Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000
Simulation Timestamp: 2024-07-03 12:21:10
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:10
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 12471.35 | 1099.25 | 1099.25 |
Net Site Energy | 12471.35 | 1099.25 | 1099.25 |
Total Source Energy | 31725.13 | 2796.33 | 2796.33 |
Net Source Energy | 31725.13 | 2796.33 | 2796.33 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 16.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 4172.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 782.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 194.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1658.18 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 813.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 498.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 144.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 302.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 94.79 | 1942.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | 62.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 8740.36 | 3730.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 16.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 4172.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 782.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 194.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 872.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 14.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 8.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 21.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 789.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 2.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 498.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 144.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 302.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 94.79 | 1942.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5742.51 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.69 | |
Refrigeration | General | 7.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 20.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 34.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 16.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 4172.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 782.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 194.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 1658.18 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 813.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 498.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 144.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 302.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 94.79 | 1942.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | Unassigned | 62.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 86.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 434.23 | 171.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 250.06 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 770.40 | 328.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 86.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 434.23 | 171.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 250.06 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 770.40 | 328.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 8740.364 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 8740.364 | 100.00 |
Total On-Site and Utility Electric Sources | 8740.364 | 100.00 |
Total Electricity End Uses | 8740.364 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 6937.84 | 100.00 |
Air to Air Heat Recovery for Heating | 0.01 | 0.00 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 6937.85 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9857.19 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9857.19 | 100.00 |
Total Water End Uses | 9857.19 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 60.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 6696.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0A
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY VNM_HOCHIMINH_TANSONHOA
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER1 |DXReportMonthly
| FLR_3_DOAS COOLING COIL | VAV WITH REHEAT COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH LAUNDRY G WATER HEATER | SWH BOOSTER E WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |CoilReportMonthly
| FLR_3_DOAS HEATING COIL | VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | FLR_3_DOAS COOLING COIL | VAV WITH REHEAT COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |PlantLoopDemandReportMonthly
| COOLSYS1 | SWHSYS1 |FanReportMonthly
| FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL_FANCOILFAN | ROOM_2_FLR_3 FAN COIL_FANCOILFAN | ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | ROOM_5_FLR_3 FAN COIL_FANCOILFAN | ROOM_6_FLR_3 FAN COIL_FANCOILFAN | ROOM_1_FLR_6 FAN COIL_FANCOILFAN | ROOM_2_FLR_6 FAN COIL_FANCOILFAN | ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN |PumpReportMonthly
| COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| COOLSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| FLR_3_DOAS | VAV WITH REHEAT |AirLoopSystemComponentLoadsMonthly
| FLR_3_DOAS | VAV WITH REHEAT |AirLoopSystemComponentEnergyUseMonthly
| FLR_3_DOAS | VAV WITH REHEAT |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:10
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21 |
RunPeriod | RUNPERIOD 1 |
Weather File | Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000 |
Latitude [deg] | 10.82 |
Longitude [deg] | 106.67 |
Elevation [m] | 5.00 |
Time Zone | 7.00 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 8.8143 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.26 | 23.26 | 11.3140 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 11.3140 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 4.6285 | 61.93 | 5.3800 |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 5.7199 | 46.45 | 2.6900 |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 4.6285 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.50 | 65.50 | 10.0104 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.08 | 85.08 | 10.7639 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 8.2882 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 8.2882 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 7.1042 | 18.58 | 0.0000 |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.74 | 6.74 | 8.2882 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 10.0104 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 10.0104 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.37 | 26.37 | 11.4097 | 4.65 | 2934.4875 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.20 | 28.20 | 7.1042 | 18.58 | 0.0000 |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 8.5566 | 7.07 | 41.0709 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 8.5566 | 7.07 | 41.0709 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 1978.83 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 8.8143 | 18.58 | 5.3800 | |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 1.00 | RETAIL_1_FLR_1 | GENERAL | RETAIL_1_FLR_1 | 11.3140 | 6.19 | 10.7600 | |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 1.00 | RETAIL_2_FLR_1 | GENERAL | RETAIL_2_FLR_1 | 11.3140 | 6.19 | 10.7600 | |
MECH_FLR_1 | 164.24 | Yes | Yes | 1.00 | MECH_FLR_1 | GENERAL | MECH_FLR_1 | 4.6285 | 61.93 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 1.00 | STORAGE_FLR_1 | GENERAL | STORAGE_FLR_1 | 5.7199 | 46.45 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 1.00 | LAUNDRY_FLR_1 | GENERAL | LAUNDRY_FLR_1 | 4.6285 | 9.29 | 597.5300 | |
CAFE_FLR_1 | 188.86 | Yes | Yes | 1.00 | CAFE_FLR_1 | GENERAL | CAFE_FLR_1 | 10.0104 | 1.33 | 5.3800 | |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 1.00 | LOBBY_FLR_1 | GENERAL | LOBBY_FLR_1 | 10.7639 | 3.10 | 8.0700 | |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_1_FLR_3 | GENERAL | ROOM_1_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_2_FLR_3 | GENERAL | ROOM_2_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 76.00 | ROOM_3_MULT19_FLR_3 | GENERAL | ROOM_3_MULT19_FLR_3 | 8.2882 | 16.35 | 10.5200 | |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 76.00 | ROOM_4_MULT19_FLR_3 | GENERAL | ROOM_4_MULT19_FLR_3 | 8.2882 | 16.35 | 10.5200 | |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_5_FLR_3 | GENERAL | ROOM_5_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_6_FLR_3 | GENERAL | ROOM_6_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 4.00 | CORRIDOR_FLR_3 | GENERAL | CORRIDOR_FLR_3 | 7.1042 | 18.58 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_1_FLR_6 | GENERAL | ROOM_1_FLR_6 | 8.2882 | 26.01 | 6.7500 | |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_2_FLR_6 | GENERAL | ROOM_2_FLR_6 | 8.2882 | 26.01 | 6.7500 | |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 9.00 | ROOM_3_MULT9_FLR_6 | GENERAL | ROOM_3_MULT9_FLR_6 | 8.2882 | 16.35 | 10.5200 | |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1.00 | BANQUET_FLR_6 | GENERAL | BANQUET_FLR_6 | 10.0104 | 1.33 | 67.8200 | |
DINING_FLR_6 | 331.66 | Yes | Yes | 1.00 | DINING_FLR_6 | GENERAL | DINING_FLR_6 | 10.0104 | 1.33 | 67.8200 | |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 1.00 | KITCHEN_FLR_6 | GENERAL | KITCHEN_FLR_6 | 11.4097 | 4.65 | 2934.4875 | |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1.00 | CORRIDOR_FLR_6 | GENERAL | CORRIDOR_FLR_6 | 7.1042 | 18.58 | 0.0000 | |
Total | 11345.29 | 8.5566 | 3.54 | 41.0709 | |||||||
Conditioned Total | 11345.29 | 8.5566 | 3.54 | 41.0709 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 11345.29 | 11345.29 | 0.00 | 0.00 | 4.6520 | 8.82 | 37.1989 |
Total | 11345.29 | 11345.29 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:10
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 13-JUN-18:19 | 11-JAN-18:00 | - | - | - | - | - | - | - | - | - | - | 17-JUL-20:00 |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 228669.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 57474.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 12338.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 77573.37 | 104248.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 28169.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 28792.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 5604.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 4751.04 | 177174.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1849.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 455161.34 | 281422.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 228669.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 57474.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 12338.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 47590.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 29272.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1050.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 26968.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 150.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 28792.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 5604.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 4751.04 | 177174.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 228.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 531.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1088.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:10
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 53.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 13214.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2478.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 614.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5251.45 | 1939.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2577.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1578.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 456.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 958.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 300.20 | 2105.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 197.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 27680.73 | 4044.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 4.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1164.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 218.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 54.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 462.88 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 227.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 139.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 40.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 84.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 26.46 | 185.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2439.84 | 356.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 4.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1164.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 218.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 54.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 462.88 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 227.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 139.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 40.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 84.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 26.46 | 185.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2439.84 | 356.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:10
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
BASEMENT VAV BOX COMPONENT | 2.96 | 0.510026 | 0.526000 | 1.56 | 1.00 | 0.500000 | 0.000747 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.303084 | 0.168628 | 0.526000 | 0.159422 | 0.526000 | 0.500000 | 0.002259 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.275390 | 0.214908 | 0.526000 | 0.144855 | 0.573089 | 0.500000 | 0.001773 |
MECH_FLR_1 VAV BOX COMPONENT | 0.281410 | 0.444736 | 0.526000 | 0.148022 | 1.00 | 0.500000 | 0.000857 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.155097 | 0.465557 | 0.526000 | 0.081581 | 1.00 | 0.500000 | 0.000818 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 3.19 | 0.018640 | 0.526000 | 1.68 | 0.526000 | 0.500000 | 0.020440 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.27 | 0.112878 | 0.526000 | 0.670621 | 0.526000 | 0.500000 | 0.003375 |
LOBBY_FLR_1 VAV BOX COMPONENT | 4.72 | 0.211091 | 0.526000 | 2.48 | 0.562908 | 0.500000 | 0.001805 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.53 | 0.777570 | 0.526000 | 0.802901 | 1.00 | 0.500000 | 0.000490 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.20 | 0.114716 | 0.526000 | 1.16 | 0.526000 | 0.500000 | 0.003321 |
DINING_FLR_6 VAV BOX COMPONENT | 2.30 | 0.109655 | 0.526000 | 1.21 | 0.526000 | 0.500000 | 0.003475 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.20 | 0.064399 | 0.526000 | 1.16 | 0.526000 | 0.500000 | 0.010641 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 0.760389 | 0.412998 | 0.526000 | 0.399965 | 1.00 | 0.500000 | 0.000923 |
Design Size Nominal Capacity [W] | |
BASEMENT VAV BOX REHEAT COIL | 44470.36 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 4558.92 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 4142.36 |
MECH_FLR_1 VAV BOX REHEAT COIL | 4232.91 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 2332.94 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 47986.26 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 19177.44 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 71032.17 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | 1431.14 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | 1430.97 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 19405.32 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 19410.63 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | 1431.14 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | 1430.97 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 22960.21 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | 357.78 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | 357.74 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 2298.59 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 33137.55 |
DINING_FLR_6 VAV BOX REHEAT COIL | 34666.95 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 33070.24 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 11437.61 |
FLR_3_DOAS HEATING COIL | 12429.56 |
VAV WITH REHEAT HEATING COIL | 133202.63 |
Design Size Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 0.061735 |
ROOM_2_FLR_3 DIRECT AIR | 0.061728 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 0.837072 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 0.837300 |
ROOM_5_FLR_3 DIRECT AIR | 0.061735 |
ROOM_6_FLR_3 DIRECT AIR | 0.061728 |
ROOM_1_FLR_6 DIRECT AIR | 0.015434 |
ROOM_2_FLR_6 DIRECT AIR | 0.015432 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 0.099154 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 0.928596 | 0.000303 |
ROOM_2_FLR_3 FAN COIL | 0.940354 | 0.000307 |
ROOM_3_MULT19_FLR_3 FAN COIL | 5.27 | 0.001681 |
ROOM_4_MULT19_FLR_3 FAN COIL | 6.34 | 0.002139 |
ROOM_5_FLR_3 FAN COIL | 0.824449 | 0.000271 |
ROOM_6_FLR_3 FAN COIL | 0.832194 | 0.000273 |
ROOM_1_FLR_6 FAN COIL | 0.254423 | 0.000083 |
ROOM_2_FLR_6 FAN COIL | 0.257392 | 0.000084 |
ROOM_3_MULT9_FLR_6 FAN COIL | 1.03 | 0.000344 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COIL_FANCOILFAN | 0.928596 |
ROOM_2_FLR_3 FAN COIL_FANCOILFAN | 0.940354 |
ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | 5.27 |
ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | 6.34 |
ROOM_5_FLR_3 FAN COIL_FANCOILFAN | 0.824449 |
ROOM_6_FLR_3 FAN COIL_FANCOILFAN | 0.832194 |
ROOM_1_FLR_6 FAN COIL_FANCOILFAN | 0.254423 |
ROOM_2_FLR_6 FAN COIL_FANCOILFAN | 0.257392 |
ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN | 1.03 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Coil Load [W] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | 21.68 | 6.70 | 0.008666 | 12.80 | 0.008500 | 0.000303 | 0.928596 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | 21.68 | 6.70 | 0.008664 | 12.80 | 0.008500 | 0.000307 | 0.940354 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 21.68 | 6.70 | 0.008582 | 12.80 | 0.008500 | 0.001681 | 5.27 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 21.68 | 6.70 | 0.008789 | 12.80 | 0.008500 | 0.002139 | 6.34 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | 21.68 | 6.70 | 0.008688 | 12.80 | 0.008500 | 0.000271 | 0.824449 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | 21.68 | 6.70 | 0.008686 | 12.80 | 0.008500 | 0.000273 | 0.832194 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | 21.68 | 6.70 | 0.008652 | 12.80 | 0.008500 | 0.000083 | 0.254423 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | 21.68 | 6.70 | 0.008650 | 12.80 | 0.008500 | 0.000084 | 0.257392 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 21.68 | 6.70 | 0.008751 | 12.80 | 0.008500 | 0.000344 | 1.03 | |
FLR_3_DOAS COOLING COIL | 35.20 | 6.70 | 0.017158 | 11.94 | 0.008500 | 0.003245 | 2.05 | 113467.39 |
VAV WITH REHEAT COOLING COIL | 29.95 | 6.70 | 0.013647 | 11.09 | 0.008500 | 0.024520 | 21.98 | 857363.51 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
VAV WITH REHEAT | 11.65 | 11.65 | 22.15 | 11.65 | 21.98 | 21.98 | 0.300000 | 0.530041 | 21.98 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
VAV WITH REHEAT_OA_CONTROLLER | 21.98 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
FLR_3_DOAS OA HEAT RECOVERY | 2.05 |
VAV WITH REHEAT OA HEAT RECOVERY | 11.66 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS FAN | 2.05 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.003245 | 0.000147 |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.024520 | 0.000019 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT FAN | 21.98 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP SECONDARY | 0.033250 | 5428.79 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1 | 0.033250 | 3.99 |
SWHSYS1 | 0.000375 | 0.045004 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.033250 | 3758.53 |
SWHSYS1 PUMP | 0.000375 | 47.91 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.033250 | 1162609.74 | 1165839.98 | 132.91 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000375 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:10
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:10
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:10
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 26.90 | 26.70 | 26.00 | 26.40 | 27.50 | 28.30 | 29.20 | 29.00 | 28.90 | 27.20 | 27.50 | 27.60 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000 | 10.82 | 106.67 | 7.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 27.60 | 3.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.58 | 23.26 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.72 | 65.50 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.80 | 85.08 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.70 | 6.74 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.96 | 26.37 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.27 | 28.20 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 8.814 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 14.194 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 11.314 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 22.074 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 11.314 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 22.074 | No |
4 | MECH_FLR_1 | 164.24 | 2.7 | 61.932 | 1.615E-002 | 4.628 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 10.008 | No |
5 | STORAGE_FLR_1 | 94.76 | 2.0 | 46.451 | 2.153E-002 | 5.720 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 8.410 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 4.628 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 602.158 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 10.010 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 15.390 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 10.764 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.834 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 8.288 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 18.808 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 8.288 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 18.808 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 21.0 | 18.581 | 5.382E-002 | 7.104 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.104 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 8.288 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 18.808 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 10.010 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 77.830 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 10.010 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 77.830 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 11.410 | 515.227 | 2419.260 | 0.000 | 0.000 | 0.000 | 2945.897 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 22.2 | 18.581 | 5.382E-002 | 7.104 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.104 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | STORAGE_FLR_1 PEOPLE | BLDG_OCC_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.0 | 2.153E-002 | 46.451 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | CORRIDOR_FLR_3 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 21.0 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 21 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
21 | CORRIDOR_FLR_6 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 22.2 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
22 | MECH_FLR_1 PEOPLE | BLDG_OCC_SCH | MECH_FLR_1 | 164.24 | 2.7 | 2.7 | 1.615E-002 | 61.932 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 3 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_BASEMENT | BASEMENT | 1978.83 | 106.5 | 17441.963 | 8.814 | 163.776 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 17441.963 |
2 | RETAIL_1_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_1_FLR_1 | 67.07 | 10.8 | 758.849 | 11.314 | 70.076 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 758.849 |
3 | RETAIL_2_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_2_FLR_1 | 77.67 | 12.5 | 878.750 | 11.314 | 70.076 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 878.750 |
4 | MECH_FLR_1_LIGHTS | LTG_SCH_MECHANIC | MECH_FLR_1 | 164.24 | 2.7 | 760.196 | 4.628 | 286.650 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 760.196 |
5 | STORAGE_FLR_1_LIGHTS | LTG_SCH_STORAGE | STORAGE_FLR_1 | 94.76 | 2.0 | 542.017 | 5.720 | 265.695 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 542.017 |
6 | LAUNDRY_FLR_1_LIGHTS | LTG_SCH_LAUNDRY | LAUNDRY_FLR_1 | 78.04 | 8.4 | 361.204 | 4.628 | 43.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 361.204 |
7 | CAFE_FLR_1_LIGHTS | LTG_SCH_DINING | CAFE_FLR_1 | 188.86 | 142.3 | 1890.589 | 10.010 | 13.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1890.589 |
8 | LOBBY_FLR_1_LIGHTS | LTG_SCH_LOBBY | LOBBY_FLR_1 | 1308.19 | 422.4 | 14081.185 | 10.764 | 33.333 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14081.185 |
9 | ROOM_1_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_3 | 39.02 | 1.5 | 323.422 | 8.288 | 215.615 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.422 |
10 | ROOM_2_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_3 | 39.02 | 1.5 | 323.384 | 8.288 | 215.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.384 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 203.259 | 8.288 | 135.506 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 203.259 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 203.314 | 8.288 | 135.543 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 203.314 |
13 | ROOM_5_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_5_FLR_3 | 39.02 | 1.5 | 323.422 | 8.288 | 215.615 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.422 |
14 | ROOM_6_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_6_FLR_3 | 39.02 | 1.5 | 323.384 | 8.288 | 215.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.384 |
15 | CORRIDOR_FLR_3_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2766.397 | 7.104 | 132.003 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2766.397 |
16 | ROOM_1_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_6 | 39.02 | 1.5 | 323.422 | 8.288 | 215.615 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.422 |
17 | ROOM_2_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_6 | 39.02 | 1.5 | 323.384 | 8.288 | 215.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.384 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 203.314 | 8.288 | 135.543 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 203.314 |
19 | BANQUET_FLR_6_LIGHTS | LTG_SCH_DINING | BANQUET_FLR_6 | 331.66 | 249.9 | 3320.034 | 10.010 | 13.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3320.034 |
20 | DINING_FLR_6_LIGHTS | LTG_SCH_DINING | DINING_FLR_6 | 331.66 | 249.9 | 3320.034 | 10.010 | 13.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3320.034 |
21 | KITCHEN_FLR_6_LIGHTS | LTG_SCH_KITCHEN | KITCHEN_FLR_6 | 103.30 | 22.2 | 1178.676 | 11.410 | 53.003 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1178.676 |
22 | CORRIDOR_FLR_6_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_6 | 412.12 | 22.2 | 2927.804 | 7.104 | 132.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2927.804 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 2.7 | 883.628 | 5.380 | 333.193 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 254.902 | 2.690 | 124.952 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 457.500 | 4.429 | 20.573 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 457.500 | 457.500 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 285.000 | 2.759 | 12.816 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 285.000 | 285.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 2.390 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
6 | RES_ROOF | 19 | 3 | 3 | 0.167 | 0.1864 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
7 | NONRES_EXT_WALL_GRD | 21 | 3 | 9 | 0.167 | 5.069 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | NONRES_EXT_WALL_MID | 22 | 3 | 9 | 0.167 | 5.069 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | NONRES_EXT_WALL_TOP | 23 | 3 | 9 | 0.167 | 5.069 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | RES_EXT_WALL_MID | 25 | 3 | 9 | 0.167 | 1.393 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | RES_EXT_WALL_TOP | 26 | 3 | 9 | 0.167 | 1.408 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | NONRES_FLOOR | 30 | 3 | 7 | 0.167 | 3.444 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
13 | NONRES_FLOOR_CEILING | 33 | 3 | 7 | 0.167 | 3.444 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
14 | BASEMENT_FLOOR | 36 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
15 | BASEMENT_WALL_NORTH_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | BASEMENT_WALL_EAST_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | BASEMENT_WALL_SOUTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
18 | BASEMENT_WALL_WEST_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4184 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
10 | RES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
11 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
12 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2994E-01 |
14 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2994E-01 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2994E-01 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | RES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5506 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
25 | RES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5431 |
26 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
27 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2994E-01 |
28 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
29 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
30 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
31 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
32 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2994E-01 |
33 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
34 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
35 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
39 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
40 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
41 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
42 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 2.3900722 | 2.3900722 | 2.3900722 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
21 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
22 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
23 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
24 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
25 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
26 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
27 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
28 | 9 | -0.34109306E-14 | 0.24909287E-15 | -0.70234472E-12 | 0.65513238E-16 |
29 | 8 | 0.13119258E-09 | 0.66225198E-13 | 0.25869970E-04 | -0.14916918E-11 |
30 | 7 | -0.11009939E-02 | 0.13568249E-07 | -0.65256785E-02 | 0.12518681E-04 |
31 | 6 | 0.10140049 | 0.81303169E-05 | 0.18905580 | -0.11654411E-02 |
32 | 5 | -2.2086417 | 0.46066432E-03 | -2.1793248 | 0.26223950E-01 |
33 | 4 | 19.715055 | 0.51780401E-02 | 12.415669 | -0.24584718 |
34 | 3 | -82.671456 | 0.14472115E-01 | -37.782151 | 1.1032137 |
35 | 2 | 168.49726 | 0.99923307E-02 | 62.094262 | -2.4465849 |
36 | 1 | -160.45852 | 0.12849016E-02 | -51.628788 | 2.5579517 |
37 | 0 | 57.057407 | 0.91053392E-05 | 16.929182 | |
38 | 9 | -0.34109306E-14 | 0.24909287E-15 | -0.70234472E-12 | 0.65513238E-16 |
39 | 8 | 0.13119258E-09 | 0.66225198E-13 | 0.25869970E-04 | -0.14916918E-11 |
40 | 7 | -0.11009939E-02 | 0.13568249E-07 | -0.65256785E-02 | 0.12518681E-04 |
41 | 6 | 0.10140049 | 0.81303169E-05 | 0.18905580 | -0.11654411E-02 |
42 | 5 | -2.2086417 | 0.46066432E-03 | -2.1793248 | 0.26223950E-01 |
43 | 4 | 19.715055 | 0.51780401E-02 | 12.415669 | -0.24584718 |
44 | 3 | -82.671456 | 0.14472115E-01 | -37.782151 | 1.1032137 |
45 | 2 | 168.49726 | 0.99923307E-02 | 62.094262 | -2.4465849 |
46 | 1 | -160.45852 | 0.12849016E-02 | -51.628788 | 2.5579517 |
47 | 0 | 57.057407 | 0.91053392E-05 | 16.929182 | |
48 | 9 | -0.34109306E-14 | 0.24909287E-15 | -0.70234472E-12 | 0.65513238E-16 |
49 | 8 | 0.13119258E-09 | 0.66225198E-13 | 0.25869970E-04 | -0.14916918E-11 |
50 | 7 | -0.11009939E-02 | 0.13568249E-07 | -0.65256785E-02 | 0.12518681E-04 |
51 | 6 | 0.10140049 | 0.81303169E-05 | 0.18905580 | -0.11654411E-02 |
52 | 5 | -2.2086417 | 0.46066432E-03 | -2.1793248 | 0.26223950E-01 |
53 | 4 | 19.715055 | 0.51780401E-02 | 12.415669 | -0.24584718 |
54 | 3 | -82.671456 | 0.14472115E-01 | -37.782151 | 1.1032137 |
55 | 2 | 168.49726 | 0.99923307E-02 | 62.094262 | -2.4465849 |
56 | 1 | -160.45852 | 0.12849016E-02 | -51.628788 | 2.5579517 |
57 | 0 | 57.057407 | 0.91053392E-05 | 16.929182 | |
58 | 9 | 0.75525440E-15 | 0.44740194E-16 | -0.12773695E-09 | -0.17413973E-17 |
59 | 8 | 0.18775242E-07 | 0.18212309E-12 | 0.34440251E-03 | -0.21348098E-09 |
60 | 7 | -0.11242372E-01 | 0.98045077E-08 | -0.21646224E-01 | 0.12782986E-03 |
61 | 6 | 0.37819669 | 0.34662877E-05 | 0.44889448 | -0.44276875E-02 |
62 | 5 | -4.9255264 | 0.13123097E-03 | -4.2627871 | 0.59897552E-01 |
63 | 4 | 31.830222 | 0.10869568E-02 | 20.742026 | -0.40655401 |
64 | 3 | -108.73045 | 0.23952585E-02 | -54.243141 | 1.4791387 |
65 | 2 | 194.65663 | 0.13606195E-02 | 76.609648 | -2.8614229 |
66 | 1 | -170.25011 | 0.14657319E-03 | -54.889188 | 2.7295613 |
67 | 0 | 57.057407 | 0.84265852E-06 | 15.620975 | |
68 | 9 | 0.85297796E-15 | 0.46957990E-16 | -0.12703153E-09 | -0.54240268E-18 |
69 | 8 | 0.18675511E-07 | 0.18384479E-12 | 0.34329809E-03 | -0.21234699E-09 |
70 | 7 | -0.11209220E-01 | 0.99091673E-08 | -0.21598424E-01 | 0.12745291E-03 |
71 | 6 | 0.37729561 | 0.35050755E-05 | 0.44812211 | -0.44170661E-02 |
72 | 5 | -4.9167295 | 0.13275736E-03 | -4.2568331 | 0.59788477E-01 |
73 | 4 | 31.791289 | 0.11000280E-02 | 20.718704 | -0.40603713 |
74 | 3 | -108.64755 | 0.24248953E-02 | -54.197012 | 1.4779412 |
75 | 2 | 194.57440 | 0.13778728E-02 | 76.567430 | -2.8601173 |
76 | 1 | -170.21971 | 0.14847322E-03 | -54.877080 | 2.7290284 |
77 | 0 | 57.057407 | 0.85387380E-06 | 15.623112 | |
78 | 7 | -0.54138470E-12 | 0.12463713E-14 | -0.64276224E-14 | 0.11113167E-15 |
79 | 6 | 0.12246794E-07 | 0.15689727E-09 | 0.20336639E-09 | -0.66085082E-11 |
80 | 5 | -0.43638646E-04 | 0.91064443E-06 | -0.10338442E-05 | 0.73798452E-07 |
81 | 4 | 0.19644206E-01 | 0.40532412E-03 | 0.96204216E-03 | -0.14823791E-03 |
82 | 3 | -1.4347347 | 0.16410182E-01 | -0.13915079 | 0.27725787E-01 |
83 | 2 | 17.082538 | 0.80550987E-01 | 2.2432332 | -0.47694951 |
84 | 1 | -41.597683 | 0.53207822E-01 | -6.4041654 | 1.4049886 |
85 | 0 | 26.083068 | 0.22662127E-02 | 4.4519555 | |
86 | 7 | -0.64276224E-14 | 0.12463713E-14 | -0.54138470E-12 | 0.11113167E-15 |
87 | 6 | 0.20336639E-09 | 0.15689727E-09 | 0.12246794E-07 | -0.66085082E-11 |
88 | 5 | -0.10338442E-05 | 0.91064443E-06 | -0.43638646E-04 | 0.73798452E-07 |
89 | 4 | 0.96204216E-03 | 0.40532412E-03 | 0.19644206E-01 | -0.14823791E-03 |
90 | 3 | -0.13915079 | 0.16410182E-01 | -1.4347347 | 0.27725787E-01 |
91 | 2 | 2.2432332 | 0.80550987E-01 | 17.082538 | -0.47694951 |
92 | 1 | -6.4041654 | 0.53207822E-01 | -41.597683 | 1.4049886 |
93 | 0 | 4.4519555 | 0.22662127E-02 | 26.083068 | |
94 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
95 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
96 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
97 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
98 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
99 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
100 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
101 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
102 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
103 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
104 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
105 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
106 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
107 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
108 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
109 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
110 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
111 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
112 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
113 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
114 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
115 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
116 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
117 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
118 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
119 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
120 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
121 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
122 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
123 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
124 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
125 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
126 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
127 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
128 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
129 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
130 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
131 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
132 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
133 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.496_SHGC_0.22 | 37 | 1 | VerySmooth | 2.820 | 2.820 | 1.000 | 0.221 | ||
2 | RESWINDOW_U_0.496_SHGC_0.22 | 38 | 1 | VerySmooth | 2.820 | 2.820 | 1.000 | 0.221 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 2.03937E-002 | 0.13126 | 0.64145 | 0.64145 | 0.24200 | 0.16318 | 0.24318 | 0.00000 | 0.84000 | 0.84000 | 0.11067 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 2.03937E-002 | 0.13126 | 0.64145 | 0.64145 | 0.24200 | 0.16318 | 0.24318 | 0.00000 | 0.84000 | 0.84000 | 0.11067 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | CAFE_FLR_1 | 1 | 0 |
2 | LOBBY_FLR_1 | 1 | 0 |
3 | BANQUET_FLR_6 | 1 | 0 |
4 | DINING_FLR_6 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | CAFE_FLR_1 | 0 | |
2 | LOBBY_FLR_1 | 0 | |
3 | BANQUET_FLR_6 | 0 | |
4 | DINING_FLR_6 | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH LAUNDRY G WATER HEATER | 1.1356 | 163316.0 | 11.511 | 0.4388 |
2 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.219 | 1.1187 |
3 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 2.2712 | 175842.6 | 5.775 | 0.3748 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 1.764E-002 | 2.631E-004 | 1.298E-004 | 0.239 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.811E-003 | 8.769E-005 | 2.388E-004 | 7.967E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 2.7 | 1.610E-002 | 9.800E-005 | 2.563E-004 | 8.904E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 9.287E-003 | 9.800E-005 | 2.127E-004 | 8.904E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 2.198E-002 | 2.816E-004 | 2.506E-004 | 0.256 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 3.900E-002 | 2.065E-004 | 1.137E-004 | 0.188 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 0.111 | 8.519E-005 | 1.629E-004 | 7.740E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 2.563E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 2.563E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 2.857E-003 | 1.165E-004 | 2.563E-004 | 0.138 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 2.858E-003 | 1.165E-004 | 2.563E-004 | 0.138 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 2.563E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 2.563E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 1.238E-002 | 3.180E-005 | 2.563E-004 | 3.755E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 1.297E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 1.297E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 5.239E-003 | 2.136E-004 | 1.165E-004 | 0.252 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 2.500E-002 | 7.539E-005 | 5.825E-005 | 8.904E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 2.500E-002 | 7.539E-005 | 5.825E-005 | 8.904E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 2.238E-002 | 2.167E-004 | 1.174E-004 | 0.256 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 2.191E-002 | 5.316E-005 | 4.403E-005 | 6.278E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 5.2957E-002 |
2 | Clear Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 2.0672E-002 |
3 | Clear Turbid Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 5.4172E-002 |
4 | Clear Turbid Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 2.0001E-002 |
5 | Intermediate Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 4.5901E-002 |
6 | Intermediate Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 1.5388E-002 |
7 | Overcast Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 2.5663E-002 |
8 | Overcast Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 8.5002E-003 |
9 | Clear Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 5.9149E-002 |
10 | Clear Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 2.6492E-002 |
11 | Clear Turbid Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 6.0526E-002 |
12 | Clear Turbid Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 2.5894E-002 |
13 | Intermediate Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 5.1055E-002 |
14 | Intermediate Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 2.0344E-002 |
15 | Overcast Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 2.8836E-002 |
16 | Overcast Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 1.1652E-002 |
17 | Clear Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 1.8428E-002 |
18 | Clear Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 9.9890E-003 |
19 | Clear Turbid Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 1.4624E-002 |
20 | Clear Turbid Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 7.7537E-003 |
21 | Intermediate Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 1.2609E-002 |
22 | Intermediate Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 4.9811E-003 |
23 | Overcast Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.5273E-002 |
24 | Overcast Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 8.9357E-003 |
25 | Clear Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 1.8428E-002 |
26 | Clear Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 9.9890E-003 |
27 | Clear Turbid Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 1.4624E-002 |
28 | Clear Turbid Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 7.7537E-003 |
29 | Intermediate Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 1.2609E-002 |
30 | Intermediate Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 4.9811E-003 |
31 | Overcast Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.5273E-002 |
32 | Overcast Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 8.9357E-003 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 40671.23725 | 40671.23725 | 2.95645 | 2.95645 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 22:00:00 | 29.42000 | 1.71471E-002 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 0.85446 | 00:10:00 | 20.10000 | 1.47983E-002 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 | |
3 | RETAIL_1_FLR_1 | Cooling | 4168.86229 | 4168.86229 | 0.30308 | 0.30308 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:40:00 | 34.23667 | 1.71563E-002 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 319.43591 | 319.43591 | 1.36990E-002 | 7.92179E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 20.10000 | 1.47983E-002 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 3788.00408 | 3788.00408 | 0.27539 | 0.27539 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 19:20:00 | 31.57333 | 1.71512E-002 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 81.83164 | 81.83164 | 3.50926E-003 | 9.17347E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 20.10000 | 1.47983E-002 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 3871.61120 | 3871.61120 | 0.28141 | 0.28141 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 19:10:00 | 31.72917 | 1.71515E-002 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 154.80401 | 154.80401 | 6.63860E-003 | 6.63860E-003 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 20.10000 | 1.47983E-002 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 2133.79621 | 2133.79621 | 0.15510 | 0.15510 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 17:30:00 | 33.58500 | 1.71551E-002 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 80.69844 | 80.69844 | 3.46066E-003 | 5.77652E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 20.10000 | 1.47983E-002 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 43885.45310 | 43885.45310 | 3.19020 | 3.19020 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:30:00 | 34.35000 | 1.71565E-002 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 341.11489 | 341.11489 | 1.46287E-002 | 1.46287E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 20.10000 | 1.47983E-002 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 17522.01726 | 17522.01726 | 1.27494 | 1.27494 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:40:00 | 35.20000 | 1.71581E-002 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 728.76898 | 728.76898 | 3.12530E-002 | 0.67639 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 20.10000 | 1.47983E-002 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 64937.73141 | 64937.73141 | 4.72232 | 4.72232 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 17:00:00 | 34.01000 | 1.71559E-002 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 1226.79357 | 1226.79357 | 5.26096E-002 | 1.89399 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 20.10000 | 1.47983E-002 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 9479.64362 | 9479.64362 | 0.92860 | 0.92860 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:20:00 | 34.46333 | 1.71567E-002 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 631.12726 | 631.12726 | 2.72250E-002 | 6.17350E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 20.10000 | 1.47983E-002 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 9599.66874 | 9599.66874 | 0.94035 | 0.94035 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:20:00 | 34.46333 | 1.71567E-002 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 636.79152 | 636.79152 | 2.74693E-002 | 6.17278E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 20.10000 | 1.47983E-002 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 53763.65555 | 53763.65555 | 5.26614 | 5.26614 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:20:00 | 35.03000 | 1.71578E-002 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 3708.74839 | 3708.74839 | 0.15998 | 0.83707 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 20.10000 | 1.47983E-002 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 64735.44916 | 64735.44916 | 6.34131 | 6.34131 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:00:00 | 34.69000 | 1.71572E-002 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 3820.38758 | 3820.38758 | 0.16480 | 0.83730 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 20.10000 | 1.47983E-002 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 8416.43375 | 8416.43375 | 0.82445 | 0.82445 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:50:00 | 31.72917 | 1.71515E-002 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 631.12726 | 631.12726 | 2.72250E-002 | 6.17350E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 20.10000 | 1.47983E-002 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 8495.49132 | 8495.49132 | 0.83219 | 0.83219 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:40:00 | 31.48833 | 1.71511E-002 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 636.79152 | 636.79152 | 2.74693E-002 | 6.17278E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 20.10000 | 1.47983E-002 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 20999.01370 | 20999.01370 | 1.52643 | 1.52643 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 17:10:00 | 33.86833 | 1.71556E-002 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 1463.87796 | 1463.87796 | 6.27764E-002 | 0.47476 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 20.10000 | 1.47983E-002 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 2597.30273 | 2597.30273 | 0.25442 | 0.25442 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:10:00 | 34.57667 | 1.71570E-002 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 202.01603 | 202.01603 | 8.71440E-003 | 1.54338E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 22:20:00 | 20.10000 | 1.47983E-002 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 2627.60951 | 2627.60951 | 0.25739 | 0.25739 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:10:00 | 34.57667 | 1.71570E-002 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 203.02457 | 203.02457 | 8.75790E-003 | 1.54319E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 20.10000 | 1.47983E-002 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 10504.81994 | 10504.81994 | 1.02904 | 1.02904 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:50:00 | 35.20000 | 1.71581E-002 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 989.80992 | 989.80992 | 4.26973E-002 | 9.91540E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 09:20:00 | 20.10000 | 1.47983E-002 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 30269.77923 | 30269.77923 | 2.20303 | 2.20303 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:10:00 | 35.11500 | 1.71580E-002 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 996.03183 | 996.03183 | 4.27138E-002 | 1.18780 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 20.10000 | 1.47983E-002 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 31667.28136 | 31667.28136 | 2.30471 | 2.30471 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:10:00 | 35.11500 | 1.71580E-002 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
40 | DINING_FLR_6 | Heating | 880.13592 | 880.13592 | 3.77437E-002 | 1.18780 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 04:20:00 | 20.10000 | 1.47983E-002 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 30165.46859 | 30165.46859 | 2.19856 | 2.19856 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 12:30:00 | 34.43500 | 1.71567E-002 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.36735 | 00:10:00 | 20.10000 | 1.47983E-002 | 103.30446 | 22.23800 | 0.36735 | 0.00000 | |
43 | CORRIDOR_FLR_6 | Cooling | 10460.67758 | 10460.67758 | 0.76039 | 0.76039 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | 35.20000 | 1.71581E-002 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 1014.97419 | 1014.97419 | 4.35260E-002 | 0.12562 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 04:20:00 | 20.10000 | 1.47983E-002 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | FLR_3_DOAS | Cooling | Sensible | 55571.34 | 16.45228 | 2.05125 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 00:00:00 |
2 | FLR_3_DOAS | Heating | Sensible | 0.00 | 0.00000 | 0.00000 | 00:00:00 | |
3 | VAV WITH REHEAT | Cooling | Sensible | 455148.27 | 21.98314 | 21.98314 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 00:00:00 |
4 | VAV WITH REHEAT | Heating | Sensible | 0.00 | 0.00000 | 0.00000 | 00:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.95645 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.51003 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52600 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.55510 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 7.47021E-004 |
8 | Coil:Heating:Electric | BASEMENT VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 44470.35777 |
9 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.30308 |
10 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16863 |
11 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52600 |
12 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15942 |
13 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52600 |
14 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.25941E-003 |
16 | Coil:Heating:Electric | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 4558.92142 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.27539 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21491 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52600 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.14486 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.57309 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.77285E-003 |
24 | Coil:Heating:Electric | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 4142.36250 |
25 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.28141 |
26 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.44474 |
27 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52600 |
28 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.14802 |
29 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
30 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
31 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 8.56688E-004 |
32 | Coil:Heating:Electric | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 4232.91185 |
33 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.15510 |
34 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.46556 |
35 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52600 |
36 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.15812E-002 |
37 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
38 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 8.18375E-004 |
40 | Coil:Heating:Electric | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 2332.94053 |
41 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.19020 |
42 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 1.86403E-002 |
43 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52600 |
44 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.67804 |
45 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52600 |
46 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.04396E-002 |
48 | Coil:Heating:Electric | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 47986.26257 |
49 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.27494 |
50 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11288 |
51 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52600 |
52 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.67062 |
53 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52600 |
54 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
55 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.37533E-003 |
56 | Coil:Heating:Electric | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 19177.43660 |
57 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 4.72232 |
58 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21109 |
59 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52600 |
60 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.48394 |
61 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.56291 |
62 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.80491E-003 |
64 | Coil:Heating:Electric | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 71032.17049 |
65 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
66 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.92860 |
67 | Fan:OnOff | ROOM_1_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 0.92860 |
68 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.03291E-004 |
69 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68283 |
70 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
71 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.66617E-003 |
72 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
73 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
74 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.03291E-004 |
75 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.92860 |
76 | Coil:Heating:Electric | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Nominal Capacity [W] | 1431.13547 |
77 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
78 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.94035 |
79 | Fan:OnOff | ROOM_2_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 0.94035 |
80 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.06957E-004 |
81 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68283 |
82 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
83 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.66406E-003 |
84 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
85 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
86 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.06957E-004 |
87 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.94035 |
88 | Coil:Heating:Electric | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Nominal Capacity [W] | 1430.96770 |
89 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83707 |
90 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 5.26614 |
91 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 5.26614 |
92 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.68125E-003 |
93 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68351 |
94 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
95 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.58180E-003 |
96 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
97 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
98 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.68125E-003 |
99 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.26614 |
100 | Coil:Heating:Electric | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Nominal Capacity [W] | 19405.32407 |
101 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83730 |
102 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 6.34131 |
103 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 6.34131 |
104 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.13900E-003 |
105 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68266 |
106 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
107 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.78856E-003 |
108 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
109 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
110 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.13900E-003 |
111 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 6.34131 |
112 | Coil:Heating:Electric | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Nominal Capacity [W] | 19410.62861 |
113 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
114 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.82445 |
115 | Fan:OnOff | ROOM_5_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 0.82445 |
116 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.70868E-004 |
117 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68279 |
118 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
119 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.68827E-003 |
120 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
121 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
122 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.70868E-004 |
123 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.82445 |
124 | Coil:Heating:Electric | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Nominal Capacity [W] | 1431.13547 |
125 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
126 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.83219 |
127 | Fan:OnOff | ROOM_6_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 0.83219 |
128 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.73280E-004 |
129 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68279 |
130 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
131 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.68646E-003 |
132 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
133 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
134 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.73280E-004 |
135 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.83219 |
136 | Coil:Heating:Electric | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Nominal Capacity [W] | 1430.96770 |
137 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.52643 |
138 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.77757 |
139 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52600 |
140 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.80290 |
141 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
142 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
143 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.89988E-004 |
144 | Coil:Heating:Electric | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 22960.21161 |
145 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54338E-002 |
146 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.25442 |
147 | Fan:OnOff | ROOM_1_FLR_6 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 0.25442 |
148 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 8.27730E-005 |
149 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68285 |
150 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
151 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.65157E-003 |
152 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
153 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
154 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 8.27730E-005 |
155 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.25442 |
156 | Coil:Heating:Electric | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Nominal Capacity [W] | 357.78336 |
157 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54319E-002 |
158 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.25739 |
159 | Fan:OnOff | ROOM_2_FLR_6 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 0.25739 |
160 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 8.36985E-005 |
161 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68285 |
162 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
163 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.64978E-003 |
164 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
165 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
166 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 8.36985E-005 |
167 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.25739 |
168 | Coil:Heating:Electric | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Nominal Capacity [W] | 357.74143 |
169 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 9.91540E-002 |
170 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.02904 |
171 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 1.02904 |
172 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.43740E-004 |
173 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68259 |
174 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
175 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.75119E-003 |
176 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
177 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
178 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.43740E-004 |
179 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.02904 |
180 | Coil:Heating:Electric | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Nominal Capacity [W] | 2298.59300 |
181 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.20303 |
182 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11472 |
183 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52600 |
184 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.15880 |
185 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52600 |
186 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
187 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.32125E-003 |
188 | Coil:Heating:Electric | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 33137.54993 |
189 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.30471 |
190 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10966 |
191 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52600 |
192 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.21228 |
193 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52600 |
194 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
195 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.47453E-003 |
196 | Coil:Heating:Electric | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 34666.94985 |
197 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.19856 |
198 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 6.43987E-002 |
199 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52600 |
200 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.15644 |
201 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52600 |
202 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
203 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.06412E-002 |
204 | Coil:Heating:Electric | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 33070.24217 |
205 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.76039 |
206 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.41300 |
207 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52600 |
208 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.39996 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 9.22523E-004 |
212 | Coil:Heating:Electric | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 11437.61184 |
213 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05132 |
214 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05132 |
215 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05132 |
216 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05132 |
217 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05132 |
218 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05132 |
219 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
220 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
221 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 11.65196 |
222 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 11.65196 |
223 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 22.15202 |
224 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 11.65196 |
225 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 21.98314 |
226 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 21.98314 |
227 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
228 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.53004 |
229 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05132 |
230 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 21.98314 |
231 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05132 |
232 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05125 |
233 | HeatExchanger:AirToAir:SensibleAndLatent | FLR_3_DOAS OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.05125 |
234 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 35.20000 |
235 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
236 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.94246 |
237 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.71581E-002 |
238 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
239 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Coil Load [W] | 113467.38685 |
240 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.24515E-003 |
241 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 2.05132 |
242 | Coil:Heating:Electric | FLR_3_DOAS HEATING COIL | Design Size Nominal Capacity [W] | 12429.56338 |
243 | Fan:ConstantVolume | FLR_3_DOAS FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05125 |
244 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.24515E-003 |
245 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.46739E-004 |
246 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 21.98314 |
247 | HeatExchanger:AirToAir:SensibleAndLatent | VAV WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 11.66146 |
248 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 29.94533 |
249 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
250 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.09012 |
251 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.36472E-002 |
252 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
253 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 857363.51044 |
254 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.45205E-002 |
255 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 21.98314 |
256 | Coil:Heating:Electric | VAV WITH REHEAT HEATING COIL | Design Size Nominal Capacity [W] | 133202.62535 |
257 | Fan:VariableVolume | VAV WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 21.98314 |
258 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.45205E-002 |
259 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.94201E-005 |
260 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 3.32505E-002 |
261 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 5428.78921 |
262 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 3.32505E-002 |
263 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 3.99006 |
264 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 3.32505E-002 |
265 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 3758.53387 |
266 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 3.32505E-002 |
267 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1162609.73817 |
268 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1165839.98000 |
269 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 132.90576 |
270 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
271 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
272 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
273 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
274 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | 15413.06 | 13231.09 | 2181.96 | 0.86 | 2795.96 | 28.36 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | 15602.25 | 13396.45 | 2205.80 | 0.86 | 2831.51 | 28.72 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 86071.00 | 74550.78 | 11520.22 | 0.87 | 15896.37 | 161.23 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 107568.90 | 91212.65 | 16356.25 | 0.85 | 19073.57 | 193.45 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | 13738.82 | 11767.02 | 1971.80 | 0.86 | 2481.14 | 25.17 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | 13863.37 | 11875.91 | 1987.47 | 0.86 | 2504.54 | 25.40 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | 4211.84 | 3621.10 | 590.75 | 0.86 | 766.34 | 7.77 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | 4259.60 | 3662.84 | 596.75 | 0.86 | 775.32 | 7.86 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 17342.84 | 14759.78 | 2583.06 | 0.85 | 3096.64 | 31.41 |
10 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | 68584.33 | 43991.18 | 24593.14 | 0.64 | 9329.01 | 94.62 |
11 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | 681215.26 | 447090.83 | 234124.44 | 0.66 | 96006.07 | 973.75 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 4.09 | 13.95 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.940 | 0.824 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 22.63 | 45.89 | 22.63 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.496_SHGC_0.22 | N/A | 2.820 | No | 23.26 | 23.26 | 23.26 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 2.390 | 2.390 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 63.73 | 129.23 | 63.73 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.496_SHGC_0.22 | N/A | 2.820 | No | 65.50 | 65.50 | 65.50 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 82.79 | 167.88 | 82.79 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.496_SHGC_0.22 | N/A | 2.820 | No | 85.08 | 85.08 | 85.08 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.393 | 1.153 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.496_SHGC_0.22 | N/A | 2.820 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.393 | 1.153 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.496_SHGC_0.22 | N/A | 2.820 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.393 | 1.153 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.496_SHGC_0.22 | N/A | 2.820 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.393 | 1.153 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.496_SHGC_0.22 | N/A | 2.820 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.393 | 1.153 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.496_SHGC_0.22 | N/A | 2.820 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.393 | 1.153 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.496_SHGC_0.22 | N/A | 2.820 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.393 | 1.153 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.496_SHGC_0.22 | N/A | 2.820 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.393 | 1.153 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.496_SHGC_0.22 | N/A | 2.820 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.393 | 1.153 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.496_SHGC_0.22 | N/A | 2.820 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.393 | 1.153 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.496_SHGC_0.22 | N/A | 2.820 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.496_SHGC_0.22 | N/A | 2.820 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.496_SHGC_0.22 | N/A | 2.820 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.496_SHGC_0.22 | N/A | 2.820 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.496_SHGC_0.22 | N/A | 2.820 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 3.444 | 2.088 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.408 | 1.163 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.496_SHGC_0.22 | N/A | 2.820 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.408 | 1.163 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.496_SHGC_0.22 | N/A | 2.820 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.408 | 1.163 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.496_SHGC_0.22 | N/A | 2.820 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.408 | 1.163 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.496_SHGC_0.22 | N/A | 2.820 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.408 | 1.163 | 13.70 | 20.44 | 13.70 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.496_SHGC_0.22 | N/A | 2.820 | No | 6.74 | 6.74 | 6.74 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.496_SHGC_0.22 | N/A | 2.820 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.496_SHGC_0.22 | N/A | 2.820 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 16.77 | 21.37 | 16.77 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.496_SHGC_0.22 | N/A | 2.820 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 34.86 | 52.03 | 34.86 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.496_SHGC_0.22 | N/A | 2.820 | No | 17.17 | 17.17 | 17.17 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.496_SHGC_0.22 | N/A | 2.820 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.496_SHGC_0.22 | N/A | 2.820 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.496_SHGC_0.22 | N/A | 2.820 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 34.86 | 52.03 | 34.86 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.496_SHGC_0.22 | N/A | 2.820 | No | 17.17 | 17.17 | 17.17 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 3.444 | 1.875 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 1.1919626593E-002 | 1.6732657289E-002 | Pass | Pass | 1.2879845157E-003 | 2.3245888814E-003 | Pass | Pass |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.3793042885E-002 | 1.8680008129E-002 | Pass | Pass | 2.5298821710E-003 | 2.6027263112E-003 | Pass | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.7369634421E-002 | 2.2684581820E-002 | Pass | Pass | 1.8975713555E-003 | 3.2057722786E-003 | Pass | Pass |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 9.5087444253E-003 | 9.3504765864E-003 | Pass | Pass | 1.0604185312E-003 | 1.3145616612E-003 | Pass | Pass |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 6.1853861542E-003 | 5.5684327109E-003 | Pass | Pass | 7.5565142537E-004 | 8.7277252012E-004 | Pass | Pass |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 6.2573181722E-002 | 0.2038965497 | Pass | Pass | 1.4681916660E-002 | 4.2993169502E-002 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 3.6098166604E-002 | 6.0972345068E-002 | Pass | Pass | 3.7072720394E-003 | 7.9484326095E-003 | Pass | Pass |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.4678734355E-002 | 3.6625579027E-002 | Pass | Pass | 2.5515481566E-003 | 4.7842001210E-003 | Pass | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.2631385903E-002 | 0.3421005986 | Pass | Pass | 0.1484950474 | 0.4874193342 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 0.1010862533 | 0.3332825811 | Pass | Pass | 0.1469915595 | 0.4923405979 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 2.8995651223E-005 | 7.8641017837E-005 | Pass | Pass | 2.4310546676E-002 | 5.0021251629E-002 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 0.1060658911 | 0.2983074570 | Pass | Pass | 0.1304826766 | 0.3400482834 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.2635591514E-002 | 0.3394000740 | Pass | Pass | 0.1462680708 | 0.5665595139 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 0.1037560091 | 0.3326121625 | Pass | Pass | 0.1387919585 | 0.4897060168 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 6.4069481341E-003 | 7.5698691815E-003 | Pass | Pass | 8.1908448854E-004 | 1.1005697711E-003 | Pass | Pass |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.2635497446E-002 | 0.3446809222 | Pass | Pass | 0.1439384987 | 0.5922139858 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 0.1024217732 | 0.3367283611 | Pass | Pass | 0.1486461927 | 0.5866489055 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.2641663395E-002 | 0.3362808749 | Pass | Pass | 0.1873677777 | 0.7432038382 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 2.6630075218E-002 | 6.0247736342E-002 | Pass | Pass | 7.3075514861E-003 | 2.5792314072E-002 | Pass | Pass |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 2.1716860455E-002 | 5.0008897800E-002 | Pass | Pass | 8.3055128053E-003 | 2.7070756365E-002 | Pass | Pass |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 3.4654577507E-002 | 9.9140665658E-002 | Pass | Pass | 1.7659257106E-002 | 3.3408412029E-002 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 1.1186941528E-002 | 6.7314718407E-003 | Pass | Pass | 1.2338669878E-003 | 9.0946071884E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:10
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3143.71 | -97.1 | -3027.6 | -12016.5 | 20204.70 | 8207.15 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:10
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 20.10 | 0.00 | 20.10 | Wetbulb [C] | 1.80 | 0.00 |
HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 35.20 | 8.50 | 25.80 | Wetbulb [C] | 4.10 | 160.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 57.00 | 12 | |||
Feb | 0.00 | 0 | |||
Mar | 153.60 | 31 | |||
Apr | 87.00 | 59 | |||
May | 227.22 | 128 | |||
Jun | 144.58 | 109 | |||
Jul | 42.40 | 24 | |||
Aug | 164.90 | 163 | |||
Sep | 119.60 | 50 | |||
Oct | 365.70 | 188 | |||
Nov | 70.90 | 67 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:10
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 211.13 | 211.13 | 0.00 | 90.00 | N |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 55.76 | 55.76 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 211.13 | 211.13 | 180.00 | 90.00 | S |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 55.76 | 55.76 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 45.89 | 22.63 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 129.23 | 63.73 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 167.88 | 82.79 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 1.153 | 1.393 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 1.153 | 1.393 | 104.06 | 69.72 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 1.153 | 1.393 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 1.153 | 1.393 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 1.153 | 1.393 | 847.14 | 567.58 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 1.153 | 1.393 | 847.37 | 567.71 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 1.153 | 1.393 | 104.06 | 69.72 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 1.153 | 1.393 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 1.153 | 1.393 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 1.153 | 1.393 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 26.02 | 17.43 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 1.163 | 1.408 | 13.94 | 9.34 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 1.163 | 1.408 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | RES_ROOF | 0.55 | 0.182 | 0.186 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | RES_EXT_WALL_TOP | 0.30 | 1.163 | 1.408 | 13.94 | 9.34 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 1.163 | 1.408 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | RES_ROOF | 0.55 | 0.182 | 0.186 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 1.163 | 1.408 | 183.96 | 123.26 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | RES_ROOF | 0.55 | 0.182 | 0.186 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 97.55 | 65.36 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 97.55 | 65.36 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 21.37 | 16.77 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 52.03 | 34.86 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 13.94 | 9.34 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 17.65 | 11.83 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 52.03 | 34.86 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 167.42 | 167.42 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_FLOOR | BASEMENT_FLOOR | 0.30 | 1.441 | 2.705 | 1978.83 | 1978.83 | 0.00 | 180.00 | |
BASEMENT_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 1.786 | 3.444 | 67.07 | 67.07 | 180.00 | 0.00 | |
BASEMENT_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 1.786 | 3.444 | 77.67 | 77.67 | 180.00 | 0.00 | |
BASEMENT_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 1.786 | 3.444 | 164.24 | 164.24 | 180.00 | 0.00 | |
BASEMENT_CEILING_4 | NONRES_FLOOR_CEILING | 0.30 | 1.786 | 3.444 | 94.76 | 94.76 | 180.00 | 0.00 | |
BASEMENT_CEILING_5 | NONRES_FLOOR_CEILING | 0.30 | 1.786 | 3.444 | 78.04 | 78.04 | 180.00 | 0.00 | |
BASEMENT_CEILING_6 | NONRES_FLOOR_CEILING | 0.30 | 1.786 | 3.444 | 188.86 | 188.86 | 180.00 | 0.00 | |
BASEMENT_CEILING_7 | NONRES_FLOOR_CEILING | 0.30 | 1.786 | 3.444 | 1088.56 | 1088.56 | 180.00 | 0.00 | |
BASEMENT_CEILING_8 | NONRES_FLOOR_CEILING | 0.30 | 1.786 | 3.444 | 219.63 | 219.63 | 90.00 | 0.00 | |
RETAIL_1_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_1_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
RETAIL_1_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 1.786 | 3.444 | 67.07 | 67.07 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
RETAIL_2_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_2_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 90.00 | 90.00 | E |
RETAIL_2_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 1.786 | 3.444 | 77.67 | 77.67 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 1.979 | 3.444 | 77.67 | 77.67 | 180.00 | 0.00 | |
MECH_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
MECH_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 180.00 | 90.00 | S |
MECH_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
MECH_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 1.786 | 3.444 | 164.24 | 164.24 | 0.00 | 180.00 | |
MECH_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 1.979 | 3.444 | 164.24 | 164.24 | 180.00 | 0.00 | |
STORAGE_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
STORAGE_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 180.00 | 90.00 | S |
STORAGE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
STORAGE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 1.786 | 3.444 | 94.76 | 94.76 | 0.00 | 180.00 | |
STORAGE_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 1.979 | 3.444 | 94.76 | 94.76 | 180.00 | 0.00 | |
LAUNDRY_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 180.00 | 90.00 | S |
LAUNDRY_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 270.00 | 90.00 | W |
LAUNDRY_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 1.786 | 3.444 | 78.04 | 78.04 | 0.00 | 180.00 | |
LAUNDRY_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 1.979 | 3.444 | 78.04 | 78.04 | 180.00 | 0.00 | |
CAFE_FLR_1_WALL_1_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_2_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
CAFE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 1.786 | 3.444 | 188.86 | 188.86 | 0.00 | 180.00 | |
LOBBY_FLR_1_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 90.00 | 90.00 | E |
LOBBY_FLR_1_FLOOR_1 | NONRES_FLOOR | 0.30 | 1.786 | 3.444 | 1088.56 | 1088.56 | 180.00 | 180.00 | |
LOBBY_FLR_1_FLOOR_2 | NONRES_FLOOR | 0.30 | 1.786 | 3.444 | 219.63 | 219.63 | 90.00 | 180.00 | |
LOBBY_FLR_1_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 1.979 | 3.444 | 1062.83 | 1062.83 | 270.00 | 0.00 | |
ROOM_1_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_1_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
ROOM_1_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 1.627 | 3.444 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_1_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 1.979 | 3.444 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_2_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
ROOM_2_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_2_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 1.627 | 3.444 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_2_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 1.979 | 3.444 | 156.07 | 156.07 | 180.00 | 0.00 | |
ROOM_3_MULT19_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.14 | 847.14 | 0.00 | 90.00 | N |
ROOM_3_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_3_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 1.627 | 3.444 | 1863.81 | 1863.81 | 0.00 | 180.00 | |
ROOM_3_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 1.979 | 3.444 | 1863.81 | 1863.81 | 180.00 | 0.00 | |
ROOM_4_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_4_MULT19_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.37 | 847.37 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_4_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 1.627 | 3.444 | 1864.32 | 1864.32 | 0.00 | 180.00 | |
ROOM_4_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 1.979 | 3.444 | 1864.32 | 1864.32 | 180.00 | 0.00 | |
ROOM_5_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
ROOM_5_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 1.627 | 3.444 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_5_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 1.979 | 3.444 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_6_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
ROOM_6_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 1.627 | 3.444 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_6_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 1.979 | 3.444 | 156.07 | 156.07 | 180.00 | 0.00 | |
CORRIDOR_FLR_3_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.28 | 847.28 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_4_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.27 | 847.27 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_FLOOR_1 | NONRES_FLOOR | 0.30 | 1.627 | 3.444 | 297.29 | 297.29 | 180.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_2 | NONRES_FLOOR | 0.30 | 1.627 | 3.444 | 963.06 | 963.06 | 270.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_3 | NONRES_FLOOR | 0.30 | 1.627 | 3.444 | 297.26 | 297.26 | 90.00 | 180.00 | |
CORRIDOR_FLR_3_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 1.979 | 3.444 | 297.29 | 297.29 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 1.979 | 3.444 | 963.06 | 963.06 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 1.979 | 3.444 | 297.26 | 297.26 | 90.00 | 0.00 | |
ROOM_1_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 0.00 | 90.00 | N |
ROOM_1_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_1_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 1.627 | 3.444 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_2_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_2_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 180.00 | 90.00 | S |
ROOM_2_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 1.627 | 3.444 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_3_MULT9_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.96 | 183.96 | 0.00 | 90.00 | N |
ROOM_3_MULT9_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 90.00 | 90.00 | E |
ROOM_3_MULT9_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 270.00 | 90.00 | W |
ROOM_3_MULT9_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 1.627 | 3.444 | 220.77 | 220.77 | 0.00 | 180.00 | |
BANQUET_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
BANQUET_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
BANQUET_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
BANQUET_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 1.627 | 3.444 | 331.66 | 331.66 | 0.00 | 180.00 | |
DINING_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
DINING_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
DINING_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
DINING_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 1.627 | 3.444 | 331.66 | 331.66 | 0.00 | 180.00 | |
KITCHEN_FLR_6_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 7.43 | 7.43 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 1.627 | 3.444 | 103.30 | 103.30 | 180.00 | 180.00 | |
CORRIDOR_FLR_6_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 104.98 | 104.98 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_1_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.95 | 183.95 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 11.15 | 11.15 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 40.88 | 40.88 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 1.627 | 3.444 | 412.12 | 412.12 | 180.00 | 180.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3957.66 | 0.00 | 90.00 | N | ||
RETAIL_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 134.14 | 0.00 | 90.00 | N | ||
RETAIL_2_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 155.34 | 0.00 | 90.00 | N | ||
MECH_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 328.49 | 0.00 | 90.00 | N | ||
STORAGE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 189.52 | 0.00 | 90.00 | N | ||
LAUNDRY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 156.08 | 0.00 | 90.00 | N | ||
CAFE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 377.72 | 0.00 | 90.00 | N | ||
LOBBY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 2616.37 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3727.63 | 0.00 | 90.00 | N | ||
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3728.64 | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3115.24 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.04 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.03 | 0.00 | 90.00 | N | ||
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 441.55 | 0.00 | 90.00 | N | ||
BANQUET_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
DINING_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 206.61 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 824.25 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.496_SHGC_0.22 | 23.26 | 0.00 | 0.00 | 23.26 | 23.26 | 2.820 | 0.221 | 0.243 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.496_SHGC_0.22 | 65.50 | 0.00 | 0.00 | 65.50 | 65.50 | 2.820 | 0.221 | 0.243 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.496_SHGC_0.22 | 85.08 | 0.00 | 0.00 | 85.08 | 85.08 | 2.820 | 0.221 | 0.243 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.496_SHGC_0.22 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.820 | 0.221 | 0.243 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.496_SHGC_0.22 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.820 | 0.221 | 0.243 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.496_SHGC_0.22 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.820 | 0.221 | 0.243 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.496_SHGC_0.22 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.820 | 0.221 | 0.243 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.496_SHGC_0.22 | 3.68 | 0.00 | 0.00 | 3.68 | 279.56 | 2.820 | 0.221 | 0.243 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.496_SHGC_0.22 | 3.68 | 0.00 | 0.00 | 3.68 | 279.65 | 2.820 | 0.221 | 0.243 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.496_SHGC_0.22 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.820 | 0.221 | 0.243 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.496_SHGC_0.22 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.820 | 0.221 | 0.243 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.496_SHGC_0.22 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.820 | 0.221 | 0.243 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.496_SHGC_0.22 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.820 | 0.221 | 0.243 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.496_SHGC_0.22 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.820 | 0.221 | 0.243 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.496_SHGC_0.22 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 2.820 | 0.221 | 0.243 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.496_SHGC_0.22 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 2.820 | 0.221 | 0.243 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.496_SHGC_0.22 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.820 | 0.221 | 0.243 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.496_SHGC_0.22 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.820 | 0.221 | 0.243 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.496_SHGC_0.22 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.820 | 0.221 | 0.243 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.496_SHGC_0.22 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.820 | 0.221 | 0.243 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.496_SHGC_0.22 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.820 | 0.221 | 0.243 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.496_SHGC_0.22 | 6.74 | 0.00 | 0.00 | 6.74 | 60.70 | 2.820 | 0.221 | 0.243 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.496_SHGC_0.22 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.820 | 0.221 | 0.243 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.496_SHGC_0.22 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.820 | 0.221 | 0.243 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.496_SHGC_0.22 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.820 | 0.221 | 0.243 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.496_SHGC_0.22 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.820 | 0.221 | 0.243 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | |||||||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.496_SHGC_0.22 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.820 | 0.221 | 0.243 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.496_SHGC_0.22 | 5.82 | 0.00 | 0.00 | 5.82 | 5.82 | 2.820 | 0.221 | 0.243 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.496_SHGC_0.22 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 2.820 | 0.221 | 0.243 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.496_SHGC_0.22 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.820 | 0.221 | 0.243 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 1213.79 | 2.820 | 0.221 | 0.243 | |||||||||||||||||
North Total or Average | 432.95 | 2.820 | 0.221 | 0.243 | |||||||||||||||||
Non-North Total or Average | 780.84 | 2.820 | 0.221 | 0.243 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 1.760 | 2.390 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:10
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:10
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 8.8143 | 1978.83 | 17441.96 | LightsWired | LTG_SCH_BASEMENT | 49.32 | 168.00 | 49.26 | 0.0000 | Y | 161.29 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | RETAIL_1_FLR_1 | GENERAL | 11.3140 | 67.07 | 758.85 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 7.31 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | RETAIL_2_FLR_1 | GENERAL | 11.3140 | 77.67 | 878.75 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 8.46 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | MECH_FLR_1 | GENERAL | 4.6285 | 164.24 | 760.20 | LightsWired | LTG_SCH_MECHANIC | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 8.37 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | STORAGE_FLR_1 | GENERAL | 5.7199 | 94.76 | 542.02 | LightsWired | LTG_SCH_STORAGE | 30.30 | 168.00 | 30.27 | 0.0000 | Y | 3.08 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | LAUNDRY_FLR_1 | GENERAL | 4.6285 | 78.04 | 361.20 | LightsWired | LTG_SCH_LAUNDRY | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 3.98 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | CAFE_FLR_1 | GENERAL | 10.0104 | 188.86 | 1890.59 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 40.44 | 0.0000 | Y | 14.35 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | LOBBY_FLR_1 | GENERAL | 10.7639 | 1308.19 | 14081.18 | LightsWired | LTG_SCH_LOBBY | 44.02 | 168.00 | 41.68 | 0.0000 | Y | 110.18 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | ROOM_1_FLR_3 | GENERAL | 8.2882 | 156.09 | 1293.69 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | ROOM_2_FLR_3 | GENERAL | 8.2882 | 156.07 | 1293.54 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | GENERAL | 8.2882 | 1863.81 | 15447.65 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 110.38 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | GENERAL | 8.2882 | 1864.32 | 15451.87 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 110.41 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | ROOM_5_FLR_3 | GENERAL | 8.2882 | 156.09 | 1293.69 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | ROOM_6_FLR_3 | GENERAL | 8.2882 | 156.07 | 1293.54 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | CORRIDOR_FLR_3 | GENERAL | 7.1042 | 1557.62 | 11065.59 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 91.33 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | ROOM_1_FLR_6 | GENERAL | 8.2882 | 39.02 | 323.42 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 2.31 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | ROOM_2_FLR_6 | GENERAL | 8.2882 | 39.02 | 323.38 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 2.31 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | GENERAL | 8.2882 | 220.77 | 1829.83 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 13.08 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | BANQUET_FLR_6 | GENERAL | 10.0104 | 331.66 | 3320.03 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 49.55 | 0.0000 | Y | 30.88 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | DINING_FLR_6 | GENERAL | 10.0104 | 331.66 | 3320.03 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 49.55 | 0.0000 | Y | 30.88 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | KITCHEN_FLR_6 | GENERAL | 11.4097 | 103.30 | 1178.68 | LightsWired | LTG_SCH_KITCHEN | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 12.97 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | CORRIDOR_FLR_6 | GENERAL | 7.1042 | 412.12 | 2927.80 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 24.17 |
Interior Lighting Total | 8.5566 | 11345.29 | 97077.49 | 456.96 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
LOBBY_FLR_1_DAYLREFPT1 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.07 | 14081.18 | 985.68 |
LOBBY_FLR_1_DAYLREFPT2 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.07 | 14081.18 | 985.68 |
CAFE_FLR_1_DAYLREFPT1 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1890.59 | 737.33 |
CAFE_FLR_1_DAYLREFPT2 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1890.59 | 737.33 |
DINING_FLR_6_DAYLREFPT1 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
DINING_FLR_6_DAYLREFPT2 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
BANQUET_FLR_6_DAYLREFPT1 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
BANQUET_FLR_6_DAYLREFPT2 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 12338.45 | AstronomicalClock | - | 83.83 | 83.83 | 194.17 | |
Exterior Lighting Total | 12338.45 | 194.17 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:10
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 1165839.98 | 2.96 | 1165839.98 | 2.96 | 4.09 | 13.95 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 10604.83 | 15413.06 | 13231.09 | 2181.96 | 0.86 | - | 2795.96 | 28.36 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 10733.02 | 15602.25 | 13396.45 | 2205.80 | 0.86 | - | 2831.51 | 28.72 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 58786.16 | 86071.00 | 74550.78 | 11520.22 | 0.87 | - | 15896.37 | 161.23 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 74791.86 | 107568.90 | 91212.65 | 16356.25 | 0.85 | - | 19073.57 | 193.45 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 9471.11 | 13738.82 | 11767.02 | 1971.80 | 0.86 | - | 2481.14 | 25.17 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 9555.47 | 13863.37 | 11875.91 | 1987.47 | 0.86 | - | 2504.54 | 25.40 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 2894.23 | 4211.84 | 3621.10 | 590.75 | 0.86 | - | 766.34 | 7.77 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 2926.59 | 4259.60 | 3662.84 | 596.75 | 0.86 | - | 775.32 | 7.86 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 12019.17 | 17342.84 | 14759.78 | 2583.06 | 0.85 | - | 3096.64 | 31.41 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | 113467.39 | 68584.33 | 43991.18 | 24593.14 | 0.64 | - | 9329.01 | 94.62 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | 857363.51 | 681215.26 | 447090.83 | 234124.44 | 0.66 | - | 96006.07 | 973.75 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Electric | 44470.36 | 1.00 | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4558.92 | 1.00 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4142.36 | 1.00 | |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4232.91 | 1.00 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 2332.94 | 1.00 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 47986.26 | 1.00 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 19177.44 | 1.00 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 71032.17 | 1.00 | |
ROOM_1_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Electric | 1431.14 | 1.00 | |
ROOM_2_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Electric | 1430.97 | 1.00 | |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Electric | 19405.32 | 1.00 | |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Electric | 19410.63 | 1.00 | |
ROOM_5_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Electric | 1431.14 | 1.00 | |
ROOM_6_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Electric | 1430.97 | 1.00 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 22960.21 | 1.00 | |
ROOM_1_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Electric | 357.78 | 1.00 | |
ROOM_2_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Electric | 357.74 | 1.00 | |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Electric | 2298.59 | 1.00 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Electric | 33137.55 | 1.00 | |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Electric | 34666.95 | 1.00 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Electric | 33070.24 | 1.00 | |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Electric | 11437.61 | 1.00 | |
FLR_3_DOAS HEATING COIL | Coil:Heating:Electric | 12429.56 | 1.00 | |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Electric | 133202.63 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 0.24 | 76.61 | 324.68 | 1.00 | 2.78 | General | ||
LOBBY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.24 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
ROOM_1_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 0.93 | 653.39 | 703.64 | 1.00 | 1.22 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:20:00 |
ROOM_2_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 0.94 | 661.67 | 703.64 | 1.00 | 1.21 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:20:00 |
ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 5.27 | 3705.45 | 703.64 | 1.00 | 0.97 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:20:00 |
ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 6.34 | 4461.98 | 703.64 | 1.00 | 0.96 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:00:00 |
ROOM_5_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 0.82 | 580.11 | 703.64 | 1.00 | 1.25 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:50:00 |
ROOM_6_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 0.83 | 585.56 | 703.64 | 1.00 | 1.25 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:40:00 |
ROOM_1_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 0.25 | 179.02 | 703.64 | 1.00 | 1.84 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:10:00 |
ROOM_2_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 0.26 | 181.11 | 703.64 | 1.00 | 1.83 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:10:00 |
ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 1.03 | 724.07 | 703.64 | 1.00 | 1.19 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:50:00 |
BANQUET_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
DINING_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 1.89 | 612.92 | 324.68 | 1.00 | 1.48 | General | ||
FLR_3_DOAS FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.93 | 1070.05 | 1.00 | 1.30 | General | ||
VAV WITH REHEAT FAN | Fan:VariableVolume | 0.62 | 1314.72 | 21.98 | 46608.09 | 2120.17 | 1.00 | 1.12 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:50:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.033250 | 5428.79 | 163269.44 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.033250 | 3758.53 | 113036.94 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH LAUNDRY G WATER HEATER | WaterHeater:Mixed | 1.14 | 163316.00 | 0.80 | 11.51 | 0.44 |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.22 | 1.12 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.60 | 0.80 | 5.78 | 0.37 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:10
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 40671.24 | 40671.24 | 20.55 | 2.956 | 2.956 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 22:00:00 | 24.00 | 24.00 | 0.00909 | 29.42 | 0.01715 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 4168.86 | 4168.86 | 62.16 | 0.303 | 0.303 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:40:00 | 24.00 | 24.00 | 0.00920 | 34.24 | 0.01716 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 3788.00 | 3788.00 | 48.77 | 0.275 | 0.275 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 19:20:00 | 24.00 | 24.00 | 0.00930 | 31.57 | 0.01715 | 0.092 | 0.00 |
MECH_FLR_1 | 3871.61 | 3871.61 | 23.57 | 0.281 | 0.281 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 19:10:00 | 24.00 | 24.00 | 0.00877 | 31.73 | 0.01715 | 0.000 | 0.00 |
STORAGE_FLR_1 | 2133.80 | 2133.80 | 22.52 | 0.155 | 0.155 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 17:30:00 | 24.00 | 24.00 | 0.00883 | 33.59 | 0.01716 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 43885.45 | 43885.45 | 562.35 | 3.190 | 3.190 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:30:00 | 24.00 | 24.00 | 0.00856 | 34.35 | 0.01716 | 0.000 | 0.00 |
CAFE_FLR_1 | 17522.02 | 17522.02 | 92.78 | 1.275 | 1.275 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:40:00 | 24.00 | 23.99 | 0.01038 | 35.20 | 0.01716 | 0.676 | 0.00 |
LOBBY_FLR_1 | 64937.73 | 64937.73 | 49.64 | 4.722 | 4.722 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 17:00:00 | 24.00 | 23.99 | 0.01001 | 34.01 | 0.01716 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 9479.64 | 9479.64 | 242.93 | 0.929 | 0.929 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:20:00 | 21.11 | 21.11 | 0.00867 | 34.46 | 0.01716 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 9599.67 | 9599.67 | 246.04 | 0.940 | 0.940 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:20:00 | 21.11 | 21.11 | 0.00866 | 34.46 | 0.01716 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 53763.66 | 53763.66 | 2192.30 | 5.266 | 5.266 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:20:00 | 21.11 | 21.11 | 0.00858 | 35.03 | 0.01716 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 64735.45 | 64735.45 | 2638.97 | 6.341 | 6.341 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:00:00 | 21.11 | 21.11 | 0.00879 | 34.69 | 0.01716 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 8416.43 | 8416.43 | 215.68 | 0.824 | 0.824 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:50:00 | 21.11 | 21.11 | 0.00869 | 31.73 | 0.01715 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 8495.49 | 8495.49 | 217.74 | 0.832 | 0.832 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:40:00 | 21.11 | 21.11 | 0.00869 | 31.49 | 0.01715 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 20999.01 | 20999.01 | 53.93 | 1.526 | 1.526 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 17:10:00 | 24.00 | 24.00 | 0.00946 | 33.87 | 0.01716 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 2597.30 | 2597.30 | 66.56 | 0.254 | 0.254 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:10:00 | 21.11 | 21.11 | 0.00865 | 34.58 | 0.01716 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2627.61 | 2627.61 | 67.34 | 0.257 | 0.257 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:10:00 | 21.11 | 21.11 | 0.00865 | 34.58 | 0.01716 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 10504.82 | 10504.82 | 428.23 | 1.029 | 1.029 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:50:00 | 21.11 | 21.11 | 0.00875 | 35.20 | 0.01716 | 0.099 | 0.00 |
BANQUET_FLR_6 | 30269.78 | 30269.78 | 91.27 | 2.203 | 2.203 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:10:00 | 24.00 | 23.98 | 0.01038 | 35.12 | 0.01716 | 1.188 | 0.00 |
DINING_FLR_6 | 31667.28 | 31667.28 | 95.48 | 2.305 | 2.305 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:10:00 | 24.00 | 23.99 | 0.01030 | 35.12 | 0.01716 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 30165.47 | 30165.47 | 292.01 | 2.199 | 2.199 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 12:30:00 | 24.00 | 23.97 | 0.01013 | 34.44 | 0.01716 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 10460.68 | 10460.68 | 25.38 | 0.760 | 0.760 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | 24.00 | 24.00 | 0.00904 | 35.20 | 0.01716 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 0.854 | 00:10:00 | 21.00 | 22.11 | 0.01480 | 20.10 | 0.01480 | 0.854 | 0.00 | |
RETAIL_1_FLR_1 | 319.44 | 319.44 | 4.76 | 0.014 | 0.079 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00963 | 20.10 | 0.01480 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 81.83 | 81.83 | 1.05 | 0.004 | 0.092 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.01021 | 20.10 | 0.01480 | 0.092 | 0.00 |
MECH_FLR_1 | 154.80 | 154.80 | 0.94 | 0.007 | 0.007 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.01056 | 20.10 | 0.01480 | 0.000 | 0.00 |
STORAGE_FLR_1 | 80.70 | 80.70 | 0.85 | 0.003 | 0.058 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.01073 | 20.10 | 0.01480 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 341.11 | 341.11 | 4.37 | 0.015 | 0.015 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00983 | 20.10 | 0.01480 | 0.000 | 0.00 |
CAFE_FLR_1 | 728.77 | 728.77 | 3.86 | 0.031 | 0.676 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00959 | 20.10 | 0.01480 | 0.676 | 0.00 |
LOBBY_FLR_1 | 1226.79 | 1226.79 | 0.94 | 0.053 | 1.894 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.01035 | 20.10 | 0.01480 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 631.13 | 631.13 | 16.17 | 0.027 | 0.062 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00983 | 20.10 | 0.01480 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 636.79 | 636.79 | 16.32 | 0.027 | 0.062 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00981 | 20.10 | 0.01480 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 3708.75 | 3708.75 | 151.23 | 0.160 | 0.837 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00969 | 20.10 | 0.01480 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 3820.39 | 3820.39 | 155.74 | 0.165 | 0.837 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00965 | 20.10 | 0.01480 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 631.13 | 631.13 | 16.17 | 0.027 | 0.062 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00983 | 20.10 | 0.01480 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 636.79 | 636.79 | 16.32 | 0.027 | 0.062 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00981 | 20.10 | 0.01480 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 1463.88 | 1463.88 | 3.76 | 0.063 | 0.475 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00910 | 20.10 | 0.01480 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 202.02 | 202.02 | 5.18 | 0.009 | 0.015 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 22:20:00 | 21.11 | 21.11 | 0.00952 | 20.10 | 0.01480 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 203.02 | 203.02 | 5.20 | 0.009 | 0.015 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00951 | 20.10 | 0.01480 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 989.81 | 989.81 | 40.35 | 0.043 | 0.099 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 09:20:00 | 21.11 | 21.11 | 0.00944 | 20.10 | 0.01480 | 0.099 | 0.00 |
BANQUET_FLR_6 | 996.03 | 996.03 | 3.00 | 0.043 | 1.188 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 21.00 | 21.00 | 0.00885 | 20.10 | 0.01480 | 1.188 | 0.00 |
DINING_FLR_6 | 880.14 | 880.14 | 2.65 | 0.038 | 1.188 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 04:20:00 | 21.00 | 21.00 | 0.00895 | 20.10 | 0.01480 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.367 | 00:10:00 | 21.00 | 24.00 | 0.00835 | 20.10 | 0.01480 | 0.367 | 0.00 | |
CORRIDOR_FLR_6 | 1014.97 | 1014.97 | 2.46 | 0.044 | 0.126 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 04:20:00 | 21.00 | 21.00 | 0.00874 | 20.10 | 0.01480 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
FLR_3_DOAS | 16.45 | 2.05 | 0.00 | 0.00 | 2.0513 | 2.0513 | 2.0513 | 1.0000 | 0.3000 |
VAV WITH REHEAT | 21.98 | 21.98 | 0.00 | 0.00 | 21.9831 | 11.6520 | 21.9831 | 0.5300 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 44470.358 | 44470.358 | -999.0 | -999.0 | -999.000 | 12/21 00:10:00 | 12/21 00:10:00 | 44470.36 | 24434.58 | 0.854459 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | -999.00 | -999.00 | ||
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 4558.921 | 4558.921 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 4558.92 | 2265.36 | 0.079218 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.00962691 | 62.0425 | 319.44 | 0.00 | -999.00 | -999.00 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 4142.362 | 4142.362 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 4142.36 | 2623.29 | 0.091735 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01021018 | 65.7426 | 81.83 | 0.00 | -999.00 | -999.00 |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 4232.912 | 4232.912 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 4232.91 | 189.84 | 0.006639 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01055881 | 67.9498 | 154.80 | 0.00 | -999.00 | -999.00 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 2332.941 | 2332.941 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 2332.94 | 1651.88 | 0.057765 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01073078 | 69.0378 | 80.70 | 0.00 | -999.00 | -999.00 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Unknown | Unknown | 47986.263 | 47986.263 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 47986.26 | 418.33 | 0.014629 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.00982525 | 63.3007 | 341.11 | 0.00 | -999.00 | -999.00 |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 19177.437 | 19177.437 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 19177.44 | 19177.44 | 0.676389 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.00958858 | 61.7996 | 728.77 | 0.00 | -999.00 | -999.00 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Unknown | Unknown | 71032.170 | 71032.170 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 71032.17 | 54161.60 | 1.893991 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01034803 | 66.6157 | 1226.79 | 0.00 | -999.00 | -999.00 |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 10604.826 | -999.000 | 0.928596 | 0.00030329 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:20:00 | unknown | 4/21 16:20:00 | 10604.83 | 10187.16 | 0.928596 | 21.68 | 15.69 | 0.00866617 | 12.80 | 12.09 | 0.00850000 | 34.46 | 0.01715674 | 25.64 | 0.0000 | 21.11 | 0.00866617 | 55.5607 | 9479.64 | 0.00 | 10619.57 | 10619.57 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 1431.135 | 1431.135 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1431.14 | 1374.77 | 0.061735 | 21.68 | 15.69 | 0.00866617 | 12.80 | 12.09 | 0.00850000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.11 | 0.00982626 | 62.8766 | 631.13 | 0.00 | -999.00 | -999.00 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 10733.018 | -999.000 | 0.940354 | 0.00030696 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:20:00 | unknown | 4/21 16:20:00 | 10733.02 | 10315.47 | 0.940354 | 21.68 | 15.69 | 0.00866406 | 12.80 | 12.09 | 0.00850000 | 34.46 | 0.01715674 | 25.64 | 0.0000 | 21.11 | 0.00866406 | 55.5473 | 9599.67 | 0.00 | 10747.98 | 10747.98 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 1430.968 | 1430.968 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1430.97 | 1375.30 | 0.061728 | 21.68 | 15.69 | 0.00866406 | 12.80 | 12.09 | 0.00850000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.11 | 0.00981425 | 62.8009 | 636.79 | 0.00 | -999.00 | -999.00 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 58786.158 | -999.000 | 5.266141 | 0.00168125 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:20:00 | unknown | 4/21 15:20:00 | 58786.16 | 57623.24 | 5.266141 | 21.68 | 15.62 | 0.00858180 | 12.80 | 12.09 | 0.00850000 | 35.03 | 0.01715783 | 25.79 | 0.0000 | 21.11 | 0.00858180 | 55.0251 | 53763.66 | 0.00 | 58876.93 | 58876.93 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 19405.324 | 19405.324 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 19405.32 | 19021.44 | 0.837072 | 21.68 | 15.62 | 0.00858180 | 12.80 | 12.09 | 0.00850000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.11 | 0.00969202 | 62.0323 | 3708.75 | 0.00 | -999.00 | -999.00 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 74791.857 | -999.000 | 6.341309 | 0.00213900 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:00:00 | unknown | 4/21 16:00:00 | 74791.86 | 69820.90 | 6.341309 | 21.68 | 15.80 | 0.00878856 | 12.80 | 12.09 | 0.00850000 | 34.69 | 0.01715717 | 25.70 | 0.0000 | 21.11 | 0.00878856 | 56.3345 | 64735.45 | 0.00 | 74895.05 | 72898.59 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 19410.629 | 19410.629 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 19410.63 | 18120.52 | 0.837300 | 21.68 | 15.80 | 0.00878856 | 12.80 | 12.09 | 0.00850000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.11 | 0.00965495 | 61.7987 | 3820.39 | 0.00 | -999.00 | -999.00 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 9471.111 | -999.000 | 0.824449 | 0.00027087 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:50:00 | unknown | 4/21 09:50:00 | 9471.11 | 9050.70 | 0.824449 | 21.68 | 15.71 | 0.00868827 | 12.80 | 12.09 | 0.00850000 | 31.73 | 0.01715153 | 24.95 | 0.0000 | 21.11 | 0.00868827 | 55.7005 | 8416.43 | 0.00 | 9483.94 | 9483.94 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 1431.135 | 1431.135 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1431.14 | 1367.61 | 0.061735 | 21.68 | 15.71 | 0.00868827 | 12.80 | 12.09 | 0.00850000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.11 | 0.00982626 | 62.8766 | 631.13 | 0.00 | -999.00 | -999.00 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 9555.467 | -999.000 | 0.832194 | 0.00027328 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:40:00 | unknown | 4/21 09:40:00 | 9555.47 | 9135.21 | 0.832194 | 21.68 | 15.71 | 0.00868646 | 12.80 | 12.09 | 0.00850000 | 31.49 | 0.01715107 | 24.89 | 0.0000 | 21.11 | 0.00868646 | 55.6890 | 8495.49 | 0.00 | 9568.44 | 9568.44 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 1430.968 | 1430.968 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1430.97 | 1368.03 | 0.061728 | 21.68 | 15.71 | 0.00868646 | 12.80 | 12.09 | 0.00850000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.11 | 0.00981425 | 62.8009 | 636.79 | 0.00 | -999.00 | -999.00 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 22960.212 | 22960.212 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 22960.21 | 13576.56 | 0.474762 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.00909851 | 58.6881 | 1463.88 | 0.00 | -999.00 | -999.00 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 2894.229 | -999.000 | 0.254423 | 0.00008277 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:10:00 | unknown | 4/21 16:10:00 | 2894.23 | 2789.90 | 0.254423 | 21.68 | 15.68 | 0.00865157 | 12.80 | 12.09 | 0.00850000 | 34.58 | 0.01715696 | 25.67 | 0.0000 | 21.11 | 0.00865157 | 55.4683 | 2597.30 | 0.00 | 2898.33 | 2898.33 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 357.783 | 357.783 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 22:20:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 22:20:00 | 357.78 | 344.89 | 0.015434 | 21.68 | 15.68 | 0.00865157 | 12.80 | 12.09 | 0.00850000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.11 | 0.00951575 | 60.9195 | 202.02 | 0.00 | -999.00 | -999.00 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 2926.587 | -999.000 | 0.257392 | 0.00008370 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:10:00 | unknown | 4/21 16:10:00 | 2926.59 | 2822.29 | 0.257392 | 21.68 | 15.68 | 0.00864978 | 12.80 | 12.09 | 0.00850000 | 34.58 | 0.01715696 | 25.67 | 0.0000 | 21.11 | 0.00864978 | 55.4570 | 2627.61 | 0.00 | 2930.74 | 2930.74 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 357.741 | 357.741 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 357.74 | 344.99 | 0.015432 | 21.68 | 15.68 | 0.00864978 | 12.80 | 12.09 | 0.00850000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.11 | 0.00950981 | 60.8820 | 203.02 | 0.00 | -999.00 | -999.00 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 12019.169 | -999.000 | 1.029038 | 0.00034374 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:50:00 | unknown | 4/21 14:50:00 | 12019.17 | 11317.73 | 1.029038 | 21.68 | 15.77 | 0.00875119 | 12.80 | 12.09 | 0.00850000 | 35.20 | 0.01715815 | 25.83 | 0.0000 | 21.11 | 0.00875119 | 56.0987 | 10504.82 | 0.00 | 12036.46 | 11827.49 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 2298.593 | 2298.593 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 09:20:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 09:20:00 | 2298.59 | 2164.45 | 0.099154 | 21.68 | 15.77 | 0.00875119 | 12.80 | 12.09 | 0.00850000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.11 | 0.00944390 | 60.4669 | 989.81 | 0.00 | -999.00 | -999.00 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Electric | Unknown | Unknown | 33137.550 | 33137.550 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 33137.55 | 33137.55 | 1.187797 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.00885022 | 57.1085 | 996.03 | 0.00 | -999.00 | -999.00 |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Electric | Unknown | Unknown | 34666.950 | 34666.950 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 04:20:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 04:20:00 | 34666.95 | 33966.90 | 1.187797 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.00894659 | 57.7215 | 880.14 | 0.00 | -999.00 | -999.00 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Electric | Unknown | Unknown | 33070.242 | 33070.242 | -999.0 | -999.0 | -999.000 | 12/21 00:10:00 | 12/21 00:10:00 | 33070.24 | 10504.95 | 0.367350 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | -999.00 | -999.00 | ||
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 11437.612 | 11437.612 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 04:20:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 04:20:00 | 11437.61 | 3592.17 | 0.125616 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.00874411 | 56.4336 | 1014.97 | 0.00 | -999.00 | -999.00 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 113467.387 | -999.000 | 2.051317 | 0.00324515 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:00:00 | 113467.39 | 59031.63 | 2.051317 | 35.20 | 25.83 | 0.01715815 | 11.94 | 11.74 | 0.00850000 | 35.20 | 0.01715815 | 25.83 | 99.9965 | 21.11 | 0.00869578 | 55.7470 | 167398.85 | 0.00 | 113576.05 | 59963.95 |
FLR_3_DOAS HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | FLR_3_DOAS | 12429.563 | 12429.563 | -999.0 | -999.0 | -999.000 | unknown | unknown | unknown | 12429.56 | 12429.56 | 0.615395 | 0.00 | -6.26 | 0.00000000 | 16.70 | 13.18 | 0.00800000 | 0.00 | 0.00000000 | -6.26 | 333.3216 | -999.00 | -999.0 | -999.0000 | 0.00 | 0.00 | -999.00 | -999.00 | |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 857363.510 | -999.000 | 21.983141 | 0.02452049 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:50:00 | 857363.51 | 503599.62 | 21.983141 | 29.95 | 22.21 | 0.01364718 | 11.09 | 11.09 | 0.00850000 | 35.20 | 0.01715815 | 25.83 | 53.0473 | 23.99 | 0.00963627 | 51.7780 | 301756.59 | 0.00 | 858331.50 | 504597.51 |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | VAV WITH REHEAT | 133202.625 | 133202.625 | -999.0 | -999.0 | -999.000 | unknown | unknown | unknown | 133202.63 | 133202.63 | 6.594942 | 0.00 | -6.26 | 0.00000000 | 16.70 | 13.18 | 0.00800000 | 0.00 | 0.00000000 | -6.26 | 176.8243 | -999.00 | -999.0 | -999.0000 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:10
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | No | unknown | No | 44470.358 | 44470.358 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | 12/21 00:10:00 | unknown | unknown | 12/21 00:10:00 | Sensible | 44470.36 | 24434.58 | 1.0000 | 1.02842241 | 0.854459 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 44470.36 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |||
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | No | unknown | No | 4558.921 | 4558.921 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 4558.92 | 2265.36 | 1.0000 | 0.09534629 | 0.079218 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4558.92 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.00 | 0.00962691 | 21.00 | 0.00962691 | 62.0425 | 319.44 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | No | unknown | No | 4142.362 | 4142.362 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 4142.36 | 2623.29 | 1.0000 | 0.11041137 | 0.091735 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4142.36 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.00 | 0.01021018 | 21.00 | 0.01021018 | 65.7426 | 81.83 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | No | unknown | No | 4232.912 | 4232.912 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 4232.91 | 189.84 | 1.0000 | 0.00799018 | 0.006639 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4232.91 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.00 | 0.01055881 | 21.00 | 0.01055881 | 67.9498 | 154.80 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | No | unknown | No | 2332.941 | 2332.941 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 2332.94 | 1651.88 | 1.0000 | 0.06952585 | 0.057765 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 2332.94 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.00 | 0.01073078 | 21.00 | 0.01073078 | 69.0378 | 80.70 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | No | unknown | No | 47986.263 | 47986.263 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 47986.26 | 418.33 | 1.0000 | 0.01760701 | 0.014629 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 47986.26 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.00 | 0.00982525 | 21.00 | 0.00982525 | 63.3007 | 341.11 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | No | unknown | No | 19177.437 | 19177.437 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 19177.44 | 19177.44 | 1.0000 | 0.81409886 | 0.676389 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19177.44 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.00 | 0.00958858 | 21.00 | 0.00958858 | 61.7996 | 728.77 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | No | unknown | No | 71032.170 | 71032.170 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 71032.17 | 54161.60 | 1.0000 | 2.27959752 | 1.893991 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 71032.17 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.00 | 0.01034803 | 21.00 | 0.01034803 | 66.6157 | 1226.79 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10604.826 | -999.000 | 0.928596 | 0.00030329 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9500 | 1004.8586 | 1.2036 | ROOM_1_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.928596 | 1.11765407 | 4197.9300 | 999.8980 | 33.24709945 | 15.03 | 6.70 | 8.33 | 1162609.74 | 0.9122 | 0.912140 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:20:00 | unknown | unknown | unknown | 4/21 16:20:00 | Sensible | 10604.83 | 10187.16 | 1.0000 | 1.11765407 | 0.928596 | 21.68 | 15.69 | 0.00866617 | 43810.7 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.30326007 | 6.70 | 15.03 | 8.33 | 0.000 | 10604.83 | 34.46 | 0.01715674 | 25.64 | 0.00000000 | 0.0000 | 21.11 | 0.00866617 | 21.11 | 0.00866617 | 55.5607 | 9479.64 | 0.00 | 10619.57 | 10619.57 | 1.11765407 | 21.68 | 15.70 | 0.00866617 | 43810.7 | 12.38 | 12.09 | 0.00866617 | 34309.0 | |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | No | unknown | No | 1431.135 | 1431.135 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6411 | 1004.8586 | 1.2036 | ROOM_1_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.928596 | 1.11765407 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1431.14 | 1374.77 | 1.0000 | 0.07430396 | 0.061735 | 21.68 | 15.69 | 0.00866617 | 43810.7 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 1431.14 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.11 | 0.00982626 | 21.11 | 0.00982626 | 62.8766 | 631.13 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10733.018 | -999.000 | 0.940354 | 0.00030696 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9461 | 1004.8586 | 1.2036 | ROOM_2_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.940354 | 1.13180500 | 4197.9300 | 999.8980 | 33.24709945 | 15.03 | 6.70 | 8.33 | 1162609.74 | 0.9232 | 0.923166 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:20:00 | unknown | unknown | unknown | 4/21 16:20:00 | Sensible | 10733.02 | 10315.47 | 1.0000 | 1.13180500 | 0.940354 | 21.68 | 15.69 | 0.00866406 | 43805.3 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.30692590 | 6.70 | 15.03 | 8.33 | 0.000 | 10733.02 | 34.46 | 0.01715674 | 25.64 | 0.00000000 | 0.0000 | 21.11 | 0.00866406 | 21.11 | 0.00866406 | 55.5473 | 9599.67 | 0.00 | 10747.98 | 10747.98 | 1.13180500 | 21.68 | 15.70 | 0.00866406 | 43805.3 | 12.38 | 12.09 | 0.00866406 | 34309.0 | |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | No | unknown | No | 1430.968 | 1430.968 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6411 | 1004.8586 | 1.2036 | ROOM_2_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.940354 | 1.13180500 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1430.97 | 1375.30 | 1.0000 | 0.07429526 | 0.061728 | 21.68 | 15.69 | 0.00866406 | 43805.3 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 1430.97 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.11 | 0.00981425 | 21.11 | 0.00981425 | 62.8009 | 636.79 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 58786.158 | -999.000 | 5.266141 | 0.00168125 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7931 | 1004.8586 | 1.2036 | ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 5.266141 | 6.33830064 | 4197.9300 | 999.8980 | 33.24709945 | 15.03 | 6.70 | 8.33 | 1162609.74 | 5.0564 | 5.056302 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:20:00 | unknown | unknown | unknown | 4/21 15:20:00 | Sensible | 58786.16 | 57623.24 | 1.0000 | 6.33830064 | 5.266141 | 21.68 | 15.62 | 0.00858180 | 43596.9 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 1.68107378 | 6.70 | 15.03 | 8.33 | 0.000 | 58786.16 | 35.03 | 0.01715783 | 25.79 | 0.00000000 | 0.0000 | 21.11 | 0.00858180 | 21.11 | 0.00858180 | 55.0251 | 53763.66 | 0.00 | 58876.93 | 58876.93 | 6.33830064 | 21.68 | 15.63 | 0.00858180 | 43596.9 | 12.58 | 12.09 | 0.00858180 | 34307.9 | |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | No | unknown | No | 19405.324 | 19405.324 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6411 | 1004.8586 | 1.2036 | ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 5.266141 | 6.33830064 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 19405.32 | 19021.44 | 1.0000 | 1.00749507 | 0.837072 | 21.68 | 15.62 | 0.00858180 | 43596.9 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19405.32 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.11 | 0.00969202 | 21.11 | 0.00969202 | 62.0323 | 3708.75 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 74791.857 | -999.000 | 6.341309 | 0.00213900 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1775 | 1004.8586 | 1.2036 | ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 6.341309 | 7.63236782 | 4197.9300 | 999.8980 | 33.24709945 | 15.03 | 6.70 | 8.33 | 1162609.74 | 6.4331 | 6.432981 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:00:00 | unknown | unknown | unknown | 4/21 16:00:00 | Sensible | 74791.86 | 69820.90 | 1.0000 | 7.63236782 | 6.341309 | 21.68 | 15.80 | 0.00878856 | 44121.5 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 2.13877949 | 6.70 | 15.03 | 8.33 | 0.000 | 74791.86 | 34.69 | 0.01715717 | 25.70 | 0.00000000 | 0.0000 | 21.11 | 0.00878856 | 21.11 | 0.00878856 | 56.3345 | 64735.45 | 0.00 | 74895.05 | 72898.59 | 7.63236782 | 21.68 | 15.81 | 0.00878856 | 44121.5 | 12.33 | 12.09 | 0.00868491 | 34308.7 | |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | No | unknown | No | 19410.629 | 19410.629 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6411 | 1004.8586 | 1.2036 | ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 6.341309 | 7.63236782 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 19410.63 | 18120.52 | 1.0000 | 1.00777057 | 0.837300 | 21.68 | 15.80 | 0.00878856 | 44121.5 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19410.63 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.11 | 0.00965495 | 21.11 | 0.00965495 | 61.7987 | 3820.39 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9471.111 | -999.000 | 0.824449 | 0.00027087 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9911 | 1004.8586 | 1.2036 | ROOM_5_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.824449 | 0.99230299 | 4197.9300 | 999.8980 | 33.24709945 | 15.03 | 6.70 | 8.33 | 1162609.74 | 0.8146 | 0.814627 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:50:00 | unknown | unknown | unknown | 4/21 09:50:00 | Sensible | 9471.11 | 9050.70 | 1.0000 | 0.99230299 | 0.824449 | 21.68 | 15.71 | 0.00868827 | 43866.8 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.27083990 | 6.70 | 15.03 | 8.33 | 0.000 | 9471.11 | 31.73 | 0.01715153 | 24.95 | 0.00000000 | 0.0000 | 21.11 | 0.00868827 | 21.11 | 0.00868827 | 55.7005 | 8416.43 | 0.00 | 9483.94 | 9483.94 | 0.99230299 | 21.68 | 15.72 | 0.00868827 | 43866.8 | 12.32 | 12.09 | 0.00868827 | 34309.3 | |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | No | unknown | No | 1431.135 | 1431.135 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6411 | 1004.8586 | 1.2036 | ROOM_5_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.824449 | 0.99230299 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1431.14 | 1367.61 | 1.0000 | 0.07430396 | 0.061735 | 21.68 | 15.71 | 0.00868827 | 43866.8 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 1431.14 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.11 | 0.00982626 | 21.11 | 0.00982626 | 62.8766 | 631.13 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9555.467 | -999.000 | 0.832194 | 0.00027328 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9877 | 1004.8586 | 1.2036 | ROOM_6_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.832194 | 1.00162414 | 4197.9300 | 999.8980 | 33.24709945 | 15.03 | 6.70 | 8.33 | 1162609.74 | 0.8219 | 0.821883 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:40:00 | unknown | unknown | unknown | 4/21 09:40:00 | Sensible | 9555.47 | 9135.21 | 1.0000 | 1.00162414 | 0.832194 | 21.68 | 15.71 | 0.00868646 | 43862.2 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.27325215 | 6.70 | 15.03 | 8.33 | 0.000 | 9555.47 | 31.49 | 0.01715107 | 24.89 | 0.00000000 | 0.0000 | 21.11 | 0.00868646 | 21.11 | 0.00868646 | 55.6890 | 8495.49 | 0.00 | 9568.44 | 9568.44 | 1.00162414 | 21.68 | 15.72 | 0.00868646 | 43862.2 | 12.33 | 12.09 | 0.00868646 | 34309.2 | |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | No | unknown | No | 1430.968 | 1430.968 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6411 | 1004.8586 | 1.2036 | ROOM_6_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.832194 | 1.00162414 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1430.97 | 1368.03 | 1.0000 | 0.07429526 | 0.061728 | 21.68 | 15.71 | 0.00868646 | 43862.2 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 1430.97 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.11 | 0.00981425 | 21.11 | 0.00981425 | 62.8009 | 636.79 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | No | unknown | No | 22960.212 | 22960.212 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 22960.21 | 13576.56 | 1.0000 | 0.57142138 | 0.474762 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22960.21 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.00 | 0.00909851 | 21.00 | 0.00909851 | 58.6881 | 1463.88 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2894.229 | -999.000 | 0.254423 | 0.00008277 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9228 | 1004.8586 | 1.2036 | ROOM_1_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.254423 | 0.30622280 | 4197.9300 | 999.8980 | 33.24709945 | 15.03 | 6.70 | 8.33 | 1162609.74 | 0.2489 | 0.248938 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:10:00 | unknown | unknown | unknown | 4/21 16:10:00 | Sensible | 2894.23 | 2789.90 | 1.0000 | 0.30622280 | 0.254423 | 21.68 | 15.68 | 0.00865157 | 43773.6 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.08276460 | 6.70 | 15.03 | 8.33 | 0.000 | 2894.23 | 34.58 | 0.01715696 | 25.67 | 0.00000000 | 0.0000 | 21.11 | 0.00865157 | 21.11 | 0.00865157 | 55.4683 | 2597.30 | 0.00 | 2898.33 | 2898.33 | 0.30622280 | 21.68 | 15.69 | 0.00865157 | 43773.6 | 12.41 | 12.09 | 0.00865157 | 34308.8 | |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | No | unknown | No | 357.783 | 357.783 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6411 | 1004.8586 | 1.2036 | ROOM_1_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.254423 | 0.30622280 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 22:20:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 22:20:00 | Sensible | 357.78 | 344.89 | 1.0000 | 0.01857599 | 0.015434 | 21.68 | 15.68 | 0.00865157 | 43773.6 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 357.78 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.11 | 0.00951575 | 21.11 | 0.00951575 | 60.9195 | 202.02 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2926.587 | -999.000 | 0.257392 | 0.00008370 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9195 | 1004.8586 | 1.2036 | ROOM_2_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.257392 | 0.30979596 | 4197.9300 | 999.8980 | 33.24709945 | 15.03 | 6.70 | 8.33 | 1162609.74 | 0.2517 | 0.251721 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:10:00 | unknown | unknown | unknown | 4/21 16:10:00 | Sensible | 2926.59 | 2822.29 | 1.0000 | 0.30979596 | 0.257392 | 21.68 | 15.68 | 0.00864978 | 43769.0 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.08368993 | 6.70 | 15.03 | 8.33 | 0.000 | 2926.59 | 34.58 | 0.01715696 | 25.67 | 0.00000000 | 0.0000 | 21.11 | 0.00864978 | 21.11 | 0.00864978 | 55.4570 | 2627.61 | 0.00 | 2930.74 | 2930.74 | 0.30979596 | 21.68 | 15.69 | 0.00864978 | 43769.0 | 12.42 | 12.09 | 0.00864978 | 34308.8 | |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | No | unknown | No | 357.741 | 357.741 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6411 | 1004.8586 | 1.2036 | ROOM_2_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.257392 | 0.30979596 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 357.74 | 344.99 | 1.0000 | 0.01857381 | 0.015432 | 21.68 | 15.68 | 0.00864978 | 43769.0 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 357.74 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.11 | 0.00950981 | 21.11 | 0.00950981 | 60.8820 | 203.02 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12019.169 | -999.000 | 1.029038 | 0.00034374 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1080 | 1004.8586 | 1.2036 | ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 1.029038 | 1.23854445 | 4197.9300 | 999.8980 | 33.24709945 | 15.03 | 6.70 | 8.33 | 1162609.74 | 1.0338 | 1.033790 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:50:00 | unknown | unknown | unknown | 4/21 14:50:00 | Sensible | 12019.17 | 11317.73 | 1.0000 | 1.23854445 | 1.029038 | 21.68 | 15.77 | 0.00875119 | 44026.5 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.34370524 | 6.70 | 15.03 | 8.33 | 0.000 | 12019.17 | 35.20 | 0.01715815 | 25.83 | 0.00000000 | 0.0000 | 21.11 | 0.00875119 | 21.11 | 0.00875119 | 56.0987 | 10504.82 | 0.00 | 12036.46 | 11827.49 | 1.23854445 | 21.68 | 15.78 | 0.00875119 | 44026.5 | 12.33 | 12.09 | 0.00868434 | 34308.2 | |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:ELECTRIC | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | No | unknown | No | 2298.593 | 2298.593 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6411 | 1004.8586 | 1.2036 | ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 1.029038 | 1.23854445 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 09:20:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 09:20:00 | Sensible | 2298.59 | 2164.45 | 1.0000 | 0.11934125 | 0.099154 | 21.68 | 15.77 | 0.00875119 | 44026.5 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 2298.59 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.11 | 0.00944390 | 21.11 | 0.00944390 | 60.4669 | 989.81 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Electric | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | No | unknown | No | 33137.550 | 33137.550 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | Sensible | 33137.55 | 33137.55 | 1.0000 | 1.42962651 | 1.187797 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 33137.55 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.00 | 0.00885022 | 21.00 | 0.00885022 | 57.1085 | 996.03 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Electric | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | No | unknown | No | 34666.950 | 34666.950 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 04:20:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 04:20:00 | Sensible | 34666.95 | 33966.90 | 1.0000 | 1.42962651 | 1.187797 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 34666.95 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.00 | 0.00894659 | 21.00 | 0.00894659 | 57.7215 | 880.14 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Electric | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | No | unknown | No | 33070.242 | 33070.242 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | 12/21 00:10:00 | unknown | unknown | 12/21 00:10:00 | Sensible | 33070.24 | 10504.95 | 1.0000 | 0.44214105 | 0.367350 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 33070.24 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |||
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | No | unknown | No | 11437.612 | 11437.612 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 04:20:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 04:20:00 | Sensible | 11437.61 | 3592.17 | 1.0000 | 0.15119032 | 0.125616 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11437.61 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.00 | 0.00874411 | 21.00 | 0.00874411 | 56.4336 | 1014.97 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 113467.387 | -999.000 | 2.051317 | 0.00324515 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1036.7361 | 1004.8586 | 1.2036 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.46886833 | 4197.9300 | 999.8980 | 33.24709945 | 15.03 | 6.70 | 8.33 | 1162609.74 | 9.7597 | 9.759714 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:20:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:00:00 | Sensible | 113467.39 | 59031.63 | 1.0000 | 2.46895513 | 2.051317 | 35.20 | 25.83 | 0.01715815 | 79404.6 | 11.94 | 11.74 | 0.00850000 | 33447.0 | 3.24482186 | 6.70 | 15.03 | 8.33 | 2195.006 | 111272.38 | 35.20 | 0.01715815 | 25.83 | 2.05124512 | 99.9965 | 21.11 | 0.00869664 | 21.11 | 0.00869578 | 55.7470 | 167398.85 | 0.00 | 113576.05 | 59963.95 | 2.46895513 | 35.20 | 25.84 | 0.01715815 | 79404.6 | 11.77 | 11.72 | 0.00855094 | 33402.9 | |
FLR_3_DOAS HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 12429.563 | 12429.563 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.46886833 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | unknown | unknown | unknown | unknown | unknown | Sensible | 12429.56 | 12429.56 | 1.0000 | 0.74068654 | 0.615395 | 0.00 | -6.26 | 0.00000000 | 25.0 | 16.70 | 13.18 | 0.00800000 | 37036.7 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12429.56 | 0.00 | 0.00000000 | -6.26 | 2.05124512 | 333.3216 | 0.00 | 0.00000000 | -999.00 | -999.0 | -999.0000 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | ||
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 857363.510 | -999.000 | 21.983141 | 0.02452049 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1030.2094 | 1004.8586 | 1.2036 | VAV WITH REHEAT FAN | Fan:VariableVolume | 21.983141 | 26.45879793 | 4197.9300 | 999.8980 | 33.24709945 | 15.03 | 6.70 | 8.33 | 1162609.74 | 73.7447 | 73.744738 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:50:00 | Sensible | 857363.51 | 503599.62 | 1.0000 | 26.45879793 | 21.983141 | 29.95 | 22.21 | 0.01364718 | 64980.7 | 11.09 | 11.09 | 0.00850000 | 32577.0 | 24.51798652 | 6.70 | 15.03 | 8.33 | 46608.087 | 810755.42 | 35.20 | 0.01715815 | 25.83 | 11.66146000 | 53.0473 | 23.99 | 0.00966745 | 23.99 | 0.00963627 | 51.7780 | 301756.59 | 0.00 | 858331.50 | 504597.51 | 26.45879793 | 29.95 | 22.22 | 0.01364718 | 64980.7 | 11.43 | 11.37 | 0.00834654 | 32540.4 | |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 133202.625 | 133202.625 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | VAV WITH REHEAT FAN | Fan:VariableVolume | 21.983141 | 26.45879793 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | unknown | unknown | unknown | unknown | unknown | Sensible | 133202.63 | 133202.63 | 1.0000 | 7.93763938 | 6.594942 | 0.00 | -6.26 | 0.00000000 | 25.0 | 16.70 | 13.18 | 0.00800000 | 37036.7 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 133202.63 | 0.00 | 0.00000000 | -6.26 | 11.66146000 | 176.8243 | 0.00 | 0.00000000 | -999.00 | -999.0 | -999.0000 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:10
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | VAV WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000610 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LAUNDRY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CAFE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001448 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_3 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
KITCHEN_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003556 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 23.83 | 6095.50 | 0.00 |
RETAIL_1_FLR_1 | 5625.67 | 1600.00 | 0.00 |
RETAIL_2_FLR_1 | 2391.67 | 3864.83 | 0.00 |
MECH_FLR_1 | 1414.50 | 4684.00 | 0.00 |
STORAGE_FLR_1 | 952.50 | 5564.83 | 0.00 |
LAUNDRY_FLR_1 | 8187.67 | 1905.33 | 1897.67 |
CAFE_FLR_1 | 7429.00 | 572.83 | 104.33 |
LOBBY_FLR_1 | 4918.67 | 1433.67 | 0.00 |
ROOM_1_FLR_3 | 0.67 | 7600.50 | 0.50 |
ROOM_2_FLR_3 | 75.33 | 7609.17 | 53.83 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 40.83 | 8756.33 | 40.83 |
ROOM_5_FLR_3 | 0.50 | 7387.67 | 0.50 |
ROOM_6_FLR_3 | 126.50 | 7411.83 | 55.83 |
CORRIDOR_FLR_3 | 36.83 | 8189.33 | 0.00 |
ROOM_1_FLR_6 | 317.33 | 7044.33 | 4.33 |
ROOM_2_FLR_6 | 318.50 | 7072.50 | 109.67 |
ROOM_3_MULT9_FLR_6 | 130.00 | 7466.83 | 4.67 |
BANQUET_FLR_6 | 8479.83 | 22.83 | 0.00 |
DINING_FLR_6 | 8701.67 | 4.00 | 0.00 |
KITCHEN_FLR_6 | 8744.67 | 6592.33 | 6592.33 |
CORRIDOR_FLR_6 | 2576.33 | 3351.17 | 0.00 |
Facility | 8760.00 | 8760.00 | 6696.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 9.17 | 0.00 | 9.17 |
ROOM_2_FLR_3 | 0.00 | 6.17 | 0.00 | 6.17 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 6.67 | 0.00 | 6.67 |
ROOM_5_FLR_3 | 0.00 | 1.33 | 0.00 | 1.33 |
ROOM_6_FLR_3 | 0.00 | 10.00 | 0.00 | 10.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 28.67 | 0.00 | 28.67 |
ROOM_2_FLR_6 | 0.00 | 24.33 | 0.00 | 24.33 |
ROOM_3_MULT9_FLR_6 | 0.00 | 47.83 | 0.00 | 47.83 |
BANQUET_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 60.50 | 0.00 | 60.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:10
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.80 | 106.50 | 4826.41 | 1.140 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 2.260 | 0.058 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.28 | 12.54 | 307.76 | 1.677 | 0.019 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.820 | 0.022 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.776 | 0.022 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 20.199 | 0.062 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.58 | 142.30 | 748.35 | 3.305 | 0.046 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.14 | 422.44 | 5183.56 | 1.722 | 0.019 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.358 | 0.075 | 0.000 | 0.007 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.358 | 0.075 | 0.000 | 0.007 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.406 | 0.033 | 0.000 | 0.011 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.358 | 0.075 | 0.000 | 0.007 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.358 | 0.075 | 0.000 | 0.007 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 0.599 | 0.009 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.358 | 0.075 | 0.000 | 0.008 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.358 | 0.075 | 0.000 | 0.008 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.406 | 0.061 | 0.000 | 0.013 |
BANQUET_FLR_6 | 145.01 | 249.90 | 1010.89 | 4.481 | 0.022 | 0.000 | 0.000 |
DINING_FLR_6 | 145.01 | 249.90 | 1010.89 | 4.723 | 0.022 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 18.261 | 0.062 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 1.138 | 0.015 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.80 | 106.50 | 4826.41 | 0.765 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 1.666 | 0.001 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.28 | 12.54 | 307.76 | 1.166 | 0.000 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.540 | 0.000 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.515 | 0.000 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 13.869 | 0.001 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.58 | 142.30 | 748.35 | 2.872 | 0.001 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.14 | 422.44 | 5183.56 | 1.271 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 0.402 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.000 | 0.001 | 0.000 | 0.000 |
BANQUET_FLR_6 | 145.01 | 249.90 | 1010.89 | 3.828 | 0.000 | 0.000 | 0.000 |
DINING_FLR_6 | 145.01 | 249.90 | 1010.89 | 3.967 | 0.000 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 10.291 | 0.001 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 0.788 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:10
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | VAV WITH REHEAT | 61.80 | 106.50 | 4826.41 | 1978.83 | 0.0000 | 0.854 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 6.28 | 10.83 | 265.76 | 67.07 | 0.0000 | 0.079 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 7.28 | 12.54 | 307.76 | 77.67 | 0.0000 | 0.092 |
MECH_FLR_1 | VAV WITH REHEAT | 1.54 | 2.65 | 650.80 | 164.24 | 0.0000 | 0.000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 1.18 | 2.04 | 375.47 | 94.76 | 0.0000 | 0.058 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 4.87 | 8.40 | 309.22 | 78.04 | 0.0000 | 0.000 |
CAFE_FLR_1 | VAV WITH REHEAT | 82.58 | 142.30 | 748.35 | 188.86 | 0.0000 | 0.676 |
LOBBY_FLR_1 | VAV WITH REHEAT | 245.14 | 422.44 | 5183.56 | 1308.19 | 0.0000 | 1.894 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 1.50 | 74.75 | 24.52 | 0.0000 | 0.837 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.837 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 12.16 | 20.96 | 1186.91 | 389.40 | 0.0000 | 0.475 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.015 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.015 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.099 |
BANQUET_FLR_6 | VAV WITH REHEAT | 145.01 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
DINING_FLR_6 | VAV WITH REHEAT | 145.01 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 12.90 | 22.24 | 314.87 | 103.30 | 0.0000 | 0.367 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 12.87 | 22.18 | 1256.16 | 412.12 | 0.0000 | 0.126 |
Total Facility | 873.39 | 1604.23 | 35184.81 | 11345.29 | 0.0000 | 137.584 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 46867012.23 | 0.00 | 46867012.23 | 0.00 | 46867012.23 | 26946214.98 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_1_FLR_1 | 5109539.29 | 0.00 | 5109539.29 | 131239.90 | 5240779.19 | 2498216.28 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_2_FLR_1 | 4394149.98 | 0.00 | 4394149.98 | 50658.77 | 4444808.74 | 2892943.94 | 0.00 | 0.00 | 8760.00 | 0.00 |
MECH_FLR_1 | 4543086.21 | 0.00 | 4543086.21 | 119727.23 | 4662813.43 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
STORAGE_FLR_1 | 2482654.82 | 0.00 | 2482654.82 | 69076.01 | 2551730.84 | 1821682.01 | 73.39 | 59.61 | 8627.00 | 0.00 |
LAUNDRY_FLR_1 | 53417214.22 | 0.00 | 53417214.22 | 163481.41 | 53580695.64 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
CAFE_FLR_1 | 20995577.44 | 0.00 | 20995577.44 | 290113.22 | 21285690.65 | 21330615.53 | 2324.95 | 5979.26 | 455.79 | 0.00 |
LOBBY_FLR_1 | 75848263.06 | 0.00 | 75848263.06 | 828919.73 | 76677182.79 | 59728886.00 | 6.22 | 18.39 | 8735.39 | 0.00 |
ROOM_1_FLR_3 | 1460156.71 | 7581.43 | 1467738.14 | 76175.01 | 1543913.15 | 1946875.62 | 2190.00 | 6378.33 | 191.67 | 0.00 |
ROOM_2_FLR_3 | 1459985.63 | 7007.03 | 1466992.67 | 76169.20 | 1543161.86 | 1946647.51 | 2190.00 | 6378.33 | 191.67 | 0.00 |
ROOM_3_MULT19_FLR_3 | 1099911.97 | 0.00 | 1099911.97 | 21253.68 | 1121165.65 | 26397887.27 | 8395.00 | 365.00 | 0.00 | 365.00 |
ROOM_4_MULT19_FLR_3 | 19803829.30 | 6951.83 | 19810781.13 | 21259.49 | 19832040.62 | 26405105.73 | 2190.00 | 6471.03 | 98.97 | 0.00 |
ROOM_5_FLR_3 | 1460156.71 | 7581.11 | 1467737.82 | 76175.01 | 1543912.83 | 1946875.62 | 2190.00 | 6378.33 | 191.67 | 0.00 |
ROOM_6_FLR_3 | 1459985.63 | 7198.80 | 1467184.44 | 76169.20 | 1543353.64 | 1946647.51 | 2190.00 | 6378.39 | 191.61 | 0.00 |
CORRIDOR_FLR_3 | 24201080.42 | 0.00 | 24201080.42 | 92110.91 | 24293191.33 | 14972100.18 | 0.00 | 0.00 | 8760.00 | 0.00 |
ROOM_1_FLR_6 | 365039.18 | 8488.46 | 373527.64 | 76190.07 | 449717.71 | 486718.90 | 2187.89 | 6374.07 | 198.04 | 0.00 |
ROOM_2_FLR_6 | 364996.41 | 8307.16 | 373303.57 | 76184.26 | 449487.83 | 486661.88 | 2186.00 | 6374.00 | 200.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 2345190.31 | 8486.65 | 2353676.96 | 38981.51 | 2392658.47 | 3126920.42 | 2190.00 | 6374.00 | 196.00 | 0.00 |
BANQUET_FLR_6 | 38426607.98 | 0.00 | 38426607.98 | 186037.01 | 38612644.98 | 37458366.31 | 4415.49 | 497.86 | 3846.65 | 0.00 |
DINING_FLR_6 | 40506574.38 | 0.00 | 40506574.38 | 186037.01 | 40692611.38 | 37458366.31 | 146.39 | 132.92 | 8480.69 | 0.00 |
KITCHEN_FLR_6 | 48806965.70 | 0.00 | 48806965.70 | 166546.25 | 48973511.96 | 11584760.86 | 0.00 | 0.00 | 8760.00 | 0.00 |
CORRIDOR_FLR_6 | 12169109.36 | 0.00 | 12169109.36 | 163006.18 | 12332115.54 | 3961413.96 | 0.00 | 0.00 | 8760.00 | 0.00 |
Total Facility | 0.21E+10 | 738988.13 | 0.21E+10 | 7676249.20 | 0.21E+10 | 0.43E+10 | 8760.00 | 8568.12 | 8760.00 | 365.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 1.4861 | 0.0000 | 1.4861 | 0.0000 | 1.4861 | 0.8545 | 0.00 | 0.00 | 8760.00 |
RETAIL_1_FLR_1 | 0.1620 | 0.0000 | 0.1620 | 0.0042 | 0.1662 | 0.0792 | 0.00 | 0.00 | 8760.00 |
RETAIL_2_FLR_1 | 0.1393 | 0.0000 | 0.1393 | 0.0016 | 0.1409 | 0.0917 | 0.00 | 0.00 | 8760.00 |
MECH_FLR_1 | 0.1441 | 0.0000 | 0.1441 | 0.0038 | 0.1479 | 0.0000 | 0.00 | 0.00 | 8760.00 |
STORAGE_FLR_1 | 0.0787 | 0.0000 | 0.0787 | 0.0022 | 0.0809 | 0.0578 | 73.39 | 59.61 | 8627.00 |
LAUNDRY_FLR_1 | 1.6938 | 0.0000 | 1.6938 | 0.0052 | 1.6990 | 0.0000 | 0.00 | 0.00 | 8760.00 |
CAFE_FLR_1 | 0.6658 | 0.0000 | 0.6658 | 0.0092 | 0.6750 | 0.6764 | 2324.95 | 5979.26 | 455.79 |
LOBBY_FLR_1 | 2.4051 | 0.0000 | 2.4051 | 0.0263 | 2.4314 | 1.8940 | 6.22 | 18.39 | 8735.39 |
ROOM_1_FLR_3 | 0.0463 | 0.0002 | 0.0465 | 0.0024 | 0.0490 | 0.0617 | 2190.00 | 6378.33 | 191.67 |
ROOM_2_FLR_3 | 0.0463 | 0.0002 | 0.0465 | 0.0024 | 0.0489 | 0.0617 | 2190.00 | 6378.33 | 191.67 |
ROOM_4_MULT19_FLR_3 | 0.6280 | 0.0002 | 0.6282 | 0.0007 | 0.6289 | 0.8373 | 2190.00 | 6471.03 | 98.97 |
ROOM_5_FLR_3 | 0.0463 | 0.0002 | 0.0465 | 0.0024 | 0.0490 | 0.0617 | 2190.00 | 6378.33 | 191.67 |
ROOM_6_FLR_3 | 0.0463 | 0.0002 | 0.0465 | 0.0024 | 0.0489 | 0.0617 | 2190.00 | 6378.39 | 191.61 |
CORRIDOR_FLR_3 | 0.7674 | 0.0000 | 0.7674 | 0.0029 | 0.7703 | 0.4748 | 0.00 | 0.00 | 8760.00 |
ROOM_1_FLR_6 | 0.0116 | 0.0003 | 0.0118 | 0.0024 | 0.0143 | 0.0154 | 2187.89 | 6374.07 | 198.04 |
ROOM_2_FLR_6 | 0.0116 | 0.0003 | 0.0118 | 0.0024 | 0.0143 | 0.0154 | 2186.00 | 6374.00 | 200.00 |
ROOM_3_MULT9_FLR_6 | 0.0744 | 0.0003 | 0.0746 | 0.0012 | 0.0759 | 0.0992 | 2190.00 | 6374.00 | 196.00 |
BANQUET_FLR_6 | 1.2185 | 0.0000 | 1.2185 | 0.0059 | 1.2244 | 1.1878 | 4415.49 | 497.86 | 3846.65 |
DINING_FLR_6 | 1.2845 | 0.0000 | 1.2845 | 0.0059 | 1.2904 | 1.1878 | 146.39 | 132.92 | 8480.69 |
KITCHEN_FLR_6 | 1.5477 | 0.0000 | 1.5477 | 0.0053 | 1.5529 | 0.3674 | 0.00 | 0.00 | 8760.00 |
CORRIDOR_FLR_6 | 0.3859 | 0.0000 | 0.3859 | 0.0052 | 0.3910 | 0.1256 | 0.00 | 0.00 | 8760.00 |
Total Facility | 63.4405 | 0.0234 | 63.4639 | 0.1922 | 63.6561 | 73.9670 | 8760.00 | 8568.12 | 8760.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
FLR_3_DOAS | 43197387.25 | 61602.48 | 43258989.72 | 64690340.46 | 8759.83 | 0.17 | 0.00 | 0.00 |
VAV WITH REHEAT | 0.55E+09 | 0.00 | 0.55E+09 | 0.22E+09 | 0.00 | 0.00 | 8760.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
FLR_3_DOAS | 1.3698 | 0.0020 | 1.3717 | 2.0513 | 8759.83 | 0.17 | 0.00 |
VAV WITH REHEAT | 17.3532 | 0.0000 | 17.3532 | 6.9969 | 0.00 | 0.00 | 8760.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
FLR_3_DOAS | 0.00 | 0.00 | 0.00 | 0.00 | 6935.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
VAV WITH REHEAT | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
FLR_3_DOAS | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.7302 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
VAV WITH REHEAT | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 17.3532 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:10
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1269 |
Defaulted Fields | 1144 |
Fields with Defaults | 3760 |
Autosized Fields | 294 |
Autosizable Fields | 344 |
Autocalculated Fields | 279 |
Autocalculatable Fields | 538 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:21:10
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 8740.36 | 146138.57 | 23-JAN-05:00 | 455161.34 | 13-JUN-18:20 |
Electricity:Building | 2447.99 | 31358.38 | 25-NOV-06:00 | 151313.73 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 304.40 | 3493.55 | 02-JAN-02:10 | 22822.84 | 02-JAN-20:10 |
Electricity:SpaceType:GENERAL | 2440.90 | 31217.23 | 25-NOV-06:00 | 151072.40 | 02-JAN-20:10 |
InteriorLights:Electricity | 782.72 | 7015.26 | 25-NOV-06:00 | 64632.59 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 161.29 | 1465.65 | 02-JAN-02:10 | 13190.31 | 02-JAN-20:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 782.72 | 7015.26 | 25-NOV-06:00 | 64632.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 782.72 | 7015.26 | 25-NOV-06:00 | 64632.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 161.29 | 1465.65 | 02-JAN-02:10 | 13190.31 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 782.72 | 7015.26 | 25-NOV-06:00 | 64632.59 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 17.49 | 210.74 | 02-JAN-02:10 | 1283.20 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 7.31 | 66.40 | 02-JAN-02:10 | 597.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 7.31 | 66.40 | 02-JAN-02:10 | 597.59 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 20.26 | 244.03 | 02-JAN-02:10 | 1485.95 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 8.46 | 76.89 | 02-JAN-02:10 | 692.02 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 8.46 | 76.89 | 02-JAN-02:10 | 692.02 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 20.84 | 252.75 | 02-JAN-02:10 | 1523.62 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.37 | 76.02 | 02-JAN-02:10 | 684.18 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.37 | 76.02 | 02-JAN-02:10 | 684.18 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 6.68 | 78.96 | 02-JAN-02:10 | 493.99 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 3.08 | 27.98 | 02-JAN-02:10 | 251.84 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 3.08 | 27.98 | 02-JAN-02:10 | 251.84 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 71.91 | 998.82 | 02-JAN-02:10 | 4897.88 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 3.98 | 36.12 | 02-JAN-02:10 | 325.08 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 3.98 | 36.12 | 02-JAN-02:10 | 325.08 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 28.69 | 318.54 | 25-NOV-06:00 | 2666.80 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 14.35 | 83.19 | 01-JAN-13:10 | 1701.53 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 | 14.35 | 83.19 | 01-JAN-13:10 | 1701.53 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 259.18 | 3142.86 | 25-NOV-06:00 | 19534.01 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 110.18 | 1031.45 | 25-NOV-06:00 | 9504.80 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 110.18 | 1031.45 | 25-NOV-06:00 | 9504.80 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 19.72 | 257.38 | 01-JAN-02:10 | 1438.51 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 19.72 | 257.35 | 01-JAN-02:10 | 1438.34 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 305.38 | 4267.82 | 01-JAN-02:10 | 22404.45 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 110.39 | 934.58 | 01-JAN-02:10 | 8496.21 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 110.39 | 934.58 | 01-JAN-02:10 | 8496.21 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 305.47 | 4268.99 | 01-JAN-02:10 | 22410.58 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 110.42 | 934.84 | 01-JAN-02:10 | 8498.53 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 110.42 | 934.84 | 01-JAN-02:10 | 8498.53 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 19.72 | 257.38 | 01-JAN-02:10 | 1438.51 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 19.72 | 257.35 | 01-JAN-02:10 | 1438.34 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 4.93 | 64.34 | 01-JAN-02:10 | 359.63 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 2.31 | 19.57 | 01-JAN-02:10 | 177.88 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 2.31 | 19.57 | 01-JAN-02:10 | 177.88 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 4.93 | 64.34 | 01-JAN-02:10 | 359.59 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 2.31 | 19.56 | 01-JAN-02:10 | 177.86 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 2.31 | 19.56 | 01-JAN-02:10 | 177.86 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 36.17 | 505.54 | 01-JAN-02:10 | 2653.88 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 13.08 | 110.70 | 01-JAN-02:10 | 1006.40 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 13.08 | 110.70 | 01-JAN-02:10 | 1006.40 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 206.74 | 2559.17 | 25-NOV-06:00 | 9735.93 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 30.88 | 309.87 | 25-NOV-06:00 | 2988.03 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 30.88 | 309.87 | 25-NOV-06:00 | 2988.03 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 206.74 | 2559.17 | 25-NOV-06:00 | 9735.93 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 30.88 | 309.87 | 25-NOV-06:00 | 2988.03 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 | 30.88 | 309.87 | 25-NOV-06:00 | 2988.03 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 453.81 | 6249.79 | 02-JAN-02:10 | 18934.39 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 12.97 | 117.87 | 02-JAN-02:10 | 1060.81 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 12.97 | 117.87 | 02-JAN-02:10 | 1060.81 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1658.18 | 24201.97 | 02-JAN-02:10 | 89171.45 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 1658.18 | 24201.97 | 02-JAN-02:10 | 89171.45 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 433.74 | 5990.78 | 01-JAN-00:10 | 16487.34 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 410.33 | 5248.28 | 01-JAN-00:10 | 15744.84 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
Refrigeration:Electricity | 62.43 | 1173.78 | 15-JUN-22:30 | 3257.13 | 17-NOV-07:50 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
Electricity:Plant | 4466.67 | 62514.15 | 23-JAN-06:20 | 258895.70 | 13-JUN-15:20 |
LowTempRefrigeration:Refrigeration:Electricity | 20.40 | 0.00 | 01-JAN-11:10 | 1892.77 | 07-MAY-10:50 |
MedTempRefrigeration:Refrigeration:Electricity | 34.95 | 1006.15 | 23-OCT-03:10 | 1191.88 | 27-DEC-09:30 |
Fans:Electricity | 498.28 | 11291.08 | 23-OCT-07:10 | 28792.11 | 13-JUN-18:20 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 839.53 | 20502.15 | 20-AUG-10:10 | 39849.90 | 12-JUN-19:10 |
ExteriorEquipment:Electricity | 813.77 | 9999.82 | 02-JAN-02:20 | 49607.07 | 13-MAR-06:20 |
Transformer:ExteriorEquipment:Electricity | 21.77 | 381.02 | 02-JAN-02:20 | 1291.59 | 02-JAN-21:10 |
ElectricityPurchased:Facility | 8740.36 | 146138.57 | 23-JAN-05:00 | 455161.34 | 13-JUN-18:20 |
ElectricityPurchased:Plant | 8740.36 | 146138.57 | 23-JAN-05:00 | 455161.34 | 13-JUN-18:20 |
Cogeneration:ElectricityPurchased | 8740.36 | 146138.57 | 23-JAN-05:00 | 455161.34 | 13-JUN-18:20 |
General:Cogeneration:ElectricityPurchased | 8740.36 | 146138.57 | 23-JAN-05:00 | 455161.34 | 13-JUN-18:20 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 8740.36 | 146138.57 | 23-JAN-05:00 | 455161.34 | 13-JUN-18:20 |
ElectricityNet:Plant | 8740.36 | 146138.57 | 23-JAN-05:00 | 455161.34 | 13-JUN-18:20 |
Cogeneration:ElectricityNet | 8740.36 | 146138.57 | 23-JAN-05:00 | 455161.34 | 13-JUN-18:20 |
General:Cogeneration:ElectricityNet | 8740.36 | 146138.57 | 23-JAN-05:00 | 455161.34 | 13-JUN-18:20 |
Heating:Electricity | 16.80 | 0.00 | 01-JAN-00:10 | 5851.03 | 23-OCT-04:00 |
General:Heating:Electricity | 16.80 | 0.00 | 01-JAN-00:10 | 5851.03 | 23-OCT-04:00 |
General:Fans:Electricity | 498.28 | 11291.08 | 23-OCT-07:10 | 28792.11 | 13-JUN-18:20 |
ExteriorLights:Electricity | 194.17 | 0.00 | 01-JAN-06:20 | 12338.45 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 194.17 | 0.00 | 01-JAN-06:20 | 12338.45 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 789.09 | 9600.00 | 01-JAN-00:10 | 48128.80 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 2.91 | 18.80 | 01-JAN-00:10 | 188.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 302.67 | 8417.13 | 01-JAN-08:40 | 9938.94 | 07-JAN-09:20 |
General:HeatRecovery:Electricity | 302.67 | 8417.13 | 01-JAN-08:40 | 9938.94 | 07-JAN-09:20 |
WaterSystems:Electricity | 94.79 | 1222.61 | 17-JUN-00:10 | 4751.13 | 25-MAY-19:00 |
Water Heater:WaterSystems:Electricity | 94.79 | 1222.61 | 17-JUN-00:10 | 4751.13 | 25-MAY-19:00 |
Cooling:Electricity | 4172.43 | 52667.75 | 23-JAN-06:20 | 249536.43 | 13-JUN-15:20 |
General:Cooling:Electricity | 4172.43 | 52667.75 | 23-JAN-06:20 | 249536.43 | 13-JUN-15:20 |
Pumps:Electricity | 144.11 | 3968.05 | 23-JAN-06:20 | 5754.05 | 31-MAY-20:20 |
General:Pumps:Electricity | 144.11 | 3968.05 | 23-JAN-06:20 | 5754.05 | 31-MAY-20:20 |
WIRED_LTG_ELECTRICITY | 27.55 | 0.00 | 01-JAN-00:10 | 2275.07 | 02-JAN-20:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 3730.99 | 21449.58 | 22-JUL-01:20 | 281422.66 | 11-JAN-19:00 |
NaturalGas:Building | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Laundry:InteriorEquipment:NaturalGas | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
NaturalGas:Plant | 1942.15 | 8087.68 | 22-JUL-01:20 | 179827.61 | 12-JAN-21:30 |
WaterSystems:NaturalGas | 1942.15 | 8087.68 | 22-JUL-01:20 | 179827.61 | 12-JAN-21:30 |
Water Heater:WaterSystems:NaturalGas | 1942.15 | 8087.68 | 22-JUL-01:20 | 179827.61 | 12-JAN-21:30 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 15729.85 | 232250.79 | 23-JAN-06:20 | 764098.79 | 13-JUN-18:10 |
PlantLoopCoolingDemand:HVAC | 15729.85 | 232250.79 | 23-JAN-06:20 | 764098.79 | 13-JUN-18:10 |
CoolingCoils:PlantLoopCoolingDemand | 15729.85 | 232250.79 | 23-JAN-06:20 | 764098.79 | 13-JUN-18:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 17-JUL-21:00 |
Water:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 17-JUL-21:00 |
WaterSystems:Water | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 17-JUL-21:00 |
Water Heater:WaterSystems:Water | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:20 |
MainsWater:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 17-JUL-21:00 |
MainsWater:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 17-JUL-21:00 |
WaterSystems:MainsWater | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 17-JUL-21:00 |
Water Heater:WaterSystems:MainsWater | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:20 |
WaterUse:WaterSystems:Water | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-07:10 |
WaterUse:WaterSystems:MainsWater | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-07:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 66506.32 | 962739.44 | 23-JAN-06:20 | 3244873.88 | 13-JUN-18:10 |
EnergyTransfer:Building | 7377.66 | 149965.12 | 20-AUG-13:10 | 361650.57 | 12-JUN-18:10 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 781.94 | 14290.80 | 23-OCT-03:00 | 35690.42 | 07-MAY-10:50 |
Refrigeration:EnergyTransfer | 186.86 | 4361.70 | 15-JUN-22:20 | 10335.60 | 08-DEC-08:20 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 93.43 | 2180.85 | 15-JUN-22:20 | 5167.80 | 08-DEC-08:20 |
General:Refrigeration:EnergyTransfer | 93.43 | 2180.85 | 15-JUN-22:20 | 5167.80 | 08-DEC-08:20 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 93.43 | 2180.85 | 15-JUN-22:20 | 5167.80 | 08-DEC-08:20 |
EnergyTransfer:Plant | 36444.15 | 545904.92 | 23-JAN-06:20 | 1794016.91 | 13-JUN-18:10 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 21.71 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 71.72 | 1968.45 | 23-OCT-03:10 | 2525.64 | 27-DEC-09:30 |
EnergyTransfer:Zone:BASEMENT | 627.67 | 18046.72 | 01-JAN-16:00 | 22201.02 | 15-JUN-21:00 |
Heating:EnergyTransfer | 0.21 | 0.00 | 01-JAN-00:10 | 2617.98 | 23-NOV-16:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 0.21 | 0.00 | 01-JAN-00:10 | 2617.98 | 23-NOV-16:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 7284.01 | 147004.86 | 20-AUG-13:10 | 358034.94 | 12-JUN-18:10 |
Cooling:EnergyTransfer:Zone:BASEMENT | 627.67 | 18046.72 | 01-JAN-16:00 | 22201.02 | 15-JUN-21:00 |
General:Cooling:EnergyTransfer | 7284.01 | 147004.86 | 20-AUG-13:10 | 358034.94 | 12-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 627.67 | 18046.72 | 01-JAN-16:00 | 22201.02 | 15-JUN-21:00 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 70.31 | 1636.76 | 20-AUG-17:00 | 3774.52 | 05-JAN-15:10 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 70.31 | 1636.76 | 20-AUG-17:00 | 3774.52 | 05-JAN-15:10 |
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 70.31 | 1636.76 | 20-AUG-17:00 | 3774.52 | 05-JAN-15:10 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 58.52 | 1506.46 | 20-AUG-15:00 | 2735.49 | 13-JUN-20:10 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 58.52 | 1506.46 | 20-AUG-15:00 | 2735.49 | 13-JUN-20:10 |
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 58.52 | 1506.46 | 20-AUG-15:00 | 2735.49 | 13-JUN-20:10 |
EnergyTransfer:Zone:MECH_FLR_1 | 61.44 | 1652.60 | 21-AUG-10:40 | 3721.40 | 13-JUN-19:30 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 61.44 | 1652.60 | 21-AUG-10:40 | 3721.40 | 13-JUN-19:30 |
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 61.44 | 1652.60 | 21-AUG-10:40 | 3721.40 | 13-JUN-19:30 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 33.30 | 911.40 | 20-AUG-16:00 | 1802.75 | 13-JUN-19:30 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 33.30 | 911.40 | 20-AUG-16:00 | 1802.75 | 13-JUN-19:30 |
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 33.30 | 911.40 | 20-AUG-16:00 | 1802.75 | 13-JUN-19:30 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 635.78 | 11062.65 | 23-OCT-04:00 | 36916.26 | 05-MAY-20:00 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 635.78 | 11062.65 | 23-OCT-04:00 | 36916.26 | 05-MAY-20:00 |
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 635.78 | 11062.65 | 23-OCT-04:00 | 36916.26 | 05-MAY-20:00 |
EnergyTransfer:Zone:CAFE_FLR_1 | 292.89 | 6457.59 | 20-AUG-15:00 | 12923.47 | 08-DEC-22:10 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 292.89 | 6457.59 | 20-AUG-15:00 | 12923.47 | 08-DEC-22:10 |
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 292.89 | 6457.59 | 20-AUG-15:00 | 12923.47 | 08-DEC-22:10 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 1038.40 | 26589.99 | 20-AUG-15:00 | 47549.67 | 13-JUN-21:10 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 1038.40 | 26589.99 | 20-AUG-15:00 | 47549.67 | 13-JUN-21:10 |
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 1038.40 | 26589.99 | 20-AUG-15:00 | 47549.67 | 13-JUN-21:10 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 118.07 | 0.00 | 01-JAN-08:10 | 9811.63 | 06-MAY-15:20 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 0.03 | 0.00 | 01-JAN-00:10 | 283.57 | 23-SEP-08:10 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 0.03 | 0.00 | 01-JAN-00:10 | 283.57 | 23-SEP-08:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 118.04 | 0.00 | 01-JAN-08:10 | 9811.63 | 06-MAY-15:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 118.04 | 0.00 | 01-JAN-08:10 | 9811.63 | 06-MAY-15:20 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 113.11 | 0.00 | 01-JAN-08:10 | 10011.35 | 13-JUN-15:20 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 0.03 | 0.00 | 01-JAN-00:10 | 290.10 | 28-NOV-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 0.03 | 0.00 | 01-JAN-00:10 | 290.10 | 28-NOV-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 113.07 | 0.00 | 01-JAN-08:10 | 10011.35 | 13-JUN-15:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 113.07 | 0.00 | 01-JAN-08:10 | 10011.35 | 13-JUN-15:20 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 585.01 | 4845.02 | 21-AUG-04:00 | 38353.51 | 07-DEC-13:50 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 585.01 | 4845.02 | 21-AUG-04:00 | 38353.51 | 07-DEC-13:50 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 585.01 | 4845.02 | 21-AUG-04:00 | 38353.51 | 07-DEC-13:50 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 889.11 | 0.00 | 01-JAN-08:10 | 75563.53 | 13-JUN-15:20 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 0.12 | 0.00 | 01-JAN-00:10 | 2617.98 | 23-NOV-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 0.12 | 0.00 | 01-JAN-00:10 | 2617.98 | 23-NOV-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 888.98 | 0.00 | 01-JAN-08:10 | 75563.53 | 13-JUN-15:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 888.98 | 0.00 | 01-JAN-08:10 | 75563.53 | 13-JUN-15:20 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 118.35 | 0.00 | 01-JAN-08:10 | 8418.32 | 06-MAY-15:20 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 180.41 | 23-OCT-08:10 |
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 180.41 | 23-OCT-08:10 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 118.35 | 0.00 | 01-JAN-08:10 | 8418.32 | 06-MAY-15:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 118.35 | 0.00 | 01-JAN-08:10 | 8418.32 | 06-MAY-15:20 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 113.09 | 0.00 | 01-JAN-08:10 | 8763.27 | 24-FEB-09:30 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 204.04 | 26-OCT-18:10 |
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 204.04 | 26-OCT-18:10 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 113.09 | 0.00 | 01-JAN-08:10 | 8763.27 | 24-FEB-09:30 |
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 113.09 | 0.00 | 01-JAN-08:10 | 8763.27 | 24-FEB-09:30 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 321.16 | 9130.06 | 21-AUG-10:40 | 12486.53 | 13-JUN-20:10 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 321.16 | 9130.06 | 21-AUG-10:40 | 12486.53 | 13-JUN-20:10 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 321.16 | 9130.06 | 21-AUG-10:40 | 12486.53 | 13-JUN-20:10 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 30.40 | 0.00 | 01-JAN-08:10 | 2885.12 | 22-FEB-16:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 0.01 | 0.00 | 01-JAN-00:10 | 73.92 | 17-DEC-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 0.01 | 0.00 | 01-JAN-00:10 | 73.92 | 17-DEC-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 30.39 | 0.00 | 01-JAN-08:10 | 2885.12 | 22-FEB-16:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 30.39 | 0.00 | 01-JAN-08:10 | 2885.12 | 22-FEB-16:10 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 29.19 | 0.00 | 01-JAN-08:10 | 2925.63 | 13-JUN-15:20 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 0.01 | 0.00 | 01-JAN-00:10 | 73.43 | 23-SEP-08:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 0.01 | 0.00 | 01-JAN-00:10 | 73.43 | 23-SEP-08:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 29.18 | 0.00 | 01-JAN-08:10 | 2925.63 | 13-JUN-15:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 29.18 | 0.00 | 01-JAN-08:10 | 2925.63 | 13-JUN-15:20 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 163.79 | 0.00 | 01-JAN-08:10 | 12824.84 | 13-DEC-16:10 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 199.48 | 27-NOV-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 199.48 | 27-NOV-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 163.79 | 0.00 | 01-JAN-08:10 | 12824.84 | 13-DEC-16:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 163.79 | 0.00 | 01-JAN-08:10 | 12824.84 | 13-DEC-16:10 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 549.08 | 13215.61 | 20-AUG-15:00 | 25406.51 | 12-JUN-21:10 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 549.08 | 13215.61 | 20-AUG-15:00 | 25406.51 | 12-JUN-21:10 |
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 549.08 | 13215.61 | 20-AUG-15:00 | 25406.51 | 12-JUN-21:10 |
EnergyTransfer:Zone:DINING_FLR_6 | 581.17 | 14150.68 | 03-MAR-14:50 | 26641.76 | 12-JUN-21:10 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 581.17 | 14150.68 | 03-MAR-14:50 | 26641.76 | 12-JUN-21:10 |
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 581.17 | 14150.68 | 03-MAR-14:50 | 26641.76 | 12-JUN-21:10 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 688.51 | 12072.70 | 23-OCT-03:00 | 30621.07 | 07-MAY-10:50 |
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 688.51 | 12072.70 | 23-OCT-03:00 | 30621.07 | 07-MAY-10:50 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 165.89 | 4355.77 | 21-AUG-06:30 | 7406.80 | 13-JUN-15:40 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 165.89 | 4355.77 | 21-AUG-06:30 | 7406.80 | 13-JUN-15:40 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 165.89 | 4355.77 | 21-AUG-06:30 | 7406.80 | 13-JUN-15:40 |
PlantLoopHeatingDemand:Facility | 499.92 | 6542.70 | 14-JUL-00:20 | 34468.21 | 12-JAN-07:10 |
PlantLoopHeatingDemand:Plant | 499.92 | 6542.70 | 14-JUL-00:20 | 34468.21 | 12-JAN-07:10 |
WaterSystems:PlantLoopHeatingDemand | 499.92 | 6542.70 | 14-JUL-00:20 | 34468.21 | 12-JAN-07:10 |
General:WaterSystems:PlantLoopHeatingDemand | 499.92 | 6542.70 | 14-JUL-00:20 | 34468.21 | 12-JAN-07:10 |
EnergyTransfer:HVAC | 22684.51 | 232250.79 | 23-JAN-06:20 | 1177099.88 | 15-JUN-10:00 |
HeatingCoils:EnergyTransfer | 16.80 | 0.00 | 01-JAN-00:10 | 5851.03 | 23-OCT-04:00 |
CoolingCoils:EnergyTransfer | 15729.85 | 232250.79 | 23-JAN-06:20 | 764098.79 | 13-JUN-18:10 |
HeatRecoveryForHeating:EnergyTransfer | 0.01 | 0.00 | 01-JAN-00:10 | 19855.92 | 10-FEB-01:00 |
HeatRecoveryForCooling:EnergyTransfer | 6937.84 | 0.00 | 08-JAN-06:50 | 453144.04 | 15-JUN-10:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 499.92 | 6542.70 | 14-JUL-00:20 | 34468.21 | 12-JAN-07:10 |
WaterUse:WaterSystems:EnergyTransfer | 499.92 | 6542.70 | 14-JUL-00:20 | 34468.21 | 12-JAN-07:10 |
Chillers:EnergyTransfer | 15839.19 | 231631.37 | 23-JAN-06:20 | 768141.14 | 13-JUN-18:10 |
HeatRejection:EnergyTransfer | 20011.61 | 284299.12 | 23-JAN-06:20 | 1002347.14 | 13-JUN-18:10 |
General:HeatRejection:EnergyTransfer | 20011.61 | 284299.12 | 23-JAN-06:20 | 1002347.14 | 13-JUN-18:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:10
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -627.670 | 0.000 | 0.000 | 140.192 | 161.294 | 143.105 | 0.000 | 0.000 | 0.000 | 183.078 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 0.000 | -70.312 | 0.000 | 0.000 | 14.156 | 7.307 | 10.186 | 17.914 | 0.000 | 0.688 | 20.774 | 0.000 | -0.706 | 0.000 | -0.007 | 0.000 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.000 | -58.519 | 0.000 | 0.000 | 16.510 | 8.462 | 11.795 | 0.000 | 0.000 | 0.285 | 21.471 | 0.000 | 0.000 | 0.000 | -0.003 | 0.000 |
MECH_FLR_1 | 0.000 | 0.000 | 0.000 | -61.437 | 0.000 | 0.000 | 3.480 | 8.366 | 12.471 | 0.000 | 0.000 | 0.649 | 36.477 | 0.000 | 0.000 | 0.000 | -0.006 | 0.000 |
STORAGE_FLR_1 | 0.000 | 0.000 | 0.000 | -33.304 | 0.000 | 0.000 | 2.691 | 3.079 | 3.598 | 0.000 | 0.000 | 0.380 | 23.559 | 0.000 | 0.000 | 0.000 | -0.003 | 0.000 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.000 | -635.783 | 0.000 | 0.000 | 11.770 | 3.975 | 658.131 | 0.000 | 0.000 | 1.117 | 0.001 | 0.000 | 0.000 | 0.000 | -0.004 | -39.206 |
CAFE_FLR_1 | 0.000 | 0.000 | 0.000 | -292.888 | 0.000 | 0.000 | 182.251 | 14.351 | 14.341 | 50.764 | 0.000 | 1.494 | 31.849 | 0.000 | -2.129 | 0.000 | -0.032 | 0.000 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.000 | -1038.401 | 0.000 | 0.000 | 545.552 | 110.179 | 148.998 | 68.622 | 0.000 | 4.420 | 163.105 | 0.000 | -2.393 | 0.000 | -0.081 | 0.000 |
ROOM_1_FLR_3 | 0.051 | -102.928 | 0.000 | -15.130 | 0.000 | 0.000 | 9.619 | 9.244 | 10.478 | 50.861 | 0.000 | 2.268 | 35.895 | 0.000 | -0.348 | 0.000 | -0.009 | 0.000 |
ROOM_2_FLR_3 | 0.054 | -97.821 | 0.000 | -15.266 | 0.000 | 0.000 | 9.588 | 9.243 | 10.477 | 47.791 | 0.000 | 2.202 | 34.132 | 0.000 | -0.370 | 0.000 | -0.031 | 0.000 |
ROOM_3_MULT19_FLR_3 | 0.000 | -566.466 | 0.000 | -18.540 | 0.000 | 0.000 | 0.000 | 110.385 | 194.997 | 188.475 | 0.000 | 3.402 | 117.312 | 0.000 | -27.877 | 0.000 | -1.688 | 0.000 |
ROOM_4_MULT19_FLR_3 | 0.447 | -682.739 | 0.000 | -206.521 | 0.000 | 0.000 | 182.459 | 110.415 | 195.050 | 213.398 | 0.000 | 12.057 | 177.084 | 0.000 | -1.314 | 0.000 | -0.336 | -0.016 |
ROOM_5_FLR_3 | 0.001 | -103.210 | 0.000 | -15.133 | 0.000 | 0.000 | 9.618 | 9.244 | 10.478 | 51.019 | 0.000 | 2.265 | 36.064 | 0.000 | -0.336 | 0.000 | -0.009 | 0.000 |
ROOM_6_FLR_3 | 0.003 | -97.796 | 0.000 | -15.292 | 0.000 | 0.000 | 9.582 | 9.243 | 10.477 | 47.892 | 0.000 | 2.196 | 34.086 | 0.000 | -0.348 | 0.000 | -0.043 | 0.000 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 0.000 | -321.160 | 0.000 | 0.000 | 111.264 | 91.336 | 0.000 | 49.231 | 0.000 | 2.060 | 68.235 | 0.000 | -0.942 | 0.000 | -0.024 | 0.000 |
ROOM_1_FLR_6 | 0.017 | -26.609 | 0.000 | -3.784 | 0.000 | 0.000 | 2.405 | 2.311 | 2.620 | 12.641 | 0.000 | 0.563 | 9.909 | 0.000 | -0.069 | 0.000 | -0.002 | 0.000 |
ROOM_2_FLR_6 | 0.016 | -25.365 | 0.000 | -3.815 | 0.000 | 0.000 | 2.398 | 2.311 | 2.619 | 11.878 | 0.000 | 0.547 | 9.496 | 0.000 | -0.076 | 0.000 | -0.008 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.008 | -139.460 | 0.000 | -24.332 | 0.000 | 0.000 | 21.641 | 13.076 | 23.098 | 54.616 | 0.000 | 2.663 | 48.997 | 0.000 | -0.288 | 0.000 | -0.019 | 0.000 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.000 | -549.079 | 0.000 | 0.000 | 316.328 | 30.881 | 175.857 | 20.221 | 0.000 | 0.888 | 5.974 | 0.000 | -1.043 | 0.000 | -0.027 | -0.000 |
DINING_FLR_6 | 0.000 | 0.000 | 0.000 | -581.176 | 0.000 | 0.000 | 315.809 | 30.881 | 175.857 | 19.804 | 0.000 | 0.877 | 39.149 | 0.000 | -1.173 | 0.000 | -0.027 | 0.000 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.000 | -688.493 | 0.000 | 0.000 | 28.910 | 12.972 | 550.372 | 25.432 | 0.000 | 0.810 | 70.844 | 0.000 | -0.835 | 0.000 | -0.014 | 0.000 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 0.000 | -165.894 | 0.000 | 0.000 | 29.018 | 24.166 | 0.000 | 20.937 | 0.000 | 0.842 | 91.545 | 0.000 | -0.605 | 0.000 | -0.010 | 0.000 |
Total Facility | 0.596 | -1842.394 | 0.000 | -5441.928 | 0.000 | 0.000 | 1965.241 | 782.723 | 2365.005 | 951.494 | 0.000 | 42.673 | 1259.034 | 0.000 | -40.852 | 0.000 | -2.386 | -39.222 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 15-JUN-21:00 | 0.00 | 0.00 | 0.00 | -22201.22 | 0.00 | 0.00 | 5924.48 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4573.48 |
RETAIL_1_FLR_1 | 05-JAN-15:10 | 0.00 | 0.00 | 0.00 | -3774.64 | 0.00 | 0.00 | 225.90 | 166.00 | 252.59 | 2466.87 | 0.00 | 49.52 | 613.76 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 13-JUN-20:10 | 0.00 | 0.00 | 0.00 | -2735.56 | 0.00 | 0.00 | 697.62 | 615.12 | 752.15 | 0.00 | 0.00 | 13.25 | 657.42 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 13-JUN-19:30 | 0.00 | 0.00 | 0.00 | -3721.34 | 0.00 | 0.00 | 129.09 | 684.18 | 839.45 | 0.00 | 0.00 | 32.36 | 2036.27 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 13-JUN-19:30 | 0.00 | 0.00 | 0.00 | -1802.72 | 0.00 | 0.00 | 99.30 | 251.84 | 242.16 | 0.00 | 0.00 | 18.67 | 1190.76 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 05-MAY-20:00 | 0.00 | 0.00 | 0.00 | -36916.32 | 0.00 | 0.00 | 408.88 | 325.08 | 44299.38 | 0.00 | 0.00 | 38.47 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -8155.50 |
CAFE_FLR_1 | 08-DEC-22:10 | 0.00 | 0.00 | 0.00 | -12924.81 | 0.00 | 0.00 | 8908.33 | 1134.35 | 711.25 | 140.66 | 0.00 | 45.10 | 1985.12 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 13-JUN-21:10 | 0.00 | 0.00 | 0.00 | -47553.39 | 0.00 | 0.00 | 26440.70 | 6336.53 | 7389.94 | 423.90 | 0.00 | 162.64 | 6799.67 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 16-AUG-15:02 | 0.00 | -10849.65 | 0.00 | -741.88 | 0.00 | 0.00 | 235.28 | 199.23 | 200.18 | 4023.04 | 0.00 | 63.78 | 6870.02 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 24-JUN-20:11 | 0.00 | -10867.49 | 0.00 | -822.38 | 0.00 | 0.00 | 315.40 | 711.45 | 726.90 | 0.00 | 0.00 | 4.23 | 9984.45 | 0.00 | -52.55 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 07-DEC-13:50 | 0.00 | -38355.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2378.94 | 2352.88 | 34921.09 | 0.00 | 382.60 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1679.54 |
ROOM_4_MULT19_FLR_3 | 19-JUL-15:02 | 0.00 | -77191.97 | 0.00 | -10321.46 | 0.00 | 0.00 | 4470.40 | 2379.59 | 3726.41 | 20289.75 | 0.00 | 610.51 | 56036.79 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 15-DEC-09:01 | 0.00 | -9857.39 | 0.00 | -767.42 | 0.00 | 0.00 | 87.14 | 313.07 | 453.05 | 5799.22 | 0.00 | 40.08 | 3932.24 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 24-FEB-09:11 | 0.00 | -10395.75 | 0.00 | -939.40 | 0.00 | 0.00 | 74.63 | 313.04 | 452.99 | 5116.69 | 0.00 | 10.91 | 5366.89 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 13-JUN-18:05 | 0.00 | 0.00 | 0.00 | -12832.61 | 0.00 | 0.00 | 4087.48 | 6639.35 | 0.00 | 1535.94 | 0.00 | 111.52 | 458.33 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 18-MAY-18:02 | 0.00 | -2938.95 | 0.00 | -183.85 | 0.00 | 0.00 | 83.87 | 158.32 | 121.16 | 120.22 | 0.00 | 18.94 | 2620.28 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 12-JUN-18:02 | 0.00 | -2983.04 | 0.00 | -189.12 | 0.00 | 0.00 | 83.87 | 158.30 | 121.15 | 709.49 | 0.00 | 26.83 | 2072.52 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 22-NOV-09:02 | 0.00 | -12316.14 | 0.00 | -1214.71 | 0.00 | 0.00 | 196.06 | 442.82 | 998.70 | 6129.29 | 0.00 | 74.48 | 5689.50 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 12-JUN-21:10 | 0.00 | 0.00 | 0.00 | -25409.14 | 0.00 | 0.00 | 15645.28 | 1992.02 | 6747.90 | 256.72 | 0.00 | 41.30 | 725.92 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 12-JUN-21:10 | 0.00 | 0.00 | 0.00 | -26644.56 | 0.00 | 0.00 | 15645.19 | 1992.02 | 6747.90 | 241.48 | 0.00 | 41.30 | 1976.66 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 07-MAY-10:50 | 0.00 | 0.00 | 0.00 | -30618.60 | 0.00 | 0.00 | 461.21 | 353.60 | 24259.91 | 2137.59 | 0.00 | 57.22 | 3349.07 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 13-JUN-15:40 | 0.00 | 0.00 | 0.00 | -7406.90 | 0.00 | 0.00 | 771.14 | 548.96 | 0.00 | 1678.03 | 0.00 | 72.62 | 4336.14 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 13-JUN-18:02 | 0.00 | -158437.20 | 0.00 | -229116.32 | 0.00 | 0.00 | 73818.17 | 56569.79 | 120482.43 | 28322.40 | 0.00 | 2310.69 | 106050.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 17-MAY-08:04 | 1808.69 | 625.95 | 0.00 | -625.95 | 0.00 | 0.00 | 87.14 | 313.07 | 453.05 | 983.55 | 0.00 | 35.71 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -3681.21 |
ROOM_2_FLR_3 | 17-MAY-08:04 | 1841.43 | 622.34 | 0.00 | -622.34 | 0.00 | 0.00 | 87.14 | 313.04 | 452.99 | 1003.68 | 0.00 | 36.27 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -3734.55 |
ROOM_3_MULT19_FLR_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 23-NOV-16:07 | 15706.70 | 8574.22 | 0.00 | -8574.22 | 0.00 | 0.00 | 2483.54 | 2804.51 | 4118.66 | 5404.25 | 0.00 | 396.45 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -30914.12 |
ROOM_5_FLR_3 | 23-OCT-08:05 | 1443.10 | 632.37 | 0.00 | -632.37 | 0.00 | 0.00 | 87.14 | 313.07 | 453.05 | 1694.11 | 0.00 | 44.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4034.46 |
ROOM_6_FLR_3 | 18-SEP-08:36 | 1413.86 | 633.98 | 0.00 | -633.98 | 0.00 | 0.00 | 85.76 | 313.04 | 452.99 | 2048.82 | 0.00 | 34.81 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4349.29 |
CORRIDOR_FLR_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 24-JAN-09:04 | 478.49 | 140.44 | 0.00 | -140.44 | 0.00 | 0.00 | 21.79 | 78.27 | 113.26 | 437.44 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -6.74 | -1122.50 |
ROOM_2_FLR_6 | 17-MAY-08:04 | 480.40 | 155.13 | 0.00 | -155.13 | 0.00 | 0.00 | 21.79 | 78.26 | 113.25 | 252.25 | 0.00 | 8.99 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -954.93 |
ROOM_3_MULT9_FLR_6 | 27-NOV-09:06 | 1396.14 | 1017.02 | 0.00 | -1017.02 | 0.00 | 0.00 | 196.07 | 442.82 | 998.70 | 2686.41 | 0.00 | 48.76 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5768.89 |
BANQUET_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 23-NOV-16:07 | -194385.40 | 167365.96 | 0.00 | -167365.96 | 0.00 | 0.00 | 32910.25 | 15614.62 | 71286.28 | 29579.09 | 0.00 | 1298.31 | 43696.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:10
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV WITH REHEAT | 22.1520 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 21.9831 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV WITH REHEAT | 11.6520 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 11.6520 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.6520 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.0400 | 0.000610 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.000000 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.000000 | 142.3000 | 0.003581 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.000000 | 422.4350 | 0.001448 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 83.8280 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003556 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.1800 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 | |
VAV WITH REHEAT | 0.00 | 0.001045 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.9565 | 2.9565 | 1.5551 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3031 | 0.3031 | 0.1594 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2754 | 0.2754 | 0.1449 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2814 | 0.2814 | 0.1480 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1551 | 0.1551 | 0.0816 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.1902 | 3.1902 | 1.6780 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2749 | 1.2749 | 0.6706 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.7223 | 4.7223 | 2.4839 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5264 | 1.5264 | 0.8029 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2030 | 2.2030 | 1.1588 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3047 | 2.3047 | 1.2123 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1986 | 2.1986 | 1.1564 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7604 | 0.7604 | 0.4000 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
VAV WITH REHEAT | 22.1520 | 21.9831 | 22.1520 | 11.6520 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5551 | 1.5551 | 1.5551 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1594 | 0.1594 | 0.1594 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1449 | 0.1449 | 0.1449 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1480 | 0.1480 | 0.1480 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0816 | 0.0816 | 0.0816 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6780 | 1.6780 | 1.6780 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6706 | 0.6706 | 0.6706 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.4839 | 2.4839 | 2.4839 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8029 | 0.8029 | 0.8029 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1588 | 1.1588 | 1.1588 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2123 | 1.2123 | 1.2123 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1564 | 1.1564 | 1.1564 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4000 | 0.4000 | 0.4000 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
VAV WITH REHEAT | 11.6520 | 11.6520 | 11.6520 | 11.6520 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:10
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 168.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 168.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 60.50 |
Number of hours not met | 60.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 16.80 | 5851.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 4172.43 | 249536.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 782.72 | 64632.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 194.17 | 12338.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 872.72 | 59188.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 14.43 | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 8.99 | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.20 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 21.77 | 1291.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 789.09 | 48128.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 2.91 | 188.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 498.28 | 28792.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 144.11 | 5754.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 302.67 | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 94.79 | 4751.13 | 1942.15 | 179827.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.09 | 2093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 20.40 | 1892.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 34.95 | 1191.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1720.61 | 8740.36 |
Natural Gas | 1788.84 | 3730.99 |
Additional | 0.00 | 0.00 |
Total | 3509.45 | 12471.35 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 68.99 |
Space Heating | 1.48 |
Space Cooling | 367.77 |
Fans (All) | 43.92 |
Service Water Heating | 8.36 |
Receptacle Equipment | 146.16 |
Miscellaneous (All) | 770.40 |
Subtotal | 770.40 |
Natural Gas [MJ/m2] | |
Space Heating | 0.00 |
Service Water Heating | 171.19 |
Miscellaneous (All) | 328.86 |
Subtotal | 328.86 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 6.28 |
Space Heating | 0.13 |
Space Cooling | 33.46 |
Fans (All) | 4.00 |
Service Water Heating | 16.33 |
Receptacle Equipment | 27.64 |
Miscellaneous | 12.17 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 486. | 5110. |
ELEVATOR_STANDBY_SCH | 7671. | 8760. |
LTG_SCH_KITCHEN | 3061. | 8760. |
LTG_SCH_DINING | 3061. | 8760. |
LTG_SCH_BASEMENT | 2572. | 8760. |
LTG_SCH_LOBBY | 2295. | 8760. |
LTG_SCH_STORAGE | 1580. | 8760. |
LTG_SCH_MECHANIC | 3061. | 8760. |
LTG_SCH_LAUNDRY | 3061. | 8760. |
LTG_SCH_GUESTROOM | 1980. | 8760. |
LTG_SCH_CORRIDOR | 2295. | 8760. |
LTG_SCH_RETAIL | 2678. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 1591. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3737. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 5740. | 6205. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 8760. | 8760. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 26.67 | 365 | 26.67 | 365 |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
HTGSETP_SCH | BASEMENT DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:10
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 6803.50 | 1956.50 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 6803.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 1956.50 | 0.00 | 0.00 | 0.00 |
Average | 8671.07 | 88.93 | 0.00 | 0.00 | 0.00 |
Sum | 190763.50 | 1956.50 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108269.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 288887.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 6355515.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8168.67 | 591.33 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8702.67 | 57.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 5337.00 | 3423.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8731.50 | 28.50 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8674.50 | 85.50 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8758.83 | 1.17 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8677.50 | 82.50 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8758.33 | 1.67 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8710.00 | 50.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 5337.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 3423.00 | 0.00 | 0.00 | 0.00 |
Average | 8563.59 | 196.41 | 0.00 | 0.00 | 0.00 |
Sum | 188399.00 | 4321.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 634726.33 | 75690.67 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4135.17 | 18.83 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4141.67 | 12.33 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4136.00 | 18.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4133.50 | 20.50 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1234515.00 | 11200.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108269.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 75690.67 | 0.00 | 0.00 | 0.00 |
Average | 284934.30 | 3952.74 | 0.00 | 0.00 | 0.00 |
Sum | 6268554.67 | 86960.33 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:10
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:10
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 1592.73 | 0.00 | 0.00 |
Sum | 0.00 | 35040.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 710417.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 2115429.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 2115429.00 | 0.00 | 0.00 |
Average | 0.00 | 241694.36 | 0.00 | 0.00 |
Sum | 0.00 | 5317276.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0A
For: Environment
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Environment
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY VNM_HOCHIMINH_TANSONHOA
For: Environment
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.528464E+11 | 20989.08 | 06-JAN-22:00 | 24.60 | 22.00 | 0.762278E+10 | 4732.66 | 06-JAN-22:10 | 24.50 | 21.98 |
February | 0.482192E+11 | 20994.27 | 24-FEB-22:00 | 26.80 | 22.90 | 0.696170E+10 | 4734.11 | 24-FEB-22:10 | 26.67 | 22.83 |
March | 0.529604E+11 | 20845.31 | 01-MAR-22:00 | 26.00 | 23.18 | 0.767588E+10 | 4699.91 | 01-MAR-22:10 | 25.83 | 23.12 |
April | 0.513464E+11 | 20947.97 | 28-APR-21:00 | 28.50 | 25.82 | 0.741778E+10 | 4723.40 | 28-APR-21:10 | 28.43 | 25.81 |
May | 0.536072E+11 | 21262.42 | 08-MAY-21:00 | 28.00 | 26.50 | 0.774751E+10 | 4796.06 | 08-MAY-21:10 | 27.23 | 25.96 |
June | 0.526415E+11 | 22201.02 | 15-JUN-21:00 | 29.00 | 26.74 | 0.762200E+10 | 4836.85 | 13-JUN-21:10 | 29.00 | 26.74 |
July | 0.538584E+11 | 21237.60 | 28-JUL-21:00 | 25.00 | 23.59 | 0.776636E+10 | 4790.79 | 28-JUL-21:10 | 24.87 | 23.50 |
August | 0.534074E+11 | 21259.21 | 15-AUG-21:00 | 27.00 | 24.83 | 0.773570E+10 | 4796.15 | 15-AUG-21:10 | 26.87 | 24.82 |
September | 0.516918E+11 | 21194.47 | 08-SEP-21:00 | 28.00 | 25.20 | 0.746382E+10 | 4780.85 | 08-SEP-21:10 | 27.68 | 24.93 |
October | 0.526119E+11 | 20914.48 | 05-OCT-21:00 | 26.50 | 25.32 | 0.759126E+10 | 4715.46 | 05-OCT-21:10 | 26.65 | 25.42 |
November | 0.513461E+11 | 21096.85 | 22-NOV-22:00 | 25.60 | 23.63 | 0.740219E+10 | 4758.08 | 22-NOV-22:10 | 25.42 | 23.59 |
December | 0.531322E+11 | 21135.26 | 08-DEC-22:00 | 28.10 | 23.77 | 0.766248E+10 | 4767.05 | 08-DEC-22:10 | 27.92 | 23.84 |
Annual Sum or Average | 0.627669E+12 | 0.906695E+11 | ||||||||
Minimum of Months | 0.482192E+11 | 20845.31 | 24.60 | 22.00 | 0.696170E+10 | 4699.91 | 24.50 | 21.98 | ||
Maximum of Months | 0.538584E+11 | 22201.02 | 29.00 | 26.74 | 0.776636E+10 | 4836.85 | 29.00 | 26.74 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.637802E+10 | 3774.52 | 05-JAN-15:10 | 33.73 | 23.23 | 0.794163E+09 | 491.82 | 17-JAN-23:19 | 24.30 | 21.68 |
February | 0.588057E+10 | 3447.65 | 03-FEB-16:03 | 33.17 | 23.89 | 0.728408E+09 | 491.82 | 22-FEB-23:19 | 26.33 | 21.98 |
March | 0.620219E+10 | 3154.76 | 13-MAR-19:20 | 29.00 | 22.70 | 0.807904E+09 | 491.82 | 02-MAR-23:19 | 29.00 | 22.70 |
April | 0.578166E+10 | 3008.80 | 11-APR-19:20 | 29.57 | 26.58 | 0.775435E+09 | 491.82 | 26-APR-22:19 | 28.13 | 23.80 |
May | 0.587041E+10 | 3282.62 | 05-MAY-19:10 | 30.92 | 26.05 | 0.794777E+09 | 491.83 | 31-MAY-22:10 | 24.07 | 23.84 |
June | 0.580325E+10 | 3306.17 | 12-JUN-19:20 | 30.93 | 27.38 | 0.777984E+09 | 491.82 | 11-JUN-23:19 | 30.93 | 27.38 |
July | 0.557991E+10 | 2925.05 | 14-JUL-20:10 | 29.32 | 24.69 | 0.782150E+09 | 491.84 | 19-JUL-22:10 | 23.42 | 22.43 |
August | 0.553957E+10 | 2912.45 | 14-AUG-19:20 | 29.40 | 27.71 | 0.774346E+09 | 491.84 | 23-AUG-22:10 | 24.25 | 23.10 |
September | 0.552928E+10 | 3152.99 | 13-SEP-19:30 | 30.25 | 26.54 | 0.758959E+09 | 491.82 | 08-SEP-22:19 | 30.25 | 26.54 |
October | 0.565430E+10 | 3033.52 | 04-OCT-19:10 | 28.42 | 25.07 | 0.774667E+09 | 491.82 | 04-OCT-22:19 | 27.00 | 25.53 |
November | 0.583473E+10 | 3381.60 | 19-NOV-13:00 | 32.40 | 24.76 | 0.760820E+09 | 491.82 | 22-NOV-23:19 | 24.33 | 23.33 |
December | 0.625749E+10 | 3748.03 | 08-DEC-14:00 | 33.00 | 23.23 | 0.789028E+09 | 491.84 | 26-DEC-23:10 | 22.00 | 19.41 |
Annual Sum or Average | 0.703114E+11 | 0.931864E+10 | ||||||||
Minimum of Months | 0.552928E+10 | 2912.45 | 28.42 | 22.70 | 0.728408E+09 | 491.82 | 22.00 | 19.41 | ||
Maximum of Months | 0.637802E+10 | 3774.52 | 33.73 | 27.71 | 0.807904E+09 | 491.84 | 30.93 | 27.38 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.490289E+10 | 2320.07 | 31-JAN-21:10 | 26.73 | 22.00 | 0.898360E+09 | 569.50 | 31-JAN-22:19 | 26.27 | 22.11 |
February | 0.454956E+10 | 2432.23 | 22-FEB-21:10 | 27.43 | 22.28 | 0.829069E+09 | 569.53 | 22-FEB-23:19 | 26.33 | 21.98 |
March | 0.507381E+10 | 2462.15 | 29-MAR-20:10 | 28.00 | 23.68 | 0.924353E+09 | 569.53 | 13-MAR-22:19 | 28.00 | 23.68 |
April | 0.493370E+10 | 2505.17 | 27-APR-20:10 | 29.37 | 24.32 | 0.891579E+09 | 569.53 | 26-APR-22:19 | 29.37 | 24.32 |
May | 0.503748E+10 | 2631.70 | 05-MAY-20:10 | 29.83 | 26.38 | 0.915196E+09 | 569.55 | 31-MAY-22:10 | 24.07 | 23.84 |
June | 0.499853E+10 | 2735.49 | 13-JUN-20:10 | 30.67 | 27.30 | 0.898050E+09 | 569.53 | 11-JUN-23:19 | 30.67 | 27.30 |
July | 0.493356E+10 | 2442.62 | 14-JUL-20:50 | 28.58 | 24.55 | 0.903710E+09 | 569.55 | 19-JUL-22:10 | 23.42 | 22.43 |
August | 0.489738E+10 | 2407.32 | 14-AUG-20:10 | 29.00 | 28.18 | 0.898305E+09 | 569.55 | 23-AUG-22:10 | 24.25 | 23.10 |
September | 0.477367E+10 | 2563.26 | 13-SEP-20:10 | 29.92 | 26.86 | 0.872391E+09 | 569.53 | 12-SEP-22:19 | 29.92 | 26.86 |
October | 0.482424E+10 | 2306.63 | 04-OCT-20:10 | 27.92 | 25.10 | 0.885367E+09 | 569.50 | 04-OCT-21:19 | 27.33 | 25.39 |
November | 0.471794E+10 | 2289.48 | 03-NOV-20:10 | 25.50 | 24.73 | 0.863496E+09 | 569.50 | 22-NOV-22:19 | 25.23 | 23.55 |
December | 0.487649E+10 | 2254.73 | 07-DEC-21:10 | 26.88 | 23.89 | 0.893690E+09 | 569.52 | 26-DEC-22:10 | 23.08 | 19.87 |
Annual Sum or Average | 0.585193E+11 | 0.106736E+11 | ||||||||
Minimum of Months | 0.454956E+10 | 2254.73 | 25.50 | 22.00 | 0.829069E+09 | 569.50 | 23.08 | 19.87 | ||
Maximum of Months | 0.507381E+10 | 2735.49 | 30.67 | 28.18 | 0.924353E+09 | 569.55 | 30.67 | 27.30 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.493390E+10 | 1994.78 | 05-JAN-21:00 | 27.00 | 23.38 | 0.186122E+09 | 117.69 | 05-JAN-22:10 | 26.38 | 23.18 |
February | 0.457732E+10 | 2013.22 | 27-FEB-21:00 | 26.50 | 22.02 | 0.172790E+09 | 118.80 | 22-FEB-22:10 | 26.50 | 22.02 |
March | 0.510291E+10 | 2186.02 | 29-MAR-20:00 | 28.00 | 23.68 | 0.193379E+09 | 120.45 | 21-MAR-21:10 | 28.00 | 23.68 |
April | 0.510187E+10 | 2747.22 | 30-APR-19:50 | 30.28 | 26.40 | 0.190172E+09 | 120.45 | 26-APR-22:19 | 30.28 | 26.40 |
May | 0.558972E+10 | 3220.25 | 05-MAY-19:30 | 30.55 | 26.16 | 0.199426E+09 | 120.45 | 31-MAY-22:10 | 24.07 | 23.84 |
June | 0.592282E+10 | 3721.40 | 13-JUN-19:30 | 30.90 | 27.22 | 0.196400E+09 | 120.45 | 26-JUN-22:19 | 24.27 | 24.10 |
July | 0.542072E+10 | 3113.33 | 14-JUL-20:00 | 29.50 | 24.72 | 0.198541E+09 | 120.45 | 19-JUL-22:10 | 23.42 | 22.43 |
August | 0.518142E+10 | 2771.69 | 01-AUG-20:00 | 29.00 | 27.47 | 0.193339E+09 | 120.45 | 15-AUG-22:19 | 26.13 | 25.18 |
September | 0.492840E+10 | 2355.53 | 08-SEP-20:00 | 29.00 | 25.99 | 0.185706E+09 | 120.45 | 08-SEP-22:10 | 26.02 | 23.59 |
October | 0.494803E+10 | 2020.23 | 04-OCT-20:00 | 28.00 | 25.05 | 0.186528E+09 | 119.27 | 04-OCT-21:10 | 27.42 | 25.35 |
November | 0.481257E+10 | 2004.86 | 21-NOV-21:00 | 28.00 | 25.20 | 0.181181E+09 | 118.33 | 21-NOV-22:10 | 27.33 | 25.20 |
December | 0.491721E+10 | 1987.82 | 08-DEC-22:00 | 28.10 | 23.77 | 0.185329E+09 | 117.34 | 08-DEC-22:10 | 27.92 | 23.84 |
Annual Sum or Average | 0.614369E+11 | 0.226891E+10 | ||||||||
Minimum of Months | 0.457732E+10 | 1987.82 | 26.50 | 22.02 | 0.172790E+09 | 117.34 | 23.42 | 22.02 | ||
Maximum of Months | 0.592282E+10 | 3721.40 | 30.90 | 27.47 | 0.199426E+09 | 120.45 | 30.28 | 26.40 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.270345E+10 | 1075.74 | 05-JAN-22:10 | 26.38 | 23.18 | 0.141982E+09 | 88.45 | 05-JAN-22:10 | 26.38 | 23.18 |
February | 0.250517E+10 | 1084.19 | 22-FEB-22:10 | 27.00 | 22.22 | 0.131647E+09 | 89.18 | 22-FEB-22:10 | 27.00 | 22.22 |
March | 0.278849E+10 | 1106.27 | 29-MAR-21:10 | 28.03 | 23.69 | 0.147202E+09 | 91.03 | 29-MAR-21:10 | 28.03 | 23.69 |
April | 0.276159E+10 | 1304.58 | 30-APR-19:20 | 32.33 | 26.74 | 0.144934E+09 | 92.65 | 27-APR-21:30 | 32.33 | 26.74 |
May | 0.298136E+10 | 1562.23 | 06-MAY-19:00 | 32.30 | 26.17 | 0.152499E+09 | 92.66 | 31-MAY-22:10 | 24.07 | 23.84 |
June | 0.313271E+10 | 1802.75 | 13-JUN-19:30 | 30.90 | 27.22 | 0.150481E+09 | 92.65 | 13-JUN-03:20 | 30.90 | 27.22 |
July | 0.290202E+10 | 1458.26 | 14-JUL-20:00 | 29.50 | 24.72 | 0.151440E+09 | 92.65 | 14-JUL-23:19 | 27.00 | 24.11 |
August | 0.280276E+10 | 1292.40 | 01-AUG-20:00 | 29.00 | 27.47 | 0.147417E+09 | 92.65 | 01-AUG-22:19 | 28.07 | 26.61 |
September | 0.268884E+10 | 1118.82 | 07-SEP-21:10 | 28.97 | 26.76 | 0.141367E+09 | 92.09 | 08-SEP-21:10 | 27.68 | 24.93 |
October | 0.270785E+10 | 1087.77 | 04-OCT-21:10 | 27.42 | 25.35 | 0.142185E+09 | 89.46 | 04-OCT-21:10 | 27.42 | 25.35 |
November | 0.263474E+10 | 1080.88 | 21-NOV-22:10 | 27.33 | 25.20 | 0.138129E+09 | 88.93 | 21-NOV-22:10 | 27.33 | 25.20 |
December | 0.269463E+10 | 1074.78 | 08-DEC-22:10 | 27.92 | 23.84 | 0.141402E+09 | 88.41 | 08-DEC-22:10 | 27.92 | 23.84 |
Annual Sum or Average | 0.333036E+11 | 0.173068E+10 | ||||||||
Minimum of Months | 0.250517E+10 | 1074.78 | 26.38 | 22.22 | 0.131647E+09 | 88.41 | 24.07 | 22.22 | ||
Maximum of Months | 0.313271E+10 | 1802.75 | 32.33 | 27.47 | 0.152499E+09 | 92.66 | 32.33 | 27.22 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.534569E+11 | 35681.32 | 04-JAN-21:00 | 26.80 | 23.34 | 0.544178E+09 | 381.52 | 23-JAN-23:10 | 22.33 | 18.26 |
February | 0.490346E+11 | 35905.67 | 22-FEB-21:00 | 27.50 | 22.29 | 0.494457E+09 | 381.50 | 22-FEB-22:30 | 26.80 | 22.14 |
March | 0.546246E+11 | 36260.66 | 29-MAR-20:00 | 28.00 | 23.68 | 0.550331E+09 | 381.50 | 02-MAR-22:30 | 28.00 | 23.68 |
April | 0.530736E+11 | 36531.78 | 28-APR-20:00 | 29.00 | 25.99 | 0.532091E+09 | 381.50 | 26-APR-21:30 | 29.00 | 25.99 |
May | 0.545775E+11 | 36916.26 | 05-MAY-20:00 | 30.00 | 26.30 | 0.549562E+09 | 381.52 | 31-MAY-22:10 | 24.07 | 23.84 |
June | 0.533960E+11 | 36861.88 | 13-JUN-20:00 | 31.00 | 27.23 | 0.534259E+09 | 381.50 | 07-JUN-21:30 | 31.00 | 27.23 |
July | 0.539744E+11 | 36374.74 | 14-JUL-20:00 | 29.50 | 24.72 | 0.545873E+09 | 381.52 | 19-JUL-22:10 | 23.42 | 22.43 |
August | 0.536726E+11 | 36249.41 | 01-AUG-20:00 | 29.00 | 27.47 | 0.547112E+09 | 381.52 | 23-AUG-22:10 | 24.25 | 23.10 |
September | 0.521207E+11 | 36184.03 | 06-SEP-20:00 | 28.50 | 26.55 | 0.528507E+09 | 381.52 | 15-SEP-22:10 | 23.17 | 23.17 |
October | 0.530000E+11 | 35836.35 | 04-OCT-20:00 | 28.00 | 25.05 | 0.543346E+09 | 381.51 | 30-OCT-21:10 | 23.98 | 23.94 |
November | 0.516821E+11 | 35589.31 | 22-NOV-21:00 | 25.00 | 23.59 | 0.526620E+09 | 381.52 | 24-NOV-23:10 | 23.27 | 20.53 |
December | 0.531699E+11 | 35570.48 | 08-DEC-21:00 | 28.00 | 24.30 | 0.543095E+09 | 381.52 | 20-DEC-23:10 | 21.00 | 17.84 |
Annual Sum or Average | 0.635783E+12 | 0.643943E+10 | ||||||||
Minimum of Months | 0.490346E+11 | 35570.48 | 25.00 | 22.29 | 0.494457E+09 | 381.50 | 21.00 | 17.84 | ||
Maximum of Months | 0.546246E+11 | 36916.26 | 31.00 | 27.47 | 0.550331E+09 | 381.52 | 31.00 | 27.23 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.260387E+11 | 12857.62 | 05-JAN-22:10 | 26.38 | 23.18 | 0.108062E+11 | 6462.43 | 23-JAN-23:10 | 22.33 | 18.26 |
February | 0.236491E+11 | 12519.40 | 22-FEB-22:10 | 27.00 | 22.22 | 0.982273E+10 | 6461.93 | 24-FEB-04:19 | 23.07 | 19.40 |
March | 0.253155E+11 | 12340.35 | 13-MAR-21:10 | 28.03 | 22.97 | 0.108401E+11 | 6461.91 | 03-MAR-04:19 | 28.03 | 22.97 |
April | 0.239377E+11 | 12020.81 | 19-APR-21:10 | 28.97 | 26.21 | 0.103704E+11 | 6461.92 | 20-APR-22:19 | 27.13 | 24.77 |
May | 0.246053E+11 | 12516.86 | 05-MAY-21:10 | 29.02 | 26.76 | 0.107068E+11 | 6462.56 | 31-MAY-22:10 | 24.07 | 23.84 |
June | 0.240770E+11 | 12449.95 | 13-JUN-21:10 | 28.97 | 27.36 | 0.104125E+11 | 6461.90 | 28-JUN-22:19 | 28.07 | 27.07 |
July | 0.238610E+11 | 11633.94 | 26-JUL-21:10 | 26.87 | 24.52 | 0.106019E+11 | 6462.62 | 19-JUL-22:10 | 26.87 | 24.52 |
August | 0.236993E+11 | 11898.32 | 14-AUG-21:10 | 28.95 | 27.94 | 0.105733E+11 | 6462.56 | 23-AUG-22:10 | 24.25 | 23.10 |
September | 0.234495E+11 | 12137.44 | 13-SEP-21:10 | 29.32 | 26.39 | 0.102921E+11 | 6462.49 | 15-SEP-22:10 | 23.17 | 23.17 |
October | 0.241580E+11 | 12214.65 | 16-OCT-21:10 | 27.02 | 25.86 | 0.106139E+11 | 6461.92 | 31-OCT-22:19 | 25.00 | 24.11 |
November | 0.243404E+11 | 12422.34 | 21-NOV-22:10 | 27.33 | 25.20 | 0.103932E+11 | 6462.50 | 24-NOV-23:10 | 23.27 | 20.53 |
December | 0.257549E+11 | 12923.47 | 08-DEC-22:10 | 27.92 | 23.84 | 0.107840E+11 | 6462.51 | 20-DEC-23:10 | 21.00 | 17.84 |
Annual Sum or Average | 0.292886E+12 | 0.126217E+12 | ||||||||
Minimum of Months | 0.234495E+11 | 11633.94 | 26.38 | 22.22 | 0.982273E+10 | 6461.90 | 21.00 | 17.84 | ||
Maximum of Months | 0.260387E+11 | 12923.47 | 29.32 | 27.94 | 0.108401E+11 | 6462.62 | 28.07 | 27.07 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.874721E+11 | 41840.88 | 05-JAN-22:10 | 26.38 | 23.18 | 0.312755E+11 | 19185.79 | 23-JAN-23:10 | 22.33 | 18.26 |
February | 0.803905E+11 | 41550.43 | 22-FEB-22:10 | 27.00 | 22.22 | 0.285842E+11 | 19184.78 | 22-FEB-23:19 | 26.33 | 21.98 |
March | 0.884396E+11 | 41377.70 | 29-MAR-21:10 | 28.03 | 23.69 | 0.316783E+11 | 19184.78 | 02-MAR-23:19 | 28.03 | 23.69 |
April | 0.858847E+11 | 42672.77 | 28-APR-21:10 | 28.43 | 25.81 | 0.305764E+11 | 19184.76 | 26-APR-22:19 | 28.43 | 25.81 |
May | 0.899902E+11 | 45564.79 | 05-MAY-21:10 | 29.02 | 26.76 | 0.317303E+11 | 19185.95 | 31-MAY-22:10 | 24.07 | 23.84 |
June | 0.897254E+11 | 47549.67 | 13-JUN-21:10 | 28.97 | 27.36 | 0.310058E+11 | 19185.14 | 28-JUN-22:19 | 28.07 | 27.07 |
July | 0.883918E+11 | 43610.67 | 14-JUL-21:10 | 28.23 | 24.46 | 0.315112E+11 | 19186.03 | 19-JUL-22:10 | 23.42 | 22.43 |
August | 0.868515E+11 | 42562.00 | 01-AUG-21:10 | 28.85 | 27.27 | 0.312597E+11 | 19185.95 | 23-AUG-22:10 | 24.25 | 23.10 |
September | 0.842124E+11 | 41411.39 | 13-SEP-21:10 | 29.32 | 26.39 | 0.302374E+11 | 19184.75 | 08-SEP-22:19 | 29.32 | 26.39 |
October | 0.857150E+11 | 40406.28 | 04-OCT-21:10 | 27.42 | 25.35 | 0.309301E+11 | 19184.74 | 10-OCT-22:19 | 24.57 | 23.94 |
November | 0.841980E+11 | 40905.16 | 21-NOV-22:10 | 27.33 | 25.20 | 0.301827E+11 | 19185.88 | 24-NOV-23:10 | 23.27 | 20.53 |
December | 0.871259E+11 | 41739.15 | 08-DEC-22:10 | 27.92 | 23.84 | 0.312030E+11 | 19185.90 | 20-DEC-23:10 | 21.00 | 17.84 |
Annual Sum or Average | 0.103840E+13 | 0.370175E+12 | ||||||||
Minimum of Months | 0.803905E+11 | 40406.28 | 26.38 | 22.22 | 0.285842E+11 | 19184.74 | 21.00 | 17.84 | ||
Maximum of Months | 0.899902E+11 | 47549.67 | 29.32 | 27.36 | 0.317303E+11 | 19186.03 | 29.32 | 27.07 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.252351E+10 | 2860.81 | 10-JAN-19:02 | 28.12 | 25.01 | 99149433.02 | 56.70 | 04-JAN-22:19 | 28.12 | 25.01 |
February | 0.244308E+10 | 2851.37 | 08-FEB-19:02 | 27.08 | 23.13 | 89568791.55 | 56.70 | 28-FEB-22:30 | 26.50 | 22.92 |
March | 0.271553E+10 | 2860.91 | 14-MAR-18:02 | 27.00 | 23.80 | 99227500.39 | 56.70 | 17-MAR-21:49 | 27.17 | 22.92 |
April | 0.262000E+10 | 2868.00 | 30-APR-08:62 | 29.32 | 26.47 | 95946028.81 | 56.70 | 24-APR-21:00 | 29.32 | 26.47 |
May | 0.259461E+10 | 2872.90 | 11-MAY-18:02 | 26.53 | 25.86 | 99190257.23 | 56.70 | 03-MAY-21:40 | 26.53 | 25.86 |
June | 0.261051E+10 | 2884.56 | 03-JUN-15:02 | 28.17 | 27.26 | 96019346.92 | 56.70 | 15-JUN-22:40 | 29.07 | 26.80 |
July | 0.234065E+10 | 2881.80 | 10-JUL-15:02 | 26.33 | 26.01 | 99096100.85 | 56.69 | 14-JUL-22:10 | 27.33 | 24.18 |
August | 0.232058E+10 | 2897.77 | 16-AUG-15:02 | 27.92 | 26.90 | 99195370.05 | 56.69 | 19-AUG-00:10 | 25.90 | 25.04 |
September | 0.230392E+10 | 2873.68 | 16-SEP-18:01 | 23.88 | 23.84 | 95931006.75 | 56.70 | 05-SEP-21:19 | 23.88 | 23.84 |
October | 0.228581E+10 | 2878.08 | 05-OCT-18:02 | 28.02 | 25.66 | 99128472.27 | 56.69 | 17-OCT-04:40 | 25.00 | 24.24 |
November | 0.232122E+10 | 2868.11 | 22-NOV-19:02 | 26.33 | 24.36 | 95976913.48 | 56.69 | 07-NOV-02:49 | 26.33 | 24.36 |
December | 0.243107E+10 | 2877.24 | 12-DEC-19:02 | 27.33 | 25.03 | 99115377.70 | 56.69 | 09-DEC-05:19 | 27.33 | 25.03 |
Annual Sum or Average | 0.295105E+11 | 0.116754E+10 | ||||||||
Minimum of Months | 0.228581E+10 | 2851.37 | 23.88 | 23.13 | 89568791.55 | 56.69 | 23.88 | 22.92 | ||
Maximum of Months | 0.271553E+10 | 2897.77 | 29.32 | 27.26 | 99227500.39 | 56.70 | 29.32 | 26.80 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.214502E+10 | 2898.73 | 02-JAN-16:02 | 30.58 | 24.43 | 0.100463E+09 | 72.02 | 23-JAN-22:00 | 22.50 | 18.29 |
February | 0.216506E+10 | 2900.41 | 15-FEB-19:02 | 28.22 | 25.28 | 90615895.46 | 56.69 | 15-FEB-03:20 | 28.22 | 25.28 |
March | 0.259027E+10 | 2903.17 | 14-MAR-18:02 | 27.00 | 23.80 | 99378127.58 | 56.70 | 21-MAR-21:40 | 27.20 | 23.46 |
April | 0.263375E+10 | 2896.49 | 13-APR-18:02 | 28.08 | 25.35 | 95992694.24 | 56.70 | 07-APR-21:00 | 28.08 | 25.35 |
May | 0.267525E+10 | 2895.53 | 13-MAY-08:62 | 31.17 | 26.47 | 99440169.24 | 79.48 | 10-MAY-21:00 | 31.17 | 26.47 |
June | 0.276248E+10 | 2922.68 | 24-JUN-20:11 | 24.00 | 24.00 | 96345845.44 | 60.90 | 25-JUN-20:00 | 23.00 | 23.00 |
July | 0.242619E+10 | 2902.19 | 06-JUL-18:02 | 24.97 | 24.23 | 99559786.16 | 81.52 | 19-JUL-21:10 | 23.32 | 22.34 |
August | 0.235719E+10 | 2913.87 | 16-AUG-15:02 | 27.92 | 26.90 | 99478061.37 | 78.20 | 23-AUG-21:00 | 24.30 | 22.91 |
September | 0.226079E+10 | 2900.48 | 16-SEP-18:01 | 23.88 | 23.84 | 96317847.57 | 75.61 | 15-SEP-21:10 | 23.88 | 23.84 |
October | 0.215121E+10 | 2909.36 | 10-OCT-18:02 | 26.92 | 25.06 | 99614271.78 | 67.17 | 30-OCT-20:49 | 24.00 | 23.94 |
November | 0.205964E+10 | 2908.96 | 20-NOV-19:02 | 28.47 | 25.77 | 97156510.52 | 75.47 | 24-NOV-22:10 | 22.87 | 20.57 |
December | 0.204118E+10 | 2889.75 | 11-DEC-16:02 | 29.17 | 25.51 | 0.100773E+09 | 75.51 | 26-DEC-22:10 | 23.08 | 19.87 |
Annual Sum or Average | 0.282680E+11 | 0.117514E+10 | ||||||||
Minimum of Months | 0.204118E+10 | 2889.75 | 23.88 | 23.80 | 90615895.46 | 56.69 | 22.50 | 18.29 | ||
Maximum of Months | 0.276248E+10 | 2922.68 | 31.17 | 26.90 | 0.100773E+09 | 81.52 | 31.17 | 26.47 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.793099E+09 | 503.57 | 05-JAN-14:30 | 33.80 | 23.21 | 0.00 | 0.00 | 01-JAN-00:10 | 33.80 | 23.21 |
February | 0.706507E+09 | 449.63 | 04-FEB-14:30 | 32.50 | 24.95 | 0.00 | 0.00 | 01-FEB-00:10 | 32.50 | 24.95 |
March | 0.675420E+09 | 370.27 | 11-MAR-09:00 | 28.00 | 23.68 | 0.00 | 0.00 | 01-MAR-00:10 | 28.00 | 23.68 |
April | 0.588335E+09 | 351.64 | 01-APR-20:20 | 29.33 | 26.00 | 0.00 | 0.00 | 01-APR-00:10 | 29.33 | 26.00 |
May | 0.601603E+09 | 364.78 | 06-MAY-08:00 | 32.00 | 26.09 | 0.00 | 0.00 | 01-MAY-00:10 | 32.00 | 26.09 |
June | 0.583724E+09 | 353.06 | 13-JUN-20:20 | 30.33 | 27.35 | 0.00 | 0.00 | 01-JUN-00:10 | 30.33 | 27.35 |
July | 0.552233E+09 | 332.45 | 15-JUL-20:10 | 28.92 | 25.01 | 0.00 | 0.00 | 01-JUL-00:10 | 28.92 | 25.01 |
August | 0.533885E+09 | 329.31 | 14-AUG-21:00 | 29.00 | 28.18 | 0.00 | 0.00 | 01-AUG-00:10 | 29.00 | 28.18 |
September | 0.567312E+09 | 344.32 | 27-SEP-20:30 | 28.00 | 25.79 | 0.00 | 0.00 | 01-SEP-00:10 | 28.00 | 25.79 |
October | 0.618917E+09 | 391.45 | 29-OCT-08:00 | 28.00 | 25.64 | 0.00 | 0.00 | 01-OCT-00:10 | 28.00 | 25.64 |
November | 0.696833E+09 | 464.87 | 23-NOV-09:00 | 28.50 | 23.82 | 0.00 | 0.00 | 01-NOV-00:10 | 28.50 | 23.82 |
December | 0.779627E+09 | 504.65 | 07-DEC-13:50 | 32.80 | 23.14 | 0.00 | 0.00 | 01-DEC-00:10 | 32.80 | 23.14 |
Annual Sum or Average | 0.769750E+10 | 0.00 | ||||||||
Minimum of Months | 0.533885E+09 | 329.31 | 28.00 | 23.14 | 0.00 | 0.00 | 28.00 | 23.14 | ||
Maximum of Months | 0.793099E+09 | 504.65 | 33.80 | 28.18 | 0.00 | 0.00 | 33.80 | 28.18 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.886818E+09 | 1141.64 | 02-JAN-19:02 | 28.18 | 24.11 | 99960244.90 | 68.77 | 23-JAN-22:00 | 22.50 | 18.29 |
February | 0.849741E+09 | 1141.81 | 18-FEB-19:02 | 27.92 | 23.71 | 90198278.83 | 56.69 | 28-FEB-23:10 | 26.00 | 22.77 |
March | 0.984457E+09 | 1139.13 | 07-MAR-19:02 | 27.08 | 24.19 | 99129140.12 | 56.69 | 02-MAR-23:10 | 27.08 | 24.19 |
April | 0.101393E+10 | 1144.98 | 10-APR-18:02 | 30.40 | 27.80 | 95793580.04 | 56.69 | 23-APR-02:00 | 24.10 | 23.36 |
May | 0.111394E+10 | 1151.45 | 01-MAY-15:02 | 34.05 | 27.30 | 99256644.33 | 73.91 | 10-MAY-21:10 | 23.20 | 23.20 |
June | 0.115450E+10 | 1149.33 | 22-JUN-15:02 | 28.53 | 25.45 | 96208686.61 | 57.68 | 25-JUN-21:10 | 23.02 | 22.98 |
July | 0.107110E+10 | 1151.47 | 19-JUL-15:02 | 32.58 | 25.33 | 99337985.81 | 76.13 | 19-JUL-21:10 | 23.32 | 22.34 |
August | 0.100548E+10 | 1151.09 | 05-AUG-08:61 | 27.33 | 26.42 | 99241219.39 | 72.96 | 23-AUG-21:10 | 23.22 | 23.00 |
September | 0.944238E+09 | 1144.16 | 25-SEP-18:02 | 28.78 | 26.66 | 96043998.87 | 73.54 | 15-SEP-21:10 | 28.78 | 26.66 |
October | 0.926081E+09 | 1145.46 | 20-OCT-18:02 | 28.23 | 24.64 | 99310481.51 | 67.20 | 30-OCT-20:49 | 24.00 | 23.94 |
November | 0.880046E+09 | 1144.32 | 06-NOV-19:02 | 26.92 | 24.52 | 96745712.93 | 72.32 | 24-NOV-22:10 | 22.87 | 20.57 |
December | 0.866785E+09 | 1141.84 | 11-DEC-19:02 | 27.33 | 25.03 | 0.100236E+09 | 71.67 | 20-DEC-22:10 | 21.83 | 18.17 |
Annual Sum or Average | 0.116971E+11 | 0.117146E+10 | ||||||||
Minimum of Months | 0.849741E+09 | 1139.13 | 26.92 | 23.71 | 90198278.83 | 56.69 | 21.83 | 18.17 | ||
Maximum of Months | 0.115450E+10 | 1151.47 | 34.05 | 27.80 | 0.100236E+09 | 76.13 | 28.78 | 26.66 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.252436E+10 | 2619.93 | 23-JAN-09:01 | 24.37 | 19.55 | 99169675.36 | 56.70 | 23-JAN-22:10 | 23.58 | 19.14 |
February | 0.246336E+10 | 2601.93 | 15-FEB-09:02 | 27.33 | 24.86 | 89578640.19 | 56.70 | 07-FEB-22:49 | 27.33 | 24.86 |
March | 0.270622E+10 | 2605.07 | 16-MAR-08:61 | 27.17 | 24.05 | 99245260.82 | 56.70 | 20-MAR-22:40 | 27.13 | 23.45 |
April | 0.263220E+10 | 2615.78 | 10-APR-18:02 | 30.40 | 27.80 | 95962799.82 | 56.70 | 19-APR-22:00 | 28.50 | 25.82 |
May | 0.261292E+10 | 2618.93 | 03-MAY-08:62 | 29.50 | 26.79 | 99201326.36 | 56.69 | 31-MAY-21:49 | 23.98 | 23.76 |
June | 0.261789E+10 | 2617.29 | 07-JUN-08:62 | 30.17 | 27.73 | 96033024.49 | 56.70 | 14-JUN-23:30 | 28.00 | 26.50 |
July | 0.233858E+10 | 2628.23 | 14-JUL-08:61 | 25.83 | 24.40 | 99125560.71 | 56.70 | 26-JUL-22:10 | 26.17 | 24.38 |
August | 0.232384E+10 | 2612.34 | 30-AUG-08:61 | 27.33 | 25.50 | 99226790.13 | 56.70 | 15-AUG-22:10 | 27.33 | 25.50 |
September | 0.232089E+10 | 2611.23 | 01-SEP-18:02 | 29.28 | 26.81 | 95949123.54 | 56.70 | 01-SEP-21:40 | 27.30 | 25.50 |
October | 0.228647E+10 | 2612.14 | 02-OCT-08:61 | 27.33 | 24.87 | 99153773.82 | 56.70 | 16-OCT-22:10 | 27.08 | 25.43 |
November | 0.232731E+10 | 2607.89 | 09-NOV-09:01 | 27.95 | 24.49 | 95989823.92 | 56.70 | 07-NOV-22:30 | 27.95 | 24.49 |
December | 0.243248E+10 | 2656.14 | 15-DEC-09:01 | 26.25 | 20.66 | 99131093.82 | 56.70 | 04-DEC-22:10 | 26.25 | 20.66 |
Annual Sum or Average | 0.295865E+11 | 0.116777E+10 | ||||||||
Minimum of Months | 0.228647E+10 | 2601.93 | 24.37 | 19.55 | 89578640.19 | 56.69 | 23.58 | 19.14 | ||
Maximum of Months | 0.270622E+10 | 2656.14 | 30.40 | 27.80 | 99245260.82 | 56.70 | 28.50 | 26.50 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.212253E+10 | 2645.68 | 21-JAN-09:11 | 25.70 | 20.28 | 0.100916E+09 | 72.50 | 23-JAN-22:00 | 22.50 | 18.29 |
February | 0.216912E+10 | 2834.04 | 24-FEB-09:11 | 26.07 | 19.98 | 90962357.23 | 56.70 | 22-FEB-22:40 | 26.07 | 19.98 |
March | 0.257878E+10 | 2643.76 | 03-MAR-16:01 | 32.33 | 23.65 | 99429291.78 | 56.70 | 09-MAR-22:30 | 26.60 | 23.45 |
April | 0.264612E+10 | 2636.92 | 10-APR-18:02 | 30.40 | 27.80 | 96000648.36 | 56.69 | 21-APR-03:00 | 26.00 | 24.56 |
May | 0.269419E+10 | 2637.26 | 19-MAY-08:62 | 30.17 | 28.35 | 99430489.33 | 77.92 | 31-MAY-21:00 | 24.10 | 23.85 |
June | 0.276977E+10 | 2639.26 | 24-JUN-20:11 | 24.00 | 24.00 | 96354377.19 | 59.87 | 25-JUN-21:10 | 23.02 | 22.98 |
July | 0.242523E+10 | 2639.00 | 14-JUL-08:61 | 25.83 | 24.40 | 99573215.63 | 78.95 | 19-JUL-21:10 | 23.32 | 22.34 |
August | 0.236119E+10 | 2644.43 | 17-AUG-08:61 | 29.33 | 27.55 | 99496839.30 | 76.65 | 23-AUG-21:00 | 24.30 | 22.91 |
September | 0.227754E+10 | 2631.04 | 01-SEP-18:02 | 29.28 | 26.81 | 96331480.94 | 75.16 | 15-SEP-21:10 | 23.03 | 23.03 |
October | 0.214921E+10 | 2642.95 | 02-OCT-08:61 | 27.33 | 24.87 | 99661213.46 | 67.38 | 30-OCT-20:49 | 24.00 | 23.94 |
November | 0.205821E+10 | 2677.25 | 22-NOV-07:41 | 25.67 | 22.37 | 97299173.23 | 75.27 | 24-NOV-22:10 | 22.87 | 20.57 |
December | 0.202054E+10 | 2665.89 | 27-DEC-09:01 | 26.40 | 20.69 | 0.101199E+09 | 74.47 | 26-DEC-22:10 | 26.40 | 20.69 |
Annual Sum or Average | 0.282724E+11 | 0.117665E+10 | ||||||||
Minimum of Months | 0.202054E+10 | 2631.04 | 24.00 | 19.98 | 90962357.23 | 56.69 | 22.50 | 18.29 | ||
Maximum of Months | 0.276977E+10 | 2834.04 | 32.33 | 28.35 | 0.101199E+09 | 78.95 | 26.60 | 24.56 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.680882E+10 | 2671.56 | 31-JAN-22:10 | 26.33 | 22.10 | 0.149062E+10 | 915.64 | 31-JAN-22:30 | 26.20 | 22.13 |
February | 0.627231E+10 | 2694.02 | 24-FEB-22:10 | 26.67 | 22.83 | 0.137463E+10 | 923.51 | 24-FEB-22:30 | 26.40 | 22.68 |
March | 0.687303E+10 | 2672.61 | 29-MAR-21:10 | 28.03 | 23.69 | 0.151338E+10 | 915.83 | 21-MAR-21:30 | 28.03 | 23.69 |
April | 0.663857E+10 | 2675.57 | 28-APR-21:10 | 28.43 | 25.81 | 0.145745E+10 | 916.82 | 28-APR-21:30 | 28.30 | 25.78 |
May | 0.692882E+10 | 2754.74 | 06-MAY-21:10 | 29.85 | 26.27 | 0.152134E+10 | 941.89 | 05-MAY-21:30 | 29.85 | 26.27 |
June | 0.685085E+10 | 3208.13 | 13-JUN-18:05 | 31.80 | 28.00 | 0.150326E+10 | 951.83 | 12-JUN-22:19 | 31.80 | 28.00 |
July | 0.677416E+10 | 2641.72 | 27-JUL-21:10 | 26.97 | 24.11 | 0.148474E+10 | 904.51 | 27-JUL-21:30 | 26.90 | 24.09 |
August | 0.667892E+10 | 2659.20 | 14-AUG-21:10 | 28.95 | 27.94 | 0.147053E+10 | 910.51 | 14-AUG-21:40 | 28.80 | 27.23 |
September | 0.646680E+10 | 2639.68 | 08-SEP-21:10 | 27.68 | 24.93 | 0.141930E+10 | 904.34 | 08-SEP-21:30 | 27.05 | 24.38 |
October | 0.666468E+10 | 2625.47 | 05-OCT-21:10 | 26.65 | 25.42 | 0.146079E+10 | 899.19 | 05-OCT-21:40 | 27.10 | 25.72 |
November | 0.655032E+10 | 2676.46 | 22-NOV-22:10 | 25.42 | 23.59 | 0.143306E+10 | 916.65 | 22-NOV-22:30 | 25.05 | 23.51 |
December | 0.678247E+10 | 2696.36 | 08-DEC-22:10 | 27.92 | 23.84 | 0.148411E+10 | 924.24 | 08-DEC-22:30 | 27.55 | 23.96 |
Annual Sum or Average | 0.802897E+11 | 0.176132E+11 | ||||||||
Minimum of Months | 0.627231E+10 | 2625.47 | 25.42 | 22.10 | 0.137463E+10 | 899.19 | 25.05 | 22.13 | ||
Maximum of Months | 0.692882E+10 | 3208.13 | 31.80 | 28.00 | 0.152134E+10 | 951.83 | 31.80 | 28.00 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.258451E+10 | 3077.80 | 10-JAN-19:02 | 28.12 | 25.01 | 99134196.84 | 56.70 | 11-JAN-00:10 | 26.15 | 23.32 |
February | 0.248997E+10 | 3074.23 | 08-FEB-19:02 | 27.08 | 23.13 | 89554620.37 | 56.70 | 17-FEB-00:00 | 25.60 | 22.66 |
March | 0.281227E+10 | 3084.74 | 07-MAR-19:02 | 27.08 | 24.19 | 99219444.70 | 56.70 | 24-MAR-00:40 | 26.87 | 24.08 |
April | 0.274473E+10 | 3096.70 | 10-APR-18:02 | 30.40 | 27.80 | 95943485.87 | 56.70 | 14-APR-21:00 | 27.30 | 25.54 |
May | 0.267572E+10 | 3122.68 | 18-MAY-18:02 | 28.90 | 27.35 | 99180834.64 | 56.70 | 06-MAY-03:39 | 28.90 | 27.35 |
June | 0.266666E+10 | 3105.91 | 29-JUN-18:02 | 28.83 | 25.94 | 96011385.59 | 56.70 | 28-JUN-00:40 | 28.83 | 25.94 |
July | 0.240644E+10 | 3102.83 | 06-JUL-18:02 | 24.97 | 24.23 | 99077849.38 | 56.70 | 17-JUL-22:10 | 24.00 | 23.26 |
August | 0.239921E+10 | 3111.89 | 30-AUG-18:02 | 25.12 | 24.91 | 99182100.51 | 56.70 | 15-AUG-23:49 | 25.12 | 24.91 |
September | 0.240203E+10 | 3109.52 | 25-SEP-18:02 | 28.78 | 26.66 | 95921831.99 | 56.70 | 28-SEP-22:00 | 26.00 | 24.56 |
October | 0.235518E+10 | 3112.97 | 03-OCT-18:02 | 28.33 | 25.79 | 99112490.11 | 56.70 | 24-OCT-22:49 | 25.97 | 25.21 |
November | 0.237550E+10 | 3101.96 | 29-NOV-19:02 | 26.50 | 24.47 | 95970448.00 | 56.70 | 13-NOV-23:49 | 26.50 | 24.47 |
December | 0.247612E+10 | 3079.63 | 18-DEC-16:02 | 26.17 | 24.97 | 99104868.80 | 56.70 | 04-DEC-22:00 | 26.17 | 24.97 |
Annual Sum or Average | 0.303883E+11 | 0.116741E+10 | ||||||||
Minimum of Months | 0.235518E+10 | 3074.23 | 24.97 | 23.13 | 89554620.37 | 56.70 | 24.00 | 22.66 | ||
Maximum of Months | 0.281227E+10 | 3122.68 | 30.40 | 27.80 | 99219444.70 | 56.70 | 28.90 | 27.35 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.220857E+10 | 3107.83 | 23-JAN-22:51 | 22.50 | 18.29 | 0.100230E+09 | 71.23 | 23-JAN-22:00 | 22.50 | 18.29 |
February | 0.221701E+10 | 3115.02 | 14-FEB-19:02 | 29.25 | 25.53 | 90438540.10 | 56.70 | 23-FEB-00:49 | 26.17 | 21.90 |
March | 0.268637E+10 | 3133.00 | 07-MAR-19:02 | 27.08 | 24.19 | 99342181.89 | 56.70 | 13-MAR-00:30 | 26.20 | 24.00 |
April | 0.275977E+10 | 3128.12 | 10-APR-18:02 | 30.40 | 27.80 | 95995341.79 | 56.70 | 01-APR-01:10 | 30.40 | 27.80 |
May | 0.276170E+10 | 3146.12 | 18-MAY-18:02 | 28.90 | 27.35 | 99434788.34 | 80.63 | 10-MAY-21:00 | 28.90 | 27.35 |
June | 0.282692E+10 | 3172.05 | 12-JUN-18:02 | 31.90 | 26.94 | 96341186.33 | 62.88 | 25-JUN-21:00 | 23.10 | 22.86 |
July | 0.249877E+10 | 3121.08 | 06-JUL-18:02 | 24.97 | 24.23 | 99555423.84 | 84.75 | 19-JUL-21:00 | 23.40 | 22.42 |
August | 0.243891E+10 | 3140.32 | 30-AUG-18:02 | 25.12 | 24.91 | 99476475.13 | 80.20 | 23-AUG-21:00 | 25.12 | 24.91 |
September | 0.235896E+10 | 3151.09 | 25-SEP-18:02 | 28.78 | 26.66 | 96342720.27 | 77.39 | 15-SEP-21:10 | 28.78 | 26.66 |
October | 0.221799E+10 | 3149.74 | 17-OCT-18:02 | 28.22 | 26.28 | 99618329.44 | 69.43 | 30-OCT-20:49 | 24.00 | 23.94 |
November | 0.211160E+10 | 3128.65 | 20-NOV-19:02 | 28.47 | 25.77 | 97111571.94 | 75.29 | 24-NOV-22:10 | 22.87 | 20.57 |
December | 0.208890E+10 | 3080.82 | 26-DEC-19:02 | 26.17 | 23.50 | 0.100557E+09 | 75.34 | 26-DEC-22:00 | 22.00 | 19.30 |
Annual Sum or Average | 0.291755E+11 | 0.117444E+10 | ||||||||
Minimum of Months | 0.208890E+10 | 3080.82 | 22.50 | 18.29 | 90438540.10 | 56.70 | 22.00 | 18.29 | ||
Maximum of Months | 0.282692E+10 | 3172.05 | 31.90 | 27.80 | 0.100557E+09 | 84.75 | 30.40 | 27.80 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.177210E+10 | 1499.32 | 12-JAN-09:02 | 27.88 | 23.53 | 99214217.52 | 56.69 | 05-JAN-00:10 | 27.88 | 23.53 |
February | 0.159111E+10 | 1497.05 | 15-FEB-16:02 | 30.08 | 24.90 | 89604079.19 | 56.69 | 13-FEB-03:09 | 30.08 | 24.90 |
March | 0.159874E+10 | 1495.56 | 07-MAR-19:02 | 27.08 | 24.19 | 99238576.28 | 56.70 | 07-MAR-22:49 | 26.07 | 22.52 |
April | 0.145117E+10 | 1493.79 | 10-APR-18:02 | 30.40 | 27.80 | 95928899.39 | 56.69 | 23-APR-00:10 | 24.72 | 23.49 |
May | 0.147993E+10 | 1498.54 | 18-MAY-18:02 | 28.90 | 27.35 | 99177205.81 | 56.69 | 09-MAY-01:30 | 28.90 | 27.35 |
June | 0.143721E+10 | 1495.19 | 24-JUN-18:02 | 24.57 | 24.34 | 96002549.05 | 56.69 | 21-JUN-01:49 | 24.57 | 24.34 |
July | 0.136045E+10 | 1494.29 | 03-JUL-18:02 | 28.00 | 24.30 | 99076486.77 | 56.69 | 03-JUL-21:19 | 27.27 | 23.87 |
August | 0.133300E+10 | 1499.65 | 21-AUG-15:02 | 27.90 | 25.69 | 99177604.81 | 56.70 | 09-AUG-22:10 | 27.90 | 25.69 |
September | 0.138052E+10 | 1494.11 | 11-SEP-18:02 | 27.92 | 25.80 | 95922886.09 | 56.69 | 09-SEP-02:20 | 27.92 | 25.80 |
October | 0.146800E+10 | 1502.27 | 24-OCT-18:02 | 26.92 | 25.49 | 99138017.64 | 56.70 | 13-OCT-21:10 | 26.92 | 25.49 |
November | 0.158717E+10 | 1503.38 | 22-NOV-09:02 | 28.22 | 23.51 | 96003415.17 | 56.70 | 20-NOV-23:40 | 28.22 | 23.51 |
December | 0.173947E+10 | 1501.61 | 02-DEC-09:02 | 27.30 | 23.76 | 99173914.62 | 56.69 | 11-DEC-22:30 | 24.70 | 24.33 |
Annual Sum or Average | 0.181989E+11 | 0.116766E+10 | ||||||||
Minimum of Months | 0.133300E+10 | 1493.79 | 24.57 | 23.51 | 89604079.19 | 56.69 | 24.57 | 22.52 | ||
Maximum of Months | 0.177210E+10 | 1503.38 | 30.40 | 27.80 | 99238576.28 | 56.70 | 30.08 | 27.35 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.453640E+11 | 23062.44 | 03-JAN-22:10 | 26.88 | 23.35 | 0.190444E+11 | 11348.41 | 23-JAN-23:10 | 22.33 | 18.26 |
February | 0.417579E+11 | 23143.55 | 15-FEB-23:00 | 27.00 | 24.40 | 0.172801E+11 | 11347.31 | 24-FEB-04:19 | 23.07 | 19.40 |
March | 0.469157E+11 | 23753.93 | 28-MAR-21:10 | 28.00 | 25.10 | 0.192214E+11 | 11347.34 | 03-MAR-23:19 | 28.00 | 25.10 |
April | 0.462126E+11 | 24189.88 | 28-APR-21:10 | 28.43 | 25.81 | 0.185894E+11 | 11347.33 | 20-APR-22:19 | 28.43 | 25.81 |
May | 0.482599E+11 | 24848.05 | 05-MAY-21:10 | 29.02 | 26.76 | 0.192231E+11 | 11348.75 | 31-MAY-22:10 | 24.07 | 23.84 |
June | 0.477452E+11 | 25406.51 | 12-JUN-21:10 | 29.73 | 26.89 | 0.186759E+11 | 11347.33 | 28-JUN-22:19 | 28.07 | 27.07 |
July | 0.472434E+11 | 24753.59 | 14-JUL-21:10 | 28.23 | 24.46 | 0.191521E+11 | 11348.88 | 19-JUL-22:10 | 23.42 | 22.43 |
August | 0.464178E+11 | 24278.71 | 01-AUG-21:10 | 28.85 | 27.27 | 0.191643E+11 | 11348.75 | 23-AUG-22:10 | 24.25 | 23.10 |
September | 0.448542E+11 | 23855.53 | 05-SEP-21:10 | 28.97 | 26.71 | 0.185057E+11 | 11348.59 | 15-SEP-22:10 | 23.17 | 23.17 |
October | 0.453897E+11 | 23301.84 | 16-OCT-21:40 | 27.07 | 25.64 | 0.190583E+11 | 11347.79 | 30-OCT-22:19 | 23.93 | 23.52 |
November | 0.439624E+11 | 23055.07 | 03-NOV-22:00 | 26.30 | 25.12 | 0.184342E+11 | 11348.60 | 24-NOV-23:10 | 23.27 | 20.53 |
December | 0.449530E+11 | 23134.36 | 08-DEC-22:10 | 27.92 | 23.84 | 0.190306E+11 | 11348.61 | 20-DEC-23:10 | 21.00 | 17.84 |
Annual Sum or Average | 0.549076E+12 | 0.225379E+12 | ||||||||
Minimum of Months | 0.417579E+11 | 23055.07 | 26.30 | 23.35 | 0.172801E+11 | 11347.31 | 21.00 | 17.84 | ||
Maximum of Months | 0.482599E+11 | 25406.51 | 29.73 | 27.27 | 0.192231E+11 | 11348.88 | 28.43 | 27.07 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.479840E+11 | 24280.22 | 03-JAN-22:10 | 26.88 | 23.35 | 0.190939E+11 | 11348.42 | 23-JAN-23:10 | 22.33 | 18.26 |
February | 0.441003E+11 | 24312.60 | 27-FEB-22:10 | 26.33 | 23.25 | 0.173132E+11 | 11347.33 | 24-FEB-04:19 | 26.33 | 23.25 |
March | 0.495681E+11 | 24961.08 | 28-MAR-21:10 | 28.00 | 25.10 | 0.192583E+11 | 11347.36 | 03-MAR-23:19 | 28.00 | 25.10 |
April | 0.488294E+11 | 25417.51 | 28-APR-21:10 | 28.43 | 25.81 | 0.186229E+11 | 11347.35 | 20-APR-22:19 | 28.43 | 25.81 |
May | 0.510170E+11 | 26068.79 | 05-MAY-21:10 | 29.02 | 26.76 | 0.192529E+11 | 11348.75 | 31-MAY-22:10 | 24.07 | 23.84 |
June | 0.504062E+11 | 26641.76 | 12-JUN-21:10 | 29.73 | 26.89 | 0.187005E+11 | 11347.34 | 28-JUN-22:19 | 28.07 | 27.07 |
July | 0.500861E+11 | 26033.92 | 14-JUL-21:10 | 28.23 | 24.46 | 0.191941E+11 | 11348.88 | 19-JUL-22:10 | 23.42 | 22.43 |
August | 0.492734E+11 | 25556.88 | 01-AUG-21:10 | 28.85 | 27.27 | 0.192196E+11 | 11348.75 | 23-AUG-22:10 | 24.25 | 23.10 |
September | 0.475597E+11 | 25102.24 | 05-SEP-21:10 | 28.97 | 26.71 | 0.185566E+11 | 11348.59 | 15-SEP-22:10 | 23.17 | 23.17 |
October | 0.481748E+11 | 24528.07 | 16-OCT-21:10 | 27.02 | 25.86 | 0.191150E+11 | 11347.81 | 30-OCT-22:19 | 23.93 | 23.52 |
November | 0.465691E+11 | 24305.50 | 14-NOV-22:10 | 27.15 | 26.04 | 0.184849E+11 | 11348.60 | 24-NOV-23:10 | 23.27 | 20.53 |
December | 0.476042E+11 | 24292.18 | 08-DEC-22:10 | 27.92 | 23.84 | 0.190866E+11 | 11348.61 | 20-DEC-23:10 | 21.00 | 17.84 |
Annual Sum or Average | 0.581172E+12 | 0.225898E+12 | ||||||||
Minimum of Months | 0.441003E+11 | 24280.22 | 26.33 | 23.25 | 0.173132E+11 | 11347.33 | 21.00 | 17.84 | ||
Maximum of Months | 0.510170E+11 | 26641.76 | 29.73 | 27.27 | 0.192583E+11 | 11348.88 | 28.43 | 27.07 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.580738E+11 | 29647.17 | 04-JAN-11:50 | 33.00 | 23.69 | 0.187805E+11 | 11319.62 | 28-JAN-18:19 | 26.73 | 22.58 |
February | 0.531661E+11 | 29830.84 | 20-FEB-11:50 | 31.33 | 23.96 | 0.169693E+11 | 11319.58 | 25-FEB-18:19 | 28.57 | 21.30 |
March | 0.589911E+11 | 30183.94 | 19-MAR-10:50 | 33.70 | 23.06 | 0.187963E+11 | 11319.65 | 18-MAR-17:19 | 33.70 | 23.06 |
April | 0.575171E+11 | 30437.12 | 09-APR-10:50 | 33.42 | 26.18 | 0.181902E+11 | 11319.65 | 15-APR-17:19 | 30.50 | 25.05 |
May | 0.590830E+11 | 30621.07 | 07-MAY-10:50 | 33.03 | 26.51 | 0.187960E+11 | 11319.65 | 27-MAY-17:19 | 32.33 | 26.08 |
June | 0.576932E+11 | 30444.88 | 24-JUN-10:50 | 32.20 | 27.56 | 0.181958E+11 | 11319.65 | 17-JUN-17:19 | 32.20 | 27.56 |
July | 0.583389E+11 | 29885.97 | 15-JUL-18:03 | 31.95 | 25.35 | 0.187877E+11 | 11319.65 | 15-JUL-17:19 | 31.95 | 25.35 |
August | 0.579423E+11 | 30118.06 | 27-AUG-10:50 | 32.72 | 27.53 | 0.187914E+11 | 11319.65 | 26-AUG-17:19 | 32.72 | 27.53 |
September | 0.564708E+11 | 30276.69 | 03-SEP-10:50 | 31.78 | 28.02 | 0.181841E+11 | 11319.65 | 02-SEP-17:19 | 31.78 | 28.02 |
October | 0.574847E+11 | 30028.95 | 07-OCT-10:50 | 31.43 | 26.03 | 0.187822E+11 | 11319.65 | 28-OCT-17:19 | 29.50 | 26.26 |
November | 0.559756E+11 | 29802.91 | 23-NOV-11:50 | 30.88 | 24.99 | 0.181748E+11 | 11319.65 | 04-NOV-17:19 | 30.88 | 24.99 |
December | 0.577750E+11 | 29741.73 | 31-DEC-11:50 | 31.00 | 24.59 | 0.187777E+11 | 11319.58 | 02-DEC-18:19 | 31.00 | 24.59 |
Annual Sum or Average | 0.688512E+12 | 0.221226E+12 | ||||||||
Minimum of Months | 0.531661E+11 | 29647.17 | 30.88 | 23.06 | 0.169693E+11 | 11319.58 | 26.73 | 21.30 | ||
Maximum of Months | 0.590830E+11 | 30621.07 | 33.70 | 28.02 | 0.187963E+11 | 11319.65 | 33.70 | 28.02 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.140317E+11 | 6840.01 | 05-JAN-16:03 | 32.17 | 22.74 | 0.161365E+10 | 1007.36 | 31-JAN-22:10 | 26.33 | 22.10 |
February | 0.129117E+11 | 6663.00 | 22-FEB-16:03 | 34.42 | 21.55 | 0.148307E+10 | 1007.36 | 24-FEB-22:10 | 26.67 | 22.83 |
March | 0.142603E+11 | 6628.56 | 28-MAR-15:13 | 34.40 | 25.56 | 0.164717E+10 | 1007.38 | 13-MAR-22:19 | 34.40 | 25.56 |
April | 0.139448E+11 | 6502.15 | 01-APR-14:40 | 35.17 | 26.82 | 0.159577E+10 | 1007.38 | 26-APR-22:19 | 28.13 | 23.80 |
May | 0.145172E+11 | 7196.40 | 06-MAY-14:30 | 37.00 | 27.34 | 0.164255E+10 | 1007.38 | 30-MAY-22:19 | 27.13 | 26.43 |
June | 0.144349E+11 | 7406.80 | 13-JUN-15:40 | 35.67 | 28.55 | 0.160881E+10 | 1007.38 | 11-JUN-23:19 | 35.67 | 28.55 |
July | 0.138792E+11 | 6370.33 | 15-JUL-17:13 | 32.67 | 25.56 | 0.160898E+10 | 1007.35 | 14-JUL-21:10 | 32.67 | 25.56 |
August | 0.136449E+11 | 6169.42 | 14-AUG-15:03 | 31.30 | 27.86 | 0.159002E+10 | 1007.38 | 14-AUG-22:19 | 28.47 | 26.67 |
September | 0.133624E+11 | 5925.62 | 06-SEP-20:10 | 28.33 | 26.54 | 0.154995E+10 | 1007.35 | 08-SEP-21:30 | 27.05 | 24.38 |
October | 0.136102E+11 | 5623.17 | 07-OCT-14:30 | 31.30 | 26.08 | 0.157910E+10 | 1007.35 | 16-OCT-21:10 | 27.02 | 25.86 |
November | 0.134131E+11 | 6248.33 | 22-NOV-14:00 | 31.50 | 24.56 | 0.154595E+10 | 1007.35 | 03-NOV-21:10 | 31.50 | 24.56 |
December | 0.138837E+11 | 6735.24 | 08-DEC-14:30 | 33.00 | 23.44 | 0.159682E+10 | 1007.38 | 08-DEC-23:19 | 26.67 | 24.28 |
Annual Sum or Average | 0.165894E+12 | 0.190618E+11 | ||||||||
Minimum of Months | 0.129117E+11 | 5623.17 | 28.33 | 21.55 | 0.148307E+10 | 1007.35 | 26.33 | 22.10 | ||
Maximum of Months | 0.145172E+11 | 7406.80 | 37.00 | 28.55 | 0.164717E+10 | 1007.38 | 35.67 | 28.55 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 335613.95 | 415.23 | 25-JAN-09:05 | 23.90 |
February | 374409.01 | 411.76 | 08-FEB-09:05 | 25.52 |
March | 868695.33 | 408.01 | 13-MAR-08:05 | 27.25 |
April | 624600.80 | 438.36 | 21-APR-08:04 | 26.17 |
May | 546765.22 | 452.18 | 17-MAY-08:04 | 24.00 |
June | 475010.38 | 419.18 | 26-JUN-08:05 | 28.33 |
July | 1012697.97 | 446.02 | 07-JUL-08:04 | 25.25 |
August | 836195.11 | 446.79 | 20-AUG-18:04 | 25.00 |
September | 955588.25 | 441.52 | 21-SEP-08:04 | 24.83 |
October | 644957.45 | 446.20 | 26-OCT-08:04 | 25.77 |
November | 544230.29 | 442.73 | 01-NOV-08:04 | 26.17 |
December | 398867.14 | 415.47 | 20-DEC-09:05 | 24.40 |
Annual Sum or Average | 7617630.87 | |||
Minimum of Months | 335613.95 | 408.01 | 23.90 | |
Maximum of Months | 1012697.97 | 452.18 | 28.33 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 408163.19 | 443.98 | 13-JAN-09:04 | 27.87 |
February | 393876.44 | 427.31 | 15-FEB-07:14 | 25.40 |
March | 1111124.00 | 418.26 | 04-MAR-09:05 | 29.40 |
April | 724819.85 | 442.63 | 10-APR-08:04 | 28.75 |
May | 461704.40 | 460.37 | 17-MAY-08:04 | 24.00 |
June | 271123.05 | 413.56 | 04-JUN-08:05 | 27.50 |
July | 787682.39 | 453.58 | 07-JUL-08:04 | 25.25 |
August | 782592.41 | 445.86 | 20-AUG-18:04 | 25.00 |
September | 1186338.06 | 448.46 | 16-SEP-08:04 | 26.33 |
October | 1009960.65 | 448.82 | 18-OCT-08:04 | 26.17 |
November | 1097513.09 | 442.09 | 01-NOV-08:04 | 26.17 |
December | 428555.84 | 412.13 | 18-DEC-19:05 | 26.08 |
Annual Sum or Average | 8663453.37 | |||
Minimum of Months | 271123.05 | 412.13 | 24.00 | |
Maximum of Months | 1186338.06 | 460.37 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 172986.57 | 187.58 | 24-JAN-16:07 | 29.50 |
February | 102451.73 | 137.42 | 12-FEB-19:07 | 27.92 |
March | 232024.02 | 156.42 | 20-MAR-18:07 | 29.87 |
April | 164995.04 | 141.07 | 04-APR-18:07 | 29.30 |
May | 38031.53 | 81.50 | 21-MAY-18:07 | 28.45 |
June | 48762.32 | 118.84 | 30-JUN-18:07 | 26.90 |
July | 65486.22 | 125.36 | 17-JUL-18:07 | 24.77 |
August | 122572.91 | 130.90 | 19-AUG-15:07 | 24.15 |
September | 181494.49 | 160.54 | 16-SEP-15:07 | 27.07 |
October | 94629.29 | 119.66 | 22-OCT-15:07 | 25.42 |
November | 176580.60 | 206.68 | 23-NOV-16:07 | 27.33 |
December | 236191.10 | 177.36 | 20-DEC-16:07 | 30.33 |
Annual Sum or Average | 1636205.82 | |||
Minimum of Months | 38031.53 | 81.50 | 24.15 | |
Maximum of Months | 236191.10 | 206.68 | 30.33 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8896.57 | 88.97 | 01-JAN-19:05 | 25.08 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 2799.82 | 24.80 | 20-AUG-15:06 | 26.00 |
September | 11452.27 | 133.61 | 18-SEP-08:06 | 24.00 |
October | 40785.62 | 360.82 | 23-OCT-08:05 | 24.75 |
November | 562.41 | 6.56 | 27-NOV-09:06 | 24.68 |
December | 643.10 | 9.65 | 22-DEC-09:04 | 26.17 |
Annual Sum or Average | 65139.80 | |||
Minimum of Months | 0.00 | 0.00 | 24.00 | |
Maximum of Months | 40785.62 | 360.82 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 48733.85 | 211.67 | 09-JAN-07:56 | 25.00 |
February | 543.33 | 6.34 | 15-FEB-07:16 | 25.40 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 4412.43 | 51.48 | 17-MAY-08:04 | 24.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 16911.88 | 197.31 | 29-JUL-06:46 | 26.08 |
August | 14309.77 | 166.95 | 20-AUG-08:06 | 26.33 |
September | 45121.27 | 353.53 | 18-SEP-08:36 | 24.00 |
October | 72123.71 | 306.06 | 26-OCT-18:05 | 24.98 |
November | 3098.70 | 41.32 | 27-NOV-09:26 | 25.05 |
December | 22804.56 | 151.62 | 17-DEC-09:46 | 26.00 |
Annual Sum or Average | 228059.51 | |||
Minimum of Months | 0.00 | 0.00 | 24.00 | |
Maximum of Months | 72123.71 | 353.53 | 27.53 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 689793.41 | 478.56 | 24-JAN-09:04 | 19.07 |
February | 677510.20 | 433.98 | 08-FEB-09:05 | 25.52 |
March | 1106599.89 | 460.09 | 16-MAR-08:04 | 27.17 |
April | 943924.72 | 471.55 | 21-APR-08:04 | 26.17 |
May | 782665.15 | 476.31 | 17-MAY-08:04 | 24.00 |
June | 763741.32 | 461.26 | 25-JUN-08:04 | 27.33 |
July | 1265098.66 | 474.96 | 17-JUL-08:04 | 25.75 |
August | 1194314.95 | 468.11 | 20-AUG-18:04 | 25.00 |
September | 1130387.53 | 466.61 | 20-SEP-08:04 | 26.17 |
October | 1012206.31 | 465.09 | 26-OCT-08:04 | 25.77 |
November | 668213.64 | 464.81 | 01-NOV-08:04 | 26.17 |
December | 568701.73 | 443.53 | 17-DEC-09:05 | 24.40 |
Annual Sum or Average | 10803157.50 | |||
Minimum of Months | 568701.73 | 433.98 | 19.07 | |
Maximum of Months | 1265098.66 | 478.56 | 27.33 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 490444.97 | 475.56 | 13-JAN-09:04 | 27.87 |
February | 412833.43 | 420.38 | 16-FEB-09:05 | 27.27 |
March | 1131459.23 | 467.11 | 16-MAR-08:04 | 27.17 |
April | 900846.90 | 473.10 | 21-APR-08:04 | 26.17 |
May | 638434.13 | 480.43 | 17-MAY-08:04 | 24.00 |
June | 389035.03 | 429.33 | 20-JUN-08:05 | 26.33 |
July | 993464.97 | 476.76 | 18-JUL-08:04 | 24.93 |
August | 1121659.22 | 467.36 | 19-AUG-08:04 | 25.33 |
September | 1202633.52 | 472.76 | 20-SEP-08:04 | 26.17 |
October | 1239974.19 | 472.78 | 18-OCT-08:04 | 26.17 |
November | 1114551.16 | 465.58 | 01-NOV-08:04 | 26.17 |
December | 543662.10 | 467.66 | 21-DEC-22:54 | 23.00 |
Annual Sum or Average | 10178998.85 | |||
Minimum of Months | 389035.03 | 420.38 | 23.00 | |
Maximum of Months | 1239974.19 | 480.43 | 27.87 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 26295.31 | 132.60 | 01-JAN-09:06 | 24.28 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 8012.18 | 91.13 | 15-MAR-08:06 | 24.50 |
April | 2405.75 | 16.20 | 23-APR-08:06 | 26.67 |
May | 4553.76 | 28.47 | 26-MAY-08:06 | 27.17 |
June | 5774.22 | 29.71 | 01-JUN-08:06 | 26.00 |
July | 9603.75 | 48.25 | 19-JUL-08:06 | 26.70 |
August | 27132.05 | 73.56 | 20-AUG-08:06 | 26.33 |
September | 9693.45 | 54.00 | 17-SEP-08:06 | 26.32 |
October | 41980.07 | 64.49 | 18-OCT-08:06 | 26.17 |
November | 13298.61 | 155.15 | 27-NOV-09:06 | 24.68 |
December | 15979.85 | 107.20 | 19-DEC-09:06 | 26.40 |
Annual Sum or Average | 164728.99 | |||
Minimum of Months | 0.00 | 0.00 | 24.28 | |
Maximum of Months | 41980.07 | 155.15 | 27.17 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.136942E+11 | 13190.31 | 02-JAN-20:10 | 0.121516E+11 | 9632.53 | 02-JAN-20:10 |
February | 0.123646E+11 | 13190.31 | 01-FEB-20:10 | 0.109726E+11 | 9632.53 | 01-FEB-20:10 |
March | 0.137364E+11 | 13190.31 | 01-MAR-20:10 | 0.121771E+11 | 9632.53 | 01-MAR-20:10 |
April | 0.132299E+11 | 13190.31 | 03-APR-19:10 | 0.117446E+11 | 9632.53 | 03-APR-19:10 |
May | 0.137180E+11 | 13190.31 | 01-MAY-19:10 | 0.121662E+11 | 9632.53 | 01-MAY-19:10 |
June | 0.132906E+11 | 13190.31 | 01-JUN-19:10 | 0.117829E+11 | 9632.53 | 01-JUN-19:10 |
July | 0.136573E+11 | 13190.31 | 03-JUL-19:10 | 0.121279E+11 | 9632.53 | 03-JUL-19:10 |
August | 0.137417E+11 | 13190.31 | 01-AUG-19:10 | 0.121808E+11 | 9632.53 | 01-AUG-19:10 |
September | 0.132352E+11 | 13190.31 | 01-SEP-19:10 | 0.117482E+11 | 9632.53 | 01-SEP-19:10 |
October | 0.136889E+11 | 13190.31 | 02-OCT-19:10 | 0.121479E+11 | 9632.53 | 02-OCT-19:10 |
November | 0.132800E+11 | 13190.31 | 01-NOV-19:10 | 0.117774E+11 | 9632.53 | 01-NOV-19:10 |
December | 0.136573E+11 | 13190.31 | 01-DEC-20:10 | 0.121279E+11 | 9632.53 | 01-DEC-20:10 |
Annual Sum or Average | 0.161294E+12 | 0.143105E+12 | ||||
Minimum of Months | 0.123646E+11 | 13190.31 | 0.109726E+11 | 9632.53 | ||
Maximum of Months | 0.137417E+11 | 13190.31 | 0.121808E+11 | 9632.53 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.620421E+09 | 597.59 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.560184E+09 | 597.59 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.622334E+09 | 597.59 | 01-MAR-20:10 | 0.866718E+09 | 685.60 | 01-MAR-20:10 |
April | 0.599386E+09 | 597.59 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.621497E+09 | 597.59 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.602135E+09 | 597.59 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.618748E+09 | 597.59 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.622573E+09 | 597.59 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.599625E+09 | 597.59 | 01-SEP-19:10 | 0.836191E+09 | 685.60 | 01-SEP-19:10 |
October | 0.620182E+09 | 597.59 | 02-OCT-19:10 | 0.864640E+09 | 685.60 | 02-OCT-19:10 |
November | 0.601657E+09 | 597.59 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.618748E+09 | 597.59 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.730749E+10 | 0.101856E+11 | ||||
Minimum of Months | 0.560184E+09 | 597.59 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.622573E+09 | 597.59 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.718450E+09 | 692.02 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.648695E+09 | 692.02 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.720665E+09 | 692.02 | 01-MAR-20:10 | 0.100366E+10 | 793.93 | 01-MAR-20:10 |
April | 0.694091E+09 | 692.02 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.719696E+09 | 692.02 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.697275E+09 | 692.02 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.716513E+09 | 692.02 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.720942E+09 | 692.02 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.694368E+09 | 692.02 | 01-SEP-19:10 | 0.968312E+09 | 793.93 | 01-SEP-19:10 |
October | 0.718174E+09 | 692.02 | 02-OCT-19:10 | 0.100126E+10 | 793.93 | 02-OCT-19:10 |
November | 0.696721E+09 | 692.02 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.716513E+09 | 692.02 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.846210E+10 | 0.117950E+11 | ||||
Minimum of Months | 0.648695E+09 | 692.02 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.720942E+09 | 692.02 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.710312E+09 | 684.18 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.641347E+09 | 684.18 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.712502E+09 | 684.18 | 01-MAR-20:10 | 0.106120E+10 | 839.45 | 01-MAR-20:10 |
April | 0.686229E+09 | 684.18 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.711544E+09 | 684.18 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.689376E+09 | 684.18 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.708397E+09 | 684.18 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.712775E+09 | 684.18 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.686503E+09 | 684.18 | 01-SEP-19:10 | 0.102382E+10 | 839.45 | 01-SEP-19:10 |
October | 0.710039E+09 | 684.18 | 02-OCT-19:10 | 0.105866E+10 | 839.45 | 02-OCT-19:10 |
November | 0.688829E+09 | 684.18 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.708397E+09 | 684.18 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.836625E+10 | 0.124712E+11 | ||||
Minimum of Months | 0.641347E+09 | 684.18 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.712775E+09 | 684.18 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.261454E+09 | 251.84 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.236069E+09 | 251.84 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.262260E+09 | 251.84 | 01-MAR-20:10 | 0.306128E+09 | 242.16 | 01-MAR-20:10 |
April | 0.252589E+09 | 251.84 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.261907E+09 | 251.84 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.253748E+09 | 251.84 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.260749E+09 | 251.84 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.262360E+09 | 251.84 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.252690E+09 | 251.84 | 01-SEP-19:10 | 0.295345E+09 | 242.16 | 01-SEP-19:10 |
October | 0.261353E+09 | 251.84 | 02-OCT-19:10 | 0.305393E+09 | 242.16 | 02-OCT-19:10 |
November | 0.253546E+09 | 251.84 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.260749E+09 | 251.84 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.307947E+10 | 0.359760E+10 | ||||
Minimum of Months | 0.236069E+09 | 251.84 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.262360E+09 | 251.84 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.337502E+09 | 325.08 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.304733E+09 | 325.08 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.338542E+09 | 325.08 | 01-MAR-20:10 | 0.578079E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.326059E+09 | 325.08 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.338087E+09 | 325.08 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.327554E+09 | 325.08 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.336592E+09 | 325.08 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.338672E+09 | 325.08 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.326189E+09 | 325.08 | 01-SEP-19:10 | 0.557718E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.337372E+09 | 325.08 | 02-OCT-19:10 | 0.576693E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.327294E+09 | 325.08 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.336592E+09 | 325.08 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.397519E+10 | 0.679355E+11 | ||||
Minimum of Months | 0.304733E+09 | 325.08 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.338672E+09 | 325.08 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123718E+10 | 1701.53 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.111771E+10 | 1701.53 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.122372E+10 | 1701.53 | 01-MAR-20:10 | 0.122027E+10 | 965.27 | 01-MAR-20:10 |
April | 0.115398E+10 | 1701.53 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.120690E+10 | 1701.53 | 01-MAY-19:10 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.115355E+10 | 1701.53 | 01-JUN-19:10 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.119926E+10 | 1701.53 | 03-JUL-19:10 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.120405E+10 | 1701.53 | 01-AUG-19:10 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.119373E+10 | 1701.53 | 01-SEP-19:10 | 0.117729E+10 | 965.27 | 01-SEP-19:10 |
October | 0.123683E+10 | 1701.53 | 02-OCT-19:10 | 0.121734E+10 | 965.27 | 02-OCT-19:10 |
November | 0.119052E+10 | 1701.53 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.123366E+10 | 1701.53 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.143511E+11 | 0.143405E+11 | ||||
Minimum of Months | 0.111771E+10 | 1701.53 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.123718E+10 | 1701.53 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.934832E+10 | 9504.80 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.844610E+10 | 9504.80 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.937823E+10 | 9504.80 | 01-MAR-20:10 | 0.126786E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.902001E+10 | 9504.80 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.937693E+10 | 9504.80 | 01-MAY-19:10 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.906877E+10 | 9504.80 | 01-JUN-19:10 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.934270E+10 | 9504.80 | 03-JUL-19:10 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.938388E+10 | 9504.80 | 01-AUG-19:10 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.905757E+10 | 9504.80 | 01-SEP-19:10 | 0.122320E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.936575E+10 | 9504.80 | 02-OCT-19:10 | 0.126482E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.906574E+10 | 9504.80 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.932461E+10 | 9504.80 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.110179E+12 | 0.148998E+12 | ||||
Minimum of Months | 0.844610E+10 | 9504.80 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.938388E+10 | 9504.80 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196602E+09 | 177.88 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.177551E+09 | 177.88 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.195039E+09 | 177.88 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.190486E+09 | 177.88 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.195821E+09 | 177.88 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.188975E+09 | 177.88 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.197358E+09 | 177.88 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.195039E+09 | 177.88 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.190538E+09 | 177.88 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.196576E+09 | 177.88 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.189731E+09 | 177.88 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.197383E+09 | 177.88 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.231110E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.177551E+09 | 177.88 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.197383E+09 | 177.88 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196579E+09 | 177.86 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.177530E+09 | 177.86 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.195017E+09 | 177.86 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.190464E+09 | 177.86 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.195798E+09 | 177.86 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.188953E+09 | 177.86 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.197334E+09 | 177.86 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.195017E+09 | 177.86 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.190515E+09 | 177.86 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.196553E+09 | 177.86 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.189708E+09 | 177.86 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.197360E+09 | 177.86 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.231083E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.177530E+09 | 177.86 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.197360E+09 | 177.86 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123557E+09 | 111.79 | 01-JAN-19:10 | 0.217935E+09 | 232.19 | 01-JAN-08:09 |
February | 0.111584E+09 | 111.79 | 01-FEB-20:10 | 0.196843E+09 | 232.19 | 01-FEB-07:10 |
March | 0.122575E+09 | 111.79 | 01-MAR-20:10 | 0.217824E+09 | 232.19 | 01-MAR-07:10 |
April | 0.119713E+09 | 111.79 | 01-APR-18:10 | 0.210923E+09 | 232.19 | 01-APR-07:10 |
May | 0.123066E+09 | 111.79 | 01-MAY-19:10 | 0.217879E+09 | 232.19 | 01-MAY-06:10 |
June | 0.118764E+09 | 111.79 | 01-JUN-19:10 | 0.210812E+09 | 232.19 | 01-JUN-06:10 |
July | 0.124032E+09 | 111.79 | 01-JUL-18:10 | 0.217991E+09 | 232.19 | 01-JUL-07:10 |
August | 0.122575E+09 | 111.79 | 01-AUG-19:10 | 0.217824E+09 | 232.19 | 01-AUG-06:10 |
September | 0.119746E+09 | 111.79 | 01-SEP-19:10 | 0.210923E+09 | 232.19 | 01-SEP-06:10 |
October | 0.123541E+09 | 111.79 | 01-OCT-18:10 | 0.217935E+09 | 232.19 | 01-OCT-07:10 |
November | 0.119238E+09 | 111.79 | 01-NOV-19:10 | 0.210867E+09 | 232.19 | 01-NOV-06:10 |
December | 0.124048E+09 | 111.79 | 01-DEC-20:10 | 0.217991E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.145244E+10 | 0.256575E+10 | ||||
Minimum of Months | 0.111584E+09 | 111.79 | 0.196843E+09 | 232.19 | ||
Maximum of Months | 0.124048E+09 | 111.79 | 0.217991E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123591E+09 | 111.82 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 0.111614E+09 | 111.82 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 0.122608E+09 | 111.82 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 0.119746E+09 | 111.82 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 0.123099E+09 | 111.82 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 0.118796E+09 | 111.82 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 0.124066E+09 | 111.82 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 0.122608E+09 | 111.82 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 0.119778E+09 | 111.82 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 0.123574E+09 | 111.82 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 0.119271E+09 | 111.82 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 0.124082E+09 | 111.82 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.145283E+10 | 0.256645E+10 | ||||
Minimum of Months | 0.111614E+09 | 111.82 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 0.124082E+09 | 111.82 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196602E+09 | 177.88 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.177551E+09 | 177.88 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.195039E+09 | 177.88 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.190486E+09 | 177.88 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.195821E+09 | 177.88 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.188975E+09 | 177.88 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.197358E+09 | 177.88 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.195039E+09 | 177.88 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.190538E+09 | 177.88 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.196576E+09 | 177.88 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.189731E+09 | 177.88 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.197383E+09 | 177.88 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.231110E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.177551E+09 | 177.88 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.197383E+09 | 177.88 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196579E+09 | 177.86 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.177530E+09 | 177.86 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.195017E+09 | 177.86 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.190464E+09 | 177.86 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.195798E+09 | 177.86 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.188953E+09 | 177.86 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.197334E+09 | 177.86 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.195017E+09 | 177.86 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.190515E+09 | 177.86 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.196553E+09 | 177.86 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.189708E+09 | 177.86 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.197360E+09 | 177.86 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.231083E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.177530E+09 | 177.86 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.197360E+09 | 177.86 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.193865E+10 | 1867.32 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.175042E+10 | 1867.32 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.194462E+10 | 1867.32 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.187292E+10 | 1867.32 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.194201E+10 | 1867.32 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.188151E+10 | 1867.32 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.193342E+10 | 1867.32 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.194537E+10 | 1867.32 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.187367E+10 | 1867.32 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.193790E+10 | 1867.32 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.188002E+10 | 1867.32 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.193342E+10 | 1867.32 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.228339E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.175042E+10 | 1867.32 | 0.00 | 0.00 | |
Maximum of Months | 0.194537E+10 | 1867.32 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196602E+09 | 177.88 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.177551E+09 | 177.88 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.195039E+09 | 177.88 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.190486E+09 | 177.88 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.195821E+09 | 177.88 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.188975E+09 | 177.88 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.197358E+09 | 177.88 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.195039E+09 | 177.88 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.190538E+09 | 177.88 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.196576E+09 | 177.88 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.189731E+09 | 177.88 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.197383E+09 | 177.88 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.231110E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.177551E+09 | 177.88 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.197383E+09 | 177.88 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196579E+09 | 177.86 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.177530E+09 | 177.86 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.195017E+09 | 177.86 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.190464E+09 | 177.86 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.195798E+09 | 177.86 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.188953E+09 | 177.86 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.197334E+09 | 177.86 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.195017E+09 | 177.86 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.190515E+09 | 177.86 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.196553E+09 | 177.86 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.189708E+09 | 177.86 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.197360E+09 | 177.86 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.231083E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.177530E+09 | 177.86 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.197360E+09 | 177.86 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123591E+09 | 111.82 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 0.111614E+09 | 111.82 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 0.122608E+09 | 111.82 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 0.119746E+09 | 111.82 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 0.123099E+09 | 111.82 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 0.118796E+09 | 111.82 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 0.124066E+09 | 111.82 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 0.122608E+09 | 111.82 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 0.119778E+09 | 111.82 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 0.123574E+09 | 111.82 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 0.119271E+09 | 111.82 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 0.124082E+09 | 111.82 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.145283E+10 | 0.256645E+10 | ||||
Minimum of Months | 0.111614E+09 | 111.82 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 0.124082E+09 | 111.82 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.267303E+10 | 2988.03 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.239872E+10 | 2988.03 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.263668E+10 | 2988.03 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.249988E+10 | 2988.03 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.258463E+10 | 2988.03 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.247556E+10 | 2988.03 | 01-JUN-19:10 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.256073E+10 | 2988.03 | 03-JUL-19:10 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.259557E+10 | 2988.03 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.254900E+10 | 2988.03 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.265767E+10 | 2988.03 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.258012E+10 | 2988.03 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.266925E+10 | 2988.03 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.308808E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.239872E+10 | 2988.03 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.267303E+10 | 2988.03 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.267303E+10 | 2988.03 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.239872E+10 | 2988.03 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.263668E+10 | 2988.03 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.249988E+10 | 2988.03 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.258463E+10 | 2988.03 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.247556E+10 | 2988.03 | 01-JUN-19:10 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.256073E+10 | 2988.03 | 03-JUL-19:10 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.259557E+10 | 2988.03 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.254900E+10 | 2988.03 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.265767E+10 | 2988.03 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.258012E+10 | 2988.03 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.266925E+10 | 2988.03 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.308808E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.239872E+10 | 2988.03 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.267303E+10 | 2988.03 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.110133E+10 | 1060.81 | 02-JAN-20:10 | 0.368383E+11 | 16487.34 | 01-JAN-07:10 |
February | 0.994402E+09 | 1060.81 | 01-FEB-20:10 | 0.332733E+11 | 16487.34 | 01-FEB-07:10 |
March | 0.110473E+10 | 1060.81 | 01-MAR-20:10 | 0.368383E+11 | 16487.34 | 01-MAR-07:10 |
April | 0.106399E+10 | 1060.81 | 03-APR-19:10 | 0.356500E+11 | 16487.34 | 01-APR-06:10 |
May | 0.110324E+10 | 1060.81 | 01-MAY-19:10 | 0.368383E+11 | 16487.34 | 01-MAY-06:10 |
June | 0.106887E+10 | 1060.81 | 01-JUN-19:10 | 0.356500E+11 | 16487.34 | 01-JUN-06:10 |
July | 0.109836E+10 | 1060.81 | 03-JUL-19:10 | 0.368383E+11 | 16487.34 | 01-JUL-06:10 |
August | 0.110515E+10 | 1060.81 | 01-AUG-19:10 | 0.368383E+11 | 16487.34 | 01-AUG-06:10 |
September | 0.106442E+10 | 1060.81 | 01-SEP-19:10 | 0.356500E+11 | 16487.34 | 01-SEP-06:10 |
October | 0.110091E+10 | 1060.81 | 02-OCT-19:10 | 0.368383E+11 | 16487.34 | 01-OCT-06:10 |
November | 0.106802E+10 | 1060.81 | 01-NOV-19:10 | 0.356500E+11 | 16487.34 | 01-NOV-06:10 |
December | 0.109836E+10 | 1060.81 | 01-DEC-20:10 | 0.368383E+11 | 16487.34 | 01-DEC-07:10 |
Annual Sum or Average | 0.129718E+11 | 0.433742E+12 | ||||
Minimum of Months | 0.994402E+09 | 1060.81 | 0.332733E+11 | 16487.34 | ||
Maximum of Months | 0.110515E+10 | 1060.81 | 0.368383E+11 | 16487.34 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.205176E+10 | 1976.27 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.185255E+10 | 1976.27 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.205809E+10 | 1976.27 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.198220E+10 | 1976.27 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.205532E+10 | 1976.27 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.199129E+10 | 1976.27 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.204623E+10 | 1976.27 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.205888E+10 | 1976.27 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.198299E+10 | 1976.27 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.205097E+10 | 1976.27 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.198971E+10 | 1976.27 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.204623E+10 | 1976.27 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.241662E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.185255E+10 | 1976.27 | 0.00 | 0.00 | |
Maximum of Months | 0.205888E+10 | 1976.27 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.136942E+11 | 0.121516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.123646E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196682E+11 | 0.137364E+11 | 0.121771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.132299E+11 | 0.117446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.137180E+11 | 0.121662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.132906E+11 | 0.117829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.136573E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.137417E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189689E+11 | 0.132352E+11 | 0.117482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195854E+11 | 0.136889E+11 | 0.121479E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.132800E+11 | 0.117774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.136573E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230861E+12 | 0.161294E+12 | 0.143105E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.176991E+11 | 0.123646E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196682E+11 | 0.137417E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.620421E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 43096623.90 | 3055224.92 |
February | 0.179968E+10 | 0.560184E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 48281158.72 | 283576.92 |
March | 0.199990E+10 | 0.622334E+09 | 0.866718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 65369518.91 | 27370.18 |
April | 0.192973E+10 | 0.599386E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 75294877.27 | 0.00 |
May | 0.199475E+10 | 0.621497E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 77046503.68 | 55479.01 |
June | 0.193394E+10 | 0.602135E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 71237763.95 | 51779.98 |
July | 0.199054E+10 | 0.618748E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 55553528.91 | 59943.58 |
August | 0.199896E+10 | 0.622573E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 61551592.06 | 28455.46 |
September | 0.192879E+10 | 0.599625E+09 | 0.836191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 57500530.31 | 694.36 |
October | 0.199148E+10 | 0.620182E+09 | 0.864640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 51174912.62 | 5619.26 |
November | 0.192552E+10 | 0.601657E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 44009261.63 | 209029.62 |
December | 0.199054E+10 | 0.618748E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 38001714.93 | 3360729.36 |
Annual Sum or Average | 0.234744E+11 | 0.730749E+10 | 0.101856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.688118E+09 | 7137902.64 |
Minimum of Months | 0.179968E+10 | 0.560184E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 38001714.93 | 0.00 |
Maximum of Months | 0.199990E+10 | 0.622573E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 77046503.68 | 3360729.36 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.718450E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19385071.03 | 1358841.55 |
February | 0.208403E+10 | 0.648695E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20616501.06 | 150204.39 |
March | 0.231589E+10 | 0.720665E+09 | 0.100366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26940809.38 | 20048.49 |
April | 0.223463E+10 | 0.694091E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30250358.25 | 0.00 |
May | 0.230993E+10 | 0.719696E+09 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30829011.30 | 21883.85 |
June | 0.223950E+10 | 0.697275E+09 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 28408083.61 | 27474.54 |
July | 0.230505E+10 | 0.716513E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22274101.67 | 24110.34 |
August | 0.231480E+10 | 0.720942E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24391557.95 | 11589.96 |
September | 0.223354E+10 | 0.694368E+09 | 0.968312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23432844.42 | 2873.76 |
October | 0.230614E+10 | 0.718174E+09 | 0.100126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21491616.32 | 0.00 |
November | 0.222975E+10 | 0.696721E+09 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19297570.23 | 128530.93 |
December | 0.230505E+10 | 0.716513E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17435781.48 | 1523573.72 |
Annual Sum or Average | 0.271834E+11 | 0.846210E+10 | 0.117950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284753E+09 | 3269131.54 |
Minimum of Months | 0.208403E+10 | 0.648695E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17435781.48 | 0.00 |
Maximum of Months | 0.231589E+10 | 0.720942E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30829011.30 | 1523573.72 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.487480E+09 | 0.710312E+09 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46838045.87 | 2706226.45 |
February | 0.440737E+09 | 0.641347E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 49380462.66 | 280449.20 |
March | 0.489771E+09 | 0.712502E+09 | 0.106120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63866764.60 | 39904.26 |
April | 0.472586E+09 | 0.686229E+09 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69167449.67 | 644.46 |
May | 0.488511E+09 | 0.711544E+09 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67445038.27 | 54751.14 |
June | 0.473617E+09 | 0.689376E+09 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61334379.45 | 165306.23 |
July | 0.487480E+09 | 0.708397E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46228562.88 | 70053.18 |
August | 0.489542E+09 | 0.712775E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53953977.17 | 20414.42 |
September | 0.472357E+09 | 0.686503E+09 | 0.102382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53355863.89 | 2080.29 |
October | 0.487709E+09 | 0.710039E+09 | 0.105866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50023967.09 | 0.00 |
November | 0.471555E+09 | 0.688829E+09 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45441553.78 | 268168.04 |
December | 0.487480E+09 | 0.708397E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41877401.92 | 2827656.61 |
Annual Sum or Average | 0.574883E+10 | 0.836625E+10 | 0.124712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.648913E+09 | 6435654.30 |
Minimum of Months | 0.440737E+09 | 0.641347E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41877401.92 | 0.00 |
Maximum of Months | 0.489771E+09 | 0.712775E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69167449.67 | 2827656.61 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.374985E+09 | 0.261454E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 27400959.38 | 1493002.68 |
February | 0.339028E+09 | 0.236069E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 28962897.12 | 142393.57 |
March | 0.376747E+09 | 0.262260E+09 | 0.306128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37461601.79 | 14308.41 |
April | 0.363528E+09 | 0.252589E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40466728.24 | 181.93 |
May | 0.375778E+09 | 0.261907E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39267926.94 | 30862.83 |
June | 0.364321E+09 | 0.253748E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35596640.95 | 72756.16 |
July | 0.374985E+09 | 0.260749E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 27183233.72 | 31803.40 |
August | 0.376571E+09 | 0.262360E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 31673023.02 | 6708.73 |
September | 0.363352E+09 | 0.252690E+09 | 0.295345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 31402008.18 | 0.00 |
October | 0.375161E+09 | 0.261353E+09 | 0.305393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 29398420.25 | 0.00 |
November | 0.362735E+09 | 0.253546E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26690231.57 | 132230.19 |
December | 0.374985E+09 | 0.260749E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 24506634.83 | 1539819.50 |
Annual Sum or Average | 0.442217E+10 | 0.307947E+10 | 0.359760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.380010E+09 | 3464067.42 |
Minimum of Months | 0.339028E+09 | 0.236069E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 24506634.83 | 0.00 |
Maximum of Months | 0.376747E+09 | 0.262360E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40466728.24 | 1539819.50 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.337502E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 76629710.40 | 1542360.09 |
February | 0.139600E+10 | 0.304733E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 83868763.81 | 269875.77 |
March | 0.155131E+10 | 0.338542E+09 | 0.578079E+10 | 0.502211E+11 | 0.00 | 0.00 | 0.00 | 0.106184E+09 | 5987.78 |
April | 0.149688E+10 | 0.326059E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 0.115874E+09 | 0.00 |
May | 0.154732E+10 | 0.338087E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 0.117502E+09 | 67530.91 |
June | 0.150015E+10 | 0.327554E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 0.110560E+09 | 81477.63 |
July | 0.154405E+10 | 0.336592E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 89074926.16 | 74423.95 |
August | 0.155059E+10 | 0.338672E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 94238136.00 | 67744.91 |
September | 0.149615E+10 | 0.326189E+09 | 0.557718E+10 | 0.484522E+11 | 0.00 | 0.00 | 0.00 | 91847992.24 | 103520.61 |
October | 0.154478E+10 | 0.337372E+09 | 0.576693E+10 | 0.501006E+11 | 0.00 | 0.00 | 0.00 | 84154813.26 | 47763.16 |
November | 0.149361E+10 | 0.327294E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 77592147.70 | 313920.66 |
December | 0.154405E+10 | 0.336592E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 69296335.62 | 1348151.92 |
Annual Sum or Average | 0.182090E+11 | 0.397519E+10 | 0.679355E+11 | 0.590196E+12 | 0.00 | 0.00 | 0.00 | 0.111682E+10 | 3922757.38 |
Minimum of Months | 0.139600E+10 | 0.304733E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 69296335.62 | 0.00 |
Maximum of Months | 0.155131E+10 | 0.338672E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 0.117502E+09 | 1542360.09 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.123718E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 93272244.23 | 11656765.07 |
February | 0.236489E+11 | 0.111771E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103782E+09 | 1800839.01 |
March | 0.262800E+11 | 0.122372E+10 | 0.122027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143674E+09 | 550982.44 |
April | 0.253579E+11 | 0.115398E+10 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167044E+09 | 0.00 |
May | 0.262123E+11 | 0.120690E+10 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169029E+09 | 131434.17 |
June | 0.254132E+11 | 0.115355E+10 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158320E+09 | 463035.94 |
July | 0.261570E+11 | 0.119926E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120205E+09 | 259257.07 |
August | 0.262677E+11 | 0.120405E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131527E+09 | 101576.16 |
September | 0.253456E+11 | 0.119373E+10 | 0.117729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124385E+09 | 201302.62 |
October | 0.261693E+11 | 0.123683E+10 | 0.121734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107153E+09 | 162475.33 |
November | 0.253025E+11 | 0.119052E+10 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 92668405.04 | 2271451.41 |
December | 0.261570E+11 | 0.123366E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83411372.47 | 14578797.63 |
Annual Sum or Average | 0.308468E+12 | 0.143511E+11 | 0.143405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149447E+10 | 32177916.86 |
Minimum of Months | 0.236489E+11 | 0.111771E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83411372.47 | 0.00 |
Maximum of Months | 0.262800E+11 | 0.123718E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169029E+09 | 14578797.63 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.934832E+10 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.297587E+09 | 30125641.50 |
February | 0.702046E+11 | 0.844610E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322443E+09 | 4455480.14 |
March | 0.780153E+11 | 0.937823E+10 | 0.126786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.429880E+09 | 1224128.54 |
April | 0.752779E+11 | 0.902001E+10 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.483478E+09 | 0.00 |
May | 0.778146E+11 | 0.937693E+10 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.482048E+09 | 377530.42 |
June | 0.754422E+11 | 0.906877E+10 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.446242E+09 | 1355712.78 |
July | 0.776503E+11 | 0.934270E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.337542E+09 | 660173.25 |
August | 0.779788E+11 | 0.938388E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.374982E+09 | 240913.31 |
September | 0.752414E+11 | 0.905757E+10 | 0.122320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.363641E+09 | 382993.60 |
October | 0.776868E+11 | 0.936575E+10 | 0.126482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.324246E+09 | 195167.22 |
November | 0.751137E+11 | 0.906574E+10 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290463E+09 | 5219287.71 |
December | 0.776503E+11 | 0.932461E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.267468E+09 | 36872175.28 |
Annual Sum or Average | 0.915726E+12 | 0.110179E+12 | 0.148998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.442002E+10 | 81109203.76 |
Minimum of Months | 0.702046E+11 | 0.844610E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.267468E+09 | 0.00 |
Maximum of Months | 0.780153E+11 | 0.938388E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.483478E+09 | 36872175.28 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196602E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37874983.21 | 522997.10 |
February | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41581043.55 | 2984.78 |
March | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 52546814.84 | 0.00 |
April | 0.293479E+09 | 0.190486E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 57162121.09 | 0.00 |
May | 0.303504E+09 | 0.195821E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 57818720.11 | 0.00 |
June | 0.293842E+09 | 0.188975E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 54812764.48 | 0.00 |
July | 0.303141E+09 | 0.197358E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 44081804.89 | 327.80 |
August | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 46420662.30 | 15412.63 |
September | 0.293479E+09 | 0.190538E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 45272095.35 | 175.78 |
October | 0.303322E+09 | 0.196576E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41318782.42 | 936.05 |
November | 0.293661E+09 | 0.189731E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 38346895.87 | 22539.47 |
December | 0.303141E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 34229062.12 | 363324.07 |
Annual Sum or Average | 0.357224E+10 | 0.231110E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.551466E+09 | 928697.68 |
Minimum of Months | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 34229062.12 | 0.00 |
Maximum of Months | 0.303685E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 57818720.11 | 522997.10 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196579E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37077059.69 | 946294.24 |
February | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40783922.45 | 155885.11 |
March | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 52431657.33 | 75.01 |
April | 0.293479E+09 | 0.190464E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 57119014.15 | 320.38 |
May | 0.303504E+09 | 0.195798E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 57715653.79 | 33850.00 |
June | 0.293842E+09 | 0.188953E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 54592027.74 | 42033.12 |
July | 0.303141E+09 | 0.197334E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 43816835.02 | 46133.26 |
August | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 46260931.07 | 41877.25 |
September | 0.293479E+09 | 0.190515E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 45057439.96 | 33751.46 |
October | 0.303322E+09 | 0.196553E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41000298.67 | 26976.21 |
November | 0.293661E+09 | 0.189708E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37675923.38 | 208157.11 |
December | 0.303141E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 33133729.58 | 625938.32 |
Annual Sum or Average | 0.357224E+10 | 0.231083E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.546664E+09 | 2161291.45 |
Minimum of Months | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 33133729.58 | 75.01 |
Maximum of Months | 0.303685E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 57715653.79 | 946294.24 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.123557E+09 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2825229.85 | 3589562.46 |
February | 0.00 | 0.111584E+09 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3467857.11 | 1932383.31 |
March | 0.00 | 0.122575E+09 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4721581.30 | 1156550.52 |
April | 0.00 | 0.119713E+09 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5578014.52 | 334229.75 |
May | 0.00 | 0.123066E+09 | 0.217879E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5910319.15 | 838580.83 |
June | 0.00 | 0.118764E+09 | 0.210812E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5477104.45 | 892442.13 |
July | 0.00 | 0.124032E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3007641.36 | 1846449.58 |
August | 0.00 | 0.122575E+09 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3322126.80 | 1500371.20 |
September | 0.00 | 0.119746E+09 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3313422.32 | 1471310.82 |
October | 0.00 | 0.123541E+09 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2436503.11 | 2068407.54 |
November | 0.00 | 0.119238E+09 | 0.210867E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2337191.59 | 2452784.98 |
December | 0.00 | 0.124048E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2365225.24 | 4130278.89 |
Annual Sum or Average | 0.00 | 0.145244E+10 | 0.256575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44762216.80 | 22213352.00 |
Minimum of Months | 0.00 | 0.111584E+09 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2337191.59 | 334229.75 |
Maximum of Months | 0.00 | 0.124048E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5910319.15 | 4130278.89 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.123591E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10472297.34 | 228796.04 |
February | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11497403.68 | 24352.53 |
March | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14736235.14 | 0.00 |
April | 0.293479E+09 | 0.119746E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16025758.35 | 0.00 |
May | 0.303504E+09 | 0.123099E+09 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16165381.26 | 2992.75 |
June | 0.293842E+09 | 0.118796E+09 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15279237.99 | 5705.34 |
July | 0.303141E+09 | 0.124066E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12289025.03 | 5214.03 |
August | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12993486.13 | 6242.53 |
September | 0.293479E+09 | 0.119778E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12668763.68 | 4222.59 |
October | 0.303322E+09 | 0.123574E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11548121.59 | 2666.28 |
November | 0.293661E+09 | 0.119271E+09 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10619329.08 | 39585.49 |
December | 0.303141E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9376336.22 | 149133.22 |
Annual Sum or Average | 0.357224E+10 | 0.145283E+10 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153671E+09 | 468910.80 |
Minimum of Months | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9376336.22 | 0.00 |
Maximum of Months | 0.303685E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16165381.26 | 228796.04 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196602E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37833075.46 | 535660.56 |
February | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41532692.51 | 4112.40 |
March | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 52485109.12 | 0.00 |
April | 0.293479E+09 | 0.190486E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 57101408.97 | 0.00 |
May | 0.303504E+09 | 0.195821E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 57774067.93 | 0.00 |
June | 0.293842E+09 | 0.188975E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 54764594.62 | 0.00 |
July | 0.303141E+09 | 0.197358E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 44023507.39 | 327.99 |
August | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 46354195.24 | 15444.66 |
September | 0.293479E+09 | 0.190538E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 45219460.73 | 135.67 |
October | 0.303322E+09 | 0.196576E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41264888.10 | 942.11 |
November | 0.293661E+09 | 0.189731E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 38303735.21 | 23790.91 |
December | 0.303141E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 34184089.07 | 366726.29 |
Annual Sum or Average | 0.357224E+10 | 0.231110E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.550841E+09 | 947140.59 |
Minimum of Months | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 34184089.07 | 0.00 |
Maximum of Months | 0.303685E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 57774067.93 | 535660.56 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196579E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 36874624.56 | 1237074.33 |
February | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40591404.71 | 336393.46 |
March | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 52336939.96 | 1130.47 |
April | 0.293479E+09 | 0.190464E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 57064341.29 | 69.65 |
May | 0.303504E+09 | 0.195798E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 57676430.81 | 26905.49 |
June | 0.293842E+09 | 0.188953E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 54544367.90 | 37379.38 |
July | 0.303141E+09 | 0.197334E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 43751509.68 | 37705.16 |
August | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 46197559.12 | 37932.16 |
September | 0.293479E+09 | 0.190515E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 45000172.75 | 30286.64 |
October | 0.303322E+09 | 0.196553E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40927420.49 | 28511.75 |
November | 0.293661E+09 | 0.189708E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37543988.56 | 243389.07 |
December | 0.303141E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 32884468.57 | 812299.61 |
Annual Sum or Average | 0.357224E+10 | 0.231083E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.545393E+09 | 2829077.16 |
Minimum of Months | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 32884468.57 | 69.65 |
Maximum of Months | 0.303685E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 57676430.81 | 1237074.33 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.385223E+10 | 0.193865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34535537.53 | 2634477.29 |
February | 0.348285E+10 | 0.175042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36854332.81 | 305253.54 |
March | 0.387034E+10 | 0.194462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49485337.72 | 37549.26 |
April | 0.373454E+10 | 0.187292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55723703.61 | 312.83 |
May | 0.386038E+10 | 0.194201E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55096250.20 | 26658.02 |
June | 0.374269E+10 | 0.188151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50094393.54 | 49332.04 |
July | 0.385223E+10 | 0.193342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40594107.02 | 4143.30 |
August | 0.386853E+10 | 0.194537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44820728.49 | 1209.28 |
September | 0.373273E+10 | 0.187367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43765596.54 | 485.93 |
October | 0.385404E+10 | 0.193790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38848205.26 | 448.96 |
November | 0.372639E+10 | 0.188002E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34413646.52 | 311197.34 |
December | 0.385223E+10 | 0.193342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30766118.83 | 2723927.79 |
Annual Sum or Average | 0.454292E+11 | 0.228339E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.514998E+09 | 6094995.57 |
Minimum of Months | 0.348285E+10 | 0.175042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30766118.83 | 312.83 |
Maximum of Months | 0.387034E+10 | 0.194537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55723703.61 | 2723927.79 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196602E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37422095.12 | 548536.77 |
February | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41155045.63 | 3315.31 |
March | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 52060364.67 | 0.00 |
April | 0.293479E+09 | 0.190486E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 56686242.75 | 0.00 |
May | 0.303504E+09 | 0.195821E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 57345520.17 | 69.32 |
June | 0.293842E+09 | 0.188975E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 54352133.43 | 69.25 |
July | 0.303141E+09 | 0.197358E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 43608801.01 | 508.21 |
August | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 45944121.22 | 17089.85 |
September | 0.293479E+09 | 0.190538E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 44802996.72 | 362.22 |
October | 0.303322E+09 | 0.196576E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40841259.53 | 1248.57 |
November | 0.293661E+09 | 0.189731E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37881073.98 | 24483.15 |
December | 0.303141E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 33770611.46 | 389596.70 |
Annual Sum or Average | 0.357224E+10 | 0.231110E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.545870E+09 | 985279.36 |
Minimum of Months | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 33770611.46 | 0.00 |
Maximum of Months | 0.303685E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 57345520.17 | 548536.77 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196579E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 36690563.47 | 873831.62 |
February | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40431998.36 | 114184.52 |
March | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 51963513.39 | 0.00 |
April | 0.293479E+09 | 0.190464E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 56639675.74 | 562.29 |
May | 0.303504E+09 | 0.195798E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 57245166.21 | 37419.14 |
June | 0.293842E+09 | 0.188953E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 54147378.17 | 52222.01 |
July | 0.303141E+09 | 0.197334E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 43357996.11 | 62281.88 |
August | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 45787875.14 | 52434.95 |
September | 0.293479E+09 | 0.190515E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 44587351.93 | 51720.60 |
October | 0.303322E+09 | 0.196553E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40537367.60 | 49639.05 |
November | 0.293661E+09 | 0.189708E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37255674.30 | 224842.63 |
December | 0.303141E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 32771407.76 | 590967.89 |
Annual Sum or Average | 0.357224E+10 | 0.231083E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.541416E+09 | 2110106.58 |
Minimum of Months | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 32771407.76 | 0.00 |
Maximum of Months | 0.303685E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 57245166.21 | 873831.62 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.123591E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19083885.71 | 286664.56 |
February | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21012856.42 | 2039.82 |
March | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26622381.86 | 0.00 |
April | 0.293479E+09 | 0.119746E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 29020406.31 | 0.00 |
May | 0.303504E+09 | 0.123099E+09 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 29346122.67 | 35.15 |
June | 0.293842E+09 | 0.118796E+09 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 27821685.85 | 35.04 |
July | 0.303141E+09 | 0.124066E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22316091.84 | 259.88 |
August | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23515698.24 | 8650.02 |
September | 0.293479E+09 | 0.119778E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22921171.15 | 136.98 |
October | 0.303322E+09 | 0.123574E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20869633.21 | 697.50 |
November | 0.293661E+09 | 0.119271E+09 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19338462.97 | 13417.31 |
December | 0.303141E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17212186.28 | 201248.50 |
Annual Sum or Average | 0.357224E+10 | 0.145283E+10 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279081E+09 | 513184.76 |
Minimum of Months | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17212186.28 | 0.00 |
Maximum of Months | 0.303685E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 29346122.67 | 286664.56 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.267303E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 60114725.01 | 8913890.97 |
February | 0.415303E+11 | 0.239872E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 66170028.64 | 1759060.96 |
March | 0.461508E+11 | 0.263668E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 87723768.38 | 559375.80 |
April | 0.445315E+11 | 0.249988E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 98829541.76 | 9927.87 |
May | 0.460320E+11 | 0.258463E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 99165550.91 | 162665.02 |
June | 0.446286E+11 | 0.247556E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 92493153.84 | 480030.88 |
July | 0.459349E+11 | 0.256073E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 66157290.87 | 386516.15 |
August | 0.461292E+11 | 0.259557E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 73262452.23 | 359687.67 |
September | 0.445099E+11 | 0.254900E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 71379685.78 | 369999.37 |
October | 0.459565E+11 | 0.265767E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 61596991.11 | 504466.16 |
November | 0.444343E+11 | 0.258012E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 57118574.52 | 2384585.85 |
December | 0.459349E+11 | 0.266925E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 53915915.01 | 11126085.24 |
Annual Sum or Average | 0.541708E+12 | 0.308808E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.887928E+09 | 27016291.94 |
Minimum of Months | 0.415303E+11 | 0.239872E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 53915915.01 | 9927.87 |
Maximum of Months | 0.461508E+11 | 0.267303E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 99165550.91 | 11126085.24 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.267303E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 59148048.98 | 8999309.79 |
February | 0.415303E+11 | 0.239872E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 65420383.48 | 1785530.98 |
March | 0.461508E+11 | 0.263668E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 86842474.07 | 560856.06 |
April | 0.445315E+11 | 0.249988E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 98036481.65 | 11443.58 |
May | 0.460320E+11 | 0.258463E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 98425718.19 | 162744.73 |
June | 0.446286E+11 | 0.247556E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 91865486.63 | 481791.95 |
July | 0.459349E+11 | 0.256073E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 65162119.63 | 389243.16 |
August | 0.461292E+11 | 0.259557E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 72076918.96 | 388998.71 |
September | 0.445099E+11 | 0.254900E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 70280079.82 | 378402.62 |
October | 0.459565E+11 | 0.265767E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 60391587.41 | 521259.98 |
November | 0.444343E+11 | 0.258012E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 56077986.47 | 2423283.65 |
December | 0.459349E+11 | 0.266925E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 52844653.98 | 11198278.06 |
Annual Sum or Average | 0.541708E+12 | 0.308808E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.876572E+09 | 27301143.26 |
Minimum of Months | 0.415303E+11 | 0.239872E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 52844653.98 | 11443.58 |
Maximum of Months | 0.461508E+11 | 0.267303E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 98425718.19 | 11198278.06 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.110133E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 52369948.29 | 4907254.49 |
February | 0.369574E+10 | 0.994402E+09 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 60876245.12 | 1133252.48 |
March | 0.410691E+10 | 0.110473E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 80389143.93 | 151012.28 |
April | 0.396281E+10 | 0.106399E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 91217180.50 | 7566.22 |
May | 0.409635E+10 | 0.110324E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 91692471.53 | 110983.00 |
June | 0.397146E+10 | 0.106887E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 86114040.65 | 226037.20 |
July | 0.408770E+10 | 0.109836E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 61839768.67 | 180843.58 |
August | 0.410499E+10 | 0.110515E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 67181752.72 | 216386.07 |
September | 0.396089E+10 | 0.106442E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 65533126.91 | 196911.00 |
October | 0.408962E+10 | 0.110091E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 56262464.07 | 225919.57 |
November | 0.395417E+10 | 0.106802E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 51720065.33 | 1079148.97 |
December | 0.408770E+10 | 0.109836E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 45178692.19 | 5216978.31 |
Annual Sum or Average | 0.482060E+11 | 0.129718E+11 | 0.392709E+12 | 0.359593E+12 | 0.00 | 0.00 | 0.00 | 0.810375E+09 | 13652293.18 |
Minimum of Months | 0.369574E+10 | 0.994402E+09 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 45178692.19 | 7566.22 |
Maximum of Months | 0.410691E+10 | 0.110515E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 91692471.53 | 5216978.31 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.407704E+10 | 0.205176E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54689507.70 | 4273457.14 |
February | 0.368610E+10 | 0.185255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60113727.02 | 415589.33 |
March | 0.409620E+10 | 0.205809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80731671.30 | 62149.87 |
April | 0.395248E+10 | 0.198220E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90943452.55 | 1351.31 |
May | 0.408566E+10 | 0.205532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92267296.42 | 82494.35 |
June | 0.396110E+10 | 0.199129E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84951539.52 | 101959.54 |
July | 0.407704E+10 | 0.204623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66113462.64 | 53996.58 |
August | 0.409429E+10 | 0.205888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74058459.76 | 24465.22 |
September | 0.395056E+10 | 0.198299E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70410922.45 | 6369.00 |
October | 0.407896E+10 | 0.205097E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63273981.14 | 430.79 |
November | 0.394385E+10 | 0.198971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55411992.33 | 360707.12 |
December | 0.407704E+10 | 0.204623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49282801.65 | 4741281.26 |
Annual Sum or Average | 0.480803E+11 | 0.241662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.842249E+09 | 10124251.49 |
Minimum of Months | 0.368610E+10 | 0.185255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49282801.65 | 430.79 |
Maximum of Months | 0.409620E+10 | 0.205888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92267296.42 | 4741281.26 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 13190.31 | 02-JAN-20:10 | 9632.53 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 13190.31 | 01-FEB-20:10 | 9632.53 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 13190.31 | 01-MAR-20:10 | 9632.53 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 13190.31 | 03-APR-19:10 | 9632.53 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 13190.31 | 01-MAY-19:10 | 9632.53 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 13190.31 | 01-JUN-19:10 | 9632.53 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 13190.31 | 03-JUL-19:10 | 9632.53 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 13190.31 | 01-AUG-19:10 | 9632.53 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 13190.31 | 01-SEP-19:10 | 9632.53 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 01-OCT-23:10 | 13190.31 | 02-OCT-19:10 | 9632.53 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 13190.31 | 01-NOV-19:10 | 9632.53 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 13190.31 | 01-DEC-20:10 | 9632.53 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 11501.89 | 13190.31 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 13190.31 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 597.59 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.43 | 04-JAN-13:00 | 19.09 | 24-JAN-09:00 |
February | 1169.53 | 01-FEB-00:10 | 597.59 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.97 | 26-FEB-14:00 | 18.56 | 21-FEB-10:00 |
March | 1169.53 | 01-MAR-00:10 | 597.59 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 62.40 | 21-MAR-13:00 | 3.40 | 03-MAR-06:00 |
April | 1169.53 | 01-APR-00:10 | 597.59 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.08 | 01-APR-14:00 | 0.00 | 01-APR-00:10 |
May | 1169.53 | 01-MAY-00:10 | 597.59 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.33 | 06-MAY-13:00 | 10.59 | 10-MAY-19:56 |
June | 1169.53 | 01-JUN-00:10 | 597.59 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.66 | 13-JUN-14:00 | 4.18 | 25-JUN-20:00 |
July | 1169.53 | 01-JUL-00:10 | 597.59 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.38 | 01-JUL-13:00 | 5.29 | 19-JUL-18:53 |
August | 1169.53 | 01-AUG-00:10 | 597.59 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.70 | 22-AUG-15:00 | 5.30 | 23-AUG-19:56 |
September | 1169.53 | 01-SEP-00:10 | 597.59 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.90 | 12-SEP-14:00 | 0.41 | 15-SEP-21:00 |
October | 1169.53 | 01-OCT-23:10 | 597.59 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.00 | 04-OCT-14:00 | 2.13 | 09-OCT-18:53 |
November | 1169.53 | 01-NOV-00:10 | 597.59 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.40 | 18-NOV-13:00 | 12.82 | 25-NOV-05:00 |
December | 1169.53 | 01-DEC-00:10 | 597.59 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.90 | 08-DEC-14:00 | 21.24 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1169.53 | 597.59 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 45.90 | 0.00 | |||||
Maximum of Months | 1169.53 | 597.59 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 68.33 | 21.24 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 692.02 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.49 | 04-JAN-13:00 | 8.61 | 23-JAN-06:00 |
February | 1354.32 | 01-FEB-00:10 | 692.02 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.01 | 26-FEB-14:00 | 5.21 | 21-FEB-10:00 |
March | 1354.32 | 01-MAR-00:10 | 692.02 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.35 | 21-MAR-13:00 | 2.30 | 03-MAR-06:00 |
April | 1354.32 | 01-APR-00:10 | 692.02 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.32 | 01-APR-14:00 | 0.00 | 01-APR-00:10 |
May | 1354.32 | 01-MAY-00:10 | 692.02 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.77 | 06-MAY-13:00 | 4.09 | 10-MAY-19:58 |
June | 1354.32 | 01-JUN-00:10 | 692.02 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.09 | 18-JUN-14:00 | 1.46 | 25-JUN-20:20 |
July | 1354.32 | 01-JUL-00:10 | 692.02 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.45 | 01-JUL-13:00 | 2.04 | 19-JUL-18:58 |
August | 1354.32 | 01-AUG-00:10 | 692.02 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.13 | 22-AUG-15:00 | 2.05 | 23-AUG-19:58 |
September | 1354.32 | 01-SEP-00:10 | 692.02 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.02 | 10-SEP-14:00 | 0.72 | 15-SEP-21:00 |
October | 1354.32 | 01-OCT-23:10 | 692.02 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.38 | 28-OCT-13:00 | 0.00 | 01-OCT-00:10 |
November | 1354.32 | 01-NOV-00:10 | 692.02 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.63 | 18-NOV-13:00 | 5.97 | 25-NOV-05:00 |
December | 1354.32 | 01-DEC-00:10 | 692.02 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.99 | 07-DEC-14:00 | 9.58 | 21-DEC-05:30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1354.32 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 19.99 | 0.00 | |||||
Maximum of Months | 1354.32 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 27.77 | 9.58 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 286.42 | 02-JAN-00:10 | 684.18 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.19 | 04-JAN-13:00 | 18.83 | 23-JAN-06:00 |
February | 286.42 | 01-FEB-00:10 | 684.18 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.43 | 21-FEB-14:00 | 13.20 | 21-FEB-10:00 |
March | 286.42 | 01-MAR-00:10 | 684.18 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.54 | 21-MAR-13:00 | 4.75 | 03-MAR-06:00 |
April | 286.42 | 01-APR-00:10 | 684.18 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.93 | 01-APR-14:00 | 1.12 | 14-APR-15:52 |
May | 286.42 | 01-MAY-00:10 | 684.18 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 62.33 | 06-MAY-13:00 | 9.67 | 10-MAY-20:00 |
June | 286.42 | 01-JUN-00:10 | 684.18 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.34 | 13-JUN-14:00 | 4.84 | 25-JUN-21:00 |
July | 286.42 | 01-JUL-00:10 | 684.18 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.49 | 01-JUL-13:00 | 4.83 | 19-JUL-18:53 |
August | 286.42 | 01-AUG-00:10 | 684.18 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.37 | 22-AUG-15:00 | 3.99 | 23-AUG-20:00 |
September | 286.42 | 01-SEP-00:10 | 684.18 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.88 | 12-SEP-14:00 | 0.95 | 15-SEP-21:00 |
October | 286.42 | 01-OCT-23:10 | 684.18 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.61 | 28-OCT-13:00 | 0.00 | 01-OCT-00:10 |
November | 286.42 | 01-NOV-00:10 | 684.18 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.81 | 18-NOV-13:00 | 13.69 | 25-NOV-05:00 |
December | 286.42 | 01-DEC-00:10 | 684.18 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.84 | 07-DEC-14:00 | 21.34 | 21-DEC-05:30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 286.42 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 44.49 | 0.00 | |||||
Maximum of Months | 286.42 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 62.33 | 21.34 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 220.32 | 02-JAN-00:10 | 251.84 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.01 | 04-JAN-13:00 | 10.74 | 23-JAN-06:00 |
February | 220.32 | 01-FEB-00:10 | 251.84 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.87 | 21-FEB-14:00 | 7.43 | 21-FEB-10:00 |
March | 220.32 | 01-MAR-00:10 | 251.84 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.89 | 21-MAR-13:00 | 2.56 | 03-MAR-06:00 |
April | 220.32 | 01-APR-00:10 | 251.84 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.21 | 01-APR-14:00 | 0.33 | 14-APR-15:52 |
May | 220.32 | 01-MAY-00:10 | 251.84 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.96 | 06-MAY-13:00 | 5.58 | 10-MAY-20:00 |
June | 220.32 | 01-JUN-00:10 | 251.84 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.93 | 13-JUN-14:00 | 2.60 | 20-JUN-24:00 |
July | 220.32 | 01-JUL-00:10 | 251.84 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.52 | 01-JUL-13:00 | 2.62 | 19-JUL-19:10 |
August | 220.32 | 01-AUG-00:10 | 251.84 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.16 | 22-AUG-15:00 | 1.40 | 23-AUG-20:40 |
September | 220.32 | 01-SEP-00:10 | 251.84 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.75 | 12-SEP-14:00 | 0.00 | 01-SEP-00:10 |
October | 220.32 | 01-OCT-23:10 | 251.84 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.30 | 28-OCT-13:00 | 0.00 | 01-OCT-00:10 |
November | 220.32 | 01-NOV-00:10 | 251.84 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.28 | 18-NOV-13:00 | 7.80 | 25-NOV-05:00 |
December | 220.32 | 01-DEC-00:10 | 251.84 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.90 | 07-DEC-14:00 | 12.20 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 220.32 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 25.52 | 0.00 | |||||
Maximum of Months | 220.32 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 35.96 | 12.20 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 325.08 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 79.93 | 04-JAN-13:00 | 24.84 | 24-JAN-07:10 |
February | 907.20 | 01-FEB-00:10 | 325.08 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 88.72 | 26-FEB-14:00 | 17.18 | 21-FEB-10:00 |
March | 907.20 | 01-MAR-00:10 | 325.08 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 93.68 | 19-MAR-14:00 | 2.66 | 14-MAR-22:00 |
April | 907.20 | 01-APR-00:10 | 325.08 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 87.88 | 02-APR-15:00 | 0.00 | 01-APR-00:10 |
May | 907.20 | 01-MAY-00:10 | 325.08 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 98.87 | 06-MAY-13:00 | 13.20 | 10-MAY-19:58 |
June | 907.20 | 01-JUN-00:10 | 325.08 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 93.01 | 18-JUN-14:00 | 6.60 | 25-JUN-21:00 |
July | 907.20 | 01-JUL-00:10 | 325.08 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 74.09 | 15-JUL-16:00 | 6.59 | 19-JUL-18:55 |
August | 907.20 | 01-AUG-00:10 | 325.08 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 82.35 | 27-AUG-14:00 | 6.61 | 23-AUG-19:54 |
September | 907.20 | 01-SEP-00:10 | 325.08 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 82.35 | 10-SEP-14:00 | 6.61 | 16-SEP-20:00 |
October | 907.20 | 01-OCT-23:10 | 325.08 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 73.64 | 28-OCT-13:00 | 5.38 | 22-OCT-18:10 |
November | 907.20 | 01-NOV-00:10 | 325.08 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 82.23 | 18-NOV-13:00 | 8.60 | 25-NOV-22:00 |
December | 907.20 | 01-DEC-00:10 | 325.08 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 73.36 | 08-DEC-14:00 | 28.89 | 21-DEC-07:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 907.20 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 73.36 | 0.00 | ||||||
Maximum of Months | 907.20 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 98.87 | 28.89 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 1701.53 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 113.71 | 04-JAN-13:00 | 58.43 | 23-JAN-06:00 |
February | 15368.40 | 01-FEB-00:10 | 1701.53 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 123.89 | 26-FEB-15:00 | 32.67 | 21-FEB-10:00 |
March | 15368.40 | 01-MAR-00:10 | 1701.53 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 142.83 | 21-MAR-13:00 | 22.62 | 03-MAR-06:00 |
April | 15368.40 | 01-APR-00:10 | 1701.53 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 134.80 | 09-APR-14:00 | 0.00 | 01-APR-00:10 |
May | 15368.40 | 01-MAY-00:10 | 1701.53 | 01-MAY-19:10 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 152.76 | 05-MAY-12:00 | 23.41 | 10-MAY-19:56 |
June | 15368.40 | 01-JUN-00:10 | 1701.53 | 01-JUN-19:10 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 142.14 | 16-JUN-13:00 | 11.66 | 25-JUN-21:00 |
July | 15368.40 | 01-JUL-00:10 | 1701.53 | 03-JUL-19:10 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 115.25 | 28-JUL-13:00 | 11.69 | 19-JUL-18:58 |
August | 15368.40 | 01-AUG-00:10 | 1701.53 | 01-AUG-19:10 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 124.66 | 22-AUG-15:00 | 11.71 | 23-AUG-19:56 |
September | 15368.40 | 01-SEP-00:10 | 1701.53 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.83 | 06-SEP-14:00 | 11.06 | 15-SEP-21:10 |
October | 15368.40 | 01-OCT-23:10 | 1701.53 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 106.72 | 04-OCT-14:00 | 10.71 | 23-OCT-24:00 |
November | 15368.40 | 01-NOV-00:10 | 1701.53 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 115.85 | 18-NOV-13:00 | 44.92 | 25-NOV-05:00 |
December | 15368.40 | 01-DEC-00:10 | 1701.53 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.48 | 08-DEC-14:00 | 65.86 | 21-DEC-05:20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 15368.40 | 1701.53 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 101.48 | 0.00 | |||||
Maximum of Months | 15368.40 | 1701.53 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 152.76 | 65.86 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 9504.80 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 355.38 | 04-JAN-13:00 | 161.52 | 23-JAN-06:00 |
February | 45622.98 | 01-FEB-00:10 | 9504.80 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 387.94 | 26-FEB-14:00 | 90.07 | 02-FEB-07:00 |
March | 45622.98 | 01-MAR-00:10 | 9504.80 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 431.20 | 21-MAR-13:00 | 57.07 | 03-MAR-06:00 |
April | 45622.98 | 01-APR-00:10 | 9504.80 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 395.95 | 01-APR-14:00 | 0.00 | 01-APR-00:10 |
May | 45622.98 | 01-MAY-00:10 | 9504.80 | 01-MAY-19:10 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 449.75 | 06-MAY-13:00 | 66.91 | 10-MAY-19:56 |
June | 45622.98 | 01-JUN-00:10 | 9504.80 | 01-JUN-19:10 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 406.87 | 16-JUN-13:00 | 33.43 | 25-JUN-21:00 |
July | 45622.98 | 01-JUL-00:10 | 9504.80 | 03-JUL-19:10 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 329.23 | 28-JUL-13:00 | 33.42 | 19-JUL-18:53 |
August | 45622.98 | 01-AUG-00:10 | 9504.80 | 01-AUG-19:10 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 371.12 | 22-AUG-15:00 | 33.48 | 23-AUG-19:56 |
September | 45622.98 | 01-SEP-00:10 | 9504.80 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 361.62 | 12-SEP-14:00 | 27.92 | 15-SEP-21:00 |
October | 45622.98 | 01-OCT-23:10 | 9504.80 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 329.64 | 04-OCT-14:00 | 20.84 | 23-OCT-05:00 |
November | 45622.98 | 01-NOV-00:10 | 9504.80 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 357.03 | 18-NOV-13:00 | 120.49 | 25-NOV-05:00 |
December | 45622.98 | 01-DEC-00:10 | 9504.80 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 317.64 | 07-DEC-14:00 | 181.65 | 21-DEC-05:30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 45622.98 | 9504.80 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 317.64 | 0.00 | |||||
Maximum of Months | 45622.98 | 9504.80 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 449.75 | 181.65 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.88 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 34.88 | 03-JAN-16:10 | 13.65 | 24-JAN-09:00 |
February | 180.00 | 01-FEB-00:10 | 177.88 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.67 | 22-FEB-16:10 | 2.66 | 21-FEB-10:00 |
March | 180.00 | 01-MAR-00:10 | 177.88 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.49 | 19-MAR-15:10 | 0.00 | 01-MAR-00:03 |
April | 180.00 | 01-APR-00:10 | 177.88 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.23 | 01-APR-15:10 | 0.00 | 01-APR-00:10 |
May | 180.00 | 01-MAY-00:10 | 177.88 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.27 | 06-MAY-15:10 | 0.00 | 01-MAY-00:10 |
June | 180.00 | 01-JUN-00:10 | 177.88 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.28 | 13-JUN-15:10 | 0.00 | 01-JUN-00:10 |
July | 180.00 | 01-JUL-00:10 | 177.88 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.56 | 15-JUL-16:00 | 0.55 | 03-JUL-13:00 |
August | 180.00 | 01-AUG-00:10 | 177.88 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.12 | 13-AUG-15:10 | 4.24 | 20-AUG-11:00 |
September | 180.00 | 01-SEP-00:10 | 177.88 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.12 | 04-SEP-16:00 | 0.64 | 15-SEP-17:10 |
October | 180.00 | 01-OCT-00:10 | 177.88 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.21 | 04-OCT-15:10 | 1.16 | 22-OCT-18:00 |
November | 180.00 | 01-NOV-00:10 | 177.88 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.25 | 18-NOV-13:00 | 3.58 | 25-NOV-05:00 |
December | 180.00 | 01-DEC-00:10 | 177.88 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.99 | 13-DEC-16:10 | 9.88 | 21-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 31.99 | 0.00 | |||||
Maximum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 45.27 | 13.65 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.86 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 34.88 | 03-JAN-16:10 | 13.88 | 24-JAN-09:00 |
February | 180.00 | 01-FEB-00:10 | 177.86 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.17 | 22-FEB-16:10 | 6.15 | 24-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 177.86 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.51 | 19-MAR-15:10 | 0.31 | 03-MAR-06:30 |
April | 180.00 | 01-APR-00:10 | 177.86 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.23 | 01-APR-15:10 | 1.68 | 14-APR-16:00 |
May | 180.00 | 01-MAY-00:10 | 177.86 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.22 | 06-MAY-15:10 | 5.28 | 10-MAY-20:40 |
June | 180.00 | 01-JUN-00:10 | 177.86 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.25 | 13-JUN-15:10 | 4.67 | 25-JUN-20:50 |
July | 180.00 | 01-JUL-00:10 | 177.86 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.56 | 15-JUL-16:00 | 4.87 | 19-JUL-20:30 |
August | 180.00 | 01-AUG-00:10 | 177.86 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.12 | 13-AUG-15:10 | 4.24 | 20-AUG-11:00 |
September | 180.00 | 01-SEP-00:10 | 177.86 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.11 | 04-SEP-16:00 | 3.17 | 15-SEP-21:00 |
October | 180.00 | 01-OCT-00:10 | 177.86 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.20 | 04-OCT-15:10 | 3.26 | 22-OCT-18:00 |
November | 180.00 | 01-NOV-00:10 | 177.86 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.25 | 18-NOV-13:00 | 5.28 | 25-NOV-06:30 |
December | 180.00 | 01-DEC-00:10 | 177.86 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.99 | 13-DEC-16:10 | 12.71 | 21-DEC-06:50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 31.99 | 0.31 | |||||
Maximum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 45.22 | 13.88 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 111.79 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6.09 | 04-JAN-13:00 | 6.97 | 23-JAN-06:00 |
February | 0.00 | 01-FEB-00:10 | 111.79 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 26-FEB-14:00 | 5.57 | 21-FEB-10:00 |
March | 0.00 | 01-MAR-00:10 | 111.79 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.90 | 21-MAR-13:00 | 4.05 | 03-MAR-06:00 |
April | 0.00 | 01-APR-00:10 | 111.79 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.19 | 01-APR-14:00 | 3.26 | 14-APR-15:52 |
May | 0.00 | 01-MAY-00:10 | 111.79 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.86 | 06-MAY-13:00 | 4.04 | 10-MAY-19:52 |
June | 0.00 | 01-JUN-00:10 | 111.79 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.60 | 13-JUN-14:00 | 3.18 | 25-JUN-23:00 |
July | 0.00 | 01-JUL-00:10 | 111.79 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.35 | 15-JUL-16:00 | 3.17 | 13-JUL-05:00 |
August | 0.00 | 01-AUG-00:10 | 111.79 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.01 | 22-AUG-15:00 | 4.05 | 20-AUG-11:00 |
September | 0.00 | 01-SEP-00:10 | 111.79 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.01 | 12-SEP-14:00 | 3.27 | 19-SEP-04:00 |
October | 0.00 | 01-OCT-00:10 | 111.79 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.21 | 04-OCT-14:00 | 3.61 | 23-OCT-05:00 |
November | 0.00 | 01-NOV-00:10 | 111.79 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.25 | 18-NOV-13:00 | 5.80 | 25-NOV-05:00 |
December | 0.00 | 01-DEC-00:10 | 111.79 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.19 | 07-DEC-14:00 | 7.61 | 21-DEC-05:20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 0.00 | 111.79 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 5.19 | 3.17 | |||||
Maximum of Months | 0.00 | 111.79 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 8.86 | 7.61 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 111.82 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9.73 | 03-JAN-16:10 | 3.58 | 24-JAN-09:00 |
February | 180.00 | 01-FEB-00:10 | 111.82 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.93 | 22-FEB-16:08 | 1.40 | 02-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 111.82 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.31 | 19-MAR-15:08 | 0.00 | 01-MAR-00:03 |
April | 180.00 | 01-APR-00:10 | 111.82 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.23 | 01-APR-15:10 | 0.00 | 01-APR-00:10 |
May | 180.00 | 01-MAY-00:10 | 111.82 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.64 | 06-MAY-15:10 | 0.86 | 10-MAY-20:40 |
June | 180.00 | 01-JUN-00:10 | 111.82 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.08 | 13-JUN-15:10 | 0.80 | 25-JUN-21:00 |
July | 180.00 | 01-JUL-00:10 | 111.82 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.93 | 15-JUL-16:00 | 0.70 | 19-JUL-20:40 |
August | 180.00 | 01-AUG-00:10 | 111.82 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.08 | 13-AUG-15:10 | 1.07 | 20-AUG-11:00 |
September | 180.00 | 01-SEP-00:10 | 111.82 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.80 | 04-SEP-16:00 | 0.63 | 15-SEP-21:00 |
October | 180.00 | 01-OCT-00:10 | 111.82 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.27 | 04-OCT-15:08 | 0.60 | 22-OCT-18:00 |
November | 180.00 | 01-NOV-00:10 | 111.82 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 18-NOV-13:00 | 1.25 | 25-NOV-08:10 |
December | 180.00 | 01-DEC-00:10 | 111.82 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.93 | 13-DEC-16:10 | 3.43 | 21-DEC-06:50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 8.93 | 0.00 | |||||
Maximum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 12.64 | 3.58 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.88 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 34.88 | 03-JAN-16:10 | 13.65 | 24-JAN-09:00 |
February | 180.00 | 01-FEB-00:10 | 177.88 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.18 | 22-FEB-16:10 | 2.66 | 21-FEB-10:00 |
March | 180.00 | 01-MAR-00:10 | 177.88 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.52 | 19-MAR-15:10 | 0.00 | 01-MAR-00:03 |
April | 180.00 | 01-APR-00:10 | 177.88 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.23 | 01-APR-15:10 | 0.00 | 01-APR-00:10 |
May | 180.00 | 01-MAY-00:10 | 177.88 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.29 | 06-MAY-15:10 | 0.00 | 01-MAY-00:10 |
June | 180.00 | 01-JUN-00:10 | 177.88 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.28 | 13-JUN-15:10 | 0.00 | 01-JUN-00:10 |
July | 180.00 | 01-JUL-00:10 | 177.88 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.56 | 15-JUL-16:00 | 0.55 | 03-JUL-13:00 |
August | 180.00 | 01-AUG-00:10 | 177.88 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.12 | 13-AUG-15:10 | 4.24 | 20-AUG-11:00 |
September | 180.00 | 01-SEP-00:10 | 177.88 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.12 | 04-SEP-16:00 | 0.46 | 15-SEP-17:10 |
October | 180.00 | 01-OCT-00:10 | 177.88 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.21 | 04-OCT-15:10 | 1.16 | 22-OCT-18:00 |
November | 180.00 | 01-NOV-00:10 | 177.88 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.25 | 18-NOV-13:00 | 3.58 | 25-NOV-05:00 |
December | 180.00 | 01-DEC-00:10 | 177.88 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.00 | 13-DEC-16:10 | 9.88 | 21-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 32.00 | 0.00 | |||||
Maximum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 45.29 | 13.65 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.86 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 34.88 | 03-JAN-16:10 | 17.06 | 24-JAN-09:00 |
February | 180.00 | 01-FEB-00:10 | 177.86 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.18 | 22-FEB-16:10 | 8.13 | 24-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 177.86 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.51 | 19-MAR-15:10 | 1.20 | 15-MAR-07:30 |
April | 180.00 | 01-APR-00:10 | 177.86 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.23 | 01-APR-15:10 | 0.58 | 14-APR-16:00 |
May | 180.00 | 01-MAY-00:10 | 177.86 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.29 | 06-MAY-15:10 | 4.57 | 10-MAY-20:30 |
June | 180.00 | 01-JUN-00:10 | 177.86 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.28 | 13-JUN-15:10 | 4.10 | 25-JUN-21:00 |
July | 180.00 | 01-JUL-00:10 | 177.86 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.56 | 15-JUL-16:00 | 3.78 | 19-JUL-20:30 |
August | 180.00 | 01-AUG-00:10 | 177.86 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.12 | 13-AUG-15:10 | 4.24 | 20-AUG-11:00 |
September | 180.00 | 01-SEP-00:10 | 177.86 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.11 | 04-SEP-16:00 | 2.97 | 15-SEP-21:00 |
October | 180.00 | 01-OCT-00:10 | 177.86 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.20 | 04-OCT-15:10 | 3.28 | 30-OCT-17:50 |
November | 180.00 | 01-NOV-00:10 | 177.86 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.25 | 18-NOV-13:00 | 7.66 | 25-NOV-08:10 |
December | 180.00 | 01-DEC-00:10 | 177.86 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.99 | 13-DEC-16:10 | 14.01 | 21-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 31.99 | 0.58 | |||||
Maximum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 45.29 | 17.06 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2263.36 | 02-JAN-00:10 | 1867.32 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.65 | 04-JAN-13:00 | 16.30 | 23-JAN-06:00 |
February | 2263.36 | 01-FEB-00:10 | 1867.32 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.78 | 21-FEB-14:00 | 10.56 | 21-FEB-10:00 |
March | 2263.36 | 01-MAR-00:10 | 1867.32 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.52 | 21-MAR-13:00 | 4.35 | 03-MAR-06:00 |
April | 2263.36 | 01-APR-00:10 | 1867.32 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.28 | 01-APR-14:00 | 0.55 | 14-APR-15:52 |
May | 2263.36 | 01-MAY-00:10 | 1867.32 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.17 | 06-MAY-13:00 | 6.31 | 10-MAY-19:52 |
June | 2263.36 | 01-JUN-00:10 | 1867.32 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.18 | 24-JUN-14:00 | 2.63 | 20-JUN-24:00 |
July | 2263.36 | 01-JUL-00:10 | 1867.32 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.61 | 15-JUL-16:00 | 0.84 | 19-JUL-18:52 |
August | 2263.36 | 01-AUG-00:10 | 1867.32 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.17 | 22-AUG-15:00 | 1.30 | 20-AUG-11:00 |
September | 2263.36 | 01-SEP-00:10 | 1867.32 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.20 | 12-SEP-14:00 | 0.33 | 15-SEP-21:00 |
October | 2263.36 | 01-OCT-23:10 | 1867.32 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.21 | 28-OCT-13:00 | 0.25 | 23-OCT-05:00 |
November | 2263.36 | 01-NOV-00:10 | 1867.32 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.67 | 18-NOV-13:00 | 11.76 | 25-NOV-05:00 |
December | 2263.36 | 01-DEC-00:10 | 1867.32 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.56 | 07-DEC-14:00 | 17.64 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.56 | 0.25 | ||||
Maximum of Months | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.17 | 17.64 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.88 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 34.71 | 03-JAN-16:10 | 13.83 | 24-JAN-09:00 |
February | 180.00 | 01-FEB-00:10 | 177.88 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.46 | 22-FEB-16:10 | 2.85 | 21-FEB-10:00 |
March | 180.00 | 01-MAR-00:10 | 177.88 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.82 | 19-MAR-15:40 | 0.00 | 01-MAR-00:03 |
April | 180.00 | 01-APR-00:10 | 177.88 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.96 | 01-APR-15:10 | 0.00 | 01-APR-00:10 |
May | 180.00 | 01-MAY-00:10 | 177.88 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.92 | 06-MAY-15:10 | 0.12 | 21-MAY-13:00 |
June | 180.00 | 01-JUN-00:10 | 177.88 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.94 | 13-JUN-15:10 | 0.12 | 30-JUN-13:00 |
July | 180.00 | 01-JUL-00:10 | 177.88 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.40 | 15-JUL-16:00 | 0.73 | 03-JUL-13:00 |
August | 180.00 | 01-AUG-00:10 | 177.88 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.95 | 13-AUG-15:10 | 4.42 | 20-AUG-11:00 |
September | 180.00 | 01-SEP-00:10 | 177.88 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.95 | 04-SEP-16:00 | 0.83 | 15-SEP-17:10 |
October | 180.00 | 01-OCT-00:10 | 177.88 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.71 | 04-OCT-15:10 | 1.34 | 22-OCT-18:00 |
November | 180.00 | 01-NOV-00:10 | 177.88 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.09 | 18-NOV-13:00 | 3.77 | 25-NOV-05:00 |
December | 180.00 | 01-DEC-00:10 | 177.88 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.77 | 13-DEC-16:10 | 10.07 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 31.77 | 0.00 | |||||
Maximum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 44.92 | 13.83 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.86 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 34.71 | 03-JAN-16:10 | 13.46 | 24-JAN-09:00 |
February | 180.00 | 01-FEB-00:10 | 177.86 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.43 | 22-FEB-16:10 | 5.08 | 24-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 177.86 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.87 | 19-MAR-15:40 | 0.00 | 01-MAR-00:03 |
April | 180.00 | 01-APR-00:10 | 177.86 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.87 | 01-APR-15:10 | 2.40 | 14-APR-16:00 |
May | 180.00 | 01-MAY-00:10 | 177.86 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.70 | 06-MAY-15:10 | 5.50 | 10-MAY-20:40 |
June | 180.00 | 01-JUN-00:10 | 177.86 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.08 | 13-JUN-15:10 | 5.71 | 25-JUN-21:30 |
July | 180.00 | 01-JUL-00:10 | 177.86 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.39 | 15-JUL-16:00 | 6.23 | 19-JUL-21:10 |
August | 180.00 | 01-AUG-00:10 | 177.86 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.94 | 13-AUG-15:10 | 4.86 | 23-AUG-21:00 |
September | 180.00 | 01-SEP-00:10 | 177.86 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.94 | 04-SEP-16:00 | 4.13 | 15-SEP-21:00 |
October | 180.00 | 01-OCT-00:10 | 177.86 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.03 | 04-OCT-15:10 | 4.36 | 30-OCT-18:00 |
November | 180.00 | 01-NOV-00:10 | 177.86 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.08 | 18-NOV-13:00 | 5.29 | 25-NOV-22:00 |
December | 180.00 | 01-DEC-00:10 | 177.86 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.82 | 13-DEC-16:10 | 11.41 | 21-DEC-06:50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 31.82 | 0.00 | |||||
Maximum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 44.70 | 13.46 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 111.82 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 17.22 | 03-JAN-16:10 | 7.08 | 24-JAN-09:00 |
February | 180.00 | 01-FEB-00:10 | 111.82 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.37 | 22-FEB-16:10 | 1.46 | 21-FEB-10:00 |
March | 180.00 | 01-MAR-00:10 | 111.82 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.36 | 19-MAR-15:40 | 0.00 | 01-MAR-00:03 |
April | 180.00 | 01-APR-00:10 | 111.82 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.36 | 11-APR-15:10 | 0.00 | 01-APR-00:10 |
May | 180.00 | 01-MAY-00:10 | 111.82 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.93 | 06-MAY-15:10 | 0.06 | 21-MAY-13:00 |
June | 180.00 | 01-JUN-00:10 | 111.82 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.05 | 13-JUN-15:10 | 0.06 | 30-JUN-13:00 |
July | 180.00 | 01-JUL-00:10 | 111.82 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.11 | 15-JUL-16:00 | 0.37 | 03-JUL-13:00 |
August | 180.00 | 01-AUG-00:10 | 111.82 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.39 | 13-AUG-15:10 | 2.26 | 20-AUG-11:00 |
September | 180.00 | 01-SEP-00:10 | 111.82 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.88 | 04-SEP-16:00 | 0.33 | 15-SEP-17:10 |
October | 180.00 | 01-OCT-00:10 | 111.82 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.63 | 04-OCT-15:10 | 0.69 | 22-OCT-18:00 |
November | 180.00 | 01-NOV-00:10 | 111.82 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.42 | 18-NOV-13:00 | 1.93 | 25-NOV-05:00 |
December | 180.00 | 01-DEC-00:10 | 111.82 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.64 | 13-DEC-16:10 | 5.15 | 21-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 15.64 | 0.00 | |||||
Maximum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 22.93 | 7.08 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2988.03 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.73 | 04-JAN-13:00 | 41.13 | 23-JAN-06:00 |
February | 26988.77 | 01-FEB-00:10 | 2988.03 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.18 | 28-FEB-14:00 | 24.18 | 02-FEB-07:00 |
March | 26988.77 | 01-MAR-00:10 | 2988.03 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 92.32 | 21-MAR-13:00 | 15.78 | 03-MAR-06:00 |
April | 26988.77 | 01-APR-00:10 | 2988.03 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.61 | 01-APR-14:00 | 7.08 | 14-APR-15:52 |
May | 26988.77 | 01-MAY-00:10 | 2988.03 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.14 | 06-MAY-13:00 | 15.77 | 10-MAY-19:56 |
June | 26988.77 | 01-JUN-00:10 | 2988.03 | 01-JUN-19:10 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.03 | 16-JUN-13:00 | 8.25 | 27-JUN-05:23 |
July | 26988.77 | 01-JUL-00:10 | 2988.03 | 03-JUL-19:10 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.37 | 28-JUL-13:00 | 8.26 | 19-JUL-18:55 |
August | 26988.77 | 01-AUG-00:10 | 2988.03 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.35 | 10-AUG-14:00 | 8.27 | 23-AUG-19:56 |
September | 26988.77 | 01-SEP-00:10 | 2988.03 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.94 | 12-SEP-14:00 | 8.98 | 19-SEP-04:00 |
October | 26988.77 | 01-OCT-23:10 | 2988.03 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.08 | 04-OCT-14:00 | 11.97 | 23-OCT-05:00 |
November | 26988.77 | 01-NOV-00:10 | 2988.03 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.25 | 18-NOV-13:00 | 31.00 | 25-NOV-05:00 |
December | 26988.77 | 01-DEC-00:10 | 2988.03 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.33 | 07-DEC-15:00 | 46.63 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 69.37 | 7.08 | |||||
Maximum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 96.14 | 46.63 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2988.03 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.93 | 04-JAN-13:00 | 41.13 | 23-JAN-06:00 |
February | 26988.77 | 01-FEB-00:10 | 2988.03 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.26 | 28-FEB-14:00 | 24.18 | 02-FEB-07:00 |
March | 26988.77 | 01-MAR-00:10 | 2988.03 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.42 | 21-MAR-13:00 | 15.78 | 03-MAR-06:00 |
April | 26988.77 | 01-APR-00:10 | 2988.03 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.61 | 01-APR-14:00 | 8.08 | 14-APR-15:52 |
May | 26988.77 | 01-MAY-00:10 | 2988.03 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.14 | 06-MAY-13:00 | 15.77 | 10-MAY-19:56 |
June | 26988.77 | 01-JUN-00:10 | 2988.03 | 01-JUN-19:10 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.26 | 13-JUN-14:00 | 8.25 | 27-JUN-05:23 |
July | 26988.77 | 01-JUL-00:10 | 2988.03 | 03-JUL-19:10 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.25 | 28-JUL-13:00 | 8.26 | 19-JUL-18:55 |
August | 26988.77 | 01-AUG-00:10 | 2988.03 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.40 | 10-AUG-14:00 | 8.73 | 20-AUG-11:00 |
September | 26988.77 | 01-SEP-00:10 | 2988.03 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.96 | 12-SEP-14:00 | 8.98 | 19-SEP-04:00 |
October | 26988.77 | 01-OCT-23:10 | 2988.03 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.13 | 04-OCT-14:00 | 11.97 | 23-OCT-05:00 |
November | 26988.77 | 01-NOV-00:10 | 2988.03 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.35 | 18-NOV-13:00 | 31.00 | 25-NOV-05:00 |
December | 26988.77 | 01-DEC-00:10 | 2988.03 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.67 | 07-DEC-15:00 | 46.63 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 68.25 | 8.08 | |||||
Maximum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 96.14 | 46.63 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 1060.81 | 02-JAN-20:10 | 14912.86 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 64.71 | 04-JAN-13:00 | 34.70 | 24-JAN-09:00 |
February | 2401.70 | 01-FEB-00:10 | 1060.81 | 01-FEB-20:10 | 14912.86 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 70.46 | 26-FEB-14:00 | 25.79 | 21-FEB-10:00 |
March | 2401.70 | 01-MAR-00:10 | 1060.81 | 01-MAR-20:10 | 14912.86 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 78.62 | 21-MAR-13:00 | 12.56 | 03-MAR-06:10 |
April | 2401.70 | 01-APR-00:10 | 1060.81 | 03-APR-19:10 | 14912.86 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 73.12 | 01-APR-14:00 | 8.04 | 14-APR-15:58 |
May | 2401.70 | 01-MAY-00:10 | 1060.81 | 01-MAY-19:10 | 14912.86 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 86.14 | 06-MAY-13:00 | 14.10 | 10-MAY-20:00 |
June | 2401.70 | 01-JUN-00:10 | 1060.81 | 01-JUN-19:10 | 14912.86 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 76.40 | 13-JUN-14:00 | 7.37 | 27-JUN-05:10 |
July | 2401.70 | 01-JUL-00:10 | 1060.81 | 03-JUL-19:10 | 14912.86 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 58.83 | 15-JUL-16:00 | 7.37 | 19-JUL-18:58 |
August | 2401.70 | 01-AUG-00:10 | 1060.81 | 01-AUG-19:10 | 14912.86 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 64.01 | 22-AUG-15:00 | 14.05 | 20-AUG-11:00 |
September | 2401.70 | 01-SEP-00:10 | 1060.81 | 01-SEP-19:10 | 14912.86 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 64.00 | 12-SEP-14:00 | 7.36 | 15-SEP-23:00 |
October | 2401.70 | 01-OCT-23:10 | 1060.81 | 02-OCT-19:10 | 14912.86 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 57.78 | 04-OCT-14:00 | 7.61 | 23-OCT-05:30 |
November | 2401.70 | 01-NOV-00:10 | 1060.81 | 01-NOV-19:10 | 14912.86 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 65.93 | 18-NOV-13:00 | 22.74 | 25-NOV-06:20 |
December | 2401.70 | 01-DEC-00:10 | 1060.81 | 01-DEC-20:10 | 14912.86 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 57.67 | 08-DEC-14:00 | 39.79 | 21-DEC-06:30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2401.70 | 1060.81 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 57.67 | 7.36 | ||||||
Maximum of Months | 2401.70 | 1060.81 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 86.14 | 39.79 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2395.44 | 02-JAN-00:10 | 1976.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.23 | 04-JAN-13:00 | 25.74 | 23-JAN-06:00 |
February | 2395.44 | 01-FEB-00:10 | 1976.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.52 | 28-FEB-14:00 | 20.78 | 21-FEB-10:00 |
March | 2395.44 | 01-MAR-00:10 | 1976.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.23 | 21-MAR-13:00 | 6.66 | 03-MAR-06:00 |
April | 2395.44 | 01-APR-00:10 | 1976.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.49 | 01-APR-14:00 | 2.33 | 14-APR-15:52 |
May | 2395.44 | 01-MAY-00:10 | 1976.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.23 | 06-MAY-13:00 | 13.83 | 10-MAY-19:54 |
June | 2395.44 | 01-JUN-00:10 | 1976.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.70 | 13-JUN-14:00 | 5.26 | 20-JUN-24:00 |
July | 2395.44 | 01-JUL-00:10 | 1976.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.43 | 28-JUL-13:00 | 5.68 | 19-JUL-18:52 |
August | 2395.44 | 01-AUG-00:10 | 1976.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.42 | 22-AUG-15:00 | 5.01 | 23-AUG-19:52 |
September | 2395.44 | 01-SEP-00:10 | 1976.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.51 | 12-SEP-14:00 | 1.51 | 15-SEP-21:00 |
October | 2395.44 | 01-OCT-23:10 | 1976.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.89 | 04-OCT-14:00 | 0.58 | 09-OCT-18:53 |
November | 2395.44 | 01-NOV-00:10 | 1976.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.43 | 18-NOV-13:00 | 18.74 | 25-NOV-05:00 |
December | 2395.44 | 01-DEC-00:10 | 1976.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.36 | 08-DEC-14:00 | 29.30 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.36 | 0.58 | ||||
Maximum of Months | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.23 | 29.30 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 20989.08 | 06-JAN-22:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 20994.27 | 24-FEB-22:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 20845.31 | 01-MAR-22:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 20947.97 | 28-APR-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 21262.42 | 08-MAY-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 22201.02 | 15-JUN-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 21237.60 | 28-JUL-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 21259.21 | 15-AUG-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 21194.47 | 08-SEP-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 20914.48 | 05-OCT-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 21096.85 | 22-NOV-22:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 21135.26 | 08-DEC-22:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 20845.31 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22201.02 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3774.52 | 05-JAN-15:10 | 389.84 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 49.52 | 0.00 |
February | 3447.65 | 03-FEB-16:03 | 3898.44 | 995.99 | 1515.54 | 0.00 | 0.00 | 0.00 | 0.00 | 46.78 | 0.00 |
March | 3154.76 | 13-MAR-19:20 | 909.64 | 597.59 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 25.83 | 0.00 |
April | 3008.80 | 11-APR-19:20 | 909.64 | 597.59 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 28.74 | 0.00 |
May | 3282.62 | 05-MAY-19:10 | 909.64 | 597.59 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 35.46 | 0.00 |
June | 3306.17 | 12-JUN-19:20 | 909.64 | 597.59 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 35.64 | 0.00 |
July | 2925.05 | 14-JUL-20:10 | 1039.58 | 531.19 | 649.52 | 0.00 | 0.00 | 0.00 | 0.00 | 27.47 | 0.00 |
August | 2912.45 | 14-AUG-19:20 | 909.64 | 597.59 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 27.87 | 0.00 |
September | 3152.99 | 13-SEP-19:30 | 909.64 | 597.59 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 32.23 | 0.00 |
October | 3033.52 | 04-OCT-19:10 | 909.64 | 597.59 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 22.92 | 0.00 |
November | 3381.60 | 19-NOV-13:00 | 389.84 | 199.20 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 42.91 | 0.00 |
December | 3748.03 | 08-DEC-14:00 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 45.90 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2912.45 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 22.92 | 0.00 | |
Maximum of Months | 3774.52 | 3898.44 | 995.99 | 1515.54 | 0.00 | 0.00 | 0.00 | 0.00 | 49.52 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2320.07 | 31-JAN-21:10 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 0.00 |
February | 2432.23 | 22-FEB-21:10 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 6.93 | 0.00 |
March | 2462.15 | 29-MAR-20:10 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 8.03 | 0.00 |
April | 2505.17 | 27-APR-20:10 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 10.69 | 0.00 |
May | 2631.70 | 05-MAY-20:10 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 11.60 | 0.00 |
June | 2735.49 | 13-JUN-20:10 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 13.25 | 0.00 |
July | 2442.62 | 14-JUL-20:50 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 9.16 | 0.00 |
August | 2407.32 | 14-AUG-20:10 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 9.98 | 0.00 |
September | 2563.26 | 13-SEP-20:10 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 11.80 | 0.00 |
October | 2306.63 | 04-OCT-20:10 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 7.86 | 0.00 |
November | 2289.48 | 03-NOV-20:10 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 3.03 | 0.00 |
December | 2254.73 | 07-DEC-21:10 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 5.81 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2254.73 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 3.03 | 0.00 | |
Maximum of Months | 2735.49 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 13.25 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1994.78 | 05-JAN-21:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 15.41 | 0.00 |
February | 2013.22 | 27-FEB-21:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 12.58 | 0.00 |
March | 2186.02 | 29-MAR-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 18.96 | 0.00 |
April | 2747.22 | 30-APR-19:50 | 190.94 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 29.48 | 0.00 |
May | 3220.25 | 05-MAY-19:30 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 30.68 | 0.00 |
June | 3721.40 | 13-JUN-19:30 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 32.36 | 0.00 |
July | 3113.33 | 14-JUL-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 25.90 | 0.00 |
August | 2771.69 | 01-AUG-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 23.57 | 0.00 |
September | 2355.53 | 08-SEP-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 23.67 | 0.00 |
October | 2020.23 | 04-OCT-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 19.45 | 0.00 |
November | 2004.86 | 21-NOV-21:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 19.85 | 0.00 |
December | 1987.82 | 08-DEC-22:00 | 254.59 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 20.78 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1987.82 | 190.94 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 12.58 | 0.00 | |
Maximum of Months | 3721.40 | 254.59 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 32.36 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1075.74 | 05-JAN-22:10 | 220.32 | 167.89 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 7.95 | 0.00 |
February | 1084.19 | 22-FEB-22:10 | 220.32 | 167.89 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 9.43 | 0.00 |
March | 1106.27 | 29-MAR-21:10 | 220.32 | 167.89 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 11.60 | 0.00 |
April | 1304.58 | 30-APR-19:20 | 146.88 | 223.85 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 22.40 | 0.00 |
May | 1562.23 | 06-MAY-19:00 | 146.88 | 195.87 | 203.92 | 0.00 | 0.00 | 0.00 | 0.00 | 22.31 | 0.00 |
June | 1802.75 | 13-JUN-19:30 | 171.36 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 18.67 | 0.00 |
July | 1458.26 | 14-JUL-20:00 | 171.36 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 14.94 | 0.00 |
August | 1292.40 | 01-AUG-20:00 | 171.36 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 13.60 | 0.00 |
September | 1118.82 | 07-SEP-21:10 | 220.32 | 167.89 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 13.79 | 0.00 |
October | 1087.77 | 04-OCT-21:10 | 220.32 | 167.89 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 10.43 | 0.00 |
November | 1080.88 | 21-NOV-22:10 | 220.32 | 167.89 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 10.38 | 0.00 |
December | 1074.78 | 08-DEC-22:10 | 220.32 | 167.89 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 12.12 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1074.78 | 146.88 | 167.89 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 7.95 | 0.00 | |
Maximum of Months | 1802.75 | 220.32 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 22.40 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 35681.32 | 04-JAN-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 18.19 | 0.00 |
February | 35905.67 | 22-FEB-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 22.77 | 0.00 |
March | 36260.66 | 29-MAR-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 25.89 | 0.00 |
April | 36531.78 | 28-APR-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 32.19 | 0.00 |
May | 36916.26 | 05-MAY-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 38.47 | 0.00 |
June | 36861.88 | 13-JUN-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 44.84 | 0.00 |
July | 36374.74 | 14-JUL-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 35.37 | 0.00 |
August | 36249.41 | 01-AUG-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 32.18 | 0.00 |
September | 36184.03 | 06-SEP-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 29.12 | 0.00 |
October | 35836.35 | 04-OCT-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 25.91 | 0.00 |
November | 35589.31 | 22-NOV-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 6.54 | 0.00 |
December | 35570.48 | 08-DEC-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 25.93 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 35570.48 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 6.54 | 0.00 | |
Maximum of Months | 36916.26 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 44.84 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12857.62 | 05-JAN-22:10 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 27.57 | 0.00 |
February | 12519.40 | 22-FEB-22:10 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 34.78 | 0.00 |
March | 12340.35 | 13-MAR-21:10 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 46.37 | 0.00 |
April | 12020.81 | 19-APR-21:10 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 56.88 | 0.00 |
May | 12516.86 | 05-MAY-21:10 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 57.40 | 0.00 |
June | 12449.95 | 13-JUN-21:10 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 56.96 | 0.00 |
July | 11633.94 | 26-JUL-21:10 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 33.09 | 0.00 |
August | 11898.32 | 14-AUG-21:10 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 56.63 | 0.00 |
September | 12137.44 | 13-SEP-21:10 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 60.93 | 0.00 |
October | 12214.65 | 16-OCT-21:10 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 34.85 | 0.00 |
November | 12422.34 | 21-NOV-22:10 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 38.45 | 0.00 |
December | 12923.47 | 08-DEC-22:10 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 45.10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 11633.94 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 27.57 | 0.00 | |
Maximum of Months | 12923.47 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 60.93 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 41840.88 | 05-JAN-22:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 78.69 | 0.00 |
February | 41550.43 | 22-FEB-22:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 99.28 | 0.00 |
March | 41377.70 | 29-MAR-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 132.57 | 0.00 |
April | 42672.77 | 28-APR-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 145.20 | 0.00 |
May | 45564.79 | 05-MAY-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 163.91 | 0.00 |
June | 47549.67 | 13-JUN-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 162.64 | 0.00 |
July | 43610.67 | 14-JUL-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 138.70 | 0.00 |
August | 42562.00 | 01-AUG-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 158.46 | 0.00 |
September | 41411.39 | 13-SEP-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 174.00 | 0.00 |
October | 40406.28 | 04-OCT-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 112.49 | 0.00 |
November | 40905.16 | 21-NOV-22:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 109.77 | 0.00 |
December | 41739.15 | 08-DEC-22:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 128.77 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 40406.28 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 78.69 | 0.00 | |
Maximum of Months | 47549.67 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 174.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2860.81 | 10-JAN-19:02 | 831.60 | 949.89 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 16.74 | 0.00 |
February | 2851.37 | 08-FEB-19:02 | 831.60 | 949.89 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 13.61 | 0.00 |
March | 2860.91 | 14-MAR-18:02 | 831.60 | 949.89 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 13.40 | 0.00 |
April | 2868.00 | 30-APR-08:62 | 324.00 | 597.68 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 20.38 | 0.00 |
May | 2872.90 | 11-MAY-18:02 | 831.60 | 949.89 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 11.96 | 0.00 |
June | 2884.56 | 03-JUN-15:02 | 324.00 | 352.21 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 16.77 | 0.00 |
July | 2881.80 | 10-JUL-15:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 11.36 | 0.00 |
August | 2897.77 | 16-AUG-15:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 15.94 | 0.00 |
September | 2873.68 | 16-SEP-18:01 | 819.00 | 1245.18 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 0.00 |
October | 2878.08 | 05-OCT-18:02 | 831.60 | 949.89 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 16.37 | 0.00 |
November | 2868.11 | 22-NOV-19:02 | 831.60 | 949.89 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 11.35 | 0.00 |
December | 2877.24 | 12-DEC-19:02 | 831.60 | 949.89 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 14.41 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2851.37 | 324.00 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 0.00 | |
Maximum of Months | 2897.77 | 831.60 | 1245.18 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 20.38 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2898.73 | 02-JAN-16:02 | 583.20 | 298.81 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 24.02 | 0.00 |
February | 2900.41 | 15-FEB-19:02 | 831.60 | 949.78 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 16.97 | 0.00 |
March | 2903.17 | 14-MAR-18:02 | 831.60 | 949.78 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 13.47 | 0.00 |
April | 2896.49 | 13-APR-18:02 | 831.60 | 949.78 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 16.59 | 0.00 |
May | 2895.53 | 13-MAY-08:62 | 324.00 | 597.61 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 25.73 | 0.00 |
June | 2922.68 | 24-JUN-20:11 | 1247.40 | 1600.75 | 1635.51 | 0.00 | 0.00 | 0.00 | 0.00 | 1.06 | 0.00 |
July | 2902.19 | 06-JUL-18:02 | 831.60 | 949.78 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 7.32 | 0.00 |
August | 2913.87 | 16-AUG-15:02 | 583.20 | 298.81 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 15.94 | 0.00 |
September | 2900.48 | 16-SEP-18:01 | 819.00 | 1245.03 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 4.01 | 0.00 |
October | 2909.36 | 10-OCT-18:02 | 831.60 | 949.78 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 13.18 | 0.00 |
November | 2908.96 | 20-NOV-19:02 | 831.60 | 949.78 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 17.74 | 0.00 |
December | 2889.75 | 11-DEC-16:02 | 583.20 | 298.81 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 19.84 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2889.75 | 324.00 | 298.81 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 1.06 | 0.00 | |
Maximum of Months | 2922.68 | 1247.40 | 1600.75 | 1635.51 | 0.00 | 0.00 | 0.00 | 0.00 | 25.73 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 503.57 | 05-JAN-14:30 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 5.84 | 0.00 |
February | 449.63 | 04-FEB-14:30 | 0.00 | 36.89 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 4.80 | 0.00 |
March | 370.27 | 11-MAR-09:00 | 0.00 | 62.60 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 1.09 | 0.00 |
April | 351.64 | 01-APR-20:20 | 0.00 | 111.79 | 178.01 | 0.00 | 0.00 | 0.00 | 0.00 | 2.19 | 0.00 |
May | 364.78 | 06-MAY-08:00 | 0.00 | 62.60 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 4.39 | 0.00 |
June | 353.06 | 13-JUN-20:20 | 0.00 | 99.50 | 178.01 | 0.00 | 0.00 | 0.00 | 0.00 | 3.02 | 0.00 |
July | 332.45 | 15-JUL-20:10 | 0.00 | 111.79 | 178.01 | 0.00 | 0.00 | 0.00 | 0.00 | 1.85 | 0.00 |
August | 329.31 | 14-AUG-21:00 | 0.00 | 99.50 | 178.01 | 0.00 | 0.00 | 0.00 | 0.00 | 1.92 | 0.00 |
September | 344.32 | 27-SEP-20:30 | 0.00 | 99.50 | 178.01 | 0.00 | 0.00 | 0.00 | 0.00 | 1.09 | 0.00 |
October | 391.45 | 29-OCT-08:00 | 0.00 | 62.60 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 1.08 | 0.00 |
November | 464.87 | 23-NOV-09:00 | 0.00 | 62.60 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 1.51 | 0.00 |
December | 504.65 | 07-DEC-13:50 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 5.03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 329.31 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 1.08 | 0.00 | |
Maximum of Months | 504.65 | 0.00 | 111.79 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 5.84 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1141.64 | 02-JAN-19:02 | 831.60 | 597.13 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 4.52 | 0.00 |
February | 1141.81 | 18-FEB-19:02 | 702.00 | 670.94 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 4.30 | 0.00 |
March | 1139.13 | 07-MAR-19:02 | 831.60 | 597.13 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 3.60 | 0.00 |
April | 1144.98 | 10-APR-18:02 | 831.60 | 597.13 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 6.31 | 0.00 |
May | 1151.45 | 01-MAY-15:02 | 583.20 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 9.19 | 0.00 |
June | 1149.33 | 22-JUN-15:02 | 583.20 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 4.75 | 0.00 |
July | 1151.47 | 19-JUL-15:02 | 583.20 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 8.03 | 0.00 |
August | 1151.09 | 05-AUG-08:61 | 378.00 | 438.35 | 1119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 3.76 | 0.00 |
September | 1144.16 | 25-SEP-18:02 | 831.60 | 597.13 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 5.01 | 0.00 |
October | 1145.46 | 20-OCT-18:02 | 831.60 | 597.13 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 4.54 | 0.00 |
November | 1144.32 | 06-NOV-19:02 | 831.60 | 597.13 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 3.46 | 0.00 |
December | 1141.84 | 11-DEC-19:02 | 831.60 | 597.13 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 3.81 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1139.13 | 378.00 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 3.46 | 0.00 | |
Maximum of Months | 1151.47 | 831.60 | 670.94 | 1119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 9.19 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2619.93 | 23-JAN-09:01 | 252.00 | 547.88 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 4.95 | 0.00 |
February | 2601.93 | 15-FEB-09:02 | 216.00 | 469.61 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 13.95 | 0.00 |
March | 2605.07 | 16-MAR-08:61 | 252.00 | 547.88 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 13.38 | 0.00 |
April | 2615.78 | 10-APR-18:02 | 831.60 | 949.89 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 23.04 | 0.00 |
May | 2618.93 | 03-MAY-08:62 | 216.00 | 469.61 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 20.31 | 0.00 |
June | 2617.29 | 07-JUN-08:62 | 216.00 | 469.61 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 22.36 | 0.00 |
July | 2628.23 | 14-JUL-08:61 | 252.00 | 547.88 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 9.35 | 0.00 |
August | 2612.34 | 30-AUG-08:61 | 252.00 | 547.88 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 13.90 | 0.00 |
September | 2611.23 | 01-SEP-18:02 | 831.60 | 949.89 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 19.85 | 0.00 |
October | 2612.14 | 02-OCT-08:61 | 252.00 | 547.88 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 13.90 | 0.00 |
November | 2607.89 | 09-NOV-09:01 | 252.00 | 547.88 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 15.65 | 0.00 |
December | 2656.14 | 15-DEC-09:01 | 360.00 | 782.68 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 10.02 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2601.93 | 216.00 | 469.61 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 4.95 | 0.00 | |
Maximum of Months | 2656.14 | 831.60 | 949.89 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 23.04 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2645.68 | 21-JAN-09:11 | 540.00 | 996.02 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 2.15 | 0.00 |
February | 2834.04 | 24-FEB-09:11 | 360.00 | 782.59 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 2.73 | 0.00 |
March | 2643.76 | 03-MAR-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 28.54 | 0.00 |
April | 2636.92 | 10-APR-18:02 | 831.60 | 949.78 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 23.06 | 0.00 |
May | 2637.26 | 19-MAY-08:62 | 216.00 | 469.55 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 22.33 | 0.00 |
June | 2639.26 | 24-JUN-20:11 | 1247.40 | 1600.75 | 1635.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.86 | 0.00 |
July | 2639.00 | 14-JUL-08:61 | 252.00 | 547.81 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 9.28 | 0.00 |
August | 2644.43 | 17-AUG-08:61 | 252.00 | 547.81 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 19.81 | 0.00 |
September | 2631.04 | 01-SEP-18:02 | 831.60 | 949.78 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 19.87 | 0.00 |
October | 2642.95 | 02-OCT-08:61 | 252.00 | 547.81 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 13.95 | 0.00 |
November | 2677.25 | 22-NOV-07:41 | 696.60 | 896.42 | 2133.28 | 0.00 | 0.00 | 0.00 | 0.00 | 4.80 | 0.00 |
December | 2665.89 | 27-DEC-09:01 | 360.00 | 782.59 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 3.99 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2631.04 | 216.00 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.86 | 0.00 | |
Maximum of Months | 2834.04 | 1247.40 | 1600.75 | 2133.28 | 0.00 | 0.00 | 0.00 | 0.00 | 28.54 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2671.56 | 31-JAN-22:10 | 2263.36 | 1244.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.92 | 0.00 |
February | 2694.02 | 24-FEB-22:10 | 2263.36 | 1244.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.84 | 0.00 |
March | 2672.61 | 29-MAR-21:10 | 2263.36 | 1244.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.10 | 0.00 |
April | 2675.57 | 28-APR-21:10 | 2263.36 | 1244.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.43 | 0.00 |
May | 2754.74 | 06-MAY-21:10 | 1760.39 | 1244.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.39 | 0.00 |
June | 3208.13 | 13-JUN-18:05 | 10562.33 | 9959.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.88 | 0.00 |
July | 2641.72 | 27-JUL-21:10 | 2263.36 | 1244.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.67 | 0.00 |
August | 2659.20 | 14-AUG-21:10 | 2263.36 | 1244.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.53 | 0.00 |
September | 2639.68 | 08-SEP-21:10 | 2263.36 | 1244.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.32 | 0.00 |
October | 2625.47 | 05-OCT-21:10 | 2263.36 | 1244.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.79 | 0.00 |
November | 2676.46 | 22-NOV-22:10 | 2263.36 | 1244.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.54 | 0.00 |
December | 2696.36 | 08-DEC-22:10 | 2263.36 | 1244.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 2625.47 | 1760.39 | 1244.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.54 | 0.00 | |
Maximum of Months | 3208.13 | 10562.33 | 9959.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.88 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3077.80 | 10-JAN-19:02 | 831.60 | 949.89 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 16.67 | 0.00 |
February | 3074.23 | 08-FEB-19:02 | 831.60 | 949.89 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 13.56 | 0.00 |
March | 3084.74 | 07-MAR-19:02 | 831.60 | 949.89 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 13.57 | 0.00 |
April | 3096.70 | 10-APR-18:02 | 831.60 | 949.89 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 23.21 | 0.00 |
May | 3122.68 | 18-MAY-18:02 | 831.60 | 949.89 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 18.94 | 0.00 |
June | 3105.91 | 29-JUN-18:02 | 831.60 | 949.89 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 18.67 | 0.00 |
July | 3102.83 | 06-JUL-18:02 | 831.60 | 949.89 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 7.27 | 0.00 |
August | 3111.89 | 30-AUG-18:02 | 831.60 | 949.89 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 7.76 | 0.00 |
September | 3109.52 | 25-SEP-18:02 | 831.60 | 949.89 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 18.59 | 0.00 |
October | 3112.97 | 03-OCT-18:02 | 831.60 | 949.89 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 17.32 | 0.00 |
November | 3101.96 | 29-NOV-19:02 | 831.60 | 949.89 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 11.81 | 0.00 |
December | 3079.63 | 18-DEC-16:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 10.96 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3074.23 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 7.27 | 0.00 | |
Maximum of Months | 3122.68 | 831.60 | 949.89 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 23.21 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3107.83 | 23-JAN-22:51 | 1260.00 | 834.17 | 626.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
February | 3115.02 | 14-FEB-19:02 | 831.60 | 949.78 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 19.94 | 0.00 |
March | 3133.00 | 07-MAR-19:02 | 831.60 | 949.78 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 13.67 | 0.00 |
April | 3128.12 | 10-APR-18:02 | 831.60 | 949.78 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 23.24 | 0.00 |
May | 3146.12 | 18-MAY-18:02 | 831.60 | 949.78 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 18.94 | 0.00 |
June | 3172.05 | 12-JUN-18:02 | 831.60 | 949.78 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 26.83 | 0.00 |
July | 3121.08 | 06-JUL-18:02 | 831.60 | 949.78 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 7.25 | 0.00 |
August | 3140.32 | 30-AUG-18:02 | 831.60 | 949.78 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 7.79 | 0.00 |
September | 3151.09 | 25-SEP-18:02 | 831.60 | 949.78 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 18.66 | 0.00 |
October | 3149.74 | 17-OCT-18:02 | 831.60 | 949.78 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 16.99 | 0.00 |
November | 3128.65 | 20-NOV-19:02 | 831.60 | 949.78 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 17.68 | 0.00 |
December | 3080.82 | 26-DEC-19:02 | 831.60 | 949.78 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 10.89 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3080.82 | 831.60 | 834.17 | 626.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3172.05 | 1260.00 | 949.78 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 26.83 | 0.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1499.32 | 12-JAN-09:02 | 216.00 | 295.21 | 665.80 | 0.00 | 0.00 | 0.00 | 0.00 | 7.82 | 0.00 |
February | 1497.05 | 15-FEB-16:02 | 583.20 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 10.80 | 0.00 |
March | 1495.56 | 07-MAR-19:02 | 831.60 | 597.13 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 6.62 | 0.00 |
April | 1493.79 | 10-APR-18:02 | 831.60 | 597.13 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 11.57 | 0.00 |
May | 1498.54 | 18-MAY-18:02 | 831.60 | 597.13 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 9.36 | 0.00 |
June | 1495.19 | 24-JUN-18:02 | 702.00 | 670.94 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2.79 | 0.00 |
July | 1494.29 | 03-JUL-18:02 | 831.60 | 597.13 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 8.05 | 0.00 |
August | 1499.65 | 21-AUG-15:02 | 583.20 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 7.84 | 0.00 |
September | 1494.11 | 11-SEP-18:02 | 831.60 | 597.13 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 7.89 | 0.00 |
October | 1502.27 | 24-OCT-18:02 | 831.60 | 597.13 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 6.36 | 0.00 |
November | 1503.38 | 22-NOV-09:02 | 216.00 | 295.21 | 665.80 | 0.00 | 0.00 | 0.00 | 0.00 | 8.28 | 0.00 |
December | 1501.61 | 02-DEC-09:02 | 324.00 | 375.72 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 6.92 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1493.79 | 216.00 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 2.79 | 0.00 | |
Maximum of Months | 1503.38 | 831.60 | 670.94 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 11.57 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 23062.44 | 03-JAN-22:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 20.62 | 0.00 |
February | 23143.55 | 15-FEB-23:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 21.43 | 0.00 |
March | 23753.93 | 28-MAR-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 28.78 | 0.00 |
April | 24189.88 | 28-APR-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 31.87 | 0.00 |
May | 24848.05 | 05-MAY-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 36.07 | 0.00 |
June | 25406.51 | 12-JUN-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 41.30 | 0.00 |
July | 24753.59 | 14-JUL-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 30.41 | 0.00 |
August | 24278.71 | 01-AUG-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 34.84 | 0.00 |
September | 23855.53 | 05-SEP-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 35.88 | 0.00 |
October | 23301.84 | 16-OCT-21:40 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 21.97 | 0.00 |
November | 23055.07 | 03-NOV-22:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 16.34 | 0.00 |
December | 23134.36 | 08-DEC-22:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 28.18 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 23055.07 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 16.34 | 0.00 | |
Maximum of Months | 25406.51 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 41.30 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 24280.22 | 03-JAN-22:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 20.62 | 0.00 |
February | 24312.60 | 27-FEB-22:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 16.61 | 0.00 |
March | 24961.08 | 28-MAR-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 28.78 | 0.00 |
April | 25417.51 | 28-APR-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 31.87 | 0.00 |
May | 26068.79 | 05-MAY-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 36.07 | 0.00 |
June | 26641.76 | 12-JUN-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 41.30 | 0.00 |
July | 26033.92 | 14-JUL-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 30.41 | 0.00 |
August | 25556.88 | 01-AUG-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 34.84 | 0.00 |
September | 25102.24 | 05-SEP-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 35.88 | 0.00 |
October | 24528.07 | 16-OCT-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 21.60 | 0.00 |
November | 24305.50 | 14-NOV-22:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 22.56 | 0.00 |
December | 24292.18 | 08-DEC-22:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 28.18 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 24280.22 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 16.61 | 0.00 | |
Maximum of Months | 26641.76 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 41.30 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 29647.17 | 04-JAN-11:50 | 533.71 | 294.67 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 57.87 | 0.00 |
February | 29830.84 | 20-FEB-11:50 | 800.57 | 353.60 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 47.36 | 0.00 |
March | 30183.94 | 19-MAR-10:50 | 800.57 | 353.60 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 62.12 | 0.00 |
April | 30437.12 | 09-APR-10:50 | 800.57 | 353.60 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 60.13 | 0.00 |
May | 30621.07 | 07-MAY-10:50 | 800.57 | 353.60 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 57.22 | 0.00 |
June | 30444.88 | 24-JUN-10:50 | 800.57 | 294.67 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 52.47 | 0.00 |
July | 29885.97 | 15-JUL-18:03 | 9606.82 | 4950.44 | 89477.13 | 89971.33 | 0.00 | 0.00 | 0.00 | 50.96 | 0.00 |
August | 30118.06 | 27-AUG-10:50 | 800.57 | 353.60 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 56.11 | 0.00 |
September | 30276.69 | 03-SEP-10:50 | 800.57 | 353.60 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 50.20 | 0.00 |
October | 30028.95 | 07-OCT-10:50 | 800.57 | 294.67 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 47.99 | 0.00 |
November | 29802.91 | 23-NOV-11:50 | 800.57 | 353.60 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 44.46 | 0.00 |
December | 29741.73 | 31-DEC-11:50 | 800.57 | 353.60 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 45.28 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 29647.17 | 533.71 | 294.67 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 44.46 | 0.00 | |
Maximum of Months | 30621.07 | 9606.82 | 4950.44 | 89477.13 | 89971.33 | 0.00 | 0.00 | 0.00 | 62.12 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6840.01 | 05-JAN-16:03 | 7984.80 | 3293.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.23 | 0.00 |
February | 6663.00 | 22-FEB-16:03 | 7984.80 | 3293.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.20 | 0.00 |
March | 6628.56 | 28-MAR-15:13 | 3992.40 | 1646.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.79 | 0.00 |
April | 6502.15 | 01-APR-14:40 | 798.48 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.43 | 0.00 |
May | 7196.40 | 06-MAY-14:30 | 798.48 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.59 | 0.00 |
June | 7406.80 | 13-JUN-15:40 | 1330.80 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.62 | 0.00 |
July | 6370.33 | 15-JUL-17:13 | 4790.88 | 3952.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.25 | 0.00 |
August | 6169.42 | 14-AUG-15:03 | 7984.80 | 3293.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.80 | 0.00 |
September | 5925.62 | 06-SEP-20:10 | 2129.28 | 1756.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.31 | 0.00 |
October | 5623.17 | 07-OCT-14:30 | 798.48 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.95 | 0.00 |
November | 6248.33 | 22-NOV-14:00 | 532.32 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.21 | 0.00 |
December | 6735.24 | 08-DEC-14:30 | 532.32 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.34 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5623.17 | 532.32 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.31 | 0.00 | |
Maximum of Months | 7406.80 | 7984.80 | 3952.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.59 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.688985E+12 | 384203.28 | 10-JAN-19:10 | 0.321673E+12 | 281422.66 | 11-JAN-18:00 |
February | 0.634273E+12 | 391481.33 | 14-FEB-19:10 | 0.289859E+12 | 281317.97 | 02-FEB-18:40 |
March | 0.718103E+12 | 393617.88 | 28-MAR-18:10 | 0.319292E+12 | 280265.55 | 01-MAR-18:00 |
April | 0.742285E+12 | 437045.34 | 10-APR-18:10 | 0.306438E+12 | 277996.83 | 04-APR-17:49 |
May | 0.805586E+12 | 443442.41 | 16-MAY-18:30 | 0.314380E+12 | 274115.01 | 01-MAY-17:00 |
June | 0.787597E+12 | 455161.34 | 13-JUN-18:19 | 0.302628E+12 | 272890.46 | 06-JUN-17:49 |
July | 0.726006E+12 | 410731.61 | 14-JUL-18:19 | 0.311921E+12 | 271840.56 | 31-JUL-17:40 |
August | 0.766529E+12 | 440789.16 | 14-AUG-18:10 | 0.312959E+12 | 273425.14 | 31-AUG-17:19 |
September | 0.733986E+12 | 426569.85 | 08-SEP-18:10 | 0.304463E+12 | 274213.21 | 29-SEP-17:49 |
October | 0.736843E+12 | 403104.95 | 16-OCT-18:10 | 0.317082E+12 | 278854.04 | 31-OCT-17:49 |
November | 0.698436E+12 | 409478.50 | 17-NOV-19:10 | 0.309242E+12 | 280333.19 | 28-NOV-18:49 |
December | 0.701735E+12 | 398987.22 | 29-DEC-19:10 | 0.321051E+12 | 281288.46 | 27-DEC-18:19 |
Annual Sum or Average | 0.874036E+13 | 0.373099E+13 | ||||
Minimum of Months | 0.634273E+12 | 384203.28 | 0.289859E+12 | 271840.56 | ||
Maximum of Months | 0.805586E+12 | 455161.34 | 0.321673E+12 | 281422.66 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.666157E+11 | 0.172936E+11 | 0.140828E+12 | 0.691143E+11 | 0.418415E+11 | 0.117818E+11 | 0.156416E+10 | 0.301084E+12 | 0.00 | 0.00 | 0.255108E+11 | 0.804813E+10 | 0.00 |
February | 0.601289E+11 | 0.153762E+11 | 0.127191E+12 | 0.624259E+11 | 0.385367E+11 | 0.106863E+11 | 0.120588E+10 | 0.283427E+12 | 0.00 | 0.00 | 0.232326E+11 | 0.727249E+10 | 0.00 |
March | 0.664572E+11 | 0.165014E+11 | 0.140882E+12 | 0.691168E+11 | 0.427165E+11 | 0.119533E+11 | 0.134460E+10 | 0.330007E+12 | 0.00 | 0.00 | 0.257713E+11 | 0.804661E+10 | 0.00 |
April | 0.642051E+11 | 0.155909E+11 | 0.136245E+12 | 0.668844E+11 | 0.417014E+11 | 0.119711E+11 | 0.116967E+10 | 0.366651E+12 | 0.00 | 0.00 | 0.249400E+11 | 0.779789E+10 | 0.00 |
May | 0.663914E+11 | 0.158352E+11 | 0.140860E+12 | 0.691155E+11 | 0.436030E+11 | 0.127768E+11 | 0.130875E+10 | 0.416582E+12 | 0.00 | 0.00 | 0.257572E+11 | 0.804798E+10 | 0.00 |
June | 0.641454E+11 | 0.151467E+11 | 0.136336E+12 | 0.668868E+11 | 0.436344E+11 | 0.124586E+11 | 0.112046E+10 | 0.410008E+12 | 0.00 | 0.00 | 0.249289E+11 | 0.778941E+10 | 0.00 |
July | 0.663642E+11 | 0.157759E+11 | 0.140770E+12 | 0.691130E+11 | 0.421932E+11 | 0.121191E+11 | 0.133638E+10 | 0.339257E+12 | 0.00 | 0.00 | 0.257406E+11 | 0.805649E+10 | 0.00 |
August | 0.663715E+11 | 0.159758E+11 | 0.140892E+12 | 0.691168E+11 | 0.415524E+11 | 0.124938E+11 | 0.157512E+10 | 0.379451E+12 | 0.00 | 0.00 | 0.257457E+11 | 0.804808E+10 | 0.00 |
September | 0.643972E+11 | 0.158574E+11 | 0.136256E+12 | 0.668846E+11 | 0.402683E+11 | 0.119918E+11 | 0.137974E+10 | 0.359089E+12 | 0.00 | 0.00 | 0.249235E+11 | 0.779936E+10 | 0.00 |
October | 0.665886E+11 | 0.168124E+11 | 0.140818E+12 | 0.691142E+11 | 0.408590E+11 | 0.122334E+11 | 0.166924E+10 | 0.349647E+12 | 0.00 | 0.00 | 0.257504E+11 | 0.804671E+10 | 0.00 |
November | 0.644575E+11 | 0.165977E+11 | 0.136330E+12 | 0.668855E+11 | 0.400289E+11 | 0.117089E+11 | 0.151980E+10 | 0.323144E+12 | 0.00 | 0.00 | 0.248591E+11 | 0.778116E+10 | 0.00 |
December | 0.666006E+11 | 0.174046E+11 | 0.140770E+12 | 0.691131E+11 | 0.413474E+11 | 0.119396E+11 | 0.161031E+10 | 0.314078E+12 | 0.00 | 0.00 | 0.255132E+11 | 0.805661E+10 | 0.00 |
Annual Sum or Average | 0.782723E+12 | 0.194168E+12 | 0.165818E+13 | 0.813771E+12 | 0.498283E+12 | 0.144114E+12 | 0.168041E+11 | 0.417243E+13 | 0.00 | 0.00 | 0.302673E+12 | 0.947909E+11 | 0.00 |
Minimum of Months | 0.601289E+11 | 0.151467E+11 | 0.127191E+12 | 0.624259E+11 | 0.385367E+11 | 0.106863E+11 | 0.112046E+10 | 0.283427E+12 | 0.00 | 0.00 | 0.232326E+11 | 0.727249E+10 | 0.00 |
Maximum of Months | 0.666157E+11 | 0.174046E+11 | 0.140892E+12 | 0.691168E+11 | 0.436344E+11 | 0.127768E+11 | 0.166924E+10 | 0.416582E+12 | 0.00 | 0.00 | 0.257713E+11 | 0.805661E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.151918E+12 | 0.00 | 0.00 | 0.00 | 0.169755E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.00 | 0.00 | 0.152655E+12 | 0.00 | 0.00 |
March | 0.152024E+12 | 0.00 | 0.00 | 0.00 | 0.167268E+12 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.00 | 0.00 | 0.159483E+12 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.00 | 0.00 | 0.162401E+12 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 0.00 | 0.00 | 0.155514E+12 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 0.00 | 0.00 | 0.160101E+12 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 0.00 | 0.00 | 0.160921E+12 | 0.00 | 0.00 |
September | 0.146971E+12 | 0.00 | 0.00 | 0.00 | 0.157492E+12 | 0.00 | 0.00 |
October | 0.151903E+12 | 0.00 | 0.00 | 0.00 | 0.165179E+12 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.00 | 0.00 | 0.162151E+12 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.00 | 0.00 | 0.169231E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178884E+13 | 0.00 | 0.00 | 0.00 | 0.194215E+13 | 0.00 | 0.00 |
Minimum of Months | 0.137204E+12 | 0.00 | 0.00 | 0.00 | 0.152655E+12 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.00 | 0.00 | 0.169755E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 64632.59 | 02-JAN-20:10 | 12338.45 | 01-JAN-00:10 | 89171.45 | 02-JAN-07:10 | 49605.57 | 02-JAN-07:19 | 24037.52 | 05-JAN-21:10 | 4913.40 | 10-JAN-19:10 | 5088.09 | 01-JAN-16:10 |
February | 64632.59 | 01-FEB-20:10 | 12338.45 | 01-FEB-00:10 | 89171.45 | 01-FEB-07:10 | 49605.38 | 06-FEB-07:19 | 23977.72 | 22-FEB-21:10 | 4963.85 | 14-FEB-19:19 | 4591.63 | 11-FEB-05:00 |
March | 64632.59 | 01-MAR-20:10 | 12338.45 | 01-MAR-00:10 | 89171.45 | 01-MAR-07:10 | 49607.07 | 13-MAR-06:19 | 24255.20 | 29-MAR-20:10 | 5185.49 | 14-MAR-21:40 | 5395.27 | 04-MAR-05:00 |
April | 64632.59 | 03-APR-19:10 | 12338.45 | 01-APR-00:10 | 89171.45 | 03-APR-06:10 | 49606.78 | 21-APR-06:19 | 24973.40 | 27-APR-20:10 | 5461.86 | 10-APR-18:19 | 5295.46 | 10-APR-03:00 |
May | 64632.59 | 01-MAY-19:10 | 12338.45 | 01-MAY-00:10 | 89171.45 | 01-MAY-06:10 | 49606.38 | 09-MAY-06:19 | 26968.56 | 05-MAY-18:30 | 5754.05 | 31-MAY-20:19 | 5106.23 | 26-MAY-03:00 |
June | 64632.59 | 01-JUN-19:10 | 12338.45 | 01-JUN-00:10 | 89171.45 | 01-JUN-06:10 | 49606.78 | 20-JUN-06:19 | 28792.11 | 13-JUN-18:19 | 5673.63 | 13-JUN-18:10 | 4723.28 | 05-JUN-03:00 |
July | 64632.59 | 03-JUL-19:10 | 12338.45 | 01-JUL-00:10 | 89171.45 | 03-JUL-06:10 | 49606.78 | 11-JUL-06:19 | 25526.44 | 14-JUL-20:10 | 5580.08 | 17-JUL-18:49 | 5204.45 | 01-JUL-04:00 |
August | 64632.59 | 01-AUG-19:10 | 12338.45 | 01-AUG-00:10 | 89171.45 | 01-AUG-06:10 | 49606.78 | 21-AUG-06:19 | 24857.18 | 14-AUG-20:10 | 5574.39 | 14-AUG-19:00 | 5806.54 | 21-AUG-03:00 |
September | 64632.59 | 01-SEP-19:10 | 12338.45 | 01-SEP-00:10 | 89171.45 | 01-SEP-06:10 | 49606.78 | 21-SEP-06:19 | 24293.50 | 13-SEP-20:10 | 5309.24 | 08-SEP-18:19 | 5758.67 | 16-SEP-04:00 |
October | 64632.59 | 02-OCT-19:10 | 12338.45 | 01-OCT-00:10 | 89171.45 | 02-OCT-06:10 | 49607.07 | 23-OCT-06:19 | 23476.21 | 04-OCT-20:10 | 5117.08 | 17-OCT-18:10 | 5851.03 | 23-OCT-03:00 |
November | 64632.59 | 01-NOV-19:10 | 12338.45 | 01-NOV-00:10 | 89171.45 | 01-NOV-06:10 | 49606.67 | 03-NOV-06:19 | 23157.00 | 21-NOV-21:10 | 5298.32 | 30-NOV-22:00 | 5410.49 | 27-NOV-04:00 |
December | 64632.59 | 01-DEC-20:10 | 12338.45 | 01-DEC-00:10 | 89171.45 | 01-DEC-07:10 | 49605.18 | 11-DEC-07:19 | 23767.76 | 08-DEC-21:10 | 5150.83 | 21-DEC-21:00 | 5061.49 | 18-DEC-04:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 64632.59 | 12338.45 | 89171.45 | 49605.18 | 23157.00 | 4913.40 | 4591.63 | |||||||
Maximum of Months | 64632.59 | 12338.45 | 89171.45 | 49607.07 | 28792.11 | 5754.05 | 5851.03 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 170460.04 | 04-JAN-16:19 | 0.00 | 0.00 | 9938.94 | 07-JAN-09:20 | 4751.13 | 05-JAN-19:00 | 0.00 |
February | 187928.80 | 13-FEB-16:19 | 0.00 | 0.00 | 9938.94 | 01-FEB-09:20 | 4751.13 | 08-FEB-19:30 | 0.00 |
March | 188896.76 | 28-MAR-15:20 | 0.00 | 0.00 | 9938.94 | 01-MAR-00:20 | 4751.13 | 27-MAR-18:30 | 0.00 |
April | 216994.52 | 10-APR-18:10 | 0.00 | 0.00 | 9938.94 | 01-APR-00:10 | 4751.13 | 20-APR-18:40 | 0.00 |
May | 230439.03 | 06-MAY-15:20 | 0.00 | 0.00 | 9938.94 | 01-MAY-00:10 | 4751.13 | 25-MAY-18:00 | 0.00 |
June | 249536.43 | 13-JUN-15:20 | 0.00 | 0.00 | 9938.94 | 01-JUN-00:10 | 4751.13 | 09-JUN-06:49 | 0.00 |
July | 192330.12 | 20-JUL-15:20 | 0.00 | 0.00 | 9938.94 | 01-JUL-00:10 | 4751.12 | 26-JUL-18:30 | 0.00 |
August | 220903.67 | 08-AUG-18:10 | 0.00 | 0.00 | 9938.94 | 01-AUG-00:10 | 4751.13 | 16-AUG-18:40 | 0.00 |
September | 204336.10 | 08-SEP-18:10 | 0.00 | 0.00 | 9938.94 | 01-SEP-00:10 | 4751.13 | 05-SEP-18:49 | 0.00 |
October | 198502.19 | 16-OCT-15:20 | 0.00 | 0.00 | 9938.94 | 01-OCT-00:10 | 4751.13 | 05-OCT-18:49 | 0.00 |
November | 190430.24 | 17-NOV-19:10 | 0.00 | 0.00 | 9938.94 | 01-NOV-00:10 | 4751.13 | 02-NOV-06:40 | 0.00 |
December | 179810.17 | 29-DEC-19:10 | 0.00 | 0.00 | 9938.94 | 15-DEC-09:09 | 4751.13 | 15-DEC-19:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 170460.04 | 0.00 | 0.00 | 9938.94 | 4751.12 | 0.00 | |||
Maximum of Months | 249536.43 | 0.00 | 0.00 | 9938.94 | 4751.13 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 384203.28 | 10-JAN-19:10 | 57474.69 | 77573.37 | 12338.45 | 28159.60 | 21283.63 | 4913.40 | 2.11 | 165913.55 | 0.00 |
February | 391481.33 | 14-FEB-19:10 | 57474.69 | 77573.37 | 12338.45 | 28159.60 | 22219.38 | 4933.29 | 924.86 | 171314.75 | 0.00 |
March | 393617.88 | 28-MAR-18:10 | 57474.69 | 77573.37 | 12338.45 | 28159.21 | 23225.40 | 4945.44 | 2493.57 | 170865.09 | 0.00 |
April | 437045.34 | 10-APR-18:10 | 57474.69 | 77573.37 | 12338.45 | 28159.31 | 21963.15 | 5438.85 | 0.00 | 216994.52 | 0.00 |
May | 443442.41 | 16-MAY-18:30 | 57474.69 | 77573.37 | 12338.45 | 28169.74 | 21928.80 | 5568.67 | 0.00 | 223842.66 | 0.00 |
June | 455161.34 | 13-JUN-18:19 | 57474.69 | 77573.37 | 12338.45 | 28169.09 | 28792.11 | 5604.90 | 0.00 | 228669.44 | 0.00 |
July | 410731.61 | 14-JUL-18:19 | 57474.69 | 77573.37 | 12338.45 | 28169.09 | 25419.61 | 5058.54 | 0.00 | 188158.09 | 0.00 |
August | 440789.16 | 14-AUG-18:10 | 57474.69 | 77573.37 | 12338.45 | 28158.62 | 23774.48 | 5483.12 | 0.00 | 218881.61 | 0.00 |
September | 426569.85 | 08-SEP-18:10 | 57474.69 | 77573.37 | 12338.45 | 28159.60 | 22589.61 | 5253.01 | 2303.23 | 204336.10 | 0.00 |
October | 403104.95 | 16-OCT-18:10 | 57474.69 | 77573.37 | 12338.45 | 28159.60 | 22584.93 | 5075.37 | 1.56 | 182793.70 | 0.00 |
November | 409478.50 | 17-NOV-19:10 | 57474.69 | 77573.37 | 12338.45 | 28159.60 | 21918.11 | 5042.03 | 0.00 | 190430.24 | 0.00 |
December | 398987.22 | 29-DEC-19:10 | 57474.69 | 77573.37 | 12338.45 | 28159.60 | 22133.01 | 4955.36 | 0.00 | 179810.17 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 384203.28 | 57474.69 | 77573.37 | 12338.45 | 28158.62 | 21283.63 | 4913.40 | 0.00 | 165913.55 | 0.00 | |
Maximum of Months | 455161.34 | 57474.69 | 77573.37 | 12338.45 | 28169.74 | 28792.11 | 5604.90 | 2493.57 | 228669.44 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 0.00 | 0.00 | 179827.61 | 12-JAN-21:30 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 0.00 | 0.00 | 179719.12 | 01-FEB-21:49 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 0.00 | 0.00 | 176286.69 | 01-MAR-21:00 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 0.00 | 0.00 | 174629.64 | 04-APR-20:00 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 0.00 | 0.00 | 172422.58 | 02-MAY-20:40 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 0.00 | 0.00 | 171023.08 | 08-JUN-20:40 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 0.00 | 0.00 | 169868.54 | 19-JUL-20:40 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 0.00 | 0.00 | 171721.58 | 30-AUG-20:00 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 0.00 | 0.00 | 172550.00 | 29-SEP-20:00 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 0.00 | 0.00 | 174903.91 | 30-OCT-20:19 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 0.00 | 0.00 | 177662.82 | 29-NOV-21:40 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 0.00 | 0.00 | 179075.12 | 21-DEC-21:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 104248.32 | 0.00 | 0.00 | 0.00 | 169868.54 | 0.00 | ||
Maximum of Months | 104248.32 | 0.00 | 0.00 | 0.00 | 179827.61 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.77 | 1.17 | 21.77 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 21.78 | 2.00 | 21.78 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 21.71 | 2.50 | 21.71 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.69 | 1.17 | 21.69 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.77 | 0.33 | 21.77 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.70 | 0.67 | 21.70 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.68 | 0.33 | 21.68 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.69 | 1.00 | 21.69 |
Annual Sum or Average | 0.00 | 0.00 | 9.17 | 21.73 | 9.17 | 21.73 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 21.78 | 2.50 | 21.78 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.69 | 0.33 | 21.69 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.73 | 0.50 | 21.73 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.69 | 0.33 | 21.69 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.68 | 0.50 | 21.68 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.73 | 1.33 | 21.73 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 21.76 | 2.17 | 21.76 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.79 | 0.50 | 21.79 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.73 | 0.17 | 21.73 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.70 | 0.17 | 21.70 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.67 | 0.17 | 21.67 |
Annual Sum or Average | 0.00 | 0.00 | 6.17 | 21.73 | 6.17 | 21.73 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 21.79 | 2.17 | 21.79 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.76 | 0.33 | 21.76 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.78 | 0.33 | 21.78 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 21.70 | 2.83 | 21.70 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 22.01 | 0.50 | 22.01 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.78 | 0.33 | 21.78 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.71 | 0.50 | 21.71 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.87 | 0.67 | 21.87 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.79 | 0.67 | 21.79 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.75 | 0.50 | 21.75 |
Annual Sum or Average | 0.00 | 0.00 | 6.67 | 21.77 | 6.67 | 21.77 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 22.01 | 2.83 | 22.01 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.67 | 0.17 | 21.67 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.69 | 0.50 | 21.69 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.67 | 0.33 | 21.67 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.71 | 0.33 | 21.71 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.33 | 21.69 | 1.33 | 21.69 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.71 | 0.50 | 21.71 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 22.01 | 2.17 | 22.01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 22.10 | 1.33 | 22.10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.74 | 0.17 | 21.74 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.74 | 0.83 | 21.74 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.71 | 1.83 | 21.71 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.87 | 0.67 | 21.87 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.72 | 0.17 | 21.72 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.67 | 0.17 | 21.67 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.78 | 0.50 | 21.78 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.82 | 0.67 | 21.82 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.96 | 1.50 | 21.96 |
Annual Sum or Average | 0.00 | 0.00 | 10.00 | 21.89 | 10.00 | 21.89 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 22.10 | 2.17 | 22.10 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 21.79 | 3.50 | 21.79 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 21.79 | 3.67 | 21.79 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 21.86 | 4.50 | 21.86 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 21.86 | 3.67 | 21.86 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 21.82 | 2.17 | 21.82 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 21.82 | 2.50 | 21.82 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.77 | 0.50 | 21.77 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.71 | 1.83 | 21.71 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.79 | 1.67 | 21.79 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.78 | 1.00 | 21.78 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.80 | 1.17 | 21.80 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 21.79 | 2.50 | 21.79 |
Annual Sum or Average | 0.00 | 0.00 | 28.67 | 21.81 | 28.67 | 21.81 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.71 | 0.50 | 21.71 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 21.86 | 4.50 | 21.86 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.74 | 1.50 | 21.74 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 21.79 | 2.33 | 21.79 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 21.81 | 4.33 | 21.81 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 21.86 | 3.67 | 21.86 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 21.82 | 2.50 | 21.82 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 21.82 | 3.00 | 21.82 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.79 | 1.67 | 21.79 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 21.73 | 2.17 | 21.73 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.77 | 1.33 | 21.77 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.73 | 0.67 | 21.73 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.70 | 0.67 | 21.70 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.69 | 0.50 | 21.69 |
Annual Sum or Average | 0.00 | 0.00 | 24.33 | 21.80 | 24.33 | 21.80 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.69 | 0.50 | 21.69 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 21.86 | 4.33 | 21.86 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 21.92 | 8.17 | 21.92 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 21.91 | 5.83 | 21.91 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 21.87 | 6.33 | 21.87 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 21.76 | 3.67 | 21.76 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 21.76 | 2.67 | 21.76 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 21.75 | 2.50 | 21.75 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.68 | 0.50 | 21.68 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.69 | 0.83 | 21.69 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 21.73 | 2.83 | 21.73 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 21.82 | 3.50 | 21.82 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 21.85 | 4.17 | 21.85 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 21.93 | 6.83 | 21.93 |
Annual Sum or Average | 0.00 | 0.00 | 47.83 | 21.85 | 47.83 | 21.85 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.68 | 0.50 | 21.68 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 21.93 | 8.17 | 21.93 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 614.00 | 23.03 | 0.00 | 23.03 | 0.00 | 23.03 |
February | 476.50 | 23.11 | 0.00 | 23.11 | 0.00 | 23.11 |
March | 623.67 | 23.06 | 0.00 | 23.06 | 0.00 | 23.06 |
April | 580.67 | 23.07 | 0.00 | 23.07 | 0.00 | 23.07 |
May | 455.17 | 23.11 | 0.17 | 23.11 | 0.00 | 23.11 |
June | 253.00 | 23.16 | 23.50 | 23.22 | 0.00 | 23.22 |
July | 366.33 | 23.13 | 0.00 | 23.13 | 0.00 | 23.13 |
August | 476.00 | 23.06 | 0.17 | 23.06 | 0.00 | 23.06 |
September | 461.17 | 23.07 | 0.00 | 23.07 | 0.00 | 23.07 |
October | 655.17 | 23.01 | 0.00 | 23.01 | 0.00 | 23.01 |
November | 564.17 | 23.06 | 0.00 | 23.06 | 0.00 | 23.06 |
December | 569.67 | 23.07 | 0.00 | 23.07 | 0.00 | 23.07 |
Annual Sum or Average | 6095.50 | 23.07 | 23.83 | 23.07 | 0.00 | 23.07 |
Minimum of Months | 253.00 | 23.01 | 0.00 | 23.01 | 0.00 | 23.01 |
Maximum of Months | 655.17 | 23.16 | 23.50 | 23.22 | 0.00 | 23.22 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 136.17 | 22.50 | 512.50 | 23.59 | 0.00 | 23.59 |
February | 52.00 | 22.68 | 516.33 | 23.77 | 0.00 | 23.77 |
March | 56.50 | 22.57 | 544.50 | 23.73 | 0.00 | 23.73 |
April | 67.83 | 22.37 | 522.83 | 23.61 | 0.00 | 23.61 |
May | 132.50 | 22.41 | 506.17 | 23.49 | 0.00 | 23.49 |
June | 86.67 | 22.57 | 537.50 | 23.60 | 0.00 | 23.60 |
July | 170.17 | 22.51 | 390.00 | 23.33 | 0.00 | 23.33 |
August | 236.00 | 22.27 | 345.83 | 23.13 | 0.00 | 23.13 |
September | 162.17 | 22.35 | 407.50 | 23.37 | 0.00 | 23.37 |
October | 217.83 | 22.31 | 391.83 | 23.26 | 0.00 | 23.26 |
November | 135.33 | 22.41 | 464.17 | 23.51 | 0.00 | 23.51 |
December | 146.83 | 22.46 | 486.50 | 23.55 | 0.00 | 23.55 |
Annual Sum or Average | 1600.00 | 22.41 | 5625.67 | 23.50 | 0.00 | 23.50 |
Minimum of Months | 52.00 | 22.27 | 345.83 | 23.13 | 0.00 | 23.13 |
Maximum of Months | 236.00 | 22.68 | 544.50 | 23.77 | 0.00 | 23.77 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 390.17 | 22.64 | 157.83 | 22.97 | 0.00 | 22.97 |
February | 222.83 | 22.79 | 214.67 | 23.28 | 0.00 | 23.28 |
March | 243.00 | 22.74 | 273.83 | 23.30 | 0.00 | 23.30 |
April | 222.17 | 22.70 | 284.83 | 23.31 | 0.00 | 23.31 |
May | 261.50 | 22.64 | 262.50 | 23.21 | 0.00 | 23.21 |
June | 179.67 | 22.69 | 312.00 | 23.40 | 0.00 | 23.40 |
July | 350.17 | 22.66 | 173.50 | 23.03 | 0.00 | 23.03 |
August | 386.17 | 22.50 | 175.33 | 22.90 | 0.00 | 22.90 |
September | 342.50 | 22.58 | 176.83 | 22.99 | 0.00 | 22.99 |
October | 454.00 | 22.54 | 108.17 | 22.77 | 0.00 | 22.77 |
November | 393.67 | 22.62 | 122.17 | 22.90 | 0.00 | 22.90 |
December | 419.00 | 22.65 | 130.00 | 22.91 | 0.00 | 22.91 |
Annual Sum or Average | 3864.83 | 22.63 | 2391.67 | 23.07 | 0.00 | 23.07 |
Minimum of Months | 179.67 | 22.50 | 108.17 | 22.77 | 0.00 | 22.77 |
Maximum of Months | 454.00 | 22.79 | 312.00 | 23.40 | 0.00 | 23.40 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 662.33 | 22.85 | 0.00 | 22.85 | 0.00 | 22.85 |
February | 472.17 | 23.04 | 0.00 | 23.04 | 0.00 | 23.04 |
March | 432.00 | 23.03 | 36.00 | 23.10 | 0.00 | 23.10 |
April | 194.33 | 23.06 | 135.83 | 23.43 | 0.00 | 23.43 |
May | 137.67 | 23.02 | 352.33 | 23.69 | 0.00 | 23.69 |
June | 33.00 | 23.18 | 495.00 | 23.92 | 0.00 | 23.92 |
July | 114.33 | 23.10 | 222.33 | 23.67 | 0.00 | 23.67 |
August | 354.33 | 22.85 | 117.33 | 23.12 | 0.00 | 23.12 |
September | 378.83 | 22.91 | 54.83 | 23.04 | 0.00 | 23.04 |
October | 617.00 | 22.83 | 0.83 | 22.83 | 0.00 | 22.83 |
November | 609.67 | 22.91 | 0.00 | 22.91 | 0.00 | 22.91 |
December | 678.33 | 22.83 | 0.00 | 22.83 | 0.00 | 22.83 |
Annual Sum or Average | 4684.00 | 22.91 | 1414.50 | 23.16 | 0.00 | 23.16 |
Minimum of Months | 33.00 | 22.83 | 0.00 | 22.83 | 0.00 | 22.83 |
Maximum of Months | 678.33 | 23.18 | 495.00 | 23.92 | 0.00 | 23.92 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 728.00 | 22.85 | 0.00 | 22.85 | 0.00 | 22.85 |
February | 577.67 | 23.07 | 0.00 | 23.07 | 0.00 | 23.07 |
March | 540.17 | 23.05 | 0.00 | 23.05 | 0.00 | 23.05 |
April | 296.00 | 23.11 | 51.67 | 23.24 | 0.00 | 23.24 |
May | 176.00 | 23.05 | 260.17 | 23.59 | 0.00 | 23.59 |
June | 50.33 | 23.19 | 441.50 | 23.89 | 0.00 | 23.89 |
July | 176.17 | 23.15 | 122.00 | 23.48 | 0.00 | 23.48 |
August | 434.17 | 22.88 | 70.67 | 23.03 | 0.00 | 23.03 |
September | 480.00 | 22.95 | 6.50 | 22.96 | 0.00 | 22.96 |
October | 687.50 | 22.83 | 0.00 | 22.83 | 0.00 | 22.83 |
November | 681.67 | 22.90 | 0.00 | 22.90 | 0.00 | 22.90 |
December | 737.17 | 22.82 | 0.00 | 22.82 | 0.00 | 22.82 |
Annual Sum or Average | 5564.83 | 22.93 | 952.50 | 23.08 | 0.00 | 23.08 |
Minimum of Months | 50.33 | 22.82 | 0.00 | 22.82 | 0.00 | 22.82 |
Maximum of Months | 737.17 | 23.19 | 441.50 | 23.89 | 0.00 | 23.89 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 152.00 | 23.96 | 678.67 | 22.50 | 152.00 | 22.73 |
February | 143.17 | 23.94 | 643.17 | 22.51 | 143.17 | 22.73 |
March | 166.67 | 23.92 | 715.00 | 22.53 | 166.67 | 22.75 |
April | 170.17 | 23.90 | 701.83 | 22.55 | 170.17 | 22.77 |
May | 170.33 | 23.91 | 702.00 | 22.56 | 170.33 | 22.78 |
June | 173.50 | 23.89 | 703.00 | 22.57 | 173.50 | 22.78 |
July | 160.00 | 23.94 | 710.33 | 22.48 | 160.00 | 22.71 |
August | 163.83 | 23.86 | 679.00 | 22.51 | 159.33 | 22.74 |
September | 157.83 | 23.91 | 673.00 | 22.51 | 156.50 | 22.73 |
October | 151.67 | 23.93 | 651.83 | 22.51 | 149.83 | 22.74 |
November | 145.83 | 23.97 | 656.50 | 22.50 | 145.83 | 22.73 |
December | 150.33 | 23.97 | 673.33 | 22.49 | 150.33 | 22.72 |
Annual Sum or Average | 1905.33 | 23.92 | 8187.67 | 22.52 | 1897.67 | 22.74 |
Minimum of Months | 143.17 | 23.86 | 643.17 | 22.48 | 143.17 | 22.71 |
Maximum of Months | 173.50 | 23.97 | 715.00 | 22.57 | 173.50 | 22.78 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 11.33 | 22.23 | 702.00 | 23.78 | 0.33 | 23.78 |
February | 0.00 | 0.00 | 667.00 | 23.81 | 0.00 | 23.81 |
March | 10.83 | 22.38 | 674.50 | 23.72 | 1.17 | 23.72 |
April | 17.00 | 22.48 | 601.33 | 23.63 | 2.33 | 23.63 |
May | 73.67 | 22.62 | 619.83 | 23.56 | 21.17 | 23.57 |
June | 43.00 | 23.05 | 612.33 | 23.62 | 20.67 | 23.63 |
July | 77.50 | 22.27 | 540.83 | 23.49 | 3.50 | 23.49 |
August | 140.00 | 22.41 | 492.00 | 23.39 | 20.33 | 23.41 |
September | 77.83 | 22.58 | 561.67 | 23.51 | 16.17 | 23.52 |
October | 81.00 | 22.41 | 595.33 | 23.50 | 11.67 | 23.51 |
November | 21.67 | 22.38 | 660.83 | 23.69 | 2.83 | 23.69 |
December | 19.00 | 22.66 | 701.33 | 23.76 | 4.17 | 23.76 |
Annual Sum or Average | 572.83 | 22.50 | 7429.00 | 23.63 | 104.33 | 23.63 |
Minimum of Months | 0.00 | 0.00 | 492.00 | 23.39 | 0.00 | 23.41 |
Maximum of Months | 140.00 | 23.05 | 702.00 | 23.81 | 21.17 | 23.81 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 101.17 | 22.59 | 382.00 | 23.51 | 0.00 | 23.51 |
February | 18.00 | 22.70 | 417.17 | 23.72 | 0.00 | 23.72 |
March | 109.00 | 22.66 | 423.33 | 23.56 | 0.00 | 23.56 |
April | 109.83 | 22.64 | 423.83 | 23.55 | 0.00 | 23.55 |
May | 87.50 | 22.53 | 486.33 | 23.59 | 0.00 | 23.59 |
June | 45.33 | 22.65 | 525.17 | 23.71 | 0.00 | 23.71 |
July | 136.50 | 22.62 | 435.17 | 23.51 | 0.00 | 23.51 |
August | 210.33 | 22.51 | 370.33 | 23.31 | 0.00 | 23.31 |
September | 173.83 | 22.56 | 370.17 | 23.37 | 0.00 | 23.37 |
October | 216.83 | 22.51 | 328.50 | 23.24 | 0.00 | 23.24 |
November | 123.67 | 22.58 | 372.33 | 23.44 | 0.00 | 23.44 |
December | 101.67 | 22.59 | 384.33 | 23.48 | 0.00 | 23.48 |
Annual Sum or Average | 1433.67 | 22.57 | 4918.67 | 23.50 | 0.00 | 23.50 |
Minimum of Months | 18.00 | 22.51 | 328.50 | 23.24 | 0.00 | 23.24 |
Maximum of Months | 216.83 | 22.70 | 525.17 | 23.72 | 0.00 | 23.72 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 644.17 | 21.50 | 0.00 | 21.50 | 0.00 | 21.50 |
February | 568.00 | 21.46 | 0.00 | 21.46 | 0.00 | 21.46 |
March | 637.83 | 21.48 | 0.00 | 21.48 | 0.00 | 21.48 |
April | 616.33 | 21.48 | 0.00 | 21.48 | 0.00 | 21.48 |
May | 636.67 | 21.48 | 0.00 | 21.48 | 0.00 | 21.48 |
June | 610.33 | 21.46 | 0.17 | 21.46 | 0.00 | 21.46 |
July | 660.33 | 21.54 | 0.00 | 21.54 | 0.00 | 21.54 |
August | 658.50 | 21.53 | 0.17 | 21.53 | 0.17 | 21.53 |
September | 630.33 | 21.51 | 0.00 | 21.51 | 0.00 | 21.51 |
October | 664.50 | 21.55 | 0.33 | 21.55 | 0.33 | 21.55 |
November | 626.17 | 21.50 | 0.00 | 21.50 | 0.00 | 21.50 |
December | 647.33 | 21.51 | 0.00 | 21.51 | 0.00 | 21.51 |
Annual Sum or Average | 7600.50 | 21.50 | 0.67 | 21.50 | 0.50 | 21.50 |
Minimum of Months | 568.00 | 21.46 | 0.00 | 21.46 | 0.00 | 21.46 |
Maximum of Months | 664.50 | 21.55 | 0.33 | 21.55 | 0.33 | 21.55 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 657.83 | 21.69 | 11.67 | 21.74 | 9.50 | 21.77 |
February | 576.00 | 21.62 | 5.33 | 21.64 | 1.17 | 21.65 |
March | 646.33 | 21.52 | 0.83 | 21.52 | 0.83 | 21.53 |
April | 613.83 | 21.48 | 0.50 | 21.48 | 0.00 | 21.48 |
May | 623.67 | 21.45 | 2.50 | 21.47 | 0.17 | 21.47 |
June | 589.33 | 21.43 | 6.83 | 21.46 | 2.00 | 21.47 |
July | 647.17 | 21.54 | 4.00 | 21.56 | 2.33 | 21.57 |
August | 654.83 | 21.55 | 5.50 | 21.56 | 5.17 | 21.58 |
September | 631.33 | 21.55 | 6.50 | 21.57 | 6.33 | 21.60 |
October | 672.33 | 21.61 | 8.00 | 21.64 | 6.83 | 21.66 |
November | 637.50 | 21.65 | 11.67 | 21.69 | 8.67 | 21.72 |
December | 659.00 | 21.71 | 12.00 | 21.75 | 10.83 | 21.79 |
Annual Sum or Average | 7609.17 | 21.57 | 75.33 | 21.59 | 53.83 | 21.61 |
Minimum of Months | 576.00 | 21.43 | 0.50 | 21.46 | 0.00 | 21.47 |
Maximum of Months | 672.33 | 21.71 | 12.00 | 21.75 | 10.83 | 21.79 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 743.83 | 21.82 | 3.50 | 21.83 | 3.50 | 21.84 |
February | 671.83 | 21.81 | 0.00 | 21.81 | 0.00 | 21.81 |
March | 744.00 | 21.71 | 0.00 | 21.71 | 0.00 | 21.71 |
April | 720.00 | 21.71 | 0.00 | 21.71 | 0.00 | 21.71 |
May | 744.00 | 21.73 | 0.00 | 21.73 | 0.00 | 21.73 |
June | 719.83 | 21.76 | 2.00 | 21.76 | 2.00 | 21.77 |
July | 743.33 | 21.74 | 2.33 | 21.75 | 2.33 | 21.76 |
August | 744.00 | 21.72 | 5.50 | 21.73 | 5.50 | 21.75 |
September | 720.00 | 21.73 | 7.33 | 21.74 | 7.33 | 21.76 |
October | 743.67 | 21.73 | 6.67 | 21.75 | 6.67 | 21.76 |
November | 717.83 | 21.79 | 4.67 | 21.80 | 4.67 | 21.81 |
December | 744.00 | 21.84 | 8.83 | 21.86 | 8.83 | 21.88 |
Annual Sum or Average | 8756.33 | 21.76 | 40.83 | 21.77 | 40.83 | 21.77 |
Minimum of Months | 671.83 | 21.71 | 0.00 | 21.71 | 0.00 | 21.71 |
Maximum of Months | 744.00 | 21.84 | 8.83 | 21.86 | 8.83 | 21.88 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 621.83 | 21.44 | 0.00 | 21.44 | 0.00 | 21.44 |
February | 540.50 | 21.37 | 0.00 | 21.37 | 0.00 | 21.37 |
March | 603.83 | 21.39 | 0.00 | 21.39 | 0.00 | 21.39 |
April | 579.67 | 21.37 | 0.00 | 21.37 | 0.00 | 21.37 |
May | 615.17 | 21.42 | 0.00 | 21.42 | 0.00 | 21.42 |
June | 578.50 | 21.37 | 0.00 | 21.37 | 0.00 | 21.37 |
July | 668.33 | 21.57 | 0.00 | 21.57 | 0.00 | 21.57 |
August | 649.00 | 21.51 | 0.17 | 21.51 | 0.17 | 21.51 |
September | 621.67 | 21.50 | 0.00 | 21.50 | 0.00 | 21.50 |
October | 658.50 | 21.54 | 0.33 | 21.54 | 0.33 | 21.54 |
November | 617.67 | 21.49 | 0.00 | 21.49 | 0.00 | 21.49 |
December | 633.00 | 21.47 | 0.00 | 21.47 | 0.00 | 21.47 |
Annual Sum or Average | 7387.67 | 21.46 | 0.50 | 21.46 | 0.50 | 21.46 |
Minimum of Months | 540.50 | 21.37 | 0.00 | 21.37 | 0.00 | 21.37 |
Maximum of Months | 668.33 | 21.57 | 0.33 | 21.57 | 0.33 | 21.57 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 642.33 | 21.70 | 29.33 | 21.82 | 10.83 | 21.87 |
February | 535.17 | 21.51 | 20.17 | 21.63 | 2.17 | 21.65 |
March | 621.67 | 21.46 | 1.17 | 21.47 | 0.33 | 21.47 |
April | 574.67 | 21.36 | 0.17 | 21.36 | 0.00 | 21.36 |
May | 599.33 | 21.38 | 2.17 | 21.39 | 0.00 | 21.39 |
June | 554.83 | 21.32 | 4.33 | 21.34 | 1.83 | 21.35 |
July | 640.17 | 21.53 | 4.67 | 21.55 | 2.33 | 21.56 |
August | 642.33 | 21.52 | 5.33 | 21.54 | 5.17 | 21.55 |
September | 624.33 | 21.54 | 6.50 | 21.56 | 6.33 | 21.58 |
October | 675.67 | 21.63 | 8.50 | 21.66 | 6.83 | 21.68 |
November | 642.67 | 21.68 | 14.50 | 21.73 | 8.33 | 21.76 |
December | 658.67 | 21.75 | 29.67 | 21.86 | 11.67 | 21.91 |
Annual Sum or Average | 7411.83 | 21.54 | 126.50 | 21.58 | 55.83 | 21.60 |
Minimum of Months | 535.17 | 21.32 | 0.17 | 21.34 | 0.00 | 21.35 |
Maximum of Months | 675.67 | 21.75 | 29.67 | 21.86 | 11.67 | 21.91 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 736.00 | 23.08 | 0.00 | 23.08 | 0.00 | 23.08 |
February | 623.83 | 23.27 | 0.00 | 23.27 | 0.00 | 23.27 |
March | 734.00 | 23.18 | 0.00 | 23.18 | 0.00 | 23.18 |
April | 707.83 | 23.16 | 0.00 | 23.16 | 0.00 | 23.16 |
May | 597.50 | 23.17 | 0.00 | 23.17 | 0.00 | 23.17 |
June | 391.67 | 23.23 | 36.83 | 23.30 | 0.00 | 23.30 |
July | 744.00 | 23.03 | 0.00 | 23.03 | 0.00 | 23.03 |
August | 743.83 | 22.89 | 0.00 | 22.89 | 0.00 | 22.89 |
September | 720.00 | 22.89 | 0.00 | 22.89 | 0.00 | 22.89 |
October | 744.00 | 22.87 | 0.00 | 22.87 | 0.00 | 22.87 |
November | 713.67 | 23.02 | 0.00 | 23.02 | 0.00 | 23.02 |
December | 733.00 | 23.04 | 0.00 | 23.04 | 0.00 | 23.04 |
Annual Sum or Average | 8189.33 | 23.06 | 36.83 | 23.06 | 0.00 | 23.06 |
Minimum of Months | 391.67 | 22.87 | 0.00 | 22.87 | 0.00 | 22.87 |
Maximum of Months | 744.00 | 23.27 | 36.83 | 23.30 | 0.00 | 23.30 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 596.33 | 21.35 | 38.00 | 21.47 | 0.00 | 21.47 |
February | 530.17 | 21.33 | 47.33 | 21.49 | 0.00 | 21.49 |
March | 590.67 | 21.34 | 44.17 | 21.48 | 0.00 | 21.48 |
April | 569.00 | 21.34 | 30.50 | 21.44 | 0.00 | 21.44 |
May | 593.50 | 21.35 | 21.00 | 21.42 | 0.00 | 21.42 |
June | 572.50 | 21.34 | 30.33 | 21.44 | 0.00 | 21.44 |
July | 607.33 | 21.38 | 2.33 | 21.39 | 0.00 | 21.39 |
August | 611.00 | 21.39 | 11.83 | 21.43 | 0.83 | 21.43 |
September | 581.67 | 21.37 | 15.67 | 21.42 | 0.67 | 21.42 |
October | 606.50 | 21.38 | 13.50 | 21.42 | 1.67 | 21.43 |
November | 584.67 | 21.38 | 22.33 | 21.45 | 0.67 | 21.45 |
December | 601.00 | 21.37 | 40.33 | 21.49 | 0.50 | 21.49 |
Annual Sum or Average | 7044.33 | 21.36 | 317.33 | 21.45 | 4.33 | 21.45 |
Minimum of Months | 530.17 | 21.33 | 2.33 | 21.39 | 0.00 | 21.39 |
Maximum of Months | 611.00 | 21.39 | 47.33 | 21.49 | 1.67 | 21.49 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 616.50 | 21.57 | 28.83 | 21.66 | 25.67 | 21.74 |
February | 539.17 | 21.49 | 25.00 | 21.58 | 6.50 | 21.61 |
March | 599.33 | 21.38 | 31.00 | 21.48 | 1.83 | 21.48 |
April | 567.00 | 21.34 | 33.17 | 21.45 | 0.00 | 21.45 |
May | 584.67 | 21.34 | 33.00 | 21.45 | 0.50 | 21.45 |
June | 560.83 | 21.34 | 53.17 | 21.52 | 3.67 | 21.54 |
July | 598.67 | 21.40 | 9.33 | 21.44 | 3.33 | 21.45 |
August | 607.17 | 21.41 | 19.67 | 21.47 | 6.00 | 21.49 |
September | 582.17 | 21.41 | 20.50 | 21.48 | 7.83 | 21.51 |
October | 613.00 | 21.45 | 15.33 | 21.50 | 10.50 | 21.54 |
November | 587.17 | 21.50 | 18.50 | 21.57 | 12.83 | 21.62 |
December | 616.83 | 21.59 | 31.00 | 21.68 | 31.00 | 21.77 |
Annual Sum or Average | 7072.50 | 21.44 | 318.50 | 21.52 | 109.67 | 21.56 |
Minimum of Months | 539.17 | 21.34 | 9.33 | 21.44 | 0.00 | 21.45 |
Maximum of Months | 616.83 | 21.59 | 53.17 | 21.68 | 31.00 | 21.77 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 599.00 | 21.38 | 40.50 | 21.51 | 0.00 | 21.51 |
February | 543.33 | 21.39 | 18.33 | 21.45 | 0.00 | 21.45 |
March | 626.33 | 21.45 | 0.00 | 21.45 | 0.00 | 21.45 |
April | 629.50 | 21.52 | 0.00 | 21.52 | 0.00 | 21.52 |
May | 649.83 | 21.51 | 0.00 | 21.51 | 0.00 | 21.51 |
June | 626.50 | 21.51 | 0.00 | 21.51 | 0.00 | 21.51 |
July | 664.67 | 21.55 | 0.00 | 21.55 | 0.00 | 21.55 |
August | 669.67 | 21.56 | 1.33 | 21.56 | 1.33 | 21.56 |
September | 624.33 | 21.50 | 1.33 | 21.50 | 1.33 | 21.51 |
October | 640.50 | 21.49 | 3.17 | 21.50 | 1.67 | 21.50 |
November | 594.00 | 21.42 | 16.67 | 21.47 | 0.33 | 21.47 |
December | 599.17 | 21.38 | 48.67 | 21.53 | 0.00 | 21.53 |
Annual Sum or Average | 7466.83 | 21.47 | 130.00 | 21.51 | 4.67 | 21.51 |
Minimum of Months | 543.33 | 21.38 | 0.00 | 21.45 | 0.00 | 21.45 |
Maximum of Months | 669.67 | 21.56 | 48.67 | 21.56 | 1.67 | 21.56 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 712.83 | 23.73 | 0.00 | 23.73 |
February | 0.00 | 0.00 | 672.00 | 23.76 | 0.00 | 23.76 |
March | 4.50 | 22.32 | 735.33 | 23.77 | 0.00 | 23.77 |
April | 0.00 | 0.00 | 718.00 | 23.83 | 0.00 | 23.83 |
May | 4.50 | 22.43 | 728.00 | 23.84 | 0.00 | 23.84 |
June | 0.00 | 0.00 | 718.17 | 23.88 | 0.00 | 23.88 |
July | 0.00 | 0.00 | 736.17 | 23.80 | 0.00 | 23.80 |
August | 6.17 | 22.36 | 708.67 | 23.76 | 0.00 | 23.76 |
September | 0.00 | 0.00 | 689.17 | 23.78 | 0.00 | 23.78 |
October | 7.50 | 22.48 | 680.83 | 23.76 | 0.00 | 23.76 |
November | 0.17 | 22.51 | 688.00 | 23.74 | 0.00 | 23.74 |
December | 0.00 | 0.00 | 692.67 | 23.74 | 0.00 | 23.74 |
Annual Sum or Average | 22.83 | 22.41 | 8479.83 | 23.78 | 0.00 | 23.78 |
Minimum of Months | 0.00 | 0.00 | 672.00 | 23.73 | 0.00 | 23.73 |
Maximum of Months | 7.50 | 22.51 | 736.17 | 23.88 | 0.00 | 23.88 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 740.33 | 23.75 | 0.00 | 23.75 |
February | 0.00 | 0.00 | 672.00 | 23.80 | 0.00 | 23.80 |
March | 2.17 | 22.37 | 737.83 | 23.82 | 0.00 | 23.82 |
April | 0.00 | 0.00 | 720.00 | 23.87 | 0.00 | 23.87 |
May | 0.00 | 0.00 | 737.50 | 23.88 | 0.00 | 23.88 |
June | 0.00 | 0.00 | 720.00 | 23.91 | 0.00 | 23.91 |
July | 0.00 | 0.00 | 744.00 | 23.84 | 0.00 | 23.84 |
August | 1.83 | 22.39 | 733.33 | 23.79 | 0.00 | 23.79 |
September | 0.00 | 0.00 | 720.00 | 23.80 | 0.00 | 23.80 |
October | 0.00 | 0.00 | 722.83 | 23.77 | 0.00 | 23.77 |
November | 0.00 | 0.00 | 712.83 | 23.77 | 0.00 | 23.77 |
December | 0.00 | 0.00 | 741.00 | 23.74 | 0.00 | 23.74 |
Annual Sum or Average | 4.00 | 22.38 | 8701.67 | 23.81 | 0.00 | 23.81 |
Minimum of Months | 0.00 | 0.00 | 672.00 | 23.74 | 0.00 | 23.74 |
Maximum of Months | 2.17 | 22.39 | 744.00 | 23.91 | 0.00 | 23.91 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 556.00 | 23.98 | 743.67 | 23.77 | 556.00 | 23.83 |
February | 505.67 | 23.98 | 672.00 | 23.78 | 505.67 | 23.84 |
March | 561.50 | 23.98 | 743.67 | 23.79 | 561.50 | 23.85 |
April | 547.00 | 23.98 | 719.67 | 23.80 | 547.00 | 23.86 |
May | 563.83 | 23.98 | 743.67 | 23.80 | 563.83 | 23.86 |
June | 548.50 | 23.98 | 719.33 | 23.81 | 548.50 | 23.86 |
July | 560.33 | 23.98 | 744.00 | 23.79 | 560.33 | 23.85 |
August | 557.33 | 23.98 | 740.83 | 23.79 | 557.33 | 23.84 |
September | 542.17 | 23.98 | 716.67 | 23.79 | 542.17 | 23.85 |
October | 554.33 | 23.98 | 739.33 | 23.78 | 554.33 | 23.84 |
November | 540.17 | 23.98 | 719.33 | 23.77 | 540.17 | 23.83 |
December | 555.50 | 23.98 | 742.50 | 23.76 | 555.50 | 23.83 |
Annual Sum or Average | 6592.33 | 23.98 | 8744.67 | 23.79 | 6592.33 | 23.85 |
Minimum of Months | 505.67 | 23.98 | 672.00 | 23.76 | 505.67 | 23.83 |
Maximum of Months | 563.83 | 23.98 | 744.00 | 23.81 | 563.83 | 23.86 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 293.17 | 22.88 | 221.33 | 23.32 | 0.00 | 23.32 |
February | 186.67 | 23.01 | 305.83 | 23.58 | 0.00 | 23.58 |
March | 206.83 | 22.99 | 298.00 | 23.54 | 0.00 | 23.54 |
April | 140.33 | 22.99 | 300.50 | 23.64 | 0.00 | 23.64 |
May | 194.50 | 22.91 | 305.67 | 23.53 | 0.00 | 23.53 |
June | 122.17 | 23.02 | 344.17 | 23.70 | 0.00 | 23.70 |
July | 326.50 | 22.95 | 108.33 | 23.18 | 0.00 | 23.18 |
August | 422.67 | 22.77 | 131.33 | 23.03 | 0.00 | 23.03 |
September | 349.17 | 22.85 | 154.67 | 23.16 | 0.00 | 23.16 |
October | 430.83 | 22.80 | 82.17 | 22.97 | 0.00 | 22.97 |
November | 337.50 | 22.87 | 152.17 | 23.19 | 0.00 | 23.19 |
December | 340.83 | 22.82 | 172.17 | 23.19 | 0.00 | 23.19 |
Annual Sum or Average | 3351.17 | 22.88 | 2576.33 | 23.33 | 0.00 | 23.33 |
Minimum of Months | 122.17 | 22.77 | 82.17 | 22.97 | 0.00 | 22.97 |
Maximum of Months | 430.83 | 23.02 | 344.17 | 23.70 | 0.00 | 23.70 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.11242 | 52.86248 | 0.25483 | 6.42884 |
February | 672.00000 | 23.21758 | 52.54470 | 0.28072 | 6.68731 |
March | 744.00000 | 23.13471 | 52.68678 | 0.25967 | 6.45457 |
April | 720.00000 | 23.15365 | 52.61400 | 0.26295 | 6.51479 |
May | 744.00000 | 23.26055 | 52.28103 | -0.6726 | 14.62564 |
June | 720.00000 | 23.41326 | 51.82756 | -0.6199 | 13.18251 |
July | 744.00000 | 23.30963 | 52.16839 | -0.6560 | 14.13608 |
August | 744.00000 | 23.22148 | 52.45762 | -0.6869 | 15.07944 |
September | 720.00000 | 23.22304 | 52.57493 | -0.6839 | 15.00106 |
October | 744.00000 | 23.06653 | 52.95331 | 0.24294 | 6.29145 |
November | 720.00000 | 23.15351 | 52.71736 | 0.26450 | 6.51646 |
December | 744.00000 | 23.16798 | 52.77476 | 0.26876 | 6.56219 |
Annual Sum or Average | 8760.00000 | 23.20238 | 52.53968 | -0.1263 | 9.80990 |
Minimum of Months | 672.00000 | 23.06653 | 51.82756 | -0.6869 | 6.29145 |
Maximum of Months | 744.00000 | 23.41326 | 52.95331 | 0.28072 | 15.07944 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.51988 | 52.23509 | 0.49514 | 10.77409 |
February | 672.00000 | 23.66016 | 51.79866 | 0.53302 | 11.35629 |
March | 744.00000 | 23.59632 | 52.07139 | 0.50711 | 10.77271 |
April | 720.00000 | 23.51328 | 52.68493 | 0.48064 | 10.26050 |
May | 744.00000 | 23.41755 | 53.26048 | -0.4398 | 10.11799 |
June | 720.00000 | 23.51786 | 52.88596 | -0.4002 | 9.13578 |
July | 744.00000 | 23.24604 | 53.50178 | -0.5134 | 11.31737 |
August | 744.00000 | 23.10166 | 54.29573 | -0.5617 | 13.02668 |
September | 720.00000 | 23.29913 | 53.71367 | -0.4852 | 11.16188 |
October | 744.00000 | 23.21283 | 53.85043 | 0.40106 | 9.08697 |
November | 720.00000 | 23.42505 | 52.92340 | 0.46296 | 10.11140 |
December | 744.00000 | 23.47170 | 52.60723 | 0.48069 | 10.51338 |
Annual Sum or Average | 8760.00000 | 23.41285 | 52.99476 | 0.07701 | 10.63547 |
Minimum of Months | 672.00000 | 23.10166 | 51.79866 | -0.5617 | 9.08697 |
Maximum of Months | 744.00000 | 23.66016 | 54.29573 | 0.53302 | 13.02668 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.03827 | 54.33863 | 0.30323 | 7.19969 |
February | 672.00000 | 23.25659 | 53.68117 | 0.35874 | 7.88925 |
March | 744.00000 | 23.27466 | 53.55837 | 0.36310 | 8.00372 |
April | 720.00000 | 23.28010 | 53.64560 | 0.36445 | 8.06875 |
May | 744.00000 | 23.20974 | 53.97316 | -0.5942 | 13.04710 |
June | 720.00000 | 23.33979 | 53.51888 | -0.5451 | 11.78377 |
July | 744.00000 | 23.08831 | 54.21068 | -0.6394 | 14.10256 |
August | 744.00000 | 22.98050 | 54.70792 | -0.6764 | 15.48688 |
September | 720.00000 | 23.05852 | 54.57195 | -0.6467 | 14.53400 |
October | 744.00000 | 22.88578 | 54.99300 | 0.26596 | 6.80026 |
November | 720.00000 | 22.98746 | 54.61440 | 0.29125 | 7.03694 |
December | 744.00000 | 22.99643 | 54.59074 | 0.29363 | 7.04676 |
Annual Sum or Average | 8760.00000 | 23.11464 | 54.20588 | -0.0746 | 10.09835 |
Minimum of Months | 672.00000 | 22.88578 | 53.51888 | -0.6764 | 6.80026 |
Maximum of Months | 744.00000 | 23.33979 | 54.99300 | 0.36445 | 15.48688 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.06931 | 53.23571 | 0.65487 | 16.10253 |
February | 672.00000 | 22.13953 | 52.99313 | 0.69047 | 17.05639 |
March | 744.00000 | 22.16016 | 52.83652 | 0.70061 | 17.39969 |
April | 720.00000 | 22.18824 | 52.77537 | 0.71330 | 17.75122 |
May | 744.00000 | 22.16617 | 52.85799 | -0.0760 | 9.47200 |
June | 720.00000 | 22.20981 | 52.68396 | -0.0422 | 9.29862 |
July | 744.00000 | 22.09855 | 53.05869 | -0.1143 | 9.61079 |
August | 744.00000 | 22.08673 | 53.16804 | -0.1326 | 9.79682 |
September | 720.00000 | 22.09917 | 53.24891 | -0.1170 | 9.63723 |
October | 744.00000 | 22.03781 | 53.37867 | 0.63700 | 15.64801 |
November | 720.00000 | 22.07262 | 53.24905 | 0.65361 | 16.04686 |
December | 744.00000 | 22.04768 | 53.39812 | 0.64513 | 15.82643 |
Annual Sum or Average | 8760.00000 | 22.11414 | 53.07527 | 0.34882 | 13.61409 |
Minimum of Months | 672.00000 | 22.03781 | 52.68396 | -0.1326 | 9.29862 |
Maximum of Months | 744.00000 | 22.20981 | 53.39812 | 0.71330 | 17.75122 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.73862 | 57.80919 | 0.61150 | 13.13456 |
February | 672.00000 | 23.80509 | 57.58039 | 0.62992 | 13.48272 |
March | 744.00000 | 23.63534 | 58.16761 | 0.57763 | 12.25532 |
April | 720.00000 | 23.48898 | 58.80809 | 0.53523 | 11.32636 |
May | 744.00000 | 23.45501 | 59.06066 | -0.3575 | 8.43142 |
June | 720.00000 | 23.49652 | 58.84294 | -0.3382 | 7.99416 |
July | 744.00000 | 23.33022 | 59.45561 | -0.4148 | 9.32844 |
August | 744.00000 | 23.24545 | 59.91256 | -0.4475 | 10.19059 |
September | 720.00000 | 23.39270 | 59.47465 | -0.3842 | 8.84866 |
October | 744.00000 | 23.40701 | 59.36661 | 0.50922 | 10.85865 |
November | 720.00000 | 23.63609 | 58.43314 | 0.57701 | 12.27705 |
December | 744.00000 | 23.71661 | 58.11612 | 0.60331 | 12.92123 |
Annual Sum or Average | 8760.00000 | 23.52698 | 58.76042 | 0.17224 | 10.90857 |
Minimum of Months | 672.00000 | 23.24545 | 57.58039 | -0.4475 | 7.99416 |
Maximum of Months | 744.00000 | 23.80509 | 59.91256 | 0.62992 | 13.48272 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.34800 | 57.39541 | 0.41216 | 8.78942 |
February | 672.00000 | 23.46771 | 57.01585 | 0.44481 | 9.31761 |
March | 744.00000 | 23.40834 | 57.14847 | 0.42851 | 9.09135 |
April | 720.00000 | 23.41470 | 57.21089 | 0.43033 | 9.15811 |
May | 744.00000 | 23.46458 | 57.07158 | -0.4663 | 10.08444 |
June | 720.00000 | 23.56870 | 56.57605 | -0.4222 | 9.15683 |
July | 744.00000 | 23.39614 | 57.22948 | -0.4948 | 10.64407 |
August | 744.00000 | 23.25406 | 57.85789 | -0.5480 | 12.02369 |
September | 720.00000 | 23.29294 | 57.85628 | -0.5317 | 11.56388 |
October | 744.00000 | 23.19763 | 58.05646 | 0.37305 | 8.21795 |
November | 720.00000 | 23.31866 | 57.61310 | 0.40496 | 8.67599 |
December | 744.00000 | 23.33095 | 57.58781 | 0.40818 | 8.70187 |
Annual Sum or Average | 8760.00000 | 23.37079 | 57.38875 | 0.03395 | 9.62102 |
Minimum of Months | 672.00000 | 23.19763 | 56.57605 | -0.5480 | 8.21795 |
Maximum of Months | 744.00000 | 23.56870 | 58.05646 | 0.44481 | 12.02369 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.74417 | 52.47814 | -0.0023 | 5.76166 |
February | 672.00000 | 21.74715 | 51.91270 | 0.00760 | 5.76075 |
March | 744.00000 | 21.74553 | 51.93132 | 0.00730 | 5.73382 |
April | 720.00000 | 21.74516 | 52.59844 | 0.00882 | 5.76825 |
May | 744.00000 | 21.74488 | 53.33764 | -1.0629 | 30.11982 |
June | 720.00000 | 21.74615 | 53.20015 | -1.0529 | 29.69651 |
July | 744.00000 | 21.73868 | 53.37288 | -1.0886 | 31.21616 |
August | 744.00000 | 21.73765 | 54.21534 | -1.0869 | 31.17183 |
September | 720.00000 | 21.74095 | 53.90917 | -1.0798 | 30.89316 |
October | 744.00000 | 21.73905 | 53.95985 | -0.0113 | 5.74902 |
November | 720.00000 | 21.74215 | 52.99209 | -0.0077 | 5.75410 |
December | 744.00000 | 21.74334 | 52.95507 | -0.0057 | 5.76760 |
Annual Sum or Average | 8760.00000 | 21.74286 | 53.08030 | -0.4507 | 16.18021 |
Minimum of Months | 672.00000 | 21.73765 | 51.91270 | -1.0886 | 5.73382 |
Maximum of Months | 744.00000 | 21.74715 | 54.21534 | 0.00882 | 31.21616 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.89197 | 53.80266 | 0.01422 | 5.84317 |
February | 672.00000 | 21.87454 | 52.86454 | 0.02220 | 5.83162 |
March | 744.00000 | 21.75901 | 52.28444 | 0.00402 | 5.72939 |
April | 720.00000 | 21.75013 | 52.53690 | 0.01068 | 5.77671 |
May | 744.00000 | 21.76109 | 53.15829 | -1.0505 | 29.63783 |
June | 720.00000 | 21.77885 | 52.91193 | -1.0284 | 28.73331 |
July | 744.00000 | 21.77627 | 53.11561 | -1.0687 | 30.42681 |
August | 744.00000 | 21.75998 | 54.08933 | -1.0763 | 30.74803 |
September | 720.00000 | 21.77176 | 54.08047 | -1.0728 | 30.63008 |
October | 744.00000 | 21.78070 | 54.53674 | -0.0073 | 5.79368 |
November | 720.00000 | 21.84949 | 53.92720 | 0.00468 | 5.83560 |
December | 744.00000 | 21.90792 | 54.30449 | 0.01407 | 5.85652 |
Annual Sum or Average | 8760.00000 | 21.80477 | 53.47381 | -0.4390 | 15.96618 |
Minimum of Months | 672.00000 | 21.75013 | 52.28444 | -1.0763 | 5.72939 |
Maximum of Months | 744.00000 | 21.90792 | 54.53674 | 0.02220 | 30.74803 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.82183 | 55.51636 | -0.0727 | 5.72429 |
February | 672.00000 | 21.80931 | 54.79985 | -0.0735 | 5.70907 |
March | 744.00000 | 21.71334 | 53.78856 | -0.0975 | 5.72776 |
April | 720.00000 | 21.71151 | 53.70958 | -0.0921 | 5.77210 |
May | 744.00000 | 21.73301 | 53.85056 | -1.1827 | 35.31277 |
June | 720.00000 | 21.75669 | 53.92229 | -1.1606 | 34.33615 |
July | 744.00000 | 21.74655 | 53.62893 | -1.1859 | 35.46902 |
August | 744.00000 | 21.72121 | 54.46681 | -1.2010 | 36.14896 |
September | 720.00000 | 21.72678 | 54.74520 | -1.2012 | 36.18110 |
October | 744.00000 | 21.73206 | 55.04203 | -0.0922 | 5.76973 |
November | 720.00000 | 21.79357 | 55.05069 | -0.0791 | 5.75846 |
December | 744.00000 | 21.84004 | 55.92569 | -0.0684 | 5.72784 |
Annual Sum or Average | 8760.00000 | 21.75854 | 54.53703 | -0.5451 | 18.21255 |
Minimum of Months | 672.00000 | 21.71151 | 53.62893 | -1.2012 | 5.70907 |
Maximum of Months | 744.00000 | 21.84004 | 55.92569 | -0.0684 | 36.18110 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.75084 | 52.93535 | 0.00299 | 5.76229 |
February | 672.00000 | 21.75386 | 52.43796 | 0.01459 | 5.76360 |
March | 744.00000 | 21.75315 | 52.29973 | 0.01174 | 5.74632 |
April | 720.00000 | 21.75293 | 52.83012 | 0.01404 | 5.78638 |
May | 744.00000 | 21.75044 | 53.58640 | -1.0567 | 29.87400 |
June | 720.00000 | 21.75233 | 53.49228 | -1.0468 | 29.45010 |
July | 744.00000 | 21.74587 | 53.56729 | -1.0840 | 31.02555 |
August | 744.00000 | 21.74588 | 54.34443 | -1.0815 | 30.95851 |
September | 720.00000 | 21.74766 | 54.04019 | -1.0739 | 30.65031 |
October | 744.00000 | 21.74571 | 54.14418 | -0.0078 | 5.75308 |
November | 720.00000 | 21.74780 | 53.56988 | -0.0019 | 5.75221 |
December | 744.00000 | 21.74927 | 53.41369 | -0.0009 | 5.76522 |
Annual Sum or Average | 8760.00000 | 21.74960 | 53.39523 | -0.4453 | 16.08763 |
Minimum of Months | 672.00000 | 21.74571 | 52.29973 | -1.0840 | 5.74632 |
Maximum of Months | 744.00000 | 21.75386 | 54.34443 | 0.01459 | 31.02555 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.95198 | 54.11416 | 0.03026 | 6.05280 |
February | 672.00000 | 21.92488 | 53.27154 | 0.03811 | 6.01327 |
March | 744.00000 | 21.77082 | 52.63906 | 0.00935 | 5.75149 |
April | 720.00000 | 21.75711 | 52.81460 | 0.01597 | 5.79141 |
May | 744.00000 | 21.76512 | 53.42714 | -1.0448 | 29.40125 |
June | 720.00000 | 21.78436 | 53.13872 | -1.0230 | 28.52002 |
July | 744.00000 | 21.78329 | 53.41272 | -1.0637 | 30.22041 |
August | 744.00000 | 21.76735 | 54.25919 | -1.0710 | 30.53593 |
September | 720.00000 | 21.77863 | 54.17915 | -1.0671 | 30.39280 |
October | 744.00000 | 21.78987 | 54.58009 | -0.0042 | 5.80101 |
November | 720.00000 | 21.87064 | 54.26429 | 0.01243 | 5.87953 |
December | 744.00000 | 21.96098 | 54.56801 | 0.02813 | 6.02945 |
Annual Sum or Average | 8760.00000 | 21.82491 | 53.72744 | -0.4312 | 15.92725 |
Minimum of Months | 672.00000 | 21.75711 | 52.63906 | -1.0710 | 5.75149 |
Maximum of Months | 744.00000 | 21.96098 | 54.58009 | 0.03811 | 30.53593 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.74452 | 53.15232 | 0.00682 | 6.01348 |
February | 672.00000 | 21.74710 | 52.54900 | 0.01574 | 6.03646 |
March | 744.00000 | 21.74772 | 52.32777 | 0.01807 | 5.98741 |
April | 720.00000 | 21.74834 | 52.75253 | 0.02112 | 6.00318 |
May | 744.00000 | 21.74573 | 53.60243 | -1.0506 | 29.98033 |
June | 720.00000 | 21.74728 | 53.48921 | -1.0428 | 29.66002 |
July | 744.00000 | 21.73882 | 53.80823 | -1.0771 | 31.06235 |
August | 744.00000 | 21.73853 | 54.60005 | -1.0742 | 30.95832 |
September | 720.00000 | 21.74252 | 54.14934 | -1.0652 | 30.62848 |
October | 744.00000 | 21.73958 | 54.44722 | -0.0022 | 5.92861 |
November | 720.00000 | 21.74323 | 53.51170 | 0.00064 | 5.96124 |
December | 744.00000 | 21.74423 | 53.66474 | 0.00237 | 6.00660 |
Annual Sum or Average | 8760.00000 | 21.74393 | 53.51271 | -0.4401 | 16.24838 |
Minimum of Months | 672.00000 | 21.73853 | 52.32777 | -1.0771 | 5.92861 |
Maximum of Months | 744.00000 | 21.74834 | 54.60005 | 0.02112 | 31.06235 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.87240 | 54.53565 | 0.01935 | 6.03308 |
February | 672.00000 | 21.85889 | 53.39849 | 0.02658 | 6.04586 |
March | 744.00000 | 21.75897 | 52.59325 | 0.01389 | 5.95523 |
April | 720.00000 | 21.75379 | 52.67387 | 0.02311 | 6.01501 |
May | 744.00000 | 21.76203 | 53.41829 | -1.0379 | 29.50652 |
June | 720.00000 | 21.77921 | 53.21300 | -1.0178 | 28.73328 |
July | 744.00000 | 21.77663 | 53.51254 | -1.0568 | 30.30175 |
August | 744.00000 | 21.76152 | 54.47175 | -1.0631 | 30.53568 |
September | 720.00000 | 21.77569 | 54.30922 | -1.0572 | 30.33583 |
October | 744.00000 | 21.78216 | 55.02610 | 0.00216 | 5.97326 |
November | 720.00000 | 21.84668 | 54.48428 | 0.01258 | 6.02582 |
December | 744.00000 | 21.88972 | 55.17948 | 0.01911 | 6.04572 |
Annual Sum or Average | 8760.00000 | 21.80114 | 53.90799 | -0.4291 | 16.02047 |
Minimum of Months | 672.00000 | 21.75379 | 52.59325 | -1.0631 | 5.95523 |
Maximum of Months | 744.00000 | 21.88972 | 55.17948 | 0.02658 | 30.53568 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.76109 | 53.78012 | 0.00627 | 6.04000 |
February | 672.00000 | 21.75886 | 53.25730 | 0.00164 | 5.98981 |
March | 744.00000 | 21.75100 | 52.87547 | -0.0194 | 5.86930 |
April | 720.00000 | 21.74384 | 53.52808 | -0.0289 | 5.87215 |
May | 744.00000 | 21.74420 | 54.16105 | -1.1120 | 32.44626 |
June | 720.00000 | 21.74391 | 54.26517 | -1.1104 | 32.37170 |
July | 744.00000 | 21.73775 | 54.23933 | -1.1319 | 33.31116 |
August | 744.00000 | 21.73627 | 54.98940 | -1.1326 | 33.34681 |
September | 720.00000 | 21.74289 | 54.45429 | -1.1169 | 32.71441 |
October | 744.00000 | 21.74592 | 54.22924 | -0.0265 | 5.87798 |
November | 720.00000 | 21.75413 | 53.82495 | -0.0083 | 5.94546 |
December | 744.00000 | 21.76062 | 54.24304 | 0.00535 | 6.04820 |
Annual Sum or Average | 8760.00000 | 21.74831 | 53.99295 | -0.4757 | 17.22180 |
Minimum of Months | 672.00000 | 21.73627 | 52.87547 | -1.1326 | 5.86930 |
Maximum of Months | 744.00000 | 21.76109 | 54.98940 | 0.00627 | 33.34681 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.69049 | 57.58406 | 0.57442 | 12.10898 |
February | 672.00000 | 23.75554 | 57.26103 | 0.59794 | 12.64113 |
March | 744.00000 | 23.76653 | 57.01575 | 0.60555 | 12.85697 |
April | 720.00000 | 23.82385 | 56.75368 | 0.62636 | 13.36757 |
May | 744.00000 | 23.82736 | 56.67171 | -0.2060 | 6.17191 |
June | 720.00000 | 23.88012 | 56.33570 | -0.1752 | 5.80510 |
July | 744.00000 | 23.79319 | 56.90356 | -0.2302 | 6.34935 |
August | 744.00000 | 23.72024 | 57.33108 | -0.2663 | 6.88543 |
September | 720.00000 | 23.74080 | 57.41203 | -0.2568 | 6.72184 |
October | 744.00000 | 23.68366 | 57.65323 | 0.57321 | 12.13009 |
November | 720.00000 | 23.70066 | 57.57638 | 0.57771 | 12.18979 |
December | 744.00000 | 23.67917 | 57.80637 | 0.56858 | 11.97673 |
Annual Sum or Average | 8760.00000 | 23.75479 | 57.19337 | 0.24685 | 9.91601 |
Minimum of Months | 672.00000 | 23.67917 | 56.33570 | -0.2663 | 5.80510 |
Maximum of Months | 744.00000 | 23.88012 | 57.80637 | 0.62636 | 13.36757 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.74387 | 56.94612 | 0.61023 | 12.96384 |
February | 672.00000 | 23.79930 | 56.66621 | 0.63091 | 13.46684 |
March | 744.00000 | 23.81171 | 56.41996 | 0.63943 | 13.71318 |
April | 720.00000 | 23.86591 | 56.17003 | 0.65982 | 14.25014 |
May | 744.00000 | 23.86522 | 56.09500 | -0.1584 | 5.74727 |
June | 720.00000 | 23.91343 | 55.79116 | -0.1294 | 5.47917 |
July | 744.00000 | 23.84396 | 56.26518 | -0.1768 | 5.83298 |
August | 744.00000 | 23.78209 | 56.64222 | -0.2087 | 6.20634 |
September | 720.00000 | 23.79894 | 56.74253 | -0.2014 | 6.10540 |
October | 744.00000 | 23.74572 | 56.95682 | 0.61267 | 13.06296 |
November | 720.00000 | 23.75724 | 56.91299 | 0.61500 | 13.08380 |
December | 744.00000 | 23.73708 | 57.14066 | 0.60588 | 12.85869 |
Annual Sum or Average | 8760.00000 | 23.80511 | 56.56329 | 0.28941 | 10.20978 |
Minimum of Months | 672.00000 | 23.73708 | 55.79116 | -0.2087 | 5.47917 |
Maximum of Months | 744.00000 | 23.91343 | 57.14066 | 0.65982 | 14.25014 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.60576 | 56.26189 | 1.23336 | 39.34339 |
February | 672.00000 | 23.63094 | 56.06467 | 1.25438 | 40.23276 |
March | 744.00000 | 23.64664 | 55.89113 | 1.25978 | 40.39641 |
April | 720.00000 | 23.66643 | 55.79260 | 1.27282 | 40.94434 |
May | 744.00000 | 23.66308 | 55.85323 | 0.70456 | 21.55299 |
June | 720.00000 | 23.67728 | 55.71895 | 0.72384 | 22.04184 |
July | 744.00000 | 23.63959 | 55.99493 | 0.67820 | 20.89472 |
August | 744.00000 | 23.62793 | 56.14782 | 0.66119 | 20.53420 |
September | 720.00000 | 23.64141 | 56.18002 | 0.67888 | 20.92986 |
October | 744.00000 | 23.61218 | 56.30987 | 1.22363 | 38.76685 |
November | 720.00000 | 23.61009 | 56.27065 | 1.23079 | 39.14237 |
December | 744.00000 | 23.59372 | 56.41997 | 1.22514 | 39.01022 |
Annual Sum or Average | 8760.00000 | 23.63446 | 56.07650 | 1.01062 | 31.92803 |
Minimum of Months | 672.00000 | 23.59372 | 55.71895 | 0.66119 | 20.53420 |
Maximum of Months | 744.00000 | 23.67728 | 56.41997 | 1.27282 | 40.94434 |
Report: OccupantComfortDataSummaryMonthly
For: STORAGE_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.86011 | 52.47165 | 0.19083 | 5.82961 |
February | 672.00000 | 23.12091 | 51.70338 | 0.25324 | 6.36966 |
March | 744.00000 | 23.17601 | 51.55200 | 0.26605 | 6.55501 |
April | 720.00000 | 23.39269 | 51.23122 | 0.31849 | 7.22682 |
May | 744.00000 | 23.59164 | 50.85310 | -0.5572 | 11.83122 |
June | 720.00000 | 23.79120 | 50.08968 | -0.4812 | 10.03094 |
July | 744.00000 | 23.52451 | 50.70425 | -0.5844 | 12.33835 |
August | 744.00000 | 23.19764 | 52.07793 | -0.6924 | 15.60788 |
September | 720.00000 | 23.13679 | 52.32124 | -0.7113 | 15.99894 |
October | 744.00000 | 22.87442 | 52.97863 | 0.19773 | 5.93581 |
November | 720.00000 | 22.92989 | 52.61121 | 0.20984 | 5.99378 |
December | 744.00000 | 22.82674 | 52.77865 | 0.18440 | 5.77556 |
Annual Sum or Average | 8760.00000 | 23.20133 | 51.78410 | -0.1197 | 9.13956 |
Minimum of Months | 672.00000 | 22.82674 | 50.08968 | -0.7113 | 5.77556 |
Maximum of Months | 744.00000 | 23.79120 | 52.97863 | 0.31849 | 15.99894 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.08632 | 55.18045 | 0.21818 | 6.07131 |
February | 672.00000 | 23.29070 | 54.60721 | 0.26729 | 6.50825 |
March | 744.00000 | 23.18291 | 54.87663 | 0.24129 | 6.24436 |
April | 720.00000 | 23.16231 | 55.10114 | 0.23617 | 6.22189 |
May | 744.00000 | 23.26561 | 54.94242 | -0.7188 | 16.03476 |
June | 720.00000 | 23.46434 | 54.35087 | -0.6514 | 14.11745 |
July | 744.00000 | 23.03328 | 55.39391 | -0.7985 | 18.50545 |
August | 744.00000 | 22.88871 | 56.05573 | -0.8455 | 20.27021 |
September | 720.00000 | 22.89416 | 56.12935 | -0.8419 | 20.14058 |
October | 744.00000 | 22.86768 | 56.07687 | 0.16808 | 5.64514 |
November | 720.00000 | 23.02497 | 55.52773 | 0.20492 | 5.92944 |
December | 744.00000 | 23.04619 | 55.43905 | 0.20966 | 5.98054 |
Annual Sum or Average | 8760.00000 | 23.09864 | 55.31285 | -0.1955 | 11.00224 |
Minimum of Months | 672.00000 | 22.86768 | 54.35087 | -0.8455 | 5.64514 |
Maximum of Months | 744.00000 | 23.46434 | 56.12935 | 0.26729 | 20.27021 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.37736 | 51.90845 | 0.33454 | 7.59104 |
February | 672.00000 | 23.55235 | 51.40368 | 0.37750 | 8.15845 |
March | 744.00000 | 23.52195 | 51.44578 | 0.37049 | 8.05691 |
April | 720.00000 | 23.56543 | 51.44791 | 0.38191 | 8.23735 |
May | 744.00000 | 23.51447 | 51.68556 | -0.5565 | 11.99097 |
June | 720.00000 | 23.62922 | 51.28044 | -0.5147 | 10.88643 |
July | 744.00000 | 23.30889 | 52.15814 | -0.6321 | 13.72774 |
August | 744.00000 | 23.13667 | 52.88021 | -0.6900 | 15.72344 |
September | 720.00000 | 23.25656 | 52.61134 | -0.6467 | 14.37835 |
October | 744.00000 | 23.12553 | 52.89265 | 0.27485 | 6.83555 |
November | 720.00000 | 23.28325 | 52.33892 | 0.31260 | 7.30750 |
December | 744.00000 | 23.28132 | 52.32488 | 0.31177 | 7.30941 |
Annual Sum or Average | 8760.00000 | 23.37740 | 52.03788 | -0.0593 | 10.03017 |
Minimum of Months | 672.00000 | 23.12553 | 51.28044 | -0.6900 | 6.83555 |
Maximum of Months | 744.00000 | 23.62922 | 52.89265 | 0.38191 | 15.72344 |
Report: OccupantComfortDataSummaryMonthly
For: MECH_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.92025 | 51.91411 | 0.20963 | 6.01693 |
February | 672.00000 | 23.19465 | 51.10360 | 0.27547 | 6.64577 |
March | 744.00000 | 23.26067 | 50.91424 | 0.29089 | 6.88180 |
April | 720.00000 | 23.47184 | 50.57461 | 0.34315 | 7.59110 |
May | 744.00000 | 23.64013 | 50.24803 | -0.5280 | 11.18395 |
June | 720.00000 | 23.82378 | 49.53256 | -0.4541 | 9.50084 |
July | 744.00000 | 23.59510 | 50.06131 | -0.5488 | 11.52269 |
August | 744.00000 | 23.27230 | 51.41914 | -0.6579 | 14.67724 |
September | 720.00000 | 23.22367 | 51.64798 | -0.6743 | 14.99481 |
October | 744.00000 | 22.94722 | 52.35657 | 0.21936 | 6.16159 |
November | 720.00000 | 22.99912 | 52.00895 | 0.23071 | 6.21415 |
December | 744.00000 | 22.88546 | 52.21858 | 0.20285 | 5.95327 |
Annual Sum or Average | 8760.00000 | 23.26892 | 51.16963 | -0.0934 | 8.95734 |
Minimum of Months | 672.00000 | 22.88546 | 49.53256 | -0.6743 | 5.95327 |
Maximum of Months | 744.00000 | 23.82378 | 52.35657 | 0.34315 | 14.99481 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.301084E+12 | 183710.74 | 10-JAN-19:03 | 744.00 | 0.118278E+13 | 0.00 | 0.148387E+13 | 3.95 | 4.48 | 24-JAN-09:53 | 0.00 | 0.00 |
February | 0.283427E+12 | 198451.98 | 13-FEB-16:03 | 672.00 | 0.108791E+13 | 0.00 | 0.137134E+13 | 3.87 | 4.43 | 21-FEB-10:00 | 0.00 | 0.00 |
March | 0.330007E+12 | 201534.89 | 28-MAR-15:03 | 744.00 | 0.124642E+13 | 0.00 | 0.157642E+13 | 3.80 | 4.31 | 03-MAR-06:00 | 0.00 | 0.00 |
April | 0.366651E+12 | 234904.98 | 10-APR-18:03 | 720.00 | 0.134887E+13 | 0.00 | 0.171552E+13 | 3.71 | 4.25 | 14-APR-16:00 | 0.00 | 0.00 |
May | 0.416582E+12 | 238334.85 | 16-MAY-18:03 | 744.00 | 0.151743E+13 | 0.00 | 0.193401E+13 | 3.68 | 4.22 | 10-MAY-19:52 | 0.00 | 0.00 |
June | 0.410008E+12 | 258434.80 | 13-JUN-15:03 | 720.00 | 0.149232E+13 | 0.00 | 0.190233E+13 | 3.68 | 4.22 | 26-JUN-01:10 | 0.00 | 0.00 |
July | 0.339257E+12 | 205425.62 | 26-JUL-18:03 | 744.00 | 0.130779E+13 | 0.00 | 0.164704E+13 | 3.88 | 4.23 | 13-JUL-05:03 | 0.00 | 0.00 |
August | 0.379451E+12 | 241748.19 | 14-AUG-18:03 | 744.00 | 0.143577E+13 | 0.00 | 0.181522E+13 | 3.82 | 4.31 | 20-AUG-11:00 | 0.00 | 0.00 |
September | 0.359089E+12 | 226727.89 | 08-SEP-18:03 | 720.00 | 0.136280E+13 | 0.00 | 0.172189E+13 | 3.83 | 4.24 | 16-SEP-03:00 | 0.00 | 0.00 |
October | 0.349647E+12 | 209986.85 | 16-OCT-15:05 | 744.00 | 0.135395E+13 | 0.00 | 0.170360E+13 | 3.90 | 4.25 | 23-OCT-03:50 | 0.00 | 0.00 |
November | 0.323144E+12 | 204630.65 | 17-NOV-19:03 | 720.00 | 0.125896E+13 | 0.00 | 0.158211E+13 | 3.92 | 4.37 | 25-NOV-05:00 | 0.00 | 0.00 |
December | 0.314078E+12 | 194044.93 | 29-DEC-19:03 | 744.00 | 0.124419E+13 | 0.00 | 0.155827E+13 | 3.98 | 4.46 | 21-DEC-05:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.417243E+13 | 8760.00 | 0.158392E+14 | 0.00 | 0.200116E+14 | 3.83 | 0.00 | 0.00 | ||||
Minimum of Months | 0.283427E+12 | 183710.74 | 672.00 | 0.108791E+13 | 0.00 | 0.137134E+13 | 3.68 | 4.22 | 0.00 | 0.00 | ||
Maximum of Months | 0.416582E+12 | 258434.80 | 744.00 | 0.151743E+13 | 0.00 | 0.193401E+13 | 3.98 | 4.48 | 0.00 | 0.00 |
Report: DXReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.568716E+11 | 0.00 | 589.00 | 0.331494E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 44040.44 | 08-JAN-09:03 | 21102.34 | 04-JAN-13:20 | 0.00 | 0.00 | 0.00 |
February | 0.518421E+11 | 0.00 | 532.00 | 0.309985E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 41854.11 | 13-FEB-06:50 | 21480.66 | 26-FEB-14:00 | 0.00 | 0.00 | 0.00 |
March | 0.598825E+11 | 0.00 | 589.00 | 0.348556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 37589.10 | 15-MAR-08:61 | 21921.37 | 19-MAR-12:05 | 0.00 | 0.00 | 0.00 |
April | 0.663997E+11 | 0.00 | 570.00 | 0.345819E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 43293.11 | 10-APR-18:02 | 21728.45 | 01-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.758943E+11 | 0.00 | 589.00 | 0.357300E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 51677.37 | 10-MAY-21:10 | 22726.80 | 06-MAY-13:00 | 0.00 | 0.00 | 0.00 |
June | 0.730128E+11 | 0.00 | 570.00 | 0.344814E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 50422.22 | 25-JUN-20:00 | 22301.64 | 16-JUN-13:00 | 0.00 | 0.00 | 0.00 |
July | 0.641685E+11 | 0.00 | 589.00 | 0.342598E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 47849.77 | 10-JUL-15:00 | 20957.89 | 15-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.727064E+11 | 0.00 | 589.00 | 0.345393E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 50776.45 | 19-AUG-18:03 | 21451.31 | 13-AUG-13:00 | 0.00 | 0.00 | 0.00 |
September | 0.687233E+11 | 0.00 | 570.00 | 0.334693E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 50918.65 | 15-SEP-21:30 | 20978.81 | 09-SEP-12:20 | 0.00 | 0.00 | 0.00 |
October | 0.689498E+11 | 0.00 | 589.00 | 0.340017E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 53022.45 | 30-OCT-18:03 | 20719.24 | 04-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.627487E+11 | 0.00 | 570.00 | 0.327348E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 46554.98 | 26-NOV-09:03 | 20919.00 | 18-NOV-13:20 | 0.00 | 0.00 | 0.00 |
December | 0.601053E+11 | 0.00 | 589.00 | 0.329093E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 44256.12 | 29-DEC-07:03 | 20516.72 | 31-DEC-13:05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.781305E+12 | 0.00 | 6935.00 | 0.405711E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.518421E+11 | 0.00 | 532.00 | 0.309985E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 37589.10 | 20516.72 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.758943E+11 | 0.00 | 589.00 | 0.357300E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 53022.45 | 22726.80 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.925071E+12 | 0.00 | 744.00 | 0.506805E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 471635.17 | 08-JAN-08:23 | 240182.16 | 05-JAN-19:07 | 0.00 | 0.00 | 0.00 |
February | 0.847528E+12 | 0.00 | 672.00 | 0.481812E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 465925.33 | 17-FEB-06:50 | 246723.49 | 22-FEB-16:05 | 0.00 | 0.00 | 0.00 |
March | 0.981663E+12 | 0.00 | 744.00 | 0.546072E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 511426.47 | 14-MAR-21:20 | 250117.61 | 29-MAR-18:10 | 0.00 | 0.00 | 0.00 |
April | 0.108147E+13 | 0.00 | 720.00 | 0.543545E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 572090.62 | 10-APR-18:07 | 270478.94 | 30-APR-19:10 | 0.00 | 0.00 | 0.00 |
May | 0.122872E+13 | 0.00 | 744.00 | 0.564441E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 607231.40 | 28-MAY-21:00 | 273164.45 | 05-MAY-19:10 | 0.00 | 0.00 | 0.00 |
June | 0.120448E+13 | 0.00 | 720.00 | 0.553137E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 588810.66 | 13-JUN-18:00 | 283728.26 | 12-JUN-19:10 | 0.00 | 0.00 | 0.00 |
July | 0.104745E+13 | 0.00 | 744.00 | 0.529490E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 599865.91 | 17-JUL-18:50 | 266591.17 | 14-JUL-18:07 | 0.00 | 0.00 | 0.00 |
August | 0.117241E+13 | 0.00 | 744.00 | 0.530931E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 588952.42 | 08-AUG-18:07 | 261228.53 | 14-AUG-18:20 | 0.00 | 0.00 | 0.00 |
September | 0.110689E+13 | 0.00 | 720.00 | 0.514217E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 601246.83 | 15-SEP-19:25 | 258045.02 | 13-SEP-20:10 | 0.00 | 0.00 | 0.00 |
October | 0.109618E+13 | 0.00 | 744.00 | 0.515293E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 567378.30 | 09-OCT-19:20 | 242241.04 | 04-OCT-20:10 | 0.00 | 0.00 | 0.00 |
November | 0.100579E+13 | 0.00 | 720.00 | 0.497945E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 553797.49 | 30-NOV-23:00 | 244341.00 | 17-NOV-19:10 | 0.00 | 0.00 | 0.00 |
December | 0.987090E+12 | 0.00 | 744.00 | 0.498627E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 521836.11 | 18-DEC-24:00 | 243409.69 | 08-DEC-21:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.126848E+14 | 0.00 | 8760.00 | 0.628232E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.847528E+12 | 0.00 | 672.00 | 0.481812E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 465925.33 | 240182.16 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.122872E+13 | 0.00 | 744.00 | 0.564441E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 607231.40 | 283728.26 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.109161E+11 | 0.00 | 715.70 | 0.674801E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13987.38 | 08-JAN-09:02 | 12287.38 | 05-JAN-09:02 | 0.00 | 0.00 | 0.00 |
February | 0.105585E+11 | 0.00 | 647.80 | 0.678005E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13265.73 | 12-FEB-09:02 | 12289.30 | 07-FEB-09:02 | 0.00 | 0.00 | 0.00 |
March | 0.117319E+11 | 0.00 | 715.52 | 0.760953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13310.89 | 15-MAR-08:61 | 12347.02 | 18-MAR-08:62 | 0.00 | 0.00 | 0.00 |
April | 0.114577E+11 | 0.00 | 692.34 | 0.735162E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12975.88 | 10-APR-08:61 | 12368.90 | 30-APR-08:62 | 0.00 | 0.00 | 0.00 |
May | 0.114823E+11 | 0.00 | 715.99 | 0.710919E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13533.73 | 17-MAY-15:02 | 12316.37 | 11-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.115573E+11 | 0.00 | 694.59 | 0.732276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13132.80 | 27-JUN-08:62 | 12355.50 | 03-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.102138E+11 | 0.00 | 710.88 | 0.600024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13635.37 | 22-JUL-08:61 | 12353.20 | 10-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.102696E+11 | 0.00 | 709.21 | 0.598874E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14907.86 | 19-AUG-18:02 | 12380.24 | 16-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.101710E+11 | 0.00 | 689.65 | 0.598880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14667.19 | 18-SEP-08:61 | 12326.32 | 16-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.100783E+11 | 0.00 | 711.48 | 0.581148E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15061.19 | 30-OCT-18:02 | 12345.68 | 20-OCT-18:02 | 0.00 | 0.00 | 0.00 |
November | 0.101781E+11 | 0.00 | 690.86 | 0.607943E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14477.16 | 26-NOV-09:02 | 12328.91 | 30-NOV-19:02 | 0.00 | 0.00 | 0.00 |
December | 0.105879E+11 | 0.00 | 715.28 | 0.635337E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14244.09 | 24-DEC-09:02 | 12345.62 | 12-DEC-19:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.129203E+12 | 0.00 | 8409.31 | 0.791432E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.100783E+11 | 0.00 | 647.80 | 0.581148E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12975.88 | 12287.38 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.117319E+11 | 0.00 | 715.99 | 0.760953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15061.19 | 12380.24 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.917437E+10 | 0.00 | 647.10 | 0.539951E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15929.41 | 07-JAN-09:11 | 12478.60 | 02-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 0.928593E+10 | 0.00 | 602.23 | 0.570433E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15649.47 | 12-FEB-09:41 | 12459.00 | 15-FEB-19:02 | 0.00 | 0.00 | 0.00 |
March | 0.111787E+11 | 0.00 | 707.02 | 0.705678E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15015.07 | 15-MAR-08:61 | 12495.08 | 21-MAR-08:62 | 0.00 | 0.00 | 0.00 |
April | 0.115198E+11 | 0.00 | 691.90 | 0.738686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14004.76 | 14-APR-17:02 | 12675.67 | 14-APR-17:02 | 0.00 | 0.00 | 0.00 |
May | 0.118277E+11 | 0.00 | 715.15 | 0.741972E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15500.74 | 10-MAY-21:51 | 12496.52 | 13-MAY-08:62 | 0.00 | 0.00 | 0.00 |
June | 0.121920E+11 | 0.00 | 690.65 | 0.794616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16320.58 | 25-JUN-21:51 | 12538.90 | 01-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.105715E+11 | 0.00 | 703.33 | 0.635280E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16475.35 | 19-JUL-21:51 | 12478.08 | 06-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.104173E+11 | 0.00 | 703.52 | 0.613416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15958.32 | 19-AUG-20:11 | 12466.79 | 24-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.996138E+10 | 0.00 | 679.74 | 0.580919E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15968.58 | 15-SEP-21:51 | 12471.49 | 19-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.944738E+10 | 0.00 | 693.74 | 0.528881E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16384.27 | 23-OCT-08:61 | 12509.20 | 10-OCT-18:02 | 0.00 | 0.00 | 0.00 |
November | 0.896143E+10 | 0.00 | 648.14 | 0.509183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15974.54 | 26-NOV-09:51 | 12483.23 | 20-NOV-19:02 | 0.00 | 0.00 | 0.00 |
December | 0.877908E+10 | 0.00 | 640.62 | 0.500866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16320.74 | 24-DEC-09:41 | 12423.08 | 11-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.123316E+12 | 0.00 | 8123.16 | 0.745988E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.877908E+10 | 0.00 | 602.23 | 0.500866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14004.76 | 12423.08 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.121920E+11 | 0.00 | 715.15 | 0.794616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16475.35 | 12675.67 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.652200E+11 | 0.00 | 744.00 | 0.415014E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 42224.60 | 04-JAN-15:00 | 38225.66 | 05-JAN-13:10 | 0.00 | 0.00 | 0.00 |
February | 0.581841E+11 | 0.00 | 672.00 | 0.358292E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 38476.64 | 04-FEB-09:00 | 32567.46 | 04-FEB-14:30 | 0.00 | 0.00 | 0.00 |
March | 0.561051E+11 | 0.00 | 744.00 | 0.298949E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 33644.73 | 11-MAR-09:00 | 22855.36 | 11-MAR-09:00 | 0.00 | 0.00 | 0.00 |
April | 0.498813E+11 | 0.00 | 719.67 | 0.238625E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 31204.94 | 30-APR-08:00 | 20610.20 | 01-APR-20:20 | 0.00 | 0.00 | 0.00 |
May | 0.517745E+11 | 0.00 | 741.47 | 0.244487E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 33534.47 | 07-MAY-08:00 | 22277.44 | 06-MAY-08:00 | 0.00 | 0.00 | 0.00 |
June | 0.502275E+11 | 0.00 | 719.00 | 0.236679E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 31995.70 | 18-JUN-08:00 | 20777.57 | 13-JUN-20:20 | 0.00 | 0.00 | 0.00 |
July | 0.467060E+11 | 0.00 | 742.50 | 0.207691E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 29186.34 | 30-JUL-08:00 | 18509.29 | 15-JUL-20:10 | 0.00 | 0.00 | 0.00 |
August | 0.460942E+11 | 0.00 | 737.90 | 0.197714E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 30894.39 | 13-AUG-08:00 | 18272.14 | 14-AUG-21:00 | 0.00 | 0.00 | 0.00 |
September | 0.485663E+11 | 0.00 | 717.81 | 0.225302E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 30946.63 | 30-SEP-08:00 | 19767.01 | 27-SEP-20:20 | 0.00 | 0.00 | 0.00 |
October | 0.526438E+11 | 0.00 | 740.94 | 0.259468E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 35960.98 | 29-OCT-08:00 | 25477.94 | 29-OCT-08:00 | 0.00 | 0.00 | 0.00 |
November | 0.583729E+11 | 0.00 | 719.00 | 0.336050E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 41476.78 | 23-NOV-09:00 | 35057.34 | 23-NOV-09:00 | 0.00 | 0.00 | 0.00 |
December | 0.645043E+11 | 0.00 | 743.67 | 0.406462E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 42926.97 | 31-DEC-08:55 | 38449.62 | 07-DEC-12:50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.648280E+12 | 0.00 | 8741.95 | 0.342473E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.460942E+11 | 0.00 | 672.00 | 0.197714E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 29186.34 | 18272.14 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.652200E+11 | 0.00 | 744.00 | 0.415014E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 42926.97 | 38449.62 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.642012E+11 | 0.00 | 592.27 | 0.385201E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 103324.62 | 07-JAN-09:11 | 85299.55 | 02-JAN-19:02 | 0.00 | 0.00 | 0.00 |
February | 0.619828E+11 | 0.00 | 554.01 | 0.379079E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 100001.81 | 23-FEB-09:11 | 85401.66 | 18-FEB-19:02 | 0.00 | 0.00 | 0.00 |
March | 0.726797E+11 | 0.00 | 647.52 | 0.457843E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 102060.41 | 15-MAR-08:61 | 85178.78 | 11-MAR-19:02 | 0.00 | 0.00 | 0.00 |
April | 0.761459E+11 | 0.00 | 638.92 | 0.496699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 92557.28 | 14-APR-18:02 | 85541.83 | 10-APR-18:02 | 0.00 | 0.00 | 0.00 |
May | 0.845785E+11 | 0.00 | 670.33 | 0.563602E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 100219.50 | 10-MAY-21:51 | 85696.52 | 01-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.879467E+11 | 0.00 | 662.72 | 0.600700E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 109261.32 | 25-JUN-21:51 | 85571.49 | 22-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.803259E+11 | 0.00 | 654.55 | 0.531620E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 110083.35 | 19-JUL-21:51 | 85660.57 | 19-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.756142E+11 | 0.00 | 647.04 | 0.480279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 109733.20 | 19-AUG-20:11 | 85626.59 | 05-AUG-08:61 | 0.00 | 0.00 | 0.00 |
September | 0.706453E+11 | 0.00 | 621.44 | 0.439389E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 108928.49 | 15-SEP-18:41 | 85474.91 | 25-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.686519E+11 | 0.00 | 627.94 | 0.415467E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 109749.60 | 23-OCT-08:61 | 85664.60 | 15-OCT-18:02 | 0.00 | 0.00 | 0.00 |
November | 0.646104E+11 | 0.00 | 592.84 | 0.391376E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 106471.46 | 26-NOV-09:51 | 85542.54 | 06-NOV-19:02 | 0.00 | 0.00 | 0.00 |
December | 0.629191E+11 | 0.00 | 587.83 | 0.372344E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 110169.32 | 20-DEC-09:02 | 85346.65 | 24-DEC-19:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.870302E+12 | 0.00 | 7497.41 | 0.551360E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.619828E+11 | 0.00 | 554.01 | 0.372344E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 92557.28 | 85178.78 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.879467E+11 | 0.00 | 670.33 | 0.600700E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 110169.32 | 85696.52 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.109022E+11 | 0.00 | 724.18 | 0.680108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12016.62 | 08-JAN-09:02 | 10970.62 | 23-JAN-19:02 | 0.00 | 0.00 | 0.00 |
February | 0.106280E+11 | 0.00 | 657.53 | 0.693525E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11290.94 | 08-FEB-09:02 | 10948.83 | 11-FEB-09:02 | 0.00 | 0.00 | 0.00 |
March | 0.116690E+11 | 0.00 | 727.30 | 0.764617E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11419.20 | 15-MAR-08:61 | 10978.12 | 28-MAR-08:62 | 0.00 | 0.00 | 0.00 |
April | 0.114937E+11 | 0.00 | 703.81 | 0.750005E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11401.85 | 14-APR-18:02 | 11017.69 | 09-APR-18:02 | 0.00 | 0.00 | 0.00 |
May | 0.115410E+11 | 0.00 | 723.55 | 0.736320E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12259.36 | 17-MAY-15:02 | 10988.80 | 10-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.115713E+11 | 0.00 | 703.29 | 0.744571E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11452.65 | 02-JUN-08:62 | 10995.75 | 26-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.101889E+11 | 0.00 | 719.13 | 0.609742E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11888.58 | 22-JUL-08:61 | 11011.50 | 07-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.102733E+11 | 0.00 | 718.15 | 0.609814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13302.65 | 19-AUG-18:02 | 10987.58 | 25-AUG-08:62 | 0.00 | 0.00 | 0.00 |
September | 0.102356E+11 | 0.00 | 698.29 | 0.619600E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12861.10 | 18-SEP-08:61 | 11002.31 | 20-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.100664E+11 | 0.00 | 718.42 | 0.594020E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13374.38 | 30-OCT-18:02 | 11005.74 | 15-OCT-18:02 | 0.00 | 0.00 | 0.00 |
November | 0.101808E+11 | 0.00 | 697.92 | 0.616939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12797.61 | 26-NOV-09:02 | 10974.86 | 06-NOV-19:02 | 0.00 | 0.00 | 0.00 |
December | 0.105850E+11 | 0.00 | 722.89 | 0.646203E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12256.63 | 17-DEC-09:02 | 10979.02 | 14-DEC-19:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.129335E+12 | 0.00 | 8514.45 | 0.806547E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.100664E+11 | 0.00 | 657.53 | 0.594020E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11290.94 | 10948.83 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.116690E+11 | 0.00 | 727.30 | 0.764617E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13374.38 | 11017.69 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.907683E+10 | 0.00 | 653.92 | 0.532807E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14816.06 | 07-JAN-09:11 | 11073.33 | 31-JAN-08:12 | 0.00 | 0.00 | 0.00 |
February | 0.929265E+10 | 0.00 | 609.96 | 0.573496E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14558.40 | 12-FEB-09:41 | 11561.51 | 24-FEB-09:11 | 0.00 | 0.00 | 0.00 |
March | 0.111107E+11 | 0.00 | 719.08 | 0.705819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13861.20 | 15-MAR-07:33 | 11084.78 | 03-MAR-16:01 | 0.00 | 0.00 | 0.00 |
April | 0.115519E+11 | 0.00 | 703.28 | 0.752447E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11893.36 | 14-APR-18:02 | 11111.60 | 10-APR-18:02 | 0.00 | 0.00 | 0.00 |
May | 0.118871E+11 | 0.00 | 721.66 | 0.770243E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13609.52 | 10-MAY-21:51 | 11094.71 | 25-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.122065E+11 | 0.00 | 697.38 | 0.816732E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14382.16 | 25-JUN-21:51 | 11066.35 | 04-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.105483E+11 | 0.00 | 710.95 | 0.644818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14424.15 | 19-JUL-21:51 | 11104.71 | 12-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.104209E+11 | 0.00 | 712.60 | 0.624921E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14195.52 | 19-AUG-20:11 | 11123.19 | 06-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.100248E+11 | 0.00 | 687.78 | 0.602527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14154.37 | 15-SEP-21:51 | 11093.19 | 01-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.943372E+10 | 0.00 | 700.24 | 0.543584E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14590.94 | 23-OCT-08:61 | 11115.81 | 15-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.894736E+10 | 0.00 | 654.71 | 0.519867E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14262.77 | 26-NOV-09:51 | 11110.02 | 06-NOV-08:62 | 0.00 | 0.00 | 0.00 |
December | 0.869682E+10 | 0.00 | 645.13 | 0.502887E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14973.54 | 20-DEC-08:42 | 11087.58 | 08-DEC-19:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.123197E+12 | 0.00 | 8216.69 | 0.759015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.869682E+10 | 0.00 | 609.96 | 0.502887E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11893.36 | 11066.35 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.122065E+11 | 0.00 | 721.66 | 0.816732E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14973.54 | 11561.51 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.279632E+10 | 0.00 | 717.68 | 0.171277E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4015.42 | 08-JAN-09:02 | 3336.41 | 10-JAN-19:02 | 0.00 | 0.00 | 0.00 |
February | 0.269264E+10 | 0.00 | 649.77 | 0.169738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3757.83 | 12-FEB-09:02 | 3328.06 | 08-FEB-19:02 | 0.00 | 0.00 | 0.00 |
March | 0.304210E+10 | 0.00 | 716.40 | 0.194418E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3868.77 | 15-MAR-08:61 | 3340.91 | 14-MAR-18:02 | 0.00 | 0.00 | 0.00 |
April | 0.300402E+10 | 0.00 | 693.82 | 0.189953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3732.80 | 10-APR-08:61 | 3346.62 | 10-APR-18:02 | 0.00 | 0.00 | 0.00 |
May | 0.296407E+10 | 0.00 | 716.71 | 0.179737E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3805.80 | 26-MAY-08:61 | 3384.82 | 18-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.295722E+10 | 0.00 | 695.19 | 0.181767E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3798.00 | 27-JUN-08:62 | 3376.21 | 30-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.262699E+10 | 0.00 | 711.69 | 0.149185E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3920.57 | 22-JUL-08:61 | 3367.93 | 06-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.265762E+10 | 0.00 | 710.93 | 0.150972E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4234.56 | 19-AUG-18:02 | 3380.30 | 30-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.265435E+10 | 0.00 | 690.40 | 0.153478E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4235.18 | 18-SEP-08:61 | 3376.30 | 26-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.259781E+10 | 0.00 | 712.48 | 0.145853E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4265.00 | 30-OCT-18:02 | 3374.40 | 13-OCT-18:02 | 0.00 | 0.00 | 0.00 |
November | 0.260522E+10 | 0.00 | 692.92 | 0.152306E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4199.36 | 26-NOV-09:02 | 3358.07 | 30-NOV-19:02 | 0.00 | 0.00 | 0.00 |
December | 0.269518E+10 | 0.00 | 716.82 | 0.160782E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4052.24 | 24-DEC-09:02 | 3350.11 | 18-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.332935E+11 | 0.00 | 8424.80 | 0.199947E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.259781E+10 | 0.00 | 649.77 | 0.145853E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3732.80 | 3328.06 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.304210E+10 | 0.00 | 717.68 | 0.194418E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4265.00 | 3384.82 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.236193E+10 | 0.00 | 649.85 | 0.136082E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4537.46 | 07-JAN-09:11 | 3395.52 | 23-JAN-22:51 | 0.00 | 0.00 | 0.00 |
February | 0.238047E+10 | 0.00 | 603.78 | 0.144784E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4390.90 | 23-FEB-09:11 | 3374.45 | 14-FEB-19:02 | 0.00 | 0.00 | 0.00 |
March | 0.290295E+10 | 0.00 | 707.65 | 0.181711E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4278.11 | 15-MAR-08:61 | 3405.28 | 07-MAR-19:02 | 0.00 | 0.00 | 0.00 |
April | 0.302088E+10 | 0.00 | 693.19 | 0.191041E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3874.48 | 14-APR-17:02 | 3583.04 | 14-APR-17:02 | 0.00 | 0.00 | 0.00 |
May | 0.305680E+10 | 0.00 | 715.12 | 0.187995E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4281.71 | 10-MAY-21:51 | 3414.03 | 18-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.312667E+10 | 0.00 | 691.18 | 0.198070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4645.03 | 25-JUN-21:51 | 3405.11 | 02-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.272478E+10 | 0.00 | 703.17 | 0.159269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4709.11 | 19-JUL-21:51 | 3389.06 | 06-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.269722E+10 | 0.00 | 705.35 | 0.154774E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4712.22 | 19-AUG-20:11 | 3416.46 | 30-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.260267E+10 | 0.00 | 680.38 | 0.148809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4556.25 | 15-SEP-21:51 | 3417.97 | 25-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.243720E+10 | 0.00 | 694.68 | 0.131694E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4711.67 | 23-OCT-08:61 | 3421.26 | 17-OCT-18:02 | 0.00 | 0.00 | 0.00 |
November | 0.229806E+10 | 0.00 | 649.80 | 0.126016E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4545.30 | 26-NOV-09:51 | 3411.82 | 30-NOV-19:02 | 0.00 | 0.00 | 0.00 |
December | 0.224476E+10 | 0.00 | 643.15 | 0.124519E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4666.14 | 24-DEC-09:41 | 3360.62 | 09-DEC-19:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.318544E+11 | 0.00 | 8137.29 | 0.188476E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.224476E+10 | 0.00 | 603.78 | 0.124519E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3874.48 | 3360.62 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.312667E+10 | 0.00 | 715.12 | 0.198070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4712.22 | 3583.04 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.169585E+11 | 0.00 | 723.81 | 0.118190E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 15963.40 | 08-JAN-09:02 | 13774.67 | 12-JAN-09:02 | 0.00 | 0.00 | 0.00 |
February | 0.151956E+11 | 0.00 | 653.35 | 0.106172E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 14789.23 | 08-FEB-09:02 | 13791.89 | 16-FEB-09:02 | 0.00 | 0.00 | 0.00 |
March | 0.151956E+11 | 0.00 | 715.64 | 0.102690E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 15226.11 | 15-MAR-08:61 | 13791.54 | 17-MAR-08:62 | 0.00 | 0.00 | 0.00 |
April | 0.139228E+11 | 0.00 | 690.07 | 0.898676E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14406.76 | 10-APR-08:61 | 13794.64 | 08-APR-08:62 | 0.00 | 0.00 | 0.00 |
May | 0.143314E+11 | 0.00 | 711.88 | 0.909531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14954.53 | 17-MAY-15:02 | 13825.59 | 05-MAY-08:62 | 0.00 | 0.00 | 0.00 |
June | 0.139472E+11 | 0.00 | 690.23 | 0.882052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14982.58 | 27-JUN-08:62 | 13820.83 | 19-JUN-08:62 | 0.00 | 0.00 | 0.00 |
July | 0.129861E+11 | 0.00 | 709.25 | 0.785475E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15676.78 | 22-JUL-08:61 | 13794.33 | 16-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.128933E+11 | 0.00 | 706.40 | 0.766941E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18827.25 | 19-AUG-18:02 | 13797.48 | 21-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.133406E+11 | 0.00 | 688.57 | 0.824250E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17670.04 | 18-SEP-08:61 | 13766.85 | 26-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.141893E+11 | 0.00 | 714.15 | 0.896744E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18332.05 | 30-OCT-18:02 | 13838.85 | 30-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.153050E+11 | 0.00 | 697.77 | 0.102224E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 17034.18 | 26-NOV-09:02 | 13805.12 | 11-NOV-19:02 | 0.00 | 0.00 | 0.00 |
December | 0.167352E+11 | 0.00 | 724.40 | 0.114339E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 16283.17 | 14-DEC-09:02 | 13782.15 | 02-DEC-09:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.175001E+12 | 0.00 | 8425.52 | 0.113998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.128933E+11 | 0.00 | 653.35 | 0.766941E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14406.76 | 13766.85 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.169585E+11 | 0.00 | 724.40 | 0.118190E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18827.25 | 13838.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 378.91 | 157.79 | 221.13 | 815.68 | 53.74 | 0.00 | 0.00 | 0.00 |
February | 320.52 | 103.37 | 217.15 | 736.63 | 40.53 | 0.00 | 0.00 | 0.00 |
March | 223.51 | 33.17 | 190.34 | 566.82 | 20.90 | 0.00 | 0.00 | 0.00 |
April | 165.70 | 0.95 | 164.74 | 455.25 | 2.71 | 0.00 | 0.00 | 0.00 |
May | 164.05 | 0.00 | 164.05 | 471.75 | 6.10 | 0.00 | 0.00 | 0.00 |
June | 163.46 | 0.00 | 163.46 | 458.04 | 7.20 | 0.00 | 0.00 | 0.00 |
July | 168.39 | 0.00 | 168.39 | 419.52 | 16.53 | 0.00 | 0.00 | 0.00 |
August | 163.72 | 0.01 | 163.71 | 413.48 | 7.86 | 0.00 | 0.00 | 0.00 |
September | 180.67 | 4.95 | 175.72 | 455.57 | 9.19 | 0.00 | 0.00 | 0.00 |
October | 235.29 | 35.70 | 199.59 | 546.83 | 14.27 | 0.00 | 0.00 | 0.00 |
November | 310.57 | 95.95 | 214.61 | 681.23 | 28.26 | 0.00 | 0.00 | 0.00 |
December | 380.24 | 162.30 | 217.94 | 804.91 | 61.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 237.60 | 49.34 | 188.26 | 568.05 | 22.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 163.46 | 0.00 | 163.46 | 413.48 | 2.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 380.24 | 162.30 | 221.13 | 815.68 | 61.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1066.99 | 444.32 | 622.68 | 2288.06 | 154.03 | 0.00 | 0.00 | 0.00 |
February | 902.57 | 291.08 | 611.49 | 2073.04 | 111.04 | 0.00 | 0.00 | 0.00 |
March | 629.40 | 93.41 | 535.99 | 1612.67 | 57.16 | 0.00 | 0.00 | 0.00 |
April | 466.60 | 2.69 | 463.91 | 1312.41 | 9.87 | 0.00 | 0.00 | 0.00 |
May | 461.95 | 0.00 | 461.95 | 1348.75 | 21.79 | 0.00 | 0.00 | 0.00 |
June | 460.29 | 0.00 | 460.29 | 1318.29 | 22.74 | 0.00 | 0.00 | 0.00 |
July | 474.16 | 0.00 | 474.16 | 1198.55 | 52.99 | 0.00 | 0.00 | 0.00 |
August | 461.03 | 0.04 | 460.99 | 1175.68 | 29.46 | 0.00 | 0.00 | 0.00 |
September | 508.76 | 13.94 | 494.81 | 1299.28 | 33.40 | 0.00 | 0.00 | 0.00 |
October | 662.57 | 100.54 | 562.03 | 1542.16 | 50.91 | 0.00 | 0.00 | 0.00 |
November | 874.53 | 270.20 | 604.34 | 1916.33 | 87.82 | 0.00 | 0.00 | 0.00 |
December | 1070.73 | 457.02 | 613.71 | 2256.91 | 179.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 669.07 | 138.93 | 530.13 | 1609.70 | 67.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 460.29 | 0.00 | 460.29 | 1175.68 | 9.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1070.73 | 457.02 | 622.68 | 2288.06 | 179.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1386.08 | 577.19 | 808.89 | 3107.42 | 173.42 | 0.00 | 0.00 | 0.00 |
February | 1172.49 | 378.13 | 794.36 | 2822.02 | 123.40 | 0.00 | 0.00 | 0.00 |
March | 817.62 | 121.34 | 696.28 | 2199.57 | 59.80 | 0.00 | 0.00 | 0.00 |
April | 606.13 | 3.49 | 602.65 | 1782.76 | 11.57 | 0.00 | 0.00 | 0.00 |
May | 600.10 | 0.00 | 600.10 | 1806.49 | 26.36 | 0.00 | 0.00 | 0.00 |
June | 597.94 | 0.00 | 597.94 | 1752.10 | 30.03 | 0.00 | 0.00 | 0.00 |
July | 615.96 | 0.00 | 615.96 | 1590.99 | 66.88 | 0.00 | 0.00 | 0.00 |
August | 598.91 | 0.05 | 598.85 | 1572.75 | 34.34 | 0.00 | 0.00 | 0.00 |
September | 660.90 | 18.11 | 642.79 | 1758.46 | 35.34 | 0.00 | 0.00 | 0.00 |
October | 860.71 | 130.60 | 730.11 | 2090.72 | 49.58 | 0.00 | 0.00 | 0.00 |
November | 1136.07 | 351.00 | 785.07 | 2604.60 | 94.33 | 0.00 | 0.00 | 0.00 |
December | 1390.94 | 593.70 | 797.25 | 3060.51 | 205.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 869.15 | 180.48 | 688.67 | 2175.99 | 75.88 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 597.94 | 0.00 | 597.94 | 1572.75 | 11.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1390.94 | 593.70 | 808.89 | 3107.42 | 205.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.92 | 31.20 | 43.72 | 175.06 | 3.82 | 0.00 | 0.00 | 0.00 |
February | 63.37 | 20.44 | 42.94 | 161.20 | 1.33 | 0.00 | 0.00 | 0.00 |
March | 44.19 | 6.56 | 37.63 | 131.15 | 0.25 | 0.00 | 0.00 | 0.00 |
April | 32.76 | 0.19 | 32.57 | 111.54 | 0.01 | 0.00 | 0.00 | 0.00 |
May | 32.44 | 0.00 | 32.44 | 113.26 | 0.04 | 0.00 | 0.00 | 0.00 |
June | 32.32 | 0.00 | 32.32 | 111.15 | 0.06 | 0.00 | 0.00 | 0.00 |
July | 33.29 | 0.00 | 33.29 | 97.51 | 0.12 | 0.00 | 0.00 | 0.00 |
August | 32.37 | 0.00 | 32.37 | 97.55 | 0.05 | 0.00 | 0.00 | 0.00 |
September | 35.72 | 0.98 | 34.74 | 106.64 | 0.03 | 0.00 | 0.00 | 0.00 |
October | 46.52 | 7.06 | 39.46 | 122.66 | 0.09 | 0.00 | 0.00 | 0.00 |
November | 61.40 | 18.97 | 42.43 | 148.99 | 0.76 | 0.00 | 0.00 | 0.00 |
December | 75.18 | 32.09 | 43.09 | 171.51 | 4.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 46.98 | 9.75 | 37.22 | 128.86 | 0.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 32.32 | 0.00 | 32.32 | 97.51 | 0.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 75.18 | 32.09 | 43.72 | 175.06 | 4.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 103.46 | 36.45 | 67.02 | 246.92 | 7.37 | 0.00 | 0.00 | 0.00 |
February | 113.56 | 40.22 | 73.33 | 276.16 | 2.54 | 0.00 | 0.00 | 0.00 |
March | 127.08 | 50.13 | 76.95 | 319.10 | 0.43 | 0.00 | 0.00 | 0.00 |
April | 127.73 | 48.84 | 78.88 | 335.85 | 0.02 | 0.00 | 0.00 | 0.00 |
May | 108.87 | 32.31 | 76.56 | 303.98 | 0.06 | 0.00 | 0.00 | 0.00 |
June | 117.86 | 40.60 | 77.25 | 318.29 | 0.09 | 0.00 | 0.00 | 0.00 |
July | 100.47 | 23.65 | 76.82 | 257.11 | 0.21 | 0.00 | 0.00 | 0.00 |
August | 109.58 | 32.57 | 77.01 | 275.68 | 0.08 | 0.00 | 0.00 | 0.00 |
September | 102.29 | 28.34 | 73.95 | 265.32 | 0.05 | 0.00 | 0.00 | 0.00 |
October | 96.18 | 24.83 | 71.35 | 238.83 | 0.20 | 0.00 | 0.00 | 0.00 |
November | 93.78 | 25.61 | 68.17 | 229.42 | 1.53 | 0.00 | 0.00 | 0.00 |
December | 96.06 | 31.48 | 64.58 | 227.77 | 9.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 108.00 | 34.53 | 73.48 | 274.38 | 1.85 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 93.78 | 23.65 | 64.58 | 227.77 | 0.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 127.73 | 50.13 | 78.88 | 335.85 | 9.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.34 | 0.00 | 28.34 | 78.80 | 3.87 | 0.00 | 0.00 | 0.00 |
February | 30.23 | 0.00 | 30.23 | 87.83 | 1.32 | 0.00 | 0.00 | 0.00 |
March | 31.04 | 0.00 | 31.04 | 99.38 | 0.23 | 0.00 | 0.00 | 0.00 |
April | 34.40 | 0.83 | 33.57 | 115.45 | 0.01 | 0.00 | 0.00 | 0.00 |
May | 43.16 | 4.50 | 38.67 | 137.70 | 0.09 | 0.00 | 0.00 | 0.00 |
June | 53.04 | 10.85 | 42.18 | 157.67 | 0.14 | 0.00 | 0.00 | 0.00 |
July | 45.54 | 4.83 | 40.71 | 124.93 | 0.24 | 0.00 | 0.00 | 0.00 |
August | 37.65 | 1.77 | 35.89 | 109.41 | 0.09 | 0.00 | 0.00 | 0.00 |
September | 31.94 | 0.06 | 31.89 | 97.94 | 0.11 | 0.00 | 0.00 | 0.00 |
October | 30.70 | 0.00 | 30.70 | 87.95 | 0.16 | 0.00 | 0.00 | 0.00 |
November | 29.05 | 0.00 | 29.05 | 81.79 | 1.06 | 0.00 | 0.00 | 0.00 |
December | 27.53 | 0.00 | 27.53 | 74.49 | 5.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 35.24 | 1.91 | 33.33 | 104.48 | 1.04 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 27.53 | 0.00 | 27.53 | 74.49 | 0.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 53.04 | 10.85 | 42.18 | 157.67 | 5.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 103.46 | 36.45 | 67.02 | 247.81 | 7.11 | 0.00 | 0.00 | 0.00 |
February | 113.56 | 40.22 | 73.33 | 276.80 | 2.40 | 0.00 | 0.00 | 0.00 |
March | 127.08 | 50.13 | 76.95 | 320.04 | 0.40 | 0.00 | 0.00 | 0.00 |
April | 127.73 | 48.84 | 78.88 | 335.60 | 0.02 | 0.00 | 0.00 | 0.00 |
May | 108.87 | 32.31 | 76.56 | 303.05 | 0.17 | 0.00 | 0.00 | 0.00 |
June | 117.86 | 40.60 | 77.25 | 316.41 | 0.26 | 0.00 | 0.00 | 0.00 |
July | 100.47 | 23.65 | 76.82 | 255.86 | 0.44 | 0.00 | 0.00 | 0.00 |
August | 109.58 | 32.57 | 77.01 | 274.97 | 0.17 | 0.00 | 0.00 | 0.00 |
September | 102.29 | 28.34 | 73.95 | 265.26 | 0.18 | 0.00 | 0.00 | 0.00 |
October | 96.18 | 24.83 | 71.35 | 239.50 | 0.27 | 0.00 | 0.00 | 0.00 |
November | 93.78 | 25.61 | 68.17 | 230.55 | 1.92 | 0.00 | 0.00 | 0.00 |
December | 96.06 | 31.48 | 64.58 | 228.51 | 9.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 108.00 | 34.53 | 73.48 | 274.38 | 1.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 93.78 | 23.65 | 64.58 | 228.51 | 0.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 127.73 | 50.13 | 78.88 | 335.60 | 9.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 59.92 | 24.95 | 34.97 | 119.02 | 17.76 | 0.00 | 0.00 | 0.00 |
February | 50.69 | 16.35 | 34.34 | 107.50 | 14.49 | 0.00 | 0.00 | 0.00 |
March | 35.35 | 5.25 | 30.10 | 80.29 | 10.91 | 0.00 | 0.00 | 0.00 |
April | 26.20 | 0.15 | 26.05 | 60.39 | 5.78 | 0.00 | 0.00 | 0.00 |
May | 25.94 | 0.00 | 25.94 | 61.32 | 6.44 | 0.00 | 0.00 | 0.00 |
June | 25.85 | 0.00 | 25.85 | 60.77 | 6.77 | 0.00 | 0.00 | 0.00 |
July | 26.63 | 0.00 | 26.63 | 54.40 | 11.00 | 0.00 | 0.00 | 0.00 |
August | 25.89 | 0.00 | 25.89 | 52.19 | 9.99 | 0.00 | 0.00 | 0.00 |
September | 28.57 | 0.78 | 27.79 | 60.38 | 9.95 | 0.00 | 0.00 | 0.00 |
October | 37.21 | 5.65 | 31.56 | 74.14 | 12.37 | 0.00 | 0.00 | 0.00 |
November | 49.11 | 15.17 | 33.94 | 97.25 | 14.11 | 0.00 | 0.00 | 0.00 |
December | 60.13 | 25.67 | 34.47 | 117.65 | 19.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 37.57 | 7.80 | 29.77 | 78.64 | 11.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.85 | 0.00 | 25.85 | 52.19 | 5.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 60.13 | 25.67 | 34.97 | 119.02 | 19.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.67 | 0.00 | 22.67 | 67.74 | 2.30 | 0.00 | 0.00 | 0.00 |
February | 24.18 | 0.00 | 24.18 | 75.88 | 0.47 | 0.00 | 0.00 | 0.00 |
March | 24.84 | 0.00 | 24.84 | 86.09 | 0.07 | 0.00 | 0.00 | 0.00 |
April | 27.53 | 0.66 | 26.86 | 98.99 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 34.53 | 3.60 | 30.94 | 116.04 | 0.02 | 0.00 | 0.00 | 0.00 |
June | 42.43 | 8.68 | 33.75 | 132.03 | 0.04 | 0.00 | 0.00 | 0.00 |
July | 36.43 | 3.87 | 32.57 | 104.90 | 0.06 | 0.00 | 0.00 | 0.00 |
August | 30.13 | 1.41 | 28.71 | 92.99 | 0.01 | 0.00 | 0.00 | 0.00 |
September | 25.56 | 0.04 | 25.51 | 83.85 | 0.02 | 0.00 | 0.00 | 0.00 |
October | 24.57 | 0.00 | 24.57 | 75.54 | 0.01 | 0.00 | 0.00 | 0.00 |
November | 23.24 | 0.00 | 23.24 | 70.26 | 0.46 | 0.00 | 0.00 | 0.00 |
December | 22.03 | 0.00 | 22.03 | 63.78 | 3.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 28.19 | 1.53 | 26.67 | 89.04 | 0.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.03 | 0.00 | 22.03 | 63.78 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 42.43 | 8.68 | 33.75 | 132.03 | 3.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.99 | 34.38 | 67.60 | 244.36 | 6.99 | 0.00 | 0.00 | 0.00 |
February | 115.59 | 42.34 | 73.25 | 281.59 | 2.43 | 0.00 | 0.00 | 0.00 |
March | 126.21 | 49.40 | 76.81 | 318.65 | 0.42 | 0.00 | 0.00 | 0.00 |
April | 127.32 | 48.57 | 78.75 | 338.37 | 0.01 | 0.00 | 0.00 | 0.00 |
May | 109.60 | 33.22 | 76.38 | 307.88 | 0.05 | 0.00 | 0.00 | 0.00 |
June | 116.66 | 38.41 | 78.25 | 318.43 | 0.07 | 0.00 | 0.00 | 0.00 |
July | 99.77 | 22.40 | 77.37 | 257.07 | 0.16 | 0.00 | 0.00 | 0.00 |
August | 109.67 | 32.24 | 77.43 | 277.62 | 0.06 | 0.00 | 0.00 | 0.00 |
September | 103.03 | 28.10 | 74.93 | 269.10 | 0.05 | 0.00 | 0.00 | 0.00 |
October | 96.67 | 24.80 | 71.86 | 241.44 | 0.16 | 0.00 | 0.00 | 0.00 |
November | 93.58 | 25.89 | 67.69 | 230.06 | 1.43 | 0.00 | 0.00 | 0.00 |
December | 95.66 | 30.72 | 64.93 | 226.66 | 8.97 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 107.89 | 34.13 | 73.76 | 275.75 | 1.74 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 93.58 | 22.40 | 64.93 | 226.66 | 0.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 127.32 | 49.40 | 78.75 | 338.37 | 8.97 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.92 | 31.20 | 43.72 | 174.88 | 3.72 | 0.00 | 0.00 | 0.00 |
February | 63.37 | 20.44 | 42.94 | 160.97 | 1.27 | 0.00 | 0.00 | 0.00 |
March | 44.19 | 6.56 | 37.63 | 131.07 | 0.22 | 0.00 | 0.00 | 0.00 |
April | 32.76 | 0.19 | 32.57 | 111.37 | 0.01 | 0.00 | 0.00 | 0.00 |
May | 32.44 | 0.00 | 32.44 | 113.10 | 0.03 | 0.00 | 0.00 | 0.00 |
June | 32.32 | 0.00 | 32.32 | 111.00 | 0.04 | 0.00 | 0.00 | 0.00 |
July | 33.29 | 0.00 | 33.29 | 97.38 | 0.10 | 0.00 | 0.00 | 0.00 |
August | 32.37 | 0.00 | 32.37 | 97.35 | 0.04 | 0.00 | 0.00 | 0.00 |
September | 35.72 | 0.98 | 34.74 | 106.46 | 0.02 | 0.00 | 0.00 | 0.00 |
October | 46.52 | 7.06 | 39.46 | 122.55 | 0.08 | 0.00 | 0.00 | 0.00 |
November | 61.40 | 18.97 | 42.43 | 148.89 | 0.75 | 0.00 | 0.00 | 0.00 |
December | 75.18 | 32.09 | 43.09 | 171.33 | 4.76 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 46.98 | 9.75 | 37.22 | 128.70 | 0.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 32.32 | 0.00 | 32.32 | 97.35 | 0.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 75.18 | 32.09 | 43.72 | 174.88 | 4.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.34 | 0.00 | 28.34 | 78.22 | 3.79 | 0.00 | 0.00 | 0.00 |
February | 30.23 | 0.00 | 30.23 | 87.28 | 1.27 | 0.00 | 0.00 | 0.00 |
March | 31.04 | 0.00 | 31.04 | 99.25 | 0.21 | 0.00 | 0.00 | 0.00 |
April | 34.40 | 0.83 | 33.57 | 115.28 | 0.01 | 0.00 | 0.00 | 0.00 |
May | 43.16 | 4.50 | 38.67 | 137.55 | 0.08 | 0.00 | 0.00 | 0.00 |
June | 53.04 | 10.85 | 42.18 | 157.54 | 0.12 | 0.00 | 0.00 | 0.00 |
July | 45.54 | 4.83 | 40.71 | 124.80 | 0.21 | 0.00 | 0.00 | 0.00 |
August | 37.65 | 1.77 | 35.89 | 109.23 | 0.08 | 0.00 | 0.00 | 0.00 |
September | 31.94 | 0.06 | 31.89 | 97.76 | 0.09 | 0.00 | 0.00 | 0.00 |
October | 30.70 | 0.00 | 30.70 | 87.81 | 0.15 | 0.00 | 0.00 | 0.00 |
November | 29.05 | 0.00 | 29.05 | 81.56 | 1.05 | 0.00 | 0.00 | 0.00 |
December | 27.53 | 0.00 | 27.53 | 73.93 | 4.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 35.24 | 1.91 | 33.33 | 104.23 | 1.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 27.53 | 0.00 | 27.53 | 73.93 | 0.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 53.04 | 10.85 | 42.18 | 157.54 | 4.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.99 | 34.38 | 67.60 | 244.17 | 6.71 | 0.00 | 0.00 | 0.00 |
February | 115.59 | 42.34 | 73.25 | 281.33 | 2.27 | 0.00 | 0.00 | 0.00 |
March | 126.21 | 49.40 | 76.81 | 319.51 | 0.39 | 0.00 | 0.00 | 0.00 |
April | 127.32 | 48.57 | 78.75 | 338.14 | 0.01 | 0.00 | 0.00 | 0.00 |
May | 109.60 | 33.22 | 76.38 | 306.96 | 0.14 | 0.00 | 0.00 | 0.00 |
June | 116.66 | 38.41 | 78.25 | 316.56 | 0.22 | 0.00 | 0.00 | 0.00 |
July | 99.77 | 22.40 | 77.37 | 255.82 | 0.38 | 0.00 | 0.00 | 0.00 |
August | 109.67 | 32.24 | 77.43 | 276.93 | 0.14 | 0.00 | 0.00 | 0.00 |
September | 103.03 | 28.10 | 74.93 | 269.03 | 0.16 | 0.00 | 0.00 | 0.00 |
October | 96.67 | 24.80 | 71.86 | 242.07 | 0.25 | 0.00 | 0.00 | 0.00 |
November | 93.58 | 25.89 | 67.69 | 230.89 | 1.82 | 0.00 | 0.00 | 0.00 |
December | 95.66 | 30.72 | 64.93 | 226.44 | 8.80 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 107.89 | 34.13 | 73.76 | 275.46 | 1.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 93.58 | 22.40 | 64.93 | 226.44 | 0.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 127.32 | 49.40 | 78.75 | 338.14 | 8.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.89 | 0.00 | 35.89 | 96.71 | 8.53 | 0.00 | 0.00 | 0.00 |
February | 38.28 | 0.00 | 38.28 | 106.56 | 5.06 | 0.00 | 0.00 | 0.00 |
March | 39.31 | 0.00 | 39.31 | 119.87 | 1.53 | 0.00 | 0.00 | 0.00 |
April | 43.57 | 1.05 | 42.52 | 139.98 | 0.20 | 0.00 | 0.00 | 0.00 |
May | 54.66 | 5.69 | 48.97 | 166.60 | 0.61 | 0.00 | 0.00 | 0.00 |
June | 67.17 | 13.75 | 53.42 | 190.46 | 0.75 | 0.00 | 0.00 | 0.00 |
July | 57.67 | 6.12 | 51.55 | 153.47 | 1.35 | 0.00 | 0.00 | 0.00 |
August | 47.69 | 2.24 | 45.45 | 134.47 | 0.50 | 0.00 | 0.00 | 0.00 |
September | 40.45 | 0.07 | 40.38 | 120.07 | 0.60 | 0.00 | 0.00 | 0.00 |
October | 38.88 | 0.00 | 38.88 | 107.11 | 1.00 | 0.00 | 0.00 | 0.00 |
November | 36.79 | 0.00 | 36.79 | 99.27 | 3.37 | 0.00 | 0.00 | 0.00 |
December | 34.86 | 0.00 | 34.86 | 91.92 | 10.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 44.63 | 2.42 | 42.21 | 127.27 | 2.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.86 | 0.00 | 34.86 | 91.92 | 0.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.17 | 13.75 | 53.42 | 190.46 | 10.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.23 | 0.00 | 13.23 | 35.65 | 3.14 | 0.00 | 0.00 | 0.00 |
February | 14.11 | 0.00 | 14.11 | 39.28 | 1.87 | 0.00 | 0.00 | 0.00 |
March | 14.49 | 0.00 | 14.49 | 44.19 | 0.57 | 0.00 | 0.00 | 0.00 |
April | 16.06 | 0.39 | 15.67 | 51.60 | 0.07 | 0.00 | 0.00 | 0.00 |
May | 20.15 | 2.10 | 18.05 | 61.41 | 0.22 | 0.00 | 0.00 | 0.00 |
June | 24.76 | 5.07 | 19.69 | 70.21 | 0.28 | 0.00 | 0.00 | 0.00 |
July | 21.26 | 2.26 | 19.00 | 56.57 | 0.50 | 0.00 | 0.00 | 0.00 |
August | 17.58 | 0.83 | 16.75 | 49.57 | 0.18 | 0.00 | 0.00 | 0.00 |
September | 14.91 | 0.03 | 14.89 | 44.26 | 0.22 | 0.00 | 0.00 | 0.00 |
October | 14.33 | 0.00 | 14.33 | 39.49 | 0.37 | 0.00 | 0.00 | 0.00 |
November | 13.56 | 0.00 | 13.56 | 36.60 | 1.24 | 0.00 | 0.00 | 0.00 |
December | 12.85 | 0.00 | 12.85 | 33.89 | 3.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 16.45 | 0.89 | 15.56 | 46.92 | 1.04 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 12.85 | 0.00 | 12.85 | 33.89 | 0.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 24.76 | 5.07 | 19.69 | 70.21 | 3.83 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.96 | 14.56 | 20.40 | 80.60 | 2.99 | 0.00 | 0.00 | 0.00 |
February | 29.57 | 9.54 | 20.03 | 73.48 | 1.79 | 0.00 | 0.00 | 0.00 |
March | 20.62 | 3.06 | 17.56 | 59.15 | 0.56 | 0.00 | 0.00 | 0.00 |
April | 15.29 | 0.09 | 15.20 | 49.70 | 0.07 | 0.00 | 0.00 | 0.00 |
May | 15.13 | 0.00 | 15.13 | 49.78 | 0.23 | 0.00 | 0.00 | 0.00 |
June | 15.08 | 0.00 | 15.08 | 48.05 | 0.28 | 0.00 | 0.00 | 0.00 |
July | 15.53 | 0.00 | 15.53 | 43.49 | 0.51 | 0.00 | 0.00 | 0.00 |
August | 15.10 | 0.00 | 15.10 | 43.86 | 0.19 | 0.00 | 0.00 | 0.00 |
September | 16.67 | 0.46 | 16.21 | 48.27 | 0.21 | 0.00 | 0.00 | 0.00 |
October | 21.71 | 3.29 | 18.41 | 55.76 | 0.34 | 0.00 | 0.00 | 0.00 |
November | 28.65 | 8.85 | 19.80 | 68.09 | 1.17 | 0.00 | 0.00 | 0.00 |
December | 35.08 | 14.97 | 20.11 | 79.16 | 3.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 21.92 | 4.55 | 17.37 | 58.21 | 1.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 15.08 | 0.00 | 15.08 | 43.49 | 0.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 35.08 | 14.97 | 20.40 | 80.60 | 3.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 94.88 | 39.51 | 55.37 | 218.76 | 8.11 | 0.00 | 0.00 | 0.00 |
February | 80.26 | 25.88 | 54.38 | 199.44 | 4.85 | 0.00 | 0.00 | 0.00 |
March | 55.97 | 8.31 | 47.66 | 160.55 | 1.53 | 0.00 | 0.00 | 0.00 |
April | 41.49 | 0.24 | 41.25 | 134.91 | 0.19 | 0.00 | 0.00 | 0.00 |
May | 41.08 | 0.00 | 41.08 | 135.10 | 0.62 | 0.00 | 0.00 | 0.00 |
June | 40.93 | 0.00 | 40.93 | 130.43 | 0.77 | 0.00 | 0.00 | 0.00 |
July | 42.16 | 0.00 | 42.16 | 118.03 | 1.38 | 0.00 | 0.00 | 0.00 |
August | 41.00 | 0.00 | 40.99 | 119.04 | 0.51 | 0.00 | 0.00 | 0.00 |
September | 45.24 | 1.24 | 44.00 | 131.00 | 0.56 | 0.00 | 0.00 | 0.00 |
October | 58.92 | 8.94 | 49.98 | 151.33 | 0.93 | 0.00 | 0.00 | 0.00 |
November | 77.76 | 24.03 | 53.74 | 184.80 | 3.17 | 0.00 | 0.00 | 0.00 |
December | 95.21 | 40.64 | 54.57 | 214.86 | 9.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 59.49 | 12.35 | 47.14 | 157.99 | 2.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 40.93 | 0.00 | 40.93 | 118.03 | 0.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 95.21 | 40.64 | 55.37 | 218.76 | 9.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.92 | 31.20 | 43.72 | 173.67 | 3.21 | 0.00 | 0.00 | 0.00 |
February | 63.37 | 20.44 | 42.94 | 160.28 | 0.88 | 0.00 | 0.00 | 0.00 |
March | 44.19 | 6.56 | 37.63 | 130.99 | 0.12 | 0.00 | 0.00 | 0.00 |
April | 32.76 | 0.19 | 32.57 | 111.52 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 32.44 | 0.00 | 32.44 | 113.22 | 0.02 | 0.00 | 0.00 | 0.00 |
June | 32.32 | 0.00 | 32.32 | 111.30 | 0.03 | 0.00 | 0.00 | 0.00 |
July | 33.29 | 0.00 | 33.29 | 97.01 | 0.07 | 0.00 | 0.00 | 0.00 |
August | 32.37 | 0.00 | 32.37 | 97.24 | 0.03 | 0.00 | 0.00 | 0.00 |
September | 35.72 | 0.98 | 34.74 | 105.90 | 0.01 | 0.00 | 0.00 | 0.00 |
October | 46.52 | 7.06 | 39.46 | 121.73 | 0.04 | 0.00 | 0.00 | 0.00 |
November | 61.40 | 18.97 | 42.43 | 147.85 | 0.52 | 0.00 | 0.00 | 0.00 |
December | 75.18 | 32.09 | 43.09 | 169.96 | 4.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 46.98 | 9.75 | 37.22 | 128.23 | 0.76 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 32.32 | 0.00 | 32.32 | 97.01 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 75.18 | 32.09 | 43.72 | 173.67 | 4.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 103.46 | 36.45 | 67.02 | 244.68 | 6.17 | 0.00 | 0.00 | 0.00 |
February | 113.56 | 40.22 | 73.33 | 274.37 | 1.68 | 0.00 | 0.00 | 0.00 |
March | 127.08 | 50.13 | 76.95 | 317.66 | 0.22 | 0.00 | 0.00 | 0.00 |
April | 127.73 | 48.84 | 78.88 | 334.20 | 0.01 | 0.00 | 0.00 | 0.00 |
May | 108.87 | 32.31 | 76.56 | 302.83 | 0.04 | 0.00 | 0.00 | 0.00 |
June | 117.86 | 40.60 | 77.25 | 317.33 | 0.05 | 0.00 | 0.00 | 0.00 |
July | 100.47 | 23.65 | 76.82 | 255.34 | 0.11 | 0.00 | 0.00 | 0.00 |
August | 109.58 | 32.57 | 77.01 | 274.08 | 0.04 | 0.00 | 0.00 | 0.00 |
September | 102.29 | 28.34 | 73.95 | 263.29 | 0.01 | 0.00 | 0.00 | 0.00 |
October | 96.18 | 24.83 | 71.35 | 237.02 | 0.09 | 0.00 | 0.00 | 0.00 |
November | 93.78 | 25.61 | 68.17 | 227.61 | 1.03 | 0.00 | 0.00 | 0.00 |
December | 96.06 | 31.48 | 64.58 | 225.33 | 8.02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 108.00 | 34.53 | 73.48 | 272.66 | 1.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 93.78 | 23.65 | 64.58 | 225.33 | 0.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 127.73 | 50.13 | 78.88 | 334.20 | 8.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.34 | 0.00 | 28.34 | 78.16 | 3.23 | 0.00 | 0.00 | 0.00 |
February | 30.23 | 0.00 | 30.23 | 87.48 | 0.87 | 0.00 | 0.00 | 0.00 |
March | 31.04 | 0.00 | 31.04 | 99.24 | 0.12 | 0.00 | 0.00 | 0.00 |
April | 34.40 | 0.83 | 33.57 | 115.05 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 43.16 | 4.50 | 38.67 | 137.18 | 0.09 | 0.00 | 0.00 | 0.00 |
June | 53.04 | 10.85 | 42.18 | 157.04 | 0.13 | 0.00 | 0.00 | 0.00 |
July | 45.54 | 4.83 | 40.71 | 124.03 | 0.21 | 0.00 | 0.00 | 0.00 |
August | 37.65 | 1.77 | 35.89 | 108.78 | 0.09 | 0.00 | 0.00 | 0.00 |
September | 31.94 | 0.06 | 31.89 | 97.22 | 0.12 | 0.00 | 0.00 | 0.00 |
October | 30.70 | 0.00 | 30.70 | 87.35 | 0.14 | 0.00 | 0.00 | 0.00 |
November | 29.05 | 0.00 | 29.05 | 81.25 | 0.85 | 0.00 | 0.00 | 0.00 |
December | 27.53 | 0.00 | 27.53 | 73.74 | 4.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 35.24 | 1.91 | 33.33 | 103.92 | 0.85 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 27.53 | 0.00 | 27.53 | 73.74 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 53.04 | 10.85 | 42.18 | 157.04 | 4.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 103.46 | 36.45 | 67.02 | 245.85 | 5.92 | 0.00 | 0.00 | 0.00 |
February | 113.56 | 40.22 | 73.33 | 275.23 | 1.55 | 0.00 | 0.00 | 0.00 |
March | 127.08 | 50.13 | 76.95 | 318.65 | 0.22 | 0.00 | 0.00 | 0.00 |
April | 127.73 | 48.84 | 78.88 | 333.91 | 0.01 | 0.00 | 0.00 | 0.00 |
May | 108.87 | 32.31 | 76.56 | 301.86 | 0.16 | 0.00 | 0.00 | 0.00 |
June | 117.86 | 40.60 | 77.25 | 315.40 | 0.24 | 0.00 | 0.00 | 0.00 |
July | 100.47 | 23.65 | 76.82 | 254.05 | 0.39 | 0.00 | 0.00 | 0.00 |
August | 109.58 | 32.57 | 77.01 | 273.34 | 0.15 | 0.00 | 0.00 | 0.00 |
September | 102.29 | 28.34 | 73.95 | 263.21 | 0.21 | 0.00 | 0.00 | 0.00 |
October | 96.18 | 24.83 | 71.35 | 237.70 | 0.24 | 0.00 | 0.00 | 0.00 |
November | 93.78 | 25.61 | 68.17 | 228.91 | 1.54 | 0.00 | 0.00 | 0.00 |
December | 96.06 | 31.48 | 64.58 | 226.40 | 7.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 108.00 | 34.53 | 73.48 | 272.72 | 1.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 93.78 | 23.65 | 64.58 | 226.40 | 0.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 127.73 | 50.13 | 78.88 | 333.91 | 7.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 109.87 | 45.75 | 64.12 | 256.21 | 4.43 | 0.00 | 0.00 | 0.00 |
February | 92.94 | 29.97 | 62.97 | 238.08 | 1.03 | 0.00 | 0.00 | 0.00 |
March | 64.81 | 9.62 | 55.19 | 197.73 | 0.13 | 0.00 | 0.00 | 0.00 |
April | 48.05 | 0.28 | 47.77 | 170.59 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 47.57 | 0.00 | 47.57 | 172.13 | 0.02 | 0.00 | 0.00 | 0.00 |
June | 47.40 | 0.00 | 47.40 | 169.77 | 0.01 | 0.00 | 0.00 | 0.00 |
July | 48.83 | 0.00 | 48.83 | 147.43 | 0.03 | 0.00 | 0.00 | 0.00 |
August | 47.48 | 0.00 | 47.47 | 148.28 | 0.01 | 0.00 | 0.00 | 0.00 |
September | 52.39 | 1.44 | 50.95 | 160.35 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 68.23 | 10.35 | 57.88 | 182.04 | 0.03 | 0.00 | 0.00 | 0.00 |
November | 90.06 | 27.82 | 62.23 | 219.04 | 0.61 | 0.00 | 0.00 | 0.00 |
December | 110.26 | 47.06 | 63.20 | 250.31 | 5.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 68.90 | 14.31 | 54.59 | 192.43 | 1.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 47.40 | 0.00 | 47.40 | 147.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 110.26 | 47.06 | 64.12 | 256.21 | 5.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 198.34 | 0.00 | 198.34 | 491.80 | 72.34 | 0.00 | 0.00 | 0.00 |
February | 211.58 | 0.00 | 211.58 | 549.90 | 48.63 | 0.00 | 0.00 | 0.00 |
March | 217.29 | 0.01 | 217.28 | 601.39 | 23.44 | 0.00 | 0.00 | 0.00 |
April | 240.82 | 5.80 | 235.01 | 693.85 | 5.59 | 0.00 | 0.00 | 0.00 |
May | 302.12 | 31.47 | 270.65 | 846.49 | 12.29 | 0.00 | 0.00 | 0.00 |
June | 371.24 | 75.98 | 295.26 | 986.37 | 13.12 | 0.00 | 0.00 | 0.00 |
July | 318.75 | 33.82 | 284.93 | 778.29 | 28.46 | 0.00 | 0.00 | 0.00 |
August | 263.57 | 12.38 | 251.20 | 661.49 | 17.25 | 0.00 | 0.00 | 0.00 |
September | 223.59 | 0.39 | 223.20 | 587.34 | 18.74 | 0.00 | 0.00 | 0.00 |
October | 214.91 | 0.00 | 214.91 | 525.22 | 28.00 | 0.00 | 0.00 | 0.00 |
November | 203.35 | 0.00 | 203.35 | 499.52 | 41.99 | 0.00 | 0.00 | 0.00 |
December | 192.69 | 0.00 | 192.69 | 470.35 | 86.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 246.66 | 13.35 | 233.31 | 641.19 | 33.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 192.69 | 0.00 | 192.69 | 470.35 | 5.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 371.24 | 75.98 | 295.26 | 986.37 | 86.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 198.34 | 0.00 | 198.34 | 480.38 | 77.96 | 0.00 | 0.00 | 0.00 |
February | 211.58 | 0.00 | 211.58 | 538.61 | 53.26 | 0.00 | 0.00 | 0.00 |
March | 217.29 | 0.01 | 217.28 | 588.42 | 27.22 | 0.00 | 0.00 | 0.00 |
April | 240.82 | 5.80 | 235.01 | 678.60 | 6.79 | 0.00 | 0.00 | 0.00 |
May | 302.12 | 31.47 | 270.65 | 832.13 | 14.49 | 0.00 | 0.00 | 0.00 |
June | 371.24 | 75.98 | 295.26 | 972.69 | 15.19 | 0.00 | 0.00 | 0.00 |
July | 318.75 | 33.82 | 284.93 | 765.11 | 32.88 | 0.00 | 0.00 | 0.00 |
August | 263.57 | 12.38 | 251.20 | 645.94 | 21.26 | 0.00 | 0.00 | 0.00 |
September | 223.59 | 0.39 | 223.20 | 573.20 | 22.81 | 0.00 | 0.00 | 0.00 |
October | 214.91 | 0.00 | 214.91 | 511.67 | 33.59 | 0.00 | 0.00 | 0.00 |
November | 203.35 | 0.00 | 203.35 | 487.54 | 47.56 | 0.00 | 0.00 | 0.00 |
December | 192.69 | 0.00 | 192.69 | 459.16 | 93.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 246.66 | 13.35 | 233.31 | 627.97 | 37.20 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 192.69 | 0.00 | 192.69 | 459.16 | 6.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 371.24 | 75.98 | 295.26 | 972.69 | 93.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.34 | 0.00 | 28.34 | 87.41 | 9.80 | 0.00 | 0.00 | 0.00 |
February | 30.23 | 0.00 | 30.23 | 95.92 | 6.71 | 0.00 | 0.00 | 0.00 |
March | 31.04 | 0.00 | 31.04 | 101.98 | 3.71 | 0.00 | 0.00 | 0.00 |
April | 34.40 | 0.83 | 33.57 | 116.09 | 1.03 | 0.00 | 0.00 | 0.00 |
May | 43.16 | 4.50 | 38.67 | 137.51 | 1.88 | 0.00 | 0.00 | 0.00 |
June | 53.04 | 10.85 | 42.18 | 159.15 | 2.02 | 0.00 | 0.00 | 0.00 |
July | 45.54 | 4.83 | 40.71 | 130.10 | 3.72 | 0.00 | 0.00 | 0.00 |
August | 37.65 | 1.77 | 35.89 | 109.50 | 2.60 | 0.00 | 0.00 | 0.00 |
September | 31.94 | 0.06 | 31.89 | 101.72 | 2.82 | 0.00 | 0.00 | 0.00 |
October | 30.70 | 0.00 | 30.70 | 90.33 | 3.87 | 0.00 | 0.00 | 0.00 |
November | 29.05 | 0.00 | 29.05 | 89.16 | 5.51 | 0.00 | 0.00 | 0.00 |
December | 27.53 | 0.00 | 27.53 | 84.60 | 11.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 35.24 | 1.91 | 33.33 | 108.64 | 4.61 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 27.53 | 0.00 | 27.53 | 84.60 | 1.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 53.04 | 10.85 | 42.18 | 159.15 | 11.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 203.96 | 68.76 | 135.19 | 521.21 | 36.45 | 0.00 | 0.00 | 0.00 |
February | 231.16 | 84.67 | 146.49 | 592.90 | 25.21 | 0.00 | 0.00 | 0.00 |
March | 252.39 | 98.79 | 153.60 | 643.80 | 13.87 | 0.00 | 0.00 | 0.00 |
April | 254.63 | 97.13 | 157.50 | 675.63 | 3.93 | 0.00 | 0.00 | 0.00 |
May | 219.18 | 66.43 | 152.76 | 610.70 | 7.15 | 0.00 | 0.00 | 0.00 |
June | 233.31 | 76.82 | 156.49 | 637.07 | 7.68 | 0.00 | 0.00 | 0.00 |
July | 199.52 | 44.79 | 154.73 | 530.87 | 14.03 | 0.00 | 0.00 | 0.00 |
August | 219.33 | 64.47 | 154.86 | 553.38 | 9.84 | 0.00 | 0.00 | 0.00 |
September | 206.05 | 56.20 | 149.85 | 551.03 | 10.63 | 0.00 | 0.00 | 0.00 |
October | 193.32 | 49.60 | 143.71 | 490.92 | 14.74 | 0.00 | 0.00 | 0.00 |
November | 187.15 | 51.78 | 135.36 | 488.00 | 20.73 | 0.00 | 0.00 | 0.00 |
December | 191.30 | 61.44 | 129.86 | 491.76 | 43.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 215.77 | 68.25 | 147.52 | 565.14 | 17.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 187.15 | 44.79 | 129.86 | 488.00 | 3.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 254.63 | 98.79 | 157.50 | 675.63 | 43.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.92 | 31.20 | 43.72 | 184.00 | 9.67 | 0.00 | 0.00 | 0.00 |
February | 63.37 | 20.44 | 42.94 | 169.30 | 6.70 | 0.00 | 0.00 | 0.00 |
March | 44.19 | 6.56 | 37.63 | 133.45 | 3.69 | 0.00 | 0.00 | 0.00 |
April | 32.76 | 0.19 | 32.57 | 111.73 | 1.04 | 0.00 | 0.00 | 0.00 |
May | 32.44 | 0.00 | 32.44 | 112.13 | 1.88 | 0.00 | 0.00 | 0.00 |
June | 32.32 | 0.00 | 32.32 | 110.89 | 2.04 | 0.00 | 0.00 | 0.00 |
July | 33.29 | 0.00 | 33.29 | 102.13 | 3.76 | 0.00 | 0.00 | 0.00 |
August | 32.37 | 0.00 | 32.37 | 96.76 | 2.61 | 0.00 | 0.00 | 0.00 |
September | 35.72 | 0.98 | 34.74 | 110.24 | 2.81 | 0.00 | 0.00 | 0.00 |
October | 46.52 | 7.06 | 39.46 | 125.16 | 3.87 | 0.00 | 0.00 | 0.00 |
November | 61.40 | 18.97 | 42.43 | 156.84 | 5.49 | 0.00 | 0.00 | 0.00 |
December | 75.18 | 32.09 | 43.09 | 182.08 | 11.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 46.98 | 9.75 | 37.22 | 132.71 | 4.59 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 32.32 | 0.00 | 32.32 | 96.76 | 1.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 75.18 | 32.09 | 43.72 | 184.00 | 11.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.89 | 0.00 | 35.89 | 89.07 | 10.84 | 0.00 | 0.00 | 0.00 |
February | 38.28 | 0.00 | 38.28 | 99.05 | 7.10 | 0.00 | 0.00 | 0.00 |
March | 39.31 | 0.00 | 39.31 | 110.28 | 2.54 | 0.00 | 0.00 | 0.00 |
April | 43.57 | 1.05 | 42.52 | 128.57 | 0.39 | 0.00 | 0.00 | 0.00 |
May | 54.66 | 5.69 | 48.97 | 157.11 | 1.15 | 0.00 | 0.00 | 0.00 |
June | 67.17 | 13.75 | 53.42 | 181.85 | 1.38 | 0.00 | 0.00 | 0.00 |
July | 57.67 | 6.12 | 51.55 | 144.70 | 2.81 | 0.00 | 0.00 | 0.00 |
August | 47.69 | 2.24 | 45.45 | 125.51 | 1.04 | 0.00 | 0.00 | 0.00 |
September | 40.45 | 0.07 | 40.38 | 109.89 | 1.40 | 0.00 | 0.00 | 0.00 |
October | 38.88 | 0.00 | 38.88 | 98.58 | 2.09 | 0.00 | 0.00 | 0.00 |
November | 36.79 | 0.00 | 36.79 | 91.53 | 5.09 | 0.00 | 0.00 | 0.00 |
December | 34.86 | 0.00 | 34.86 | 85.37 | 12.92 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 44.63 | 2.42 | 42.21 | 118.52 | 4.06 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.86 | 0.00 | 34.86 | 85.37 | 0.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.17 | 13.75 | 53.42 | 181.85 | 12.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.11 | 0.00 | 32.11 | 79.69 | 9.70 | 0.00 | 0.00 | 0.00 |
February | 34.25 | 0.00 | 34.25 | 88.62 | 6.35 | 0.00 | 0.00 | 0.00 |
March | 35.17 | 0.00 | 35.17 | 98.67 | 2.27 | 0.00 | 0.00 | 0.00 |
April | 38.98 | 0.94 | 38.04 | 115.03 | 0.35 | 0.00 | 0.00 | 0.00 |
May | 48.91 | 5.09 | 43.81 | 140.57 | 1.03 | 0.00 | 0.00 | 0.00 |
June | 60.09 | 12.30 | 47.80 | 162.70 | 1.24 | 0.00 | 0.00 | 0.00 |
July | 51.60 | 5.47 | 46.12 | 129.46 | 2.52 | 0.00 | 0.00 | 0.00 |
August | 42.67 | 2.00 | 40.66 | 112.30 | 0.93 | 0.00 | 0.00 | 0.00 |
September | 36.19 | 0.06 | 36.13 | 98.32 | 1.25 | 0.00 | 0.00 | 0.00 |
October | 34.79 | 0.00 | 34.79 | 88.20 | 1.87 | 0.00 | 0.00 | 0.00 |
November | 32.92 | 0.00 | 32.92 | 81.89 | 4.56 | 0.00 | 0.00 | 0.00 |
December | 31.19 | 0.00 | 31.19 | 76.38 | 11.56 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 39.93 | 2.16 | 37.77 | 106.04 | 3.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.19 | 0.00 | 31.19 | 76.38 | 0.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 60.09 | 12.30 | 47.80 | 162.70 | 11.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 279.69 | 116.47 | 163.22 | 619.90 | 30.62 | 0.00 | 0.00 | 0.00 |
February | 236.59 | 76.30 | 160.29 | 563.96 | 20.20 | 0.00 | 0.00 | 0.00 |
March | 164.98 | 24.49 | 140.50 | 444.43 | 7.31 | 0.00 | 0.00 | 0.00 |
April | 122.31 | 0.70 | 121.61 | 364.92 | 1.14 | 0.00 | 0.00 | 0.00 |
May | 121.09 | 0.00 | 121.09 | 371.51 | 3.47 | 0.00 | 0.00 | 0.00 |
June | 120.66 | 0.00 | 120.66 | 361.24 | 4.21 | 0.00 | 0.00 | 0.00 |
July | 124.29 | 0.00 | 124.29 | 323.23 | 8.53 | 0.00 | 0.00 | 0.00 |
August | 120.85 | 0.01 | 120.84 | 325.07 | 3.11 | 0.00 | 0.00 | 0.00 |
September | 133.36 | 3.65 | 129.71 | 355.89 | 4.15 | 0.00 | 0.00 | 0.00 |
October | 173.68 | 26.35 | 147.33 | 419.52 | 6.01 | 0.00 | 0.00 | 0.00 |
November | 229.24 | 70.83 | 158.41 | 519.96 | 14.51 | 0.00 | 0.00 | 0.00 |
December | 280.67 | 119.80 | 160.87 | 611.64 | 36.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 175.38 | 36.42 | 138.96 | 439.52 | 11.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 120.66 | 0.00 | 120.66 | 323.23 | 1.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 280.67 | 119.80 | 163.22 | 619.90 | 36.66 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.101488E+10 | 0.422614E+09 | 0.592265E+09 | 0.218472E+10 | 0.143946E+09 |
February | 0.775409E+09 | 0.250070E+09 | 0.525339E+09 | 0.178205E+10 | 98060683.94 |
March | 0.598658E+09 | 88846440.13 | 0.509811E+09 | 0.151817E+10 | 55987543.51 |
April | 0.429490E+09 | 2472579.53 | 0.427018E+09 | 0.118002E+10 | 7013914.13 |
May | 0.439386E+09 | 0.00 | 0.439386E+09 | 0.126353E+10 | 16326729.18 |
June | 0.423681E+09 | 0.00 | 0.423681E+09 | 0.118723E+10 | 18655585.16 |
July | 0.451004E+09 | 0.00 | 0.451004E+09 | 0.112364E+10 | 44271401.06 |
August | 0.438513E+09 | 36987.92 | 0.438476E+09 | 0.110747E+10 | 21046867.76 |
September | 0.468298E+09 | 12832635.36 | 0.455465E+09 | 0.118084E+10 | 23815457.58 |
October | 0.630206E+09 | 95626572.27 | 0.534580E+09 | 0.146463E+10 | 38216026.67 |
November | 0.804987E+09 | 0.248710E+09 | 0.556277E+09 | 0.176575E+10 | 73241411.04 |
December | 0.101844E+10 | 0.434702E+09 | 0.583736E+09 | 0.215587E+10 | 0.165869E+09 |
Annual Sum or Average | 0.749295E+10 | 0.155591E+10 | 0.593704E+10 | 0.179139E+11 | 0.706451E+09 |
Minimum of Months | 0.423681E+09 | 0.00 | 0.423681E+09 | 0.110747E+10 | 7013914.13 |
Maximum of Months | 0.101844E+10 | 0.434702E+09 | 0.592265E+09 | 0.218472E+10 | 0.165869E+09 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.285783E+10 | 0.119005E+10 | 0.166778E+10 | 0.612835E+10 | 0.412564E+09 |
February | 0.218350E+10 | 0.704181E+09 | 0.147932E+10 | 0.501509E+10 | 0.268617E+09 |
March | 0.168578E+10 | 0.250186E+09 | 0.143560E+10 | 0.431937E+10 | 0.153093E+09 |
April | 0.120942E+10 | 6962620.92 | 0.120245E+10 | 0.340178E+10 | 25572490.93 |
May | 0.123728E+10 | 0.00 | 0.123728E+10 | 0.361250E+10 | 58350531.60 |
June | 0.119306E+10 | 0.00 | 0.119306E+10 | 0.341702E+10 | 58953394.42 |
July | 0.127000E+10 | 0.00 | 0.127000E+10 | 0.321019E+10 | 0.141940E+09 |
August | 0.123482E+10 | 104155.55 | 0.123472E+10 | 0.314895E+10 | 78915553.82 |
September | 0.131870E+10 | 36135855.08 | 0.128256E+10 | 0.336773E+10 | 86583377.90 |
October | 0.177462E+10 | 0.269278E+09 | 0.150534E+10 | 0.413052E+10 | 0.136357E+09 |
November | 0.226679E+10 | 0.700352E+09 | 0.156644E+10 | 0.496712E+10 | 0.227623E+09 |
December | 0.286785E+10 | 0.122409E+10 | 0.164376E+10 | 0.604492E+10 | 0.480686E+09 |
Annual Sum or Average | 0.210997E+11 | 0.438134E+10 | 0.167183E+11 | 0.507635E+11 | 0.212926E+10 |
Minimum of Months | 0.119306E+10 | 0.00 | 0.119306E+10 | 0.314895E+10 | 25572490.93 |
Maximum of Months | 0.286785E+10 | 0.122409E+10 | 0.166778E+10 | 0.612835E+10 | 0.480686E+09 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.371249E+10 | 0.154595E+10 | 0.216654E+10 | 0.832291E+10 | 0.464480E+09 |
February | 0.283649E+10 | 0.914771E+09 | 0.192172E+10 | 0.682703E+10 | 0.298532E+09 |
March | 0.218993E+10 | 0.325005E+09 | 0.186492E+10 | 0.589133E+10 | 0.160180E+09 |
April | 0.157110E+10 | 9044840.82 | 0.156206E+10 | 0.462092E+10 | 29990168.97 |
May | 0.160730E+10 | 0.00 | 0.160730E+10 | 0.483849E+10 | 70591411.08 |
June | 0.154985E+10 | 0.00 | 0.154985E+10 | 0.454143E+10 | 77842349.43 |
July | 0.164980E+10 | 0.00 | 0.164980E+10 | 0.426131E+10 | 0.179123E+09 |
August | 0.160411E+10 | 135303.99 | 0.160397E+10 | 0.421245E+10 | 91965838.21 |
September | 0.171306E+10 | 46942532.26 | 0.166612E+10 | 0.455792E+10 | 91601152.16 |
October | 0.230533E+10 | 0.349808E+09 | 0.195552E+10 | 0.559977E+10 | 0.132783E+09 |
November | 0.294469E+10 | 0.909796E+09 | 0.203489E+10 | 0.675113E+10 | 0.244513E+09 |
December | 0.372551E+10 | 0.159016E+10 | 0.213534E+10 | 0.819727E+10 | 0.551375E+09 |
Annual Sum or Average | 0.274097E+11 | 0.569162E+10 | 0.217180E+11 | 0.686220E+11 | 0.239298E+10 |
Minimum of Months | 0.154985E+10 | 0.00 | 0.154985E+10 | 0.421245E+10 | 29990168.97 |
Maximum of Months | 0.372551E+10 | 0.159016E+10 | 0.216654E+10 | 0.832291E+10 | 0.551375E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200660E+09 | 83558065.46 | 0.117102E+09 | 0.468877E+09 | 10218844.53 |
February | 0.153313E+09 | 49443162.07 | 0.103869E+09 | 0.389978E+09 | 3221059.48 |
March | 0.118366E+09 | 17566467.14 | 0.100800E+09 | 0.351267E+09 | 660906.88 |
April | 84918671.58 | 488871.44 | 84429800.14 | 0.289122E+09 | 34953.33 |
May | 86875063.81 | 0.00 | 86875063.81 | 0.303346E+09 | 96992.31 |
June | 83770057.37 | 0.00 | 83770057.37 | 0.288109E+09 | 143574.18 |
July | 89172140.46 | 0.00 | 89172140.46 | 0.261181E+09 | 313636.60 |
August | 86702524.22 | 7313.15 | 86695211.08 | 0.261265E+09 | 132730.18 |
September | 92591347.20 | 2537232.41 | 90054114.79 | 0.276411E+09 | 70038.32 |
October | 0.124603E+09 | 18907015.71 | 0.105696E+09 | 0.328532E+09 | 245159.41 |
November | 0.159160E+09 | 49174278.34 | 0.109986E+09 | 0.386178E+09 | 1977623.79 |
December | 0.201363E+09 | 85948028.30 | 0.115415E+09 | 0.459380E+09 | 13069929.45 |
Annual Sum or Average | 0.148150E+10 | 0.307630E+09 | 0.117387E+10 | 0.406365E+10 | 30185448.47 |
Minimum of Months | 83770057.37 | 0.00 | 83770057.37 | 0.261181E+09 | 34953.33 |
Maximum of Months | 0.201363E+09 | 85948028.30 | 0.117102E+09 | 0.468877E+09 | 13069929.45 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.277116E+09 | 97620505.06 | 0.179496E+09 | 0.661346E+09 | 19732925.34 |
February | 0.274714E+09 | 97306347.91 | 0.177407E+09 | 0.668085E+09 | 6146200.06 |
March | 0.340359E+09 | 0.134263E+09 | 0.206097E+09 | 0.854678E+09 | 1156977.18 |
April | 0.331064E+09 | 0.126602E+09 | 0.204462E+09 | 0.870517E+09 | 61457.25 |
May | 0.291585E+09 | 86531119.76 | 0.205054E+09 | 0.814186E+09 | 169594.50 |
June | 0.305486E+09 | 0.105248E+09 | 0.200238E+09 | 0.825011E+09 | 243991.36 |
July | 0.269101E+09 | 63355417.25 | 0.205746E+09 | 0.688638E+09 | 555712.83 |
August | 0.293491E+09 | 87226460.46 | 0.206265E+09 | 0.738373E+09 | 223589.12 |
September | 0.265143E+09 | 73469774.93 | 0.191673E+09 | 0.687717E+09 | 139492.86 |
October | 0.257604E+09 | 66510095.26 | 0.191094E+09 | 0.639688E+09 | 522311.03 |
November | 0.243072E+09 | 66369645.99 | 0.176702E+09 | 0.594658E+09 | 3963988.75 |
December | 0.257289E+09 | 84315877.95 | 0.172973E+09 | 0.610058E+09 | 25355344.48 |
Annual Sum or Average | 0.340602E+10 | 0.108882E+10 | 0.231721E+10 | 0.865295E+10 | 58271584.76 |
Minimum of Months | 0.243072E+09 | 63355417.25 | 0.172973E+09 | 0.594658E+09 | 61457.25 |
Maximum of Months | 0.340359E+09 | 0.134263E+09 | 0.206265E+09 | 0.870517E+09 | 25355344.48 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 75895064.98 | 0.00 | 75895064.98 | 0.211058E+09 | 10367448.99 |
February | 73124503.65 | 0.00 | 73124503.65 | 0.212480E+09 | 3188053.86 |
March | 83142971.03 | 4145.82 | 83138825.21 | 0.266169E+09 | 618318.28 |
April | 89174642.51 | 2148891.47 | 87025751.04 | 0.299241E+09 | 33658.65 |
May | 0.115603E+09 | 12040221.69 | 0.103563E+09 | 0.368825E+09 | 244435.82 |
June | 0.137470E+09 | 28135669.83 | 0.109335E+09 | 0.408679E+09 | 357711.32 |
July | 0.121967E+09 | 12940053.38 | 0.109027E+09 | 0.334602E+09 | 640899.89 |
August | 0.100855E+09 | 4735876.35 | 96118693.75 | 0.293047E+09 | 249918.14 |
September | 82795951.88 | 145737.55 | 82650214.33 | 0.253869E+09 | 274471.73 |
October | 82234050.60 | 0.00 | 82234050.60 | 0.235554E+09 | 417204.80 |
November | 75301476.29 | 0.00 | 75301476.29 | 0.211987E+09 | 2756289.02 |
December | 73730995.89 | 0.00 | 73730995.89 | 0.199505E+09 | 13565782.06 |
Annual Sum or Average | 0.111129E+10 | 60150596.10 | 0.105114E+10 | 0.329502E+10 | 32714192.56 |
Minimum of Months | 73124503.65 | 0.00 | 73124503.65 | 0.199505E+09 | 33658.65 |
Maximum of Months | 0.137470E+09 | 28135669.83 | 0.109335E+09 | 0.408679E+09 | 13565782.06 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.277116E+09 | 97620505.06 | 0.179496E+09 | 0.663723E+09 | 19038029.05 |
February | 0.274714E+09 | 97306347.91 | 0.177407E+09 | 0.669645E+09 | 5794147.36 |
March | 0.340359E+09 | 0.134263E+09 | 0.206097E+09 | 0.857193E+09 | 1076938.80 |
April | 0.331064E+09 | 0.126602E+09 | 0.204462E+09 | 0.869870E+09 | 63936.06 |
May | 0.291585E+09 | 86531119.76 | 0.205054E+09 | 0.811692E+09 | 452285.47 |
June | 0.305486E+09 | 0.105248E+09 | 0.200238E+09 | 0.820144E+09 | 661422.91 |
July | 0.269101E+09 | 63355417.25 | 0.205746E+09 | 0.685300E+09 | 1171815.75 |
August | 0.293491E+09 | 87226460.46 | 0.206265E+09 | 0.736466E+09 | 452310.54 |
September | 0.265143E+09 | 73469774.93 | 0.191673E+09 | 0.687566E+09 | 459626.08 |
October | 0.257604E+09 | 66510095.26 | 0.191094E+09 | 0.641486E+09 | 720942.14 |
November | 0.243072E+09 | 66369645.99 | 0.176702E+09 | 0.597598E+09 | 4968026.89 |
December | 0.257289E+09 | 84315877.95 | 0.172973E+09 | 0.612034E+09 | 24920975.08 |
Annual Sum or Average | 0.340602E+10 | 0.108882E+10 | 0.231721E+10 | 0.865272E+10 | 59780456.14 |
Minimum of Months | 0.243072E+09 | 63355417.25 | 0.172973E+09 | 0.597598E+09 | 63936.06 |
Maximum of Months | 0.340359E+09 | 0.134263E+09 | 0.206265E+09 | 0.869870E+09 | 24920975.08 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.160496E+09 | 66833161.06 | 93662786.16 | 0.318791E+09 | 47572780.73 |
February | 0.122626E+09 | 39546664.89 | 83078992.27 | 0.260072E+09 | 35047286.91 |
March | 94673987.22 | 14050379.47 | 80623607.75 | 0.215055E+09 | 29228296.49 |
April | 67921429.52 | 391019.39 | 67530410.13 | 0.156520E+09 | 14978970.25 |
May | 69486232.11 | 0.00 | 69486232.11 | 0.164232E+09 | 17245169.69 |
June | 67002720.86 | 0.00 | 67002720.86 | 0.157513E+09 | 17540171.45 |
July | 71323528.04 | 0.00 | 71323528.04 | 0.145712E+09 | 29473026.20 |
August | 69348227.89 | 5849.35 | 69342378.53 | 0.139773E+09 | 26754623.29 |
September | 74058349.55 | 2029382.34 | 72028967.21 | 0.156497E+09 | 25797036.01 |
October | 99662864.04 | 15122605.09 | 84540258.96 | 0.198565E+09 | 33136685.02 |
November | 0.127303E+09 | 39331600.67 | 87971427.44 | 0.252083E+09 | 36578164.08 |
December | 0.161059E+09 | 68744751.16 | 92314006.95 | 0.315120E+09 | 53445237.66 |
Annual Sum or Average | 0.118496E+10 | 0.246055E+09 | 0.938905E+09 | 0.247993E+10 | 0.366797E+09 |
Minimum of Months | 67002720.86 | 0.00 | 67002720.86 | 0.139773E+09 | 14978970.25 |
Maximum of Months | 0.161059E+09 | 68744751.16 | 93662786.16 | 0.318791E+09 | 53445237.66 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 60724100.24 | 0.00 | 60724100.24 | 0.181445E+09 | 6162318.53 |
February | 58507357.38 | 0.00 | 58507357.38 | 0.183581E+09 | 1140539.82 |
March | 66523193.68 | 3317.10 | 66519876.59 | 0.230590E+09 | 195688.46 |
April | 71349170.49 | 1719341.05 | 69629829.44 | 0.256592E+09 | 0.00 |
May | 92494836.56 | 9633454.15 | 82861382.42 | 0.310804E+09 | 55827.16 |
June | 0.109991E+09 | 22511519.50 | 87479435.91 | 0.342226E+09 | 106159.99 |
July | 97586225.79 | 10353414.93 | 87232810.86 | 0.280957E+09 | 153590.57 |
August | 80694351.16 | 3789203.30 | 76905147.87 | 0.249056E+09 | 26298.93 |
September | 66245541.57 | 116605.50 | 66128936.07 | 0.217343E+09 | 44733.60 |
October | 65795960.95 | 0.00 | 65795960.95 | 0.202325E+09 | 30055.59 |
November | 60249166.34 | 0.00 | 60249166.34 | 0.182121E+09 | 1183749.30 |
December | 58992615.48 | 0.00 | 58992615.48 | 0.170824E+09 | 8192751.56 |
Annual Sum or Average | 0.889153E+09 | 48126855.52 | 0.841027E+09 | 0.280786E+10 | 17291713.52 |
Minimum of Months | 58507357.38 | 0.00 | 58507357.38 | 0.170824E+09 | 0.00 |
Maximum of Months | 0.109991E+09 | 22511519.50 | 87479435.91 | 0.342226E+09 | 8192751.56 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.273157E+09 | 92096303.80 | 0.181060E+09 | 0.654504E+09 | 18723742.53 |
February | 0.279632E+09 | 0.102419E+09 | 0.177212E+09 | 0.681218E+09 | 5869408.25 |
March | 0.338031E+09 | 0.132310E+09 | 0.205721E+09 | 0.853476E+09 | 1121211.66 |
April | 0.330020E+09 | 0.125890E+09 | 0.204130E+09 | 0.877043E+09 | 17085.40 |
May | 0.293553E+09 | 88968658.34 | 0.204584E+09 | 0.824613E+09 | 139382.41 |
June | 0.302391E+09 | 99564373.77 | 0.202827E+09 | 0.825366E+09 | 191757.69 |
July | 0.267221E+09 | 59987150.76 | 0.207234E+09 | 0.688545E+09 | 433145.98 |
August | 0.293747E+09 | 86350089.41 | 0.207397E+09 | 0.743577E+09 | 162199.14 |
September | 0.267059E+09 | 72837236.32 | 0.194222E+09 | 0.697502E+09 | 124350.17 |
October | 0.258910E+09 | 66433527.72 | 0.192476E+09 | 0.646675E+09 | 438828.45 |
November | 0.242558E+09 | 67113721.24 | 0.175444E+09 | 0.596317E+09 | 3694398.08 |
December | 0.256204E+09 | 82286475.08 | 0.173918E+09 | 0.607078E+09 | 24032307.92 |
Annual Sum or Average | 0.340248E+10 | 0.107626E+10 | 0.232623E+10 | 0.869591E+10 | 54947817.67 |
Minimum of Months | 0.242558E+09 | 59987150.76 | 0.173918E+09 | 0.596317E+09 | 17085.40 |
Maximum of Months | 0.338031E+09 | 0.132310E+09 | 0.207397E+09 | 0.877043E+09 | 24032307.92 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200660E+09 | 83558065.46 | 0.117102E+09 | 0.468393E+09 | 9953015.62 |
February | 0.153313E+09 | 49443162.07 | 0.103869E+09 | 0.389424E+09 | 3064934.02 |
March | 0.118366E+09 | 17566467.14 | 0.100800E+09 | 0.351066E+09 | 599925.77 |
April | 84918671.58 | 488871.44 | 84429800.14 | 0.288684E+09 | 17894.94 |
May | 86875063.81 | 0.00 | 86875063.81 | 0.302914E+09 | 81740.08 |
June | 83770057.37 | 0.00 | 83770057.37 | 0.287715E+09 | 114007.25 |
July | 89172140.46 | 0.00 | 89172140.46 | 0.260829E+09 | 260466.90 |
August | 86702524.22 | 7313.15 | 86695211.08 | 0.260755E+09 | 98761.39 |
September | 92591347.20 | 2537232.41 | 90054114.79 | 0.275947E+09 | 57864.02 |
October | 0.124603E+09 | 18907015.71 | 0.105696E+09 | 0.328246E+09 | 223374.81 |
November | 0.159160E+09 | 49174278.34 | 0.109986E+09 | 0.385920E+09 | 1940431.82 |
December | 0.201363E+09 | 85948028.30 | 0.115415E+09 | 0.458888E+09 | 12746649.23 |
Annual Sum or Average | 0.148150E+10 | 0.307630E+09 | 0.117387E+10 | 0.405878E+10 | 29159065.86 |
Minimum of Months | 83770057.37 | 0.00 | 83770057.37 | 0.260755E+09 | 17894.94 |
Maximum of Months | 0.201363E+09 | 85948028.30 | 0.117102E+09 | 0.468393E+09 | 12746649.23 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 75895064.98 | 0.00 | 75895064.98 | 0.209510E+09 | 10144691.91 |
February | 73124503.65 | 0.00 | 73124503.65 | 0.211144E+09 | 3065056.98 |
March | 83142971.03 | 4145.82 | 83138825.21 | 0.265825E+09 | 566246.78 |
April | 89174642.51 | 2148891.47 | 87025751.04 | 0.298816E+09 | 14394.32 |
May | 0.115603E+09 | 12040221.69 | 0.103563E+09 | 0.368425E+09 | 210859.43 |
June | 0.137470E+09 | 28135669.83 | 0.109335E+09 | 0.408336E+09 | 311195.99 |
July | 0.121967E+09 | 12940053.38 | 0.109027E+09 | 0.334272E+09 | 571237.55 |
August | 0.100855E+09 | 4735876.35 | 96118693.75 | 0.292573E+09 | 208877.13 |
September | 82795951.88 | 145737.55 | 82650214.33 | 0.253385E+09 | 242381.74 |
October | 82234050.60 | 0.00 | 82234050.60 | 0.235192E+09 | 396269.20 |
November | 75301476.29 | 0.00 | 75301476.29 | 0.211408E+09 | 2723505.99 |
December | 73730995.89 | 0.00 | 73730995.89 | 0.198011E+09 | 13241035.59 |
Annual Sum or Average | 0.111129E+10 | 60150596.10 | 0.105114E+10 | 0.328690E+10 | 31695752.63 |
Minimum of Months | 73124503.65 | 0.00 | 73124503.65 | 0.198011E+09 | 14394.32 |
Maximum of Months | 0.137470E+09 | 28135669.83 | 0.109335E+09 | 0.408336E+09 | 13241035.59 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.273157E+09 | 92096303.80 | 0.181060E+09 | 0.653984E+09 | 17965147.13 |
February | 0.279632E+09 | 0.102419E+09 | 0.177212E+09 | 0.680597E+09 | 5499261.91 |
March | 0.338031E+09 | 0.132310E+09 | 0.205721E+09 | 0.855778E+09 | 1046309.63 |
April | 0.330020E+09 | 0.125890E+09 | 0.204130E+09 | 0.876460E+09 | 18812.55 |
May | 0.293553E+09 | 88968658.34 | 0.204584E+09 | 0.822154E+09 | 387170.74 |
June | 0.302391E+09 | 99564373.77 | 0.202827E+09 | 0.820512E+09 | 574851.25 |
July | 0.267221E+09 | 59987150.76 | 0.207234E+09 | 0.685192E+09 | 1006318.73 |
August | 0.293747E+09 | 86350089.41 | 0.207397E+09 | 0.741720E+09 | 377948.78 |
September | 0.267059E+09 | 72837236.32 | 0.194222E+09 | 0.697324E+09 | 411010.52 |
October | 0.258910E+09 | 66433527.72 | 0.192476E+09 | 0.648358E+09 | 656527.35 |
November | 0.242558E+09 | 67113721.24 | 0.175444E+09 | 0.598472E+09 | 4721011.43 |
December | 0.256204E+09 | 82286475.08 | 0.173918E+09 | 0.606508E+09 | 23571660.95 |
Annual Sum or Average | 0.340248E+10 | 0.107626E+10 | 0.232623E+10 | 0.868706E+10 | 56236030.98 |
Minimum of Months | 0.242558E+09 | 59987150.76 | 0.173918E+09 | 0.598472E+09 | 18812.55 |
Maximum of Months | 0.338031E+09 | 0.132310E+09 | 0.207397E+09 | 0.876460E+09 | 23571660.95 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 96116311.08 | 0.00 | 96116311.08 | 0.259035E+09 | 22841588.81 |
February | 92607569.98 | 0.00 | 92607569.98 | 0.257795E+09 | 12244432.92 |
March | 0.105295E+09 | 5250.42 | 0.105290E+09 | 0.321053E+09 | 4108563.85 |
April | 0.112934E+09 | 2721435.46 | 0.110213E+09 | 0.362839E+09 | 508575.39 |
May | 0.146404E+09 | 15248181.07 | 0.131156E+09 | 0.446210E+09 | 1633983.76 |
June | 0.174098E+09 | 35632050.58 | 0.138466E+09 | 0.493670E+09 | 1943398.97 |
July | 0.154463E+09 | 16387761.13 | 0.138075E+09 | 0.411042E+09 | 3623903.62 |
August | 0.127726E+09 | 5997688.58 | 0.121728E+09 | 0.360174E+09 | 1342906.26 |
September | 0.104856E+09 | 184567.42 | 0.104671E+09 | 0.311218E+09 | 1547164.98 |
October | 0.104144E+09 | 0.00 | 0.104144E+09 | 0.286888E+09 | 2681837.73 |
November | 95364568.46 | 0.00 | 95364568.46 | 0.257318E+09 | 8733783.92 |
December | 93375654.12 | 0.00 | 93375654.12 | 0.246199E+09 | 27841889.88 |
Annual Sum or Average | 0.140738E+10 | 76176934.66 | 0.133121E+10 | 0.401344E+10 | 89052030.10 |
Minimum of Months | 92607569.98 | 0.00 | 92607569.98 | 0.246199E+09 | 508575.39 |
Maximum of Months | 0.174098E+09 | 35632050.58 | 0.138466E+09 | 0.493670E+09 | 27841889.88 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 35432452.13 | 0.00 | 35432452.13 | 95491181.10 | 8420355.43 |
February | 34138984.87 | 0.00 | 34138984.87 | 95033873.07 | 4514047.58 |
March | 38816217.39 | 1935.52 | 38814281.86 | 0.118353E+09 | 1514586.76 |
April | 41632170.06 | 1003233.80 | 40628936.26 | 0.133758E+09 | 187481.95 |
May | 53970645.19 | 5621110.92 | 48349534.27 | 0.164492E+09 | 602354.07 |
June | 64179613.14 | 13135449.25 | 51044163.89 | 0.181987E+09 | 716417.33 |
July | 56941465.74 | 6041207.32 | 50900258.43 | 0.151527E+09 | 1335920.93 |
August | 47085073.69 | 2210996.36 | 44874077.33 | 0.132775E+09 | 495050.85 |
September | 38654207.65 | 68039.19 | 38586168.46 | 0.114728E+09 | 570349.07 |
October | 38391877.81 | 0.00 | 38391877.81 | 0.105759E+09 | 988636.43 |
November | 35155328.67 | 0.00 | 35155328.67 | 94857927.65 | 3219634.39 |
December | 34422132.49 | 0.00 | 34422132.49 | 90758986.01 | 10263673.45 |
Annual Sum or Average | 0.518820E+09 | 28081972.36 | 0.490738E+09 | 0.147952E+10 | 32828508.25 |
Minimum of Months | 34138984.87 | 0.00 | 34138984.87 | 90758986.01 | 187481.95 |
Maximum of Months | 64179613.14 | 13135449.25 | 51044163.89 | 0.181987E+09 | 10263673.45 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93627068.97 | 38987856.63 | 54639212.34 | 0.215874E+09 | 8004305.09 |
February | 71535020.42 | 23069980.18 | 48465040.24 | 0.177767E+09 | 4320177.23 |
March | 55229107.56 | 8196442.78 | 47032664.78 | 0.158436E+09 | 1506024.87 |
April | 39622709.96 | 228105.44 | 39394604.52 | 0.128835E+09 | 177847.30 |
May | 40535554.69 | 0.00 | 40535554.69 | 0.133322E+09 | 615228.21 |
June | 39086771.20 | 0.00 | 39086771.20 | 0.124553E+09 | 732937.70 |
July | 41607361.40 | 0.00 | 41607361.40 | 0.116473E+09 | 1358325.89 |
August | 40455048.42 | 3412.29 | 40451636.13 | 0.117474E+09 | 504854.84 |
September | 43202749.49 | 1183862.42 | 42018887.07 | 0.125104E+09 | 539283.00 |
October | 58139423.51 | 8821937.34 | 49317486.17 | 0.149336E+09 | 916130.35 |
November | 74263616.00 | 22944520.11 | 51319095.89 | 0.176481E+09 | 3023724.03 |
December | 93955390.88 | 40103003.66 | 53852387.21 | 0.212026E+09 | 9752626.09 |
Annual Sum or Average | 0.691260E+09 | 0.143539E+09 | 0.547721E+09 | 0.183568E+10 | 31451464.60 |
Minimum of Months | 39086771.20 | 0.00 | 39086771.20 | 0.116473E+09 | 177847.30 |
Maximum of Months | 93955390.88 | 40103003.66 | 54639212.34 | 0.215874E+09 | 9752626.09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.254123E+09 | 0.105821E+09 | 0.148302E+09 | 0.585925E+09 | 21725321.27 |
February | 0.194161E+09 | 62616645.07 | 0.131544E+09 | 0.482495E+09 | 11725844.67 |
March | 0.149903E+09 | 22246822.25 | 0.127656E+09 | 0.430029E+09 | 4087659.55 |
April | 0.107544E+09 | 619124.83 | 0.106925E+09 | 0.349686E+09 | 482713.96 |
May | 0.110022E+09 | 0.00 | 0.110022E+09 | 0.361863E+09 | 1669855.19 |
June | 0.106089E+09 | 0.00 | 0.106089E+09 | 0.338062E+09 | 1989342.84 |
July | 0.112931E+09 | 0.00 | 0.112931E+09 | 0.316131E+09 | 3686774.31 |
August | 0.109803E+09 | 9261.64 | 0.109794E+09 | 0.318849E+09 | 1370279.31 |
September | 0.117261E+09 | 3213244.76 | 0.114048E+09 | 0.339559E+09 | 1463724.37 |
October | 0.157802E+09 | 23944542.43 | 0.133858E+09 | 0.405329E+09 | 2486565.15 |
November | 0.201567E+09 | 62276120.79 | 0.139291E+09 | 0.479004E+09 | 8207005.49 |
December | 0.255014E+09 | 0.108848E+09 | 0.146166E+09 | 0.575483E+09 | 26470622.07 |
Annual Sum or Average | 0.187622E+10 | 0.389595E+09 | 0.148663E+10 | 0.498242E+10 | 85365708.19 |
Minimum of Months | 0.106089E+09 | 0.00 | 0.106089E+09 | 0.316131E+09 | 482713.96 |
Maximum of Months | 0.255014E+09 | 0.108848E+09 | 0.148302E+09 | 0.585925E+09 | 26470622.07 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200660E+09 | 83558065.46 | 0.117102E+09 | 0.465149E+09 | 8590695.33 |
February | 0.153313E+09 | 49443162.07 | 0.103869E+09 | 0.387752E+09 | 2138900.16 |
March | 0.118366E+09 | 17566467.14 | 0.100800E+09 | 0.350831E+09 | 314245.00 |
April | 84918671.58 | 488871.44 | 84429800.14 | 0.289051E+09 | 9342.61 |
May | 86875063.81 | 0.00 | 86875063.81 | 0.303259E+09 | 64727.94 |
June | 83770057.37 | 0.00 | 83770057.37 | 0.288487E+09 | 78349.65 |
July | 89172140.46 | 0.00 | 89172140.46 | 0.259830E+09 | 178752.30 |
August | 86702524.22 | 7313.15 | 86695211.08 | 0.260454E+09 | 70423.94 |
September | 92591347.20 | 2537232.41 | 90054114.79 | 0.274498E+09 | 18968.87 |
October | 0.124603E+09 | 18907015.71 | 0.105696E+09 | 0.326049E+09 | 113494.51 |
November | 0.159160E+09 | 49174278.34 | 0.109986E+09 | 0.383229E+09 | 1339140.00 |
December | 0.201363E+09 | 85948028.30 | 0.115415E+09 | 0.455231E+09 | 11147204.59 |
Annual Sum or Average | 0.148150E+10 | 0.307630E+09 | 0.117387E+10 | 0.404382E+10 | 24064244.89 |
Minimum of Months | 83770057.37 | 0.00 | 83770057.37 | 0.259830E+09 | 9342.61 |
Maximum of Months | 0.201363E+09 | 85948028.30 | 0.117102E+09 | 0.465149E+09 | 11147204.59 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.277116E+09 | 97620505.06 | 0.179496E+09 | 0.655345E+09 | 16534037.88 |
February | 0.274714E+09 | 97306347.91 | 0.177407E+09 | 0.663751E+09 | 4053541.18 |
March | 0.340359E+09 | 0.134263E+09 | 0.206097E+09 | 0.850822E+09 | 588220.67 |
April | 0.331064E+09 | 0.126602E+09 | 0.204462E+09 | 0.866234E+09 | 13180.05 |
May | 0.291585E+09 | 86531119.76 | 0.205054E+09 | 0.811105E+09 | 115293.79 |
June | 0.305486E+09 | 0.105248E+09 | 0.200238E+09 | 0.822527E+09 | 129792.31 |
July | 0.269101E+09 | 63355417.25 | 0.205746E+09 | 0.683893E+09 | 302946.06 |
August | 0.293491E+09 | 87226460.46 | 0.206265E+09 | 0.734084E+09 | 105416.74 |
September | 0.265143E+09 | 73469774.93 | 0.191673E+09 | 0.682435E+09 | 34466.64 |
October | 0.257604E+09 | 66510095.26 | 0.191094E+09 | 0.634838E+09 | 245575.26 |
November | 0.243072E+09 | 66369645.99 | 0.176702E+09 | 0.589977E+09 | 2660119.59 |
December | 0.257289E+09 | 84315877.95 | 0.172973E+09 | 0.603531E+09 | 21477559.08 |
Annual Sum or Average | 0.340602E+10 | 0.108882E+10 | 0.231721E+10 | 0.859854E+10 | 46260149.24 |
Minimum of Months | 0.243072E+09 | 63355417.25 | 0.172973E+09 | 0.589977E+09 | 13180.05 |
Maximum of Months | 0.340359E+09 | 0.134263E+09 | 0.206265E+09 | 0.866234E+09 | 21477559.08 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 75895064.98 | 0.00 | 75895064.98 | 0.209338E+09 | 8657947.12 |
February | 73124503.65 | 0.00 | 73124503.65 | 0.211633E+09 | 2095439.08 |
March | 83142971.03 | 4145.82 | 83138825.21 | 0.265817E+09 | 323078.15 |
April | 89174642.51 | 2148891.47 | 87025751.04 | 0.298201E+09 | 6882.14 |
May | 0.115603E+09 | 12040221.69 | 0.103563E+09 | 0.367427E+09 | 229031.08 |
June | 0.137470E+09 | 28135669.83 | 0.109335E+09 | 0.407060E+09 | 343876.82 |
July | 0.121967E+09 | 12940053.38 | 0.109027E+09 | 0.332191E+09 | 567442.43 |
August | 0.100855E+09 | 4735876.35 | 96118693.75 | 0.291364E+09 | 229871.36 |
September | 82795951.88 | 145737.55 | 82650214.33 | 0.252001E+09 | 302918.45 |
October | 82234050.60 | 0.00 | 82234050.60 | 0.233960E+09 | 369078.95 |
November | 75301476.29 | 0.00 | 75301476.29 | 0.210595E+09 | 2216046.42 |
December | 73730995.89 | 0.00 | 73730995.89 | 0.197511E+09 | 11566126.32 |
Annual Sum or Average | 0.111129E+10 | 60150596.10 | 0.105114E+10 | 0.327710E+10 | 26907738.32 |
Minimum of Months | 73124503.65 | 0.00 | 73124503.65 | 0.197511E+09 | 6882.14 |
Maximum of Months | 0.137470E+09 | 28135669.83 | 0.109335E+09 | 0.407060E+09 | 11566126.32 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.277116E+09 | 97620505.06 | 0.179496E+09 | 0.658479E+09 | 15861074.57 |
February | 0.274714E+09 | 97306347.91 | 0.177407E+09 | 0.665845E+09 | 3751147.16 |
March | 0.340359E+09 | 0.134263E+09 | 0.206097E+09 | 0.853467E+09 | 577549.04 |
April | 0.331064E+09 | 0.126602E+09 | 0.204462E+09 | 0.865502E+09 | 14132.82 |
May | 0.291585E+09 | 86531119.76 | 0.205054E+09 | 0.808501E+09 | 420306.59 |
June | 0.305486E+09 | 0.105248E+09 | 0.200238E+09 | 0.817524E+09 | 627436.99 |
July | 0.269101E+09 | 63355417.25 | 0.205746E+09 | 0.680455E+09 | 1033339.90 |
August | 0.293491E+09 | 87226460.46 | 0.206265E+09 | 0.732101E+09 | 404165.36 |
September | 0.265143E+09 | 73469774.93 | 0.191673E+09 | 0.682253E+09 | 541412.64 |
October | 0.257604E+09 | 66510095.26 | 0.191094E+09 | 0.636667E+09 | 639974.37 |
November | 0.243072E+09 | 66369645.99 | 0.176702E+09 | 0.593325E+09 | 3992964.98 |
December | 0.257289E+09 | 84315877.95 | 0.172973E+09 | 0.606396E+09 | 21232395.72 |
Annual Sum or Average | 0.340602E+10 | 0.108882E+10 | 0.231721E+10 | 0.860051E+10 | 49095900.15 |
Minimum of Months | 0.243072E+09 | 63355417.25 | 0.172973E+09 | 0.593325E+09 | 14132.82 |
Maximum of Months | 0.340359E+09 | 0.134263E+09 | 0.206265E+09 | 0.865502E+09 | 21232395.72 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.294287E+09 | 0.122546E+09 | 0.171741E+09 | 0.686235E+09 | 11854647.66 |
February | 0.224848E+09 | 72513142.25 | 0.152334E+09 | 0.575957E+09 | 2486035.27 |
March | 0.173595E+09 | 25762909.92 | 0.147832E+09 | 0.529595E+09 | 340029.11 |
April | 0.124541E+09 | 716976.88 | 0.123824E+09 | 0.442166E+09 | 0.00 |
May | 0.127411E+09 | 0.00 | 0.127411E+09 | 0.461029E+09 | 54598.68 |
June | 0.122857E+09 | 0.00 | 0.122857E+09 | 0.440057E+09 | 22736.96 |
July | 0.130780E+09 | 0.00 | 0.130780E+09 | 0.394883E+09 | 88947.15 |
August | 0.127158E+09 | 10725.43 | 0.127147E+09 | 0.397153E+09 | 13756.96 |
September | 0.135794E+09 | 3721094.83 | 0.132073E+09 | 0.415634E+09 | 3437.57 |
October | 0.182743E+09 | 27728953.05 | 0.155014E+09 | 0.487586E+09 | 70237.90 |
November | 0.233424E+09 | 72118798.45 | 0.161305E+09 | 0.567748E+09 | 1582872.44 |
December | 0.295319E+09 | 0.126051E+09 | 0.169268E+09 | 0.670417E+09 | 15510904.05 |
Annual Sum or Average | 0.217276E+10 | 0.451170E+09 | 0.172159E+10 | 0.606846E+10 | 32028203.74 |
Minimum of Months | 0.122857E+09 | 0.00 | 0.122857E+09 | 0.394883E+09 | 0.00 |
Maximum of Months | 0.295319E+09 | 0.126051E+09 | 0.171741E+09 | 0.686235E+09 | 15510904.05 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.531245E+09 | 0.00 | 0.531245E+09 | 0.131723E+10 | 0.193746E+09 |
February | 0.511852E+09 | 0.00 | 0.511852E+09 | 0.133033E+10 | 0.117647E+09 |
March | 0.581979E+09 | 29019.66 | 0.581950E+09 | 0.161076E+10 | 62774432.38 |
April | 0.624199E+09 | 15041670.60 | 0.609157E+09 | 0.179847E+10 | 14501288.71 |
May | 0.809192E+09 | 84278359.80 | 0.724914E+09 | 0.226723E+10 | 32913295.49 |
June | 0.962257E+09 | 0.196942E+09 | 0.765315E+09 | 0.255668E+10 | 34017347.56 |
July | 0.853734E+09 | 90576943.10 | 0.763157E+09 | 0.208458E+10 | 76221559.53 |
August | 0.705955E+09 | 33149878.94 | 0.672805E+09 | 0.177173E+10 | 46197147.51 |
September | 0.579550E+09 | 1020124.24 | 0.578530E+09 | 0.152238E+10 | 48583694.87 |
October | 0.575617E+09 | 0.00 | 0.575617E+09 | 0.140674E+10 | 75006391.71 |
November | 0.527090E+09 | 0.00 | 0.527090E+09 | 0.129476E+10 | 0.108838E+09 |
December | 0.516097E+09 | 0.00 | 0.516097E+09 | 0.125979E+10 | 0.232297E+09 |
Annual Sum or Average | 0.777877E+10 | 0.421038E+09 | 0.735773E+10 | 0.202207E+11 | 0.104274E+10 |
Minimum of Months | 0.511852E+09 | 0.00 | 0.511852E+09 | 0.125979E+10 | 14501288.71 |
Maximum of Months | 0.962257E+09 | 0.196942E+09 | 0.765315E+09 | 0.255668E+10 | 0.232297E+09 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.531245E+09 | 0.00 | 0.531245E+09 | 0.128665E+10 | 0.208798E+09 |
February | 0.511852E+09 | 0.00 | 0.511852E+09 | 0.130301E+10 | 0.128844E+09 |
March | 0.581979E+09 | 29019.66 | 0.581950E+09 | 0.157603E+10 | 72915908.94 |
April | 0.624199E+09 | 15041670.60 | 0.609157E+09 | 0.175894E+10 | 17610425.72 |
May | 0.809192E+09 | 84278359.80 | 0.724914E+09 | 0.222877E+10 | 38798218.64 |
June | 0.962257E+09 | 0.196942E+09 | 0.765315E+09 | 0.252121E+10 | 39373623.01 |
July | 0.853734E+09 | 90576943.10 | 0.763157E+09 | 0.204927E+10 | 88056519.75 |
August | 0.705955E+09 | 33149878.94 | 0.672805E+09 | 0.173009E+10 | 56936922.95 |
September | 0.579550E+09 | 1020124.24 | 0.578530E+09 | 0.148572E+10 | 59116141.08 |
October | 0.575617E+09 | 0.00 | 0.575617E+09 | 0.137045E+10 | 89970290.88 |
November | 0.527090E+09 | 0.00 | 0.527090E+09 | 0.126371E+10 | 0.123268E+09 |
December | 0.516097E+09 | 0.00 | 0.516097E+09 | 0.122981E+10 | 0.249373E+09 |
Annual Sum or Average | 0.777877E+10 | 0.421038E+09 | 0.735773E+10 | 0.198037E+11 | 0.117306E+10 |
Minimum of Months | 0.511852E+09 | 0.00 | 0.511852E+09 | 0.122981E+10 | 17610425.72 |
Maximum of Months | 0.962257E+09 | 0.196942E+09 | 0.765315E+09 | 0.252121E+10 | 0.249373E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 75895064.98 | 0.00 | 75895064.98 | 0.234128E+09 | 26241040.43 |
February | 73124503.65 | 0.00 | 73124503.65 | 0.232055E+09 | 16237499.05 |
March | 83142971.03 | 4145.82 | 83138825.21 | 0.273145E+09 | 9934288.23 |
April | 89174642.51 | 2148891.47 | 87025751.04 | 0.300899E+09 | 2682379.38 |
May | 0.115603E+09 | 12040221.69 | 0.103563E+09 | 0.368309E+09 | 5035444.21 |
June | 0.137470E+09 | 28135669.83 | 0.109335E+09 | 0.412528E+09 | 5235481.73 |
July | 0.121967E+09 | 12940053.38 | 0.109027E+09 | 0.348451E+09 | 9969879.56 |
August | 0.100855E+09 | 4735876.35 | 96118693.75 | 0.293278E+09 | 6953818.87 |
September | 82795951.88 | 145737.55 | 82650214.33 | 0.263668E+09 | 7303842.33 |
October | 82234050.60 | 0.00 | 82234050.60 | 0.241950E+09 | 10376073.99 |
November | 75301476.29 | 0.00 | 75301476.29 | 0.231102E+09 | 14283522.61 |
December | 73730995.89 | 0.00 | 73730995.89 | 0.226584E+09 | 31005535.22 |
Annual Sum or Average | 0.111129E+10 | 60150596.10 | 0.105114E+10 | 0.342610E+10 | 0.145259E+09 |
Minimum of Months | 73124503.65 | 0.00 | 73124503.65 | 0.226584E+09 | 2682379.38 |
Maximum of Months | 0.137470E+09 | 28135669.83 | 0.109335E+09 | 0.412528E+09 | 31005535.22 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.546275E+09 | 0.184180E+09 | 0.362095E+09 | 0.139601E+10 | 97624312.59 |
February | 0.559224E+09 | 0.204824E+09 | 0.354400E+09 | 0.143435E+10 | 60993737.87 |
March | 0.676014E+09 | 0.264601E+09 | 0.411414E+09 | 0.172434E+10 | 37159236.96 |
April | 0.659994E+09 | 0.251763E+09 | 0.408231E+09 | 0.175124E+10 | 10180986.58 |
May | 0.587064E+09 | 0.177925E+09 | 0.409139E+09 | 0.163569E+10 | 19142026.33 |
June | 0.604740E+09 | 0.199115E+09 | 0.405625E+09 | 0.165128E+10 | 19905887.45 |
July | 0.534404E+09 | 0.119966E+09 | 0.414438E+09 | 0.142188E+10 | 37584513.37 |
August | 0.587453E+09 | 0.172688E+09 | 0.414765E+09 | 0.148217E+10 | 26354078.03 |
September | 0.534080E+09 | 0.145664E+09 | 0.388416E+09 | 0.142826E+10 | 27548443.56 |
October | 0.517782E+09 | 0.132858E+09 | 0.384925E+09 | 0.131489E+10 | 39481611.73 |
November | 0.485082E+09 | 0.134218E+09 | 0.350864E+09 | 0.126489E+10 | 53739246.34 |
December | 0.512372E+09 | 0.164561E+09 | 0.347811E+09 | 0.131713E+10 | 0.115832E+09 |
Annual Sum or Average | 0.680448E+10 | 0.215236E+10 | 0.465212E+10 | 0.178221E+11 | 0.545546E+09 |
Minimum of Months | 0.485082E+09 | 0.119966E+09 | 0.347811E+09 | 0.126489E+10 | 10180986.58 |
Maximum of Months | 0.676014E+09 | 0.264601E+09 | 0.414765E+09 | 0.175124E+10 | 0.115832E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200660E+09 | 83558065.46 | 0.117102E+09 | 0.492833E+09 | 25905239.72 |
February | 0.153313E+09 | 49443162.07 | 0.103869E+09 | 0.409574E+09 | 16198433.14 |
March | 0.118366E+09 | 17566467.14 | 0.100800E+09 | 0.357422E+09 | 9876861.94 |
April | 84918671.58 | 488871.44 | 84429800.14 | 0.289599E+09 | 2695108.18 |
May | 86875063.81 | 0.00 | 86875063.81 | 0.300328E+09 | 5037373.77 |
June | 83770057.37 | 0.00 | 83770057.37 | 0.287419E+09 | 5295705.04 |
July | 89172140.46 | 0.00 | 89172140.46 | 0.273541E+09 | 10081937.02 |
August | 86702524.22 | 7313.15 | 86695211.08 | 0.259150E+09 | 6989450.27 |
September | 92591347.20 | 2537232.41 | 90054114.79 | 0.285746E+09 | 7292671.39 |
October | 0.124603E+09 | 18907015.71 | 0.105696E+09 | 0.335224E+09 | 10358730.15 |
November | 0.159160E+09 | 49174278.34 | 0.109986E+09 | 0.406529E+09 | 14223817.89 |
December | 0.201363E+09 | 85948028.30 | 0.115415E+09 | 0.487686E+09 | 30725304.33 |
Annual Sum or Average | 0.148150E+10 | 0.307630E+09 | 0.117387E+10 | 0.418505E+10 | 0.144681E+09 |
Minimum of Months | 83770057.37 | 0.00 | 83770057.37 | 0.259150E+09 | 2695108.18 |
Maximum of Months | 0.201363E+09 | 85948028.30 | 0.117102E+09 | 0.492833E+09 | 30725304.33 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 96116311.08 | 0.00 | 96116311.08 | 0.238563E+09 | 29038406.04 |
February | 92607569.98 | 0.00 | 92607569.98 | 0.239625E+09 | 17180853.67 |
March | 0.105295E+09 | 5250.42 | 0.105290E+09 | 0.295386E+09 | 6809795.12 |
April | 0.112934E+09 | 2721435.46 | 0.110213E+09 | 0.333254E+09 | 1018302.04 |
May | 0.146404E+09 | 15248181.07 | 0.131156E+09 | 0.420805E+09 | 3089285.26 |
June | 0.174098E+09 | 35632050.58 | 0.138466E+09 | 0.471347E+09 | 3583903.95 |
July | 0.154463E+09 | 16387761.13 | 0.138075E+09 | 0.387563E+09 | 7539421.34 |
August | 0.127726E+09 | 5997688.58 | 0.121728E+09 | 0.336168E+09 | 2775285.56 |
September | 0.104856E+09 | 184567.42 | 0.104671E+09 | 0.284844E+09 | 3632975.64 |
October | 0.104144E+09 | 0.00 | 0.104144E+09 | 0.264045E+09 | 5592430.10 |
November | 95364568.46 | 0.00 | 95364568.46 | 0.237252E+09 | 13197845.30 |
December | 93375654.12 | 0.00 | 93375654.12 | 0.228659E+09 | 34598032.39 |
Annual Sum or Average | 0.140738E+10 | 76176934.66 | 0.133121E+10 | 0.373751E+10 | 0.128057E+09 |
Minimum of Months | 92607569.98 | 0.00 | 92607569.98 | 0.228659E+09 | 1018302.04 |
Maximum of Months | 0.174098E+09 | 35632050.58 | 0.138466E+09 | 0.471347E+09 | 34598032.39 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 85995627.71 | 0.00 | 85995627.71 | 0.213443E+09 | 25980771.91 |
February | 82856343.75 | 0.00 | 82856343.75 | 0.214393E+09 | 15373654.27 |
March | 94208127.83 | 4697.57 | 94203430.26 | 0.264283E+09 | 6092749.50 |
April | 0.101043E+09 | 2434878.62 | 98607651.10 | 0.298164E+09 | 911078.69 |
May | 0.130988E+09 | 13642605.38 | 0.117346E+09 | 0.376496E+09 | 2763995.22 |
June | 0.155766E+09 | 31880130.66 | 0.123886E+09 | 0.421716E+09 | 3206532.45 |
July | 0.138199E+09 | 14662191.98 | 0.123536E+09 | 0.346755E+09 | 6745548.84 |
August | 0.114277E+09 | 5366154.70 | 0.108911E+09 | 0.300771E+09 | 2483058.50 |
September | 93814925.33 | 165133.17 | 93649792.16 | 0.254851E+09 | 3250437.07 |
October | 93178242.92 | 0.00 | 93178242.92 | 0.236242E+09 | 5003568.40 |
November | 85323040.73 | 0.00 | 85323040.73 | 0.212270E+09 | 11808737.27 |
December | 83543551.54 | 0.00 | 83543551.54 | 0.204582E+09 | 30954990.67 |
Annual Sum or Average | 0.125919E+10 | 68155792.08 | 0.119104E+10 | 0.334396E+10 | 0.114575E+09 |
Minimum of Months | 82856343.75 | 0.00 | 82856343.75 | 0.204582E+09 | 911078.69 |
Maximum of Months | 0.155766E+09 | 31880130.66 | 0.123886E+09 | 0.421716E+09 | 30954990.67 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.749123E+09 | 0.311947E+09 | 0.437176E+09 | 0.166035E+10 | 82012771.47 |
February | 0.572361E+09 | 0.184586E+09 | 0.387775E+09 | 0.136433E+10 | 48876191.80 |
March | 0.441896E+09 | 65580856.37 | 0.376315E+09 | 0.119036E+10 | 19574987.43 |
April | 0.317027E+09 | 1825102.76 | 0.315202E+09 | 0.945865E+09 | 2958936.82 |
May | 0.324331E+09 | 0.00 | 0.324331E+09 | 0.995040E+09 | 9305637.68 |
June | 0.312739E+09 | 0.00 | 0.312739E+09 | 0.936322E+09 | 10907660.21 |
July | 0.332906E+09 | 0.00 | 0.332906E+09 | 0.865730E+09 | 22844260.30 |
August | 0.323686E+09 | 27302.16 | 0.323659E+09 | 0.870667E+09 | 8325904.07 |
September | 0.345671E+09 | 9472244.64 | 0.336199E+09 | 0.922460E+09 | 10765762.93 |
October | 0.465181E+09 | 70585523.65 | 0.394596E+09 | 0.112365E+10 | 16090963.59 |
November | 0.594193E+09 | 0.183582E+09 | 0.410611E+09 | 0.134774E+10 | 37597045.62 |
December | 0.751750E+09 | 0.320870E+09 | 0.430880E+09 | 0.163822E+10 | 98177866.70 |
Annual Sum or Average | 0.553086E+10 | 0.114848E+10 | 0.438239E+10 | 0.138607E+11 | 0.367438E+09 |
Minimum of Months | 0.312739E+09 | 0.00 | 0.312739E+09 | 0.865730E+09 | 2958936.82 |
Maximum of Months | 0.751750E+09 | 0.320870E+09 | 0.437176E+09 | 0.166035E+10 | 98177866.70 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 815.68 | 53.74 | 378.91 | 157.79 | 221.13 | 0.00 | 0.00 |
February | 736.63 | 40.53 | 320.52 | 103.37 | 217.15 | 0.00 | 0.00 |
March | 566.82 | 20.90 | 223.51 | 33.17 | 190.34 | 0.00 | 0.00 |
April | 455.25 | 2.71 | 165.70 | 0.95 | 164.74 | 0.00 | 0.00 |
May | 471.75 | 6.10 | 164.05 | 0.00 | 164.05 | 0.00 | 0.00 |
June | 458.04 | 7.20 | 163.46 | 0.00 | 163.46 | 0.00 | 0.00 |
July | 419.52 | 16.53 | 168.39 | 0.00 | 168.39 | 0.00 | 0.00 |
August | 413.48 | 7.86 | 163.72 | 0.01 | 163.71 | 0.00 | 0.00 |
September | 455.57 | 9.19 | 180.67 | 4.95 | 175.72 | 0.00 | 0.00 |
October | 546.83 | 14.27 | 235.29 | 35.70 | 199.59 | 0.00 | 0.00 |
November | 681.23 | 28.26 | 310.57 | 95.95 | 214.61 | 0.00 | 0.00 |
December | 804.91 | 61.93 | 380.24 | 162.30 | 217.94 | 0.00 | 0.00 |
Annual Sum or Average | 568.05 | 22.40 | 237.60 | 49.34 | 188.26 | 0.00 | 0.00 |
Minimum of Months | 413.48 | 2.71 | 163.46 | 0.00 | 163.46 | 0.00 | 0.00 |
Maximum of Months | 815.68 | 61.93 | 380.24 | 162.30 | 221.13 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2288.06 | 154.03 | 1066.99 | 444.32 | 622.68 | 0.00 | 0.00 |
February | 2073.04 | 111.04 | 902.57 | 291.08 | 611.49 | 0.00 | 0.00 |
March | 1612.67 | 57.16 | 629.40 | 93.41 | 535.99 | 0.00 | 0.00 |
April | 1312.41 | 9.87 | 466.60 | 2.69 | 463.91 | 0.00 | 0.00 |
May | 1348.75 | 21.79 | 461.95 | 0.00 | 461.95 | 0.00 | 0.00 |
June | 1318.29 | 22.74 | 460.29 | 0.00 | 460.29 | 0.00 | 0.00 |
July | 1198.55 | 52.99 | 474.16 | 0.00 | 474.16 | 0.00 | 0.00 |
August | 1175.68 | 29.46 | 461.03 | 0.04 | 460.99 | 0.00 | 0.00 |
September | 1299.28 | 33.40 | 508.76 | 13.94 | 494.81 | 0.00 | 0.00 |
October | 1542.16 | 50.91 | 662.57 | 100.54 | 562.03 | 0.00 | 0.00 |
November | 1916.33 | 87.82 | 874.53 | 270.20 | 604.34 | 0.00 | 0.00 |
December | 2256.91 | 179.47 | 1070.73 | 457.02 | 613.71 | 0.00 | 0.00 |
Annual Sum or Average | 1609.70 | 67.52 | 669.07 | 138.93 | 530.13 | 0.00 | 0.00 |
Minimum of Months | 1175.68 | 9.87 | 460.29 | 0.00 | 460.29 | 0.00 | 0.00 |
Maximum of Months | 2288.06 | 179.47 | 1070.73 | 457.02 | 622.68 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3107.42 | 173.42 | 1386.08 | 577.19 | 808.89 | 0.00 | 0.00 |
February | 2822.02 | 123.40 | 1172.49 | 378.13 | 794.36 | 0.00 | 0.00 |
March | 2199.57 | 59.80 | 817.62 | 121.34 | 696.28 | 0.00 | 0.00 |
April | 1782.76 | 11.57 | 606.13 | 3.49 | 602.65 | 0.00 | 0.00 |
May | 1806.49 | 26.36 | 600.10 | 0.00 | 600.10 | 0.00 | 0.00 |
June | 1752.10 | 30.03 | 597.94 | 0.00 | 597.94 | 0.00 | 0.00 |
July | 1590.99 | 66.88 | 615.96 | 0.00 | 615.96 | 0.00 | 0.00 |
August | 1572.75 | 34.34 | 598.91 | 0.05 | 598.85 | 0.00 | 0.00 |
September | 1758.46 | 35.34 | 660.90 | 18.11 | 642.79 | 0.00 | 0.00 |
October | 2090.72 | 49.58 | 860.71 | 130.60 | 730.11 | 0.00 | 0.00 |
November | 2604.60 | 94.33 | 1136.07 | 351.00 | 785.07 | 0.00 | 0.00 |
December | 3060.51 | 205.86 | 1390.94 | 593.70 | 797.25 | 0.00 | 0.00 |
Annual Sum or Average | 2175.99 | 75.88 | 869.15 | 180.48 | 688.67 | 0.00 | 0.00 |
Minimum of Months | 1572.75 | 11.57 | 597.94 | 0.00 | 597.94 | 0.00 | 0.00 |
Maximum of Months | 3107.42 | 205.86 | 1390.94 | 593.70 | 808.89 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 421.77 | 10.97 | 178.38 | 67.64 | 110.74 | 0.00 | 0.00 |
February | 437.29 | 3.81 | 176.93 | 60.66 | 116.27 | 0.00 | 0.00 |
March | 450.25 | 0.68 | 171.27 | 56.69 | 114.58 | 0.00 | 0.00 |
April | 447.39 | 0.04 | 160.49 | 49.03 | 111.46 | 0.00 | 0.00 |
May | 417.24 | 0.10 | 141.30 | 32.31 | 108.99 | 0.00 | 0.00 |
June | 429.44 | 0.15 | 150.18 | 40.60 | 109.57 | 0.00 | 0.00 |
July | 354.62 | 0.32 | 133.76 | 23.65 | 110.11 | 0.00 | 0.00 |
August | 373.22 | 0.13 | 141.95 | 32.57 | 109.38 | 0.00 | 0.00 |
September | 371.96 | 0.08 | 138.01 | 29.32 | 108.69 | 0.00 | 0.00 |
October | 361.49 | 0.29 | 142.70 | 31.89 | 110.81 | 0.00 | 0.00 |
November | 378.39 | 2.27 | 155.18 | 44.58 | 110.61 | 0.00 | 0.00 |
December | 399.06 | 14.13 | 171.24 | 63.57 | 107.67 | 0.00 | 0.00 |
Annual Sum or Average | 403.20 | 2.76 | 154.98 | 44.28 | 110.70 | 0.00 | 0.00 |
Minimum of Months | 354.62 | 0.04 | 133.76 | 23.65 | 107.67 | 0.00 | 0.00 |
Maximum of Months | 450.25 | 14.13 | 178.38 | 67.64 | 116.27 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 326.61 | 10.98 | 131.80 | 36.45 | 95.35 | 0.00 | 0.00 |
February | 364.63 | 3.71 | 143.78 | 40.22 | 103.56 | 0.00 | 0.00 |
March | 419.41 | 0.63 | 158.12 | 50.13 | 107.99 | 0.00 | 0.00 |
April | 451.05 | 0.04 | 162.13 | 49.67 | 112.46 | 0.00 | 0.00 |
May | 440.75 | 0.26 | 152.03 | 36.80 | 115.22 | 0.00 | 0.00 |
June | 474.08 | 0.39 | 170.89 | 51.46 | 119.43 | 0.00 | 0.00 |
July | 380.79 | 0.68 | 146.01 | 28.49 | 117.52 | 0.00 | 0.00 |
August | 384.37 | 0.26 | 147.23 | 34.33 | 112.90 | 0.00 | 0.00 |
September | 363.21 | 0.28 | 134.24 | 28.40 | 105.83 | 0.00 | 0.00 |
October | 327.45 | 0.42 | 126.88 | 24.83 | 102.05 | 0.00 | 0.00 |
November | 312.34 | 2.98 | 122.83 | 25.61 | 97.22 | 0.00 | 0.00 |
December | 302.99 | 14.37 | 123.59 | 31.48 | 92.11 | 0.00 | 0.00 |
Annual Sum or Average | 378.86 | 2.93 | 143.24 | 36.43 | 106.81 | 0.00 | 0.00 |
Minimum of Months | 302.99 | 0.04 | 122.83 | 24.83 | 92.11 | 0.00 | 0.00 |
Maximum of Months | 474.08 | 14.37 | 170.89 | 51.46 | 119.43 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 119.02 | 17.76 | 59.92 | 24.95 | 34.97 | 0.00 | 0.00 |
February | 107.50 | 14.49 | 50.69 | 16.35 | 34.34 | 0.00 | 0.00 |
March | 80.29 | 10.91 | 35.35 | 5.25 | 30.10 | 0.00 | 0.00 |
April | 60.39 | 5.78 | 26.20 | 0.15 | 26.05 | 0.00 | 0.00 |
May | 61.32 | 6.44 | 25.94 | 0.00 | 25.94 | 0.00 | 0.00 |
June | 60.77 | 6.77 | 25.85 | 0.00 | 25.85 | 0.00 | 0.00 |
July | 54.40 | 11.00 | 26.63 | 0.00 | 26.63 | 0.00 | 0.00 |
August | 52.19 | 9.99 | 25.89 | 0.00 | 25.89 | 0.00 | 0.00 |
September | 60.38 | 9.95 | 28.57 | 0.78 | 27.79 | 0.00 | 0.00 |
October | 74.14 | 12.37 | 37.21 | 5.65 | 31.56 | 0.00 | 0.00 |
November | 97.25 | 14.11 | 49.11 | 15.17 | 33.94 | 0.00 | 0.00 |
December | 117.65 | 19.95 | 60.13 | 25.67 | 34.47 | 0.00 | 0.00 |
Annual Sum or Average | 78.64 | 11.63 | 37.57 | 7.80 | 29.77 | 0.00 | 0.00 |
Minimum of Months | 52.19 | 5.78 | 25.85 | 0.00 | 25.85 | 0.00 | 0.00 |
Maximum of Months | 119.02 | 19.95 | 60.13 | 25.67 | 34.97 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 67.74 | 2.30 | 22.67 | 0.00 | 22.67 | 0.00 | 0.00 |
February | 75.88 | 0.47 | 24.18 | 0.00 | 24.18 | 0.00 | 0.00 |
March | 86.09 | 0.07 | 24.84 | 0.00 | 24.84 | 0.00 | 0.00 |
April | 98.99 | 0.00 | 27.53 | 0.66 | 26.86 | 0.00 | 0.00 |
May | 116.04 | 0.02 | 34.53 | 3.60 | 30.94 | 0.00 | 0.00 |
June | 132.03 | 0.04 | 42.43 | 8.68 | 33.75 | 0.00 | 0.00 |
July | 104.90 | 0.06 | 36.43 | 3.87 | 32.57 | 0.00 | 0.00 |
August | 92.99 | 0.01 | 30.13 | 1.41 | 28.71 | 0.00 | 0.00 |
September | 83.85 | 0.02 | 25.56 | 0.04 | 25.51 | 0.00 | 0.00 |
October | 75.54 | 0.01 | 24.57 | 0.00 | 24.57 | 0.00 | 0.00 |
November | 70.26 | 0.46 | 23.24 | 0.00 | 23.24 | 0.00 | 0.00 |
December | 63.78 | 3.06 | 22.03 | 0.00 | 22.03 | 0.00 | 0.00 |
Annual Sum or Average | 89.04 | 0.55 | 28.19 | 1.53 | 26.67 | 0.00 | 0.00 |
Minimum of Months | 63.78 | 0.00 | 22.03 | 0.00 | 22.03 | 0.00 | 0.00 |
Maximum of Months | 132.03 | 3.06 | 42.43 | 8.68 | 33.75 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 419.24 | 10.71 | 176.90 | 65.58 | 111.32 | 0.00 | 0.00 |
February | 442.56 | 3.69 | 178.96 | 62.77 | 116.19 | 0.00 | 0.00 |
March | 449.72 | 0.64 | 170.40 | 55.96 | 114.44 | 0.00 | 0.00 |
April | 449.74 | 0.01 | 160.08 | 48.76 | 111.33 | 0.00 | 0.00 |
May | 420.97 | 0.08 | 142.04 | 33.22 | 108.82 | 0.00 | 0.00 |
June | 429.43 | 0.12 | 148.98 | 38.41 | 110.57 | 0.00 | 0.00 |
July | 354.45 | 0.26 | 133.06 | 22.40 | 110.67 | 0.00 | 0.00 |
August | 374.97 | 0.10 | 142.04 | 32.24 | 109.80 | 0.00 | 0.00 |
September | 375.56 | 0.07 | 138.75 | 29.08 | 109.67 | 0.00 | 0.00 |
October | 363.99 | 0.25 | 143.19 | 31.86 | 111.32 | 0.00 | 0.00 |
November | 378.95 | 2.17 | 154.98 | 44.86 | 110.12 | 0.00 | 0.00 |
December | 397.99 | 13.73 | 170.84 | 62.81 | 108.02 | 0.00 | 0.00 |
Annual Sum or Average | 404.45 | 2.67 | 154.87 | 43.88 | 110.99 | 0.00 | 0.00 |
Minimum of Months | 354.45 | 0.01 | 133.06 | 22.40 | 108.02 | 0.00 | 0.00 |
Maximum of Months | 449.74 | 13.73 | 178.96 | 65.58 | 116.19 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 322.23 | 10.33 | 130.32 | 34.38 | 95.94 | 0.00 | 0.00 |
February | 368.55 | 3.48 | 145.82 | 42.34 | 103.48 | 0.00 | 0.00 |
March | 418.76 | 0.60 | 157.25 | 49.40 | 107.85 | 0.00 | 0.00 |
April | 453.42 | 0.01 | 161.73 | 49.40 | 112.33 | 0.00 | 0.00 |
May | 444.51 | 0.22 | 152.76 | 37.71 | 115.05 | 0.00 | 0.00 |
June | 474.09 | 0.34 | 169.70 | 49.27 | 120.43 | 0.00 | 0.00 |
July | 380.62 | 0.59 | 145.31 | 27.23 | 118.08 | 0.00 | 0.00 |
August | 386.16 | 0.22 | 147.33 | 34.01 | 113.32 | 0.00 | 0.00 |
September | 366.79 | 0.25 | 134.97 | 28.16 | 106.82 | 0.00 | 0.00 |
October | 329.88 | 0.39 | 127.37 | 24.80 | 102.56 | 0.00 | 0.00 |
November | 312.44 | 2.86 | 122.63 | 25.89 | 96.74 | 0.00 | 0.00 |
December | 300.23 | 13.60 | 123.18 | 30.72 | 92.46 | 0.00 | 0.00 |
Annual Sum or Average | 379.66 | 2.76 | 143.13 | 36.04 | 107.10 | 0.00 | 0.00 |
Minimum of Months | 300.23 | 0.01 | 122.63 | 24.80 | 92.46 | 0.00 | 0.00 |
Maximum of Months | 474.09 | 13.60 | 169.70 | 49.40 | 120.43 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 431.28 | 22.33 | 178.95 | 54.07 | 124.88 | 0.00 | 0.00 |
February | 418.53 | 13.31 | 162.22 | 35.42 | 126.80 | 0.00 | 0.00 |
March | 383.76 | 4.19 | 130.39 | 11.37 | 119.02 | 0.00 | 0.00 |
April | 376.20 | 0.52 | 116.41 | 1.76 | 114.65 | 0.00 | 0.00 |
May | 412.89 | 1.69 | 131.02 | 7.79 | 123.23 | 0.00 | 0.00 |
June | 439.13 | 2.06 | 147.94 | 18.81 | 129.12 | 0.00 | 0.00 |
July | 371.55 | 3.73 | 136.63 | 8.37 | 128.25 | 0.00 | 0.00 |
August | 346.95 | 1.39 | 121.37 | 3.07 | 118.30 | 0.00 | 0.00 |
September | 343.60 | 1.59 | 117.27 | 1.79 | 115.48 | 0.00 | 0.00 |
October | 353.68 | 2.64 | 133.84 | 12.23 | 121.61 | 0.00 | 0.00 |
November | 388.68 | 8.87 | 156.77 | 32.88 | 123.89 | 0.00 | 0.00 |
December | 419.38 | 27.30 | 178.00 | 55.61 | 122.39 | 0.00 | 0.00 |
Annual Sum or Average | 390.28 | 7.47 | 142.49 | 20.21 | 122.28 | 0.00 | 0.00 |
Minimum of Months | 343.60 | 0.52 | 116.41 | 1.76 | 114.65 | 0.00 | 0.00 |
Maximum of Months | 439.13 | 27.30 | 178.95 | 55.61 | 129.12 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 418.18 | 9.22 | 178.38 | 67.64 | 110.74 | 0.00 | 0.00 |
February | 434.61 | 2.52 | 176.93 | 60.66 | 116.27 | 0.00 | 0.00 |
March | 448.64 | 0.34 | 171.27 | 56.69 | 114.58 | 0.00 | 0.00 |
April | 445.71 | 0.01 | 160.49 | 49.03 | 111.46 | 0.00 | 0.00 |
May | 416.06 | 0.07 | 141.30 | 32.31 | 108.99 | 0.00 | 0.00 |
June | 428.63 | 0.08 | 150.18 | 40.60 | 109.57 | 0.00 | 0.00 |
July | 352.35 | 0.18 | 133.76 | 23.65 | 110.11 | 0.00 | 0.00 |
August | 371.32 | 0.06 | 141.95 | 32.57 | 109.38 | 0.00 | 0.00 |
September | 369.19 | 0.02 | 138.01 | 29.32 | 108.69 | 0.00 | 0.00 |
October | 358.75 | 0.13 | 142.70 | 31.89 | 110.81 | 0.00 | 0.00 |
November | 375.45 | 1.53 | 155.18 | 44.58 | 110.61 | 0.00 | 0.00 |
December | 395.12 | 12.01 | 171.24 | 63.57 | 107.67 | 0.00 | 0.00 |
Annual Sum or Average | 400.85 | 2.20 | 154.98 | 44.28 | 110.70 | 0.00 | 0.00 |
Minimum of Months | 352.35 | 0.01 | 133.76 | 23.65 | 107.67 | 0.00 | 0.00 |
Maximum of Months | 448.64 | 12.01 | 178.38 | 67.64 | 116.27 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 324.01 | 9.15 | 131.80 | 36.45 | 95.35 | 0.00 | 0.00 |
February | 362.71 | 2.42 | 143.78 | 40.22 | 103.56 | 0.00 | 0.00 |
March | 417.89 | 0.34 | 158.12 | 50.13 | 107.99 | 0.00 | 0.00 |
April | 448.96 | 0.01 | 162.13 | 49.67 | 112.46 | 0.00 | 0.00 |
May | 439.04 | 0.24 | 152.03 | 36.80 | 115.22 | 0.00 | 0.00 |
June | 472.45 | 0.37 | 170.89 | 51.46 | 119.43 | 0.00 | 0.00 |
July | 378.08 | 0.60 | 146.01 | 28.49 | 117.52 | 0.00 | 0.00 |
August | 382.12 | 0.24 | 147.23 | 34.33 | 112.90 | 0.00 | 0.00 |
September | 360.43 | 0.32 | 134.24 | 28.40 | 105.83 | 0.00 | 0.00 |
October | 325.05 | 0.37 | 126.88 | 24.83 | 102.05 | 0.00 | 0.00 |
November | 310.15 | 2.39 | 122.83 | 25.61 | 97.22 | 0.00 | 0.00 |
December | 300.14 | 12.24 | 123.59 | 31.48 | 92.11 | 0.00 | 0.00 |
Annual Sum or Average | 376.64 | 2.41 | 143.24 | 36.43 | 106.81 | 0.00 | 0.00 |
Minimum of Months | 300.14 | 0.01 | 122.83 | 24.83 | 92.11 | 0.00 | 0.00 |
Maximum of Months | 472.45 | 12.24 | 170.89 | 51.46 | 119.43 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 256.21 | 4.43 | 109.87 | 45.75 | 64.12 | 0.00 | 0.00 |
February | 238.08 | 1.03 | 92.94 | 29.97 | 62.97 | 0.00 | 0.00 |
March | 197.73 | 0.13 | 64.81 | 9.62 | 55.19 | 0.00 | 0.00 |
April | 170.59 | 0.00 | 48.05 | 0.28 | 47.77 | 0.00 | 0.00 |
May | 172.13 | 0.02 | 47.57 | 0.00 | 47.57 | 0.00 | 0.00 |
June | 169.77 | 0.01 | 47.40 | 0.00 | 47.40 | 0.00 | 0.00 |
July | 147.43 | 0.03 | 48.83 | 0.00 | 48.83 | 0.00 | 0.00 |
August | 148.28 | 0.01 | 47.48 | 0.00 | 47.47 | 0.00 | 0.00 |
September | 160.35 | 0.00 | 52.39 | 1.44 | 50.95 | 0.00 | 0.00 |
October | 182.04 | 0.03 | 68.23 | 10.35 | 57.88 | 0.00 | 0.00 |
November | 219.04 | 0.61 | 90.06 | 27.82 | 62.23 | 0.00 | 0.00 |
December | 250.31 | 5.79 | 110.26 | 47.06 | 63.20 | 0.00 | 0.00 |
Annual Sum or Average | 192.43 | 1.02 | 68.90 | 14.31 | 54.59 | 0.00 | 0.00 |
Minimum of Months | 147.43 | 0.00 | 47.40 | 0.00 | 47.40 | 0.00 | 0.00 |
Maximum of Months | 256.21 | 5.79 | 110.26 | 47.06 | 64.12 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 491.80 | 72.34 | 198.34 | 0.00 | 198.34 | 0.00 | 0.00 |
February | 549.90 | 48.63 | 211.58 | 0.00 | 211.58 | 0.00 | 0.00 |
March | 601.39 | 23.44 | 217.29 | 0.01 | 217.28 | 0.00 | 0.00 |
April | 693.85 | 5.59 | 240.82 | 5.80 | 235.01 | 0.00 | 0.00 |
May | 846.49 | 12.29 | 302.12 | 31.47 | 270.65 | 0.00 | 0.00 |
June | 986.37 | 13.12 | 371.24 | 75.98 | 295.26 | 0.00 | 0.00 |
July | 778.29 | 28.46 | 318.75 | 33.82 | 284.93 | 0.00 | 0.00 |
August | 661.49 | 17.25 | 263.57 | 12.38 | 251.20 | 0.00 | 0.00 |
September | 587.34 | 18.74 | 223.59 | 0.39 | 223.20 | 0.00 | 0.00 |
October | 525.22 | 28.00 | 214.91 | 0.00 | 214.91 | 0.00 | 0.00 |
November | 499.52 | 41.99 | 203.35 | 0.00 | 203.35 | 0.00 | 0.00 |
December | 470.35 | 86.73 | 192.69 | 0.00 | 192.69 | 0.00 | 0.00 |
Annual Sum or Average | 641.19 | 33.07 | 246.66 | 13.35 | 233.31 | 0.00 | 0.00 |
Minimum of Months | 470.35 | 5.59 | 192.69 | 0.00 | 192.69 | 0.00 | 0.00 |
Maximum of Months | 986.37 | 86.73 | 371.24 | 75.98 | 295.26 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 480.38 | 77.96 | 198.34 | 0.00 | 198.34 | 0.00 | 0.00 |
February | 538.61 | 53.26 | 211.58 | 0.00 | 211.58 | 0.00 | 0.00 |
March | 588.42 | 27.22 | 217.29 | 0.01 | 217.28 | 0.00 | 0.00 |
April | 678.60 | 6.79 | 240.82 | 5.80 | 235.01 | 0.00 | 0.00 |
May | 832.13 | 14.49 | 302.12 | 31.47 | 270.65 | 0.00 | 0.00 |
June | 972.69 | 15.19 | 371.24 | 75.98 | 295.26 | 0.00 | 0.00 |
July | 765.11 | 32.88 | 318.75 | 33.82 | 284.93 | 0.00 | 0.00 |
August | 645.94 | 21.26 | 263.57 | 12.38 | 251.20 | 0.00 | 0.00 |
September | 573.20 | 22.81 | 223.59 | 0.39 | 223.20 | 0.00 | 0.00 |
October | 511.67 | 33.59 | 214.91 | 0.00 | 214.91 | 0.00 | 0.00 |
November | 487.54 | 47.56 | 203.35 | 0.00 | 203.35 | 0.00 | 0.00 |
December | 459.16 | 93.11 | 192.69 | 0.00 | 192.69 | 0.00 | 0.00 |
Annual Sum or Average | 627.97 | 37.20 | 246.66 | 13.35 | 233.31 | 0.00 | 0.00 |
Minimum of Months | 459.16 | 6.79 | 192.69 | 0.00 | 192.69 | 0.00 | 0.00 |
Maximum of Months | 972.69 | 93.11 | 371.24 | 75.98 | 295.26 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 792.50 | 55.80 | 307.21 | 99.96 | 207.25 | 0.00 | 0.00 |
February | 858.11 | 38.60 | 324.76 | 105.10 | 219.66 | 0.00 | 0.00 |
March | 879.22 | 21.27 | 327.63 | 105.35 | 222.28 | 0.00 | 0.00 |
April | 903.45 | 6.00 | 321.79 | 98.15 | 223.64 | 0.00 | 0.00 |
May | 860.33 | 10.91 | 294.78 | 70.92 | 223.86 | 0.00 | 0.00 |
June | 907.10 | 11.73 | 318.67 | 87.67 | 230.99 | 0.00 | 0.00 |
July | 763.08 | 21.50 | 278.35 | 49.62 | 228.73 | 0.00 | 0.00 |
August | 759.63 | 15.04 | 289.36 | 66.25 | 223.11 | 0.00 | 0.00 |
September | 762.99 | 16.26 | 273.71 | 57.23 | 216.48 | 0.00 | 0.00 |
October | 706.41 | 22.48 | 270.54 | 56.66 | 213.88 | 0.00 | 0.00 |
November | 733.95 | 31.68 | 277.60 | 70.75 | 206.85 | 0.00 | 0.00 |
December | 758.34 | 66.19 | 294.01 | 93.53 | 200.48 | 0.00 | 0.00 |
Annual Sum or Average | 806.46 | 26.47 | 297.99 | 79.91 | 218.07 | 0.00 | 0.00 |
Minimum of Months | 706.41 | 6.00 | 270.54 | 49.62 | 200.48 | 0.00 | 0.00 |
Maximum of Months | 907.10 | 66.19 | 327.63 | 105.35 | 230.99 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 787.95 | 50.45 | 347.68 | 116.47 | 231.22 | 0.00 | 0.00 |
February | 751.22 | 33.25 | 309.12 | 76.30 | 232.82 | 0.00 | 0.00 |
March | 653.37 | 12.11 | 239.47 | 24.49 | 214.98 | 0.00 | 0.00 |
April | 608.52 | 1.88 | 204.86 | 2.69 | 202.17 | 0.00 | 0.00 |
May | 669.18 | 5.66 | 224.66 | 10.79 | 213.87 | 0.00 | 0.00 |
June | 705.73 | 6.78 | 247.92 | 26.05 | 221.87 | 0.00 | 0.00 |
July | 597.37 | 13.85 | 233.56 | 11.59 | 221.97 | 0.00 | 0.00 |
August | 562.87 | 5.06 | 211.20 | 4.25 | 206.95 | 0.00 | 0.00 |
September | 564.10 | 6.80 | 210.01 | 3.79 | 206.22 | 0.00 | 0.00 |
October | 606.30 | 9.96 | 247.35 | 26.35 | 221.00 | 0.00 | 0.00 |
November | 693.25 | 24.02 | 298.95 | 70.83 | 228.12 | 0.00 | 0.00 |
December | 772.68 | 60.42 | 346.73 | 119.80 | 226.93 | 0.00 | 0.00 |
Annual Sum or Average | 663.90 | 19.17 | 259.94 | 40.99 | 218.94 | 0.00 | 0.00 |
Minimum of Months | 562.87 | 1.88 | 204.86 | 2.69 | 202.17 | 0.00 | 0.00 |
Maximum of Months | 787.95 | 60.42 | 347.68 | 119.80 | 232.82 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.218472E+10 | 0.143946E+09 | 0.101488E+10 | 0.422614E+09 | 0.592265E+09 | 0.00 | 0.00 |
February | 0.178205E+10 | 98060683.94 | 0.775409E+09 | 0.250070E+09 | 0.525339E+09 | 0.00 | 0.00 |
March | 0.151817E+10 | 55987543.51 | 0.598658E+09 | 88846440.13 | 0.509811E+09 | 0.00 | 0.00 |
April | 0.118002E+10 | 7013914.13 | 0.429490E+09 | 2472579.53 | 0.427018E+09 | 0.00 | 0.00 |
May | 0.126353E+10 | 16326729.18 | 0.439386E+09 | 0.00 | 0.439386E+09 | 0.00 | 0.00 |
June | 0.118723E+10 | 18655585.16 | 0.423681E+09 | 0.00 | 0.423681E+09 | 0.00 | 0.00 |
July | 0.112364E+10 | 44271401.06 | 0.451004E+09 | 0.00 | 0.451004E+09 | 0.00 | 0.00 |
August | 0.110747E+10 | 21046867.76 | 0.438513E+09 | 36987.92 | 0.438476E+09 | 0.00 | 0.00 |
September | 0.118084E+10 | 23815457.58 | 0.468298E+09 | 12832635.36 | 0.455465E+09 | 0.00 | 0.00 |
October | 0.146463E+10 | 38216026.67 | 0.630206E+09 | 95626572.27 | 0.534580E+09 | 0.00 | 0.00 |
November | 0.176575E+10 | 73241411.04 | 0.804987E+09 | 0.248710E+09 | 0.556277E+09 | 0.00 | 0.00 |
December | 0.215587E+10 | 0.165869E+09 | 0.101844E+10 | 0.434702E+09 | 0.583736E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.179139E+11 | 0.706451E+09 | 0.749295E+10 | 0.155591E+10 | 0.593704E+10 | 0.00 | 0.00 |
Minimum of Months | 0.110747E+10 | 7013914.13 | 0.423681E+09 | 0.00 | 0.423681E+09 | 0.00 | 0.00 |
Maximum of Months | 0.218472E+10 | 0.165869E+09 | 0.101844E+10 | 0.434702E+09 | 0.592265E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.612835E+10 | 0.412564E+09 | 0.285783E+10 | 0.119005E+10 | 0.166778E+10 | 0.00 | 0.00 |
February | 0.501509E+10 | 0.268617E+09 | 0.218350E+10 | 0.704181E+09 | 0.147932E+10 | 0.00 | 0.00 |
March | 0.431937E+10 | 0.153093E+09 | 0.168578E+10 | 0.250186E+09 | 0.143560E+10 | 0.00 | 0.00 |
April | 0.340178E+10 | 25572490.93 | 0.120942E+10 | 6962620.92 | 0.120245E+10 | 0.00 | 0.00 |
May | 0.361250E+10 | 58350531.60 | 0.123728E+10 | 0.00 | 0.123728E+10 | 0.00 | 0.00 |
June | 0.341702E+10 | 58953394.42 | 0.119306E+10 | 0.00 | 0.119306E+10 | 0.00 | 0.00 |
July | 0.321019E+10 | 0.141940E+09 | 0.127000E+10 | 0.00 | 0.127000E+10 | 0.00 | 0.00 |
August | 0.314895E+10 | 78915553.82 | 0.123482E+10 | 104155.55 | 0.123472E+10 | 0.00 | 0.00 |
September | 0.336773E+10 | 86583377.90 | 0.131870E+10 | 36135855.08 | 0.128256E+10 | 0.00 | 0.00 |
October | 0.413052E+10 | 0.136357E+09 | 0.177462E+10 | 0.269278E+09 | 0.150534E+10 | 0.00 | 0.00 |
November | 0.496712E+10 | 0.227623E+09 | 0.226679E+10 | 0.700352E+09 | 0.156644E+10 | 0.00 | 0.00 |
December | 0.604492E+10 | 0.480686E+09 | 0.286785E+10 | 0.122409E+10 | 0.164376E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.507635E+11 | 0.212926E+10 | 0.210997E+11 | 0.438134E+10 | 0.167183E+11 | 0.00 | 0.00 |
Minimum of Months | 0.314895E+10 | 25572490.93 | 0.119306E+10 | 0.00 | 0.119306E+10 | 0.00 | 0.00 |
Maximum of Months | 0.612835E+10 | 0.480686E+09 | 0.286785E+10 | 0.122409E+10 | 0.166778E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.832291E+10 | 0.464480E+09 | 0.371249E+10 | 0.154595E+10 | 0.216654E+10 | 0.00 | 0.00 |
February | 0.682703E+10 | 0.298532E+09 | 0.283649E+10 | 0.914771E+09 | 0.192172E+10 | 0.00 | 0.00 |
March | 0.589133E+10 | 0.160180E+09 | 0.218993E+10 | 0.325005E+09 | 0.186492E+10 | 0.00 | 0.00 |
April | 0.462092E+10 | 29990168.97 | 0.157110E+10 | 9044840.82 | 0.156206E+10 | 0.00 | 0.00 |
May | 0.483849E+10 | 70591411.08 | 0.160730E+10 | 0.00 | 0.160730E+10 | 0.00 | 0.00 |
June | 0.454143E+10 | 77842349.43 | 0.154985E+10 | 0.00 | 0.154985E+10 | 0.00 | 0.00 |
July | 0.426131E+10 | 0.179123E+09 | 0.164980E+10 | 0.00 | 0.164980E+10 | 0.00 | 0.00 |
August | 0.421245E+10 | 91965838.21 | 0.160411E+10 | 135303.99 | 0.160397E+10 | 0.00 | 0.00 |
September | 0.455792E+10 | 91601152.16 | 0.171306E+10 | 46942532.26 | 0.166612E+10 | 0.00 | 0.00 |
October | 0.559977E+10 | 0.132783E+09 | 0.230533E+10 | 0.349808E+09 | 0.195552E+10 | 0.00 | 0.00 |
November | 0.675113E+10 | 0.244513E+09 | 0.294469E+10 | 0.909796E+09 | 0.203489E+10 | 0.00 | 0.00 |
December | 0.819727E+10 | 0.551375E+09 | 0.372551E+10 | 0.159016E+10 | 0.213534E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.686220E+11 | 0.239298E+10 | 0.274097E+11 | 0.569162E+10 | 0.217180E+11 | 0.00 | 0.00 |
Minimum of Months | 0.421245E+10 | 29990168.97 | 0.154985E+10 | 0.00 | 0.154985E+10 | 0.00 | 0.00 |
Maximum of Months | 0.832291E+10 | 0.551375E+09 | 0.372551E+10 | 0.159016E+10 | 0.216654E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.112966E+10 | 29387285.58 | 0.477776E+09 | 0.181179E+09 | 0.296597E+09 | 0.00 | 0.00 |
February | 0.105790E+10 | 9206245.88 | 0.428026E+09 | 0.146750E+09 | 0.281277E+09 | 0.00 | 0.00 |
March | 0.120594E+10 | 1815265.63 | 0.458725E+09 | 0.151829E+09 | 0.306896E+09 | 0.00 | 0.00 |
April | 0.115964E+10 | 96410.58 | 0.415983E+09 | 0.127091E+09 | 0.288892E+09 | 0.00 | 0.00 |
May | 0.111753E+10 | 266095.51 | 0.378460E+09 | 86531119.76 | 0.291929E+09 | 0.00 | 0.00 |
June | 0.111312E+10 | 386284.49 | 0.389256E+09 | 0.105248E+09 | 0.284008E+09 | 0.00 | 0.00 |
July | 0.949818E+09 | 868508.08 | 0.358273E+09 | 63355417.25 | 0.294918E+09 | 0.00 | 0.00 |
August | 0.999636E+09 | 354561.58 | 0.380194E+09 | 87233773.61 | 0.292960E+09 | 0.00 | 0.00 |
September | 0.964127E+09 | 208421.61 | 0.357734E+09 | 76007007.34 | 0.281727E+09 | 0.00 | 0.00 |
October | 0.968219E+09 | 766101.88 | 0.382207E+09 | 85417110.97 | 0.296790E+09 | 0.00 | 0.00 |
November | 0.980779E+09 | 5885263.26 | 0.402232E+09 | 0.115544E+09 | 0.286689E+09 | 0.00 | 0.00 |
December | 0.106885E+10 | 37839369.52 | 0.458652E+09 | 0.170264E+09 | 0.288388E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.127152E+11 | 87079813.60 | 0.488752E+10 | 0.139645E+10 | 0.349107E+10 | 0.00 | 0.00 |
Minimum of Months | 0.949818E+09 | 96410.58 | 0.357734E+09 | 63355417.25 | 0.281277E+09 | 0.00 | 0.00 |
Maximum of Months | 0.120594E+10 | 37839369.52 | 0.477776E+09 | 0.181179E+09 | 0.306896E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.874780E+09 | 29403612.72 | 0.353011E+09 | 97620505.06 | 0.255391E+09 | 0.00 | 0.00 |
February | 0.882125E+09 | 8981674.87 | 0.347838E+09 | 97306347.91 | 0.250532E+09 | 0.00 | 0.00 |
March | 0.112336E+10 | 1693973.51 | 0.423502E+09 | 0.134267E+09 | 0.289236E+09 | 0.00 | 0.00 |
April | 0.116911E+10 | 97429.97 | 0.420239E+09 | 0.128751E+09 | 0.291488E+09 | 0.00 | 0.00 |
May | 0.118052E+10 | 695913.39 | 0.407188E+09 | 98571341.44 | 0.308617E+09 | 0.00 | 0.00 |
June | 0.122882E+10 | 1013146.34 | 0.442956E+09 | 0.133384E+09 | 0.309573E+09 | 0.00 | 0.00 |
July | 0.101990E+10 | 1811620.60 | 0.391068E+09 | 76295470.63 | 0.314772E+09 | 0.00 | 0.00 |
August | 0.102951E+10 | 698721.47 | 0.394346E+09 | 91962336.82 | 0.302383E+09 | 0.00 | 0.00 |
September | 0.941432E+09 | 731013.42 | 0.347939E+09 | 73615512.48 | 0.274324E+09 | 0.00 | 0.00 |
October | 0.877037E+09 | 1135042.50 | 0.339838E+09 | 66510095.26 | 0.273328E+09 | 0.00 | 0.00 |
November | 0.809581E+09 | 7720247.69 | 0.318373E+09 | 66369645.99 | 0.252004E+09 | 0.00 | 0.00 |
December | 0.811536E+09 | 38483332.15 | 0.331020E+09 | 84315877.95 | 0.246704E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.119477E+11 | 92465728.62 | 0.451732E+10 | 0.114897E+10 | 0.336835E+10 | 0.00 | 0.00 |
Minimum of Months | 0.809581E+09 | 97429.97 | 0.318373E+09 | 66369645.99 | 0.246704E+09 | 0.00 | 0.00 |
Maximum of Months | 0.122882E+10 | 38483332.15 | 0.442956E+09 | 0.134267E+09 | 0.314772E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.318791E+09 | 47572780.73 | 0.160496E+09 | 66833161.06 | 93662786.16 | 0.00 | 0.00 |
February | 0.260072E+09 | 35047286.91 | 0.122626E+09 | 39546664.89 | 83078992.27 | 0.00 | 0.00 |
March | 0.215055E+09 | 29228296.49 | 94673987.22 | 14050379.47 | 80623607.75 | 0.00 | 0.00 |
April | 0.156520E+09 | 14978970.25 | 67921429.52 | 391019.39 | 67530410.13 | 0.00 | 0.00 |
May | 0.164232E+09 | 17245169.69 | 69486232.11 | 0.00 | 69486232.11 | 0.00 | 0.00 |
June | 0.157513E+09 | 17540171.45 | 67002720.86 | 0.00 | 67002720.86 | 0.00 | 0.00 |
July | 0.145712E+09 | 29473026.20 | 71323528.04 | 0.00 | 71323528.04 | 0.00 | 0.00 |
August | 0.139773E+09 | 26754623.29 | 69348227.89 | 5849.35 | 69342378.53 | 0.00 | 0.00 |
September | 0.156497E+09 | 25797036.01 | 74058349.55 | 2029382.34 | 72028967.21 | 0.00 | 0.00 |
October | 0.198565E+09 | 33136685.02 | 99662864.04 | 15122605.09 | 84540258.96 | 0.00 | 0.00 |
November | 0.252083E+09 | 36578164.08 | 0.127303E+09 | 39331600.67 | 87971427.44 | 0.00 | 0.00 |
December | 0.315120E+09 | 53445237.66 | 0.161059E+09 | 68744751.16 | 92314006.95 | 0.00 | 0.00 |
Annual Sum or Average | 0.247993E+10 | 0.366797E+09 | 0.118496E+10 | 0.246055E+09 | 0.938905E+09 | 0.00 | 0.00 |
Minimum of Months | 0.139773E+09 | 14978970.25 | 67002720.86 | 0.00 | 67002720.86 | 0.00 | 0.00 |
Maximum of Months | 0.318791E+09 | 53445237.66 | 0.161059E+09 | 68744751.16 | 93662786.16 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.181445E+09 | 6162318.53 | 60724100.24 | 0.00 | 60724100.24 | 0.00 | 0.00 |
February | 0.183581E+09 | 1140539.82 | 58507357.38 | 0.00 | 58507357.38 | 0.00 | 0.00 |
March | 0.230590E+09 | 195688.46 | 66523193.68 | 3317.10 | 66519876.59 | 0.00 | 0.00 |
April | 0.256592E+09 | 0.00 | 71349170.49 | 1719341.05 | 69629829.44 | 0.00 | 0.00 |
May | 0.310804E+09 | 55827.16 | 92494836.56 | 9633454.15 | 82861382.42 | 0.00 | 0.00 |
June | 0.342226E+09 | 106159.99 | 0.109991E+09 | 22511519.50 | 87479435.91 | 0.00 | 0.00 |
July | 0.280957E+09 | 153590.57 | 97586225.79 | 10353414.93 | 87232810.86 | 0.00 | 0.00 |
August | 0.249056E+09 | 26298.93 | 80694351.16 | 3789203.30 | 76905147.87 | 0.00 | 0.00 |
September | 0.217343E+09 | 44733.60 | 66245541.57 | 116605.50 | 66128936.07 | 0.00 | 0.00 |
October | 0.202325E+09 | 30055.59 | 65795960.95 | 0.00 | 65795960.95 | 0.00 | 0.00 |
November | 0.182121E+09 | 1183749.30 | 60249166.34 | 0.00 | 60249166.34 | 0.00 | 0.00 |
December | 0.170824E+09 | 8192751.56 | 58992615.48 | 0.00 | 58992615.48 | 0.00 | 0.00 |
Annual Sum or Average | 0.280786E+10 | 17291713.52 | 0.889153E+09 | 48126855.52 | 0.841027E+09 | 0.00 | 0.00 |
Minimum of Months | 0.170824E+09 | 0.00 | 58507357.38 | 0.00 | 58507357.38 | 0.00 | 0.00 |
Maximum of Months | 0.342226E+09 | 8192751.56 | 0.109991E+09 | 22511519.50 | 87479435.91 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.112290E+10 | 28675639.45 | 0.473817E+09 | 0.175654E+09 | 0.298162E+09 | 0.00 | 0.00 |
February | 0.107064E+10 | 8933640.57 | 0.432945E+09 | 0.151863E+09 | 0.281082E+09 | 0.00 | 0.00 |
March | 0.120454E+10 | 1720988.02 | 0.456397E+09 | 0.149876E+09 | 0.306521E+09 | 0.00 | 0.00 |
April | 0.116573E+10 | 34526.83 | 0.414939E+09 | 0.126379E+09 | 0.288560E+09 | 0.00 | 0.00 |
May | 0.112753E+10 | 219268.52 | 0.380428E+09 | 88968658.34 | 0.291459E+09 | 0.00 | 0.00 |
June | 0.111308E+10 | 304958.78 | 0.386161E+09 | 99564373.77 | 0.286597E+09 | 0.00 | 0.00 |
July | 0.949372E+09 | 691449.03 | 0.356393E+09 | 59987150.76 | 0.296406E+09 | 0.00 | 0.00 |
August | 0.100433E+10 | 259661.56 | 0.380450E+09 | 86357402.56 | 0.294092E+09 | 0.00 | 0.00 |
September | 0.973448E+09 | 181148.75 | 0.359650E+09 | 75374468.73 | 0.284276E+09 | 0.00 | 0.00 |
October | 0.974921E+09 | 661540.28 | 0.383513E+09 | 85340543.43 | 0.298172E+09 | 0.00 | 0.00 |
November | 0.982235E+09 | 5632546.90 | 0.401718E+09 | 0.116288E+09 | 0.285430E+09 | 0.00 | 0.00 |
December | 0.106597E+10 | 36777884.84 | 0.457568E+09 | 0.168235E+09 | 0.289333E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.127547E+11 | 84093253.53 | 0.488398E+10 | 0.138389E+10 | 0.350009E+10 | 0.00 | 0.00 |
Minimum of Months | 0.949372E+09 | 34526.83 | 0.356393E+09 | 59987150.76 | 0.281082E+09 | 0.00 | 0.00 |
Maximum of Months | 0.120454E+10 | 36777884.84 | 0.473817E+09 | 0.175654E+09 | 0.306521E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.863056E+09 | 27672537.13 | 0.349052E+09 | 92096303.80 | 0.256955E+09 | 0.00 | 0.00 |
February | 0.891602E+09 | 8425761.47 | 0.352756E+09 | 0.102419E+09 | 0.250337E+09 | 0.00 | 0.00 |
March | 0.112160E+10 | 1606599.40 | 0.421174E+09 | 0.132314E+09 | 0.288860E+09 | 0.00 | 0.00 |
April | 0.117528E+10 | 32698.92 | 0.419195E+09 | 0.128039E+09 | 0.291156E+09 | 0.00 | 0.00 |
May | 0.119058E+10 | 596731.72 | 0.409156E+09 | 0.101009E+09 | 0.308147E+09 | 0.00 | 0.00 |
June | 0.122885E+10 | 885514.87 | 0.439862E+09 | 0.127700E+09 | 0.312162E+09 | 0.00 | 0.00 |
July | 0.101946E+10 | 1575811.57 | 0.389188E+09 | 72927204.14 | 0.316260E+09 | 0.00 | 0.00 |
August | 0.103429E+10 | 585804.91 | 0.394602E+09 | 91085965.77 | 0.303516E+09 | 0.00 | 0.00 |
September | 0.950708E+09 | 652447.51 | 0.349855E+09 | 72982973.88 | 0.276872E+09 | 0.00 | 0.00 |
October | 0.883548E+09 | 1050604.85 | 0.341144E+09 | 66433527.72 | 0.274710E+09 | 0.00 | 0.00 |
November | 0.809838E+09 | 7402839.56 | 0.317860E+09 | 67113721.24 | 0.250746E+09 | 0.00 | 0.00 |
December | 0.804124E+09 | 36417122.16 | 0.329935E+09 | 82286475.08 | 0.247649E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.119729E+11 | 86904474.08 | 0.451378E+10 | 0.113641E+10 | 0.337737E+10 | 0.00 | 0.00 |
Minimum of Months | 0.804124E+09 | 32698.92 | 0.317860E+09 | 66433527.72 | 0.247649E+09 | 0.00 | 0.00 |
Maximum of Months | 0.122885E+10 | 36417122.16 | 0.439862E+09 | 0.132314E+09 | 0.316260E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.115514E+10 | 59805475.73 | 0.479299E+09 | 0.144809E+09 | 0.334490E+09 | 0.00 | 0.00 |
February | 0.101250E+10 | 32209302.19 | 0.392442E+09 | 85686625.25 | 0.306756E+09 | 0.00 | 0.00 |
March | 0.102787E+10 | 11214004.11 | 0.349244E+09 | 30450450.97 | 0.318793E+09 | 0.00 | 0.00 |
April | 0.975117E+09 | 1355998.70 | 0.301733E+09 | 4571899.53 | 0.297161E+09 | 0.00 | 0.00 |
May | 0.110588E+10 | 4516169.38 | 0.350932E+09 | 20869291.99 | 0.330063E+09 | 0.00 | 0.00 |
June | 0.113823E+10 | 5343453.53 | 0.383454E+09 | 48767499.82 | 0.334686E+09 | 0.00 | 0.00 |
July | 0.995168E+09 | 10000768.13 | 0.365943E+09 | 22428968.45 | 0.343514E+09 | 0.00 | 0.00 |
August | 0.929269E+09 | 3710010.57 | 0.325069E+09 | 8221358.87 | 0.316848E+09 | 0.00 | 0.00 |
September | 0.890605E+09 | 4116161.13 | 0.303974E+09 | 4649713.78 | 0.299324E+09 | 0.00 | 0.00 |
October | 0.947307E+09 | 7066891.94 | 0.358478E+09 | 32766479.77 | 0.325711E+09 | 0.00 | 0.00 |
November | 0.100747E+10 | 22993694.72 | 0.406350E+09 | 85220640.90 | 0.321130E+09 | 0.00 | 0.00 |
December | 0.112326E+10 | 73125058.43 | 0.476767E+09 | 0.148951E+09 | 0.327817E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.123078E+11 | 0.235457E+09 | 0.449368E+10 | 0.637393E+09 | 0.385629E+10 | 0.00 | 0.00 |
Minimum of Months | 0.890605E+09 | 1355998.70 | 0.301733E+09 | 4571899.53 | 0.297161E+09 | 0.00 | 0.00 |
Maximum of Months | 0.115514E+10 | 73125058.43 | 0.479299E+09 | 0.148951E+09 | 0.343514E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.112005E+10 | 24684013.18 | 0.477776E+09 | 0.181179E+09 | 0.296597E+09 | 0.00 | 0.00 |
February | 0.105141E+10 | 6098396.23 | 0.428026E+09 | 0.146750E+09 | 0.281277E+09 | 0.00 | 0.00 |
March | 0.120165E+10 | 899624.31 | 0.458725E+09 | 0.151829E+09 | 0.306896E+09 | 0.00 | 0.00 |
April | 0.115528E+10 | 22522.65 | 0.415983E+09 | 0.127091E+09 | 0.288892E+09 | 0.00 | 0.00 |
May | 0.111436E+10 | 179922.39 | 0.378460E+09 | 86531119.76 | 0.291929E+09 | 0.00 | 0.00 |
June | 0.111101E+10 | 207496.50 | 0.389256E+09 | 0.105248E+09 | 0.284008E+09 | 0.00 | 0.00 |
July | 0.943723E+09 | 481534.62 | 0.358273E+09 | 63355417.25 | 0.294918E+09 | 0.00 | 0.00 |
August | 0.994535E+09 | 172647.28 | 0.380194E+09 | 87233773.61 | 0.292960E+09 | 0.00 | 0.00 |
September | 0.956931E+09 | 51033.73 | 0.357734E+09 | 76007007.34 | 0.281727E+09 | 0.00 | 0.00 |
October | 0.960885E+09 | 357311.59 | 0.382207E+09 | 85417110.97 | 0.296790E+09 | 0.00 | 0.00 |
November | 0.973165E+09 | 3958479.37 | 0.402232E+09 | 0.115544E+09 | 0.286689E+09 | 0.00 | 0.00 |
December | 0.105830E+10 | 32160475.41 | 0.458652E+09 | 0.170264E+09 | 0.288388E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.126413E+11 | 69273457.26 | 0.488752E+10 | 0.139645E+10 | 0.349107E+10 | 0.00 | 0.00 |
Minimum of Months | 0.943723E+09 | 22522.65 | 0.357734E+09 | 63355417.25 | 0.281277E+09 | 0.00 | 0.00 |
Maximum of Months | 0.120165E+10 | 32160475.41 | 0.477776E+09 | 0.181179E+09 | 0.306896E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.867816E+09 | 24517879.55 | 0.353011E+09 | 97620505.06 | 0.255391E+09 | 0.00 | 0.00 |
February | 0.877477E+09 | 5844943.67 | 0.347838E+09 | 97306347.91 | 0.250532E+09 | 0.00 | 0.00 |
March | 0.111928E+10 | 900072.74 | 0.423502E+09 | 0.134267E+09 | 0.289236E+09 | 0.00 | 0.00 |
April | 0.116370E+10 | 20988.86 | 0.420239E+09 | 0.128751E+09 | 0.291488E+09 | 0.00 | 0.00 |
May | 0.117593E+10 | 648952.08 | 0.407188E+09 | 98571341.44 | 0.308617E+09 | 0.00 | 0.00 |
June | 0.122458E+10 | 969801.05 | 0.442956E+09 | 0.133384E+09 | 0.309573E+09 | 0.00 | 0.00 |
July | 0.101265E+10 | 1600216.47 | 0.391068E+09 | 76295470.63 | 0.314772E+09 | 0.00 | 0.00 |
August | 0.102346E+10 | 632879.18 | 0.394346E+09 | 91962336.82 | 0.302383E+09 | 0.00 | 0.00 |
September | 0.934247E+09 | 837074.11 | 0.347939E+09 | 73615512.48 | 0.274324E+09 | 0.00 | 0.00 |
October | 0.870619E+09 | 1000540.52 | 0.339838E+09 | 66510095.26 | 0.273328E+09 | 0.00 | 0.00 |
November | 0.803916E+09 | 6205310.33 | 0.318373E+09 | 66369645.99 | 0.252004E+09 | 0.00 | 0.00 |
December | 0.803905E+09 | 32796008.46 | 0.331020E+09 | 84315877.95 | 0.246704E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.118776E+11 | 75974667.02 | 0.451732E+10 | 0.114897E+10 | 0.336835E+10 | 0.00 | 0.00 |
Minimum of Months | 0.803905E+09 | 20988.86 | 0.318373E+09 | 66369645.99 | 0.246704E+09 | 0.00 | 0.00 |
Maximum of Months | 0.122458E+10 | 32796008.46 | 0.442956E+09 | 0.134267E+09 | 0.314772E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.686235E+09 | 11854647.66 | 0.294287E+09 | 0.122546E+09 | 0.171741E+09 | 0.00 | 0.00 |
February | 0.575957E+09 | 2486035.27 | 0.224848E+09 | 72513142.25 | 0.152334E+09 | 0.00 | 0.00 |
March | 0.529595E+09 | 340029.11 | 0.173595E+09 | 25762909.92 | 0.147832E+09 | 0.00 | 0.00 |
April | 0.442166E+09 | 0.00 | 0.124541E+09 | 716976.88 | 0.123824E+09 | 0.00 | 0.00 |
May | 0.461029E+09 | 54598.68 | 0.127411E+09 | 0.00 | 0.127411E+09 | 0.00 | 0.00 |
June | 0.440057E+09 | 22736.96 | 0.122857E+09 | 0.00 | 0.122857E+09 | 0.00 | 0.00 |
July | 0.394883E+09 | 88947.15 | 0.130780E+09 | 0.00 | 0.130780E+09 | 0.00 | 0.00 |
August | 0.397153E+09 | 13756.96 | 0.127158E+09 | 10725.43 | 0.127147E+09 | 0.00 | 0.00 |
September | 0.415634E+09 | 3437.57 | 0.135794E+09 | 3721094.83 | 0.132073E+09 | 0.00 | 0.00 |
October | 0.487586E+09 | 70237.90 | 0.182743E+09 | 27728953.05 | 0.155014E+09 | 0.00 | 0.00 |
November | 0.567748E+09 | 1582872.44 | 0.233424E+09 | 72118798.45 | 0.161305E+09 | 0.00 | 0.00 |
December | 0.670417E+09 | 15510904.05 | 0.295319E+09 | 0.126051E+09 | 0.169268E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.606846E+10 | 32028203.74 | 0.217276E+10 | 0.451170E+09 | 0.172159E+10 | 0.00 | 0.00 |
Minimum of Months | 0.394883E+09 | 0.00 | 0.122857E+09 | 0.00 | 0.122857E+09 | 0.00 | 0.00 |
Maximum of Months | 0.686235E+09 | 15510904.05 | 0.295319E+09 | 0.126051E+09 | 0.171741E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.131723E+10 | 0.193746E+09 | 0.531245E+09 | 0.00 | 0.531245E+09 | 0.00 | 0.00 |
February | 0.133033E+10 | 0.117647E+09 | 0.511852E+09 | 0.00 | 0.511852E+09 | 0.00 | 0.00 |
March | 0.161076E+10 | 62774432.38 | 0.581979E+09 | 29019.66 | 0.581950E+09 | 0.00 | 0.00 |
April | 0.179847E+10 | 14501288.71 | 0.624199E+09 | 15041670.60 | 0.609157E+09 | 0.00 | 0.00 |
May | 0.226723E+10 | 32913295.49 | 0.809192E+09 | 84278359.80 | 0.724914E+09 | 0.00 | 0.00 |
June | 0.255668E+10 | 34017347.56 | 0.962257E+09 | 0.196942E+09 | 0.765315E+09 | 0.00 | 0.00 |
July | 0.208458E+10 | 76221559.53 | 0.853734E+09 | 90576943.10 | 0.763157E+09 | 0.00 | 0.00 |
August | 0.177173E+10 | 46197147.51 | 0.705955E+09 | 33149878.94 | 0.672805E+09 | 0.00 | 0.00 |
September | 0.152238E+10 | 48583694.87 | 0.579550E+09 | 1020124.24 | 0.578530E+09 | 0.00 | 0.00 |
October | 0.140674E+10 | 75006391.71 | 0.575617E+09 | 0.00 | 0.575617E+09 | 0.00 | 0.00 |
November | 0.129476E+10 | 0.108838E+09 | 0.527090E+09 | 0.00 | 0.527090E+09 | 0.00 | 0.00 |
December | 0.125979E+10 | 0.232297E+09 | 0.516097E+09 | 0.00 | 0.516097E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.202207E+11 | 0.104274E+10 | 0.777877E+10 | 0.421038E+09 | 0.735773E+10 | 0.00 | 0.00 |
Minimum of Months | 0.125979E+10 | 14501288.71 | 0.511852E+09 | 0.00 | 0.511852E+09 | 0.00 | 0.00 |
Maximum of Months | 0.255668E+10 | 0.232297E+09 | 0.962257E+09 | 0.196942E+09 | 0.765315E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.128665E+10 | 0.208798E+09 | 0.531245E+09 | 0.00 | 0.531245E+09 | 0.00 | 0.00 |
February | 0.130301E+10 | 0.128844E+09 | 0.511852E+09 | 0.00 | 0.511852E+09 | 0.00 | 0.00 |
March | 0.157603E+10 | 72915908.94 | 0.581979E+09 | 29019.66 | 0.581950E+09 | 0.00 | 0.00 |
April | 0.175894E+10 | 17610425.72 | 0.624199E+09 | 15041670.60 | 0.609157E+09 | 0.00 | 0.00 |
May | 0.222877E+10 | 38798218.64 | 0.809192E+09 | 84278359.80 | 0.724914E+09 | 0.00 | 0.00 |
June | 0.252121E+10 | 39373623.01 | 0.962257E+09 | 0.196942E+09 | 0.765315E+09 | 0.00 | 0.00 |
July | 0.204927E+10 | 88056519.75 | 0.853734E+09 | 90576943.10 | 0.763157E+09 | 0.00 | 0.00 |
August | 0.173009E+10 | 56936922.95 | 0.705955E+09 | 33149878.94 | 0.672805E+09 | 0.00 | 0.00 |
September | 0.148572E+10 | 59116141.08 | 0.579550E+09 | 1020124.24 | 0.578530E+09 | 0.00 | 0.00 |
October | 0.137045E+10 | 89970290.88 | 0.575617E+09 | 0.00 | 0.575617E+09 | 0.00 | 0.00 |
November | 0.126371E+10 | 0.123268E+09 | 0.527090E+09 | 0.00 | 0.527090E+09 | 0.00 | 0.00 |
December | 0.122981E+10 | 0.249373E+09 | 0.516097E+09 | 0.00 | 0.516097E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.198037E+11 | 0.117306E+10 | 0.777877E+10 | 0.421038E+09 | 0.735773E+10 | 0.00 | 0.00 |
Minimum of Months | 0.122981E+10 | 17610425.72 | 0.511852E+09 | 0.00 | 0.511852E+09 | 0.00 | 0.00 |
Maximum of Months | 0.252121E+10 | 0.249373E+09 | 0.962257E+09 | 0.196942E+09 | 0.765315E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.212264E+10 | 0.149446E+09 | 0.822829E+09 | 0.267738E+09 | 0.555092E+09 | 0.00 | 0.00 |
February | 0.207594E+10 | 93390645.65 | 0.785661E+09 | 0.254268E+09 | 0.531394E+09 | 0.00 | 0.00 |
March | 0.235491E+10 | 56964544.39 | 0.877523E+09 | 0.282171E+09 | 0.595352E+09 | 0.00 | 0.00 |
April | 0.234173E+10 | 15555993.25 | 0.834087E+09 | 0.254401E+09 | 0.579686E+09 | 0.00 | 0.00 |
May | 0.230432E+10 | 29208462.51 | 0.789542E+09 | 0.189965E+09 | 0.599577E+09 | 0.00 | 0.00 |
June | 0.235120E+10 | 30408423.17 | 0.825980E+09 | 0.227250E+09 | 0.598730E+09 | 0.00 | 0.00 |
July | 0.204383E+10 | 57590355.99 | 0.745543E+09 | 0.132906E+09 | 0.612637E+09 | 0.00 | 0.00 |
August | 0.203460E+10 | 40292639.42 | 0.775010E+09 | 0.177431E+09 | 0.597579E+09 | 0.00 | 0.00 |
September | 0.197768E+10 | 42141740.03 | 0.709467E+09 | 0.148347E+09 | 0.561120E+09 | 0.00 | 0.00 |
October | 0.189205E+10 | 60204036.19 | 0.724620E+09 | 0.151765E+09 | 0.572855E+09 | 0.00 | 0.00 |
November | 0.190240E+10 | 82125126.82 | 0.719544E+09 | 0.183392E+09 | 0.536151E+09 | 0.00 | 0.00 |
December | 0.203113E+10 | 0.177286E+09 | 0.787467E+09 | 0.250509E+09 | 0.536957E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.254324E+11 | 0.834615E+09 | 0.939727E+10 | 0.252014E+10 | 0.687713E+10 | 0.00 | 0.00 |
Minimum of Months | 0.189205E+10 | 15555993.25 | 0.709467E+09 | 0.132906E+09 | 0.531394E+09 | 0.00 | 0.00 |
Maximum of Months | 0.235491E+10 | 0.177286E+09 | 0.877523E+09 | 0.282171E+09 | 0.612637E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.211044E+10 | 0.135116E+09 | 0.931235E+09 | 0.311947E+09 | 0.619288E+09 | 0.00 | 0.00 |
February | 0.181735E+10 | 80441310.40 | 0.747825E+09 | 0.184586E+09 | 0.563239E+09 | 0.00 | 0.00 |
March | 0.174999E+10 | 32433910.84 | 0.641399E+09 | 65590804.37 | 0.575808E+09 | 0.00 | 0.00 |
April | 0.157728E+10 | 4881913.85 | 0.531003E+09 | 6981416.84 | 0.524022E+09 | 0.00 | 0.00 |
May | 0.179233E+10 | 15149869.53 | 0.601723E+09 | 28890786.45 | 0.572832E+09 | 0.00 | 0.00 |
June | 0.182925E+10 | 17565446.22 | 0.642602E+09 | 67512181.24 | 0.575090E+09 | 0.00 | 0.00 |
July | 0.160001E+10 | 37087886.55 | 0.625568E+09 | 31049953.11 | 0.594518E+09 | 0.00 | 0.00 |
August | 0.150758E+10 | 13558425.72 | 0.565689E+09 | 11391145.45 | 0.554298E+09 | 0.00 | 0.00 |
September | 0.146214E+10 | 17632174.29 | 0.544342E+09 | 9821945.23 | 0.534520E+09 | 0.00 | 0.00 |
October | 0.162392E+10 | 26672267.94 | 0.662504E+09 | 70585523.65 | 0.591918E+09 | 0.00 | 0.00 |
November | 0.179691E+10 | 62258175.16 | 0.774881E+09 | 0.183582E+09 | 0.591299E+09 | 0.00 | 0.00 |
December | 0.206956E+10 | 0.161829E+09 | 0.928669E+09 | 0.320870E+09 | 0.607799E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.209368E+11 | 0.604626E+09 | 0.819744E+10 | 0.129281E+10 | 0.690463E+10 | 0.00 | 0.00 |
Minimum of Months | 0.146214E+10 | 4881913.85 | 0.531003E+09 | 6981416.84 | 0.524022E+09 | 0.00 | 0.00 |
Maximum of Months | 0.211044E+10 | 0.161829E+09 | 0.931235E+09 | 0.320870E+09 | 0.619288E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 26.42 | 22.38 | 20.70 | 2.25 | 18.66 | 103.85 | 146.57 | 0.01 |
February | 27.50 | 22.91 | 21.01 | 2.37 | 18.54 | 110.59 | 164.59 | 0.00 |
March | 28.33 | 23.63 | 21.77 | 3.67 | 19.85 | 110.33 | 194.39 | 0.01 |
April | 29.15 | 25.37 | 24.04 | 2.98 | 21.51 | 118.69 | 185.56 | 0.03 |
May | 29.01 | 26.53 | 25.72 | 3.19 | 23.00 | 127.71 | 124.87 | 0.08 |
June | 28.86 | 26.50 | 25.74 | 3.10 | 22.78 | 123.38 | 156.09 | 0.05 |
July | 27.25 | 24.29 | 23.20 | 2.32 | 21.53 | 137.39 | 88.28 | 0.02 |
August | 27.54 | 25.86 | 25.31 | 3.22 | 21.55 | 129.55 | 122.00 | 0.07 |
September | 27.58 | 25.59 | 24.93 | 2.22 | 22.01 | 128.30 | 103.37 | 0.04 |
October | 26.89 | 25.07 | 24.46 | 2.18 | 21.39 | 123.79 | 92.41 | 0.11 |
November | 26.68 | 24.14 | 23.20 | 1.94 | 20.29 | 113.70 | 103.30 | 0.02 |
December | 25.97 | 22.85 | 21.57 | 2.00 | 18.63 | 101.83 | 131.96 | 0.00 |
Annual Sum or Average | 27.59 | 24.60 | 23.48 | 2.62 | 20.82 | 119.14 | 134.17 | 0.04 |
Minimum of Months | 25.97 | 22.38 | 20.70 | 1.94 | 18.54 | 101.83 | 88.28 | 0.00 |
Maximum of Months | 29.15 | 26.53 | 25.74 | 3.67 | 23.00 | 137.39 | 194.39 | 0.11 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 34.10 | 04-JAN-12:00 | 23.67 | 19.40 | 5.00 | 24.66 | 266.50 | 576.50 |
February | 35.00 | 21-FEB-13:00 | 22.02 | 16.00 | 2.10 | 24.16 | 230.00 | 672.50 |
March | 36.40 | 21-MAR-12:00 | 23.01 | 17.00 | 5.00 | 26.97 | 269.50 | 658.50 |
April | 35.50 | 01-APR-13:00 | 26.96 | 24.00 | 2.50 | 27.14 | 295.50 | 519.50 |
May | 37.60 | 06-MAY-12:00 | 26.43 | 22.60 | 4.00 | 29.39 | 317.00 | 525.50 |
June | 36.00 | 12-JUN-14:00 | 27.60 | 25.00 | 4.00 | 28.43 | 235.00 | 472.00 |
July | 33.20 | 15-JUL-15:00 | 25.63 | 23.00 | 2.00 | 27.95 | 219.00 | 181.00 |
August | 34.00 | 10-AUG-13:00 | 27.86 | 26.00 | 5.00 | 26.65 | 344.50 | 278.50 |
September | 34.00 | 06-SEP-13:00 | 26.51 | 24.00 | 4.00 | 25.00 | 258.00 | 581.50 |
October | 33.00 | 04-OCT-13:00 | 26.23 | 24.00 | 4.00 | 25.16 | 303.00 | 428.50 |
November | 34.30 | 18-NOV-12:00 | 25.34 | 22.20 | 3.00 | 25.49 | 289.50 | 511.50 |
December | 33.00 | 07-DEC-13:00 | 23.23 | 19.00 | 3.00 | 22.98 | 215.00 | 596.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 33.00 | 22.02 | 16.00 | 2.00 | 22.98 | 215.00 | 181.00 | |
Maximum of Months | 37.60 | 27.86 | 26.00 | 5.00 | 29.39 | 344.50 | 672.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 18.70 | 23-JAN-05:00 | 16.92 | 16.00 | 2.00 | 7.75 | 0.00 | 0.00 |
February | 20.30 | 21-FEB-09:00 | 19.04 | 18.40 | 2.00 | 10.50 | 258.50 | 564.00 |
March | 22.00 | 03-MAR-05:00 | 19.94 | 19.00 | 3.00 | 13.35 | 0.00 | 0.00 |
April | 22.90 | 14-APR-15:00 | 22.90 | 22.90 | 3.00 | 14.65 | 199.50 | 264.50 |
May | 22.00 | 10-MAY-19:00 | 22.00 | 22.00 | 2.00 | 18.28 | 0.00 | 0.00 |
June | 23.00 | 20-JUN-23:00 | 23.00 | 23.00 | 2.00 | 19.35 | 0.00 | 0.00 |
July | 23.00 | 13-JUL-04:00 | 22.27 | 22.00 | 0.00 | 13.91 | 0.00 | 0.00 |
August | 22.00 | 20-AUG-10:00 | 22.00 | 22.00 | 5.00 | 18.28 | 430.50 | 41.50 |
September | 22.90 | 19-SEP-03:00 | 22.78 | 22.78 | 0.00 | 21.27 | 0.00 | 0.00 |
October | 22.50 | 23-OCT-04:00 | 22.50 | 22.50 | 2.80 | 18.82 | 0.00 | 0.00 |
November | 20.00 | 25-NOV-04:00 | 18.63 | 18.00 | 2.00 | 10.69 | 0.00 | 0.00 |
December | 18.00 | 21-DEC-04:00 | 17.36 | 17.00 | 3.00 | 9.13 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 18.00 | 16.92 | 16.00 | 0.00 | 7.75 | 0.00 | 0.00 | |
Maximum of Months | 23.00 | 23.00 | 23.00 | 5.00 | 21.27 | 430.50 | 564.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 25.53 | 12-JAN-12:00 | 32.40 | 23.10 | 2.00 | 25.00 | 353.00 | 347.00 |
February | 26.17 | 14-FEB-15:00 | 32.30 | 24.20 | 2.00 | 25.16 | 200.00 | 199.00 |
March | 26.28 | 27-MAR-12:00 | 34.20 | 23.60 | 4.00 | 26.32 | 326.00 | 535.00 |
April | 27.93 | 10-APR-16:49 | 31.52 | 26.85 | 4.08 | 27.70 | 110.67 | 57.00 |
May | 29.00 | 28-MAY-20:00 | 29.00 | 29.00 | 3.00 | 22.47 | 0.00 | 0.00 |
June | 30.11 | 15-JUN-09:00 | 33.20 | 29.20 | 5.00 | 26.48 | 320.50 | 421.00 |
July | 26.43 | 20-JUL-14:00 | 32.80 | 24.20 | 1.00 | 26.65 | 305.00 | 253.00 |
August | 28.81 | 14-AUG-16:00 | 32.00 | 28.00 | 1.00 | 25.16 | 107.50 | 223.00 |
September | 30.06 | 30-SEP-10:00 | 32.80 | 29.40 | 3.00 | 25.66 | 398.00 | 359.50 |
October | 27.36 | 16-OCT-14:00 | 31.50 | 26.00 | 3.00 | 24.16 | 239.00 | 346.50 |
November | 27.56 | 10-NOV-12:00 | 31.00 | 26.40 | 6.00 | 28.11 | 388.00 | 95.50 |
December | 26.86 | 03-DEC-12:00 | 31.50 | 25.30 | 1.00 | 23.49 | 301.00 | 468.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 25.53 | 29.00 | 23.10 | 1.00 | 22.47 | 0.00 | 0.00 | |
Maximum of Months | 30.11 | 34.20 | 29.40 | 6.00 | 28.11 | 398.00 | 535.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 24.20 | 09-JAN-21:00 | 26.50 | 24.77 | 4.00 | 25.16 | 0.00 | 0.00 |
February | 24.40 | 15-FEB-18:00 | 28.30 | 25.33 | 4.00 | 20.75 | 0.00 | 0.00 |
March | 25.30 | 28-MAR-06:00 | 27.20 | 25.72 | 3.00 | 19.87 | 103.00 | 28.00 |
April | 27.00 | 10-APR-17:00 | 30.50 | 27.87 | 4.50 | 25.00 | 20.00 | 20.50 |
May | 29.00 | 28-MAY-20:00 | 29.00 | 29.00 | 3.00 | 22.47 | 0.00 | 0.00 |
June | 29.20 | 15-JUN-09:00 | 33.20 | 30.11 | 5.00 | 26.48 | 320.50 | 421.00 |
July | 26.00 | 10-JUL-14:00 | 26.50 | 26.11 | 2.30 | 23.49 | 286.00 | 36.50 |
August | 28.00 | 02-AUG-10:00 | 31.00 | 28.65 | 4.00 | 24.16 | 419.00 | 195.50 |
September | 29.40 | 30-SEP-10:00 | 32.80 | 30.06 | 3.00 | 25.66 | 398.00 | 359.50 |
October | 26.50 | 16-OCT-08:00 | 29.00 | 27.04 | 2.50 | 21.78 | 300.00 | 326.00 |
November | 26.40 | 10-NOV-12:00 | 31.00 | 27.56 | 6.00 | 28.11 | 388.00 | 95.50 |
December | 26.00 | 10-DEC-17:00 | 29.00 | 26.74 | 3.00 | 21.78 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 24.20 | 26.50 | 24.77 | 2.30 | 19.87 | 0.00 | 0.00 | |
Maximum of Months | 29.40 | 33.20 | 30.11 | 6.00 | 28.11 | 419.00 | 421.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 29.71 | 38.82 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 29.90 | 44.34 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 30.35 | 50.49 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 30.97 | 51.18 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 31.58 | 43.47 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 32.02 | 46.77 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 32.16 | 39.95 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 31.97 | 43.65 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 31.50 | 40.53 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 30.87 | 37.35 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 30.27 | 35.77 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 29.84 | 36.19 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 30.93 | 42.35 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 29.71 | 35.77 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 32.16 | 51.18 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH LAUNDRY G WATER HEATER
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.906184E+11 | -0.888382E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.178017E+10 | 82.17 | 0.00 | 0.00 |
February | 0.815553E+11 | -0.799502E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.160503E+10 | 82.17 | 0.00 | 0.00 |
March | 0.895248E+11 | -0.877453E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.177950E+10 | 82.17 | 0.00 | 0.00 |
April | 0.856194E+11 | -0.838979E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.172154E+10 | 82.17 | 0.00 | 0.00 |
May | 0.874377E+11 | -0.856620E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.177571E+10 | 82.17 | 0.00 | 0.00 |
June | 0.838990E+11 | -0.821850E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.171397E+10 | 82.17 | 0.00 | 0.00 |
July | 0.864584E+11 | -0.846842E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.177423E+10 | 82.17 | 0.00 | 0.00 |
August | 0.867885E+11 | -0.850116E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.177688E+10 | 82.17 | 0.00 | 0.00 |
September | 0.847605E+11 | -0.830410E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.171952E+10 | 82.17 | 0.00 | 0.00 |
October | 0.886460E+11 | -0.868644E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.178155E+10 | 82.17 | 0.00 | 0.00 |
November | 0.867788E+11 | -0.850573E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.172154E+10 | 82.17 | 0.00 | 0.00 |
December | 0.903934E+11 | -0.886149E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.177849E+10 | 82.17 | 0.00 | 0.00 |
Annual Sum or Average | 0.104248E+13 | -0.102155E+13 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.209281E+11 | 82.17 | 0.00 | 0.00 |
Minimum of Months | 0.815553E+11 | -0.888382E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.178155E+10 | 82.17 | 0.00 | 0.00 |
Maximum of Months | 0.906184E+11 | -0.799502E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.160503E+10 | 82.17 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.804814E+10 | -0.788296E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -165175218.0 | 82.17 | 0.00 | 0.00 |
February | 0.727249E+10 | -0.712336E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -149127392.3 | 82.17 | 0.00 | 0.00 |
March | 0.804662E+10 | -0.788155E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -165061930.2 | 82.17 | 0.00 | 0.00 |
April | 0.779788E+10 | -0.763820E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -159683501.3 | 82.17 | 0.00 | 0.00 |
May | 0.804798E+10 | -0.788296E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -165016575.4 | 82.17 | 0.00 | 0.00 |
June | 0.778942E+10 | -0.762976E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -159655332.9 | 82.17 | 0.00 | 0.00 |
July | 0.805648E+10 | -0.789140E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -165082660.6 | 82.17 | 0.00 | 0.00 |
August | 0.804808E+10 | -0.788296E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -165116043.7 | 82.17 | 0.00 | 0.00 |
September | 0.779936E+10 | -0.763961E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -159753162.3 | 82.17 | 0.00 | 0.00 |
October | 0.804671E+10 | -0.788155E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -165161073.7 | 82.17 | 0.00 | 0.00 |
November | 0.778116E+10 | -0.762132E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -159838804.4 | 82.17 | 0.00 | 0.00 |
December | 0.805661E+10 | -0.789140E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -165208727.6 | 82.17 | 0.00 | 0.00 |
Annual Sum or Average | 0.947909E+11 | -0.928470E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.194388E+10 | 82.17 | 0.00 | 0.00 |
Minimum of Months | 0.727249E+10 | -0.789140E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -165208727.6 | 82.17 | 0.00 | 0.00 |
Maximum of Months | 0.805661E+10 | -0.712336E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -149127392.3 | 82.17 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.457938E+11 | -0.442504E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.154345E+10 | 60.05 | 0.00 | 0.00 |
February | 0.411152E+11 | -0.397251E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.139011E+10 | 60.05 | 0.00 | 0.00 |
March | 0.448882E+11 | -0.433457E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.154251E+10 | 60.05 | 0.00 | 0.00 |
April | 0.425378E+11 | -0.410458E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.149199E+10 | 60.05 | 0.00 | 0.00 |
May | 0.430656E+11 | -0.415284E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.153726E+10 | 60.05 | 0.00 | 0.00 |
June | 0.410698E+11 | -0.395883E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.148150E+10 | 60.05 | 0.00 | 0.00 |
July | 0.421967E+11 | -0.406615E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.153521E+10 | 60.05 | 0.00 | 0.00 |
August | 0.425250E+11 | -0.409861E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.153889E+10 | 60.05 | 0.00 | 0.00 |
September | 0.417981E+11 | -0.403089E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.148918E+10 | 60.05 | 0.00 | 0.00 |
October | 0.440886E+11 | -0.425433E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.154536E+10 | 60.05 | 0.00 | 0.00 |
November | 0.435224E+11 | -0.420304E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.149199E+10 | 60.05 | 0.00 | 0.00 |
December | 0.455961E+11 | -0.440550E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.154112E+10 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.518197E+12 | -0.500069E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.181286E+11 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.410698E+11 | -0.442504E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.154536E+10 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.457938E+11 | -0.395883E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.139011E+10 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: LOBBY_FLR_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.87 | 0.86 | 01-JAN-08:09 | 1647.95 | 25.47 | 140.67 | 325.50 | 583.86 | 24.45 | 304.17 | 306.83 |
February | 321.17 | 0.87 | 0.86 | 01-FEB-06:49 | 1282.84 | 20.74 | 21.83 | 294.83 | 487.53 | 21.83 | 249.33 | 265.17 |
March | 361.17 | 0.87 | 0.86 | 01-MAR-08:09 | 969.28 | 19.79 | 0.00 | 330.33 | 389.62 | 21.52 | 257.17 | 287.67 |
April | 358.33 | 0.87 | 0.86 | 01-APR-07:19 | 794.33 | 19.48 | 0.00 | 327.67 | 326.80 | 21.20 | 200.00 | 267.33 |
May | 376.33 | 0.88 | 0.86 | 01-MAY-07:30 | 678.43 | 18.30 | 0.00 | 334.33 | 270.27 | 20.02 | 76.33 | 230.83 |
June | 370.50 | 0.88 | 0.86 | 01-JUN-08:30 | 655.00 | 18.57 | 0.00 | 327.00 | 272.11 | 20.32 | 59.67 | 242.67 |
July | 383.17 | 0.88 | 0.86 | 01-JUL-07:00 | 641.74 | 17.79 | 0.00 | 331.33 | 247.37 | 19.51 | 0.83 | 210.00 |
August | 369.33 | 0.88 | 0.86 | 01-AUG-07:40 | 761.87 | 18.76 | 0.00 | 333.67 | 299.90 | 20.46 | 113.50 | 258.50 |
September | 357.83 | 0.88 | 0.86 | 01-SEP-07:19 | 874.12 | 18.43 | 0.00 | 316.83 | 330.91 | 20.11 | 129.67 | 257.67 |
October | 356.83 | 0.87 | 0.86 | 01-OCT-07:49 | 1142.53 | 19.35 | 5.00 | 328.83 | 420.77 | 20.92 | 170.00 | 270.50 |
November | 337.67 | 0.87 | 0.86 | 01-NOV-07:30 | 1475.84 | 23.60 | 105.33 | 317.17 | 519.44 | 22.24 | 225.67 | 276.50 |
December | 349.33 | 0.87 | 0.86 | 01-DEC-06:00 | 1728.36 | 25.79 | 149.50 | 323.00 | 590.36 | 24.28 | 282.33 | 298.83 |
Annual Sum or Average | 4292.33 | 0.88 | 1041.97 | 20.44 | 422.33 | 3890.50 | 390.79 | 21.36 | 2068.67 | 3172.50 | ||
Minimum of Months | 321.17 | 0.87 | 0.86 | 641.74 | 17.79 | 0.00 | 294.83 | 247.37 | 19.51 | 0.83 | 210.00 | |
Maximum of Months | 383.17 | 0.88 | 0.86 | 1728.36 | 25.79 | 149.50 | 334.33 | 590.36 | 24.45 | 304.17 | 306.83 |
Report: DaylightingReportMonthly
For: CAFE_FLR_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.26 | 0.22 | 01-JAN-07:19 | 1879.71 | 25.69 | 144.50 | 331.00 | 814.79 | 24.70 | 321.50 | 319.67 |
February | 321.17 | 0.27 | 0.22 | 01-FEB-06:49 | 1485.46 | 21.33 | 48.83 | 300.00 | 689.44 | 22.27 | 265.50 | 284.33 |
March | 361.17 | 0.26 | 0.22 | 01-MAR-07:40 | 1124.39 | 20.56 | 22.33 | 342.17 | 544.21 | 22.06 | 288.83 | 316.67 |
April | 358.33 | 0.26 | 0.22 | 01-APR-06:49 | 919.53 | 20.34 | 1.00 | 341.00 | 451.54 | 21.83 | 261.50 | 308.17 |
May | 376.33 | 0.28 | 0.22 | 01-MAY-06:40 | 784.10 | 19.27 | 0.00 | 351.33 | 375.52 | 20.74 | 156.50 | 308.00 |
June | 370.50 | 0.28 | 0.22 | 01-JUN-07:30 | 760.79 | 19.50 | 0.00 | 344.33 | 377.51 | 21.01 | 198.33 | 302.17 |
July | 383.17 | 0.29 | 0.22 | 01-JUL-06:00 | 739.71 | 18.81 | 0.00 | 348.67 | 344.96 | 20.27 | 91.33 | 303.50 |
August | 369.33 | 0.27 | 0.22 | 01-AUG-06:49 | 876.77 | 19.70 | 0.00 | 351.33 | 414.34 | 21.16 | 192.50 | 309.67 |
September | 357.83 | 0.29 | 0.22 | 01-SEP-06:49 | 998.38 | 19.36 | 1.67 | 327.33 | 454.63 | 20.81 | 174.33 | 295.83 |
October | 356.83 | 0.26 | 0.22 | 01-OCT-06:30 | 1299.51 | 20.18 | 21.17 | 340.00 | 576.94 | 21.54 | 231.17 | 306.50 |
November | 337.67 | 0.25 | 0.22 | 01-NOV-06:00 | 1674.96 | 24.01 | 111.33 | 326.00 | 717.67 | 22.71 | 265.67 | 302.50 |
December | 349.33 | 0.26 | 0.22 | 01-DEC-06:40 | 1959.84 | 26.01 | 149.50 | 329.33 | 821.16 | 24.55 | 313.33 | 315.50 |
Annual Sum or Average | 4292.33 | 0.27 | 1194.50 | 21.17 | 500.33 | 4032.50 | 542.74 | 21.93 | 2760.50 | 3672.50 | ||
Minimum of Months | 321.17 | 0.25 | 0.22 | 739.71 | 18.81 | 0.00 | 300.00 | 344.96 | 20.27 | 91.33 | 284.33 | |
Maximum of Months | 383.17 | 0.29 | 0.22 | 1959.84 | 26.01 | 149.50 | 351.33 | 821.16 | 24.70 | 321.50 | 319.67 |
Report: DaylightingReportMonthly
For: DINING_FLR_6_DAYLCTRL
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.66 | 0.60 | 01-JAN-09:09 | 501.47 | 15.96 | 0.00 | 311.00 | 229.27 | 19.17 | 0.00 | 239.83 |
February | 321.17 | 0.65 | 0.60 | 01-FEB-08:09 | 550.90 | 16.45 | 0.00 | 287.00 | 252.35 | 19.63 | 0.00 | 242.33 |
March | 361.17 | 0.63 | 0.60 | 01-MAR-08:09 | 632.98 | 17.31 | 0.00 | 333.17 | 290.54 | 20.48 | 14.17 | 293.00 |
April | 358.33 | 0.62 | 0.60 | 01-APR-06:00 | 799.57 | 18.10 | 0.00 | 343.17 | 350.28 | 21.28 | 122.50 | 304.83 |
May | 376.33 | 0.62 | 0.60 | 01-MAY-06:19 | 950.69 | 18.70 | 27.67 | 357.17 | 387.47 | 21.32 | 156.83 | 323.17 |
June | 370.50 | 0.62 | 0.60 | 01-JUN-07:19 | 1155.80 | 22.10 | 102.50 | 356.00 | 455.56 | 23.22 | 253.00 | 332.67 |
July | 383.17 | 0.62 | 0.60 | 01-JUL-06:40 | 1000.84 | 19.92 | 71.50 | 358.83 | 389.15 | 22.83 | 158.67 | 327.00 |
August | 369.33 | 0.62 | 0.60 | 01-AUG-06:10 | 887.58 | 17.81 | 0.00 | 354.17 | 368.14 | 20.97 | 128.00 | 314.33 |
September | 357.83 | 0.64 | 0.60 | 01-SEP-06:49 | 712.23 | 16.72 | 0.00 | 324.33 | 294.94 | 19.80 | 40.33 | 278.00 |
October | 356.83 | 0.64 | 0.60 | 01-OCT-07:40 | 622.12 | 16.54 | 0.00 | 324.83 | 260.69 | 19.63 | 0.00 | 264.17 |
November | 337.67 | 0.65 | 0.60 | 01-NOV-07:49 | 548.86 | 16.25 | 0.00 | 302.83 | 237.05 | 19.39 | 0.00 | 235.67 |
December | 349.33 | 0.66 | 0.60 | 01-DEC-07:40 | 492.48 | 15.74 | 0.00 | 304.67 | 222.09 | 18.94 | 0.00 | 230.50 |
Annual Sum or Average | 4292.33 | 0.64 | 745.38 | 17.69 | 201.67 | 3957.17 | 313.99 | 20.60 | 873.50 | 3385.50 | ||
Minimum of Months | 321.17 | 0.62 | 0.60 | 492.48 | 15.74 | 0.00 | 287.00 | 222.09 | 18.94 | 0.00 | 230.50 | |
Maximum of Months | 383.17 | 0.66 | 0.60 | 1155.80 | 22.10 | 102.50 | 358.83 | 455.56 | 23.22 | 253.00 | 332.67 |
Report: DaylightingReportMonthly
For: BANQUET_FLR_6_DAYLCTRL
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.66 | 0.60 | 01-JAN-09:09 | 501.47 | 15.96 | 0.00 | 311.00 | 229.27 | 19.17 | 0.00 | 239.83 |
February | 321.17 | 0.65 | 0.60 | 01-FEB-08:09 | 550.90 | 16.45 | 0.00 | 287.00 | 252.35 | 19.63 | 0.00 | 242.33 |
March | 361.17 | 0.63 | 0.60 | 01-MAR-08:09 | 632.98 | 17.31 | 0.00 | 333.17 | 290.54 | 20.48 | 14.17 | 293.00 |
April | 358.33 | 0.62 | 0.60 | 01-APR-06:00 | 799.57 | 18.10 | 0.00 | 343.17 | 350.28 | 21.28 | 122.50 | 304.83 |
May | 376.33 | 0.62 | 0.60 | 01-MAY-06:19 | 950.69 | 18.70 | 27.67 | 357.17 | 387.47 | 21.32 | 156.83 | 323.17 |
June | 370.50 | 0.62 | 0.60 | 01-JUN-07:19 | 1155.80 | 22.10 | 102.50 | 356.00 | 455.56 | 23.22 | 253.00 | 332.67 |
July | 383.17 | 0.62 | 0.60 | 01-JUL-06:40 | 1000.84 | 19.92 | 71.50 | 358.83 | 389.15 | 22.83 | 158.67 | 327.00 |
August | 369.33 | 0.62 | 0.60 | 01-AUG-06:10 | 887.58 | 17.81 | 0.00 | 354.17 | 368.14 | 20.97 | 128.00 | 314.33 |
September | 357.83 | 0.64 | 0.60 | 01-SEP-06:49 | 712.23 | 16.72 | 0.00 | 324.33 | 294.94 | 19.80 | 40.33 | 278.00 |
October | 356.83 | 0.64 | 0.60 | 01-OCT-07:40 | 622.12 | 16.54 | 0.00 | 324.83 | 260.69 | 19.63 | 0.00 | 264.17 |
November | 337.67 | 0.65 | 0.60 | 01-NOV-07:49 | 548.86 | 16.25 | 0.00 | 302.83 | 237.05 | 19.39 | 0.00 | 235.67 |
December | 349.33 | 0.66 | 0.60 | 01-DEC-07:40 | 492.48 | 15.74 | 0.00 | 304.67 | 222.09 | 18.94 | 0.00 | 230.50 |
Annual Sum or Average | 4292.33 | 0.64 | 745.38 | 17.69 | 201.67 | 3957.17 | 313.99 | 20.60 | 873.50 | 3385.50 | ||
Minimum of Months | 321.17 | 0.62 | 0.60 | 492.48 | 15.74 | 0.00 | 287.00 | 222.09 | 18.94 | 0.00 | 230.50 | |
Maximum of Months | 383.17 | 0.66 | 0.60 | 1155.80 | 22.10 | 102.50 | 358.83 | 455.56 | 23.22 | 253.00 | 332.67 |
Report: CoilReportMonthly
For: FLR_3_DOAS HEATING COIL
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.151980E+10 | 5081.62 | 02-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.117046E+10 | 4591.63 | 11-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.128193E+10 | 5395.27 | 04-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.112050E+10 | 5295.46 | 10-APR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.128446E+10 | 5106.23 | 26-MAY-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.109730E+10 | 4723.28 | 05-JUN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.130855E+10 | 5204.45 | 01-JUL-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.153171E+10 | 5806.54 | 21-AUG-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.132761E+10 | 5758.67 | 16-SEP-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.162488E+10 | 5851.03 | 23-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.146609E+10 | 5410.49 | 27-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.155432E+10 | 5061.49 | 18-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.162876E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.109730E+10 | 4591.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.162488E+10 | 5851.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 824291.57 | 307.98 | 20-AUG-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 824291.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 824291.57 | 307.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 2127814.24 | 1431.14 | 01-JAN-19:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2308048.61 | 1431.14 | 08-FEB-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 3782650.72 | 1431.14 | 04-MAR-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3157353.08 | 1431.14 | 06-APR-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2619675.31 | 1431.14 | 09-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2068678.97 | 1431.14 | 02-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 4051017.10 | 1431.14 | 02-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 3690556.62 | 1431.14 | 01-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 4041174.69 | 1431.14 | 01-SEP-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3236046.86 | 1431.14 | 10-OCT-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2862944.39 | 1431.14 | 01-NOV-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2131390.82 | 1431.14 | 15-DEC-09:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 36077351.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 2068678.97 | 1431.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4051017.10 | 1431.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 1941846.77 | 1430.97 | 01-JAN-19:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1643425.87 | 1430.97 | 01-FEB-09:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 4187904.09 | 1430.97 | 01-MAR-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3374200.84 | 1430.97 | 05-APR-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2206950.79 | 1430.97 | 09-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1160955.56 | 1430.97 | 02-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 3264939.11 | 1430.97 | 03-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 3683266.52 | 1430.97 | 01-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 4641201.12 | 1430.97 | 01-SEP-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4096395.53 | 1430.97 | 06-OCT-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 4390179.22 | 1430.97 | 01-NOV-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2159268.04 | 1430.97 | 10-DEC-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 36750533.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1160955.56 | 1430.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4641201.12 | 1430.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 37904480.53 | 19090.25 | 01-JAN-16:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 30178849.92 | 17558.61 | 12-FEB-19:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 52371532.61 | 18883.19 | 20-MAR-18:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 40393780.29 | 17805.44 | 04-APR-18:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17253864.72 | 13590.97 | 21-MAY-18:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 18346449.35 | 16242.92 | 30-JUN-18:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17223725.89 | 16710.14 | 17-JUL-18:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 31412270.26 | 17045.12 | 19-AUG-15:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 40138545.41 | 19126.67 | 16-SEP-15:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 32257739.99 | 16247.88 | 22-OCT-15:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 43774654.34 | 19410.63 | 23-NOV-16:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 49529603.57 | 19211.60 | 22-DEC-16:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.410785E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 17223725.89 | 13590.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 52371532.61 | 19410.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 92436.18 | 825.37 | 01-JAN-19:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 26656.33 | 310.99 | 17-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 107841.46 | 642.02 | 20-AUG-15:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 87935.14 | 1025.91 | 18-SEP-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 233424.89 | 1431.14 | 23-OCT-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 102328.95 | 579.70 | 27-NOV-09:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 45136.31 | 574.14 | 22-DEC-09:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 695759.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 233424.89 | 1431.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 477435.23 | 1287.24 | 09-JAN-07:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 64925.31 | 574.11 | 15-FEB-07:16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 58504.59 | 682.55 | 17-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 22429.54 | 336.44 | 24-JUN-20:16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 106526.20 | 1242.81 | 29-JUL-06:46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 150388.48 | 1137.38 | 20-AUG-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 233812.03 | 1408.64 | 18-SEP-08:36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 536892.75 | 1343.33 | 26-OCT-18:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 135856.49 | 701.98 | 27-NOV-09:26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 360995.75 | 1083.51 | 17-DEC-09:46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2147766.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 536892.75 | 1408.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 815110.38 | 357.78 | 09-JAN-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 798390.26 | 357.78 | 02-FEB-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1037048.17 | 357.78 | 02-MAR-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 995106.76 | 357.78 | 06-APR-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 829871.59 | 357.78 | 09-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 814602.28 | 357.78 | 02-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1094511.58 | 357.78 | 01-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1111693.31 | 357.78 | 01-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1111364.65 | 357.78 | 01-SEP-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1035988.09 | 357.78 | 02-OCT-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 870537.73 | 357.78 | 01-NOV-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 714585.72 | 357.78 | 11-DEC-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 11228810.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 714585.72 | 357.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1111693.31 | 357.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 523172.97 | 357.74 | 03-JAN-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 421845.08 | 357.74 | 01-FEB-09:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1036087.31 | 357.74 | 04-MAR-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 996332.26 | 357.74 | 06-APR-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 726464.46 | 357.74 | 09-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 462955.85 | 357.74 | 02-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 955398.12 | 357.74 | 03-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1105380.90 | 357.74 | 01-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1148034.11 | 357.74 | 04-SEP-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1189840.86 | 357.74 | 02-OCT-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1161691.84 | 357.74 | 01-NOV-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 685745.02 | 357.74 | 08-DEC-07:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 10412948.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 421845.08 | 357.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1189840.86 | 357.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 477429.10 | 1988.86 | 01-JAN-09:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 255829.93 | 1654.08 | 15-MAR-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 245746.38 | 1045.71 | 23-APR-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 575306.43 | 1146.36 | 26-MAY-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 282121.66 | 1156.51 | 01-JUN-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1133917.22 | 1306.46 | 19-JUL-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1332294.39 | 1504.22 | 20-AUG-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 726476.36 | 1351.64 | 17-SEP-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1768211.86 | 1440.41 | 18-OCT-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 416539.37 | 2167.11 | 27-NOV-09:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 370014.26 | 1783.60 | 19-DEC-09:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 7583886.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1768211.86 | 2167.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.568716E+11 | 0.331494E+11 | 44040.44 | 08-JAN-09:03 | 15315.95 | 0.79 |
February | 0.00 | 0.00 | 0.518421E+11 | 0.309985E+11 | 41854.11 | 13-FEB-06:50 | 15474.74 | 0.79 |
March | 0.00 | 0.00 | 0.598825E+11 | 0.348556E+11 | 37589.10 | 15-MAR-08:61 | 17636.32 | 0.79 |
April | 0.00 | 0.00 | 0.663997E+11 | 0.345819E+11 | 43293.11 | 10-APR-18:02 | 20068.38 | 0.79 |
May | 0.00 | 0.00 | 0.758943E+11 | 0.357300E+11 | 51677.37 | 10-MAY-21:10 | 17105.00 | 0.79 |
June | 0.00 | 0.00 | 0.730128E+11 | 0.344814E+11 | 50422.22 | 25-JUN-20:00 | 16793.82 | 0.79 |
July | 0.00 | 0.00 | 0.641685E+11 | 0.342598E+11 | 47849.77 | 10-JUL-15:00 | 15337.53 | 0.79 |
August | 0.00 | 0.00 | 0.727064E+11 | 0.345393E+11 | 50776.45 | 19-AUG-18:03 | 17022.32 | 0.79 |
September | 0.00 | 0.00 | 0.687233E+11 | 0.334693E+11 | 50918.65 | 15-SEP-21:30 | 16948.24 | 0.79 |
October | 0.00 | 0.00 | 0.689498E+11 | 0.340017E+11 | 53022.45 | 30-OCT-18:03 | 17592.92 | 0.79 |
November | 0.00 | 0.00 | 0.627487E+11 | 0.327348E+11 | 46554.98 | 26-NOV-09:03 | 17587.83 | 0.79 |
December | 0.00 | 0.00 | 0.601053E+11 | 0.329093E+11 | 44256.12 | 29-DEC-07:03 | 15492.78 | 0.79 |
Annual Sum or Average | 0.00 | 0.00 | 0.781305E+12 | 0.405711E+12 | 0.79 | |||
Minimum of Months | 0.00 | 0.00 | 0.518421E+11 | 0.309985E+11 | 37589.10 | 15315.95 | 0.79 | |
Maximum of Months | 0.00 | 0.00 | 0.758943E+11 | 0.357300E+11 | 53022.45 | 20068.38 | 0.79 |
Report: CoilReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.925071E+12 | 0.506805E+12 | 471635.17 | 08-JAN-08:23 | 164685.04 | 1.00 |
February | 0.00 | 0.00 | 0.847528E+12 | 0.481812E+12 | 465925.33 | 17-FEB-06:50 | 172713.46 | 1.00 |
March | 0.00 | 0.00 | 0.981663E+12 | 0.546072E+12 | 511426.47 | 14-MAR-21:20 | 207958.49 | 1.00 |
April | 0.00 | 0.00 | 0.108147E+13 | 0.543545E+12 | 572090.62 | 10-APR-18:07 | 247339.34 | 1.00 |
May | 0.00 | 0.00 | 0.122872E+13 | 0.564441E+12 | 607231.40 | 28-MAY-21:00 | 230760.94 | 1.00 |
June | 0.00 | 0.00 | 0.120448E+13 | 0.553137E+12 | 588810.66 | 13-JUN-18:00 | 265218.51 | 1.00 |
July | 0.00 | 0.00 | 0.104745E+13 | 0.529490E+12 | 599865.91 | 17-JUL-18:50 | 206882.64 | 1.00 |
August | 0.00 | 0.00 | 0.117241E+13 | 0.530931E+12 | 588952.42 | 08-AUG-18:07 | 244627.91 | 1.00 |
September | 0.00 | 0.00 | 0.110689E+13 | 0.514217E+12 | 601246.83 | 15-SEP-19:25 | 198611.51 | 1.00 |
October | 0.00 | 0.00 | 0.109618E+13 | 0.515293E+12 | 567378.30 | 09-OCT-19:20 | 198079.84 | 1.00 |
November | 0.00 | 0.00 | 0.100579E+13 | 0.497945E+12 | 553797.49 | 30-NOV-23:00 | 198628.39 | 1.00 |
December | 0.00 | 0.00 | 0.987090E+12 | 0.498627E+12 | 521836.11 | 18-DEC-24:00 | 177738.28 | 1.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.126848E+14 | 0.628232E+13 | 1.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.847528E+12 | 0.481812E+12 | 465925.33 | 164685.04 | 1.00 | |
Maximum of Months | 0.00 | 0.00 | 0.122872E+13 | 0.564441E+12 | 607231.40 | 265218.51 | 1.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.109161E+11 | 0.674801E+10 | 13987.38 | 08-JAN-09:02 | 10877.15 | 0.96 |
February | 0.00 | 0.00 | 0.105585E+11 | 0.678005E+10 | 13265.73 | 12-FEB-09:02 | 11433.70 | 0.96 |
March | 0.00 | 0.00 | 0.117319E+11 | 0.760953E+10 | 13310.89 | 15-MAR-08:61 | 11401.93 | 0.96 |
April | 0.00 | 0.00 | 0.114577E+11 | 0.735162E+10 | 12975.88 | 10-APR-08:61 | 11581.92 | 0.96 |
May | 0.00 | 0.00 | 0.114823E+11 | 0.710919E+10 | 13533.73 | 17-MAY-15:02 | 11149.24 | 0.96 |
June | 0.00 | 0.00 | 0.115573E+11 | 0.732276E+10 | 13132.80 | 27-JUN-08:62 | 11498.30 | 0.96 |
July | 0.00 | 0.00 | 0.102138E+11 | 0.600024E+10 | 13635.37 | 22-JUL-08:61 | 11121.33 | 0.96 |
August | 0.00 | 0.00 | 0.102696E+11 | 0.598874E+10 | 14907.86 | 19-AUG-18:02 | 10092.65 | 0.95 |
September | 0.00 | 0.00 | 0.101710E+11 | 0.598880E+10 | 14667.19 | 18-SEP-08:61 | 10351.88 | 0.96 |
October | 0.00 | 0.00 | 0.100783E+11 | 0.581148E+10 | 15061.19 | 30-OCT-18:02 | 9983.69 | 0.96 |
November | 0.00 | 0.00 | 0.101781E+11 | 0.607943E+10 | 14477.16 | 26-NOV-09:02 | 10488.05 | 0.96 |
December | 0.00 | 0.00 | 0.105879E+11 | 0.635337E+10 | 14244.09 | 24-DEC-09:02 | 10703.65 | 0.96 |
Annual Sum or Average | 0.00 | 0.00 | 0.129203E+12 | 0.791432E+11 | 0.96 | |||
Minimum of Months | 0.00 | 0.00 | 0.100783E+11 | 0.581148E+10 | 12975.88 | 9983.69 | 0.95 | |
Maximum of Months | 0.00 | 0.00 | 0.117319E+11 | 0.760953E+10 | 15061.19 | 11581.92 | 0.96 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.917437E+10 | 0.539951E+10 | 15929.41 | 07-JAN-09:11 | 10888.40 | 0.87 |
February | 0.00 | 0.00 | 0.928593E+10 | 0.570433E+10 | 15649.47 | 12-FEB-09:41 | 10675.34 | 0.90 |
March | 0.00 | 0.00 | 0.111787E+11 | 0.705678E+10 | 15015.07 | 15-MAR-08:61 | 10362.19 | 0.95 |
April | 0.00 | 0.00 | 0.115198E+11 | 0.738686E+10 | 14004.76 | 14-APR-17:02 | 12675.67 | 0.96 |
May | 0.00 | 0.00 | 0.118277E+11 | 0.741972E+10 | 15500.74 | 10-MAY-21:51 | 11424.42 | 0.96 |
June | 0.00 | 0.00 | 0.121920E+11 | 0.794616E+10 | 16320.58 | 25-JUN-21:51 | 10698.62 | 0.96 |
July | 0.00 | 0.00 | 0.105715E+11 | 0.635280E+10 | 16475.35 | 19-JUL-21:51 | 10906.42 | 0.95 |
August | 0.00 | 0.00 | 0.104173E+11 | 0.613416E+10 | 15958.32 | 19-AUG-20:11 | 10033.43 | 0.95 |
September | 0.00 | 0.00 | 0.996138E+10 | 0.580919E+10 | 15968.58 | 15-SEP-21:51 | 10162.52 | 0.94 |
October | 0.00 | 0.00 | 0.944738E+10 | 0.528881E+10 | 16384.27 | 23-OCT-08:61 | 9846.65 | 0.93 |
November | 0.00 | 0.00 | 0.896143E+10 | 0.509183E+10 | 15974.54 | 26-NOV-09:51 | 10085.53 | 0.90 |
December | 0.00 | 0.00 | 0.877908E+10 | 0.500866E+10 | 16320.74 | 24-DEC-09:41 | 10009.67 | 0.86 |
Annual Sum or Average | 0.00 | 0.00 | 0.123316E+12 | 0.745988E+11 | 0.93 | |||
Minimum of Months | 0.00 | 0.00 | 0.877908E+10 | 0.500866E+10 | 14004.76 | 9846.65 | 0.86 | |
Maximum of Months | 0.00 | 0.00 | 0.121920E+11 | 0.794616E+10 | 16475.35 | 12675.67 | 0.96 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.652200E+11 | 0.415014E+11 | 42224.60 | 04-JAN-15:00 | 37588.38 | 1.00 |
February | 0.00 | 0.00 | 0.581841E+11 | 0.358292E+11 | 38476.64 | 04-FEB-09:00 | 30668.60 | 1.00 |
March | 0.00 | 0.00 | 0.561051E+11 | 0.298949E+11 | 33644.73 | 11-MAR-09:00 | 22855.36 | 1.00 |
April | 0.00 | 0.00 | 0.498813E+11 | 0.238625E+11 | 31204.94 | 30-APR-08:00 | 18938.57 | 1.00 |
May | 0.00 | 0.00 | 0.517745E+11 | 0.244487E+11 | 33534.47 | 07-MAY-08:00 | 22259.51 | 1.00 |
June | 0.00 | 0.00 | 0.502275E+11 | 0.236679E+11 | 31995.70 | 18-JUN-08:00 | 19703.38 | 1.00 |
July | 0.00 | 0.00 | 0.467060E+11 | 0.207691E+11 | 29186.34 | 30-JUL-08:00 | 16798.07 | 1.00 |
August | 0.00 | 0.00 | 0.460942E+11 | 0.197714E+11 | 30894.39 | 13-AUG-08:00 | 18224.63 | 0.99 |
September | 0.00 | 0.00 | 0.485663E+11 | 0.225302E+11 | 30946.63 | 30-SEP-08:00 | 18637.48 | 1.00 |
October | 0.00 | 0.00 | 0.526438E+11 | 0.259468E+11 | 35960.98 | 29-OCT-08:00 | 25477.94 | 1.00 |
November | 0.00 | 0.00 | 0.583729E+11 | 0.336050E+11 | 41476.78 | 23-NOV-09:00 | 35057.34 | 1.00 |
December | 0.00 | 0.00 | 0.645043E+11 | 0.406462E+11 | 42926.97 | 31-DEC-08:55 | 36460.24 | 1.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.648280E+12 | 0.342473E+12 | 1.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.460942E+11 | 0.197714E+11 | 29186.34 | 16798.07 | 0.99 | |
Maximum of Months | 0.00 | 0.00 | 0.652200E+11 | 0.415014E+11 | 42926.97 | 37588.38 | 1.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.642012E+11 | 0.385201E+11 | 103324.62 | 07-JAN-09:11 | 74106.76 | 0.80 |
February | 0.00 | 0.00 | 0.619828E+11 | 0.379079E+11 | 100001.81 | 23-FEB-09:11 | 74827.74 | 0.82 |
March | 0.00 | 0.00 | 0.726797E+11 | 0.457843E+11 | 102060.41 | 15-MAR-08:61 | 71874.03 | 0.87 |
April | 0.00 | 0.00 | 0.761459E+11 | 0.496699E+11 | 92557.28 | 14-APR-18:02 | 78542.63 | 0.89 |
May | 0.00 | 0.00 | 0.845785E+11 | 0.563602E+11 | 100219.50 | 10-MAY-21:51 | 75765.04 | 0.90 |
June | 0.00 | 0.00 | 0.879467E+11 | 0.600700E+11 | 109261.32 | 25-JUN-21:51 | 70096.23 | 0.92 |
July | 0.00 | 0.00 | 0.803259E+11 | 0.531620E+11 | 110083.35 | 19-JUL-21:51 | 70305.77 | 0.88 |
August | 0.00 | 0.00 | 0.756142E+11 | 0.480279E+11 | 109733.20 | 19-AUG-20:11 | 67823.81 | 0.87 |
September | 0.00 | 0.00 | 0.706453E+11 | 0.439389E+11 | 108928.49 | 15-SEP-18:41 | 66678.75 | 0.86 |
October | 0.00 | 0.00 | 0.686519E+11 | 0.415467E+11 | 109749.60 | 23-OCT-08:61 | 68297.20 | 0.84 |
November | 0.00 | 0.00 | 0.646104E+11 | 0.391376E+11 | 106471.46 | 26-NOV-09:51 | 69055.47 | 0.82 |
December | 0.00 | 0.00 | 0.629191E+11 | 0.372344E+11 | 110169.32 | 20-DEC-09:02 | 65901.42 | 0.79 |
Annual Sum or Average | 0.00 | 0.00 | 0.870302E+12 | 0.551360E+12 | 0.86 | |||
Minimum of Months | 0.00 | 0.00 | 0.619828E+11 | 0.372344E+11 | 92557.28 | 65901.42 | 0.79 | |
Maximum of Months | 0.00 | 0.00 | 0.879467E+11 | 0.600700E+11 | 110169.32 | 78542.63 | 0.92 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.109022E+11 | 0.680108E+10 | 12016.62 | 08-JAN-09:02 | 10015.81 | 0.97 |
February | 0.00 | 0.00 | 0.106280E+11 | 0.693525E+10 | 11290.94 | 08-FEB-09:02 | 10561.95 | 0.98 |
March | 0.00 | 0.00 | 0.116690E+11 | 0.764617E+10 | 11419.20 | 15-MAR-08:61 | 10468.69 | 0.98 |
April | 0.00 | 0.00 | 0.114937E+11 | 0.750005E+10 | 11401.85 | 14-APR-18:02 | 10440.86 | 0.98 |
May | 0.00 | 0.00 | 0.115410E+11 | 0.736320E+10 | 12259.36 | 17-MAY-15:02 | 9769.35 | 0.97 |
June | 0.00 | 0.00 | 0.115713E+11 | 0.744571E+10 | 11452.65 | 02-JUN-08:62 | 10391.59 | 0.98 |
July | 0.00 | 0.00 | 0.101889E+11 | 0.609742E+10 | 11888.58 | 22-JUL-08:61 | 10090.73 | 0.97 |
August | 0.00 | 0.00 | 0.102733E+11 | 0.609814E+10 | 13302.65 | 19-AUG-18:02 | 8970.21 | 0.97 |
September | 0.00 | 0.00 | 0.102356E+11 | 0.619600E+10 | 12861.10 | 18-SEP-08:61 | 9375.27 | 0.97 |
October | 0.00 | 0.00 | 0.100664E+11 | 0.594020E+10 | 13374.38 | 30-OCT-18:02 | 8924.98 | 0.97 |
November | 0.00 | 0.00 | 0.101808E+11 | 0.616939E+10 | 12797.61 | 26-NOV-09:02 | 9413.63 | 0.97 |
December | 0.00 | 0.00 | 0.105850E+11 | 0.646203E+10 | 12256.63 | 17-DEC-09:02 | 9835.59 | 0.97 |
Annual Sum or Average | 0.00 | 0.00 | 0.129335E+12 | 0.806547E+11 | 0.97 | |||
Minimum of Months | 0.00 | 0.00 | 0.100664E+11 | 0.594020E+10 | 11290.94 | 8924.98 | 0.97 | |
Maximum of Months | 0.00 | 0.00 | 0.116690E+11 | 0.764617E+10 | 13374.38 | 10561.95 | 0.98 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.907683E+10 | 0.532807E+10 | 14816.06 | 07-JAN-09:11 | 10177.49 | 0.88 |
February | 0.00 | 0.00 | 0.929265E+10 | 0.573496E+10 | 14558.40 | 12-FEB-09:41 | 10008.63 | 0.91 |
March | 0.00 | 0.00 | 0.111107E+11 | 0.705819E+10 | 13861.20 | 15-MAR-07:33 | 10025.22 | 0.97 |
April | 0.00 | 0.00 | 0.115519E+11 | 0.752447E+10 | 11893.36 | 14-APR-18:02 | 10251.79 | 0.98 |
May | 0.00 | 0.00 | 0.118871E+11 | 0.770243E+10 | 13609.52 | 10-MAY-21:51 | 9968.90 | 0.97 |
June | 0.00 | 0.00 | 0.122065E+11 | 0.816732E+10 | 14382.16 | 25-JUN-21:51 | 9356.98 | 0.97 |
July | 0.00 | 0.00 | 0.105483E+11 | 0.644818E+10 | 14424.15 | 19-JUL-21:51 | 9415.64 | 0.96 |
August | 0.00 | 0.00 | 0.104209E+11 | 0.624921E+10 | 14195.52 | 19-AUG-20:11 | 8907.20 | 0.96 |
September | 0.00 | 0.00 | 0.100248E+11 | 0.602527E+10 | 14154.37 | 15-SEP-21:51 | 8971.24 | 0.96 |
October | 0.00 | 0.00 | 0.943372E+10 | 0.543584E+10 | 14590.94 | 23-OCT-08:61 | 8810.76 | 0.94 |
November | 0.00 | 0.00 | 0.894736E+10 | 0.519867E+10 | 14262.77 | 26-NOV-09:51 | 9043.72 | 0.91 |
December | 0.00 | 0.00 | 0.869682E+10 | 0.502887E+10 | 14973.54 | 20-DEC-08:42 | 9702.89 | 0.87 |
Annual Sum or Average | 0.00 | 0.00 | 0.123197E+12 | 0.759015E+11 | 0.94 | |||
Minimum of Months | 0.00 | 0.00 | 0.869682E+10 | 0.502887E+10 | 11893.36 | 8810.76 | 0.87 | |
Maximum of Months | 0.00 | 0.00 | 0.122065E+11 | 0.816732E+10 | 14973.54 | 10251.79 | 0.98 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.279632E+10 | 0.171277E+10 | 4015.42 | 08-JAN-09:02 | 2826.45 | 0.96 |
February | 0.00 | 0.00 | 0.269264E+10 | 0.169738E+10 | 3757.83 | 12-FEB-09:02 | 3028.85 | 0.97 |
March | 0.00 | 0.00 | 0.304210E+10 | 0.194418E+10 | 3868.77 | 15-MAR-08:61 | 2944.34 | 0.96 |
April | 0.00 | 0.00 | 0.300402E+10 | 0.189953E+10 | 3732.80 | 10-APR-08:61 | 3029.20 | 0.96 |
May | 0.00 | 0.00 | 0.296407E+10 | 0.179737E+10 | 3805.80 | 26-MAY-08:61 | 2989.03 | 0.96 |
June | 0.00 | 0.00 | 0.295722E+10 | 0.181767E+10 | 3798.00 | 27-JUN-08:62 | 2988.59 | 0.97 |
July | 0.00 | 0.00 | 0.262699E+10 | 0.149185E+10 | 3920.57 | 22-JUL-08:61 | 2893.98 | 0.96 |
August | 0.00 | 0.00 | 0.265762E+10 | 0.150972E+10 | 4234.56 | 19-AUG-18:02 | 2632.61 | 0.96 |
September | 0.00 | 0.00 | 0.265435E+10 | 0.153478E+10 | 4235.18 | 18-SEP-08:61 | 2651.77 | 0.96 |
October | 0.00 | 0.00 | 0.259781E+10 | 0.145853E+10 | 4265.00 | 30-OCT-18:02 | 2611.44 | 0.96 |
November | 0.00 | 0.00 | 0.260522E+10 | 0.152306E+10 | 4199.36 | 26-NOV-09:02 | 2677.15 | 0.96 |
December | 0.00 | 0.00 | 0.269518E+10 | 0.160782E+10 | 4052.24 | 24-DEC-09:02 | 2803.99 | 0.96 |
Annual Sum or Average | 0.00 | 0.00 | 0.332935E+11 | 0.199947E+11 | 0.96 | |||
Minimum of Months | 0.00 | 0.00 | 0.259781E+10 | 0.145853E+10 | 3732.80 | 2611.44 | 0.96 | |
Maximum of Months | 0.00 | 0.00 | 0.304210E+10 | 0.194418E+10 | 4265.00 | 3029.20 | 0.97 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.236193E+10 | 0.136082E+10 | 4537.46 | 07-JAN-09:11 | 2876.27 | 0.87 |
February | 0.00 | 0.00 | 0.238047E+10 | 0.144784E+10 | 4390.90 | 23-FEB-09:11 | 3039.05 | 0.90 |
March | 0.00 | 0.00 | 0.290295E+10 | 0.181711E+10 | 4278.11 | 15-MAR-08:61 | 2690.28 | 0.95 |
April | 0.00 | 0.00 | 0.302088E+10 | 0.191041E+10 | 3874.48 | 14-APR-17:02 | 3583.04 | 0.96 |
May | 0.00 | 0.00 | 0.305680E+10 | 0.187995E+10 | 4281.71 | 10-MAY-21:51 | 3138.31 | 0.96 |
June | 0.00 | 0.00 | 0.312667E+10 | 0.198070E+10 | 4645.03 | 25-JUN-21:51 | 2899.78 | 0.96 |
July | 0.00 | 0.00 | 0.272478E+10 | 0.159269E+10 | 4709.11 | 19-JUL-21:51 | 2989.13 | 0.95 |
August | 0.00 | 0.00 | 0.269722E+10 | 0.154774E+10 | 4712.22 | 19-AUG-20:11 | 2552.59 | 0.95 |
September | 0.00 | 0.00 | 0.260267E+10 | 0.148809E+10 | 4556.25 | 15-SEP-21:51 | 2721.97 | 0.94 |
October | 0.00 | 0.00 | 0.243720E+10 | 0.131694E+10 | 4711.67 | 23-OCT-08:61 | 2517.44 | 0.93 |
November | 0.00 | 0.00 | 0.229806E+10 | 0.126016E+10 | 4545.30 | 26-NOV-09:51 | 2670.12 | 0.90 |
December | 0.00 | 0.00 | 0.224476E+10 | 0.124519E+10 | 4666.14 | 24-DEC-09:41 | 2675.56 | 0.86 |
Annual Sum or Average | 0.00 | 0.00 | 0.318544E+11 | 0.188476E+11 | 0.93 | |||
Minimum of Months | 0.00 | 0.00 | 0.224476E+10 | 0.124519E+10 | 3874.48 | 2517.44 | 0.86 | |
Maximum of Months | 0.00 | 0.00 | 0.312667E+10 | 0.198070E+10 | 4712.22 | 3583.04 | 0.96 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.169585E+11 | 0.118190E+11 | 15963.40 | 08-JAN-09:02 | 11977.09 | 0.97 |
February | 0.00 | 0.00 | 0.151956E+11 | 0.106172E+11 | 14789.23 | 08-FEB-09:02 | 12856.69 | 0.97 |
March | 0.00 | 0.00 | 0.151956E+11 | 0.102690E+11 | 15226.11 | 15-MAR-08:61 | 12538.64 | 0.96 |
April | 0.00 | 0.00 | 0.139228E+11 | 0.898676E+10 | 14406.76 | 10-APR-08:61 | 13056.37 | 0.96 |
May | 0.00 | 0.00 | 0.143314E+11 | 0.909531E+10 | 14954.53 | 17-MAY-15:02 | 12643.33 | 0.96 |
June | 0.00 | 0.00 | 0.139472E+11 | 0.882052E+10 | 14982.58 | 27-JUN-08:62 | 12676.06 | 0.96 |
July | 0.00 | 0.00 | 0.129861E+11 | 0.785475E+10 | 15676.78 | 22-JUL-08:61 | 12165.36 | 0.95 |
August | 0.00 | 0.00 | 0.128933E+11 | 0.766941E+10 | 18827.25 | 19-AUG-18:02 | 9666.46 | 0.95 |
September | 0.00 | 0.00 | 0.133406E+11 | 0.824250E+10 | 17670.04 | 18-SEP-08:61 | 10668.10 | 0.96 |
October | 0.00 | 0.00 | 0.141893E+11 | 0.896744E+10 | 18332.05 | 30-OCT-18:02 | 10078.13 | 0.96 |
November | 0.00 | 0.00 | 0.153050E+11 | 0.102224E+11 | 17034.18 | 26-NOV-09:02 | 11149.87 | 0.97 |
December | 0.00 | 0.00 | 0.167352E+11 | 0.114339E+11 | 16283.17 | 14-DEC-09:02 | 11760.85 | 0.97 |
Annual Sum or Average | 0.00 | 0.00 | 0.175001E+12 | 0.113998E+12 | 0.96 | |||
Minimum of Months | 0.00 | 0.00 | 0.128933E+11 | 0.766941E+10 | 14406.76 | 9666.46 | 0.95 | |
Maximum of Months | 0.00 | 0.00 | 0.169585E+11 | 0.118190E+11 | 18827.25 | 13056.37 | 0.97 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 441601.09 | 671839.35 | 10-JAN-19:03 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 449698.67 | 662277.58 | 14-FEB-19:02 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 465358.88 | 675041.83 | 28-MAR-18:02 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 520397.99 | 792043.77 | 10-APR-18:03 | 0.00 | 0.00 | 01-APR-00:10 |
May | 566542.52 | 810386.71 | 22-MAY-18:03 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 575740.02 | 798265.80 | 11-JUN-18:05 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 488271.90 | 740027.91 | 17-JUL-18:50 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 536054.21 | 808417.21 | 08-AUG-18:03 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 525771.32 | 769788.10 | 08-SEP-18:03 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 505506.85 | 730310.36 | 17-OCT-18:03 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 485711.46 | 724664.02 | 14-NOV-19:03 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 464526.87 | 696055.08 | 10-DEC-19:03 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 502257.31 | 0.00 | ||||
Minimum of Months | 441601.09 | 662277.58 | 0.00 | 0.00 | ||
Maximum of Months | 575740.02 | 810386.71 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 16426.64 | 34376.87 | 12-JAN-07:55 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 16326.32 | 34295.24 | 01-FEB-08:00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 16089.33 | 33926.27 | 01-MAR-07:40 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15741.97 | 33218.89 | 03-APR-06:30 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15411.80 | 32546.29 | 01-MAY-06:15 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15180.45 | 31917.19 | 01-JUN-06:20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15088.62 | 31610.57 | 31-JUL-06:20 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 15209.63 | 32007.09 | 31-AUG-06:20 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 15458.08 | 32621.97 | 29-SEP-06:15 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 15790.18 | 33389.94 | 31-OCT-07:00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 16121.29 | 33998.99 | 30-NOV-08:00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 16353.77 | 34332.18 | 29-DEC-08:00 |
Annual Sum or Average | 0.00 | 15763.45 | ||||
Minimum of Months | 0.00 | 0.00 | 15088.62 | 31610.57 | ||
Maximum of Months | 0.00 | 0.00 | 16426.64 | 34376.87 |
Report: FanReportMonthly
For: FLR_3_DOAS FAN
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.271000E+10 | 0.69 | 1299.30 | 04-JAN-16:25 | 0.87 |
February | 0.244774E+10 | 0.69 | 1299.30 | 01-FEB-09:15 | 0.87 |
March | 0.271000E+10 | 0.69 | 1299.30 | 02-MAR-16:25 | 0.87 |
April | 0.262258E+10 | 0.69 | 1299.30 | 01-APR-15:17 | 0.87 |
May | 0.271000E+10 | 0.69 | 1299.30 | 01-MAY-15:07 | 0.87 |
June | 0.262258E+10 | 0.69 | 1299.30 | 01-JUN-19:10 | 0.87 |
July | 0.271000E+10 | 0.69 | 1299.30 | 01-JUL-17:00 | 0.87 |
August | 0.271000E+10 | 0.69 | 1299.30 | 01-AUG-15:20 | 0.87 |
September | 0.262258E+10 | 0.69 | 1299.30 | 02-SEP-15:20 | 0.87 |
October | 0.271000E+10 | 0.69 | 1299.30 | 01-OCT-16:30 | 0.87 |
November | 0.262258E+10 | 0.69 | 1299.30 | 02-NOV-15:17 | 0.87 |
December | 0.271000E+10 | 0.69 | 1299.30 | 03-DEC-16:07 | 0.87 |
Annual Sum or Average | 0.319080E+11 | 0.69 | |||
Minimum of Months | 0.244774E+10 | 0.69 | 1299.30 | 0.87 | |
Maximum of Months | 0.271000E+10 | 0.69 | 1299.30 | 0.87 |
Report: FanReportMonthly
For: VAV WITH REHEAT FAN
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.303833E+11 | 0.73 | 17141.79 | 05-JAN-21:10 | 0.93 |
February | 0.278378E+11 | 0.74 | 17087.78 | 22-FEB-21:10 | 0.93 |
March | 0.309440E+11 | 0.74 | 17335.04 | 29-MAR-20:10 | 0.94 |
April | 0.301874E+11 | 0.74 | 17924.03 | 27-APR-20:10 | 0.95 |
May | 0.315054E+11 | 0.75 | 19521.87 | 05-MAY-20:10 | 1.00 |
June | 0.314087E+11 | 0.76 | 20918.38 | 13-JUN-20:10 | 1.05 |
July | 0.307288E+11 | 0.74 | 18340.55 | 14-JUL-20:10 | 0.97 |
August | 0.304292E+11 | 0.73 | 17815.31 | 14-AUG-20:10 | 0.95 |
September | 0.294439E+11 | 0.73 | 17321.33 | 13-SEP-20:10 | 0.93 |
October | 0.299257E+11 | 0.73 | 16668.45 | 04-OCT-20:10 | 0.91 |
November | 0.291763E+11 | 0.73 | 16460.11 | 21-NOV-21:10 | 0.91 |
December | 0.301192E+11 | 0.73 | 16910.94 | 08-DEC-21:10 | 0.92 |
Annual Sum or Average | 0.362090E+12 | 0.74 | |||
Minimum of Months | 0.278378E+11 | 0.73 | 16460.11 | 0.91 | |
Maximum of Months | 0.315054E+11 | 0.76 | 20918.38 | 1.05 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205205E+09 | 0.26 | 76.61 | 01-JAN-00:05 | 0.26 |
February | 0.185347E+09 | 0.26 | 76.61 | 01-FEB-00:03 | 0.26 |
March | 0.205205E+09 | 0.26 | 76.61 | 01-MAR-00:03 | 0.26 |
April | 0.198586E+09 | 0.26 | 76.61 | 01-APR-00:10 | 0.26 |
May | 0.205205E+09 | 0.26 | 76.61 | 01-MAY-00:10 | 0.26 |
June | 0.198586E+09 | 0.26 | 76.61 | 01-JUN-00:10 | 0.26 |
July | 0.205205E+09 | 0.26 | 76.61 | 01-JUL-00:10 | 0.26 |
August | 0.205205E+09 | 0.26 | 76.61 | 01-AUG-00:10 | 0.26 |
September | 0.198586E+09 | 0.26 | 76.61 | 01-SEP-00:10 | 0.26 |
October | 0.205205E+09 | 0.26 | 76.61 | 01-OCT-00:10 | 0.26 |
November | 0.198586E+09 | 0.26 | 76.61 | 01-NOV-00:10 | 0.26 |
December | 0.205205E+09 | 0.26 | 76.61 | 01-DEC-00:03 | 0.26 |
Annual Sum or Average | 0.241613E+10 | 0.26 | |||
Minimum of Months | 0.185347E+09 | 0.26 | 76.61 | 0.26 | |
Maximum of Months | 0.205205E+09 | 0.26 | 76.61 | 0.26 |
Report: FanReportMonthly
For: LOBBY_FLR_1 EXHAUST FAN
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:10 | -0.0 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | -0.0 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 EXHAUST FAN
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 EXHAUST FAN
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116283E+10 | 0.19 | 612.92 | 01-JAN-07:03 | 0.26 |
February | 0.105030E+10 | 0.19 | 612.92 | 01-FEB-07:03 | 0.26 |
March | 0.116283E+10 | 0.19 | 612.92 | 01-MAR-07:03 | 0.26 |
April | 0.112532E+10 | 0.19 | 612.92 | 01-APR-06:10 | 0.26 |
May | 0.116283E+10 | 0.19 | 612.92 | 01-MAY-06:03 | 0.26 |
June | 0.112532E+10 | 0.19 | 612.92 | 01-JUN-06:03 | 0.26 |
July | 0.116283E+10 | 0.19 | 612.92 | 01-JUL-06:05 | 0.26 |
August | 0.116283E+10 | 0.19 | 612.92 | 01-AUG-06:03 | 0.26 |
September | 0.112532E+10 | 0.19 | 612.92 | 01-SEP-06:03 | 0.26 |
October | 0.116283E+10 | 0.19 | 612.92 | 01-OCT-06:03 | 0.26 |
November | 0.112532E+10 | 0.19 | 612.92 | 01-NOV-06:03 | 0.26 |
December | 0.116283E+10 | 0.19 | 612.92 | 01-DEC-07:03 | 0.26 |
Annual Sum or Average | 0.136914E+11 | 0.19 | |||
Minimum of Months | 0.105030E+10 | 0.19 | 612.92 | 0.26 | |
Maximum of Months | 0.116283E+10 | 0.19 | 612.92 | 0.26 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.450008E+09 | 0.55 | 653.39 | 01-JAN-09:01 | 0.57 |
February | 0.440335E+09 | 0.55 | 653.39 | 01-FEB-09:02 | 0.57 |
March | 0.495725E+09 | 0.55 | 653.39 | 01-MAR-09:02 | 0.57 |
April | 0.480221E+09 | 0.55 | 653.39 | 01-APR-08:62 | 0.57 |
May | 0.471803E+09 | 0.55 | 653.39 | 01-MAY-08:62 | 0.57 |
June | 0.480259E+09 | 0.55 | 653.39 | 01-JUN-08:61 | 0.57 |
July | 0.417007E+09 | 0.55 | 653.39 | 01-JUL-08:61 | 0.57 |
August | 0.414263E+09 | 0.55 | 653.39 | 01-AUG-08:62 | 0.57 |
September | 0.412224E+09 | 0.55 | 653.39 | 01-SEP-08:62 | 0.57 |
October | 0.403293E+09 | 0.55 | 653.39 | 01-OCT-08:62 | 0.57 |
November | 0.407513E+09 | 0.55 | 653.39 | 01-NOV-08:61 | 0.57 |
December | 0.429568E+09 | 0.55 | 653.39 | 01-DEC-09:02 | 0.57 |
Annual Sum or Average | 0.530222E+10 | 0.55 | |||
Minimum of Months | 0.403293E+09 | 0.55 | 653.39 | 0.57 | |
Maximum of Months | 0.495725E+09 | 0.55 | 653.39 | 0.57 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.370596E+09 | 0.50 | 661.67 | 01-JAN-09:01 | 0.57 |
February | 0.382580E+09 | 0.51 | 661.67 | 01-FEB-09:11 | 0.57 |
March | 0.468083E+09 | 0.55 | 661.67 | 01-MAR-09:02 | 0.57 |
April | 0.481794E+09 | 0.55 | 661.67 | 01-APR-08:62 | 0.57 |
May | 0.489365E+09 | 0.55 | 661.67 | 01-MAY-08:62 | 0.57 |
June | 0.515068E+09 | 0.55 | 661.67 | 01-JUN-08:61 | 0.57 |
July | 0.434301E+09 | 0.54 | 661.67 | 01-JUL-08:61 | 0.57 |
August | 0.420808E+09 | 0.54 | 661.67 | 01-AUG-08:62 | 0.57 |
September | 0.402913E+09 | 0.54 | 661.67 | 01-SEP-08:62 | 0.57 |
October | 0.376504E+09 | 0.53 | 661.67 | 01-OCT-08:62 | 0.57 |
November | 0.355306E+09 | 0.52 | 661.67 | 01-NOV-08:61 | 0.57 |
December | 0.347831E+09 | 0.49 | 661.67 | 01-DEC-09:02 | 0.57 |
Annual Sum or Average | 0.504515E+10 | 0.53 | |||
Minimum of Months | 0.347831E+09 | 0.49 | 661.67 | 0.57 | |
Maximum of Months | 0.515068E+09 | 0.55 | 661.67 | 0.57 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.204158E+10 | 0.57 | 1743.96 | 05-JAN-14:00 | 0.57 |
February | 0.181566E+10 | 0.57 | 1128.14 | 04-FEB-14:30 | 0.57 |
March | 0.176811E+10 | 0.57 | 960.36 | 11-MAR-09:00 | 0.57 |
April | 0.156494E+10 | 0.57 | 911.91 | 01-APR-20:20 | 0.57 |
May | 0.160643E+10 | 0.57 | 950.04 | 06-MAY-08:00 | 0.57 |
June | 0.155849E+10 | 0.57 | 915.61 | 13-JUN-20:20 | 0.57 |
July | 0.148440E+10 | 0.57 | 866.09 | 15-JUL-20:10 | 0.57 |
August | 0.144542E+10 | 0.57 | 866.90 | 13-AUG-08:00 | 0.57 |
September | 0.151619E+10 | 0.57 | 893.26 | 27-SEP-20:20 | 0.57 |
October | 0.164174E+10 | 0.57 | 1012.73 | 29-OCT-08:00 | 0.57 |
November | 0.181152E+10 | 0.57 | 1174.34 | 23-NOV-09:00 | 0.57 |
December | 0.201084E+10 | 0.57 | 1757.01 | 07-DEC-13:30 | 0.57 |
Annual Sum or Average | 0.202653E+11 | 0.57 | |||
Minimum of Months | 0.144542E+10 | 0.57 | 866.09 | 0.57 | |
Maximum of Months | 0.204158E+10 | 0.57 | 1757.01 | 0.57 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.271465E+10 | 0.46 | 4461.98 | 01-JAN-09:01 | 0.57 |
February | 0.264865E+10 | 0.47 | 4461.98 | 01-FEB-09:11 | 0.57 |
March | 0.308348E+10 | 0.50 | 4461.98 | 01-MAR-09:02 | 0.57 |
April | 0.322186E+10 | 0.51 | 4461.98 | 01-APR-08:62 | 0.57 |
May | 0.362279E+10 | 0.52 | 4461.98 | 01-MAY-08:62 | 0.57 |
June | 0.387985E+10 | 0.53 | 4461.98 | 01-JUN-08:61 | 0.57 |
July | 0.342673E+10 | 0.50 | 4461.98 | 01-JUL-08:61 | 0.57 |
August | 0.317030E+10 | 0.50 | 4461.98 | 01-AUG-08:62 | 0.57 |
September | 0.294945E+10 | 0.50 | 4461.98 | 01-SEP-08:62 | 0.57 |
October | 0.285003E+10 | 0.48 | 4461.98 | 01-OCT-08:62 | 0.57 |
November | 0.269602E+10 | 0.47 | 4461.98 | 01-NOV-08:61 | 0.57 |
December | 0.262968E+10 | 0.45 | 4461.98 | 01-DEC-09:02 | 0.57 |
Annual Sum or Average | 0.368935E+11 | 0.49 | |||
Minimum of Months | 0.262968E+10 | 0.45 | 4461.98 | 0.57 | |
Maximum of Months | 0.387985E+10 | 0.53 | 4461.98 | 0.57 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.461655E+09 | 0.56 | 580.11 | 01-JAN-09:01 | 0.57 |
February | 0.455244E+09 | 0.56 | 580.11 | 01-FEB-09:02 | 0.57 |
March | 0.499343E+09 | 0.56 | 580.11 | 01-MAR-09:02 | 0.57 |
April | 0.487909E+09 | 0.56 | 580.11 | 01-APR-08:62 | 0.57 |
May | 0.482677E+09 | 0.56 | 580.11 | 01-MAY-08:62 | 0.57 |
June | 0.488093E+09 | 0.56 | 580.11 | 01-JUN-08:61 | 0.57 |
July | 0.422958E+09 | 0.55 | 580.11 | 01-JUL-08:61 | 0.57 |
August | 0.421052E+09 | 0.55 | 580.11 | 01-AUG-08:62 | 0.57 |
September | 0.420623E+09 | 0.56 | 580.11 | 01-SEP-08:62 | 0.57 |
October | 0.410214E+09 | 0.55 | 580.11 | 01-OCT-08:62 | 0.57 |
November | 0.421030E+09 | 0.56 | 580.11 | 01-NOV-08:61 | 0.57 |
December | 0.441174E+09 | 0.56 | 580.11 | 01-DEC-09:02 | 0.57 |
Annual Sum or Average | 0.541197E+10 | 0.56 | |||
Minimum of Months | 0.410214E+09 | 0.55 | 580.11 | 0.57 | |
Maximum of Months | 0.499343E+09 | 0.56 | 580.11 | 0.57 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.379214E+09 | 0.50 | 585.56 | 01-JAN-09:01 | 0.57 |
February | 0.396373E+09 | 0.52 | 585.56 | 01-FEB-09:11 | 0.57 |
March | 0.473323E+09 | 0.55 | 585.56 | 01-MAR-09:02 | 0.57 |
April | 0.491011E+09 | 0.56 | 585.56 | 01-APR-08:62 | 0.57 |
May | 0.500863E+09 | 0.56 | 585.56 | 01-MAY-08:62 | 0.57 |
June | 0.520791E+09 | 0.55 | 585.56 | 01-JUN-08:61 | 0.57 |
July | 0.441639E+09 | 0.55 | 585.56 | 01-JUL-08:61 | 0.57 |
August | 0.428389E+09 | 0.55 | 585.56 | 01-AUG-08:62 | 0.57 |
September | 0.410892E+09 | 0.55 | 585.56 | 01-SEP-08:62 | 0.57 |
October | 0.380496E+09 | 0.54 | 585.56 | 01-OCT-08:62 | 0.57 |
November | 0.363205E+09 | 0.52 | 585.56 | 01-NOV-08:61 | 0.57 |
December | 0.354658E+09 | 0.50 | 585.56 | 01-DEC-08:42 | 0.57 |
Annual Sum or Average | 0.514085E+10 | 0.54 | |||
Minimum of Months | 0.354658E+09 | 0.50 | 585.56 | 0.57 | |
Maximum of Months | 0.520791E+09 | 0.56 | 585.56 | 0.57 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.115994E+09 | 0.55 | 179.02 | 01-JAN-09:01 | 0.57 |
February | 0.112770E+09 | 0.55 | 179.02 | 01-FEB-09:02 | 0.57 |
March | 0.130194E+09 | 0.55 | 179.02 | 01-MAR-09:02 | 0.57 |
April | 0.127841E+09 | 0.55 | 179.02 | 01-APR-08:62 | 0.57 |
May | 0.122158E+09 | 0.55 | 179.02 | 01-MAY-08:62 | 0.57 |
June | 0.123393E+09 | 0.55 | 179.02 | 01-JUN-08:61 | 0.57 |
July | 0.108298E+09 | 0.55 | 179.02 | 01-JUL-08:61 | 0.57 |
August | 0.108256E+09 | 0.55 | 179.02 | 01-AUG-08:62 | 0.57 |
September | 0.108322E+09 | 0.55 | 179.02 | 01-SEP-08:62 | 0.57 |
October | 0.105024E+09 | 0.55 | 179.02 | 01-OCT-08:62 | 0.57 |
November | 0.104639E+09 | 0.55 | 179.02 | 01-NOV-08:61 | 0.57 |
December | 0.109624E+09 | 0.55 | 179.02 | 01-DEC-09:02 | 0.57 |
Annual Sum or Average | 0.137651E+10 | 0.55 | |||
Minimum of Months | 0.104639E+09 | 0.55 | 179.02 | 0.57 | |
Maximum of Months | 0.130194E+09 | 0.55 | 179.02 | 0.57 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 96228008.20 | 0.50 | 181.11 | 01-JAN-09:01 | 0.57 |
February | 97889851.04 | 0.51 | 181.11 | 01-FEB-09:11 | 0.57 |
March | 0.122665E+09 | 0.55 | 181.11 | 01-MAR-09:02 | 0.57 |
April | 0.128420E+09 | 0.55 | 181.11 | 01-APR-08:62 | 0.57 |
May | 0.127025E+09 | 0.55 | 181.11 | 01-MAY-08:62 | 0.57 |
June | 0.131802E+09 | 0.55 | 181.11 | 01-JUN-08:61 | 0.57 |
July | 0.112772E+09 | 0.54 | 181.11 | 01-JUL-08:61 | 0.57 |
August | 0.110164E+09 | 0.54 | 181.11 | 01-AUG-08:62 | 0.57 |
September | 0.106016E+09 | 0.54 | 181.11 | 01-SEP-08:62 | 0.57 |
October | 98208281.12 | 0.54 | 181.11 | 01-OCT-08:62 | 0.57 |
November | 91696564.36 | 0.52 | 181.11 | 01-NOV-08:61 | 0.57 |
December | 89922352.60 | 0.50 | 181.11 | 01-DEC-09:02 | 0.57 |
Annual Sum or Average | 0.131281E+10 | 0.53 | |||
Minimum of Months | 89922352.60 | 0.50 | 181.11 | 0.57 | |
Maximum of Months | 0.131802E+09 | 0.55 | 181.11 | 0.57 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.750272E+09 | 0.56 | 724.07 | 01-JAN-09:01 | 0.57 |
February | 0.666065E+09 | 0.56 | 724.07 | 01-FEB-09:02 | 0.57 |
March | 0.653597E+09 | 0.55 | 724.07 | 01-MAR-09:02 | 0.57 |
April | 0.583572E+09 | 0.55 | 724.07 | 01-APR-08:62 | 0.57 |
May | 0.596489E+09 | 0.55 | 724.07 | 01-MAY-08:62 | 0.57 |
June | 0.581485E+09 | 0.55 | 724.07 | 01-JUN-08:61 | 0.57 |
July | 0.538279E+09 | 0.55 | 724.07 | 01-JUL-08:61 | 0.57 |
August | 0.526481E+09 | 0.54 | 724.07 | 01-AUG-08:62 | 0.57 |
September | 0.551332E+09 | 0.55 | 724.07 | 01-SEP-08:62 | 0.57 |
October | 0.589777E+09 | 0.55 | 724.07 | 01-OCT-08:62 | 0.57 |
November | 0.655265E+09 | 0.55 | 724.07 | 01-NOV-08:61 | 0.57 |
December | 0.736858E+09 | 0.56 | 724.07 | 01-DEC-09:02 | 0.57 |
Annual Sum or Average | 0.742947E+10 | 0.55 | |||
Minimum of Months | 0.526481E+09 | 0.54 | 724.07 | 0.57 | |
Maximum of Months | 0.750272E+09 | 0.56 | 724.07 | 0.57 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.158658E+10 | 0.142792E+10 | 1240.19 | 10-JAN-19:02 | 1116.17 | 1116.17 | 6.72 | 18.20 |
February | 0.147774E+10 | 0.132996E+10 | 1263.42 | 14-FEB-19:02 | 1137.08 | 1137.08 | 6.72 | 18.34 |
March | 0.175817E+10 | 0.158235E+10 | 1379.05 | 14-MAR-21:40 | 1241.14 | 1241.14 | 6.72 | 19.03 |
April | 0.210477E+10 | 0.189429E+10 | 1784.44 | 10-APR-18:02 | 1605.99 | 1605.99 | 6.72 | 21.19 |
May | 0.258164E+10 | 0.232348E+10 | 1947.61 | 31-MAY-20:20 | 1752.84 | 1752.84 | 6.72 | 21.97 |
June | 0.259226E+10 | 0.233304E+10 | 1953.28 | 07-JUN-18:02 | 1757.95 | 1757.95 | 6.72 | 22.00 |
July | 0.192393E+10 | 0.173154E+10 | 1773.63 | 17-JUL-18:50 | 1596.27 | 1596.27 | 6.72 | 21.14 |
August | 0.229862E+10 | 0.206876E+10 | 1897.78 | 14-AUG-18:02 | 1708.01 | 1708.01 | 6.72 | 21.74 |
September | 0.212554E+10 | 0.191299E+10 | 1712.67 | 08-SEP-18:02 | 1541.40 | 1541.40 | 6.72 | 20.83 |
October | 0.203826E+10 | 0.183443E+10 | 1499.64 | 17-OCT-18:02 | 1349.68 | 1349.68 | 6.72 | 19.71 |
November | 0.184260E+10 | 0.165834E+10 | 1491.88 | 30-NOV-23:00 | 1342.69 | 1342.69 | 6.72 | 19.67 |
December | 0.174440E+10 | 0.156996E+10 | 1344.39 | 21-DEC-22:00 | 1209.95 | 1209.95 | 6.72 | 18.83 |
Annual Sum or Average | 0.240745E+11 | 0.216671E+11 | ||||||
Minimum of Months | 0.147774E+10 | 0.132996E+10 | 1240.19 | 1116.17 | 1116.17 | 6.72 | 18.20 | |
Maximum of Months | 0.259226E+10 | 0.233304E+10 | 1953.28 | 1757.95 | 1757.95 | 6.72 | 22.00 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.100669E+11 | 0.906017E+10 | 3758.53 | 01-JAN-00:05 | 3382.68 | 3382.68 | 9.76 | 33.25 |
February | 0.909265E+10 | 0.818338E+10 | 3758.53 | 01-FEB-00:03 | 3382.68 | 3382.68 | 9.72 | 33.25 |
March | 0.100669E+11 | 0.906017E+10 | 3758.53 | 01-MAR-00:03 | 3382.68 | 3382.68 | 9.78 | 33.25 |
April | 0.974212E+10 | 0.876791E+10 | 3758.53 | 01-APR-00:10 | 3382.68 | 3382.68 | 10.11 | 33.25 |
May | 0.100669E+11 | 0.906017E+10 | 3758.53 | 01-MAY-00:10 | 3382.68 | 3382.68 | 10.44 | 33.25 |
June | 0.974212E+10 | 0.876791E+10 | 3758.53 | 01-JUN-00:10 | 3382.68 | 3382.68 | 10.07 | 33.25 |
July | 0.100669E+11 | 0.906017E+10 | 3758.53 | 01-JUL-00:10 | 3382.68 | 3382.68 | 9.96 | 33.25 |
August | 0.100669E+11 | 0.906017E+10 | 3758.53 | 01-AUG-00:10 | 3382.68 | 3382.68 | 10.11 | 33.25 |
September | 0.974212E+10 | 0.876791E+10 | 3758.53 | 01-SEP-00:10 | 3382.68 | 3382.68 | 10.25 | 33.25 |
October | 0.100669E+11 | 0.906017E+10 | 3758.53 | 01-OCT-00:10 | 3382.68 | 3382.68 | 10.18 | 33.25 |
November | 0.974212E+10 | 0.876791E+10 | 3758.53 | 01-NOV-00:10 | 3382.68 | 3382.68 | 10.00 | 33.25 |
December | 0.100669E+11 | 0.906017E+10 | 3758.53 | 01-DEC-00:03 | 3382.68 | 3382.68 | 9.90 | 33.25 |
Annual Sum or Average | 0.118529E+12 | 0.106676E+12 | ||||||
Minimum of Months | 0.909265E+10 | 0.818338E+10 | 3758.53 | 3382.68 | 3382.68 | 9.72 | 33.25 | |
Maximum of Months | 0.100669E+11 | 0.906017E+10 | 3758.53 | 3382.68 | 3382.68 | 10.44 | 33.25 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:05 | 14.37 | 14.37 | 52.99 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:03 | 14.37 | 14.37 | 53.57 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:03 | 14.37 | 14.37 | 53.64 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 55.51 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:10 | 14.37 | 14.37 | 55.61 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:10 | 14.37 | 14.37 | 55.69 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 55.74 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:10 | 14.37 | 14.37 | 55.73 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:10 | 14.37 | 14.37 | 55.68 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:10 | 14.37 | 14.37 | 55.06 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:10 | 14.37 | 14.37 | 55.49 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:03 | 14.37 | 14.37 | 53.63 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 52.99 | 0.37 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 55.74 | 0.37 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 441601.09 | 671839.35 | 10-JAN-19:03 | 11.52 | 6.70 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 449698.67 | 662277.58 | 14-FEB-19:02 | 11.45 | 6.70 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 465358.88 | 675041.83 | 28-MAR-18:02 | 11.55 | 6.70 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 520397.99 | 792043.77 | 10-APR-18:03 | 12.39 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 566542.52 | 810386.71 | 22-MAY-18:03 | 12.52 | 6.70 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 575740.02 | 798265.80 | 11-JUN-18:05 | 12.43 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 488271.90 | 740027.91 | 17-JUL-18:50 | 12.01 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 536054.21 | 808417.21 | 08-AUG-18:03 | 12.51 | 6.70 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 525771.32 | 769788.10 | 08-SEP-18:03 | 12.23 | 6.70 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 505506.85 | 730310.36 | 17-OCT-18:03 | 11.94 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 485711.46 | 724664.02 | 14-NOV-19:03 | 11.90 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 464526.87 | 696055.08 | 10-DEC-19:03 | 11.70 | 6.70 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 502257.31 | 0.00 | ||||||
Minimum of Months | 441601.09 | 662277.58 | 11.45 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 575740.02 | 810386.71 | 12.52 | 6.70 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 52.99 | 60.05 | 16426.64 | 34376.87 | 12-JAN-07:55 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 53.57 | 60.05 | 16326.32 | 34295.24 | 01-FEB-08:00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 53.64 | 60.05 | 16089.33 | 33926.27 | 01-MAR-07:40 |
April | 0.00 | 0.00 | 01-APR-00:10 | 55.51 | 60.05 | 15741.97 | 33218.89 | 03-APR-06:30 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 55.61 | 60.05 | 15411.80 | 32546.29 | 01-MAY-06:15 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 55.69 | 60.05 | 15180.45 | 31917.19 | 01-JUN-06:20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 55.74 | 60.05 | 15088.62 | 31610.57 | 31-JUL-06:20 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 55.73 | 60.05 | 15209.63 | 32007.09 | 31-AUG-06:20 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 55.68 | 60.05 | 15458.08 | 32621.97 | 29-SEP-06:15 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 55.06 | 60.05 | 15790.18 | 33389.94 | 31-OCT-07:00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 55.49 | 60.05 | 16121.29 | 33998.99 | 30-NOV-08:00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 53.63 | 60.05 | 16353.77 | 34332.18 | 29-DEC-08:00 |
Annual Sum or Average | 0.00 | 15763.45 | ||||||
Minimum of Months | 0.00 | 0.00 | 52.99 | 60.05 | 15088.62 | 31610.57 | ||
Maximum of Months | 0.00 | 0.00 | 55.74 | 60.05 | 16426.64 | 34376.87 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.568716E+11 | 0.271000E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.518421E+11 | 0.244774E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.598825E+11 | 0.271000E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.663997E+11 | 0.262258E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.758943E+11 | 0.271000E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.730128E+11 | 0.262258E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.641685E+11 | 0.271000E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.727064E+11 | 0.271000E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.687233E+11 | 0.262258E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.689498E+11 | 0.271000E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.627487E+11 | 0.262258E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.601053E+11 | 0.271000E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.781305E+12 | 0.319080E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.518421E+11 | 0.244774E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.758943E+11 | 0.271000E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.925071E+12 | 0.319031E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.847528E+12 | 0.290083E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.981663E+12 | 0.322259E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.108147E+13 | 0.313079E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.122872E+13 | 0.327898E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.120448E+13 | 0.325060E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.104745E+13 | 0.320373E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.117241E+13 | 0.319617E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.110689E+13 | 0.307715E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.109618E+13 | 0.315506E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.100579E+13 | 0.306423E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.987090E+12 | 0.316735E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.126848E+14 | 0.378378E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.847528E+12 | 0.290083E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.122872E+13 | 0.327898E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.271000E+10 | 0.568716E+11 | 0.00 | 0.00 | 0.392558E+11 | 0.00 | 0.00 | 0.00 |
February | 0.244774E+10 | 0.518421E+11 | 0.00 | 0.00 | 0.402329E+11 | 0.00 | 0.00 | 0.00 |
March | 0.271000E+10 | 0.598825E+11 | 0.00 | 0.00 | 0.514711E+11 | 0.00 | 0.00 | 0.00 |
April | 0.262258E+10 | 0.663997E+11 | 0.00 | 0.00 | 0.623939E+11 | 0.00 | 0.00 | 0.00 |
May | 0.271000E+10 | 0.758943E+11 | 0.00 | 0.00 | 0.729236E+11 | 0.00 | 0.00 | 0.00 |
June | 0.262258E+10 | 0.730128E+11 | 0.00 | 0.00 | 0.696977E+11 | 0.00 | 0.00 | 0.00 |
July | 0.271000E+10 | 0.641685E+11 | 0.00 | 0.00 | 0.549852E+11 | 0.00 | 0.00 | 0.00 |
August | 0.271000E+10 | 0.727064E+11 | 0.00 | 0.00 | 0.657620E+11 | 0.00 | 0.00 | 0.00 |
September | 0.262258E+10 | 0.687233E+11 | 0.00 | 0.00 | 0.617432E+11 | 0.00 | 0.00 | 0.00 |
October | 0.271000E+10 | 0.689498E+11 | 0.00 | 0.00 | 0.595748E+11 | 0.00 | 0.00 | 0.00 |
November | 0.262258E+10 | 0.627487E+11 | 0.00 | 0.00 | 0.506432E+11 | 0.00 | 0.00 | 0.00 |
December | 0.271000E+10 | 0.601053E+11 | 0.00 | 164860.88 | 0.411889E+11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319080E+11 | 0.781305E+12 | 0.00 | 164860.88 | 0.669872E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244774E+10 | 0.518421E+11 | 0.00 | 0.00 | 0.392558E+11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.271000E+10 | 0.758943E+11 | 0.00 | 164860.88 | 0.729236E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.303833E+11 | 0.925071E+12 | 0.151980E+10 | 0.00 | 0.323720E+12 | 0.00 | 0.00 | 0.00 |
February | 0.278378E+11 | 0.847528E+12 | 0.117046E+10 | 14541445.54 | 0.348513E+12 | 0.00 | 0.00 | 0.00 |
March | 0.309440E+11 | 0.981663E+12 | 0.128193E+10 | 0.00 | 0.454919E+12 | 0.00 | 0.00 | 0.00 |
April | 0.301874E+11 | 0.108147E+13 | 0.112050E+10 | 0.00 | 0.591358E+12 | 0.00 | 0.00 | 0.00 |
May | 0.315054E+11 | 0.122872E+13 | 0.128446E+10 | 0.00 | 0.712255E+12 | 0.00 | 0.00 | 0.00 |
June | 0.314087E+11 | 0.120448E+13 | 0.109730E+10 | 0.00 | 0.680585E+12 | 0.00 | 0.00 | 0.00 |
July | 0.307288E+11 | 0.104745E+13 | 0.130855E+10 | 0.00 | 0.522612E+12 | 0.00 | 0.00 | 0.00 |
August | 0.304292E+11 | 0.117241E+13 | 0.153253E+10 | 0.00 | 0.656650E+12 | 0.00 | 0.00 | 0.00 |
September | 0.294439E+11 | 0.110689E+13 | 0.132761E+10 | 0.00 | 0.601586E+12 | 0.00 | 0.00 | 0.00 |
October | 0.299257E+11 | 0.109618E+13 | 0.162488E+10 | 0.00 | 0.579281E+12 | 0.00 | 0.00 | 0.00 |
November | 0.291763E+11 | 0.100579E+13 | 0.146609E+10 | 0.00 | 0.462630E+12 | 0.00 | 0.00 | 0.00 |
December | 0.301192E+11 | 0.987090E+12 | 0.155432E+10 | 0.00 | 0.333857E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.362090E+12 | 0.126848E+14 | 0.162884E+11 | 14541445.54 | 0.626797E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.278378E+11 | 0.847528E+12 | 0.109730E+10 | 0.00 | 0.323720E+12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.315054E+11 | 0.122872E+13 | 0.162488E+10 | 14541445.54 | 0.712255E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.271000E+10 | 0.00 | 0.568716E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244774E+10 | 0.00 | 0.518421E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.271000E+10 | 0.00 | 0.598825E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.262258E+10 | 0.00 | 0.663997E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.271000E+10 | 0.00 | 0.758943E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.262258E+10 | 0.00 | 0.730128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.271000E+10 | 0.00 | 0.641685E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.271000E+10 | 0.00 | 0.727064E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.262258E+10 | 0.00 | 0.687233E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.271000E+10 | 0.00 | 0.689498E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.262258E+10 | 0.00 | 0.627487E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.271000E+10 | 0.00 | 0.601053E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319080E+11 | 0.00 | 0.781305E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244774E+10 | 0.00 | 0.518421E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.271000E+10 | 0.00 | 0.758943E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.303833E+11 | 0.00 | 0.925071E+12 | 0.00 | 0.00 | 0.151980E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.278378E+11 | 0.00 | 0.847528E+12 | 0.00 | 0.00 | 0.117046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.309440E+11 | 0.00 | 0.981663E+12 | 0.00 | 0.00 | 0.128193E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.301874E+11 | 0.00 | 0.108147E+13 | 0.00 | 0.00 | 0.112050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.315054E+11 | 0.00 | 0.122872E+13 | 0.00 | 0.00 | 0.128446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.314087E+11 | 0.00 | 0.120448E+13 | 0.00 | 0.00 | 0.109730E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.307288E+11 | 0.00 | 0.104745E+13 | 0.00 | 0.00 | 0.130855E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.304292E+11 | 0.00 | 0.117241E+13 | 0.00 | 0.00 | 0.153253E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.294439E+11 | 0.00 | 0.110689E+13 | 0.00 | 0.00 | 0.132761E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.299257E+11 | 0.00 | 0.109618E+13 | 0.00 | 0.00 | 0.162488E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.291763E+11 | 0.00 | 0.100579E+13 | 0.00 | 0.00 | 0.146609E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.301192E+11 | 0.00 | 0.987090E+12 | 0.00 | 0.00 | 0.155432E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.362090E+12 | 0.00 | 0.126848E+14 | 0.00 | 0.00 | 0.162884E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.278378E+11 | 0.00 | 0.847528E+12 | 0.00 | 0.00 | 0.109730E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.315054E+11 | 0.00 | 0.122872E+13 | 0.00 | 0.00 | 0.162488E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 49243576.71 | 0.732610E+10 | 0.00 | 0.00 | 0.360662E+11 | 0.00 | 0.00 | 0.00 | 1.13 |
February | 0.00 | 0.870640E+10 | 0.00 | 4409.57 | 0.307094E+11 | 0.00 | 2131397.65 | 0.00 | 1.12 |
March | 0.00 | 0.790048E+10 | 0.00 | 0.00 | 0.409963E+11 | 0.00 | 0.00 | 0.00 | 1.12 |
April | 0.00 | 0.127014E+11 | 0.00 | 0.00 | 0.500851E+11 | 0.00 | 0.00 | 0.00 | 1.13 |
May | 0.00 | 0.246114E+11 | 0.00 | 0.00 | 0.530541E+11 | 0.00 | 0.00 | 0.00 | 1.14 |
June | 0.00 | 0.365176E+11 | 0.00 | 0.00 | 0.384550E+11 | 0.00 | 0.00 | 0.00 | 1.13 |
July | 0.00 | 0.223371E+11 | 0.00 | 0.00 | 0.349945E+11 | 0.00 | 0.00 | 0.00 | 1.16 |
August | 0.00 | 0.218274E+11 | 0.00 | 0.00 | 0.517823E+11 | 0.00 | 0.00 | 0.00 | 1.16 |
September | 0.00 | 0.198979E+11 | 0.00 | 0.00 | 0.478029E+11 | 0.00 | 0.00 | 0.00 | 1.15 |
October | 0.00 | 0.945539E+10 | 0.00 | 0.00 | 0.560368E+11 | 0.00 | 0.00 | 0.00 | 1.16 |
November | 0.00 | 0.116524E+11 | 0.00 | 0.00 | 0.441026E+11 | 0.00 | 0.00 | 0.00 | 1.14 |
December | 8884304.10 | 0.109474E+11 | 0.00 | 0.00 | 0.406115E+11 | 0.00 | 0.00 | 0.00 | 1.14 |
Annual Sum or Average | 58127880.81 | 0.193881E+12 | 0.00 | 4409.57 | 0.524697E+12 | 0.00 | 2131397.65 | 0.00 | 1.14 |
Minimum of Months | 0.00 | 0.732610E+10 | 0.00 | 0.00 | 0.307094E+11 | 0.00 | 0.00 | 0.00 | 1.12 |
Maximum of Months | 49243576.71 | 0.365176E+11 | 0.00 | 4409.57 | 0.560368E+11 | 0.00 | 2131397.65 | 0.00 | 1.16 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 5048252.54 | 0.411688E+10 | 0.00 | 0.00 | 0.919090E+09 | 0.00 | 0.00 | 0.00 | 2.36 |
February | 0.00 | 0.422371E+10 | 0.00 | 4398.43 | 0.436546E+09 | 0.00 | 214555.89 | 0.00 | 2.36 |
March | 0.00 | 0.482940E+10 | 0.00 | 0.00 | 0.660500E+09 | 0.00 | 0.00 | 0.00 | 2.27 |
April | 0.00 | 0.582173E+10 | 0.00 | 0.00 | 0.991794E+09 | 0.00 | 0.00 | 0.00 | 2.23 |
May | 0.00 | 0.663239E+10 | 0.00 | 0.00 | 0.171015E+10 | 0.00 | 0.00 | 0.00 | 2.22 |
June | 0.00 | 0.690256E+10 | 0.00 | 0.00 | 0.124738E+10 | 0.00 | 0.00 | 0.00 | 2.22 |
July | 0.00 | 0.434212E+10 | 0.00 | 0.00 | 0.162282E+10 | 0.00 | 0.00 | 0.00 | 2.20 |
August | 0.00 | 0.495631E+10 | 0.00 | 0.00 | 0.275435E+10 | 0.00 | 0.00 | 0.00 | 2.21 |
September | 0.00 | 0.528139E+10 | 0.00 | 0.00 | 0.189159E+10 | 0.00 | 0.00 | 0.00 | 2.21 |
October | 0.00 | 0.486051E+10 | 0.00 | 0.00 | 0.207688E+10 | 0.00 | 0.00 | 0.00 | 2.22 |
November | 0.00 | 0.497793E+10 | 0.00 | 0.00 | 0.122195E+10 | 0.00 | 0.00 | 0.00 | 2.28 |
December | 910782.96 | 0.463580E+10 | 0.00 | 0.00 | 0.122664E+10 | 0.00 | 0.00 | 0.00 | 2.35 |
Annual Sum or Average | 5959035.50 | 0.615807E+11 | 0.00 | 4398.43 | 0.167597E+11 | 0.00 | 214555.89 | 0.00 | 2.26 |
Minimum of Months | 0.00 | 0.411688E+10 | 0.00 | 0.00 | 0.436546E+09 | 0.00 | 0.00 | 0.00 | 2.20 |
Maximum of Months | 5048252.54 | 0.690256E+10 | 0.00 | 4398.43 | 0.275435E+10 | 0.00 | 214555.89 | 0.00 | 2.36 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 4453487.38 | 0.157680E+10 | 0.00 | 150.93 | 0.247283E+10 | 0.00 | 133344.02 | 0.00 | 1.65 |
February | 0.00 | 0.182404E+10 | 0.00 | 3159.30 | 0.187005E+10 | 0.00 | 195788.68 | 0.00 | 1.64 |
March | 0.00 | 0.248823E+10 | 0.00 | 0.00 | 0.211934E+10 | 0.00 | 0.00 | 0.00 | 1.66 |
April | 0.00 | 0.328816E+10 | 0.00 | 0.00 | 0.264878E+10 | 0.00 | 0.00 | 0.00 | 1.68 |
May | 0.00 | 0.386311E+10 | 0.00 | 0.00 | 0.344732E+10 | 0.00 | 0.00 | 0.00 | 1.68 |
June | 0.00 | 0.456356E+10 | 0.00 | 0.00 | 0.256525E+10 | 0.00 | 0.00 | 0.00 | 1.68 |
July | 0.00 | 0.228169E+10 | 0.00 | 0.00 | 0.307730E+10 | 0.00 | 0.00 | 0.00 | 1.71 |
August | 0.00 | 0.269952E+10 | 0.00 | 0.00 | 0.419789E+10 | 0.00 | 0.00 | 0.00 | 1.71 |
September | 0.00 | 0.255464E+10 | 0.00 | 0.00 | 0.378540E+10 | 0.00 | 0.00 | 0.00 | 1.69 |
October | 0.00 | 0.196997E+10 | 0.00 | 0.00 | 0.413777E+10 | 0.00 | 0.00 | 0.00 | 1.69 |
November | 0.00 | 0.186538E+10 | 0.00 | 0.00 | 0.333663E+10 | 0.00 | 0.00 | 0.00 | 1.67 |
December | 827562.67 | 0.179098E+10 | 0.00 | 0.00 | 0.301623E+10 | 0.00 | 0.00 | 0.00 | 1.66 |
Annual Sum or Average | 5281050.05 | 0.307661E+11 | 0.00 | 3310.23 | 0.366748E+11 | 0.00 | 329132.70 | 0.00 | 1.68 |
Minimum of Months | 0.00 | 0.157680E+10 | 0.00 | 0.00 | 0.187005E+10 | 0.00 | 0.00 | 0.00 | 1.64 |
Maximum of Months | 4453487.38 | 0.456356E+10 | 0.00 | 3159.30 | 0.419789E+10 | 0.00 | 195788.68 | 0.00 | 1.71 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 4687250.79 | 0.212450E+09 | 0.00 | 0.00 | 0.391785E+10 | 0.00 | 0.00 | 0.00 | 0.79 |
February | 203296.85 | 0.547112E+09 | 0.00 | 0.00 | 0.320468E+10 | 0.00 | 0.00 | 0.00 | 0.79 |
March | 0.00 | 0.972215E+09 | 0.00 | 0.00 | 0.368417E+10 | 0.00 | 0.00 | 0.00 | 0.79 |
April | 0.00 | 0.263177E+10 | 0.00 | 0.00 | 0.341334E+10 | 0.00 | 0.00 | 0.00 | 0.81 |
May | 0.00 | 0.520290E+10 | 0.00 | 0.00 | 0.256533E+10 | 0.00 | 0.00 | 0.00 | 0.84 |
June | 0.00 | 0.684041E+10 | 0.00 | 0.00 | 0.121088E+10 | 0.00 | 0.00 | 0.00 | 0.90 |
July | 0.00 | 0.334689E+10 | 0.00 | 0.00 | 0.225893E+10 | 0.00 | 0.00 | 0.00 | 0.84 |
August | 0.00 | 0.266164E+10 | 0.00 | 0.00 | 0.443551E+10 | 0.00 | 0.00 | 0.00 | 0.83 |
September | 0.00 | 0.148336E+10 | 0.00 | 0.00 | 0.497113E+10 | 0.00 | 0.00 | 0.00 | 0.81 |
October | 0.00 | 0.447023E+09 | 0.00 | 0.00 | 0.578685E+10 | 0.00 | 0.00 | 0.00 | 0.82 |
November | 0.00 | 0.426515E+09 | 0.00 | 0.00 | 0.488052E+10 | 0.00 | 0.00 | 0.00 | 0.80 |
December | 845652.65 | 0.241248E+09 | 0.00 | 0.00 | 0.466639E+10 | 0.00 | 0.00 | 0.00 | 0.80 |
Annual Sum or Average | 5736200.29 | 0.250135E+11 | 0.00 | 0.00 | 0.449956E+11 | 0.00 | 0.00 | 0.00 | 0.82 |
Minimum of Months | 0.00 | 0.212450E+09 | 0.00 | 0.00 | 0.121088E+10 | 0.00 | 0.00 | 0.00 | 0.79 |
Maximum of Months | 4687250.79 | 0.684041E+10 | 0.00 | 0.00 | 0.578685E+10 | 0.00 | 0.00 | 0.00 | 0.90 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 2583346.35 | 4620195.70 | 0.00 | 0.00 | 0.227177E+10 | 0.00 | 0.00 | 0.00 | 0.76 |
February | 112045.67 | 79252217.50 | 0.00 | 0.00 | 0.198852E+10 | 0.00 | 0.00 | 0.00 | 0.75 |
March | 0.00 | 0.290008E+09 | 0.00 | 0.00 | 0.227514E+10 | 0.00 | 0.00 | 0.00 | 0.76 |
April | 0.00 | 0.103521E+10 | 0.00 | 0.00 | 0.226545E+10 | 0.00 | 0.00 | 0.00 | 0.77 |
May | 0.00 | 0.252602E+10 | 0.00 | 0.00 | 0.164820E+10 | 0.00 | 0.00 | 0.00 | 0.79 |
June | 0.00 | 0.348591E+10 | 0.00 | 0.00 | 0.809197E+09 | 0.00 | 0.00 | 0.00 | 0.83 |
July | 0.00 | 0.148188E+10 | 0.00 | 0.00 | 0.154446E+10 | 0.00 | 0.00 | 0.00 | 0.79 |
August | 0.00 | 0.109270E+10 | 0.00 | 0.00 | 0.277837E+10 | 0.00 | 0.00 | 0.00 | 0.79 |
September | 0.00 | 0.481526E+09 | 0.00 | 0.00 | 0.307009E+10 | 0.00 | 0.00 | 0.00 | 0.78 |
October | 0.00 | 74624877.19 | 0.00 | 0.00 | 0.336113E+10 | 0.00 | 0.00 | 0.00 | 0.78 |
November | 0.00 | 25569664.04 | 0.00 | 0.00 | 0.289937E+10 | 0.00 | 0.00 | 0.00 | 0.77 |
December | 466075.70 | 3691673.16 | 0.00 | 0.00 | 0.270112E+10 | 0.00 | 0.00 | 0.00 | 0.77 |
Annual Sum or Average | 3161467.72 | 0.105810E+11 | 0.00 | 0.00 | 0.276128E+11 | 0.00 | 0.00 | 0.00 | 0.78 |
Minimum of Months | 0.00 | 3691673.16 | 0.00 | 0.00 | 0.809197E+09 | 0.00 | 0.00 | 0.00 | 0.75 |
Maximum of Months | 2583346.35 | 0.348591E+10 | 0.00 | 0.00 | 0.336113E+10 | 0.00 | 0.00 | 0.00 | 0.83 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 422553.95 | 0.483570E+11 | 0.00 | 488065.77 | 0.890941E+09 | 0.00 | 52226240.90 | 0.00 | 19.86 |
February | 0.00 | 0.441001E+11 | 0.00 | 31770.23 | 0.765657E+09 | 0.00 | 2272897.68 | 0.00 | 19.70 |
March | 0.00 | 0.548995E+11 | 0.00 | 0.00 | 0.982871E+09 | 0.00 | 0.00 | 0.00 | 19.91 |
April | 0.00 | 0.708785E+11 | 0.00 | 0.00 | 0.115690E+10 | 0.00 | 0.00 | 0.00 | 20.15 |
May | 0.00 | 0.876351E+11 | 0.00 | 0.00 | 0.135128E+10 | 0.00 | 0.00 | 0.00 | 20.23 |
June | 0.00 | 0.846606E+11 | 0.00 | 0.00 | 0.126893E+10 | 0.00 | 0.00 | 0.00 | 20.08 |
July | 0.00 | 0.645538E+11 | 0.00 | 0.00 | 0.107974E+10 | 0.00 | 0.00 | 0.00 | 20.68 |
August | 0.00 | 0.826291E+11 | 0.00 | 0.00 | 0.147157E+10 | 0.00 | 0.00 | 0.00 | 20.66 |
September | 0.00 | 0.759993E+11 | 0.00 | 0.00 | 0.134070E+10 | 0.00 | 0.00 | 0.00 | 20.40 |
October | 0.00 | 0.731226E+11 | 0.00 | 0.00 | 0.135629E+10 | 0.00 | 0.00 | 0.00 | 20.46 |
November | 0.00 | 0.625833E+11 | 0.00 | 0.00 | 0.104828E+10 | 0.00 | 0.00 | 0.00 | 20.14 |
December | 0.00 | 0.573467E+11 | 0.00 | 204098.65 | 0.987546E+09 | 0.00 | 9382614.17 | 0.00 | 20.06 |
Annual Sum or Average | 422553.95 | 0.806766E+12 | 0.00 | 723934.64 | 0.137007E+11 | 0.00 | 63881752.75 | 0.00 | 20.20 |
Minimum of Months | 0.00 | 0.441001E+11 | 0.00 | 0.00 | 0.765657E+09 | 0.00 | 0.00 | 0.00 | 19.70 |
Maximum of Months | 422553.95 | 0.876351E+11 | 0.00 | 488065.77 | 0.147157E+10 | 0.00 | 52226240.90 | 0.00 | 20.68 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.188911E+11 | 0.00 | 330439.33 | 0.103171E+10 | 0.00 | 20905404.44 | 0.00 | 3.35 |
February | 0.00 | 0.174961E+11 | 0.00 | 31110.62 | 0.568172E+09 | 0.00 | 1000014.30 | 0.00 | 3.31 |
March | 0.00 | 0.203123E+11 | 0.00 | 0.00 | 0.170462E+10 | 0.00 | 0.00 | 0.00 | 3.27 |
April | 0.00 | 0.252961E+11 | 0.00 | 0.00 | 0.272905E+10 | 0.00 | 0.00 | 0.00 | 3.28 |
May | 0.00 | 0.300979E+11 | 0.00 | 0.00 | 0.451750E+10 | 0.00 | 0.00 | 0.00 | 3.28 |
June | 0.00 | 0.299763E+11 | 0.00 | 0.00 | 0.358104E+10 | 0.00 | 0.00 | 0.00 | 3.27 |
July | 0.00 | 0.209411E+11 | 0.00 | 0.00 | 0.422402E+10 | 0.00 | 0.00 | 0.00 | 3.31 |
August | 0.00 | 0.254175E+11 | 0.00 | 0.00 | 0.691641E+10 | 0.00 | 0.00 | 0.00 | 3.31 |
September | 0.00 | 0.255510E+11 | 0.00 | 0.00 | 0.437700E+10 | 0.00 | 0.00 | 0.00 | 3.29 |
October | 0.00 | 0.245797E+11 | 0.00 | 0.00 | 0.429425E+10 | 0.00 | 0.00 | 0.00 | 3.30 |
November | 0.00 | 0.232800E+11 | 0.00 | 0.00 | 0.174540E+10 | 0.00 | 0.00 | 0.00 | 3.31 |
December | 308581.00 | 0.224200E+11 | 0.00 | 85291.94 | 0.105620E+10 | 0.00 | 3437402.26 | 0.00 | 3.36 |
Annual Sum or Average | 308581.00 | 0.284259E+12 | 0.00 | 446841.88 | 0.367454E+11 | 0.00 | 25342821.00 | 0.00 | 3.30 |
Minimum of Months | 0.00 | 0.174961E+11 | 0.00 | 0.00 | 0.568172E+09 | 0.00 | 0.00 | 0.00 | 3.27 |
Maximum of Months | 308581.00 | 0.300979E+11 | 0.00 | 330439.33 | 0.691641E+10 | 0.00 | 20905404.44 | 0.00 | 3.36 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 16558451.86 | 0.453739E+11 | 0.00 | 569356.34 | 0.245025E+11 | 0.00 | 61528589.27 | 0.00 | 1.69 |
February | 0.00 | 0.440405E+11 | 0.00 | 98089.28 | 0.197286E+11 | 0.00 | 3313419.66 | 0.00 | 1.68 |
March | 0.00 | 0.492841E+11 | 0.00 | 0.00 | 0.298501E+11 | 0.00 | 0.00 | 0.00 | 1.69 |
April | 0.00 | 0.647322E+11 | 0.00 | 0.00 | 0.371146E+11 | 0.00 | 0.00 | 0.00 | 1.72 |
May | 0.00 | 0.909037E+11 | 0.00 | 0.00 | 0.360376E+11 | 0.00 | 0.00 | 0.00 | 1.74 |
June | 0.00 | 0.971682E+11 | 0.00 | 0.00 | 0.272544E+11 | 0.00 | 0.00 | 0.00 | 1.75 |
July | 0.00 | 0.573000E+11 | 0.00 | 0.00 | 0.355804E+11 | 0.00 | 0.00 | 0.00 | 1.76 |
August | 0.00 | 0.650987E+11 | 0.00 | 0.00 | 0.537089E+11 | 0.00 | 0.00 | 0.00 | 1.75 |
September | 0.00 | 0.610969E+11 | 0.00 | 0.00 | 0.479956E+11 | 0.00 | 0.00 | 0.00 | 1.73 |
October | 0.00 | 0.550475E+11 | 0.00 | 0.00 | 0.499874E+11 | 0.00 | 0.00 | 0.00 | 1.73 |
November | 0.00 | 0.554187E+11 | 0.00 | 0.00 | 0.342463E+11 | 0.00 | 0.00 | 0.00 | 1.71 |
December | 4157375.42 | 0.555165E+11 | 0.00 | 134472.28 | 0.273496E+11 | 0.00 | 9898984.92 | 0.00 | 1.71 |
Annual Sum or Average | 20715827.28 | 0.740981E+12 | 0.00 | 801917.90 | 0.423356E+12 | 0.00 | 74740993.84 | 0.00 | 1.72 |
Minimum of Months | 0.00 | 0.440405E+11 | 0.00 | 0.00 | 0.197286E+11 | 0.00 | 0.00 | 0.00 | 1.68 |
Maximum of Months | 16558451.86 | 0.971682E+11 | 0.00 | 569356.34 | 0.537089E+11 | 0.00 | 61528589.27 | 0.00 | 1.76 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.126128E+10 | 843438.29 | 65398.44 | 0.00 | 18260.21 | 346144.25 | 12562.80 | 0.36 |
February | 0.00 | 0.118558E+10 | 1030415.11 | 0.00 | 0.00 | 0.00 | 0.00 | 13421.13 | 0.36 |
March | 0.00 | 0.149977E+10 | 2017660.61 | 0.00 | 0.00 | 0.00 | 0.00 | 33296.17 | 0.36 |
April | 0.00 | 0.186476E+10 | 2459856.03 | 0.00 | 0.00 | 0.00 | 0.00 | 23958.34 | 0.36 |
May | 0.00 | 0.225487E+10 | 2182884.81 | 0.00 | 0.00 | 0.00 | 0.00 | 23103.89 | 0.36 |
June | 0.00 | 0.215352E+10 | 1471329.64 | 0.00 | 0.00 | 0.00 | 0.00 | 21532.91 | 0.36 |
July | 0.00 | 0.167636E+10 | 2509637.64 | 0.00 | 0.00 | 0.00 | 0.00 | 47815.46 | 0.36 |
August | 0.00 | 0.204650E+10 | 3241133.28 | 0.00 | 904622.71 | 0.00 | 0.00 | 35636.41 | 0.36 |
September | 0.00 | 0.190772E+10 | 3004549.70 | 0.00 | 0.00 | 0.00 | 0.00 | 38832.33 | 0.36 |
October | 0.00 | 0.184867E+10 | 2258988.86 | 0.00 | 0.00 | 0.00 | 0.00 | 27444.14 | 0.36 |
November | 0.00 | 0.158552E+10 | 1810303.24 | 0.00 | 0.00 | 0.00 | 0.00 | 21999.37 | 0.36 |
December | 0.00 | 0.138518E+10 | 777862.69 | 10679.70 | 0.00 | 1044.72 | 0.00 | 15195.92 | 0.36 |
Annual Sum or Average | 0.00 | 0.206697E+11 | 23608059.91 | 76078.14 | 904622.71 | 19304.93 | 346144.25 | 314798.86 | 0.36 |
Minimum of Months | 0.00 | 0.118558E+10 | 777862.69 | 0.00 | 0.00 | 0.00 | 0.00 | 12562.80 | 0.36 |
Maximum of Months | 0.00 | 0.225487E+10 | 3241133.28 | 65398.44 | 904622.71 | 18260.21 | 346144.25 | 47815.46 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 426520.90 | 0.116561E+10 | 768188.99 | 3231.64 | 95586577.87 | 0.00 | 0.00 | 21548.62 | 0.36 |
February | 0.00 | 0.111266E+10 | 722362.20 | 0.00 | 73079498.65 | 0.00 | 0.00 | 20255.66 | 0.36 |
March | 0.00 | 0.148813E+10 | 2029587.10 | 0.00 | 11432967.02 | 0.00 | 0.00 | 48695.35 | 0.36 |
April | 0.00 | 0.186092E+10 | 2644746.99 | 0.00 | 3430034.83 | 0.00 | 0.00 | 28612.19 | 0.36 |
May | 0.00 | 0.224437E+10 | 1854957.79 | 0.00 | 10558671.44 | 0.00 | 0.00 | 19873.40 | 0.36 |
June | 0.00 | 0.213281E+10 | 997851.86 | 0.00 | 20942985.88 | 0.00 | 0.00 | 10593.73 | 0.36 |
July | 0.00 | 0.165352E+10 | 1840254.78 | 0.00 | 23329934.69 | 0.00 | 0.00 | 36998.59 | 0.36 |
August | 0.00 | 0.203519E+10 | 3239590.03 | 0.00 | 11984925.29 | 0.00 | 0.00 | 33531.95 | 0.36 |
September | 0.00 | 0.188844E+10 | 3309507.19 | 0.00 | 18742841.01 | 0.00 | 0.00 | 52629.54 | 0.36 |
October | 0.00 | 0.182114E+10 | 2746914.26 | 0.00 | 26810741.19 | 0.00 | 0.00 | 43783.58 | 0.36 |
November | 0.00 | 0.151221E+10 | 2610300.58 | 0.00 | 72299833.67 | 0.00 | 0.00 | 50454.40 | 0.36 |
December | 0.00 | 0.127360E+10 | 1060114.88 | 11723.05 | 0.111135E+09 | 0.00 | 0.00 | 18811.80 | 0.36 |
Annual Sum or Average | 426520.90 | 0.201886E+11 | 23824376.66 | 14954.69 | 0.479334E+09 | 0.00 | 0.00 | 385788.81 | 0.36 |
Minimum of Months | 0.00 | 0.111266E+10 | 722362.20 | 0.00 | 3430034.83 | 0.00 | 0.00 | 10593.73 | 0.36 |
Maximum of Months | 426520.90 | 0.224437E+10 | 3309507.19 | 11723.05 | 0.111135E+09 | 0.00 | 0.00 | 52629.54 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.928380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
February | 0.00 | 0.987619E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
March | 0.00 | 0.112202E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
April | 0.00 | 0.131139E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
May | 0.00 | 0.165328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
June | 0.00 | 0.158224E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
July | 0.00 | 0.134696E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
August | 0.00 | 0.177738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
September | 0.00 | 0.156447E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
October | 0.00 | 0.159193E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
November | 0.00 | 0.136354E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
December | 0.00 | 0.106398E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
Annual Sum or Average | 0.00 | 0.162932E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
Minimum of Months | 0.00 | 0.928380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
Maximum of Months | 0.00 | 0.177738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 5785500.15 | 0.151535E+11 | 17764593.12 | 43835.22 | 0.194670E+10 | 0.00 | 0.00 | 135251.96 | 0.41 |
February | 0.00 | 0.146267E+11 | 13453338.17 | 0.00 | 0.145369E+10 | 0.00 | 0.00 | 80439.18 | 0.41 |
March | 0.00 | 0.195283E+11 | 37322484.25 | 0.00 | 0.803129E+09 | 0.00 | 0.00 | 170489.42 | 0.41 |
April | 0.00 | 0.248071E+11 | 32616333.07 | 0.00 | 0.485288E+09 | 0.00 | 0.00 | 121136.63 | 0.41 |
May | 0.00 | 0.302891E+11 | 15742404.90 | 0.00 | 0.307401E+09 | 0.00 | 0.00 | 27168.57 | 0.41 |
June | 0.00 | 0.288835E+11 | 16550204.90 | 0.00 | 0.328032E+09 | 0.00 | 0.00 | 35300.21 | 0.41 |
July | 0.00 | 0.223437E+11 | 10064697.15 | 0.00 | 0.417060E+09 | 0.00 | 0.00 | 48349.09 | 0.41 |
August | 0.00 | 0.269802E+11 | 31866731.18 | 0.00 | 0.800938E+09 | 0.00 | 0.00 | 89649.98 | 0.41 |
September | 0.00 | 0.247739E+11 | 35839020.04 | 0.00 | 0.110551E+10 | 0.00 | 0.00 | 134143.49 | 0.41 |
October | 0.00 | 0.236197E+11 | 22162265.42 | 0.00 | 0.146225E+10 | 0.00 | 0.00 | 68421.20 | 0.41 |
November | 0.00 | 0.196226E+11 | 32619506.71 | 0.00 | 0.187366E+10 | 0.00 | 0.00 | 128682.74 | 0.41 |
December | 0.00 | 0.165420E+11 | 24936455.79 | 159016.14 | 0.223063E+10 | 0.00 | 0.00 | 177707.13 | 0.41 |
Annual Sum or Average | 5785500.15 | 0.267170E+12 | 0.290938E+09 | 202851.37 | 0.132143E+11 | 0.00 | 0.00 | 1216739.60 | 0.41 |
Minimum of Months | 0.00 | 0.146267E+11 | 10064697.15 | 0.00 | 0.307401E+09 | 0.00 | 0.00 | 27168.57 | 0.41 |
Maximum of Months | 5785500.15 | 0.302891E+11 | 37322484.25 | 159016.14 | 0.223063E+10 | 0.00 | 0.00 | 177707.13 | 0.41 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.126206E+10 | 71543.28 | 93442.01 | 0.00 | 0.00 | 336360.89 | 284.53 | 0.36 |
February | 0.00 | 0.118662E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
March | 0.00 | 0.150182E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
April | 0.00 | 0.186724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
May | 0.00 | 0.225707E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
June | 0.00 | 0.215502E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
July | 0.00 | 0.167892E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
August | 0.00 | 0.205037E+10 | 130170.60 | 0.00 | 181793.91 | 0.00 | 0.00 | 125.59 | 0.36 |
September | 0.00 | 0.191072E+10 | 45850.56 | 0.00 | 0.00 | 0.00 | 0.00 | 531.17 | 0.36 |
October | 0.00 | 0.185083E+10 | 132314.92 | 0.00 | 0.00 | 0.00 | 0.00 | 2103.29 | 0.36 |
November | 0.00 | 0.158733E+10 | 30741.63 | 0.00 | 0.00 | 0.00 | 0.00 | 25.82 | 0.36 |
December | 0.00 | 0.138595E+10 | 24612.94 | 11724.42 | 0.00 | 0.00 | 0.00 | 9.18 | 0.36 |
Annual Sum or Average | 0.00 | 0.206940E+11 | 435233.92 | 105166.43 | 181793.91 | 0.00 | 336360.89 | 3079.58 | 0.36 |
Minimum of Months | 0.00 | 0.118662E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
Maximum of Months | 0.00 | 0.225707E+10 | 132314.92 | 93442.01 | 181793.91 | 0.00 | 336360.89 | 2103.29 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 426520.90 | 0.116605E+10 | 342989.07 | 3231.64 | 95586577.87 | 0.00 | 0.00 | 2028.59 | 0.36 |
February | 0.00 | 0.111335E+10 | 68360.45 | 0.00 | 73065308.00 | 0.00 | 0.00 | 18.14 | 0.36 |
March | 0.00 | 0.149021E+10 | 0.00 | 0.00 | 11432967.02 | 0.00 | 0.00 | 0.00 | 0.36 |
April | 0.00 | 0.186360E+10 | 0.00 | 0.00 | 3430034.83 | 0.00 | 0.00 | 0.00 | 0.36 |
May | 0.00 | 0.224618E+10 | 69319.18 | 0.00 | 10558671.44 | 0.00 | 0.00 | 113.96 | 0.36 |
June | 0.00 | 0.213382E+10 | 0.00 | 0.00 | 20942985.88 | 0.00 | 0.00 | 0.00 | 0.36 |
July | 0.00 | 0.165533E+10 | 65973.67 | 0.00 | 23329934.69 | 0.00 | 0.00 | 777.22 | 0.36 |
August | 0.00 | 0.203840E+10 | 59437.48 | 0.00 | 11984925.29 | 0.00 | 0.00 | 657.46 | 0.36 |
September | 0.00 | 0.189169E+10 | 105038.69 | 0.00 | 18742841.01 | 0.00 | 0.00 | 2011.05 | 0.36 |
October | 0.00 | 0.182368E+10 | 247552.64 | 0.00 | 26810741.19 | 0.00 | 0.00 | 2963.03 | 0.36 |
November | 0.00 | 0.151484E+10 | 35896.67 | 0.00 | 72299833.67 | 0.00 | 0.00 | 165.25 | 0.36 |
December | 0.00 | 0.127454E+10 | 134565.07 | 11723.05 | 0.111135E+09 | 0.00 | 0.00 | 1100.98 | 0.36 |
Annual Sum or Average | 426520.90 | 0.202117E+11 | 1129132.92 | 14954.69 | 0.479320E+09 | 0.00 | 0.00 | 9835.70 | 0.36 |
Minimum of Months | 0.00 | 0.111335E+10 | 0.00 | 0.00 | 3430034.83 | 0.00 | 0.00 | 0.00 | 0.36 |
Maximum of Months | 426520.90 | 0.224618E+10 | 342989.07 | 11723.05 | 0.111135E+09 | 0.00 | 0.00 | 2963.03 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 25424642.36 | 0.00 | 0.00 | 0.00 | 0.224036E+11 | 0.00 | 0.00 | 0.00 | 0.59 |
February | 1102725.24 | 0.292078E+09 | 0.00 | 0.00 | 0.200584E+11 | 0.00 | 0.00 | 0.00 | 0.59 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.252456E+11 | 0.00 | 0.00 | 0.00 | 0.59 |
April | 0.00 | 12645797.32 | 0.00 | 0.00 | 0.324043E+11 | 0.00 | 0.00 | 0.00 | 0.60 |
May | 0.00 | 0.384310E+10 | 0.00 | 0.00 | 0.362559E+11 | 0.00 | 0.00 | 0.00 | 0.60 |
June | 0.00 | 0.123317E+11 | 0.00 | 0.00 | 0.264534E+11 | 0.00 | 0.00 | 0.00 | 0.59 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.296005E+11 | 0.00 | 0.00 | 0.00 | 0.61 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.380050E+11 | 0.00 | 0.00 | 0.00 | 0.61 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.349541E+11 | 0.00 | 0.00 | 0.00 | 0.60 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.338139E+11 | 0.00 | 0.00 | 0.00 | 0.61 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.287865E+11 | 0.00 | 0.00 | 0.00 | 0.60 |
December | 4586999.35 | 0.156067E+09 | 0.00 | 0.00 | 0.264640E+11 | 0.00 | 0.00 | 0.00 | 0.60 |
Annual Sum or Average | 31114366.95 | 0.166356E+11 | 0.00 | 0.00 | 0.354445E+12 | 0.00 | 0.00 | 0.00 | 0.60 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.200584E+11 | 0.00 | 0.00 | 0.00 | 0.59 |
Maximum of Months | 25424642.36 | 0.123317E+11 | 0.00 | 0.00 | 0.380050E+11 | 0.00 | 0.00 | 0.00 | 0.61 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.315219E+09 | 307849.87 | 16327.68 | 0.00 | 4565.05 | 86557.99 | 6216.38 | 0.36 |
February | 0.00 | 0.296361E+09 | 287736.87 | 0.00 | 0.00 | 0.00 | 0.00 | 6371.54 | 0.36 |
March | 0.00 | 0.374911E+09 | 533350.30 | 0.00 | 0.00 | 0.00 | 0.00 | 10585.86 | 0.36 |
April | 0.00 | 0.466091E+09 | 710711.15 | 0.00 | 0.00 | 0.00 | 0.00 | 9434.51 | 0.36 |
May | 0.00 | 0.563568E+09 | 691808.17 | 0.00 | 0.00 | 0.00 | 0.00 | 8845.05 | 0.36 |
June | 0.00 | 0.538039E+09 | 706737.15 | 0.00 | 0.00 | 0.00 | 0.00 | 8440.47 | 0.36 |
July | 0.00 | 0.419086E+09 | 628423.88 | 0.00 | 0.00 | 0.00 | 0.00 | 15855.92 | 0.36 |
August | 0.00 | 0.511727E+09 | 931211.47 | 0.00 | 0.00 | 0.00 | 0.00 | 13374.82 | 0.36 |
September | 0.00 | 0.476826E+09 | 854460.62 | 0.00 | 0.00 | 0.00 | 0.00 | 11952.26 | 0.36 |
October | 0.00 | 0.462049E+09 | 680039.72 | 0.00 | 0.00 | 0.00 | 0.00 | 10790.73 | 0.36 |
November | 0.00 | 0.396289E+09 | 543491.32 | 0.00 | 0.00 | 0.00 | 0.00 | 6574.65 | 0.36 |
December | 0.00 | 0.346232E+09 | 256070.16 | 2669.93 | 0.00 | 261.18 | 0.00 | 5461.92 | 0.36 |
Annual Sum or Average | 0.00 | 0.516640E+10 | 7131890.67 | 18997.61 | 0.00 | 4826.23 | 86557.99 | 113904.12 | 0.36 |
Minimum of Months | 0.00 | 0.296361E+09 | 256070.16 | 0.00 | 0.00 | 0.00 | 0.00 | 5461.92 | 0.36 |
Maximum of Months | 0.00 | 0.563568E+09 | 931211.47 | 16327.68 | 0.00 | 4565.05 | 86557.99 | 15855.92 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 106630.23 | 0.291371E+09 | 221651.48 | 807.91 | 23896644.47 | 0.00 | 0.00 | 7079.25 | 0.36 |
February | 0.00 | 0.278144E+09 | 201520.42 | 0.00 | 18269874.66 | 0.00 | 0.00 | 4941.81 | 0.36 |
March | 0.00 | 0.372017E+09 | 524247.77 | 0.00 | 2858241.75 | 0.00 | 0.00 | 11709.50 | 0.36 |
April | 0.00 | 0.465205E+09 | 685042.08 | 0.00 | 857508.71 | 0.00 | 0.00 | 9086.09 | 0.36 |
May | 0.00 | 0.560968E+09 | 587112.96 | 0.00 | 2639667.86 | 0.00 | 0.00 | 7680.05 | 0.36 |
June | 0.00 | 0.533087E+09 | 363794.68 | 0.00 | 5235746.47 | 0.00 | 0.00 | 3797.50 | 0.36 |
July | 0.00 | 0.413259E+09 | 577596.95 | 0.00 | 5832483.67 | 0.00 | 0.00 | 12114.78 | 0.36 |
August | 0.00 | 0.508671E+09 | 931942.53 | 0.00 | 2996231.32 | 0.00 | 0.00 | 12533.09 | 0.36 |
September | 0.00 | 0.472077E+09 | 860382.95 | 0.00 | 4685710.25 | 0.00 | 0.00 | 13440.23 | 0.36 |
October | 0.00 | 0.455184E+09 | 784759.41 | 0.00 | 6702685.30 | 0.00 | 0.00 | 14740.47 | 0.36 |
November | 0.00 | 0.378014E+09 | 691558.77 | 0.00 | 18074958.42 | 0.00 | 0.00 | 12425.44 | 0.36 |
December | 0.00 | 0.318345E+09 | 318201.25 | 2930.76 | 27783756.66 | 0.00 | 0.00 | 6334.86 | 0.36 |
Annual Sum or Average | 106630.23 | 0.504634E+10 | 6747811.26 | 3738.67 | 0.119834E+09 | 0.00 | 0.00 | 115883.06 | 0.36 |
Minimum of Months | 0.00 | 0.278144E+09 | 201520.42 | 0.00 | 857508.71 | 0.00 | 0.00 | 3797.50 | 0.36 |
Maximum of Months | 106630.23 | 0.560968E+09 | 931942.53 | 2930.76 | 27783756.66 | 0.00 | 0.00 | 14740.47 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.202698E+10 | 159039.58 | 124195.91 | 0.00 | 26875.30 | 539244.82 | 1669.96 | 0.41 |
February | 0.00 | 0.190586E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
March | 0.00 | 0.241192E+10 | 185708.22 | 0.00 | 0.00 | 0.00 | 0.00 | 824.52 | 0.41 |
April | 0.00 | 0.299877E+10 | 249404.05 | 0.00 | 0.00 | 0.00 | 0.00 | 238.66 | 0.41 |
May | 0.00 | 0.362423E+10 | 907513.53 | 0.00 | 0.00 | 0.00 | 0.00 | 445.89 | 0.41 |
June | 0.00 | 0.346080E+10 | 415847.95 | 0.00 | 0.00 | 0.00 | 0.00 | 585.49 | 0.41 |
July | 0.00 | 0.269588E+10 | 673740.65 | 0.00 | 0.00 | 0.00 | 0.00 | 968.58 | 0.41 |
August | 0.00 | 0.329146E+10 | 1896268.06 | 0.00 | 291983.26 | 0.00 | 0.00 | 2747.46 | 0.41 |
September | 0.00 | 0.306826E+10 | 669730.00 | 0.00 | 0.00 | 0.00 | 0.00 | 980.01 | 0.41 |
October | 0.00 | 0.297086E+10 | 2001882.89 | 0.00 | 0.00 | 0.00 | 0.00 | 4289.54 | 0.41 |
November | 0.00 | 0.254944E+10 | 48043.20 | 0.00 | 0.00 | 0.00 | 0.00 | 1373.08 | 0.41 |
December | 0.00 | 0.222589E+10 | 154148.16 | 18830.86 | 0.00 | 0.00 | 0.00 | 1655.06 | 0.41 |
Annual Sum or Average | 0.00 | 0.332303E+11 | 7361326.29 | 143026.77 | 291983.26 | 26875.30 | 539244.82 | 15778.26 | 0.41 |
Minimum of Months | 0.00 | 0.190586E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.00 | 0.362423E+10 | 2001882.89 | 124195.91 | 291983.26 | 26875.30 | 539244.82 | 4289.54 | 0.41 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.338678E+11 | 0.00 | 995539.43 | 0.776046E+09 | 0.00 | 36628967.10 | 0.00 | 4.33 |
February | 0.00 | 0.312289E+11 | 0.00 | 55612.10 | 0.513984E+09 | 0.00 | 1788631.60 | 0.00 | 4.33 |
March | 0.00 | 0.392990E+11 | 0.00 | 0.00 | 0.722593E+09 | 0.00 | 0.00 | 0.00 | 4.42 |
April | 0.00 | 0.515863E+11 | 0.00 | 0.00 | 0.533520E+09 | 0.00 | 0.00 | 0.00 | 4.53 |
May | 0.00 | 0.643753E+11 | 0.00 | 0.00 | 0.748453E+09 | 0.00 | 0.00 | 0.00 | 4.60 |
June | 0.00 | 0.633938E+11 | 0.00 | 0.00 | 0.331604E+09 | 0.00 | 0.00 | 0.00 | 4.63 |
July | 0.00 | 0.466088E+11 | 0.00 | 0.00 | 0.694084E+09 | 0.00 | 0.00 | 0.00 | 4.63 |
August | 0.00 | 0.587092E+11 | 0.00 | 0.00 | 0.124841E+10 | 0.00 | 0.00 | 0.00 | 4.57 |
September | 0.00 | 0.540529E+11 | 0.00 | 0.00 | 0.933016E+09 | 0.00 | 0.00 | 0.00 | 4.51 |
October | 0.00 | 0.511155E+11 | 0.00 | 0.00 | 0.130401E+10 | 0.00 | 0.00 | 0.00 | 4.47 |
November | 0.00 | 0.437066E+11 | 0.00 | 0.00 | 0.922718E+09 | 0.00 | 0.00 | 0.00 | 4.39 |
December | 0.00 | 0.402006E+11 | 0.00 | 328653.45 | 0.805666E+09 | 0.00 | 6332008.11 | 0.00 | 4.34 |
Annual Sum or Average | 0.00 | 0.578145E+12 | 0.00 | 1379804.98 | 0.953410E+10 | 0.00 | 44749606.80 | 0.00 | 4.48 |
Minimum of Months | 0.00 | 0.312289E+11 | 0.00 | 0.00 | 0.331604E+09 | 0.00 | 0.00 | 0.00 | 4.33 |
Maximum of Months | 0.00 | 0.643753E+11 | 0.00 | 995539.43 | 0.130401E+10 | 0.00 | 36628967.10 | 0.00 | 4.63 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.359469E+11 | 0.00 | 1050008.75 | 0.529657E+09 | 0.00 | 38484977.21 | 0.00 | 4.56 |
February | 0.00 | 0.330466E+11 | 0.00 | 58379.98 | 0.367850E+09 | 0.00 | 1877349.74 | 0.00 | 4.56 |
March | 0.00 | 0.417132E+11 | 0.00 | 0.00 | 0.422574E+09 | 0.00 | 0.00 | 0.00 | 4.65 |
April | 0.00 | 0.547190E+11 | 0.00 | 0.00 | 0.212718E+09 | 0.00 | 0.00 | 0.00 | 4.77 |
May | 0.00 | 0.682843E+11 | 0.00 | 0.00 | 0.405090E+09 | 0.00 | 0.00 | 0.00 | 4.84 |
June | 0.00 | 0.670824E+11 | 0.00 | 0.00 | 88346874.63 | 0.00 | 0.00 | 0.00 | 4.87 |
July | 0.00 | 0.496619E+11 | 0.00 | 0.00 | 0.302412E+09 | 0.00 | 0.00 | 0.00 | 4.89 |
August | 0.00 | 0.626434E+11 | 0.00 | 0.00 | 0.668877E+09 | 0.00 | 0.00 | 0.00 | 4.83 |
September | 0.00 | 0.575104E+11 | 0.00 | 0.00 | 0.517897E+09 | 0.00 | 0.00 | 0.00 | 4.76 |
October | 0.00 | 0.545160E+11 | 0.00 | 0.00 | 0.815924E+09 | 0.00 | 0.00 | 0.00 | 4.72 |
November | 0.00 | 0.465293E+11 | 0.00 | 0.00 | 0.531947E+09 | 0.00 | 0.00 | 0.00 | 4.63 |
December | 0.00 | 0.426510E+11 | 0.00 | 351412.14 | 0.544691E+09 | 0.00 | 6658890.34 | 0.00 | 4.58 |
Annual Sum or Average | 0.00 | 0.614304E+12 | 0.00 | 1459800.88 | 0.540798E+10 | 0.00 | 47021217.29 | 0.00 | 4.72 |
Minimum of Months | 0.00 | 0.330466E+11 | 0.00 | 0.00 | 88346874.63 | 0.00 | 0.00 | 0.00 | 4.56 |
Maximum of Months | 0.00 | 0.682843E+11 | 0.00 | 1050008.75 | 0.815924E+09 | 0.00 | 38484977.21 | 0.00 | 4.89 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.455952E+11 | 0.00 | 711776.64 | 0.00 | 0.00 | 36353884.40 | 0.00 | 17.93 |
February | 0.00 | 0.426670E+11 | 0.00 | 35480.06 | 0.00 | 0.00 | 1552806.29 | 0.00 | 17.97 |
March | 0.00 | 0.527418E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.11 |
April | 0.00 | 0.684147E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.45 |
May | 0.00 | 0.838314E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.40 |
June | 0.00 | 0.818926E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.39 |
July | 0.00 | 0.613478E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.59 |
August | 0.00 | 0.785899E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.48 |
September | 0.00 | 0.726544E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.39 |
October | 0.00 | 0.692637E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.26 |
November | 0.00 | 0.592556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.10 |
December | 0.00 | 0.532895E+11 | 0.00 | 236411.67 | 0.00 | 0.00 | 6402202.47 | 0.00 | 18.04 |
Annual Sum or Average | 0.00 | 0.769544E+12 | 0.00 | 983668.36 | 0.00 | 0.00 | 44308893.16 | 0.00 | 18.26 |
Minimum of Months | 0.00 | 0.426670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.93 |
Maximum of Months | 0.00 | 0.838314E+11 | 0.00 | 711776.64 | 0.00 | 0.00 | 36353884.40 | 0.00 | 18.59 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 12665266.13 | 0.578524E+10 | 0.00 | 0.00 | 0.544920E+10 | 0.00 | 0.00 | 0.00 | 1.12 |
February | 0.00 | 0.684661E+10 | 0.00 | 4783.38 | 0.338290E+10 | 0.00 | 544538.35 | 0.00 | 1.11 |
March | 0.00 | 0.813398E+10 | 0.00 | 0.00 | 0.456426E+10 | 0.00 | 0.00 | 0.00 | 1.12 |
April | 0.00 | 0.111636E+11 | 0.00 | 0.00 | 0.525262E+10 | 0.00 | 0.00 | 0.00 | 1.14 |
May | 0.00 | 0.132834E+11 | 0.00 | 0.00 | 0.723525E+10 | 0.00 | 0.00 | 0.00 | 1.15 |
June | 0.00 | 0.152089E+11 | 0.00 | 0.00 | 0.497348E+10 | 0.00 | 0.00 | 0.00 | 1.16 |
July | 0.00 | 0.682729E+10 | 0.00 | 0.00 | 0.794840E+10 | 0.00 | 0.00 | 0.00 | 1.15 |
August | 0.00 | 0.676232E+10 | 0.00 | 0.00 | 0.121991E+11 | 0.00 | 0.00 | 0.00 | 1.15 |
September | 0.00 | 0.762272E+10 | 0.00 | 0.00 | 0.982017E+10 | 0.00 | 0.00 | 0.00 | 1.14 |
October | 0.00 | 0.591579E+10 | 0.00 | 0.00 | 0.109293E+11 | 0.00 | 0.00 | 0.00 | 1.14 |
November | 0.00 | 0.646524E+10 | 0.00 | 0.00 | 0.792340E+10 | 0.00 | 0.00 | 0.00 | 1.13 |
December | 2285010.21 | 0.594888E+10 | 0.00 | 0.00 | 0.737510E+10 | 0.00 | 0.00 | 0.00 | 1.13 |
Annual Sum or Average | 14950276.34 | 0.999640E+11 | 0.00 | 4783.38 | 0.870532E+11 | 0.00 | 544538.35 | 0.00 | 1.14 |
Minimum of Months | 0.00 | 0.578524E+10 | 0.00 | 0.00 | 0.338290E+10 | 0.00 | 0.00 | 0.00 | 1.11 |
Maximum of Months | 12665266.13 | 0.152089E+11 | 0.00 | 4783.38 | 0.121991E+11 | 0.00 | 544538.35 | 0.00 | 1.16 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:21:10
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.209021E+12 | -0.568889E+10 | -0.169913E+12 | -0.670914E+12 | 0.150071E+13 |
February | 0.209948E+12 | -0.561233E+10 | -0.170332E+12 | -0.667162E+12 | 0.138658E+13 |
March | 0.291673E+12 | -0.695617E+10 | -0.212406E+12 | -0.851868E+12 | 0.159280E+13 |
April | 0.291941E+12 | -0.875149E+10 | -0.275321E+12 | -0.109746E+13 | 0.173118E+13 |
May | 0.305040E+12 | -0.105764E+11 | -0.336700E+12 | -0.133693E+13 | 0.195013E+13 |
June | 0.319643E+12 | -0.102226E+11 | -0.328824E+12 | -0.128838E+13 | 0.191801E+13 |
July | 0.263240E+12 | -0.778984E+10 | -0.239561E+12 | -0.983645E+12 | 0.166303E+13 |
August | 0.328338E+12 | -0.980606E+10 | -0.311599E+12 | -0.123900E+13 | 0.183137E+13 |
September | 0.249210E+12 | -0.912672E+10 | -0.287588E+12 | -0.113818E+13 | 0.173752E+13 |
October | 0.270385E+12 | -0.883350E+10 | -0.275095E+12 | -0.109521E+13 | 0.171987E+13 |
November | 0.210217E+12 | -0.747196E+10 | -0.230799E+12 | -0.905196E+12 | 0.159812E+13 |
December | 0.195054E+12 | -0.628847E+10 | -0.189473E+12 | -0.742467E+12 | 0.157522E+13 |
Annual Sum or Average | 0.314371E+13 | -0.971244E+11 | -0.302761E+13 | -0.120164E+14 | 0.202045E+14 |
Minimum of Months | 0.195054E+12 | -0.105764E+11 | -0.336700E+12 | -0.133693E+13 | 0.138658E+13 |
Maximum of Months | 0.328338E+12 | -0.561233E+10 | -0.169913E+12 | -0.667162E+12 | 0.195013E+13 |