Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190
Simulation Timestamp: 2024-07-03 12:21:21
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 10751.07 | 947.62 | 947.62 |
Net Site Energy | 10751.07 | 947.62 | 947.62 |
Total Source Energy | 25214.50 | 2222.46 | 2222.46 |
Net Source Energy | 25214.50 | 2222.46 | 2222.46 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 765.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1440.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 783.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 194.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1658.18 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 813.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 451.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 94.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 152.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 94.80 | 2452.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | 61.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 6510.00 | 4241.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 765.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 1440.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 783.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 194.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 872.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 14.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 8.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 21.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 789.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 2.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 451.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 94.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 152.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 94.80 | 2452.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5742.51 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.69 | |
Refrigeration | General | 7.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 20.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 34.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 765.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 1440.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 783.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 194.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 1658.18 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 813.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 451.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 94.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 152.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 94.80 | 2452.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | Unassigned | 61.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 86.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 250.94 | 216.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 236.72 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 573.81 | 373.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 86.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 250.94 | 216.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 236.72 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 573.81 | 373.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 6510.002 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 6510.002 | 100.00 |
Total On-Site and Utility Electric Sources | 6510.002 | 100.00 |
Total Electricity End Uses | 6510.002 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 1102.65 | 61.95 |
Air to Air Heat Recovery for Heating | 677.20 | 38.05 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 1779.85 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9857.19 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9857.19 | 100.00 |
Total Water End Uses | 9857.19 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 5.83 |
Time Setpoint Not Met During Occupied Cooling | 47.83 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 7619.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER1 |DXReportMonthly
| FLR_3_DOAS COOLING COIL | VAV WITH REHEAT COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH LAUNDRY G WATER HEATER | SWH BOOSTER E WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |CoilReportMonthly
| FLR_3_DOAS HEATING COIL | VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | FLR_3_DOAS COOLING COIL | VAV WITH REHEAT COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |PlantLoopDemandReportMonthly
| COOLSYS1 | SWHSYS1 |FanReportMonthly
| FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL_FANCOILFAN | ROOM_2_FLR_3 FAN COIL_FANCOILFAN | ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | ROOM_5_FLR_3 FAN COIL_FANCOILFAN | ROOM_6_FLR_3 FAN COIL_FANCOILFAN | ROOM_1_FLR_6 FAN COIL_FANCOILFAN | ROOM_2_FLR_6 FAN COIL_FANCOILFAN | ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN |PumpReportMonthly
| COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| COOLSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| FLR_3_DOAS | VAV WITH REHEAT |AirLoopSystemComponentLoadsMonthly
| FLR_3_DOAS | VAV WITH REHEAT |AirLoopSystemComponentEnergyUseMonthly
| FLR_3_DOAS | VAV WITH REHEAT |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21 |
RunPeriod | RUNPERIOD 1 |
Weather File | Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 |
Latitude [deg] | 33.63 |
Longitude [deg] | -84.4 |
Elevation [m] | 308.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 8.8143 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.26 | 23.26 | 11.3140 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 11.3140 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 4.6285 | 61.93 | 5.3800 |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 5.7199 | 46.45 | 2.6900 |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 4.6285 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.50 | 65.50 | 10.0104 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.08 | 85.08 | 10.7639 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 8.2882 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 8.2882 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 7.1042 | 18.58 | 0.0000 |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.74 | 6.74 | 8.2882 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 10.0104 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 10.0104 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.37 | 26.37 | 11.4097 | 4.65 | 2934.4875 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.20 | 28.20 | 7.1042 | 18.58 | 0.0000 |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 8.5566 | 7.07 | 41.0709 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 8.5566 | 7.07 | 41.0709 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 1978.83 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 8.8143 | 18.58 | 5.3800 | |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 1.00 | RETAIL_1_FLR_1 | GENERAL | RETAIL_1_FLR_1 | 11.3140 | 6.19 | 10.7600 | |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 1.00 | RETAIL_2_FLR_1 | GENERAL | RETAIL_2_FLR_1 | 11.3140 | 6.19 | 10.7600 | |
MECH_FLR_1 | 164.24 | Yes | Yes | 1.00 | MECH_FLR_1 | GENERAL | MECH_FLR_1 | 4.6285 | 61.93 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 1.00 | STORAGE_FLR_1 | GENERAL | STORAGE_FLR_1 | 5.7199 | 46.45 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 1.00 | LAUNDRY_FLR_1 | GENERAL | LAUNDRY_FLR_1 | 4.6285 | 9.29 | 597.5300 | |
CAFE_FLR_1 | 188.86 | Yes | Yes | 1.00 | CAFE_FLR_1 | GENERAL | CAFE_FLR_1 | 10.0104 | 1.33 | 5.3800 | |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 1.00 | LOBBY_FLR_1 | GENERAL | LOBBY_FLR_1 | 10.7639 | 3.10 | 8.0700 | |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_1_FLR_3 | GENERAL | ROOM_1_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_2_FLR_3 | GENERAL | ROOM_2_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 76.00 | ROOM_3_MULT19_FLR_3 | GENERAL | ROOM_3_MULT19_FLR_3 | 8.2882 | 16.35 | 10.5200 | |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 76.00 | ROOM_4_MULT19_FLR_3 | GENERAL | ROOM_4_MULT19_FLR_3 | 8.2882 | 16.35 | 10.5200 | |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_5_FLR_3 | GENERAL | ROOM_5_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_6_FLR_3 | GENERAL | ROOM_6_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 4.00 | CORRIDOR_FLR_3 | GENERAL | CORRIDOR_FLR_3 | 7.1042 | 18.58 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_1_FLR_6 | GENERAL | ROOM_1_FLR_6 | 8.2882 | 26.01 | 6.7500 | |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_2_FLR_6 | GENERAL | ROOM_2_FLR_6 | 8.2882 | 26.01 | 6.7500 | |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 9.00 | ROOM_3_MULT9_FLR_6 | GENERAL | ROOM_3_MULT9_FLR_6 | 8.2882 | 16.35 | 10.5200 | |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1.00 | BANQUET_FLR_6 | GENERAL | BANQUET_FLR_6 | 10.0104 | 1.33 | 67.8200 | |
DINING_FLR_6 | 331.66 | Yes | Yes | 1.00 | DINING_FLR_6 | GENERAL | DINING_FLR_6 | 10.0104 | 1.33 | 67.8200 | |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 1.00 | KITCHEN_FLR_6 | GENERAL | KITCHEN_FLR_6 | 11.4097 | 4.65 | 2934.4875 | |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1.00 | CORRIDOR_FLR_6 | GENERAL | CORRIDOR_FLR_6 | 7.1042 | 18.58 | 0.0000 | |
Total | 11345.29 | 8.5566 | 3.54 | 41.0709 | |||||||
Conditioned Total | 11345.29 | 8.5566 | 3.54 | 41.0709 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 11345.29 | 11345.29 | 0.00 | 0.00 | 4.6520 | 8.82 | 37.1989 |
Total | 11345.29 | 11345.29 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 03-JAN-07:40 | 03-FEB-18:19 | - | - | - | - | - | - | - | - | - | - | 29-MAR-20:19 |
Heating | 186734.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2631.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 36001.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 12338.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89171.45 | 104248.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 49607.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 15377.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2515.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 1521.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 4751.04 | 238177.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 3213.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 403863.18 | 342425.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 186734.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 2631.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 36001.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 12338.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 59188.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 29272.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1290.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 48128.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 188.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 15377.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 2515.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 1521.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 4751.04 | 238177.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 191.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 1889.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1132.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 2424.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 4562.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2480.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 614.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5251.45 | 1939.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2577.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1431.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 298.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 482.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 300.22 | 2658.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 194.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 20617.18 | 4597.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 213.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 402.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 218.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 54.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 462.88 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 227.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 126.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 26.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 42.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 26.46 | 234.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1817.25 | 405.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 213.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 402.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 218.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 54.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 462.88 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 227.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 126.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 26.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 42.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 26.46 | 234.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1817.25 | 405.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
BASEMENT VAV BOX COMPONENT | 2.53 | 0.595480 | 0.529000 | 1.34 | 1.00 | 0.500000 | 0.000640 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.311595 | 0.164022 | 0.529000 | 0.164834 | 0.529000 | 0.500000 | 0.002323 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.237002 | 0.249718 | 0.529000 | 0.125374 | 0.665914 | 0.500000 | 0.001526 |
MECH_FLR_1 VAV BOX COMPONENT | 0.201443 | 0.621283 | 0.529000 | 0.106563 | 1.00 | 0.500000 | 0.000613 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.120097 | 0.601235 | 0.529000 | 0.063531 | 1.00 | 0.500000 | 0.000634 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 3.37 | 0.017637 | 0.529000 | 1.78 | 0.529000 | 0.500000 | 0.021602 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.38 | 0.104337 | 0.529000 | 0.729654 | 0.529000 | 0.500000 | 0.003652 |
LOBBY_FLR_1 VAV BOX COMPONENT | 4.78 | 0.208505 | 0.529000 | 2.53 | 0.556012 | 0.500000 | 0.001827 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.50 | 0.793578 | 0.529000 | 0.791193 | 1.00 | 0.500000 | 0.000480 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.23 | 0.113551 | 0.529000 | 1.18 | 0.529000 | 0.500000 | 0.003355 |
DINING_FLR_6 VAV BOX COMPONENT | 2.33 | 0.108358 | 0.529000 | 1.23 | 0.529000 | 0.500000 | 0.003516 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.31 | 0.061345 | 0.529000 | 1.22 | 0.529000 | 0.500000 | 0.011171 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 0.755991 | 0.415400 | 0.529000 | 0.399919 | 1.00 | 0.500000 | 0.000917 |
Design Size Nominal Capacity [W] | |
BASEMENT VAV BOX REHEAT COIL | 36949.54 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 4546.76 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 3458.32 |
MECH_FLR_1 VAV BOX REHEAT COIL | 2939.44 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 1752.45 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 49198.70 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 20126.76 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 69762.38 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | 5842.73 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | 5855.20 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 33672.04 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 33918.13 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | 5817.25 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | 5829.72 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 21824.24 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | 1793.86 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | 1798.79 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 8595.94 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 32476.32 |
DINING_FLR_6 VAV BOX REHEAT COIL | 34032.62 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 33678.13 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 11031.36 |
FLR_3_DOAS HEATING COIL | 16512.40 |
VAV WITH REHEAT HEATING COIL | 176488.48 |
Design Size Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 0.061735 |
ROOM_2_FLR_3 DIRECT AIR | 0.061728 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 0.837072 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 0.837300 |
ROOM_5_FLR_3 DIRECT AIR | 0.061735 |
ROOM_6_FLR_3 DIRECT AIR | 0.061728 |
ROOM_1_FLR_6 DIRECT AIR | 0.015434 |
ROOM_2_FLR_6 DIRECT AIR | 0.015432 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 0.099154 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 1.01 | 0.000315 |
ROOM_2_FLR_3 FAN COIL | 0.994555 | 0.000311 |
ROOM_3_MULT19_FLR_3 FAN COIL | 6.05 | 0.001852 |
ROOM_4_MULT19_FLR_3 FAN COIL | 6.40 | 0.002080 |
ROOM_5_FLR_3 FAN COIL | 0.911211 | 0.000286 |
ROOM_6_FLR_3 FAN COIL | 0.903670 | 0.000284 |
ROOM_1_FLR_6 FAN COIL | 0.264190 | 0.000083 |
ROOM_2_FLR_6 FAN COIL | 0.261102 | 0.000082 |
ROOM_3_MULT9_FLR_6 FAN COIL | 1.19 | 0.000380 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COIL_FANCOILFAN | 1.01 |
ROOM_2_FLR_3 FAN COIL_FANCOILFAN | 0.994555 |
ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | 6.05 |
ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | 6.40 |
ROOM_5_FLR_3 FAN COIL_FANCOILFAN | 0.911211 |
ROOM_6_FLR_3 FAN COIL_FANCOILFAN | 0.903670 |
ROOM_1_FLR_6 FAN COIL_FANCOILFAN | 0.264190 |
ROOM_2_FLR_6 FAN COIL_FANCOILFAN | 0.261102 |
ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN | 1.19 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Coil Load [W] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008632 | 12.80 | 0.008500 | 0.000315 | 1.01 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008633 | 12.80 | 0.008500 | 0.000311 | 0.994555 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008549 | 12.80 | 0.008500 | 0.001852 | 6.05 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008773 | 12.80 | 0.008500 | 0.002080 | 6.40 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008646 | 12.80 | 0.008500 | 0.000286 | 0.911211 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008647 | 12.80 | 0.008500 | 0.000284 | 0.903670 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008625 | 12.80 | 0.008500 | 0.000083 | 0.264190 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008627 | 12.80 | 0.008500 | 0.000082 | 0.261102 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008698 | 12.80 | 0.008500 | 0.000380 | 1.19 | |
FLR_3_DOAS COOLING COIL | 34.40 | 6.70 | 0.014473 | 11.91 | 0.008500 | 0.002607 | 2.05 | 91161.11 |
VAV WITH REHEAT COOLING COIL | 29.53 | 6.70 | 0.012239 | 10.92 | 0.008500 | 0.020780 | 21.92 | 726568.33 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
VAV WITH REHEAT | 11.67 | 11.67 | 22.05 | 11.67 | 21.92 | 21.92 | 0.300000 | 0.532059 | 21.92 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
VAV WITH REHEAT_OA_CONTROLLER | 21.92 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
FLR_3_DOAS OA HEAT RECOVERY | 2.05 |
VAV WITH REHEAT OA HEAT RECOVERY | 11.66 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS FAN | 2.05 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.002607 | 0.000183 |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.020780 | 0.000023 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT FAN | 21.92 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP SECONDARY | 0.029059 | 4744.44 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1 | 0.029059 | 3.49 |
SWHSYS1 | 0.000375 | 0.045004 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.029059 | 3284.74 |
SWHSYS1 PUMP | 0.000375 | 47.91 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.029059 | 1016052.10 | 1016659.59 | 115.90 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000375 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 11.90 | 7.70 | 4.00 | 7.90 | 13.80 | 17.20 | 20.80 | 24.80 | 26.10 | 26.50 | 22.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 | 33.63 | -84.43 | -5.00 | 308.00 | 97679 | 1.1610 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 16.60 | 22.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.58 | 23.26 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.72 | 65.50 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.80 | 85.08 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.70 | 6.74 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.96 | 26.37 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.27 | 28.20 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 8.814 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 14.194 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 11.314 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 22.074 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 11.314 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 22.074 | No |
4 | MECH_FLR_1 | 164.24 | 2.7 | 61.932 | 1.615E-002 | 4.628 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 10.008 | No |
5 | STORAGE_FLR_1 | 94.76 | 2.0 | 46.451 | 2.153E-002 | 5.720 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 8.410 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 4.628 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 602.158 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 10.010 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 15.390 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 10.764 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.834 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 8.288 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 18.808 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 8.288 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 18.808 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 21.0 | 18.581 | 5.382E-002 | 7.104 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.104 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 8.288 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 18.808 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 10.010 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 77.830 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 10.010 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 77.830 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 11.410 | 515.227 | 2419.260 | 0.000 | 0.000 | 0.000 | 2945.897 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 22.2 | 18.581 | 5.382E-002 | 7.104 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.104 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | STORAGE_FLR_1 PEOPLE | BLDG_OCC_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.0 | 2.153E-002 | 46.451 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | CORRIDOR_FLR_3 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 21.0 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 21 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
21 | CORRIDOR_FLR_6 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 22.2 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
22 | MECH_FLR_1 PEOPLE | BLDG_OCC_SCH | MECH_FLR_1 | 164.24 | 2.7 | 2.7 | 1.615E-002 | 61.932 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 3 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_BASEMENT | BASEMENT | 1978.83 | 106.5 | 17441.963 | 8.814 | 163.776 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 17441.963 |
2 | RETAIL_1_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_1_FLR_1 | 67.07 | 10.8 | 758.849 | 11.314 | 70.076 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 758.849 |
3 | RETAIL_2_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_2_FLR_1 | 77.67 | 12.5 | 878.750 | 11.314 | 70.076 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 878.750 |
4 | MECH_FLR_1_LIGHTS | LTG_SCH_MECHANIC | MECH_FLR_1 | 164.24 | 2.7 | 760.196 | 4.628 | 286.650 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 760.196 |
5 | STORAGE_FLR_1_LIGHTS | LTG_SCH_STORAGE | STORAGE_FLR_1 | 94.76 | 2.0 | 542.017 | 5.720 | 265.695 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 542.017 |
6 | LAUNDRY_FLR_1_LIGHTS | LTG_SCH_LAUNDRY | LAUNDRY_FLR_1 | 78.04 | 8.4 | 361.204 | 4.628 | 43.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 361.204 |
7 | CAFE_FLR_1_LIGHTS | LTG_SCH_DINING | CAFE_FLR_1 | 188.86 | 142.3 | 1890.589 | 10.010 | 13.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1890.589 |
8 | LOBBY_FLR_1_LIGHTS | LTG_SCH_LOBBY | LOBBY_FLR_1 | 1308.19 | 422.4 | 14081.185 | 10.764 | 33.333 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14081.185 |
9 | ROOM_1_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_3 | 39.02 | 1.5 | 323.422 | 8.288 | 215.615 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.422 |
10 | ROOM_2_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_3 | 39.02 | 1.5 | 323.384 | 8.288 | 215.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.384 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 203.259 | 8.288 | 135.506 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 203.259 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 203.314 | 8.288 | 135.543 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 203.314 |
13 | ROOM_5_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_5_FLR_3 | 39.02 | 1.5 | 323.422 | 8.288 | 215.615 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.422 |
14 | ROOM_6_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_6_FLR_3 | 39.02 | 1.5 | 323.384 | 8.288 | 215.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.384 |
15 | CORRIDOR_FLR_3_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2766.397 | 7.104 | 132.003 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2766.397 |
16 | ROOM_1_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_6 | 39.02 | 1.5 | 323.422 | 8.288 | 215.615 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.422 |
17 | ROOM_2_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_6 | 39.02 | 1.5 | 323.384 | 8.288 | 215.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.384 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 203.314 | 8.288 | 135.543 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 203.314 |
19 | BANQUET_FLR_6_LIGHTS | LTG_SCH_DINING | BANQUET_FLR_6 | 331.66 | 249.9 | 3320.034 | 10.010 | 13.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3320.034 |
20 | DINING_FLR_6_LIGHTS | LTG_SCH_DINING | DINING_FLR_6 | 331.66 | 249.9 | 3320.034 | 10.010 | 13.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3320.034 |
21 | KITCHEN_FLR_6_LIGHTS | LTG_SCH_KITCHEN | KITCHEN_FLR_6 | 103.30 | 22.2 | 1178.676 | 11.410 | 53.003 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1178.676 |
22 | CORRIDOR_FLR_6_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_6 | 412.12 | 22.2 | 2927.804 | 7.104 | 132.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2927.804 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 2.7 | 883.628 | 5.380 | 333.193 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 254.902 | 2.690 | 124.952 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 457.500 | 4.429 | 20.573 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 457.500 | 457.500 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 285.000 | 2.759 | 12.816 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 285.000 | 285.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 2.390 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
6 | RES_ROOF | 19 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
7 | NONRES_EXT_WALL_GRD | 21 | 3 | 9 | 0.167 | 0.9589 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | NONRES_EXT_WALL_MID | 22 | 3 | 9 | 0.167 | 1.167 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | NONRES_EXT_WALL_TOP | 23 | 3 | 9 | 0.167 | 1.181 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | RES_EXT_WALL_MID | 25 | 3 | 9 | 0.167 | 1.021 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | RES_EXT_WALL_TOP | 26 | 3 | 9 | 0.167 | 1.034 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | NONRES_FLOOR | 30 | 3 | 7 | 0.167 | 0.3181 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
13 | NONRES_FLOOR_CEILING | 33 | 3 | 7 | 0.167 | 0.3181 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
14 | BASEMENT_FLOOR | 36 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
15 | BASEMENT_WALL_NORTH_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | BASEMENT_WALL_EAST_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | BASEMENT_WALL_SOUTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
18 | BASEMENT_WALL_WEST_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4184 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
10 | RES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
11 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
12 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8756 |
14 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6894 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6793 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | RES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8120 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
25 | RES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7993 |
26 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
27 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.883 |
28 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
29 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
30 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
31 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
32 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.883 |
33 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
34 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
35 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
39 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
40 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
41 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
42 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 2.3900722 | 2.3900722 | 2.3900722 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
21 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
22 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
23 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
24 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
25 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
26 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
27 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
28 | 9 | -0.56372661E-17 | 0.35603042E-16 | -0.14834456E-09 | -0.22354951E-17 |
29 | 8 | 0.21681598E-07 | 0.12895413E-12 | 0.37576420E-03 | -0.24652724E-09 |
30 | 7 | -0.12181032E-01 | 0.67087143E-08 | -0.22998674E-01 | 0.13850277E-03 |
31 | 6 | 0.40370585 | 0.23395349E-05 | 0.47069069 | -0.47283774E-02 |
32 | 5 | -5.1745154 | 0.87537405E-04 | -4.4305073 | 0.62984858E-01 |
33 | 4 | 32.931872 | 0.71743813E-03 | 21.398312 | -0.42118042 |
34 | 3 | -111.07522 | 0.15662534E-02 | -55.540939 | 1.5130129 |
35 | 2 | 196.98158 | 0.88235367E-03 | 77.798628 | -2.8983416 |
36 | 1 | -171.10930 | 0.94326468E-04 | -55.232514 | 2.7446195 |
37 | 0 | 57.057407 | 0.53780718E-06 | 15.562302 | |
38 | 9 | 0.13788181E-14 | 0.42316407E-16 | -0.13850765E-09 | -0.36591458E-17 |
39 | 8 | 0.20295421E-07 | 0.15509090E-12 | 0.36099725E-03 | -0.23076592E-09 |
40 | 7 | -0.11739701E-01 | 0.81955471E-08 | -0.22363010E-01 | 0.13348467E-03 |
41 | 6 | 0.39171309 | 0.28760220E-05 | 0.46045976 | -0.45870120E-02 |
42 | 5 | -5.0574682 | 0.10819265E-03 | -4.3518524 | 0.61533536E-01 |
43 | 4 | 32.414067 | 0.89103805E-03 | 21.090697 | -0.41430552 |
44 | 3 | -109.97331 | 0.19536482E-02 | -54.932704 | 1.4970936 |
45 | 2 | 195.88922 | 0.11048200E-02 | 77.241099 | -2.8809953 |
46 | 1 | -170.70571 | 0.11852782E-03 | -55.070977 | 2.7375462 |
47 | 0 | 57.057407 | 0.67841551E-06 | 15.589460 | |
48 | 9 | 0.13857471E-14 | 0.43057560E-16 | -0.13784678E-09 | -0.68945926E-17 |
49 | 8 | 0.20202246E-07 | 0.15680163E-12 | 0.35999259E-03 | -0.22970649E-09 |
50 | 7 | -0.11709634E-01 | 0.82948599E-08 | -0.22319691E-01 | 0.13314280E-03 |
51 | 6 | 0.39089600 | 0.29121450E-05 | 0.45976168 | -0.45773805E-02 |
52 | 5 | -5.0494928 | 0.10959277E-03 | -4.3464810 | 0.61434646E-01 |
53 | 4 | 32.378781 | 0.90287364E-03 | 21.069680 | -0.41383702 |
54 | 3 | -109.89821 | 0.19801908E-02 | -54.891143 | 1.4960086 |
55 | 2 | 195.81476 | 0.11201274E-02 | 77.203021 | -2.8798128 |
56 | 1 | -170.67819 | 0.12019965E-03 | -55.059979 | 2.7370639 |
57 | 0 | 57.057407 | 0.68811227E-06 | 15.591337 | |
58 | 9 | 0.14302076E-15 | 0.35792568E-16 | -0.14541430E-09 | -0.27421543E-17 |
59 | 8 | 0.21269444E-07 | 0.13686051E-12 | 0.37140784E-03 | -0.24184090E-09 |
60 | 7 | -0.12050952E-01 | 0.71525680E-08 | -0.22811354E-01 | 0.13702371E-03 |
61 | 6 | 0.40017121 | 0.24988627E-05 | 0.46767819 | -0.46867126E-02 |
62 | 5 | -5.1400200 | 0.93645327E-04 | -4.4073602 | 0.62557131E-01 |
63 | 4 | 32.779281 | 0.76858103E-03 | 21.307814 | -0.41915444 |
64 | 3 | -110.75053 | 0.16800125E-02 | -55.362013 | 1.5083221 |
65 | 2 | 196.65975 | 0.94749847E-03 | 77.634567 | -2.8932310 |
66 | 1 | -170.99041 | 0.10139533E-03 | -55.184883 | 2.7425359 |
67 | 0 | 57.057407 | 0.57877233E-06 | 15.570231 | |
68 | 9 | 0.33566835E-16 | 0.35384250E-16 | -0.14478218E-09 | -0.87565041E-18 |
69 | 8 | 0.21180494E-07 | 0.13854999E-12 | 0.37046393E-03 | -0.24082951E-09 |
70 | 7 | -0.12022754E-01 | 0.72481687E-08 | -0.22770744E-01 | 0.13670309E-03 |
71 | 6 | 0.39940498 | 0.25332696E-05 | 0.46702484 | -0.46776806E-02 |
72 | 5 | -5.1325420 | 0.94967185E-04 | -4.4023386 | 0.62464408E-01 |
73 | 4 | 32.746200 | 0.77967008E-03 | 21.288178 | -0.41871522 |
74 | 3 | -110.68014 | 0.17047184E-02 | -55.323188 | 1.5073051 |
75 | 2 | 196.58997 | 0.96166638E-03 | 77.598974 | -2.8921229 |
76 | 1 | -170.96463 | 0.10293464E-03 | -55.174560 | 2.7420841 |
77 | 0 | 57.057407 | 0.58770932E-06 | 15.571958 | |
78 | 7 | -0.11407965E-14 | 0.23474115E-16 | -0.22119674E-13 | 0.51962024E-15 |
79 | 6 | 0.16676876E-10 | 0.39440661E-11 | 0.52102403E-09 | -0.18553030E-10 |
80 | 5 | -0.80001662E-07 | 0.19215958E-07 | -0.21848785E-05 | 0.17095694E-06 |
81 | 4 | 0.10228101E-03 | 0.72538432E-05 | 0.17630655E-02 | -0.28160064E-03 |
82 | 3 | -0.15120274E-01 | 0.25611913E-03 | -0.21515117 | 0.43248511E-01 |
83 | 2 | 0.21482172 | 0.11124906E-02 | 2.8969963 | -0.61829830 |
84 | 1 | -0.54366453 | 0.69706713E-03 | -7.1337069 | 1.5687761 |
85 | 0 | 0.34594624 | 0.12518961E-04 | 4.4521846 | |
86 | 7 | -0.22119674E-13 | 0.23474115E-16 | -0.11407965E-14 | 0.51962024E-15 |
87 | 6 | 0.52102403E-09 | 0.39440661E-11 | 0.16676876E-10 | -0.18553030E-10 |
88 | 5 | -0.21848785E-05 | 0.19215958E-07 | -0.80001662E-07 | 0.17095694E-06 |
89 | 4 | 0.17630655E-02 | 0.72538432E-05 | 0.10228101E-03 | -0.28160064E-03 |
90 | 3 | -0.21515117 | 0.25611913E-03 | -0.15120274E-01 | 0.43248511E-01 |
91 | 2 | 2.8969963 | 0.11124906E-02 | 0.21482172 | -0.61829830 |
92 | 1 | -7.1337069 | 0.69706713E-03 | -0.54366453 | 1.5687761 |
93 | 0 | 4.4521846 | 0.12518961E-04 | 0.34594624 | |
94 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
95 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
96 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
97 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
98 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
99 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
100 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
101 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
102 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
103 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
104 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
105 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
106 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
107 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
108 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
109 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
110 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
111 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
112 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
113 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
114 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
115 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
116 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
117 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
118 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
119 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
120 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
121 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
122 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
123 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
124 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
125 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
126 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
127 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
128 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
129 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
130 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
131 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
132 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
133 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.45_SHGC_0.25 | 37 | 1 | VerySmooth | 2.557 | 2.557 | 1.000 | 0.251 | ||
2 | RESWINDOW_U_0.487_SHGC_0.25 | 38 | 1 | VerySmooth | 2.769 | 2.769 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 2.66719E-002 | 0.16139 | 0.61727 | 0.61727 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.12129 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 2.17016E-002 | 0.16139 | 0.61276 | 0.61276 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.11379 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | CAFE_FLR_1 | 1 | 0 |
2 | LOBBY_FLR_1 | 1 | 0 |
3 | BANQUET_FLR_6 | 1 | 0 |
4 | DINING_FLR_6 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | CAFE_FLR_1 | 0 | |
2 | LOBBY_FLR_1 | 0 | |
3 | BANQUET_FLR_6 | 0 | |
4 | DINING_FLR_6 | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH LAUNDRY G WATER HEATER | 1.1356 | 163316.0 | 11.511 | 0.4388 |
2 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.219 | 1.1187 |
3 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 2.2712 | 175842.6 | 5.775 | 0.3748 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 1.764E-002 | 2.631E-004 | 1.298E-004 | 0.239 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.811E-003 | 8.769E-005 | 2.388E-004 | 7.967E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 2.7 | 1.610E-002 | 9.800E-005 | 2.563E-004 | 8.904E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 9.287E-003 | 9.800E-005 | 2.127E-004 | 8.904E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 2.198E-002 | 2.816E-004 | 2.506E-004 | 0.256 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 3.900E-002 | 2.065E-004 | 1.137E-004 | 0.188 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 0.111 | 8.519E-005 | 1.629E-004 | 7.740E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 2.563E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 2.563E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 2.857E-003 | 1.165E-004 | 2.563E-004 | 0.138 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 2.858E-003 | 1.165E-004 | 2.563E-004 | 0.138 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 2.563E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 2.563E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 1.238E-002 | 3.180E-005 | 2.563E-004 | 3.755E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 1.297E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 1.297E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 5.239E-003 | 2.136E-004 | 1.165E-004 | 0.252 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 2.500E-002 | 7.539E-005 | 5.825E-005 | 8.904E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 2.500E-002 | 7.539E-005 | 5.825E-005 | 8.904E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 2.238E-002 | 2.167E-004 | 1.174E-004 | 0.256 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 2.191E-002 | 5.316E-005 | 4.403E-005 | 6.278E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 9.8537E-002 |
2 | Clear Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 4.0323E-002 |
3 | Clear Turbid Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1102 |
4 | Clear Turbid Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 4.3566E-002 |
5 | Intermediate Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 7.1969E-002 |
6 | Intermediate Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 2.5953E-002 |
7 | Overcast Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 2.9162E-002 |
8 | Overcast Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 9.6591E-003 |
9 | Clear Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1080 |
10 | Clear Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 4.9517E-002 |
11 | Clear Turbid Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1204 |
12 | Clear Turbid Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 5.3475E-002 |
13 | Intermediate Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 7.9001E-002 |
14 | Intermediate Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 3.2853E-002 |
15 | Overcast Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 3.2764E-002 |
16 | Overcast Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 1.3236E-002 |
17 | Clear Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.3109E-002 |
18 | Clear Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.3137E-002 |
19 | Clear Turbid Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 1.7873E-002 |
20 | Clear Turbid Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 9.9610E-003 |
21 | Intermediate Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 1.7300E-002 |
22 | Intermediate Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 6.9150E-003 |
23 | Overcast Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.8719E-002 |
24 | Overcast Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.0154E-002 |
25 | Clear Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.3109E-002 |
26 | Clear Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.3137E-002 |
27 | Clear Turbid Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 1.7873E-002 |
28 | Clear Turbid Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 9.9610E-003 |
29 | Intermediate Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 1.7300E-002 |
30 | Intermediate Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 6.9150E-003 |
31 | Overcast Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.8719E-002 |
32 | Overcast Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.0154E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 33601.04462 | 33601.04462 | 2.53219 | 2.53219 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 20:50:00 | 28.93750 | 1.44633E-002 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
2 | BASEMENT | Heating | 1416.69275 | 1416.69275 | 6.29827E-002 | 0.85446 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -6.30000 | 2.29779E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
3 | RETAIL_1_FLR_1 | Cooling | 4134.19824 | 4134.19824 | 0.31159 | 0.31159 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 34.40000 | 1.44733E-002 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 2612.59979 | 2612.59979 | 0.11615 | 0.11615 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -6.30000 | 2.29779E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 3144.52785 | 3144.52785 | 0.23700 | 0.23700 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 32.12000 | 1.44691E-002 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 864.96211 | 864.96211 | 3.84537E-002 | 9.17347E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -6.30000 | 2.29779E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 2673.31171 | 2673.31171 | 0.20144 | 0.20144 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 20:10:00 | 29.50750 | 1.44643E-002 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 1567.83361 | 1567.83361 | 6.97013E-002 | 6.97013E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -6.30000 | 2.29779E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 1593.77168 | 1593.77168 | 0.12010 | 0.12010 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 31.88250 | 1.44687E-002 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 1050.65967 | 1050.65967 | 4.67093E-002 | 5.77652E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -6.30000 | 2.29779E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 44739.61174 | 44739.61174 | 3.37164 | 3.37164 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 33.92500 | 1.44724E-002 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 2032.64463 | 2032.64463 | 9.03639E-002 | 9.03639E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -6.30000 | 2.29779E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 18285.02461 | 18285.02461 | 1.37931 | 1.37931 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 34.40000 | 1.44733E-002 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 6642.37080 | 6642.37080 | 0.29530 | 0.67639 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -6.30000 | 2.29779E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 63414.63149 | 63414.63149 | 4.78089 | 4.78089 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 34.40000 | 1.44733E-002 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 15493.62493 | 15493.62493 | 0.68880 | 1.89399 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -6.30000 | 2.29779E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 9899.67934 | 9899.67934 | 1.00532 | 1.00532 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 32.91167 | 1.44705E-002 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 5842.76387 | 5842.76387 | 0.26127 | 0.26127 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -6.30000 | 2.29779E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 9793.63081 | 9793.63081 | 0.99455 | 0.99455 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 32.75333 | 1.44703E-002 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 5855.22984 | 5855.22984 | 0.26183 | 0.26183 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -6.30000 | 2.29779E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 59607.73973 | 59607.73973 | 6.05285 | 6.05285 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 34.40000 | 1.44733E-002 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 33672.12995 | 33672.12995 | 1.50576 | 1.50576 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -6.30000 | 2.29779E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 63059.54999 | 63059.54999 | 6.40386 | 6.40386 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 34.02000 | 1.44726E-002 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 33918.21578 | 33918.21578 | 1.51676 | 1.51676 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -6.30000 | 2.29779E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 8972.91103 | 8972.91103 | 0.91121 | 0.91121 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 31.50250 | 1.44680E-002 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 5817.27720 | 5817.27720 | 0.26013 | 0.26013 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -6.30000 | 2.29779E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 8898.65647 | 8898.65647 | 0.90367 | 0.90367 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 31.26500 | 1.44675E-002 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 5829.75103 | 5829.75103 | 0.26069 | 0.26069 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -6.30000 | 2.29779E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 19846.86133 | 19846.86133 | 1.49564 | 1.49564 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 34.30500 | 1.44731E-002 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 9276.36483 | 9276.36483 | 0.41240 | 0.47476 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -6.30000 | 2.29779E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 2601.54609 | 2601.54609 | 0.26419 | 0.26419 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 33.07000 | 1.44708E-002 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 1793.86576 | 1793.86576 | 8.02175E-002 | 8.02175E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -6.30000 | 2.29779E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 2571.13541 | 2571.13541 | 0.26110 | 0.26110 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 32.91167 | 1.44705E-002 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 1798.80069 | 1798.80069 | 8.04382E-002 | 8.04382E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -6.30000 | 2.29779E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 11764.10053 | 11764.10053 | 1.19468 | 1.19468 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 34.40000 | 1.44733E-002 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 8595.97950 | 8595.97950 | 0.38439 | 0.38439 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -6.30000 | 2.29779E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 29496.66258 | 29496.66258 | 2.22564 | 2.22564 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 34.40000 | 1.44733E-002 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 5933.95517 | 5933.95517 | 0.26381 | 1.18780 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -6.30000 | 2.29779E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 30910.66604 | 30910.66604 | 2.33229 | 2.33229 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 34.40000 | 1.44733E-002 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
40 | DINING_FLR_6 | Heating | 6065.27678 | 6065.27678 | 0.26964 | 1.18780 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | -6.30000 | 2.29779E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 30545.23759 | 30545.23759 | 2.30800 | 2.30800 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 33.54500 | 1.44717E-002 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 1842.11826 | 1842.11826 | 8.18846E-002 | 0.36735 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | -6.30000 | 2.29779E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
43 | CORRIDOR_FLR_6 | Cooling | 10031.92118 | 10031.92118 | 0.75599 | 0.75599 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 34.40000 | 1.44733E-002 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 6259.46154 | 6259.46154 | 0.27828 | 0.27828 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | -6.30000 | 2.29779E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | FLR_3_DOAS | Cooling | Sensible | 51689.19 | 17.35224 | 2.05125 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | FLR_3_DOAS | Heating | Sensible | 55039.41 | 4.61151 | 2.05125 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 |
3 | VAV WITH REHEAT | Cooling | Sensible | 427824.95 | 21.92496 | 21.92496 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | VAV WITH REHEAT | Heating | Sensible | 197123.17 | 7.34652 | 7.34652 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.53219 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.59548 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52900 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.33953 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.39820E-004 |
8 | Coil:Heating:Electric | BASEMENT VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 36949.53938 |
9 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.31159 |
10 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16402 |
11 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52900 |
12 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16483 |
13 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52900 |
14 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.32286E-003 |
16 | Coil:Heating:Electric | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 4546.76200 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.23700 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24972 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52900 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.12537 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.66591 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.52572E-003 |
24 | Coil:Heating:Electric | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 3458.32025 |
25 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.20144 |
26 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.62128 |
27 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52900 |
28 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.10656 |
29 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
30 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
31 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.13247E-004 |
32 | Coil:Heating:Electric | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 2939.44355 |
33 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.12010 |
34 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.60123 |
35 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52900 |
36 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 6.35314E-002 |
37 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
38 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.33696E-004 |
40 | Coil:Heating:Electric | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 1752.44750 |
41 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.37164 |
42 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 1.76371E-002 |
43 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52900 |
44 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.78360 |
45 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52900 |
46 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.16021E-002 |
48 | Coil:Heating:Electric | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 49198.69849 |
49 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.37931 |
50 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10434 |
51 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52900 |
52 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.72965 |
53 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52900 |
54 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
55 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.65163E-003 |
56 | Coil:Heating:Electric | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 20126.76248 |
57 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 4.78089 |
58 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20850 |
59 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52900 |
60 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.52909 |
61 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.55601 |
62 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.82730E-003 |
64 | Coil:Heating:Electric | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 69762.37754 |
65 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
66 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.00532 |
67 | Fan:OnOff | ROOM_1_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 1.00532 |
68 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.14528E-004 |
69 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70401 |
70 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
71 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.63177E-003 |
72 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
73 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
74 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.14528E-004 |
75 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.00532 |
76 | Coil:Heating:Electric | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Nominal Capacity [W] | 5842.73223 |
77 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
78 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.99455 |
79 | Fan:OnOff | ROOM_2_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 0.99455 |
80 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.11296E-004 |
81 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70401 |
82 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
83 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.63341E-003 |
84 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
85 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
86 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.11296E-004 |
87 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.99455 |
88 | Coil:Heating:Electric | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Nominal Capacity [W] | 5855.19814 |
89 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83707 |
90 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 6.05285 |
91 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 6.05285 |
92 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.85180E-003 |
93 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70463 |
94 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
95 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.54946E-003 |
96 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
97 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
98 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.85180E-003 |
99 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 6.05285 |
100 | Coil:Heating:Electric | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Nominal Capacity [W] | 33672.04277 |
101 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83730 |
102 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 6.40386 |
103 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 6.40386 |
104 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.07984E-003 |
105 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70374 |
106 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
107 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.77311E-003 |
108 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
109 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
110 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.07984E-003 |
111 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 6.40386 |
112 | Coil:Heating:Electric | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Nominal Capacity [W] | 33918.12802 |
113 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
114 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.91121 |
115 | Fan:OnOff | ROOM_5_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 0.91121 |
116 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.86158E-004 |
117 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70399 |
118 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
119 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.64575E-003 |
120 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
121 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
122 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.86158E-004 |
123 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.91121 |
124 | Coil:Heating:Electric | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Nominal Capacity [W] | 5817.24569 |
125 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
126 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.90367 |
127 | Fan:OnOff | ROOM_6_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 0.90367 |
128 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.83887E-004 |
129 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70399 |
130 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
131 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.64703E-003 |
132 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
133 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
134 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.83887E-004 |
135 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.90367 |
136 | Coil:Heating:Electric | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Nominal Capacity [W] | 5829.71945 |
137 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.49564 |
138 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.79358 |
139 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52900 |
140 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.79119 |
141 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
142 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
143 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.80104E-004 |
144 | Coil:Heating:Electric | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 21824.23989 |
145 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54338E-002 |
146 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.26419 |
147 | Fan:OnOff | ROOM_1_FLR_6 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 0.26419 |
148 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 8.25102E-005 |
149 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70402 |
150 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
151 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.62527E-003 |
152 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
153 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
154 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 8.25102E-005 |
155 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.26419 |
156 | Coil:Heating:Electric | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Nominal Capacity [W] | 1793.85642 |
157 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54319E-002 |
158 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.26110 |
159 | Fan:OnOff | ROOM_2_FLR_6 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 0.26110 |
160 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 8.15814E-005 |
161 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70402 |
162 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
163 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.62689E-003 |
164 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
165 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
166 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 8.15814E-005 |
167 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.26110 |
168 | Coil:Heating:Electric | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Nominal Capacity [W] | 1798.79132 |
169 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 9.91540E-002 |
170 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.19468 |
171 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 1.19468 |
172 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.80404E-004 |
173 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70377 |
174 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
175 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.69767E-003 |
176 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
177 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
178 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.80404E-004 |
179 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.19468 |
180 | Coil:Heating:Electric | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Nominal Capacity [W] | 8595.94400 |
181 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.22564 |
182 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11355 |
183 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52900 |
184 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.17736 |
185 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52900 |
186 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
187 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.35533E-003 |
188 | Coil:Heating:Electric | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 32476.32007 |
189 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.33229 |
190 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10836 |
191 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52900 |
192 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.23378 |
193 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52900 |
194 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
195 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.51612E-003 |
196 | Coil:Heating:Electric | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 34032.62442 |
197 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.30800 |
198 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 6.13450E-002 |
199 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52900 |
200 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.22093 |
201 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52900 |
202 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
203 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.11709E-002 |
204 | Coil:Heating:Electric | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 33678.12602 |
205 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.75599 |
206 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.41540 |
207 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52900 |
208 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.39992 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 9.17188E-004 |
212 | Coil:Heating:Electric | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 11031.36457 |
213 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05132 |
214 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05132 |
215 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05132 |
216 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05132 |
217 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05132 |
218 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05132 |
219 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
220 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
221 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 11.66536 |
222 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 11.66536 |
223 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 22.05173 |
224 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 11.66536 |
225 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 21.92496 |
226 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 21.92496 |
227 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
228 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.53206 |
229 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05132 |
230 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 21.92496 |
231 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05132 |
232 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05125 |
233 | HeatExchanger:AirToAir:SensibleAndLatent | FLR_3_DOAS OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.05125 |
234 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 34.40000 |
235 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
236 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.90668 |
237 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.44733E-002 |
238 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
239 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Coil Load [W] | 91161.10877 |
240 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.60720E-003 |
241 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 2.05132 |
242 | Coil:Heating:Electric | FLR_3_DOAS HEATING COIL | Design Size Nominal Capacity [W] | 16512.40431 |
243 | Fan:ConstantVolume | FLR_3_DOAS FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05125 |
244 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.60720E-003 |
245 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.82645E-004 |
246 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 21.92496 |
247 | HeatExchanger:AirToAir:SensibleAndLatent | VAV WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 11.66146 |
248 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 29.52626 |
249 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
250 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.92186 |
251 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.22387E-002 |
252 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
253 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 726568.32661 |
254 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.07798E-002 |
255 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 21.92496 |
256 | Coil:Heating:Electric | VAV WITH REHEAT HEATING COIL | Design Size Nominal Capacity [W] | 176488.47681 |
257 | Fan:VariableVolume | VAV WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 21.92496 |
258 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.07798E-002 |
259 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 2.29161E-005 |
260 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 2.90590E-002 |
261 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 4744.44047 |
262 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 2.90590E-002 |
263 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 3.48708 |
264 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 2.90590E-002 |
265 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 3284.73616 |
266 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 2.90590E-002 |
267 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1016052.10229 |
268 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1016659.59000 |
269 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 115.89919 |
270 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
271 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
272 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
273 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
274 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | 16600.37 | 14080.56 | 2519.80 | 0.85 | 3699.77 | 37.53 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | 16427.48 | 13931.35 | 2496.13 | 0.85 | 3659.04 | 37.11 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 98418.19 | 84274.40 | 14143.79 | 0.86 | 22616.68 | 229.39 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 108470.22 | 90607.99 | 17862.23 | 0.84 | 23098.81 | 234.28 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | 15084.82 | 12775.06 | 2309.77 | 0.85 | 3345.02 | 33.93 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | 14963.46 | 12670.48 | 2292.98 | 0.85 | 3316.60 | 33.64 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | 4357.22 | 3698.54 | 658.69 | 0.85 | 973.43 | 9.87 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | 4307.57 | 3655.73 | 651.85 | 0.85 | 961.76 | 9.75 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 19966.09 | 16812.45 | 3153.64 | 0.84 | 4352.51 | 44.15 |
10 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | 64827.35 | 41208.20 | 23619.15 | 0.64 | 8819.06 | 89.45 |
11 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | 650938.25 | 422466.64 | 228471.60 | 0.65 | 96781.99 | 981.62 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 4.09 | 13.95 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.940 | 0.824 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 22.63 | 45.89 | 22.63 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 23.26 | 23.26 | 23.26 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 2.390 | 2.390 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 63.73 | 129.23 | 63.73 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 65.50 | 65.50 | 65.50 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 82.79 | 167.88 | 82.79 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 85.08 | 85.08 | 85.08 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.167 | 0.994 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.167 | 0.994 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.167 | 0.994 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.167 | 0.994 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.034 | 0.896 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.034 | 0.896 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.034 | 0.896 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.034 | 0.896 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.034 | 0.896 | 13.70 | 20.44 | 13.70 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 6.74 | 6.74 | 6.74 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 16.77 | 21.37 | 16.77 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 34.86 | 52.03 | 34.86 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 17.17 | 17.17 | 17.17 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 34.86 | 52.03 | 34.86 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 17.17 | 17.17 | 17.17 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 1.3797207235E-002 | 1.9950890703E-002 | Pass | Pass | 5.4242972586E-003 | 1.8408337004E-002 | Pass | Pass |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 7.6603802284E-005 | 1.4234524365E-004 | Pass | Pass | 0.2063045636 | 0.7433146371 | Pass | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.2884245605E-003 | 1.2426117523E-002 | Pass | Pass | 1.5959410348E-002 | 4.3344294219E-002 | Pass | Pass |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.2935744177E-005 | 3.2167207311E-005 | Pass | Pass | 2.5880171571E-002 | 5.9579382909E-002 | Pass | Pass |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.2931209399E-005 | 5.3438648484E-005 | Pass | Pass | 5.0702714254E-002 | 8.3946291897E-002 | Pass | Pass |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 5.7237858172E-002 | 0.1905761923 | Pass | Pass | 1.8448655123E-002 | 5.1022804058E-002 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 3.2090855981E-003 | 1.2908852858E-002 | Pass | Pass | 2.4393444979E-002 | 6.7725721764E-002 | Pass | Pass |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.4382983474E-002 | 2.8123116534E-002 | Pass | Pass | 1.4415336526E-002 | 4.4440537552E-002 | Pass | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.5024637662E-002 | 0.1413783370 | Pass | Pass | 0.1295764895 | 0.5063376231 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.6776832910E-002 | 0.1478150147 | Pass | Pass | 0.1238514471 | 0.4825350997 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 3.8780258994E-002 | 4.7214647611E-002 | Pass | Pass | 7.2148722227E-003 | 7.4203852474E-002 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.6762249390E-002 | 0.1310096526 | Pass | Pass | 0.9325790979 | 7.6932760841 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.3533816486E-002 | 0.1370733185 | Pass | Pass | 0.1356312799 | 0.5307680094 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.5252665002E-002 | 0.1433605500 | Pass | Pass | 0.1291334547 | 0.5046071604 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 1.6053879114E-005 | 4.3059493053E-005 | Pass | Pass | 3.1031915686E-002 | 6.5648880877E-002 | Pass | Pass |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 6.5522864769E-002 | 0.2082747612 | Pass | Pass | 9.1804704380E-002 | 0.3285848712 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 6.7453290618E-002 | 0.2150134207 | Pass | Pass | 8.8678324515E-002 | 0.3170856902 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 3.0273775365E-002 | 9.3769477724E-002 | Pass | Pass | 0.2028083970 | 0.9995856594 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 4.9913519055E-002 | 9.8317970251E-002 | Pass | Pass | 6.1320998450E-003 | 1.4120028788E-002 | Pass | Pass |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 5.0622835294E-002 | 9.3565325113E-002 | Pass | Pass | 5.4247130263E-003 | 1.2316600160E-002 | Pass | Pass |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 4.5892190642E-002 | 0.1404250012 | Pass | Pass | 1.8801737296E-002 | 3.2484125150E-002 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 2.0124775305E-005 | 4.4175249599E-005 | Pass | Pass | 2.7307885270E-002 | 3.4671269861E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3000.37 | 15.15 | 463.32 | 1500.47 | 7474.09 | 12453.39 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | -6.30 | 0.00 | -6.30 | Wetbulb [C] | 5.30 | 320.00 |
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 34.40 | 9.50 | 23.50 | Wetbulb [C] | 4.00 | 300.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 90.00 | 25 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 211.13 | 211.13 | 0.00 | 90.00 | N |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 55.76 | 55.76 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 211.13 | 211.13 | 180.00 | 90.00 | S |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 55.76 | 55.76 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 45.89 | 22.63 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 129.23 | 63.73 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 167.88 | 82.79 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 104.06 | 69.72 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 847.14 | 567.58 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 847.37 | 567.71 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 104.06 | 69.72 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 26.02 | 17.43 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 13.94 | 9.34 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | RES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 13.94 | 9.34 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 183.96 | 123.26 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 97.55 | 65.36 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 97.55 | 65.36 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 21.37 | 16.77 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 52.03 | 34.86 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 13.94 | 9.34 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 17.65 | 11.83 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 52.03 | 34.86 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 167.42 | 167.42 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_FLOOR | BASEMENT_FLOOR | 0.30 | 1.441 | 2.705 | 1978.83 | 1978.83 | 0.00 | 180.00 | |
BASEMENT_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 67.07 | 67.07 | 180.00 | 0.00 | |
BASEMENT_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 77.67 | 77.67 | 180.00 | 0.00 | |
BASEMENT_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 164.24 | 164.24 | 180.00 | 0.00 | |
BASEMENT_CEILING_4 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 94.76 | 94.76 | 180.00 | 0.00 | |
BASEMENT_CEILING_5 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 78.04 | 78.04 | 180.00 | 0.00 | |
BASEMENT_CEILING_6 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 188.86 | 188.86 | 180.00 | 0.00 | |
BASEMENT_CEILING_7 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 1088.56 | 1088.56 | 180.00 | 0.00 | |
BASEMENT_CEILING_8 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 219.63 | 219.63 | 90.00 | 0.00 | |
RETAIL_1_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_1_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
RETAIL_1_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 67.07 | 67.07 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
RETAIL_2_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_2_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 90.00 | 90.00 | E |
RETAIL_2_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 77.67 | 77.67 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 77.67 | 77.67 | 180.00 | 0.00 | |
MECH_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
MECH_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 180.00 | 90.00 | S |
MECH_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
MECH_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 164.24 | 164.24 | 0.00 | 180.00 | |
MECH_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 164.24 | 164.24 | 180.00 | 0.00 | |
STORAGE_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
STORAGE_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 180.00 | 90.00 | S |
STORAGE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
STORAGE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 94.76 | 94.76 | 0.00 | 180.00 | |
STORAGE_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 94.76 | 94.76 | 180.00 | 0.00 | |
LAUNDRY_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 180.00 | 90.00 | S |
LAUNDRY_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 270.00 | 90.00 | W |
LAUNDRY_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 78.04 | 78.04 | 0.00 | 180.00 | |
LAUNDRY_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 78.04 | 78.04 | 180.00 | 0.00 | |
CAFE_FLR_1_WALL_1_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_2_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
CAFE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 188.86 | 188.86 | 0.00 | 180.00 | |
LOBBY_FLR_1_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 90.00 | 90.00 | E |
LOBBY_FLR_1_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 1088.56 | 1088.56 | 180.00 | 180.00 | |
LOBBY_FLR_1_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 219.63 | 219.63 | 90.00 | 180.00 | |
LOBBY_FLR_1_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 1062.83 | 1062.83 | 270.00 | 0.00 | |
ROOM_1_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_1_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
ROOM_1_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_1_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_2_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
ROOM_2_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_2_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_2_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 156.07 | 156.07 | 180.00 | 0.00 | |
ROOM_3_MULT19_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.14 | 847.14 | 0.00 | 90.00 | N |
ROOM_3_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_3_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 1863.81 | 1863.81 | 0.00 | 180.00 | |
ROOM_3_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 1863.81 | 1863.81 | 180.00 | 0.00 | |
ROOM_4_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_4_MULT19_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.37 | 847.37 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_4_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 1864.32 | 1864.32 | 0.00 | 180.00 | |
ROOM_4_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 1864.32 | 1864.32 | 180.00 | 0.00 | |
ROOM_5_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
ROOM_5_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_5_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_6_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
ROOM_6_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_6_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 156.07 | 156.07 | 180.00 | 0.00 | |
CORRIDOR_FLR_3_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.28 | 847.28 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_4_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.27 | 847.27 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 297.29 | 297.29 | 180.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 963.06 | 963.06 | 270.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_3 | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 297.26 | 297.26 | 90.00 | 180.00 | |
CORRIDOR_FLR_3_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 297.29 | 297.29 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 963.06 | 963.06 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 297.26 | 297.26 | 90.00 | 0.00 | |
ROOM_1_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 0.00 | 90.00 | N |
ROOM_1_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_1_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_2_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_2_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 180.00 | 90.00 | S |
ROOM_2_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_3_MULT9_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.96 | 183.96 | 0.00 | 90.00 | N |
ROOM_3_MULT9_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 90.00 | 90.00 | E |
ROOM_3_MULT9_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 270.00 | 90.00 | W |
ROOM_3_MULT9_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 220.77 | 220.77 | 0.00 | 180.00 | |
BANQUET_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
BANQUET_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
BANQUET_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
BANQUET_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 331.66 | 331.66 | 0.00 | 180.00 | |
DINING_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
DINING_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
DINING_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
DINING_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 331.66 | 331.66 | 0.00 | 180.00 | |
KITCHEN_FLR_6_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 7.43 | 7.43 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 103.30 | 103.30 | 180.00 | 180.00 | |
CORRIDOR_FLR_6_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 104.98 | 104.98 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_1_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.95 | 183.95 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 11.15 | 11.15 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 40.88 | 40.88 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 412.12 | 412.12 | 180.00 | 180.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3957.66 | 0.00 | 90.00 | N | ||
RETAIL_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 134.14 | 0.00 | 90.00 | N | ||
RETAIL_2_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 155.34 | 0.00 | 90.00 | N | ||
MECH_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 328.49 | 0.00 | 90.00 | N | ||
STORAGE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 189.52 | 0.00 | 90.00 | N | ||
LAUNDRY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 156.08 | 0.00 | 90.00 | N | ||
CAFE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 377.72 | 0.00 | 90.00 | N | ||
LOBBY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 2616.37 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3727.63 | 0.00 | 90.00 | N | ||
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3728.64 | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3115.24 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.04 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.03 | 0.00 | 90.00 | N | ||
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 441.55 | 0.00 | 90.00 | N | ||
BANQUET_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
DINING_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 206.61 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 824.25 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 23.26 | 0.00 | 0.00 | 23.26 | 23.26 | 2.557 | 0.251 | 0.276 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 65.50 | 0.00 | 0.00 | 65.50 | 65.50 | 2.557 | 0.251 | 0.276 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 85.08 | 0.00 | 0.00 | 85.08 | 85.08 | 2.557 | 0.251 | 0.276 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.769 | 0.251 | 0.276 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.769 | 0.251 | 0.276 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.769 | 0.251 | 0.276 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.769 | 0.251 | 0.276 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 3.68 | 0.00 | 0.00 | 3.68 | 279.56 | 2.769 | 0.251 | 0.276 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 3.68 | 0.00 | 0.00 | 3.68 | 279.65 | 2.769 | 0.251 | 0.276 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.769 | 0.251 | 0.276 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.769 | 0.251 | 0.276 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.769 | 0.251 | 0.276 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.769 | 0.251 | 0.276 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.557 | 0.251 | 0.276 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 2.557 | 0.251 | 0.276 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 2.557 | 0.251 | 0.276 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.557 | 0.251 | 0.276 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.769 | 0.251 | 0.276 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.769 | 0.251 | 0.276 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.769 | 0.251 | 0.276 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.769 | 0.251 | 0.276 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 6.74 | 0.00 | 0.00 | 6.74 | 60.70 | 2.769 | 0.251 | 0.276 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.557 | 0.251 | 0.276 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.557 | 0.251 | 0.276 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.557 | 0.251 | 0.276 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.557 | 0.251 | 0.276 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | |||||||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.557 | 0.251 | 0.276 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 5.82 | 0.00 | 0.00 | 5.82 | 5.82 | 2.557 | 0.251 | 0.276 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 2.557 | 0.251 | 0.276 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.557 | 0.251 | 0.276 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 1213.79 | 2.707 | 0.251 | 0.276 | |||||||||||||||||
North Total or Average | 432.95 | 2.714 | 0.251 | 0.276 | |||||||||||||||||
Non-North Total or Average | 780.84 | 2.702 | 0.251 | 0.276 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 1.760 | 2.390 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 8.8143 | 1978.83 | 17441.96 | LightsWired | LTG_SCH_BASEMENT | 49.32 | 168.00 | 49.26 | 0.0000 | Y | 161.29 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | RETAIL_1_FLR_1 | GENERAL | 11.3140 | 67.07 | 758.85 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 7.31 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | RETAIL_2_FLR_1 | GENERAL | 11.3140 | 77.67 | 878.75 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 8.46 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | MECH_FLR_1 | GENERAL | 4.6285 | 164.24 | 760.20 | LightsWired | LTG_SCH_MECHANIC | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 8.37 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | STORAGE_FLR_1 | GENERAL | 5.7199 | 94.76 | 542.02 | LightsWired | LTG_SCH_STORAGE | 30.30 | 168.00 | 30.27 | 0.0000 | Y | 3.08 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | LAUNDRY_FLR_1 | GENERAL | 4.6285 | 78.04 | 361.20 | LightsWired | LTG_SCH_LAUNDRY | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 3.98 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | CAFE_FLR_1 | GENERAL | 10.0104 | 188.86 | 1890.59 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 40.20 | 0.0000 | Y | 14.27 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | LOBBY_FLR_1 | GENERAL | 10.7639 | 1308.19 | 14081.18 | LightsWired | LTG_SCH_LOBBY | 44.02 | 168.00 | 41.70 | 0.0000 | Y | 110.23 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | ROOM_1_FLR_3 | GENERAL | 8.2882 | 156.09 | 1293.69 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | ROOM_2_FLR_3 | GENERAL | 8.2882 | 156.07 | 1293.54 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | GENERAL | 8.2882 | 1863.81 | 15447.65 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 110.38 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | GENERAL | 8.2882 | 1864.32 | 15451.87 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 110.41 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | ROOM_5_FLR_3 | GENERAL | 8.2882 | 156.09 | 1293.69 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | ROOM_6_FLR_3 | GENERAL | 8.2882 | 156.07 | 1293.54 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | CORRIDOR_FLR_3 | GENERAL | 7.1042 | 1557.62 | 11065.59 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 91.33 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | ROOM_1_FLR_6 | GENERAL | 8.2882 | 39.02 | 323.42 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 2.31 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | ROOM_2_FLR_6 | GENERAL | 8.2882 | 39.02 | 323.38 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 2.31 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | GENERAL | 8.2882 | 220.77 | 1829.83 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 13.08 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | BANQUET_FLR_6 | GENERAL | 10.0104 | 331.66 | 3320.03 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 50.07 | 0.0000 | Y | 31.20 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | DINING_FLR_6 | GENERAL | 10.0104 | 331.66 | 3320.03 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 50.07 | 0.0000 | Y | 31.20 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | KITCHEN_FLR_6 | GENERAL | 11.4097 | 103.30 | 1178.68 | LightsWired | LTG_SCH_KITCHEN | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 12.97 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | CORRIDOR_FLR_6 | GENERAL | 7.1042 | 412.12 | 2927.80 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 24.17 |
Interior Lighting Total | 8.5566 | 11345.29 | 97077.49 | 457.58 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
LOBBY_FLR_1_DAYLREFPT1 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.07 | 14081.18 | 985.68 |
LOBBY_FLR_1_DAYLREFPT2 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.07 | 14081.18 | 985.68 |
CAFE_FLR_1_DAYLREFPT1 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1890.59 | 737.33 |
CAFE_FLR_1_DAYLREFPT2 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1890.59 | 737.33 |
DINING_FLR_6_DAYLREFPT1 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
DINING_FLR_6_DAYLREFPT2 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
BANQUET_FLR_6_DAYLREFPT1 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
BANQUET_FLR_6_DAYLREFPT2 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 12338.45 | AstronomicalClock | - | 83.77 | 83.77 | 194.02 | |
Exterior Lighting Total | 12338.45 | 194.02 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 1016659.59 | 2.96 | 1016659.59 | 2.96 | 4.09 | 13.95 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 10997.73 | 16600.37 | 14080.56 | 2519.80 | 0.85 | - | 3699.77 | 37.53 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 10884.74 | 16427.48 | 13931.35 | 2496.13 | 0.85 | - | 3659.04 | 37.11 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 64749.62 | 98418.19 | 84274.40 | 14143.79 | 0.86 | - | 22616.68 | 229.39 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 72723.43 | 108470.22 | 90607.99 | 17862.23 | 0.84 | - | 23098.81 | 234.28 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 10005.75 | 15084.82 | 12775.06 | 2309.77 | 0.85 | - | 3345.02 | 33.93 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 9926.34 | 14963.46 | 12670.48 | 2292.98 | 0.85 | - | 3316.60 | 33.64 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 2885.04 | 4357.22 | 3698.54 | 658.69 | 0.85 | - | 973.43 | 9.87 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 2852.56 | 4307.57 | 3655.73 | 651.85 | 0.85 | - | 961.76 | 9.75 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 13301.16 | 19966.09 | 16812.45 | 3153.64 | 0.84 | - | 4352.51 | 44.15 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | 91161.11 | 64827.35 | 41208.20 | 23619.15 | 0.64 | - | 8819.06 | 89.45 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | 726568.33 | 650938.25 | 422466.64 | 228471.60 | 0.65 | - | 96781.99 | 981.62 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Electric | 36949.54 | 1.00 | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4546.76 | 1.00 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 3458.32 | 1.00 | |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 2939.44 | 1.00 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 1752.45 | 1.00 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 49198.70 | 1.00 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 20126.76 | 1.00 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 69762.38 | 1.00 | |
ROOM_1_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Electric | 5842.73 | 1.00 | |
ROOM_2_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Electric | 5855.20 | 1.00 | |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Electric | 33672.04 | 1.00 | |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Electric | 33918.13 | 1.00 | |
ROOM_5_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Electric | 5817.25 | 1.00 | |
ROOM_6_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Electric | 5829.72 | 1.00 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 21824.24 | 1.00 | |
ROOM_1_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Electric | 1793.86 | 1.00 | |
ROOM_2_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Electric | 1798.79 | 1.00 | |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Electric | 8595.94 | 1.00 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Electric | 32476.32 | 1.00 | |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Electric | 34032.62 | 1.00 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Electric | 33678.13 | 1.00 | |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Electric | 11031.36 | 1.00 | |
FLR_3_DOAS HEATING COIL | Coil:Heating:Electric | 16512.40 | 1.00 | |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Electric | 176488.48 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 0.24 | 76.61 | 324.68 | 1.00 | 2.78 | General | ||
LOBBY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.24 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
ROOM_1_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 1.01 | 707.38 | 703.64 | 1.00 | 1.20 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 |
ROOM_2_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 0.99 | 699.80 | 703.64 | 1.00 | 1.20 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 |
ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 6.05 | 4259.01 | 703.64 | 1.00 | 0.96 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 |
ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 6.40 | 4505.99 | 703.64 | 1.00 | 0.95 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 |
ROOM_5_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 0.91 | 641.16 | 703.64 | 1.00 | 1.22 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 |
ROOM_6_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 0.90 | 635.86 | 703.64 | 1.00 | 1.22 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 |
ROOM_1_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 0.26 | 185.89 | 703.64 | 1.00 | 1.81 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
ROOM_2_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 0.26 | 183.72 | 703.64 | 1.00 | 1.82 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 |
ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 1.19 | 840.62 | 703.64 | 1.00 | 1.16 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 |
BANQUET_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
DINING_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 1.89 | 612.92 | 324.68 | 1.00 | 1.48 | General | ||
FLR_3_DOAS FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.93 | 1070.05 | 1.00 | 1.30 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 |
VAV WITH REHEAT FAN | Fan:VariableVolume | 0.62 | 1389.42 | 21.92 | 49125.92 | 2240.64 | 1.00 | 1.11 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.029059 | 4744.44 | 163269.44 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.029059 | 3284.74 | 113036.94 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH LAUNDRY G WATER HEATER | WaterHeater:Mixed | 1.14 | 163316.00 | 0.80 | 11.51 | 0.44 |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.22 | 1.12 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.60 | 0.80 | 5.78 | 0.37 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 33601.04 | 33601.04 | 16.98 | 2.532 | 2.532 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 20:50:00 | 24.00 | 24.00 | 0.00922 | 28.94 | 0.01446 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 4134.20 | 4134.20 | 61.64 | 0.312 | 0.312 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00916 | 34.40 | 0.01447 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 3144.53 | 3144.53 | 40.49 | 0.237 | 0.237 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 24.00 | 24.00 | 0.00944 | 32.12 | 0.01447 | 0.092 | 0.00 |
MECH_FLR_1 | 2673.31 | 2673.31 | 16.28 | 0.201 | 0.201 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 20:10:00 | 24.00 | 24.00 | 0.00883 | 29.51 | 0.01446 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1593.77 | 1593.77 | 16.82 | 0.120 | 0.120 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 24.00 | 24.00 | 0.00889 | 31.88 | 0.01447 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 44739.61 | 44739.61 | 573.29 | 3.372 | 3.372 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 24.00 | 24.00 | 0.00855 | 33.92 | 0.01447 | 0.000 | 0.00 |
CAFE_FLR_1 | 18285.02 | 18285.02 | 96.82 | 1.379 | 1.379 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 23.99 | 0.01029 | 34.40 | 0.01447 | 0.676 | 0.00 |
LOBBY_FLR_1 | 63414.63 | 63414.63 | 48.48 | 4.781 | 4.781 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 24.00 | 23.99 | 0.01003 | 34.40 | 0.01447 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 9899.68 | 9899.68 | 253.69 | 1.005 | 1.005 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 21.11 | 21.11 | 0.00863 | 32.91 | 0.01447 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 9793.63 | 9793.63 | 251.01 | 0.995 | 0.995 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 21.11 | 21.11 | 0.00863 | 32.75 | 0.01447 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 59607.74 | 59607.74 | 2430.60 | 6.053 | 6.053 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 21.11 | 21.11 | 0.00855 | 34.40 | 0.01447 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 63059.55 | 63059.55 | 2570.65 | 6.404 | 6.404 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 21.11 | 21.11 | 0.00877 | 34.02 | 0.01447 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 8972.91 | 8972.91 | 229.94 | 0.911 | 0.911 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 21.11 | 21.11 | 0.00865 | 31.50 | 0.01447 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 8898.66 | 8898.66 | 228.07 | 0.904 | 0.904 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 21.11 | 21.11 | 0.00865 | 31.26 | 0.01447 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 19846.86 | 19846.86 | 50.97 | 1.496 | 1.496 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00950 | 34.30 | 0.01447 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 2601.55 | 2601.55 | 66.67 | 0.264 | 0.264 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 21.11 | 21.11 | 0.00863 | 33.07 | 0.01447 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2571.14 | 2571.14 | 65.90 | 0.261 | 0.261 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 21.11 | 21.11 | 0.00863 | 32.91 | 0.01447 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 11764.10 | 11764.10 | 479.57 | 1.195 | 1.195 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 21.11 | 21.11 | 0.00870 | 34.40 | 0.01447 | 0.099 | 0.00 |
BANQUET_FLR_6 | 29496.66 | 29496.66 | 88.94 | 2.226 | 2.226 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 23.98 | 0.01042 | 34.40 | 0.01447 | 1.188 | 0.00 |
DINING_FLR_6 | 30910.67 | 30910.67 | 93.20 | 2.332 | 2.332 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 23.98 | 0.01034 | 34.40 | 0.01447 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 30545.24 | 30545.24 | 295.68 | 2.308 | 2.308 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 24.00 | 23.97 | 0.01011 | 33.55 | 0.01447 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 10031.92 | 10031.92 | 24.34 | 0.756 | 0.756 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00904 | 34.40 | 0.01447 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 1416.69 | 1416.69 | 0.72 | 0.063 | 0.854 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00796 | -6.30 | 0.00230 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 2612.60 | 2612.60 | 38.95 | 0.116 | 0.116 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00777 | -6.30 | 0.00230 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 864.96 | 864.96 | 11.14 | 0.038 | 0.092 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00774 | -6.30 | 0.00230 | 0.092 | 0.00 |
MECH_FLR_1 | 1567.83 | 1567.83 | 9.55 | 0.070 | 0.070 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00766 | -6.30 | 0.00230 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1050.66 | 1050.66 | 11.09 | 0.047 | 0.058 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00771 | -6.30 | 0.00230 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 2032.64 | 2032.64 | 26.05 | 0.090 | 0.090 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00764 | -6.30 | 0.00230 | 0.000 | 0.00 |
CAFE_FLR_1 | 6642.37 | 6642.37 | 35.17 | 0.295 | 0.676 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00780 | -6.30 | 0.00230 | 0.676 | 0.00 |
LOBBY_FLR_1 | 15493.62 | 15493.62 | 11.84 | 0.689 | 1.894 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00776 | -6.30 | 0.00230 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 5842.76 | 5842.76 | 149.73 | 0.261 | 0.261 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.11 | 21.11 | 0.00777 | -6.30 | 0.00230 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 5855.23 | 5855.23 | 150.07 | 0.262 | 0.262 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.11 | 21.11 | 0.00777 | -6.30 | 0.00230 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 33672.13 | 33672.13 | 1373.04 | 1.506 | 1.506 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.11 | 21.11 | 0.00778 | -6.30 | 0.00230 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 33918.22 | 33918.22 | 1382.69 | 1.517 | 1.517 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.11 | 21.11 | 0.00779 | -6.30 | 0.00230 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 5817.28 | 5817.28 | 149.08 | 0.260 | 0.260 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.11 | 21.11 | 0.00776 | -6.30 | 0.00230 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 5829.75 | 5829.75 | 149.41 | 0.261 | 0.261 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.11 | 21.11 | 0.00777 | -6.30 | 0.00230 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 9276.36 | 9276.36 | 23.82 | 0.412 | 0.475 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00782 | -6.30 | 0.00230 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 1793.87 | 1793.87 | 45.97 | 0.080 | 0.080 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.11 | 21.11 | 0.00781 | -6.30 | 0.00230 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 1798.80 | 1798.80 | 46.10 | 0.080 | 0.080 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.11 | 21.11 | 0.00781 | -6.30 | 0.00230 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8595.98 | 8595.98 | 350.42 | 0.384 | 0.384 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.11 | 21.11 | 0.00781 | -6.30 | 0.00230 | 0.099 | 0.00 |
BANQUET_FLR_6 | 5933.96 | 5933.96 | 17.89 | 0.264 | 1.188 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.00 | 21.00 | 0.00786 | -6.30 | 0.00230 | 1.188 | 0.00 |
DINING_FLR_6 | 6065.28 | 6065.28 | 18.29 | 0.270 | 1.188 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 21.00 | 21.00 | 0.00786 | -6.30 | 0.00230 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 1842.12 | 1842.12 | 17.83 | 0.082 | 0.367 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 21.00 | 21.00 | 0.00664 | -6.30 | 0.00230 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 6259.46 | 6259.46 | 15.19 | 0.278 | 0.278 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 21.00 | 21.00 | 0.00788 | -6.30 | 0.00230 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
FLR_3_DOAS | 17.35 | 2.05 | 4.61 | 2.05 | 2.0513 | 2.0513 | 2.0513 | 1.0000 | 0.3000 |
VAV WITH REHEAT | 21.92 | 21.92 | 7.35 | 7.35 | 21.9250 | 11.6654 | 21.9250 | 0.5321 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 36949.539 | 36949.539 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 36949.54 | 23569.37 | 0.854459 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00796014 | 49.6171 | 1416.69 | 0.00 | -999.00 | -999.00 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 4546.762 | 4546.762 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 4546.76 | 3203.79 | 0.116147 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00777255 | 48.4631 | 2612.60 | 0.00 | -999.00 | -999.00 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 3458.320 | 3458.320 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 3458.32 | 2530.41 | 0.091735 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00773656 | 48.2409 | 864.96 | 0.00 | -999.00 | -999.00 |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 2939.444 | 2939.444 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 2939.44 | 1922.64 | 0.069701 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00766125 | 47.7771 | 1567.83 | 0.00 | -999.00 | -999.00 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 1752.448 | 1752.448 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 1752.45 | 1593.39 | 0.057765 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00770593 | 48.0523 | 1050.66 | 0.00 | -999.00 | -999.00 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Unknown | Unknown | 49198.698 | 49198.698 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 49198.70 | 2492.60 | 0.090364 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00764436 | 47.6735 | 2032.64 | 0.00 | -999.00 | -999.00 |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 20126.762 | 20126.762 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 20126.76 | 18657.50 | 0.676389 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00780121 | 48.6394 | 6642.37 | 0.00 | -999.00 | -999.00 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Unknown | Unknown | 69762.378 | 69762.378 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 69762.38 | 52243.77 | 1.893991 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00775838 | 48.3753 | 15493.62 | 0.00 | -999.00 | -999.00 |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 10997.733 | -999.000 | 1.005324 | 0.00031453 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | 7/21 17:10:00 | 10997.73 | 10669.25 | 1.005324 | 21.70 | 15.31 | 0.00863177 | 12.80 | 11.77 | 0.00850000 | 32.91 | 0.01447054 | 23.14 | 0.0000 | 21.11 | 0.00863177 | 53.3830 | 9899.68 | 0.00 | 11410.79 | 11410.79 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 5842.732 | 5842.732 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 5842.73 | 5668.22 | 0.261275 | 21.70 | 15.31 | 0.00863177 | 12.80 | 11.77 | 0.00850000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.11 | 0.00776555 | 48.0912 | 5842.76 | 0.00 | -999.00 | -999.00 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 10884.737 | -999.000 | 0.994555 | 0.00031130 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | 7/21 17:20:00 | 10884.74 | 10555.71 | 0.994555 | 21.70 | 15.31 | 0.00863341 | 12.80 | 11.77 | 0.00850000 | 32.75 | 0.01447025 | 23.10 | 0.0000 | 21.11 | 0.00863341 | 53.3931 | 9793.63 | 0.00 | 11293.43 | 11293.43 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 5855.198 | 5855.198 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 5855.20 | 5678.20 | 0.261832 | 21.70 | 15.31 | 0.00863341 | 12.80 | 11.77 | 0.00850000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.11 | 0.00776605 | 48.0942 | 5855.23 | 0.00 | -999.00 | -999.00 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 64749.618 | -999.000 | 6.052850 | 0.00185180 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | unknown | 7/21 14:20:00 | 64749.62 | 64009.95 | 6.052850 | 21.70 | 15.24 | 0.00854946 | 12.80 | 11.77 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 0.0000 | 21.11 | 0.00854946 | 52.8792 | 59607.74 | 0.00 | 67211.32 | 67211.32 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 33672.043 | 33672.043 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 33672.04 | 33287.39 | 1.505759 | 21.70 | 15.24 | 0.00854946 | 12.80 | 11.77 | 0.00850000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.11 | 0.00778363 | 48.2011 | 33672.13 | 0.00 | -999.00 | -999.00 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 72723.425 | -999.000 | 6.403863 | 0.00207984 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | unknown | 7/21 15:40:00 | 72723.43 | 68361.02 | 6.403863 | 21.70 | 15.44 | 0.00877311 | 12.80 | 11.77 | 0.00850000 | 34.02 | 0.01447257 | 23.44 | 0.0000 | 21.11 | 0.00877311 | 54.2454 | 63059.55 | 0.00 | 75405.67 | 73177.91 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 33918.128 | 33918.128 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 33918.13 | 31883.51 | 1.516764 | 21.70 | 15.44 | 0.00877311 | 12.80 | 11.77 | 0.00850000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.11 | 0.00778508 | 48.2100 | 33918.22 | 0.00 | -999.00 | -999.00 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 10005.751 | -999.000 | 0.911211 | 0.00028616 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | unknown | 7/21 10:30:00 | 10005.75 | 9676.23 | 0.911211 | 21.70 | 15.33 | 0.00864575 | 12.80 | 11.77 | 0.00850000 | 31.50 | 0.01446797 | 22.76 | 0.0000 | 21.11 | 0.00864575 | 53.4684 | 8972.91 | 0.00 | 10380.56 | 10380.56 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 5817.246 | 5817.246 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 5817.25 | 5625.66 | 0.260135 | 21.70 | 15.33 | 0.00864575 | 12.80 | 11.77 | 0.00850000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.11 | 0.00776457 | 48.0852 | 5817.28 | 0.00 | -999.00 | -999.00 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 9926.345 | -999.000 | 0.903670 | 0.00028389 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | unknown | 7/21 10:20:00 | 9926.34 | 9596.67 | 0.903670 | 21.70 | 15.33 | 0.00864703 | 12.80 | 11.77 | 0.00850000 | 31.26 | 0.01446754 | 22.70 | 0.0000 | 21.11 | 0.00864703 | 53.4762 | 8898.66 | 0.00 | 10298.09 | 10298.09 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 5829.719 | 5829.719 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 5829.72 | 5636.10 | 0.260693 | 21.70 | 15.33 | 0.00864703 | 12.80 | 11.77 | 0.00850000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.11 | 0.00776507 | 48.0882 | 5829.75 | 0.00 | -999.00 | -999.00 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 21824.240 | 21824.240 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21824.24 | 13095.82 | 0.474762 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00781865 | 48.7462 | 9276.36 | 0.00 | -999.00 | -999.00 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 2885.040 | -999.000 | 0.264190 | 0.00008251 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | 7/21 17:00:00 | 2885.04 | 2803.00 | 0.264190 | 21.70 | 15.31 | 0.00862527 | 12.80 | 11.77 | 0.00850000 | 33.07 | 0.01447082 | 23.19 | 0.0000 | 21.11 | 0.00862527 | 53.3434 | 2601.55 | 0.00 | 2993.53 | 2993.53 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 1793.856 | 1793.856 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 1793.86 | 1742.85 | 0.080217 | 21.70 | 15.31 | 0.00862527 | 12.80 | 11.77 | 0.00850000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.11 | 0.00780759 | 48.3483 | 1793.87 | 0.00 | -999.00 | -999.00 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 2852.564 | -999.000 | 0.261102 | 0.00008158 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | 7/21 17:10:00 | 2852.56 | 2770.43 | 0.261102 | 21.70 | 15.31 | 0.00862689 | 12.80 | 11.77 | 0.00850000 | 32.91 | 0.01447054 | 23.14 | 0.0000 | 21.11 | 0.00862689 | 53.3533 | 2571.14 | 0.00 | 2959.80 | 2959.80 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 1798.791 | 1798.791 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 1798.79 | 1747.00 | 0.080438 | 21.70 | 15.31 | 0.00862689 | 12.80 | 11.77 | 0.00850000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.11 | 0.00780811 | 48.3515 | 1798.80 | 0.00 | -999.00 | -999.00 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 13301.158 | -999.000 | 1.194683 | 0.00038040 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | unknown | 7/21 14:20:00 | 13301.16 | 12713.95 | 1.194683 | 21.70 | 15.37 | 0.00869767 | 12.80 | 11.77 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 0.0000 | 21.11 | 0.00869767 | 53.7855 | 11764.10 | 0.00 | 13796.53 | 13796.53 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 8595.944 | 8595.944 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 8595.94 | 8216.46 | 0.384394 | 21.70 | 15.37 | 0.00869767 | 12.80 | 11.77 | 0.00850000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.11 | 0.00781486 | 48.3925 | 8595.98 | 0.00 | -999.00 | -999.00 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Electric | Unknown | Unknown | 32476.320 | 32476.320 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 32476.32 | 32476.32 | 1.187797 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00785588 | 48.9757 | 5933.96 | 0.00 | -999.00 | -999.00 |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Electric | Unknown | Unknown | 34032.624 | 34032.624 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 34032.62 | 32764.15 | 1.187797 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00785893 | 48.9945 | 6065.28 | 0.00 | -999.00 | -999.00 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Electric | Unknown | Unknown | 33678.126 | 33678.126 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 33678.13 | 10132.98 | 0.367350 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00664349 | 41.5039 | 1842.12 | 0.00 | -999.00 | -999.00 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 11031.365 | 11031.365 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 11031.36 | 7676.01 | 0.278278 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00787978 | 49.1227 | 6259.46 | 0.00 | -999.00 | -999.00 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 91161.109 | -999.000 | 2.051317 | 0.00260720 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 91161.11 | 55491.40 | 2.051317 | 34.40 | 23.54 | 0.01447326 | 11.91 | 11.41 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 99.9965 | 21.11 | 0.00866543 | 53.5878 | 170440.71 | 0.00 | 92683.44 | 56170.47 |
FLR_3_DOAS HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | FLR_3_DOAS | 16512.404 | 16512.404 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 16512.40 | 16512.40 | 0.615395 | -6.30 | -6.30 | 0.00229779 | 16.70 | 12.85 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 333.3216 | 21.11 | 0.00778448 | 48.2064 | 103124.01 | 0.00 | -999.00 | -999.00 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 726568.327 | -999.000 | 21.924963 | 0.02077976 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 726568.33 | 482240.34 | 21.924963 | 29.53 | 20.69 | 0.01223873 | 10.92 | 10.92 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 53.1880 | 23.99 | 0.00966658 | 50.1001 | 290737.98 | 0.00 | 741567.41 | 481113.07 |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | VAV WITH REHEAT | 176488.477 | 176488.477 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | 176488.48 | 176488.48 | 6.577489 | -6.30 | -6.30 | 0.00229779 | 16.70 | 12.85 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 177.2935 | 21.02 | 0.00779188 | 48.5241 | 60417.06 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | No | unknown | No | 36949.539 | 36949.539 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 36949.54 | 23569.37 | 1.0000 | 0.99200670 | 0.854459 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 36949.54 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00796014 | 21.00 | 0.00796014 | 49.6171 | 1416.69 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | No | unknown | No | 4546.762 | 4546.762 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 4546.76 | 3203.79 | 1.0000 | 0.13484377 | 0.116147 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4546.76 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00777255 | 21.00 | 0.00777255 | 48.4631 | 2612.60 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | No | unknown | No | 3458.320 | 3458.320 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 3458.32 | 2530.41 | 1.0000 | 0.10650178 | 0.091735 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 3458.32 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00773656 | 21.00 | 0.00773656 | 48.2409 | 864.96 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | No | unknown | No | 2939.444 | 2939.444 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 2939.44 | 1922.64 | 1.0000 | 0.08092157 | 0.069701 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 2939.44 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00766125 | 21.00 | 0.00766125 | 47.7771 | 1567.83 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | No | unknown | No | 1752.448 | 1752.448 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 1752.45 | 1593.39 | 1.0000 | 0.06706399 | 0.057765 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 1752.45 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00770593 | 21.00 | 0.00770593 | 48.0523 | 1050.66 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | No | unknown | No | 49198.698 | 49198.698 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 49198.70 | 2492.60 | 1.0000 | 0.10491042 | 0.090364 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 49198.70 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00764436 | 21.00 | 0.00764436 | 47.6735 | 2032.64 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | No | unknown | No | 20126.762 | 20126.762 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 20126.76 | 18657.50 | 1.0000 | 0.78527220 | 0.676389 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20126.76 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00780121 | 21.00 | 0.00780121 | 48.6394 | 6642.37 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | No | unknown | No | 69762.378 | 69762.378 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 69762.38 | 52243.77 | 1.0000 | 2.19887860 | 1.893991 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 69762.38 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00775838 | 21.00 | 0.00775838 | 48.3753 | 15493.62 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10997.733 | -999.000 | 1.005324 | 0.00031453 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8860 | 1004.8586 | 1.1610 | ROOM_1_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.005324 | 1.16715784 | 4197.9300 | 999.8980 | 29.05599719 | 15.03 | 6.70 | 8.33 | 1016052.10 | 1.0824 | 1.082378 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | unknown | unknown | 7/21 17:10:00 | Sensible | 10997.73 | 10669.25 | 1.0000 | 1.16715784 | 1.005324 | 21.70 | 15.31 | 0.00863177 | 43744.9 | 12.80 | 11.77 | 0.00850000 | 34322.2 | 0.31449580 | 6.70 | 15.03 | 8.33 | 0.000 | 10997.73 | 32.91 | 0.01447054 | 23.14 | 0.00000000 | 0.0000 | 21.11 | 0.00863177 | 21.11 | 0.00863177 | 53.3830 | 9899.68 | 0.00 | 11410.79 | 11410.79 | 1.16715784 | 21.70 | 15.68 | 0.00863177 | 43744.9 | 12.13 | 11.95 | 0.00863177 | 33968.3 | |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | No | unknown | No | 5842.732 | 5842.732 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6411 | 1004.8586 | 1.1610 | ROOM_1_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.005324 | 1.16715784 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 5842.73 | 5668.22 | 1.0000 | 0.30333371 | 0.261275 | 21.70 | 15.31 | 0.00863177 | 43744.9 | 12.80 | 11.77 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5842.73 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00776555 | 21.11 | 0.00776555 | 48.0912 | 5842.76 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10884.737 | -999.000 | 0.994555 | 0.00031130 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8891 | 1004.8586 | 1.1610 | ROOM_2_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.994555 | 1.15465492 | 4197.9300 | 999.8980 | 29.05599719 | 15.03 | 6.70 | 8.33 | 1016052.10 | 1.0713 | 1.071257 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | unknown | unknown | 7/21 17:20:00 | Sensible | 10884.74 | 10555.71 | 1.0000 | 1.15465492 | 0.994555 | 21.70 | 15.31 | 0.00863341 | 43749.0 | 12.80 | 11.77 | 0.00850000 | 34322.2 | 0.31126452 | 6.70 | 15.03 | 8.33 | 0.000 | 10884.74 | 32.75 | 0.01447025 | 23.10 | 0.00000000 | 0.0000 | 21.11 | 0.00863341 | 21.11 | 0.00863341 | 53.3931 | 9793.63 | 0.00 | 11293.43 | 11293.43 | 1.15465492 | 21.70 | 15.68 | 0.00863341 | 43749.0 | 12.12 | 11.95 | 0.00863341 | 33968.2 | |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | No | unknown | No | 5855.198 | 5855.198 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6411 | 1004.8586 | 1.1610 | ROOM_2_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.994555 | 1.15465492 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 5855.20 | 5678.20 | 1.0000 | 0.30398090 | 0.261832 | 21.70 | 15.31 | 0.00863341 | 43749.0 | 12.80 | 11.77 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5855.20 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00776605 | 21.11 | 0.00776605 | 48.0942 | 5855.23 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 64749.618 | -999.000 | 6.052850 | 0.00185180 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7330 | 1004.8586 | 1.1610 | ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 6.052850 | 7.02721654 | 4197.9300 | 999.8980 | 29.05599719 | 15.03 | 6.70 | 8.33 | 1016052.10 | 6.3727 | 6.372548 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | unknown | unknown | unknown | 7/21 14:20:00 | Sensible | 64749.62 | 64009.95 | 1.0000 | 7.02721654 | 6.052850 | 21.70 | 15.24 | 0.00854946 | 43536.3 | 12.80 | 11.77 | 0.00850000 | 34322.2 | 1.85160741 | 6.70 | 15.03 | 8.33 | 0.000 | 64749.62 | 34.40 | 0.01447326 | 23.54 | 0.00000000 | 0.0000 | 21.11 | 0.00854946 | 21.11 | 0.00854946 | 52.8792 | 59607.74 | 0.00 | 67211.32 | 67211.32 | 7.02721654 | 21.70 | 15.61 | 0.00854946 | 43536.3 | 12.33 | 11.96 | 0.00854946 | 33971.9 | |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | No | unknown | No | 33672.043 | 33672.043 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6411 | 1004.8586 | 1.1610 | ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 6.052850 | 7.02721654 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 33672.04 | 33287.39 | 1.0000 | 1.74815113 | 1.505759 | 21.70 | 15.24 | 0.00854946 | 43536.3 | 12.80 | 11.77 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 33672.04 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00778363 | 21.11 | 0.00778363 | 48.2011 | 33672.13 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 72723.425 | -999.000 | 6.403863 | 0.00207984 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1488 | 1004.8586 | 1.1610 | ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 6.403863 | 7.43473502 | 4197.9300 | 999.8980 | 29.05599719 | 15.03 | 6.70 | 8.33 | 1016052.10 | 7.1575 | 7.157317 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | unknown | unknown | unknown | 7/21 15:40:00 | Sensible | 72723.43 | 68361.02 | 1.0000 | 7.43473502 | 6.403863 | 21.70 | 15.44 | 0.00877311 | 44103.8 | 12.80 | 11.77 | 0.00850000 | 34322.2 | 2.07962976 | 6.70 | 15.03 | 8.33 | 0.000 | 72723.43 | 34.02 | 0.01447257 | 23.44 | 0.00000000 | 0.0000 | 21.11 | 0.00877311 | 21.11 | 0.00877311 | 54.2454 | 63059.55 | 0.00 | 75405.67 | 73177.91 | 7.43473502 | 21.70 | 15.80 | 0.00877311 | 44103.8 | 12.06 | 11.95 | 0.00865437 | 33961.4 | |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | No | unknown | No | 33918.128 | 33918.128 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6411 | 1004.8586 | 1.1610 | ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 6.403863 | 7.43473502 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 33918.13 | 31883.51 | 1.0000 | 1.76092714 | 1.516764 | 21.70 | 15.44 | 0.00877311 | 44103.8 | 12.80 | 11.77 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 33918.13 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00778508 | 21.11 | 0.00778508 | 48.2100 | 33918.22 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10005.751 | -999.000 | 0.911211 | 0.00028616 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9120 | 1004.8586 | 1.1610 | ROOM_5_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.911211 | 1.05789454 | 4197.9300 | 999.8980 | 29.05599719 | 15.03 | 6.70 | 8.33 | 1016052.10 | 0.9848 | 0.984749 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | unknown | unknown | unknown | 7/21 10:30:00 | Sensible | 10005.75 | 9676.23 | 1.0000 | 1.05789454 | 0.911211 | 21.70 | 15.33 | 0.00864575 | 43780.4 | 12.80 | 11.77 | 0.00850000 | 34322.2 | 0.28612869 | 6.70 | 15.03 | 8.33 | 0.000 | 10005.75 | 31.50 | 0.01446797 | 22.76 | 0.00000000 | 0.0000 | 21.11 | 0.00864575 | 21.11 | 0.00864575 | 53.4684 | 8972.91 | 0.00 | 10380.56 | 10380.56 | 1.05789454 | 21.70 | 15.69 | 0.00864575 | 43780.4 | 12.09 | 11.95 | 0.00864575 | 33967.9 | |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | No | unknown | No | 5817.246 | 5817.246 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6411 | 1004.8586 | 1.1610 | ROOM_5_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.911211 | 1.05789454 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 5817.25 | 5625.66 | 1.0000 | 0.30201054 | 0.260135 | 21.70 | 15.33 | 0.00864575 | 43780.4 | 12.80 | 11.77 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5817.25 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00776457 | 21.11 | 0.00776457 | 48.0852 | 5817.28 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9926.345 | -999.000 | 0.903670 | 0.00028389 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9144 | 1004.8586 | 1.1610 | ROOM_6_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.903670 | 1.04914013 | 4197.9300 | 999.8980 | 29.05599719 | 15.03 | 6.70 | 8.33 | 1016052.10 | 0.9770 | 0.976934 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | unknown | unknown | unknown | 7/21 10:20:00 | Sensible | 9926.34 | 9596.67 | 1.0000 | 1.04914013 | 0.903670 | 21.70 | 15.33 | 0.00864703 | 43783.6 | 12.80 | 11.77 | 0.00850000 | 34322.2 | 0.28385794 | 6.70 | 15.03 | 8.33 | 0.000 | 9926.34 | 31.26 | 0.01446754 | 22.70 | 0.00000000 | 0.0000 | 21.11 | 0.00864703 | 21.11 | 0.00864703 | 53.4762 | 8898.66 | 0.00 | 10298.09 | 10298.09 | 1.04914013 | 21.70 | 15.69 | 0.00864703 | 43783.6 | 12.09 | 11.95 | 0.00864703 | 33967.9 | |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | No | unknown | No | 5829.719 | 5829.719 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6411 | 1004.8586 | 1.1610 | ROOM_6_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.903670 | 1.04914013 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 5829.72 | 5636.10 | 1.0000 | 0.30265813 | 0.260693 | 21.70 | 15.33 | 0.00864703 | 43783.6 | 12.80 | 11.77 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5829.72 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00776507 | 21.11 | 0.00776507 | 48.0882 | 5829.75 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | No | unknown | No | 21824.240 | 21824.240 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 21824.24 | 13095.82 | 1.0000 | 0.55118776 | 0.474762 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21824.24 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00781865 | 21.00 | 0.00781865 | 48.7462 | 9276.36 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2885.040 | -999.000 | 0.264190 | 0.00008251 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8739 | 1004.8586 | 1.1610 | ROOM_1_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.264190 | 0.30671836 | 4197.9300 | 999.8980 | 29.05599719 | 15.03 | 6.70 | 8.33 | 1016052.10 | 0.2839 | 0.283941 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | unknown | unknown | 7/21 17:00:00 | Sensible | 2885.04 | 2803.00 | 1.0000 | 0.30671836 | 0.264190 | 21.70 | 15.31 | 0.00862527 | 43728.3 | 12.80 | 11.77 | 0.00850000 | 34322.2 | 0.08250182 | 6.70 | 15.03 | 8.33 | 0.000 | 2885.04 | 33.07 | 0.01447082 | 23.19 | 0.00000000 | 0.0000 | 21.11 | 0.00862527 | 21.11 | 0.00862527 | 53.3434 | 2601.55 | 0.00 | 2993.53 | 2993.53 | 0.30671836 | 21.70 | 15.67 | 0.00862527 | 43728.3 | 12.14 | 11.95 | 0.00862527 | 33968.5 | |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | No | unknown | No | 1793.856 | 1793.856 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6411 | 1004.8586 | 1.1610 | ROOM_1_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.264190 | 0.30671836 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 1793.86 | 1742.85 | 1.0000 | 0.09313062 | 0.080217 | 21.70 | 15.31 | 0.00862527 | 43728.3 | 12.80 | 11.77 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 1793.86 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00780759 | 21.11 | 0.00780759 | 48.3483 | 1793.87 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2852.564 | -999.000 | 0.261102 | 0.00008158 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8770 | 1004.8586 | 1.1610 | ROOM_2_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.261102 | 0.30313301 | 4197.9300 | 999.8980 | 29.05599719 | 15.03 | 6.70 | 8.33 | 1016052.10 | 0.2807 | 0.280745 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | unknown | unknown | 7/21 17:10:00 | Sensible | 2852.56 | 2770.43 | 1.0000 | 0.30313301 | 0.261102 | 21.70 | 15.31 | 0.00862689 | 43732.5 | 12.80 | 11.77 | 0.00850000 | 34322.2 | 0.08157312 | 6.70 | 15.03 | 8.33 | 0.000 | 2852.56 | 32.91 | 0.01447054 | 23.14 | 0.00000000 | 0.0000 | 21.11 | 0.00862689 | 21.11 | 0.00862689 | 53.3533 | 2571.14 | 0.00 | 2959.80 | 2959.80 | 0.30313301 | 21.70 | 15.67 | 0.00862689 | 43732.5 | 12.14 | 11.95 | 0.00862689 | 33968.4 | |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | No | unknown | No | 1798.791 | 1798.791 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6411 | 1004.8586 | 1.1610 | ROOM_2_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.261102 | 0.30313301 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 1798.79 | 1747.00 | 1.0000 | 0.09338682 | 0.080438 | 21.70 | 15.31 | 0.00862689 | 43732.5 | 12.80 | 11.77 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 1798.79 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00780811 | 21.11 | 0.00780811 | 48.3515 | 1798.80 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13301.158 | -999.000 | 1.194683 | 0.00038040 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0085 | 1004.8586 | 1.1610 | ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 1.194683 | 1.38699860 | 4197.9300 | 999.8980 | 29.05599719 | 15.03 | 6.70 | 8.33 | 1016052.10 | 1.3091 | 1.309077 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | unknown | unknown | unknown | 7/21 14:20:00 | Sensible | 13301.16 | 12713.95 | 1.0000 | 1.38699860 | 1.194683 | 21.70 | 15.37 | 0.00869767 | 43912.1 | 12.80 | 11.77 | 0.00850000 | 34322.2 | 0.38036551 | 6.70 | 15.03 | 8.33 | 0.000 | 13301.16 | 34.40 | 0.01447326 | 23.54 | 0.00000000 | 0.0000 | 21.11 | 0.00869767 | 21.11 | 0.00869767 | 53.7855 | 11764.10 | 0.00 | 13796.53 | 13796.53 | 1.38699860 | 21.70 | 15.74 | 0.00869767 | 43912.1 | 11.96 | 11.95 | 0.00869767 | 33965.0 | |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | No | unknown | No | 8595.944 | 8595.944 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6411 | 1004.8586 | 1.1610 | ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 1.194683 | 1.38699860 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 8595.94 | 8216.46 | 1.0000 | 0.44627244 | 0.384394 | 21.70 | 15.37 | 0.00869767 | 43912.1 | 12.80 | 11.77 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8595.94 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00781486 | 21.11 | 0.00781486 | 48.3925 | 8595.98 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Electric | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | No | unknown | No | 32476.320 | 32476.320 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 32476.32 | 32476.32 | 1.0000 | 1.37900446 | 1.187797 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32476.32 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00785588 | 21.00 | 0.00785588 | 48.9757 | 5933.96 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Electric | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | No | unknown | No | 34032.624 | 34032.624 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | Sensible | 34032.62 | 32764.15 | 1.0000 | 1.37900446 | 1.187797 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 34032.62 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00785893 | 21.00 | 0.00785893 | 48.9945 | 6065.28 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Electric | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | No | unknown | No | 33678.126 | 33678.126 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | Sensible | 33678.13 | 10132.98 | 1.0000 | 0.42648515 | 0.367350 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 33678.13 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.44 | 0.00664349 | 21.00 | 0.00664349 | 41.5039 | 1842.12 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | No | unknown | No | 11031.365 | 11031.365 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | Sensible | 11031.36 | 7676.01 | 1.0000 | 0.32307423 | 0.278278 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11031.36 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00787978 | 21.00 | 0.00787978 | 49.1227 | 6259.46 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 91161.109 | -999.000 | 2.051317 | 0.00260720 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1031.7451 | 1004.8586 | 1.1610 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.38144746 | 4197.9300 | 999.8980 | 29.05599719 | 15.03 | 6.70 | 8.33 | 1016052.10 | 8.9721 | 8.972090 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | Sensible | 91161.11 | 55491.40 | 1.0000 | 2.38153119 | 2.051317 | 34.40 | 23.54 | 0.01447326 | 71688.8 | 11.91 | 11.41 | 0.00850000 | 33410.4 | 2.60693021 | 6.70 | 15.03 | 8.33 | 2195.006 | 88966.10 | 34.40 | 0.01447326 | 23.54 | 2.05124512 | 99.9965 | 21.11 | 0.00866616 | 21.11 | 0.00866543 | 53.5878 | 170440.71 | 0.00 | 92683.44 | 56170.47 | 2.38153119 | 34.40 | 23.99 | 0.01447326 | 71688.8 | 11.54 | 11.47 | 0.00839502 | 32771.2 | |
FLR_3_DOAS HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 16512.404 | 16512.404 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.38144746 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 16512.40 | 16512.40 | 1.0000 | 0.71445936 | 0.615395 | -6.30 | -6.30 | 0.00229779 | -610.8 | 16.70 | 12.85 | 0.00800000 | 37036.7 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16512.40 | -6.30 | 0.00229779 | -6.30 | 2.05124512 | 333.3216 | 21.11 | 0.00778340 | 21.11 | 0.00778448 | 48.2064 | 103124.01 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 726568.327 | -999.000 | 21.924963 | 0.02077976 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1027.5912 | 1004.8586 | 1.1610 | VAV WITH REHEAT FAN | Fan:VariableVolume | 21.924963 | 25.45436779 | 4197.9300 | 999.8980 | 29.05599719 | 15.03 | 6.70 | 8.33 | 1016052.10 | 71.5090 | 71.508963 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | Sensible | 726568.33 | 482240.34 | 1.0000 | 25.45436779 | 21.924963 | 29.53 | 20.69 | 0.01223873 | 60949.2 | 10.92 | 10.92 | 0.00850000 | 32405.3 | 20.77764242 | 6.70 | 15.03 | 8.33 | 49125.919 | 677442.41 | 34.40 | 0.01447326 | 23.54 | 11.66146000 | 53.1880 | 23.99 | 0.00969983 | 23.99 | 0.00966658 | 50.1001 | 290737.98 | 0.00 | 741567.41 | 481113.07 | 25.45436779 | 29.53 | 21.11 | 0.01223873 | 60949.2 | 11.13 | 11.07 | 0.00818096 | 31816.0 | |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 176488.477 | 176488.477 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | VAV WITH REHEAT FAN | Fan:VariableVolume | 21.924963 | 25.45436779 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | Sensible | 176488.48 | 176488.48 | 1.0000 | 7.63631034 | 6.577489 | -6.30 | -6.30 | 0.00229779 | -610.8 | 16.70 | 12.85 | 0.00800000 | 37036.7 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 176488.48 | -6.30 | 0.00229779 | -6.30 | 11.66146000 | 177.2935 | 20.97 | 0.00776472 | 21.02 | 0.00779188 | 48.5241 | 60417.06 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - | |||
VAV WITH REHEAT_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 21.92 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | VAV WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000610 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LAUNDRY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CAFE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001448 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_3 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
KITCHEN_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003556 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 75.67 | 8710.17 | 75.67 |
RETAIL_1_FLR_1 | 1527.83 | 7674.17 | 983.33 |
RETAIL_2_FLR_1 | 296.00 | 8191.50 | 87.67 |
MECH_FLR_1 | 989.17 | 8707.50 | 989.17 |
STORAGE_FLR_1 | 1126.83 | 8760.00 | 1126.83 |
LAUNDRY_FLR_1 | 4766.50 | 3962.17 | 1770.83 |
CAFE_FLR_1 | 1808.67 | 6438.17 | 293.33 |
LOBBY_FLR_1 | 705.50 | 7487.33 | 10.00 |
ROOM_1_FLR_3 | 1017.67 | 8291.17 | 1016.00 |
ROOM_2_FLR_3 | 1871.50 | 8193.00 | 1814.17 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 1043.00 | 8741.33 | 1042.33 |
ROOM_5_FLR_3 | 970.33 | 8220.00 | 969.33 |
ROOM_6_FLR_3 | 1855.67 | 8135.00 | 1780.17 |
CORRIDOR_FLR_3 | 576.67 | 8760.00 | 576.67 |
ROOM_1_FLR_6 | 1692.17 | 8079.67 | 1655.83 |
ROOM_2_FLR_6 | 2535.83 | 7937.67 | 2409.50 |
ROOM_3_MULT9_FLR_6 | 589.83 | 8203.00 | 585.00 |
BANQUET_FLR_6 | 3779.50 | 4561.17 | 606.33 |
DINING_FLR_6 | 4553.67 | 3385.17 | 281.67 |
KITCHEN_FLR_6 | 7690.83 | 6880.67 | 6108.33 |
CORRIDOR_FLR_6 | 935.67 | 8227.83 | 856.00 |
Facility | 8430.00 | 8760.00 | 7619.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 2.33 | 1.17 | 2.33 | 1.17 |
ROOM_2_FLR_3 | 4.33 | 3.17 | 4.33 | 3.17 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 1.00 | 12.83 | 1.00 | 12.83 |
ROOM_5_FLR_3 | 1.67 | 0.33 | 1.67 | 0.33 |
ROOM_6_FLR_3 | 3.33 | 22.83 | 3.33 | 22.83 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 2.00 | 6.50 | 2.00 | 6.50 |
ROOM_2_FLR_6 | 3.83 | 9.83 | 3.83 | 9.83 |
ROOM_3_MULT9_FLR_6 | 0.33 | 12.67 | 0.33 | 12.67 |
BANQUET_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 1.17 | 0.00 | 1.17 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 5.83 | 47.83 | 5.83 | 47.83 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.79 | 106.50 | 4826.41 | 0.997 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 2.226 | 0.061 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.28 | 12.54 | 307.76 | 1.463 | 0.020 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.587 | 0.023 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.607 | 0.023 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 21.995 | 0.065 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.56 | 142.30 | 748.35 | 3.512 | 0.048 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.09 | 422.44 | 5183.56 | 1.756 | 0.020 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.354 | 0.079 | 0.000 | 0.068 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.355 | 0.079 | 0.000 | 0.069 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.403 | 0.035 | 0.000 | 0.108 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.354 | 0.079 | 0.000 | 0.068 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.355 | 0.079 | 0.000 | 0.068 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 0.598 | 0.010 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.354 | 0.079 | 0.000 | 0.081 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.355 | 0.079 | 0.000 | 0.081 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.403 | 0.064 | 0.000 | 0.130 |
BANQUET_FLR_6 | 144.99 | 249.90 | 1010.89 | 4.341 | 0.023 | 0.000 | 0.000 |
DINING_FLR_6 | 144.99 | 249.90 | 1010.89 | 4.597 | 0.023 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 18.296 | 0.065 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 1.142 | 0.016 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.79 | 106.50 | 4826.41 | 0.875 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 1.956 | 0.001 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.28 | 12.54 | 307.76 | 1.288 | 0.000 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.516 | 0.000 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.533 | 0.000 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 18.309 | 0.001 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.56 | 142.30 | 748.35 | 3.141 | 0.001 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.09 | 422.44 | 5183.56 | 1.544 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 0.525 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.000 | 0.001 | 0.000 | 0.000 |
BANQUET_FLR_6 | 144.99 | 249.90 | 1010.89 | 4.096 | 0.000 | 0.000 | 0.000 |
DINING_FLR_6 | 144.99 | 249.90 | 1010.89 | 4.292 | 0.000 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 12.450 | 0.001 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 1.003 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | VAV WITH REHEAT | 61.79 | 106.50 | 4826.41 | 1978.83 | 0.0000 | 0.854 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 6.28 | 10.83 | 265.76 | 67.07 | 0.0000 | 0.079 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 7.28 | 12.54 | 307.76 | 77.67 | 0.0000 | 0.092 |
MECH_FLR_1 | VAV WITH REHEAT | 1.54 | 2.65 | 650.80 | 164.24 | 0.0000 | 0.000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 1.18 | 2.04 | 375.47 | 94.76 | 0.0000 | 0.058 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 4.87 | 8.40 | 309.22 | 78.04 | 0.0000 | 0.000 |
CAFE_FLR_1 | VAV WITH REHEAT | 82.56 | 142.30 | 748.35 | 188.86 | 0.0000 | 0.676 |
LOBBY_FLR_1 | VAV WITH REHEAT | 245.09 | 422.44 | 5183.56 | 1308.19 | 0.0000 | 1.894 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 1.50 | 74.75 | 24.52 | 0.0000 | 0.837 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.837 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 12.16 | 20.96 | 1186.91 | 389.40 | 0.0000 | 0.475 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.015 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.015 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.099 |
BANQUET_FLR_6 | VAV WITH REHEAT | 144.99 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
DINING_FLR_6 | VAV WITH REHEAT | 144.99 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 12.90 | 22.24 | 314.87 | 103.30 | 0.0000 | 0.367 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 12.87 | 22.18 | 1256.16 | 412.12 | 0.0000 | 0.126 |
Total Facility | 873.25 | 1604.23 | 35184.81 | 11345.29 | 0.0000 | 137.584 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 41614233.11 | 0.00 | 41614233.11 | 0.00 | 41614233.11 | 26946214.98 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_1_FLR_1 | 5123380.94 | 0.00 | 5123380.94 | 139599.38 | 5262980.33 | 2498216.28 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_2_FLR_1 | 3895567.13 | 0.00 | 3895567.13 | 53885.54 | 3949452.66 | 2892943.94 | 0.00 | 0.00 | 8760.00 | 0.00 |
MECH_FLR_1 | 3310533.53 | 0.00 | 3310533.53 | 127353.40 | 3437886.94 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
STORAGE_FLR_1 | 1973685.20 | 0.00 | 1973685.20 | 73475.90 | 2047161.10 | 1821682.01 | 546.92 | 563.84 | 7649.23 | 0.00 |
LAUNDRY_FLR_1 | 58857480.62 | 0.00 | 58857480.62 | 173894.57 | 59031375.19 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
CAFE_FLR_1 | 22683967.97 | 0.00 | 22683967.97 | 308592.34 | 22992560.31 | 21330615.53 | 1054.48 | 136.14 | 7569.38 | 0.00 |
LOBBY_FLR_1 | 78587482.44 | 0.00 | 78587482.44 | 881718.81 | 79469201.25 | 59728886.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
ROOM_1_FLR_3 | 1460156.71 | 69884.89 | 1530041.60 | 81027.53 | 1611069.13 | 1946875.62 | 2190.00 | 5688.17 | 881.83 | 0.00 |
ROOM_2_FLR_3 | 1459985.63 | 70470.89 | 1530456.53 | 81021.35 | 1611477.87 | 1946647.51 | 2190.00 | 5693.64 | 876.36 | 0.00 |
ROOM_3_MULT19_FLR_3 | 1099911.97 | 3238.90 | 1103150.87 | 22607.59 | 1125758.46 | 26397887.27 | 8395.00 | 365.00 | 0.00 | 396.50 |
ROOM_4_MULT19_FLR_3 | 19803829.30 | 69793.03 | 19873622.32 | 22613.77 | 19896236.10 | 26405105.73 | 2190.00 | 5735.86 | 834.14 | 0.00 |
ROOM_5_FLR_3 | 1460156.71 | 69911.68 | 1530068.39 | 81027.53 | 1611095.92 | 1946875.62 | 2190.00 | 5688.17 | 881.83 | 0.00 |
ROOM_6_FLR_3 | 1459985.63 | 69899.78 | 1529885.42 | 81021.35 | 1610906.76 | 1946647.51 | 2190.00 | 5688.25 | 881.75 | 0.00 |
CORRIDOR_FLR_3 | 24579440.53 | 0.00 | 24579440.53 | 97978.58 | 24677419.12 | 14972100.18 | 0.00 | 0.00 | 8760.00 | 0.00 |
ROOM_1_FLR_6 | 365039.18 | 83673.10 | 448712.28 | 81044.19 | 529756.47 | 486718.90 | 1994.39 | 5687.87 | 1077.74 | 0.00 |
ROOM_2_FLR_6 | 364996.41 | 82646.68 | 447643.09 | 81038.01 | 528681.10 | 486661.88 | 1996.21 | 5702.33 | 1061.47 | 0.00 |
ROOM_3_MULT9_FLR_6 | 2345190.31 | 83737.08 | 2428927.39 | 41465.04 | 2470392.44 | 3126920.42 | 2190.00 | 5684.17 | 885.83 | 0.00 |
BANQUET_FLR_6 | 37737821.66 | 0.00 | 37737821.66 | 197889.55 | 37935711.21 | 37458366.31 | 371.85 | 7157.85 | 1230.30 | 0.00 |
DINING_FLR_6 | 39941030.74 | 0.00 | 39941030.74 | 197889.55 | 40138920.29 | 37458366.31 | 0.00 | 0.12 | 8759.88 | 0.00 |
KITCHEN_FLR_6 | 49467332.92 | 0.00 | 49467332.92 | 177157.02 | 49644489.95 | 11584760.86 | 0.00 | 0.00 | 8760.00 | 0.00 |
CORRIDOR_FLR_6 | 12424551.80 | 0.00 | 12424551.80 | 173391.41 | 12597943.20 | 3961413.96 | 0.00 | 0.00 | 8760.00 | 0.00 |
Total Facility | 0.21E+10 | 7591049.44 | 0.21E+10 | 8165243.82 | 0.21E+10 | 0.43E+10 | 8760.00 | 8551.32 | 8760.00 | 396.50 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 1.3196 | 0.0000 | 1.3196 | 0.0000 | 1.3196 | 0.8545 | 0.00 | 0.00 | 8760.00 |
RETAIL_1_FLR_1 | 0.1625 | 0.0000 | 0.1625 | 0.0044 | 0.1669 | 0.0792 | 0.00 | 0.00 | 8760.00 |
RETAIL_2_FLR_1 | 0.1235 | 0.0000 | 0.1235 | 0.0017 | 0.1252 | 0.0917 | 0.00 | 0.00 | 8760.00 |
MECH_FLR_1 | 0.1050 | 0.0000 | 0.1050 | 0.0040 | 0.1090 | 0.0000 | 0.00 | 0.00 | 8760.00 |
STORAGE_FLR_1 | 0.0626 | 0.0000 | 0.0626 | 0.0023 | 0.0649 | 0.0578 | 546.92 | 563.84 | 7649.23 |
LAUNDRY_FLR_1 | 1.8664 | 0.0000 | 1.8664 | 0.0055 | 1.8719 | 0.0000 | 0.00 | 0.00 | 8760.00 |
CAFE_FLR_1 | 0.7193 | 0.0000 | 0.7193 | 0.0098 | 0.7291 | 0.6764 | 1054.48 | 136.14 | 7569.38 |
LOBBY_FLR_1 | 2.4920 | 0.0000 | 2.4920 | 0.0280 | 2.5200 | 1.8940 | 0.00 | 0.00 | 8760.00 |
ROOM_1_FLR_3 | 0.0463 | 0.0022 | 0.0485 | 0.0026 | 0.0511 | 0.0617 | 2190.00 | 5688.17 | 881.83 |
ROOM_2_FLR_3 | 0.0463 | 0.0022 | 0.0485 | 0.0026 | 0.0511 | 0.0617 | 2190.00 | 5693.64 | 876.36 |
ROOM_4_MULT19_FLR_3 | 0.6280 | 0.0022 | 0.6302 | 0.0007 | 0.6309 | 0.8373 | 2190.00 | 5735.86 | 834.14 |
ROOM_5_FLR_3 | 0.0463 | 0.0022 | 0.0485 | 0.0026 | 0.0511 | 0.0617 | 2190.00 | 5688.17 | 881.83 |
ROOM_6_FLR_3 | 0.0463 | 0.0022 | 0.0485 | 0.0026 | 0.0511 | 0.0617 | 2190.00 | 5688.25 | 881.75 |
CORRIDOR_FLR_3 | 0.7794 | 0.0000 | 0.7794 | 0.0031 | 0.7825 | 0.4748 | 0.00 | 0.00 | 8760.00 |
ROOM_1_FLR_6 | 0.0116 | 0.0027 | 0.0142 | 0.0026 | 0.0168 | 0.0154 | 1994.39 | 5687.87 | 1077.74 |
ROOM_2_FLR_6 | 0.0116 | 0.0026 | 0.0142 | 0.0026 | 0.0168 | 0.0154 | 1996.21 | 5702.33 | 1061.47 |
ROOM_3_MULT9_FLR_6 | 0.0744 | 0.0027 | 0.0770 | 0.0013 | 0.0783 | 0.0992 | 2190.00 | 5684.17 | 885.83 |
BANQUET_FLR_6 | 1.1967 | 0.0000 | 1.1967 | 0.0063 | 1.2029 | 1.1878 | 371.85 | 7157.85 | 1230.30 |
DINING_FLR_6 | 1.2665 | 0.0000 | 1.2665 | 0.0063 | 1.2728 | 1.1878 | 0.00 | 0.12 | 8759.88 |
KITCHEN_FLR_6 | 1.5686 | 0.0000 | 1.5686 | 0.0056 | 1.5742 | 0.3674 | 0.00 | 0.00 | 8760.00 |
CORRIDOR_FLR_6 | 0.3940 | 0.0000 | 0.3940 | 0.0055 | 0.3995 | 0.1256 | 0.00 | 0.00 | 8760.00 |
Total Facility | 63.5535 | 0.2329 | 63.7864 | 0.2044 | 63.9909 | 73.9670 | 8760.00 | 8551.32 | 8760.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
FLR_3_DOAS | 40192371.46 | 603256.04 | 40795627.50 | 64690340.46 | 8759.50 | 0.17 | 0.33 | 0.00 |
VAV WITH REHEAT | 0.51E+09 | 0.00 | 0.51E+09 | 0.22E+09 | 0.00 | 0.00 | 8760.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
FLR_3_DOAS | 1.2745 | 0.0191 | 1.2936 | 2.0513 | 8759.50 | 0.17 | 0.33 |
VAV WITH REHEAT | 16.2499 | 0.0000 | 16.2499 | 6.9969 | 0.00 | 0.00 | 8760.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
FLR_3_DOAS | 0.00 | 0.00 | 0.00 | 0.00 | 6935.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
VAV WITH REHEAT | 0.00 | 0.00 | 4461.31 | 0.00 | 0.00 | 0.00 | 4298.69 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
FLR_3_DOAS | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.6099 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
VAV WITH REHEAT | 0.0000 | 0.0000 | 16.3485 | 0.0000 | 0.0000 | 0.0000 | 16.1512 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1269 |
Defaulted Fields | 1144 |
Fields with Defaults | 3760 |
Autosized Fields | 294 |
Autosizable Fields | 344 |
Autocalculated Fields | 279 |
Autocalculatable Fields | 538 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 6510.00 | 84331.70 | 28-FEB-03:20 | 403863.18 | 03-JAN-07:40 |
Electricity:Building | 2448.61 | 31501.02 | 02-JAN-02:10 | 151313.73 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 304.40 | 3493.55 | 02-JAN-02:10 | 22822.84 | 02-JAN-20:10 |
Electricity:SpaceType:GENERAL | 2441.52 | 31359.87 | 02-JAN-02:10 | 151072.40 | 02-JAN-20:10 |
InteriorLights:Electricity | 783.34 | 7157.90 | 02-JAN-02:10 | 64632.59 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 161.29 | 1465.65 | 02-JAN-02:10 | 13190.31 | 02-JAN-20:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 783.34 | 7157.90 | 02-JAN-02:10 | 64632.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 783.34 | 7157.90 | 02-JAN-02:10 | 64632.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 161.29 | 1465.65 | 02-JAN-02:10 | 13190.31 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 783.34 | 7157.90 | 02-JAN-02:10 | 64632.59 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 17.49 | 210.74 | 02-JAN-02:10 | 1283.20 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 7.31 | 66.40 | 02-JAN-02:10 | 597.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 7.31 | 66.40 | 02-JAN-02:10 | 597.59 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 20.26 | 244.03 | 02-JAN-02:10 | 1485.95 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 8.46 | 76.89 | 02-JAN-02:10 | 692.02 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 8.46 | 76.89 | 02-JAN-02:10 | 692.02 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 20.84 | 252.75 | 02-JAN-02:10 | 1523.62 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.37 | 76.02 | 02-JAN-02:10 | 684.18 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.37 | 76.02 | 02-JAN-02:10 | 684.18 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 6.68 | 78.96 | 02-JAN-02:10 | 493.99 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 3.08 | 27.98 | 02-JAN-02:10 | 251.84 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 3.08 | 27.98 | 02-JAN-02:10 | 251.84 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 71.91 | 998.82 | 02-JAN-02:10 | 4897.88 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 3.98 | 36.12 | 02-JAN-02:10 | 325.08 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 3.98 | 36.12 | 02-JAN-02:10 | 325.08 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 28.61 | 388.01 | 01-JAN-13:10 | 2666.80 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 14.27 | 83.19 | 01-JAN-13:10 | 1701.53 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 | 14.27 | 83.19 | 01-JAN-13:10 | 1701.53 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 259.23 | 3167.50 | 02-JAN-02:10 | 19534.01 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 110.23 | 1056.09 | 02-JAN-02:10 | 9504.80 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 110.23 | 1056.09 | 02-JAN-02:10 | 9504.80 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 19.72 | 257.38 | 01-JAN-02:10 | 1438.51 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 19.72 | 257.35 | 01-JAN-02:10 | 1438.34 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 305.38 | 4267.82 | 01-JAN-02:10 | 22404.45 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 110.39 | 934.58 | 01-JAN-02:10 | 8496.21 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 110.39 | 934.58 | 01-JAN-02:10 | 8496.21 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 305.47 | 4268.99 | 01-JAN-02:10 | 22410.58 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 110.42 | 934.84 | 01-JAN-02:10 | 8498.53 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 110.42 | 934.84 | 01-JAN-02:10 | 8498.53 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 19.72 | 257.38 | 01-JAN-02:10 | 1438.51 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 19.72 | 257.35 | 01-JAN-02:10 | 1438.34 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 4.93 | 64.34 | 01-JAN-02:10 | 359.63 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 2.31 | 19.57 | 01-JAN-02:10 | 177.88 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 2.31 | 19.57 | 01-JAN-02:10 | 177.88 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 4.93 | 64.34 | 01-JAN-02:10 | 359.59 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 2.31 | 19.56 | 01-JAN-02:10 | 177.86 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 2.31 | 19.56 | 01-JAN-02:10 | 177.86 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 36.17 | 505.54 | 01-JAN-02:10 | 2653.88 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 13.08 | 110.70 | 01-JAN-02:10 | 1006.40 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 13.08 | 110.70 | 01-JAN-02:10 | 1006.40 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 207.06 | 2581.30 | 02-JAN-02:10 | 9735.93 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 31.20 | 332.00 | 02-JAN-02:10 | 2988.03 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 31.20 | 332.00 | 02-JAN-02:10 | 2988.03 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 207.06 | 2581.30 | 02-JAN-02:10 | 9735.93 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 31.20 | 332.00 | 02-JAN-02:10 | 2988.03 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 | 31.20 | 332.00 | 02-JAN-02:10 | 2988.03 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 453.81 | 6249.79 | 02-JAN-02:10 | 18934.39 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 12.97 | 117.87 | 02-JAN-02:10 | 1060.81 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 12.97 | 117.87 | 02-JAN-02:10 | 1060.81 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1658.18 | 24201.97 | 02-JAN-02:10 | 89171.45 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 1658.18 | 24201.97 | 02-JAN-02:10 | 89171.45 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 433.74 | 5990.78 | 01-JAN-00:10 | 16487.34 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 410.33 | 5248.28 | 01-JAN-00:10 | 15744.84 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
Refrigeration:Electricity | 61.52 | 1105.23 | 03-DEC-23:30 | 3253.40 | 20-JAN-07:30 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
Electricity:Plant | 1684.03 | 2546.81 | 18-MAR-02:20 | 187445.55 | 06-JUL-18:10 |
LowTempRefrigeration:Refrigeration:Electricity | 20.22 | 0.00 | 01-JAN-11:10 | 1907.61 | 15-APR-10:40 |
MedTempRefrigeration:Refrigeration:Electricity | 34.21 | 927.64 | 20-MAR-02:40 | 1192.28 | 17-FEB-14:10 |
Fans:Electricity | 451.94 | 10962.99 | 07-JAN-08:10 | 25689.69 | 07-JUL-18:20 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 1391.35 | 12679.17 | 24-SEP-05:20 | 233502.11 | 03-JAN-16:10 |
ExteriorEquipment:Electricity | 813.77 | 9999.82 | 02-JAN-02:20 | 49607.07 | 02-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 21.77 | 381.02 | 02-JAN-02:20 | 1291.59 | 02-JAN-21:10 |
ElectricityPurchased:Facility | 6510.00 | 84331.70 | 28-FEB-03:20 | 403863.18 | 03-JAN-07:40 |
ElectricityPurchased:Plant | 6510.00 | 84331.70 | 28-FEB-03:20 | 403863.18 | 03-JAN-07:40 |
Cogeneration:ElectricityPurchased | 6510.00 | 84331.70 | 28-FEB-03:20 | 403863.18 | 03-JAN-07:40 |
General:Cogeneration:ElectricityPurchased | 6510.00 | 84331.70 | 28-FEB-03:20 | 403863.18 | 03-JAN-07:40 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 6510.00 | 84331.70 | 28-FEB-03:20 | 403863.18 | 03-JAN-07:40 |
ElectricityNet:Plant | 6510.00 | 84331.70 | 28-FEB-03:20 | 403863.18 | 03-JAN-07:40 |
Cogeneration:ElectricityNet | 6510.00 | 84331.70 | 28-FEB-03:20 | 403863.18 | 03-JAN-07:40 |
General:Cogeneration:ElectricityNet | 6510.00 | 84331.70 | 28-FEB-03:20 | 403863.18 | 03-JAN-07:40 |
Heating:Electricity | 765.43 | 0.00 | 21-FEB-20:30 | 212663.19 | 03-JAN-16:10 |
General:Heating:Electricity | 765.43 | 0.00 | 21-FEB-20:30 | 212663.19 | 03-JAN-16:10 |
General:Fans:Electricity | 451.94 | 10962.99 | 07-JAN-08:10 | 25689.69 | 07-JUL-18:20 |
ExteriorLights:Electricity | 194.02 | 0.00 | 01-JAN-07:50 | 12338.45 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 194.02 | 0.00 | 01-JAN-07:50 | 12338.45 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 789.09 | 9600.00 | 01-JAN-00:10 | 48128.80 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 2.91 | 18.80 | 01-JAN-00:10 | 188.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 152.20 | 0.00 | 01-JAN-08:10 | 9938.94 | 06-MAY-09:00 |
General:HeatRecovery:Electricity | 152.20 | 0.00 | 01-JAN-08:10 | 9938.94 | 06-MAY-09:00 |
WaterSystems:Electricity | 94.80 | 1222.69 | 22-JUL-00:10 | 4751.85 | 13-FEB-07:10 |
Water Heater:WaterSystems:Electricity | 94.80 | 1222.69 | 22-JUL-00:10 | 4751.85 | 13-FEB-07:10 |
Cooling:Electricity | 1440.55 | 0.00 | 01-JAN-00:10 | 176077.58 | 06-JUL-18:10 |
General:Cooling:Electricity | 1440.55 | 0.00 | 01-JAN-00:10 | 176077.58 | 06-JUL-18:10 |
Pumps:Electricity | 94.26 | 47.91 | 02-JAN-18:10 | 4670.58 | 18-JUL-19:00 |
General:Pumps:Electricity | 94.26 | 47.91 | 02-JAN-18:10 | 4670.58 | 18-JUL-19:00 |
WIRED_LTG_ELECTRICITY | 27.57 | 0.00 | 01-JAN-00:10 | 2275.07 | 02-JAN-20:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 4241.07 | 23554.00 | 05-AUG-01:30 | 342425.84 | 03-FEB-18:20 |
NaturalGas:Building | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Laundry:InteriorEquipment:NaturalGas | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
NaturalGas:Plant | 2452.23 | 10192.10 | 05-AUG-01:30 | 240345.44 | 01-FEB-21:20 |
WaterSystems:NaturalGas | 2452.23 | 10192.10 | 05-AUG-01:30 | 240345.44 | 01-FEB-21:20 |
Water Heater:WaterSystems:NaturalGas | 2452.23 | 10192.10 | 05-AUG-01:30 | 240345.44 | 01-FEB-21:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 5760.84 | 0.00 | 01-JAN-00:10 | 638396.01 | 25-JUL-22:00 |
PlantLoopCoolingDemand:HVAC | 5760.84 | 0.00 | 01-JAN-00:10 | 638396.01 | 25-JUL-22:00 |
CoolingCoils:PlantLoopCoolingDemand | 5760.84 | 0.00 | 01-JAN-00:10 | 638396.01 | 25-JUL-22:00 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 29-MAR-20:20 |
Water:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 29-MAR-20:20 |
WaterSystems:Water | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 29-MAR-20:20 |
Water Heater:WaterSystems:Water | 5742.51 | 0.00 | 09-NOV-03:50 | 0.00 | 02-JAN-19:10 |
MainsWater:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 29-MAR-20:20 |
MainsWater:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 29-MAR-20:20 |
WaterSystems:MainsWater | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 29-MAR-20:20 |
Water Heater:WaterSystems:MainsWater | 5742.51 | 0.00 | 09-NOV-03:50 | 0.00 | 02-JAN-19:10 |
WaterUse:WaterSystems:Water | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-07:10 |
WaterUse:WaterSystems:MainsWater | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-07:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 27587.68 | 144165.00 | 30-OCT-13:20 | 2512763.83 | 06-JUL-18:10 |
EnergyTransfer:Building | 5383.03 | 75828.88 | 06-FEB-11:10 | 332208.43 | 07-JUL-18:20 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 730.97 | 10255.70 | 12-FEB-04:00 | 36017.41 | 08-JUL-10:50 |
Refrigeration:EnergyTransfer | 182.22 | 3939.52 | 01-FEB-03:10 | 10328.36 | 07-JUL-07:20 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 91.11 | 1969.76 | 01-FEB-03:10 | 5164.18 | 07-JUL-07:20 |
General:Refrigeration:EnergyTransfer | 91.11 | 1969.76 | 01-FEB-03:10 | 5164.18 | 07-JUL-07:20 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 91.11 | 1969.76 | 01-FEB-03:10 | 5164.18 | 07-JUL-07:20 |
EnergyTransfer:Plant | 13898.52 | 11278.86 | 26-OCT-02:30 | 1472521.58 | 25-JUL-22:00 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 21.60 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 69.51 | 1732.92 | 20-MAR-02:40 | 2526.83 | 17-FEB-14:10 |
EnergyTransfer:Zone:BASEMENT | 428.74 | 4619.45 | 30-APR-15:00 | 17401.36 | 13-OCT-21:00 |
Heating:EnergyTransfer | 79.28 | 0.00 | 01-JAN-08:10 | 70704.04 | 07-JAN-16:20 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 79.28 | 0.00 | 01-JAN-08:10 | 70704.04 | 07-JAN-16:20 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 5212.64 | 66420.66 | 08-JAN-15:00 | 329516.35 | 07-JUL-18:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 428.74 | 4619.45 | 30-APR-15:00 | 17401.36 | 13-OCT-21:00 |
General:Cooling:EnergyTransfer | 5212.64 | 66420.66 | 08-JAN-15:00 | 329516.35 | 07-JUL-18:20 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 428.74 | 4619.45 | 30-APR-15:00 | 17401.36 | 13-OCT-21:00 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 42.82 | 0.05 | 17-JAN-08:00 | 2698.66 | 10-OCT-13:30 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.58 | 0.00 | 01-JAN-00:10 | 1406.94 | 12-FEB-06:00 |
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.58 | 0.00 | 01-JAN-00:10 | 1406.94 | 12-FEB-06:00 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 42.25 | 0.00 | 01-JAN-16:40 | 2698.66 | 10-OCT-13:30 |
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 42.25 | 0.00 | 01-JAN-16:40 | 2698.66 | 10-OCT-13:30 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 39.91 | 202.31 | 08-JAN-16:00 | 1956.37 | 18-AUG-21:00 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 39.91 | 202.31 | 08-JAN-16:00 | 1956.37 | 18-AUG-21:00 |
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 39.91 | 202.31 | 08-JAN-16:00 | 1956.37 | 18-AUG-21:00 |
EnergyTransfer:Zone:MECH_FLR_1 | 28.16 | 0.10 | 03-JAN-13:10 | 1391.28 | 18-AUG-21:10 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.21 | 0.00 | 01-JAN-00:10 | 417.86 | 08-JAN-13:40 |
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.21 | 0.00 | 01-JAN-00:10 | 417.86 | 08-JAN-13:40 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 27.95 | 0.00 | 03-JAN-13:20 | 1391.28 | 18-AUG-21:10 |
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 27.95 | 0.00 | 03-JAN-13:20 | 1391.28 | 18-AUG-21:10 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 15.38 | 0.00 | 21-NOV-04:50 | 802.40 | 18-AUG-21:10 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.40 | 0.00 | 01-JAN-00:10 | 423.97 | 12-FEB-06:00 |
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.40 | 0.00 | 01-JAN-00:10 | 423.97 | 12-FEB-06:00 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 14.98 | 0.00 | 02-JAN-09:10 | 802.40 | 18-AUG-21:10 |
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 14.98 | 0.00 | 02-JAN-09:10 | 802.40 | 18-AUG-21:10 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 608.12 | 8870.59 | 13-FEB-05:00 | 38561.21 | 07-JUL-20:00 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 608.12 | 8870.59 | 13-FEB-05:00 | 38561.21 | 07-JUL-20:00 |
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 608.12 | 8870.59 | 13-FEB-05:00 | 38561.21 | 07-JUL-20:00 |
EnergyTransfer:Zone:CAFE_FLR_1 | 242.84 | 51.47 | 10-JAN-09:10 | 11727.82 | 18-AUG-21:10 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 208.56 | 09-JAN-09:20 |
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 208.56 | 09-JAN-09:20 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 242.84 | 0.00 | 09-JAN-09:10 | 11727.82 | 18-AUG-21:10 |
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 242.84 | 0.00 | 09-JAN-09:10 | 11727.82 | 18-AUG-21:10 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 853.33 | 6585.14 | 08-JAN-16:00 | 38174.53 | 18-AUG-21:10 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 853.33 | 6585.14 | 08-JAN-16:00 | 38174.53 | 18-AUG-21:10 |
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 853.33 | 6585.14 | 08-JAN-16:00 | 38174.53 | 18-AUG-21:10 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 60.90 | 0.00 | 01-JAN-08:10 | 9910.77 | 21-JUL-18:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 8.39 | 0.00 | 01-JAN-08:10 | 5269.46 | 07-JAN-19:20 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 8.39 | 0.00 | 01-JAN-08:10 | 5269.46 | 07-JAN-19:20 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 52.51 | 0.00 | 01-JAN-00:10 | 9910.77 | 21-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 52.51 | 0.00 | 01-JAN-00:10 | 9910.77 | 21-JUL-18:10 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 53.66 | 0.00 | 01-JAN-08:10 | 10008.26 | 21-JUL-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 11.38 | 0.00 | 01-JAN-08:10 | 5810.33 | 12-FEB-09:20 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 11.38 | 0.00 | 01-JAN-08:10 | 5810.33 | 12-FEB-09:20 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 42.27 | 0.00 | 01-JAN-00:10 | 10008.26 | 21-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 42.27 | 0.00 | 01-JAN-00:10 | 10008.26 | 21-JUL-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 294.36 | 0.00 | 01-JAN-00:10 | 38689.16 | 10-OCT-13:30 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 294.36 | 0.00 | 01-JAN-00:10 | 38689.16 | 10-OCT-13:30 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 294.36 | 0.00 | 01-JAN-00:10 | 38689.16 | 10-OCT-13:30 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 448.09 | 0.00 | 01-JAN-08:10 | 73588.83 | 16-JUL-08:10 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 22.03 | 0.00 | 01-JAN-00:10 | 31690.85 | 03-FEB-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 22.03 | 0.00 | 01-JAN-00:10 | 31690.85 | 03-FEB-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 426.06 | 0.00 | 01-JAN-08:10 | 73588.83 | 16-JUL-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 426.06 | 0.00 | 01-JAN-08:10 | 73588.83 | 16-JUL-08:10 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 61.07 | 0.00 | 01-JAN-08:10 | 9021.29 | 07-JUL-08:10 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 8.39 | 0.00 | 01-JAN-08:10 | 5520.00 | 07-JAN-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 8.39 | 0.00 | 01-JAN-08:10 | 5520.00 | 07-JAN-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 52.68 | 0.00 | 01-JAN-00:10 | 9021.29 | 07-JUL-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 52.68 | 0.00 | 01-JAN-00:10 | 9021.29 | 07-JUL-08:10 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 53.90 | 0.00 | 01-JAN-08:10 | 9878.00 | 04-JUN-09:10 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 11.31 | 0.00 | 01-JAN-08:10 | 5756.45 | 07-JAN-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 11.31 | 0.00 | 01-JAN-08:10 | 5756.45 | 07-JAN-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 42.59 | 0.00 | 01-JAN-00:10 | 9878.00 | 04-JUN-09:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 42.59 | 0.00 | 01-JAN-00:10 | 9878.00 | 04-JUN-09:10 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 221.95 | 2.32 | 12-FEB-02:40 | 9858.44 | 18-AUG-21:10 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.23 | 0.00 | 01-JAN-00:10 | 2255.44 | 07-JAN-17:00 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.23 | 0.00 | 01-JAN-00:10 | 2255.44 | 07-JAN-17:00 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 221.72 | 0.00 | 03-JAN-09:10 | 9858.44 | 18-AUG-21:10 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 221.72 | 0.00 | 03-JAN-09:10 | 9858.44 | 18-AUG-21:10 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 17.25 | 0.00 | 01-JAN-08:10 | 2685.35 | 21-JUL-18:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 3.52 | 0.00 | 01-JAN-08:10 | 1765.25 | 07-JAN-19:20 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 3.52 | 0.00 | 01-JAN-08:10 | 1765.25 | 07-JAN-19:20 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 13.73 | 0.00 | 01-JAN-00:10 | 2685.35 | 21-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 13.73 | 0.00 | 01-JAN-00:10 | 2685.35 | 21-JUL-18:10 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 15.82 | 0.00 | 01-JAN-08:10 | 2789.60 | 21-JUL-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 4.52 | 0.00 | 01-JAN-08:10 | 1820.53 | 12-FEB-09:20 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 4.52 | 0.00 | 01-JAN-08:10 | 1820.53 | 12-FEB-09:20 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 11.30 | 0.00 | 01-JAN-00:10 | 2789.60 | 21-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 11.30 | 0.00 | 01-JAN-00:10 | 2789.60 | 21-JUL-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 92.53 | 0.00 | 01-JAN-08:10 | 14041.66 | 10-OCT-15:10 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 7.35 | 0.00 | 01-JAN-08:10 | 8245.46 | 07-JAN-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 7.35 | 0.00 | 01-JAN-08:10 | 8245.46 | 07-JAN-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 85.19 | 0.00 | 01-JAN-00:10 | 14041.66 | 10-OCT-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 85.19 | 0.00 | 01-JAN-00:10 | 14041.66 | 10-OCT-15:10 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 465.28 | 8033.36 | 08-JAN-16:00 | 23282.75 | 07-JUL-21:10 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 465.28 | 8033.36 | 08-JAN-16:00 | 23282.75 | 07-JUL-21:10 |
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 465.28 | 8033.36 | 08-JAN-16:00 | 23282.75 | 07-JUL-21:10 |
EnergyTransfer:Zone:DINING_FLR_6 | 502.04 | 9446.65 | 08-JAN-16:00 | 24589.00 | 07-JUL-21:10 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 502.04 | 9446.65 | 08-JAN-16:00 | 24589.00 | 07-JUL-21:10 |
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 502.04 | 9446.65 | 08-JAN-16:00 | 24589.00 | 07-JUL-21:10 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 639.87 | 8272.89 | 12-FEB-04:00 | 30954.49 | 08-JUL-10:50 |
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 639.87 | 8272.89 | 12-FEB-04:00 | 30954.49 | 08-JUL-10:50 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 105.91 | 0.04 | 18-DEC-01:00 | 5955.10 | 08-JUL-17:20 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.98 | 0.00 | 01-JAN-00:10 | 2797.60 | 12-FEB-06:00 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.98 | 0.00 | 01-JAN-00:10 | 2797.60 | 12-FEB-06:00 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 104.93 | 0.00 | 03-JAN-08:50 | 5955.10 | 08-JUL-17:20 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 104.93 | 0.00 | 03-JAN-08:50 | 5955.10 | 08-JUL-17:20 |
PlantLoopHeatingDemand:Facility | 689.09 | 7890.45 | 03-AUG-00:30 | 52969.01 | 01-FEB-07:20 |
PlantLoopHeatingDemand:Plant | 689.09 | 7890.45 | 03-AUG-00:30 | 52969.01 | 01-FEB-07:20 |
WaterSystems:PlantLoopHeatingDemand | 689.09 | 7890.45 | 03-AUG-00:30 | 52969.01 | 01-FEB-07:20 |
General:WaterSystems:PlantLoopHeatingDemand | 689.09 | 7890.45 | 03-AUG-00:30 | 52969.01 | 01-FEB-07:20 |
EnergyTransfer:HVAC | 8306.13 | 5732.06 | 27-DEC-18:50 | 809993.71 | 06-JUL-18:10 |
HeatingCoils:EnergyTransfer | 765.43 | 0.00 | 21-FEB-20:30 | 212663.19 | 03-JAN-16:10 |
CoolingCoils:EnergyTransfer | 5760.84 | 0.00 | 01-JAN-00:10 | 638396.01 | 25-JUL-22:00 |
HeatRecoveryForHeating:EnergyTransfer | 677.20 | 0.00 | 01-JAN-08:10 | 419262.87 | 12-FEB-07:00 |
HeatRecoveryForCooling:EnergyTransfer | 1102.65 | 0.00 | 01-JAN-00:10 | 264425.37 | 07-JUL-12:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 689.09 | 7890.45 | 03-AUG-00:30 | 52969.01 | 01-FEB-07:20 |
WaterUse:WaterSystems:EnergyTransfer | 689.09 | 7890.45 | 03-AUG-00:30 | 52969.01 | 01-FEB-07:20 |
Chillers:EnergyTransfer | 5838.89 | 0.00 | 01-JAN-00:10 | 642881.29 | 25-JUL-22:00 |
HeatRejection:EnergyTransfer | 7279.43 | 0.00 | 01-JAN-00:10 | 803426.16 | 25-JUL-22:00 |
General:HeatRejection:EnergyTransfer | 7279.43 | 0.00 | 01-JAN-00:10 | 803426.16 | 25-JUL-22:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -428.737 | 0.000 | 0.000 | 151.267 | 161.294 | 143.105 | 0.000 | 0.000 | 0.000 | 0.004 | 0.000 | 0.000 | 0.000 | 0.000 | -26.929 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 0.576 | -42.246 | 0.000 | 0.000 | 15.677 | 7.307 | 10.186 | 19.222 | 0.000 | 0.204 | 0.000 | 0.000 | -8.008 | 0.000 | -1.078 | -1.839 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.000 | -39.913 | 0.000 | 0.000 | 17.770 | 8.462 | 11.795 | 0.000 | 0.000 | 0.081 | 2.236 | 0.000 | 0.000 | 0.000 | -0.431 | -0.000 |
MECH_FLR_1 | 0.000 | 0.000 | 0.209 | -27.955 | 0.000 | 0.000 | 3.825 | 8.366 | 12.471 | 0.000 | 0.000 | 0.195 | 3.877 | 0.000 | 0.000 | 0.000 | -0.988 | -0.000 |
STORAGE_FLR_1 | 0.000 | 0.000 | 0.402 | -14.976 | 0.000 | 0.000 | 2.963 | 3.079 | 3.598 | 0.000 | 0.000 | 0.117 | 5.381 | 0.000 | 0.000 | 0.000 | -0.565 | -0.000 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.000 | -608.117 | 0.000 | 0.000 | 11.868 | 3.975 | 658.131 | 0.000 | 0.000 | 0.294 | 0.000 | 0.000 | 0.000 | 0.000 | -1.442 | -64.709 |
CAFE_FLR_1 | 0.000 | 0.000 | 0.000 | -242.839 | 0.000 | 0.000 | 197.841 | 14.268 | 14.341 | 53.552 | 0.000 | 0.432 | 0.000 | 0.000 | -24.089 | 0.000 | -2.545 | -10.962 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.000 | -853.333 | 0.000 | 0.000 | 587.950 | 110.230 | 148.998 | 71.552 | 0.000 | 1.303 | 0.000 | 0.000 | -31.868 | 0.000 | -7.279 | -27.555 |
ROOM_1_FLR_3 | 11.185 | -43.383 | 0.000 | -11.917 | 0.000 | 0.000 | 9.694 | 9.244 | 10.478 | 39.146 | 0.000 | 0.674 | 0.000 | 0.000 | -19.793 | 0.000 | -3.202 | -2.127 |
ROOM_2_FLR_3 | 14.530 | -33.062 | 0.000 | -12.355 | 0.000 | 0.000 | 9.595 | 9.243 | 10.477 | 30.196 | 0.000 | 0.540 | 0.000 | 0.000 | -21.058 | 0.000 | -3.543 | -4.562 |
ROOM_3_MULT19_FLR_3 | 0.000 | -278.542 | 0.000 | -15.818 | 0.000 | 0.000 | 0.000 | 110.385 | 194.997 | 196.885 | 0.000 | 0.802 | 0.002 | 0.000 | -156.675 | 0.000 | -21.990 | -30.044 |
ROOM_4_MULT19_FLR_3 | 43.853 | -281.070 | 0.000 | -166.791 | 0.000 | 0.000 | 182.385 | 110.415 | 195.050 | 91.503 | 0.000 | 3.467 | 0.000 | 0.000 | -118.817 | 0.000 | -30.750 | -29.245 |
ROOM_5_FLR_3 | 11.169 | -43.523 | 0.000 | -11.927 | 0.000 | 0.000 | 9.687 | 9.244 | 10.478 | 38.925 | 0.000 | 0.673 | 0.001 | 0.000 | -19.103 | 0.000 | -3.213 | -2.412 |
ROOM_6_FLR_3 | 14.434 | -33.366 | 0.000 | -12.349 | 0.000 | 0.000 | 9.600 | 9.243 | 10.477 | 29.426 | 0.000 | 0.543 | 0.000 | 0.000 | -19.801 | 0.000 | -3.480 | -4.728 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 0.228 | -221.721 | 0.000 | 0.000 | 121.046 | 91.336 | 0.000 | 36.448 | 0.000 | 0.598 | 0.003 | 0.000 | -23.241 | 0.000 | -3.056 | -1.637 |
ROOM_1_FLR_6 | 4.328 | -11.563 | 0.000 | -2.977 | 0.000 | 0.000 | 2.426 | 2.311 | 2.620 | 9.681 | 0.000 | 0.172 | 0.000 | 0.000 | -4.916 | 0.000 | -0.829 | -1.253 |
ROOM_2_FLR_6 | 5.380 | -9.074 | 0.000 | -3.090 | 0.000 | 0.000 | 2.400 | 2.311 | 2.619 | 7.461 | 0.000 | 0.135 | 0.000 | 0.000 | -5.244 | 0.000 | -0.926 | -1.971 |
ROOM_3_MULT9_FLR_6 | 10.598 | -69.204 | 0.000 | -19.232 | 0.000 | 0.000 | 21.755 | 13.076 | 23.098 | 49.427 | 0.000 | 0.967 | 0.005 | 0.000 | -22.819 | 0.000 | -4.787 | -2.878 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.000 | -465.286 | 0.000 | 0.000 | 327.939 | 31.204 | 175.857 | 9.378 | 0.000 | 0.227 | 0.000 | 0.000 | -15.161 | 0.000 | -1.813 | -62.346 |
DINING_FLR_6 | 0.000 | 0.000 | 0.000 | -502.042 | 0.000 | 0.000 | 325.100 | 31.204 | 175.857 | 9.039 | 0.000 | 0.219 | 0.000 | 0.000 | -15.774 | 0.000 | -1.845 | -21.758 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.000 | -639.844 | 0.000 | 0.000 | 29.416 | 12.972 | 550.372 | 18.337 | 0.000 | 0.182 | 40.878 | 0.000 | -10.622 | 0.000 | -1.691 | -0.000 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 0.983 | -104.931 | 0.000 | 0.000 | 31.935 | 24.166 | 0.000 | 17.144 | 0.000 | 0.238 | 42.344 | 0.000 | -10.525 | 0.000 | -1.354 | -0.001 |
Total Facility | 115.476 | -802.787 | 2.397 | -4448.395 | 0.000 | 0.000 | 2072.140 | 783.338 | 2365.005 | 727.323 | 0.000 | 12.061 | 94.731 | 0.000 | -527.515 | 0.000 | -96.805 | -296.957 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 13-OCT-21:00 | 0.00 | 0.00 | 0.00 | -17402.05 | 0.00 | 0.00 | 6012.40 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -9460.56 |
RETAIL_1_FLR_1 | 10-OCT-13:30 | 0.00 | 0.00 | 0.00 | -2698.64 | 0.00 | 0.00 | 150.60 | 166.00 | 252.59 | 4144.31 | 0.00 | 24.33 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2039.19 |
RETAIL_2_FLR_1 | 18-AUG-21:00 | 0.00 | 0.00 | 0.00 | -1956.38 | 0.00 | 0.00 | 697.62 | 615.12 | 752.15 | 0.00 | 0.00 | 13.64 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -122.14 |
MECH_FLR_1 | 18-AUG-21:10 | 0.00 | 0.00 | 0.00 | -1391.30 | 0.00 | 0.00 | 168.21 | 456.12 | 618.54 | 0.00 | 0.00 | 32.01 | 116.42 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 18-AUG-21:10 | 0.00 | 0.00 | 0.00 | -802.41 | 0.00 | 0.00 | 132.59 | 167.89 | 178.43 | 0.00 | 0.00 | 19.41 | 304.09 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 07-JUL-20:00 | 0.00 | 0.00 | 0.00 | -38561.34 | 0.00 | 0.00 | 408.88 | 325.08 | 44299.38 | 0.00 | 0.00 | 44.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -6516.01 |
CAFE_FLR_1 | 18-AUG-21:10 | 0.00 | 0.00 | 0.00 | -11729.00 | 0.00 | 0.00 | 8908.41 | 1134.35 | 711.25 | 446.63 | 0.00 | 75.10 | 453.24 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 18-AUG-21:10 | 0.00 | 0.00 | 0.00 | -38177.31 | 0.00 | 0.00 | 26440.84 | 6336.53 | 7389.94 | 651.57 | 0.00 | 214.49 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2856.07 |
ROOM_1_FLR_3 | 27-FEB-16:01 | 0.00 | -12989.90 | 0.00 | -706.19 | 0.00 | 0.00 | 235.28 | 199.23 | 200.18 | 6713.88 | 0.00 | 5.80 | 6341.71 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 09-MAY-20:41 | 0.00 | -13553.27 | 0.00 | -567.22 | 0.00 | 0.00 | 369.64 | 633.19 | 726.90 | 0.00 | 0.00 | 0.00 | 14065.72 | 0.00 | -1557.28 | 0.00 | -117.67 | 0.00 |
ROOM_3_MULT19_FLR_3 | 10-OCT-13:30 | 0.00 | -38687.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2378.94 | 2352.88 | 48519.74 | 0.00 | 132.03 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -14696.31 |
ROOM_4_MULT19_FLR_3 | 09-MAY-20:41 | 0.00 | -89697.32 | 0.00 | -7850.12 | 0.00 | 0.00 | 7105.55 | 7563.69 | 13532.74 | 0.00 | 0.00 | 0.00 | 77840.29 | 0.00 | -7859.69 | 0.00 | -635.14 | 0.00 |
ROOM_5_FLR_3 | 27-FEB-16:01 | 0.00 | -11756.27 | 0.00 | -704.33 | 0.00 | 0.00 | 235.28 | 199.23 | 200.18 | 2256.48 | 0.00 | 6.80 | 9562.63 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 04-JUN-08:51 | 0.00 | -11907.78 | 0.00 | -923.37 | 0.00 | 0.00 | 107.51 | 398.41 | 653.15 | 6844.01 | 0.00 | 0.00 | 4840.21 | 0.00 | -0.00 | 0.00 | -12.14 | 0.00 |
CORRIDOR_FLR_3 | 18-AUG-21:10 | 0.00 | 0.00 | 0.00 | -9858.88 | 0.00 | 0.00 | 5506.49 | 4979.51 | 0.00 | 704.39 | 0.00 | 105.13 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1436.64 |
ROOM_1_FLR_6 | 09-APR-18:01 | 0.00 | -3419.68 | 0.00 | -171.98 | 0.00 | 0.00 | 70.80 | 177.88 | 121.16 | 1074.35 | 0.00 | 0.00 | 2197.51 | 0.00 | -0.00 | 0.00 | -50.05 | 0.00 |
ROOM_2_FLR_6 | 09-MAY-20:41 | 0.00 | -3657.94 | 0.00 | -150.46 | 0.00 | 0.00 | 89.04 | 158.30 | 181.72 | 0.00 | 0.00 | 0.00 | 3821.40 | 0.00 | -411.03 | 0.00 | -31.03 | 0.00 |
ROOM_3_MULT9_FLR_6 | 10-MAR-16:01 | 0.00 | -15676.27 | 0.00 | -1096.72 | 0.00 | 0.00 | 529.39 | 281.79 | 441.28 | 3072.67 | 0.00 | 0.00 | 12988.43 | 0.00 | -0.00 | 0.00 | -540.57 | 0.00 |
BANQUET_FLR_6 | 07-JUL-21:10 | 0.00 | 0.00 | 0.00 | -23285.03 | 0.00 | 0.00 | 15645.48 | 1992.02 | 6747.90 | 291.26 | 0.00 | 44.57 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1436.19 |
DINING_FLR_6 | 07-JUL-21:10 | 0.00 | 0.00 | 0.00 | -24591.48 | 0.00 | 0.00 | 15645.37 | 1992.02 | 6747.90 | 276.11 | 0.00 | 44.57 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -114.49 |
KITCHEN_FLR_6 | 15-APR-10:40 | 0.00 | 0.00 | 0.00 | -31265.70 | 0.00 | 0.00 | 448.83 | 294.67 | 24259.91 | 3099.28 | 0.00 | 1.90 | 3161.12 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 08-JUL-17:13 | 0.00 | 0.00 | 0.00 | -5955.61 | 0.00 | 0.00 | 925.36 | 1317.51 | 0.00 | 1285.86 | 0.00 | 62.96 | 2363.91 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 18-AUG-18:02 | 0.00 | -161328.32 | 0.00 | -195575.89 | 0.00 | 0.00 | 75638.33 | 53381.59 | 120482.43 | 44234.43 | 0.00 | 2825.43 | 60342.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 12-FEB-06:00 | 0.00 | 0.00 | 1406.95 | 0.00 | 0.00 | 0.00 | 626.53 | 132.80 | 216.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1657.81 | 0.00 | -196.16 | -528.81 |
RETAIL_2_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 08-JAN-13:40 | 0.00 | 0.00 | 417.86 | 0.00 | 0.00 | 0.00 | 43.84 | 152.04 | 265.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -110.66 | -768.17 |
STORAGE_FLR_1 | 12-FEB-06:00 | 0.00 | 0.00 | 423.97 | 0.00 | 0.00 | 0.00 | 118.03 | 55.96 | 76.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -103.24 | -571.20 |
LAUNDRY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 09-JAN-09:13 | 0.00 | 0.00 | 209.87 | 0.00 | 0.00 | 0.00 | 2352.41 | 166.37 | 508.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1999.81 | 0.00 | -301.09 | -935.78 |
LOBBY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 22-NOV-09:09 | 6142.75 | 409.41 | 0.00 | -409.41 | 0.00 | 0.00 | 106.92 | 313.07 | 453.05 | 225.52 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -258.39 | -6982.92 |
ROOM_2_FLR_3 | 04-FEB-19:09 | 6179.06 | 407.49 | 0.00 | -407.49 | 0.00 | 0.00 | 347.22 | 711.45 | 484.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2253.92 | 0.00 | -237.99 | -5230.42 |
ROOM_3_MULT19_FLR_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 23-FEB-16:03 | 34810.71 | 5620.59 | 0.00 | -5620.59 | 0.00 | 0.00 | 4858.47 | 2379.59 | 3726.41 | 1401.07 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -22658.06 | -24518.19 |
ROOM_5_FLR_3 | 26-JAN-19:09 | 6010.64 | 409.16 | 0.00 | -409.16 | 0.00 | 0.00 | 408.64 | 633.26 | 484.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2723.57 | 0.00 | -283.84 | -4529.78 |
ROOM_6_FLR_3 | 17-JAN-16:10 | 6097.92 | 408.31 | 0.00 | -408.31 | 0.00 | 0.00 | 293.98 | 199.20 | 200.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1268.37 | 0.00 | -213.52 | -5309.37 |
CORRIDOR_FLR_3 | 07-JAN-17:00 | 0.00 | 0.00 | 2255.40 | 0.00 | 0.00 | 0.00 | 2078.69 | 2074.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3224.45 | 0.00 | -415.06 | -2769.38 |
ROOM_1_FLR_6 | 26-JAN-19:09 | 1891.57 | 101.99 | 0.00 | -101.99 | 0.00 | 0.00 | 103.86 | 158.32 | 121.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -679.94 | 0.00 | -71.11 | -1523.85 |
ROOM_2_FLR_6 | 27-JAN-09:11 | 1870.38 | 90.85 | 0.00 | -90.85 | 0.00 | 0.00 | 24.66 | 78.26 | 113.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -614.73 | 0.00 | -83.12 | -1388.71 |
ROOM_3_MULT9_FLR_6 | 03-JAN-19:09 | 8802.99 | 658.80 | 0.00 | -658.80 | 0.00 | 0.00 | 932.83 | 895.70 | 1068.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2356.25 | 0.00 | -271.26 | -9072.39 |
BANQUET_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 12-FEB-06:00 | 0.00 | 0.00 | 2797.61 | 0.00 | 0.00 | 0.00 | 1283.31 | 439.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2226.23 | 0.00 | -244.39 | -2049.47 |
Total Facility | 07-JAN-16:13 | -6219.30 | 82413.16 | 5248.04 | -82413.16 | 0.00 | 0.00 | 36892.44 | 17941.45 | 74838.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -51193.56 | 0.00 | -8120.83 | -69386.51 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV WITH REHEAT | 22.0517 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 21.9250 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV WITH REHEAT | 11.6654 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 11.6654 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.6520 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.0400 | 0.000610 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.000000 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.000000 | 142.3000 | 0.003581 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.000000 | 422.4350 | 0.001448 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 83.8280 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003556 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.1800 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 | |
VAV WITH REHEAT | 0.00 | 0.001045 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.5322 | 2.5322 | 1.3395 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3116 | 0.3116 | 0.1648 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2370 | 0.2370 | 0.1254 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2014 | 0.2014 | 0.1066 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1201 | 0.1201 | 0.0635 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.3716 | 3.3716 | 1.7836 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3793 | 1.3793 | 0.7297 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.7809 | 4.7809 | 2.5291 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4956 | 1.4956 | 0.7912 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2256 | 2.2256 | 1.1774 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3323 | 2.3323 | 1.2338 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3080 | 2.3080 | 1.2209 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7560 | 0.7560 | 0.3999 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
VAV WITH REHEAT | 22.0517 | 21.9250 | 22.0517 | 11.6654 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3395 | 1.3395 | 1.3395 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1648 | 0.1648 | 0.1648 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1254 | 0.1254 | 0.1254 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1066 | 0.1066 | 0.1066 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0635 | 0.0635 | 0.0635 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7836 | 1.7836 | 1.7836 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7297 | 0.7297 | 0.7297 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.5291 | 2.5291 | 2.5291 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7912 | 0.7912 | 0.7912 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1774 | 1.1774 | 1.1774 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2338 | 1.2338 | 1.2338 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2209 | 1.2209 | 1.2209 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3999 | 0.3999 | 0.3999 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
VAV WITH REHEAT | 11.6654 | 11.6654 | 11.6654 | 11.6654 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 168.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 168.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 5.83 |
Number of hours cooling loads not met | 47.83 |
Number of hours not met | 53.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 765.43 | 212663.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 1440.55 | 176077.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 783.34 | 64632.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 194.02 | 12338.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 872.72 | 59188.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 14.43 | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 8.99 | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.20 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 21.77 | 1291.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 789.09 | 48128.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 2.91 | 188.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 451.94 | 25689.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 94.26 | 4670.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 152.20 | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 94.80 | 4751.85 | 2452.23 | 240345.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.09 | 2093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 20.22 | 1907.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 34.21 | 1192.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1719.70 | 6510.00 |
Natural Gas | 1788.84 | 4241.07 |
Additional | 0.00 | 0.00 |
Total | 3508.54 | 10751.07 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 69.05 |
Space Heating | 67.47 |
Space Cooling | 126.97 |
Fans (All) | 39.84 |
Service Water Heating | 8.36 |
Receptacle Equipment | 146.16 |
Miscellaneous (All) | 573.81 |
Subtotal | 573.81 |
Natural Gas [MJ/m2] | |
Space Heating | 0.00 |
Service Water Heating | 216.15 |
Miscellaneous (All) | 373.82 |
Subtotal | 373.82 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 7.29 |
Space Heating | 7.12 |
Space Cooling | 13.40 |
Fans (All) | 4.20 |
Service Water Heating | 23.69 |
Receptacle Equipment | 32.06 |
Miscellaneous | 12.24 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 486. | 5110. |
ELEVATOR_STANDBY_SCH | 7671. | 8760. |
LTG_SCH_KITCHEN | 3061. | 8760. |
LTG_SCH_DINING | 3061. | 8760. |
LTG_SCH_BASEMENT | 2572. | 8760. |
LTG_SCH_LOBBY | 2295. | 8760. |
LTG_SCH_STORAGE | 1580. | 8760. |
LTG_SCH_MECHANIC | 3061. | 8760. |
LTG_SCH_LAUNDRY | 3061. | 8760. |
LTG_SCH_GUESTROOM | 1980. | 8760. |
LTG_SCH_CORRIDOR | 2295. | 8760. |
LTG_SCH_RETAIL | 2678. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 1591. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3737. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 5740. | 6205. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 8760. | 8760. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 26.67 | 365 | 26.67 | 365 |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
HTGSETP_SCH | BASEMENT DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8759.67 | 0.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8042.83 | 717.17 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8755.17 | 4.83 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8758.33 | 1.67 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8042.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 717.17 | 0.00 | 0.00 | 0.00 |
Average | 8727.09 | 32.91 | 0.00 | 0.00 | 0.00 |
Sum | 191996.00 | 724.00 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108269.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 288887.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 6355515.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8758.50 | 1.50 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8592.67 | 167.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 7429.17 | 1330.83 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8625.00 | 135.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8758.67 | 1.33 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8548.83 | 211.17 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8751.67 | 8.33 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8549.50 | 210.50 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8749.00 | 11.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8655.17 | 104.83 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 7429.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 1330.83 | 0.00 | 0.00 | 0.00 |
Average | 8660.83 | 99.17 | 0.00 | 0.00 | 0.00 |
Sum | 190538.17 | 2181.83 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4118.83 | 35.17 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4119.17 | 34.83 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4118.33 | 35.67 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4105.00 | 49.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1222232.33 | 23482.67 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108269.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 23482.67 | 0.00 | 0.00 | 0.00 |
Average | 287812.62 | 1074.42 | 0.00 | 0.00 | 0.00 |
Sum | 6331877.67 | 23637.33 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 1592.73 | 0.00 | 0.00 |
Sum | 0.00 | 35040.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 710417.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 2115429.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 2115429.00 | 0.00 | 0.00 |
Average | 0.00 | 241694.36 | 0.00 | 0.00 |
Sum | 0.00 | 5317276.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A
For: Environment
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Environment
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA
For: Environment
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.357030E+11 | 14794.99 | 20-JAN-21:50 | 11.88 | 8.39 | 0.640163E+10 | 4033.41 | 27-JAN-22:10 | -0.7 | -4.0 |
February | 0.294044E+11 | 14556.81 | 01-FEB-22:00 | 8.90 | 8.32 | 0.564917E+10 | 3967.70 | 01-FEB-22:10 | 8.72 | 8.24 |
March | 0.289897E+11 | 14289.48 | 01-MAR-22:10 | 11.02 | 10.13 | 0.619681E+10 | 3862.49 | 01-MAR-22:10 | 11.02 | 10.13 |
April | 0.244079E+11 | 13741.15 | 19-APR-21:00 | 18.90 | 16.14 | 0.594134E+10 | 3753.18 | 14-APR-21:10 | 18.90 | 16.14 |
May | 0.294646E+11 | 14080.46 | 19-MAY-21:00 | 23.90 | 16.26 | 0.618299E+10 | 3836.63 | 19-MAY-21:10 | 23.62 | 16.17 |
June | 0.346861E+11 | 14821.25 | 30-JUN-21:00 | 22.80 | 21.19 | 0.621045E+10 | 4025.76 | 30-JUN-21:10 | 22.77 | 21.16 |
July | 0.383903E+11 | 15643.36 | 14-JUL-21:00 | 28.30 | 21.42 | 0.671202E+10 | 4240.89 | 14-JUL-21:10 | 28.22 | 21.44 |
August | 0.407677E+11 | 16515.82 | 18-AUG-21:00 | 31.10 | 22.83 | 0.713221E+10 | 4475.08 | 18-AUG-21:10 | 30.82 | 22.88 |
September | 0.414783E+11 | 17292.74 | 15-SEP-21:00 | 25.00 | 18.13 | 0.722460E+10 | 4692.92 | 14-SEP-21:10 | 25.00 | 18.13 |
October | 0.432457E+11 | 17401.36 | 13-OCT-21:00 | 13.30 | 9.72 | 0.754076E+10 | 4743.05 | 13-OCT-21:10 | 13.12 | 9.56 |
November | 0.417166E+11 | 17352.57 | 09-NOV-22:00 | 13.90 | 10.78 | 0.729465E+10 | 4723.55 | 08-NOV-22:10 | 13.90 | 10.78 |
December | 0.404821E+11 | 16818.46 | 01-DEC-22:00 | 3.90 | 0.00 | 0.710792E+10 | 4615.46 | 01-DEC-22:10 | 3.80 | -0.3 |
Annual Sum or Average | 0.428736E+12 | 0.795946E+11 | ||||||||
Minimum of Months | 0.244079E+11 | 13741.15 | 3.90 | 0.00 | 0.564917E+10 | 3753.18 | -0.7 | -4.0 | ||
Maximum of Months | 0.432457E+11 | 17401.36 | 31.10 | 22.83 | 0.754076E+10 | 4743.05 | 30.82 | 22.88 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.142212E+10 | 2035.68 | 29-JAN-13:30 | 14.45 | 6.22 | 0.621993E+09 | 364.00 | 09-JAN-05:10 | 14.45 | 6.22 |
February | 0.181502E+10 | 2132.60 | 21-FEB-14:30 | 22.25 | 10.82 | 0.566476E+09 | 401.63 | 28-FEB-22:10 | 18.63 | 10.80 |
March | 0.321776E+10 | 2084.98 | 30-MAR-14:20 | 27.80 | 17.60 | 0.638262E+09 | 438.59 | 30-MAR-21:10 | 23.72 | 16.82 |
April | 0.356376E+10 | 2079.17 | 15-APR-14:00 | 27.80 | 15.01 | 0.623121E+09 | 431.53 | 17-APR-21:10 | 20.00 | 14.08 |
May | 0.422274E+10 | 2007.04 | 19-MAY-19:20 | 27.40 | 17.96 | 0.655161E+09 | 443.19 | 19-MAY-21:10 | 23.62 | 16.17 |
June | 0.464908E+10 | 2093.78 | 13-JUN-19:20 | 30.20 | 22.02 | 0.674713E+09 | 466.25 | 13-JUN-21:10 | 28.12 | 21.63 |
July | 0.500127E+10 | 2346.05 | 08-JUL-17:17 | 34.40 | 23.36 | 0.718518E+09 | 491.79 | 07-JUL-21:10 | 34.40 | 23.36 |
August | 0.523806E+10 | 2667.74 | 19-AUG-13:40 | 33.70 | 23.70 | 0.745247E+09 | 491.79 | 18-AUG-21:19 | 33.70 | 23.70 |
September | 0.450277E+10 | 2536.31 | 25-SEP-15:03 | 29.40 | 19.56 | 0.664271E+09 | 478.69 | 07-SEP-21:10 | 29.40 | 19.56 |
October | 0.375614E+10 | 2698.66 | 10-OCT-13:30 | 28.85 | 20.88 | 0.653362E+09 | 453.64 | 10-OCT-21:10 | 21.10 | 18.77 |
November | 0.288982E+10 | 2168.58 | 15-NOV-14:00 | 21.10 | 11.33 | 0.610883E+09 | 397.74 | 08-NOV-22:10 | 21.10 | 11.33 |
December | 0.196754E+10 | 2112.75 | 10-DEC-14:00 | 16.70 | 7.82 | 0.625044E+09 | 390.77 | 12-DEC-22:10 | 18.30 | 14.66 |
Annual Sum or Average | 0.422461E+11 | 0.779705E+10 | ||||||||
Minimum of Months | 0.142212E+10 | 2007.04 | 14.45 | 6.22 | 0.566476E+09 | 364.00 | 14.45 | 6.22 | ||
Maximum of Months | 0.523806E+10 | 2698.66 | 34.40 | 23.70 | 0.745247E+09 | 491.79 | 34.40 | 23.70 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.243781E+10 | 1393.59 | 31-JAN-22:10 | 14.52 | 10.85 | 0.727655E+09 | 477.27 | 31-JAN-22:10 | 14.52 | 10.85 |
February | 0.246731E+10 | 1471.44 | 28-FEB-22:10 | 18.63 | 10.80 | 0.667704E+09 | 504.57 | 28-FEB-22:10 | 18.63 | 10.80 |
March | 0.325839E+10 | 1560.45 | 30-MAR-21:00 | 23.90 | 16.89 | 0.770722E+09 | 531.64 | 30-MAR-21:10 | 23.72 | 16.82 |
April | 0.335063E+10 | 1566.39 | 17-APR-21:10 | 20.00 | 14.08 | 0.764249E+09 | 534.68 | 14-APR-21:10 | 20.00 | 14.08 |
May | 0.363708E+10 | 1609.46 | 19-MAY-21:00 | 23.90 | 16.26 | 0.812850E+09 | 548.62 | 19-MAY-21:10 | 23.62 | 16.17 |
June | 0.372982E+10 | 1647.67 | 27-JUN-21:10 | 27.02 | 21.02 | 0.830382E+09 | 561.67 | 27-JUN-21:10 | 27.02 | 21.02 |
July | 0.394755E+10 | 1875.93 | 07-JUL-21:00 | 30.60 | 22.80 | 0.872498E+09 | 569.50 | 17-JUL-21:19 | 25.93 | 20.55 |
August | 0.402684E+10 | 1956.37 | 18-AUG-21:00 | 31.10 | 22.83 | 0.892423E+09 | 569.50 | 18-AUG-21:19 | 30.53 | 22.93 |
September | 0.366969E+10 | 1738.95 | 08-SEP-21:00 | 25.60 | 21.61 | 0.815001E+09 | 569.49 | 08-SEP-21:19 | 25.40 | 21.58 |
October | 0.347782E+10 | 1597.70 | 11-OCT-21:10 | 15.82 | 9.51 | 0.791093E+09 | 548.06 | 11-OCT-21:10 | 15.82 | 9.51 |
November | 0.310858E+10 | 1464.63 | 02-NOV-21:10 | 17.02 | 14.40 | 0.733160E+09 | 503.42 | 08-NOV-22:10 | 13.62 | 6.96 |
December | 0.280157E+10 | 1449.77 | 12-DEC-22:10 | 18.30 | 14.66 | 0.736056E+09 | 493.96 | 12-DEC-22:10 | 18.30 | 14.66 |
Annual Sum or Average | 0.399131E+11 | 0.941379E+10 | ||||||||
Minimum of Months | 0.243781E+10 | 1393.59 | 14.52 | 9.51 | 0.667704E+09 | 477.27 | 13.62 | 6.96 | ||
Maximum of Months | 0.402684E+10 | 1956.37 | 31.10 | 22.83 | 0.892423E+09 | 569.50 | 30.53 | 22.93 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.622479E+09 | 1082.11 | 20-JAN-21:50 | 11.88 | 8.39 | 0.151779E+09 | 92.50 | 20-JAN-22:10 | 11.52 | 8.16 |
February | 0.105538E+10 | 1116.98 | 28-FEB-22:10 | 18.63 | 10.80 | 0.137508E+09 | 95.94 | 28-FEB-22:10 | 18.63 | 10.80 |
March | 0.206978E+10 | 1185.54 | 30-MAR-21:00 | 23.90 | 16.89 | 0.154295E+09 | 100.87 | 30-MAR-21:10 | 23.72 | 16.82 |
April | 0.249537E+10 | 1203.20 | 19-APR-21:10 | 18.72 | 16.07 | 0.151966E+09 | 102.23 | 19-APR-21:10 | 18.72 | 16.07 |
May | 0.296593E+10 | 1260.23 | 19-MAY-21:00 | 23.90 | 16.26 | 0.163873E+09 | 107.03 | 19-MAY-21:10 | 23.62 | 16.17 |
June | 0.314392E+10 | 1341.03 | 29-JUN-21:10 | 25.92 | 21.53 | 0.172146E+09 | 113.73 | 29-JUN-21:10 | 25.92 | 21.53 |
July | 0.336142E+10 | 1386.62 | 07-JUL-21:10 | 30.40 | 22.79 | 0.182940E+09 | 117.78 | 07-JUL-21:10 | 30.40 | 22.79 |
August | 0.340045E+10 | 1391.28 | 18-AUG-21:10 | 30.82 | 22.88 | 0.185732E+09 | 118.20 | 18-AUG-21:10 | 30.82 | 22.88 |
September | 0.305058E+10 | 1330.87 | 08-SEP-21:00 | 25.60 | 21.61 | 0.166622E+09 | 112.97 | 08-SEP-21:10 | 25.50 | 21.60 |
October | 0.262641E+10 | 1216.95 | 19-OCT-21:10 | 17.12 | 15.78 | 0.157252E+09 | 103.40 | 11-OCT-21:10 | 17.12 | 15.78 |
November | 0.195771E+10 | 1135.27 | 03-NOV-21:10 | 18.22 | 16.16 | 0.148040E+09 | 96.78 | 03-NOV-21:10 | 18.22 | 16.16 |
December | 0.120539E+10 | 1114.01 | 13-DEC-22:10 | 13.22 | 12.84 | 0.151940E+09 | 95.06 | 13-DEC-22:10 | 13.22 | 12.84 |
Annual Sum or Average | 0.279548E+11 | 0.192409E+10 | ||||||||
Minimum of Months | 0.622479E+09 | 1082.11 | 11.88 | 8.39 | 0.137508E+09 | 92.50 | 11.52 | 8.16 | ||
Maximum of Months | 0.340045E+10 | 1391.28 | 30.82 | 22.88 | 0.185732E+09 | 118.20 | 30.82 | 22.88 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.166569E+09 | 609.12 | 31-JAN-22:00 | 14.90 | 11.03 | 0.116690E+09 | 68.56 | 11-JAN-05:10 | 14.90 | 11.03 |
February | 0.427328E+09 | 641.04 | 28-FEB-22:10 | 18.63 | 10.80 | 0.105542E+09 | 71.13 | 28-FEB-22:10 | 18.63 | 10.80 |
March | 0.101095E+10 | 679.35 | 30-MAR-21:00 | 23.90 | 16.89 | 0.117753E+09 | 74.73 | 30-MAR-21:10 | 23.72 | 16.82 |
April | 0.135515E+10 | 686.12 | 19-APR-21:10 | 18.72 | 16.07 | 0.115012E+09 | 75.24 | 19-APR-21:10 | 18.72 | 16.07 |
May | 0.171150E+10 | 720.88 | 19-MAY-21:00 | 23.90 | 16.26 | 0.123290E+09 | 79.07 | 19-MAY-21:10 | 23.62 | 16.17 |
June | 0.183660E+10 | 769.84 | 29-JUN-21:10 | 25.92 | 21.53 | 0.129481E+09 | 84.07 | 29-JUN-21:10 | 25.92 | 21.53 |
July | 0.196462E+10 | 799.79 | 07-JUL-21:10 | 30.40 | 22.79 | 0.137645E+09 | 87.43 | 07-JUL-21:10 | 30.40 | 22.79 |
August | 0.198792E+10 | 802.40 | 18-AUG-21:10 | 30.82 | 22.88 | 0.139794E+09 | 87.73 | 18-AUG-21:10 | 30.82 | 22.88 |
September | 0.177320E+10 | 763.41 | 07-SEP-21:10 | 25.40 | 21.43 | 0.125042E+09 | 83.44 | 08-SEP-21:10 | 25.50 | 21.60 |
October | 0.140931E+10 | 695.80 | 18-OCT-21:10 | 23.22 | 22.46 | 0.118976E+09 | 76.13 | 18-OCT-21:10 | 23.22 | 22.46 |
November | 0.917605E+09 | 649.75 | 03-NOV-21:10 | 18.22 | 16.16 | 0.113070E+09 | 71.54 | 03-NOV-21:10 | 18.22 | 16.16 |
December | 0.415053E+09 | 637.58 | 12-DEC-22:10 | 18.30 | 14.66 | 0.116721E+09 | 70.33 | 12-DEC-22:10 | 18.30 | 14.66 |
Annual Sum or Average | 0.149758E+11 | 0.145902E+10 | ||||||||
Minimum of Months | 0.166569E+09 | 609.12 | 14.90 | 10.80 | 0.105542E+09 | 68.56 | 14.90 | 10.80 | ||
Maximum of Months | 0.198792E+10 | 802.40 | 30.82 | 22.88 | 0.139794E+09 | 87.73 | 30.82 | 22.88 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.483306E+11 | 36462.62 | 31-JAN-21:00 | 17.20 | 12.43 | 0.532537E+09 | 383.13 | 20-JAN-22:00 | 17.20 | 12.43 |
February | 0.445024E+11 | 36968.03 | 28-FEB-21:00 | 20.60 | 11.78 | 0.482745E+09 | 381.57 | 10-FEB-23:10 | 20.60 | 11.78 |
March | 0.509452E+11 | 37426.05 | 30-MAR-20:00 | 24.40 | 16.98 | 0.539186E+09 | 383.08 | 01-MAR-22:40 | 24.40 | 16.98 |
April | 0.500915E+11 | 37590.45 | 17-APR-20:00 | 22.80 | 15.38 | 0.521117E+09 | 382.74 | 25-APR-21:10 | 10.92 | 6.58 |
May | 0.528293E+11 | 37945.87 | 19-MAY-20:00 | 25.60 | 17.28 | 0.540632E+09 | 381.53 | 15-MAY-21:40 | 25.60 | 17.28 |
June | 0.521697E+11 | 38298.34 | 13-JUN-20:00 | 29.40 | 21.98 | 0.526000E+09 | 381.56 | 08-JUN-21:40 | 29.40 | 21.98 |
July | 0.541032E+11 | 38561.21 | 07-JUL-20:00 | 31.10 | 23.22 | 0.541835E+09 | 381.52 | 13-JUL-22:10 | 23.48 | 21.29 |
August | 0.544563E+11 | 38463.01 | 18-AUG-20:00 | 31.70 | 22.32 | 0.544754E+09 | 381.52 | 31-AUG-22:10 | 21.58 | 19.54 |
September | 0.513171E+11 | 38200.24 | 07-SEP-20:00 | 27.20 | 22.45 | 0.522919E+09 | 381.56 | 14-SEP-21:00 | 18.90 | 14.00 |
October | 0.514695E+11 | 37528.48 | 10-OCT-20:00 | 22.20 | 19.19 | 0.537387E+09 | 381.57 | 06-OCT-21:10 | 22.20 | 19.19 |
November | 0.487881E+11 | 36874.20 | 02-NOV-20:00 | 17.80 | 14.77 | 0.518463E+09 | 381.60 | 21-NOV-23:10 | 0.82 | -1.2 |
December | 0.491138E+11 | 36700.17 | 12-DEC-21:00 | 18.30 | 14.62 | 0.533414E+09 | 381.57 | 15-DEC-22:10 | 5.50 | 3.86 |
Annual Sum or Average | 0.608117E+12 | 0.634099E+10 | ||||||||
Minimum of Months | 0.445024E+11 | 36462.62 | 17.20 | 11.78 | 0.482745E+09 | 381.52 | 0.82 | -1.2 | ||
Maximum of Months | 0.544563E+11 | 38561.21 | 31.70 | 23.22 | 0.544754E+09 | 383.13 | 29.40 | 21.98 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.159014E+11 | 9030.10 | 29-JAN-13:00 | 13.90 | 6.14 | 0.841237E+10 | 5730.00 | 31-JAN-22:40 | 13.37 | 10.31 |
February | 0.157010E+11 | 9162.98 | 28-FEB-22:30 | 18.10 | 10.49 | 0.782919E+10 | 6113.08 | 28-FEB-22:40 | 17.83 | 10.34 |
March | 0.199502E+11 | 9626.68 | 30-MAR-21:51 | 22.80 | 16.45 | 0.918475E+10 | 6382.94 | 30-MAR-21:00 | 22.80 | 16.45 |
April | 0.200164E+11 | 9488.89 | 17-APR-21:30 | 20.00 | 13.99 | 0.899658E+10 | 6303.02 | 17-APR-22:10 | 19.72 | 13.80 |
May | 0.215901E+11 | 9605.18 | 19-MAY-21:12 | 23.33 | 16.07 | 0.955486E+10 | 6368.24 | 19-MAY-21:19 | 23.33 | 16.07 |
June | 0.220908E+11 | 10440.12 | 13-JUN-21:10 | 28.12 | 21.63 | 0.968244E+10 | 6461.58 | 14-JUN-22:19 | 25.20 | 19.70 |
July | 0.233889E+11 | 11252.49 | 07-JUL-21:10 | 30.40 | 22.79 | 0.101488E+11 | 6462.55 | 13-JUL-22:10 | 23.48 | 21.29 |
August | 0.241126E+11 | 11727.82 | 18-AUG-21:10 | 30.82 | 22.88 | 0.104306E+11 | 6462.47 | 07-AUG-22:10 | 30.82 | 22.88 |
September | 0.220275E+11 | 10934.29 | 25-SEP-15:06 | 29.40 | 19.56 | 0.960789E+10 | 6462.48 | 11-SEP-22:10 | 29.40 | 19.56 |
October | 0.211591E+11 | 11529.63 | 11-OCT-15:03 | 27.02 | 19.63 | 0.944991E+10 | 6462.39 | 10-OCT-22:10 | 27.02 | 19.63 |
November | 0.191809E+11 | 9499.89 | 11-NOV-13:00 | 21.10 | 11.68 | 0.870370E+10 | 6078.56 | 08-NOV-22:40 | 21.10 | 11.68 |
December | 0.177180E+11 | 9307.34 | 10-DEC-13:00 | 15.60 | 7.72 | 0.862588E+10 | 6079.03 | 12-DEC-23:10 | 18.22 | 14.85 |
Annual Sum or Average | 0.242837E+12 | 0.110627E+12 | ||||||||
Minimum of Months | 0.157010E+11 | 9030.10 | 13.90 | 6.14 | 0.782919E+10 | 5730.00 | 13.37 | 10.31 | ||
Maximum of Months | 0.241126E+11 | 11727.82 | 30.82 | 22.88 | 0.104306E+11 | 6462.55 | 30.82 | 22.88 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.593823E+11 | 29797.94 | 31-JAN-22:30 | 13.75 | 10.50 | 0.252965E+11 | 16990.64 | 31-JAN-22:40 | 13.37 | 10.31 |
February | 0.570422E+11 | 30992.92 | 28-FEB-22:55 | 17.30 | 10.02 | 0.233889E+11 | 17721.77 | 28-FEB-23:10 | 17.02 | 9.75 |
March | 0.700202E+11 | 32312.34 | 30-MAR-22:00 | 22.80 | 16.45 | 0.270931E+11 | 18351.84 | 30-MAR-22:10 | 22.62 | 16.35 |
April | 0.701814E+11 | 32103.36 | 17-APR-22:00 | 20.00 | 13.85 | 0.266578E+11 | 18270.02 | 17-APR-22:10 | 19.72 | 13.80 |
May | 0.753880E+11 | 32835.88 | 19-MAY-22:00 | 22.20 | 15.66 | 0.282953E+11 | 18661.85 | 19-MAY-22:10 | 21.93 | 15.69 |
June | 0.765459E+11 | 33693.91 | 29-JUN-21:10 | 25.92 | 21.53 | 0.286431E+11 | 19155.44 | 13-JUN-22:10 | 25.92 | 21.53 |
July | 0.807126E+11 | 36962.29 | 07-JUL-21:10 | 30.40 | 22.79 | 0.299605E+11 | 19185.95 | 13-JUL-22:10 | 23.48 | 21.29 |
August | 0.821294E+11 | 38174.53 | 18-AUG-21:10 | 30.82 | 22.88 | 0.305606E+11 | 19185.85 | 07-AUG-22:10 | 30.82 | 22.88 |
September | 0.759761E+11 | 35187.70 | 07-SEP-21:10 | 25.40 | 21.43 | 0.283069E+11 | 19182.13 | 08-SEP-21:10 | 25.50 | 21.60 |
October | 0.736051E+11 | 32867.97 | 10-OCT-22:00 | 21.10 | 18.56 | 0.277963E+11 | 18679.59 | 11-OCT-21:40 | 14.97 | 9.20 |
November | 0.676773E+11 | 31085.25 | 02-NOV-22:00 | 16.10 | 14.10 | 0.259160E+11 | 17656.61 | 08-NOV-22:40 | 12.77 | 6.65 |
December | 0.646684E+11 | 30982.79 | 12-DEC-23:00 | 18.30 | 14.87 | 0.258607E+11 | 17592.51 | 12-DEC-23:10 | 18.22 | 14.85 |
Annual Sum or Average | 0.853329E+12 | 0.327776E+12 | ||||||||
Minimum of Months | 0.570422E+11 | 29797.94 | 13.75 | 10.02 | 0.233889E+11 | 16990.64 | 12.77 | 6.65 | ||
Maximum of Months | 0.821294E+11 | 38174.53 | 30.82 | 22.88 | 0.305606E+11 | 19185.95 | 30.82 | 22.88 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 58570719.74 | 3329.11 | 29-JAN-16:01 | 16.52 | 6.64 | 94433088.40 | 56.69 | 30-JAN-00:49 | 5.97 | 1.79 |
February | 0.200362E+09 | 3424.10 | 27-FEB-16:01 | 22.70 | 11.34 | 86160760.97 | 57.46 | 16-FEB-22:40 | 22.70 | 11.34 |
March | 0.645813E+09 | 3392.01 | 10-MAR-16:01 | 20.10 | 8.83 | 97641927.35 | 60.46 | 23-MAR-21:30 | 15.00 | 10.40 |
April | 0.106532E+10 | 3421.38 | 09-APR-18:01 | 20.45 | 11.08 | 95099350.83 | 56.69 | 12-APR-21:00 | 17.80 | 13.32 |
May | 0.151677E+10 | 3404.32 | 09-MAY-18:01 | 19.63 | 9.69 | 98776826.75 | 56.69 | 31-MAY-21:00 | 21.80 | 18.82 |
June | 0.203308E+10 | 3054.64 | 26-JUN-18:02 | 23.22 | 21.66 | 95892201.23 | 56.69 | 20-JUN-22:00 | 23.22 | 21.66 |
July | 0.228114E+10 | 2983.17 | 27-JUL-15:02 | 24.03 | 20.92 | 99007824.79 | 56.69 | 10-JUL-01:49 | 24.03 | 20.92 |
August | 0.239836E+10 | 3010.68 | 19-AUG-08:62 | 27.57 | 23.59 | 99172833.07 | 56.69 | 20-AUG-01:00 | 24.40 | 23.26 |
September | 0.161701E+10 | 3017.66 | 04-SEP-15:02 | 28.22 | 22.25 | 95541588.86 | 56.69 | 19-SEP-21:30 | 19.15 | 15.19 |
October | 0.855745E+09 | 3238.13 | 31-OCT-18:01 | 12.20 | 6.42 | 97792127.11 | 56.69 | 10-OCT-21:00 | 12.20 | 6.42 |
November | 0.345549E+09 | 3379.79 | 14-NOV-16:01 | 19.13 | 9.12 | 93847327.21 | 56.69 | 02-NOV-21:30 | 19.13 | 9.12 |
December | 0.108917E+09 | 3332.86 | 09-DEC-16:01 | 14.13 | 6.24 | 95323843.77 | 56.69 | 13-DEC-00:10 | 17.62 | 14.70 |
Annual Sum or Average | 0.131266E+11 | 0.114869E+10 | ||||||||
Minimum of Months | 58570719.74 | 2983.17 | 12.20 | 6.24 | 86160760.97 | 56.69 | 5.97 | 1.79 | ||
Maximum of Months | 0.239836E+10 | 3424.10 | 28.22 | 23.59 | 99172833.07 | 60.46 | 24.40 | 23.26 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 16810206.64 | 3045.18 | 29-JAN-16:01 | 16.52 | 6.64 | 93298096.03 | 57.69 | 31-JAN-22:10 | 14.52 | 10.85 |
February | 75002301.76 | 3356.03 | 27-FEB-16:01 | 22.70 | 11.34 | 85953990.02 | 66.19 | 28-FEB-22:40 | 17.83 | 10.34 |
March | 0.349847E+09 | 3331.66 | 10-MAR-16:01 | 20.10 | 8.83 | 99289621.17 | 71.89 | 29-MAR-21:10 | 22.62 | 17.00 |
April | 0.757816E+09 | 3510.92 | 26-APR-18:41 | 14.60 | 7.53 | 99466346.65 | 74.13 | 14-APR-21:30 | 14.60 | 7.53 |
May | 0.125778E+10 | 3530.12 | 09-MAY-20:41 | 13.68 | 6.54 | 0.104438E+09 | 74.95 | 31-MAY-21:10 | 22.13 | 18.80 |
June | 0.188996E+10 | 3011.32 | 16-JUN-21:51 | 23.30 | 20.62 | 99450371.03 | 81.68 | 26-JUN-21:10 | 23.22 | 21.66 |
July | 0.212586E+10 | 3037.81 | 02-JUL-21:51 | 22.80 | 18.09 | 0.102344E+09 | 79.75 | 18-JUL-21:10 | 22.80 | 21.57 |
August | 0.217658E+10 | 3047.95 | 08-AUG-18:01 | 26.88 | 23.69 | 0.101513E+09 | 75.56 | 23-AUG-21:19 | 23.90 | 23.53 |
September | 0.128185E+10 | 3284.05 | 18-SEP-16:01 | 25.40 | 17.60 | 99602070.49 | 75.02 | 11-SEP-21:19 | 25.40 | 17.60 |
October | 0.466836E+09 | 3106.66 | 31-OCT-18:01 | 12.20 | 6.42 | 0.100395E+09 | 71.89 | 10-OCT-21:10 | 12.20 | 6.42 |
November | 0.135042E+09 | 3311.29 | 14-NOV-16:01 | 19.13 | 9.12 | 93591845.65 | 62.74 | 02-NOV-21:40 | 19.13 | 9.12 |
December | 35231544.26 | 2984.88 | 09-DEC-16:01 | 14.13 | 6.24 | 94123953.23 | 60.77 | 12-DEC-22:30 | 18.30 | 14.75 |
Annual Sum or Average | 0.105686E+11 | 0.117347E+10 | ||||||||
Minimum of Months | 16810206.64 | 2984.88 | 12.20 | 6.24 | 85953990.02 | 57.69 | 12.20 | 6.42 | ||
Maximum of Months | 0.217658E+10 | 3530.12 | 26.88 | 23.69 | 0.104438E+09 | 81.68 | 25.40 | 23.53 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 28182351.27 | 292.20 | 29-JAN-13:30 | 14.45 | 6.22 | 0.00 | 0.00 | 01-JAN-00:10 | 14.45 | 6.22 |
February | 88018041.65 | 394.12 | 26-FEB-14:25 | 24.70 | 12.65 | 0.00 | 0.00 | 01-FEB-00:10 | 24.70 | 12.65 |
March | 0.242464E+09 | 369.60 | 30-MAR-13:40 | 27.43 | 17.97 | 0.00 | 0.00 | 01-MAR-00:10 | 27.43 | 17.97 |
April | 0.286757E+09 | 348.59 | 15-APR-13:50 | 27.62 | 15.00 | 0.00 | 0.00 | 01-APR-00:10 | 27.62 | 15.00 |
May | 0.367631E+09 | 297.14 | 19-MAY-19:10 | 27.85 | 18.11 | 0.00 | 0.00 | 01-MAY-00:10 | 27.85 | 18.11 |
June | 0.475558E+09 | 337.52 | 24-JUN-19:10 | 30.22 | 21.43 | 0.00 | 0.00 | 01-JUN-00:10 | 30.22 | 21.43 |
July | 0.553046E+09 | 376.59 | 08-JUL-17:30 | 34.40 | 23.36 | 0.00 | 0.00 | 01-JUL-00:10 | 34.40 | 23.36 |
August | 0.634766E+09 | 408.88 | 19-AUG-13:40 | 33.70 | 23.70 | 0.00 | 0.00 | 01-AUG-00:10 | 33.70 | 23.70 |
September | 0.490431E+09 | 473.83 | 24-SEP-12:40 | 28.70 | 19.86 | 0.00 | 0.00 | 01-SEP-00:10 | 28.70 | 19.86 |
October | 0.366663E+09 | 509.07 | 10-OCT-13:30 | 28.85 | 20.88 | 0.00 | 0.00 | 01-OCT-00:10 | 28.85 | 20.88 |
November | 0.230742E+09 | 445.05 | 15-NOV-14:00 | 21.10 | 11.33 | 0.00 | 0.00 | 01-NOV-00:10 | 21.10 | 11.33 |
December | 0.108951E+09 | 427.38 | 10-DEC-14:25 | 17.50 | 8.24 | 0.00 | 0.00 | 01-DEC-00:10 | 17.50 | 8.24 |
Annual Sum or Average | 0.387321E+10 | 0.00 | ||||||||
Minimum of Months | 28182351.27 | 292.20 | 14.45 | 6.22 | 0.00 | 0.00 | 14.45 | 6.22 | ||
Maximum of Months | 0.634766E+09 | 509.07 | 34.40 | 23.70 | 0.00 | 0.00 | 34.40 | 23.70 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 59768812.30 | 985.72 | 31-JAN-16:01 | 19.90 | 13.55 | 94855274.98 | 64.78 | 31-JAN-22:19 | 14.13 | 10.68 |
February | 0.134435E+09 | 1201.72 | 28-FEB-22:52 | 17.30 | 10.02 | 86845642.29 | 69.36 | 28-FEB-22:00 | 17.30 | 10.02 |
March | 0.317517E+09 | 1199.32 | 31-MAR-20:12 | 13.87 | 8.46 | 98512812.31 | 70.93 | 28-MAR-21:10 | 13.87 | 8.46 |
April | 0.464026E+09 | 1205.22 | 09-APR-20:11 | 13.70 | 8.28 | 98331047.90 | 73.61 | 24-APR-21:10 | 13.22 | 9.86 |
May | 0.641950E+09 | 1283.52 | 09-MAY-20:41 | 13.68 | 6.54 | 0.103316E+09 | 74.41 | 31-MAY-21:10 | 22.13 | 18.80 |
June | 0.829109E+09 | 1140.59 | 29-JUN-15:02 | 30.68 | 22.87 | 98696387.42 | 78.60 | 26-JUN-21:10 | 30.68 | 22.87 |
July | 0.902200E+09 | 1137.22 | 09-JUL-15:02 | 33.90 | 23.21 | 0.101883E+09 | 77.41 | 25-JUL-21:10 | 22.80 | 21.95 |
August | 0.897396E+09 | 1139.08 | 06-AUG-15:02 | 31.88 | 23.78 | 0.101042E+09 | 75.64 | 31-AUG-21:30 | 21.65 | 19.90 |
September | 0.638196E+09 | 1125.91 | 10-SEP-18:01 | 26.52 | 22.32 | 99213695.15 | 76.08 | 01-SEP-21:10 | 26.52 | 22.32 |
October | 0.384825E+09 | 1202.60 | 11-OCT-21:52 | 14.40 | 8.97 | 99893330.43 | 73.25 | 18-OCT-21:10 | 23.22 | 22.46 |
November | 0.229481E+09 | 1136.64 | 28-NOV-19:02 | 11.52 | 4.78 | 94256123.41 | 68.80 | 03-NOV-21:49 | 11.52 | 4.78 |
December | 0.107203E+09 | 995.52 | 11-DEC-16:01 | 21.02 | 15.88 | 95593575.89 | 65.92 | 12-DEC-22:49 | 18.30 | 14.83 |
Annual Sum or Average | 0.560611E+10 | 0.117244E+10 | ||||||||
Minimum of Months | 59768812.30 | 985.72 | 11.52 | 4.78 | 86845642.29 | 64.78 | 11.52 | 4.78 | ||
Maximum of Months | 0.902200E+09 | 1283.52 | 33.90 | 23.78 | 0.103316E+09 | 78.60 | 30.68 | 22.87 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 55617765.28 | 3029.22 | 29-JAN-16:01 | 16.52 | 6.64 | 94546226.15 | 56.69 | 30-JAN-00:49 | 5.97 | 1.79 |
February | 0.217142E+09 | 3115.23 | 27-FEB-16:01 | 22.70 | 11.34 | 86347614.40 | 57.03 | 16-FEB-22:40 | 22.70 | 11.34 |
March | 0.581846E+09 | 3085.76 | 10-MAR-16:01 | 20.10 | 8.83 | 97829950.92 | 57.61 | 23-MAR-21:30 | 15.00 | 10.40 |
April | 0.102904E+10 | 3086.99 | 09-APR-18:01 | 20.45 | 11.08 | 95369588.22 | 56.69 | 18-APR-21:40 | 19.60 | 14.79 |
May | 0.154929E+10 | 3084.15 | 09-MAY-18:01 | 19.63 | 9.69 | 98987985.51 | 56.69 | 22-MAY-21:49 | 19.08 | 17.15 |
June | 0.207770E+10 | 2821.61 | 05-JUN-08:61 | 23.77 | 18.74 | 96005771.37 | 56.69 | 26-JUN-23:10 | 22.88 | 22.05 |
July | 0.235690E+10 | 2864.78 | 21-JUL-08:61 | 26.15 | 22.30 | 99065977.43 | 56.69 | 18-JUL-01:30 | 26.15 | 22.30 |
August | 0.241393E+10 | 2848.12 | 01-AUG-08:61 | 26.38 | 22.61 | 99215344.22 | 56.69 | 09-AUG-01:39 | 24.60 | 23.32 |
September | 0.162338E+10 | 2829.58 | 09-SEP-08:61 | 25.55 | 21.79 | 95634195.34 | 56.69 | 08-SEP-00:49 | 25.55 | 21.79 |
October | 0.833215E+09 | 2777.79 | 17-OCT-18:01 | 24.32 | 20.52 | 97959084.52 | 56.69 | 10-OCT-21:00 | 24.32 | 20.52 |
November | 0.324846E+09 | 3063.96 | 14-NOV-16:01 | 19.13 | 9.12 | 94048160.86 | 56.69 | 02-NOV-21:40 | 19.13 | 9.12 |
December | 0.105963E+09 | 2930.67 | 09-DEC-16:01 | 14.13 | 6.24 | 95456981.87 | 56.69 | 12-DEC-22:19 | 18.30 | 14.70 |
Annual Sum or Average | 0.131689E+11 | 0.115047E+10 | ||||||||
Minimum of Months | 55617765.28 | 2777.79 | 14.13 | 6.24 | 86347614.40 | 56.69 | 5.97 | 1.79 | ||
Maximum of Months | 0.241393E+10 | 3115.23 | 26.38 | 22.61 | 99215344.22 | 57.61 | 26.15 | 23.32 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 17642872.34 | 2240.48 | 31-JAN-16:01 | 19.90 | 13.55 | 93353146.28 | 58.25 | 31-JAN-22:10 | 14.52 | 10.85 |
February | 95572886.05 | 3063.33 | 27-FEB-16:01 | 22.70 | 11.34 | 85892704.36 | 65.46 | 28-FEB-22:40 | 17.83 | 10.34 |
March | 0.329528E+09 | 2976.70 | 10-MAR-16:01 | 20.10 | 8.83 | 98499487.06 | 68.72 | 29-MAR-21:10 | 22.62 | 17.00 |
April | 0.747647E+09 | 2962.24 | 14-APR-08:51 | 19.40 | 14.17 | 98854536.24 | 71.85 | 17-APR-21:00 | 20.00 | 13.85 |
May | 0.128717E+10 | 3158.05 | 16-MAY-08:51 | 21.70 | 15.85 | 0.104256E+09 | 75.82 | 31-MAY-21:10 | 22.13 | 18.80 |
June | 0.190701E+10 | 3207.87 | 04-JUN-08:51 | 24.40 | 18.28 | 99810681.30 | 78.46 | 26-JUN-21:10 | 23.22 | 21.66 |
July | 0.216842E+10 | 3003.30 | 17-JUL-08:51 | 26.10 | 21.47 | 0.102930E+09 | 80.21 | 25-JUL-21:10 | 22.80 | 21.95 |
August | 0.217514E+10 | 3050.60 | 26-AUG-08:51 | 24.40 | 19.19 | 0.101807E+09 | 76.86 | 07-AUG-21:00 | 24.40 | 19.19 |
September | 0.127581E+10 | 3073.40 | 15-SEP-08:51 | 21.70 | 14.94 | 99691716.81 | 74.57 | 01-SEP-21:10 | 21.70 | 14.94 |
October | 0.474799E+09 | 2732.45 | 11-OCT-15:01 | 27.02 | 19.63 | 99799647.69 | 71.49 | 17-OCT-21:10 | 23.22 | 20.61 |
November | 0.136811E+09 | 2640.24 | 07-NOV-16:01 | 18.03 | 8.19 | 93179232.09 | 63.07 | 03-NOV-21:30 | 18.03 | 8.19 |
December | 32099625.93 | 2197.60 | 19-DEC-09:04 | 2.57 | -1.3 | 94105059.83 | 60.24 | 12-DEC-22:30 | 2.57 | -1.3 |
Annual Sum or Average | 0.106477E+11 | 0.117218E+10 | ||||||||
Minimum of Months | 17642872.34 | 2197.60 | 2.57 | -1.3 | 85892704.36 | 58.25 | 2.57 | -1.3 | ||
Maximum of Months | 0.217514E+10 | 3207.87 | 27.02 | 21.47 | 0.104256E+09 | 80.21 | 24.40 | 21.95 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.204939E+10 | 1970.07 | 31-JAN-22:10 | 14.52 | 10.85 | 0.119903E+10 | 718.68 | 31-JAN-22:30 | 13.75 | 10.50 |
February | 0.263084E+10 | 2062.16 | 28-FEB-22:10 | 18.63 | 10.80 | 0.108781E+10 | 751.70 | 28-FEB-22:30 | 18.10 | 10.49 |
March | 0.455105E+10 | 2151.11 | 30-MAR-21:51 | 22.80 | 16.45 | 0.122601E+10 | 778.78 | 30-MAR-22:10 | 22.62 | 16.35 |
April | 0.505463E+10 | 2222.15 | 19-APR-21:10 | 18.72 | 16.07 | 0.122031E+10 | 800.93 | 17-APR-22:10 | 18.72 | 16.07 |
May | 0.562292E+10 | 2270.09 | 19-MAY-21:12 | 23.33 | 16.07 | 0.130957E+10 | 820.19 | 19-MAY-21:19 | 23.33 | 16.07 |
June | 0.580639E+10 | 2395.58 | 29-JUN-21:10 | 25.92 | 21.53 | 0.134807E+10 | 861.37 | 29-JUN-21:19 | 25.73 | 21.59 |
July | 0.615684E+10 | 2442.35 | 07-JUL-21:10 | 30.40 | 22.79 | 0.142106E+10 | 879.00 | 07-JUL-21:19 | 30.20 | 22.78 |
August | 0.618966E+10 | 2464.61 | 18-AUG-21:10 | 30.82 | 22.88 | 0.143426E+10 | 886.98 | 18-AUG-21:19 | 30.53 | 22.93 |
September | 0.564546E+10 | 2360.28 | 08-SEP-21:10 | 25.50 | 21.60 | 0.130866E+10 | 849.65 | 08-SEP-21:19 | 25.40 | 21.58 |
October | 0.494480E+10 | 2201.67 | 11-OCT-21:10 | 15.82 | 9.51 | 0.124668E+10 | 797.95 | 11-OCT-21:19 | 15.53 | 9.41 |
November | 0.392930E+10 | 2029.07 | 02-NOV-21:10 | 17.02 | 14.40 | 0.116626E+10 | 735.80 | 02-NOV-21:40 | 16.47 | 14.23 |
December | 0.284869E+10 | 2018.03 | 12-DEC-22:10 | 18.30 | 14.66 | 0.119999E+10 | 733.41 | 12-DEC-23:10 | 18.22 | 14.85 |
Annual Sum or Average | 0.554300E+11 | 0.151677E+11 | ||||||||
Minimum of Months | 0.204939E+10 | 1970.07 | 14.52 | 9.51 | 0.108781E+10 | 718.68 | 13.75 | 9.41 | ||
Maximum of Months | 0.618966E+10 | 2464.61 | 30.82 | 22.88 | 0.143426E+10 | 886.98 | 30.53 | 22.93 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 43401287.54 | 3473.19 | 29-JAN-16:01 | 16.52 | 6.64 | 93791966.19 | 56.69 | 30-JAN-00:49 | 5.97 | 1.79 |
February | 0.182183E+09 | 3591.55 | 27-FEB-16:01 | 22.70 | 11.34 | 85665297.99 | 56.69 | 22-FEB-02:00 | 22.70 | 11.34 |
March | 0.634295E+09 | 3556.18 | 10-MAR-16:01 | 20.10 | 8.83 | 97396482.77 | 59.14 | 23-MAR-21:30 | 15.00 | 10.40 |
April | 0.111095E+10 | 3591.69 | 09-APR-18:01 | 20.45 | 11.08 | 95010426.93 | 56.69 | 12-APR-21:49 | 18.07 | 13.39 |
May | 0.163547E+10 | 3563.80 | 09-MAY-18:01 | 19.63 | 9.69 | 98748145.17 | 56.70 | 08-MAY-21:30 | 19.63 | 9.69 |
June | 0.218168E+10 | 3121.61 | 26-JUN-18:02 | 23.22 | 21.66 | 95877111.31 | 56.70 | 26-JUN-00:00 | 23.22 | 21.66 |
July | 0.244719E+10 | 3075.48 | 27-JUL-15:02 | 24.03 | 20.92 | 98995769.89 | 56.70 | 21-JUL-21:10 | 24.03 | 20.92 |
August | 0.256612E+10 | 3088.08 | 08-AUG-18:01 | 26.88 | 23.69 | 99166104.44 | 56.69 | 05-AUG-01:10 | 26.88 | 23.69 |
September | 0.167890E+10 | 3181.34 | 09-SEP-18:02 | 23.80 | 21.22 | 95485690.38 | 56.69 | 15-SEP-22:40 | 24.23 | 17.65 |
October | 0.852173E+09 | 3405.93 | 31-OCT-18:01 | 12.20 | 6.42 | 97589324.31 | 56.69 | 10-OCT-21:40 | 12.20 | 6.42 |
November | 0.311075E+09 | 3536.98 | 14-NOV-16:01 | 19.13 | 9.12 | 93522171.89 | 56.69 | 04-NOV-04:30 | 19.13 | 9.12 |
December | 87783662.05 | 3477.78 | 09-DEC-16:01 | 14.13 | 6.24 | 94700571.05 | 56.69 | 12-DEC-00:30 | 14.75 | 13.61 |
Annual Sum or Average | 0.137312E+11 | 0.114595E+10 | ||||||||
Minimum of Months | 43401287.54 | 3075.48 | 12.20 | 6.24 | 85665297.99 | 56.69 | 5.97 | 1.79 | ||
Maximum of Months | 0.256612E+10 | 3591.69 | 26.88 | 23.69 | 99166104.44 | 59.14 | 26.88 | 23.69 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 11779790.70 | 2314.24 | 20-JAN-16:01 | 17.12 | 12.56 | 92808666.99 | 56.69 | 30-JAN-00:49 | 5.97 | 1.79 |
February | 63062490.22 | 3512.18 | 27-FEB-16:01 | 22.70 | 11.34 | 85613390.79 | 66.91 | 28-FEB-22:40 | 17.83 | 10.34 |
March | 0.335902E+09 | 3485.36 | 10-MAR-16:01 | 20.10 | 8.83 | 99191632.91 | 72.55 | 29-MAR-21:10 | 22.62 | 17.00 |
April | 0.799134E+09 | 3726.09 | 26-APR-18:41 | 14.60 | 7.53 | 0.100003E+09 | 76.46 | 14-APR-21:30 | 14.60 | 7.53 |
May | 0.139534E+10 | 3808.41 | 09-MAY-20:41 | 13.68 | 6.54 | 0.104946E+09 | 78.61 | 09-MAY-18:10 | 13.68 | 6.54 |
June | 0.206495E+10 | 3145.98 | 07-JUN-21:51 | 17.80 | 12.14 | 99457171.15 | 84.05 | 26-JUN-21:10 | 23.22 | 21.66 |
July | 0.231837E+10 | 3189.35 | 02-JUL-21:51 | 22.80 | 18.09 | 0.102266E+09 | 80.48 | 18-JUL-21:10 | 22.80 | 21.57 |
August | 0.235943E+10 | 3196.47 | 08-AUG-18:01 | 26.88 | 23.69 | 0.101426E+09 | 75.84 | 07-AUG-21:00 | 26.88 | 23.69 |
September | 0.135814E+10 | 3402.23 | 18-SEP-16:01 | 25.40 | 17.60 | 99617526.14 | 75.26 | 11-SEP-21:00 | 25.40 | 17.60 |
October | 0.457441E+09 | 3358.32 | 15-OCT-16:21 | 24.15 | 17.28 | 0.100418E+09 | 72.56 | 10-OCT-21:10 | 24.15 | 17.28 |
November | 0.111223E+09 | 3448.66 | 14-NOV-16:01 | 19.13 | 9.12 | 93186716.86 | 62.39 | 02-NOV-21:40 | 19.13 | 9.12 |
December | 25336797.07 | 2827.08 | 11-DEC-16:01 | 21.02 | 15.88 | 93493468.66 | 59.77 | 12-DEC-22:30 | 18.30 | 14.75 |
Annual Sum or Average | 0.113001E+11 | 0.117243E+10 | ||||||||
Minimum of Months | 11779790.70 | 2314.24 | 13.68 | 6.54 | 85613390.79 | 56.69 | 5.97 | 1.79 | ||
Maximum of Months | 0.235943E+10 | 3808.41 | 26.88 | 23.69 | 0.104946E+09 | 84.05 | 26.88 | 23.69 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.182418E+09 | 1823.66 | 27-JAN-16:01 | 4.40 | -1.8 | 96161361.71 | 58.56 | 19-JAN-22:49 | 4.40 | -1.8 |
February | 0.278605E+09 | 1841.49 | 26-FEB-19:01 | 20.00 | 10.72 | 87380765.54 | 61.89 | 16-FEB-22:49 | 20.00 | 10.72 |
March | 0.577078E+09 | 1863.85 | 10-MAR-16:01 | 20.10 | 8.83 | 98047755.23 | 63.33 | 23-MAR-21:30 | 15.00 | 10.40 |
April | 0.717067E+09 | 1843.19 | 09-APR-18:01 | 20.45 | 11.08 | 95189330.69 | 56.69 | 20-APR-21:49 | 18.90 | 15.37 |
May | 0.923797E+09 | 1838.74 | 10-MAY-18:01 | 20.92 | 10.48 | 98755991.81 | 56.69 | 17-MAY-22:49 | 20.78 | 15.59 |
June | 0.117918E+10 | 1646.51 | 30-JUN-18:02 | 25.10 | 21.60 | 95869208.06 | 56.69 | 13-JUN-00:20 | 25.10 | 21.60 |
July | 0.134628E+10 | 1656.23 | 27-JUL-15:02 | 24.03 | 20.92 | 98986698.74 | 56.70 | 21-JUL-21:19 | 24.03 | 20.92 |
August | 0.149545E+10 | 1657.99 | 08-AUG-18:01 | 26.88 | 23.69 | 99172257.74 | 56.69 | 28-AUG-21:10 | 25.92 | 22.23 |
September | 0.112378E+10 | 1657.77 | 17-SEP-18:01 | 24.03 | 19.88 | 95576854.72 | 56.69 | 27-SEP-01:39 | 23.50 | 20.17 |
October | 0.810727E+09 | 1822.38 | 12-OCT-18:01 | 17.23 | 10.36 | 98166088.64 | 56.69 | 11-OCT-00:20 | 17.23 | 10.36 |
November | 0.528569E+09 | 1810.50 | 15-NOV-19:01 | 14.13 | 8.31 | 94820101.01 | 59.61 | 12-NOV-02:09 | 14.13 | 8.31 |
December | 0.302333E+09 | 1840.24 | 19-DEC-16:01 | 14.32 | 5.15 | 96845089.55 | 62.67 | 10-DEC-00:30 | 14.32 | 5.15 |
Annual Sum or Average | 0.946528E+10 | 0.115497E+10 | ||||||||
Minimum of Months | 0.182418E+09 | 1646.51 | 4.40 | -1.8 | 87380765.54 | 56.69 | 4.40 | -1.8 | ||
Maximum of Months | 0.149545E+10 | 1863.85 | 26.88 | 23.69 | 99172257.74 | 63.33 | 25.92 | 22.23 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.338583E+11 | 17509.82 | 19-JAN-22:57 | 18.30 | 16.51 | 0.166777E+11 | 11361.27 | 20-JAN-22:00 | 10.60 | 7.51 |
February | 0.319000E+11 | 18713.82 | 28-FEB-22:53 | 17.30 | 10.02 | 0.155026E+11 | 11348.04 | 28-FEB-23:10 | 17.02 | 9.75 |
March | 0.378398E+11 | 20363.76 | 30-MAR-21:53 | 22.80 | 16.45 | 0.180172E+11 | 11359.02 | 06-MAR-23:10 | 22.80 | 16.45 |
April | 0.382547E+11 | 20447.83 | 18-APR-21:53 | 19.40 | 14.44 | 0.178009E+11 | 11355.86 | 25-APR-21:10 | 10.92 | 6.58 |
May | 0.415468E+11 | 21368.17 | 19-MAY-21:05 | 23.62 | 16.17 | 0.187968E+11 | 11348.57 | 16-MAY-22:10 | 23.62 | 16.17 |
June | 0.425502E+11 | 22558.57 | 13-JUN-22:00 | 27.20 | 20.99 | 0.184618E+11 | 11348.71 | 07-JUN-22:10 | 27.20 | 20.99 |
July | 0.447390E+11 | 23282.75 | 07-JUL-21:10 | 30.40 | 22.79 | 0.190443E+11 | 11348.72 | 13-JUL-22:10 | 23.48 | 21.29 |
August | 0.448837E+11 | 23011.32 | 18-AUG-21:10 | 30.82 | 22.88 | 0.191443E+11 | 11348.55 | 31-AUG-22:10 | 21.58 | 19.54 |
September | 0.403716E+11 | 21753.38 | 07-SEP-21:10 | 25.40 | 21.43 | 0.181837E+11 | 11349.89 | 15-SEP-23:19 | 24.03 | 17.59 |
October | 0.385805E+11 | 20240.98 | 18-OCT-21:53 | 22.80 | 21.95 | 0.180997E+11 | 11348.35 | 02-OCT-22:10 | 22.80 | 21.95 |
November | 0.355770E+11 | 18615.66 | 03-NOV-21:53 | 17.80 | 16.05 | 0.169955E+11 | 11348.08 | 03-NOV-22:10 | 17.80 | 16.05 |
December | 0.351816E+11 | 18140.87 | 12-DEC-22:54 | 18.30 | 14.87 | 0.170438E+11 | 11347.71 | 12-DEC-23:10 | 18.22 | 14.85 |
Annual Sum or Average | 0.465283E+12 | 0.213768E+12 | ||||||||
Minimum of Months | 0.319000E+11 | 17509.82 | 17.30 | 10.02 | 0.155026E+11 | 11347.71 | 10.60 | 6.58 | ||
Maximum of Months | 0.448837E+11 | 23282.75 | 30.82 | 22.88 | 0.191443E+11 | 11361.27 | 27.20 | 21.95 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.367780E+11 | 19440.19 | 19-JAN-22:57 | 18.30 | 16.51 | 0.170064E+11 | 11362.61 | 20-JAN-22:00 | 10.60 | 7.51 |
February | 0.346248E+11 | 20608.48 | 28-FEB-22:53 | 17.30 | 10.02 | 0.158156E+11 | 11348.36 | 14-FEB-22:49 | 17.30 | 10.02 |
March | 0.410309E+11 | 22153.53 | 30-MAR-21:53 | 22.80 | 16.45 | 0.183635E+11 | 11360.21 | 06-MAR-23:10 | 22.80 | 16.45 |
April | 0.414575E+11 | 22126.62 | 18-APR-21:53 | 19.40 | 14.44 | 0.180660E+11 | 11356.91 | 25-APR-21:10 | 10.92 | 6.58 |
May | 0.449317E+11 | 22945.95 | 30-MAY-21:05 | 23.62 | 21.16 | 0.189692E+11 | 11348.58 | 16-MAY-22:10 | 23.62 | 21.16 |
June | 0.456284E+11 | 24020.34 | 13-JUN-21:10 | 28.12 | 21.63 | 0.185452E+11 | 11348.71 | 07-JUN-22:10 | 28.12 | 21.63 |
July | 0.477770E+11 | 24589.00 | 07-JUL-21:10 | 30.40 | 22.79 | 0.191152E+11 | 11348.73 | 13-JUL-22:10 | 23.48 | 21.29 |
August | 0.478761E+11 | 24301.81 | 18-AUG-21:10 | 30.82 | 22.88 | 0.192037E+11 | 11348.56 | 31-AUG-22:10 | 21.58 | 19.54 |
September | 0.435027E+11 | 23227.54 | 07-SEP-21:10 | 25.40 | 21.43 | 0.183336E+11 | 11350.10 | 15-SEP-23:19 | 24.03 | 17.59 |
October | 0.417774E+11 | 22058.85 | 18-OCT-21:53 | 22.80 | 21.95 | 0.184180E+11 | 11348.36 | 02-OCT-22:10 | 22.80 | 21.95 |
November | 0.385396E+11 | 20577.63 | 03-NOV-21:53 | 17.80 | 16.05 | 0.173588E+11 | 11348.43 | 24-NOV-22:19 | 4.23 | 2.63 |
December | 0.381151E+11 | 20084.76 | 12-DEC-22:54 | 18.30 | 14.87 | 0.174124E+11 | 11348.36 | 08-DEC-23:30 | 18.30 | 14.87 |
Annual Sum or Average | 0.502039E+12 | 0.216608E+12 | ||||||||
Minimum of Months | 0.346248E+11 | 19440.19 | 17.30 | 10.02 | 0.158156E+11 | 11348.36 | 4.23 | 2.63 | ||
Maximum of Months | 0.478761E+11 | 24589.00 | 30.82 | 22.88 | 0.192037E+11 | 11362.61 | 28.12 | 21.95 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.485265E+11 | 26841.49 | 29-JAN-11:40 | 12.43 | 5.39 | 0.187054E+11 | 11319.55 | 07-JAN-18:19 | 12.43 | 5.39 |
February | 0.453480E+11 | 28008.56 | 26-FEB-11:40 | 22.07 | 11.70 | 0.169045E+11 | 11319.55 | 11-FEB-18:19 | 22.07 | 11.70 |
March | 0.530335E+11 | 28429.04 | 30-MAR-10:45 | 21.83 | 17.67 | 0.187385E+11 | 11319.51 | 04-MAR-18:19 | 21.83 | 17.67 |
April | 0.531660E+11 | 31287.24 | 15-APR-10:40 | 24.83 | 14.24 | 0.181412E+11 | 11319.69 | 15-APR-17:19 | 26.13 | 15.35 |
May | 0.567528E+11 | 30148.74 | 15-MAY-18:09 | 27.70 | 16.54 | 0.187610E+11 | 11329.92 | 13-MAY-17:00 | 27.70 | 16.54 |
June | 0.564873E+11 | 30496.53 | 25-JUN-10:40 | 29.80 | 23.29 | 0.181725E+11 | 11319.69 | 10-JUN-17:19 | 29.80 | 23.29 |
July | 0.588461E+11 | 30954.49 | 08-JUL-10:50 | 33.53 | 24.57 | 0.187775E+11 | 11319.65 | 15-JUL-17:19 | 33.30 | 24.04 |
August | 0.589261E+11 | 30803.03 | 27-AUG-10:50 | 30.03 | 22.67 | 0.187868E+11 | 11319.65 | 12-AUG-17:19 | 30.03 | 22.67 |
September | 0.549161E+11 | 30313.24 | 09-SEP-10:50 | 30.32 | 23.97 | 0.181604E+11 | 11319.65 | 23-SEP-17:19 | 27.23 | 18.81 |
October | 0.538981E+11 | 29044.62 | 09-OCT-10:50 | 24.03 | 18.11 | 0.187405E+11 | 11319.57 | 14-OCT-17:19 | 21.67 | 13.44 |
November | 0.501025E+11 | 27650.90 | 11-NOV-11:40 | 18.50 | 11.57 | 0.181189E+11 | 11319.52 | 04-NOV-17:19 | 18.50 | 11.57 |
December | 0.498621E+11 | 27242.60 | 12-DEC-11:50 | 20.22 | 16.28 | 0.187127E+11 | 11319.51 | 23-DEC-18:19 | 11.83 | 10.77 |
Annual Sum or Average | 0.639865E+12 | 0.220720E+12 | ||||||||
Minimum of Months | 0.453480E+11 | 26841.49 | 12.43 | 5.39 | 0.169045E+11 | 11319.51 | 11.83 | 5.39 | ||
Maximum of Months | 0.589261E+11 | 31287.24 | 33.53 | 24.57 | 0.187868E+11 | 11329.92 | 33.30 | 24.04 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.251687E+10 | 3902.17 | 31-JAN-22:10 | 14.52 | 10.85 | 0.126874E+10 | 747.31 | 31-JAN-22:10 | 14.52 | 10.85 |
February | 0.411750E+10 | 4139.99 | 28-FEB-22:10 | 18.63 | 10.80 | 0.114999E+10 | 790.69 | 28-FEB-22:10 | 18.63 | 10.80 |
March | 0.815055E+10 | 4466.15 | 30-MAR-21:10 | 23.72 | 16.82 | 0.129204E+10 | 846.13 | 30-MAR-21:19 | 23.53 | 16.75 |
April | 0.964203E+10 | 4655.40 | 17-APR-18:03 | 26.42 | 16.07 | 0.128679E+10 | 867.26 | 17-APR-21:10 | 20.00 | 14.08 |
May | 0.114354E+11 | 4852.12 | 20-MAY-15:30 | 28.05 | 18.93 | 0.139499E+10 | 905.14 | 19-MAY-21:10 | 28.05 | 18.93 |
June | 0.120588E+11 | 5092.59 | 24-JUN-18:02 | 31.93 | 22.02 | 0.145862E+10 | 950.26 | 13-JUN-21:10 | 31.93 | 22.02 |
July | 0.128531E+11 | 5955.60 | 08-JUL-17:13 | 34.40 | 23.36 | 0.154578E+10 | 998.54 | 07-JUL-21:10 | 34.40 | 23.36 |
August | 0.129649E+11 | 5310.36 | 18-AUG-15:50 | 34.90 | 23.12 | 0.156628E+10 | 995.35 | 18-AUG-21:10 | 30.82 | 22.88 |
September | 0.113268E+11 | 4997.60 | 07-SEP-16:00 | 31.70 | 23.71 | 0.137579E+10 | 932.06 | 07-SEP-21:10 | 25.40 | 21.43 |
October | 0.916955E+10 | 4581.63 | 11-OCT-15:50 | 26.28 | 17.62 | 0.130656E+10 | 847.87 | 10-OCT-21:10 | 26.28 | 17.62 |
November | 0.660308E+10 | 4150.17 | 05-NOV-15:10 | 23.98 | 18.38 | 0.123090E+10 | 772.26 | 02-NOV-21:30 | 23.98 | 18.38 |
December | 0.409235E+10 | 4035.11 | 12-DEC-22:10 | 18.30 | 14.66 | 0.126915E+10 | 768.28 | 12-DEC-23:10 | 18.22 | 14.85 |
Annual Sum or Average | 0.104931E+12 | 0.161456E+11 | ||||||||
Minimum of Months | 0.251687E+10 | 3902.17 | 14.52 | 10.80 | 0.114999E+10 | 747.31 | 14.52 | 10.80 | ||
Maximum of Months | 0.129649E+11 | 5955.60 | 34.90 | 23.71 | 0.156628E+10 | 998.54 | 34.40 | 23.36 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 5.70 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 9.92 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 1.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.80 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.333196E+09 | 1130.21 | 08-JAN-05:10 | -5.5 |
February | 0.167598E+09 | 1406.94 | 12-FEB-06:00 | -12.2 |
March | 1980338.94 | 133.17 | 22-MAR-09:20 | 4.40 |
April | 531875.21 | 126.55 | 06-APR-06:03 | 1.20 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 4761.02 | 8.87 | 31-OCT-08:03 | 7.80 |
November | 14153140.41 | 545.77 | 21-NOV-07:07 | -2.8 |
December | 58127701.93 | 683.71 | 01-DEC-07:07 | -3.8 |
Annual Sum or Average | 0.575592E+09 | |||
Minimum of Months | 0.00 | 0.00 | -12.2 | |
Maximum of Months | 0.333196E+09 | 1406.94 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 5.70 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 9.92 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 1.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.80 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.124631E+09 | 417.86 | 08-JAN-13:40 | -0.8 |
February | 79564665.95 | 397.01 | 12-FEB-13:20 | -0.5 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 4726694.88 | 110.84 | 18-DEC-10:23 | 1.95 |
Annual Sum or Average | 0.208922E+09 | |||
Minimum of Months | 0.00 | 0.00 | -0.8 | |
Maximum of Months | 0.124631E+09 | 417.86 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.232133E+09 | 392.74 | 08-JAN-06:00 | -5.0 |
February | 0.133278E+09 | 423.97 | 12-FEB-06:00 | -12.2 |
March | 8145.73 | 5.99 | 19-MAR-05:00 | 2.20 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 2956874.46 | 87.31 | 22-NOV-08:04 | -2.2 |
December | 33633983.70 | 203.42 | 18-DEC-08:04 | -5.0 |
Annual Sum or Average | 0.402010E+09 | |||
Minimum of Months | 0.00 | 0.00 | -12.2 | |
Maximum of Months | 0.232133E+09 | 423.97 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 5.70 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 9.92 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 1.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.80 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 350215.93 | 209.88 | 09-JAN-09:13 | -3.1 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 9.92 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 1.80 |
Annual Sum or Average | 350215.93 | |||
Minimum of Months | 0.00 | 0.00 | -3.1 | |
Maximum of Months | 350215.93 | 209.88 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 5.70 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 9.92 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 1.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.80 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.830302E+09 | 1500.95 | 07-JAN-16:13 | -4.3 |
February | 0.475131E+09 | 1524.74 | 12-FEB-19:09 | 0.50 |
March | 71560962.30 | 1400.70 | 23-MAR-08:62 | 6.97 |
April | 22294097.52 | 1399.19 | 06-APR-08:62 | 5.37 |
May | 2211205.55 | 1302.95 | 24-MAY-15:04 | 18.30 |
June | 1249604.63 | 1044.63 | 04-JUN-08:04 | 22.57 |
July | 775374.23 | 838.81 | 03-JUL-08:04 | 24.60 |
August | 865687.03 | 971.59 | 09-AUG-08:04 | 26.38 |
September | 1989751.61 | 1131.17 | 28-SEP-15:04 | 19.22 |
October | 43893278.07 | 1415.15 | 26-OCT-08:61 | 5.05 |
November | 0.159410E+09 | 1535.73 | 22-NOV-09:09 | 1.05 |
December | 0.487960E+09 | 1434.54 | 01-DEC-09:01 | -0.2 |
Annual Sum or Average | 0.209764E+10 | |||
Minimum of Months | 775374.23 | 838.81 | -4.3 | |
Maximum of Months | 0.830302E+09 | 1535.73 | 26.38 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.107909E+10 | 1520.91 | 27-JAN-09:11 | -4.4 |
February | 0.624821E+09 | 1544.78 | 04-FEB-19:09 | 2.62 |
March | 0.100902E+09 | 1417.31 | 07-MAR-09:01 | 6.47 |
April | 26602295.62 | 1404.78 | 06-APR-08:62 | 5.37 |
May | 1856194.74 | 1035.37 | 13-MAY-08:53 | 20.00 |
June | 566917.16 | 971.92 | 07-JUN-08:53 | 18.90 |
July | 225643.52 | 316.98 | 15-JUL-08:05 | 26.97 |
August | 368365.67 | 963.09 | 09-AUG-08:04 | 26.38 |
September | 1717961.82 | 994.23 | 23-SEP-08:53 | 22.20 |
October | 60141297.57 | 1470.57 | 26-OCT-08:09 | 5.05 |
November | 0.256799E+09 | 1450.12 | 22-NOV-09:01 | 1.05 |
December | 0.693040E+09 | 1540.46 | 07-DEC-09:09 | 3.45 |
Annual Sum or Average | 0.284613E+10 | |||
Minimum of Months | 225643.52 | 316.98 | -4.4 | |
Maximum of Months | 0.107909E+10 | 1544.78 | 26.97 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 5.70 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 9.92 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 1.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.80 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.136716E+09 | 435.69 | 03-JAN-16:10 | 2.80 |
February | 77264949.99 | 458.17 | 23-FEB-16:03 | 16.02 |
March | 5916843.91 | 446.78 | 07-MAR-16:03 | 15.78 |
April | 5495419.41 | 433.31 | 26-APR-15:04 | 15.68 |
May | 459110.50 | 349.93 | 24-MAY-15:06 | 18.30 |
June | 81274.35 | 257.05 | 07-JUN-15:06 | 23.98 |
July | 39746.17 | 214.08 | 28-JUL-15:06 | 19.40 |
August | 139182.93 | 169.61 | 30-AUG-21:56 | 22.80 |
September | 278304.88 | 259.33 | 19-SEP-08:54 | 19.40 |
October | 1705548.29 | 423.25 | 23-OCT-15:05 | 17.62 |
November | 14510928.29 | 435.73 | 25-NOV-19:03 | 12.43 |
December | 47270625.64 | 435.08 | 09-DEC-09:03 | 3.68 |
Annual Sum or Average | 0.289878E+09 | |||
Minimum of Months | 39746.17 | 169.61 | 2.80 | |
Maximum of Months | 0.136716E+09 | 458.17 | 23.98 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.840054E+09 | 1502.66 | 26-JAN-19:09 | -0.7 |
February | 0.470680E+09 | 1455.88 | 11-FEB-19:13 | -6.3 |
March | 78601198.39 | 1391.75 | 23-MAR-08:62 | 6.97 |
April | 21907917.33 | 1156.42 | 03-APR-15:04 | 15.78 |
May | 809969.06 | 773.97 | 09-MAY-18:04 | 19.63 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 127750.92 | 605.53 | 28-JUL-18:05 | 18.90 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 743172.79 | 719.68 | 01-SEP-08:05 | 20.18 |
October | 45709326.77 | 1392.38 | 31-OCT-08:62 | 7.80 |
November | 0.159924E+09 | 1418.29 | 30-NOV-16:01 | 7.20 |
December | 0.479580E+09 | 1423.67 | 25-DEC-16:01 | 6.02 |
Annual Sum or Average | 0.209814E+10 | |||
Minimum of Months | 0.00 | 0.00 | -6.3 | |
Maximum of Months | 0.840054E+09 | 1502.66 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.109095E+10 | 1524.49 | 17-JAN-16:10 | 4.32 |
February | 0.609567E+09 | 1472.03 | 11-FEB-19:13 | -6.3 |
March | 0.106921E+09 | 1395.16 | 23-MAR-08:62 | 6.97 |
April | 26491703.81 | 1172.67 | 03-APR-15:04 | 15.78 |
May | 648788.93 | 808.18 | 15-MAY-21:54 | 22.20 |
June | 146976.52 | 569.04 | 07-JUN-21:54 | 17.80 |
July | 50830.09 | 269.73 | 29-JUL-08:55 | 17.80 |
August | 55693.23 | 264.22 | 30-AUG-21:54 | 22.80 |
September | 977266.20 | 852.76 | 29-SEP-15:04 | 21.52 |
October | 64706037.16 | 1395.40 | 31-OCT-08:62 | 7.80 |
November | 0.249171E+09 | 1423.20 | 30-NOV-16:01 | 7.20 |
December | 0.676966E+09 | 1435.26 | 02-DEC-19:01 | 0.92 |
Annual Sum or Average | 0.282666E+10 | |||
Minimum of Months | 50830.09 | 264.22 | -6.3 | |
Maximum of Months | 0.109095E+10 | 1524.49 | 22.80 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 47296347.10 | 563.86 | 07-JAN-17:00 | -5.0 |
February | 9713187.34 | 284.14 | 12-FEB-08:03 | -11.9 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 1.80 |
Annual Sum or Average | 57009534.45 | |||
Minimum of Months | 0.00 | 0.00 | -11.9 | |
Maximum of Months | 47296347.10 | 563.86 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.128977E+10 | 1891.56 | 26-JAN-19:09 | -0.7 |
February | 0.763731E+09 | 1849.65 | 13-FEB-19:09 | 4.90 |
March | 0.161306E+09 | 1716.57 | 07-MAR-09:01 | 6.47 |
April | 48716644.20 | 1716.20 | 26-APR-08:61 | 8.35 |
May | 2195303.93 | 1199.73 | 24-MAY-15:04 | 18.30 |
June | 1248209.25 | 1002.62 | 15-JUN-08:04 | 22.57 |
July | 737654.34 | 877.53 | 03-JUL-08:04 | 24.60 |
August | 923064.97 | 940.68 | 26-AUG-08:04 | 23.07 |
September | 3102046.32 | 1093.03 | 28-SEP-15:04 | 19.22 |
October | 0.105127E+09 | 1733.04 | 26-OCT-08:61 | 5.05 |
November | 0.315728E+09 | 1749.96 | 22-NOV-09:01 | 1.05 |
December | 0.826487E+09 | 1883.12 | 17-DEC-19:09 | -0.2 |
Annual Sum or Average | 0.351907E+10 | |||
Minimum of Months | 737654.34 | 877.53 | -0.7 | |
Maximum of Months | 0.128977E+10 | 1891.56 | 24.60 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.160447E+10 | 1870.40 | 27-JAN-09:11 | -4.4 |
February | 0.957817E+09 | 1868.31 | 12-FEB-09:13 | -9.8 |
March | 0.206527E+09 | 1733.84 | 07-MAR-09:01 | 6.47 |
April | 53448449.26 | 1719.01 | 26-APR-08:61 | 8.35 |
May | 1769420.14 | 1061.70 | 24-MAY-15:04 | 18.30 |
June | 616014.25 | 1200.82 | 10-JUN-08:53 | 20.60 |
July | 144313.52 | 438.00 | 28-JUL-21:54 | 17.80 |
August | 358999.37 | 966.06 | 09-AUG-08:04 | 26.38 |
September | 2178947.94 | 1247.70 | 28-SEP-15:04 | 19.22 |
October | 0.134116E+09 | 1749.65 | 26-OCT-08:61 | 5.05 |
November | 0.461418E+09 | 1777.43 | 22-NOV-09:01 | 1.05 |
December | 0.109255E+10 | 1793.16 | 18-DEC-09:15 | -1.3 |
Annual Sum or Average | 0.451541E+10 | |||
Minimum of Months | 144313.52 | 438.00 | -9.8 | |
Maximum of Months | 0.160447E+10 | 1870.40 | 26.38 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.350301E+09 | 978.13 | 03-JAN-19:09 | 2.80 |
February | 0.190007E+09 | 929.14 | 12-FEB-09:13 | -9.8 |
March | 27282562.24 | 901.53 | 02-MAR-16:04 | 16.52 |
April | 12113520.00 | 899.21 | 06-APR-08:62 | 5.37 |
May | 649078.64 | 622.28 | 10-MAY-18:04 | 20.92 |
June | 149758.01 | 356.30 | 08-JUN-08:03 | 17.57 |
July | 140269.93 | 245.62 | 28-JUL-18:05 | 18.90 |
August | 108333.02 | 170.38 | 11-AUG-08:06 | 23.48 |
September | 505763.72 | 378.34 | 19-SEP-08:04 | 18.07 |
October | 14751712.95 | 899.86 | 31-OCT-08:62 | 7.80 |
November | 48132866.09 | 917.68 | 30-NOV-16:01 | 7.20 |
December | 0.171990E+09 | 921.79 | 25-DEC-16:01 | 6.02 |
Annual Sum or Average | 0.816133E+09 | |||
Minimum of Months | 108333.02 | 170.38 | -9.8 | |
Maximum of Months | 0.350301E+09 | 978.13 | 23.48 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 5.70 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 9.92 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 1.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.80 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 5.70 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 9.92 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 1.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.80 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 5.70 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 9.92 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 1.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.80 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.583062E+09 | 2244.20 | 08-JAN-06:00 | -5.0 |
February | 0.302473E+09 | 2797.60 | 12-FEB-06:00 | -12.2 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 16896694.86 | 893.93 | 22-NOV-07:07 | -3.2 |
December | 80118629.35 | 1412.07 | 18-DEC-07:07 | -5.1 |
Annual Sum or Average | 0.982550E+09 | |||
Minimum of Months | 0.00 | 0.00 | -12.2 | |
Maximum of Months | 0.583062E+09 | 2797.60 | 25.13 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.136942E+11 | 13190.31 | 02-JAN-20:10 | 0.121516E+11 | 9632.53 | 02-JAN-20:10 |
February | 0.123646E+11 | 13190.31 | 01-FEB-20:10 | 0.109726E+11 | 9632.53 | 01-FEB-20:10 |
March | 0.137364E+11 | 13190.31 | 01-MAR-20:10 | 0.121771E+11 | 9632.53 | 01-MAR-20:10 |
April | 0.132299E+11 | 13190.31 | 03-APR-19:10 | 0.117446E+11 | 9632.53 | 03-APR-19:10 |
May | 0.137180E+11 | 13190.31 | 01-MAY-19:10 | 0.121662E+11 | 9632.53 | 01-MAY-19:10 |
June | 0.132906E+11 | 13190.31 | 01-JUN-19:10 | 0.117829E+11 | 9632.53 | 01-JUN-19:10 |
July | 0.136573E+11 | 13190.31 | 03-JUL-19:10 | 0.121279E+11 | 9632.53 | 03-JUL-19:10 |
August | 0.137417E+11 | 13190.31 | 01-AUG-19:10 | 0.121808E+11 | 9632.53 | 01-AUG-19:10 |
September | 0.132352E+11 | 13190.31 | 01-SEP-19:10 | 0.117482E+11 | 9632.53 | 01-SEP-19:10 |
October | 0.136889E+11 | 13190.31 | 02-OCT-19:10 | 0.121479E+11 | 9632.53 | 02-OCT-19:10 |
November | 0.132800E+11 | 13190.31 | 01-NOV-19:10 | 0.117774E+11 | 9632.53 | 01-NOV-19:10 |
December | 0.136573E+11 | 13190.31 | 01-DEC-20:10 | 0.121279E+11 | 9632.53 | 01-DEC-20:10 |
Annual Sum or Average | 0.161294E+12 | 0.143105E+12 | ||||
Minimum of Months | 0.123646E+11 | 13190.31 | 0.109726E+11 | 9632.53 | ||
Maximum of Months | 0.137417E+11 | 13190.31 | 0.121808E+11 | 9632.53 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.620421E+09 | 597.59 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.560184E+09 | 597.59 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.622334E+09 | 597.59 | 01-MAR-20:10 | 0.866718E+09 | 685.60 | 01-MAR-20:10 |
April | 0.599386E+09 | 597.59 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.621497E+09 | 597.59 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.602135E+09 | 597.59 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.618748E+09 | 597.59 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.622573E+09 | 597.59 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.599625E+09 | 597.59 | 01-SEP-19:10 | 0.836191E+09 | 685.60 | 01-SEP-19:10 |
October | 0.620182E+09 | 597.59 | 02-OCT-19:10 | 0.864640E+09 | 685.60 | 02-OCT-19:10 |
November | 0.601657E+09 | 597.59 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.618748E+09 | 597.59 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.730749E+10 | 0.101856E+11 | ||||
Minimum of Months | 0.560184E+09 | 597.59 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.622573E+09 | 597.59 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.718450E+09 | 692.02 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.648695E+09 | 692.02 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.720665E+09 | 692.02 | 01-MAR-20:10 | 0.100366E+10 | 793.93 | 01-MAR-20:10 |
April | 0.694091E+09 | 692.02 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.719696E+09 | 692.02 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.697275E+09 | 692.02 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.716513E+09 | 692.02 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.720942E+09 | 692.02 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.694368E+09 | 692.02 | 01-SEP-19:10 | 0.968312E+09 | 793.93 | 01-SEP-19:10 |
October | 0.718174E+09 | 692.02 | 02-OCT-19:10 | 0.100126E+10 | 793.93 | 02-OCT-19:10 |
November | 0.696721E+09 | 692.02 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.716513E+09 | 692.02 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.846210E+10 | 0.117950E+11 | ||||
Minimum of Months | 0.648695E+09 | 692.02 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.720942E+09 | 692.02 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.710312E+09 | 684.18 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.641347E+09 | 684.18 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.712502E+09 | 684.18 | 01-MAR-20:10 | 0.106120E+10 | 839.45 | 01-MAR-20:10 |
April | 0.686229E+09 | 684.18 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.711544E+09 | 684.18 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.689376E+09 | 684.18 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.708397E+09 | 684.18 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.712775E+09 | 684.18 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.686503E+09 | 684.18 | 01-SEP-19:10 | 0.102382E+10 | 839.45 | 01-SEP-19:10 |
October | 0.710039E+09 | 684.18 | 02-OCT-19:10 | 0.105866E+10 | 839.45 | 02-OCT-19:10 |
November | 0.688829E+09 | 684.18 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.708397E+09 | 684.18 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.836625E+10 | 0.124712E+11 | ||||
Minimum of Months | 0.641347E+09 | 684.18 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.712775E+09 | 684.18 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.261454E+09 | 251.84 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.236069E+09 | 251.84 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.262260E+09 | 251.84 | 01-MAR-20:10 | 0.306128E+09 | 242.16 | 01-MAR-20:10 |
April | 0.252589E+09 | 251.84 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.261907E+09 | 251.84 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.253748E+09 | 251.84 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.260749E+09 | 251.84 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.262360E+09 | 251.84 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.252690E+09 | 251.84 | 01-SEP-19:10 | 0.295345E+09 | 242.16 | 01-SEP-19:10 |
October | 0.261353E+09 | 251.84 | 02-OCT-19:10 | 0.305393E+09 | 242.16 | 02-OCT-19:10 |
November | 0.253546E+09 | 251.84 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.260749E+09 | 251.84 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.307947E+10 | 0.359760E+10 | ||||
Minimum of Months | 0.236069E+09 | 251.84 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.262360E+09 | 251.84 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.337502E+09 | 325.08 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.304733E+09 | 325.08 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.338542E+09 | 325.08 | 01-MAR-20:10 | 0.578079E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.326059E+09 | 325.08 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.338087E+09 | 325.08 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.327554E+09 | 325.08 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.336592E+09 | 325.08 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.338672E+09 | 325.08 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.326189E+09 | 325.08 | 01-SEP-19:10 | 0.557718E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.337372E+09 | 325.08 | 02-OCT-19:10 | 0.576693E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.327294E+09 | 325.08 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.336592E+09 | 325.08 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.397519E+10 | 0.679355E+11 | ||||
Minimum of Months | 0.304733E+09 | 325.08 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.338672E+09 | 325.08 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.134280E+10 | 1701.53 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.120899E+10 | 1701.53 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.123603E+10 | 1701.53 | 01-MAR-20:10 | 0.122027E+10 | 965.27 | 01-MAR-20:10 |
April | 0.111336E+10 | 1701.53 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.108100E+10 | 1701.53 | 01-MAY-19:19 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.101086E+10 | 1701.53 | 01-JUN-19:30 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.106112E+10 | 1701.53 | 03-JUL-19:30 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.111364E+10 | 1701.53 | 01-AUG-19:10 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.117807E+10 | 1701.53 | 01-SEP-19:10 | 0.117729E+10 | 965.27 | 01-SEP-19:10 |
October | 0.130270E+10 | 1701.53 | 02-OCT-19:10 | 0.121734E+10 | 965.27 | 02-OCT-19:10 |
November | 0.128147E+10 | 1701.53 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.133830E+10 | 1701.53 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.142683E+11 | 0.143405E+11 | ||||
Minimum of Months | 0.101086E+10 | 1701.53 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.134280E+10 | 1701.53 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.946100E+10 | 9504.80 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.854664E+10 | 9504.80 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.940393E+10 | 9504.80 | 01-MAR-20:10 | 0.126786E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.900238E+10 | 9504.80 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.926941E+10 | 9504.80 | 01-MAY-19:10 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.894715E+10 | 9504.80 | 01-JUN-19:19 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.921296E+10 | 9504.80 | 03-JUL-19:30 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.930143E+10 | 9504.80 | 01-AUG-19:10 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.905589E+10 | 9504.80 | 01-SEP-19:10 | 0.122320E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.943856E+10 | 9504.80 | 02-OCT-19:10 | 0.126482E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.915501E+10 | 9504.80 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.943598E+10 | 9504.80 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.110230E+12 | 0.148998E+12 | ||||
Minimum of Months | 0.854664E+10 | 9504.80 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.946100E+10 | 9504.80 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196602E+09 | 177.88 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.177551E+09 | 177.88 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.195039E+09 | 177.88 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.190486E+09 | 177.88 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.195821E+09 | 177.88 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.188975E+09 | 177.88 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.197358E+09 | 177.88 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.195039E+09 | 177.88 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.190538E+09 | 177.88 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.196576E+09 | 177.88 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.189731E+09 | 177.88 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.197383E+09 | 177.88 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.231110E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.177551E+09 | 177.88 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.197383E+09 | 177.88 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196579E+09 | 177.86 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.177530E+09 | 177.86 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.195017E+09 | 177.86 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.190464E+09 | 177.86 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.195798E+09 | 177.86 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.188953E+09 | 177.86 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.197334E+09 | 177.86 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.195017E+09 | 177.86 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.190515E+09 | 177.86 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.196553E+09 | 177.86 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.189708E+09 | 177.86 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.197360E+09 | 177.86 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.231083E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.177530E+09 | 177.86 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.197360E+09 | 177.86 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123557E+09 | 111.79 | 01-JAN-19:10 | 0.217935E+09 | 232.19 | 01-JAN-08:09 |
February | 0.111584E+09 | 111.79 | 01-FEB-20:10 | 0.196843E+09 | 232.19 | 01-FEB-07:10 |
March | 0.122575E+09 | 111.79 | 01-MAR-20:10 | 0.217824E+09 | 232.19 | 01-MAR-07:10 |
April | 0.119713E+09 | 111.79 | 01-APR-18:10 | 0.210923E+09 | 232.19 | 01-APR-07:10 |
May | 0.123066E+09 | 111.79 | 01-MAY-19:10 | 0.217879E+09 | 232.19 | 01-MAY-06:10 |
June | 0.118764E+09 | 111.79 | 01-JUN-19:10 | 0.210812E+09 | 232.19 | 01-JUN-06:10 |
July | 0.124032E+09 | 111.79 | 01-JUL-18:10 | 0.217991E+09 | 232.19 | 01-JUL-07:10 |
August | 0.122575E+09 | 111.79 | 01-AUG-19:10 | 0.217824E+09 | 232.19 | 01-AUG-06:10 |
September | 0.119746E+09 | 111.79 | 01-SEP-19:10 | 0.210923E+09 | 232.19 | 01-SEP-06:10 |
October | 0.123541E+09 | 111.79 | 01-OCT-18:10 | 0.217935E+09 | 232.19 | 01-OCT-07:10 |
November | 0.119238E+09 | 111.79 | 01-NOV-19:10 | 0.210867E+09 | 232.19 | 01-NOV-06:10 |
December | 0.124048E+09 | 111.79 | 01-DEC-20:10 | 0.217991E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.145244E+10 | 0.256575E+10 | ||||
Minimum of Months | 0.111584E+09 | 111.79 | 0.196843E+09 | 232.19 | ||
Maximum of Months | 0.124048E+09 | 111.79 | 0.217991E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123591E+09 | 111.82 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 0.111614E+09 | 111.82 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 0.122608E+09 | 111.82 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 0.119746E+09 | 111.82 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 0.123099E+09 | 111.82 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 0.118796E+09 | 111.82 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 0.124066E+09 | 111.82 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 0.122608E+09 | 111.82 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 0.119778E+09 | 111.82 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 0.123574E+09 | 111.82 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 0.119271E+09 | 111.82 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 0.124082E+09 | 111.82 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.145283E+10 | 0.256645E+10 | ||||
Minimum of Months | 0.111614E+09 | 111.82 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 0.124082E+09 | 111.82 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196602E+09 | 177.88 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.177551E+09 | 177.88 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.195039E+09 | 177.88 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.190486E+09 | 177.88 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.195821E+09 | 177.88 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.188975E+09 | 177.88 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.197358E+09 | 177.88 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.195039E+09 | 177.88 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.190538E+09 | 177.88 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.196576E+09 | 177.88 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.189731E+09 | 177.88 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.197383E+09 | 177.88 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.231110E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.177551E+09 | 177.88 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.197383E+09 | 177.88 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196579E+09 | 177.86 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.177530E+09 | 177.86 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.195017E+09 | 177.86 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.190464E+09 | 177.86 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.195798E+09 | 177.86 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.188953E+09 | 177.86 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.197334E+09 | 177.86 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.195017E+09 | 177.86 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.190515E+09 | 177.86 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.196553E+09 | 177.86 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.189708E+09 | 177.86 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.197360E+09 | 177.86 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.231083E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.177530E+09 | 177.86 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.197360E+09 | 177.86 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.193865E+10 | 1867.32 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.175042E+10 | 1867.32 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.194462E+10 | 1867.32 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.187292E+10 | 1867.32 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.194201E+10 | 1867.32 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.188151E+10 | 1867.32 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.193342E+10 | 1867.32 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.194537E+10 | 1867.32 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.187367E+10 | 1867.32 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.193790E+10 | 1867.32 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.188002E+10 | 1867.32 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.193342E+10 | 1867.32 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.228339E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.175042E+10 | 1867.32 | 0.00 | 0.00 | |
Maximum of Months | 0.194537E+10 | 1867.32 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196602E+09 | 177.88 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.177551E+09 | 177.88 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.195039E+09 | 177.88 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.190486E+09 | 177.88 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.195821E+09 | 177.88 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.188975E+09 | 177.88 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.197358E+09 | 177.88 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.195039E+09 | 177.88 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.190538E+09 | 177.88 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.196576E+09 | 177.88 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.189731E+09 | 177.88 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.197383E+09 | 177.88 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.231110E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.177551E+09 | 177.88 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.197383E+09 | 177.88 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196579E+09 | 177.86 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.177530E+09 | 177.86 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.195017E+09 | 177.86 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.190464E+09 | 177.86 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.195798E+09 | 177.86 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.188953E+09 | 177.86 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.197334E+09 | 177.86 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.195017E+09 | 177.86 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.190515E+09 | 177.86 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.196553E+09 | 177.86 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.189708E+09 | 177.86 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.197360E+09 | 177.86 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.231083E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.177530E+09 | 177.86 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.197360E+09 | 177.86 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123591E+09 | 111.82 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 0.111614E+09 | 111.82 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 0.122608E+09 | 111.82 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 0.119746E+09 | 111.82 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 0.123099E+09 | 111.82 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 0.118796E+09 | 111.82 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 0.124066E+09 | 111.82 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 0.122608E+09 | 111.82 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 0.119778E+09 | 111.82 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 0.123574E+09 | 111.82 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 0.119271E+09 | 111.82 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 0.124082E+09 | 111.82 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.145283E+10 | 0.256645E+10 | ||||
Minimum of Months | 0.111614E+09 | 111.82 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 0.124082E+09 | 111.82 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.282832E+10 | 2988.03 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.254291E+10 | 2988.03 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.269152E+10 | 2988.03 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.249082E+10 | 2988.03 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.246334E+10 | 2988.03 | 01-MAY-19:19 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.233884E+10 | 2988.03 | 01-JUN-19:30 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.243716E+10 | 2988.03 | 03-JUL-19:30 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.251767E+10 | 2988.03 | 01-AUG-19:19 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.256392E+10 | 2988.03 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.279095E+10 | 2988.03 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.271429E+10 | 2988.03 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.282403E+10 | 2988.03 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.312038E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.233884E+10 | 2988.03 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.282832E+10 | 2988.03 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.282832E+10 | 2988.03 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.254291E+10 | 2988.03 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.269152E+10 | 2988.03 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.249082E+10 | 2988.03 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.246334E+10 | 2988.03 | 01-MAY-19:19 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.233884E+10 | 2988.03 | 01-JUN-19:30 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.243716E+10 | 2988.03 | 03-JUL-19:30 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.251767E+10 | 2988.03 | 01-AUG-19:19 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.256392E+10 | 2988.03 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.279095E+10 | 2988.03 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.271429E+10 | 2988.03 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.282403E+10 | 2988.03 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.312038E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.233884E+10 | 2988.03 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.282832E+10 | 2988.03 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.110133E+10 | 1060.81 | 02-JAN-20:10 | 0.368383E+11 | 16487.34 | 01-JAN-07:10 |
February | 0.994402E+09 | 1060.81 | 01-FEB-20:10 | 0.332733E+11 | 16487.34 | 01-FEB-07:10 |
March | 0.110473E+10 | 1060.81 | 01-MAR-20:10 | 0.368383E+11 | 16487.34 | 01-MAR-07:10 |
April | 0.106399E+10 | 1060.81 | 03-APR-19:10 | 0.356500E+11 | 16487.34 | 01-APR-06:10 |
May | 0.110324E+10 | 1060.81 | 01-MAY-19:10 | 0.368383E+11 | 16487.34 | 01-MAY-06:10 |
June | 0.106887E+10 | 1060.81 | 01-JUN-19:10 | 0.356500E+11 | 16487.34 | 01-JUN-06:10 |
July | 0.109836E+10 | 1060.81 | 03-JUL-19:10 | 0.368383E+11 | 16487.34 | 01-JUL-06:10 |
August | 0.110515E+10 | 1060.81 | 01-AUG-19:10 | 0.368383E+11 | 16487.34 | 01-AUG-06:10 |
September | 0.106442E+10 | 1060.81 | 01-SEP-19:10 | 0.356500E+11 | 16487.34 | 01-SEP-06:10 |
October | 0.110091E+10 | 1060.81 | 02-OCT-19:10 | 0.368383E+11 | 16487.34 | 01-OCT-06:10 |
November | 0.106802E+10 | 1060.81 | 01-NOV-19:10 | 0.356500E+11 | 16487.34 | 01-NOV-06:10 |
December | 0.109836E+10 | 1060.81 | 01-DEC-20:10 | 0.368383E+11 | 16487.34 | 01-DEC-07:10 |
Annual Sum or Average | 0.129718E+11 | 0.433742E+12 | ||||
Minimum of Months | 0.994402E+09 | 1060.81 | 0.332733E+11 | 16487.34 | ||
Maximum of Months | 0.110515E+10 | 1060.81 | 0.368383E+11 | 16487.34 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.205176E+10 | 1976.27 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.185255E+10 | 1976.27 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.205809E+10 | 1976.27 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.198220E+10 | 1976.27 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.205532E+10 | 1976.27 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.199129E+10 | 1976.27 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.204623E+10 | 1976.27 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.205888E+10 | 1976.27 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.198299E+10 | 1976.27 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.205097E+10 | 1976.27 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.198971E+10 | 1976.27 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.204623E+10 | 1976.27 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.241662E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.185255E+10 | 1976.27 | 0.00 | 0.00 | |
Maximum of Months | 0.205888E+10 | 1976.27 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.136942E+11 | 0.121516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.123646E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196682E+11 | 0.137364E+11 | 0.121771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.132299E+11 | 0.117446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.137180E+11 | 0.121662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.132906E+11 | 0.117829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.136573E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.137417E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189689E+11 | 0.132352E+11 | 0.117482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195854E+11 | 0.136889E+11 | 0.121479E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.132800E+11 | 0.117774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.136573E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230861E+12 | 0.161294E+12 | 0.143105E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.176991E+11 | 0.123646E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196682E+11 | 0.137417E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.620421E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 347.10 | 0.254477E+09 |
February | 0.179968E+10 | 0.560184E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 298809.70 | 0.176797E+09 |
March | 0.199990E+10 | 0.622334E+09 | 0.866718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2035712.81 | 0.110407E+09 |
April | 0.192973E+10 | 0.599386E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8335696.82 | 66490611.23 |
May | 0.199475E+10 | 0.621497E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19503394.70 | 29828915.39 |
June | 0.193394E+10 | 0.602135E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 43683831.93 | 8600995.26 |
July | 0.199054E+10 | 0.618748E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 52272714.82 | 3210426.78 |
August | 0.199896E+10 | 0.622573E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 51562878.26 | 623001.96 |
September | 0.192879E+10 | 0.599625E+09 | 0.836191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21632774.50 | 15453655.18 |
October | 0.199148E+10 | 0.620182E+09 | 0.864640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4112896.45 | 84088527.26 |
November | 0.192552E+10 | 0.601657E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 554803.49 | 0.131338E+09 |
December | 0.199054E+10 | 0.618748E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20636.43 | 0.197161E+09 |
Annual Sum or Average | 0.234744E+11 | 0.730749E+10 | 0.101856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204014E+09 | 0.107848E+10 |
Minimum of Months | 0.179968E+10 | 0.560184E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 347.10 | 623001.96 |
Maximum of Months | 0.199990E+10 | 0.622573E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 52272714.82 | 0.254477E+09 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.718450E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 133.39 | 98294487.67 |
February | 0.208403E+10 | 0.648695E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 307233.85 | 68575522.45 |
March | 0.231589E+10 | 0.720665E+09 | 0.100366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1061774.06 | 43827255.42 |
April | 0.223463E+10 | 0.694091E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3904065.41 | 28027052.62 |
May | 0.230993E+10 | 0.719696E+09 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7938667.72 | 14312467.64 |
June | 0.223950E+10 | 0.697275E+09 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16684729.03 | 5222110.49 |
July | 0.230505E+10 | 0.716513E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19958392.51 | 2558798.27 |
August | 0.231480E+10 | 0.720942E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19781709.10 | 785491.10 |
September | 0.223354E+10 | 0.694368E+09 | 0.968312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8802379.77 | 8089498.55 |
October | 0.230614E+10 | 0.718174E+09 | 0.100126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2241054.77 | 33864787.76 |
November | 0.222975E+10 | 0.696721E+09 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 281883.53 | 51223220.25 |
December | 0.230505E+10 | 0.716513E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 38197.30 | 76168820.00 |
Annual Sum or Average | 0.271834E+11 | 0.846210E+10 | 0.117950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 81000220.44 | 0.430950E+09 |
Minimum of Months | 0.208403E+10 | 0.648695E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 133.39 | 785491.10 |
Maximum of Months | 0.231589E+10 | 0.720942E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19958392.51 | 98294487.67 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.487480E+09 | 0.710312E+09 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 313.75 | 0.231113E+09 |
February | 0.440737E+09 | 0.641347E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 777788.41 | 0.160041E+09 |
March | 0.489771E+09 | 0.712502E+09 | 0.106120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2916927.58 | 99055473.88 |
April | 0.472586E+09 | 0.686229E+09 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10159876.15 | 61552257.66 |
May | 0.488511E+09 | 0.711544E+09 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19596396.69 | 30429619.30 |
June | 0.473617E+09 | 0.689376E+09 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39270130.89 | 11312858.88 |
July | 0.487480E+09 | 0.708397E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46615909.68 | 5934165.70 |
August | 0.489542E+09 | 0.712775E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47012258.24 | 1617462.54 |
September | 0.472357E+09 | 0.686503E+09 | 0.102382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21664970.73 | 17403956.57 |
October | 0.487709E+09 | 0.710039E+09 | 0.105866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6144387.70 | 74846280.33 |
November | 0.471555E+09 | 0.688829E+09 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 741480.68 | 0.117079E+09 |
December | 0.487480E+09 | 0.708397E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 94227.55 | 0.177933E+09 |
Annual Sum or Average | 0.574883E+10 | 0.836625E+10 | 0.124712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194995E+09 | 0.988319E+09 |
Minimum of Months | 0.440737E+09 | 0.641347E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 313.75 | 1617462.54 |
Maximum of Months | 0.489771E+09 | 0.712775E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47012258.24 | 0.231113E+09 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.374985E+09 | 0.261454E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 180.92 | 0.133313E+09 |
February | 0.339028E+09 | 0.236069E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 450482.30 | 92238245.99 |
March | 0.376747E+09 | 0.262260E+09 | 0.306128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1742580.86 | 56795142.80 |
April | 0.363528E+09 | 0.252589E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6007074.65 | 34769227.22 |
May | 0.375778E+09 | 0.261907E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11642683.16 | 16568489.05 |
June | 0.364321E+09 | 0.253748E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23373694.64 | 5888109.56 |
July | 0.374985E+09 | 0.260749E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 27775128.05 | 2891665.61 |
August | 0.376571E+09 | 0.262360E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 28303353.37 | 708757.82 |
September | 0.363352E+09 | 0.252690E+09 | 0.295345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13203476.09 | 9197169.32 |
October | 0.375161E+09 | 0.261353E+09 | 0.305393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3681638.94 | 42362010.81 |
November | 0.362735E+09 | 0.253546E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 436826.08 | 67206532.30 |
December | 0.374985E+09 | 0.260749E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 54364.10 | 0.102592E+09 |
Annual Sum or Average | 0.442217E+10 | 0.307947E+10 | 0.359760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116671E+09 | 0.564531E+09 |
Minimum of Months | 0.339028E+09 | 0.236069E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 180.92 | 708757.82 |
Maximum of Months | 0.376747E+09 | 0.262360E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 28303353.37 | 0.133313E+09 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.337502E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 434.37 | 0.330408E+09 |
February | 0.139600E+10 | 0.304733E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 1017278.93 | 0.231927E+09 |
March | 0.155131E+10 | 0.338542E+09 | 0.578079E+10 | 0.502211E+11 | 0.00 | 0.00 | 0.00 | 3092523.22 | 0.148668E+09 |
April | 0.149688E+10 | 0.326059E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 12360329.64 | 93885298.00 |
May | 0.154732E+10 | 0.338087E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 25574774.24 | 46124430.82 |
June | 0.150015E+10 | 0.327554E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 58324368.87 | 13510746.26 |
July | 0.154405E+10 | 0.336592E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 74240408.57 | 6495139.63 |
August | 0.155059E+10 | 0.338672E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 77517737.30 | 1672008.57 |
September | 0.149615E+10 | 0.326189E+09 | 0.557718E+10 | 0.484522E+11 | 0.00 | 0.00 | 0.00 | 32879477.77 | 24618165.86 |
October | 0.154478E+10 | 0.337372E+09 | 0.576693E+10 | 0.501006E+11 | 0.00 | 0.00 | 0.00 | 7881011.91 | 0.112819E+09 |
November | 0.149361E+10 | 0.327294E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 941437.00 | 0.173875E+09 |
December | 0.154405E+10 | 0.336592E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 128668.50 | 0.257818E+09 |
Annual Sum or Average | 0.182090E+11 | 0.397519E+10 | 0.679355E+11 | 0.590196E+12 | 0.00 | 0.00 | 0.00 | 0.293958E+09 | 0.144182E+10 |
Minimum of Months | 0.139600E+10 | 0.304733E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 434.37 | 1672008.57 |
Maximum of Months | 0.155131E+10 | 0.338672E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 77517737.30 | 0.330408E+09 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.134280E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 773.50 | 0.568454E+09 |
February | 0.236489E+11 | 0.120899E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 697102.26 | 0.400056E+09 |
March | 0.262800E+11 | 0.123603E+10 | 0.122027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3961262.44 | 0.262263E+09 |
April | 0.253579E+11 | 0.111336E+10 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18008162.80 | 0.165282E+09 |
May | 0.262123E+11 | 0.108100E+10 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42002807.24 | 86345650.84 |
June | 0.254132E+11 | 0.101086E+10 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 93504311.41 | 32645042.44 |
July | 0.261570E+11 | 0.106112E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111645E+09 | 16679531.46 |
August | 0.262677E+11 | 0.111364E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107922E+09 | 5998022.96 |
September | 0.253456E+11 | 0.117807E+10 | 0.117729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44576246.76 | 49911847.73 |
October | 0.261693E+11 | 0.130270E+10 | 0.121734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8658322.17 | 0.205293E+09 |
November | 0.253025E+11 | 0.128147E+10 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1136242.94 | 0.306272E+09 |
December | 0.261570E+11 | 0.133830E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47512.79 | 0.445705E+09 |
Annual Sum or Average | 0.308468E+12 | 0.142683E+11 | 0.143405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.432159E+09 | 0.254490E+10 |
Minimum of Months | 0.236489E+11 | 0.101086E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 773.50 | 5998022.96 |
Maximum of Months | 0.262800E+11 | 0.134280E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111645E+09 | 0.568454E+09 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.946100E+10 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2191.80 | 0.162696E+10 |
February | 0.702046E+11 | 0.854664E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4333242.54 | 0.114347E+10 |
March | 0.780153E+11 | 0.940393E+10 | 0.126786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 15816733.40 | 0.743086E+09 |
April | 0.752779E+11 | 0.900238E+10 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 61741694.37 | 0.478295E+09 |
May | 0.778146E+11 | 0.926941E+10 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127323E+09 | 0.252422E+09 |
June | 0.754422E+11 | 0.894715E+10 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270745E+09 | 96424230.55 |
July | 0.776503E+11 | 0.921296E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.325049E+09 | 50889836.54 |
August | 0.779788E+11 | 0.930143E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319853E+09 | 17236498.09 |
September | 0.752414E+11 | 0.905589E+10 | 0.122320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139424E+09 | 0.147408E+09 |
October | 0.776868E+11 | 0.943856E+10 | 0.126482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 33763465.76 | 0.580779E+09 |
November | 0.751137E+11 | 0.915501E+10 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4109484.97 | 0.869365E+09 |
December | 0.776503E+11 | 0.943598E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 493284.46 | 0.127219E+10 |
Annual Sum or Average | 0.915726E+12 | 0.110230E+12 | 0.148998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130265E+10 | 0.727852E+10 |
Minimum of Months | 0.702046E+11 | 0.854664E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2191.80 | 17236498.09 |
Maximum of Months | 0.780153E+11 | 0.946100E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.325049E+09 | 0.162696E+10 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196602E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146603E+09 |
February | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 206093.33 | 0.102283E+09 |
March | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1304985.57 | 65817041.40 |
April | 0.293479E+09 | 0.190486E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4435683.96 | 40149579.43 |
May | 0.303504E+09 | 0.195821E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10522300.82 | 18178223.50 |
June | 0.293842E+09 | 0.188975E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 27414759.31 | 4744076.65 |
July | 0.303141E+09 | 0.197358E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35358351.94 | 1921217.23 |
August | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37508049.51 | 263355.77 |
September | 0.293479E+09 | 0.190538E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14765881.37 | 9033915.32 |
October | 0.303322E+09 | 0.196576E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2775638.82 | 48763660.30 |
November | 0.293661E+09 | 0.189731E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 180237.53 | 77040237.28 |
December | 0.303141E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8286.76 | 0.114246E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231110E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134480E+09 | 0.629044E+09 |
Minimum of Months | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 263355.77 |
Maximum of Months | 0.303685E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37508049.51 | 0.146603E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196579E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144539E+09 |
February | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 169869.82 | 0.101230E+09 |
March | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1094196.32 | 66115513.26 |
April | 0.293479E+09 | 0.190464E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4077732.47 | 42380695.45 |
May | 0.303504E+09 | 0.195798E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9859455.85 | 21317709.46 |
June | 0.293842E+09 | 0.188953E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26262461.12 | 6372747.80 |
July | 0.303141E+09 | 0.197334E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 34096260.48 | 3424327.15 |
August | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 36100550.90 | 903766.68 |
September | 0.293479E+09 | 0.190515E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13695796.96 | 10854604.96 |
October | 0.303322E+09 | 0.196553E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2412906.08 | 49588127.92 |
November | 0.293661E+09 | 0.189708E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 128108.93 | 75824655.61 |
December | 0.303141E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9553.48 | 0.112007E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231083E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127907E+09 | 0.634558E+09 |
Minimum of Months | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 903766.68 |
Maximum of Months | 0.303685E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 36100550.90 | 0.144539E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.123557E+09 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44387128.95 |
February | 0.00 | 0.111584E+09 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35284443.92 |
March | 0.00 | 0.122575E+09 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9525.54 | 29353638.60 |
April | 0.00 | 0.119713E+09 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 85969.47 | 21006751.03 |
May | 0.00 | 0.123066E+09 | 0.217879E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 480768.05 | 13777579.12 |
June | 0.00 | 0.118764E+09 | 0.210812E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2494534.29 | 6743531.31 |
July | 0.00 | 0.124032E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3536648.40 | 5116199.21 |
August | 0.00 | 0.122575E+09 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3186999.65 | 3645426.72 |
September | 0.00 | 0.119746E+09 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 699997.39 | 9819579.64 |
October | 0.00 | 0.123541E+09 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 52325.45 | 24276797.23 |
November | 0.00 | 0.119238E+09 | 0.210867E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32654714.07 |
December | 0.00 | 0.124048E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41711399.58 |
Annual Sum or Average | 0.00 | 0.145244E+10 | 0.256575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10546768.24 | 0.267777E+09 |
Minimum of Months | 0.00 | 0.111584E+09 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3645426.72 |
Maximum of Months | 0.00 | 0.124048E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3536648.40 | 44387128.95 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.123591E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40990018.96 |
February | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68311.92 | 28673282.92 |
March | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 338124.68 | 18374680.73 |
April | 0.293479E+09 | 0.119746E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1223819.47 | 11696625.11 |
May | 0.303504E+09 | 0.123099E+09 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2824761.14 | 5790960.35 |
June | 0.293842E+09 | 0.118796E+09 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7393529.93 | 1674813.20 |
July | 0.303141E+09 | 0.124066E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9581363.51 | 898427.17 |
August | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10168788.07 | 205663.51 |
September | 0.293479E+09 | 0.119778E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3913028.08 | 3017710.72 |
October | 0.303322E+09 | 0.123574E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 741080.77 | 13852684.50 |
November | 0.293661E+09 | 0.119271E+09 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 45582.17 | 21401043.96 |
December | 0.303141E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6604.41 | 31862360.94 |
Annual Sum or Average | 0.357224E+10 | 0.145283E+10 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36304994.15 | 0.178438E+09 |
Minimum of Months | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205663.51 |
Maximum of Months | 0.303685E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10168788.07 | 40990018.96 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196602E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146888E+09 |
February | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 206086.61 | 0.102692E+09 |
March | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1316248.20 | 66396556.90 |
April | 0.293479E+09 | 0.190486E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4433639.58 | 40668322.34 |
May | 0.303504E+09 | 0.195821E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10477908.08 | 18427834.12 |
June | 0.293842E+09 | 0.188975E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 27363450.16 | 4850765.82 |
July | 0.303141E+09 | 0.197358E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35296910.63 | 1957329.55 |
August | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37450227.76 | 277761.50 |
September | 0.293479E+09 | 0.190538E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14744989.87 | 9135841.84 |
October | 0.303322E+09 | 0.196576E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2773966.97 | 49101757.82 |
November | 0.293661E+09 | 0.189731E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 184473.83 | 77377319.03 |
December | 0.303141E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8246.40 | 0.114519E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231110E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134256E+09 | 0.632293E+09 |
Minimum of Months | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 277761.50 |
Maximum of Months | 0.303685E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37450227.76 | 0.146888E+09 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196579E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144705E+09 |
February | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 161003.84 | 0.101430E+09 |
March | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1137923.81 | 66102988.10 |
April | 0.293479E+09 | 0.190464E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4030258.90 | 42507262.54 |
May | 0.303504E+09 | 0.195798E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9785079.13 | 21643701.31 |
June | 0.293842E+09 | 0.188953E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26079586.80 | 6904460.19 |
July | 0.303141E+09 | 0.197334E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 33896542.52 | 3947047.12 |
August | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35970774.96 | 1185354.16 |
September | 0.293479E+09 | 0.190515E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13597346.35 | 11170575.07 |
October | 0.303322E+09 | 0.196553E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2410364.64 | 49622453.37 |
November | 0.293661E+09 | 0.189708E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 175452.63 | 75627228.15 |
December | 0.303141E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19863.26 | 0.112116E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231083E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127264E+09 | 0.636962E+09 |
Minimum of Months | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1185354.16 |
Maximum of Months | 0.303685E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35970774.96 | 0.144705E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.385223E+10 | 0.193865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.98 | 0.178227E+09 |
February | 0.348285E+10 | 0.175042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 543577.82 | 0.123548E+09 |
March | 0.387034E+10 | 0.194462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2103985.92 | 76932801.80 |
April | 0.373454E+10 | 0.187292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7026751.89 | 48424477.62 |
May | 0.386038E+10 | 0.194201E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14139651.14 | 24143880.41 |
June | 0.374269E+10 | 0.188151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30156121.20 | 8491820.43 |
July | 0.385223E+10 | 0.193342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36525156.99 | 4277485.79 |
August | 0.386853E+10 | 0.194537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37503469.50 | 1029342.49 |
September | 0.373273E+10 | 0.187367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16435763.43 | 13200919.95 |
October | 0.385404E+10 | 0.193790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4346185.68 | 58075055.70 |
November | 0.372639E+10 | 0.188002E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 530159.47 | 90266327.69 |
December | 0.385223E+10 | 0.193342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68157.96 | 0.137281E+09 |
Annual Sum or Average | 0.454292E+11 | 0.228339E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149379E+09 | 0.763898E+09 |
Minimum of Months | 0.348285E+10 | 0.175042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.98 | 1029342.49 |
Maximum of Months | 0.387034E+10 | 0.194537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37503469.50 | 0.178227E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196602E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146105E+09 |
February | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 196265.82 | 0.101993E+09 |
March | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1269194.48 | 65906607.62 |
April | 0.293479E+09 | 0.190486E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4317178.34 | 40400298.15 |
May | 0.303504E+09 | 0.195821E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10309261.49 | 18440080.09 |
June | 0.293842E+09 | 0.188975E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 27067001.97 | 4853274.14 |
July | 0.303141E+09 | 0.197358E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 34947521.96 | 1983382.42 |
August | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37044009.14 | 274341.03 |
September | 0.293479E+09 | 0.190538E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14475672.21 | 9148112.41 |
October | 0.303322E+09 | 0.196576E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2695128.31 | 48877354.14 |
November | 0.293661E+09 | 0.189731E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 167299.52 | 77020644.33 |
December | 0.303141E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7558.30 | 0.113767E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231110E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132496E+09 | 0.628769E+09 |
Minimum of Months | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 274341.03 |
Maximum of Months | 0.303685E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37044009.14 | 0.146105E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196579E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144365E+09 |
February | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 160095.74 | 0.101175E+09 |
March | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1049371.89 | 66279694.37 |
April | 0.293479E+09 | 0.190464E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3929191.74 | 42995814.78 |
May | 0.303504E+09 | 0.195798E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9657367.95 | 21868493.82 |
June | 0.293842E+09 | 0.188953E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25938500.39 | 6478290.01 |
July | 0.303141E+09 | 0.197334E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 33723360.59 | 3452504.90 |
August | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35687897.73 | 891074.67 |
September | 0.293479E+09 | 0.190515E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13420496.44 | 10987537.13 |
October | 0.303322E+09 | 0.196553E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2305039.78 | 49804413.68 |
November | 0.293661E+09 | 0.189708E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 121710.12 | 75703586.37 |
December | 0.303141E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9580.25 | 0.111559E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231083E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126003E+09 | 0.635561E+09 |
Minimum of Months | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 891074.67 |
Maximum of Months | 0.303685E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35687897.73 | 0.144365E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.123591E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76768973.00 |
February | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 98163.52 | 53588773.92 |
March | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 647691.42 | 34314720.75 |
April | 0.293479E+09 | 0.119746E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2207403.53 | 20853393.22 |
May | 0.303504E+09 | 0.123099E+09 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5285840.37 | 9442194.15 |
June | 0.293842E+09 | 0.118796E+09 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13868465.53 | 2483496.40 |
July | 0.303141E+09 | 0.124066E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17898431.81 | 1014953.69 |
August | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18954769.07 | 141933.98 |
September | 0.293479E+09 | 0.119778E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7392152.55 | 4727196.35 |
October | 0.303322E+09 | 0.123574E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1363595.50 | 25465432.20 |
November | 0.293661E+09 | 0.119271E+09 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 82805.90 | 40400637.81 |
December | 0.303141E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3776.85 | 59946987.89 |
Annual Sum or Average | 0.357224E+10 | 0.145283E+10 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67803096.06 | 0.329149E+09 |
Minimum of Months | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141933.98 |
Maximum of Months | 0.303685E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18954769.07 | 76768973.00 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.282832E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.384272E+09 |
February | 0.415303E+11 | 0.254291E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 568282.19 | 0.275095E+09 |
March | 0.461508E+11 | 0.269152E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1958516.03 | 0.188504E+09 |
April | 0.445315E+11 | 0.249082E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 8403963.14 | 0.126824E+09 |
May | 0.460320E+11 | 0.246334E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18700293.03 | 72936354.58 |
June | 0.446286E+11 | 0.233884E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 48090081.00 | 29699106.87 |
July | 0.459349E+11 | 0.243716E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 60634351.25 | 18065557.94 |
August | 0.461292E+11 | 0.251767E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 59583431.90 | 7373517.68 |
September | 0.445099E+11 | 0.256392E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 23545437.40 | 43718227.88 |
October | 0.459565E+11 | 0.279095E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5264456.86 | 0.147623E+09 |
November | 0.444343E+11 | 0.271429E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 411659.24 | 0.213774E+09 |
December | 0.459349E+11 | 0.282403E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 55728.01 | 0.305202E+09 |
Annual Sum or Average | 0.541708E+12 | 0.312038E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227216E+09 | 0.181309E+10 |
Minimum of Months | 0.415303E+11 | 0.233884E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7373517.68 |
Maximum of Months | 0.461508E+11 | 0.282832E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 60634351.25 | 0.384272E+09 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.282832E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.388209E+09 |
February | 0.415303E+11 | 0.254291E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 445416.74 | 0.278933E+09 |
March | 0.461508E+11 | 0.269152E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1652795.67 | 0.193068E+09 |
April | 0.445315E+11 | 0.249082E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 7416468.68 | 0.129784E+09 |
May | 0.460320E+11 | 0.246334E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 17354439.26 | 74531931.43 |
June | 0.446286E+11 | 0.233884E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 46824815.33 | 30124502.40 |
July | 0.459349E+11 | 0.243716E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 59568591.61 | 18457723.17 |
August | 0.461292E+11 | 0.251767E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 58445367.23 | 7558143.76 |
September | 0.445099E+11 | 0.256392E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 22147328.58 | 44872369.22 |
October | 0.459565E+11 | 0.279095E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4584635.39 | 0.151470E+09 |
November | 0.444343E+11 | 0.271429E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 284048.39 | 0.218526E+09 |
December | 0.459349E+11 | 0.282403E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 33279.48 | 0.309896E+09 |
Annual Sum or Average | 0.541708E+12 | 0.312038E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218757E+09 | 0.184543E+10 |
Minimum of Months | 0.415303E+11 | 0.233884E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7558143.76 |
Maximum of Months | 0.461508E+11 | 0.282832E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 59568591.61 | 0.388209E+09 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.110133E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.365412E+09 |
February | 0.369574E+10 | 0.994402E+09 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 63999.34 | 0.261115E+09 |
March | 0.410691E+10 | 0.110473E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 854717.31 | 0.177689E+09 |
April | 0.396281E+10 | 0.106399E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 4549737.90 | 0.115437E+09 |
May | 0.409635E+10 | 0.110324E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 12733224.25 | 62593482.42 |
June | 0.397146E+10 | 0.106887E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 39520826.45 | 21906252.78 |
July | 0.408770E+10 | 0.109836E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 52629007.92 | 12809824.76 |
August | 0.410499E+10 | 0.110515E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 52821394.79 | 4676428.06 |
September | 0.396089E+10 | 0.106442E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 16819576.42 | 36537775.65 |
October | 0.408962E+10 | 0.110091E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 2370870.54 | 0.138037E+09 |
November | 0.395417E+10 | 0.106802E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 5741.05 | 0.203454E+09 |
December | 0.408770E+10 | 0.109836E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291143E+09 |
Annual Sum or Average | 0.482060E+11 | 0.129718E+11 | 0.392709E+12 | 0.359593E+12 | 0.00 | 0.00 | 0.00 | 0.182369E+09 | 0.169081E+10 |
Minimum of Months | 0.369574E+10 | 0.994402E+09 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4676428.06 |
Maximum of Months | 0.410691E+10 | 0.110515E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 52821394.79 | 0.365412E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.407704E+10 | 0.205176E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.316474E+09 |
February | 0.368610E+10 | 0.185255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 819923.81 | 0.219465E+09 |
March | 0.409620E+10 | 0.205809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3299084.18 | 0.136559E+09 |
April | 0.395248E+10 | 0.198220E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10852147.04 | 85231565.05 |
May | 0.408566E+10 | 0.205532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21885452.81 | 42465957.48 |
June | 0.396110E+10 | 0.199129E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48367080.70 | 15303463.07 |
July | 0.407704E+10 | 0.204623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58361170.00 | 7633305.89 |
August | 0.409429E+10 | 0.205888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59425846.08 | 1932162.14 |
September | 0.395056E+10 | 0.198299E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27071568.99 | 21867967.02 |
October | 0.407896E+10 | 0.205097E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6924008.87 | 0.102133E+09 |
November | 0.394385E+10 | 0.198971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 813403.62 | 0.160497E+09 |
December | 0.407704E+10 | 0.204623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102494.04 | 0.243939E+09 |
Annual Sum or Average | 0.480803E+11 | 0.241662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237922E+09 | 0.135350E+10 |
Minimum of Months | 0.368610E+10 | 0.185255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1932162.14 |
Maximum of Months | 0.409620E+10 | 0.205888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59425846.08 | 0.316474E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 13190.31 | 02-JAN-20:10 | 9632.53 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 13190.31 | 01-FEB-20:10 | 9632.53 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 13190.31 | 01-MAR-20:10 | 9632.53 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 13190.31 | 03-APR-19:10 | 9632.53 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 13190.31 | 01-MAY-19:10 | 9632.53 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 13190.31 | 01-JUN-19:10 | 9632.53 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 13190.31 | 03-JUL-19:10 | 9632.53 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 13190.31 | 01-AUG-19:10 | 9632.53 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 13190.31 | 01-SEP-19:10 | 9632.53 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 01-OCT-23:10 | 13190.31 | 02-OCT-19:10 | 9632.53 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 13190.31 | 01-NOV-19:10 | 9632.53 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 13190.31 | 01-DEC-20:10 | 9632.53 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 11501.89 | 13190.31 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 13190.31 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 597.59 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.51 | 31-JAN-15:00 | 159.67 | 27-JAN-08:00 |
February | 1169.53 | 01-FEB-00:10 | 597.59 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.90 | 28-FEB-14:40 | 200.36 | 12-FEB-07:00 |
March | 1169.53 | 01-MAR-00:10 | 597.59 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.95 | 30-MAR-16:00 | 110.80 | 19-MAR-07:00 |
April | 1169.53 | 01-APR-00:10 | 597.59 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.01 | 17-APR-16:00 | 116.94 | 06-APR-05:00 |
May | 1169.53 | 01-MAY-00:10 | 597.59 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.30 | 30-MAY-14:00 | 71.28 | 11-MAY-06:00 |
June | 1169.53 | 01-JUN-00:10 | 597.59 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.60 | 06-JUN-15:00 | 52.86 | 10-JUN-05:00 |
July | 1169.53 | 01-JUL-00:10 | 597.59 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 62.76 | 08-JUL-16:00 | 20.35 | 28-JUL-23:00 |
August | 1169.53 | 01-AUG-00:10 | 597.59 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.65 | 01-AUG-17:00 | 16.41 | 25-AUG-06:00 |
September | 1169.53 | 01-SEP-00:10 | 597.59 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.01 | 03-SEP-17:00 | 49.53 | 29-SEP-04:00 |
October | 1169.53 | 01-OCT-23:10 | 597.59 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.94 | 10-OCT-16:00 | 103.89 | 26-OCT-06:53 |
November | 1169.53 | 01-NOV-00:10 | 597.59 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.69 | 19-NOV-15:40 | 136.53 | 22-NOV-06:00 |
December | 1169.53 | 01-DEC-00:10 | 597.59 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.54 | 12-DEC-15:50 | 152.24 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1169.53 | 597.59 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.51 | 16.41 | |||||
Maximum of Months | 1169.53 | 597.59 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 62.76 | 200.36 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 692.02 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.19 | 31-JAN-15:00 | 61.63 | 27-JAN-08:00 |
February | 1354.32 | 01-FEB-00:10 | 692.02 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.85 | 26-FEB-15:00 | 77.34 | 12-FEB-07:00 |
March | 1354.32 | 01-MAR-00:10 | 692.02 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.44 | 30-MAR-14:00 | 42.77 | 19-MAR-07:00 |
April | 1354.32 | 01-APR-00:10 | 692.02 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.74 | 12-APR-14:00 | 45.42 | 06-APR-05:00 |
May | 1354.32 | 01-MAY-00:10 | 692.02 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.55 | 30-MAY-14:00 | 29.09 | 11-MAY-06:00 |
June | 1354.32 | 01-JUN-00:10 | 692.02 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.38 | 06-JUN-15:00 | 22.63 | 10-JUN-05:00 |
July | 1354.32 | 01-JUL-00:10 | 692.02 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.44 | 08-JUL-15:00 | 10.75 | 28-JUL-23:00 |
August | 1354.32 | 01-AUG-00:10 | 692.02 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.43 | 01-AUG-15:00 | 9.01 | 25-AUG-06:00 |
September | 1354.32 | 01-SEP-00:10 | 692.02 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.79 | 07-SEP-15:00 | 20.87 | 14-SEP-06:00 |
October | 1354.32 | 01-OCT-23:10 | 692.02 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.97 | 10-OCT-16:00 | 40.50 | 26-OCT-05:00 |
November | 1354.32 | 01-NOV-00:10 | 692.02 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.65 | 19-NOV-15:00 | 52.70 | 22-NOV-06:13 |
December | 1354.32 | 01-DEC-00:10 | 692.02 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.56 | 12-DEC-15:00 | 58.76 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1354.32 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.19 | 9.01 | |||||
Maximum of Months | 1354.32 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 26.44 | 77.34 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 286.42 | 02-JAN-00:10 | 684.18 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.46 | 31-JAN-15:00 | 145.66 | 27-JAN-08:00 |
February | 286.42 | 01-FEB-00:10 | 684.18 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.55 | 26-FEB-15:00 | 182.78 | 12-FEB-07:00 |
March | 286.42 | 01-MAR-00:10 | 684.18 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.53 | 30-MAR-14:00 | 101.08 | 19-MAR-07:00 |
April | 286.42 | 01-APR-00:10 | 684.18 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.57 | 12-APR-14:00 | 106.68 | 06-APR-05:00 |
May | 286.42 | 01-MAY-00:10 | 684.18 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.78 | 30-MAY-14:00 | 65.51 | 11-MAY-06:00 |
June | 286.42 | 01-JUN-00:10 | 684.18 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.56 | 06-JUN-15:00 | 51.68 | 10-JUN-05:00 |
July | 286.42 | 01-JUL-00:10 | 684.18 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.52 | 08-JUL-15:00 | 24.41 | 28-JUL-23:00 |
August | 286.42 | 01-AUG-00:10 | 684.18 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.53 | 01-AUG-15:00 | 20.86 | 25-AUG-06:00 |
September | 286.42 | 01-SEP-00:10 | 684.18 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.25 | 07-SEP-15:00 | 48.03 | 14-SEP-06:00 |
October | 286.42 | 01-OCT-23:10 | 684.18 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.22 | 10-OCT-16:00 | 94.77 | 26-OCT-06:53 |
November | 286.42 | 01-NOV-00:10 | 684.18 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.77 | 05-NOV-16:00 | 124.55 | 22-NOV-07:00 |
December | 286.42 | 01-DEC-00:10 | 684.18 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.45 | 12-DEC-14:00 | 138.88 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 286.42 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.46 | 20.86 | |||||
Maximum of Months | 286.42 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 61.52 | 182.78 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 220.32 | 02-JAN-00:10 | 251.84 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 | 31-JAN-15:00 | 84.04 | 27-JAN-08:00 |
February | 220.32 | 01-FEB-00:10 | 251.84 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.70 | 26-FEB-15:00 | 105.45 | 12-FEB-07:00 |
March | 220.32 | 01-MAR-00:10 | 251.84 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.68 | 30-MAR-14:00 | 58.32 | 19-MAR-07:00 |
April | 220.32 | 01-APR-00:10 | 251.84 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.10 | 12-APR-14:00 | 61.55 | 06-APR-05:00 |
May | 220.32 | 01-MAY-00:10 | 251.84 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.55 | 30-MAY-14:00 | 37.52 | 11-MAY-06:00 |
June | 220.32 | 01-JUN-00:10 | 251.84 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.59 | 06-JUN-15:00 | 29.10 | 10-JUN-05:00 |
July | 220.32 | 01-JUL-00:10 | 251.84 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.49 | 08-JUL-15:00 | 13.21 | 28-JUL-23:00 |
August | 220.32 | 01-AUG-00:10 | 251.84 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.13 | 01-AUG-15:00 | 11.18 | 25-AUG-06:00 |
September | 220.32 | 01-SEP-00:10 | 251.84 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.46 | 07-SEP-15:00 | 26.79 | 29-SEP-04:00 |
October | 220.32 | 01-OCT-23:10 | 251.84 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.63 | 10-OCT-16:00 | 54.68 | 26-OCT-06:53 |
November | 220.32 | 01-NOV-00:10 | 251.84 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.10 | 05-NOV-16:00 | 71.86 | 22-NOV-07:00 |
December | 220.32 | 01-DEC-00:10 | 251.84 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.88 | 12-DEC-14:00 | 80.13 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 220.32 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 | 11.18 | |||||
Maximum of Months | 220.32 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 35.49 | 105.45 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 325.08 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.63 | 31-JAN-15:00 | 213.50 | 27-JAN-08:00 |
February | 907.20 | 01-FEB-00:10 | 325.08 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 25.33 | 26-FEB-15:00 | 252.07 | 12-FEB-07:20 |
March | 907.20 | 01-MAR-00:10 | 325.08 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 42.54 | 30-MAR-14:00 | 145.58 | 19-MAR-07:00 |
April | 907.20 | 01-APR-00:10 | 325.08 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 49.93 | 12-APR-14:00 | 150.21 | 06-APR-06:10 |
May | 907.20 | 01-MAY-00:10 | 325.08 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 59.81 | 19-MAY-14:00 | 101.03 | 11-MAY-06:10 |
June | 907.20 | 01-JUN-00:10 | 325.08 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 81.37 | 06-JUN-15:00 | 74.32 | 08-JUN-06:10 |
July | 907.20 | 01-JUL-00:10 | 325.08 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 95.73 | 08-JUL-15:00 | 40.52 | 28-JUL-22:00 |
August | 907.20 | 01-AUG-00:10 | 325.08 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 86.14 | 02-AUG-16:00 | 32.66 | 25-AUG-06:20 |
September | 907.20 | 01-SEP-00:10 | 325.08 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 66.07 | 07-SEP-16:00 | 72.65 | 14-SEP-06:20 |
October | 907.20 | 01-OCT-23:10 | 325.08 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 55.94 | 10-OCT-16:00 | 145.27 | 26-OCT-07:00 |
November | 907.20 | 01-NOV-00:10 | 325.08 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 21.53 | 05-NOV-16:00 | 182.10 | 22-NOV-07:20 |
December | 907.20 | 01-DEC-00:10 | 325.08 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 11.55 | 12-DEC-14:00 | 204.10 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 907.20 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.63 | 32.66 | ||||||
Maximum of Months | 907.20 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 95.73 | 252.07 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 1701.53 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.12 | 31-JAN-15:00 | 352.96 | 27-JAN-08:00 |
February | 15368.40 | 01-FEB-00:10 | 1701.53 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.68 | 28-FEB-14:40 | 442.91 | 12-FEB-07:00 |
March | 15368.40 | 01-MAR-00:10 | 1701.53 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.78 | 30-MAR-14:00 | 244.91 | 19-MAR-07:00 |
April | 15368.40 | 01-APR-00:10 | 1701.53 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.71 | 17-APR-14:00 | 262.02 | 06-APR-05:00 |
May | 15368.40 | 01-MAY-00:10 | 1701.53 | 01-MAY-19:19 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.76 | 30-MAY-14:00 | 163.57 | 11-MAY-05:00 |
June | 15368.40 | 01-JUN-00:10 | 1701.53 | 01-JUN-19:30 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 129.73 | 06-JUN-15:00 | 134.23 | 10-JUN-05:00 |
July | 15368.40 | 01-JUL-00:10 | 1701.53 | 03-JUL-19:30 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 146.50 | 08-JUL-16:00 | 67.19 | 28-JUL-23:00 |
August | 15368.40 | 01-AUG-00:10 | 1701.53 | 01-AUG-19:10 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 129.62 | 01-AUG-15:00 | 51.11 | 25-AUG-06:00 |
September | 15368.40 | 01-SEP-00:10 | 1701.53 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.00 | 08-SEP-14:00 | 123.56 | 14-SEP-05:00 |
October | 15368.40 | 01-OCT-23:10 | 1701.53 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.20 | 10-OCT-16:00 | 236.32 | 26-OCT-05:00 |
November | 15368.40 | 01-NOV-00:10 | 1701.53 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.78 | 19-NOV-15:30 | 301.80 | 22-NOV-06:13 |
December | 15368.40 | 01-DEC-00:10 | 1701.53 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.96 | 12-DEC-15:50 | 336.53 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 15368.40 | 1701.53 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 1.12 | 51.11 | |||||
Maximum of Months | 15368.40 | 1701.53 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 146.50 | 442.91 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 9504.80 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.19 | 31-JAN-15:00 | 1013.87 | 14-JAN-06:00 |
February | 45622.98 | 01-FEB-00:10 | 9504.80 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 126.59 | 28-FEB-14:40 | 1265.44 | 12-FEB-07:00 |
March | 45622.98 | 01-MAR-00:10 | 9504.80 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 197.68 | 30-MAR-14:00 | 710.64 | 19-MAR-07:00 |
April | 45622.98 | 01-APR-00:10 | 9504.80 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 239.77 | 12-APR-14:00 | 768.07 | 06-APR-05:00 |
May | 45622.98 | 01-MAY-00:10 | 9504.80 | 01-MAY-19:10 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 287.56 | 30-MAY-14:00 | 486.76 | 11-MAY-06:00 |
June | 45622.98 | 01-JUN-00:10 | 9504.80 | 01-JUN-19:19 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 384.65 | 06-JUN-15:00 | 389.52 | 10-JUN-05:00 |
July | 45622.98 | 01-JUL-00:10 | 9504.80 | 03-JUL-19:30 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 437.89 | 08-JUL-16:00 | 195.37 | 28-JUL-23:00 |
August | 45622.98 | 01-AUG-00:10 | 9504.80 | 01-AUG-19:10 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 399.36 | 01-AUG-15:00 | 156.84 | 25-AUG-06:00 |
September | 45622.98 | 01-SEP-00:10 | 9504.80 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 290.10 | 07-SEP-15:00 | 361.90 | 29-SEP-04:00 |
October | 45622.98 | 01-OCT-23:10 | 9504.80 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 235.81 | 10-OCT-16:00 | 688.46 | 26-OCT-05:00 |
November | 45622.98 | 01-NOV-00:10 | 9504.80 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.89 | 19-NOV-15:00 | 880.69 | 22-NOV-06:00 |
December | 45622.98 | 01-DEC-00:10 | 9504.80 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.36 | 12-DEC-15:00 | 961.50 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 45622.98 | 9504.80 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 3.19 | 156.84 | |||||
Maximum of Months | 45622.98 | 9504.80 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 437.89 | 1265.44 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.88 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 93.19 | 27-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 177.88 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.35 | 26-FEB-16:09 | 116.82 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 177.88 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.37 | 30-MAR-16:00 | 64.81 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 177.88 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.58 | 17-APR-15:09 | 68.37 | 06-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 177.88 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.40 | 19-MAY-16:00 | 41.85 | 11-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 177.88 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.25 | 06-JUN-15:10 | 31.16 | 10-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 177.88 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.16 | 08-JUL-15:10 | 14.96 | 29-JUL-08:00 |
August | 180.00 | 01-AUG-00:10 | 177.88 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.71 | 02-AUG-16:00 | 8.67 | 25-AUG-07:10 |
September | 180.00 | 01-SEP-00:10 | 177.88 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.34 | 07-SEP-16:00 | 29.22 | 29-SEP-04:00 |
October | 180.00 | 01-OCT-00:10 | 177.88 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.62 | 10-OCT-16:00 | 60.79 | 26-OCT-06:53 |
November | 180.00 | 01-NOV-00:10 | 177.88 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.58 | 05-NOV-16:00 | 79.75 | 22-NOV-06:13 |
December | 180.00 | 01-DEC-00:10 | 177.88 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.88 | 12-DEC-16:07 | 88.87 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | |||||
Maximum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 44.16 | 116.82 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.86 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 93.18 | 27-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 177.86 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.35 | 26-FEB-16:07 | 116.81 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 177.86 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.37 | 30-MAR-16:00 | 64.80 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 177.86 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.57 | 17-APR-15:09 | 68.37 | 06-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 177.86 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.40 | 19-MAY-16:00 | 41.85 | 11-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 177.86 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.24 | 06-JUN-15:10 | 31.16 | 10-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 177.86 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.16 | 08-JUL-15:10 | 15.80 | 28-JUL-21:50 |
August | 180.00 | 01-AUG-00:10 | 177.86 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.71 | 02-AUG-16:00 | 12.11 | 25-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 177.86 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.34 | 07-SEP-16:00 | 29.22 | 29-SEP-04:00 |
October | 180.00 | 01-OCT-00:10 | 177.86 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.62 | 10-OCT-16:00 | 60.79 | 26-OCT-06:53 |
November | 180.00 | 01-NOV-00:10 | 177.86 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.58 | 05-NOV-16:00 | 79.74 | 22-NOV-06:13 |
December | 180.00 | 01-DEC-00:10 | 177.86 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.93 | 12-DEC-14:00 | 88.86 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.11 | |||||
Maximum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 44.16 | 116.81 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 111.79 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 28.41 | 27-JAN-08:00 |
February | 0.00 | 01-FEB-00:10 | 111.79 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 30.78 | 12-FEB-07:10 |
March | 0.00 | 01-MAR-00:10 | 111.79 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.88 | 30-MAR-14:10 | 22.11 | 19-MAR-07:00 |
April | 0.00 | 01-APR-00:10 | 111.79 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.80 | 12-APR-14:00 | 22.53 | 06-APR-05:10 |
May | 0.00 | 01-MAY-00:10 | 111.79 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.15 | 19-MAY-14:00 | 16.39 | 11-MAY-06:00 |
June | 0.00 | 01-JUN-00:10 | 111.79 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.07 | 06-JUN-15:00 | 13.37 | 10-JUN-05:00 |
July | 0.00 | 01-JUL-00:10 | 111.79 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.92 | 08-JUL-15:00 | 8.09 | 28-JUL-23:15 |
August | 0.00 | 01-AUG-00:10 | 111.79 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.63 | 02-AUG-16:00 | 7.07 | 25-AUG-06:00 |
September | 0.00 | 01-SEP-00:10 | 111.79 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 07-SEP-16:00 | 12.45 | 14-SEP-06:00 |
October | 0.00 | 01-OCT-00:10 | 111.79 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.66 | 10-OCT-16:00 | 21.35 | 26-OCT-07:00 |
November | 0.00 | 01-NOV-00:10 | 111.79 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 25.48 | 22-NOV-08:00 |
December | 0.00 | 01-DEC-00:10 | 111.79 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 28.30 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 0.00 | 111.79 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.07 | |||||
Maximum of Months | 0.00 | 111.79 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 7.92 | 30.78 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 111.82 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 26.01 | 27-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 111.82 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.61 | 26-FEB-16:07 | 32.60 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 111.82 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.41 | 30-MAR-16:00 | 18.09 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 111.82 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.30 | 17-APR-15:10 | 19.12 | 06-APR-05:20 |
May | 180.00 | 01-MAY-00:10 | 111.82 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.65 | 19-MAY-16:00 | 11.68 | 11-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 111.82 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.39 | 06-JUN-15:10 | 8.70 | 10-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 111.82 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.32 | 08-JUL-15:10 | 4.91 | 28-JUL-21:50 |
August | 180.00 | 01-AUG-00:10 | 111.82 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.08 | 02-AUG-16:00 | 3.27 | 25-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 111.82 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.47 | 07-SEP-16:00 | 8.16 | 29-SEP-04:00 |
October | 180.00 | 01-OCT-00:10 | 111.82 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.15 | 10-OCT-16:00 | 17.33 | 26-OCT-06:53 |
November | 180.00 | 01-NOV-00:10 | 111.82 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 05-NOV-16:00 | 22.26 | 22-NOV-06:20 |
December | 180.00 | 01-DEC-00:10 | 111.82 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.25 | 12-DEC-14:00 | 24.80 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.27 | |||||
Maximum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 12.32 | 32.60 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.88 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 93.19 | 27-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 177.88 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.35 | 26-FEB-16:07 | 116.82 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 177.88 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.37 | 30-MAR-16:00 | 64.81 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 177.88 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.58 | 17-APR-15:10 | 68.37 | 06-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 177.88 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.40 | 19-MAY-16:00 | 41.85 | 11-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 177.88 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.25 | 06-JUN-15:10 | 31.16 | 10-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 177.88 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.16 | 08-JUL-15:10 | 14.89 | 29-JUL-08:00 |
August | 180.00 | 01-AUG-00:10 | 177.88 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.71 | 02-AUG-16:00 | 9.62 | 25-AUG-07:20 |
September | 180.00 | 01-SEP-00:10 | 177.88 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.34 | 07-SEP-16:00 | 29.22 | 29-SEP-04:00 |
October | 180.00 | 01-OCT-00:10 | 177.88 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.62 | 10-OCT-16:00 | 60.79 | 26-OCT-06:53 |
November | 180.00 | 01-NOV-00:10 | 177.88 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.58 | 05-NOV-16:00 | 79.75 | 22-NOV-06:13 |
December | 180.00 | 01-DEC-00:10 | 177.88 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.88 | 12-DEC-16:07 | 88.87 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.62 | |||||
Maximum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 44.16 | 116.82 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.86 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 93.18 | 27-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 177.86 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.35 | 26-FEB-16:07 | 116.81 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 177.86 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.37 | 30-MAR-16:00 | 64.80 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 177.86 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.58 | 17-APR-15:09 | 68.37 | 06-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 177.86 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.40 | 19-MAY-16:00 | 41.85 | 11-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 177.86 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.24 | 06-JUN-15:10 | 31.16 | 10-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 177.86 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.16 | 08-JUL-15:10 | 15.53 | 29-JUL-08:00 |
August | 180.00 | 01-AUG-00:10 | 177.86 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.71 | 02-AUG-16:00 | 11.78 | 27-AUG-08:00 |
September | 180.00 | 01-SEP-00:10 | 177.86 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.34 | 07-SEP-16:00 | 29.22 | 29-SEP-04:00 |
October | 180.00 | 01-OCT-00:10 | 177.86 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.62 | 10-OCT-16:00 | 60.79 | 26-OCT-06:53 |
November | 180.00 | 01-NOV-00:10 | 177.86 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.58 | 05-NOV-16:00 | 79.74 | 22-NOV-06:13 |
December | 180.00 | 01-DEC-00:10 | 177.86 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.89 | 12-DEC-14:00 | 88.86 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.78 | |||||
Maximum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 44.16 | 116.81 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2263.36 | 02-JAN-00:10 | 1867.32 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.20 | 31-JAN-15:00 | 112.24 | 27-JAN-08:00 |
February | 2263.36 | 01-FEB-00:10 | 1867.32 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.73 | 26-FEB-15:00 | 140.80 | 12-FEB-07:00 |
March | 2263.36 | 01-MAR-00:10 | 1867.32 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.17 | 30-MAR-14:00 | 77.93 | 19-MAR-07:00 |
April | 2263.36 | 01-APR-00:10 | 1867.32 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.36 | 12-APR-14:00 | 82.24 | 06-APR-05:00 |
May | 2263.36 | 01-MAY-00:10 | 1867.32 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.34 | 30-MAY-14:00 | 51.50 | 11-MAY-06:00 |
June | 2263.36 | 01-JUN-00:10 | 1867.32 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.14 | 06-JUN-15:00 | 40.55 | 10-JUN-05:00 |
July | 2263.36 | 01-JUL-00:10 | 1867.32 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.41 | 08-JUL-15:00 | 18.82 | 28-JUL-23:00 |
August | 2263.36 | 01-AUG-00:10 | 1867.32 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.68 | 01-AUG-15:00 | 15.03 | 25-AUG-06:00 |
September | 2263.36 | 01-SEP-00:10 | 1867.32 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.05 | 07-SEP-15:00 | 37.02 | 29-SEP-04:00 |
October | 2263.36 | 01-OCT-23:10 | 1867.32 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.36 | 10-OCT-16:00 | 73.08 | 26-OCT-06:53 |
November | 2263.36 | 01-NOV-00:10 | 1867.32 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.95 | 19-NOV-15:00 | 95.99 | 22-NOV-07:00 |
December | 2263.36 | 01-DEC-00:10 | 1867.32 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.34 | 12-DEC-14:50 | 107.02 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.20 | 15.03 | ||||
Maximum of Months | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.41 | 140.80 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.88 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 93.41 | 27-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 177.88 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.18 | 26-FEB-16:09 | 117.05 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 177.88 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.20 | 30-MAR-15:40 | 65.01 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 177.88 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.41 | 17-APR-15:10 | 68.58 | 06-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 177.88 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.24 | 19-MAY-16:00 | 42.05 | 11-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 177.88 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.08 | 06-JUN-15:10 | 31.35 | 10-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 177.88 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.95 | 08-JUL-16:00 | 14.26 | 29-JUL-08:00 |
August | 180.00 | 01-AUG-00:10 | 177.88 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.54 | 02-AUG-16:00 | 8.78 | 25-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 177.88 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.17 | 07-SEP-16:00 | 29.41 | 29-SEP-04:00 |
October | 180.00 | 01-OCT-00:10 | 177.88 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.45 | 10-OCT-16:00 | 60.99 | 26-OCT-06:53 |
November | 180.00 | 01-NOV-00:10 | 177.88 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.41 | 05-NOV-16:00 | 79.96 | 22-NOV-06:13 |
December | 180.00 | 01-DEC-00:10 | 177.88 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.70 | 12-DEC-16:09 | 89.09 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.78 | |||||
Maximum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 43.95 | 117.05 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.86 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 93.40 | 27-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 177.86 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.18 | 26-FEB-16:07 | 117.04 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 177.86 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.20 | 30-MAR-16:00 | 65.01 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 177.86 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.41 | 17-APR-15:09 | 68.57 | 06-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 177.86 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.23 | 19-MAY-16:00 | 42.05 | 11-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 177.86 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.08 | 06-JUN-15:10 | 31.35 | 10-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 177.86 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.95 | 08-JUL-16:00 | 15.84 | 28-JUL-21:50 |
August | 180.00 | 01-AUG-00:10 | 177.86 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.54 | 02-AUG-16:00 | 11.57 | 25-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 177.86 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.17 | 07-SEP-16:00 | 29.41 | 29-SEP-04:00 |
October | 180.00 | 01-OCT-00:10 | 177.86 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.45 | 10-OCT-16:00 | 60.99 | 26-OCT-06:53 |
November | 180.00 | 01-NOV-00:10 | 177.86 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.41 | 05-NOV-16:00 | 79.95 | 22-NOV-06:13 |
December | 180.00 | 01-DEC-00:10 | 177.86 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.98 | 12-DEC-14:00 | 89.08 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.57 | |||||
Maximum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 43.95 | 117.04 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 111.82 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 47.79 | 27-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 111.82 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.69 | 26-FEB-16:10 | 59.89 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 111.82 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.82 | 30-MAR-16:00 | 33.26 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 111.82 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.46 | 17-APR-15:10 | 35.09 | 06-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 111.82 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.93 | 19-MAY-16:00 | 21.51 | 11-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 111.82 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.97 | 06-JUN-15:10 | 16.04 | 10-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 111.82 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.51 | 08-JUL-15:10 | 7.64 | 29-JUL-08:00 |
August | 180.00 | 01-AUG-00:10 | 111.82 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.23 | 02-AUG-16:00 | 4.49 | 25-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 111.82 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.44 | 07-SEP-16:00 | 15.05 | 29-SEP-04:00 |
October | 180.00 | 01-OCT-00:10 | 111.82 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.02 | 10-OCT-16:00 | 31.21 | 26-OCT-06:53 |
November | 180.00 | 01-NOV-00:10 | 111.82 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.81 | 05-NOV-16:00 | 40.91 | 22-NOV-06:13 |
December | 180.00 | 01-DEC-00:10 | 111.82 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.38 | 12-DEC-16:10 | 45.58 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.49 | |||||
Maximum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 22.51 | 59.89 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2988.03 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 238.19 | 14-JAN-06:00 |
February | 26988.77 | 01-FEB-00:10 | 2988.03 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.36 | 26-FEB-15:00 | 291.26 | 12-FEB-07:10 |
March | 26988.77 | 01-MAR-00:10 | 2988.03 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.89 | 30-MAR-14:00 | 172.26 | 19-MAR-07:00 |
April | 26988.77 | 01-APR-00:10 | 2988.03 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.88 | 12-APR-14:00 | 182.67 | 06-APR-05:00 |
May | 26988.77 | 01-MAY-00:10 | 2988.03 | 01-MAY-19:19 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.63 | 19-MAY-14:00 | 120.76 | 11-MAY-06:00 |
June | 26988.77 | 01-JUN-00:10 | 2988.03 | 01-JUN-19:30 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.80 | 06-JUN-15:00 | 97.12 | 10-JUN-05:00 |
July | 26988.77 | 01-JUL-00:10 | 2988.03 | 03-JUL-19:30 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.43 | 08-JUL-15:00 | 51.40 | 28-JUL-23:10 |
August | 26988.77 | 01-AUG-00:10 | 2988.03 | 01-AUG-19:19 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.90 | 01-AUG-15:00 | 42.64 | 25-AUG-06:00 |
September | 26988.77 | 01-SEP-00:10 | 2988.03 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.03 | 07-SEP-15:00 | 90.80 | 29-SEP-04:00 |
October | 26988.77 | 01-OCT-23:10 | 2988.03 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.58 | 10-OCT-14:00 | 163.56 | 26-OCT-05:00 |
November | 26988.77 | 01-NOV-00:10 | 2988.03 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.86 | 19-NOV-15:00 | 207.16 | 22-NOV-06:00 |
December | 26988.77 | 01-DEC-00:10 | 2988.03 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.55 | 12-DEC-15:00 | 222.61 | 18-DEC-05:30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.64 | |||||
Maximum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 87.43 | 291.26 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2988.03 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 239.20 | 14-JAN-06:00 |
February | 26988.77 | 01-FEB-00:10 | 2988.03 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.90 | 26-FEB-15:00 | 292.55 | 12-FEB-07:10 |
March | 26988.77 | 01-MAR-00:10 | 2988.03 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.70 | 30-MAR-14:00 | 174.02 | 19-MAR-07:00 |
April | 26988.77 | 01-APR-00:10 | 2988.03 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.71 | 12-APR-14:00 | 183.95 | 06-APR-05:00 |
May | 26988.77 | 01-MAY-00:10 | 2988.03 | 01-MAY-19:19 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.00 | 19-MAY-14:00 | 122.20 | 11-MAY-06:00 |
June | 26988.77 | 01-JUN-00:10 | 2988.03 | 01-JUN-19:30 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.43 | 06-JUN-15:00 | 97.94 | 10-JUN-05:00 |
July | 26988.77 | 01-JUL-00:10 | 2988.03 | 03-JUL-19:30 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.42 | 08-JUL-15:00 | 51.40 | 28-JUL-23:10 |
August | 26988.77 | 01-AUG-00:10 | 2988.03 | 01-AUG-19:19 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.53 | 01-AUG-15:00 | 42.64 | 25-AUG-06:00 |
September | 26988.77 | 01-SEP-00:10 | 2988.03 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.72 | 07-SEP-15:00 | 91.81 | 29-SEP-04:00 |
October | 26988.77 | 01-OCT-23:10 | 2988.03 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.50 | 10-OCT-14:00 | 164.83 | 26-OCT-05:00 |
November | 26988.77 | 01-NOV-00:10 | 2988.03 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.30 | 19-NOV-15:00 | 208.28 | 22-NOV-06:00 |
December | 26988.77 | 01-DEC-00:10 | 2988.03 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.15 | 12-DEC-15:00 | 223.66 | 18-DEC-05:30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.64 | |||||
Maximum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 87.42 | 292.55 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 1060.81 | 02-JAN-20:10 | 14912.86 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 225.20 | 27-JAN-08:00 |
February | 2401.70 | 01-FEB-00:10 | 1060.81 | 01-FEB-20:10 | 14912.86 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 5.86 | 26-FEB-15:00 | 269.63 | 12-FEB-08:10 |
March | 2401.70 | 01-MAR-00:10 | 1060.81 | 01-MAR-20:10 | 14912.86 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 23.68 | 30-MAR-15:40 | 162.40 | 19-MAR-07:00 |
April | 2401.70 | 01-APR-00:10 | 1060.81 | 03-APR-19:10 | 14912.86 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 30.96 | 12-APR-14:00 | 160.10 | 06-APR-06:20 |
May | 2401.70 | 01-MAY-00:10 | 1060.81 | 01-MAY-19:10 | 14912.86 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 41.32 | 19-MAY-15:40 | 111.25 | 11-MAY-06:00 |
June | 2401.70 | 01-JUN-00:10 | 1060.81 | 01-JUN-19:10 | 14912.86 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 63.78 | 06-JUN-15:00 | 83.26 | 08-JUN-06:00 |
July | 2401.70 | 01-JUL-00:10 | 1060.81 | 03-JUL-19:10 | 14912.86 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 78.34 | 08-JUL-15:00 | 45.98 | 28-JUL-23:00 |
August | 2401.70 | 01-AUG-00:10 | 1060.81 | 01-AUG-19:10 | 14912.86 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 68.44 | 02-AUG-16:00 | 38.14 | 25-AUG-06:00 |
September | 2401.70 | 01-SEP-00:10 | 1060.81 | 01-SEP-19:10 | 14912.86 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 47.90 | 07-SEP-16:00 | 79.88 | 14-SEP-06:00 |
October | 2401.70 | 01-OCT-23:10 | 1060.81 | 02-OCT-19:10 | 14912.86 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 37.45 | 10-OCT-16:00 | 153.53 | 26-OCT-07:00 |
November | 2401.70 | 01-NOV-00:10 | 1060.81 | 01-NOV-19:10 | 14912.86 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 2.02 | 05-NOV-16:00 | 192.33 | 22-NOV-07:40 |
December | 2401.70 | 01-DEC-00:10 | 1060.81 | 01-DEC-20:10 | 14912.86 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 215.29 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2401.70 | 1060.81 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 0.00 | 38.14 | ||||||
Maximum of Months | 2401.70 | 1060.81 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 78.34 | 269.63 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2395.44 | 02-JAN-00:10 | 1976.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 199.06 | 27-JAN-08:00 |
February | 2395.44 | 01-FEB-00:10 | 1976.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.93 | 28-FEB-14:40 | 249.62 | 12-FEB-07:00 |
March | 2395.44 | 01-MAR-00:10 | 1976.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.53 | 30-MAR-14:00 | 138.33 | 19-MAR-07:00 |
April | 2395.44 | 01-APR-00:10 | 1976.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.01 | 12-APR-14:00 | 145.96 | 06-APR-05:00 |
May | 2395.44 | 01-MAY-00:10 | 1976.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.67 | 19-MAY-14:00 | 89.22 | 11-MAY-06:00 |
June | 2395.44 | 01-JUN-00:10 | 1976.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.60 | 06-JUN-15:00 | 68.48 | 10-JUN-05:00 |
July | 2395.44 | 01-JUL-00:10 | 1976.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.59 | 08-JUL-15:00 | 31.59 | 28-JUL-23:00 |
August | 2395.44 | 01-AUG-00:10 | 1976.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.42 | 01-AUG-15:00 | 25.95 | 25-AUG-06:00 |
September | 2395.44 | 01-SEP-00:10 | 1976.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.54 | 07-SEP-15:00 | 62.19 | 29-SEP-04:00 |
October | 2395.44 | 01-OCT-23:10 | 1976.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.38 | 10-OCT-16:00 | 129.73 | 26-OCT-06:53 |
November | 2395.44 | 01-NOV-00:10 | 1976.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.77 | 19-NOV-15:00 | 170.30 | 22-NOV-07:00 |
December | 2395.44 | 01-DEC-00:10 | 1976.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.04 | 12-DEC-15:00 | 189.82 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.95 | ||||
Maximum of Months | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.59 | 249.62 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 14794.99 | 20-JAN-21:50 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 14556.81 | 01-FEB-22:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 14289.48 | 01-MAR-22:10 | 11501.89 | 8793.54 | 7097.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 13741.15 | 19-APR-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 14080.46 | 19-MAY-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 14821.25 | 30-JUN-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 15643.36 | 14-JUL-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16515.82 | 18-AUG-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17292.74 | 15-SEP-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17401.36 | 13-OCT-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17352.57 | 09-NOV-22:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16818.46 | 01-DEC-22:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 13741.15 | 10223.90 | 8793.54 | 7097.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17401.36 | 11501.89 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2035.68 | 29-JAN-13:30 | 259.90 | 132.80 | 216.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.60 |
February | 2132.60 | 21-FEB-14:30 | 519.79 | 332.00 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 |
March | 2084.98 | 30-MAR-14:20 | 389.84 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 21.78 | 0.00 |
April | 2079.17 | 15-APR-14:00 | 389.84 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 21.78 | 0.00 |
May | 2007.04 | 19-MAY-19:20 | 909.64 | 597.59 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 21.94 | 0.00 |
June | 2093.78 | 13-JUN-19:20 | 909.64 | 597.59 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 33.49 | 0.00 |
July | 2346.05 | 08-JUL-17:17 | 2339.06 | 1195.19 | 1515.54 | 0.00 | 0.00 | 0.00 | 0.00 | 51.20 | 0.00 |
August | 2667.74 | 19-AUG-13:40 | 389.84 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 47.82 | 0.00 |
September | 2536.31 | 25-SEP-15:03 | 4548.18 | 1161.99 | 1768.14 | 0.00 | 0.00 | 0.00 | 0.00 | 27.04 | 0.00 |
October | 2698.66 | 10-OCT-13:30 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 24.33 | 0.00 |
November | 2168.58 | 15-NOV-14:00 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.78 |
December | 2112.75 | 10-DEC-14:00 | 259.90 | 132.80 | 216.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.98 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2007.04 | 259.90 | 132.80 | 216.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2698.66 | 4548.18 | 1195.19 | 1768.14 | 0.00 | 0.00 | 0.00 | 0.00 | 51.20 | 47.60 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1393.59 | 31-JAN-22:10 | 1354.32 | 461.34 | 585.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.70 |
February | 1471.44 | 28-FEB-22:10 | 1354.32 | 461.34 | 585.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.16 |
March | 1560.45 | 30-MAR-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 1.23 | 0.00 |
April | 1566.39 | 17-APR-21:10 | 1354.32 | 461.34 | 585.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.59 |
May | 1609.46 | 19-MAY-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 | 0.00 |
June | 1647.67 | 27-JUN-21:10 | 1354.32 | 461.34 | 585.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.22 | 0.00 |
July | 1875.93 | 07-JUL-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 12.70 | 0.00 |
August | 1956.37 | 18-AUG-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 13.64 | 0.00 |
September | 1738.95 | 08-SEP-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 3.13 | 0.00 |
October | 1597.70 | 11-OCT-21:10 | 1354.32 | 461.34 | 585.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.63 |
November | 1464.63 | 02-NOV-21:10 | 1354.32 | 461.34 | 585.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.32 |
December | 1449.77 | 12-DEC-22:10 | 1354.32 | 461.34 | 585.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1393.59 | 1203.84 | 461.34 | 585.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1956.37 | 1354.32 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 13.64 | 15.70 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1082.11 | 20-JAN-21:50 | 254.59 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.64 |
February | 1116.98 | 28-FEB-22:10 | 286.42 | 456.12 | 618.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.34 |
March | 1185.54 | 30-MAR-21:00 | 254.59 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 7.98 | 0.00 |
April | 1203.20 | 19-APR-21:10 | 286.42 | 456.12 | 618.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.96 |
May | 1260.23 | 19-MAY-21:00 | 254.59 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 5.26 | 0.00 |
June | 1341.03 | 29-JUN-21:10 | 286.42 | 456.12 | 618.54 | 0.00 | 0.00 | 0.00 | 0.00 | 11.81 | 0.00 |
July | 1386.62 | 07-JUL-21:10 | 286.42 | 456.12 | 618.54 | 0.00 | 0.00 | 0.00 | 0.00 | 30.32 | 0.00 |
August | 1391.28 | 18-AUG-21:10 | 286.42 | 456.12 | 618.54 | 0.00 | 0.00 | 0.00 | 0.00 | 32.01 | 0.00 |
September | 1330.87 | 08-SEP-21:00 | 254.59 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 10.52 | 0.00 |
October | 1216.95 | 19-OCT-21:10 | 286.42 | 456.12 | 618.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.05 |
November | 1135.27 | 03-NOV-21:10 | 286.42 | 456.12 | 618.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.88 |
December | 1114.01 | 13-DEC-22:10 | 286.42 | 456.12 | 618.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.58 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1082.11 | 254.59 | 456.12 | 618.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1391.28 | 286.42 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 32.01 | 45.64 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 609.12 | 31-JAN-22:00 | 391.68 | 447.71 | 458.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.06 |
February | 641.04 | 28-FEB-22:10 | 220.32 | 167.89 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.37 |
March | 679.35 | 30-MAR-21:00 | 195.84 | 223.85 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 5.58 | 0.00 |
April | 686.12 | 19-APR-21:10 | 220.32 | 167.89 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.65 |
May | 720.88 | 19-MAY-21:00 | 195.84 | 223.85 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 4.13 | 0.00 |
June | 769.84 | 29-JUN-21:10 | 220.32 | 167.89 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 7.87 | 0.00 |
July | 799.79 | 07-JUL-21:10 | 220.32 | 167.89 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 18.43 | 0.00 |
August | 802.40 | 18-AUG-21:10 | 220.32 | 167.89 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 19.41 | 0.00 |
September | 763.41 | 07-SEP-21:10 | 220.32 | 167.89 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 6.69 | 0.00 |
October | 695.80 | 18-OCT-21:10 | 220.32 | 167.89 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 3.30 | 0.00 |
November | 649.75 | 03-NOV-21:10 | 220.32 | 167.89 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.75 |
December | 637.58 | 12-DEC-22:10 | 220.32 | 167.89 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.08 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 609.12 | 195.84 | 167.89 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 802.40 | 391.68 | 447.71 | 458.82 | 0.00 | 0.00 | 0.00 | 0.00 | 19.41 | 17.06 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 36462.62 | 31-JAN-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 44.65 |
February | 36968.03 | 28-FEB-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 21.82 |
March | 37426.05 | 30-MAR-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 2.51 | 0.00 |
April | 37590.45 | 17-APR-20:00 | 1411.20 | 650.17 | 9145.60 | 79453.15 | 0.00 | 0.00 | 0.00 | 0.00 | 7.69 |
May | 37945.87 | 19-MAY-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 10.11 | 0.00 |
June | 38298.34 | 13-JUN-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 33.71 | 0.00 |
July | 38561.21 | 07-JUL-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 44.00 | 0.00 |
August | 38463.01 | 18-AUG-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 47.61 | 0.00 |
September | 38200.24 | 07-SEP-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 20.06 | 0.00 |
October | 37528.48 | 10-OCT-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 11.51 |
November | 36874.20 | 02-NOV-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 40.49 |
December | 36700.17 | 12-DEC-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 37.20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 36462.62 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 38561.21 | 1411.20 | 650.17 | 9145.60 | 79453.15 | 0.00 | 0.00 | 0.00 | 47.61 | 44.65 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9030.10 | 29-JAN-13:00 | 5122.80 | 124.78 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.13 |
February | 9162.98 | 28-FEB-22:30 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.92 |
March | 9626.68 | 30-MAR-21:51 | 107578.80 | 7940.47 | 4978.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.04 |
April | 9488.89 | 17-APR-21:30 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.76 |
May | 9605.18 | 19-MAY-21:12 | 61473.60 | 4537.41 | 2845.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.86 |
June | 10440.12 | 13-JUN-21:10 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 45.86 | 0.00 |
July | 11252.49 | 07-JUL-21:10 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 70.61 | 0.00 |
August | 11727.82 | 18-AUG-21:10 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 75.10 | 0.00 |
September | 10934.29 | 25-SEP-15:06 | 59766.00 | 727.88 | 2489.39 | 0.00 | 0.00 | 0.00 | 0.00 | 59.78 | 0.00 |
October | 11529.63 | 11-OCT-15:03 | 59766.00 | 727.88 | 2489.39 | 0.00 | 0.00 | 0.00 | 0.00 | 33.52 | 0.00 |
November | 9499.89 | 11-NOV-13:00 | 5122.80 | 124.78 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.21 |
December | 9307.34 | 10-DEC-13:00 | 5122.80 | 124.78 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.19 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9030.10 | 5122.80 | 124.78 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11727.82 | 107578.80 | 7940.47 | 4978.78 | 0.00 | 0.00 | 0.00 | 0.00 | 75.10 | 112.13 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 29797.94 | 31-JAN-22:30 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 302.67 |
February | 30992.92 | 28-FEB-22:55 | 273737.88 | 38019.20 | 44339.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.68 |
March | 32312.34 | 30-MAR-22:00 | 319360.86 | 44355.73 | 51729.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.55 |
April | 32103.36 | 17-APR-22:00 | 364983.84 | 50692.26 | 59119.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.04 |
May | 32835.88 | 19-MAY-22:00 | 319360.86 | 44355.73 | 51729.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.93 |
June | 33693.91 | 29-JUN-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 62.92 | 0.00 |
July | 36962.29 | 07-JUL-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 201.66 | 0.00 |
August | 38174.53 | 18-AUG-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 214.49 | 0.00 |
September | 35187.70 | 07-SEP-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 44.79 | 0.00 |
October | 32867.97 | 10-OCT-22:00 | 319360.86 | 44355.73 | 51729.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.96 |
November | 31085.25 | 02-NOV-22:00 | 228114.90 | 31682.67 | 36949.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233.88 |
December | 30982.79 | 12-DEC-23:00 | 228114.90 | 31682.67 | 36949.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.31 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 29797.94 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 38174.53 | 364983.84 | 50692.26 | 59119.55 | 0.00 | 0.00 | 0.00 | 0.00 | 214.49 | 302.67 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3329.11 | 29-JAN-16:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.03 |
February | 3424.10 | 27-FEB-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.47 | 0.00 |
March | 3392.01 | 10-MAR-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.14 |
April | 3421.38 | 09-APR-18:01 | 819.00 | 1245.18 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.36 |
May | 3404.32 | 09-MAY-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.60 |
June | 3054.64 | 26-JUN-18:02 | 831.60 | 949.89 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 1.90 | 0.00 |
July | 2983.17 | 27-JUL-15:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 4.62 | 0.00 |
August | 3010.68 | 19-AUG-08:62 | 324.00 | 597.68 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 15.01 | 0.00 |
September | 3017.66 | 04-SEP-15:02 | 324.00 | 352.21 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 16.30 | 0.00 |
October | 3238.13 | 31-OCT-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.37 |
November | 3379.79 | 14-NOV-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 |
December | 3332.86 | 09-DEC-16:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.63 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2983.17 | 324.00 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3424.10 | 970.20 | 1245.18 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 16.30 | 30.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3045.18 | 29-JAN-16:01 | 378.00 | 410.86 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.68 |
February | 3356.03 | 27-FEB-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.79 | 0.00 |
March | 3331.66 | 10-MAR-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.89 |
April | 3510.92 | 26-APR-18:41 | 1247.40 | 1424.67 | 1090.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.53 |
May | 3530.12 | 09-MAY-20:41 | 1602.00 | 1582.97 | 1817.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.42 |
June | 3011.32 | 16-JUN-21:51 | 1260.00 | 834.17 | 626.82 | 0.00 | 0.00 | 0.00 | 0.00 | 1.93 | 0.00 |
July | 3037.81 | 02-JUL-21:51 | 1108.80 | 1209.46 | 716.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.61 |
August | 3047.95 | 08-AUG-18:01 | 970.20 | 1108.08 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 11.93 | 0.00 |
September | 3284.05 | 18-SEP-16:01 | 972.00 | 498.01 | 1264.17 | 0.00 | 0.00 | 0.00 | 0.00 | 3.31 | 0.00 |
October | 3106.66 | 31-OCT-18:01 | 970.20 | 1108.08 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.03 |
November | 3311.29 | 14-NOV-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 |
December | 2984.88 | 09-DEC-16:01 | 378.00 | 410.86 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2984.88 | 378.00 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3530.12 | 1602.00 | 1582.97 | 1817.24 | 0.00 | 0.00 | 0.00 | 0.00 | 11.93 | 29.42 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 292.20 | 29-JAN-13:30 | 0.00 | 36.89 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.64 |
February | 394.12 | 26-FEB-14:25 | 0.00 | 73.78 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.66 |
March | 369.60 | 30-MAR-13:40 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 | 0.00 |
April | 348.59 | 15-APR-13:50 | 0.00 | 36.89 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.74 | 0.00 |
May | 297.14 | 19-MAY-19:10 | 0.00 | 111.79 | 159.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.93 | 0.00 |
June | 337.52 | 24-JUN-19:10 | 0.00 | 111.79 | 159.95 | 0.00 | 0.00 | 0.00 | 0.00 | 2.84 | 0.00 |
July | 376.59 | 08-JUL-17:30 | 0.00 | 190.05 | 247.67 | 0.00 | 0.00 | 0.00 | 0.00 | 6.13 | 0.00 |
August | 408.88 | 19-AUG-13:40 | 0.00 | 36.89 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 5.58 | 0.00 |
September | 473.83 | 24-SEP-12:40 | 0.00 | 36.89 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 1.62 | 0.00 |
October | 509.07 | 10-OCT-13:30 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 1.74 | 0.00 |
November | 445.05 | 15-NOV-14:00 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 |
December | 427.38 | 10-DEC-14:25 | 0.00 | 73.78 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.84 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 292.20 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 509.07 | 0.00 | 190.05 | 247.67 | 0.00 | 0.00 | 0.00 | 0.00 | 6.13 | 10.64 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 985.72 | 31-JAN-16:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.34 |
February | 1201.72 | 28-FEB-22:52 | 1080.00 | 449.53 | 526.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.36 |
March | 1199.32 | 31-MAR-20:12 | 961.20 | 597.13 | 1068.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.43 |
April | 1205.22 | 09-APR-20:11 | 1247.40 | 1006.40 | 1602.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.68 |
May | 1283.52 | 09-MAY-20:41 | 1602.00 | 995.22 | 1780.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.36 |
June | 1140.59 | 29-JUN-15:02 | 583.20 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 6.34 | 0.00 |
July | 1137.22 | 09-JUL-15:02 | 324.00 | 221.41 | 325.16 | 0.00 | 0.00 | 0.00 | 0.00 | 8.86 | 0.00 |
August | 1139.08 | 06-AUG-15:02 | 324.00 | 221.41 | 325.16 | 0.00 | 0.00 | 0.00 | 0.00 | 7.30 | 0.00 |
September | 1125.91 | 10-SEP-18:01 | 819.00 | 782.76 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 2.98 | 0.00 |
October | 1202.60 | 11-OCT-21:52 | 1080.00 | 449.53 | 526.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 |
November | 1136.64 | 28-NOV-19:02 | 831.60 | 597.13 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.95 |
December | 995.52 | 11-DEC-16:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.19 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 985.72 | 324.00 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1283.52 | 1602.00 | 1006.40 | 1780.62 | 0.00 | 0.00 | 0.00 | 0.00 | 8.86 | 8.95 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3029.22 | 29-JAN-16:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.98 |
February | 3115.23 | 27-FEB-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.55 | 0.00 |
March | 3085.76 | 10-MAR-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.06 |
April | 3086.99 | 09-APR-18:01 | 819.00 | 1245.18 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.01 |
May | 3084.15 | 09-MAY-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.40 |
June | 2821.61 | 05-JUN-08:61 | 252.00 | 547.88 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 2.94 | 0.00 |
July | 2864.78 | 21-JUL-08:61 | 360.00 | 782.68 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 9.52 | 0.00 |
August | 2848.12 | 01-AUG-08:61 | 252.00 | 547.88 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 10.68 | 0.00 |
September | 2829.58 | 09-SEP-08:61 | 378.00 | 697.30 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 0.00 |
October | 2777.79 | 17-OCT-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 5.27 | 0.00 |
November | 3063.96 | 14-NOV-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.82 |
December | 2930.67 | 09-DEC-16:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.08 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2777.79 | 252.00 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3115.23 | 970.20 | 1245.18 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 10.68 | 24.08 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2240.48 | 31-JAN-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.98 |
February | 3063.33 | 27-FEB-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.84 | 0.00 |
March | 2976.70 | 10-MAR-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.87 |
April | 2962.24 | 14-APR-08:51 | 360.00 | 782.59 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.59 |
May | 3158.05 | 16-MAY-08:51 | 360.00 | 782.59 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.99 |
June | 3207.87 | 04-JUN-08:51 | 540.00 | 996.02 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.04 |
July | 3003.30 | 17-JUL-08:51 | 360.00 | 782.59 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 1.91 | 0.00 |
August | 3050.60 | 26-AUG-08:51 | 540.00 | 996.02 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.06 |
September | 3073.40 | 15-SEP-08:51 | 360.00 | 782.59 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.74 |
October | 2732.45 | 11-OCT-15:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 12.81 | 0.00 |
November | 2640.24 | 07-NOV-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.64 |
December | 2197.60 | 19-DEC-09:04 | 252.00 | 547.81 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.66 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2197.60 | 252.00 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3207.87 | 680.40 | 996.02 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 12.81 | 59.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1970.07 | 31-JAN-22:10 | 2263.36 | 1244.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.06 |
February | 2062.16 | 28-FEB-22:10 | 2263.36 | 1244.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.97 |
March | 2151.11 | 30-MAR-21:51 | 15843.49 | 8714.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.88 | 0.00 |
April | 2222.15 | 19-APR-21:10 | 2263.36 | 1244.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.98 |
May | 2270.09 | 19-MAY-21:12 | 9053.42 | 4979.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.98 | 0.00 |
June | 2395.58 | 29-JUN-21:10 | 2263.36 | 1244.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.40 | 0.00 |
July | 2442.35 | 07-JUL-21:10 | 2263.36 | 1244.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.19 | 0.00 |
August | 2464.61 | 18-AUG-21:10 | 2263.36 | 1244.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.28 | 0.00 |
September | 2360.28 | 08-SEP-21:10 | 2263.36 | 1244.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.40 | 0.00 |
October | 2201.67 | 11-OCT-21:10 | 2263.36 | 1244.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.54 |
November | 2029.07 | 02-NOV-21:10 | 2263.36 | 1244.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.34 |
December | 2018.03 | 12-DEC-22:10 | 2263.36 | 1244.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.41 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 1970.07 | 2263.36 | 1244.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2464.61 | 15843.49 | 8714.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.28 | 25.06 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3473.19 | 29-JAN-16:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.05 |
February | 3591.55 | 27-FEB-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 | 0.00 |
March | 3556.18 | 10-MAR-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.32 |
April | 3591.69 | 09-APR-18:01 | 819.00 | 1245.18 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.59 |
May | 3563.80 | 09-MAY-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.74 |
June | 3121.61 | 26-JUN-18:02 | 831.60 | 949.89 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 0.00 |
July | 3075.48 | 27-JUL-15:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 4.41 | 0.00 |
August | 3088.08 | 08-AUG-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 12.36 | 0.00 |
September | 3181.34 | 09-SEP-18:02 | 702.00 | 1067.29 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 3.57 | 0.00 |
October | 3405.93 | 31-OCT-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.74 |
November | 3536.98 | 14-NOV-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.12 |
December | 3477.78 | 09-DEC-16:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.66 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3075.48 | 378.00 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3591.69 | 970.20 | 1245.18 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 12.36 | 30.74 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2314.24 | 20-JAN-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.59 |
February | 3512.18 | 27-FEB-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.63 | 0.00 |
March | 3485.36 | 10-MAR-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.03 |
April | 3726.09 | 26-APR-18:41 | 1247.40 | 1424.67 | 1090.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.37 |
May | 3808.41 | 09-MAY-20:41 | 1602.00 | 1582.97 | 1817.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.03 |
June | 3145.98 | 07-JUN-21:51 | 1620.00 | 1072.50 | 805.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.98 |
July | 3189.35 | 02-JUL-21:51 | 1108.80 | 1209.46 | 716.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.79 |
August | 3196.47 | 08-AUG-18:01 | 970.20 | 1108.08 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 11.69 | 0.00 |
September | 3402.23 | 18-SEP-16:01 | 972.00 | 498.01 | 1264.17 | 0.00 | 0.00 | 0.00 | 0.00 | 2.12 | 0.00 |
October | 3358.32 | 15-OCT-16:21 | 858.60 | 528.25 | 948.12 | 0.00 | 0.00 | 0.00 | 0.00 | 1.20 | 0.00 |
November | 3448.66 | 14-NOV-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 |
December | 2827.08 | 11-DEC-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.44 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2314.24 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3808.41 | 1620.00 | 1582.97 | 1817.24 | 0.00 | 0.00 | 0.00 | 0.00 | 11.69 | 31.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1823.66 | 27-JAN-16:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.01 |
February | 1841.49 | 26-FEB-19:01 | 819.00 | 782.76 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.99 |
March | 1863.85 | 10-MAR-16:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.04 |
April | 1843.19 | 09-APR-18:01 | 819.00 | 782.76 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.31 |
May | 1838.74 | 10-MAY-18:01 | 970.20 | 696.66 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.48 |
June | 1646.51 | 30-JUN-18:02 | 831.60 | 597.13 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 3.66 | 0.00 |
July | 1656.23 | 27-JUL-15:02 | 583.20 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 2.06 | 0.00 |
August | 1657.99 | 08-AUG-18:01 | 970.20 | 696.66 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 6.13 | 0.00 |
September | 1657.77 | 17-SEP-18:01 | 819.00 | 782.76 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 1.94 | 0.00 |
October | 1822.38 | 12-OCT-18:01 | 970.20 | 696.66 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.30 |
November | 1810.50 | 15-NOV-19:01 | 970.20 | 696.66 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.18 |
December | 1840.24 | 19-DEC-16:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.23 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1646.51 | 583.20 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1863.85 | 970.20 | 782.76 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 6.13 | 30.01 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 17509.82 | 19-JAN-22:57 | 80966.30 | 5976.06 | 20243.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.43 |
February | 18713.82 | 28-FEB-22:53 | 161932.61 | 11952.12 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.16 |
March | 20363.76 | 30-MAR-21:53 | 188921.38 | 13944.14 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.43 |
April | 20447.83 | 18-APR-21:53 | 188921.38 | 13944.14 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.67 |
May | 21368.17 | 19-MAY-21:05 | 107955.07 | 7968.08 | 26991.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.52 |
June | 22558.57 | 13-JUN-22:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 22.23 | 0.00 |
July | 23282.75 | 07-JUL-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 44.57 | 0.00 |
August | 23011.32 | 18-AUG-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 47.45 | 0.00 |
September | 21753.38 | 07-SEP-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 9.35 | 0.00 |
October | 20240.98 | 18-OCT-21:53 | 161932.61 | 11952.12 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.46 |
November | 18615.66 | 03-NOV-21:53 | 161932.61 | 11952.12 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.84 |
December | 18140.87 | 12-DEC-22:54 | 134943.84 | 9960.10 | 33739.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 17509.82 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23282.75 | 188921.38 | 13944.14 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 47.45 | 50.16 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19440.19 | 19-JAN-22:57 | 80966.30 | 5976.06 | 20243.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.43 |
February | 20608.48 | 28-FEB-22:53 | 161932.61 | 11952.12 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.16 |
March | 22153.53 | 30-MAR-21:53 | 188921.38 | 13944.14 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.43 |
April | 22126.62 | 18-APR-21:53 | 188921.38 | 13944.14 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.67 |
May | 22945.95 | 30-MAY-21:05 | 107955.07 | 7968.08 | 26991.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.52 |
June | 24020.34 | 13-JUN-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 28.69 | 0.00 |
July | 24589.00 | 07-JUL-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 44.57 | 0.00 |
August | 24301.81 | 18-AUG-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 47.45 | 0.00 |
September | 23227.54 | 07-SEP-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 9.35 | 0.00 |
October | 22058.85 | 18-OCT-21:53 | 161932.61 | 11952.12 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.46 |
November | 20577.63 | 03-NOV-21:53 | 161932.61 | 11952.12 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.84 |
December | 20084.76 | 12-DEC-22:54 | 134943.84 | 9960.10 | 33739.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 19440.19 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24589.00 | 188921.38 | 13944.14 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 47.45 | 50.16 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 26841.49 | 29-JAN-11:40 | 1601.14 | 707.21 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 80.01 |
February | 28008.56 | 26-FEB-11:40 | 1601.14 | 707.21 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 13.23 |
March | 28429.04 | 30-MAR-10:45 | 1067.42 | 589.34 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 14.72 |
April | 31287.24 | 15-APR-10:40 | 1601.14 | 589.34 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 1.90 | 0.00 |
May | 30148.74 | 15-MAY-18:09 | 13075.94 | 6600.59 | 104389.99 | 104966.55 | 0.00 | 0.00 | 0.00 | 23.40 | 0.00 |
June | 30496.53 | 25-JUN-10:40 | 1601.14 | 707.21 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 36.33 | 0.00 |
July | 30954.49 | 08-JUL-10:50 | 800.57 | 294.67 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 58.85 | 0.00 |
August | 30803.03 | 27-AUG-10:50 | 800.57 | 353.60 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 37.55 | 0.00 |
September | 30313.24 | 09-SEP-10:50 | 800.57 | 294.67 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 39.48 | 0.00 |
October | 29044.62 | 09-OCT-10:50 | 1601.14 | 707.21 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
November | 27650.90 | 11-NOV-11:40 | 1601.14 | 707.21 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 37.00 |
December | 27242.60 | 12-DEC-11:50 | 1067.42 | 589.34 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 25.66 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 26841.49 | 800.57 | 294.67 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31287.24 | 13075.94 | 6600.59 | 104389.99 | 104966.55 | 0.00 | 0.00 | 0.00 | 58.85 | 80.01 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3902.17 | 31-JAN-22:10 | 2395.44 | 1317.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.66 |
February | 4139.99 | 28-FEB-22:10 | 2395.44 | 1317.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.44 |
March | 4466.15 | 30-MAR-21:10 | 9581.76 | 5270.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.88 | 0.00 |
April | 4655.40 | 17-APR-18:03 | 13041.84 | 12296.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.22 | 0.00 |
May | 4852.12 | 20-MAY-15:30 | 798.48 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.77 | 0.00 |
June | 5092.59 | 24-JUN-18:02 | 9581.76 | 9222.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.33 | 0.00 |
July | 5955.60 | 08-JUL-17:13 | 4790.88 | 3952.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.96 | 0.00 |
August | 5310.36 | 18-AUG-15:50 | 1330.80 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.96 | 0.00 |
September | 4997.60 | 07-SEP-16:00 | 1330.80 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.91 | 0.00 |
October | 4581.63 | 11-OCT-15:50 | 1330.80 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.32 | 0.00 |
November | 4150.17 | 05-NOV-15:10 | 5589.36 | 3074.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.77 | 0.00 |
December | 4035.11 | 12-DEC-22:10 | 2395.44 | 1317.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 3902.17 | 798.48 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5955.60 | 13041.84 | 12296.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.96 | 43.66 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.558793E+12 | 403863.18 | 03-JAN-07:40 | 0.384525E+12 | 342272.59 | 30-JAN-18:49 |
February | 0.468251E+12 | 386284.36 | 07-FEB-07:10 | 0.347650E+12 | 342425.84 | 03-FEB-18:19 |
March | 0.477015E+12 | 364365.96 | 06-MAR-07:19 | 0.379121E+12 | 339611.83 | 01-MAR-18:19 |
April | 0.468530E+12 | 386567.29 | 07-APR-06:19 | 0.356010E+12 | 329670.12 | 05-APR-17:49 |
May | 0.529957E+12 | 334393.07 | 30-MAY-18:10 | 0.354903E+12 | 319561.45 | 01-MAY-17:00 |
June | 0.590873E+12 | 362504.31 | 28-JUN-18:10 | 0.332218E+12 | 305297.08 | 01-JUN-17:40 |
July | 0.667847E+12 | 381553.97 | 06-JUL-18:10 | 0.335965E+12 | 296795.84 | 03-JUL-17:30 |
August | 0.681725E+12 | 380045.19 | 18-AUG-18:19 | 0.335699E+12 | 295376.31 | 29-AUG-17:30 |
September | 0.560151E+12 | 357704.92 | 07-SEP-18:00 | 0.330610E+12 | 303558.81 | 29-SEP-17:19 |
October | 0.484386E+12 | 395167.73 | 26-OCT-06:10 | 0.352788E+12 | 316072.87 | 30-OCT-17:49 |
November | 0.478975E+12 | 383203.06 | 14-NOV-07:10 | 0.354182E+12 | 328478.01 | 30-NOV-18:49 |
December | 0.543500E+12 | 391194.17 | 07-DEC-07:10 | 0.377399E+12 | 337538.30 | 29-DEC-18:40 |
Annual Sum or Average | 0.651000E+13 | 0.424107E+13 | ||||
Minimum of Months | 0.468251E+12 | 334393.07 | 0.330610E+12 | 295376.31 | ||
Maximum of Months | 0.681725E+12 | 403863.18 | 0.384525E+12 | 342425.84 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.671446E+11 | 0.192036E+11 | 0.140828E+12 | 0.691146E+11 | 0.353836E+11 | 0.295600E+10 | 0.191968E+12 | 0.607837E+10 | 0.00 | 0.00 | 0.129348E+11 | 0.804914E+10 | 0.00 |
February | 0.606091E+11 | 0.163904E+11 | 0.127191E+12 | 0.624262E+11 | 0.320960E+11 | 0.437833E+10 | 0.127562E+12 | 0.178338E+11 | 0.00 | 0.00 | 0.784322E+10 | 0.727334E+10 | 0.00 |
March | 0.666049E+11 | 0.167606E+11 | 0.140882E+12 | 0.691169E+11 | 0.362811E+11 | 0.796733E+10 | 0.766701E+11 | 0.456138E+11 | 0.00 | 0.00 | 0.388490E+10 | 0.804737E+10 | 0.00 |
April | 0.641287E+11 | 0.148358E+11 | 0.136245E+12 | 0.668844E+11 | 0.364895E+11 | 0.866503E+10 | 0.373119E+11 | 0.840499E+11 | 0.00 | 0.00 | 0.706389E+10 | 0.779851E+10 | 0.00 |
May | 0.659154E+11 | 0.141251E+11 | 0.140860E+12 | 0.691151E+11 | 0.394489E+11 | 0.952473E+10 | 0.121909E+11 | 0.152049E+12 | 0.00 | 0.00 | 0.134019E+11 | 0.804841E+10 | 0.00 |
June | 0.636076E+11 | 0.131404E+11 | 0.136336E+12 | 0.668864E+11 | 0.406883E+11 | 0.972415E+10 | 0.357352E+10 | 0.224119E+12 | 0.00 | 0.00 | 0.198865E+11 | 0.778971E+10 | 0.00 |
July | 0.658492E+11 | 0.137771E+11 | 0.140770E+12 | 0.691126E+11 | 0.428320E+11 | 0.104125E+11 | 0.260600E+10 | 0.284363E+12 | 0.00 | 0.00 | 0.247934E+11 | 0.805661E+10 | 0.00 |
August | 0.660429E+11 | 0.147839E+11 | 0.140892E+12 | 0.691166E+11 | 0.432159E+11 | 0.105279E+11 | 0.250706E+10 | 0.295816E+12 | 0.00 | 0.00 | 0.254719E+11 | 0.804813E+10 | 0.00 |
September | 0.644097E+11 | 0.156205E+11 | 0.136256E+12 | 0.668846E+11 | 0.386551E+11 | 0.955391E+10 | 0.364332E+10 | 0.194736E+12 | 0.00 | 0.00 | 0.174688E+11 | 0.779966E+10 | 0.00 |
October | 0.669938E+11 | 0.175749E+11 | 0.140818E+12 | 0.691144E+11 | 0.370746E+11 | 0.889161E+10 | 0.374166E+11 | 0.858187E+11 | 0.00 | 0.00 | 0.739321E+10 | 0.804726E+10 | 0.00 |
November | 0.649060E+11 | 0.182634E+11 | 0.136330E+12 | 0.668858E+11 | 0.346066E+11 | 0.701264E+10 | 0.951984E+11 | 0.378537E+11 | 0.00 | 0.00 | 0.513064E+10 | 0.778190E+10 | 0.00 |
December | 0.671261E+11 | 0.195441E+11 | 0.140770E+12 | 0.691135E+11 | 0.351721E+11 | 0.464110E+10 | 0.174784E+12 | 0.122149E+11 | 0.00 | 0.00 | 0.692611E+10 | 0.805748E+10 | 0.00 |
Annual Sum or Average | 0.783338E+12 | 0.194020E+12 | 0.165818E+13 | 0.813771E+12 | 0.451944E+12 | 0.942552E+11 | 0.765433E+12 | 0.144055E+13 | 0.00 | 0.00 | 0.152199E+12 | 0.947975E+11 | 0.00 |
Minimum of Months | 0.606091E+11 | 0.131404E+11 | 0.127191E+12 | 0.624262E+11 | 0.320960E+11 | 0.295600E+10 | 0.250706E+10 | 0.607837E+10 | 0.00 | 0.00 | 0.388490E+10 | 0.727334E+10 | 0.00 |
Maximum of Months | 0.671446E+11 | 0.195441E+11 | 0.140892E+12 | 0.691169E+11 | 0.432159E+11 | 0.105279E+11 | 0.191968E+12 | 0.295816E+12 | 0.00 | 0.00 | 0.254719E+11 | 0.805748E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.151918E+12 | 0.00 | 0.00 | 0.00 | 0.232606E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.00 | 0.00 | 0.210446E+12 | 0.00 | 0.00 |
March | 0.152024E+12 | 0.00 | 0.00 | 0.00 | 0.227098E+12 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.00 | 0.00 | 0.209055E+12 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.00 | 0.00 | 0.202925E+12 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 0.00 | 0.00 | 0.185104E+12 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 0.00 | 0.00 | 0.184145E+12 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 0.00 | 0.00 | 0.183660E+12 | 0.00 | 0.00 |
September | 0.146971E+12 | 0.00 | 0.00 | 0.00 | 0.183639E+12 | 0.00 | 0.00 |
October | 0.151903E+12 | 0.00 | 0.00 | 0.00 | 0.200885E+12 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.00 | 0.00 | 0.207091E+12 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.00 | 0.00 | 0.225578E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178884E+13 | 0.00 | 0.00 | 0.00 | 0.245223E+13 | 0.00 | 0.00 |
Minimum of Months | 0.137204E+12 | 0.00 | 0.00 | 0.00 | 0.183639E+12 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.00 | 0.00 | 0.232606E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 64632.59 | 02-JAN-20:10 | 12338.45 | 01-JAN-00:10 | 89171.45 | 02-JAN-07:10 | 49607.07 | 02-JAN-07:19 | 20639.35 | 07-JAN-16:10 | 3511.90 | 19-JAN-22:00 | 212663.19 | 03-JAN-16:10 |
February | 64632.59 | 01-FEB-20:10 | 12338.45 | 01-FEB-00:10 | 89171.45 | 01-FEB-07:10 | 49607.07 | 01-FEB-07:19 | 19170.91 | 11-FEB-19:10 | 3564.67 | 28-FEB-16:10 | 204377.74 | 07-FEB-09:09 |
March | 64632.59 | 01-MAR-20:10 | 12338.45 | 01-MAR-00:10 | 89171.45 | 01-MAR-07:10 | 49607.07 | 01-MAR-07:19 | 21493.75 | 30-MAR-18:10 | 3818.18 | 30-MAR-19:19 | 169724.58 | 22-MAR-08:30 |
April | 64632.59 | 03-APR-19:10 | 12338.45 | 01-APR-00:10 | 89171.45 | 03-APR-06:10 | 49607.07 | 03-APR-06:19 | 22760.03 | 17-APR-18:10 | 3938.52 | 13-APR-15:09 | 170758.59 | 07-APR-06:19 |
May | 64632.59 | 01-MAY-19:19 | 12338.45 | 01-MAY-00:10 | 89171.45 | 01-MAY-06:10 | 49607.07 | 08-MAY-06:19 | 23157.64 | 16-MAY-18:30 | 4273.27 | 30-MAY-21:00 | 60791.95 | 11-MAY-05:00 |
June | 64632.59 | 01-JUN-19:30 | 12338.45 | 01-JUN-00:10 | 89171.45 | 01-JUN-06:10 | 49606.78 | 23-JUN-06:19 | 24763.16 | 05-JUN-18:19 | 4481.53 | 26-JUN-21:00 | 19895.52 | 10-JUN-04:00 |
July | 64632.59 | 03-JUL-19:30 | 12338.45 | 01-JUL-00:10 | 89171.45 | 03-JUL-06:10 | 49606.97 | 28-JUL-06:19 | 25689.69 | 07-JUL-18:19 | 4670.58 | 18-JUL-18:00 | 6939.25 | 29-JUL-04:00 |
August | 64632.59 | 01-AUG-19:19 | 12338.45 | 01-AUG-00:10 | 89171.45 | 01-AUG-06:10 | 49607.07 | 14-AUG-06:19 | 25099.19 | 18-AUG-18:19 | 4562.92 | 23-AUG-22:00 | 5906.27 | 21-AUG-03:00 |
September | 64632.59 | 01-SEP-19:10 | 12338.45 | 01-SEP-00:10 | 89171.45 | 01-SEP-06:10 | 49607.07 | 01-SEP-06:19 | 23459.41 | 07-SEP-18:10 | 4384.62 | 09-SEP-21:00 | 14667.51 | 14-SEP-15:39 |
October | 64632.59 | 02-OCT-19:10 | 12338.45 | 01-OCT-00:10 | 89171.45 | 02-OCT-06:10 | 49607.07 | 02-OCT-06:19 | 21176.96 | 10-OCT-18:10 | 4417.10 | 18-OCT-21:00 | 180983.59 | 26-OCT-06:10 |
November | 64632.59 | 01-NOV-19:10 | 12338.45 | 01-NOV-00:10 | 89171.45 | 01-NOV-06:10 | 49607.07 | 01-NOV-06:19 | 18511.15 | 05-NOV-15:09 | 3734.74 | 05-NOV-15:30 | 184456.98 | 22-NOV-09:30 |
December | 64632.59 | 01-DEC-20:10 | 12338.45 | 01-DEC-00:10 | 89171.45 | 01-DEC-07:10 | 49607.07 | 01-DEC-07:19 | 18696.35 | 13-DEC-21:10 | 3568.78 | 13-DEC-10:00 | 199522.65 | 21-DEC-09:09 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 64632.59 | 12338.45 | 89171.45 | 49606.78 | 18511.15 | 3511.90 | 5906.27 | |||||||
Maximum of Months | 64632.59 | 12338.45 | 89171.45 | 49607.07 | 25689.69 | 4670.58 | 212663.19 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 55621.61 | 19-JAN-22:00 | 0.00 | 0.00 | 9938.94 | 02-JAN-03:39 | 4751.74 | 09-JAN-07:10 | 0.00 |
February | 70861.16 | 28-FEB-16:10 | 0.00 | 0.00 | 9938.94 | 01-FEB-03:09 | 4751.85 | 13-FEB-07:10 | 0.00 |
March | 90338.43 | 30-MAR-18:10 | 0.00 | 0.00 | 9938.94 | 04-MAR-16:49 | 4751.33 | 23-MAR-06:10 | 0.00 |
April | 92427.85 | 04-APR-15:09 | 0.00 | 0.00 | 9938.94 | 02-APR-12:39 | 4751.40 | 06-APR-06:10 | 0.00 |
May | 131333.24 | 30-MAY-18:10 | 0.00 | 0.00 | 9938.94 | 06-MAY-08:00 | 4751.26 | 15-MAY-18:00 | 0.00 |
June | 158182.64 | 28-JUN-18:10 | 0.00 | 0.00 | 9938.94 | 03-JUN-08:00 | 4751.13 | 01-JUN-18:40 | 0.00 |
July | 176077.58 | 06-JUL-18:10 | 0.00 | 0.00 | 9938.94 | 02-JUL-08:00 | 4751.13 | 31-JUL-18:49 | 0.00 |
August | 174729.43 | 18-AUG-18:19 | 0.00 | 0.00 | 9938.94 | 06-AUG-08:30 | 4751.13 | 02-AUG-06:00 | 0.00 |
September | 152877.97 | 07-SEP-15:20 | 0.00 | 0.00 | 9938.94 | 04-SEP-08:00 | 4751.13 | 20-SEP-06:49 | 0.00 |
October | 151570.08 | 18-OCT-21:00 | 0.00 | 0.00 | 9938.94 | 01-OCT-15:20 | 4751.39 | 26-OCT-06:10 | 0.00 |
November | 86951.71 | 05-NOV-15:09 | 0.00 | 0.00 | 9938.94 | 02-NOV-12:30 | 4751.66 | 22-NOV-07:10 | 0.00 |
December | 61481.96 | 13-DEC-10:00 | 0.00 | 0.00 | 9938.94 | 01-DEC-00:10 | 4751.69 | 04-DEC-07:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 55621.61 | 0.00 | 0.00 | 9938.94 | 4751.13 | 0.00 | |||
Maximum of Months | 176077.58 | 0.00 | 0.00 | 9938.94 | 4751.85 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 403863.18 | 03-JAN-07:40 | 36001.17 | 89171.45 | 12338.45 | 49607.07 | 15377.46 | 2515.47 | 186734.08 | 2631.88 | 0.00 |
February | 386284.36 | 07-FEB-07:10 | 36001.17 | 89171.45 | 12338.45 | 49600.84 | 13310.70 | 47.91 | 176323.23 | 0.00 | 0.00 |
March | 364365.96 | 06-MAR-07:19 | 36001.17 | 89171.45 | 0.00 | 49607.07 | 13556.29 | 3334.80 | 161996.74 | 2604.21 | 0.00 |
April | 386567.29 | 07-APR-06:19 | 36001.17 | 89171.45 | 12338.45 | 49607.07 | 14069.01 | 3333.96 | 170758.59 | 1806.92 | 0.00 |
May | 334393.07 | 30-MAY-18:10 | 53578.21 | 77573.37 | 0.00 | 28157.54 | 22418.07 | 4125.27 | 664.02 | 131333.24 | 0.00 |
June | 362504.31 | 28-JUN-18:10 | 53184.46 | 77573.37 | 0.00 | 28157.33 | 23994.08 | 4309.92 | 0.00 | 158182.64 | 0.00 |
July | 381553.97 | 06-JUL-18:10 | 53184.46 | 77573.37 | 0.00 | 28157.33 | 25025.51 | 4433.50 | 0.00 | 176077.58 | 0.00 |
August | 380045.19 | 18-AUG-18:19 | 53578.21 | 77573.37 | 0.00 | 28166.83 | 25099.19 | 4360.47 | 0.00 | 174729.43 | 0.00 |
September | 357704.92 | 07-SEP-18:00 | 57474.69 | 77573.37 | 12338.45 | 28169.74 | 21999.92 | 4238.09 | 0.00 | 138809.73 | 0.00 |
October | 395167.73 | 26-OCT-06:10 | 36001.17 | 89171.45 | 12338.45 | 49600.84 | 14281.69 | 2515.45 | 180983.59 | 2180.76 | 0.00 |
November | 383203.06 | 14-NOV-07:10 | 36001.17 | 89171.45 | 12338.45 | 49600.84 | 15234.59 | 2243.33 | 166013.58 | 3125.44 | 0.00 |
December | 391194.17 | 07-DEC-07:10 | 36001.17 | 89171.45 | 12338.45 | 49600.84 | 14302.34 | 2515.37 | 177093.34 | 2072.14 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 334393.07 | 36001.17 | 77573.37 | 0.00 | 28157.33 | 13310.70 | 47.91 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 403863.18 | 57474.69 | 89171.45 | 12338.45 | 49607.07 | 25099.19 | 4433.50 | 186734.08 | 176077.58 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 0.00 | 0.00 | 240343.53 | 31-JAN-21:19 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 0.00 | 0.00 | 240345.44 | 01-FEB-21:19 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 0.00 | 0.00 | 238028.45 | 01-MAR-21:00 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 0.00 | 0.00 | 228132.18 | 03-APR-20:49 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 0.00 | 0.00 | 216571.49 | 01-MAY-20:30 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 0.00 | 0.00 | 203975.15 | 01-JUN-20:19 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 0.00 | 0.00 | 193911.11 | 03-JUL-20:00 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 0.00 | 0.00 | 193758.86 | 31-AUG-20:40 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 0.00 | 0.00 | 202218.84 | 29-SEP-20:40 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 0.00 | 0.00 | 214982.93 | 31-OCT-20:19 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 0.00 | 0.00 | 226845.24 | 30-NOV-21:19 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 0.00 | 0.00 | 236489.20 | 28-DEC-21:19 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 104248.32 | 0.00 | 0.00 | 0.00 | 193758.86 | 0.00 | ||
Maximum of Months | 104248.32 | 0.00 | 0.00 | 0.00 | 240345.44 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.83 | 20.49 | 1.83 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 |
February | 0.50 | 20.51 | 0.50 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.68 | 0.50 | 21.68 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.70 | 0.67 | 21.70 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.33 | 20.50 | 2.33 | 20.50 | 1.17 | 20.74 | 1.17 | 20.89 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.83 | 20.51 | 1.83 | 20.51 | 0.67 | 21.70 | 0.67 | 21.70 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.17 | 20.48 | 3.17 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 |
February | 1.00 | 20.44 | 1.00 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.71 | 0.67 | 21.71 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.77 | 1.83 | 21.77 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.80 | 0.17 | 21.80 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.72 | 0.33 | 21.72 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.72 | 0.17 | 21.72 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 20.53 | 0.17 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 |
Annual Sum or Average | 4.33 | 20.47 | 4.33 | 20.47 | 3.17 | 20.81 | 3.17 | 21.01 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.17 | 20.53 | 3.17 | 20.53 | 1.83 | 21.80 | 1.83 | 21.80 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 20.38 | 0.67 | 20.38 | 0.00 | 20.38 | 0.00 | 20.38 |
February | 0.33 | 20.37 | 0.33 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.75 | 0.67 | 21.75 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 21.75 | 2.17 | 21.75 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 21.79 | 2.67 | 21.79 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 21.89 | 3.83 | 21.89 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 21.83 | 2.00 | 21.83 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.83 | 1.00 | 21.83 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.69 | 0.50 | 21.69 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.00 | 20.38 | 1.00 | 20.38 | 12.83 | 21.62 | 12.83 | 21.71 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 20.38 | 0.67 | 20.38 | 3.83 | 21.89 | 3.83 | 21.89 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.50 | 20.47 | 1.50 | 20.47 | 0.17 | 20.54 | 0.17 | 20.61 |
February | 0.17 | 20.53 | 0.17 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.73 | 0.17 | 21.73 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.67 | 20.48 | 1.67 | 20.48 | 0.33 | 20.60 | 0.33 | 20.70 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.50 | 20.53 | 1.50 | 20.53 | 0.17 | 21.73 | 0.17 | 21.73 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.33 | 20.47 | 2.33 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
February | 1.00 | 20.53 | 1.00 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.93 | 0.83 | 21.93 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 22.14 | 2.33 | 22.14 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 22.12 | 6.00 | 22.12 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 22.20 | 6.67 | 22.20 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 22.10 | 4.00 | 22.10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 22.05 | 3.00 | 22.05 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3.33 | 20.49 | 3.33 | 20.49 | 22.83 | 21.76 | 22.83 | 21.92 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.33 | 20.53 | 2.33 | 20.53 | 6.67 | 22.20 | 6.67 | 22.20 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.67 | 20.49 | 1.67 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 |
February | 0.33 | 20.48 | 0.33 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.69 | 0.67 | 21.69 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 21.76 | 2.67 | 21.76 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 21.78 | 2.33 | 21.78 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.74 | 0.83 | 21.74 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.00 | 20.49 | 2.00 | 20.49 | 6.50 | 21.27 | 6.50 | 21.46 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.67 | 20.49 | 1.67 | 20.49 | 2.67 | 21.78 | 2.67 | 21.78 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.83 | 20.47 | 2.83 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
February | 0.83 | 20.38 | 0.83 | 20.38 | 0.00 | 20.38 | 0.00 | 20.38 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.76 | 0.17 | 21.76 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 21.72 | 2.00 | 21.72 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 21.76 | 5.17 | 21.76 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 21.75 | 2.00 | 21.75 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.85 | 0.33 | 21.85 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.79 | 0.17 | 21.79 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 20.53 | 0.17 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 |
Annual Sum or Average | 3.83 | 20.45 | 3.83 | 20.45 | 9.83 | 21.18 | 9.83 | 21.39 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.83 | 20.53 | 2.83 | 20.53 | 5.17 | 21.85 | 5.17 | 21.85 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 20.44 | 0.33 | 20.44 | 0.50 | 21.01 | 0.50 | 21.23 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.81 | 1.17 | 21.81 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.80 | 0.50 | 21.80 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.71 | 1.00 | 21.71 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.71 | 1.00 | 21.71 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 21.81 | 2.67 | 21.81 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 21.82 | 2.50 | 21.82 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 21.83 | 2.33 | 21.83 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.79 | 0.50 | 21.79 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.78 | 0.50 | 21.78 |
Annual Sum or Average | 0.33 | 20.44 | 0.33 | 20.44 | 12.67 | 21.73 | 12.67 | 21.76 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 20.44 | 0.33 | 20.44 | 2.67 | 21.83 | 2.67 | 21.83 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.77 | 0.50 | 24.77 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.71 | 0.67 | 24.71 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.17 | 24.74 | 1.17 | 24.74 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.77 | 0.67 | 24.77 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.36 | 3.67 | 21.36 | 3.67 | 21.36 |
February | 672.00 | 21.17 | 43.50 | 21.16 | 43.50 | 21.15 |
March | 744.00 | 21.08 | 25.67 | 21.08 | 25.67 | 21.08 |
April | 720.00 | 21.04 | 2.83 | 21.04 | 2.83 | 21.04 |
May | 744.00 | 21.08 | 0.00 | 21.08 | 0.00 | 21.08 |
June | 720.00 | 21.35 | 0.00 | 21.35 | 0.00 | 21.35 |
July | 744.00 | 21.81 | 0.00 | 21.81 | 0.00 | 21.81 |
August | 744.00 | 22.37 | 0.00 | 22.37 | 0.00 | 22.37 |
September | 693.00 | 22.84 | 0.00 | 22.84 | 0.00 | 22.84 |
October | 727.83 | 22.96 | 0.00 | 22.96 | 0.00 | 22.96 |
November | 713.33 | 22.98 | 0.00 | 22.98 | 0.00 | 22.98 |
December | 744.00 | 22.38 | 0.00 | 22.38 | 0.00 | 22.38 |
Annual Sum or Average | 8710.17 | 21.87 | 75.67 | 21.86 | 75.67 | 21.85 |
Minimum of Months | 672.00 | 21.04 | 0.00 | 21.04 | 0.00 | 21.04 |
Maximum of Months | 744.00 | 22.98 | 43.50 | 22.98 | 43.50 | 22.98 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.08 | 397.00 | 21.05 | 397.00 | 21.04 |
February | 666.50 | 21.15 | 231.67 | 21.11 | 231.67 | 21.09 |
March | 730.67 | 21.27 | 52.67 | 21.26 | 49.67 | 21.24 |
April | 694.67 | 21.32 | 14.33 | 21.32 | 14.33 | 21.31 |
May | 735.33 | 21.50 | 0.00 | 21.50 | 0.00 | 21.50 |
June | 592.67 | 21.86 | 11.33 | 21.89 | 0.00 | 21.89 |
July | 484.00 | 21.92 | 140.83 | 22.29 | 0.00 | 22.29 |
August | 373.83 | 22.10 | 251.50 | 22.71 | 0.00 | 22.71 |
September | 561.33 | 21.61 | 96.00 | 21.91 | 0.00 | 21.91 |
October | 664.50 | 21.39 | 38.50 | 21.52 | 0.67 | 21.52 |
November | 689.83 | 21.20 | 63.33 | 21.19 | 60.67 | 21.18 |
December | 736.83 | 21.14 | 230.67 | 21.11 | 229.33 | 21.09 |
Annual Sum or Average | 7674.17 | 21.41 | 1527.83 | 21.50 | 983.33 | 21.45 |
Minimum of Months | 373.83 | 21.08 | 0.00 | 21.05 | 0.00 | 21.04 |
Maximum of Months | 744.00 | 22.10 | 397.00 | 22.71 | 397.00 | 22.71 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.09 | 29.83 | 21.09 | 29.83 | 21.09 |
February | 672.00 | 21.19 | 53.17 | 21.18 | 53.17 | 21.17 |
March | 744.00 | 21.47 | 0.00 | 21.47 | 0.00 | 21.47 |
April | 720.00 | 21.70 | 0.00 | 21.70 | 0.00 | 21.70 |
May | 734.00 | 21.93 | 0.00 | 21.93 | 0.00 | 21.93 |
June | 627.17 | 22.32 | 20.33 | 22.36 | 0.00 | 22.36 |
July | 574.33 | 22.43 | 71.50 | 22.58 | 0.00 | 22.58 |
August | 515.50 | 22.58 | 97.83 | 22.77 | 0.00 | 22.77 |
September | 655.67 | 22.21 | 18.67 | 22.25 | 0.00 | 22.25 |
October | 740.83 | 21.73 | 0.00 | 21.73 | 0.00 | 21.73 |
November | 720.00 | 21.38 | 0.00 | 21.38 | 0.00 | 21.38 |
December | 744.00 | 21.17 | 4.67 | 21.17 | 4.67 | 21.17 |
Annual Sum or Average | 8191.50 | 21.72 | 296.00 | 21.77 | 87.67 | 21.76 |
Minimum of Months | 515.50 | 21.09 | 0.00 | 21.09 | 0.00 | 21.09 |
Maximum of Months | 744.00 | 22.58 | 97.83 | 22.77 | 53.17 | 22.77 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.00 | 451.83 | 21.00 | 451.83 | 21.00 |
February | 672.00 | 21.02 | 228.83 | 21.01 | 228.83 | 21.01 |
March | 744.00 | 21.09 | 65.17 | 21.08 | 65.17 | 21.07 |
April | 720.00 | 21.25 | 2.50 | 21.25 | 2.50 | 21.24 |
May | 744.00 | 21.62 | 0.00 | 21.62 | 0.00 | 21.62 |
June | 720.00 | 22.40 | 0.00 | 22.40 | 0.00 | 22.40 |
July | 715.67 | 22.69 | 0.00 | 22.69 | 0.00 | 22.69 |
August | 719.83 | 22.81 | 0.00 | 22.81 | 0.00 | 22.81 |
September | 720.00 | 22.11 | 0.00 | 22.11 | 0.00 | 22.11 |
October | 744.00 | 21.27 | 0.00 | 21.27 | 0.00 | 21.27 |
November | 720.00 | 21.06 | 36.33 | 21.06 | 36.33 | 21.05 |
December | 744.00 | 21.01 | 204.50 | 21.01 | 204.50 | 21.01 |
Annual Sum or Average | 8707.50 | 21.61 | 989.17 | 21.55 | 989.17 | 21.49 |
Minimum of Months | 672.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
Maximum of Months | 744.00 | 22.81 | 451.83 | 22.81 | 451.83 | 22.81 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.00 | 485.50 | 21.00 | 485.50 | 21.00 |
February | 672.00 | 21.00 | 255.17 | 21.00 | 255.17 | 21.00 |
March | 744.00 | 21.03 | 73.50 | 21.03 | 73.50 | 21.03 |
April | 720.00 | 21.12 | 4.00 | 21.12 | 4.00 | 21.12 |
May | 744.00 | 21.44 | 0.00 | 21.44 | 0.00 | 21.44 |
June | 720.00 | 22.20 | 0.00 | 22.20 | 0.00 | 22.20 |
July | 744.00 | 22.53 | 0.00 | 22.53 | 0.00 | 22.53 |
August | 744.00 | 22.64 | 0.00 | 22.64 | 0.00 | 22.64 |
September | 720.00 | 21.89 | 0.00 | 21.89 | 0.00 | 21.89 |
October | 744.00 | 21.14 | 0.00 | 21.14 | 0.00 | 21.14 |
November | 720.00 | 21.01 | 55.00 | 21.01 | 55.00 | 21.01 |
December | 744.00 | 21.00 | 253.67 | 21.00 | 253.67 | 21.00 |
Annual Sum or Average | 8760.00 | 21.50 | 1126.83 | 21.45 | 1126.83 | 21.40 |
Minimum of Months | 672.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
Maximum of Months | 744.00 | 22.64 | 485.50 | 22.64 | 485.50 | 22.64 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 541.17 | 21.67 | 224.17 | 22.18 | 119.33 | 22.43 |
February | 456.50 | 21.74 | 230.00 | 22.26 | 112.33 | 22.50 |
March | 428.83 | 21.97 | 300.67 | 22.45 | 138.83 | 22.70 |
April | 305.00 | 22.40 | 345.50 | 22.66 | 143.67 | 22.89 |
May | 226.50 | 23.11 | 480.00 | 22.68 | 163.50 | 22.91 |
June | 190.00 | 23.60 | 556.33 | 22.62 | 170.00 | 22.86 |
July | 185.33 | 23.78 | 602.83 | 22.60 | 178.00 | 22.84 |
August | 185.00 | 23.86 | 618.50 | 22.60 | 183.17 | 22.84 |
September | 194.17 | 23.44 | 499.83 | 22.68 | 162.50 | 22.91 |
October | 308.33 | 22.41 | 369.17 | 22.63 | 146.83 | 22.87 |
November | 429.17 | 21.89 | 286.67 | 22.38 | 128.00 | 22.63 |
December | 512.17 | 21.73 | 252.83 | 22.24 | 124.67 | 22.49 |
Annual Sum or Average | 3962.17 | 22.32 | 4766.50 | 22.50 | 1770.83 | 22.74 |
Minimum of Months | 185.00 | 21.67 | 224.17 | 22.18 | 112.33 | 22.43 |
Maximum of Months | 541.17 | 23.86 | 618.50 | 22.68 | 183.17 | 22.91 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 742.17 | 21.26 | 79.83 | 21.24 | 79.83 | 21.21 |
February | 661.17 | 21.47 | 45.50 | 21.44 | 45.50 | 21.41 |
March | 684.33 | 21.80 | 21.67 | 21.84 | 0.00 | 21.84 |
April | 612.00 | 21.82 | 25.00 | 21.88 | 0.00 | 21.88 |
May | 566.50 | 21.93 | 72.83 | 22.09 | 0.00 | 22.09 |
June | 348.33 | 21.99 | 263.33 | 22.62 | 7.17 | 22.63 |
July | 277.67 | 22.12 | 370.83 | 22.91 | 26.50 | 22.95 |
August | 247.17 | 22.67 | 512.50 | 23.25 | 98.33 | 23.30 |
September | 365.33 | 22.05 | 286.17 | 22.66 | 28.50 | 22.71 |
October | 544.83 | 21.90 | 108.33 | 22.15 | 1.83 | 22.15 |
November | 663.33 | 21.71 | 13.50 | 21.75 | 0.00 | 21.75 |
December | 725.33 | 21.43 | 9.17 | 21.44 | 5.67 | 21.43 |
Annual Sum or Average | 6438.17 | 21.75 | 1808.67 | 22.09 | 293.33 | 22.10 |
Minimum of Months | 247.17 | 21.26 | 9.17 | 21.24 | 0.00 | 21.21 |
Maximum of Months | 742.17 | 22.67 | 512.50 | 23.25 | 98.33 | 23.30 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.29 | 5.67 | 21.29 | 5.67 | 21.29 |
February | 672.00 | 21.46 | 4.33 | 21.46 | 4.33 | 21.46 |
March | 738.17 | 21.76 | 0.67 | 21.76 | 0.00 | 21.76 |
April | 704.83 | 21.92 | 0.00 | 21.92 | 0.00 | 21.92 |
May | 683.67 | 22.09 | 11.00 | 22.11 | 0.00 | 22.11 |
June | 474.67 | 22.22 | 108.33 | 22.48 | 0.00 | 22.48 |
July | 416.33 | 22.28 | 204.17 | 22.73 | 0.00 | 22.73 |
August | 351.67 | 22.37 | 286.50 | 22.94 | 0.00 | 22.94 |
September | 522.83 | 22.24 | 80.67 | 22.43 | 0.00 | 22.43 |
October | 715.17 | 22.02 | 4.17 | 22.03 | 0.00 | 22.03 |
November | 720.00 | 21.74 | 0.00 | 21.74 | 0.00 | 21.74 |
December | 744.00 | 21.45 | 0.00 | 21.45 | 0.00 | 21.45 |
Annual Sum or Average | 7487.33 | 21.85 | 705.50 | 22.00 | 10.00 | 22.00 |
Minimum of Months | 351.67 | 21.29 | 0.00 | 21.29 | 0.00 | 21.29 |
Maximum of Months | 744.00 | 22.37 | 286.50 | 22.94 | 5.67 | 22.94 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.91 | 416.67 | 20.84 | 416.67 | 20.81 |
February | 671.67 | 21.08 | 249.33 | 20.97 | 249.33 | 20.90 |
March | 736.67 | 21.44 | 20.67 | 21.41 | 20.67 | 21.39 |
April | 700.33 | 21.54 | 6.67 | 21.55 | 6.67 | 21.55 |
May | 701.00 | 21.58 | 1.83 | 21.58 | 1.83 | 21.58 |
June | 633.33 | 21.51 | 2.67 | 21.51 | 2.67 | 21.52 |
July | 637.17 | 21.46 | 9.83 | 21.48 | 8.83 | 21.50 |
August | 623.33 | 21.43 | 4.17 | 21.44 | 3.50 | 21.45 |
September | 658.17 | 21.53 | 5.83 | 21.54 | 5.83 | 21.55 |
October | 724.83 | 21.47 | 34.33 | 21.46 | 34.33 | 21.45 |
November | 716.67 | 21.37 | 50.00 | 21.34 | 50.00 | 21.32 |
December | 744.00 | 21.10 | 215.67 | 21.03 | 215.67 | 20.98 |
Annual Sum or Average | 8291.17 | 21.36 | 1017.67 | 21.30 | 1016.00 | 21.25 |
Minimum of Months | 623.33 | 20.91 | 1.83 | 20.84 | 1.83 | 20.81 |
Maximum of Months | 744.00 | 21.58 | 416.67 | 21.58 | 416.67 | 21.58 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.67 | 555.67 | 20.62 | 555.67 | 20.60 |
February | 672.00 | 20.95 | 310.50 | 20.81 | 310.50 | 20.74 |
March | 737.00 | 21.50 | 44.83 | 21.45 | 44.83 | 21.41 |
April | 685.33 | 21.81 | 29.33 | 21.87 | 19.33 | 21.87 |
May | 655.00 | 21.92 | 64.00 | 22.08 | 43.83 | 22.13 |
June | 607.67 | 21.82 | 56.00 | 22.00 | 46.83 | 22.12 |
July | 621.67 | 21.82 | 89.00 | 22.05 | 81.17 | 22.21 |
August | 624.50 | 21.73 | 61.33 | 21.91 | 58.67 | 22.05 |
September | 662.33 | 21.93 | 58.50 | 22.06 | 53.67 | 22.15 |
October | 719.50 | 21.58 | 60.67 | 21.59 | 58.00 | 21.60 |
November | 720.00 | 21.23 | 115.50 | 21.17 | 115.50 | 21.12 |
December | 744.00 | 20.83 | 426.17 | 20.76 | 426.17 | 20.72 |
Annual Sum or Average | 8193.00 | 21.46 | 1871.50 | 21.42 | 1814.17 | 21.37 |
Minimum of Months | 607.67 | 20.67 | 29.33 | 20.62 | 19.33 | 20.60 |
Maximum of Months | 744.00 | 21.93 | 555.67 | 22.08 | 555.67 | 22.21 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.94 | 349.67 | 20.87 | 349.67 | 20.83 |
February | 672.00 | 21.14 | 208.00 | 21.04 | 208.00 | 20.99 |
March | 744.00 | 21.47 | 10.50 | 21.46 | 10.50 | 21.45 |
April | 717.83 | 21.82 | 5.33 | 21.83 | 5.33 | 21.84 |
May | 735.83 | 22.03 | 27.33 | 22.07 | 27.33 | 22.11 |
June | 717.67 | 22.00 | 47.00 | 22.10 | 46.67 | 22.18 |
July | 740.83 | 22.01 | 79.17 | 22.15 | 78.83 | 22.26 |
August | 742.83 | 21.93 | 59.83 | 22.04 | 59.83 | 22.13 |
September | 718.33 | 22.00 | 42.67 | 22.09 | 42.67 | 22.16 |
October | 744.00 | 21.64 | 25.83 | 21.67 | 25.83 | 21.70 |
November | 720.00 | 21.33 | 19.67 | 21.32 | 19.67 | 21.31 |
December | 744.00 | 21.09 | 168.00 | 21.04 | 168.00 | 21.00 |
Annual Sum or Average | 8741.33 | 21.62 | 1043.00 | 21.60 | 1042.33 | 21.59 |
Minimum of Months | 672.00 | 20.94 | 5.33 | 20.87 | 5.33 | 20.83 |
Maximum of Months | 744.00 | 22.03 | 349.67 | 22.15 | 349.67 | 22.26 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.95 | 402.50 | 20.88 | 402.50 | 20.84 |
February | 672.00 | 21.14 | 238.17 | 21.03 | 238.17 | 20.96 |
March | 744.00 | 21.52 | 25.00 | 21.50 | 25.00 | 21.48 |
April | 713.33 | 21.64 | 7.17 | 21.65 | 7.17 | 21.65 |
May | 705.00 | 21.63 | 1.50 | 21.63 | 1.50 | 21.63 |
June | 606.33 | 21.45 | 0.83 | 21.45 | 0.67 | 21.45 |
July | 590.00 | 21.33 | 7.50 | 21.35 | 6.83 | 21.36 |
August | 589.67 | 21.33 | 3.33 | 21.34 | 3.17 | 21.35 |
September | 656.17 | 21.54 | 5.50 | 21.55 | 5.50 | 21.56 |
October | 735.50 | 21.53 | 33.50 | 21.53 | 33.50 | 21.52 |
November | 720.00 | 21.42 | 44.17 | 21.40 | 44.17 | 21.37 |
December | 744.00 | 21.13 | 201.17 | 21.07 | 201.17 | 21.03 |
Annual Sum or Average | 8220.00 | 21.38 | 970.33 | 21.33 | 969.33 | 21.28 |
Minimum of Months | 589.67 | 20.95 | 0.83 | 20.88 | 0.67 | 20.84 |
Maximum of Months | 744.00 | 21.64 | 402.50 | 21.65 | 402.50 | 21.65 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.69 | 546.17 | 20.63 | 546.17 | 20.61 |
February | 672.00 | 20.98 | 309.83 | 20.84 | 309.83 | 20.77 |
March | 744.00 | 21.51 | 46.67 | 21.47 | 46.67 | 21.44 |
April | 712.50 | 21.92 | 20.83 | 21.94 | 18.00 | 21.95 |
May | 665.17 | 22.02 | 65.67 | 22.18 | 44.50 | 22.25 |
June | 566.33 | 21.80 | 68.50 | 22.10 | 48.17 | 22.27 |
July | 574.50 | 21.80 | 96.17 | 22.15 | 82.00 | 22.38 |
August | 584.67 | 21.68 | 66.00 | 21.94 | 59.17 | 22.12 |
September | 665.33 | 21.99 | 63.67 | 22.15 | 54.00 | 22.26 |
October | 742.50 | 21.66 | 55.67 | 21.67 | 55.17 | 21.67 |
November | 720.00 | 21.20 | 111.83 | 21.16 | 111.83 | 21.12 |
December | 744.00 | 20.84 | 404.67 | 20.78 | 404.67 | 20.74 |
Annual Sum or Average | 8135.00 | 21.49 | 1855.67 | 21.46 | 1780.17 | 21.43 |
Minimum of Months | 566.33 | 20.69 | 20.83 | 20.63 | 18.00 | 20.61 |
Maximum of Months | 744.00 | 22.02 | 546.17 | 22.18 | 546.17 | 22.38 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.00 | 251.83 | 21.00 | 251.83 | 21.00 |
February | 672.00 | 21.03 | 176.83 | 21.02 | 176.83 | 21.02 |
March | 744.00 | 21.13 | 27.50 | 21.13 | 27.50 | 21.12 |
April | 720.00 | 21.40 | 0.00 | 21.40 | 0.00 | 21.40 |
May | 744.00 | 21.75 | 0.00 | 21.75 | 0.00 | 21.75 |
June | 720.00 | 22.34 | 0.00 | 22.34 | 0.00 | 22.34 |
July | 744.00 | 22.58 | 0.00 | 22.58 | 0.00 | 22.58 |
August | 744.00 | 22.63 | 0.00 | 22.63 | 0.00 | 22.63 |
September | 720.00 | 22.07 | 0.00 | 22.07 | 0.00 | 22.07 |
October | 744.00 | 21.32 | 0.00 | 21.32 | 0.00 | 21.32 |
November | 720.00 | 21.04 | 9.33 | 21.04 | 9.33 | 21.04 |
December | 744.00 | 21.01 | 111.17 | 21.01 | 111.17 | 21.01 |
Annual Sum or Average | 8760.00 | 21.61 | 576.67 | 21.57 | 576.67 | 21.54 |
Minimum of Months | 672.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
Maximum of Months | 744.00 | 22.63 | 251.83 | 22.63 | 251.83 | 22.63 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.79 | 562.83 | 20.74 | 562.83 | 20.71 |
February | 670.33 | 20.98 | 341.50 | 20.86 | 341.50 | 20.80 |
March | 731.33 | 21.38 | 61.50 | 21.33 | 61.50 | 21.29 |
April | 678.17 | 21.47 | 30.33 | 21.48 | 30.33 | 21.48 |
May | 661.00 | 21.47 | 14.00 | 21.48 | 13.67 | 21.48 |
June | 598.50 | 21.40 | 10.83 | 21.43 | 8.00 | 21.45 |
July | 606.83 | 21.37 | 35.17 | 21.46 | 19.17 | 21.49 |
August | 596.17 | 21.35 | 26.00 | 21.42 | 12.00 | 21.45 |
September | 626.83 | 21.43 | 18.33 | 21.46 | 15.17 | 21.48 |
October | 707.67 | 21.38 | 60.00 | 21.36 | 60.00 | 21.33 |
November | 714.83 | 21.30 | 128.50 | 21.25 | 128.50 | 21.21 |
December | 744.00 | 20.98 | 403.17 | 20.89 | 403.17 | 20.85 |
Annual Sum or Average | 8079.67 | 21.27 | 1692.17 | 21.20 | 1655.83 | 21.14 |
Minimum of Months | 596.17 | 20.79 | 10.83 | 20.74 | 8.00 | 20.71 |
Maximum of Months | 744.00 | 21.47 | 562.83 | 21.48 | 562.83 | 21.49 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.59 | 628.17 | 20.55 | 628.17 | 20.54 |
February | 670.50 | 20.87 | 393.50 | 20.75 | 393.50 | 20.69 |
March | 731.17 | 21.45 | 96.50 | 21.36 | 95.83 | 21.29 |
April | 641.67 | 21.71 | 69.17 | 21.82 | 46.67 | 21.82 |
May | 601.67 | 21.79 | 100.83 | 22.07 | 60.50 | 22.14 |
June | 573.17 | 21.72 | 73.67 | 21.96 | 57.17 | 22.10 |
July | 593.17 | 21.74 | 116.83 | 22.03 | 95.17 | 22.20 |
August | 594.83 | 21.65 | 83.17 | 21.88 | 73.67 | 22.03 |
September | 619.00 | 21.81 | 79.17 | 21.97 | 72.17 | 22.08 |
October | 705.00 | 21.51 | 105.00 | 21.52 | 96.83 | 21.49 |
November | 719.50 | 21.16 | 244.67 | 21.07 | 244.67 | 21.02 |
December | 744.00 | 20.72 | 545.17 | 20.65 | 545.17 | 20.63 |
Annual Sum or Average | 7937.67 | 21.36 | 2535.83 | 21.33 | 2409.50 | 21.27 |
Minimum of Months | 573.17 | 20.59 | 69.17 | 20.55 | 46.67 | 20.54 |
Maximum of Months | 744.00 | 21.81 | 628.17 | 22.07 | 628.17 | 22.20 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.25 | 241.00 | 21.12 | 241.00 | 21.05 |
February | 662.83 | 21.32 | 137.33 | 21.21 | 137.33 | 21.14 |
March | 725.50 | 21.50 | 16.50 | 21.49 | 16.50 | 21.47 |
April | 687.83 | 21.55 | 3.67 | 21.55 | 3.67 | 21.54 |
May | 702.83 | 21.58 | 4.83 | 21.58 | 4.83 | 21.59 |
June | 650.00 | 21.55 | 10.00 | 21.57 | 10.00 | 21.59 |
July | 650.50 | 21.50 | 18.00 | 21.53 | 18.00 | 21.55 |
August | 633.33 | 21.46 | 15.33 | 21.49 | 15.33 | 21.52 |
September | 643.50 | 21.50 | 9.33 | 21.51 | 8.00 | 21.53 |
October | 681.67 | 21.43 | 26.00 | 21.44 | 22.50 | 21.43 |
November | 685.83 | 21.47 | 22.17 | 21.45 | 22.17 | 21.43 |
December | 735.17 | 21.36 | 85.67 | 21.30 | 85.67 | 21.24 |
Annual Sum or Average | 8203.00 | 21.45 | 589.83 | 21.42 | 585.00 | 21.39 |
Minimum of Months | 633.33 | 21.25 | 3.67 | 21.12 | 3.67 | 21.05 |
Maximum of Months | 744.00 | 21.58 | 241.00 | 21.58 | 241.00 | 21.59 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 719.00 | 22.05 | 20.33 | 22.10 | 9.33 | 22.11 |
February | 590.83 | 22.20 | 39.50 | 22.29 | 7.17 | 22.31 |
March | 523.00 | 22.47 | 119.33 | 22.73 | 27.33 | 22.77 |
April | 336.67 | 22.61 | 281.83 | 23.16 | 44.00 | 23.21 |
May | 228.00 | 23.13 | 490.33 | 23.57 | 109.00 | 23.63 |
June | 103.50 | 23.70 | 605.33 | 23.77 | 82.50 | 23.79 |
July | 65.00 | 23.79 | 688.50 | 23.77 | 57.17 | 23.78 |
August | 63.17 | 23.88 | 680.33 | 23.78 | 58.67 | 23.80 |
September | 214.83 | 23.22 | 507.00 | 23.62 | 118.83 | 23.67 |
October | 431.17 | 22.48 | 233.50 | 22.94 | 50.00 | 23.01 |
November | 590.33 | 22.39 | 81.67 | 22.55 | 29.00 | 22.60 |
December | 695.67 | 22.21 | 31.83 | 22.27 | 13.33 | 22.30 |
Annual Sum or Average | 4561.17 | 22.46 | 3779.50 | 23.06 | 606.33 | 23.12 |
Minimum of Months | 63.17 | 22.05 | 20.33 | 22.10 | 7.17 | 22.11 |
Maximum of Months | 719.00 | 23.88 | 688.50 | 23.78 | 118.83 | 23.80 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 680.67 | 22.17 | 33.83 | 22.24 | 6.50 | 22.25 |
February | 504.50 | 22.24 | 70.50 | 22.43 | 5.50 | 22.44 |
March | 401.00 | 22.55 | 186.50 | 22.95 | 22.67 | 22.98 |
April | 212.33 | 22.74 | 392.50 | 23.42 | 33.83 | 23.45 |
May | 104.17 | 23.39 | 595.00 | 23.71 | 63.50 | 23.73 |
June | 15.33 | 23.40 | 683.00 | 23.75 | 8.50 | 23.76 |
July | 8.67 | 23.45 | 728.00 | 23.78 | 5.67 | 23.78 |
August | 0.67 | 23.99 | 734.67 | 23.77 | 0.67 | 23.77 |
September | 90.00 | 23.47 | 609.17 | 23.70 | 61.00 | 23.73 |
October | 272.17 | 22.55 | 341.00 | 23.24 | 41.17 | 23.28 |
November | 472.17 | 22.47 | 132.50 | 22.76 | 26.00 | 22.80 |
December | 623.50 | 22.31 | 47.00 | 22.42 | 6.67 | 22.43 |
Annual Sum or Average | 3385.17 | 22.44 | 4553.67 | 23.20 | 281.67 | 23.23 |
Minimum of Months | 0.67 | 22.17 | 33.83 | 22.24 | 0.67 | 22.25 |
Maximum of Months | 680.67 | 23.99 | 734.67 | 23.78 | 63.50 | 23.78 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 607.83 | 23.23 | 557.33 | 23.56 | 446.17 | 23.68 |
February | 556.83 | 23.33 | 514.83 | 23.61 | 426.33 | 23.71 |
March | 610.00 | 23.53 | 609.17 | 23.68 | 508.67 | 23.77 |
April | 553.33 | 23.77 | 621.00 | 23.76 | 508.67 | 23.83 |
May | 555.83 | 23.93 | 708.00 | 23.75 | 545.00 | 23.82 |
June | 538.50 | 23.97 | 704.83 | 23.77 | 535.33 | 23.83 |
July | 559.33 | 23.98 | 742.83 | 23.76 | 559.33 | 23.83 |
August | 561.00 | 23.98 | 744.00 | 23.77 | 561.00 | 23.83 |
September | 531.83 | 23.98 | 704.83 | 23.75 | 530.67 | 23.82 |
October | 584.67 | 23.72 | 639.50 | 23.73 | 526.67 | 23.81 |
November | 596.00 | 23.47 | 573.83 | 23.66 | 485.33 | 23.75 |
December | 625.50 | 23.31 | 570.67 | 23.59 | 475.17 | 23.71 |
Annual Sum or Average | 6880.67 | 23.67 | 7690.83 | 23.70 | 6108.33 | 23.79 |
Minimum of Months | 531.83 | 23.23 | 514.83 | 23.56 | 426.33 | 23.68 |
Maximum of Months | 625.50 | 23.98 | 744.00 | 23.77 | 561.00 | 23.83 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.00 | 395.50 | 21.00 | 395.50 | 21.00 |
February | 672.00 | 21.03 | 215.33 | 21.02 | 215.33 | 21.02 |
March | 744.00 | 21.12 | 35.83 | 21.11 | 35.83 | 21.11 |
April | 720.00 | 21.41 | 0.00 | 21.41 | 0.00 | 21.41 |
May | 744.00 | 21.86 | 0.00 | 21.86 | 0.00 | 21.86 |
June | 663.67 | 22.54 | 0.00 | 22.54 | 0.00 | 22.54 |
July | 517.00 | 22.62 | 48.50 | 22.72 | 0.00 | 22.72 |
August | 498.83 | 22.76 | 31.17 | 22.83 | 0.00 | 22.83 |
September | 716.33 | 22.04 | 0.00 | 22.04 | 0.00 | 22.04 |
October | 744.00 | 21.27 | 0.00 | 21.27 | 0.00 | 21.27 |
November | 720.00 | 21.03 | 38.17 | 21.03 | 38.17 | 21.03 |
December | 744.00 | 21.00 | 171.17 | 21.00 | 171.17 | 21.00 |
Annual Sum or Average | 8227.83 | 21.58 | 935.67 | 21.54 | 856.00 | 21.50 |
Minimum of Months | 498.83 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
Maximum of Months | 744.00 | 22.76 | 395.50 | 22.83 | 395.50 | 22.83 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.36137 | 28.53182 | -0.3755 | 8.12299 |
February | 672.00000 | 21.17380 | 31.52319 | -0.4128 | 8.75710 |
March | 744.00000 | 21.08264 | 38.35255 | -0.4054 | 8.61589 |
April | 720.00000 | 21.04020 | 48.43041 | -0.3696 | 7.99135 |
May | 744.00000 | 21.08482 | 56.33118 | -1.4972 | 50.76202 |
June | 720.00000 | 21.34986 | 56.47579 | -1.3787 | 44.45910 |
July | 744.00000 | 21.81144 | 57.28280 | -1.2028 | 35.53139 |
August | 744.00000 | 22.36853 | 55.57643 | -1.0106 | 26.76705 |
September | 720.00000 | 22.86516 | 53.66686 | -0.8414 | 20.17148 |
October | 744.00000 | 22.97568 | 46.04037 | 0.14902 | 5.59598 |
November | 720.00000 | 22.98067 | 34.87481 | 0.07695 | 5.33352 |
December | 744.00000 | 22.37801 | 30.59212 | -0.1039 | 5.43835 |
Annual Sum or Average | 8760.00000 | 21.87638 | 44.87674 | -0.6158 | 19.04029 |
Minimum of Months | 672.00000 | 21.04020 | 28.53182 | -1.4972 | 5.33352 |
Maximum of Months | 744.00000 | 22.98067 | 57.28280 | 0.14902 | 50.76202 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.08185 | 28.12470 | -0.5055 | 10.88697 |
February | 672.00000 | 21.17007 | 30.77405 | -0.4308 | 9.71964 |
March | 744.00000 | 21.30178 | 37.18126 | -0.2872 | 7.67255 |
April | 720.00000 | 21.38684 | 46.92116 | -0.1861 | 6.66586 |
May | 744.00000 | 21.51351 | 54.59349 | -1.1889 | 35.53980 |
June | 720.00000 | 22.06987 | 54.07587 | -0.9627 | 25.85380 |
July | 744.00000 | 22.40319 | 55.63768 | -0.8253 | 21.04808 |
August | 744.00000 | 22.75758 | 54.65885 | -0.6944 | 16.65627 |
September | 720.00000 | 22.00697 | 56.07757 | -0.9827 | 27.66964 |
October | 744.00000 | 21.61235 | 48.92193 | -0.1171 | 6.70152 |
November | 720.00000 | 21.30168 | 37.31377 | -0.3005 | 7.95279 |
December | 744.00000 | 21.16497 | 31.70242 | -0.4233 | 9.50689 |
Annual Sum or Average | 8760.00000 | 21.65100 | 44.73631 | -0.5762 | 15.51996 |
Minimum of Months | 672.00000 | 21.08185 | 28.12470 | -1.1889 | 6.66586 |
Maximum of Months | 744.00000 | 22.75758 | 56.07757 | -0.1171 | 35.53980 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.09350 | 29.69628 | -0.4330 | 9.11746 |
February | 672.00000 | 21.19425 | 32.31505 | -0.3793 | 8.36665 |
March | 744.00000 | 21.46856 | 38.46378 | -0.2510 | 6.84904 |
April | 720.00000 | 21.69902 | 47.70991 | -0.1314 | 5.93580 |
May | 744.00000 | 21.95295 | 54.82696 | -1.1021 | 31.27252 |
June | 720.00000 | 22.46818 | 54.36661 | -0.9139 | 23.44188 |
July | 744.00000 | 22.68600 | 56.03822 | -0.8221 | 20.15206 |
August | 744.00000 | 22.87598 | 55.53208 | -0.7546 | 17.65808 |
September | 720.00000 | 22.32368 | 56.47737 | -0.9524 | 24.99130 |
October | 744.00000 | 21.74161 | 50.10879 | -0.1046 | 5.71233 |
November | 720.00000 | 21.38180 | 38.66221 | -0.2734 | 6.94958 |
December | 744.00000 | 21.16903 | 33.24217 | -0.3766 | 8.26111 |
Annual Sum or Average | 8760.00000 | 21.84174 | 45.68893 | -0.5422 | 14.09185 |
Minimum of Months | 672.00000 | 21.09350 | 29.69628 | -1.1021 | 5.71233 |
Maximum of Months | 744.00000 | 22.87598 | 56.47737 | -0.1046 | 31.27252 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.81189 | 24.40748 | 0.29607 | 10.36093 |
February | 672.00000 | 21.84190 | 26.96876 | 0.34105 | 11.09222 |
March | 744.00000 | 21.89662 | 33.32849 | 0.43061 | 12.61100 |
April | 720.00000 | 21.91702 | 42.87166 | 0.51313 | 14.13868 |
May | 744.00000 | 21.95340 | 50.40745 | -0.2234 | 13.17879 |
June | 720.00000 | 21.99475 | 51.18849 | -0.1702 | 12.85764 |
July | 744.00000 | 22.00287 | 53.39596 | -0.1442 | 12.48304 |
August | 744.00000 | 22.01694 | 53.35435 | -0.1320 | 12.56707 |
September | 720.00000 | 21.96193 | 53.02230 | -0.1952 | 12.84158 |
October | 744.00000 | 21.90378 | 45.28670 | 0.51843 | 14.10617 |
November | 720.00000 | 21.87706 | 33.39588 | 0.41422 | 12.15622 |
December | 744.00000 | 21.83177 | 27.88209 | 0.34148 | 10.99402 |
Annual Sum or Average | 8760.00000 | 21.91789 | 41.36825 | 0.16468 | 12.45407 |
Minimum of Months | 672.00000 | 21.81189 | 24.40748 | -0.2234 | 10.36093 |
Maximum of Months | 744.00000 | 22.01694 | 53.39596 | 0.51843 | 14.13868 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.26585 | 33.79908 | -0.3518 | 8.22884 |
February | 672.00000 | 21.49165 | 36.23340 | -0.2521 | 7.34121 |
March | 744.00000 | 21.89968 | 42.11781 | -0.0637 | 6.13755 |
April | 720.00000 | 22.00653 | 51.41696 | 0.03426 | 6.01636 |
May | 744.00000 | 22.21073 | 58.55003 | -0.8787 | 22.48011 |
June | 720.00000 | 22.63287 | 58.43564 | -0.6974 | 16.55464 |
July | 744.00000 | 22.84240 | 60.12671 | -0.5971 | 13.79017 |
August | 744.00000 | 23.10671 | 59.42739 | -0.4912 | 11.14024 |
September | 720.00000 | 22.64726 | 60.04458 | -0.6857 | 16.72049 |
October | 744.00000 | 22.24704 | 53.28280 | 0.11328 | 6.50292 |
November | 720.00000 | 21.82639 | 42.24957 | -0.0863 | 6.23092 |
December | 744.00000 | 21.47340 | 37.14922 | -0.2456 | 7.11726 |
Annual Sum or Average | 8760.00000 | 22.14131 | 49.47118 | -0.3509 | 10.70832 |
Minimum of Months | 672.00000 | 21.26585 | 33.79908 | -0.8787 | 6.01636 |
Maximum of Months | 744.00000 | 23.10671 | 60.12671 | 0.11328 | 22.48011 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.29373 | 32.51903 | -0.3479 | 7.87159 |
February | 672.00000 | 21.46273 | 35.00467 | -0.2788 | 7.18058 |
March | 744.00000 | 21.77470 | 41.07300 | -0.1419 | 6.10631 |
April | 720.00000 | 21.95194 | 50.25941 | -0.0344 | 5.71440 |
May | 744.00000 | 22.18934 | 57.31620 | -0.9748 | 26.00608 |
June | 720.00000 | 22.62487 | 57.12376 | -0.8063 | 19.75624 |
July | 744.00000 | 22.80638 | 58.85319 | -0.7236 | 17.01444 |
August | 744.00000 | 22.97052 | 58.44065 | -0.6626 | 15.05369 |
September | 720.00000 | 22.55636 | 58.95769 | -0.8202 | 20.15376 |
October | 744.00000 | 22.07338 | 52.40953 | 0.01358 | 5.57975 |
November | 720.00000 | 21.74460 | 41.12303 | -0.1498 | 6.02186 |
December | 744.00000 | 21.45178 | 35.91921 | -0.2713 | 6.99564 |
Annual Sum or Average | 8760.00000 | 22.07848 | 48.31919 | -0.4342 | 11.98328 |
Minimum of Months | 672.00000 | 21.29373 | 32.51903 | -0.9748 | 5.57975 |
Maximum of Months | 744.00000 | 22.97052 | 58.95769 | 0.01358 | 26.00608 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.91249 | 43.10353 | -0.5397 | 11.69511 |
February | 672.00000 | 21.08216 | 44.11231 | -0.4519 | 10.22172 |
March | 744.00000 | 21.45504 | 45.61246 | -0.2696 | 7.38179 |
April | 720.00000 | 21.59320 | 52.06004 | -0.1555 | 6.42937 |
May | 744.00000 | 21.67842 | 54.97680 | -1.1865 | 35.84070 |
June | 720.00000 | 21.72573 | 52.67054 | -1.1226 | 32.96632 |
July | 744.00000 | 21.72970 | 54.20914 | -1.0940 | 31.67197 |
August | 744.00000 | 21.73881 | 53.28891 | -1.0838 | 31.24777 |
September | 720.00000 | 21.68182 | 56.06848 | -1.1619 | 34.74209 |
October | 744.00000 | 21.51351 | 56.06909 | -0.1754 | 6.49273 |
November | 720.00000 | 21.37872 | 48.54069 | -0.3084 | 7.82822 |
December | 744.00000 | 21.10054 | 46.05944 | -0.4473 | 9.77708 |
Annual Sum or Average | 8760.00000 | 21.46758 | 50.59791 | -0.6679 | 18.91099 |
Minimum of Months | 672.00000 | 20.91249 | 43.10353 | -1.1865 | 6.42937 |
Maximum of Months | 744.00000 | 21.73881 | 56.06909 | -0.1555 | 35.84070 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.67012 | 43.67495 | -0.6217 | 13.72923 |
February | 672.00000 | 20.95064 | 44.45123 | -0.5101 | 11.54984 |
March | 744.00000 | 21.52065 | 46.11745 | -0.2806 | 7.67501 |
April | 720.00000 | 21.92562 | 52.21664 | -0.0990 | 6.55400 |
May | 744.00000 | 22.15200 | 55.51851 | -1.0508 | 30.27911 |
June | 720.00000 | 22.08539 | 53.21820 | -1.0147 | 28.74989 |
July | 744.00000 | 22.07453 | 55.19114 | -0.9889 | 27.62239 |
August | 744.00000 | 21.99513 | 54.47145 | -1.0146 | 28.55079 |
September | 720.00000 | 22.05558 | 57.59453 | -1.0651 | 30.69287 |
October | 744.00000 | 21.66301 | 57.35476 | -0.1667 | 6.69619 |
November | 720.00000 | 21.23355 | 49.53983 | -0.3712 | 8.68282 |
December | 744.00000 | 20.83325 | 46.90579 | -0.5351 | 11.55614 |
Annual Sum or Average | 8760.00000 | 21.59943 | 51.39169 | -0.6444 | 17.73468 |
Minimum of Months | 672.00000 | 20.67012 | 43.67495 | -1.0651 | 6.55400 |
Maximum of Months | 744.00000 | 22.15200 | 57.59453 | -0.0990 | 30.69287 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.94223 | 40.26618 | -0.5161 | 10.95547 |
February | 672.00000 | 21.13513 | 40.70171 | -0.4438 | 9.65639 |
March | 744.00000 | 21.46834 | 43.05382 | -0.3066 | 7.46272 |
April | 720.00000 | 21.82381 | 49.43004 | -0.1607 | 6.35344 |
May | 744.00000 | 22.04746 | 54.54752 | -1.1467 | 33.84900 |
June | 720.00000 | 22.00722 | 54.17360 | -1.1293 | 33.22885 |
July | 744.00000 | 22.01938 | 56.56274 | -1.1025 | 32.13103 |
August | 744.00000 | 21.93199 | 56.20119 | -1.1372 | 33.53898 |
September | 720.00000 | 22.00697 | 56.62857 | -1.1475 | 33.91486 |
October | 744.00000 | 21.63529 | 53.72973 | -0.1934 | 6.34234 |
November | 720.00000 | 21.33323 | 45.54433 | -0.3420 | 7.90128 |
December | 744.00000 | 21.08687 | 43.23636 | -0.4456 | 9.47949 |
Annual Sum or Average | 8760.00000 | 21.62192 | 49.55745 | -0.6742 | 18.79140 |
Minimum of Months | 672.00000 | 20.94223 | 40.26618 | -1.1475 | 6.34234 |
Maximum of Months | 744.00000 | 22.04746 | 56.62857 | -0.1607 | 33.91486 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.94526 | 43.02143 | -0.5330 | 11.53322 |
February | 672.00000 | 21.13529 | 43.93195 | -0.4372 | 9.97656 |
March | 744.00000 | 21.52294 | 45.29929 | -0.2596 | 7.33031 |
April | 720.00000 | 21.65866 | 51.33527 | -0.1445 | 6.40286 |
May | 744.00000 | 21.71474 | 53.76861 | -1.1741 | 35.33365 |
June | 720.00000 | 21.74615 | 51.94732 | -1.1119 | 32.56972 |
July | 744.00000 | 21.74193 | 53.60466 | -1.0835 | 31.30446 |
August | 744.00000 | 21.74790 | 52.92761 | -1.0794 | 31.13383 |
September | 720.00000 | 21.69761 | 55.31423 | -1.1580 | 34.61455 |
October | 744.00000 | 21.55474 | 55.12973 | -0.1712 | 6.48585 |
November | 720.00000 | 21.41975 | 48.32465 | -0.3011 | 7.70462 |
December | 744.00000 | 21.13228 | 45.93256 | -0.4395 | 9.58863 |
Annual Sum or Average | 8760.00000 | 21.50303 | 50.07655 | -0.6593 | 18.71809 |
Minimum of Months | 672.00000 | 20.94526 | 43.02143 | -1.1741 | 6.40286 |
Maximum of Months | 744.00000 | 21.74790 | 55.31423 | -0.1445 | 35.33365 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.68897 | 43.63345 | -0.6178 | 13.60885 |
February | 672.00000 | 20.97726 | 44.35556 | -0.5001 | 11.26905 |
March | 744.00000 | 21.51147 | 45.99545 | -0.2862 | 7.55144 |
April | 720.00000 | 21.94655 | 51.63147 | -0.0971 | 6.36906 |
May | 744.00000 | 22.20129 | 54.43756 | -1.0343 | 29.75226 |
June | 720.00000 | 22.17789 | 52.52997 | -0.9829 | 28.15801 |
July | 744.00000 | 22.16509 | 54.57605 | -0.9553 | 27.16879 |
August | 744.00000 | 22.04688 | 54.00384 | -0.9983 | 28.39264 |
September | 720.00000 | 22.10911 | 56.65312 | -1.0510 | 30.38857 |
October | 744.00000 | 21.66651 | 56.56750 | -0.1701 | 6.56240 |
November | 720.00000 | 21.20054 | 49.51647 | -0.3788 | 8.61748 |
December | 744.00000 | 20.84381 | 46.84679 | -0.5313 | 11.40475 |
Annual Sum or Average | 8760.00000 | 21.63077 | 50.93087 | -0.6347 | 17.47726 |
Minimum of Months | 672.00000 | 20.68897 | 43.63345 | -1.0510 | 6.36906 |
Maximum of Months | 744.00000 | 22.20129 | 56.65312 | -0.0971 | 30.38857 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.79019 | 44.10814 | -0.6033 | 13.31671 |
February | 672.00000 | 20.98331 | 45.13508 | -0.5003 | 11.44684 |
March | 744.00000 | 21.40974 | 46.37063 | -0.2888 | 7.82291 |
April | 720.00000 | 21.58004 | 52.86040 | -0.1550 | 6.63703 |
May | 744.00000 | 21.67808 | 55.46652 | -1.1710 | 35.34031 |
June | 720.00000 | 21.72660 | 52.90932 | -1.1041 | 32.35429 |
July | 744.00000 | 21.73099 | 54.59718 | -1.0733 | 30.97602 |
August | 744.00000 | 21.74063 | 53.56071 | -1.0635 | 30.56764 |
September | 720.00000 | 21.67514 | 56.92143 | -1.1539 | 34.55522 |
October | 744.00000 | 21.47721 | 57.30752 | -0.1867 | 6.77198 |
November | 720.00000 | 21.31671 | 49.62975 | -0.3388 | 8.45352 |
December | 744.00000 | 20.98101 | 47.32545 | -0.5021 | 11.01939 |
Annual Sum or Average | 8760.00000 | 21.42611 | 51.38145 | -0.6798 | 19.15281 |
Minimum of Months | 672.00000 | 20.79019 | 44.10814 | -1.1710 | 6.63703 |
Maximum of Months | 744.00000 | 21.74063 | 57.30752 | -0.1550 | 35.34031 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.58521 | 44.64724 | -0.6793 | 15.39597 |
February | 672.00000 | 20.88202 | 45.43237 | -0.5540 | 12.77219 |
March | 744.00000 | 21.48576 | 46.80549 | -0.2982 | 8.19158 |
April | 720.00000 | 21.96300 | 52.75015 | -0.0862 | 6.92947 |
May | 744.00000 | 22.18642 | 55.62225 | -1.0215 | 29.58042 |
June | 720.00000 | 22.08276 | 53.32000 | -0.9947 | 28.18309 |
July | 744.00000 | 22.06684 | 55.46945 | -0.9684 | 26.98472 |
August | 744.00000 | 21.98752 | 54.67825 | -0.9955 | 27.92469 |
September | 720.00000 | 22.04957 | 58.21367 | -1.0546 | 30.53008 |
October | 744.00000 | 21.64305 | 58.52538 | -0.1746 | 7.10810 |
November | 720.00000 | 21.15769 | 50.68565 | -0.4066 | 9.48763 |
December | 744.00000 | 20.71660 | 48.19796 | -0.5912 | 13.03310 |
Annual Sum or Average | 8760.00000 | 21.57014 | 52.06443 | -0.6530 | 18.04467 |
Minimum of Months | 672.00000 | 20.58521 | 44.64724 | -1.0546 | 6.92947 |
Maximum of Months | 744.00000 | 22.18642 | 58.52538 | -0.0862 | 30.53008 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.25325 | 43.49280 | -0.4217 | 9.94814 |
February | 672.00000 | 21.34272 | 44.16027 | -0.3617 | 8.92636 |
March | 744.00000 | 21.55031 | 45.11191 | -0.2399 | 7.27431 |
April | 720.00000 | 21.62537 | 51.75194 | -0.1618 | 6.58264 |
May | 744.00000 | 21.67709 | 55.36001 | -1.2157 | 37.30154 |
June | 720.00000 | 21.72149 | 53.80075 | -1.1633 | 34.85503 |
July | 744.00000 | 21.72648 | 55.42239 | -1.1313 | 33.36267 |
August | 744.00000 | 21.74056 | 54.06939 | -1.1120 | 32.57160 |
September | 720.00000 | 21.69042 | 55.63900 | -1.1719 | 35.35083 |
October | 744.00000 | 21.58967 | 54.30330 | -0.1481 | 6.49387 |
November | 720.00000 | 21.56009 | 47.48824 | -0.2334 | 7.25923 |
December | 744.00000 | 21.38597 | 45.82568 | -0.3393 | 8.47468 |
Annual Sum or Average | 8760.00000 | 21.57299 | 50.56996 | -0.6435 | 19.09480 |
Minimum of Months | 672.00000 | 21.25325 | 43.49280 | -1.2157 | 6.49387 |
Maximum of Months | 744.00000 | 21.74056 | 55.63900 | -0.1481 | 37.30154 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.10706 | 33.77650 | -0.1230 | 6.47108 |
February | 672.00000 | 22.37959 | 35.91111 | -0.0215 | 6.47755 |
March | 744.00000 | 22.83257 | 41.44924 | 0.16049 | 6.69815 |
April | 720.00000 | 23.14605 | 49.61271 | 0.31424 | 7.98533 |
May | 744.00000 | 23.42303 | 55.76863 | -0.4554 | 10.25895 |
June | 720.00000 | 23.63305 | 55.64963 | -0.3437 | 8.02539 |
July | 744.00000 | 23.68731 | 57.40420 | -0.2998 | 7.31817 |
August | 744.00000 | 23.68613 | 57.38189 | -0.2990 | 7.28501 |
September | 720.00000 | 23.42988 | 58.12965 | -0.4339 | 9.80862 |
October | 744.00000 | 22.95270 | 52.34611 | 0.27122 | 7.45581 |
November | 720.00000 | 22.62092 | 41.77028 | 0.09536 | 6.37741 |
December | 744.00000 | 22.30714 | 36.93311 | -0.0360 | 6.23263 |
Annual Sum or Average | 8760.00000 | 23.02027 | 48.07460 | -0.0983 | 7.53586 |
Minimum of Months | 672.00000 | 22.10706 | 33.77650 | -0.4554 | 6.23263 |
Maximum of Months | 744.00000 | 23.68731 | 58.12965 | 0.31424 | 10.25895 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.29606 | 33.08434 | -0.0445 | 6.27819 |
February | 672.00000 | 22.59418 | 35.11580 | 0.06321 | 6.60352 |
March | 744.00000 | 23.07489 | 40.48117 | 0.25161 | 7.34168 |
April | 720.00000 | 23.35157 | 48.56394 | 0.39623 | 9.04733 |
May | 744.00000 | 23.57355 | 54.72986 | -0.3580 | 8.35188 |
June | 720.00000 | 23.72389 | 54.81803 | -0.2711 | 6.93233 |
July | 744.00000 | 23.76298 | 56.63466 | -0.2345 | 6.45960 |
August | 744.00000 | 23.75512 | 56.63633 | -0.2368 | 6.47345 |
September | 720.00000 | 23.56563 | 57.13111 | -0.3437 | 8.10700 |
October | 744.00000 | 23.17994 | 51.24021 | 0.35813 | 8.46026 |
November | 720.00000 | 22.87104 | 40.82258 | 0.18811 | 6.86018 |
December | 744.00000 | 22.53680 | 36.12381 | 0.05174 | 6.27458 |
Annual Sum or Average | 8760.00000 | 23.19332 | 47.17850 | -0.0157 | 7.26612 |
Minimum of Months | 672.00000 | 22.29606 | 33.08434 | -0.3580 | 6.27458 |
Maximum of Months | 744.00000 | 23.76298 | 57.13111 | 0.39623 | 9.04733 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.25501 | 32.21862 | 0.79203 | 23.37215 |
February | 672.00000 | 23.29996 | 34.12131 | 0.85148 | 25.34722 |
March | 744.00000 | 23.38483 | 39.11535 | 0.96516 | 29.20676 |
April | 720.00000 | 23.43822 | 47.31564 | 1.06917 | 33.16965 |
May | 744.00000 | 23.50578 | 53.61722 | 0.56842 | 19.96007 |
June | 720.00000 | 23.57262 | 54.05777 | 0.64159 | 21.03676 |
July | 744.00000 | 23.59372 | 55.92643 | 0.67678 | 21.62861 |
August | 744.00000 | 23.60926 | 55.85235 | 0.68219 | 21.50738 |
September | 720.00000 | 23.53393 | 55.88477 | 0.59241 | 19.80530 |
October | 744.00000 | 23.42003 | 49.55572 | 1.05736 | 32.49996 |
November | 720.00000 | 23.34194 | 39.44778 | 0.93010 | 27.93835 |
December | 744.00000 | 23.29093 | 34.95227 | 0.84721 | 25.11245 |
Annual Sum or Average | 8760.00000 | 23.43794 | 46.06836 | 0.80576 | 25.04146 |
Minimum of Months | 672.00000 | 23.25501 | 32.21862 | 0.56842 | 19.80530 |
Maximum of Months | 744.00000 | 23.60926 | 55.92643 | 1.06917 | 33.16965 |
Report: OccupantComfortDataSummaryMonthly
For: STORAGE_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.00006 | 26.67645 | -0.5418 | 11.29383 |
February | 672.00000 | 21.00258 | 29.52760 | -0.5051 | 10.55406 |
March | 744.00000 | 21.02997 | 36.24353 | -0.4255 | 9.01797 |
April | 720.00000 | 21.12166 | 46.06183 | -0.3301 | 7.53138 |
May | 744.00000 | 21.43837 | 53.39448 | -1.3454 | 42.77638 |
June | 720.00000 | 22.20385 | 52.30906 | -1.0799 | 29.91519 |
July | 744.00000 | 22.52636 | 53.94302 | -0.9556 | 24.62495 |
August | 744.00000 | 22.64079 | 53.73265 | -0.9162 | 22.86206 |
September | 720.00000 | 21.89134 | 55.03429 | -1.1720 | 34.14561 |
October | 744.00000 | 21.14180 | 48.76588 | -0.3076 | 7.14917 |
November | 720.00000 | 21.01106 | 36.34323 | -0.4320 | 9.08617 |
December | 744.00000 | 21.00177 | 30.44218 | -0.4952 | 10.30370 |
Annual Sum or Average | 8760.00000 | 21.50428 | 43.61197 | -0.7100 | 18.31434 |
Minimum of Months | 672.00000 | 21.00006 | 26.67645 | -1.3454 | 7.14917 |
Maximum of Months | 744.00000 | 22.64079 | 55.03429 | -0.3076 | 42.77638 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.00149 | 30.09490 | -0.5028 | 10.39604 |
February | 672.00000 | 21.02682 | 32.87246 | -0.4690 | 9.76815 |
March | 744.00000 | 21.13102 | 39.36227 | -0.3851 | 8.35550 |
April | 720.00000 | 21.40032 | 48.60577 | -0.2587 | 6.76079 |
May | 744.00000 | 21.74971 | 55.66476 | -1.2551 | 38.13851 |
June | 720.00000 | 22.33968 | 55.02330 | -1.0507 | 28.49686 |
July | 744.00000 | 22.58099 | 56.66334 | -0.9549 | 24.44917 |
August | 744.00000 | 22.63244 | 56.58414 | -0.9374 | 23.64816 |
September | 720.00000 | 22.07476 | 57.51540 | -1.1274 | 31.97924 |
October | 744.00000 | 21.31806 | 51.50743 | -0.2642 | 6.64345 |
November | 720.00000 | 21.04106 | 39.57862 | -0.4117 | 8.70344 |
December | 744.00000 | 21.00649 | 33.79077 | -0.4686 | 9.73571 |
Annual Sum or Average | 8760.00000 | 21.61220 | 46.50909 | -0.6751 | 17.29885 |
Minimum of Months | 672.00000 | 21.00149 | 30.09490 | -1.2551 | 6.64345 |
Maximum of Months | 744.00000 | 22.63244 | 57.51540 | -0.2587 | 38.13851 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.00018 | 27.82099 | -0.5198 | 10.81069 |
February | 672.00000 | 21.02688 | 30.57903 | -0.4723 | 9.91940 |
March | 744.00000 | 21.11998 | 37.07999 | -0.3695 | 8.20598 |
April | 720.00000 | 21.41030 | 46.29804 | -0.2272 | 6.63313 |
May | 744.00000 | 21.86229 | 52.94191 | -1.1566 | 33.70358 |
June | 720.00000 | 22.60630 | 51.77137 | -0.8941 | 22.53068 |
July | 744.00000 | 22.90105 | 53.25007 | -0.7780 | 18.53777 |
August | 744.00000 | 22.99438 | 53.01666 | -0.7460 | 17.14900 |
September | 720.00000 | 22.05078 | 55.19383 | -1.0742 | 29.93063 |
October | 744.00000 | 21.26799 | 49.28483 | -0.2522 | 6.62834 |
November | 720.00000 | 21.03322 | 37.32477 | -0.4037 | 8.63015 |
December | 744.00000 | 21.00304 | 31.51954 | -0.4746 | 9.89365 |
Annual Sum or Average | 8760.00000 | 21.69421 | 43.90736 | -0.6148 | 15.23912 |
Minimum of Months | 672.00000 | 21.00018 | 27.82099 | -1.1566 | 6.62834 |
Maximum of Months | 744.00000 | 22.99438 | 55.19383 | -0.2272 | 33.70358 |
Report: OccupantComfortDataSummaryMonthly
For: MECH_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.00360 | 26.34316 | -0.5300 | 11.02473 |
February | 672.00000 | 21.01731 | 29.17794 | -0.4931 | 10.30772 |
March | 744.00000 | 21.08609 | 35.78685 | -0.4086 | 8.76390 |
April | 720.00000 | 21.24618 | 45.38886 | -0.3008 | 7.21362 |
May | 744.00000 | 21.61965 | 52.52793 | -1.2892 | 39.95274 |
June | 720.00000 | 22.39801 | 51.42251 | -1.0203 | 27.37669 |
July | 744.00000 | 22.72231 | 53.03555 | -0.8953 | 22.32991 |
August | 744.00000 | 22.83657 | 52.83149 | -0.8560 | 20.67537 |
September | 720.00000 | 22.11196 | 54.02908 | -1.1036 | 31.00311 |
October | 744.00000 | 21.27126 | 48.09604 | -0.2764 | 6.82330 |
November | 720.00000 | 21.05966 | 35.91170 | -0.4154 | 8.81985 |
December | 744.00000 | 21.01053 | 30.09726 | -0.4840 | 10.08222 |
Annual Sum or Average | 8760.00000 | 21.61920 | 42.95839 | -0.6738 | 17.06913 |
Minimum of Months | 672.00000 | 21.00360 | 26.34316 | -1.2892 | 6.82330 |
Maximum of Months | 744.00000 | 22.83657 | 54.02908 | -0.2764 | 39.95274 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.607837E+10 | 65155.99 | 19-JAN-22:53 | 238.07 | 0.276312E+11 | 0.00 | 0.337096E+11 | 1.50 | 4.72 | 01-JAN-00:50 | 0.00 | 0.00 |
February | 0.178338E+11 | 83704.58 | 26-FEB-16:01 | 357.68 | 0.792508E+11 | 0.00 | 0.970846E+11 | 2.45 | 4.72 | 01-FEB-01:00 | 0.00 | 0.00 |
March | 0.456138E+11 | 102073.36 | 30-MAR-18:03 | 652.19 | 0.198516E+12 | 0.00 | 0.244130E+12 | 3.99 | 4.72 | 01-MAR-03:00 | 0.00 | 0.00 |
April | 0.840499E+11 | 108475.08 | 04-APR-15:03 | 697.16 | 0.357688E+12 | 0.00 | 0.441738E+12 | 4.28 | 4.72 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.152049E+12 | 145606.02 | 30-MAY-18:03 | 743.75 | 0.636684E+12 | 0.00 | 0.788733E+12 | 4.27 | 4.72 | 09-MAY-21:20 | 0.00 | 0.00 |
June | 0.224119E+12 | 169826.44 | 28-JUN-18:03 | 720.00 | 0.888006E+12 | 0.00 | 0.111213E+13 | 4.04 | 4.72 | 08-JUN-01:50 | 0.00 | 0.00 |
July | 0.284363E+12 | 186007.46 | 06-JUL-18:03 | 744.00 | 0.110966E+13 | 0.00 | 0.139402E+13 | 3.96 | 4.60 | 28-JUL-21:56 | 0.00 | 0.00 |
August | 0.295816E+12 | 185154.10 | 18-AUG-18:03 | 744.00 | 0.114774E+13 | 0.00 | 0.144355E+13 | 3.92 | 4.45 | 30-AUG-07:00 | 0.00 | 0.00 |
September | 0.194736E+12 | 162964.41 | 07-SEP-18:03 | 720.00 | 0.802120E+12 | 0.00 | 0.996856E+12 | 4.20 | 4.72 | 14-SEP-04:30 | 0.00 | 0.00 |
October | 0.858187E+11 | 164812.15 | 18-OCT-21:53 | 712.27 | 0.368687E+12 | 0.00 | 0.454505E+12 | 4.30 | 4.72 | 03-OCT-03:02 | 0.00 | 0.00 |
November | 0.378537E+11 | 102293.66 | 05-NOV-15:03 | 574.41 | 0.167642E+12 | 0.00 | 0.205495E+12 | 3.66 | 4.72 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.122149E+11 | 77845.48 | 12-DEC-16:01 | 379.47 | 0.552630E+11 | 0.00 | 0.674779E+11 | 2.38 | 4.72 | 01-DEC-10:40 | 0.00 | 0.00 |
Annual Sum or Average | 0.144055E+13 | 7283.00 | 0.583889E+13 | 0.00 | 0.727943E+13 | 3.58 | 0.00 | 0.00 | ||||
Minimum of Months | 0.607837E+10 | 65155.99 | 238.07 | 0.276312E+11 | 0.00 | 0.337096E+11 | 1.50 | 4.45 | 0.00 | 0.00 | ||
Maximum of Months | 0.295816E+12 | 186007.46 | 744.00 | 0.114774E+13 | 0.00 | 0.144355E+13 | 4.30 | 4.72 | 0.00 | 0.00 |
Report: DXReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.697973E+09 | 0.00 | 30.83 | 0.528688E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13371.86 | 19-JAN-16:03 | 12205.06 | 31-JAN-14:00 | 0.00 | 0.00 | 0.00 |
February | 0.197469E+10 | 0.00 | 88.33 | 0.195126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16170.00 | 28-FEB-16:01 | 16170.00 | 28-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.711478E+10 | 0.00 | 245.33 | 0.650656E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22731.69 | 28-MAR-15:01 | 18080.31 | 30-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.142755E+11 | 0.00 | 373.17 | 0.114850E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 29104.22 | 30-APR-15:01 | 18442.88 | 17-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.300411E+11 | 0.00 | 535.17 | 0.200519E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 39092.00 | 30-MAY-21:50 | 19090.69 | 19-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.443953E+11 | 0.00 | 553.17 | 0.279599E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 45326.50 | 29-JUN-08:03 | 20561.09 | 06-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.555144E+11 | 0.00 | 589.00 | 0.314992E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 49419.14 | 26-JUL-08:03 | 21493.27 | 08-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.567570E+11 | 0.00 | 589.00 | 0.326592E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 47944.72 | 24-AUG-08:61 | 20880.06 | 01-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.397304E+11 | 0.00 | 550.67 | 0.243946E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 45948.22 | 17-SEP-08:03 | 19662.34 | 07-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.161233E+11 | 0.00 | 307.17 | 0.100475E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 45040.26 | 18-OCT-21:40 | 18631.16 | 10-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.572898E+10 | 0.00 | 170.67 | 0.416618E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27191.69 | 19-NOV-24:00 | 16656.23 | 05-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 0.118613E+10 | 0.00 | 51.67 | 0.941126E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19688.72 | 13-DEC-11:00 | 14720.89 | 12-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.273540E+12 | 0.00 | 4084.17 | 0.172191E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.697973E+09 | 0.00 | 30.83 | 0.528688E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13371.86 | 12205.06 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.567570E+11 | 0.00 | 589.00 | 0.326592E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 49419.14 | 21493.27 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.197359E+11 | 0.00 | 85.17 | 0.145909E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 194711.61 | 19-JAN-22:00 | 128201.76 | 31-JAN-15:00 | 0.00 | 0.00 | 0.00 |
February | 0.585295E+11 | 0.00 | 240.17 | 0.504319E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 178171.02 | 26-FEB-15:50 | 178171.02 | 26-FEB-15:50 | 0.00 | 0.00 | 0.00 |
March | 0.140026E+12 | 0.00 | 436.67 | 0.123605E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 246313.88 | 31-MAR-10:50 | 208823.15 | 30-MAR-19:50 | 0.00 | 0.00 | 0.00 |
April | 0.265050E+12 | 0.00 | 600.67 | 0.210801E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 296796.21 | 21-APR-18:06 | 234428.95 | 13-APR-16:20 | 0.00 | 0.00 | 0.00 |
May | 0.491269E+12 | 0.00 | 720.83 | 0.322746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 419610.41 | 30-MAY-21:20 | 263871.15 | 15-MAY-18:07 | 0.00 | 0.00 | 0.00 |
June | 0.688613E+12 | 0.00 | 714.67 | 0.420656E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 465802.48 | 26-JUN-21:00 | 262199.27 | 10-JUN-17:15 | 0.00 | 0.00 | 0.00 |
July | 0.876468E+12 | 0.00 | 744.00 | 0.469958E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 487260.69 | 18-JUL-19:04 | 257838.71 | 07-JUL-18:20 | 0.00 | 0.00 | 0.00 |
August | 0.903697E+12 | 0.00 | 744.00 | 0.489545E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 486145.79 | 23-AUG-23:00 | 256144.63 | 18-AUG-20:10 | 0.00 | 0.00 | 0.00 |
September | 0.633046E+12 | 0.00 | 718.50 | 0.367710E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 468173.39 | 27-SEP-18:09 | 237792.48 | 14-SEP-14:03 | 0.00 | 0.00 | 0.00 |
October | 0.277225E+12 | 0.00 | 540.50 | 0.177561E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 504704.10 | 18-OCT-21:00 | 203609.72 | 11-OCT-16:10 | 0.00 | 0.00 | 0.00 |
November | 0.121794E+12 | 0.00 | 367.33 | 0.898072E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 269829.35 | 27-NOV-19:20 | 160287.15 | 05-NOV-16:00 | 0.00 | 0.00 | 0.00 |
December | 0.360329E+11 | 0.00 | 166.00 | 0.265778E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 221678.23 | 13-DEC-11:40 | 152545.69 | 12-DEC-15:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.451149E+13 | 0.00 | 6078.50 | 0.276399E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.197359E+11 | 0.00 | 85.17 | 0.145909E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 178171.02 | 128201.76 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.903697E+12 | 0.00 | 744.00 | 0.489545E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 504704.10 | 263871.15 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.133512E+09 | 0.00 | 37.97 | 0.109449E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14688.14 | 28-JAN-16:01 | 14688.14 | 28-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.588845E+09 | 0.00 | 117.64 | 0.469659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15089.28 | 19-FEB-16:02 | 14690.93 | 28-FEB-19:01 | 0.00 | 0.00 | 0.00 |
March | 0.224737E+10 | 0.00 | 354.22 | 0.140855E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15261.47 | 28-MAR-15:01 | 14687.11 | 06-MAR-16:01 | 0.00 | 0.00 | 0.00 |
April | 0.407613E+10 | 0.00 | 531.27 | 0.211202E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15748.58 | 03-APR-15:01 | 14685.75 | 25-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.630776E+10 | 0.00 | 662.02 | 0.308681E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15892.85 | 27-MAY-08:62 | 14690.02 | 09-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.868662E+10 | 0.00 | 678.55 | 0.473743E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16414.05 | 29-JUN-08:61 | 13171.71 | 26-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.100227E+11 | 0.00 | 701.65 | 0.566264E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17031.30 | 30-JUL-08:62 | 13012.19 | 27-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.105640E+11 | 0.00 | 710.81 | 0.601849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16424.20 | 29-AUG-08:61 | 13167.36 | 19-AUG-08:62 | 0.00 | 0.00 | 0.00 |
September | 0.686065E+10 | 0.00 | 642.12 | 0.335577E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16600.67 | 17-SEP-08:61 | 13078.70 | 01-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.327093E+10 | 0.00 | 454.98 | 0.152150E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16357.99 | 01-OCT-15:01 | 14401.98 | 31-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.109890E+10 | 0.00 | 241.72 | 0.580470E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16078.54 | 04-NOV-15:01 | 14690.13 | 07-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.302901E+09 | 0.00 | 80.80 | 0.186149E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15153.29 | 13-DEC-16:01 | 14690.60 | 08-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.541603E+11 | 0.00 | 5213.75 | 0.292489E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.133512E+09 | 0.00 | 37.97 | 0.109449E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14688.14 | 13012.19 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.105640E+11 | 0.00 | 710.81 | 0.601849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17031.30 | 14690.93 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 10667398.00 | 0.00 | 3.76 | 7400876.05 | 0.00 | 0.00 | 0.00 | 0.00 | 13796.72 | 20-JAN-16:01 | 13573.81 | 29-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.113244E+09 | 0.00 | 40.64 | 74135124.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14774.53 | 19-FEB-16:02 | 14532.13 | 27-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.955902E+09 | 0.00 | 184.67 | 0.502937E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15275.11 | 28-MAR-15:01 | 14531.27 | 06-MAR-16:01 | 0.00 | 0.00 | 0.00 |
April | 0.259275E+10 | 0.00 | 378.59 | 0.122822E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15761.39 | 02-APR-15:01 | 15187.76 | 26-APR-18:41 | 0.00 | 0.00 | 0.00 |
May | 0.494200E+10 | 0.00 | 489.75 | 0.246840E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16252.70 | 07-MAY-17:42 | 15155.37 | 09-MAY-20:41 | 0.00 | 0.00 | 0.00 |
June | 0.788125E+10 | 0.00 | 562.13 | 0.454366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17405.05 | 26-JUN-08:21 | 13104.75 | 16-JUN-21:51 | 0.00 | 0.00 | 0.00 |
July | 0.909017E+10 | 0.00 | 587.78 | 0.542488E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17573.17 | 23-JUL-08:51 | 13044.53 | 02-JUL-21:51 | 0.00 | 0.00 | 0.00 |
August | 0.939230E+10 | 0.00 | 619.09 | 0.545053E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18385.58 | 20-AUG-07:52 | 13648.40 | 08-AUG-17:52 | 0.00 | 0.00 | 0.00 |
September | 0.514298E+10 | 0.00 | 481.86 | 0.249239E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16711.36 | 17-SEP-08:52 | 13826.47 | 18-SEP-16:01 | 0.00 | 0.00 | 0.00 |
October | 0.145608E+10 | 0.00 | 254.86 | 0.580994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16545.82 | 18-OCT-21:52 | 13843.81 | 31-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.220697E+09 | 0.00 | 80.97 | 0.102641E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15942.67 | 04-NOV-15:01 | 14534.03 | 07-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 39185438.82 | 0.00 | 13.53 | 23415560.29 | 0.00 | 0.00 | 0.00 | 0.00 | 15169.61 | 13-DEC-16:01 | 13284.84 | 09-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.418372E+11 | 0.00 | 3697.62 | 0.228996E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 10667398.00 | 0.00 | 3.76 | 7400876.05 | 0.00 | 0.00 | 0.00 | 0.00 | 13796.72 | 13044.53 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.939230E+10 | 0.00 | 619.09 | 0.545053E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18385.58 | 15187.76 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.138207E+10 | 0.00 | 48.21 | 0.113588E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22971.64 | 29-JAN-13:30 | 22971.64 | 29-JAN-13:30 | 0.00 | 0.00 | 0.00 |
February | 0.594838E+10 | 0.00 | 140.24 | 0.550006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30939.90 | 26-FEB-14:25 | 30939.90 | 26-FEB-14:25 | 0.00 | 0.00 | 0.00 |
March | 0.180425E+11 | 0.00 | 475.52 | 0.110760E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 31707.98 | 30-MAR-13:30 | 28751.47 | 13-MAR-16:10 | 0.00 | 0.00 | 0.00 |
April | 0.218781E+11 | 0.00 | 568.96 | 0.864923E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28127.60 | 15-APR-13:40 | 21704.50 | 10-APR-15:03 | 0.00 | 0.00 | 0.00 |
May | 0.292406E+11 | 0.00 | 694.62 | 0.101412E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 24574.51 | 19-MAY-19:10 | 13062.04 | 19-MAY-19:10 | 0.00 | 0.00 | 0.00 |
June | 0.386492E+11 | 0.00 | 707.76 | 0.153059E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 28589.99 | 24-JUN-17:20 | 16662.02 | 24-JUN-19:10 | 0.00 | 0.00 | 0.00 |
July | 0.457626E+11 | 0.00 | 741.88 | 0.192990E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 31961.66 | 08-JUL-17:25 | 20552.61 | 08-JUL-17:25 | 0.00 | 0.00 | 0.00 |
August | 0.526712E+11 | 0.00 | 742.97 | 0.243638E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 35030.87 | 19-AUG-15:02 | 23976.31 | 19-AUG-13:40 | 0.00 | 0.00 | 0.00 |
September | 0.398279E+11 | 0.00 | 696.38 | 0.176051E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 39128.80 | 24-SEP-12:30 | 31766.71 | 24-SEP-12:40 | 0.00 | 0.00 | 0.00 |
October | 0.285450E+11 | 0.00 | 562.93 | 0.133756E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 42085.26 | 10-OCT-13:30 | 36477.40 | 10-OCT-13:30 | 0.00 | 0.00 | 0.00 |
November | 0.171645E+11 | 0.00 | 438.08 | 0.119831E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 35203.66 | 06-NOV-13:40 | 34921.94 | 15-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 0.754238E+10 | 0.00 | 206.43 | 0.579348E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33561.16 | 12-DEC-12:30 | 33540.97 | 10-DEC-14:25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.306654E+12 | 0.00 | 6023.99 | 0.144228E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.138207E+10 | 0.00 | 48.21 | 0.113588E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22971.64 | 13062.04 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.526712E+11 | 0.00 | 742.97 | 0.243638E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 42085.26 | 36477.40 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.163641E+10 | 0.00 | 62.87 | 0.808420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 93848.12 | 19-JAN-22:53 | 77196.19 | 01-JAN-09:02 | 0.00 | 0.00 | 0.00 |
February | 0.520130E+10 | 0.00 | 158.71 | 0.314354E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 94034.66 | 18-FEB-09:02 | 92996.38 | 28-FEB-22:52 | 0.00 | 0.00 | 0.00 |
March | 0.148908E+11 | 0.00 | 334.05 | 0.907437E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 93569.30 | 28-MAR-21:52 | 93453.40 | 31-MAR-20:12 | 0.00 | 0.00 | 0.00 |
April | 0.278714E+11 | 0.00 | 384.68 | 0.157248E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 102494.66 | 30-APR-21:52 | 92402.64 | 09-APR-20:11 | 0.00 | 0.00 | 0.00 |
May | 0.436160E+11 | 0.00 | 441.91 | 0.250817E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 105793.66 | 07-MAY-17:42 | 97403.34 | 09-MAY-20:41 | 0.00 | 0.00 | 0.00 |
June | 0.593947E+11 | 0.00 | 518.76 | 0.364971E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 111765.30 | 26-JUN-08:21 | 85236.03 | 29-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.666538E+11 | 0.00 | 548.21 | 0.408607E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 113947.84 | 23-JUL-08:51 | 85035.54 | 09-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.664347E+11 | 0.00 | 570.78 | 0.395717E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 121730.15 | 20-AUG-07:52 | 88228.60 | 08-AUG-17:52 | 0.00 | 0.00 | 0.00 |
September | 0.437892E+11 | 0.00 | 439.80 | 0.242126E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 109201.95 | 17-SEP-08:52 | 84017.32 | 11-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.212640E+11 | 0.00 | 384.00 | 0.985482E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 111741.06 | 18-OCT-21:52 | 93843.81 | 11-OCT-21:52 | 0.00 | 0.00 | 0.00 |
November | 0.968461E+10 | 0.00 | 258.61 | 0.541972E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 100647.76 | 05-NOV-21:52 | 89817.40 | 06-NOV-19:12 | 0.00 | 0.00 | 0.00 |
December | 0.335314E+10 | 0.00 | 126.49 | 0.174684E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 97710.60 | 13-DEC-21:02 | 77402.48 | 31-DEC-09:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.363790E+12 | 0.00 | 4228.87 | 0.211996E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.163641E+10 | 0.00 | 62.87 | 0.808420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 93569.30 | 77196.19 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.666538E+11 | 0.00 | 570.78 | 0.408607E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 121730.15 | 97403.34 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.119518E+09 | 0.00 | 34.39 | 88569479.38 | 0.00 | 0.00 | 0.00 | 0.00 | 13305.47 | 29-JAN-16:01 | 13305.47 | 29-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.665348E+09 | 0.00 | 131.11 | 0.510437E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13483.36 | 19-FEB-16:02 | 13326.30 | 28-FEB-19:01 | 0.00 | 0.00 | 0.00 |
March | 0.197275E+10 | 0.00 | 382.45 | 0.110322E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13702.18 | 28-MAR-15:01 | 13323.78 | 06-MAR-16:01 | 0.00 | 0.00 | 0.00 |
April | 0.394105E+10 | 0.00 | 549.28 | 0.196839E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14262.48 | 02-APR-15:01 | 13319.41 | 09-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.650623E+10 | 0.00 | 684.68 | 0.330127E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14478.91 | 27-MAY-08:62 | 13323.65 | 09-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.891940E+10 | 0.00 | 697.69 | 0.496338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14685.91 | 23-JUN-08:61 | 11980.19 | 02-JUN-08:61 | 0.00 | 0.00 | 0.00 |
July | 0.103854E+11 | 0.00 | 715.60 | 0.598159E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15430.62 | 30-JUL-08:62 | 11970.20 | 03-JUL-08:61 | 0.00 | 0.00 | 0.00 |
August | 0.106498E+11 | 0.00 | 722.08 | 0.616489E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14756.14 | 24-AUG-08:61 | 11968.12 | 01-AUG-08:61 | 0.00 | 0.00 | 0.00 |
September | 0.692479E+10 | 0.00 | 652.41 | 0.350780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15076.76 | 17-SEP-08:61 | 11917.79 | 15-SEP-08:62 | 0.00 | 0.00 | 0.00 |
October | 0.322326E+10 | 0.00 | 469.28 | 0.149604E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15005.18 | 01-OCT-15:01 | 11947.60 | 17-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.100151E+10 | 0.00 | 250.35 | 0.482538E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14511.39 | 04-NOV-15:01 | 13326.24 | 07-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.276478E+09 | 0.00 | 81.32 | 0.134963E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13606.55 | 13-DEC-16:01 | 12897.62 | 09-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.545855E+11 | 0.00 | 5370.63 | 0.297031E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.119518E+09 | 0.00 | 34.39 | 88569479.38 | 0.00 | 0.00 | 0.00 | 0.00 | 13305.47 | 11917.79 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.106498E+11 | 0.00 | 722.08 | 0.616489E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15430.62 | 13326.30 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 12196151.49 | 0.00 | 3.62 | 6518849.74 | 0.00 | 0.00 | 0.00 | 0.00 | 10237.59 | 31-JAN-16:01 | 8917.34 | 31-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.191958E+09 | 0.00 | 48.96 | 0.112106E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13215.63 | 27-FEB-16:01 | 13215.63 | 27-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.873036E+09 | 0.00 | 193.85 | 0.404899E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13740.30 | 28-MAR-15:01 | 12915.52 | 10-MAR-16:01 | 0.00 | 0.00 | 0.00 |
April | 0.258082E+10 | 0.00 | 396.29 | 0.122437E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14415.27 | 02-APR-15:01 | 12725.41 | 09-APR-20:11 | 0.00 | 0.00 | 0.00 |
May | 0.511893E+10 | 0.00 | 510.07 | 0.265511E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15209.63 | 30-MAY-08:51 | 13265.89 | 09-MAY-20:41 | 0.00 | 0.00 | 0.00 |
June | 0.799767E+10 | 0.00 | 576.06 | 0.463837E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16561.82 | 29-JUN-08:51 | 13213.55 | 04-JUN-08:51 | 0.00 | 0.00 | 0.00 |
July | 0.931461E+10 | 0.00 | 598.91 | 0.557964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16430.48 | 23-JUL-08:51 | 12404.24 | 07-JUL-06:51 | 0.00 | 0.00 | 0.00 |
August | 0.943107E+10 | 0.00 | 627.10 | 0.551833E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16790.47 | 20-AUG-07:52 | 12647.15 | 08-AUG-17:52 | 0.00 | 0.00 | 0.00 |
September | 0.516246E+10 | 0.00 | 498.94 | 0.256825E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16168.89 | 06-SEP-08:31 | 12777.40 | 15-SEP-08:51 | 0.00 | 0.00 | 0.00 |
October | 0.153988E+10 | 0.00 | 267.74 | 0.634929E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15087.58 | 18-OCT-21:52 | 11726.04 | 14-OCT-08:61 | 0.00 | 0.00 | 0.00 |
November | 0.228896E+09 | 0.00 | 75.29 | 89106571.73 | 0.00 | 0.00 | 0.00 | 0.00 | 14487.68 | 05-NOV-15:01 | 11540.35 | 07-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 27363073.84 | 0.00 | 11.65 | 10231113.74 | 0.00 | 0.00 | 0.00 | 0.00 | 13667.21 | 13-DEC-16:01 | 9412.70 | 12-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.424789E+11 | 0.00 | 3808.47 | 0.234419E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 12196151.49 | 0.00 | 3.62 | 6518849.74 | 0.00 | 0.00 | 0.00 | 0.00 | 10237.59 | 8917.34 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.943107E+10 | 0.00 | 627.10 | 0.557964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16790.47 | 13265.89 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 23383430.84 | 0.00 | 21.47 | 20377442.74 | 0.00 | 0.00 | 0.00 | 0.00 | 3858.53 | 28-JAN-16:01 | 3858.53 | 28-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.140560E+09 | 0.00 | 95.39 | 0.116437E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4053.53 | 19-FEB-16:02 | 3858.74 | 28-FEB-19:01 | 0.00 | 0.00 | 0.00 |
March | 0.573911E+09 | 0.00 | 315.35 | 0.371808E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3987.58 | 28-MAR-15:01 | 3858.25 | 06-MAR-16:01 | 0.00 | 0.00 | 0.00 |
April | 0.108330E+10 | 0.00 | 499.38 | 0.598896E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4210.40 | 03-APR-15:01 | 3857.43 | 25-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.171103E+10 | 0.00 | 657.09 | 0.886489E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4313.61 | 27-MAY-08:62 | 3858.25 | 09-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.234056E+10 | 0.00 | 679.23 | 0.132294E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4488.93 | 29-JUN-08:61 | 3375.00 | 26-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.269922E+10 | 0.00 | 701.64 | 0.157852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4704.90 | 30-JUL-08:62 | 3364.08 | 27-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.283615E+10 | 0.00 | 710.45 | 0.166073E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4521.94 | 29-AUG-08:61 | 3374.15 | 31-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.178849E+10 | 0.00 | 625.79 | 0.908350E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4571.01 | 17-SEP-08:61 | 3454.04 | 09-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.837502E+09 | 0.00 | 407.52 | 0.415739E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4426.20 | 18-OCT-08:62 | 3806.14 | 31-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.261898E+09 | 0.00 | 197.12 | 0.145736E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4321.41 | 04-NOV-15:01 | 3859.10 | 07-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 63486829.12 | 0.00 | 61.09 | 39011053.38 | 0.00 | 0.00 | 0.00 | 0.00 | 4045.91 | 13-DEC-16:01 | 3858.77 | 09-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.143595E+11 | 0.00 | 4971.52 | 0.806503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 23383430.84 | 0.00 | 21.47 | 20377442.74 | 0.00 | 0.00 | 0.00 | 0.00 | 3858.53 | 3364.08 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.283615E+10 | 0.00 | 710.45 | 0.166073E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4704.90 | 3859.10 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 2052678.79 | 0.00 | 1.21 | 1161517.71 | 0.00 | 0.00 | 0.00 | 0.00 | 3421.62 | 20-JAN-16:01 | 2458.12 | 20-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 25060049.77 | 0.00 | 24.36 | 17301760.47 | 0.00 | 0.00 | 0.00 | 0.00 | 3961.47 | 19-FEB-16:02 | 3813.97 | 27-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.243185E+09 | 0.00 | 165.13 | 0.131970E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4009.39 | 28-MAR-15:01 | 3822.77 | 12-MAR-19:01 | 0.00 | 0.00 | 0.00 |
April | 0.702761E+09 | 0.00 | 363.76 | 0.351593E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4174.55 | 30-APR-21:52 | 4044.27 | 26-APR-18:41 | 0.00 | 0.00 | 0.00 |
May | 0.138988E+10 | 0.00 | 497.25 | 0.735528E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4334.59 | 07-MAY-17:42 | 4098.03 | 09-MAY-20:41 | 0.00 | 0.00 | 0.00 |
June | 0.216724E+10 | 0.00 | 566.55 | 0.130244E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4767.09 | 26-JUN-08:21 | 3403.23 | 03-JUN-21:51 | 0.00 | 0.00 | 0.00 |
July | 0.249282E+10 | 0.00 | 590.39 | 0.153662E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4749.42 | 23-JUL-08:51 | 3446.21 | 02-JUL-21:51 | 0.00 | 0.00 | 0.00 |
August | 0.255939E+10 | 0.00 | 620.53 | 0.153018E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5063.60 | 20-AUG-07:52 | 3616.37 | 08-AUG-17:52 | 0.00 | 0.00 | 0.00 |
September | 0.137412E+10 | 0.00 | 481.67 | 0.689078E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4566.73 | 17-SEP-08:52 | 3596.21 | 18-SEP-16:01 | 0.00 | 0.00 | 0.00 |
October | 0.375103E+09 | 0.00 | 221.03 | 0.158154E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4547.43 | 18-OCT-21:52 | 3647.85 | 31-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 46333603.18 | 0.00 | 50.27 | 22885405.53 | 0.00 | 0.00 | 0.00 | 0.00 | 4280.52 | 04-NOV-15:01 | 3814.37 | 07-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 5558584.44 | 0.00 | 7.23 | 3102358.32 | 0.00 | 0.00 | 0.00 | 0.00 | 4026.65 | 13-DEC-16:01 | 3116.87 | 11-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.113835E+11 | 0.00 | 3589.39 | 0.648002E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2052678.79 | 0.00 | 1.21 | 1161517.71 | 0.00 | 0.00 | 0.00 | 0.00 | 3421.62 | 2458.12 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.255939E+10 | 0.00 | 620.53 | 0.153662E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5063.60 | 4098.03 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.133307E+10 | 0.00 | 154.11 | 0.105700E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17529.30 | 26-JAN-16:01 | 17529.30 | 26-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.206846E+10 | 0.00 | 219.17 | 0.164299E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18276.45 | 19-FEB-16:02 | 17529.60 | 24-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.459725E+10 | 0.00 | 471.63 | 0.301428E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17646.20 | 31-MAR-15:01 | 17528.88 | 20-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.616321E+10 | 0.00 | 552.61 | 0.331446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18781.24 | 03-APR-15:01 | 17520.53 | 09-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.856651E+10 | 0.00 | 662.41 | 0.427452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19202.83 | 27-MAY-08:62 | 17527.76 | 10-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.112303E+11 | 0.00 | 673.78 | 0.605200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21239.31 | 29-JUN-08:61 | 15574.34 | 30-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.132659E+11 | 0.00 | 698.01 | 0.740035E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21624.52 | 27-JUL-08:61 | 15672.70 | 27-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.147318E+11 | 0.00 | 708.51 | 0.877089E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21035.67 | 29-AUG-08:61 | 15624.66 | 23-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.107491E+11 | 0.00 | 645.63 | 0.595725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20796.20 | 17-SEP-08:61 | 15579.78 | 17-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.718414E+10 | 0.00 | 555.79 | 0.416609E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20288.80 | 18-OCT-08:62 | 17527.39 | 12-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.430063E+10 | 0.00 | 430.86 | 0.274707E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19156.85 | 04-NOV-15:01 | 17529.45 | 15-NOV-19:01 | 0.00 | 0.00 | 0.00 |
December | 0.237754E+10 | 0.00 | 253.85 | 0.172808E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18143.71 | 13-DEC-16:01 | 17528.59 | 05-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.865679E+11 | 0.00 | 6026.37 | 0.501250E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.133307E+10 | 0.00 | 154.11 | 0.105700E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17529.30 | 15574.34 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.147318E+11 | 0.00 | 708.51 | 0.877089E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21624.52 | 17529.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 527.26 | 366.27 | 160.99 | 606.49 | 579.17 | 0.00 | 0.00 | 0.00 |
February | 491.15 | 327.66 | 163.48 | 617.78 | 477.34 | 0.00 | 0.00 | 0.00 |
March | 449.12 | 235.68 | 213.44 | 636.60 | 296.09 | 0.00 | 0.00 | 0.00 |
April | 338.00 | 112.77 | 225.23 | 546.28 | 227.82 | 0.00 | 0.00 | 0.00 |
May | 271.69 | 33.25 | 238.45 | 481.92 | 130.53 | 0.00 | 0.00 | 0.00 |
June | 249.47 | 13.93 | 235.54 | 519.33 | 71.43 | 0.00 | 0.00 | 0.00 |
July | 250.25 | 16.88 | 233.37 | 541.58 | 41.48 | 0.00 | 0.00 | 0.00 |
August | 301.54 | 56.67 | 244.87 | 642.06 | 31.90 | 0.00 | 0.00 | 0.00 |
September | 340.43 | 132.46 | 207.97 | 621.54 | 101.24 | 0.00 | 0.00 | 0.00 |
October | 478.03 | 308.97 | 169.06 | 735.12 | 261.63 | 0.00 | 0.00 | 0.00 |
November | 522.27 | 348.52 | 173.76 | 717.26 | 365.34 | 0.00 | 0.00 | 0.00 |
December | 523.54 | 368.30 | 155.25 | 648.06 | 476.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 394.80 | 192.80 | 202.00 | 609.52 | 253.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 249.47 | 13.93 | 155.25 | 481.92 | 31.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 527.26 | 368.30 | 244.87 | 735.12 | 579.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1484.72 | 1031.40 | 453.32 | 1688.92 | 1664.87 | 0.00 | 0.00 | 0.00 |
February | 1383.03 | 922.68 | 460.35 | 1720.50 | 1390.96 | 0.00 | 0.00 | 0.00 |
March | 1264.70 | 663.66 | 601.04 | 1770.18 | 895.29 | 0.00 | 0.00 | 0.00 |
April | 951.78 | 317.55 | 634.23 | 1517.27 | 697.14 | 0.00 | 0.00 | 0.00 |
May | 765.07 | 93.63 | 671.45 | 1333.43 | 423.16 | 0.00 | 0.00 | 0.00 |
June | 702.49 | 39.22 | 663.27 | 1444.61 | 243.45 | 0.00 | 0.00 | 0.00 |
July | 704.68 | 47.53 | 657.15 | 1514.00 | 151.25 | 0.00 | 0.00 | 0.00 |
August | 849.11 | 159.58 | 689.52 | 1803.34 | 121.40 | 0.00 | 0.00 | 0.00 |
September | 958.64 | 373.00 | 585.64 | 1730.91 | 339.24 | 0.00 | 0.00 | 0.00 |
October | 1346.11 | 870.05 | 476.06 | 2049.95 | 802.10 | 0.00 | 0.00 | 0.00 |
November | 1470.69 | 981.40 | 489.29 | 1998.61 | 1088.19 | 0.00 | 0.00 | 0.00 |
December | 1474.27 | 1037.10 | 437.17 | 1804.59 | 1387.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1111.73 | 542.91 | 568.82 | 1698.12 | 763.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 702.49 | 39.22 | 437.17 | 1333.43 | 121.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1484.72 | 1037.10 | 689.52 | 2049.95 | 1664.87 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1928.74 | 1339.84 | 588.89 | 2237.05 | 2233.88 | 0.00 | 0.00 | 0.00 |
February | 1796.64 | 1198.62 | 598.02 | 2287.41 | 1857.31 | 0.00 | 0.00 | 0.00 |
March | 1642.92 | 862.13 | 780.79 | 2366.96 | 1177.77 | 0.00 | 0.00 | 0.00 |
April | 1236.41 | 412.51 | 823.90 | 2031.50 | 920.43 | 0.00 | 0.00 | 0.00 |
May | 993.87 | 121.63 | 872.25 | 1786.79 | 554.04 | 0.00 | 0.00 | 0.00 |
June | 912.57 | 50.95 | 861.62 | 1935.33 | 313.95 | 0.00 | 0.00 | 0.00 |
July | 915.42 | 61.75 | 853.67 | 2032.17 | 191.25 | 0.00 | 0.00 | 0.00 |
August | 1103.04 | 207.31 | 895.73 | 2426.89 | 144.81 | 0.00 | 0.00 | 0.00 |
September | 1245.33 | 484.54 | 760.78 | 2317.14 | 436.49 | 0.00 | 0.00 | 0.00 |
October | 1748.68 | 1130.24 | 618.43 | 2742.39 | 1050.93 | 0.00 | 0.00 | 0.00 |
November | 1910.51 | 1274.89 | 635.62 | 2663.54 | 1442.05 | 0.00 | 0.00 | 0.00 |
December | 1915.16 | 1347.25 | 567.91 | 2397.45 | 1855.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1444.20 | 705.27 | 738.93 | 2268.91 | 1010.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 912.57 | 50.95 | 567.91 | 1786.79 | 144.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1928.74 | 1347.25 | 895.73 | 2742.39 | 2233.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 104.25 | 72.42 | 31.83 | 117.16 | 126.59 | 0.00 | 0.00 | 0.00 |
February | 97.11 | 64.78 | 32.32 | 119.46 | 104.14 | 0.00 | 0.00 | 0.00 |
March | 88.80 | 46.60 | 42.20 | 122.42 | 64.13 | 0.00 | 0.00 | 0.00 |
April | 66.83 | 22.30 | 44.53 | 105.28 | 49.13 | 0.00 | 0.00 | 0.00 |
May | 53.72 | 6.57 | 47.15 | 93.49 | 27.00 | 0.00 | 0.00 | 0.00 |
June | 49.32 | 2.75 | 46.57 | 106.12 | 12.47 | 0.00 | 0.00 | 0.00 |
July | 49.48 | 3.34 | 46.14 | 113.73 | 5.87 | 0.00 | 0.00 | 0.00 |
August | 59.62 | 11.20 | 48.41 | 136.24 | 2.92 | 0.00 | 0.00 | 0.00 |
September | 67.31 | 26.19 | 41.12 | 124.93 | 18.44 | 0.00 | 0.00 | 0.00 |
October | 94.52 | 61.09 | 33.43 | 144.99 | 54.62 | 0.00 | 0.00 | 0.00 |
November | 103.26 | 68.91 | 34.36 | 140.30 | 78.30 | 0.00 | 0.00 | 0.00 |
December | 103.51 | 72.82 | 30.70 | 125.84 | 103.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 78.06 | 38.12 | 39.94 | 120.86 | 53.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 49.32 | 2.75 | 30.70 | 93.49 | 2.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 104.25 | 72.82 | 48.41 | 144.99 | 126.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.12 | 38.65 | 44.47 | 61.62 | 268.35 | 0.00 | 0.00 | 0.00 |
February | 95.23 | 44.63 | 50.60 | 94.68 | 216.73 | 0.00 | 0.00 | 0.00 |
March | 139.71 | 67.38 | 72.33 | 176.49 | 124.53 | 0.00 | 0.00 | 0.00 |
April | 157.43 | 72.01 | 85.43 | 235.37 | 90.48 | 0.00 | 0.00 | 0.00 |
May | 158.41 | 60.12 | 98.28 | 266.44 | 49.98 | 0.00 | 0.00 | 0.00 |
June | 166.42 | 64.08 | 102.34 | 322.56 | 23.15 | 0.00 | 0.00 | 0.00 |
July | 156.65 | 57.94 | 98.71 | 320.31 | 10.87 | 0.00 | 0.00 | 0.00 |
August | 153.87 | 57.55 | 96.32 | 316.97 | 5.44 | 0.00 | 0.00 | 0.00 |
September | 125.70 | 52.55 | 73.15 | 221.06 | 34.57 | 0.00 | 0.00 | 0.00 |
October | 111.85 | 58.15 | 53.69 | 158.62 | 107.89 | 0.00 | 0.00 | 0.00 |
November | 88.83 | 39.72 | 49.11 | 100.54 | 161.98 | 0.00 | 0.00 | 0.00 |
December | 73.57 | 32.23 | 41.35 | 60.46 | 219.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 126.06 | 53.79 | 72.27 | 195.14 | 108.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 73.57 | 32.23 | 41.35 | 60.46 | 5.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 166.42 | 72.01 | 102.34 | 322.56 | 268.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.63 | 0.00 | 19.63 | 2.69 | 151.92 | 0.00 | 0.00 | 0.00 |
February | 21.76 | 0.00 | 21.76 | 9.68 | 121.22 | 0.00 | 0.00 | 0.00 |
March | 30.56 | 0.00 | 30.56 | 22.62 | 69.06 | 0.00 | 0.00 | 0.00 |
April | 37.06 | 0.22 | 36.84 | 44.95 | 50.37 | 0.00 | 0.00 | 0.00 |
May | 44.21 | 1.39 | 42.83 | 69.41 | 27.38 | 0.00 | 0.00 | 0.00 |
June | 48.63 | 3.19 | 45.44 | 100.96 | 12.44 | 0.00 | 0.00 | 0.00 |
July | 46.05 | 2.36 | 43.69 | 103.64 | 6.40 | 0.00 | 0.00 | 0.00 |
August | 40.90 | 0.48 | 40.42 | 95.93 | 3.24 | 0.00 | 0.00 | 0.00 |
September | 30.88 | 0.01 | 30.86 | 54.46 | 20.01 | 0.00 | 0.00 | 0.00 |
October | 23.46 | 0.00 | 23.46 | 24.06 | 59.18 | 0.00 | 0.00 | 0.00 |
November | 21.00 | 0.00 | 21.00 | 12.49 | 87.51 | 0.00 | 0.00 | 0.00 |
December | 18.15 | 0.00 | 18.15 | 3.34 | 120.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 31.91 | 0.64 | 31.27 | 45.56 | 60.48 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.15 | 0.00 | 18.15 | 2.69 | 3.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 48.63 | 3.19 | 45.44 | 103.64 | 151.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.12 | 38.65 | 44.47 | 65.41 | 263.65 | 0.00 | 0.00 | 0.00 |
February | 95.23 | 44.63 | 50.60 | 98.21 | 213.55 | 0.00 | 0.00 | 0.00 |
March | 139.71 | 67.38 | 72.33 | 179.00 | 124.06 | 0.00 | 0.00 | 0.00 |
April | 157.43 | 72.01 | 85.43 | 235.28 | 93.12 | 0.00 | 0.00 | 0.00 |
May | 158.41 | 60.12 | 98.28 | 264.01 | 53.64 | 0.00 | 0.00 | 0.00 |
June | 166.42 | 64.08 | 102.34 | 319.56 | 25.00 | 0.00 | 0.00 | 0.00 |
July | 156.65 | 57.94 | 98.71 | 317.43 | 12.35 | 0.00 | 0.00 | 0.00 |
August | 153.87 | 57.55 | 96.32 | 315.57 | 6.14 | 0.00 | 0.00 | 0.00 |
September | 125.70 | 52.55 | 73.15 | 220.66 | 37.04 | 0.00 | 0.00 | 0.00 |
October | 111.85 | 58.15 | 53.69 | 161.09 | 108.18 | 0.00 | 0.00 | 0.00 |
November | 88.83 | 39.72 | 49.11 | 105.06 | 158.95 | 0.00 | 0.00 | 0.00 |
December | 73.57 | 32.23 | 41.35 | 64.83 | 214.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 126.06 | 53.79 | 72.27 | 196.04 | 108.68 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 73.57 | 32.23 | 41.35 | 64.83 | 6.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 166.42 | 72.01 | 102.34 | 319.56 | 263.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.38 | 57.92 | 25.46 | 87.40 | 112.92 | 0.00 | 0.00 | 0.00 |
February | 77.67 | 51.82 | 25.85 | 86.03 | 105.68 | 0.00 | 0.00 | 0.00 |
March | 71.03 | 37.27 | 33.75 | 83.53 | 79.96 | 0.00 | 0.00 | 0.00 |
April | 53.45 | 17.83 | 35.62 | 69.75 | 64.89 | 0.00 | 0.00 | 0.00 |
May | 42.97 | 5.26 | 37.71 | 59.20 | 43.67 | 0.00 | 0.00 | 0.00 |
June | 39.45 | 2.20 | 37.25 | 66.58 | 27.45 | 0.00 | 0.00 | 0.00 |
July | 39.57 | 2.67 | 36.91 | 71.41 | 20.19 | 0.00 | 0.00 | 0.00 |
August | 47.69 | 8.96 | 38.72 | 88.90 | 17.46 | 0.00 | 0.00 | 0.00 |
September | 53.84 | 20.95 | 32.89 | 84.37 | 36.89 | 0.00 | 0.00 | 0.00 |
October | 75.60 | 48.86 | 26.74 | 102.15 | 72.54 | 0.00 | 0.00 | 0.00 |
November | 82.59 | 55.11 | 27.48 | 97.92 | 93.85 | 0.00 | 0.00 | 0.00 |
December | 82.79 | 58.24 | 24.55 | 88.59 | 111.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 62.43 | 30.49 | 31.95 | 82.15 | 65.37 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 39.45 | 2.20 | 24.55 | 59.20 | 17.46 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 83.38 | 58.24 | 38.72 | 102.15 | 112.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 15.71 | 0.00 | 15.71 | 1.94 | 127.54 | 0.00 | 0.00 | 0.00 |
February | 17.41 | 0.00 | 17.41 | 7.68 | 101.25 | 0.00 | 0.00 | 0.00 |
March | 24.45 | 0.00 | 24.45 | 18.90 | 55.74 | 0.00 | 0.00 | 0.00 |
April | 29.65 | 0.17 | 29.48 | 37.79 | 39.83 | 0.00 | 0.00 | 0.00 |
May | 35.37 | 1.11 | 34.27 | 58.14 | 21.11 | 0.00 | 0.00 | 0.00 |
June | 38.91 | 2.55 | 36.35 | 84.61 | 8.87 | 0.00 | 0.00 | 0.00 |
July | 36.85 | 1.89 | 34.96 | 87.14 | 4.33 | 0.00 | 0.00 | 0.00 |
August | 32.73 | 0.38 | 32.34 | 81.52 | 1.88 | 0.00 | 0.00 | 0.00 |
September | 24.70 | 0.01 | 24.69 | 46.04 | 15.28 | 0.00 | 0.00 | 0.00 |
October | 18.77 | 0.00 | 18.77 | 20.12 | 47.98 | 0.00 | 0.00 | 0.00 |
November | 16.80 | 0.00 | 16.80 | 9.87 | 72.57 | 0.00 | 0.00 | 0.00 |
December | 14.52 | 0.00 | 14.52 | 2.26 | 101.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 25.53 | 0.51 | 25.02 | 38.18 | 49.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.52 | 0.00 | 14.52 | 1.94 | 1.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 38.91 | 2.55 | 36.35 | 87.14 | 127.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 81.12 | 36.93 | 44.18 | 51.63 | 260.87 | 0.00 | 0.00 | 0.00 |
February | 101.81 | 54.80 | 47.00 | 94.23 | 205.05 | 0.00 | 0.00 | 0.00 |
March | 128.09 | 58.43 | 69.66 | 147.54 | 115.27 | 0.00 | 0.00 | 0.00 |
April | 154.84 | 70.67 | 84.16 | 223.83 | 83.26 | 0.00 | 0.00 | 0.00 |
May | 169.62 | 71.73 | 97.89 | 280.22 | 45.94 | 0.00 | 0.00 | 0.00 |
June | 175.44 | 73.48 | 101.96 | 335.84 | 20.97 | 0.00 | 0.00 | 0.00 |
July | 171.00 | 71.74 | 99.26 | 343.47 | 10.44 | 0.00 | 0.00 | 0.00 |
August | 156.73 | 62.17 | 94.56 | 322.39 | 5.10 | 0.00 | 0.00 | 0.00 |
September | 128.45 | 56.76 | 71.69 | 224.52 | 32.82 | 0.00 | 0.00 | 0.00 |
October | 109.86 | 57.18 | 52.68 | 147.17 | 100.35 | 0.00 | 0.00 | 0.00 |
November | 87.50 | 39.47 | 48.03 | 85.77 | 149.09 | 0.00 | 0.00 | 0.00 |
December | 75.93 | 34.56 | 41.37 | 51.90 | 206.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 128.49 | 57.32 | 71.17 | 192.91 | 102.48 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 75.93 | 34.56 | 41.37 | 51.63 | 5.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 175.44 | 73.48 | 101.96 | 343.47 | 260.87 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 104.25 | 72.42 | 31.83 | 116.54 | 126.29 | 0.00 | 0.00 | 0.00 |
February | 97.11 | 64.78 | 32.32 | 118.41 | 103.92 | 0.00 | 0.00 | 0.00 |
March | 88.80 | 46.60 | 42.20 | 121.49 | 63.59 | 0.00 | 0.00 | 0.00 |
April | 66.83 | 22.30 | 44.53 | 104.30 | 48.81 | 0.00 | 0.00 | 0.00 |
May | 53.72 | 6.57 | 47.15 | 92.54 | 26.83 | 0.00 | 0.00 | 0.00 |
June | 49.32 | 2.75 | 46.57 | 105.31 | 12.32 | 0.00 | 0.00 | 0.00 |
July | 49.48 | 3.34 | 46.14 | 113.02 | 5.79 | 0.00 | 0.00 | 0.00 |
August | 59.62 | 11.20 | 48.41 | 135.91 | 2.82 | 0.00 | 0.00 | 0.00 |
September | 67.31 | 26.19 | 41.12 | 124.43 | 18.24 | 0.00 | 0.00 | 0.00 |
October | 94.52 | 61.09 | 33.43 | 144.18 | 54.24 | 0.00 | 0.00 | 0.00 |
November | 103.26 | 68.91 | 34.36 | 139.64 | 77.97 | 0.00 | 0.00 | 0.00 |
December | 103.51 | 72.82 | 30.70 | 125.21 | 103.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 78.06 | 38.12 | 39.94 | 120.11 | 53.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 49.32 | 2.75 | 30.70 | 92.54 | 2.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 104.25 | 72.82 | 48.41 | 144.18 | 126.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.63 | 0.00 | 19.63 | 2.54 | 151.99 | 0.00 | 0.00 | 0.00 |
February | 21.76 | 0.00 | 21.76 | 9.27 | 121.40 | 0.00 | 0.00 | 0.00 |
March | 30.56 | 0.00 | 30.56 | 22.21 | 68.31 | 0.00 | 0.00 | 0.00 |
April | 37.06 | 0.22 | 36.84 | 44.05 | 49.73 | 0.00 | 0.00 | 0.00 |
May | 44.21 | 1.39 | 42.83 | 68.16 | 26.98 | 0.00 | 0.00 | 0.00 |
June | 48.63 | 3.19 | 45.44 | 99.53 | 12.20 | 0.00 | 0.00 | 0.00 |
July | 46.05 | 2.36 | 43.69 | 102.37 | 6.37 | 0.00 | 0.00 | 0.00 |
August | 40.90 | 0.48 | 40.42 | 95.26 | 3.13 | 0.00 | 0.00 | 0.00 |
September | 30.88 | 0.01 | 30.86 | 53.60 | 19.77 | 0.00 | 0.00 | 0.00 |
October | 23.46 | 0.00 | 23.46 | 23.36 | 58.58 | 0.00 | 0.00 | 0.00 |
November | 21.00 | 0.00 | 21.00 | 12.29 | 86.99 | 0.00 | 0.00 | 0.00 |
December | 18.15 | 0.00 | 18.15 | 3.20 | 120.71 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 31.91 | 0.64 | 31.27 | 44.86 | 60.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.15 | 0.00 | 18.15 | 2.54 | 3.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 48.63 | 3.19 | 45.44 | 102.37 | 151.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 81.12 | 36.93 | 44.18 | 53.61 | 254.18 | 0.00 | 0.00 | 0.00 |
February | 101.81 | 54.80 | 47.00 | 97.29 | 200.94 | 0.00 | 0.00 | 0.00 |
March | 128.09 | 58.43 | 69.66 | 150.81 | 114.06 | 0.00 | 0.00 | 0.00 |
April | 154.84 | 70.67 | 84.16 | 224.15 | 85.41 | 0.00 | 0.00 | 0.00 |
May | 169.62 | 71.73 | 97.89 | 277.22 | 49.20 | 0.00 | 0.00 | 0.00 |
June | 175.44 | 73.48 | 101.96 | 331.30 | 22.57 | 0.00 | 0.00 | 0.00 |
July | 171.00 | 71.74 | 99.26 | 339.05 | 11.84 | 0.00 | 0.00 | 0.00 |
August | 156.73 | 62.17 | 94.56 | 320.04 | 5.68 | 0.00 | 0.00 | 0.00 |
September | 128.45 | 56.76 | 71.69 | 223.13 | 35.01 | 0.00 | 0.00 | 0.00 |
October | 109.86 | 57.18 | 52.68 | 149.87 | 100.01 | 0.00 | 0.00 | 0.00 |
November | 87.50 | 39.47 | 48.03 | 90.46 | 145.02 | 0.00 | 0.00 | 0.00 |
December | 75.93 | 34.56 | 41.37 | 54.91 | 200.02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 128.49 | 57.32 | 71.17 | 193.17 | 101.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 75.93 | 34.56 | 41.37 | 53.61 | 5.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 175.44 | 73.48 | 101.96 | 339.05 | 254.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 24.87 | 0.00 | 24.87 | 3.28 | 192.22 | 0.00 | 0.00 | 0.00 |
February | 27.56 | 0.00 | 27.56 | 12.93 | 151.17 | 0.00 | 0.00 | 0.00 |
March | 38.70 | 0.00 | 38.70 | 32.67 | 81.39 | 0.00 | 0.00 | 0.00 |
April | 46.93 | 0.27 | 46.65 | 63.55 | 57.89 | 0.00 | 0.00 | 0.00 |
May | 55.99 | 1.76 | 54.24 | 95.78 | 31.21 | 0.00 | 0.00 | 0.00 |
June | 61.58 | 4.04 | 57.54 | 132.12 | 15.79 | 0.00 | 0.00 | 0.00 |
July | 58.32 | 2.99 | 55.33 | 132.94 | 9.12 | 0.00 | 0.00 | 0.00 |
August | 51.80 | 0.61 | 51.19 | 121.90 | 5.44 | 0.00 | 0.00 | 0.00 |
September | 39.10 | 0.02 | 39.09 | 73.11 | 24.43 | 0.00 | 0.00 | 0.00 |
October | 29.71 | 0.00 | 29.71 | 33.84 | 70.37 | 0.00 | 0.00 | 0.00 |
November | 26.59 | 0.00 | 26.59 | 17.03 | 106.97 | 0.00 | 0.00 | 0.00 |
December | 22.99 | 0.00 | 22.99 | 3.93 | 151.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.42 | 0.81 | 39.60 | 60.52 | 74.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.99 | 0.00 | 22.99 | 3.28 | 5.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 61.58 | 4.04 | 57.54 | 132.94 | 192.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 9.17 | 0.00 | 9.17 | 1.21 | 70.86 | 0.00 | 0.00 | 0.00 |
February | 10.16 | 0.00 | 10.16 | 4.77 | 55.73 | 0.00 | 0.00 | 0.00 |
March | 14.27 | 0.00 | 14.27 | 12.04 | 30.01 | 0.00 | 0.00 | 0.00 |
April | 17.30 | 0.10 | 17.20 | 23.43 | 21.34 | 0.00 | 0.00 | 0.00 |
May | 20.64 | 0.65 | 19.99 | 35.31 | 11.51 | 0.00 | 0.00 | 0.00 |
June | 22.70 | 1.49 | 21.21 | 48.70 | 5.82 | 0.00 | 0.00 | 0.00 |
July | 21.50 | 1.10 | 20.40 | 49.01 | 3.36 | 0.00 | 0.00 | 0.00 |
August | 19.10 | 0.22 | 18.87 | 44.94 | 2.00 | 0.00 | 0.00 | 0.00 |
September | 14.41 | 0.01 | 14.41 | 26.95 | 9.01 | 0.00 | 0.00 | 0.00 |
October | 10.95 | 0.00 | 10.95 | 12.48 | 25.94 | 0.00 | 0.00 | 0.00 |
November | 9.80 | 0.00 | 9.80 | 6.28 | 39.43 | 0.00 | 0.00 | 0.00 |
December | 8.47 | 0.00 | 8.47 | 1.45 | 56.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 14.90 | 0.30 | 14.60 | 22.31 | 27.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 8.47 | 0.00 | 8.47 | 1.21 | 2.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 22.70 | 1.49 | 21.21 | 49.01 | 70.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 48.64 | 33.79 | 14.85 | 55.35 | 57.77 | 0.00 | 0.00 | 0.00 |
February | 45.31 | 30.23 | 15.08 | 56.88 | 47.12 | 0.00 | 0.00 | 0.00 |
March | 41.43 | 21.74 | 19.69 | 59.50 | 28.02 | 0.00 | 0.00 | 0.00 |
April | 31.18 | 10.40 | 20.78 | 51.54 | 21.54 | 0.00 | 0.00 | 0.00 |
May | 25.07 | 3.07 | 22.00 | 45.82 | 12.19 | 0.00 | 0.00 | 0.00 |
June | 23.01 | 1.28 | 21.73 | 50.26 | 6.27 | 0.00 | 0.00 | 0.00 |
July | 23.09 | 1.56 | 21.53 | 52.90 | 3.49 | 0.00 | 0.00 | 0.00 |
August | 27.82 | 5.23 | 22.59 | 63.18 | 2.03 | 0.00 | 0.00 | 0.00 |
September | 31.41 | 12.22 | 19.19 | 59.50 | 8.93 | 0.00 | 0.00 | 0.00 |
October | 44.10 | 28.50 | 15.60 | 69.65 | 24.25 | 0.00 | 0.00 | 0.00 |
November | 48.18 | 32.15 | 16.03 | 67.24 | 34.72 | 0.00 | 0.00 | 0.00 |
December | 48.30 | 33.98 | 14.32 | 59.67 | 46.80 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 36.42 | 17.79 | 18.64 | 57.63 | 24.31 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 23.01 | 1.28 | 14.32 | 45.82 | 2.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 48.64 | 33.98 | 22.59 | 69.65 | 57.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 132.02 | 91.71 | 40.31 | 150.23 | 156.80 | 0.00 | 0.00 | 0.00 |
February | 122.98 | 82.05 | 40.94 | 154.38 | 127.90 | 0.00 | 0.00 | 0.00 |
March | 112.46 | 59.01 | 53.45 | 161.48 | 76.06 | 0.00 | 0.00 | 0.00 |
April | 84.63 | 28.24 | 56.40 | 139.90 | 58.47 | 0.00 | 0.00 | 0.00 |
May | 68.03 | 8.33 | 59.71 | 124.36 | 33.09 | 0.00 | 0.00 | 0.00 |
June | 62.47 | 3.49 | 58.98 | 136.42 | 17.03 | 0.00 | 0.00 | 0.00 |
July | 62.66 | 4.23 | 58.43 | 143.57 | 9.46 | 0.00 | 0.00 | 0.00 |
August | 75.50 | 14.19 | 61.31 | 171.48 | 5.50 | 0.00 | 0.00 | 0.00 |
September | 85.24 | 33.17 | 52.08 | 161.49 | 24.24 | 0.00 | 0.00 | 0.00 |
October | 119.70 | 77.37 | 42.33 | 189.03 | 65.81 | 0.00 | 0.00 | 0.00 |
November | 130.78 | 87.27 | 43.51 | 182.51 | 94.23 | 0.00 | 0.00 | 0.00 |
December | 131.09 | 92.22 | 38.87 | 161.95 | 127.02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 98.86 | 48.28 | 50.58 | 156.43 | 65.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 62.47 | 3.49 | 38.87 | 124.36 | 5.50 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 132.02 | 92.22 | 61.31 | 189.03 | 156.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 104.25 | 72.42 | 31.83 | 116.66 | 126.06 | 0.00 | 0.00 | 0.00 |
February | 97.11 | 64.78 | 32.32 | 118.62 | 103.64 | 0.67 | 0.00 | 0.00 |
March | 88.80 | 46.60 | 42.20 | 120.90 | 63.82 | 0.00 | 0.00 | 0.00 |
April | 66.83 | 22.30 | 44.53 | 103.63 | 49.04 | 0.00 | 0.00 | 0.00 |
May | 53.72 | 6.57 | 47.15 | 91.80 | 26.94 | 0.00 | 0.00 | 0.00 |
June | 49.32 | 2.75 | 46.57 | 104.89 | 12.21 | 0.00 | 0.00 | 0.00 |
July | 49.48 | 3.34 | 46.14 | 112.56 | 5.64 | 0.00 | 0.00 | 0.00 |
August | 59.62 | 11.20 | 48.41 | 134.95 | 2.70 | 0.00 | 0.00 | 0.00 |
September | 67.31 | 26.19 | 41.12 | 123.56 | 18.12 | 0.00 | 0.00 | 0.00 |
October | 94.52 | 61.09 | 33.43 | 143.51 | 54.24 | 0.50 | 0.00 | 0.00 |
November | 103.26 | 68.91 | 34.36 | 139.32 | 77.71 | 0.00 | 0.00 | 0.00 |
December | 103.51 | 72.82 | 30.70 | 125.22 | 102.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 78.06 | 38.12 | 39.94 | 119.66 | 53.30 | 1.17 | 0.00 | 0.00 |
Minimum of Months | 49.32 | 2.75 | 30.70 | 91.80 | 2.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 104.25 | 72.82 | 48.41 | 143.51 | 126.06 | 0.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.12 | 38.65 | 44.47 | 61.42 | 267.36 | 0.00 | 0.00 | 0.00 |
February | 95.23 | 44.63 | 50.60 | 93.82 | 215.53 | 2.33 | 0.00 | 0.00 |
March | 139.71 | 67.38 | 72.33 | 173.87 | 123.76 | 0.00 | 0.00 | 0.00 |
April | 157.43 | 72.01 | 85.43 | 231.85 | 90.23 | 0.00 | 0.00 | 0.00 |
May | 158.41 | 60.12 | 98.28 | 262.56 | 49.81 | 0.00 | 0.00 | 0.00 |
June | 166.42 | 64.08 | 102.34 | 318.98 | 22.59 | 0.00 | 0.00 | 0.00 |
July | 156.65 | 57.94 | 98.71 | 317.28 | 10.42 | 0.00 | 0.00 | 0.00 |
August | 153.87 | 57.55 | 96.32 | 314.02 | 5.04 | 0.00 | 0.00 | 0.00 |
September | 125.70 | 52.55 | 73.15 | 218.54 | 33.90 | 0.00 | 0.00 | 0.00 |
October | 111.85 | 58.15 | 53.69 | 156.47 | 107.04 | 0.50 | 0.00 | 0.00 |
November | 88.83 | 39.72 | 49.11 | 99.44 | 160.78 | 0.00 | 0.00 | 0.00 |
December | 73.57 | 32.23 | 41.35 | 60.23 | 217.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 126.06 | 53.79 | 72.27 | 192.91 | 108.17 | 2.83 | 0.00 | 0.00 |
Minimum of Months | 73.57 | 32.23 | 41.35 | 60.23 | 5.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 166.42 | 72.01 | 102.34 | 318.98 | 267.36 | 2.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.63 | 0.00 | 19.63 | 2.78 | 151.46 | 0.00 | 0.00 | 0.00 |
February | 21.76 | 0.00 | 21.76 | 9.75 | 120.75 | 2.67 | 0.00 | 0.00 |
March | 30.56 | 0.00 | 30.56 | 22.20 | 68.93 | 0.00 | 0.00 | 0.00 |
April | 37.06 | 0.22 | 36.84 | 43.81 | 50.85 | 0.00 | 0.00 | 0.00 |
May | 44.21 | 1.39 | 42.83 | 67.77 | 27.84 | 0.00 | 0.00 | 0.00 |
June | 48.63 | 3.19 | 45.44 | 99.73 | 12.33 | 0.00 | 0.00 | 0.00 |
July | 46.05 | 2.36 | 43.69 | 102.49 | 6.29 | 0.00 | 0.00 | 0.00 |
August | 40.90 | 0.48 | 40.42 | 94.94 | 3.04 | 0.00 | 0.00 | 0.00 |
September | 30.88 | 0.01 | 30.86 | 53.62 | 19.85 | 0.00 | 0.00 | 0.00 |
October | 23.46 | 0.00 | 23.46 | 23.69 | 59.03 | 0.50 | 0.00 | 0.00 |
November | 21.00 | 0.00 | 21.00 | 12.61 | 86.80 | 0.00 | 0.00 | 0.00 |
December | 18.15 | 0.00 | 18.15 | 3.57 | 119.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 31.91 | 0.64 | 31.27 | 44.95 | 60.27 | 3.17 | 0.00 | 0.00 |
Minimum of Months | 18.15 | 0.00 | 18.15 | 2.78 | 3.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 48.63 | 3.19 | 45.44 | 102.49 | 151.46 | 2.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.12 | 38.65 | 44.47 | 65.32 | 262.98 | 0.00 | 0.00 | 0.00 |
February | 95.23 | 44.63 | 50.60 | 97.47 | 212.61 | 2.50 | 0.00 | 0.00 |
March | 139.71 | 67.38 | 72.33 | 176.51 | 123.54 | 0.00 | 0.00 | 0.00 |
April | 157.43 | 72.01 | 85.43 | 231.39 | 93.80 | 0.00 | 0.00 | 0.00 |
May | 158.41 | 60.12 | 98.28 | 259.67 | 54.28 | 0.00 | 0.00 | 0.00 |
June | 166.42 | 64.08 | 102.34 | 315.81 | 24.66 | 0.00 | 0.00 | 0.00 |
July | 156.65 | 57.94 | 98.71 | 314.25 | 12.01 | 0.00 | 0.00 | 0.00 |
August | 153.87 | 57.55 | 96.32 | 312.53 | 5.75 | 0.00 | 0.00 | 0.00 |
September | 125.70 | 52.55 | 73.15 | 218.01 | 36.68 | 0.00 | 0.00 | 0.00 |
October | 111.85 | 58.15 | 53.69 | 159.04 | 107.70 | 0.50 | 0.00 | 0.00 |
November | 88.83 | 39.72 | 49.11 | 104.48 | 157.58 | 0.00 | 0.00 | 0.00 |
December | 73.57 | 32.23 | 41.35 | 65.05 | 213.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 126.06 | 53.79 | 72.27 | 193.82 | 108.21 | 3.00 | 0.00 | 0.00 |
Minimum of Months | 73.57 | 32.23 | 41.35 | 65.05 | 5.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 166.42 | 72.01 | 102.34 | 315.81 | 262.98 | 2.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 152.89 | 106.21 | 46.68 | 162.83 | 193.13 | 0.00 | 0.00 | 0.00 |
February | 142.42 | 95.01 | 47.41 | 167.66 | 158.63 | 0.00 | 0.00 | 0.00 |
March | 130.23 | 68.34 | 61.89 | 174.43 | 95.62 | 0.00 | 0.00 | 0.00 |
April | 98.01 | 32.70 | 65.31 | 152.18 | 71.45 | 0.00 | 0.00 | 0.00 |
May | 78.78 | 9.64 | 69.14 | 137.15 | 38.23 | 0.00 | 0.00 | 0.00 |
June | 72.34 | 4.04 | 68.30 | 158.11 | 16.60 | 0.00 | 0.00 | 0.00 |
July | 72.57 | 4.89 | 67.67 | 169.67 | 7.39 | 0.00 | 0.00 | 0.00 |
August | 87.44 | 16.43 | 71.00 | 202.14 | 3.38 | 0.00 | 0.00 | 0.00 |
September | 98.72 | 38.41 | 60.31 | 182.28 | 26.11 | 0.00 | 0.00 | 0.00 |
October | 138.62 | 89.59 | 49.02 | 207.83 | 81.79 | 0.00 | 0.00 | 0.00 |
November | 151.44 | 101.06 | 50.39 | 198.79 | 119.11 | 0.00 | 0.00 | 0.00 |
December | 151.81 | 106.80 | 45.02 | 175.88 | 158.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 114.48 | 55.91 | 58.58 | 174.15 | 80.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 72.34 | 4.04 | 45.02 | 137.15 | 3.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 152.89 | 106.80 | 71.00 | 207.83 | 193.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 137.44 | 0.00 | 137.44 | 14.69 | 1140.64 | 0.00 | 0.00 | 0.00 |
February | 152.33 | 0.00 | 152.33 | 60.19 | 924.32 | 0.00 | 0.00 | 0.00 |
March | 213.92 | 0.00 | 213.92 | 148.31 | 542.23 | 0.00 | 0.00 | 0.00 |
April | 259.38 | 1.51 | 257.87 | 302.73 | 398.27 | 0.00 | 0.00 | 0.00 |
May | 309.48 | 9.71 | 299.77 | 465.51 | 236.63 | 0.00 | 0.00 | 0.00 |
June | 340.37 | 22.32 | 318.05 | 664.18 | 129.76 | 0.00 | 0.00 | 0.00 |
July | 322.35 | 16.52 | 305.83 | 672.64 | 83.58 | 0.00 | 0.00 | 0.00 |
August | 286.31 | 3.36 | 282.94 | 615.47 | 62.63 | 0.00 | 0.00 | 0.00 |
September | 216.12 | 0.08 | 216.03 | 359.26 | 190.72 | 0.00 | 0.00 | 0.00 |
October | 164.21 | 0.00 | 164.21 | 157.95 | 475.71 | 0.00 | 0.00 | 0.00 |
November | 146.96 | 0.00 | 146.96 | 75.58 | 682.34 | 0.00 | 0.00 | 0.00 |
December | 127.05 | 0.00 | 127.05 | 16.02 | 928.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 223.38 | 4.48 | 218.90 | 297.39 | 480.74 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 127.05 | 0.00 | 127.05 | 14.69 | 62.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 340.37 | 22.32 | 318.05 | 672.64 | 1140.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 137.44 | 0.00 | 137.44 | 13.02 | 1171.51 | 0.00 | 0.00 | 0.00 |
February | 152.33 | 0.00 | 152.33 | 55.42 | 954.53 | 0.00 | 0.00 | 0.00 |
March | 213.92 | 0.00 | 213.92 | 136.53 | 567.48 | 0.00 | 0.00 | 0.00 |
April | 259.38 | 1.51 | 257.87 | 287.32 | 416.33 | 0.00 | 0.00 | 0.00 |
May | 309.48 | 9.71 | 299.77 | 448.69 | 248.49 | 0.00 | 0.00 | 0.00 |
June | 340.37 | 22.32 | 318.05 | 649.05 | 136.97 | 0.00 | 0.00 | 0.00 |
July | 322.35 | 16.52 | 305.83 | 658.73 | 89.62 | 0.00 | 0.00 | 0.00 |
August | 286.31 | 3.36 | 282.94 | 602.15 | 68.43 | 0.00 | 0.00 | 0.00 |
September | 216.12 | 0.08 | 216.03 | 345.18 | 203.36 | 0.00 | 0.00 | 0.00 |
October | 164.21 | 0.00 | 164.21 | 147.07 | 499.98 | 0.00 | 0.00 | 0.00 |
November | 146.96 | 0.00 | 146.96 | 67.25 | 711.00 | 0.00 | 0.00 | 0.00 |
December | 127.05 | 0.00 | 127.05 | 13.41 | 961.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 223.38 | 4.48 | 218.90 | 286.64 | 500.18 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 127.05 | 0.00 | 127.05 | 13.02 | 68.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 340.37 | 22.32 | 318.05 | 658.73 | 1171.51 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.63 | 0.00 | 19.63 | 2.56 | 159.63 | 0.00 | 0.00 | 0.00 |
February | 21.76 | 0.00 | 21.76 | 10.01 | 128.81 | 0.00 | 0.00 | 0.00 |
March | 30.56 | 0.00 | 30.56 | 25.89 | 73.76 | 0.00 | 0.00 | 0.00 |
April | 37.06 | 0.22 | 36.84 | 52.90 | 53.25 | 0.00 | 0.00 | 0.00 |
May | 44.21 | 1.39 | 42.83 | 81.14 | 31.64 | 0.00 | 0.00 | 0.00 |
June | 48.63 | 3.19 | 45.44 | 113.00 | 17.66 | 0.00 | 0.00 | 0.00 |
July | 46.05 | 2.36 | 43.69 | 116.02 | 10.96 | 0.00 | 0.00 | 0.00 |
August | 40.90 | 0.48 | 40.42 | 107.54 | 7.92 | 0.00 | 0.00 | 0.00 |
September | 30.88 | 0.01 | 30.86 | 64.57 | 23.66 | 0.00 | 0.00 | 0.00 |
October | 23.46 | 0.00 | 23.46 | 28.47 | 63.42 | 0.00 | 0.00 | 0.00 |
November | 21.00 | 0.00 | 21.00 | 13.96 | 92.70 | 0.00 | 0.00 | 0.00 |
December | 18.15 | 0.00 | 18.15 | 2.97 | 128.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 31.91 | 0.64 | 31.27 | 51.82 | 65.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.15 | 0.00 | 18.15 | 2.56 | 7.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 48.63 | 3.19 | 45.44 | 116.02 | 159.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 162.23 | 73.86 | 88.36 | 108.33 | 536.57 | 0.00 | 0.00 | 0.00 |
February | 203.60 | 109.60 | 94.00 | 199.84 | 431.61 | 0.00 | 0.00 | 0.00 |
March | 256.16 | 116.85 | 139.31 | 319.73 | 251.66 | 0.00 | 0.00 | 0.00 |
April | 309.65 | 141.33 | 168.31 | 484.64 | 187.24 | 0.00 | 0.00 | 0.00 |
May | 339.21 | 143.45 | 195.76 | 602.51 | 116.88 | 0.00 | 0.00 | 0.00 |
June | 350.85 | 146.95 | 203.90 | 713.48 | 65.84 | 0.00 | 0.00 | 0.00 |
July | 341.97 | 143.47 | 198.50 | 726.44 | 41.31 | 0.00 | 0.00 | 0.00 |
August | 313.43 | 124.33 | 189.10 | 682.84 | 29.88 | 0.00 | 0.00 | 0.00 |
September | 256.88 | 113.51 | 143.37 | 488.65 | 86.72 | 0.00 | 0.00 | 0.00 |
October | 219.71 | 114.36 | 105.35 | 322.99 | 220.84 | 0.00 | 0.00 | 0.00 |
November | 174.98 | 78.93 | 96.05 | 190.37 | 311.52 | 0.00 | 0.00 | 0.00 |
December | 151.85 | 69.12 | 82.73 | 110.52 | 429.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 256.97 | 114.63 | 142.34 | 413.66 | 224.76 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 151.85 | 69.12 | 82.73 | 108.33 | 29.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 350.85 | 146.95 | 203.90 | 726.44 | 536.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 104.25 | 72.42 | 31.83 | 119.05 | 130.15 | 0.00 | 0.00 | 0.00 |
February | 97.11 | 64.78 | 32.32 | 122.06 | 109.16 | 0.00 | 0.00 | 0.00 |
March | 88.80 | 46.60 | 42.20 | 128.31 | 69.00 | 0.00 | 0.00 | 0.00 |
April | 66.83 | 22.30 | 44.53 | 113.49 | 53.56 | 0.00 | 0.00 | 0.00 |
May | 53.72 | 6.57 | 47.15 | 103.87 | 32.80 | 0.00 | 0.00 | 0.00 |
June | 49.32 | 2.75 | 46.57 | 116.60 | 18.45 | 0.00 | 0.00 | 0.00 |
July | 49.48 | 3.34 | 46.14 | 124.14 | 11.11 | 0.00 | 0.00 | 0.00 |
August | 59.62 | 11.20 | 48.41 | 146.64 | 7.93 | 0.00 | 0.00 | 0.00 |
September | 67.31 | 26.19 | 41.12 | 135.21 | 23.36 | 0.00 | 0.00 | 0.00 |
October | 94.52 | 61.09 | 33.43 | 152.24 | 59.36 | 0.00 | 0.00 | 0.00 |
November | 103.26 | 68.91 | 34.36 | 145.93 | 81.78 | 0.00 | 0.00 | 0.00 |
December | 103.51 | 72.82 | 30.70 | 128.41 | 107.56 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 78.06 | 38.12 | 39.94 | 128.05 | 58.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 49.32 | 2.75 | 30.70 | 103.87 | 7.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 104.25 | 72.82 | 48.41 | 152.24 | 130.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 24.87 | 0.00 | 24.87 | 3.00 | 195.77 | 0.00 | 0.00 | 0.00 |
February | 27.56 | 0.00 | 27.56 | 12.02 | 154.25 | 0.00 | 0.00 | 0.00 |
March | 38.70 | 0.00 | 38.70 | 30.34 | 83.48 | 0.00 | 0.00 | 0.00 |
April | 46.93 | 0.27 | 46.65 | 60.24 | 59.55 | 0.00 | 0.00 | 0.00 |
May | 55.99 | 1.76 | 54.24 | 91.00 | 33.23 | 0.00 | 0.00 | 0.00 |
June | 61.58 | 4.04 | 57.54 | 125.59 | 17.99 | 0.00 | 0.00 | 0.00 |
July | 58.32 | 2.99 | 55.33 | 125.40 | 11.07 | 0.00 | 0.00 | 0.00 |
August | 51.80 | 0.61 | 51.19 | 114.11 | 7.57 | 0.00 | 0.00 | 0.00 |
September | 39.10 | 0.02 | 39.09 | 69.67 | 25.63 | 0.00 | 0.00 | 0.00 |
October | 29.71 | 0.00 | 29.71 | 31.70 | 72.11 | 0.00 | 0.00 | 0.00 |
November | 26.59 | 0.00 | 26.59 | 15.59 | 109.42 | 0.00 | 0.00 | 0.00 |
December | 22.99 | 0.00 | 22.99 | 3.42 | 155.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.42 | 0.81 | 39.60 | 57.09 | 76.73 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.99 | 0.00 | 22.99 | 3.00 | 7.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 61.58 | 4.04 | 57.54 | 125.59 | 195.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.25 | 0.00 | 22.25 | 2.69 | 175.15 | 0.00 | 0.00 | 0.00 |
February | 24.66 | 0.00 | 24.66 | 10.75 | 138.01 | 0.00 | 0.00 | 0.00 |
March | 34.63 | 0.00 | 34.63 | 27.14 | 74.69 | 0.00 | 0.00 | 0.00 |
April | 41.99 | 0.25 | 41.74 | 53.89 | 53.28 | 0.00 | 0.00 | 0.00 |
May | 50.10 | 1.57 | 48.53 | 81.41 | 29.73 | 0.00 | 0.00 | 0.00 |
June | 55.10 | 3.61 | 51.48 | 112.37 | 16.10 | 0.00 | 0.00 | 0.00 |
July | 52.18 | 2.67 | 49.51 | 112.20 | 9.91 | 0.00 | 0.00 | 0.00 |
August | 46.35 | 0.54 | 45.80 | 102.10 | 6.77 | 0.00 | 0.00 | 0.00 |
September | 34.98 | 0.01 | 34.97 | 62.33 | 22.93 | 0.00 | 0.00 | 0.00 |
October | 26.58 | 0.00 | 26.58 | 28.36 | 64.52 | 0.00 | 0.00 | 0.00 |
November | 23.79 | 0.00 | 23.79 | 13.95 | 97.90 | 0.00 | 0.00 | 0.00 |
December | 20.57 | 0.00 | 20.57 | 3.06 | 138.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 36.16 | 0.73 | 35.43 | 51.08 | 68.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.57 | 0.00 | 20.57 | 2.69 | 6.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 55.10 | 3.61 | 51.48 | 112.37 | 175.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 389.19 | 270.36 | 118.83 | 434.91 | 468.61 | 0.00 | 0.00 | 0.00 |
February | 362.53 | 241.86 | 120.67 | 446.42 | 384.15 | 0.00 | 0.00 | 0.00 |
March | 331.52 | 173.96 | 157.55 | 464.58 | 229.72 | 0.00 | 0.00 | 0.00 |
April | 249.49 | 83.24 | 166.25 | 400.27 | 177.67 | 0.00 | 0.00 | 0.00 |
May | 200.55 | 24.54 | 176.01 | 351.75 | 104.15 | 0.00 | 0.00 | 0.00 |
June | 184.14 | 10.28 | 173.86 | 382.82 | 57.25 | 0.00 | 0.00 | 0.00 |
July | 184.72 | 12.46 | 172.26 | 400.82 | 34.13 | 0.00 | 0.00 | 0.00 |
August | 222.58 | 41.83 | 180.75 | 481.31 | 22.84 | 0.00 | 0.00 | 0.00 |
September | 251.29 | 97.77 | 153.51 | 463.81 | 75.45 | 0.00 | 0.00 | 0.00 |
October | 352.86 | 228.06 | 124.79 | 546.62 | 198.80 | 0.00 | 0.00 | 0.00 |
November | 385.51 | 257.25 | 128.26 | 528.68 | 283.40 | 0.00 | 0.00 | 0.00 |
December | 386.45 | 271.85 | 114.60 | 468.85 | 380.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 291.42 | 142.31 | 149.11 | 447.62 | 200.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 184.14 | 10.28 | 114.60 | 351.75 | 22.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 389.19 | 271.85 | 180.75 | 546.62 | 468.61 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.141220E+10 | 0.981020E+09 | 0.431183E+09 | 0.162442E+10 | 0.155125E+10 |
February | 0.118818E+10 | 0.792686E+09 | 0.395494E+09 | 0.149453E+10 | 0.115479E+10 |
March | 0.120293E+10 | 0.631243E+09 | 0.571687E+09 | 0.170507E+10 | 0.793037E+09 |
April | 0.876087E+09 | 0.292293E+09 | 0.583795E+09 | 0.141596E+10 | 0.590509E+09 |
May | 0.727706E+09 | 89053889.35 | 0.638652E+09 | 0.129078E+10 | 0.349621E+09 |
June | 0.646621E+09 | 36100811.87 | 0.610520E+09 | 0.134610E+10 | 0.185152E+09 |
July | 0.670261E+09 | 45210453.17 | 0.625050E+09 | 0.145056E+10 | 0.111103E+09 |
August | 0.807634E+09 | 0.151787E+09 | 0.655847E+09 | 0.171968E+10 | 85442102.01 |
September | 0.882405E+09 | 0.343335E+09 | 0.539070E+09 | 0.161103E+10 | 0.262424E+09 |
October | 0.128037E+10 | 0.827554E+09 | 0.452812E+09 | 0.196894E+10 | 0.700738E+09 |
November | 0.135373E+10 | 0.903351E+09 | 0.450383E+09 | 0.185913E+10 | 0.946964E+09 |
December | 0.140226E+10 | 0.986443E+09 | 0.415820E+09 | 0.173575E+10 | 0.127702E+10 |
Annual Sum or Average | 0.124504E+11 | 0.608008E+10 | 0.637031E+10 | 0.192219E+11 | 0.800805E+10 |
Minimum of Months | 0.646621E+09 | 36100811.87 | 0.395494E+09 | 0.129078E+10 | 85442102.01 |
Maximum of Months | 0.141220E+10 | 0.986443E+09 | 0.655847E+09 | 0.196894E+10 | 0.155125E+10 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.397667E+10 | 0.276249E+10 | 0.121418E+10 | 0.452361E+10 | 0.445919E+10 |
February | 0.334584E+10 | 0.223215E+10 | 0.111368E+10 | 0.416223E+10 | 0.336501E+10 |
March | 0.338737E+10 | 0.177754E+10 | 0.160983E+10 | 0.474124E+10 | 0.239794E+10 |
April | 0.246700E+10 | 0.823077E+09 | 0.164393E+10 | 0.393275E+10 | 0.180698E+10 |
May | 0.204917E+10 | 0.250770E+09 | 0.179840E+10 | 0.357146E+10 | 0.113340E+10 |
June | 0.182084E+10 | 0.101658E+09 | 0.171918E+10 | 0.374443E+10 | 0.631023E+09 |
July | 0.188741E+10 | 0.127310E+09 | 0.176010E+10 | 0.405510E+10 | 0.405105E+09 |
August | 0.227424E+10 | 0.427422E+09 | 0.184682E+10 | 0.483007E+10 | 0.325165E+09 |
September | 0.248479E+10 | 0.966809E+09 | 0.151798E+10 | 0.448652E+10 | 0.879313E+09 |
October | 0.360543E+10 | 0.233034E+10 | 0.127509E+10 | 0.549059E+10 | 0.214833E+10 |
November | 0.381203E+10 | 0.254378E+10 | 0.126825E+10 | 0.518040E+10 | 0.282059E+10 |
December | 0.394868E+10 | 0.277776E+10 | 0.117092E+10 | 0.483341E+10 | 0.371723E+10 |
Annual Sum or Average | 0.350595E+11 | 0.171211E+11 | 0.179384E+11 | 0.535518E+11 | 0.240893E+11 |
Minimum of Months | 0.182084E+10 | 0.101658E+09 | 0.111368E+10 | 0.357146E+10 | 0.325165E+09 |
Maximum of Months | 0.397667E+10 | 0.277776E+10 | 0.184682E+10 | 0.549059E+10 | 0.445919E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.516592E+10 | 0.358863E+10 | 0.157729E+10 | 0.599171E+10 | 0.598322E+10 |
February | 0.434643E+10 | 0.289969E+10 | 0.144674E+10 | 0.553370E+10 | 0.449319E+10 |
March | 0.440039E+10 | 0.230912E+10 | 0.209126E+10 | 0.633966E+10 | 0.315455E+10 |
April | 0.320478E+10 | 0.106922E+10 | 0.213555E+10 | 0.526564E+10 | 0.238575E+10 |
May | 0.266199E+10 | 0.325764E+09 | 0.233623E+10 | 0.478573E+10 | 0.148394E+10 |
June | 0.236538E+10 | 0.132059E+09 | 0.223332E+10 | 0.501637E+10 | 0.813771E+09 |
July | 0.245185E+10 | 0.165382E+09 | 0.228647E+10 | 0.544297E+10 | 0.512244E+09 |
August | 0.295437E+10 | 0.555246E+09 | 0.239913E+10 | 0.650018E+10 | 0.387852E+09 |
September | 0.322789E+10 | 0.125594E+10 | 0.197195E+10 | 0.600603E+10 | 0.113137E+10 |
October | 0.468365E+10 | 0.302724E+10 | 0.165641E+10 | 0.734523E+10 | 0.281482E+10 |
November | 0.495204E+10 | 0.330451E+10 | 0.164753E+10 | 0.690390E+10 | 0.373778E+10 |
December | 0.512956E+10 | 0.360846E+10 | 0.152109E+10 | 0.642133E+10 | 0.496962E+10 |
Annual Sum or Average | 0.455443E+11 | 0.222413E+11 | 0.233030E+11 | 0.715525E+11 | 0.318681E+11 |
Minimum of Months | 0.236538E+10 | 0.132059E+09 | 0.144674E+10 | 0.478573E+10 | 0.387852E+09 |
Maximum of Months | 0.516592E+10 | 0.360846E+10 | 0.239913E+10 | 0.734523E+10 | 0.598322E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.279218E+09 | 0.193965E+09 | 85252967.91 | 0.313806E+09 | 0.339069E+09 |
February | 0.234924E+09 | 0.156728E+09 | 78196598.94 | 0.289006E+09 | 0.251936E+09 |
March | 0.237841E+09 | 0.124808E+09 | 0.113033E+09 | 0.327882E+09 | 0.171773E+09 |
April | 0.173219E+09 | 57791307.85 | 0.115427E+09 | 0.272884E+09 | 0.127349E+09 |
May | 0.143881E+09 | 17607483.41 | 0.126274E+09 | 0.250392E+09 | 72311415.75 |
June | 0.127849E+09 | 7137750.53 | 0.120712E+09 | 0.275053E+09 | 32327495.58 |
July | 0.132523E+09 | 8938883.07 | 0.123585E+09 | 0.304615E+09 | 15734821.82 |
August | 0.159684E+09 | 30010917.68 | 0.129673E+09 | 0.364898E+09 | 7819709.16 |
September | 0.174468E+09 | 67883271.16 | 0.106584E+09 | 0.323820E+09 | 47793209.24 |
October | 0.253151E+09 | 0.163622E+09 | 89529587.28 | 0.388334E+09 | 0.146297E+09 |
November | 0.267657E+09 | 0.178608E+09 | 89049108.36 | 0.363650E+09 | 0.202961E+09 |
December | 0.277252E+09 | 0.195037E+09 | 82215273.99 | 0.337044E+09 | 0.276677E+09 |
Annual Sum or Average | 0.246167E+10 | 0.120214E+10 | 0.125953E+10 | 0.381138E+10 | 0.169205E+10 |
Minimum of Months | 0.127849E+09 | 7137750.53 | 78196598.94 | 0.250392E+09 | 7819709.16 |
Maximum of Months | 0.279218E+09 | 0.195037E+09 | 0.129673E+09 | 0.388334E+09 | 0.339069E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222627E+09 | 0.103516E+09 | 0.119111E+09 | 0.165038E+09 | 0.718739E+09 |
February | 0.230374E+09 | 0.107973E+09 | 0.122401E+09 | 0.229048E+09 | 0.524317E+09 |
March | 0.374198E+09 | 0.180474E+09 | 0.193725E+09 | 0.472722E+09 | 0.333547E+09 |
April | 0.408065E+09 | 0.186640E+09 | 0.221425E+09 | 0.610087E+09 | 0.234523E+09 |
May | 0.424277E+09 | 0.161030E+09 | 0.263246E+09 | 0.713630E+09 | 0.133862E+09 |
June | 0.431370E+09 | 0.166096E+09 | 0.265273E+09 | 0.836064E+09 | 59995049.14 |
July | 0.419570E+09 | 0.155192E+09 | 0.264378E+09 | 0.857910E+09 | 29126891.25 |
August | 0.412124E+09 | 0.154141E+09 | 0.257983E+09 | 0.848965E+09 | 14567642.21 |
September | 0.325820E+09 | 0.136209E+09 | 0.189611E+09 | 0.572989E+09 | 89602133.13 |
October | 0.299566E+09 | 0.155754E+09 | 0.143812E+09 | 0.424842E+09 | 0.288972E+09 |
November | 0.230249E+09 | 0.102964E+09 | 0.127285E+09 | 0.260588E+09 | 0.419848E+09 |
December | 0.197060E+09 | 86321527.55 | 0.110739E+09 | 0.161940E+09 | 0.587962E+09 |
Annual Sum or Average | 0.397530E+10 | 0.169631E+10 | 0.227899E+10 | 0.615382E+10 | 0.343506E+10 |
Minimum of Months | 0.197060E+09 | 86321527.55 | 0.110739E+09 | 0.161940E+09 | 14567642.21 |
Maximum of Months | 0.431370E+09 | 0.186640E+09 | 0.265273E+09 | 0.857910E+09 | 0.718739E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52588594.07 | 0.00 | 52588594.07 | 7192498.17 | 0.406893E+09 |
February | 52648446.06 | 0.00 | 52648446.06 | 23420544.91 | 0.293245E+09 |
March | 81855013.60 | 1648.52 | 81853365.08 | 60591843.28 | 0.184970E+09 |
April | 96048332.89 | 560963.03 | 95487369.87 | 0.116519E+09 | 0.130563E+09 |
May | 0.118419E+09 | 3714011.78 | 0.114705E+09 | 0.185918E+09 | 73347809.10 |
June | 0.126039E+09 | 8265554.72 | 0.117773E+09 | 0.261676E+09 | 32235787.76 |
July | 0.123345E+09 | 6320378.90 | 0.117025E+09 | 0.277595E+09 | 17141584.00 |
August | 0.109554E+09 | 1287040.28 | 0.108267E+09 | 0.256938E+09 | 8683057.83 |
September | 80028430.11 | 31459.51 | 79996970.60 | 0.141155E+09 | 51867741.77 |
October | 62833545.17 | 0.00 | 62833545.17 | 64449958.75 | 0.158521E+09 |
November | 54419711.70 | 0.00 | 54419711.70 | 32372566.14 | 0.226828E+09 |
December | 48614241.33 | 0.00 | 48614241.33 | 8937405.24 | 0.323041E+09 |
Annual Sum or Average | 0.100639E+10 | 20181056.73 | 0.986211E+09 | 0.143677E+10 | 0.190734E+10 |
Minimum of Months | 48614241.33 | 0.00 | 48614241.33 | 7192498.17 | 8683057.83 |
Maximum of Months | 0.126039E+09 | 8265554.72 | 0.117773E+09 | 0.277595E+09 | 0.406893E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222627E+09 | 0.103516E+09 | 0.119111E+09 | 0.175207E+09 | 0.706173E+09 |
February | 0.230374E+09 | 0.107973E+09 | 0.122401E+09 | 0.237582E+09 | 0.516629E+09 |
March | 0.374198E+09 | 0.180474E+09 | 0.193725E+09 | 0.479443E+09 | 0.332276E+09 |
April | 0.408065E+09 | 0.186640E+09 | 0.221425E+09 | 0.609847E+09 | 0.241363E+09 |
May | 0.424277E+09 | 0.161030E+09 | 0.263246E+09 | 0.707131E+09 | 0.143668E+09 |
June | 0.431370E+09 | 0.166096E+09 | 0.265273E+09 | 0.828296E+09 | 64797039.86 |
July | 0.419570E+09 | 0.155192E+09 | 0.264378E+09 | 0.850205E+09 | 33075755.99 |
August | 0.412124E+09 | 0.154141E+09 | 0.257983E+09 | 0.845224E+09 | 16455849.49 |
September | 0.325820E+09 | 0.136209E+09 | 0.189611E+09 | 0.571940E+09 | 96008193.78 |
October | 0.299566E+09 | 0.155754E+09 | 0.143812E+09 | 0.431474E+09 | 0.289755E+09 |
November | 0.230249E+09 | 0.102964E+09 | 0.127285E+09 | 0.272319E+09 | 0.411987E+09 |
December | 0.197060E+09 | 86321527.55 | 0.110739E+09 | 0.173645E+09 | 0.575158E+09 |
Annual Sum or Average | 0.397530E+10 | 0.169631E+10 | 0.227899E+10 | 0.618231E+10 | 0.342735E+10 |
Minimum of Months | 0.197060E+09 | 86321527.55 | 0.110739E+09 | 0.173645E+09 | 16455849.49 |
Maximum of Months | 0.431370E+09 | 0.186640E+09 | 0.265273E+09 | 0.850205E+09 | 0.706173E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.223330E+09 | 0.155141E+09 | 68188813.41 | 0.234103E+09 | 0.302453E+09 |
February | 0.187902E+09 | 0.125357E+09 | 62544840.67 | 0.208117E+09 | 0.255665E+09 |
March | 0.190235E+09 | 99826196.68 | 90408627.06 | 0.223721E+09 | 0.214160E+09 |
April | 0.138547E+09 | 46223853.60 | 92323562.43 | 0.180797E+09 | 0.168204E+09 |
May | 0.115082E+09 | 14083185.96 | 0.100999E+09 | 0.158558E+09 | 0.116971E+09 |
June | 0.102259E+09 | 5709065.05 | 96550134.41 | 0.172577E+09 | 71152875.43 |
July | 0.105998E+09 | 7149684.58 | 98847981.78 | 0.191254E+09 | 54088354.71 |
August | 0.127722E+09 | 24003960.40 | 0.103718E+09 | 0.238108E+09 | 46773701.58 |
September | 0.139546E+09 | 54295818.95 | 85250458.26 | 0.218694E+09 | 95626972.54 |
October | 0.202481E+09 | 0.130871E+09 | 71609428.64 | 0.273597E+09 | 0.194283E+09 |
November | 0.214083E+09 | 0.142858E+09 | 71225121.93 | 0.253801E+09 | 0.243252E+09 |
December | 0.221757E+09 | 0.155998E+09 | 65759141.47 | 0.237273E+09 | 0.298886E+09 |
Annual Sum or Average | 0.196894E+10 | 0.961517E+09 | 0.100743E+10 | 0.259060E+10 | 0.206152E+10 |
Minimum of Months | 0.102259E+09 | 5709065.05 | 62544840.67 | 0.158558E+09 | 46773701.58 |
Maximum of Months | 0.223330E+09 | 0.155998E+09 | 0.103718E+09 | 0.273597E+09 | 0.302453E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 42076451.99 | 0.00 | 42076451.99 | 5201365.22 | 0.341593E+09 |
February | 42124339.93 | 0.00 | 42124339.93 | 18587407.70 | 0.244953E+09 |
March | 65492691.15 | 1318.99 | 65491372.16 | 50630160.12 | 0.149283E+09 |
April | 76848851.72 | 448829.91 | 76400021.81 | 97939717.13 | 0.103238E+09 |
May | 94747450.04 | 2971603.27 | 91775846.77 | 0.155730E+09 | 56534500.33 |
June | 0.100844E+09 | 6613320.29 | 94230889.24 | 0.219305E+09 | 22999594.73 |
July | 98689421.90 | 5056973.36 | 93632448.53 | 0.233400E+09 | 11609809.75 |
August | 87654522.95 | 1029768.70 | 86624754.24 | 0.218331E+09 | 5029408.33 |
September | 64031230.67 | 25170.94 | 64006059.72 | 0.119342E+09 | 39597070.69 |
October | 50273499.29 | 0.00 | 50273499.29 | 53885002.01 | 0.128497E+09 |
November | 43541540.27 | 0.00 | 43541540.27 | 25583965.20 | 0.188092E+09 |
December | 38896548.34 | 0.00 | 38896548.34 | 6048985.61 | 0.271958E+09 |
Annual Sum or Average | 0.805221E+09 | 16146985.47 | 0.789074E+09 | 0.120398E+10 | 0.156338E+10 |
Minimum of Months | 38896548.34 | 0.00 | 38896548.34 | 5201365.22 | 5029408.33 |
Maximum of Months | 0.100844E+09 | 6613320.29 | 94230889.24 | 0.233400E+09 | 0.341593E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.217269E+09 | 98926312.94 | 0.118343E+09 | 0.138290E+09 | 0.698720E+09 |
February | 0.246295E+09 | 0.132584E+09 | 0.113711E+09 | 0.227953E+09 | 0.496048E+09 |
March | 0.343073E+09 | 0.156492E+09 | 0.186581E+09 | 0.395175E+09 | 0.308739E+09 |
April | 0.401332E+09 | 0.183183E+09 | 0.218149E+09 | 0.580164E+09 | 0.215798E+09 |
May | 0.454306E+09 | 0.192122E+09 | 0.262184E+09 | 0.750529E+09 | 0.123047E+09 |
June | 0.454739E+09 | 0.190467E+09 | 0.264272E+09 | 0.870510E+09 | 54360136.91 |
July | 0.458002E+09 | 0.192153E+09 | 0.265848E+09 | 0.919956E+09 | 27969805.53 |
August | 0.419782E+09 | 0.166515E+09 | 0.253266E+09 | 0.863481E+09 | 13663364.32 |
September | 0.332940E+09 | 0.147113E+09 | 0.185827E+09 | 0.581951E+09 | 85073626.33 |
October | 0.294256E+09 | 0.153163E+09 | 0.141093E+09 | 0.394176E+09 | 0.268775E+09 |
November | 0.226791E+09 | 0.102303E+09 | 0.124488E+09 | 0.222317E+09 | 0.386438E+09 |
December | 0.203367E+09 | 92572432.32 | 0.110794E+09 | 0.139007E+09 | 0.553070E+09 |
Annual Sum or Average | 0.405215E+10 | 0.180759E+10 | 0.224456E+10 | 0.608351E+10 | 0.323170E+10 |
Minimum of Months | 0.203367E+09 | 92572432.32 | 0.110794E+09 | 0.138290E+09 | 13663364.32 |
Maximum of Months | 0.458002E+09 | 0.192153E+09 | 0.265848E+09 | 0.919956E+09 | 0.698720E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.279218E+09 | 0.193965E+09 | 85252967.91 | 0.312130E+09 | 0.338261E+09 |
February | 0.234924E+09 | 0.156728E+09 | 78196598.94 | 0.286469E+09 | 0.251408E+09 |
March | 0.237841E+09 | 0.124808E+09 | 0.113033E+09 | 0.325402E+09 | 0.170314E+09 |
April | 0.173219E+09 | 57791307.85 | 0.115427E+09 | 0.270355E+09 | 0.126524E+09 |
May | 0.143881E+09 | 17607483.41 | 0.126274E+09 | 0.247856E+09 | 71873874.86 |
June | 0.127849E+09 | 7137750.53 | 0.120712E+09 | 0.272971E+09 | 31920540.40 |
July | 0.132523E+09 | 8938883.07 | 0.123585E+09 | 0.302725E+09 | 15512764.48 |
August | 0.159684E+09 | 30010917.68 | 0.129673E+09 | 0.364013E+09 | 7543604.11 |
September | 0.174468E+09 | 67883271.16 | 0.106584E+09 | 0.322514E+09 | 47276166.23 |
October | 0.253151E+09 | 0.163622E+09 | 89529587.28 | 0.386180E+09 | 0.145282E+09 |
November | 0.267657E+09 | 0.178608E+09 | 89049108.36 | 0.361943E+09 | 0.202095E+09 |
December | 0.277252E+09 | 0.195037E+09 | 82215273.99 | 0.335361E+09 | 0.276122E+09 |
Annual Sum or Average | 0.246167E+10 | 0.120214E+10 | 0.125953E+10 | 0.378792E+10 | 0.168413E+10 |
Minimum of Months | 0.127849E+09 | 7137750.53 | 78196598.94 | 0.247856E+09 | 7543604.11 |
Maximum of Months | 0.279218E+09 | 0.195037E+09 | 0.129673E+09 | 0.386180E+09 | 0.338261E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52588594.07 | 0.00 | 52588594.07 | 6812118.02 | 0.407099E+09 |
February | 52648446.06 | 0.00 | 52648446.06 | 22423700.98 | 0.293692E+09 |
March | 81855013.60 | 1648.52 | 81853365.08 | 59495024.91 | 0.182958E+09 |
April | 96048332.89 | 560963.03 | 95487369.87 | 0.114185E+09 | 0.128903E+09 |
May | 0.118419E+09 | 3714011.78 | 0.114705E+09 | 0.182570E+09 | 72256294.67 |
June | 0.126039E+09 | 8265554.72 | 0.117773E+09 | 0.257978E+09 | 31624648.29 |
July | 0.123345E+09 | 6320378.90 | 0.117025E+09 | 0.274184E+09 | 17049359.74 |
August | 0.109554E+09 | 1287040.28 | 0.108267E+09 | 0.255142E+09 | 8370982.00 |
September | 80028430.11 | 31459.51 | 79996970.60 | 0.138938E+09 | 51254969.29 |
October | 62833545.17 | 0.00 | 62833545.17 | 62570257.53 | 0.156913E+09 |
November | 54419711.70 | 0.00 | 54419711.70 | 31844383.25 | 0.225470E+09 |
December | 48614241.33 | 0.00 | 48614241.33 | 8558609.32 | 0.323318E+09 |
Annual Sum or Average | 0.100639E+10 | 20181056.73 | 0.986211E+09 | 0.141470E+10 | 0.189891E+10 |
Minimum of Months | 48614241.33 | 0.00 | 48614241.33 | 6812118.02 | 8370982.00 |
Maximum of Months | 0.126039E+09 | 8265554.72 | 0.117773E+09 | 0.274184E+09 | 0.407099E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.217269E+09 | 98926312.94 | 0.118343E+09 | 0.143600E+09 | 0.680789E+09 |
February | 0.246295E+09 | 0.132584E+09 | 0.113711E+09 | 0.235369E+09 | 0.486103E+09 |
March | 0.343073E+09 | 0.156492E+09 | 0.186581E+09 | 0.403918E+09 | 0.305500E+09 |
April | 0.401332E+09 | 0.183183E+09 | 0.218149E+09 | 0.580990E+09 | 0.221395E+09 |
May | 0.454306E+09 | 0.192122E+09 | 0.262184E+09 | 0.742517E+09 | 0.131767E+09 |
June | 0.454739E+09 | 0.190467E+09 | 0.264272E+09 | 0.858741E+09 | 58501451.99 |
July | 0.458002E+09 | 0.192153E+09 | 0.265848E+09 | 0.908105E+09 | 31703068.58 |
August | 0.419782E+09 | 0.166515E+09 | 0.253266E+09 | 0.857188E+09 | 15219169.79 |
September | 0.332940E+09 | 0.147113E+09 | 0.185827E+09 | 0.578341E+09 | 90748725.40 |
October | 0.294256E+09 | 0.153163E+09 | 0.141093E+09 | 0.401420E+09 | 0.267867E+09 |
November | 0.226791E+09 | 0.102303E+09 | 0.124488E+09 | 0.234472E+09 | 0.375882E+09 |
December | 0.203367E+09 | 92572432.32 | 0.110794E+09 | 0.147059E+09 | 0.535734E+09 |
Annual Sum or Average | 0.405215E+10 | 0.180759E+10 | 0.224456E+10 | 0.609172E+10 | 0.320121E+10 |
Minimum of Months | 0.203367E+09 | 92572432.32 | 0.110794E+09 | 0.143600E+09 | 15219169.79 |
Maximum of Months | 0.458002E+09 | 0.192153E+09 | 0.265848E+09 | 0.908105E+09 | 0.680789E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 66600136.23 | 0.00 | 66600136.23 | 8781019.50 | 0.514853E+09 |
February | 66675935.00 | 0.00 | 66675935.00 | 31281568.21 | 0.365710E+09 |
March | 0.103664E+09 | 2087.74 | 0.103662E+09 | 87512844.44 | 0.218008E+09 |
April | 0.121639E+09 | 710424.28 | 0.120929E+09 | 0.164725E+09 | 0.150052E+09 |
May | 0.149970E+09 | 4703561.58 | 0.145266E+09 | 0.256545E+09 | 83602379.01 |
June | 0.159620E+09 | 10467803.52 | 0.149152E+09 | 0.342453E+09 | 40936374.41 |
July | 0.156209E+09 | 8004361.08 | 0.148205E+09 | 0.356068E+09 | 24440235.61 |
August | 0.138743E+09 | 1629955.30 | 0.137113E+09 | 0.326499E+09 | 14558189.52 |
September | 0.101351E+09 | 39841.48 | 0.101311E+09 | 0.189510E+09 | 63325357.70 |
October | 79574720.39 | 0.00 | 79574720.39 | 90649698.15 | 0.188490E+09 |
November | 68919131.17 | 0.00 | 68919131.17 | 44134455.42 | 0.277259E+09 |
December | 61566869.25 | 0.00 | 61566869.25 | 10521529.51 | 0.406850E+09 |
Annual Sum or Average | 0.127453E+10 | 25558034.99 | 0.124897E+10 | 0.190868E+10 | 0.234808E+10 |
Minimum of Months | 61566869.25 | 0.00 | 61566869.25 | 8781019.50 | 14558189.52 |
Maximum of Months | 0.159620E+09 | 10467803.52 | 0.149152E+09 | 0.356068E+09 | 0.514853E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 24551567.91 | 0.00 | 24551567.91 | 3237047.38 | 0.189796E+09 |
February | 24579510.47 | 0.00 | 24579510.47 | 11531681.31 | 0.134816E+09 |
March | 38214920.19 | 769.63 | 38214150.56 | 32260858.08 | 80366800.28 |
April | 44841228.59 | 261891.81 | 44579336.78 | 60724625.50 | 55315414.76 |
May | 55285042.92 | 1733927.56 | 53551115.36 | 94573034.44 | 30819298.60 |
June | 58842496.02 | 3858865.82 | 54983630.20 | 0.126242E+09 | 15090842.65 |
July | 57585179.58 | 2950738.93 | 54634440.65 | 0.131262E+09 | 9009682.84 |
August | 51146327.01 | 600869.02 | 50545457.99 | 0.120361E+09 | 5366751.46 |
September | 37362159.44 | 14687.22 | 37347472.22 | 69861246.85 | 23344348.95 |
October | 29334536.86 | 0.00 | 29334536.86 | 33417232.25 | 69485105.73 |
November | 25406445.47 | 0.00 | 25406445.47 | 16269787.73 | 0.102209E+09 |
December | 22696097.29 | 0.00 | 22696097.29 | 3878671.44 | 0.149982E+09 |
Annual Sum or Average | 0.469846E+09 | 9421749.97 | 0.460424E+09 | 0.703619E+09 | 0.865601E+09 |
Minimum of Months | 22696097.29 | 0.00 | 22696097.29 | 3237047.38 | 5366751.46 |
Maximum of Months | 58842496.02 | 3858865.82 | 54983630.20 | 0.131262E+09 | 0.189796E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.130282E+09 | 90503082.87 | 39778691.28 | 0.148246E+09 | 0.154732E+09 |
February | 0.109615E+09 | 73128454.63 | 36486217.96 | 0.137602E+09 | 0.114000E+09 |
March | 0.110976E+09 | 58234705.39 | 52740862.99 | 0.159355E+09 | 75059149.53 |
April | 80823152.87 | 26965191.36 | 53857961.51 | 0.133600E+09 | 55832882.69 |
May | 67134435.80 | 8215580.81 | 58918854.99 | 0.122716E+09 | 32650749.83 |
June | 59654024.21 | 3330445.64 | 56323578.57 | 0.130281E+09 | 16258531.23 |
July | 61834899.83 | 4170846.82 | 57664053.01 | 0.141679E+09 | 9338801.01 |
August | 74508055.00 | 14002973.25 | 60505081.75 | 0.169219E+09 | 5426763.33 |
September | 81405849.48 | 31674060.78 | 49731788.71 | 0.154215E+09 | 23153305.27 |
October | 0.118119E+09 | 76345167.07 | 41774144.65 | 0.186539E+09 | 64943572.87 |
November | 0.124888E+09 | 83337782.51 | 41549955.12 | 0.174293E+09 | 89982656.61 |
December | 0.129365E+09 | 91003310.47 | 38361315.54 | 0.159817E+09 | 0.125346E+09 |
Annual Sum or Average | 0.114860E+10 | 0.560912E+09 | 0.587693E+09 | 0.181756E+10 | 0.766725E+09 |
Minimum of Months | 59654024.21 | 3330445.64 | 36486217.96 | 0.122716E+09 | 5426763.33 |
Maximum of Months | 0.130282E+09 | 91003310.47 | 60505081.75 | 0.186539E+09 | 0.154732E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.353611E+09 | 0.245644E+09 | 0.107968E+09 | 0.402369E+09 | 0.419975E+09 |
February | 0.297517E+09 | 0.198486E+09 | 99031058.63 | 0.373481E+09 | 0.309420E+09 |
March | 0.301210E+09 | 0.158061E+09 | 0.143149E+09 | 0.432521E+09 | 0.203726E+09 |
April | 0.219371E+09 | 73189044.97 | 0.146182E+09 | 0.362617E+09 | 0.151542E+09 |
May | 0.182217E+09 | 22298766.77 | 0.159918E+09 | 0.333076E+09 | 88620813.61 |
June | 0.161913E+09 | 9039510.68 | 0.152874E+09 | 0.353608E+09 | 44128979.36 |
July | 0.167833E+09 | 11320531.40 | 0.156512E+09 | 0.384545E+09 | 25347416.14 |
August | 0.202230E+09 | 38006933.66 | 0.164223E+09 | 0.459296E+09 | 14729345.71 |
September | 0.220952E+09 | 85969879.73 | 0.134982E+09 | 0.418572E+09 | 62842806.41 |
October | 0.320600E+09 | 0.207216E+09 | 0.113384E+09 | 0.506304E+09 | 0.176270E+09 |
November | 0.338971E+09 | 0.226196E+09 | 0.112775E+09 | 0.473066E+09 | 0.244231E+09 |
December | 0.351122E+09 | 0.247002E+09 | 0.104120E+09 | 0.433777E+09 | 0.340215E+09 |
Annual Sum or Average | 0.311755E+10 | 0.152243E+10 | 0.159512E+10 | 0.493323E+10 | 0.208105E+10 |
Minimum of Months | 0.161913E+09 | 9039510.68 | 99031058.63 | 0.333076E+09 | 14729345.71 |
Maximum of Months | 0.353611E+09 | 0.247002E+09 | 0.164223E+09 | 0.506304E+09 | 0.419975E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.279218E+09 | 0.193965E+09 | 85252967.91 | 0.312454E+09 | 0.337650E+09 |
February | 0.234924E+09 | 0.156728E+09 | 78196598.94 | 0.286976E+09 | 0.250725E+09 |
March | 0.237841E+09 | 0.124808E+09 | 0.113033E+09 | 0.323806E+09 | 0.170929E+09 |
April | 0.173219E+09 | 57791307.85 | 0.115427E+09 | 0.268605E+09 | 0.127121E+09 |
May | 0.143881E+09 | 17607483.41 | 0.126274E+09 | 0.245890E+09 | 72142990.73 |
June | 0.127849E+09 | 7137750.53 | 0.120712E+09 | 0.271883E+09 | 31637108.81 |
July | 0.132523E+09 | 8938883.07 | 0.123585E+09 | 0.301476E+09 | 15102196.77 |
August | 0.159684E+09 | 30010917.68 | 0.129673E+09 | 0.361454E+09 | 7237945.77 |
September | 0.174468E+09 | 67883271.16 | 0.106584E+09 | 0.320275E+09 | 46954204.37 |
October | 0.253151E+09 | 0.163622E+09 | 89529587.28 | 0.384374E+09 | 0.145271E+09 |
November | 0.267657E+09 | 0.178608E+09 | 89049108.36 | 0.361128E+09 | 0.201436E+09 |
December | 0.277252E+09 | 0.195037E+09 | 82215273.99 | 0.335382E+09 | 0.274755E+09 |
Annual Sum or Average | 0.246167E+10 | 0.120214E+10 | 0.125953E+10 | 0.377370E+10 | 0.168096E+10 |
Minimum of Months | 0.127849E+09 | 7137750.53 | 78196598.94 | 0.245890E+09 | 7237945.77 |
Maximum of Months | 0.279218E+09 | 0.195037E+09 | 0.129673E+09 | 0.384374E+09 | 0.337650E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222627E+09 | 0.103516E+09 | 0.119111E+09 | 0.164516E+09 | 0.716094E+09 |
February | 0.230374E+09 | 0.107973E+09 | 0.122401E+09 | 0.226978E+09 | 0.521405E+09 |
March | 0.374198E+09 | 0.180474E+09 | 0.193725E+09 | 0.465681E+09 | 0.331479E+09 |
April | 0.408065E+09 | 0.186640E+09 | 0.221425E+09 | 0.600963E+09 | 0.233887E+09 |
May | 0.424277E+09 | 0.161030E+09 | 0.263246E+09 | 0.703244E+09 | 0.133420E+09 |
June | 0.431370E+09 | 0.166096E+09 | 0.265273E+09 | 0.826796E+09 | 58543277.69 |
July | 0.419570E+09 | 0.155192E+09 | 0.264378E+09 | 0.849813E+09 | 27906103.63 |
August | 0.412124E+09 | 0.154141E+09 | 0.257983E+09 | 0.841059E+09 | 13502123.32 |
September | 0.325820E+09 | 0.136209E+09 | 0.189611E+09 | 0.566450E+09 | 87866620.50 |
October | 0.299566E+09 | 0.155754E+09 | 0.143812E+09 | 0.419100E+09 | 0.286689E+09 |
November | 0.230249E+09 | 0.102964E+09 | 0.127285E+09 | 0.257752E+09 | 0.416738E+09 |
December | 0.197060E+09 | 86321527.55 | 0.110739E+09 | 0.161322E+09 | 0.583601E+09 |
Annual Sum or Average | 0.397530E+10 | 0.169631E+10 | 0.227899E+10 | 0.608367E+10 | 0.341113E+10 |
Minimum of Months | 0.197060E+09 | 86321527.55 | 0.110739E+09 | 0.161322E+09 | 13502123.32 |
Maximum of Months | 0.431370E+09 | 0.186640E+09 | 0.265273E+09 | 0.849813E+09 | 0.716094E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52588594.07 | 0.00 | 52588594.07 | 7447657.04 | 0.405680E+09 |
February | 52648446.06 | 0.00 | 52648446.06 | 23591170.31 | 0.292109E+09 |
March | 81855013.60 | 1648.52 | 81853365.08 | 59472915.38 | 0.184632E+09 |
April | 96048332.89 | 560963.03 | 95487369.87 | 0.113557E+09 | 0.131815E+09 |
May | 0.118419E+09 | 3714011.78 | 0.114705E+09 | 0.181521E+09 | 74554989.49 |
June | 0.126039E+09 | 8265554.72 | 0.117773E+09 | 0.258494E+09 | 31967607.54 |
July | 0.123345E+09 | 6320378.90 | 0.117025E+09 | 0.274522E+09 | 16846710.24 |
August | 0.109554E+09 | 1287040.28 | 0.108267E+09 | 0.254292E+09 | 8138918.89 |
September | 80028430.11 | 31459.51 | 79996970.60 | 0.138972E+09 | 51441758.70 |
October | 62833545.17 | 0.00 | 62833545.17 | 63450087.60 | 0.158107E+09 |
November | 54419711.70 | 0.00 | 54419711.70 | 32675828.45 | 0.224974E+09 |
December | 48614241.33 | 0.00 | 48614241.33 | 9561358.35 | 0.320286E+09 |
Annual Sum or Average | 0.100639E+10 | 20181056.73 | 0.986211E+09 | 0.141756E+10 | 0.190055E+10 |
Minimum of Months | 48614241.33 | 0.00 | 48614241.33 | 7447657.04 | 8138918.89 |
Maximum of Months | 0.126039E+09 | 8265554.72 | 0.117773E+09 | 0.274522E+09 | 0.405680E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222627E+09 | 0.103516E+09 | 0.119111E+09 | 0.174944E+09 | 0.704355E+09 |
February | 0.230374E+09 | 0.107973E+09 | 0.122401E+09 | 0.235809E+09 | 0.514358E+09 |
March | 0.374198E+09 | 0.180474E+09 | 0.193725E+09 | 0.472763E+09 | 0.330889E+09 |
April | 0.408065E+09 | 0.186640E+09 | 0.221425E+09 | 0.599761E+09 | 0.243117E+09 |
May | 0.424277E+09 | 0.161030E+09 | 0.263246E+09 | 0.695487E+09 | 0.145377E+09 |
June | 0.431370E+09 | 0.166096E+09 | 0.265273E+09 | 0.818585E+09 | 63925282.46 |
July | 0.419570E+09 | 0.155192E+09 | 0.264378E+09 | 0.841698E+09 | 32156032.02 |
August | 0.412124E+09 | 0.154141E+09 | 0.257983E+09 | 0.837076E+09 | 15401991.78 |
September | 0.325820E+09 | 0.136209E+09 | 0.189611E+09 | 0.565074E+09 | 95083790.66 |
October | 0.299566E+09 | 0.155754E+09 | 0.143812E+09 | 0.425980E+09 | 0.288461E+09 |
November | 0.230249E+09 | 0.102964E+09 | 0.127285E+09 | 0.270814E+09 | 0.408454E+09 |
December | 0.197060E+09 | 86321527.55 | 0.110739E+09 | 0.174240E+09 | 0.570974E+09 |
Annual Sum or Average | 0.397530E+10 | 0.169631E+10 | 0.227899E+10 | 0.611223E+10 | 0.341255E+10 |
Minimum of Months | 0.197060E+09 | 86321527.55 | 0.110739E+09 | 0.174240E+09 | 15401991.78 |
Maximum of Months | 0.431370E+09 | 0.186640E+09 | 0.265273E+09 | 0.841698E+09 | 0.704355E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.409499E+09 | 0.284468E+09 | 0.125032E+09 | 0.436123E+09 | 0.517268E+09 |
February | 0.344539E+09 | 0.229856E+09 | 0.114683E+09 | 0.405609E+09 | 0.383764E+09 |
March | 0.348816E+09 | 0.183042E+09 | 0.165774E+09 | 0.467193E+09 | 0.256096E+09 |
April | 0.254042E+09 | 84756499.22 | 0.169285E+09 | 0.394451E+09 | 0.185191E+09 |
May | 0.211016E+09 | 25823064.22 | 0.185193E+09 | 0.367338E+09 | 0.102388E+09 |
June | 0.187503E+09 | 10468196.17 | 0.177035E+09 | 0.409832E+09 | 43031870.27 |
July | 0.194358E+09 | 13109729.90 | 0.181249E+09 | 0.454439E+09 | 19797741.00 |
August | 0.234192E+09 | 44013890.93 | 0.190178E+09 | 0.541413E+09 | 9063997.13 |
September | 0.255873E+09 | 99557331.94 | 0.156316E+09 | 0.472466E+09 | 67674174.86 |
October | 0.371270E+09 | 0.239967E+09 | 0.131304E+09 | 0.556649E+09 | 0.219076E+09 |
November | 0.392545E+09 | 0.261946E+09 | 0.130599E+09 | 0.515258E+09 | 0.308735E+09 |
December | 0.406617E+09 | 0.286040E+09 | 0.120577E+09 | 0.471069E+09 | 0.423315E+09 |
Annual Sum or Average | 0.361027E+10 | 0.176305E+10 | 0.184722E+10 | 0.549184E+10 | 0.253540E+10 |
Minimum of Months | 0.187503E+09 | 10468196.17 | 0.114683E+09 | 0.367338E+09 | 9063997.13 |
Maximum of Months | 0.409499E+09 | 0.286040E+09 | 0.190178E+09 | 0.556649E+09 | 0.517268E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.368106E+09 | 0.00 | 0.368106E+09 | 39356133.70 | 0.305509E+10 |
February | 0.368525E+09 | 0.00 | 0.368525E+09 | 0.145605E+09 | 0.223611E+10 |
March | 0.572963E+09 | 11539.19 | 0.572952E+09 | 0.397243E+09 | 0.145230E+10 |
April | 0.672313E+09 | 3926592.47 | 0.668386E+09 | 0.784677E+09 | 0.103233E+10 |
May | 0.828899E+09 | 25997097.83 | 0.802902E+09 | 0.124681E+10 | 0.633797E+09 |
June | 0.882236E+09 | 57856691.74 | 0.824380E+09 | 0.172155E+10 | 0.336341E+09 |
July | 0.863385E+09 | 44240976.70 | 0.819144E+09 | 0.180161E+10 | 0.223866E+09 |
August | 0.766846E+09 | 9008940.72 | 0.757837E+09 | 0.164848E+10 | 0.167756E+09 |
September | 0.560178E+09 | 220208.23 | 0.559958E+09 | 0.931213E+09 | 0.494350E+09 |
October | 0.439818E+09 | 0.00 | 0.439818E+09 | 0.423052E+09 | 0.127415E+10 |
November | 0.380924E+09 | 0.00 | 0.380924E+09 | 0.195892E+09 | 0.176864E+10 |
December | 0.340287E+09 | 0.00 | 0.340287E+09 | 42904557.66 | 0.248598E+10 |
Annual Sum or Average | 0.704448E+10 | 0.141262E+09 | 0.690322E+10 | 0.937839E+10 | 0.151607E+11 |
Minimum of Months | 0.340287E+09 | 0.00 | 0.340287E+09 | 39356133.70 | 0.167756E+09 |
Maximum of Months | 0.882236E+09 | 57856691.74 | 0.824380E+09 | 0.180161E+10 | 0.305509E+10 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.368106E+09 | 0.00 | 0.368106E+09 | 34875965.26 | 0.313778E+10 |
February | 0.368525E+09 | 0.00 | 0.368525E+09 | 0.134081E+09 | 0.230919E+10 |
March | 0.572963E+09 | 11539.19 | 0.572952E+09 | 0.365691E+09 | 0.151994E+10 |
April | 0.672313E+09 | 3926592.47 | 0.668386E+09 | 0.744740E+09 | 0.107914E+10 |
May | 0.828899E+09 | 25997097.83 | 0.802902E+09 | 0.120176E+10 | 0.665560E+09 |
June | 0.882236E+09 | 57856691.74 | 0.824380E+09 | 0.168234E+10 | 0.355037E+09 |
July | 0.863385E+09 | 44240976.70 | 0.819144E+09 | 0.176435E+10 | 0.240041E+09 |
August | 0.766846E+09 | 9008940.72 | 0.757837E+09 | 0.161279E+10 | 0.183279E+09 |
September | 0.560178E+09 | 220208.23 | 0.559958E+09 | 0.894707E+09 | 0.527100E+09 |
October | 0.439818E+09 | 0.00 | 0.439818E+09 | 0.393908E+09 | 0.133913E+10 |
November | 0.380924E+09 | 0.00 | 0.380924E+09 | 0.174315E+09 | 0.184292E+10 |
December | 0.340287E+09 | 0.00 | 0.340287E+09 | 35922521.05 | 0.257456E+10 |
Annual Sum or Average | 0.704448E+10 | 0.141262E+09 | 0.690322E+10 | 0.903948E+10 | 0.157737E+11 |
Minimum of Months | 0.340287E+09 | 0.00 | 0.340287E+09 | 34875965.26 | 0.183279E+09 |
Maximum of Months | 0.882236E+09 | 57856691.74 | 0.824380E+09 | 0.176435E+10 | 0.313778E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52588594.07 | 0.00 | 52588594.07 | 6848284.83 | 0.427548E+09 |
February | 52648446.06 | 0.00 | 52648446.06 | 24213669.59 | 0.311618E+09 |
March | 81855013.60 | 1648.52 | 81853365.08 | 69340054.61 | 0.197564E+09 |
April | 96048332.89 | 560963.03 | 95487369.87 | 0.137108E+09 | 0.138032E+09 |
May | 0.118419E+09 | 3714011.78 | 0.114705E+09 | 0.217316E+09 | 84752855.58 |
June | 0.126039E+09 | 8265554.72 | 0.117773E+09 | 0.292890E+09 | 45773165.06 |
July | 0.123345E+09 | 6320378.90 | 0.117025E+09 | 0.310757E+09 | 29342115.90 |
August | 0.109554E+09 | 1287040.28 | 0.108267E+09 | 0.288026E+09 | 21215455.93 |
September | 80028430.11 | 31459.51 | 79996970.60 | 0.167376E+09 | 61321315.60 |
October | 62833545.17 | 0.00 | 62833545.17 | 76252093.24 | 0.169867E+09 |
November | 54419711.70 | 0.00 | 54419711.70 | 36183181.30 | 0.240284E+09 |
December | 48614241.33 | 0.00 | 48614241.33 | 7956890.42 | 0.344535E+09 |
Annual Sum or Average | 0.100639E+10 | 20181056.73 | 0.986211E+09 | 0.163427E+10 | 0.207185E+10 |
Minimum of Months | 48614241.33 | 0.00 | 48614241.33 | 6848284.83 | 21215455.93 |
Maximum of Months | 0.126039E+09 | 8265554.72 | 0.117773E+09 | 0.310757E+09 | 0.427548E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.434507E+09 | 0.197839E+09 | 0.236668E+09 | 0.290144E+09 | 0.143714E+10 |
February | 0.492555E+09 | 0.265149E+09 | 0.227406E+09 | 0.483458E+09 | 0.104416E+10 |
March | 0.686097E+09 | 0.312962E+09 | 0.373136E+09 | 0.856375E+09 | 0.674046E+09 |
April | 0.802608E+09 | 0.366340E+09 | 0.436268E+09 | 0.125619E+10 | 0.485316E+09 |
May | 0.908547E+09 | 0.384217E+09 | 0.524331E+09 | 0.161377E+10 | 0.313062E+09 |
June | 0.909412E+09 | 0.380907E+09 | 0.528506E+09 | 0.184934E+10 | 0.170658E+09 |
July | 0.915938E+09 | 0.384279E+09 | 0.531659E+09 | 0.194569E+10 | 0.110638E+09 |
August | 0.839504E+09 | 0.333007E+09 | 0.506497E+09 | 0.182892E+10 | 80022429.00 |
September | 0.665833E+09 | 0.294206E+09 | 0.371628E+09 | 0.126658E+10 | 0.224771E+09 |
October | 0.588469E+09 | 0.306304E+09 | 0.282165E+09 | 0.865109E+09 | 0.591485E+09 |
November | 0.453550E+09 | 0.204592E+09 | 0.248958E+09 | 0.493452E+09 | 0.807470E+09 |
December | 0.406705E+09 | 0.185132E+09 | 0.221573E+09 | 0.296008E+09 | 0.114918E+10 |
Annual Sum or Average | 0.810373E+10 | 0.361493E+10 | 0.448879E+10 | 0.130450E+11 | 0.708795E+10 |
Minimum of Months | 0.406705E+09 | 0.185132E+09 | 0.221573E+09 | 0.290144E+09 | 80022429.00 |
Maximum of Months | 0.915938E+09 | 0.384279E+09 | 0.531659E+09 | 0.194569E+10 | 0.143714E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.279218E+09 | 0.193965E+09 | 85252967.91 | 0.318871E+09 | 0.348588E+09 |
February | 0.234924E+09 | 0.156728E+09 | 78196598.94 | 0.295279E+09 | 0.264083E+09 |
March | 0.237841E+09 | 0.124808E+09 | 0.113033E+09 | 0.343656E+09 | 0.184801E+09 |
April | 0.173219E+09 | 57791307.85 | 0.115427E+09 | 0.294175E+09 | 0.138818E+09 |
May | 0.143881E+09 | 17607483.41 | 0.126274E+09 | 0.278215E+09 | 87853427.29 |
June | 0.127849E+09 | 7137750.53 | 0.120712E+09 | 0.302240E+09 | 47813918.36 |
July | 0.132523E+09 | 8938883.07 | 0.123585E+09 | 0.332502E+09 | 29754027.25 |
August | 0.159684E+09 | 30010917.68 | 0.129673E+09 | 0.392772E+09 | 21246157.60 |
September | 0.174468E+09 | 67883271.16 | 0.106584E+09 | 0.350455E+09 | 60547251.18 |
October | 0.253151E+09 | 0.163622E+09 | 89529587.28 | 0.407747E+09 | 0.158998E+09 |
November | 0.267657E+09 | 0.178608E+09 | 89049108.36 | 0.378261E+09 | 0.211982E+09 |
December | 0.277252E+09 | 0.195037E+09 | 82215273.99 | 0.343938E+09 | 0.288092E+09 |
Annual Sum or Average | 0.246167E+10 | 0.120214E+10 | 0.125953E+10 | 0.403811E+10 | 0.184258E+10 |
Minimum of Months | 0.127849E+09 | 7137750.53 | 78196598.94 | 0.278215E+09 | 21246157.60 |
Maximum of Months | 0.279218E+09 | 0.195037E+09 | 0.129673E+09 | 0.407747E+09 | 0.348588E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 66600136.23 | 0.00 | 66600136.23 | 8040108.21 | 0.524350E+09 |
February | 66675935.00 | 0.00 | 66675935.00 | 29077436.28 | 0.373154E+09 |
March | 0.103664E+09 | 2087.74 | 0.103662E+09 | 81251477.51 | 0.223593E+09 |
April | 0.121639E+09 | 710424.28 | 0.120929E+09 | 0.156134E+09 | 0.154355E+09 |
May | 0.149970E+09 | 4703561.58 | 0.145266E+09 | 0.243724E+09 | 89009580.98 |
June | 0.159620E+09 | 10467803.52 | 0.149152E+09 | 0.325533E+09 | 46631643.09 |
July | 0.156209E+09 | 8004361.08 | 0.148205E+09 | 0.335881E+09 | 29652019.61 |
August | 0.138743E+09 | 1629955.30 | 0.137113E+09 | 0.305643E+09 | 20266365.31 |
September | 0.101351E+09 | 39841.48 | 0.101311E+09 | 0.180586E+09 | 66443481.99 |
October | 79574720.39 | 0.00 | 79574720.39 | 84910610.11 | 0.193151E+09 |
November | 68919131.17 | 0.00 | 68919131.17 | 40406548.60 | 0.283624E+09 |
December | 61566869.25 | 0.00 | 61566869.25 | 9154660.22 | 0.415553E+09 |
Annual Sum or Average | 0.127453E+10 | 25558034.99 | 0.124897E+10 | 0.180034E+10 | 0.241978E+10 |
Minimum of Months | 61566869.25 | 0.00 | 61566869.25 | 8040108.21 | 20266365.31 |
Maximum of Months | 0.159620E+09 | 10467803.52 | 0.149152E+09 | 0.335881E+09 | 0.524350E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 59587394.23 | 0.00 | 59587394.23 | 7193515.28 | 0.469129E+09 |
February | 59655211.68 | 0.00 | 59655211.68 | 26015692.42 | 0.333863E+09 |
March | 92748761.43 | 1867.91 | 92746893.52 | 72696004.79 | 0.200050E+09 |
April | 0.108831E+09 | 635619.29 | 0.108195E+09 | 0.139693E+09 | 0.138102E+09 |
May | 0.134178E+09 | 4208294.36 | 0.129970E+09 | 0.218061E+09 | 79637209.36 |
June | 0.142813E+09 | 9365583.47 | 0.133447E+09 | 0.291256E+09 | 41721507.76 |
July | 0.139761E+09 | 7161532.19 | 0.132599E+09 | 0.300514E+09 | 26529774.30 |
August | 0.124134E+09 | 1458327.18 | 0.122675E+09 | 0.273460E+09 | 18132393.83 |
September | 90679085.44 | 35646.33 | 90643439.12 | 0.161571E+09 | 59447235.09 |
October | 71195803.84 | 0.00 | 71195803.84 | 75969844.59 | 0.172813E+09 |
November | 61662207.79 | 0.00 | 61662207.79 | 36151892.13 | 0.253757E+09 |
December | 55084111.20 | 0.00 | 55084111.20 | 8190709.18 | 0.371782E+09 |
Annual Sum or Average | 0.114033E+10 | 22866870.75 | 0.111746E+10 | 0.161077E+10 | 0.216496E+10 |
Minimum of Months | 55084111.20 | 0.00 | 55084111.20 | 7193515.28 | 18132393.83 |
Maximum of Months | 0.142813E+09 | 9365583.47 | 0.133447E+09 | 0.300514E+09 | 0.469129E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.104240E+10 | 0.724128E+09 | 0.318275E+09 | 0.116486E+10 | 0.125512E+10 |
February | 0.877042E+09 | 0.585111E+09 | 0.291931E+09 | 0.107997E+10 | 0.929334E+09 |
March | 0.887931E+09 | 0.465944E+09 | 0.421987E+09 | 0.124434E+10 | 0.615283E+09 |
April | 0.646677E+09 | 0.215752E+09 | 0.430925E+09 | 0.103750E+10 | 0.460515E+09 |
May | 0.537152E+09 | 65733982.34 | 0.471418E+09 | 0.942125E+09 | 0.278950E+09 |
June | 0.477300E+09 | 26647349.68 | 0.450653E+09 | 0.992278E+09 | 0.148403E+09 |
July | 0.494749E+09 | 33371514.17 | 0.461378E+09 | 0.107356E+10 | 91402092.68 |
August | 0.596149E+09 | 0.112040E+09 | 0.484109E+09 | 0.128913E+10 | 61182807.48 |
September | 0.651339E+09 | 0.253428E+09 | 0.397911E+09 | 0.120221E+10 | 0.195573E+09 |
October | 0.945089E+09 | 0.610848E+09 | 0.334241E+09 | 0.146406E+10 | 0.532458E+09 |
November | 0.999244E+09 | 0.666797E+09 | 0.332447E+09 | 0.137035E+10 | 0.734560E+09 |
December | 0.103506E+10 | 0.728130E+09 | 0.306934E+09 | 0.125576E+10 | 0.102033E+10 |
Annual Sum or Average | 0.919014E+10 | 0.448793E+10 | 0.470221E+10 | 0.141161E+11 | 0.632311E+10 |
Minimum of Months | 0.477300E+09 | 26647349.68 | 0.291931E+09 | 0.942125E+09 | 61182807.48 |
Maximum of Months | 0.104240E+10 | 0.728130E+09 | 0.484109E+09 | 0.146406E+10 | 0.125512E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 606.49 | 579.17 | 527.26 | 366.27 | 160.99 | 0.00 | 0.00 |
February | 617.78 | 477.34 | 491.15 | 327.66 | 163.48 | 0.00 | 0.00 |
March | 636.60 | 296.09 | 449.12 | 235.68 | 213.44 | 0.00 | 0.00 |
April | 546.28 | 227.82 | 338.00 | 112.77 | 225.23 | 0.00 | 0.00 |
May | 481.92 | 130.53 | 271.69 | 33.25 | 238.45 | 0.00 | 0.00 |
June | 519.33 | 71.43 | 249.47 | 13.93 | 235.54 | 0.00 | 0.00 |
July | 541.58 | 41.48 | 250.25 | 16.88 | 233.37 | 0.00 | 0.00 |
August | 642.06 | 31.90 | 301.54 | 56.67 | 244.87 | 0.00 | 0.00 |
September | 621.54 | 101.24 | 340.43 | 132.46 | 207.97 | 0.00 | 0.00 |
October | 735.12 | 261.63 | 478.03 | 308.97 | 169.06 | 0.00 | 0.00 |
November | 717.26 | 365.34 | 522.27 | 348.52 | 173.76 | 0.00 | 0.00 |
December | 648.06 | 476.79 | 523.54 | 368.30 | 155.25 | 0.00 | 0.00 |
Annual Sum or Average | 609.52 | 253.93 | 394.80 | 192.80 | 202.00 | 0.00 | 0.00 |
Minimum of Months | 481.92 | 31.90 | 249.47 | 13.93 | 155.25 | 0.00 | 0.00 |
Maximum of Months | 735.12 | 579.17 | 527.26 | 368.30 | 244.87 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1688.92 | 1664.87 | 1484.72 | 1031.40 | 453.32 | 0.00 | 0.00 |
February | 1720.50 | 1390.96 | 1383.03 | 922.68 | 460.35 | 0.00 | 0.00 |
March | 1770.18 | 895.29 | 1264.70 | 663.66 | 601.04 | 0.00 | 0.00 |
April | 1517.27 | 697.14 | 951.78 | 317.55 | 634.23 | 0.00 | 0.00 |
May | 1333.43 | 423.16 | 765.07 | 93.63 | 671.45 | 0.00 | 0.00 |
June | 1444.61 | 243.45 | 702.49 | 39.22 | 663.27 | 0.00 | 0.00 |
July | 1514.00 | 151.25 | 704.68 | 47.53 | 657.15 | 0.00 | 0.00 |
August | 1803.34 | 121.40 | 849.11 | 159.58 | 689.52 | 0.00 | 0.00 |
September | 1730.91 | 339.24 | 958.64 | 373.00 | 585.64 | 0.00 | 0.00 |
October | 2049.95 | 802.10 | 1346.11 | 870.05 | 476.06 | 0.00 | 0.00 |
November | 1998.61 | 1088.19 | 1470.69 | 981.40 | 489.29 | 0.00 | 0.00 |
December | 1804.59 | 1387.86 | 1474.27 | 1037.10 | 437.17 | 0.00 | 0.00 |
Annual Sum or Average | 1698.12 | 763.87 | 1111.73 | 542.91 | 568.82 | 0.00 | 0.00 |
Minimum of Months | 1333.43 | 121.40 | 702.49 | 39.22 | 437.17 | 0.00 | 0.00 |
Maximum of Months | 2049.95 | 1664.87 | 1484.72 | 1037.10 | 689.52 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2237.05 | 2233.88 | 1928.74 | 1339.84 | 588.89 | 0.00 | 0.00 |
February | 2287.41 | 1857.31 | 1796.64 | 1198.62 | 598.02 | 0.00 | 0.00 |
March | 2366.96 | 1177.77 | 1642.92 | 862.13 | 780.79 | 0.00 | 0.00 |
April | 2031.50 | 920.43 | 1236.41 | 412.51 | 823.90 | 0.00 | 0.00 |
May | 1786.79 | 554.04 | 993.87 | 121.63 | 872.25 | 0.00 | 0.00 |
June | 1935.33 | 313.95 | 912.57 | 50.95 | 861.62 | 0.00 | 0.00 |
July | 2032.17 | 191.25 | 915.42 | 61.75 | 853.67 | 0.00 | 0.00 |
August | 2426.89 | 144.81 | 1103.04 | 207.31 | 895.73 | 0.00 | 0.00 |
September | 2317.14 | 436.49 | 1245.33 | 484.54 | 760.78 | 0.00 | 0.00 |
October | 2742.39 | 1050.93 | 1748.68 | 1130.24 | 618.43 | 0.00 | 0.00 |
November | 2663.54 | 1442.05 | 1910.51 | 1274.89 | 635.62 | 0.00 | 0.00 |
December | 2397.45 | 1855.44 | 1915.16 | 1347.25 | 567.91 | 0.00 | 0.00 |
Annual Sum or Average | 2268.91 | 1010.53 | 1444.20 | 705.27 | 738.93 | 0.00 | 0.00 |
Minimum of Months | 1786.79 | 144.81 | 912.57 | 50.95 | 567.91 | 0.00 | 0.00 |
Maximum of Months | 2742.39 | 2233.88 | 1928.74 | 1347.25 | 895.73 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 158.85 | 375.01 | 187.37 | 111.07 | 76.30 | 0.00 | 0.00 |
February | 199.41 | 306.14 | 192.34 | 109.42 | 82.92 | 0.00 | 0.00 |
March | 294.88 | 184.63 | 228.51 | 113.98 | 114.53 | 0.00 | 0.00 |
April | 339.29 | 138.25 | 224.26 | 94.30 | 129.96 | 0.00 | 0.00 |
May | 359.73 | 76.78 | 212.13 | 66.70 | 145.43 | 0.00 | 0.00 |
June | 428.64 | 35.59 | 215.75 | 66.83 | 148.91 | 0.00 | 0.00 |
July | 434.02 | 16.74 | 206.13 | 61.28 | 144.85 | 0.00 | 0.00 |
August | 453.20 | 8.36 | 213.49 | 68.75 | 144.73 | 0.00 | 0.00 |
September | 345.86 | 52.88 | 193.01 | 78.74 | 114.27 | 0.00 | 0.00 |
October | 300.43 | 159.33 | 206.36 | 119.24 | 87.12 | 0.00 | 0.00 |
November | 232.21 | 231.66 | 192.09 | 108.63 | 83.46 | 0.00 | 0.00 |
December | 170.01 | 306.54 | 177.09 | 105.05 | 72.04 | 0.00 | 0.00 |
Annual Sum or Average | 310.33 | 156.91 | 204.11 | 91.91 | 112.21 | 0.00 | 0.00 |
Minimum of Months | 158.85 | 8.36 | 177.09 | 61.28 | 72.04 | 0.00 | 0.00 |
Maximum of Months | 453.20 | 375.01 | 228.51 | 119.24 | 148.91 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 59.64 | 407.11 | 102.75 | 38.65 | 64.11 | 0.00 | 0.00 |
February | 102.03 | 328.91 | 116.99 | 44.63 | 72.36 | 0.00 | 0.00 |
March | 199.50 | 191.00 | 170.27 | 67.38 | 102.89 | 0.00 | 0.00 |
April | 279.16 | 142.42 | 194.49 | 72.22 | 122.27 | 0.00 | 0.00 |
May | 332.80 | 80.40 | 202.62 | 61.51 | 141.11 | 0.00 | 0.00 |
June | 419.73 | 36.66 | 215.05 | 67.27 | 147.78 | 0.00 | 0.00 |
July | 420.73 | 18.40 | 202.70 | 60.30 | 142.40 | 0.00 | 0.00 |
August | 411.43 | 9.31 | 194.77 | 58.03 | 136.74 | 0.00 | 0.00 |
September | 275.00 | 56.94 | 156.58 | 52.56 | 104.02 | 0.00 | 0.00 |
October | 183.94 | 166.15 | 135.30 | 58.15 | 77.15 | 0.00 | 0.00 |
November | 115.69 | 244.60 | 109.83 | 39.72 | 70.10 | 0.00 | 0.00 |
December | 63.85 | 331.03 | 91.72 | 32.23 | 59.50 | 0.00 | 0.00 |
Annual Sum or Average | 239.38 | 166.94 | 157.97 | 54.43 | 103.54 | 0.00 | 0.00 |
Minimum of Months | 59.64 | 9.31 | 91.72 | 32.23 | 59.50 | 0.00 | 0.00 |
Maximum of Months | 420.73 | 407.11 | 215.05 | 72.22 | 147.78 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 87.40 | 112.92 | 83.38 | 57.92 | 25.46 | 0.00 | 0.00 |
February | 86.03 | 105.68 | 77.67 | 51.82 | 25.85 | 0.00 | 0.00 |
March | 83.53 | 79.96 | 71.03 | 37.27 | 33.75 | 0.00 | 0.00 |
April | 69.75 | 64.89 | 53.45 | 17.83 | 35.62 | 0.00 | 0.00 |
May | 59.20 | 43.67 | 42.97 | 5.26 | 37.71 | 0.00 | 0.00 |
June | 66.58 | 27.45 | 39.45 | 2.20 | 37.25 | 0.00 | 0.00 |
July | 71.41 | 20.19 | 39.57 | 2.67 | 36.91 | 0.00 | 0.00 |
August | 88.90 | 17.46 | 47.69 | 8.96 | 38.72 | 0.00 | 0.00 |
September | 84.37 | 36.89 | 53.84 | 20.95 | 32.89 | 0.00 | 0.00 |
October | 102.15 | 72.54 | 75.60 | 48.86 | 26.74 | 0.00 | 0.00 |
November | 97.92 | 93.85 | 82.59 | 55.11 | 27.48 | 0.00 | 0.00 |
December | 88.59 | 111.59 | 82.79 | 58.24 | 24.55 | 0.00 | 0.00 |
Annual Sum or Average | 82.15 | 65.37 | 62.43 | 30.49 | 31.95 | 0.00 | 0.00 |
Minimum of Months | 59.20 | 17.46 | 39.45 | 2.20 | 24.55 | 0.00 | 0.00 |
Maximum of Months | 102.15 | 112.92 | 83.38 | 58.24 | 38.72 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1.94 | 127.54 | 15.71 | 0.00 | 15.71 | 0.00 | 0.00 |
February | 7.68 | 101.25 | 17.41 | 0.00 | 17.41 | 0.00 | 0.00 |
March | 18.90 | 55.74 | 24.45 | 0.00 | 24.45 | 0.00 | 0.00 |
April | 37.79 | 39.83 | 29.65 | 0.17 | 29.48 | 0.00 | 0.00 |
May | 58.14 | 21.11 | 35.37 | 1.11 | 34.27 | 0.00 | 0.00 |
June | 84.61 | 8.87 | 38.91 | 2.55 | 36.35 | 0.00 | 0.00 |
July | 87.14 | 4.33 | 36.85 | 1.89 | 34.96 | 0.00 | 0.00 |
August | 81.52 | 1.88 | 32.73 | 0.38 | 32.34 | 0.00 | 0.00 |
September | 46.04 | 15.28 | 24.70 | 0.01 | 24.69 | 0.00 | 0.00 |
October | 20.12 | 47.98 | 18.77 | 0.00 | 18.77 | 0.00 | 0.00 |
November | 9.87 | 72.57 | 16.80 | 0.00 | 16.80 | 0.00 | 0.00 |
December | 2.26 | 101.54 | 14.52 | 0.00 | 14.52 | 0.00 | 0.00 |
Annual Sum or Average | 38.18 | 49.57 | 25.53 | 0.51 | 25.02 | 0.00 | 0.00 |
Minimum of Months | 1.94 | 1.88 | 14.52 | 0.00 | 14.52 | 0.00 | 0.00 |
Maximum of Months | 87.14 | 127.54 | 38.91 | 2.55 | 36.35 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 150.52 | 369.51 | 185.37 | 109.35 | 76.01 | 0.00 | 0.00 |
February | 202.76 | 299.09 | 198.92 | 119.59 | 79.33 | 0.00 | 0.00 |
March | 265.73 | 175.56 | 216.89 | 105.03 | 111.86 | 0.00 | 0.00 |
April | 324.39 | 128.33 | 221.66 | 92.97 | 128.69 | 0.00 | 0.00 |
May | 370.93 | 70.95 | 223.34 | 78.30 | 145.03 | 0.00 | 0.00 |
June | 440.21 | 32.34 | 224.76 | 76.24 | 148.53 | 0.00 | 0.00 |
July | 456.33 | 16.06 | 220.48 | 75.08 | 145.40 | 0.00 | 0.00 |
August | 458.23 | 7.85 | 216.35 | 73.37 | 142.97 | 0.00 | 0.00 |
September | 348.37 | 50.49 | 195.76 | 82.95 | 112.81 | 0.00 | 0.00 |
October | 289.47 | 152.71 | 204.38 | 118.27 | 86.10 | 0.00 | 0.00 |
November | 221.98 | 223.62 | 190.76 | 108.38 | 82.38 | 0.00 | 0.00 |
December | 167.01 | 299.48 | 179.44 | 107.38 | 72.06 | 0.00 | 0.00 |
Annual Sum or Average | 308.58 | 151.44 | 206.55 | 95.44 | 111.11 | 0.00 | 0.00 |
Minimum of Months | 150.52 | 7.85 | 179.44 | 73.37 | 72.06 | 0.00 | 0.00 |
Maximum of Months | 458.23 | 369.51 | 224.76 | 119.59 | 148.53 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 44.36 | 394.37 | 100.75 | 36.93 | 63.82 | 0.00 | 0.00 |
February | 94.96 | 310.73 | 123.57 | 54.80 | 68.77 | 0.00 | 0.00 |
March | 166.87 | 176.22 | 158.65 | 58.43 | 100.22 | 0.00 | 0.00 |
April | 264.46 | 131.40 | 191.89 | 70.89 | 121.00 | 0.00 | 0.00 |
May | 344.66 | 75.44 | 213.83 | 73.12 | 140.71 | 0.00 | 0.00 |
June | 430.69 | 34.63 | 224.07 | 76.67 | 147.39 | 0.00 | 0.00 |
July | 441.40 | 18.19 | 217.05 | 74.10 | 142.95 | 0.00 | 0.00 |
August | 415.27 | 8.78 | 197.63 | 62.65 | 134.98 | 0.00 | 0.00 |
September | 275.90 | 53.95 | 159.32 | 56.77 | 102.56 | 0.00 | 0.00 |
October | 168.69 | 154.05 | 133.32 | 57.18 | 76.14 | 0.00 | 0.00 |
November | 95.45 | 224.71 | 108.49 | 39.47 | 69.02 | 0.00 | 0.00 |
December | 47.49 | 310.13 | 94.08 | 34.56 | 59.52 | 0.00 | 0.00 |
Annual Sum or Average | 233.27 | 156.97 | 160.41 | 57.96 | 102.45 | 0.00 | 0.00 |
Minimum of Months | 44.36 | 8.78 | 94.08 | 34.56 | 59.52 | 0.00 | 0.00 |
Maximum of Months | 441.40 | 394.37 | 224.07 | 76.67 | 147.39 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 177.43 | 445.02 | 214.70 | 125.50 | 89.19 | 0.00 | 0.00 |
February | 208.08 | 361.05 | 206.01 | 112.27 | 93.74 | 0.00 | 0.00 |
March | 262.25 | 212.04 | 206.86 | 80.76 | 126.11 | 0.00 | 0.00 |
April | 278.06 | 158.88 | 180.04 | 39.01 | 141.03 | 0.00 | 0.00 |
May | 300.58 | 87.31 | 169.73 | 13.80 | 155.93 | 0.00 | 0.00 |
June | 366.63 | 44.03 | 169.76 | 10.30 | 159.46 | 0.00 | 0.00 |
July | 378.06 | 25.08 | 165.57 | 9.87 | 155.70 | 0.00 | 0.00 |
August | 401.43 | 14.90 | 174.22 | 20.25 | 153.97 | 0.00 | 0.00 |
September | 320.98 | 66.54 | 170.17 | 45.41 | 124.76 | 0.00 | 0.00 |
October | 301.66 | 183.04 | 204.46 | 105.87 | 98.59 | 0.00 | 0.00 |
November | 262.48 | 264.76 | 215.35 | 119.42 | 95.93 | 0.00 | 0.00 |
December | 204.14 | 358.86 | 210.85 | 126.20 | 84.66 | 0.00 | 0.00 |
Annual Sum or Average | 288.94 | 184.25 | 190.59 | 67.17 | 123.42 | 0.00 | 0.00 |
Minimum of Months | 177.43 | 14.90 | 165.57 | 9.87 | 84.66 | 0.00 | 0.00 |
Maximum of Months | 401.43 | 445.02 | 215.35 | 126.20 | 159.46 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 158.44 | 373.78 | 187.37 | 111.07 | 76.30 | 0.00 | 0.00 |
February | 197.94 | 304.66 | 192.34 | 109.42 | 82.92 | 0.00 | 0.00 |
March | 290.76 | 183.58 | 228.51 | 113.98 | 114.53 | 0.00 | 0.00 |
April | 334.07 | 137.87 | 224.26 | 94.30 | 129.96 | 0.00 | 0.00 |
May | 354.15 | 76.54 | 212.13 | 66.70 | 145.43 | 0.00 | 0.00 |
June | 423.84 | 34.76 | 215.75 | 66.83 | 148.91 | 0.00 | 0.00 |
July | 429.83 | 16.04 | 206.13 | 61.28 | 144.85 | 0.00 | 0.00 |
August | 448.97 | 7.74 | 213.49 | 68.75 | 144.73 | 0.00 | 0.00 |
September | 341.97 | 51.88 | 193.01 | 78.74 | 114.27 | 0.00 | 0.00 |
October | 296.85 | 158.15 | 206.36 | 119.24 | 87.12 | 0.00 | 0.00 |
November | 230.36 | 230.09 | 192.09 | 108.63 | 83.46 | 0.00 | 0.00 |
December | 169.46 | 304.48 | 177.09 | 105.05 | 72.04 | 0.00 | 0.00 |
Annual Sum or Average | 306.99 | 155.89 | 204.11 | 91.91 | 112.21 | 0.00 | 0.00 |
Minimum of Months | 158.44 | 7.74 | 177.09 | 61.28 | 72.04 | 0.00 | 0.00 |
Maximum of Months | 448.97 | 373.78 | 228.51 | 119.24 | 148.91 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 59.91 | 406.25 | 102.75 | 38.65 | 64.11 | 0.00 | 0.00 |
February | 101.47 | 327.61 | 116.99 | 44.63 | 72.36 | 0.00 | 0.00 |
March | 196.52 | 190.28 | 170.27 | 67.38 | 102.89 | 0.00 | 0.00 |
April | 274.02 | 143.47 | 194.49 | 72.22 | 122.27 | 0.00 | 0.00 |
May | 326.80 | 81.48 | 202.62 | 61.51 | 141.11 | 0.00 | 0.00 |
June | 414.80 | 36.26 | 215.05 | 67.27 | 147.78 | 0.00 | 0.00 |
July | 416.44 | 17.99 | 202.70 | 60.30 | 142.40 | 0.00 | 0.00 |
August | 407.41 | 8.73 | 194.77 | 58.03 | 136.74 | 0.00 | 0.00 |
September | 271.49 | 56.40 | 156.58 | 52.56 | 104.02 | 0.00 | 0.00 |
October | 181.45 | 165.45 | 135.30 | 58.15 | 77.15 | 0.00 | 0.00 |
November | 115.28 | 242.58 | 109.83 | 39.72 | 70.10 | 0.00 | 0.00 |
December | 64.56 | 328.69 | 91.72 | 32.23 | 59.50 | 0.00 | 0.00 |
Annual Sum or Average | 236.59 | 166.30 | 157.97 | 54.43 | 103.54 | 0.00 | 0.00 |
Minimum of Months | 59.91 | 8.73 | 91.72 | 32.23 | 59.50 | 0.00 | 0.00 |
Maximum of Months | 416.44 | 406.25 | 215.05 | 72.22 | 147.78 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 162.83 | 193.13 | 152.89 | 106.21 | 46.68 | 0.00 | 0.00 |
February | 167.66 | 158.63 | 142.42 | 95.01 | 47.41 | 0.00 | 0.00 |
March | 174.43 | 95.62 | 130.23 | 68.34 | 61.89 | 0.00 | 0.00 |
April | 152.18 | 71.45 | 98.01 | 32.70 | 65.31 | 0.00 | 0.00 |
May | 137.15 | 38.23 | 78.78 | 9.64 | 69.14 | 0.00 | 0.00 |
June | 158.11 | 16.60 | 72.34 | 4.04 | 68.30 | 0.00 | 0.00 |
July | 169.67 | 7.39 | 72.57 | 4.89 | 67.67 | 0.00 | 0.00 |
August | 202.14 | 3.38 | 87.44 | 16.43 | 71.00 | 0.00 | 0.00 |
September | 182.28 | 26.11 | 98.72 | 38.41 | 60.31 | 0.00 | 0.00 |
October | 207.83 | 81.79 | 138.62 | 89.59 | 49.02 | 0.00 | 0.00 |
November | 198.79 | 119.11 | 151.44 | 101.06 | 50.39 | 0.00 | 0.00 |
December | 175.88 | 158.05 | 151.81 | 106.80 | 45.02 | 0.00 | 0.00 |
Annual Sum or Average | 174.15 | 80.40 | 114.48 | 55.91 | 58.58 | 0.00 | 0.00 |
Minimum of Months | 137.15 | 3.38 | 72.34 | 4.04 | 45.02 | 0.00 | 0.00 |
Maximum of Months | 207.83 | 193.13 | 152.89 | 106.80 | 71.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 14.69 | 1140.64 | 137.44 | 0.00 | 137.44 | 0.00 | 0.00 |
February | 60.19 | 924.32 | 152.33 | 0.00 | 152.33 | 0.00 | 0.00 |
March | 148.31 | 542.23 | 213.92 | 0.00 | 213.92 | 0.00 | 0.00 |
April | 302.73 | 398.27 | 259.38 | 1.51 | 257.87 | 0.00 | 0.00 |
May | 465.51 | 236.63 | 309.48 | 9.71 | 299.77 | 0.00 | 0.00 |
June | 664.18 | 129.76 | 340.37 | 22.32 | 318.05 | 0.00 | 0.00 |
July | 672.64 | 83.58 | 322.35 | 16.52 | 305.83 | 0.00 | 0.00 |
August | 615.47 | 62.63 | 286.31 | 3.36 | 282.94 | 0.00 | 0.00 |
September | 359.26 | 190.72 | 216.12 | 0.08 | 216.03 | 0.00 | 0.00 |
October | 157.95 | 475.71 | 164.21 | 0.00 | 164.21 | 0.00 | 0.00 |
November | 75.58 | 682.34 | 146.96 | 0.00 | 146.96 | 0.00 | 0.00 |
December | 16.02 | 928.16 | 127.05 | 0.00 | 127.05 | 0.00 | 0.00 |
Annual Sum or Average | 297.39 | 480.74 | 223.38 | 4.48 | 218.90 | 0.00 | 0.00 |
Minimum of Months | 14.69 | 62.63 | 127.05 | 0.00 | 127.05 | 0.00 | 0.00 |
Maximum of Months | 672.64 | 1140.64 | 340.37 | 22.32 | 318.05 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 13.02 | 1171.51 | 137.44 | 0.00 | 137.44 | 0.00 | 0.00 |
February | 55.42 | 954.53 | 152.33 | 0.00 | 152.33 | 0.00 | 0.00 |
March | 136.53 | 567.48 | 213.92 | 0.00 | 213.92 | 0.00 | 0.00 |
April | 287.32 | 416.33 | 259.38 | 1.51 | 257.87 | 0.00 | 0.00 |
May | 448.69 | 248.49 | 309.48 | 9.71 | 299.77 | 0.00 | 0.00 |
June | 649.05 | 136.97 | 340.37 | 22.32 | 318.05 | 0.00 | 0.00 |
July | 658.73 | 89.62 | 322.35 | 16.52 | 305.83 | 0.00 | 0.00 |
August | 602.15 | 68.43 | 286.31 | 3.36 | 282.94 | 0.00 | 0.00 |
September | 345.18 | 203.36 | 216.12 | 0.08 | 216.03 | 0.00 | 0.00 |
October | 147.07 | 499.98 | 164.21 | 0.00 | 164.21 | 0.00 | 0.00 |
November | 67.25 | 711.00 | 146.96 | 0.00 | 146.96 | 0.00 | 0.00 |
December | 13.41 | 961.23 | 127.05 | 0.00 | 127.05 | 0.00 | 0.00 |
Annual Sum or Average | 286.64 | 500.18 | 223.38 | 4.48 | 218.90 | 0.00 | 0.00 |
Minimum of Months | 13.02 | 68.43 | 127.05 | 0.00 | 127.05 | 0.00 | 0.00 |
Maximum of Months | 658.73 | 1171.51 | 340.37 | 22.32 | 318.05 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 181.83 | 778.24 | 286.11 | 146.28 | 139.83 | 0.00 | 0.00 |
February | 301.09 | 638.77 | 322.47 | 174.39 | 148.09 | 0.00 | 0.00 |
March | 465.05 | 385.54 | 375.52 | 163.44 | 212.08 | 0.00 | 0.00 |
April | 644.93 | 287.94 | 413.53 | 163.85 | 249.68 | 0.00 | 0.00 |
May | 785.57 | 179.38 | 437.14 | 151.41 | 285.73 | 0.00 | 0.00 |
June | 942.16 | 101.02 | 448.80 | 152.90 | 295.91 | 0.00 | 0.00 |
July | 966.45 | 63.22 | 437.50 | 149.17 | 288.33 | 0.00 | 0.00 |
August | 936.99 | 45.70 | 413.96 | 136.02 | 277.94 | 0.00 | 0.00 |
September | 687.63 | 132.93 | 355.07 | 139.71 | 215.36 | 0.00 | 0.00 |
October | 497.89 | 337.81 | 337.68 | 175.45 | 162.23 | 0.00 | 0.00 |
November | 338.10 | 473.84 | 299.24 | 147.84 | 151.40 | 0.00 | 0.00 |
December | 212.02 | 635.37 | 273.51 | 141.94 | 131.57 | 0.00 | 0.00 |
Annual Sum or Average | 581.46 | 336.82 | 366.94 | 153.39 | 213.55 | 0.00 | 0.00 |
Minimum of Months | 181.83 | 45.70 | 273.51 | 136.02 | 131.57 | 0.00 | 0.00 |
Maximum of Months | 966.45 | 778.24 | 448.80 | 175.45 | 295.91 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 391.71 | 790.65 | 436.30 | 270.36 | 165.94 | 0.00 | 0.00 |
February | 437.65 | 644.86 | 414.75 | 241.86 | 172.89 | 0.00 | 0.00 |
March | 516.54 | 382.37 | 404.85 | 173.96 | 230.88 | 0.00 | 0.00 |
April | 513.77 | 289.87 | 338.41 | 83.76 | 254.65 | 0.00 | 0.00 |
May | 522.84 | 165.79 | 306.64 | 27.87 | 278.77 | 0.00 | 0.00 |
June | 619.07 | 89.62 | 300.82 | 17.93 | 282.89 | 0.00 | 0.00 |
July | 637.61 | 54.29 | 295.22 | 18.12 | 277.10 | 0.00 | 0.00 |
August | 697.32 | 36.98 | 320.72 | 42.98 | 277.74 | 0.00 | 0.00 |
September | 595.71 | 123.91 | 325.37 | 97.80 | 227.57 | 0.00 | 0.00 |
October | 601.44 | 330.19 | 409.15 | 228.06 | 181.08 | 0.00 | 0.00 |
November | 541.96 | 474.46 | 435.89 | 257.25 | 178.64 | 0.00 | 0.00 |
December | 440.82 | 640.40 | 430.00 | 271.85 | 158.15 | 0.00 | 0.00 |
Annual Sum or Average | 543.63 | 333.73 | 367.99 | 143.85 | 224.15 | 0.00 | 0.00 |
Minimum of Months | 391.71 | 36.98 | 295.22 | 17.93 | 158.15 | 0.00 | 0.00 |
Maximum of Months | 697.32 | 790.65 | 436.30 | 271.85 | 282.89 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.162442E+10 | 0.155125E+10 | 0.141220E+10 | 0.981020E+09 | 0.431183E+09 | 0.00 | 0.00 |
February | 0.149453E+10 | 0.115479E+10 | 0.118818E+10 | 0.792686E+09 | 0.395494E+09 | 0.00 | 0.00 |
March | 0.170507E+10 | 0.793037E+09 | 0.120293E+10 | 0.631243E+09 | 0.571687E+09 | 0.00 | 0.00 |
April | 0.141596E+10 | 0.590509E+09 | 0.876087E+09 | 0.292293E+09 | 0.583795E+09 | 0.00 | 0.00 |
May | 0.129078E+10 | 0.349621E+09 | 0.727706E+09 | 89053889.35 | 0.638652E+09 | 0.00 | 0.00 |
June | 0.134610E+10 | 0.185152E+09 | 0.646621E+09 | 36100811.87 | 0.610520E+09 | 0.00 | 0.00 |
July | 0.145056E+10 | 0.111103E+09 | 0.670261E+09 | 45210453.17 | 0.625050E+09 | 0.00 | 0.00 |
August | 0.171968E+10 | 85442102.01 | 0.807634E+09 | 0.151787E+09 | 0.655847E+09 | 0.00 | 0.00 |
September | 0.161103E+10 | 0.262424E+09 | 0.882405E+09 | 0.343335E+09 | 0.539070E+09 | 0.00 | 0.00 |
October | 0.196894E+10 | 0.700738E+09 | 0.128037E+10 | 0.827554E+09 | 0.452812E+09 | 0.00 | 0.00 |
November | 0.185913E+10 | 0.946964E+09 | 0.135373E+10 | 0.903351E+09 | 0.450383E+09 | 0.00 | 0.00 |
December | 0.173575E+10 | 0.127702E+10 | 0.140226E+10 | 0.986443E+09 | 0.415820E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.192219E+11 | 0.800805E+10 | 0.124504E+11 | 0.608008E+10 | 0.637031E+10 | 0.00 | 0.00 |
Minimum of Months | 0.129078E+10 | 85442102.01 | 0.646621E+09 | 36100811.87 | 0.395494E+09 | 0.00 | 0.00 |
Maximum of Months | 0.196894E+10 | 0.155125E+10 | 0.141220E+10 | 0.986443E+09 | 0.655847E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.452361E+10 | 0.445919E+10 | 0.397667E+10 | 0.276249E+10 | 0.121418E+10 | 0.00 | 0.00 |
February | 0.416223E+10 | 0.336501E+10 | 0.334584E+10 | 0.223215E+10 | 0.111368E+10 | 0.00 | 0.00 |
March | 0.474124E+10 | 0.239794E+10 | 0.338737E+10 | 0.177754E+10 | 0.160983E+10 | 0.00 | 0.00 |
April | 0.393275E+10 | 0.180698E+10 | 0.246700E+10 | 0.823077E+09 | 0.164393E+10 | 0.00 | 0.00 |
May | 0.357146E+10 | 0.113340E+10 | 0.204917E+10 | 0.250770E+09 | 0.179840E+10 | 0.00 | 0.00 |
June | 0.374443E+10 | 0.631023E+09 | 0.182084E+10 | 0.101658E+09 | 0.171918E+10 | 0.00 | 0.00 |
July | 0.405510E+10 | 0.405105E+09 | 0.188741E+10 | 0.127310E+09 | 0.176010E+10 | 0.00 | 0.00 |
August | 0.483007E+10 | 0.325165E+09 | 0.227424E+10 | 0.427422E+09 | 0.184682E+10 | 0.00 | 0.00 |
September | 0.448652E+10 | 0.879313E+09 | 0.248479E+10 | 0.966809E+09 | 0.151798E+10 | 0.00 | 0.00 |
October | 0.549059E+10 | 0.214833E+10 | 0.360543E+10 | 0.233034E+10 | 0.127509E+10 | 0.00 | 0.00 |
November | 0.518040E+10 | 0.282059E+10 | 0.381203E+10 | 0.254378E+10 | 0.126825E+10 | 0.00 | 0.00 |
December | 0.483341E+10 | 0.371723E+10 | 0.394868E+10 | 0.277776E+10 | 0.117092E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.535518E+11 | 0.240893E+11 | 0.350595E+11 | 0.171211E+11 | 0.179384E+11 | 0.00 | 0.00 |
Minimum of Months | 0.357146E+10 | 0.325165E+09 | 0.182084E+10 | 0.101658E+09 | 0.111368E+10 | 0.00 | 0.00 |
Maximum of Months | 0.549059E+10 | 0.445919E+10 | 0.397667E+10 | 0.277776E+10 | 0.184682E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.599171E+10 | 0.598322E+10 | 0.516592E+10 | 0.358863E+10 | 0.157729E+10 | 0.00 | 0.00 |
February | 0.553370E+10 | 0.449319E+10 | 0.434643E+10 | 0.289969E+10 | 0.144674E+10 | 0.00 | 0.00 |
March | 0.633966E+10 | 0.315455E+10 | 0.440039E+10 | 0.230912E+10 | 0.209126E+10 | 0.00 | 0.00 |
April | 0.526564E+10 | 0.238575E+10 | 0.320478E+10 | 0.106922E+10 | 0.213555E+10 | 0.00 | 0.00 |
May | 0.478573E+10 | 0.148394E+10 | 0.266199E+10 | 0.325764E+09 | 0.233623E+10 | 0.00 | 0.00 |
June | 0.501637E+10 | 0.813771E+09 | 0.236538E+10 | 0.132059E+09 | 0.223332E+10 | 0.00 | 0.00 |
July | 0.544297E+10 | 0.512244E+09 | 0.245185E+10 | 0.165382E+09 | 0.228647E+10 | 0.00 | 0.00 |
August | 0.650018E+10 | 0.387852E+09 | 0.295437E+10 | 0.555246E+09 | 0.239913E+10 | 0.00 | 0.00 |
September | 0.600603E+10 | 0.113137E+10 | 0.322789E+10 | 0.125594E+10 | 0.197195E+10 | 0.00 | 0.00 |
October | 0.734523E+10 | 0.281482E+10 | 0.468365E+10 | 0.302724E+10 | 0.165641E+10 | 0.00 | 0.00 |
November | 0.690390E+10 | 0.373778E+10 | 0.495204E+10 | 0.330451E+10 | 0.164753E+10 | 0.00 | 0.00 |
December | 0.642133E+10 | 0.496962E+10 | 0.512956E+10 | 0.360846E+10 | 0.152109E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.715525E+11 | 0.318681E+11 | 0.455443E+11 | 0.222413E+11 | 0.233030E+11 | 0.00 | 0.00 |
Minimum of Months | 0.478573E+10 | 0.387852E+09 | 0.236538E+10 | 0.132059E+09 | 0.144674E+10 | 0.00 | 0.00 |
Maximum of Months | 0.734523E+10 | 0.598322E+10 | 0.516592E+10 | 0.360846E+10 | 0.239913E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.425470E+09 | 0.100443E+10 | 0.501844E+09 | 0.297480E+09 | 0.204364E+09 | 0.00 | 0.00 |
February | 0.482425E+09 | 0.740625E+09 | 0.465298E+09 | 0.264700E+09 | 0.200598E+09 | 0.00 | 0.00 |
March | 0.789797E+09 | 0.494514E+09 | 0.612039E+09 | 0.305281E+09 | 0.306758E+09 | 0.00 | 0.00 |
April | 0.879448E+09 | 0.358349E+09 | 0.581284E+09 | 0.244432E+09 | 0.336852E+09 | 0.00 | 0.00 |
May | 0.963505E+09 | 0.205657E+09 | 0.568158E+09 | 0.178638E+09 | 0.389520E+09 | 0.00 | 0.00 |
June | 0.111104E+10 | 92241988.14 | 0.559219E+09 | 0.173234E+09 | 0.385985E+09 | 0.00 | 0.00 |
July | 0.116249E+10 | 44828194.99 | 0.552093E+09 | 0.164131E+09 | 0.387962E+09 | 0.00 | 0.00 |
August | 0.121386E+10 | 22386250.72 | 0.571808E+09 | 0.184152E+09 | 0.387656E+09 | 0.00 | 0.00 |
September | 0.896469E+09 | 0.137055E+09 | 0.500287E+09 | 0.204092E+09 | 0.296195E+09 | 0.00 | 0.00 |
October | 0.804667E+09 | 0.426761E+09 | 0.552717E+09 | 0.319376E+09 | 0.233342E+09 | 0.00 | 0.00 |
November | 0.601892E+09 | 0.600464E+09 | 0.497906E+09 | 0.281572E+09 | 0.216334E+09 | 0.00 | 0.00 |
December | 0.455368E+09 | 0.821023E+09 | 0.474312E+09 | 0.281358E+09 | 0.192954E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.978643E+10 | 0.494834E+10 | 0.643697E+10 | 0.289845E+10 | 0.353852E+10 | 0.00 | 0.00 |
Minimum of Months | 0.425470E+09 | 22386250.72 | 0.465298E+09 | 0.164131E+09 | 0.192954E+09 | 0.00 | 0.00 |
Maximum of Months | 0.121386E+10 | 0.100443E+10 | 0.612039E+09 | 0.319376E+09 | 0.389520E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.159727E+09 | 0.109039E+10 | 0.275215E+09 | 0.103516E+09 | 0.171700E+09 | 0.00 | 0.00 |
February | 0.246819E+09 | 0.795691E+09 | 0.283022E+09 | 0.107973E+09 | 0.175050E+09 | 0.00 | 0.00 |
March | 0.534350E+09 | 0.511562E+09 | 0.456053E+09 | 0.180475E+09 | 0.275578E+09 | 0.00 | 0.00 |
April | 0.723591E+09 | 0.369152E+09 | 0.504114E+09 | 0.187201E+09 | 0.316912E+09 | 0.00 | 0.00 |
May | 0.891365E+09 | 0.215332E+09 | 0.542695E+09 | 0.164744E+09 | 0.377951E+09 | 0.00 | 0.00 |
June | 0.108795E+10 | 95012056.94 | 0.557408E+09 | 0.174362E+09 | 0.383046E+09 | 0.00 | 0.00 |
July | 0.112688E+10 | 49293276.77 | 0.542915E+09 | 0.161512E+09 | 0.381403E+09 | 0.00 | 0.00 |
August | 0.110197E+10 | 24946086.44 | 0.521677E+09 | 0.155428E+09 | 0.366249E+09 | 0.00 | 0.00 |
September | 0.712808E+09 | 0.147589E+09 | 0.405848E+09 | 0.136240E+09 | 0.269608E+09 | 0.00 | 0.00 |
October | 0.492677E+09 | 0.445029E+09 | 0.362400E+09 | 0.155754E+09 | 0.206646E+09 | 0.00 | 0.00 |
November | 0.299868E+09 | 0.633992E+09 | 0.284668E+09 | 0.102964E+09 | 0.181704E+09 | 0.00 | 0.00 |
December | 0.171013E+09 | 0.886630E+09 | 0.245674E+09 | 86321527.55 | 0.159353E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.754901E+10 | 0.526462E+10 | 0.498169E+10 | 0.171649E+10 | 0.326520E+10 | 0.00 | 0.00 |
Minimum of Months | 0.159727E+09 | 24946086.44 | 0.245674E+09 | 86321527.55 | 0.159353E+09 | 0.00 | 0.00 |
Maximum of Months | 0.112688E+10 | 0.109039E+10 | 0.557408E+09 | 0.187201E+09 | 0.383046E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.234103E+09 | 0.302453E+09 | 0.223330E+09 | 0.155141E+09 | 68188813.41 | 0.00 | 0.00 |
February | 0.208117E+09 | 0.255665E+09 | 0.187902E+09 | 0.125357E+09 | 62544840.67 | 0.00 | 0.00 |
March | 0.223721E+09 | 0.214160E+09 | 0.190235E+09 | 99826196.68 | 90408627.06 | 0.00 | 0.00 |
April | 0.180797E+09 | 0.168204E+09 | 0.138547E+09 | 46223853.60 | 92323562.43 | 0.00 | 0.00 |
May | 0.158558E+09 | 0.116971E+09 | 0.115082E+09 | 14083185.96 | 0.100999E+09 | 0.00 | 0.00 |
June | 0.172577E+09 | 71152875.43 | 0.102259E+09 | 5709065.05 | 96550134.41 | 0.00 | 0.00 |
July | 0.191254E+09 | 54088354.71 | 0.105998E+09 | 7149684.58 | 98847981.78 | 0.00 | 0.00 |
August | 0.238108E+09 | 46773701.58 | 0.127722E+09 | 24003960.40 | 0.103718E+09 | 0.00 | 0.00 |
September | 0.218694E+09 | 95626972.54 | 0.139546E+09 | 54295818.95 | 85250458.26 | 0.00 | 0.00 |
October | 0.273597E+09 | 0.194283E+09 | 0.202481E+09 | 0.130871E+09 | 71609428.64 | 0.00 | 0.00 |
November | 0.253801E+09 | 0.243252E+09 | 0.214083E+09 | 0.142858E+09 | 71225121.93 | 0.00 | 0.00 |
December | 0.237273E+09 | 0.298886E+09 | 0.221757E+09 | 0.155998E+09 | 65759141.47 | 0.00 | 0.00 |
Annual Sum or Average | 0.259060E+10 | 0.206152E+10 | 0.196894E+10 | 0.961517E+09 | 0.100743E+10 | 0.00 | 0.00 |
Minimum of Months | 0.158558E+09 | 46773701.58 | 0.102259E+09 | 5709065.05 | 62544840.67 | 0.00 | 0.00 |
Maximum of Months | 0.273597E+09 | 0.302453E+09 | 0.223330E+09 | 0.155998E+09 | 0.103718E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 5201365.22 | 0.341593E+09 | 42076451.99 | 0.00 | 42076451.99 | 0.00 | 0.00 |
February | 18587407.70 | 0.244953E+09 | 42124339.93 | 0.00 | 42124339.93 | 0.00 | 0.00 |
March | 50630160.12 | 0.149283E+09 | 65492691.15 | 1318.99 | 65491372.16 | 0.00 | 0.00 |
April | 97939717.13 | 0.103238E+09 | 76848851.72 | 448829.91 | 76400021.81 | 0.00 | 0.00 |
May | 0.155730E+09 | 56534500.33 | 94747450.04 | 2971603.27 | 91775846.77 | 0.00 | 0.00 |
June | 0.219305E+09 | 22999594.73 | 0.100844E+09 | 6613320.29 | 94230889.24 | 0.00 | 0.00 |
July | 0.233400E+09 | 11609809.75 | 98689421.90 | 5056973.36 | 93632448.53 | 0.00 | 0.00 |
August | 0.218331E+09 | 5029408.33 | 87654522.95 | 1029768.70 | 86624754.24 | 0.00 | 0.00 |
September | 0.119342E+09 | 39597070.69 | 64031230.67 | 25170.94 | 64006059.72 | 0.00 | 0.00 |
October | 53885002.01 | 0.128497E+09 | 50273499.29 | 0.00 | 50273499.29 | 0.00 | 0.00 |
November | 25583965.20 | 0.188092E+09 | 43541540.27 | 0.00 | 43541540.27 | 0.00 | 0.00 |
December | 6048985.61 | 0.271958E+09 | 38896548.34 | 0.00 | 38896548.34 | 0.00 | 0.00 |
Annual Sum or Average | 0.120398E+10 | 0.156338E+10 | 0.805221E+09 | 16146985.47 | 0.789074E+09 | 0.00 | 0.00 |
Minimum of Months | 5201365.22 | 5029408.33 | 38896548.34 | 0.00 | 38896548.34 | 0.00 | 0.00 |
Maximum of Months | 0.233400E+09 | 0.341593E+09 | 0.100844E+09 | 6613320.29 | 94230889.24 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.403146E+09 | 0.989708E+09 | 0.496486E+09 | 0.292891E+09 | 0.203596E+09 | 0.00 | 0.00 |
February | 0.490514E+09 | 0.723548E+09 | 0.481219E+09 | 0.289311E+09 | 0.191908E+09 | 0.00 | 0.00 |
March | 0.711738E+09 | 0.470215E+09 | 0.580914E+09 | 0.281299E+09 | 0.299614E+09 | 0.00 | 0.00 |
April | 0.840820E+09 | 0.332624E+09 | 0.574551E+09 | 0.240974E+09 | 0.333577E+09 | 0.00 | 0.00 |
May | 0.993492E+09 | 0.190029E+09 | 0.598187E+09 | 0.209729E+09 | 0.388458E+09 | 0.00 | 0.00 |
June | 0.114103E+10 | 83828208.58 | 0.582588E+09 | 0.197605E+09 | 0.384983E+09 | 0.00 | 0.00 |
July | 0.122222E+10 | 43023344.89 | 0.590525E+09 | 0.201092E+09 | 0.389433E+09 | 0.00 | 0.00 |
August | 0.122732E+10 | 21037752.85 | 0.579466E+09 | 0.196526E+09 | 0.382940E+09 | 0.00 | 0.00 |
September | 0.902983E+09 | 0.130868E+09 | 0.507408E+09 | 0.214997E+09 | 0.292411E+09 | 0.00 | 0.00 |
October | 0.775330E+09 | 0.409031E+09 | 0.547407E+09 | 0.316785E+09 | 0.230622E+09 | 0.00 | 0.00 |
November | 0.575362E+09 | 0.579635E+09 | 0.494448E+09 | 0.280911E+09 | 0.213537E+09 | 0.00 | 0.00 |
December | 0.447313E+09 | 0.802138E+09 | 0.480619E+09 | 0.287609E+09 | 0.193010E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.973127E+10 | 0.477569E+10 | 0.651382E+10 | 0.300973E+10 | 0.350409E+10 | 0.00 | 0.00 |
Minimum of Months | 0.403146E+09 | 21037752.85 | 0.480619E+09 | 0.196526E+09 | 0.191908E+09 | 0.00 | 0.00 |
Maximum of Months | 0.122732E+10 | 0.989708E+09 | 0.598187E+09 | 0.316785E+09 | 0.389433E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.118805E+09 | 0.105628E+10 | 0.269858E+09 | 98926312.94 | 0.170931E+09 | 0.00 | 0.00 |
February | 0.229722E+09 | 0.751724E+09 | 0.298943E+09 | 0.132584E+09 | 0.166359E+09 | 0.00 | 0.00 |
March | 0.446950E+09 | 0.471995E+09 | 0.424928E+09 | 0.156494E+09 | 0.268435E+09 | 0.00 | 0.00 |
April | 0.685476E+09 | 0.340599E+09 | 0.497381E+09 | 0.183744E+09 | 0.313637E+09 | 0.00 | 0.00 |
May | 0.923133E+09 | 0.202070E+09 | 0.572725E+09 | 0.195836E+09 | 0.376889E+09 | 0.00 | 0.00 |
June | 0.111636E+10 | 89762981.37 | 0.580777E+09 | 0.198732E+09 | 0.382045E+09 | 0.00 | 0.00 |
July | 0.118225E+10 | 48717504.93 | 0.581347E+09 | 0.198474E+09 | 0.382873E+09 | 0.00 | 0.00 |
August | 0.111226E+10 | 23519836.56 | 0.529335E+09 | 0.167803E+09 | 0.361533E+09 | 0.00 | 0.00 |
September | 0.715126E+09 | 0.139850E+09 | 0.412969E+09 | 0.147145E+09 | 0.265824E+09 | 0.00 | 0.00 |
October | 0.451810E+09 | 0.412600E+09 | 0.357089E+09 | 0.153163E+09 | 0.203926E+09 | 0.00 | 0.00 |
November | 0.247409E+09 | 0.582445E+09 | 0.281211E+09 | 0.102303E+09 | 0.178908E+09 | 0.00 | 0.00 |
December | 0.127208E+09 | 0.830642E+09 | 0.251981E+09 | 92572432.32 | 0.159409E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.735651E+10 | 0.495020E+10 | 0.505854E+10 | 0.182778E+10 | 0.323077E+10 | 0.00 | 0.00 |
Minimum of Months | 0.118805E+09 | 23519836.56 | 0.251981E+09 | 92572432.32 | 0.159409E+09 | 0.00 | 0.00 |
Maximum of Months | 0.118225E+10 | 0.105628E+10 | 0.581347E+09 | 0.198732E+09 | 0.382873E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.475228E+09 | 0.119195E+10 | 0.575045E+09 | 0.336147E+09 | 0.238898E+09 | 0.00 | 0.00 |
February | 0.503397E+09 | 0.873447E+09 | 0.498387E+09 | 0.271614E+09 | 0.226773E+09 | 0.00 | 0.00 |
March | 0.702410E+09 | 0.567921E+09 | 0.554065E+09 | 0.216298E+09 | 0.337767E+09 | 0.00 | 0.00 |
April | 0.720738E+09 | 0.411814E+09 | 0.466674E+09 | 0.101127E+09 | 0.365548E+09 | 0.00 | 0.00 |
May | 0.805069E+09 | 0.233852E+09 | 0.454606E+09 | 36951836.71 | 0.417654E+09 | 0.00 | 0.00 |
June | 0.950298E+09 | 0.114129E+09 | 0.440030E+09 | 26696625.66 | 0.413333E+09 | 0.00 | 0.00 |
July | 0.101259E+10 | 67170287.83 | 0.443462E+09 | 26446478.24 | 0.417015E+09 | 0.00 | 0.00 |
August | 0.107519E+10 | 39900748.29 | 0.466627E+09 | 54240731.23 | 0.412387E+09 | 0.00 | 0.00 |
September | 0.831974E+09 | 0.172481E+09 | 0.441071E+09 | 0.117698E+09 | 0.323373E+09 | 0.00 | 0.00 |
October | 0.807974E+09 | 0.490252E+09 | 0.547629E+09 | 0.283562E+09 | 0.264067E+09 | 0.00 | 0.00 |
November | 0.680340E+09 | 0.686258E+09 | 0.558184E+09 | 0.309534E+09 | 0.248651E+09 | 0.00 | 0.00 |
December | 0.546781E+09 | 0.961180E+09 | 0.564750E+09 | 0.338005E+09 | 0.226745E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.911199E+10 | 0.581036E+10 | 0.601053E+10 | 0.211832E+10 | 0.389221E+10 | 0.00 | 0.00 |
Minimum of Months | 0.475228E+09 | 39900748.29 | 0.440030E+09 | 26446478.24 | 0.226745E+09 | 0.00 | 0.00 |
Maximum of Months | 0.107519E+10 | 0.119195E+10 | 0.575045E+09 | 0.338005E+09 | 0.417654E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.424362E+09 | 0.100114E+10 | 0.501844E+09 | 0.297480E+09 | 0.204364E+09 | 0.00 | 0.00 |
February | 0.478860E+09 | 0.737035E+09 | 0.465298E+09 | 0.264700E+09 | 0.200598E+09 | 0.00 | 0.00 |
March | 0.778783E+09 | 0.491704E+09 | 0.612039E+09 | 0.305281E+09 | 0.306758E+09 | 0.00 | 0.00 |
April | 0.865918E+09 | 0.357359E+09 | 0.581284E+09 | 0.244432E+09 | 0.336852E+09 | 0.00 | 0.00 |
May | 0.948565E+09 | 0.204994E+09 | 0.568158E+09 | 0.178638E+09 | 0.389520E+09 | 0.00 | 0.00 |
June | 0.109859E+10 | 90090453.81 | 0.559219E+09 | 0.173234E+09 | 0.385985E+09 | 0.00 | 0.00 |
July | 0.115125E+10 | 42970489.88 | 0.552093E+09 | 0.164131E+09 | 0.387962E+09 | 0.00 | 0.00 |
August | 0.120251E+10 | 20738486.18 | 0.571808E+09 | 0.184152E+09 | 0.387656E+09 | 0.00 | 0.00 |
September | 0.886382E+09 | 0.134478E+09 | 0.500287E+09 | 0.204092E+09 | 0.296195E+09 | 0.00 | 0.00 |
October | 0.795090E+09 | 0.423576E+09 | 0.552717E+09 | 0.319376E+09 | 0.233342E+09 | 0.00 | 0.00 |
November | 0.597104E+09 | 0.596398E+09 | 0.497906E+09 | 0.281572E+09 | 0.216334E+09 | 0.00 | 0.00 |
December | 0.453873E+09 | 0.815525E+09 | 0.474312E+09 | 0.281358E+09 | 0.192954E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.968129E+10 | 0.491600E+10 | 0.643697E+10 | 0.289845E+10 | 0.353852E+10 | 0.00 | 0.00 |
Minimum of Months | 0.424362E+09 | 20738486.18 | 0.465298E+09 | 0.164131E+09 | 0.192954E+09 | 0.00 | 0.00 |
Maximum of Months | 0.120251E+10 | 0.100114E+10 | 0.612039E+09 | 0.319376E+09 | 0.389520E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.160452E+09 | 0.108809E+10 | 0.275215E+09 | 0.103516E+09 | 0.171700E+09 | 0.00 | 0.00 |
February | 0.245482E+09 | 0.792549E+09 | 0.283022E+09 | 0.107973E+09 | 0.175050E+09 | 0.00 | 0.00 |
March | 0.526367E+09 | 0.509652E+09 | 0.456053E+09 | 0.180475E+09 | 0.275578E+09 | 0.00 | 0.00 |
April | 0.710248E+09 | 0.371862E+09 | 0.504114E+09 | 0.187201E+09 | 0.316912E+09 | 0.00 | 0.00 |
May | 0.875303E+09 | 0.218227E+09 | 0.542695E+09 | 0.164744E+09 | 0.377951E+09 | 0.00 | 0.00 |
June | 0.107517E+10 | 93982553.88 | 0.557408E+09 | 0.174362E+09 | 0.383046E+09 | 0.00 | 0.00 |
July | 0.111540E+10 | 48187320.99 | 0.542915E+09 | 0.161512E+09 | 0.381403E+09 | 0.00 | 0.00 |
August | 0.109120E+10 | 23370322.06 | 0.521677E+09 | 0.155428E+09 | 0.366249E+09 | 0.00 | 0.00 |
September | 0.703702E+09 | 0.146181E+09 | 0.405848E+09 | 0.136240E+09 | 0.269608E+09 | 0.00 | 0.00 |
October | 0.486003E+09 | 0.443141E+09 | 0.362400E+09 | 0.155754E+09 | 0.206646E+09 | 0.00 | 0.00 |
November | 0.298818E+09 | 0.628757E+09 | 0.284668E+09 | 0.102964E+09 | 0.181704E+09 | 0.00 | 0.00 |
December | 0.172918E+09 | 0.880376E+09 | 0.245674E+09 | 86321527.55 | 0.159353E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.746106E+10 | 0.524438E+10 | 0.498169E+10 | 0.171649E+10 | 0.326520E+10 | 0.00 | 0.00 |
Minimum of Months | 0.160452E+09 | 23370322.06 | 0.245674E+09 | 86321527.55 | 0.159353E+09 | 0.00 | 0.00 |
Maximum of Months | 0.111540E+10 | 0.108809E+10 | 0.557408E+09 | 0.187201E+09 | 0.383046E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.436123E+09 | 0.517268E+09 | 0.409499E+09 | 0.284468E+09 | 0.125032E+09 | 0.00 | 0.00 |
February | 0.405609E+09 | 0.383764E+09 | 0.344539E+09 | 0.229856E+09 | 0.114683E+09 | 0.00 | 0.00 |
March | 0.467193E+09 | 0.256096E+09 | 0.348816E+09 | 0.183042E+09 | 0.165774E+09 | 0.00 | 0.00 |
April | 0.394451E+09 | 0.185191E+09 | 0.254042E+09 | 84756499.22 | 0.169285E+09 | 0.00 | 0.00 |
May | 0.367338E+09 | 0.102388E+09 | 0.211016E+09 | 25823064.22 | 0.185193E+09 | 0.00 | 0.00 |
June | 0.409832E+09 | 43031870.27 | 0.187503E+09 | 10468196.17 | 0.177035E+09 | 0.00 | 0.00 |
July | 0.454439E+09 | 19797741.00 | 0.194358E+09 | 13109729.90 | 0.181249E+09 | 0.00 | 0.00 |
August | 0.541413E+09 | 9063997.13 | 0.234192E+09 | 44013890.93 | 0.190178E+09 | 0.00 | 0.00 |
September | 0.472466E+09 | 67674174.86 | 0.255873E+09 | 99557331.94 | 0.156316E+09 | 0.00 | 0.00 |
October | 0.556649E+09 | 0.219076E+09 | 0.371270E+09 | 0.239967E+09 | 0.131304E+09 | 0.00 | 0.00 |
November | 0.515258E+09 | 0.308735E+09 | 0.392545E+09 | 0.261946E+09 | 0.130599E+09 | 0.00 | 0.00 |
December | 0.471069E+09 | 0.423315E+09 | 0.406617E+09 | 0.286040E+09 | 0.120577E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.549184E+10 | 0.253540E+10 | 0.361027E+10 | 0.176305E+10 | 0.184722E+10 | 0.00 | 0.00 |
Minimum of Months | 0.367338E+09 | 9063997.13 | 0.187503E+09 | 10468196.17 | 0.114683E+09 | 0.00 | 0.00 |
Maximum of Months | 0.556649E+09 | 0.517268E+09 | 0.409499E+09 | 0.286040E+09 | 0.190178E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 39356133.70 | 0.305509E+10 | 0.368106E+09 | 0.00 | 0.368106E+09 | 0.00 | 0.00 |
February | 0.145605E+09 | 0.223611E+10 | 0.368525E+09 | 0.00 | 0.368525E+09 | 0.00 | 0.00 |
March | 0.397243E+09 | 0.145230E+10 | 0.572963E+09 | 11539.19 | 0.572952E+09 | 0.00 | 0.00 |
April | 0.784677E+09 | 0.103233E+10 | 0.672313E+09 | 3926592.47 | 0.668386E+09 | 0.00 | 0.00 |
May | 0.124681E+10 | 0.633797E+09 | 0.828899E+09 | 25997097.83 | 0.802902E+09 | 0.00 | 0.00 |
June | 0.172155E+10 | 0.336341E+09 | 0.882236E+09 | 57856691.74 | 0.824380E+09 | 0.00 | 0.00 |
July | 0.180161E+10 | 0.223866E+09 | 0.863385E+09 | 44240976.70 | 0.819144E+09 | 0.00 | 0.00 |
August | 0.164848E+10 | 0.167756E+09 | 0.766846E+09 | 9008940.72 | 0.757837E+09 | 0.00 | 0.00 |
September | 0.931213E+09 | 0.494350E+09 | 0.560178E+09 | 220208.23 | 0.559958E+09 | 0.00 | 0.00 |
October | 0.423052E+09 | 0.127415E+10 | 0.439818E+09 | 0.00 | 0.439818E+09 | 0.00 | 0.00 |
November | 0.195892E+09 | 0.176864E+10 | 0.380924E+09 | 0.00 | 0.380924E+09 | 0.00 | 0.00 |
December | 42904557.66 | 0.248598E+10 | 0.340287E+09 | 0.00 | 0.340287E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.937839E+10 | 0.151607E+11 | 0.704448E+10 | 0.141262E+09 | 0.690322E+10 | 0.00 | 0.00 |
Minimum of Months | 39356133.70 | 0.167756E+09 | 0.340287E+09 | 0.00 | 0.340287E+09 | 0.00 | 0.00 |
Maximum of Months | 0.180161E+10 | 0.305509E+10 | 0.882236E+09 | 57856691.74 | 0.824380E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 34875965.26 | 0.313778E+10 | 0.368106E+09 | 0.00 | 0.368106E+09 | 0.00 | 0.00 |
February | 0.134081E+09 | 0.230919E+10 | 0.368525E+09 | 0.00 | 0.368525E+09 | 0.00 | 0.00 |
March | 0.365691E+09 | 0.151994E+10 | 0.572963E+09 | 11539.19 | 0.572952E+09 | 0.00 | 0.00 |
April | 0.744740E+09 | 0.107914E+10 | 0.672313E+09 | 3926592.47 | 0.668386E+09 | 0.00 | 0.00 |
May | 0.120176E+10 | 0.665560E+09 | 0.828899E+09 | 25997097.83 | 0.802902E+09 | 0.00 | 0.00 |
June | 0.168234E+10 | 0.355037E+09 | 0.882236E+09 | 57856691.74 | 0.824380E+09 | 0.00 | 0.00 |
July | 0.176435E+10 | 0.240041E+09 | 0.863385E+09 | 44240976.70 | 0.819144E+09 | 0.00 | 0.00 |
August | 0.161279E+10 | 0.183279E+09 | 0.766846E+09 | 9008940.72 | 0.757837E+09 | 0.00 | 0.00 |
September | 0.894707E+09 | 0.527100E+09 | 0.560178E+09 | 220208.23 | 0.559958E+09 | 0.00 | 0.00 |
October | 0.393908E+09 | 0.133913E+10 | 0.439818E+09 | 0.00 | 0.439818E+09 | 0.00 | 0.00 |
November | 0.174315E+09 | 0.184292E+10 | 0.380924E+09 | 0.00 | 0.380924E+09 | 0.00 | 0.00 |
December | 35922521.05 | 0.257456E+10 | 0.340287E+09 | 0.00 | 0.340287E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.903948E+10 | 0.157737E+11 | 0.704448E+10 | 0.141262E+09 | 0.690322E+10 | 0.00 | 0.00 |
Minimum of Months | 34875965.26 | 0.183279E+09 | 0.340287E+09 | 0.00 | 0.340287E+09 | 0.00 | 0.00 |
Maximum of Months | 0.176435E+10 | 0.313778E+10 | 0.882236E+09 | 57856691.74 | 0.824380E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.487024E+09 | 0.208444E+10 | 0.766313E+09 | 0.391803E+09 | 0.374510E+09 | 0.00 | 0.00 |
February | 0.728394E+09 | 0.154530E+10 | 0.780127E+09 | 0.421877E+09 | 0.358251E+09 | 0.00 | 0.00 |
March | 0.124558E+10 | 0.103262E+10 | 0.100579E+10 | 0.437771E+09 | 0.568023E+09 | 0.00 | 0.00 |
April | 0.167166E+10 | 0.746351E+09 | 0.107188E+10 | 0.424692E+09 | 0.647183E+09 | 0.00 | 0.00 |
May | 0.210408E+10 | 0.480447E+09 | 0.117085E+10 | 0.405538E+09 | 0.765309E+09 | 0.00 | 0.00 |
June | 0.244207E+10 | 0.261849E+09 | 0.116330E+10 | 0.396310E+09 | 0.766990E+09 | 0.00 | 0.00 |
July | 0.258854E+10 | 0.169330E+09 | 0.117181E+10 | 0.399539E+09 | 0.772269E+09 | 0.00 | 0.00 |
August | 0.250963E+10 | 0.122396E+09 | 0.110874E+10 | 0.364305E+09 | 0.744437E+09 | 0.00 | 0.00 |
September | 0.178233E+10 | 0.344560E+09 | 0.920329E+09 | 0.362120E+09 | 0.558209E+09 | 0.00 | 0.00 |
October | 0.133354E+10 | 0.904780E+09 | 0.904454E+09 | 0.469926E+09 | 0.434528E+09 | 0.00 | 0.00 |
November | 0.876359E+09 | 0.122820E+10 | 0.775627E+09 | 0.383200E+09 | 0.392427E+09 | 0.00 | 0.00 |
December | 0.567862E+09 | 0.170177E+10 | 0.732571E+09 | 0.380168E+09 | 0.352403E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.183371E+11 | 0.106220E+11 | 0.115718E+11 | 0.483725E+10 | 0.673454E+10 | 0.00 | 0.00 |
Minimum of Months | 0.487024E+09 | 0.122396E+09 | 0.732571E+09 | 0.362120E+09 | 0.352403E+09 | 0.00 | 0.00 |
Maximum of Months | 0.258854E+10 | 0.208444E+10 | 0.117181E+10 | 0.469926E+09 | 0.772269E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.104917E+10 | 0.211767E+10 | 0.116859E+10 | 0.724128E+09 | 0.444462E+09 | 0.00 | 0.00 |
February | 0.105876E+10 | 0.156004E+10 | 0.100337E+10 | 0.585111E+09 | 0.418262E+09 | 0.00 | 0.00 |
March | 0.138350E+10 | 0.102414E+10 | 0.108434E+10 | 0.465948E+09 | 0.618396E+09 | 0.00 | 0.00 |
April | 0.133170E+10 | 0.751342E+09 | 0.877147E+09 | 0.217098E+09 | 0.660049E+09 | 0.00 | 0.00 |
May | 0.140036E+10 | 0.444048E+09 | 0.821300E+09 | 74645838.28 | 0.746654E+09 | 0.00 | 0.00 |
June | 0.160462E+10 | 0.232307E+09 | 0.779732E+09 | 46480736.68 | 0.733252E+09 | 0.00 | 0.00 |
July | 0.170777E+10 | 0.145400E+09 | 0.790720E+09 | 48537407.44 | 0.742182E+09 | 0.00 | 0.00 |
August | 0.186771E+10 | 99053795.44 | 0.859026E+09 | 0.115128E+09 | 0.743898E+09 | 0.00 | 0.00 |
September | 0.154408E+10 | 0.321176E+09 | 0.843369E+09 | 0.253504E+09 | 0.589865E+09 | 0.00 | 0.00 |
October | 0.161091E+10 | 0.884389E+09 | 0.109586E+10 | 0.610848E+09 | 0.485011E+09 | 0.00 | 0.00 |
November | 0.140476E+10 | 0.122980E+10 | 0.112983E+10 | 0.666797E+09 | 0.463028E+09 | 0.00 | 0.00 |
December | 0.118069E+10 | 0.171526E+10 | 0.115171E+10 | 0.728130E+09 | 0.423585E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.171440E+11 | 0.105246E+11 | 0.116050E+11 | 0.453636E+10 | 0.706864E+10 | 0.00 | 0.00 |
Minimum of Months | 0.104917E+10 | 99053795.44 | 0.779732E+09 | 46480736.68 | 0.418262E+09 | 0.00 | 0.00 |
Maximum of Months | 0.186771E+10 | 0.211767E+10 | 0.116859E+10 | 0.728130E+09 | 0.746654E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 3.96 | 1.39 | -3.0 | 4.56 | -7.8 | 48.74 | 150.20 | 0.00 |
February | 7.94 | 4.18 | -1.3 | 5.19 | -4.0 | 51.84 | 169.20 | 0.00 |
March | 13.76 | 8.97 | 3.80 | 4.89 | 2.25 | 76.95 | 193.22 | 0.00 |
April | 17.21 | 12.54 | 8.82 | 3.95 | 6.45 | 95.37 | 211.82 | 0.00 |
May | 20.84 | 16.44 | 13.69 | 3.50 | 11.46 | 117.34 | 200.00 | 0.00 |
June | 24.80 | 19.35 | 16.45 | 3.85 | 15.08 | 121.81 | 213.08 | 0.00 |
July | 26.06 | 21.68 | 19.85 | 3.24 | 17.64 | 119.92 | 194.46 | 0.00 |
August | 26.55 | 22.42 | 20.72 | 3.39 | 18.21 | 115.12 | 179.15 | 0.00 |
September | 22.53 | 18.74 | 16.82 | 3.06 | 13.44 | 83.74 | 156.58 | 0.02 |
October | 16.03 | 13.02 | 10.77 | 4.05 | 5.85 | 53.01 | 190.38 | 0.00 |
November | 11.94 | 8.22 | 4.17 | 4.16 | 0.30 | 52.20 | 150.38 | 0.00 |
December | 7.70 | 4.64 | 0.26 | 4.69 | -4.1 | 44.81 | 142.03 | 0.00 |
Annual Sum or Average | 16.65 | 12.68 | 9.31 | 4.04 | 6.29 | 81.91 | 179.25 | 0.00 |
Minimum of Months | 3.96 | 1.39 | -3.0 | 3.06 | -7.8 | 44.81 | 142.03 | 0.00 |
Maximum of Months | 26.55 | 22.42 | 20.72 | 5.19 | 18.21 | 121.81 | 213.08 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.10 | 31-JAN-14:00 | 12.97 | 6.70 | 5.70 | 12.22 | 200.50 | 90.50 |
February | 25.00 | 26-FEB-14:00 | 12.75 | 1.70 | 4.10 | 8.15 | 91.50 | 816.00 |
March | 27.80 | 30-MAR-13:00 | 17.87 | 12.20 | 5.70 | 16.30 | 231.50 | 710.50 |
April | 28.90 | 17-APR-14:20 | 16.56 | 8.13 | 2.03 | 13.35 | 125.83 | 887.67 |
May | 30.60 | 19-MAY-13:00 | 18.49 | 11.70 | 4.60 | 15.76 | 140.00 | 875.50 |
June | 34.40 | 06-JUN-14:00 | 22.39 | 17.20 | 8.20 | 22.13 | 251.00 | 561.00 |
July | 36.70 | 08-JUL-14:00 | 23.91 | 18.90 | 2.10 | 24.66 | 274.00 | 567.00 |
August | 35.00 | 01-AUG-14:00 | 23.84 | 19.40 | 2.60 | 26.15 | 306.00 | 508.00 |
September | 31.70 | 07-SEP-15:09 | 23.05 | 19.60 | 4.02 | 22.55 | 218.67 | 591.33 |
October | 30.00 | 10-OCT-15:00 | 20.56 | 16.10 | 3.60 | 17.57 | 97.00 | 561.00 |
November | 24.40 | 05-NOV-15:00 | 17.95 | 14.40 | 2.10 | 14.10 | 117.50 | 361.50 |
December | 22.80 | 12-DEC-14:20 | 16.78 | 13.33 | 5.20 | 13.35 | 144.17 | 433.83 |
Annual Sum or Average | ||||||||
Minimum of Months | 21.10 | 12.75 | 1.70 | 2.03 | 8.15 | 91.50 | 90.50 | |
Maximum of Months | 36.70 | 23.91 | 19.60 | 8.20 | 26.15 | 306.00 | 887.67 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -6.7 | 14-JAN-06:10 | -7.8 | -10.6 | 4.95 | -24.7 | 0.00 | 0.00 |
February | -12.8 | 12-FEB-06:00 | -13.8 | -18.3 | 7.20 | -30.1 | 0.00 | 0.00 |
March | 1.10 | 19-MAR-06:00 | -1.5 | -6.1 | 0.00 | -16.2 | 17.00 | 290.50 |
April | 0.00 | 06-APR-04:00 | -1.1 | -2.8 | 3.10 | -16.5 | 0.00 | 0.00 |
May | 7.80 | 11-MAY-05:00 | 5.45 | 2.80 | 4.10 | -7.8 | 21.50 | 204.50 |
June | 11.10 | 10-JUN-04:00 | 8.73 | 6.70 | 0.00 | -2.5 | 0.00 | 0.00 |
July | 17.20 | 28-JUL-22:00 | 16.88 | 16.70 | 4.10 | 14.28 | 0.00 | 0.00 |
August | 18.30 | 25-AUG-05:00 | 17.20 | 16.70 | 3.60 | 5.13 | 0.00 | 0.00 |
September | 11.70 | 29-SEP-03:00 | 11.07 | 10.60 | 2.60 | -2.3 | 0.00 | 0.00 |
October | 2.20 | 26-OCT-04:00 | 1.95 | 1.70 | 3.10 | -13.4 | 0.00 | 0.00 |
November | -3.3 | 22-NOV-05:00 | -4.0 | -5.6 | 5.20 | -20.2 | 0.00 | 0.00 |
December | -5.6 | 18-DEC-07:00 | -7.3 | -11.7 | 2.60 | -22.7 | 17.00 | 320.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -12.8 | -13.8 | -18.3 | 0.00 | -30.1 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 17.20 | 16.70 | 7.20 | 14.28 | 21.50 | 320.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.51 | 19-JAN-21:00 | 18.30 | 15.60 | 8.80 | 15.21 | 0.00 | 0.00 |
February | 15.81 | 18-FEB-15:00 | 17.20 | 15.00 | 5.20 | 13.91 | 73.00 | 1.00 |
March | 18.16 | 30-MAR-12:30 | 25.85 | 13.85 | 5.45 | 15.39 | 323.00 | 600.00 |
April | 20.01 | 04-APR-13:00 | 25.00 | 17.80 | 9.30 | 18.64 | 307.00 | 197.50 |
May | 22.34 | 30-MAY-17:00 | 27.80 | 20.00 | 4.10 | 21.96 | 97.50 | 79.50 |
June | 24.32 | 23-JUN-11:39 | 31.13 | 21.87 | 4.83 | 22.98 | 338.17 | 565.17 |
July | 25.06 | 07-JUL-11:00 | 33.30 | 22.20 | 3.60 | 20.75 | 116.50 | 900.00 |
August | 25.13 | 19-AUG-16:00 | 30.00 | 23.30 | 3.10 | 23.66 | 197.00 | 136.50 |
September | 24.10 | 09-SEP-10:00 | 30.60 | 21.70 | 2.60 | 21.27 | 236.00 | 482.00 |
October | 23.20 | 18-OCT-15:00 | 25.60 | 22.20 | 5.70 | 23.82 | 159.00 | 2.00 |
November | 18.88 | 19-NOV-14:00 | 24.40 | 16.10 | 8.20 | 13.91 | 143.00 | 384.50 |
December | 17.57 | 13-DEC-10:00 | 19.40 | 16.70 | 4.60 | 14.47 | 227.50 | 77.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.81 | 17.20 | 13.85 | 2.60 | 13.91 | 0.00 | 0.00 | |
Maximum of Months | 25.13 | 33.30 | 23.30 | 9.30 | 23.82 | 338.17 | 900.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 15.60 | 19-JAN-17:00 | 17.20 | 16.13 | 6.70 | 14.10 | 0.00 | 0.00 |
February | 15.00 | 18-FEB-16:19 | 17.20 | 15.81 | 5.53 | 13.91 | 50.33 | 1.00 |
March | 16.10 | 31-MAR-10:00 | 21.70 | 18.06 | 13.90 | 18.64 | 268.00 | 8.00 |
April | 17.80 | 04-APR-09:20 | 20.77 | 18.74 | 7.53 | 16.79 | 242.00 | 111.50 |
May | 20.60 | 30-MAY-19:00 | 25.00 | 21.79 | 2.60 | 12.41 | 0.00 | 0.00 |
June | 22.80 | 18-JUN-16:00 | 28.30 | 24.23 | 0.00 | 24.66 | 140.50 | 115.50 |
July | 23.30 | 26-JUL-09:00 | 26.10 | 24.10 | 3.60 | 24.66 | 338.00 | 251.50 |
August | 23.90 | 08-AUG-19:00 | 26.10 | 24.51 | 1.50 | 24.83 | 0.00 | 0.00 |
September | 23.30 | 16-SEP-16:00 | 25.60 | 23.89 | 2.10 | 22.13 | 108.00 | 57.50 |
October | 22.20 | 18-OCT-14:00 | 25.00 | 23.04 | 4.60 | 23.32 | 234.50 | 2.00 |
November | 17.20 | 04-NOV-13:00 | 17.80 | 17.48 | 3.60 | 15.02 | 276.50 | 2.50 |
December | 16.70 | 13-DEC-16:19 | 17.03 | 16.82 | 2.93 | 14.10 | 54.00 | 4.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.00 | 17.03 | 15.81 | 0.00 | 12.41 | 0.00 | 0.00 | |
Maximum of Months | 23.90 | 28.30 | 24.51 | 13.90 | 24.83 | 338.00 | 251.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 13.74 | 22.89 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 13.65 | 27.55 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 15.17 | 38.46 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 17.98 | 47.59 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 21.32 | 52.44 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 24.28 | 55.84 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 26.07 | 52.33 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 26.20 | 48.31 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 24.63 | 36.35 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 21.78 | 31.91 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 18.45 | 24.33 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 15.51 | 20.76 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 19.94 | 38.29 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 13.65 | 20.76 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 26.20 | 55.84 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH LAUNDRY G WATER HEATER
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.117702E+12 | -0.115869E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.183295E+10 | 82.17 | 0.00 | 0.00 |
February | 0.106455E+12 | -0.104794E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.166068E+10 | 82.17 | 0.00 | 0.00 |
March | 0.115293E+12 | -0.113452E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.184136E+10 | 82.17 | 0.00 | 0.00 |
April | 0.106972E+12 | -0.105189E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.178321E+10 | 82.17 | 0.00 | 0.00 |
May | 0.104886E+12 | -0.103045E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.184129E+10 | 82.17 | 0.00 | 0.00 |
June | 0.966350E+11 | -0.948609E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.177416E+10 | 82.17 | 0.00 | 0.00 |
July | 0.968130E+11 | -0.949936E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.181938E+10 | 82.17 | 0.00 | 0.00 |
August | 0.965812E+11 | -0.947787E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.180259E+10 | 82.17 | 0.00 | 0.00 |
September | 0.960287E+11 | -0.942987E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.172995E+10 | 82.17 | 0.00 | 0.00 |
October | 0.104040E+12 | -0.102256E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.178427E+10 | 82.17 | 0.00 | 0.00 |
November | 0.106154E+12 | -0.104428E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.172658E+10 | 82.17 | 0.00 | 0.00 |
December | 0.114683E+12 | -0.112881E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.180230E+10 | 82.17 | 0.00 | 0.00 |
Annual Sum or Average | 0.126224E+13 | -0.124084E+13 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.213987E+11 | 82.17 | 0.00 | 0.00 |
Minimum of Months | 0.960287E+11 | -0.115869E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.184136E+10 | 82.17 | 0.00 | 0.00 |
Maximum of Months | 0.117702E+12 | -0.942987E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.166068E+10 | 82.17 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.804914E+10 | -0.788296E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -166183458.5 | 82.17 | 0.00 | 0.00 |
February | 0.727334E+10 | -0.712336E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -149983746.2 | 82.17 | 0.00 | 0.00 |
March | 0.804736E+10 | -0.788155E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -165808018.9 | 82.17 | 0.00 | 0.00 |
April | 0.779851E+10 | -0.763820E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -160310306.9 | 82.17 | 0.00 | 0.00 |
May | 0.804842E+10 | -0.788296E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -165461466.7 | 82.17 | 0.00 | 0.00 |
June | 0.778970E+10 | -0.762976E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -159941078.2 | 82.17 | 0.00 | 0.00 |
July | 0.805661E+10 | -0.789140E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -165213376.3 | 82.17 | 0.00 | 0.00 |
August | 0.804813E+10 | -0.788296E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -165169732.0 | 82.17 | 0.00 | 0.00 |
September | 0.779965E+10 | -0.763961E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -160047744.6 | 82.17 | 0.00 | 0.00 |
October | 0.804726E+10 | -0.788155E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -165707166.1 | 82.17 | 0.00 | 0.00 |
November | 0.778190E+10 | -0.762132E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -160579829.5 | 82.17 | 0.00 | 0.00 |
December | 0.805748E+10 | -0.789140E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -166078736.8 | 82.17 | 0.00 | 0.00 |
Annual Sum or Average | 0.947975E+11 | -0.928470E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.195048E+10 | 82.17 | 0.00 | 0.00 |
Minimum of Months | 0.727334E+10 | -0.789140E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -166183458.5 | 82.17 | 0.00 | 0.00 |
Maximum of Months | 0.805748E+10 | -0.712336E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -149983746.2 | 82.17 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.692056E+11 | -0.675890E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.161662E+10 | 60.05 | 0.00 | 0.00 |
February | 0.626464E+11 | -0.611792E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.146726E+10 | 60.05 | 0.00 | 0.00 |
March | 0.671883E+11 | -0.655600E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.162828E+10 | 60.05 | 0.00 | 0.00 |
April | 0.610125E+11 | -0.594350E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.157747E+10 | 60.05 | 0.00 | 0.00 |
May | 0.581735E+11 | -0.565454E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.162818E+10 | 60.05 | 0.00 | 0.00 |
June | 0.521071E+11 | -0.505422E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.156493E+10 | 60.05 | 0.00 | 0.00 |
July | 0.511597E+11 | -0.495619E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.159780E+10 | 60.05 | 0.00 | 0.00 |
August | 0.510016E+11 | -0.494271E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.157453E+10 | 60.05 | 0.00 | 0.00 |
September | 0.515372E+11 | -0.500336E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.150364E+10 | 60.05 | 0.00 | 0.00 |
October | 0.573807E+11 | -0.558316E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.154914E+10 | 60.05 | 0.00 | 0.00 |
November | 0.602525E+11 | -0.587536E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.149898E+10 | 60.05 | 0.00 | 0.00 |
December | 0.665778E+11 | -0.650037E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.157412E+10 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.708243E+12 | -0.689462E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.187809E+11 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.510016E+11 | -0.675890E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.162828E+10 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.692056E+11 | -0.494271E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.146726E+10 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: LOBBY_FLR_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.87 | 0.86 | 01-JAN-09:30 | 5291.40 | 34.04 | 271.33 | 275.83 | 815.87 | 25.51 | 167.33 | 246.50 |
February | 263.00 | 0.88 | 0.86 | 01-FEB-13:39 | 4693.55 | 30.88 | 192.00 | 250.50 | 574.83 | 21.91 | 111.17 | 205.33 |
March | 351.67 | 0.88 | 0.86 | 01-MAR-09:09 | 1162.57 | 19.56 | 11.17 | 322.50 | 447.11 | 20.97 | 162.33 | 257.83 |
April | 369.33 | 0.88 | 0.86 | 01-APR-10:09 | 929.75 | 19.06 | 0.00 | 329.17 | 368.40 | 20.80 | 152.83 | 251.33 |
May | 407.00 | 0.88 | 0.86 | 01-MAY-07:00 | 880.72 | 19.02 | 0.00 | 363.00 | 349.28 | 20.75 | 190.50 | 279.17 |
June | 411.67 | 0.88 | 0.86 | 01-JUN-07:40 | 813.01 | 18.79 | 0.00 | 364.33 | 327.03 | 20.53 | 175.17 | 263.33 |
July | 411.00 | 0.88 | 0.86 | 01-JUL-08:39 | 860.31 | 18.88 | 0.00 | 369.00 | 343.09 | 20.61 | 208.67 | 277.83 |
August | 390.50 | 0.88 | 0.86 | 01-AUG-08:20 | 1065.38 | 19.54 | 0.83 | 355.17 | 416.56 | 21.25 | 236.33 | 289.83 |
September | 298.50 | 0.88 | 0.86 | 01-SEP-08:09 | 1120.56 | 19.48 | 0.17 | 312.67 | 442.39 | 21.21 | 176.83 | 239.67 |
October | 293.50 | 0.88 | 0.86 | 01-OCT-10:39 | 2703.03 | 24.73 | 106.17 | 294.50 | 457.32 | 21.05 | 108.67 | 222.50 |
November | 299.00 | 0.87 | 0.86 | 01-NOV-09:09 | 5262.95 | 34.79 | 286.00 | 275.67 | 661.27 | 25.18 | 182.17 | 246.00 |
December | 285.17 | 0.87 | 0.86 | 01-DEC-07:00 | 4951.97 | 34.55 | 270.50 | 271.83 | 914.41 | 26.67 | 174.83 | 236.67 |
Annual Sum or Average | 4071.00 | 0.88 | 2235.57 | 23.61 | 1138.17 | 3784.17 | 488.05 | 21.99 | 2046.83 | 3016.00 | ||
Minimum of Months | 263.00 | 0.87 | 0.86 | 813.01 | 18.79 | 0.00 | 250.50 | 327.03 | 20.53 | 108.67 | 205.33 | |
Maximum of Months | 411.67 | 0.88 | 0.86 | 5291.40 | 34.79 | 286.00 | 369.00 | 914.41 | 26.67 | 236.33 | 289.83 |
Report: DaylightingReportMonthly
For: CAFE_FLR_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.25 | 0.22 | 01-JAN-08:00 | 5610.83 | 34.17 | 273.00 | 283.33 | 1134.61 | 25.42 | 177.00 | 265.50 |
February | 263.00 | 0.28 | 0.22 | 01-FEB-10:30 | 4997.31 | 30.97 | 193.17 | 261.17 | 877.96 | 21.97 | 111.50 | 226.17 |
March | 351.67 | 0.27 | 0.22 | 01-MAR-08:39 | 1409.85 | 19.99 | 34.33 | 334.00 | 693.58 | 21.25 | 180.50 | 301.33 |
April | 369.33 | 0.28 | 0.22 | 01-APR-08:20 | 1112.00 | 19.73 | 14.00 | 344.83 | 550.07 | 21.25 | 191.67 | 306.67 |
May | 407.00 | 0.28 | 0.22 | 01-MAY-07:30 | 1027.85 | 19.84 | 16.83 | 384.00 | 495.86 | 21.34 | 258.00 | 335.00 |
June | 411.67 | 0.28 | 0.22 | 01-JUN-06:00 | 947.65 | 19.65 | 13.17 | 383.33 | 461.17 | 21.17 | 242.33 | 336.33 |
July | 411.00 | 0.28 | 0.22 | 01-JUL-07:10 | 999.10 | 19.73 | 22.33 | 387.00 | 481.35 | 21.23 | 258.17 | 338.50 |
August | 390.50 | 0.27 | 0.22 | 01-AUG-07:10 | 1236.39 | 20.27 | 57.67 | 369.83 | 586.92 | 21.77 | 278.67 | 333.00 |
September | 298.50 | 0.28 | 0.22 | 01-SEP-07:30 | 1332.47 | 20.05 | 36.17 | 325.67 | 653.62 | 21.58 | 199.00 | 291.83 |
October | 293.50 | 0.27 | 0.22 | 01-OCT-08:20 | 3000.10 | 24.84 | 115.67 | 307.00 | 751.50 | 21.10 | 119.67 | 268.50 |
November | 299.00 | 0.26 | 0.22 | 01-NOV-08:09 | 5569.13 | 34.88 | 287.17 | 282.50 | 965.39 | 25.14 | 184.17 | 267.00 |
December | 285.17 | 0.25 | 0.22 | 01-DEC-07:49 | 5276.78 | 34.65 | 272.33 | 280.33 | 1236.96 | 26.58 | 181.33 | 259.67 |
Annual Sum or Average | 4071.00 | 0.27 | 2456.83 | 24.11 | 1335.83 | 3943.00 | 708.31 | 22.32 | 2382.00 | 3529.50 | ||
Minimum of Months | 263.00 | 0.25 | 0.22 | 947.65 | 19.65 | 13.17 | 261.17 | 461.17 | 21.10 | 111.50 | 226.17 | |
Maximum of Months | 411.67 | 0.28 | 0.22 | 5610.83 | 34.88 | 287.17 | 387.00 | 1236.96 | 26.58 | 278.67 | 338.50 |
Report: DaylightingReportMonthly
For: DINING_FLR_6_DAYLCTRL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.72 | 0.60 | 01-JAN-11:20 | 331.85 | 14.09 | 0.00 | 214.67 | 153.87 | 17.52 | 0.00 | 58.67 |
February | 263.00 | 0.72 | 0.60 | 01-FEB-13:50 | 342.24 | 14.28 | 0.00 | 202.17 | 162.28 | 17.66 | 0.00 | 76.83 |
March | 351.67 | 0.67 | 0.60 | 01-MAR-09:30 | 443.23 | 15.80 | 0.00 | 316.00 | 206.82 | 19.04 | 0.00 | 177.00 |
April | 369.33 | 0.65 | 0.60 | 01-APR-10:39 | 538.88 | 16.69 | 0.00 | 342.17 | 245.36 | 19.89 | 7.17 | 228.83 |
May | 407.00 | 0.62 | 0.60 | 01-MAY-07:40 | 686.13 | 18.19 | 18.33 | 391.67 | 312.86 | 21.71 | 109.83 | 350.17 |
June | 411.67 | 0.62 | 0.60 | 01-JUN-06:40 | 763.10 | 19.79 | 55.83 | 393.67 | 350.28 | 23.20 | 188.83 | 367.50 |
July | 411.00 | 0.62 | 0.60 | 01-JUL-06:10 | 775.45 | 18.71 | 27.50 | 395.00 | 338.79 | 22.57 | 176.17 | 356.17 |
August | 390.50 | 0.63 | 0.60 | 01-AUG-06:00 | 680.92 | 17.58 | 0.00 | 370.83 | 308.38 | 20.75 | 78.17 | 327.83 |
September | 298.50 | 0.65 | 0.60 | 01-SEP-07:40 | 498.93 | 16.52 | 0.00 | 316.17 | 234.50 | 19.70 | 0.17 | 207.00 |
October | 293.50 | 0.71 | 0.60 | 01-OCT-10:50 | 348.12 | 14.72 | 0.00 | 232.50 | 170.61 | 18.12 | 0.00 | 102.00 |
November | 299.00 | 0.71 | 0.60 | 01-NOV-10:30 | 343.34 | 14.35 | 0.00 | 242.83 | 161.75 | 17.72 | 0.00 | 63.00 |
December | 285.17 | 0.72 | 0.60 | 01-DEC-12:30 | 321.40 | 14.14 | 0.00 | 216.67 | 151.18 | 17.60 | 0.00 | 41.83 |
Annual Sum or Average | 4071.00 | 0.66 | 531.76 | 16.52 | 101.67 | 3634.33 | 244.04 | 19.91 | 560.33 | 2356.83 | ||
Minimum of Months | 263.00 | 0.62 | 0.60 | 321.40 | 14.09 | 0.00 | 202.17 | 151.18 | 17.52 | 0.00 | 41.83 | |
Maximum of Months | 411.67 | 0.72 | 0.60 | 775.45 | 19.79 | 55.83 | 395.00 | 350.28 | 23.20 | 188.83 | 367.50 |
Report: DaylightingReportMonthly
For: BANQUET_FLR_6_DAYLCTRL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.72 | 0.60 | 01-JAN-11:20 | 331.85 | 14.09 | 0.00 | 214.67 | 153.87 | 17.52 | 0.00 | 58.67 |
February | 263.00 | 0.72 | 0.60 | 01-FEB-13:50 | 342.24 | 14.28 | 0.00 | 202.17 | 162.28 | 17.66 | 0.00 | 76.83 |
March | 351.67 | 0.67 | 0.60 | 01-MAR-09:30 | 443.23 | 15.80 | 0.00 | 316.00 | 206.82 | 19.04 | 0.00 | 177.00 |
April | 369.33 | 0.65 | 0.60 | 01-APR-10:39 | 538.88 | 16.69 | 0.00 | 342.17 | 245.36 | 19.89 | 7.17 | 228.83 |
May | 407.00 | 0.62 | 0.60 | 01-MAY-07:40 | 686.13 | 18.19 | 18.33 | 391.67 | 312.86 | 21.71 | 109.83 | 350.17 |
June | 411.67 | 0.62 | 0.60 | 01-JUN-06:40 | 763.10 | 19.79 | 55.83 | 393.67 | 350.28 | 23.20 | 188.83 | 367.50 |
July | 411.00 | 0.62 | 0.60 | 01-JUL-06:10 | 775.45 | 18.71 | 27.50 | 395.00 | 338.79 | 22.57 | 176.17 | 356.17 |
August | 390.50 | 0.63 | 0.60 | 01-AUG-06:00 | 680.92 | 17.58 | 0.00 | 370.83 | 308.38 | 20.75 | 78.17 | 327.83 |
September | 298.50 | 0.65 | 0.60 | 01-SEP-07:40 | 498.93 | 16.52 | 0.00 | 316.17 | 234.50 | 19.70 | 0.17 | 207.00 |
October | 293.50 | 0.71 | 0.60 | 01-OCT-10:50 | 348.12 | 14.72 | 0.00 | 232.50 | 170.61 | 18.12 | 0.00 | 102.00 |
November | 299.00 | 0.71 | 0.60 | 01-NOV-10:30 | 343.34 | 14.35 | 0.00 | 242.83 | 161.75 | 17.72 | 0.00 | 63.00 |
December | 285.17 | 0.72 | 0.60 | 01-DEC-12:30 | 321.40 | 14.14 | 0.00 | 216.67 | 151.18 | 17.60 | 0.00 | 41.83 |
Annual Sum or Average | 4071.00 | 0.66 | 531.76 | 16.52 | 101.67 | 3634.33 | 244.04 | 19.91 | 560.33 | 2356.83 | ||
Minimum of Months | 263.00 | 0.62 | 0.60 | 321.40 | 14.09 | 0.00 | 202.17 | 151.18 | 17.52 | 0.00 | 41.83 | |
Maximum of Months | 411.67 | 0.72 | 0.60 | 775.45 | 19.79 | 55.83 | 395.00 | 350.28 | 23.20 | 188.83 | 367.50 |
Report: CoilReportMonthly
For: FLR_3_DOAS HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.694661E+09 | 4203.12 | 07-JAN-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.591939E+09 | 5201.58 | 12-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 36515003.30 | 1148.19 | 22-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.122900E+09 | 2127.20 | 18-DEC-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144601E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.694661E+09 | 5201.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.100535E+12 | 147137.92 | 15-JAN-22:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.673384E+11 | 139113.24 | 08-FEB-21:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.508864E+11 | 135504.07 | 18-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.181049E+11 | 143301.28 | 05-APR-22:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.211447E+10 | 58503.70 | 11-MAY-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.276954E+09 | 42370.49 | 08-JUN-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 67857172.32 | 40152.97 | 14-SEP-14:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.244770E+11 | 136110.74 | 26-OCT-06:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.678058E+11 | 154390.91 | 21-NOV-23:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.115958E+12 | 145283.31 | 03-DEC-21:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.447564E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.115958E+12 | 154390.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.439328E+09 | 2764.09 | 01-JAN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.254880E+10 | 5083.05 | 12-FEB-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.606438E+10 | 6804.79 | 19-MAR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.940863E+10 | 8408.68 | 30-APR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.577338E+10 | 7227.13 | 01-MAY-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.533140E+09 | 4250.40 | 01-JUN-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.247677E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.940863E+10 | 8408.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.320911E+10 | 2717.20 | 08-JAN-05:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.227977E+10 | 2989.49 | 12-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.121048E+10 | 1723.79 | 22-MAR-09:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.772907E+09 | 1715.93 | 06-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.337756E+09 | 1042.97 | 11-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 50038440.72 | 645.03 | 08-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 34521162.17 | 557.61 | 29-JUL-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.172711E+09 | 961.22 | 29-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.859154E+09 | 1605.14 | 31-OCT-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.140768E+10 | 2132.70 | 21-NOV-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.243703E+10 | 2270.12 | 01-DEC-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.127712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.320911E+10 | 2989.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.838966E+09 | 1005.76 | 08-JAN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.531136E+09 | 867.50 | 06-FEB-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.177091E+09 | 643.29 | 23-MAR-09:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 70054239.38 | 490.45 | 06-APR-09:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 9018010.79 | 183.08 | 01-MAY-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5047532.51 | 170.27 | 30-SEP-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 79574514.89 | 609.40 | 30-OCT-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.182977E+09 | 598.60 | 22-NOV-10:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.509115E+09 | 759.05 | 25-DEC-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.240298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.838966E+09 | 1005.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.225432E+10 | 1455.20 | 08-JAN-13:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.151639E+10 | 1419.92 | 12-FEB-13:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.718209E+09 | 858.20 | 19-MAR-12:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.260912E+09 | 737.08 | 06-APR-10:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17063570.37 | 240.04 | 11-MAY-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.235102E+09 | 672.91 | 26-OCT-09:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.732029E+09 | 988.04 | 22-NOV-11:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.155704E+10 | 1135.42 | 18-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.729107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.225432E+10 | 1455.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.170555E+10 | 1004.69 | 08-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.118902E+10 | 1034.19 | 12-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.639952E+09 | 617.27 | 19-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.263900E+09 | 545.68 | 06-APR-09:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 30497676.97 | 231.54 | 11-MAY-09:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2548486.98 | 127.69 | 30-SEP-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.270679E+09 | 512.57 | 26-OCT-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.679473E+09 | 701.08 | 22-NOV-08:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.126084E+10 | 813.68 | 18-DEC-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.604245E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.170555E+10 | 1034.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.563254E+10 | 8299.22 | 09-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.461047E+10 | 8280.67 | 13-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.428026E+10 | 7431.74 | 23-MAR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363065E+10 | 7202.37 | 06-APR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.329479E+10 | 6680.69 | 01-MAY-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.265278E+10 | 6234.30 | 10-JUN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.252352E+10 | 6511.59 | 29-JUL-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.246875E+10 | 5906.27 | 21-AUG-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.300904E+10 | 6695.06 | 30-SEP-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.393646E+10 | 7281.57 | 30-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.432439E+10 | 7654.70 | 22-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.512512E+10 | 8032.98 | 18-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.454888E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.246875E+10 | 5906.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.563254E+10 | 8299.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.358940E+10 | 7235.07 | 09-JAN-09:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.239127E+10 | 6287.82 | 06-FEB-10:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.106908E+10 | 5207.23 | 22-MAR-09:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.610808E+09 | 4739.15 | 06-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.261425E+09 | 3054.92 | 11-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 29429545.53 | 1753.06 | 08-JUN-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 29247276.29 | 1221.79 | 28-JUL-12:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.151999E+09 | 2891.76 | 29-SEP-09:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.754496E+09 | 5041.12 | 30-OCT-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.996165E+09 | 5151.33 | 30-NOV-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.227615E+10 | 5571.42 | 25-DEC-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.121595E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.358940E+10 | 7235.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.838993E+10 | 17787.60 | 08-JAN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.544817E+10 | 15643.01 | 07-FEB-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.180878E+10 | 11229.92 | 22-MAR-11:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.863142E+09 | 7784.12 | 06-APR-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.147092E+09 | 3052.10 | 11-MAY-09:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 58949531.00 | 2799.22 | 29-SEP-12:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.901119E+09 | 10991.20 | 30-OCT-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.160535E+10 | 10917.19 | 30-NOV-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.444982E+10 | 13831.17 | 25-DEC-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.236724E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.838993E+10 | 17787.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.124304E+11 | 9865.29 | 07-JAN-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.805300E+10 | 8730.75 | 12-FEB-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.262865E+10 | 6377.61 | 23-MAR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.642607E+09 | 4776.39 | 06-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6938167.47 | 736.61 | 01-MAY-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1037363.63 | 411.21 | 30-SEP-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.160494E+10 | 6460.32 | 30-OCT-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.422493E+10 | 7008.07 | 22-NOV-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.908293E+10 | 7543.00 | 25-DEC-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.386754E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.124304E+11 | 9865.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.839113E+10 | 6095.28 | 08-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.555009E+10 | 6637.72 | 12-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.235852E+10 | 3841.86 | 19-MAR-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.907155E+09 | 3653.72 | 06-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 71762693.64 | 1352.56 | 11-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 49698283.27 | 883.48 | 29-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.156814E+10 | 3585.34 | 26-OCT-06:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.347763E+10 | 4745.64 | 22-NOV-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.632874E+10 | 5256.24 | 18-DEC-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.287029E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.839113E+10 | 6637.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.790873E+09 | 3926.32 | 09-JAN-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.422128E+09 | 3587.26 | 03-FEB-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6447644.51 | 576.03 | 22-MAR-11:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2299670.65 | 492.12 | 30-OCT-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 57605235.03 | 2115.02 | 22-NOV-09:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.272953E+09 | 3620.98 | 04-DEC-09:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.155231E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.790873E+09 | 3926.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.325763E+09 | 2448.66 | 08-JAN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158547E+09 | 3402.82 | 13-FEB-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2950092.55 | 287.06 | 22-NOV-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 46498426.39 | 2022.07 | 18-DEC-09:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.533758E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.325763E+09 | 3402.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.458166E+09 | 3095.43 | 08-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.271634E+09 | 3467.30 | 12-FEB-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 50839450.85 | 1486.95 | 19-MAR-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 18856874.30 | 1516.86 | 06-APR-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 418838.22 | 249.05 | 11-MAY-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 84584.89 | 107.52 | 29-SEP-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 18350690.21 | 1389.20 | 26-OCT-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.107727E+09 | 2225.80 | 22-NOV-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.262523E+09 | 2520.74 | 18-DEC-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.118860E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.458166E+09 | 3467.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.387552E+10 | 5842.73 | 01-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.231634E+10 | 5842.73 | 01-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.526240E+09 | 5842.73 | 18-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.160893E+09 | 5842.73 | 06-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11704320.28 | 5461.93 | 24-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6245661.58 | 4571.24 | 04-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 4516976.90 | 3773.66 | 03-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 4694528.22 | 4291.06 | 09-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 15972327.58 | 4840.19 | 28-SEP-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.353743E+09 | 5842.73 | 25-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.982940E+09 | 5842.73 | 20-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.250372E+10 | 5842.73 | 01-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.107625E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 4516976.90 | 3773.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.387552E+10 | 5842.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.487838E+10 | 5855.20 | 01-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.294897E+10 | 5855.20 | 01-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.694856E+09 | 5855.20 | 03-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.179916E+09 | 5855.20 | 06-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 9490545.06 | 4524.78 | 13-MAY-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3338004.25 | 4224.91 | 07-JUN-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1809284.04 | 1792.58 | 15-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2206210.63 | 4260.20 | 09-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11144775.10 | 4399.22 | 23-SEP-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.450392E+09 | 5855.20 | 25-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.145433E+10 | 5855.20 | 07-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.335433E+10 | 5855.20 | 01-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.139892E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1809284.04 | 1792.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.487838E+10 | 5855.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.175341E+11 | 33918.13 | 01-JAN-22:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.997155E+10 | 33918.13 | 01-FEB-01:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.124242E+10 | 33918.13 | 02-MAR-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.694165E+09 | 33918.13 | 05-APR-22:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 67812515.50 | 32051.70 | 24-MAY-15:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 15389199.27 | 26422.78 | 07-JUN-15:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6786661.12 | 22593.42 | 28-JUL-15:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 26657019.38 | 20214.66 | 30-AUG-21:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 49910583.85 | 25982.14 | 19-SEP-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.407281E+09 | 33918.13 | 23-OCT-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.297386E+10 | 33918.13 | 07-NOV-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.902984E+10 | 33918.13 | 01-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.420198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 6786661.12 | 20214.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.175341E+11 | 33918.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.392657E+10 | 5817.25 | 01-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.230604E+10 | 5817.25 | 01-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.553677E+09 | 5817.25 | 22-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.163043E+09 | 4846.33 | 03-APR-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 8376752.86 | 3504.58 | 09-MAY-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 58114.69 | 492.11 | 23-JUN-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 814132.86 | 2839.79 | 28-JUL-18:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 111849.64 | 443.07 | 24-AUG-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 10433445.09 | 3319.05 | 01-SEP-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.368725E+09 | 5817.25 | 25-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.979587E+09 | 5817.25 | 20-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.246664E+10 | 5817.25 | 01-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.107841E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 58114.69 | 443.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.392657E+10 | 5817.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.493923E+10 | 5829.72 | 01-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.288601E+10 | 5829.72 | 01-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.715223E+09 | 5829.72 | 22-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.186159E+09 | 4914.82 | 03-APR-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5352208.58 | 3687.98 | 15-MAY-21:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 951020.89 | 2663.43 | 07-JUN-21:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 395521.08 | 1518.55 | 29-JUL-08:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 538488.67 | 1580.39 | 30-AUG-21:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 7594091.59 | 3862.94 | 29-SEP-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.474692E+09 | 5829.72 | 25-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.142225E+10 | 5829.72 | 01-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.330484E+10 | 5829.72 | 01-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.139432E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 395521.08 | 1518.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.493923E+10 | 5829.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.142377E+10 | 1793.86 | 01-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.872953E+09 | 1793.86 | 01-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.241272E+09 | 1793.86 | 06-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 78532441.39 | 1793.86 | 06-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5819840.39 | 1275.84 | 24-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1562557.55 | 1109.23 | 15-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1103805.43 | 987.88 | 03-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1246132.90 | 1049.79 | 26-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 8436844.13 | 1181.77 | 28-SEP-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.167094E+09 | 1793.86 | 25-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.419908E+09 | 1793.86 | 13-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.966912E+09 | 1793.86 | 01-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.418861E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1103805.43 | 987.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.142377E+10 | 1793.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.173883E+10 | 1798.79 | 01-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.107209E+10 | 1798.79 | 01-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.293362E+09 | 1798.79 | 03-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 80116091.26 | 1798.79 | 06-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2711991.51 | 1143.24 | 24-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 883015.10 | 1300.67 | 10-JUN-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 310405.97 | 538.60 | 28-JUL-21:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 528334.38 | 1075.12 | 09-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5147009.97 | 1330.13 | 28-SEP-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.201517E+09 | 1798.79 | 13-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.578702E+09 | 1798.79 | 01-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.123579E+10 | 1798.79 | 01-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.520999E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 310405.97 | 538.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.173883E+10 | 1798.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.396693E+10 | 8595.94 | 01-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.228770E+10 | 8595.94 | 01-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.503978E+09 | 8595.94 | 18-MAR-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.214539E+09 | 8595.94 | 06-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 14971321.80 | 6330.61 | 10-MAY-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2750352.49 | 3852.63 | 08-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 2967298.38 | 2967.98 | 28-JUL-18:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2331240.96 | 2433.69 | 11-AUG-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 15706744.29 | 4062.51 | 19-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.285887E+09 | 8595.94 | 25-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.745599E+09 | 8595.94 | 08-NOV-00:21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.223288E+10 | 8595.94 | 01-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.102762E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 2331240.96 | 2433.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.396693E+10 | 8595.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.697973E+09 | 0.528688E+09 | 13371.86 | 19-JAN-16:03 | 8414.77 | 0.03 |
February | 0.00 | 0.00 | 0.197469E+10 | 0.195126E+10 | 16170.00 | 28-FEB-16:01 | 16170.00 | 0.04 |
March | 0.00 | 0.00 | 0.711478E+10 | 0.650656E+10 | 22731.69 | 28-MAR-15:01 | 16455.60 | 0.20 |
April | 0.00 | 0.00 | 0.142755E+11 | 0.114850E+11 | 29104.22 | 30-APR-15:01 | 15804.81 | 0.46 |
May | 0.00 | 0.00 | 0.300411E+11 | 0.200519E+11 | 39092.00 | 30-MAY-21:50 | 15428.41 | 0.70 |
June | 0.00 | 0.00 | 0.443953E+11 | 0.279599E+11 | 45326.50 | 29-JUN-08:03 | 17336.41 | 0.73 |
July | 0.00 | 0.00 | 0.555144E+11 | 0.314992E+11 | 49419.14 | 26-JUL-08:03 | 16840.26 | 0.79 |
August | 0.00 | 0.00 | 0.567570E+11 | 0.326592E+11 | 47944.72 | 24-AUG-08:61 | 17407.09 | 0.79 |
September | 0.00 | 0.00 | 0.397304E+11 | 0.243946E+11 | 45948.22 | 17-SEP-08:03 | 17077.80 | 0.76 |
October | 0.00 | 0.00 | 0.161233E+11 | 0.100475E+11 | 45040.26 | 18-OCT-21:40 | 16176.17 | 0.36 |
November | 0.00 | 0.00 | 0.572898E+10 | 0.416618E+10 | 27191.69 | 19-NOV-24:00 | 13347.23 | 0.16 |
December | 0.00 | 0.00 | 0.118613E+10 | 0.941126E+09 | 19688.72 | 13-DEC-11:00 | 9728.33 | 0.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.273540E+12 | 0.172191E+12 | 0.43 | |||
Minimum of Months | 0.00 | 0.00 | 0.697973E+09 | 0.528688E+09 | 13371.86 | 8414.77 | 0.03 | |
Maximum of Months | 0.00 | 0.00 | 0.567570E+11 | 0.326592E+11 | 49419.14 | 17407.09 | 0.79 |
Report: CoilReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.197359E+11 | 0.145909E+11 | 194711.61 | 19-JAN-22:00 | 99912.88 | 0.08 |
February | 0.00 | 0.00 | 0.585295E+11 | 0.504319E+11 | 178171.02 | 26-FEB-15:50 | 178171.02 | 0.16 |
March | 0.00 | 0.00 | 0.140026E+12 | 0.123605E+12 | 246313.88 | 31-MAR-10:50 | 141901.55 | 0.31 |
April | 0.00 | 0.00 | 0.265050E+12 | 0.210801E+12 | 296796.21 | 21-APR-18:06 | 153939.42 | 0.69 |
May | 0.00 | 0.00 | 0.491269E+12 | 0.322746E+12 | 419610.41 | 30-MAY-21:20 | 185169.15 | 0.92 |
June | 0.00 | 0.00 | 0.688613E+12 | 0.420656E+12 | 465802.48 | 26-JUN-21:00 | 193349.26 | 0.92 |
July | 0.00 | 0.00 | 0.876468E+12 | 0.469958E+12 | 487260.69 | 18-JUL-19:04 | 192806.21 | 1.00 |
August | 0.00 | 0.00 | 0.903697E+12 | 0.489545E+12 | 486145.79 | 23-AUG-23:00 | 173884.57 | 1.00 |
September | 0.00 | 0.00 | 0.633046E+12 | 0.367710E+12 | 468173.39 | 27-SEP-18:09 | 182594.62 | 1.00 |
October | 0.00 | 0.00 | 0.277225E+12 | 0.177561E+12 | 504704.10 | 18-OCT-21:00 | 189570.50 | 0.60 |
November | 0.00 | 0.00 | 0.121794E+12 | 0.898072E+11 | 269829.35 | 27-NOV-19:20 | 140568.75 | 0.28 |
December | 0.00 | 0.00 | 0.360329E+11 | 0.265778E+11 | 221678.23 | 13-DEC-11:40 | 115507.50 | 0.13 |
Annual Sum or Average | 0.00 | 0.00 | 0.451149E+13 | 0.276399E+13 | 0.59 | |||
Minimum of Months | 0.00 | 0.00 | 0.197359E+11 | 0.145909E+11 | 178171.02 | 99912.88 | 0.08 | |
Maximum of Months | 0.00 | 0.00 | 0.903697E+12 | 0.489545E+12 | 504704.10 | 193349.26 | 1.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.133512E+09 | 0.109449E+09 | 14688.14 | 28-JAN-16:01 | 14688.14 | 0.02 |
February | 0.00 | 0.00 | 0.588845E+09 | 0.469659E+09 | 15089.28 | 19-FEB-16:02 | 10459.04 | 0.08 |
March | 0.00 | 0.00 | 0.224737E+10 | 0.140855E+10 | 15261.47 | 28-MAR-15:01 | 11450.61 | 0.32 |
April | 0.00 | 0.00 | 0.407613E+10 | 0.211202E+10 | 15748.58 | 03-APR-15:01 | 10822.66 | 0.70 |
May | 0.00 | 0.00 | 0.630776E+10 | 0.308681E+10 | 15892.85 | 27-MAY-08:62 | 10262.01 | 0.86 |
June | 0.00 | 0.00 | 0.868662E+10 | 0.473743E+10 | 16414.05 | 29-JUN-08:61 | 10531.38 | 0.94 |
July | 0.00 | 0.00 | 0.100227E+11 | 0.566264E+10 | 17031.30 | 30-JUL-08:62 | 10021.68 | 0.94 |
August | 0.00 | 0.00 | 0.105640E+11 | 0.601849E+10 | 16424.20 | 29-AUG-08:61 | 10520.95 | 0.96 |
September | 0.00 | 0.00 | 0.686065E+10 | 0.335577E+10 | 16600.67 | 17-SEP-08:61 | 10366.30 | 0.89 |
October | 0.00 | 0.00 | 0.327093E+10 | 0.152150E+10 | 16357.99 | 01-OCT-15:01 | 10562.29 | 0.61 |
November | 0.00 | 0.00 | 0.109890E+10 | 0.580470E+09 | 16078.54 | 04-NOV-15:01 | 10097.82 | 0.26 |
December | 0.00 | 0.00 | 0.302901E+09 | 0.186149E+09 | 15153.29 | 13-DEC-16:01 | 10250.50 | 0.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.541603E+11 | 0.292489E+11 | 0.56 | |||
Minimum of Months | 0.00 | 0.00 | 0.133512E+09 | 0.109449E+09 | 14688.14 | 10021.68 | 0.02 | |
Maximum of Months | 0.00 | 0.00 | 0.105640E+11 | 0.601849E+10 | 17031.30 | 14688.14 | 0.96 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 10667398.00 | 7400876.05 | 13796.72 | 20-JAN-16:01 | 10868.50 | 0.00 |
February | 0.00 | 0.00 | 0.113244E+09 | 74135124.00 | 14774.53 | 19-FEB-16:02 | 10099.47 | 0.04 |
March | 0.00 | 0.00 | 0.955902E+09 | 0.502937E+09 | 15275.11 | 28-MAR-15:01 | 11193.44 | 0.19 |
April | 0.00 | 0.00 | 0.259275E+10 | 0.122822E+10 | 15761.39 | 02-APR-15:01 | 10803.60 | 0.50 |
May | 0.00 | 0.00 | 0.494200E+10 | 0.246840E+10 | 16252.70 | 07-MAY-17:42 | 12455.09 | 0.64 |
June | 0.00 | 0.00 | 0.788125E+10 | 0.454366E+10 | 17405.05 | 26-JUN-08:21 | 10702.37 | 0.78 |
July | 0.00 | 0.00 | 0.909017E+10 | 0.542488E+10 | 17573.17 | 23-JUL-08:51 | 10344.21 | 0.79 |
August | 0.00 | 0.00 | 0.939230E+10 | 0.545053E+10 | 18385.58 | 20-AUG-07:52 | 10535.63 | 0.83 |
September | 0.00 | 0.00 | 0.514298E+10 | 0.249239E+10 | 16711.36 | 17-SEP-08:52 | 9725.33 | 0.67 |
October | 0.00 | 0.00 | 0.145608E+10 | 0.580994E+09 | 16545.82 | 18-OCT-21:52 | 9852.98 | 0.34 |
November | 0.00 | 0.00 | 0.220697E+09 | 0.102641E+09 | 15942.67 | 04-NOV-15:01 | 9777.37 | 0.09 |
December | 0.00 | 0.00 | 39185438.82 | 23415560.29 | 15169.61 | 13-DEC-16:01 | 9616.17 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.418372E+11 | 0.228996E+11 | 0.41 | |||
Minimum of Months | 0.00 | 0.00 | 10667398.00 | 7400876.05 | 13796.72 | 9616.17 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.939230E+10 | 0.545053E+10 | 18385.58 | 12455.09 | 0.83 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.138207E+10 | 0.113588E+10 | 22971.64 | 29-JAN-13:30 | 22971.64 | 0.02 |
February | 0.00 | 0.00 | 0.594838E+10 | 0.550006E+10 | 30939.90 | 26-FEB-14:25 | 30939.90 | 0.04 |
March | 0.00 | 0.00 | 0.180425E+11 | 0.110760E+11 | 31707.98 | 30-MAR-13:30 | 19767.79 | 0.39 |
April | 0.00 | 0.00 | 0.218781E+11 | 0.864923E+10 | 28127.60 | 15-APR-13:40 | 17580.26 | 0.75 |
May | 0.00 | 0.00 | 0.292406E+11 | 0.101412E+11 | 24574.51 | 19-MAY-19:10 | 13062.04 | 0.93 |
June | 0.00 | 0.00 | 0.386492E+11 | 0.153059E+11 | 28589.99 | 24-JUN-17:20 | 16445.06 | 0.98 |
July | 0.00 | 0.00 | 0.457626E+11 | 0.192990E+11 | 31961.66 | 08-JUL-17:25 | 20552.61 | 1.00 |
August | 0.00 | 0.00 | 0.526712E+11 | 0.243638E+11 | 35030.87 | 19-AUG-15:02 | 22839.02 | 1.00 |
September | 0.00 | 0.00 | 0.398279E+11 | 0.176051E+11 | 39128.80 | 24-SEP-12:30 | 31594.12 | 0.97 |
October | 0.00 | 0.00 | 0.285450E+11 | 0.133756E+11 | 42085.26 | 10-OCT-13:30 | 36477.40 | 0.76 |
November | 0.00 | 0.00 | 0.171645E+11 | 0.119831E+11 | 35203.66 | 06-NOV-13:40 | 26638.89 | 0.32 |
December | 0.00 | 0.00 | 0.754238E+10 | 0.579348E+10 | 33561.16 | 12-DEC-12:30 | 21511.02 | 0.11 |
Annual Sum or Average | 0.00 | 0.00 | 0.306654E+12 | 0.144228E+12 | 0.61 | |||
Minimum of Months | 0.00 | 0.00 | 0.138207E+10 | 0.113588E+10 | 22971.64 | 13062.04 | 0.02 | |
Maximum of Months | 0.00 | 0.00 | 0.526712E+11 | 0.243638E+11 | 42085.26 | 36477.40 | 1.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.163641E+10 | 0.808420E+09 | 93848.12 | 19-JAN-22:53 | 67008.20 | 0.07 |
February | 0.00 | 0.00 | 0.520130E+10 | 0.314354E+10 | 94034.66 | 18-FEB-09:02 | 72799.21 | 0.15 |
March | 0.00 | 0.00 | 0.148908E+11 | 0.907437E+10 | 93569.30 | 28-MAR-21:52 | 77042.90 | 0.29 |
April | 0.00 | 0.00 | 0.278714E+11 | 0.157248E+11 | 102494.66 | 30-APR-21:52 | 72094.39 | 0.49 |
May | 0.00 | 0.00 | 0.436160E+11 | 0.250817E+11 | 105793.66 | 07-MAY-17:42 | 78165.28 | 0.57 |
June | 0.00 | 0.00 | 0.593947E+11 | 0.364971E+11 | 111765.30 | 26-JUN-08:21 | 67203.07 | 0.72 |
July | 0.00 | 0.00 | 0.666538E+11 | 0.408607E+11 | 113947.84 | 23-JUL-08:51 | 67030.38 | 0.74 |
August | 0.00 | 0.00 | 0.664347E+11 | 0.395717E+11 | 121730.15 | 20-AUG-07:52 | 65203.21 | 0.77 |
September | 0.00 | 0.00 | 0.437892E+11 | 0.242126E+11 | 109201.95 | 17-SEP-08:52 | 65351.01 | 0.61 |
October | 0.00 | 0.00 | 0.212640E+11 | 0.985482E+10 | 111741.06 | 18-OCT-21:52 | 65563.74 | 0.51 |
November | 0.00 | 0.00 | 0.968461E+10 | 0.541972E+10 | 100647.76 | 05-NOV-21:52 | 69932.61 | 0.24 |
December | 0.00 | 0.00 | 0.335314E+10 | 0.174684E+10 | 97710.60 | 13-DEC-21:02 | 69744.75 | 0.11 |
Annual Sum or Average | 0.00 | 0.00 | 0.363790E+12 | 0.211996E+12 | 0.44 | |||
Minimum of Months | 0.00 | 0.00 | 0.163641E+10 | 0.808420E+09 | 93569.30 | 65203.21 | 0.07 | |
Maximum of Months | 0.00 | 0.00 | 0.666538E+11 | 0.408607E+11 | 121730.15 | 78165.28 | 0.77 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.119518E+09 | 88569479.38 | 13305.47 | 29-JAN-16:01 | 13305.47 | 0.03 |
February | 0.00 | 0.00 | 0.665348E+09 | 0.510437E+09 | 13483.36 | 19-FEB-16:02 | 9104.12 | 0.10 |
March | 0.00 | 0.00 | 0.197275E+10 | 0.110322E+10 | 13702.18 | 28-MAR-15:01 | 10520.68 | 0.36 |
April | 0.00 | 0.00 | 0.394105E+10 | 0.196839E+10 | 14262.48 | 02-APR-15:01 | 10078.13 | 0.72 |
May | 0.00 | 0.00 | 0.650623E+10 | 0.330127E+10 | 14478.91 | 27-MAY-08:62 | 9421.16 | 0.90 |
June | 0.00 | 0.00 | 0.891940E+10 | 0.496338E+10 | 14685.91 | 23-JUN-08:61 | 9750.92 | 0.97 |
July | 0.00 | 0.00 | 0.103854E+11 | 0.598159E+10 | 15430.62 | 30-JUL-08:62 | 9136.53 | 0.96 |
August | 0.00 | 0.00 | 0.106498E+11 | 0.616489E+10 | 14756.14 | 24-AUG-08:61 | 9682.59 | 0.97 |
September | 0.00 | 0.00 | 0.692479E+10 | 0.350780E+10 | 15076.76 | 17-SEP-08:61 | 9417.13 | 0.91 |
October | 0.00 | 0.00 | 0.322326E+10 | 0.149604E+10 | 15005.18 | 01-OCT-15:01 | 9473.31 | 0.62 |
November | 0.00 | 0.00 | 0.100151E+10 | 0.482538E+09 | 14511.39 | 04-NOV-15:01 | 9120.76 | 0.28 |
December | 0.00 | 0.00 | 0.276478E+09 | 0.134963E+09 | 13606.55 | 13-DEC-16:01 | 9453.34 | 0.08 |
Annual Sum or Average | 0.00 | 0.00 | 0.545855E+11 | 0.297031E+11 | 0.58 | |||
Minimum of Months | 0.00 | 0.00 | 0.119518E+09 | 88569479.38 | 13305.47 | 9104.12 | 0.03 | |
Maximum of Months | 0.00 | 0.00 | 0.106498E+11 | 0.616489E+10 | 15430.62 | 13305.47 | 0.97 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 12196151.49 | 6518849.74 | 10237.59 | 31-JAN-16:01 | 8917.34 | 0.00 |
February | 0.00 | 0.00 | 0.191958E+09 | 0.112106E+09 | 13215.63 | 27-FEB-16:01 | 13215.63 | 0.05 |
March | 0.00 | 0.00 | 0.873036E+09 | 0.404899E+09 | 13740.30 | 28-MAR-15:01 | 10318.94 | 0.21 |
April | 0.00 | 0.00 | 0.258082E+10 | 0.122437E+10 | 14415.27 | 02-APR-15:01 | 9782.47 | 0.53 |
May | 0.00 | 0.00 | 0.511893E+10 | 0.265511E+10 | 15209.63 | 30-MAY-08:51 | 12219.67 | 0.67 |
June | 0.00 | 0.00 | 0.799767E+10 | 0.463837E+10 | 16561.82 | 29-JUN-08:51 | 10845.54 | 0.80 |
July | 0.00 | 0.00 | 0.931461E+10 | 0.557964E+10 | 16430.48 | 23-JUL-08:51 | 11353.36 | 0.80 |
August | 0.00 | 0.00 | 0.943107E+10 | 0.551833E+10 | 16790.47 | 20-AUG-07:52 | 9674.06 | 0.84 |
September | 0.00 | 0.00 | 0.516246E+10 | 0.256825E+10 | 16168.89 | 06-SEP-08:31 | 11004.62 | 0.69 |
October | 0.00 | 0.00 | 0.153988E+10 | 0.634929E+09 | 15087.58 | 18-OCT-21:52 | 8981.17 | 0.36 |
November | 0.00 | 0.00 | 0.228896E+09 | 89106571.73 | 14487.68 | 05-NOV-15:01 | 9578.57 | 0.10 |
December | 0.00 | 0.00 | 27363073.84 | 10231113.74 | 13667.21 | 13-DEC-16:01 | 8873.60 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.424789E+11 | 0.234419E+11 | 0.42 | |||
Minimum of Months | 0.00 | 0.00 | 12196151.49 | 6518849.74 | 10237.59 | 8873.60 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.943107E+10 | 0.557964E+10 | 16790.47 | 13215.63 | 0.84 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 23383430.84 | 20377442.74 | 3858.53 | 28-JAN-16:01 | 3858.53 | 0.01 |
February | 0.00 | 0.00 | 0.140560E+09 | 0.116437E+09 | 4053.53 | 19-FEB-16:02 | 2640.71 | 0.06 |
March | 0.00 | 0.00 | 0.573911E+09 | 0.371808E+09 | 3987.58 | 28-MAR-15:01 | 3021.82 | 0.29 |
April | 0.00 | 0.00 | 0.108330E+10 | 0.598896E+09 | 4210.40 | 03-APR-15:01 | 2843.51 | 0.66 |
May | 0.00 | 0.00 | 0.171103E+10 | 0.886489E+09 | 4313.61 | 27-MAY-08:62 | 2505.97 | 0.86 |
June | 0.00 | 0.00 | 0.234056E+10 | 0.132294E+10 | 4488.93 | 29-JUN-08:61 | 2616.57 | 0.94 |
July | 0.00 | 0.00 | 0.269922E+10 | 0.157852E+10 | 4704.90 | 30-JUL-08:62 | 2421.62 | 0.94 |
August | 0.00 | 0.00 | 0.283615E+10 | 0.166073E+10 | 4521.94 | 29-AUG-08:61 | 2588.38 | 0.95 |
September | 0.00 | 0.00 | 0.178849E+10 | 0.908350E+09 | 4571.01 | 17-SEP-08:61 | 2544.41 | 0.87 |
October | 0.00 | 0.00 | 0.837502E+09 | 0.415739E+09 | 4426.20 | 18-OCT-08:62 | 2362.12 | 0.54 |
November | 0.00 | 0.00 | 0.261898E+09 | 0.145736E+09 | 4321.41 | 04-NOV-15:01 | 2593.17 | 0.21 |
December | 0.00 | 0.00 | 63486829.12 | 39011053.38 | 4045.91 | 13-DEC-16:01 | 2651.54 | 0.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.143595E+11 | 0.806503E+10 | 0.54 | |||
Minimum of Months | 0.00 | 0.00 | 23383430.84 | 20377442.74 | 3858.53 | 2362.12 | 0.01 | |
Maximum of Months | 0.00 | 0.00 | 0.283615E+10 | 0.166073E+10 | 4704.90 | 3858.53 | 0.95 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 2052678.79 | 1161517.71 | 3421.62 | 20-JAN-16:01 | 2458.12 | 0.00 |
February | 0.00 | 0.00 | 25060049.77 | 17301760.47 | 3961.47 | 19-FEB-16:02 | 2534.16 | 0.02 |
March | 0.00 | 0.00 | 0.243185E+09 | 0.131970E+09 | 4009.39 | 28-MAR-15:01 | 2933.80 | 0.18 |
April | 0.00 | 0.00 | 0.702761E+09 | 0.351593E+09 | 4174.55 | 30-APR-21:52 | 2700.28 | 0.49 |
May | 0.00 | 0.00 | 0.138988E+10 | 0.735528E+09 | 4334.59 | 07-MAY-17:42 | 3350.52 | 0.65 |
June | 0.00 | 0.00 | 0.216724E+10 | 0.130244E+10 | 4767.09 | 26-JUN-08:21 | 2664.15 | 0.79 |
July | 0.00 | 0.00 | 0.249282E+10 | 0.153662E+10 | 4749.42 | 23-JUL-08:51 | 2610.79 | 0.79 |
August | 0.00 | 0.00 | 0.255939E+10 | 0.153018E+10 | 5063.60 | 20-AUG-07:52 | 2536.87 | 0.83 |
September | 0.00 | 0.00 | 0.137412E+10 | 0.689078E+09 | 4566.73 | 17-SEP-08:52 | 2412.23 | 0.67 |
October | 0.00 | 0.00 | 0.375103E+09 | 0.158154E+09 | 4547.43 | 18-OCT-21:52 | 2467.00 | 0.30 |
November | 0.00 | 0.00 | 46333603.18 | 22885405.53 | 4280.52 | 04-NOV-15:01 | 2497.99 | 0.06 |
December | 0.00 | 0.00 | 5558584.44 | 3102358.32 | 4026.65 | 13-DEC-16:01 | 2468.40 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.113835E+11 | 0.648002E+10 | 0.40 | |||
Minimum of Months | 0.00 | 0.00 | 2052678.79 | 1161517.71 | 3421.62 | 2412.23 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.255939E+10 | 0.153662E+10 | 5063.60 | 3350.52 | 0.83 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.133307E+10 | 0.105700E+10 | 17529.30 | 26-JAN-16:01 | 17529.30 | 0.11 |
February | 0.00 | 0.00 | 0.206846E+10 | 0.164299E+10 | 18276.45 | 19-FEB-16:02 | 12918.84 | 0.18 |
March | 0.00 | 0.00 | 0.459725E+10 | 0.301428E+10 | 17646.20 | 31-MAR-15:01 | 14219.24 | 0.45 |
April | 0.00 | 0.00 | 0.616321E+10 | 0.331446E+10 | 18781.24 | 03-APR-15:01 | 13353.14 | 0.73 |
May | 0.00 | 0.00 | 0.856651E+10 | 0.427452E+10 | 19202.83 | 27-MAY-08:62 | 12046.05 | 0.87 |
June | 0.00 | 0.00 | 0.112303E+11 | 0.605200E+10 | 21239.31 | 29-JUN-08:61 | 11387.43 | 0.94 |
July | 0.00 | 0.00 | 0.132659E+11 | 0.740035E+10 | 21624.52 | 27-JUL-08:61 | 10934.78 | 0.94 |
August | 0.00 | 0.00 | 0.147318E+11 | 0.877089E+10 | 21035.67 | 29-AUG-08:61 | 11552.69 | 0.95 |
September | 0.00 | 0.00 | 0.107491E+11 | 0.595725E+10 | 20796.20 | 17-SEP-08:61 | 11737.11 | 0.90 |
October | 0.00 | 0.00 | 0.718414E+10 | 0.416609E+10 | 20288.80 | 18-OCT-08:62 | 11078.44 | 0.73 |
November | 0.00 | 0.00 | 0.430063E+10 | 0.274707E+10 | 19156.85 | 04-NOV-15:01 | 12922.32 | 0.49 |
December | 0.00 | 0.00 | 0.237754E+10 | 0.172808E+10 | 18143.71 | 13-DEC-16:01 | 13607.72 | 0.20 |
Annual Sum or Average | 0.00 | 0.00 | 0.865679E+11 | 0.501250E+11 | 0.63 | |||
Minimum of Months | 0.00 | 0.00 | 0.133307E+10 | 0.105700E+10 | 17529.30 | 10934.78 | 0.11 | |
Maximum of Months | 0.00 | 0.00 | 0.147318E+11 | 0.877089E+10 | 21624.52 | 17529.30 | 0.95 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 10316.31 | 290228.22 | 19-JAN-22:53 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 32759.11 | 347349.06 | 27-FEB-16:03 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 74117.29 | 418318.54 | 28-MAR-18:03 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 137997.10 | 435664.49 | 04-APR-15:03 | 0.00 | 0.00 | 01-APR-00:10 |
May | 237710.56 | 592305.69 | 30-MAY-21:53 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 342594.98 | 657055.37 | 26-JUN-21:53 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 414300.18 | 680469.42 | 25-JUL-21:52 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 428515.82 | 664747.15 | 20-AUG-21:52 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 309459.94 | 630407.86 | 09-SEP-21:52 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 137651.86 | 657495.35 | 18-OCT-21:53 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 64676.52 | 424601.10 | 05-NOV-15:03 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 20632.86 | 353382.51 | 13-DEC-16:01 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 185149.87 | 0.00 | ||||
Minimum of Months | 10316.31 | 290228.22 | 0.00 | 0.00 | ||
Maximum of Months | 428515.82 | 680469.42 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 25127.79 | 52865.38 | 31-JAN-08:00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 25181.90 | 52868.26 | 01-FEB-07:54 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 24371.42 | 52032.93 | 01-MAR-07:20 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22826.61 | 52871.13 | 14-APR-17:02 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 21010.56 | 45776.86 | 01-MAY-07:00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 19400.48 | 43501.56 | 02-JUN-18:01 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18406.83 | 39075.12 | 03-JUL-06:40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18356.59 | 38929.31 | 31-AUG-06:30 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19204.50 | 41387.60 | 29-SEP-06:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 20744.43 | 45222.92 | 31-OCT-06:20 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22564.03 | 48905.61 | 30-NOV-08:00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 24164.01 | 51621.47 | 29-DEC-07:30 |
Annual Sum or Average | 0.00 | 21760.53 | ||||
Minimum of Months | 0.00 | 0.00 | 18356.59 | 38929.31 | ||
Maximum of Months | 0.00 | 0.00 | 25181.90 | 52871.13 |
Report: FanReportMonthly
For: FLR_3_DOAS FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.271000E+10 | 0.72 | 1299.30 | 01-JAN-00:03 | 0.91 |
February | 0.244774E+10 | 0.72 | 1299.30 | 01-FEB-00:03 | 0.91 |
March | 0.271000E+10 | 0.72 | 1299.30 | 01-MAR-00:05 | 0.91 |
April | 0.262258E+10 | 0.72 | 1299.30 | 01-APR-00:10 | 0.91 |
May | 0.271000E+10 | 0.71 | 1299.30 | 01-MAY-00:10 | 0.90 |
June | 0.262258E+10 | 0.71 | 1299.30 | 01-JUN-00:10 | 0.90 |
July | 0.271000E+10 | 0.71 | 1299.30 | 01-JUL-00:10 | 0.90 |
August | 0.271000E+10 | 0.71 | 1299.30 | 01-AUG-00:10 | 0.90 |
September | 0.262258E+10 | 0.71 | 1299.30 | 01-SEP-00:10 | 0.90 |
October | 0.271000E+10 | 0.72 | 1299.30 | 01-OCT-00:10 | 0.90 |
November | 0.262258E+10 | 0.72 | 1299.30 | 01-NOV-00:10 | 0.91 |
December | 0.271000E+10 | 0.72 | 1299.30 | 01-DEC-00:03 | 0.91 |
Annual Sum or Average | 0.319080E+11 | 0.72 | |||
Minimum of Months | 0.244774E+10 | 0.71 | 1299.30 | 0.90 | |
Maximum of Months | 0.271000E+10 | 0.72 | 1299.30 | 0.91 |
Report: FanReportMonthly
For: VAV WITH REHEAT FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.292990E+11 | 0.77 | 13560.45 | 19-JAN-21:00 | 0.86 |
February | 0.267134E+11 | 0.78 | 14115.82 | 28-FEB-21:10 | 0.89 |
March | 0.301125E+11 | 0.78 | 15000.71 | 30-MAR-20:10 | 0.91 |
April | 0.295514E+11 | 0.79 | 15427.11 | 17-APR-18:07 | 0.93 |
May | 0.311178E+11 | 0.79 | 18340.85 | 15-MAY-18:07 | 1.03 |
June | 0.308630E+11 | 0.80 | 16126.58 | 12-JUN-19:40 | 0.95 |
July | 0.321185E+11 | 0.81 | 17225.95 | 07-JUL-20:10 | 0.99 |
August | 0.322299E+11 | 0.81 | 17494.35 | 18-AUG-20:10 | 1.00 |
September | 0.300956E+11 | 0.79 | 16136.36 | 07-SEP-20:30 | 0.95 |
October | 0.302333E+11 | 0.78 | 14839.39 | 18-OCT-20:10 | 0.91 |
November | 0.288482E+11 | 0.78 | 13968.07 | 02-NOV-20:00 | 0.88 |
December | 0.294730E+11 | 0.78 | 13760.81 | 13-DEC-21:00 | 0.87 |
Annual Sum or Average | 0.360656E+12 | 0.79 | |||
Minimum of Months | 0.267134E+11 | 0.77 | 13560.45 | 0.86 | |
Maximum of Months | 0.322299E+11 | 0.81 | 18340.85 | 1.03 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205205E+09 | 0.28 | 76.61 | 01-JAN-00:03 | 0.28 |
February | 0.185347E+09 | 0.28 | 76.61 | 01-FEB-00:03 | 0.28 |
March | 0.205205E+09 | 0.28 | 76.61 | 01-MAR-00:05 | 0.28 |
April | 0.198586E+09 | 0.27 | 76.61 | 01-APR-00:10 | 0.28 |
May | 0.205205E+09 | 0.27 | 76.61 | 01-MAY-00:10 | 0.27 |
June | 0.198586E+09 | 0.27 | 76.61 | 01-JUN-00:10 | 0.27 |
July | 0.205205E+09 | 0.27 | 76.61 | 01-JUL-00:10 | 0.27 |
August | 0.205205E+09 | 0.27 | 76.61 | 01-AUG-00:10 | 0.27 |
September | 0.198586E+09 | 0.27 | 76.61 | 01-SEP-00:10 | 0.27 |
October | 0.205205E+09 | 0.27 | 76.61 | 01-OCT-00:10 | 0.27 |
November | 0.198586E+09 | 0.28 | 76.61 | 01-NOV-00:10 | 0.28 |
December | 0.205205E+09 | 0.28 | 76.61 | 01-DEC-00:03 | 0.28 |
Annual Sum or Average | 0.241613E+10 | 0.27 | |||
Minimum of Months | 0.185347E+09 | 0.27 | 76.61 | 0.27 | |
Maximum of Months | 0.205205E+09 | 0.28 | 76.61 | 0.28 |
Report: FanReportMonthly
For: LOBBY_FLR_1 EXHAUST FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | -0.0 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | -0.0 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | -0.0 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:10 | -0.0 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 EXHAUST FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 EXHAUST FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116283E+10 | 0.19 | 612.92 | 01-JAN-07:05 | 0.27 |
February | 0.105030E+10 | 0.19 | 612.92 | 01-FEB-07:02 | 0.28 |
March | 0.116283E+10 | 0.19 | 612.92 | 01-MAR-07:03 | 0.27 |
April | 0.112532E+10 | 0.19 | 612.92 | 01-APR-06:05 | 0.27 |
May | 0.116283E+10 | 0.19 | 612.92 | 01-MAY-06:03 | 0.27 |
June | 0.112532E+10 | 0.19 | 612.92 | 01-JUN-06:03 | 0.27 |
July | 0.116283E+10 | 0.19 | 612.92 | 01-JUL-06:05 | 0.27 |
August | 0.116283E+10 | 0.19 | 612.92 | 01-AUG-06:03 | 0.27 |
September | 0.112532E+10 | 0.19 | 612.92 | 01-SEP-06:03 | 0.27 |
October | 0.116283E+10 | 0.19 | 612.92 | 01-OCT-06:03 | 0.27 |
November | 0.112532E+10 | 0.19 | 612.92 | 01-NOV-06:03 | 0.27 |
December | 0.116283E+10 | 0.19 | 612.92 | 01-DEC-07:03 | 0.28 |
Annual Sum or Average | 0.136914E+11 | 0.19 | |||
Minimum of Months | 0.105030E+10 | 0.19 | 612.92 | 0.27 | |
Maximum of Months | 0.116283E+10 | 0.19 | 612.92 | 0.28 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.170569E+09 | 0.44 | 707.38 | 01-JAN-16:02 | 0.59 |
February | 0.127767E+09 | 0.43 | 707.38 | 01-FEB-09:01 | 0.60 |
March | 0.126741E+09 | 0.46 | 707.38 | 02-MAR-16:01 | 0.59 |
April | 0.189477E+09 | 0.50 | 707.38 | 01-APR-15:01 | 0.59 |
May | 0.266881E+09 | 0.53 | 707.38 | 01-MAY-15:01 | 0.59 |
June | 0.362113E+09 | 0.56 | 707.38 | 01-JUN-08:61 | 0.59 |
July | 0.408873E+09 | 0.56 | 707.38 | 01-JUL-08:61 | 0.59 |
August | 0.429522E+09 | 0.57 | 707.38 | 01-AUG-08:61 | 0.59 |
September | 0.282641E+09 | 0.54 | 707.38 | 01-SEP-08:62 | 0.59 |
October | 0.160586E+09 | 0.49 | 707.38 | 01-OCT-15:01 | 0.59 |
November | 93166393.04 | 0.45 | 707.38 | 01-NOV-15:01 | 0.59 |
December | 0.118396E+09 | 0.43 | 707.38 | 01-DEC-09:01 | 0.60 |
Annual Sum or Average | 0.273673E+10 | 0.50 | |||
Minimum of Months | 93166393.04 | 0.43 | 707.38 | 0.59 | |
Maximum of Months | 0.429522E+09 | 0.57 | 707.38 | 0.60 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.204765E+09 | 0.46 | 699.80 | 01-JAN-16:02 | 0.59 |
February | 0.130026E+09 | 0.42 | 699.80 | 01-FEB-09:01 | 0.60 |
March | 73514286.52 | 0.35 | 699.80 | 03-MAR-09:02 | 0.59 |
April | 0.124154E+09 | 0.37 | 699.80 | 01-APR-08:62 | 0.59 |
May | 0.208917E+09 | 0.39 | 699.80 | 01-MAY-08:52 | 0.59 |
June | 0.331582E+09 | 0.46 | 699.80 | 01-JUN-08:51 | 0.59 |
July | 0.375815E+09 | 0.47 | 699.80 | 01-JUL-08:31 | 0.59 |
August | 0.384310E+09 | 0.49 | 699.80 | 01-AUG-07:51 | 0.59 |
September | 0.211102E+09 | 0.40 | 699.80 | 01-SEP-08:51 | 0.59 |
October | 81846151.51 | 0.35 | 699.80 | 01-OCT-15:01 | 0.59 |
November | 70648519.40 | 0.37 | 699.80 | 01-NOV-15:01 | 0.59 |
December | 0.140188E+09 | 0.41 | 699.80 | 01-DEC-09:01 | 0.60 |
Annual Sum or Average | 0.233687E+10 | 0.41 | |||
Minimum of Months | 70648519.40 | 0.35 | 699.80 | 0.59 | |
Maximum of Months | 0.384310E+09 | 0.49 | 699.80 | 0.60 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 56782997.93 | 0.04 | 764.67 | 29-JAN-13:30 | 0.60 |
February | 0.220189E+09 | 0.12 | 987.25 | 26-FEB-14:25 | 0.60 |
March | 0.678483E+09 | 0.38 | 1010.95 | 11-MAR-14:40 | 0.60 |
April | 0.805098E+09 | 0.47 | 903.42 | 15-APR-13:50 | 0.59 |
May | 0.102259E+10 | 0.55 | 785.60 | 19-MAY-19:10 | 0.59 |
June | 0.128931E+10 | 0.58 | 882.57 | 24-JUN-19:10 | 0.59 |
July | 0.148227E+10 | 0.59 | 976.02 | 08-JUL-17:25 | 0.59 |
August | 0.167958E+10 | 0.59 | 1049.00 | 19-AUG-13:40 | 0.59 |
September | 0.131631E+10 | 0.57 | 1199.84 | 24-SEP-12:40 | 0.59 |
October | 0.995106E+09 | 0.45 | 1282.60 | 10-OCT-13:30 | 0.59 |
November | 0.636501E+09 | 0.36 | 1158.06 | 12-NOV-14:00 | 0.60 |
December | 0.283484E+09 | 0.17 | 1060.84 | 10-DEC-14:25 | 0.60 |
Annual Sum or Average | 0.104657E+11 | 0.41 | |||
Minimum of Months | 56782997.93 | 0.04 | 764.67 | 0.59 | |
Maximum of Months | 0.167958E+10 | 0.59 | 1282.60 | 0.60 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.910545E+09 | 0.41 | 4505.99 | 01-JAN-09:02 | 0.59 |
February | 0.724157E+09 | 0.38 | 4505.99 | 01-FEB-16:01 | 0.60 |
March | 0.748535E+09 | 0.34 | 4505.99 | 01-MAR-09:02 | 0.60 |
April | 0.121816E+10 | 0.34 | 4505.99 | 01-APR-08:62 | 0.59 |
May | 0.179948E+10 | 0.35 | 4505.99 | 01-MAY-08:52 | 0.59 |
June | 0.254377E+10 | 0.43 | 4505.99 | 01-JUN-08:51 | 0.59 |
July | 0.280420E+10 | 0.44 | 4505.99 | 01-JUL-08:31 | 0.59 |
August | 0.277623E+10 | 0.46 | 4505.99 | 01-AUG-07:51 | 0.59 |
September | 0.175202E+10 | 0.36 | 4505.99 | 01-SEP-08:51 | 0.59 |
October | 0.907521E+09 | 0.33 | 4505.99 | 01-OCT-08:53 | 0.59 |
November | 0.594290E+09 | 0.36 | 4505.99 | 01-NOV-15:01 | 0.59 |
December | 0.580925E+09 | 0.40 | 4505.99 | 01-DEC-09:01 | 0.60 |
Annual Sum or Average | 0.173598E+11 | 0.38 | |||
Minimum of Months | 0.580925E+09 | 0.33 | 4505.99 | 0.59 | |
Maximum of Months | 0.280420E+10 | 0.46 | 4505.99 | 0.60 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.156560E+09 | 0.44 | 641.16 | 01-JAN-16:02 | 0.59 |
February | 0.121192E+09 | 0.44 | 641.16 | 01-FEB-09:01 | 0.60 |
March | 0.112910E+09 | 0.48 | 641.16 | 02-MAR-16:01 | 0.59 |
April | 0.177024E+09 | 0.52 | 641.16 | 01-APR-15:01 | 0.59 |
May | 0.264810E+09 | 0.55 | 641.16 | 01-MAY-15:01 | 0.59 |
June | 0.367218E+09 | 0.58 | 641.16 | 01-JUN-08:61 | 0.59 |
July | 0.424010E+09 | 0.57 | 641.16 | 01-JUL-08:61 | 0.59 |
August | 0.431210E+09 | 0.58 | 641.16 | 01-AUG-08:61 | 0.59 |
September | 0.278166E+09 | 0.55 | 641.16 | 01-SEP-08:62 | 0.59 |
October | 0.149641E+09 | 0.51 | 641.16 | 01-OCT-08:62 | 0.59 |
November | 85178016.30 | 0.46 | 641.16 | 01-NOV-15:01 | 0.59 |
December | 0.105978E+09 | 0.43 | 641.16 | 01-DEC-09:01 | 0.60 |
Annual Sum or Average | 0.267390E+10 | 0.51 | |||
Minimum of Months | 85178016.30 | 0.43 | 641.16 | 0.59 | |
Maximum of Months | 0.431210E+09 | 0.58 | 641.16 | 0.60 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.190420E+09 | 0.46 | 635.86 | 01-JAN-16:02 | 0.59 |
February | 0.119802E+09 | 0.41 | 635.86 | 01-FEB-09:01 | 0.60 |
March | 67212755.28 | 0.35 | 635.86 | 02-MAR-16:01 | 0.59 |
April | 0.118990E+09 | 0.39 | 635.86 | 01-APR-15:01 | 0.59 |
May | 0.210713E+09 | 0.41 | 635.86 | 01-MAY-08:52 | 0.59 |
June | 0.336327E+09 | 0.48 | 635.86 | 01-JUN-08:51 | 0.59 |
July | 0.390367E+09 | 0.48 | 635.86 | 01-JUL-08:31 | 0.59 |
August | 0.386764E+09 | 0.50 | 635.86 | 01-AUG-07:51 | 0.59 |
September | 0.207112E+09 | 0.41 | 635.86 | 01-SEP-08:51 | 0.59 |
October | 81720240.38 | 0.36 | 635.86 | 01-OCT-15:01 | 0.59 |
November | 63673714.15 | 0.36 | 635.86 | 01-NOV-08:62 | 0.59 |
December | 0.125578E+09 | 0.41 | 635.86 | 01-DEC-09:01 | 0.60 |
Annual Sum or Average | 0.229868E+10 | 0.42 | |||
Minimum of Months | 63673714.15 | 0.35 | 635.86 | 0.59 | |
Maximum of Months | 0.390367E+09 | 0.50 | 635.86 | 0.60 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 52415729.20 | 0.45 | 185.89 | 01-JAN-16:02 | 0.59 |
February | 38497908.92 | 0.45 | 185.89 | 01-FEB-09:01 | 0.60 |
March | 35123371.11 | 0.46 | 185.89 | 02-MAR-16:01 | 0.59 |
April | 51435901.08 | 0.50 | 185.89 | 01-APR-15:01 | 0.59 |
May | 73267941.71 | 0.54 | 185.89 | 01-MAY-15:01 | 0.59 |
June | 98694065.07 | 0.56 | 185.89 | 01-JUN-08:61 | 0.59 |
July | 0.112364E+09 | 0.56 | 185.89 | 01-JUL-08:61 | 0.59 |
August | 0.117413E+09 | 0.57 | 185.89 | 01-AUG-08:61 | 0.59 |
September | 74634459.85 | 0.54 | 185.89 | 01-SEP-08:62 | 0.59 |
October | 43060683.02 | 0.49 | 185.89 | 01-OCT-15:01 | 0.59 |
November | 26989779.52 | 0.46 | 185.89 | 01-NOV-15:01 | 0.59 |
December | 37469465.15 | 0.44 | 185.89 | 01-DEC-09:01 | 0.59 |
Annual Sum or Average | 0.761366E+09 | 0.50 | |||
Minimum of Months | 26989779.52 | 0.44 | 185.89 | 0.59 | |
Maximum of Months | 0.117413E+09 | 0.57 | 185.89 | 0.60 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 62183560.10 | 0.50 | 183.72 | 01-JAN-16:02 | 0.59 |
February | 39572028.38 | 0.44 | 183.72 | 01-FEB-09:01 | 0.60 |
March | 21505211.18 | 0.36 | 183.72 | 03-MAR-09:02 | 0.59 |
April | 34553883.25 | 0.38 | 183.72 | 01-APR-15:01 | 0.59 |
May | 59363648.05 | 0.40 | 183.72 | 01-MAY-08:52 | 0.59 |
June | 92485034.15 | 0.47 | 183.72 | 01-JUN-08:51 | 0.59 |
July | 0.106165E+09 | 0.47 | 183.72 | 01-JUL-08:31 | 0.59 |
August | 0.106591E+09 | 0.50 | 183.72 | 01-AUG-07:51 | 0.59 |
September | 57141841.67 | 0.41 | 183.72 | 01-SEP-08:51 | 0.59 |
October | 23107390.58 | 0.36 | 183.72 | 01-OCT-15:01 | 0.59 |
November | 22377109.05 | 0.37 | 183.72 | 01-NOV-08:62 | 0.59 |
December | 43796194.53 | 0.44 | 183.72 | 01-DEC-09:01 | 0.59 |
Annual Sum or Average | 0.668843E+09 | 0.42 | |||
Minimum of Months | 21505211.18 | 0.36 | 183.72 | 0.59 | |
Maximum of Months | 0.106591E+09 | 0.50 | 183.72 | 0.60 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.202328E+09 | 0.47 | 840.62 | 01-JAN-16:02 | 0.59 |
February | 0.177964E+09 | 0.46 | 840.62 | 01-FEB-09:01 | 0.59 |
March | 0.226540E+09 | 0.50 | 840.62 | 02-MAR-16:01 | 0.59 |
April | 0.272682E+09 | 0.51 | 840.62 | 01-APR-08:62 | 0.59 |
May | 0.347050E+09 | 0.54 | 840.62 | 01-MAY-15:01 | 0.59 |
June | 0.457389E+09 | 0.56 | 840.62 | 01-JUN-08:61 | 0.59 |
July | 0.531415E+09 | 0.56 | 840.62 | 01-JUL-08:61 | 0.59 |
August | 0.596323E+09 | 0.57 | 840.62 | 01-AUG-08:61 | 0.59 |
September | 0.433864E+09 | 0.54 | 840.62 | 01-SEP-08:62 | 0.59 |
October | 0.320666E+09 | 0.52 | 840.62 | 01-OCT-08:62 | 0.59 |
November | 0.219156E+09 | 0.50 | 840.62 | 01-NOV-15:01 | 0.59 |
December | 0.185262E+09 | 0.48 | 840.62 | 01-DEC-09:01 | 0.60 |
Annual Sum or Average | 0.397064E+10 | 0.52 | |||
Minimum of Months | 0.177964E+09 | 0.46 | 840.62 | 0.59 | |
Maximum of Months | 0.596323E+09 | 0.57 | 840.62 | 0.60 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12485174.39 | 11236656.95 | 271.00 | 31-JAN-16:01 | 243.90 | 243.90 | 6.72 | 8.61 |
February | 32840829.14 | 29556746.23 | 296.66 | 26-FEB-16:03 | 266.99 | 266.99 | 6.72 | 8.98 |
March | 0.126833E+09 | 0.114149E+09 | 514.89 | 30-MAR-18:03 | 463.40 | 463.40 | 6.72 | 11.52 |
April | 0.296860E+09 | 0.267174E+09 | 713.02 | 13-APR-15:01 | 641.72 | 641.72 | 6.72 | 13.29 |
May | 0.601531E+09 | 0.541378E+09 | 1103.68 | 30-MAY-21:53 | 993.31 | 993.31 | 6.72 | 16.03 |
June | 0.108594E+10 | 0.977342E+09 | 1245.11 | 26-JUN-21:52 | 1120.60 | 1120.60 | 6.72 | 16.86 |
July | 0.148633E+10 | 0.133770E+10 | 1337.94 | 18-JUL-19:00 | 1204.14 | 1204.14 | 6.72 | 17.38 |
August | 0.160175E+10 | 0.144157E+10 | 1281.59 | 20-AUG-21:52 | 1153.43 | 1153.43 | 6.72 | 17.07 |
September | 0.915702E+09 | 0.824132E+09 | 1142.76 | 09-SEP-21:52 | 1028.48 | 1028.48 | 6.72 | 16.26 |
October | 0.340690E+09 | 0.306621E+09 | 1227.81 | 18-OCT-21:52 | 1105.03 | 1105.03 | 6.72 | 16.76 |
November | 96064442.44 | 86457998.20 | 490.59 | 05-NOV-15:01 | 441.53 | 441.53 | 6.72 | 11.28 |
December | 25524704.89 | 22972234.40 | 349.66 | 13-DEC-16:01 | 314.70 | 314.70 | 6.72 | 9.68 |
Annual Sum or Average | 0.662254E+10 | 0.596029E+10 | ||||||
Minimum of Months | 12485174.39 | 11236656.95 | 271.00 | 243.90 | 243.90 | 6.72 | 8.61 | |
Maximum of Months | 0.160175E+10 | 0.144157E+10 | 1337.94 | 1204.14 | 1204.14 | 6.72 | 17.38 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.281520E+10 | 0.253368E+10 | 3284.74 | 01-JAN-00:50 | 2956.26 | 2956.26 | 6.73 | 29.06 |
February | 0.422960E+10 | 0.380664E+10 | 3284.74 | 01-FEB-00:03 | 2956.26 | 2956.26 | 6.78 | 29.06 |
March | 0.771218E+10 | 0.694096E+10 | 3284.74 | 01-MAR-00:05 | 2956.26 | 2956.26 | 7.37 | 29.06 |
April | 0.824400E+10 | 0.741960E+10 | 3284.74 | 01-APR-00:10 | 2956.26 | 2956.26 | 6.84 | 29.06 |
May | 0.879488E+10 | 0.791539E+10 | 3284.74 | 01-MAY-00:10 | 2956.26 | 2956.26 | 8.56 | 29.06 |
June | 0.851404E+10 | 0.766263E+10 | 3284.74 | 01-JUN-00:10 | 2956.26 | 2956.26 | 9.51 | 29.06 |
July | 0.879784E+10 | 0.791805E+10 | 3284.74 | 01-JUL-00:10 | 2956.26 | 2956.26 | 10.54 | 29.06 |
August | 0.879784E+10 | 0.791805E+10 | 3284.74 | 01-AUG-00:10 | 2956.26 | 2956.26 | 9.78 | 29.06 |
September | 0.851404E+10 | 0.766263E+10 | 3284.74 | 01-SEP-00:10 | 2956.26 | 2956.26 | 9.39 | 29.06 |
October | 0.842260E+10 | 0.758034E+10 | 3284.74 | 01-OCT-00:10 | 2956.26 | 2956.26 | 8.12 | 29.06 |
November | 0.679240E+10 | 0.611316E+10 | 3284.74 | 01-NOV-00:10 | 2956.26 | 2956.26 | 6.73 | 29.06 |
December | 0.448726E+10 | 0.403854E+10 | 3284.74 | 01-DEC-09:04 | 2956.26 | 2956.26 | 6.78 | 29.06 |
Annual Sum or Average | 0.861219E+11 | 0.775097E+11 | ||||||
Minimum of Months | 0.281520E+10 | 0.253368E+10 | 3284.74 | 2956.26 | 2956.26 | 6.73 | 29.06 | |
Maximum of Months | 0.879784E+10 | 0.791805E+10 | 3284.74 | 2956.26 | 2956.26 | 10.54 | 29.06 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:03 | 14.37 | 14.37 | 48.81 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:03 | 14.37 | 14.37 | 50.07 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:05 | 14.37 | 14.37 | 50.43 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 53.31 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:10 | 14.37 | 14.37 | 53.80 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:10 | 14.37 | 14.37 | 54.32 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 54.70 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:10 | 14.37 | 14.37 | 54.86 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:10 | 14.37 | 14.37 | 54.73 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:10 | 14.37 | 14.37 | 53.69 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:10 | 14.37 | 14.37 | 53.87 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:03 | 14.37 | 14.37 | 50.64 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 48.81 | 0.37 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 54.86 | 0.37 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 10316.31 | 290228.22 | 19-JAN-22:53 | 9.08 | 6.70 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 32759.11 | 347349.06 | 27-FEB-16:03 | 9.55 | 6.70 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 74117.29 | 418318.54 | 28-MAR-18:03 | 10.14 | 6.70 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 137997.10 | 435664.49 | 04-APR-15:03 | 10.28 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 237710.56 | 592305.69 | 30-MAY-21:53 | 11.57 | 6.70 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 342594.98 | 657055.37 | 26-JUN-21:53 | 12.10 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 414300.18 | 680469.42 | 25-JUL-21:52 | 12.29 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 428515.82 | 664747.15 | 20-AUG-21:52 | 12.16 | 6.70 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 309459.94 | 630407.86 | 09-SEP-21:52 | 11.88 | 6.70 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 137651.86 | 657495.35 | 18-OCT-21:53 | 12.10 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 64676.52 | 424601.10 | 05-NOV-15:03 | 10.19 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 20632.86 | 353382.51 | 13-DEC-16:01 | 9.60 | 6.70 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 185149.87 | 0.00 | ||||||
Minimum of Months | 10316.31 | 290228.22 | 9.08 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 428515.82 | 680469.42 | 12.29 | 6.70 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 48.81 | 60.05 | 25127.79 | 52865.38 | 31-JAN-08:00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 50.07 | 60.05 | 25181.90 | 52868.26 | 01-FEB-07:54 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 50.43 | 60.05 | 24371.42 | 52032.93 | 01-MAR-07:20 |
April | 0.00 | 0.00 | 01-APR-00:10 | 53.31 | 60.05 | 22826.61 | 52871.13 | 14-APR-17:02 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 53.80 | 60.05 | 21010.56 | 45776.86 | 01-MAY-07:00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 54.32 | 60.05 | 19400.48 | 43501.56 | 02-JUN-18:01 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 54.70 | 60.05 | 18406.83 | 39075.12 | 03-JUL-06:40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 54.86 | 60.05 | 18356.59 | 38929.31 | 31-AUG-06:30 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 54.73 | 60.05 | 19204.50 | 41387.60 | 29-SEP-06:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 53.69 | 60.05 | 20744.43 | 45222.92 | 31-OCT-06:20 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 53.87 | 60.05 | 22564.03 | 48905.61 | 30-NOV-08:00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 50.64 | 60.05 | 24164.01 | 51621.47 | 29-DEC-07:30 |
Annual Sum or Average | 0.00 | 21760.53 | ||||||
Minimum of Months | 0.00 | 0.00 | 48.81 | 60.05 | 18356.59 | 38929.31 | ||
Maximum of Months | 0.00 | 0.00 | 54.86 | 60.05 | 25181.90 | 52871.13 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.697973E+09 | 0.340466E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.197469E+10 | 0.303968E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.711478E+10 | 0.271000E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.142755E+11 | 0.262258E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.300411E+11 | 0.271000E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.443953E+11 | 0.262258E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.555144E+11 | 0.271000E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.567570E+11 | 0.271000E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.397304E+11 | 0.262258E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.161233E+11 | 0.271000E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.572898E+10 | 0.265909E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.118613E+10 | 0.283290E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.273540E+12 | 0.333540E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.697973E+09 | 0.262258E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.567570E+11 | 0.340466E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.197359E+11 | 0.178289E+12 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.585295E+11 | 0.129022E+12 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.140026E+12 | 0.102012E+12 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.265050E+12 | 0.651060E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.491269E+12 | 0.431825E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.688613E+12 | 0.344053E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.876468E+12 | 0.347058E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.903697E+12 | 0.346987E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.633046E+12 | 0.336146E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.277225E+12 | 0.649406E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.121794E+12 | 0.114453E+12 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.360329E+11 | 0.179039E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.451149E+13 | 0.101347E+13 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.197359E+11 | 0.336146E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.903697E+12 | 0.179039E+12 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.271000E+10 | 0.697973E+09 | 0.694661E+09 | 0.439446E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244774E+10 | 0.197469E+10 | 0.591939E+09 | 0.274738E+11 | 723762.95 | 0.00 | 0.00 | 0.00 |
March | 0.271000E+10 | 0.711478E+10 | 0.00 | 0.123966E+11 | 0.413912E+09 | 0.00 | 0.00 | 0.00 |
April | 0.262258E+10 | 0.142755E+11 | 0.00 | 0.576631E+10 | 0.882620E+09 | 0.00 | 0.00 | 0.00 |
May | 0.271000E+10 | 0.300411E+11 | 0.00 | 0.101383E+10 | 0.479662E+10 | 0.00 | 0.00 | 0.00 |
June | 0.262258E+10 | 0.443953E+11 | 0.00 | 0.298817E+09 | 0.184457E+11 | 0.00 | 0.00 | 0.00 |
July | 0.271000E+10 | 0.555144E+11 | 0.00 | 0.00 | 0.300951E+11 | 0.00 | 0.00 | 0.00 |
August | 0.271000E+10 | 0.567570E+11 | 0.00 | 135840.46 | 0.389170E+11 | 0.00 | 0.00 | 0.00 |
September | 0.262258E+10 | 0.397304E+11 | 0.00 | 0.193335E+09 | 0.140161E+11 | 0.00 | 0.00 | 0.00 |
October | 0.271000E+10 | 0.161233E+11 | 0.00 | 0.757055E+10 | 0.235065E+10 | 0.00 | 0.00 | 0.00 |
November | 0.262258E+10 | 0.572898E+10 | 36515003.30 | 0.175183E+11 | 0.108270E+09 | 0.00 | 0.00 | 0.00 |
December | 0.271000E+10 | 0.118613E+10 | 0.122900E+09 | 0.315113E+11 | 1277258.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319080E+11 | 0.273540E+12 | 0.144601E+10 | 0.147687E+12 | 0.110028E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244774E+10 | 0.697973E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.271000E+10 | 0.567570E+11 | 0.694661E+09 | 0.439446E+11 | 0.389170E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.292990E+11 | 0.197359E+11 | 0.148990E+12 | 0.258237E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.267134E+11 | 0.585295E+11 | 0.102309E+12 | 0.143168E+12 | 0.195680E+09 | 0.00 | 0.00 | 0.00 |
March | 0.301125E+11 | 0.140026E+12 | 0.718991E+11 | 0.473035E+10 | 0.319512E+10 | 0.00 | 0.00 | 0.00 |
April | 0.295514E+11 | 0.265050E+12 | 0.355546E+11 | 0.663593E+10 | 0.134994E+11 | 0.00 | 0.00 | 0.00 |
May | 0.311178E+11 | 0.491269E+12 | 0.120646E+11 | 0.00 | 0.546444E+11 | 0.00 | 0.00 | 0.00 |
June | 0.308630E+11 | 0.688613E+12 | 0.354234E+10 | 0.00 | 0.172757E+12 | 0.00 | 0.00 | 0.00 |
July | 0.321185E+11 | 0.876468E+12 | 0.258729E+10 | 0.00 | 0.264733E+12 | 0.00 | 0.00 | 0.00 |
August | 0.322299E+11 | 0.903697E+12 | 0.246875E+10 | 0.00 | 0.339653E+12 | 0.00 | 0.00 | 0.00 |
September | 0.300956E+11 | 0.633046E+12 | 0.351897E+10 | 0.00 | 0.116695E+12 | 0.00 | 0.00 | 0.00 |
October | 0.302333E+11 | 0.277225E+12 | 0.347073E+11 | 0.147308E+10 | 0.249318E+11 | 0.00 | 0.00 | 0.00 |
November | 0.288482E+11 | 0.121794E+12 | 0.856047E+11 | 0.270411E+11 | 0.224453E+10 | 0.00 | 0.00 | 0.00 |
December | 0.294730E+11 | 0.360329E+11 | 0.149566E+12 | 0.882314E+11 | 73737375.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.360656E+12 | 0.451149E+13 | 0.652813E+12 | 0.529517E+12 | 0.992623E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.267134E+11 | 0.197359E+11 | 0.246875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.322299E+11 | 0.903697E+12 | 0.149566E+12 | 0.258237E+12 | 0.339653E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.271000E+10 | 0.00 | 0.697973E+09 | 0.00 | 0.00 | 0.694661E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244774E+10 | 0.00 | 0.197469E+10 | 0.00 | 0.00 | 0.591939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.271000E+10 | 0.00 | 0.711478E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.262258E+10 | 0.00 | 0.142755E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.271000E+10 | 0.00 | 0.300411E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.262258E+10 | 0.00 | 0.443953E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.271000E+10 | 0.00 | 0.555144E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.271000E+10 | 0.00 | 0.567570E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.262258E+10 | 0.00 | 0.397304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.271000E+10 | 0.00 | 0.161233E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.262258E+10 | 0.00 | 0.572898E+10 | 0.00 | 0.00 | 36515003.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.271000E+10 | 0.00 | 0.118613E+10 | 0.00 | 0.00 | 0.122900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319080E+11 | 0.00 | 0.273540E+12 | 0.00 | 0.00 | 0.144601E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244774E+10 | 0.00 | 0.697973E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.271000E+10 | 0.00 | 0.567570E+11 | 0.00 | 0.00 | 0.694661E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.292990E+11 | 0.00 | 0.197359E+11 | 0.00 | 0.00 | 0.148990E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.267134E+11 | 0.00 | 0.585295E+11 | 0.00 | 0.00 | 0.102309E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.301125E+11 | 0.00 | 0.140026E+12 | 0.00 | 0.00 | 0.718991E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.295514E+11 | 0.00 | 0.265050E+12 | 0.00 | 0.00 | 0.355546E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.311178E+11 | 0.00 | 0.491269E+12 | 0.00 | 0.00 | 0.120646E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.308630E+11 | 0.00 | 0.688613E+12 | 0.00 | 0.00 | 0.354234E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.321185E+11 | 0.00 | 0.876468E+12 | 0.00 | 0.00 | 0.258729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.322299E+11 | 0.00 | 0.903697E+12 | 0.00 | 0.00 | 0.246875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.300956E+11 | 0.00 | 0.633046E+12 | 0.00 | 0.00 | 0.351897E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.302333E+11 | 0.00 | 0.277225E+12 | 0.00 | 0.00 | 0.347073E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.288482E+11 | 0.00 | 0.121794E+12 | 0.00 | 0.00 | 0.856047E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.294730E+11 | 0.00 | 0.360329E+11 | 0.00 | 0.00 | 0.149566E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.360656E+12 | 0.00 | 0.451149E+13 | 0.00 | 0.00 | 0.652813E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.267134E+11 | 0.00 | 0.197359E+11 | 0.00 | 0.00 | 0.246875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.322299E+11 | 0.00 | 0.903697E+12 | 0.00 | 0.00 | 0.149566E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.609856E+11 | 0.00 | 0.00 | 0.00 | 7094784.90 | 0.00 | 0.00 | 0.00 | 1.00 |
February | 0.485416E+11 | 0.00 | 0.00 | 0.00 | 5676925.96 | 0.00 | 0.00 | 0.00 | 1.00 |
March | 0.445434E+11 | 0.00 | 0.00 | 0.00 | 0.392693E+09 | 0.00 | 0.00 | 0.00 | 1.00 |
April | 0.278707E+11 | 0.00 | 0.00 | 0.00 | 0.195144E+10 | 0.00 | 0.00 | 0.00 | 1.01 |
May | 0.109453E+11 | 0.00 | 0.00 | 0.00 | 0.824097E+10 | 0.00 | 0.00 | 0.00 | 1.00 |
June | 0.462561E+10 | 0.00 | 0.00 | 0.00 | 0.230107E+11 | 0.00 | 0.00 | 0.00 | 0.98 |
July | 73464899.25 | 0.00 | 0.00 | 0.00 | 0.358254E+11 | 0.00 | 0.00 | 0.00 | 0.97 |
August | 11655340.56 | 0.00 | 0.00 | 0.00 | 0.376207E+11 | 0.00 | 0.00 | 0.00 | 0.97 |
September | 0.586503E+10 | 0.117126E+10 | 0.00 | 621779.19 | 0.183344E+11 | 0.00 | 0.778375E+09 | 0.00 | 1.00 |
October | 0.298168E+11 | 0.581470E+09 | 0.00 | 1934678.72 | 0.522667E+10 | 0.00 | 0.430906E+10 | 0.00 | 1.01 |
November | 0.416330E+11 | 46319475.77 | 0.00 | 2343057.75 | 0.767430E+09 | 0.00 | 0.610704E+10 | 0.00 | 1.01 |
December | 0.619588E+11 | 0.00 | 0.00 | 23111.67 | 0.128778E+09 | 0.00 | 0.266841E+09 | 0.00 | 1.01 |
Annual Sum or Average | 0.336871E+12 | 0.179905E+10 | 0.00 | 4922627.33 | 0.131512E+12 | 0.00 | 0.114613E+11 | 0.00 | 1.00 |
Minimum of Months | 11655340.56 | 0.00 | 0.00 | 0.00 | 5676925.96 | 0.00 | 0.00 | 0.00 | 0.97 |
Maximum of Months | 0.619588E+11 | 0.117126E+10 | 0.00 | 2343057.75 | 0.376207E+11 | 0.00 | 0.610704E+10 | 0.00 | 1.01 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.503767E+10 | 0.00 | 0.00 | 11084.84 | 873036.55 | 0.243453E+10 | 32262429.58 | 0.00 | 2.23 |
February | 0.464408E+10 | 49887.86 | 0.00 | 59670.51 | 648676.50 | 0.129831E+10 | 30759377.99 | 0.00 | 2.24 |
March | 0.537060E+10 | 5156766.58 | 0.00 | 12032.38 | 43165397.60 | 0.102823E+09 | 7776734.17 | 0.00 | 2.25 |
April | 0.340985E+10 | 8253572.18 | 0.00 | 4438.25 | 0.231878E+09 | 19319028.46 | 413120.01 | 0.00 | 2.25 |
May | 0.134508E+10 | 13421700.55 | 0.00 | 2901.95 | 0.100066E+10 | 0.00 | 1769553.65 | 0.00 | 2.24 |
June | 0.569178E+09 | 0.598284E+09 | 0.00 | 127.44 | 0.223326E+10 | 0.00 | 18605.70 | 0.00 | 2.19 |
July | 9040096.78 | 0.139204E+10 | 0.00 | 0.00 | 0.301721E+10 | 0.00 | 0.00 | 0.00 | 2.17 |
August | 1434227.88 | 0.221667E+10 | 0.00 | 0.00 | 0.242741E+10 | 0.00 | 0.00 | 0.00 | 2.17 |
September | 0.814522E+09 | 0.522616E+09 | 0.00 | 52212.41 | 0.188172E+10 | 0.00 | 3001338.71 | 0.00 | 2.23 |
October | 0.408316E+10 | 0.115104E+09 | 0.00 | 283995.54 | 0.604572E+09 | 1897132.39 | 0.114219E+09 | 0.00 | 2.26 |
November | 0.553380E+10 | 1951555.46 | 0.00 | 336941.81 | 98183000.22 | 0.209519E+09 | 0.131200E+09 | 0.00 | 2.25 |
December | 0.660345E+10 | 1576535.76 | 0.00 | 55328.71 | 14270031.58 | 0.956468E+09 | 97094663.78 | 0.00 | 2.24 |
Annual Sum or Average | 0.374219E+11 | 0.487513E+10 | 0.00 | 818733.84 | 0.115538E+11 | 0.502287E+10 | 0.418515E+09 | 0.00 | 2.23 |
Minimum of Months | 1434227.88 | 0.00 | 0.00 | 0.00 | 648676.50 | 0.00 | 0.00 | 0.00 | 2.17 |
Maximum of Months | 0.660345E+10 | 0.221667E+10 | 0.00 | 336941.81 | 0.301721E+10 | 0.243453E+10 | 0.131200E+09 | 0.00 | 2.26 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.570800E+10 | 0.00 | 0.00 | 0.00 | 664041.79 | 0.00 | 0.00 | 0.00 | 1.47 |
February | 0.454329E+10 | 0.00 | 0.00 | 0.00 | 531336.20 | 0.00 | 0.00 | 0.00 | 1.47 |
March | 0.416844E+10 | 0.00 | 0.00 | 1926.46 | 36754402.15 | 0.00 | 626257.75 | 0.00 | 1.48 |
April | 0.257468E+10 | 0.00 | 0.00 | 12661.80 | 0.182647E+09 | 0.00 | 33889154.08 | 0.00 | 1.48 |
May | 0.101332E+10 | 14458352.81 | 0.00 | 24433.47 | 0.756861E+09 | 0.00 | 11087868.65 | 0.00 | 1.47 |
June | 0.406426E+09 | 0.288019E+09 | 0.00 | 21493.29 | 0.186568E+10 | 0.00 | 26490667.60 | 0.00 | 1.44 |
July | 6876003.14 | 0.606739E+09 | 0.00 | 0.00 | 0.274843E+10 | 0.00 | 0.00 | 0.00 | 1.42 |
August | 1090890.47 | 0.893389E+09 | 0.00 | 0.00 | 0.263243E+10 | 0.00 | 0.00 | 0.00 | 1.42 |
September | 0.566380E+09 | 0.195377E+09 | 0.00 | 38877.23 | 0.163037E+10 | 0.00 | 55434019.44 | 0.00 | 1.47 |
October | 0.315606E+10 | 7811623.94 | 0.00 | 16345.14 | 0.535805E+09 | 0.00 | 38140413.83 | 0.00 | 1.48 |
November | 0.446848E+10 | 0.00 | 0.00 | 0.00 | 76163511.95 | 0.00 | 0.00 | 0.00 | 1.48 |
December | 0.582405E+10 | 0.00 | 0.00 | 0.00 | 12053084.10 | 0.00 | 0.00 | 0.00 | 1.47 |
Annual Sum or Average | 0.324371E+11 | 0.200579E+10 | 0.00 | 115737.39 | 0.104784E+11 | 0.00 | 0.165668E+09 | 0.00 | 1.46 |
Minimum of Months | 1090890.47 | 0.00 | 0.00 | 0.00 | 531336.20 | 0.00 | 0.00 | 0.00 | 1.42 |
Maximum of Months | 0.582405E+10 | 0.893389E+09 | 0.00 | 38877.23 | 0.274843E+10 | 0.00 | 55434019.44 | 0.00 | 1.48 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.336912E+10 | 0.00 | 0.00 | 0.00 | 564410.82 | 0.148246E+10 | 0.00 | 0.00 | 0.59 |
February | 0.304125E+10 | 0.00 | 0.00 | 0.00 | 451616.01 | 0.820380E+09 | 0.00 | 0.00 | 0.59 |
March | 0.354355E+10 | 0.00 | 0.00 | 0.00 | 31239874.46 | 0.00 | 0.00 | 0.00 | 0.59 |
April | 0.221720E+10 | 0.00 | 0.00 | 0.00 | 0.155243E+09 | 0.00 | 0.00 | 0.00 | 0.59 |
May | 0.870727E+09 | 0.00 | 0.00 | 0.00 | 0.655593E+09 | 0.00 | 0.00 | 0.00 | 0.59 |
June | 0.367981E+09 | 0.00 | 0.00 | 0.00 | 0.183057E+10 | 0.00 | 0.00 | 0.00 | 0.58 |
July | 5844346.86 | 41391649.72 | 0.00 | 0.00 | 0.280862E+10 | 0.00 | 0.00 | 0.00 | 0.57 |
August | 927216.31 | 49437815.25 | 0.00 | 0.00 | 0.294340E+10 | 0.00 | 0.00 | 0.00 | 0.57 |
September | 0.528552E+09 | 0.00 | 0.00 | 0.00 | 0.155173E+10 | 0.00 | 0.00 | 0.00 | 0.59 |
October | 0.271496E+10 | 0.00 | 0.00 | 0.00 | 0.462054E+09 | 0.00 | 0.00 | 0.00 | 0.59 |
November | 0.379804E+10 | 0.00 | 0.00 | 0.00 | 64736151.66 | 0.00 | 0.00 | 0.00 | 0.59 |
December | 0.474914E+10 | 0.00 | 0.00 | 0.00 | 10244673.08 | 0.201087E+09 | 0.00 | 0.00 | 0.59 |
Annual Sum or Average | 0.252073E+11 | 90829464.96 | 0.00 | 0.00 | 0.105144E+11 | 0.250393E+10 | 0.00 | 0.00 | 0.59 |
Minimum of Months | 927216.31 | 0.00 | 0.00 | 0.00 | 451616.01 | 0.00 | 0.00 | 0.00 | 0.57 |
Maximum of Months | 0.474914E+10 | 49437815.25 | 0.00 | 0.00 | 0.294340E+10 | 0.148246E+10 | 0.00 | 0.00 | 0.59 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.118136E+10 | 0.00 | 0.00 | 0.00 | 336492.37 | 0.171108E+10 | 0.00 | 0.00 | 0.61 |
February | 0.135858E+10 | 0.00 | 0.00 | 0.00 | 269245.97 | 0.943660E+09 | 0.00 | 0.00 | 0.61 |
March | 0.211047E+10 | 0.00 | 0.00 | 0.00 | 18624695.13 | 2136339.79 | 0.00 | 0.00 | 0.61 |
April | 0.132186E+10 | 0.00 | 0.00 | 0.00 | 92553182.66 | 0.00 | 0.00 | 0.00 | 0.61 |
May | 0.519113E+09 | 0.00 | 0.00 | 0.00 | 0.390854E+09 | 0.00 | 0.00 | 0.00 | 0.61 |
June | 0.219384E+09 | 0.00 | 0.00 | 0.00 | 0.109135E+10 | 0.00 | 0.00 | 0.00 | 0.60 |
July | 3484302.69 | 0.00 | 0.00 | 0.00 | 0.169913E+10 | 0.00 | 0.00 | 0.00 | 0.59 |
August | 552790.99 | 0.00 | 0.00 | 0.00 | 0.178428E+10 | 0.00 | 0.00 | 0.00 | 0.59 |
September | 0.315114E+09 | 0.00 | 0.00 | 0.00 | 0.925116E+09 | 0.00 | 0.00 | 0.00 | 0.61 |
October | 0.161862E+10 | 0.00 | 0.00 | 0.00 | 0.275469E+09 | 0.00 | 0.00 | 0.00 | 0.61 |
November | 0.218258E+10 | 0.00 | 0.00 | 0.00 | 38594620.16 | 81753916.79 | 0.00 | 0.00 | 0.61 |
December | 0.236413E+10 | 0.00 | 0.00 | 0.00 | 6107704.21 | 0.587110E+09 | 0.00 | 0.00 | 0.61 |
Annual Sum or Average | 0.131952E+11 | 0.00 | 0.00 | 0.00 | 0.632269E+10 | 0.332574E+10 | 0.00 | 0.00 | 0.61 |
Minimum of Months | 552790.99 | 0.00 | 0.00 | 0.00 | 269245.97 | 0.00 | 0.00 | 0.00 | 0.59 |
Maximum of Months | 0.236413E+10 | 0.00 | 0.00 | 0.00 | 0.178428E+10 | 0.171108E+10 | 0.00 | 0.00 | 0.61 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.262546E+10 | 9446780.37 | 0.00 | 79638815.73 | 0.00 | 0.00 | 0.829527E+11 | 0.00 | 21.93 |
February | 0.187105E+10 | 7352368.10 | 0.00 | 71377642.38 | 206518.25 | 0.00 | 0.664874E+11 | 0.00 | 22.08 |
March | 0.100349E+10 | 0.521669E+09 | 0.00 | 78429221.46 | 19625362.75 | 0.00 | 0.616214E+11 | 0.00 | 22.26 |
April | 0.877110E+09 | 0.264486E+10 | 0.00 | 74088306.73 | 72442670.40 | 0.00 | 0.382094E+11 | 0.00 | 22.30 |
May | 0.119046E+09 | 0.112648E+11 | 0.00 | 43314725.93 | 0.363771E+09 | 0.00 | 0.150187E+11 | 0.00 | 22.21 |
June | 46049409.96 | 0.319138E+11 | 0.00 | 19296185.17 | 0.663850E+09 | 0.00 | 0.631945E+10 | 0.00 | 21.76 |
July | 0.00 | 0.498190E+11 | 0.00 | 664829.34 | 0.921017E+09 | 0.00 | 97154453.06 | 0.00 | 21.43 |
August | 0.00 | 0.526336E+11 | 0.00 | 151885.17 | 0.922631E+09 | 0.00 | 15367322.80 | 0.00 | 21.43 |
September | 73482081.63 | 0.269237E+11 | 0.00 | 27029949.59 | 0.554792E+09 | 0.00 | 0.934075E+10 | 0.00 | 22.05 |
October | 0.519907E+09 | 0.811450E+10 | 0.00 | 64775790.14 | 0.160825E+09 | 0.00 | 0.476404E+11 | 0.00 | 22.26 |
November | 0.134221E+10 | 0.111014E+10 | 0.00 | 73764005.05 | 23790259.41 | 0.00 | 0.662108E+11 | 0.00 | 22.22 |
December | 0.161195E+10 | 0.169295E+09 | 0.00 | 78951703.57 | 2174146.45 | 0.00 | 0.860884E+11 | 0.00 | 22.04 |
Annual Sum or Average | 0.100897E+11 | 0.185132E+12 | 0.00 | 0.611483E+09 | 0.370513E+10 | 0.00 | 0.480002E+12 | 0.00 | 22.00 |
Minimum of Months | 0.00 | 7352368.10 | 0.00 | 151885.17 | 0.00 | 0.00 | 15367322.80 | 0.00 | 21.43 |
Maximum of Months | 0.262546E+10 | 0.526336E+11 | 0.00 | 79638815.73 | 0.922631E+09 | 0.00 | 0.860884E+11 | 0.00 | 22.30 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.315140E+11 | 0.00 | 0.00 | 341980.13 | 3864596.23 | 19781617.72 | 0.168535E+10 | 0.00 | 3.52 |
February | 0.231705E+11 | 352081.37 | 0.00 | 1507283.34 | 2740193.73 | 0.00 | 0.326911E+10 | 0.00 | 3.53 |
March | 0.165433E+11 | 45674681.72 | 0.00 | 3805130.20 | 0.168229E+09 | 0.00 | 0.771612E+10 | 0.00 | 3.55 |
April | 0.895167E+10 | 0.222354E+09 | 0.00 | 4663382.33 | 0.840614E+09 | 0.00 | 0.622510E+10 | 0.00 | 3.55 |
May | 0.222038E+10 | 0.147359E+10 | 0.00 | 4976841.62 | 0.301534E+10 | 0.00 | 0.373663E+10 | 0.00 | 3.53 |
June | 0.884474E+09 | 0.708436E+10 | 0.00 | 2189121.49 | 0.545322E+10 | 0.00 | 0.163295E+10 | 0.00 | 3.46 |
July | 5342125.71 | 0.126153E+11 | 0.00 | 206625.13 | 0.693633E+10 | 0.00 | 34468272.44 | 0.00 | 3.42 |
August | 159243.76 | 0.156695E+11 | 0.00 | 92449.32 | 0.492089E+10 | 0.00 | 6097080.82 | 0.00 | 3.42 |
September | 0.110462E+10 | 0.653588E+10 | 0.00 | 3580112.00 | 0.410370E+10 | 0.00 | 0.251087E+10 | 0.00 | 3.52 |
October | 0.103166E+11 | 0.171516E+10 | 0.00 | 6266955.94 | 0.145112E+10 | 0.00 | 0.826689E+10 | 0.00 | 3.56 |
November | 0.187192E+11 | 88345169.14 | 0.00 | 3795841.72 | 0.354912E+09 | 0.00 | 0.728272E+10 | 0.00 | 3.55 |
December | 0.298091E+11 | 7036424.85 | 0.00 | 1288937.55 | 63110219.56 | 0.00 | 0.408447E+10 | 0.00 | 3.53 |
Annual Sum or Average | 0.143239E+12 | 0.454576E+11 | 0.00 | 32714660.77 | 0.273141E+11 | 19781617.72 | 0.464508E+11 | 0.00 | 3.51 |
Minimum of Months | 159243.76 | 0.00 | 0.00 | 92449.32 | 2740193.73 | 0.00 | 6097080.82 | 0.00 | 3.42 |
Maximum of Months | 0.315140E+11 | 0.156695E+11 | 0.00 | 6266955.94 | 0.693633E+10 | 19781617.72 | 0.826689E+10 | 0.00 | 3.56 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.115144E+12 | 0.00 | 0.00 | 0.00 | 13395270.18 | 0.00 | 0.00 | 0.00 | 1.76 |
February | 0.910279E+11 | 0.00 | 0.00 | 157219.40 | 10718289.29 | 0.00 | 0.620769E+09 | 0.00 | 1.77 |
March | 0.819873E+11 | 12526662.12 | 0.00 | 869139.08 | 0.728895E+09 | 0.00 | 0.211173E+10 | 0.00 | 1.77 |
April | 0.488219E+11 | 15658621.03 | 0.00 | 2274049.61 | 0.366875E+10 | 0.00 | 0.379692E+10 | 0.00 | 1.78 |
May | 0.173184E+11 | 0.193813E+10 | 0.00 | 3344241.32 | 0.136212E+11 | 0.00 | 0.334336E+10 | 0.00 | 1.77 |
June | 0.575070E+10 | 0.146386E+11 | 0.00 | 2616417.69 | 0.288066E+11 | 0.00 | 0.298005E+10 | 0.00 | 1.73 |
July | 46106570.17 | 0.240181E+11 | 0.00 | 136186.60 | 0.436758E+11 | 0.00 | 92462248.02 | 0.00 | 1.71 |
August | 4178792.79 | 0.297007E+11 | 0.00 | 147854.74 | 0.414555E+11 | 0.00 | 17679155.03 | 0.00 | 1.71 |
September | 0.730773E+10 | 0.104919E+11 | 0.00 | 3909462.36 | 0.263420E+11 | 0.00 | 0.523258E+10 | 0.00 | 1.76 |
October | 0.587671E+11 | 0.270939E+10 | 0.00 | 2336124.81 | 0.825663E+10 | 0.00 | 0.566532E+10 | 0.00 | 1.78 |
November | 0.883397E+11 | 13556187.04 | 0.00 | 398002.34 | 0.152284E+10 | 0.00 | 0.179959E+10 | 0.00 | 1.78 |
December | 0.117121E+12 | 0.00 | 0.00 | 64153.02 | 0.243139E+09 | 0.00 | 0.363957E+09 | 0.00 | 1.77 |
Annual Sum or Average | 0.631635E+12 | 0.835387E+11 | 0.00 | 16252850.97 | 0.168346E+12 | 0.00 | 0.260244E+11 | 0.00 | 1.76 |
Minimum of Months | 4178792.79 | 0.00 | 0.00 | 0.00 | 10718289.29 | 0.00 | 0.00 | 0.00 | 1.71 |
Maximum of Months | 0.117121E+12 | 0.297007E+11 | 0.00 | 3909462.36 | 0.436758E+11 | 0.00 | 0.566532E+10 | 0.00 | 1.78 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 68995906.65 | 0.00 | 0.00 | 796804.95 | 0.00 | 0.127341E+10 | 0.127945E+09 | 0.00 | 0.35 |
February | 77323227.98 | 1288.34 | 0.00 | 2396534.47 | 0.00 | 0.880878E+09 | 0.310782E+09 | 0.00 | 0.35 |
March | 67101019.70 | 11313321.97 | 2914.24 | 5838526.97 | 265232.34 | 0.350217E+09 | 0.715671E+09 | 3612.13 | 0.35 |
April | 24312927.82 | 47555091.28 | 84147.72 | 8127451.87 | 3461532.37 | 0.100102E+09 | 0.663299E+09 | 12485.58 | 0.35 |
May | 1903944.84 | 0.269952E+09 | 129883.66 | 5381591.81 | 1335275.32 | 944230.19 | 0.278945E+09 | 18499.59 | 0.36 |
June | 507663.16 | 0.793563E+09 | 363114.82 | 2626169.52 | 0.00 | 236883.68 | 0.123936E+09 | 34561.47 | 0.36 |
July | 0.00 | 0.112754E+10 | 779814.47 | 191446.09 | 3192357.23 | 71200.23 | 3393813.12 | 31295.13 | 0.35 |
August | 0.00 | 0.122576E+10 | 836078.63 | 70429.56 | 0.00 | 10933.69 | 322544.68 | 35514.04 | 0.36 |
September | 1391432.53 | 0.599393E+09 | 645995.90 | 2707818.18 | 5708787.38 | 1259618.05 | 0.160931E+09 | 51973.28 | 0.36 |
October | 34864481.82 | 0.158292E+09 | 180582.78 | 6155906.69 | 4512528.31 | 0.228486E+09 | 0.627779E+09 | 18850.72 | 0.36 |
November | 44146708.01 | 9542015.30 | 10590.51 | 3649838.85 | 1383188.81 | 0.563121E+09 | 0.586377E+09 | 9623.23 | 0.35 |
December | 78572768.65 | 437333.23 | 0.00 | 1403090.45 | 268888.55 | 0.111894E+10 | 0.232700E+09 | 1313.38 | 0.35 |
Annual Sum or Average | 0.399120E+09 | 0.424336E+10 | 3033122.73 | 39345609.41 | 20127790.32 | 0.451768E+10 | 0.383208E+10 | 217728.55 | 0.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 70429.56 | 0.00 | 10933.69 | 322544.68 | 0.00 | 0.35 |
Maximum of Months | 78572768.65 | 0.122576E+10 | 836078.63 | 8127451.87 | 5708787.38 | 0.127341E+10 | 0.715671E+09 | 51973.28 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 64118423.47 | 0.00 | 0.00 | 139556.24 | 0.00 | 0.136781E+10 | 38912023.89 | 0.00 | 0.35 |
February | 0.106132E+09 | 1288.19 | 0.00 | 844083.10 | 0.00 | 0.975926E+09 | 0.188330E+09 | 0.00 | 0.35 |
March | 0.215601E+09 | 9351888.91 | 16369.13 | 2746234.97 | 2203519.32 | 0.465430E+09 | 0.454917E+09 | 11945.96 | 0.35 |
April | 0.153352E+09 | 37112812.44 | 137800.80 | 5898453.28 | 13844538.11 | 0.105339E+09 | 0.531158E+09 | 12116.95 | 0.35 |
May | 93978294.81 | 0.228661E+09 | 289105.24 | 3336186.90 | 42411679.88 | 626310.27 | 0.189200E+09 | 41780.26 | 0.36 |
June | 26910883.82 | 0.671007E+09 | 387672.93 | 2237247.86 | 0.122454E+09 | 102791.63 | 98041344.10 | 19101.43 | 0.36 |
July | 3529536.38 | 0.962333E+09 | 473787.36 | 66235.04 | 0.168598E+09 | 13224.12 | 47035.48 | 9478.12 | 0.36 |
August | 403860.61 | 0.110099E+10 | 591712.83 | 0.00 | 0.124893E+09 | 0.00 | 0.00 | 18078.59 | 0.36 |
September | 57182972.84 | 0.476540E+09 | 732620.37 | 1825740.57 | 0.128407E+09 | 1028836.87 | 0.106233E+09 | 49939.58 | 0.36 |
October | 0.153536E+09 | 0.120241E+09 | 507845.90 | 2665212.52 | 42205706.92 | 0.309433E+09 | 0.431546E+09 | 30560.61 | 0.36 |
November | 0.149394E+09 | 5469930.99 | 40221.21 | 1391103.42 | 5426596.08 | 0.776951E+09 | 0.269419E+09 | 7387.14 | 0.35 |
December | 0.102871E+09 | 413165.00 | 0.00 | 359626.95 | 292974.04 | 0.125286E+10 | 75366637.82 | 1313.22 | 0.35 |
Annual Sum or Average | 0.112701E+10 | 0.361212E+10 | 3177135.78 | 21509680.85 | 0.650737E+09 | 0.525551E+10 | 0.238317E+10 | 201701.87 | 0.35 |
Minimum of Months | 403860.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 0.215601E+09 | 0.110099E+10 | 732620.37 | 5898453.28 | 0.168598E+09 | 0.136781E+10 | 0.531158E+09 | 49939.58 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.993729E+09 | 0.00 | 0.00 | 202021.46 | 3201396.13 | 0.00 | 0.125503E+09 | 0.00 | 0.02 |
February | 0.731326E+09 | 0.00 | 0.00 | 875221.75 | 0.00 | 0.00 | 0.286141E+09 | 0.00 | 0.02 |
March | 0.283729E+09 | 20330152.22 | 0.00 | 1946131.64 | 0.00 | 0.00 | 0.838144E+09 | 0.00 | 0.02 |
April | 0.133399E+09 | 0.107227E+09 | 0.00 | 1767941.35 | 3303250.10 | 0.00 | 0.377296E+09 | 0.00 | 0.02 |
May | 3249539.59 | 0.343561E+09 | 0.00 | 386036.85 | 0.00 | 0.00 | 0.129882E+09 | 0.00 | 0.02 |
June | 0.00 | 0.584003E+09 | 0.00 | 171299.20 | 0.00 | 0.00 | 53330179.59 | 0.00 | 0.02 |
July | 0.00 | 0.878278E+09 | 0.00 | 0.00 | 8045774.01 | 0.00 | 0.00 | 0.00 | 0.02 |
August | 0.00 | 0.961951E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
September | 25419099.82 | 0.654223E+09 | 0.00 | 380233.04 | 13041243.26 | 0.00 | 23779144.02 | 0.00 | 0.02 |
October | 0.182796E+09 | 0.241548E+09 | 0.00 | 2183082.74 | 14497824.73 | 0.00 | 0.520959E+09 | 0.00 | 0.02 |
November | 0.324581E+09 | 46226672.75 | 0.00 | 2189070.84 | 8331447.57 | 0.00 | 0.767638E+09 | 0.00 | 0.02 |
December | 0.700104E+09 | 0.00 | 0.00 | 1245093.36 | 0.00 | 0.00 | 0.667689E+09 | 0.00 | 0.02 |
Annual Sum or Average | 0.337833E+10 | 0.383735E+10 | 0.00 | 11346132.24 | 50420935.80 | 0.00 | 0.379036E+10 | 0.00 | 0.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
Maximum of Months | 0.993729E+09 | 0.961951E+09 | 0.00 | 2189070.84 | 14497824.73 | 0.00 | 0.838144E+09 | 0.00 | 0.02 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.130186E+10 | 0.00 | 0.00 | 12259731.32 | 0.00 | 0.127866E+11 | 0.585215E+10 | 0.00 | 0.40 |
February | 0.172698E+10 | 4409.90 | 0.00 | 28012250.23 | 0.00 | 0.713872E+10 | 0.834979E+10 | 13063.57 | 0.40 |
March | 0.292450E+10 | 0.122497E+09 | 508075.81 | 55680779.69 | 34064567.61 | 0.516582E+09 | 0.119489E+11 | 56908.60 | 0.40 |
April | 0.208719E+10 | 0.484056E+09 | 800044.99 | 89689847.26 | 0.208347E+09 | 0.109987E+09 | 0.850698E+10 | 35988.05 | 0.40 |
May | 0.128497E+10 | 0.294955E+10 | 6276078.26 | 45834316.86 | 0.725375E+09 | 4453965.43 | 0.255963E+10 | 222315.60 | 0.40 |
June | 0.378695E+09 | 0.909084E+10 | 1747105.25 | 24491950.54 | 0.167573E+10 | 338255.64 | 0.132312E+10 | 27352.93 | 0.40 |
July | 47876043.59 | 0.130381E+11 | 1601624.64 | 1354477.64 | 0.230723E+10 | 0.00 | 361346.39 | 32865.24 | 0.40 |
August | 5478126.92 | 0.148521E+11 | 11759385.13 | 0.00 | 0.177264E+10 | 0.00 | 0.00 | 107301.62 | 0.40 |
September | 0.780489E+09 | 0.621451E+10 | 8090942.42 | 28122407.08 | 0.199362E+10 | 3479178.91 | 0.144327E+10 | 131173.49 | 0.41 |
October | 0.208263E+10 | 0.159943E+10 | 3683922.42 | 54256673.80 | 0.607613E+09 | 0.115539E+09 | 0.991729E+10 | 70366.30 | 0.40 |
November | 0.202644E+10 | 74511863.60 | 296486.08 | 44939203.70 | 73608520.46 | 0.189005E+10 | 0.122773E+11 | 33761.53 | 0.40 |
December | 0.144029E+10 | 5622148.46 | 0.00 | 21556721.50 | 3974017.08 | 0.713938E+10 | 0.108156E+11 | 0.00 | 0.40 |
Annual Sum or Average | 0.160874E+11 | 0.484312E+11 | 34763664.99 | 0.406198E+09 | 0.940220E+10 | 0.297052E+11 | 0.729944E+11 | 731096.92 | 0.40 |
Minimum of Months | 5478126.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.40 |
Maximum of Months | 0.292450E+10 | 0.148521E+11 | 11759385.13 | 89689847.26 | 0.230723E+10 | 0.127866E+11 | 0.122773E+11 | 222315.60 | 0.41 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 67960240.19 | 0.00 | 0.00 | 948508.90 | 0.00 | 0.126334E+10 | 0.138902E+09 | 0.00 | 0.35 |
February | 71580975.23 | 1288.34 | 0.00 | 2919148.24 | 0.00 | 0.876905E+09 | 0.319976E+09 | 0.00 | 0.35 |
March | 51840468.92 | 11354822.43 | 12941.19 | 5537881.31 | 211526.59 | 0.360704E+09 | 0.720744E+09 | 5790.47 | 0.35 |
April | 16181179.00 | 48371052.55 | 45909.25 | 8314134.41 | 2689354.59 | 92042734.97 | 0.679303E+09 | 6940.56 | 0.35 |
May | 9452.33 | 0.270062E+09 | 32547.63 | 5872020.33 | 1335275.32 | 603051.16 | 0.280690E+09 | 5328.39 | 0.36 |
June | 0.00 | 0.793961E+09 | 0.00 | 2922340.78 | 0.00 | 0.00 | 0.124385E+09 | 0.00 | 0.36 |
July | 0.00 | 0.112831E+10 | 46198.40 | 189445.01 | 3192357.23 | 71200.23 | 3395814.19 | 667.92 | 0.35 |
August | 0.00 | 0.122664E+10 | 0.00 | 87168.40 | 0.00 | 0.00 | 316739.54 | 0.00 | 0.36 |
September | 1391432.53 | 0.600444E+09 | 208805.79 | 2978378.92 | 5137240.52 | 746443.33 | 0.161174E+09 | 9832.19 | 0.36 |
October | 22188776.57 | 0.159605E+09 | 143007.94 | 5981983.79 | 3246384.61 | 0.239210E+09 | 0.629905E+09 | 10059.81 | 0.36 |
November | 43248831.66 | 9828337.58 | 10898.72 | 3709311.18 | 1096866.53 | 0.544655E+09 | 0.605682E+09 | 9315.01 | 0.35 |
December | 77940274.84 | 437333.23 | 0.00 | 1391041.99 | 268888.55 | 0.108833E+10 | 0.263956E+09 | 1313.38 | 0.35 |
Annual Sum or Average | 0.352342E+09 | 0.424901E+10 | 500308.94 | 40851363.26 | 17177893.93 | 0.446661E+10 | 0.392843E+10 | 49247.73 | 0.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 87168.40 | 0.00 | 0.00 | 316739.54 | 0.00 | 0.35 |
Maximum of Months | 77940274.84 | 0.122664E+10 | 208805.79 | 8314134.41 | 5137240.52 | 0.126334E+10 | 0.720744E+09 | 10059.81 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 70852946.88 | 0.00 | 0.00 | 128788.78 | 0.00 | 0.136507E+10 | 34928187.64 | 0.00 | 0.35 |
February | 0.110579E+09 | 1288.19 | 0.00 | 1114392.90 | 0.00 | 0.958404E+09 | 0.201134E+09 | 0.00 | 0.35 |
March | 0.214372E+09 | 9339264.50 | 26234.04 | 2722554.11 | 2203519.32 | 0.455318E+09 | 0.466281E+09 | 14705.45 | 0.35 |
April | 0.150882E+09 | 37982580.95 | 127202.68 | 6206374.17 | 12991402.86 | 0.102075E+09 | 0.536585E+09 | 6081.80 | 0.35 |
May | 91797637.83 | 0.230448E+09 | 137106.26 | 3581195.86 | 40810652.79 | 370998.90 | 0.191391E+09 | 8033.59 | 0.36 |
June | 26146835.45 | 0.673513E+09 | 90615.31 | 2436518.45 | 0.120259E+09 | 62117.78 | 98646795.73 | 4638.20 | 0.36 |
July | 3529536.38 | 0.966212E+09 | 52558.37 | 66008.01 | 0.165148E+09 | 743.65 | 59742.99 | 921.51 | 0.36 |
August | 403860.61 | 0.110243E+10 | 218028.71 | 0.00 | 0.123843E+09 | 0.00 | 0.00 | 2621.40 | 0.36 |
September | 56732622.45 | 0.478514E+09 | 430588.53 | 1943369.96 | 0.126763E+09 | 632544.88 | 0.106962E+09 | 20678.48 | 0.36 |
October | 0.152654E+09 | 0.124993E+09 | 376494.27 | 2852391.74 | 37592546.82 | 0.334199E+09 | 0.407475E+09 | 23118.24 | 0.36 |
November | 0.149394E+09 | 5477132.91 | 35623.31 | 1235197.24 | 5426596.08 | 0.734240E+09 | 0.312286E+09 | 4783.12 | 0.35 |
December | 0.106181E+09 | 414478.22 | 0.00 | 236812.73 | 292974.04 | 0.125623E+10 | 68809451.96 | 0.00 | 0.35 |
Annual Sum or Average | 0.113353E+10 | 0.362932E+10 | 1494451.50 | 22523603.95 | 0.635332E+09 | 0.520659E+10 | 0.242456E+10 | 85581.79 | 0.35 |
Minimum of Months | 403860.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 0.214372E+09 | 0.110243E+10 | 430588.53 | 6206374.17 | 0.165148E+09 | 0.136507E+10 | 0.536585E+09 | 23118.24 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.332283E+11 | 0.00 | 0.00 | 0.00 | 4190533.64 | 0.279282E+10 | 0.00 | 0.00 | 0.60 |
February | 0.274957E+11 | 0.00 | 0.00 | 0.00 | 3353075.47 | 0.117546E+10 | 0.00 | 0.00 | 0.60 |
March | 0.263095E+11 | 0.00 | 0.00 | 0.00 | 0.231944E+09 | 0.00 | 0.00 | 0.00 | 0.60 |
April | 0.164618E+11 | 0.00 | 0.00 | 0.00 | 0.115262E+10 | 0.00 | 0.00 | 0.00 | 0.60 |
May | 0.646481E+10 | 0.00 | 0.00 | 0.00 | 0.486753E+10 | 0.00 | 0.00 | 0.00 | 0.60 |
June | 0.273212E+10 | 0.00 | 0.00 | 0.00 | 0.135913E+11 | 0.00 | 0.00 | 0.00 | 0.59 |
July | 43392031.70 | 0.00 | 0.00 | 0.00 | 0.211602E+11 | 0.00 | 0.00 | 0.00 | 0.58 |
August | 6884225.15 | 0.00 | 0.00 | 0.00 | 0.222207E+11 | 0.00 | 0.00 | 0.00 | 0.58 |
September | 0.392430E+10 | 0.00 | 0.00 | 0.00 | 0.115210E+11 | 0.00 | 0.00 | 0.00 | 0.60 |
October | 0.201576E+11 | 0.00 | 0.00 | 0.00 | 0.343058E+10 | 0.00 | 0.00 | 0.00 | 0.60 |
November | 0.281990E+11 | 0.00 | 0.00 | 0.00 | 0.480641E+09 | 0.00 | 0.00 | 0.00 | 0.60 |
December | 0.367536E+11 | 0.00 | 0.00 | 0.00 | 76062764.51 | 0.00 | 0.00 | 0.00 | 0.60 |
Annual Sum or Average | 0.201777E+12 | 0.00 | 0.00 | 0.00 | 0.787401E+11 | 0.396827E+10 | 0.00 | 0.00 | 0.60 |
Minimum of Months | 6884225.15 | 0.00 | 0.00 | 0.00 | 3353075.47 | 0.00 | 0.00 | 0.00 | 0.58 |
Maximum of Months | 0.367536E+11 | 0.00 | 0.00 | 0.00 | 0.222207E+11 | 0.279282E+10 | 0.00 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 16572198.13 | 0.00 | 0.00 | 148659.45 | 0.00 | 0.327640E+09 | 23426175.05 | 0.00 | 0.35 |
February | 17512679.05 | 322.08 | 0.00 | 544363.76 | 0.00 | 0.243604E+09 | 56183641.65 | 0.00 | 0.35 |
March | 16792778.53 | 2849993.08 | 670.37 | 1375854.98 | 44645.49 | 0.134962E+09 | 0.131576E+09 | 961.23 | 0.35 |
April | 5443293.59 | 12054056.04 | 19222.07 | 1972056.56 | 701928.98 | 41127936.42 | 0.150417E+09 | 3107.15 | 0.35 |
May | 405717.91 | 67712997.20 | 27102.28 | 1305104.21 | 115032.64 | 2695854.46 | 67386941.84 | 3691.99 | 0.36 |
June | 0.00 | 0.198391E+09 | 90718.18 | 639467.42 | 0.00 | 59466.84 | 31127861.57 | 8700.90 | 0.36 |
July | 0.00 | 0.281853E+09 | 163212.64 | 41883.14 | 862740.68 | 9786.53 | 862445.19 | 7950.34 | 0.35 |
August | 0.00 | 0.306455E+09 | 194192.24 | 16235.62 | 0.00 | 2733.42 | 82007.94 | 9685.41 | 0.36 |
September | 347858.13 | 0.149874E+09 | 154344.68 | 603734.08 | 1408356.70 | 3102178.62 | 37518817.51 | 13257.27 | 0.36 |
October | 8164006.67 | 39867172.80 | 68055.58 | 1455418.09 | 811596.15 | 91599043.71 | 0.123103E+09 | 4252.09 | 0.36 |
November | 10844746.96 | 2457084.40 | 2629.73 | 809198.58 | 274216.63 | 0.183536E+09 | 0.104134E+09 | 2423.71 | 0.35 |
December | 18050136.84 | 109333.31 | 0.00 | 293492.05 | 67222.14 | 0.302145E+09 | 37416860.15 | 328.34 | 0.35 |
Annual Sum or Average | 94133415.82 | 0.106162E+10 | 720147.76 | 9205467.94 | 4285739.41 | 0.133048E+10 | 0.763235E+09 | 54358.43 | 0.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 16235.62 | 0.00 | 2733.42 | 82007.94 | 0.00 | 0.35 |
Maximum of Months | 18050136.84 | 0.306455E+09 | 194192.24 | 1972056.56 | 1408356.70 | 0.327640E+09 | 0.150417E+09 | 13257.27 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 11210230.14 | 0.00 | 0.00 | 23318.98 | 0.00 | 0.352281E+09 | 4229829.77 | 0.00 | 0.35 |
February | 25306429.06 | 322.05 | 0.00 | 178228.84 | 0.00 | 0.268871E+09 | 23452740.30 | 0.00 | 0.35 |
March | 53890125.57 | 2337972.23 | 3529.43 | 617378.59 | 550879.83 | 0.152990E+09 | 77176187.94 | 3549.34 | 0.35 |
April | 38212906.42 | 9516536.18 | 32507.35 | 1478372.04 | 3224630.34 | 39765215.31 | 0.119481E+09 | 3143.19 | 0.36 |
May | 23092048.57 | 57430495.98 | 73875.13 | 843417.49 | 10335845.49 | 167298.51 | 47682442.18 | 10656.87 | 0.36 |
June | 6554787.03 | 0.167758E+09 | 90769.09 | 560307.92 | 30613463.67 | 30660.71 | 24677311.19 | 4340.93 | 0.36 |
July | 882570.01 | 0.240670E+09 | 74577.70 | 16010.72 | 42107877.18 | 3120.12 | 12306.91 | 1380.26 | 0.36 |
August | 100965.15 | 0.275272E+09 | 123866.67 | 0.00 | 31223303.47 | 0.00 | 0.00 | 4399.86 | 0.36 |
September | 14193580.26 | 0.119652E+09 | 175008.94 | 415202.78 | 31593384.19 | 1957267.66 | 25001666.80 | 12164.72 | 0.36 |
October | 38482184.71 | 30922597.37 | 133257.43 | 582079.31 | 9683479.95 | 0.106325E+09 | 78905720.68 | 6967.29 | 0.36 |
November | 36058109.05 | 1367482.75 | 9570.35 | 282078.00 | 1356649.02 | 0.223710E+09 | 39238439.33 | 2331.74 | 0.35 |
December | 20390001.41 | 103291.25 | 0.00 | 57715.52 | 73243.51 | 0.327615E+09 | 9800673.90 | 328.31 | 0.35 |
Annual Sum or Average | 0.268374E+09 | 0.905030E+09 | 716962.09 | 5054110.19 | 0.160763E+09 | 0.147371E+10 | 0.449658E+09 | 49262.50 | 0.35 |
Minimum of Months | 100965.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 53890125.57 | 0.275272E+09 | 175008.94 | 1478372.04 | 42107877.18 | 0.352281E+09 | 0.119481E+09 | 12164.72 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 70251064.95 | 0.00 | 0.00 | 6151800.38 | 0.00 | 0.161468E+10 | 0.671759E+09 | 0.00 | 0.40 |
February | 85148914.65 | 522.23 | 0.00 | 7353982.43 | 0.00 | 0.105778E+10 | 0.891708E+09 | 1547.00 | 0.40 |
March | 49838775.45 | 18465523.10 | 10184.77 | 11157712.81 | 131051.58 | 0.350256E+09 | 0.141784E+10 | 297.39 | 0.40 |
April | 28304534.91 | 78063105.71 | 56100.10 | 11852538.37 | 3974039.14 | 0.147139E+09 | 0.109092E+10 | 898.70 | 0.40 |
May | 494555.09 | 0.433805E+09 | 4076.32 | 7224372.71 | 2144615.52 | 1379141.12 | 0.452139E+09 | 4931.25 | 0.40 |
June | 0.00 | 0.127501E+10 | 180011.19 | 3159229.34 | 0.00 | 372018.35 | 0.200940E+09 | 5255.06 | 0.40 |
July | 0.00 | 0.181126E+10 | 586475.86 | 265281.85 | 5542668.27 | 114356.29 | 5493083.03 | 9564.15 | 0.40 |
August | 0.00 | 0.196947E+10 | 644807.38 | 104746.78 | 0.00 | 0.00 | 543978.77 | 10886.23 | 0.40 |
September | 2234810.87 | 0.963421E+09 | 334503.11 | 4301120.92 | 9229053.81 | 3645655.08 | 0.256901E+09 | 4447.23 | 0.40 |
October | 18007762.62 | 0.256472E+09 | 113888.47 | 12707514.68 | 5214090.83 | 0.196634E+09 | 0.121380E+10 | 4387.41 | 0.40 |
November | 29888049.53 | 16105286.54 | 0.00 | 11598820.43 | 1474393.53 | 0.461078E+09 | 0.142044E+10 | 0.00 | 0.40 |
December | 57124641.56 | 1136388.02 | 0.00 | 7685247.57 | 0.00 | 0.122895E+10 | 0.100560E+10 | 0.00 | 0.40 |
Annual Sum or Average | 0.341293E+09 | 0.682322E+10 | 1930047.19 | 83562368.29 | 27709912.67 | 0.506203E+10 | 0.862809E+10 | 42214.42 | 0.40 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 104746.78 | 0.00 | 0.00 | 543978.77 | 0.00 | 0.40 |
Maximum of Months | 85148914.65 | 0.196947E+10 | 644807.38 | 12707514.68 | 9229053.81 | 0.161468E+10 | 0.142044E+10 | 10886.23 | 0.40 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.265794E+11 | 0.00 | 0.00 | 17901860.62 | 6235869.49 | 0.00 | 0.270358E+11 | 0.00 | 4.22 |
February | 0.169513E+11 | 470178.71 | 0.00 | 23128790.71 | 4519481.99 | 0.00 | 0.258013E+11 | 0.00 | 4.25 |
March | 0.998114E+10 | 0.232442E+09 | 0.00 | 37403895.95 | 0.114032E+09 | 0.00 | 0.294472E+11 | 0.00 | 4.29 |
April | 0.351110E+10 | 0.144938E+10 | 0.00 | 44319081.88 | 0.277302E+09 | 0.00 | 0.214030E+11 | 0.00 | 4.35 |
May | 0.485946E+09 | 0.683435E+10 | 0.00 | 35589377.79 | 0.639186E+09 | 0.00 | 0.942970E+10 | 0.00 | 4.41 |
June | 0.115356E+09 | 0.209577E+11 | 0.00 | 16057637.96 | 0.755194E+09 | 0.00 | 0.413087E+10 | 0.00 | 4.46 |
July | 0.00 | 0.329089E+11 | 0.00 | 1094819.19 | 0.100835E+10 | 0.00 | 66189289.66 | 0.00 | 4.45 |
August | 0.00 | 0.348779E+11 | 0.00 | 345116.09 | 0.103302E+10 | 0.00 | 10454336.42 | 0.00 | 4.45 |
September | 0.256947E+09 | 0.168551E+11 | 0.00 | 18891560.79 | 0.101324E+10 | 0.00 | 0.577863E+10 | 0.00 | 4.39 |
October | 0.600444E+10 | 0.456962E+10 | 0.00 | 33084262.13 | 0.699075E+09 | 0.00 | 0.242543E+11 | 0.00 | 4.31 |
November | 0.117009E+11 | 0.423980E+09 | 0.00 | 28719471.75 | 0.295038E+09 | 0.00 | 0.303864E+11 | 0.00 | 4.27 |
December | 0.212528E+11 | 5310128.09 | 0.00 | 23136792.90 | 0.107878E+09 | 0.00 | 0.334713E+11 | 0.00 | 4.24 |
Annual Sum or Average | 0.968394E+11 | 0.119115E+12 | 0.00 | 0.279673E+09 | 0.595306E+10 | 0.00 | 0.211215E+12 | 0.00 | 4.34 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 345116.09 | 4519481.99 | 0.00 | 10454336.42 | 0.00 | 4.22 |
Maximum of Months | 0.265794E+11 | 0.348779E+11 | 0.00 | 44319081.88 | 0.103302E+10 | 0.00 | 0.334713E+11 | 0.00 | 4.46 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.229445E+11 | 2088220.77 | 0.00 | 24414267.76 | 4446479.10 | 0.00 | 0.332982E+11 | 0.00 | 4.43 |
February | 0.146432E+11 | 3876148.45 | 0.00 | 31307570.91 | 1352622.80 | 0.00 | 0.303213E+11 | 0.00 | 4.47 |
March | 0.692888E+10 | 0.299655E+09 | 0.00 | 48865105.21 | 65366486.50 | 0.00 | 0.347473E+11 | 0.00 | 4.55 |
April | 0.209680E+10 | 0.167319E+10 | 0.00 | 55860410.62 | 0.154420E+09 | 0.00 | 0.243383E+11 | 0.00 | 4.62 |
May | 0.216051E+09 | 0.754514E+10 | 0.00 | 42142602.46 | 0.397582E+09 | 0.00 | 0.103433E+11 | 0.00 | 4.70 |
June | 65285290.57 | 0.224146E+11 | 0.00 | 18746150.36 | 0.648736E+09 | 0.00 | 0.444958E+10 | 0.00 | 4.74 |
July | 0.00 | 0.352071E+11 | 0.00 | 1181544.79 | 0.755335E+09 | 0.00 | 70893859.28 | 0.00 | 4.72 |
August | 0.00 | 0.372122E+11 | 0.00 | 366421.99 | 0.855706E+09 | 0.00 | 11084089.34 | 0.00 | 4.71 |
September | 0.129932E+09 | 0.183287E+11 | 0.00 | 22799225.03 | 0.660191E+09 | 0.00 | 0.629315E+10 | 0.00 | 4.67 |
October | 0.390580E+10 | 0.509806E+10 | 0.00 | 42912879.17 | 0.521926E+09 | 0.00 | 0.280841E+11 | 0.00 | 4.57 |
November | 0.962885E+10 | 0.613760E+09 | 0.00 | 38318499.63 | 0.145612E+09 | 0.00 | 0.347186E+11 | 0.00 | 4.51 |
December | 0.186398E+11 | 91882989.65 | 0.00 | 31237748.06 | 26728953.34 | 0.00 | 0.388504E+11 | 0.00 | 4.46 |
Annual Sum or Average | 0.791991E+11 | 0.128490E+12 | 0.00 | 0.358152E+09 | 0.423740E+10 | 0.00 | 0.245526E+12 | 0.00 | 4.60 |
Minimum of Months | 0.00 | 2088220.77 | 0.00 | 366421.99 | 1352622.80 | 0.00 | 11084089.34 | 0.00 | 4.43 |
Maximum of Months | 0.229445E+11 | 0.372122E+11 | 0.00 | 55860410.62 | 0.855706E+09 | 0.00 | 0.388504E+11 | 0.00 | 4.74 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 19375979.93 | 8303966.23 | 0.00 | 0.117984E+09 | 0.00 | 0.00 | 0.662303E+11 | 0.00 | 16.93 |
February | 0.187266E+09 | 7163512.57 | 0.00 | 0.106271E+09 | 0.00 | 0.00 | 0.526544E+11 | 0.00 | 17.43 |
March | 0.187926E+09 | 0.527163E+09 | 0.00 | 0.109661E+09 | 0.00 | 0.00 | 0.488894E+11 | 0.00 | 18.16 |
April | 0.314057E+09 | 0.258819E+10 | 0.00 | 97891475.30 | 0.00 | 0.00 | 0.296714E+11 | 0.00 | 18.70 |
May | 2783557.16 | 0.111137E+11 | 0.00 | 54778954.45 | 0.00 | 0.00 | 0.113635E+11 | 0.00 | 19.02 |
June | 0.00 | 0.297829E+11 | 0.00 | 25335368.85 | 0.00 | 0.00 | 0.478732E+10 | 0.00 | 19.05 |
July | 0.00 | 0.462544E+11 | 0.00 | 811605.44 | 0.00 | 0.00 | 67948782.26 | 0.00 | 18.92 |
August | 0.00 | 0.486375E+11 | 0.00 | 272151.43 | 0.00 | 0.00 | 10577916.19 | 0.00 | 18.89 |
September | 3078616.85 | 0.245372E+11 | 0.00 | 34353561.39 | 0.00 | 0.00 | 0.708436E+10 | 0.00 | 18.89 |
October | 6520582.73 | 0.723190E+10 | 0.00 | 91496113.32 | 0.00 | 0.00 | 0.373827E+11 | 0.00 | 18.35 |
November | 0.335470E+09 | 0.105958E+10 | 0.00 | 0.101992E+09 | 0.00 | 0.00 | 0.518994E+11 | 0.00 | 17.85 |
December | 19013849.61 | 0.162526E+09 | 0.00 | 0.113037E+09 | 0.00 | 0.00 | 0.680505E+11 | 0.00 | 17.30 |
Annual Sum or Average | 0.107549E+10 | 0.171911E+12 | 0.00 | 0.853884E+09 | 0.00 | 0.00 | 0.378092E+12 | 0.00 | 18.30 |
Minimum of Months | 0.00 | 7163512.57 | 0.00 | 272151.43 | 0.00 | 0.00 | 10577916.19 | 0.00 | 16.93 |
Maximum of Months | 0.335470E+09 | 0.486375E+11 | 0.00 | 0.117984E+09 | 0.00 | 0.00 | 0.680505E+11 | 0.00 | 19.05 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.134867E+11 | 0.00 | 0.00 | 0.00 | 2118163.31 | 0.472070E+10 | 0.00 | 0.00 | 1.15 |
February | 0.121027E+11 | 0.00 | 0.00 | 0.00 | 1694858.47 | 0.238948E+10 | 0.00 | 0.00 | 1.15 |
March | 0.132985E+11 | 0.00 | 0.00 | 0.00 | 0.117239E+09 | 0.00 | 0.00 | 0.00 | 1.15 |
April | 0.832086E+10 | 0.00 | 0.00 | 0.00 | 0.582607E+09 | 0.00 | 0.00 | 0.00 | 1.16 |
May | 0.326773E+10 | 0.00 | 0.00 | 0.00 | 0.246036E+10 | 0.00 | 0.00 | 0.00 | 1.15 |
June | 0.138099E+10 | 0.284511E+09 | 0.00 | 0.00 | 0.658538E+10 | 0.00 | 0.00 | 0.00 | 1.13 |
July | 21933103.91 | 0.232694E+10 | 0.00 | 0.00 | 0.837511E+10 | 0.00 | 0.00 | 0.00 | 1.11 |
August | 3479727.03 | 0.233927E+10 | 0.00 | 0.00 | 0.889246E+10 | 0.00 | 0.00 | 0.00 | 1.11 |
September | 0.198359E+10 | 0.00 | 0.00 | 0.00 | 0.582345E+10 | 0.00 | 0.00 | 0.00 | 1.14 |
October | 0.101889E+11 | 0.00 | 0.00 | 0.00 | 0.173403E+10 | 0.00 | 0.00 | 0.00 | 1.15 |
November | 0.138976E+11 | 0.00 | 0.00 | 0.00 | 0.242947E+09 | 0.355958E+09 | 0.00 | 0.00 | 1.15 |
December | 0.174881E+11 | 0.00 | 0.00 | 0.00 | 38446978.68 | 0.108947E+10 | 0.00 | 0.00 | 1.15 |
Annual Sum or Average | 0.954412E+11 | 0.495072E+10 | 0.00 | 0.00 | 0.348559E+11 | 0.855561E+10 | 0.00 | 0.00 | 1.14 |
Minimum of Months | 3479727.03 | 0.00 | 0.00 | 0.00 | 1694858.47 | 0.00 | 0.00 | 0.00 | 1.11 |
Maximum of Months | 0.174881E+11 | 0.233927E+10 | 0.00 | 0.00 | 0.889246E+10 | 0.472070E+10 | 0.00 | 0.00 | 1.16 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.178741E+12 | 0.750836E+10 | 0.220046E+12 | 0.810523E+12 | 0.499521E+11 |
February | 0.186113E+12 | 0.554898E+10 | 0.159116E+12 | 0.585549E+12 | 0.111390E+12 |
March | 0.275695E+12 | 0.410578E+10 | 0.114579E+12 | 0.404865E+12 | 0.259542E+12 |
April | 0.311551E+12 | 0.228276E+10 | 0.651930E+11 | 0.232876E+12 | 0.458101E+12 |
May | 0.343027E+12 | -117907397.1 | -0.143769E+10 | -0.272971E+11 | 0.806238E+12 |
June | 0.350081E+12 | -0.303394E+10 | -0.849573E+11 | -0.340240E+12 | 0.112923E+13 |
July | 0.325729E+12 | -0.532530E+10 | -0.148460E+12 | -0.590836E+12 | 0.141129E+13 |
August | 0.300625E+12 | -0.612214E+10 | -0.169711E+12 | -0.687319E+12 | 0.146072E+13 |
September | 0.224913E+12 | -0.205628E+10 | -0.546611E+11 | -0.233347E+12 | 0.101354E+13 |
October | 0.214143E+12 | 0.224343E+10 | 0.666676E+11 | 0.235873E+12 | 0.470542E+12 |
November | 0.148204E+12 | 0.418695E+10 | 0.121377E+12 | 0.455086E+12 | 0.220483E+12 |
December | 0.141542E+12 | 0.593206E+10 | 0.175572E+12 | 0.654688E+12 | 0.830613E+11 |
Annual Sum or Average | 0.300037E+13 | 0.151528E+11 | 0.463324E+12 | 0.150042E+13 | 0.747409E+13 |
Minimum of Months | 0.141542E+12 | -0.612214E+10 | -0.169711E+12 | -0.687319E+12 | 0.499521E+11 |
Maximum of Months | 0.350081E+12 | 0.750836E+10 | 0.220046E+12 | 0.810523E+12 | 0.146072E+13 |