Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21

Tabular Output Report in Format: HTML

Building: HotelLarge

Environment: RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930

Simulation Timestamp: 2024-07-03 12:21:35


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:35

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 10436.55 919.90 919.90
Net Site Energy 10436.55 919.90 919.90
Total Source Energy 20909.00 1842.97 1842.97
Net Source Energy 20909.00 1842.97 1842.97


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 11345.29
Net Conditioned Building Area 11345.29
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 1341.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 316.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 782.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 193.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1658.18 1788.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 813.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 499.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 65.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 120.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 94.78 2699.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9857.19
Refrigeration 61.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 4606.71 5829.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9857.19
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 1341.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 316.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 782.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 193.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 872.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Cooking 762.04 1198.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInFreezer 14.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInRefrigerator 8.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Laundry 0.00 590.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 21.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 789.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 2.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 499.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 65.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 120.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 94.78 2699.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5742.51
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4114.69
Refrigeration General 7.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  LowTempRefrigeration 20.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MedTempRefrigeration 34.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 0.00 1341.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 316.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 782.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 193.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 1658.18 1788.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 813.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 499.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 65.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery Unassigned 120.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 94.78 2699.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9857.19
Refrigeration Unassigned 61.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 86.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 86.00 356.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87
Other 233.99 157.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 406.05 513.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 86.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 86.00 356.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87
Other 233.99 157.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 406.05 513.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 4606.710 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 4606.710 100.00
     
Total On-Site and Utility Electric Sources 4606.710 100.00
Total Electricity End Uses 4606.710 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00 0.00
Air to Air Heat Recovery for Cooling 14.43 0.68
Air to Air Heat Recovery for Heating 2118.81 99.32
High-Temperature Geothermal* 0.00 0.00
Solar Water Thermal 0.00 0.00
Solar Air Thermal 0.00 0.00
Total On-Site Thermal Sources 2133.24 100.00


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 9857.19 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 9857.19 100.00
Total Water End Uses 9857.19 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 18.83
Time Setpoint Not Met During Occupied Cooling 30.00
Time Not Comfortable Based on Simple ASHRAE 55-2004 7073.50


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

ZoneCoolingSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

ZoneHeatingSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

ZoneElectricSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

SpaceGainsMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

PeakSpaceGainsMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

SpaceGainComponentsAtCoolingPeakMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

ComfortReportSimple55Monthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

OccupantComfortDataSummaryMonthly

| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |

ChillerReportMonthly

| COOLSYS1 CHILLER1 |

BoilerReportMonthly

| HEATSYS1 BOILER |

DXReportMonthly

| FLR_3_DOAS COOLING COIL | VAV WITH REHEAT COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |

WindowReportMonthly

| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |

WindowEnergyReportMonthly

| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |

WindowZoneSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

WindowEnergyZoneSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWH LAUNDRY G WATER HEATER | SWH BOOSTER E WATER HEATER | SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |

CoilReportMonthly

| FLR_3_DOAS HEATING COIL | VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | FLR_3_DOAS COOLING COIL | VAV WITH REHEAT COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |

PlantLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1 | SWHSYS1 |

FanReportMonthly

| FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL_FANCOILFAN | ROOM_2_FLR_3 FAN COIL_FANCOILFAN | ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | ROOM_5_FLR_3 FAN COIL_FANCOILFAN | ROOM_6_FLR_3 FAN COIL_FANCOILFAN | ROOM_1_FLR_6 FAN COIL_FANCOILFAN | ROOM_2_FLR_6 FAN COIL_FANCOILFAN | ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN |

PumpReportMonthly

| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |

CondLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1 | SWHSYS1 |

ZoneTemperatureOscillationReportMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

AirLoopSystemEnergyAndWaterUseMonthly

| FLR_3_DOAS | VAV WITH REHEAT |

AirLoopSystemComponentLoadsMonthly

| FLR_3_DOAS | VAV WITH REHEAT |

AirLoopSystemComponentEnergyUseMonthly

| FLR_3_DOAS | VAV WITH REHEAT |

MechanicalVentilationLoadsMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:35

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21
RunPeriod RUNPERIOD 1
Weather File Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930
Latitude [deg] 47.47
Longitude [deg] -122.3
Elevation [m] 122.00
Time Zone -8.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 4559.59 1873.43 406.47 1873.22 406.47
Above Ground Wall Area [m2] 4025.82 1662.30 350.71 1662.10 350.71
Window Opening Area [m2] 1213.79 432.95 85.85 609.15 85.85
Gross Window-Wall Ratio [%] 26.62 23.11 21.12 32.52 21.12
Above Ground Window-Wall Ratio [%] 30.15 26.05 24.48 36.65 24.48


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 4559.59 1873.43 406.47 1873.22 406.47
Above Ground Wall Area [m2] 4025.82 1662.30 350.71 1662.10 350.71
Window Opening Area [m2] 1213.79 432.95 85.85 609.15 85.85
Gross Window-Wall Ratio [%] 26.62 23.11 21.12 32.52 21.12
Above Ground Window-Wall Ratio [%] 30.15 26.05 24.48 36.65 24.48


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 1978.84
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
BASEMENT 1978.83 Yes Yes 4826.41 1.00 0.00 533.77 0.00 0.00 8.8143 18.58 5.3800
RETAIL_1_FLR_1 67.07 Yes Yes 265.76 1.00 68.84 0.00 23.26 23.26 11.3140 6.19 10.7600
RETAIL_2_FLR_1 77.67 Yes Yes 307.76 1.00 26.57 0.00 0.00 0.00 11.3140 6.19 10.7600
MECH_FLR_1 164.24 Yes Yes 650.80 1.00 62.80 0.00 0.00 0.00 4.6285 61.93 5.3800
STORAGE_FLR_1 94.76 Yes Yes 375.47 1.00 36.23 0.00 0.00 0.00 5.7199 46.45 2.6900
LAUNDRY_FLR_1 78.04 Yes Yes 309.22 1.00 85.75 0.00 0.00 0.00 4.6285 9.29 597.5300
CAFE_FLR_1 188.86 Yes Yes 748.35 1.00 152.17 0.00 65.50 65.50 10.0104 1.33 5.3800
LOBBY_FLR_1 1308.19 Yes Yes 5183.56 1.00 434.79 0.00 85.08 85.08 10.7639 3.10 8.0700
ROOM_1_FLR_3 39.02 Yes Yes 118.94 4.00 39.95 0.00 13.18 13.18 8.2882 26.01 6.7500
ROOM_2_FLR_3 39.02 Yes Yes 118.93 4.00 39.95 0.00 13.18 13.18 8.2882 26.01 6.7500
ROOM_3_MULT19_FLR_3 24.52 Yes Yes 74.75 76.00 11.15 0.00 3.68 3.68 8.2882 16.35 10.5200
ROOM_4_MULT19_FLR_3 24.53 Yes Yes 74.77 76.00 11.15 0.00 3.68 3.68 8.2882 16.35 10.5200
ROOM_5_FLR_3 39.02 Yes Yes 118.94 4.00 39.95 0.00 13.18 13.18 8.2882 26.01 6.7500
ROOM_6_FLR_3 39.02 Yes Yes 118.93 4.00 39.95 0.00 13.18 13.18 8.2882 26.01 6.7500
CORRIDOR_FLR_3 389.40 Yes Yes 1186.91 4.00 48.31 0.00 15.94 15.94 7.1042 18.58 0.0000
ROOM_1_FLR_6 39.02 Yes Yes 118.94 1.00 39.95 0.00 13.18 13.18 8.2882 26.01 6.7500
ROOM_2_FLR_6 39.02 Yes Yes 118.93 1.00 39.95 0.00 13.18 13.18 8.2882 26.01 6.7500
ROOM_3_MULT9_FLR_6 24.53 Yes Yes 74.77 9.00 20.44 0.00 6.74 6.74 8.2882 16.35 10.5200
BANQUET_FLR_6 331.66 Yes Yes 1010.89 1.00 97.55 0.00 32.19 32.19 10.0104 1.33 67.8200
DINING_FLR_6 331.66 Yes Yes 1010.89 1.00 97.55 0.00 32.19 32.19 10.0104 1.33 67.8200
KITCHEN_FLR_6 103.30 Yes Yes 314.87 1.00 87.33 0.00 26.37 26.37 11.4097 4.65 2934.4875
CORRIDOR_FLR_6 412.12 Yes Yes 1256.16 1.00 85.47 0.00 28.20 28.20 7.1042 18.58 0.0000
Total 11345.29     35184.81   4025.82 533.77 1213.79 1213.79 8.5566 7.07 41.0709
Conditioned Total 11345.29     35184.81   4025.82 533.77 1213.79 1213.79 8.5566 7.07 41.0709
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 0.00     0.00   0.00 0.00 0.00 0.00      


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
BASEMENT 1978.83 Yes Yes 1.00 BASEMENT GENERAL BASEMENT 8.8143 18.58 5.3800  
RETAIL_1_FLR_1 67.07 Yes Yes 1.00 RETAIL_1_FLR_1 GENERAL RETAIL_1_FLR_1 11.3140 6.19 10.7600  
RETAIL_2_FLR_1 77.67 Yes Yes 1.00 RETAIL_2_FLR_1 GENERAL RETAIL_2_FLR_1 11.3140 6.19 10.7600  
MECH_FLR_1 164.24 Yes Yes 1.00 MECH_FLR_1 GENERAL MECH_FLR_1 4.6285 61.93 5.3800  
STORAGE_FLR_1 94.76 Yes Yes 1.00 STORAGE_FLR_1 GENERAL STORAGE_FLR_1 5.7199 46.45 2.6900  
LAUNDRY_FLR_1 78.04 Yes Yes 1.00 LAUNDRY_FLR_1 GENERAL LAUNDRY_FLR_1 4.6285 9.29 597.5300  
CAFE_FLR_1 188.86 Yes Yes 1.00 CAFE_FLR_1 GENERAL CAFE_FLR_1 10.0104 1.33 5.3800  
LOBBY_FLR_1 1308.19 Yes Yes 1.00 LOBBY_FLR_1 GENERAL LOBBY_FLR_1 10.7639 3.10 8.0700  
ROOM_1_FLR_3 39.02 Yes Yes 4.00 ROOM_1_FLR_3 GENERAL ROOM_1_FLR_3 8.2882 26.01 6.7500  
ROOM_2_FLR_3 39.02 Yes Yes 4.00 ROOM_2_FLR_3 GENERAL ROOM_2_FLR_3 8.2882 26.01 6.7500  
ROOM_3_MULT19_FLR_3 24.52 Yes Yes 76.00 ROOM_3_MULT19_FLR_3 GENERAL ROOM_3_MULT19_FLR_3 8.2882 16.35 10.5200  
ROOM_4_MULT19_FLR_3 24.53 Yes Yes 76.00 ROOM_4_MULT19_FLR_3 GENERAL ROOM_4_MULT19_FLR_3 8.2882 16.35 10.5200  
ROOM_5_FLR_3 39.02 Yes Yes 4.00 ROOM_5_FLR_3 GENERAL ROOM_5_FLR_3 8.2882 26.01 6.7500  
ROOM_6_FLR_3 39.02 Yes Yes 4.00 ROOM_6_FLR_3 GENERAL ROOM_6_FLR_3 8.2882 26.01 6.7500  
CORRIDOR_FLR_3 389.40 Yes Yes 4.00 CORRIDOR_FLR_3 GENERAL CORRIDOR_FLR_3 7.1042 18.58 0.0000  
ROOM_1_FLR_6 39.02 Yes Yes 1.00 ROOM_1_FLR_6 GENERAL ROOM_1_FLR_6 8.2882 26.01 6.7500  
ROOM_2_FLR_6 39.02 Yes Yes 1.00 ROOM_2_FLR_6 GENERAL ROOM_2_FLR_6 8.2882 26.01 6.7500  
ROOM_3_MULT9_FLR_6 24.53 Yes Yes 9.00 ROOM_3_MULT9_FLR_6 GENERAL ROOM_3_MULT9_FLR_6 8.2882 16.35 10.5200  
BANQUET_FLR_6 331.66 Yes Yes 1.00 BANQUET_FLR_6 GENERAL BANQUET_FLR_6 10.0104 1.33 67.8200  
DINING_FLR_6 331.66 Yes Yes 1.00 DINING_FLR_6 GENERAL DINING_FLR_6 10.0104 1.33 67.8200  
KITCHEN_FLR_6 103.30 Yes Yes 1.00 KITCHEN_FLR_6 GENERAL KITCHEN_FLR_6 11.4097 4.65 2934.4875  
CORRIDOR_FLR_6 412.12 Yes Yes 1.00 CORRIDOR_FLR_6 GENERAL CORRIDOR_FLR_6 7.1042 18.58 0.0000  
Total 11345.29             8.5566 3.54 41.0709  
Conditioned Total 11345.29             8.5566 3.54 41.0709  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 0.00             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 11345.29 11345.29 0.00 0.00 4.6520 8.82 37.1989
Total 11345.29 11345.29 0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:35

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 10-AUG-18:10 22-MAR-17:40 - - - - - - - - - - 08-MAY-20:10
Heating 0.00 192332.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 130336.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 53578.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 77573.37 104248.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 28157.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 25257.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 3389.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 9938.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 4751.03 243401.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 2416.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 335399.91 539983.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 192332.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 130336.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 53578.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 47590.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Cooking 29240.64 74976.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInFreezer 457.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInRefrigerator 285.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Laundry 0.00 29272.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 1038.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 26968.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 150.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 25257.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 3389.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 9938.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 4751.03 243401.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 228.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  LowTempRefrigeration 1093.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MedTempRefrigeration 1093.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:35

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 1453.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 1002.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 2479.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 612.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 5251.45 1939.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 2577.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 1580.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 206.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 382.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 300.18 2926.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 196.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 14589.45 6319.55 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 128.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 88.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 218.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 54.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 462.88 170.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 227.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 139.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 18.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 33.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 26.46 257.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 17.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1285.95 557.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 128.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 88.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 218.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 54.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 462.88 170.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 227.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 139.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 18.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 33.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 26.46 257.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 17.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1285.95 557.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:35

AirTerminal:SingleDuct:VAV:Reheat

Design Size Maximum Air Flow Rate [m3/s] Design Size Constant Minimum Air Flow Fraction User-Specified Constant Minimum Air Flow Fraction Design Size Minimum Air Flow Rate [m3/s] Design Size Maximum Flow Fraction during Reheat [] User-Specified Maximum Flow Fraction during Reheat [] Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] Design Size Maximum Reheat Water Flow Rate [m3/s] Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] Design Size Reheat Coil Sizing Inlet Air Temperature [C] Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir]
BASEMENT VAV BOX COMPONENT 2.55 0.591906 0.513000 1.31 1.00 0.500000 0.000644 0.000060 1.31 16.70 0.008000
RETAIL_1_FLR_1 VAV BOX COMPONENT 0.442493 0.115501 0.513000 0.226999 0.513000 0.500000 0.003299 0.000029 0.226999 16.70 0.008000
RETAIL_2_FLR_1 VAV BOX COMPONENT 0.232046 0.255052 0.513000 0.119040 0.680138 0.500000 0.001494 0.000012 0.119040 16.70 0.008000
MECH_FLR_1 VAV BOX COMPONENT 0.174022 0.719179 0.513000 0.089274 1.00 0.500000 0.000530 0.000015 0.089274 16.70 0.008000
STORAGE_FLR_1 VAV BOX COMPONENT 0.103423 0.698170 0.513000 0.053056 1.00 0.500000 0.000546 0.000010 0.053056 16.70 0.008000
LAUNDRY_FLR_1 VAV BOX COMPONENT 3.29 0.018088 0.513000 1.69 0.513000 0.500000 0.021063 0.000091 1.69 16.70 0.008000
CAFE_FLR_1 VAV BOX COMPONENT 1.77 0.081450 0.513000 0.906411 0.513000 0.500000 0.004678 0.000088 0.906411 16.70 0.008000
LOBBY_FLR_1 VAV BOX COMPONENT 5.14 0.193875 0.513000 2.64 0.517000 0.500000 0.001965 0.000229 2.64 16.70 0.008000
CORRIDOR_FLR_3 VAV BOX COMPONENT 1.61 0.738384 0.513000 0.824615 1.00 0.500000 0.000516 0.000104 0.824615 16.70 0.008000
BANQUET_FLR_6 VAV BOX COMPONENT 2.12 0.119360 0.513000 1.09 0.513000 0.500000 0.003192 0.000091 1.09 16.70 0.008000
DINING_FLR_6 VAV BOX COMPONENT 2.22 0.113953 0.513000 1.14 0.513000 0.500000 0.003343 0.000095 1.14 16.70 0.008000
KITCHEN_FLR_6 VAV BOX COMPONENT 2.27 0.062335 0.513000 1.17 0.513000 0.500000 0.010993 0.000062 1.17 16.70 0.008000
CORRIDOR_FLR_6 VAV BOX COMPONENT 0.804123 0.390536 0.513000 0.412515 1.00 0.500000 0.000976 0.000063 0.412515 16.70 0.008000
User-Specified values were used. Design Size values were used if no User-Specified values were provided. Design Size values may be derived from alternate User-Specified values.

Coil:Heating:Water

Design Size Rated Capacity [W] Design Size Maximum Water Flow Rate [m3/s] Design Size U-Factor Times Area Value [W/K]
BASEMENT VAV BOX REHEAT COIL 6801.76 0.000060 141.84
RETAIL_1_FLR_1 VAV BOX REHEAT COIL 3305.38 0.000029 76.09
RETAIL_2_FLR_1 VAV BOX REHEAT COIL 1331.70 0.000012 29.54
MECH_FLR_1 VAV BOX REHEAT COIL 1731.54 0.000015 42.17
STORAGE_FLR_1 VAV BOX REHEAT COIL 1153.85 0.000010 28.92
LAUNDRY_FLR_1 VAV BOX REHEAT COIL 10449.05 0.000091 220.07
CAFE_FLR_1 VAV BOX REHEAT COIL 10115.52 0.000088 224.32
LOBBY_FLR_1 VAV BOX REHEAT COIL 26217.27 0.000229 573.93
ROOM_1_FLR_3 FAN COIL HEATING COIL 4651.52 0.000041 132.91
ROOM_2_FLR_3 FAN COIL HEATING COIL 4654.79 0.000041 133.00
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL 26893.42 0.000235 768.43
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL 26967.92 0.000236 770.56
ROOM_5_FLR_3 FAN COIL HEATING COIL 4658.62 0.000041 133.11
ROOM_6_FLR_3 FAN COIL HEATING COIL 4661.89 0.000041 133.21
CORRIDOR_FLR_3 VAV BOX REHEAT COIL 11871.41 0.000104 272.78
ROOM_1_FLR_6 FAN COIL HEATING COIL 1427.71 0.000012 40.79
ROOM_2_FLR_6 FAN COIL HEATING COIL 1429.36 0.000013 40.84
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL 6868.36 0.000060 196.25
BANQUET_FLR_6 VAV BOX REHEAT COIL 10447.66 0.000091 227.94
DINING_FLR_6 VAV BOX REHEAT COIL 10820.47 0.000095 235.80
KITCHEN_FLR_6 VAV BOX REHEAT COIL 7057.59 0.000062 148.43
CORRIDOR_FLR_6 VAV BOX REHEAT COIL 7206.92 0.000063 171.55
FLR_3_DOAS HEATING COIL 15340.96 0.000134 261.90
VAV WITH REHEAT HEATING COIL 168952.24 0.001478 2884.39
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
ROOM_1_FLR_3 DIRECT AIR 0.061735
ROOM_2_FLR_3 DIRECT AIR 0.061728
ROOM_3_MULT19_FLR_3 DIRECT AIR 0.837072
ROOM_4_MULT19_FLR_3 DIRECT AIR 0.837300
ROOM_5_FLR_3 DIRECT AIR 0.061735
ROOM_6_FLR_3 DIRECT AIR 0.061728
ROOM_1_FLR_6 DIRECT AIR 0.015434
ROOM_2_FLR_6 DIRECT AIR 0.015432
ROOM_3_MULT9_FLR_6 DIRECT AIR 0.099154
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

ZoneHVAC:FourPipeFanCoil

Design Size Maximum Supply Air Flow Rate [m3/s] Design Size Maximum Hot Water Flow [m3/s] Design Size Maximum Cold Water Flow [m3/s]
ROOM_1_FLR_3 FAN COIL 1.18 0.000041 0.000369
ROOM_2_FLR_3 FAN COIL 1.07 0.000041 0.000335
ROOM_3_MULT19_FLR_3 FAN COIL 8.31 0.000235 0.002562
ROOM_4_MULT19_FLR_3 FAN COIL 5.57 0.000236 0.001838
ROOM_5_FLR_3 FAN COIL 1.06 0.000041 0.000334
ROOM_6_FLR_3 FAN COIL 0.970524 0.000041 0.000306
ROOM_1_FLR_6 FAN COIL 0.306756 0.000012 0.000096
ROOM_2_FLR_6 FAN COIL 0.275957 0.000013 0.000087
ROOM_3_MULT9_FLR_6 FAN COIL 1.68 0.000060 0.000532
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [m3/s]
ROOM_1_FLR_3 FAN COIL_FANCOILFAN 1.18
ROOM_2_FLR_3 FAN COIL_FANCOILFAN 1.07
ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN 8.31
ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN 5.57
ROOM_5_FLR_3 FAN COIL_FANCOILFAN 1.06
ROOM_6_FLR_3 FAN COIL_FANCOILFAN 0.970524
ROOM_1_FLR_6 FAN COIL_FANCOILFAN 0.306756
ROOM_2_FLR_6 FAN COIL_FANCOILFAN 0.275957
ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN 1.68
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:Water

Design Size Design Inlet Air Temperature [C] Design Size Design Inlet Water Temperature [C] Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Outlet Air Temperature [C] Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Water Flow Rate [m3/s] Design Size Design Air Flow Rate [m3/s] Design Size Design Coil Load [W]
ROOM_1_FLR_3 FAN COIL COOLING COIL 21.69 6.70 0.008566 12.80 0.008500 0.000369 1.18  
ROOM_2_FLR_3 FAN COIL COOLING COIL 21.69 6.70 0.008572 12.80 0.008500 0.000335 1.07  
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL 21.69 6.70 0.008502 12.80 0.008500 0.002562 8.31  
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL 21.69 6.70 0.008757 12.80 0.008500 0.001838 5.57  
ROOM_5_FLR_3 FAN COIL COOLING COIL 21.69 6.70 0.008573 12.80 0.008500 0.000334 1.06  
ROOM_6_FLR_3 FAN COIL COOLING COIL 21.69 6.70 0.008580 12.80 0.008500 0.000306 0.970524  
ROOM_1_FLR_6 FAN COIL COOLING COIL 21.69 6.70 0.008563 12.80 0.008500 0.000096 0.306756  
ROOM_2_FLR_6 FAN COIL COOLING COIL 21.69 6.70 0.008570 12.80 0.008500 0.000087 0.275957  
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL 21.69 6.70 0.008602 12.80 0.008500 0.000532 1.68  
FLR_3_DOAS COOLING COIL 29.40 6.70 0.008822 11.92 0.008500 0.001300 2.05 45447.84
VAV WITH REHEAT COOLING COIL 26.78 6.70 0.009207 10.95 0.008500 0.013775 22.59 481649.27
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
FLR_3_DOAS 2.05 2.05 2.05 2.05 2.05 2.05 0.300000 1.00 2.05
VAV WITH REHEAT 11.65 11.65 22.71 11.65 22.59 22.59 0.300000 0.515772 22.59
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
FLR_3_DOAS_OA_CONTROLLER 2.05 2.05
VAV WITH REHEAT_OA_CONTROLLER 22.59  
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeatExchanger:AirToAir:SensibleAndLatent

Design Size Nominal Supply Air Flow Rate [m3/s]
FLR_3_DOAS OA HEAT RECOVERY 2.05
VAV WITH REHEAT OA HEAT RECOVERY 11.66
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ConstantVolume

User-Specified Maximum Flow Rate [m3/s]
FLR_3_DOAS FAN 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:WaterCoil

Maximum Actuated Flow [m3/s] Controller Convergence Tolerance
FLR_3_DOAS_COOLC_CONTROLLER 0.001300 0.000366
FLR_3_DOAS_HEATC_CONTROLLER 0.000134  
VAV WITH REHEAT_COOLC_CONTROLLER 0.013775 0.000035
VAV WITH REHEAT_HEATC_CONTROLLER 0.001478  
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:VariableVolume

Design Size Maximum Flow Rate [m3/s]
VAV WITH REHEAT FAN 22.59
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W] Design Minimum Flow Rate [m3/s]
COOLSYS1 PUMP SECONDARY 0.021534 3515.82  
HEATSYS1 PUMP 0.003281 988.04 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
HEATSYS1 0.003281 0.393697
COOLSYS1 0.021534 2.58
SWHSYS1 0.000375 0.045004
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Boiler:HotWater

Design Size Nominal Capacity [W] User-Specified Nominal Capacity [W] Design Size Design Water Flow Rate [m3/s]
HEATSYS1 BOILER 375016.92 375016.92 0.003281
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
COOLSYS1 PUMP 0.021534 2434.12
SWHSYS1 PUMP 0.000375 47.91
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Chiller:Electric:EIR

Design Size Reference Chilled Water Flow Rate [m3/s] Design Size Reference Capacity [W] User-Specified Reference Capacity [W] Design Size Reference Condenser Fluid Flow Rate [m3/s]
COOLSYS1 CHILLER1 0.021534 752935.70 753560.40 85.91
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SWHSYS1 WATER HEATER 0.000375
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:35

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
RETAIL_1_FLR_1_CEILING ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH |
CAFE_FLR_1_CEILING ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH |
LOBBY_FLR_1_CEILING_2 ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
RETAIL_1_FLR_1_WALL_SOUTH RETAIL_1_FLR_1_WALL_SOUTH_WINDOW |
RETAIL_2_FLR_1_WALL_WEST RETAIL_2_FLR_1_WALL_WEST_DOOR |
STORAGE_FLR_1_WALL_NORTH STORAGE_FLR_1_WALL_NORTH_ROLLDOOR |
LAUNDRY_FLR_1_WALL_EAST LAUNDRY_FLR_1_WALL_EAST_DOOR |
CAFE_FLR_1_WALL_EAST CAFE_FLR_1_WALL_EAST_DOOR |
CAFE_FLR_1_WALL_SOUTH CAFE_FLR_1_WALL_SOUTH_WINDOW |
LOBBY_FLR_1_WALL_1_NORTH LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 |
LOBBY_FLR_1_WALL_1_SOUTH LOBBY_FLR_1_WALL_SOUTH_WINDOW |
ROOM_1_FLR_3_WALL_SOUTH ROOM_1_FLR_3_WALL_SOUTH_WINDOW |
ROOM_1_FLR_3_WALL_WEST ROOM_1_FLR_3_WALL_WEST_WINDOW |
ROOM_2_FLR_3_WALL_NORTH ROOM_2_FLR_3_WALL_NORTH_WINDOW |
ROOM_2_FLR_3_WALL_WEST ROOM_2_FLR_3_WALL_WEST_WINDOW |
ROOM_3_MULT19_FLR_3_WALL_SOUTH ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW |
ROOM_4_MULT19_FLR_3_WALL_NORTH ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW |
ROOM_5_FLR_3_WALL_EAST ROOM_5_FLR_3_WALL_EAST_WINDOW |
ROOM_5_FLR_3_WALL_SOUTH ROOM_5_FLR_3_WALL_SOUTH_WINDOW |
ROOM_6_FLR_3_WALL_NORTH ROOM_6_FLR_3_WALL_NORTH_WINDOW |
ROOM_6_FLR_3_WALL_EAST ROOM_6_FLR_3_WALL_EAST_WINDOW |
CORRIDOR_FLR_3_WALL_1_NORTH CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW |
CORRIDOR_FLR_3_WALL_2_NORTH CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW |
CORRIDOR_FLR_3_WALL_1_SOUTH CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW |
CORRIDOR_FLR_3_WALL_2_SOUTH CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW |
ROOM_1_FLR_6_WALL_SOUTH ROOM_1_FLR_6_WALL_SOUTH_WINDOW |
ROOM_1_FLR_6_WALL_WEST ROOM_1_FLR_6_WALL_WEST_WINDOW |
ROOM_2_FLR_6_WALL_NORTH ROOM_2_FLR_6_WALL_NORTH_WINDOW |
ROOM_2_FLR_6_WALL_WEST ROOM_2_FLR_6_WALL_WEST_WINDOW |
ROOM_3_MULT9_FLR_6_WALL_SOUTH ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW |
BANQUET_FLR_6_WALL_NORTH BANQUET_FLR_6_WALL_NORTH_WINDOW |
DINING_FLR_6_WALL_NORTH DINING_FLR_6_WALL_NORTH_WINDOW |
KITCHEN_FLR_6_WALL_NORTH KITCHEN_FLR_6_WALL_NORTH_WINDOW |
KITCHEN_FLR_6_WALL_EAST KITCHEN_FLR_6_WALL_EAST_WINDOW |
KITCHEN_FLR_6_WALL_1_SOUTH KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW |
CORRIDOR_FLR_6_WALL_1_NORTH CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW |
CORRIDOR_FLR_6_WALL_2_NORTH CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW |
CORRIDOR_FLR_6_WALL_2_SOUTH CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:35

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:35

Version

Version ID
1 22.1


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 11.40 8.10 5.40 4.50 5.80 8.30 10.90 13.00 15.60 17.70 18.80 15.10


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 47.47 -122.32 -8.00 122.00 99868 1.1870


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 11.22 14.30 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 HotelLarge 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 DOE-2


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 22 235 36


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 BASEMENT 0.0 0.00 0.00 0.00 41.45 11.51 -1.22 1 1 1 0.00 86.56 0.00 22.86 -2.44 0.00 2.44 4826.41 TARP DOE-2 1978.83 0.00 0.00 0.00 13 0 0 Yes
2 RETAIL_1_FLR_1 0.0 0.00 0.00 0.00 5.79 2.90 1.98 1 1 1 0.00 11.58 0.00 5.79 0.00 3.96 3.96 265.76 TARP DOE-2 67.07 68.84 45.58 23.26 6 1 0 Yes
3 RETAIL_2_FLR_1 0.0 0.00 0.00 0.00 5.79 9.14 1.98 1 1 1 0.00 11.58 5.79 12.50 0.00 3.96 3.96 307.76 TARP DOE-2 77.67 26.57 24.62 0.00 6 1 0 Yes
4 MECH_FLR_1 0.0 0.00 0.00 0.00 61.87 17.68 1.98 1 1 1 53.95 69.80 12.50 22.86 0.00 3.96 3.96 650.80 TARP DOE-2 164.24 62.80 62.80 0.00 6 0 0 Yes
5 STORAGE_FLR_1 0.0 0.00 0.00 0.00 74.37 17.68 1.98 1 1 1 69.80 78.94 12.50 22.86 0.00 3.96 3.96 375.47 TARP DOE-2 94.76 36.23 28.80 0.00 6 1 0 Yes
6 LAUNDRY_FLR_1 0.0 0.00 0.00 0.00 84.28 14.33 1.98 1 1 1 81.99 86.56 5.79 22.86 0.00 3.96 3.96 309.22 TARP DOE-2 78.04 85.75 83.80 0.00 6 1 0 Yes
7 CAFE_FLR_1 0.0 0.00 0.00 0.00 70.26 2.90 1.98 1 1 1 53.95 86.56 0.00 5.79 0.00 3.96 3.96 748.35 TARP DOE-2 188.86 152.17 84.72 65.50 7 2 0 Yes
8 LOBBY_FLR_1 0.0 0.00 0.00 0.00 38.29 12.45 1.98 1 1 1 0.00 81.99 0.00 22.86 0.00 3.96 3.96 5183.56 TARP DOE-2 1308.19 434.79 345.80 85.08 18 3 0 Yes
9 ROOM_1_FLR_3 0.0 0.00 0.00 0.00 2.29 10.06 8.53 1 4 1 0.00 4.57 5.79 14.33 7.01 10.06 3.05 118.94 TARP DOE-2 39.02 39.95 26.77 13.18 6 2 0 Yes
10 ROOM_2_FLR_3 0.0 0.00 0.00 0.00 2.29 18.59 8.53 1 4 1 0.00 4.57 14.33 22.86 7.01 10.06 3.05 118.93 TARP DOE-2 39.02 39.95 26.76 13.18 6 2 0 Yes
11 ROOM_3_MULT19_FLR_3 0.0 0.00 0.00 0.00 8.53 9.14 8.53 1 76 1 6.71 10.36 5.79 12.50 7.01 10.06 3.05 74.75 TARP DOE-2 24.52 11.15 7.47 3.68 6 1 0 Yes
12 ROOM_4_MULT19_FLR_3 0.0 0.00 0.00 0.00 12.19 19.51 8.53 1 76 1 10.36 14.02 16.15 22.86 7.01 10.06 3.05 74.77 TARP DOE-2 24.53 11.15 7.47 3.68 6 1 0 Yes
13 ROOM_5_FLR_3 0.0 0.00 0.00 0.00 84.28 10.06 8.53 1 4 1 81.99 86.56 5.79 14.33 7.01 10.06 3.05 118.94 TARP DOE-2 39.02 39.95 26.77 13.18 6 2 0 Yes
14 ROOM_6_FLR_3 0.0 0.00 0.00 0.00 84.28 18.59 8.53 1 4 1 81.99 86.56 14.33 22.86 7.01 10.06 3.05 118.93 TARP DOE-2 39.02 39.95 26.76 13.18 6 2 0 Yes
15 CORRIDOR_FLR_3 0.0 0.00 0.00 0.00 43.28 14.33 8.53 1 4 1 4.57 81.99 5.79 22.86 7.01 10.06 3.05 1186.91 TARP DOE-2 389.40 48.31 32.37 15.94 20 4 0 Yes
16 ROOM_1_FLR_6 0.0 0.00 0.00 0.00 2.29 10.06 17.68 1 1 1 0.00 4.57 5.79 14.33 16.15 19.20 3.05 118.94 TARP DOE-2 39.02 39.95 26.77 13.18 6 2 0 Yes
17 ROOM_2_FLR_6 0.0 0.00 0.00 0.00 2.29 18.59 17.68 1 1 1 0.00 4.57 14.33 22.86 16.15 19.20 3.05 118.93 TARP DOE-2 39.02 39.95 26.76 13.18 6 2 0 Yes
18 ROOM_3_MULT9_FLR_6 0.0 0.00 0.00 0.00 7.93 7.62 17.68 1 9 1 4.57 11.28 5.79 9.45 16.15 19.20 3.05 74.77 TARP DOE-2 24.53 20.44 13.70 6.74 6 1 0 Yes
19 BANQUET_FLR_6 0.0 0.00 0.00 0.00 26.37 17.68 17.68 1 1 1 10.36 42.37 12.50 22.86 16.15 19.20 3.05 1010.89 TARP DOE-2 331.66 97.55 65.36 32.19 6 1 0 Yes
20 DINING_FLR_6 0.0 0.00 0.00 0.00 63.55 17.68 17.68 1 1 1 47.55 79.55 12.50 22.86 16.15 19.20 3.05 1010.89 TARP DOE-2 331.66 97.55 65.36 32.19 6 1 0 Yes
21 KITCHEN_FLR_6 0.0 0.00 0.00 0.00 82.99 14.11 17.68 1 1 1 79.55 86.56 5.79 22.86 16.15 19.20 3.05 314.87 TARP DOE-2 103.30 87.33 60.96 26.37 8 3 0 Yes
22 CORRIDOR_FLR_6 0.0 0.00 0.00 0.00 41.51 13.35 17.68 1 1 1 4.57 81.99 5.79 22.86 16.15 19.20 3.05 1256.16 TARP DOE-2 412.12 85.47 57.27 28.20 15 3 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 BASEMENT 1978.83 106.5 18.581 5.382E-002 8.814 5.380 0.000 0.000 0.000 0.000 14.194 No
2 RETAIL_1_FLR_1 67.07 10.8 6.194 0.161 11.314 10.760 0.000 0.000 0.000 0.000 22.074 No
3 RETAIL_2_FLR_1 77.67 12.5 6.194 0.161 11.314 10.760 0.000 0.000 0.000 0.000 22.074 No
4 MECH_FLR_1 164.24 2.7 61.932 1.615E-002 4.628 5.380 0.000 0.000 0.000 0.000 10.008 No
5 STORAGE_FLR_1 94.76 2.0 46.451 2.153E-002 5.720 2.690 0.000 0.000 0.000 0.000 8.410 No
6 LAUNDRY_FLR_1 78.04 8.4 9.290 0.108 4.628 61.680 535.850 0.000 0.000 0.000 602.158 No
7 CAFE_FLR_1 188.86 142.3 1.327 0.753 10.010 5.380 0.000 0.000 0.000 0.000 15.390 No
8 LOBBY_FLR_1 1308.19 422.4 3.097 0.323 10.764 8.070 0.000 0.000 0.000 0.000 18.834 No
9 ROOM_1_FLR_3 39.02 1.5 26.015 3.844E-002 8.288 6.750 0.000 0.000 0.000 0.000 15.038 No
10 ROOM_2_FLR_3 39.02 1.5 26.012 3.844E-002 8.288 6.750 0.000 0.000 0.000 0.000 15.038 No
11 ROOM_3_MULT19_FLR_3 24.52 1.5 16.349 6.116E-002 8.288 10.520 0.000 0.000 0.000 0.000 18.808 No
12 ROOM_4_MULT19_FLR_3 24.53 1.5 16.354 6.115E-002 8.288 10.520 0.000 0.000 0.000 0.000 18.808 No
13 ROOM_5_FLR_3 39.02 1.5 26.015 3.844E-002 8.288 6.750 0.000 0.000 0.000 0.000 15.038 No
14 ROOM_6_FLR_3 39.02 1.5 26.012 3.844E-002 8.288 6.750 0.000 0.000 0.000 0.000 15.038 No
15 CORRIDOR_FLR_3 389.40 21.0 18.581 5.382E-002 7.104 0.000 0.000 0.000 0.000 0.000 7.104 No
16 ROOM_1_FLR_6 39.02 1.5 26.015 3.844E-002 8.288 6.750 0.000 0.000 0.000 0.000 15.038 No
17 ROOM_2_FLR_6 39.02 1.5 26.012 3.844E-002 8.288 6.750 0.000 0.000 0.000 0.000 15.038 No
18 ROOM_3_MULT9_FLR_6 24.53 1.5 16.354 6.115E-002 8.288 10.520 0.000 0.000 0.000 0.000 18.808 No
19 BANQUET_FLR_6 331.66 249.9 1.327 0.753 10.010 67.820 0.000 0.000 0.000 0.000 77.830 No
20 DINING_FLR_6 331.66 249.9 1.327 0.753 10.010 67.820 0.000 0.000 0.000 0.000 77.830 No
21 KITCHEN_FLR_6 103.30 22.2 4.645 0.215 11.410 515.227 2419.260 0.000 0.000 0.000 2945.897 No
22 CORRIDOR_FLR_6 412.12 22.2 18.581 5.382E-002 7.104 0.000 0.000 0.000 0.000 0.000 7.104 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People MRT Calculation Type Work Efficiency Clothing Insulation Calculation Method Clothing Insulation Calculation Method Schedule Clothing Air Velocity Fanger Calculation Pierce Calculation KSU Calculation Cooling Effect Calculation Ankle Draft Calculation
1 BASEMENT PEOPLE BLDG_OCC_SCH BASEMENT 1978.83 106.5 106.5 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 106 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
2 RETAIL_1_FLR_1 PEOPLE BLDG_OCC_SCH RETAIL_1_FLR_1 67.07 10.8 10.8 0.161 6.194 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
3 RETAIL_2_FLR_1 PEOPLE BLDG_OCC_SCH RETAIL_2_FLR_1 77.67 12.5 12.5 0.161 6.194 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 13 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
4 LAUNDRY_FLR_1 PEOPLE BLDG_OCC_SCH LAUNDRY_FLR_1 78.04 8.4 8.4 0.108 9.290 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 8 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
5 CAFE_FLR_1 PEOPLE BLDG_OCC_SCH CAFE_FLR_1 188.86 142.3 142.3 0.753 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 142 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
6 LOBBY_FLR_1 PEOPLE BLDG_OCC_SCH LOBBY_FLR_1 1308.19 422.4 422.4 0.323 3.097 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 422 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
7 ROOM_1_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_1_FLR_3 39.02 1.5 1.5 3.844E-002 26.015 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
8 ROOM_2_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_2_FLR_3 39.02 1.5 1.5 3.844E-002 26.012 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
9 ROOM_3_MULT19_FLR_3 PEOPLE ALWAYS_OFF ROOM_3_MULT19_FLR_3 24.52 1.5 1.5 6.116E-002 16.349 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
10 ROOM_4_MULT19_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_4_MULT19_FLR_3 24.53 1.5 1.5 6.115E-002 16.354 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
11 ROOM_5_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_5_FLR_3 39.02 1.5 1.5 3.844E-002 26.015 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
12 ROOM_6_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_6_FLR_3 39.02 1.5 1.5 3.844E-002 26.012 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
13 ROOM_1_FLR_6 PEOPLE GUESTROOM_OCC_SCH ROOM_1_FLR_6 39.02 1.5 1.5 3.844E-002 26.015 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
14 ROOM_2_FLR_6 PEOPLE GUESTROOM_OCC_SCH ROOM_2_FLR_6 39.02 1.5 1.5 3.844E-002 26.012 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
15 ROOM_3_MULT9_FLR_6 PEOPLE GUESTROOM_OCC_SCH ROOM_3_MULT9_FLR_6 24.53 1.5 1.5 6.115E-002 16.354 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
16 BANQUET_FLR_6 PEOPLE BLDG_OCC_SCH BANQUET_FLR_6 331.66 249.9 249.9 0.753 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 250 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
17 DINING_FLR_6 PEOPLE BLDG_OCC_SCH DINING_FLR_6 331.66 249.9 249.9 0.753 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 250 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
18 KITCHEN_FLR_6 PEOPLE BLDG_OCC_SCH KITCHEN_FLR_6 103.30 22.2 22.2 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 22 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
19 STORAGE_FLR_1 PEOPLE BLDG_OCC_SCH STORAGE_FLR_1 94.76 2.0 2.0 2.153E-002 46.451 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
20 CORRIDOR_FLR_3 PEOPLE BLDG_OCC_SCH CORRIDOR_FLR_3 389.40 21.0 21.0 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 21 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
21 CORRIDOR_FLR_6 PEOPLE BLDG_OCC_SCH CORRIDOR_FLR_6 412.12 22.2 22.2 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 22 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
22 MECH_FLR_1 PEOPLE BLDG_OCC_SCH MECH_FLR_1 164.24 2.7 2.7 1.615E-002 61.932 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 3 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 BASEMENT_LIGHTS LTG_SCH_BASEMENT BASEMENT 1978.83 106.5 17441.963 8.814 163.776 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 17441.963
2 RETAIL_1_FLR_1_LIGHTS LTG_SCH_RETAIL RETAIL_1_FLR_1 67.07 10.8 758.849 11.314 70.076 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 758.849
3 RETAIL_2_FLR_1_LIGHTS LTG_SCH_RETAIL RETAIL_2_FLR_1 77.67 12.5 878.750 11.314 70.076 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 878.750
4 MECH_FLR_1_LIGHTS LTG_SCH_MECHANIC MECH_FLR_1 164.24 2.7 760.196 4.628 286.650 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 760.196
5 STORAGE_FLR_1_LIGHTS LTG_SCH_STORAGE STORAGE_FLR_1 94.76 2.0 542.017 5.720 265.695 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 542.017
6 LAUNDRY_FLR_1_LIGHTS LTG_SCH_LAUNDRY LAUNDRY_FLR_1 78.04 8.4 361.204 4.628 43.000 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 361.204
7 CAFE_FLR_1_LIGHTS LTG_SCH_DINING CAFE_FLR_1 188.86 142.3 1890.589 10.010 13.286 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1890.589
8 LOBBY_FLR_1_LIGHTS LTG_SCH_LOBBY LOBBY_FLR_1 1308.19 422.4 14081.185 10.764 33.333 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 14081.185
9 ROOM_1_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_1_FLR_3 39.02 1.5 323.422 8.288 215.615 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 323.422
10 ROOM_2_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_2_FLR_3 39.02 1.5 323.384 8.288 215.590 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 323.384
11 ROOM_3_MULT19_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_3_MULT19_FLR_3 24.52 1.5 203.259 8.288 135.506 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 203.259
12 ROOM_4_MULT19_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_4_MULT19_FLR_3 24.53 1.5 203.314 8.288 135.543 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 203.314
13 ROOM_5_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_5_FLR_3 39.02 1.5 323.422 8.288 215.615 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 323.422
14 ROOM_6_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_6_FLR_3 39.02 1.5 323.384 8.288 215.590 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 323.384
15 CORRIDOR_FLR_3_LIGHTS LTG_SCH_CORRIDOR CORRIDOR_FLR_3 389.40 21.0 2766.397 7.104 132.003 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2766.397
16 ROOM_1_FLR_6_LIGHTS LTG_SCH_GUESTROOM ROOM_1_FLR_6 39.02 1.5 323.422 8.288 215.615 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 323.422
17 ROOM_2_FLR_6_LIGHTS LTG_SCH_GUESTROOM ROOM_2_FLR_6 39.02 1.5 323.384 8.288 215.590 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 323.384
18 ROOM_3_MULT9_FLR_6_LIGHTS LTG_SCH_GUESTROOM ROOM_3_MULT9_FLR_6 24.53 1.5 203.314 8.288 135.543 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 203.314
19 BANQUET_FLR_6_LIGHTS LTG_SCH_DINING BANQUET_FLR_6 331.66 249.9 3320.034 10.010 13.286 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3320.034
20 DINING_FLR_6_LIGHTS LTG_SCH_DINING DINING_FLR_6 331.66 249.9 3320.034 10.010 13.286 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3320.034
21 KITCHEN_FLR_6_LIGHTS LTG_SCH_KITCHEN KITCHEN_FLR_6 103.30 22.2 1178.676 11.410 53.003 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1178.676
22 CORRIDOR_FLR_6_LIGHTS LTG_SCH_CORRIDOR CORRIDOR_FLR_6 412.12 22.2 2927.804 7.104 132.002 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2927.804


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 BASEMENT_MISCPLUG_EQUIP BASEMENT_EQUIP_SCH BASEMENT 1978.83 106.5 10646.106 5.380 99.964 0.000 0.500 0.000 0.500 MiscPlug 0.000 10646.106
2 RETAIL_1_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH RETAIL_1_FLR_1 67.07 10.8 721.688 10.760 66.644 0.000 0.500 0.000 0.500 MiscPlug 0.000 721.688
3 RETAIL_2_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH RETAIL_2_FLR_1 77.67 12.5 835.717 10.760 66.644 0.000 0.500 0.000 0.500 MiscPlug 0.000 835.717
4 MECH_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH MECH_FLR_1 164.24 2.7 883.628 5.380 333.193 0.000 0.500 0.000 0.500 MiscPlug 0.000 883.628
5 STORAGE_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH STORAGE_FLR_1 94.76 2.0 254.902 2.690 124.952 0.000 0.500 0.000 0.500 MiscPlug 0.000 254.902
6 LAUNDRY_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH LAUNDRY_FLR_1 78.04 8.4 4813.474 61.680 573.033 0.000 0.500 0.000 0.500 MiscPlug 0.000 4813.474
7 CAFE_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH CAFE_FLR_1 188.86 142.3 1016.077 5.380 7.140 0.000 0.500 0.000 0.500 MiscPlug 0.000 1016.077
8 LOBBY_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH LOBBY_FLR_1 1308.19 422.4 10557.062 8.070 24.991 0.000 0.500 0.000 0.500 MiscPlug 0.000 10557.062
9 ROOM_1_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_1_FLR_3 39.02 1.5 263.399 6.750 175.599 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.399
10 ROOM_2_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_2_FLR_3 39.02 1.5 263.368 6.750 175.579 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.368
11 ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_3_MULT19_FLR_3 24.52 1.5 257.991 10.520 171.994 0.000 0.500 0.000 0.500 MiscPlug 0.000 257.991
12 ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_4_MULT19_FLR_3 24.53 1.5 258.061 10.520 172.041 0.000 0.500 0.000 0.500 MiscPlug 0.000 258.061
13 ROOM_5_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_5_FLR_3 39.02 1.5 263.399 6.750 175.599 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.399
14 ROOM_6_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_6_FLR_3 39.02 1.5 263.368 6.750 175.579 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.368
15 ROOM_1_FLR_6_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_1_FLR_6 39.02 1.5 263.399 6.750 175.599 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.399
16 ROOM_2_FLR_6_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_2_FLR_6 39.02 1.5 263.368 6.750 175.579 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.368
17 ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_ADVA ROOM_3_MULT9_FLR_6 24.53 1.5 258.061 10.520 172.041 0.000 0.500 0.000 0.500 MiscPlug 0.000 258.061
18 BANQUET_FLR_6_MISCPLUG_EQUIP KITCHEN_ELEC_EQUIP_SCH BANQUET_FLR_6 331.66 249.9 22493.008 67.820 90.009 0.000 0.500 0.000 0.500 Cooking 0.000 6747.903
19 DINING_FLR_6_MISCPLUG_EQUIP KITCHEN_ELEC_EQUIP_SCH DINING_FLR_6 331.66 249.9 22493.008 67.820 90.009 0.000 0.500 0.000 0.500 Cooking 0.000 6747.903
20 KITCHEN_FLR_6_MISCELEC_EQUIP KITCHEN_ELEC_EQUIP_SCH KITCHEN_FLR_6 103.30 22.2 52482.799 508.040 2360.050 0.200 0.500 0.100 0.200 Cooking 0.000 15744.840
21 KITCHEN_FLR_6_REACH-IN-FREEZER ALWAYS_ON KITCHEN_FLR_6 103.30 22.2 457.500 4.429 20.573 0.000 0.250 0.000 0.750 ReachInFreezer 457.500 457.500
22 KITCHEN_FLR_6_REACH-IN-REFRIGERATOR ALWAYS_ON KITCHEN_FLR_6 103.30 22.2 285.000 2.759 12.816 0.000 0.250 0.000 0.750 ReachInRefrigerator 285.000 285.000


GasEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 LAUNDRY_FLR_1_MISCGAS_EQUIP BLDG_EQUIP_SCH LAUNDRY_FLR_1 78.04 8.4 41817.449 535.850 4978.268 0.000 0.500 0.000 0.500 Laundry 0.000 41817.449
2 KITCHEN_FLR_6_MISCGAS_EQUIP KITCHEN_GAS_EQUIP_SCH KITCHEN_FLR_6 103.30 22.2 249920.353 2419.260 11238.437 0.100 0.200 0.700 0.000 Cooking 0.000 74976.106


Construction CTF

Construction Name Index #Layers #CTFs Time Step {hours} ThermalConductance {w/m2-K} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 SWINGING DOOR_CON 1 1 1 0.167 3.065 0.900 0.900 0.700 0.700 MediumRough
2 OVERHEAD DOOR_CON 2 1 1 0.167 2.390 0.900 0.900 0.700 0.700 MediumRough
3 INTERIORFURNISHINGS 3 1 9 0.167 0.8000 0.900 0.900 0.700 0.700 MediumSmooth
4 INT_WALL 8 2 4 0.167 6.299 0.900 0.900 0.700 0.700 Smooth
5 NONRES_ROOF 18 3 3 0.167 0.1864 0.900 0.900 0.770 0.700 Rough
6 RES_ROOF 19 3 3 0.167 0.1864 0.900 0.900 0.770 0.700 Rough
7 NONRES_EXT_WALL_GRD 21 3 9 0.167 0.8203 0.900 0.900 0.700 0.700 MediumRough
8 NONRES_EXT_WALL_MID 22 3 9 0.167 1.021 0.900 0.900 0.700 0.700 MediumRough
9 NONRES_EXT_WALL_TOP 23 3 9 0.167 1.034 0.900 0.900 0.700 0.700 MediumRough
10 RES_EXT_WALL_MID 25 3 9 0.167 0.9169 0.900 0.900 0.700 0.700 MediumRough
11 RES_EXT_WALL_TOP 26 3 9 0.167 0.9299 0.900 0.900 0.700 0.700 MediumRough
12 NONRES_FLOOR 30 3 7 0.167 0.2277 0.900 0.900 0.700 0.700 MediumSmooth
13 NONRES_FLOOR_CEILING 33 3 7 0.167 0.2277 0.900 0.900 0.700 0.700 VeryRough
14 BASEMENT_FLOOR 36 2 7 0.333 2.705 0.900 0.900 0.700 0.700 MediumRough
15 BASEMENT_WALL_NORTH_CFACTOR 39 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
16 BASEMENT_WALL_EAST_CFACTOR 40 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
17 BASEMENT_WALL_SOUTH_CFACTOR 41 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
18 BASEMENT_WALL_WEST_CFACTOR 42 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough


Material CTF Summary

Material Name Thickness {m} Conductivity {w/m-K} Density {kg/m3} Specific Heat {J/kg-K} ThermalResistance {m2-K/w}
1 OPAQUE DOOR PANEL_CON 0.0000 0.000 0.000 0.000 0.3263
2 OVERHEAD DOOR_CON PANEL 0.0000 0.000 0.000 0.000 0.4184
3 STD WOOD 6INCH 0.1500 0.120 540.000 1210.000 1.250
4 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
5 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
6 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
7 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 5.307
8 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
9 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
10 RES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 5.307
11 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
12 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
13 NONRES_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 1.052
14 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
15 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
16 NONRES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 0.8120
17 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
18 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
19 NONRES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.7993
20 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
21 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
22 RES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 0.9233
23 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
24 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
25 RES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.9080
26 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
27 NONRES_FLOOR_INSULATION 0.0000 0.000 0.000 0.000 4.131
28 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
29 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
30 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
31 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
32 NONRES_FLOOR_INSULATION 0.0000 0.000 0.000 0.000 4.131
33 M10 200MM CONCRETE BLOCK BASEMENT WALL 0.2032 1.326 1842.000 912.000 0.1532
34 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
35 ~FC_Insulation_1 0.0000 0.000 0.000 0.000 2.312
36 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
37 ~FC_Insulation_2 0.0000 0.000 0.000 0.000 2.312
38 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
39 ~FC_Insulation_3 0.0000 0.000 0.000 0.000 2.312
40 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
41 ~FC_Insulation_4 0.0000 0.000 0.000 0.000 2.312
42 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01


CTF

Time Outside Cross Inside Flux (except final one)
1 1 0.0000000 0.0000000 -0.0000000 -0.0000000
2 0 3.0649134 3.0649134 3.0649134  
3 1 0.0000000 0.0000000 -0.0000000 -0.0000000
4 0 2.3900722 2.3900722 2.3900722  
5 9 -0.27580628E-02 0.97439125E-12 -0.27580628E-02 0.28516790E-03
6 8 0.73590997E-01 0.21837543E-08 0.73590997E-01 -0.77836043E-02
7 7 -0.82599318 0.23162835E-06 -0.82599318 0.89703933E-01
8 6 5.1113916 0.48671053E-05 5.1113916 -0.57224845
9 5 -19.214933 0.30163627E-04 -19.214933 2.2266322
10 4 45.557404 0.63181060E-04 45.557404 -5.4853312
11 3 -68.275533 0.44785456E-04 -68.275533 8.5710568
12 2 62.555368 0.93952058E-05 62.555368 -8.2111738
13 1 -31.904423 0.39200004E-06 -31.904423 4.3886678
14 0 6.9260389 0.77047546E-09 6.9260389  
15 4 0.68458728E-09 0.26079551E-09 0.68458728E-09 -0.34507121E-18
16 3 -0.72180374E-03 0.24295686E-03 -0.72180374E-03 0.69691454E-09
17 2 0.83054762 0.27682775 0.83054762 -0.35168967E-03
18 1 -12.650482 3.3590720 -12.650482 0.19281313
19 0 16.907513 1.4507143 16.907513  
20 3 -0.62854340E-06 0.84784826E-09 -0.38512804E-05 0.91756347E-17
21 2 0.78257096 0.11428808E-02 1.0614277 -0.73836085E-06
22 1 -21.991499 0.76199851E-01 -6.3161914 0.20349372
23 0 21.357363 0.71091016E-01 5.4032014  
24 3 -0.62854340E-06 0.84784826E-09 -0.38512804E-05 0.91756347E-17
25 2 0.78257096 0.11428808E-02 1.0614277 -0.73836085E-06
26 1 -21.991499 0.76199851E-01 -6.3161914 0.20349372
27 0 21.357363 0.71091016E-01 5.4032014  
28 9 -0.15703352E-14 0.29012323E-16 -0.15483104E-09 0.40370831E-16
29 8 0.22592825E-07 0.11106548E-12 0.38529762E-03 -0.25688817E-09
30 7 -0.12465369E-01 0.57225352E-08 -0.23408026E-01 0.14173579E-03
31 6 0.41143163 0.19878644E-05 0.47726710 -0.48194459E-02
32 5 -5.2499075 0.74130146E-04 -4.4810026 0.63919688E-01
33 4 33.265337 0.60571720E-03 21.595652 -0.42560793
34 3 -111.78466 0.13187857E-02 -55.931065 1.5232626
35 2 197.68466 0.74115454E-03 78.156489 -2.9095067
36 1 -171.36898 0.79055603E-04 -55.336681 2.7491709
37 0 57.057407 0.44959794E-06 15.545184  
38 9 0.14302076E-15 0.35792568E-16 -0.14541430E-09 -0.27421543E-17
39 8 0.21269444E-07 0.13686051E-12 0.37140784E-03 -0.24184090E-09
40 7 -0.12050952E-01 0.71525680E-08 -0.22811354E-01 0.13702371E-03
41 6 0.40017121 0.24988627E-05 0.46767819 -0.46867126E-02
42 5 -5.1400200 0.93645327E-04 -4.4073602 0.62557131E-01
43 4 32.779281 0.76858103E-03 21.307814 -0.41915444
44 3 -110.75053 0.16800125E-02 -55.362013 1.5083221
45 2 196.65975 0.94749847E-03 77.634567 -2.8932310
46 1 -170.99041 0.10139533E-03 -55.184883 2.7425359
47 0 57.057407 0.57877233E-06 15.570231  
48 9 0.33566835E-16 0.35384250E-16 -0.14478218E-09 -0.87565041E-18
49 8 0.21180494E-07 0.13854999E-12 0.37046393E-03 -0.24082951E-09
50 7 -0.12022754E-01 0.72481687E-08 -0.22770744E-01 0.13670309E-03
51 6 0.39940498 0.25332696E-05 0.46702484 -0.46776806E-02
52 5 -5.1325420 0.94967185E-04 -4.4023386 0.62464408E-01
53 4 32.746200 0.77967008E-03 21.288178 -0.41871522
54 3 -110.68014 0.17047184E-02 -55.323188 1.5073051
55 2 196.58997 0.96166638E-03 77.598974 -2.8921229
56 1 -170.96463 0.10293464E-03 -55.174560 2.7420841
57 0 57.057407 0.58770932E-06 15.571958  
58 9 -0.29206544E-14 0.31488305E-16 -0.15031727E-09 0.48064473E-16
59 8 0.21958778E-07 0.12356532E-12 0.37867817E-03 -0.24967887E-09
60 7 -0.12267989E-01 0.64094198E-08 -0.23123879E-01 0.13949151E-03
61 6 0.40606866 0.22324768E-05 0.47270315 -0.47562292E-02
62 5 -5.1975737 0.83445227E-04 -4.4459647 0.63270770E-01
63 4 33.033866 0.68326082E-03 21.458733 -0.42253461
64 3 -111.29222 0.14903991E-02 -55.660391 1.5161481
65 2 197.19665 0.83899866E-03 77.908180 -2.9017570
66 1 -171.18874 0.89630080E-04 -55.264364 2.7460119
67 0 57.057407 0.51068186E-06 15.557036  
68 9 -0.29497736E-14 0.32939851E-16 -0.14970570E-09 0.45584202E-16
69 8 0.21872815E-07 0.12523736E-12 0.37777579E-03 -0.24870145E-09
70 7 -0.12241065E-01 0.65023057E-08 -0.23085114E-01 0.13918537E-03
71 6 0.40533708 0.22656711E-05 0.47208016 -0.47476058E-02
72 5 -5.1904345 0.84713026E-04 -4.4411801 0.63182247E-01
73 4 33.002288 0.69384191E-03 21.440032 -0.42211534
74 3 -111.22504 0.15138688E-02 -55.623419 1.5151774
75 2 197.13007 0.85240592E-03 77.874271 -2.9006996
76 1 -171.16415 0.91081681E-04 -55.254501 2.7455809
77 0 57.057407 0.51907125E-06 15.558664  
78 7 -0.14139450E-14 -0.18802902E-16 -0.22311785E-13 0.54375338E-15
79 6 0.16999971E-10 0.27590984E-11 0.52267399E-09 -0.18616555E-10
80 5 -0.63950587E-07 0.13451749E-07 -0.21905428E-05 0.17144787E-06
81 4 0.72477507E-04 0.50724086E-05 0.17668371E-02 -0.28223350E-03
82 3 -0.10573811E-01 0.17927531E-03 -0.21549182 0.43318087E-01
83 2 0.15010112 0.77388015E-03 2.8998331 -0.61891034
84 1 -0.37982851 0.49528818E-03 -7.1368477 1.5694772
85 0 0.24168561 0.34021171E-05 4.4521969  
86 7 -0.22311785E-13 -0.18802902E-16 -0.14139450E-14 0.54375338E-15
87 6 0.52267399E-09 0.27590984E-11 0.16999971E-10 -0.18616555E-10
88 5 -0.21905428E-05 0.13451749E-07 -0.63950587E-07 0.17144787E-06
89 4 0.17668371E-02 0.50724086E-05 0.72477507E-04 -0.28223350E-03
90 3 -0.21549182 0.17927531E-03 -0.10573811E-01 0.43318087E-01
91 2 2.8998331 0.77388015E-03 0.15010112 -0.61891034
92 1 -7.1368477 0.49528818E-03 -0.37982851 1.5694772
93 0 4.4521969 0.34021171E-05 0.24168561  
94 7 -0.52459208E-15 -0.63961428E-15 -0.12292524E-09 -0.35846135E-17
95 6 0.39860198E-02 0.96339020E-07 0.40499006E-03 -0.70890431E-04
96 5 -0.20832379 0.49172556E-04 -0.20585669E-01 0.38489246E-02
97 4 3.5198270 0.18993977E-02 0.34924834 -0.69168259E-01
98 3 -23.366787 0.13311857E-01 -2.4329538 0.50524779
99 2 64.890127 0.19943872E-01 7.3672511 -1.5911358
100 1 -76.040094 0.56792084E-02 -9.5568013 2.1361271
101 0 31.242244 0.96490710E-04 4.3344156  
102 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
103 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
104 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
105 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
106 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
107 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
108 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
109 0 0.43108349 0.21254961E-04 60.838472  
110 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
111 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
112 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
113 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
114 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
115 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
116 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
117 0 0.43108349 0.21254961E-04 60.838472  
118 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
119 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
120 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
121 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
122 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
123 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
124 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
125 0 0.43108349 0.21254961E-04 60.838472  
126 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
127 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
128 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
129 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
130 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
131 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
132 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
133 0 0.43108349 0.21254961E-04 60.838472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {W/m2-K} Conductance (Before Adjusted) {W/m2-K} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 NONRESWINDOW_U_0.38_SHGC_0.36 37 1 VerySmooth 2.159 2.159 1.000 0.361    
2 RESWINDOW_U_0.38_SHGC_0.36 38 1 VerySmooth 2.159 2.159 1.000 0.361    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {m} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLAZING LAYER SpectralAverage   3.45900E-002 0.27318 0.51781 0.51781 0.39600 0.13802 0.18068 0.00000 0.84000 0.84000 0.11893 1.00000 No
2 RESIDENTIAL WINDOW GLAZING LAYER SpectralAverage   3.45900E-002 0.27318 0.51781 0.51781 0.39600 0.13802 0.18068 0.00000 0.84000 0.84000 0.11893 1.00000 No


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 7 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Enclosure/Window Adjacency Daylighting Counts

Enclosure Name Number of Exterior Windows Number of Exterior Windows in Adjacent Enclosures
1 CAFE_FLR_1 1 0
2 LOBBY_FLR_1 1 0
3 BANQUET_FLR_6 1 0
4 DINING_FLR_6 1 0


Enclosure/Window Adjacency Daylighting Matrix

Enclosure Name Number of Adjacent Enclosures with Windows Adjacent Enclosure Names - 1st 100 (max)
1 CAFE_FLR_1 0  
2 LOBBY_FLR_1 0  
3 BANQUET_FLR_6 0  
4 DINING_FLR_6 0  


#Refrigeration Compressor Racks

Number of Refrigeration Compressor Racks
1 2


Refrigeration Compressor Rack

Compressor Rack Name # Refrigerated Cases Connected # WalkIn Coolers Connected Heat Rejection Location Condenser Type COP
1 RACK1 1 0 Zone Air-Cooled 1.500
2 RACK2 1 0 Zone Air-Cooled 3.000


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWH LAUNDRY G WATER HEATER 1.1356 163316.0 11.511 0.4388
2 WaterHeater:Mixed SWH BOOSTER E WATER HEATER 2.2712E-002 8000.0 1.219 1.1187
3 WaterHeater:Mixed SWHSYS1 WATER HEATER 2.2712 175842.6 5.775 0.3748


Surface Convection Parameters

Surface Name Outside Model Assignment Outside Area [m2] Outside Perimeter [m] Outside Height [m] Inside Model Assignment Inside Height [m] Inside Perimeter Envelope [m] Inside Hydraulic Diameter [m] Window Wall Ratio Window Location Near Radiant {Yes/No} Has Active HVAC {Yes/No}
1 BASEMENT_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
2 BASEMENT_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
3 BASEMENT_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
4 BASEMENT_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
5 BASEMENT_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
6 BASEMENT_CEILING_1 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
7 BASEMENT_CEILING_2 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
8 BASEMENT_CEILING_3 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
9 BASEMENT_CEILING_4 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
10 BASEMENT_CEILING_5 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
11 BASEMENT_CEILING_6 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
12 BASEMENT_CEILING_7 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
13 BASEMENT_CEILING_8 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
14 BASEMENT_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
15 RETAIL_1_FLR_1_WALL_SOUTH 0 506.51 211.91 19.20 0 3.96 17.37 7.72 0.34 4 No No
16 RETAIL_1_FLR_1_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.96 17.37 7.72 0.34 1 No No
17 RETAIL_1_FLR_1_WALL_WEST 0 194.63 84.12 19.20 0 3.96 17.37 7.72 0.34 3 No No
18 RETAIL_1_FLR_1_WALL_NORTH 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
19 RETAIL_1_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
20 RETAIL_1_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
21 RETAIL_1_FLR_1_CEILING 0 1782.60 293.11 15.24 0 3.96 17.37 7.72 0.34 0 No No
22 RETAIL_1_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
23 RETAIL_2_FLR_1_WALL_WEST 0 194.63 84.12 19.20 0 3.96 6.71 8.49 0.00 0 No No
24 RETAIL_2_FLR_1_WALL_WEST_DOOR 0 194.63 84.12 19.20 0 3.96 6.71 8.49 0.00 0 No No
25 RETAIL_2_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
26 RETAIL_2_FLR_1_WALL_NORTH 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
27 RETAIL_2_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
28 RETAIL_2_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
29 RETAIL_2_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
30 RETAIL_2_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
31 MECH_FLR_1_WALL_NORTH 0 670.01 217.46 19.20 0 3.96 15.85 12.53 0.00 0 No No
32 MECH_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
33 MECH_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
34 MECH_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
35 MECH_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
36 MECH_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
37 MECH_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
38 STORAGE_FLR_1_WALL_NORTH 0 670.01 217.46 19.20 0 3.96 9.14 9.72 0.00 0 No No
39 STORAGE_FLR_1_WALL_NORTH_ROLLDOOR 0 670.01 217.46 19.20 0 3.96 9.14 9.72 0.00 0 No No
40 STORAGE_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
41 STORAGE_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
42 STORAGE_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
43 STORAGE_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
44 STORAGE_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
45 STORAGE_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
46 LAUNDRY_FLR_1_WALL_NORTH 0 670.01 217.46 19.20 0 3.96 21.64 7.21 0.00 0 No No
47 LAUNDRY_FLR_1_WALL_EAST 0 194.63 217.46 19.20 0 3.96 21.64 7.21 0.00 0 No No
48 LAUNDRY_FLR_1_WALL_EAST_DOOR 0 194.63 217.46 19.20 0 3.96 21.64 7.21 0.00 0 No No
49 LAUNDRY_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
50 LAUNDRY_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
51 LAUNDRY_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
52 LAUNDRY_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
53 LAUNDRY_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
54 CAFE_FLR_1_WALL_EAST 0 194.63 217.46 19.20 0 3.96 38.40 9.84 0.43 3 No No
55 CAFE_FLR_1_WALL_EAST_DOOR 0 194.63 217.46 19.20 0 3.96 38.40 9.84 0.43 0 No No
56 CAFE_FLR_1_WALL_SOUTH 0 506.51 211.91 19.20 0 3.96 38.40 9.84 0.43 4 No No
57 CAFE_FLR_1_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.96 38.40 9.84 0.43 1 No No
58 CAFE_FLR_1_WALL_1_NORTH 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
59 CAFE_FLR_1_WALL_2_NORTH 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
60 CAFE_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
61 CAFE_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
62 CAFE_FLR_1_CEILING 0 1782.60 293.11 15.24 0 3.96 38.40 9.84 0.43 0 No No
63 CAFE_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
64 LOBBY_FLR_1_WALL_1_NORTH 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 3 No No
65 LOBBY_FLR_1_WALL_1_NORTH_DOOR1 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 0 No No
66 LOBBY_FLR_1_WALL_1_NORTH_DOOR2 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 0 No No
67 LOBBY_FLR_1_WALL_2_NORTH 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 4 No No
68 LOBBY_FLR_1_WALL_1_SOUTH 0 506.51 211.91 19.20 0 3.96 109.73 24.95 0.20 4 No No
69 LOBBY_FLR_1_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.96 109.73 24.95 0.20 1 No No
70 LOBBY_FLR_1_WALL_1_WEST 0 194.63 84.12 19.20 0 3.96 109.73 24.95 0.20 3 No No
71 LOBBY_FLR_1_WALL_2_SOUTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
72 LOBBY_FLR_1_WALL_3_SOUTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
73 LOBBY_FLR_1_WALL_2_WEST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
74 LOBBY_FLR_1_WALL_3_WEST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
75 LOBBY_FLR_1_WALL_4_WEST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
76 LOBBY_FLR_1_WALL_3_NORTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
77 LOBBY_FLR_1_WALL_4_NORTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
78 LOBBY_FLR_1_WALL_1_EAST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
79 LOBBY_FLR_1_WALL_2_EAST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
80 LOBBY_FLR_1_WALL_3_EAST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
81 LOBBY_FLR_1_FLOOR_1 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
82 LOBBY_FLR_1_FLOOR_2 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
83 LOBBY_FLR_1_CEILING_1 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
84 LOBBY_FLR_1_CEILING_2 0 1782.60 293.11 15.24 0 3.96 109.73 24.95 0.20 0 No No
85 LOBBY_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
86 ROOM_1_FLR_3_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 3 No No
87 ROOM_1_FLR_3_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 2 No No
88 ROOM_1_FLR_3_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
89 ROOM_1_FLR_3_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
90 ROOM_1_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
91 ROOM_1_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
92 ROOM_1_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
93 ROOM_1_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
94 ROOM_1_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
95 ROOM_2_FLR_3_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
96 ROOM_2_FLR_3_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
97 ROOM_2_FLR_3_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
98 ROOM_2_FLR_3_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
99 ROOM_2_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
100 ROOM_2_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
101 ROOM_2_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
102 ROOM_2_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
103 ROOM_2_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
104 ROOM_3_MULT19_FLR_3_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 3.66 4.73 0.33 3 No No
105 ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 3.66 4.73 0.33 2 No No
106 ROOM_3_MULT19_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
107 ROOM_3_MULT19_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
108 ROOM_3_MULT19_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
109 ROOM_3_MULT19_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
110 ROOM_3_MULT19_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
111 ROOM_3_MULT19_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
112 ROOM_4_MULT19_FLR_3_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 3.66 4.73 0.33 3 No No
113 ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 3.66 4.73 0.33 2 No No
114 ROOM_4_MULT19_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
115 ROOM_4_MULT19_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
116 ROOM_4_MULT19_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
117 ROOM_4_MULT19_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
118 ROOM_4_MULT19_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
119 ROOM_4_MULT19_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
120 ROOM_5_FLR_3_WALL_EAST 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
121 ROOM_5_FLR_3_WALL_EAST_WINDOW 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
122 ROOM_5_FLR_3_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 3 No No
123 ROOM_5_FLR_3_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 2 No No
124 ROOM_5_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
125 ROOM_5_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
126 ROOM_5_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
127 ROOM_5_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
128 ROOM_5_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
129 ROOM_6_FLR_3_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
130 ROOM_6_FLR_3_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
131 ROOM_6_FLR_3_WALL_EAST 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
132 ROOM_6_FLR_3_WALL_EAST_WINDOW 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
133 ROOM_6_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
134 ROOM_6_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
135 ROOM_6_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
136 ROOM_6_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
137 ROOM_6_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
138 CORRIDOR_FLR_3_WALL_1_NORTH 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 3 No No
139 CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 2 No No
140 CORRIDOR_FLR_3_WALL_2_NORTH 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 3 No No
141 CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 2 No No
142 CORRIDOR_FLR_3_WALL_1_SOUTH 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 3 No No
143 CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 2 No No
144 CORRIDOR_FLR_3_WALL_2_SOUTH 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 3 No No
145 CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 2 No No
146 CORRIDOR_FLR_3_WALL_3_NORTH 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
147 CORRIDOR_FLR_3_WALL_1_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
148 CORRIDOR_FLR_3_WALL_2_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
149 CORRIDOR_FLR_3_WALL_3_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
150 CORRIDOR_FLR_3_WALL_4_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
151 CORRIDOR_FLR_3_WALL_3_SOUTH 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
152 CORRIDOR_FLR_3_WALL_1_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
153 CORRIDOR_FLR_3_WALL_2_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
154 CORRIDOR_FLR_3_WALL_3_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
155 CORRIDOR_FLR_3_WALL_4_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
156 CORRIDOR_FLR_3_FLOOR_1 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
157 CORRIDOR_FLR_3_FLOOR_2 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
158 CORRIDOR_FLR_3_FLOOR_3 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
159 CORRIDOR_FLR_3_CEILING_1 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
160 CORRIDOR_FLR_3_CEILING_2 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
161 CORRIDOR_FLR_3_CEILING_3 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
162 CORRIDOR_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
163 ROOM_1_FLR_6_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 3 No No
164 ROOM_1_FLR_6_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 2 No No
165 ROOM_1_FLR_6_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
166 ROOM_1_FLR_6_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
167 ROOM_1_FLR_6_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
168 ROOM_1_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
169 ROOM_1_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
170 ROOM_1_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 13.11 5.95 0.33 0 No No
171 ROOM_1_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
172 ROOM_2_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
173 ROOM_2_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
174 ROOM_2_FLR_6_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
175 ROOM_2_FLR_6_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
176 ROOM_2_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
177 ROOM_2_FLR_6_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
178 ROOM_2_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
179 ROOM_2_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 13.11 5.95 0.33 0 No No
180 ROOM_2_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
181 ROOM_3_MULT9_FLR_6_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 6.71 4.73 0.33 3 No No
182 ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 6.71 4.73 0.33 2 No No
183 ROOM_3_MULT9_FLR_6_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
184 ROOM_3_MULT9_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
185 ROOM_3_MULT9_FLR_6_WALL_WEST 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
186 ROOM_3_MULT9_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
187 ROOM_3_MULT9_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 6.71 4.73 0.33 0 No No
188 ROOM_3_MULT9_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
189 BANQUET_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 3 No No
190 BANQUET_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 2 No No
191 BANQUET_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
192 BANQUET_FLR_6_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
193 BANQUET_FLR_6_WALL_WEST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
194 BANQUET_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
195 BANQUET_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 32.00 15.66 0.33 0 No No
196 BANQUET_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
197 DINING_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 3 No No
198 DINING_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 2 No No
199 DINING_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
200 DINING_FLR_6_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
201 DINING_FLR_6_WALL_WEST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
202 DINING_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
203 DINING_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 32.00 15.66 0.33 0 No No
204 DINING_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
205 KITCHEN_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 28.65 8.58 0.30 3 No No
206 KITCHEN_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 28.65 8.58 0.30 2 No No
207 KITCHEN_FLR_6_WALL_EAST 0 194.63 217.46 19.20 0 3.05 28.65 8.58 0.30 3 No No
208 KITCHEN_FLR_6_WALL_EAST_WINDOW 0 194.63 217.46 19.20 0 3.05 28.65 8.58 0.30 2 No No
209 KITCHEN_FLR_6_WALL_1_SOUTH 0 506.51 211.91 19.20 0 3.05 28.65 8.58 0.30 3 No No
210 KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 28.65 8.58 0.30 2 No No
211 KITCHEN_FLR_6_WALL_2_SOUTH 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
212 KITCHEN_FLR_6_WALL_1_WEST 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
213 KITCHEN_FLR_6_WALL_2_WEST 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
214 KITCHEN_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
215 KITCHEN_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 28.65 8.58 0.30 0 No No
216 KITCHEN_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
217 CORRIDOR_FLR_6_WALL_1_NORTH 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 3 No No
218 CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 2 No No
219 CORRIDOR_FLR_6_WALL_2_NORTH 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 3 No No
220 CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 2 No No
221 CORRIDOR_FLR_6_WALL_2_SOUTH 0 506.51 211.91 19.20 0 3.05 28.04 8.72 0.33 3 No No
222 CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 28.04 8.72 0.33 2 No No
223 CORRIDOR_FLR_6_WALL_3_NORTH 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
224 CORRIDOR_FLR_6_WALL_4_NORTH 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
225 CORRIDOR_FLR_6_WALL_1_SOUTH 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
226 CORRIDOR_FLR_6_WALL_1_WEST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
227 CORRIDOR_FLR_6_WALL_2_WEST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
228 CORRIDOR_FLR_6_WALL_3_WEST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
229 CORRIDOR_FLR_6_WALL_1_EAST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
230 CORRIDOR_FLR_6_WALL_2_EAST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
231 CORRIDOR_FLR_6_WALL_3_EAST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
232 CORRIDOR_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
233 CORRIDOR_FLR_6_CEILING_1 0 1782.60 293.11 15.24 0 3.05 28.04 8.72 0.33 0 No No
234 CORRIDOR_FLR_6_CEILING_2 0 1782.60 293.11 15.24 0 3.05 28.04 8.72 0.33 0 No No
235 CORRIDOR_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 RETAIL_1_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH RETAIL_1_FLR_1 67.07 10.8 1.764E-002 2.631E-004 1.298E-004 0.239 1.000 0.000 0.000 0.000
2 RETAIL_2_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH RETAIL_2_FLR_1 77.67 12.5 6.811E-003 8.769E-005 2.388E-004 7.967E-002 1.000 0.000 0.000 0.000
3 MECH_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH MECH_FLR_1 164.24 2.7 1.610E-002 9.800E-005 2.563E-004 8.904E-002 1.000 0.000 0.000 0.000
4 STORAGE_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH STORAGE_FLR_1 94.76 2.0 9.287E-003 9.800E-005 2.127E-004 8.904E-002 1.000 0.000 0.000 0.000
5 LAUNDRY_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH LAUNDRY_FLR_1 78.04 8.4 2.198E-002 2.816E-004 2.506E-004 0.256 1.000 0.000 0.000 0.000
6 CAFE_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH CAFE_FLR_1 188.86 142.3 3.900E-002 2.065E-004 1.137E-004 0.188 1.000 0.000 0.000 0.000
7 LOBBY_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH LOBBY_FLR_1 1308.19 422.4 0.111 8.519E-005 1.629E-004 7.740E-002 1.000 0.000 0.000 0.000
8 ROOM_1_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_1_FLR_3 39.02 1.5 1.024E-002 2.624E-004 2.563E-004 0.310 1.000 0.000 0.000 0.000
9 ROOM_2_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_2_FLR_3 39.02 1.5 1.024E-002 2.624E-004 2.563E-004 0.310 1.000 0.000 0.000 0.000
10 ROOM_3_MULT19_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_3_MULT19_FLR_3 24.52 1.5 2.857E-003 1.165E-004 2.563E-004 0.138 1.000 0.000 0.000 0.000
11 ROOM_4_MULT19_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_4_MULT19_FLR_3 24.53 1.5 2.858E-003 1.165E-004 2.563E-004 0.138 1.000 0.000 0.000 0.000
12 ROOM_5_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_5_FLR_3 39.02 1.5 1.024E-002 2.624E-004 2.563E-004 0.310 1.000 0.000 0.000 0.000
13 ROOM_6_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_6_FLR_3 39.02 1.5 1.024E-002 2.624E-004 2.563E-004 0.310 1.000 0.000 0.000 0.000
14 CORRIDOR_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH CORRIDOR_FLR_3 389.40 21.0 1.238E-002 3.180E-005 2.563E-004 3.755E-002 1.000 0.000 0.000 0.000
15 ROOM_1_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_1_FLR_6 39.02 1.5 1.024E-002 2.624E-004 1.297E-004 0.310 1.000 0.000 0.000 0.000
16 ROOM_2_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_2_FLR_6 39.02 1.5 1.024E-002 2.624E-004 1.297E-004 0.310 1.000 0.000 0.000 0.000
17 ROOM_3_MULT9_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_3_MULT9_FLR_6 24.53 1.5 5.239E-003 2.136E-004 1.165E-004 0.252 1.000 0.000 0.000 0.000
18 BANQUET_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH BANQUET_FLR_6 331.66 249.9 2.500E-002 7.539E-005 5.825E-005 8.904E-002 1.000 0.000 0.000 0.000
19 DINING_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH DINING_FLR_6 331.66 249.9 2.500E-002 7.539E-005 5.825E-005 8.904E-002 1.000 0.000 0.000 0.000
20 KITCHEN_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH KITCHEN_FLR_6 103.30 22.2 2.238E-002 2.167E-004 1.174E-004 0.256 1.000 0.000 0.000 0.000
21 CORRIDOR_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH CORRIDOR_FLR_6 412.12 22.2 2.191E-002 5.316E-005 4.403E-005 6.278E-002 1.000 0.000 0.000 0.000


ZoneVentilation Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/person Area {m3/s-person} ACH - Air Changes per Hour Fan Type {Exhaust;Intake;Natural} Fan Pressure Rise {Pa} Fan Efficiency {} Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2} Minimum Indoor Temperature{C}/Schedule Maximum Indoor Temperature{C}/Schedule Delta Temperature{C}/Schedule Minimum Outdoor Temperature{C}/Schedule Maximum Outdoor Temperature{C}/Schedule Maximum WindSpeed{m/s}
1 ROOM_1_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_1_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
2 ROOM_2_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_2_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
3 ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_3_MULT19_FLR_3 24.52 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
4 ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_4_MULT19_FLR_3 24.53 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
5 ROOM_5_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_5_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
6 ROOM_6_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_6_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
7 ROOM_1_FLR_6 SLIDING DOOR VENTILATION Constant-0.0 ROOM_1_FLR_6 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
8 ROOM_2_FLR_6 SLIDING DOOR VENTILATION Constant-0.0 ROOM_2_FLR_6 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
9 ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION Constant-0.0 ROOM_3_MULT9_FLR_6 24.53 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 BASEMENT Mixing/Well-Stirred
2 RETAIL_1_FLR_1 Mixing/Well-Stirred
3 RETAIL_2_FLR_1 Mixing/Well-Stirred
4 MECH_FLR_1 Mixing/Well-Stirred
5 STORAGE_FLR_1 Mixing/Well-Stirred
6 LAUNDRY_FLR_1 Mixing/Well-Stirred
7 CAFE_FLR_1 Mixing/Well-Stirred
8 LOBBY_FLR_1 Mixing/Well-Stirred
9 ROOM_1_FLR_3 Mixing/Well-Stirred
10 ROOM_2_FLR_3 Mixing/Well-Stirred
11 ROOM_3_MULT19_FLR_3 Mixing/Well-Stirred
12 ROOM_4_MULT19_FLR_3 Mixing/Well-Stirred
13 ROOM_5_FLR_3 Mixing/Well-Stirred
14 ROOM_6_FLR_3 Mixing/Well-Stirred
15 CORRIDOR_FLR_3 Mixing/Well-Stirred
16 ROOM_1_FLR_6 Mixing/Well-Stirred
17 ROOM_2_FLR_6 Mixing/Well-Stirred
18 ROOM_3_MULT9_FLR_6 Mixing/Well-Stirred
19 BANQUET_FLR_6 Mixing/Well-Stirred
20 DINING_FLR_6 Mixing/Well-Stirred
21 KITCHEN_FLR_6 Mixing/Well-Stirred
22 CORRIDOR_FLR_6 Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Sky Daylight Factors

Sky Type MonthAndDay Daylighting Control Name Enclosure Name Window Name Reference Point Daylight Factor
1 Clear Sky 12/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 0.1490
2 Clear Sky 12/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 8.8401E-002
3 Clear Turbid Sky 12/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 0.1700
4 Clear Turbid Sky 12/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 0.1033
5 Intermediate Sky 12/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 9.9040E-002
6 Intermediate Sky 12/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 4.0567E-002
7 Overcast Sky 12/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 4.1657E-002
8 Overcast Sky 12/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 1.3839E-002
9 Clear Sky 12/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 0.1708
10 Clear Sky 12/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 0.1058
11 Clear Turbid Sky 12/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 0.1958
12 Clear Turbid Sky 12/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 0.1233
13 Intermediate Sky 12/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 0.1096
14 Intermediate Sky 12/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 5.0553E-002
15 Overcast Sky 12/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 4.6776E-002
16 Overcast Sky 12/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 1.8924E-002
17 Clear Sky 12/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 3.9132E-002
18 Clear Sky 12/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 2.2626E-002
19 Clear Turbid Sky 12/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 3.0128E-002
20 Clear Turbid Sky 12/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 1.7133E-002
21 Intermediate Sky 12/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 2.8567E-002
22 Intermediate Sky 12/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 1.1374E-002
23 Overcast Sky 12/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 4.1005E-002
24 Overcast Sky 12/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 1.4540E-002
25 Clear Sky 12/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 3.9132E-002
26 Clear Sky 12/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 2.2626E-002
27 Clear Turbid Sky 12/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 3.0128E-002
28 Clear Turbid Sky 12/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 1.7133E-002
29 Intermediate Sky 12/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 2.8567E-002
30 Intermediate Sky 12/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 1.1374E-002
31 Overcast Sky 12/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 4.1005E-002
32 Overcast Sky 12/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 1.4540E-002


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 BASEMENT Cooling 34561.46706 34561.46706 2.54748 2.54748 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 25.86400 8.81585E-003 1978.83018 106.49900 0.85446 0.00000
2 BASEMENT Heating 0.00000 0.00000 0.00000 0.85446 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -4.20000 2.69032E-003 1978.83018 106.49900 0.85446 0.00000
3 RETAIL_1_FLR_1 Cooling 6002.75136 6002.75136 0.44249 0.44249 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 13:20:00 29.05333 8.82094E-003 67.07136 10.82900 7.92179E-002 0.00000
4 RETAIL_1_FLR_1 Heating 2124.55339 2124.55339 9.23803E-002 9.23803E-002 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -4.20000 2.69032E-003 67.07136 10.82900 7.92179E-002 0.00000
5 RETAIL_2_FLR_1 Cooling 3147.79599 3147.79599 0.23205 0.23205 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:40:00 28.98400 8.82083E-003 77.66889 12.54000 9.17347E-002 0.00000
6 RETAIL_2_FLR_1 Heating 712.48325 712.48325 3.09808E-002 9.17347E-002 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -4.20000 2.69032E-003 77.66889 12.54000 9.17347E-002 0.00000
7 MECH_FLR_1 Cooling 2361.19338 2361.19338 0.17402 0.17402 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:40:00 28.98400 8.82083E-003 164.24319 2.65200 0.00000 0.00000
8 MECH_FLR_1 Heating 1267.24394 1267.24394 5.51033E-002 5.51033E-002 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -4.20000 2.69032E-003 164.24319 2.65200 0.00000 0.00000
9 STORAGE_FLR_1 Cooling 1403.26081 1403.26081 0.10342 0.10342 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 29.40000 8.82150E-003 94.75927 2.04000 5.77652E-002 0.00000
10 STORAGE_FLR_1 Heating 877.88084 877.88084 3.81727E-002 5.77652E-002 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -4.20000 2.69032E-003 94.75927 2.04000 5.77652E-002 0.00000
11 LAUNDRY_FLR_1 Cooling 44601.96818 44601.96818 3.28752 3.28752 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 29.40000 8.82150E-003 78.03947 8.40000 0.00000 0.00000
12 LAUNDRY_FLR_1 Heating 1678.32187 1678.32187 7.29771E-002 7.29771E-002 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -4.20000 2.69032E-003 78.03947 8.40000 0.00000 0.00000
13 CAFE_FLR_1 Cooling 23949.81398 23949.81398 1.76688 1.76688 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 13:20:00 29.05333 8.82094E-003 188.86188 142.30000 0.67639 0.00000
14 CAFE_FLR_1 Heating 5400.13062 5400.13062 0.23481 0.67639 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -4.20000 2.69032E-003 188.86188 142.30000 0.67639 0.00000
15 LOBBY_FLR_1 Cooling 69729.68513 69729.68513 5.14165 5.14165 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 13:40:00 29.22667 8.82122E-003 1308.18612 422.43500 1.89399 0.00000
16 LOBBY_FLR_1 Heating 12496.35959 12496.35959 0.54338 1.89399 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -4.20000 2.69032E-003 1308.18612 422.43500 1.89399 0.00000
17 ROOM_1_FLR_3 Cooling 11843.53612 11843.53612 1.17633 1.17633 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00 28.36000 8.81983E-003 39.02202 1.50000 6.17350E-002 0.00000
18 ROOM_1_FLR_3 Heating 4651.57260 4651.57260 0.20345 0.20345 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -4.20000 2.69032E-003 39.02202 1.50000 6.17350E-002 0.00000
19 ROOM_2_FLR_3 Cooling 10733.21187 10733.21187 1.06605 1.06605 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 16:50:00 28.08267 8.81938E-003 39.01745 1.50000 6.17278E-002 0.00000
20 ROOM_2_FLR_3 Heating 4654.84776 4654.84776 0.20359 0.20359 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -4.20000 2.69032E-003 39.01745 1.50000 6.17278E-002 0.00000
21 ROOM_3_MULT19_FLR_3 Cooling 83692.74210 83692.74210 8.31217 8.31217 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 29.14000 8.82108E-003 24.52384 1.50000 0.83707 0.00000
22 ROOM_3_MULT19_FLR_3 Heating 26893.56477 26893.56477 1.17628 1.17628 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -4.20000 2.69032E-003 24.52384 1.50000 0.83707 0.00000
23 ROOM_4_MULT19_FLR_3 Cooling 56028.34518 56028.34518 5.56504 5.56504 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 29.40000 8.82150E-003 24.53055 1.50000 0.83730 0.00000
24 ROOM_4_MULT19_FLR_3 Heating 26968.06721 26968.06721 1.17953 1.17953 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -4.20000 2.69032E-003 24.53055 1.50000 0.83730 0.00000
25 ROOM_5_FLR_3 Cooling 10693.38554 10693.38554 1.06209 1.06209 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 10:00:00 25.44800 8.81519E-003 39.02202 1.50000 6.17350E-002 0.00000
26 ROOM_5_FLR_3 Heating 4658.67236 4658.67236 0.20376 0.20376 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -4.20000 2.69032E-003 39.02202 1.50000 6.17350E-002 0.00000
27 ROOM_6_FLR_3 Cooling 9771.45290 9771.45290 0.97052 0.97052 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 09:00:00 23.68000 8.81240E-003 39.01745 1.50000 6.17278E-002 0.00000
28 ROOM_6_FLR_3 Heating 4661.94656 4661.94656 0.20390 0.20390 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -4.20000 2.69032E-003 39.01745 1.50000 6.17278E-002 0.00000
29 CORRIDOR_FLR_3 Cooling 21808.50071 21808.50071 1.60744 1.60744 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 29.40000 8.82150E-003 389.40468 20.95700 0.47476 0.00000
30 CORRIDOR_FLR_3 Heating 7581.23420 7581.23420 0.32966 0.47476 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -4.20000 2.69032E-003 389.40468 20.95700 0.47476 0.00000
31 ROOM_1_FLR_6 Cooling 3088.49743 3088.49743 0.30676 0.30676 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00 28.36000 8.81983E-003 39.02202 1.50000 1.54338E-002 0.00000
32 ROOM_1_FLR_6 Heating 1427.72104 1427.72104 6.24451E-002 6.24451E-002 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -4.20000 2.69032E-003 39.02202 1.50000 1.54338E-002 0.00000
33 ROOM_2_FLR_6 Cooling 2778.40158 2778.40158 0.27596 0.27596 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 27.94400 8.81916E-003 39.01745 1.50000 1.54319E-002 0.00000
34 ROOM_2_FLR_6 Heating 1429.37229 1429.37229 6.25173E-002 6.25173E-002 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -4.20000 2.69032E-003 39.01745 1.50000 1.54319E-002 0.00000
35 ROOM_3_MULT9_FLR_6 Cooling 16913.12864 16913.12864 1.67989 1.67989 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 13:40:00 29.22667 8.82122E-003 24.53055 1.50000 9.91540E-002 0.00000
36 ROOM_3_MULT9_FLR_6 Heating 6868.42325 6868.42325 0.30041 0.30041 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -4.20000 2.69032E-003 24.53055 1.50000 9.91540E-002 0.00000
37 BANQUET_FLR_6 Cooling 28690.49121 28690.49121 2.11732 2.11732 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 29.40000 8.82150E-003 331.65745 249.89600 1.18780 0.00000
38 BANQUET_FLR_6 Heating 4796.25938 4796.25938 0.20855 1.18780 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -4.20000 2.69032E-003 331.65745 249.89600 1.18780 0.00000
39 DINING_FLR_6 Cooling 30052.14742 30052.14742 2.21778 2.21778 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 29.40000 8.82150E-003 331.65745 249.89600 1.18780 0.00000
40 DINING_FLR_6 Heating 4901.05272 4901.05272 0.21311 1.18780 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 19:10:00 -4.20000 2.69032E-003 331.65745 249.89600 1.18780 0.00000
41 KITCHEN_FLR_6 Cooling 30735.29545 30735.29545 2.27133 2.27133 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 12:30:00 28.46400 8.82000E-003 103.30446 22.23800 0.36735 0.00000
42 KITCHEN_FLR_6 Heating 1026.39523 1026.39523 4.46249E-002 0.36735 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 23:30:00 -4.20000 2.69032E-003 103.30446 22.23800 0.36735 0.00000
43 CORRIDOR_FLR_6 Cooling 10909.82741 10909.82741 0.80412 0.80412 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 29.40000 8.82150E-003 412.12471 22.18000 0.12562 0.00000
44 CORRIDOR_FLR_6 Heating 5060.53477 5060.53477 0.22005 0.22005 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 19:10:00 -4.20000 2.69032E-003 412.12471 22.18000 0.12562 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 FLR_3_DOAS Cooling Sensible 40614.20 19.16137 2.05125 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 00:00:00
2 FLR_3_DOAS Heating Sensible 51134.75 3.59588 2.05125 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00
3 VAV WITH REHEAT Cooling Sensible 376643.77 22.59145 22.59145 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 00:00:00
4 VAV WITH REHEAT Heating Sensible 180294.09 7.23241 7.23241 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 19:30:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.54748
2 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.59191
3 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.51300
4 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.30686
5 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
6 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
7 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 6.43684E-004
8 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 5.95048E-005
9 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.30686
10 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
11 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
12 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size Rated Capacity [W] 6801.76349
13 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 5.95048E-005
14 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 141.83905
15 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.44249
16 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.11550
17 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.51300
18 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.22700
19 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.51300
20 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
21 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.29868E-003
22 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.89169E-005
23 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.22700
24 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
25 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
26 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 3305.37991
27 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.89169E-005
28 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 76.09021
29 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.23205
30 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.25505
31 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.51300
32 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.11904
33 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.68014
34 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
35 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.49382E-003
36 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.16503E-005
37 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.11904
38 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
39 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
40 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1331.69539
41 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.16503E-005
42 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 29.53949
43 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.17402
44 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.71918
45 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.51300
46 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 8.92735E-002
47 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
48 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
49 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 5.29771E-004
50 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.51483E-005
51 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 8.92735E-002
52 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
53 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
54 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1731.54259
55 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.51483E-005
56 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 42.16644
57 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.10342
58 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.69817
59 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.51300
60 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 5.30558E-002
61 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
62 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
63 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 5.45713E-004
64 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.00944E-005
65 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 5.30558E-002
66 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
67 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
68 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1153.84735
69 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.00944E-005
70 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 28.92258
71 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 3.28752
72 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 1.80884E-002
73 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.51300
74 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.68650
75 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.51300
76 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
77 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.10632E-002
78 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.14128E-005
79 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.68650
80 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
81 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
82 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 10449.05013
83 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.14128E-005
84 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 220.07044
85 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.76688
86 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 8.14501E-002
87 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.51300
88 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.90641
89 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.51300
90 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
91 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 4.67771E-003
92 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 8.84950E-005
93 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.90641
94 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
95 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
96 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 10115.52116
97 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 8.84950E-005
98 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 224.31602
99 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 5.14165
100 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.19388
101 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.51300
102 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.63767
103 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.51700
104 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
105 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.96518E-003
106 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.29360E-004
107 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.63767
108 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
109 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
110 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 26217.26750
111 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.29360E-004
112 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 573.92818
113 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_1_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17350E-002
114 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.17633
115 Fan:OnOff ROOM_1_FLR_3 FAN COIL_FANCOILFAN Design Size Maximum Flow Rate [m3/s] 1.17633
116 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 4.06935E-005
117 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 3.69063E-004
118 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69135
119 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
120 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.56579E-003
121 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
122 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
123 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 3.69063E-004
124 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.17633
125 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 4651.51968
126 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 4.06935E-005
127 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 132.91021
128 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_2_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17278E-002
129 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.06605
130 Fan:OnOff ROOM_2_FLR_3 FAN COIL_FANCOILFAN Design Size Maximum Flow Rate [m3/s] 1.06605
131 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 4.07222E-005
132 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 3.35067E-004
133 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69134
134 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
135 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.57235E-003
136 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
137 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
138 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 3.35067E-004
139 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.06605
140 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 4654.79481
141 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 4.07222E-005
142 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 133.00378
143 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_3_MULT19_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.83707
144 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT19_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 8.31217
145 Fan:OnOff ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN Design Size Maximum Flow Rate [m3/s] 8.31217
146 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT19_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 2.35275E-004
147 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT19_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 2.56225E-003
148 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69179
149 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
150 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.50199E-003
151 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
152 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
153 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 2.56225E-003
154 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 8.31217
155 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 26893.41674
156 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.35275E-004
157 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 768.43062
158 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_4_MULT19_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.83730
159 ZoneHVAC:FourPipeFanCoil ROOM_4_MULT19_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 5.56504
160 Fan:OnOff ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN Design Size Maximum Flow Rate [m3/s] 5.56504
161 ZoneHVAC:FourPipeFanCoil ROOM_4_MULT19_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 2.35927E-004
162 ZoneHVAC:FourPipeFanCoil ROOM_4_MULT19_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 1.83786E-003
163 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69087
164 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
165 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.75736E-003
166 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
167 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
168 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.83786E-003
169 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 5.56504
170 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 26967.91880
171 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.35927E-004
172 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 770.55911
173 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_5_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17350E-002
174 ZoneHVAC:FourPipeFanCoil ROOM_5_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.06209
175 Fan:OnOff ROOM_5_FLR_3 FAN COIL_FANCOILFAN Design Size Maximum Flow Rate [m3/s] 1.06209
176 ZoneHVAC:FourPipeFanCoil ROOM_5_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 4.07556E-005
177 ZoneHVAC:FourPipeFanCoil ROOM_5_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 3.33881E-004
178 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69134
179 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
180 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.57298E-003
181 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
182 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
183 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 3.33881E-004
184 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.06209
185 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 4658.61937
186 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 4.07556E-005
187 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 133.11304
188 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_6_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17278E-002
189 ZoneHVAC:FourPipeFanCoil ROOM_6_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.97052
190 Fan:OnOff ROOM_6_FLR_3 FAN COIL_FANCOILFAN Design Size Maximum Flow Rate [m3/s] 0.97052
191 ZoneHVAC:FourPipeFanCoil ROOM_6_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 4.07843E-005
192 ZoneHVAC:FourPipeFanCoil ROOM_6_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 3.05665E-004
193 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69133
194 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
195 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.57979E-003
196 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
197 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
198 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 3.05665E-004
199 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.97052
200 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 4661.89354
201 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 4.07843E-005
202 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 133.20658
203 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.60744
204 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.73838
205 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.51300
206 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.82461
207 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
208 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
209 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 5.15992E-004
210 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.03856E-004
211 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.82461
212 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
213 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
214 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 11871.41494
215 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.03856E-004
216 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 272.77522
217 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_1_FLR_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 1.54338E-002
218 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_6 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.30676
219 Fan:OnOff ROOM_1_FLR_6 FAN COIL_FANCOILFAN Design Size Maximum Flow Rate [m3/s] 0.30676
220 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_6 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 1.24902E-005
221 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_6 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 9.61715E-005
222 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69136
223 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
224 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.56311E-003
225 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
226 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
227 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 9.61715E-005
228 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.30676
229 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL Design Size Rated Capacity [W] 1427.70541
230 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.24902E-005
231 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 40.79337
232 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_2_FLR_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 1.54319E-002
233 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_6 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.27596
234 Fan:OnOff ROOM_2_FLR_6 FAN COIL_FANCOILFAN Design Size Maximum Flow Rate [m3/s] 0.27596
235 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_6 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 1.25046E-005
236 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_6 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 8.66871E-005
237 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69135
238 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
239 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.57032E-003
240 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
241 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
242 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 8.66871E-005
243 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.27596
244 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL Design Size Rated Capacity [W] 1429.35664
245 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.25046E-005
246 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 40.84055
247 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_3_MULT9_FLR_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 9.91540E-002
248 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT9_FLR_6 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.67989
249 Fan:OnOff ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN Design Size Maximum Flow Rate [m3/s] 1.67989
250 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT9_FLR_6 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 6.00874E-005
251 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT9_FLR_6 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 5.32302E-004
252 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69112
253 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
254 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.60211E-003
255 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
256 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
257 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 5.32302E-004
258 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.67989
259 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Design Size Rated Capacity [W] 6868.36292
260 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 6.00874E-005
261 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 196.24659
262 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.11732
263 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.11936
264 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.51300
265 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.08619
266 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.51300
267 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
268 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.19203E-003
269 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.14007E-005
270 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.08619
271 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
272 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
273 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 10447.65910
274 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.14007E-005
275 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 227.93863
276 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.21778
277 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.11395
278 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.51300
279 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.13772
280 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.51300
281 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
282 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.34348E-003
283 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.46622E-005
284 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.13772
285 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
286 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
287 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 10820.47004
288 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.46622E-005
289 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 235.80412
290 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.27133
291 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 6.23354E-002
292 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.51300
293 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.16519
294 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.51300
295 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
296 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.09934E-002
297 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 6.17429E-005
298 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.16519
299 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
300 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
301 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 7057.59388
302 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 6.17429E-005
303 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 148.43458
304 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.80412
305 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.39054
306 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.51300
307 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.41252
308 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
309 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
310 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 9.75582E-004
311 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 6.30493E-005
312 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.41252
313 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
314 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
315 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 7206.92457
316 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 6.30493E-005
317 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 171.54597
318 AirLoopHVAC FLR_3_DOAS Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 2.05132
319 AirLoopHVAC FLR_3_DOAS Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 2.05132
320 AirLoopHVAC FLR_3_DOAS Sum of Air Terminal Maximum Flow Rates [m3/s] 2.05132
321 AirLoopHVAC FLR_3_DOAS Adjusted Heating Design Air Flow Rate [m3/s] 2.05132
322 AirLoopHVAC FLR_3_DOAS Adjusted Cooling Design Air Flow Rate [m3/s] 2.05132
323 AirLoopHVAC FLR_3_DOAS Adjusted Main Design Air Flow Rate [m3/s] 2.05132
324 AirLoopHVAC FLR_3_DOAS User Heating Air Flow Ratio [] 0.30000
325 AirLoopHVAC FLR_3_DOAS Calculated Heating Air Flow Ratio [] 1.00000
326 AirLoopHVAC VAV WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 11.65203
327 AirLoopHVAC VAV WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 11.65203
328 AirLoopHVAC VAV WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 22.71351
329 AirLoopHVAC VAV WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 11.65203
330 AirLoopHVAC VAV WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 22.59145
331 AirLoopHVAC VAV WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 22.59145
332 AirLoopHVAC VAV WITH REHEAT User Heating Air Flow Ratio [] 0.30000
333 AirLoopHVAC VAV WITH REHEAT Calculated Heating Air Flow Ratio [] 0.51577
334 AirLoopHVAC FLR_3_DOAS Design Supply Air Flow Rate [m3/s] 2.05132
335 AirLoopHVAC VAV WITH REHEAT Design Supply Air Flow Rate [m3/s] 22.59145
336 Controller:OutdoorAir FLR_3_DOAS_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 2.05132
337 Controller:OutdoorAir FLR_3_DOAS_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 2.05125
338 HeatExchanger:AirToAir:SensibleAndLatent FLR_3_DOAS OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 2.05125
339 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Inlet Air Temperature [C] 29.40000
340 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
341 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Outlet Air Temperature [C] 11.91727
342 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.82150E-003
343 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
344 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Coil Load [W] 45447.83718
345 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.29980E-003
346 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Air Flow Rate [m3/s] 2.05132
347 Coil:Heating:Water FLR_3_DOAS HEATING COIL Design Size Rated Capacity [W] 15340.96456
348 Coil:Heating:Water FLR_3_DOAS HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.34209E-004
349 Coil:Heating:Water FLR_3_DOAS HEATING COIL Design Size U-Factor Times Area Value [W/K] 261.90442
350 Fan:ConstantVolume FLR_3_DOAS FAN User-Specified Maximum Flow Rate [m3/s] 2.05125
351 Controller:WaterCoil FLR_3_DOAS_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 1.29980E-003
352 Controller:WaterCoil FLR_3_DOAS_COOLC_CONTROLLER Controller Convergence Tolerance 3.66356E-004
353 Controller:WaterCoil FLR_3_DOAS_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 1.34209E-004
354 Controller:OutdoorAir VAV WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 22.59145
355 HeatExchanger:AirToAir:SensibleAndLatent VAV WITH REHEAT OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 11.66146
356 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 26.78336
357 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
358 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 10.95289
359 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 9.20731E-003
360 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
361 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 481649.26568
362 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.37751E-002
363 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 22.59145
364 Coil:Heating:Water VAV WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 168952.24094
365 Coil:Heating:Water VAV WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.47807E-003
366 Coil:Heating:Water VAV WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 2884.39088
367 Fan:VariableVolume VAV WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 22.59145
368 Controller:WaterCoil VAV WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 1.37751E-002
369 Controller:WaterCoil VAV WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 3.45689E-005
370 Controller:WaterCoil VAV WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 1.47807E-003
371 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Flow Rate [m3/s] 2.15339E-002
372 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Power Consumption [W] 3515.82228
373 PlantLoop HEATSYS1 Maximum Loop Flow Rate [m3/s] 3.28081E-003
374 PlantLoop HEATSYS1 Plant Loop Volume [m3] 0.39370
375 Pump:VariableSpeed HEATSYS1 PUMP Design Flow Rate [m3/s] 3.28081E-003
376 Pump:VariableSpeed HEATSYS1 PUMP Design Power Consumption [W] 988.03639
377 Pump:VariableSpeed HEATSYS1 PUMP Design Minimum Flow Rate [m3/s] 0.00000
378 Boiler:HotWater HEATSYS1 BOILER Design Size Nominal Capacity [W] 375016.92346
379 Boiler:HotWater HEATSYS1 BOILER User-Specified Nominal Capacity [W] 375016.92000
380 Boiler:HotWater HEATSYS1 BOILER Design Size Design Water Flow Rate [m3/s] 3.28081E-003
381 PlantLoop COOLSYS1 Maximum Loop Flow Rate [m3/s] 2.15339E-002
382 PlantLoop COOLSYS1 Plant Loop Volume [m3] 2.58406
383 Pump:ConstantSpeed COOLSYS1 PUMP Design Flow Rate [m3/s] 2.15339E-002
384 Pump:ConstantSpeed COOLSYS1 PUMP Design Power Consumption [W] 2434.12235
385 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Chilled Water Flow Rate [m3/s] 2.15339E-002
386 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Capacity [W] 752935.70441
387 Chiller:Electric:EIR COOLSYS1 CHILLER1 User-Specified Reference Capacity [W] 753560.40000
388 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Condenser Fluid Flow Rate [m3/s] 85.90589
389 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 3.75036E-004
390 PlantLoop SWHSYS1 Plant Loop Volume [m3] 4.50044E-002
391 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 3.75036E-004
392 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 47.90688
393 WaterHeater:Mixed SWHSYS1 WATER HEATER Use Side Design Flow Rate [m3/s] 3.75036E-004


Water Heating Coil Capacity Information

Component Type Name Nominal Total Capacity {W}
1 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL 6836.93
2 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL 3320.71
3 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL 1338.11
4 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL 1739.03
5 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL 1158.69
6 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL 10502.58
7 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL 10164.23
8 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL 26347.03
9 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL 5009.85
10 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL 5013.38
11 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL 28965.01
12 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL 29045.25
13 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL 5017.50
14 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL 5021.02
15 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL 11926.58
16 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL 1537.66
17 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL 1539.44
18 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL 7397.33
19 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL 10499.52
20 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL 10874.23
21 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL 7093.79
22 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL 7239.34
23 Coil:Heating:Water FLR_3_DOAS HEATING COIL 11685.10
24 Coil:Heating:Water VAV WITH REHEAT HEATING COIL 128689.70


Water Cooling Coil Capacity Information

Component Type Name Nominal Total Capacity {W} Nominal Sensible Capacity {W} Nominal Latent Capacity {W} Nominal Sensible Heat Ratio Nominal Coil UA Value {W/C} Nominal Coil Surface Area {m2}
1 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL 19173.09 16554.96 2618.14 0.86 3802.76 38.57
2 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL 17397.01 15010.27 2386.74 0.86 3444.30 34.93
3 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL 133833.60 116412.11 17421.49 0.87 27003.90 273.89
4 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL 93929.54 79454.82 14474.72 0.85 17795.61 180.49
5 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL 17334.49 14955.26 2379.23 0.86 3431.33 34.80
6 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL 15860.14 13672.81 2187.33 0.86 3133.69 31.78
7 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL 4997.35 4316.26 681.09 0.86 991.90 10.06
8 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL 4501.68 3884.97 616.71 0.86 891.75 9.04
9 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL 27566.19 23705.54 3860.65 0.86 5414.39 54.92
10 Coil:Cooling:Water FLR_3_DOAS COOLING COIL 49570.73 35167.84 14402.90 0.71 6912.11 70.11
11 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL 559090.64 394703.21 164387.43 0.71 88515.67 897.78


Chiller Standard Rating Information

Component Type Component Name IPLV in SI Units {W/W} IPLV in IP Units {Btu/W-h}
1 Chiller:Electric:EIR COOLSYS1 CHILLER1 4.09 13.95


Zone Surfaces

Zone Name # Surfaces
1 BASEMENT 14
2 RETAIL_1_FLR_1 8
3 RETAIL_2_FLR_1 8
4 MECH_FLR_1 7
5 STORAGE_FLR_1 8
6 LAUNDRY_FLR_1 8
7 CAFE_FLR_1 10
8 LOBBY_FLR_1 22
9 ROOM_1_FLR_3 9
10 ROOM_2_FLR_3 9
11 ROOM_3_MULT19_FLR_3 8
12 ROOM_4_MULT19_FLR_3 8
13 ROOM_5_FLR_3 9
14 ROOM_6_FLR_3 9
15 CORRIDOR_FLR_3 25
16 ROOM_1_FLR_6 9
17 ROOM_2_FLR_6 9
18 ROOM_3_MULT9_FLR_6 8
19 BANQUET_FLR_6 8
20 DINING_FLR_6 8
21 KITCHEN_FLR_6 12
22 CORRIDOR_FLR_6 19


HeatTransfer Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Construction Nominal U (w/o film coefs) {W/m2-K} Nominal U (with film coefs) {W/m2-K} Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m} ExtBoundCondition ExtConvCoeffCalc IntConvCoeffCalc SunExposure WindExposure ViewFactorToGround ViewFactorToSky ViewFactorToGround-IR ViewFactorToSky-IR #Sides
1 BASEMENT_WALL_NORTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_NORTH_CFACTOR 0.419 0.394   211.13 211.13 211.13 0.00 90.00 86.56 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
2 BASEMENT_WALL_EAST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_EAST_CFACTOR 0.419 0.394   55.76 55.76 55.76 90.00 90.00 22.86 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
3 BASEMENT_WALL_SOUTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_SOUTH_CFACTOR 0.419 0.394   211.13 211.13 211.13 180.00 90.00 86.56 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
4 BASEMENT_WALL_WEST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_WEST_CFACTOR 0.419 0.394   55.76 55.76 55.76 270.00 90.00 22.86 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
5 BASEMENT_FLOOR Floor   CTF - ConductionTransferFunction BASEMENT_FLOOR 2.705 1.632   1978.83 1978.83 1978.83 0.00 180.00 86.56 22.86 0.00 BASEMENT_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
6 BASEMENT_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.228 0.218   67.07 67.07 67.07 180.00 0.00 11.58 5.79 0.00 RETAIL_1_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
7 BASEMENT_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.228 0.218   77.67 77.67 77.67 180.00 0.00 11.58 6.71 0.00 RETAIL_2_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
8 BASEMENT_CEILING_3 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.228 0.218   164.24 164.24 164.24 180.00 0.00 15.85 10.36 0.00 MECH_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
9 BASEMENT_CEILING_4 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.228 0.218   94.76 94.76 94.76 180.00 0.00 9.14 10.36 0.00 STORAGE_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
10 BASEMENT_CEILING_5 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.228 0.218   78.04 78.04 78.04 180.00 0.00 4.57 17.07 0.00 LAUNDRY_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
11 BASEMENT_CEILING_6 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.228 0.218   188.86 188.86 188.86 180.00 0.00 32.61 5.79 0.00 CAFE_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
12 BASEMENT_CEILING_7 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.228 0.218   1088.56 1088.56 1088.56 180.00 0.00 32.99 32.99 0.00 LOBBY_FLR_1_FLOOR_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
13 BASEMENT_CEILING_8 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.228 0.218   219.63 219.63 219.63 90.00 0.00 14.82 14.82 0.00 LOBBY_FLR_1_FLOOR_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
14 BASEMENT_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   3957.66 3957.66 3957.66 0.00 90.00 3957.66 1.00 0.00 BASEMENT_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
15 RETAIL_1_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.820 0.731   22.63 45.89 22.63 180.00 90.00 11.58 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
16 RETAIL_1_FLR_1_WALL_SOUTH_WINDOW Window RETAIL_1_FLR_1_WALL_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.38_SHGC_0.36 N/A 2.159 No 23.26 23.26 23.26 180.00 90.00 10.92 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
17 RETAIL_1_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.820 0.731   22.95 22.95 22.95 270.00 90.00 5.79 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
18 RETAIL_1_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 0.00 90.00 11.58 3.96 0.00 RETAIL_2_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
19 RETAIL_1_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 90.00 90.00 5.79 3.96 0.00 LOBBY_FLR_1_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
20 RETAIL_1_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.228 0.216   67.07 67.07 67.07 0.00 180.00 11.58 5.79 0.00 BASEMENT_CEILING_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
21 RETAIL_1_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   67.07 67.07 67.07 180.00 0.00 11.58 5.79 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 7.62E-002 0.92 4
22 RETAIL_1_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   134.14 134.14 134.14 0.00 90.00 134.14 1.00 0.00 RETAIL_1_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
23 RETAIL_2_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.820 0.731   24.62 26.57 24.62 270.00 90.00 6.71 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
24 RETAIL_2_FLR_1_WALL_WEST_DOOR Door RETAIL_2_FLR_1_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
25 RETAIL_2_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 180.00 90.00 11.58 3.96 0.00 RETAIL_1_FLR_1_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
26 RETAIL_2_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 0.00 90.00 11.58 3.96 0.00 LOBBY_FLR_1_WALL_2_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
27 RETAIL_2_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.57 26.57 26.57 90.00 90.00 6.71 3.96 0.00 LOBBY_FLR_1_WALL_3_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
28 RETAIL_2_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.228 0.216   77.67 77.67 77.67 0.00 180.00 11.58 6.71 0.00 BASEMENT_CEILING_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
29 RETAIL_2_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.228 0.218   77.67 77.67 77.67 180.00 0.00 11.58 6.71 0.00 RETAIL_2_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
30 RETAIL_2_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   155.34 155.34 155.34 0.00 90.00 155.34 1.00 0.00 RETAIL_2_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
31 MECH_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.820 0.731   62.80 62.80 62.80 0.00 90.00 15.85 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
32 MECH_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 90.00 90.00 10.36 3.96 0.00 STORAGE_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
33 MECH_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   62.80 62.80 62.80 180.00 90.00 15.85 3.96 0.00 LOBBY_FLR_1_WALL_3_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
34 MECH_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 LOBBY_FLR_1_WALL_1_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
35 MECH_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.228 0.216   164.24 164.24 164.24 0.00 180.00 15.85 10.36 0.00 BASEMENT_CEILING_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
36 MECH_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.228 0.218   164.24 164.24 164.24 180.00 0.00 15.85 10.36 0.00 MECH_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
37 MECH_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   328.49 328.49 328.49 0.00 90.00 328.49 1.00 0.00 MECH_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
38 STORAGE_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.820 0.731   28.80 36.23 28.80 0.00 90.00 9.14 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
39 STORAGE_FLR_1_WALL_NORTH_ROLLDOOR Door STORAGE_FLR_1_WALL_NORTH CTF - ConductionTransferFunction OVERHEAD DOOR_CON 2.390 2.390   7.43 7.43 7.43 0.00 90.00 3.05 2.44 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
40 STORAGE_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 90.00 90.00 10.36 3.96 0.00 LOBBY_FLR_1_WALL_4_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
41 STORAGE_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.23 36.23 36.23 180.00 90.00 9.14 3.96 0.00 LOBBY_FLR_1_WALL_4_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
42 STORAGE_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 MECH_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
43 STORAGE_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.228 0.216   94.76 94.76 94.76 0.00 180.00 9.14 10.36 0.00 BASEMENT_CEILING_4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
44 STORAGE_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.228 0.218   94.76 94.76 94.76 180.00 0.00 9.14 10.36 0.00 STORAGE_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
45 STORAGE_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   189.52 189.52 189.52 0.00 90.00 189.52 1.00 0.00 STORAGE_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
46 LAUNDRY_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.820 0.731   18.12 18.12 18.12 0.00 90.00 4.57 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
47 LAUNDRY_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.820 0.731   65.68 67.63 65.68 90.00 90.00 17.07 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
48 LAUNDRY_FLR_1_WALL_EAST_DOOR Door LAUNDRY_FLR_1_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
49 LAUNDRY_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.12 18.12 18.12 180.00 90.00 4.57 3.96 0.00 CAFE_FLR_1_WALL_2_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
50 LAUNDRY_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   67.63 67.63 67.63 270.00 90.00 17.07 3.96 0.00 LOBBY_FLR_1_WALL_3_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
51 LAUNDRY_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.228 0.216   78.04 78.04 78.04 0.00 180.00 4.57 17.07 0.00 BASEMENT_CEILING_5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
52 LAUNDRY_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.228 0.218   78.04 78.04 78.04 180.00 0.00 4.57 17.07 0.00 LAUNDRY_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
53 LAUNDRY_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   156.08 156.08 156.08 0.00 90.00 156.08 1.00 0.00 LAUNDRY_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
54 CAFE_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.820 0.731   21.00 22.95 21.00 90.00 90.00 5.79 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
55 CAFE_FLR_1_WALL_EAST_DOOR Door CAFE_FLR_1_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
56 CAFE_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.820 0.731   63.73 129.23 63.73 180.00 90.00 32.61 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
57 CAFE_FLR_1_WALL_SOUTH_WINDOW Window CAFE_FLR_1_WALL_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.38_SHGC_0.36 N/A 2.159 No 65.50 65.50 65.50 180.00 90.00 30.75 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
58 CAFE_FLR_1_WALL_1_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.11 111.11 111.11 0.00 90.00 28.04 3.96 0.00 LOBBY_FLR_1_WALL_3_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
59 CAFE_FLR_1_WALL_2_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.12 18.12 18.12 0.00 90.00 4.57 3.96 0.00 LAUNDRY_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
60 CAFE_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 270.00 90.00 5.79 3.96 0.00 LOBBY_FLR_1_WALL_2_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
61 CAFE_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.228 0.216   188.86 188.86 188.86 0.00 180.00 32.61 5.79 0.00 BASEMENT_CEILING_6 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
62 CAFE_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   188.86 188.86 188.86 180.00 0.00 32.61 5.79 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 3.86E-002 0.96 4
63 CAFE_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   377.72 377.72 377.72 0.00 90.00 377.72 1.00 0.00 CAFE_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
64 LOBBY_FLR_1_WALL_1_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.820 0.731   209.87 213.77 209.87 0.00 90.00 53.95 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
65 LOBBY_FLR_1_WALL_1_NORTH_DOOR1 Door LOBBY_FLR_1_WALL_1_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
66 LOBBY_FLR_1_WALL_1_NORTH_DOOR2 Door LOBBY_FLR_1_WALL_1_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
67 LOBBY_FLR_1_WALL_2_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.820 0.731   12.08 12.08 12.08 0.00 90.00 3.05 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
68 LOBBY_FLR_1_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.820 0.731   82.79 167.88 82.79 180.00 90.00 42.37 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
69 LOBBY_FLR_1_WALL_SOUTH_WINDOW Window LOBBY_FLR_1_WALL_1_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.38_SHGC_0.36 N/A 2.159 No 85.08 85.08 85.08 180.00 90.00 39.95 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
70 LOBBY_FLR_1_WALL_1_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.820 0.731   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
71 LOBBY_FLR_1_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 180.00 90.00 11.58 3.96 0.00 RETAIL_2_FLR_1_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
72 LOBBY_FLR_1_WALL_3_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.11 111.11 111.11 180.00 90.00 28.04 3.96 0.00 CAFE_FLR_1_WALL_1_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
73 LOBBY_FLR_1_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 270.00 90.00 5.79 3.96 0.00 RETAIL_1_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
74 LOBBY_FLR_1_WALL_3_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.57 26.57 26.57 270.00 90.00 6.71 3.96 0.00 RETAIL_2_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
75 LOBBY_FLR_1_WALL_4_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 STORAGE_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
76 LOBBY_FLR_1_WALL_3_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   62.80 62.80 62.80 0.00 90.00 15.85 3.96 0.00 MECH_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
77 LOBBY_FLR_1_WALL_4_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.23 36.23 36.23 0.00 90.00 9.14 3.96 0.00 STORAGE_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
78 LOBBY_FLR_1_WALL_1_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 90.00 90.00 10.36 3.96 0.00 MECH_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
79 LOBBY_FLR_1_WALL_2_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 90.00 90.00 5.79 3.96 0.00 CAFE_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
80 LOBBY_FLR_1_WALL_3_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   67.63 67.63 67.63 90.00 90.00 17.07 3.96 0.00 LAUNDRY_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
81 LOBBY_FLR_1_FLOOR_1 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.228 0.216   1088.56 1088.56 1088.56 180.00 180.00 32.99 32.99 0.00 BASEMENT_CEILING_7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
82 LOBBY_FLR_1_FLOOR_2 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.228 0.216   219.63 219.63 219.63 90.00 180.00 14.82 14.82 0.00 BASEMENT_CEILING_8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
83 LOBBY_FLR_1_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.228 0.218   1062.83 1062.83 1062.83 270.00 0.00 32.60 32.60 0.00 LOBBY_FLR_1_CEILING_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 10
84 LOBBY_FLR_1_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   245.35 245.35 245.35 180.00 0.00 42.37 5.79 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 4.22E-003 1.00 4
85 LOBBY_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   2616.37 2616.37 2616.37 0.00 90.00 2616.37 1.00 0.00 LOBBY_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
86 ROOM_1_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.917 0.806   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
87 ROOM_1_FLR_3_WALL_SOUTH_WINDOW Window ROOM_1_FLR_3_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.38_SHGC_0.36 N/A 2.159 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
88 ROOM_1_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.917 0.806   17.43 26.01 17.43 270.00 90.00 8.54 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
89 ROOM_1_FLR_3_WALL_WEST_WINDOW Window ROOM_1_FLR_3_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.38_SHGC_0.36 N/A 2.159 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
90 ROOM_1_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ROOM_2_FLR_3_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
91 ROOM_1_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.54 3.05 0.00 CORRIDOR_FLR_3_WALL_3_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
92 ROOM_1_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.228 0.216   39.02 39.02 39.02 0.00 180.00 4.57 8.54 0.00 ROOM_1_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
93 ROOM_1_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.228 0.218   39.02 39.02 39.02 180.00 0.00 4.57 8.54 0.00 ROOM_1_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
94 ROOM_1_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 ROOM_1_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
95 ROOM_2_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.917 0.806   9.34 13.94 9.34 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
96 ROOM_2_FLR_3_WALL_NORTH_WINDOW Window ROOM_2_FLR_3_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.38_SHGC_0.36 N/A 2.159 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
97 ROOM_2_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.917 0.806   17.43 26.01 17.43 270.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
98 ROOM_2_FLR_3_WALL_WEST_WINDOW Window ROOM_2_FLR_3_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.38_SHGC_0.36 N/A 2.159 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
99 ROOM_2_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.53 3.05 0.00 CORRIDOR_FLR_3_WALL_4_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
100 ROOM_2_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ROOM_1_FLR_3_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
101 ROOM_2_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.228 0.216   39.02 39.02 39.02 0.00 180.00 4.57 8.53 0.00 ROOM_2_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
102 ROOM_2_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.228 0.218   39.02 39.02 39.02 180.00 0.00 4.57 8.53 0.00 ROOM_2_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
103 ROOM_2_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.03 78.03 78.03 0.00 90.00 78.03 1.00 0.00 ROOM_2_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
104 ROOM_3_MULT19_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.917 0.806   7.47 11.15 7.47 180.00 90.00 3.66 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
105 ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW Window ROOM_3_MULT19_FLR_3_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.38_SHGC_0.36 N/A 2.159 No 3.68 3.68 3.68 180.00 90.00 3.02 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
106 ROOM_3_MULT19_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 0.00 90.00 3.66 3.05 0.00 ROOM_3_MULT19_FLR_3_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
107 ROOM_3_MULT19_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 ROOM_3_MULT19_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
108 ROOM_3_MULT19_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 ROOM_3_MULT19_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
109 ROOM_3_MULT19_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.228 0.216   24.52 24.52 24.52 0.00 180.00 3.66 6.71 0.00 ROOM_3_MULT19_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
110 ROOM_3_MULT19_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.228 0.218   24.52 24.52 24.52 180.00 0.00 3.66 6.71 0.00 ROOM_3_MULT19_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
111 ROOM_3_MULT19_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   49.05 49.05 49.05 0.00 90.00 49.05 1.00 0.00 ROOM_3_MULT19_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
112 ROOM_4_MULT19_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.917 0.806   7.47 11.15 7.47 0.00 90.00 3.66 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
113 ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW Window ROOM_4_MULT19_FLR_3_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.38_SHGC_0.36 N/A 2.159 No 3.68 3.68 3.68 0.00 90.00 3.02 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
114 ROOM_4_MULT19_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 ROOM_4_MULT19_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
115 ROOM_4_MULT19_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 180.00 90.00 3.66 3.05 0.00 ROOM_4_MULT19_FLR_3_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
116 ROOM_4_MULT19_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 ROOM_4_MULT19_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
117 ROOM_4_MULT19_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.228 0.216   24.53 24.53 24.53 0.00 180.00 3.66 6.71 0.00 ROOM_4_MULT19_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
118 ROOM_4_MULT19_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.228 0.218   24.53 24.53 24.53 180.00 0.00 3.66 6.71 0.00 ROOM_4_MULT19_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
119 ROOM_4_MULT19_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   49.06 49.06 49.06 0.00 90.00 49.06 1.00 0.00 ROOM_4_MULT19_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
120 ROOM_5_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.917 0.806   17.43 26.01 17.43 90.00 90.00 8.54 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
121 ROOM_5_FLR_3_WALL_EAST_WINDOW Window ROOM_5_FLR_3_WALL_EAST Window5 Detailed Fenestration RESWINDOW_U_0.38_SHGC_0.36 N/A 2.159 No 8.58 8.58 8.58 90.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
122 ROOM_5_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.917 0.806   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
123 ROOM_5_FLR_3_WALL_SOUTH_WINDOW Window ROOM_5_FLR_3_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.38_SHGC_0.36 N/A 2.159 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
124 ROOM_5_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ROOM_6_FLR_3_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
125 ROOM_5_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.54 3.05 0.00 CORRIDOR_FLR_3_WALL_3_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
126 ROOM_5_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.228 0.216   39.02 39.02 39.02 0.00 180.00 4.57 8.54 0.00 ROOM_5_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
127 ROOM_5_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.228 0.218   39.02 39.02 39.02 180.00 0.00 4.57 8.54 0.00 ROOM_5_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
128 ROOM_5_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 ROOM_5_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
129 ROOM_6_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.917 0.806   9.34 13.94 9.34 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
130 ROOM_6_FLR_3_WALL_NORTH_WINDOW Window ROOM_6_FLR_3_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.38_SHGC_0.36 N/A 2.159 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
131 ROOM_6_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.917 0.806   17.43 26.01 17.43 90.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
132 ROOM_6_FLR_3_WALL_EAST_WINDOW Window ROOM_6_FLR_3_WALL_EAST Window5 Detailed Fenestration RESWINDOW_U_0.38_SHGC_0.36 N/A 2.159 No 8.58 8.58 8.58 90.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
133 ROOM_6_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ROOM_5_FLR_3_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
134 ROOM_6_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.53 3.05 0.00 CORRIDOR_FLR_3_WALL_4_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
135 ROOM_6_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.228 0.216   39.02 39.02 39.02 0.00 180.00 4.57 8.53 0.00 ROOM_6_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
136 ROOM_6_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.228 0.218   39.02 39.02 39.02 180.00 0.00 4.57 8.53 0.00 ROOM_6_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
137 ROOM_6_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.03 78.03 78.03 0.00 90.00 78.03 1.00 0.00 ROOM_6_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
138 CORRIDOR_FLR_3_WALL_1_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.021 0.886   11.83 17.65 11.83 0.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
139 CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW Window CORRIDOR_FLR_3_WALL_1_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.38_SHGC_0.36 N/A 2.159 No 5.82 5.82 5.82 0.00 90.00 4.78 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
140 CORRIDOR_FLR_3_WALL_2_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.021 0.886   4.35 6.50 4.35 0.00 90.00 2.13 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
141 CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW Window CORRIDOR_FLR_3_WALL_2_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.38_SHGC_0.36 N/A 2.159 No 2.15 2.15 2.15 0.00 90.00 1.76 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
142 CORRIDOR_FLR_3_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.021 0.886   4.36 6.50 4.36 180.00 90.00 2.13 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
143 CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW Window CORRIDOR_FLR_3_WALL_1_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.38_SHGC_0.36 N/A 2.159 No 2.15 2.15 2.15 180.00 90.00 1.76 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
144 CORRIDOR_FLR_3_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.021 0.886   11.83 17.65 11.83 180.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
145 CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW Window CORRIDOR_FLR_3_WALL_2_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.38_SHGC_0.36 N/A 2.159 No 5.82 5.82 5.82 180.00 90.00 4.78 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
146 CORRIDOR_FLR_3_WALL_3_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   211.82 211.82 211.82 0.00 90.00 69.50 3.05 0.00 CORRIDOR_FLR_3_WALL_3_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
147 CORRIDOR_FLR_3_WALL_1_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_1_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
148 CORRIDOR_FLR_3_WALL_2_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_2_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
149 CORRIDOR_FLR_3_WALL_3_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.54 3.05 0.00 ROOM_5_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
150 CORRIDOR_FLR_3_WALL_4_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.53 3.05 0.00 ROOM_6_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
151 CORRIDOR_FLR_3_WALL_3_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   211.82 211.82 211.82 180.00 90.00 69.49 3.05 0.00 CORRIDOR_FLR_3_WALL_3_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
152 CORRIDOR_FLR_3_WALL_1_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_1_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
153 CORRIDOR_FLR_3_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
154 CORRIDOR_FLR_3_WALL_3_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.54 3.05 0.00 ROOM_1_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
155 CORRIDOR_FLR_3_WALL_4_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.53 3.05 0.00 ROOM_2_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
156 CORRIDOR_FLR_3_FLOOR_1 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.228 0.216   74.32 74.32 74.32 180.00 180.00 8.62 8.62 0.00 CORRIDOR_FLR_3_FLOOR_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
157 CORRIDOR_FLR_3_FLOOR_2 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.228 0.216   240.77 240.77 240.77 270.00 180.00 3.66 65.84 0.00 CORRIDOR_FLR_3_FLOOR_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
158 CORRIDOR_FLR_3_FLOOR_3 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.228 0.216   74.32 74.32 74.32 90.00 180.00 8.62 8.62 0.00 CORRIDOR_FLR_3_FLOOR_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
159 CORRIDOR_FLR_3_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.228 0.218   74.32 74.32 74.32 90.00 0.00 8.62 8.62 0.00 CORRIDOR_FLR_3_CEILING_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
160 CORRIDOR_FLR_3_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.228 0.218   240.77 240.77 240.77 90.00 0.00 3.66 65.84 0.00 CORRIDOR_FLR_3_CEILING_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
161 CORRIDOR_FLR_3_CEILING_3 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.228 0.218   74.32 74.32 74.32 90.00 0.00 8.62 8.62 0.00 CORRIDOR_FLR_3_CEILING_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
162 CORRIDOR_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   778.81 778.81 778.81 0.00 90.00 778.81 1.00 0.00 CORRIDOR_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
163 ROOM_1_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 0.930 0.816   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
164 ROOM_1_FLR_6_WALL_SOUTH_WINDOW Window ROOM_1_FLR_6_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.38_SHGC_0.36 N/A 2.159 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
165 ROOM_1_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 0.930 0.816   17.43 26.01 17.43 270.00 90.00 8.54 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
166 ROOM_1_FLR_6_WALL_WEST_WINDOW Window ROOM_1_FLR_6_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.38_SHGC_0.36 N/A 2.159 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
167 ROOM_1_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ROOM_2_FLR_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
168 ROOM_1_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.54 3.05 0.00 ROOM_1_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
169 ROOM_1_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.228 0.216   39.02 39.02 39.02 0.00 180.00 4.57 8.54 0.00 ROOM_1_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
170 ROOM_1_FLR_6_CEILING Roof   CTF - ConductionTransferFunction RES_ROOF 0.186 0.180   39.02 39.02 39.02 180.00 0.00 4.57 8.54 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
171 ROOM_1_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 ROOM_1_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
172 ROOM_2_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 0.930 0.816   9.34 13.94 9.34 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
173 ROOM_2_FLR_6_WALL_NORTH_WINDOW Window ROOM_2_FLR_6_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.38_SHGC_0.36 N/A 2.159 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
174 ROOM_2_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 0.930 0.816   17.43 26.01 17.43 270.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
175 ROOM_2_FLR_6_WALL_WEST_WINDOW Window ROOM_2_FLR_6_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.38_SHGC_0.36 N/A 2.159 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
176 ROOM_2_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.53 3.05 0.00 ROOM_2_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
177 ROOM_2_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ROOM_1_FLR_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
178 ROOM_2_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.228 0.216   39.02 39.02 39.02 0.00 180.00 4.57 8.53 0.00 ROOM_2_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
179 ROOM_2_FLR_6_CEILING Roof   CTF - ConductionTransferFunction RES_ROOF 0.186 0.180   39.02 39.02 39.02 180.00 0.00 4.57 8.53 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
180 ROOM_2_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.03 78.03 78.03 0.00 90.00 78.03 1.00 0.00 ROOM_2_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
181 ROOM_3_MULT9_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 0.930 0.816   13.70 20.44 13.70 180.00 90.00 6.71 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
182 ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW Window ROOM_3_MULT9_FLR_6_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.38_SHGC_0.36 N/A 2.159 No 6.74 6.74 6.74 180.00 90.00 5.53 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
183 ROOM_3_MULT9_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 0.00 90.00 6.71 3.05 0.00 ROOM_3_MULT9_FLR_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
184 ROOM_3_MULT9_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 90.00 90.00 3.66 3.05 0.00 ROOM_3_MULT9_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
185 ROOM_3_MULT9_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 270.00 90.00 3.66 3.05 0.00 ROOM_3_MULT9_FLR_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
186 ROOM_3_MULT9_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.228 0.216   24.53 24.53 24.53 0.00 180.00 6.71 3.66 0.00 ROOM_3_MULT9_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
187 ROOM_3_MULT9_FLR_6_CEILING Roof   CTF - ConductionTransferFunction RES_ROOF 0.186 0.180   24.53 24.53 24.53 180.00 0.00 6.71 3.66 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
188 ROOM_3_MULT9_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   49.06 49.06 49.06 0.00 90.00 49.06 1.00 0.00 ROOM_3_MULT9_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
189 BANQUET_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.034 0.896   65.36 97.55 65.36 0.00 90.00 32.00 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
190 BANQUET_FLR_6_WALL_NORTH_WINDOW Window BANQUET_FLR_6_WALL_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.38_SHGC_0.36 N/A 2.159 No 32.19 32.19 32.19 0.00 90.00 26.40 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
191 BANQUET_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 CORRIDOR_FLR_6_WALL_3_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
192 BANQUET_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   97.55 97.55 97.55 180.00 90.00 32.00 3.05 0.00 CORRIDOR_FLR_6_WALL_3_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
193 BANQUET_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 CORRIDOR_FLR_6_WALL_1_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
194 BANQUET_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.228 0.216   331.66 331.66 331.66 0.00 180.00 32.00 10.36 0.00 BANQUET_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
195 BANQUET_FLR_6_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   331.66 331.66 331.66 180.00 0.00 32.00 10.36 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
196 BANQUET_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   663.31 663.31 663.31 0.00 90.00 663.31 1.00 0.00 BANQUET_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
197 DINING_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.034 0.896   65.36 97.55 65.36 0.00 90.00 32.00 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
198 DINING_FLR_6_WALL_NORTH_WINDOW Window DINING_FLR_6_WALL_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.38_SHGC_0.36 N/A 2.159 No 32.19 32.19 32.19 0.00 90.00 26.40 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
199 DINING_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 KITCHEN_FLR_6_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
200 DINING_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   97.55 97.55 97.55 180.00 90.00 32.00 3.05 0.00 DINING_FLR_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
201 DINING_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 CORRIDOR_FLR_6_WALL_2_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
202 DINING_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.228 0.216   331.66 331.66 331.66 0.00 180.00 32.00 10.36 0.00 DINING_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
203 DINING_FLR_6_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   331.66 331.66 331.66 180.00 0.00 32.00 10.36 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
204 DINING_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   663.31 663.31 663.31 0.00 90.00 663.31 1.00 0.00 DINING_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
205 KITCHEN_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.034 0.896   16.77 21.37 16.77 0.00 90.00 7.01 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
206 KITCHEN_FLR_6_WALL_NORTH_WINDOW Window KITCHEN_FLR_6_WALL_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.38_SHGC_0.36 N/A 2.159 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
207 KITCHEN_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.034 0.896   34.86 52.03 34.86 90.00 90.00 17.07 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
208 KITCHEN_FLR_6_WALL_EAST_WINDOW Window KITCHEN_FLR_6_WALL_EAST Window5 Detailed Fenestration NONRESWINDOW_U_0.38_SHGC_0.36 N/A 2.159 No 17.17 17.17 17.17 90.00 90.00 14.08 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
209 KITCHEN_FLR_6_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.034 0.896   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
210 KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW Window KITCHEN_FLR_6_WALL_1_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.38_SHGC_0.36 N/A 2.159 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
211 KITCHEN_FLR_6_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 180.00 90.00 2.44 3.05 0.00 KITCHEN_FLR_6_WALL_2_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
212 KITCHEN_FLR_6_WALL_1_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_6_WALL_3_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
213 KITCHEN_FLR_6_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 DINING_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
214 KITCHEN_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.228 0.216   103.30 103.30 103.30 180.00 180.00 10.16 10.16 0.00 KITCHEN_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
215 KITCHEN_FLR_6_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   103.30 103.30 103.30 270.00 0.00 10.16 10.16 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 6
216 KITCHEN_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   206.61 206.61 206.61 0.00 90.00 206.61 1.00 0.00 KITCHEN_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
217 CORRIDOR_FLR_6_WALL_1_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.034 0.896   11.83 17.65 11.83 0.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
218 CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW Window CORRIDOR_FLR_6_WALL_1_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.38_SHGC_0.36 N/A 2.159 No 5.82 5.82 5.82 0.00 90.00 4.78 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
219 CORRIDOR_FLR_6_WALL_2_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.034 0.896   10.58 15.79 10.58 0.00 90.00 5.18 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
220 CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW Window CORRIDOR_FLR_6_WALL_2_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.38_SHGC_0.36 N/A 2.159 No 5.21 5.21 5.21 0.00 90.00 4.27 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
221 CORRIDOR_FLR_6_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.034 0.896   34.86 52.03 34.86 180.00 90.00 17.07 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
222 CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW Window CORRIDOR_FLR_6_WALL_2_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.38_SHGC_0.36 N/A 2.159 No 17.17 17.17 17.17 180.00 90.00 14.08 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
223 CORRIDOR_FLR_6_WALL_3_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   97.55 97.55 97.55 0.00 90.00 32.00 3.05 0.00 BANQUET_FLR_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
224 CORRIDOR_FLR_6_WALL_4_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   104.98 104.98 104.98 0.00 90.00 34.44 3.05 0.00 CORRIDOR_FLR_6_WALL_4_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
225 CORRIDOR_FLR_6_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   183.95 183.95 183.95 180.00 90.00 60.35 3.05 0.00 CORRIDOR_FLR_6_WALL_1_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
226 CORRIDOR_FLR_6_WALL_1_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 270.00 90.00 3.66 3.05 0.00 CORRIDOR_FLR_6_WALL_1_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
227 CORRIDOR_FLR_6_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   40.88 40.88 40.88 270.00 90.00 13.41 3.05 0.00 CORRIDOR_FLR_6_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
228 CORRIDOR_FLR_6_WALL_3_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 BANQUET_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
229 CORRIDOR_FLR_6_WALL_1_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 BANQUET_FLR_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
230 CORRIDOR_FLR_6_WALL_2_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 DINING_FLR_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
231 CORRIDOR_FLR_6_WALL_3_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 KITCHEN_FLR_6_WALL_1_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
232 CORRIDOR_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.228 0.216   412.12 412.12 412.12 180.00 180.00 20.30 20.30 0.00 CORRIDOR_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 12
233 CORRIDOR_FLR_6_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   244.71 244.71 244.71 90.00 0.00 15.64 15.64 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 8
234 CORRIDOR_FLR_6_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   167.42 167.42 167.42 270.00 0.00 12.94 12.94 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 6
235 CORRIDOR_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   824.25 824.25 824.25 0.00 90.00 824.25 1.00 0.00 CORRIDOR_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 BASEMENT RunPeriod: RUNPERIOD 1 1.8488594988E-002 2.2974074959E-002 Pass Pass 4.9569037922E-003 1.4977626802E-002 Pass Pass
2 RETAIL_1_FLR_1 RunPeriod: RUNPERIOD 1 1.8887459915E-003 1.4578722389E-003 Pass Pass 0.3353849653 0.9544137540 Pass Pass
3 RETAIL_2_FLR_1 RunPeriod: RUNPERIOD 1 2.1100874448E-002 2.9470838200E-002 Pass Pass 1.2823253019E-002 3.3016054019E-002 Pass Pass
4 MECH_FLR_1 RunPeriod: RUNPERIOD 1 3.9650809377E-003 9.7986082554E-003 Pass Pass 2.6637532891E-002 6.1267690089E-002 Pass Pass
5 STORAGE_FLR_1 RunPeriod: RUNPERIOD 1 3.3711051241E-004 2.7846206786E-004 Pass Pass 0.2171921824 1.3485721334 Pass Pass
6 LAUNDRY_FLR_1 RunPeriod: RUNPERIOD 1 6.9118705310E-002 0.2042853969 Pass Pass 1.9430974578E-002 5.2395281092E-002 Pass Pass
7 CAFE_FLR_1 RunPeriod: RUNPERIOD 1 1.3071775497E-002 4.2760540289E-002 Pass Pass 2.5584843043E-002 7.9956799351E-002 Pass Pass
8 LOBBY_FLR_1 RunPeriod: RUNPERIOD 1 2.9769615282E-002 4.7731752855E-002 Pass Pass 1.3400404218E-002 3.6622174781E-002 Pass Pass
9 ROOM_1_FLR_3 RunPeriod: RUNPERIOD 1 6.9897292769E-002 0.2088997344 Pass Pass 8.5628166182E-002 0.3346990275 Pass Pass
10 ROOM_2_FLR_3 RunPeriod: RUNPERIOD 1 7.0277517597E-002 0.2094129695 Pass Pass 8.6546415946E-002 0.3391737901 Pass Pass
11 ROOM_3_MULT19_FLR_3 RunPeriod: RUNPERIOD 1 3.8141918404E-002 3.6404111060E-002 Pass Pass 7.3022170539E-003 6.6639791027E-002 Pass Pass
12 ROOM_4_MULT19_FLR_3 RunPeriod: RUNPERIOD 1 2.7992803800E-002 8.7225029039E-002 Pass Pass 0.2000083775 0.6415293123 Pass Pass
13 ROOM_5_FLR_3 RunPeriod: RUNPERIOD 1 6.9468167277E-002 0.2072746925 Pass Pass 8.7529242391E-002 0.3436611285 Pass Pass
14 ROOM_6_FLR_3 RunPeriod: RUNPERIOD 1 6.9808207792E-002 0.2077777308 Pass Pass 8.9590965285E-002 0.3525749450 Pass Pass
15 CORRIDOR_FLR_3 RunPeriod: RUNPERIOD 1 4.4281993367E-004 3.3088679879E-004 Pass Pass 0.1231482578 0.4735711270 Pass Pass
16 ROOM_1_FLR_6 RunPeriod: RUNPERIOD 1 8.3260952093E-002 0.2586722274 Pass Pass 6.7631424739E-002 0.2174486788 Pass Pass
17 ROOM_2_FLR_6 RunPeriod: RUNPERIOD 1 8.3505029892E-002 0.2585725913 Pass Pass 7.0578586520E-002 0.2292271660 Pass Pass
18 ROOM_3_MULT9_FLR_6 RunPeriod: RUNPERIOD 1 5.4520699784E-002 0.1749875913 Pass Pass 7.3085334011E-002 0.2270344001 Pass Pass
19 BANQUET_FLR_6 RunPeriod: RUNPERIOD 1 2.7935332518E-002 6.6740056639E-002 Pass Pass 1.3571226362E-002 4.1274763372E-002 Pass Pass
20 DINING_FLR_6 RunPeriod: RUNPERIOD 1 1.9074654504E-002 4.8127803758E-002 Pass Pass 1.3740882676E-002 3.9961070806E-002 Pass Pass
21 KITCHEN_FLR_6 RunPeriod: RUNPERIOD 1 2.1440819553E-002 6.0450003670E-002 Pass Pass 2.1027794326E-002 4.2458882834E-002 Pass Pass
22 CORRIDOR_FLR_6 RunPeriod: RUNPERIOD 1 7.1941917326E-004 5.1317068149E-004 Pass Pass 2.6713901822E-002 3.7285758752E-002 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:35

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 3532.16 61.40 1821.26 7450.52 2337.33 15202.68



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:35

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB -4.20 0.00 -4.20 Wetbulb [C] 4.30 20.00
SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 29.40 10.40 18.30 Wetbulb [C] 4.20 350.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 0.00 0      
Feb 0.00 0      
Mar 22.00 23      
Apr 0.00 0      
May 0.00 0      
Jun 16.00 20      
Jul 0.00 0      
Aug 24.00 18      
Sep 12.00 15      
Oct 61.00 41      
Nov 0.00 0      
Dec 45.00 41      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:35

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_NORTH BASEMENT_WALL_NORTH_CFACTOR 1.00 0.399 0.419 211.13 211.13 0.00 90.00 N
BASEMENT_WALL_EAST BASEMENT_WALL_EAST_CFACTOR 1.00 0.399 0.419 55.76 55.76 90.00 90.00 E
BASEMENT_WALL_SOUTH BASEMENT_WALL_SOUTH_CFACTOR 1.00 0.399 0.419 211.13 211.13 180.00 90.00 S
BASEMENT_WALL_WEST BASEMENT_WALL_WEST_CFACTOR 1.00 0.399 0.419 55.76 55.76 270.00 90.00 W
RETAIL_1_FLR_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.731 0.820 45.89 22.63 180.00 90.00 S
RETAIL_1_FLR_1_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.731 0.820 22.95 22.95 270.00 90.00 W
RETAIL_1_FLR_1_CEILING NONRES_ROOF 0.23 0.182 0.186 67.07 67.07 180.00 0.00  
RETAIL_2_FLR_1_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.731 0.820 26.57 24.62 270.00 90.00 W
MECH_FLR_1_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.731 0.820 62.80 62.80 0.00 90.00 N
STORAGE_FLR_1_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.731 0.820 36.23 28.80 0.00 90.00 N
LAUNDRY_FLR_1_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.731 0.820 18.12 18.12 0.00 90.00 N
LAUNDRY_FLR_1_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.731 0.820 67.63 65.68 90.00 90.00 E
CAFE_FLR_1_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.731 0.820 22.95 21.00 90.00 90.00 E
CAFE_FLR_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.731 0.820 129.23 63.73 180.00 90.00 S
CAFE_FLR_1_CEILING NONRES_ROOF 0.23 0.182 0.186 188.86 188.86 180.00 0.00  
LOBBY_FLR_1_WALL_1_NORTH NONRES_EXT_WALL_GRD 0.30 0.731 0.820 213.77 209.87 0.00 90.00 N
LOBBY_FLR_1_WALL_2_NORTH NONRES_EXT_WALL_GRD 0.30 0.731 0.820 12.08 12.08 0.00 90.00 N
LOBBY_FLR_1_WALL_1_SOUTH NONRES_EXT_WALL_GRD 0.30 0.731 0.820 167.88 82.79 180.00 90.00 S
LOBBY_FLR_1_WALL_1_WEST NONRES_EXT_WALL_GRD 0.30 0.731 0.820 41.06 41.06 270.00 90.00 W
LOBBY_FLR_1_CEILING_2 NONRES_ROOF 0.23 0.182 0.186 245.35 245.35 180.00 0.00  
ROOM_1_FLR_3_WALL_SOUTH RES_EXT_WALL_MID 0.30 0.806 0.917 55.74 37.35 180.00 90.00 S
ROOM_1_FLR_3_WALL_WEST RES_EXT_WALL_MID 0.30 0.806 0.917 104.06 69.72 270.00 90.00 W
ROOM_2_FLR_3_WALL_NORTH RES_EXT_WALL_MID 0.30 0.806 0.917 55.74 37.35 0.00 90.00 N
ROOM_2_FLR_3_WALL_WEST RES_EXT_WALL_MID 0.30 0.806 0.917 104.05 69.71 270.00 90.00 W
ROOM_3_MULT19_FLR_3_WALL_SOUTH RES_EXT_WALL_MID 0.30 0.806 0.917 847.14 567.58 180.00 90.00 S
ROOM_4_MULT19_FLR_3_WALL_NORTH RES_EXT_WALL_MID 0.30 0.806 0.917 847.37 567.71 0.00 90.00 N
ROOM_5_FLR_3_WALL_EAST RES_EXT_WALL_MID 0.30 0.806 0.917 104.06 69.72 90.00 90.00 E
ROOM_5_FLR_3_WALL_SOUTH RES_EXT_WALL_MID 0.30 0.806 0.917 55.74 37.35 180.00 90.00 S
ROOM_6_FLR_3_WALL_NORTH RES_EXT_WALL_MID 0.30 0.806 0.917 55.74 37.35 0.00 90.00 N
ROOM_6_FLR_3_WALL_EAST RES_EXT_WALL_MID 0.30 0.806 0.917 104.05 69.71 90.00 90.00 E
CORRIDOR_FLR_3_WALL_1_NORTH NONRES_EXT_WALL_MID 0.30 0.886 1.021 70.60 47.31 0.00 90.00 N
CORRIDOR_FLR_3_WALL_2_NORTH NONRES_EXT_WALL_MID 0.30 0.886 1.021 26.01 17.42 0.00 90.00 N
CORRIDOR_FLR_3_WALL_1_SOUTH NONRES_EXT_WALL_MID 0.30 0.886 1.021 26.02 17.43 180.00 90.00 S
CORRIDOR_FLR_3_WALL_2_SOUTH NONRES_EXT_WALL_MID 0.30 0.886 1.021 70.60 47.31 180.00 90.00 S
ROOM_1_FLR_6_WALL_SOUTH RES_EXT_WALL_TOP 0.30 0.816 0.930 13.94 9.34 180.00 90.00 S
ROOM_1_FLR_6_WALL_WEST RES_EXT_WALL_TOP 0.30 0.816 0.930 26.01 17.43 270.00 90.00 W
ROOM_1_FLR_6_CEILING RES_ROOF 0.23 0.182 0.186 39.02 39.02 180.00 0.00  
ROOM_2_FLR_6_WALL_NORTH RES_EXT_WALL_TOP 0.30 0.816 0.930 13.94 9.34 0.00 90.00 N
ROOM_2_FLR_6_WALL_WEST RES_EXT_WALL_TOP 0.30 0.816 0.930 26.01 17.43 270.00 90.00 W
ROOM_2_FLR_6_CEILING RES_ROOF 0.23 0.182 0.186 39.02 39.02 180.00 0.00  
ROOM_3_MULT9_FLR_6_WALL_SOUTH RES_EXT_WALL_TOP 0.30 0.816 0.930 183.96 123.26 180.00 90.00 S
ROOM_3_MULT9_FLR_6_CEILING RES_ROOF 0.23 0.182 0.186 220.77 220.77 180.00 0.00  
BANQUET_FLR_6_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 0.896 1.034 97.55 65.36 0.00 90.00 N
BANQUET_FLR_6_CEILING NONRES_ROOF 0.23 0.182 0.186 331.66 331.66 180.00 0.00  
DINING_FLR_6_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 0.896 1.034 97.55 65.36 0.00 90.00 N
DINING_FLR_6_CEILING NONRES_ROOF 0.23 0.182 0.186 331.66 331.66 180.00 0.00  
KITCHEN_FLR_6_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 0.896 1.034 21.37 16.77 0.00 90.00 N
KITCHEN_FLR_6_WALL_EAST NONRES_EXT_WALL_TOP 0.30 0.896 1.034 52.03 34.86 90.00 90.00 E
KITCHEN_FLR_6_WALL_1_SOUTH NONRES_EXT_WALL_TOP 0.30 0.896 1.034 13.94 9.34 180.00 90.00 S
KITCHEN_FLR_6_CEILING NONRES_ROOF 0.23 0.182 0.186 103.30 103.30 270.00 0.00  
CORRIDOR_FLR_6_WALL_1_NORTH NONRES_EXT_WALL_TOP 0.30 0.896 1.034 17.65 11.83 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_NORTH NONRES_EXT_WALL_TOP 0.30 0.896 1.034 15.79 10.58 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_SOUTH NONRES_EXT_WALL_TOP 0.30 0.896 1.034 52.03 34.86 180.00 90.00 S
CORRIDOR_FLR_6_CEILING_1 NONRES_ROOF 0.23 0.182 0.186 244.71 244.71 90.00 0.00  
CORRIDOR_FLR_6_CEILING_2 NONRES_ROOF 0.23 0.182 0.186 167.42 167.42 270.00 0.00  


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_FLOOR BASEMENT_FLOOR 0.30 1.441 2.705 1978.83 1978.83 0.00 180.00  
BASEMENT_CEILING_1 NONRES_FLOOR_CEILING 0.30 0.215 0.228 67.07 67.07 180.00 0.00  
BASEMENT_CEILING_2 NONRES_FLOOR_CEILING 0.30 0.215 0.228 77.67 77.67 180.00 0.00  
BASEMENT_CEILING_3 NONRES_FLOOR_CEILING 0.30 0.215 0.228 164.24 164.24 180.00 0.00  
BASEMENT_CEILING_4 NONRES_FLOOR_CEILING 0.30 0.215 0.228 94.76 94.76 180.00 0.00  
BASEMENT_CEILING_5 NONRES_FLOOR_CEILING 0.30 0.215 0.228 78.04 78.04 180.00 0.00  
BASEMENT_CEILING_6 NONRES_FLOOR_CEILING 0.30 0.215 0.228 188.86 188.86 180.00 0.00  
BASEMENT_CEILING_7 NONRES_FLOOR_CEILING 0.30 0.215 0.228 1088.56 1088.56 180.00 0.00  
BASEMENT_CEILING_8 NONRES_FLOOR_CEILING 0.30 0.215 0.228 219.63 219.63 90.00 0.00  
RETAIL_1_FLR_1_WALL_NORTH INT_WALL 0.30 2.511 6.299 45.89 45.89 0.00 90.00 N
RETAIL_1_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 22.95 22.95 90.00 90.00 E
RETAIL_1_FLR_1_FLOOR NONRES_FLOOR 0.30 0.215 0.228 67.07 67.07 0.00 180.00  
RETAIL_2_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 45.89 45.89 180.00 90.00 S
RETAIL_2_FLR_1_WALL_NORTH INT_WALL 0.30 2.511 6.299 45.89 45.89 0.00 90.00 N
RETAIL_2_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 26.57 26.57 90.00 90.00 E
RETAIL_2_FLR_1_FLOOR NONRES_FLOOR 0.30 0.215 0.228 77.67 77.67 0.00 180.00  
RETAIL_2_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.217 0.228 77.67 77.67 180.00 0.00  
MECH_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 41.06 41.06 90.00 90.00 E
MECH_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 62.80 62.80 180.00 90.00 S
MECH_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 41.06 41.06 270.00 90.00 W
MECH_FLR_1_FLOOR NONRES_FLOOR 0.30 0.215 0.228 164.24 164.24 0.00 180.00  
MECH_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.217 0.228 164.24 164.24 180.00 0.00  
STORAGE_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 41.06 41.06 90.00 90.00 E
STORAGE_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 36.23 36.23 180.00 90.00 S
STORAGE_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 41.06 41.06 270.00 90.00 W
STORAGE_FLR_1_FLOOR NONRES_FLOOR 0.30 0.215 0.228 94.76 94.76 0.00 180.00  
STORAGE_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.217 0.228 94.76 94.76 180.00 0.00  
LAUNDRY_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 18.12 18.12 180.00 90.00 S
LAUNDRY_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 67.63 67.63 270.00 90.00 W
LAUNDRY_FLR_1_FLOOR NONRES_FLOOR 0.30 0.215 0.228 78.04 78.04 0.00 180.00  
LAUNDRY_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.217 0.228 78.04 78.04 180.00 0.00  
CAFE_FLR_1_WALL_1_NORTH INT_WALL 0.30 2.511 6.299 111.11 111.11 0.00 90.00 N
CAFE_FLR_1_WALL_2_NORTH INT_WALL 0.30 2.511 6.299 18.12 18.12 0.00 90.00 N
CAFE_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 22.95 22.95 270.00 90.00 W
CAFE_FLR_1_FLOOR NONRES_FLOOR 0.30 0.215 0.228 188.86 188.86 0.00 180.00  
LOBBY_FLR_1_WALL_2_SOUTH INT_WALL 0.30 2.511 6.299 45.89 45.89 180.00 90.00 S
LOBBY_FLR_1_WALL_3_SOUTH INT_WALL 0.30 2.511 6.299 111.11 111.11 180.00 90.00 S
LOBBY_FLR_1_WALL_2_WEST INT_WALL 0.30 2.511 6.299 22.95 22.95 270.00 90.00 W
LOBBY_FLR_1_WALL_3_WEST INT_WALL 0.30 2.511 6.299 26.57 26.57 270.00 90.00 W
LOBBY_FLR_1_WALL_4_WEST INT_WALL 0.30 2.511 6.299 41.06 41.06 270.00 90.00 W
LOBBY_FLR_1_WALL_3_NORTH INT_WALL 0.30 2.511 6.299 62.80 62.80 0.00 90.00 N
LOBBY_FLR_1_WALL_4_NORTH INT_WALL 0.30 2.511 6.299 36.23 36.23 0.00 90.00 N
LOBBY_FLR_1_WALL_1_EAST INT_WALL 0.30 2.511 6.299 41.06 41.06 90.00 90.00 E
LOBBY_FLR_1_WALL_2_EAST INT_WALL 0.30 2.511 6.299 22.95 22.95 90.00 90.00 E
LOBBY_FLR_1_WALL_3_EAST INT_WALL 0.30 2.511 6.299 67.63 67.63 90.00 90.00 E
LOBBY_FLR_1_FLOOR_1 NONRES_FLOOR 0.30 0.215 0.228 1088.56 1088.56 180.00 180.00  
LOBBY_FLR_1_FLOOR_2 NONRES_FLOOR 0.30 0.215 0.228 219.63 219.63 90.00 180.00  
LOBBY_FLR_1_CEILING_1 NONRES_FLOOR_CEILING 0.30 0.217 0.228 1062.83 1062.83 270.00 0.00  
ROOM_1_FLR_3_WALL_NORTH INT_WALL 0.30 2.511 6.299 55.74 55.74 0.00 90.00 N
ROOM_1_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 104.06 104.06 90.00 90.00 E
ROOM_1_FLR_3_FLOOR NONRES_FLOOR 0.30 0.212 0.228 156.09 156.09 0.00 180.00  
ROOM_1_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.217 0.228 156.09 156.09 180.00 0.00  
ROOM_2_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 104.05 104.05 90.00 90.00 E
ROOM_2_FLR_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 55.74 55.74 180.00 90.00 S
ROOM_2_FLR_3_FLOOR NONRES_FLOOR 0.30 0.212 0.228 156.07 156.07 0.00 180.00  
ROOM_2_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.217 0.228 156.07 156.07 180.00 0.00  
ROOM_3_MULT19_FLR_3_WALL_NORTH INT_WALL 0.30 2.511 6.299 847.14 847.14 0.00 90.00 N
ROOM_3_MULT19_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 90.00 90.00 E
ROOM_3_MULT19_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 270.00 90.00 W
ROOM_3_MULT19_FLR_3_FLOOR NONRES_FLOOR 0.30 0.212 0.228 1863.81 1863.81 0.00 180.00  
ROOM_3_MULT19_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.217 0.228 1863.81 1863.81 180.00 0.00  
ROOM_4_MULT19_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 90.00 90.00 E
ROOM_4_MULT19_FLR_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 847.37 847.37 180.00 90.00 S
ROOM_4_MULT19_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 270.00 90.00 W
ROOM_4_MULT19_FLR_3_FLOOR NONRES_FLOOR 0.30 0.212 0.228 1864.32 1864.32 0.00 180.00  
ROOM_4_MULT19_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.217 0.228 1864.32 1864.32 180.00 0.00  
ROOM_5_FLR_3_WALL_NORTH INT_WALL 0.30 2.511 6.299 55.74 55.74 0.00 90.00 N
ROOM_5_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 104.06 104.06 270.00 90.00 W
ROOM_5_FLR_3_FLOOR NONRES_FLOOR 0.30 0.212 0.228 156.09 156.09 0.00 180.00  
ROOM_5_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.217 0.228 156.09 156.09 180.00 0.00  
ROOM_6_FLR_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 55.74 55.74 180.00 90.00 S
ROOM_6_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 104.05 104.05 270.00 90.00 W
ROOM_6_FLR_3_FLOOR NONRES_FLOOR 0.30 0.212 0.228 156.07 156.07 0.00 180.00  
ROOM_6_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.217 0.228 156.07 156.07 180.00 0.00  
CORRIDOR_FLR_3_WALL_3_NORTH INT_WALL 0.30 2.511 6.299 847.28 847.28 0.00 90.00 N
CORRIDOR_FLR_3_WALL_1_EAST INT_WALL 0.30 2.511 6.299 81.76 81.76 90.00 90.00 E
CORRIDOR_FLR_3_WALL_2_EAST INT_WALL 0.30 2.511 6.299 81.76 81.76 90.00 90.00 E
CORRIDOR_FLR_3_WALL_3_EAST INT_WALL 0.30 2.511 6.299 104.06 104.06 90.00 90.00 E
CORRIDOR_FLR_3_WALL_4_EAST INT_WALL 0.30 2.511 6.299 104.05 104.05 90.00 90.00 E
CORRIDOR_FLR_3_WALL_3_SOUTH INT_WALL 0.30 2.511 6.299 847.27 847.27 180.00 90.00 S
CORRIDOR_FLR_3_WALL_1_WEST INT_WALL 0.30 2.511 6.299 81.76 81.76 270.00 90.00 W
CORRIDOR_FLR_3_WALL_2_WEST INT_WALL 0.30 2.511 6.299 81.76 81.76 270.00 90.00 W
CORRIDOR_FLR_3_WALL_3_WEST INT_WALL 0.30 2.511 6.299 104.06 104.06 270.00 90.00 W
CORRIDOR_FLR_3_WALL_4_WEST INT_WALL 0.30 2.511 6.299 104.05 104.05 270.00 90.00 W
CORRIDOR_FLR_3_FLOOR_1 NONRES_FLOOR 0.30 0.212 0.228 297.29 297.29 180.00 180.00  
CORRIDOR_FLR_3_FLOOR_2 NONRES_FLOOR 0.30 0.212 0.228 963.06 963.06 270.00 180.00  
CORRIDOR_FLR_3_FLOOR_3 NONRES_FLOOR 0.30 0.212 0.228 297.26 297.26 90.00 180.00  
CORRIDOR_FLR_3_CEILING_1 NONRES_FLOOR_CEILING 0.30 0.217 0.228 297.29 297.29 90.00 0.00  
CORRIDOR_FLR_3_CEILING_2 NONRES_FLOOR_CEILING 0.30 0.217 0.228 963.06 963.06 90.00 0.00  
CORRIDOR_FLR_3_CEILING_3 NONRES_FLOOR_CEILING 0.30 0.217 0.228 297.26 297.26 90.00 0.00  
ROOM_1_FLR_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 13.94 13.94 0.00 90.00 N
ROOM_1_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 26.01 26.01 90.00 90.00 E
ROOM_1_FLR_6_FLOOR NONRES_FLOOR 0.30 0.212 0.228 39.02 39.02 0.00 180.00  
ROOM_2_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 26.01 26.01 90.00 90.00 E
ROOM_2_FLR_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 13.94 13.94 180.00 90.00 S
ROOM_2_FLR_6_FLOOR NONRES_FLOOR 0.30 0.212 0.228 39.02 39.02 0.00 180.00  
ROOM_3_MULT9_FLR_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 183.96 183.96 0.00 90.00 N
ROOM_3_MULT9_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 100.35 100.35 90.00 90.00 E
ROOM_3_MULT9_FLR_6_WALL_WEST INT_WALL 0.30 2.511 6.299 100.35 100.35 270.00 90.00 W
ROOM_3_MULT9_FLR_6_FLOOR NONRES_FLOOR 0.30 0.212 0.228 220.77 220.77 0.00 180.00  
BANQUET_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
BANQUET_FLR_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 97.55 97.55 180.00 90.00 S
BANQUET_FLR_6_WALL_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
BANQUET_FLR_6_FLOOR NONRES_FLOOR 0.30 0.212 0.228 331.66 331.66 0.00 180.00  
DINING_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
DINING_FLR_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 97.55 97.55 180.00 90.00 S
DINING_FLR_6_WALL_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
DINING_FLR_6_FLOOR NONRES_FLOOR 0.30 0.212 0.228 331.66 331.66 0.00 180.00  
KITCHEN_FLR_6_WALL_2_SOUTH INT_WALL 0.30 2.511 6.299 7.43 7.43 180.00 90.00 S
KITCHEN_FLR_6_WALL_1_WEST INT_WALL 0.30 2.511 6.299 20.44 20.44 270.00 90.00 W
KITCHEN_FLR_6_WALL_2_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
KITCHEN_FLR_6_FLOOR NONRES_FLOOR 0.30 0.212 0.228 103.30 103.30 180.00 180.00  
CORRIDOR_FLR_6_WALL_3_NORTH INT_WALL 0.30 2.511 6.299 97.55 97.55 0.00 90.00 N
CORRIDOR_FLR_6_WALL_4_NORTH INT_WALL 0.30 2.511 6.299 104.98 104.98 0.00 90.00 N
CORRIDOR_FLR_6_WALL_1_SOUTH INT_WALL 0.30 2.511 6.299 183.95 183.95 180.00 90.00 S
CORRIDOR_FLR_6_WALL_1_WEST INT_WALL 0.30 2.511 6.299 11.15 11.15 270.00 90.00 W
CORRIDOR_FLR_6_WALL_2_WEST INT_WALL 0.30 2.511 6.299 40.88 40.88 270.00 90.00 W
CORRIDOR_FLR_6_WALL_3_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
CORRIDOR_FLR_6_WALL_1_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
CORRIDOR_FLR_6_WALL_2_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
CORRIDOR_FLR_6_WALL_3_EAST INT_WALL 0.30 2.511 6.299 20.44 20.44 90.00 90.00 E
CORRIDOR_FLR_6_FLOOR NONRES_FLOOR 0.30 0.212 0.228 412.12 412.12 180.00 180.00  
BASEMENT_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3957.66   0.00 90.00 N
RETAIL_1_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 134.14   0.00 90.00 N
RETAIL_2_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 155.34   0.00 90.00 N
MECH_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 328.49   0.00 90.00 N
STORAGE_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 189.52   0.00 90.00 N
LAUNDRY_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 156.08   0.00 90.00 N
CAFE_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 377.72   0.00 90.00 N
LOBBY_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 2616.37   0.00 90.00 N
ROOM_1_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.18   0.00 90.00 N
ROOM_2_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.14   0.00 90.00 N
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3727.63   0.00 90.00 N
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3728.64   0.00 90.00 N
ROOM_5_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.18   0.00 90.00 N
ROOM_6_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.14   0.00 90.00 N
CORRIDOR_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3115.24   0.00 90.00 N
ROOM_1_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 78.04   0.00 90.00 N
ROOM_2_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 78.03   0.00 90.00 N
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 441.55   0.00 90.00 N
BANQUET_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 663.31   0.00 90.00 N
DINING_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 663.31   0.00 90.00 N
KITCHEN_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 206.61   0.00 90.00 N
CORRIDOR_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 824.25   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.38_SHGC_0.36   23.26 0.00 0.00 23.26 23.26 2.159 0.361 0.397             No RETAIL_1_FLR_1_WALL_SOUTH 180.00 90.00 S
CAFE_FLR_1_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.38_SHGC_0.36   65.50 0.00 0.00 65.50 65.50 2.159 0.361 0.397             No CAFE_FLR_1_WALL_SOUTH 180.00 90.00 S
LOBBY_FLR_1_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.38_SHGC_0.36   85.08 0.00 0.00 85.08 85.08 2.159 0.361 0.397             No LOBBY_FLR_1_WALL_1_SOUTH 180.00 90.00 S
ROOM_1_FLR_3_WALL_SOUTH_WINDOW RESWINDOW_U_0.38_SHGC_0.36   4.60 0.00 0.00 4.60 18.40 2.159 0.361 0.397             No ROOM_1_FLR_3_WALL_SOUTH 180.00 90.00 S
ROOM_1_FLR_3_WALL_WEST_WINDOW RESWINDOW_U_0.38_SHGC_0.36   8.58 0.00 0.00 8.58 34.34 2.159 0.361 0.397             No ROOM_1_FLR_3_WALL_WEST 270.00 90.00 W
ROOM_2_FLR_3_WALL_NORTH_WINDOW RESWINDOW_U_0.38_SHGC_0.36   4.60 0.00 0.00 4.60 18.40 2.159 0.361 0.397             No ROOM_2_FLR_3_WALL_NORTH 0.00 90.00 N
ROOM_2_FLR_3_WALL_WEST_WINDOW RESWINDOW_U_0.38_SHGC_0.36   8.58 0.00 0.00 8.58 34.34 2.159 0.361 0.397             No ROOM_2_FLR_3_WALL_WEST 270.00 90.00 W
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW RESWINDOW_U_0.38_SHGC_0.36   3.68 0.00 0.00 3.68 279.56 2.159 0.361 0.397             No ROOM_3_MULT19_FLR_3_WALL_SOUTH 180.00 90.00 S
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW RESWINDOW_U_0.38_SHGC_0.36   3.68 0.00 0.00 3.68 279.65 2.159 0.361 0.397             No ROOM_4_MULT19_FLR_3_WALL_NORTH 0.00 90.00 N
ROOM_5_FLR_3_WALL_EAST_WINDOW RESWINDOW_U_0.38_SHGC_0.36   8.58 0.00 0.00 8.58 34.34 2.159 0.361 0.397             No ROOM_5_FLR_3_WALL_EAST 90.00 90.00 E
ROOM_5_FLR_3_WALL_SOUTH_WINDOW RESWINDOW_U_0.38_SHGC_0.36   4.60 0.00 0.00 4.60 18.40 2.159 0.361 0.397             No ROOM_5_FLR_3_WALL_SOUTH 180.00 90.00 S
ROOM_6_FLR_3_WALL_NORTH_WINDOW RESWINDOW_U_0.38_SHGC_0.36   4.60 0.00 0.00 4.60 18.40 2.159 0.361 0.397             No ROOM_6_FLR_3_WALL_NORTH 0.00 90.00 N
ROOM_6_FLR_3_WALL_EAST_WINDOW RESWINDOW_U_0.38_SHGC_0.36   8.58 0.00 0.00 8.58 34.34 2.159 0.361 0.397             No ROOM_6_FLR_3_WALL_EAST 90.00 90.00 E
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW NONRESWINDOW_U_0.38_SHGC_0.36   5.82 0.00 0.00 5.82 23.30 2.159 0.361 0.397             No CORRIDOR_FLR_3_WALL_1_NORTH 0.00 90.00 N
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW NONRESWINDOW_U_0.38_SHGC_0.36   2.15 0.00 0.00 2.15 8.59 2.159 0.361 0.397             No CORRIDOR_FLR_3_WALL_2_NORTH 0.00 90.00 N
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW NONRESWINDOW_U_0.38_SHGC_0.36   2.15 0.00 0.00 2.15 8.58 2.159 0.361 0.397             No CORRIDOR_FLR_3_WALL_1_SOUTH 180.00 90.00 S
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW NONRESWINDOW_U_0.38_SHGC_0.36   5.82 0.00 0.00 5.82 23.30 2.159 0.361 0.397             No CORRIDOR_FLR_3_WALL_2_SOUTH 180.00 90.00 S
ROOM_1_FLR_6_WALL_SOUTH_WINDOW RESWINDOW_U_0.38_SHGC_0.36   4.60 0.00 0.00 4.60 4.60 2.159 0.361 0.397             No ROOM_1_FLR_6_WALL_SOUTH 180.00 90.00 S
ROOM_1_FLR_6_WALL_WEST_WINDOW RESWINDOW_U_0.38_SHGC_0.36   8.58 0.00 0.00 8.58 8.58 2.159 0.361 0.397             No ROOM_1_FLR_6_WALL_WEST 270.00 90.00 W
ROOM_2_FLR_6_WALL_NORTH_WINDOW RESWINDOW_U_0.38_SHGC_0.36   4.60 0.00 0.00 4.60 4.60 2.159 0.361 0.397             No ROOM_2_FLR_6_WALL_NORTH 0.00 90.00 N
ROOM_2_FLR_6_WALL_WEST_WINDOW RESWINDOW_U_0.38_SHGC_0.36   8.58 0.00 0.00 8.58 8.58 2.159 0.361 0.397             No ROOM_2_FLR_6_WALL_WEST 270.00 90.00 W
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW RESWINDOW_U_0.38_SHGC_0.36   6.74 0.00 0.00 6.74 60.70 2.159 0.361 0.397             No ROOM_3_MULT9_FLR_6_WALL_SOUTH 180.00 90.00 S
BANQUET_FLR_6_WALL_NORTH_WINDOW NONRESWINDOW_U_0.38_SHGC_0.36   32.19 0.00 0.00 32.19 32.19 2.159 0.361 0.397             No BANQUET_FLR_6_WALL_NORTH 0.00 90.00 N
DINING_FLR_6_WALL_NORTH_WINDOW NONRESWINDOW_U_0.38_SHGC_0.36   32.19 0.00 0.00 32.19 32.19 2.159 0.361 0.397             No DINING_FLR_6_WALL_NORTH 0.00 90.00 N
KITCHEN_FLR_6_WALL_NORTH_WINDOW NONRESWINDOW_U_0.38_SHGC_0.36   4.60 0.00 0.00 4.60 4.60 2.159 0.361 0.397             No KITCHEN_FLR_6_WALL_NORTH 0.00 90.00 N
KITCHEN_FLR_6_WALL_EAST_WINDOW NONRESWINDOW_U_0.38_SHGC_0.36   17.17 0.00 0.00 17.17 17.17 2.159 0.361 0.397             No KITCHEN_FLR_6_WALL_EAST 90.00 90.00 E
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW NONRESWINDOW_U_0.38_SHGC_0.36   4.60 0.00 0.00 4.60 4.60 2.159 0.361 0.397             No KITCHEN_FLR_6_WALL_1_SOUTH 180.00 90.00 S
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW NONRESWINDOW_U_0.38_SHGC_0.36   5.82 0.00 0.00 5.82 5.82 2.159 0.361 0.397             No CORRIDOR_FLR_6_WALL_1_NORTH 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW NONRESWINDOW_U_0.38_SHGC_0.36   5.21 0.00 0.00 5.21 5.21 2.159 0.361 0.397             No CORRIDOR_FLR_6_WALL_2_NORTH 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW NONRESWINDOW_U_0.38_SHGC_0.36   17.17 0.00 0.00 17.17 17.17 2.159 0.361 0.397             No CORRIDOR_FLR_6_WALL_2_SOUTH 180.00 90.00 S
Total or Average             1213.79 2.159 0.361 0.397                      
North Total or Average             432.95 2.159 0.361 0.397                      
Non-North Total or Average             780.84 2.159 0.361 0.397                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
RETAIL_2_FLR_1_WALL_WEST_DOOR SWINGING DOOR_CON 2.101 3.065 1.95 RETAIL_2_FLR_1_WALL_WEST
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR OVERHEAD DOOR_CON 1.760 2.390 7.43 STORAGE_FLR_1_WALL_NORTH
LAUNDRY_FLR_1_WALL_EAST_DOOR SWINGING DOOR_CON 2.101 3.065 1.95 LAUNDRY_FLR_1_WALL_EAST
CAFE_FLR_1_WALL_EAST_DOOR SWINGING DOOR_CON 2.101 3.065 1.95 CAFE_FLR_1_WALL_EAST
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 SWINGING DOOR_CON 2.101 3.065 1.95 LOBBY_FLR_1_WALL_1_NORTH
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 SWINGING DOOR_CON 2.101 3.065 1.95 LOBBY_FLR_1_WALL_1_NORTH


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:35

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
CAFE_FLR_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
LOBBY_FLR_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
ROOM_1_FLR_3_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
ROOM_1_FLR_3_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_2_FLR_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
ROOM_5_FLR_3_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
ROOM_6_FLR_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
ROOM_1_FLR_6_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
ROOM_1_FLR_6_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_2_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
BANQUET_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
DINING_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:35

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
BASEMENT_LIGHTS BASEMENT BASEMENT GENERAL 8.8143 1978.83 17441.96 LightsWired LTG_SCH_BASEMENT 49.32 168.00 49.26 0.0000 Y 161.29
RETAIL_1_FLR_1_LIGHTS RETAIL_1_FLR_1 RETAIL_1_FLR_1 GENERAL 11.3140 67.07 758.85 LightsWired LTG_SCH_RETAIL 51.36 168.00 51.30 0.0000 Y 7.31
RETAIL_2_FLR_1_LIGHTS RETAIL_2_FLR_1 RETAIL_2_FLR_1 GENERAL 11.3140 77.67 878.75 LightsWired LTG_SCH_RETAIL 51.36 168.00 51.30 0.0000 Y 8.46
MECH_FLR_1_LIGHTS MECH_FLR_1 MECH_FLR_1 GENERAL 4.6285 164.24 760.20 LightsWired LTG_SCH_MECHANIC 58.69 168.00 58.63 0.0000 Y 8.37
STORAGE_FLR_1_LIGHTS STORAGE_FLR_1 STORAGE_FLR_1 GENERAL 5.7199 94.76 542.02 LightsWired LTG_SCH_STORAGE 30.30 168.00 30.27 0.0000 Y 3.08
LAUNDRY_FLR_1_LIGHTS LAUNDRY_FLR_1 LAUNDRY_FLR_1 GENERAL 4.6285 78.04 361.20 LightsWired LTG_SCH_LAUNDRY 58.69 168.00 58.63 0.0000 Y 3.98
CAFE_FLR_1_LIGHTS CAFE_FLR_1 CAFE_FLR_1 GENERAL 10.0104 188.86 1890.59 LightsWired LTG_SCH_DINING 58.69 168.00 40.13 0.0000 Y 14.24
LOBBY_FLR_1_LIGHTS LOBBY_FLR_1 LOBBY_FLR_1 GENERAL 10.7639 1308.19 14081.18 LightsWired LTG_SCH_LOBBY 44.02 168.00 41.68 0.0000 Y 110.17
ROOM_1_FLR_3_LIGHTS ROOM_1_FLR_3 ROOM_1_FLR_3 GENERAL 8.2882 156.09 1293.69 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 9.24
ROOM_2_FLR_3_LIGHTS ROOM_2_FLR_3 ROOM_2_FLR_3 GENERAL 8.2882 156.07 1293.54 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 9.24
ROOM_3_MULT19_FLR_3_LIGHTS ROOM_3_MULT19_FLR_3 ROOM_3_MULT19_FLR_3 GENERAL 8.2882 1863.81 15447.65 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 110.38
ROOM_4_MULT19_FLR_3_LIGHTS ROOM_4_MULT19_FLR_3 ROOM_4_MULT19_FLR_3 GENERAL 8.2882 1864.32 15451.87 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 110.41
ROOM_5_FLR_3_LIGHTS ROOM_5_FLR_3 ROOM_5_FLR_3 GENERAL 8.2882 156.09 1293.69 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 9.24
ROOM_6_FLR_3_LIGHTS ROOM_6_FLR_3 ROOM_6_FLR_3 GENERAL 8.2882 156.07 1293.54 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 9.24
CORRIDOR_FLR_3_LIGHTS CORRIDOR_FLR_3 CORRIDOR_FLR_3 GENERAL 7.1042 1557.62 11065.59 LightsWired LTG_SCH_CORRIDOR 44.02 168.00 43.97 0.0000 Y 91.33
ROOM_1_FLR_6_LIGHTS ROOM_1_FLR_6 ROOM_1_FLR_6 GENERAL 8.2882 39.02 323.42 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 2.31
ROOM_2_FLR_6_LIGHTS ROOM_2_FLR_6 ROOM_2_FLR_6 GENERAL 8.2882 39.02 323.38 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 2.31
ROOM_3_MULT9_FLR_6_LIGHTS ROOM_3_MULT9_FLR_6 ROOM_3_MULT9_FLR_6 GENERAL 8.2882 220.77 1829.83 LightsWired LTG_SCH_GUESTROOM 37.96 168.00 38.07 0.0000 Y 13.08
BANQUET_FLR_6_LIGHTS BANQUET_FLR_6 BANQUET_FLR_6 GENERAL 10.0104 331.66 3320.03 LightsWired LTG_SCH_DINING 58.69 168.00 49.75 0.0000 Y 31.01
DINING_FLR_6_LIGHTS DINING_FLR_6 DINING_FLR_6 GENERAL 10.0104 331.66 3320.03 LightsWired LTG_SCH_DINING 58.69 168.00 49.75 0.0000 Y 31.01
KITCHEN_FLR_6_LIGHTS KITCHEN_FLR_6 KITCHEN_FLR_6 GENERAL 11.4097 103.30 1178.68 LightsWired LTG_SCH_KITCHEN 58.69 168.00 58.63 0.0000 Y 12.97
CORRIDOR_FLR_6_LIGHTS CORRIDOR_FLR_6 CORRIDOR_FLR_6 GENERAL 7.1042 412.12 2927.80 LightsWired LTG_SCH_CORRIDOR 44.02 168.00 43.97 0.0000 Y 24.17
Interior Lighting Total       8.5566 11345.29 97077.49               457.10


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
LOBBY_FLR_1_DAYLREFPT1 LOBBY_FLR_1 LOBBY_FLR_1_DAYLCTRL SplitFlux Stepped 0.07 14081.18 985.68
LOBBY_FLR_1_DAYLREFPT2 LOBBY_FLR_1 LOBBY_FLR_1_DAYLCTRL SplitFlux Stepped 0.07 14081.18 985.68
CAFE_FLR_1_DAYLREFPT1 CAFE_FLR_1 CAFE_FLR_1_DAYLCTRL SplitFlux Stepped 0.39 1890.59 737.33
CAFE_FLR_1_DAYLREFPT2 CAFE_FLR_1 CAFE_FLR_1_DAYLCTRL SplitFlux Stepped 0.39 1890.59 737.33
DINING_FLR_6_DAYLREFPT1 DINING_FLR_6 DINING_FLR_6_DAYLCTRL SplitFlux Stepped 0.20 3320.03 664.01
DINING_FLR_6_DAYLREFPT2 DINING_FLR_6 DINING_FLR_6_DAYLCTRL SplitFlux Stepped 0.20 3320.03 664.01
BANQUET_FLR_6_DAYLREFPT1 BANQUET_FLR_6 BANQUET_FLR_6_DAYLCTRL SplitFlux Stepped 0.20 3320.03 664.01
BANQUET_FLR_6_DAYLREFPT2 BANQUET_FLR_6 BANQUET_FLR_6_DAYLCTRL SplitFlux Stepped 0.20 3320.03 664.01


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR FACADE LIGHTING 12338.45 AstronomicalClock -   83.55 83.55 193.50
Exterior Lighting Total 12338.45           193.50



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:35

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
HEATSYS1 BOILER Boiler:HotWater 375016.92 0.80        
COOLSYS1 CHILLER1 Chiller:Electric:EIR 753560.40 2.96 753560.40 2.96 4.09 13.95


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
ROOM_1_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 12904.59 19173.09 16554.96 2618.14 0.86 - 3802.76 38.57
ROOM_2_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 11715.90 17397.01 15010.27 2386.74 0.86 - 3444.30 34.93
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 89591.38 133833.60 116412.11 17421.49 0.87 - 27003.90 273.89
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 64262.48 93929.54 79454.82 14474.72 0.85 - 17795.61 180.49
ROOM_5_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 11674.44 17334.49 14955.26 2379.23 0.86 - 3431.33 34.80
ROOM_6_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 10687.84 15860.14 13672.81 2187.33 0.86 - 3133.69 31.78
ROOM_1_FLR_6 FAN COIL COOLING COIL Coil:Cooling:Water 3362.72 4997.35 4316.26 681.09 0.86 - 991.90 10.06
ROOM_2_FLR_6 FAN COIL COOLING COIL Coil:Cooling:Water 3031.09 4501.68 3884.97 616.71 0.86 - 891.75 9.04
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Coil:Cooling:Water 18612.38 27566.19 23705.54 3860.65 0.86 - 5414.39 54.92
FLR_3_DOAS COOLING COIL Coil:Cooling:Water 45447.84 49570.73 35167.84 14402.90 0.71 - 6912.11 70.11
VAV WITH REHEAT COOLING COIL Coil:Cooling:Water 481649.27 559090.64 394703.21 164387.43 0.71 - 88515.67 897.78
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
None              


DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
None                  


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
BASEMENT VAV BOX REHEAT COIL Coil:Heating:Water 6801.76 6836.93 -
RETAIL_1_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 3305.38 3320.71 -
RETAIL_2_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 1331.70 1338.11 -
MECH_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 1731.54 1739.03 -
STORAGE_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 1153.85 1158.69 -
LAUNDRY_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 10449.05 10502.58 -
CAFE_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 10115.52 10164.23 -
LOBBY_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 26217.27 26347.03 -
ROOM_1_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 4651.52 5009.85 -
ROOM_2_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 4654.79 5013.38 -
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 26893.42 28965.01 -
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 26967.92 29045.25 -
ROOM_5_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 4658.62 5017.50 -
ROOM_6_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 4661.89 5021.02 -
CORRIDOR_FLR_3 VAV BOX REHEAT COIL Coil:Heating:Water 11871.41 11926.58 -
ROOM_1_FLR_6 FAN COIL HEATING COIL Coil:Heating:Water 1427.71 1537.66 -
ROOM_2_FLR_6 FAN COIL HEATING COIL Coil:Heating:Water 1429.36 1539.44 -
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Coil:Heating:Water 6868.36 7397.33 -
BANQUET_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 10447.66 10499.52 -
DINING_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 10820.47 10874.23 -
KITCHEN_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 7057.59 7093.79 -
CORRIDOR_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 7206.92 7239.34 -
FLR_3_DOAS HEATING COIL Coil:Heating:Water 15340.96 11685.10 -
VAV WITH REHEAT HEATING COIL Coil:Heating:Water 168952.24 128689.70 -
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
LAUNDRY_FLR_1 EXHAUST FAN Fan:ZoneExhaust 0.39 125.00 0.24 76.61 324.68 1.00 2.78 General    
LOBBY_FLR_1 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.24 0.00 0.00 1.00 0.00 General    
ROOM_1_FLR_3 FAN COIL_FANCOILFAN Fan:OnOff 0.39 270.90 1.18 827.71 703.64 1.00 1.16 General SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00
ROOM_2_FLR_3 FAN COIL_FANCOILFAN Fan:OnOff 0.39 270.90 1.07 750.11 703.64 1.00 1.18 General SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 16:50:00
ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN Fan:OnOff 0.39 270.90 8.31 5848.75 703.64 1.00 0.94 General SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00
ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN Fan:OnOff 0.39 270.90 5.57 3915.77 703.64 1.00 0.96 General SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00
ROOM_5_FLR_3 FAN COIL_FANCOILFAN Fan:OnOff 0.39 270.90 1.06 747.33 703.64 1.00 1.18 General SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 10:00:00
ROOM_6_FLR_3 FAN COIL_FANCOILFAN Fan:OnOff 0.39 270.90 0.97 682.90 703.64 1.00 1.20 General SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 09:00:00
ROOM_1_FLR_6 FAN COIL_FANCOILFAN Fan:OnOff 0.39 270.90 0.31 215.84 703.64 1.00 1.70 General SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00
ROOM_2_FLR_6 FAN COIL_FANCOILFAN Fan:OnOff 0.39 270.90 0.28 194.17 703.64 1.00 1.77 General SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00
ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN Fan:OnOff 0.39 270.90 1.68 1182.03 703.64 1.00 1.09 General SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 13:40:00
BANQUET_FLR_6 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.87 0.00 0.00 1.00 0.00 General    
DINING_FLR_6 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.87 0.00 0.00 1.00 0.00 General    
KITCHEN_FLR_6 EXHAUST FAN Fan:ZoneExhaust 0.39 125.00 1.89 612.92 324.68 1.00 1.48 General    
FLR_3_DOAS FAN Fan:ConstantVolume 0.58 622.50 2.05 2194.93 1070.05 1.00 1.30 General SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00
VAV WITH REHEAT FAN Fan:VariableVolume 0.62 1389.42 22.59 50619.28 2240.64 1.00 1.11 General SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 13:40:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
COOLSYS1 PUMP SECONDARY Pump:VariableSpeed Intermittent 105797.75 0.021534 3515.82 163269.44 0.90 General
HEATSYS1 PUMP Pump:VariableSpeed Intermittent 180705.70 0.003281 988.04 301156.09 0.90 General
COOLSYS1 PUMP Pump:ConstantSpeed Intermittent 73247.35 0.021534 2434.12 113036.94 0.90 General
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 29891.00 0.000375 47.91 127739.32 0.30 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWH LAUNDRY G WATER HEATER WaterHeater:Mixed 1.14 163316.00 0.80 11.51 0.44
SWH BOOSTER E WATER HEATER WaterHeater:Mixed 0.02 8000.00 1.00 1.22 1.12
SWHSYS1 WATER HEATER WaterHeater:Mixed 2.27 175842.60 0.80 5.78 0.37



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:35

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 34561.47 34561.47 17.47 2.547 2.547 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 24.00 24.00 0.00920 25.86 0.00882 0.854 0.00
RETAIL_1_FLR_1 6002.75 6002.75 89.50 0.442 0.442 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 13:20:00 24.00 24.00 0.00891 29.05 0.00882 0.079 0.00
RETAIL_2_FLR_1 3147.80 3147.80 40.53 0.232 0.232 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:40:00 24.00 24.00 0.00940 28.98 0.00882 0.092 0.00
MECH_FLR_1 2361.19 2361.19 14.38 0.174 0.174 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:40:00 24.00 24.00 0.00876 28.98 0.00882 0.000 0.00
STORAGE_FLR_1 1403.26 1403.26 14.81 0.103 0.103 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 24.00 24.00 0.00883 29.40 0.00882 0.058 0.00
LAUNDRY_FLR_1 44601.97 44601.97 571.53 3.288 3.288 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 24.00 24.00 0.00854 29.40 0.00882 0.000 0.00
CAFE_FLR_1 23949.81 23949.81 126.81 1.767 1.767 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 13:20:00 24.00 23.99 0.00984 29.05 0.00882 0.676 0.00
LOBBY_FLR_1 69729.69 69729.69 53.30 5.142 5.142 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 13:40:00 24.00 23.99 0.00987 29.23 0.00882 1.894 0.00
ROOM_1_FLR_3 11843.54 11843.54 303.51 1.176 1.176 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00 21.11 21.11 0.00857 28.36 0.00882 0.062 0.00
ROOM_2_FLR_3 10733.21 10733.21 275.09 1.066 1.066 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 16:50:00 21.11 21.11 0.00857 28.08 0.00882 0.062 0.00
ROOM_3_MULT19_FLR_3 83692.74 83692.74 3412.71 8.312 8.312 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 21.11 21.11 0.00850 29.14 0.00882 0.837 0.00
ROOM_4_MULT19_FLR_3 56028.35 56028.35 2284.02 5.565 5.565 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 21.11 21.11 0.00876 29.40 0.00882 0.837 0.00
ROOM_5_FLR_3 10693.39 10693.39 274.03 1.062 1.062 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 10:00:00 21.11 21.11 0.00857 25.45 0.00882 0.062 0.00
ROOM_6_FLR_3 9771.45 9771.45 250.44 0.971 0.971 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 09:00:00 21.11 21.11 0.00858 23.68 0.00881 0.062 0.00
CORRIDOR_FLR_3 21808.50 21808.50 56.00 1.607 1.607 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 24.00 24.00 0.00937 29.40 0.00882 0.475 0.00
ROOM_1_FLR_6 3088.50 3088.50 79.15 0.307 0.307 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00 21.11 21.11 0.00856 28.36 0.00882 0.015 0.00
ROOM_2_FLR_6 2778.40 2778.40 71.21 0.276 0.276 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 21.11 21.11 0.00857 27.94 0.00882 0.015 0.00
ROOM_3_MULT9_FLR_6 16913.13 16913.13 689.47 1.680 1.680 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 13:40:00 21.11 21.11 0.00860 29.23 0.00882 0.099 0.00
BANQUET_FLR_6 28690.49 28690.49 86.51 2.117 2.117 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 24.00 23.98 0.01046 29.40 0.00882 1.188 0.00
DINING_FLR_6 30052.15 30052.15 90.61 2.218 2.218 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 24.00 23.99 0.01037 29.40 0.00882 1.188 0.00
KITCHEN_FLR_6 30735.30 30735.30 297.52 2.271 2.271 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 12:30:00 24.00 23.97 0.01008 28.46 0.00882 0.367 0.00
CORRIDOR_FLR_6 10909.83 10909.83 26.47 0.804 0.804 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 24.00 24.00 0.00896 29.40 0.00882 0.126 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 0.00 0.00 0.00 0.000 0.854 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.89 0.00269 -4.20 0.00269 0.854 0.00
RETAIL_1_FLR_1 2124.55 2124.55 31.68 0.092 0.092 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00774 -4.20 0.00269 0.079 0.00
RETAIL_2_FLR_1 712.48 712.48 9.17 0.031 0.092 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00770 -4.20 0.00269 0.092 0.00
MECH_FLR_1 1267.24 1267.24 7.72 0.055 0.055 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00761 -4.20 0.00269 0.000 0.00
STORAGE_FLR_1 877.88 877.88 9.26 0.038 0.058 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00767 -4.20 0.00269 0.058 0.00
LAUNDRY_FLR_1 1678.32 1678.32 21.51 0.073 0.073 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00760 -4.20 0.00269 0.000 0.00
CAFE_FLR_1 5400.13 5400.13 28.59 0.235 0.676 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00777 -4.20 0.00269 0.676 0.00
LOBBY_FLR_1 12496.36 12496.36 9.55 0.543 1.894 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00772 -4.20 0.00269 1.894 0.00
ROOM_1_FLR_3 4651.57 4651.57 119.20 0.203 0.203 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00772 -4.20 0.00269 0.062 0.00
ROOM_2_FLR_3 4654.85 4654.85 119.30 0.204 0.204 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00773 -4.20 0.00269 0.062 0.00
ROOM_3_MULT19_FLR_3 26893.56 26893.56 1096.63 1.176 1.176 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00775 -4.20 0.00269 0.837 0.00
ROOM_4_MULT19_FLR_3 26968.07 26968.07 1099.37 1.180 1.180 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00775 -4.20 0.00269 0.837 0.00
ROOM_5_FLR_3 4658.67 4658.67 119.39 0.204 0.204 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00773 -4.20 0.00269 0.062 0.00
ROOM_6_FLR_3 4661.95 4661.95 119.48 0.204 0.204 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00773 -4.20 0.00269 0.062 0.00
CORRIDOR_FLR_3 7581.23 7581.23 19.47 0.330 0.475 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00779 -4.20 0.00269 0.475 0.00
ROOM_1_FLR_6 1427.72 1427.72 36.59 0.062 0.062 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00777 -4.20 0.00269 0.015 0.00
ROOM_2_FLR_6 1429.37 1429.37 36.63 0.063 0.063 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00777 -4.20 0.00269 0.015 0.00
ROOM_3_MULT9_FLR_6 6868.42 6868.42 279.99 0.300 0.300 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00778 -4.20 0.00269 0.099 0.00
BANQUET_FLR_6 4796.26 4796.26 14.46 0.209 1.188 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00783 -4.20 0.00269 1.188 0.00
DINING_FLR_6 4901.05 4901.05 14.78 0.213 1.188 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 19:10:00 21.00 21.00 0.00784 -4.20 0.00269 1.188 0.00
KITCHEN_FLR_6 1026.40 1026.40 9.94 0.045 0.367 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 23:30:00 21.00 21.00 0.00541 -4.20 0.00269 0.367 0.00
CORRIDOR_FLR_6 5060.53 5060.53 12.28 0.220 0.220 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 19:10:00 21.00 21.00 0.00786 -4.20 0.00269 0.126 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
FLR_3_DOAS 19.16 2.05 3.60 2.05 2.0513 2.0513 2.0513 1.0000 0.3000
VAV WITH REHEAT 22.59 22.59 7.23 7.23 22.5915 11.6520 22.5915 0.5158 0.3000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
BASEMENT VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT BASEMENT VAV BOX 6801.763 6801.763 1.306858 0.00005950 141.839 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 6801.76 6801.76 1.306858 16.70 13.06 0.00800000 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00800000 50.9797 0.00 0.00 6839.99 6839.99
RETAIL_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_1_FLR_1 VAV BOX 3305.380 3305.380 0.226999 0.00002892 76.090 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3305.38 3305.38 0.226999 16.70 13.06 0.00800000 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00773838 49.3337 2124.55 0.00 3323.10 3323.10
RETAIL_2_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_2_FLR_1 VAV BOX 1331.695 1331.695 0.119040 0.00001165 29.539 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 1331.70 1331.70 0.119040 16.70 13.06 0.00800000 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00770095 49.0975 712.48 0.00 1338.93 1338.93
MECH_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT MECH_FLR_1 VAV BOX 1731.543 1731.543 0.089274 0.00001515 42.166 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 1731.54 1731.54 0.089274 16.70 13.06 0.00800000 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00760975 48.5232 1267.24 0.00 1740.55 1740.55
STORAGE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT STORAGE_FLR_1 VAV BOX 1153.847 1153.847 0.053056 0.00001009 28.923 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 1153.85 1153.85 0.053056 16.70 13.06 0.00800000 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00767103 48.9091 877.88 0.00 1159.79 1159.79
LAUNDRY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 10449.050 10449.050 1.686497 0.00009141 220.070 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 10449.05 10449.05 1.686497 16.70 13.06 0.00800000 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00759883 48.4548 1678.32 0.00 10507.57 10507.57
CAFE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CAFE_FLR_1 VAV BOX 10115.521 10115.521 0.906411 0.00008849 224.316 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 10115.52 10115.52 0.906411 16.70 13.06 0.00800000 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00777100 49.5390 5400.13 0.00 10170.51 10170.51
LOBBY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 26217.268 26217.268 2.637666 0.00022936 573.928 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 26217.27 26217.27 2.637666 16.70 13.06 0.00800000 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00771996 49.2173 12496.36 0.00 26362.38 26362.38
ROOM_1_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL 12904.592 -999.000 1.176326 0.00036906 -999.000 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00 unknown 8/21 16:30:00 12904.59 12702.77 1.176326 21.69 15.47 0.00856579 12.80 11.97 0.00850000 28.36 0.00881983 18.00 0.0000 21.11 0.00856579 54.1668 11843.54 0.00 13095.37 13095.37
ROOM_1_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL 4651.520 4651.520 0.203448 0.00004069 132.910 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 4651.52 4651.52 0.203448 21.11 14.50 0.00772493 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.11 0.00772493 48.9145 4651.57 0.00 5014.48 5014.48
ROOM_2_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL 11715.903 -999.000 1.066047 0.00033507 -999.000 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 16:50:00 unknown 8/21 16:50:00 11715.90 11514.70 1.066047 21.69 15.48 0.00857235 12.80 11.97 0.00850000 28.08 0.00881938 17.91 0.0000 21.11 0.00857235 54.2077 10733.21 0.00 11888.82 11888.82
ROOM_2_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL 4654.795 4654.795 0.203592 0.00004072 133.004 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 4654.79 4654.79 0.203592 21.11 14.50 0.00772514 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.11 0.00772514 48.9158 4654.85 0.00 5018.01 5018.01
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL 89591.379 -999.000 8.312172 0.00256225 -999.000 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 unknown 8/21 13:30:00 89591.38 89548.33 8.312172 21.69 15.42 0.00850199 12.80 11.97 0.00850000 29.14 0.00882108 18.26 0.0000 21.11 0.00850199 53.7675 83692.74 0.00 90923.28 90923.28
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL 26893.417 26893.417 1.176276 0.00023528 768.431 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 26893.42 26893.42 1.176276 21.11 14.52 0.00774669 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.11 0.00774669 49.0501 26893.56 0.00 28992.01 28992.01
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL 64262.482 -999.000 5.565044 0.00183786 -999.000 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 unknown 8/21 15:00:00 64262.48 60501.94 5.565044 21.69 15.64 0.00875736 12.80 11.97 0.00850000 29.40 0.00882150 18.34 0.0000 21.11 0.00875736 55.3623 56028.35 0.00 65190.74 63826.20
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL 26967.919 26967.919 1.179535 0.00023593 770.559 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 26967.92 26967.92 1.179535 21.11 14.52 0.00774729 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.11 0.00774729 49.0538 26968.07 0.00 29072.33 29072.33
ROOM_5_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL 11674.441 -999.000 1.062091 0.00033388 -999.000 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 10:00:00 unknown 8/21 10:00:00 11674.44 11472.23 1.062091 21.69 15.48 0.00857298 12.80 11.97 0.00850000 25.45 0.00881519 17.01 0.0000 21.11 0.00857298 54.2117 10693.39 0.00 11846.72 11846.72
ROOM_5_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL 4658.619 4658.619 0.203759 0.00004076 133.113 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 4658.62 4658.62 0.203759 21.11 14.50 0.00772533 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.11 0.00772533 48.9170 4658.67 0.00 5022.14 5022.14
ROOM_6_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL 10687.837 -999.000 0.970524 0.00030567 -999.000 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 09:00:00 unknown 8/21 09:00:00 10687.84 10485.79 0.970524 21.69 15.48 0.00857979 12.80 11.97 0.00850000 23.68 0.00881240 16.40 0.0000 21.11 0.00857979 54.2541 9771.45 0.00 10845.28 10845.28
ROOM_6_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL 4661.894 4661.894 0.203902 0.00004078 133.207 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 4661.89 4661.89 0.203902 21.11 14.50 0.00772554 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.11 0.00772554 48.9182 4661.95 0.00 5025.67 5025.67
CORRIDOR_FLR_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_3 VAV BOX 11871.415 11871.415 0.824615 0.00010386 272.775 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 11871.41 11871.41 0.824615 16.70 13.06 0.00800000 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00779186 49.6699 7581.23 0.00 11935.11 11935.11
ROOM_1_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL 3362.718 -999.000 0.306756 0.00009617 -999.000 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00 unknown 8/21 16:30:00 3362.72 3312.23 0.306756 21.69 15.47 0.00856311 12.80 11.97 0.00850000 28.36 0.00881983 18.00 0.0000 21.11 0.00856311 54.1500 3088.50 0.00 3412.47 3412.47
ROOM_1_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL 1427.705 1427.705 0.062445 0.00001249 40.793 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 1427.71 1427.71 0.062445 21.11 14.55 0.00777374 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.11 0.00777374 49.2197 1427.72 0.00 1539.11 1539.11
ROOM_2_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL 3031.088 -999.000 0.275957 0.00008669 -999.000 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 unknown 8/21 17:00:00 3031.09 2980.47 0.275957 21.69 15.48 0.00857032 12.80 11.97 0.00850000 27.94 0.00881916 17.86 0.0000 21.11 0.00857032 54.1950 2778.40 0.00 3075.85 3075.85
ROOM_2_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL 1429.357 1429.357 0.062517 0.00001250 40.841 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 1429.36 1429.36 0.062517 21.11 14.55 0.00777401 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.11 0.00777401 49.2214 1429.37 0.00 1540.89 1540.89
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL 18612.379 -999.000 1.679889 0.00053230 -999.000 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 13:40:00 unknown 8/21 13:40:00 18612.38 18164.43 1.679889 21.69 15.50 0.00860211 12.80 11.97 0.00850000 29.23 0.00882122 18.29 0.0000 21.11 0.00860211 54.3940 16913.13 0.00 18885.04 18885.04
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL 6868.363 6868.363 0.300410 0.00006009 196.247 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 6868.36 6868.36 0.300410 21.11 14.55 0.00778303 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.11 0.00778303 49.2776 6868.42 0.00 7404.31 7404.31
BANQUET_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 10447.659 10447.659 1.086187 0.00009140 227.939 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 10447.66 10447.66 1.086187 16.70 13.06 0.00800000 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00783265 49.9268 4796.26 0.00 10505.54 10505.54
DINING_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 10820.470 10820.470 1.137720 0.00009466 235.804 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 19:10:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 19:10:00 10820.47 10820.47 1.137720 16.70 13.06 0.00800000 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00783610 49.9488 4901.05 0.00 10880.43 10880.43
KITCHEN_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 7057.594 7057.594 1.165192 0.00006174 148.435 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 23:30:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 23:30:00 7057.59 7057.59 1.165192 16.70 13.06 0.00800000 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00540943 34.6207 1026.40 0.00 7097.14 7097.14
CORRIDOR_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_6 VAV BOX 7206.925 7206.925 0.412515 0.00006305 171.546 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 19:10:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 19:10:00 7206.92 7206.92 0.412515 16.70 13.06 0.00800000 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00786026 50.1007 5060.53 0.00 7245.20 7245.20
FLR_3_DOAS COOLING COIL Coil:Cooling:Water AirLoopHVAC FLR_3_DOAS 45447.837 -999.000 2.051317 0.00129980 -999.000 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 45447.84 43504.21 2.051317 29.40 18.34 0.00882150 11.92 11.61 0.00850000 29.40 0.00882150 18.34 99.9965 21.11 0.00860544 54.4137 192922.69 0.00 45917.97 43441.59
FLR_3_DOAS HEATING COIL Coil:Heating:Water AirLoopHVAC FLR_3_DOAS 15340.965 15340.965 0.615395 0.00013421 261.904 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 15340.96 15340.96 0.615395 -4.20 -4.20 0.00269032 16.70 13.06 0.00800000 -4.20 0.00269032 -4.20 333.3216 21.11 0.00774716 49.0530 82214.19 0.00 14133.30 14133.30
VAV WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV WITH REHEAT 481649.266 -999.000 22.591451 0.01377511 -999.000 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 13:40:00 481649.27 432061.98 22.591451 26.78 17.79 0.00920731 10.95 10.95 0.00850000 29.40 0.00882150 18.34 51.6189 23.99 0.00957604 50.7488 306177.77 0.00 487018.06 422262.48
VAV WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV WITH REHEAT 168952.241 168952.241 6.777435 0.00147807 2884.391 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 19:30:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 19:30:00 168952.24 168952.24 6.777435 -4.20 -4.20 0.00269032 16.70 13.06 0.00800000 -4.20 0.00269032 -4.20 172.0630 21.21 0.00661006 41.6679 47220.32 0.00 155652.07 155652.07



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2024-07-03 12:21:35

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
BASEMENT VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT BASEMENT VAV BOX BASEMENT N/A N/A N/A Yes Yes Yes No 6801.763 6801.763 1.306858 0.00005950 141.839 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.28047697 54.44 82.22 27.78 382564.29 1.7779 1.813722 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 6801.76 6801.76 1.0000 1.55122827 1.306858 16.70 13.06 0.00800000 37036.7 40.00 21.01 0.00800000 60796.0 0.05949872 60.00 32.22 27.78 0.000 6801.76 -4.20 0.00269032 -4.20 0.00000000 0.0000 21.00 0.00800000 21.00 0.00800000 50.9797 0.00 0.00 6839.99 6839.99 1.55122827 16.60 13.15 0.00800000 36934.7 20.92 14.82 0.00800000 41344.1
RETAIL_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_1_FLR_1 VAV BOX RETAIL_1_FLR_1 N/A N/A N/A Yes Yes Yes No 3305.380 3305.380 0.226999 0.00002892 76.090 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.28047697 54.44 82.22 27.78 382564.29 0.8640 0.881395 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 3305.38 3305.38 1.0000 0.26944582 0.226999 16.70 13.06 0.00800000 37036.7 40.00 21.01 0.00800000 60796.0 0.02891396 60.00 32.22 27.78 0.000 3305.38 -4.20 0.00269032 -4.20 0.00000000 0.0000 21.00 0.00773838 21.00 0.00773838 49.3337 2124.55 0.00 3323.10 3323.10 0.26944582 16.60 13.15 0.00800000 36934.7 28.69 17.60 0.00800000 49267.8
RETAIL_2_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_2_FLR_1 VAV BOX RETAIL_2_FLR_1 N/A N/A N/A Yes Yes Yes No 1331.695 1331.695 0.119040 0.00001165 29.539 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.28047697 54.44 82.22 27.78 382564.29 0.3481 0.355103 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 1331.70 1331.70 1.0000 0.14129891 0.119040 16.70 13.06 0.00800000 37036.7 40.00 21.01 0.00800000 60796.0 0.01164906 60.00 32.22 27.78 0.000 1331.70 -4.20 0.00269032 -4.20 0.00000000 0.0000 21.00 0.00770095 21.00 0.00770095 49.0975 712.48 0.00 1338.93 1338.93 0.14129891 16.60 13.15 0.00800000 36934.7 25.89 16.63 0.00800000 46410.6
MECH_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT MECH_FLR_1 VAV BOX MECH_FLR_1 N/A N/A N/A Yes Yes Yes No 1731.543 1731.543 0.089274 0.00001515 42.166 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.28047697 54.44 82.22 27.78 382564.29 0.4526 0.461724 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 1731.54 1731.54 1.0000 0.10596684 0.089274 16.70 13.06 0.00800000 37036.7 40.00 21.01 0.00800000 60796.0 0.01514674 60.00 32.22 27.78 0.000 1731.54 -4.20 0.00269032 -4.20 0.00000000 0.0000 21.00 0.00760975 21.00 0.00760975 48.5232 1267.24 0.00 1740.55 1740.55 0.10596684 16.60 13.15 0.00800000 36934.7 32.71 18.93 0.00800000 53360.1
STORAGE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT STORAGE_FLR_1 VAV BOX STORAGE_FLR_1 N/A N/A N/A Yes Yes Yes No 1153.847 1153.847 0.053056 0.00001009 28.923 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.28047697 54.44 82.22 27.78 382564.29 0.3016 0.307679 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 1153.85 1153.85 1.0000 0.06297677 0.053056 16.70 13.06 0.00800000 37036.7 40.00 21.01 0.00800000 60796.0 0.01009333 60.00 32.22 27.78 0.000 1153.85 -4.20 0.00269032 -4.20 0.00000000 0.0000 21.00 0.00767103 21.00 0.00767103 48.9091 877.88 0.00 1159.79 1159.79 0.06297677 16.60 13.15 0.00800000 36934.7 34.66 19.55 0.00800000 55350.9
LAUNDRY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown LAUNDRY_FLR_1 N/A N/A N/A Yes Yes Yes No 10449.050 10449.050 1.686497 0.00009141 220.070 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.28047697 54.44 82.22 27.78 382564.29 2.7313 2.786288 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 10449.05 10449.05 1.0000 2.00185598 1.686497 16.70 13.06 0.00800000 37036.7 40.00 21.01 0.00800000 60796.0 0.09140352 60.00 32.22 27.78 0.000 10449.05 -4.20 0.00269032 -4.20 0.00000000 0.0000 21.00 0.00759883 21.00 0.00759883 48.4548 1678.32 0.00 10507.57 10507.57 2.00185598 16.60 13.15 0.00800000 36934.7 21.75 15.13 0.00800000 42183.6
CAFE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CAFE_FLR_1 VAV BOX CAFE_FLR_1 N/A N/A N/A Yes Yes Yes No 10115.521 10115.521 0.906411 0.00008849 224.316 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.28047697 54.44 82.22 27.78 382564.29 2.6441 2.697351 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 10115.52 10115.52 1.0000 1.07590121 0.906411 16.70 13.06 0.00800000 37036.7 40.00 21.01 0.00800000 60796.0 0.08848596 60.00 32.22 27.78 0.000 10115.52 -4.20 0.00269032 -4.20 0.00000000 0.0000 21.00 0.00777100 21.00 0.00777100 49.5390 5400.13 0.00 10170.51 10170.51 1.07590121 16.60 13.15 0.00800000 36934.7 25.87 16.62 0.00800000 46387.8
LOBBY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown LOBBY_FLR_1 N/A N/A N/A Yes Yes Yes No 26217.268 26217.268 2.637666 0.00022936 573.928 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.28047697 54.44 82.22 27.78 382564.29 6.8530 6.990956 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 26217.27 26217.27 1.0000 3.13088476 2.637666 16.70 13.06 0.00800000 37036.7 40.00 21.01 0.00800000 60796.0 0.22933670 60.00 32.22 27.78 0.000 26217.27 -4.20 0.00269032 -4.20 0.00000000 0.0000 21.00 0.00771996 21.00 0.00771996 49.2173 12496.36 0.00 26362.38 26362.38 3.13088476 16.60 13.15 0.00800000 36934.7 24.86 16.26 0.00800000 45354.8
ROOM_1_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL ROOM_1_FLR_3 N/A N/A N/A Yes Yes Yes No 12904.592 -999.000 1.176326 0.00036906 -999.000 -999.0000 1.00000 1.00000 1020.7634 1004.8586 1.1870 ROOM_1_FLR_3 FAN COIL_FANCOILFAN Fan:OnOff 1.176326 1.39628853   4197.9300 999.8980 21.53166916 15.03 6.70 8.33 752935.70 1.7139 1.713872 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00 unknown unknown unknown 8/21 16:30:00 Sensible 12904.59 12702.77 1.0000 1.39628853 1.176326 21.69 15.47 0.00856579 43564.3 12.80 11.97 0.00850000 34322.2 0.36902517 6.70 15.03 8.33 0.000 12904.59 28.36 0.00881983 18.00 0.00000000 0.0000 21.11 0.00856579 21.11 0.00856579 54.1668 11843.54 0.00 13095.37 13095.37 1.39628853 21.69 15.62 0.00856579 43564.3 12.50 12.04 0.00856579 34185.6
ROOM_1_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL ROOM_1_FLR_3 N/A N/A N/A Yes Yes Yes No 4651.520 4651.520 0.203448 0.00004069 132.910 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 ROOM_1_FLR_3 FAN COIL_FANCOILFAN Fan:OnOff 1.176326 1.39628853   4197.9300 999.8980 3.28047697 54.44 82.22 27.78 382564.29 1.2159 1.240349 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 4651.52 4651.52 1.0000 0.24149148 0.203448 21.11 14.50 0.00772493 40835.6 40.00 21.01 0.00800000 60796.0 0.04068937 60.00 32.22 27.78 0.000 4651.52 -4.20 0.00269032 -4.20 0.00000000 0.0000 21.11 0.00772493 21.11 0.00772493 48.9145 4651.57 0.00 5014.48 5014.48 0.24149148 16.60 12.88 0.00772493 36238.3 36.97 20.06 0.00772493 57003.0
ROOM_2_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL ROOM_2_FLR_3 N/A N/A N/A Yes Yes Yes No 11715.903 -999.000 1.066047 0.00033507 -999.000 -999.0000 1.00000 1.00000 1020.7756 1004.8586 1.1870 ROOM_2_FLR_3 FAN COIL_FANCOILFAN Fan:OnOff 1.066047 1.26538853   4197.9300 999.8980 21.53166916 15.03 6.70 8.33 752935.70 1.5560 1.556001 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 16:50:00 unknown unknown unknown 8/21 16:50:00 Sensible 11715.90 11514.70 1.0000 1.26538853 1.066047 21.69 15.48 0.00857235 43580.9 12.80 11.97 0.00850000 34322.2 0.33503291 6.70 15.03 8.33 0.000 11715.90 28.08 0.00881938 17.91 0.00000000 0.0000 21.11 0.00857235 21.11 0.00857235 54.2077 10733.21 0.00 11888.82 11888.82 1.26538853 21.69 15.62 0.00857235 43580.9 12.49 12.04 0.00857235 34185.5
ROOM_2_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL ROOM_2_FLR_3 N/A N/A N/A Yes Yes Yes No 4654.795 4654.795 0.203592 0.00004072 133.004 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 ROOM_2_FLR_3 FAN COIL_FANCOILFAN Fan:OnOff 1.066047 1.26538853   4197.9300 999.8980 3.28047697 54.44 82.22 27.78 382564.29 1.2167 1.241223 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 4654.79 4654.79 1.0000 0.24166151 0.203592 21.11 14.50 0.00772514 40836.2 40.00 21.01 0.00800000 60796.0 0.04071802 60.00 32.22 27.78 0.000 4654.79 -4.20 0.00269032 -4.20 0.00000000 0.0000 21.11 0.00772514 21.11 0.00772514 48.9158 4654.85 0.00 5018.01 5018.01 0.24166151 16.60 12.88 0.00772514 36238.8 36.97 20.06 0.00772514 57003.5
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL ROOM_3_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 89591.379 -999.000 8.312172 0.00256225 -999.000 -999.0000 1.00000 1.00000 1020.6448 1004.8586 1.1870 ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN Fan:OnOff 8.312172 9.86647102   4197.9300 999.8980 21.53166916 15.03 6.70 8.33 752935.70 11.8989 11.898719 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 unknown unknown unknown 8/21 13:30:00 Sensible 89591.38 89548.33 1.0000 9.86647102 8.312172 21.69 15.42 0.00850199 43402.6 12.80 11.97 0.00850000 34322.2 2.56199287 6.70 15.03 8.33 0.000 89591.38 29.14 0.00882108 18.26 0.00000000 0.0000 21.11 0.00850199 21.11 0.00850199 53.7675 83692.74 0.00 90923.28 90923.28 9.86647102 21.69 15.56 0.00850199 43402.6 12.66 12.05 0.00850199 34187.2
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL ROOM_3_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 26893.417 26893.417 1.176276 0.00023528 768.431 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN Fan:OnOff 8.312172 9.86647102   4197.9300 999.8980 3.28047697 54.44 82.22 27.78 382564.29 7.0298 7.171254 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 26893.42 26893.42 1.0000 1.39622878 1.176276 21.11 14.52 0.00774669 40891.1 40.00 21.01 0.00800000 60796.0 0.23525134 60.00 32.22 27.78 0.000 26893.42 -4.20 0.00269032 -4.20 0.00000000 0.0000 21.11 0.00774669 21.11 0.00774669 49.0501 26893.56 0.00 28992.01 28992.01 1.39622878 16.60 12.90 0.00774669 36293.4 36.97 20.08 0.00774669 57057.9
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL ROOM_4_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 64262.482 -999.000 5.565044 0.00183786 -999.000 -999.0000 1.00000 1.00000 1021.1195 1004.8586 1.1870 ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN Fan:OnOff 5.565044 6.60565594   4197.9300 999.8980 21.53166916 15.03 6.70 8.33 752935.70 8.5349 8.534764 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 unknown unknown unknown 8/21 15:00:00 Sensible 64262.48 60501.94 1.0000 6.60565594 5.565044 21.69 15.64 0.00875736 44050.6 12.80 11.97 0.00850000 34322.2 1.83767706 6.70 15.03 8.33 0.000 64262.48 29.40 0.00882150 18.34 0.00000000 0.0000 21.11 0.00875736 21.11 0.00875736 55.3623 56028.35 0.00 65190.74 63826.20 6.60565594 21.69 15.78 0.00875736 44050.6 12.23 12.04 0.00867550 34181.7
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL ROOM_4_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 26967.919 26967.919 1.179535 0.00023593 770.559 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN Fan:OnOff 5.565044 6.60565594   4197.9300 999.8980 3.28047697 54.44 82.22 27.78 382564.29 7.0493 7.191120 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 26967.92 26967.92 1.0000 1.40009672 1.179535 21.11 14.52 0.00774729 40892.6 40.00 21.01 0.00800000 60796.0 0.23590305 60.00 32.22 27.78 0.000 26967.92 -4.20 0.00269032 -4.20 0.00000000 0.0000 21.11 0.00774729 21.11 0.00774729 49.0538 26968.07 0.00 29072.33 29072.33 1.40009672 16.60 12.90 0.00774729 36294.9 36.97 20.08 0.00774729 57059.4
ROOM_5_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL ROOM_5_FLR_3 N/A N/A N/A Yes Yes Yes No 11674.441 -999.000 1.062091 0.00033388 -999.000 -999.0000 1.00000 1.00000 1020.7768 1004.8586 1.1870 ROOM_5_FLR_3 FAN COIL_FANCOILFAN Fan:OnOff 1.062091 1.26069220   4197.9300 999.8980 21.53166916 15.03 6.70 8.33 752935.70 1.5505 1.550494 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 10:00:00 unknown unknown unknown 8/21 10:00:00 Sensible 11674.44 11472.23 1.0000 1.26069220 1.062091 21.69 15.48 0.00857298 43582.5 12.80 11.97 0.00850000 34322.2 0.33384723 6.70 15.03 8.33 0.000 11674.44 25.45 0.00881519 17.01 0.00000000 0.0000 21.11 0.00857298 21.11 0.00857298 54.2117 10693.39 0.00 11846.72 11846.72 1.26069220 21.69 15.62 0.00857298 43582.5 12.49 12.04 0.00857298 34185.5
ROOM_5_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL ROOM_5_FLR_3 N/A N/A N/A Yes Yes Yes No 4658.619 4658.619 0.203759 0.00004076 133.113 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 ROOM_5_FLR_3 FAN COIL_FANCOILFAN Fan:OnOff 1.062091 1.26069220   4197.9300 999.8980 3.28047697 54.44 82.22 27.78 382564.29 1.2177 1.242242 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 4658.62 4658.62 1.0000 0.24186007 0.203759 21.11 14.50 0.00772533 40836.6 40.00 21.01 0.00800000 60796.0 0.04075148 60.00 32.22 27.78 0.000 4658.62 -4.20 0.00269032 -4.20 0.00000000 0.0000 21.11 0.00772533 21.11 0.00772533 48.9170 4658.67 0.00 5022.14 5022.14 0.24186007 16.60 12.88 0.00772533 36239.3 36.97 20.06 0.00772533 57004.0
ROOM_6_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL ROOM_6_FLR_3 N/A N/A N/A Yes Yes Yes No 10687.837 -999.000 0.970524 0.00030567 -999.000 -999.0000 1.00000 1.00000 1020.7894 1004.8586 1.1870 ROOM_6_FLR_3 FAN COIL_FANCOILFAN Fan:OnOff 0.970524 1.15200247   4197.9300 999.8980 21.53166916 15.03 6.70 8.33 752935.70 1.4195 1.419462 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 09:00:00 unknown unknown unknown 8/21 09:00:00 Sensible 10687.84 10485.79 1.0000 1.15200247 0.970524 21.69 15.48 0.00857979 43599.8 12.80 11.97 0.00850000 34322.2 0.30563389 6.70 15.03 8.33 0.000 10687.84 23.68 0.00881240 16.40 0.00000000 0.0000 21.11 0.00857979 21.11 0.00857979 54.2541 9771.45 0.00 10845.28 10845.28 1.15200247 21.69 15.63 0.00857979 43599.8 12.47 12.04 0.00857979 34185.5
ROOM_6_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL ROOM_6_FLR_3 N/A N/A N/A Yes Yes Yes No 4661.894 4661.894 0.203902 0.00004078 133.207 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 ROOM_6_FLR_3 FAN COIL_FANCOILFAN Fan:OnOff 0.970524 1.15200247   4197.9300 999.8980 3.28047697 54.44 82.22 27.78 382564.29 1.2186 1.243116 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 4661.89 4661.89 1.0000 0.24203006 0.203902 21.11 14.50 0.00772554 40837.2 40.00 21.01 0.00800000 60796.0 0.04078012 60.00 32.22 27.78 0.000 4661.89 -4.20 0.00269032 -4.20 0.00000000 0.0000 21.11 0.00772554 21.11 0.00772554 48.9182 4661.95 0.00 5025.67 5025.67 0.24203006 16.60 12.88 0.00772554 36239.8 36.97 20.06 0.00772554 57004.5
CORRIDOR_FLR_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_3 VAV BOX CORRIDOR_FLR_3 N/A N/A N/A Yes Yes Yes No 11871.415 11871.415 0.824615 0.00010386 272.775 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.28047697 54.44 82.22 27.78 382564.29 3.1031 3.165568 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 11871.41 11871.41 1.0000 0.97881036 0.824615 16.70 13.06 0.00800000 37036.7 40.00 21.01 0.00800000 60796.0 0.10384572 60.00 32.22 27.78 0.000 11871.41 -4.20 0.00269032 -4.20 0.00000000 0.0000 21.00 0.00779186 21.00 0.00779186 49.6699 7581.23 0.00 11935.11 11935.11 0.97881036 16.60 13.15 0.00800000 36934.7 28.56 17.55 0.00800000 49128.2
ROOM_1_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL ROOM_1_FLR_6 N/A N/A N/A Yes Yes Yes No 3362.718 -999.000 0.306756 0.00009617 -999.000 -999.0000 1.00000 1.00000 1020.7584 1004.8586 1.1870 ROOM_1_FLR_6 FAN COIL_FANCOILFAN Fan:OnOff 0.306756 0.36411693   4197.9300 999.8980 21.53166916 15.03 6.70 8.33 752935.70 0.4466 0.446606 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00 unknown unknown unknown 8/21 16:30:00 Sensible 3362.72 3312.23 1.0000 0.36411693 0.306756 21.69 15.47 0.00856311 43557.5 12.80 11.97 0.00850000 34322.2 0.09616169 6.70 15.03 8.33 0.000 3362.72 28.36 0.00881983 18.00 0.00000000 0.0000 21.11 0.00856311 21.11 0.00856311 54.1500 3088.50 0.00 3412.47 3412.47 0.36411693 21.69 15.61 0.00856311 43557.5 12.51 12.04 0.00856311 34185.6
ROOM_1_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL ROOM_1_FLR_6 N/A N/A N/A Yes Yes Yes No 1427.705 1427.705 0.062445 0.00001249 40.793 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 ROOM_1_FLR_6 FAN COIL_FANCOILFAN Fan:OnOff 0.306756 0.36411693   4197.9300 999.8980 3.28047697 54.44 82.22 27.78 382564.29 0.3732 0.380704 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 1427.71 1427.71 1.0000 0.07412174 0.062445 21.11 14.55 0.00777374 40959.6 40.00 21.01 0.00800000 60796.0 0.01248892 60.00 32.22 27.78 0.000 1427.71 -4.20 0.00269032 -4.20 0.00000000 0.0000 21.11 0.00777374 21.11 0.00777374 49.2197 1427.72 0.00 1539.11 1539.11 0.07412174 16.60 12.93 0.00777374 36361.9 36.97 20.10 0.00777374 57126.5
ROOM_2_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL ROOM_2_FLR_6 N/A N/A N/A Yes Yes Yes No 3031.088 -999.000 0.275957 0.00008669 -999.000 -999.0000 1.00000 1.00000 1020.7718 1004.8586 1.1870 ROOM_2_FLR_6 FAN COIL_FANCOILFAN Fan:OnOff 0.275957 0.32755854   4197.9300 999.8980 21.53166916 15.03 6.70 8.33 752935.70 0.4026 0.402562 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 unknown unknown unknown 8/21 17:00:00 Sensible 3031.09 2980.47 1.0000 0.32755854 0.275957 21.69 15.48 0.00857032 43575.8 12.80 11.97 0.00850000 34322.2 0.08667827 6.70 15.03 8.33 0.000 3031.09 27.94 0.00881916 17.86 0.00000000 0.0000 21.11 0.00857032 21.11 0.00857032 54.1950 2778.40 0.00 3075.85 3075.85 0.32755854 21.69 15.62 0.00857032 43575.8 12.49 12.04 0.00857032 34185.6
ROOM_2_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL ROOM_2_FLR_6 N/A N/A N/A Yes Yes Yes No 1429.357 1429.357 0.062517 0.00001250 40.841 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 ROOM_2_FLR_6 FAN COIL_FANCOILFAN Fan:OnOff 0.275957 0.32755854   4197.9300 999.8980 3.28047697 54.44 82.22 27.78 382564.29 0.3736 0.381145 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 1429.36 1429.36 1.0000 0.07420746 0.062517 21.11 14.55 0.00777401 40960.3 40.00 21.01 0.00800000 60796.0 0.01250336 60.00 32.22 27.78 0.000 1429.36 -4.20 0.00269032 -4.20 0.00000000 0.0000 21.11 0.00777401 21.11 0.00777401 49.2214 1429.37 0.00 1540.89 1540.89 0.07420746 16.60 12.93 0.00777401 36362.6 36.97 20.10 0.00777401 57127.2
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL ROOM_3_MULT9_FLR_6 N/A N/A N/A Yes Yes Yes No 18612.379 -999.000 1.679889 0.00053230 -999.000 -999.0000 1.00000 1.00000 1020.8309 1004.8586 1.1870 ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN Fan:OnOff 1.679889 1.99401223   4197.9300 999.8980 21.53166916 15.03 6.70 8.33 752935.70 2.4720 2.471928 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 13:40:00 unknown unknown unknown 8/21 13:40:00 Sensible 18612.38 18164.43 1.0000 1.99401223 1.679889 21.69 15.50 0.00860211 43656.3 12.80 11.97 0.00850000 34322.2 0.53224744 6.70 15.03 8.33 0.000 18612.38 29.23 0.00882122 18.29 0.00000000 0.0000 21.11 0.00860211 21.11 0.00860211 54.3940 16913.13 0.00 18885.04 18885.04 1.99401223 21.69 15.65 0.00860211 43656.3 12.41 12.04 0.00860211 34185.5
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL ROOM_3_MULT9_FLR_6 N/A N/A N/A Yes Yes Yes No 6868.363 6868.363 0.300410 0.00006009 196.247 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN Fan:OnOff 1.679889 1.99401223   4197.9300 999.8980 3.28047697 54.44 82.22 27.78 382564.29 1.7953 1.831481 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 6868.36 6868.36 1.0000 0.35658369 0.300410 21.11 14.55 0.00778303 40983.3 40.00 21.01 0.00800000 60796.0 0.06008131 60.00 32.22 27.78 0.000 6868.36 -4.20 0.00269032 -4.20 0.00000000 0.0000 21.11 0.00778303 21.11 0.00778303 49.2776 6868.42 0.00 7404.31 7404.31 0.35658369 16.60 12.94 0.00778303 36385.4 36.97 20.11 0.00778303 57150.0
BANQUET_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown BANQUET_FLR_6 N/A N/A N/A Yes Yes Yes No 10447.659 10447.659 1.086187 0.00009140 227.939 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.28047697 54.44 82.22 27.78 382564.29 2.7310 2.785917 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 10447.66 10447.66 1.0000 1.28929405 1.086187 16.70 13.06 0.00800000 37036.7 40.00 21.01 0.00800000 60796.0 0.09139136 60.00 32.22 27.78 0.000 10447.66 -4.20 0.00269032 -4.20 0.00000000 0.0000 21.00 0.00783265 21.00 0.00783265 49.9268 4796.26 0.00 10505.54 10505.54 1.28929405 16.60 13.15 0.00800000 36934.7 24.59 16.17 0.00800000 45083.0
DINING_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown DINING_FLR_6 N/A N/A N/A Yes Yes Yes No 10820.470 10820.470 1.137720 0.00009466 235.804 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.28047697 54.44 82.22 27.78 382564.29 2.8284 2.885328 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 19:10:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 19:10:00 Sensible 10820.47 10820.47 1.0000 1.35046356 1.137720 16.70 13.06 0.00800000 37036.7 40.00 21.01 0.00800000 60796.0 0.09465254 60.00 32.22 27.78 0.000 10820.47 -4.20 0.00269032 -4.20 0.00000000 0.0000 21.00 0.00783610 21.00 0.00783610 49.9488 4901.05 0.00 10880.43 10880.43 1.35046356 16.60 13.15 0.00800000 36934.7 24.50 16.14 0.00800000 44991.5
KITCHEN_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown KITCHEN_FLR_6 N/A N/A N/A Yes Yes Yes No 7057.594 7057.594 1.165192 0.00006174 148.435 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.28047697 54.44 82.22 27.78 382564.29 1.8448 1.881940 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 23:30:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 23:30:00 Sensible 7057.59 7057.59 1.0000 1.38307250 1.165192 16.70 13.06 0.00800000 37036.7 40.00 21.01 0.00800000 60796.0 0.06173661 60.00 32.22 27.78 0.000 7057.59 -4.20 0.00269032 -4.20 0.00000000 0.0000 19.93 0.00540943 21.00 0.00540943 34.6207 1026.40 0.00 7097.14 7097.14 1.38307250 16.60 13.15 0.00800000 36934.7 21.63 15.09 0.00800000 42066.2
CORRIDOR_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_6 VAV BOX CORRIDOR_FLR_6 N/A N/A N/A Yes Yes Yes No 7206.925 7206.925 0.412515 0.00006305 171.546 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.28047697 54.44 82.22 27.78 382564.29 1.8838 1.921760 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 19:10:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 19:10:00 Sensible 7206.92 7206.92 1.0000 0.48965162 0.412515 16.70 13.06 0.00800000 37036.7 40.00 21.01 0.00800000 60796.0 0.06304289 60.00 32.22 27.78 0.000 7206.92 -4.20 0.00269032 -4.20 0.00000000 0.0000 21.00 0.00786026 21.00 0.00786026 50.1007 5060.53 0.00 7245.20 7245.20 0.48965162 16.60 13.15 0.00800000 36934.7 31.11 18.41 0.00800000 51731.4
FLR_3_DOAS COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC FLR_3_DOAS ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 45447.837 -999.000 2.051317 0.00129980 -999.000 -999.0000 1.00000 1.00000 1021.2387 1004.8586 1.1870 FLR_3_DOAS FAN Fan:ConstantVolume 2.051245 2.43480905   4197.9300 999.8980 21.53166916 15.03 6.70 8.33 752935.70 6.0361 6.036085 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 Sensible 45447.84 43504.21 1.0000 2.43489466 2.051317 29.40 18.34 0.00882150 52086.5 11.92 11.61 0.00850000 33421.2 1.29966980 6.70 15.03 8.33 2195.006 43252.83 29.40 0.00882150 18.34 2.05124512 99.9965 21.11 0.00860263 21.11 0.00860544 54.4137 192922.69 0.00 45917.97 43441.59 2.43489466 29.40 18.50 0.00882150 52086.5 11.93 11.66 0.00841841 33228.2
FLR_3_DOAS HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC FLR_3_DOAS ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 15340.965 15340.965 0.615395 0.00013421 261.904 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 FLR_3_DOAS FAN Fan:ConstantVolume 2.051245 2.43480905   4197.9300 999.8980 3.28047697 54.44 82.22 27.78 382564.29 4.0100 4.090739 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 15340.96 15340.96 1.0000 0.73046840 0.615395 -4.20 -4.20 0.00269032 2487.0 16.70 13.06 0.00800000 37036.7 0.13419576 60.00 32.22 27.78 0.000 15340.96 -4.20 0.00269032 -4.20 2.05124512 333.3216 21.11 0.00774601 21.11 0.00774716 49.0530 82214.19 0.00 14133.30 14133.30 0.73046840 2.80 0.07 0.00269032 9555.9 21.96 9.93 0.00269032 28904.2
VAV WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV WITH REHEAT BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 481649.266 -999.000 22.591451 0.01377511 -999.000 -999.0000 1.00000 1.00000 1021.9559 1004.8586 1.1870 VAV WITH REHEAT FAN Fan:VariableVolume 22.591451 26.81584376   4197.9300 999.8980 21.53166916 15.03 6.70 8.33 752935.70 63.9695 63.969508 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 13:40:00 Sensible 481649.27 432061.98 1.0000 26.81584376 22.591451 26.78 17.79 0.00920731 50398.3 10.95 10.95 0.00850000 32437.0 13.77370282 6.70 15.03 8.33 50619.277 431029.99 29.40 0.00882150 18.34 11.66146000 51.6189 23.99 0.00961928 23.99 0.00957604 50.7488 306177.77 0.00 487018.06 422262.48 26.81584376 26.78 17.94 0.00920731 50398.3 11.37 11.25 0.00824983 32236.8
VAV WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV WITH REHEAT BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 168952.241 168952.241 6.777435 0.00147807 2884.391 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 VAV WITH REHEAT FAN Fan:VariableVolume 22.591451 26.81584376   4197.9300 999.8980 3.28047697 54.44 82.22 27.78 382564.29 44.1631 45.051898 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 19:30:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 19:30:00 Sensible 168952.24 168952.24 1.0000 8.04475313 6.777435 -4.20 -4.20 0.00269032 2487.0 16.70 13.06 0.00800000 37036.7 1.47791713 60.00 32.22 27.78 0.000 168952.24 -4.20 0.00269032 -4.20 11.66146000 172.0630 18.45 0.00706731 21.21 0.00661006 41.6679 47220.32 0.00 155652.07 155652.07 8.04475313 2.80 0.07 0.00269032 9555.9 21.96 9.93 0.00269032 28904.2



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:35

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
FLR_3_DOAS_OA_CONTROLLER DifferentialDryBulb 2.05 2.05 -      
VAV WITH REHEAT_OA_CONTROLLER DifferentialDryBulb 0.00 22.59 -      


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
BASEMENT VAV WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
RETAIL_1_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.001181 0.000000 0.000000 Flow/Area   1.00 1.00  
RETAIL_2_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.001181 0.000000 0.000000 Flow/Area   1.00 1.00  
MECH_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.000000 0.000000 0.000000 Flow/Area   1.00 1.00  
STORAGE_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.000610 0.000000 0.000000 Flow/Area   1.00 1.00  
LAUNDRY_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.000000 0.000000 0.000000 Flow/Area   1.00 1.00  
CAFE_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.003581 0.000000 0.000000 Flow/Area   1.00 1.00  
LOBBY_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.001448 0.000000 0.000000 Flow/Area   1.00 1.00  
CORRIDOR_FLR_3 VAV WITH REHEAT_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  
BANQUET_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.003581 0.000000 0.000000 Flow/Area   1.00 1.00  
DINING_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.003581 0.000000 0.000000 Flow/Area   1.00 1.00  
KITCHEN_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.003556 0.000000 0.000000 Flow/Area   1.00 1.00  
CORRIDOR_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
BASEMENT 56.33 7634.83 0.00
RETAIL_1_FLR_1 967.17 8035.83 538.33
RETAIL_2_FLR_1 368.17 7658.83 0.00
MECH_FLR_1 39.17 8596.00 35.67
STORAGE_FLR_1 119.50 8735.50 119.50
LAUNDRY_FLR_1 7308.83 3229.33 2579.83
CAFE_FLR_1 1138.83 6900.00 44.50
LOBBY_FLR_1 1043.67 6487.50 32.67
ROOM_1_FLR_3 1008.50 8433.50 974.33
ROOM_2_FLR_3 1775.33 8169.83 1479.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 201.50 8747.17 201.33
ROOM_5_FLR_3 980.67 8443.33 977.83
ROOM_6_FLR_3 1533.17 8408.67 1449.50
CORRIDOR_FLR_3 24.17 8755.33 24.17
ROOM_1_FLR_6 1827.67 8320.33 1741.17
ROOM_2_FLR_6 2663.83 8089.00 2323.00
ROOM_3_MULT9_FLR_6 596.33 8214.67 523.00
BANQUET_FLR_6 4423.17 1732.00 39.50
DINING_FLR_6 5855.83 765.83 21.33
KITCHEN_FLR_6 8532.33 6234.83 6218.83
CORRIDOR_FLR_6 165.83 8345.00 45.50
Facility 8757.00 8760.00 7073.50
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
BASEMENT 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 0.00 0.00 0.00 0.00
MECH_FLR_1 0.00 0.00 0.00 0.00
STORAGE_FLR_1 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 0.00 0.00 0.00 0.00
CAFE_FLR_1 0.00 0.00 0.00 0.00
LOBBY_FLR_1 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 4.50 3.17 4.50 3.17
ROOM_2_FLR_3 9.00 6.83 9.00 6.83
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 0.00 12.17 0.00 12.17
ROOM_5_FLR_3 5.17 0.00 5.17 0.00
ROOM_6_FLR_3 12.17 7.33 12.17 7.33
CORRIDOR_FLR_3 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 7.33 6.67 7.33 6.67
ROOM_2_FLR_6 16.00 13.33 16.00 13.33
ROOM_3_MULT9_FLR_6 1.83 1.67 1.83 1.67
BANQUET_FLR_6 0.00 0.00 0.00 0.00
DINING_FLR_6 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 0.00 0.00 0.00 0.00
Facility 18.83 30.00 18.83 30.00
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:35

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 61.76 106.50 4826.41 1.001 0.000 0.000 0.000
RETAIL_1_FLR_1 6.28 10.83 265.76 3.130 0.062 0.000 0.000
RETAIL_2_FLR_1 7.27 12.54 307.76 1.424 0.021 0.000 0.000
MECH_FLR_1 1.54 2.65 650.80 0.501 0.023 0.000 0.000
STORAGE_FLR_1 1.18 2.04 375.47 0.516 0.023 0.000 0.000
LAUNDRY_FLR_1 4.87 8.40 309.22 23.331 0.067 0.000 0.000
CAFE_FLR_1 82.52 142.30 748.35 4.453 0.049 0.000 0.000
LOBBY_FLR_1 244.96 422.44 5183.56 1.880 0.020 0.000 0.000
ROOM_1_FLR_3 0.95 1.50 118.94 0.355 0.080 0.000 0.042
ROOM_2_FLR_3 0.95 1.50 118.93 0.356 0.081 0.000 0.040
ROOM_3_MULT19_FLR_3   1.50 74.75        
ROOM_4_MULT19_FLR_3 0.95 1.50 74.77 0.403 0.036 0.000 0.075
ROOM_5_FLR_3 0.95 1.50 118.94 0.355 0.080 0.000 0.042
ROOM_6_FLR_3 0.95 1.50 118.93 0.355 0.080 0.000 0.048
CORRIDOR_FLR_3 12.15 20.96 1186.91 0.634 0.010 0.000 0.000
ROOM_1_FLR_6 0.95 1.50 118.94 0.355 0.080 0.000 0.049
ROOM_2_FLR_6 0.95 1.50 118.93 0.356 0.081 0.000 0.042
ROOM_3_MULT9_FLR_6 0.95 1.50 74.77 0.403 0.066 0.000 0.079
BANQUET_FLR_6 144.91 249.90 1010.89 4.756 0.023 0.000 0.000
DINING_FLR_6 144.91 249.90 1010.89 5.184 0.023 0.000 0.000
KITCHEN_FLR_6 12.90 22.24 314.87 22.117 0.067 0.000 0.000
CORRIDOR_FLR_6 12.86 22.18 1256.16 1.199 0.016 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 61.76 106.50 4826.41 0.966 0.000 0.000 0.000
RETAIL_1_FLR_1 6.28 10.83 265.76 3.027 0.001 0.000 0.000
RETAIL_2_FLR_1 7.27 12.54 307.76 1.373 0.000 0.000 0.000
MECH_FLR_1 1.54 2.65 650.80 0.486 0.000 0.000 0.000
STORAGE_FLR_1 1.18 2.04 375.47 0.501 0.000 0.000 0.000
LAUNDRY_FLR_1 4.87 8.40 309.22 19.394 0.001 0.000 0.000
CAFE_FLR_1 82.52 142.30 748.35 4.294 0.001 0.000 0.000
LOBBY_FLR_1 244.96 422.44 5183.56 1.806 0.000 0.000 0.000
ROOM_1_FLR_3 0.95 1.50 118.94 0.000 0.001 0.000 0.000
ROOM_2_FLR_3 0.95 1.50 118.93 0.000 0.001 0.000 0.000
ROOM_3_MULT19_FLR_3   1.50 74.75        
ROOM_4_MULT19_FLR_3 0.95 1.50 74.77 0.000 0.001 0.000 0.000
ROOM_5_FLR_3 0.95 1.50 118.94 0.000 0.001 0.000 0.000
ROOM_6_FLR_3 0.95 1.50 118.93 0.000 0.001 0.000 0.000
CORRIDOR_FLR_3 12.15 20.96 1186.91 0.616 0.000 0.000 0.000
ROOM_1_FLR_6 0.95 1.50 118.94 0.000 0.001 0.000 0.000
ROOM_2_FLR_6 0.95 1.50 118.93 0.000 0.001 0.000 0.000
ROOM_3_MULT9_FLR_6 0.95 1.50 74.77 0.000 0.001 0.000 0.000
BANQUET_FLR_6 144.91 249.90 1010.89 3.832 0.000 0.000 0.000
DINING_FLR_6 144.91 249.90 1010.89 4.019 0.000 0.000 0.000
KITCHEN_FLR_6 12.90 22.24 314.87 13.231 0.001 0.000 0.000
CORRIDOR_FLR_6 12.86 22.18 1256.16 1.164 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2024-07-03 12:21:35

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
BASEMENT VAV WITH REHEAT 61.76 106.50 4826.41 1978.83 0.0000 0.854
RETAIL_1_FLR_1 VAV WITH REHEAT 6.28 10.83 265.76 67.07 0.0000 0.079
RETAIL_2_FLR_1 VAV WITH REHEAT 7.27 12.54 307.76 77.67 0.0000 0.092
MECH_FLR_1 VAV WITH REHEAT 1.54 2.65 650.80 164.24 0.0000 0.000
STORAGE_FLR_1 VAV WITH REHEAT 1.18 2.04 375.47 94.76 0.0000 0.058
LAUNDRY_FLR_1 VAV WITH REHEAT 4.87 8.40 309.22 78.04 0.0000 0.000
CAFE_FLR_1 VAV WITH REHEAT 82.52 142.30 748.35 188.86 0.0000 0.676
LOBBY_FLR_1 VAV WITH REHEAT 244.96 422.44 5183.56 1308.19 0.0000 1.894
ROOM_1_FLR_3 FLR_3_DOAS 0.95 1.50 118.94 39.02 0.0000 0.062
ROOM_2_FLR_3 FLR_3_DOAS 0.95 1.50 118.93 39.02 0.0000 0.062
ROOM_3_MULT19_FLR_3 FLR_3_DOAS   1.50 74.75 24.52 0.0000 0.837
ROOM_4_MULT19_FLR_3 FLR_3_DOAS 0.95 1.50 74.77 24.53 0.0000 0.837
ROOM_5_FLR_3 FLR_3_DOAS 0.95 1.50 118.94 39.02 0.0000 0.062
ROOM_6_FLR_3 FLR_3_DOAS 0.95 1.50 118.93 39.02 0.0000 0.062
CORRIDOR_FLR_3 VAV WITH REHEAT 12.15 20.96 1186.91 389.40 0.0000 0.475
ROOM_1_FLR_6 FLR_3_DOAS 0.95 1.50 118.94 39.02 0.0000 0.015
ROOM_2_FLR_6 FLR_3_DOAS 0.95 1.50 118.93 39.02 0.0000 0.015
ROOM_3_MULT9_FLR_6 FLR_3_DOAS 0.95 1.50 74.77 24.53 0.0000 0.099
BANQUET_FLR_6 VAV WITH REHEAT 144.91 249.90 1010.89 331.66 0.0000 1.188
DINING_FLR_6 VAV WITH REHEAT 144.91 249.90 1010.89 331.66 0.0000 1.188
KITCHEN_FLR_6 VAV WITH REHEAT 12.90 22.24 314.87 103.30 0.0000 0.367
CORRIDOR_FLR_6 VAV WITH REHEAT 12.86 22.18 1256.16 412.12 0.0000 0.126
Total Facility   872.83 1604.23 35184.81 11345.29 0.0000 137.584


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
BASEMENT 41514557.94 0.00 41514557.94 0.00 41514557.94 26946214.98 0.00 0.00 8760.00 0.00
RETAIL_1_FLR_1 7195756.99 0.00 7195756.99 142406.96 7338163.95 2498216.28 0.00 0.00 8760.00 0.00
RETAIL_2_FLR_1 3774271.31 0.00 3774271.31 54969.27 3829240.58 2892943.94 0.00 0.00 8760.00 0.00
MECH_FLR_1 2815957.39 0.00 2815957.39 129914.69 2945872.08 0.00 0.00 0.00 8760.00 0.00
STORAGE_FLR_1 1673168.38 0.00 1673168.38 74953.62 1748122.00 1821682.01 8760.00 0.00 0.00 0.00
LAUNDRY_FLR_1 62066829.84 0.00 62066829.84 177391.88 62244221.72 0.00 0.00 0.00 8760.00 0.00
CAFE_FLR_1 28706709.60 0.00 28706709.60 314798.65 29021508.25 21330615.53 0.00 0.00 8760.00 0.00
LOBBY_FLR_1 83783214.31 0.00 83783214.31 899451.65 84682665.96 59728886.00 0.00 0.00 8760.00 0.00
ROOM_1_FLR_3 1460156.71 43586.13 1503742.85 82657.34 1586400.19 1946875.62 2190.00 6018.50 551.50 0.00
ROOM_2_FLR_3 1459985.63 41153.94 1501139.58 82651.04 1583790.62 1946647.51 2190.00 6122.98 447.02 0.00
ROOM_3_MULT19_FLR_3 1099911.97 66.61 1099978.58 23062.33 1123040.90 26397887.27 8395.00 365.00 0.00 365.83
ROOM_4_MULT19_FLR_3 19803829.30 48066.93 19851896.23 23068.63 19874964.86 26405105.73 2190.00 6028.17 541.83 0.00
ROOM_5_FLR_3 1460156.71 43546.31 1503703.03 82657.34 1586360.37 1946875.62 2190.00 6018.50 551.50 0.00
ROOM_6_FLR_3 1459985.63 48793.52 1508779.15 82651.04 1591430.19 1946647.51 2190.00 6019.17 550.83 0.00
CORRIDOR_FLR_3 26005057.44 0.00 26005057.44 99949.36 26105006.80 14972100.18 0.00 0.00 8760.00 0.00
ROOM_1_FLR_6 365039.18 50872.72 415911.90 82674.64 498586.54 486718.90 2074.00 6019.43 666.58 0.00
ROOM_2_FLR_6 364996.41 42956.52 407952.93 82668.33 490621.26 486661.88 2105.15 6165.50 489.35 0.00
ROOM_3_MULT9_FLR_6 2345190.31 50798.26 2395988.57 42299.24 2438287.81 3126920.42 2190.00 6017.83 552.17 0.00
BANQUET_FLR_6 41157191.91 0.00 41157191.91 201870.69 41359062.60 37458366.31 3745.91 166.68 4847.41 0.00
DINING_FLR_6 44855404.40 0.00 44855404.40 201870.69 45057275.09 37458366.31 2490.13 208.01 6061.86 0.00
KITCHEN_FLR_6 59648498.48 0.00 59648498.48 180721.07 59829219.55 11584760.86 0.00 0.00 8760.00 0.00
CORRIDOR_FLR_6 13013445.54 0.00 13013445.54 176879.70 13190325.25 3961413.96 0.00 0.00 8760.00 0.00
Total Facility 0.21E+10 4917482.31 0.21E+10 8329482.29 0.21E+10 0.43E+10 8760.00 6685.45 8760.00 365.83


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
BASEMENT 1.3164 0.0000 1.3164 0.0000 1.3164 0.8545 0.00 0.00 8760.00
RETAIL_1_FLR_1 0.2282 0.0000 0.2282 0.0045 0.2327 0.0792 0.00 0.00 8760.00
RETAIL_2_FLR_1 0.1197 0.0000 0.1197 0.0017 0.1214 0.0917 0.00 0.00 8760.00
MECH_FLR_1 0.0893 0.0000 0.0893 0.0041 0.0934 0.0000 0.00 0.00 8760.00
STORAGE_FLR_1 0.0531 0.0000 0.0531 0.0024 0.0554 0.0578 8760.00 0.00 0.00
LAUNDRY_FLR_1 1.9681 0.0000 1.9681 0.0056 1.9738 0.0000 0.00 0.00 8760.00
CAFE_FLR_1 0.9103 0.0000 0.9103 0.0100 0.9203 0.6764 0.00 0.00 8760.00
LOBBY_FLR_1 2.6567 0.0000 2.6567 0.0285 2.6853 1.8940 0.00 0.00 8760.00
ROOM_1_FLR_3 0.0463 0.0014 0.0477 0.0026 0.0503 0.0617 2190.00 6018.50 551.50
ROOM_2_FLR_3 0.0463 0.0013 0.0476 0.0026 0.0502 0.0617 2190.00 6122.98 447.02
ROOM_4_MULT19_FLR_3 0.6280 0.0015 0.6295 0.0007 0.6302 0.8373 2190.00 6028.17 541.83
ROOM_5_FLR_3 0.0463 0.0014 0.0477 0.0026 0.0503 0.0617 2190.00 6018.50 551.50
ROOM_6_FLR_3 0.0463 0.0015 0.0478 0.0026 0.0505 0.0617 2190.00 6019.17 550.83
CORRIDOR_FLR_3 0.8246 0.0000 0.8246 0.0032 0.8278 0.4748 0.00 0.00 8760.00
ROOM_1_FLR_6 0.0116 0.0016 0.0132 0.0026 0.0158 0.0154 2074.00 6019.43 666.58
ROOM_2_FLR_6 0.0116 0.0014 0.0129 0.0026 0.0156 0.0154 2105.15 6165.50 489.35
ROOM_3_MULT9_FLR_6 0.0744 0.0016 0.0760 0.0013 0.0773 0.0992 2190.00 6017.83 552.17
BANQUET_FLR_6 1.3051 0.0000 1.3051 0.0064 1.3115 1.1878 3745.91 166.68 4847.41
DINING_FLR_6 1.4224 0.0000 1.4224 0.0064 1.4288 1.1878 2490.13 208.01 6061.86
KITCHEN_FLR_6 1.8914 0.0000 1.8914 0.0057 1.8972 0.3674 0.00 0.00 8760.00
CORRIDOR_FLR_6 0.4127 0.0000 0.4127 0.0056 0.4183 0.1256 0.00 0.00 8760.00
Total Facility 64.8311 0.1558 64.9869 0.2085 65.1954 73.9670 8760.00 6685.45 8760.00


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
FLR_3_DOAS 42013749.02 369840.95 42383589.97 64690340.46 8754.17 4.95 0.88 0.00
VAV WITH REHEAT 0.59E+09 0.00 0.59E+09 0.22E+09 0.00 0.00 8760.00 0.00


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
FLR_3_DOAS 1.3322 0.0117 1.3440 2.0513 8754.17 4.95 0.88
VAV WITH REHEAT 18.5952 0.0000 18.5952 6.9969 0.00 0.00 8760.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
FLR_3_DOAS 0.00 0.00 0.00 0.00 6935.00 0.00 0.00 0.00 0.00 0.00
VAV WITH REHEAT 0.00 0.00 5342.21 0.00 0.00 0.00 3417.79 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
FLR_3_DOAS 0.0000 0.0000 0.0000 0.0000 1.6828 0.0000 0.0000 0.0000 0.0000 0.0000
VAV WITH REHEAT 0.0000 0.0000 18.7453 0.0000 0.0000 0.0000 18.3659 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:35

Surfaces by Class

Total Outdoors
Wall 119 44
Floor 25 0
Roof 33 11
Internal Mass 22 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 30 30
Door 6 6
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 2
Conditioned Zones 22
Unconditioned Zones 0
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 1333
Defaulted Fields 1182
Fields with Defaults 4000
Autosized Fields 349
Autosizable Fields 402
Autocalculated Fields 280
Autocalculatable Fields 539



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2024-07-03 12:21:35

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 4606.71 66637.43 05-AUG-05:00 335399.91 10-AUG-18:10
Electricity:Building 2448.13 31038.54 01-JUL-05:00 151313.73 02-JAN-20:10
Electricity:Zone:BASEMENT 304.40 3493.55 02-JAN-02:10 22822.84 02-JAN-20:10
Electricity:SpaceType:GENERAL 2441.03 30897.39 01-JUL-05:00 151072.40 02-JAN-20:10
InteriorLights:Electricity 782.86 6695.42 01-JUL-05:00 64632.59 02-JAN-20:10
InteriorLights:Electricity:Zone:BASEMENT 161.29 1465.65 02-JAN-02:10 13190.31 02-JAN-20:10
InteriorLights:Electricity:SpaceType:GENERAL 782.86 6695.42 01-JUL-05:00 64632.59 02-JAN-20:10
LightsWired:InteriorLights:Electricity 782.86 6695.42 01-JUL-05:00 64632.59 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:BASEMENT 161.29 1465.65 02-JAN-02:10 13190.31 02-JAN-20:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 782.86 6695.42 01-JUL-05:00 64632.59 02-JAN-20:10
Electricity:Zone:RETAIL_1_FLR_1 17.49 210.74 02-JAN-02:10 1283.20 02-JAN-20:10
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 7.31 66.40 02-JAN-02:10 597.59 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 7.31 66.40 02-JAN-02:10 597.59 02-JAN-20:10
Electricity:Zone:RETAIL_2_FLR_1 20.26 244.03 02-JAN-02:10 1485.95 02-JAN-20:10
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 8.46 76.89 02-JAN-02:10 692.02 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 8.46 76.89 02-JAN-02:10 692.02 02-JAN-20:10
Electricity:Zone:MECH_FLR_1 20.84 252.75 02-JAN-02:10 1523.62 02-JAN-20:10
InteriorLights:Electricity:Zone:MECH_FLR_1 8.37 76.02 02-JAN-02:10 684.18 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 8.37 76.02 02-JAN-02:10 684.18 02-JAN-20:10
Electricity:Zone:STORAGE_FLR_1 6.68 78.96 02-JAN-02:10 493.99 02-JAN-20:10
InteriorLights:Electricity:Zone:STORAGE_FLR_1 3.08 27.98 02-JAN-02:10 251.84 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 3.08 27.98 02-JAN-02:10 251.84 02-JAN-20:10
Electricity:Zone:LAUNDRY_FLR_1 71.91 998.82 02-JAN-02:10 4897.88 02-JAN-20:10
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 3.98 36.12 02-JAN-02:10 325.08 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 3.98 36.12 02-JAN-02:10 325.08 02-JAN-20:10
Electricity:Zone:CAFE_FLR_1 28.58 293.96 03-JUN-05:00 2666.80 02-JAN-20:10
InteriorLights:Electricity:Zone:CAFE_FLR_1 14.24 83.19 01-JAN-13:10 1701.53 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 14.24 83.19 01-JAN-13:10 1701.53 02-JAN-20:10
Electricity:Zone:LOBBY_FLR_1 259.17 3068.93 01-JUL-05:00 19534.01 02-JAN-20:10
InteriorLights:Electricity:Zone:LOBBY_FLR_1 110.17 957.52 01-JUL-05:00 9504.80 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 110.17 957.52 01-JUL-05:00 9504.80 02-JAN-20:10
Electricity:Zone:ROOM_1_FLR_3 19.72 257.38 01-JAN-02:10 1438.51 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 9.24 78.27 01-JAN-02:10 711.53 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 9.24 78.27 01-JAN-02:10 711.53 01-JAN-19:10
Electricity:Zone:ROOM_2_FLR_3 19.72 257.35 01-JAN-02:10 1438.34 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 9.24 78.26 01-JAN-02:10 711.45 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 9.24 78.26 01-JAN-02:10 711.45 01-JAN-19:10
Electricity:Zone:ROOM_3_MULT19_FLR_3 305.38 4267.82 01-JAN-02:10 22404.45 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 110.39 934.58 01-JAN-02:10 8496.21 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 110.39 934.58 01-JAN-02:10 8496.21 01-JAN-19:10
Electricity:Zone:ROOM_4_MULT19_FLR_3 305.47 4268.99 01-JAN-02:10 22410.58 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 110.42 934.84 01-JAN-02:10 8498.53 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 110.42 934.84 01-JAN-02:10 8498.53 01-JAN-19:10
Electricity:Zone:ROOM_5_FLR_3 19.72 257.38 01-JAN-02:10 1438.51 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 9.24 78.27 01-JAN-02:10 711.53 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 9.24 78.27 01-JAN-02:10 711.53 01-JAN-19:10
Electricity:Zone:ROOM_6_FLR_3 19.72 257.35 01-JAN-02:10 1438.34 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 9.24 78.26 01-JAN-02:10 711.45 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 9.24 78.26 01-JAN-02:10 711.45 01-JAN-19:10
Electricity:Zone:CORRIDOR_FLR_3 91.34 829.92 02-JAN-02:10 7469.27 02-JAN-20:10
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 91.34 829.92 02-JAN-02:10 7469.27 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 91.34 829.92 02-JAN-02:10 7469.27 02-JAN-20:10
Electricity:Zone:ROOM_1_FLR_6 4.93 64.34 01-JAN-02:10 359.63 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 2.31 19.57 01-JAN-02:10 177.88 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 2.31 19.57 01-JAN-02:10 177.88 01-JAN-19:10
Electricity:Zone:ROOM_2_FLR_6 4.93 64.34 01-JAN-02:10 359.59 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 2.31 19.56 01-JAN-02:10 177.86 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 2.31 19.56 01-JAN-02:10 177.86 01-JAN-19:10
Electricity:Zone:ROOM_3_MULT9_FLR_6 36.17 505.54 01-JAN-02:10 2653.88 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 13.08 110.70 01-JAN-02:10 1006.40 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 13.08 110.70 01-JAN-02:10 1006.40 01-JAN-19:10
Electricity:Zone:BANQUET_FLR_6 206.86 2448.50 10-JUN-05:00 9735.93 02-JAN-20:10
InteriorLights:Electricity:Zone:BANQUET_FLR_6 31.01 199.20 10-JUN-05:00 2988.03 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 31.01 199.20 10-JUN-05:00 2988.03 02-JAN-20:10
Electricity:Zone:DINING_FLR_6 206.86 2448.50 10-JUN-05:00 9735.93 02-JAN-20:10
InteriorLights:Electricity:Zone:DINING_FLR_6 31.01 199.20 10-JUN-05:00 2988.03 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 31.01 199.20 10-JUN-05:00 2988.03 02-JAN-20:10
Electricity:Zone:KITCHEN_FLR_6 453.81 6249.79 02-JAN-02:10 18934.39 01-JAN-11:10
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 12.97 117.87 02-JAN-02:10 1060.81 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 12.97 117.87 02-JAN-02:10 1060.81 02-JAN-20:10
Electricity:Zone:CORRIDOR_FLR_6 24.17 219.59 02-JAN-02:10 1976.27 02-JAN-20:10
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 24.17 219.59 02-JAN-02:10 1976.27 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 24.17 219.59 02-JAN-02:10 1976.27 02-JAN-20:10
InteriorEquipment:Electricity 1658.18 24201.97 02-JAN-02:10 89171.45 02-JAN-07:10
InteriorEquipment:Electricity:Zone:BASEMENT 143.11 2027.90 02-JAN-02:10 9632.53 02-JAN-20:10
InteriorEquipment:Electricity:SpaceType:GENERAL 1658.18 24201.97 02-JAN-02:10 89171.45 02-JAN-07:10
MiscPlug:InteriorEquipment:Electricity 872.72 13712.59 02-JAN-02:10 59188.31 02-JAN-07:10
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT 143.11 2027.90 02-JAN-02:10 9632.53 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 872.72 13712.59 02-JAN-02:10 59188.31 02-JAN-07:10
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 10.19 144.34 02-JAN-02:10 685.60 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 10.19 144.34 02-JAN-02:10 685.60 02-JAN-20:10
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 11.79 167.14 02-JAN-02:10 793.93 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 11.79 167.14 02-JAN-02:10 793.93 02-JAN-20:10
InteriorEquipment:Electricity:Zone:MECH_FLR_1 12.47 176.73 02-JAN-02:10 839.45 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 12.47 176.73 02-JAN-02:10 839.45 02-JAN-20:10
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 3.60 50.98 02-JAN-02:10 242.16 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 3.60 50.98 02-JAN-02:10 242.16 02-JAN-20:10
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 67.94 962.69 02-JAN-02:10 4572.80 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 67.94 962.69 02-JAN-02:10 4572.80 02-JAN-20:10
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 14.34 203.22 02-JAN-02:10 965.27 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 14.34 203.22 02-JAN-02:10 965.27 02-JAN-20:10
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 149.00 2111.41 02-JAN-02:10 10029.21 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 149.00 2111.41 02-JAN-02:10 10029.21 02-JAN-20:10
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 10.48 126.43 02-JAN-10:10 948.23 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 10.48 126.43 02-JAN-10:10 948.23 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 10.48 126.42 02-JAN-10:10 948.12 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 10.48 126.42 02-JAN-10:10 948.12 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 195.00 2352.88 02-JAN-10:10 17646.57 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 195.00 2352.88 02-JAN-10:10 17646.57 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 195.05 2353.52 02-JAN-10:10 17651.40 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 195.05 2353.52 02-JAN-10:10 17651.40 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 10.48 126.43 02-JAN-10:10 948.23 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 10.48 126.43 02-JAN-10:10 948.23 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 10.48 126.42 02-JAN-10:10 948.12 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 10.48 126.42 02-JAN-10:10 948.12 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 2.62 31.61 02-JAN-10:10 237.06 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 2.62 31.61 02-JAN-10:10 237.06 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 2.62 31.60 02-JAN-10:10 237.03 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 2.62 31.60 02-JAN-10:10 237.03 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 23.10 278.71 02-JAN-10:10 2090.30 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 23.10 278.71 02-JAN-10:10 2090.30 01-JAN-08:10
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
Cooking:InteriorEquipment:Electricity 762.04 9746.88 01-JAN-00:10 29240.64 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL 762.04 9746.88 01-JAN-00:10 29240.64 01-JAN-07:10
InteriorEquipment:Electricity:Zone:DINING_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 433.74 5990.78 01-JAN-00:10 16487.34 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 410.33 5248.28 01-JAN-00:10 15744.84 01-JAN-07:10
ReachInFreezer:InteriorEquipment:Electricity 14.43 457.50 01-JAN-00:10 457.50 01-JAN-00:10
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 14.43 457.50 01-JAN-00:10 457.50 01-JAN-00:10
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL 14.43 457.50 01-JAN-00:10 457.50 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity 8.99 285.00 01-JAN-00:10 285.00 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 8.99 285.00 01-JAN-00:10 285.00 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL 8.99 285.00 01-JAN-00:10 285.00 01-JAN-00:10
Refrigeration:Electricity 61.96 1115.58 11-FEB-23:30 3259.19 29-AUG-06:50
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 7.09 88.82 02-JAN-11:30 2093.44 01-JAN-11:10
General:Refrigeration:Electricity 7.09 88.82 02-JAN-11:30 2093.44 01-JAN-11:10
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 7.09 88.82 02-JAN-11:30 2093.44 01-JAN-11:10
Electricity:Plant 531.51 2756.46 17-OCT-02:20 140664.97 10-AUG-18:10
LowTempRefrigeration:Refrigeration:Electricity 20.46 0.00 01-JAN-11:10 1891.74 13-AUG-10:50
MedTempRefrigeration:Refrigeration:Electricity 34.41 978.20 12-FEB-04:10 1201.92 30-AUG-13:30
Fans:Electricity 499.01 11724.09 07-JAN-08:10 31141.22 24-AUG-22:00
Fans:Electricity:Zone:ROOM_1_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_2_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_5_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_6_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_1_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_2_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Electricity:HVAC 641.57 12480.70 22-JAN-15:00 40518.36 10-AUG-20:30
ExteriorEquipment:Electricity 813.77 9999.82 02-JAN-02:20 49607.07 02-JAN-07:20
Transformer:ExteriorEquipment:Electricity 21.77 380.96 17-JUN-05:00 1291.59 02-JAN-21:10
ElectricityPurchased:Facility 4606.71 66637.43 05-AUG-05:00 335399.91 10-AUG-18:10
ElectricityPurchased:Plant 4606.71 66637.43 05-AUG-05:00 335399.91 10-AUG-18:10
Cogeneration:ElectricityPurchased 4606.71 66637.43 05-AUG-05:00 335399.91 10-AUG-18:10
General:Cogeneration:ElectricityPurchased 4606.71 66637.43 05-AUG-05:00 335399.91 10-AUG-18:10
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 4606.71 66637.43 05-AUG-05:00 335399.91 10-AUG-18:10
ElectricityNet:Plant 4606.71 66637.43 05-AUG-05:00 335399.91 10-AUG-18:10
Cogeneration:ElectricityNet 4606.71 66637.43 05-AUG-05:00 335399.91 10-AUG-18:10
General:Cogeneration:ElectricityNet 4606.71 66637.43 05-AUG-05:00 335399.91 10-AUG-18:10
General:Fans:Electricity 499.01 11724.09 07-JAN-08:10 31141.22 24-AUG-22:00
ExteriorLights:Electricity 193.50 0.00 01-JAN-08:10 12338.45 01-JAN-00:10
General:ExteriorLights:Electricity 193.50 0.00 01-JAN-08:10 12338.45 01-JAN-00:10
ElevatorLift:ExteriorEquipment:Electricity 789.09 9600.00 01-JAN-00:10 48128.80 01-JAN-07:10
ElevatorLightsFan:ExteriorEquipment:Electricity 2.91 18.80 01-JAN-00:10 188.00 01-JAN-07:10
HeatRecovery:Electricity 120.79 0.00 01-JAN-08:40 9938.94 22-JUN-16:30
General:HeatRecovery:Electricity 120.79 0.00 01-JAN-08:40 9938.94 22-JUN-16:30
WaterSystems:Electricity 94.78 1222.48 25-AUG-01:00 4751.13 15-NOV-19:50
Water Heater:WaterSystems:Electricity 94.78 1222.48 25-AUG-01:00 4751.13 15-NOV-19:50
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:Electricity 316.58 0.00 01-JAN-00:10 130336.53 10-AUG-18:10
General:Cooling:Electricity 316.58 0.00 01-JAN-00:10 130336.53 10-AUG-18:10
Pumps:Electricity 65.28 50.09 21-OCT-13:50 3389.68 10-AUG-18:10
General:Pumps:Electricity 65.28 50.09 21-OCT-13:50 3389.68 10-AUG-18:10
WIRED_LTG_ELECTRICITY 27.56 0.00 01-JAN-00:10 2275.07 02-JAN-20:20


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 5829.84 25738.07 11-AUG-01:20 539983.04 22-MAR-17:40
NaturalGas:Building 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
NaturalGas:Zone:LAUNDRY_FLR_1 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
NaturalGas:SpaceType:GENERAL 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
InteriorEquipment:NaturalGas 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
InteriorEquipment:NaturalGas:SpaceType:GENERAL 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
Laundry:InteriorEquipment:NaturalGas 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
NaturalGas:Zone:KITCHEN_FLR_6 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
Cooking:InteriorEquipment:NaturalGas 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
NaturalGas:Plant 4041.00 12376.17 11-AUG-01:20 435734.72 22-MAR-17:40
WaterSystems:NaturalGas 2699.81 12376.17 11-AUG-01:20 250435.74 07-FEB-21:30
Water Heater:WaterSystems:NaturalGas 2699.81 12376.17 11-AUG-01:20 250435.74 07-FEB-21:30
Heating:NaturalGas 1341.19 0.00 27-FEB-11:20 210727.42 11-NOV-11:50
Boiler:Heating:NaturalGas 1341.19 0.00 27-FEB-11:20 210727.42 11-NOV-11:50


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
PlantLoopCoolingDemand:Facility 1327.72 0.00 01-JAN-00:10 445234.04 10-AUG-18:10
PlantLoopCoolingDemand:HVAC 1327.72 0.00 01-JAN-00:10 445234.04 10-AUG-18:10
CoolingCoils:PlantLoopCoolingDemand 1327.72 0.00 01-JAN-00:10 445234.04 10-AUG-18:10


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 9857.19 0.00 02-JAN-01:20 0.00 08-MAY-20:10
Water:Plant 9857.19 0.00 02-JAN-01:20 0.00 08-MAY-20:10
WaterSystems:Water 9857.19 0.00 02-JAN-01:20 0.00 08-MAY-20:10
Water Heater:WaterSystems:Water 5742.51 0.00 02-JAN-01:10 0.00 02-JAN-19:10
MainsWater:Facility 9857.19 0.00 02-JAN-01:20 0.00 08-MAY-20:10
MainsWater:Plant 9857.19 0.00 02-JAN-01:20 0.00 08-MAY-20:10
WaterSystems:MainsWater 9857.19 0.00 02-JAN-01:20 0.00 08-MAY-20:10
Water Heater:WaterSystems:MainsWater 5742.51 0.00 02-JAN-01:10 0.00 02-JAN-19:10
WaterUse:WaterSystems:Water 4114.69 0.00 02-JAN-01:20 0.00 28-JUN-07:00
WaterUse:WaterSystems:MainsWater 4114.69 0.00 02-JAN-01:20 0.00 28-JUN-07:00


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 13946.26 131951.85 09-MAR-14:20 1913920.56 10-AUG-18:10
EnergyTransfer:Building 4761.08 80996.85 26-DEC-11:10 335491.49 10-AUG-18:20
EnergyTransfer:Zone:KITCHEN_FLR_6 717.13 11295.25 19-FEB-04:00 36165.76 13-AUG-10:40
Refrigeration:EnergyTransfer 183.45 4022.28 11-FEB-23:20 10345.15 29-AUG-06:50
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 91.73 2011.14 11-FEB-23:20 5172.57 29-AUG-06:50
General:Refrigeration:EnergyTransfer 91.73 2011.14 11-FEB-23:20 5172.57 29-AUG-06:50
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 91.73 2011.14 11-FEB-23:20 5172.57 29-AUG-06:50
EnergyTransfer:Plant 4832.63 17380.95 17-OCT-03:00 1061397.10 10-AUG-18:10
LowTempRefrigeration:Refrigeration:EnergyTransfer 21.61 0.00 01-JAN-11:10 2686.44 01-JAN-11:40
MedTempRefrigeration:Refrigeration:EnergyTransfer 70.11 1884.59 12-FEB-04:10 2555.76 30-AUG-13:30
EnergyTransfer:Zone:BASEMENT 398.99 10528.77 23-APR-15:00 18924.04 06-OCT-21:00
Heating:EnergyTransfer 74.62 0.00 01-JAN-08:10 47369.38 26-DEC-16:10
Heating:EnergyTransfer:Zone:BASEMENT 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer 74.62 0.00 01-JAN-08:10 47369.38 26-DEC-16:10
General:Heating:EnergyTransfer:Zone:BASEMENT 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer 4594.74 73209.95 26-DEC-15:00 331881.08 10-AUG-18:20
Cooling:EnergyTransfer:Zone:BASEMENT 398.99 10528.77 23-APR-15:00 18924.04 06-OCT-21:00
General:Cooling:EnergyTransfer 4594.74 73209.95 26-DEC-15:00 331881.08 10-AUG-18:20
General:Cooling:EnergyTransfer:Zone:BASEMENT 398.99 10528.77 23-APR-15:00 18924.04 06-OCT-21:00
EnergyTransfer:Zone:RETAIL_1_FLR_1 38.40 0.44 22-DEC-05:30 4006.98 04-OCT-12:50
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 0.21 0.00 01-JAN-00:10 623.77 26-DEC-12:00
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 0.21 0.00 01-JAN-00:10 623.77 26-DEC-12:00
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 38.20 0.00 01-JAN-02:40 4006.98 04-OCT-12:50
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 38.20 0.00 01-JAN-02:40 4006.98 04-OCT-12:50
EnergyTransfer:Zone:RETAIL_2_FLR_1 32.87 403.92 16-JAN-16:00 2008.30 10-AUG-21:00
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 32.87 403.92 16-JAN-16:00 2008.30 10-AUG-21:00
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 32.87 403.92 16-JAN-16:00 2008.30 10-AUG-21:00
EnergyTransfer:Zone:MECH_FLR_1 21.70 0.59 26-DEC-11:30 1298.48 10-AUG-21:00
Heating:EnergyTransfer:Zone:MECH_FLR_1 0.00 0.00 01-JAN-00:10 71.89 16-JAN-15:50
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 0.00 0.00 01-JAN-00:10 71.89 16-JAN-15:50
Cooling:EnergyTransfer:Zone:MECH_FLR_1 21.69 0.00 15-JAN-15:30 1298.48 10-AUG-21:00
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 21.69 0.00 15-JAN-15:30 1298.48 10-AUG-21:00
EnergyTransfer:Zone:STORAGE_FLR_1 11.43 0.01 25-DEC-05:30 663.76 10-AUG-18:10
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 0.04 0.00 01-JAN-00:10 167.68 16-JAN-16:00
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 0.04 0.00 01-JAN-00:10 167.68 16-JAN-16:00
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 11.39 0.00 01-JAN-14:40 663.76 10-AUG-18:10
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 11.39 0.00 01-JAN-14:40 663.76 10-AUG-18:10
EnergyTransfer:Zone:LAUNDRY_FLR_1 591.64 9749.25 17-JAN-05:00 38660.34 10-AUG-20:00
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 591.64 9749.25 17-JAN-05:00 38660.34 10-AUG-20:00
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 591.64 9749.25 17-JAN-05:00 38660.34 10-AUG-20:00
EnergyTransfer:Zone:CAFE_FLR_1 231.61 618.95 26-DEC-12:30 14123.84 04-OCT-12:50
Heating:EnergyTransfer:Zone:CAFE_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 231.61 618.95 26-DEC-12:30 14123.84 04-OCT-12:50
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 231.61 618.95 26-DEC-12:30 14123.84 04-OCT-12:50
EnergyTransfer:Zone:LOBBY_FLR_1 761.03 10472.79 26-DEC-15:00 39328.61 10-AUG-21:10
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 761.03 10472.79 26-DEC-15:00 39328.61 10-AUG-21:10
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 761.03 10472.79 26-DEC-15:00 39328.61 10-AUG-21:10
EnergyTransfer:Zone:ROOM_1_FLR_3 47.06 0.00 01-JAN-08:10 11634.61 10-AUG-18:10
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 10.59 0.00 01-JAN-08:10 4432.66 26-DEC-16:20
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 10.59 0.00 01-JAN-08:10 4432.66 26-DEC-16:20
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 36.47 0.00 01-JAN-00:10 11634.61 10-AUG-18:10
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 36.47 0.00 01-JAN-00:10 11634.61 10-AUG-18:10
EnergyTransfer:Zone:ROOM_2_FLR_3 37.22 0.00 01-JAN-08:10 11935.41 14-JUL-16:40
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 13.25 0.00 01-JAN-08:10 4499.91 26-DEC-16:20
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 13.25 0.00 01-JAN-08:10 4499.91 26-DEC-16:20
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 23.97 0.00 01-JAN-00:10 11935.41 14-JUL-16:40
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 23.97 0.00 01-JAN-00:10 11935.41 14-JUL-16:40
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 231.86 0.00 01-JAN-00:10 53212.93 04-OCT-12:40
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 231.86 0.00 01-JAN-00:10 53212.93 04-OCT-12:40
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 231.86 0.00 01-JAN-00:10 53212.93 04-OCT-12:40
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 301.45 0.00 01-JAN-08:10 64148.23 11-JUL-20:50
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 7.93 0.00 01-JAN-00:10 20265.46 26-DEC-16:10
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 7.93 0.00 01-JAN-00:10 20265.46 26-DEC-16:10
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 293.51 0.00 01-JAN-08:10 64148.23 11-JUL-20:50
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 293.51 0.00 01-JAN-08:10 64148.23 11-JUL-20:50
EnergyTransfer:Zone:ROOM_5_FLR_3 45.35 0.00 01-JAN-08:10 10560.76 10-AUG-08:10
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 10.64 0.00 01-JAN-08:10 4432.87 26-DEC-16:20
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 10.64 0.00 01-JAN-08:10 4432.87 26-DEC-16:20
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 34.70 0.00 01-JAN-00:10 10560.76 10-AUG-08:10
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 34.70 0.00 01-JAN-00:10 10560.76 10-AUG-08:10
EnergyTransfer:Zone:ROOM_6_FLR_3 36.77 0.00 01-JAN-08:10 11606.00 13-AUG-09:00
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 13.21 0.00 01-JAN-08:10 4479.39 26-DEC-16:20
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 13.21 0.00 01-JAN-08:10 4479.39 26-DEC-16:20
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 23.56 0.00 01-JAN-00:10 11606.00 13-AUG-09:00
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 23.56 0.00 01-JAN-00:10 11606.00 13-AUG-09:00
EnergyTransfer:Zone:CORRIDOR_FLR_3 179.23 1.38 22-DEC-13:50 10288.06 13-AUG-10:40
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 0.05 0.00 01-JAN-00:10 1361.76 26-DEC-15:00
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 0.05 0.00 01-JAN-00:10 1361.76 26-DEC-15:00
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 179.18 0.00 01-JAN-15:00 10288.06 13-AUG-10:40
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 179.18 0.00 01-JAN-15:00 10288.06 13-AUG-10:40
EnergyTransfer:Zone:ROOM_1_FLR_6 13.42 0.00 01-JAN-08:10 3245.17 10-AUG-18:10
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 4.48 0.00 01-JAN-08:10 1453.49 26-DEC-16:20
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 4.48 0.00 01-JAN-08:10 1453.49 26-DEC-16:20
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 8.95 0.00 01-JAN-00:10 3245.17 10-AUG-18:10
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 8.95 0.00 01-JAN-00:10 3245.17 10-AUG-18:10
EnergyTransfer:Zone:ROOM_2_FLR_6 11.28 0.00 01-JAN-08:10 3186.23 14-JUL-16:30
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 5.38 0.00 01-JAN-08:10 1424.93 26-DEC-16:20
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 5.38 0.00 01-JAN-08:10 1424.93 26-DEC-16:20
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 5.89 0.00 01-JAN-00:10 3186.23 14-JUL-16:30
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 5.89 0.00 01-JAN-00:10 3186.23 14-JUL-16:30
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 71.45 0.00 01-JAN-08:10 17253.39 14-SEP-15:10
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 8.82 0.00 01-JAN-08:10 6941.43 26-DEC-16:20
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 8.82 0.00 01-JAN-08:10 6941.43 26-DEC-16:20
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 62.62 0.00 01-JAN-00:10 17253.39 14-SEP-15:10
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 62.62 0.00 01-JAN-00:10 17253.39 14-SEP-15:10
EnergyTransfer:Zone:BANQUET_FLR_6 423.96 8520.76 26-DEC-15:00 22260.17 24-JUL-21:10
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 423.96 8520.76 26-DEC-15:00 22260.17 24-JUL-21:10
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 423.96 8520.76 26-DEC-15:00 22260.17 24-JUL-21:10
EnergyTransfer:Zone:DINING_FLR_6 466.99 9543.87 26-DEC-15:00 23521.14 24-JUL-21:20
Heating:EnergyTransfer:Zone:DINING_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:DINING_FLR_6 466.99 9543.87 26-DEC-15:00 23521.14 24-JUL-21:20
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 466.99 9543.87 26-DEC-15:00 23521.14 24-JUL-21:20
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 625.41 9157.89 19-FEB-04:00 31074.49 13-AUG-10:40
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 625.41 9157.89 19-FEB-04:00 31074.49 13-AUG-10:40
EnergyTransfer:Zone:CORRIDOR_FLR_6 90.26 1.05 16-JAN-16:40 6157.07 10-AUG-15:10
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 0.01 0.00 01-JAN-00:10 484.13 19-FEB-06:00
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 0.01 0.00 01-JAN-00:10 484.13 19-FEB-06:00
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 90.25 0.00 06-JAN-07:50 6157.07 10-AUG-15:10
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 90.25 0.00 06-JAN-07:50 6157.07 10-AUG-15:10
PlantLoopHeatingDemand:Facility 1673.27 9877.26 12-AUG-00:10 183670.94 03-JAN-07:20
PlantLoopHeatingDemand:Plant 781.70 9877.26 12-AUG-00:10 55604.03 10-FEB-07:30
WaterSystems:PlantLoopHeatingDemand 781.70 9877.26 12-AUG-00:10 55604.03 10-FEB-07:30
General:WaterSystems:PlantLoopHeatingDemand 781.70 9877.26 12-AUG-00:10 55604.03 10-FEB-07:30
EnergyTransfer:HVAC 4352.54 403.15 21-OCT-13:50 524924.78 10-AUG-18:10
HeatingCoils:EnergyTransfer 891.58 0.00 27-FEB-11:20 148590.34 16-DEC-16:20
PlantLoopHeatingDemand:HVAC 891.58 0.00 27-FEB-11:20 148590.34 16-DEC-16:20
HeatingCoils:PlantLoopHeatingDemand 891.58 0.00 27-FEB-11:20 148590.34 16-DEC-16:20
CoolingCoils:EnergyTransfer 1327.72 0.00 01-JAN-00:10 445234.04 10-AUG-18:10
HeatRecoveryForHeating:EnergyTransfer 2118.81 0.00 01-JAN-08:40 377584.14 19-FEB-06:40
HeatRecoveryForCooling:EnergyTransfer 14.43 0.00 01-JAN-00:10 84238.76 29-AUG-13:00
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
WaterSystems:EnergyTransfer 781.70 9877.26 12-AUG-00:10 55604.03 10-FEB-07:30
WaterUse:WaterSystems:EnergyTransfer 781.70 9877.26 12-AUG-00:10 55604.03 10-FEB-07:30
Boilers:EnergyTransfer 884.95 0.00 27-FEB-11:20 148984.30 16-DEC-16:10
Chillers:EnergyTransfer 1378.84 0.00 01-JAN-00:10 448092.67 10-AUG-18:10
HeatRejection:EnergyTransfer 1695.42 0.00 01-JAN-00:10 578429.20 10-AUG-18:10
General:HeatRejection:EnergyTransfer 1695.42 0.00 01-JAN-00:10 578429.20 10-AUG-18:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:35

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
BASEMENT 0.000 0.000 0.000 -398.990 0.000 0.000 139.547 161.294 143.105 0.000 0.000 0.000 0.001 0.000 0.000 0.000 0.000 -44.957
RETAIL_1_FLR_1 0.000 0.000 0.206 -38.199 0.000 0.000 15.892 7.307 10.186 20.671 0.000 0.013 0.000 0.000 -9.995 0.000 -1.786 -4.296
RETAIL_2_FLR_1 0.000 0.000 0.000 -32.867 0.000 0.000 17.086 8.462 11.795 0.000 0.000 0.005 0.000 0.000 0.000 0.000 -0.761 -3.720
MECH_FLR_1 0.000 0.000 0.001 -21.694 0.000 0.000 3.738 8.366 12.471 0.000 0.000 0.013 0.000 0.000 0.000 0.000 -1.723 -1.173
STORAGE_FLR_1 0.000 0.000 0.037 -11.390 0.000 0.000 2.917 3.079 3.598 0.000 0.000 0.008 2.723 0.000 0.000 0.000 -0.973 -0.000
LAUNDRY_FLR_1 0.000 0.000 0.000 -591.643 0.000 0.000 11.245 3.975 658.131 0.000 0.000 0.019 0.000 0.000 0.000 0.000 -2.571 -79.157
CAFE_FLR_1 0.000 0.000 0.000 -231.611 0.000 0.000 197.346 14.244 14.341 57.359 0.000 0.027 0.000 0.000 -30.039 0.000 -4.243 -17.423
LOBBY_FLR_1 0.000 0.000 0.000 -761.038 0.000 0.000 563.295 110.169 148.998 75.381 0.000 0.083 0.000 0.000 -41.713 0.000 -12.774 -82.402
ROOM_1_FLR_3 14.833 -30.217 0.000 -10.495 0.000 0.000 9.725 9.244 10.478 38.939 0.000 0.096 0.000 0.000 -22.896 0.000 -4.770 -14.938
ROOM_2_FLR_3 17.887 -17.615 0.000 -10.985 0.000 0.000 9.596 9.243 10.477 26.904 0.000 0.047 0.000 0.000 -23.520 0.000 -5.208 -16.826
ROOM_3_MULT19_FLR_3 0.000 -217.704 0.000 -14.148 0.000 0.000 0.000 110.385 194.997 225.700 0.000 0.030 0.003 0.000 -167.239 0.000 -30.494 -101.526
ROOM_4_MULT19_FLR_3 31.574 -171.405 0.000 -145.738 0.000 0.000 183.307 110.415 195.050 64.829 0.000 0.481 0.000 0.000 -130.696 0.000 -39.060 -98.757
ROOM_5_FLR_3 14.883 -28.445 0.000 -10.497 0.000 0.000 9.721 9.244 10.478 37.127 0.000 0.097 0.000 0.000 -22.424 0.000 -4.771 -15.414
ROOM_6_FLR_3 17.843 -17.358 0.000 -10.834 0.000 0.000 9.647 9.243 10.477 25.086 0.000 0.049 0.000 0.000 -22.832 0.000 -5.191 -16.129
CORRIDOR_FLR_3 0.000 0.000 0.049 -179.177 0.000 0.000 120.331 91.336 0.000 35.066 0.000 0.042 0.000 0.000 -29.498 0.000 -5.177 -32.971
ROOM_1_FLR_6 5.691 -7.542 0.000 -2.620 0.000 0.000 2.435 2.311 2.620 9.663 0.000 0.026 0.000 0.000 -5.676 0.000 -1.217 -5.690
ROOM_2_FLR_6 6.673 -4.421 0.000 -2.760 0.000 0.000 2.397 2.311 2.619 6.658 0.000 0.012 0.000 0.000 -5.844 0.000 -1.318 -6.326
ROOM_3_MULT9_FLR_6 14.084 -50.949 0.000 -16.934 0.000 0.000 21.821 13.076 23.098 53.040 0.000 0.182 0.000 0.000 -26.770 0.000 -6.444 -24.205
BANQUET_FLR_6 0.000 0.000 0.000 -423.962 0.000 0.000 316.003 31.006 175.857 6.311 0.000 0.013 0.000 0.000 -18.266 0.000 -3.123 -83.839
DINING_FLR_6 0.000 0.000 0.000 -466.991 0.000 0.000 314.906 31.006 175.857 6.104 0.000 0.013 0.000 0.000 -18.833 0.000 -3.149 -38.913
KITCHEN_FLR_6 0.000 0.000 0.000 -625.391 0.000 0.000 28.294 12.972 550.372 17.565 0.000 0.012 31.224 0.000 -12.233 0.000 -2.814 -0.000
CORRIDOR_FLR_6 0.000 0.000 0.013 -90.251 0.000 0.000 31.810 24.166 0.000 17.089 0.000 0.014 32.866 0.000 -13.396 0.000 -2.311 0.000
Total Facility 123.468 -545.655 0.306 -4098.214 0.000 0.000 2011.057 782.856 2365.005 723.492 0.000 1.281 66.817 0.000 -601.870 0.000 -139.879 -688.661


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 06-OCT-21:00 0.00 0.00 0.00 -18924.24 0.00 0.00 5924.44 11724.66 9125.55 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -7850.42
RETAIL_1_FLR_1 04-OCT-12:50 0.00 0.00 0.00 -4006.54 0.00 0.00 150.60 166.00 252.59 6353.19 0.00 0.00 0.00 0.00 -0.00 0.00 -17.84 -2898.00
RETAIL_2_FLR_1 10-AUG-20:55 0.00 0.00 0.00 -2008.49 0.00 0.00 697.58 615.12 752.15 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -2.01 -54.34
MECH_FLR_1 10-AUG-20:57 0.00 0.00 0.00 -1298.51 0.00 0.00 147.52 608.16 795.27 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -4.75 -247.69
STORAGE_FLR_1 10-AUG-18:10 0.00 0.00 0.00 -665.62 0.00 0.00 102.91 223.85 229.41 0.00 0.00 18.76 90.67 0.00 -0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 10-AUG-20:00 0.00 0.00 0.00 -38661.54 0.00 0.00 408.86 325.08 44299.38 0.00 0.00 10.23 0.00 0.00 -0.00 0.00 0.00 -6382.01
CAFE_FLR_1 04-OCT-12:50 0.00 0.00 0.00 -14122.26 0.00 0.00 1979.10 103.98 355.63 17817.44 0.00 0.00 0.00 0.00 -0.00 0.00 -39.44 -6094.46
LOBBY_FLR_1 10-AUG-21:05 0.00 0.00 0.00 -39344.91 0.00 0.00 26437.38 6336.53 7389.94 0.00 0.00 0.00 0.00 0.00 -673.42 0.00 -35.58 -109.95
ROOM_1_FLR_3 14-MAY-18:01 0.00 -14897.60 0.00 -725.79 0.00 0.00 283.21 711.53 484.65 6185.16 0.00 0.00 8015.54 0.00 -0.00 0.00 -56.71 0.00
ROOM_2_FLR_3 25-APR-17:41 0.00 -15572.86 0.00 0.00 0.00 0.00 193.47 476.67 505.67 5885.14 0.00 0.00 8642.35 0.00 -0.00 0.00 -130.44 0.00
ROOM_3_MULT19_FLR_3 04-OCT-12:40 0.00 -53212.92 0.00 0.00 0.00 0.00 0.00 2378.94 2352.88 76152.85 0.00 0.00 0.00 0.00 -0.00 0.00 -394.67 -27277.07
ROOM_4_MULT19_FLR_3 14-MAY-21:51 0.00 -74923.83 0.00 -8216.81 0.00 0.00 6347.31 7223.75 6668.31 0.00 0.00 0.00 67867.39 0.00 -4546.73 0.00 -419.38 0.00
ROOM_5_FLR_3 14-MAY-18:01 0.00 -13252.22 0.00 -713.69 0.00 0.00 283.21 711.53 484.65 343.86 0.00 0.00 12187.34 0.00 -0.00 0.00 -44.68 0.00
ROOM_6_FLR_3 24-JUL-08:32 0.00 -13596.91 0.00 -1051.05 0.00 0.00 58.85 313.04 452.99 9318.08 0.00 0.00 4549.48 0.00 -0.00 0.00 -44.48 0.00
CORRIDOR_FLR_3 13-AUG-10:33 0.00 0.00 0.00 -10313.74 0.00 0.00 1850.29 2489.76 0.00 7053.07 0.00 14.96 0.00 0.00 -0.00 0.00 0.00 -1094.34
ROOM_1_FLR_6 14-MAY-18:01 0.00 -3890.01 0.00 -181.71 0.00 0.00 70.80 177.88 121.16 1531.43 0.00 0.00 2188.44 0.00 -0.00 0.00 -18.01 0.00
ROOM_2_FLR_6 25-APR-17:41 0.00 -4036.24 0.00 0.00 0.00 0.00 48.37 119.17 126.42 1450.07 0.00 0.00 2325.09 0.00 -0.00 0.00 -32.86 0.00
ROOM_3_MULT9_FLR_6 25-MAR-15:01 0.00 -21222.02 0.00 -835.64 0.00 0.00 294.09 332.11 487.74 7016.73 0.00 0.00 14086.52 0.00 -0.00 0.00 -159.53 0.00
BANQUET_FLR_6 24-JUL-21:10 0.00 0.00 0.00 -22261.32 0.00 0.00 15644.05 1992.02 6747.90 0.00 0.00 0.00 0.00 0.00 -217.44 0.00 -12.36 -1892.86
DINING_FLR_6 24-JUL-21:20 0.00 0.00 0.00 -23522.51 0.00 0.00 15629.92 1992.02 6747.90 0.00 0.00 0.00 0.00 0.00 -254.33 0.00 -15.12 -577.88
KITCHEN_FLR_6 13-AUG-10:40 0.00 0.00 0.00 -31081.50 0.00 0.00 464.20 353.60 24259.91 3650.54 0.00 0.02 2353.23 0.00 -0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 10-AUG-15:03 0.00 0.00 0.00 -6159.30 0.00 0.00 771.14 548.96 0.00 2449.02 0.00 39.42 2350.75 0.00 -0.00 0.00 0.00 0.00
Total Facility 10-AUG-18:02 0.00 -163454.81 0.00 -201969.72 0.00 0.00 75199.71 53578.21 120482.43 47564.63 0.00 1961.29 66638.26 0.00 0.00 0.00 0.00 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 26-DEC-12:00 0.00 0.00 623.76 0.00 0.00 0.00 179.27 166.00 252.59 0.00 0.00 0.00 0.00 0.00 -554.01 0.00 -118.80 -548.80
RETAIL_2_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MECH_FLR_1 16-JAN-15:50 0.00 0.00 71.89 0.00 0.00 0.00 43.84 152.04 265.09 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -97.71 -435.14
STORAGE_FLR_1 16-JAN-16:00 0.00 0.00 167.67 0.00 0.00 0.00 33.72 55.96 76.47 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -56.38 -277.45
LAUNDRY_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 18-APR-15:04 5220.88 419.38 0.00 -419.38 0.00 0.00 235.75 199.23 200.18 2176.12 0.00 0.00 0.00 0.00 -0.00 0.00 -152.05 -7880.11
ROOM_2_FLR_3 24-MAR-15:03 5109.14 416.25 0.00 -416.25 0.00 0.00 252.31 199.20 200.16 2771.48 0.00 0.00 0.00 0.00 -0.00 0.00 -151.04 -8381.26
ROOM_3_MULT19_FLR_3 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 07-JAN-16:01 25357.18 4669.59 0.00 -4669.59 0.00 0.00 2968.12 2804.51 4118.66 0.00 0.00 0.00 0.00 0.00 -8405.24 0.00 -1214.47 -25628.76
ROOM_5_FLR_3 01-OCT-15:04 5064.74 465.73 0.00 -465.73 0.00 0.00 130.71 234.80 221.25 2083.19 0.00 0.00 0.00 0.00 -0.00 0.00 -530.12 -7204.59
ROOM_6_FLR_3 29-MAY-15:04 4976.47 426.09 0.00 -426.09 0.00 0.00 130.71 234.78 221.23 2658.43 0.00 0.00 0.00 0.00 -0.00 0.00 -718.71 -7502.92
CORRIDOR_FLR_3 26-DEC-15:00 0.00 0.00 1361.76 0.00 0.00 0.00 1385.83 2074.80 0.00 0.00 0.00 0.00 0.00 0.00 -1796.77 0.00 -299.43 -2726.19
ROOM_1_FLR_6 26-DEC-16:13 1520.00 90.71 0.00 -90.71 0.00 0.00 67.02 49.81 50.05 0.00 0.00 0.00 0.00 0.00 -401.86 0.00 -54.60 -1230.42
ROOM_2_FLR_6 26-DEC-16:13 1484.92 89.67 0.00 -89.67 0.00 0.00 67.26 49.80 50.04 0.00 0.00 0.00 0.00 0.00 -398.62 0.00 -54.42 -1198.97
ROOM_3_MULT9_FLR_6 26-DEC-16:13 7417.28 590.81 0.00 -590.81 0.00 0.00 600.58 281.79 441.28 0.00 0.00 0.00 0.00 0.00 -1897.97 0.00 -252.47 -6590.49
BANQUET_FLR_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
DINING_FLR_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 19-FEB-06:00 0.00 0.00 484.11 0.00 0.00 0.00 1283.30 439.17 0.00 0.00 0.00 0.00 0.00 0.00 -1511.06 0.00 -190.23 -505.30
Total Facility 16-JAN-16:13 -25057.65 87179.53 1150.23 -87179.53 0.00 0.00 35481.86 16549.49 71286.28 0.00 0.00 0.00 0.00 0.00 -37120.36 0.00 -6346.92 -55942.93



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:35

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
FLR_3_DOAS 2.0513 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.0513 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV WITH REHEAT 22.7135 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 22.5915 0.0000 1.0000 Not calculated 0.0000 0.0000    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
FLR_3_DOAS 2.0513 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.0513 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV WITH REHEAT 11.6520 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 11.6520 0.0000 1.0000 Not calculated 0.0000 0.0000    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
BASEMENT VAV WITH REHEAT 0.000000 106.4990 0.000432 1978.83 0.0000 1.0000 0.0000 1.000 0.0000
RETAIL_1_FLR_1 VAV WITH REHEAT 0.000000 10.8290 0.001181 67.07 0.0000 1.0000 0.0000 1.000 0.0000
RETAIL_2_FLR_1 VAV WITH REHEAT 0.000000 12.5400 0.001181 77.67 0.0000 1.0000 0.0000 1.000 0.0000
MECH_FLR_1 VAV WITH REHEAT 0.000000 2.6520 0.000000 164.24 0.0000 1.0000 0.0000 1.000 0.0000
STORAGE_FLR_1 VAV WITH REHEAT 0.000000 2.0400 0.000610 94.76 0.0000 1.0000 0.0000 1.000 0.0000
LAUNDRY_FLR_1 VAV WITH REHEAT 0.000000 8.4000 0.000000 78.04 0.0000 1.0000 0.0000 1.000 0.0000
CAFE_FLR_1 VAV WITH REHEAT 0.000000 142.3000 0.003581 188.86 0.0000 1.0000 0.0000 1.000 0.0000
LOBBY_FLR_1 VAV WITH REHEAT 0.000000 422.4350 0.001448 1308.19 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_1_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.09 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_2_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.07 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_3_MULT19_FLR_3 FLR_3_DOAS 0.000000 114.0000 0.000449 1863.81 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_4_MULT19_FLR_3 FLR_3_DOAS 0.000000 114.0000 0.000449 1864.32 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_5_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.09 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_6_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.07 0.0000 1.0000 0.0000 1.000 0.0000
CORRIDOR_FLR_3 VAV WITH REHEAT 0.000000 83.8280 0.000305 1557.62 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_1_FLR_6 FLR_3_DOAS 0.000000 1.5000 0.000396 39.02 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_2_FLR_6 FLR_3_DOAS 0.000000 1.5000 0.000396 39.02 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_3_MULT9_FLR_6 FLR_3_DOAS 0.000000 13.5000 0.000449 220.77 0.0000 1.0000 0.0000 1.000 0.0000
BANQUET_FLR_6 VAV WITH REHEAT 0.000000 249.8960 0.003581 331.66 0.0000 1.0000 0.0000 1.000 0.0000
DINING_FLR_6 VAV WITH REHEAT 0.000000 249.8960 0.003581 331.66 0.0000 1.0000 0.0000 1.000 0.0000
KITCHEN_FLR_6 VAV WITH REHEAT 0.000000 22.2380 0.003556 103.30 0.0000 1.0000 0.0000 1.000 0.0000
CORRIDOR_FLR_6 VAV WITH REHEAT 0.000000 22.1800 0.000305 412.12 0.0000 1.0000 0.0000 1.000 0.0000


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
FLR_3_DOAS   0.00 0.000441 4651.2638 0.0000 0.0000 0.0000
VAV WITH REHEAT   0.00 0.001045 6694.0231 0.0000 0.0000 0.0000


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.5475 2.5475 1.3069 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_1_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4425 0.4425 0.2270 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_2_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2320 0.2320 0.1190 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
MECH_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1740 0.1740 0.0893 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
STORAGE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1034 0.1034 0.0531 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LAUNDRY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 3.2875 3.2875 1.6865 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CAFE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.7669 1.7669 0.9064 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LOBBY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.1416 5.1416 2.6377 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8371 0.8371 0.8371 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_4_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8373 0.8373 0.8373 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_5_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_6_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_3 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.6074 1.6074 0.8246 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT9_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0992 0.0992 0.0992 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
BANQUET_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.1173 2.1173 1.0862 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DINING_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.2178 2.2178 1.1377 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
KITCHEN_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.2713 2.2713 1.1652 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.8041 0.8041 0.4125 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
FLR_3_DOAS 2.0513 2.0513 2.0513 2.0513 0.0000 1.0000
VAV WITH REHEAT 22.7135 22.5915 22.7135 11.6520 0.0000 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.3069 1.3069 1.3069 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_1_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2270 0.2270 0.2270 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_2_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1190 0.1190 0.1190 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
MECH_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0893 0.0893 0.0893 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
STORAGE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0531 0.0531 0.0531 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LAUNDRY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.6865 1.6865 1.6865 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CAFE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.9064 0.9064 0.9064 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LOBBY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.6377 2.6377 2.6377 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8371 0.8371 0.8371 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_4_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8373 0.8373 0.8373 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_5_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_6_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_3 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.8246 0.8246 0.8246 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT9_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0992 0.0992 0.0992 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
BANQUET_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.0862 1.0862 1.0862 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DINING_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1377 1.1377 1.1377 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
KITCHEN_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1652 1.1652 1.1652 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4125 0.4125 0.4125 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
FLR_3_DOAS 2.0513 2.0513 2.0513 2.0513 0.0000 1.0000
VAV WITH REHEAT 11.6520 11.6520 11.6520 11.6520 0.0000 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:35

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930
Total gross floor area [m2] 11345.29
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
BASEMENT 1978.83 1978.83 0.00 168.00
RETAIL_1_FLR_1 67.07 67.07 0.00 168.00
RETAIL_2_FLR_1 77.67 77.67 0.00 168.00
MECH_FLR_1 164.24 164.24 0.00 168.00
STORAGE_FLR_1 94.76 94.76 0.00 168.00
LAUNDRY_FLR_1 78.04 78.04 0.00 168.00
CAFE_FLR_1 188.86 188.86 0.00 168.00
LOBBY_FLR_1 1308.19 1308.19 0.00 168.00
ROOM_1_FLR_3 39.02 39.02 0.00 168.00
ROOM_2_FLR_3 39.02 39.02 0.00 168.00
ROOM_3_MULT19_FLR_3 24.52 24.52 0.00 0.00
ROOM_4_MULT19_FLR_3 24.53 24.53 0.00 168.00
ROOM_5_FLR_3 39.02 39.02 0.00 168.00
ROOM_6_FLR_3 39.02 39.02 0.00 168.00
CORRIDOR_FLR_3 389.40 389.40 0.00 168.00
ROOM_1_FLR_6 39.02 39.02 0.00 168.00
ROOM_2_FLR_6 39.02 39.02 0.00 168.00
ROOM_3_MULT9_FLR_6 24.53 24.53 0.00 168.00
BANQUET_FLR_6 331.66 331.66 0.00 168.00
DINING_FLR_6 331.66 331.66 0.00 168.00
KITCHEN_FLR_6 103.30 103.30 0.00 168.00
CORRIDOR_FLR_6 412.12 412.12 0.00 168.00
Totals 11345.29 11345.29 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 18.83
Number of hours cooling loads not met 30.00
Number of hours not met 48.83


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler 0.00 0.00 1341.19 210727.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 316.58 130336.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 782.86 64632.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 193.50 12338.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 872.72 59188.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- Cooking 762.04 29240.64 1198.64 74976.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ReachInFreezer 14.43 457.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ReachInRefrigerator 8.99 285.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- Laundry 0.00 0.00 590.20 39726.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Transformer 21.77 1291.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLift 789.09 48128.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLightsFan 2.91 188.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 499.01 31141.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 65.28 3389.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- General 120.79 9938.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 94.78 4751.13 2699.81 250435.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- General 7.09 2093.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- LowTempRefrigeration 20.46 1891.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- MedTempRefrigeration 34.41 1201.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 1720.14 4606.71
Natural Gas 1788.84 5829.84
Additional 0.00 0.00
Total 3508.98 10436.55


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 69.00
Space Heating 0.00
Space Cooling 27.90
Fans (All) 43.98
Service Water Heating 8.35
Receptacle Equipment 146.16
Miscellaneous (All) 406.05
Subtotal 406.05


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 118.22
Service Water Heating 237.97
Miscellaneous (All) 513.86
Subtotal 513.86


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 7.50
Space Heating 12.85
Space Cooling 3.03
Fans (All) 4.78
Service Water Heating 26.78
Receptacle Equipment 33.03
Miscellaneous 12.03


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
ELEVATOR_RUNNING_SCH 486. 5110.
ELEVATOR_STANDBY_SCH 7671. 8760.
LTG_SCH_KITCHEN 3061. 8760.
LTG_SCH_DINING 3061. 8760.
LTG_SCH_BASEMENT 2572. 8760.
LTG_SCH_LOBBY 2295. 8760.
LTG_SCH_STORAGE 1580. 8760.
LTG_SCH_MECHANIC 3061. 8760.
LTG_SCH_LAUNDRY 3061. 8760.
LTG_SCH_GUESTROOM 1980. 8760.
LTG_SCH_CORRIDOR 2295. 8760.
LTG_SCH_RETAIL 2678. 8760.
WALKIN_OCC_LGHT_SCH_2 1591. 8760.
EXTERIOR_LTG_SCH 4380. 4380.
BASEMENT_EQUIP_SCH 3737. 8760.
BLDG_EQUIP_SCH 3924. 8760.
GUESTROOM_EQP_SCH_BASE 3239. 8760.
GUESTROOM_EQP_SCH_ADVA 2762. 8760.
LOBBY_EQP_SCH 3292. 8760.
OFFICE_EQP_SCH 4941. 8760.
EMPLOYEELOUNGE_EQP_SCH 4044. 8760.
LAUNDRYROOM_EQP_ELEC_SCH 2920. 2920.
LAUNDRYROOM_EQP_GAS_SCH 2920. 2920.
MEETINGROOM_EQP_SCH 1336. 4745.
EXERCISEROOM_EQP_SCH 3832. 5840.
KITCHEN_ELEC_EQUIP_SCH 2172. 8760.
KITCHEN_GAS_EQUIP_SCH 1332. 8760.
KITCHEN_EXHAUST_SCH 6205. 6205.
ELEV_LIGHT_FAN_SCH_24_7 8760. 8760.
ELEV_LIGHT_FAN_SCH_ADD_DF 2154. 8760.
BLDG_OCC_SCH 5026. 8760.
GUESTROOM_OCC_SCH 5515. 8760.
LOBBY_OCC_SCH 2304. 8760.
OFFICE_OCC_SCH 3954. 8760.
EMPLOYEELOUNGE_OCC_SCH 948. 5475.
MEETINGROOM_OCC_SCH 1168. 4745.
LAUNDRYROOM_OCC_SCH 427. 2920.
EXERCISEROOM_OCC_SCH 5292. 5840.
INFIL_SCH 8760. 8760.
INFIL_HALF_ON_SCH 4380. 8760.
INFIL_QUARTER_ON_SCH 2190. 8760.
LAUNDRY_SWH_SCH 2555. 2555.
BLDG_SWH_SCH 3301. 8760.
GUESTROOM_SWH_SCH 2899. 8760.
LAUNDRYROOM_SWH_SCH 2920. 2920.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
ALWAYS_ON 8760. 8760.
ALWAYS_OFF 0. 0.
FAN_SCH 8760. 8760.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
OCC_GUESTROOM_VENT_CTRL_30MIN 6570. 6570.
OCC_GUESTROOM_VENT_CTRL_20MIN 6327. 6327.
VAC_GUESTROOM_VENTILATION_SCHEDULE 365. 365.
MINOA_MOTORIZEDDAMPER_SCHED 8760. 8760.
MINOA_SCHED 8760. 8760.
WORK_EFF_SCH 0. 0.
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED 2774. 8760.
FLR_3_DOAS_OAMINOAFRACSCHEDULE 8760. 8760.
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE 5740. 6205.
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE 8760. 8760.
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH 3285. 3285.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
VACGUESTROOM_HTGSP_SCH VACGUESTROOM THERMOSTAT DUAL SP CONTROL January 15.56 365 15.56 365
VACGUESTROOM_CLGSP_SCH VACGUESTROOM THERMOSTAT DUAL SP CONTROL July 26.67 365 26.67 365
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL January 21.11 365 21.11 365
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL July 23.33 365 21.11 365
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL January 21.11 365 21.11 365
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL July 23.33 365 21.11 365
HTGSETP_SCH BASEMENT DUAL SP CONTROL January 21.00 365 21.00 365
CLGSETP_SCH BASEMENT DUAL SP CONTROL July 24.00 365 24.00 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:35

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 8760.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 8760.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 8760.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8760.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 8760.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 8760.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 8697.50 62.50 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 8546.17 213.83 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 8748.83 11.17 0.00 0.00 0.00
CORRIDOR_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 8760.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 8646.17 113.83 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 8760.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 8760.00 0.00 0.00 0.00 0.00
DINING_FLR_6 8760.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 8760.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 8760.00 0.00 0.00 0.00 0.00
Min 8546.17 0.00 0.00 0.00 0.00
Max 8760.00 213.83 0.00 0.00 0.00
Average 8741.76 18.24 0.00 0.00 0.00
Sum 192318.67 401.33 0.00 0.00 0.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 529331.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 50179.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 59156.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8977.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 5588.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 37203.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 710417.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 2115429.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 4135.17 18.83 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 4154.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 100358.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 4113.33 40.67 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 4154.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 1245715.00 0.00 0.00 0.00 0.00
DINING_FLR_6 1245715.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 108269.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 105946.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 2115429.00 40.67 0.00 0.00 0.00
Average 288884.34 2.70 0.00 0.00 0.00
Sum 6355455.50 59.50 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 8760.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 8760.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 8760.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8760.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 8760.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 8741.33 18.67 0.00 0.00 0.00
LOBBY_FLR_1 8733.67 26.33 0.00 0.00 0.00
ROOM_1_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 8681.50 78.50 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 8206.00 554.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 8739.00 21.00 0.00 0.00 0.00
CORRIDOR_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 8760.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 8622.00 138.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 8760.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 8719.83 40.17 0.00 0.00 0.00
DINING_FLR_6 8739.33 20.67 0.00 0.00 0.00
KITCHEN_FLR_6 8753.00 7.00 0.00 0.00 0.00
CORRIDOR_FLR_6 8760.00 0.00 0.00 0.00 0.00
Min 8206.00 0.00 0.00 0.00 0.00
Max 8760.00 554.00 0.00 0.00 0.00
Average 8718.89 41.11 0.00 0.00 0.00
Sum 191815.67 904.33 0.00 0.00 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 529331.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 50179.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 59156.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8977.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 5588.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 37203.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 708027.67 2389.33 0.00 0.00 0.00
LOBBY_FLR_1 2105606.50 9822.50 0.00 0.00 0.00
ROOM_1_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 4119.17 34.83 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 4154.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 100358.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 4087.33 66.67 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 4154.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 1236917.67 8797.33 0.00 0.00 0.00
DINING_FLR_6 1241185.67 4529.33 0.00 0.00 0.00
KITCHEN_FLR_6 108225.50 43.50 0.00 0.00 0.00
CORRIDOR_FLR_6 105946.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 2105606.50 9822.50 0.00 0.00 0.00
Average 287719.61 1167.43 0.00 0.00 0.00
Sum 6329831.50 25683.50 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:35

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:35

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 0.00 0.00 0.00 0.00
MECH_FLR_1 0.00 0.00 0.00 0.00
STORAGE_FLR_1 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 0.00 0.00 0.00 0.00
CAFE_FLR_1 0.00 8760.00 0.00 0.00
LOBBY_FLR_1 0.00 8760.00 0.00 0.00
ROOM_1_FLR_3 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 0.00 0.00 0.00 0.00
BANQUET_FLR_6 0.00 8760.00 0.00 0.00
DINING_FLR_6 0.00 8760.00 0.00 0.00
KITCHEN_FLR_6 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 8760.00 0.00 0.00
Average 0.00 1592.73 0.00 0.00
Sum 0.00 35040.00 0.00 0.00


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 0.00 0.00 0.00 0.00
MECH_FLR_1 0.00 0.00 0.00 0.00
STORAGE_FLR_1 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 0.00 0.00 0.00 0.00
CAFE_FLR_1 0.00 710417.00 0.00 0.00
LOBBY_FLR_1 0.00 2115429.00 0.00 0.00
ROOM_1_FLR_3 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 0.00 0.00 0.00 0.00
BANQUET_FLR_6 0.00 1245715.00 0.00 0.00
DINING_FLR_6 0.00 1245715.00 0.00 0.00
KITCHEN_FLR_6 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 2115429.00 0.00 0.00
Average 0.00 241694.36 0.00 0.00
Sum 0.00 5317276.00 0.00 0.00



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C

For: Environment

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.496
February 5.822
March 8.326
April 10.851
May 12.973
June 15.587
July 17.665
August 18.800
September 15.086
October 11.426
November 8.070
December 5.416
   
Annual Sum or Average 11.241
Minimum of Months 4.496
Maximum of Months 18.800



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.496
February 5.822
March 8.326
April 10.851
May 12.973
June 15.587
July 17.665
August 18.800
September 15.086
October 11.426
November 8.070
December 5.416
   
Annual Sum or Average 11.241
Minimum of Months 4.496
Maximum of Months 18.800



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

For: Environment

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.496
February 5.822
March 8.326
April 10.851
May 12.973
June 15.587
July 17.665
August 18.800
September 15.086
October 11.426
November 8.070
December 5.416
   
Annual Sum or Average 11.241
Minimum of Months 4.496
Maximum of Months 18.800



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016

For: Environment

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.496
February 5.822
March 8.326
April 10.851
May 12.973
June 15.587
July 17.665
August 18.800
September 15.086
October 11.426
November 8.070
December 5.416
   
Annual Sum or Average 11.241
Minimum of Months 4.496
Maximum of Months 18.800



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE

For: Environment

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.496
February 5.822
March 8.326
April 10.851
May 12.973
June 15.587
July 17.665
August 18.800
September 15.086
October 11.426
November 8.070
December 5.416
   
Annual Sum or Average 11.241
Minimum of Months 4.496
Maximum of Months 18.800



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE

For: Environment

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.496
February 5.822
March 8.326
April 10.851
May 12.973
June 15.587
July 17.665
August 18.800
September 15.086
October 11.426
November 8.070
December 5.416
   
Annual Sum or Average 11.241
Minimum of Months 4.496
Maximum of Months 18.800



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.496
February 5.822
March 8.326
April 10.851
May 12.973
June 15.587
July 17.665
August 18.800
September 15.086
October 11.426
November 8.070
December 5.416
   
Annual Sum or Average 11.241
Minimum of Months 4.496
Maximum of Months 18.800



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED

For: Environment

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.496
February 5.822
March 8.326
April 10.851
May 12.973
June 15.587
July 17.665
August 18.800
September 15.086
October 11.426
November 8.070
December 5.416
   
Annual Sum or Average 11.241
Minimum of Months 4.496
Maximum of Months 18.800



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.496
February 5.822
March 8.326
April 10.851
May 12.973
June 15.587
July 17.665
August 18.800
September 15.086
October 11.426
November 8.070
December 5.416
   
Annual Sum or Average 11.241
Minimum of Months 4.496
Maximum of Months 18.800



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BASEMENT

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.326644E+11 14368.56 11-JAN-21:00 11.10 10.22 0.773642E+10 4833.51 13-JAN-22:10 0.60 0.60
February 0.289740E+11 14221.27 01-FEB-21:00 6.70 5.41 0.687705E+10 4775.28 01-FEB-22:10 6.60 5.31
March 0.315923E+11 14304.51 25-MAR-10:33 8.87 1.80 0.750406E+10 4688.90 03-MAR-22:10 8.87 1.80
April 0.305699E+11 14725.32 27-APR-10:33 20.37 13.53 0.716308E+10 4590.96 14-APR-21:10 20.37 13.53
May 0.322970E+11 15190.50 14-MAY-10:33 20.03 12.68 0.746710E+10 4641.22 18-MAY-21:10 8.90 7.04
June 0.322909E+11 15590.92 25-JUN-10:33 18.87 13.09 0.735829E+10 4723.74 23-JUN-22:10 18.87 13.09
July 0.345298E+11 16122.79 30-JUL-10:33 23.33 16.24 0.772981E+10 4817.66 28-JUL-22:10 23.33 16.24
August 0.354496E+11 16354.47 13-AUG-10:33 24.17 17.28 0.789715E+10 4837.10 15-AUG-22:10 18.18 14.52
September 0.349199E+11 17575.13 15-SEP-21:00 16.10 14.33 0.774164E+10 4837.09 11-SEP-22:10 16.10 14.33
October 0.363529E+11 18924.04 06-OCT-21:00 12.80 10.62 0.807085E+10 4837.08 04-OCT-21:30 12.80 10.62
November 0.349908E+11 18782.45 08-NOV-22:00 8.90 7.25 0.781563E+10 4837.03 16-NOV-22:19 5.20 4.52
December 0.343574E+11 17689.75 01-DEC-22:00 5.00 4.72 0.795294E+10 4837.04 22-DEC-22:19 1.90 1.47
                     
Annual Sum or Average 0.398989E+12         0.913140E+11        
Minimum of Months 0.289740E+11 14221.27   5.00 1.80 0.687705E+10 4590.96   0.60 0.60
Maximum of Months 0.363529E+11 18924.04   24.17 17.28 0.807085E+10 4837.10   23.33 16.24



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.984917E+09 2277.79 20-JAN-11:50 5.60 3.57 0.620875E+09 364.22 03-JAN-01:00 5.60 3.57
February 0.175555E+10 2779.69 08-FEB-13:30 6.40 3.77 0.565344E+09 389.72 27-FEB-22:40 12.20 10.25
March 0.274675E+10 3427.10 02-MAR-13:20 12.57 7.60 0.633106E+09 407.24 14-MAR-21:30 12.50 8.53
April 0.344856E+10 3203.26 27-APR-13:05 26.10 16.37 0.618882E+09 437.30 27-APR-21:30 15.80 11.30
May 0.405073E+10 3094.00 04-MAY-13:20 22.77 15.31 0.645538E+09 434.51 04-MAY-21:30 18.35 12.20
June 0.428329E+10 2568.56 28-JUN-10:33 21.50 14.65 0.630437E+09 431.62 28-JUN-21:30 17.50 13.87
July 0.495267E+10 3026.55 31-JUL-13:20 27.57 18.47 0.673585E+09 452.37 24-JUL-21:30 27.57 18.47
August 0.513441E+10 3845.17 24-AUG-13:10 28.93 19.36 0.687116E+09 465.74 10-AUG-21:19 28.93 19.36
September 0.446400E+10 3980.43 14-SEP-13:15 23.17 17.52 0.644288E+09 452.15 12-SEP-21:30 23.17 17.52
October 0.341285E+10 4006.98 04-OCT-12:50 20.60 11.27 0.638269E+09 434.52 04-OCT-21:30 15.00 9.56
November 0.175265E+10 3260.01 04-NOV-13:30 20.85 16.00 0.602579E+09 364.86 02-NOV-21:30 20.85 16.00
December 0.121249E+10 2544.74 05-DEC-12:20 10.20 6.11 0.622325E+09 364.21 13-DEC-23:49 7.80 2.39
                     
Annual Sum or Average 0.381989E+11         0.758234E+10        
Minimum of Months 0.984917E+09 2277.79   5.60 3.57 0.565344E+09 364.21   5.60 2.39
Maximum of Months 0.513441E+10 4006.98   28.93 19.36 0.687116E+09 465.74   28.93 19.36



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.231627E+10 1141.51 11-JAN-21:00 11.10 10.22 0.781287E+09 516.13 11-JAN-23:10 9.22 8.15
February 0.222765E+10 1252.97 27-FEB-21:00 12.20 10.06 0.727077E+09 548.68 27-FEB-23:10 12.20 10.40
March 0.264279E+10 1279.22 02-MAR-21:00 6.70 5.56 0.838631E+09 556.41 02-MAR-23:10 7.12 6.08
April 0.271605E+10 1621.11 27-APR-21:00 17.20 11.44 0.833733E+09 569.55 27-APR-22:10 14.40 11.00
May 0.294909E+10 1594.67 04-MAY-21:00 17.80 12.21 0.885801E+09 569.55 15-MAY-21:30 13.35 11.02
June 0.295066E+10 1670.87 28-JUN-21:00 16.70 13.67 0.871739E+09 569.55 27-JUN-22:10 16.70 13.67
July 0.322471E+10 1860.11 31-JUL-21:00 21.70 16.73 0.920404E+09 569.55 21-JUL-22:10 21.70 16.73
August 0.327705E+10 2008.44 10-AUG-20:55 23.00 16.96 0.927504E+09 569.55 15-AUG-22:10 18.18 14.52
September 0.298204E+10 1806.55 14-SEP-21:00 18.30 14.89 0.875204E+09 569.55 11-SEP-22:10 18.30 14.89
October 0.278407E+10 1572.60 04-OCT-21:00 13.90 9.05 0.860617E+09 569.55 04-OCT-21:30 15.00 9.56
November 0.243269E+10 1268.63 04-NOV-18:10 15.00 13.34 0.785468E+09 535.10 06-NOV-23:10 15.40 14.28
December 0.236396E+10 1190.31 05-DEC-21:00 5.60 1.73 0.789881E+09 529.32 05-DEC-23:10 4.03 2.13
                     
Annual Sum or Average 0.328670E+11         0.100973E+11        
Minimum of Months 0.222765E+10 1141.51   5.60 1.73 0.727077E+09 516.13   4.03 2.13
Maximum of Months 0.327705E+10 2008.44   23.00 16.96 0.927504E+09 569.55   21.70 16.73



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: MECH_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.111144E+10 747.74 11-JAN-21:00 11.10 10.22 0.153160E+09 96.97 11-JAN-22:10 10.82 10.11
February 0.123654E+10 827.99 27-FEB-19:10 15.73 11.89 0.140610E+09 103.19 28-FEB-22:10 8.12 7.00
March 0.174533E+10 837.55 18-MAR-10:33 11.27 7.86 0.161741E+09 102.61 10-MAR-22:10 11.27 7.86
April 0.184448E+10 988.56 27-APR-18:10 25.55 15.86 0.162966E+09 111.65 28-APR-21:10 12.20 10.91
May 0.207876E+10 1047.32 06-MAY-10:33 20.93 16.16 0.177567E+09 114.98 05-MAY-21:19 20.93 16.16
June 0.213079E+10 1068.69 28-JUN-10:33 21.50 14.65 0.178039E+09 117.98 28-JUN-22:10 17.75 13.83
July 0.232496E+10 1173.92 24-JUL-21:00 22.80 16.50 0.189815E+09 120.45 31-JUL-21:19 21.23 16.56
August 0.236299E+10 1298.48 10-AUG-20:57 23.00 16.96 0.192461E+09 120.45 24-AUG-21:19 23.10 17.55
September 0.211011E+10 1077.25 14-SEP-10:33 19.43 16.41 0.177219E+09 118.65 14-SEP-21:19 17.93 14.75
October 0.192234E+10 972.37 04-OCT-10:33 18.33 11.02 0.170239E+09 112.03 04-OCT-21:19 14.63 9.40
November 0.155742E+10 887.41 04-NOV-10:33 17.23 14.47 0.153625E+09 104.54 06-NOV-22:10 15.10 14.35
December 0.126876E+10 762.28 03-DEC-11:33 11.33 5.78 0.153652E+09 96.72 05-DEC-22:10 4.90 1.99
                     
Annual Sum or Average 0.216939E+11         0.201110E+10        
Minimum of Months 0.111144E+10 747.74   11.10 5.78 0.140610E+09 96.72   4.90 1.99
Maximum of Months 0.236299E+10 1298.48   25.55 16.96 0.192461E+09 120.45   23.10 17.55



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.342734E+09 419.11 11-JAN-19:10 12.30 9.41 0.116774E+09 71.44 11-JAN-23:10 9.22 8.15
February 0.515433E+09 471.39 28-FEB-11:33 11.50 10.37 0.106393E+09 75.50 27-FEB-23:10 11.50 10.37
March 0.932782E+09 481.99 18-MAR-10:33 11.27 7.86 0.120257E+09 75.12 10-MAR-23:10 11.27 7.86
April 0.104112E+10 573.39 29-APR-10:33 15.03 12.68 0.121031E+09 82.40 27-APR-21:40 15.03 12.68
May 0.118269E+10 613.64 06-MAY-10:33 20.93 16.16 0.132048E+09 84.92 05-MAY-22:10 20.93 16.16
June 0.121846E+10 623.03 28-JUN-10:33 21.50 14.65 0.132777E+09 87.13 28-JUN-22:10 17.75 13.83
July 0.133292E+10 657.57 24-JUL-18:10 28.72 17.86 0.141767E+09 90.21 24-JUL-21:40 21.33 16.04
August 0.135276E+10 665.62 10-AUG-18:10 30.57 19.31 0.143784E+09 91.33 10-AUG-22:10 21.82 15.74
September 0.120237E+10 626.42 14-SEP-10:33 19.43 16.41 0.131915E+09 87.35 14-SEP-21:40 17.57 14.62
October 0.108233E+10 564.00 04-OCT-10:33 18.33 11.02 0.126202E+09 82.48 04-OCT-22:10 15.73 10.00
November 0.734010E+09 512.21 04-NOV-10:33 17.23 14.47 0.115235E+09 76.68 06-NOV-23:10 15.40 14.28
December 0.451987E+09 441.51 03-DEC-11:33 11.33 5.78 0.116817E+09 70.59 05-DEC-23:10 4.03 2.13
                     
Annual Sum or Average 0.113896E+11         0.150500E+10        
Minimum of Months 0.342734E+09 419.11   11.27 5.78 0.106393E+09 70.59   4.03 2.13
Maximum of Months 0.135276E+10 665.62   30.57 19.31 0.143784E+09 91.33   21.82 16.16



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.481530E+11 36766.16 11-JAN-21:00 11.10 10.22 0.585811E+09 381.60 10-JAN-23:10 11.10 10.22
February 0.440086E+11 37231.64 27-FEB-21:00 12.20 10.06 0.530816E+09 381.61 03-FEB-22:10 12.20 10.06
March 0.496540E+11 37364.02 14-MAR-20:00 14.40 9.49 0.590910E+09 381.68 28-MAR-21:10 7.70 4.73
April 0.487177E+11 38175.36 27-APR-20:00 19.40 13.66 0.572546E+09 381.68 28-APR-21:10 12.20 10.91
May 0.510485E+11 38115.47 15-MAY-20:00 17.20 11.19 0.593025E+09 381.67 10-MAY-21:10 17.20 11.19
June 0.500723E+11 38322.53 28-JUN-19:55 21.70 15.30 0.575889E+09 381.71 26-JUN-21:10 21.70 15.30
July 0.519930E+11 38591.13 24-JUL-20:00 23.90 16.63 0.595000E+09 381.65 12-JUL-21:10 23.90 16.63
August 0.524004E+11 38660.34 10-AUG-20:00 25.60 17.66 0.596887E+09 381.69 08-AUG-21:10 25.60 17.66
September 0.496787E+11 38250.48 14-SEP-20:00 18.90 14.81 0.574817E+09 381.70 05-SEP-21:10 18.90 14.81
October 0.501330E+11 37858.86 04-OCT-20:00 17.20 10.66 0.591919E+09 381.68 06-OCT-21:10 12.70 10.58
November 0.475180E+11 37111.38 02-NOV-20:00 12.80 10.42 0.569820E+09 381.63 16-NOV-22:10 5.40 4.66
December 0.482648E+11 36691.63 05-DEC-21:00 5.60 1.73 0.586425E+09 381.64 22-DEC-22:10 2.10 1.63
                     
Annual Sum or Average 0.591642E+12         0.696387E+10        
Minimum of Months 0.440086E+11 36691.63   5.60 1.73 0.530816E+09 381.60   2.10 1.63
Maximum of Months 0.524004E+11 38660.34   25.60 17.66 0.596887E+09 381.71   25.60 17.66



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.149792E+11 9465.09 08-JAN-11:35 1.33 0.94 0.866360E+10 5749.24 11-JAN-22:40 9.97 8.97
February 0.155555E+11 10937.42 08-FEB-13:30 6.40 3.77 0.808642E+10 6213.71 27-FEB-22:40 12.20 10.25
March 0.188479E+11 12724.48 02-MAR-13:20 12.57 7.60 0.928564E+10 6368.41 14-MAR-21:40 12.40 8.44
April 0.197376E+11 11668.75 27-APR-14:10 26.28 16.91 0.918430E+10 6462.70 27-APR-22:10 14.40 11.00
May 0.211454E+11 11381.55 04-MAY-14:10 23.98 15.25 0.965283E+10 6462.75 04-MAY-22:10 18.43 12.09
June 0.211148E+11 10668.45 10-JUN-10:33 20.20 14.80 0.950875E+10 6462.71 28-JUN-22:10 17.75 13.83
July 0.229289E+11 11382.64 30-JUL-10:33 23.33 16.24 0.100424E+11 6462.74 20-JUL-22:10 23.33 16.24
August 0.236026E+11 13252.01 24-AUG-15:03 29.62 19.18 0.102012E+11 6462.78 11-AUG-22:10 29.62 19.18
September 0.218611E+11 14068.15 23-SEP-13:15 22.57 17.43 0.962877E+10 6462.78 11-SEP-22:10 22.57 17.43
October 0.201613E+11 14123.84 04-OCT-12:50 20.60 11.27 0.949663E+10 6462.61 04-OCT-21:30 15.00 9.56
November 0.162247E+11 12716.09 04-NOV-13:30 20.85 16.00 0.863797E+10 5968.02 02-NOV-21:40 20.85 16.00
December 0.154505E+11 10447.00 02-DEC-11:33 11.83 6.03 0.873422E+10 5890.99 05-DEC-22:40 4.60 2.18
                     
Annual Sum or Average 0.231609E+12         0.111123E+12        
Minimum of Months 0.149792E+11 9465.09   1.33 0.94 0.808642E+10 5749.24   4.60 2.18
Maximum of Months 0.236026E+11 14123.84   29.62 19.18 0.102012E+11 6462.78   29.62 19.18



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.553353E+11 26379.15 11-JAN-22:00 11.10 10.49 0.277647E+11 18393.91 11-JAN-23:10 9.22 8.15
February 0.528331E+11 28454.18 27-FEB-21:00 12.20 10.06 0.257770E+11 19183.09 27-FEB-22:00 12.20 10.35
March 0.618554E+11 29204.60 14-MAR-21:20 12.60 8.62 0.295573E+11 19183.19 02-MAR-22:49 12.60 8.62
April 0.628565E+11 34277.33 27-APR-21:10 16.73 11.41 0.291297E+11 19186.16 27-APR-22:10 14.40 11.00
May 0.675360E+11 34319.19 04-MAY-21:52 18.90 12.17 0.306917E+11 19186.32 15-MAY-21:30 13.35 11.02
June 0.674263E+11 35106.36 28-JUN-21:52 18.30 14.03 0.301400E+11 19186.27 27-JUN-22:10 18.30 14.03
July 0.726260E+11 37863.37 24-JUL-21:10 22.43 16.40 0.314640E+11 19186.25 21-JUL-22:10 22.43 16.40
August 0.740916E+11 39345.61 10-AUG-21:05 22.92 16.74 0.317183E+11 19186.24 31-AUG-22:10 16.50 13.64
September 0.681526E+11 37737.92 14-SEP-21:10 18.12 14.82 0.302020E+11 19186.25 11-SEP-22:10 18.12 14.82
October 0.648630E+11 35229.85 04-OCT-21:10 14.27 9.23 0.301794E+11 19186.00 04-OCT-21:30 15.00 9.56
November 0.571879E+11 29161.79 04-NOV-10:33 17.23 14.47 0.277876E+11 18960.42 06-NOV-23:10 15.40 14.28
December 0.562701E+11 27573.83 03-DEC-11:33 11.33 5.78 0.280199E+11 18758.20 05-DEC-22:49 4.50 2.23
                     
Annual Sum or Average 0.761034E+12         0.352432E+12        
Minimum of Months 0.528331E+11 26379.15   11.10 5.78 0.257770E+11 18393.91   4.50 2.23
Maximum of Months 0.740916E+11 39345.61   22.92 16.74 0.317183E+11 19186.32   22.43 16.40



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 11832991.99 2782.23 05-JAN-16:01 5.73 4.38 93899893.71 56.69 17-JAN-04:19 1.70 -0.1
February 84029528.17 3739.23 12-FEB-16:01 6.52 1.59 86018417.81 56.69 27-FEB-22:19 12.20 10.16
March 0.254152E+09 3783.66 25-MAR-15:01 11.70 3.86 96555957.90 56.69 18-MAR-23:40 11.70 3.86
April 0.658433E+09 3769.96 13-APR-18:01 16.52 9.25 94556866.54 56.69 27-APR-21:30 15.80 11.30
May 0.114736E+10 3905.88 14-MAY-18:01 21.83 11.88 98433889.40 56.69 15-MAY-21:19 13.53 10.95
June 0.132749E+10 3398.63 23-JUN-15:01 16.88 12.55 95569783.84 56.70 28-JUN-21:00 18.30 14.03
July 0.193539E+10 3403.01 25-JUL-08:61 15.18 13.46 98822502.00 56.70 31-JUL-22:49 19.05 15.07
August 0.186452E+10 3457.93 18-AUG-15:01 20.62 14.05 98892538.93 56.70 24-AUG-22:00 20.20 16.47
September 0.129315E+10 3421.22 22-SEP-18:01 20.40 16.20 95169088.32 56.70 13-SEP-21:30 20.40 16.20
October 0.455714E+09 3737.16 03-OCT-18:01 16.02 9.78 96996174.87 56.69 06-OCT-21:10 12.70 10.58
November 66261091.04 3240.64 04-NOV-15:01 20.92 15.94 91949862.42 56.69 04-NOV-23:10 13.30 12.93
December 18808888.64 3143.59 10-DEC-16:01 9.72 8.43 94195360.83 56.69 12-DEC-04:19 1.33 1.33
                     
Annual Sum or Average 0.911714E+10         0.114106E+10        
Minimum of Months 11832991.99 2782.23   5.73 1.59 86018417.81 56.69   1.33 -0.1
Maximum of Months 0.193539E+10 3905.88   21.83 16.20 98892538.93 56.70   20.40 16.47



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 6659749.85 442.14 20-JAN-16:03 5.40 3.78 93227159.84 56.69 17-JAN-04:19 5.40 3.78
February 29528734.82 3116.07 12-FEB-16:01 6.52 1.59 85150177.36 56.69 14-FEB-04:19 0.93 -0.1
March 0.107994E+09 3382.76 25-MAR-15:01 11.70 3.86 95837623.01 57.40 14-MAR-18:10 11.70 3.86
April 0.406250E+09 3893.21 25-APR-17:41 14.60 8.96 95253795.41 73.61 27-APR-21:40 15.33 11.23
May 0.771572E+09 3461.03 29-MAY-19:41 13.27 10.89 0.103462E+09 83.84 31-MAY-18:10 20.40 14.89
June 0.958500E+09 3485.39 18-JUN-20:11 14.63 11.86 0.102402E+09 86.52 19-JUN-18:10 19.22 12.49
July 0.138303E+10 3648.35 25-JUL-16:51 25.60 18.36 0.109588E+09 90.53 21-JUL-18:10 25.60 18.36
August 0.133998E+10 3526.86 02-AUG-18:11 14.53 12.84 0.105846E+09 80.09 08-AUG-21:10 24.15 15.61
September 0.745010E+09 3542.28 22-SEP-16:11 24.43 17.44 0.100734E+09 79.63 08-SEP-18:10 24.43 17.44
October 0.207370E+09 3159.30 06-OCT-15:01 17.30 12.22 96848665.10 70.84 04-OCT-21:10 17.30 12.22
November 28875508.34 2923.63 04-NOV-15:01 20.92 15.94 91377782.64 56.69 04-NOV-23:10 13.30 12.93
December 6988074.06 1063.82 02-DEC-16:01 10.40 4.47 93418721.21 56.69 26-DEC-04:19 -0.9 -0.9
                     
Annual Sum or Average 0.599176E+10         0.117315E+10        
Minimum of Months 6659749.85 442.14   5.40 1.59 85150177.36 56.69   -0.9 -0.9
Maximum of Months 0.138303E+10 3893.21   25.60 18.36 0.109588E+09 90.53   25.60 18.36



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 8738062.53 129.71 08-JAN-15:15 5.20 2.41 0.00 0.00 01-JAN-00:10 5.20 2.41
February 61914643.11 475.70 08-FEB-13:40 6.50 3.79 0.00 0.00 01-FEB-00:10 6.50 3.79
March 0.165703E+09 605.89 02-MAR-13:00 12.20 7.34 0.00 0.00 01-MAR-00:10 12.20 7.34
April 0.260067E+09 550.05 27-APR-13:05 26.10 16.37 0.00 0.00 01-APR-00:10 26.10 16.37
May 0.325207E+09 530.52 04-MAY-13:20 22.77 15.31 0.00 0.00 01-MAY-00:10 22.77 15.31
June 0.359694E+09 399.86 28-JUN-13:05 24.50 15.71 0.00 0.00 01-JUN-00:10 24.50 15.71
July 0.485950E+09 499.21 31-JUL-13:20 27.57 18.47 0.00 0.00 01-JUL-00:10 27.57 18.47
August 0.547027E+09 626.10 24-AUG-13:05 28.93 19.36 0.00 0.00 01-AUG-00:10 28.93 19.36
September 0.467400E+09 670.75 14-SEP-13:30 23.35 17.43 0.00 0.00 01-SEP-00:10 23.35 17.43
October 0.279338E+09 700.17 04-OCT-12:40 20.60 11.32 0.00 0.00 01-OCT-00:10 20.60 11.32
November 57323539.07 542.82 04-NOV-13:30 20.85 16.00 0.00 0.00 01-NOV-00:10 20.85 16.00
December 32369909.92 432.40 05-DEC-12:30 10.30 6.13 0.00 0.00 01-DEC-00:10 10.30 6.13
                     
Annual Sum or Average 0.305073E+10         0.00        
Minimum of Months 8738062.53 129.71   5.20 2.41 0.00 0.00   5.20 2.41
Maximum of Months 0.547027E+09 700.17   28.93 19.36 0.00 0.00   28.93 19.36



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 74977347.93 808.46 01-JAN-09:02 7.80 6.49 95175589.53 56.69 11-JAN-22:10 10.82 10.11
February 0.111168E+09 909.70 26-FEB-09:02 9.60 8.77 86418366.02 56.69 27-FEB-22:10 12.20 10.11
March 0.226056E+09 992.67 28-MAR-18:01 10.92 4.32 96579252.53 56.69 09-MAR-22:10 10.92 4.32
April 0.339639E+09 1029.71 01-APR-21:52 20.60 9.92 94678050.56 70.01 27-APR-21:00 14.40 11.03
May 0.461595E+09 1093.96 14-MAY-21:51 16.70 9.76 99968129.83 75.73 15-MAY-21:10 13.72 10.88
June 0.521547E+09 1010.03 22-JUN-21:51 15.60 12.67 98887542.96 74.38 22-JUN-21:49 15.60 12.67
July 0.590220E+09 1017.51 25-JUL-15:02 22.98 16.69 0.103564E+09 76.31 26-JUL-21:10 20.68 16.76
August 0.578615E+09 1015.09 08-AUG-21:31 23.70 15.01 0.102709E+09 73.93 18-AUG-21:10 15.13 12.34
September 0.426144E+09 1008.00 11-SEP-15:01 23.30 15.89 97242937.74 72.33 13-SEP-21:49 18.30 14.68
October 0.291501E+09 1016.02 02-OCT-18:01 14.32 8.97 96949203.91 68.33 04-OCT-21:10 14.27 9.23
November 0.163895E+09 901.27 05-NOV-08:62 12.88 12.19 92910215.64 56.69 06-NOV-23:30 15.00 13.69
December 76656931.62 941.01 03-DEC-09:02 7.98 3.60 95225712.45 56.69 12-DEC-04:19 1.33 1.33
                     
Annual Sum or Average 0.386202E+10         0.116031E+10        
Minimum of Months 74977347.93 808.46   7.80 3.60 86418366.02 56.69   1.33 1.33
Maximum of Months 0.590220E+09 1093.96   23.70 16.69 0.103564E+09 76.31   20.68 16.76



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 12165589.78 471.52 20-JAN-16:02 5.40 3.78 93820006.30 56.69 17-JAN-04:19 5.40 3.78
February 78663920.26 3222.62 12-FEB-16:01 6.52 1.59 86069873.27 56.69 19-FEB-02:20 -4.0 -4.7
March 0.249291E+09 3438.76 25-MAR-08:61 4.78 0.26 96767147.90 56.69 18-MAR-23:19 4.78 0.26
April 0.674947E+09 3319.40 13-APR-18:01 16.52 9.25 94898051.54 56.69 29-APR-23:00 15.00 12.75
May 0.101000E+10 3491.51 14-MAY-18:01 21.83 11.88 98495565.58 56.69 15-MAY-21:10 13.72 10.88
June 0.139221E+10 3120.84 18-JUN-08:62 12.57 10.53 95738974.97 56.70 28-JUN-21:30 17.50 13.87
July 0.169940E+10 3138.89 11-JUL-15:01 21.88 17.19 98894271.43 56.70 24-JUL-22:49 19.60 15.45
August 0.183390E+10 3191.38 25-AUG-08:61 19.83 16.44 99014203.29 56.70 25-AUG-21:30 21.25 16.32
September 0.117965E+10 3168.61 23-SEP-08:61 14.27 13.74 95140588.47 56.70 12-SEP-21:40 14.27 13.74
October 0.447314E+09 3281.83 03-OCT-18:01 16.02 9.78 97115979.28 56.69 04-OCT-23:40 13.50 9.95
November 71102019.48 3167.07 04-NOV-15:01 20.92 15.94 91923667.38 56.69 04-NOV-23:10 13.30 12.93
December 27289292.31 2377.31 02-DEC-09:02 8.58 4.35 94115969.73 56.69 26-DEC-04:19 -0.9 -0.9
                     
Annual Sum or Average 0.867593E+10         0.114199E+10        
Minimum of Months 12165589.78 471.52   4.78 0.26 86069873.27 56.69   -4.0 -4.7
Maximum of Months 0.183390E+10 3491.51   21.88 17.19 99014203.29 56.70   21.25 16.32



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 5902699.24 354.13 27-JAN-19:06 8.30 5.90 93158393.40 56.69 17-JAN-04:19 8.30 5.90
February 25640873.50 2509.90 27-FEB-16:01 19.32 12.38 85089899.06 56.69 14-FEB-04:19 19.32 12.38
March 0.100108E+09 3157.57 25-MAR-08:61 4.78 0.26 95879193.53 56.69 19-MAR-01:19 4.78 0.26
April 0.430995E+09 3130.84 25-APR-18:01 13.95 8.77 95203236.98 71.11 27-APR-21:40 15.33 11.23
May 0.719269E+09 3387.43 06-MAY-08:51 19.40 15.38 0.100907E+09 75.83 15-MAY-21:10 13.72 10.88
June 0.106713E+10 3205.99 10-JUN-08:51 18.30 14.28 0.100536E+09 74.47 21-JUN-21:40 16.33 12.50
July 0.125029E+10 3662.15 24-JUL-08:32 23.17 16.50 0.105464E+09 77.58 24-JUL-21:19 22.07 16.28
August 0.132918E+10 3578.19 10-AUG-08:32 22.00 17.03 0.104789E+09 77.44 08-AUG-21:10 22.00 17.03
September 0.714696E+09 3324.97 13-SEP-08:51 18.30 15.25 98265335.46 74.44 13-SEP-21:40 18.30 14.73
October 0.208233E+09 2803.02 07-OCT-08:61 10.18 9.20 96627653.04 67.19 04-OCT-21:10 10.18 9.20
November 30221871.52 2465.33 04-NOV-15:01 20.92 15.94 91280826.95 56.69 12-NOV-02:20 2.80 2.46
December 7783159.08 812.59 02-DEC-09:02 8.58 4.35 93326230.91 56.69 26-DEC-04:19 -0.9 -0.9
                     
Annual Sum or Average 0.588945E+10         0.116053E+10        
Minimum of Months 5902699.24 354.13   4.78 0.26 85089899.06 56.69   -0.9 -0.9
Maximum of Months 0.132918E+10 3662.15   23.17 17.03 0.105464E+09 77.58   22.07 17.03



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.189700E+10 1574.00 11-JAN-21:00 11.10 10.22 0.119930E+10 722.26 11-JAN-22:49 9.68 8.60
February 0.241833E+10 1788.66 27-FEB-19:10 15.73 11.89 0.109023E+10 756.31 27-FEB-23:10 12.20 10.40
March 0.357212E+10 1900.42 25-MAR-10:33 8.87 1.80 0.123326E+10 768.66 02-MAR-22:49 8.87 1.80
April 0.401413E+10 2241.77 27-APR-18:10 25.55 15.86 0.123744E+10 840.83 27-APR-21:40 15.33 11.23
May 0.458348E+10 2340.16 06-MAY-10:33 20.93 16.16 0.135294E+10 861.72 15-MAY-21:40 13.17 11.09
June 0.466864E+10 2398.50 28-JUN-10:33 21.50 14.65 0.134908E+10 880.83 28-JUN-22:10 17.75 13.83
July 0.510409E+10 2532.57 24-JUL-18:10 28.72 17.86 0.143913E+10 908.53 24-JUL-21:40 21.33 16.04
August 0.518568E+10 2578.50 13-AUG-10:33 24.17 17.28 0.145998E+10 920.07 10-AUG-21:40 24.17 17.28
September 0.462786E+10 2480.27 14-SEP-10:33 19.43 16.41 0.134484E+10 904.20 14-SEP-21:40 17.57 14.62
October 0.396640E+10 2202.16 04-OCT-10:33 18.33 11.02 0.127185E+10 839.57 04-OCT-22:10 15.73 10.00
November 0.266014E+10 1910.63 04-NOV-10:33 17.23 14.47 0.116846E+10 745.94 05-NOV-23:19 11.10 9.49
December 0.209622E+10 1736.49 03-DEC-11:33 11.33 5.78 0.120002E+10 725.63 05-DEC-22:49 4.50 2.23
                     
Annual Sum or Average 0.447941E+11         0.153465E+11        
Minimum of Months 0.189700E+10 1574.00   8.87 1.80 0.109023E+10 722.26   4.50 1.80
Maximum of Months 0.518568E+10 2578.50   28.72 17.86 0.145998E+10 920.07   24.17 17.28



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 8214409.01 2846.45 05-JAN-16:01 5.73 4.38 93258913.14 56.69 17-JAN-04:19 1.70 -0.1
February 71413914.50 3880.23 12-FEB-16:01 6.52 1.59 85527114.74 56.69 17-FEB-04:19 1.50 -0.2
March 0.236488E+09 3937.58 25-MAR-15:01 11.70 3.86 96180250.91 56.69 19-MAR-00:30 11.70 3.86
April 0.639447E+09 3924.50 13-APR-18:01 16.52 9.25 94359577.84 56.69 28-APR-00:00 14.40 12.20
May 0.113078E+10 4071.74 14-MAY-18:01 21.83 11.88 98306593.21 56.69 26-MAY-22:19 10.73 10.73
June 0.132558E+10 3537.66 23-JUN-15:01 16.88 12.55 95496303.66 56.70 22-JUN-21:00 16.88 12.55
July 0.197377E+10 3436.55 24-JUL-08:61 22.07 16.26 98747575.79 56.70 27-JUL-21:30 18.35 14.93
August 0.185966E+10 3586.09 18-AUG-15:01 20.62 14.05 98805029.62 56.70 24-AUG-22:30 21.05 16.84
September 0.124308E+10 3549.10 22-SEP-18:01 20.40 16.20 94992808.72 56.69 22-SEP-22:49 15.78 14.24
October 0.390621E+09 3919.09 04-OCT-18:01 17.52 10.01 96644800.63 56.69 16-OCT-21:30 9.70 8.39
November 55918450.57 3356.65 04-NOV-18:01 15.00 13.34 91429214.06 56.69 05-NOV-02:30 13.05 12.26
December 12699577.90 3220.79 10-DEC-16:01 9.72 8.43 93652902.22 56.69 22-DEC-04:19 0.20 -0.9
                     
Annual Sum or Average 0.894768E+10         0.113740E+10        
Minimum of Months 8214409.01 2846.45   5.73 1.59 85527114.74 56.69   0.20 -0.9
Maximum of Months 0.197377E+10 4071.74   22.07 16.26 98805029.62 56.70   21.05 16.84



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 1996174.39 432.48 20-JAN-16:05 5.40 3.78 92708419.71 56.69 16-JAN-02:20 5.40 3.78
February 20440061.53 3052.08 26-FEB-16:01 14.40 10.25 84651624.81 56.69 14-FEB-04:19 14.40 10.25
March 90684292.42 3471.91 25-MAR-15:01 11.70 3.86 95441348.91 60.83 14-MAR-18:10 11.70 3.86
April 0.381677E+09 4036.24 25-APR-17:41 14.60 8.96 95258835.56 75.79 26-APR-21:19 14.67 10.66
May 0.755337E+09 4031.89 21-MAY-17:41 15.60 9.45 0.104445E+09 90.41 31-MAY-18:10 20.40 14.89
June 0.970660E+09 3674.11 19-JUN-21:51 16.70 12.03 0.103518E+09 94.03 19-JUN-21:10 16.70 12.03
July 0.145249E+10 3788.39 19-JUL-21:51 16.70 12.02 0.111287E+09 97.08 21-JUL-21:10 17.12 12.73
August 0.135485E+10 3715.74 06-AUG-21:51 17.90 14.41 0.106358E+09 83.64 11-AUG-18:10 20.88 15.38
September 0.691410E+09 3656.96 22-SEP-16:11 24.43 17.44 0.101584E+09 86.85 08-SEP-18:10 24.43 17.44
October 0.151049E+09 3267.18 07-OCT-15:01 18.03 12.32 96485916.51 71.48 04-OCT-21:10 18.03 12.32
November 19288948.37 3004.83 04-NOV-15:01 20.92 15.94 90838958.26 56.69 29-NOV-00:20 8.00 7.36
December 3466904.39 359.90 29-DEC-19:06 9.32 7.90 92884539.99 56.69 12-DEC-04:19 9.32 7.90
                     
Annual Sum or Average 0.589335E+10         0.117546E+10        
Minimum of Months 1996174.39 359.90   5.40 3.78 84651624.81 56.69   5.40 3.78
Maximum of Months 0.145249E+10 4036.24   24.43 17.44 0.111287E+09 97.08   24.43 17.44



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 68836498.76 1976.31 05-JAN-16:01 5.73 4.38 95187880.77 56.69 20-JAN-04:19 -0.4 -0.8
February 0.229836E+09 2126.45 26-FEB-16:01 14.40 10.25 87134909.51 56.69 27-FEB-23:10 12.20 10.40
March 0.399456E+09 2450.94 25-MAR-15:01 11.70 3.86 97421529.59 56.69 18-MAR-23:40 11.70 3.86
April 0.591384E+09 2360.62 13-APR-18:01 16.52 9.25 94999841.17 56.69 27-APR-21:10 16.73 11.41
May 0.735303E+09 2438.96 14-MAY-18:01 21.83 11.88 98484010.23 56.69 06-MAY-23:49 21.83 11.88
June 0.818758E+09 2170.71 25-JUN-08:61 15.78 11.63 95559299.48 56.69 08-JUN-21:30 15.78 11.63
July 0.107508E+10 2184.61 11-JUL-15:01 21.88 17.19 98727263.04 56.70 24-JUL-21:00 20.60 15.77
August 0.117383E+10 2211.69 18-AUG-15:01 20.62 14.05 98825093.88 56.70 29-AUG-21:00 19.90 15.56
September 0.978858E+09 2224.92 22-SEP-18:01 20.40 16.20 95255869.11 56.70 14-SEP-21:00 20.40 16.20
October 0.584753E+09 2412.00 04-OCT-18:01 17.52 10.01 97732182.76 56.69 04-OCT-21:10 14.27 9.23
November 0.171239E+09 2143.39 02-NOV-15:01 13.30 11.14 92987808.11 56.69 04-NOV-23:10 13.30 12.93
December 0.130980E+09 2123.83 10-DEC-16:01 9.72 8.43 95361021.54 56.69 04-DEC-00:20 9.72 8.43
                     
Annual Sum or Average 0.695831E+10         0.114768E+10        
Minimum of Months 68836498.76 1976.31   5.73 3.86 87134909.51 56.69   -0.4 -0.8
Maximum of Months 0.117383E+10 2450.94   21.88 17.19 98825093.88 56.70   21.83 16.20



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.314696E+11 18024.62 11-JAN-23:00 9.40 8.23 0.189072E+11 11347.93 20-JAN-04:19 -0.4 -0.8
February 0.292260E+11 19050.19 27-FEB-23:00 12.20 10.35 0.171628E+11 11347.91 10-FEB-04:19 12.20 10.35
March 0.341390E+11 18939.41 10-MAR-23:00 11.10 10.84 0.192030E+11 11347.94 30-MAR-23:19 7.60 4.67
April 0.348895E+11 20763.65 27-APR-21:10 16.73 11.41 0.186076E+11 11349.01 27-APR-22:10 14.40 11.00
May 0.381110E+11 21101.62 05-MAY-21:53 17.80 12.72 0.192908E+11 11349.23 15-MAY-21:30 13.35 11.02
June 0.384357E+11 21541.59 28-JUN-21:52 18.30 14.03 0.187215E+11 11349.22 27-JUN-22:10 18.30 14.03
July 0.408682E+11 22260.17 24-JUL-21:10 22.43 16.40 0.192853E+11 11349.21 21-JUL-22:10 22.43 16.40
August 0.408698E+11 22252.06 10-AUG-21:52 22.50 15.63 0.193584E+11 11349.20 11-AUG-22:10 15.85 13.74
September 0.370639E+11 20993.24 12-SEP-21:52 18.30 14.27 0.186448E+11 11349.20 11-SEP-22:10 18.30 14.27
October 0.351800E+11 19842.50 04-OCT-22:00 16.10 10.03 0.191637E+11 11348.80 04-OCT-21:30 16.10 10.03
November 0.320508E+11 18994.71 06-NOV-23:00 15.60 14.58 0.184121E+11 11347.85 09-NOV-00:20 7.97 6.86
December 0.316566E+11 17779.87 29-DEC-23:00 8.90 7.76 0.189473E+11 11348.12 04-DEC-00:20 8.90 7.76
                     
Annual Sum or Average 0.423960E+12         0.225705E+12        
Minimum of Months 0.292260E+11 17779.87   8.90 7.76 0.171628E+11 11347.85   -0.4 -0.8
Maximum of Months 0.408698E+11 22260.17   22.50 16.40 0.193584E+11 11349.23   22.43 16.40



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DINING_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.352262E+11 20072.51 11-JAN-22:10 10.82 10.11 0.191075E+11 11347.97 17-JAN-04:19 1.70 -0.1
February 0.326637E+11 20862.22 27-FEB-23:00 12.20 10.35 0.173173E+11 11347.95 10-FEB-04:19 12.20 10.35
March 0.380223E+11 20842.23 08-MAR-23:00 13.90 9.29 0.193135E+11 11347.96 30-MAR-23:19 7.60 4.67
April 0.385910E+11 22275.99 27-APR-21:10 16.73 11.41 0.186777E+11 11349.01 27-APR-22:10 14.40 11.00
May 0.417513E+11 22607.98 05-MAY-21:20 18.53 12.90 0.193306E+11 11368.65 05-MAY-21:19 18.53 12.90
June 0.418089E+11 22890.50 28-JUN-21:20 17.23 13.81 0.187492E+11 11369.48 27-JUN-21:19 17.23 13.81
July 0.441611E+11 23521.14 24-JUL-21:20 22.07 16.28 0.193037E+11 11369.62 21-JUL-21:19 22.07 16.28
August 0.441035E+11 23456.67 10-AUG-21:05 22.92 16.74 0.193817E+11 11369.88 23-AUG-21:19 21.47 16.20
September 0.404221E+11 22321.33 12-SEP-21:20 19.03 14.58 0.186851E+11 11349.28 12-SEP-21:19 19.03 14.58
October 0.389836E+11 21367.20 04-OCT-22:00 16.10 10.03 0.192501E+11 11348.81 04-OCT-21:30 16.10 10.03
November 0.358041E+11 20857.51 06-NOV-23:00 15.60 14.58 0.185546E+11 11347.86 09-NOV-00:20 7.97 6.86
December 0.354504E+11 19809.67 29-DEC-23:00 8.90 7.76 0.191308E+11 11348.18 04-DEC-00:20 8.90 7.76
                     
Annual Sum or Average 0.466988E+12         0.226802E+12        
Minimum of Months 0.326637E+11 19809.67   8.90 7.76 0.173173E+11 11347.86   1.70 -0.1
Maximum of Months 0.441611E+11 23521.14   22.92 16.74 0.193817E+11 11369.88   22.07 16.28



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.492109E+11 26602.78 30-JAN-11:33 8.13 6.36 0.188193E+11 11319.62 21-JAN-18:19 8.13 6.36
February 0.454186E+11 27755.78 27-FEB-11:45 16.23 10.66 0.170028E+11 11319.62 18-FEB-18:19 16.23 10.66
March 0.517697E+11 28894.50 14-MAR-10:45 11.42 8.58 0.188394E+11 11319.62 18-MAR-17:19 19.03 9.50
April 0.518344E+11 30227.01 27-APR-10:33 20.37 13.53 0.182339E+11 11319.65 29-APR-17:19 20.57 14.52
May 0.547707E+11 30342.60 14-MAY-10:33 20.03 12.68 0.188485E+11 11319.65 20-MAY-17:19 16.87 9.98
June 0.542583E+11 30623.93 10-JUN-10:33 20.20 14.80 0.182502E+11 11319.65 24-JUN-17:19 19.23 11.83
July 0.567124E+11 31021.13 24-JUL-10:37 25.93 17.48 0.188559E+11 11319.69 29-JUL-17:19 23.17 15.48
August 0.569796E+11 31091.67 13-AUG-10:40 24.17 17.28 0.188647E+11 11319.68 12-AUG-17:19 24.17 17.28
September 0.533915E+11 30544.84 10-SEP-10:33 18.33 13.89 0.182450E+11 11319.66 23-SEP-17:19 21.67 16.65
October 0.526095E+11 29366.68 07-OCT-10:33 14.63 10.97 0.188401E+11 11319.60 28-OCT-17:19 10.73 7.68
November 0.489733E+11 28888.15 04-NOV-10:45 17.52 14.63 0.182212E+11 11319.64 25-NOV-18:19 7.40 6.48
December 0.494769E+11 27114.85 03-DEC-11:50 11.52 5.93 0.188208E+11 11319.61 23-DEC-18:19 5.60 4.96
                     
Annual Sum or Average 0.625406E+12         0.221842E+12        
Minimum of Months 0.454186E+11 26602.78   8.13 5.93 0.170028E+11 11319.60   5.60 4.96
Maximum of Months 0.569796E+11 31091.67   25.93 17.48 0.188647E+11 11319.69   24.17 17.28



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.373648E+10 3346.98 30-JAN-11:33 8.13 6.36 0.126910E+10 765.10 11-JAN-22:40 8.13 6.36
February 0.469627E+10 3751.87 27-FEB-11:45 16.23 10.66 0.115471E+10 819.49 27-FEB-22:40 12.20 10.25
March 0.710433E+10 3974.38 02-MAR-11:33 9.63 6.30 0.130596E+10 833.22 14-MAR-21:40 12.40 8.44
April 0.807847E+10 4787.93 27-APR-18:10 25.55 15.86 0.131557E+10 920.31 27-APR-21:30 15.80 11.30
May 0.926972E+10 4945.36 06-MAY-10:33 20.93 16.16 0.143164E+10 926.78 15-MAY-21:30 13.35 11.02
June 0.956570E+10 5090.45 28-JUN-18:10 25.40 16.48 0.144202E+10 959.19 28-JUN-21:30 17.50 13.87
July 0.104578E+11 5360.37 24-JUL-18:10 28.72 17.86 0.153889E+10 993.07 24-JUL-21:30 21.70 16.16
August 0.105609E+11 6159.39 10-AUG-15:03 30.37 18.88 0.155244E+10 1005.53 10-AUG-21:30 22.75 16.30
September 0.926779E+10 5093.60 14-SEP-10:33 19.43 16.41 0.141498E+10 958.02 14-SEP-21:30 17.75 14.69
October 0.793499E+10 4562.15 04-OCT-10:33 18.33 11.02 0.133658E+10 888.01 04-OCT-22:10 15.73 10.00
November 0.548544E+10 4044.72 04-NOV-10:50 17.52 14.63 0.123876E+10 803.16 05-NOV-23:19 11.10 9.49
December 0.409284E+10 3610.45 03-DEC-11:33 11.33 5.78 0.126979E+10 753.05 29-DEC-22:40 8.90 7.67
                     
Annual Sum or Average 0.902506E+11         0.162704E+11        
Minimum of Months 0.373648E+10 3346.98   8.13 5.78 0.115471E+10 753.05   8.13 6.36
Maximum of Months 0.105609E+11 6159.39   30.37 18.88 0.155244E+10 1005.53   22.75 16.30



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BASEMENT

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 5.92
February 0.00 0.00 01-FEB-00:03 7.00
March 0.00 0.00 01-MAR-00:03 5.92
April 0.00 0.00 01-APR-00:10 7.93
May 0.00 0.00 01-MAY-00:05 10.38
June 0.00 0.00 01-JUN-00:05 12.83
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:05 17.17
September 0.00 0.00 01-SEP-00:05 16.38
October 0.00 0.00 01-OCT-00:10 14.35
November 0.00 0.00 01-NOV-00:05 9.22
December 0.00 0.00 01-DEC-00:03 4.40
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   4.40
Maximum of Months 0.00 0.00   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 78654395.50 458.93 16-JAN-17:00 1.70
February 32662351.08 611.45 19-FEB-06:00 -5.6
March 107098.37 51.02 05-MAR-18:00 5.60
April 0.00 0.00 01-APR-00:10 7.93
May 0.00 0.00 01-MAY-00:05 10.38
June 0.00 0.00 01-JUN-00:05 12.83
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:05 17.17
September 0.00 0.00 01-SEP-00:05 16.38
October 0.00 0.00 01-OCT-00:10 14.35
November 10118138.99 276.13 30-NOV-16:00 4.40
December 84523361.88 623.77 26-DEC-12:00 0.20
         
Annual Sum or Average 0.206065E+09      
Minimum of Months 0.00 0.00   -5.6
Maximum of Months 84523361.88 623.77   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 5.92
February 0.00 0.00 01-FEB-00:03 7.00
March 0.00 0.00 01-MAR-00:03 5.92
April 0.00 0.00 01-APR-00:10 7.93
May 0.00 0.00 01-MAY-00:05 10.38
June 0.00 0.00 01-JUN-00:05 12.83
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:05 17.17
September 0.00 0.00 01-SEP-00:05 16.38
October 0.00 0.00 01-OCT-00:10 14.35
November 0.00 0.00 01-NOV-00:05 9.22
December 0.00 0.00 01-DEC-00:03 4.40
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   4.40
Maximum of Months 0.00 0.00   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: MECH_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 1069286.70 71.89 16-JAN-15:50 2.20
February 0.00 0.00 01-FEB-00:03 7.00
March 0.00 0.00 01-MAR-00:03 5.92
April 0.00 0.00 01-APR-00:10 7.93
May 0.00 0.00 01-MAY-00:05 10.38
June 0.00 0.00 01-JUN-00:05 12.83
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:05 17.17
September 0.00 0.00 01-SEP-00:05 16.38
October 0.00 0.00 01-OCT-00:10 14.35
November 0.00 0.00 01-NOV-00:05 9.22
December 285259.28 31.35 26-DEC-14:50 2.03
         
Annual Sum or Average 1354545.98      
Minimum of Months 0.00 0.00   2.03
Maximum of Months 1069286.70 71.89   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 18034691.49 167.68 16-JAN-16:00 2.20
February 8841903.90 134.33 19-FEB-06:00 -5.6
March 0.00 0.00 01-MAR-00:03 5.92
April 0.00 0.00 01-APR-00:10 7.93
May 0.00 0.00 01-MAY-00:05 10.38
June 0.00 0.00 01-JUN-00:05 12.83
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:05 17.17
September 0.00 0.00 01-SEP-00:05 16.38
October 0.00 0.00 01-OCT-00:10 14.35
November 14611.92 7.85 30-NOV-16:00 4.40
December 9837511.69 153.51 26-DEC-14:50 2.03
         
Annual Sum or Average 36728719.00      
Minimum of Months 0.00 0.00   -5.6
Maximum of Months 18034691.49 167.68   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 5.92
February 0.00 0.00 01-FEB-00:03 7.00
March 0.00 0.00 01-MAR-00:03 5.92
April 0.00 0.00 01-APR-00:10 7.93
May 0.00 0.00 01-MAY-00:05 10.38
June 0.00 0.00 01-JUN-00:05 12.83
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:05 17.17
September 0.00 0.00 01-SEP-00:05 16.38
October 0.00 0.00 01-OCT-00:10 14.35
November 0.00 0.00 01-NOV-00:05 9.22
December 0.00 0.00 01-DEC-00:03 4.40
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   4.40
Maximum of Months 0.00 0.00   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 5.92
February 0.00 0.00 01-FEB-00:03 7.00
March 0.00 0.00 01-MAR-00:03 5.92
April 0.00 0.00 01-APR-00:10 7.93
May 0.00 0.00 01-MAY-00:05 10.38
June 0.00 0.00 01-JUN-00:05 12.83
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:05 17.17
September 0.00 0.00 01-SEP-00:05 16.38
October 0.00 0.00 01-OCT-00:10 14.35
November 0.00 0.00 01-NOV-00:05 9.22
December 0.00 0.00 01-DEC-00:03 4.40
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   4.40
Maximum of Months 0.00 0.00   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 5.92
February 0.00 0.00 01-FEB-00:03 7.00
March 0.00 0.00 01-MAR-00:03 5.92
April 0.00 0.00 01-APR-00:10 7.93
May 0.00 0.00 01-MAY-00:05 10.38
June 0.00 0.00 01-JUN-00:05 12.83
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:05 17.17
September 0.00 0.00 01-SEP-00:05 16.38
October 0.00 0.00 01-OCT-00:10 14.35
November 0.00 0.00 01-NOV-00:05 9.22
December 0.00 0.00 01-DEC-00:03 4.40
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   4.40
Maximum of Months 0.00 0.00   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.767817E+09 1249.63 16-JAN-16:13 2.03
February 0.433986E+09 1229.95 03-FEB-16:03 8.90
March 0.186791E+09 1265.46 15-MAR-18:04 10.40
April 59653728.50 1305.25 18-APR-15:04 9.22
May 10167926.45 1176.34 12-MAY-08:03 10.97
June 3210512.53 1237.30 13-JUN-18:04 11.02
July 2066511.49 1010.49 17-JUL-18:04 17.02
August 2719924.70 1038.10 08-AUG-08:04 20.10
September 6043860.88 1147.74 27-SEP-15:03 13.30
October 80192812.60 1137.58 27-OCT-15:02 10.82
November 0.395929E+09 1240.26 30-NOV-16:13 4.60
December 0.698665E+09 1259.72 26-DEC-16:13 3.73
         
Annual Sum or Average 0.264724E+10      
Minimum of Months 2066511.49 1010.49   2.03
Maximum of Months 0.767817E+09 1305.25   20.10



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.905368E+09 1232.79 16-JAN-16:13 2.03
February 0.574247E+09 1274.49 12-FEB-16:03 6.52
March 0.267388E+09 1277.32 24-MAR-15:03 9.32
April 80668188.67 1218.64 13-APR-19:44 14.60
May 10961189.40 1109.09 11-MAY-18:04 12.12
June 3706664.78 1241.36 06-JUN-18:04 10.78
July 2007242.40 1065.92 25-JUL-08:04 15.18
August 2426101.03 1183.06 23-AUG-08:53 21.20
September 6787206.93 1198.14 21-SEP-15:04 17.30
October 0.123336E+09 1259.66 14-OCT-15:03 11.60
November 0.497003E+09 1216.40 30-NOV-16:13 4.60
December 0.839424E+09 1234.43 26-DEC-16:13 3.73
         
Annual Sum or Average 0.331332E+10      
Minimum of Months 2007242.40 1065.92   2.03
Maximum of Months 0.905368E+09 1277.32   21.20



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 5.92
February 0.00 0.00 01-FEB-00:03 7.00
March 0.00 0.00 01-MAR-00:03 5.92
April 0.00 0.00 01-APR-00:10 7.93
May 0.00 0.00 01-MAY-00:05 10.38
June 0.00 0.00 01-JUN-00:05 12.83
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:05 17.17
September 0.00 0.00 01-SEP-00:05 16.38
October 0.00 0.00 01-OCT-00:10 14.35
November 0.00 0.00 01-NOV-00:05 9.22
December 0.00 0.00 01-DEC-00:03 4.40
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   4.40
Maximum of Months 0.00 0.00   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 42434475.01 333.65 07-JAN-16:01 2.70
February 23066497.40 330.64 12-FEB-09:04 1.97
March 2049874.50 330.56 01-MAR-16:03 12.20
April 750255.28 327.37 06-APR-08:04 9.18
May 509902.24 329.02 21-MAY-15:06 16.10
June 149264.96 325.46 04-JUN-15:06 17.12
July 130507.35 330.69 03-JUL-15:06 16.42
August 242848.02 305.63 02-AUG-15:06 18.37
September 582828.01 328.07 28-SEP-08:04 10.28
October 1599597.82 316.70 12-OCT-15:04 14.90
November 6327095.30 318.20 12-NOV-16:01 4.72
December 26563743.94 328.64 23-DEC-09:04 4.40
         
Annual Sum or Average 0.104407E+09      
Minimum of Months 130507.35 305.63   1.97
Maximum of Months 42434475.01 333.65   18.37



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.772918E+09 1224.38 16-JAN-16:13 2.03
February 0.435703E+09 1190.12 16-FEB-16:13 2.80
March 0.180806E+09 1220.50 21-MAR-15:04 13.12
April 55734651.33 1244.85 09-APR-15:04 14.32
May 12483556.27 1160.59 16-MAY-18:04 13.72
June 2565958.95 1209.36 14-JUN-15:04 14.40
July 2334988.76 1235.28 16-JUL-15:04 17.80
August 2341762.62 1173.33 17-AUG-18:04 18.58
September 7856641.27 1247.22 21-SEP-15:04 17.30
October 83163885.72 1266.50 01-OCT-15:04 16.70
November 0.399783E+09 1214.51 30-NOV-16:13 4.60
December 0.705275E+09 1232.91 26-DEC-16:13 3.73
         
Annual Sum or Average 0.266097E+10      
Minimum of Months 2334988.76 1160.59   2.03
Maximum of Months 0.772918E+09 1266.50   18.58



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.912474E+09 1215.59 07-JAN-16:01 2.70
February 0.573288E+09 1197.74 19-FEB-16:01 2.62
March 0.251474E+09 1222.28 26-MAR-15:03 10.60
April 75095212.37 1115.55 23-APR-15:04 18.30
May 14167422.78 1244.34 29-MAY-15:04 15.68
June 2742851.09 1218.14 07-JUN-15:04 15.92
July 1976161.31 1164.11 01-JUL-08:04 15.10
August 1481090.85 1122.65 03-AUG-15:04 19.30
September 9194612.56 1227.75 06-SEP-15:04 16.02
October 0.124952E+09 1224.36 07-OCT-15:04 18.03
November 0.494287E+09 1199.85 12-NOV-16:01 4.72
December 0.840844E+09 1209.31 26-DEC-16:13 3.73
         
Annual Sum or Average 0.330198E+10      
Minimum of Months 1481090.85 1115.55   2.62
Maximum of Months 0.912474E+09 1244.34   19.30



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 3271975.39 238.36 16-JAN-16:00 2.20
February 72909.29 32.00 17-FEB-10:30 1.15
March 0.00 0.00 01-MAR-00:03 5.92
April 0.00 0.00 01-APR-00:10 7.93
May 0.00 0.00 01-MAY-00:05 10.38
June 0.00 0.00 01-JUN-00:05 12.83
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:05 17.17
September 0.00 0.00 01-SEP-00:05 16.38
October 0.00 0.00 01-OCT-00:10 14.35
November 313353.26 66.58 30-NOV-15:00 5.00
December 8645497.41 340.44 26-DEC-15:00 2.20
         
Annual Sum or Average 12303735.35      
Minimum of Months 0.00 0.00   1.15
Maximum of Months 8645497.41 340.44   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.118808E+10 1510.83 16-JAN-16:13 2.03
February 0.719073E+09 1471.18 18-FEB-19:13 -1.0
March 0.379837E+09 1420.62 05-MAR-16:02 6.02
April 0.144463E+09 1381.26 19-APR-08:62 5.87
May 39657593.47 1313.87 18-MAY-08:62 6.28
June 7116457.20 1081.29 13-JUN-18:04 11.02
July 2172658.71 1200.21 04-JUL-08:03 12.98
August 2526357.13 957.65 17-AUG-18:04 18.58
September 16563319.61 1170.40 27-SEP-15:03 13.30
October 0.196270E+09 1385.29 28-OCT-15:03 12.20
November 0.683396E+09 1499.97 30-NOV-16:13 4.60
December 0.109685E+10 1520.02 26-DEC-16:13 3.73
         
Annual Sum or Average 0.447601E+10      
Minimum of Months 2172658.71 957.65   -1.0
Maximum of Months 0.118808E+10 1520.02   18.58



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.135980E+10 1483.42 16-JAN-16:13 2.03
February 0.902900E+09 1466.53 19-FEB-09:13 -2.9
March 0.499092E+09 1408.37 25-MAR-08:61 4.78
April 0.184263E+09 1374.23 19-APR-08:62 5.87
May 41518572.90 1293.41 18-MAY-08:62 6.28
June 7318532.11 1229.88 27-JUN-08:53 17.80
July 1674670.91 1020.09 19-JUL-08:04 15.97
August 2119085.17 1034.82 23-AUG-08:53 21.20
September 19177370.51 1355.46 28-SEP-08:61 10.28
October 0.279049E+09 1371.49 25-OCT-08:61 9.37
November 0.812166E+09 1466.55 30-NOV-16:13 4.60
December 0.127547E+10 1484.93 26-DEC-16:13 3.73
         
Annual Sum or Average 0.538454E+10      
Minimum of Months 1674670.91 1020.09   -2.9
Maximum of Months 0.135980E+10 1484.93   21.20



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.309239E+09 799.46 26-JAN-16:13 6.67
February 0.152636E+09 770.33 16-FEB-16:13 2.80
March 48458992.43 773.61 08-MAR-16:04 16.02
April 18181168.33 695.28 09-APR-08:03 8.40
May 5222828.87 711.09 24-MAY-18:04 12.70
June 2033182.20 672.45 07-JUN-08:03 11.88
July 1437003.81 711.72 12-JUL-08:03 12.80
August 1660698.20 628.82 17-AUG-18:04 18.58
September 3218845.76 675.58 28-SEP-08:03 10.28
October 14788303.03 676.10 29-OCT-18:04 9.82
November 0.131533E+09 811.24 30-NOV-16:13 4.60
December 0.292093E+09 824.14 26-DEC-16:13 3.73
         
Annual Sum or Average 0.980501E+09      
Minimum of Months 1437003.81 628.82   2.80
Maximum of Months 0.309239E+09 824.14   18.58



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 5.92
February 0.00 0.00 01-FEB-00:03 7.00
March 0.00 0.00 01-MAR-00:03 5.92
April 0.00 0.00 01-APR-00:10 7.93
May 0.00 0.00 01-MAY-00:05 10.38
June 0.00 0.00 01-JUN-00:05 12.83
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:05 17.17
September 0.00 0.00 01-SEP-00:05 16.38
October 0.00 0.00 01-OCT-00:10 14.35
November 0.00 0.00 01-NOV-00:05 9.22
December 0.00 0.00 01-DEC-00:03 4.40
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   4.40
Maximum of Months 0.00 0.00   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DINING_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 5.92
February 0.00 0.00 01-FEB-00:03 7.00
March 0.00 0.00 01-MAR-00:03 5.92
April 0.00 0.00 01-APR-00:10 7.93
May 0.00 0.00 01-MAY-00:05 10.38
June 0.00 0.00 01-JUN-00:05 12.83
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:05 17.17
September 0.00 0.00 01-SEP-00:05 16.38
October 0.00 0.00 01-OCT-00:10 14.35
November 0.00 0.00 01-NOV-00:05 9.22
December 0.00 0.00 01-DEC-00:03 4.40
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   4.40
Maximum of Months 0.00 0.00   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 5.92
February 0.00 0.00 01-FEB-00:03 7.00
March 0.00 0.00 01-MAR-00:03 5.92
April 0.00 0.00 01-APR-00:10 7.93
May 0.00 0.00 01-MAY-00:05 10.38
June 0.00 0.00 01-JUN-00:05 12.83
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:05 17.17
September 0.00 0.00 01-SEP-00:05 16.38
October 0.00 0.00 01-OCT-00:10 14.35
November 0.00 0.00 01-NOV-00:05 9.22
December 0.00 0.00 01-DEC-00:03 4.40
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   4.40
Maximum of Months 0.00 0.00   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 1652666.73 128.87 16-JAN-05:20 -2.2
February 5346550.83 484.13 19-FEB-06:00 -5.6
March 0.00 0.00 01-MAR-00:03 5.92
April 0.00 0.00 01-APR-00:10 7.93
May 0.00 0.00 01-MAY-00:05 10.38
June 0.00 0.00 01-JUN-00:05 12.83
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:05 17.17
September 0.00 0.00 01-SEP-00:05 16.38
October 0.00 0.00 01-OCT-00:10 14.35
November 0.00 0.00 01-NOV-00:05 9.22
December 5820300.43 293.73 26-DEC-11:05 0.12
         
Annual Sum or Average 12819517.98      
Minimum of Months 0.00 0.00   -5.6
Maximum of Months 5820300.43 484.13   17.17



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BASEMENT

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.136942E+11 13190.31 02-JAN-20:10 0.121516E+11 9632.53 02-JAN-20:10
February 0.123646E+11 13190.31 01-FEB-20:10 0.109726E+11 9632.53 01-FEB-20:10
March 0.137364E+11 13190.31 01-MAR-20:10 0.121771E+11 9632.53 01-MAR-20:10
April 0.132299E+11 13190.31 03-APR-19:10 0.117446E+11 9632.53 03-APR-19:10
May 0.137180E+11 13190.31 01-MAY-19:10 0.121662E+11 9632.53 01-MAY-19:10
June 0.132906E+11 13190.31 01-JUN-19:10 0.117829E+11 9632.53 01-JUN-19:10
July 0.136573E+11 13190.31 03-JUL-19:10 0.121279E+11 9632.53 03-JUL-19:10
August 0.137417E+11 13190.31 01-AUG-19:10 0.121808E+11 9632.53 01-AUG-19:10
September 0.132352E+11 13190.31 01-SEP-19:10 0.117482E+11 9632.53 01-SEP-19:10
October 0.136889E+11 13190.31 02-OCT-19:10 0.121479E+11 9632.53 02-OCT-19:10
November 0.132800E+11 13190.31 01-NOV-19:10 0.117774E+11 9632.53 01-NOV-19:10
December 0.136573E+11 13190.31 01-DEC-20:10 0.121279E+11 9632.53 01-DEC-20:10
             
Annual Sum or Average 0.161294E+12     0.143105E+12    
Minimum of Months 0.123646E+11 13190.31   0.109726E+11 9632.53  
Maximum of Months 0.137417E+11 13190.31   0.121808E+11 9632.53  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.620421E+09 597.59 02-JAN-20:10 0.864900E+09 685.60 02-JAN-20:10
February 0.560184E+09 597.59 01-FEB-20:10 0.780982E+09 685.60 01-FEB-20:10
March 0.622334E+09 597.59 01-MAR-20:10 0.866718E+09 685.60 01-MAR-20:10
April 0.599386E+09 597.59 03-APR-19:10 0.835931E+09 685.60 03-APR-19:10
May 0.621497E+09 597.59 01-MAY-19:10 0.865939E+09 685.60 01-MAY-19:10
June 0.602135E+09 597.59 01-JUN-19:10 0.838659E+09 685.60 01-JUN-19:10
July 0.618748E+09 597.59 03-JUL-19:10 0.863211E+09 685.60 03-JUL-19:10
August 0.622573E+09 597.59 01-AUG-19:10 0.866978E+09 685.60 01-AUG-19:10
September 0.599625E+09 597.59 01-SEP-19:10 0.836191E+09 685.60 01-SEP-19:10
October 0.620182E+09 597.59 02-OCT-19:10 0.864640E+09 685.60 02-OCT-19:10
November 0.601657E+09 597.59 01-NOV-19:10 0.838269E+09 685.60 01-NOV-19:10
December 0.618748E+09 597.59 01-DEC-20:10 0.863211E+09 685.60 01-DEC-20:10
             
Annual Sum or Average 0.730749E+10     0.101856E+11    
Minimum of Months 0.560184E+09 597.59   0.780982E+09 685.60  
Maximum of Months 0.622573E+09 597.59   0.866978E+09 685.60  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.718450E+09 692.02 02-JAN-20:10 0.100156E+10 793.93 02-JAN-20:10
February 0.648695E+09 692.02 01-FEB-20:10 0.904380E+09 793.93 01-FEB-20:10
March 0.720665E+09 692.02 01-MAR-20:10 0.100366E+10 793.93 01-MAR-20:10
April 0.694091E+09 692.02 03-APR-19:10 0.968011E+09 793.93 03-APR-19:10
May 0.719696E+09 692.02 01-MAY-19:10 0.100276E+10 793.93 01-MAY-19:10
June 0.697275E+09 692.02 01-JUN-19:10 0.971170E+09 793.93 01-JUN-19:10
July 0.716513E+09 692.02 03-JUL-19:10 0.999601E+09 793.93 03-JUL-19:10
August 0.720942E+09 692.02 01-AUG-19:10 0.100396E+10 793.93 01-AUG-19:10
September 0.694368E+09 692.02 01-SEP-19:10 0.968312E+09 793.93 01-SEP-19:10
October 0.718174E+09 692.02 02-OCT-19:10 0.100126E+10 793.93 02-OCT-19:10
November 0.696721E+09 692.02 01-NOV-19:10 0.970719E+09 793.93 01-NOV-19:10
December 0.716513E+09 692.02 01-DEC-20:10 0.999601E+09 793.93 01-DEC-20:10
             
Annual Sum or Average 0.846210E+10     0.117950E+11    
Minimum of Months 0.648695E+09 692.02   0.904380E+09 793.93  
Maximum of Months 0.720942E+09 692.02   0.100396E+10 793.93  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: MECH_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.710312E+09 684.18 02-JAN-20:10 0.105898E+10 839.45 02-JAN-20:10
February 0.641347E+09 684.18 01-FEB-20:10 0.956227E+09 839.45 01-FEB-20:10
March 0.712502E+09 684.18 01-MAR-20:10 0.106120E+10 839.45 01-MAR-20:10
April 0.686229E+09 684.18 03-APR-19:10 0.102351E+10 839.45 03-APR-19:10
May 0.711544E+09 684.18 01-MAY-19:10 0.106025E+10 839.45 01-MAY-19:10
June 0.689376E+09 684.18 01-JUN-19:10 0.102685E+10 839.45 01-JUN-19:10
July 0.708397E+09 684.18 03-JUL-19:10 0.105691E+10 839.45 03-JUL-19:10
August 0.712775E+09 684.18 01-AUG-19:10 0.106152E+10 839.45 01-AUG-19:10
September 0.686503E+09 684.18 01-SEP-19:10 0.102382E+10 839.45 01-SEP-19:10
October 0.710039E+09 684.18 02-OCT-19:10 0.105866E+10 839.45 02-OCT-19:10
November 0.688829E+09 684.18 01-NOV-19:10 0.102637E+10 839.45 01-NOV-19:10
December 0.708397E+09 684.18 01-DEC-20:10 0.105691E+10 839.45 01-DEC-20:10
             
Annual Sum or Average 0.836625E+10     0.124712E+11    
Minimum of Months 0.641347E+09 684.18   0.956227E+09 839.45  
Maximum of Months 0.712775E+09 684.18   0.106152E+10 839.45  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.261454E+09 251.84 02-JAN-20:10 0.305485E+09 242.16 02-JAN-20:10
February 0.236069E+09 251.84 01-FEB-20:10 0.275845E+09 242.16 01-FEB-20:10
March 0.262260E+09 251.84 01-MAR-20:10 0.306128E+09 242.16 01-MAR-20:10
April 0.252589E+09 251.84 03-APR-19:10 0.295253E+09 242.16 03-APR-19:10
May 0.261907E+09 251.84 01-MAY-19:10 0.305852E+09 242.16 01-MAY-19:10
June 0.253748E+09 251.84 01-JUN-19:10 0.296217E+09 242.16 01-JUN-19:10
July 0.260749E+09 251.84 03-JUL-19:10 0.304889E+09 242.16 03-JUL-19:10
August 0.262360E+09 251.84 01-AUG-19:10 0.306219E+09 242.16 01-AUG-19:10
September 0.252690E+09 251.84 01-SEP-19:10 0.295345E+09 242.16 01-SEP-19:10
October 0.261353E+09 251.84 02-OCT-19:10 0.305393E+09 242.16 02-OCT-19:10
November 0.253546E+09 251.84 01-NOV-19:10 0.296079E+09 242.16 01-NOV-19:10
December 0.260749E+09 251.84 01-DEC-20:10 0.304889E+09 242.16 01-DEC-20:10
             
Annual Sum or Average 0.307947E+10     0.359760E+10    
Minimum of Months 0.236069E+09 251.84   0.275845E+09 242.16  
Maximum of Months 0.262360E+09 251.84   0.306219E+09 242.16  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.337502E+09 325.08 02-JAN-20:10 0.576866E+10 4572.80 02-JAN-20:10
February 0.304733E+09 325.08 01-FEB-20:10 0.520895E+10 4572.80 01-FEB-20:10
March 0.338542E+09 325.08 01-MAR-20:10 0.578079E+10 4572.80 01-MAR-20:10
April 0.326059E+09 325.08 03-APR-19:10 0.557545E+10 4572.80 03-APR-19:10
May 0.338087E+09 325.08 01-MAY-19:10 0.577559E+10 4572.80 01-MAY-19:10
June 0.327554E+09 325.08 01-JUN-19:10 0.559364E+10 4572.80 01-JUN-19:10
July 0.336592E+09 325.08 03-JUL-19:10 0.575740E+10 4572.80 03-JUL-19:10
August 0.338672E+09 325.08 01-AUG-19:10 0.578252E+10 4572.80 01-AUG-19:10
September 0.326189E+09 325.08 01-SEP-19:10 0.557718E+10 4572.80 01-SEP-19:10
October 0.337372E+09 325.08 02-OCT-19:10 0.576693E+10 4572.80 02-OCT-19:10
November 0.327294E+09 325.08 01-NOV-19:10 0.559104E+10 4572.80 01-NOV-19:10
December 0.336592E+09 325.08 01-DEC-20:10 0.575740E+10 4572.80 01-DEC-20:10
             
Annual Sum or Average 0.397519E+10     0.679355E+11    
Minimum of Months 0.304733E+09 325.08   0.520895E+10 4572.80  
Maximum of Months 0.338672E+09 325.08   0.578252E+10 4572.80  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.141930E+10 1701.53 02-JAN-20:10 0.121771E+10 965.27 02-JAN-20:10
February 0.120632E+10 1701.53 01-FEB-20:10 0.109956E+10 965.27 01-FEB-20:10
March 0.125166E+10 1701.53 01-MAR-20:10 0.122027E+10 965.27 01-MAR-20:10
April 0.108886E+10 1701.53 03-APR-19:10 0.117692E+10 965.27 03-APR-19:10
May 0.103943E+10 1701.53 01-MAY-19:10 0.121917E+10 965.27 01-MAY-19:10
June 0.922157E+09 1701.53 01-JUN-19:40 0.118076E+10 965.27 01-JUN-19:10
July 0.985607E+09 1701.53 03-JUL-19:00 0.121533E+10 965.27 03-JUL-19:10
August 0.106554E+10 1701.53 01-AUG-19:19 0.122063E+10 965.27 01-AUG-19:10
September 0.117377E+10 1701.53 01-SEP-19:10 0.117729E+10 965.27 01-SEP-19:10
October 0.132050E+10 1701.53 02-OCT-19:10 0.121734E+10 965.27 02-OCT-19:10
November 0.134594E+10 1701.53 01-NOV-19:10 0.118021E+10 965.27 01-NOV-19:10
December 0.142460E+10 1701.53 01-DEC-20:10 0.121533E+10 965.27 01-DEC-20:10
             
Annual Sum or Average 0.142437E+11     0.143405E+11    
Minimum of Months 0.922157E+09 1701.53   0.109956E+10 965.27  
Maximum of Months 0.142460E+10 1701.53   0.122063E+10 965.27  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.954301E+10 9504.80 02-JAN-20:10 0.126520E+11 10029.21 02-JAN-20:10
February 0.853979E+10 9504.80 01-FEB-20:10 0.114244E+11 10029.21 01-FEB-20:10
March 0.941463E+10 9504.80 01-MAR-20:10 0.126786E+11 10029.21 01-MAR-20:10
April 0.896188E+10 9504.80 03-APR-19:10 0.122282E+11 10029.21 03-APR-19:10
May 0.921214E+10 9504.80 01-MAY-19:10 0.126672E+11 10029.21 01-MAY-19:10
June 0.885814E+10 9504.80 01-JUN-19:30 0.122682E+11 10029.21 01-JUN-19:10
July 0.914681E+10 9504.80 03-JUL-19:40 0.126273E+11 10029.21 03-JUL-19:10
August 0.925746E+10 9504.80 01-AUG-19:19 0.126824E+11 10029.21 01-AUG-19:10
September 0.903708E+10 9504.80 01-SEP-19:10 0.122320E+11 10029.21 01-SEP-19:10
October 0.944307E+10 9504.80 02-OCT-19:10 0.126482E+11 10029.21 02-OCT-19:10
November 0.922463E+10 9504.80 01-NOV-19:10 0.122624E+11 10029.21 01-NOV-19:10
December 0.953034E+10 9504.80 01-DEC-20:10 0.126273E+11 10029.21 01-DEC-20:10
             
Annual Sum or Average 0.110169E+12     0.148998E+12    
Minimum of Months 0.853979E+10 9504.80   0.114244E+11 10029.21  
Maximum of Months 0.954301E+10 9504.80   0.126824E+11 10029.21  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.196602E+09 177.88 01-JAN-19:10 0.222503E+09 237.06 01-JAN-08:09
February 0.177551E+09 177.88 01-FEB-20:10 0.200969E+09 237.06 01-FEB-07:10
March 0.195039E+09 177.88 01-MAR-20:10 0.222390E+09 237.06 01-MAR-07:10
April 0.190486E+09 177.88 01-APR-18:10 0.215344E+09 237.06 01-APR-07:10
May 0.195821E+09 177.88 01-MAY-19:10 0.222446E+09 237.06 01-MAY-06:10
June 0.188975E+09 177.88 01-JUN-19:10 0.215230E+09 237.06 01-JUN-06:10
July 0.197358E+09 177.88 01-JUL-18:10 0.222560E+09 237.06 01-JUL-07:10
August 0.195039E+09 177.88 01-AUG-19:10 0.222390E+09 237.06 01-AUG-06:10
September 0.190538E+09 177.88 01-SEP-19:10 0.215344E+09 237.06 01-SEP-06:10
October 0.196576E+09 177.88 01-OCT-18:10 0.222503E+09 237.06 01-OCT-07:10
November 0.189731E+09 177.88 01-NOV-19:10 0.215287E+09 237.06 01-NOV-06:10
December 0.197383E+09 177.88 01-DEC-20:10 0.222560E+09 237.06 01-DEC-07:10
             
Annual Sum or Average 0.231110E+10     0.261953E+10    
Minimum of Months 0.177551E+09 177.88   0.200969E+09 237.06  
Maximum of Months 0.197383E+09 177.88   0.222560E+09 237.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.196579E+09 177.86 01-JAN-19:10 0.222477E+09 237.03 01-JAN-08:09
February 0.177530E+09 177.86 01-FEB-20:10 0.200945E+09 237.03 01-FEB-07:10
March 0.195017E+09 177.86 01-MAR-20:10 0.222364E+09 237.03 01-MAR-07:10
April 0.190464E+09 177.86 01-APR-18:10 0.215319E+09 237.03 01-APR-07:10
May 0.195798E+09 177.86 01-MAY-19:10 0.222420E+09 237.03 01-MAY-06:10
June 0.188953E+09 177.86 01-JUN-19:10 0.215205E+09 237.03 01-JUN-06:10
July 0.197334E+09 177.86 01-JUL-18:10 0.222534E+09 237.03 01-JUL-07:10
August 0.195017E+09 177.86 01-AUG-19:10 0.222364E+09 237.03 01-AUG-06:10
September 0.190515E+09 177.86 01-SEP-19:10 0.215319E+09 237.03 01-SEP-06:10
October 0.196553E+09 177.86 01-OCT-18:10 0.222477E+09 237.03 01-OCT-07:10
November 0.189708E+09 177.86 01-NOV-19:10 0.215262E+09 237.03 01-NOV-06:10
December 0.197360E+09 177.86 01-DEC-20:10 0.222534E+09 237.03 01-DEC-07:10
             
Annual Sum or Average 0.231083E+10     0.261922E+10    
Minimum of Months 0.177530E+09 177.86   0.200945E+09 237.03  
Maximum of Months 0.197360E+09 177.86   0.222534E+09 237.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.123557E+09 111.79 01-JAN-19:10 0.217935E+09 232.19 01-JAN-08:09
February 0.111584E+09 111.79 01-FEB-20:10 0.196843E+09 232.19 01-FEB-07:10
March 0.122575E+09 111.79 01-MAR-20:10 0.217824E+09 232.19 01-MAR-07:10
April 0.119713E+09 111.79 01-APR-18:10 0.210923E+09 232.19 01-APR-07:10
May 0.123066E+09 111.79 01-MAY-19:10 0.217879E+09 232.19 01-MAY-06:10
June 0.118764E+09 111.79 01-JUN-19:10 0.210812E+09 232.19 01-JUN-06:10
July 0.124032E+09 111.79 01-JUL-18:10 0.217991E+09 232.19 01-JUL-07:10
August 0.122575E+09 111.79 01-AUG-19:10 0.217824E+09 232.19 01-AUG-06:10
September 0.119746E+09 111.79 01-SEP-19:10 0.210923E+09 232.19 01-SEP-06:10
October 0.123541E+09 111.79 01-OCT-18:10 0.217935E+09 232.19 01-OCT-07:10
November 0.119238E+09 111.79 01-NOV-19:10 0.210867E+09 232.19 01-NOV-06:10
December 0.124048E+09 111.79 01-DEC-20:10 0.217991E+09 232.19 01-DEC-07:10
             
Annual Sum or Average 0.145244E+10     0.256575E+10    
Minimum of Months 0.111584E+09 111.79   0.196843E+09 232.19  
Maximum of Months 0.124048E+09 111.79   0.217991E+09 232.19  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.123591E+09 111.82 01-JAN-19:10 0.217995E+09 232.26 01-JAN-08:09
February 0.111614E+09 111.82 01-FEB-20:10 0.196897E+09 232.26 01-FEB-07:10
March 0.122608E+09 111.82 01-MAR-20:10 0.217883E+09 232.26 01-MAR-07:10
April 0.119746E+09 111.82 01-APR-18:10 0.210981E+09 232.26 01-APR-07:10
May 0.123099E+09 111.82 01-MAY-19:10 0.217939E+09 232.26 01-MAY-06:10
June 0.118796E+09 111.82 01-JUN-19:10 0.210869E+09 232.26 01-JUN-06:10
July 0.124066E+09 111.82 01-JUL-18:10 0.218051E+09 232.26 01-JUL-07:10
August 0.122608E+09 111.82 01-AUG-19:10 0.217883E+09 232.26 01-AUG-06:10
September 0.119778E+09 111.82 01-SEP-19:10 0.210981E+09 232.26 01-SEP-06:10
October 0.123574E+09 111.82 01-OCT-18:10 0.217995E+09 232.26 01-OCT-07:10
November 0.119271E+09 111.82 01-NOV-19:10 0.210925E+09 232.26 01-NOV-06:10
December 0.124082E+09 111.82 01-DEC-20:10 0.218051E+09 232.26 01-DEC-07:10
             
Annual Sum or Average 0.145283E+10     0.256645E+10    
Minimum of Months 0.111614E+09 111.82   0.196897E+09 232.26  
Maximum of Months 0.124082E+09 111.82   0.218051E+09 232.26  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.196602E+09 177.88 01-JAN-19:10 0.222503E+09 237.06 01-JAN-08:09
February 0.177551E+09 177.88 01-FEB-20:10 0.200969E+09 237.06 01-FEB-07:10
March 0.195039E+09 177.88 01-MAR-20:10 0.222390E+09 237.06 01-MAR-07:10
April 0.190486E+09 177.88 01-APR-18:10 0.215344E+09 237.06 01-APR-07:10
May 0.195821E+09 177.88 01-MAY-19:10 0.222446E+09 237.06 01-MAY-06:10
June 0.188975E+09 177.88 01-JUN-19:10 0.215230E+09 237.06 01-JUN-06:10
July 0.197358E+09 177.88 01-JUL-18:10 0.222560E+09 237.06 01-JUL-07:10
August 0.195039E+09 177.88 01-AUG-19:10 0.222390E+09 237.06 01-AUG-06:10
September 0.190538E+09 177.88 01-SEP-19:10 0.215344E+09 237.06 01-SEP-06:10
October 0.196576E+09 177.88 01-OCT-18:10 0.222503E+09 237.06 01-OCT-07:10
November 0.189731E+09 177.88 01-NOV-19:10 0.215287E+09 237.06 01-NOV-06:10
December 0.197383E+09 177.88 01-DEC-20:10 0.222560E+09 237.06 01-DEC-07:10
             
Annual Sum or Average 0.231110E+10     0.261953E+10    
Minimum of Months 0.177551E+09 177.88   0.200969E+09 237.06  
Maximum of Months 0.197383E+09 177.88   0.222560E+09 237.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.196579E+09 177.86 01-JAN-19:10 0.222477E+09 237.03 01-JAN-08:09
February 0.177530E+09 177.86 01-FEB-20:10 0.200945E+09 237.03 01-FEB-07:10
March 0.195017E+09 177.86 01-MAR-20:10 0.222364E+09 237.03 01-MAR-07:10
April 0.190464E+09 177.86 01-APR-18:10 0.215319E+09 237.03 01-APR-07:10
May 0.195798E+09 177.86 01-MAY-19:10 0.222420E+09 237.03 01-MAY-06:10
June 0.188953E+09 177.86 01-JUN-19:10 0.215205E+09 237.03 01-JUN-06:10
July 0.197334E+09 177.86 01-JUL-18:10 0.222534E+09 237.03 01-JUL-07:10
August 0.195017E+09 177.86 01-AUG-19:10 0.222364E+09 237.03 01-AUG-06:10
September 0.190515E+09 177.86 01-SEP-19:10 0.215319E+09 237.03 01-SEP-06:10
October 0.196553E+09 177.86 01-OCT-18:10 0.222477E+09 237.03 01-OCT-07:10
November 0.189708E+09 177.86 01-NOV-19:10 0.215262E+09 237.03 01-NOV-06:10
December 0.197360E+09 177.86 01-DEC-20:10 0.222534E+09 237.03 01-DEC-07:10
             
Annual Sum or Average 0.231083E+10     0.261922E+10    
Minimum of Months 0.177530E+09 177.86   0.200945E+09 237.03  
Maximum of Months 0.197360E+09 177.86   0.222534E+09 237.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY []
January 0.193865E+10 1867.32 02-JAN-20:10 0.00 0.00
February 0.175042E+10 1867.32 01-FEB-20:10 0.00 0.00
March 0.194462E+10 1867.32 01-MAR-20:10 0.00 0.00
April 0.187292E+10 1867.32 03-APR-19:10 0.00 0.00
May 0.194201E+10 1867.32 01-MAY-19:10 0.00 0.00
June 0.188151E+10 1867.32 01-JUN-19:10 0.00 0.00
July 0.193342E+10 1867.32 03-JUL-19:10 0.00 0.00
August 0.194537E+10 1867.32 01-AUG-19:10 0.00 0.00
September 0.187367E+10 1867.32 01-SEP-19:10 0.00 0.00
October 0.193790E+10 1867.32 02-OCT-19:10 0.00 0.00
November 0.188002E+10 1867.32 01-NOV-19:10 0.00 0.00
December 0.193342E+10 1867.32 01-DEC-20:10 0.00 0.00
           
Annual Sum or Average 0.228339E+11     0.00 0.00
Minimum of Months 0.175042E+10 1867.32   0.00 0.00
Maximum of Months 0.194537E+10 1867.32   0.00 0.00



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.196602E+09 177.88 01-JAN-19:10 0.222503E+09 237.06 01-JAN-08:09
February 0.177551E+09 177.88 01-FEB-20:10 0.200969E+09 237.06 01-FEB-07:10
March 0.195039E+09 177.88 01-MAR-20:10 0.222390E+09 237.06 01-MAR-07:10
April 0.190486E+09 177.88 01-APR-18:10 0.215344E+09 237.06 01-APR-07:10
May 0.195821E+09 177.88 01-MAY-19:10 0.222446E+09 237.06 01-MAY-06:10
June 0.188975E+09 177.88 01-JUN-19:10 0.215230E+09 237.06 01-JUN-06:10
July 0.197358E+09 177.88 01-JUL-18:10 0.222560E+09 237.06 01-JUL-07:10
August 0.195039E+09 177.88 01-AUG-19:10 0.222390E+09 237.06 01-AUG-06:10
September 0.190538E+09 177.88 01-SEP-19:10 0.215344E+09 237.06 01-SEP-06:10
October 0.196576E+09 177.88 01-OCT-18:10 0.222503E+09 237.06 01-OCT-07:10
November 0.189731E+09 177.88 01-NOV-19:10 0.215287E+09 237.06 01-NOV-06:10
December 0.197383E+09 177.88 01-DEC-20:10 0.222560E+09 237.06 01-DEC-07:10
             
Annual Sum or Average 0.231110E+10     0.261953E+10    
Minimum of Months 0.177551E+09 177.88   0.200969E+09 237.06  
Maximum of Months 0.197383E+09 177.88   0.222560E+09 237.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.196579E+09 177.86 01-JAN-19:10 0.222477E+09 237.03 01-JAN-08:09
February 0.177530E+09 177.86 01-FEB-20:10 0.200945E+09 237.03 01-FEB-07:10
March 0.195017E+09 177.86 01-MAR-20:10 0.222364E+09 237.03 01-MAR-07:10
April 0.190464E+09 177.86 01-APR-18:10 0.215319E+09 237.03 01-APR-07:10
May 0.195798E+09 177.86 01-MAY-19:10 0.222420E+09 237.03 01-MAY-06:10
June 0.188953E+09 177.86 01-JUN-19:10 0.215205E+09 237.03 01-JUN-06:10
July 0.197334E+09 177.86 01-JUL-18:10 0.222534E+09 237.03 01-JUL-07:10
August 0.195017E+09 177.86 01-AUG-19:10 0.222364E+09 237.03 01-AUG-06:10
September 0.190515E+09 177.86 01-SEP-19:10 0.215319E+09 237.03 01-SEP-06:10
October 0.196553E+09 177.86 01-OCT-18:10 0.222477E+09 237.03 01-OCT-07:10
November 0.189708E+09 177.86 01-NOV-19:10 0.215262E+09 237.03 01-NOV-06:10
December 0.197360E+09 177.86 01-DEC-20:10 0.222534E+09 237.03 01-DEC-07:10
             
Annual Sum or Average 0.231083E+10     0.261922E+10    
Minimum of Months 0.177530E+09 177.86   0.200945E+09 237.03  
Maximum of Months 0.197360E+09 177.86   0.222534E+09 237.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.123591E+09 111.82 01-JAN-19:10 0.217995E+09 232.26 01-JAN-08:09
February 0.111614E+09 111.82 01-FEB-20:10 0.196897E+09 232.26 01-FEB-07:10
March 0.122608E+09 111.82 01-MAR-20:10 0.217883E+09 232.26 01-MAR-07:10
April 0.119746E+09 111.82 01-APR-18:10 0.210981E+09 232.26 01-APR-07:10
May 0.123099E+09 111.82 01-MAY-19:10 0.217939E+09 232.26 01-MAY-06:10
June 0.118796E+09 111.82 01-JUN-19:10 0.210869E+09 232.26 01-JUN-06:10
July 0.124066E+09 111.82 01-JUL-18:10 0.218051E+09 232.26 01-JUL-07:10
August 0.122608E+09 111.82 01-AUG-19:10 0.217883E+09 232.26 01-AUG-06:10
September 0.119778E+09 111.82 01-SEP-19:10 0.210981E+09 232.26 01-SEP-06:10
October 0.123574E+09 111.82 01-OCT-18:10 0.217995E+09 232.26 01-OCT-07:10
November 0.119271E+09 111.82 01-NOV-19:10 0.210925E+09 232.26 01-NOV-06:10
December 0.124082E+09 111.82 01-DEC-20:10 0.218051E+09 232.26 01-DEC-07:10
             
Annual Sum or Average 0.145283E+10     0.256645E+10    
Minimum of Months 0.111614E+09 111.82   0.196897E+09 232.26  
Maximum of Months 0.124082E+09 111.82   0.218051E+09 232.26  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.287054E+10 2988.03 02-JAN-20:10 0.149358E+11 6747.90 01-JAN-07:10
February 0.250957E+10 2988.03 01-FEB-20:10 0.134904E+11 6747.90 01-FEB-07:10
March 0.268827E+10 2988.03 01-MAR-20:10 0.149358E+11 6747.90 01-MAR-07:10
April 0.245393E+10 2988.03 03-APR-19:10 0.144540E+11 6747.90 01-APR-06:10
May 0.244131E+10 2988.03 01-MAY-19:10 0.149358E+11 6747.90 01-MAY-06:10
June 0.226940E+10 2988.03 01-JUN-19:40 0.144540E+11 6747.90 01-JUN-06:10
July 0.235884E+10 2988.03 10-JUL-19:30 0.149358E+11 6747.90 01-JUL-06:10
August 0.247234E+10 2988.03 01-AUG-19:19 0.149358E+11 6747.90 01-AUG-06:10
September 0.254653E+10 2988.03 01-SEP-19:10 0.144540E+11 6747.90 01-SEP-06:10
October 0.275942E+10 2988.03 02-OCT-19:10 0.149358E+11 6747.90 01-OCT-06:10
November 0.275372E+10 2988.03 01-NOV-19:10 0.144540E+11 6747.90 01-NOV-06:10
December 0.288189E+10 2988.03 01-DEC-20:10 0.149358E+11 6747.90 01-DEC-07:10
             
Annual Sum or Average 0.310058E+11     0.175857E+12    
Minimum of Months 0.226940E+10 2988.03   0.134904E+11 6747.90  
Maximum of Months 0.288189E+10 2988.03   0.149358E+11 6747.90  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DINING_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.287054E+10 2988.03 02-JAN-20:10 0.149358E+11 6747.90 01-JAN-07:10
February 0.250957E+10 2988.03 01-FEB-20:10 0.134904E+11 6747.90 01-FEB-07:10
March 0.268827E+10 2988.03 01-MAR-20:10 0.149358E+11 6747.90 01-MAR-07:10
April 0.245393E+10 2988.03 03-APR-19:10 0.144540E+11 6747.90 01-APR-06:10
May 0.244131E+10 2988.03 01-MAY-19:10 0.149358E+11 6747.90 01-MAY-06:10
June 0.226940E+10 2988.03 01-JUN-19:40 0.144540E+11 6747.90 01-JUN-06:10
July 0.235884E+10 2988.03 10-JUL-19:30 0.149358E+11 6747.90 01-JUL-06:10
August 0.247234E+10 2988.03 01-AUG-19:19 0.149358E+11 6747.90 01-AUG-06:10
September 0.254653E+10 2988.03 01-SEP-19:10 0.144540E+11 6747.90 01-SEP-06:10
October 0.275942E+10 2988.03 02-OCT-19:10 0.149358E+11 6747.90 01-OCT-06:10
November 0.275372E+10 2988.03 01-NOV-19:10 0.144540E+11 6747.90 01-NOV-06:10
December 0.288189E+10 2988.03 01-DEC-20:10 0.149358E+11 6747.90 01-DEC-07:10
             
Annual Sum or Average 0.310058E+11     0.175857E+12    
Minimum of Months 0.226940E+10 2988.03   0.134904E+11 6747.90  
Maximum of Months 0.288189E+10 2988.03   0.149358E+11 6747.90  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.110133E+10 1060.81 02-JAN-20:10 0.368383E+11 16487.34 01-JAN-07:10
February 0.994402E+09 1060.81 01-FEB-20:10 0.332733E+11 16487.34 01-FEB-07:10
March 0.110473E+10 1060.81 01-MAR-20:10 0.368383E+11 16487.34 01-MAR-07:10
April 0.106399E+10 1060.81 03-APR-19:10 0.356500E+11 16487.34 01-APR-06:10
May 0.110324E+10 1060.81 01-MAY-19:10 0.368383E+11 16487.34 01-MAY-06:10
June 0.106887E+10 1060.81 01-JUN-19:10 0.356500E+11 16487.34 01-JUN-06:10
July 0.109836E+10 1060.81 03-JUL-19:10 0.368383E+11 16487.34 01-JUL-06:10
August 0.110515E+10 1060.81 01-AUG-19:10 0.368383E+11 16487.34 01-AUG-06:10
September 0.106442E+10 1060.81 01-SEP-19:10 0.356500E+11 16487.34 01-SEP-06:10
October 0.110091E+10 1060.81 02-OCT-19:10 0.368383E+11 16487.34 01-OCT-06:10
November 0.106802E+10 1060.81 01-NOV-19:10 0.356500E+11 16487.34 01-NOV-06:10
December 0.109836E+10 1060.81 01-DEC-20:10 0.368383E+11 16487.34 01-DEC-07:10
             
Annual Sum or Average 0.129718E+11     0.433742E+12    
Minimum of Months 0.994402E+09 1060.81   0.332733E+11 16487.34  
Maximum of Months 0.110515E+10 1060.81   0.368383E+11 16487.34  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY []
January 0.205176E+10 1976.27 02-JAN-20:10 0.00 0.00
February 0.185255E+10 1976.27 01-FEB-20:10 0.00 0.00
March 0.205809E+10 1976.27 01-MAR-20:10 0.00 0.00
April 0.198220E+10 1976.27 03-APR-19:10 0.00 0.00
May 0.205532E+10 1976.27 01-MAY-19:10 0.00 0.00
June 0.199129E+10 1976.27 01-JUN-19:10 0.00 0.00
July 0.204623E+10 1976.27 03-JUL-19:10 0.00 0.00
August 0.205888E+10 1976.27 01-AUG-19:10 0.00 0.00
September 0.198299E+10 1976.27 01-SEP-19:10 0.00 0.00
October 0.205097E+10 1976.27 02-OCT-19:10 0.00 0.00
November 0.198971E+10 1976.27 01-NOV-19:10 0.00 0.00
December 0.204623E+10 1976.27 01-DEC-20:10 0.00 0.00
           
Annual Sum or Average 0.241662E+11     0.00 0.00
Minimum of Months 0.185255E+10 1976.27   0.00 0.00
Maximum of Months 0.205888E+10 1976.27   0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: BASEMENT

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.195762E+11 0.136942E+11 0.121516E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.176991E+11 0.123646E+11 0.109726E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.196682E+11 0.137364E+11 0.121771E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.189781E+11 0.132299E+11 0.117446E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.196176E+11 0.137180E+11 0.121662E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.190195E+11 0.132906E+11 0.117829E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.195762E+11 0.136573E+11 0.121279E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.196590E+11 0.137417E+11 0.121808E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.189689E+11 0.132352E+11 0.117482E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.195854E+11 0.136889E+11 0.121479E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.189367E+11 0.132800E+11 0.117774E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.195762E+11 0.136573E+11 0.121279E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.230861E+12 0.161294E+12 0.143105E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.176991E+11 0.123646E+11 0.109726E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.196682E+11 0.137417E+11 0.121808E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: RETAIL_1_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.199054E+10 0.620421E+09 0.864900E+09 0.00 0.00 0.00 0.00 0.00 0.248298E+09
February 0.179968E+10 0.560184E+09 0.780982E+09 0.00 0.00 0.00 0.00 0.00 0.205951E+09
March 0.199990E+10 0.622334E+09 0.866718E+09 0.00 0.00 0.00 0.00 0.00 0.191216E+09
April 0.192973E+10 0.599386E+09 0.835931E+09 0.00 0.00 0.00 0.00 697441.60 0.150712E+09
May 0.199475E+10 0.621497E+09 0.865939E+09 0.00 0.00 0.00 0.00 270607.17 0.124507E+09
June 0.193394E+10 0.602135E+09 0.838659E+09 0.00 0.00 0.00 0.00 945786.84 84165592.83
July 0.199054E+10 0.618748E+09 0.863211E+09 0.00 0.00 0.00 0.00 3984501.58 65336397.95
August 0.199896E+10 0.622573E+09 0.866978E+09 0.00 0.00 0.00 0.00 7508999.52 54494129.69
September 0.192879E+10 0.599625E+09 0.836191E+09 0.00 0.00 0.00 0.00 84018.04 94093706.70
October 0.199148E+10 0.620182E+09 0.864640E+09 0.00 0.00 0.00 0.00 0.00 0.145672E+09
November 0.192552E+10 0.601657E+09 0.838269E+09 0.00 0.00 0.00 0.00 0.00 0.187063E+09
December 0.199054E+10 0.618748E+09 0.863211E+09 0.00 0.00 0.00 0.00 0.00 0.234487E+09
                   
Annual Sum or Average 0.234744E+11 0.730749E+10 0.101856E+11 0.00 0.00 0.00 0.00 13491354.74 0.178600E+10
Minimum of Months 0.179968E+10 0.560184E+09 0.780982E+09 0.00 0.00 0.00 0.00 0.00 54494129.69
Maximum of Months 0.199990E+10 0.622573E+09 0.866978E+09 0.00 0.00 0.00 0.00 7508999.52 0.248298E+09



Table of Contents

Report: SpaceGainsMonthly

For: RETAIL_2_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.230505E+10 0.718450E+09 0.100156E+10 0.00 0.00 0.00 0.00 0.00 99202772.06
February 0.208403E+10 0.648695E+09 0.904380E+09 0.00 0.00 0.00 0.00 0.00 83285371.76
March 0.231589E+10 0.720665E+09 0.100366E+10 0.00 0.00 0.00 0.00 0.00 79508782.89
April 0.223463E+10 0.694091E+09 0.968011E+09 0.00 0.00 0.00 0.00 328914.92 64662309.50
May 0.230993E+10 0.719696E+09 0.100276E+10 0.00 0.00 0.00 0.00 102259.50 55710400.06
June 0.223950E+10 0.697275E+09 0.971170E+09 0.00 0.00 0.00 0.00 280650.50 40300655.14
July 0.230505E+10 0.716513E+09 0.999601E+09 0.00 0.00 0.00 0.00 1443537.39 32707525.08
August 0.231480E+10 0.720942E+09 0.100396E+10 0.00 0.00 0.00 0.00 2946616.27 28119096.70
September 0.223354E+10 0.694368E+09 0.968312E+09 0.00 0.00 0.00 0.00 58874.67 43315852.06
October 0.230614E+10 0.718174E+09 0.100126E+10 0.00 0.00 0.00 0.00 0.00 62820575.56
November 0.222975E+10 0.696721E+09 0.970719E+09 0.00 0.00 0.00 0.00 0.00 77167078.51
December 0.230505E+10 0.716513E+09 0.999601E+09 0.00 0.00 0.00 0.00 0.00 94268533.07
                   
Annual Sum or Average 0.271834E+11 0.846210E+10 0.117950E+11 0.00 0.00 0.00 0.00 5160853.25 0.761069E+09
Minimum of Months 0.208403E+10 0.648695E+09 0.904380E+09 0.00 0.00 0.00 0.00 0.00 28119096.70
Maximum of Months 0.231589E+10 0.720942E+09 0.100396E+10 0.00 0.00 0.00 0.00 2946616.27 99202772.06



Table of Contents

Report: SpaceGainsMonthly

For: MECH_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.487480E+09 0.710312E+09 0.105898E+10 0.00 0.00 0.00 0.00 0.00 0.226745E+09
February 0.440737E+09 0.641347E+09 0.956227E+09 0.00 0.00 0.00 0.00 0.00 0.188036E+09
March 0.489771E+09 0.712502E+09 0.106120E+10 0.00 0.00 0.00 0.00 0.00 0.177444E+09
April 0.472586E+09 0.686229E+09 0.102351E+10 0.00 0.00 0.00 0.00 1062476.49 0.144460E+09
May 0.488511E+09 0.711544E+09 0.106025E+10 0.00 0.00 0.00 0.00 393684.19 0.126110E+09
June 0.473617E+09 0.689376E+09 0.102685E+10 0.00 0.00 0.00 0.00 798430.97 92307336.49
July 0.487480E+09 0.708397E+09 0.105691E+10 0.00 0.00 0.00 0.00 3540572.80 75328989.61
August 0.489542E+09 0.712775E+09 0.106152E+10 0.00 0.00 0.00 0.00 7155313.81 65314584.07
September 0.472357E+09 0.686503E+09 0.102382E+10 0.00 0.00 0.00 0.00 314248.22 98200125.24
October 0.487709E+09 0.710039E+09 0.105866E+10 0.00 0.00 0.00 0.00 0.00 0.141079E+09
November 0.471555E+09 0.688829E+09 0.102637E+10 0.00 0.00 0.00 0.00 0.00 0.174219E+09
December 0.487480E+09 0.708397E+09 0.105691E+10 0.00 0.00 0.00 0.00 0.00 0.213866E+09
                   
Annual Sum or Average 0.574883E+10 0.836625E+10 0.124712E+11 0.00 0.00 0.00 0.00 13264726.48 0.172311E+10
Minimum of Months 0.440737E+09 0.641347E+09 0.956227E+09 0.00 0.00 0.00 0.00 0.00 65314584.07
Maximum of Months 0.489771E+09 0.712775E+09 0.106152E+10 0.00 0.00 0.00 0.00 7155313.81 0.226745E+09



Table of Contents

Report: SpaceGainsMonthly

For: STORAGE_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.374985E+09 0.261454E+09 0.305485E+09 0.00 0.00 0.00 0.00 0.00 0.130349E+09
February 0.339028E+09 0.236069E+09 0.275845E+09 0.00 0.00 0.00 0.00 0.00 0.107599E+09
March 0.376747E+09 0.262260E+09 0.306128E+09 0.00 0.00 0.00 0.00 0.00 0.100115E+09
April 0.363528E+09 0.252589E+09 0.295253E+09 0.00 0.00 0.00 0.00 635308.76 81025668.27
May 0.375778E+09 0.261907E+09 0.305852E+09 0.00 0.00 0.00 0.00 255097.56 70428975.64
June 0.364321E+09 0.253748E+09 0.296217E+09 0.00 0.00 0.00 0.00 518624.24 51195989.92
July 0.374985E+09 0.260749E+09 0.304889E+09 0.00 0.00 0.00 0.00 2182677.56 41486868.41
August 0.376571E+09 0.262360E+09 0.306219E+09 0.00 0.00 0.00 0.00 4352519.60 35799172.34
September 0.363352E+09 0.252690E+09 0.295345E+09 0.00 0.00 0.00 0.00 211643.90 54398615.37
October 0.375161E+09 0.261353E+09 0.305393E+09 0.00 0.00 0.00 0.00 0.00 78777839.98
November 0.362735E+09 0.253546E+09 0.296079E+09 0.00 0.00 0.00 0.00 0.00 98960670.71
December 0.374985E+09 0.260749E+09 0.304889E+09 0.00 0.00 0.00 0.00 0.00 0.122735E+09
                   
Annual Sum or Average 0.442217E+10 0.307947E+10 0.359760E+10 0.00 0.00 0.00 0.00 8155871.62 0.972871E+09
Minimum of Months 0.339028E+09 0.236069E+09 0.275845E+09 0.00 0.00 0.00 0.00 0.00 35799172.34
Maximum of Months 0.376747E+09 0.262360E+09 0.306219E+09 0.00 0.00 0.00 0.00 4352519.60 0.130349E+09



Table of Contents

Report: SpaceGainsMonthly

For: LAUNDRY_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.154405E+10 0.337502E+09 0.576866E+10 0.501157E+11 0.00 0.00 0.00 0.00 0.344874E+09
February 0.139600E+10 0.304733E+09 0.520895E+10 0.452532E+11 0.00 0.00 0.00 0.00 0.286704E+09
March 0.155131E+10 0.338542E+09 0.578079E+10 0.502211E+11 0.00 0.00 0.00 0.00 0.270322E+09
April 0.149688E+10 0.326059E+09 0.557545E+10 0.484372E+11 0.00 0.00 0.00 1027275.66 0.216946E+09
May 0.154732E+10 0.338087E+09 0.577559E+10 0.501759E+11 0.00 0.00 0.00 529623.49 0.183680E+09
June 0.150015E+10 0.327554E+09 0.559364E+10 0.485952E+11 0.00 0.00 0.00 1062666.69 0.131408E+09
July 0.154405E+10 0.336592E+09 0.575740E+10 0.500179E+11 0.00 0.00 0.00 5421278.94 0.102915E+09
August 0.155059E+10 0.338672E+09 0.578252E+10 0.502361E+11 0.00 0.00 0.00 10724756.11 87895629.60
September 0.149615E+10 0.326189E+09 0.557718E+10 0.484522E+11 0.00 0.00 0.00 629233.68 0.140179E+09
October 0.154478E+10 0.337372E+09 0.576693E+10 0.501006E+11 0.00 0.00 0.00 0.00 0.211482E+09
November 0.149361E+10 0.327294E+09 0.559104E+10 0.485726E+11 0.00 0.00 0.00 0.00 0.267216E+09
December 0.154405E+10 0.336592E+09 0.575740E+10 0.500179E+11 0.00 0.00 0.00 0.00 0.327015E+09
                   
Annual Sum or Average 0.182090E+11 0.397519E+10 0.679355E+11 0.590196E+12 0.00 0.00 0.00 19394834.57 0.257064E+10
Minimum of Months 0.139600E+10 0.304733E+09 0.520895E+10 0.452532E+11 0.00 0.00 0.00 0.00 87895629.60
Maximum of Months 0.155131E+10 0.338672E+09 0.578252E+10 0.502361E+11 0.00 0.00 0.00 10724756.11 0.344874E+09



Table of Contents

Report: SpaceGainsMonthly

For: CAFE_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.261570E+11 0.141930E+10 0.121771E+10 0.00 0.00 0.00 0.00 0.00 0.561785E+09
February 0.236489E+11 0.120632E+10 0.109956E+10 0.00 0.00 0.00 0.00 0.00 0.472556E+09
March 0.262800E+11 0.125166E+10 0.122027E+10 0.00 0.00 0.00 0.00 0.00 0.447975E+09
April 0.253579E+11 0.108886E+10 0.117692E+10 0.00 0.00 0.00 0.00 1346093.19 0.360980E+09
May 0.262123E+11 0.103943E+10 0.121917E+10 0.00 0.00 0.00 0.00 435635.88 0.305741E+09
June 0.254132E+11 0.922157E+09 0.118076E+10 0.00 0.00 0.00 0.00 1594857.16 0.217451E+09
July 0.261570E+11 0.985607E+09 0.121533E+10 0.00 0.00 0.00 0.00 8185229.68 0.174184E+09
August 0.262677E+11 0.106554E+10 0.122063E+10 0.00 0.00 0.00 0.00 15708901.99 0.148842E+09
September 0.253456E+11 0.117377E+10 0.117729E+10 0.00 0.00 0.00 0.00 140025.66 0.237779E+09
October 0.261693E+11 0.132050E+10 0.121734E+10 0.00 0.00 0.00 0.00 0.00 0.351019E+09
November 0.253025E+11 0.134594E+10 0.118021E+10 0.00 0.00 0.00 0.00 0.00 0.431960E+09
December 0.261570E+11 0.142460E+10 0.121533E+10 0.00 0.00 0.00 0.00 0.00 0.532936E+09
                   
Annual Sum or Average 0.308468E+12 0.142437E+11 0.143405E+11 0.00 0.00 0.00 0.00 27410743.57 0.424321E+10
Minimum of Months 0.236489E+11 0.922157E+09 0.109956E+10 0.00 0.00 0.00 0.00 0.00 0.148842E+09
Maximum of Months 0.262800E+11 0.142460E+10 0.122063E+10 0.00 0.00 0.00 0.00 15708901.99 0.561785E+09



Table of Contents

Report: SpaceGainsMonthly

For: LOBBY_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.776503E+11 0.954301E+10 0.126520E+11 0.00 0.00 0.00 0.00 0.00 0.166245E+10
February 0.702046E+11 0.853979E+10 0.114244E+11 0.00 0.00 0.00 0.00 0.00 0.139862E+10
March 0.780153E+11 0.941463E+10 0.126786E+11 0.00 0.00 0.00 0.00 0.00 0.133624E+10
April 0.752779E+11 0.896188E+10 0.122282E+11 0.00 0.00 0.00 0.00 4905056.93 0.108550E+10
May 0.778146E+11 0.921214E+10 0.126672E+11 0.00 0.00 0.00 0.00 1553859.53 0.932743E+09
June 0.754422E+11 0.885814E+10 0.122682E+11 0.00 0.00 0.00 0.00 4481867.44 0.677855E+09
July 0.776503E+11 0.914681E+10 0.126273E+11 0.00 0.00 0.00 0.00 23858516.81 0.545646E+09
August 0.779788E+11 0.925746E+10 0.126824E+11 0.00 0.00 0.00 0.00 47355506.97 0.470096E+09
September 0.752414E+11 0.903708E+10 0.122320E+11 0.00 0.00 0.00 0.00 742508.54 0.726877E+09
October 0.776868E+11 0.944307E+10 0.126482E+11 0.00 0.00 0.00 0.00 0.00 0.105973E+10
November 0.751137E+11 0.922463E+10 0.122624E+11 0.00 0.00 0.00 0.00 0.00 0.129769E+10
December 0.776503E+11 0.953034E+10 0.126273E+11 0.00 0.00 0.00 0.00 0.00 0.158068E+10
                   
Annual Sum or Average 0.915726E+12 0.110169E+12 0.148998E+12 0.00 0.00 0.00 0.00 82897316.21 0.127741E+11
Minimum of Months 0.702046E+11 0.853979E+10 0.114244E+11 0.00 0.00 0.00 0.00 0.00 0.470096E+09
Maximum of Months 0.780153E+11 0.954301E+10 0.126824E+11 0.00 0.00 0.00 0.00 47355506.97 0.166245E+10



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_1_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.196602E+09 0.222503E+09 0.00 0.00 0.00 0.00 0.00 0.142321E+09
February 0.273974E+09 0.177551E+09 0.200969E+09 0.00 0.00 0.00 0.00 0.00 0.118997E+09
March 0.303685E+09 0.195039E+09 0.222390E+09 0.00 0.00 0.00 0.00 0.00 0.111452E+09
April 0.293479E+09 0.190486E+09 0.215344E+09 0.00 0.00 0.00 0.00 597426.59 88934045.10
May 0.303504E+09 0.195821E+09 0.222446E+09 0.00 0.00 0.00 0.00 352854.22 74023709.27
June 0.293842E+09 0.188975E+09 0.215230E+09 0.00 0.00 0.00 0.00 824966.41 50615456.29
July 0.303141E+09 0.197358E+09 0.222560E+09 0.00 0.00 0.00 0.00 3277386.45 37571271.16
August 0.303685E+09 0.195039E+09 0.222390E+09 0.00 0.00 0.00 0.00 6211225.21 31052132.02
September 0.293479E+09 0.190538E+09 0.215344E+09 0.00 0.00 0.00 0.00 478508.93 53959081.43
October 0.303322E+09 0.196576E+09 0.222503E+09 0.00 0.00 0.00 0.00 1628.93 84701795.03
November 0.293661E+09 0.189731E+09 0.215287E+09 0.00 0.00 0.00 0.00 0.00 0.108122E+09
December 0.303141E+09 0.197383E+09 0.222560E+09 0.00 0.00 0.00 0.00 0.00 0.134483E+09
                   
Annual Sum or Average 0.357224E+10 0.231110E+10 0.261953E+10 0.00 0.00 0.00 0.00 11743996.74 0.103623E+10
Minimum of Months 0.273974E+09 0.177551E+09 0.200969E+09 0.00 0.00 0.00 0.00 0.00 31052132.02
Maximum of Months 0.303685E+09 0.197383E+09 0.222560E+09 0.00 0.00 0.00 0.00 6211225.21 0.142321E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_2_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.196579E+09 0.222477E+09 0.00 0.00 0.00 0.00 0.00 0.140985E+09
February 0.273974E+09 0.177530E+09 0.200945E+09 0.00 0.00 0.00 0.00 0.00 0.117333E+09
March 0.303685E+09 0.195017E+09 0.222364E+09 0.00 0.00 0.00 0.00 0.00 0.109945E+09
April 0.293479E+09 0.190464E+09 0.215319E+09 0.00 0.00 0.00 0.00 578001.80 88758633.60
May 0.303504E+09 0.195798E+09 0.222420E+09 0.00 0.00 0.00 0.00 148209.76 77094664.25
June 0.293842E+09 0.188953E+09 0.215205E+09 0.00 0.00 0.00 0.00 543719.35 54732624.10
July 0.303141E+09 0.197334E+09 0.222534E+09 0.00 0.00 0.00 0.00 2668594.70 43905696.15
August 0.303685E+09 0.195017E+09 0.222364E+09 0.00 0.00 0.00 0.00 5601238.23 35088353.68
September 0.293479E+09 0.190515E+09 0.215319E+09 0.00 0.00 0.00 0.00 189461.16 57334693.90
October 0.303322E+09 0.196553E+09 0.222477E+09 0.00 0.00 0.00 0.00 556.66 83790586.09
November 0.293661E+09 0.189708E+09 0.215262E+09 0.00 0.00 0.00 0.00 0.00 0.106994E+09
December 0.303141E+09 0.197360E+09 0.222534E+09 0.00 0.00 0.00 0.00 0.00 0.133018E+09
                   
Annual Sum or Average 0.357224E+10 0.231083E+10 0.261922E+10 0.00 0.00 0.00 0.00 9729781.67 0.104898E+10
Minimum of Months 0.273974E+09 0.177530E+09 0.200945E+09 0.00 0.00 0.00 0.00 0.00 35088353.68
Maximum of Months 0.303685E+09 0.197360E+09 0.222534E+09 0.00 0.00 0.00 0.00 5601238.23 0.140985E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.123557E+09 0.217935E+09 0.00 0.00 0.00 0.00 0.00 41376624.36
February 0.00 0.111584E+09 0.196843E+09 0.00 0.00 0.00 0.00 0.00 39937816.36
March 0.00 0.122575E+09 0.217824E+09 0.00 0.00 0.00 0.00 0.00 42621200.95
April 0.00 0.119713E+09 0.210923E+09 0.00 0.00 0.00 0.00 3171.21 36056513.21
May 0.00 0.123066E+09 0.217879E+09 0.00 0.00 0.00 0.00 0.00 32210537.44
June 0.00 0.118764E+09 0.210812E+09 0.00 0.00 0.00 0.00 0.00 25101676.50
July 0.00 0.124032E+09 0.217991E+09 0.00 0.00 0.00 0.00 84303.61 21151862.03
August 0.00 0.122575E+09 0.217824E+09 0.00 0.00 0.00 0.00 301721.72 18674521.19
September 0.00 0.119746E+09 0.210923E+09 0.00 0.00 0.00 0.00 0.00 26271561.60
October 0.00 0.123541E+09 0.217935E+09 0.00 0.00 0.00 0.00 0.00 35552933.05
November 0.00 0.119238E+09 0.210867E+09 0.00 0.00 0.00 0.00 0.00 39532263.00
December 0.00 0.124048E+09 0.217991E+09 0.00 0.00 0.00 0.00 0.00 42051853.08
                   
Annual Sum or Average 0.00 0.145244E+10 0.256575E+10 0.00 0.00 0.00 0.00 389196.54 0.400539E+09
Minimum of Months 0.00 0.111584E+09 0.196843E+09 0.00 0.00 0.00 0.00 0.00 18674521.19
Maximum of Months 0.00 0.124048E+09 0.217991E+09 0.00 0.00 0.00 0.00 301721.72 42621200.95



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.123591E+09 0.217995E+09 0.00 0.00 0.00 0.00 0.00 40239154.93
February 0.273974E+09 0.111614E+09 0.196897E+09 0.00 0.00 0.00 0.00 0.00 33297128.30
March 0.303685E+09 0.122608E+09 0.217883E+09 0.00 0.00 0.00 0.00 0.00 31051531.67
April 0.293479E+09 0.119746E+09 0.210981E+09 0.00 0.00 0.00 0.00 180326.08 24711107.28
May 0.303504E+09 0.123099E+09 0.217939E+09 0.00 0.00 0.00 0.00 56529.59 20788098.31
June 0.293842E+09 0.118796E+09 0.210869E+09 0.00 0.00 0.00 0.00 170250.22 14582810.60
July 0.303141E+09 0.124066E+09 0.218051E+09 0.00 0.00 0.00 0.00 793767.26 11153706.77
August 0.303685E+09 0.122608E+09 0.217883E+09 0.00 0.00 0.00 0.00 1638370.21 9190111.12
September 0.293479E+09 0.119778E+09 0.210981E+09 0.00 0.00 0.00 0.00 83796.14 15269855.22
October 0.303322E+09 0.123574E+09 0.217995E+09 0.00 0.00 0.00 0.00 159.46 23520410.01
November 0.293661E+09 0.119271E+09 0.210925E+09 0.00 0.00 0.00 0.00 0.00 30535866.70
December 0.303141E+09 0.124082E+09 0.218051E+09 0.00 0.00 0.00 0.00 0.00 37934563.63
                   
Annual Sum or Average 0.357224E+10 0.145283E+10 0.256645E+10 0.00 0.00 0.00 0.00 2923198.96 0.292274E+09
Minimum of Months 0.273974E+09 0.111614E+09 0.196897E+09 0.00 0.00 0.00 0.00 0.00 9190111.12
Maximum of Months 0.303685E+09 0.124082E+09 0.218051E+09 0.00 0.00 0.00 0.00 1638370.21 40239154.93



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_5_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.196602E+09 0.222503E+09 0.00 0.00 0.00 0.00 0.00 0.142202E+09
February 0.273974E+09 0.177551E+09 0.200969E+09 0.00 0.00 0.00 0.00 0.00 0.119105E+09
March 0.303685E+09 0.195039E+09 0.222390E+09 0.00 0.00 0.00 0.00 0.00 0.111939E+09
April 0.293479E+09 0.190486E+09 0.215344E+09 0.00 0.00 0.00 0.00 604270.99 89556754.99
May 0.303504E+09 0.195821E+09 0.222446E+09 0.00 0.00 0.00 0.00 357806.11 74174626.43
June 0.293842E+09 0.188975E+09 0.215230E+09 0.00 0.00 0.00 0.00 833715.66 50907679.10
July 0.303141E+09 0.197358E+09 0.222560E+09 0.00 0.00 0.00 0.00 3301250.67 37704961.91
August 0.303685E+09 0.195039E+09 0.222390E+09 0.00 0.00 0.00 0.00 6224065.74 31232828.71
September 0.293479E+09 0.190538E+09 0.215344E+09 0.00 0.00 0.00 0.00 486420.77 53990008.04
October 0.303322E+09 0.196576E+09 0.222503E+09 0.00 0.00 0.00 0.00 1942.68 84948308.12
November 0.293661E+09 0.189731E+09 0.215287E+09 0.00 0.00 0.00 0.00 0.00 0.108083E+09
December 0.303141E+09 0.197383E+09 0.222560E+09 0.00 0.00 0.00 0.00 0.00 0.134341E+09
                   
Annual Sum or Average 0.357224E+10 0.231110E+10 0.261953E+10 0.00 0.00 0.00 0.00 11809472.62 0.103819E+10
Minimum of Months 0.273974E+09 0.177551E+09 0.200969E+09 0.00 0.00 0.00 0.00 0.00 31232828.71
Maximum of Months 0.303685E+09 0.197383E+09 0.222560E+09 0.00 0.00 0.00 0.00 6224065.74 0.142202E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_6_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.196579E+09 0.222477E+09 0.00 0.00 0.00 0.00 0.00 0.140868E+09
February 0.273974E+09 0.177530E+09 0.200945E+09 0.00 0.00 0.00 0.00 0.00 0.117293E+09
March 0.303685E+09 0.195017E+09 0.222364E+09 0.00 0.00 0.00 0.00 0.00 0.110384E+09
April 0.293479E+09 0.190464E+09 0.215319E+09 0.00 0.00 0.00 0.00 581019.21 89348129.38
May 0.303504E+09 0.195798E+09 0.222420E+09 0.00 0.00 0.00 0.00 159219.00 75615333.93
June 0.293842E+09 0.188953E+09 0.215205E+09 0.00 0.00 0.00 0.00 566385.36 53974101.99
July 0.303141E+09 0.197334E+09 0.222534E+09 0.00 0.00 0.00 0.00 2700752.80 41820581.45
August 0.303685E+09 0.195017E+09 0.222364E+09 0.00 0.00 0.00 0.00 5585582.28 34983173.44
September 0.293479E+09 0.190515E+09 0.215319E+09 0.00 0.00 0.00 0.00 225612.00 55789547.92
October 0.303322E+09 0.196553E+09 0.222477E+09 0.00 0.00 0.00 0.00 579.36 83896101.74
November 0.293661E+09 0.189708E+09 0.215262E+09 0.00 0.00 0.00 0.00 0.00 0.106869E+09
December 0.303141E+09 0.197360E+09 0.222534E+09 0.00 0.00 0.00 0.00 0.00 0.132833E+09
                   
Annual Sum or Average 0.357224E+10 0.231083E+10 0.261922E+10 0.00 0.00 0.00 0.00 9819150.02 0.104367E+10
Minimum of Months 0.273974E+09 0.177530E+09 0.200945E+09 0.00 0.00 0.00 0.00 0.00 34983173.44
Maximum of Months 0.303685E+09 0.197360E+09 0.222534E+09 0.00 0.00 0.00 0.00 5585582.28 0.140868E+09



Table of Contents

Report: SpaceGainsMonthly

For: CORRIDOR_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.385223E+10 0.193865E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.174249E+09
February 0.348285E+10 0.175042E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.143694E+09
March 0.387034E+10 0.194462E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.133845E+09
April 0.373454E+10 0.187292E+10 0.00 0.00 0.00 0.00 0.00 800480.91 0.108017E+09
May 0.386038E+10 0.194201E+10 0.00 0.00 0.00 0.00 0.00 300972.84 94060993.45
June 0.374269E+10 0.188151E+10 0.00 0.00 0.00 0.00 0.00 673404.30 67602661.72
July 0.385223E+10 0.193342E+10 0.00 0.00 0.00 0.00 0.00 2870769.95 54501061.45
August 0.386853E+10 0.194537E+10 0.00 0.00 0.00 0.00 0.00 5769819.08 46996171.92
September 0.373273E+10 0.187367E+10 0.00 0.00 0.00 0.00 0.00 203403.47 72133494.35
October 0.385404E+10 0.193790E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.103714E+09
November 0.372639E+10 0.188002E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.131301E+09
December 0.385223E+10 0.193342E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.164123E+09
                   
Annual Sum or Average 0.454292E+11 0.228339E+11 0.00 0.00 0.00 0.00 0.00 10618850.55 0.129424E+10
Minimum of Months 0.348285E+10 0.175042E+10 0.00 0.00 0.00 0.00 0.00 0.00 46996171.92
Maximum of Months 0.387034E+10 0.194537E+10 0.00 0.00 0.00 0.00 0.00 5769819.08 0.174249E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_1_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.196602E+09 0.222503E+09 0.00 0.00 0.00 0.00 0.00 0.141764E+09
February 0.273974E+09 0.177551E+09 0.200969E+09 0.00 0.00 0.00 0.00 0.00 0.118672E+09
March 0.303685E+09 0.195039E+09 0.222390E+09 0.00 0.00 0.00 0.00 0.00 0.111370E+09
April 0.293479E+09 0.190486E+09 0.215344E+09 0.00 0.00 0.00 0.00 582992.96 89143246.32
May 0.303504E+09 0.195821E+09 0.222446E+09 0.00 0.00 0.00 0.00 333241.03 74353278.16
June 0.293842E+09 0.188975E+09 0.215230E+09 0.00 0.00 0.00 0.00 795572.78 50991321.58
July 0.303141E+09 0.197358E+09 0.222560E+09 0.00 0.00 0.00 0.00 3198964.50 37916062.77
August 0.303685E+09 0.195039E+09 0.222390E+09 0.00 0.00 0.00 0.00 6079392.52 31311934.55
September 0.293479E+09 0.190538E+09 0.215344E+09 0.00 0.00 0.00 0.00 457419.79 54182208.79
October 0.303322E+09 0.196576E+09 0.222503E+09 0.00 0.00 0.00 0.00 1068.49 84679020.10
November 0.293661E+09 0.189731E+09 0.215287E+09 0.00 0.00 0.00 0.00 0.00 0.107777E+09
December 0.303141E+09 0.197383E+09 0.222560E+09 0.00 0.00 0.00 0.00 0.00 0.134140E+09
                   
Annual Sum or Average 0.357224E+10 0.231110E+10 0.261953E+10 0.00 0.00 0.00 0.00 11448652.08 0.103630E+10
Minimum of Months 0.273974E+09 0.177551E+09 0.200969E+09 0.00 0.00 0.00 0.00 0.00 31311934.55
Maximum of Months 0.303685E+09 0.197383E+09 0.222560E+09 0.00 0.00 0.00 0.00 6079392.52 0.141764E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_2_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.196579E+09 0.222477E+09 0.00 0.00 0.00 0.00 0.00 0.140655E+09
February 0.273974E+09 0.177530E+09 0.200945E+09 0.00 0.00 0.00 0.00 0.00 0.116980E+09
March 0.303685E+09 0.195017E+09 0.222364E+09 0.00 0.00 0.00 0.00 0.00 0.109785E+09
April 0.293479E+09 0.190464E+09 0.215319E+09 0.00 0.00 0.00 0.00 561706.76 89096206.07
May 0.303504E+09 0.195798E+09 0.222420E+09 0.00 0.00 0.00 0.00 138463.43 78129164.28
June 0.293842E+09 0.188953E+09 0.215205E+09 0.00 0.00 0.00 0.00 521705.02 55852501.24
July 0.303141E+09 0.197334E+09 0.222534E+09 0.00 0.00 0.00 0.00 2610774.61 45256877.88
August 0.303685E+09 0.195017E+09 0.222364E+09 0.00 0.00 0.00 0.00 5484367.75 35693854.71
September 0.293479E+09 0.190515E+09 0.215319E+09 0.00 0.00 0.00 0.00 180390.14 58243871.25
October 0.303322E+09 0.196553E+09 0.222477E+09 0.00 0.00 0.00 0.00 479.78 83680163.15
November 0.293661E+09 0.189708E+09 0.215262E+09 0.00 0.00 0.00 0.00 0.00 0.106595E+09
December 0.303141E+09 0.197360E+09 0.222534E+09 0.00 0.00 0.00 0.00 0.00 0.132679E+09
                   
Annual Sum or Average 0.357224E+10 0.231083E+10 0.261922E+10 0.00 0.00 0.00 0.00 9497887.49 0.105265E+10
Minimum of Months 0.273974E+09 0.177530E+09 0.200945E+09 0.00 0.00 0.00 0.00 0.00 35693854.71
Maximum of Months 0.303685E+09 0.197360E+09 0.222534E+09 0.00 0.00 0.00 0.00 5484367.75 0.140655E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.123591E+09 0.217995E+09 0.00 0.00 0.00 0.00 0.00 74238325.48
February 0.273974E+09 0.111614E+09 0.196897E+09 0.00 0.00 0.00 0.00 0.00 62049279.96
March 0.303685E+09 0.122608E+09 0.217883E+09 0.00 0.00 0.00 0.00 0.00 58016743.92
April 0.293479E+09 0.119746E+09 0.210981E+09 0.00 0.00 0.00 0.00 300041.45 46130600.09
May 0.303504E+09 0.123099E+09 0.217939E+09 0.00 0.00 0.00 0.00 174141.01 38185101.26
June 0.293842E+09 0.118796E+09 0.210869E+09 0.00 0.00 0.00 0.00 412000.11 26151505.26
July 0.303141E+09 0.124066E+09 0.218051E+09 0.00 0.00 0.00 0.00 1650749.97 19396933.35
August 0.303685E+09 0.122608E+09 0.217883E+09 0.00 0.00 0.00 0.00 3122624.53 16050956.37
September 0.293479E+09 0.119778E+09 0.210981E+09 0.00 0.00 0.00 0.00 236818.25 27940198.16
October 0.303322E+09 0.123574E+09 0.217995E+09 0.00 0.00 0.00 0.00 256.90 44166789.61
November 0.293661E+09 0.119271E+09 0.210925E+09 0.00 0.00 0.00 0.00 0.00 56473571.21
December 0.303141E+09 0.124082E+09 0.218051E+09 0.00 0.00 0.00 0.00 0.00 70083267.08
                   
Annual Sum or Average 0.357224E+10 0.145283E+10 0.256645E+10 0.00 0.00 0.00 0.00 5896632.22 0.538883E+09
Minimum of Months 0.273974E+09 0.111614E+09 0.196897E+09 0.00 0.00 0.00 0.00 0.00 16050956.37
Maximum of Months 0.303685E+09 0.124082E+09 0.218051E+09 0.00 0.00 0.00 0.00 3122624.53 74238325.48



Table of Contents

Report: SpaceGainsMonthly

For: BANQUET_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.459349E+11 0.287054E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.406953E+09
February 0.415303E+11 0.250957E+10 0.134904E+11 0.00 0.00 0.00 0.00 0.00 0.340082E+09
March 0.461508E+11 0.268827E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.324840E+09
April 0.445315E+11 0.245393E+10 0.144540E+11 0.00 0.00 0.00 0.00 654518.87 0.264382E+09
May 0.460320E+11 0.244131E+10 0.149358E+11 0.00 0.00 0.00 0.00 37725.73 0.228245E+09
June 0.446286E+11 0.226940E+10 0.144540E+11 0.00 0.00 0.00 0.00 345116.17 0.167884E+09
July 0.459349E+11 0.235884E+10 0.149358E+11 0.00 0.00 0.00 0.00 3671746.80 0.134446E+09
August 0.461292E+11 0.247234E+10 0.149358E+11 0.00 0.00 0.00 0.00 8264911.93 0.115539E+09
September 0.445099E+11 0.254653E+10 0.144540E+11 0.00 0.00 0.00 0.00 52147.93 0.177124E+09
October 0.459565E+11 0.275942E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.257720E+09
November 0.444343E+11 0.275372E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.00 0.319132E+09
December 0.459349E+11 0.288189E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.386994E+09
                   
Annual Sum or Average 0.541708E+12 0.310058E+11 0.175857E+12 0.00 0.00 0.00 0.00 13026167.42 0.312334E+10
Minimum of Months 0.415303E+11 0.226940E+10 0.134904E+11 0.00 0.00 0.00 0.00 0.00 0.115539E+09
Maximum of Months 0.461508E+11 0.288189E+10 0.149358E+11 0.00 0.00 0.00 0.00 8264911.93 0.406953E+09



Table of Contents

Report: SpaceGainsMonthly

For: DINING_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.459349E+11 0.287054E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.411118E+09
February 0.415303E+11 0.250957E+10 0.134904E+11 0.00 0.00 0.00 0.00 0.00 0.343388E+09
March 0.461508E+11 0.268827E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.327629E+09
April 0.445315E+11 0.245393E+10 0.144540E+11 0.00 0.00 0.00 0.00 642433.48 0.266269E+09
May 0.460320E+11 0.244131E+10 0.149358E+11 0.00 0.00 0.00 0.00 37721.86 0.229436E+09
June 0.446286E+11 0.226940E+10 0.144540E+11 0.00 0.00 0.00 0.00 345099.80 0.168745E+09
July 0.459349E+11 0.235884E+10 0.149358E+11 0.00 0.00 0.00 0.00 3648544.48 0.134990E+09
August 0.461292E+11 0.247234E+10 0.149358E+11 0.00 0.00 0.00 0.00 8172960.64 0.116158E+09
September 0.445099E+11 0.254653E+10 0.144540E+11 0.00 0.00 0.00 0.00 52142.56 0.178297E+09
October 0.459565E+11 0.275942E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.259977E+09
November 0.444343E+11 0.275372E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.00 0.322338E+09
December 0.459349E+11 0.288189E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.390904E+09
                   
Annual Sum or Average 0.541708E+12 0.310058E+11 0.175857E+12 0.00 0.00 0.00 0.00 12898902.82 0.314925E+10
Minimum of Months 0.415303E+11 0.226940E+10 0.134904E+11 0.00 0.00 0.00 0.00 0.00 0.116158E+09
Maximum of Months 0.461508E+11 0.288189E+10 0.149358E+11 0.00 0.00 0.00 0.00 8172960.64 0.411118E+09



Table of Contents

Report: SpaceGainsMonthly

For: KITCHEN_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.408770E+10 0.110133E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 0.00 0.368825E+09
February 0.369574E+10 0.994402E+09 0.301256E+11 0.275852E+11 0.00 0.00 0.00 0.00 0.307441E+09
March 0.410691E+10 0.110473E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 0.00 0.292690E+09
April 0.396281E+10 0.106399E+10 0.322775E+11 0.295556E+11 0.00 0.00 0.00 577689.95 0.237231E+09
May 0.409635E+10 0.110324E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 34626.32 0.204071E+09
June 0.397146E+10 0.106887E+10 0.322775E+11 0.295556E+11 0.00 0.00 0.00 312372.15 0.150112E+09
July 0.408770E+10 0.109836E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 3269096.17 0.120001E+09
August 0.410499E+10 0.110515E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 7299946.39 0.103367E+09
September 0.396089E+10 0.106442E+10 0.322775E+11 0.295556E+11 0.00 0.00 0.00 47823.15 0.158984E+09
October 0.408962E+10 0.110091E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 0.00 0.232246E+09
November 0.395417E+10 0.106802E+10 0.322775E+11 0.295556E+11 0.00 0.00 0.00 0.00 0.288711E+09
December 0.408770E+10 0.109836E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 0.00 0.350509E+09
                   
Annual Sum or Average 0.482060E+11 0.129718E+11 0.392709E+12 0.359593E+12 0.00 0.00 0.00 11541554.14 0.281419E+10
Minimum of Months 0.369574E+10 0.994402E+09 0.301256E+11 0.275852E+11 0.00 0.00 0.00 0.00 0.103367E+09
Maximum of Months 0.410691E+10 0.110515E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 7299946.39 0.368825E+09



Table of Contents

Report: SpaceGainsMonthly

For: CORRIDOR_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.407704E+10 0.205176E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.309491E+09
February 0.368610E+10 0.185255E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.255765E+09
March 0.409620E+10 0.205809E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.238926E+09
April 0.395248E+10 0.198220E+10 0.00 0.00 0.00 0.00 0.00 1008670.73 0.193666E+09
May 0.408566E+10 0.205532E+10 0.00 0.00 0.00 0.00 0.00 167512.78 0.168498E+09
June 0.396110E+10 0.199129E+10 0.00 0.00 0.00 0.00 0.00 547631.48 0.123035E+09
July 0.407704E+10 0.204623E+10 0.00 0.00 0.00 0.00 0.00 3719428.63 99331755.95
August 0.409429E+10 0.205888E+10 0.00 0.00 0.00 0.00 0.00 8083414.52 83988436.88
September 0.395056E+10 0.198299E+10 0.00 0.00 0.00 0.00 0.00 103184.25 0.128546E+09
October 0.407896E+10 0.205097E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.184308E+09
November 0.394385E+10 0.198971E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.233951E+09
December 0.407704E+10 0.204623E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.291675E+09
                   
Annual Sum or Average 0.480803E+11 0.241662E+11 0.00 0.00 0.00 0.00 0.00 13629842.39 0.231118E+10
Minimum of Months 0.368610E+10 0.185255E+10 0.00 0.00 0.00 0.00 0.00 0.00 83988436.88
Maximum of Months 0.409620E+10 0.205888E+10 0.00 0.00 0.00 0.00 0.00 8083414.52 0.309491E+09



Table of Contents

Report: PeakSpaceGainsMonthly

For: BASEMENT

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 11501.89 02-JAN-00:10 13190.31 02-JAN-20:10 9632.53 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 0.00
February 11501.89 01-FEB-00:10 13190.31 01-FEB-20:10 9632.53 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 0.00
March 11501.89 01-MAR-00:10 13190.31 01-MAR-20:10 9632.53 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 0.00
April 11501.89 01-APR-00:10 13190.31 03-APR-19:10 9632.53 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 0.00
May 11501.89 01-MAY-00:10 13190.31 01-MAY-19:10 9632.53 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 0.00
June 11501.89 01-JUN-00:10 13190.31 01-JUN-19:10 9632.53 01-JUN-19:10 0.00 0.00 0.00 0.00 0.00 0.00
July 11501.89 01-JUL-00:10 13190.31 03-JUL-19:10 9632.53 03-JUL-19:10 0.00 0.00 0.00 0.00 0.00 0.00
August 11501.89 01-AUG-00:10 13190.31 01-AUG-19:10 9632.53 01-AUG-19:10 0.00 0.00 0.00 0.00 0.00 0.00
September 11501.89 01-SEP-00:10 13190.31 01-SEP-19:10 9632.53 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 0.00
October 11501.89 01-OCT-23:10 13190.31 02-OCT-19:10 9632.53 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 0.00
November 11501.89 01-NOV-00:10 13190.31 01-NOV-19:10 9632.53 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 0.00
December 11501.89 01-DEC-00:10 13190.31 01-DEC-20:10 9632.53 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 11501.89   13190.31   9632.53   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 11501.89   13190.31   9632.53   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: RETAIL_1_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1169.53 02-JAN-00:10 597.59 02-JAN-20:10 685.60 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 145.51 15-JAN-08:00
February 1169.53 01-FEB-00:10 597.59 01-FEB-20:10 685.60 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 152.57 19-FEB-06:00
March 1169.53 01-MAR-00:10 597.59 01-MAR-20:10 685.60 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 123.98 01-MAR-07:00
April 1169.53 01-APR-00:10 597.59 03-APR-19:10 685.60 03-APR-19:10 0.00 0.00 0.00 0.00 21.67 01-APR-17:00 109.76 19-APR-05:00
May 1169.53 01-MAY-00:10 597.59 01-MAY-19:10 685.60 01-MAY-19:10 0.00 0.00 0.00 0.00 13.86 05-MAY-16:00 92.79 11-MAY-03:50
June 1169.53 01-JUN-00:10 597.59 01-JUN-19:10 685.60 01-JUN-19:10 0.00 0.00 0.00 0.00 22.07 28-JUN-17:00 69.77 15-JUN-03:50
July 1169.53 01-JUL-00:10 597.59 03-JUL-19:10 685.60 03-JUL-19:10 0.00 0.00 0.00 0.00 33.55 24-JUL-15:00 54.22 07-JUL-05:00
August 1169.53 01-AUG-00:10 597.59 01-AUG-19:10 685.60 01-AUG-19:10 0.00 0.00 0.00 0.00 42.62 10-AUG-17:00 55.83 01-AUG-06:00
September 1169.53 01-SEP-00:10 597.59 01-SEP-19:10 685.60 01-SEP-19:10 0.00 0.00 0.00 0.00 8.55 14-SEP-17:00 76.47 27-SEP-05:00
October 1169.53 01-OCT-23:10 597.59 02-OCT-19:10 685.60 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 85.63 13-OCT-05:00
November 1169.53 01-NOV-00:10 597.59 01-NOV-19:10 685.60 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 119.24 11-NOV-07:30
December 1169.53 01-DEC-00:10 597.59 01-DEC-20:10 685.60 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 131.10 26-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1169.53   597.59   685.60   0.00 0.00 0.00 0.00 0.00   54.22  
Maximum of Months 1169.53   597.59   685.60   0.00 0.00 0.00 0.00 42.62   152.57  



Table of Contents

Report: PeakSpaceGainsMonthly

For: RETAIL_2_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1354.32 02-JAN-00:10 692.02 02-JAN-20:10 793.93 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 57.51 15-JAN-08:00
February 1354.32 01-FEB-00:10 692.02 01-FEB-20:10 793.93 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 59.31 19-FEB-05:00
March 1354.32 01-MAR-00:10 692.02 01-MAR-20:10 793.93 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 51.14 01-MAR-07:00
April 1354.32 01-APR-00:10 692.02 03-APR-19:10 793.93 03-APR-19:10 0.00 0.00 0.00 0.00 9.73 01-APR-16:00 45.19 19-APR-05:00
May 1354.32 01-MAY-00:10 692.02 01-MAY-19:10 793.93 01-MAY-19:10 0.00 0.00 0.00 0.00 4.12 05-MAY-16:00 39.57 11-MAY-03:00
June 1354.32 01-JUN-00:10 692.02 01-JUN-19:10 793.93 01-JUN-19:10 0.00 0.00 0.00 0.00 7.24 28-JUN-17:00 30.61 15-JUN-03:00
July 1354.32 01-JUL-00:10 692.02 03-JUL-19:10 793.93 03-JUL-19:10 0.00 0.00 0.00 0.00 14.21 24-JUL-15:00 26.02 07-JUL-05:00
August 1354.32 01-AUG-00:10 692.02 01-AUG-19:10 793.93 01-AUG-19:10 0.00 0.00 0.00 0.00 16.17 29-AUG-16:00 26.31 01-AUG-06:00
September 1354.32 01-SEP-00:10 692.02 01-SEP-19:10 793.93 01-SEP-19:10 0.00 0.00 0.00 0.00 3.80 22-SEP-16:00 33.01 27-SEP-05:00
October 1354.32 01-OCT-23:10 692.02 02-OCT-19:10 793.93 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 37.16 13-OCT-05:00
November 1354.32 01-NOV-00:10 692.02 01-NOV-19:10 793.93 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 48.51 11-NOV-08:00
December 1354.32 01-DEC-00:10 692.02 01-DEC-20:10 793.93 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 51.72 26-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1354.32   692.02   793.93   0.00 0.00 0.00 0.00 0.00   26.02  
Maximum of Months 1354.32   692.02   793.93   0.00 0.00 0.00 0.00 16.17   59.31  



Table of Contents

Report: PeakSpaceGainsMonthly

For: MECH_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 286.42 02-JAN-00:10 684.18 02-JAN-20:10 839.45 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 132.73 15-JAN-08:00
February 286.42 01-FEB-00:10 684.18 01-FEB-20:10 839.45 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 139.18 19-FEB-06:00
March 286.42 01-MAR-00:10 684.18 01-MAR-20:10 839.45 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 116.94 01-MAR-07:00
April 286.42 01-APR-00:10 684.18 03-APR-19:10 839.45 03-APR-19:10 0.00 0.00 0.00 0.00 26.97 01-APR-16:00 101.84 19-APR-05:00
May 286.42 01-MAY-00:10 684.18 01-MAY-19:10 839.45 01-MAY-19:10 0.00 0.00 0.00 0.00 11.26 05-MAY-16:00 90.74 11-MAY-03:00
June 286.42 01-JUN-00:10 684.18 01-JUN-19:10 839.45 01-JUN-19:10 0.00 0.00 0.00 0.00 18.08 28-JUN-17:00 69.98 15-JUN-03:00
July 286.42 01-JUL-00:10 684.18 03-JUL-19:10 839.45 03-JUL-19:10 0.00 0.00 0.00 0.00 34.00 24-JUL-15:00 59.05 19-JUL-05:00
August 286.42 01-AUG-00:10 684.18 01-AUG-19:10 839.45 01-AUG-19:10 0.00 0.00 0.00 0.00 38.70 29-AUG-16:00 60.64 01-AUG-06:00
September 286.42 01-SEP-00:10 684.18 01-SEP-19:10 839.45 01-SEP-19:10 0.00 0.00 0.00 0.00 11.74 22-SEP-16:00 75.16 27-SEP-05:00
October 286.42 01-OCT-23:10 684.18 02-OCT-19:10 839.45 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 83.40 13-OCT-05:00
November 286.42 01-NOV-00:10 684.18 01-NOV-19:10 839.45 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 110.12 11-NOV-08:00
December 286.42 01-DEC-00:10 684.18 01-DEC-20:10 839.45 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 119.58 26-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 286.42   684.18   839.45   0.00 0.00 0.00 0.00 0.00   59.05  
Maximum of Months 286.42   684.18   839.45   0.00 0.00 0.00 0.00 38.70   139.18  



Table of Contents

Report: PeakSpaceGainsMonthly

For: STORAGE_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 220.32 02-JAN-00:10 251.84 02-JAN-20:10 242.16 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 76.57 15-JAN-08:00
February 220.32 01-FEB-00:10 251.84 01-FEB-20:10 242.16 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 80.30 19-FEB-06:00
March 220.32 01-MAR-00:10 251.84 01-MAR-20:10 242.16 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 66.00 01-MAR-07:00
April 220.32 01-APR-00:10 251.84 03-APR-19:10 242.16 03-APR-19:10 0.00 0.00 0.00 0.00 15.62 01-APR-16:00 57.77 19-APR-05:00
May 220.32 01-MAY-00:10 251.84 01-MAY-19:10 242.16 01-MAY-19:10 0.00 0.00 0.00 0.00 6.75 05-MAY-16:00 51.28 11-MAY-03:00
June 220.32 01-JUN-00:10 251.84 01-JUN-19:10 242.16 01-JUN-19:10 0.00 0.00 0.00 0.00 10.69 28-JUN-17:00 39.47 15-JUN-03:00
July 220.32 01-JUL-00:10 251.84 03-JUL-19:10 242.16 03-JUL-19:10 0.00 0.00 0.00 0.00 19.74 24-JUL-15:00 33.39 19-JUL-05:00
August 220.32 01-AUG-00:10 251.84 01-AUG-19:10 242.16 01-AUG-19:10 0.00 0.00 0.00 0.00 22.48 10-AUG-17:00 34.04 01-AUG-06:00
September 220.32 01-SEP-00:10 251.84 01-SEP-19:10 242.16 01-SEP-19:10 0.00 0.00 0.00 0.00 7.06 22-SEP-16:00 42.36 27-SEP-05:00
October 220.32 01-OCT-23:10 251.84 02-OCT-19:10 242.16 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 47.14 13-OCT-05:00
November 220.32 01-NOV-00:10 251.84 01-NOV-19:10 242.16 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 62.75 11-NOV-08:00
December 220.32 01-DEC-00:10 251.84 01-DEC-20:10 242.16 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 68.99 26-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 220.32   251.84   242.16   0.00 0.00 0.00 0.00 0.00   33.39  
Maximum of Months 220.32   251.84   242.16   0.00 0.00 0.00 0.00 22.48   80.30  



Table of Contents

Report: PeakSpaceGainsMonthly

For: LAUNDRY_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 907.20 02-JAN-00:10 325.08 02-JAN-20:10 4572.80 02-JAN-20:10 39726.58 02-JAN-20:10 0.00 0.00 0.00 0.00 01-JAN-00:10 203.03 15-JAN-08:00
February 907.20 01-FEB-00:10 325.08 01-FEB-20:10 4572.80 01-FEB-20:10 39726.58 01-FEB-20:10 0.00 0.00 0.00 0.00 01-FEB-00:03 206.90 19-FEB-08:00
March 907.20 01-MAR-00:10 325.08 01-MAR-20:10 4572.80 01-MAR-20:10 39726.58 01-MAR-20:10 0.00 0.00 0.00 0.00 01-MAR-00:03 175.81 01-MAR-07:00
April 907.20 01-APR-00:10 325.08 03-APR-19:10 4572.80 03-APR-19:10 39726.58 03-APR-19:10 0.00 0.00 0.00 32.15 01-APR-16:00 156.59 19-APR-05:10
May 907.20 01-MAY-00:10 325.08 01-MAY-19:10 4572.80 01-MAY-19:10 39726.58 01-MAY-19:10 0.00 0.00 0.00 17.60 05-MAY-16:00 130.93 11-MAY-05:10
June 907.20 01-JUN-00:10 325.08 01-JUN-19:10 4572.80 01-JUN-19:10 39726.58 01-JUN-19:10 0.00 0.00 0.00 30.33 28-JUN-17:00 102.31 15-JUN-05:10
July 907.20 01-JUL-00:10 325.08 03-JUL-19:10 4572.80 03-JUL-19:10 39726.58 03-JUL-19:10 0.00 0.00 0.00 49.38 24-JUL-15:00 84.82 07-JUL-05:10
August 907.20 01-AUG-00:10 325.08 01-AUG-19:10 4572.80 01-AUG-19:10 39726.58 01-AUG-19:10 0.00 0.00 0.00 61.63 10-AUG-17:00 86.67 21-AUG-05:10
September 907.20 01-SEP-00:10 325.08 01-SEP-19:10 4572.80 01-SEP-19:10 39726.58 01-SEP-19:10 0.00 0.00 0.00 18.85 14-SEP-17:00 114.21 27-SEP-05:10
October 907.20 01-OCT-23:10 325.08 02-OCT-19:10 4572.80 02-OCT-19:10 39726.58 02-OCT-19:10 0.00 0.00 0.00 0.00 01-OCT-00:10 125.74 13-OCT-05:10
November 907.20 01-NOV-00:10 325.08 01-NOV-19:10 4572.80 01-NOV-19:10 39726.58 01-NOV-19:10 0.00 0.00 0.00 0.00 01-NOV-00:05 169.68 11-NOV-08:00
December 907.20 01-DEC-00:10 325.08 01-DEC-20:10 4572.80 01-DEC-20:10 39726.58 01-DEC-20:10 0.00 0.00 0.00 0.00 01-DEC-00:03 184.71 26-DEC-07:00
                               
Annual Sum or Average                 0.00 0.00 0.00        
Minimum of Months 907.20   325.08   4572.80   39726.58   0.00 0.00 0.00 0.00   84.82  
Maximum of Months 907.20   325.08   4572.80   39726.58   0.00 0.00 0.00 61.63   206.90  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CAFE_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 15368.40 02-JAN-00:10 1701.53 02-JAN-20:10 965.27 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 321.67 15-JAN-08:00
February 15368.40 01-FEB-00:10 1701.53 01-FEB-20:10 965.27 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 337.33 19-FEB-06:00
March 15368.40 01-MAR-00:10 1701.53 01-MAR-20:10 965.27 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 281.68 01-MAR-07:00
April 15368.40 01-APR-00:10 1701.53 03-APR-19:10 965.27 03-APR-19:10 0.00 0.00 0.00 0.00 43.84 01-APR-16:00 257.25 19-APR-05:00
May 15368.40 01-MAY-00:10 1701.53 01-MAY-19:10 965.27 01-MAY-19:10 0.00 0.00 0.00 0.00 25.35 05-MAY-16:00 223.49 11-MAY-03:00
June 15368.40 01-JUN-00:10 1701.53 01-JUN-19:40 965.27 01-JUN-19:10 0.00 0.00 0.00 0.00 44.20 28-JUN-17:00 172.97 15-JUN-03:00
July 15368.40 01-JUL-00:10 1701.53 03-JUL-19:00 965.27 03-JUL-19:10 0.00 0.00 0.00 0.00 75.59 24-JUL-15:00 146.78 19-JUL-05:00
August 15368.40 01-AUG-00:10 1701.53 01-AUG-19:19 965.27 01-AUG-19:10 0.00 0.00 0.00 0.00 92.90 10-AUG-17:00 146.67 01-AUG-05:00
September 15368.40 01-SEP-00:10 1701.53 01-SEP-19:10 965.27 01-SEP-19:10 0.00 0.00 0.00 0.00 16.52 14-SEP-17:00 186.10 27-SEP-05:00
October 15368.40 01-OCT-23:10 1701.53 02-OCT-19:10 965.27 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 211.82 13-OCT-05:00
November 15368.40 01-NOV-00:10 1701.53 01-NOV-19:10 965.27 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 269.73 11-NOV-08:00
December 15368.40 01-DEC-00:10 1701.53 01-DEC-20:10 965.27 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 289.80 26-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 15368.40   1701.53   965.27   0.00 0.00 0.00 0.00 0.00   146.67  
Maximum of Months 15368.40   1701.53   965.27   0.00 0.00 0.00 0.00 92.90   337.33  



Table of Contents

Report: PeakSpaceGainsMonthly

For: LOBBY_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 45622.98 02-JAN-00:10 9504.80 02-JAN-20:10 10029.21 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 961.25 15-JAN-08:00
February 45622.98 01-FEB-00:10 9504.80 01-FEB-20:10 10029.21 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 991.36 19-FEB-05:00
March 45622.98 01-MAR-00:10 9504.80 01-MAR-20:10 10029.21 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 852.43 01-MAR-07:00
April 45622.98 01-APR-00:10 9504.80 03-APR-19:10 10029.21 03-APR-19:10 0.00 0.00 0.00 0.00 151.42 01-APR-16:00 766.02 19-APR-05:00
May 45622.98 01-MAY-00:10 9504.80 01-MAY-19:10 10029.21 01-MAY-19:10 0.00 0.00 0.00 0.00 66.38 05-MAY-16:00 669.10 11-MAY-03:00
June 45622.98 01-JUN-00:10 9504.80 01-JUN-19:30 10029.21 01-JUN-19:10 0.00 0.00 0.00 0.00 121.77 28-JUN-17:00 522.98 15-JUN-03:00
July 45622.98 01-JUL-00:10 9504.80 03-JUL-19:40 10029.21 03-JUL-19:10 0.00 0.00 0.00 0.00 234.42 24-JUL-15:00 441.51 19-JUL-05:00
August 45622.98 01-AUG-00:10 9504.80 01-AUG-19:19 10029.21 01-AUG-19:10 0.00 0.00 0.00 0.00 268.24 10-AUG-17:00 437.28 21-AUG-05:00
September 45622.98 01-SEP-00:10 9504.80 01-SEP-19:10 10029.21 01-SEP-19:10 0.00 0.00 0.00 0.00 53.21 22-SEP-16:00 563.48 27-SEP-05:00
October 45622.98 01-OCT-23:10 9504.80 02-OCT-19:10 10029.21 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 630.45 13-OCT-05:00
November 45622.98 01-NOV-00:10 9504.80 01-NOV-19:10 10029.21 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 812.40 11-NOV-08:00
December 45622.98 01-DEC-00:10 9504.80 01-DEC-20:10 10029.21 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 867.95 26-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 45622.98   9504.80   10029.21   0.00 0.00 0.00 0.00 0.00   437.28  
Maximum of Months 45622.98   9504.80   10029.21   0.00 0.00 0.00 0.00 268.24   991.36  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_1_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 177.88 01-JAN-19:10 237.06 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 84.96 15-JAN-08:00
February 180.00 01-FEB-00:10 177.88 01-FEB-20:10 237.06 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 89.06 19-FEB-06:00
March 180.00 01-MAR-00:10 177.88 01-MAR-20:10 237.06 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 72.46 01-MAR-07:00
April 180.00 01-APR-00:10 177.88 01-APR-18:10 237.06 01-APR-07:10 0.00 0.00 0.00 0.00 18.02 27-APR-15:10 64.21 19-APR-05:00
May 180.00 01-MAY-00:10 177.88 01-MAY-19:10 237.06 01-MAY-06:10 0.00 0.00 0.00 0.00 11.58 05-MAY-16:00 54.34 11-MAY-03:10
June 180.00 01-JUN-00:10 177.88 01-JUN-19:10 237.06 01-JUN-06:10 0.00 0.00 0.00 0.00 16.64 28-JUN-17:00 40.97 15-JUN-04:00
July 180.00 01-JUL-00:10 177.88 01-JUL-18:10 237.06 01-JUL-07:10 0.00 0.00 0.00 0.00 27.06 24-JUL-15:10 32.52 04-JUL-07:20
August 180.00 01-AUG-00:10 177.88 01-AUG-19:10 237.06 01-AUG-06:10 0.00 0.00 0.00 0.00 31.13 10-AUG-17:00 36.53 01-AUG-08:00
September 180.00 01-SEP-00:10 177.88 01-SEP-19:10 237.06 01-SEP-06:10 0.00 0.00 0.00 0.00 11.60 14-SEP-17:00 44.87 27-SEP-05:00
October 180.00 01-OCT-00:10 177.88 01-OCT-18:10 237.06 01-OCT-07:10 0.00 0.00 0.00 0.00 1.34 04-OCT-15:10 50.18 13-OCT-05:00
November 180.00 01-NOV-00:10 177.88 01-NOV-19:10 237.06 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 69.70 11-NOV-07:10
December 180.00 01-DEC-00:10 177.88 01-DEC-20:10 237.06 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 76.59 26-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   177.88   237.06   0.00 0.00 0.00 0.00 0.00   32.52  
Maximum of Months 180.00   177.88   237.06   0.00 0.00 0.00 0.00 31.13   89.06  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_2_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 177.86 01-JAN-19:10 237.03 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 84.96 15-JAN-08:00
February 180.00 01-FEB-00:10 177.86 01-FEB-20:10 237.03 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 89.06 19-FEB-06:00
March 180.00 01-MAR-00:10 177.86 01-MAR-20:10 237.03 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 72.46 01-MAR-07:00
April 180.00 01-APR-00:10 177.86 01-APR-18:10 237.03 01-APR-07:10 0.00 0.00 0.00 0.00 18.02 27-APR-15:10 64.21 19-APR-05:00
May 180.00 01-MAY-00:10 177.86 01-MAY-19:10 237.03 01-MAY-06:10 0.00 0.00 0.00 0.00 11.58 05-MAY-16:00 54.34 11-MAY-03:10
June 180.00 01-JUN-00:10 177.86 01-JUN-19:10 237.03 01-JUN-06:10 0.00 0.00 0.00 0.00 16.63 28-JUN-17:00 40.97 15-JUN-04:00
July 180.00 01-JUL-00:10 177.86 01-JUL-18:10 237.03 01-JUL-07:10 0.00 0.00 0.00 0.00 27.06 24-JUL-15:10 36.43 11-JUL-19:55
August 180.00 01-AUG-00:10 177.86 01-AUG-19:10 237.03 01-AUG-06:10 0.00 0.00 0.00 0.00 31.13 10-AUG-17:00 36.52 01-AUG-08:00
September 180.00 01-SEP-00:10 177.86 01-SEP-19:10 237.03 01-SEP-06:10 0.00 0.00 0.00 0.00 11.60 14-SEP-17:00 44.86 27-SEP-05:00
October 180.00 01-OCT-00:10 177.86 01-OCT-18:10 237.03 01-OCT-07:10 0.00 0.00 0.00 0.00 1.34 04-OCT-15:10 50.18 13-OCT-05:00
November 180.00 01-NOV-00:10 177.86 01-NOV-19:10 237.03 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 69.69 11-NOV-07:10
December 180.00 01-DEC-00:10 177.86 01-DEC-20:10 237.03 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 76.59 26-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   177.86   237.03   0.00 0.00 0.00 0.00 0.00   36.43  
Maximum of Months 180.00   177.86   237.03   0.00 0.00 0.00 0.00 31.13   89.06  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 01-JAN-00:10 111.79 01-JAN-19:10 232.19 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 24.44 15-JAN-08:10
February 0.00 01-FEB-00:10 111.79 01-FEB-20:10 232.19 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 25.67 09-FEB-08:00
March 0.00 01-MAR-00:10 111.79 01-MAR-20:10 232.19 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 24.44 01-MAR-07:00
April 0.00 01-APR-00:10 111.79 01-APR-18:10 232.19 01-APR-07:10 0.00 0.00 0.00 0.00 0.41 27-APR-15:00 21.73 19-APR-05:10
May 0.00 01-MAY-00:10 111.79 01-MAY-19:10 232.19 01-MAY-06:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:05 19.49 11-MAY-03:00
June 0.00 01-JUN-00:10 111.79 01-JUN-19:10 232.19 01-JUN-06:10 0.00 0.00 0.00 0.00 0.00 01-JUN-00:05 15.86 01-JUN-04:40
July 0.00 01-JUL-00:10 111.79 01-JUL-18:10 232.19 01-JUL-07:10 0.00 0.00 0.00 0.00 3.20 24-JUL-15:00 13.84 07-JUL-05:00
August 0.00 01-AUG-00:10 111.79 01-AUG-19:10 232.19 01-AUG-06:10 0.00 0.00 0.00 0.00 4.15 10-AUG-17:00 13.91 06-AUG-05:00
September 0.00 01-SEP-00:10 111.79 01-SEP-19:10 232.19 01-SEP-06:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:05 16.55 27-SEP-05:10
October 0.00 01-OCT-00:10 111.79 01-OCT-18:10 232.19 01-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 18.75 13-OCT-05:10
November 0.00 01-NOV-00:10 111.79 01-NOV-19:10 232.19 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 23.54 11-NOV-23:00
December 0.00 01-DEC-00:10 111.79 01-DEC-20:10 232.19 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 23.92 06-DEC-21:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 0.00   111.79   232.19   0.00 0.00 0.00 0.00 0.00   13.84  
Maximum of Months 0.00   111.79   232.19   0.00 0.00 0.00 0.00 4.15   25.67  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 111.82 01-JAN-19:10 232.26 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 23.71 15-JAN-08:00
February 180.00 01-FEB-00:10 111.82 01-FEB-20:10 232.26 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 24.86 19-FEB-06:00
March 180.00 01-MAR-00:10 111.82 01-MAR-20:10 232.26 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 20.22 01-MAR-07:00
April 180.00 01-APR-00:10 111.82 01-APR-18:10 232.26 01-APR-07:10 0.00 0.00 0.00 0.00 5.03 27-APR-15:10 17.92 19-APR-05:00
May 180.00 01-MAY-00:10 111.82 01-MAY-19:10 232.26 01-MAY-06:10 0.00 0.00 0.00 0.00 3.23 05-MAY-16:00 15.17 11-MAY-03:10
June 180.00 01-JUN-00:10 111.82 01-JUN-19:10 232.26 01-JUN-06:10 0.00 0.00 0.00 0.00 4.64 28-JUN-17:00 11.43 15-JUN-04:00
July 180.00 01-JUL-00:10 111.82 01-JUL-18:10 232.26 01-JUL-07:10 0.00 0.00 0.00 0.00 7.55 24-JUL-15:10 9.53 04-JUL-07:20
August 180.00 01-AUG-00:10 111.82 01-AUG-19:10 232.26 01-AUG-06:10 0.00 0.00 0.00 0.00 8.69 10-AUG-17:00 10.03 01-AUG-08:00
September 180.00 01-SEP-00:10 111.82 01-SEP-19:10 232.26 01-SEP-06:10 0.00 0.00 0.00 0.00 3.24 14-SEP-17:00 12.52 27-SEP-05:00
October 180.00 01-OCT-00:10 111.82 01-OCT-18:10 232.26 01-OCT-07:10 0.00 0.00 0.00 0.00 0.37 04-OCT-15:09 14.15 29-OCT-08:00
November 180.00 01-NOV-00:10 111.82 01-NOV-19:10 232.26 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 19.75 11-NOV-08:20
December 180.00 01-DEC-00:10 111.82 01-DEC-20:10 232.26 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 21.38 26-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   111.82   232.26   0.00 0.00 0.00 0.00 0.00   9.53  
Maximum of Months 180.00   111.82   232.26   0.00 0.00 0.00 0.00 8.69   24.86  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_5_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 177.88 01-JAN-19:10 237.06 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 84.96 15-JAN-08:00
February 180.00 01-FEB-00:10 177.88 01-FEB-20:10 237.06 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 89.06 19-FEB-06:00
March 180.00 01-MAR-00:10 177.88 01-MAR-20:10 237.06 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 72.46 01-MAR-07:00
April 180.00 01-APR-00:10 177.88 01-APR-18:10 237.06 01-APR-07:10 0.00 0.00 0.00 0.00 18.02 27-APR-15:10 64.21 19-APR-05:00
May 180.00 01-MAY-00:10 177.88 01-MAY-19:10 237.06 01-MAY-06:10 0.00 0.00 0.00 0.00 11.58 05-MAY-16:00 54.34 11-MAY-03:10
June 180.00 01-JUN-00:10 177.88 01-JUN-19:10 237.06 01-JUN-06:10 0.00 0.00 0.00 0.00 16.64 28-JUN-17:00 40.97 15-JUN-04:00
July 180.00 01-JUL-00:10 177.88 01-JUL-18:10 237.06 01-JUL-07:10 0.00 0.00 0.00 0.00 27.06 24-JUL-15:10 32.46 04-JUL-07:20
August 180.00 01-AUG-00:10 177.88 01-AUG-19:10 237.06 01-AUG-06:10 0.00 0.00 0.00 0.00 31.13 10-AUG-17:00 37.41 01-AUG-07:20
September 180.00 01-SEP-00:10 177.88 01-SEP-19:10 237.06 01-SEP-06:10 0.00 0.00 0.00 0.00 11.60 14-SEP-17:00 44.87 27-SEP-05:00
October 180.00 01-OCT-00:10 177.88 01-OCT-18:10 237.06 01-OCT-07:10 0.00 0.00 0.00 0.00 1.34 04-OCT-15:10 50.18 13-OCT-05:00
November 180.00 01-NOV-00:10 177.88 01-NOV-19:10 237.06 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 69.70 11-NOV-07:10
December 180.00 01-DEC-00:10 177.88 01-DEC-20:10 237.06 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 76.60 26-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   177.88   237.06   0.00 0.00 0.00 0.00 0.00   32.46  
Maximum of Months 180.00   177.88   237.06   0.00 0.00 0.00 0.00 31.13   89.06  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_6_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 177.86 01-JAN-19:10 237.03 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 84.96 15-JAN-08:00
February 180.00 01-FEB-00:10 177.86 01-FEB-20:10 237.03 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 89.06 19-FEB-06:00
March 180.00 01-MAR-00:10 177.86 01-MAR-20:10 237.03 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 72.46 01-MAR-07:00
April 180.00 01-APR-00:10 177.86 01-APR-18:10 237.03 01-APR-07:10 0.00 0.00 0.00 0.00 18.02 27-APR-15:10 64.21 19-APR-05:00
May 180.00 01-MAY-00:10 177.86 01-MAY-19:10 237.03 01-MAY-06:10 0.00 0.00 0.00 0.00 11.58 05-MAY-16:00 54.34 11-MAY-03:10
June 180.00 01-JUN-00:10 177.86 01-JUN-19:10 237.03 01-JUN-06:10 0.00 0.00 0.00 0.00 16.63 28-JUN-17:00 40.97 15-JUN-04:00
July 180.00 01-JUL-00:10 177.86 01-JUL-18:10 237.03 01-JUL-07:10 0.00 0.00 0.00 0.00 27.06 24-JUL-15:10 32.61 04-JUL-07:20
August 180.00 01-AUG-00:10 177.86 01-AUG-19:10 237.03 01-AUG-06:10 0.00 0.00 0.00 0.00 31.13 10-AUG-17:00 37.41 01-AUG-07:20
September 180.00 01-SEP-00:10 177.86 01-SEP-19:10 237.03 01-SEP-06:10 0.00 0.00 0.00 0.00 11.60 14-SEP-17:00 44.86 27-SEP-05:00
October 180.00 01-OCT-00:10 177.86 01-OCT-18:10 237.03 01-OCT-07:10 0.00 0.00 0.00 0.00 1.34 04-OCT-15:09 50.18 13-OCT-05:00
November 180.00 01-NOV-00:10 177.86 01-NOV-19:10 237.03 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 69.69 11-NOV-07:20
December 180.00 01-DEC-00:10 177.86 01-DEC-20:10 237.03 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 76.59 26-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   177.86   237.03   0.00 0.00 0.00 0.00 0.00   32.61  
Maximum of Months 180.00   177.86   237.03   0.00 0.00 0.00 0.00 31.13   89.06  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORRIDOR_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2263.36 02-JAN-00:10 1867.32 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 102.29 15-JAN-08:00
February 2263.36 01-FEB-00:10 1867.32 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 107.25 19-FEB-06:00
March 2263.36 01-MAR-00:10 1867.32 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 87.35 01-MAR-07:00
April 2263.36 01-APR-00:10 1867.32 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 20.38 01-APR-16:00 77.32 19-APR-05:00
May 2263.36 01-MAY-00:10 1867.32 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 9.09 05-MAY-16:00 68.98 11-MAY-03:00
June 2263.36 01-JUN-00:10 1867.32 01-JUN-19:10 0.00 0.00 0.00 0.00 0.00 14.22 28-JUN-17:00 52.72 15-JUN-03:00
July 2263.36 01-JUL-00:10 1867.32 03-JUL-19:10 0.00 0.00 0.00 0.00 0.00 26.20 24-JUL-15:00 44.15 19-JUL-05:00
August 2263.36 01-AUG-00:10 1867.32 01-AUG-19:10 0.00 0.00 0.00 0.00 0.00 30.26 29-AUG-16:00 44.94 01-AUG-06:00
September 2263.36 01-SEP-00:10 1867.32 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 9.20 22-SEP-16:00 56.12 27-SEP-05:00
October 2263.36 01-OCT-23:10 1867.32 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 62.99 13-OCT-05:00
November 2263.36 01-NOV-00:10 1867.32 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 83.84 11-NOV-07:30
December 2263.36 01-DEC-00:10 1867.32 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 92.18 26-DEC-07:00
                           
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00        
Minimum of Months 2263.36   1867.32   0.00 0.00 0.00 0.00 0.00 0.00   44.15  
Maximum of Months 2263.36   1867.32   0.00 0.00 0.00 0.00 0.00 30.26   107.25  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_1_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 177.88 01-JAN-19:10 237.06 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 85.18 15-JAN-08:00
February 180.00 01-FEB-00:10 177.88 01-FEB-20:10 237.06 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 89.28 19-FEB-06:00
March 180.00 01-MAR-00:10 177.88 01-MAR-20:10 237.06 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 72.67 01-MAR-07:00
April 180.00 01-APR-00:10 177.88 01-APR-18:10 237.06 01-APR-07:10 0.00 0.00 0.00 0.00 17.84 27-APR-15:50 64.42 19-APR-05:00
May 180.00 01-MAY-00:10 177.88 01-MAY-19:10 237.06 01-MAY-06:10 0.00 0.00 0.00 0.00 11.40 05-MAY-16:00 54.55 11-MAY-03:00
June 180.00 01-JUN-00:10 177.88 01-JUN-19:10 237.06 01-JUN-06:10 0.00 0.00 0.00 0.00 16.46 28-JUN-17:00 41.17 15-JUN-04:00
July 180.00 01-JUL-00:10 177.88 01-JUL-18:10 237.06 01-JUL-07:10 0.00 0.00 0.00 0.00 26.89 24-JUL-15:10 32.15 07-JUL-05:00
August 180.00 01-AUG-00:10 177.88 01-AUG-19:10 237.06 01-AUG-06:10 0.00 0.00 0.00 0.00 30.96 10-AUG-17:00 35.98 01-AUG-08:00
September 180.00 01-SEP-00:10 177.88 01-SEP-19:10 237.06 01-SEP-06:10 0.00 0.00 0.00 0.00 11.42 14-SEP-17:00 45.07 27-SEP-05:00
October 180.00 01-OCT-00:10 177.88 01-OCT-18:10 237.06 01-OCT-07:10 0.00 0.00 0.00 0.00 1.16 04-OCT-15:10 50.39 13-OCT-05:00
November 180.00 01-NOV-00:10 177.88 01-NOV-19:10 237.06 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 69.91 11-NOV-07:30
December 180.00 01-DEC-00:10 177.88 01-DEC-20:10 237.06 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 76.81 26-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   177.88   237.06   0.00 0.00 0.00 0.00 0.00   32.15  
Maximum of Months 180.00   177.88   237.06   0.00 0.00 0.00 0.00 30.96   89.28  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_2_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 177.86 01-JAN-19:10 237.03 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 85.18 15-JAN-08:00
February 180.00 01-FEB-00:10 177.86 01-FEB-20:10 237.03 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 89.27 19-FEB-06:00
March 180.00 01-MAR-00:10 177.86 01-MAR-20:10 237.03 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 72.67 01-MAR-07:00
April 180.00 01-APR-00:10 177.86 01-APR-18:10 237.03 01-APR-07:10 0.00 0.00 0.00 0.00 17.84 27-APR-15:10 64.42 19-APR-05:00
May 180.00 01-MAY-00:10 177.86 01-MAY-19:10 237.03 01-MAY-06:10 0.00 0.00 0.00 0.00 11.40 05-MAY-16:00 54.54 11-MAY-03:10
June 180.00 01-JUN-00:10 177.86 01-JUN-19:10 237.03 01-JUN-06:10 0.00 0.00 0.00 0.00 16.46 28-JUN-17:00 41.16 15-JUN-04:00
July 180.00 01-JUL-00:10 177.86 01-JUL-18:10 237.03 01-JUL-07:10 0.00 0.00 0.00 0.00 26.88 24-JUL-15:10 40.48 11-JUL-19:55
August 180.00 01-AUG-00:10 177.86 01-AUG-19:10 237.03 01-AUG-06:10 0.00 0.00 0.00 0.00 30.96 10-AUG-17:00 36.19 01-AUG-08:00
September 180.00 01-SEP-00:10 177.86 01-SEP-19:10 237.03 01-SEP-06:10 0.00 0.00 0.00 0.00 11.42 14-SEP-17:00 45.06 27-SEP-05:00
October 180.00 01-OCT-00:10 177.86 01-OCT-18:10 237.03 01-OCT-07:10 0.00 0.00 0.00 0.00 1.16 04-OCT-15:10 50.38 13-OCT-05:00
November 180.00 01-NOV-00:10 177.86 01-NOV-19:10 237.03 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 69.91 11-NOV-07:10
December 180.00 01-DEC-00:10 177.86 01-DEC-20:10 237.03 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 76.80 26-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   177.86   237.03   0.00 0.00 0.00 0.00 0.00   36.19  
Maximum of Months 180.00   177.86   237.03   0.00 0.00 0.00 0.00 30.96   89.27  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 111.82 01-JAN-19:10 232.26 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 43.58 15-JAN-08:00
February 180.00 01-FEB-00:10 111.82 01-FEB-20:10 232.26 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 45.68 19-FEB-06:00
March 180.00 01-MAR-00:10 111.82 01-MAR-20:10 232.26 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 37.18 01-MAR-07:00
April 180.00 01-APR-00:10 111.82 01-APR-18:10 232.26 01-APR-07:10 0.00 0.00 0.00 0.00 9.13 27-APR-15:10 32.96 19-APR-05:00
May 180.00 01-MAY-00:10 111.82 01-MAY-19:10 232.26 01-MAY-06:10 0.00 0.00 0.00 0.00 5.83 05-MAY-16:00 27.91 11-MAY-03:10
June 180.00 01-JUN-00:10 111.82 01-JUN-19:10 232.26 01-JUN-06:10 0.00 0.00 0.00 0.00 8.42 28-JUN-17:00 21.06 15-JUN-04:00
July 180.00 01-JUL-00:10 111.82 01-JUL-18:10 232.26 01-JUL-07:10 0.00 0.00 0.00 0.00 13.76 24-JUL-15:10 16.82 04-JUL-07:20
August 180.00 01-AUG-00:10 111.82 01-AUG-19:10 232.26 01-AUG-06:10 0.00 0.00 0.00 0.00 15.84 10-AUG-17:00 18.54 01-AUG-08:00
September 180.00 01-SEP-00:10 111.82 01-SEP-19:10 232.26 01-SEP-06:10 0.00 0.00 0.00 0.00 5.84 14-SEP-17:00 23.06 27-SEP-05:00
October 180.00 01-OCT-00:10 111.82 01-OCT-18:10 232.26 01-OCT-07:10 0.00 0.00 0.00 0.00 0.34 04-OCT-15:10 25.78 13-OCT-05:00
November 180.00 01-NOV-00:10 111.82 01-NOV-19:10 232.26 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 35.77 11-NOV-07:10
December 180.00 01-DEC-00:10 111.82 01-DEC-20:10 232.26 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 39.30 26-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   111.82   232.26   0.00 0.00 0.00 0.00 0.00   16.82  
Maximum of Months 180.00   111.82   232.26   0.00 0.00 0.00 0.00 15.84   45.68  



Table of Contents

Report: PeakSpaceGainsMonthly

For: BANQUET_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 26988.77 02-JAN-00:10 2988.03 02-JAN-20:10 6747.90 01-JAN-07:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 231.89 15-JAN-08:00
February 26988.77 01-FEB-00:10 2988.03 01-FEB-20:10 6747.90 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 239.08 19-FEB-06:10
March 26988.77 01-MAR-00:10 2988.03 01-MAR-20:10 6747.90 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 200.92 01-MAR-07:00
April 26988.77 01-APR-00:10 2988.03 03-APR-19:10 6747.90 01-APR-06:10 0.00 0.00 0.00 0.00 24.31 01-APR-16:00 180.55 19-APR-05:00
May 26988.77 01-MAY-00:10 2988.03 01-MAY-19:10 6747.90 01-MAY-06:10 0.00 0.00 0.00 0.00 6.61 05-MAY-16:00 156.05 11-MAY-03:10
June 26988.77 01-JUN-00:10 2988.03 01-JUN-19:40 6747.90 01-JUN-06:10 0.00 0.00 0.00 0.00 19.04 28-JUN-17:00 122.97 15-JUN-03:10
July 26988.77 01-JUL-00:10 2988.03 10-JUL-19:30 6747.90 01-JUL-06:10 0.00 0.00 0.00 0.00 46.83 24-JUL-15:00 100.89 07-JUL-05:00
August 26988.77 01-AUG-00:10 2988.03 01-AUG-19:19 6747.90 01-AUG-06:10 0.00 0.00 0.00 0.00 54.99 10-AUG-17:00 101.72 21-AUG-05:00
September 26988.77 01-SEP-00:10 2988.03 01-SEP-19:10 6747.90 01-SEP-06:10 0.00 0.00 0.00 0.00 6.62 14-SEP-17:00 132.68 27-SEP-05:00
October 26988.77 01-OCT-23:10 2988.03 02-OCT-19:10 6747.90 01-OCT-06:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 145.75 13-OCT-05:00
November 26988.77 01-NOV-00:10 2988.03 01-NOV-19:10 6747.90 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 193.92 11-NOV-07:10
December 26988.77 01-DEC-00:10 2988.03 01-DEC-20:10 6747.90 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 211.16 26-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 26988.77   2988.03   6747.90   0.00 0.00 0.00 0.00 0.00   100.89  
Maximum of Months 26988.77   2988.03   6747.90   0.00 0.00 0.00 0.00 54.99   239.08  



Table of Contents

Report: PeakSpaceGainsMonthly

For: DINING_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 26988.77 02-JAN-00:10 2988.03 02-JAN-20:10 6747.90 01-JAN-07:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 231.89 15-JAN-08:00
February 26988.77 01-FEB-00:10 2988.03 01-FEB-20:10 6747.90 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 240.50 19-FEB-06:10
March 26988.77 01-MAR-00:10 2988.03 01-MAR-20:10 6747.90 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 200.92 01-MAR-07:00
April 26988.77 01-APR-00:10 2988.03 03-APR-19:10 6747.90 01-APR-06:10 0.00 0.00 0.00 0.00 22.56 27-APR-16:00 180.55 19-APR-05:00
May 26988.77 01-MAY-00:10 2988.03 01-MAY-19:10 6747.90 01-MAY-06:10 0.00 0.00 0.00 0.00 6.61 05-MAY-16:00 156.05 11-MAY-03:10
June 26988.77 01-JUN-00:10 2988.03 01-JUN-19:40 6747.90 01-JUN-06:10 0.00 0.00 0.00 0.00 19.04 28-JUN-17:00 122.97 15-JUN-03:10
July 26988.77 01-JUL-00:10 2988.03 10-JUL-19:30 6747.90 01-JUL-06:10 0.00 0.00 0.00 0.00 46.83 24-JUL-15:00 100.89 07-JUL-05:00
August 26988.77 01-AUG-00:10 2988.03 01-AUG-19:19 6747.90 01-AUG-06:10 0.00 0.00 0.00 0.00 54.99 10-AUG-17:00 101.72 21-AUG-05:00
September 26988.77 01-SEP-00:10 2988.03 01-SEP-19:10 6747.90 01-SEP-06:10 0.00 0.00 0.00 0.00 6.62 14-SEP-17:00 132.68 27-SEP-05:00
October 26988.77 01-OCT-23:10 2988.03 02-OCT-19:10 6747.90 01-OCT-06:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 145.75 13-OCT-05:00
November 26988.77 01-NOV-00:10 2988.03 01-NOV-19:10 6747.90 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 193.92 11-NOV-07:10
December 26988.77 01-DEC-00:10 2988.03 01-DEC-20:10 6747.90 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 211.16 26-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 26988.77   2988.03   6747.90   0.00 0.00 0.00 0.00 0.00   100.89  
Maximum of Months 26988.77   2988.03   6747.90   0.00 0.00 0.00 0.00 54.99   240.50  



Table of Contents

Report: PeakSpaceGainsMonthly

For: KITCHEN_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2401.70 02-JAN-00:10 1060.81 02-JAN-20:10 14912.86 01-JAN-07:10 22492.83 01-JAN-16:10 0.00 0.00 0.00 0.00 01-JAN-00:10 207.55 15-JAN-08:00
February 2401.70 01-FEB-00:10 1060.81 01-FEB-20:10 14912.86 01-FEB-07:10 22492.83 01-FEB-16:10 0.00 0.00 0.00 0.00 01-FEB-00:03 215.09 19-FEB-06:10
March 2401.70 01-MAR-00:10 1060.81 01-MAR-20:10 14912.86 01-MAR-07:10 22492.83 01-MAR-16:10 0.00 0.00 0.00 0.00 01-MAR-00:03 179.83 01-MAR-07:00
April 2401.70 01-APR-00:10 1060.81 03-APR-19:10 14912.86 01-APR-06:10 22492.83 01-APR-15:09 0.00 0.00 0.00 20.28 27-APR-15:40 161.02 19-APR-05:10
May 2401.70 01-MAY-00:10 1060.81 01-MAY-19:10 14912.86 01-MAY-06:10 22492.83 01-MAY-15:09 0.00 0.00 0.00 5.99 05-MAY-16:00 135.58 11-MAY-03:30
June 2401.70 01-JUN-00:10 1060.81 01-JUN-19:10 14912.86 01-JUN-06:10 22492.83 01-JUN-15:09 0.00 0.00 0.00 17.12 28-JUN-17:00 106.95 15-JUN-03:30
July 2401.70 01-JUL-00:10 1060.81 03-JUL-19:10 14912.86 01-JUL-06:10 22492.83 01-JUL-15:09 0.00 0.00 0.00 41.98 24-JUL-15:00 90.32 07-JUL-05:00
August 2401.70 01-AUG-00:10 1060.81 01-AUG-19:10 14912.86 01-AUG-06:10 22492.83 01-AUG-15:09 0.00 0.00 0.00 49.30 10-AUG-17:00 91.06 21-AUG-05:00
September 2401.70 01-SEP-00:10 1060.81 01-SEP-19:10 14912.86 01-SEP-06:10 22492.83 01-SEP-15:09 0.00 0.00 0.00 6.01 14-SEP-17:00 117.43 27-SEP-05:10
October 2401.70 01-OCT-23:10 1060.81 02-OCT-19:10 14912.86 01-OCT-06:10 22492.83 01-OCT-15:09 0.00 0.00 0.00 0.00 01-OCT-00:10 130.48 13-OCT-05:00
November 2401.70 01-NOV-00:10 1060.81 01-NOV-19:10 14912.86 01-NOV-06:10 22492.83 01-NOV-15:09 0.00 0.00 0.00 0.00 01-NOV-00:05 173.58 11-NOV-07:10
December 2401.70 01-DEC-00:10 1060.81 01-DEC-20:10 14912.86 01-DEC-07:10 22492.83 01-DEC-16:10 0.00 0.00 0.00 0.00 01-DEC-00:03 189.01 26-DEC-07:00
                               
Annual Sum or Average                 0.00 0.00 0.00        
Minimum of Months 2401.70   1060.81   14912.86   22492.83   0.00 0.00 0.00 0.00   90.32  
Maximum of Months 2401.70   1060.81   14912.86   22492.83   0.00 0.00 0.00 49.30   215.09  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORRIDOR_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2395.44 02-JAN-00:10 1976.27 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 181.46 15-JAN-08:00
February 2395.44 01-FEB-00:10 1976.27 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 190.23 19-FEB-06:00
March 2395.44 01-MAR-00:10 1976.27 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 154.70 01-MAR-07:00
April 2395.44 01-APR-00:10 1976.27 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 30.19 01-APR-16:00 137.06 19-APR-05:00
May 2395.44 01-MAY-00:10 1976.27 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 11.72 05-MAY-16:00 118.89 11-MAY-03:00
June 2395.44 01-JUN-00:10 1976.27 01-JUN-19:10 0.00 0.00 0.00 0.00 0.00 19.73 28-JUN-17:00 91.09 15-JUN-03:00
July 2395.44 01-JUL-00:10 1976.27 03-JUL-19:10 0.00 0.00 0.00 0.00 0.00 41.02 24-JUL-15:00 77.45 19-JUL-05:00
August 2395.44 01-AUG-00:10 1976.27 01-AUG-19:10 0.00 0.00 0.00 0.00 0.00 48.16 10-AUG-17:00 78.79 01-AUG-06:00
September 2395.44 01-SEP-00:10 1976.27 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 11.16 22-SEP-16:00 96.47 27-SEP-04:03
October 2395.44 01-OCT-23:10 1976.27 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 108.66 13-OCT-05:00
November 2395.44 01-NOV-00:10 1976.27 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 148.80 11-NOV-08:00
December 2395.44 01-DEC-00:10 1976.27 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 163.55 26-DEC-07:00
                           
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00        
Minimum of Months 2395.44   1976.27   0.00 0.00 0.00 0.00 0.00 0.00   77.45  
Maximum of Months 2395.44   1976.27   0.00 0.00 0.00 0.00 0.00 48.16   190.23  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BASEMENT

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 14368.56 11-JAN-21:00 8945.92 13190.31 9632.53 0.00 0.00 0.00 0.00 0.00 0.00
February 14221.27 01-FEB-21:00 8945.92 13190.31 9632.53 0.00 0.00 0.00 0.00 0.00 0.00
March 14304.51 25-MAR-10:33 11501.89 10992.10 10646.48 0.00 0.00 0.00 0.00 0.00 0.00
April 14725.32 27-APR-10:33 7667.93 10992.10 10646.48 0.00 0.00 0.00 0.00 0.00 0.00
May 15190.50 14-MAY-10:33 11501.89 13190.31 12167.41 0.00 0.00 0.00 0.00 0.00 0.00
June 15590.92 25-JUN-10:33 11501.89 13190.31 12167.41 0.00 0.00 0.00 0.00 0.00 0.00
July 16122.79 30-JUL-10:33 11501.89 13190.31 12167.41 0.00 0.00 0.00 0.00 0.00 0.00
August 16354.47 13-AUG-10:33 11501.89 13190.31 12167.41 0.00 0.00 0.00 0.00 0.00 0.00
September 17575.13 15-SEP-21:00 10223.90 11724.66 9125.55 0.00 0.00 0.00 0.00 0.00 0.00
October 18924.04 06-OCT-21:00 10223.90 11724.66 9125.55 0.00 0.00 0.00 0.00 0.00 0.00
November 18782.45 08-NOV-22:00 10223.90 11724.66 9125.55 0.00 0.00 0.00 0.00 0.00 0.00
December 17689.75 01-DEC-22:00 10223.90 11724.66 9125.55 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 14221.27   7667.93 10992.10 9125.55 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 18924.04   11501.89 13190.31 12167.41 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: RETAIL_1_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2277.79 20-JAN-11:50 519.79 332.00 505.18 0.00 0.00 0.00 0.00 0.00 95.76
February 2779.69 08-FEB-13:30 259.90 166.00 252.59 0.00 0.00 0.00 0.00 0.00 97.87
March 3427.10 02-MAR-13:20 259.90 166.00 252.59 0.00 0.00 0.00 0.00 0.00 62.05
April 3203.26 27-APR-13:05 519.79 332.00 505.18 0.00 0.00 0.00 0.00 10.82 0.00
May 3094.00 04-MAY-13:20 519.79 332.00 505.18 0.00 0.00 0.00 0.00 0.00 6.49
June 2568.56 28-JUN-10:33 779.69 497.99 757.77 0.00 0.00 0.00 0.00 0.00 4.02
July 3026.55 31-JUL-13:20 259.90 166.00 252.59 0.00 0.00 0.00 0.00 18.42 0.00
August 3845.17 24-AUG-13:10 519.79 332.00 505.18 0.00 0.00 0.00 0.00 25.24 0.00
September 3980.43 14-SEP-13:15 519.79 332.00 505.18 0.00 0.00 0.00 0.00 0.00 4.38
October 4006.98 04-OCT-12:50 259.90 166.00 252.59 0.00 0.00 0.00 0.00 0.00 17.84
November 3260.01 04-NOV-13:30 779.69 332.00 505.18 0.00 0.00 0.00 0.00 0.00 16.65
December 2544.74 05-DEC-12:20 259.90 166.00 252.59 0.00 0.00 0.00 0.00 0.00 74.89
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2277.79   259.90 166.00 252.59 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4006.98   779.69 497.99 757.77 0.00 0.00 0.00 0.00 25.24 97.87



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: RETAIL_2_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1141.51 11-JAN-21:00 1053.36 692.02 793.93 0.00 0.00 0.00 0.00 0.00 24.27
February 1252.97 27-FEB-21:00 1053.36 692.02 793.93 0.00 0.00 0.00 0.00 0.00 23.34
March 1279.22 02-MAR-21:00 1053.36 692.02 793.93 0.00 0.00 0.00 0.00 0.00 35.80
April 1621.11 27-APR-21:00 1203.84 615.12 752.15 0.00 0.00 0.00 0.00 0.00 13.92
May 1594.67 04-MAY-21:00 1203.84 615.12 752.15 0.00 0.00 0.00 0.00 0.00 12.75
June 1670.87 28-JUN-21:00 1203.84 615.12 752.15 0.00 0.00 0.00 0.00 0.00 15.08
July 1860.11 31-JUL-21:00 1203.84 615.12 752.15 0.00 0.00 0.00 0.00 0.00 4.68
August 2008.44 10-AUG-20:55 4815.36 2460.50 3008.58 0.00 0.00 0.00 0.00 0.00 2.01
September 1806.55 14-SEP-21:00 1203.84 615.12 752.15 0.00 0.00 0.00 0.00 0.00 11.70
October 1572.60 04-OCT-21:00 1203.84 615.12 752.15 0.00 0.00 0.00 0.00 0.00 20.86
November 1268.63 04-NOV-18:10 6320.16 3767.64 4680.02 0.00 0.00 0.00 0.00 0.00 16.48
December 1190.31 05-DEC-21:00 1053.36 692.02 793.93 0.00 0.00 0.00 0.00 0.00 36.97
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1141.51   1053.36 615.12 752.15 0.00 0.00 0.00 0.00 0.00 2.01
Maximum of Months 2008.44   6320.16 3767.64 4680.02 0.00 0.00 0.00 0.00 0.00 36.97



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: MECH_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 747.74 11-JAN-21:00 222.77 684.18 839.45 0.00 0.00 0.00 0.00 0.00 52.47
February 827.99 27-FEB-19:10 1113.84 3040.79 3976.33 0.00 0.00 0.00 0.00 0.00 29.87
March 837.55 18-MAR-10:33 286.42 570.15 927.81 0.00 0.00 0.00 0.00 0.00 50.19
April 988.56 27-APR-18:10 1336.61 3648.94 4771.59 0.00 0.00 0.00 0.00 13.77 0.00
May 1047.32 06-MAY-10:33 286.42 570.15 927.81 0.00 0.00 0.00 0.00 0.00 8.59
June 1068.69 28-JUN-10:33 190.94 570.15 927.81 0.00 0.00 0.00 0.00 0.00 6.28
July 1173.92 24-JUL-21:00 254.59 608.16 795.27 0.00 0.00 0.00 0.00 0.00 5.73
August 1298.48 10-AUG-20:57 1018.37 2432.63 3181.06 0.00 0.00 0.00 0.00 0.00 4.75
September 1077.25 14-SEP-10:33 190.94 570.15 927.81 0.00 0.00 0.00 0.00 0.00 17.00
October 972.37 04-OCT-10:33 190.94 570.15 927.81 0.00 0.00 0.00 0.00 0.00 19.26
November 887.41 04-NOV-10:33 286.42 570.15 927.81 0.00 0.00 0.00 0.00 0.00 22.03
December 762.28 03-DEC-11:33 286.42 684.18 1060.35 0.00 0.00 0.00 0.00 0.00 48.80
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 747.74   190.94 570.15 795.27 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1298.48   1336.61 3648.94 4771.59 0.00 0.00 0.00 0.00 13.77 52.47



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: STORAGE_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 419.11 11-JAN-19:10 514.08 671.56 688.24 0.00 0.00 0.00 0.00 0.00 24.77
February 471.39 28-FEB-11:33 146.88 209.86 267.65 0.00 0.00 0.00 0.00 0.00 28.45
March 481.99 18-MAR-10:33 220.32 209.86 267.65 0.00 0.00 0.00 0.00 0.00 28.25
April 573.39 29-APR-10:33 220.32 209.86 267.65 0.00 0.00 0.00 0.00 0.00 20.01
May 613.64 06-MAY-10:33 220.32 209.86 267.65 0.00 0.00 0.00 0.00 0.00 4.57
June 623.03 28-JUN-10:33 146.88 209.86 267.65 0.00 0.00 0.00 0.00 0.00 3.10
July 657.57 24-JUL-18:10 1028.16 1343.12 1376.47 0.00 0.00 0.00 0.00 14.43 0.00
August 665.62 10-AUG-18:10 1028.16 1343.12 1376.47 0.00 0.00 0.00 0.00 18.76 0.00
September 626.42 14-SEP-10:33 146.88 209.86 267.65 0.00 0.00 0.00 0.00 0.00 9.21
October 564.00 04-OCT-10:33 146.88 209.86 267.65 0.00 0.00 0.00 0.00 0.00 10.51
November 512.21 04-NOV-10:33 220.32 209.86 267.65 0.00 0.00 0.00 0.00 0.00 12.04
December 441.51 03-DEC-11:33 220.32 251.83 305.88 0.00 0.00 0.00 0.00 0.00 27.64
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 419.11   146.88 209.86 267.65 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 665.62   1028.16 1343.12 1376.47 0.00 0.00 0.00 0.00 18.76 28.45



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: LAUNDRY_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 36766.16 11-JAN-21:00 705.60 325.08 4572.80 39726.58 0.00 0.00 0.00 0.00 87.32
February 37231.64 27-FEB-21:00 705.60 325.08 4572.80 39726.58 0.00 0.00 0.00 0.00 79.94
March 37364.02 14-MAR-20:00 705.60 325.08 4572.80 39726.58 0.00 0.00 0.00 0.00 64.47
April 38175.36 27-APR-20:00 705.60 325.08 4572.80 39726.58 0.00 0.00 0.00 0.00 30.16
May 38115.47 15-MAY-20:00 705.60 325.08 4572.80 39726.58 0.00 0.00 0.00 0.00 45.00
June 38322.53 28-JUN-19:55 1411.20 650.17 9145.60 79453.15 0.00 0.00 0.00 0.00 15.08
July 38591.13 24-JUL-20:00 705.60 325.08 4572.80 39726.58 0.00 0.00 0.00 0.00 0.67
August 38660.34 10-AUG-20:00 705.60 325.08 4572.80 39726.58 0.00 0.00 0.00 10.23 0.00
September 38250.48 14-SEP-20:00 705.60 325.08 4572.80 39726.58 0.00 0.00 0.00 0.00 33.72
October 37858.86 04-OCT-20:00 705.60 325.08 4572.80 39726.58 0.00 0.00 0.00 0.00 44.83
November 37111.38 02-NOV-20:00 705.60 325.08 4572.80 39726.58 0.00 0.00 0.00 0.00 75.95
December 36691.63 05-DEC-21:00 705.60 325.08 4572.80 39726.58 0.00 0.00 0.00 0.00 126.07
                       
Annual Sum or Average             0.00 0.00 0.00    
Minimum of Months 36691.63   705.60 325.08 4572.80 39726.58 0.00 0.00 0.00 0.00 0.00
Maximum of Months 38660.34   1411.20 650.17 9145.60 79453.15 0.00 0.00 0.00 10.23 126.07



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CAFE_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 9465.09 08-JAN-11:35 10245.60 249.56 812.86 0.00 0.00 0.00 0.00 0.00 272.98
February 10937.42 08-FEB-13:30 3415.20 103.98 355.63 0.00 0.00 0.00 0.00 0.00 216.35
March 12724.48 02-MAR-13:20 3415.20 103.98 355.63 0.00 0.00 0.00 0.00 0.00 137.15
April 11668.75 27-APR-14:10 5122.80 103.98 355.63 0.00 0.00 0.00 0.00 26.00 0.00
May 11381.55 04-MAY-14:10 5122.80 103.98 355.63 0.00 0.00 0.00 0.00 0.00 0.22
June 10668.45 10-JUN-10:33 15368.40 311.95 1066.88 0.00 0.00 0.00 0.00 0.00 27.90
July 11382.64 30-JUL-10:33 15368.40 374.34 1219.29 0.00 0.00 0.00 0.00 2.23 0.00
August 13252.01 24-AUG-15:03 51228.00 623.89 2133.76 0.00 0.00 0.00 0.00 63.26 0.00
September 14068.15 23-SEP-13:15 10245.60 207.96 711.25 0.00 0.00 0.00 0.00 0.00 16.56
October 14123.84 04-OCT-12:50 3415.20 103.98 355.63 0.00 0.00 0.00 0.00 0.00 39.44
November 12716.09 04-NOV-13:30 10245.60 207.96 711.25 0.00 0.00 0.00 0.00 0.00 36.80
December 10447.00 02-DEC-11:33 15368.40 311.95 1066.88 0.00 0.00 0.00 0.00 0.00 141.86
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 9465.09   3415.20 103.98 355.63 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 14123.84   51228.00 623.89 2133.76 0.00 0.00 0.00 0.00 63.26 272.98



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: LOBBY_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 26379.15 11-JAN-22:00 40553.76 8448.71 9501.36 0.00 0.00 0.00 0.00 0.00 418.63
February 28454.18 27-FEB-21:00 35484.54 9504.80 10029.21 0.00 0.00 0.00 0.00 0.00 389.05
March 29204.60 14-MAR-21:20 45622.98 6336.53 7389.94 0.00 0.00 0.00 0.00 0.00 390.82
April 34277.33 27-APR-21:10 45622.98 6336.53 7389.94 0.00 0.00 0.00 0.00 0.00 243.72
May 34319.19 04-MAY-21:52 456229.80 63365.33 73899.43 0.00 0.00 0.00 0.00 0.00 170.85
June 35106.36 28-JUN-21:52 410606.82 57028.80 66509.49 0.00 0.00 0.00 0.00 0.00 191.63
July 37863.37 24-JUL-21:10 45622.98 6336.53 7389.94 0.00 0.00 0.00 0.00 0.00 51.80
August 39345.61 10-AUG-21:05 91245.96 12673.07 14779.89 0.00 0.00 0.00 0.00 0.00 35.58
September 37737.92 14-SEP-21:10 45622.98 6336.53 7389.94 0.00 0.00 0.00 0.00 0.00 197.64
October 35229.85 04-OCT-21:10 45622.98 6336.53 7389.94 0.00 0.00 0.00 0.00 0.00 328.47
November 29161.79 04-NOV-10:33 45622.98 6811.77 11084.92 0.00 0.00 0.00 0.00 0.00 183.13
December 27573.83 03-DEC-11:33 45622.98 8174.13 12668.47 0.00 0.00 0.00 0.00 0.00 392.07
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 26379.15   35484.54 6336.53 7389.94 0.00 0.00 0.00 0.00 0.00 35.58
Maximum of Months 39345.61   456229.80 63365.33 73899.43 0.00 0.00 0.00 0.00 0.00 418.63



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_1_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2782.23 05-JAN-16:01 680.40 348.65 350.32 0.00 0.00 0.00 0.00 0.00 50.82
February 3739.23 12-FEB-16:01 378.00 410.91 387.20 0.00 0.00 0.00 0.00 0.00 50.06
March 3783.66 25-MAR-15:01 378.00 410.91 387.20 0.00 0.00 0.00 0.00 0.00 34.04
April 3769.96 13-APR-18:01 970.20 1108.21 848.14 0.00 0.00 0.00 0.00 0.00 18.03
May 3905.88 14-MAY-18:01 819.00 1245.18 848.14 0.00 0.00 0.00 0.00 0.00 2.31
June 3398.63 23-JUN-15:01 680.40 348.65 350.32 0.00 0.00 0.00 0.00 0.00 17.17
July 3403.01 25-JUL-08:61 252.00 547.88 792.83 0.00 0.00 0.00 0.00 0.00 22.30
August 3457.93 18-AUG-15:01 680.40 348.65 350.32 0.00 0.00 0.00 0.00 0.00 5.78
September 3421.22 22-SEP-18:01 970.20 1108.21 848.14 0.00 0.00 0.00 0.00 0.00 6.20
October 3737.16 03-OCT-18:01 970.20 1108.21 848.14 0.00 0.00 0.00 0.00 0.00 19.41
November 3240.64 04-NOV-15:01 378.00 410.91 387.20 0.00 0.00 0.00 0.00 0.00 5.30
December 3143.59 10-DEC-16:01 378.00 410.91 387.20 0.00 0.00 0.00 0.00 0.00 38.48
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2782.23   252.00 348.65 350.32 0.00 0.00 0.00 0.00 0.00 2.31
Maximum of Months 3905.88   970.20 1245.18 848.14 0.00 0.00 0.00 0.00 0.00 50.82



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_2_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 442.14 20-JAN-16:03 583.20 298.81 300.24 0.00 0.00 0.00 0.00 0.00 51.30
February 3116.07 12-FEB-16:01 378.00 410.86 387.15 0.00 0.00 0.00 0.00 0.00 46.80
March 3382.76 25-MAR-15:01 378.00 410.86 387.15 0.00 0.00 0.00 0.00 0.00 33.31
April 3893.21 25-APR-17:41 777.60 953.34 1011.33 0.00 0.00 0.00 0.00 0.00 32.61
May 3461.03 29-MAY-19:41 1170.00 1778.61 1632.88 0.00 0.00 0.00 0.00 0.00 36.18
June 3485.39 18-JUN-20:11 1386.00 1778.61 1817.24 0.00 0.00 0.00 0.00 0.00 32.42
July 3648.35 25-JUL-16:51 972.00 498.01 1264.17 0.00 0.00 0.00 0.00 1.04 0.00
August 3526.86 02-AUG-18:11 1386.00 1582.97 1211.49 0.00 0.00 0.00 0.00 0.00 30.65
September 3542.28 22-SEP-16:11 972.00 498.01 1264.17 0.00 0.00 0.00 0.00 0.00 1.65
October 3159.30 06-OCT-15:01 680.40 348.61 350.28 0.00 0.00 0.00 0.00 0.00 15.91
November 2923.63 04-NOV-15:01 378.00 410.86 387.15 0.00 0.00 0.00 0.00 0.00 5.04
December 1063.82 02-DEC-16:01 378.00 410.86 387.15 0.00 0.00 0.00 0.00 0.00 33.89
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 442.14   378.00 298.81 300.24 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3893.21   1386.00 1778.61 1817.24 0.00 0.00 0.00 0.00 1.04 51.30



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 129.71 08-JAN-15:15 0.00 73.78 67.08 0.00 0.00 0.00 0.00 0.00 18.26
February 475.70 08-FEB-13:40 0.00 31.30 30.96 0.00 0.00 0.00 0.00 0.00 18.19
March 605.89 02-MAR-13:00 0.00 31.30 30.96 0.00 0.00 0.00 0.00 0.00 12.77
April 550.05 27-APR-13:05 0.00 62.60 61.92 0.00 0.00 0.00 0.00 0.00 0.51
May 530.52 04-MAY-13:20 0.00 62.60 61.92 0.00 0.00 0.00 0.00 0.00 3.35
June 399.86 28-JUN-13:05 0.00 62.60 61.92 0.00 0.00 0.00 0.00 0.00 1.87
July 499.21 31-JUL-13:20 0.00 31.30 30.96 0.00 0.00 0.00 0.00 0.71 0.00
August 626.10 24-AUG-13:05 0.00 62.60 61.92 0.00 0.00 0.00 0.00 1.84 0.00
September 670.75 14-SEP-13:30 0.00 31.30 30.96 0.00 0.00 0.00 0.00 0.00 2.85
October 700.17 04-OCT-12:40 0.00 31.30 30.96 0.00 0.00 0.00 0.00 0.00 5.19
November 542.82 04-NOV-13:30 0.00 73.78 67.08 0.00 0.00 0.00 0.00 0.00 5.01
December 432.40 05-DEC-12:30 0.00 31.30 30.96 0.00 0.00 0.00 0.00 0.00 14.42
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 129.71   0.00 31.30 30.96 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 700.17   0.00 73.78 67.08 0.00 0.00 0.00 0.00 1.84 18.26



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 808.46 01-JAN-09:02 270.00 313.10 799.99 0.00 0.00 0.00 0.00 0.00 12.04
February 909.70 26-FEB-09:02 270.00 313.10 799.99 0.00 0.00 0.00 0.00 0.00 11.13
March 992.67 28-MAR-18:01 970.20 696.66 830.96 0.00 0.00 0.00 0.00 0.00 9.64
April 1029.71 01-APR-21:52 693.00 475.25 438.70 0.00 0.00 0.00 0.00 0.00 1.21
May 1093.96 14-MAY-21:51 1386.00 950.49 877.41 0.00 0.00 0.00 0.00 0.00 5.52
June 1010.03 22-JUN-21:51 1800.00 749.21 877.41 0.00 0.00 0.00 0.00 0.00 6.88
July 1017.51 25-JUL-15:02 583.20 187.86 294.19 0.00 0.00 0.00 0.00 0.11 0.00
August 1015.09 08-AUG-21:31 1620.00 674.29 789.67 0.00 0.00 0.00 0.00 0.52 0.00
September 1008.00 11-SEP-15:01 680.40 219.17 343.22 0.00 0.00 0.00 0.00 0.34 0.00
October 1016.02 02-OCT-18:01 970.20 696.66 830.96 0.00 0.00 0.00 0.00 0.00 6.91
November 901.27 05-NOV-08:62 324.00 375.72 959.99 0.00 0.00 0.00 0.00 0.00 8.30
December 941.01 03-DEC-09:02 216.00 250.48 639.99 0.00 0.00 0.00 0.00 0.00 11.87
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 808.46   216.00 187.86 294.19 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1093.96   1800.00 950.49 959.99 0.00 0.00 0.00 0.00 0.52 12.04



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_5_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 471.52 20-JAN-16:02 583.20 298.84 300.27 0.00 0.00 0.00 0.00 0.00 51.32
February 3222.62 12-FEB-16:01 378.00 410.91 387.20 0.00 0.00 0.00 0.00 0.00 47.77
March 3438.76 25-MAR-08:61 378.00 697.30 1143.15 0.00 0.00 0.00 0.00 0.00 57.72
April 3319.40 13-APR-18:01 970.20 1108.21 848.14 0.00 0.00 0.00 0.00 0.00 16.75
May 3491.51 14-MAY-18:01 819.00 1245.18 848.14 0.00 0.00 0.00 0.00 0.00 1.82
June 3120.84 18-JUN-08:62 324.00 597.68 979.84 0.00 0.00 0.00 0.00 0.00 31.24
July 3138.89 11-JUL-15:01 680.40 348.65 350.32 0.00 0.00 0.00 0.00 0.00 2.00
August 3191.38 25-AUG-08:61 252.00 547.88 792.83 0.00 0.00 0.00 0.00 0.00 8.65
September 3168.61 23-SEP-08:61 378.00 697.30 1143.15 0.00 0.00 0.00 0.00 0.00 26.14
October 3281.83 03-OCT-18:01 970.20 1108.21 848.14 0.00 0.00 0.00 0.00 0.00 17.89
November 3167.07 04-NOV-15:01 378.00 410.91 387.20 0.00 0.00 0.00 0.00 0.00 4.83
December 2377.31 02-DEC-09:02 270.00 498.07 816.54 0.00 0.00 0.00 0.00 0.00 40.36
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 471.52   252.00 298.84 300.27 0.00 0.00 0.00 0.00 0.00 1.82
Maximum of Months 3491.51   970.20 1245.18 1143.15 0.00 0.00 0.00 0.00 0.00 57.72



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_6_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 354.13 27-JAN-19:06 693.00 791.48 605.75 0.00 0.00 0.00 0.00 0.00 40.25
February 2509.90 27-FEB-16:01 680.40 348.61 350.28 0.00 0.00 0.00 0.00 0.00 6.68
March 3157.57 25-MAR-08:61 378.00 697.22 1143.02 0.00 0.00 0.00 0.00 0.00 57.74
April 3130.84 25-APR-18:01 970.20 1108.08 848.04 0.00 0.00 0.00 0.00 0.00 26.33
May 3387.43 06-MAY-08:51 540.00 996.02 1632.88 0.00 0.00 0.00 0.00 0.00 17.41
June 3205.99 10-JUN-08:51 540.00 996.02 1632.88 0.00 0.00 0.00 0.00 0.00 22.04
July 3662.15 24-JUL-08:32 216.00 469.55 679.49 0.00 0.00 0.00 0.00 0.00 11.12
August 3578.19 10-AUG-08:32 216.00 469.55 679.49 0.00 0.00 0.00 0.00 0.00 14.78
September 3324.97 13-SEP-08:51 360.00 782.59 1132.48 0.00 0.00 0.00 0.00 0.00 21.82
October 2803.02 07-OCT-08:61 378.00 697.22 1143.02 0.00 0.00 0.00 0.00 0.00 39.75
November 2465.33 04-NOV-15:01 378.00 410.86 387.15 0.00 0.00 0.00 0.00 0.00 2.53
December 812.59 02-DEC-09:02 270.00 498.01 816.44 0.00 0.00 0.00 0.00 0.00 39.95
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 354.13   216.00 348.61 350.28 0.00 0.00 0.00 0.00 0.00 2.53
Maximum of Months 3662.15   970.20 1108.08 1632.88 0.00 0.00 0.00 0.00 0.00 57.74



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORRIDOR_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1574.00 11-JAN-21:00 1760.39 1867.32 0.00 0.00 0.00 0.00 0.00 0.00 38.16
February 1788.66 27-FEB-19:10 8801.94 8299.19 0.00 0.00 0.00 0.00 0.00 0.00 21.25
March 1900.42 25-MAR-10:33 2263.36 1556.10 0.00 0.00 0.00 0.00 0.00 0.00 47.88
April 2241.77 27-APR-18:10 10562.33 9959.03 0.00 0.00 0.00 0.00 0.00 11.07 0.00
May 2340.16 06-MAY-10:33 2263.36 1556.10 0.00 0.00 0.00 0.00 0.00 0.00 5.57
June 2398.50 28-JUN-10:33 1508.90 1556.10 0.00 0.00 0.00 0.00 0.00 0.00 3.94
July 2532.57 24-JUL-18:10 10562.33 9959.03 0.00 0.00 0.00 0.00 0.00 19.44 0.00
August 2578.50 13-AUG-10:33 2263.36 1867.32 0.00 0.00 0.00 0.00 0.00 3.74 0.00
September 2480.27 14-SEP-10:33 1508.90 1556.10 0.00 0.00 0.00 0.00 0.00 0.00 13.10
October 2202.16 04-OCT-10:33 1508.90 1556.10 0.00 0.00 0.00 0.00 0.00 0.00 14.32
November 1910.63 04-NOV-10:33 2263.36 1556.10 0.00 0.00 0.00 0.00 0.00 0.00 15.01
December 1736.49 03-DEC-11:33 2263.36 1867.32 0.00 0.00 0.00 0.00 0.00 0.00 37.32
                       
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00    
Minimum of Months 1574.00   1508.90 1556.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2578.50   10562.33 9959.03 0.00 0.00 0.00 0.00 0.00 19.44 47.88



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_1_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2846.45 05-JAN-16:01 680.40 348.65 350.32 0.00 0.00 0.00 0.00 0.00 50.12
February 3880.23 12-FEB-16:01 378.00 410.91 387.20 0.00 0.00 0.00 0.00 0.00 50.14
March 3937.58 25-MAR-15:01 378.00 410.91 387.20 0.00 0.00 0.00 0.00 0.00 34.21
April 3924.50 13-APR-18:01 970.20 1108.21 848.14 0.00 0.00 0.00 0.00 0.00 18.21
May 4071.74 14-MAY-18:01 819.00 1245.18 848.14 0.00 0.00 0.00 0.00 0.00 2.54
June 3537.66 23-JUN-15:01 680.40 348.65 350.32 0.00 0.00 0.00 0.00 0.00 17.27
July 3436.55 24-JUL-08:61 252.00 547.88 792.83 0.00 0.00 0.00 0.00 0.00 1.09
August 3586.09 18-AUG-15:01 680.40 348.65 350.32 0.00 0.00 0.00 0.00 0.00 5.91
September 3549.10 22-SEP-18:01 970.20 1108.21 848.14 0.00 0.00 0.00 0.00 0.00 6.37
October 3919.09 04-OCT-18:01 970.20 1108.21 848.14 0.00 0.00 0.00 0.00 0.00 14.84
November 3356.65 04-NOV-18:01 819.00 1245.18 848.14 0.00 0.00 0.00 0.00 0.00 22.43
December 3220.79 10-DEC-16:01 378.00 410.91 387.20 0.00 0.00 0.00 0.00 0.00 38.82
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2846.45   252.00 348.65 350.32 0.00 0.00 0.00 0.00 0.00 1.09
Maximum of Months 4071.74   970.20 1245.18 848.14 0.00 0.00 0.00 0.00 0.00 50.14



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_2_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 432.48 20-JAN-16:05 583.20 298.81 300.24 0.00 0.00 0.00 0.00 0.00 51.51
February 3052.08 26-FEB-16:01 378.00 410.86 387.15 0.00 0.00 0.00 0.00 0.00 24.61
March 3471.91 25-MAR-15:01 378.00 410.86 387.15 0.00 0.00 0.00 0.00 0.00 33.21
April 4036.24 25-APR-17:41 777.60 953.34 1011.33 0.00 0.00 0.00 0.00 0.00 32.86
May 4031.89 21-MAY-17:41 777.60 1209.46 1011.33 0.00 0.00 0.00 0.00 0.00 29.40
June 3674.11 19-JUN-21:51 1800.00 1191.67 895.45 0.00 0.00 0.00 0.00 0.00 25.75
July 3788.39 19-JUL-21:51 1800.00 1191.67 895.45 0.00 0.00 0.00 0.00 0.00 25.61
August 3715.74 06-AUG-21:51 1386.00 1511.82 895.45 0.00 0.00 0.00 0.00 0.00 22.48
September 3656.96 22-SEP-16:11 972.00 498.01 1264.17 0.00 0.00 0.00 0.00 0.00 2.84
October 3267.18 07-OCT-15:01 378.00 410.86 387.15 0.00 0.00 0.00 0.00 0.00 13.95
November 3004.83 04-NOV-15:01 378.00 410.86 387.15 0.00 0.00 0.00 0.00 0.00 5.22
December 359.90 29-DEC-19:06 693.00 791.48 605.75 0.00 0.00 0.00 0.00 0.00 38.16
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 359.90   378.00 298.81 300.24 0.00 0.00 0.00 0.00 0.00 2.84
Maximum of Months 4036.24   1800.00 1511.82 1264.17 0.00 0.00 0.00 0.00 0.00 51.51



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1976.31 05-JAN-16:01 680.40 219.17 343.22 0.00 0.00 0.00 0.00 0.00 27.60
February 2126.45 26-FEB-16:01 378.00 258.31 379.35 0.00 0.00 0.00 0.00 0.00 12.97
March 2450.94 25-MAR-15:01 378.00 258.31 379.35 0.00 0.00 0.00 0.00 0.00 17.73
April 2360.62 13-APR-18:01 970.20 696.66 830.96 0.00 0.00 0.00 0.00 0.00 8.92
May 2438.96 14-MAY-18:01 819.00 782.76 830.96 0.00 0.00 0.00 0.00 0.00 0.87
June 2170.71 25-JUN-08:61 378.00 438.35 1119.99 0.00 0.00 0.00 0.00 0.00 10.53
July 2184.61 11-JUL-15:01 680.40 219.17 343.22 0.00 0.00 0.00 0.00 0.00 1.09
August 2211.69 18-AUG-15:01 680.40 219.17 343.22 0.00 0.00 0.00 0.00 0.00 2.98
September 2224.92 22-SEP-18:01 970.20 696.66 830.96 0.00 0.00 0.00 0.00 0.00 3.28
October 2412.00 04-OCT-18:01 970.20 696.66 830.96 0.00 0.00 0.00 0.00 0.00 7.62
November 2143.39 02-NOV-15:01 680.40 219.17 343.22 0.00 0.00 0.00 0.00 0.00 14.79
December 2123.83 10-DEC-16:01 378.00 258.31 379.35 0.00 0.00 0.00 0.00 0.00 21.06
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1976.31   378.00 219.17 343.22 0.00 0.00 0.00 0.00 0.00 0.87
Maximum of Months 2450.94   970.20 782.76 1119.99 0.00 0.00 0.00 0.00 0.00 27.60



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BANQUET_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 18024.62 11-JAN-23:00 26988.77 1992.02 6747.90 0.00 0.00 0.00 0.00 0.00 113.60
February 19050.19 27-FEB-23:00 26988.77 1992.02 6747.90 0.00 0.00 0.00 0.00 0.00 91.73
March 18939.41 10-MAR-23:00 26988.77 1992.02 6747.90 0.00 0.00 0.00 0.00 0.00 100.21
April 20763.65 27-APR-21:10 26988.77 1992.02 6747.90 0.00 0.00 0.00 0.00 0.00 55.44
May 21101.62 05-MAY-21:53 188921.38 13944.14 47235.32 0.00 0.00 0.00 0.00 0.00 47.56
June 21541.59 28-JUN-21:52 242898.91 17928.18 60731.12 0.00 0.00 0.00 0.00 0.00 43.77
July 22260.17 24-JUL-21:10 26988.77 1992.02 6747.90 0.00 0.00 0.00 0.00 0.00 12.36
August 22252.06 10-AUG-21:52 242898.91 17928.18 60731.12 0.00 0.00 0.00 0.00 0.00 11.81
September 20993.24 12-SEP-21:52 215910.14 15936.16 53983.22 0.00 0.00 0.00 0.00 0.00 43.56
October 19842.50 04-OCT-22:00 26988.77 1992.02 6747.90 0.00 0.00 0.00 0.00 0.00 60.20
November 18994.71 06-NOV-23:00 26988.77 1992.02 6747.90 0.00 0.00 0.00 0.00 0.00 63.44
December 17779.87 29-DEC-23:00 26988.77 1992.02 6747.90 0.00 0.00 0.00 0.00 0.00 119.21
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 17779.87   26988.77 1992.02 6747.90 0.00 0.00 0.00 0.00 0.00 11.81
Maximum of Months 22260.17   242898.91 17928.18 60731.12 0.00 0.00 0.00 0.00 0.00 119.21



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DINING_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 20072.51 11-JAN-22:10 26988.77 1992.02 6747.90 0.00 0.00 0.00 0.00 0.00 102.18
February 20862.22 27-FEB-23:00 26988.77 1992.02 6747.90 0.00 0.00 0.00 0.00 0.00 91.73
March 20842.23 08-MAR-23:00 26988.77 1992.02 6747.90 0.00 0.00 0.00 0.00 0.00 77.97
April 22275.99 27-APR-21:10 26988.77 1992.02 6747.90 0.00 0.00 0.00 0.00 0.00 55.44
May 22607.98 05-MAY-21:20 26988.77 1992.02 6747.90 0.00 0.00 0.00 0.00 0.00 41.94
June 22890.50 28-JUN-21:20 26988.77 1992.02 6747.90 0.00 0.00 0.00 0.00 0.00 52.01
July 23521.14 24-JUL-21:20 26988.77 1992.02 6747.90 0.00 0.00 0.00 0.00 0.00 15.12
August 23456.67 10-AUG-21:05 53977.54 3984.04 13495.81 0.00 0.00 0.00 0.00 0.00 8.72
September 22321.33 12-SEP-21:20 26988.77 1992.02 6747.90 0.00 0.00 0.00 0.00 0.00 37.99
October 21367.20 04-OCT-22:00 26988.77 1992.02 6747.90 0.00 0.00 0.00 0.00 0.00 60.20
November 20857.51 06-NOV-23:00 26988.77 1992.02 6747.90 0.00 0.00 0.00 0.00 0.00 63.44
December 19809.67 29-DEC-23:00 26988.77 1992.02 6747.90 0.00 0.00 0.00 0.00 0.00 119.22
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 19809.67   26988.77 1992.02 6747.90 0.00 0.00 0.00 0.00 0.00 8.72
Maximum of Months 23521.14   53977.54 3984.04 13495.81 0.00 0.00 0.00 0.00 0.00 119.22



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: KITCHEN_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 26602.78 30-JAN-11:33 1601.14 884.01 44738.57 56232.08 0.00 0.00 0.00 0.00 111.15
February 27755.78 27-FEB-11:45 1067.42 589.34 29825.71 37488.05 0.00 0.00 0.00 0.00 53.42
March 28894.50 14-MAR-10:45 1067.42 589.34 29825.71 37488.05 0.00 0.00 0.00 0.00 88.05
April 30227.01 27-APR-10:33 1601.14 884.01 44738.57 56232.08 0.00 0.00 0.00 0.00 24.93
May 30342.60 14-MAY-10:33 2401.70 1060.81 44738.57 56232.08 0.00 0.00 0.00 0.00 27.16
June 30623.93 10-JUN-10:33 2401.70 884.01 44738.57 56232.08 0.00 0.00 0.00 0.00 26.18
July 31021.13 24-JUL-10:37 1601.14 884.01 44738.57 56232.08 0.00 0.00 0.00 11.85 0.00
August 31091.67 13-AUG-10:40 2401.70 1060.81 44738.57 56232.08 0.00 0.00 0.00 0.02 0.00
September 30544.84 10-SEP-10:33 2401.70 1060.81 44738.57 56232.08 0.00 0.00 0.00 0.00 38.83
October 29366.68 07-OCT-10:33 2401.70 884.01 44738.57 56232.08 0.00 0.00 0.00 0.00 65.01
November 28888.15 04-NOV-10:45 1601.14 589.34 29825.71 37488.05 0.00 0.00 0.00 0.00 44.64
December 27114.85 03-DEC-11:50 800.57 353.60 14912.86 18744.03 0.00 0.00 0.00 0.00 86.52
                       
Annual Sum or Average             0.00 0.00 0.00    
Minimum of Months 26602.78   800.57 353.60 14912.86 18744.03 0.00 0.00 0.00 0.00 0.00
Maximum of Months 31091.67   2401.70 1060.81 44738.57 56232.08 0.00 0.00 0.00 11.85 111.15



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORRIDOR_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3346.98 30-JAN-11:33 1596.96 1646.89 0.00 0.00 0.00 0.00 0.00 0.00 88.50
February 3751.87 27-FEB-11:45 1064.64 1097.93 0.00 0.00 0.00 0.00 0.00 0.00 35.13
March 3974.38 02-MAR-11:33 1596.96 1646.89 0.00 0.00 0.00 0.00 0.00 0.00 83.67
April 4787.93 27-APR-18:10 11178.72 10540.09 0.00 0.00 0.00 0.00 0.00 15.32 0.00
May 4945.36 06-MAY-10:33 2395.44 1646.89 0.00 0.00 0.00 0.00 0.00 0.00 13.69
June 5090.45 28-JUN-18:10 11178.72 10540.09 0.00 0.00 0.00 0.00 0.00 11.49 0.00
July 5360.37 24-JUL-18:10 11178.72 10540.09 0.00 0.00 0.00 0.00 0.00 30.28 0.00
August 6159.39 10-AUG-15:03 7984.80 3293.78 0.00 0.00 0.00 0.00 0.00 39.42 0.00
September 5093.60 14-SEP-10:33 1596.96 1646.89 0.00 0.00 0.00 0.00 0.00 0.00 25.31
October 4562.15 04-OCT-10:33 1596.96 1646.89 0.00 0.00 0.00 0.00 0.00 0.00 27.82
November 4044.72 04-NOV-10:50 1596.96 1097.93 0.00 0.00 0.00 0.00 0.00 0.00 27.88
December 3610.45 03-DEC-11:33 2395.44 1976.27 0.00 0.00 0.00 0.00 0.00 0.00 68.32
                       
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00    
Minimum of Months 3346.98   1064.64 1097.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6159.39   11178.72 10540.09 0.00 0.00 0.00 0.00 0.00 39.42 88.50



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.377150E+12 225168.97 03-JAN-07:00 0.528473E+12 534395.30 25-JAN-18:00
February 0.338418E+12 224903.63 03-FEB-07:30 0.489094E+12 520464.05 04-FEB-18:49
March 0.373716E+12 225168.46 15-MAR-06:19 0.546422E+12 539983.04 22-MAR-17:40
April 0.368700E+12 290829.02 27-APR-18:10 0.517596E+12 514456.73 18-APR-17:10
May 0.387440E+12 253628.26 04-MAY-19:19 0.503159E+12 490823.92 17-MAY-19:10
June 0.387473E+12 290728.86 28-JUN-18:10 0.423889E+12 415098.34 13-JUN-21:10
July 0.426366E+12 317190.60 24-JUL-18:10 0.390639E+12 331885.62 04-JUL-20:00
August 0.445270E+12 335399.91 10-AUG-18:10 0.385314E+12 325648.33 31-AUG-17:30
September 0.387915E+12 260000.28 13-SEP-18:30 0.424512E+12 421489.01 27-SEP-20:00
October 0.375568E+12 235734.73 04-OCT-18:10 0.560542E+12 476974.58 31-OCT-18:10
November 0.361588E+12 226976.26 04-NOV-17:10 0.528066E+12 532987.96 21-NOV-18:40
December 0.377107E+12 224660.91 15-DEC-07:49 0.532137E+12 536781.22 14-DEC-18:30
             
Annual Sum or Average 0.460671E+13     0.582984E+13    
Minimum of Months 0.338418E+12 224660.91   0.385314E+12 325648.33  
Maximum of Months 0.445270E+12 335399.91   0.560542E+12 539983.04  



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [J] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [J] WATERSYSTEMS:ELECTRICITY [J] COGENERATION:ELECTRICITY []
January 0.673876E+11 0.210395E+11 0.140828E+12 0.691147E+11 0.401416E+11 0.226579E+10 0.00 0.638853E+09 0.00 0.00 0.224671E+11 0.804765E+10 0.00
February 0.605329E+11 0.173454E+11 0.127191E+12 0.624261E+11 0.362981E+11 0.326451E+10 0.00 0.296017E+10 0.00 0.00 0.164118E+11 0.727208E+10 0.00
March 0.666248E+11 0.169308E+11 0.140882E+12 0.691169E+11 0.405808E+11 0.527534E+10 0.00 0.715482E+10 0.00 0.00 0.138738E+11 0.804609E+10 0.00
April 0.639899E+11 0.141028E+11 0.136245E+12 0.668843E+11 0.404336E+11 0.658909E+10 0.00 0.188866E+11 0.00 0.00 0.870059E+10 0.779734E+10 0.00
May 0.657725E+11 0.125260E+11 0.140860E+12 0.691150E+11 0.431287E+11 0.719885E+10 0.00 0.304821E+11 0.00 0.00 0.503699E+10 0.804734E+10 0.00
June 0.632910E+11 0.110232E+11 0.136336E+12 0.668862E+11 0.429155E+11 0.687712E+10 0.00 0.445722E+11 0.00 0.00 0.266012E+10 0.778876E+10 0.00
July 0.655509E+11 0.118967E+11 0.140770E+12 0.691124E+11 0.457350E+11 0.703271E+10 0.00 0.692126E+11 0.00 0.00 0.371227E+10 0.805564E+10 0.00
August 0.658601E+11 0.136587E+11 0.140892E+12 0.691164E+11 0.462702E+11 0.708239E+10 0.00 0.836526E+11 0.00 0.00 0.535483E+10 0.804720E+10 0.00
September 0.643518E+11 0.153910E+11 0.136256E+12 0.668846E+11 0.426069E+11 0.680215E+10 0.00 0.402850E+11 0.00 0.00 0.239300E+10 0.779861E+10 0.00
October 0.669530E+11 0.182634E+11 0.140818E+12 0.691144E+11 0.415576E+11 0.652036E+10 0.00 0.138221E+11 0.00 0.00 0.520904E+10 0.804600E+10 0.00
November 0.651190E+11 0.197440E+11 0.136330E+12 0.668859E+11 0.391317E+11 0.380209E+10 0.00 0.374244E+10 0.00 0.00 0.139786E+11 0.778058E+10 0.00
December 0.674225E+11 0.215799E+11 0.140770E+12 0.691136E+11 0.402105E+11 0.256519E+10 0.00 0.117132E+10 0.00 0.00 0.209916E+11 0.805607E+10 0.00
                           
Annual Sum or Average 0.782856E+12 0.193501E+12 0.165818E+13 0.813771E+12 0.499010E+12 0.652756E+11 0.00 0.316581E+12 0.00 0.00 0.120790E+12 0.947834E+11 0.00
Minimum of Months 0.605329E+11 0.110232E+11 0.127191E+12 0.624261E+11 0.362981E+11 0.226579E+10 0.00 0.638853E+09 0.00 0.00 0.239300E+10 0.727208E+10 0.00
Maximum of Months 0.674225E+11 0.215799E+11 0.140892E+12 0.691169E+11 0.462702E+11 0.719885E+10 0.00 0.836526E+11 0.00 0.00 0.224671E+11 0.805607E+10 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [J] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [J] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.151918E+12 0.00 0.135205E+12 0.00 0.241350E+12 0.00 0.00
February 0.137204E+12 0.00 0.132691E+12 0.00 0.219199E+12 0.00 0.00
March 0.152024E+12 0.00 0.153760E+12 0.00 0.240638E+12 0.00 0.00
April 0.146956E+12 0.00 0.142770E+12 0.00 0.227870E+12 0.00 0.00
May 0.151978E+12 0.00 0.122498E+12 0.00 0.228682E+12 0.00 0.00
June 0.147114E+12 0.00 0.618497E+11 0.00 0.214925E+12 0.00 0.00
July 0.151820E+12 0.00 0.214627E+11 0.00 0.217355E+12 0.00 0.00
August 0.152039E+12 0.00 0.172866E+11 0.00 0.215989E+12 0.00 0.00
September 0.146971E+12 0.00 0.664399E+11 0.00 0.211101E+12 0.00 0.00
October 0.151903E+12 0.00 0.185329E+12 0.00 0.223310E+12 0.00 0.00
November 0.147091E+12 0.00 0.158282E+12 0.00 0.222692E+12 0.00 0.00
December 0.151820E+12 0.00 0.143619E+12 0.00 0.236697E+12 0.00 0.00
               
Annual Sum or Average 0.178884E+13 0.00 0.134119E+13 0.00 0.269981E+13 0.00 0.00
Minimum of Months 0.137204E+12 0.00 0.172866E+11 0.00 0.211101E+12 0.00 0.00
Maximum of Months 0.152039E+12 0.00 0.185329E+12 0.00 0.241350E+12 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 64632.59 02-JAN-20:10 12338.45 01-JAN-00:10 89171.45 02-JAN-07:10 49607.07 02-JAN-07:19 21469.47 13-JAN-19:10 3173.91 03-JAN-07:19 0.00 01-JAN-00:10
February 64632.59 01-FEB-20:10 12338.45 01-FEB-00:10 89171.45 01-FEB-07:10 49607.07 01-FEB-07:19 22361.17 27-FEB-21:19 3206.97 08-FEB-11:39 0.00 01-FEB-00:10
March 64632.59 01-MAR-20:10 12338.45 01-MAR-00:10 89171.45 01-MAR-07:10 49607.07 13-MAR-06:19 23429.51 18-MAR-20:49 3203.68 02-MAR-10:09 0.00 01-MAR-00:10
April 64632.59 03-APR-19:10 12338.45 01-APR-00:10 89171.45 03-APR-06:10 49606.78 04-APR-06:19 28197.80 27-APR-21:00 3164.10 06-APR-06:10 0.00 01-APR-00:10
May 64632.59 01-MAY-19:10 12338.45 01-MAY-00:10 89171.45 01-MAY-06:10 49606.67 01-MAY-06:19 29769.36 15-MAY-21:30 3153.14 18-MAY-09:09 0.00 01-MAY-00:10
June 64632.59 01-JUN-19:40 12338.45 01-JUN-00:10 89171.45 01-JUN-06:10 49605.70 22-JUN-06:19 29254.20 28-JUN-21:00 3093.47 20-JUN-18:19 0.00 01-JUN-00:10
July 64632.59 10-JUL-19:30 12338.45 01-JUL-00:10 89171.45 03-JUL-06:10 49605.70 10-JUL-06:19 30160.05 31-JUL-21:00 3272.05 31-JUL-18:10 0.00 01-JUL-00:10
August 64632.59 01-AUG-19:19 12338.45 01-AUG-00:10 89171.45 01-AUG-06:10 49606.38 16-AUG-06:19 31141.22 24-AUG-21:00 3389.68 10-AUG-18:10 0.00 01-AUG-00:10
September 64632.59 01-SEP-19:10 12338.45 01-SEP-00:10 89171.45 01-SEP-06:10 49607.07 06-SEP-06:19 31062.20 13-SEP-21:00 3131.00 08-SEP-15:09 0.00 01-SEP-00:10
October 64632.59 02-OCT-19:10 12338.45 01-OCT-00:10 89171.45 02-OCT-06:10 49607.07 02-OCT-06:19 30123.55 04-OCT-21:19 3187.66 30-OCT-08:09 0.00 01-OCT-00:10
November 64632.59 01-NOV-19:10 12338.45 01-NOV-00:10 89171.45 01-NOV-06:10 49607.07 01-NOV-06:19 23100.74 06-NOV-21:00 3212.26 11-NOV-11:39 0.00 01-NOV-00:10
December 64632.59 01-DEC-20:10 12338.45 01-DEC-00:10 89171.45 01-DEC-07:10 49607.07 01-DEC-07:19 21727.64 26-DEC-19:10 3189.41 05-DEC-10:20 0.00 01-DEC-00:10
                             
Annual Sum or Average                            
Minimum of Months 64632.59   12338.45   89171.45   49605.70   21469.47   3093.47   0.00  
Maximum of Months 64632.59   12338.45   89171.45   49607.07   31141.22   3389.68   0.00  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY {Maximum} [W] HEATRECOVERY:ELECTRICITY {TIMESTAMP} WATERSYSTEMS:ELECTRICITY {Maximum} [W] WATERSYSTEMS:ELECTRICITY {TIMESTAMP} COGENERATION:ELECTRICITY []
January 4290.45 11-JAN-19:10 0.00 0.00 9938.94 01-JAN-00:10 4751.13 17-JAN-07:10 0.00
February 36346.04 27-FEB-16:10 0.00 0.00 9938.94 01-FEB-00:20 4751.13 14-FEB-19:49 0.00
March 45617.27 18-MAR-15:09 0.00 0.00 9938.94 01-MAR-00:20 4751.12 14-MAR-06:19 0.00
April 87825.73 27-APR-15:09 0.00 0.00 9938.94 01-APR-00:10 4751.13 07-APR-18:49 0.00
May 76868.64 04-MAY-15:09 0.00 0.00 9938.94 03-MAY-03:49 4751.13 24-MAY-06:40 0.00
June 87343.71 28-JUN-18:10 0.00 0.00 9938.94 22-JUN-16:30 4751.13 21-JUN-06:30 0.00
July 112626.72 24-JUL-18:10 0.00 0.00 9938.94 14-JUL-16:30 4751.13 27-JUL-06:19 0.00
August 130336.53 10-AUG-18:10 0.00 0.00 9938.94 06-AUG-15:09 4751.13 04-AUG-06:00 0.00
September 87303.51 14-SEP-15:20 0.00 0.00 9938.94 22-SEP-16:19 4751.12 13-SEP-06:49 0.00
October 62129.49 04-OCT-15:09 0.00 0.00 9938.94 03-OCT-04:00 4751.13 24-OCT-06:40 0.00
November 54436.94 04-NOV-15:09 0.00 0.00 9938.94 08-NOV-22:10 4751.13 15-NOV-19:49 0.00
December 9332.83 05-DEC-12:30 0.00 0.00 9938.94 01-DEC-00:20 4751.13 06-DEC-07:30 0.00
                   
Annual Sum or Average     0.00 0.00         0.00
Minimum of Months 4290.45   0.00 0.00 9938.94   4751.12   0.00
Maximum of Months 130336.53   0.00 0.00 9938.94   4751.13   0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY []
January 225168.97 03-JAN-07:00 36001.17 89171.45 12338.45 49607.07 16017.06 2676.25 0.00 1445.88 0.00
February 224903.63 03-FEB-07:30 36001.17 89171.45 12338.45 49607.07 15805.86 2629.10 0.00 1436.61 0.00
March 225168.46 15-MAR-06:19 36001.17 89171.45 12338.45 49607.07 15303.49 2526.77 0.00 3676.09 0.00
April 290829.02 27-APR-18:10 53578.21 77573.37 0.00 28157.33 24205.38 3096.27 0.00 87119.71 0.00
May 253628.26 04-MAY-19:19 64632.59 86439.81 12338.45 10999.77 21859.35 2789.58 0.00 48210.23 0.00
June 290728.86 28-JUN-18:10 53184.46 77573.37 0.00 28157.23 24299.68 3064.38 0.00 87343.71 0.00
July 317190.60 24-JUL-18:10 52987.32 77573.37 0.00 28157.23 25485.57 3254.16 0.00 112626.72 0.00
August 335399.91 10-AUG-18:10 53578.21 77573.37 0.00 28157.73 25257.88 3389.68 0.00 130336.53 0.00
September 260000.28 13-SEP-18:30 57474.69 77573.37 12338.45 28169.74 20895.81 2731.35 0.00 53646.98 0.00
October 235734.73 04-OCT-18:10 57474.69 77573.37 12338.45 28159.60 20228.88 2576.43 0.00 30261.37 0.00
November 226976.26 04-NOV-17:10 46975.58 72654.62 12338.45 49247.41 15176.94 2534.00 0.00 21862.67 0.00
December 224660.91 15-DEC-07:49 36001.17 89171.45 12338.45 49607.07 15890.90 2656.25 0.00 1097.88 0.00
                       
Annual Sum or Average                     0.00
Minimum of Months 224660.91   36001.17 72654.62 0.00 10999.77 15176.94 2526.77 0.00 1097.88 0.00
Maximum of Months 335399.91   64632.59 89171.45 12338.45 49607.07 25485.57 3389.68 0.00 130336.53 0.00



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS {Maximum} [W] INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS {Maximum} [W] WATERSYSTEMS:NATURALGAS {TIMESTAMP} COGENERATION:NATURALGAS []
January 104248.32 02-JAN-18:10 0.00 198238.14 20-JAN-11:50 0.00 250400.13 30-JAN-21:40 0.00
February 104248.32 01-FEB-18:10 0.00 201745.73 08-FEB-11:50 0.00 250435.74 07-FEB-21:30 0.00
March 104248.32 01-MAR-18:10 0.00 200552.63 03-MAR-11:50 0.00 249312.41 03-MAR-21:40 0.00
April 104248.32 01-APR-17:10 0.00 187313.49 24-APR-22:40 0.00 245699.11 03-APR-20:19 0.00
May 104248.32 01-MAY-17:10 0.00 183508.26 18-MAY-09:20 0.00 239024.97 01-MAY-20:40 0.00
June 104248.32 01-JUN-17:10 0.00 154150.82 15-JUN-04:30 0.00 233032.45 01-JUN-20:30 0.00
July 104248.32 01-JUL-17:10 0.00 91284.20 03-JUL-03:00 0.00 226631.85 03-JUL-20:19 0.00
August 104248.32 01-AUG-17:10 0.00 94384.82 21-AUG-04:00 0.00 223915.36 30-AUG-20:30 0.00
September 104248.32 01-SEP-17:10 0.00 169813.55 27-SEP-03:09 0.00 226909.21 29-SEP-20:19 0.00
October 104248.32 02-OCT-17:10 0.00 195368.30 30-OCT-08:09 0.00 233988.33 31-OCT-20:00 0.00
November 104248.32 01-NOV-17:10 0.00 210727.42 11-NOV-11:50 0.00 240294.52 30-NOV-21:49 0.00
December 104248.32 01-DEC-18:10 0.00 203987.69 12-DEC-11:50 0.00 246841.34 29-DEC-21:40 0.00
                   
Annual Sum or Average     0.00     0.00     0.00
Minimum of Months 104248.32   0.00 91284.20   0.00 223915.36   0.00
Maximum of Months 104248.32   0.00 210727.42   0.00 250435.74   0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BASEMENT

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: RETAIL_1_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: RETAIL_2_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: MECH_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: STORAGE_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: LAUNDRY_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CAFE_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: LOBBY_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_1_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 1.67 20.47 1.67 20.47 0.00 20.47 0.00 20.47
February 0.17 20.50 0.17 20.50 0.00 20.50 0.00 20.50
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.33 21.71 0.33 21.71
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.50 21.69 0.50 21.69
August 0.00 0.00 0.00 0.00 1.50 21.78 1.50 21.78
September 0.00 0.00 0.00 0.00 0.83 21.74 0.83 21.74
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.67 20.49 0.67 20.49 0.00 20.49 0.00 20.49
December 2.00 20.44 2.00 20.44 0.00 20.44 0.00 20.44
                 
Annual Sum or Average 4.50 20.46 4.50 20.46 3.17 20.80 3.17 20.99
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2.00 20.50 2.00 20.50 1.50 21.78 1.50 21.78



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_2_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 4.00 20.46 4.00 20.46 0.00 20.46 0.00 20.46
February 1.17 20.46 1.17 20.46 0.00 20.46 0.00 20.46
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 1.67 21.96 1.67 21.96
June 0.00 0.00 0.00 0.00 0.83 21.94 0.83 21.94
July 0.00 0.00 0.00 0.00 2.50 21.90 2.50 21.90
August 0.00 0.00 0.00 0.00 1.67 21.72 1.67 21.72
September 0.00 0.00 0.00 0.00 0.17 22.02 0.17 22.02
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.67 20.45 0.67 20.45 0.00 20.45 0.00 20.45
December 3.17 20.43 3.17 20.43 0.00 20.43 0.00 20.43
                 
Annual Sum or Average 9.00 20.45 9.00 20.45 6.83 20.84 6.83 21.06
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4.00 20.46 4.00 20.46 2.50 22.02 2.50 22.02



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.17 21.78 0.17 21.78
May 0.00 0.00 0.00 0.00 2.17 21.76 2.17 21.76
June 0.00 0.00 0.00 0.00 3.17 21.82 3.17 21.82
July 0.00 0.00 0.00 0.00 4.67 21.84 4.67 21.84
August 0.00 0.00 0.00 0.00 1.50 21.76 1.50 21.76
September 0.00 0.00 0.00 0.00 0.50 21.71 0.50 21.71
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   12.17 21.80 12.17 21.80
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 4.67 21.84 4.67 21.84



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_5_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 1.67 20.46 1.67 20.46 0.00 20.46 0.00 20.46
February 0.17 20.47 0.17 20.47 0.00 20.47 0.00 20.47
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.67 20.47 0.67 20.47 0.00 20.47 0.00 20.47
December 2.67 20.45 2.67 20.45 0.00 20.45 0.00 20.45
                 
Annual Sum or Average 5.17 20.46 5.17 20.46 0.00 20.46 0.00 20.46
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2.67 20.47 2.67 20.47 0.00 20.47 0.00 20.47



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_6_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 5.33 20.45 5.33 20.45 0.00 20.45 0.00 20.45
February 1.83 20.49 1.83 20.49 0.00 20.49 0.00 20.49
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.17 22.33 0.17 22.33
May 0.00 0.00 0.00 0.00 0.33 21.95 0.33 21.95
June 0.00 0.00 0.00 0.00 0.67 22.45 0.67 22.45
July 0.00 0.00 0.00 0.00 2.50 22.33 2.50 22.33
August 0.00 0.00 0.00 0.00 3.33 22.31 3.33 22.31
September 0.00 0.00 0.00 0.00 0.33 22.26 0.33 22.26
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 1.00 20.46 1.00 20.46 0.00 20.46 0.00 20.46
December 4.00 20.44 4.00 20.44 0.00 20.44 0.00 20.44
                 
Annual Sum or Average 12.17 20.45 12.17 20.45 7.33 20.88 7.33 21.15
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5.33 20.49 5.33 20.49 3.33 22.45 3.33 22.45



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORRIDOR_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_1_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 3.17 20.51 3.17 20.51 0.00 20.51 0.00 20.51
February 0.33 20.54 0.33 20.54 0.00 20.54 0.00 20.54
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.17 21.74 0.17 21.74
May 0.00 0.00 0.00 0.00 0.50 21.86 0.50 21.86
June 0.00 0.00 0.00 0.00 0.17 21.70 0.17 21.70
July 0.00 0.00 0.00 0.00 1.50 21.73 1.50 21.73
August 0.00 0.00 0.00 0.00 3.33 21.79 3.33 21.79
September 0.00 0.00 0.00 0.00 1.00 21.86 1.00 21.86
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.83 20.51 0.83 20.51 0.00 20.51 0.00 20.51
December 3.00 20.48 3.00 20.48 0.00 20.48 0.00 20.48
                 
Annual Sum or Average 7.33 20.50 7.33 20.50 6.67 20.90 6.67 21.11
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3.17 20.54 3.17 20.54 3.33 21.86 3.33 21.86



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_2_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 6.50 20.49 6.50 20.49 0.00 20.49 0.00 20.49
February 2.83 20.52 2.83 20.52 0.00 20.52 0.00 20.52
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 2.67 22.02 2.67 22.02
June 0.00 0.00 0.00 0.00 2.17 21.94 2.17 21.94
July 0.00 0.00 0.00 0.00 4.83 21.92 4.83 21.92
August 0.00 0.00 0.00 0.00 3.33 21.79 3.33 21.79
September 0.00 0.00 0.00 0.00 0.33 21.94 0.33 21.94
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 1.33 20.51 1.33 20.51 0.00 20.51 0.00 20.51
December 5.33 20.48 5.33 20.48 0.00 20.48 0.00 20.48
                 
Annual Sum or Average 16.00 20.50 16.00 20.50 13.33 20.91 13.33 21.14
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6.50 20.52 6.50 20.52 4.83 22.02 4.83 22.02



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.67 20.51 0.67 20.51 0.00 20.51 0.00 20.51
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.67 21.70 0.67 21.70
September 0.00 0.00 0.00 0.00 0.83 21.71 0.83 21.71
October 0.00 0.00 0.00 0.00 0.17 21.84 0.17 21.84
November 0.17 20.48 0.17 20.48 0.00 20.48 0.00 20.48
December 1.00 20.46 1.00 20.46 0.00 20.46 0.00 20.46
                 
Annual Sum or Average 1.83 20.48 1.83 20.48 1.67 20.87 1.67 21.07
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1.00 20.51 1.00 20.51 0.83 21.84 0.83 21.84



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BANQUET_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DINING_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: KITCHEN_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORRIDOR_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: BASEMENT

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 742.33 23.24 0.00 23.24 0.00 23.24
February 672.00 23.07 0.00 23.07 0.00 23.07
March 744.00 22.88 0.00 22.88 0.00 22.88
April 720.00 22.76 0.00 22.76 0.00 22.76
May 744.00 22.85 0.00 22.85 0.00 22.85
June 719.67 23.01 0.00 23.01 0.00 23.01
July 686.50 23.18 0.67 23.18 0.00 23.18
August 513.17 23.26 13.50 23.28 0.00 23.28
September 390.33 23.40 30.67 23.44 0.00 23.44
October 473.83 23.59 0.00 23.59 0.00 23.59
November 510.50 23.65 11.50 23.65 0.00 23.65
December 718.50 23.53 0.00 23.53 0.00 23.53
             
Annual Sum or Average 7634.83 23.16 56.33 23.17 0.00 23.17
Minimum of Months 390.33 22.76 0.00 22.76 0.00 22.76
Maximum of Months 744.00 23.65 30.67 23.65 0.00 23.65



Table of Contents

Report: ComfortReportSimple55Monthly

For: RETAIL_1_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 740.50 21.04 209.33 21.03 209.33 21.02
February 652.00 21.10 129.33 21.11 121.67 21.10
March 713.17 21.16 24.00 21.21 9.00 21.21
April 678.83 21.26 22.83 21.35 0.00 21.35
May 689.50 21.33 29.33 21.43 0.00 21.43
June 676.50 21.42 15.00 21.47 0.00 21.47
July 616.00 21.62 76.33 21.83 0.00 21.83
August 560.67 21.59 122.33 21.96 0.00 21.96
September 585.17 21.38 94.33 21.72 0.00 21.72
October 682.50 21.20 37.67 21.35 0.00 21.35
November 706.83 21.05 35.17 21.08 27.67 21.07
December 734.17 21.06 171.50 21.05 170.67 21.05
             
Annual Sum or Average 8035.83 21.26 967.17 21.36 538.33 21.34
Minimum of Months 560.67 21.04 15.00 21.03 0.00 21.02
Maximum of Months 740.50 21.62 209.33 21.96 209.33 21.96



Table of Contents

Report: ComfortReportSimple55Monthly

For: RETAIL_2_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.63 0.00 21.63 0.00 21.63
February 672.00 21.91 0.00 21.91 0.00 21.91
March 744.00 22.26 0.00 22.26 0.00 22.26
April 694.67 22.52 1.83 22.53 0.00 22.53
May 686.17 22.76 6.67 22.77 0.00 22.77
June 605.83 22.84 14.33 22.87 0.00 22.87
July 453.67 22.97 105.67 23.15 0.00 23.15
August 361.33 22.88 172.67 23.21 0.00 23.21
September 511.17 22.82 67.00 22.94 0.00 22.94
October 723.50 22.54 0.00 22.54 0.00 22.54
November 718.50 22.00 0.00 22.00 0.00 22.00
December 744.00 21.75 0.00 21.75 0.00 21.75
             
Annual Sum or Average 7658.83 22.34 368.17 22.42 0.00 22.42
Minimum of Months 361.33 21.63 0.00 21.63 0.00 21.63
Maximum of Months 744.00 22.97 172.67 23.21 0.00 23.21



Table of Contents

Report: ComfortReportSimple55Monthly

For: MECH_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.06 16.33 21.06 16.33 21.06
February 672.00 21.19 18.17 21.19 18.17 21.18
March 744.00 21.49 1.17 21.48 1.17 21.48
April 720.00 21.90 0.00 21.90 0.00 21.90
May 744.00 22.41 0.00 22.41 0.00 22.41
June 718.50 22.75 0.00 22.75 0.00 22.75
July 700.17 23.07 0.00 23.07 0.00 23.07
August 635.33 23.11 3.50 23.12 0.00 23.12
September 710.00 22.72 0.00 22.72 0.00 22.72
October 744.00 22.02 0.00 22.02 0.00 22.02
November 720.00 21.38 0.00 21.38 0.00 21.38
December 744.00 21.09 0.00 21.09 0.00 21.09
             
Annual Sum or Average 8596.00 22.00 39.17 22.00 35.67 21.99
Minimum of Months 635.33 21.06 0.00 21.06 0.00 21.06
Maximum of Months 744.00 23.11 18.17 23.12 18.17 23.12



Table of Contents

Report: ComfortReportSimple55Monthly

For: STORAGE_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.00 51.83 21.00 51.83 21.00
February 672.00 21.07 51.00 21.06 51.00 21.06
March 744.00 21.19 12.17 21.19 12.17 21.19
April 720.00 21.58 0.00 21.58 0.00 21.58
May 744.00 22.10 0.00 22.10 0.00 22.10
June 720.00 22.46 0.00 22.46 0.00 22.46
July 737.00 22.82 0.00 22.82 0.00 22.82
August 726.50 22.91 0.00 22.91 0.00 22.91
September 720.00 22.42 0.00 22.42 0.00 22.42
October 744.00 21.68 0.00 21.68 0.00 21.68
November 720.00 21.17 0.00 21.17 0.00 21.17
December 744.00 21.01 4.50 21.01 4.50 21.01
             
Annual Sum or Average 8735.50 21.79 119.50 21.78 119.50 21.77
Minimum of Months 672.00 21.00 0.00 21.00 0.00 21.00
Maximum of Months 744.00 22.91 51.83 22.91 51.83 22.91



Table of Contents

Report: ComfortReportSimple55Monthly

For: LAUNDRY_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 245.33 22.87 531.00 23.27 146.33 23.38
February 225.50 23.00 492.83 23.30 145.67 23.42
March 249.83 23.11 588.33 23.31 173.00 23.43
April 257.50 23.33 604.00 23.34 198.00 23.46
May 291.67 23.54 645.33 23.37 244.33 23.50
June 292.83 23.74 638.33 23.42 265.83 23.55
July 297.67 23.87 678.83 23.44 284.83 23.56
August 307.00 23.92 696.33 23.42 299.50 23.55
September 297.50 23.77 650.17 23.42 274.00 23.55
October 277.50 23.41 635.83 23.36 220.50 23.48
November 251.17 23.19 585.50 23.32 181.33 23.44
December 235.83 22.92 562.33 23.26 146.50 23.38
             
Annual Sum or Average 3229.33 23.42 7308.83 23.36 2579.83 23.48
Minimum of Months 225.50 22.87 492.83 23.26 145.67 23.38
Maximum of Months 307.00 23.92 696.33 23.44 299.50 23.56



Table of Contents

Report: ComfortReportSimple55Monthly

For: CAFE_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 735.00 21.41 10.50 21.42 7.17 21.42
February 634.67 21.66 17.50 21.72 0.00 21.72
March 688.00 21.91 27.33 21.99 0.00 21.99
April 613.67 22.10 49.50 22.21 0.00 22.21
May 592.33 22.21 69.83 22.35 0.00 22.35
June 517.17 22.30 73.67 22.44 0.00 22.44
July 338.50 22.33 243.00 22.81 2.17 22.81
August 336.17 22.35 327.83 22.99 26.50 23.02
September 408.17 22.16 221.83 22.70 0.33 22.70
October 614.33 22.05 68.33 22.22 0.00 22.22
November 697.50 21.63 15.17 21.67 1.33 21.67
December 724.50 21.49 14.33 21.50 7.00 21.50
             
Annual Sum or Average 6900.00 21.90 1138.83 22.14 44.50 22.14
Minimum of Months 336.17 21.41 10.50 21.42 0.00 21.42
Maximum of Months 735.00 22.35 327.83 22.99 26.50 23.02



Table of Contents

Report: ComfortReportSimple55Monthly

For: LOBBY_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 22.04 0.00 22.04 0.00 22.04
February 665.17 22.32 0.00 22.32 0.00 22.32
March 725.83 22.61 0.00 22.61 0.00 22.61
April 616.50 22.74 16.67 22.77 0.00 22.77
May 535.00 22.82 44.83 22.90 0.00 22.90
June 404.50 22.76 109.33 23.01 0.00 23.01
July 263.17 22.84 253.33 23.35 2.67 23.35
August 207.00 22.86 376.00 23.49 26.00 23.51
September 287.00 22.70 224.67 23.20 2.33 23.21
October 601.83 22.73 13.00 22.75 0.00 22.75
November 693.50 22.34 5.83 22.36 1.67 22.36
December 744.00 22.15 0.00 22.15 0.00 22.15
             
Annual Sum or Average 6487.50 22.51 1043.67 22.69 32.67 22.70
Minimum of Months 207.00 22.04 0.00 22.04 0.00 22.04
Maximum of Months 744.00 22.86 376.00 23.49 26.00 23.51



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_1_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.80 369.50 20.69 369.50 20.63
February 670.50 21.06 190.17 20.96 190.17 20.90
March 740.67 21.27 19.17 21.25 19.17 21.23
April 704.33 21.46 1.00 21.46 0.67 21.46
May 706.17 21.53 1.33 21.54 0.00 21.54
June 682.83 21.58 0.83 21.58 0.00 21.58
July 662.67 21.50 11.17 21.53 0.00 21.53
August 665.00 21.51 15.17 21.55 0.00 21.55
September 663.00 21.46 5.33 21.48 0.00 21.48
October 732.33 21.35 0.00 21.35 0.00 21.35
November 718.00 20.99 110.33 20.89 110.33 20.81
December 744.00 20.87 284.50 20.73 284.50 20.65
             
Annual Sum or Average 8433.50 21.27 1008.50 21.20 974.33 21.13
Minimum of Months 662.67 20.80 0.00 20.69 0.00 20.63
Maximum of Months 744.00 21.58 369.50 21.58 369.50 21.58



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_2_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.64 477.83 20.55 477.83 20.51
February 672.00 20.85 297.00 20.75 297.00 20.69
March 743.50 21.10 59.50 21.05 59.50 21.01
April 702.00 21.42 7.00 21.45 1.50 21.45
May 664.83 21.69 54.00 22.02 9.50 22.09
June 623.67 21.84 56.00 22.16 4.83 22.19
July 584.17 22.03 112.33 22.63 24.00 22.80
August 621.00 21.90 56.17 22.17 5.50 22.21
September 611.00 21.66 58.00 21.97 3.67 22.00
October 739.67 21.26 2.67 21.26 0.83 21.26
November 720.00 20.87 181.17 20.73 181.17 20.65
December 744.00 20.70 413.67 20.58 413.67 20.53
             
Annual Sum or Average 8169.83 21.30 1775.33 21.31 1479.00 21.23
Minimum of Months 584.17 20.64 2.67 20.55 0.83 20.51
Maximum of Months 744.00 22.03 477.83 22.63 477.83 22.80



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.01 81.67 20.95 81.67 20.90
February 672.00 21.11 54.83 21.07 54.83 21.03
March 744.00 21.25 0.00 21.25 0.00 21.25
April 720.00 21.45 0.00 21.45 0.00 21.45
May 743.83 21.70 0.00 21.70 0.00 21.70
June 719.50 21.90 0.00 21.90 0.00 21.90
July 732.50 22.01 0.17 22.01 0.00 22.01
August 743.33 21.96 0.00 21.96 0.00 21.96
September 720.00 21.73 0.00 21.73 0.00 21.73
October 744.00 21.33 0.00 21.33 0.00 21.33
November 720.00 21.16 12.50 21.14 12.50 21.13
December 744.00 21.03 52.33 20.98 52.33 20.94
             
Annual Sum or Average 8747.17 21.47 201.50 21.45 201.33 21.42
Minimum of Months 672.00 21.01 0.00 20.95 0.00 20.90
Maximum of Months 744.00 22.01 81.67 22.01 81.67 22.01



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_5_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.78 377.33 20.68 377.33 20.63
February 672.00 21.08 180.83 20.99 180.83 20.93
March 744.00 21.33 15.00 21.32 15.00 21.30
April 709.33 21.55 0.50 21.55 0.50 21.55
May 713.33 21.57 0.00 21.57 0.00 21.57
June 673.67 21.59 0.00 21.59 0.00 21.59
July 669.33 21.54 1.00 21.54 0.00 21.54
August 652.83 21.49 1.83 21.50 0.00 21.50
September 663.33 21.46 0.00 21.46 0.00 21.46
October 737.50 21.39 0.00 21.39 0.00 21.39
November 720.00 21.00 112.67 20.89 112.67 20.81
December 744.00 20.85 291.50 20.72 291.50 20.65
             
Annual Sum or Average 8443.33 21.30 980.67 21.21 977.83 21.14
Minimum of Months 652.83 20.78 0.00 20.68 0.00 20.63
Maximum of Months 744.00 21.59 377.33 21.59 377.33 21.59



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_6_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.63 472.00 20.53 472.00 20.48
February 672.00 20.85 294.17 20.75 294.17 20.70
March 744.00 21.15 36.50 21.12 36.50 21.08
April 718.33 21.55 1.50 21.56 0.67 21.56
May 722.83 21.78 2.33 21.79 0.00 21.79
June 659.67 21.94 13.00 22.00 0.00 22.00
July 626.50 21.98 35.50 22.14 4.33 22.18
August 623.50 21.93 34.17 22.11 5.00 22.15
September 689.83 21.78 7.17 21.81 0.00 21.81
October 744.00 21.29 1.33 21.28 1.33 21.28
November 720.00 20.85 194.50 20.72 194.50 20.64
December 744.00 20.67 441.00 20.57 441.00 20.52
             
Annual Sum or Average 8408.67 21.35 1533.17 21.24 1449.50 21.14
Minimum of Months 623.50 20.63 1.33 20.53 0.00 20.48
Maximum of Months 744.00 21.98 472.00 22.14 472.00 22.18



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORRIDOR_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.00 13.83 21.00 13.83 21.00
February 672.00 21.05 10.00 21.04 10.00 21.04
March 744.00 21.18 0.00 21.18 0.00 21.18
April 720.00 21.54 0.00 21.54 0.00 21.54
May 744.00 22.08 0.00 22.08 0.00 22.08
June 720.00 22.35 0.00 22.35 0.00 22.35
July 744.00 22.71 0.00 22.71 0.00 22.71
August 739.33 22.81 0.00 22.81 0.00 22.81
September 720.00 22.35 0.00 22.35 0.00 22.35
October 744.00 21.51 0.00 21.51 0.00 21.51
November 720.00 21.06 0.00 21.06 0.00 21.06
December 744.00 21.01 0.33 21.01 0.33 21.01
             
Annual Sum or Average 8755.33 21.72 24.17 21.72 24.17 21.72
Minimum of Months 672.00 21.00 0.00 21.00 0.00 21.00
Maximum of Months 744.00 22.81 13.83 22.81 13.83 22.81



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_1_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.67 569.33 20.61 569.33 20.59
February 670.00 20.95 300.33 20.84 300.33 20.78
March 738.33 21.19 96.00 21.11 96.00 21.04
April 696.17 21.41 9.00 21.41 5.67 21.40
May 689.67 21.47 8.67 21.49 0.00 21.49
June 661.00 21.51 5.00 21.52 0.00 21.52
July 634.83 21.42 23.50 21.49 0.00 21.49
August 644.67 21.44 29.67 21.52 0.17 21.52
September 652.33 21.40 17.50 21.45 1.67 21.45
October 727.83 21.27 10.50 21.26 9.83 21.24
November 717.50 20.89 263.83 20.78 263.83 20.72
December 744.00 20.76 494.33 20.67 494.33 20.63
             
Annual Sum or Average 8320.33 21.19 1827.67 21.09 1741.17 21.01
Minimum of Months 634.83 20.67 5.00 20.61 0.00 20.59
Maximum of Months 744.00 21.51 569.33 21.52 569.33 21.52



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_2_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.54 640.67 20.50 640.67 20.48
February 672.00 20.74 412.67 20.65 412.67 20.61
March 742.00 21.01 166.83 20.92 166.83 20.86
April 689.67 21.35 16.17 21.38 9.00 21.38
May 663.67 21.78 67.67 22.21 23.83 22.39
June 606.33 21.89 76.00 22.33 15.33 22.45
July 567.00 22.15 132.33 22.88 40.50 23.18
August 606.17 21.89 75.17 22.26 13.17 22.35
September 596.67 21.63 84.00 22.10 11.33 22.18
October 737.83 21.17 26.00 21.15 23.33 21.11
November 719.67 20.76 337.50 20.65 337.50 20.59
December 744.00 20.59 628.83 20.55 628.83 20.54
             
Annual Sum or Average 8089.00 21.25 2663.83 21.28 2323.00 21.19
Minimum of Months 567.00 20.54 16.17 20.50 9.00 20.48
Maximum of Months 744.00 22.15 640.67 22.88 640.67 23.18



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 737.33 21.03 209.33 20.93 209.33 20.86
February 649.17 21.23 106.33 21.17 106.33 21.12
March 717.50 21.37 9.83 21.37 7.83 21.36
April 677.17 21.48 2.33 21.49 0.00 21.49
May 688.00 21.50 1.33 21.50 0.00 21.50
June 664.00 21.53 0.00 21.53 0.00 21.53
July 649.83 21.45 0.83 21.45 0.00 21.45
August 655.33 21.47 24.00 21.53 0.00 21.53
September 645.00 21.43 32.50 21.53 0.00 21.53
October 692.00 21.38 7.67 21.40 0.00 21.40
November 707.33 21.17 41.00 21.12 38.33 21.07
December 732.00 21.05 161.17 20.93 161.17 20.84
             
Annual Sum or Average 8214.67 21.34 596.33 21.30 523.00 21.26
Minimum of Months 645.00 21.03 0.00 20.93 0.00 20.84
Maximum of Months 737.33 21.53 209.33 21.53 209.33 21.53



Table of Contents

Report: ComfortReportSimple55Monthly

For: BANQUET_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 385.33 23.14 26.67 23.20 0.00 23.20
February 288.83 23.18 97.83 23.39 0.00 23.39
March 208.67 23.20 129.83 23.50 0.00 23.50
April 85.17 23.20 270.67 23.79 0.00 23.79
May 6.83 23.17 561.17 23.97 0.00 23.97
June 0.50 23.06 651.17 23.97 0.00 23.97
July 2.33 23.99 730.00 23.96 2.33 23.96
August 26.67 23.99 741.50 23.95 26.67 23.95
September 12.83 23.70 646.50 23.94 8.50 23.94
October 130.50 23.13 354.33 23.75 0.00 23.75
November 244.33 23.10 182.83 23.47 2.00 23.47
December 340.00 23.09 30.67 23.17 0.00 23.17
             
Annual Sum or Average 1732.00 23.16 4423.17 23.74 39.50 23.74
Minimum of Months 0.50 23.06 26.67 23.17 0.00 23.17
Maximum of Months 385.33 23.99 741.50 23.97 26.67 23.97



Table of Contents

Report: ComfortReportSimple55Monthly

For: DINING_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 223.50 23.21 149.50 23.52 0.00 23.52
February 154.00 23.28 208.67 23.68 0.00 23.68
March 70.83 23.32 341.50 23.87 0.00 23.87
April 4.83 23.27 498.33 23.98 0.00 23.98
May 0.00 0.00 702.67 23.98 0.00 23.98
June 0.00 0.00 712.00 23.98 0.00 23.98
July 0.00 0.00 743.00 23.99 0.00 23.99
August 18.33 23.99 744.00 23.98 18.33 23.98
September 1.83 24.00 706.67 23.96 1.83 23.96
October 4.33 23.25 543.17 23.98 0.00 23.98
November 103.83 23.20 336.17 23.80 1.17 23.80
December 184.33 23.17 170.17 23.57 0.00 23.57
             
Annual Sum or Average 765.83 23.24 5855.83 23.90 21.33 23.90
Minimum of Months 0.00 0.00 149.50 23.52 0.00 23.52
Maximum of Months 223.50 24.00 744.00 23.99 18.33 23.99



Table of Contents

Report: ComfortReportSimple55Monthly

For: KITCHEN_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 499.83 23.96 676.17 23.92 491.00 23.94
February 458.83 23.97 621.17 23.92 451.83 23.94
March 519.00 23.99 725.17 23.91 519.00 23.94
April 512.33 23.99 716.50 23.92 512.33 23.94
May 537.00 23.99 744.00 23.93 537.00 23.95
June 531.67 23.99 720.00 23.95 531.67 23.96
July 557.00 23.99 744.00 23.96 557.00 23.97
August 565.17 23.99 744.00 23.97 565.17 23.97
September 530.17 23.99 720.00 23.95 530.17 23.96
October 527.67 23.99 744.00 23.92 527.67 23.94
November 498.83 23.99 692.33 23.92 498.83 23.94
December 497.33 23.99 685.00 23.92 497.17 23.94
             
Annual Sum or Average 6234.83 23.99 8532.33 23.93 6218.83 23.95
Minimum of Months 458.83 23.96 621.17 23.91 451.83 23.94
Maximum of Months 565.17 23.99 744.00 23.97 565.17 23.97



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORRIDOR_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.00 23.00 21.00 23.00 21.00
February 672.00 21.07 22.50 21.07 22.50 21.07
March 744.00 21.24 0.00 21.24 0.00 21.24
April 717.83 21.65 0.00 21.65 0.00 21.65
May 735.33 22.14 0.00 22.14 0.00 22.14
June 695.17 22.49 0.00 22.49 0.00 22.49
July 602.50 22.73 32.50 22.79 0.00 22.79
August 564.67 22.69 71.17 22.83 0.00 22.83
September 661.50 22.25 16.67 22.29 0.00 22.29
October 744.00 21.49 0.00 21.49 0.00 21.49
November 720.00 21.09 0.00 21.09 0.00 21.09
December 744.00 21.02 0.00 21.02 0.00 21.02
             
Annual Sum or Average 8345.00 21.70 165.83 21.73 45.50 21.72
Minimum of Months 564.67 21.00 0.00 21.00 0.00 21.00
Maximum of Months 744.00 22.73 71.17 22.83 23.00 22.83



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BASEMENT PEOPLE

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.24269 32.94383 0.09747 5.31959
February 672.00000 23.06586 34.09152 0.05984 5.22691
March 744.00000 22.87548 34.80752 0.01653 5.16977
April 720.00000 22.76470 38.35291 0.01106 5.16733
May 744.00000 22.84714 42.39340 -0.9671 24.94524
June 720.00000 23.01157 44.92684 -0.8891 21.91839
July 744.00000 23.22544 48.95740 -0.7831 18.16156
August 744.00000 23.40461 52.67330 -0.6923 15.27202
September 720.00000 23.58798 48.62677 -0.6510 14.11057
October 744.00000 23.70499 39.49527 0.26714 6.57449
November 720.00000 23.72572 37.79159 0.25991 6.50221
December 744.00000 23.54299 33.81569 0.18234 5.79689
           
Annual Sum or Average 8760.00000 23.25120 40.77585 -0.2593 11.22119
Minimum of Months 672.00000 22.76470 32.94383 -0.9671 5.16733
Maximum of Months 744.00000 23.72572 52.67330 0.26714 24.94524



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: RETAIL_1_FLR_1 PEOPLE

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.04717 35.01496 -0.4860 10.21497
February 672.00000 21.17912 35.81060 -0.3944 9.12940
March 744.00000 21.26476 36.15953 -0.3275 8.16325
April 720.00000 21.39649 39.51773 -0.2340 7.34520
May 744.00000 21.48354 43.89713 -1.2749 40.55277
June 720.00000 21.52742 47.00136 -1.2163 37.24238
July 744.00000 21.90750 50.80971 -1.0293 29.67655
August 744.00000 22.04095 55.00152 -0.9496 27.17094
September 720.00000 21.79166 51.92714 -1.0875 33.45715
October 744.00000 21.40827 43.05752 -0.2196 7.32445
November 720.00000 21.09832 41.70471 -0.3858 8.71928
December 744.00000 21.09590 36.59222 -0.4546 9.80498
           
Annual Sum or Average 8760.00000 21.43869 43.07873 -0.6732 19.11970
Minimum of Months 672.00000 21.04717 35.01496 -1.2749 7.32445
Maximum of Months 744.00000 22.04095 55.00152 -0.2196 40.55277



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: RETAIL_2_FLR_1 PEOPLE

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.62984 36.62558 -0.2684 6.78557
February 672.00000 21.91229 37.03545 -0.1891 6.21281
March 744.00000 22.26306 36.94471 -0.0959 5.56571
April 720.00000 22.56735 39.75960 0.00420 5.49282
May 744.00000 22.84239 43.47289 -0.9088 23.11917
June 720.00000 22.99107 46.04526 -0.8347 20.35171
July 744.00000 23.27131 49.82839 -0.7011 15.97230
August 744.00000 23.31094 53.90572 -0.6581 14.75776
September 720.00000 23.07760 51.03873 -0.7684 18.30290
October 744.00000 22.57778 43.06032 0.02699 5.41786
November 720.00000 21.99868 42.37182 -0.1335 5.82877
December 744.00000 21.74699 38.04821 -0.2294 6.38409
           
Annual Sum or Average 8760.00000 22.51917 43.21073 -0.3976 11.20910
Minimum of Months 672.00000 21.62984 36.62558 -0.9088 5.41786
Maximum of Months 744.00000 23.31094 53.90572 0.02699 23.11917



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: LAUNDRY_FLR_1 PEOPLE

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 22.95842 29.66178 0.60339 15.25362
February 672.00000 22.99023 30.48108 0.63080 15.98976
March 744.00000 23.01348 30.85184 0.65949 16.69801
April 720.00000 23.03883 34.11992 0.70494 17.95228
May 744.00000 23.04752 38.23984 0.02448 10.09580
June 720.00000 23.06193 41.10070 0.07014 10.16980
July 744.00000 23.08156 45.62210 0.11807 10.14799
August 744.00000 23.08156 49.85891 0.15466 10.39218
September 720.00000 23.07365 46.31808 0.09837 10.20114
October 744.00000 23.06023 37.20534 0.72540 18.51299
November 720.00000 23.01746 35.55514 0.67819 17.25920
December 744.00000 22.97334 31.09712 0.62028 15.65262
           
Annual Sum or Average 8760.00000 23.03337 37.54775 0.42271 14.01243
Minimum of Months 672.00000 22.95842 29.66178 0.02448 10.09580
Maximum of Months 744.00000 23.08156 49.85891 0.72540 18.51299



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CAFE_FLR_1 PEOPLE

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.43835 39.31669 -0.2905 7.26939
February 672.00000 21.76354 39.71695 -0.1642 6.68437
March 744.00000 22.03884 39.83186 -0.0638 6.11845
April 720.00000 22.28955 42.81879 0.04680 6.09265
May 744.00000 22.43515 46.88212 -0.8853 23.15689
June 720.00000 22.55923 49.61156 -0.8066 19.82757
July 744.00000 22.86154 53.48393 -0.6477 15.24721
August 744.00000 22.96450 57.47639 -0.5728 13.94684
September 720.00000 22.75437 54.40511 -0.6925 18.08089
October 744.00000 22.30779 46.10423 0.06619 6.36706
November 720.00000 21.68333 45.42610 -0.1570 6.44384
December 744.00000 21.53833 40.81822 -0.2495 6.98403
           
Annual Sum or Average 8760.00000 22.22217 46.35956 -0.3694 11.37616
Minimum of Months 672.00000 21.43835 39.31669 -0.8853 6.09265
Maximum of Months 744.00000 22.96450 57.47639 0.06619 23.15689



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: LOBBY_FLR_1 PEOPLE

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 22.04435 38.54332 -0.1404 5.92114
February 672.00000 22.33601 38.93666 -0.0539 5.69710
March 744.00000 22.64109 38.96496 0.03373 5.54719
April 720.00000 22.87832 41.85826 0.12212 5.82016
May 744.00000 23.07297 45.66192 -0.7722 18.30420
June 720.00000 23.20063 48.22967 -0.7008 16.04074
July 744.00000 23.38316 52.19258 -0.5965 13.03846
August 744.00000 23.43043 56.13113 -0.5484 11.88524
September 720.00000 23.28480 53.12532 -0.6345 14.35161
October 744.00000 22.92304 44.98153 0.15356 6.00329
November 720.00000 22.38577 44.23529 -0.0063 5.67933
December 744.00000 22.15151 39.95922 -0.1023 5.74003
           
Annual Sum or Average 8760.00000 22.81353 45.26892 -0.2719 9.52301
Minimum of Months 672.00000 22.04435 38.54332 -0.7722 5.54719
Maximum of Months 744.00000 23.43043 56.13113 0.15356 18.30420



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_1_FLR_3 PEOPLE

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.79627 48.32192 -0.5446 11.51091
February 672.00000 21.06623 48.36796 -0.4421 9.74109
March 744.00000 21.27618 48.29712 -0.3481 8.12232
April 720.00000 21.50514 49.64707 -0.2310 6.97532
May 744.00000 21.62415 51.18464 -1.2697 40.01787
June 720.00000 21.66798 51.66749 -1.2222 37.63047
July 744.00000 21.70246 51.41641 -1.1509 34.47814
August 744.00000 21.69741 53.65248 -1.1484 34.34939
September 720.00000 21.60924 55.08930 -1.2292 38.04771
October 744.00000 21.38192 53.93312 -0.2599 7.09509
November 720.00000 21.00148 53.84453 -0.4272 9.31468
December 744.00000 20.86527 49.69810 -0.5133 10.99417
           
Annual Sum or Average 8760.00000 21.35075 51.26951 -0.7341 20.75452
Minimum of Months 672.00000 20.79627 48.29712 -1.2697 6.97532
Maximum of Months 744.00000 21.70246 55.08930 -0.2310 40.01787



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_2_FLR_3 PEOPLE

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.64397 48.74846 -0.5917 12.66930
February 672.00000 20.85263 48.99948 -0.5128 10.98008
March 744.00000 21.10033 48.81545 -0.4122 8.87680
April 720.00000 21.48960 49.93264 -0.2588 7.30124
May 744.00000 22.02232 50.73967 -1.1788 38.00824
June 720.00000 22.21950 50.56942 -1.0824 33.19017
July 744.00000 22.54578 50.16792 -0.9280 28.68615
August 744.00000 22.26295 53.63300 -1.0108 29.61750
September 720.00000 22.06982 55.42138 -1.1313 35.21202
October 744.00000 21.27542 54.68990 -0.3109 7.52488
November 720.00000 20.86677 54.44301 -0.4720 10.06749
December 744.00000 20.69565 50.18528 -0.5672 12.05400
           
Annual Sum or Average 8760.00000 21.50735 51.36808 -0.7060 19.56469
Minimum of Months 672.00000 20.64397 48.74846 -1.1788 7.30124
Maximum of Months 744.00000 22.54578 55.42138 -0.2588 38.00824



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_3_MULT19_FLR_3 PEOPLE

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 0.00000 0.00000 0.00000 0.00000 0.00000
February 0.00000 0.00000 0.00000 0.00000 0.00000
March 0.00000 0.00000 0.00000 0.00000 0.00000
April 0.00000 0.00000 0.00000 0.00000 0.00000
May 0.00000 0.00000 0.00000 0.00000 0.00000
June 0.00000 0.00000 0.00000 0.00000 0.00000
July 0.00000 0.00000 0.00000 0.00000 0.00000
August 0.00000 0.00000 0.00000 0.00000 0.00000
September 0.00000 0.00000 0.00000 0.00000 0.00000
October 0.00000 0.00000 0.00000 0.00000 0.00000
November 0.00000 0.00000 0.00000 0.00000 0.00000
December 0.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 0.00000        
Minimum of Months 0.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 0.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_4_MULT19_FLR_3 PEOPLE

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.01234 45.02492 -0.4594 9.51165
February 672.00000 21.10664 45.37316 -0.4226 8.92393
March 744.00000 21.25260 45.33044 -0.3629 7.83909
April 720.00000 21.45075 46.99155 -0.2853 6.98024
May 744.00000 21.69858 48.41708 -1.3372 42.76095
June 720.00000 21.89961 48.44609 -1.2508 38.57474
July 744.00000 22.04499 50.24406 -1.1791 35.33643
August 744.00000 21.96652 53.21770 -1.1923 35.74253
September 720.00000 21.72598 53.49246 -1.3005 40.85307
October 744.00000 21.33022 50.99498 -0.2995 6.97055
November 720.00000 21.15709 50.23631 -0.3712 8.02525
December 744.00000 21.03065 46.49852 -0.4448 9.21125
           
Annual Sum or Average 8760.00000 21.47507 48.70411 -0.7441 20.96278
Minimum of Months 672.00000 21.01234 45.02492 -1.3372 6.97055
Maximum of Months 744.00000 22.04499 53.49246 -0.2853 42.76095



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_5_FLR_3 PEOPLE

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.78249 48.33350 -0.5479 11.54944
February 672.00000 21.07979 48.32156 -0.4398 9.63043
March 744.00000 21.33292 48.08354 -0.3345 7.97228
April 720.00000 21.57961 48.99231 -0.2125 6.88692
May 744.00000 21.64126 50.88001 -1.2793 40.47573
June 720.00000 21.70290 50.73105 -1.2058 36.93066
July 744.00000 21.71553 51.35689 -1.1686 35.28822
August 744.00000 21.71747 53.03675 -1.1457 34.26328
September 720.00000 21.61188 55.19932 -1.2406 38.60030
October 744.00000 21.41093 53.60217 -0.2553 7.08228
November 720.00000 20.99678 53.79210 -0.4282 9.30160
December 744.00000 20.84863 49.73329 -0.5169 11.00369
           
Annual Sum or Average 8760.00000 21.36958 51.01441 -0.7332 20.81622
Minimum of Months 672.00000 20.78249 48.08354 -1.2793 6.88692
Maximum of Months 744.00000 21.71747 55.19932 -0.2125 40.47573



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_6_FLR_3 PEOPLE

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.63029 48.77063 -0.5954 12.79265
February 672.00000 20.84675 48.98373 -0.5145 10.93075
March 744.00000 21.15074 48.60205 -0.4001 8.57896
April 720.00000 21.55960 49.35872 -0.2408 6.99947
May 744.00000 21.84098 50.79108 -1.2461 38.98467
June 720.00000 22.12090 50.01297 -1.1044 32.75560
July 744.00000 22.28785 50.98026 -1.0232 29.86490
August 744.00000 22.25145 53.11496 -1.0164 29.61401
September 720.00000 21.87122 56.13929 -1.2016 36.87027
October 744.00000 21.28719 54.33151 -0.3108 7.41691
November 720.00000 20.85141 54.44083 -0.4750 10.10630
December 744.00000 20.67402 50.22211 -0.5719 12.17674
           
Annual Sum or Average 8760.00000 21.45096 51.31860 -0.7264 19.80905
Minimum of Months 672.00000 20.63029 48.60205 -1.2461 6.99947
Maximum of Months 744.00000 22.28785 56.13929 -0.2408 38.98467



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_1_FLR_6 PEOPLE

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.66872 49.87038 -0.6025 13.01039
February 672.00000 20.96133 49.84877 -0.4897 10.83710
March 744.00000 21.20439 49.71101 -0.3808 8.76963
April 720.00000 21.47082 50.84021 -0.2469 7.31451
May 744.00000 21.60450 52.22835 -1.2826 40.91481
June 720.00000 21.65757 52.58358 -1.2251 38.00401
July 744.00000 21.69330 52.34170 -1.1475 34.58704
August 744.00000 21.68501 54.97492 -1.1490 34.61851
September 720.00000 21.57884 56.83226 -1.2437 38.98461
October 744.00000 21.31773 55.60464 -0.2881 7.53973
November 720.00000 20.89769 55.66205 -0.4715 10.29401
December 744.00000 20.76249 51.26169 -0.5648 12.25382
           
Annual Sum or Average 8760.00000 21.29338 52.65502 -0.7595 21.49004
Minimum of Months 672.00000 20.66872 49.71101 -1.2826 7.31451
Maximum of Months 744.00000 21.69330 56.83226 -0.2469 40.91481



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_2_FLR_6 PEOPLE

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.54229 50.25582 -0.6459 14.19461
February 672.00000 20.74413 50.54479 -0.5630 12.25948
March 744.00000 21.01930 50.29823 -0.4489 9.65713
April 720.00000 21.47172 51.12129 -0.2724 7.71586
May 744.00000 22.08661 51.58936 -1.1631 38.78741
June 720.00000 22.30116 51.10215 -1.0526 33.15850
July 744.00000 22.65600 50.41636 -0.8819 28.88503
August 744.00000 22.29068 54.55166 -0.9961 29.82625
September 720.00000 22.12370 56.80080 -1.1185 35.85051
October 744.00000 21.20083 56.47985 -0.3432 8.09676
November 720.00000 20.75648 56.31886 -0.5186 11.18902
December 744.00000 20.59329 51.79531 -0.6198 13.45752
           
Annual Sum or Average 8760.00000 21.48626 52.60968 -0.7197 20.30336
Minimum of Months 672.00000 20.54229 50.25582 -1.1631 7.71586
Maximum of Months 744.00000 22.65600 56.80080 -0.2724 38.78741



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_3_MULT9_FLR_6 PEOPLE

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.05332 48.20491 -0.4622 10.11918
February 672.00000 21.29776 48.06825 -0.3554 8.70386
March 744.00000 21.44202 47.98464 -0.2834 7.66236
April 720.00000 21.59442 49.31854 -0.2028 6.98032
May 744.00000 21.63663 51.19208 -1.2911 41.25952
June 720.00000 21.67137 51.74264 -1.2506 39.16228
July 744.00000 21.68931 52.09413 -1.2026 37.02810
August 744.00000 21.68916 53.90001 -1.1789 35.94996
September 720.00000 21.63058 54.45776 -1.2290 38.38805
October 744.00000 21.51275 52.59759 -0.2088 6.89929
November 720.00000 21.21073 52.90877 -0.3585 8.43480
December 744.00000 21.09139 49.47318 -0.4343 9.86835
           
Annual Sum or Average 8760.00000 21.46055 51.00708 -0.7071 20.94537
Minimum of Months 672.00000 21.05332 47.98464 -1.2911 6.89929
Maximum of Months 744.00000 21.68931 54.45776 -0.2028 41.25952



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BANQUET_FLR_6 PEOPLE

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.54003 38.37685 0.24226 6.67089
February 672.00000 23.61734 38.88250 0.27690 7.05560
March 744.00000 23.73376 38.81755 0.32831 7.52803
April 720.00000 23.83444 41.49543 0.39568 8.46821
May 744.00000 23.90657 44.91075 -0.4111 8.70316
June 720.00000 23.93325 47.32748 -0.3587 7.81083
July 744.00000 23.95787 51.39058 -0.3023 7.03082
August 744.00000 23.94473 55.43465 -0.2811 6.74982
September 720.00000 23.89542 52.59917 -0.3583 7.88519
October 744.00000 23.78436 44.66721 0.39461 8.44963
November 720.00000 23.65804 43.62549 0.32915 7.65944
December 744.00000 23.57177 39.74023 0.26168 6.83478
           
Annual Sum or Average 8760.00000 23.78228 44.80441 0.04163 7.57054
Minimum of Months 672.00000 23.54003 38.37685 -0.4111 6.67089
Maximum of Months 744.00000 23.95787 55.43465 0.39568 8.70316



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DINING_FLR_6 PEOPLE

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.73668 37.17943 0.33059 7.54871
February 672.00000 23.79226 37.72372 0.35951 7.98826
March 744.00000 23.86775 37.71889 0.39994 8.50023
April 720.00000 23.92946 40.49760 0.45605 9.46792
May 744.00000 23.96467 44.05847 -0.3399 7.51825
June 720.00000 23.97698 46.57604 -0.2957 6.90118
July 744.00000 23.98594 50.72452 -0.2480 6.38529
August 744.00000 23.98007 54.75175 -0.2249 6.12652
September 720.00000 23.95479 51.75808 -0.2893 6.87005
October 744.00000 23.89417 43.60285 0.45888 9.50719
November 720.00000 23.81612 42.43373 0.40773 8.71705
December 744.00000 23.75704 38.51822 0.34731 7.75775
           
Annual Sum or Average 8760.00000 23.88844 43.82851 0.11198 7.76992
Minimum of Months 672.00000 23.73668 37.17943 -0.3399 6.12652
Maximum of Months 744.00000 23.98594 54.75175 0.45888 9.50719



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: KITCHEN_FLR_6 PEOPLE

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.77940 35.56519 0.95820 26.49878
February 672.00000 23.79580 36.18374 0.98914 27.82027
March 744.00000 23.83658 36.40091 1.03190 29.35986
April 720.00000 23.86733 39.36040 1.09599 32.21725
May 744.00000 23.89380 43.14740 0.57855 16.55779
June 720.00000 23.92354 45.73706 0.64362 17.91770
July 744.00000 23.93977 49.93568 0.69746 19.49293
August 744.00000 23.94717 53.77770 0.72968 20.26482
September 720.00000 23.91963 50.60708 0.64722 17.98962
October 744.00000 23.86863 42.28509 1.09601 32.05763
November 720.00000 23.82486 40.91337 1.03487 29.54745
December 744.00000 23.78813 36.88328 0.97431 27.09472
           
Annual Sum or Average 8760.00000 23.86576 42.60146 0.87232 24.71301
Minimum of Months 672.00000 23.77940 35.56519 0.57855 16.55779
Maximum of Months 744.00000 23.94717 53.77770 1.09601 32.21725



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: STORAGE_FLR_1 PEOPLE

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.00451 34.53376 -0.4714 9.67927
February 672.00000 21.06535 35.42810 -0.4402 9.18855
March 744.00000 21.19416 35.68449 -0.3908 8.29731
April 720.00000 21.58389 38.49154 -0.2749 6.88910
May 744.00000 22.10412 41.83539 -1.2192 36.44847
June 720.00000 22.46130 44.04654 -1.0798 29.83164
July 744.00000 22.83089 47.73136 -0.9254 23.37047
August 744.00000 22.92799 51.80719 -0.8652 21.12018
September 720.00000 22.42482 49.59959 -1.0573 28.97177
October 744.00000 21.68047 41.89870 -0.2302 6.32283
November 720.00000 21.16738 40.99928 -0.3739 8.14842
December 744.00000 21.00720 36.18316 -0.4556 9.35924
           
Annual Sum or Average 8760.00000 21.79228 41.55066 -0.6499 16.50695
Minimum of Months 672.00000 21.00451 34.53376 -1.2192 6.32283
Maximum of Months 744.00000 22.92799 51.80719 -0.2302 36.44847



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORRIDOR_FLR_3 PEOPLE

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.00284 37.56582 -0.4610 9.46498
February 672.00000 21.04500 38.48075 -0.4343 9.02174
March 744.00000 21.18482 38.73267 -0.3874 8.20291
April 720.00000 21.54333 41.58990 -0.2774 6.88938
May 744.00000 22.08004 44.93655 -1.2236 36.61879
June 720.00000 22.35279 47.36419 -1.1117 31.25975
July 744.00000 22.71123 51.12900 -0.9601 24.78015
August 744.00000 22.81508 55.23530 -0.8971 22.30088
September 720.00000 22.35001 52.82646 -1.0775 30.03509
October 744.00000 21.50762 45.25560 -0.2658 6.73799
November 720.00000 21.05685 44.25685 -0.3974 8.39896
December 744.00000 21.00835 39.20138 -0.4480 9.21168
           
Annual Sum or Average 8760.00000 21.72592 44.74611 -0.6630 16.95053
Minimum of Months 672.00000 21.00284 37.56582 -1.2236 6.73799
Maximum of Months 744.00000 22.81508 55.23530 -0.2658 36.61879



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORRIDOR_FLR_6 PEOPLE

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.00381 35.42398 -0.4547 9.35082
February 672.00000 21.07480 36.26979 -0.4163 8.77209
March 744.00000 21.23949 36.47529 -0.3552 7.77457
April 720.00000 21.65373 39.18475 -0.2260 6.54851
May 744.00000 22.15813 42.51704 -1.1490 33.42985
June 720.00000 22.53078 44.67522 -0.9993 26.64867
July 744.00000 22.89467 48.34275 -0.8423 20.73574
August 744.00000 22.92728 52.58840 -0.8032 19.45151
September 720.00000 22.36012 50.54905 -1.0246 28.18234
October 744.00000 21.49184 43.10105 -0.2460 6.58354
November 720.00000 21.08757 42.01464 -0.3750 8.12535
December 744.00000 21.01529 37.05031 -0.4391 9.05493
           
Annual Sum or Average 8760.00000 21.79097 42.38008 -0.6120 15.42075
Minimum of Months 672.00000 21.00381 35.42398 -1.1490 6.54851
Maximum of Months 744.00000 22.92728 52.58840 -0.2260 33.42985



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: MECH_FLR_1 PEOPLE

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.06476 34.02497 -0.4492 9.27384
February 672.00000 21.19209 34.76497 -0.4069 8.67150
March 744.00000 21.48529 34.71348 -0.3269 7.38528
April 720.00000 21.89766 37.42342 -0.2077 6.22362
May 744.00000 22.41206 40.71774 -1.1250 31.99903
June 720.00000 22.75009 42.92619 -0.9913 26.06110
July 744.00000 23.11117 46.57135 -0.8390 20.19235
August 744.00000 23.20881 50.57200 -0.7785 18.12779
September 720.00000 22.73586 48.32640 -0.9616 24.96557
October 744.00000 22.02178 40.70433 -0.1565 5.73776
November 720.00000 21.37508 40.11030 -0.3247 7.52241
December 744.00000 21.09077 35.63587 -0.4294 8.89099
           
Annual Sum or Average 8760.00000 22.03390 40.57025 -0.5841 14.61863
Minimum of Months 672.00000 21.06476 34.02497 -1.1250 5.73776
Maximum of Months 744.00000 23.20881 50.57200 -0.1565 31.99903



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.638853E+09 7287.92 11-JAN-19:03 159.36 0.301303E+10 0.00 0.365188E+10 1.01 4.72 01-JAN-19:02 0.00 0.00
February 0.296017E+10 49318.38 27-FEB-16:03 284.24 0.137947E+11 0.00 0.167549E+11 1.99 4.72 01-FEB-06:08 0.00 0.00
March 0.715482E+10 59775.06 18-MAR-15:01 508.55 0.333749E+11 0.00 0.405297E+11 3.22 4.72 01-MAR-01:10 0.00 0.00
April 0.188866E+11 99116.90 27-APR-18:03 660.85 0.841844E+11 0.00 0.103071E+12 4.28 4.72 01-APR-06:05 0.00 0.00
May 0.304821E+11 86909.36 04-MAY-15:03 734.68 0.135987E+12 0.00 0.166469E+12 4.57 4.72 01-MAY-02:40 0.00 0.00
June 0.445722E+11 99608.13 28-JUN-18:03 719.39 0.196308E+12 0.00 0.240880E+12 4.55 4.72 01-JUN-05:50 0.00 0.00
July 0.692126E+11 123540.98 24-JUL-18:03 744.00 0.296681E+12 0.00 0.365893E+12 4.46 4.72 02-JUL-03:05 0.00 0.00
August 0.836526E+11 143742.81 10-AUG-18:03 744.00 0.350563E+12 0.00 0.434215E+12 4.39 4.72 01-AUG-03:20 0.00 0.00
September 0.402850E+11 96231.89 14-SEP-15:03 712.08 0.178598E+12 0.00 0.218883E+12 4.53 4.72 02-SEP-06:30 0.00 0.00
October 0.138221E+11 71743.49 04-OCT-15:03 638.89 0.635698E+11 0.00 0.773918E+11 4.02 4.72 01-OCT-22:10 0.00 0.00
November 0.374244E+10 68779.82 04-NOV-15:03 336.78 0.172429E+11 0.00 0.209853E+11 2.20 4.72 01-NOV-03:40 0.00 0.00
December 0.117132E+10 9716.22 02-DEC-09:02 193.72 0.552444E+10 0.00 0.669576E+10 1.23 4.72 01-DEC-14:00 0.00 0.00
                         
Annual Sum or Average 0.316581E+12     6436.54 0.137884E+13 0.00 0.169542E+13 3.38     0.00 0.00
Minimum of Months 0.638853E+09 7287.92   159.36 0.301303E+10 0.00 0.365188E+10 1.01 4.72   0.00 0.00
Maximum of Months 0.836526E+11 143742.81   744.00 0.350563E+12 0.00 0.434215E+12 4.57 4.72   0.00 0.00



Table of Contents

Report: BoilerReportMonthly

For: HEATSYS1 BOILER

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO {Maximum} [] BOILER PART LOAD RATIO {TIMESTAMP}
January 0.896645E+11 0.00 744.00 163121.08 02-JAN-16:02 0.00 39.08 60.00 0.36 0.00 0.09 0.43 02-JAN-16:02
February 0.855076E+11 0.00 663.30 158030.82 22-FEB-09:04 0.00 37.91 59.58 0.36 0.00 0.09 0.42 22-FEB-09:04
March 0.981709E+11 0.00 723.71 144112.30 15-MAR-08:07 0.00 36.72 59.06 0.34 0.00 0.10 0.38 15-MAR-08:07
April 0.950044E+11 0.00 605.01 129681.18 18-APR-15:04 0.00 32.61 54.63 0.32 0.00 0.10 0.35 18-APR-15:04
May 0.850980E+11 0.00 515.35 120978.54 28-MAY-08:03 0.00 29.07 49.40 0.27 0.00 0.08 0.32 28-MAY-08:03
June 0.434233E+11 0.00 361.22 100869.71 15-JUN-04:00 0.00 25.82 42.59 0.13 0.00 0.04 0.27 15-JUN-04:00
July 0.162345E+11 0.00 236.04 58593.92 19-JUL-05:00 0.00 25.16 36.26 0.04 0.00 0.02 0.16 19-JUL-05:00
August 0.124870E+11 0.00 190.94 65555.32 01-AUG-08:04 0.00 27.29 36.08 0.03 0.00 0.01 0.17 01-AUG-08:04
September 0.455968E+11 0.00 410.15 106483.59 28-SEP-08:04 0.00 26.64 45.50 0.14 0.00 0.05 0.28 28-SEP-08:04
October 0.119684E+12 0.00 646.84 153595.98 30-OCT-08:05 0.00 31.28 55.71 0.39 0.00 0.12 0.41 30-OCT-08:05
November 0.100789E+12 0.00 705.96 168464.52 17-NOV-09:04 0.00 36.21 59.44 0.37 0.00 0.10 0.45 17-NOV-09:04
December 0.932875E+11 0.00 744.00 167650.85 16-DEC-19:04 0.00 38.59 60.00 0.37 0.00 0.09 0.45 16-DEC-19:04
                           
Annual Sum or Average 0.884948E+12 0.00 6546.53     0.00 32.17 51.47 0.26 0.00 0.07    
Minimum of Months 0.124870E+11 0.00 190.94 58593.92   0.00 25.16 36.08 0.03 0.00 0.01 0.16  
Maximum of Months 0.119684E+12 0.00 744.00 168464.52   0.00 39.08 60.00 0.39 0.00 0.12 0.45  



Table of Contents

Report: DXReportMonthly

For: FLR_3_DOAS COOLING COIL

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 0.00 0.00
February 0.108438E+09 0.00 5.00 0.108438E+09 0.00 0.00 0.00 0.00 9635.08 27-FEB-16:09 9635.08 27-FEB-16:09 0.00 0.00 0.00
March 0.232884E+09 0.00 18.50 0.232884E+09 0.00 0.00 0.00 0.00 12388.66 18-MAR-16:00 12388.66 18-MAR-16:00 0.00 0.00 0.00
April 0.179842E+10 0.00 73.00 0.179842E+10 0.00 0.00 0.00 0.00 18212.60 27-APR-15:02 18212.60 27-APR-15:02 0.00 0.00 0.00
May 0.355559E+10 0.00 145.50 0.343568E+10 0.00 0.00 0.00 0.00 20677.56 05-MAY-18:03 17245.92 05-MAY-15:02 0.00 0.00 0.00
June 0.630895E+10 0.00 267.83 0.630895E+10 0.00 0.00 0.00 0.00 17791.40 28-JUN-15:02 17791.40 28-JUN-15:02 0.00 0.00 0.00
July 0.116585E+11 0.00 399.17 0.109079E+11 0.00 0.00 0.00 0.00 23708.15 15-JUL-18:03 19376.32 24-JUL-15:02 0.00 0.00 0.00
August 0.152262E+11 0.00 453.17 0.141063E+11 0.00 0.00 0.00 0.00 24768.28 30-AUG-12:40 19655.88 29-AUG-15:02 0.00 0.00 0.00
September 0.544189E+10 0.00 235.33 0.511333E+10 0.00 0.00 0.00 0.00 22992.79 14-SEP-12:50 17201.20 12-SEP-15:02 0.00 0.00 0.00
October 0.903800E+09 0.00 70.67 0.903800E+09 0.00 0.00 0.00 0.00 14148.91 04-OCT-15:01 14148.91 04-OCT-15:01 0.00 0.00 0.00
November 0.218215E+09 0.00 15.50 0.196313E+09 0.00 0.00 0.00 0.00 15659.16 04-NOV-15:01 13199.77 04-NOV-15:01 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 0.00 01-DEC-00:03 0.00 0.00 0.00
                               
Annual Sum or Average 0.454529E+11 0.00 1683.67 0.431120E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00 0.00 0.00
Maximum of Months 0.152262E+11 0.00 453.17 0.141063E+11 0.00 0.00 0.00 0.00 24768.28   19655.88   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV WITH REHEAT COOLING COIL

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 0.00 0.00
February 0.177965E+10 0.00 10.83 0.177965E+10 0.00 0.00 0.00 0.00 78982.59 27-FEB-15:00 78982.59 27-FEB-15:00 0.00 0.00 0.00
March 0.394681E+10 0.00 33.33 0.394681E+10 0.00 0.00 0.00 0.00 104148.08 18-MAR-16:10 104148.08 18-MAR-16:10 0.00 0.00 0.00
April 0.284700E+11 0.00 121.33 0.284700E+11 0.00 0.00 0.00 0.00 204755.85 27-APR-18:10 204755.85 27-APR-18:10 0.00 0.00 0.00
May 0.551595E+11 0.00 242.23 0.548024E+11 0.00 0.00 0.00 0.00 206707.51 05-MAY-18:00 176797.98 04-MAY-18:03 0.00 0.00 0.00
June 0.986138E+11 0.00 390.00 0.985076E+11 0.00 0.00 0.00 0.00 209018.02 28-JUN-18:10 209018.02 28-JUN-18:10 0.00 0.00 0.00
July 0.166404E+12 0.00 537.50 0.161479E+12 0.00 0.00 0.00 0.00 264497.45 27-JUL-18:03 235021.89 24-JUL-18:10 0.00 0.00 0.00
August 0.209638E+12 0.00 589.83 0.201849E+12 0.00 0.00 0.00 0.00 286685.50 10-AUG-18:10 249248.48 10-AUG-18:50 0.00 0.00 0.00
September 0.803282E+11 0.00 342.83 0.784403E+11 0.00 0.00 0.00 0.00 198570.87 14-SEP-17:15 180590.89 14-SEP-17:04 0.00 0.00 0.00
October 0.149889E+11 0.00 120.00 0.149718E+11 0.00 0.00 0.00 0.00 124339.99 04-OCT-15:15 124339.99 04-OCT-15:15 0.00 0.00 0.00
November 0.341840E+10 0.00 26.00 0.341840E+10 0.00 0.00 0.00 0.00 102902.96 04-NOV-14:30 102902.96 04-NOV-14:30 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 0.00 01-DEC-00:03 0.00 0.00 0.00
                               
Annual Sum or Average 0.662748E+12 0.00 2413.90 0.647665E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00 0.00 0.00
Maximum of Months 0.209638E+12 0.00 589.83 0.201849E+12 0.00 0.00 0.00 0.00 286685.50   249248.48   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_1_FLR_3 FAN COIL COOLING COIL

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 10367649.58 0.00 2.16 6049164.85 0.00 0.00 0.00 0.00 12746.79 05-JAN-16:01 12746.79 05-JAN-16:01 0.00 0.00 0.00
February 0.220335E+09 0.00 56.06 0.104331E+09 0.00 0.00 0.00 0.00 16838.06 12-FEB-16:01 16838.06 12-FEB-16:01 0.00 0.00 0.00
March 0.784666E+09 0.00 155.67 0.485889E+09 0.00 0.00 0.00 0.00 16838.93 28-MAR-15:01 16838.93 28-MAR-15:01 0.00 0.00 0.00
April 0.228306E+10 0.00 354.28 0.125430E+10 0.00 0.00 0.00 0.00 16833.78 13-APR-18:01 16833.78 13-APR-18:01 0.00 0.00 0.00
May 0.426025E+10 0.00 539.17 0.233314E+10 0.00 0.00 0.00 0.00 16840.09 20-MAY-18:01 16840.09 20-MAY-18:01 0.00 0.00 0.00
June 0.502958E+10 0.00 608.42 0.254741E+10 0.00 0.00 0.00 0.00 16995.33 12-JUN-15:01 15353.49 24-JUN-08:61 0.00 0.00 0.00
July 0.783209E+10 0.00 679.68 0.437955E+10 0.00 0.00 0.00 0.00 16525.47 16-JUL-15:01 15453.84 25-JUL-08:61 0.00 0.00 0.00
August 0.764520E+10 0.00 672.54 0.419540E+10 0.00 0.00 0.00 0.00 17228.09 30-AUG-08:62 15246.36 16-AUG-18:02 0.00 0.00 0.00
September 0.511176E+10 0.00 568.63 0.261404E+10 0.00 0.00 0.00 0.00 16527.19 23-SEP-08:61 15333.88 06-SEP-15:01 0.00 0.00 0.00
October 0.149068E+10 0.00 283.68 0.699597E+09 0.00 0.00 0.00 0.00 16839.66 03-OCT-18:01 16839.66 03-OCT-18:01 0.00 0.00 0.00
November 0.173443E+09 0.00 47.42 66535432.22 0.00 0.00 0.00 0.00 17054.25 05-NOV-15:01 14601.79 04-NOV-18:01 0.00 0.00 0.00
December 24451951.66 0.00 10.59 13301003.62 0.00 0.00 0.00 0.00 14991.55 10-DEC-16:01 14329.93 10-DEC-16:01 0.00 0.00 0.00
                               
Annual Sum or Average 0.348659E+11 0.00 3978.29 0.186996E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 10367649.58 0.00 2.16 6049164.85 0.00 0.00 0.00 0.00 12746.79   12746.79   0.00 0.00 0.00
Maximum of Months 0.783209E+10 0.00 679.68 0.437955E+10 0.00 0.00 0.00 0.00 17228.09   16840.09   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_2_FLR_3 FAN COIL COOLING COIL

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 1356388.22 0.00 0.65 251363.27 0.00 0.00 0.00 0.00 1421.33 20-JAN-16:03 444.61 20-JAN-16:03 0.00 0.00 0.00
February 47358347.19 0.00 16.09 20279881.12 0.00 0.00 0.00 0.00 14008.45 12-FEB-16:01 14008.45 12-FEB-16:01 0.00 0.00 0.00
March 0.257554E+09 0.00 68.74 0.146797E+09 0.00 0.00 0.00 0.00 15102.86 25-MAR-15:01 15102.86 25-MAR-15:01 0.00 0.00 0.00
April 0.125531E+10 0.00 240.46 0.635699E+09 0.00 0.00 0.00 0.00 17674.76 25-APR-17:41 17674.76 25-APR-17:41 0.00 0.00 0.00
May 0.255917E+10 0.00 419.77 0.118639E+10 0.00 0.00 0.00 0.00 15667.62 08-MAY-20:01 14890.85 29-MAY-19:41 0.00 0.00 0.00
June 0.334869E+10 0.00 453.52 0.157633E+10 0.00 0.00 0.00 0.00 16133.74 22-JUN-21:51 14966.44 18-JUN-20:11 0.00 0.00 0.00
July 0.526460E+10 0.00 501.26 0.283200E+10 0.00 0.00 0.00 0.00 17448.54 15-JUL-21:51 15405.46 25-JUL-16:51 0.00 0.00 0.00
August 0.515946E+10 0.00 491.78 0.278664E+10 0.00 0.00 0.00 0.00 16059.82 26-AUG-21:51 15170.31 02-AUG-18:11 0.00 0.00 0.00
September 0.256435E+10 0.00 403.50 0.102994E+10 0.00 0.00 0.00 0.00 16037.85 24-SEP-18:11 14948.38 22-SEP-16:11 0.00 0.00 0.00
October 0.501741E+09 0.00 157.13 0.183897E+09 0.00 0.00 0.00 0.00 15584.61 01-OCT-15:01 14039.66 06-OCT-15:01 0.00 0.00 0.00
November 37433914.07 0.00 13.99 12256786.94 0.00 0.00 0.00 0.00 15313.45 05-NOV-15:01 12777.90 04-NOV-15:01 0.00 0.00 0.00
December 2600525.61 0.00 0.86 912733.46 0.00 0.00 0.00 0.00 4251.77 10-DEC-16:01 3184.94 02-DEC-16:01 0.00 0.00 0.00
                               
Annual Sum or Average 0.209996E+11 0.00 2767.76 0.104114E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 1356388.22 0.00 0.65 251363.27 0.00 0.00 0.00 0.00 1421.33   444.61   0.00 0.00 0.00
Maximum of Months 0.526460E+10 0.00 501.26 0.283200E+10 0.00 0.00 0.00 0.00 17674.76   17674.76   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 0.00 0.00
February 0.398136E+10 0.00 96.44 0.345728E+10 0.00 0.00 0.00 0.00 37380.75 08-FEB-13:40 37380.75 08-FEB-13:40 0.00 0.00 0.00
March 0.119107E+11 0.00 274.68 0.843996E+10 0.00 0.00 0.00 0.00 47719.56 02-MAR-13:00 41340.91 02-MAR-13:00 0.00 0.00 0.00
April 0.193943E+11 0.00 479.09 0.909172E+10 0.00 0.00 0.00 0.00 43942.81 27-APR-13:00 31555.47 27-APR-13:05 0.00 0.00 0.00
May 0.246056E+11 0.00 566.96 0.854564E+10 0.00 0.00 0.00 0.00 43083.26 04-MAY-13:00 29645.07 04-MAY-13:15 0.00 0.00 0.00
June 0.272618E+11 0.00 627.10 0.873149E+10 0.00 0.00 0.00 0.00 32629.85 28-JUN-13:00 17352.10 28-JUN-13:05 0.00 0.00 0.00
July 0.377326E+11 0.00 716.26 0.136682E+11 0.00 0.00 0.00 0.00 41194.86 31-JUL-12:50 26469.83 31-JUL-13:05 0.00 0.00 0.00
August 0.428340E+11 0.00 707.19 0.177077E+11 0.00 0.00 0.00 0.00 51050.96 24-AUG-13:00 40492.40 24-AUG-13:00 0.00 0.00 0.00
September 0.363342E+11 0.00 632.23 0.165338E+11 0.00 0.00 0.00 0.00 54044.42 14-SEP-13:15 46102.34 14-SEP-13:30 0.00 0.00 0.00
October 0.209240E+11 0.00 444.83 0.923041E+10 0.00 0.00 0.00 0.00 54983.46 04-OCT-12:40 50437.90 04-OCT-12:40 0.00 0.00 0.00
November 0.357538E+10 0.00 105.23 0.131882E+10 0.00 0.00 0.00 0.00 44767.79 04-NOV-13:25 30918.43 04-NOV-13:25 0.00 0.00 0.00
December 0.174235E+10 0.00 46.38 0.163441E+10 0.00 0.00 0.00 0.00 33996.75 05-DEC-12:30 33996.75 05-DEC-12:30 0.00 0.00 0.00
                               
Annual Sum or Average 0.230296E+12 0.00 4696.40 0.983594E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00 0.00 0.00
Maximum of Months 0.428340E+11 0.00 716.26 0.177077E+11 0.00 0.00 0.00 0.00 54983.46   50437.90   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.127853E+10 0.00 102.79 0.414090E+09 0.00 0.00 0.00 0.00 63145.74 01-JAN-09:02 63145.74 01-JAN-09:02 0.00 0.00 0.00
February 0.336465E+10 0.00 161.59 0.126126E+10 0.00 0.00 0.00 0.00 76049.44 25-FEB-09:02 70591.02 26-FEB-09:02 0.00 0.00 0.00
March 0.797714E+10 0.00 333.27 0.395410E+10 0.00 0.00 0.00 0.00 76739.66 18-MAR-20:42 76739.66 18-MAR-20:42 0.00 0.00 0.00
April 0.164513E+11 0.00 437.14 0.886768E+10 0.00 0.00 0.00 0.00 78093.30 20-APR-18:01 78093.30 20-APR-18:01 0.00 0.00 0.00
May 0.261891E+11 0.00 462.54 0.154526E+11 0.00 0.00 0.00 0.00 81551.40 06-MAY-21:51 81217.16 14-MAY-21:51 0.00 0.00 0.00
June 0.318460E+11 0.00 422.08 0.199549E+11 0.00 0.00 0.00 0.00 80341.17 12-JUN-18:01 75063.48 11-JUN-21:31 0.00 0.00 0.00
July 0.373715E+11 0.00 432.08 0.239237E+11 0.00 0.00 0.00 0.00 85347.82 26-JUL-21:51 75447.95 28-JUL-21:51 0.00 0.00 0.00
August 0.374883E+11 0.00 428.70 0.223534E+11 0.00 0.00 0.00 0.00 85952.31 26-AUG-21:51 74794.77 01-AUG-20:41 0.00 0.00 0.00
September 0.255177E+11 0.00 401.77 0.131501E+11 0.00 0.00 0.00 0.00 82815.27 15-SEP-21:51 74164.88 02-SEP-15:01 0.00 0.00 0.00
October 0.125895E+11 0.00 437.93 0.533314E+10 0.00 0.00 0.00 0.00 80385.17 01-OCT-15:01 77582.05 02-OCT-18:01 0.00 0.00 0.00
November 0.565920E+10 0.00 254.20 0.198128E+10 0.00 0.00 0.00 0.00 76211.58 04-NOV-15:01 69519.29 05-NOV-18:42 0.00 0.00 0.00
December 0.119099E+10 0.00 110.92 0.461661E+09 0.00 0.00 0.00 0.00 74807.91 03-DEC-09:02 74807.91 03-DEC-09:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.206924E+12 0.00 3985.00 0.117108E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.119099E+10 0.00 102.79 0.414090E+09 0.00 0.00 0.00 0.00 63145.74   63145.74   0.00 0.00 0.00
Maximum of Months 0.374883E+11 0.00 462.54 0.239237E+11 0.00 0.00 0.00 0.00 85952.31   81217.16   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_5_FLR_3 FAN COIL COOLING COIL

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 6761682.63 0.00 4.39 1184824.20 0.00 0.00 0.00 0.00 1572.81 20-JAN-16:02 523.43 20-JAN-16:02 0.00 0.00 0.00
February 0.198050E+09 0.00 47.73 85848414.78 0.00 0.00 0.00 0.00 14498.98 12-FEB-16:01 14498.98 12-FEB-16:01 0.00 0.00 0.00
March 0.751570E+09 0.00 172.28 0.441640E+09 0.00 0.00 0.00 0.00 15212.93 28-MAR-15:01 15212.93 28-MAR-15:01 0.00 0.00 0.00
April 0.236585E+10 0.00 386.37 0.121383E+10 0.00 0.00 0.00 0.00 15022.04 30-APR-15:01 14826.17 13-APR-18:01 0.00 0.00 0.00
May 0.370808E+10 0.00 530.63 0.185995E+10 0.00 0.00 0.00 0.00 15211.59 14-MAY-18:01 15211.59 14-MAY-18:01 0.00 0.00 0.00
June 0.535543E+10 0.00 633.46 0.276254E+10 0.00 0.00 0.00 0.00 14704.87 12-JUN-15:01 13888.10 18-JUN-08:62 0.00 0.00 0.00
July 0.683111E+10 0.00 693.08 0.360811E+10 0.00 0.00 0.00 0.00 15530.27 16-JUL-15:01 13892.49 25-JUL-08:61 0.00 0.00 0.00
August 0.755454E+10 0.00 690.69 0.412684E+10 0.00 0.00 0.00 0.00 15640.78 30-AUG-08:62 13737.05 25-AUG-08:61 0.00 0.00 0.00
September 0.461389E+10 0.00 564.63 0.232205E+10 0.00 0.00 0.00 0.00 15480.96 24-SEP-15:01 13882.77 06-SEP-15:01 0.00 0.00 0.00
October 0.147376E+10 0.00 299.98 0.676987E+09 0.00 0.00 0.00 0.00 15958.36 01-OCT-15:01 14663.00 03-OCT-18:01 0.00 0.00 0.00
November 0.183456E+09 0.00 51.90 57312453.87 0.00 0.00 0.00 0.00 15264.12 05-NOV-15:01 13837.43 04-NOV-15:01 0.00 0.00 0.00
December 55759226.55 0.00 14.45 20551316.70 0.00 0.00 0.00 0.00 11053.03 02-DEC-09:02 10740.82 02-DEC-09:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.330983E+11 0.00 4089.58 0.171769E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 6761682.63 0.00 4.39 1184824.20 0.00 0.00 0.00 0.00 1572.81   523.43   0.00 0.00 0.00
Maximum of Months 0.755454E+10 0.00 693.08 0.412684E+10 0.00 0.00 0.00 0.00 15958.36   15212.93   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_6_FLR_3 FAN COIL COOLING COIL

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 1167286.50 0.00 0.51 218781.49 0.00 0.00 0.00 0.00 1156.48 27-JAN-19:06 267.81 27-JAN-19:06 0.00 0.00 0.00
February 26962366.04 0.00 16.72 9705940.86 0.00 0.00 0.00 0.00 11063.55 27-FEB-16:01 11063.55 27-FEB-16:01 0.00 0.00 0.00
March 0.206922E+09 0.00 66.78 0.117763E+09 0.00 0.00 0.00 0.00 13905.82 25-MAR-08:61 13905.82 25-MAR-08:61 0.00 0.00 0.00
April 0.135549E+10 0.00 270.87 0.663145E+09 0.00 0.00 0.00 0.00 13837.86 25-APR-18:01 13837.86 25-APR-18:01 0.00 0.00 0.00
May 0.239386E+10 0.00 414.66 0.115738E+10 0.00 0.00 0.00 0.00 14551.90 06-MAY-08:51 14196.97 06-MAY-08:51 0.00 0.00 0.00
June 0.386189E+10 0.00 494.40 0.200963E+10 0.00 0.00 0.00 0.00 14030.75 12-JUN-18:01 13395.89 10-JUN-08:51 0.00 0.00 0.00
July 0.469090E+10 0.00 521.80 0.245401E+10 0.00 0.00 0.00 0.00 16658.91 31-JUL-08:32 15704.15 24-JUL-08:32 0.00 0.00 0.00
August 0.516350E+10 0.00 519.84 0.274949E+10 0.00 0.00 0.00 0.00 16865.73 10-AUG-08:32 15328.57 13-AUG-08:32 0.00 0.00 0.00
September 0.243866E+10 0.00 399.68 0.110653E+10 0.00 0.00 0.00 0.00 14461.35 24-SEP-15:01 13943.95 13-SEP-08:51 0.00 0.00 0.00
October 0.532710E+09 0.00 145.58 0.237209E+09 0.00 0.00 0.00 0.00 14522.44 01-OCT-15:01 12282.14 06-OCT-15:01 0.00 0.00 0.00
November 37320501.03 0.00 16.44 10998431.23 0.00 0.00 0.00 0.00 13568.60 05-NOV-15:01 10782.68 04-NOV-15:01 0.00 0.00 0.00
December 2546414.82 0.00 1.52 686184.57 0.00 0.00 0.00 0.00 3338.17 02-DEC-09:02 1868.21 02-DEC-09:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.207119E+11 0.00 2868.80 0.105168E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 1167286.50 0.00 0.51 218781.49 0.00 0.00 0.00 0.00 1156.48   267.81   0.00 0.00 0.00
Maximum of Months 0.516350E+10 0.00 521.80 0.274949E+10 0.00 0.00 0.00 0.00 16865.73   15704.15   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_1_FLR_6 FAN COIL COOLING COIL

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 2192228.88 0.00 1.63 1408926.32 0.00 0.00 0.00 0.00 3274.88 05-JAN-16:01 3261.03 20-JAN-16:02 0.00 0.00 0.00
February 54066503.67 0.00 38.91 27452591.81 0.00 0.00 0.00 0.00 4390.20 12-FEB-16:01 4390.20 12-FEB-16:01 0.00 0.00 0.00
March 0.196455E+09 0.00 121.93 0.128358E+09 0.00 0.00 0.00 0.00 4390.60 28-MAR-15:01 4390.60 28-MAR-15:01 0.00 0.00 0.00
April 0.575201E+09 0.00 292.90 0.340481E+09 0.00 0.00 0.00 0.00 4486.10 30-APR-08:61 4388.60 23-APR-18:02 0.00 0.00 0.00
May 0.107673E+10 0.00 471.18 0.637987E+09 0.00 0.00 0.00 0.00 4390.24 20-MAY-18:01 4390.24 20-MAY-18:01 0.00 0.00 0.00
June 0.126726E+10 0.00 569.16 0.683854E+09 0.00 0.00 0.00 0.00 4408.03 12-JUN-15:01 3990.02 23-JUN-15:01 0.00 0.00 0.00
July 0.199780E+10 0.00 672.27 0.117562E+10 0.00 0.00 0.00 0.00 4418.73 15-JUL-08:61 3886.86 23-JUL-08:62 0.00 0.00 0.00
August 0.190064E+10 0.00 654.63 0.109123E+10 0.00 0.00 0.00 0.00 4592.38 20-AUG-08:61 3978.60 09-AUG-08:61 0.00 0.00 0.00
September 0.123509E+10 0.00 516.75 0.677452E+09 0.00 0.00 0.00 0.00 4564.86 23-SEP-08:61 3987.38 06-SEP-15:01 0.00 0.00 0.00
October 0.336503E+09 0.00 212.19 0.174360E+09 0.00 0.00 0.00 0.00 4544.38 01-OCT-08:62 4390.84 04-OCT-18:01 0.00 0.00 0.00
November 41900589.23 0.00 32.41 18045904.95 0.00 0.00 0.00 0.00 4487.39 05-NOV-15:01 3842.84 04-NOV-18:01 0.00 0.00 0.00
December 5255959.83 0.00 6.88 2943633.72 0.00 0.00 0.00 0.00 4001.85 10-DEC-16:01 3688.94 10-DEC-16:01 0.00 0.00 0.00
                               
Annual Sum or Average 0.868909E+10 0.00 3590.86 0.495920E+10 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 2192228.88 0.00 1.63 1408926.32 0.00 0.00 0.00 0.00 3274.88   3261.03   0.00 0.00 0.00
Maximum of Months 0.199780E+10 0.00 672.27 0.117562E+10 0.00 0.00 0.00 0.00 4592.38   4390.84   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_2_FLR_6 FAN COIL COOLING COIL

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 177959.83 0.00 0.31 32661.36 0.00 0.00 0.00 0.00 346.08 20-JAN-16:05 102.42 20-JAN-16:05 0.00 0.00 0.00
February 9398724.44 0.00 11.79 3815606.67 0.00 0.00 0.00 0.00 3618.99 26-FEB-16:01 3439.78 26-FEB-16:01 0.00 0.00 0.00
March 58883214.72 0.00 49.22 34430336.28 0.00 0.00 0.00 0.00 3893.02 25-MAR-15:01 3893.02 25-MAR-15:01 0.00 0.00 0.00
April 0.310058E+09 0.00 188.86 0.170709E+09 0.00 0.00 0.00 0.00 4574.65 25-APR-17:41 4574.65 25-APR-17:41 0.00 0.00 0.00
May 0.649119E+09 0.00 366.16 0.326146E+09 0.00 0.00 0.00 0.00 4575.60 21-MAY-17:41 4575.60 21-MAY-17:41 0.00 0.00 0.00
June 0.860962E+09 0.00 435.16 0.428483E+09 0.00 0.00 0.00 0.00 4342.25 22-JUN-21:51 3939.29 19-JUN-21:51 0.00 0.00 0.00
July 0.139279E+10 0.00 510.12 0.772536E+09 0.00 0.00 0.00 0.00 4626.26 26-JUL-21:51 4064.16 19-JUL-21:51 0.00 0.00 0.00
August 0.130159E+10 0.00 488.65 0.735660E+09 0.00 0.00 0.00 0.00 4300.23 11-AUG-21:51 3969.00 06-AUG-21:51 0.00 0.00 0.00
September 0.595839E+09 0.00 361.45 0.253485E+09 0.00 0.00 0.00 0.00 4240.37 13-SEP-21:51 3861.63 22-SEP-16:11 0.00 0.00 0.00
October 93671335.49 0.00 98.22 37543185.37 0.00 0.00 0.00 0.00 4088.31 01-OCT-08:62 3612.76 07-OCT-15:01 0.00 0.00 0.00
November 7750853.19 0.00 8.06 2571218.02 0.00 0.00 0.00 0.00 4046.14 05-NOV-15:01 3291.75 04-NOV-15:01 0.00 0.00 0.00
December 187484.93 0.00 0.31 67757.81 0.00 0.00 0.00 0.00 323.64 29-DEC-19:06 244.15 02-DEC-19:06 0.00 0.00 0.00
                               
Annual Sum or Average 0.528043E+10 0.00 2518.31 0.276548E+10 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 177959.83 0.00 0.31 32661.36 0.00 0.00 0.00 0.00 323.64   102.42   0.00 0.00 0.00
Maximum of Months 0.139279E+10 0.00 510.12 0.772536E+09 0.00 0.00 0.00 0.00 4626.26   4575.60   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.455824E+09 0.00 63.71 0.203203E+09 0.00 0.00 0.00 0.00 20036.61 05-JAN-16:01 20036.61 05-JAN-16:01 0.00 0.00 0.00
February 0.176052E+10 0.00 179.71 0.961059E+09 0.00 0.00 0.00 0.00 22633.93 28-FEB-16:01 21449.79 26-FEB-16:01 0.00 0.00 0.00
March 0.302958E+10 0.00 307.79 0.191849E+10 0.00 0.00 0.00 0.00 24114.24 25-MAR-15:01 24114.24 25-MAR-15:01 0.00 0.00 0.00
April 0.469085E+10 0.00 450.04 0.245489E+10 0.00 0.00 0.00 0.00 24464.34 30-APR-15:01 23870.08 13-APR-18:01 0.00 0.00 0.00
May 0.599950E+10 0.00 555.03 0.298076E+10 0.00 0.00 0.00 0.00 24109.44 14-MAY-18:01 24109.44 14-MAY-18:01 0.00 0.00 0.00
June 0.681200E+10 0.00 618.41 0.311330E+10 0.00 0.00 0.00 0.00 24208.15 12-JUN-15:01 22043.94 05-JUN-15:01 0.00 0.00 0.00
July 0.956897E+10 0.00 675.13 0.472205E+10 0.00 0.00 0.00 0.00 24540.83 16-JUL-15:01 21998.97 25-JUL-08:61 0.00 0.00 0.00
August 0.107165E+11 0.00 672.83 0.568579E+10 0.00 0.00 0.00 0.00 23877.42 29-AUG-08:62 21932.84 02-AUG-18:01 0.00 0.00 0.00
September 0.874662E+10 0.00 588.70 0.487032E+10 0.00 0.00 0.00 0.00 23675.97 16-SEP-15:01 22012.09 22-SEP-18:01 0.00 0.00 0.00
October 0.467255E+10 0.00 441.23 0.253512E+10 0.00 0.00 0.00 0.00 24114.70 04-OCT-18:01 24114.70 04-OCT-18:01 0.00 0.00 0.00
November 0.123165E+10 0.00 152.88 0.559186E+09 0.00 0.00 0.00 0.00 23020.96 05-NOV-08:62 21653.30 02-NOV-15:01 0.00 0.00 0.00
December 0.971341E+09 0.00 104.50 0.512672E+09 0.00 0.00 0.00 0.00 21524.65 10-DEC-16:01 21524.65 10-DEC-16:01 0.00 0.00 0.00
                               
Annual Sum or Average 0.586559E+11 0.00 4809.96 0.305168E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.455824E+09 0.00 63.71 0.203203E+09 0.00 0.00 0.00 0.00 20036.61   20036.61   0.00 0.00 0.00
Maximum of Months 0.107165E+11 0.00 675.13 0.568579E+10 0.00 0.00 0.00 0.00 24540.83   24114.70   0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 381.12 226.72 154.40 337.78 510.06 0.00 0.00 0.00
February 586.49 363.88 222.60 596.42 447.88 0.00 0.00 0.00
March 622.14 328.93 293.21 670.22 372.79 0.00 0.00 0.00
April 657.40 282.14 375.26 757.86 299.99 0.00 0.00 0.00
May 612.50 186.73 425.76 725.14 238.83 0.00 0.00 0.00
June 554.17 148.32 405.85 678.90 176.85 0.00 0.00 0.00
July 602.08 218.62 383.46 803.01 156.93 0.00 0.00 0.00
August 641.87 294.94 346.93 876.28 151.61 0.00 0.00 0.00
September 711.91 389.37 322.54 903.95 224.72 0.00 0.00 0.00
October 643.99 394.27 249.72 744.27 315.16 0.00 0.00 0.00
November 385.41 220.61 164.80 373.43 403.85 0.00 0.00 0.00
December 403.36 260.85 142.51 395.63 512.02 0.00 0.00 0.00
                 
Annual Sum or Average 566.59 275.74 290.86 655.47 316.94 0.00 0.00 0.00
Minimum of Months 381.12 148.32 142.51 337.78 151.61 0.00 0.00 0.00
Maximum of Months 711.91 394.27 425.76 903.95 512.02 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CAFE_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1073.21 638.43 434.78 936.50 1482.97 0.00 0.00 0.00
February 1651.51 1024.67 626.84 1656.80 1315.40 0.00 0.00 0.00
March 1751.91 926.24 825.67 1862.36 1116.51 0.00 0.00 0.00
April 1851.19 794.48 1056.71 2102.59 910.80 0.00 0.00 0.00
May 1724.75 525.83 1198.93 2007.99 735.25 0.00 0.00 0.00
June 1560.51 417.65 1142.85 1871.57 560.95 0.00 0.00 0.00
July 1695.42 615.61 1079.81 2226.63 497.33 0.00 0.00 0.00
August 1807.46 830.52 976.94 2435.47 484.34 0.00 0.00 0.00
September 2004.70 1096.43 908.26 2516.26 697.80 0.00 0.00 0.00
October 1813.42 1110.24 703.18 2068.81 961.74 0.00 0.00 0.00
November 1085.28 621.22 464.06 1034.07 1194.93 0.00 0.00 0.00
December 1135.85 734.54 401.31 1099.33 1493.07 0.00 0.00 0.00
                 
Annual Sum or Average 1595.49 776.46 819.03 1818.84 952.53 0.00 0.00 0.00
Minimum of Months 1073.21 417.65 401.31 936.50 484.34 0.00 0.00 0.00
Maximum of Months 2004.70 1110.24 1198.93 2516.26 1493.07 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: LOBBY_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1394.16 829.35 564.80 1224.42 2057.81 0.00 0.00 0.00
February 2145.41 1331.11 814.30 2176.56 1814.82 0.00 0.00 0.00
March 2275.84 1203.24 1072.60 2450.89 1546.67 0.00 0.00 0.00
April 2404.80 1032.08 1372.72 2768.32 1260.23 0.00 0.00 0.00
May 2240.55 683.08 1557.47 2639.00 1026.63 0.00 0.00 0.00
June 2027.19 542.56 1484.63 2453.89 786.67 0.00 0.00 0.00
July 2202.45 799.71 1402.74 2931.38 692.15 0.00 0.00 0.00
August 2348.00 1078.89 1269.10 3208.13 668.38 0.00 0.00 0.00
September 2604.21 1424.33 1179.88 3312.20 964.49 0.00 0.00 0.00
October 2355.74 1442.27 913.47 2719.76 1336.74 0.00 0.00 0.00
November 1409.84 807.00 602.84 1349.03 1673.41 0.00 0.00 0.00
December 1475.53 954.20 521.33 1440.04 2072.48 0.00 0.00 0.00
                 
Annual Sum or Average 2072.64 1008.67 1063.97 2390.33 1322.70 0.00 0.00 0.00
Minimum of Months 1394.16 542.56 521.33 1224.42 668.38 0.00 0.00 0.00
Maximum of Months 2604.21 1442.27 1557.47 3312.20 2072.48 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 75.35 44.83 30.53 67.51 102.46 0.00 0.00 0.00
February 115.96 71.95 44.01 118.59 89.93 0.00 0.00 0.00
March 123.01 65.03 57.97 132.83 75.03 0.00 0.00 0.00
April 129.98 55.78 74.20 148.89 60.84 0.00 0.00 0.00
May 121.10 36.92 84.18 141.36 48.41 0.00 0.00 0.00
June 109.57 29.33 80.24 132.14 35.17 0.00 0.00 0.00
July 119.04 43.22 75.82 157.94 30.07 0.00 0.00 0.00
August 126.91 58.31 68.60 173.72 27.95 0.00 0.00 0.00
September 140.76 76.98 63.77 179.81 43.58 0.00 0.00 0.00
October 127.33 77.95 49.37 147.73 62.34 0.00 0.00 0.00
November 76.20 43.62 32.58 74.55 80.54 0.00 0.00 0.00
December 79.75 51.57 28.18 79.12 101.98 0.00 0.00 0.00
                 
Annual Sum or Average 112.03 54.52 57.51 129.56 63.06 0.00 0.00 0.00
Minimum of Months 75.35 29.33 28.18 67.51 27.95 0.00 0.00 0.00
Maximum of Months 140.76 77.95 84.18 179.81 102.46 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_3_WALL_WEST_WINDOW

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 54.10 16.09 38.01 22.20 207.29 0.00 0.00 0.00
February 96.50 36.23 60.27 65.55 179.62 0.00 0.00 0.00
March 135.19 45.71 89.48 113.71 142.95 0.00 0.00 0.00
April 205.42 78.44 126.98 211.05 110.90 0.00 0.00 0.00
May 264.84 107.82 157.02 300.78 87.51 0.00 0.00 0.00
June 254.15 98.49 155.66 297.94 63.59 0.00 0.00 0.00
July 314.18 165.10 149.08 402.41 54.51 0.00 0.00 0.00
August 260.02 132.62 127.39 338.12 51.38 0.00 0.00 0.00
September 212.43 102.19 110.24 253.46 81.31 0.00 0.00 0.00
October 121.48 49.94 71.54 113.95 120.27 0.00 0.00 0.00
November 60.16 17.10 43.06 33.73 159.56 0.00 0.00 0.00
December 50.78 17.63 33.15 26.78 205.09 0.00 0.00 0.00
                 
Annual Sum or Average 169.55 72.56 96.99 182.40 121.72 0.00 0.00 0.00
Minimum of Months 50.78 16.09 33.15 22.20 51.38 0.00 0.00 0.00
Maximum of Months 314.18 165.10 157.02 402.41 207.29 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 16.99 0.00 16.99 0.54 114.61 0.00 0.00 0.00
February 26.44 0.00 26.44 5.16 99.24 0.00 0.00 0.00
March 38.96 0.00 38.96 17.23 77.79 0.00 0.00 0.00
April 55.32 0.34 54.98 37.42 59.68 0.00 0.00 0.00
May 70.97 2.13 68.84 58.98 46.56 0.00 0.00 0.00
June 74.69 5.00 69.70 70.07 33.86 0.00 0.00 0.00
July 71.09 5.72 65.37 74.63 30.01 0.00 0.00 0.00
August 57.63 1.73 55.90 63.57 27.93 0.00 0.00 0.00
September 44.60 0.03 44.57 36.53 45.71 0.00 0.00 0.00
October 30.54 0.00 30.54 15.28 65.17 0.00 0.00 0.00
November 19.24 0.00 19.24 3.13 87.04 0.00 0.00 0.00
December 14.44 0.00 14.44 0.28 111.69 0.00 0.00 0.00
                 
Annual Sum or Average 43.49 1.26 42.24 32.07 66.45 0.00 0.00 0.00
Minimum of Months 14.44 0.00 14.44 0.28 27.93 0.00 0.00 0.00
Maximum of Months 74.69 5.72 69.70 74.63 114.61 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_3_WALL_WEST_WINDOW

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 54.10 16.09 38.01 23.74 205.23 0.00 0.00 0.00
February 96.50 36.23 60.27 68.60 176.86 0.00 0.00 0.00
March 135.19 45.71 89.48 117.42 141.00 0.00 0.00 0.00
April 205.42 78.44 126.98 213.83 110.35 0.00 0.00 0.00
May 264.84 107.82 157.02 299.30 89.13 0.00 0.00 0.00
June 254.15 98.49 155.66 295.12 66.33 0.00 0.00 0.00
July 314.18 165.10 149.08 397.77 58.84 0.00 0.00 0.00
August 260.02 132.62 127.39 336.89 54.55 0.00 0.00 0.00
September 212.43 102.19 110.24 253.41 83.59 0.00 0.00 0.00
October 121.48 49.94 71.54 117.29 118.61 0.00 0.00 0.00
November 60.16 17.10 43.06 35.50 157.67 0.00 0.00 0.00
December 50.78 17.63 33.15 28.54 202.78 0.00 0.00 0.00
                 
Annual Sum or Average 169.55 72.56 96.99 183.03 121.82 0.00 0.00 0.00
Minimum of Months 50.78 16.09 33.15 23.74 54.55 0.00 0.00 0.00
Maximum of Months 314.18 165.10 157.02 397.77 205.23 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 60.27 35.85 24.42 51.65 88.32 0.00 0.00 0.00
February 92.75 57.55 35.20 87.86 89.57 0.00 0.00 0.00
March 98.39 52.02 46.37 96.33 85.78 0.00 0.00 0.00
April 103.96 44.62 59.34 107.18 71.55 0.00 0.00 0.00
May 96.86 29.53 67.33 101.17 59.09 0.00 0.00 0.00
June 87.64 23.46 64.18 92.49 46.63 0.00 0.00 0.00
July 95.22 34.57 60.64 113.99 41.67 0.00 0.00 0.00
August 101.51 46.64 54.87 126.47 40.53 0.00 0.00 0.00
September 112.58 61.58 51.01 132.81 55.81 0.00 0.00 0.00
October 101.84 62.35 39.49 107.77 76.20 0.00 0.00 0.00
November 60.95 34.89 26.06 52.58 88.67 0.00 0.00 0.00
December 63.79 41.25 22.54 59.39 94.90 0.00 0.00 0.00
                 
Annual Sum or Average 89.60 43.61 46.00 94.17 69.78 0.00 0.00 0.00
Minimum of Months 60.27 23.46 22.54 51.65 40.53 0.00 0.00 0.00
Maximum of Months 112.58 62.35 67.33 132.81 94.90 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 13.60 0.00 13.60 0.26 97.33 0.00 0.00 0.00
February 21.15 0.00 21.15 3.57 83.18 0.00 0.00 0.00
March 31.17 0.00 31.17 13.35 64.37 0.00 0.00 0.00
April 44.26 0.27 43.99 30.89 48.17 0.00 0.00 0.00
May 56.79 1.71 55.08 50.28 36.54 0.00 0.00 0.00
June 59.76 4.00 55.77 59.42 26.22 0.00 0.00 0.00
July 56.88 4.58 52.30 64.59 22.19 0.00 0.00 0.00
August 46.11 1.38 44.72 54.50 20.82 0.00 0.00 0.00
September 35.69 0.03 35.66 31.56 34.99 0.00 0.00 0.00
October 24.44 0.00 24.44 12.20 53.47 0.00 0.00 0.00
November 15.39 0.00 15.39 2.09 73.94 0.00 0.00 0.00
December 11.55 0.00 11.55 0.11 94.80 0.00 0.00 0.00
                 
Annual Sum or Average 34.80 1.00 33.80 27.05 54.53 0.00 0.00 0.00
Minimum of Months 11.55 0.00 11.55 0.11 20.82 0.00 0.00 0.00
Maximum of Months 59.76 4.58 55.77 64.59 97.33 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_5_FLR_3_WALL_EAST_WINDOW

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 50.77 12.72 38.05 16.37 205.38 0.00 0.00 0.00
February 93.53 33.13 60.40 58.26 176.16 0.00 0.00 0.00
March 140.17 50.83 89.34 115.57 138.21 0.00 0.00 0.00
April 216.49 89.84 126.65 221.30 106.50 0.00 0.00 0.00
May 230.51 80.26 150.25 251.80 84.87 0.00 0.00 0.00
June 275.89 120.08 155.81 326.46 60.99 0.00 0.00 0.00
July 257.29 115.68 141.62 320.87 50.05 0.00 0.00 0.00
August 252.57 126.34 126.23 324.71 47.89 0.00 0.00 0.00
September 187.04 86.42 100.63 213.79 77.72 0.00 0.00 0.00
October 122.30 52.26 70.05 112.51 117.06 0.00 0.00 0.00
November 59.85 16.95 42.90 31.53 157.34 0.00 0.00 0.00
December 48.96 15.74 33.22 21.46 201.47 0.00 0.00 0.00
                 
Annual Sum or Average 161.58 66.83 94.75 168.46 118.36 0.00 0.00 0.00
Minimum of Months 48.96 12.72 33.22 16.37 47.89 0.00 0.00 0.00
Maximum of Months 275.89 126.34 155.81 326.46 205.38 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 75.35 44.83 30.53 67.48 102.32 0.00 0.00 0.00
February 115.96 71.95 44.01 118.31 89.72 0.00 0.00 0.00
March 123.01 65.03 57.97 132.09 74.83 0.00 0.00 0.00
April 129.98 55.78 74.20 147.78 60.63 0.00 0.00 0.00
May 121.10 36.92 84.18 141.24 47.78 0.00 0.00 0.00
June 109.57 29.33 80.24 131.09 34.87 0.00 0.00 0.00
July 119.04 43.22 75.82 157.99 29.26 0.00 0.00 0.00
August 126.91 58.31 68.60 173.21 27.54 0.00 0.00 0.00
September 140.76 76.98 63.77 179.67 42.85 0.00 0.00 0.00
October 127.33 77.95 49.37 147.25 62.05 0.00 0.00 0.00
November 76.20 43.62 32.58 74.42 80.41 0.00 0.00 0.00
December 79.75 51.57 28.18 79.08 101.82 0.00 0.00 0.00
                 
Annual Sum or Average 112.03 54.52 57.51 129.18 62.71 0.00 0.00 0.00
Minimum of Months 75.35 29.33 28.18 67.48 27.54 0.00 0.00 0.00
Maximum of Months 140.76 77.95 84.18 179.67 102.32 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_6_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 16.99 0.00 16.99 0.52 114.51 0.00 0.00 0.00
February 26.44 0.00 26.44 5.05 99.09 0.00 0.00 0.00
March 38.96 0.00 38.96 16.59 77.64 0.00 0.00 0.00
April 55.32 0.34 54.98 36.41 59.56 0.00 0.00 0.00
May 70.97 2.13 68.84 59.73 45.48 0.00 0.00 0.00
June 74.69 5.00 69.70 69.56 33.19 0.00 0.00 0.00
July 71.09 5.72 65.37 75.78 28.34 0.00 0.00 0.00
August 57.63 1.73 55.90 62.79 27.10 0.00 0.00 0.00
September 44.60 0.03 44.57 36.86 44.12 0.00 0.00 0.00
October 30.54 0.00 30.54 14.80 64.70 0.00 0.00 0.00
November 19.24 0.00 19.24 3.01 86.84 0.00 0.00 0.00
December 14.44 0.00 14.44 0.25 111.54 0.00 0.00 0.00
                 
Annual Sum or Average 43.49 1.26 42.24 31.95 65.85 0.00 0.00 0.00
Minimum of Months 14.44 0.00 14.44 0.25 27.10 0.00 0.00 0.00
Maximum of Months 74.69 5.72 69.70 75.78 114.51 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_6_FLR_3_WALL_EAST_WINDOW

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 50.77 12.72 38.05 16.98 202.39 0.00 0.00 0.00
February 93.53 33.13 60.40 60.28 172.08 0.00 0.00 0.00
March 140.17 50.83 89.34 119.08 135.89 0.00 0.00 0.00
April 216.49 89.84 126.65 224.03 105.71 0.00 0.00 0.00
May 230.51 80.26 150.25 252.49 85.73 0.00 0.00 0.00
June 275.89 120.08 155.81 325.40 63.40 0.00 0.00 0.00
July 257.29 115.68 141.62 318.99 53.13 0.00 0.00 0.00
August 252.57 126.34 126.23 323.33 50.50 0.00 0.00 0.00
September 187.04 86.42 100.63 215.38 78.72 0.00 0.00 0.00
October 122.30 52.26 70.05 115.85 114.97 0.00 0.00 0.00
November 59.85 16.95 42.90 32.71 154.67 0.00 0.00 0.00
December 48.96 15.74 33.22 22.24 198.09 0.00 0.00 0.00
                 
Annual Sum or Average 161.58 66.83 94.75 169.45 117.69 0.00 0.00 0.00
Minimum of Months 48.96 12.72 33.22 16.98 50.50 0.00 0.00 0.00
Maximum of Months 275.89 126.34 155.81 325.40 202.39 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 21.52 0.00 21.52 0.39 157.32 0.00 0.00 0.00
February 33.48 0.00 33.48 5.60 134.39 0.00 0.00 0.00
March 49.34 0.00 49.34 21.09 103.68 0.00 0.00 0.00
April 70.06 0.43 69.63 48.84 78.89 0.00 0.00 0.00
May 89.88 2.70 87.19 78.78 62.00 0.00 0.00 0.00
June 94.60 6.33 88.27 92.79 45.25 0.00 0.00 0.00
July 90.04 7.25 82.79 99.72 39.69 0.00 0.00 0.00
August 72.98 2.19 70.79 82.61 38.75 0.00 0.00 0.00
September 56.49 0.04 56.45 47.88 61.20 0.00 0.00 0.00
October 38.68 0.00 38.68 18.57 88.10 0.00 0.00 0.00
November 24.36 0.00 24.36 3.37 118.73 0.00 0.00 0.00
December 18.29 0.00 18.29 0.15 153.28 0.00 0.00 0.00
                 
Annual Sum or Average 55.08 1.59 53.49 41.87 89.90 0.00 0.00 0.00
Minimum of Months 18.29 0.00 18.29 0.15 38.75 0.00 0.00 0.00
Maximum of Months 94.60 7.25 88.27 99.72 157.32 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 7.93 0.00 7.93 0.14 57.99 0.00 0.00 0.00
February 12.34 0.00 12.34 2.06 49.54 0.00 0.00 0.00
March 18.19 0.00 18.19 7.77 38.22 0.00 0.00 0.00
April 25.83 0.16 25.67 18.01 29.08 0.00 0.00 0.00
May 33.14 0.99 32.14 29.04 22.86 0.00 0.00 0.00
June 34.87 2.33 32.54 34.21 16.68 0.00 0.00 0.00
July 33.19 2.67 30.52 36.76 14.63 0.00 0.00 0.00
August 26.90 0.81 26.10 30.45 14.28 0.00 0.00 0.00
September 20.82 0.02 20.81 17.65 22.56 0.00 0.00 0.00
October 14.26 0.00 14.26 6.85 32.48 0.00 0.00 0.00
November 8.98 0.00 8.98 1.24 43.77 0.00 0.00 0.00
December 6.74 0.00 6.74 0.05 56.50 0.00 0.00 0.00
                 
Annual Sum or Average 20.31 0.59 19.72 15.44 33.14 0.00 0.00 0.00
Minimum of Months 6.74 0.00 6.74 0.05 14.28 0.00 0.00 0.00
Maximum of Months 34.87 2.67 32.54 36.76 57.99 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 35.16 20.92 14.24 30.98 50.76 0.00 0.00 0.00
February 54.11 33.57 20.54 55.39 43.88 0.00 0.00 0.00
March 57.40 30.35 27.05 62.59 36.32 0.00 0.00 0.00
April 60.65 26.03 34.62 70.65 29.45 0.00 0.00 0.00
May 56.51 17.23 39.28 67.15 24.18 0.00 0.00 0.00
June 51.12 13.68 37.44 62.57 18.16 0.00 0.00 0.00
July 55.54 20.17 35.38 74.60 15.96 0.00 0.00 0.00
August 59.22 27.21 32.01 81.62 15.26 0.00 0.00 0.00
September 65.68 35.92 29.76 84.59 22.23 0.00 0.00 0.00
October 59.41 36.37 23.04 69.53 30.63 0.00 0.00 0.00
November 35.56 20.35 15.20 34.68 39.75 0.00 0.00 0.00
December 37.21 24.06 13.15 36.74 50.53 0.00 0.00 0.00
                 
Annual Sum or Average 52.27 25.44 26.83 60.95 31.37 0.00 0.00 0.00
Minimum of Months 35.16 13.68 13.15 30.98 15.26 0.00 0.00 0.00
Maximum of Months 65.68 36.37 39.28 84.59 50.76 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 95.43 56.77 38.66 84.08 137.77 0.00 0.00 0.00
February 146.85 91.12 55.74 150.33 119.09 0.00 0.00 0.00
March 155.78 82.36 73.42 169.89 98.58 0.00 0.00 0.00
April 164.61 70.65 93.96 191.76 79.94 0.00 0.00 0.00
May 153.37 46.76 106.61 182.26 65.62 0.00 0.00 0.00
June 138.76 37.14 101.62 169.83 49.30 0.00 0.00 0.00
July 150.76 54.74 96.02 202.49 43.33 0.00 0.00 0.00
August 160.72 73.85 86.87 221.54 41.41 0.00 0.00 0.00
September 178.26 97.50 80.76 229.60 60.34 0.00 0.00 0.00
October 161.25 98.72 62.53 188.71 83.14 0.00 0.00 0.00
November 96.50 55.24 41.26 94.12 107.88 0.00 0.00 0.00
December 101.00 65.32 35.69 99.73 137.16 0.00 0.00 0.00
                 
Annual Sum or Average 141.87 69.04 72.83 165.42 85.14 0.00 0.00 0.00
Minimum of Months 95.43 37.14 35.69 84.08 41.41 0.00 0.00 0.00
Maximum of Months 178.26 98.72 106.61 229.60 137.77 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 75.35 44.83 30.53 67.61 101.75 0.00 0.00 0.00
February 115.96 71.95 44.01 118.30 89.37 0.00 0.00 0.00
March 123.01 65.03 57.97 132.14 74.63 0.00 0.00 0.00
April 129.98 55.78 74.20 147.59 60.76 0.00 0.00 0.00
May 121.10 36.92 84.18 139.84 48.28 0.00 0.00 0.00
June 109.57 29.33 80.24 130.59 35.01 0.00 0.00 0.00
July 119.04 43.22 75.82 156.33 29.91 0.00 0.00 0.00
August 126.91 58.31 68.60 172.42 27.60 0.00 0.00 0.00
September 140.76 76.98 63.77 178.89 43.11 0.00 0.00 0.00
October 127.33 77.95 49.37 147.05 61.73 0.00 0.00 0.00
November 76.20 43.62 32.58 74.50 79.80 0.00 0.00 0.00
December 79.75 51.57 28.18 79.14 101.08 0.00 0.00 0.00
                 
Annual Sum or Average 112.03 54.52 57.51 128.74 62.62 0.00 0.00 0.00
Minimum of Months 75.35 29.33 28.18 67.61 27.60 0.00 0.00 0.00
Maximum of Months 140.76 77.95 84.18 178.89 101.75 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_6_WALL_WEST_WINDOW

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 54.10 16.09 38.01 22.48 205.41 0.00 0.00 0.00
February 96.50 36.23 60.27 65.33 178.10 0.00 0.00 0.00
March 135.19 45.71 89.48 112.83 141.86 0.00 0.00 0.00
April 205.42 78.44 126.98 208.69 110.57 0.00 0.00 0.00
May 264.84 107.82 157.02 297.56 87.12 0.00 0.00 0.00
June 254.15 98.49 155.66 294.65 63.16 0.00 0.00 0.00
July 314.18 165.10 149.08 398.76 54.06 0.00 0.00 0.00
August 260.02 132.62 127.39 335.51 50.61 0.00 0.00 0.00
September 212.43 102.19 110.24 251.74 80.27 0.00 0.00 0.00
October 121.48 49.94 71.54 113.18 118.80 0.00 0.00 0.00
November 60.16 17.10 43.06 33.84 157.66 0.00 0.00 0.00
December 50.78 17.63 33.15 26.91 202.64 0.00 0.00 0.00
                 
Annual Sum or Average 169.55 72.56 96.99 180.88 120.58 0.00 0.00 0.00
Minimum of Months 50.78 16.09 33.15 22.48 50.61 0.00 0.00 0.00
Maximum of Months 314.18 165.10 157.02 398.76 205.41 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 16.99 0.00 16.99 0.61 113.36 0.00 0.00 0.00
February 26.44 0.00 26.44 5.30 98.34 0.00 0.00 0.00
March 38.96 0.00 38.96 17.28 77.17 0.00 0.00 0.00
April 55.32 0.34 54.98 36.94 59.53 0.00 0.00 0.00
May 70.97 2.13 68.84 57.70 46.81 0.00 0.00 0.00
June 74.69 5.00 69.70 68.57 34.19 0.00 0.00 0.00
July 71.09 5.72 65.37 73.02 30.59 0.00 0.00 0.00
August 57.63 1.73 55.90 62.83 27.97 0.00 0.00 0.00
September 44.60 0.03 44.57 36.00 45.85 0.00 0.00 0.00
October 30.54 0.00 30.54 15.48 64.28 0.00 0.00 0.00
November 19.24 0.00 19.24 3.25 85.82 0.00 0.00 0.00
December 14.44 0.00 14.44 0.33 110.13 0.00 0.00 0.00
                 
Annual Sum or Average 43.49 1.26 42.24 31.61 66.01 0.00 0.00 0.00
Minimum of Months 14.44 0.00 14.44 0.33 27.97 0.00 0.00 0.00
Maximum of Months 74.69 5.72 69.70 73.02 113.36 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_6_WALL_WEST_WINDOW

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 54.10 16.09 38.01 24.07 203.51 0.00 0.00 0.00
February 96.50 36.23 60.27 68.73 175.34 0.00 0.00 0.00
March 135.19 45.71 89.48 116.89 139.79 0.00 0.00 0.00
April 205.42 78.44 126.98 211.57 110.14 0.00 0.00 0.00
May 264.84 107.82 157.02 295.36 89.59 0.00 0.00 0.00
June 254.15 98.49 155.66 290.88 66.93 0.00 0.00 0.00
July 314.18 165.10 149.08 392.93 59.87 0.00 0.00 0.00
August 260.02 132.62 127.39 333.93 54.54 0.00 0.00 0.00
September 212.43 102.19 110.24 251.24 83.56 0.00 0.00 0.00
October 121.48 49.94 71.54 116.91 117.01 0.00 0.00 0.00
November 60.16 17.10 43.06 35.81 155.71 0.00 0.00 0.00
December 50.78 17.63 33.15 28.88 200.36 0.00 0.00 0.00
                 
Annual Sum or Average 169.55 72.56 96.99 181.34 121.11 0.00 0.00 0.00
Minimum of Months 50.78 16.09 33.15 24.07 54.54 0.00 0.00 0.00
Maximum of Months 314.18 165.10 157.02 392.93 203.51 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 110.51 65.74 44.77 94.98 155.59 0.00 0.00 0.00
February 170.06 105.52 64.55 168.51 136.58 0.00 0.00 0.00
March 180.40 95.38 85.02 189.89 113.49 0.00 0.00 0.00
April 190.63 81.81 108.82 214.12 90.67 0.00 0.00 0.00
May 177.61 54.15 123.46 205.24 70.60 0.00 0.00 0.00
June 160.69 43.01 117.69 192.34 50.74 0.00 0.00 0.00
July 174.59 63.39 111.20 231.30 42.37 0.00 0.00 0.00
August 186.12 85.52 100.60 253.83 39.54 0.00 0.00 0.00
September 206.43 112.91 93.53 261.36 63.37 0.00 0.00 0.00
October 186.74 114.33 72.41 211.95 94.08 0.00 0.00 0.00
November 111.76 63.97 47.79 105.73 122.62 0.00 0.00 0.00
December 116.96 75.64 41.33 112.33 154.63 0.00 0.00 0.00
                 
Annual Sum or Average 164.30 79.96 84.34 186.88 94.32 0.00 0.00 0.00
Minimum of Months 110.51 43.01 41.33 94.98 39.54 0.00 0.00 0.00
Maximum of Months 206.43 114.33 123.46 261.36 155.59 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: BANQUET_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 118.94 0.00 118.94 0.51 1002.39 0.00 0.00 0.00
February 185.07 0.00 185.07 18.70 868.16 0.00 0.00 0.00
March 272.70 0.00 272.70 83.59 679.19 0.00 0.00 0.00
April 387.23 2.38 384.85 219.62 515.73 0.00 0.00 0.00
May 496.80 14.92 481.88 378.21 393.01 0.00 0.00 0.00
June 522.84 34.98 487.86 452.63 287.79 0.00 0.00 0.00
July 497.64 40.06 457.58 502.37 248.59 0.00 0.00 0.00
August 403.39 12.11 391.28 416.97 242.72 0.00 0.00 0.00
September 312.22 0.23 311.99 230.69 382.98 0.00 0.00 0.00
October 213.77 0.00 213.77 74.74 582.09 0.00 0.00 0.00
November 134.66 0.00 134.66 9.37 785.31 0.00 0.00 0.00
December 101.07 0.00 101.07 0.13 979.37 0.00 0.00 0.00
                 
Annual Sum or Average 304.45 8.79 295.66 200.12 579.21 0.00 0.00 0.00
Minimum of Months 101.07 0.00 101.07 0.13 242.72 0.00 0.00 0.00
Maximum of Months 522.84 40.06 487.86 502.37 1002.39 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: DINING_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 118.94 0.00 118.94 0.26 1034.72 0.00 0.00 0.00
February 185.07 0.00 185.07 16.38 896.97 0.00 0.00 0.00
March 272.70 0.00 272.70 75.82 699.37 0.00 0.00 0.00
April 387.23 2.38 384.85 208.97 529.62 0.00 0.00 0.00
May 496.80 14.92 481.88 367.27 402.57 0.00 0.00 0.00
June 522.84 34.98 487.86 441.43 295.19 0.00 0.00 0.00
July 497.64 40.06 457.58 492.82 255.34 0.00 0.00 0.00
August 403.39 12.11 391.28 407.71 250.12 0.00 0.00 0.00
September 312.22 0.23 311.99 222.41 394.00 0.00 0.00 0.00
October 213.77 0.00 213.77 67.90 601.10 0.00 0.00 0.00
November 134.66 0.00 134.66 7.82 813.57 0.00 0.00 0.00
December 101.07 0.00 101.07 0.07 1011.20 0.00 0.00 0.00
                 
Annual Sum or Average 304.45 8.79 295.66 193.55 597.19 0.00 0.00 0.00
Minimum of Months 101.07 0.00 101.07 0.07 250.12 0.00 0.00 0.00
Maximum of Months 522.84 40.06 487.86 492.82 1034.72 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 16.99 0.00 16.99 0.94 119.74 0.00 0.00 0.00
February 26.44 0.00 26.44 7.08 104.38 0.00 0.00 0.00
March 38.96 0.00 38.96 21.96 82.52 0.00 0.00 0.00
April 55.32 0.34 54.98 47.63 64.69 0.00 0.00 0.00
May 70.97 2.13 68.84 75.94 50.95 0.00 0.00 0.00
June 74.69 5.00 69.70 89.47 38.89 0.00 0.00 0.00
July 71.09 5.72 65.37 97.63 33.32 0.00 0.00 0.00
August 57.63 1.73 55.90 84.06 31.86 0.00 0.00 0.00
September 44.60 0.03 44.57 52.22 45.69 0.00 0.00 0.00
October 30.54 0.00 30.54 21.10 69.12 0.00 0.00 0.00
November 19.24 0.00 19.24 5.25 91.04 0.00 0.00 0.00
December 14.44 0.00 14.44 0.73 116.22 0.00 0.00 0.00
                 
Annual Sum or Average 43.49 1.26 42.24 42.21 70.54 0.00 0.00 0.00
Minimum of Months 14.44 0.00 14.44 0.73 31.86 0.00 0.00 0.00
Maximum of Months 74.69 5.72 69.70 97.63 119.74 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_FLR_6_WALL_EAST_WINDOW

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 101.53 25.44 76.09 38.47 429.51 0.00 0.00 0.00
February 187.04 66.25 120.79 132.36 368.69 0.00 0.00 0.00
March 280.32 101.65 178.67 262.35 294.12 0.00 0.00 0.00
April 432.94 179.66 253.29 494.93 233.94 0.00 0.00 0.00
May 460.98 160.51 300.48 565.99 191.35 0.00 0.00 0.00
June 551.74 240.14 311.60 724.31 146.60 0.00 0.00 0.00
July 514.55 231.34 283.21 718.71 123.55 0.00 0.00 0.00
August 505.11 252.66 252.44 727.43 118.95 0.00 0.00 0.00
September 374.06 172.82 201.24 492.31 167.01 0.00 0.00 0.00
October 244.59 104.51 140.08 260.20 250.70 0.00 0.00 0.00
November 119.70 33.90 85.80 76.78 330.81 0.00 0.00 0.00
December 97.92 31.47 66.44 50.51 420.22 0.00 0.00 0.00
                 
Annual Sum or Average 323.14 133.66 189.48 379.97 255.77 0.00 0.00 0.00
Minimum of Months 97.92 25.44 66.44 38.47 118.95 0.00 0.00 0.00
Maximum of Months 551.74 252.66 311.60 727.43 429.51 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 75.35 44.83 30.53 70.32 108.30 0.00 0.00 0.00
February 115.96 71.95 44.01 124.62 95.13 0.00 0.00 0.00
March 123.01 65.03 57.97 141.48 79.74 0.00 0.00 0.00
April 129.98 55.78 74.20 161.31 66.06 0.00 0.00 0.00
May 121.10 36.92 84.18 157.37 53.25 0.00 0.00 0.00
June 109.57 29.33 80.24 149.69 41.41 0.00 0.00 0.00
July 119.04 43.22 75.82 178.04 35.16 0.00 0.00 0.00
August 126.91 58.31 68.60 193.56 33.22 0.00 0.00 0.00
September 140.76 76.98 63.77 197.18 45.40 0.00 0.00 0.00
October 127.33 77.95 49.37 157.82 67.09 0.00 0.00 0.00
November 76.20 43.62 32.58 79.35 85.51 0.00 0.00 0.00
December 79.75 51.57 28.18 83.01 107.69 0.00 0.00 0.00
                 
Annual Sum or Average 112.03 54.52 57.51 141.22 68.03 0.00 0.00 0.00
Minimum of Months 75.35 29.33 28.18 70.32 33.22 0.00 0.00 0.00
Maximum of Months 140.76 77.95 84.18 197.18 108.30 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 21.52 0.00 21.52 0.30 161.04 0.00 0.00 0.00
February 33.48 0.00 33.48 4.83 138.21 0.00 0.00 0.00
March 49.34 0.00 49.34 18.88 106.64 0.00 0.00 0.00
April 70.06 0.43 69.63 45.23 81.42 0.00 0.00 0.00
May 89.88 2.70 87.19 74.43 63.69 0.00 0.00 0.00
June 94.60 6.33 88.27 87.56 47.18 0.00 0.00 0.00
July 90.04 7.25 82.79 94.48 41.54 0.00 0.00 0.00
August 72.98 2.19 70.79 78.34 40.44 0.00 0.00 0.00
September 56.49 0.04 56.45 44.78 62.62 0.00 0.00 0.00
October 38.68 0.00 38.68 16.66 90.32 0.00 0.00 0.00
November 24.36 0.00 24.36 2.79 122.46 0.00 0.00 0.00
December 18.29 0.00 18.29 0.10 156.70 0.00 0.00 0.00
                 
Annual Sum or Average 55.08 1.59 53.49 39.25 92.47 0.00 0.00 0.00
Minimum of Months 18.29 0.00 18.29 0.10 40.44 0.00 0.00 0.00
Maximum of Months 94.60 7.25 88.27 94.48 161.04 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.25 0.00 19.25 0.27 144.07 0.00 0.00 0.00
February 29.96 0.00 29.96 4.32 123.66 0.00 0.00 0.00
March 44.14 0.00 44.14 16.89 95.41 0.00 0.00 0.00
April 62.68 0.39 62.30 40.47 72.85 0.00 0.00 0.00
May 80.42 2.41 78.01 66.59 56.99 0.00 0.00 0.00
June 84.63 5.66 78.97 78.34 42.21 0.00 0.00 0.00
July 80.56 6.48 74.07 84.53 37.17 0.00 0.00 0.00
August 65.30 1.96 63.34 70.09 36.19 0.00 0.00 0.00
September 50.54 0.04 50.50 40.06 56.03 0.00 0.00 0.00
October 34.60 0.00 34.60 14.91 80.81 0.00 0.00 0.00
November 21.80 0.00 21.80 2.50 109.57 0.00 0.00 0.00
December 16.36 0.00 16.36 0.09 140.19 0.00 0.00 0.00
                 
Annual Sum or Average 49.28 1.42 47.86 35.11 82.73 0.00 0.00 0.00
Minimum of Months 16.36 0.00 16.36 0.09 36.19 0.00 0.00 0.00
Maximum of Months 84.63 6.48 78.97 84.53 144.07 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 281.32 167.35 113.97 243.32 416.30 0.00 0.00 0.00
February 432.91 268.60 164.31 435.06 359.84 0.00 0.00 0.00
March 459.23 242.79 216.43 490.74 299.40 0.00 0.00 0.00
April 485.25 208.26 277.00 551.38 244.07 0.00 0.00 0.00
May 452.11 137.83 314.28 522.46 199.70 0.00 0.00 0.00
June 409.06 109.48 299.58 483.85 152.46 0.00 0.00 0.00
July 444.42 161.37 283.05 579.78 134.48 0.00 0.00 0.00
August 473.79 217.70 256.09 638.22 127.98 0.00 0.00 0.00
September 525.49 287.41 238.08 665.52 182.46 0.00 0.00 0.00
October 475.35 291.03 184.33 546.64 251.77 0.00 0.00 0.00
November 284.48 162.84 121.64 271.66 328.12 0.00 0.00 0.00
December 297.74 192.54 105.20 289.60 413.68 0.00 0.00 0.00
                 
Annual Sum or Average 418.23 203.53 214.69 476.68 258.72 0.00 0.00 0.00
Minimum of Months 281.32 109.48 105.20 243.32 127.98 0.00 0.00 0.00
Maximum of Months 525.49 291.03 314.28 665.52 416.30 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.102079E+10 0.607247E+09 0.413543E+09 0.904710E+09 0.136614E+10
February 0.141883E+10 0.880309E+09 0.538522E+09 0.144286E+10 0.108351E+10
March 0.166635E+10 0.881003E+09 0.785345E+09 0.179511E+10 0.998468E+09
April 0.170398E+10 0.731303E+09 0.972674E+09 0.196437E+10 0.777568E+09
May 0.164051E+10 0.500145E+09 0.114037E+10 0.194222E+10 0.639693E+09
June 0.143641E+10 0.384441E+09 0.105197E+10 0.175971E+10 0.458393E+09
July 0.161261E+10 0.585540E+09 0.102707E+10 0.215079E+10 0.420315E+09
August 0.171918E+10 0.789956E+09 0.929228E+09 0.234704E+10 0.406070E+09
September 0.184527E+10 0.100924E+10 0.836033E+09 0.234305E+10 0.582473E+09
October 0.172485E+10 0.105602E+10 0.668837E+09 0.199345E+10 0.844130E+09
November 0.998973E+09 0.571820E+09 0.427153E+09 0.967933E+09 0.104679E+10
December 0.108037E+10 0.698661E+09 0.381712E+09 0.105965E+10 0.137139E+10
           
Annual Sum or Average 0.178681E+11 0.869568E+10 0.917246E+10 0.206709E+11 0.999494E+10
Minimum of Months 0.998973E+09 0.384441E+09 0.381712E+09 0.904710E+09 0.406070E+09
Maximum of Months 0.184527E+10 0.105602E+10 0.114037E+10 0.234704E+10 0.137139E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: CAFE_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.287448E+10 0.170997E+10 0.116451E+10 0.250833E+10 0.397198E+10
February 0.399533E+10 0.247889E+10 0.151644E+10 0.400813E+10 0.318222E+10
March 0.469233E+10 0.248085E+10 0.221148E+10 0.498816E+10 0.299046E+10
April 0.479829E+10 0.205930E+10 0.273898E+10 0.544990E+10 0.236078E+10
May 0.461958E+10 0.140838E+10 0.321120E+10 0.537820E+10 0.196930E+10
June 0.404484E+10 0.108256E+10 0.296227E+10 0.485112E+10 0.145398E+10
July 0.454101E+10 0.164884E+10 0.289217E+10 0.596381E+10 0.133206E+10
August 0.484111E+10 0.222446E+10 0.261664E+10 0.652316E+10 0.129727E+10
September 0.519617E+10 0.284196E+10 0.235421E+10 0.652216E+10 0.180869E+10
October 0.485707E+10 0.297367E+10 0.188340E+10 0.554110E+10 0.257592E+10
November 0.281304E+10 0.161021E+10 0.120283E+10 0.268032E+10 0.309726E+10
December 0.304226E+10 0.196738E+10 0.107488E+10 0.294443E+10 0.399904E+10
           
Annual Sum or Average 0.503155E+11 0.244865E+11 0.258290E+11 0.573588E+11 0.300390E+11
Minimum of Months 0.281304E+10 0.108256E+10 0.107488E+10 0.250833E+10 0.129727E+10
Maximum of Months 0.519617E+10 0.297367E+10 0.321120E+10 0.652316E+10 0.399904E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: LOBBY_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.373411E+10 0.222134E+10 0.151276E+10 0.327949E+10 0.551163E+10
February 0.519017E+10 0.322022E+10 0.196994E+10 0.526553E+10 0.439041E+10
March 0.609560E+10 0.322276E+10 0.287284E+10 0.656445E+10 0.414259E+10
April 0.623325E+10 0.267515E+10 0.355810E+10 0.717549E+10 0.326652E+10
May 0.600109E+10 0.182956E+10 0.417153E+10 0.706830E+10 0.274973E+10
June 0.525447E+10 0.140631E+10 0.384816E+10 0.636049E+10 0.203906E+10
July 0.589903E+10 0.214194E+10 0.375709E+10 0.785141E+10 0.185386E+10
August 0.628888E+10 0.288971E+10 0.339917E+10 0.859266E+10 0.179019E+10
September 0.675012E+10 0.369187E+10 0.305826E+10 0.858522E+10 0.249996E+10
October 0.630961E+10 0.386297E+10 0.244665E+10 0.728462E+10 0.358031E+10
November 0.365430E+10 0.209175E+10 0.156255E+10 0.349668E+10 0.433748E+10
December 0.395207E+10 0.255574E+10 0.139632E+10 0.385700E+10 0.555093E+10
           
Annual Sum or Average 0.653627E+11 0.318093E+11 0.335534E+11 0.753813E+11 0.417127E+11
Minimum of Months 0.365430E+10 0.140631E+10 0.139632E+10 0.327949E+10 0.179019E+10
Maximum of Months 0.675012E+10 0.386297E+10 0.417153E+10 0.859266E+10 0.555093E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.201828E+09 0.120063E+09 81764855.83 0.180826E+09 0.274427E+09
February 0.280528E+09 0.174052E+09 0.106476E+09 0.286897E+09 0.217552E+09
March 0.329467E+09 0.174190E+09 0.155277E+09 0.355781E+09 0.200952E+09
April 0.336907E+09 0.144591E+09 0.192316E+09 0.385917E+09 0.157701E+09
May 0.324360E+09 98887279.29 0.225472E+09 0.378616E+09 0.129649E+09
June 0.284005E+09 76010646.67 0.207994E+09 0.342499E+09 91166134.92
July 0.318843E+09 0.115771E+09 0.203072E+09 0.423025E+09 80530755.24
August 0.339914E+09 0.156188E+09 0.183726E+09 0.465284E+09 74866181.28
September 0.364844E+09 0.199544E+09 0.165299E+09 0.466055E+09 0.112948E+09
October 0.341034E+09 0.208792E+09 0.132241E+09 0.395688E+09 0.166977E+09
November 0.197514E+09 0.113059E+09 84455881.64 0.193228E+09 0.208759E+09
December 0.213609E+09 0.138137E+09 75471285.47 0.211915E+09 0.273144E+09
           
Annual Sum or Average 0.353285E+10 0.171929E+10 0.181357E+10 0.408573E+10 0.198867E+10
Minimum of Months 0.197514E+09 76010646.67 75471285.47 0.180826E+09 74866181.28
Maximum of Months 0.364844E+09 0.208792E+09 0.225472E+09 0.466055E+09 0.274427E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_3_WALL_WEST_WINDOW

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.144896E+09 43103720.32 0.101793E+09 59455203.86 0.555206E+09
February 0.233458E+09 87642964.17 0.145815E+09 0.158573E+09 0.434529E+09
March 0.362082E+09 0.122417E+09 0.239665E+09 0.304565E+09 0.382883E+09
April 0.532452E+09 0.203310E+09 0.329141E+09 0.547038E+09 0.287444E+09
May 0.709342E+09 0.288786E+09 0.420557E+09 0.805614E+09 0.234381E+09
June 0.658756E+09 0.255289E+09 0.403468E+09 0.772255E+09 0.164835E+09
July 0.841502E+09 0.442194E+09 0.399308E+09 0.107781E+10 0.145988E+09
August 0.696429E+09 0.355219E+09 0.341210E+09 0.905615E+09 0.137607E+09
September 0.550628E+09 0.264873E+09 0.285755E+09 0.656978E+09 0.210751E+09
October 0.325383E+09 0.133761E+09 0.191622E+09 0.305214E+09 0.322140E+09
November 0.155943E+09 44331374.38 0.111611E+09 87424008.34 0.413590E+09
December 0.136017E+09 47217705.85 88798972.09 71732635.66 0.549304E+09
           
Annual Sum or Average 0.534689E+10 0.228814E+10 0.305874E+10 0.575228E+10 0.383866E+10
Minimum of Months 0.136017E+09 43103720.32 88798972.09 59455203.86 0.137607E+09
Maximum of Months 0.841502E+09 0.442194E+09 0.420557E+09 0.107781E+10 0.555206E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 45510498.67 0.00 45510498.67 1452376.70 0.306961E+09
February 63962484.45 0.00 63962484.45 12474701.33 0.240092E+09
March 0.104345E+09 340.22 0.104345E+09 46141517.03 0.208351E+09
April 0.143391E+09 882204.25 0.142509E+09 96990988.13 0.154702E+09
May 0.190097E+09 5707817.87 0.184389E+09 0.157972E+09 0.124705E+09
June 0.193607E+09 12952148.54 0.180655E+09 0.181633E+09 87765174.34
July 0.190420E+09 15329272.49 0.175090E+09 0.199882E+09 80378884.59
August 0.154354E+09 4635653.25 0.149719E+09 0.170254E+09 74812507.59
September 0.115615E+09 86607.59 0.115529E+09 94685137.33 0.118473E+09
October 81798730.60 0.00 81798730.60 40937941.19 0.174544E+09
November 49862977.19 0.00 49862977.19 8111109.51 0.225608E+09
December 38672190.66 0.00 38672190.66 741217.46 0.299162E+09
           
Annual Sum or Average 0.137164E+10 39594044.20 0.133204E+10 0.101128E+10 0.209555E+10
Minimum of Months 38672190.66 0.00 38672190.66 741217.46 74812507.59
Maximum of Months 0.193607E+09 15329272.49 0.184389E+09 0.199882E+09 0.306961E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_3_WALL_WEST_WINDOW

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.144896E+09 43103720.32 0.101793E+09 63592030.41 0.549699E+09
February 0.233458E+09 87642964.17 0.145815E+09 0.165957E+09 0.427855E+09
March 0.362082E+09 0.122417E+09 0.239665E+09 0.314510E+09 0.377649E+09
April 0.532452E+09 0.203310E+09 0.329141E+09 0.554255E+09 0.286020E+09
May 0.709342E+09 0.288786E+09 0.420557E+09 0.801658E+09 0.238731E+09
June 0.658756E+09 0.255289E+09 0.403468E+09 0.764950E+09 0.171931E+09
July 0.841502E+09 0.442194E+09 0.399308E+09 0.106539E+10 0.157603E+09
August 0.696429E+09 0.355219E+09 0.341210E+09 0.902334E+09 0.146097E+09
September 0.550628E+09 0.264873E+09 0.285755E+09 0.656826E+09 0.216668E+09
October 0.325383E+09 0.133761E+09 0.191622E+09 0.314147E+09 0.317688E+09
November 0.155943E+09 44331374.38 0.111611E+09 92020331.23 0.408690E+09
December 0.136017E+09 47217705.85 88798972.09 76445599.53 0.543139E+09
           
Annual Sum or Average 0.534689E+10 0.228814E+10 0.305874E+10 0.577208E+10 0.384177E+10
Minimum of Months 0.136017E+09 43103720.32 88798972.09 63592030.41 0.146097E+09
Maximum of Months 0.841502E+09 0.442194E+09 0.420557E+09 0.106539E+10 0.549699E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.161430E+09 96031370.32 65398878.59 0.138345E+09 0.236559E+09
February 0.224378E+09 0.139214E+09 85163535.41 0.212559E+09 0.216680E+09
March 0.263521E+09 0.139324E+09 0.124197E+09 0.258003E+09 0.229742E+09
April 0.269472E+09 0.115650E+09 0.153822E+09 0.277818E+09 0.185456E+09
May 0.259436E+09 79094093.75 0.180342E+09 0.270975E+09 0.158277E+09
June 0.227159E+09 60796426.56 0.166362E+09 0.239743E+09 0.120867E+09
July 0.255024E+09 92598617.16 0.162425E+09 0.305305E+09 0.111608E+09
August 0.271877E+09 0.124925E+09 0.146952E+09 0.338731E+09 0.108565E+09
September 0.291817E+09 0.159604E+09 0.132213E+09 0.344240E+09 0.144658E+09
October 0.272773E+09 0.167001E+09 0.105772E+09 0.288663E+09 0.204107E+09
November 0.157980E+09 90428875.66 67551271.18 0.136284E+09 0.229820E+09
December 0.170853E+09 0.110488E+09 60365023.40 0.159073E+09 0.254175E+09
           
Annual Sum or Average 0.282572E+10 0.137516E+10 0.145056E+10 0.296974E+10 0.220052E+10
Minimum of Months 0.157980E+09 60796426.56 60365023.40 0.136284E+09 0.108565E+09
Maximum of Months 0.291817E+09 0.167001E+09 0.180342E+09 0.344240E+09 0.254175E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 36413225.08 0.00 36413225.08 701082.84 0.260699E+09
February 51176770.43 0.00 51176770.43 8639307.11 0.201232E+09
March 83487367.90 272.21 83487095.69 35761776.39 0.172401E+09
April 0.114728E+09 705856.95 0.114022E+09 80075429.18 0.124862E+09
May 0.152098E+09 4566859.58 0.147531E+09 0.134657E+09 97864401.29
June 0.154906E+09 10363092.34 0.144543E+09 0.154022E+09 67958831.48
July 0.152356E+09 12265043.58 0.140091E+09 0.172989E+09 59434891.13
August 0.123500E+09 3709014.18 0.119791E+09 0.145977E+09 55768778.77
September 92504439.09 69295.25 92435143.84 81808772.32 90686870.81
October 65447658.79 0.00 65447658.79 32680784.65 0.143225E+09
November 39895669.45 0.00 39895669.45 5412035.22 0.191644E+09
December 30941853.50 0.00 30941853.50 287529.25 0.253911E+09
           
Annual Sum or Average 0.109745E+10 31679434.09 0.106578E+10 0.853012E+09 0.171969E+10
Minimum of Months 30941853.50 0.00 30941853.50 287529.25 55768778.77
Maximum of Months 0.154906E+09 12265043.58 0.147531E+09 0.172989E+09 0.260699E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_5_FLR_3_WALL_EAST_WINDOW

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.135983E+09 34077660.85 0.101905E+09 43858507.90 0.550094E+09
February 0.226258E+09 80141237.88 0.146117E+09 0.140954E+09 0.426173E+09
March 0.375425E+09 0.136136E+09 0.239289E+09 0.309548E+09 0.370193E+09
April 0.561134E+09 0.232853E+09 0.328282E+09 0.573603E+09 0.276050E+09
May 0.617389E+09 0.214964E+09 0.402426E+09 0.674425E+09 0.227318E+09
June 0.715100E+09 0.311241E+09 0.403858E+09 0.846192E+09 0.158077E+09
July 0.689138E+09 0.309834E+09 0.379304E+09 0.859429E+09 0.134054E+09
August 0.676486E+09 0.338392E+09 0.338094E+09 0.869704E+09 0.128268E+09
September 0.484815E+09 0.223992E+09 0.260822E+09 0.554145E+09 0.201457E+09
October 0.327581E+09 0.139970E+09 0.187611E+09 0.301337E+09 0.313530E+09
November 0.155138E+09 43931896.31 0.111207E+09 81730010.20 0.407831E+09
December 0.131139E+09 42150042.10 88988570.02 57488559.01 0.539606E+09
           
Annual Sum or Average 0.509559E+10 0.210768E+10 0.298790E+10 0.531241E+10 0.373265E+10
Minimum of Months 0.131139E+09 34077660.85 88988570.02 43858507.90 0.128268E+09
Maximum of Months 0.715100E+09 0.338392E+09 0.403858E+09 0.869704E+09 0.550094E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.201828E+09 0.120063E+09 81764855.83 0.180747E+09 0.274048E+09
February 0.280528E+09 0.174052E+09 0.106476E+09 0.286224E+09 0.217042E+09
March 0.329467E+09 0.174190E+09 0.155277E+09 0.353781E+09 0.200425E+09
April 0.336907E+09 0.144591E+09 0.192316E+09 0.383050E+09 0.157159E+09
May 0.324360E+09 98887279.29 0.225472E+09 0.378285E+09 0.127986E+09
June 0.284005E+09 76010646.67 0.207994E+09 0.339783E+09 90383887.47
July 0.318843E+09 0.115771E+09 0.203072E+09 0.423153E+09 78376875.04
August 0.339914E+09 0.156188E+09 0.183726E+09 0.463936E+09 73770782.17
September 0.364844E+09 0.199544E+09 0.165299E+09 0.465693E+09 0.111071E+09
October 0.341034E+09 0.208792E+09 0.132241E+09 0.394395E+09 0.166207E+09
November 0.197514E+09 0.113059E+09 84455881.64 0.192897E+09 0.208417E+09
December 0.213609E+09 0.138137E+09 75471285.47 0.211809E+09 0.272707E+09
           
Annual Sum or Average 0.353285E+10 0.171929E+10 0.181357E+10 0.407375E+10 0.197759E+10
Minimum of Months 0.197514E+09 76010646.67 75471285.47 0.180747E+09 73770782.17
Maximum of Months 0.364844E+09 0.208792E+09 0.225472E+09 0.465693E+09 0.274048E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_6_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 45510498.67 0.00 45510498.67 1395287.77 0.306713E+09
February 63962484.45 0.00 63962484.45 12209123.12 0.239712E+09
March 0.104345E+09 340.22 0.104345E+09 44437029.24 0.207955E+09
April 0.143391E+09 882204.25 0.142509E+09 94374985.47 0.154391E+09
May 0.190097E+09 5707817.87 0.184389E+09 0.159993E+09 0.121826E+09
June 0.193607E+09 12952148.54 0.180655E+09 0.180312E+09 86035048.78
July 0.190420E+09 15329272.49 0.175090E+09 0.202962E+09 75903204.53
August 0.154354E+09 4635653.25 0.149719E+09 0.168181E+09 72579364.49
September 0.115615E+09 86607.59 0.115529E+09 95541387.06 0.114357E+09
October 81798730.60 0.00 81798730.60 39632118.00 0.173303E+09
November 49862977.19 0.00 49862977.19 7799821.04 0.225091E+09
December 38672190.66 0.00 38672190.66 656315.62 0.298762E+09
           
Annual Sum or Average 0.137164E+10 39594044.20 0.133204E+10 0.100749E+10 0.207663E+10
Minimum of Months 38672190.66 0.00 38672190.66 656315.62 72579364.49
Maximum of Months 0.193607E+09 15329272.49 0.184389E+09 0.202962E+09 0.306713E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_6_FLR_3_WALL_EAST_WINDOW

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.135983E+09 34077660.85 0.101905E+09 45486514.44 0.542091E+09
February 0.226258E+09 80141237.88 0.146117E+09 0.145838E+09 0.416307E+09
March 0.375425E+09 0.136136E+09 0.239289E+09 0.318933E+09 0.363977E+09
April 0.561134E+09 0.232853E+09 0.328282E+09 0.580678E+09 0.274010E+09
May 0.617389E+09 0.214964E+09 0.402426E+09 0.676260E+09 0.229624E+09
June 0.715100E+09 0.311241E+09 0.403858E+09 0.843434E+09 0.164324E+09
July 0.689138E+09 0.309834E+09 0.379304E+09 0.854382E+09 0.142311E+09
August 0.676486E+09 0.338392E+09 0.338094E+09 0.865999E+09 0.135251E+09
September 0.484815E+09 0.223992E+09 0.260822E+09 0.558255E+09 0.204031E+09
October 0.327581E+09 0.139970E+09 0.187611E+09 0.310303E+09 0.307941E+09
November 0.155138E+09 43931896.31 0.111207E+09 84775710.01 0.400916E+09
December 0.131139E+09 42150042.10 88988570.02 59563543.34 0.530559E+09
           
Annual Sum or Average 0.509559E+10 0.210768E+10 0.298790E+10 0.534391E+10 0.371134E+10
Minimum of Months 0.131139E+09 34077660.85 88988570.02 45486514.44 0.135251E+09
Maximum of Months 0.715100E+09 0.338392E+09 0.403858E+09 0.865999E+09 0.542091E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 57636175.01 0.00 57636175.01 1031262.33 0.421357E+09
February 81004450.75 0.00 81004450.75 13548855.00 0.325125E+09
March 0.132147E+09 430.86 0.132146E+09 56480410.04 0.277698E+09
April 0.181596E+09 1117256.01 0.180479E+09 0.126600E+09 0.204484E+09
May 0.240746E+09 7228591.19 0.233517E+09 0.211014E+09 0.166062E+09
June 0.245191E+09 16403078.89 0.228788E+09 0.240512E+09 0.117293E+09
July 0.241154E+09 19413556.39 0.221741E+09 0.267092E+09 0.106303E+09
August 0.195480E+09 5870762.35 0.189609E+09 0.221266E+09 0.103782E+09
September 0.146419E+09 109683.05 0.146310E+09 0.124094E+09 0.158625E+09
October 0.103593E+09 0.00 0.103593E+09 49747864.10 0.235976E+09
November 63148314.43 0.00 63148314.43 8732723.81 0.307755E+09
December 48975889.39 0.00 48975889.39 390958.80 0.410534E+09
           
Annual Sum or Average 0.173709E+10 50143358.74 0.168695E+10 0.132051E+10 0.283499E+10
Minimum of Months 48975889.39 0.00 48975889.39 390958.80 0.103782E+09
Maximum of Months 0.245191E+09 19413556.39 0.233517E+09 0.267092E+09 0.421357E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 21247080.64 0.00 21247080.64 380166.00 0.155329E+09
February 29861594.68 0.00 29861594.68 4994668.97 0.119854E+09
March 48714796.18 158.83 48714637.34 20821017.81 0.102371E+09
April 66943790.08 411866.83 66531923.25 46670115.43 75381419.73
May 88748888.58 2664758.02 86084130.55 77788626.88 61217350.19
June 90387603.67 6046854.08 84340749.59 88662846.77 43239141.08
July 88899508.73 7156640.74 81742867.99 98461108.64 39187619.84
August 72062069.48 2164206.09 69897863.39 81567732.36 38258417.46
September 53976248.26 40433.71 53935814.54 45746164.56 58475571.00
October 38188643.85 0.00 38188643.85 18339122.60 86990582.86
November 23279083.47 0.00 23279083.47 3219243.59 0.113451E+09
December 18054540.76 0.00 18054540.76 144123.60 0.151340E+09
           
Annual Sum or Average 0.640364E+09 18484918.30 0.621879E+09 0.486795E+09 0.104510E+10
Minimum of Months 18054540.76 0.00 18054540.76 144123.60 38258417.46
Maximum of Months 90387603.67 7156640.74 86084130.55 98461108.64 0.155329E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 94172104.10 56020951.86 38151152.24 82969963.84 0.135950E+09
February 0.130893E+09 81212052.17 49681081.31 0.133994E+09 0.106146E+09
March 0.153728E+09 81276128.21 72451757.76 0.167647E+09 97280864.31
April 0.157199E+09 67465641.93 89733781.59 0.183123E+09 76336329.34
May 0.151345E+09 46140406.03 0.105205E+09 0.179854E+09 64754229.76
June 0.132516E+09 35466261.44 97049331.00 0.162181E+09 47076418.22
July 0.148771E+09 54018417.70 94752617.30 0.199819E+09 42754374.86
August 0.158603E+09 72876646.06 85725869.59 0.218619E+09 40863103.35
September 0.170235E+09 93106622.21 77128015.79 0.219262E+09 57619923.80
October 0.159125E+09 97421719.72 61703299.94 0.186222E+09 82044615.43
November 92159449.27 52752675.23 39406774.04 89881046.14 0.103022E+09
December 99668866.61 64454268.94 35214597.67 98413784.82 0.135349E+09
           
Annual Sum or Average 0.164841E+10 0.802212E+09 0.846203E+09 0.192199E+10 0.989197E+09
Minimum of Months 92159449.27 35466261.44 35214597.67 82969963.84 40863103.35
Maximum of Months 0.170235E+09 97421719.72 0.105205E+09 0.219262E+09 0.135950E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.255602E+09 0.152052E+09 0.103550E+09 0.225197E+09 0.368995E+09
February 0.355271E+09 0.220426E+09 0.134845E+09 0.363688E+09 0.288102E+09
March 0.417249E+09 0.220600E+09 0.196649E+09 0.455029E+09 0.264040E+09
April 0.426671E+09 0.183116E+09 0.243556E+09 0.497034E+09 0.207192E+09
May 0.410781E+09 0.125234E+09 0.285547E+09 0.488159E+09 0.175756E+09
June 0.359674E+09 96262688.00 0.263412E+09 0.440191E+09 0.127775E+09
July 0.403795E+09 0.146617E+09 0.257178E+09 0.542349E+09 0.116044E+09
August 0.430480E+09 0.197802E+09 0.232678E+09 0.593377E+09 0.110911E+09
September 0.462052E+09 0.252710E+09 0.209341E+09 0.595121E+09 0.156392E+09
October 0.431898E+09 0.264422E+09 0.167475E+09 0.505446E+09 0.222686E+09
November 0.250140E+09 0.143182E+09 0.106958E+09 0.243956E+09 0.279623E+09
December 0.270522E+09 0.174942E+09 95579621.07 0.267115E+09 0.367365E+09
           
Annual Sum or Average 0.447413E+10 0.217737E+10 0.229677E+10 0.521666E+10 0.268488E+10
Minimum of Months 0.250140E+09 96262688.00 95579621.07 0.225197E+09 0.110911E+09
Maximum of Months 0.462052E+09 0.264422E+09 0.285547E+09 0.595121E+09 0.368995E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.201828E+09 0.120063E+09 81764855.83 0.181089E+09 0.272537E+09
February 0.280528E+09 0.174052E+09 0.106476E+09 0.286185E+09 0.216203E+09
March 0.329467E+09 0.174190E+09 0.155277E+09 0.353937E+09 0.199889E+09
April 0.336907E+09 0.144591E+09 0.192316E+09 0.382554E+09 0.157493E+09
May 0.324360E+09 98887279.29 0.225472E+09 0.374555E+09 0.129310E+09
June 0.284005E+09 76010646.67 0.207994E+09 0.338478E+09 90750241.79
July 0.318843E+09 0.115771E+09 0.203072E+09 0.418702E+09 80099182.56
August 0.339914E+09 0.156188E+09 0.183726E+09 0.461797E+09 73910658.32
September 0.364844E+09 0.199544E+09 0.165299E+09 0.463678E+09 0.111746E+09
October 0.341034E+09 0.208792E+09 0.132241E+09 0.393847E+09 0.165337E+09
November 0.197514E+09 0.113059E+09 84455881.64 0.193097E+09 0.206832E+09
December 0.213609E+09 0.138137E+09 75471285.47 0.211958E+09 0.270736E+09
           
Annual Sum or Average 0.353285E+10 0.171929E+10 0.181357E+10 0.405988E+10 0.197484E+10
Minimum of Months 0.197514E+09 76010646.67 75471285.47 0.181089E+09 73910658.32
Maximum of Months 0.364844E+09 0.208792E+09 0.225472E+09 0.463678E+09 0.272537E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_6_WALL_WEST_WINDOW

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.144896E+09 43103720.32 0.101793E+09 60215619.82 0.550169E+09
February 0.233458E+09 87642964.17 0.145815E+09 0.158041E+09 0.430862E+09
March 0.362082E+09 0.122417E+09 0.239665E+09 0.302199E+09 0.379971E+09
April 0.532452E+09 0.203310E+09 0.329141E+09 0.540932E+09 0.286606E+09
May 0.709342E+09 0.288786E+09 0.420557E+09 0.796978E+09 0.233346E+09
June 0.658756E+09 0.255289E+09 0.403468E+09 0.763724E+09 0.163715E+09
July 0.841502E+09 0.442194E+09 0.399308E+09 0.106805E+10 0.144792E+09
August 0.696429E+09 0.355219E+09 0.341210E+09 0.898639E+09 0.135551E+09
September 0.550628E+09 0.264873E+09 0.285755E+09 0.652520E+09 0.208047E+09
October 0.325383E+09 0.133761E+09 0.191622E+09 0.303150E+09 0.318185E+09
November 0.155943E+09 44331374.38 0.111611E+09 87718535.82 0.408651E+09
December 0.136017E+09 47217705.85 88798972.09 72066364.35 0.542753E+09
           
Annual Sum or Average 0.534689E+10 0.228814E+10 0.305874E+10 0.570423E+10 0.380265E+10
Minimum of Months 0.136017E+09 43103720.32 88798972.09 60215619.82 0.135551E+09
Maximum of Months 0.841502E+09 0.442194E+09 0.420557E+09 0.106805E+10 0.550169E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 45510498.67 0.00 45510498.67 1629391.18 0.303629E+09
February 63962484.45 0.00 63962484.45 12829938.37 0.237893E+09
March 0.104345E+09 340.22 0.104345E+09 46273675.64 0.206679E+09
April 0.143391E+09 882204.25 0.142509E+09 95738927.06 0.154307E+09
May 0.190097E+09 5707817.87 0.184389E+09 0.154550E+09 0.125374E+09
June 0.193607E+09 12952148.54 0.180655E+09 0.177730E+09 88632382.24
July 0.190420E+09 15329272.49 0.175090E+09 0.195577E+09 81925499.00
August 0.154354E+09 4635653.25 0.149719E+09 0.168291E+09 74923397.51
September 0.115615E+09 86607.59 0.115529E+09 93319055.98 0.118830E+09
October 81798730.60 0.00 81798730.60 41452060.73 0.172169E+09
November 49862977.19 0.00 49862977.19 8433231.91 0.222441E+09
December 38672190.66 0.00 38672190.66 890728.17 0.294983E+09
           
Annual Sum or Average 0.137164E+10 39594044.20 0.133204E+10 0.996714E+09 0.208179E+10
Minimum of Months 38672190.66 0.00 38672190.66 890728.17 74923397.51
Maximum of Months 0.193607E+09 15329272.49 0.184389E+09 0.195577E+09 0.303629E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_6_WALL_WEST_WINDOW

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.144896E+09 43103720.32 0.101793E+09 64457562.17 0.545087E+09
February 0.233458E+09 87642964.17 0.145815E+09 0.166264E+09 0.424190E+09
March 0.362082E+09 0.122417E+09 0.239665E+09 0.313073E+09 0.374405E+09
April 0.532452E+09 0.203310E+09 0.329141E+09 0.548393E+09 0.285484E+09
May 0.709342E+09 0.288786E+09 0.420557E+09 0.791104E+09 0.239960E+09
June 0.658756E+09 0.255289E+09 0.403468E+09 0.753963E+09 0.173482E+09
July 0.841502E+09 0.442194E+09 0.399308E+09 0.105243E+10 0.160359E+09
August 0.696429E+09 0.355219E+09 0.341210E+09 0.894403E+09 0.146084E+09
September 0.550628E+09 0.264873E+09 0.285755E+09 0.651211E+09 0.216586E+09
October 0.325383E+09 0.133761E+09 0.191622E+09 0.313119E+09 0.313405E+09
November 0.155943E+09 44331374.38 0.111611E+09 92822645.68 0.403601E+09
December 0.136017E+09 47217705.85 88798972.09 77346950.85 0.536642E+09
           
Annual Sum or Average 0.534689E+10 0.228814E+10 0.305874E+10 0.571858E+10 0.381928E+10
Minimum of Months 0.136017E+09 43103720.32 88798972.09 64457562.17 0.146084E+09
Maximum of Months 0.841502E+09 0.442194E+09 0.420557E+09 0.105243E+10 0.545087E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.296000E+09 0.176084E+09 0.119916E+09 0.254400E+09 0.416722E+09
February 0.411421E+09 0.255264E+09 0.156157E+09 0.407661E+09 0.330418E+09
March 0.483195E+09 0.255466E+09 0.227729E+09 0.508610E+09 0.303974E+09
April 0.494106E+09 0.212057E+09 0.282050E+09 0.554993E+09 0.235024E+09
May 0.475705E+09 0.145028E+09 0.330677E+09 0.549720E+09 0.189092E+09
June 0.416521E+09 0.111477E+09 0.305044E+09 0.498545E+09 0.131527E+09
July 0.467614E+09 0.169790E+09 0.297825E+09 0.619527E+09 0.113496E+09
August 0.498517E+09 0.229065E+09 0.269452E+09 0.679845E+09 0.105908E+09
September 0.535078E+09 0.292651E+09 0.242427E+09 0.677455E+09 0.164260E+09
October 0.500159E+09 0.306214E+09 0.193945E+09 0.567688E+09 0.251990E+09
November 0.289674E+09 0.165811E+09 0.123863E+09 0.274059E+09 0.317840E+09
December 0.313277E+09 0.202591E+09 0.110686E+09 0.300873E+09 0.414172E+09
           
Annual Sum or Average 0.518127E+10 0.252150E+10 0.265977E+10 0.589338E+10 0.297442E+10
Minimum of Months 0.289674E+09 0.111477E+09 0.110686E+09 0.254400E+09 0.105908E+09
Maximum of Months 0.535078E+09 0.306214E+09 0.330677E+09 0.679845E+09 0.416722E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: BANQUET_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.318561E+09 0.00 0.318561E+09 1369555.18 0.268481E+10
February 0.447720E+09 0.00 0.447720E+09 45237698.48 0.210024E+10
March 0.730390E+09 2381.43 0.730388E+09 0.223900E+09 0.181915E+10
April 0.100370E+10 6175195.84 0.997525E+09 0.569268E+09 0.133676E+10
May 0.133063E+10 39953211.88 0.129068E+10 0.101299E+10 0.105264E+10
June 0.135520E+10 90661606.03 0.126454E+10 0.117320E+10 0.745944E+09
July 0.133289E+10 0.107301E+09 0.122559E+10 0.134554E+10 0.665837E+09
August 0.108044E+10 32448343.77 0.104799E+10 0.111680E+10 0.650114E+09
September 0.809276E+09 606230.16 0.808670E+09 0.597949E+09 0.992684E+09
October 0.572569E+09 0.00 0.572569E+09 0.200195E+09 0.155908E+10
November 0.349028E+09 0.00 0.349028E+09 24289375.55 0.203553E+10
December 0.270695E+09 0.00 0.270695E+09 359972.49 0.262315E+10
           
Annual Sum or Average 0.960109E+10 0.277148E+09 0.932395E+10 0.631110E+10 0.182659E+11
Minimum of Months 0.270695E+09 0.00 0.270695E+09 359972.49 0.650114E+09
Maximum of Months 0.135520E+10 0.107301E+09 0.129068E+10 0.134554E+10 0.268481E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: DINING_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.318561E+09 0.00 0.318561E+09 687444.12 0.277140E+10
February 0.447720E+09 0.00 0.447720E+09 39623527.95 0.216995E+10
March 0.730390E+09 2381.43 0.730388E+09 0.203067E+09 0.187318E+10
April 0.100370E+10 6175195.84 0.997525E+09 0.541639E+09 0.137277E+10
May 0.133063E+10 39953211.88 0.129068E+10 0.983699E+09 0.107824E+10
June 0.135520E+10 90661606.03 0.126454E+10 0.114418E+10 0.765134E+09
July 0.133289E+10 0.107301E+09 0.122559E+10 0.131997E+10 0.683892E+09
August 0.108044E+10 32448343.77 0.104799E+10 0.109201E+10 0.669926E+09
September 0.809276E+09 606230.16 0.808670E+09 0.576484E+09 0.102126E+10
October 0.572569E+09 0.00 0.572569E+09 0.181873E+09 0.160999E+10
November 0.349028E+09 0.00 0.349028E+09 20281496.21 0.210877E+10
December 0.270695E+09 0.00 0.270695E+09 193458.55 0.270839E+10
           
Annual Sum or Average 0.960109E+10 0.277148E+09 0.932395E+10 0.610372E+10 0.188329E+11
Minimum of Months 0.270695E+09 0.00 0.270695E+09 193458.55 0.669926E+09
Maximum of Months 0.135520E+10 0.107301E+09 0.129068E+10 0.131997E+10 0.277140E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 45510498.67 0.00 45510498.67 2507640.87 0.320722E+09
February 63962484.45 0.00 63962484.45 17132774.31 0.252514E+09
March 0.104345E+09 340.22 0.104345E+09 58807777.14 0.221013E+09
April 0.143391E+09 882204.25 0.142509E+09 0.123450E+09 0.167674E+09
May 0.190097E+09 5707817.87 0.184389E+09 0.203393E+09 0.136458E+09
June 0.193607E+09 12952148.54 0.180655E+09 0.231902E+09 0.100798E+09
July 0.190420E+09 15329272.49 0.175090E+09 0.261490E+09 89233609.95
August 0.154354E+09 4635653.25 0.149719E+09 0.225152E+09 85341355.16
September 0.115615E+09 86607.59 0.115529E+09 0.135354E+09 0.118432E+09
October 81798730.60 0.00 81798730.60 56512198.14 0.185134E+09
November 49862977.19 0.00 49862977.19 13614318.76 0.235982E+09
December 38672190.66 0.00 38672190.66 1943138.12 0.311286E+09
           
Annual Sum or Average 0.137164E+10 39594044.20 0.133204E+10 0.133126E+10 0.222459E+10
Minimum of Months 38672190.66 0.00 38672190.66 1943138.12 85341355.16
Maximum of Months 0.193607E+09 15329272.49 0.184389E+09 0.261490E+09 0.320722E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_FLR_6_WALL_EAST_WINDOW

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.271947E+09 68150481.81 0.203796E+09 0.103027E+09 0.115039E+10
February 0.452484E+09 0.160271E+09 0.292213E+09 0.320194E+09 0.891940E+09
March 0.750798E+09 0.272253E+09 0.478545E+09 0.702691E+09 0.787783E+09
April 0.112219E+10 0.465673E+09 0.656516E+09 0.128285E+10 0.606372E+09
May 0.123469E+10 0.429897E+09 0.804794E+09 0.151594E+10 0.512501E+09
June 0.143010E+10 0.622438E+09 0.807660E+09 0.187742E+10 0.379979E+09
July 0.137818E+10 0.619625E+09 0.758553E+09 0.192500E+10 0.330905E+09
August 0.135288E+10 0.676736E+09 0.676140E+09 0.194835E+10 0.318585E+09
September 0.969561E+09 0.447953E+09 0.521608E+09 0.127606E+10 0.432884E+09
October 0.655116E+09 0.279920E+09 0.375195E+09 0.696927E+09 0.671488E+09
November 0.310255E+09 87857553.18 0.222397E+09 0.199002E+09 0.857463E+09
December 0.262259E+09 84294097.83 0.177965E+09 0.135277E+09 0.112552E+10
           
Annual Sum or Average 0.101905E+11 0.421507E+10 0.597538E+10 0.119827E+11 0.806581E+10
Minimum of Months 0.262259E+09 68150481.81 0.177965E+09 0.103027E+09 0.318585E+09
Maximum of Months 0.143010E+10 0.676736E+09 0.807660E+09 0.194835E+10 0.115039E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.201828E+09 0.120063E+09 81764855.83 0.188349E+09 0.290058E+09
February 0.280528E+09 0.174052E+09 0.106476E+09 0.301485E+09 0.230128E+09
March 0.329467E+09 0.174190E+09 0.155277E+09 0.378934E+09 0.213583E+09
April 0.336907E+09 0.144591E+09 0.192316E+09 0.418115E+09 0.171216E+09
May 0.324360E+09 98887279.29 0.225472E+09 0.421488E+09 0.142618E+09
June 0.284005E+09 76010646.67 0.207994E+09 0.388009E+09 0.107347E+09
July 0.318843E+09 0.115771E+09 0.203072E+09 0.476860E+09 94169567.48
August 0.339914E+09 0.156188E+09 0.183726E+09 0.518424E+09 88985745.85
September 0.364844E+09 0.199544E+09 0.165299E+09 0.511085E+09 0.117669E+09
October 0.341034E+09 0.208792E+09 0.132241E+09 0.422692E+09 0.179698E+09
November 0.197514E+09 0.113059E+09 84455881.64 0.205664E+09 0.221653E+09
December 0.213609E+09 0.138137E+09 75471285.47 0.222329E+09 0.288424E+09
           
Annual Sum or Average 0.353285E+10 0.171929E+10 0.181357E+10 0.445343E+10 0.214555E+10
Minimum of Months 0.197514E+09 76010646.67 75471285.47 0.188349E+09 88985745.85
Maximum of Months 0.364844E+09 0.208792E+09 0.225472E+09 0.518424E+09 0.290058E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 57636175.01 0.00 57636175.01 796179.67 0.431326E+09
February 81004450.75 0.00 81004450.75 11673527.02 0.334357E+09
March 0.132147E+09 430.86 0.132146E+09 50569662.86 0.285620E+09
April 0.181596E+09 1117256.01 0.180479E+09 0.117248E+09 0.211042E+09
May 0.240746E+09 7228591.19 0.233517E+09 0.199357E+09 0.170594E+09
June 0.245191E+09 16403078.89 0.228788E+09 0.226958E+09 0.122283E+09
July 0.241154E+09 19413556.39 0.221741E+09 0.253043E+09 0.111274E+09
August 0.195480E+09 5870762.35 0.189609E+09 0.209836E+09 0.108325E+09
September 0.146419E+09 109683.05 0.146310E+09 0.116070E+09 0.162308E+09
October 0.103593E+09 0.00 0.103593E+09 44631873.54 0.241921E+09
November 63148314.43 0.00 63148314.43 7235445.82 0.317427E+09
December 48975889.39 0.00 48975889.39 271103.97 0.419713E+09
           
Annual Sum or Average 0.173709E+10 50143358.74 0.168695E+10 0.123769E+10 0.291619E+10
Minimum of Months 48975889.39 0.00 48975889.39 271103.97 0.108325E+09
Maximum of Months 0.245191E+09 19413556.39 0.233517E+09 0.253043E+09 0.431326E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 51567304.17 0.00 51567304.17 712344.96 0.385888E+09
February 72474989.01 0.00 72474989.01 10444348.86 0.299149E+09
March 0.118232E+09 385.50 0.118232E+09 45244868.97 0.255545E+09
April 0.162475E+09 999613.19 0.161475E+09 0.104902E+09 0.188820E+09
May 0.215396E+09 6467447.92 0.208929E+09 0.178365E+09 0.152631E+09
June 0.219373E+09 14675896.84 0.204698E+09 0.203061E+09 0.109407E+09
July 0.215762E+09 17369382.46 0.198392E+09 0.226398E+09 99557049.18
August 0.174897E+09 5252593.31 0.169644E+09 0.187741E+09 96918732.83
September 0.131002E+09 98133.84 0.130904E+09 0.103848E+09 0.145217E+09
October 92684987.96 0.00 92684987.96 39932306.37 0.216448E+09
November 56499036.19 0.00 56499036.19 6473580.79 0.283994E+09
December 43818913.81 0.00 43818913.81 242557.75 0.375475E+09
           
Annual Sum or Average 0.155418E+10 44863453.06 0.150932E+10 0.110737E+10 0.260905E+10
Minimum of Months 43818913.81 0.00 43818913.81 242557.75 96918732.83
Maximum of Months 0.219373E+09 17369382.46 0.208929E+09 0.226398E+09 0.385888E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.753484E+09 0.448231E+09 0.305253E+09 0.651712E+09 0.111501E+10
February 0.104729E+10 0.649789E+09 0.397505E+09 0.105250E+10 0.870523E+09
March 0.123000E+10 0.650301E+09 0.579696E+09 0.131439E+10 0.801901E+09
April 0.125777E+10 0.539802E+09 0.717972E+09 0.142918E+10 0.632623E+09
May 0.121093E+10 0.369176E+09 0.841756E+09 0.139936E+10 0.534887E+09
June 0.106028E+10 0.283770E+09 0.776505E+09 0.125413E+10 0.395177E+09
July 0.119034E+10 0.432209E+09 0.758129E+09 0.155287E+10 0.360193E+09
August 0.126900E+10 0.583096E+09 0.685904E+09 0.170941E+10 0.342791E+09
September 0.136207E+10 0.744959E+09 0.617112E+09 0.172503E+10 0.472949E+09
October 0.127318E+10 0.779484E+09 0.493697E+09 0.146411E+10 0.674332E+09
November 0.737380E+09 0.422081E+09 0.315299E+09 0.704131E+09 0.850493E+09
December 0.797464E+09 0.515707E+09 0.281757E+09 0.775652E+09 0.110799E+10
           
Annual Sum or Average 0.131892E+11 0.641861E+10 0.677058E+10 0.150325E+11 0.815888E+10
Minimum of Months 0.737380E+09 0.283770E+09 0.281757E+09 0.651712E+09 0.342791E+09
Maximum of Months 0.136207E+10 0.779484E+09 0.841756E+09 0.172503E+10 0.111501E+10



Table of Contents

Report: WindowZoneSummaryMonthly

For: BASEMENT

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 337.78 510.06 381.12 226.72 154.40 0.00 0.00
February 596.42 447.88 586.49 363.88 222.60 0.00 0.00
March 670.22 372.79 622.14 328.93 293.21 0.00 0.00
April 757.86 299.99 657.40 282.14 375.26 0.00 0.00
May 725.14 238.83 612.50 186.73 425.76 0.00 0.00
June 678.90 176.85 554.17 148.32 405.85 0.00 0.00
July 803.01 156.93 602.08 218.62 383.46 0.00 0.00
August 876.28 151.61 641.87 294.94 346.93 0.00 0.00
September 903.95 224.72 711.91 389.37 322.54 0.00 0.00
October 744.27 315.16 643.99 394.27 249.72 0.00 0.00
November 373.43 403.85 385.41 220.61 164.80 0.00 0.00
December 395.63 512.02 403.36 260.85 142.51 0.00 0.00
               
Annual Sum or Average 655.47 316.94 566.59 275.74 290.86 0.00 0.00
Minimum of Months 337.78 151.61 381.12 148.32 142.51 0.00 0.00
Maximum of Months 903.95 512.02 711.91 394.27 425.76 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: MECH_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 936.50 1482.97 1073.21 638.43 434.78 0.00 0.00
February 1656.80 1315.40 1651.51 1024.67 626.84 0.00 0.00
March 1862.36 1116.51 1751.91 926.24 825.67 0.00 0.00
April 2102.59 910.80 1851.19 794.48 1056.71 0.00 0.00
May 2007.99 735.25 1724.75 525.83 1198.93 0.00 0.00
June 1871.57 560.95 1560.51 417.65 1142.85 0.00 0.00
July 2226.63 497.33 1695.42 615.61 1079.81 0.00 0.00
August 2435.47 484.34 1807.46 830.52 976.94 0.00 0.00
September 2516.26 697.80 2004.70 1096.43 908.26 0.00 0.00
October 2068.81 961.74 1813.42 1110.24 703.18 0.00 0.00
November 1034.07 1194.93 1085.28 621.22 464.06 0.00 0.00
December 1099.33 1493.07 1135.85 734.54 401.31 0.00 0.00
               
Annual Sum or Average 1818.84 952.53 1595.49 776.46 819.03 0.00 0.00
Minimum of Months 936.50 484.34 1073.21 417.65 401.31 0.00 0.00
Maximum of Months 2516.26 1493.07 2004.70 1110.24 1198.93 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1224.42 2057.81 1394.16 829.35 564.80 0.00 0.00
February 2176.56 1814.82 2145.41 1331.11 814.30 0.00 0.00
March 2450.89 1546.67 2275.84 1203.24 1072.60 0.00 0.00
April 2768.32 1260.23 2404.80 1032.08 1372.72 0.00 0.00
May 2639.00 1026.63 2240.55 683.08 1557.47 0.00 0.00
June 2453.89 786.67 2027.19 542.56 1484.63 0.00 0.00
July 2931.38 692.15 2202.45 799.71 1402.74 0.00 0.00
August 3208.13 668.38 2348.00 1078.89 1269.10 0.00 0.00
September 3312.20 964.49 2604.21 1424.33 1179.88 0.00 0.00
October 2719.76 1336.74 2355.74 1442.27 913.47 0.00 0.00
November 1349.03 1673.41 1409.84 807.00 602.84 0.00 0.00
December 1440.04 2072.48 1475.53 954.20 521.33 0.00 0.00
               
Annual Sum or Average 2390.33 1322.70 2072.64 1008.67 1063.97 0.00 0.00
Minimum of Months 1224.42 668.38 1394.16 542.56 521.33 0.00 0.00
Maximum of Months 3312.20 2072.48 2604.21 1442.27 1557.47 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 81.08 301.12 129.45 60.92 68.53 0.00 0.00
February 176.40 261.81 212.46 108.17 104.29 0.00 0.00
March 243.72 215.16 258.19 110.74 147.45 0.00 0.00
April 358.27 170.08 335.40 134.22 201.18 0.00 0.00
May 441.01 134.78 385.94 144.74 241.20 0.00 0.00
June 429.32 98.01 363.72 127.82 235.90 0.00 0.00
July 559.68 83.91 433.22 208.32 224.90 0.00 0.00
August 511.44 78.94 386.93 190.94 195.99 0.00 0.00
September 432.29 123.91 353.19 179.17 174.02 0.00 0.00
October 259.23 180.16 248.81 127.89 120.92 0.00 0.00
November 103.77 235.59 136.36 60.72 75.64 0.00 0.00
December 98.08 299.24 130.54 69.20 61.33 0.00 0.00
               
Annual Sum or Average 308.69 181.51 281.57 127.07 154.50 0.00 0.00
Minimum of Months 81.08 78.94 129.45 60.72 61.33 0.00 0.00
Maximum of Months 559.68 301.12 433.22 208.32 241.20 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 20.97 316.52 71.09 16.09 55.00 0.00 0.00
February 70.33 272.68 122.94 36.23 86.71 0.00 0.00
March 132.78 216.92 174.14 45.71 128.44 0.00 0.00
April 250.21 168.99 260.74 78.78 181.96 0.00 0.00
May 357.21 134.61 335.81 109.95 225.86 0.00 0.00
June 363.50 98.49 328.84 103.49 225.36 0.00 0.00
July 470.96 87.42 385.28 170.82 214.46 0.00 0.00
August 399.59 81.61 317.65 134.35 183.29 0.00 0.00
September 288.97 128.33 257.04 102.22 154.82 0.00 0.00
October 131.09 182.29 152.02 49.94 102.08 0.00 0.00
November 36.66 242.74 79.40 17.10 62.30 0.00 0.00
December 26.02 311.68 65.22 17.63 47.59 0.00 0.00
               
Annual Sum or Average 213.28 186.45 213.04 73.81 139.23 0.00 0.00
Minimum of Months 20.97 81.61 65.22 16.09 47.59 0.00 0.00
Maximum of Months 470.96 316.52 385.28 170.82 225.86 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 51.65 88.32 60.27 35.85 24.42 0.00 0.00
February 87.86 89.57 92.75 57.55 35.20 0.00 0.00
March 96.33 85.78 98.39 52.02 46.37 0.00 0.00
April 107.18 71.55 103.96 44.62 59.34 0.00 0.00
May 101.17 59.09 96.86 29.53 67.33 0.00 0.00
June 92.49 46.63 87.64 23.46 64.18 0.00 0.00
July 113.99 41.67 95.22 34.57 60.64 0.00 0.00
August 126.47 40.53 101.51 46.64 54.87 0.00 0.00
September 132.81 55.81 112.58 61.58 51.01 0.00 0.00
October 107.77 76.20 101.84 62.35 39.49 0.00 0.00
November 52.58 88.67 60.95 34.89 26.06 0.00 0.00
December 59.39 94.90 63.79 41.25 22.54 0.00 0.00
               
Annual Sum or Average 94.17 69.78 89.60 43.61 46.00 0.00 0.00
Minimum of Months 51.65 40.53 60.27 23.46 22.54 0.00 0.00
Maximum of Months 132.81 94.90 112.58 62.35 67.33 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.26 97.33 13.60 0.00 13.60 0.00 0.00
February 3.57 83.18 21.15 0.00 21.15 0.00 0.00
March 13.35 64.37 31.17 0.00 31.17 0.00 0.00
April 30.89 48.17 44.26 0.27 43.99 0.00 0.00
May 50.28 36.54 56.79 1.71 55.08 0.00 0.00
June 59.42 26.22 59.76 4.00 55.77 0.00 0.00
July 64.59 22.19 56.88 4.58 52.30 0.00 0.00
August 54.50 20.82 46.11 1.38 44.72 0.00 0.00
September 31.56 34.99 35.69 0.03 35.66 0.00 0.00
October 12.20 53.47 24.44 0.00 24.44 0.00 0.00
November 2.09 73.94 15.39 0.00 15.39 0.00 0.00
December 0.11 94.80 11.55 0.00 11.55 0.00 0.00
               
Annual Sum or Average 27.05 54.53 34.80 1.00 33.80 0.00 0.00
Minimum of Months 0.11 20.82 11.55 0.00 11.55 0.00 0.00
Maximum of Months 64.59 97.33 59.76 4.58 55.77 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 75.83 299.67 126.12 57.55 68.57 0.00 0.00
February 170.32 259.63 209.48 105.07 104.41 0.00 0.00
March 245.45 210.83 263.18 115.86 147.31 0.00 0.00
April 366.17 164.22 346.47 145.62 200.85 0.00 0.00
May 391.32 130.93 351.61 117.18 234.43 0.00 0.00
June 455.95 94.25 385.46 149.40 236.05 0.00 0.00
July 477.36 77.81 376.34 158.90 217.43 0.00 0.00
August 496.21 73.71 379.48 184.65 194.83 0.00 0.00
September 391.97 119.09 327.80 163.40 164.40 0.00 0.00
October 258.16 177.51 249.63 130.21 119.42 0.00 0.00
November 102.06 233.85 136.05 60.57 75.49 0.00 0.00
December 93.61 296.35 128.71 67.31 61.40 0.00 0.00
               
Annual Sum or Average 294.33 177.76 273.61 121.35 152.25 0.00 0.00
Minimum of Months 75.83 73.71 126.12 57.55 61.40 0.00 0.00
Maximum of Months 496.21 299.67 385.46 184.65 236.05 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 13.70 313.10 67.76 12.72 55.04 0.00 0.00
February 60.22 266.06 119.97 33.13 86.84 0.00 0.00
March 131.81 209.68 179.13 50.83 128.30 0.00 0.00
April 257.58 162.42 271.81 90.18 181.63 0.00 0.00
May 311.23 130.23 301.48 82.39 219.09 0.00 0.00
June 394.12 95.74 350.58 125.07 225.51 0.00 0.00
July 393.54 80.24 328.39 121.40 206.99 0.00 0.00
August 385.54 77.02 310.20 128.07 182.13 0.00 0.00
September 250.25 120.84 231.65 86.45 145.20 0.00 0.00
October 127.84 176.86 152.84 52.26 100.59 0.00 0.00
November 33.04 238.83 79.09 16.95 62.14 0.00 0.00
December 18.63 305.78 63.40 15.74 47.66 0.00 0.00
               
Annual Sum or Average 198.87 181.00 205.07 68.09 136.98 0.00 0.00
Minimum of Months 13.70 77.02 63.40 12.72 47.66 0.00 0.00
Maximum of Months 394.12 313.10 350.58 128.07 225.51 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 99.21 387.46 160.04 77.69 82.36 0.00 0.00
February 200.21 333.72 246.79 124.69 122.10 0.00 0.00
March 258.42 273.88 280.70 112.71 168.00 0.00 0.00
April 328.78 216.89 321.15 97.26 223.88 0.00 0.00
May 355.45 172.87 332.89 67.68 265.22 0.00 0.00
June 356.73 126.73 319.36 59.48 259.87 0.00 0.00
July 410.89 110.93 329.53 84.83 244.70 0.00 0.00
August 415.04 108.51 319.83 104.06 215.77 0.00 0.00
September 379.19 165.80 321.25 133.47 187.78 0.00 0.00
October 280.12 230.81 273.60 135.10 138.50 0.00 0.00
November 124.79 301.52 165.40 75.59 89.81 0.00 0.00
December 121.90 382.70 163.24 89.38 73.86 0.00 0.00
               
Annual Sum or Average 277.98 233.85 269.53 96.66 172.88 0.00 0.00
Minimum of Months 99.21 108.51 160.04 59.48 73.86 0.00 0.00
Maximum of Months 415.04 387.46 332.89 135.10 265.22 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 81.65 298.72 129.45 60.92 68.53 0.00 0.00
February 176.08 259.93 212.46 108.17 104.29 0.00 0.00
March 242.21 213.73 258.19 110.74 147.45 0.00 0.00
April 354.60 169.66 335.40 134.22 201.18 0.00 0.00
May 436.22 134.22 385.94 144.74 241.20 0.00 0.00
June 424.43 97.38 363.72 127.82 235.90 0.00 0.00
July 554.38 83.26 433.22 208.32 224.90 0.00 0.00
August 507.51 77.79 386.93 190.94 195.99 0.00 0.00
September 429.65 122.40 353.19 179.17 174.02 0.00 0.00
October 257.86 178.16 248.81 127.89 120.92 0.00 0.00
November 103.97 233.09 136.36 60.72 75.64 0.00 0.00
December 98.46 296.14 130.54 69.20 61.33 0.00 0.00
               
Annual Sum or Average 306.40 179.99 281.57 127.07 154.50 0.00 0.00
Minimum of Months 81.65 77.79 129.45 60.72 61.33 0.00 0.00
Maximum of Months 554.38 298.72 433.22 208.32 241.20 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 21.46 313.66 71.09 16.09 55.00 0.00 0.00
February 70.74 270.39 122.94 36.23 86.71 0.00 0.00
March 132.26 215.05 174.14 45.71 128.44 0.00 0.00
April 247.42 168.58 260.74 78.78 181.96 0.00 0.00
May 351.95 135.29 335.81 109.95 225.86 0.00 0.00
June 357.75 99.42 328.84 103.49 225.36 0.00 0.00
July 464.53 89.04 385.28 170.82 214.46 0.00 0.00
August 395.87 81.62 317.65 134.35 183.29 0.00 0.00
September 286.14 128.30 257.04 102.22 154.82 0.00 0.00
October 130.88 179.79 152.02 49.94 102.08 0.00 0.00
November 37.19 239.65 79.40 17.10 62.30 0.00 0.00
December 26.58 307.86 65.22 17.63 47.59 0.00 0.00
               
Annual Sum or Average 211.14 185.32 213.04 73.81 139.23 0.00 0.00
Minimum of Months 21.46 81.62 65.22 16.09 47.59 0.00 0.00
Maximum of Months 464.53 313.66 385.28 170.82 225.86 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 94.98 155.59 110.51 65.74 44.77 0.00 0.00
February 168.51 136.58 170.06 105.52 64.55 0.00 0.00
March 189.89 113.49 180.40 95.38 85.02 0.00 0.00
April 214.12 90.67 190.63 81.81 108.82 0.00 0.00
May 205.24 70.60 177.61 54.15 123.46 0.00 0.00
June 192.34 50.74 160.69 43.01 117.69 0.00 0.00
July 231.30 42.37 174.59 63.39 111.20 0.00 0.00
August 253.83 39.54 186.12 85.52 100.60 0.00 0.00
September 261.36 63.37 206.43 112.91 93.53 0.00 0.00
October 211.95 94.08 186.74 114.33 72.41 0.00 0.00
November 105.73 122.62 111.76 63.97 47.79 0.00 0.00
December 112.33 154.63 116.96 75.64 41.33 0.00 0.00
               
Annual Sum or Average 186.88 94.32 164.30 79.96 84.34 0.00 0.00
Minimum of Months 94.98 39.54 110.51 43.01 41.33 0.00 0.00
Maximum of Months 261.36 155.59 206.43 114.33 123.46 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.51 1002.39 118.94 0.00 118.94 0.00 0.00
February 18.70 868.16 185.07 0.00 185.07 0.00 0.00
March 83.59 679.19 272.70 0.00 272.70 0.00 0.00
April 219.62 515.73 387.23 2.38 384.85 0.00 0.00
May 378.21 393.01 496.80 14.92 481.88 0.00 0.00
June 452.63 287.79 522.84 34.98 487.86 0.00 0.00
July 502.37 248.59 497.64 40.06 457.58 0.00 0.00
August 416.97 242.72 403.39 12.11 391.28 0.00 0.00
September 230.69 382.98 312.22 0.23 311.99 0.00 0.00
October 74.74 582.09 213.77 0.00 213.77 0.00 0.00
November 9.37 785.31 134.66 0.00 134.66 0.00 0.00
December 0.13 979.37 101.07 0.00 101.07 0.00 0.00
               
Annual Sum or Average 200.12 579.21 304.45 8.79 295.66 0.00 0.00
Minimum of Months 0.13 242.72 101.07 0.00 101.07 0.00 0.00
Maximum of Months 502.37 1002.39 522.84 40.06 487.86 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DINING_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.26 1034.72 118.94 0.00 118.94 0.00 0.00
February 16.38 896.97 185.07 0.00 185.07 0.00 0.00
March 75.82 699.37 272.70 0.00 272.70 0.00 0.00
April 208.97 529.62 387.23 2.38 384.85 0.00 0.00
May 367.27 402.57 496.80 14.92 481.88 0.00 0.00
June 441.43 295.19 522.84 34.98 487.86 0.00 0.00
July 492.82 255.34 497.64 40.06 457.58 0.00 0.00
August 407.71 250.12 403.39 12.11 391.28 0.00 0.00
September 222.41 394.00 312.22 0.23 311.99 0.00 0.00
October 67.90 601.10 213.77 0.00 213.77 0.00 0.00
November 7.82 813.57 134.66 0.00 134.66 0.00 0.00
December 0.07 1011.20 101.07 0.00 101.07 0.00 0.00
               
Annual Sum or Average 193.55 597.19 304.45 8.79 295.66 0.00 0.00
Minimum of Months 0.07 250.12 101.07 0.00 101.07 0.00 0.00
Maximum of Months 492.82 1034.72 522.84 40.06 487.86 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 91.67 639.49 193.88 70.27 123.61 0.00 0.00
February 249.51 553.65 329.44 138.20 191.24 0.00 0.00
March 420.76 451.35 442.28 166.68 275.60 0.00 0.00
April 699.24 360.06 618.24 235.78 382.46 0.00 0.00
May 796.99 293.23 653.06 199.56 453.50 0.00 0.00
June 961.33 224.75 736.00 274.46 461.54 0.00 0.00
July 992.38 190.02 704.69 280.29 424.40 0.00 0.00
August 1003.33 182.31 689.64 312.71 376.94 0.00 0.00
September 739.45 255.84 559.42 249.84 309.58 0.00 0.00
October 435.87 383.67 402.46 182.46 220.00 0.00 0.00
November 153.92 499.91 215.14 77.51 137.62 0.00 0.00
December 120.10 629.98 192.11 83.05 109.06 0.00 0.00
               
Annual Sum or Average 556.98 387.92 478.66 189.43 289.22 0.00 0.00
Minimum of Months 91.67 182.31 192.11 70.27 109.06 0.00 0.00
Maximum of Months 1003.33 639.49 736.00 312.71 461.54 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 219.11 696.63 322.09 167.35 154.74 0.00 0.00
February 423.45 600.95 496.35 268.60 227.75 0.00 0.00
March 521.84 496.77 552.71 242.80 309.91 0.00 0.00
April 636.31 397.56 618.00 209.07 408.92 0.00 0.00
May 660.28 317.18 622.41 142.95 479.47 0.00 0.00
June 644.30 236.39 588.29 121.47 466.82 0.00 0.00
July 753.15 207.57 615.01 175.10 439.91 0.00 0.00
August 784.58 202.53 612.07 221.86 390.22 0.00 0.00
September 749.54 300.28 632.52 287.49 345.03 0.00 0.00
October 572.56 417.26 548.63 291.03 257.61 0.00 0.00
November 263.20 546.41 330.64 162.84 167.80 0.00 0.00
December 266.94 687.72 332.38 192.54 139.84 0.00 0.00
               
Annual Sum or Average 541.89 424.77 522.59 206.55 316.05 0.00 0.00
Minimum of Months 219.11 202.53 322.09 121.47 139.84 0.00 0.00
Maximum of Months 784.58 696.63 632.52 291.03 479.47 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BASEMENT

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.904710E+09 0.136614E+10 0.102079E+10 0.607247E+09 0.413543E+09 0.00 0.00
February 0.144286E+10 0.108351E+10 0.141883E+10 0.880309E+09 0.538522E+09 0.00 0.00
March 0.179511E+10 0.998468E+09 0.166635E+10 0.881003E+09 0.785345E+09 0.00 0.00
April 0.196437E+10 0.777568E+09 0.170398E+10 0.731303E+09 0.972674E+09 0.00 0.00
May 0.194222E+10 0.639693E+09 0.164051E+10 0.500145E+09 0.114037E+10 0.00 0.00
June 0.175971E+10 0.458393E+09 0.143641E+10 0.384441E+09 0.105197E+10 0.00 0.00
July 0.215079E+10 0.420315E+09 0.161261E+10 0.585540E+09 0.102707E+10 0.00 0.00
August 0.234704E+10 0.406070E+09 0.171918E+10 0.789956E+09 0.929228E+09 0.00 0.00
September 0.234305E+10 0.582473E+09 0.184527E+10 0.100924E+10 0.836033E+09 0.00 0.00
October 0.199345E+10 0.844130E+09 0.172485E+10 0.105602E+10 0.668837E+09 0.00 0.00
November 0.967933E+09 0.104679E+10 0.998973E+09 0.571820E+09 0.427153E+09 0.00 0.00
December 0.105965E+10 0.137139E+10 0.108037E+10 0.698661E+09 0.381712E+09 0.00 0.00
               
Annual Sum or Average 0.206709E+11 0.999494E+10 0.178681E+11 0.869568E+10 0.917246E+10 0.00 0.00
Minimum of Months 0.904710E+09 0.406070E+09 0.998973E+09 0.384441E+09 0.381712E+09 0.00 0.00
Maximum of Months 0.234704E+10 0.137139E+10 0.184527E+10 0.105602E+10 0.114037E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: MECH_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.250833E+10 0.397198E+10 0.287448E+10 0.170997E+10 0.116451E+10 0.00 0.00
February 0.400813E+10 0.318222E+10 0.399533E+10 0.247889E+10 0.151644E+10 0.00 0.00
March 0.498816E+10 0.299046E+10 0.469233E+10 0.248085E+10 0.221148E+10 0.00 0.00
April 0.544990E+10 0.236078E+10 0.479829E+10 0.205930E+10 0.273898E+10 0.00 0.00
May 0.537820E+10 0.196930E+10 0.461958E+10 0.140838E+10 0.321120E+10 0.00 0.00
June 0.485112E+10 0.145398E+10 0.404484E+10 0.108256E+10 0.296227E+10 0.00 0.00
July 0.596381E+10 0.133206E+10 0.454101E+10 0.164884E+10 0.289217E+10 0.00 0.00
August 0.652316E+10 0.129727E+10 0.484111E+10 0.222446E+10 0.261664E+10 0.00 0.00
September 0.652216E+10 0.180869E+10 0.519617E+10 0.284196E+10 0.235421E+10 0.00 0.00
October 0.554110E+10 0.257592E+10 0.485707E+10 0.297367E+10 0.188340E+10 0.00 0.00
November 0.268032E+10 0.309726E+10 0.281304E+10 0.161021E+10 0.120283E+10 0.00 0.00
December 0.294443E+10 0.399904E+10 0.304226E+10 0.196738E+10 0.107488E+10 0.00 0.00
               
Annual Sum or Average 0.573588E+11 0.300390E+11 0.503155E+11 0.244865E+11 0.258290E+11 0.00 0.00
Minimum of Months 0.250833E+10 0.129727E+10 0.281304E+10 0.108256E+10 0.107488E+10 0.00 0.00
Maximum of Months 0.652316E+10 0.399904E+10 0.519617E+10 0.297367E+10 0.321120E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.327949E+10 0.551163E+10 0.373411E+10 0.222134E+10 0.151276E+10 0.00 0.00
February 0.526553E+10 0.439041E+10 0.519017E+10 0.322022E+10 0.196994E+10 0.00 0.00
March 0.656445E+10 0.414259E+10 0.609560E+10 0.322276E+10 0.287284E+10 0.00 0.00
April 0.717549E+10 0.326652E+10 0.623325E+10 0.267515E+10 0.355810E+10 0.00 0.00
May 0.706830E+10 0.274973E+10 0.600109E+10 0.182956E+10 0.417153E+10 0.00 0.00
June 0.636049E+10 0.203906E+10 0.525447E+10 0.140631E+10 0.384816E+10 0.00 0.00
July 0.785141E+10 0.185386E+10 0.589903E+10 0.214194E+10 0.375709E+10 0.00 0.00
August 0.859266E+10 0.179019E+10 0.628888E+10 0.288971E+10 0.339917E+10 0.00 0.00
September 0.858522E+10 0.249996E+10 0.675012E+10 0.369187E+10 0.305826E+10 0.00 0.00
October 0.728462E+10 0.358031E+10 0.630961E+10 0.386297E+10 0.244665E+10 0.00 0.00
November 0.349668E+10 0.433748E+10 0.365430E+10 0.209175E+10 0.156255E+10 0.00 0.00
December 0.385700E+10 0.555093E+10 0.395207E+10 0.255574E+10 0.139632E+10 0.00 0.00
               
Annual Sum or Average 0.753813E+11 0.417127E+11 0.653627E+11 0.318093E+11 0.335534E+11 0.00 0.00
Minimum of Months 0.327949E+10 0.179019E+10 0.365430E+10 0.140631E+10 0.139632E+10 0.00 0.00
Maximum of Months 0.859266E+10 0.555093E+10 0.675012E+10 0.386297E+10 0.417153E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.217174E+09 0.806526E+09 0.346724E+09 0.163167E+09 0.183558E+09 0.00 0.00
February 0.426757E+09 0.633368E+09 0.513985E+09 0.261695E+09 0.252290E+09 0.00 0.00
March 0.652789E+09 0.576278E+09 0.691549E+09 0.296606E+09 0.394943E+09 0.00 0.00
April 0.928647E+09 0.440838E+09 0.869359E+09 0.347902E+09 0.521457E+09 0.00 0.00
May 0.118119E+10 0.360991E+09 0.103370E+10 0.387673E+09 0.646029E+09 0.00 0.00
June 0.111279E+10 0.254035E+09 0.942761E+09 0.331299E+09 0.611462E+09 0.00 0.00
July 0.149905E+10 0.224737E+09 0.116035E+10 0.557965E+09 0.602380E+09 0.00 0.00
August 0.136985E+10 0.211427E+09 0.103634E+10 0.511407E+09 0.524936E+09 0.00 0.00
September 0.112050E+10 0.321169E+09 0.915471E+09 0.464417E+09 0.451054E+09 0.00 0.00
October 0.694317E+09 0.482531E+09 0.666417E+09 0.342553E+09 0.323863E+09 0.00 0.00
November 0.268962E+09 0.610660E+09 0.353457E+09 0.157390E+09 0.196067E+09 0.00 0.00
December 0.262693E+09 0.801494E+09 0.349625E+09 0.185355E+09 0.164270E+09 0.00 0.00
               
Annual Sum or Average 0.973473E+10 0.572405E+10 0.887974E+10 0.400743E+10 0.487231E+10 0.00 0.00
Minimum of Months 0.217174E+09 0.211427E+09 0.346724E+09 0.157390E+09 0.164270E+09 0.00 0.00
Maximum of Months 0.149905E+10 0.806526E+09 0.116035E+10 0.557965E+09 0.646029E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 56159025.65 0.847775E+09 0.190407E+09 43103720.32 0.147303E+09 0.00 0.00
February 0.170151E+09 0.659667E+09 0.297420E+09 87642964.17 0.209777E+09 0.00 0.00
March 0.355645E+09 0.580994E+09 0.466427E+09 0.122417E+09 0.344011E+09 0.00 0.00
April 0.648551E+09 0.438026E+09 0.675843E+09 0.204193E+09 0.471650E+09 0.00 0.00
May 0.956747E+09 0.360552E+09 0.899439E+09 0.294493E+09 0.604946E+09 0.00 0.00
June 0.942179E+09 0.255293E+09 0.852363E+09 0.268241E+09 0.584122E+09 0.00 0.00
July 0.126142E+10 0.234136E+09 0.103192E+10 0.457523E+09 0.574398E+09 0.00 0.00
August 0.107027E+10 0.218594E+09 0.850783E+09 0.359854E+09 0.490929E+09 0.00 0.00
September 0.749014E+09 0.332644E+09 0.666243E+09 0.264960E+09 0.401283E+09 0.00 0.00
October 0.351109E+09 0.488257E+09 0.407182E+09 0.133761E+09 0.273421E+09 0.00 0.00
November 95028185.43 0.629195E+09 0.205806E+09 44331374.38 0.161474E+09 0.00 0.00
December 69682752.85 0.834797E+09 0.174689E+09 47217705.85 0.127471E+09 0.00 0.00
               
Annual Sum or Average 0.672596E+10 0.587993E+10 0.671852E+10 0.232774E+10 0.439079E+10 0.00 0.00
Minimum of Months 56159025.65 0.218594E+09 0.174689E+09 43103720.32 0.127471E+09 0.00 0.00
Maximum of Months 0.126142E+10 0.847775E+09 0.103192E+10 0.457523E+09 0.604946E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.138345E+09 0.236559E+09 0.161430E+09 96031370.32 65398878.59 0.00 0.00
February 0.212559E+09 0.216680E+09 0.224378E+09 0.139214E+09 85163535.41 0.00 0.00
March 0.258003E+09 0.229742E+09 0.263521E+09 0.139324E+09 0.124197E+09 0.00 0.00
April 0.277818E+09 0.185456E+09 0.269472E+09 0.115650E+09 0.153822E+09 0.00 0.00
May 0.270975E+09 0.158277E+09 0.259436E+09 79094093.75 0.180342E+09 0.00 0.00
June 0.239743E+09 0.120867E+09 0.227159E+09 60796426.56 0.166362E+09 0.00 0.00
July 0.305305E+09 0.111608E+09 0.255024E+09 92598617.16 0.162425E+09 0.00 0.00
August 0.338731E+09 0.108565E+09 0.271877E+09 0.124925E+09 0.146952E+09 0.00 0.00
September 0.344240E+09 0.144658E+09 0.291817E+09 0.159604E+09 0.132213E+09 0.00 0.00
October 0.288663E+09 0.204107E+09 0.272773E+09 0.167001E+09 0.105772E+09 0.00 0.00
November 0.136284E+09 0.229820E+09 0.157980E+09 90428875.66 67551271.18 0.00 0.00
December 0.159073E+09 0.254175E+09 0.170853E+09 0.110488E+09 60365023.40 0.00 0.00
               
Annual Sum or Average 0.296974E+10 0.220052E+10 0.282572E+10 0.137516E+10 0.145056E+10 0.00 0.00
Minimum of Months 0.136284E+09 0.108565E+09 0.157980E+09 60796426.56 60365023.40 0.00 0.00
Maximum of Months 0.344240E+09 0.254175E+09 0.291817E+09 0.167001E+09 0.180342E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 701082.84 0.260699E+09 36413225.08 0.00 36413225.08 0.00 0.00
February 8639307.11 0.201232E+09 51176770.43 0.00 51176770.43 0.00 0.00
March 35761776.39 0.172401E+09 83487367.90 272.21 83487095.69 0.00 0.00
April 80075429.18 0.124862E+09 0.114728E+09 705856.95 0.114022E+09 0.00 0.00
May 0.134657E+09 97864401.29 0.152098E+09 4566859.58 0.147531E+09 0.00 0.00
June 0.154022E+09 67958831.48 0.154906E+09 10363092.34 0.144543E+09 0.00 0.00
July 0.172989E+09 59434891.13 0.152356E+09 12265043.58 0.140091E+09 0.00 0.00
August 0.145977E+09 55768778.77 0.123500E+09 3709014.18 0.119791E+09 0.00 0.00
September 81808772.32 90686870.81 92504439.09 69295.25 92435143.84 0.00 0.00
October 32680784.65 0.143225E+09 65447658.79 0.00 65447658.79 0.00 0.00
November 5412035.22 0.191644E+09 39895669.45 0.00 39895669.45 0.00 0.00
December 287529.25 0.253911E+09 30941853.50 0.00 30941853.50 0.00 0.00
               
Annual Sum or Average 0.853012E+09 0.171969E+10 0.109745E+10 31679434.09 0.106578E+10 0.00 0.00
Minimum of Months 287529.25 55768778.77 30941853.50 0.00 30941853.50 0.00 0.00
Maximum of Months 0.172989E+09 0.260699E+09 0.154906E+09 12265043.58 0.147531E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.203109E+09 0.802646E+09 0.337811E+09 0.154141E+09 0.183670E+09 0.00 0.00
February 0.412048E+09 0.628085E+09 0.506786E+09 0.254193E+09 0.252592E+09 0.00 0.00
March 0.657400E+09 0.564688E+09 0.704892E+09 0.310326E+09 0.394567E+09 0.00 0.00
April 0.949108E+09 0.425665E+09 0.898041E+09 0.377444E+09 0.520597E+09 0.00 0.00
May 0.104810E+10 0.350693E+09 0.941749E+09 0.313851E+09 0.627898E+09 0.00 0.00
June 0.118182E+10 0.244304E+09 0.999105E+09 0.387252E+09 0.611853E+09 0.00 0.00
July 0.127857E+10 0.208414E+09 0.100798E+10 0.425606E+09 0.582376E+09 0.00 0.00
August 0.132904E+10 0.197437E+09 0.101640E+10 0.494580E+09 0.521820E+09 0.00 0.00
September 0.101599E+10 0.308677E+09 0.849659E+09 0.423537E+09 0.426122E+09 0.00 0.00
October 0.691449E+09 0.475455E+09 0.668615E+09 0.348763E+09 0.319852E+09 0.00 0.00
November 0.264530E+09 0.606151E+09 0.352653E+09 0.156990E+09 0.195662E+09 0.00 0.00
December 0.250718E+09 0.793733E+09 0.344747E+09 0.180287E+09 0.164460E+09 0.00 0.00
               
Annual Sum or Average 0.928187E+10 0.560595E+10 0.862844E+10 0.382697E+10 0.480147E+10 0.00 0.00
Minimum of Months 0.203109E+09 0.197437E+09 0.337811E+09 0.154141E+09 0.164460E+09 0.00 0.00
Maximum of Months 0.132904E+10 0.802646E+09 0.101640E+10 0.494580E+09 0.627898E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 36688979.34 0.838610E+09 0.181494E+09 34077660.85 0.147416E+09 0.00 0.00
February 0.145687E+09 0.643659E+09 0.290220E+09 80141237.88 0.210079E+09 0.00 0.00
March 0.353037E+09 0.561600E+09 0.479771E+09 0.136136E+09 0.343635E+09 0.00 0.00
April 0.667648E+09 0.420996E+09 0.704526E+09 0.233735E+09 0.470791E+09 0.00 0.00
May 0.833604E+09 0.348802E+09 0.807486E+09 0.220672E+09 0.586815E+09 0.00 0.00
June 0.102155E+10 0.248166E+09 0.908707E+09 0.324193E+09 0.584513E+09 0.00 0.00
July 0.105405E+10 0.214921E+09 0.879557E+09 0.325164E+09 0.554394E+09 0.00 0.00
August 0.103264E+10 0.206286E+09 0.830840E+09 0.343027E+09 0.487813E+09 0.00 0.00
September 0.648638E+09 0.313229E+09 0.600430E+09 0.224079E+09 0.376351E+09 0.00 0.00
October 0.342399E+09 0.473707E+09 0.409380E+09 0.139970E+09 0.269410E+09 0.00 0.00
November 85627052.90 0.619059E+09 0.205001E+09 43931896.31 0.161070E+09 0.00 0.00
December 49911332.63 0.819012E+09 0.169811E+09 42150042.10 0.127661E+09 0.00 0.00
               
Annual Sum or Average 0.627148E+10 0.570805E+10 0.646722E+10 0.214728E+10 0.431995E+10 0.00 0.00
Minimum of Months 36688979.34 0.206286E+09 0.169811E+09 34077660.85 0.127661E+09 0.00 0.00
Maximum of Months 0.105405E+10 0.838610E+09 0.908707E+09 0.343027E+09 0.586815E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.265727E+09 0.103778E+10 0.428658E+09 0.208073E+09 0.220584E+09 0.00 0.00
February 0.484337E+09 0.807338E+09 0.597030E+09 0.301638E+09 0.295392E+09 0.00 0.00
March 0.692152E+09 0.733564E+09 0.751838E+09 0.301877E+09 0.449962E+09 0.00 0.00
April 0.852204E+09 0.562171E+09 0.832411E+09 0.252110E+09 0.580300E+09 0.00 0.00
May 0.952029E+09 0.463003E+09 0.891621E+09 0.181268E+09 0.710352E+09 0.00 0.00
June 0.924653E+09 0.328490E+09 0.827769E+09 0.154179E+09 0.673590E+09 0.00 0.00
July 0.110053E+10 0.297102E+09 0.882620E+09 0.227206E+09 0.655414E+09 0.00 0.00
August 0.111165E+10 0.290638E+09 0.856624E+09 0.278714E+09 0.577911E+09 0.00 0.00
September 0.982862E+09 0.429751E+09 0.832682E+09 0.345967E+09 0.486715E+09 0.00 0.00
October 0.750268E+09 0.618209E+09 0.732804E+09 0.361844E+09 0.370960E+09 0.00 0.00
November 0.323464E+09 0.781527E+09 0.428726E+09 0.195934E+09 0.232792E+09 0.00 0.00
December 0.326492E+09 0.102502E+10 0.437221E+09 0.239396E+09 0.197825E+09 0.00 0.00
               
Annual Sum or Average 0.876638E+10 0.737459E+10 0.850000E+10 0.304821E+10 0.545180E+10 0.00 0.00
Minimum of Months 0.265727E+09 0.290638E+09 0.428658E+09 0.154179E+09 0.197825E+09 0.00 0.00
Maximum of Months 0.111165E+10 0.103778E+10 0.891621E+09 0.361844E+09 0.710352E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.218697E+09 0.800099E+09 0.346724E+09 0.163167E+09 0.183558E+09 0.00 0.00
February 0.425974E+09 0.628813E+09 0.513985E+09 0.261695E+09 0.252290E+09 0.00 0.00
March 0.648728E+09 0.572452E+09 0.691549E+09 0.296606E+09 0.394943E+09 0.00 0.00
April 0.919133E+09 0.439746E+09 0.869359E+09 0.347902E+09 0.521457E+09 0.00 0.00
May 0.116836E+10 0.359483E+09 0.103370E+10 0.387673E+09 0.646029E+09 0.00 0.00
June 0.110014E+10 0.252399E+09 0.942761E+09 0.331299E+09 0.611462E+09 0.00 0.00
July 0.148485E+10 0.222992E+09 0.116035E+10 0.557965E+09 0.602380E+09 0.00 0.00
August 0.135932E+10 0.208347E+09 0.103634E+10 0.511407E+09 0.524936E+09 0.00 0.00
September 0.111366E+10 0.317253E+09 0.915471E+09 0.464417E+09 0.451054E+09 0.00 0.00
October 0.690650E+09 0.477175E+09 0.666417E+09 0.342553E+09 0.323863E+09 0.00 0.00
November 0.269492E+09 0.604160E+09 0.353457E+09 0.157390E+09 0.196067E+09 0.00 0.00
December 0.263728E+09 0.793193E+09 0.349625E+09 0.185355E+09 0.164270E+09 0.00 0.00
               
Annual Sum or Average 0.966273E+10 0.567611E+10 0.887974E+10 0.400743E+10 0.487231E+10 0.00 0.00
Minimum of Months 0.218697E+09 0.208347E+09 0.346724E+09 0.157390E+09 0.164270E+09 0.00 0.00
Maximum of Months 0.148485E+10 0.800099E+09 0.116035E+10 0.557965E+09 0.646029E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 57484275.48 0.840113E+09 0.190407E+09 43103720.32 0.147303E+09 0.00 0.00
February 0.171144E+09 0.654133E+09 0.297420E+09 87642964.17 0.209777E+09 0.00 0.00
March 0.354251E+09 0.575987E+09 0.466427E+09 0.122417E+09 0.344011E+09 0.00 0.00
April 0.641302E+09 0.436961E+09 0.675843E+09 0.204193E+09 0.471650E+09 0.00 0.00
May 0.942672E+09 0.362352E+09 0.899439E+09 0.294493E+09 0.604946E+09 0.00 0.00
June 0.927286E+09 0.257708E+09 0.852363E+09 0.268241E+09 0.584122E+09 0.00 0.00
July 0.124420E+10 0.238482E+09 0.103192E+10 0.457523E+09 0.574398E+09 0.00 0.00
August 0.106030E+10 0.218613E+09 0.850783E+09 0.359854E+09 0.490929E+09 0.00 0.00
September 0.741678E+09 0.332564E+09 0.666243E+09 0.264960E+09 0.401283E+09 0.00 0.00
October 0.350540E+09 0.481543E+09 0.407182E+09 0.133761E+09 0.273421E+09 0.00 0.00
November 96389717.12 0.621176E+09 0.205806E+09 44331374.38 0.161474E+09 0.00 0.00
December 71190792.17 0.824578E+09 0.174689E+09 47217705.85 0.127471E+09 0.00 0.00
               
Annual Sum or Average 0.665844E+10 0.584421E+10 0.671852E+10 0.232774E+10 0.439079E+10 0.00 0.00
Minimum of Months 57484275.48 0.218613E+09 0.174689E+09 43103720.32 0.127471E+09 0.00 0.00
Maximum of Months 0.124420E+10 0.840113E+09 0.103192E+10 0.457523E+09 0.604946E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.254400E+09 0.416722E+09 0.296000E+09 0.176084E+09 0.119916E+09 0.00 0.00
February 0.407661E+09 0.330418E+09 0.411421E+09 0.255264E+09 0.156157E+09 0.00 0.00
March 0.508610E+09 0.303974E+09 0.483195E+09 0.255466E+09 0.227729E+09 0.00 0.00
April 0.554993E+09 0.235024E+09 0.494106E+09 0.212057E+09 0.282050E+09 0.00 0.00
May 0.549720E+09 0.189092E+09 0.475705E+09 0.145028E+09 0.330677E+09 0.00 0.00
June 0.498545E+09 0.131527E+09 0.416521E+09 0.111477E+09 0.305044E+09 0.00 0.00
July 0.619527E+09 0.113496E+09 0.467614E+09 0.169790E+09 0.297825E+09 0.00 0.00
August 0.679845E+09 0.105908E+09 0.498517E+09 0.229065E+09 0.269452E+09 0.00 0.00
September 0.677455E+09 0.164260E+09 0.535078E+09 0.292651E+09 0.242427E+09 0.00 0.00
October 0.567688E+09 0.251990E+09 0.500159E+09 0.306214E+09 0.193945E+09 0.00 0.00
November 0.274059E+09 0.317840E+09 0.289674E+09 0.165811E+09 0.123863E+09 0.00 0.00
December 0.300873E+09 0.414172E+09 0.313277E+09 0.202591E+09 0.110686E+09 0.00 0.00
               
Annual Sum or Average 0.589338E+10 0.297442E+10 0.518127E+10 0.252150E+10 0.265977E+10 0.00 0.00
Minimum of Months 0.254400E+09 0.105908E+09 0.289674E+09 0.111477E+09 0.110686E+09 0.00 0.00
Maximum of Months 0.679845E+09 0.416722E+09 0.535078E+09 0.306214E+09 0.330677E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 1369555.18 0.268481E+10 0.318561E+09 0.00 0.318561E+09 0.00 0.00
February 45237698.48 0.210024E+10 0.447720E+09 0.00 0.447720E+09 0.00 0.00
March 0.223900E+09 0.181915E+10 0.730390E+09 2381.43 0.730388E+09 0.00 0.00
April 0.569268E+09 0.133676E+10 0.100370E+10 6175195.84 0.997525E+09 0.00 0.00
May 0.101299E+10 0.105264E+10 0.133063E+10 39953211.88 0.129068E+10 0.00 0.00
June 0.117320E+10 0.745944E+09 0.135520E+10 90661606.03 0.126454E+10 0.00 0.00
July 0.134554E+10 0.665837E+09 0.133289E+10 0.107301E+09 0.122559E+10 0.00 0.00
August 0.111680E+10 0.650114E+09 0.108044E+10 32448343.77 0.104799E+10 0.00 0.00
September 0.597949E+09 0.992684E+09 0.809276E+09 606230.16 0.808670E+09 0.00 0.00
October 0.200195E+09 0.155908E+10 0.572569E+09 0.00 0.572569E+09 0.00 0.00
November 24289375.55 0.203553E+10 0.349028E+09 0.00 0.349028E+09 0.00 0.00
December 359972.49 0.262315E+10 0.270695E+09 0.00 0.270695E+09 0.00 0.00
               
Annual Sum or Average 0.631110E+10 0.182659E+11 0.960109E+10 0.277148E+09 0.932395E+10 0.00 0.00
Minimum of Months 359972.49 0.650114E+09 0.270695E+09 0.00 0.270695E+09 0.00 0.00
Maximum of Months 0.134554E+10 0.268481E+10 0.135520E+10 0.107301E+09 0.129068E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DINING_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 687444.12 0.277140E+10 0.318561E+09 0.00 0.318561E+09 0.00 0.00
February 39623527.95 0.216995E+10 0.447720E+09 0.00 0.447720E+09 0.00 0.00
March 0.203067E+09 0.187318E+10 0.730390E+09 2381.43 0.730388E+09 0.00 0.00
April 0.541639E+09 0.137277E+10 0.100370E+10 6175195.84 0.997525E+09 0.00 0.00
May 0.983699E+09 0.107824E+10 0.133063E+10 39953211.88 0.129068E+10 0.00 0.00
June 0.114418E+10 0.765134E+09 0.135520E+10 90661606.03 0.126454E+10 0.00 0.00
July 0.131997E+10 0.683892E+09 0.133289E+10 0.107301E+09 0.122559E+10 0.00 0.00
August 0.109201E+10 0.669926E+09 0.108044E+10 32448343.77 0.104799E+10 0.00 0.00
September 0.576484E+09 0.102126E+10 0.809276E+09 606230.16 0.808670E+09 0.00 0.00
October 0.181873E+09 0.160999E+10 0.572569E+09 0.00 0.572569E+09 0.00 0.00
November 20281496.21 0.210877E+10 0.349028E+09 0.00 0.349028E+09 0.00 0.00
December 193458.55 0.270839E+10 0.270695E+09 0.00 0.270695E+09 0.00 0.00
               
Annual Sum or Average 0.610372E+10 0.188329E+11 0.960109E+10 0.277148E+09 0.932395E+10 0.00 0.00
Minimum of Months 193458.55 0.669926E+09 0.270695E+09 0.00 0.270695E+09 0.00 0.00
Maximum of Months 0.131997E+10 0.277140E+10 0.135520E+10 0.107301E+09 0.129068E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.245539E+09 0.171282E+10 0.519285E+09 0.188214E+09 0.331072E+09 0.00 0.00
February 0.603611E+09 0.133938E+10 0.796974E+09 0.334323E+09 0.462651E+09 0.00 0.00
March 0.112696E+10 0.120891E+10 0.118461E+10 0.446443E+09 0.738167E+09 0.00 0.00
April 0.181243E+10 0.933283E+09 0.160249E+10 0.611146E+09 0.991341E+09 0.00 0.00
May 0.213465E+10 0.785399E+09 0.174915E+10 0.534492E+09 0.121466E+10 0.00 0.00
June 0.249176E+10 0.582554E+09 0.190771E+10 0.711401E+09 0.119631E+10 0.00 0.00
July 0.265799E+10 0.508952E+09 0.188744E+10 0.750725E+09 0.113672E+10 0.00 0.00
August 0.268733E+10 0.488312E+09 0.184714E+10 0.837559E+09 0.100959E+10 0.00 0.00
September 0.191664E+10 0.663130E+09 0.145002E+10 0.647584E+09 0.802436E+09 0.00 0.00
October 0.116744E+10 0.102763E+10 0.107795E+10 0.488713E+09 0.589235E+09 0.00 0.00
November 0.398955E+09 0.129577E+10 0.557632E+09 0.200916E+09 0.356716E+09 0.00 0.00
December 0.321668E+09 0.168735E+10 0.514539E+09 0.222431E+09 0.292108E+09 0.00 0.00
               
Annual Sum or Average 0.175650E+11 0.122335E+11 0.150949E+11 0.597395E+10 0.912099E+10 0.00 0.00
Minimum of Months 0.245539E+09 0.488312E+09 0.514539E+09 0.188214E+09 0.292108E+09 0.00 0.00
Maximum of Months 0.268733E+10 0.171282E+10 0.190771E+10 0.837559E+09 0.121466E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.586857E+09 0.186586E+10 0.862687E+09 0.448231E+09 0.414456E+09 0.00 0.00
February 0.102441E+10 0.145382E+10 0.120077E+10 0.649789E+09 0.550985E+09 0.00 0.00
March 0.139770E+10 0.133056E+10 0.148038E+10 0.650302E+09 0.830075E+09 0.00 0.00
April 0.164931E+10 0.103047E+10 0.160184E+10 0.541919E+09 0.105993E+10 0.00 0.00
May 0.176850E+10 0.849532E+09 0.166707E+10 0.382872E+09 0.128420E+10 0.00 0.00
June 0.167001E+10 0.612729E+09 0.152484E+10 0.314849E+09 0.120999E+10 0.00 0.00
July 0.201724E+10 0.555947E+09 0.164725E+10 0.468992E+09 0.117826E+10 0.00 0.00
August 0.210142E+10 0.542462E+09 0.163938E+10 0.594219E+09 0.104516E+10 0.00 0.00
September 0.194281E+10 0.778331E+09 0.163949E+10 0.745167E+09 0.894325E+09 0.00 0.00
October 0.153355E+10 0.111758E+10 0.146946E+10 0.779484E+09 0.689974E+09 0.00 0.00
November 0.682215E+09 0.141629E+10 0.857028E+09 0.422081E+09 0.434946E+09 0.00 0.00
December 0.714980E+09 0.184200E+10 0.890259E+09 0.515707E+09 0.374552E+09 0.00 0.00
               
Annual Sum or Average 0.170890E+11 0.133956E+11 0.164805E+11 0.651361E+10 0.996685E+10 0.00 0.00
Minimum of Months 0.586857E+09 0.542462E+09 0.857028E+09 0.314849E+09 0.374552E+09 0.00 0.00
Maximum of Months 0.210142E+10 0.186586E+10 0.166707E+10 0.779484E+09 0.128420E+10 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January 4.50 3.10 1.22 3.91 -4.2 29.50 44.23 0.00
February 5.82 4.07 1.77 3.94 -3.8 43.80 82.64 0.00
March 8.33 5.86 2.94 3.85 -1.4 65.55 100.60 0.02
April 10.85 8.04 5.25 4.23 1.22 89.73 150.02 0.00
May 12.97 10.02 7.49 3.85 3.75 114.98 168.60 0.00
June 15.59 11.80 8.88 4.02 5.93 107.53 199.74 0.01
July 17.66 13.41 10.38 3.76 8.02 92.25 247.81 0.00
August 18.80 14.57 11.86 3.84 8.90 79.20 215.47 0.01
September 15.09 12.55 10.74 2.23 5.47 68.06 162.11 0.01
October 11.43 9.19 7.19 4.02 2.10 48.18 106.36 0.04
November 8.07 6.72 5.29 3.86 0.13 33.26 46.10 0.00
December 5.42 4.09 2.46 3.51 -3.8 24.03 50.49 0.04
                 
Annual Sum or Average 11.24 8.64 6.31 3.75 1.89 66.43 131.49 0.01
Minimum of Months 4.50 3.10 1.22 2.23 -4.2 24.03 44.23 0.00
Maximum of Months 18.80 14.57 11.86 4.23 8.90 114.98 247.81 0.04



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 14.40 11-JAN-14:20 10.49 7.20 8.40 3.89 99.17 130.33
February 20.00 27-FEB-14:00 12.17 5.60 2.60 5.54 87.00 691.00
March 20.60 18-MAR-15:00 10.43 0.00 6.20 6.55 111.50 465.50
April 27.20 27-APR-15:09 17.22 11.02 4.10 12.63 151.33 598.33
May 25.00 05-MAY-15:00 17.36 12.80 2.60 18.99 208.50 29.50
June 26.70 28-JUN-16:00 16.74 10.60 3.10 11.84 131.50 527.00
July 30.60 24-JUL-14:00 18.78 12.20 3.10 20.75 267.00 383.50
August 31.80 10-AUG-16:00 18.70 11.10 2.60 16.85 50.50 750.50
September 25.00 14-SEP-16:00 16.69 11.70 3.10 13.54 100.50 235.00
October 21.70 04-OCT-14:00 11.49 1.70 5.20 4.92 56.50 783.50
November 21.10 04-NOV-13:00 15.94 12.80 0.00 6.95 52.50 729.00
December 13.30 14-DEC-11:00 8.44 3.60 13.90 5.33 127.50 85.00
                 
Annual Sum or Average                
Minimum of Months 13.30   8.44 0.00 0.00 3.89 50.50 29.50
Maximum of Months 31.80   18.78 12.80 13.90 20.75 267.00 783.50



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -3.9 07-JAN-07:00 -3.9 -3.9 2.10 -14.4 0.00 0.00
February -5.6 19-FEB-05:10 -6.1 -7.3 3.77 -22.8 0.00 0.00
March -0.6 01-MAR-06:00 -2.0 -3.9 1.50 -17.3 16.50 102.00
April 1.70 19-APR-04:00 1.21 0.60 3.10 -11.9 0.00 0.00
May 4.40 11-MAY-02:00 3.92 3.30 3.10 -10.9 0.00 0.00
June 8.30 15-JUN-02:00 7.50 6.70 3.10 -3.2 0.00 0.00
July 11.10 03-JUL-03:00 8.19 5.00 2.60 5.54 0.00 0.00
August 11.00 06-AUG-04:00 10.57 10.20 2.60 -3.2 11.00 135.50
September 7.20 27-SEP-04:49 6.72 6.20 0.25 -4.0 0.00 0.00
October 5.60 13-OCT-04:00 4.51 3.30 2.10 -8.5 0.00 0.00
November 0.00 11-NOV-06:00 -0.2 -0.6 2.10 -16.0 0.00 0.00
December -1.7 26-DEC-06:00 -1.7 -1.7 2.10 -15.7 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months -5.6   -6.1 -7.3 0.25 -22.8 0.00 0.00
Maximum of Months 11.10   10.57 10.20 3.77 5.54 16.50 135.50



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 10.49 11-JAN-13:00 14.40 7.20 8.20 2.85 105.50 249.00
February 12.42 27-FEB-15:00 19.40 6.70 2.60 6.35 88.00 342.50
March 12.45 09-MAR-11:00 17.20 8.90 2.10 12.41 178.00 40.00
April 17.29 27-APR-14:00 27.20 11.10 4.10 12.41 147.50 646.00
May 17.58 06-MAY-12:00 23.90 13.90 5.20 15.57 365.50 282.50
June 16.74 28-JUN-16:00 26.70 10.60 3.10 11.84 131.50 527.00
July 19.18 31-JUL-15:00 28.90 13.90 4.10 14.65 45.00 848.50
August 20.13 29-AUG-12:00 28.90 15.70 2.60 17.39 136.50 655.00
September 17.97 23-SEP-13:00 23.30 15.00 2.10 9.72 148.00 670.50
October 15.15 01-OCT-11:00 17.20 13.90 4.60 13.73 236.50 63.50
November 16.05 04-NOV-12:00 20.60 13.30 0.00 7.95 62.00 746.50
December 10.71 16-DEC-11:00 11.70 10.00 6.70 7.35 89.50 0.00
                 
Annual Sum or Average                
Minimum of Months 10.49   11.70 6.70 0.00 2.85 45.00 0.00
Maximum of Months 20.13   28.90 15.70 8.20 17.39 365.50 848.50



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 10.00 11-JAN-21:00 11.10 10.49 4.60 6.75 0.00 0.00
February 11.70 24-FEB-00:00 12.80 12.15 4.10 8.74 0.00 0.00
March 11.70 09-MAR-16:00 12.80 12.15 2.10 8.74 37.50 0.00
April 12.80 28-APR-12:00 16.70 14.35 4.10 8.35 265.50 596.00
May 13.90 05-MAY-16:00 22.80 17.10 2.60 19.17 111.50 27.50
June 13.90 12-JUN-12:00 16.70 15.00 3.60 13.16 263.50 0.00
July 15.00 11-JUL-09:20 16.13 15.49 4.60 12.91 204.17 28.17
August 16.40 30-AUG-07:00 17.40 16.77 5.20 12.41 168.50 34.50
September 15.00 14-SEP-11:20 20.37 16.93 2.10 6.89 152.83 748.17
October 13.90 01-OCT-10:00 16.70 15.01 4.10 13.16 184.50 0.00
November 13.90 03-NOV-19:00 15.00 14.31 4.60 11.46 0.00 0.00
December 10.00 16-DEC-10:00 11.10 10.48 7.70 6.75 81.00 0.00
                 
Annual Sum or Average                
Minimum of Months 10.00   11.10 10.48 2.10 6.75 0.00 0.00
Maximum of Months 16.40   22.80 17.10 7.70 19.17 265.50 748.17



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 11.48 8.35 0.00
February 18.00 13.00 16.00 11.14 14.81 0.00
March 18.00 13.00 16.00 11.69 23.26 0.00
April 18.00 13.00 16.00 12.99 36.00 0.00
May 18.00 13.00 16.00 14.72 45.46 0.00
June 18.00 13.00 16.00 16.40 49.26 0.00
July 18.00 13.00 16.00 17.58 51.50 0.00
August 18.00 13.00 16.00 17.95 42.11 0.00
September 18.00 13.00 16.00 17.39 30.76 0.00
October 18.00 13.00 16.00 16.06 18.91 0.00
November 18.00 13.00 16.00 14.32 9.65 0.00
December 18.00 13.00 16.00 12.65 7.39 0.00
             
Annual Sum or Average 18.00 13.00 16.00 14.55 28.19 0.00
Minimum of Months 18.00 13.00 16.00 11.14 7.39 0.00
Maximum of Months 18.00 13.00 16.00 17.95 51.50 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWH LAUNDRY G WATER HEATER

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.121488E+12 -0.119712E+12 0.00 0.00 744.00 0.00 -0.177623E+10 82.17 0.00 0.00
February 0.110243E+12 -0.108633E+12 0.00 0.00 672.00 0.00 -0.160915E+10 82.17 0.00 0.00
March 0.121144E+12 -0.119356E+12 0.00 0.00 744.00 0.00 -0.178730E+10 82.17 0.00 0.00
April 0.115098E+12 -0.113365E+12 0.00 0.00 720.00 0.00 -0.173287E+10 82.17 0.00 0.00
May 0.116005E+12 -0.114217E+12 0.00 0.00 744.00 0.00 -0.178815E+10 82.17 0.00 0.00
June 0.109501E+12 -0.107775E+12 0.00 0.00 720.00 0.00 -0.172568E+10 82.17 0.00 0.00
July 0.111144E+12 -0.109368E+12 0.00 0.00 744.00 0.00 -0.177677E+10 82.17 0.00 0.00
August 0.110523E+12 -0.108751E+12 0.00 0.00 744.00 0.00 -0.177135E+10 82.17 0.00 0.00
September 0.107873E+12 -0.106164E+12 0.00 0.00 720.00 0.00 -0.170886E+10 82.17 0.00 0.00
October 0.113716E+12 -0.111954E+12 0.00 0.00 744.00 0.00 -0.176229E+10 82.17 0.00 0.00
November 0.112887E+12 -0.111182E+12 0.00 0.00 720.00 0.00 -0.170485E+10 82.17 0.00 0.00
December 0.119487E+12 -0.117720E+12 0.00 0.00 744.00 0.00 -0.176718E+10 82.17 0.00 0.00
                     
Annual Sum or Average 0.136911E+13 -0.134820E+13 0.00 0.00 8760.00 0.00 -0.209107E+11 82.17 0.00 0.00
Minimum of Months 0.107873E+12 -0.119712E+12 0.00 0.00 672.00 0.00 -0.178815E+10 82.17 0.00 0.00
Maximum of Months 0.121488E+12 -0.106164E+12 0.00 0.00 744.00 0.00 -0.160915E+10 82.17 0.00 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWH BOOSTER E WATER HEATER

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.804766E+10 -0.788296E+10 0.00 0.00 744.00 0.00 -164694608.6 82.17 0.00 0.00
February 0.727208E+10 -0.712336E+10 0.00 0.00 672.00 0.00 -148715182.0 82.17 0.00 0.00
March 0.804609E+10 -0.788155E+10 0.00 0.00 744.00 0.00 -164534156.8 82.17 0.00 0.00
April 0.779735E+10 -0.763820E+10 0.00 0.00 720.00 0.00 -159144973.2 82.17 0.00 0.00
May 0.804734E+10 -0.788296E+10 0.00 0.00 744.00 0.00 -164377361.4 82.17 0.00 0.00
June 0.778876E+10 -0.762976E+10 0.00 0.00 720.00 0.00 -158994786.4 82.17 0.00 0.00
July 0.805565E+10 -0.789140E+10 0.00 0.00 744.00 0.00 -164249807.4 82.17 0.00 0.00
August 0.804719E+10 -0.788296E+10 0.00 0.00 744.00 0.00 -164230507.4 82.17 0.00 0.00
September 0.779861E+10 -0.763961E+10 0.00 0.00 720.00 0.00 -159005414.6 82.17 0.00 0.00
October 0.804600E+10 -0.788155E+10 0.00 0.00 744.00 0.00 -164446023.7 82.17 0.00 0.00
November 0.778058E+10 -0.762132E+10 0.00 0.00 720.00 0.00 -159259857.2 82.17 0.00 0.00
December 0.805607E+10 -0.789140E+10 0.00 0.00 744.00 0.00 -164670320.7 82.17 0.00 0.00
                     
Annual Sum or Average 0.947834E+11 -0.928470E+11 0.00 0.00 8760.00 0.00 -0.193632E+10 82.17 0.00 0.00
Minimum of Months 0.727208E+10 -0.789140E+10 0.00 0.00 672.00 0.00 -164694608.6 82.17 0.00 0.00
Maximum of Months 0.805607E+10 -0.712336E+10 0.00 0.00 744.00 0.00 -148715182.0 82.17 0.00 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.724447E+11 -0.709067E+11 0.00 0.00 744.00 0.00 -0.153799E+10 60.05 0.00 0.00
February 0.658905E+11 -0.644947E+11 0.00 0.00 672.00 0.00 -0.139583E+10 60.05 0.00 0.00
March 0.722161E+11 -0.706628E+11 0.00 0.00 744.00 0.00 -0.155333E+10 60.05 0.00 0.00
April 0.680036E+11 -0.664959E+11 0.00 0.00 720.00 0.00 -0.150770E+10 60.05 0.00 0.00
May 0.677494E+11 -0.661949E+11 0.00 0.00 744.00 0.00 -0.155452E+10 60.05 0.00 0.00
June 0.632001E+11 -0.617024E+11 0.00 0.00 720.00 0.00 -0.149773E+10 60.05 0.00 0.00
July 0.635103E+11 -0.619716E+11 0.00 0.00 744.00 0.00 -0.153873E+10 60.05 0.00 0.00
August 0.630338E+11 -0.615025E+11 0.00 0.00 744.00 0.00 -0.153123E+10 60.05 0.00 0.00
September 0.617559E+11 -0.602815E+11 0.00 0.00 720.00 0.00 -0.147441E+10 60.05 0.00 0.00
October 0.657225E+11 -0.642038E+11 0.00 0.00 744.00 0.00 -0.151867E+10 60.05 0.00 0.00
November 0.660540E+11 -0.645851E+11 0.00 0.00 720.00 0.00 -0.146885E+10 60.05 0.00 0.00
December 0.707072E+11 -0.691817E+11 0.00 0.00 744.00 0.00 -0.152543E+10 60.05 0.00 0.00
                     
Annual Sum or Average 0.800288E+12 -0.782184E+12 0.00 0.00 8760.00 0.00 -0.181044E+11 60.05 0.00 0.00
Minimum of Months 0.617559E+11 -0.709067E+11 0.00 0.00 672.00 0.00 -0.155452E+10 60.05 0.00 0.00
Maximum of Months 0.724447E+11 -0.602815E+11 0.00 0.00 744.00 0.00 -0.139583E+10 60.05 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: LOBBY_FLR_1_DAYLCTRL

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 237.83 0.88 0.86 01-JAN-10:09 2313.90 32.52 223.50 221.83 1753.65 33.48 226.67 177.67
February 259.50 0.87 0.86 01-FEB-08:39 4072.80 33.17 241.00 245.50 1755.64 29.18 209.67 212.83
March 247.00 0.87 0.86 01-MAR-07:30 5992.21 30.52 183.83 315.50 753.73 22.30 170.50 254.00
April 379.50 0.87 0.86 01-APR-07:19 1564.44 19.76 106.17 349.67 605.54 21.50 244.67 288.17
May 427.83 0.88 0.86 01-MAY-07:30 1442.36 19.59 108.50 389.00 552.25 21.29 259.83 317.00
June 375.17 0.88 0.86 01-JUN-06:00 1222.26 19.58 57.67 399.50 490.02 21.32 256.17 318.00
July 471.00 0.89 0.86 01-JUL-09:00 1053.37 18.55 68.33 397.83 422.07 20.31 212.17 289.67
August 366.67 0.88 0.86 01-AUG-06:30 1218.12 19.63 53.33 377.83 495.75 21.37 240.50 301.50
September 301.17 0.87 0.86 01-SEP-07:00 3413.00 24.83 149.17 322.33 683.10 22.35 226.00 269.17
October 245.33 0.87 0.86 01-OCT-08:09 6361.65 34.77 221.33 287.33 913.20 24.24 188.67 244.33
November 242.67 0.87 0.86 01-NOV-08:30 2612.59 32.24 226.33 228.50 1732.70 32.54 224.67 185.67
December 160.33 0.87 0.86 01-DEC-09:39 3101.92 35.76 150.33 211.17 2530.32 36.82 150.33 154.17
                         
Annual Sum or Average 3714.00 0.88     2536.17 24.93 1789.50 3746.00 900.71 24.28 2609.83 3012.17
Minimum of Months 160.33 0.87 0.86   1053.37 18.55 53.33 211.17 422.07 20.31 150.33 154.17
Maximum of Months 471.00 0.89 0.86   6361.65 35.76 241.00 399.50 2530.32 36.82 259.83 318.00



Table of Contents

Report: DaylightingReportMonthly

For: CAFE_FLR_1_DAYLCTRL

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 237.83 0.27 0.22 01-JAN-09:39 2537.74 32.63 224.33 233.83 1975.68 33.57 227.50 206.33
February 259.50 0.26 0.22 01-FEB-08:30 4378.38 33.29 242.33 254.33 2058.85 29.30 217.33 232.50
March 247.00 0.26 0.22 01-MAR-07:19 6368.42 30.77 184.33 328.67 1127.58 22.39 175.33 290.50
April 379.50 0.27 0.22 01-APR-06:00 1850.55 20.23 114.17 362.00 890.56 21.80 256.17 327.50
May 427.83 0.27 0.22 01-MAY-07:10 1692.12 20.16 134.67 404.33 801.02 21.68 288.83 366.17
June 375.17 0.28 0.22 01-JUN-05:49 1453.91 20.13 114.00 418.17 720.93 21.70 291.83 371.00
July 471.00 0.31 0.22 01-JUL-05:30 1274.56 19.13 103.00 418.67 642.62 20.71 233.50 366.67
August 366.67 0.28 0.22 01-AUG-05:00 1497.50 19.98 84.83 394.00 774.37 21.56 246.00 352.17
September 301.17 0.26 0.22 01-SEP-07:40 3775.30 25.02 157.50 332.00 1044.42 22.44 225.00 304.17
October 245.33 0.27 0.22 01-OCT-07:49 6743.61 34.93 221.33 299.67 1295.45 24.23 186.00 269.83
November 242.67 0.26 0.22 01-NOV-07:00 2836.08 32.35 227.67 239.83 1955.13 32.63 224.83 213.67
December 160.33 0.26 0.22 01-DEC-09:39 3407.81 35.90 150.33 223.67 2834.37 36.92 150.33 192.33
                         
Annual Sum or Average 3714.00 0.27     2816.34 25.28 1958.50 3909.17 1179.77 24.50 2722.67 3492.83
Minimum of Months 160.33 0.26 0.22   1274.56 19.13 84.83 223.67 642.62 20.71 150.33 192.33
Maximum of Months 471.00 0.31 0.22   6743.61 35.90 242.33 418.67 2834.37 36.92 291.83 371.00



Table of Contents

Report: DaylightingReportMonthly

For: DINING_FLR_6_DAYLCTRL

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 237.83 0.71 0.60 03-JAN-10:30 350.19 13.75 0.00 199.67 149.72 16.99 0.00 36.17
February 259.50 0.68 0.60 01-FEB-11:09 434.41 15.01 0.00 231.83 192.00 18.30 0.00 111.67
March 247.00 0.65 0.60 01-MAR-09:09 563.11 16.39 0.00 315.00 259.94 19.64 2.33 206.67
April 379.50 0.63 0.60 01-APR-07:19 674.58 17.16 0.00 360.67 301.35 20.33 50.50 304.83
May 427.83 0.62 0.60 01-MAY-07:19 843.04 18.34 17.67 409.00 373.09 21.95 192.33 366.83
June 375.17 0.62 0.60 01-JUN-05:30 876.37 19.62 40.17 427.00 408.72 23.56 225.17 391.33
July 471.00 0.64 0.60 01-JUL-04:00 735.34 18.60 48.00 435.17 344.16 22.67 207.67 340.17
August 366.67 0.63 0.60 01-AUG-05:40 627.16 17.86 13.17 400.00 293.70 21.05 83.33 332.33
September 301.17 0.63 0.60 01-SEP-07:49 600.90 17.20 0.00 325.00 285.74 20.41 25.33 254.17
October 245.33 0.67 0.60 01-OCT-08:50 451.85 15.60 0.00 276.00 215.84 18.93 0.17 145.83
November 242.67 0.70 0.60 01-NOV-11:39 378.80 14.21 0.00 212.00 160.91 17.43 0.00 51.33
December 160.33 0.72 0.60 01-DEC-10:20 316.81 13.88 0.00 179.33 149.55 17.36 0.00 27.00
                         
Annual Sum or Average 3714.00 0.65     616.97 16.94 119.00 3770.67 282.39 20.41 786.83 2568.33
Minimum of Months 160.33 0.62 0.60   316.81 13.75 0.00 179.33 149.55 16.99 0.00 27.00
Maximum of Months 471.00 0.72 0.60   876.37 19.62 48.00 435.17 408.72 23.56 225.17 391.33



Table of Contents

Report: DaylightingReportMonthly

For: BANQUET_FLR_6_DAYLCTRL

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 237.83 0.71 0.60 03-JAN-10:30 350.19 13.75 0.00 199.67 149.72 16.99 0.00 36.17
February 259.50 0.68 0.60 01-FEB-11:09 434.41 15.01 0.00 231.83 192.00 18.30 0.00 111.67
March 247.00 0.65 0.60 01-MAR-09:09 563.11 16.39 0.00 315.00 259.94 19.64 2.33 206.67
April 379.50 0.63 0.60 01-APR-07:19 674.58 17.16 0.00 360.67 301.35 20.33 50.50 304.83
May 427.83 0.62 0.60 01-MAY-07:19 843.04 18.34 17.67 409.00 373.09 21.95 192.33 366.83
June 375.17 0.62 0.60 01-JUN-05:30 876.37 19.62 40.17 427.00 408.72 23.56 225.17 391.33
July 471.00 0.64 0.60 01-JUL-04:00 735.34 18.60 48.00 435.17 344.16 22.67 207.67 340.17
August 366.67 0.63 0.60 01-AUG-05:40 627.16 17.86 13.17 400.00 293.70 21.05 83.33 332.33
September 301.17 0.63 0.60 01-SEP-07:49 600.90 17.20 0.00 325.00 285.74 20.41 25.33 254.17
October 245.33 0.67 0.60 01-OCT-08:50 451.85 15.60 0.00 276.00 215.84 18.93 0.17 145.83
November 242.67 0.70 0.60 01-NOV-11:39 378.80 14.21 0.00 212.00 160.91 17.43 0.00 51.33
December 160.33 0.72 0.60 01-DEC-10:20 316.81 13.88 0.00 179.33 149.55 17.36 0.00 27.00
                         
Annual Sum or Average 3714.00 0.65     616.97 16.94 119.00 3770.67 282.39 20.41 786.83 2568.33
Minimum of Months 160.33 0.62 0.60   316.81 13.75 0.00 179.33 149.55 16.99 0.00 27.00
Maximum of Months 471.00 0.72 0.60   876.37 19.62 48.00 435.17 408.72 23.56 225.17 391.33



Table of Contents

Report: CoilReportMonthly

For: FLR_3_DOAS HEATING COIL

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.107885E+09 1467.73 07-JAN-08:00 0.00 0.00 0.00 0.00 0.00
February 94116059.72 2209.45 19-FEB-05:00 0.00 0.00 0.00 0.00 0.00
March 14570.92 21.20 01-MAR-07:00 0.00 0.00 0.00 0.00 0.00
April 5374.59 0.53 26-APR-15:50 0.00 0.00 0.00 0.00 0.00
May 7907.92 0.53 05-MAY-08:15 0.00 0.00 0.00 0.00 0.00
June 24976.93 0.53 21-JUN-22:20 0.00 0.00 0.00 0.00 0.00
July 25196.21 0.54 30-JUL-03:05 0.00 0.00 0.00 0.00 0.00
August 28778.06 0.53 26-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 21135.78 0.54 23-SEP-22:50 0.00 0.00 0.00 0.00 0.00
October 4594.50 0.53 05-OCT-12:50 0.00 0.00 0.00 0.00 0.00
November 134237.44 221.09 30-NOV-13:10 0.00 0.00 0.00 0.00 0.00
December 14198385.80 2203.07 26-DEC-13:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.216466E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 4594.50 0.53   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.107885E+09 2209.45   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV WITH REHEAT HEATING COIL

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.416026E+11 121549.82 20-JAN-11:50 0.00 0.00 0.00 0.00 0.00
February 0.568448E+11 133958.02 08-FEB-11:37 0.00 0.00 0.00 0.00 0.00
March 0.858799E+11 119564.07 03-MAR-11:40 0.00 0.00 0.00 0.00 0.00
April 0.911593E+11 118060.58 25-APR-06:40 0.00 0.00 0.00 0.00 0.00
May 0.840791E+11 112555.94 21-MAY-06:40 0.00 0.00 0.00 0.00 0.00
June 0.432190E+11 98195.93 15-JUN-03:00 0.00 0.00 0.00 0.00 0.00
July 0.161707E+11 58196.05 07-JUL-05:00 0.00 0.00 0.00 0.00 0.00
August 0.123476E+11 58254.14 21-AUG-05:00 0.00 0.00 0.00 0.00 0.00
September 0.448933E+11 101700.08 28-SEP-05:40 0.00 0.00 0.00 0.00 0.00
October 0.113700E+12 119477.12 12-OCT-06:05 0.00 0.00 0.00 0.00 0.00
November 0.757441E+11 137305.51 11-NOV-11:37 0.00 0.00 0.00 0.00 0.00
December 0.497012E+11 127591.54 21-DEC-11:40 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.715342E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.123476E+11 58196.05   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.113700E+12 137305.51   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: BASEMENT VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.315281E+10 1928.68 16-JAN-18:00 0.00 0.00 0.00 0.00 0.00
February 0.206333E+10 2083.77 19-FEB-06:00 0.00 0.00 0.00 0.00 0.00
March 0.158188E+10 1588.95 05-MAR-18:00 0.00 0.00 0.00 0.00 0.00
April 0.899391E+09 1294.56 18-APR-06:05 0.00 0.00 0.00 0.00 0.00
May 0.562584E+09 1071.65 18-MAY-08:07 0.00 0.00 0.00 0.00 0.00
June 0.265343E+09 903.65 14-JUN-10:37 0.00 0.00 0.00 0.00 0.00
July 83400762.73 693.60 12-JUL-10:37 0.00 0.00 0.00 0.00 0.00
August 0.111127E+09 616.01 22-AUG-07:03 0.00 0.00 0.00 0.00 0.00
September 0.381780E+09 1245.85 26-SEP-10:35 0.00 0.00 0.00 0.00 0.00
October 0.108124E+10 1374.75 27-OCT-10:50 0.00 0.00 0.00 0.00 0.00
November 0.226794E+10 1878.27 30-NOV-11:50 0.00 0.00 0.00 0.00 0.00
December 0.297329E+10 2182.06 26-DEC-11:50 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.154241E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 83400762.73 616.01   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.315281E+10 2182.06   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 39341566.01 374.38 17-JAN-11:50 0.00 0.00 0.00 0.00 0.00
February 11392824.72 290.94 17-FEB-11:50 0.00 0.00 0.00 0.00 0.00
March 90030.76 46.69 05-MAR-16:00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 5203445.79 174.09 26-NOV-16:00 0.00 0.00 0.00 0.00 0.00
December 39914865.79 402.81 26-DEC-11:50 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 95942733.07     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 39914865.79 402.81   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: MECH_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.491234E+09 650.14 16-JAN-15:50 0.00 0.00 0.00 0.00 0.00
February 0.253128E+09 552.05 20-FEB-11:50 0.00 0.00 0.00 0.00 0.00
March 10164493.56 257.67 05-MAR-18:00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 94564333.79 376.83 26-NOV-17:50 0.00 0.00 0.00 0.00 0.00
December 0.343038E+09 645.44 26-DEC-11:50 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.119213E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.491234E+09 650.14   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: STORAGE_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.616756E+09 511.30 16-JAN-16:00 0.00 0.00 0.00 0.00 0.00
February 0.359086E+09 478.44 19-FEB-06:00 0.00 0.00 0.00 0.00 0.00
March 60730578.57 308.55 05-MAR-18:00 0.00 0.00 0.00 0.00 0.00
April 3115063.43 157.07 19-APR-10:33 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 1662944.99 93.11 31-OCT-17:00 0.00 0.00 0.00 0.00 0.00
November 0.213314E+09 364.22 30-NOV-11:50 0.00 0.00 0.00 0.00 0.00
December 0.501229E+09 519.74 26-DEC-11:50 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.175589E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.616756E+09 519.74   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.104559E+09 1202.40 17-JAN-04:50 0.00 0.00 0.00 0.00 0.00
February 66522406.29 1202.38 18-FEB-06:00 0.00 0.00 0.00 0.00 0.00
March 31958224.03 800.03 06-MAR-04:50 0.00 0.00 0.00 0.00 0.00
April 12687994.15 640.52 01-APR-05:00 0.00 0.00 0.00 0.00 0.00
May 1770397.43 245.97 18-MAY-03:50 0.00 0.00 0.00 0.00 0.00
June 38391.82 63.99 14-JUN-04:00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 566747.78 186.45 27-SEP-03:50 0.00 0.00 0.00 0.00 0.00
October 12952952.97 586.18 28-OCT-05:00 0.00 0.00 0.00 0.00 0.00
November 46087017.98 954.64 13-NOV-05:00 0.00 0.00 0.00 0.00 0.00
December 99469170.08 1202.40 26-DEC-04:50 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.376613E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.104559E+09 1202.40   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CAFE_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.240613E+10 4843.10 26-JAN-11:50 0.00 0.00 0.00 0.00 0.00
February 0.114386E+10 4839.17 17-FEB-11:40 0.00 0.00 0.00 0.00 0.00
March 0.741264E+09 3725.91 22-MAR-10:50 0.00 0.00 0.00 0.00 0.00
April 0.187395E+09 2797.42 10-APR-10:37 0.00 0.00 0.00 0.00 0.00
May 96782293.64 2544.97 17-MAY-10:50 0.00 0.00 0.00 0.00 0.00
June 20549157.80 2239.81 14-JUN-10:33 0.00 0.00 0.00 0.00 0.00
July 8935077.15 1867.88 12-JUL-10:50 0.00 0.00 0.00 0.00 0.00
August 3362755.39 1322.07 01-AUG-10:40 0.00 0.00 0.00 0.00 0.00
September 0.129895E+09 3267.01 26-SEP-10:50 0.00 0.00 0.00 0.00 0.00
October 0.430158E+09 3563.98 27-OCT-10:50 0.00 0.00 0.00 0.00 0.00
November 0.148737E+10 4960.52 30-NOV-11:50 0.00 0.00 0.00 0.00 0.00
December 0.225888E+10 5823.91 26-DEC-11:50 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.891458E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 3362755.39 1322.07   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.240613E+10 5823.91   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: LOBBY_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.445884E+09 6102.42 16-JAN-16:00 0.00 0.00 0.00 0.00 0.00
February 95286855.88 4748.54 17-FEB-11:50 0.00 0.00 0.00 0.00 0.00
March 2077552.31 1061.23 05-MAR-16:00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 84357083.75 3589.84 30-NOV-11:50 0.00 0.00 0.00 0.00 0.00
December 0.498001E+09 7293.09 26-DEC-11:50 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.112561E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.498001E+09 7293.09   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.706121E+10 6294.52 16-JAN-16:00 0.00 0.00 0.00 0.00 0.00
February 0.374174E+10 5984.06 17-FEB-11:50 0.00 0.00 0.00 0.00 0.00
March 0.114026E+10 4296.93 05-MAR-16:00 0.00 0.00 0.00 0.00 0.00
April 82676080.48 2450.28 11-APR-10:35 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.534489E+09 3782.73 31-OCT-10:50 0.00 0.00 0.00 0.00 0.00
November 0.380769E+10 5859.66 30-NOV-11:50 0.00 0.00 0.00 0.00 0.00
December 0.632350E+10 6862.05 26-DEC-11:50 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.226916E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.706121E+10 6862.05   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.358555E+10 2807.22 16-JAN-06:00 0.00 0.00 0.00 0.00 0.00
February 0.205237E+10 3159.85 19-FEB-05:50 0.00 0.00 0.00 0.00 0.00
March 0.681739E+09 1607.75 25-MAR-06:10 0.00 0.00 0.00 0.00 0.00
April 0.132265E+09 1299.11 18-APR-06:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 229608.56 245.86 28-SEP-06:15 0.00 0.00 0.00 0.00 0.00
October 0.242731E+09 1249.44 31-OCT-10:50 0.00 0.00 0.00 0.00 0.00
November 0.177788E+10 2416.27 30-NOV-11:50 0.00 0.00 0.00 0.00 0.00
December 0.325980E+10 3195.10 26-DEC-11:50 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.117326E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.358555E+10 3195.10   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: BANQUET_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: DINING_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: KITCHEN_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_3 FAN COIL HEATING COIL

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.354306E+10 4974.52 01-JAN-16:02 0.00 0.00 0.00 0.00 0.00
February 0.214739E+10 4971.45 16-FEB-16:02 0.00 0.00 0.00 0.00 0.00
March 0.116247E+10 4903.72 05-MAR-16:02 0.00 0.00 0.00 0.00 0.00
April 0.453309E+09 4813.54 18-APR-08:62 0.00 0.00 0.00 0.00 0.00
May 0.117062E+09 4333.59 28-MAY-08:03 0.00 0.00 0.00 0.00 0.00
June 25739043.85 4470.30 13-JUN-18:04 0.00 0.00 0.00 0.00 0.00
July 8899479.02 3970.44 31-JUL-08:04 0.00 0.00 0.00 0.00 0.00
August 12814736.56 4149.02 08-AUG-08:04 0.00 0.00 0.00 0.00 0.00
September 58511823.03 4366.60 27-SEP-15:03 0.00 0.00 0.00 0.00 0.00
October 0.607686E+09 4814.56 27-OCT-15:02 0.00 0.00 0.00 0.00 0.00
November 0.205874E+10 4974.29 29-NOV-16:02 0.00 0.00 0.00 0.00 0.00
December 0.327082E+10 4975.09 16-DEC-16:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.134665E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 8899479.02 3970.44   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.354306E+10 4975.09   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_3 FAN COIL HEATING COIL

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.409125E+10 4905.86 01-JAN-16:02 0.00 0.00 0.00 0.00 0.00
February 0.273652E+10 4905.15 16-FEB-16:02 0.00 0.00 0.00 0.00 0.00
March 0.155086E+10 4857.35 05-MAR-16:02 0.00 0.00 0.00 0.00 0.00
April 0.594429E+09 4752.05 18-APR-08:62 0.00 0.00 0.00 0.00 0.00
May 0.129242E+09 4265.55 11-MAY-18:04 0.00 0.00 0.00 0.00 0.00
June 29059818.44 4548.24 06-JUN-18:04 0.00 0.00 0.00 0.00 0.00
July 8627019.47 4137.06 25-JUL-08:04 0.00 0.00 0.00 0.00 0.00
August 11531299.13 4535.28 23-AUG-08:53 0.00 0.00 0.00 0.00 0.00
September 67127199.61 4457.04 21-SEP-15:04 0.00 0.00 0.00 0.00 0.00
October 0.864522E+09 4767.13 31-OCT-15:02 0.00 0.00 0.00 0.00 0.00
November 0.248247E+10 4905.65 26-NOV-16:02 0.00 0.00 0.00 0.00 0.00
December 0.384123E+10 4906.47 16-DEC-16:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.164069E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 8627019.47 4137.06   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.409125E+10 4906.47   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.912973E+10 27233.78 07-JAN-16:01 0.00 0.00 0.00 0.00 0.00
February 0.589629E+10 27120.88 19-FEB-16:01 0.00 0.00 0.00 0.00 0.00
March 0.142802E+10 26439.57 24-MAR-15:03 0.00 0.00 0.00 0.00 0.00
April 0.288920E+09 26442.70 06-APR-08:04 0.00 0.00 0.00 0.00 0.00
May 72645115.45 26452.03 24-MAY-15:06 0.00 0.00 0.00 0.00 0.00
June 28560525.17 26438.64 04-JUN-15:06 0.00 0.00 0.00 0.00 0.00
July 28433221.01 26395.39 16-JUL-15:06 0.00 0.00 0.00 0.00 0.00
August 41985644.09 25904.61 02-AUG-15:06 0.00 0.00 0.00 0.00 0.00
September 85405480.62 26444.06 24-SEP-15:06 0.00 0.00 0.00 0.00 0.00
October 0.437799E+09 25760.62 12-OCT-15:04 0.00 0.00 0.00 0.00 0.00
November 0.337516E+10 26979.66 30-NOV-16:02 0.00 0.00 0.00 0.00 0.00
December 0.780201E+10 27317.85 26-DEC-16:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.286149E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 28433221.01 25760.62   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.912973E+10 27317.85   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_5_FLR_3 FAN COIL HEATING COIL

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.358143E+10 4906.47 01-JAN-16:02 0.00 0.00 0.00 0.00 0.00
February 0.217007E+10 4905.76 16-FEB-16:02 0.00 0.00 0.00 0.00 0.00
March 0.113883E+10 4828.45 05-MAR-16:02 0.00 0.00 0.00 0.00 0.00
April 0.431036E+09 4738.87 18-APR-08:62 0.00 0.00 0.00 0.00 0.00
May 0.148381E+09 4248.35 29-MAY-08:03 0.00 0.00 0.00 0.00 0.00
June 27431613.53 4441.28 14-JUN-15:04 0.00 0.00 0.00 0.00 0.00
July 10015896.80 4580.56 16-JUL-15:04 0.00 0.00 0.00 0.00 0.00
August 10465886.00 4422.63 17-AUG-18:04 0.00 0.00 0.00 0.00 0.00
September 69889737.55 4635.47 21-SEP-15:04 0.00 0.00 0.00 0.00 0.00
October 0.631880E+09 4754.06 31-OCT-15:02 0.00 0.00 0.00 0.00 0.00
November 0.207858E+10 4906.21 29-NOV-16:02 0.00 0.00 0.00 0.00 0.00
December 0.331342E+10 4907.07 16-DEC-16:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.136114E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 10015896.80 4248.35   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.358143E+10 4907.07   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_6_FLR_3 FAN COIL HEATING COIL

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.414015E+10 4839.17 01-JAN-16:02 0.00 0.00 0.00 0.00 0.00
February 0.274455E+10 4838.41 16-FEB-16:02 0.00 0.00 0.00 0.00 0.00
March 0.148778E+10 4783.05 05-MAR-16:02 0.00 0.00 0.00 0.00 0.00
April 0.555022E+09 4678.80 18-APR-08:62 0.00 0.00 0.00 0.00 0.00
May 0.168757E+09 4574.39 29-MAY-19:43 0.00 0.00 0.00 0.00 0.00
June 29787337.83 4502.38 07-JUN-15:04 0.00 0.00 0.00 0.00 0.00
July 8558190.61 4297.37 01-JUL-08:04 0.00 0.00 0.00 0.00 0.00
August 7121109.56 4281.13 03-AUG-15:04 0.00 0.00 0.00 0.00 0.00
September 87005936.91 4572.89 06-SEP-15:04 0.00 0.00 0.00 0.00 0.00
October 0.883392E+09 4709.53 31-OCT-15:02 0.00 0.00 0.00 0.00 0.00
November 0.248155E+10 4838.94 26-NOV-16:02 0.00 0.00 0.00 0.00 0.00
December 0.386294E+10 4839.81 16-DEC-16:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.164566E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 7121109.56 4281.13   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.414015E+10 4839.81   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_6 FAN COIL HEATING COIL

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.129035E+10 1489.69 01-JAN-16:02 0.00 0.00 0.00 0.00 0.00
February 0.818187E+09 1489.64 15-FEB-16:02 0.00 0.00 0.00 0.00 0.00
March 0.488679E+09 1489.51 05-MAR-16:02 0.00 0.00 0.00 0.00 0.00
April 0.213699E+09 1461.08 18-APR-08:62 0.00 0.00 0.00 0.00 0.00
May 79528028.83 1443.03 18-MAY-08:62 0.00 0.00 0.00 0.00 0.00
June 19695306.03 1052.89 06-JUN-18:04 0.00 0.00 0.00 0.00 0.00
July 2564776.76 1142.32 04-JUL-08:03 0.00 0.00 0.00 0.00 0.00
August 4457550.77 1012.14 17-AUG-18:04 0.00 0.00 0.00 0.00 0.00
September 37910622.00 1122.06 27-SEP-15:03 0.00 0.00 0.00 0.00 0.00
October 0.288386E+09 1461.68 27-OCT-15:02 0.00 0.00 0.00 0.00 0.00
November 0.796144E+09 1489.61 26-NOV-16:02 0.00 0.00 0.00 0.00 0.00
December 0.120228E+10 1489.90 16-DEC-16:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.524188E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 2564776.76 1012.14   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.129035E+10 1489.90   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_6 FAN COIL HEATING COIL

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.146052E+10 1464.74 01-JAN-16:02 0.00 0.00 0.00 0.00 0.00
February 0.100395E+10 1464.69 15-FEB-16:02 0.00 0.00 0.00 0.00 0.00
March 0.619387E+09 1464.55 05-MAR-16:02 0.00 0.00 0.00 0.00 0.00
April 0.265903E+09 1437.96 18-APR-08:62 0.00 0.00 0.00 0.00 0.00
May 81232644.94 1417.13 18-MAY-08:62 0.00 0.00 0.00 0.00 0.00
June 18650450.34 1216.97 27-JUN-08:53 0.00 0.00 0.00 0.00 0.00
July 1888546.12 1005.76 19-JUL-08:04 0.00 0.00 0.00 0.00 0.00
August 3066654.88 1066.17 23-AUG-08:53 0.00 0.00 0.00 0.00 0.00
September 42687168.82 1405.21 28-SEP-08:61 0.00 0.00 0.00 0.00 0.00
October 0.387822E+09 1443.24 31-OCT-15:02 0.00 0.00 0.00 0.00 0.00
November 0.929411E+09 1464.73 17-NOV-16:02 0.00 0.00 0.00 0.00 0.00
December 0.138096E+10 1464.97 16-DEC-16:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.619548E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 1888546.12 1005.76   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.146052E+10 1464.97   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.358716E+10 7309.67 26-JAN-16:02 0.00 0.00 0.00 0.00 0.00
February 0.195500E+10 7232.13 16-FEB-16:02 0.00 0.00 0.00 0.00 0.00
March 0.899887E+09 7114.12 05-MAR-16:02 0.00 0.00 0.00 0.00 0.00
April 0.394923E+09 6534.10 18-APR-08:62 0.00 0.00 0.00 0.00 0.00
May 0.147748E+09 6194.94 24-MAY-18:04 0.00 0.00 0.00 0.00 0.00
June 37001244.38 5855.58 07-JUN-08:03 0.00 0.00 0.00 0.00 0.00
July 15327838.75 6152.42 12-JUL-08:03 0.00 0.00 0.00 0.00 0.00
August 18601738.41 5723.35 18-AUG-18:04 0.00 0.00 0.00 0.00 0.00
September 63873192.97 5913.03 28-SEP-08:03 0.00 0.00 0.00 0.00 0.00
October 0.397906E+09 6287.76 27-OCT-15:02 0.00 0.00 0.00 0.00 0.00
November 0.182137E+10 7309.43 30-NOV-16:02 0.00 0.00 0.00 0.00 0.00
December 0.337676E+10 7309.89 17-DEC-16:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.127156E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 15327838.75 5723.35   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.358716E+10 7309.89   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLR_3_DOAS COOLING COIL

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 0.00 0.00
February 0.00 0.00 0.108438E+09 0.108438E+09 9635.08 27-FEB-16:09 9635.08 0.00
March 0.00 0.00 0.232884E+09 0.232884E+09 12388.66 18-MAR-16:00 12388.66 0.01
April 0.00 0.00 0.179842E+10 0.179842E+10 18212.60 27-APR-15:02 18212.60 0.04
May 0.00 0.00 0.355559E+10 0.343568E+10 20677.56 05-MAY-18:03 16125.17 0.14
June 0.00 0.00 0.630895E+10 0.630895E+10 17791.40 28-JUN-15:02 17791.40 0.32
July 0.00 0.00 0.116585E+11 0.109079E+11 23708.15 15-JUL-18:03 15807.51 0.51
August 0.00 0.00 0.152262E+11 0.141063E+11 24768.28 30-AUG-12:40 15889.63 0.61
September 0.00 0.00 0.544189E+10 0.511333E+10 22992.79 14-SEP-12:50 15654.77 0.32
October 0.00 0.00 0.903800E+09 0.903800E+09 14148.91 04-OCT-15:01 14148.91 0.06
November 0.00 0.00 0.218215E+09 0.196313E+09 15659.16 04-NOV-15:01 13199.77 0.02
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.454529E+11 0.431120E+11       0.17
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.152262E+11 0.141063E+11 24768.28   18212.60 0.61



Table of Contents

Report: CoilReportMonthly

For: VAV WITH REHEAT COOLING COIL

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 0.00 0.00
February 0.00 0.00 0.177965E+10 0.177965E+10 78982.59 27-FEB-15:00 78982.59 0.01
March 0.00 0.00 0.394681E+10 0.394681E+10 104148.08 18-MAR-16:10 104148.08 0.02
April 0.00 0.00 0.284700E+11 0.284700E+11 204755.85 27-APR-18:10 204755.85 0.07
May 0.00 0.00 0.551595E+11 0.548024E+11 206707.51 05-MAY-18:00 171305.65 0.21
June 0.00 0.00 0.986138E+11 0.985076E+11 209018.02 28-JUN-18:10 209018.02 0.46
July 0.00 0.00 0.166404E+12 0.161479E+12 264497.45 27-JUL-18:03 202410.67 0.68
August 0.00 0.00 0.209638E+12 0.201849E+12 286685.50 10-AUG-18:10 248114.84 0.79
September 0.00 0.00 0.803282E+11 0.784403E+11 198570.87 14-SEP-17:15 179635.18 0.47
October 0.00 0.00 0.149889E+11 0.149718E+11 124339.99 04-OCT-15:15 124339.99 0.10
November 0.00 0.00 0.341840E+10 0.341840E+10 102902.96 04-NOV-14:30 102902.96 0.04
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.662748E+12 0.647665E+12       0.24
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.209638E+12 0.201849E+12 286685.50   248114.84 0.79



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_3 FAN COIL COOLING COIL

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 10367649.58 6049164.85 12746.79 05-JAN-16:01 12746.79 0.00
February 0.00 0.00 0.220335E+09 0.104331E+09 16838.06 12-FEB-16:01 16838.06 0.08
March 0.00 0.00 0.784666E+09 0.485889E+09 16838.93 28-MAR-15:01 16838.93 0.16
April 0.00 0.00 0.228306E+10 0.125430E+10 16833.78 13-APR-18:01 16833.78 0.47
May 0.00 0.00 0.426025E+10 0.233314E+10 16840.09 20-MAY-18:01 16840.09 0.71
June 0.00 0.00 0.502958E+10 0.254741E+10 16995.33 12-JUN-15:01 13917.39 0.85
July 0.00 0.00 0.783209E+10 0.437955E+10 16525.47 16-JUL-15:01 14305.75 0.91
August 0.00 0.00 0.764520E+10 0.419540E+10 17228.09 30-AUG-08:62 12555.05 0.90
September 0.00 0.00 0.511176E+10 0.261404E+10 16527.19 23-SEP-08:61 14296.41 0.79
October 0.00 0.00 0.149068E+10 0.699597E+09 16839.66 03-OCT-18:01 16839.66 0.37
November 0.00 0.00 0.173443E+09 66535432.22 17054.25 05-NOV-15:01 13878.91 0.07
December 0.00 0.00 24451951.66 13301003.62 14991.55 10-DEC-16:01 14329.93 0.01
                 
Annual Sum or Average 0.00 0.00 0.348659E+11 0.186996E+11       0.45
Minimum of Months 0.00 0.00 10367649.58 6049164.85 12746.79   12555.05 0.00
Maximum of Months 0.00 0.00 0.783209E+10 0.437955E+10 17228.09   16840.09 0.91



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_3 FAN COIL COOLING COIL

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 1356388.22 251363.27 1421.33 20-JAN-16:03 444.61 0.00
February 0.00 0.00 47358347.19 20279881.12 14008.45 12-FEB-16:01 14008.45 0.02
March 0.00 0.00 0.257554E+09 0.146797E+09 15102.86 25-MAR-15:01 15102.86 0.07
April 0.00 0.00 0.125531E+10 0.635699E+09 17674.76 25-APR-17:41 17674.76 0.32
May 0.00 0.00 0.255917E+10 0.118639E+10 15667.62 08-MAY-20:01 14250.55 0.56
June 0.00 0.00 0.334869E+10 0.157633E+10 16133.74 22-JUN-21:51 14277.23 0.63
July 0.00 0.00 0.526460E+10 0.283200E+10 17448.54 15-JUL-21:51 14126.48 0.67
August 0.00 0.00 0.515946E+10 0.278664E+10 16059.82 26-AUG-21:51 12212.93 0.66
September 0.00 0.00 0.256435E+10 0.102994E+10 16037.85 24-SEP-18:11 13032.72 0.56
October 0.00 0.00 0.501741E+09 0.183897E+09 15584.61 01-OCT-15:01 12506.07 0.21
November 0.00 0.00 37433914.07 12256786.94 15313.45 05-NOV-15:01 11847.75 0.02
December 0.00 0.00 2600525.61 912733.46 4251.77 10-DEC-16:01 1859.79 0.00
                 
Annual Sum or Average 0.00 0.00 0.209996E+11 0.104114E+11       0.31
Minimum of Months 0.00 0.00 1356388.22 251363.27 1421.33   444.61 0.00
Maximum of Months 0.00 0.00 0.526460E+10 0.283200E+10 17674.76   17674.76 0.67



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 0.00 0.00
February 0.00 0.00 0.398136E+10 0.345728E+10 37380.75 08-FEB-13:40 37380.75 0.04
March 0.00 0.00 0.119107E+11 0.843996E+10 47719.56 02-MAR-13:00 41340.91 0.19
April 0.00 0.00 0.193943E+11 0.909172E+10 43942.81 27-APR-13:00 31540.88 0.56
May 0.00 0.00 0.246056E+11 0.854564E+10 43083.26 04-MAY-13:00 29481.49 0.76
June 0.00 0.00 0.272618E+11 0.873149E+10 32629.85 28-JUN-13:00 17271.06 0.87
July 0.00 0.00 0.377326E+11 0.136682E+11 41194.86 31-JUL-12:50 26151.68 0.96
August 0.00 0.00 0.428340E+11 0.177077E+11 51050.96 24-AUG-13:00 40492.40 0.95
September 0.00 0.00 0.363342E+11 0.165338E+11 54044.42 14-SEP-13:15 46053.25 0.88
October 0.00 0.00 0.209240E+11 0.923041E+10 54983.46 04-OCT-12:40 50437.90 0.60
November 0.00 0.00 0.357538E+10 0.131882E+10 44767.79 04-NOV-13:25 30918.43 0.14
December 0.00 0.00 0.174235E+10 0.163441E+10 33996.75 05-DEC-12:30 33996.75 0.01
                 
Annual Sum or Average 0.00 0.00 0.230296E+12 0.983594E+11       0.50
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.428340E+11 0.177077E+11 54983.46   50437.90 0.96



Table of Contents

Report: CoilReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.127853E+10 0.414090E+09 63145.74 01-JAN-09:02 63145.74 0.13
February 0.00 0.00 0.336465E+10 0.126126E+10 76049.44 25-FEB-09:02 67722.04 0.23
March 0.00 0.00 0.797714E+10 0.395410E+10 76739.66 18-MAR-20:42 76739.66 0.39
April 0.00 0.00 0.164513E+11 0.886768E+10 78093.30 20-APR-18:01 78093.30 0.57
May 0.00 0.00 0.261891E+11 0.154526E+11 81551.40 06-MAY-21:51 68988.80 0.61
June 0.00 0.00 0.318460E+11 0.199549E+11 80341.17 12-JUN-18:01 68987.45 0.59
July 0.00 0.00 0.373715E+11 0.239237E+11 85347.82 26-JUL-21:51 69811.36 0.58
August 0.00 0.00 0.374883E+11 0.223534E+11 85952.31 26-AUG-21:51 67398.15 0.58
September 0.00 0.00 0.255177E+11 0.131501E+11 82815.27 15-SEP-21:51 68190.29 0.56
October 0.00 0.00 0.125895E+11 0.533314E+10 80385.17 01-OCT-15:01 65454.31 0.58
November 0.00 0.00 0.565920E+10 0.198128E+10 76211.58 04-NOV-15:01 64929.41 0.35
December 0.00 0.00 0.119099E+10 0.461661E+09 74807.91 03-DEC-09:02 74807.91 0.13
                 
Annual Sum or Average 0.00 0.00 0.206924E+12 0.117108E+12       0.44
Minimum of Months 0.00 0.00 0.119099E+10 0.414090E+09 63145.74   63145.74 0.13
Maximum of Months 0.00 0.00 0.374883E+11 0.239237E+11 85952.31   78093.30 0.61



Table of Contents

Report: CoilReportMonthly

For: ROOM_5_FLR_3 FAN COIL COOLING COIL

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 6761682.63 1184824.20 1572.81 20-JAN-16:02 523.43 0.01
February 0.00 0.00 0.198050E+09 85848414.78 14498.98 12-FEB-16:01 14498.98 0.07
March 0.00 0.00 0.751570E+09 0.441640E+09 15212.93 28-MAR-15:01 15212.93 0.18
April 0.00 0.00 0.236585E+10 0.121383E+10 15022.04 30-APR-15:01 12378.49 0.51
May 0.00 0.00 0.370808E+10 0.185995E+10 15211.59 14-MAY-18:01 15211.59 0.70
June 0.00 0.00 0.535543E+10 0.276254E+10 14704.87 12-JUN-15:01 13085.65 0.88
July 0.00 0.00 0.683111E+10 0.360811E+10 15530.27 16-JUL-15:01 12463.75 0.93
August 0.00 0.00 0.755454E+10 0.412684E+10 15640.78 30-AUG-08:62 11552.11 0.93
September 0.00 0.00 0.461389E+10 0.232205E+10 15480.96 24-SEP-15:01 12496.89 0.78
October 0.00 0.00 0.147376E+10 0.676987E+09 15958.36 01-OCT-15:01 12120.08 0.40
November 0.00 0.00 0.183456E+09 57312453.87 15264.12 05-NOV-15:01 12229.82 0.07
December 0.00 0.00 55759226.55 20551316.70 11053.03 02-DEC-09:02 10740.82 0.02
                 
Annual Sum or Average 0.00 0.00 0.330983E+11 0.171769E+11       0.46
Minimum of Months 0.00 0.00 6761682.63 1184824.20 1572.81   523.43 0.01
Maximum of Months 0.00 0.00 0.755454E+10 0.412684E+10 15958.36   15212.93 0.93



Table of Contents

Report: CoilReportMonthly

For: ROOM_6_FLR_3 FAN COIL COOLING COIL

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 1167286.50 218781.49 1156.48 27-JAN-19:06 267.81 0.00
February 0.00 0.00 26962366.04 9705940.86 11063.55 27-FEB-16:01 11063.55 0.02
March 0.00 0.00 0.206922E+09 0.117763E+09 13905.82 25-MAR-08:61 13905.82 0.07
April 0.00 0.00 0.135549E+10 0.663145E+09 13837.86 25-APR-18:01 13837.86 0.36
May 0.00 0.00 0.239386E+10 0.115738E+10 14551.90 06-MAY-08:51 14196.97 0.56
June 0.00 0.00 0.386189E+10 0.200963E+10 14030.75 12-JUN-18:01 11443.19 0.69
July 0.00 0.00 0.469090E+10 0.245401E+10 16658.91 31-JUL-08:32 15278.55 0.70
August 0.00 0.00 0.516350E+10 0.274949E+10 16865.73 10-AUG-08:32 15325.50 0.70
September 0.00 0.00 0.243866E+10 0.110653E+10 14461.35 24-SEP-15:01 11111.16 0.56
October 0.00 0.00 0.532710E+09 0.237209E+09 14522.44 01-OCT-15:01 10340.90 0.20
November 0.00 0.00 37320501.03 10998431.23 13568.60 05-NOV-15:01 10191.58 0.02
December 0.00 0.00 2546414.82 686184.57 3338.17 02-DEC-09:02 1868.21 0.00
                 
Annual Sum or Average 0.00 0.00 0.207119E+11 0.105168E+11       0.32
Minimum of Months 0.00 0.00 1167286.50 218781.49 1156.48   267.81 0.00
Maximum of Months 0.00 0.00 0.516350E+10 0.274949E+10 16865.73   15325.50 0.70



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_6 FAN COIL COOLING COIL

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 2192228.88 1408926.32 3274.88 05-JAN-16:01 3237.78 0.00
February 0.00 0.00 54066503.67 27452591.81 4390.20 12-FEB-16:01 4390.20 0.05
March 0.00 0.00 0.196455E+09 0.128358E+09 4390.60 28-MAR-15:01 4390.60 0.12
April 0.00 0.00 0.575201E+09 0.340481E+09 4486.10 30-APR-08:61 3365.09 0.38
May 0.00 0.00 0.107673E+10 0.637987E+09 4390.24 20-MAY-18:01 4390.24 0.62
June 0.00 0.00 0.126726E+10 0.683854E+09 4408.03 12-JUN-15:01 3645.54 0.79
July 0.00 0.00 0.199780E+10 0.117562E+10 4418.73 15-JUL-08:61 3613.21 0.90
August 0.00 0.00 0.190064E+10 0.109123E+10 4592.38 20-AUG-08:61 3225.65 0.88
September 0.00 0.00 0.123509E+10 0.677452E+09 4564.86 23-SEP-08:61 3391.54 0.72
October 0.00 0.00 0.336503E+09 0.174360E+09 4544.38 01-OCT-08:62 3179.33 0.28
November 0.00 0.00 41900589.23 18045904.95 4487.39 05-NOV-15:01 3585.16 0.05
December 0.00 0.00 5255959.83 2943633.72 4001.85 10-DEC-16:01 3688.94 0.01
                 
Annual Sum or Average 0.00 0.00 0.868909E+10 0.495920E+10       0.40
Minimum of Months 0.00 0.00 2192228.88 1408926.32 3274.88   3179.33 0.00
Maximum of Months 0.00 0.00 0.199780E+10 0.117562E+10 4592.38   4390.60 0.90



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_6 FAN COIL COOLING COIL

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 177959.83 32661.36 346.08 20-JAN-16:05 102.42 0.00
February 0.00 0.00 9398724.44 3815606.67 3618.99 26-FEB-16:01 3439.78 0.02
March 0.00 0.00 58883214.72 34430336.28 3893.02 25-MAR-15:01 3893.02 0.05
April 0.00 0.00 0.310058E+09 0.170709E+09 4574.65 25-APR-17:41 4574.65 0.25
May 0.00 0.00 0.649119E+09 0.326146E+09 4575.60 21-MAY-17:41 4575.60 0.49
June 0.00 0.00 0.860962E+09 0.428483E+09 4342.25 22-JUN-21:51 3806.88 0.60
July 0.00 0.00 0.139279E+10 0.772536E+09 4626.26 26-JUL-21:51 3677.71 0.69
August 0.00 0.00 0.130159E+10 0.735660E+09 4300.23 11-AUG-21:51 3570.57 0.66
September 0.00 0.00 0.595839E+09 0.253485E+09 4240.37 13-SEP-21:51 3487.10 0.50
October 0.00 0.00 93671335.49 37543185.37 4088.31 01-OCT-08:62 2843.18 0.13
November 0.00 0.00 7750853.19 2571218.02 4046.14 05-NOV-15:01 3000.41 0.01
December 0.00 0.00 187484.93 67757.81 323.64 29-DEC-19:06 64.48 0.00
                 
Annual Sum or Average 0.00 0.00 0.528043E+10 0.276548E+10       0.29
Minimum of Months 0.00 0.00 177959.83 32661.36 323.64   64.48 0.00
Maximum of Months 0.00 0.00 0.139279E+10 0.772536E+09 4626.26   4575.60 0.69



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.455824E+09 0.203203E+09 20036.61 05-JAN-16:01 20036.61 0.08
February 0.00 0.00 0.176052E+10 0.961059E+09 22633.93 28-FEB-16:01 21333.92 0.25
March 0.00 0.00 0.302958E+10 0.191849E+10 24114.24 25-MAR-15:01 24114.24 0.35
April 0.00 0.00 0.469085E+10 0.245489E+10 24464.34 30-APR-15:01 19903.15 0.60
May 0.00 0.00 0.599950E+10 0.298076E+10 24109.44 14-MAY-18:01 24109.44 0.73
June 0.00 0.00 0.681200E+10 0.311330E+10 24208.15 12-JUN-15:01 20109.43 0.86
July 0.00 0.00 0.956897E+10 0.472205E+10 24540.83 16-JUL-15:01 19882.51 0.91
August 0.00 0.00 0.107165E+11 0.568579E+10 23877.42 29-AUG-08:62 20086.02 0.90
September 0.00 0.00 0.874662E+10 0.487032E+10 23675.97 16-SEP-15:01 20551.07 0.82
October 0.00 0.00 0.467255E+10 0.253512E+10 24114.70 04-OCT-18:01 24114.70 0.58
November 0.00 0.00 0.123165E+10 0.559186E+09 23020.96 05-NOV-08:62 20204.29 0.21
December 0.00 0.00 0.971341E+09 0.512672E+09 21524.65 10-DEC-16:01 21524.65 0.12
                 
Annual Sum or Average 0.00 0.00 0.586559E+11 0.305168E+11       0.54
Minimum of Months 0.00 0.00 0.455824E+09 0.203203E+09 20036.61   19882.51 0.08
Maximum of Months 0.00 0.00 0.107165E+11 0.568579E+10 24540.83   24114.70 0.91



Table of Contents

Report: PlantLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 33476.87 163121.08 02-JAN-16:02
February 0.00 0.00 01-FEB-00:03 35345.41 158030.82 22-FEB-09:04
March 0.00 0.00 01-MAR-00:03 36652.82 144112.30 15-MAR-08:07
April 0.00 0.00 01-APR-00:10 36652.92 129681.18 18-APR-15:04
May 0.00 0.00 01-MAY-00:05 31771.97 120978.54 28-MAY-08:03
June 0.00 0.00 01-JUN-00:05 16752.82 100869.71 15-JUN-04:00
July 0.00 0.00 01-JUL-00:10 6061.27 58593.92 19-JUL-05:00
August 0.00 0.00 01-AUG-00:05 4662.11 65555.32 01-AUG-08:04
September 0.00 0.00 01-SEP-00:05 17591.35 106483.59 28-SEP-08:04
October 0.00 0.00 01-OCT-00:10 44685.06 153595.98 30-OCT-08:05
November 0.00 0.00 01-NOV-00:05 38884.56 168464.52 17-NOV-09:04
December 0.00 0.00 01-DEC-00:03 34829.55 167650.85 16-DEC-19:04
             
Annual Sum or Average 0.00     28061.51    
Minimum of Months 0.00 0.00   4662.11 58593.92  
Maximum of Months 0.00 0.00   44685.06 168464.52  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 1124.94 34372.80 11-JAN-19:03 0.00 0.00 01-JAN-00:10
February 5702.19 216998.28 27-FEB-16:03 0.00 0.00 01-FEB-00:03
March 12460.75 265608.87 18-MAR-15:01 0.00 0.00 01-MAR-00:03
April 32478.55 389617.12 27-APR-18:03 0.00 0.00 01-APR-00:10
May 50771.85 354540.72 04-MAY-15:03 0.00 0.00 01-MAY-00:05
June 75736.02 392319.47 28-JUN-18:03 0.00 0.00 01-JUN-00:05
July 110767.84 455087.94 27-JUL-18:03 0.00 0.00 01-JUL-00:10
August 130885.15 487055.67 10-AUG-18:03 0.00 0.00 01-AUG-00:05
September 68903.44 390036.38 14-SEP-15:03 0.00 0.00 01-SEP-00:05
October 23734.24 310852.05 04-OCT-15:03 0.00 0.00 01-OCT-00:10
November 6652.34 301776.38 04-NOV-15:03 0.00 0.00 01-NOV-00:05
December 2062.59 45825.67 02-DEC-09:02 0.00 0.00 01-DEC-00:03
             
Annual Sum or Average 43722.74     0.00    
Minimum of Months 1124.94 34372.80   0.00 0.00  
Maximum of Months 130885.15 487055.67   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 26364.65 55433.29 31-JAN-08:00
February 0.00 0.00 01-FEB-00:03 26550.39 55500.92 10-FEB-07:15
March 0.00 0.00 01-MAR-00:03 26273.73 55310.08 01-MAR-07:20
April 0.00 0.00 01-APR-00:10 25546.60 54075.96 03-APR-06:30
May 0.00 0.00 01-MAY-00:05 24608.09 52394.42 01-MAY-06:50
June 0.00 0.00 01-JUN-00:05 23700.05 50335.89 01-JUN-06:40
July 0.00 0.00 01-JUL-00:10 23033.61 48581.04 03-JUL-07:00
August 0.00 0.00 01-AUG-00:05 22858.77 47874.14 31-AUG-06:20
September 0.00 0.00 01-SEP-00:05 23152.66 48916.89 29-SEP-07:00
October 0.00 0.00 01-OCT-00:10 23865.82 50808.06 31-OCT-06:40
November 0.00 0.00 01-NOV-00:05 24810.55 52801.40 30-NOV-07:20
December 0.00 0.00 01-DEC-00:03 25721.57 54432.65 29-DEC-07:50
             
Annual Sum or Average 0.00     24696.49    
Minimum of Months 0.00 0.00   22858.77 47874.14  
Maximum of Months 0.00 0.00   26550.39 55500.92  



Table of Contents

Report: FanReportMonthly

For: FLR_3_DOAS FAN

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.271000E+10 0.70 1299.30 17-JAN-09:13 0.89
February 0.244774E+10 0.70 1299.30 01-FEB-00:03 0.89
March 0.271000E+10 0.70 1299.30 02-MAR-19:04 0.89
April 0.262258E+10 0.70 1299.30 01-APR-18:09 0.89
May 0.271000E+10 0.70 1299.30 05-MAY-22:20 0.89
June 0.262258E+10 0.70 1299.30 01-JUN-21:20 0.89
July 0.271000E+10 0.70 1299.30 04-JUL-18:40 0.89
August 0.271000E+10 0.70 1299.30 01-AUG-21:20 0.88
September 0.262258E+10 0.70 1299.30 02-SEP-18:03 0.88
October 0.271000E+10 0.70 1299.30 20-OCT-08:07 0.88
November 0.262258E+10 0.70 1299.30 21-NOV-09:07 0.88
December 0.271000E+10 0.70 1299.30 03-DEC-09:05 0.89
           
Annual Sum or Average 0.319080E+11 0.70      
Minimum of Months 0.244774E+10 0.70 1299.30   0.88
Maximum of Months 0.271000E+10 0.70 1299.30   0.89



Table of Contents

Report: FanReportMonthly

For: VAV WITH REHEAT FAN

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.331375E+11 0.79 18388.37 11-JAN-21:10 0.99
February 0.302954E+11 0.80 19120.75 27-FEB-22:10 1.01
March 0.342830E+11 0.81 19480.63 14-MAR-21:10 1.03
April 0.338123E+11 0.82 23921.22 27-APR-21:10 1.16
May 0.357228E+11 0.82 23806.57 04-MAY-21:10 1.16
June 0.352161E+11 0.83 23754.36 28-JUN-21:10 1.15
July 0.369387E+11 0.84 24789.83 31-JUL-21:10 1.18
August 0.373513E+11 0.84 25849.35 24-AUG-21:10 1.21
September 0.350692E+11 0.83 26784.71 14-SEP-21:10 1.24
October 0.350156E+11 0.81 24970.38 04-OCT-21:10 1.19
November 0.330394E+11 0.80 19959.55 03-NOV-21:10 1.04
December 0.332969E+11 0.79 18519.20 28-DEC-21:10 1.00
           
Annual Sum or Average 0.413178E+12 0.82      
Minimum of Months 0.302954E+11 0.79 18388.37   0.99
Maximum of Months 0.373513E+11 0.84 26784.71   1.24



Table of Contents

Report: FanReportMonthly

For: LAUNDRY_FLR_1 EXHAUST FAN

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.205205E+09 0.27 76.61 01-JAN-00:10 0.27
February 0.185347E+09 0.27 76.61 01-FEB-00:03 0.27
March 0.205205E+09 0.27 76.61 01-MAR-00:03 0.27
April 0.198586E+09 0.27 76.61 01-APR-00:10 0.27
May 0.205205E+09 0.27 76.61 01-MAY-00:05 0.27
June 0.198586E+09 0.27 76.61 01-JUN-00:05 0.27
July 0.205205E+09 0.27 76.61 01-JUL-00:10 0.27
August 0.205205E+09 0.27 76.61 01-AUG-00:05 0.27
September 0.198586E+09 0.27 76.61 01-SEP-00:05 0.27
October 0.205205E+09 0.27 76.61 01-OCT-00:10 0.27
November 0.198586E+09 0.27 76.61 01-NOV-00:05 0.27
December 0.205205E+09 0.27 76.61 01-DEC-00:03 0.27
           
Annual Sum or Average 0.241613E+10 0.27      
Minimum of Months 0.185347E+09 0.27 76.61   0.27
Maximum of Months 0.205205E+09 0.27 76.61   0.27



Table of Contents

Report: FanReportMonthly

For: LOBBY_FLR_1 EXHAUST FAN

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 0.00 0.00 01-JAN-00:10 0.00
February 0.00 -0.0 0.00 01-FEB-00:03 -0.0
March 0.00 0.00 0.00 01-MAR-00:03 -0.0
April 0.00 -0.0 0.00 01-APR-00:10 0.00
May 0.00 -0.0 0.00 01-MAY-00:05 0.00
June 0.00 -0.0 0.00 01-JUN-00:05 -0.0
July 0.00 0.00 0.00 01-JUL-00:10 0.00
August 0.00 -0.0 0.00 01-AUG-00:05 -0.0
September 0.00 -0.0 0.00 01-SEP-00:05 0.00
October 0.00 -0.0 0.00 01-OCT-00:10 0.00
November 0.00 -0.0 0.00 01-NOV-00:05 0.00
December 0.00 0.00 0.00 01-DEC-00:03 -0.0
           
Annual Sum or Average 0.00 -0.0      
Minimum of Months 0.00 -0.0 0.00   -0.0
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: BANQUET_FLR_6 EXHAUST FAN

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 0.00 0.00 01-JAN-00:10 0.00
February 0.00 0.00 0.00 01-FEB-00:03 0.00
March 0.00 0.00 0.00 01-MAR-00:03 0.00
April 0.00 -0.0 0.00 01-APR-00:10 0.00
May 0.00 0.00 0.00 01-MAY-00:05 0.00
June 0.00 -0.0 0.00 01-JUN-00:05 0.00
July 0.00 -0.0 0.00 01-JUL-00:10 0.00
August 0.00 -0.0 0.00 01-AUG-00:05 0.00
September 0.00 -0.0 0.00 01-SEP-00:05 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00
November 0.00 -0.0 0.00 01-NOV-00:05 0.00
December 0.00 0.00 0.00 01-DEC-00:03 0.00
           
Annual Sum or Average 0.00 -0.0      
Minimum of Months 0.00 -0.0 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: DINING_FLR_6 EXHAUST FAN

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 0.00 0.00 01-JAN-00:10 0.00
February 0.00 -0.0 0.00 01-FEB-00:03 0.00
March 0.00 -0.0 0.00 01-MAR-00:03 0.00
April 0.00 -0.0 0.00 01-APR-00:10 0.00
May 0.00 -0.0 0.00 01-MAY-00:05 0.00
June 0.00 0.00 0.00 01-JUN-00:05 0.00
July 0.00 -0.0 0.00 01-JUL-00:10 0.00
August 0.00 0.00 0.00 01-AUG-00:05 0.00
September 0.00 -0.0 0.00 01-SEP-00:05 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00
November 0.00 -0.0 0.00 01-NOV-00:05 0.00
December 0.00 -0.0 0.00 01-DEC-00:03 0.00
           
Annual Sum or Average 0.00 -0.0      
Minimum of Months 0.00 -0.0 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: KITCHEN_FLR_6 EXHAUST FAN

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.116283E+10 0.19 612.92 01-JAN-07:05 0.27
February 0.105030E+10 0.19 612.92 01-FEB-07:05 0.27
March 0.116283E+10 0.19 612.92 01-MAR-07:05 0.27
April 0.112532E+10 0.19 612.92 01-APR-06:05 0.27
May 0.116283E+10 0.19 612.92 01-MAY-06:05 0.27
June 0.112532E+10 0.19 612.92 01-JUN-06:05 0.27
July 0.116283E+10 0.19 612.92 01-JUL-06:10 0.27
August 0.116283E+10 0.19 612.92 01-AUG-06:05 0.27
September 0.112532E+10 0.19 612.92 01-SEP-06:05 0.27
October 0.116283E+10 0.19 612.92 01-OCT-06:10 0.27
November 0.112532E+10 0.19 612.92 01-NOV-06:05 0.27
December 0.116283E+10 0.19 612.92 01-DEC-07:10 0.27
           
Annual Sum or Average 0.136914E+11 0.19      
Minimum of Months 0.105030E+10 0.19 612.92   0.27
Maximum of Months 0.116283E+10 0.19 612.92   0.27



Table of Contents

Report: FanReportMonthly

For: ROOM_1_FLR_3 FAN COIL_FANCOILFAN

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.341884E+09 0.42 827.71 01-JAN-09:02 0.58
February 0.232939E+09 0.42 827.71 01-FEB-09:02 0.58
March 0.185276E+09 0.43 827.71 01-MAR-16:01 0.58
April 0.178359E+09 0.46 827.71 01-APR-15:01 0.58
May 0.229611E+09 0.50 827.71 01-MAY-15:01 0.58
June 0.243942E+09 0.51 827.71 01-JUN-08:62 0.58
July 0.359229E+09 0.53 827.71 01-JUL-08:61 0.58
August 0.344609E+09 0.53 827.71 01-AUG-08:61 0.58
September 0.243123E+09 0.49 827.71 01-SEP-15:01 0.58
October 0.160174E+09 0.45 827.71 01-OCT-08:62 0.58
November 0.231100E+09 0.42 827.71 02-NOV-15:01 0.58
December 0.323708E+09 0.43 827.71 01-DEC-09:02 0.58
           
Annual Sum or Average 0.307395E+10 0.47      
Minimum of Months 0.160174E+09 0.42 827.71   0.58
Maximum of Months 0.359229E+09 0.53 827.71   0.58



Table of Contents

Report: FanReportMonthly

For: ROOM_2_FLR_3 FAN COIL_FANCOILFAN

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.354437E+09 0.43 750.11 01-JAN-09:02 0.58
February 0.251731E+09 0.42 750.11 01-FEB-09:02 0.58
March 0.182537E+09 0.41 750.11 01-MAR-09:02 0.58
April 0.138178E+09 0.41 750.11 01-APR-15:01 0.58
May 0.143622E+09 0.41 750.11 01-MAY-15:01 0.58
June 0.160076E+09 0.39 750.11 01-JUN-08:62 0.58
July 0.235579E+09 0.39 750.11 01-JUL-08:61 0.58
August 0.231315E+09 0.39 750.11 01-AUG-08:61 0.58
September 0.125685E+09 0.37 750.11 01-SEP-08:52 0.58
October 0.132986E+09 0.40 750.11 01-OCT-08:62 0.58
November 0.240920E+09 0.41 750.11 02-NOV-08:62 0.58
December 0.340181E+09 0.44 750.11 01-DEC-09:02 0.58
           
Annual Sum or Average 0.253725E+10 0.40      
Minimum of Months 0.125685E+09 0.37 750.11   0.58
Maximum of Months 0.354437E+09 0.44 750.11   0.58



Table of Contents

Report: FanReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 0.00 0.00 01-JAN-00:10 0.00
February 0.163863E+09 0.08 1227.72 08-FEB-13:40 0.58
March 0.499837E+09 0.22 1672.09 02-MAR-13:00 0.58
April 0.824221E+09 0.39 1409.40 27-APR-13:05 0.58
May 0.100274E+10 0.44 1372.39 04-MAY-13:15 0.58
June 0.108427E+10 0.51 1064.74 28-JUN-13:05 0.58
July 0.140880E+10 0.56 1302.11 31-JUL-13:05 0.58
August 0.154074E+10 0.55 1589.48 24-AUG-13:00 0.58
September 0.132419E+10 0.51 1689.54 14-SEP-13:30 0.58
October 0.836219E+09 0.35 1770.52 04-OCT-12:40 0.58
November 0.149590E+09 0.08 1399.22 04-NOV-13:25 0.58
December 73571056.28 0.04 1134.24 05-DEC-12:30 0.58
           
Annual Sum or Average 0.890804E+10 0.31      
Minimum of Months 0.00 0.00 0.00   0.00
Maximum of Months 0.154074E+10 0.56 1770.52   0.58



Table of Contents

Report: FanReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.972966E+09 0.41 3915.77 01-JAN-09:02 0.58
February 0.770033E+09 0.41 3915.77 01-FEB-19:03 0.58
March 0.632848E+09 0.41 3915.77 01-MAR-09:02 0.58
April 0.852512E+09 0.39 3915.77 01-APR-08:62 0.58
May 0.120590E+10 0.36 3915.77 01-MAY-08:62 0.58
June 0.140697E+10 0.34 3915.77 01-JUN-08:62 0.58
July 0.162607E+10 0.34 3915.77 01-JUL-08:61 0.58
August 0.156183E+10 0.34 3915.77 01-AUG-08:61 0.58
September 0.106685E+10 0.33 3915.77 01-SEP-08:52 0.58
October 0.681758E+09 0.39 3915.77 01-OCT-08:62 0.58
November 0.666940E+09 0.41 3915.77 01-NOV-18:03 0.58
December 0.878430E+09 0.41 3915.77 01-DEC-16:01 0.58
           
Annual Sum or Average 0.123231E+11 0.38      
Minimum of Months 0.632848E+09 0.33 3915.77   0.58
Maximum of Months 0.162607E+10 0.41 3915.77   0.58



Table of Contents

Report: FanReportMonthly

For: ROOM_5_FLR_3 FAN COIL_FANCOILFAN

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.317256E+09 0.42 747.33 01-JAN-09:02 0.58
February 0.215978E+09 0.42 747.33 02-FEB-09:02 0.58
March 0.169681E+09 0.44 747.33 01-MAR-09:02 0.58
April 0.171617E+09 0.48 747.33 01-APR-08:62 0.58
May 0.197928E+09 0.51 747.33 01-MAY-15:01 0.58
June 0.250538E+09 0.53 747.33 01-JUN-08:62 0.58
July 0.302719E+09 0.54 747.33 01-JUL-08:61 0.58
August 0.328686E+09 0.54 747.33 01-AUG-08:61 0.58
September 0.216918E+09 0.50 747.33 01-SEP-15:01 0.58
October 0.153795E+09 0.46 747.33 01-OCT-08:62 0.58
November 0.214761E+09 0.42 747.33 02-NOV-15:01 0.58
December 0.302901E+09 0.43 747.33 01-DEC-09:02 0.58
           
Annual Sum or Average 0.284278E+10 0.47      
Minimum of Months 0.153795E+09 0.42 747.33   0.58
Maximum of Months 0.328686E+09 0.54 747.33   0.58



Table of Contents

Report: FanReportMonthly

For: ROOM_6_FLR_3 FAN COIL_FANCOILFAN

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.335412E+09 0.44 682.90 01-JAN-09:02 0.58
February 0.234330E+09 0.42 682.90 01-FEB-09:02 0.58
March 0.162067E+09 0.41 682.90 01-MAR-09:02 0.58
April 0.131633E+09 0.42 682.90 01-APR-08:62 0.58
May 0.139758E+09 0.42 682.90 01-MAY-15:01 0.58
June 0.182664E+09 0.42 682.90 01-JUN-08:62 0.58
July 0.209855E+09 0.41 682.90 01-JUL-08:61 0.58
August 0.225122E+09 0.41 682.90 01-AUG-08:61 0.58
September 0.124411E+09 0.38 682.90 01-SEP-08:52 0.58
October 0.127086E+09 0.40 682.90 01-OCT-08:62 0.58
November 0.224072E+09 0.41 682.90 04-NOV-15:01 0.58
December 0.318756E+09 0.44 682.90 01-DEC-09:02 0.58
           
Annual Sum or Average 0.241517E+10 0.41      
Minimum of Months 0.124411E+09 0.38 682.90   0.58
Maximum of Months 0.335412E+09 0.44 682.90   0.58



Table of Contents

Report: FanReportMonthly

For: ROOM_1_FLR_6 FAN COIL_FANCOILFAN

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.106591E+09 0.45 215.84 01-JAN-09:02 0.58
February 74410254.75 0.44 215.84 01-FEB-09:02 0.58
March 59272872.60 0.43 215.84 01-MAR-09:02 0.58
April 53010064.80 0.46 215.84 01-APR-15:01 0.58
May 63565013.81 0.50 215.84 01-MAY-15:01 0.58
June 63559627.24 0.51 215.84 01-JUN-08:62 0.58
July 93192412.10 0.53 215.84 01-JUL-08:61 0.58
August 88027134.37 0.52 215.84 01-AUG-08:61 0.58
September 62572246.80 0.49 215.84 01-SEP-15:01 0.58
October 49212153.99 0.45 215.84 01-OCT-08:62 0.58
November 74126543.93 0.43 215.84 02-NOV-15:01 0.58
December 0.101665E+09 0.46 215.84 01-DEC-09:02 0.58
           
Annual Sum or Average 0.889205E+09 0.47      
Minimum of Months 49212153.99 0.43 215.84   0.58
Maximum of Months 0.106591E+09 0.53 215.84   0.58



Table of Contents

Report: FanReportMonthly

For: ROOM_2_FLR_6 FAN COIL_FANCOILFAN

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.111865E+09 0.49 194.17 01-JAN-09:02 0.58
February 79673051.76 0.44 194.17 01-FEB-09:02 0.58
March 58030435.18 0.41 194.17 01-MAR-09:02 0.58
April 42388950.15 0.41 194.17 01-APR-08:62 0.58
May 40767717.20 0.41 194.17 01-MAY-15:01 0.58
June 42529916.48 0.39 194.17 01-JUN-08:62 0.58
July 64028254.68 0.40 194.17 01-JUL-08:61 0.58
August 60396341.19 0.39 194.17 01-AUG-08:61 0.58
September 32159721.99 0.37 194.17 01-SEP-08:52 0.58
October 43274928.85 0.40 194.17 01-OCT-08:62 0.58
November 76095652.56 0.43 194.17 02-NOV-08:62 0.58
December 0.105402E+09 0.48 194.17 01-DEC-09:02 0.58
           
Annual Sum or Average 0.756611E+09 0.42      
Minimum of Months 32159721.99 0.37 194.17   0.58
Maximum of Months 0.111865E+09 0.49 194.17   0.58



Table of Contents

Report: FanReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.385665E+09 0.43 1182.03 01-JAN-16:02 0.58
February 0.296326E+09 0.46 1182.03 01-FEB-16:01 0.58
March 0.270178E+09 0.47 1182.03 01-MAR-09:02 0.58
April 0.282841E+09 0.49 1182.03 01-APR-15:01 0.58
May 0.303912E+09 0.51 1182.03 01-MAY-15:01 0.58
June 0.318349E+09 0.51 1182.03 01-JUN-08:62 0.58
July 0.418812E+09 0.53 1182.03 01-JUL-08:61 0.58
August 0.460139E+09 0.53 1182.03 01-AUG-08:61 0.58
September 0.395380E+09 0.50 1182.03 01-SEP-15:01 0.58
October 0.279458E+09 0.48 1182.03 01-OCT-08:62 0.58
November 0.268140E+09 0.44 1182.03 02-NOV-15:01 0.58
December 0.390953E+09 0.45 1182.03 01-DEC-09:02 0.58
           
Annual Sum or Average 0.407015E+10 0.48      
Minimum of Months 0.268140E+09 0.43 1182.03   0.58
Maximum of Months 0.460139E+09 0.53 1182.03   0.58



Table of Contents

Report: PumpReportMonthly

For: HEATSYS1 PUMP

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.740369E+09 0.666332E+09 731.08 02-JAN-16:02 657.97 657.97 34.37 1.52
February 0.652426E+09 0.587184E+09 736.43 22-FEB-09:04 662.79 662.79 35.77 1.56
March 0.674883E+09 0.607395E+09 719.71 15-MAR-08:07 647.74 647.74 36.17 1.45
April 0.609781E+09 0.548803E+09 679.31 06-APR-06:05 611.38 611.38 41.48 1.23
May 0.529553E+09 0.476598E+09 670.41 18-MAY-09:05 603.37 603.37 40.10 1.20
June 0.270481E+09 0.243433E+09 607.61 15-JUN-04:00 546.85 546.85 35.26 0.98
July 0.101293E+09 91164052.07 361.76 07-JUL-05:00 325.59 325.59 29.18 0.45
August 78219101.83 70397191.65 386.32 01-AUG-08:04 347.69 347.69 28.21 0.49
September 0.286539E+09 0.257885E+09 627.05 27-SEP-03:10 564.35 564.35 35.65 1.04
October 0.755932E+09 0.680339E+09 726.15 30-OCT-08:05 653.54 653.54 35.32 1.49
November 0.719245E+09 0.647321E+09 738.12 17-NOV-09:04 664.31 664.31 34.39 1.57
December 0.737784E+09 0.664005E+09 734.90 16-DEC-19:04 661.41 661.41 34.13 1.55
                 
Annual Sum or Average 0.615651E+10 0.554086E+10            
Minimum of Months 78219101.83 70397191.65 361.76   325.59 325.59 28.21 0.45
Maximum of Months 0.755932E+09 0.680339E+09 738.12   664.31 664.31 41.48 1.57



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP SECONDARY

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 659685.07 593716.57 22.09 11-JAN-19:03 19.88 19.88 6.72 2.07
February 5444300.74 4899870.67 361.58 27-FEB-16:01 325.42 325.42 6.72 8.34
March 15777559.41 14199803.47 277.50 18-MAR-15:01 249.75 249.75 6.72 7.40
April 64238926.13 57815033.51 725.67 26-APR-15:01 653.11 653.11 6.72 11.29
May 0.103096E+09 92786404.14 654.30 04-MAY-15:02 588.87 588.87 6.72 10.80
June 0.178575E+09 0.160717E+09 709.91 20-JUN-18:02 638.92 638.92 6.72 11.18
July 0.283550E+09 0.255195E+09 868.95 31-JUL-18:02 782.06 782.06 6.72 12.18
August 0.356300E+09 0.320670E+09 1005.08 10-AUG-18:03 904.57 904.57 6.72 12.95
September 0.151563E+09 0.136407E+09 749.09 08-SEP-15:01 674.18 674.18 6.72 11.44
October 37587938.52 33829144.66 385.70 04-OCT-15:03 347.13 347.13 6.72 8.58
November 7561695.62 6805526.06 394.54 04-NOV-15:01 355.09 355.09 6.72 8.67
December 1593814.34 1434432.90 40.32 02-DEC-09:02 36.29 36.29 6.72 2.88
                 
Annual Sum or Average 0.120595E+10 0.108535E+10            
Minimum of Months 659685.07 593716.57 22.09   19.88 19.88 6.72 2.07
Maximum of Months 0.356300E+09 0.320670E+09 1005.08   904.57 904.57 6.72 12.95



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.139645E+10 0.125681E+10 2434.12 01-JAN-09:02 2190.71 2190.71 6.99 21.53
February 0.249074E+10 0.224167E+10 2434.12 01-FEB-06:03 2190.71 2190.71 6.74 21.53
March 0.445637E+10 0.401073E+10 2434.12 01-MAR-00:03 2190.71 2190.71 6.76 21.53
April 0.579090E+10 0.521181E+10 2434.12 01-APR-00:10 2190.71 2190.71 6.73 21.53
May 0.643789E+10 0.579410E+10 2434.12 01-MAY-00:05 2190.71 2190.71 6.83 21.53
June 0.630389E+10 0.567350E+10 2434.12 01-JUN-00:05 2190.71 2190.71 7.15 21.53
July 0.651955E+10 0.586760E+10 2434.12 01-JUL-00:10 2190.71 2190.71 7.33 21.53
August 0.651955E+10 0.586760E+10 2434.12 01-AUG-00:05 2190.71 2190.71 7.84 21.53
September 0.623987E+10 0.561589E+10 2434.12 01-SEP-00:05 2190.71 2190.71 7.47 21.53
October 0.559853E+10 0.503868E+10 2434.12 01-OCT-00:10 2190.71 2190.71 6.91 21.53
November 0.295111E+10 0.265600E+10 2434.12 01-NOV-00:05 2190.71 2190.71 6.73 21.53
December 0.169749E+10 0.152774E+10 2434.12 01-DEC-07:10 2190.71 2190.71 6.73 21.53
                 
Annual Sum or Average 0.564023E+11 0.507621E+11            
Minimum of Months 0.139645E+10 0.125681E+10 2434.12   2190.71 2190.71 6.73 21.53
Maximum of Months 0.651955E+10 0.586760E+10 2434.12   2190.71 2190.71 7.84 21.53



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.128314E+09 38494137.67 47.91 01-JAN-00:10 14.37 14.37 49.18 0.37
February 0.115896E+09 34768898.54 47.91 01-FEB-00:03 14.37 14.37 49.58 0.37
March 0.128314E+09 38494137.67 47.91 01-MAR-00:03 14.37 14.37 49.61 0.37
April 0.124175E+09 37252391.29 47.91 01-APR-00:10 14.37 14.37 52.66 0.37
May 0.128314E+09 38494137.67 47.91 01-MAY-00:05 14.37 14.37 52.67 0.37
June 0.124175E+09 37252391.29 47.91 01-JUN-00:05 14.37 14.37 52.96 0.37
July 0.128314E+09 38494137.67 47.91 01-JUL-00:10 14.37 14.37 53.41 0.37
August 0.128314E+09 38494137.67 47.91 01-AUG-00:05 14.37 14.37 53.33 0.37
September 0.124175E+09 37252391.29 47.91 01-SEP-00:05 14.37 14.37 53.31 0.37
October 0.128314E+09 38494137.67 47.91 01-OCT-00:10 14.37 14.37 52.56 0.37
November 0.124175E+09 37252391.29 47.91 01-NOV-00:05 14.37 14.37 52.89 0.37
December 0.128314E+09 38494137.67 47.91 01-DEC-00:03 14.37 14.37 50.07 0.37
                 
Annual Sum or Average 0.151079E+10 0.453237E+09            
Minimum of Months 0.115896E+09 34768898.54 47.91   14.37 14.37 49.18 0.37
Maximum of Months 0.128314E+09 38494137.67 47.91   14.37 14.37 53.41 0.37



Table of Contents

Report: CondLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 42.74 60.00 33476.87 163121.08 02-JAN-16:02
February 0.00 0.00 01-FEB-00:03 44.52 60.00 35345.41 158030.82 22-FEB-09:04
March 0.00 0.00 01-MAR-00:03 45.77 60.00 36652.82 144112.30 15-MAR-08:07
April 0.00 0.00 01-APR-00:10 37.38 60.00 36652.92 129681.18 18-APR-15:04
May 0.00 0.00 01-MAY-00:05 31.16 60.00 31771.97 120978.54 28-MAY-08:03
June 0.00 0.00 01-JUN-00:05 25.25 60.00 16752.82 100869.71 15-JUN-04:00
July 0.00 0.00 01-JUL-00:10 26.84 26.84 6061.27 58593.92 19-JUL-05:00
August 0.00 0.00 01-AUG-00:05 27.02 27.02 4662.11 65555.32 01-AUG-08:04
September 0.00 0.00 01-SEP-00:05 29.32 29.32 17591.35 106483.59 28-SEP-08:04
October 0.00 0.00 01-OCT-00:10 23.60 60.00 44685.06 153595.98 30-OCT-08:05
November 0.00 0.00 01-NOV-00:05 34.49 60.00 38884.56 168464.52 17-NOV-09:04
December 0.00 0.00 01-DEC-00:03 42.40 60.00 34829.55 167650.85 16-DEC-19:04
                 
Annual Sum or Average 0.00         28061.51    
Minimum of Months 0.00 0.00   23.60 26.84 4662.11 58593.92  
Maximum of Months 0.00 0.00   45.77 60.00 44685.06 168464.52  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 1124.94 34372.80 11-JAN-19:03 7.08 6.70 0.00 0.00 01-JAN-00:10
February 5702.19 216998.28 27-FEB-16:03 9.10 6.70 0.00 0.00 01-FEB-00:03
March 12460.75 265608.87 18-MAR-15:01 9.64 6.70 0.00 0.00 01-MAR-00:03
April 32478.55 389617.12 27-APR-18:03 11.02 6.70 0.00 0.00 01-APR-00:10
May 50771.85 354540.72 04-MAY-15:03 10.63 6.70 0.00 0.00 01-MAY-00:05
June 75736.02 392319.47 28-JUN-18:03 11.05 6.70 0.00 0.00 01-JUN-00:05
July 110767.84 455087.94 27-JUL-18:03 11.75 6.70 0.00 0.00 01-JUL-00:10
August 130885.15 487055.67 10-AUG-18:03 12.10 6.70 0.00 0.00 01-AUG-00:05
September 68903.44 390036.38 14-SEP-15:03 11.02 6.70 0.00 0.00 01-SEP-00:05
October 23734.24 310852.05 04-OCT-15:03 10.14 6.70 0.00 0.00 01-OCT-00:10
November 6652.34 301776.38 04-NOV-15:03 10.04 6.70 0.00 0.00 01-NOV-00:05
December 2062.59 45825.67 02-DEC-09:02 7.21 6.70 0.00 0.00 01-DEC-00:03
                 
Annual Sum or Average 43722.74         0.00    
Minimum of Months 1124.94 34372.80   7.08 6.70 0.00 0.00  
Maximum of Months 130885.15 487055.67   12.10 6.70 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 49.18 60.05 26364.65 55433.29 31-JAN-08:00
February 0.00 0.00 01-FEB-00:03 49.58 60.05 26550.39 55500.92 10-FEB-07:15
March 0.00 0.00 01-MAR-00:03 49.61 60.05 26273.73 55310.08 01-MAR-07:20
April 0.00 0.00 01-APR-00:10 52.66 60.05 25546.60 54075.96 03-APR-06:30
May 0.00 0.00 01-MAY-00:05 52.67 60.05 24608.09 52394.42 01-MAY-06:50
June 0.00 0.00 01-JUN-00:05 52.96 60.05 23700.05 50335.89 01-JUN-06:40
July 0.00 0.00 01-JUL-00:10 53.41 60.05 23033.61 48581.04 03-JUL-07:00
August 0.00 0.00 01-AUG-00:05 53.33 60.05 22858.77 47874.14 31-AUG-06:20
September 0.00 0.00 01-SEP-00:05 53.31 60.05 23152.66 48916.89 29-SEP-07:00
October 0.00 0.00 01-OCT-00:10 52.56 60.05 23865.82 50808.06 31-OCT-06:40
November 0.00 0.00 01-NOV-00:05 52.89 60.05 24810.55 52801.40 30-NOV-07:20
December 0.00 0.00 01-DEC-00:03 50.07 60.05 25721.57 54432.65 29-DEC-07:50
                 
Annual Sum or Average 0.00         24696.49    
Minimum of Months 0.00 0.00   49.18 60.05 22858.77 47874.14  
Maximum of Months 0.00 0.00   53.41 60.05 26550.39 55500.92  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BASEMENT

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: RETAIL_1_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: RETAIL_2_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: MECH_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: STORAGE_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: LAUNDRY_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CAFE_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: LOBBY_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_1_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_2_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_5_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_6_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORRIDOR_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_1_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_2_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BANQUET_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DINING_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: KITCHEN_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORRIDOR_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: FLR_3_DOAS

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.107885E+09 0.00 0.00 0.271000E+10 0.00 0.00
February 94116059.72 0.00 0.108438E+09 0.244774E+10 0.00 0.00
March 14570.92 0.00 0.232884E+09 0.271000E+10 0.00 0.00
April 5374.59 0.00 0.179842E+10 0.262258E+10 0.00 0.00
May 7907.92 0.00 0.355559E+10 0.271000E+10 0.00 0.00
June 24976.93 0.00 0.630895E+10 0.262258E+10 0.00 0.00
July 25196.21 0.00 0.116585E+11 0.271000E+10 0.00 0.00
August 28778.06 0.00 0.152262E+11 0.271000E+10 0.00 0.00
September 21135.78 0.00 0.544189E+10 0.262258E+10 0.00 0.00
October 4594.50 0.00 0.903800E+09 0.271000E+10 0.00 0.00
November 134237.44 0.00 0.218215E+09 0.262258E+10 0.00 0.00
December 14198385.80 0.00 0.00 0.271000E+10 0.00 0.00
             
Annual Sum or Average 0.216466E+09 0.00 0.454529E+11 0.319080E+11 0.00 0.00
Minimum of Months 4594.50 0.00 0.00 0.244774E+10 0.00 0.00
Maximum of Months 0.107885E+09 0.00 0.152262E+11 0.271000E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV WITH REHEAT

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.595061E+11 0.00 0.00 0.331375E+11 0.00 0.00
February 0.666315E+11 0.00 0.177965E+10 0.302954E+11 0.00 0.00
March 0.901301E+11 0.00 0.394681E+10 0.342830E+11 0.00 0.00
April 0.924768E+11 0.00 0.284700E+11 0.338123E+11 0.00 0.00
May 0.847403E+11 0.00 0.551595E+11 0.357228E+11 0.00 0.00
June 0.435050E+11 0.00 0.986138E+11 0.352161E+11 0.00 0.00
July 0.162630E+11 0.00 0.166404E+12 0.369387E+11 0.00 0.00
August 0.124621E+11 0.00 0.209638E+12 0.373513E+11 0.00 0.00
September 0.454058E+11 0.00 0.803282E+11 0.350692E+11 0.00 0.00
October 0.116004E+12 0.00 0.149889E+11 0.350156E+11 0.00 0.00
November 0.855285E+11 0.00 0.341840E+10 0.330394E+11 0.00 0.00
December 0.659983E+11 0.00 0.00 0.332969E+11 0.00 0.00
             
Annual Sum or Average 0.778651E+12 0.00 0.662748E+12 0.413178E+12 0.00 0.00
Minimum of Months 0.124621E+11 0.00 0.00 0.302954E+11 0.00 0.00
Maximum of Months 0.116004E+12 0.00 0.209638E+12 0.373513E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: FLR_3_DOAS

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.271000E+10 0.00 0.107885E+09 0.428279E+11 0.00 0.00 0.00 0.00
February 0.244774E+10 0.108438E+09 94116059.72 0.342462E+11 0.00 0.00 0.00 0.00
March 0.271000E+10 0.232884E+09 14570.92 0.285506E+11 0.00 0.00 0.00 0.00
April 0.262258E+10 0.179842E+10 5374.59 0.195564E+11 66000322.98 0.00 0.00 0.00
May 0.271000E+10 0.355559E+10 7907.92 0.126563E+11 47890353.55 0.00 0.00 0.00
June 0.262258E+10 0.630895E+10 24976.93 0.461220E+10 70261490.73 0.00 0.00 0.00
July 0.271000E+10 0.116585E+11 25196.21 0.166400E+10 0.805621E+09 0.00 0.00 0.00
August 0.271000E+10 0.152262E+11 28778.06 0.112849E+10 0.177236E+10 0.00 0.00 0.00
September 0.262258E+10 0.544189E+10 21135.78 0.468909E+10 0.122063E+09 0.00 0.00 0.00
October 0.271000E+10 0.903800E+09 4594.50 0.160422E+11 0.00 0.00 0.00 0.00
November 0.262258E+10 0.218215E+09 134237.44 0.277552E+11 0.00 0.00 0.00 0.00
December 0.271000E+10 0.00 14198385.80 0.396913E+11 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.319080E+11 0.454529E+11 0.216466E+09 0.233420E+12 0.288419E+10 0.00 0.00 0.00
Minimum of Months 0.244774E+10 0.00 4594.50 0.112849E+10 0.00 0.00 0.00 0.00
Maximum of Months 0.271000E+10 0.152262E+11 0.107885E+09 0.428279E+11 0.177236E+10 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV WITH REHEAT

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.331375E+11 0.00 0.595061E+11 0.465655E+12 0.00 0.00 0.00 0.00
February 0.302954E+11 0.177965E+10 0.666315E+11 0.339163E+12 0.00 0.00 0.00 0.00
March 0.342830E+11 0.394681E+10 0.901301E+11 0.227734E+12 0.00 0.00 0.00 0.00
April 0.338123E+11 0.284700E+11 0.924768E+11 0.110523E+12 0.277059E+09 0.00 0.00 0.00
May 0.357228E+11 0.551595E+11 0.847403E+11 0.390086E+11 0.00 0.00 0.00 0.00
June 0.352161E+11 0.986138E+11 0.435050E+11 0.197899E+10 24945550.41 0.00 0.00 0.00
July 0.369387E+11 0.166404E+12 0.162630E+11 0.176997E+10 0.302243E+10 0.00 0.00 0.00
August 0.373513E+11 0.209638E+12 0.124621E+11 0.292313E+10 0.822426E+10 0.00 0.00 0.00
September 0.350692E+11 0.803282E+11 0.454058E+11 0.234667E+10 0.00 0.00 0.00 0.00
October 0.350156E+11 0.149889E+11 0.116004E+12 0.419041E+11 0.00 0.00 0.00 0.00
November 0.330394E+11 0.341840E+10 0.855285E+11 0.239018E+12 0.00 0.00 0.00 0.00
December 0.332969E+11 0.00 0.659983E+11 0.413367E+12 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.413178E+12 0.662748E+12 0.778651E+12 0.188539E+13 0.115487E+11 0.00 0.00 0.00
Minimum of Months 0.302954E+11 0.00 0.124621E+11 0.176997E+10 0.00 0.00 0.00 0.00
Maximum of Months 0.373513E+11 0.209638E+12 0.116004E+12 0.465655E+12 0.822426E+10 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: FLR_3_DOAS

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.271000E+10 0.107885E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.244774E+10 94116059.72 0.108438E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.271000E+10 14570.92 0.232884E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.262258E+10 5374.59 0.179842E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.271000E+10 7907.92 0.355559E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.262258E+10 24976.93 0.630895E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.271000E+10 25196.21 0.116585E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.271000E+10 28778.06 0.152262E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.262258E+10 21135.78 0.544189E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.271000E+10 4594.50 0.903800E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.262258E+10 134237.44 0.218215E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.271000E+10 14198385.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.319080E+11 0.216466E+09 0.454529E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.244774E+10 4594.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.271000E+10 0.107885E+09 0.152262E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV WITH REHEAT

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.331375E+11 0.595061E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.302954E+11 0.666315E+11 0.177965E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.342830E+11 0.901301E+11 0.394681E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.338123E+11 0.924768E+11 0.284700E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.357228E+11 0.847403E+11 0.551595E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.352161E+11 0.435050E+11 0.986138E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.369387E+11 0.162630E+11 0.166404E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.373513E+11 0.124621E+11 0.209638E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.350692E+11 0.454058E+11 0.803282E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.350156E+11 0.116004E+12 0.149889E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.330394E+11 0.855285E+11 0.341840E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.332969E+11 0.659983E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.413178E+12 0.778651E+12 0.662748E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.302954E+11 0.124621E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.373513E+11 0.116004E+12 0.209638E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BASEMENT

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.394109E+11 0.00 0.00 5018573.52 0.00 0.00 0.875337E+10 0.00 0.99
February 0.407849E+11 0.00 0.00 1760336.82 0.00 0.00 0.508241E+10 0.00 1.00
March 0.521809E+11 0.00 0.00 218736.30 0.00 0.00 0.154945E+10 0.00 0.99
April 0.513941E+11 0.00 0.00 0.00 8470882.52 0.00 0.00 0.00 0.99
May 0.489624E+11 0.00 0.00 113524.82 0.00 0.00 0.172215E+10 0.00 0.99
June 0.382172E+11 0.00 0.00 1247766.69 0.00 0.00 0.363330E+10 0.00 0.99
July 0.294207E+11 101091.57 0.00 4294909.06 0.101677E+09 0.00 0.591071E+10 0.00 0.99
August 0.182740E+11 8094467.32 0.00 12809667.94 0.334449E+09 0.00 0.132622E+11 0.00 1.00
September 0.141177E+11 0.00 0.00 22396631.10 0.00 0.00 0.304614E+11 0.00 1.01
October 0.162106E+11 0.00 0.00 30687910.12 0.00 0.00 0.421910E+11 0.00 1.03
November 0.154419E+11 0.00 0.00 30999760.89 0.00 0.00 0.371761E+11 0.00 1.03
December 0.251917E+11 0.00 0.00 15494494.54 0.00 0.00 0.247539E+11 0.00 1.00
                   
Annual Sum or Average 0.389607E+12 8195558.89 0.00 0.125042E+09 0.444596E+09 0.00 0.174496E+12 0.00 1.00
Minimum of Months 0.141177E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.99
Maximum of Months 0.521809E+11 8094467.32 0.00 30999760.89 0.334449E+09 0.00 0.421910E+11 0.00 1.03



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: RETAIL_1_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.664260E+10 0.00 0.00 32688.22 0.00 0.167620E+10 48091152.50 0.00 3.10
February 0.708180E+10 0.00 0.00 271764.43 0.00 0.606146E+09 0.288097E+09 0.00 3.13
March 0.886546E+10 0.00 0.00 534561.09 0.00 9914772.38 0.490043E+09 0.00 3.12
April 0.862716E+10 1856810.51 0.00 461666.17 0.00 0.00 0.301517E+09 0.00 3.12
May 0.854185E+10 0.00 0.00 512660.94 0.00 0.00 0.263704E+09 0.00 3.12
June 0.713178E+10 0.00 0.00 228686.88 0.00 0.00 0.137562E+09 0.00 3.12
July 0.589663E+10 13847473.75 0.00 702932.10 4452895.31 0.00 0.240673E+09 0.00 3.13
August 0.516028E+10 62453403.41 0.00 1034735.91 5612654.10 0.00 0.307379E+09 0.00 3.18
September 0.702296E+10 0.00 0.00 2354472.66 0.00 0.00 0.659063E+09 0.00 3.20
October 0.927922E+10 0.00 0.00 980056.67 0.00 0.00 0.615785E+09 0.00 3.15
November 0.848948E+10 0.00 0.00 183291.84 0.00 0.231917E+09 0.136874E+09 0.00 3.11
December 0.681010E+10 0.00 0.00 103870.96 0.00 0.158084E+10 0.197107E+09 0.00 3.10
                   
Annual Sum or Average 0.895493E+11 78157687.67 0.00 7401387.86 10065549.41 0.410501E+10 0.368589E+10 0.00 3.13
Minimum of Months 0.516028E+10 0.00 0.00 32688.22 0.00 0.00 48091152.50 0.00 3.10
Maximum of Months 0.927922E+10 62453403.41 0.00 2354472.66 5612654.10 0.167620E+10 0.659063E+09 0.00 3.20



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: RETAIL_2_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.438766E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.41
February 0.413352E+10 0.00 0.00 7767.22 0.00 0.00 44614847.83 0.00 1.42
March 0.472667E+10 0.00 0.00 46120.04 0.00 0.00 0.167514E+09 0.00 1.41
April 0.414505E+10 0.00 0.00 282970.49 771599.16 0.00 0.541113E+09 0.00 1.42
May 0.359988E+10 0.00 0.00 687771.67 0.00 0.00 0.102523E+10 0.00 1.42
June 0.269677E+10 0.00 0.00 995744.73 0.00 0.00 0.113031E+10 0.00 1.43
July 0.158769E+10 4087266.98 0.00 2091588.82 5194776.34 0.00 0.168055E+10 0.00 1.45
August 0.141266E+10 11993599.22 0.00 2407492.73 19390471.78 0.00 0.150506E+10 0.00 1.46
September 0.268373E+10 0.00 0.00 1262347.81 0.00 0.00 0.135573E+10 0.00 1.44
October 0.462031E+10 0.00 0.00 278619.18 0.00 0.00 0.550522E+09 0.00 1.42
November 0.461992E+10 0.00 0.00 3759.25 0.00 0.00 23680068.49 0.00 1.41
December 0.450331E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.41
                   
Annual Sum or Average 0.431172E+11 16080866.20 0.00 8064181.94 25356847.28 0.00 0.802433E+10 0.00 1.42
Minimum of Months 0.141266E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.41
Maximum of Months 0.472667E+10 11993599.22 0.00 2407492.73 19390471.78 0.00 0.168055E+10 0.00 1.46



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: MECH_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.326111E+10 0.00 0.00 0.00 0.00 29406343.75 0.00 0.00 0.50
February 0.313339E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.50
March 0.367042E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.50
April 0.351081E+10 0.00 0.00 0.00 578659.27 0.00 0.00 0.00 0.50
May 0.346235E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.50
June 0.285327E+10 0.00 0.00 1645.31 0.00 0.00 5686695.99 0.00 0.50
July 0.234001E+10 6905.72 0.00 124341.29 6945695.72 0.00 74461155.65 0.00 0.50
August 0.200643E+10 412682.95 0.00 318406.42 22990706.03 0.00 0.145184E+09 0.00 0.51
September 0.297806E+10 0.00 0.00 8948.50 0.00 0.00 24242396.08 0.00 0.50
October 0.387483E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.50
November 0.348246E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.50
December 0.335973E+10 0.00 0.00 0.00 0.00 17523053.71 0.00 0.00 0.50
                   
Annual Sum or Average 0.379329E+11 419588.67 0.00 453341.52 30515061.03 46929397.46 0.249574E+09 0.00 0.50
Minimum of Months 0.200643E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.50
Maximum of Months 0.387483E+10 412682.95 0.00 318406.42 22990706.03 29406343.75 0.145184E+09 0.00 0.51



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: STORAGE_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.167120E+10 0.00 0.00 0.00 0.00 0.284380E+09 0.00 0.00 0.51
February 0.168750E+10 0.00 0.00 0.00 0.00 0.174694E+09 0.00 0.00 0.52
March 0.218135E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.51
April 0.208650E+10 0.00 0.00 0.00 343900.92 0.00 0.00 0.00 0.51
May 0.205769E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.52
June 0.169910E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.52
July 0.143456E+10 0.00 0.00 0.00 4131975.63 0.00 0.00 0.00 0.52
August 0.127481E+10 53155.03 0.00 2190.66 13853417.67 0.00 2490723.33 0.00 0.52
September 0.178429E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.52
October 0.230284E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.52
November 0.206767E+10 0.00 0.00 0.00 0.00 1977705.45 0.00 0.00 0.51
December 0.186359E+10 0.00 0.00 0.00 0.00 0.143531E+09 0.00 0.00 0.51
                   
Annual Sum or Average 0.221111E+11 53155.03 0.00 2190.66 18329294.22 0.604583E+09 2490723.33 0.00 0.52
Minimum of Months 0.127481E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.51
Maximum of Months 0.230284E+10 53155.03 0.00 2190.66 13853417.67 0.284380E+09 2490723.33 0.00 0.52



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: LAUNDRY_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.232474E+09 0.00 0.00 90961917.37 0.00 0.00 0.723315E+11 0.00 23.18
February 0.173710E+09 0.00 0.00 81701675.73 0.00 0.00 0.690093E+11 0.00 23.37
March 0.187004E+09 0.00 0.00 92226189.49 0.00 0.00 0.814107E+11 0.00 23.36
April 0.145553E+09 10931651.48 0.00 98072671.49 0.00 0.00 0.777161E+11 0.00 23.31
May 0.123989E+09 0.00 0.00 0.109907E+09 0.00 0.00 0.766896E+11 0.00 23.36
June 51581703.23 0.00 0.00 0.113773E+09 0.00 0.00 0.628713E+11 0.00 23.41
July 62371327.44 0.140808E+09 0.00 0.122164E+09 1363971.10 0.00 0.526559E+11 0.00 23.30
August 30268309.92 0.464923E+09 0.00 0.117637E+09 1174711.21 0.00 0.471168E+11 0.00 23.49
September 83595808.41 0.00 0.00 0.108929E+09 0.00 0.00 0.661075E+11 0.00 23.39
October 0.176398E+09 0.00 0.00 95751670.66 0.00 0.00 0.857428E+11 0.00 23.41
November 0.174567E+09 0.00 0.00 87874487.92 0.00 0.00 0.765544E+11 0.00 23.27
December 0.245849E+09 0.00 0.00 90183309.78 0.00 0.00 0.738642E+11 0.00 23.13
                   
Annual Sum or Average 0.168736E+10 0.616663E+09 0.00 0.120918E+10 2538682.31 0.00 0.842070E+12 0.00 23.33
Minimum of Months 30268309.92 0.00 0.00 81701675.73 0.00 0.00 0.471168E+11 0.00 23.13
Maximum of Months 0.245849E+09 0.464923E+09 0.00 0.122164E+09 1363971.10 0.00 0.857428E+11 0.00 23.49



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CAFE_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.302231E+11 0.00 0.00 605389.46 0.00 0.00 0.318556E+10 0.00 4.41
February 0.231926E+11 0.00 0.00 3142265.32 0.00 0.00 0.865969E+10 0.00 4.45
March 0.216878E+11 0.00 0.00 6326835.90 0.00 0.00 0.157080E+11 0.00 4.44
April 0.184814E+11 6828949.27 0.00 8308747.94 0.00 0.00 0.171669E+11 0.00 4.44
May 0.156057E+11 0.00 0.00 10692154.86 0.00 0.00 0.195478E+11 0.00 4.44
June 0.104044E+11 0.00 0.00 11503290.09 0.00 0.00 0.186124E+11 0.00 4.44
July 0.698125E+10 63045211.02 0.00 17414047.70 8406344.56 0.00 0.175224E+11 0.00 4.45
August 0.628784E+10 0.244694E+09 0.00 20218663.99 12271951.28 0.00 0.155861E+11 0.00 4.52
September 0.107564E+11 0.00 0.00 21943302.27 0.00 0.00 0.198929E+11 0.00 4.53
October 0.191299E+11 0.00 0.00 11082126.71 0.00 0.00 0.203561E+11 0.00 4.48
November 0.262074E+11 0.00 0.00 2567355.16 0.00 0.00 0.916737E+10 0.00 4.42
December 0.295322E+11 0.00 0.00 1308175.36 0.00 0.00 0.476726E+10 0.00 4.41
                   
Annual Sum or Average 0.218490E+12 0.314569E+09 0.00 0.115112E+09 20678295.84 0.00 0.170173E+12 0.00 4.45
Minimum of Months 0.628784E+10 0.00 0.00 605389.46 0.00 0.00 0.318556E+10 0.00 4.41
Maximum of Months 0.302231E+11 0.244694E+09 0.00 21943302.27 12271951.28 0.00 0.203561E+11 0.00 4.53



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: LOBBY_FLR_1

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.919761E+11 0.00 0.00 872886.30 0.00 0.00 0.524433E+10 0.00 1.86
February 0.780481E+11 0.00 0.00 4436689.95 0.00 0.00 0.145305E+11 0.00 1.87
March 0.756936E+11 0.00 0.00 12141342.07 0.00 0.00 0.327604E+11 0.00 1.86
April 0.596440E+11 12277206.61 0.00 22837466.76 4819798.04 0.00 0.442614E+11 0.00 1.87
May 0.470872E+11 0.00 0.00 38493724.75 0.00 0.00 0.556230E+11 0.00 1.88
June 0.309905E+11 0.00 0.00 51711886.82 0.00 0.00 0.541570E+11 0.00 1.89
July 0.194638E+11 0.124214E+09 0.00 71376851.07 81212615.79 0.00 0.533741E+11 0.00 1.91
August 0.167586E+11 0.505511E+09 0.00 77564490.46 0.186964E+09 0.00 0.487426E+11 0.00 1.94
September 0.313030E+11 0.00 0.00 57439718.74 0.00 0.00 0.586917E+11 0.00 1.90
October 0.616485E+11 0.00 0.00 26992166.29 0.00 0.00 0.531660E+11 0.00 1.88
November 0.817943E+11 0.00 0.00 6033702.08 0.00 0.00 0.210921E+11 0.00 1.86
December 0.923654E+11 0.00 0.00 1735465.02 0.00 0.00 0.741677E+10 0.00 1.85
                   
Annual Sum or Average 0.686773E+12 0.642002E+09 0.00 0.371636E+09 0.272996E+09 0.00 0.449060E+12 0.00 1.88
Minimum of Months 0.167586E+11 0.00 0.00 872886.30 0.00 0.00 0.524433E+10 0.00 1.85
Maximum of Months 0.923654E+11 0.505511E+09 0.00 77564490.46 0.186964E+09 0.00 0.586917E+11 0.00 1.94



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_1_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 68403761.98 0.00 0.00 128465.52 0.00 0.141156E+10 13714524.41 0.00 0.35
February 66722030.63 0.00 0.00 994159.62 0.00 0.104871E+10 0.228604E+09 0.00 0.36
March 77146645.11 0.00 0.00 3088707.12 0.00 0.883506E+09 0.527672E+09 0.00 0.35
April 59200699.32 858256.74 0.00 7111786.94 0.00 0.389178E+09 0.900227E+09 0.00 0.36
May 31047599.14 1597998.20 0.00 13323598.21 0.00 96926486.06 0.114448E+10 0.00 0.36
June 18608644.35 747072.97 0.00 14397816.67 0.00 3553347.52 0.103028E+10 0.00 0.36
July 1724771.82 16706797.76 0.00 16411734.10 0.00 1937548.82 0.838442E+09 0.00 0.35
August 4437375.15 40381902.49 10172.30 12325083.20 0.00 2048132.98 0.626796E+09 2999.06 0.36
September 28450022.80 4684449.21 0.00 12663294.19 0.00 37303473.60 0.953266E+09 0.00 0.36
October 56344842.23 0.00 0.00 5067060.89 0.00 0.528813E+09 0.837423E+09 0.00 0.36
November 67058600.87 0.00 0.00 740950.87 0.00 0.116373E+10 0.187370E+09 0.00 0.35
December 62266434.61 0.00 0.00 261736.81 0.00 0.135848E+10 69605271.47 0.00 0.35
                   
Annual Sum or Average 0.541411E+09 64976477.37 10172.30 86514394.12 0.00 0.692575E+10 0.735788E+10 2999.06 0.36
Minimum of Months 1724771.82 0.00 0.00 128465.52 0.00 1937548.82 13714524.41 0.00 0.35
Maximum of Months 77146645.11 40381902.49 10172.30 16411734.10 0.00 0.141156E+10 0.114448E+10 2999.06 0.36



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_2_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 60770912.60 0.00 0.00 20410.64 0.00 0.142991E+10 2932581.59 0.00 0.35
February 73636550.31 0.00 0.00 367461.73 0.00 0.116057E+10 0.110307E+09 0.00 0.36
March 0.101445E+09 0.00 0.00 1537154.62 0.00 0.106763E+10 0.320627E+09 0.00 0.35
April 0.128823E+09 854305.23 0.00 4737735.57 3850.95 0.510868E+09 0.711129E+09 0.00 0.36
May 0.184511E+09 1292544.00 5507.35 9834728.19 299478.36 0.109506E+09 0.981776E+09 281.26 0.36
June 0.216492E+09 664909.83 0.00 10849495.77 82075.61 3942571.41 0.835435E+09 0.00 0.36
July 0.201059E+09 14100928.02 1822.36 12541632.19 2600894.93 1905040.28 0.642909E+09 1195.00 0.36
August 0.175839E+09 37579307.81 15475.45 8226436.51 2788288.26 1996311.88 0.459469E+09 7269.46 0.36
September 0.206294E+09 3492917.03 0.00 7895336.33 1190983.32 45002564.70 0.772371E+09 0.00 0.36
October 0.127747E+09 0.00 0.00 2510676.28 0.00 0.703774E+09 0.593449E+09 0.00 0.36
November 75411052.59 0.00 0.00 284278.71 0.00 0.123794E+10 0.105099E+09 0.00 0.35
December 57325342.92 0.00 0.00 36929.69 0.00 0.142903E+10 4040467.90 0.00 0.35
                   
Annual Sum or Average 0.160935E+10 57984911.92 22805.15 58842276.25 6965571.43 0.770207E+10 0.553954E+10 8745.73 0.36
Minimum of Months 57325342.92 0.00 0.00 20410.64 0.00 1905040.28 2932581.59 0.00 0.35
Maximum of Months 0.216492E+09 37579307.81 15475.45 12541632.19 2788288.26 0.142991E+10 0.981776E+09 7269.46 0.36



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.918003E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.02
February 0.792905E+09 0.00 0.00 841226.40 0.00 0.00 0.371290E+09 0.00 0.02
March 0.606650E+09 0.00 0.00 2127187.21 0.00 0.00 0.979089E+09 0.00 0.02
April 0.277566E+09 5060235.45 0.00 2545844.74 0.00 0.00 0.112225E+10 0.00 0.02
May 0.237708E+09 1532831.23 0.00 2988066.47 0.00 0.00 0.105785E+10 0.00 0.02
June 29227501.74 0.00 0.00 3021112.13 0.00 0.00 0.106238E+10 0.00 0.02
July 0.00 36374494.43 0.00 3104297.25 0.00 0.00 0.519147E+09 0.00 0.02
August 0.00 99871961.16 0.00 2057983.88 0.00 0.00 0.385587E+09 0.00 0.02
September 0.225604E+09 40128408.89 0.00 3062867.92 0.00 0.00 0.644725E+09 0.00 0.02
October 0.591607E+09 0.00 0.00 2845216.53 0.00 0.00 0.917565E+09 0.00 0.02
November 0.101224E+10 0.00 0.00 535348.08 0.00 0.00 0.248257E+09 0.00 0.02
December 0.917282E+09 0.00 0.00 244769.91 0.00 0.00 0.162099E+09 0.00 0.02
                   
Annual Sum or Average 0.560879E+10 0.182968E+09 0.00 23373920.51 0.00 0.00 0.747024E+10 0.00 0.02
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.02
Maximum of Months 0.101224E+10 99871961.16 0.00 3104297.25 0.00 0.00 0.112225E+10 0.00 0.02



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.964134E+09 0.00 0.00 11870559.74 0.00 0.781185E+10 0.114724E+11 0.00 0.40
February 0.100373E+10 0.00 0.00 19240675.20 0.00 0.554214E+10 0.116773E+11 0.00 0.40
March 0.137604E+10 0.00 0.00 43749863.33 0.00 0.333718E+09 0.184743E+11 0.00 0.40
April 0.175887E+10 10725927.44 0.00 80489611.27 914446.35 80194428.51 0.164678E+11 0.00 0.40
May 0.268835E+10 12554324.33 80680.62 0.126202E+09 9025277.20 32545796.98 0.145917E+11 13065.14 0.40
June 0.321302E+10 9019102.98 0.00 0.145984E+09 1113306.42 11763011.33 0.110986E+11 0.00 0.40
July 0.306358E+10 0.167088E+09 113157.21 0.151480E+09 59382752.81 6256510.81 0.842257E+10 6894.25 0.40
August 0.248127E+10 0.436107E+09 1033835.43 0.104690E+09 0.110682E+09 7527060.05 0.616276E+10 48560.15 0.40
September 0.285584E+10 25648321.65 0.00 0.103346E+09 37885976.82 32800039.41 0.110005E+11 0.00 0.40
October 0.172490E+10 0.00 0.00 58868462.99 0.00 0.188383E+09 0.173908E+11 0.00 0.40
November 0.105005E+10 0.00 0.00 28531071.35 0.00 0.208131E+10 0.160844E+11 0.00 0.40
December 0.985779E+09 0.00 0.00 12219422.01 0.00 0.732099E+10 0.118979E+11 0.00 0.40
                   
Annual Sum or Average 0.231656E+11 0.661143E+09 1227673.26 0.886672E+09 0.219003E+09 0.234495E+11 0.154741E+12 68519.54 0.40
Minimum of Months 0.964134E+09 0.00 0.00 11870559.74 0.00 6256510.81 0.616276E+10 0.00 0.40
Maximum of Months 0.321302E+10 0.436107E+09 1033835.43 0.151480E+09 0.110682E+09 0.781185E+10 0.184743E+11 48560.15 0.40



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_5_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 68166545.25 0.00 0.00 62002.82 0.00 0.140136E+10 24220602.01 0.00 0.35
February 67125714.25 0.00 0.00 872420.44 0.00 0.105473E+10 0.222304E+09 0.00 0.36
March 67599448.08 0.00 0.00 2944221.46 0.00 0.860600E+09 0.560271E+09 0.00 0.35
April 36091451.62 858256.74 0.00 7516405.82 0.00 0.364884E+09 0.947225E+09 0.00 0.36
May 26687209.21 1592208.91 5183.40 11331154.81 0.00 0.123708E+09 0.112405E+10 605.89 0.36
June 15026102.53 746980.05 0.00 15043445.97 0.00 12309863.72 0.102446E+10 92.92 0.36
July 2825036.38 16706797.76 0.00 15594575.24 0.00 1814247.35 0.838282E+09 0.00 0.35
August 4353342.60 40382558.80 10168.02 13372148.05 0.00 1629750.41 0.626251E+09 2347.03 0.36
September 28685131.58 4684449.21 0.00 11584300.80 0.00 46595899.65 0.944818E+09 0.00 0.36
October 46470362.68 0.00 0.00 4909739.44 0.00 0.538407E+09 0.837860E+09 0.00 0.36
November 66567349.10 0.00 0.00 714868.15 0.00 0.115163E+10 0.199990E+09 0.00 0.35
December 63303489.23 0.00 0.00 229708.11 0.00 0.136676E+10 60314315.83 0.00 0.35
                   
Annual Sum or Average 0.492901E+09 64971251.46 15351.42 84174991.10 0.00 0.692443E+10 0.741005E+10 3045.85 0.36
Minimum of Months 2825036.38 0.00 0.00 62002.82 0.00 1629750.41 24220602.01 0.00 0.35
Maximum of Months 68166545.25 40382558.80 10168.02 15594575.24 0.00 0.140136E+10 0.112405E+10 2347.03 0.36



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_6_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 53669069.99 0.00 0.00 18733.92 0.00 0.143591E+10 4039181.44 0.00 0.35
February 73997413.53 0.00 0.00 212869.01 0.00 0.114684E+10 0.123825E+09 0.00 0.36
March 0.101885E+09 0.00 0.00 1180170.60 0.00 0.101262E+10 0.375549E+09 0.00 0.35
April 0.125615E+09 854305.23 0.00 5297983.03 3850.95 0.465048E+09 0.759597E+09 0.00 0.36
May 0.169491E+09 1292544.00 4497.61 8516054.30 299478.36 0.147849E+09 0.959772E+09 1291.00 0.36
June 0.203913E+09 664909.83 0.00 12017119.79 82075.61 14331507.43 0.836458E+09 0.00 0.36
July 0.200171E+09 13958550.13 8335.50 11969126.34 2736936.93 1869929.85 0.644406E+09 1017.75 0.36
August 0.167982E+09 37739445.03 0.00 8873110.39 2650895.95 1569197.23 0.467106E+09 0.00 0.36
September 0.200060E+09 3577079.18 3085.28 7441917.59 1102158.45 50352936.67 0.773708E+09 1577.45 0.36
October 0.126467E+09 0.00 0.00 2431231.63 0.00 0.713693E+09 0.584889E+09 0.00 0.36
November 75121967.12 0.00 0.00 266495.12 0.00 0.121317E+10 0.130171E+09 0.00 0.35
December 57295511.87 0.00 0.00 38276.01 0.00 0.141316E+10 19943282.17 0.00 0.35
                   
Annual Sum or Average 0.155567E+10 58086833.40 15918.39 58263087.72 6875396.25 0.761642E+10 0.567946E+10 3886.20 0.36
Minimum of Months 53669069.99 0.00 0.00 18733.92 0.00 1569197.23 4039181.44 0.00 0.35
Maximum of Months 0.203913E+09 37739445.03 8335.50 12017119.79 2736936.93 0.143591E+10 0.959772E+09 1577.45 0.36



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORRIDOR_FLR_3

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.299521E+11 0.00 0.00 0.00 0.00 0.442231E+09 0.00 0.00 0.63
February 0.289117E+11 0.00 0.00 0.00 0.00 31263798.71 0.00 0.00 0.63
March 0.339035E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.63
April 0.324292E+11 0.00 0.00 0.00 5345046.71 0.00 0.00 0.00 0.63
May 0.319815E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.63
June 0.264080E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.64
July 0.222965E+11 0.00 0.00 0.00 64220831.00 0.00 0.00 0.00 0.64
August 0.198523E+11 0.00 0.00 0.00 0.216142E+09 0.00 0.00 0.00 0.64
September 0.277322E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.64
October 0.357916E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.64
November 0.321009E+11 0.00 0.00 0.00 0.00 66451785.15 0.00 0.00 0.63
December 0.304928E+11 0.00 0.00 0.00 0.00 0.702680E+09 0.00 0.00 0.63
                   
Annual Sum or Average 0.351852E+12 0.00 0.00 0.00 0.285707E+09 0.124263E+10 0.00 0.00 0.63
Minimum of Months 0.198523E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.63
Maximum of Months 0.357916E+11 0.00 0.00 0.00 0.216142E+09 0.702680E+09 0.00 0.00 0.64



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_1_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 12056630.35 0.00 0.00 24863.14 0.00 0.359833E+09 1537609.79 0.00 0.35
February 15232758.92 0.00 0.00 222985.74 0.00 0.289376E+09 31426872.35 0.00 0.36
March 19226978.74 0.00 0.00 730881.51 0.00 0.262293E+09 90602264.56 0.00 0.35
April 14787032.92 214564.18 0.00 1696734.66 0.00 0.141321E+09 0.181124E+09 0.00 0.36
May 6707205.34 399499.55 0.00 3291801.15 0.00 65689820.37 0.245756E+09 0.00 0.36
June 4432323.48 186768.24 0.00 3535079.69 0.00 15049669.67 0.243694E+09 0.00 0.36
July 704816.80 4176699.44 0.00 4005202.52 0.00 472471.92 0.209447E+09 0.00 0.35
August 1449583.24 10095475.62 2623.78 2860691.98 0.00 692409.88 0.156399E+09 669.06 0.36
September 7264195.36 1171112.30 0.00 2987055.31 0.00 28074915.00 0.219595E+09 0.00 0.36
October 14591982.81 0.00 0.00 1112663.18 0.00 0.191105E+09 0.150102E+09 0.00 0.36
November 15673781.22 0.00 0.00 164652.30 0.00 0.313235E+09 25650535.09 0.00 0.35
December 11646286.77 0.00 0.00 58448.56 0.00 0.354705E+09 6243155.62 0.00 0.35
                   
Annual Sum or Average 0.123774E+09 16244119.34 2623.78 20691059.76 0.00 0.202185E+10 0.156158E+10 669.06 0.36
Minimum of Months 704816.80 0.00 0.00 24863.14 0.00 472471.92 1537609.79 0.00 0.35
Maximum of Months 19226978.74 10095475.62 2623.78 4005202.52 0.00 0.359833E+09 0.245756E+09 669.06 0.36



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_2_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 6184098.78 0.00 0.00 2394.50 0.00 0.366913E+09 308922.05 0.00 0.35
February 14098736.38 0.00 0.00 66309.59 0.00 0.309283E+09 12771095.81 0.00 0.36
March 25361256.84 0.00 0.00 335999.44 0.00 0.295214E+09 51898859.03 0.00 0.35
April 32017831.04 213576.31 0.00 1110985.99 962.74 0.166683E+09 0.139078E+09 0.00 0.36
May 44249068.65 324583.15 0.00 2485021.31 74869.59 66073266.00 0.208600E+09 0.00 0.36
June 51045093.24 166227.46 0.00 2745123.92 20518.90 15747631.22 0.197142E+09 0.00 0.36
July 49301437.21 3525232.01 371.20 3240010.62 650223.73 427150.07 0.161635E+09 383.14 0.36
August 43460176.42 9395672.00 4026.32 1932354.81 695713.75 558016.38 0.115432E+09 2173.16 0.36
September 50941792.61 911738.89 0.00 1838941.89 259236.20 33456407.30 0.171653E+09 0.00 0.36
October 31896029.56 0.00 0.00 488951.71 0.00 0.231735E+09 92750303.21 0.00 0.36
November 16758789.99 0.00 0.00 47846.11 0.00 0.326808E+09 11068150.87 0.00 0.35
December 7997274.88 0.00 0.00 2948.27 0.00 0.364123E+09 485729.07 0.00 0.35
                   
Annual Sum or Average 0.373312E+09 14537029.81 4397.53 14296888.16 1701524.92 0.217702E+10 0.116282E+10 2556.30 0.36
Minimum of Months 6184098.78 0.00 0.00 2394.50 0.00 427150.07 308922.05 0.00 0.35
Maximum of Months 51045093.24 9395672.00 4026.32 3240010.62 695713.75 0.366913E+09 0.208600E+09 2173.16 0.36



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 93815361.42 0.00 0.00 1351301.31 0.00 0.198764E+10 0.316436E+09 0.00 0.40
February 61537797.27 0.00 0.00 4362123.11 0.00 0.126791E+10 0.826476E+09 0.00 0.41
March 57662379.15 0.00 0.00 8347436.36 0.00 0.788050E+09 0.154133E+10 0.00 0.40
April 34019696.06 1378465.32 0.00 12717150.51 0.00 0.336229E+09 0.179448E+10 0.00 0.40
May 22291445.98 2566580.60 0.00 17547701.16 0.00 97800746.44 0.192748E+10 0.00 0.40
June 25452081.02 1199890.59 0.00 19311051.36 0.00 7716356.25 0.166100E+10 0.00 0.40
July 4337333.69 26833161.04 0.00 20261650.82 0.00 3593320.02 0.135069E+10 0.00 0.40
August 8138262.67 64858275.54 17149.94 16747829.45 0.00 3259070.26 0.100878E+10 4004.88 0.40
September 40111077.65 7523798.50 0.00 19603427.52 0.00 39941547.30 0.155735E+10 0.00 0.40
October 53058018.78 0.00 0.00 12126920.48 0.00 0.379010E+09 0.184878E+10 0.00 0.40
November 81969571.04 0.00 0.00 3257188.19 0.00 0.130558E+10 0.888119E+09 0.00 0.40
December 78096544.35 0.00 0.00 2357021.90 0.00 0.183648E+10 0.477167E+09 0.00 0.40
                   
Annual Sum or Average 0.560490E+09 0.104360E+09 17149.94 0.137991E+09 0.00 0.805321E+10 0.151981E+11 4004.88 0.40
Minimum of Months 4337333.69 0.00 0.00 1351301.31 0.00 3259070.26 0.316436E+09 0.00 0.40
Maximum of Months 93815361.42 64858275.54 17149.94 20261650.82 0.00 0.198764E+10 0.192748E+10 4004.88 0.41



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BANQUET_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.328151E+10 0.00 0.00 47548009.07 0.00 0.00 0.412942E+11 0.00 4.37
February 0.196989E+10 0.00 0.00 46745410.93 0.00 0.00 0.410869E+11 0.00 4.46
March 0.134454E+10 0.00 0.00 60705090.89 0.00 0.00 0.505022E+11 0.00 4.58
April 0.603019E+09 7505081.69 0.00 70737738.21 0.00 0.00 0.511415E+11 0.00 4.74
May 0.115496E+09 0.00 0.00 89176420.31 0.00 0.00 0.534597E+11 0.00 4.93
June 18129426.03 0.00 0.00 94484161.64 0.00 0.00 0.460188E+11 0.00 5.08
July 1151911.26 99868009.36 0.00 0.104579E+09 0.00 0.00 0.400587E+11 0.00 5.18
August 8957291.87 0.322050E+09 0.00 94899341.84 235232.18 0.00 0.357586E+11 0.00 5.19
September 0.133956E+09 0.00 0.00 86513737.92 0.00 0.00 0.466697E+11 0.00 4.95
October 0.767161E+09 0.00 0.00 66386138.63 0.00 0.00 0.557966E+11 0.00 4.69
November 0.163607E+10 0.00 0.00 53169469.23 0.00 0.00 0.471244E+11 0.00 4.51
December 0.301828E+10 0.00 0.00 48895945.10 0.00 0.00 0.426731E+11 0.00 4.37
                   
Annual Sum or Average 0.128981E+11 0.429423E+09 0.00 0.863840E+09 235232.18 0.00 0.551584E+12 0.00 4.76
Minimum of Months 1151911.26 0.00 0.00 46745410.93 0.00 0.00 0.357586E+11 0.00 4.37
Maximum of Months 0.328151E+10 0.322050E+09 0.00 0.104579E+09 235232.18 0.00 0.557966E+11 0.00 5.19



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DINING_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.959513E+09 0.00 0.00 63406127.66 0.00 0.00 0.478863E+11 0.00 4.78
February 0.496122E+09 0.00 0.00 60770025.25 0.00 0.00 0.467460E+11 0.00 4.89
March 0.126282E+09 0.00 0.00 75263758.38 0.00 0.00 0.568264E+11 0.00 5.03
April 20703152.94 8381410.40 0.00 84472171.08 0.00 0.00 0.566766E+11 0.00 5.19
May 0.00 0.00 0.00 0.102094E+09 0.00 0.00 0.583317E+11 0.00 5.37
June 0.00 0.00 0.00 0.106697E+09 0.00 0.00 0.497730E+11 0.00 5.50
July 0.00 0.107679E+09 0.00 0.116293E+09 0.00 0.00 0.430523E+11 0.00 5.59
August 0.00 0.348551E+09 0.00 0.106292E+09 0.00 0.00 0.383896E+11 0.00 5.59
September 0.00 0.00 0.00 98887492.30 0.00 0.00 0.507418E+11 0.00 5.37
October 50307921.29 0.00 0.00 80317833.41 0.00 0.00 0.620069E+11 0.00 5.14
November 0.259240E+09 0.00 0.00 67818991.25 0.00 0.00 0.533331E+11 0.00 4.95
December 0.783239E+09 0.00 0.00 64450373.09 0.00 0.00 0.493622E+11 0.00 4.79
                   
Annual Sum or Average 0.269541E+10 0.464611E+09 0.00 0.102676E+10 0.00 0.00 0.613126E+12 0.00 5.18
Minimum of Months 0.00 0.00 0.00 60770025.25 0.00 0.00 0.383896E+11 0.00 4.78
Maximum of Months 0.959513E+09 0.348551E+09 0.00 0.116293E+09 0.00 0.00 0.620069E+11 0.00 5.59



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: KITCHEN_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 0.109457E+09 0.00 0.00 0.666394E+11 0.00 21.20
February 0.00 0.00 0.00 99250984.69 0.00 0.00 0.643201E+11 0.00 21.64
March 0.00 0.00 0.00 0.113192E+09 0.00 0.00 0.771594E+11 0.00 21.87
April 0.00 14704966.42 0.00 0.122741E+09 0.00 0.00 0.733371E+11 0.00 22.26
May 0.00 0.00 0.00 0.142612E+09 0.00 0.00 0.711455E+11 0.00 22.48
June 0.00 0.00 0.00 0.146852E+09 0.00 0.00 0.579744E+11 0.00 22.74
July 0.00 0.176641E+09 0.00 0.156961E+09 0.00 0.00 0.479466E+11 0.00 22.79
August 0.00 0.594586E+09 0.00 0.143310E+09 0.00 0.00 0.424723E+11 0.00 22.90
September 0.00 0.00 0.00 0.140517E+09 0.00 0.00 0.611349E+11 0.00 22.56
October 0.00 0.00 0.00 0.118543E+09 0.00 0.00 0.798501E+11 0.00 22.13
November 0.00 0.00 0.00 0.105682E+09 0.00 0.00 0.711622E+11 0.00 21.57
December 0.00 0.00 0.00 0.109120E+09 0.00 0.00 0.685733E+11 0.00 21.24
                   
Annual Sum or Average 0.00 0.785932E+09 0.00 0.150824E+10 0.00 0.00 0.781715E+12 0.00 22.12
Minimum of Months 0.00 0.00 0.00 99250984.69 0.00 0.00 0.424723E+11 0.00 21.20
Maximum of Months 0.00 0.594586E+09 0.00 0.156961E+09 0.00 0.00 0.798501E+11 0.00 22.90



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORRIDOR_FLR_6

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.150802E+11 0.00 0.00 0.00 0.00 0.124608E+09 0.00 0.00 1.19
February 0.143494E+11 0.00 0.00 0.00 0.00 0.129317E+09 0.00 0.00 1.20
March 0.169603E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.19
April 0.162227E+11 1583434.89 0.00 137.32 1090434.21 0.00 87700.98 0.00 1.20
May 0.159853E+11 0.00 0.00 24343.23 0.00 0.00 13515139.90 0.00 1.20
June 0.131390E+11 0.00 0.00 116472.86 0.00 0.00 71571229.40 0.00 1.20
July 0.107642E+11 25505185.93 0.00 654695.13 7147271.69 0.00 0.389041E+09 0.00 1.20
August 0.944094E+10 91364250.86 0.00 1059812.15 20357592.76 0.00 0.489436E+09 0.00 1.21
September 0.137171E+11 0.00 0.00 565097.34 0.00 0.00 0.155566E+09 0.00 1.20
October 0.179048E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.20
November 0.160918E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.19
December 0.154459E+11 0.00 0.00 0.00 0.00 0.159739E+09 0.00 0.00 1.19
                   
Annual Sum or Average 0.175101E+12 0.118453E+09 0.00 2420558.02 28595298.66 0.413664E+09 0.111922E+10 0.00 1.20
Minimum of Months 0.944094E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.19
Maximum of Months 0.179048E+11 91364250.86 0.00 1059812.15 20357592.76 0.159739E+09 0.489436E+09 0.00 1.21



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2024-07-03 12:21:35

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.604553E+11 0.772854E+10 0.235430E+12 0.935829E+12 0.637284E+11
February 0.132335E+12 0.647635E+10 0.196149E+12 0.791883E+12 0.768838E+11
March 0.251618E+12 0.624868E+10 0.185092E+12 0.767380E+12 0.110401E+12
April 0.405045E+12 0.515783E+10 0.149777E+12 0.629969E+12 0.165672E+12
May 0.531481E+12 0.459325E+10 0.130677E+12 0.552870E+12 0.220408E+12
June 0.547216E+12 0.367741E+10 0.101461E+12 0.425358E+12 0.275958E+12
July 0.569419E+12 0.298194E+10 0.821845E+11 0.351256E+12 0.389411E+12
August 0.448963E+12 0.255185E+10 0.706203E+11 0.301879E+12 0.457216E+12
September 0.285569E+12 0.364896E+10 0.107394E+12 0.440631E+12 0.256092E+12
October 0.190393E+12 0.497931E+10 0.150228E+12 0.612924E+12 0.157792E+12
November 0.708633E+11 0.600515E+10 0.187910E+12 0.743304E+12 0.922716E+11
December 0.388054E+11 0.735080E+10 0.224337E+12 0.897030E+12 0.714876E+11
           
Annual Sum or Average 0.353216E+13 0.614001E+11 0.182126E+13 0.745031E+13 0.233732E+13
Minimum of Months 0.388054E+11 0.255185E+10 0.706203E+11 0.301879E+12 0.637284E+11
Maximum of Months 0.569419E+12 0.772854E+10 0.235430E+12 0.935829E+12 0.457216E+12