10 1556.21 0.35
                   
Annual Sum or Average 0.147928E+09 0.962252E+09 171264.34 0.116065E+09 5270721.84 0.196364E+10 0.116809E+11 35541.20 0.36
Minimum of Months 0.00 1584546.67 0.00 6545839.88 0.00 619817.72 0.239678E+09 0.00 0.35
Maximum of Months 39518817.52 0.339108E+09 92960.40 13237647.03 3772446.33 0.546120E+09 0.143108E+10 11830.52 0.36



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_2_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.124475E+09 1133750.22 18608.27 2886919.09 2144626.69 0.940539E+09 0.779287E+09 7827.24 0.35
February 0.108547E+09 573111.79 0.00 3447968.55 1011249.23 0.535949E+09 0.947240E+09 0.00 0.36
March 0.105449E+09 577507.21 0.00 4151072.51 2222383.10 0.722696E+09 0.100573E+10 0.00 0.36
April 0.158887E+09 4556869.23 0.00 8430598.41 2511250.42 64318553.07 0.102325E+10 0.00 0.36
May 0.225721E+09 2557072.55 0.00 10243709.36 239002.82 36766340.02 0.998484E+09 0.00 0.36
June 0.298115E+09 35014997.32 40946.54 9222237.10 8763044.05 1178028.08 0.423255E+09 8226.76 0.36
July 0.214009E+09 0.218276E+09 104666.89 6894913.19 42440084.20 163601.26 0.109003E+09 7581.71 0.36
August 0.170586E+09 0.280136E+09 85310.52 4583710.34 58888909.47 238253.98 73504770.17 5233.37 0.36
September 0.230850E+09 88141571.69 129911.55 6662138.95 18413609.04 1099199.21 0.315955E+09 9921.47 0.36
October 0.235642E+09 0.156445E+09 203694.77 4987718.89 35419413.15 1774586.74 0.623919E+09 16076.81 0.36
November 0.163288E+09 2249011.22 12599.17 4060891.17 646920.31 0.344462E+09 0.104517E+10 2904.46 0.35
December 0.139483E+09 3332610.65 43850.04 2987080.50 1211330.33 0.830593E+09 0.838699E+09 12814.64 0.35
                   
Annual Sum or Average 0.217505E+10 0.792994E+09 639587.75 68558958.05 0.173912E+09 0.347978E+10 0.818349E+10 70586.45 0.36
Minimum of Months 0.105449E+09 573111.79 0.00 2886919.09 239002.82 163601.26 73504770.17 0.00 0.35
Maximum of Months 0.298115E+09 0.280136E+09 203694.77 10243709.36 58888909.47 0.940539E+09 0.104517E+10 16076.81 0.36



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 98915629.49 999740.93 0.00 4362673.07 0.00 0.00 0.102176E+10 0.00 0.02
February 0.395865E+09 0.00 0.00 2614381.62 0.00 0.00 0.759550E+09 0.00 0.02
March 0.588558E+09 7500674.86 0.00 1904939.19 0.00 0.00 0.630637E+09 0.00 0.02
April 0.146785E+09 288357.43 0.00 2125214.88 0.00 0.00 0.661888E+09 0.00 0.02
May 0.665821E+09 0.00 0.00 450823.00 0.00 0.00 0.308045E+09 0.00 0.02
June 0.373810E+09 22078718.67 0.00 232574.53 559329.18 0.00 0.175283E+09 0.00 0.02
July 33178457.94 0.358784E+09 0.00 194304.03 1459769.80 0.00 0.102205E+09 0.00 0.02
August 0.00 0.537111E+09 0.00 245474.02 0.00 0.00 22671334.64 0.00 0.02
September 0.00 0.188751E+09 0.00 1562519.44 0.00 0.00 0.152150E+09 0.00 0.02
October 30206293.52 0.203162E+09 0.00 2699714.19 0.00 0.00 0.335983E+09 0.00 0.02
November 20821618.73 0.00 0.00 4000202.47 0.00 0.00 0.983225E+09 0.00 0.02
December 79848721.30 0.00 0.00 4600362.55 0.00 0.00 0.108581E+10 0.00 0.02
                   
Annual Sum or Average 0.243381E+10 0.131868E+10 0.00 24993183.00 2019098.99 0.00 0.623921E+10 0.00 0.02
Minimum of Months 0.00 0.00 0.00 194304.03 0.00 0.00 22671334.64 0.00 0.02
Maximum of Months 0.665821E+09 0.537111E+09 0.00 4600362.55 1459769.80 0.00 0.108581E+10 0.00 0.02



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.169040E+10 13143072.24 398344.02 57459603.32 31264661.54 0.170403E+09 0.231377E+11 21720.04 0.40
February 0.147386E+10 6520141.59 219789.79 59635694.86 14750901.50 0.106450E+09 0.199978E+11 73.89 0.40
March 0.144288E+10 7498231.41 325994.03 70370122.69 30145293.53 0.130247E+09 0.232883E+11 9313.45 0.40
April 0.218164E+10 41322919.61 406025.49 96989169.40 54114236.45 29759682.53 0.147133E+11 31621.32 0.40
May 0.314797E+10 13146931.69 185042.15 0.122506E+09 24594922.73 22815901.73 0.139500E+11 188.51 0.40
June 0.412098E+10 0.329784E+09 322402.29 0.116010E+09 0.264381E+09 6946563.31 0.568209E+10 3211.85 0.41
July 0.291110E+10 0.243877E+10 962755.86 84140149.90 0.109823E+10 1935335.39 0.148003E+10 10823.87 0.41
August 0.231390E+10 0.309819E+10 1098360.07 56290633.13 0.150060E+10 1498946.33 0.100467E+10 7214.56 0.41
September 0.316652E+10 0.947085E+09 477600.70 76132538.67 0.499651E+09 10794717.56 0.426892E+10 39844.45 0.41
October 0.321215E+10 0.178261E+10 2722200.46 66592059.02 0.820091E+09 16543232.46 0.845586E+10 91937.26 0.40
November 0.222891E+10 20409340.38 328556.57 64915816.13 18726834.08 73160193.39 0.187525E+11 27140.32 0.40
December 0.189152E+10 42917681.54 596896.60 56111729.77 18814858.99 0.113066E+09 0.225148E+11 75018.68 0.40
                   
Annual Sum or Average 0.297818E+11 0.874140E+10 8043968.03 0.927153E+09 0.437537E+10 0.683621E+09 0.157246E+12 318108.19 0.40
Minimum of Months 0.144288E+10 6520141.59 185042.15 56111729.77 14750901.50 1498946.33 0.100467E+10 73.89 0.40
Maximum of Months 0.412098E+10 0.309819E+10 2722200.46 0.122506E+09 0.150060E+10 0.170403E+09 0.232883E+11 91937.26 0.41



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_5_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 11529572.38 2465863.57 22488.69 8202199.97 811455.21 0.530918E+09 0.129675E+10 5392.20 0.35
February 26853816.66 1584546.67 0.00 6484868.24 0.00 0.362865E+09 0.119917E+10 0.00 0.36
March 41770004.17 2800218.40 0.00 6993555.19 0.00 0.580528E+09 0.120895E+10 0.00 0.36
April 10502231.78 7068947.88 0.00 11351498.66 0.00 52314195.23 0.118086E+10 0.00 0.36
May 19993925.02 2796403.01 0.00 11779307.31 0.00 72426616.29 0.116716E+10 0.00 0.36
June 8020855.80 43832350.27 0.00 11947212.11 0.00 2120914.30 0.709768E+09 0.00 0.36
July 0.00 0.260859E+09 0.00 10531218.20 0.00 399692.28 0.319178E+09 0.00 0.36
August 0.00 0.339155E+09 0.00 8631362.68 0.00 313159.96 0.239998E+09 0.00 0.36
September 1614375.76 0.102913E+09 0.00 10273612.42 3794706.14 1639565.76 0.541104E+09 0.00 0.36
October 3599895.74 0.190813E+09 0.00 9929719.91 1291946.58 2359011.73 0.850536E+09 1584.45 0.36
November 10517212.05 2555814.01 0.00 8930673.30 355962.31 0.168295E+09 0.136942E+10 0.00 0.35
December 14103352.34 4585814.36 11429.07 8441005.55 0.00 0.443315E+09 0.134611E+10 3901.32 0.35
                   
Annual Sum or Average 0.148505E+09 0.961431E+09 33917.75 0.113496E+09 6254070.23 0.221749E+10 0.114290E+11 10877.98 0.36
Minimum of Months 0.00 1584546.67 0.00 6484868.24 0.00 313159.96 0.239998E+09 0.00 0.35
Maximum of Months 41770004.17 0.339155E+09 22488.69 11947212.11 3794706.14 0.580528E+09 0.136942E+10 5392.20 0.36



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_6_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.124924E+09 981227.37 26909.07 3492906.06 2292274.75 0.855386E+09 0.863385E+09 4401.22 0.35
February 0.108656E+09 558309.58 10840.65 3368159.24 1011249.23 0.636986E+09 0.846174E+09 3961.56 0.36
March 0.105353E+09 970247.70 0.00 4409130.45 1829642.61 0.734250E+09 0.994016E+09 0.00 0.36
April 0.154688E+09 6415163.95 0.00 8219788.74 652955.70 81017297.15 0.101096E+10 0.00 0.36
May 0.221933E+09 2729197.05 0.00 9842282.65 66878.33 68583515.98 0.970856E+09 0.00 0.36
June 0.297198E+09 35248892.81 0.00 7991311.92 8578321.87 1263334.50 0.425318E+09 0.00 0.36
July 0.212559E+09 0.220435E+09 0.00 5936187.50 40393512.58 315596.08 0.111259E+09 0.00 0.36
August 0.170352E+09 0.283939E+09 0.00 3999454.39 55176334.34 311762.48 74249647.37 0.00 0.36
September 0.231145E+09 87224193.10 60087.81 5748976.82 19407571.73 1029168.02 0.316644E+09 3161.11 0.36
October 0.235494E+09 0.157795E+09 195847.00 5317805.51 34086874.99 3116871.12 0.622395E+09 6569.04 0.36
November 0.164358E+09 2047470.64 16491.12 4262840.25 842642.39 0.447501E+09 0.940858E+09 4831.01 0.35
December 0.139337E+09 3238163.21 32998.85 3302286.12 1324025.37 0.825965E+09 0.843158E+09 5418.23 0.35
                   
Annual Sum or Average 0.216600E+10 0.801582E+09 343174.49 65891129.64 0.165662E+09 0.365573E+10 0.801927E+10 28342.18 0.36
Minimum of Months 0.105353E+09 558309.58 0.00 3302286.12 66878.33 311762.48 74249647.37 0.00 0.35
Maximum of Months 0.297198E+09 0.283939E+09 195847.00 9842282.65 55176334.34 0.855386E+09 0.101096E+10 6569.04 0.36



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORRIDOR_FLR_3

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.313042E+11 0.00 0.00 0.00 45210810.70 0.00 0.00 0.00 0.60
February 0.280571E+11 0.00 0.00 0.00 8273603.57 0.00 0.00 0.00 0.60
March 0.321713E+11 0.00 0.00 0.00 77103.00 0.00 0.00 0.00 0.60
April 0.252264E+11 0.00 0.00 0.00 46392403.52 0.00 0.00 0.00 0.60
May 0.253654E+11 0.00 0.00 0.00 6619381.27 0.00 0.00 0.00 0.60
June 0.187592E+11 0.00 0.00 0.00 0.327646E+09 0.00 0.00 0.00 0.60
July 0.120581E+11 0.00 0.00 0.00 0.271051E+10 0.00 0.00 0.00 0.60
August 0.102355E+11 0.00 0.00 0.00 0.326033E+10 0.00 0.00 0.00 0.61
September 0.163536E+11 0.00 0.00 0.00 0.102933E+10 0.00 0.00 0.00 0.61
October 0.172901E+11 0.00 0.00 0.00 0.181741E+10 0.00 0.00 0.00 0.60
November 0.282637E+11 0.00 0.00 0.00 30130241.22 0.00 0.00 0.00 0.60
December 0.306755E+11 0.00 0.00 0.00 16023719.67 0.00 0.00 0.00 0.60
                   
Annual Sum or Average 0.275760E+12 0.00 0.00 0.00 0.929795E+10 0.00 0.00 0.00 0.60
Minimum of Months 0.102355E+11 0.00 0.00 0.00 77103.00 0.00 0.00 0.00 0.60
Maximum of Months 0.321713E+11 0.00 0.00 0.00 0.326033E+10 0.00 0.00 0.00 0.61



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_1_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 2274430.40 614127.08 910.13 1409536.69 210045.19 0.234090E+09 0.224077E+09 1217.51 0.35
February 6419419.29 396136.67 0.00 1344374.75 0.00 0.185138E+09 0.205941E+09 0.00 0.36
March 9507167.67 700054.60 0.00 1499115.66 0.00 0.224163E+09 0.224392E+09 0.00 0.36
April 3157560.90 1767236.97 0.00 2913800.06 0.00 50199331.23 0.257487E+09 0.00 0.36
May 5065714.70 699100.75 0.00 3078648.07 0.00 41176489.32 0.268520E+09 0.00 0.36
June 2033204.63 10955517.60 0.00 3168700.46 2569.97 3052126.28 0.174710E+09 0.00 0.36
July 0.00 65210832.33 3208.24 2690495.52 0.00 195384.33 79641329.89 675.37 0.36
August 0.00 84776914.66 10016.25 2033706.36 0.00 171453.33 60030402.58 1930.46 0.36
September 403593.94 26163686.42 2941.42 2617807.49 509443.98 468455.64 0.135168E+09 807.21 0.36
October 1419230.48 48000557.17 23137.63 2056620.79 0.00 24621695.53 0.188509E+09 3060.10 0.36
November 3147613.88 662956.55 0.00 1739113.85 64987.53 0.129119E+09 0.255284E+09 0.00 0.35
December 3172363.64 1146453.59 3466.65 1543510.50 0.00 0.219870E+09 0.228407E+09 365.95 0.35
                   
Annual Sum or Average 36600299.53 0.241094E+09 43680.33 26095430.21 787046.67 0.111227E+10 0.230217E+10 8056.59 0.36
Minimum of Months 0.00 396136.67 0.00 1344374.75 0.00 171453.33 60030402.58 0.00 0.35
Maximum of Months 9507167.67 84776914.66 23137.63 3168700.46 509443.98 0.234090E+09 0.268520E+09 3060.10 0.36



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_2_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 31113296.66 312214.00 4842.23 503884.64 507380.23 0.334559E+09 95620493.06 1766.65 0.35
February 27379694.61 143277.95 0.00 636220.76 252812.31 0.252952E+09 0.117828E+09 0.00 0.36
March 26334544.78 144376.80 0.00 865372.96 555595.77 0.266302E+09 0.166006E+09 0.00 0.36
April 39239260.94 1488329.42 0.00 1995391.87 278700.50 51680062.89 0.220806E+09 0.00 0.36
May 54967813.61 682299.26 0.00 2510386.73 16719.58 29737457.63 0.230588E+09 0.00 0.36
June 74357964.49 8801266.44 666.19 2345906.36 2154268.74 679767.67 0.105559E+09 602.29 0.36
July 53502277.86 54576755.87 19064.08 1799293.41 10610021.05 28284.24 27187684.96 1234.07 0.36
August 42646586.84 70039295.86 16267.97 1147013.30 14722227.37 67548.38 18367121.95 1135.92 0.36
September 57493504.92 22329831.98 31537.52 1522842.85 4309560.31 289501.83 79335893.42 2823.63 0.36
October 58959692.29 39209565.91 28838.19 968823.02 8779131.44 34259367.35 0.122393E+09 3592.31 0.36
November 40928715.66 562252.81 2911.49 684458.48 161730.08 0.204791E+09 0.142840E+09 964.42 0.35
December 34853017.11 825976.10 6583.68 500627.58 315387.27 0.314651E+09 0.102936E+09 2204.36 0.35
                   
Annual Sum or Average 0.541776E+09 0.199115E+09 110711.35 15480221.95 42663534.64 0.149000E+10 0.142947E+10 14323.66 0.36
Minimum of Months 26334544.78 143277.95 0.00 500627.58 16719.58 28284.24 18367121.95 0.00 0.35
Maximum of Months 74357964.49 70039295.86 31537.52 2510386.73 14722227.37 0.334559E+09 0.230588E+09 3592.31 0.36



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 8116256.74 5294886.00 12965.18 19603184.68 0.00 0.250074E+09 0.268936E+10 703.82 0.40
February 26960571.36 2544975.80 0.00 14195938.30 0.00 0.165451E+09 0.235575E+10 0.00 0.40
March 48240602.87 4497493.31 0.00 12732792.96 0.00 0.565855E+09 0.232562E+10 0.00 0.40
April 10834717.43 11353595.08 0.00 15708694.72 0.00 80256768.69 0.190893E+10 0.00 0.40
May 28628177.29 4491365.34 0.00 13162667.24 0.00 0.124162E+09 0.187601E+10 0.00 0.40
June 13754760.01 70102652.47 0.00 12978022.98 297464.32 4435628.14 0.114428E+10 0.00 0.40
July 0.00 0.418971E+09 0.00 11412578.85 0.00 1817212.91 0.516965E+09 0.00 0.40
August 0.00 0.544725E+09 0.00 10232112.12 0.00 1092770.60 0.388507E+09 0.00 0.41
September 2592884.96 0.166842E+09 0.00 15142953.53 4543619.46 3160236.71 0.869911E+09 0.00 0.41
October 1788220.56 0.308264E+09 20251.50 16208384.00 257828.61 5580026.67 0.136801E+10 5018.29 0.40
November 1970336.62 4676668.98 0.00 19591519.23 0.00 2990454.49 0.247644E+10 0.00 0.40
December 9322027.33 7390001.35 0.00 20634924.05 0.00 95653748.57 0.278464E+10 0.00 0.40
                   
Annual Sum or Average 0.152209E+09 0.154915E+10 33216.69 0.181604E+09 5098912.39 0.130053E+10 0.207044E+11 5722.11 0.40
Minimum of Months 0.00 2544975.80 0.00 10232112.12 0.00 1092770.60 0.388507E+09 0.00 0.40
Maximum of Months 48240602.87 0.544725E+09 20251.50 20634924.05 4543619.46 0.565855E+09 0.278464E+10 5018.29 0.41



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BANQUET_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.223845E+10 66355984.56 0.00 58177871.82 926423.05 0.00 0.491917E+11 0.00 4.59
February 0.982248E+09 11523001.18 0.00 56598933.88 789716.94 0.00 0.465888E+11 0.00 4.71
March 0.158428E+10 0.00 0.00 62794074.93 114744.14 0.00 0.522594E+11 0.00 4.68
April 0.301217E+09 67740756.94 0.00 77737016.53 1321400.35 0.00 0.449127E+11 0.00 4.89
May 0.186941E+09 9630981.65 0.00 85487267.79 219934.58 0.00 0.459142E+11 0.00 4.96
June 49130763.50 0.495959E+09 0.00 91132350.11 196288.69 0.00 0.356844E+11 0.00 5.13
July 4654141.19 0.419904E+10 0.00 82872748.13 9638780.25 0.00 0.238334E+11 0.00 5.21
August 28636216.76 0.494159E+10 0.00 72316059.14 37957110.11 0.00 0.204813E+11 0.00 5.21
September 0.130614E+09 0.159571E+10 0.00 78292517.44 16082918.32 0.00 0.305203E+11 0.00 5.09
October 0.123953E+09 0.278951E+10 0.00 71170851.71 20707963.67 0.00 0.320896E+11 0.00 5.05
November 0.651214E+09 45479324.32 0.00 63935725.38 51565.93 0.00 0.481604E+11 0.00 4.76
December 0.110244E+10 21613401.76 0.00 60563245.37 2232984.12 0.00 0.498803E+11 0.00 4.62
                   
Annual Sum or Average 0.738378E+10 0.142442E+11 0.00 0.861079E+09 90239830.14 0.00 0.479516E+12 0.00 4.91
Minimum of Months 4654141.19 0.00 0.00 56598933.88 51565.93 0.00 0.204813E+11 0.00 4.59
Maximum of Months 0.223845E+10 0.494159E+10 0.00 91132350.11 37957110.11 0.00 0.522594E+11 0.00 5.21



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DINING_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.109719E+10 70818377.19 0.00 74034765.80 0.00 0.00 0.545365E+11 0.00 4.95
February 0.162554E+09 12903402.37 0.00 71246362.17 8593.35 0.00 0.515550E+11 0.00 5.11
March 0.414296E+09 120328.90 0.00 79145742.97 0.00 0.00 0.579962E+11 0.00 5.06
April 5061627.90 72853733.38 0.00 93149252.45 0.00 0.00 0.491566E+11 0.00 5.30
May 2359719.33 10408319.76 0.00 0.101639E+09 0.00 0.00 0.501210E+11 0.00 5.37
June 0.00 0.526175E+09 0.00 0.104956E+09 0.00 0.00 0.386339E+11 0.00 5.54
July 0.00 0.452538E+10 0.00 92562799.33 0.00 0.00 0.255951E+11 0.00 5.60
August 0.00 0.532356E+10 0.00 80023597.17 0.00 0.00 0.219689E+11 0.00 5.58
September 2148153.83 0.172057E+10 0.00 89850214.71 0.00 0.00 0.330464E+11 0.00 5.48
October 20760031.36 0.299608E+10 0.00 81308990.54 1669419.04 0.00 0.347127E+11 0.00 5.43
November 95614798.54 48219914.34 0.00 79188188.69 0.00 0.00 0.528898E+11 0.00 5.14
December 0.317963E+09 24589962.94 0.00 76746276.95 417060.65 0.00 0.549177E+11 0.00 4.98
                   
Annual Sum or Average 0.211795E+10 0.153317E+11 0.00 0.102385E+10 2095073.05 0.00 0.525130E+12 0.00 5.30
Minimum of Months 0.00 120328.90 0.00 71246362.17 0.00 0.00 0.219689E+11 0.00 4.95
Maximum of Months 0.109719E+10 0.532356E+10 0.00 0.104956E+09 1669419.04 0.00 0.579962E+11 0.00 5.60



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: KITCHEN_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.128536E+09 0.00 0.125926E+09 0.00 0.00 0.697667E+11 0.00 21.69
February 0.00 23589400.13 0.00 0.113289E+09 0.00 0.00 0.644422E+11 0.00 22.01
March 17988514.34 219986.89 0.00 0.124888E+09 0.00 0.00 0.728999E+11 0.00 21.90
April 0.00 0.132304E+09 0.00 0.138578E+09 0.00 0.00 0.578176E+11 0.00 22.41
May 0.00 18853229.10 0.00 0.146816E+09 0.00 0.00 0.581578E+11 0.00 22.43
June 0.00 0.934010E+09 0.00 0.143370E+09 0.00 0.00 0.426656E+11 0.00 22.64
July 0.00 0.772838E+10 0.00 0.115488E+09 0.00 0.00 0.263041E+11 0.00 22.76
August 0.00 0.929686E+10 0.00 96376145.27 0.00 0.00 0.220056E+11 0.00 22.80
September 0.00 0.290405E+10 0.00 0.125187E+09 0.00 0.00 0.370316E+11 0.00 22.68
October 0.00 0.512048E+10 0.00 0.111867E+09 0.00 0.00 0.385972E+11 0.00 22.52
November 4383145.51 85664555.22 0.00 0.125054E+09 0.00 0.00 0.647077E+11 0.00 22.15
December 8921803.90 45621893.39 0.00 0.127052E+09 0.00 0.00 0.688947E+11 0.00 21.82
                   
Annual Sum or Average 31293463.75 0.264186E+11 0.00 0.149389E+10 0.00 0.00 0.623291E+12 0.00 22.32
Minimum of Months 0.00 219986.89 0.00 96376145.27 0.00 0.00 0.220056E+11 0.00 21.69
Maximum of Months 17988514.34 0.929686E+10 0.00 0.146816E+09 0.00 0.00 0.728999E+11 0.00 22.80



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORRIDOR_FLR_6

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.154875E+11 0.00 0.00 0.00 22367693.73 0.00 0.00 0.00 1.11
February 0.138810E+11 0.00 0.00 0.00 4093300.43 0.00 0.00 0.00 1.12
March 0.159165E+11 0.00 0.00 0.00 38146.10 0.00 0.00 0.00 1.12
April 0.124806E+11 0.00 0.00 0.00 22952277.51 0.00 0.00 0.00 1.12
May 0.125493E+11 0.00 0.00 0.00 3274886.93 0.00 0.00 0.00 1.12
June 0.928097E+10 0.00 0.00 0.00 0.162100E+09 0.00 0.00 0.00 1.13
July 0.596564E+10 26828706.04 0.00 0.00 0.131417E+10 0.00 0.00 0.00 1.13
August 0.506383E+10 0.134727E+09 0.00 384.89 0.147829E+10 0.00 95750.14 0.00 1.13
September 0.807072E+10 0.172589E+09 0.00 30495.21 0.342627E+09 0.00 20089513.88 0.00 1.13
October 0.844365E+10 0.364757E+09 0.00 59457.16 0.538663E+09 0.00 0.110438E+09 0.00 1.13
November 0.139832E+11 0.00 0.00 0.00 14906700.35 0.00 0.00 0.00 1.12
December 0.151765E+11 0.00 0.00 0.00 7927609.53 0.00 0.00 0.00 1.11
                   
Annual Sum or Average 0.136299E+12 0.698902E+09 0.00 90337.26 0.391142E+10 0.00 0.130623E+09 0.00 1.12
Minimum of Months 0.506383E+10 0.00 0.00 0.00 38146.10 0.00 0.00 0.00 1.11
Maximum of Months 0.159165E+11 0.364757E+09 0.00 59457.16 0.147829E+10 0.00 0.110438E+09 0.00 1.13



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2024-07-03 12:21:51

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.160043E+12 0.433629E+10 0.124845E+12 0.505820E+12 0.222773E+12
February 0.209135E+12 0.385413E+10 0.115929E+12 0.457796E+12 0.165091E+12
March 0.298193E+12 0.435765E+10 0.132145E+12 0.522121E+12 0.181512E+12
April 0.387434E+12 0.357011E+10 0.102098E+12 0.412668E+12 0.241922E+12
May 0.415826E+12 0.382282E+10 0.103352E+12 0.417584E+12 0.239918E+12
June 0.410269E+12 0.289451E+10 0.757646E+11 0.300525E+12 0.339133E+12
July 0.434648E+12 0.121288E+10 0.357631E+11 0.147059E+12 0.604429E+12
August 0.394824E+12 0.792095E+09 0.254933E+11 0.107892E+12 0.671329E+12
September 0.310478E+12 0.227027E+10 0.613739E+11 0.245468E+12 0.444261E+12
October 0.211444E+12 0.239624E+10 0.587486E+11 0.256195E+12 0.501902E+12
November 0.176530E+12 0.398221E+10 0.112008E+12 0.463420E+12 0.222643E+12
December 0.140259E+12 0.435126E+10 0.121752E+12 0.499380E+12 0.241520E+12
           
Annual Sum or Average 0.354909E+13 0.378405E+11 0.106927E+13 0.433593E+13 0.407643E+13
Minimum of Months 0.140259E+12 0.792095E+09 0.254933E+11 0.107892E+12 0.165091E+12
Maximum of Months 0.434648E+12 0.435765E+10 0.132145E+12 0.522121E+12 0.671329E+12