Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** El Paso International Ap Ut TX USA TMY3 WMO#=722700
Simulation Timestamp: 2024-07-03 12:22:03
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:03
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 10448.27 | 920.93 | 920.93 |
Net Site Energy | 10448.27 | 920.93 | 920.93 |
Total Source Energy | 22836.89 | 2012.90 | 2012.90 |
Net Source Energy | 22836.89 | 2012.90 | 2012.90 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 744.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1098.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 783.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 194.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1658.18 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 813.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 602.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 84.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 134.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 94.78 | 2388.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | 61.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 5526.15 | 4922.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 744.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 1098.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 783.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 194.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 872.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 14.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 8.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 21.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 789.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 2.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 602.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 84.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 134.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 94.78 | 2388.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5742.51 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.69 | |
Refrigeration | General | 7.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 20.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 34.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 744.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 1098.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 783.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 194.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 1658.18 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 813.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 602.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 84.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 134.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 94.78 | 2388.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | Unassigned | 61.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 86.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 165.80 | 276.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 235.15 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 487.09 | 433.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 86.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 165.80 | 276.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 235.15 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 487.09 | 433.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 5526.150 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 5526.150 | 100.00 |
Total On-Site and Utility Electric Sources | 5526.150 | 100.00 |
Total Electricity End Uses | 5526.150 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 243.47 | 23.59 |
Air to Air Heat Recovery for Heating | 788.70 | 76.41 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 1032.17 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9857.19 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9857.19 | 100.00 |
Total Water End Uses | 9857.19 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 551.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 7682.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3B
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_TX_ELPASO
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER1 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| FLR_3_DOAS COOLING COIL | VAV WITH REHEAT COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH LAUNDRY G WATER HEATER | SWH BOOSTER E WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |CoilReportMonthly
| FLR_3_DOAS HEATING COIL | VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | FLR_3_DOAS COOLING COIL | VAV WITH REHEAT COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |FanReportMonthly
| FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL_FANCOILFAN | ROOM_2_FLR_3 FAN COIL_FANCOILFAN | ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | ROOM_5_FLR_3 FAN COIL_FANCOILFAN | ROOM_6_FLR_3 FAN COIL_FANCOILFAN | ROOM_1_FLR_6 FAN COIL_FANCOILFAN | ROOM_2_FLR_6 FAN COIL_FANCOILFAN | ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| FLR_3_DOAS | VAV WITH REHEAT |AirLoopSystemComponentLoadsMonthly
| FLR_3_DOAS | VAV WITH REHEAT |AirLoopSystemComponentEnergyUseMonthly
| FLR_3_DOAS | VAV WITH REHEAT |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:03
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21 |
RunPeriod | RUNPERIOD 1 |
Weather File | El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Latitude [deg] | 31.77 |
Longitude [deg] | -106.5 |
Elevation [m] | 1186.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 8.8143 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.26 | 23.26 | 11.3140 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 11.3140 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 4.6285 | 61.93 | 5.3800 |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 5.7199 | 46.45 | 2.6900 |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 4.6285 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.50 | 65.50 | 10.0104 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.08 | 85.08 | 10.7639 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 8.2882 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 8.2882 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 7.1042 | 18.58 | 0.0000 |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.74 | 6.74 | 8.2882 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 10.0104 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 10.0104 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.37 | 26.37 | 11.4097 | 4.65 | 2934.4875 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.20 | 28.20 | 7.1042 | 18.58 | 0.0000 |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 8.5566 | 7.07 | 41.0709 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 8.5566 | 7.07 | 41.0709 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 1978.83 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 8.8143 | 18.58 | 5.3800 | |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 1.00 | RETAIL_1_FLR_1 | GENERAL | RETAIL_1_FLR_1 | 11.3140 | 6.19 | 10.7600 | |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 1.00 | RETAIL_2_FLR_1 | GENERAL | RETAIL_2_FLR_1 | 11.3140 | 6.19 | 10.7600 | |
MECH_FLR_1 | 164.24 | Yes | Yes | 1.00 | MECH_FLR_1 | GENERAL | MECH_FLR_1 | 4.6285 | 61.93 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 1.00 | STORAGE_FLR_1 | GENERAL | STORAGE_FLR_1 | 5.7199 | 46.45 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 1.00 | LAUNDRY_FLR_1 | GENERAL | LAUNDRY_FLR_1 | 4.6285 | 9.29 | 597.5300 | |
CAFE_FLR_1 | 188.86 | Yes | Yes | 1.00 | CAFE_FLR_1 | GENERAL | CAFE_FLR_1 | 10.0104 | 1.33 | 5.3800 | |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 1.00 | LOBBY_FLR_1 | GENERAL | LOBBY_FLR_1 | 10.7639 | 3.10 | 8.0700 | |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_1_FLR_3 | GENERAL | ROOM_1_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_2_FLR_3 | GENERAL | ROOM_2_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 76.00 | ROOM_3_MULT19_FLR_3 | GENERAL | ROOM_3_MULT19_FLR_3 | 8.2882 | 16.35 | 10.5200 | |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 76.00 | ROOM_4_MULT19_FLR_3 | GENERAL | ROOM_4_MULT19_FLR_3 | 8.2882 | 16.35 | 10.5200 | |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_5_FLR_3 | GENERAL | ROOM_5_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_6_FLR_3 | GENERAL | ROOM_6_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 4.00 | CORRIDOR_FLR_3 | GENERAL | CORRIDOR_FLR_3 | 7.1042 | 18.58 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_1_FLR_6 | GENERAL | ROOM_1_FLR_6 | 8.2882 | 26.01 | 6.7500 | |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_2_FLR_6 | GENERAL | ROOM_2_FLR_6 | 8.2882 | 26.01 | 6.7500 | |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 9.00 | ROOM_3_MULT9_FLR_6 | GENERAL | ROOM_3_MULT9_FLR_6 | 8.2882 | 16.35 | 10.5200 | |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1.00 | BANQUET_FLR_6 | GENERAL | BANQUET_FLR_6 | 10.0104 | 1.33 | 67.8200 | |
DINING_FLR_6 | 331.66 | Yes | Yes | 1.00 | DINING_FLR_6 | GENERAL | DINING_FLR_6 | 10.0104 | 1.33 | 67.8200 | |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 1.00 | KITCHEN_FLR_6 | GENERAL | KITCHEN_FLR_6 | 11.4097 | 4.65 | 2934.4875 | |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1.00 | CORRIDOR_FLR_6 | GENERAL | CORRIDOR_FLR_6 | 7.1042 | 18.58 | 0.0000 | |
Total | 11345.29 | 8.5566 | 3.54 | 41.0709 | |||||||
Conditioned Total | 11345.29 | 8.5566 | 3.54 | 41.0709 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 11345.29 | 11345.29 | 0.00 | 0.00 | 4.6520 | 8.82 | 37.1989 |
Total | 11345.29 | 11345.29 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:03
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 21-JUL-20:00 | 08-FEB-18:00 | - | - | - | - | - | - | - | - | - | - | 21-FEB-21:40 |
Heating | 0.00 | 201338.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 158737.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 57474.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 12338.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 88218.55 | 104248.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 10998.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 38446.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 3932.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 4349.58 | 230079.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1746.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 386181.05 | 535667.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 201338.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 158737.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 57474.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 12338.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 58235.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 29272.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1285.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 9600.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 112.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 38446.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 3932.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 4349.58 | 230079.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 228.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 423.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1094.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:03
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 807.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3480.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2480.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 614.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5251.45 | 1939.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2577.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1908.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 268.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 424.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 300.17 | 2589.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 195.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 17501.32 | 5335.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 71.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 306.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 218.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 54.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 462.88 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 227.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 168.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 23.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 37.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 26.46 | 228.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1542.61 | 470.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 71.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 306.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 218.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 54.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 462.88 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 227.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 168.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 23.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 37.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 26.46 | 228.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1542.61 | 470.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:03
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
BASEMENT VAV BOX COMPONENT | 2.89 | 0.522163 | 0.468000 | 1.35 | 1.00 | 0.500000 | 0.000730 | 0.000054 | 1.35 | 16.70 | 0.008000 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.357066 | 0.143134 | 0.468000 | 0.167107 | 0.468000 | 0.500000 | 0.002662 | 0.000028 | 0.167107 | 16.70 | 0.008000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.268201 | 0.220669 | 0.468000 | 0.125518 | 0.588452 | 0.500000 | 0.001727 | 0.000012 | 0.125518 | 16.70 | 0.008000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.232930 | 0.537300 | 0.468000 | 0.109011 | 1.00 | 0.500000 | 0.000709 | 0.000017 | 0.109011 | 16.70 | 0.008000 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.140346 | 0.514490 | 0.468000 | 0.065682 | 1.00 | 0.500000 | 0.000741 | 0.000011 | 0.065682 | 16.70 | 0.008000 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 3.76 | 0.015826 | 0.468000 | 1.76 | 0.468000 | 0.500000 | 0.024074 | 0.000087 | 1.76 | 16.70 | 0.008000 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.56 | 0.092207 | 0.468000 | 0.730438 | 0.468000 | 0.500000 | 0.004132 | 0.000084 | 0.730438 | 16.70 | 0.008000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 5.38 | 0.185233 | 0.468000 | 2.52 | 0.493955 | 0.500000 | 0.002057 | 0.000223 | 2.52 | 16.70 | 0.008000 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.72 | 0.689252 | 0.468000 | 0.805905 | 1.00 | 0.500000 | 0.000553 | 0.000108 | 0.805905 | 16.70 | 0.008000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.52 | 0.100272 | 0.468000 | 1.18 | 0.468000 | 0.500000 | 0.003800 | 0.000097 | 1.18 | 16.70 | 0.008000 |
DINING_FLR_6 VAV BOX COMPONENT | 2.64 | 0.095736 | 0.468000 | 1.24 | 0.468000 | 0.500000 | 0.003980 | 0.000100 | 1.24 | 16.70 | 0.008000 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.57 | 0.055030 | 0.468000 | 1.20 | 0.468000 | 0.500000 | 0.012453 | 0.000062 | 1.20 | 16.70 | 0.008000 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 0.878248 | 0.357574 | 0.468000 | 0.411020 | 0.953531 | 0.500000 | 0.001066 | 0.000070 | 0.411020 | 16.70 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
BASEMENT VAV BOX REHEAT COIL | 6188.53 | 0.000054 | 129.05 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 3209.27 | 0.000028 | 80.53 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1355.44 | 0.000012 | 30.42 |
MECH_FLR_1 VAV BOX REHEAT COIL | 1896.03 | 0.000017 | 46.38 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 1239.31 | 0.000011 | 30.95 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 9932.59 | 0.000087 | 209.67 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 9553.81 | 0.000084 | 220.69 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 25543.47 | 0.000223 | 568.68 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | 5403.61 | 0.000047 | 154.39 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | 5397.48 | 0.000047 | 154.22 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 31335.12 | 0.000274 | 895.31 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 31235.48 | 0.000273 | 892.46 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | 5391.96 | 0.000047 | 154.06 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | 5385.83 | 0.000047 | 153.89 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 12317.36 | 0.000108 | 292.85 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | 1682.36 | 0.000015 | 48.07 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | 1681.62 | 0.000015 | 48.05 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 8130.64 | 0.000071 | 232.31 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 11100.02 | 0.000097 | 244.93 |
DINING_FLR_6 VAV BOX REHEAT COIL | 11478.17 | 0.000100 | 252.91 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 7142.69 | 0.000062 | 151.27 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 7968.35 | 0.000070 | 200.46 |
FLR_3_DOAS HEATING COIL | 14143.00 | 0.000124 | 240.09 |
VAV WITH REHEAT HEATING COIL | 170897.27 | 0.001495 | 2901.16 |
Design Size Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 0.061735 |
ROOM_2_FLR_3 DIRECT AIR | 0.061728 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 0.837072 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 0.837300 |
ROOM_5_FLR_3 DIRECT AIR | 0.061735 |
ROOM_6_FLR_3 DIRECT AIR | 0.061728 |
ROOM_1_FLR_6 DIRECT AIR | 0.015434 |
ROOM_2_FLR_6 DIRECT AIR | 0.015432 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 0.099154 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Hot Water Flow [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 1.17 | 0.000047 | 0.000324 |
ROOM_2_FLR_3 FAN COIL | 1.16 | 0.000047 | 0.000322 |
ROOM_3_MULT19_FLR_3 FAN COIL | 6.92 | 0.000274 | 0.001892 |
ROOM_4_MULT19_FLR_3 FAN COIL | 7.51 | 0.000273 | 0.002169 |
ROOM_5_FLR_3 FAN COIL | 1.03 | 0.000047 | 0.000287 |
ROOM_6_FLR_3 FAN COIL | 1.02 | 0.000047 | 0.000285 |
ROOM_1_FLR_6 FAN COIL | 0.309801 | 0.000015 | 0.000086 |
ROOM_2_FLR_6 FAN COIL | 0.307357 | 0.000015 | 0.000085 |
ROOM_3_MULT9_FLR_6 FAN COIL | 1.38 | 0.000071 | 0.000391 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COIL_FANCOILFAN | 1.17 |
ROOM_2_FLR_3 FAN COIL_FANCOILFAN | 1.16 |
ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | 6.92 |
ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | 7.51 |
ROOM_5_FLR_3 FAN COIL_FANCOILFAN | 1.03 |
ROOM_6_FLR_3 FAN COIL_FANCOILFAN | 1.02 |
ROOM_1_FLR_6 FAN COIL_FANCOILFAN | 0.309801 |
ROOM_2_FLR_6 FAN COIL_FANCOILFAN | 0.307357 |
ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN | 1.38 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Coil Load [W] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | 21.77 | 6.70 | 0.008559 | 12.80 | 0.008500 | 0.000324 | 1.17 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | 21.77 | 6.70 | 0.008560 | 12.80 | 0.008500 | 0.000322 | 1.16 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 21.77 | 6.70 | 0.008488 | 12.80 | 0.008488 | 0.001892 | 6.92 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 21.77 | 6.70 | 0.008704 | 12.80 | 0.008500 | 0.002169 | 7.51 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | 21.77 | 6.70 | 0.008567 | 12.80 | 0.008500 | 0.000287 | 1.03 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | 21.77 | 6.70 | 0.008567 | 12.80 | 0.008500 | 0.000285 | 1.02 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | 21.77 | 6.70 | 0.008556 | 12.80 | 0.008500 | 0.000086 | 0.309801 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | 21.77 | 6.70 | 0.008556 | 12.80 | 0.008500 | 0.000085 | 0.307357 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 21.77 | 6.70 | 0.008625 | 12.80 | 0.008500 | 0.000391 | 1.38 | |
FLR_3_DOAS COOLING COIL | 38.10 | 6.70 | 0.006871 | 11.79 | 0.006871 | 0.001640 | 2.05 | 57348.72 |
VAV WITH REHEAT COOLING COIL | 30.63 | 6.70 | 0.008344 | 10.70 | 0.008344 | 0.015055 | 24.79 | 526412.02 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
VAV WITH REHEAT | 12.46 | 11.66 | 24.92 | 11.66 | 24.79 | 24.79 | 0.300000 | 0.470496 | 24.79 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
VAV WITH REHEAT_OA_CONTROLLER | 24.79 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
FLR_3_DOAS OA HEAT RECOVERY | 2.05 |
VAV WITH REHEAT OA HEAT RECOVERY | 11.66 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS FAN | 2.05 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.001640 | 0.000290 |
FLR_3_DOAS_HEATC_CONTROLLER | 0.000124 | |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.015055 | 0.000032 |
VAV WITH REHEAT_HEATC_CONTROLLER | 0.001495 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT FAN | 24.79 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.022537 | 3679.62 | |
HEATSYS1 PUMP | 0.003408 | 1026.48 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.003408 | 0.409017 |
COOLSYS1 | 0.022537 | 2.70 |
SWHSYS1 | 0.000375 | 0.045004 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 389609.40 | 389609.40 | 0.003408 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.022537 | 2547.52 |
SWHSYS1 PUMP | 0.000375 | 47.91 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.022537 | 788013.65 | 788681.89 | 89.91 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000375 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:03
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:03
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:03
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.30 | 11.20 | 6.80 | 8.10 | 10.30 | 12.50 | 19.20 | 23.80 | 27.90 | 27.50 | 26.30 | 23.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | El Paso International Ap Ut TX USA TMY3 WMO#=722700 | 31.77 | -106.50 | -7.00 | 1186.00 | 87865 | 1.0443 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 17.94 | 21.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.58 | 23.26 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.72 | 65.50 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.80 | 85.08 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.70 | 6.74 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.96 | 26.37 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.27 | 28.20 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 8.814 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 14.194 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 11.314 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 22.074 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 11.314 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 22.074 | No |
4 | MECH_FLR_1 | 164.24 | 2.7 | 61.932 | 1.615E-002 | 4.628 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 10.008 | No |
5 | STORAGE_FLR_1 | 94.76 | 2.0 | 46.451 | 2.153E-002 | 5.720 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 8.410 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 4.628 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 602.158 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 10.010 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 15.390 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 10.764 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.834 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 8.288 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 18.808 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 8.288 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 18.808 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 21.0 | 18.581 | 5.382E-002 | 7.104 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.104 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 8.288 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 18.808 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 10.010 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 77.830 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 10.010 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 77.830 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 11.410 | 515.227 | 2419.260 | 0.000 | 0.000 | 0.000 | 2945.897 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 22.2 | 18.581 | 5.382E-002 | 7.104 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.104 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | STORAGE_FLR_1 PEOPLE | BLDG_OCC_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.0 | 2.153E-002 | 46.451 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | CORRIDOR_FLR_3 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 21.0 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 21 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
21 | CORRIDOR_FLR_6 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 22.2 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
22 | MECH_FLR_1 PEOPLE | BLDG_OCC_SCH | MECH_FLR_1 | 164.24 | 2.7 | 2.7 | 1.615E-002 | 61.932 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 3 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_BASEMENT | BASEMENT | 1978.83 | 106.5 | 17441.963 | 8.814 | 163.776 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 17441.963 |
2 | RETAIL_1_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_1_FLR_1 | 67.07 | 10.8 | 758.849 | 11.314 | 70.076 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 758.849 |
3 | RETAIL_2_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_2_FLR_1 | 77.67 | 12.5 | 878.750 | 11.314 | 70.076 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 878.750 |
4 | MECH_FLR_1_LIGHTS | LTG_SCH_MECHANIC | MECH_FLR_1 | 164.24 | 2.7 | 760.196 | 4.628 | 286.650 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 760.196 |
5 | STORAGE_FLR_1_LIGHTS | LTG_SCH_STORAGE | STORAGE_FLR_1 | 94.76 | 2.0 | 542.017 | 5.720 | 265.695 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 542.017 |
6 | LAUNDRY_FLR_1_LIGHTS | LTG_SCH_LAUNDRY | LAUNDRY_FLR_1 | 78.04 | 8.4 | 361.204 | 4.628 | 43.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 361.204 |
7 | CAFE_FLR_1_LIGHTS | LTG_SCH_DINING | CAFE_FLR_1 | 188.86 | 142.3 | 1890.589 | 10.010 | 13.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1890.589 |
8 | LOBBY_FLR_1_LIGHTS | LTG_SCH_LOBBY | LOBBY_FLR_1 | 1308.19 | 422.4 | 14081.185 | 10.764 | 33.333 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14081.185 |
9 | ROOM_1_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_3 | 39.02 | 1.5 | 323.422 | 8.288 | 215.615 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.422 |
10 | ROOM_2_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_3 | 39.02 | 1.5 | 323.384 | 8.288 | 215.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.384 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 203.259 | 8.288 | 135.506 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 203.259 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 203.314 | 8.288 | 135.543 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 203.314 |
13 | ROOM_5_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_5_FLR_3 | 39.02 | 1.5 | 323.422 | 8.288 | 215.615 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.422 |
14 | ROOM_6_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_6_FLR_3 | 39.02 | 1.5 | 323.384 | 8.288 | 215.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.384 |
15 | CORRIDOR_FLR_3_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2766.397 | 7.104 | 132.003 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2766.397 |
16 | ROOM_1_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_6 | 39.02 | 1.5 | 323.422 | 8.288 | 215.615 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.422 |
17 | ROOM_2_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_6 | 39.02 | 1.5 | 323.384 | 8.288 | 215.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.384 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 203.314 | 8.288 | 135.543 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 203.314 |
19 | BANQUET_FLR_6_LIGHTS | LTG_SCH_DINING | BANQUET_FLR_6 | 331.66 | 249.9 | 3320.034 | 10.010 | 13.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3320.034 |
20 | DINING_FLR_6_LIGHTS | LTG_SCH_DINING | DINING_FLR_6 | 331.66 | 249.9 | 3320.034 | 10.010 | 13.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3320.034 |
21 | KITCHEN_FLR_6_LIGHTS | LTG_SCH_KITCHEN | KITCHEN_FLR_6 | 103.30 | 22.2 | 1178.676 | 11.410 | 53.003 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1178.676 |
22 | CORRIDOR_FLR_6_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_6 | 412.12 | 22.2 | 2927.804 | 7.104 | 132.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2927.804 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 2.7 | 883.628 | 5.380 | 333.193 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 254.902 | 2.690 | 124.952 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 457.500 | 4.429 | 20.573 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 457.500 | 457.500 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 285.000 | 2.759 | 12.816 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 285.000 | 285.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 2.390 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
6 | RES_ROOF | 19 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
7 | NONRES_EXT_WALL_GRD | 21 | 3 | 9 | 0.167 | 0.9589 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | NONRES_EXT_WALL_MID | 22 | 3 | 9 | 0.167 | 1.167 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | NONRES_EXT_WALL_TOP | 23 | 3 | 9 | 0.167 | 1.181 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | RES_EXT_WALL_MID | 25 | 3 | 9 | 0.167 | 1.021 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | RES_EXT_WALL_TOP | 26 | 3 | 9 | 0.167 | 1.034 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | NONRES_FLOOR | 30 | 3 | 7 | 0.167 | 0.3181 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
13 | NONRES_FLOOR_CEILING | 33 | 3 | 7 | 0.167 | 0.3181 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
14 | BASEMENT_FLOOR | 36 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
15 | BASEMENT_WALL_NORTH_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | BASEMENT_WALL_EAST_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | BASEMENT_WALL_SOUTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
18 | BASEMENT_WALL_WEST_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4184 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
10 | RES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
11 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
12 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8756 |
14 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6894 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6793 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | RES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8120 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
25 | RES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7993 |
26 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
27 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.883 |
28 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
29 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
30 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
31 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
32 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.883 |
33 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
34 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
35 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
39 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
40 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
41 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
42 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 2.3900722 | 2.3900722 | 2.3900722 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
21 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
22 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
23 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
24 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
25 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
26 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
27 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
28 | 9 | -0.56372661E-17 | 0.35603042E-16 | -0.14834456E-09 | -0.22354951E-17 |
29 | 8 | 0.21681598E-07 | 0.12895413E-12 | 0.37576420E-03 | -0.24652724E-09 |
30 | 7 | -0.12181032E-01 | 0.67087143E-08 | -0.22998674E-01 | 0.13850277E-03 |
31 | 6 | 0.40370585 | 0.23395349E-05 | 0.47069069 | -0.47283774E-02 |
32 | 5 | -5.1745154 | 0.87537405E-04 | -4.4305073 | 0.62984858E-01 |
33 | 4 | 32.931872 | 0.71743813E-03 | 21.398312 | -0.42118042 |
34 | 3 | -111.07522 | 0.15662534E-02 | -55.540939 | 1.5130129 |
35 | 2 | 196.98158 | 0.88235367E-03 | 77.798628 | -2.8983416 |
36 | 1 | -171.10930 | 0.94326468E-04 | -55.232514 | 2.7446195 |
37 | 0 | 57.057407 | 0.53780718E-06 | 15.562302 | |
38 | 9 | 0.13788181E-14 | 0.42316407E-16 | -0.13850765E-09 | -0.36591458E-17 |
39 | 8 | 0.20295421E-07 | 0.15509090E-12 | 0.36099725E-03 | -0.23076592E-09 |
40 | 7 | -0.11739701E-01 | 0.81955471E-08 | -0.22363010E-01 | 0.13348467E-03 |
41 | 6 | 0.39171309 | 0.28760220E-05 | 0.46045976 | -0.45870120E-02 |
42 | 5 | -5.0574682 | 0.10819265E-03 | -4.3518524 | 0.61533536E-01 |
43 | 4 | 32.414067 | 0.89103805E-03 | 21.090697 | -0.41430552 |
44 | 3 | -109.97331 | 0.19536482E-02 | -54.932704 | 1.4970936 |
45 | 2 | 195.88922 | 0.11048200E-02 | 77.241099 | -2.8809953 |
46 | 1 | -170.70571 | 0.11852782E-03 | -55.070977 | 2.7375462 |
47 | 0 | 57.057407 | 0.67841551E-06 | 15.589460 | |
48 | 9 | 0.13857471E-14 | 0.43057560E-16 | -0.13784678E-09 | -0.68945926E-17 |
49 | 8 | 0.20202246E-07 | 0.15680163E-12 | 0.35999259E-03 | -0.22970649E-09 |
50 | 7 | -0.11709634E-01 | 0.82948599E-08 | -0.22319691E-01 | 0.13314280E-03 |
51 | 6 | 0.39089600 | 0.29121450E-05 | 0.45976168 | -0.45773805E-02 |
52 | 5 | -5.0494928 | 0.10959277E-03 | -4.3464810 | 0.61434646E-01 |
53 | 4 | 32.378781 | 0.90287364E-03 | 21.069680 | -0.41383702 |
54 | 3 | -109.89821 | 0.19801908E-02 | -54.891143 | 1.4960086 |
55 | 2 | 195.81476 | 0.11201274E-02 | 77.203021 | -2.8798128 |
56 | 1 | -170.67819 | 0.12019965E-03 | -55.059979 | 2.7370639 |
57 | 0 | 57.057407 | 0.68811227E-06 | 15.591337 | |
58 | 9 | 0.14302076E-15 | 0.35792568E-16 | -0.14541430E-09 | -0.27421543E-17 |
59 | 8 | 0.21269444E-07 | 0.13686051E-12 | 0.37140784E-03 | -0.24184090E-09 |
60 | 7 | -0.12050952E-01 | 0.71525680E-08 | -0.22811354E-01 | 0.13702371E-03 |
61 | 6 | 0.40017121 | 0.24988627E-05 | 0.46767819 | -0.46867126E-02 |
62 | 5 | -5.1400200 | 0.93645327E-04 | -4.4073602 | 0.62557131E-01 |
63 | 4 | 32.779281 | 0.76858103E-03 | 21.307814 | -0.41915444 |
64 | 3 | -110.75053 | 0.16800125E-02 | -55.362013 | 1.5083221 |
65 | 2 | 196.65975 | 0.94749847E-03 | 77.634567 | -2.8932310 |
66 | 1 | -170.99041 | 0.10139533E-03 | -55.184883 | 2.7425359 |
67 | 0 | 57.057407 | 0.57877233E-06 | 15.570231 | |
68 | 9 | 0.33566835E-16 | 0.35384250E-16 | -0.14478218E-09 | -0.87565041E-18 |
69 | 8 | 0.21180494E-07 | 0.13854999E-12 | 0.37046393E-03 | -0.24082951E-09 |
70 | 7 | -0.12022754E-01 | 0.72481687E-08 | -0.22770744E-01 | 0.13670309E-03 |
71 | 6 | 0.39940498 | 0.25332696E-05 | 0.46702484 | -0.46776806E-02 |
72 | 5 | -5.1325420 | 0.94967185E-04 | -4.4023386 | 0.62464408E-01 |
73 | 4 | 32.746200 | 0.77967008E-03 | 21.288178 | -0.41871522 |
74 | 3 | -110.68014 | 0.17047184E-02 | -55.323188 | 1.5073051 |
75 | 2 | 196.58997 | 0.96166638E-03 | 77.598974 | -2.8921229 |
76 | 1 | -170.96463 | 0.10293464E-03 | -55.174560 | 2.7420841 |
77 | 0 | 57.057407 | 0.58770932E-06 | 15.571958 | |
78 | 7 | -0.11407965E-14 | 0.23474115E-16 | -0.22119674E-13 | 0.51962024E-15 |
79 | 6 | 0.16676876E-10 | 0.39440661E-11 | 0.52102403E-09 | -0.18553030E-10 |
80 | 5 | -0.80001662E-07 | 0.19215958E-07 | -0.21848785E-05 | 0.17095694E-06 |
81 | 4 | 0.10228101E-03 | 0.72538432E-05 | 0.17630655E-02 | -0.28160064E-03 |
82 | 3 | -0.15120274E-01 | 0.25611913E-03 | -0.21515117 | 0.43248511E-01 |
83 | 2 | 0.21482172 | 0.11124906E-02 | 2.8969963 | -0.61829830 |
84 | 1 | -0.54366453 | 0.69706713E-03 | -7.1337069 | 1.5687761 |
85 | 0 | 0.34594624 | 0.12518961E-04 | 4.4521846 | |
86 | 7 | -0.22119674E-13 | 0.23474115E-16 | -0.11407965E-14 | 0.51962024E-15 |
87 | 6 | 0.52102403E-09 | 0.39440661E-11 | 0.16676876E-10 | -0.18553030E-10 |
88 | 5 | -0.21848785E-05 | 0.19215958E-07 | -0.80001662E-07 | 0.17095694E-06 |
89 | 4 | 0.17630655E-02 | 0.72538432E-05 | 0.10228101E-03 | -0.28160064E-03 |
90 | 3 | -0.21515117 | 0.25611913E-03 | -0.15120274E-01 | 0.43248511E-01 |
91 | 2 | 2.8969963 | 0.11124906E-02 | 0.21482172 | -0.61829830 |
92 | 1 | -7.1337069 | 0.69706713E-03 | -0.54366453 | 1.5687761 |
93 | 0 | 4.4521846 | 0.12518961E-04 | 0.34594624 | |
94 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
95 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
96 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
97 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
98 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
99 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
100 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
101 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
102 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
103 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
104 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
105 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
106 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
107 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
108 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
109 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
110 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
111 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
112 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
113 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
114 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
115 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
116 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
117 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
118 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
119 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
120 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
121 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
122 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
123 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
124 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
125 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
126 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
127 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
128 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
129 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
130 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
131 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
132 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
133 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.45_SHGC_0.25 | 37 | 1 | VerySmooth | 2.557 | 2.557 | 1.000 | 0.251 | ||
2 | RESWINDOW_U_0.487_SHGC_0.25 | 38 | 1 | VerySmooth | 2.769 | 2.769 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 2.66719E-002 | 0.16139 | 0.61727 | 0.61727 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.12129 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 2.17016E-002 | 0.16139 | 0.61276 | 0.61276 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.11379 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | CAFE_FLR_1 | 1 | 0 |
2 | LOBBY_FLR_1 | 1 | 0 |
3 | BANQUET_FLR_6 | 1 | 0 |
4 | DINING_FLR_6 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | CAFE_FLR_1 | 0 | |
2 | LOBBY_FLR_1 | 0 | |
3 | BANQUET_FLR_6 | 0 | |
4 | DINING_FLR_6 | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH LAUNDRY G WATER HEATER | 1.1356 | 163316.0 | 11.511 | 0.4388 |
2 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.219 | 1.1187 |
3 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 2.2712 | 175842.6 | 5.775 | 0.3748 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 1.764E-002 | 2.631E-004 | 1.298E-004 | 0.239 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.811E-003 | 8.769E-005 | 2.388E-004 | 7.967E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 2.7 | 1.610E-002 | 9.800E-005 | 2.563E-004 | 8.904E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 9.287E-003 | 9.800E-005 | 2.127E-004 | 8.904E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 2.198E-002 | 2.816E-004 | 2.506E-004 | 0.256 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 3.900E-002 | 2.065E-004 | 1.137E-004 | 0.188 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 0.111 | 8.519E-005 | 1.629E-004 | 7.740E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 2.563E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 2.563E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 2.857E-003 | 1.165E-004 | 2.563E-004 | 0.138 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 2.858E-003 | 1.165E-004 | 2.563E-004 | 0.138 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 2.563E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 2.563E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 1.238E-002 | 3.180E-005 | 2.563E-004 | 3.755E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 1.297E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 1.297E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 5.239E-003 | 2.136E-004 | 1.165E-004 | 0.252 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 2.500E-002 | 7.539E-005 | 5.825E-005 | 8.904E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 2.500E-002 | 7.539E-005 | 5.825E-005 | 8.904E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 2.238E-002 | 2.167E-004 | 1.174E-004 | 0.256 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 2.191E-002 | 5.316E-005 | 4.403E-005 | 6.278E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 9.3945E-002 |
2 | Clear Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 4.1877E-002 |
3 | Clear Turbid Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1040 |
4 | Clear Turbid Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 4.5473E-002 |
5 | Intermediate Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 7.1944E-002 |
6 | Intermediate Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 2.6614E-002 |
7 | Overcast Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 2.9162E-002 |
8 | Overcast Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 9.6591E-003 |
9 | Clear Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1062 |
10 | Clear Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 5.1341E-002 |
11 | Clear Turbid Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1179 |
12 | Clear Turbid Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 5.5711E-002 |
13 | Intermediate Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 7.9683E-002 |
14 | Intermediate Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 3.3635E-002 |
15 | Overcast Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 3.2764E-002 |
16 | Overcast Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 1.3236E-002 |
17 | Clear Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.3060E-002 |
18 | Clear Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.3169E-002 |
19 | Clear Turbid Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 1.7765E-002 |
20 | Clear Turbid Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 9.9456E-003 |
21 | Intermediate Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 1.6976E-002 |
22 | Intermediate Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 6.7808E-003 |
23 | Overcast Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.8719E-002 |
24 | Overcast Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.0154E-002 |
25 | Clear Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.3060E-002 |
26 | Clear Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.3169E-002 |
27 | Clear Turbid Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 1.7765E-002 |
28 | Clear Turbid Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 9.9456E-003 |
29 | Intermediate Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 1.6976E-002 |
30 | Intermediate Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 6.7808E-003 |
31 | Overcast Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.8719E-002 |
32 | Overcast Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.0154E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 34468.75060 | 34468.75060 | 2.88774 | 2.88774 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:40:00 | 30.82000 | 6.85992E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 0.85446 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
3 | RETAIL_1_FLR_1 | Cooling | 4261.63526 | 4261.63526 | 0.35707 | 0.35707 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 37.99167 | 6.87130E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 2444.37426 | 2444.37426 | 0.12081 | 0.12081 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 3200.93839 | 3200.93839 | 0.26820 | 0.26820 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 35.84667 | 6.86787E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 780.93385 | 780.93385 | 3.85959E-002 | 9.17347E-002 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 2780.63451 | 2780.63451 | 0.23293 | 0.23293 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:40:00 | 32.07667 | 6.86190E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 1397.13983 | 1397.13983 | 6.90504E-002 | 6.90504E-002 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 1675.38363 | 1675.38363 | 0.14035 | 0.14035 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 35.84667 | 6.86787E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 938.69365 | 938.69365 | 4.63928E-002 | 5.77652E-002 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 44850.94881 | 44850.94881 | 3.75746 | 3.75746 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 36.80000 | 6.86940E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 1885.23776 | 1885.23776 | 9.31723E-002 | 9.31723E-002 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 18611.18383 | 18611.18383 | 1.56077 | 1.56077 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 37.99167 | 6.87130E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 6210.22673 | 6210.22673 | 0.30692 | 0.67639 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 64208.55527 | 64208.55527 | 5.38153 | 5.38153 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 38.10000 | 6.87148E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 14015.42234 | 14015.42234 | 0.69268 | 1.89399 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 10330.39961 | 10330.39961 | 1.16619 | 1.16619 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 36.80000 | 6.86940E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 5403.66805 | 5403.66805 | 0.26863 | 0.26863 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 10261.49873 | 10261.49873 | 1.15841 | 1.15841 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 36.62667 | 6.86912E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 5397.53743 | 5397.53743 | 0.26832 | 0.26832 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 61286.34404 | 61286.34404 | 6.91826 | 6.91826 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 38.10000 | 6.87148E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 31335.28939 | 31335.28939 | 1.55777 | 1.55777 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 66502.87018 | 66502.87018 | 7.50774 | 7.50774 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 37.71000 | 6.87086E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 31235.65171 | 31235.65171 | 1.55282 | 1.55282 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 9122.87895 | 9122.87895 | 1.02987 | 1.02987 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 33.48500 | 6.86412E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 5392.01774 | 5392.01774 | 0.26805 | 0.26805 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 9056.98600 | 9056.98600 | 1.02244 | 1.02244 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 33.16000 | 6.86360E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 5385.88542 | 5385.88542 | 0.26775 | 0.26775 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 20555.03993 | 20555.03993 | 1.72202 | 1.72202 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 37.84000 | 6.87107E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 8628.10978 | 8628.10978 | 0.42643 | 0.47476 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 2744.29647 | 2744.29647 | 0.30980 | 0.30980 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 36.80000 | 6.86940E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 1682.38217 | 1682.38217 | 8.36352E-002 | 8.36352E-002 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 2722.64807 | 2722.64807 | 0.30736 | 0.30736 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 36.80000 | 6.86940E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 1681.63463 | 1681.63463 | 8.35981E-002 | 8.35981E-002 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 12249.35049 | 12249.35049 | 1.38286 | 1.38286 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 38.10000 | 6.87148E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 8130.71094 | 8130.71094 | 0.40420 | 0.40420 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 30045.16922 | 30045.16922 | 2.52038 | 2.52038 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 38.10000 | 6.87148E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 5700.06092 | 5700.06092 | 0.28171 | 1.18780 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 31469.16416 | 31469.16416 | 2.63979 | 2.63979 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 38.10000 | 6.87148E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
40 | DINING_FLR_6 | Heating | 5822.53382 | 5822.53382 | 0.28776 | 1.18780 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | -5.20000 | 2.80840E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 30626.71524 | 30626.71524 | 2.57288 | 2.57288 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 36.93000 | 6.86961E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 1645.95460 | 1645.95460 | 8.13372E-002 | 0.36735 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | -5.20000 | 2.80840E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
43 | CORRIDOR_FLR_6 | Cooling | 10483.39319 | 10483.39319 | 0.87825 | 0.87825 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 38.10000 | 6.87148E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 6086.60293 | 6086.60293 | 0.30082 | 0.30082 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -5.20000 | 2.80840E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | FLR_3_DOAS | Cooling | Sensible | 54460.49 | 20.29712 | 2.05125 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | FLR_3_DOAS | Heating | Sensible | 47141.68 | 4.75477 | 2.05125 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
3 | VAV WITH REHEAT | Cooling | Sensible | 463723.42 | 24.78714 | 24.78714 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | VAV WITH REHEAT | Heating | Sensible | 169512.32 | 7.37588 | 7.37588 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:50:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.88774 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.52216 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.46800 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.35146 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 7.29658E-004 |
8 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.41400E-005 |
9 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.35146 |
10 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6188.53356 |
13 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.41400E-005 |
14 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 129.05120 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.35707 |
16 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14313 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.46800 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16711 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46800 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.66184E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.80761E-005 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.16711 |
24 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3209.26560 |
27 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.80761E-005 |
28 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 80.52532 |
29 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.26820 |
30 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22067 |
31 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.46800 |
32 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.12552 |
33 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.58845 |
34 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.72657E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.18580E-005 |
37 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.12552 |
38 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1355.43924 |
41 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.18580E-005 |
42 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 30.42187 |
43 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.23293 |
44 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.53730 |
45 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.46800 |
46 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.10901 |
47 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 7.09101E-004 |
50 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.65873E-005 |
51 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.10901 |
52 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1896.02601 |
55 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.65873E-005 |
56 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 46.38082 |
57 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.14035 |
58 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.51449 |
59 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.46800 |
60 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 6.56819E-002 |
61 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 7.40539E-004 |
64 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.08420E-005 |
65 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 6.56819E-002 |
66 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1239.30724 |
69 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.08420E-005 |
70 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 30.94778 |
71 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.75746 |
72 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 1.58262E-002 |
73 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.46800 |
74 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.75849 |
75 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46800 |
76 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.40741E-002 |
78 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.68946E-005 |
79 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.75849 |
80 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9932.58506 |
83 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.68946E-005 |
84 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 209.66694 |
85 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.56077 |
86 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.22065E-002 |
87 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.46800 |
88 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.73044 |
89 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46800 |
90 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.13203E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.35809E-005 |
93 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.73044 |
94 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9553.81438 |
97 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.35809E-005 |
98 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 220.68786 |
99 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.38153 |
100 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18523 |
101 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.46800 |
102 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.51856 |
103 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.49396 |
104 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
105 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.05687E-003 |
106 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.23465E-004 |
107 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.51856 |
108 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
110 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 25543.46978 |
111 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.23465E-004 |
112 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 568.68299 |
113 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
114 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.16619 |
115 | Fan:OnOff | ROOM_1_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 1.16619 |
116 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.72731E-005 |
117 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.24156E-004 |
118 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.77075 |
119 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
120 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.55929E-003 |
121 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
122 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
123 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.24156E-004 |
124 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.16619 |
125 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 5403.60819 |
126 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.72731E-005 |
127 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 154.39387 |
128 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
129 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.15841 |
130 | Fan:OnOff | ROOM_2_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 1.15841 |
131 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.72195E-005 |
132 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.22031E-004 |
133 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.77075 |
134 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
135 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.55970E-003 |
136 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
137 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
138 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.22031E-004 |
139 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.15841 |
140 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 5397.47762 |
141 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.72195E-005 |
142 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 154.21873 |
143 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83707 |
144 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 6.91826 |
145 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 6.91826 |
146 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.74133E-004 |
147 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.89193E-003 |
148 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.77119 |
149 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
150 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.48817E-003 |
151 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
152 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.48817E-003 |
153 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.89193E-003 |
154 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 6.91826 |
155 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 31335.12116 |
156 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.74133E-004 |
157 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 895.31095 |
158 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83730 |
159 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 7.50774 |
160 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 7.50774 |
161 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.73262E-004 |
162 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.16915E-003 |
163 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.77025 |
164 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
165 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.70388E-003 |
166 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
167 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
168 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.16915E-003 |
169 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 7.50774 |
170 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 31235.48394 |
171 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.73262E-004 |
172 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 892.46444 |
173 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
174 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.02987 |
175 | Fan:OnOff | ROOM_5_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 1.02987 |
176 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.71712E-005 |
177 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.86856E-004 |
178 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.77073 |
179 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
180 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.56684E-003 |
181 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
182 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
183 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.86856E-004 |
184 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.02987 |
185 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 5391.95799 |
186 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.71712E-005 |
187 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 154.06104 |
188 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
189 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.02244 |
190 | Fan:OnOff | ROOM_6_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 1.02244 |
191 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.71176E-005 |
192 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.84819E-004 |
193 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.77073 |
194 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
195 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.56729E-003 |
196 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
197 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
198 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.84819E-004 |
199 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.02244 |
200 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 5385.82573 |
201 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.71176E-005 |
202 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 153.88584 |
203 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.72202 |
204 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.68925 |
205 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.46800 |
206 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.80591 |
207 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.52773E-004 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.07758E-004 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.80591 |
212 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
213 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
214 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12317.36278 |
215 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.07758E-004 |
216 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 292.84914 |
217 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54338E-002 |
218 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.30980 |
219 | Fan:OnOff | ROOM_1_FLR_6 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 0.30980 |
220 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.47181E-005 |
221 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 8.60325E-005 |
222 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.77075 |
223 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
224 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.55587E-003 |
225 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
226 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
227 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 8.60325E-005 |
228 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.30980 |
229 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1682.36435 |
230 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.47181E-005 |
231 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 48.06802 |
232 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54319E-002 |
233 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.30736 |
234 | Fan:OnOff | ROOM_2_FLR_6 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 0.30736 |
235 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.47115E-005 |
236 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 8.53630E-005 |
237 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.77075 |
238 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
239 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.55626E-003 |
240 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
241 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
242 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 8.53630E-005 |
243 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.30736 |
244 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1681.61682 |
245 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.47115E-005 |
246 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 48.04666 |
247 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 9.91540E-002 |
248 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.38286 |
249 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 1.38286 |
250 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 7.11304E-005 |
251 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.91271E-004 |
252 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.77042 |
253 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
254 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.62505E-003 |
255 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
256 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
257 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.91271E-004 |
258 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.38286 |
259 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 8130.64203 |
260 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.11304E-005 |
261 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 232.30537 |
262 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.52038 |
263 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10027 |
264 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.46800 |
265 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.17954 |
266 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46800 |
267 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
268 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.79967E-003 |
269 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.71078E-005 |
270 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.17954 |
271 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
272 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
273 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11100.02067 |
274 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.71078E-005 |
275 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 244.92825 |
276 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.63979 |
277 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.57361E-002 |
278 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.46800 |
279 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.23542 |
280 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46800 |
281 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
282 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.97969E-003 |
283 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.00416E-004 |
284 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.23542 |
285 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
286 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
287 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11478.17144 |
288 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.00416E-004 |
289 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 252.90561 |
290 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.57288 |
291 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 5.50295E-002 |
292 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.46800 |
293 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.20411 |
294 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46800 |
295 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
296 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.24529E-002 |
297 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.24874E-005 |
298 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.20411 |
299 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
300 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
301 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7142.68839 |
302 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.24874E-005 |
303 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 151.26794 |
304 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.87825 |
305 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.35757 |
306 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.46800 |
307 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.41102 |
308 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.95353 |
309 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
310 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.06551E-003 |
311 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.97106E-005 |
312 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.41102 |
313 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
314 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
315 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7968.34689 |
316 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.97106E-005 |
317 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 200.45758 |
318 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05132 |
319 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05132 |
320 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05132 |
321 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05132 |
322 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05132 |
323 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05132 |
324 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
325 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
326 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 12.45967 |
327 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 11.66225 |
328 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 24.91934 |
329 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 11.66225 |
330 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 24.78714 |
331 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 24.78714 |
332 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
333 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.47050 |
334 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05132 |
335 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 24.78714 |
336 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05132 |
337 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05125 |
338 | HeatExchanger:AirToAir:SensibleAndLatent | FLR_3_DOAS OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.05125 |
339 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 38.10000 |
340 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
341 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.79311 |
342 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 6.87148E-003 |
343 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 6.87148E-003 |
344 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Coil Load [W] | 57348.72296 |
345 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.64017E-003 |
346 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 2.05132 |
347 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Rated Capacity [W] | 14143.00265 |
348 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.23729E-004 |
349 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 240.09207 |
350 | Fan:ConstantVolume | FLR_3_DOAS FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05125 |
351 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.64017E-003 |
352 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 2.90331E-004 |
353 | Controller:WaterCoil | FLR_3_DOAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.23729E-004 |
354 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 24.78714 |
355 | HeatExchanger:AirToAir:SensibleAndLatent | VAV WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 11.66146 |
356 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 30.62745 |
357 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
358 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.69727 |
359 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.34411E-003 |
360 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.34411E-003 |
361 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 526412.01776 |
362 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.50553E-002 |
363 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 24.78714 |
364 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 170897.27323 |
365 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.49508E-003 |
366 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 2901.15763 |
367 | Fan:VariableVolume | VAV WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 24.78714 |
368 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.50553E-002 |
369 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 3.16294E-005 |
370 | Controller:WaterCoil | VAV WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.49508E-003 |
371 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 2.25371E-002 |
372 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 3679.61825 |
373 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 3.40847E-003 |
374 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.40902 |
375 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 3.40847E-003 |
376 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 1026.48240 |
377 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
378 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 389609.40475 |
379 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 389609.40000 |
380 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 3.40847E-003 |
381 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 2.25371E-002 |
382 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 2.70445 |
383 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 2.25371E-002 |
384 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 2547.52382 |
385 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 2.25371E-002 |
386 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 788013.65238 |
387 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 788681.89000 |
388 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 89.90974 |
389 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
390 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
391 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
392 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
393 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | 6220.88 |
2 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 3223.56 |
3 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1362.07 |
4 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | 1904.63 |
5 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | 1244.85 |
6 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 9984.06 |
7 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | 9599.61 |
8 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | 25669.28 |
9 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | 5821.40 |
10 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | 5814.80 |
11 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 33757.74 |
12 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 33650.41 |
13 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | 5808.85 |
14 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | 5802.24 |
15 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 12375.28 |
16 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | 1812.42 |
17 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | 1811.61 |
18 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 8759.14 |
19 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | 11155.07 |
20 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | 11535.17 |
21 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | 7179.62 |
22 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 8003.77 |
23 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | 10651.46 |
24 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | 128707.14 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | 12645.50 | 10013.18 | 2632.32 | 0.79 | 1068.56 | 10.84 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | 12562.39 | 9947.17 | 2615.23 | 0.79 | 1061.55 | 10.77 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 81138.13 | 65511.22 | 15626.91 | 0.81 | 7916.55 | 80.29 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 84166.83 | 66177.06 | 17989.77 | 0.79 | 7151.67 | 72.54 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | 11187.25 | 8855.18 | 2332.07 | 0.79 | 945.61 | 9.59 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | 11107.63 | 8791.96 | 2315.67 | 0.79 | 938.89 | 9.52 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | 3356.60 | 2658.33 | 698.27 | 0.79 | 283.60 | 2.88 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | 3330.43 | 2637.55 | 692.88 | 0.79 | 281.39 | 2.85 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 15226.59 | 12018.10 | 3208.49 | 0.79 | 1289.91 | 13.08 |
10 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | 49472.21 | 31519.61 | 17952.61 | 0.64 | 5383.03 | 54.60 |
11 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | 649369.60 | 407018.78 | 242350.82 | 0.63 | 135789.97 | 1377.26 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 4.09 | 13.95 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.940 | 0.824 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 22.63 | 45.89 | 22.63 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 23.26 | 23.26 | 23.26 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 2.390 | 2.390 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 63.73 | 129.23 | 63.73 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 65.50 | 65.50 | 65.50 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 82.79 | 167.88 | 82.79 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 85.08 | 85.08 | 85.08 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.959 | 0.839 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.021 | 0.886 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.167 | 0.994 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.167 | 0.994 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.167 | 0.994 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.167 | 0.994 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.034 | 0.896 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.034 | 0.896 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.034 | 0.896 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.034 | 0.896 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.034 | 0.896 | 13.70 | 20.44 | 13.70 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.487_SHGC_0.25 | N/A | 2.769 | No | 6.74 | 6.74 | 6.74 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 16.77 | 21.37 | 16.77 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 34.86 | 52.03 | 34.86 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 17.17 | 17.17 | 17.17 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.181 | 1.004 | 34.86 | 52.03 | 34.86 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 17.17 | 17.17 | 17.17 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 1.5008689351E-002 | 2.4258958552E-002 | Pass | Pass | 8.7869908170E-003 | 2.2058133149E-002 | Pass | Pass |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.7872904112E-002 | 7.9411237361E-002 | Pass | Pass | 1.9030864613E-002 | 2.2132863390E-002 | Pass | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.5780514647E-002 | 2.9743371794E-002 | Pass | Pass | 7.5151315358E-003 | 1.9276044712E-002 | Pass | Pass |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.3186664390E-002 | 1.5108971650E-002 | Pass | Pass | 8.1033738876E-003 | 2.3143783329E-002 | Pass | Pass |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.0306114337E-002 | 1.0084872410E-002 | Pass | Pass | 8.1201991200E-003 | 2.3636785080E-002 | Pass | Pass |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 5.2363338099E-002 | 0.1711291575 | Pass | Pass | 1.9578671278E-002 | 5.2534204864E-002 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 3.5201245554E-002 | 6.8972409543E-002 | Pass | Pass | 1.6213321703E-002 | 2.2932127059E-002 | Pass | Pass |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.9540949734E-002 | 4.0344540869E-002 | Pass | Pass | 1.0162935458E-002 | 2.2145114024E-002 | Pass | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 6.2038444356E-002 | 0.2138214957 | Pass | Pass | 0.1786630654 | 0.5952396219 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.7480583381E-002 | 0.1725854534 | Pass | Pass | 0.2713612869 | 1.1481171249 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 7.3444320168E-003 | 2.0665891864E-002 | Pass | Pass | 9.7861340853E-002 | 0.2997648006 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.3549905654E-002 | 0.1308536911 | Pass | Pass | 0.4204132685 | 3.1008853009 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 6.3026221411E-002 | 0.2257953090 | Pass | Pass | 0.3018098749 | 1.4010192168 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 2.3108159185E-002 | 6.3755558219E-002 | Pass | Pass | 0.4387949613 | 1.7116555341 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 1.2462230352E-002 | 1.1747879186E-002 | Pass | Pass | 8.1845099819E-003 | 2.2683893697E-002 | Pass | Pass |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 5.6327382717E-002 | 0.1900100730 | Pass | Pass | 0.1315691152 | 0.2863750494 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 5.6938647971E-002 | 0.1845864077 | Pass | Pass | 0.1461113321 | 0.3898722410 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 8.2911135182E-002 | 0.2788651053 | Pass | Pass | 0.1457963617 | 0.3873046640 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 1.8386313312E-002 | 5.3389761133E-002 | Pass | Pass | 1.5255899870E-002 | 4.4737582915E-002 | Pass | Pass |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 1.1531086300E-002 | 3.9084337234E-002 | Pass | Pass | 1.4803116978E-002 | 4.2227184048E-002 | Pass | Pass |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 1.4065880752E-002 | 4.3197573050E-002 | Pass | Pass | 2.1153508746E-002 | 4.2466575877E-002 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 2.2778407581E-002 | 2.1147612145E-002 | Pass | Pass | 9.1875019951E-003 | 2.1598905926E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:03
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3230.49 | 34.04 | 862.80 | 3927.56 | 5859.28 | 13914.17 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:03
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | -5.20 | 0.00 | -5.20 | Wetbulb [C] | 2.20 | 20.00 |
EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 38.10 | 13.00 | 18.10 | Wetbulb [C] | 3.90 | 280.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 3.00 | 6 | |||
Feb | 3.00 | 4 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 18.00 | 7 | |||
Jul | 27.00 | 16 | |||
Aug | 41.00 | 15 | |||
Sep | 0.00 | 0 | |||
Oct | 23.00 | 18 | |||
Nov | 0.00 | 0 | |||
Dec | 7.00 | 7 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:03
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 211.13 | 211.13 | 0.00 | 90.00 | N |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 55.76 | 55.76 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 211.13 | 211.13 | 180.00 | 90.00 | S |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 55.76 | 55.76 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 45.89 | 22.63 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 129.23 | 63.73 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 167.88 | 82.79 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.839 | 0.959 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 104.06 | 69.72 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 847.14 | 567.58 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 847.37 | 567.71 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 104.06 | 69.72 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 26.02 | 17.43 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.994 | 1.167 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 13.94 | 9.34 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | RES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 13.94 | 9.34 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 183.96 | 123.26 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 97.55 | 65.36 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 97.55 | 65.36 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 21.37 | 16.77 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 52.03 | 34.86 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 13.94 | 9.34 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 17.65 | 11.83 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.004 | 1.181 | 52.03 | 34.86 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 167.42 | 167.42 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_FLOOR | BASEMENT_FLOOR | 0.30 | 1.441 | 2.705 | 1978.83 | 1978.83 | 0.00 | 180.00 | |
BASEMENT_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 67.07 | 67.07 | 180.00 | 0.00 | |
BASEMENT_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 77.67 | 77.67 | 180.00 | 0.00 | |
BASEMENT_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 164.24 | 164.24 | 180.00 | 0.00 | |
BASEMENT_CEILING_4 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 94.76 | 94.76 | 180.00 | 0.00 | |
BASEMENT_CEILING_5 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 78.04 | 78.04 | 180.00 | 0.00 | |
BASEMENT_CEILING_6 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 188.86 | 188.86 | 180.00 | 0.00 | |
BASEMENT_CEILING_7 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 1088.56 | 1088.56 | 180.00 | 0.00 | |
BASEMENT_CEILING_8 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 219.63 | 219.63 | 90.00 | 0.00 | |
RETAIL_1_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_1_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
RETAIL_1_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 67.07 | 67.07 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
RETAIL_2_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_2_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 90.00 | 90.00 | E |
RETAIL_2_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 77.67 | 77.67 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 77.67 | 77.67 | 180.00 | 0.00 | |
MECH_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
MECH_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 180.00 | 90.00 | S |
MECH_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
MECH_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 164.24 | 164.24 | 0.00 | 180.00 | |
MECH_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 164.24 | 164.24 | 180.00 | 0.00 | |
STORAGE_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
STORAGE_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 180.00 | 90.00 | S |
STORAGE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
STORAGE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 94.76 | 94.76 | 0.00 | 180.00 | |
STORAGE_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 94.76 | 94.76 | 180.00 | 0.00 | |
LAUNDRY_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 180.00 | 90.00 | S |
LAUNDRY_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 270.00 | 90.00 | W |
LAUNDRY_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 78.04 | 78.04 | 0.00 | 180.00 | |
LAUNDRY_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 78.04 | 78.04 | 180.00 | 0.00 | |
CAFE_FLR_1_WALL_1_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_2_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
CAFE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 188.86 | 188.86 | 0.00 | 180.00 | |
LOBBY_FLR_1_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 90.00 | 90.00 | E |
LOBBY_FLR_1_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 1088.56 | 1088.56 | 180.00 | 180.00 | |
LOBBY_FLR_1_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 219.63 | 219.63 | 90.00 | 180.00 | |
LOBBY_FLR_1_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 1062.83 | 1062.83 | 270.00 | 0.00 | |
ROOM_1_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_1_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
ROOM_1_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_1_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_2_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
ROOM_2_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_2_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_2_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 156.07 | 156.07 | 180.00 | 0.00 | |
ROOM_3_MULT19_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.14 | 847.14 | 0.00 | 90.00 | N |
ROOM_3_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_3_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 1863.81 | 1863.81 | 0.00 | 180.00 | |
ROOM_3_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 1863.81 | 1863.81 | 180.00 | 0.00 | |
ROOM_4_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_4_MULT19_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.37 | 847.37 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_4_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 1864.32 | 1864.32 | 0.00 | 180.00 | |
ROOM_4_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 1864.32 | 1864.32 | 180.00 | 0.00 | |
ROOM_5_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
ROOM_5_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_5_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_6_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
ROOM_6_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_6_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 156.07 | 156.07 | 180.00 | 0.00 | |
CORRIDOR_FLR_3_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.28 | 847.28 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_4_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.27 | 847.27 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 297.29 | 297.29 | 180.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 963.06 | 963.06 | 270.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_3 | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 297.26 | 297.26 | 90.00 | 180.00 | |
CORRIDOR_FLR_3_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 297.29 | 297.29 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 963.06 | 963.06 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 297.26 | 297.26 | 90.00 | 0.00 | |
ROOM_1_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 0.00 | 90.00 | N |
ROOM_1_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_1_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_2_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_2_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 180.00 | 90.00 | S |
ROOM_2_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_3_MULT9_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.96 | 183.96 | 0.00 | 90.00 | N |
ROOM_3_MULT9_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 90.00 | 90.00 | E |
ROOM_3_MULT9_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 270.00 | 90.00 | W |
ROOM_3_MULT9_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 220.77 | 220.77 | 0.00 | 180.00 | |
BANQUET_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
BANQUET_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
BANQUET_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
BANQUET_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 331.66 | 331.66 | 0.00 | 180.00 | |
DINING_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
DINING_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
DINING_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
DINING_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 331.66 | 331.66 | 0.00 | 180.00 | |
KITCHEN_FLR_6_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 7.43 | 7.43 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 103.30 | 103.30 | 180.00 | 180.00 | |
CORRIDOR_FLR_6_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 104.98 | 104.98 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_1_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.95 | 183.95 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 11.15 | 11.15 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 40.88 | 40.88 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 412.12 | 412.12 | 180.00 | 180.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3957.66 | 0.00 | 90.00 | N | ||
RETAIL_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 134.14 | 0.00 | 90.00 | N | ||
RETAIL_2_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 155.34 | 0.00 | 90.00 | N | ||
MECH_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 328.49 | 0.00 | 90.00 | N | ||
STORAGE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 189.52 | 0.00 | 90.00 | N | ||
LAUNDRY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 156.08 | 0.00 | 90.00 | N | ||
CAFE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 377.72 | 0.00 | 90.00 | N | ||
LOBBY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 2616.37 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3727.63 | 0.00 | 90.00 | N | ||
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3728.64 | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3115.24 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.04 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.03 | 0.00 | 90.00 | N | ||
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 441.55 | 0.00 | 90.00 | N | ||
BANQUET_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
DINING_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 206.61 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 824.25 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 23.26 | 0.00 | 0.00 | 23.26 | 23.26 | 2.557 | 0.251 | 0.276 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 65.50 | 0.00 | 0.00 | 65.50 | 65.50 | 2.557 | 0.251 | 0.276 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 85.08 | 0.00 | 0.00 | 85.08 | 85.08 | 2.557 | 0.251 | 0.276 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.769 | 0.251 | 0.276 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.769 | 0.251 | 0.276 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.769 | 0.251 | 0.276 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.769 | 0.251 | 0.276 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 3.68 | 0.00 | 0.00 | 3.68 | 279.56 | 2.769 | 0.251 | 0.276 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 3.68 | 0.00 | 0.00 | 3.68 | 279.65 | 2.769 | 0.251 | 0.276 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.769 | 0.251 | 0.276 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.769 | 0.251 | 0.276 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.769 | 0.251 | 0.276 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.769 | 0.251 | 0.276 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.557 | 0.251 | 0.276 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 2.557 | 0.251 | 0.276 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 2.557 | 0.251 | 0.276 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.557 | 0.251 | 0.276 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.769 | 0.251 | 0.276 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.769 | 0.251 | 0.276 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.769 | 0.251 | 0.276 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.769 | 0.251 | 0.276 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.487_SHGC_0.25 | 6.74 | 0.00 | 0.00 | 6.74 | 60.70 | 2.769 | 0.251 | 0.276 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.557 | 0.251 | 0.276 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.557 | 0.251 | 0.276 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.557 | 0.251 | 0.276 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.557 | 0.251 | 0.276 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | |||||||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.557 | 0.251 | 0.276 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 5.82 | 0.00 | 0.00 | 5.82 | 5.82 | 2.557 | 0.251 | 0.276 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 2.557 | 0.251 | 0.276 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.557 | 0.251 | 0.276 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 1213.79 | 2.707 | 0.251 | 0.276 | |||||||||||||||||
North Total or Average | 432.95 | 2.714 | 0.251 | 0.276 | |||||||||||||||||
Non-North Total or Average | 780.84 | 2.702 | 0.251 | 0.276 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 1.760 | 2.390 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:03
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:03
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 8.8143 | 1978.83 | 17441.96 | LightsWired | LTG_SCH_BASEMENT | 49.32 | 168.00 | 49.26 | 0.0000 | Y | 161.29 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | RETAIL_1_FLR_1 | GENERAL | 11.3140 | 67.07 | 758.85 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 7.31 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | RETAIL_2_FLR_1 | GENERAL | 11.3140 | 77.67 | 878.75 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 8.46 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | MECH_FLR_1 | GENERAL | 4.6285 | 164.24 | 760.20 | LightsWired | LTG_SCH_MECHANIC | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 8.37 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | STORAGE_FLR_1 | GENERAL | 5.7199 | 94.76 | 542.02 | LightsWired | LTG_SCH_STORAGE | 30.30 | 168.00 | 30.27 | 0.0000 | Y | 3.08 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | LAUNDRY_FLR_1 | GENERAL | 4.6285 | 78.04 | 361.20 | LightsWired | LTG_SCH_LAUNDRY | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 3.98 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | CAFE_FLR_1 | GENERAL | 10.0104 | 188.86 | 1890.59 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 40.22 | 0.0000 | Y | 14.27 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | LOBBY_FLR_1 | GENERAL | 10.7639 | 1308.19 | 14081.18 | LightsWired | LTG_SCH_LOBBY | 44.02 | 168.00 | 41.68 | 0.0000 | Y | 110.17 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | ROOM_1_FLR_3 | GENERAL | 8.2882 | 156.09 | 1293.69 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | ROOM_2_FLR_3 | GENERAL | 8.2882 | 156.07 | 1293.54 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | GENERAL | 8.2882 | 1863.81 | 15447.65 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 110.38 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | GENERAL | 8.2882 | 1864.32 | 15451.87 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 110.41 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | ROOM_5_FLR_3 | GENERAL | 8.2882 | 156.09 | 1293.69 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | ROOM_6_FLR_3 | GENERAL | 8.2882 | 156.07 | 1293.54 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | CORRIDOR_FLR_3 | GENERAL | 7.1042 | 1557.62 | 11065.59 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 91.33 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | ROOM_1_FLR_6 | GENERAL | 8.2882 | 39.02 | 323.42 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 2.31 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | ROOM_2_FLR_6 | GENERAL | 8.2882 | 39.02 | 323.38 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 2.31 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | GENERAL | 8.2882 | 220.77 | 1829.83 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 13.08 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | BANQUET_FLR_6 | GENERAL | 10.0104 | 331.66 | 3320.03 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 49.99 | 0.0000 | Y | 31.15 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | DINING_FLR_6 | GENERAL | 10.0104 | 331.66 | 3320.03 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 49.99 | 0.0000 | Y | 31.15 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | KITCHEN_FLR_6 | GENERAL | 11.4097 | 103.30 | 1178.68 | LightsWired | LTG_SCH_KITCHEN | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 12.97 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | CORRIDOR_FLR_6 | GENERAL | 7.1042 | 412.12 | 2927.80 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 24.17 |
Interior Lighting Total | 8.5566 | 11345.29 | 97077.49 | 457.42 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
LOBBY_FLR_1_DAYLREFPT1 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.07 | 14081.18 | 985.68 |
LOBBY_FLR_1_DAYLREFPT2 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.07 | 14081.18 | 985.68 |
CAFE_FLR_1_DAYLREFPT1 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1890.59 | 737.33 |
CAFE_FLR_1_DAYLREFPT2 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1890.59 | 737.33 |
DINING_FLR_6_DAYLREFPT1 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
DINING_FLR_6_DAYLREFPT2 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
BANQUET_FLR_6_DAYLREFPT1 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
BANQUET_FLR_6_DAYLREFPT2 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 12338.45 | AstronomicalClock | - | 83.77 | 83.77 | 194.01 | |
Exterior Lighting Total | 12338.45 | 194.01 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:03
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 389609.40 | 0.80 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 788681.89 | 2.96 | 788681.89 | 2.96 | 4.09 | 13.95 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 11334.39 | 12645.50 | 10013.18 | 2632.32 | 0.79 | - | 1068.56 | 10.84 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 11260.08 | 12562.39 | 9947.17 | 2615.23 | 0.79 | - | 1061.55 | 10.77 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 66152.96 | 81138.13 | 65511.22 | 15626.91 | 0.81 | - | 7916.55 | 80.29 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 75846.09 | 84166.83 | 66177.06 | 17989.77 | 0.79 | - | 7151.67 | 72.54 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 10030.15 | 11187.25 | 8855.18 | 2332.07 | 0.79 | - | 945.61 | 9.59 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 9958.93 | 11107.63 | 8791.96 | 2315.67 | 0.79 | - | 938.89 | 9.52 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3008.20 | 3356.60 | 2658.33 | 698.27 | 0.79 | - | 283.60 | 2.88 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 2984.79 | 3330.43 | 2637.55 | 692.88 | 0.79 | - | 281.39 | 2.85 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 13681.13 | 15226.59 | 12018.10 | 3208.49 | 0.79 | - | 1289.91 | 13.08 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | 57348.72 | 49472.21 | 31519.61 | 17952.61 | 0.64 | - | 5383.03 | 54.60 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | 526412.02 | 649369.60 | 407018.78 | 242350.82 | 0.63 | - | 135789.97 | 1377.26 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 6188.53 | 6220.88 | - |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 3209.27 | 3223.56 | - |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1355.44 | 1362.07 | - |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1896.03 | 1904.63 | - |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1239.31 | 1244.85 | - |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 9932.59 | 9984.06 | - |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 9553.81 | 9599.61 | - |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 25543.47 | 25669.28 | - |
ROOM_1_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 5403.61 | 5821.40 | - |
ROOM_2_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 5397.48 | 5814.80 | - |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 31335.12 | 33757.74 | - |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 31235.48 | 33650.41 | - |
ROOM_5_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 5391.96 | 5808.85 | - |
ROOM_6_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 5385.83 | 5802.24 | - |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 12317.36 | 12375.28 | - |
ROOM_1_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 1682.36 | 1812.42 | - |
ROOM_2_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 1681.62 | 1811.61 | - |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 8130.64 | 8759.14 | - |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 11100.02 | 11155.07 | - |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 11478.17 | 11535.17 | - |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 7142.69 | 7179.62 | - |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 7968.35 | 8003.77 | - |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | 14143.00 | 10651.46 | - |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | 170897.27 | 128707.14 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 0.24 | 76.61 | 324.68 | 1.00 | 2.78 | General | ||
LOBBY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.24 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
ROOM_1_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 1.17 | 820.57 | 703.64 | 1.00 | 1.16 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 |
ROOM_2_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 1.16 | 815.10 | 703.64 | 1.00 | 1.16 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 |
ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 6.92 | 4867.94 | 703.64 | 1.00 | 0.95 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 |
ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 7.51 | 5282.72 | 703.64 | 1.00 | 0.95 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 |
ROOM_5_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 1.03 | 724.66 | 703.64 | 1.00 | 1.19 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 |
ROOM_6_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 1.02 | 719.42 | 703.64 | 1.00 | 1.19 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 |
ROOM_1_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 0.31 | 217.99 | 703.64 | 1.00 | 1.69 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 |
ROOM_2_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 0.31 | 216.27 | 703.64 | 1.00 | 1.70 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 |
ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 1.38 | 973.03 | 703.64 | 1.00 | 1.13 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 |
BANQUET_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
DINING_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 1.89 | 612.92 | 324.68 | 1.00 | 1.48 | General | ||
FLR_3_DOAS FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.93 | 1070.05 | 1.00 | 1.30 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
VAV WITH REHEAT FAN | Fan:VariableVolume | 0.62 | 1389.42 | 24.79 | 55539.01 | 2240.64 | 1.00 | 1.11 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.022537 | 3679.62 | 163269.44 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.003408 | 1026.48 | 301156.09 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.022537 | 2547.52 | 113036.94 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH LAUNDRY G WATER HEATER | WaterHeater:Mixed | 1.14 | 163316.00 | 0.80 | 11.51 | 0.44 |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.22 | 1.12 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.60 | 0.80 | 5.78 | 0.37 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:03
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 34468.75 | 34468.75 | 17.42 | 2.888 | 2.888 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:40:00 | 24.00 | 24.00 | 0.00920 | 30.82 | 0.00686 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 4261.64 | 4261.64 | 63.54 | 0.357 | 0.357 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 24.00 | 24.00 | 0.00905 | 37.99 | 0.00687 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 3200.94 | 3200.94 | 41.21 | 0.268 | 0.268 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 24.00 | 24.00 | 0.00937 | 35.85 | 0.00687 | 0.092 | 0.00 |
MECH_FLR_1 | 2780.63 | 2780.63 | 16.93 | 0.233 | 0.233 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:40:00 | 24.00 | 24.00 | 0.00869 | 32.08 | 0.00686 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1675.38 | 1675.38 | 17.68 | 0.140 | 0.140 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 24.00 | 24.00 | 0.00875 | 35.85 | 0.00687 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 44850.95 | 44850.95 | 574.72 | 3.757 | 3.757 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 24.00 | 24.00 | 0.00854 | 36.80 | 0.00687 | 0.000 | 0.00 |
CAFE_FLR_1 | 18611.18 | 18611.18 | 98.54 | 1.561 | 1.561 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 24.00 | 23.99 | 0.01021 | 37.99 | 0.00687 | 0.676 | 0.00 |
LOBBY_FLR_1 | 64208.56 | 64208.56 | 49.08 | 5.382 | 5.382 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 23.99 | 0.00997 | 38.10 | 0.00687 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 10330.40 | 10330.40 | 264.73 | 1.166 | 1.166 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 21.11 | 21.11 | 0.00856 | 36.80 | 0.00687 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 10261.50 | 10261.50 | 263.00 | 1.158 | 1.158 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 21.11 | 21.11 | 0.00856 | 36.63 | 0.00687 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 61286.34 | 61286.34 | 2499.05 | 6.918 | 6.918 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 21.11 | 21.11 | 0.00849 | 38.10 | 0.00687 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 66502.87 | 66502.87 | 2711.02 | 7.508 | 7.508 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 21.11 | 21.11 | 0.00870 | 37.71 | 0.00687 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 9122.88 | 9122.88 | 233.79 | 1.030 | 1.030 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 21.11 | 21.11 | 0.00857 | 33.48 | 0.00686 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 9056.99 | 9056.99 | 232.13 | 1.022 | 1.022 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 21.11 | 21.11 | 0.00857 | 33.16 | 0.00686 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 20555.04 | 20555.04 | 52.79 | 1.722 | 1.722 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 24.00 | 24.00 | 0.00941 | 37.84 | 0.00687 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 2744.30 | 2744.30 | 70.33 | 0.310 | 0.310 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 21.11 | 21.11 | 0.00856 | 36.80 | 0.00687 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2722.65 | 2722.65 | 69.78 | 0.307 | 0.307 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 21.11 | 21.11 | 0.00856 | 36.80 | 0.00687 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 12249.35 | 12249.35 | 499.35 | 1.383 | 1.383 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 21.11 | 21.11 | 0.00863 | 38.10 | 0.00687 | 0.099 | 0.00 |
BANQUET_FLR_6 | 30045.17 | 30045.17 | 90.59 | 2.520 | 2.520 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 23.98 | 0.01037 | 38.10 | 0.00687 | 1.188 | 0.00 |
DINING_FLR_6 | 31469.16 | 31469.16 | 94.88 | 2.640 | 2.640 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 23.98 | 0.01029 | 38.10 | 0.00687 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 30626.72 | 30626.72 | 296.47 | 2.573 | 2.573 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 24.00 | 23.97 | 0.01009 | 36.93 | 0.00687 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 10483.39 | 10483.39 | 25.44 | 0.878 | 0.878 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 24.00 | 0.00897 | 38.10 | 0.00687 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 0.854 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 22.94 | 0.00281 | -5.20 | 0.00281 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 2444.37 | 2444.37 | 36.44 | 0.121 | 0.121 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00780 | -5.20 | 0.00281 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 780.93 | 780.93 | 10.05 | 0.039 | 0.092 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00776 | -5.20 | 0.00281 | 0.092 | 0.00 |
MECH_FLR_1 | 1397.14 | 1397.14 | 8.51 | 0.069 | 0.069 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00769 | -5.20 | 0.00281 | 0.000 | 0.00 |
STORAGE_FLR_1 | 938.69 | 938.69 | 9.91 | 0.046 | 0.058 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00773 | -5.20 | 0.00281 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 1885.24 | 1885.24 | 24.16 | 0.093 | 0.093 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00769 | -5.20 | 0.00281 | 0.000 | 0.00 |
CAFE_FLR_1 | 6210.23 | 6210.23 | 32.88 | 0.307 | 0.676 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00783 | -5.20 | 0.00281 | 0.676 | 0.00 |
LOBBY_FLR_1 | 14015.42 | 14015.42 | 10.71 | 0.693 | 1.894 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00778 | -5.20 | 0.00281 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 5403.67 | 5403.67 | 138.48 | 0.269 | 0.269 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00779 | -5.20 | 0.00281 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 5397.54 | 5397.54 | 138.34 | 0.268 | 0.268 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00779 | -5.20 | 0.00281 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 31335.29 | 31335.29 | 1277.75 | 1.558 | 1.558 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00781 | -5.20 | 0.00281 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 31235.65 | 31235.65 | 1273.34 | 1.553 | 1.553 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00781 | -5.20 | 0.00281 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 5392.02 | 5392.02 | 138.18 | 0.268 | 0.268 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00779 | -5.20 | 0.00281 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 5385.89 | 5385.89 | 138.04 | 0.268 | 0.268 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00779 | -5.20 | 0.00281 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 8628.11 | 8628.11 | 22.16 | 0.426 | 0.475 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00784 | -5.20 | 0.00281 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 1682.38 | 1682.38 | 43.11 | 0.084 | 0.084 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00783 | -5.20 | 0.00281 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 1681.63 | 1681.63 | 43.10 | 0.084 | 0.084 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00783 | -5.20 | 0.00281 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8130.71 | 8130.71 | 331.45 | 0.404 | 0.404 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00784 | -5.20 | 0.00281 | 0.099 | 0.00 |
BANQUET_FLR_6 | 5700.06 | 5700.06 | 17.19 | 0.282 | 1.188 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00788 | -5.20 | 0.00281 | 1.188 | 0.00 |
DINING_FLR_6 | 5822.53 | 5822.53 | 17.56 | 0.288 | 1.188 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | 21.00 | 21.00 | 0.00788 | -5.20 | 0.00281 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 1645.95 | 1645.95 | 15.93 | 0.081 | 0.367 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 21.00 | 21.00 | 0.00664 | -5.20 | 0.00281 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 6086.60 | 6086.60 | 14.77 | 0.301 | 0.301 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00790 | -5.20 | 0.00281 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
FLR_3_DOAS | 20.30 | 2.05 | 4.75 | 2.05 | 2.0513 | 2.0513 | 2.0513 | 1.0000 | 0.3000 |
VAV WITH REHEAT | 24.79 | 24.79 | 7.38 | 7.38 | 24.7871 | 11.6623 | 24.7871 | 0.4705 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 6188.534 | 6188.534 | 1.351461 | 0.00005414 | 129.051 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 6188.53 | 6188.53 | 1.351461 | 16.70 | 11.86 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00800000 | 44.8527 | 0.00 | 0.00 | 6223.32 | 6223.32 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 3209.266 | 3209.266 | 0.167107 | 0.00002808 | 80.525 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3209.27 | 3209.27 | 0.167107 | 16.70 | 11.86 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00780143 | 43.7537 | 2444.37 | 0.00 | 3225.79 | 3225.79 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 1355.439 | 1355.439 | 0.125518 | 0.00001186 | 30.422 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1355.44 | 1355.44 | 0.125518 | 16.70 | 11.86 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00776194 | 43.5346 | 780.93 | 0.00 | 1362.77 | 1362.77 |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 1896.026 | 1896.026 | 0.109011 | 0.00001659 | 46.381 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1896.03 | 1896.03 | 0.109011 | 16.70 | 11.86 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00769005 | 43.1363 | 1397.14 | 0.00 | 1905.87 | 1905.87 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 1239.307 | 1239.307 | 0.065682 | 0.00001084 | 30.948 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1239.31 | 1239.31 | 0.065682 | 16.70 | 11.86 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00773159 | 43.3665 | 938.69 | 0.00 | 1245.70 | 1245.70 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 9932.585 | 9932.585 | 1.758489 | 0.00008689 | 209.667 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 9932.59 | 9932.59 | 1.758489 | 16.70 | 11.86 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00768664 | 43.1179 | 1885.24 | 0.00 | 9988.17 | 9988.17 |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 9553.814 | 9553.814 | 0.730438 | 0.00008358 | 220.688 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 9553.81 | 9553.81 | 0.730438 | 16.70 | 11.86 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00782636 | 43.8917 | 6210.23 | 0.00 | 9604.98 | 9604.98 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 25543.470 | 25543.470 | 2.518556 | 0.00022347 | 568.683 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 25543.47 | 25543.47 | 2.518556 | 16.70 | 11.86 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00778208 | 43.6462 | 14015.42 | 0.00 | 25682.12 | 25682.12 |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 11334.393 | -999.000 | 1.166190 | 0.00032416 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | unknown | 7/21 16:30:00 | 11334.39 | 11200.04 | 1.166190 | 21.77 | 14.21 | 0.00855929 | 12.80 | 10.82 | 0.00850000 | 36.80 | 0.00686940 | 17.78 | 0.0000 | 21.11 | 0.00855929 | 47.6209 | 10330.40 | 0.00 | 8282.22 | 8282.22 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 5403.608 | 5403.608 | 0.268629 | 0.00004727 | 154.394 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 5403.61 | 5403.61 | 0.268629 | 21.11 | 13.31 | 0.00779302 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.11 | 0.00779302 | 43.4102 | 5403.67 | 0.00 | 5825.26 | 5825.26 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 11260.077 | -999.000 | 1.158412 | 0.00032203 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | unknown | 7/21 16:40:00 | 11260.08 | 11125.68 | 1.158412 | 21.77 | 14.21 | 0.00855970 | 12.80 | 10.82 | 0.00850000 | 36.63 | 0.00686912 | 17.72 | 0.0000 | 21.11 | 0.00855970 | 47.6231 | 10261.50 | 0.00 | 8228.11 | 8228.11 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 5397.478 | 5397.478 | 0.268324 | 0.00004722 | 154.219 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 5397.48 | 5397.48 | 0.268324 | 21.11 | 13.31 | 0.00779281 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.11 | 0.00779281 | 43.4091 | 5397.54 | 0.00 | 5818.65 | 5818.65 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 66152.964 | -999.000 | 6.918264 | 0.00189193 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | unknown | 7/21 14:00:00 | 66152.96 | 66152.96 | 6.918264 | 21.77 | 14.15 | 0.00848817 | 12.80 | 10.81 | 0.00848817 | 38.10 | 0.00687148 | 18.17 | 0.0000 | 21.11 | 0.00848817 | 47.2295 | 61286.34 | 0.00 | 53129.03 | 53129.03 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 31335.121 | 31335.121 | 1.557772 | 0.00027413 | 895.311 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 31335.12 | 31335.12 | 1.557772 | 21.11 | 13.33 | 0.00781013 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.11 | 0.00781013 | 43.5040 | 31335.29 | 0.00 | 33780.33 | 33780.33 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 75846.092 | -999.000 | 7.507741 | 0.00216915 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | unknown | 7/21 15:30:00 | 75846.09 | 72841.29 | 7.507741 | 21.77 | 14.33 | 0.00870388 | 12.80 | 10.82 | 0.00850000 | 37.71 | 0.00687086 | 18.05 | 0.0000 | 21.11 | 0.00870388 | 48.4151 | 66502.87 | 0.00 | 55864.22 | 54750.53 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 31235.484 | 31235.484 | 1.552818 | 0.00027326 | 892.464 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 31235.48 | 31235.48 | 1.552818 | 21.11 | 13.33 | 0.00780950 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.11 | 0.00780950 | 43.5005 | 31235.65 | 0.00 | 33672.91 | 33672.91 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 10030.149 | -999.000 | 1.029875 | 0.00028686 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | unknown | 7/21 10:10:00 | 10030.15 | 9896.32 | 1.029875 | 21.77 | 14.22 | 0.00856684 | 12.80 | 10.82 | 0.00850000 | 33.48 | 0.00686412 | 16.74 | 0.0000 | 21.11 | 0.00856684 | 47.6623 | 9122.88 | 0.00 | 7332.27 | 7332.27 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 5391.958 | 5391.958 | 0.268050 | 0.00004717 | 154.061 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 5391.96 | 5391.96 | 0.268050 | 21.11 | 13.31 | 0.00779259 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.11 | 0.00779259 | 43.4078 | 5392.02 | 0.00 | 5812.70 | 5812.70 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 9958.933 | -999.000 | 1.022436 | 0.00028482 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | unknown | 7/21 10:00:00 | 9958.93 | 9825.16 | 1.022436 | 21.77 | 14.22 | 0.00856729 | 12.80 | 10.82 | 0.00850000 | 33.16 | 0.00686360 | 16.64 | 0.0000 | 21.11 | 0.00856729 | 47.6648 | 9056.99 | 0.00 | 7280.40 | 7280.40 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 5385.826 | 5385.826 | 0.267745 | 0.00004712 | 153.886 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 5385.83 | 5385.83 | 0.267745 | 21.11 | 13.31 | 0.00779238 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.11 | 0.00779238 | 43.4067 | 5385.89 | 0.00 | 5806.09 | 5806.09 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 12317.363 | 12317.363 | 0.805905 | 0.00010776 | 292.849 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 12317.36 | 12317.36 | 0.805905 | 16.70 | 11.86 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00784077 | 43.9711 | 8628.11 | 0.00 | 12382.79 | 12382.79 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 3008.200 | -999.000 | 0.309801 | 0.00008603 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | unknown | 7/21 16:30:00 | 3008.20 | 2974.58 | 0.309801 | 21.77 | 14.21 | 0.00855587 | 12.80 | 10.82 | 0.00850000 | 36.80 | 0.00686940 | 17.78 | 0.0000 | 21.11 | 0.00855587 | 47.6021 | 2744.30 | 0.00 | 2197.72 | 2197.72 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 1682.364 | 1682.364 | 0.083635 | 0.00001472 | 48.068 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1682.36 | 1682.36 | 0.083635 | 21.11 | 13.35 | 0.00783245 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.11 | 0.00783245 | 43.6271 | 1682.38 | 0.00 | 1813.64 | 1813.64 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 2984.790 | -999.000 | 0.307357 | 0.00008536 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | unknown | 7/21 16:30:00 | 2984.79 | 2951.20 | 0.307357 | 21.77 | 14.21 | 0.00855626 | 12.80 | 10.82 | 0.00850000 | 36.80 | 0.00686940 | 17.78 | 0.0000 | 21.11 | 0.00855626 | 47.6042 | 2722.65 | 0.00 | 2180.66 | 2180.66 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 1681.617 | 1681.617 | 0.083598 | 0.00001471 | 48.047 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1681.62 | 1681.62 | 0.083598 | 21.11 | 13.35 | 0.00783239 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.11 | 0.00783239 | 43.6268 | 1681.63 | 0.00 | 1812.84 | 1812.84 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 13681.129 | -999.000 | 1.382860 | 0.00039127 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | unknown | 7/21 14:10:00 | 13681.13 | 13343.51 | 1.382860 | 21.77 | 14.27 | 0.00862505 | 12.80 | 10.82 | 0.00850000 | 38.10 | 0.00687148 | 18.17 | 0.0000 | 21.11 | 0.00862505 | 47.9825 | 12249.35 | 0.00 | 10033.51 | 10033.51 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 8130.642 | 8130.642 | 0.404199 | 0.00007113 | 232.305 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 8130.64 | 8130.64 | 0.404199 | 21.11 | 13.36 | 0.00784012 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.11 | 0.00784012 | 43.6691 | 8130.71 | 0.00 | 8765.10 | 8765.10 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 11100.021 | 11100.021 | 1.179537 | 0.00009711 | 244.928 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 11100.02 | 11100.02 | 1.179537 | 16.70 | 11.86 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00787745 | 44.1744 | 5700.06 | 0.00 | 11160.49 | 11160.49 |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 11478.171 | 11478.171 | 1.235421 | 0.00010042 | 252.906 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | 11478.17 | 11478.17 | 1.235421 | 16.70 | 11.86 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00787997 | 44.1887 | 5822.53 | 0.00 | 11540.74 | 11540.74 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 7142.688 | 7142.688 | 1.204107 | 0.00006249 | 151.268 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 7142.69 | 7142.69 | 1.204107 | 16.70 | 11.86 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00664265 | 37.3291 | 1645.95 | 0.00 | 7182.62 | 7182.62 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 7968.347 | 7968.347 | 0.411020 | 0.00006971 | 200.458 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 7968.35 | 7968.35 | 0.411020 | 16.70 | 11.86 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00789900 | 44.2937 | 6086.60 | 0.00 | 8009.35 | 8009.35 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 57348.723 | -999.000 | 2.051317 | 0.00164017 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 57348.72 | 57348.72 | 2.051317 | 38.10 | 18.17 | 0.00687148 | 11.79 | 8.78 | 0.00687148 | 38.10 | 0.00687148 | 18.17 | 99.9965 | 21.11 | 0.00860074 | 47.8484 | 179557.30 | 0.00 | 50441.98 | 50441.98 |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | FLR_3_DOAS | 14143.003 | 14143.003 | 0.615395 | 0.00012373 | 240.092 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 14143.00 | 14143.00 | 0.615395 | -5.20 | -5.20 | 0.00280840 | 16.70 | 11.86 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 333.3216 | 21.11 | 0.00780998 | 43.5031 | 95644.78 | 0.00 | 12879.82 | 12879.82 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 526412.018 | -999.000 | 24.787135 | 0.01505532 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 526412.02 | 526412.02 | 24.787135 | 30.63 | 16.98 | 0.00834411 | 10.70 | 9.82 | 0.00834411 | 38.10 | 0.00687148 | 18.17 | 47.0464 | 23.99 | 0.00961146 | 44.8139 | 295663.54 | 0.00 | 583338.81 | 540763.11 |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV WITH REHEAT | 170897.273 | 170897.273 | 7.436141 | 0.00149508 | 2901.158 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:50:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:50:00 | 170897.27 | 170897.27 | 7.436141 | -5.20 | -5.20 | 0.00280840 | 16.70 | 11.86 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 156.8214 | 21.37 | 0.00689656 | 37.8614 | 55098.98 | 0.00 | 155633.59 | 155633.59 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:22:03
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | Yes | Yes | No | 6188.534 | 6188.534 | 1.351461 | 0.00005414 | 129.051 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.40812534 | 54.44 | 82.22 | 27.78 | 397450.45 | 1.5571 | 1.588394 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 6188.53 | 6188.53 | 1.0000 | 1.41137342 | 1.351461 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.05413447 | 60.00 | 32.22 | 27.78 | 0.000 | 6188.53 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 44.8527 | 0.00 | 0.00 | 6223.32 | 6223.32 | 1.41137342 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 20.92 | 14.82 | 0.00800000 | 41344.1 | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3209.266 | 3209.266 | 0.167107 | 0.00002808 | 80.525 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.40812534 | 54.44 | 82.22 | 27.78 | 397450.45 | 0.8075 | 0.823714 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 3209.27 | 3209.27 | 1.0000 | 0.17451508 | 0.167107 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.02807319 | 60.00 | 32.22 | 27.78 | 0.000 | 3209.27 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00780143 | 21.00 | 0.00780143 | 43.7537 | 2444.37 | 0.00 | 3225.79 | 3225.79 | 0.17451508 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 34.73 | 19.57 | 0.00800000 | 55419.0 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1355.439 | 1355.439 | 0.125518 | 0.00001186 | 30.422 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.40812534 | 54.44 | 82.22 | 27.78 | 397450.45 | 0.3410 | 0.347897 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1355.44 | 1355.44 | 1.0000 | 0.13108242 | 0.125518 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.01185676 | 60.00 | 32.22 | 27.78 | 0.000 | 1355.44 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00776194 | 21.00 | 0.00776194 | 43.5346 | 780.93 | 0.00 | 1362.77 | 1362.77 | 0.13108242 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 26.80 | 16.95 | 0.00800000 | 47331.0 | |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1896.026 | 1896.026 | 0.109011 | 0.00001659 | 46.381 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.40812534 | 54.44 | 82.22 | 27.78 | 397450.45 | 0.4770 | 0.486648 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1896.03 | 1896.03 | 1.0000 | 0.11384389 | 0.109011 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.01658557 | 60.00 | 32.22 | 27.78 | 0.000 | 1896.03 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00769005 | 21.00 | 0.00769005 | 43.1363 | 1397.14 | 0.00 | 1905.87 | 1905.87 | 0.11384389 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 33.02 | 19.03 | 0.00800000 | 53675.8 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1239.307 | 1239.307 | 0.065682 | 0.00001084 | 30.948 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.40812534 | 54.44 | 82.22 | 27.78 | 397450.45 | 0.3118 | 0.318090 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1239.31 | 1239.31 | 1.0000 | 0.06859365 | 0.065682 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.01084089 | 60.00 | 32.22 | 27.78 | 0.000 | 1239.31 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00773159 | 21.00 | 0.00773159 | 43.3665 | 938.69 | 0.00 | 1245.70 | 1245.70 | 0.06859365 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 34.41 | 19.47 | 0.00800000 | 55095.3 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9932.585 | 9932.585 | 1.758489 | 0.00008689 | 209.667 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.40812534 | 54.44 | 82.22 | 27.78 | 397450.45 | 2.4991 | 2.549370 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 9932.59 | 9932.59 | 1.0000 | 1.83644627 | 1.758489 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.08688572 | 60.00 | 32.22 | 27.78 | 0.000 | 9932.59 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00768664 | 21.00 | 0.00768664 | 43.1179 | 1885.24 | 0.00 | 9988.17 | 9988.17 | 1.83644627 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.93 | 15.20 | 0.00800000 | 42373.6 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9553.814 | 9553.814 | 0.730438 | 0.00008358 | 220.688 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.40812534 | 54.44 | 82.22 | 27.78 | 397450.45 | 2.4038 | 2.452152 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 9553.81 | 9553.81 | 1.0000 | 0.76281963 | 0.730438 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.08357241 | 60.00 | 32.22 | 27.78 | 0.000 | 9553.81 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00782636 | 21.00 | 0.00782636 | 43.8917 | 6210.23 | 0.00 | 9604.98 | 9604.98 | 0.76281963 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 28.95 | 17.68 | 0.00800000 | 49526.2 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 25543.470 | 25543.470 | 2.518556 | 0.00022347 | 568.683 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.40812534 | 54.44 | 82.22 | 27.78 | 397450.45 | 6.4268 | 6.556174 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 25543.47 | 25543.47 | 1.0000 | 2.63020831 | 2.518556 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.22344262 | 60.00 | 32.22 | 27.78 | 0.000 | 25543.47 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00778208 | 21.00 | 0.00778208 | 43.6462 | 14015.42 | 0.00 | 25682.12 | 25682.12 | 2.63020831 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 26.18 | 16.73 | 0.00800000 | 46699.0 | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11334.393 | -999.000 | 1.166190 | 0.00032416 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7513 | 1004.8586 | 1.0443 | ROOM_1_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.166190 | 1.21788944 | 4197.9300 | 999.8980 | 22.53479169 | 15.03 | 6.70 | 8.33 | 788013.65 | 1.4383 | 1.438323 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | unknown | unknown | unknown | 7/21 16:30:00 | Sensible | 11334.39 | 11200.04 | 1.0000 | 1.21788944 | 1.166190 | 21.77 | 14.21 | 0.00855929 | 43628.8 | 12.80 | 10.82 | 0.00850000 | 34322.2 | 0.32412307 | 6.70 | 15.03 | 8.33 | 0.000 | 11334.39 | 36.80 | 0.00686940 | 17.78 | 0.00000000 | 0.0000 | 21.11 | 0.00855929 | 21.11 | 0.00855929 | 47.6209 | 10330.40 | 0.00 | 8282.22 | 8282.22 | 1.21788944 | 21.77 | 15.64 | 0.00855929 | 43628.8 | 15.11 | 13.10 | 0.00855929 | 36828.3 | |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5403.608 | 5403.608 | 0.268629 | 0.00004727 | 154.394 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | ROOM_1_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.166190 | 1.21788944 | 4197.9300 | 999.8980 | 3.40812534 | 54.44 | 82.22 | 27.78 | 397450.45 | 1.3596 | 1.386930 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 5403.61 | 5403.61 | 1.0000 | 0.28053785 | 0.268629 | 21.11 | 13.31 | 0.00779302 | 41008.6 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.04726830 | 60.00 | 32.22 | 27.78 | 0.000 | 5403.61 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.11 | 0.00779302 | 21.11 | 0.00779302 | 43.4102 | 5403.67 | 0.00 | 5825.26 | 5825.26 | 0.28053785 | 16.60 | 12.95 | 0.00779302 | 36410.7 | 36.97 | 20.11 | 0.00779302 | 57175.3 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11260.077 | -999.000 | 1.158412 | 0.00032203 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7521 | 1004.8586 | 1.0443 | ROOM_2_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.158412 | 1.20976648 | 4197.9300 | 999.8980 | 22.53479169 | 15.03 | 6.70 | 8.33 | 788013.65 | 1.4289 | 1.428892 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | unknown | unknown | unknown | 7/21 16:40:00 | Sensible | 11260.08 | 11125.68 | 1.0000 | 1.20976648 | 1.158412 | 21.77 | 14.21 | 0.00855970 | 43629.8 | 12.80 | 10.82 | 0.00850000 | 34322.2 | 0.32199790 | 6.70 | 15.03 | 8.33 | 0.000 | 11260.08 | 36.63 | 0.00686912 | 17.72 | 0.00000000 | 0.0000 | 21.11 | 0.00855970 | 21.11 | 0.00855970 | 47.6231 | 10261.50 | 0.00 | 8228.11 | 8228.11 | 1.20976648 | 21.77 | 15.64 | 0.00855970 | 43629.8 | 15.11 | 13.10 | 0.00855970 | 36828.4 | |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5397.478 | 5397.478 | 0.268324 | 0.00004722 | 154.219 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | ROOM_2_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.158412 | 1.20976648 | 4197.9300 | 999.8980 | 3.40812534 | 54.44 | 82.22 | 27.78 | 397450.45 | 1.3580 | 1.385356 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 5397.48 | 5397.48 | 1.0000 | 0.28021957 | 0.268324 | 21.11 | 13.31 | 0.00779281 | 41008.1 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.04721467 | 60.00 | 32.22 | 27.78 | 0.000 | 5397.48 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.11 | 0.00779281 | 21.11 | 0.00779281 | 43.4091 | 5397.54 | 0.00 | 5818.65 | 5818.65 | 0.28021957 | 16.60 | 12.95 | 0.00779281 | 36410.2 | 36.97 | 20.11 | 0.00779281 | 57174.8 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 66152.964 | -999.000 | 6.918264 | 0.00189193 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6191 | 1004.8586 | 1.0443 | ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 6.918264 | 7.22496222 | 4197.9300 | 999.8980 | 22.53479169 | 15.03 | 6.70 | 8.33 | 788013.65 | 8.3949 | 8.394744 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | unknown | unknown | unknown | 7/21 14:00:00 | Sensible | 66152.96 | 66152.96 | 1.0000 | 7.22496222 | 6.918264 | 21.77 | 14.15 | 0.00848817 | 43448.5 | 12.80 | 10.81 | 0.00848817 | 34292.3 | 1.89173807 | 6.70 | 15.03 | 8.33 | 0.000 | 66152.96 | 38.10 | 0.00687148 | 18.17 | 0.00000000 | 0.0000 | 21.11 | 0.00848817 | 21.11 | 0.00848817 | 47.2295 | 61286.34 | 0.00 | 53129.03 | 53129.03 | 7.22496222 | 21.77 | 15.58 | 0.00848817 | 43448.5 | 14.57 | 12.81 | 0.00848817 | 36095.0 | |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 31335.121 | 31335.121 | 1.557772 | 0.00027413 | 895.311 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 6.918264 | 7.22496222 | 4197.9300 | 999.8980 | 3.40812534 | 54.44 | 82.22 | 27.78 | 397450.45 | 7.8840 | 8.042701 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 31335.12 | 31335.12 | 1.0000 | 1.62683038 | 1.557772 | 21.11 | 13.33 | 0.00781013 | 41052.2 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.27410535 | 60.00 | 32.22 | 27.78 | 0.000 | 31335.12 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.11 | 0.00781013 | 21.11 | 0.00781013 | 43.5040 | 31335.29 | 0.00 | 33780.33 | 33780.33 | 1.62683038 | 16.60 | 12.97 | 0.00781013 | 36454.0 | 36.97 | 20.13 | 0.00781013 | 57218.5 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 75846.092 | -999.000 | 7.507741 | 0.00216915 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0201 | 1004.8586 | 1.0443 | ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 7.507741 | 7.84057267 | 4197.9300 | 999.8980 | 22.53479169 | 15.03 | 6.70 | 8.33 | 788013.65 | 9.6250 | 9.624792 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | unknown | unknown | unknown | 7/21 15:30:00 | Sensible | 75846.09 | 72841.29 | 1.0000 | 7.84057267 | 7.507741 | 21.77 | 14.33 | 0.00870388 | 43995.7 | 12.80 | 10.82 | 0.00850000 | 34322.2 | 2.16892683 | 6.70 | 15.03 | 8.33 | 0.000 | 75846.09 | 37.71 | 0.00687086 | 18.05 | 0.00000000 | 0.0000 | 21.11 | 0.00870388 | 21.11 | 0.00870388 | 48.4151 | 66502.87 | 0.00 | 55864.22 | 54750.53 | 7.84057267 | 21.77 | 15.77 | 0.00870388 | 43995.7 | 14.93 | 13.11 | 0.00864770 | 36870.7 | |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 31235.484 | 31235.484 | 1.552818 | 0.00027326 | 892.464 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 7.507741 | 7.84057267 | 4197.9300 | 999.8980 | 3.40812534 | 54.44 | 82.22 | 27.78 | 397450.45 | 7.8590 | 8.017128 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 31235.48 | 31235.48 | 1.0000 | 1.62165750 | 1.552818 | 21.11 | 13.33 | 0.00780950 | 41050.6 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.27323376 | 60.00 | 32.22 | 27.78 | 0.000 | 31235.48 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.11 | 0.00780950 | 21.11 | 0.00780950 | 43.5005 | 31235.65 | 0.00 | 33672.91 | 33672.91 | 1.62165750 | 16.60 | 12.97 | 0.00780950 | 36452.4 | 36.97 | 20.13 | 0.00780950 | 57216.9 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10030.149 | -999.000 | 1.029875 | 0.00028686 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7653 | 1004.8586 | 1.0443 | ROOM_5_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.029875 | 1.07553080 | 4197.9300 | 999.8980 | 22.53479169 | 15.03 | 6.70 | 8.33 | 788013.65 | 1.2728 | 1.272816 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | unknown | unknown | unknown | 7/21 10:10:00 | Sensible | 10030.15 | 9896.32 | 1.0000 | 1.07553080 | 1.029875 | 21.77 | 14.22 | 0.00856684 | 43648.0 | 12.80 | 10.82 | 0.00850000 | 34322.2 | 0.28682637 | 6.70 | 15.03 | 8.33 | 0.000 | 10030.15 | 33.48 | 0.00686412 | 16.74 | 0.00000000 | 0.0000 | 21.11 | 0.00856684 | 21.11 | 0.00856684 | 47.6623 | 9122.88 | 0.00 | 7332.27 | 7332.27 | 1.07553080 | 21.77 | 15.65 | 0.00856684 | 43648.0 | 15.09 | 13.10 | 0.00856684 | 36830.6 | |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5391.958 | 5391.958 | 0.268050 | 0.00004717 | 154.061 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | ROOM_5_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.029875 | 1.07553080 | 4197.9300 | 999.8980 | 3.40812534 | 54.44 | 82.22 | 27.78 | 397450.45 | 1.3566 | 1.383939 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 5391.96 | 5391.96 | 1.0000 | 0.27993301 | 0.268050 | 21.11 | 13.31 | 0.00779259 | 41007.5 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.04716639 | 60.00 | 32.22 | 27.78 | 0.000 | 5391.96 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.11 | 0.00779259 | 21.11 | 0.00779259 | 43.4078 | 5392.02 | 0.00 | 5812.70 | 5812.70 | 0.27993301 | 16.60 | 12.95 | 0.00779259 | 36409.6 | 36.97 | 20.11 | 0.00779259 | 57174.2 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9958.933 | -999.000 | 1.022436 | 0.00028482 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7662 | 1004.8586 | 1.0443 | ROOM_6_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.022436 | 1.06776247 | 4197.9300 | 999.8980 | 22.53479169 | 15.03 | 6.70 | 8.33 | 788013.65 | 1.2638 | 1.263779 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | unknown | unknown | unknown | 7/21 10:00:00 | Sensible | 9958.93 | 9825.16 | 1.0000 | 1.06776247 | 1.022436 | 21.77 | 14.22 | 0.00856729 | 43649.1 | 12.80 | 10.82 | 0.00850000 | 34322.2 | 0.28478985 | 6.70 | 15.03 | 8.33 | 0.000 | 9958.93 | 33.16 | 0.00686360 | 16.64 | 0.00000000 | 0.0000 | 21.11 | 0.00856729 | 21.11 | 0.00856729 | 47.6648 | 9056.99 | 0.00 | 7280.40 | 7280.40 | 1.06776247 | 21.77 | 15.65 | 0.00856729 | 43649.1 | 15.09 | 13.10 | 0.00856729 | 36830.7 | |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5385.826 | 5385.826 | 0.267745 | 0.00004712 | 153.886 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | ROOM_6_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.022436 | 1.06776247 | 4197.9300 | 999.8980 | 3.40812534 | 54.44 | 82.22 | 27.78 | 397450.45 | 1.3551 | 1.382365 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 5385.83 | 5385.83 | 1.0000 | 0.27961464 | 0.267745 | 21.11 | 13.31 | 0.00779238 | 41007.0 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.04711275 | 60.00 | 32.22 | 27.78 | 0.000 | 5385.83 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.11 | 0.00779238 | 21.11 | 0.00779238 | 43.4067 | 5385.89 | 0.00 | 5806.09 | 5806.09 | 0.27961464 | 16.60 | 12.95 | 0.00779238 | 36409.1 | 36.97 | 20.11 | 0.00779238 | 57173.7 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12317.363 | 12317.363 | 0.805905 | 0.00010776 | 292.849 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.40812534 | 54.44 | 82.22 | 27.78 | 397450.45 | 3.0991 | 3.161464 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 12317.36 | 12317.36 | 1.0000 | 0.84163218 | 0.805905 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.10774667 | 60.00 | 32.22 | 27.78 | 0.000 | 12317.36 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00784077 | 21.00 | 0.00784077 | 43.9711 | 8628.11 | 0.00 | 12382.79 | 12382.79 | 0.84163218 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 31.03 | 18.38 | 0.00800000 | 51647.6 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3008.200 | -999.000 | 0.309801 | 0.00008603 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7449 | 1004.8586 | 1.0443 | ROOM_1_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.309801 | 0.32353522 | 4197.9300 | 999.8980 | 22.53479169 | 15.03 | 6.70 | 8.33 | 788013.65 | 0.3817 | 0.381738 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | unknown | unknown | unknown | 7/21 16:30:00 | Sensible | 3008.20 | 2974.58 | 1.0000 | 0.32353522 | 0.309801 | 21.77 | 14.21 | 0.00855587 | 43620.1 | 12.80 | 10.82 | 0.00850000 | 34322.2 | 0.08602376 | 6.70 | 15.03 | 8.33 | 0.000 | 3008.20 | 36.80 | 0.00686940 | 17.78 | 0.00000000 | 0.0000 | 21.11 | 0.00855587 | 21.11 | 0.00855587 | 47.6021 | 2744.30 | 0.00 | 2197.72 | 2197.72 | 0.32353522 | 21.77 | 15.64 | 0.00855587 | 43620.1 | 15.12 | 13.10 | 0.00855587 | 36827.3 | |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1682.364 | 1682.364 | 0.083635 | 0.00001472 | 48.068 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | ROOM_1_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.309801 | 0.32353522 | 4197.9300 | 999.8980 | 3.40812534 | 54.44 | 82.22 | 27.78 | 397450.45 | 0.4233 | 0.431808 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1682.36 | 1682.36 | 1.0000 | 0.08734292 | 0.083635 | 21.11 | 13.35 | 0.00783245 | 41108.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.01471656 | 60.00 | 32.22 | 27.78 | 0.000 | 1682.36 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.11 | 0.00783245 | 21.11 | 0.00783245 | 43.6271 | 1682.38 | 0.00 | 1813.64 | 1813.64 | 0.08734292 | 16.60 | 12.99 | 0.00783245 | 36510.5 | 36.97 | 20.14 | 0.00783245 | 57275.1 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2984.790 | -999.000 | 0.307357 | 0.00008536 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7457 | 1004.8586 | 1.0443 | ROOM_2_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.307357 | 0.32098306 | 4197.9300 | 999.8980 | 22.53479169 | 15.03 | 6.70 | 8.33 | 788013.65 | 0.3788 | 0.378767 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | unknown | unknown | unknown | 7/21 16:30:00 | Sensible | 2984.79 | 2951.20 | 1.0000 | 0.32098306 | 0.307357 | 21.77 | 14.21 | 0.00855626 | 43621.1 | 12.80 | 10.82 | 0.00850000 | 34322.2 | 0.08535432 | 6.70 | 15.03 | 8.33 | 0.000 | 2984.79 | 36.80 | 0.00686940 | 17.78 | 0.00000000 | 0.0000 | 21.11 | 0.00855626 | 21.11 | 0.00855626 | 47.6042 | 2722.65 | 0.00 | 2180.66 | 2180.66 | 0.32098306 | 21.77 | 15.64 | 0.00855626 | 43621.1 | 15.12 | 13.10 | 0.00855626 | 36827.4 | |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1681.617 | 1681.617 | 0.083598 | 0.00001471 | 48.047 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | ROOM_2_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.307357 | 0.32098306 | 4197.9300 | 999.8980 | 3.40812534 | 54.44 | 82.22 | 27.78 | 397450.45 | 0.4231 | 0.431616 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1681.62 | 1681.62 | 1.0000 | 0.08730411 | 0.083598 | 21.11 | 13.35 | 0.00783239 | 41108.6 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.01471002 | 60.00 | 32.22 | 27.78 | 0.000 | 1681.62 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.11 | 0.00783239 | 21.11 | 0.00783239 | 43.6268 | 1681.63 | 0.00 | 1812.84 | 1812.84 | 0.08730411 | 16.60 | 12.99 | 0.00783239 | 36510.4 | 36.97 | 20.14 | 0.00783239 | 57275.0 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13681.129 | -999.000 | 1.382860 | 0.00039127 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8735 | 1004.8586 | 1.0443 | ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 1.382860 | 1.44416445 | 4197.9300 | 999.8980 | 22.53479169 | 15.03 | 6.70 | 8.33 | 788013.65 | 1.7362 | 1.736121 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | unknown | unknown | unknown | 7/21 14:10:00 | Sensible | 13681.13 | 13343.51 | 1.0000 | 1.44416445 | 1.382860 | 21.77 | 14.27 | 0.00862505 | 43795.6 | 12.80 | 10.82 | 0.00850000 | 34322.2 | 0.39123134 | 6.70 | 15.03 | 8.33 | 0.000 | 13681.13 | 38.10 | 0.00687148 | 18.17 | 0.00000000 | 0.0000 | 21.11 | 0.00862505 | 21.11 | 0.00862505 | 47.9825 | 12249.35 | 0.00 | 10033.51 | 10033.51 | 1.44416445 | 21.77 | 15.70 | 0.00862505 | 43795.6 | 14.96 | 13.10 | 0.00862505 | 36848.0 | |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8130.642 | 8130.642 | 0.404199 | 0.00007113 | 232.305 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 1.382860 | 1.44416445 | 4197.9300 | 999.8980 | 3.40812534 | 54.44 | 82.22 | 27.78 | 397450.45 | 2.0457 | 2.086870 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 8130.64 | 8130.64 | 1.0000 | 0.42211778 | 0.404199 | 21.11 | 13.36 | 0.00784012 | 41128.3 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.07112315 | 60.00 | 32.22 | 27.78 | 0.000 | 8130.64 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.11 | 0.00784012 | 21.11 | 0.00784012 | 43.6691 | 8130.71 | 0.00 | 8765.10 | 8765.10 | 0.42211778 | 16.60 | 13.00 | 0.00784012 | 36529.9 | 36.97 | 20.15 | 0.00784012 | 57294.5 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11100.021 | 11100.021 | 1.179537 | 0.00009711 | 244.928 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.40812534 | 54.44 | 82.22 | 27.78 | 397450.45 | 2.7928 | 2.849013 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 11100.02 | 11100.02 | 1.0000 | 1.23182819 | 1.179537 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.09709792 | 60.00 | 32.22 | 27.78 | 0.000 | 11100.02 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00787745 | 21.00 | 0.00787745 | 44.1744 | 5700.06 | 0.00 | 11160.49 | 11160.49 | 1.23182819 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 25.48 | 16.49 | 0.00800000 | 45994.8 | |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11478.171 | 11478.171 | 1.235421 | 0.00010042 | 252.906 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.40812534 | 54.44 | 82.22 | 27.78 | 397450.45 | 2.8880 | 2.946071 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | Sensible | 11478.17 | 11478.17 | 1.0000 | 1.29018892 | 1.235421 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.10040581 | 60.00 | 32.22 | 27.78 | 0.000 | 11478.17 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00787997 | 21.00 | 0.00787997 | 44.1887 | 5822.53 | 0.00 | 11540.74 | 11540.74 | 1.29018892 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 25.37 | 16.45 | 0.00800000 | 45879.7 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7142.688 | 7142.688 | 1.204107 | 0.00006249 | 151.268 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.40812534 | 54.44 | 82.22 | 27.78 | 397450.45 | 1.7971 | 1.833295 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | Sensible | 7142.69 | 7142.69 | 1.0000 | 1.25748737 | 1.204107 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.06248098 | 60.00 | 32.22 | 27.78 | 0.000 | 7142.69 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.37 | 0.00664265 | 21.00 | 0.00664265 | 37.3291 | 1645.95 | 0.00 | 7182.62 | 7182.62 | 1.25748737 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 22.20 | 15.30 | 0.00800000 | 42646.6 | |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7968.347 | 7968.347 | 0.411020 | 0.00006971 | 200.458 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.40812534 | 54.44 | 82.22 | 27.78 | 397450.45 | 2.0049 | 2.045214 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 7968.35 | 7968.35 | 1.0000 | 0.42924146 | 0.411020 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.06970346 | 60.00 | 32.22 | 27.78 | 0.000 | 7968.35 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00789900 | 21.00 | 0.00789900 | 44.2937 | 6086.60 | 0.00 | 8009.35 | 8009.35 | 0.42924146 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 34.90 | 19.63 | 0.00800000 | 55594.0 | |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 57348.723 | -999.000 | 2.051317 | 0.00164017 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.6137 | 1004.8586 | 1.0443 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.14218037 | 4197.9300 | 999.8980 | 22.53479169 | 15.03 | 6.70 | 8.33 | 788013.65 | 7.2776 | 7.277631 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 57348.72 | 57348.72 | 1.0000 | 2.14225568 | 2.051317 | 38.10 | 18.17 | 0.00687148 | 55956.2 | 11.79 | 8.78 | 0.00687148 | 29186.0 | 1.63999890 | 6.70 | 15.03 | 8.33 | 2195.006 | 55153.72 | 38.10 | 0.00687148 | 18.17 | 2.05124512 | 99.9965 | 21.11 | 0.00859530 | 21.11 | 0.00860074 | 47.8484 | 179557.30 | 0.00 | 50441.98 | 50441.98 | 2.14225568 | 38.10 | 19.77 | 0.00687148 | 55956.2 | 14.96 | 11.35 | 0.00687148 | 32410.0 | |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 14143.003 | 14143.003 | 0.615395 | 0.00012373 | 240.092 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.14218037 | 4197.9300 | 999.8980 | 3.40812534 | 54.44 | 82.22 | 27.78 | 397450.45 | 3.5584 | 3.630047 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 14143.00 | 14143.00 | 1.0000 | 0.64267671 | 0.615395 | -5.20 | -5.20 | 0.00280840 | 1771.3 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 0.12371654 | 60.00 | 32.22 | 27.78 | 0.000 | 14143.00 | -5.20 | 0.00280840 | -5.20 | 2.05124512 | 333.3216 | 21.11 | 0.00780932 | 21.11 | 0.00780998 | 43.5031 | 95644.78 | 0.00 | 12879.82 | 12879.82 | 0.64267671 | 2.80 | 0.24 | 0.00280840 | 9851.8 | 22.64 | 10.36 | 0.00280840 | 29892.7 | |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 526412.018 | -999.000 | 24.787135 | 0.01505532 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.3513 | 1004.8586 | 1.0443 | VAV WITH REHEAT FAN | Fan:VariableVolume | 24.787135 | 25.88599212 | 4197.9300 | 999.8980 | 22.53479169 | 15.03 | 6.70 | 8.33 | 788013.65 | 66.8024 | 66.802398 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | Sensible | 526412.02 | 526412.02 | 1.0000 | 25.88599212 | 24.787135 | 30.63 | 16.98 | 0.00834411 | 52118.9 | 10.70 | 9.82 | 0.00834411 | 31783.1 | 15.05378127 | 6.70 | 15.03 | 8.33 | 55539.013 | 470873.01 | 38.10 | 0.00687148 | 18.17 | 11.66146000 | 47.0464 | 23.99 | 0.00965247 | 23.99 | 0.00961146 | 44.8139 | 295663.54 | 0.00 | 583338.81 | 540763.11 | 25.88599212 | 30.63 | 18.52 | 0.00834411 | 52118.9 | 10.15 | 10.13 | 0.00769139 | 29584.0 | |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 170897.273 | 170897.273 | 7.436141 | 0.00149508 | 2901.158 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | VAV WITH REHEAT FAN | Fan:VariableVolume | 24.787135 | 25.88599212 | 4197.9300 | 999.8980 | 3.40812534 | 54.44 | 82.22 | 27.78 | 397450.45 | 42.9984 | 43.863744 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:50:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:50:00 | Sensible | 170897.27 | 170897.27 | 1.0000 | 7.76579763 | 7.436141 | -5.20 | -5.20 | 0.00280840 | 1771.3 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 1.49493138 | 60.00 | 32.22 | 27.78 | 0.000 | 170897.27 | -5.20 | 0.00280840 | -5.20 | 11.66146000 | 156.8214 | 18.54 | 0.00719261 | 21.37 | 0.00689656 | 37.8614 | 55098.98 | 0.00 | 155633.59 | 155633.59 | 7.76579763 | 2.80 | 0.24 | 0.00280840 | 9851.8 | 22.64 | 10.36 | 0.00280840 | 29892.7 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:03
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - | |||
VAV WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 24.79 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | VAV WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000610 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LAUNDRY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CAFE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001448 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_3 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
KITCHEN_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003556 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 1997.33 | 6353.50 | 948.00 |
RETAIL_1_FLR_1 | 3245.33 | 5330.83 | 975.67 |
RETAIL_2_FLR_1 | 2802.33 | 5713.17 | 1108.67 |
MECH_FLR_1 | 1991.50 | 6337.00 | 559.83 |
STORAGE_FLR_1 | 1790.17 | 6609.17 | 675.17 |
LAUNDRY_FLR_1 | 8020.50 | 3746.33 | 3451.83 |
CAFE_FLR_1 | 4485.50 | 4404.33 | 1881.33 |
LOBBY_FLR_1 | 3399.67 | 5243.50 | 1697.33 |
ROOM_1_FLR_3 | 605.83 | 7876.83 | 319.33 |
ROOM_2_FLR_3 | 1395.00 | 7727.83 | 1055.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 458.00 | 8729.33 | 453.50 |
ROOM_5_FLR_3 | 500.33 | 7810.00 | 333.33 |
ROOM_6_FLR_3 | 1451.67 | 7615.50 | 1078.83 |
CORRIDOR_FLR_3 | 1948.83 | 7257.33 | 1296.50 |
ROOM_1_FLR_6 | 1425.67 | 7697.83 | 928.00 |
ROOM_2_FLR_6 | 2453.17 | 7605.67 | 1922.83 |
ROOM_3_MULT9_FLR_6 | 320.50 | 7818.17 | 136.17 |
BANQUET_FLR_6 | 4414.33 | 3399.83 | 1801.00 |
DINING_FLR_6 | 4835.33 | 2253.67 | 1694.17 |
KITCHEN_FLR_6 | 8572.17 | 6691.33 | 6689.17 |
CORRIDOR_FLR_6 | 2522.67 | 6277.67 | 872.50 |
Facility | 8755.83 | 8760.00 | 7682.17 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 237.67 | 0.00 | 237.67 |
ROOM_2_FLR_3 | 0.00 | 232.67 | 0.00 | 232.67 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 100.67 | 0.00 | 100.67 |
ROOM_5_FLR_3 | 0.00 | 163.67 | 0.00 | 163.67 |
ROOM_6_FLR_3 | 0.00 | 246.17 | 0.00 | 246.17 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 278.33 | 0.00 | 278.33 |
ROOM_2_FLR_6 | 0.00 | 263.33 | 0.00 | 263.33 |
ROOM_3_MULT9_FLR_6 | 0.00 | 158.83 | 0.00 | 158.83 |
BANQUET_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 551.67 | 0.00 | 551.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:03
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.80 | 106.50 | 4826.41 | 1.038 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 2.268 | 0.061 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.28 | 12.54 | 307.76 | 1.474 | 0.020 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.577 | 0.023 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.588 | 0.023 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 23.186 | 0.065 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.58 | 142.30 | 748.35 | 3.735 | 0.048 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.14 | 422.44 | 5183.56 | 1.818 | 0.020 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.355 | 0.079 | 0.000 | 0.055 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.355 | 0.079 | 0.000 | 0.059 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.403 | 0.035 | 0.000 | 0.090 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.355 | 0.079 | 0.000 | 0.056 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.355 | 0.079 | 0.000 | 0.056 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 0.570 | 0.010 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.355 | 0.079 | 0.000 | 0.066 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.355 | 0.079 | 0.000 | 0.068 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.403 | 0.064 | 0.000 | 0.105 |
BANQUET_FLR_6 | 145.01 | 249.90 | 1010.89 | 5.122 | 0.023 | 0.000 | 0.000 |
DINING_FLR_6 | 145.01 | 249.90 | 1010.89 | 5.523 | 0.023 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 23.152 | 0.065 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 1.128 | 0.016 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.80 | 106.50 | 4826.41 | 0.492 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 1.421 | 0.001 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.28 | 12.54 | 307.76 | 0.999 | 0.000 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.445 | 0.000 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.420 | 0.000 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 11.621 | 0.001 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.58 | 142.30 | 748.35 | 2.594 | 0.001 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.14 | 422.44 | 5183.56 | 1.188 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 0.331 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.000 | 0.001 | 0.000 | 0.000 |
BANQUET_FLR_6 | 145.01 | 249.90 | 1010.89 | 3.690 | 0.000 | 0.000 | 0.000 |
DINING_FLR_6 | 145.01 | 249.90 | 1010.89 | 3.881 | 0.000 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 10.144 | 0.001 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 0.748 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:22:03
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | VAV WITH REHEAT | 61.80 | 106.50 | 4826.41 | 1978.83 | 0.0000 | 0.854 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 6.28 | 10.83 | 265.76 | 67.07 | 0.0000 | 0.079 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 7.28 | 12.54 | 307.76 | 77.67 | 0.0000 | 0.092 |
MECH_FLR_1 | VAV WITH REHEAT | 1.54 | 2.65 | 650.80 | 164.24 | 0.0000 | 0.000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 1.18 | 2.04 | 375.47 | 94.76 | 0.0000 | 0.058 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 4.87 | 8.40 | 309.22 | 78.04 | 0.0000 | 0.000 |
CAFE_FLR_1 | VAV WITH REHEAT | 82.58 | 142.30 | 748.35 | 188.86 | 0.0000 | 0.676 |
LOBBY_FLR_1 | VAV WITH REHEAT | 245.14 | 422.44 | 5183.56 | 1308.19 | 0.0000 | 1.894 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 1.50 | 74.75 | 24.52 | 0.0000 | 0.837 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.837 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 12.16 | 20.96 | 1186.91 | 389.40 | 0.0000 | 0.475 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.015 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.015 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.099 |
BANQUET_FLR_6 | VAV WITH REHEAT | 145.01 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
DINING_FLR_6 | VAV WITH REHEAT | 145.01 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 12.90 | 22.24 | 314.87 | 103.30 | 0.0000 | 0.367 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 12.87 | 22.18 | 1256.16 | 412.12 | 0.0000 | 0.126 |
Total Facility | 873.39 | 1604.23 | 35184.81 | 11345.29 | 0.0000 | 137.584 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 43082714.80 | 0.00 | 43082714.80 | 0.00 | 43082714.80 | 26946214.98 | 123.59 | 17.41 | 8618.99 | 0.00 |
RETAIL_1_FLR_1 | 5195459.01 | 0.00 | 5195459.01 | 139421.75 | 5334880.76 | 2498216.28 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_2_FLR_1 | 3899493.17 | 0.00 | 3899493.17 | 53816.97 | 3953310.14 | 2892943.94 | 6.33 | 2.83 | 8750.83 | 0.00 |
MECH_FLR_1 | 3238952.91 | 0.00 | 3238952.91 | 127191.35 | 3366144.25 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
STORAGE_FLR_1 | 1907451.11 | 0.00 | 1907451.11 | 73382.40 | 1980833.51 | 1821682.01 | 2276.75 | 777.38 | 5705.87 | 0.00 |
LAUNDRY_FLR_1 | 61730953.79 | 0.00 | 61730953.79 | 173673.29 | 61904627.08 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
CAFE_FLR_1 | 23988143.36 | 0.00 | 23988143.36 | 308199.66 | 24296343.03 | 21330615.53 | 2992.61 | 216.86 | 5550.52 | 0.00 |
LOBBY_FLR_1 | 80879819.96 | 0.00 | 80879819.96 | 880596.83 | 81760416.79 | 59728886.00 | 13.49 | 6.19 | 8740.32 | 0.00 |
ROOM_1_FLR_3 | 1460156.71 | 57041.65 | 1517198.36 | 80924.37 | 1598122.73 | 1946875.62 | 2190.00 | 5876.83 | 693.17 | 0.00 |
ROOM_2_FLR_3 | 1459985.63 | 60145.74 | 1520131.37 | 80918.19 | 1601049.57 | 1946647.51 | 2190.00 | 5879.39 | 690.61 | 0.00 |
ROOM_3_MULT19_FLR_3 | 1099911.97 | 0.00 | 1099911.97 | 22578.81 | 1122490.78 | 26397887.27 | 8395.00 | 365.00 | 0.00 | 365.00 |
ROOM_4_MULT19_FLR_3 | 19803829.30 | 58068.85 | 19861898.15 | 22584.98 | 19884483.13 | 26405105.73 | 2190.00 | 5928.62 | 641.38 | 0.00 |
ROOM_5_FLR_3 | 1460156.71 | 57198.95 | 1517355.66 | 80924.37 | 1598280.03 | 1946875.62 | 2190.00 | 5876.83 | 693.17 | 0.00 |
ROOM_6_FLR_3 | 1459985.63 | 57507.16 | 1517492.80 | 80918.19 | 1598410.99 | 1946647.51 | 2190.00 | 5880.58 | 689.42 | 0.00 |
CORRIDOR_FLR_3 | 23331359.52 | 0.00 | 23331359.52 | 97853.84 | 23429213.36 | 14972100.18 | 8.94 | 9.56 | 8741.50 | 0.00 |
ROOM_1_FLR_6 | 365039.18 | 67676.02 | 432715.20 | 80940.93 | 513656.13 | 486718.90 | 2055.03 | 5876.59 | 828.38 | 0.00 |
ROOM_2_FLR_6 | 364996.41 | 69483.19 | 434479.60 | 80934.75 | 515414.35 | 486661.88 | 2053.78 | 5881.92 | 824.30 | 0.00 |
ROOM_3_MULT9_FLR_6 | 2345190.31 | 67738.35 | 2412928.66 | 41412.21 | 2454340.87 | 3126920.42 | 2190.00 | 5874.00 | 696.00 | 0.00 |
BANQUET_FLR_6 | 44386202.78 | 0.00 | 44386202.78 | 197637.40 | 44583840.19 | 37458366.31 | 763.88 | 2204.04 | 5792.08 | 0.00 |
DINING_FLR_6 | 47861027.70 | 0.00 | 47861027.70 | 197637.40 | 48058665.10 | 37458366.31 | 61.13 | 54.69 | 8644.18 | 0.00 |
KITCHEN_FLR_6 | 62560461.04 | 0.00 | 62560461.04 | 176931.30 | 62737392.34 | 11584760.86 | 0.00 | 0.00 | 8760.00 | 0.00 |
CORRIDOR_FLR_6 | 12226026.02 | 0.00 | 12226026.02 | 173170.48 | 12399196.50 | 3961413.96 | 0.00 | 0.00 | 8760.00 | 0.00 |
Total Facility | 0.21E+10 | 6087611.00 | 0.21E+10 | 8154847.90 | 0.21E+10 | 0.43E+10 | 8760.00 | 7504.19 | 8760.00 | 365.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 1.3661 | 0.0000 | 1.3661 | 0.0000 | 1.3661 | 0.8545 | 123.59 | 17.41 | 8618.99 |
RETAIL_1_FLR_1 | 0.1647 | 0.0000 | 0.1647 | 0.0044 | 0.1692 | 0.0792 | 0.00 | 0.00 | 8760.00 |
RETAIL_2_FLR_1 | 0.1237 | 0.0000 | 0.1237 | 0.0017 | 0.1254 | 0.0917 | 6.33 | 2.83 | 8750.83 |
MECH_FLR_1 | 0.1027 | 0.0000 | 0.1027 | 0.0040 | 0.1067 | 0.0000 | 0.00 | 0.00 | 8760.00 |
STORAGE_FLR_1 | 0.0605 | 0.0000 | 0.0605 | 0.0023 | 0.0628 | 0.0578 | 2276.75 | 777.38 | 5705.87 |
LAUNDRY_FLR_1 | 1.9575 | 0.0000 | 1.9575 | 0.0055 | 1.9630 | 0.0000 | 0.00 | 0.00 | 8760.00 |
CAFE_FLR_1 | 0.7607 | 0.0000 | 0.7607 | 0.0098 | 0.7704 | 0.6764 | 2992.61 | 216.86 | 5550.52 |
LOBBY_FLR_1 | 2.5647 | 0.0000 | 2.5647 | 0.0279 | 2.5926 | 1.8940 | 13.49 | 6.19 | 8740.32 |
ROOM_1_FLR_3 | 0.0463 | 0.0018 | 0.0481 | 0.0026 | 0.0507 | 0.0617 | 2190.00 | 5876.83 | 693.17 |
ROOM_2_FLR_3 | 0.0463 | 0.0019 | 0.0482 | 0.0026 | 0.0508 | 0.0617 | 2190.00 | 5879.39 | 690.61 |
ROOM_4_MULT19_FLR_3 | 0.6280 | 0.0018 | 0.6298 | 0.0007 | 0.6305 | 0.8373 | 2190.00 | 5928.62 | 641.38 |
ROOM_5_FLR_3 | 0.0463 | 0.0018 | 0.0481 | 0.0026 | 0.0507 | 0.0617 | 2190.00 | 5876.83 | 693.17 |
ROOM_6_FLR_3 | 0.0463 | 0.0018 | 0.0481 | 0.0026 | 0.0507 | 0.0617 | 2190.00 | 5880.58 | 689.42 |
CORRIDOR_FLR_3 | 0.7398 | 0.0000 | 0.7398 | 0.0031 | 0.7429 | 0.4748 | 8.94 | 9.56 | 8741.50 |
ROOM_1_FLR_6 | 0.0116 | 0.0021 | 0.0137 | 0.0026 | 0.0163 | 0.0154 | 2055.03 | 5876.59 | 828.38 |
ROOM_2_FLR_6 | 0.0116 | 0.0022 | 0.0138 | 0.0026 | 0.0163 | 0.0154 | 2053.78 | 5881.92 | 824.30 |
ROOM_3_MULT9_FLR_6 | 0.0744 | 0.0021 | 0.0765 | 0.0013 | 0.0778 | 0.0992 | 2190.00 | 5874.00 | 696.00 |
BANQUET_FLR_6 | 1.4075 | 0.0000 | 1.4075 | 0.0063 | 1.4137 | 1.1878 | 763.88 | 2204.04 | 5792.08 |
DINING_FLR_6 | 1.5177 | 0.0000 | 1.5177 | 0.0063 | 1.5239 | 1.1878 | 61.13 | 54.69 | 8644.18 |
KITCHEN_FLR_6 | 1.9838 | 0.0000 | 1.9838 | 0.0056 | 1.9894 | 0.3674 | 0.00 | 0.00 | 8760.00 |
CORRIDOR_FLR_6 | 0.3877 | 0.0000 | 0.3877 | 0.0055 | 0.3932 | 0.1256 | 0.00 | 0.00 | 8760.00 |
Total Facility | 64.5158 | 0.1930 | 64.7089 | 0.2042 | 64.9130 | 73.9670 | 8760.00 | 7504.19 | 8760.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
FLR_3_DOAS | 32521733.86 | 494859.90 | 33016593.76 | 64690340.46 | 8759.83 | 0.17 | 0.00 | 0.00 |
VAV WITH REHEAT | 0.45E+09 | 0.00 | 0.45E+09 | 0.22E+09 | 0.00 | 0.00 | 8760.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
FLR_3_DOAS | 1.0313 | 0.0157 | 1.0469 | 2.0513 | 8759.83 | 0.17 | 0.00 |
VAV WITH REHEAT | 14.3276 | 0.0000 | 14.3276 | 6.9969 | 0.00 | 0.00 | 8760.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
FLR_3_DOAS | 0.00 | 0.00 | 0.00 | 0.00 | 6935.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
VAV WITH REHEAT | 0.00 | 0.00 | 5090.27 | 0.00 | 0.00 | 0.00 | 3669.73 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
FLR_3_DOAS | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.3026 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
VAV WITH REHEAT | 0.0000 | 0.0000 | 15.0833 | 0.0000 | 0.0000 | 0.0000 | 13.2831 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:03
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1333 |
Defaulted Fields | 1182 |
Fields with Defaults | 4000 |
Autosized Fields | 349 |
Autosizable Fields | 402 |
Autocalculated Fields | 280 |
Autocalculatable Fields | 539 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:22:03
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 5526.15 | 70693.99 | 31-MAR-01:20 | 386181.05 | 21-JUL-21:00 |
Electricity:Building | 2448.45 | 31501.02 | 02-JAN-02:10 | 151313.73 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 304.40 | 3493.55 | 02-JAN-02:10 | 22822.84 | 02-JAN-20:10 |
Electricity:SpaceType:GENERAL | 2441.36 | 31359.87 | 02-JAN-02:10 | 151072.40 | 02-JAN-20:10 |
InteriorLights:Electricity | 783.18 | 7157.90 | 02-JAN-02:10 | 64632.59 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 161.29 | 1465.65 | 02-JAN-02:10 | 13190.31 | 02-JAN-20:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 783.18 | 7157.90 | 02-JAN-02:10 | 64632.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 783.18 | 7157.90 | 02-JAN-02:10 | 64632.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 161.29 | 1465.65 | 02-JAN-02:10 | 13190.31 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 783.18 | 7157.90 | 02-JAN-02:10 | 64632.59 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 17.49 | 210.74 | 02-JAN-02:10 | 1283.20 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 7.31 | 66.40 | 02-JAN-02:10 | 597.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 7.31 | 66.40 | 02-JAN-02:10 | 597.59 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 20.26 | 244.03 | 02-JAN-02:10 | 1485.95 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 8.46 | 76.89 | 02-JAN-02:10 | 692.02 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 8.46 | 76.89 | 02-JAN-02:10 | 692.02 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 20.84 | 252.75 | 02-JAN-02:10 | 1523.62 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.37 | 76.02 | 02-JAN-02:10 | 684.18 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.37 | 76.02 | 02-JAN-02:10 | 684.18 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 6.68 | 78.96 | 02-JAN-02:10 | 493.99 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 3.08 | 27.98 | 02-JAN-02:10 | 251.84 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 3.08 | 27.98 | 02-JAN-02:10 | 251.84 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 71.91 | 998.82 | 02-JAN-02:10 | 4897.88 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 3.98 | 36.12 | 02-JAN-02:10 | 325.08 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 3.98 | 36.12 | 02-JAN-02:10 | 325.08 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 28.61 | 388.01 | 01-JAN-13:10 | 2666.80 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 14.27 | 83.19 | 01-JAN-13:10 | 1701.53 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 | 14.27 | 83.19 | 01-JAN-13:10 | 1701.53 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 259.17 | 3167.50 | 02-JAN-02:10 | 19534.01 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 110.17 | 1056.09 | 02-JAN-02:10 | 9504.80 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 110.17 | 1056.09 | 02-JAN-02:10 | 9504.80 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 19.72 | 257.38 | 01-JAN-02:10 | 1438.51 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 19.72 | 257.35 | 01-JAN-02:10 | 1438.34 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 305.38 | 4267.82 | 01-JAN-02:10 | 22404.45 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 110.39 | 934.58 | 01-JAN-02:10 | 8496.21 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 110.39 | 934.58 | 01-JAN-02:10 | 8496.21 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 305.47 | 4268.99 | 01-JAN-02:10 | 22410.58 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 110.42 | 934.84 | 01-JAN-02:10 | 8498.53 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 110.42 | 934.84 | 01-JAN-02:10 | 8498.53 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 19.72 | 257.38 | 01-JAN-02:10 | 1438.51 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 19.72 | 257.35 | 01-JAN-02:10 | 1438.34 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 4.93 | 64.34 | 01-JAN-02:10 | 359.63 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 2.31 | 19.57 | 01-JAN-02:10 | 177.88 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 2.31 | 19.57 | 01-JAN-02:10 | 177.88 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 4.93 | 64.34 | 01-JAN-02:10 | 359.59 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 2.31 | 19.56 | 01-JAN-02:10 | 177.86 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 2.31 | 19.56 | 01-JAN-02:10 | 177.86 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 36.17 | 505.54 | 01-JAN-02:10 | 2653.88 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 13.08 | 110.70 | 01-JAN-02:10 | 1006.40 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 13.08 | 110.70 | 01-JAN-02:10 | 1006.40 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 207.01 | 2581.30 | 02-JAN-02:10 | 9735.93 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 31.15 | 332.00 | 02-JAN-02:10 | 2988.03 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 31.15 | 332.00 | 02-JAN-02:10 | 2988.03 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 207.01 | 2581.30 | 02-JAN-02:10 | 9735.93 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 31.15 | 332.00 | 02-JAN-02:10 | 2988.03 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 | 31.15 | 332.00 | 02-JAN-02:10 | 2988.03 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 453.81 | 6249.79 | 02-JAN-02:10 | 18934.39 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 12.97 | 117.87 | 02-JAN-02:10 | 1060.81 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 12.97 | 117.87 | 02-JAN-02:10 | 1060.81 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1658.18 | 24201.97 | 02-JAN-02:10 | 89171.45 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 1658.18 | 24201.97 | 02-JAN-02:10 | 89171.45 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 433.74 | 5990.78 | 01-JAN-00:10 | 16487.34 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 410.33 | 5248.28 | 01-JAN-00:10 | 15744.84 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
Refrigeration:Electricity | 61.76 | 1114.40 | 21-APR-22:30 | 3261.47 | 15-AUG-06:20 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
Electricity:Plant | 1333.12 | 2771.70 | 18-MAR-00:20 | 168536.77 | 21-JUL-21:00 |
LowTempRefrigeration:Refrigeration:Electricity | 20.48 | 0.00 | 01-JAN-11:10 | 1892.44 | 02-JUL-10:50 |
MedTempRefrigeration:Refrigeration:Electricity | 34.19 | 978.67 | 20-DEC-03:50 | 1201.23 | 16-OCT-13:40 |
Fans:Electricity | 602.61 | 11259.66 | 15-JAN-15:00 | 50113.58 | 07-AUG-21:10 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 758.57 | 11798.96 | 15-JAN-15:00 | 60894.33 | 07-AUG-21:10 |
ExteriorEquipment:Electricity | 813.77 | 9999.82 | 02-JAN-02:20 | 49607.07 | 02-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 21.77 | 381.02 | 02-JAN-02:20 | 1291.59 | 02-JAN-21:10 |
ElectricityPurchased:Facility | 5526.15 | 70693.99 | 31-MAR-01:20 | 386181.05 | 21-JUL-21:00 |
ElectricityPurchased:Plant | 5526.15 | 70693.99 | 31-MAR-01:20 | 386181.05 | 21-JUL-21:00 |
Cogeneration:ElectricityPurchased | 5526.15 | 70693.99 | 31-MAR-01:20 | 386181.05 | 21-JUL-21:00 |
General:Cogeneration:ElectricityPurchased | 5526.15 | 70693.99 | 31-MAR-01:20 | 386181.05 | 21-JUL-21:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 5526.15 | 70693.99 | 31-MAR-01:20 | 386181.05 | 21-JUL-21:00 |
ElectricityNet:Plant | 5526.15 | 70693.99 | 31-MAR-01:20 | 386181.05 | 21-JUL-21:00 |
Cogeneration:ElectricityNet | 5526.15 | 70693.99 | 31-MAR-01:20 | 386181.05 | 21-JUL-21:00 |
General:Cogeneration:ElectricityNet | 5526.15 | 70693.99 | 31-MAR-01:20 | 386181.05 | 21-JUL-21:00 |
General:Fans:Electricity | 602.61 | 11259.66 | 15-JAN-15:00 | 50113.58 | 07-AUG-21:10 |
ExteriorLights:Electricity | 194.01 | 0.00 | 01-JAN-07:20 | 12338.45 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 194.01 | 0.00 | 01-JAN-07:20 | 12338.45 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 789.09 | 9600.00 | 01-JAN-00:10 | 48128.80 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 2.91 | 18.80 | 01-JAN-00:10 | 188.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 134.18 | 0.00 | 01-JAN-08:10 | 9938.94 | 14-JUN-08:20 |
General:HeatRecovery:Electricity | 134.18 | 0.00 | 01-JAN-08:10 | 9938.94 | 14-JUN-08:20 |
WaterSystems:Electricity | 94.78 | 1222.48 | 02-OCT-00:50 | 4751.13 | 14-MAR-06:50 |
Water Heater:WaterSystems:Electricity | 94.78 | 1222.48 | 02-OCT-00:50 | 4751.13 | 14-MAR-06:50 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 1098.88 | 0.00 | 01-JAN-03:40 | 158737.09 | 21-JUL-21:00 |
General:Cooling:Electricity | 1098.88 | 0.00 | 01-JAN-03:40 | 158737.09 | 21-JUL-21:00 |
Pumps:Electricity | 84.80 | 48.04 | 27-MAR-08:00 | 4073.02 | 16-JUN-20:30 |
General:Pumps:Electricity | 84.80 | 48.04 | 27-MAR-08:00 | 4073.02 | 16-JUN-20:30 |
WIRED_LTG_ELECTRICITY | 27.57 | 0.00 | 01-JAN-00:10 | 2275.07 | 02-JAN-20:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 4922.12 | 23535.48 | 02-AUG-02:20 | 535667.15 | 08-FEB-19:00 |
NaturalGas:Building | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Laundry:InteriorEquipment:NaturalGas | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
NaturalGas:Plant | 3133.28 | 10173.58 | 02-AUG-02:20 | 431418.83 | 08-FEB-19:00 |
WaterSystems:NaturalGas | 2388.61 | 10173.58 | 02-AUG-02:20 | 236198.06 | 01-FEB-21:50 |
Water Heater:WaterSystems:NaturalGas | 2388.61 | 10173.58 | 02-AUG-02:20 | 236198.06 | 01-FEB-21:50 |
Heating:NaturalGas | 744.67 | 0.00 | 01-JAN-11:40 | 215373.04 | 26-JAN-11:50 |
Boiler:Heating:NaturalGas | 744.67 | 0.00 | 01-JAN-11:40 | 215373.04 | 26-JAN-11:50 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 4235.69 | 0.00 | 01-JAN-03:40 | 603260.80 | 21-JUL-21:00 |
PlantLoopCoolingDemand:HVAC | 4235.69 | 0.00 | 01-JAN-03:40 | 603260.80 | 21-JUL-21:00 |
CoolingCoils:PlantLoopCoolingDemand | 4235.69 | 0.00 | 01-JAN-03:40 | 603260.80 | 21-JUL-21:00 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 21-FEB-21:40 |
Water:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 21-FEB-21:40 |
WaterSystems:Water | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 21-FEB-21:40 |
Water Heater:WaterSystems:Water | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:10 |
MainsWater:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 21-FEB-21:40 |
MainsWater:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 21-FEB-21:40 |
WaterSystems:MainsWater | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 21-FEB-21:40 |
Water Heater:WaterSystems:MainsWater | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:10 |
WaterUse:WaterSystems:Water | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 21-APR-06:30 |
WaterUse:WaterSystems:MainsWater | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 21-APR-06:30 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 22180.44 | 124463.04 | 24-MAR-13:40 | 2306948.90 | 21-JUL-21:00 |
EnergyTransfer:Building | 5486.25 | 87469.31 | 26-DEC-15:00 | 338669.02 | 07-AUG-18:20 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 738.49 | 11021.99 | 19-DEC-04:00 | 36168.49 | 02-JUL-10:40 |
Refrigeration:EnergyTransfer | 182.03 | 4015.92 | 21-APR-22:30 | 10358.67 | 15-AUG-06:20 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 91.01 | 2007.96 | 21-APR-22:30 | 5179.33 | 15-AUG-06:20 |
General:Refrigeration:EnergyTransfer | 91.01 | 2007.96 | 21-APR-22:30 | 5179.33 | 15-AUG-06:20 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 91.01 | 2007.96 | 21-APR-22:30 | 5179.33 | 15-AUG-06:20 |
EnergyTransfer:Plant | 10943.20 | 17544.08 | 30-MAR-00:20 | 1396249.29 | 21-JUL-21:00 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 21.57 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 69.45 | 1886.02 | 20-DEC-03:50 | 2553.68 | 16-OCT-13:40 |
EnergyTransfer:Zone:BASEMENT | 414.83 | 8643.41 | 26-MAR-15:00 | 24615.22 | 22-SEP-21:00 |
Heating:EnergyTransfer | 31.06 | 0.00 | 01-JAN-08:10 | 37038.65 | 26-DEC-16:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 31.06 | 0.00 | 01-JAN-08:10 | 37038.65 | 26-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 5364.18 | 83773.59 | 26-DEC-15:00 | 335066.75 | 07-AUG-18:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 414.83 | 8643.41 | 26-MAR-15:00 | 24615.22 | 22-SEP-21:00 |
General:Cooling:EnergyTransfer | 5364.18 | 83773.59 | 26-DEC-15:00 | 335066.75 | 07-AUG-18:20 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 414.83 | 8643.41 | 26-MAR-15:00 | 24615.22 | 22-SEP-21:00 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 46.53 | 1.66 | 28-NOV-03:20 | 3607.01 | 18-OCT-13:00 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.01 | 0.00 | 01-JAN-00:10 | 567.02 | 27-DEC-07:30 |
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.01 | 0.00 | 01-JAN-00:10 | 567.02 | 27-DEC-07:30 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 46.52 | 0.00 | 26-JAN-07:10 | 3607.01 | 18-OCT-13:00 |
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 46.52 | 0.00 | 26-JAN-07:10 | 3607.01 | 18-OCT-13:00 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 38.31 | 768.09 | 26-DEC-12:00 | 2330.86 | 15-JUN-21:00 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 38.31 | 768.09 | 26-DEC-12:00 | 2330.86 | 15-JUN-21:00 |
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 38.31 | 768.09 | 26-DEC-12:00 | 2330.86 | 15-JUN-21:00 |
EnergyTransfer:Zone:MECH_FLR_1 | 29.45 | 367.74 | 27-DEC-11:00 | 2087.29 | 15-JUN-20:00 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 29.45 | 367.74 | 27-DEC-11:00 | 2087.29 | 15-JUN-20:00 |
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 29.45 | 367.74 | 27-DEC-11:00 | 2087.29 | 15-JUN-20:00 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 16.60 | 85.96 | 27-DEC-05:00 | 1033.81 | 15-JUN-18:40 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 16.60 | 85.96 | 27-DEC-05:00 | 1033.81 | 15-JUN-18:40 |
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 16.60 | 85.96 | 27-DEC-05:00 | 1033.81 | 15-JUN-18:40 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 609.34 | 10113.60 | 27-DEC-05:00 | 39336.58 | 15-JUN-20:00 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 609.34 | 10113.60 | 27-DEC-05:00 | 39336.58 | 15-JUN-20:00 |
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 609.34 | 10113.60 | 27-DEC-05:00 | 39336.58 | 15-JUN-20:00 |
EnergyTransfer:Zone:CAFE_FLR_1 | 239.76 | 2646.37 | 26-DEC-11:30 | 12786.04 | 11-NOV-11:00 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 239.76 | 2646.37 | 26-DEC-11:30 | 12786.04 | 11-NOV-11:00 |
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 239.76 | 2646.37 | 26-DEC-11:30 | 12786.04 | 11-NOV-11:00 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 811.27 | 15945.34 | 26-DEC-15:00 | 43572.45 | 07-AUG-21:10 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 811.27 | 15945.34 | 26-DEC-15:00 | 43572.45 | 07-AUG-21:10 |
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 811.27 | 15945.34 | 26-DEC-15:00 | 43572.45 | 07-AUG-21:10 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 73.81 | 0.00 | 01-JAN-08:10 | 8674.21 | 14-JUN-15:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 3.31 | 0.00 | 01-JAN-00:10 | 3754.95 | 26-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 3.31 | 0.00 | 01-JAN-00:10 | 3754.95 | 26-DEC-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 70.49 | 0.00 | 01-JAN-03:20 | 8674.21 | 14-JUN-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 70.49 | 0.00 | 01-JAN-03:20 | 8674.21 | 14-JUN-15:10 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 62.24 | 0.00 | 01-JAN-08:10 | 8719.02 | 14-JUN-16:30 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 5.98 | 0.00 | 01-JAN-08:10 | 3921.06 | 27-DEC-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 5.98 | 0.00 | 01-JAN-08:10 | 3921.06 | 27-DEC-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 56.26 | 0.00 | 01-JAN-00:10 | 8719.02 | 14-JUN-16:30 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 56.26 | 0.00 | 01-JAN-00:10 | 8719.02 | 14-JUN-16:30 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 395.98 | 0.00 | 01-JAN-01:00 | 44050.87 | 22-OCT-13:20 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 395.98 | 0.00 | 01-JAN-01:00 | 44050.87 | 22-OCT-13:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 395.98 | 0.00 | 01-JAN-01:00 | 44050.87 | 22-OCT-13:20 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 460.39 | 0.00 | 01-JAN-08:10 | 59770.61 | 14-JUN-18:20 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 5.19 | 0.00 | 01-JAN-00:10 | 17257.24 | 22-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 5.19 | 0.00 | 01-JAN-00:10 | 17257.24 | 22-DEC-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 455.19 | 0.00 | 01-JAN-08:10 | 59770.61 | 14-JUN-18:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 455.19 | 0.00 | 01-JAN-08:10 | 59770.61 | 14-JUN-18:20 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 75.14 | 0.00 | 01-JAN-08:10 | 7745.22 | 17-JUN-08:10 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 3.45 | 0.00 | 01-JAN-00:10 | 3768.90 | 26-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 3.45 | 0.00 | 01-JAN-00:10 | 3768.90 | 26-DEC-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 71.69 | 0.00 | 01-JAN-00:20 | 7745.22 | 17-JUN-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 71.69 | 0.00 | 01-JAN-00:20 | 7745.22 | 17-JUN-08:10 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 62.67 | 0.00 | 01-JAN-08:10 | 8391.92 | 14-JUN-08:20 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 5.97 | 0.00 | 01-JAN-08:10 | 3855.22 | 26-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 5.97 | 0.00 | 01-JAN-08:10 | 3855.22 | 26-DEC-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 56.70 | 0.00 | 01-JAN-00:10 | 8391.92 | 14-JUN-08:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 56.70 | 0.00 | 01-JAN-00:10 | 8391.92 | 14-JUN-08:20 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 205.99 | 338.88 | 27-DEC-07:10 | 12695.61 | 15-JUN-18:40 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 205.99 | 338.88 | 27-DEC-07:10 | 12695.61 | 15-JUN-18:40 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 205.99 | 338.88 | 27-DEC-07:10 | 12695.61 | 15-JUN-18:40 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 19.07 | 0.00 | 01-JAN-08:10 | 2327.44 | 14-JUN-16:30 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 1.88 | 0.00 | 01-JAN-08:10 | 1123.81 | 26-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 1.88 | 0.00 | 01-JAN-08:10 | 1123.81 | 26-DEC-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 17.19 | 0.00 | 01-JAN-00:10 | 2327.44 | 14-JUN-16:30 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 17.19 | 0.00 | 01-JAN-00:10 | 2327.44 | 14-JUN-16:30 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 16.92 | 0.00 | 01-JAN-08:10 | 2337.38 | 14-JUN-16:30 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 2.93 | 0.00 | 01-JAN-08:10 | 1249.84 | 26-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 2.93 | 0.00 | 01-JAN-08:10 | 1249.84 | 26-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 13.99 | 0.00 | 01-JAN-00:10 | 2337.38 | 14-JUN-16:30 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 13.99 | 0.00 | 01-JAN-00:10 | 2337.38 | 14-JUN-16:30 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 109.26 | 0.00 | 01-JAN-08:10 | 10975.36 | 22-OCT-15:10 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 2.32 | 0.00 | 01-JAN-00:10 | 4191.47 | 27-DEC-06:00 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 2.32 | 0.00 | 01-JAN-00:10 | 4191.47 | 27-DEC-06:00 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 106.94 | 0.00 | 01-JAN-08:10 | 10975.36 | 22-OCT-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 106.94 | 0.00 | 01-JAN-08:10 | 10975.36 | 22-OCT-15:10 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 457.98 | 8506.36 | 26-DEC-12:00 | 23785.66 | 15-JUN-21:20 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 457.98 | 8506.36 | 26-DEC-12:00 | 23785.66 | 15-JUN-21:20 |
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 457.98 | 8506.36 | 26-DEC-12:00 | 23785.66 | 15-JUN-21:20 |
EnergyTransfer:Zone:DINING_FLR_6 | 495.92 | 9489.96 | 26-DEC-12:00 | 24970.42 | 15-JUN-21:20 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 495.92 | 9489.96 | 26-DEC-12:00 | 24970.42 | 15-JUN-21:20 |
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 495.92 | 9489.96 | 26-DEC-12:00 | 24970.42 | 15-JUN-21:20 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 647.48 | 8883.35 | 19-DEC-04:00 | 31083.24 | 02-JUL-10:40 |
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 647.48 | 8883.35 | 19-DEC-04:00 | 31083.24 | 02-JUL-10:40 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 106.30 | 1.15 | 19-DEC-06:30 | 6866.53 | 03-JUL-12:50 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.01 | 0.00 | 01-JAN-00:10 | 801.30 | 27-DEC-07:20 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.01 | 0.00 | 01-JAN-00:10 | 801.30 | 27-DEC-07:20 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 106.28 | 0.00 | 27-JAN-07:10 | 6866.53 | 03-JUL-12:50 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 106.28 | 0.00 | 27-JAN-07:10 | 6866.53 | 03-JUL-12:50 |
PlantLoopHeatingDemand:Facility | 1149.13 | 7610.31 | 31-JUL-00:10 | 175495.81 | 13-MAR-06:10 |
PlantLoopHeatingDemand:Plant | 666.01 | 7610.31 | 31-JUL-00:10 | 51272.17 | 30-JAN-08:00 |
WaterSystems:PlantLoopHeatingDemand | 666.01 | 7610.31 | 31-JUL-00:10 | 51272.17 | 30-JAN-08:00 |
General:WaterSystems:PlantLoopHeatingDemand | 666.01 | 7610.31 | 31-JUL-00:10 | 51272.17 | 30-JAN-08:00 |
EnergyTransfer:HVAC | 5750.99 | 536.17 | 24-MAR-13:40 | 654386.48 | 21-JUL-18:10 |
HeatingCoils:EnergyTransfer | 483.12 | 0.00 | 01-JAN-11:40 | 138217.91 | 27-DEC-17:40 |
PlantLoopHeatingDemand:HVAC | 483.12 | 0.00 | 01-JAN-11:40 | 138217.91 | 27-DEC-17:40 |
HeatingCoils:PlantLoopHeatingDemand | 483.12 | 0.00 | 01-JAN-11:40 | 138217.91 | 27-DEC-17:40 |
CoolingCoils:EnergyTransfer | 4235.69 | 0.00 | 01-JAN-03:40 | 603260.80 | 21-JUL-21:00 |
HeatRecoveryForHeating:EnergyTransfer | 788.70 | 0.00 | 01-JAN-08:10 | 351224.24 | 03-FEB-07:00 |
HeatRecoveryForCooling:EnergyTransfer | 243.47 | 0.00 | 01-JAN-00:10 | 144996.62 | 21-JUL-18:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 666.01 | 7610.31 | 31-JUL-00:10 | 51272.17 | 30-JAN-08:00 |
WaterUse:WaterSystems:EnergyTransfer | 666.01 | 7610.31 | 31-JUL-00:10 | 51272.17 | 30-JAN-08:00 |
Boilers:EnergyTransfer | 479.54 | 0.00 | 01-JAN-11:40 | 137941.89 | 27-DEC-17:40 |
Chillers:EnergyTransfer | 4303.88 | 0.00 | 01-JAN-03:40 | 602697.12 | 21-JUL-21:00 |
HeatRejection:EnergyTransfer | 5402.76 | 0.00 | 01-JAN-03:40 | 761434.21 | 21-JUL-21:00 |
General:HeatRejection:EnergyTransfer | 5402.76 | 0.00 | 01-JAN-03:40 | 761434.21 | 21-JUL-21:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:03
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -414.830 | 0.000 | 0.000 | 138.747 | 161.294 | 143.105 | 0.000 | 0.000 | 0.000 | 0.001 | 0.000 | 0.000 | 0.000 | 0.000 | -28.316 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 0.011 | -46.522 | 0.000 | 0.000 | 14.643 | 7.307 | 10.186 | 23.580 | 0.000 | 0.208 | 0.024 | 0.000 | -8.457 | 0.000 | -0.980 | -0.000 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.000 | -38.311 | 0.000 | 0.000 | 16.179 | 8.462 | 11.795 | 0.000 | 0.000 | 0.082 | 2.205 | 0.000 | 0.000 | 0.000 | -0.412 | -0.000 |
MECH_FLR_1 | 0.000 | 0.000 | 0.000 | -29.445 | 0.000 | 0.000 | 3.563 | 8.366 | 12.471 | 0.000 | 0.000 | 0.197 | 5.740 | 0.000 | 0.000 | 0.000 | -0.892 | -0.000 |
STORAGE_FLR_1 | 0.000 | 0.000 | 0.000 | -16.603 | 0.000 | 0.000 | 2.779 | 3.079 | 3.598 | 0.000 | 0.000 | 0.116 | 7.532 | 0.000 | 0.000 | 0.000 | -0.500 | 0.000 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.000 | -609.345 | 0.000 | 0.000 | 11.000 | 3.975 | 658.131 | 0.000 | 0.000 | 0.279 | 0.000 | 0.000 | 0.000 | 0.000 | -1.336 | -62.704 |
CAFE_FLR_1 | 0.000 | 0.000 | 0.000 | -239.762 | 0.000 | 0.000 | 181.806 | 14.273 | 14.341 | 65.446 | 0.000 | 0.460 | 0.001 | 0.000 | -25.750 | 0.000 | -2.410 | -8.404 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.000 | -811.277 | 0.000 | 0.000 | 537.538 | 110.171 | 148.998 | 87.199 | 0.000 | 1.340 | 0.000 | 0.000 | -34.095 | 0.000 | -6.936 | -32.937 |
ROOM_1_FLR_3 | 5.050 | -61.289 | 0.000 | -10.939 | 0.000 | 0.000 | 9.647 | 9.244 | 10.478 | 50.798 | 0.000 | 0.795 | 7.518 | 0.000 | -18.722 | 0.000 | -2.581 | -0.001 |
ROOM_2_FLR_3 | 8.310 | -47.273 | 0.000 | -11.320 | 0.000 | 0.000 | 9.557 | 9.243 | 10.477 | 38.156 | 0.000 | 0.690 | 4.808 | 0.000 | -19.714 | 0.000 | -2.935 | -0.001 |
ROOM_3_MULT19_FLR_3 | 0.000 | -380.978 | 0.000 | -15.000 | 0.000 | 0.000 | 0.000 | 110.385 | 194.997 | 256.521 | 0.000 | 1.337 | 1.888 | 0.000 | -151.647 | 0.000 | -17.502 | -0.001 |
ROOM_4_MULT19_FLR_3 | 18.976 | -318.191 | 0.000 | -150.776 | 0.000 | 0.000 | 182.579 | 110.415 | 195.050 | 101.205 | 0.000 | 4.321 | 0.000 | 0.000 | -106.729 | 0.000 | -23.395 | -13.457 |
ROOM_5_FLR_3 | 5.174 | -62.485 | 0.000 | -10.928 | 0.000 | 0.000 | 9.645 | 9.244 | 10.478 | 50.853 | 0.000 | 0.800 | 7.801 | 0.000 | -17.984 | 0.000 | -2.599 | -0.001 |
ROOM_6_FLR_3 | 8.226 | -47.601 | 0.000 | -11.354 | 0.000 | 0.000 | 9.553 | 9.243 | 10.477 | 37.417 | 0.000 | 0.690 | 4.541 | 0.000 | -18.311 | 0.000 | -2.881 | -0.001 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 0.000 | -205.991 | 0.000 | 0.000 | 113.499 | 91.336 | 0.000 | 42.905 | 0.000 | 0.608 | 0.002 | 0.000 | -23.379 | 0.000 | -2.717 | -16.260 |
ROOM_1_FLR_6 | 2.472 | -15.047 | 0.000 | -2.736 | 0.000 | 0.000 | 2.414 | 2.311 | 2.620 | 12.621 | 0.000 | 0.201 | 0.407 | 0.000 | -4.596 | 0.000 | -0.665 | -0.000 |
ROOM_2_FLR_6 | 3.632 | -11.867 | 0.000 | -2.821 | 0.000 | 0.000 | 2.394 | 2.311 | 2.619 | 9.497 | 0.000 | 0.172 | 0.000 | 0.000 | -4.830 | 0.000 | -0.753 | -0.354 |
ROOM_3_MULT9_FLR_6 | 4.201 | -91.247 | 0.000 | -17.576 | 0.000 | 0.000 | 21.681 | 13.076 | 23.098 | 63.761 | 0.000 | 1.066 | 7.062 | 0.000 | -21.338 | 0.000 | -3.785 | -0.001 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.000 | -457.984 | 0.000 | 0.000 | 314.882 | 31.154 | 175.857 | 9.540 | 0.000 | 0.281 | 0.000 | 0.000 | -14.699 | 0.000 | -1.604 | -57.428 |
DINING_FLR_6 | 0.000 | 0.000 | 0.000 | -495.929 | 0.000 | 0.000 | 314.362 | 31.154 | 175.857 | 9.317 | 0.000 | 0.281 | 0.000 | 0.000 | -15.144 | 0.000 | -1.616 | -18.282 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.000 | -647.463 | 0.000 | 0.000 | 28.062 | 12.972 | 550.372 | 23.544 | 0.000 | 0.252 | 44.082 | 0.000 | -10.374 | 0.000 | -1.446 | 0.000 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 0.014 | -106.282 | 0.000 | 0.000 | 30.213 | 24.166 | 0.000 | 20.678 | 0.000 | 0.253 | 42.576 | 0.000 | -10.429 | 0.000 | -1.188 | 0.000 |
Total Facility | 56.042 | -1035.978 | 0.025 | -4353.196 | 0.000 | 0.000 | 1954.742 | 783.183 | 2365.005 | 903.039 | 0.000 | 14.429 | 136.188 | 0.000 | -506.199 | 0.000 | -79.135 | -238.147 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 22-SEP-21:00 | 0.00 | 0.00 | 0.00 | -24615.55 | 0.00 | 0.00 | 5924.45 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2159.11 |
RETAIL_1_FLR_1 | 18-OCT-13:00 | 0.00 | 0.00 | 0.00 | -3606.91 | 0.00 | 0.00 | 150.60 | 166.00 | 252.59 | 4409.59 | 0.00 | 17.27 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1389.14 |
RETAIL_2_FLR_1 | 15-JUN-21:00 | 0.00 | 0.00 | 0.00 | -2331.01 | 0.00 | 0.00 | 697.61 | 615.12 | 752.15 | 0.00 | 0.00 | 15.93 | 250.20 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 15-JUN-20:00 | 0.00 | 0.00 | 0.00 | -2087.47 | 0.00 | 0.00 | 129.08 | 684.18 | 839.45 | 0.00 | 0.00 | 39.81 | 394.95 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 15-JUN-18:40 | 0.00 | 0.00 | 0.00 | -1033.91 | 0.00 | 0.00 | 99.29 | 223.85 | 229.41 | 0.00 | 0.00 | 26.35 | 455.00 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 15-JUN-20:00 | 0.00 | 0.00 | 0.00 | -39337.73 | 0.00 | 0.00 | 408.85 | 325.08 | 44299.38 | 0.00 | 0.00 | 54.36 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5749.95 |
CAFE_FLR_1 | 11-NOV-11:00 | 0.00 | 0.00 | 0.00 | -12780.44 | 0.00 | 0.00 | 4948.61 | 124.78 | 406.43 | 12564.68 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -82.40 | -5181.66 |
LOBBY_FLR_1 | 07-AUG-21:10 | 0.00 | 0.00 | 0.00 | -43577.96 | 0.00 | 0.00 | 26440.05 | 6336.53 | 7389.94 | 829.21 | 0.00 | 205.51 | 2376.72 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 14-JUN-15:02 | 0.00 | -8356.09 | 0.00 | -669.24 | 0.00 | 0.00 | 235.28 | 199.23 | 200.18 | 8009.13 | 0.00 | 150.97 | 230.53 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 19-JUN-18:51 | 0.00 | -9161.13 | 0.00 | -818.90 | 0.00 | 0.00 | 280.94 | 633.19 | 484.60 | 1354.18 | 0.00 | 20.81 | 7206.32 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 22-OCT-13:15 | 0.00 | -44051.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2803.75 | 2548.95 | 50904.64 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -41.84 | -12163.85 |
ROOM_4_MULT19_FLR_3 | 14-JUN-08:11 | 0.00 | -58901.17 | 0.00 | -9790.94 | 0.00 | 0.00 | 1589.90 | 3739.35 | 8433.45 | 9584.73 | 0.00 | 225.67 | 45119.01 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 11-JUL-08:62 | 0.00 | -7454.57 | 0.00 | -673.65 | 0.00 | 0.00 | 87.14 | 313.07 | 453.05 | 7306.03 | 0.00 | 47.11 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -78.17 |
ROOM_6_FLR_3 | 20-MAY-08:32 | 0.00 | -8696.82 | 0.00 | -896.00 | 0.00 | 0.00 | 93.39 | 398.41 | 653.15 | 6949.02 | 0.00 | 0.00 | 1506.71 | 0.00 | -0.00 | 0.00 | -7.85 | 0.00 |
CORRIDOR_FLR_3 | 15-JUN-18:40 | 0.00 | 0.00 | 0.00 | -12697.11 | 0.00 | 0.00 | 4080.29 | 6639.35 | 0.00 | 2508.83 | 0.00 | 140.02 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -671.38 |
ROOM_1_FLR_6 | 14-JUN-15:02 | 0.00 | -2231.98 | 0.00 | -168.00 | 0.00 | 0.00 | 58.82 | 49.81 | 50.05 | 1988.18 | 0.00 | 37.49 | 215.65 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 19-JUN-18:51 | 0.00 | -2412.74 | 0.00 | -207.62 | 0.00 | 0.00 | 69.01 | 158.30 | 121.15 | 329.11 | 0.00 | 4.57 | 1938.21 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 18-OCT-15:02 | 0.00 | -10134.90 | 0.00 | -1097.80 | 0.00 | 0.00 | 529.39 | 281.79 | 441.28 | 7101.73 | 0.00 | 68.32 | 2810.19 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 15-JUN-21:20 | 0.00 | 0.00 | 0.00 | -23789.13 | 0.00 | 0.00 | 15622.02 | 1992.02 | 6747.90 | 253.79 | 0.00 | 48.83 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -875.43 |
DINING_FLR_6 | 15-JUN-21:20 | 0.00 | 0.00 | 0.00 | -24974.17 | 0.00 | 0.00 | 15614.84 | 1992.02 | 6747.90 | 240.35 | 0.00 | 48.82 | 330.23 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 02-JUL-10:40 | 0.00 | 0.00 | 0.00 | -31094.47 | 0.00 | 0.00 | 464.24 | 353.60 | 24259.91 | 2635.31 | 0.00 | 45.71 | 3335.70 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 03-JUL-12:50 | 0.00 | 0.00 | 0.00 | -6865.52 | 0.00 | 0.00 | 308.46 | 548.96 | 0.00 | 1960.11 | 0.00 | 68.02 | 3979.97 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 07-AUG-18:02 | 0.00 | -126097.67 | 0.00 | -215090.80 | 0.00 | 0.00 | 73663.08 | 54680.24 | 120482.43 | 43156.58 | 0.00 | 2552.44 | 46653.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 27-DEC-07:30 | 0.00 | 0.00 | 566.77 | 0.00 | 0.00 | 0.00 | 358.00 | 332.00 | 433.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1208.03 | 0.00 | -127.97 | -353.77 |
RETAIL_2_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 26-DEC-16:02 | 5423.45 | 256.74 | 0.00 | -256.74 | 0.00 | 0.00 | 293.98 | 199.23 | 200.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1587.58 | 0.00 | -200.39 | -4328.87 |
ROOM_2_FLR_3 | 27-DEC-09:02 | 5458.12 | 254.54 | 0.00 | -254.54 | 0.00 | 0.00 | 108.88 | 313.04 | 452.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1302.63 | 0.00 | -235.50 | -4794.91 |
ROOM_3_MULT19_FLR_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 29-MAR-15:03 | 30881.85 | 5317.26 | 0.00 | -5317.26 | 0.00 | 0.00 | 4916.34 | 2379.59 | 3726.41 | 1688.14 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -9629.40 | -33962.93 |
ROOM_5_FLR_3 | 26-DEC-16:02 | 5294.52 | 255.16 | 0.00 | -255.16 | 0.00 | 0.00 | 293.98 | 199.23 | 200.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1701.66 | 0.00 | -200.11 | -4086.15 |
ROOM_6_FLR_3 | 26-DEC-16:02 | 5312.31 | 253.32 | 0.00 | -253.32 | 0.00 | 0.00 | 293.98 | 199.20 | 200.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1721.87 | 0.00 | -199.78 | -4084.01 |
CORRIDOR_FLR_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 26-DEC-16:02 | 1636.79 | 64.59 | 0.00 | -64.59 | 0.00 | 0.00 | 73.50 | 49.81 | 50.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -390.02 | 0.00 | -50.35 | -1369.77 |
ROOM_2_FLR_6 | 27-DEC-09:02 | 1645.55 | 64.09 | 0.00 | -64.09 | 0.00 | 0.00 | 27.22 | 78.26 | 113.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -314.66 | 0.00 | -59.14 | -1490.48 |
ROOM_3_MULT9_FLR_6 | 26-DEC-16:02 | 7472.59 | 496.65 | 0.00 | -496.65 | 0.00 | 0.00 | 639.89 | 281.79 | 441.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2014.65 | 0.00 | -242.13 | -6578.78 |
BANQUET_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 27-DEC-07:20 | 0.00 | 0.00 | 801.15 | 0.00 | 0.00 | 0.00 | 733.31 | 1097.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1577.34 | 0.00 | -160.14 | -894.90 |
Total Facility | 26-DEC-16:02 | -27398.16 | 95857.03 | 0.00 | -95857.03 | 0.00 | 0.00 | 58884.16 | 17287.14 | 73912.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -43809.44 | 0.00 | -5668.88 | -73207.41 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:03
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV WITH REHEAT | 24.9193 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 24.7871 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV WITH REHEAT | 12.4597 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 11.6623 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.6520 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.0400 | 0.000610 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.000000 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.000000 | 142.3000 | 0.003581 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.000000 | 422.4350 | 0.001448 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 83.8280 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003556 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.1800 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 | |
VAV WITH REHEAT | 0.00 | 0.001045 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8877 | 2.8877 | 1.3515 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3571 | 0.3571 | 0.1671 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2682 | 0.2682 | 0.1255 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2329 | 0.2329 | 0.1090 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1403 | 0.1403 | 0.0657 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.7575 | 3.7575 | 1.7585 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5608 | 1.5608 | 0.7304 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.3815 | 5.3815 | 2.5186 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7220 | 1.7220 | 0.8059 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.5204 | 2.5204 | 1.1795 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6398 | 2.6398 | 1.2354 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.5729 | 2.5729 | 1.2041 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8782 | 0.8782 | 0.4110 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
VAV WITH REHEAT | 24.9193 | 24.7871 | 24.9193 | 11.6623 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4439 | 1.4439 | 1.3515 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1785 | 0.1785 | 0.1671 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1341 | 0.1341 | 0.1255 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1165 | 0.1165 | 0.1090 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0702 | 0.0702 | 0.0657 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8787 | 1.8787 | 1.7585 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7804 | 0.7804 | 0.7304 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6908 | 2.6908 | 2.5186 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8610 | 0.8610 | 0.8059 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2602 | 1.2602 | 1.1795 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3199 | 1.3199 | 1.2354 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2864 | 1.2864 | 1.2041 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4391 | 0.4391 | 0.4110 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
VAV WITH REHEAT | 12.4597 | 11.6623 | 11.6623 | 11.6623 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:03
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 168.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 168.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 551.67 |
Number of hours not met | 551.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 744.67 | 215373.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 1098.88 | 158737.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 783.18 | 64632.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 194.01 | 12338.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 872.72 | 59188.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 14.43 | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 8.99 | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.20 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 21.77 | 1291.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 789.09 | 48128.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 2.91 | 188.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 602.61 | 50113.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 84.80 | 4073.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 134.18 | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 94.78 | 4751.13 | 2388.61 | 236198.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.09 | 2093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 20.48 | 1892.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 34.19 | 1201.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1719.93 | 5526.15 |
Natural Gas | 1788.84 | 4922.12 |
Additional | 0.00 | 0.00 |
Total | 3508.77 | 10448.27 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 69.03 |
Space Heating | 0.00 |
Space Cooling | 96.86 |
Fans (All) | 53.12 |
Service Water Heating | 8.35 |
Receptacle Equipment | 146.16 |
Miscellaneous (All) | 487.09 |
Subtotal | 487.09 |
Natural Gas [MJ/m2] | |
Space Heating | 65.64 |
Service Water Heating | 210.54 |
Miscellaneous (All) | 433.85 |
Subtotal | 433.85 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 7.50 |
Space Heating | 7.13 |
Space Cooling | 10.52 |
Fans (All) | 5.77 |
Service Water Heating | 23.77 |
Receptacle Equipment | 32.99 |
Miscellaneous | 12.33 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 486. | 5110. |
ELEVATOR_STANDBY_SCH | 7671. | 8760. |
LTG_SCH_KITCHEN | 3061. | 8760. |
LTG_SCH_DINING | 3061. | 8760. |
LTG_SCH_BASEMENT | 2572. | 8760. |
LTG_SCH_LOBBY | 2295. | 8760. |
LTG_SCH_STORAGE | 1580. | 8760. |
LTG_SCH_MECHANIC | 3061. | 8760. |
LTG_SCH_LAUNDRY | 3061. | 8760. |
LTG_SCH_GUESTROOM | 1980. | 8760. |
LTG_SCH_CORRIDOR | 2295. | 8760. |
LTG_SCH_RETAIL | 2678. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 1591. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3737. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 5740. | 6205. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 8760. | 8760. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 26.67 | 365 | 26.67 | 365 |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
HTGSETP_SCH | BASEMENT DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:03
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8091.00 | 669.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8717.50 | 42.50 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8091.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 669.00 | 0.00 | 0.00 | 0.00 |
Average | 8727.66 | 32.34 | 0.00 | 0.00 | 0.00 |
Sum | 192008.50 | 711.50 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108269.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 288887.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 6355515.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8734.83 | 25.17 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8153.67 | 606.33 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8309.50 | 450.50 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8717.83 | 42.17 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 7698.33 | 1061.67 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8751.00 | 9.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8629.33 | 130.67 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8759.83 | 0.17 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8715.83 | 44.17 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8759.67 | 0.33 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8288.83 | 471.17 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8323.00 | 437.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8753.17 | 6.83 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 7698.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 1061.67 | 0.00 | 0.00 | 0.00 |
Average | 8610.67 | 149.33 | 0.00 | 0.00 | 0.00 |
Sum | 189434.83 | 3285.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 58882.67 | 273.33 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 639202.33 | 71214.67 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 1956872.50 | 158556.50 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4151.17 | 2.83 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4151.67 | 2.33 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4149.33 | 4.67 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1146998.67 | 98716.33 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1153393.67 | 92321.33 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108240.17 | 28.83 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 1956872.50 | 158556.50 | 0.00 | 0.00 | 0.00 |
Average | 269745.19 | 19141.86 | 0.00 | 0.00 | 0.00 |
Sum | 5934394.17 | 421120.83 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:03
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:03
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 1592.73 | 0.00 | 0.00 |
Sum | 0.00 | 35040.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 710417.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 2115429.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 2115429.00 | 0.00 | 0.00 |
Average | 0.00 | 241694.36 | 0.00 | 0.00 |
Sum | 0.00 | 5317276.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3B
For: Environment
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Environment
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_TX_ELPASO
For: Environment
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.333698E+11 | 18300.50 | 05-JAN-22:00 | 5.60 | -2.2 | 0.810179E+10 | 4837.09 | 25-JAN-22:00 | 5.60 | 3.72 |
February | 0.262620E+11 | 15326.60 | 01-FEB-22:00 | 1.70 | -2.7 | 0.681132E+10 | 4836.99 | 01-FEB-22:30 | 1.95 | -2.3 |
March | 0.264615E+11 | 12200.59 | 01-MAR-21:00 | 1.70 | -3.0 | 0.703620E+10 | 4537.16 | 01-MAR-22:10 | 1.02 | -3.3 |
April | 0.266495E+11 | 13096.58 | 30-APR-10:33 | 24.07 | 13.08 | 0.685798E+10 | 4423.46 | 07-APR-22:10 | 24.07 | 13.08 |
May | 0.292792E+11 | 13673.79 | 21-MAY-10:33 | 29.47 | 14.38 | 0.730757E+10 | 4555.09 | 12-MAY-22:10 | 29.47 | 14.38 |
June | 0.301341E+11 | 14369.70 | 15-JUN-18:10 | 35.92 | 14.47 | 0.730402E+10 | 4700.43 | 23-JUN-22:10 | 23.40 | 15.27 |
July | 0.355269E+11 | 18890.48 | 19-JUL-21:00 | 23.90 | 20.39 | 0.807879E+10 | 4837.14 | 05-JUL-21:00 | 23.90 | 20.39 |
August | 0.404126E+11 | 22176.14 | 24-AUG-21:00 | 26.70 | 16.71 | 0.823450E+10 | 4837.26 | 22-AUG-00:10 | 26.70 | 16.71 |
September | 0.433801E+11 | 24615.22 | 22-SEP-21:00 | 25.00 | 17.90 | 0.797312E+10 | 4837.39 | 19-SEP-04:10 | 25.00 | 17.90 |
October | 0.441514E+11 | 24396.74 | 20-OCT-21:00 | 18.90 | 10.31 | 0.823394E+10 | 4837.31 | 10-OCT-21:19 | 18.90 | 10.31 |
November | 0.409120E+11 | 23821.68 | 10-NOV-22:00 | 15.60 | 8.38 | 0.796106E+10 | 4837.45 | 01-NOV-01:10 | 15.60 | 8.38 |
December | 0.382889E+11 | 22137.70 | 01-DEC-22:00 | 7.20 | 2.26 | 0.821448E+10 | 4837.20 | 13-DEC-00:10 | 6.47 | 5.55 |
Annual Sum or Average | 0.414828E+12 | 0.921148E+11 | ||||||||
Minimum of Months | 0.262620E+11 | 12200.59 | 1.70 | -3.0 | 0.681132E+10 | 4423.46 | 1.02 | -3.3 | ||
Maximum of Months | 0.441514E+11 | 24615.22 | 35.92 | 20.39 | 0.823450E+10 | 4837.45 | 29.47 | 20.39 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.297030E+10 | 2870.18 | 12-JAN-13:50 | 18.03 | 9.58 | 0.673561E+09 | 450.15 | 12-JAN-22:19 | 9.47 | 5.03 |
February | 0.288996E+10 | 2902.71 | 07-FEB-13:30 | 20.30 | 9.54 | 0.618283E+09 | 471.25 | 06-FEB-22:30 | 20.30 | 9.54 |
March | 0.318960E+10 | 2264.61 | 16-MAR-13:20 | 22.40 | 9.11 | 0.695054E+09 | 473.47 | 16-MAR-21:30 | 16.65 | 6.00 |
April | 0.362888E+10 | 2343.33 | 03-APR-14:10 | 26.70 | 11.67 | 0.724522E+09 | 491.84 | 28-APR-22:10 | 21.52 | 12.87 |
May | 0.408374E+10 | 2294.12 | 31-MAY-18:04 | 30.92 | 15.25 | 0.787825E+09 | 491.84 | 17-MAY-22:10 | 30.92 | 15.25 |
June | 0.453454E+10 | 2662.32 | 15-JUN-18:20 | 35.73 | 14.50 | 0.793839E+09 | 491.86 | 30-JUN-22:10 | 28.43 | 17.10 |
July | 0.472098E+10 | 2656.65 | 26-JUL-18:04 | 33.77 | 19.75 | 0.818523E+09 | 491.84 | 05-JUL-21:00 | 33.77 | 19.75 |
August | 0.478967E+10 | 2829.19 | 27-AUG-12:00 | 33.30 | 15.93 | 0.816703E+09 | 491.86 | 22-AUG-00:10 | 33.30 | 15.93 |
September | 0.485063E+10 | 3456.72 | 20-SEP-12:50 | 32.12 | 17.95 | 0.782776E+09 | 491.84 | 19-SEP-23:10 | 32.12 | 17.95 |
October | 0.455146E+10 | 3607.01 | 18-OCT-13:00 | 27.80 | 18.14 | 0.771153E+09 | 491.85 | 05-OCT-23:49 | 27.80 | 18.14 |
November | 0.358659E+10 | 3406.10 | 10-NOV-12:00 | 21.10 | 12.09 | 0.685545E+09 | 491.81 | 09-NOV-22:19 | 21.10 | 12.09 |
December | 0.272516E+10 | 2608.10 | 16-DEC-13:30 | 14.45 | 3.99 | 0.663467E+09 | 435.51 | 15-DEC-22:30 | 14.45 | 3.99 |
Annual Sum or Average | 0.465215E+11 | 0.883125E+10 | ||||||||
Minimum of Months | 0.272516E+10 | 2264.61 | 14.45 | 3.99 | 0.618283E+09 | 435.51 | 9.47 | 3.99 | ||
Maximum of Months | 0.485063E+10 | 3607.01 | 35.73 | 19.75 | 0.818523E+09 | 491.86 | 33.77 | 19.75 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.267130E+10 | 1425.67 | 12-JAN-22:00 | 10.60 | 5.73 | 0.887536E+09 | 569.52 | 04-JAN-22:30 | 10.60 | 5.73 |
February | 0.247710E+10 | 1573.57 | 21-FEB-22:00 | 14.40 | 4.35 | 0.811521E+09 | 569.54 | 22-FEB-22:19 | 14.40 | 4.92 |
March | 0.281147E+10 | 1632.07 | 16-MAR-21:00 | 17.20 | 5.94 | 0.911774E+09 | 569.55 | 16-MAR-22:10 | 15.27 | 5.99 |
April | 0.306413E+10 | 1950.18 | 28-APR-20:55 | 22.80 | 12.84 | 0.912922E+09 | 569.66 | 17-APR-01:10 | 22.80 | 12.84 |
May | 0.350319E+10 | 2124.90 | 19-MAY-21:00 | 30.00 | 13.65 | 0.959146E+09 | 569.58 | 18-MAY-00:10 | 30.00 | 13.65 |
June | 0.374170E+10 | 2330.86 | 15-JUN-21:00 | 33.30 | 13.72 | 0.936807E+09 | 569.57 | 30-JUN-22:10 | 28.43 | 17.10 |
July | 0.386636E+10 | 2293.03 | 26-JUL-21:00 | 28.90 | 18.16 | 0.964780E+09 | 569.55 | 19-JUL-22:10 | 28.90 | 18.16 |
August | 0.381506E+10 | 2324.96 | 07-AUG-21:00 | 31.70 | 16.85 | 0.968104E+09 | 569.57 | 22-AUG-00:10 | 24.22 | 16.48 |
September | 0.361724E+10 | 2215.18 | 20-SEP-20:10 | 25.40 | 15.25 | 0.934757E+09 | 569.58 | 19-SEP-04:10 | 25.40 | 15.25 |
October | 0.332775E+10 | 2143.33 | 05-OCT-20:10 | 23.80 | 16.56 | 0.952762E+09 | 569.56 | 10-OCT-21:10 | 14.13 | 9.16 |
November | 0.280558E+10 | 1819.51 | 09-NOV-22:00 | 18.90 | 11.06 | 0.888729E+09 | 569.57 | 01-NOV-00:00 | 18.90 | 11.06 |
December | 0.261018E+10 | 1272.51 | 07-DEC-21:20 | 8.30 | 3.05 | 0.875824E+09 | 569.52 | 07-DEC-22:30 | 5.55 | 1.60 |
Annual Sum or Average | 0.383111E+11 | 0.110047E+11 | ||||||||
Minimum of Months | 0.247710E+10 | 1272.51 | 8.30 | 3.05 | 0.811521E+09 | 569.52 | 5.55 | 1.60 | ||
Maximum of Months | 0.386636E+10 | 2330.86 | 33.30 | 18.16 | 0.968104E+09 | 569.66 | 30.00 | 18.16 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.191819E+10 | 918.95 | 03-JAN-21:00 | 14.40 | 6.79 | 0.163688E+09 | 105.68 | 03-JAN-22:10 | 12.43 | 6.06 |
February | 0.179822E+10 | 977.95 | 20-FEB-11:33 | 20.37 | 8.19 | 0.150802E+09 | 108.60 | 23-FEB-22:10 | 11.93 | 4.94 |
March | 0.208224E+10 | 1015.73 | 16-MAR-18:10 | 19.82 | 7.14 | 0.171791E+09 | 111.39 | 16-MAR-21:10 | 17.02 | 5.96 |
April | 0.231310E+10 | 1189.09 | 30-APR-10:33 | 24.07 | 13.08 | 0.179861E+09 | 120.45 | 21-APR-21:19 | 24.07 | 13.08 |
May | 0.272962E+10 | 1725.40 | 31-MAY-20:00 | 29.40 | 14.60 | 0.198410E+09 | 120.45 | 24-MAY-21:00 | 29.40 | 14.60 |
June | 0.312020E+10 | 2087.29 | 15-JUN-20:00 | 33.90 | 14.00 | 0.198137E+09 | 120.46 | 30-JUN-22:10 | 28.43 | 17.10 |
July | 0.325873E+10 | 2072.12 | 03-JUL-20:00 | 28.30 | 19.12 | 0.204159E+09 | 120.46 | 05-JUL-22:10 | 27.70 | 17.66 |
August | 0.308611E+10 | 2024.52 | 07-AUG-20:00 | 31.70 | 17.36 | 0.203934E+09 | 120.46 | 22-AUG-00:10 | 24.22 | 16.48 |
September | 0.274930E+10 | 1724.37 | 22-SEP-20:00 | 26.10 | 18.64 | 0.194630E+09 | 120.46 | 20-SEP-22:10 | 26.10 | 18.64 |
October | 0.248850E+10 | 1529.41 | 05-OCT-20:00 | 23.90 | 16.65 | 0.190329E+09 | 120.45 | 03-OCT-21:19 | 23.90 | 16.65 |
November | 0.205803E+10 | 1067.77 | 10-NOV-11:33 | 20.93 | 12.02 | 0.168363E+09 | 115.00 | 10-NOV-22:10 | 15.50 | 8.35 |
December | 0.184278E+10 | 910.71 | 10-DEC-11:35 | 15.93 | 7.48 | 0.161274E+09 | 103.45 | 11-DEC-22:10 | 8.80 | 4.97 |
Annual Sum or Average | 0.294450E+11 | 0.218538E+10 | ||||||||
Minimum of Months | 0.179822E+10 | 910.71 | 14.40 | 6.79 | 0.150802E+09 | 103.45 | 8.80 | 4.94 | ||
Maximum of Months | 0.325873E+10 | 2087.29 | 33.90 | 19.12 | 0.204159E+09 | 120.46 | 29.40 | 18.64 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.108622E+10 | 539.76 | 01-JAN-11:33 | 13.87 | 8.54 | 0.121775E+09 | 77.64 | 03-JAN-22:40 | 11.33 | 5.60 |
February | 0.102751E+10 | 580.28 | 20-FEB-11:33 | 20.37 | 8.19 | 0.112330E+09 | 79.99 | 07-FEB-23:10 | 20.37 | 8.19 |
March | 0.119726E+10 | 597.03 | 16-MAR-10:33 | 20.03 | 8.28 | 0.127965E+09 | 82.12 | 16-MAR-21:40 | 16.47 | 6.01 |
April | 0.134712E+10 | 703.21 | 30-APR-10:33 | 24.07 | 13.08 | 0.134520E+09 | 89.52 | 21-APR-22:10 | 24.07 | 13.08 |
May | 0.156015E+10 | 783.78 | 31-MAY-21:00 | 28.30 | 13.66 | 0.149402E+09 | 92.66 | 31-MAY-21:19 | 27.97 | 13.53 |
June | 0.171724E+10 | 1033.81 | 15-JUN-18:40 | 35.37 | 14.55 | 0.151454E+09 | 92.66 | 30-JUN-22:10 | 28.43 | 17.10 |
July | 0.178466E+10 | 1026.41 | 03-JUL-18:30 | 34.45 | 19.49 | 0.156213E+09 | 92.66 | 05-JUL-22:10 | 27.70 | 17.66 |
August | 0.170754E+10 | 992.18 | 07-AUG-21:00 | 31.70 | 16.85 | 0.155272E+09 | 92.66 | 21-AUG-23:49 | 25.23 | 16.56 |
September | 0.155492E+10 | 766.08 | 22-SEP-21:00 | 25.00 | 17.90 | 0.146797E+09 | 92.66 | 20-SEP-22:10 | 25.00 | 17.90 |
October | 0.143914E+10 | 731.74 | 05-OCT-10:33 | 27.60 | 18.63 | 0.142317E+09 | 92.66 | 05-OCT-22:10 | 22.98 | 16.25 |
November | 0.117923E+10 | 631.44 | 10-NOV-11:33 | 20.93 | 12.02 | 0.125245E+09 | 84.61 | 09-NOV-22:40 | 20.93 | 12.02 |
December | 0.100225E+10 | 536.17 | 10-DEC-11:35 | 15.93 | 7.48 | 0.120308E+09 | 76.07 | 15-DEC-23:10 | 13.80 | 4.57 |
Annual Sum or Average | 0.166032E+11 | 0.164360E+10 | ||||||||
Minimum of Months | 0.100225E+10 | 536.17 | 13.87 | 7.48 | 0.112330E+09 | 76.07 | 11.33 | 4.57 | ||
Maximum of Months | 0.178466E+10 | 1033.81 | 35.37 | 19.49 | 0.156213E+09 | 92.66 | 28.43 | 17.90 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.493990E+11 | 37506.08 | 12-JAN-21:00 | 12.80 | 7.31 | 0.605892E+09 | 381.75 | 03-JAN-22:10 | 12.80 | 7.31 |
February | 0.451230E+11 | 37833.00 | 21-FEB-20:55 | 15.00 | 4.44 | 0.548940E+09 | 381.74 | 23-FEB-22:10 | 11.93 | 4.94 |
March | 0.506115E+11 | 37955.97 | 16-MAR-20:00 | 17.20 | 5.94 | 0.610509E+09 | 381.72 | 28-MAR-21:10 | 4.82 | 1.75 |
April | 0.502816E+11 | 38680.17 | 28-APR-20:00 | 25.00 | 12.84 | 0.593947E+09 | 381.73 | 18-APR-21:10 | 25.00 | 12.84 |
May | 0.530586E+11 | 38974.23 | 30-MAY-20:00 | 28.90 | 14.28 | 0.616295E+09 | 381.76 | 23-MAY-21:10 | 28.90 | 14.28 |
June | 0.523052E+11 | 39336.58 | 15-JUN-20:00 | 33.90 | 14.00 | 0.598659E+09 | 381.83 | 27-JUN-21:10 | 28.62 | 16.18 |
July | 0.537931E+11 | 39308.52 | 03-JUL-20:00 | 28.30 | 19.12 | 0.616282E+09 | 381.83 | 28-JUL-21:10 | 29.03 | 16.95 |
August | 0.537238E+11 | 39215.74 | 04-AUG-20:00 | 33.30 | 17.89 | 0.617249E+09 | 381.83 | 08-AUG-21:10 | 26.42 | 18.40 |
September | 0.514703E+11 | 38934.53 | 20-SEP-20:00 | 25.60 | 15.27 | 0.595222E+09 | 381.88 | 19-SEP-21:10 | 25.60 | 15.27 |
October | 0.517932E+11 | 38718.90 | 05-OCT-20:00 | 23.90 | 16.65 | 0.612284E+09 | 381.83 | 31-OCT-21:10 | 10.60 | 4.71 |
November | 0.487108E+11 | 38082.28 | 09-NOV-21:00 | 20.00 | 11.27 | 0.588996E+09 | 381.79 | 22-NOV-22:10 | 10.22 | 3.96 |
December | 0.490725E+11 | 37296.26 | 15-DEC-21:00 | 14.40 | 4.76 | 0.604915E+09 | 381.77 | 04-DEC-22:10 | 14.40 | 4.76 |
Annual Sum or Average | 0.609343E+12 | 0.720919E+10 | ||||||||
Minimum of Months | 0.451230E+11 | 37296.26 | 12.80 | 4.44 | 0.548940E+09 | 381.72 | 4.82 | 1.75 | ||
Maximum of Months | 0.537931E+11 | 39336.58 | 33.90 | 19.12 | 0.617249E+09 | 381.88 | 29.03 | 18.40 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.176508E+11 | 11519.69 | 01-JAN-11:00 | 12.80 | 8.11 | 0.104585E+11 | 6461.81 | 14-JAN-02:20 | 8.50 | 3.32 |
February | 0.163793E+11 | 11387.69 | 20-FEB-13:00 | 21.10 | 8.39 | 0.954874E+10 | 6462.30 | 22-FEB-22:19 | 14.40 | 4.92 |
March | 0.178118E+11 | 10233.80 | 14-MAR-15:03 | 23.98 | 9.90 | 0.106508E+11 | 6462.47 | 16-MAR-22:10 | 15.27 | 5.99 |
April | 0.188488E+11 | 11079.69 | 19-APR-21:10 | 28.12 | 12.29 | 0.104606E+11 | 6463.25 | 17-APR-01:10 | 28.12 | 12.29 |
May | 0.205832E+11 | 11408.17 | 31-MAY-21:10 | 28.13 | 13.59 | 0.108864E+11 | 6462.62 | 17-MAY-22:10 | 28.13 | 13.59 |
June | 0.217835E+11 | 11975.53 | 15-JUN-21:10 | 32.57 | 13.55 | 0.106123E+11 | 6462.61 | 22-JUN-22:10 | 23.22 | 16.10 |
July | 0.226419E+11 | 11912.14 | 25-JUL-21:10 | 31.42 | 17.57 | 0.109331E+11 | 6462.60 | 19-JUL-22:10 | 31.42 | 17.57 |
August | 0.229318E+11 | 12340.83 | 07-AUG-21:10 | 31.25 | 17.07 | 0.109772E+11 | 6462.61 | 11-AUG-22:10 | 22.80 | 17.38 |
September | 0.227577E+11 | 12152.87 | 19-SEP-15:03 | 33.40 | 16.39 | 0.106141E+11 | 6462.68 | 28-SEP-22:10 | 24.40 | 12.24 |
October | 0.221830E+11 | 12762.13 | 22-OCT-12:00 | 23.90 | 13.84 | 0.108817E+11 | 6462.63 | 05-OCT-22:10 | 23.90 | 13.84 |
November | 0.190608E+11 | 12786.04 | 11-NOV-11:00 | 16.10 | 7.51 | 0.102967E+11 | 6462.34 | 08-NOV-23:10 | 16.10 | 7.51 |
December | 0.171269E+11 | 11099.26 | 16-DEC-13:30 | 14.45 | 3.99 | 0.103419E+11 | 6461.78 | 16-DEC-02:20 | 14.45 | 3.99 |
Annual Sum or Average | 0.239760E+12 | 0.126662E+12 | ||||||||
Minimum of Months | 0.163793E+11 | 10233.80 | 12.80 | 3.99 | 0.954874E+10 | 6461.78 | 8.50 | 3.32 | ||
Maximum of Months | 0.229318E+11 | 12786.04 | 33.40 | 17.57 | 0.109772E+11 | 6463.25 | 31.42 | 17.57 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.588582E+11 | 32460.31 | 03-JAN-22:10 | 12.43 | 6.06 | 0.314929E+11 | 19184.98 | 06-JAN-01:19 | 3.67 | -3.4 |
February | 0.543325E+11 | 33687.47 | 07-FEB-22:10 | 15.10 | 7.63 | 0.286332E+11 | 19185.63 | 22-FEB-22:19 | 14.40 | 4.92 |
March | 0.610273E+11 | 34355.45 | 16-MAR-21:10 | 17.02 | 5.96 | 0.318590E+11 | 19185.87 | 16-MAR-22:10 | 15.27 | 5.99 |
April | 0.650836E+11 | 37890.41 | 21-APR-21:10 | 24.90 | 9.61 | 0.311248E+11 | 19189.56 | 17-APR-01:10 | 24.90 | 9.61 |
May | 0.726840E+11 | 40719.23 | 31-MAY-21:10 | 28.13 | 13.59 | 0.323355E+11 | 19186.03 | 17-MAY-22:10 | 28.13 | 13.59 |
June | 0.760086E+11 | 43082.31 | 15-JUN-21:10 | 32.57 | 13.55 | 0.314988E+11 | 19186.00 | 22-JUN-22:10 | 23.22 | 16.10 |
July | 0.789278E+11 | 42881.52 | 26-JUL-21:10 | 28.62 | 18.19 | 0.324519E+11 | 19186.03 | 19-JUL-22:10 | 28.62 | 18.19 |
August | 0.784616E+11 | 43572.45 | 07-AUG-21:10 | 31.25 | 17.07 | 0.326040E+11 | 19186.03 | 11-AUG-22:10 | 22.80 | 17.38 |
September | 0.749332E+11 | 41891.79 | 21-SEP-21:10 | 26.10 | 17.46 | 0.315216E+11 | 19186.11 | 28-SEP-22:10 | 24.40 | 12.24 |
October | 0.717343E+11 | 41271.68 | 05-OCT-21:10 | 23.22 | 16.17 | 0.324239E+11 | 19186.04 | 05-OCT-22:10 | 22.98 | 16.25 |
November | 0.616395E+11 | 37775.13 | 09-NOV-22:10 | 18.53 | 10.92 | 0.309658E+11 | 19185.93 | 01-NOV-01:10 | 18.53 | 10.92 |
December | 0.575786E+11 | 30836.08 | 15-DEC-22:10 | 14.32 | 4.61 | 0.312769E+11 | 19184.92 | 16-DEC-02:20 | 10.60 | 3.59 |
Annual Sum or Average | 0.811269E+12 | 0.378188E+12 | ||||||||
Minimum of Months | 0.543325E+11 | 30836.08 | 12.43 | 4.61 | 0.286332E+11 | 19184.92 | 3.67 | -3.4 | ||
Maximum of Months | 0.789278E+11 | 43572.45 | 32.57 | 18.19 | 0.326040E+11 | 19189.56 | 28.62 | 18.19 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.284894E+09 | 2114.78 | 30-JAN-16:02 | 15.60 | 6.01 | 96847951.48 | 56.69 | 03-JAN-22:10 | 15.60 | 6.01 |
February | 0.415100E+09 | 2212.35 | 20-FEB-16:02 | 23.12 | 8.59 | 87990132.33 | 56.69 | 06-FEB-22:00 | 23.12 | 8.59 |
March | 0.729208E+09 | 2205.48 | 16-MAR-15:02 | 22.70 | 8.66 | 98059279.86 | 56.69 | 21-MAR-21:19 | 16.30 | 5.41 |
April | 0.150207E+10 | 2234.64 | 16-APR-15:02 | 29.50 | 11.50 | 95629454.92 | 56.69 | 17-APR-03:20 | 15.73 | 11.53 |
May | 0.216474E+10 | 2239.44 | 17-MAY-15:02 | 29.40 | 13.34 | 99582194.18 | 56.70 | 22-MAY-23:10 | 22.70 | 14.88 |
June | 0.262128E+10 | 2256.35 | 14-JUN-15:02 | 37.88 | 15.65 | 96913888.49 | 58.96 | 15-JUN-21:10 | 32.57 | 13.55 |
July | 0.262998E+10 | 2227.19 | 31-JUL-18:02 | 33.22 | 19.45 | 99457797.64 | 56.70 | 28-JUL-21:40 | 33.22 | 19.45 |
August | 0.248527E+10 | 2239.16 | 28-AUG-18:02 | 29.03 | 17.18 | 99559285.49 | 56.70 | 05-AUG-00:40 | 29.03 | 17.18 |
September | 0.228381E+10 | 2242.13 | 01-SEP-18:02 | 31.13 | 18.07 | 96214701.59 | 56.70 | 12-SEP-21:49 | 25.78 | 17.09 |
October | 0.161988E+10 | 2226.76 | 31-OCT-15:02 | 21.60 | 7.74 | 98976834.78 | 56.70 | 05-OCT-21:00 | 21.60 | 7.74 |
November | 0.695491E+09 | 2187.01 | 07-NOV-16:02 | 21.52 | 10.29 | 94675761.58 | 56.69 | 01-NOV-02:30 | 21.52 | 10.29 |
December | 0.191585E+09 | 2109.16 | 16-DEC-16:02 | 14.72 | 4.08 | 96584598.52 | 56.69 | 21-DEC-05:19 | 1.13 | -2.2 |
Annual Sum or Average | 0.176233E+11 | 0.116049E+10 | ||||||||
Minimum of Months | 0.191585E+09 | 2109.16 | 14.72 | 4.08 | 87990132.33 | 56.69 | 1.13 | -2.2 | ||
Maximum of Months | 0.262998E+10 | 2256.35 | 37.88 | 19.45 | 99582194.18 | 58.96 | 33.22 | 19.45 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 70510567.14 | 2034.13 | 30-JAN-16:02 | 15.60 | 6.01 | 95275733.27 | 56.69 | 06-JAN-05:19 | 15.60 | 6.01 |
February | 0.131821E+09 | 2153.34 | 20-FEB-16:02 | 23.12 | 8.59 | 87630304.84 | 64.33 | 22-FEB-22:10 | 14.40 | 4.90 |
March | 0.341682E+09 | 2155.65 | 16-MAR-15:02 | 22.70 | 8.66 | 0.100213E+09 | 69.92 | 16-MAR-21:40 | 16.47 | 6.01 |
April | 0.117830E+10 | 2416.46 | 06-APR-18:11 | 14.63 | 6.39 | 99320483.65 | 75.78 | 28-APR-21:40 | 22.07 | 12.89 |
May | 0.198997E+10 | 2362.37 | 20-MAY-08:51 | 26.70 | 12.19 | 0.102763E+09 | 79.77 | 23-MAY-21:10 | 22.02 | 16.25 |
June | 0.253422E+10 | 2495.02 | 19-JUN-18:51 | 27.20 | 19.20 | 99409699.15 | 79.71 | 23-JUN-21:10 | 23.30 | 15.34 |
July | 0.251287E+10 | 2222.59 | 12-JUL-08:11 | 26.33 | 18.31 | 0.102060E+09 | 76.31 | 21-JUL-21:00 | 23.90 | 20.39 |
August | 0.224280E+10 | 2339.15 | 26-AUG-08:11 | 27.07 | 15.12 | 0.102494E+09 | 80.43 | 11-AUG-21:10 | 27.07 | 15.12 |
September | 0.180579E+10 | 2229.76 | 01-SEP-18:02 | 31.13 | 18.07 | 0.100268E+09 | 79.14 | 13-SEP-21:10 | 21.70 | 17.29 |
October | 0.978842E+09 | 2212.36 | 03-OCT-18:21 | 24.70 | 18.40 | 0.104078E+09 | 81.02 | 05-OCT-21:10 | 23.22 | 16.17 |
November | 0.240701E+09 | 2124.70 | 03-NOV-15:02 | 23.40 | 13.55 | 94726887.93 | 69.18 | 09-NOV-22:40 | 17.43 | 10.49 |
December | 37671055.96 | 2046.60 | 16-DEC-16:02 | 14.72 | 4.08 | 94754181.93 | 56.69 | 21-DEC-05:19 | 1.13 | -2.2 |
Annual Sum or Average | 0.140652E+11 | 0.118299E+10 | ||||||||
Minimum of Months | 37671055.96 | 2034.13 | 14.63 | 4.08 | 87630304.84 | 56.69 | 1.13 | -2.2 | ||
Maximum of Months | 0.253422E+10 | 2495.02 | 31.13 | 19.20 | 0.104078E+09 | 81.02 | 27.07 | 20.39 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.273768E+09 | 504.53 | 12-JAN-14:25 | 18.60 | 9.87 | 0.00 | 0.00 | 01-JAN-00:10 | 18.60 | 9.87 |
February | 0.276952E+09 | 474.16 | 07-FEB-13:40 | 20.20 | 9.50 | 0.00 | 0.00 | 01-FEB-00:10 | 20.20 | 9.50 |
March | 0.261653E+09 | 370.31 | 16-MAR-12:50 | 22.02 | 8.91 | 0.00 | 0.00 | 01-MAR-00:10 | 22.02 | 8.91 |
April | 0.360096E+09 | 348.94 | 03-APR-14:00 | 26.70 | 11.71 | 0.00 | 0.00 | 01-APR-00:10 | 26.70 | 11.71 |
May | 0.439304E+09 | 332.77 | 19-MAY-20:20 | 30.73 | 14.26 | 0.00 | 0.00 | 01-MAY-00:10 | 30.73 | 14.26 |
June | 0.543815E+09 | 374.62 | 15-JUN-20:20 | 33.70 | 13.91 | 0.00 | 0.00 | 01-JUN-00:10 | 33.70 | 13.91 |
July | 0.572607E+09 | 377.12 | 02-JUL-20:50 | 32.98 | 17.29 | 0.00 | 0.00 | 01-JUL-00:10 | 32.98 | 17.29 |
August | 0.593833E+09 | 399.82 | 27-AUG-13:40 | 34.40 | 16.46 | 0.00 | 0.00 | 01-AUG-00:10 | 34.40 | 16.46 |
September | 0.648801E+09 | 508.03 | 19-SEP-13:30 | 33.35 | 16.80 | 0.00 | 0.00 | 01-SEP-00:10 | 33.35 | 16.80 |
October | 0.586730E+09 | 579.63 | 22-OCT-13:15 | 25.97 | 14.61 | 0.00 | 0.00 | 01-OCT-00:10 | 25.97 | 14.61 |
November | 0.417349E+09 | 543.94 | 09-NOV-13:50 | 23.22 | 12.39 | 0.00 | 0.00 | 01-NOV-00:10 | 23.22 | 12.39 |
December | 0.235393E+09 | 429.34 | 16-DEC-13:40 | 14.63 | 4.10 | 0.00 | 0.00 | 01-DEC-00:10 | 14.63 | 4.10 |
Annual Sum or Average | 0.521030E+10 | 0.00 | ||||||||
Minimum of Months | 0.235393E+09 | 332.77 | 14.63 | 4.10 | 0.00 | 0.00 | 14.63 | 4.10 | ||
Maximum of Months | 0.648801E+09 | 579.63 | 34.40 | 17.29 | 0.00 | 0.00 | 34.40 | 17.29 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.116098E+09 | 730.60 | 13-JAN-19:02 | 13.12 | 6.39 | 95725483.45 | 56.69 | 03-JAN-23:10 | 13.12 | 6.39 |
February | 0.165038E+09 | 786.27 | 22-FEB-16:01 | 22.62 | 8.47 | 87310092.28 | 68.17 | 22-FEB-22:10 | 14.40 | 4.90 |
March | 0.277657E+09 | 819.16 | 15-MAR-21:52 | 19.40 | 7.29 | 98416374.47 | 70.97 | 09-MAR-22:10 | 19.40 | 7.29 |
April | 0.519331E+09 | 839.39 | 21-APR-18:02 | 29.95 | 11.64 | 97380940.07 | 73.10 | 25-APR-21:49 | 18.22 | 11.64 |
May | 0.761720E+09 | 883.92 | 20-MAY-08:51 | 26.70 | 12.19 | 0.101236E+09 | 75.18 | 23-MAY-21:10 | 22.02 | 16.25 |
June | 0.932110E+09 | 903.85 | 14-JUN-08:11 | 27.93 | 12.20 | 98004977.55 | 75.38 | 23-JUN-21:10 | 23.30 | 15.34 |
July | 0.947506E+09 | 872.98 | 06-JUL-08:61 | 26.38 | 18.59 | 0.101061E+09 | 71.98 | 18-JUL-21:00 | 19.40 | 19.40 |
August | 0.842573E+09 | 857.42 | 29-AUG-21:51 | 22.20 | 14.62 | 0.101370E+09 | 77.50 | 14-AUG-21:10 | 22.20 | 14.62 |
September | 0.667827E+09 | 839.21 | 11-SEP-21:51 | 18.90 | 10.00 | 98677150.82 | 74.13 | 13-SEP-21:10 | 21.70 | 17.29 |
October | 0.470503E+09 | 839.35 | 04-OCT-18:02 | 28.22 | 19.05 | 0.101502E+09 | 75.14 | 05-OCT-21:10 | 23.22 | 16.17 |
November | 0.201817E+09 | 797.85 | 09-NOV-16:02 | 23.22 | 12.98 | 93743777.71 | 68.92 | 09-NOV-22:49 | 17.07 | 10.34 |
December | 87216974.73 | 733.63 | 16-DEC-09:02 | 8.48 | 2.42 | 95454388.58 | 56.69 | 13-DEC-00:20 | 8.48 | 2.42 |
Annual Sum or Average | 0.598940E+10 | 0.116988E+10 | ||||||||
Minimum of Months | 87216974.73 | 730.60 | 8.48 | 2.42 | 87310092.28 | 56.69 | 8.48 | 2.42 | ||
Maximum of Months | 0.947506E+09 | 903.85 | 29.95 | 19.05 | 0.101502E+09 | 77.50 | 23.30 | 19.40 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.262709E+09 | 1876.68 | 31-JAN-09:02 | 10.78 | 4.13 | 97100334.75 | 56.69 | 03-JAN-22:10 | 10.78 | 4.13 |
February | 0.463470E+09 | 1938.00 | 20-FEB-16:02 | 23.12 | 8.59 | 88418261.85 | 56.69 | 21-FEB-22:10 | 13.67 | 4.04 |
March | 0.744980E+09 | 1939.94 | 16-MAR-15:02 | 22.70 | 8.66 | 98448737.73 | 56.69 | 21-MAR-21:19 | 16.30 | 5.41 |
April | 0.157256E+10 | 1975.58 | 21-APR-15:02 | 32.02 | 15.38 | 95882621.52 | 56.69 | 17-APR-03:20 | 32.02 | 15.38 |
May | 0.222139E+10 | 2013.62 | 20-MAY-08:62 | 24.37 | 10.75 | 99352335.62 | 56.69 | 28-MAY-00:40 | 20.77 | 16.69 |
June | 0.270014E+10 | 2024.92 | 21-JUN-08:62 | 27.43 | 15.97 | 96563758.99 | 58.68 | 14-JUN-21:10 | 27.43 | 15.97 |
July | 0.270113E+10 | 2032.16 | 11-JUL-08:62 | 27.48 | 17.81 | 99298015.77 | 56.70 | 03-JUL-03:09 | 27.48 | 17.81 |
August | 0.254873E+10 | 2018.38 | 04-AUG-08:61 | 25.97 | 17.82 | 99348784.74 | 56.70 | 28-AUG-22:10 | 23.72 | 16.65 |
September | 0.230465E+10 | 2013.23 | 16-SEP-08:62 | 22.07 | 16.46 | 96058103.20 | 56.70 | 14-SEP-21:40 | 22.07 | 16.46 |
October | 0.153229E+10 | 2020.13 | 05-OCT-08:62 | 23.17 | 17.04 | 98870537.91 | 56.70 | 05-OCT-21:00 | 22.80 | 16.23 |
November | 0.668283E+09 | 1940.97 | 09-NOV-09:02 | 16.97 | 7.95 | 94870505.84 | 56.69 | 08-NOV-22:19 | 16.97 | 7.95 |
December | 0.202573E+09 | 1885.99 | 16-DEC-09:02 | 8.48 | 2.42 | 96817239.35 | 56.69 | 13-DEC-01:19 | 8.48 | 2.42 |
Annual Sum or Average | 0.179229E+11 | 0.116103E+10 | ||||||||
Minimum of Months | 0.202573E+09 | 1876.68 | 8.48 | 2.42 | 88418261.85 | 56.69 | 8.48 | 2.42 | ||
Maximum of Months | 0.270113E+10 | 2032.16 | 32.02 | 17.82 | 99352335.62 | 58.68 | 32.02 | 17.81 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 59734160.16 | 1757.11 | 31-JAN-09:02 | 10.78 | 4.13 | 95081636.32 | 56.69 | 30-JAN-05:19 | 10.78 | 4.13 |
February | 0.184817E+09 | 1905.76 | 22-FEB-16:01 | 22.62 | 8.47 | 87588987.58 | 65.79 | 22-FEB-22:10 | 14.40 | 4.90 |
March | 0.404012E+09 | 1900.35 | 22-MAR-15:02 | 23.90 | 8.87 | 99587407.72 | 68.50 | 15-MAR-21:30 | 23.90 | 8.87 |
April | 0.123838E+10 | 2314.74 | 27-APR-08:51 | 20.60 | 11.74 | 99315347.66 | 74.24 | 28-APR-21:40 | 22.07 | 12.89 |
May | 0.197971E+10 | 2398.19 | 20-MAY-08:32 | 25.77 | 11.62 | 0.103471E+09 | 75.95 | 17-MAY-21:19 | 25.77 | 11.62 |
June | 0.255206E+10 | 2396.94 | 13-JUN-08:12 | 25.93 | 11.50 | 0.100159E+09 | 78.76 | 23-JUN-21:10 | 23.30 | 15.34 |
July | 0.253118E+10 | 2328.05 | 04-JUL-08:62 | 25.18 | 18.51 | 0.102835E+09 | 74.69 | 21-JUL-21:00 | 23.90 | 20.39 |
August | 0.224893E+10 | 2296.22 | 30-AUG-08:51 | 23.30 | 15.51 | 0.103160E+09 | 80.55 | 11-AUG-21:10 | 23.30 | 15.51 |
September | 0.176043E+10 | 2270.87 | 19-SEP-08:51 | 26.10 | 16.81 | 0.101001E+09 | 77.48 | 06-SEP-21:10 | 26.10 | 16.81 |
October | 0.925166E+09 | 2213.77 | 03-OCT-08:51 | 23.30 | 15.83 | 0.102811E+09 | 78.92 | 05-OCT-21:10 | 23.22 | 16.17 |
November | 0.246743E+09 | 2058.26 | 09-NOV-09:51 | 18.30 | 8.77 | 94289347.33 | 68.17 | 09-NOV-22:40 | 17.43 | 10.49 |
December | 43791457.17 | 1811.41 | 16-DEC-09:02 | 8.48 | 2.42 | 94686146.05 | 56.69 | 19-DEC-05:19 | -3.5 | -7.1 |
Annual Sum or Average | 0.141750E+11 | 0.118399E+10 | ||||||||
Minimum of Months | 43791457.17 | 1757.11 | 8.48 | 2.42 | 87588987.58 | 56.69 | -3.5 | -7.1 | ||
Maximum of Months | 0.255206E+10 | 2398.19 | 26.10 | 18.51 | 0.103471E+09 | 80.55 | 26.10 | 20.39 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.337263E+10 | 1725.09 | 01-JAN-11:33 | 13.87 | 8.54 | 0.126184E+10 | 808.93 | 03-JAN-22:40 | 11.33 | 5.60 |
February | 0.327175E+10 | 1823.02 | 20-FEB-11:33 | 20.37 | 8.19 | 0.117506E+10 | 835.36 | 22-FEB-23:10 | 14.03 | 4.88 |
March | 0.382471E+10 | 1867.86 | 16-MAR-18:10 | 19.82 | 7.14 | 0.134743E+10 | 858.83 | 16-MAR-21:40 | 16.47 | 6.01 |
April | 0.423459E+10 | 2168.42 | 30-APR-10:33 | 24.07 | 13.08 | 0.140638E+10 | 914.47 | 21-APR-21:49 | 24.07 | 13.08 |
May | 0.482402E+10 | 2284.29 | 20-MAY-10:33 | 28.30 | 13.16 | 0.154467E+10 | 951.82 | 31-MAY-21:19 | 27.97 | 13.53 |
June | 0.519568E+10 | 3173.90 | 15-JUN-18:40 | 35.37 | 14.55 | 0.155519E+10 | 951.86 | 27-JUN-22:10 | 27.12 | 17.05 |
July | 0.525687E+10 | 2789.46 | 26-JUL-18:25 | 32.50 | 19.69 | 0.159537E+10 | 951.86 | 05-JUL-21:00 | 32.50 | 19.69 |
August | 0.516295E+10 | 2848.69 | 07-AUG-18:25 | 33.05 | 18.14 | 0.159242E+10 | 951.85 | 11-AUG-22:10 | 22.80 | 17.38 |
September | 0.487688E+10 | 2566.65 | 20-SEP-18:17 | 30.40 | 15.98 | 0.152791E+10 | 951.85 | 20-SEP-22:10 | 26.52 | 16.85 |
October | 0.453755E+10 | 2274.33 | 05-OCT-10:33 | 27.60 | 18.63 | 0.149109E+10 | 951.85 | 05-OCT-22:10 | 22.98 | 16.25 |
November | 0.376391E+10 | 1976.40 | 10-NOV-11:33 | 20.93 | 12.02 | 0.132003E+10 | 881.71 | 01-NOV-00:10 | 20.93 | 12.02 |
December | 0.317587E+10 | 1653.09 | 10-DEC-11:35 | 15.93 | 7.48 | 0.123715E+10 | 766.63 | 15-DEC-22:49 | 13.98 | 4.58 |
Annual Sum or Average | 0.514974E+11 | 0.170545E+11 | ||||||||
Minimum of Months | 0.317587E+10 | 1653.09 | 13.87 | 7.14 | 0.117506E+10 | 766.63 | 11.33 | 4.58 | ||
Maximum of Months | 0.525687E+10 | 3173.90 | 35.37 | 19.69 | 0.159537E+10 | 951.86 | 32.50 | 19.69 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.220397E+09 | 2226.73 | 30-JAN-16:02 | 15.60 | 6.01 | 96307814.79 | 56.69 | 03-JAN-22:10 | 15.60 | 6.01 |
February | 0.340971E+09 | 2338.04 | 20-FEB-16:02 | 23.12 | 8.59 | 87606720.37 | 56.69 | 21-FEB-01:10 | 8.98 | 2.51 |
March | 0.632548E+09 | 2334.39 | 14-MAR-15:02 | 23.98 | 9.90 | 97742409.53 | 56.69 | 15-MAR-01:19 | 8.53 | 3.47 |
April | 0.144745E+10 | 2374.88 | 16-APR-15:02 | 29.50 | 11.50 | 95535732.86 | 56.70 | 23-APR-01:39 | 12.03 | 4.60 |
May | 0.215799E+10 | 2375.79 | 17-MAY-15:02 | 29.40 | 13.34 | 99637657.95 | 56.69 | 22-MAY-22:10 | 23.22 | 14.22 |
June | 0.270698E+10 | 2400.00 | 14-JUN-15:02 | 37.88 | 15.65 | 97125717.32 | 59.04 | 15-JUN-21:10 | 32.57 | 13.55 |
July | 0.271486E+10 | 2359.00 | 31-JUL-18:02 | 33.22 | 19.45 | 99576779.00 | 56.70 | 06-JUL-22:30 | 33.22 | 19.45 |
August | 0.253022E+10 | 2361.79 | 28-AUG-18:02 | 29.03 | 17.18 | 99620047.93 | 56.70 | 06-AUG-23:00 | 29.03 | 17.18 |
September | 0.225355E+10 | 2361.64 | 01-SEP-18:02 | 31.13 | 18.07 | 96218205.68 | 56.70 | 20-SEP-21:49 | 26.32 | 16.59 |
October | 0.147799E+10 | 2346.33 | 31-OCT-15:02 | 21.60 | 7.74 | 98788173.18 | 56.70 | 18-OCT-21:49 | 21.60 | 7.74 |
November | 0.563888E+09 | 2309.57 | 07-NOV-16:02 | 21.52 | 10.29 | 94256519.65 | 56.69 | 15-NOV-00:40 | 10.37 | 4.00 |
December | 0.144724E+09 | 2226.48 | 16-DEC-16:02 | 14.72 | 4.08 | 96039579.96 | 56.69 | 21-DEC-05:19 | 1.13 | -2.2 |
Annual Sum or Average | 0.171916E+11 | 0.115846E+10 | ||||||||
Minimum of Months | 0.144724E+09 | 2226.48 | 14.72 | 4.08 | 87606720.37 | 56.69 | 1.13 | -2.2 | ||
Maximum of Months | 0.271486E+10 | 2400.00 | 37.88 | 19.45 | 99637657.95 | 59.04 | 33.22 | 19.45 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 48540297.42 | 2085.02 | 30-JAN-16:02 | 15.60 | 6.01 | 94536651.64 | 56.69 | 23-JAN-05:19 | 15.60 | 6.01 |
February | 92085733.85 | 2266.71 | 20-FEB-16:02 | 23.12 | 8.59 | 87060915.85 | 61.71 | 22-FEB-22:10 | 14.40 | 4.90 |
March | 0.263617E+09 | 2265.04 | 16-MAR-15:02 | 22.70 | 8.66 | 99853647.59 | 69.19 | 16-MAR-21:40 | 16.47 | 6.01 |
April | 0.114033E+10 | 2552.90 | 06-APR-18:11 | 14.63 | 6.39 | 99162911.94 | 75.68 | 28-APR-21:40 | 22.07 | 12.89 |
May | 0.201442E+10 | 2486.26 | 20-MAY-08:51 | 26.70 | 12.19 | 0.102556E+09 | 79.30 | 23-MAY-21:10 | 22.02 | 16.25 |
June | 0.264982E+10 | 2620.37 | 19-JUN-18:51 | 27.20 | 19.20 | 99398864.04 | 79.12 | 23-JUN-21:19 | 23.30 | 15.34 |
July | 0.262668E+10 | 2408.61 | 25-JUL-18:02 | 34.32 | 19.47 | 0.101958E+09 | 75.81 | 21-JUL-21:00 | 34.32 | 19.47 |
August | 0.231540E+10 | 2422.60 | 26-AUG-08:11 | 27.07 | 15.12 | 0.102271E+09 | 80.04 | 11-AUG-21:10 | 27.07 | 15.12 |
September | 0.180463E+10 | 2349.93 | 01-SEP-18:02 | 31.13 | 18.07 | 99820025.46 | 78.40 | 13-SEP-21:10 | 21.70 | 17.29 |
October | 0.851632E+09 | 2312.27 | 03-OCT-18:21 | 24.70 | 18.40 | 0.103705E+09 | 80.49 | 05-OCT-21:10 | 23.22 | 16.17 |
November | 0.153863E+09 | 2226.33 | 07-NOV-16:02 | 21.52 | 10.29 | 94053935.04 | 67.80 | 09-NOV-22:40 | 17.43 | 10.49 |
December | 26174162.53 | 2140.72 | 16-DEC-16:02 | 14.72 | 4.08 | 94049430.84 | 56.69 | 22-DEC-05:19 | -3.5 | -5.3 |
Annual Sum or Average | 0.139872E+11 | 0.117843E+10 | ||||||||
Minimum of Months | 26174162.53 | 2085.02 | 14.63 | 4.08 | 87060915.85 | 56.69 | -3.5 | -5.3 | ||
Maximum of Months | 0.264982E+10 | 2620.37 | 34.32 | 19.47 | 0.103705E+09 | 80.49 | 34.32 | 19.47 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.570135E+09 | 1191.55 | 28-JAN-16:02 | 13.22 | 5.14 | 98072683.45 | 56.69 | 03-JAN-22:19 | 13.22 | 5.14 |
February | 0.576134E+09 | 1232.18 | 20-FEB-16:02 | 23.12 | 8.59 | 88807858.73 | 56.69 | 21-FEB-22:00 | 10.00 | 2.29 |
March | 0.592285E+09 | 1233.28 | 14-MAR-15:02 | 23.98 | 9.90 | 98388625.45 | 56.69 | 21-MAR-21:10 | 16.20 | 5.40 |
April | 0.862340E+09 | 1221.91 | 15-APR-15:02 | 27.20 | 11.79 | 95554712.33 | 56.69 | 28-APR-21:10 | 22.62 | 12.85 |
May | 0.109344E+10 | 1202.51 | 24-MAY-15:02 | 28.58 | 18.02 | 99025921.79 | 56.69 | 22-MAY-22:00 | 28.58 | 18.02 |
June | 0.135136E+10 | 1209.59 | 28-JUN-15:02 | 27.88 | 17.30 | 96294586.98 | 58.31 | 14-JUN-21:10 | 27.88 | 17.30 |
July | 0.141394E+10 | 1217.97 | 26-JUL-15:02 | 36.60 | 20.09 | 99161967.53 | 56.70 | 03-JUL-22:40 | 36.60 | 20.09 |
August | 0.141709E+10 | 1224.65 | 05-AUG-15:02 | 32.98 | 18.87 | 99250243.27 | 56.70 | 18-AUG-21:40 | 25.20 | 17.95 |
September | 0.143332E+10 | 1235.57 | 06-SEP-15:02 | 27.43 | 17.91 | 96081182.50 | 56.69 | 12-SEP-22:40 | 25.20 | 17.43 |
October | 0.123230E+10 | 1248.10 | 18-OCT-15:02 | 28.90 | 17.08 | 99173009.22 | 56.70 | 17-OCT-21:40 | 28.90 | 17.08 |
November | 0.819868E+09 | 1224.86 | 14-NOV-16:02 | 20.92 | 8.21 | 95320712.47 | 56.69 | 09-NOV-22:19 | 20.92 | 8.21 |
December | 0.520364E+09 | 1192.10 | 16-DEC-16:02 | 14.72 | 4.08 | 98054522.99 | 56.69 | 05-DEC-22:10 | 14.72 | 4.08 |
Annual Sum or Average | 0.118826E+11 | 0.116319E+10 | ||||||||
Minimum of Months | 0.520364E+09 | 1191.55 | 13.22 | 4.08 | 88807858.73 | 56.69 | 10.00 | 2.29 | ||
Maximum of Months | 0.143332E+10 | 1248.10 | 36.60 | 20.09 | 99250243.27 | 58.31 | 36.60 | 20.09 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.322187E+11 | 18395.97 | 03-JAN-22:10 | 12.43 | 6.06 | 0.190992E+11 | 11347.38 | 30-JAN-00:20 | 4.03 | -0.8 |
February | 0.302681E+11 | 19458.15 | 07-FEB-23:00 | 15.60 | 8.35 | 0.173248E+11 | 11348.12 | 22-FEB-22:19 | 14.40 | 4.92 |
March | 0.352227E+11 | 20318.07 | 15-MAR-21:53 | 19.40 | 7.29 | 0.192998E+11 | 11348.49 | 16-MAR-22:10 | 15.27 | 5.99 |
April | 0.382047E+11 | 22208.21 | 19-APR-22:00 | 27.20 | 11.76 | 0.186942E+11 | 11349.86 | 17-APR-01:10 | 27.20 | 11.76 |
May | 0.428720E+11 | 23185.42 | 31-MAY-21:10 | 28.13 | 13.59 | 0.193446E+11 | 11352.47 | 31-MAY-22:00 | 26.20 | 12.33 |
June | 0.443970E+11 | 23785.66 | 15-JUN-21:20 | 31.83 | 13.36 | 0.187602E+11 | 11366.75 | 15-JUN-21:19 | 31.83 | 13.36 |
July | 0.456032E+11 | 23589.18 | 25-JUL-21:10 | 31.42 | 17.57 | 0.193093E+11 | 11363.01 | 27-JUL-22:00 | 27.20 | 17.66 |
August | 0.445810E+11 | 23739.04 | 07-AUG-21:20 | 30.80 | 17.26 | 0.193895E+11 | 11364.97 | 04-AUG-22:00 | 30.80 | 17.26 |
September | 0.412723E+11 | 22608.90 | 22-SEP-22:00 | 25.00 | 17.90 | 0.187059E+11 | 11348.98 | 28-SEP-22:10 | 24.40 | 12.24 |
October | 0.388890E+11 | 22102.47 | 05-OCT-21:52 | 22.80 | 16.23 | 0.192871E+11 | 11348.86 | 05-OCT-22:10 | 22.98 | 16.25 |
November | 0.330315E+11 | 20276.40 | 09-NOV-22:10 | 18.53 | 10.92 | 0.185549E+11 | 11348.19 | 08-NOV-23:10 | 18.53 | 10.92 |
December | 0.314189E+11 | 18326.95 | 15-DEC-23:00 | 13.90 | 4.56 | 0.190560E+11 | 11347.50 | 01-DEC-05:19 | 13.90 | 4.56 |
Annual Sum or Average | 0.457979E+12 | 0.226825E+12 | ||||||||
Minimum of Months | 0.302681E+11 | 18326.95 | 12.43 | 4.56 | 0.173248E+11 | 11347.38 | 4.03 | -0.8 | ||
Maximum of Months | 0.456032E+11 | 23785.66 | 31.83 | 17.90 | 0.193895E+11 | 11366.75 | 31.83 | 17.66 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.359039E+11 | 20187.10 | 03-JAN-22:10 | 12.43 | 6.06 | 0.192151E+11 | 11347.52 | 30-JAN-00:20 | 4.03 | -0.8 |
February | 0.335866E+11 | 21126.53 | 06-FEB-22:20 | 18.33 | 6.86 | 0.174020E+11 | 11348.15 | 22-FEB-22:19 | 14.40 | 4.92 |
March | 0.388879E+11 | 21883.92 | 15-MAR-21:53 | 19.40 | 7.29 | 0.193630E+11 | 11348.50 | 16-MAR-22:10 | 15.27 | 5.99 |
April | 0.414159E+11 | 23570.51 | 19-APR-21:10 | 28.12 | 12.29 | 0.187119E+11 | 11350.06 | 17-APR-01:10 | 28.12 | 12.29 |
May | 0.458325E+11 | 24370.50 | 19-MAY-21:20 | 29.80 | 13.44 | 0.193491E+11 | 11355.06 | 31-MAY-21:19 | 27.97 | 13.53 |
June | 0.470797E+11 | 24970.42 | 15-JUN-21:20 | 31.83 | 13.36 | 0.187611E+11 | 11373.93 | 15-JUN-21:19 | 31.83 | 13.36 |
July | 0.483670E+11 | 24766.35 | 25-JUL-21:10 | 31.42 | 17.57 | 0.193101E+11 | 11364.53 | 10-JUL-22:00 | 31.42 | 17.57 |
August | 0.473653E+11 | 24905.72 | 07-AUG-21:20 | 30.80 | 17.26 | 0.193910E+11 | 11364.57 | 04-AUG-22:00 | 30.80 | 17.26 |
September | 0.439999E+11 | 23734.90 | 22-SEP-21:10 | 25.00 | 17.90 | 0.187096E+11 | 11348.98 | 28-SEP-22:10 | 24.40 | 12.24 |
October | 0.419965E+11 | 23252.41 | 04-OCT-21:10 | 25.32 | 17.67 | 0.193082E+11 | 11348.86 | 05-OCT-22:10 | 22.98 | 16.25 |
November | 0.364005E+11 | 21762.87 | 09-NOV-22:10 | 18.53 | 10.92 | 0.186289E+11 | 11348.21 | 08-NOV-23:10 | 18.53 | 10.92 |
December | 0.350887E+11 | 20157.71 | 15-DEC-23:00 | 13.90 | 4.56 | 0.191956E+11 | 11347.60 | 01-DEC-05:19 | 13.90 | 4.56 |
Annual Sum or Average | 0.495924E+12 | 0.227346E+12 | ||||||||
Minimum of Months | 0.335866E+11 | 20157.71 | 12.43 | 4.56 | 0.174020E+11 | 11347.52 | 4.03 | -0.8 | ||
Maximum of Months | 0.483670E+11 | 24970.42 | 31.83 | 17.90 | 0.193910E+11 | 11373.93 | 31.83 | 17.57 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.504439E+11 | 27522.86 | 01-JAN-11:50 | 14.13 | 8.64 | 0.188428E+11 | 11319.52 | 07-JAN-18:19 | 12.07 | 5.16 |
February | 0.465437E+11 | 28520.90 | 20-FEB-11:50 | 20.73 | 8.30 | 0.170248E+11 | 11319.48 | 04-FEB-18:19 | 20.73 | 8.30 |
March | 0.526287E+11 | 28753.43 | 19-MAR-10:33 | 18.67 | 7.01 | 0.188610E+11 | 11319.58 | 25-MAR-17:19 | 21.10 | 8.62 |
April | 0.536892E+11 | 30338.64 | 30-APR-10:50 | 24.53 | 12.98 | 0.182582E+11 | 11319.65 | 15-APR-17:19 | 24.53 | 12.98 |
May | 0.574812E+11 | 30487.57 | 21-MAY-10:33 | 29.47 | 14.38 | 0.188711E+11 | 11319.65 | 06-MAY-17:19 | 29.47 | 14.38 |
June | 0.574624E+11 | 30951.57 | 18-JUN-10:40 | 32.43 | 16.35 | 0.182662E+11 | 11319.63 | 24-JUN-17:19 | 31.67 | 16.29 |
July | 0.593126E+11 | 31104.54 | 02-JUL-10:40 | 32.23 | 20.13 | 0.188684E+11 | 11319.66 | 22-JUL-17:19 | 30.60 | 19.89 |
August | 0.587240E+11 | 31018.34 | 06-AUG-10:37 | 31.67 | 18.03 | 0.188756E+11 | 11319.65 | 19-AUG-17:19 | 31.33 | 15.73 |
September | 0.559839E+11 | 30709.45 | 17-SEP-10:33 | 29.47 | 15.71 | 0.182614E+11 | 11319.66 | 23-SEP-17:19 | 17.80 | 17.32 |
October | 0.550521E+11 | 30188.70 | 05-OCT-10:33 | 27.60 | 18.63 | 0.188648E+11 | 11319.63 | 28-OCT-17:19 | 22.23 | 13.64 |
November | 0.501857E+11 | 28307.68 | 10-NOV-11:50 | 21.02 | 12.06 | 0.182412E+11 | 11319.51 | 04-NOV-17:19 | 21.02 | 12.06 |
December | 0.499734E+11 | 27482.13 | 10-DEC-11:50 | 16.32 | 7.64 | 0.188382E+11 | 11319.77 | 02-DEC-18:19 | 16.32 | 7.64 |
Annual Sum or Average | 0.647481E+12 | 0.222074E+12 | ||||||||
Minimum of Months | 0.465437E+11 | 27482.13 | 14.13 | 7.01 | 0.170248E+11 | 11319.48 | 12.07 | 5.16 | ||
Maximum of Months | 0.593126E+11 | 31104.54 | 32.43 | 20.13 | 0.188756E+11 | 11319.77 | 31.67 | 19.89 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.612033E+10 | 3511.92 | 01-JAN-11:33 | 13.87 | 8.54 | 0.130538E+10 | 835.05 | 12-JAN-22:30 | 8.90 | 4.67 |
February | 0.619411E+10 | 3840.50 | 20-FEB-11:33 | 20.37 | 8.19 | 0.121299E+10 | 869.94 | 07-FEB-22:40 | 20.37 | 8.19 |
March | 0.745696E+10 | 3863.26 | 16-MAR-10:33 | 20.03 | 8.28 | 0.138998E+10 | 905.61 | 16-MAR-21:40 | 16.47 | 6.01 |
April | 0.869017E+10 | 4623.95 | 30-APR-10:33 | 24.07 | 13.08 | 0.148599E+10 | 1000.38 | 21-APR-21:40 | 24.07 | 13.08 |
May | 0.102134E+11 | 5654.31 | 30-MAY-15:02 | 34.32 | 17.72 | 0.164540E+10 | 1007.39 | 17-MAY-22:10 | 34.32 | 17.72 |
June | 0.117466E+11 | 6522.71 | 17-JUN-17:13 | 36.10 | 16.68 | 0.164936E+10 | 1007.44 | 30-JUN-22:10 | 28.43 | 17.10 |
July | 0.120540E+11 | 6866.53 | 03-JUL-12:50 | 36.52 | 18.58 | 0.169769E+10 | 1007.42 | 05-JUL-21:00 | 27.80 | 17.53 |
August | 0.115784E+11 | 6718.28 | 07-AUG-15:04 | 35.37 | 18.63 | 0.169255E+10 | 1007.44 | 22-AUG-00:10 | 24.22 | 16.48 |
September | 0.105000E+11 | 6241.23 | 21-SEP-14:10 | 31.78 | 18.05 | 0.160801E+10 | 1007.41 | 20-SEP-22:10 | 31.78 | 18.05 |
October | 0.921099E+10 | 5784.88 | 05-OCT-15:03 | 30.68 | 17.34 | 0.155180E+10 | 1007.40 | 05-OCT-22:10 | 22.98 | 16.25 |
November | 0.707431E+10 | 4161.86 | 10-NOV-11:33 | 20.93 | 12.02 | 0.133829E+10 | 924.25 | 09-NOV-22:30 | 20.93 | 12.02 |
December | 0.544273E+10 | 3426.20 | 16-DEC-11:33 | 12.77 | 3.51 | 0.129023E+10 | 810.73 | 15-DEC-22:40 | 12.77 | 3.51 |
Annual Sum or Average | 0.106282E+12 | 0.178677E+11 | ||||||||
Minimum of Months | 0.544273E+10 | 3426.20 | 12.77 | 3.51 | 0.121299E+10 | 810.73 | 8.90 | 3.51 | ||
Maximum of Months | 0.120540E+11 | 6866.53 | 36.52 | 18.63 | 0.169769E+10 | 1007.44 | 34.32 | 18.05 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 533247.04 | 127.16 | 27-JAN-07:30 | -4.2 |
February | 242824.06 | 75.11 | 03-FEB-07:05 | -5.1 |
March | 26633.72 | 28.56 | 02-MAR-07:10 | -1.6 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 356453.54 | 87.06 | 28-NOV-05:00 | -0.6 |
December | 10182411.57 | 567.02 | 27-DEC-07:30 | -4.2 |
Annual Sum or Average | 11341569.93 | |||
Minimum of Months | 0.00 | 0.00 | -5.1 | |
Maximum of Months | 10182411.57 | 567.02 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.223083E+09 | 1312.21 | 15-JAN-16:02 | 10.00 |
February | 0.127588E+09 | 1298.45 | 02-FEB-09:02 | 1.38 |
March | 54447717.16 | 1310.77 | 02-MAR-09:02 | 0.47 |
April | 2421301.33 | 609.46 | 13-APR-08:03 | 11.33 |
May | 283354.29 | 547.01 | 08-MAY-08:05 | 20.23 |
June | 21106.44 | 211.06 | 29-JUN-08:05 | 18.58 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 112879.09 | 292.91 | 14-AUG-08:06 | 18.40 |
September | 123699.83 | 448.66 | 28-SEP-08:05 | 18.68 |
October | 793013.60 | 609.95 | 14-OCT-18:05 | 18.72 |
November | 93562168.39 | 1317.38 | 27-NOV-09:02 | 3.98 |
December | 0.325862E+09 | 1355.88 | 26-DEC-16:02 | 2.12 |
Annual Sum or Average | 0.828298E+09 | |||
Minimum of Months | 0.00 | 0.00 | 0.47 | |
Maximum of Months | 0.325862E+09 | 1355.88 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.420756E+09 | 1342.68 | 26-JAN-09:02 | 2.30 |
February | 0.236035E+09 | 1349.47 | 02-FEB-09:02 | 1.38 |
March | 86085992.65 | 1331.01 | 02-MAR-09:02 | 0.47 |
April | 2685156.74 | 661.66 | 13-APR-08:03 | 11.33 |
May | 262271.28 | 520.94 | 04-MAY-06:44 | 15.10 |
June | 1630.35 | 13.98 | 13-JUN-08:36 | 26.87 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 4700.67 | 43.48 | 08-AUG-06:56 | 24.40 |
September | 124398.93 | 371.84 | 29-SEP-06:25 | 15.80 |
October | 889164.15 | 645.78 | 11-OCT-08:03 | 12.15 |
November | 0.163082E+09 | 1331.77 | 28-NOV-09:02 | 4.18 |
December | 0.584309E+09 | 1364.57 | 27-DEC-09:02 | -0.7 |
Annual Sum or Average | 0.149424E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.7 | |
Maximum of Months | 0.584309E+09 | 1364.57 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 15938229.59 | 393.41 | 27-JAN-16:02 | 9.50 |
February | 10526591.11 | 391.68 | 07-FEB-16:04 | 18.98 |
March | 2187383.74 | 406.41 | 29-MAR-15:03 | 16.28 |
April | 205677.49 | 403.37 | 11-APR-15:04 | 16.78 |
May | 23288.07 | 230.37 | 01-MAY-08:54 | 17.20 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 12084.91 | 61.60 | 20-SEP-08:56 | 26.10 |
October | 49438.73 | 192.73 | 25-OCT-08:05 | 11.15 |
November | 3448296.10 | 385.72 | 28-NOV-16:02 | 11.52 |
December | 35935180.96 | 402.66 | 10-DEC-16:03 | 17.12 |
Annual Sum or Average | 68326170.70 | |||
Minimum of Months | 0.00 | 0.00 | 9.50 | |
Maximum of Months | 35935180.96 | 406.41 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.240571E+09 | 1283.11 | 15-JAN-16:02 | 10.00 |
February | 0.122158E+09 | 1029.85 | 13-FEB-16:02 | 12.30 |
March | 58494349.52 | 1244.32 | 02-MAR-09:02 | 0.47 |
April | 1873084.78 | 270.88 | 22-APR-18:05 | 18.03 |
May | 8531.18 | 71.09 | 03-MAY-08:06 | 19.18 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.03 |
July | 9352.40 | 93.52 | 19-JUL-08:07 | 20.78 |
August | 51929.06 | 237.78 | 17-AUG-08:06 | 18.48 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 447108.04 | 485.73 | 15-OCT-18:05 | 18.72 |
November | 0.104923E+09 | 1276.77 | 28-NOV-16:02 | 11.52 |
December | 0.334382E+09 | 1323.65 | 26-DEC-16:02 | 2.12 |
Annual Sum or Average | 0.862918E+09 | |||
Minimum of Months | 0.00 | 0.00 | 0.47 | |
Maximum of Months | 0.334382E+09 | 1323.65 | 25.03 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.431125E+09 | 1287.41 | 15-JAN-16:02 | 10.00 |
February | 0.211266E+09 | 1268.78 | 02-FEB-16:02 | 10.60 |
March | 94176226.10 | 1263.72 | 02-MAR-16:01 | 12.30 |
April | 2448970.75 | 1021.43 | 11-APR-15:04 | 16.78 |
May | 14284.93 | 88.43 | 04-MAY-21:56 | 20.60 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 1543902.02 | 589.88 | 07-OCT-15:05 | 17.88 |
November | 0.176893E+09 | 1291.41 | 28-NOV-16:02 | 11.52 |
December | 0.574887E+09 | 1328.10 | 26-DEC-16:02 | 2.12 |
Annual Sum or Average | 0.149235E+10 | |||
Minimum of Months | 0.00 | 0.00 | 2.12 | |
Maximum of Months | 0.574887E+09 | 1328.10 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.485668E+09 | 1603.11 | 14-JAN-16:02 | 7.88 |
February | 0.306260E+09 | 1592.80 | 02-FEB-09:02 | 1.38 |
March | 0.174432E+09 | 1600.07 | 02-MAR-09:02 | 0.47 |
April | 20555952.69 | 1532.85 | 11-APR-08:62 | 6.88 |
May | 590962.17 | 548.77 | 26-MAY-08:05 | 20.37 |
June | 81210.03 | 446.09 | 29-JUN-08:05 | 18.58 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 296995.37 | 470.50 | 16-AUG-08:05 | 20.60 |
September | 297300.39 | 499.14 | 25-SEP-08:04 | 16.57 |
October | 4956733.30 | 556.25 | 06-OCT-18:05 | 14.22 |
November | 0.248702E+09 | 1607.00 | 27-NOV-09:02 | 3.98 |
December | 0.637642E+09 | 1636.82 | 26-DEC-16:02 | 2.12 |
Annual Sum or Average | 0.187948E+10 | |||
Minimum of Months | 0.00 | 0.00 | 0.47 | |
Maximum of Months | 0.637642E+09 | 1636.82 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.787677E+09 | 1624.57 | 06-JAN-09:02 | 2.07 |
February | 0.484235E+09 | 1629.32 | 02-FEB-09:02 | 1.38 |
March | 0.233623E+09 | 1620.36 | 02-MAR-09:02 | 0.47 |
April | 20517903.89 | 1533.98 | 11-APR-08:62 | 6.88 |
May | 272146.24 | 702.06 | 01-MAY-08:53 | 17.20 |
June | 16846.93 | 144.29 | 11-JUN-08:36 | 25.53 |
July | 4681.36 | 41.06 | 29-JUL-06:55 | 25.00 |
August | 12259.44 | 179.62 | 30-AUG-08:54 | 23.30 |
September | 201274.01 | 431.27 | 25-SEP-08:53 | 18.90 |
October | 7215736.23 | 746.18 | 25-OCT-08:62 | 11.15 |
November | 0.393393E+09 | 1617.65 | 28-NOV-09:02 | 4.18 |
December | 0.100386E+10 | 1645.60 | 27-DEC-09:02 | -0.7 |
Annual Sum or Average | 0.293103E+10 | |||
Minimum of Months | 4681.36 | 41.06 | -0.7 | |
Maximum of Months | 0.100386E+10 | 1645.60 | 25.53 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 60557225.35 | 820.39 | 15-JAN-16:02 | 10.00 |
February | 38646747.49 | 272.59 | 02-FEB-06:00 | -3.3 |
March | 25363876.85 | 805.56 | 02-MAR-09:02 | 0.47 |
April | 2318624.43 | 304.98 | 13-APR-08:03 | 11.33 |
May | 229407.51 | 238.38 | 10-MAY-08:05 | 20.78 |
June | 26366.96 | 263.67 | 29-JUN-08:05 | 18.58 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 18867.63 | 112.08 | 14-AUG-08:06 | 18.40 |
September | 13495.75 | 80.70 | 24-SEP-08:05 | 16.93 |
October | 122804.41 | 306.79 | 07-OCT-18:05 | 17.62 |
November | 32967535.45 | 814.90 | 27-NOV-09:02 | 3.98 |
December | 97316766.59 | 830.31 | 26-DEC-16:02 | 2.12 |
Annual Sum or Average | 0.257582E+09 | |||
Minimum of Months | 0.00 | 0.00 | -3.3 | |
Maximum of Months | 97316766.59 | 830.31 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1183913.75 | 302.80 | 27-JAN-07:30 | -4.2 |
February | 1572251.32 | 420.01 | 03-FEB-07:05 | -5.1 |
March | 12920.02 | 28.33 | 02-MAR-07:10 | -1.6 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.60 |
December | 11173279.82 | 801.30 | 27-DEC-07:20 | -4.2 |
Annual Sum or Average | 13942364.91 | |||
Minimum of Months | 0.00 | 0.00 | -5.1 | |
Maximum of Months | 11173279.82 | 801.30 | 27.63 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.136942E+11 | 13190.31 | 02-JAN-20:10 | 0.121516E+11 | 9632.53 | 02-JAN-20:10 |
February | 0.123646E+11 | 13190.31 | 01-FEB-20:10 | 0.109726E+11 | 9632.53 | 01-FEB-20:10 |
March | 0.137364E+11 | 13190.31 | 01-MAR-20:10 | 0.121771E+11 | 9632.53 | 01-MAR-20:10 |
April | 0.132299E+11 | 13190.31 | 03-APR-19:10 | 0.117446E+11 | 9632.53 | 03-APR-19:10 |
May | 0.137180E+11 | 13190.31 | 01-MAY-19:10 | 0.121662E+11 | 9632.53 | 01-MAY-19:10 |
June | 0.132906E+11 | 13190.31 | 01-JUN-19:10 | 0.117829E+11 | 9632.53 | 01-JUN-19:10 |
July | 0.136573E+11 | 13190.31 | 03-JUL-19:10 | 0.121279E+11 | 9632.53 | 03-JUL-19:10 |
August | 0.137417E+11 | 13190.31 | 01-AUG-19:10 | 0.121808E+11 | 9632.53 | 01-AUG-19:10 |
September | 0.132352E+11 | 13190.31 | 01-SEP-19:10 | 0.117482E+11 | 9632.53 | 01-SEP-19:10 |
October | 0.136889E+11 | 13190.31 | 02-OCT-19:10 | 0.121479E+11 | 9632.53 | 02-OCT-19:10 |
November | 0.132800E+11 | 13190.31 | 01-NOV-19:10 | 0.117774E+11 | 9632.53 | 01-NOV-19:10 |
December | 0.136573E+11 | 13190.31 | 01-DEC-20:10 | 0.121279E+11 | 9632.53 | 01-DEC-20:10 |
Annual Sum or Average | 0.161294E+12 | 0.143105E+12 | ||||
Minimum of Months | 0.123646E+11 | 13190.31 | 0.109726E+11 | 9632.53 | ||
Maximum of Months | 0.137417E+11 | 13190.31 | 0.121808E+11 | 9632.53 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.620421E+09 | 597.59 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.560184E+09 | 597.59 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.622334E+09 | 597.59 | 01-MAR-20:10 | 0.866718E+09 | 685.60 | 01-MAR-20:10 |
April | 0.599386E+09 | 597.59 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.621497E+09 | 597.59 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.602135E+09 | 597.59 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.618748E+09 | 597.59 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.622573E+09 | 597.59 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.599625E+09 | 597.59 | 01-SEP-19:10 | 0.836191E+09 | 685.60 | 01-SEP-19:10 |
October | 0.620182E+09 | 597.59 | 02-OCT-19:10 | 0.864640E+09 | 685.60 | 02-OCT-19:10 |
November | 0.601657E+09 | 597.59 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.618748E+09 | 597.59 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.730749E+10 | 0.101856E+11 | ||||
Minimum of Months | 0.560184E+09 | 597.59 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.622573E+09 | 597.59 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.718450E+09 | 692.02 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.648695E+09 | 692.02 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.720665E+09 | 692.02 | 01-MAR-20:10 | 0.100366E+10 | 793.93 | 01-MAR-20:10 |
April | 0.694091E+09 | 692.02 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.719696E+09 | 692.02 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.697275E+09 | 692.02 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.716513E+09 | 692.02 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.720942E+09 | 692.02 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.694368E+09 | 692.02 | 01-SEP-19:10 | 0.968312E+09 | 793.93 | 01-SEP-19:10 |
October | 0.718174E+09 | 692.02 | 02-OCT-19:10 | 0.100126E+10 | 793.93 | 02-OCT-19:10 |
November | 0.696721E+09 | 692.02 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.716513E+09 | 692.02 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.846210E+10 | 0.117950E+11 | ||||
Minimum of Months | 0.648695E+09 | 692.02 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.720942E+09 | 692.02 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.710312E+09 | 684.18 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.641347E+09 | 684.18 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.712502E+09 | 684.18 | 01-MAR-20:10 | 0.106120E+10 | 839.45 | 01-MAR-20:10 |
April | 0.686229E+09 | 684.18 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.711544E+09 | 684.18 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.689376E+09 | 684.18 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.708397E+09 | 684.18 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.712775E+09 | 684.18 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.686503E+09 | 684.18 | 01-SEP-19:10 | 0.102382E+10 | 839.45 | 01-SEP-19:10 |
October | 0.710039E+09 | 684.18 | 02-OCT-19:10 | 0.105866E+10 | 839.45 | 02-OCT-19:10 |
November | 0.688829E+09 | 684.18 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.708397E+09 | 684.18 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.836625E+10 | 0.124712E+11 | ||||
Minimum of Months | 0.641347E+09 | 684.18 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.712775E+09 | 684.18 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.261454E+09 | 251.84 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.236069E+09 | 251.84 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.262260E+09 | 251.84 | 01-MAR-20:10 | 0.306128E+09 | 242.16 | 01-MAR-20:10 |
April | 0.252589E+09 | 251.84 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.261907E+09 | 251.84 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.253748E+09 | 251.84 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.260749E+09 | 251.84 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.262360E+09 | 251.84 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.252690E+09 | 251.84 | 01-SEP-19:10 | 0.295345E+09 | 242.16 | 01-SEP-19:10 |
October | 0.261353E+09 | 251.84 | 02-OCT-19:10 | 0.305393E+09 | 242.16 | 02-OCT-19:10 |
November | 0.253546E+09 | 251.84 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.260749E+09 | 251.84 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.307947E+10 | 0.359760E+10 | ||||
Minimum of Months | 0.236069E+09 | 251.84 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.262360E+09 | 251.84 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.337502E+09 | 325.08 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.304733E+09 | 325.08 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.338542E+09 | 325.08 | 01-MAR-20:10 | 0.578079E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.326059E+09 | 325.08 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.338087E+09 | 325.08 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.327554E+09 | 325.08 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.336592E+09 | 325.08 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.338672E+09 | 325.08 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.326189E+09 | 325.08 | 01-SEP-19:10 | 0.557718E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.337372E+09 | 325.08 | 02-OCT-19:10 | 0.576693E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.327294E+09 | 325.08 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.336592E+09 | 325.08 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.397519E+10 | 0.679355E+11 | ||||
Minimum of Months | 0.304733E+09 | 325.08 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.338672E+09 | 325.08 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.132566E+10 | 1701.53 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.115622E+10 | 1701.53 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.123068E+10 | 1701.53 | 01-MAR-20:10 | 0.122027E+10 | 965.27 | 01-MAR-20:10 |
April | 0.112060E+10 | 1701.53 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.112432E+10 | 1701.53 | 01-MAY-19:10 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.105682E+10 | 1701.53 | 01-JUN-19:10 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.109484E+10 | 1701.53 | 03-JUL-19:10 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.116397E+10 | 1701.53 | 01-AUG-19:10 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.115946E+10 | 1701.53 | 01-SEP-19:10 | 0.117729E+10 | 965.27 | 01-SEP-19:10 |
October | 0.128391E+10 | 1701.53 | 02-OCT-19:10 | 0.121734E+10 | 965.27 | 02-OCT-19:10 |
November | 0.124152E+10 | 1701.53 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.131487E+10 | 1701.53 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.142729E+11 | 0.143405E+11 | ||||
Minimum of Months | 0.105682E+10 | 1701.53 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.132566E+10 | 1701.53 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.943854E+10 | 9504.80 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.848695E+10 | 9504.80 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.939774E+10 | 9504.80 | 01-MAR-20:10 | 0.126786E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.899513E+10 | 9504.80 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.929943E+10 | 9504.80 | 01-MAY-19:10 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.899697E+10 | 9504.80 | 01-JUN-19:10 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.925861E+10 | 9504.80 | 03-JUL-19:10 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.934824E+10 | 9504.80 | 01-AUG-19:10 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.904139E+10 | 9504.80 | 01-SEP-19:10 | 0.122320E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.939822E+10 | 9504.80 | 02-OCT-19:10 | 0.126482E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.910852E+10 | 9504.80 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.940104E+10 | 9504.80 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.110171E+12 | 0.148998E+12 | ||||
Minimum of Months | 0.848695E+10 | 9504.80 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.943854E+10 | 9504.80 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196602E+09 | 177.88 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.177551E+09 | 177.88 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.195039E+09 | 177.88 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.190486E+09 | 177.88 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.195821E+09 | 177.88 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.188975E+09 | 177.88 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.197358E+09 | 177.88 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.195039E+09 | 177.88 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.190538E+09 | 177.88 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.196576E+09 | 177.88 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.189731E+09 | 177.88 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.197383E+09 | 177.88 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.231110E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.177551E+09 | 177.88 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.197383E+09 | 177.88 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196579E+09 | 177.86 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.177530E+09 | 177.86 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.195017E+09 | 177.86 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.190464E+09 | 177.86 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.195798E+09 | 177.86 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.188953E+09 | 177.86 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.197334E+09 | 177.86 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.195017E+09 | 177.86 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.190515E+09 | 177.86 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.196553E+09 | 177.86 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.189708E+09 | 177.86 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.197360E+09 | 177.86 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.231083E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.177530E+09 | 177.86 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.197360E+09 | 177.86 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123557E+09 | 111.79 | 01-JAN-19:10 | 0.217935E+09 | 232.19 | 01-JAN-08:09 |
February | 0.111584E+09 | 111.79 | 01-FEB-20:10 | 0.196843E+09 | 232.19 | 01-FEB-07:10 |
March | 0.122575E+09 | 111.79 | 01-MAR-20:10 | 0.217824E+09 | 232.19 | 01-MAR-07:10 |
April | 0.119713E+09 | 111.79 | 01-APR-18:10 | 0.210923E+09 | 232.19 | 01-APR-07:10 |
May | 0.123066E+09 | 111.79 | 01-MAY-19:10 | 0.217879E+09 | 232.19 | 01-MAY-06:10 |
June | 0.118764E+09 | 111.79 | 01-JUN-19:10 | 0.210812E+09 | 232.19 | 01-JUN-06:10 |
July | 0.124032E+09 | 111.79 | 01-JUL-18:10 | 0.217991E+09 | 232.19 | 01-JUL-07:10 |
August | 0.122575E+09 | 111.79 | 01-AUG-19:10 | 0.217824E+09 | 232.19 | 01-AUG-06:10 |
September | 0.119746E+09 | 111.79 | 01-SEP-19:10 | 0.210923E+09 | 232.19 | 01-SEP-06:10 |
October | 0.123541E+09 | 111.79 | 01-OCT-18:10 | 0.217935E+09 | 232.19 | 01-OCT-07:10 |
November | 0.119238E+09 | 111.79 | 01-NOV-19:10 | 0.210867E+09 | 232.19 | 01-NOV-06:10 |
December | 0.124048E+09 | 111.79 | 01-DEC-20:10 | 0.217991E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.145244E+10 | 0.256575E+10 | ||||
Minimum of Months | 0.111584E+09 | 111.79 | 0.196843E+09 | 232.19 | ||
Maximum of Months | 0.124048E+09 | 111.79 | 0.217991E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123591E+09 | 111.82 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 0.111614E+09 | 111.82 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 0.122608E+09 | 111.82 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 0.119746E+09 | 111.82 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 0.123099E+09 | 111.82 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 0.118796E+09 | 111.82 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 0.124066E+09 | 111.82 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 0.122608E+09 | 111.82 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 0.119778E+09 | 111.82 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 0.123574E+09 | 111.82 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 0.119271E+09 | 111.82 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 0.124082E+09 | 111.82 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.145283E+10 | 0.256645E+10 | ||||
Minimum of Months | 0.111614E+09 | 111.82 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 0.124082E+09 | 111.82 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196602E+09 | 177.88 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.177551E+09 | 177.88 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.195039E+09 | 177.88 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.190486E+09 | 177.88 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.195821E+09 | 177.88 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.188975E+09 | 177.88 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.197358E+09 | 177.88 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.195039E+09 | 177.88 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.190538E+09 | 177.88 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.196576E+09 | 177.88 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.189731E+09 | 177.88 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.197383E+09 | 177.88 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.231110E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.177551E+09 | 177.88 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.197383E+09 | 177.88 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196579E+09 | 177.86 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.177530E+09 | 177.86 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.195017E+09 | 177.86 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.190464E+09 | 177.86 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.195798E+09 | 177.86 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.188953E+09 | 177.86 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.197334E+09 | 177.86 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.195017E+09 | 177.86 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.190515E+09 | 177.86 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.196553E+09 | 177.86 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.189708E+09 | 177.86 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.197360E+09 | 177.86 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.231083E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.177530E+09 | 177.86 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.197360E+09 | 177.86 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.193865E+10 | 1867.32 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.175042E+10 | 1867.32 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.194462E+10 | 1867.32 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.187292E+10 | 1867.32 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.194201E+10 | 1867.32 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.188151E+10 | 1867.32 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.193342E+10 | 1867.32 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.194537E+10 | 1867.32 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.187367E+10 | 1867.32 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.193790E+10 | 1867.32 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.188002E+10 | 1867.32 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.193342E+10 | 1867.32 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.228339E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.175042E+10 | 1867.32 | 0.00 | 0.00 | |
Maximum of Months | 0.194537E+10 | 1867.32 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196602E+09 | 177.88 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.177551E+09 | 177.88 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.195039E+09 | 177.88 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.190486E+09 | 177.88 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.195821E+09 | 177.88 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.188975E+09 | 177.88 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.197358E+09 | 177.88 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.195039E+09 | 177.88 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.190538E+09 | 177.88 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.196576E+09 | 177.88 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.189731E+09 | 177.88 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.197383E+09 | 177.88 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.231110E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.177551E+09 | 177.88 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.197383E+09 | 177.88 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196579E+09 | 177.86 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.177530E+09 | 177.86 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.195017E+09 | 177.86 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.190464E+09 | 177.86 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.195798E+09 | 177.86 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.188953E+09 | 177.86 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.197334E+09 | 177.86 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.195017E+09 | 177.86 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.190515E+09 | 177.86 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.196553E+09 | 177.86 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.189708E+09 | 177.86 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.197360E+09 | 177.86 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.231083E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.177530E+09 | 177.86 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.197360E+09 | 177.86 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123591E+09 | 111.82 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 0.111614E+09 | 111.82 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 0.122608E+09 | 111.82 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 0.119746E+09 | 111.82 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 0.123099E+09 | 111.82 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 0.118796E+09 | 111.82 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 0.124066E+09 | 111.82 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 0.122608E+09 | 111.82 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 0.119778E+09 | 111.82 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 0.123574E+09 | 111.82 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 0.119271E+09 | 111.82 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 0.124082E+09 | 111.82 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.145283E+10 | 0.256645E+10 | ||||
Minimum of Months | 0.111614E+09 | 111.82 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 0.124082E+09 | 111.82 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.280761E+10 | 2988.03 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.248271E+10 | 2988.03 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.269049E+10 | 2988.03 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.248234E+10 | 2988.03 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.250357E+10 | 2988.03 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.238414E+10 | 2988.03 | 01-JUN-19:10 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.245742E+10 | 2988.03 | 03-JUL-19:19 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.256390E+10 | 2988.03 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.256111E+10 | 2988.03 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.274401E+10 | 2988.03 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.268836E+10 | 2988.03 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.278826E+10 | 2988.03 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.311539E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.238414E+10 | 2988.03 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.280761E+10 | 2988.03 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.280761E+10 | 2988.03 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.248271E+10 | 2988.03 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.269049E+10 | 2988.03 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.248234E+10 | 2988.03 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.250357E+10 | 2988.03 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.238414E+10 | 2988.03 | 01-JUN-19:10 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.245742E+10 | 2988.03 | 03-JUL-19:19 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.256390E+10 | 2988.03 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.256104E+10 | 2988.03 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.274401E+10 | 2988.03 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.268836E+10 | 2988.03 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.278826E+10 | 2988.03 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.311538E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.238414E+10 | 2988.03 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.280761E+10 | 2988.03 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.110133E+10 | 1060.81 | 02-JAN-20:10 | 0.368383E+11 | 16487.34 | 01-JAN-07:10 |
February | 0.994402E+09 | 1060.81 | 01-FEB-20:10 | 0.332733E+11 | 16487.34 | 01-FEB-07:10 |
March | 0.110473E+10 | 1060.81 | 01-MAR-20:10 | 0.368383E+11 | 16487.34 | 01-MAR-07:10 |
April | 0.106399E+10 | 1060.81 | 03-APR-19:10 | 0.356500E+11 | 16487.34 | 01-APR-06:10 |
May | 0.110324E+10 | 1060.81 | 01-MAY-19:10 | 0.368383E+11 | 16487.34 | 01-MAY-06:10 |
June | 0.106887E+10 | 1060.81 | 01-JUN-19:10 | 0.356500E+11 | 16487.34 | 01-JUN-06:10 |
July | 0.109836E+10 | 1060.81 | 03-JUL-19:10 | 0.368383E+11 | 16487.34 | 01-JUL-06:10 |
August | 0.110515E+10 | 1060.81 | 01-AUG-19:10 | 0.368383E+11 | 16487.34 | 01-AUG-06:10 |
September | 0.106442E+10 | 1060.81 | 01-SEP-19:10 | 0.356500E+11 | 16487.34 | 01-SEP-06:10 |
October | 0.110091E+10 | 1060.81 | 02-OCT-19:10 | 0.368383E+11 | 16487.34 | 01-OCT-06:10 |
November | 0.106802E+10 | 1060.81 | 01-NOV-19:10 | 0.356500E+11 | 16487.34 | 01-NOV-06:10 |
December | 0.109836E+10 | 1060.81 | 01-DEC-20:10 | 0.368383E+11 | 16487.34 | 01-DEC-07:10 |
Annual Sum or Average | 0.129718E+11 | 0.433742E+12 | ||||
Minimum of Months | 0.994402E+09 | 1060.81 | 0.332733E+11 | 16487.34 | ||
Maximum of Months | 0.110515E+10 | 1060.81 | 0.368383E+11 | 16487.34 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.205176E+10 | 1976.27 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.185255E+10 | 1976.27 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.205809E+10 | 1976.27 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.198220E+10 | 1976.27 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.205532E+10 | 1976.27 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.199129E+10 | 1976.27 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.204623E+10 | 1976.27 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.205888E+10 | 1976.27 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.198299E+10 | 1976.27 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.205097E+10 | 1976.27 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.198971E+10 | 1976.27 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.204623E+10 | 1976.27 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.241662E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.185255E+10 | 1976.27 | 0.00 | 0.00 | |
Maximum of Months | 0.205888E+10 | 1976.27 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.136942E+11 | 0.121516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.123646E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196682E+11 | 0.137364E+11 | 0.121771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.132299E+11 | 0.117446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.137180E+11 | 0.121662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.132906E+11 | 0.117829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.136573E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.137417E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189689E+11 | 0.132352E+11 | 0.117482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195854E+11 | 0.136889E+11 | 0.121479E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.132800E+11 | 0.117774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.136573E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230861E+12 | 0.161294E+12 | 0.143105E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.176991E+11 | 0.123646E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196682E+11 | 0.137417E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.620421E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181528E+09 |
February | 0.179968E+10 | 0.560184E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139966E+09 |
March | 0.199990E+10 | 0.622334E+09 | 0.866718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 98516.98 | 0.124871E+09 |
April | 0.192973E+10 | 0.599386E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9922691.44 | 55428445.89 |
May | 0.199475E+10 | 0.621497E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 27468020.91 | 22409586.74 |
June | 0.193394E+10 | 0.602135E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 53786684.27 | 6538934.79 |
July | 0.199054E+10 | 0.618748E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 49479620.80 | 4191846.52 |
August | 0.199896E+10 | 0.622573E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39883136.37 | 9216977.06 |
September | 0.192879E+10 | 0.599625E+09 | 0.836191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21955875.30 | 26457574.97 |
October | 0.199148E+10 | 0.620182E+09 | 0.864640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5222254.22 | 68073825.01 |
November | 0.192552E+10 | 0.601657E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142359E+09 |
December | 0.199054E+10 | 0.618748E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199166E+09 |
Annual Sum or Average | 0.234744E+11 | 0.730749E+10 | 0.101856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207817E+09 | 0.980208E+09 |
Minimum of Months | 0.179968E+10 | 0.560184E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4191846.52 |
Maximum of Months | 0.199990E+10 | 0.622573E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 53786684.27 | 0.199166E+09 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.718450E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74435095.25 |
February | 0.208403E+10 | 0.648695E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 414.68 | 57893502.73 |
March | 0.231589E+10 | 0.720665E+09 | 0.100366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 108598.20 | 52820193.45 |
April | 0.223463E+10 | 0.694091E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4211161.42 | 24909649.30 |
May | 0.230993E+10 | 0.719696E+09 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10747454.70 | 10741767.31 |
June | 0.223950E+10 | 0.697275E+09 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20898814.68 | 3291565.23 |
July | 0.230505E+10 | 0.716513E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19153810.32 | 2276268.77 |
August | 0.231480E+10 | 0.720942E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15583945.70 | 4602481.40 |
September | 0.223354E+10 | 0.694368E+09 | 0.968312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8833566.96 | 11614737.42 |
October | 0.230614E+10 | 0.718174E+09 | 0.100126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2203963.44 | 28895475.04 |
November | 0.222975E+10 | 0.696721E+09 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2777.78 | 58867541.73 |
December | 0.230505E+10 | 0.716513E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81249065.18 |
Annual Sum or Average | 0.271834E+11 | 0.846210E+10 | 0.117950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 81744507.88 | 0.411597E+09 |
Minimum of Months | 0.208403E+10 | 0.648695E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2276268.77 |
Maximum of Months | 0.231589E+10 | 0.720942E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20898814.68 | 81249065.18 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.487480E+09 | 0.710312E+09 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160955E+09 |
February | 0.440737E+09 | 0.641347E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 138606.20 | 0.124164E+09 |
March | 0.489771E+09 | 0.712502E+09 | 0.106120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 811589.64 | 0.113056E+09 |
April | 0.472586E+09 | 0.686229E+09 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11752338.37 | 53349385.60 |
May | 0.488511E+09 | 0.711544E+09 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25947423.09 | 23798949.90 |
June | 0.473617E+09 | 0.689376E+09 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48848954.27 | 7662262.70 |
July | 0.487480E+09 | 0.708397E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44681282.58 | 5291321.56 |
August | 0.489542E+09 | 0.712775E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36667524.82 | 10582903.92 |
September | 0.472357E+09 | 0.686503E+09 | 0.102382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21584348.03 | 26424772.07 |
October | 0.487709E+09 | 0.710039E+09 | 0.105866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6190459.00 | 62832475.58 |
November | 0.471555E+09 | 0.688829E+09 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 104184.00 | 0.127271E+09 |
December | 0.487480E+09 | 0.708397E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176850E+09 |
Annual Sum or Average | 0.574883E+10 | 0.836625E+10 | 0.124712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196727E+09 | 0.892239E+09 |
Minimum of Months | 0.440737E+09 | 0.641347E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5291321.56 |
Maximum of Months | 0.489771E+09 | 0.712775E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48848954.27 | 0.176850E+09 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.374985E+09 | 0.261454E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90866187.72 |
February | 0.339028E+09 | 0.236069E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 89283.75 | 69928785.32 |
March | 0.376747E+09 | 0.262260E+09 | 0.306128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 506670.25 | 63348964.52 |
April | 0.363528E+09 | 0.252589E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7103787.59 | 29447867.22 |
May | 0.375778E+09 | 0.261907E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15507586.14 | 12906118.09 |
June | 0.364321E+09 | 0.253748E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 28377144.69 | 4177091.30 |
July | 0.374985E+09 | 0.260749E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25981121.52 | 2868295.48 |
August | 0.376571E+09 | 0.262360E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21444805.54 | 5675232.96 |
September | 0.363352E+09 | 0.252690E+09 | 0.295345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12838256.51 | 14379682.86 |
October | 0.375161E+09 | 0.261353E+09 | 0.305393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3763772.79 | 34651968.56 |
November | 0.362735E+09 | 0.253546E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 70494.18 | 71465508.06 |
December | 0.374985E+09 | 0.260749E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100253E+09 |
Annual Sum or Average | 0.442217E+10 | 0.307947E+10 | 0.359760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115683E+09 | 0.499969E+09 |
Minimum of Months | 0.339028E+09 | 0.236069E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2868295.48 |
Maximum of Months | 0.376747E+09 | 0.262360E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 28377144.69 | 0.100253E+09 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.337502E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247386E+09 |
February | 0.139600E+10 | 0.304733E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 6840.63 | 0.191877E+09 |
March | 0.155131E+10 | 0.338542E+09 | 0.578079E+10 | 0.502211E+11 | 0.00 | 0.00 | 0.00 | 245483.70 | 0.174632E+09 |
April | 0.149688E+10 | 0.326059E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 13418605.75 | 78882701.99 |
May | 0.154732E+10 | 0.338087E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 35747579.64 | 31486231.12 |
June | 0.150015E+10 | 0.327554E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 70869770.02 | 8254807.43 |
July | 0.154405E+10 | 0.336592E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 65981966.01 | 5235099.17 |
August | 0.155059E+10 | 0.338672E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 53752751.59 | 11999429.94 |
September | 0.149615E+10 | 0.326189E+09 | 0.557718E+10 | 0.484522E+11 | 0.00 | 0.00 | 0.00 | 30738808.53 | 33263408.89 |
October | 0.154478E+10 | 0.337372E+09 | 0.576693E+10 | 0.501006E+11 | 0.00 | 0.00 | 0.00 | 8227389.72 | 90133670.16 |
November | 0.149361E+10 | 0.327294E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 11198.57 | 0.191662E+09 |
December | 0.154405E+10 | 0.336592E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.271279E+09 |
Annual Sum or Average | 0.182090E+11 | 0.397519E+10 | 0.679355E+11 | 0.590196E+12 | 0.00 | 0.00 | 0.00 | 0.279000E+09 | 0.133609E+10 |
Minimum of Months | 0.139600E+10 | 0.304733E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5235099.17 |
Maximum of Months | 0.155131E+10 | 0.338672E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 70869770.02 | 0.271279E+09 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.132566E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.439439E+09 |
February | 0.236489E+11 | 0.115622E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.343116E+09 |
March | 0.262800E+11 | 0.123068E+10 | 0.122027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 143479.13 | 0.311677E+09 |
April | 0.253579E+11 | 0.112060E+10 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21180656.50 | 0.143034E+09 |
May | 0.262123E+11 | 0.112432E+10 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60456952.90 | 60078099.08 |
June | 0.254132E+11 | 0.105682E+10 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119921E+09 | 18059362.58 |
July | 0.261570E+11 | 0.109484E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109901E+09 | 12430594.72 |
August | 0.262677E+11 | 0.116397E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 88455935.67 | 25131611.61 |
September | 0.253456E+11 | 0.115946E+10 | 0.117729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48779171.76 | 65599756.12 |
October | 0.261693E+11 | 0.128391E+10 | 0.121734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11504425.92 | 0.167307E+09 |
November | 0.253025E+11 | 0.124152E+10 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344438E+09 |
December | 0.261570E+11 | 0.131487E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.479617E+09 |
Annual Sum or Average | 0.308468E+12 | 0.142729E+11 | 0.143405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.460342E+09 | 0.240993E+10 |
Minimum of Months | 0.236489E+11 | 0.105682E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12430594.72 |
Maximum of Months | 0.262800E+11 | 0.132566E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119921E+09 | 0.479617E+09 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.943854E+10 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126129E+10 |
February | 0.702046E+11 | 0.848695E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.982172E+09 |
March | 0.780153E+11 | 0.939774E+10 | 0.126786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1189720.56 | 0.893258E+09 |
April | 0.752779E+11 | 0.899513E+10 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 67301921.63 | 0.415261E+09 |
May | 0.778146E+11 | 0.929943E+10 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177292E+09 | 0.176503E+09 |
June | 0.754422E+11 | 0.899697E+10 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344960E+09 | 53529151.55 |
July | 0.776503E+11 | 0.925861E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.316024E+09 | 37049525.14 |
August | 0.779788E+11 | 0.934824E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255869E+09 | 75124156.44 |
September | 0.752414E+11 | 0.904139E+10 | 0.122320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143049E+09 | 0.190118E+09 |
October | 0.776868E+11 | 0.939822E+10 | 0.126482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 34084650.63 | 0.481705E+09 |
November | 0.751137E+11 | 0.910852E+10 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3180.74 | 0.992495E+09 |
December | 0.776503E+11 | 0.940104E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137770E+10 |
Annual Sum or Average | 0.915726E+12 | 0.110171E+12 | 0.148998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133977E+10 | 0.693621E+10 |
Minimum of Months | 0.702046E+11 | 0.848695E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37049525.14 |
Maximum of Months | 0.780153E+11 | 0.943854E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344960E+09 | 0.137770E+10 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196602E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100648E+09 |
February | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 62343.89 | 76816731.24 |
March | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 376077.97 | 68285581.16 |
April | 0.293479E+09 | 0.190486E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8976704.96 | 27413204.47 |
May | 0.303504E+09 | 0.195821E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22589807.97 | 8829065.75 |
June | 0.293842E+09 | 0.188975E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41551285.44 | 1449688.65 |
July | 0.303141E+09 | 0.197358E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40462293.05 | 463800.84 |
August | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 33381177.46 | 2291227.63 |
September | 0.293479E+09 | 0.190538E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19133571.48 | 8966820.41 |
October | 0.303322E+09 | 0.196576E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5395407.42 | 31271785.64 |
November | 0.293661E+09 | 0.189731E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 74296.62 | 76046822.18 |
December | 0.303141E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111497E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231110E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172003E+09 | 0.513980E+09 |
Minimum of Months | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 463800.84 |
Maximum of Months | 0.303685E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41551285.44 | 0.111497E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196579E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98148134.46 |
February | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13157.50 | 75570347.87 |
March | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 226148.38 | 68877555.42 |
April | 0.293479E+09 | 0.190464E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8581229.12 | 29127409.44 |
May | 0.303504E+09 | 0.195798E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21860288.85 | 10385002.10 |
June | 0.293842E+09 | 0.188953E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40482240.20 | 2395032.11 |
July | 0.303141E+09 | 0.197334E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39176401.92 | 1267683.94 |
August | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 32459569.56 | 3567835.87 |
September | 0.293479E+09 | 0.190515E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18461803.90 | 10955742.58 |
October | 0.303322E+09 | 0.196553E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4985887.67 | 33680071.70 |
November | 0.293661E+09 | 0.189708E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14092.54 | 75250889.14 |
December | 0.303141E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108672E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231083E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166261E+09 | 0.517898E+09 |
Minimum of Months | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1267683.94 |
Maximum of Months | 0.303685E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40482240.20 | 0.108672E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.123557E+09 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38346902.67 |
February | 0.00 | 0.111584E+09 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30751990.33 |
March | 0.00 | 0.122575E+09 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29130975.18 |
April | 0.00 | 0.119713E+09 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 469602.04 | 15273088.06 |
May | 0.00 | 0.123066E+09 | 0.217879E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1959503.75 | 7835887.79 |
June | 0.00 | 0.118764E+09 | 0.210812E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5288869.12 | 3298227.60 |
July | 0.00 | 0.124032E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4466639.06 | 2958030.13 |
August | 0.00 | 0.122575E+09 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3473707.77 | 4491756.73 |
September | 0.00 | 0.119746E+09 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1632024.42 | 8248826.33 |
October | 0.00 | 0.123541E+09 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 295538.18 | 17578945.16 |
November | 0.00 | 0.119238E+09 | 0.210867E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31019363.71 |
December | 0.00 | 0.124048E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41359717.92 |
Annual Sum or Average | 0.00 | 0.145244E+10 | 0.256575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17585884.36 | 0.230294E+09 |
Minimum of Months | 0.00 | 0.111584E+09 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2958030.13 |
Maximum of Months | 0.00 | 0.124048E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5288869.12 | 41359717.92 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.123591E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27552829.37 |
February | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23946.78 | 21038271.28 |
March | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 114288.34 | 18885590.17 |
April | 0.293479E+09 | 0.119746E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2526407.03 | 7830770.96 |
May | 0.303504E+09 | 0.123099E+09 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6288004.08 | 2735277.48 |
June | 0.293842E+09 | 0.118796E+09 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11516083.92 | 578961.85 |
July | 0.303141E+09 | 0.124066E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11076274.27 | 266323.36 |
August | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9221018.83 | 885345.07 |
September | 0.293479E+09 | 0.119778E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5320830.85 | 2874591.91 |
October | 0.303322E+09 | 0.123574E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1533924.12 | 8979169.92 |
November | 0.293661E+09 | 0.119271E+09 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 31379.43 | 20739329.64 |
December | 0.303141E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30569475.88 |
Annual Sum or Average | 0.357224E+10 | 0.145283E+10 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47652157.66 | 0.142936E+09 |
Minimum of Months | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 266323.36 |
Maximum of Months | 0.303685E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11516083.92 | 30569475.88 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196602E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101017E+09 |
February | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 64062.07 | 77399182.82 |
March | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 382360.58 | 68915216.90 |
April | 0.293479E+09 | 0.190486E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9042648.03 | 27874073.63 |
May | 0.303504E+09 | 0.195821E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22771157.48 | 9030189.04 |
June | 0.293842E+09 | 0.188975E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41565954.37 | 1484081.92 |
July | 0.303141E+09 | 0.197358E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40429208.09 | 476914.36 |
August | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 33443662.21 | 2333594.11 |
September | 0.293479E+09 | 0.190538E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19242627.90 | 9087432.51 |
October | 0.303322E+09 | 0.196576E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5544841.42 | 31414561.36 |
November | 0.293661E+09 | 0.189731E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 82569.72 | 76305357.57 |
December | 0.303141E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111792E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231110E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172569E+09 | 0.517130E+09 |
Minimum of Months | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 476914.36 |
Maximum of Months | 0.303685E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41565954.37 | 0.111792E+09 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196579E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98019302.60 |
February | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18090.53 | 75778827.27 |
March | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 232818.88 | 69021852.88 |
April | 0.293479E+09 | 0.190464E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8591870.77 | 29780497.06 |
May | 0.303504E+09 | 0.195798E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21896331.01 | 11638644.62 |
June | 0.293842E+09 | 0.188953E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40244894.36 | 3247788.22 |
July | 0.303141E+09 | 0.197334E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 38914234.05 | 1965878.88 |
August | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 32284651.68 | 4339386.34 |
September | 0.293479E+09 | 0.190515E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18334942.18 | 11982953.24 |
October | 0.303322E+09 | 0.196553E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5042016.52 | 33248865.23 |
November | 0.293661E+09 | 0.189708E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 29692.63 | 74985611.14 |
December | 0.303141E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108592E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231083E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165590E+09 | 0.522602E+09 |
Minimum of Months | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1965878.88 |
Maximum of Months | 0.303685E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40244894.36 | 0.108592E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.385223E+10 | 0.193865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122341E+09 |
February | 0.348285E+10 | 0.175042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66297.65 | 94991078.12 |
March | 0.387034E+10 | 0.194462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 470865.60 | 86769659.88 |
April | 0.373454E+10 | 0.187292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8954327.72 | 40604150.66 |
May | 0.386038E+10 | 0.194201E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20262379.23 | 17691428.13 |
June | 0.374269E+10 | 0.188151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37725736.74 | 5659447.61 |
July | 0.385223E+10 | 0.193342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34950721.35 | 3763708.21 |
August | 0.386853E+10 | 0.194537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28576123.33 | 7653057.22 |
September | 0.373273E+10 | 0.187367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16364267.68 | 19942945.76 |
October | 0.385404E+10 | 0.193790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4550306.82 | 47890048.58 |
November | 0.372639E+10 | 0.188002E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55694.05 | 97865510.81 |
December | 0.385223E+10 | 0.193342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134195E+09 |
Annual Sum or Average | 0.454292E+11 | 0.228339E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151977E+09 | 0.679367E+09 |
Minimum of Months | 0.348285E+10 | 0.175042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3763708.21 |
Maximum of Months | 0.387034E+10 | 0.194537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37725736.74 | 0.134195E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196602E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100397E+09 |
February | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 57859.79 | 76738527.53 |
March | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 359367.32 | 68307244.63 |
April | 0.293479E+09 | 0.190486E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8788303.90 | 27521096.56 |
May | 0.303504E+09 | 0.195821E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22239613.86 | 8921351.35 |
June | 0.293842E+09 | 0.188975E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41056142.08 | 1488314.72 |
July | 0.303141E+09 | 0.197358E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39986367.35 | 485848.02 |
August | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 32972839.35 | 2338686.17 |
September | 0.293479E+09 | 0.190538E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18832044.99 | 9067276.51 |
October | 0.303322E+09 | 0.196576E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5278615.06 | 31372042.93 |
November | 0.293661E+09 | 0.189731E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 67716.00 | 75974391.99 |
December | 0.303141E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111258E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231110E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169639E+09 | 0.513870E+09 |
Minimum of Months | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 485848.02 |
Maximum of Months | 0.303685E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41056142.08 | 0.111258E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196579E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97598896.51 |
February | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13110.43 | 75273724.12 |
March | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 216687.94 | 68823887.29 |
April | 0.293479E+09 | 0.190464E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8407129.26 | 29175378.91 |
May | 0.303504E+09 | 0.195798E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21535053.14 | 10274417.13 |
June | 0.293842E+09 | 0.188953E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40017115.78 | 2287619.47 |
July | 0.303141E+09 | 0.197334E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 38743809.04 | 1169180.70 |
August | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 32090650.00 | 3427594.44 |
September | 0.293479E+09 | 0.190515E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18214242.49 | 10750904.16 |
October | 0.303322E+09 | 0.196553E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4900273.02 | 33651634.31 |
November | 0.293661E+09 | 0.189708E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12525.42 | 74875040.22 |
December | 0.303141E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108172E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231083E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164151E+09 | 0.515481E+09 |
Minimum of Months | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1169180.70 |
Maximum of Months | 0.303685E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40017115.78 | 0.108172E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.123591E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52549419.86 |
February | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25597.02 | 40070942.36 |
March | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 179037.48 | 35456987.94 |
April | 0.293479E+09 | 0.119746E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4528519.68 | 14176027.43 |
May | 0.303504E+09 | 0.123099E+09 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11608382.71 | 4562151.41 |
June | 0.293842E+09 | 0.118796E+09 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21293621.48 | 757564.82 |
July | 0.303141E+09 | 0.124066E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20620340.04 | 248426.98 |
August | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17016897.75 | 1199343.34 |
September | 0.293479E+09 | 0.119778E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9700561.96 | 4662264.94 |
October | 0.303322E+09 | 0.123574E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2651727.50 | 16231958.16 |
November | 0.293661E+09 | 0.119271E+09 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26114.55 | 39521389.20 |
December | 0.303141E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58282125.22 |
Annual Sum or Average | 0.357224E+10 | 0.145283E+10 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 87650800.19 | 0.267719E+09 |
Minimum of Months | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 248426.98 |
Maximum of Months | 0.303685E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21293621.48 | 58282125.22 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.280761E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290179E+09 |
February | 0.415303E+11 | 0.248271E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226921E+09 |
March | 0.461508E+11 | 0.269049E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 86336.97 | 0.208801E+09 |
April | 0.445315E+11 | 0.248234E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 12610214.72 | 97557939.11 |
May | 0.460320E+11 | 0.250357E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 35707161.25 | 41578465.04 |
June | 0.446286E+11 | 0.238414E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 73673028.06 | 12725320.18 |
July | 0.459349E+11 | 0.245742E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 67334575.13 | 8940347.00 |
August | 0.461292E+11 | 0.256390E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 54560882.11 | 18069605.09 |
September | 0.445099E+11 | 0.256111E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 30346320.09 | 43973545.66 |
October | 0.459565E+11 | 0.274401E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 7122811.35 | 0.111281E+09 |
November | 0.444343E+11 | 0.268836E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 72.77 | 0.227271E+09 |
December | 0.459349E+11 | 0.278826E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.317010E+09 |
Annual Sum or Average | 0.541708E+12 | 0.311539E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281441E+09 | 0.160431E+10 |
Minimum of Months | 0.415303E+11 | 0.238414E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8940347.00 |
Maximum of Months | 0.461508E+11 | 0.280761E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 73673028.06 | 0.317010E+09 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.280761E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292690E+09 |
February | 0.415303E+11 | 0.248271E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228681E+09 |
March | 0.461508E+11 | 0.269049E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 72745.08 | 0.210336E+09 |
April | 0.445315E+11 | 0.248234E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 12552440.95 | 97969889.60 |
May | 0.460320E+11 | 0.250357E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 35679233.26 | 41671495.94 |
June | 0.446286E+11 | 0.238414E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 73657308.39 | 12728179.48 |
July | 0.459349E+11 | 0.245742E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 67319277.82 | 8941767.43 |
August | 0.461292E+11 | 0.256390E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 54542872.04 | 18088710.53 |
September | 0.445099E+11 | 0.256104E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 30299835.73 | 44023515.64 |
October | 0.459565E+11 | 0.274401E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 7097371.80 | 0.111820E+09 |
November | 0.444343E+11 | 0.268836E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228971E+09 |
December | 0.459349E+11 | 0.278826E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319816E+09 |
Annual Sum or Average | 0.541708E+12 | 0.311538E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281221E+09 | 0.161574E+10 |
Minimum of Months | 0.415303E+11 | 0.238414E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8941767.43 |
Maximum of Months | 0.461508E+11 | 0.280761E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 73657308.39 | 0.319816E+09 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.110133E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262348E+09 |
February | 0.369574E+10 | 0.994402E+09 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204648E+09 |
March | 0.410691E+10 | 0.110473E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 65614.95 | 0.188100E+09 |
April | 0.396281E+10 | 0.106399E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 11256905.32 | 87568663.32 |
May | 0.409635E+10 | 0.110324E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 31971764.33 | 37263613.14 |
June | 0.397146E+10 | 0.106887E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 65989984.99 | 11389652.29 |
July | 0.408770E+10 | 0.109836E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 60305947.67 | 8000672.69 |
August | 0.410499E+10 | 0.110515E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 48856522.54 | 16187097.15 |
September | 0.396089E+10 | 0.106442E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 27144354.64 | 39385570.56 |
October | 0.408962E+10 | 0.110091E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 6360498.61 | 0.100029E+09 |
November | 0.395417E+10 | 0.106802E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204853E+09 |
December | 0.408770E+10 | 0.109836E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286642E+09 |
Annual Sum or Average | 0.482060E+11 | 0.129718E+11 | 0.392709E+12 | 0.359593E+12 | 0.00 | 0.00 | 0.00 | 0.251952E+09 | 0.144642E+10 |
Minimum of Months | 0.369574E+10 | 0.994402E+09 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 8000672.69 |
Maximum of Months | 0.410691E+10 | 0.110515E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 65989984.99 | 0.286642E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.407704E+10 | 0.205176E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215171E+09 |
February | 0.368610E+10 | 0.185255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14730.60 | 0.166536E+09 |
March | 0.409620E+10 | 0.205809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 552606.36 | 0.151313E+09 |
April | 0.395248E+10 | 0.198220E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13544753.46 | 71048216.75 |
May | 0.408566E+10 | 0.205532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32852407.94 | 31082280.01 |
June | 0.396110E+10 | 0.199129E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64773705.38 | 9908601.90 |
July | 0.407704E+10 | 0.204623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59412094.08 | 6739657.56 |
August | 0.409429E+10 | 0.205888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48252353.83 | 13524486.66 |
September | 0.395056E+10 | 0.198299E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27092968.56 | 34224495.78 |
October | 0.407896E+10 | 0.205097E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6831535.32 | 82742445.37 |
November | 0.394385E+10 | 0.198971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34776.93 | 0.168836E+09 |
December | 0.407704E+10 | 0.204623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237331E+09 |
Annual Sum or Average | 0.480803E+11 | 0.241662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253362E+09 | 0.118846E+10 |
Minimum of Months | 0.368610E+10 | 0.185255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6739657.56 |
Maximum of Months | 0.409620E+10 | 0.205888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64773705.38 | 0.237331E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 13190.31 | 02-JAN-20:10 | 9632.53 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 13190.31 | 01-FEB-20:10 | 9632.53 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 13190.31 | 01-MAR-20:10 | 9632.53 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 13190.31 | 03-APR-19:10 | 9632.53 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 13190.31 | 01-MAY-19:10 | 9632.53 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 13190.31 | 01-JUN-19:10 | 9632.53 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 13190.31 | 03-JUL-19:10 | 9632.53 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 13190.31 | 01-AUG-19:10 | 9632.53 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 13190.31 | 01-SEP-19:10 | 9632.53 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 01-OCT-23:10 | 13190.31 | 02-OCT-19:10 | 9632.53 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 13190.31 | 01-NOV-19:10 | 9632.53 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 13190.31 | 01-DEC-20:10 | 9632.53 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 11501.89 | 13190.31 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 13190.31 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 597.59 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 128.81 | 27-JAN-07:00 |
February | 1169.53 | 01-FEB-00:10 | 597.59 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 135.35 | 03-FEB-07:00 |
March | 1169.53 | 01-MAR-00:10 | 597.59 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.97 | 21-MAR-16:00 | 127.34 | 02-MAR-05:40 |
April | 1169.53 | 01-APR-00:10 | 597.59 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.41 | 21-APR-14:00 | 86.69 | 12-APR-06:00 |
May | 1169.53 | 01-MAY-00:10 | 597.59 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.75 | 21-MAY-14:00 | 58.68 | 02-MAY-06:00 |
June | 1169.53 | 01-JUN-00:10 | 597.59 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.09 | 02-JUN-16:00 | 37.87 | 13-JUN-05:00 |
July | 1169.53 | 01-JUL-00:10 | 597.59 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 62.72 | 02-JUL-16:00 | 23.13 | 05-JUL-06:00 |
August | 1169.53 | 01-AUG-00:10 | 597.59 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.09 | 07-AUG-16:00 | 29.77 | 31-AUG-06:00 |
September | 1169.53 | 01-SEP-00:10 | 597.59 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.92 | 19-SEP-14:00 | 66.91 | 30-SEP-06:00 |
October | 1169.53 | 01-OCT-23:10 | 597.59 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.27 | 01-OCT-15:00 | 72.20 | 11-OCT-06:00 |
November | 1169.53 | 01-NOV-00:10 | 597.59 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 109.17 | 28-NOV-05:00 |
December | 1169.53 | 01-DEC-00:10 | 597.59 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 129.28 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1169.53 | 597.59 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.13 | |||||
Maximum of Months | 1169.53 | 597.59 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 65.09 | 135.35 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 692.02 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 52.83 | 27-JAN-07:00 |
February | 1354.32 | 01-FEB-00:10 | 692.02 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 | 20-FEB-15:00 | 55.57 | 03-FEB-07:00 |
March | 1354.32 | 01-MAR-00:10 | 692.02 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.52 | 22-MAR-13:00 | 52.25 | 02-MAR-05:50 |
April | 1354.32 | 01-APR-00:10 | 692.02 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.08 | 21-APR-14:00 | 37.67 | 12-APR-06:00 |
May | 1354.32 | 01-MAY-00:10 | 692.02 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.47 | 19-MAY-14:00 | 26.53 | 02-MAY-06:00 |
June | 1354.32 | 01-JUN-00:10 | 692.02 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.29 | 02-JUN-16:00 | 16.41 | 13-JUN-05:00 |
July | 1354.32 | 01-JUL-00:10 | 692.02 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.65 | 02-JUL-16:00 | 11.23 | 05-JUL-06:00 |
August | 1354.32 | 01-AUG-00:10 | 692.02 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.42 | 07-AUG-16:00 | 13.34 | 31-AUG-06:00 |
September | 1354.32 | 01-SEP-00:10 | 692.02 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.10 | 19-SEP-14:00 | 29.19 | 30-SEP-06:00 |
October | 1354.32 | 01-OCT-23:10 | 692.02 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.52 | 01-OCT-15:00 | 31.99 | 25-OCT-06:00 |
November | 1354.32 | 01-NOV-00:10 | 692.02 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.74 | 03-NOV-16:00 | 45.99 | 17-NOV-04:00 |
December | 1354.32 | 01-DEC-00:10 | 692.02 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 52.73 | 19-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1354.32 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.23 | |||||
Maximum of Months | 1354.32 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 25.29 | 55.57 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 286.42 | 02-JAN-00:10 | 684.18 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 118.49 | 27-JAN-07:00 |
February | 286.42 | 01-FEB-00:10 | 684.18 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.26 | 20-FEB-15:00 | 124.15 | 03-FEB-07:00 |
March | 286.42 | 01-MAR-00:10 | 684.18 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.19 | 21-MAR-16:00 | 117.07 | 02-MAR-05:40 |
April | 286.42 | 01-APR-00:10 | 684.18 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.60 | 21-APR-14:00 | 84.79 | 12-APR-06:00 |
May | 286.42 | 01-MAY-00:10 | 684.18 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.99 | 19-MAY-16:00 | 59.99 | 02-MAY-06:00 |
June | 286.42 | 01-JUN-00:10 | 684.18 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.89 | 02-JUN-16:00 | 38.66 | 13-JUN-05:00 |
July | 286.42 | 01-JUL-00:10 | 684.18 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.58 | 02-JUL-16:00 | 26.07 | 05-JUL-06:00 |
August | 286.42 | 01-AUG-00:10 | 684.18 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.99 | 07-AUG-16:00 | 31.06 | 31-AUG-06:00 |
September | 286.42 | 01-SEP-00:10 | 684.18 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.40 | 19-SEP-14:00 | 66.68 | 30-SEP-06:00 |
October | 286.42 | 01-OCT-23:10 | 684.18 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.77 | 01-OCT-15:00 | 72.05 | 11-OCT-06:00 |
November | 286.42 | 01-NOV-00:10 | 684.18 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.07 | 08-NOV-15:00 | 102.74 | 17-NOV-04:00 |
December | 286.42 | 01-DEC-00:10 | 684.18 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 117.93 | 19-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 286.42 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.07 | |||||
Maximum of Months | 286.42 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 59.89 | 124.15 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 220.32 | 02-JAN-00:10 | 251.84 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 67.79 | 27-JAN-07:00 |
February | 220.32 | 01-FEB-00:10 | 251.84 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.19 | 20-FEB-15:00 | 71.23 | 03-FEB-07:00 |
March | 220.32 | 01-MAR-00:10 | 251.84 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.80 | 21-MAR-16:00 | 67.01 | 02-MAR-06:00 |
April | 220.32 | 01-APR-00:10 | 251.84 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.29 | 21-APR-14:00 | 47.83 | 12-APR-06:00 |
May | 220.32 | 01-MAY-00:10 | 251.84 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.68 | 19-MAY-14:00 | 33.67 | 02-MAY-06:00 |
June | 220.32 | 01-JUN-00:10 | 251.84 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.52 | 02-JUN-16:00 | 21.65 | 13-JUN-05:00 |
July | 220.32 | 01-JUL-00:10 | 251.84 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.12 | 02-JUL-16:00 | 14.45 | 05-JUL-06:00 |
August | 220.32 | 01-AUG-00:10 | 251.84 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.57 | 07-AUG-16:00 | 17.14 | 31-AUG-06:00 |
September | 220.32 | 01-SEP-00:10 | 251.84 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.02 | 19-SEP-16:00 | 37.45 | 30-SEP-06:00 |
October | 220.32 | 01-OCT-23:10 | 251.84 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.46 | 01-OCT-15:00 | 40.49 | 11-OCT-06:00 |
November | 220.32 | 01-NOV-00:10 | 251.84 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.76 | 03-NOV-16:00 | 58.39 | 17-NOV-04:00 |
December | 220.32 | 01-DEC-00:10 | 251.84 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 68.04 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 220.32 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.45 | |||||
Maximum of Months | 220.32 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 34.52 | 71.23 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 325.08 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 179.35 | 27-JAN-07:00 |
February | 907.20 | 01-FEB-00:10 | 325.08 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 1.41 | 20-FEB-16:08 | 187.58 | 03-FEB-07:00 |
March | 907.20 | 01-MAR-00:10 | 325.08 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 11.00 | 21-MAR-16:00 | 174.64 | 02-MAR-06:10 |
April | 907.20 | 01-APR-00:10 | 325.08 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 47.73 | 21-APR-15:20 | 126.25 | 12-APR-06:00 |
May | 907.20 | 01-MAY-00:10 | 325.08 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 67.23 | 21-MAY-16:00 | 87.13 | 02-MAY-06:00 |
June | 907.20 | 01-JUN-00:10 | 325.08 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 87.56 | 02-JUN-16:30 | 50.95 | 13-JUN-05:10 |
July | 907.20 | 01-JUL-00:10 | 325.08 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 88.00 | 02-JUL-16:00 | 36.24 | 05-JUL-06:00 |
August | 907.20 | 01-AUG-00:10 | 325.08 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 78.39 | 07-AUG-16:00 | 43.03 | 31-AUG-06:00 |
September | 907.20 | 01-SEP-00:10 | 325.08 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 60.43 | 19-SEP-16:00 | 94.46 | 30-SEP-06:00 |
October | 907.20 | 01-OCT-23:10 | 325.08 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 55.33 | 01-OCT-15:20 | 105.39 | 25-OCT-06:00 |
November | 907.20 | 01-NOV-00:10 | 325.08 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 4.88 | 03-NOV-16:00 | 152.24 | 17-NOV-06:10 |
December | 907.20 | 01-DEC-00:10 | 325.08 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 180.01 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 907.20 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 36.24 | ||||||
Maximum of Months | 907.20 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 88.00 | 187.58 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 1701.53 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 299.99 | 27-JAN-07:00 |
February | 15368.40 | 01-FEB-00:10 | 1701.53 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 314.49 | 03-FEB-07:00 |
March | 15368.40 | 01-MAR-00:10 | 1701.53 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.03 | 21-MAR-16:00 | 302.79 | 02-MAR-05:10 |
April | 15368.40 | 01-APR-00:10 | 1701.53 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.49 | 21-APR-14:00 | 212.84 | 12-APR-06:00 |
May | 15368.40 | 01-MAY-00:10 | 1701.53 | 01-MAY-19:10 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 107.78 | 21-MAY-14:00 | 149.62 | 02-MAY-06:00 |
June | 15368.40 | 01-JUN-00:10 | 1701.53 | 01-JUN-19:10 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 143.91 | 02-JUN-16:00 | 93.96 | 13-JUN-05:00 |
July | 15368.40 | 01-JUL-00:10 | 1701.53 | 03-JUL-19:10 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 138.65 | 02-JUL-16:00 | 64.27 | 05-JUL-06:00 |
August | 15368.40 | 01-AUG-00:10 | 1701.53 | 01-AUG-19:10 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 128.43 | 07-AUG-16:00 | 76.36 | 31-AUG-06:00 |
September | 15368.40 | 01-SEP-00:10 | 1701.53 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.11 | 19-SEP-14:00 | 164.69 | 30-SEP-06:00 |
October | 15368.40 | 01-OCT-23:10 | 1701.53 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.81 | 01-OCT-15:00 | 181.73 | 25-OCT-05:00 |
November | 15368.40 | 01-NOV-00:10 | 1701.53 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 267.58 | 17-NOV-04:00 |
December | 15368.40 | 01-DEC-00:10 | 1701.53 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 305.56 | 19-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 15368.40 | 1701.53 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.27 | |||||
Maximum of Months | 15368.40 | 1701.53 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 143.91 | 314.49 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 9504.80 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 885.55 | 27-JAN-07:00 |
February | 45622.98 | 01-FEB-00:10 | 9504.80 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 927.41 | 03-FEB-07:00 |
March | 45622.98 | 01-MAR-00:10 | 9504.80 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.32 | 22-MAR-13:00 | 883.34 | 02-MAR-05:50 |
April | 45622.98 | 01-APR-00:10 | 9504.80 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 243.23 | 21-APR-14:00 | 631.06 | 12-APR-06:00 |
May | 45622.98 | 01-MAY-00:10 | 9504.80 | 01-MAY-19:10 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 320.63 | 19-MAY-14:00 | 441.95 | 02-MAY-06:00 |
June | 45622.98 | 01-JUN-00:10 | 9504.80 | 01-JUN-19:10 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 413.15 | 02-JUN-16:00 | 268.54 | 13-JUN-05:00 |
July | 45622.98 | 01-JUL-00:10 | 9504.80 | 03-JUL-19:10 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 408.31 | 02-JUL-16:00 | 183.70 | 05-JUL-06:00 |
August | 45622.98 | 01-AUG-00:10 | 9504.80 | 01-AUG-19:10 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 366.90 | 07-AUG-16:00 | 218.23 | 31-AUG-06:00 |
September | 45622.98 | 01-SEP-00:10 | 9504.80 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 277.46 | 19-SEP-14:00 | 479.50 | 30-SEP-06:00 |
October | 45622.98 | 01-OCT-23:10 | 9504.80 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 250.05 | 01-OCT-15:00 | 534.40 | 25-OCT-06:00 |
November | 45622.98 | 01-NOV-00:10 | 9504.80 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.34 | 08-NOV-15:00 | 774.61 | 17-NOV-04:00 |
December | 45622.98 | 01-DEC-00:10 | 9504.80 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 889.56 | 19-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 45622.98 | 9504.80 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.70 | |||||
Maximum of Months | 45622.98 | 9504.80 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 413.15 | 927.41 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.88 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 75.21 | 27-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 177.88 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.21 | 20-FEB-16:10 | 79.01 | 03-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 177.88 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.13 | 21-MAR-16:00 | 74.36 | 02-MAR-05:10 |
April | 180.00 | 01-APR-00:10 | 177.88 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.66 | 21-APR-15:10 | 50.74 | 12-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 177.88 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.32 | 19-MAY-16:00 | 32.70 | 02-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 177.88 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.49 | 02-JUN-17:00 | 16.88 | 13-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 177.88 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.55 | 03-JUL-16:00 | 9.14 | 05-JUL-06:00 |
August | 180.00 | 01-AUG-00:10 | 177.88 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.52 | 07-AUG-16:00 | 13.24 | 14-AUG-08:00 |
September | 180.00 | 01-SEP-00:10 | 177.88 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.65 | 19-SEP-16:00 | 36.08 | 30-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 177.88 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.65 | 01-OCT-15:10 | 41.03 | 25-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 177.88 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.30 | 03-NOV-16:00 | 63.80 | 28-NOV-05:00 |
December | 180.00 | 01-DEC-00:10 | 177.88 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 75.49 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.14 | |||||
Maximum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 43.55 | 79.01 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.86 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 75.20 | 27-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 177.86 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.26 | 20-FEB-16:10 | 79.00 | 03-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 177.86 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.13 | 21-MAR-16:00 | 74.35 | 02-MAR-05:10 |
April | 180.00 | 01-APR-00:10 | 177.86 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.95 | 21-APR-15:10 | 50.74 | 12-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 177.86 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.25 | 19-MAY-16:00 | 32.70 | 02-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 177.86 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.26 | 02-JUN-17:00 | 17.66 | 13-JUN-06:00 |
July | 180.00 | 01-JUL-00:10 | 177.86 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.54 | 03-JUL-16:00 | 12.91 | 05-JUL-06:00 |
August | 180.00 | 01-AUG-00:10 | 177.86 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.71 | 07-AUG-16:00 | 15.38 | 31-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 177.86 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.56 | 19-SEP-16:00 | 36.08 | 30-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 177.86 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.06 | 01-OCT-15:10 | 41.03 | 25-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 177.86 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.98 | 03-NOV-15:10 | 63.80 | 28-NOV-05:00 |
December | 180.00 | 01-DEC-00:10 | 177.86 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 75.48 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.91 | |||||
Maximum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 43.54 | 79.00 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 111.79 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 24.37 | 27-JAN-08:00 |
February | 0.00 | 01-FEB-00:10 | 111.79 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 25.54 | 03-FEB-07:00 |
March | 0.00 | 01-MAR-00:10 | 111.79 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 23.59 | 02-MAR-05:00 |
April | 0.00 | 01-APR-00:10 | 111.79 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.95 | 21-APR-14:00 | 18.06 | 12-APR-06:00 |
May | 0.00 | 01-MAY-00:10 | 111.79 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.95 | 21-MAY-14:00 | 13.44 | 02-MAY-06:00 |
June | 0.00 | 01-JUN-00:10 | 111.79 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.62 | 02-JUN-16:00 | 8.96 | 13-JUN-05:00 |
July | 0.00 | 01-JUL-00:10 | 111.79 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.23 | 02-JUL-16:00 | 6.77 | 05-JUL-06:00 |
August | 0.00 | 01-AUG-00:10 | 111.79 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.47 | 07-AUG-16:00 | 7.67 | 31-AUG-06:00 |
September | 0.00 | 01-SEP-00:10 | 111.79 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 19-SEP-14:00 | 14.42 | 30-SEP-06:00 |
October | 0.00 | 01-OCT-00:10 | 111.79 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.40 | 01-OCT-15:00 | 15.85 | 25-OCT-06:00 |
November | 0.00 | 01-NOV-00:10 | 111.79 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 21.52 | 17-NOV-04:00 |
December | 0.00 | 01-DEC-00:10 | 111.79 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 24.14 | 19-DEC-04:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 0.00 | 111.79 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.77 | |||||
Maximum of Months | 0.00 | 111.79 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 8.62 | 25.54 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 111.82 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 20.99 | 27-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 111.82 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.47 | 20-FEB-16:10 | 22.05 | 03-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 111.82 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 21-MAR-16:00 | 20.75 | 02-MAR-05:10 |
April | 180.00 | 01-APR-00:10 | 111.82 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.81 | 21-APR-15:10 | 14.16 | 12-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 111.82 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.91 | 19-MAY-16:00 | 9.13 | 02-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 111.82 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.56 | 02-JUN-16:00 | 4.71 | 13-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 111.82 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.18 | 02-JUL-16:00 | 3.42 | 05-JUL-06:00 |
August | 180.00 | 01-AUG-00:10 | 111.82 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.44 | 07-AUG-16:00 | 4.44 | 16-AUG-21:40 |
September | 180.00 | 01-SEP-00:10 | 111.82 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.15 | 19-SEP-16:00 | 10.07 | 30-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 111.82 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.29 | 01-OCT-15:10 | 11.45 | 25-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 111.82 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 03-NOV-15:08 | 17.81 | 28-NOV-05:00 |
December | 180.00 | 01-DEC-00:10 | 111.82 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 21.07 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.42 | |||||
Maximum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 12.56 | 22.05 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.88 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 75.20 | 27-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 177.88 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.26 | 20-FEB-16:10 | 79.01 | 03-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 177.88 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.13 | 21-MAR-16:00 | 74.35 | 02-MAR-05:10 |
April | 180.00 | 01-APR-00:10 | 177.88 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.97 | 21-APR-15:10 | 50.74 | 12-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 177.88 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.46 | 19-MAY-16:00 | 32.70 | 02-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 177.88 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.53 | 14-JUN-16:00 | 16.88 | 13-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 177.88 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.49 | 03-JUL-16:00 | 9.51 | 05-JUL-07:10 |
August | 180.00 | 01-AUG-00:10 | 177.88 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.96 | 07-AUG-16:00 | 13.73 | 30-AUG-07:10 |
September | 180.00 | 01-SEP-00:10 | 177.88 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.73 | 19-SEP-16:00 | 36.08 | 30-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 177.88 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.11 | 01-OCT-15:10 | 41.03 | 25-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 177.88 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.31 | 03-NOV-16:00 | 63.81 | 28-NOV-05:00 |
December | 180.00 | 01-DEC-00:10 | 177.88 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 75.49 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.51 | |||||
Maximum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 43.53 | 79.01 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.86 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 75.20 | 27-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 177.86 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.26 | 20-FEB-16:08 | 79.00 | 03-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 177.86 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.13 | 21-MAR-16:00 | 74.35 | 02-MAR-05:10 |
April | 180.00 | 01-APR-00:10 | 177.86 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.97 | 21-APR-15:10 | 50.74 | 12-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 177.86 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.22 | 19-MAY-16:00 | 32.70 | 02-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 177.86 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.28 | 14-JUN-16:50 | 18.67 | 13-JUN-06:00 |
July | 180.00 | 01-JUL-00:10 | 177.86 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.49 | 03-JUL-16:10 | 15.44 | 05-JUL-06:40 |
August | 180.00 | 01-AUG-00:10 | 177.86 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.63 | 07-AUG-16:00 | 16.97 | 30-AUG-07:10 |
September | 180.00 | 01-SEP-00:10 | 177.86 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.77 | 19-SEP-16:00 | 36.08 | 30-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 177.86 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.70 | 01-OCT-15:10 | 41.03 | 25-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 177.86 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.98 | 03-NOV-15:08 | 63.80 | 28-NOV-05:00 |
December | 180.00 | 01-DEC-00:10 | 177.86 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 75.48 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.44 | |||||
Maximum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 43.49 | 79.00 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2263.36 | 02-JAN-00:10 | 1867.32 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 90.55 | 27-JAN-07:00 |
February | 2263.36 | 01-FEB-00:10 | 1867.32 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.29 | 20-FEB-16:00 | 95.14 | 03-FEB-07:00 |
March | 2263.36 | 01-MAR-00:10 | 1867.32 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.43 | 21-MAR-16:00 | 89.95 | 02-MAR-05:10 |
April | 2263.36 | 01-APR-00:10 | 1867.32 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.05 | 21-APR-14:00 | 65.13 | 12-APR-06:00 |
May | 2263.36 | 01-MAY-00:10 | 1867.32 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.18 | 19-MAY-14:00 | 45.67 | 02-MAY-06:00 |
June | 2263.36 | 01-JUN-00:10 | 1867.32 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.97 | 02-JUN-16:00 | 29.23 | 13-JUN-05:00 |
July | 2263.36 | 01-JUL-00:10 | 1867.32 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.60 | 02-JUL-16:00 | 19.48 | 05-JUL-06:00 |
August | 2263.36 | 01-AUG-00:10 | 1867.32 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.63 | 07-AUG-16:00 | 23.13 | 31-AUG-06:00 |
September | 2263.36 | 01-SEP-00:10 | 1867.32 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.98 | 19-SEP-14:00 | 50.88 | 30-SEP-06:00 |
October | 2263.36 | 01-OCT-23:10 | 1867.32 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.69 | 01-OCT-15:00 | 54.93 | 25-OCT-06:00 |
November | 2263.36 | 01-NOV-00:10 | 1867.32 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.03 | 08-NOV-15:00 | 79.77 | 17-NOV-04:00 |
December | 2263.36 | 01-DEC-00:10 | 1867.32 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 90.88 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.48 | ||||
Maximum of Months | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.97 | 95.14 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.88 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 75.40 | 27-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 177.88 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.92 | 20-FEB-16:10 | 79.20 | 03-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 177.88 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.97 | 21-MAR-16:00 | 74.55 | 02-MAR-05:10 |
April | 180.00 | 01-APR-00:10 | 177.88 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.32 | 21-APR-15:10 | 50.92 | 12-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 177.88 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.78 | 19-MAY-16:00 | 32.87 | 02-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 177.88 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.61 | 02-JUN-17:00 | 17.04 | 13-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 177.88 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.39 | 03-JUL-16:00 | 9.30 | 05-JUL-06:00 |
August | 180.00 | 01-AUG-00:10 | 177.88 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.80 | 07-AUG-16:00 | 12.52 | 14-AUG-08:00 |
September | 180.00 | 01-SEP-00:10 | 177.88 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.83 | 19-SEP-16:00 | 36.26 | 30-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 177.88 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.29 | 01-OCT-16:30 | 41.21 | 25-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 177.88 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.84 | 03-NOV-16:00 | 63.99 | 28-NOV-05:00 |
December | 180.00 | 01-DEC-00:10 | 177.88 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 75.68 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.30 | |||||
Maximum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 43.39 | 79.20 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.86 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 75.39 | 27-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 177.86 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.10 | 20-FEB-16:10 | 79.19 | 03-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 177.86 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.97 | 21-MAR-16:00 | 74.54 | 02-MAR-05:10 |
April | 180.00 | 01-APR-00:10 | 177.86 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.78 | 21-APR-15:10 | 50.92 | 12-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 177.86 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.54 | 19-MAY-16:00 | 32.87 | 02-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 177.86 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.39 | 02-JUN-17:00 | 17.04 | 13-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 177.86 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.39 | 03-JUL-16:00 | 12.24 | 18-JUL-21:50 |
August | 180.00 | 01-AUG-00:10 | 177.86 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.96 | 07-AUG-16:00 | 14.64 | 16-AUG-21:30 |
September | 180.00 | 01-SEP-00:10 | 177.86 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.89 | 19-SEP-16:00 | 36.25 | 30-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 177.86 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.73 | 01-OCT-15:10 | 41.21 | 25-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 177.86 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 03-NOV-15:10 | 63.99 | 28-NOV-05:00 |
December | 180.00 | 01-DEC-00:10 | 177.86 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 75.67 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.24 | |||||
Maximum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 43.39 | 79.19 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 111.82 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 38.57 | 27-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 111.82 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.91 | 22-FEB-16:10 | 40.52 | 03-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 111.82 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.10 | 21-MAR-16:00 | 38.14 | 02-MAR-05:10 |
April | 180.00 | 01-APR-00:10 | 111.82 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.09 | 21-APR-15:10 | 26.05 | 12-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 111.82 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.07 | 19-MAY-16:00 | 16.82 | 02-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 111.82 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.89 | 02-JUN-16:00 | 8.72 | 13-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 111.82 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.17 | 03-JUL-16:00 | 4.76 | 05-JUL-06:00 |
August | 180.00 | 01-AUG-00:10 | 111.82 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.51 | 07-AUG-16:00 | 6.35 | 31-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 111.82 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.66 | 19-SEP-16:00 | 18.55 | 30-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 111.82 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.31 | 01-OCT-15:10 | 21.09 | 25-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 111.82 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.69 | 03-NOV-16:00 | 32.74 | 28-NOV-05:00 |
December | 180.00 | 01-DEC-00:10 | 111.82 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 38.72 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.76 | |||||
Maximum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 22.17 | 40.52 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2988.03 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 204.82 | 27-JAN-07:00 |
February | 26988.77 | 01-FEB-00:10 | 2988.03 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 214.19 | 03-FEB-07:00 |
March | 26988.77 | 01-MAR-00:10 | 2988.03 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.07 | 22-MAR-13:00 | 202.95 | 02-MAR-05:10 |
April | 26988.77 | 01-APR-00:10 | 2988.03 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.97 | 21-APR-14:00 | 144.36 | 12-APR-06:00 |
May | 26988.77 | 01-MAY-00:10 | 2988.03 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.48 | 21-MAY-14:00 | 99.86 | 02-MAY-06:00 |
June | 26988.77 | 01-JUN-00:10 | 2988.03 | 01-JUN-19:10 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.66 | 02-JUN-16:00 | 60.93 | 13-JUN-05:00 |
July | 26988.77 | 01-JUL-00:10 | 2988.03 | 03-JUL-19:19 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.28 | 02-JUL-16:00 | 41.89 | 05-JUL-06:00 |
August | 26988.77 | 01-AUG-00:10 | 2988.03 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.72 | 07-AUG-16:00 | 49.64 | 31-AUG-06:00 |
September | 26988.77 | 01-SEP-00:10 | 2988.03 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.64 | 19-SEP-14:00 | 108.30 | 30-SEP-06:00 |
October | 26988.77 | 01-OCT-23:10 | 2988.03 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.02 | 01-OCT-15:00 | 120.62 | 25-OCT-06:00 |
November | 26988.77 | 01-NOV-00:10 | 2988.03 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 | 08-NOV-15:00 | 176.91 | 28-NOV-05:00 |
December | 26988.77 | 01-DEC-00:10 | 2988.03 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 205.59 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.89 | |||||
Maximum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 91.66 | 214.19 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2988.03 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 204.83 | 27-JAN-07:00 |
February | 26988.77 | 01-FEB-00:10 | 2988.03 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 214.19 | 03-FEB-07:00 |
March | 26988.77 | 01-MAR-00:10 | 2988.03 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.78 | 21-MAR-16:00 | 202.95 | 02-MAR-05:10 |
April | 26988.77 | 01-APR-00:10 | 2988.03 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.97 | 21-APR-14:00 | 144.36 | 12-APR-06:00 |
May | 26988.77 | 01-MAY-00:10 | 2988.03 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.48 | 21-MAY-14:00 | 99.87 | 02-MAY-06:00 |
June | 26988.77 | 01-JUN-00:10 | 2988.03 | 01-JUN-19:10 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.66 | 02-JUN-16:00 | 60.93 | 13-JUN-05:00 |
July | 26988.77 | 01-JUL-00:10 | 2988.03 | 03-JUL-19:19 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.28 | 02-JUL-16:00 | 41.89 | 05-JUL-06:00 |
August | 26988.77 | 01-AUG-00:10 | 2988.03 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.72 | 07-AUG-16:00 | 49.64 | 31-AUG-06:00 |
September | 26988.77 | 01-SEP-00:10 | 2988.03 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.63 | 19-SEP-14:00 | 108.30 | 30-SEP-06:00 |
October | 26988.77 | 01-OCT-23:10 | 2988.03 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.02 | 01-OCT-15:00 | 120.63 | 25-OCT-06:00 |
November | 26988.77 | 01-NOV-00:10 | 2988.03 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 176.91 | 28-NOV-05:00 |
December | 26988.77 | 01-DEC-00:10 | 2988.03 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 205.59 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.89 | |||||
Maximum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 91.66 | 214.19 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 1060.81 | 02-JAN-20:10 | 14912.86 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 183.33 | 27-JAN-07:00 |
February | 2401.70 | 01-FEB-00:10 | 1060.81 | 01-FEB-20:10 | 14912.86 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 191.72 | 03-FEB-07:00 |
March | 2401.70 | 01-MAR-00:10 | 1060.81 | 01-MAR-20:10 | 14912.86 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 5.25 | 21-MAR-16:00 | 178.99 | 02-MAR-06:10 |
April | 2401.70 | 01-APR-00:10 | 1060.81 | 03-APR-19:10 | 14912.86 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 45.68 | 21-APR-14:00 | 129.21 | 12-APR-06:00 |
May | 2401.70 | 01-MAY-00:10 | 1060.81 | 01-MAY-19:10 | 14912.86 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 61.35 | 21-MAY-14:00 | 89.37 | 02-MAY-06:00 |
June | 2401.70 | 01-JUN-00:10 | 1060.81 | 01-JUN-19:10 | 14912.86 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 82.13 | 02-JUN-16:00 | 54.54 | 13-JUN-05:00 |
July | 2401.70 | 01-JUL-00:10 | 1060.81 | 03-JUL-19:10 | 14912.86 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 79.11 | 02-JUL-16:00 | 37.48 | 05-JUL-06:00 |
August | 2401.70 | 01-AUG-00:10 | 1060.81 | 01-AUG-19:10 | 14912.86 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 73.24 | 07-AUG-16:00 | 44.42 | 31-AUG-06:00 |
September | 2401.70 | 01-SEP-00:10 | 1060.81 | 01-SEP-19:10 | 14912.86 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 55.23 | 19-SEP-14:00 | 96.92 | 30-SEP-06:00 |
October | 2401.70 | 01-OCT-23:10 | 1060.81 | 02-OCT-19:10 | 14912.86 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 49.32 | 01-OCT-15:00 | 107.96 | 25-OCT-06:00 |
November | 2401.70 | 01-NOV-00:10 | 1060.81 | 01-NOV-19:10 | 14912.86 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 158.38 | 28-NOV-05:00 |
December | 2401.70 | 01-DEC-00:10 | 1060.81 | 01-DEC-20:10 | 14912.86 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 184.02 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2401.70 | 1060.81 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 0.00 | 37.48 | ||||||
Maximum of Months | 2401.70 | 1060.81 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 82.13 | 191.72 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2395.44 | 02-JAN-00:10 | 1976.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 160.63 | 27-JAN-07:00 |
February | 2395.44 | 01-FEB-00:10 | 1976.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.38 | 20-FEB-16:00 | 168.75 | 03-FEB-07:00 |
March | 2395.44 | 01-MAR-00:10 | 1976.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.80 | 21-MAR-16:00 | 158.80 | 02-MAR-05:40 |
April | 2395.44 | 01-APR-00:10 | 1976.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.41 | 21-APR-15:00 | 110.11 | 12-APR-06:00 |
May | 2395.44 | 01-MAY-00:10 | 1976.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.99 | 21-MAY-14:00 | 78.04 | 02-MAY-06:00 |
June | 2395.44 | 01-JUN-00:10 | 1976.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.29 | 02-JUN-16:00 | 50.35 | 13-JUN-05:00 |
July | 2395.44 | 01-JUL-00:10 | 1976.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.34 | 02-JUL-16:00 | 32.90 | 05-JUL-06:00 |
August | 2395.44 | 01-AUG-00:10 | 1976.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.59 | 07-AUG-16:00 | 39.51 | 31-AUG-06:00 |
September | 2395.44 | 01-SEP-00:10 | 1976.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.00 | 19-SEP-14:00 | 86.63 | 30-SEP-06:00 |
October | 2395.44 | 01-OCT-23:10 | 1976.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.20 | 01-OCT-15:00 | 92.65 | 11-OCT-06:00 |
November | 2395.44 | 01-NOV-00:10 | 1976.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.76 | 08-NOV-15:00 | 136.22 | 28-NOV-05:00 |
December | 2395.44 | 01-DEC-00:10 | 1976.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 161.22 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.90 | ||||
Maximum of Months | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.29 | 168.75 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 18300.50 | 05-JAN-22:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 15326.60 | 01-FEB-22:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 12200.59 | 01-MAR-21:00 | 8945.92 | 13190.31 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 13096.58 | 30-APR-10:33 | 11501.89 | 13190.31 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 13673.79 | 21-MAY-10:33 | 11501.89 | 13190.31 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 14369.70 | 15-JUN-18:10 | 26837.75 | 35173.99 | 27376.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 18890.48 | 19-JUL-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 22176.14 | 24-AUG-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 24615.22 | 22-SEP-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 24396.74 | 20-OCT-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 23821.68 | 10-NOV-22:00 | 20447.81 | 23449.32 | 18251.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 22137.70 | 01-DEC-22:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 12200.59 | 8945.92 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24615.22 | 26837.75 | 35173.99 | 27376.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2870.18 | 12-JAN-13:50 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.15 |
February | 2902.71 | 07-FEB-13:30 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.09 |
March | 2264.61 | 16-MAR-13:20 | 519.79 | 332.00 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.34 |
April | 2343.33 | 03-APR-14:10 | 389.84 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 12.25 | 0.00 |
May | 2294.12 | 31-MAY-18:04 | 4548.18 | 2655.97 | 3247.60 | 0.00 | 0.00 | 0.00 | 0.00 | 31.02 | 0.00 |
June | 2662.32 | 15-JUN-18:20 | 1819.27 | 1062.39 | 1299.04 | 0.00 | 0.00 | 0.00 | 0.00 | 51.63 | 0.00 |
July | 2656.65 | 26-JUL-18:04 | 4548.18 | 2655.97 | 3247.60 | 0.00 | 0.00 | 0.00 | 0.00 | 43.49 | 0.00 |
August | 2829.19 | 27-AUG-12:00 | 389.84 | 199.20 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 41.57 | 0.00 |
September | 3456.72 | 20-SEP-12:50 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 36.28 | 0.00 |
October | 3607.01 | 18-OCT-13:00 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 17.27 | 0.00 |
November | 3406.10 | 10-NOV-12:00 | 519.79 | 332.00 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.41 |
December | 2608.10 | 16-DEC-13:30 | 389.84 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.65 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2264.61 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3607.01 | 4548.18 | 2655.97 | 3247.60 | 0.00 | 0.00 | 0.00 | 0.00 | 51.63 | 45.65 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1425.67 | 12-JAN-22:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.03 |
February | 1573.57 | 21-FEB-22:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.59 |
March | 1632.07 | 16-MAR-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.28 |
April | 1950.18 | 28-APR-20:55 | 2407.68 | 1230.25 | 1504.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.14 |
May | 2124.90 | 19-MAY-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 10.38 | 0.00 |
June | 2330.86 | 15-JUN-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 15.93 | 0.00 |
July | 2293.03 | 26-JUL-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 8.56 | 0.00 |
August | 2324.96 | 07-AUG-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 13.32 | 0.00 |
September | 2215.18 | 20-SEP-20:10 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 2.46 | 0.00 |
October | 2143.33 | 05-OCT-20:10 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
November | 1819.51 | 09-NOV-22:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.16 |
December | 1272.51 | 07-DEC-21:20 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.31 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1272.51 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2330.86 | 2407.68 | 1230.25 | 1504.29 | 0.00 | 0.00 | 0.00 | 0.00 | 15.93 | 29.31 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 918.95 | 03-JAN-21:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.08 |
February | 977.95 | 20-FEB-11:33 | 286.42 | 684.18 | 1060.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.97 |
March | 1015.73 | 16-MAR-18:10 | 1336.61 | 3648.94 | 4771.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.26 |
April | 1189.09 | 30-APR-10:33 | 286.42 | 684.18 | 1060.35 | 0.00 | 0.00 | 0.00 | 0.00 | 3.74 | 0.00 |
May | 1725.40 | 31-MAY-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 22.20 | 0.00 |
June | 2087.29 | 15-JUN-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 39.81 | 0.00 |
July | 2072.12 | 03-JUL-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 17.72 | 0.00 |
August | 2024.52 | 07-AUG-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 31.37 | 0.00 |
September | 1724.37 | 22-SEP-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 8.71 | 0.00 |
October | 1529.41 | 05-OCT-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 |
November | 1067.77 | 10-NOV-11:33 | 190.94 | 570.15 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.21 |
December | 910.71 | 10-DEC-11:35 | 190.94 | 456.12 | 706.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.31 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 910.71 | 190.94 | 456.12 | 706.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2087.29 | 1336.61 | 3648.94 | 4771.59 | 0.00 | 0.00 | 0.00 | 0.00 | 39.81 | 35.08 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 539.76 | 01-JAN-11:33 | 220.32 | 251.83 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.67 |
February | 580.28 | 20-FEB-11:33 | 220.32 | 251.83 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.70 |
March | 597.03 | 16-MAR-10:33 | 146.88 | 209.86 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.01 |
April | 703.21 | 30-APR-10:33 | 220.32 | 251.83 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 2.62 | 0.00 |
May | 783.78 | 31-MAY-21:00 | 195.84 | 223.85 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 10.23 | 0.00 |
June | 1033.81 | 15-JUN-18:40 | 171.36 | 223.85 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 26.35 | 0.00 |
July | 1026.41 | 03-JUL-18:30 | 342.72 | 447.71 | 458.82 | 0.00 | 0.00 | 0.00 | 0.00 | 24.37 | 0.00 |
August | 992.18 | 07-AUG-21:00 | 195.84 | 223.85 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 18.16 | 0.00 |
September | 766.08 | 22-SEP-21:00 | 195.84 | 223.85 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 2.40 | 0.00 |
October | 731.74 | 05-OCT-10:33 | 146.88 | 209.86 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 9.95 | 0.00 |
November | 631.44 | 10-NOV-11:33 | 146.88 | 209.86 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.32 |
December | 536.17 | 10-DEC-11:35 | 146.88 | 167.88 | 203.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.15 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 536.17 | 146.88 | 167.88 | 203.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1033.81 | 342.72 | 447.71 | 458.82 | 0.00 | 0.00 | 0.00 | 0.00 | 26.35 | 19.67 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 37506.08 | 12-JAN-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 67.01 |
February | 37833.00 | 21-FEB-20:55 | 1411.20 | 650.17 | 9145.60 | 79453.15 | 0.00 | 0.00 | 0.00 | 0.00 | 53.15 |
March | 37955.97 | 16-MAR-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 39.61 |
April | 38680.17 | 28-APR-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 5.67 | 0.00 |
May | 38974.23 | 30-MAY-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 27.54 | 0.00 |
June | 39336.58 | 15-JUN-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 54.36 | 0.00 |
July | 39308.52 | 03-JUL-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 24.20 | 0.00 |
August | 39215.74 | 04-AUG-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 51.46 | 0.00 |
September | 38934.53 | 20-SEP-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 9.07 | 0.00 |
October | 38718.90 | 05-OCT-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
November | 38082.28 | 09-NOV-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 23.12 |
December | 37296.26 | 15-DEC-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 56.63 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 37296.26 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 39336.58 | 1411.20 | 650.17 | 9145.60 | 79453.15 | 0.00 | 0.00 | 0.00 | 54.36 | 67.01 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11519.69 | 01-JAN-11:00 | 8538.00 | 124.78 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.91 |
February | 11387.69 | 20-FEB-13:00 | 5122.80 | 124.78 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.88 |
March | 10233.80 | 14-MAR-15:03 | 51228.00 | 623.89 | 2133.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.20 |
April | 11079.69 | 19-APR-21:10 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 41.11 | 0.00 |
May | 11408.17 | 31-MAY-21:10 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 41.38 | 0.00 |
June | 11975.53 | 15-JUN-21:10 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 84.25 | 0.00 |
July | 11912.14 | 25-JUL-21:10 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 73.74 | 0.00 |
August | 12340.83 | 07-AUG-21:10 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 71.95 | 0.00 |
September | 12152.87 | 19-SEP-15:03 | 51228.00 | 623.89 | 2133.76 | 0.00 | 0.00 | 0.00 | 0.00 | 92.24 | 0.00 |
October | 12762.13 | 22-OCT-12:00 | 5122.80 | 124.78 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.03 |
November | 12786.04 | 11-NOV-11:00 | 8538.00 | 124.78 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.40 |
December | 11099.26 | 16-DEC-13:30 | 5122.80 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.89 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10233.80 | 5122.80 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12786.04 | 51228.00 | 1134.35 | 2133.76 | 0.00 | 0.00 | 0.00 | 0.00 | 92.24 | 118.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 32460.31 | 03-JAN-22:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 346.86 |
February | 33687.47 | 07-FEB-22:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 263.24 |
March | 34355.45 | 16-MAR-21:10 | 91245.96 | 12673.07 | 14779.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206.59 |
April | 37890.41 | 21-APR-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 25.74 | 0.00 |
May | 40719.23 | 31-MAY-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 118.15 | 0.00 |
June | 43082.31 | 15-JUN-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 240.65 | 0.00 |
July | 42881.52 | 26-JUL-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 132.06 | 0.00 |
August | 43572.45 | 07-AUG-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 205.51 | 0.00 |
September | 41891.79 | 21-SEP-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 60.42 | 0.00 |
October | 41271.68 | 05-OCT-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.80 |
November | 37775.13 | 09-NOV-22:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.75 |
December | 30836.08 | 15-DEC-22:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 289.59 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 30836.08 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 43572.45 | 91245.96 | 12673.07 | 14779.89 | 0.00 | 0.00 | 0.00 | 0.00 | 240.65 | 346.86 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2114.78 | 30-JAN-16:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.53 |
February | 2212.35 | 20-FEB-16:02 | 324.00 | 352.21 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 | 0.00 |
March | 2205.48 | 16-MAR-15:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
April | 2234.64 | 16-APR-15:02 | 324.00 | 352.21 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 17.11 | 0.00 |
May | 2239.44 | 17-MAY-15:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 16.82 | 0.00 |
June | 2256.35 | 14-JUN-15:02 | 486.00 | 249.04 | 250.23 | 0.00 | 0.00 | 0.00 | 0.00 | 37.74 | 0.00 |
July | 2227.19 | 31-JUL-18:02 | 693.00 | 791.58 | 605.82 | 0.00 | 0.00 | 0.00 | 0.00 | 26.44 | 0.00 |
August | 2239.16 | 28-AUG-18:02 | 831.60 | 949.89 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 15.99 | 0.00 |
September | 2242.13 | 01-SEP-18:02 | 831.60 | 949.89 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 21.13 | 0.00 |
October | 2226.76 | 31-OCT-15:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.69 |
November | 2187.01 | 07-NOV-16:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.56 |
December | 2109.16 | 16-DEC-16:02 | 324.00 | 352.21 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.21 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2109.16 | 324.00 | 249.04 | 250.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2256.35 | 831.60 | 949.89 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 37.74 | 22.21 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2034.13 | 30-JAN-16:02 | 583.20 | 298.81 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.84 |
February | 2153.34 | 20-FEB-16:02 | 324.00 | 352.17 | 331.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.92 | 0.00 |
March | 2155.65 | 16-MAR-15:02 | 583.20 | 298.81 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.22 |
April | 2416.46 | 06-APR-18:11 | 1386.00 | 1582.97 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.59 |
May | 2362.37 | 20-MAY-08:51 | 486.00 | 896.42 | 1469.59 | 0.00 | 0.00 | 0.00 | 0.00 | 6.88 | 0.00 |
June | 2495.02 | 19-JUN-18:51 | 1386.00 | 1582.97 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 5.20 | 0.00 |
July | 2222.59 | 12-JUL-08:11 | 324.00 | 704.33 | 1019.23 | 0.00 | 0.00 | 0.00 | 0.00 | 4.99 | 0.00 |
August | 2339.15 | 26-AUG-08:11 | 486.00 | 896.42 | 1469.59 | 0.00 | 0.00 | 0.00 | 0.00 | 7.81 | 0.00 |
September | 2229.76 | 01-SEP-18:02 | 831.60 | 949.78 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 21.17 | 0.00 |
October | 2212.36 | 03-OCT-18:21 | 1108.80 | 1266.37 | 969.19 | 0.00 | 0.00 | 0.00 | 0.00 | 2.02 | 0.00 |
November | 2124.70 | 03-NOV-15:02 | 583.20 | 298.81 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 1.71 | 0.00 |
December | 2046.60 | 16-DEC-16:02 | 324.00 | 352.17 | 331.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.78 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2034.13 | 324.00 | 298.81 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2495.02 | 1386.00 | 1582.97 | 1469.59 | 0.00 | 0.00 | 0.00 | 0.00 | 21.17 | 27.59 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 504.53 | 12-JAN-14:25 | 0.00 | 62.60 | 61.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.18 |
February | 474.16 | 07-FEB-13:40 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.87 |
March | 370.31 | 16-MAR-12:50 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.49 |
April | 348.94 | 03-APR-14:00 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
May | 332.77 | 19-MAY-20:20 | 0.00 | 99.50 | 178.01 | 0.00 | 0.00 | 0.00 | 0.00 | 2.91 | 0.00 |
June | 374.62 | 15-JUN-20:20 | 0.00 | 99.50 | 178.01 | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 0.00 |
July | 377.12 | 02-JUL-20:50 | 0.00 | 111.79 | 178.01 | 0.00 | 0.00 | 0.00 | 0.00 | 4.53 | 0.00 |
August | 399.82 | 27-AUG-13:40 | 0.00 | 36.89 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 5.52 | 0.00 |
September | 508.03 | 19-SEP-13:30 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 4.78 | 0.00 |
October | 579.63 | 22-OCT-13:15 | 0.00 | 73.78 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.55 |
November | 543.94 | 09-NOV-13:50 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.60 |
December | 429.34 | 16-DEC-13:40 | 0.00 | 36.89 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.34 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 332.77 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 579.63 | 0.00 | 111.79 | 178.01 | 0.00 | 0.00 | 0.00 | 0.00 | 5.52 | 9.34 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 730.60 | 13-JAN-19:02 | 831.60 | 597.13 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.66 |
February | 786.27 | 22-FEB-16:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 | 0.00 |
March | 819.16 | 15-MAR-21:52 | 1080.00 | 449.53 | 526.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.55 |
April | 839.39 | 21-APR-18:02 | 831.60 | 597.13 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 5.07 | 0.00 |
May | 883.92 | 20-MAY-08:51 | 486.00 | 563.59 | 1439.98 | 0.00 | 0.00 | 0.00 | 0.00 | 2.30 | 0.00 |
June | 903.85 | 14-JUN-08:11 | 360.00 | 492.02 | 1109.66 | 0.00 | 0.00 | 0.00 | 0.00 | 2.97 | 0.00 |
July | 872.98 | 06-JUL-08:61 | 324.00 | 442.82 | 998.70 | 0.00 | 0.00 | 0.00 | 0.00 | 1.69 | 0.00 |
August | 857.42 | 29-AUG-21:51 | 1440.00 | 599.37 | 701.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.85 |
September | 839.21 | 11-SEP-21:51 | 1260.00 | 524.45 | 614.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.18 |
October | 839.35 | 04-OCT-18:02 | 831.60 | 597.13 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 3.88 | 0.00 |
November | 797.85 | 09-NOV-16:02 | 583.20 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.69 | 0.00 |
December | 733.63 | 16-DEC-09:02 | 324.00 | 375.72 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 730.60 | 324.00 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 903.85 | 1440.00 | 599.37 | 1439.98 | 0.00 | 0.00 | 0.00 | 0.00 | 5.07 | 10.50 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1876.68 | 31-JAN-09:02 | 216.00 | 469.61 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.97 |
February | 1938.00 | 20-FEB-16:02 | 324.00 | 352.21 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.90 | 0.00 |
March | 1939.94 | 16-MAR-15:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.24 |
April | 1975.58 | 21-APR-15:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 23.46 | 0.00 |
May | 2013.62 | 20-MAY-08:62 | 324.00 | 597.68 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 3.52 | 0.00 |
June | 2024.92 | 21-JUN-08:62 | 216.00 | 469.61 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 11.48 | 0.00 |
July | 2032.16 | 11-JUL-08:62 | 216.00 | 469.61 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 11.78 | 0.00 |
August | 2018.38 | 04-AUG-08:61 | 324.00 | 704.41 | 1019.35 | 0.00 | 0.00 | 0.00 | 0.00 | 7.48 | 0.00 |
September | 2013.23 | 16-SEP-08:62 | 324.00 | 597.68 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.48 |
October | 2020.13 | 05-OCT-08:62 | 216.00 | 469.61 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 | 0.00 |
November | 1940.97 | 09-NOV-09:02 | 216.00 | 469.61 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.18 |
December | 1885.99 | 16-DEC-09:02 | 324.00 | 597.68 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.38 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1876.68 | 216.00 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2032.16 | 583.20 | 704.41 | 1019.35 | 0.00 | 0.00 | 0.00 | 0.00 | 23.46 | 40.38 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1757.11 | 31-JAN-09:02 | 216.00 | 469.55 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.98 |
February | 1905.76 | 22-FEB-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 |
March | 1900.35 | 22-MAR-15:02 | 583.20 | 298.81 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 3.16 | 0.00 |
April | 2314.74 | 27-APR-08:51 | 324.00 | 704.33 | 1019.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.22 |
May | 2398.19 | 20-MAY-08:32 | 270.00 | 498.01 | 816.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.96 |
June | 2396.94 | 13-JUN-08:12 | 180.00 | 391.30 | 566.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.52 |
July | 2328.05 | 04-JUL-08:62 | 324.00 | 597.61 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.29 |
August | 2296.22 | 30-AUG-08:51 | 324.00 | 704.33 | 1019.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.91 |
September | 2270.87 | 19-SEP-08:51 | 288.00 | 626.07 | 905.99 | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 0.00 |
October | 2213.77 | 03-OCT-08:51 | 288.00 | 626.07 | 905.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.97 |
November | 2058.26 | 09-NOV-09:51 | 288.00 | 626.07 | 905.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.10 |
December | 1811.41 | 16-DEC-09:02 | 324.00 | 597.61 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.44 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1757.11 | 180.00 | 298.81 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2398.19 | 680.40 | 704.33 | 1019.23 | 0.00 | 0.00 | 0.00 | 0.00 | 3.16 | 39.44 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1725.09 | 01-JAN-11:33 | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.43 |
February | 1823.02 | 20-FEB-11:33 | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.71 |
March | 1867.86 | 16-MAR-18:10 | 10562.33 | 9959.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.39 |
April | 2168.42 | 30-APR-10:33 | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.22 | 0.00 |
May | 2284.29 | 20-MAY-10:33 | 2263.36 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.81 | 0.00 |
June | 3173.90 | 15-JUN-18:40 | 1760.39 | 1659.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.00 | 0.00 |
July | 2789.46 | 26-JUL-18:25 | 3520.78 | 3319.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.55 | 0.00 |
August | 2848.69 | 07-AUG-18:25 | 3520.78 | 3319.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.17 | 0.00 |
September | 2566.65 | 20-SEP-18:17 | 5281.16 | 4979.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.00 | 0.00 |
October | 2274.33 | 05-OCT-10:33 | 1508.90 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.72 | 0.00 |
November | 1976.40 | 10-NOV-11:33 | 1508.90 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.47 |
December | 1653.09 | 10-DEC-11:35 | 1508.90 | 1244.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.12 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 1653.09 | 1508.90 | 1244.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3173.90 | 10562.33 | 9959.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.00 | 27.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2226.73 | 30-JAN-16:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.61 |
February | 2338.04 | 20-FEB-16:02 | 324.00 | 352.21 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 | 0.00 |
March | 2334.39 | 14-MAR-15:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 2.71 | 0.00 |
April | 2374.88 | 16-APR-15:02 | 324.00 | 352.21 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 16.86 | 0.00 |
May | 2375.79 | 17-MAY-15:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 16.60 | 0.00 |
June | 2400.00 | 14-JUN-15:02 | 486.00 | 249.04 | 250.23 | 0.00 | 0.00 | 0.00 | 0.00 | 37.49 | 0.00 |
July | 2359.00 | 31-JUL-18:02 | 693.00 | 791.58 | 605.82 | 0.00 | 0.00 | 0.00 | 0.00 | 26.20 | 0.00 |
August | 2361.79 | 28-AUG-18:02 | 831.60 | 949.89 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 15.80 | 0.00 |
September | 2361.64 | 01-SEP-18:02 | 831.60 | 949.89 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 20.89 | 0.00 |
October | 2346.33 | 31-OCT-15:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.79 |
November | 2309.57 | 07-NOV-16:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.70 |
December | 2226.48 | 16-DEC-16:02 | 324.00 | 352.21 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.33 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2226.48 | 324.00 | 249.04 | 250.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2400.00 | 831.60 | 949.89 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 37.49 | 22.33 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2085.02 | 30-JAN-16:02 | 583.20 | 298.81 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.00 |
February | 2266.71 | 20-FEB-16:02 | 324.00 | 352.17 | 331.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.81 | 0.00 |
March | 2265.04 | 16-MAR-15:02 | 583.20 | 298.81 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
April | 2552.90 | 06-APR-18:11 | 1386.00 | 1582.97 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.83 |
May | 2486.26 | 20-MAY-08:51 | 486.00 | 896.42 | 1469.59 | 0.00 | 0.00 | 0.00 | 0.00 | 6.76 | 0.00 |
June | 2620.37 | 19-JUN-18:51 | 1386.00 | 1582.97 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 4.57 | 0.00 |
July | 2408.61 | 25-JUL-18:02 | 693.00 | 791.48 | 605.75 | 0.00 | 0.00 | 0.00 | 0.00 | 28.83 | 0.00 |
August | 2422.60 | 26-AUG-08:11 | 486.00 | 896.42 | 1469.59 | 0.00 | 0.00 | 0.00 | 0.00 | 8.44 | 0.00 |
September | 2349.93 | 01-SEP-18:02 | 831.60 | 949.78 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 20.95 | 0.00 |
October | 2312.27 | 03-OCT-18:21 | 1108.80 | 1266.37 | 969.19 | 0.00 | 0.00 | 0.00 | 0.00 | 2.06 | 0.00 |
November | 2226.33 | 07-NOV-16:02 | 583.20 | 298.81 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.18 |
December | 2140.72 | 16-DEC-16:02 | 324.00 | 352.17 | 331.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.70 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2085.02 | 324.00 | 298.81 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2620.37 | 1386.00 | 1582.97 | 1469.59 | 0.00 | 0.00 | 0.00 | 0.00 | 28.83 | 27.83 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1191.55 | 28-JAN-16:02 | 324.00 | 221.41 | 325.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.85 |
February | 1232.18 | 20-FEB-16:02 | 324.00 | 221.41 | 325.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.06 | 0.00 |
March | 1233.28 | 14-MAR-15:02 | 583.20 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 1.23 | 0.00 |
April | 1221.91 | 15-APR-15:02 | 324.00 | 221.41 | 325.16 | 0.00 | 0.00 | 0.00 | 0.00 | 5.66 | 0.00 |
May | 1202.51 | 24-MAY-15:02 | 583.20 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 0.00 |
June | 1209.59 | 28-JUN-15:02 | 583.20 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 6.75 | 0.00 |
July | 1217.97 | 26-JUL-15:02 | 486.00 | 156.55 | 245.16 | 0.00 | 0.00 | 0.00 | 0.00 | 17.80 | 0.00 |
August | 1224.65 | 05-AUG-15:02 | 270.00 | 184.51 | 270.96 | 0.00 | 0.00 | 0.00 | 0.00 | 13.29 | 0.00 |
September | 1235.57 | 06-SEP-15:02 | 583.20 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 5.86 | 0.00 |
October | 1248.10 | 18-OCT-15:02 | 583.20 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 7.59 | 0.00 |
November | 1224.86 | 14-NOV-16:02 | 583.20 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.91 |
December | 1192.10 | 16-DEC-16:02 | 324.00 | 221.41 | 325.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.78 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1191.55 | 270.00 | 156.55 | 245.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1248.10 | 583.20 | 221.41 | 325.16 | 0.00 | 0.00 | 0.00 | 0.00 | 17.80 | 13.85 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18395.97 | 03-JAN-22:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.51 |
February | 19458.15 | 07-FEB-23:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.32 |
March | 20318.07 | 15-MAR-21:53 | 161932.61 | 11952.12 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.89 |
April | 22208.21 | 19-APR-22:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 19.91 | 0.00 |
May | 23185.42 | 31-MAY-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 25.88 | 0.00 |
June | 23785.66 | 15-JUN-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 48.83 | 0.00 |
July | 23589.18 | 25-JUL-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 46.64 | 0.00 |
August | 23739.04 | 07-AUG-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 42.68 | 0.00 |
September | 22608.90 | 22-SEP-22:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 5.84 | 0.00 |
October | 22102.47 | 05-OCT-21:52 | 215910.14 | 15936.16 | 53983.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.54 |
November | 20276.40 | 09-NOV-22:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.73 |
December | 18326.95 | 15-DEC-23:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.49 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 18326.95 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23785.66 | 215910.14 | 15936.16 | 53983.22 | 0.00 | 0.00 | 0.00 | 0.00 | 48.83 | 78.51 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 20187.10 | 03-JAN-22:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.51 |
February | 21126.53 | 06-FEB-22:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.03 |
March | 21883.92 | 15-MAR-21:53 | 161932.61 | 11952.12 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.89 |
April | 23570.51 | 19-APR-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 25.71 | 0.00 |
May | 24370.50 | 19-MAY-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 36.23 | 0.00 |
June | 24970.42 | 15-JUN-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 48.82 | 0.00 |
July | 24766.35 | 25-JUL-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 46.64 | 0.00 |
August | 24905.72 | 07-AUG-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 42.67 | 0.00 |
September | 23734.90 | 22-SEP-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 0.00 |
October | 23252.41 | 04-OCT-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 7.87 | 0.00 |
November | 21762.87 | 09-NOV-22:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.73 |
December | 20157.71 | 15-DEC-23:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.49 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 20157.71 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24970.42 | 161932.61 | 11952.12 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 48.82 | 78.51 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 27522.86 | 01-JAN-11:50 | 800.57 | 353.60 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 60.36 |
February | 28520.90 | 20-FEB-11:50 | 800.57 | 353.60 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 19.89 |
March | 28753.43 | 19-MAR-10:33 | 2401.70 | 1060.81 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 31.96 |
April | 30338.64 | 30-APR-10:50 | 800.57 | 353.60 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 2.59 | 0.00 |
May | 30487.57 | 21-MAY-10:33 | 2401.70 | 1060.81 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 30.72 | 0.00 |
June | 30951.57 | 18-JUN-10:40 | 2401.70 | 1060.81 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 47.12 | 0.00 |
July | 31104.54 | 02-JUL-10:40 | 2401.70 | 1060.81 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 45.71 | 0.00 |
August | 31018.34 | 06-AUG-10:37 | 2401.70 | 1060.81 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 42.90 | 0.00 |
September | 30709.45 | 17-SEP-10:33 | 2401.70 | 1060.81 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 30.83 | 0.00 |
October | 30188.70 | 05-OCT-10:33 | 1601.14 | 884.01 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 20.22 | 0.00 |
November | 28307.68 | 10-NOV-11:50 | 533.71 | 294.67 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 18.03 |
December | 27482.13 | 10-DEC-11:50 | 800.57 | 353.60 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 46.47 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 27482.13 | 533.71 | 294.67 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31104.54 | 2401.70 | 1060.81 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 47.12 | 60.36 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3511.92 | 01-JAN-11:33 | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.82 |
February | 3840.50 | 20-FEB-11:33 | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.12 |
March | 3863.26 | 16-MAR-10:33 | 1596.96 | 1646.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.08 |
April | 4623.95 | 30-APR-10:33 | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.68 | 0.00 |
May | 5654.31 | 30-MAY-15:02 | 5323.20 | 2195.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.42 | 0.00 |
June | 6522.71 | 17-JUN-17:13 | 4790.88 | 3952.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.66 | 0.00 |
July | 6866.53 | 03-JUL-12:50 | 532.32 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.02 | 0.00 |
August | 6718.28 | 07-AUG-15:04 | 6654.00 | 2744.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.95 | 0.00 |
September | 6241.23 | 21-SEP-14:10 | 798.48 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.65 | 0.00 |
October | 5784.88 | 05-OCT-15:03 | 7984.80 | 3293.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.71 | 0.00 |
November | 4161.86 | 10-NOV-11:33 | 1596.96 | 1646.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.55 |
December | 3426.20 | 16-DEC-11:33 | 2395.44 | 1646.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.84 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 3426.20 | 532.32 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6866.53 | 7984.80 | 3952.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.02 | 54.84 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.374774E+12 | 229770.04 | 03-JAN-19:10 | 0.569803E+12 | 494287.64 | 05-JAN-18:00 |
February | 0.345447E+12 | 234687.03 | 06-FEB-21:00 | 0.462760E+12 | 535667.15 | 08-FEB-18:00 |
March | 0.389568E+12 | 260324.10 | 14-MAR-18:10 | 0.473870E+12 | 488000.27 | 01-MAR-17:00 |
April | 0.435340E+12 | 316825.18 | 19-APR-18:40 | 0.379415E+12 | 360202.17 | 10-APR-20:00 |
May | 0.510264E+12 | 343142.66 | 19-MAY-19:10 | 0.349915E+12 | 312870.31 | 01-MAY-17:49 |
June | 0.557796E+12 | 368704.03 | 05-JUN-19:10 | 0.326648E+12 | 300673.48 | 01-JUN-17:00 |
July | 0.613397E+12 | 386181.05 | 21-JUL-20:00 | 0.330801E+12 | 291243.50 | 03-JUL-17:40 |
August | 0.572535E+12 | 368561.94 | 01-AUG-20:49 | 0.331122E+12 | 292407.18 | 31-AUG-17:30 |
September | 0.519303E+12 | 348444.72 | 19-SEP-18:19 | 0.328295E+12 | 301003.03 | 29-SEP-17:49 |
October | 0.451563E+12 | 350377.53 | 04-OCT-18:19 | 0.366690E+12 | 312901.30 | 31-OCT-17:30 |
November | 0.378960E+12 | 255307.97 | 09-NOV-19:19 | 0.466219E+12 | 480291.68 | 27-NOV-17:00 |
December | 0.377203E+12 | 223581.18 | 15-DEC-19:10 | 0.536580E+12 | 533462.53 | 21-DEC-18:00 |
Annual Sum or Average | 0.552615E+13 | 0.492212E+13 | ||||
Minimum of Months | 0.345447E+12 | 223581.18 | 0.326648E+12 | 291243.50 | ||
Maximum of Months | 0.613397E+12 | 386181.05 | 0.569803E+12 | 535667.15 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.670636E+11 | 0.190555E+11 | 0.140828E+12 | 0.691145E+11 | 0.414872E+11 | 0.614988E+10 | 0.00 | 0.922451E+10 | 0.00 | 0.00 | 0.861493E+10 | 0.804736E+10 | 0.00 |
February | 0.603762E+11 | 0.163016E+11 | 0.127191E+12 | 0.624260E+11 | 0.378532E+11 | 0.596842E+10 | 0.00 | 0.170537E+11 | 0.00 | 0.00 | 0.632989E+10 | 0.727180E+10 | 0.00 |
March | 0.665913E+11 | 0.167531E+11 | 0.140882E+12 | 0.691169E+11 | 0.427373E+11 | 0.705010E+10 | 0.00 | 0.279212E+11 | 0.00 | 0.00 | 0.529575E+10 | 0.804584E+10 | 0.00 |
April | 0.641117E+11 | 0.149098E+11 | 0.136245E+12 | 0.668844E+11 | 0.472592E+11 | 0.712962E+10 | 0.00 | 0.779896E+11 | 0.00 | 0.00 | 0.799192E+10 | 0.779706E+10 | 0.00 |
May | 0.660692E+11 | 0.142879E+11 | 0.140860E+12 | 0.691152E+11 | 0.548606E+11 | 0.758560E+10 | 0.00 | 0.130294E+12 | 0.00 | 0.00 | 0.138953E+11 | 0.804708E+10 | 0.00 |
June | 0.637940E+11 | 0.132663E+11 | 0.136336E+12 | 0.668866E+11 | 0.594592E+11 | 0.768621E+10 | 0.00 | 0.178680E+12 | 0.00 | 0.00 | 0.187737E+11 | 0.778858E+10 | 0.00 |
July | 0.659690E+11 | 0.139548E+11 | 0.140770E+12 | 0.691127E+11 | 0.608417E+11 | 0.809303E+10 | 0.00 | 0.220511E+12 | 0.00 | 0.00 | 0.207517E+11 | 0.805551E+10 | 0.00 |
August | 0.662325E+11 | 0.149098E+11 | 0.140892E+12 | 0.691167E+11 | 0.606137E+11 | 0.794852E+10 | 0.00 | 0.182337E+12 | 0.00 | 0.00 | 0.170908E+11 | 0.804707E+10 | 0.00 |
September | 0.643709E+11 | 0.156353E+11 | 0.136256E+12 | 0.668846E+11 | 0.573637E+11 | 0.752423E+10 | 0.00 | 0.146513E+12 | 0.00 | 0.00 | 0.117959E+11 | 0.779842E+10 | 0.00 |
October | 0.668408E+11 | 0.175157E+11 | 0.140818E+12 | 0.691144E+11 | 0.533123E+11 | 0.737700E+10 | 0.00 | 0.779270E+11 | 0.00 | 0.00 | 0.533066E+10 | 0.804571E+10 | 0.00 |
November | 0.647677E+11 | 0.180857E+11 | 0.136330E+12 | 0.668856E+11 | 0.448351E+11 | 0.630946E+10 | 0.00 | 0.230263E+11 | 0.00 | 0.00 | 0.591997E+10 | 0.778035E+10 | 0.00 |
December | 0.669963E+11 | 0.193368E+11 | 0.140770E+12 | 0.691134E+11 | 0.419895E+11 | 0.597558E+10 | 0.00 | 0.739712E+10 | 0.00 | 0.00 | 0.123920E+11 | 0.805586E+10 | 0.00 |
Annual Sum or Average | 0.783183E+12 | 0.194012E+12 | 0.165818E+13 | 0.813771E+12 | 0.602613E+12 | 0.847976E+11 | 0.00 | 0.109888E+13 | 0.00 | 0.00 | 0.134183E+12 | 0.947806E+11 | 0.00 |
Minimum of Months | 0.603762E+11 | 0.132663E+11 | 0.127191E+12 | 0.624260E+11 | 0.378532E+11 | 0.596842E+10 | 0.00 | 0.739712E+10 | 0.00 | 0.00 | 0.529575E+10 | 0.727180E+10 | 0.00 |
Maximum of Months | 0.670636E+11 | 0.193368E+11 | 0.140892E+12 | 0.691169E+11 | 0.608417E+11 | 0.809303E+10 | 0.00 | 0.220511E+12 | 0.00 | 0.00 | 0.207517E+11 | 0.805586E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.151918E+12 | 0.00 | 0.191063E+12 | 0.00 | 0.226822E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.120761E+12 | 0.00 | 0.204796E+12 | 0.00 | 0.00 |
March | 0.152024E+12 | 0.00 | 0.101260E+12 | 0.00 | 0.220587E+12 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.297401E+11 | 0.00 | 0.202719E+12 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.129238E+10 | 0.00 | 0.196644E+12 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 4905902.19 | 0.00 | 0.179529E+12 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 4233654.98 | 0.00 | 0.178977E+12 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 11471699.83 | 0.00 | 0.179072E+12 | 0.00 | 0.00 |
September | 0.146971E+12 | 0.00 | 0.177374E+10 | 0.00 | 0.179550E+12 | 0.00 | 0.00 |
October | 0.151903E+12 | 0.00 | 0.181078E+11 | 0.00 | 0.196679E+12 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.116393E+12 | 0.00 | 0.202735E+12 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.164263E+12 | 0.00 | 0.220497E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178884E+13 | 0.00 | 0.744674E+12 | 0.00 | 0.238861E+13 | 0.00 | 0.00 |
Minimum of Months | 0.137204E+12 | 0.00 | 4233654.98 | 0.00 | 0.178977E+12 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.191063E+12 | 0.00 | 0.226822E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 64632.59 | 02-JAN-20:10 | 12338.45 | 01-JAN-00:10 | 89171.45 | 02-JAN-07:10 | 49607.07 | 02-JAN-07:19 | 29584.37 | 03-JAN-22:10 | 3355.62 | 06-JAN-10:50 | 0.00 | 01-JAN-00:10 |
February | 64632.59 | 01-FEB-20:10 | 12338.45 | 01-FEB-00:10 | 89171.45 | 01-FEB-07:10 | 49607.07 | 01-FEB-07:19 | 31567.82 | 22-FEB-22:10 | 3334.96 | 01-FEB-10:50 | 0.00 | 01-FEB-00:10 |
March | 64632.59 | 01-MAR-20:10 | 12338.45 | 01-MAR-00:10 | 89171.45 | 01-MAR-07:10 | 49607.07 | 13-MAR-06:19 | 32533.40 | 15-MAR-21:00 | 3342.63 | 25-MAR-06:19 | 0.00 | 01-MAR-00:10 |
April | 64632.59 | 03-APR-19:10 | 12338.45 | 01-APR-00:10 | 89171.45 | 03-APR-06:10 | 49606.97 | 04-APR-06:19 | 38459.84 | 21-APR-21:10 | 3646.81 | 28-APR-18:19 | 0.00 | 01-APR-00:10 |
May | 64632.59 | 01-MAY-19:10 | 12338.45 | 01-MAY-00:10 | 89171.45 | 01-MAY-06:10 | 49606.78 | 03-MAY-06:19 | 42351.08 | 16-MAY-21:10 | 3861.86 | 19-MAY-20:19 | 0.00 | 01-MAY-00:10 |
June | 64632.59 | 01-JUN-19:10 | 12338.45 | 01-JUN-00:10 | 89171.45 | 01-JUN-06:10 | 49605.40 | 28-JUN-06:19 | 48649.82 | 15-JUN-21:10 | 4073.02 | 16-JUN-20:30 | 0.00 | 01-JUN-00:10 |
July | 64632.59 | 03-JUL-19:19 | 12338.45 | 01-JUL-00:10 | 89171.45 | 03-JUL-06:10 | 49605.70 | 18-JUL-06:19 | 47172.79 | 26-JUL-21:10 | 3932.03 | 21-JUL-20:00 | 0.00 | 01-JUL-00:10 |
August | 64632.59 | 01-AUG-19:10 | 12338.45 | 01-AUG-00:10 | 89171.45 | 01-AUG-06:10 | 49606.97 | 14-AUG-06:19 | 50113.58 | 07-AUG-21:10 | 3999.68 | 22-AUG-19:00 | 0.00 | 01-AUG-00:10 |
September | 64632.59 | 01-SEP-19:10 | 12338.45 | 01-SEP-00:10 | 89171.45 | 01-SEP-06:10 | 49607.07 | 25-SEP-06:19 | 48255.76 | 22-SEP-21:10 | 3722.47 | 17-SEP-18:19 | 0.00 | 01-SEP-00:10 |
October | 64632.59 | 02-OCT-19:10 | 12338.45 | 01-OCT-00:10 | 89171.45 | 02-OCT-06:10 | 49607.07 | 02-OCT-06:19 | 46168.37 | 05-OCT-21:00 | 3716.55 | 01-OCT-19:10 | 0.00 | 01-OCT-00:10 |
November | 64632.59 | 01-NOV-19:10 | 12338.45 | 01-NOV-00:10 | 89171.45 | 01-NOV-06:10 | 49607.07 | 01-NOV-06:19 | 39453.63 | 09-NOV-22:00 | 3373.29 | 25-NOV-09:20 | 0.00 | 01-NOV-00:10 |
December | 64632.59 | 01-DEC-20:10 | 12338.45 | 01-DEC-00:10 | 89171.45 | 01-DEC-07:10 | 49607.07 | 11-DEC-07:19 | 29982.70 | 15-DEC-22:10 | 3347.67 | 31-DEC-10:39 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 64632.59 | 12338.45 | 89171.45 | 49605.40 | 29584.37 | 3334.96 | 0.00 | |||||||
Maximum of Months | 64632.59 | 12338.45 | 89171.45 | 49607.07 | 50113.58 | 4073.02 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 34719.87 | 03-JAN-16:10 | 0.00 | 0.00 | 9938.94 | 02-JAN-01:19 | 4751.13 | 25-JAN-07:00 | 0.00 |
February | 58719.65 | 20-FEB-16:10 | 0.00 | 0.00 | 9938.94 | 01-FEB-01:30 | 4751.12 | 22-FEB-07:40 | 0.00 |
March | 62310.78 | 22-MAR-15:09 | 0.00 | 0.00 | 9938.94 | 01-MAR-02:30 | 4751.13 | 14-MAR-06:49 | 0.00 |
April | 95960.34 | 19-APR-18:19 | 0.00 | 0.00 | 9938.94 | 01-APR-12:09 | 4751.13 | 07-APR-06:49 | 0.00 |
May | 119341.60 | 19-MAY-18:19 | 0.00 | 0.00 | 9938.94 | 02-MAY-15:30 | 4751.12 | 10-MAY-18:49 | 0.00 |
June | 140159.16 | 14-JUN-18:10 | 0.00 | 0.00 | 9938.94 | 14-JUN-08:20 | 4751.11 | 06-JUN-18:00 | 0.00 |
July | 158737.09 | 21-JUL-20:00 | 0.00 | 0.00 | 9938.94 | 01-JUL-00:10 | 4751.13 | 05-JUL-06:00 | 0.00 |
August | 148614.92 | 01-AUG-20:49 | 0.00 | 0.00 | 9938.94 | 01-AUG-00:10 | 4751.12 | 07-AUG-06:30 | 0.00 |
September | 116942.06 | 01-SEP-18:19 | 0.00 | 0.00 | 9938.94 | 01-SEP-08:30 | 4751.10 | 12-SEP-18:00 | 0.00 |
October | 121121.28 | 03-OCT-19:30 | 0.00 | 0.00 | 9938.94 | 01-OCT-09:50 | 4751.13 | 03-OCT-06:30 | 0.00 |
November | 62857.06 | 09-NOV-16:10 | 0.00 | 0.00 | 9938.94 | 03-NOV-15:50 | 4751.13 | 30-NOV-07:49 | 0.00 |
December | 18998.72 | 23-DEC-14:00 | 0.00 | 0.00 | 9938.94 | 01-DEC-04:00 | 4751.13 | 28-DEC-07:49 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 18998.72 | 0.00 | 0.00 | 9938.94 | 4751.10 | 0.00 | |||
Maximum of Months | 158737.09 | 0.00 | 0.00 | 9938.94 | 4751.13 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 229770.04 | 03-JAN-19:10 | 57474.69 | 77573.37 | 12338.45 | 28159.60 | 21583.90 | 2659.64 | 0.00 | 23450.73 | 0.00 |
February | 234687.03 | 06-FEB-21:00 | 57474.69 | 88218.55 | 12338.45 | 10998.34 | 26061.03 | 2673.56 | 0.00 | 30485.48 | 0.00 |
March | 260324.10 | 14-MAR-18:10 | 57474.69 | 77573.37 | 12338.45 | 28159.00 | 22092.17 | 2724.90 | 0.00 | 52405.90 | 0.00 |
April | 316825.18 | 19-APR-18:40 | 57474.69 | 77573.37 | 12338.45 | 28169.74 | 30064.16 | 3005.85 | 0.00 | 91133.05 | 0.00 |
May | 343142.66 | 19-MAY-19:10 | 64632.59 | 86439.81 | 12338.45 | 10993.88 | 36431.56 | 3840.30 | 0.00 | 112727.41 | 0.00 |
June | 368704.03 | 05-JUN-19:10 | 64632.59 | 86439.81 | 12338.45 | 10993.43 | 36928.28 | 4042.54 | 0.00 | 137051.15 | 0.00 |
July | 386181.05 | 21-JUL-20:00 | 57474.69 | 88218.55 | 12338.45 | 10998.34 | 38446.51 | 3932.03 | 0.00 | 158737.09 | 0.00 |
August | 368561.94 | 01-AUG-20:49 | 57474.69 | 88218.55 | 12338.45 | 10998.34 | 39421.86 | 3860.00 | 0.00 | 148614.92 | 0.00 |
September | 348444.72 | 19-SEP-18:19 | 57474.69 | 77573.37 | 12338.45 | 28169.74 | 38220.80 | 3564.25 | 0.00 | 114577.85 | 0.00 |
October | 350377.53 | 04-OCT-18:19 | 57474.69 | 77573.37 | 12338.45 | 28169.74 | 33614.99 | 3485.14 | 0.00 | 120618.43 | 0.00 |
November | 255307.97 | 09-NOV-19:19 | 57474.69 | 77573.37 | 12338.45 | 28169.74 | 26157.82 | 2723.15 | 0.00 | 43745.07 | 0.00 |
December | 223581.18 | 15-DEC-19:10 | 57474.69 | 77573.37 | 12338.45 | 28159.60 | 23878.49 | 2688.16 | 0.00 | 14938.46 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 223581.18 | 57474.69 | 77573.37 | 12338.45 | 10993.43 | 21583.90 | 2659.64 | 0.00 | 14938.46 | 0.00 | |
Maximum of Months | 386181.05 | 64632.59 | 88218.55 | 12338.45 | 28169.74 | 39421.86 | 4042.54 | 0.00 | 158737.09 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 215373.04 | 26-JAN-11:50 | 0.00 | 236076.68 | 25-JAN-21:49 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 201338.93 | 08-FEB-18:00 | 0.00 | 236198.06 | 01-FEB-21:49 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 205687.52 | 13-MAR-06:10 | 0.00 | 232128.84 | 01-MAR-21:40 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 191579.41 | 07-APR-06:10 | 0.00 | 222498.37 | 03-APR-20:19 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 85673.37 | 02-MAY-05:00 | 0.00 | 211541.03 | 02-MAY-20:40 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 2641.68 | 29-JUN-08:09 | 0.00 | 198707.11 | 01-JUN-20:30 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 1417.42 | 19-JUL-08:09 | 0.00 | 189759.92 | 03-JUL-20:30 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 3070.22 | 14-AUG-08:09 | 0.00 | 189919.46 | 31-AUG-20:49 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 109917.91 | 30-SEP-05:00 | 0.00 | 198505.59 | 28-SEP-20:30 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 186302.23 | 25-OCT-06:10 | 0.00 | 211581.21 | 30-OCT-20:40 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 204692.72 | 25-NOV-09:20 | 0.00 | 222755.17 | 29-NOV-21:19 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 205833.35 | 27-DEC-11:50 | 0.00 | 230978.12 | 28-DEC-21:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 104248.32 | 0.00 | 1417.42 | 0.00 | 189759.92 | 0.00 | |||
Maximum of Months | 104248.32 | 0.00 | 215373.04 | 0.00 | 236198.06 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.69 | 0.67 | 21.69 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.82 | 0.50 | 21.82 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.75 | 0.83 | 21.75 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 21.91 | 12.17 | 21.91 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 37.33 | 22.26 | 37.33 | 22.26 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 59.83 | 22.20 | 59.83 | 22.20 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 35.17 | 21.92 | 35.17 | 21.92 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 36.33 | 22.01 | 36.33 | 22.01 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 32.33 | 22.06 | 32.33 | 22.06 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 20.17 | 22.02 | 20.17 | 22.02 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 21.99 | 2.17 | 21.99 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.69 | 0.17 | 21.69 |
Annual Sum or Average | 0.00 | 0.00 | 237.67 | 22.08 | 237.67 | 22.08 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.69 | 0.17 | 21.69 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 59.83 | 22.26 | 59.83 | 22.26 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 21.91 | 10.00 | 21.91 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 42.33 | 22.24 | 42.33 | 22.24 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 71.00 | 22.26 | 71.00 | 22.26 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 43.17 | 21.94 | 43.17 | 21.94 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 36.83 | 21.97 | 36.83 | 21.97 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 24.50 | 21.93 | 24.50 | 21.93 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 21.89 | 4.67 | 21.89 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 22.01 | 0.17 | 22.01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 232.67 | 22.09 | 232.67 | 22.09 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 71.00 | 22.26 | 71.00 | 22.26 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 21.77 | 4.00 | 21.77 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 16.00 | 21.84 | 16.00 | 21.84 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 30.50 | 21.90 | 30.50 | 21.90 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 18.33 | 21.86 | 18.33 | 21.86 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 14.17 | 21.81 | 14.17 | 21.81 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 21.75 | 12.33 | 21.75 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 21.75 | 5.17 | 21.75 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.74 | 0.17 | 21.74 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 100.67 | 21.84 | 100.67 | 21.84 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 30.50 | 21.90 | 30.50 | 21.90 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.69 | 0.17 | 21.69 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.77 | 0.67 | 21.77 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.75 | 1.50 | 21.75 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 21.86 | 7.00 | 21.86 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 25.00 | 21.96 | 25.00 | 21.96 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 50.33 | 22.10 | 50.33 | 22.10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 27.33 | 21.92 | 27.33 | 21.92 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 22.33 | 21.93 | 22.33 | 21.93 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 19.50 | 21.91 | 19.50 | 21.91 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 21.85 | 7.33 | 21.85 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 21.89 | 2.33 | 21.89 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.68 | 0.17 | 21.68 |
Annual Sum or Average | 0.00 | 0.00 | 163.67 | 21.97 | 163.67 | 21.97 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.68 | 0.17 | 21.68 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 50.33 | 22.10 | 50.33 | 22.10 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.71 | 0.17 | 21.71 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.70 | 0.83 | 21.70 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 22.17 | 9.83 | 22.17 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 36.17 | 22.26 | 36.17 | 22.26 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 80.17 | 22.28 | 80.17 | 22.28 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 49.50 | 22.21 | 49.50 | 22.21 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 38.67 | 22.22 | 38.67 | 22.22 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 26.17 | 22.27 | 26.17 | 22.27 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 22.14 | 4.33 | 22.14 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 22.12 | 0.33 | 22.12 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 246.17 | 22.24 | 246.17 | 22.24 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 80.17 | 22.28 | 80.17 | 22.28 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.75 | 0.17 | 21.75 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.88 | 0.50 | 21.88 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.75 | 0.83 | 21.75 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 16.33 | 21.99 | 16.33 | 21.99 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 42.00 | 22.33 | 42.00 | 22.33 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 68.83 | 22.37 | 68.83 | 22.37 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 44.17 | 22.01 | 44.17 | 22.01 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 42.83 | 22.09 | 42.83 | 22.09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 38.33 | 22.10 | 38.33 | 22.10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 22.00 | 22.04 | 22.00 | 22.04 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 21.98 | 2.33 | 21.98 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 278.33 | 22.17 | 278.33 | 22.17 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 68.83 | 22.37 | 68.83 | 22.37 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 14.33 | 21.98 | 14.33 | 21.98 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 46.50 | 22.32 | 46.50 | 22.32 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 76.50 | 22.43 | 76.50 | 22.43 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 50.67 | 22.05 | 50.67 | 22.05 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 44.00 | 22.05 | 44.00 | 22.05 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 26.33 | 22.00 | 26.33 | 22.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 21.90 | 4.83 | 21.90 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.96 | 0.17 | 21.96 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 263.33 | 22.19 | 263.33 | 22.19 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 76.50 | 22.43 | 76.50 | 22.43 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 21.98 | 6.33 | 21.98 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 21.92 | 4.17 | 21.92 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 21.87 | 3.33 | 21.87 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 21.96 | 9.17 | 21.96 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 21.88 | 11.00 | 21.88 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 27.00 | 21.97 | 27.00 | 21.97 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 21.89 | 12.17 | 21.89 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 14.17 | 21.92 | 14.17 | 21.92 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 23.67 | 22.01 | 23.67 | 22.01 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 30.67 | 22.15 | 30.67 | 22.15 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 21.98 | 12.50 | 21.98 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 21.96 | 4.67 | 21.96 |
Annual Sum or Average | 0.00 | 0.00 | 158.83 | 21.99 | 158.83 | 21.99 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 21.87 | 3.33 | 21.87 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 30.67 | 22.15 | 30.67 | 22.15 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 704.83 | 23.75 | 0.00 | 23.75 | 0.00 | 23.75 |
February | 672.00 | 22.96 | 0.00 | 22.96 | 0.00 | 22.96 |
March | 744.00 | 22.22 | 0.00 | 22.22 | 0.00 | 22.22 |
April | 720.00 | 22.32 | 0.00 | 22.32 | 0.00 | 22.32 |
May | 744.00 | 22.62 | 10.67 | 22.62 | 10.67 | 22.63 |
June | 708.17 | 22.92 | 64.33 | 22.93 | 64.33 | 22.95 |
July | 422.00 | 23.77 | 506.00 | 23.82 | 378.17 | 23.83 |
August | 236.17 | 23.98 | 606.33 | 23.95 | 231.50 | 23.95 |
September | 215.83 | 24.00 | 495.17 | 23.99 | 215.33 | 23.99 |
October | 116.67 | 23.99 | 299.83 | 23.99 | 48.00 | 23.99 |
November | 456.33 | 23.99 | 15.00 | 23.99 | 0.00 | 23.99 |
December | 613.50 | 23.94 | 0.00 | 23.94 | 0.00 | 23.94 |
Annual Sum or Average | 6353.50 | 23.16 | 1997.33 | 23.34 | 948.00 | 23.39 |
Minimum of Months | 116.67 | 22.22 | 0.00 | 22.22 | 0.00 | 22.22 |
Maximum of Months | 744.00 | 24.00 | 606.33 | 23.99 | 378.17 | 23.99 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 633.50 | 21.72 | 37.67 | 21.79 | 13.33 | 21.77 |
February | 572.00 | 21.87 | 14.67 | 21.88 | 9.17 | 21.87 |
March | 663.83 | 22.00 | 16.67 | 21.98 | 16.67 | 21.95 |
April | 533.83 | 22.54 | 35.17 | 22.63 | 0.17 | 22.63 |
May | 363.67 | 22.88 | 211.83 | 23.24 | 9.50 | 23.24 |
June | 117.17 | 23.30 | 519.83 | 23.75 | 48.83 | 23.73 |
July | 353.33 | 23.61 | 739.00 | 23.72 | 352.67 | 23.69 |
August | 242.50 | 23.41 | 668.00 | 23.66 | 213.17 | 23.63 |
September | 290.17 | 23.28 | 581.33 | 23.61 | 208.83 | 23.58 |
October | 382.00 | 22.58 | 297.83 | 23.14 | 47.33 | 23.16 |
November | 531.50 | 21.99 | 78.17 | 22.19 | 12.33 | 22.16 |
December | 647.33 | 21.63 | 45.17 | 21.59 | 43.67 | 21.56 |
Annual Sum or Average | 5330.83 | 22.33 | 3245.33 | 22.86 | 975.67 | 22.90 |
Minimum of Months | 117.17 | 21.63 | 14.67 | 21.59 | 0.17 | 21.56 |
Maximum of Months | 663.83 | 23.61 | 739.00 | 23.75 | 352.67 | 23.73 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 732.50 | 22.90 | 0.00 | 22.90 | 0.00 | 22.90 |
February | 665.67 | 23.03 | 0.00 | 23.03 | 0.00 | 23.03 |
March | 738.67 | 23.11 | 0.00 | 23.11 | 0.00 | 23.11 |
April | 554.17 | 23.42 | 13.17 | 23.43 | 0.00 | 23.43 |
May | 283.33 | 23.54 | 176.33 | 23.69 | 22.17 | 23.70 |
June | 137.17 | 23.84 | 426.67 | 23.91 | 73.67 | 23.92 |
July | 404.50 | 23.95 | 729.83 | 23.92 | 404.50 | 23.93 |
August | 276.67 | 23.90 | 676.50 | 23.90 | 275.00 | 23.90 |
September | 274.33 | 23.91 | 535.17 | 23.91 | 252.33 | 23.92 |
October | 275.00 | 23.49 | 240.50 | 23.66 | 81.00 | 23.68 |
November | 627.17 | 23.21 | 4.17 | 23.22 | 0.00 | 23.22 |
December | 744.00 | 22.79 | 0.00 | 22.79 | 0.00 | 22.79 |
Annual Sum or Average | 5713.17 | 23.27 | 2802.33 | 23.48 | 1108.67 | 23.53 |
Minimum of Months | 137.17 | 22.79 | 0.00 | 22.79 | 0.00 | 22.79 |
Maximum of Months | 744.00 | 23.95 | 729.83 | 23.92 | 404.50 | 23.93 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.65 | 12.33 | 21.64 | 12.33 | 21.63 |
February | 672.00 | 21.83 | 7.17 | 21.82 | 7.17 | 21.81 |
March | 744.00 | 22.06 | 2.83 | 22.05 | 2.83 | 22.05 |
April | 719.67 | 22.87 | 0.00 | 22.87 | 0.00 | 22.87 |
May | 522.33 | 23.45 | 46.50 | 23.49 | 0.83 | 23.49 |
June | 136.00 | 23.88 | 249.17 | 23.93 | 12.33 | 23.92 |
July | 239.17 | 23.94 | 719.83 | 23.94 | 238.17 | 23.94 |
August | 136.50 | 23.78 | 508.83 | 23.88 | 125.50 | 23.87 |
September | 325.67 | 23.63 | 379.00 | 23.75 | 141.67 | 23.76 |
October | 633.67 | 23.04 | 58.00 | 23.11 | 11.17 | 23.12 |
November | 720.00 | 22.25 | 0.00 | 22.25 | 0.00 | 22.25 |
December | 744.00 | 21.52 | 7.83 | 21.51 | 7.83 | 21.51 |
Annual Sum or Average | 6337.00 | 22.48 | 1991.50 | 22.81 | 559.83 | 22.87 |
Minimum of Months | 136.00 | 21.52 | 0.00 | 21.51 | 0.00 | 21.51 |
Maximum of Months | 744.00 | 23.94 | 719.83 | 23.94 | 238.17 | 23.94 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.36 | 23.17 | 21.35 | 23.17 | 21.34 |
February | 672.00 | 21.55 | 16.17 | 21.54 | 16.17 | 21.53 |
March | 744.00 | 21.77 | 7.50 | 21.77 | 7.50 | 21.76 |
April | 720.00 | 22.61 | 0.00 | 22.61 | 0.00 | 22.61 |
May | 605.00 | 23.28 | 16.33 | 23.29 | 1.67 | 23.29 |
June | 157.33 | 23.76 | 192.67 | 23.84 | 15.83 | 23.83 |
July | 271.50 | 23.85 | 711.33 | 23.87 | 271.50 | 23.87 |
August | 183.50 | 23.63 | 456.83 | 23.76 | 139.67 | 23.75 |
September | 387.33 | 23.42 | 302.83 | 23.54 | 158.83 | 23.55 |
October | 660.50 | 22.79 | 36.83 | 22.83 | 14.33 | 22.84 |
November | 720.00 | 21.95 | 0.00 | 21.95 | 0.00 | 21.95 |
December | 744.00 | 21.26 | 26.50 | 21.25 | 26.50 | 21.24 |
Annual Sum or Average | 6609.17 | 22.28 | 1790.17 | 22.58 | 675.17 | 22.65 |
Minimum of Months | 157.33 | 21.26 | 0.00 | 21.25 | 0.00 | 21.24 |
Maximum of Months | 744.00 | 23.85 | 711.33 | 23.87 | 271.50 | 23.87 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 216.17 | 23.30 | 632.33 | 23.55 | 157.17 | 23.62 |
February | 190.33 | 23.37 | 569.00 | 23.59 | 142.50 | 23.65 |
March | 210.33 | 23.39 | 628.83 | 23.59 | 158.00 | 23.66 |
April | 224.83 | 23.78 | 638.67 | 23.67 | 203.50 | 23.74 |
May | 296.00 | 23.95 | 696.00 | 23.69 | 291.33 | 23.75 |
June | 360.33 | 23.92 | 708.00 | 23.64 | 360.33 | 23.71 |
July | 565.83 | 23.64 | 744.00 | 23.55 | 565.83 | 23.58 |
August | 478.67 | 23.75 | 744.00 | 23.58 | 478.67 | 23.62 |
September | 451.67 | 23.75 | 712.50 | 23.58 | 451.67 | 23.63 |
October | 327.50 | 23.94 | 706.67 | 23.66 | 325.83 | 23.73 |
November | 214.17 | 23.50 | 621.83 | 23.62 | 171.50 | 23.68 |
December | 210.50 | 23.21 | 618.67 | 23.54 | 145.50 | 23.61 |
Annual Sum or Average | 3746.33 | 23.67 | 8020.50 | 23.60 | 3451.83 | 23.66 |
Minimum of Months | 190.33 | 23.21 | 569.00 | 23.54 | 142.50 | 23.58 |
Maximum of Months | 565.83 | 23.95 | 744.00 | 23.69 | 565.83 | 23.75 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 464.17 | 23.04 | 91.00 | 23.20 | 0.00 | 23.20 |
February | 397.33 | 23.18 | 66.67 | 23.30 | 1.67 | 23.30 |
March | 430.17 | 23.15 | 57.33 | 23.24 | 0.83 | 23.25 |
April | 246.67 | 23.23 | 186.83 | 23.54 | 0.00 | 23.54 |
May | 185.83 | 23.49 | 426.17 | 23.75 | 90.17 | 23.76 |
June | 192.67 | 23.85 | 639.50 | 23.86 | 183.83 | 23.86 |
July | 604.50 | 23.88 | 743.67 | 23.87 | 604.50 | 23.87 |
August | 450.50 | 23.84 | 740.67 | 23.85 | 450.17 | 23.85 |
September | 381.50 | 23.91 | 689.00 | 23.93 | 377.33 | 23.93 |
October | 223.33 | 23.61 | 560.50 | 23.84 | 170.50 | 23.85 |
November | 299.33 | 23.03 | 209.50 | 23.42 | 2.33 | 23.43 |
December | 528.33 | 23.02 | 74.67 | 23.14 | 0.00 | 23.14 |
Annual Sum or Average | 4404.33 | 23.43 | 4485.50 | 23.67 | 1881.33 | 23.70 |
Minimum of Months | 185.83 | 23.02 | 57.33 | 23.14 | 0.00 | 23.14 |
Maximum of Months | 604.50 | 23.91 | 743.67 | 23.93 | 604.50 | 23.93 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 604.33 | 23.33 | 0.00 | 23.33 | 0.00 | 23.33 |
February | 576.00 | 23.44 | 5.50 | 23.44 | 0.00 | 23.44 |
March | 628.33 | 23.39 | 10.17 | 23.40 | 0.00 | 23.40 |
April | 418.17 | 23.46 | 57.67 | 23.52 | 0.00 | 23.52 |
May | 230.00 | 23.51 | 247.17 | 23.70 | 64.50 | 23.72 |
June | 175.33 | 23.83 | 501.50 | 23.88 | 145.33 | 23.89 |
July | 552.17 | 23.91 | 739.33 | 23.88 | 552.17 | 23.89 |
August | 422.17 | 23.89 | 731.83 | 23.87 | 422.17 | 23.88 |
September | 368.33 | 23.93 | 645.17 | 23.93 | 368.33 | 23.93 |
October | 194.83 | 23.75 | 416.50 | 23.87 | 144.83 | 23.88 |
November | 390.00 | 23.45 | 44.83 | 23.51 | 0.00 | 23.51 |
December | 683.83 | 23.32 | 0.00 | 23.32 | 0.00 | 23.32 |
Annual Sum or Average | 5243.50 | 23.55 | 3399.67 | 23.69 | 1697.33 | 23.72 |
Minimum of Months | 175.33 | 23.32 | 0.00 | 23.32 | 0.00 | 23.32 |
Maximum of Months | 683.83 | 23.93 | 739.33 | 23.93 | 552.17 | 23.93 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 742.17 | 21.37 | 73.67 | 21.33 | 73.67 | 21.30 |
February | 670.50 | 21.47 | 41.17 | 21.44 | 41.17 | 21.42 |
March | 743.50 | 21.55 | 15.33 | 21.54 | 15.33 | 21.53 |
April | 690.50 | 21.62 | 1.17 | 21.63 | 0.00 | 21.63 |
May | 645.83 | 21.57 | 13.50 | 21.61 | 0.00 | 21.61 |
June | 566.83 | 21.47 | 46.17 | 21.61 | 0.00 | 21.61 |
July | 572.67 | 21.36 | 74.17 | 21.58 | 5.17 | 21.59 |
August | 576.00 | 21.38 | 66.50 | 21.58 | 3.50 | 21.58 |
September | 558.67 | 21.37 | 74.00 | 21.59 | 3.83 | 21.60 |
October | 661.17 | 21.52 | 34.33 | 21.59 | 11.33 | 21.60 |
November | 705.00 | 21.49 | 25.00 | 21.47 | 24.50 | 21.44 |
December | 744.00 | 21.34 | 140.83 | 21.28 | 140.83 | 21.23 |
Annual Sum or Average | 7876.83 | 21.46 | 605.83 | 21.51 | 319.33 | 21.49 |
Minimum of Months | 558.67 | 21.34 | 1.17 | 21.28 | 0.00 | 21.23 |
Maximum of Months | 744.00 | 21.62 | 140.83 | 21.63 | 140.83 | 21.63 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.05 | 211.83 | 20.97 | 211.83 | 20.93 |
February | 671.83 | 21.30 | 151.83 | 21.22 | 151.83 | 21.17 |
March | 732.50 | 21.61 | 44.50 | 21.57 | 43.67 | 21.53 |
April | 681.33 | 21.87 | 8.67 | 21.92 | 0.00 | 21.92 |
May | 612.83 | 21.81 | 31.67 | 21.91 | 3.83 | 21.92 |
June | 502.17 | 21.58 | 89.83 | 21.90 | 8.00 | 21.93 |
July | 541.17 | 21.63 | 141.83 | 22.04 | 60.00 | 22.19 |
August | 558.00 | 21.68 | 113.17 | 22.00 | 47.67 | 22.10 |
September | 568.50 | 21.83 | 113.67 | 22.10 | 66.17 | 22.21 |
October | 654.83 | 21.86 | 56.33 | 21.98 | 31.33 | 22.01 |
November | 716.67 | 21.42 | 72.83 | 21.37 | 71.83 | 21.32 |
December | 744.00 | 20.97 | 358.83 | 20.90 | 358.83 | 20.86 |
Annual Sum or Average | 7727.83 | 21.53 | 1395.00 | 21.59 | 1055.00 | 21.56 |
Minimum of Months | 502.17 | 20.97 | 8.67 | 20.90 | 0.00 | 20.86 |
Maximum of Months | 744.00 | 21.87 | 358.83 | 22.10 | 358.83 | 22.21 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.12 | 99.50 | 21.09 | 99.50 | 21.07 |
February | 672.00 | 21.25 | 69.83 | 21.22 | 69.83 | 21.19 |
March | 744.00 | 21.46 | 8.00 | 21.45 | 8.00 | 21.45 |
April | 720.00 | 21.77 | 0.00 | 21.77 | 0.00 | 21.77 |
May | 742.00 | 21.92 | 0.00 | 21.92 | 0.00 | 21.92 |
June | 708.67 | 21.94 | 1.17 | 21.94 | 0.17 | 21.94 |
July | 734.50 | 21.94 | 49.00 | 22.03 | 45.67 | 22.10 |
August | 738.17 | 21.94 | 27.83 | 21.99 | 27.67 | 22.03 |
September | 718.83 | 21.98 | 46.33 | 22.04 | 46.33 | 22.10 |
October | 743.17 | 21.82 | 8.83 | 21.83 | 8.83 | 21.85 |
November | 720.00 | 21.28 | 15.67 | 21.27 | 15.67 | 21.26 |
December | 744.00 | 21.08 | 131.83 | 21.04 | 131.83 | 21.01 |
Annual Sum or Average | 8729.33 | 21.63 | 458.00 | 21.62 | 453.50 | 21.62 |
Minimum of Months | 672.00 | 21.08 | 0.00 | 21.04 | 0.00 | 21.01 |
Maximum of Months | 744.00 | 21.98 | 131.83 | 22.04 | 131.83 | 22.10 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.43 | 76.33 | 21.39 | 76.33 | 21.35 |
February | 672.00 | 21.56 | 35.83 | 21.54 | 35.83 | 21.52 |
March | 744.00 | 21.63 | 18.50 | 21.62 | 18.50 | 21.61 |
April | 696.50 | 21.69 | 0.00 | 21.69 | 0.00 | 21.69 |
May | 648.50 | 21.56 | 1.83 | 21.57 | 0.00 | 21.57 |
June | 538.83 | 21.36 | 27.17 | 21.45 | 0.00 | 21.45 |
July | 545.83 | 21.25 | 53.50 | 21.43 | 3.00 | 21.44 |
August | 561.50 | 21.29 | 39.50 | 21.41 | 3.17 | 21.41 |
September | 541.17 | 21.28 | 47.50 | 21.44 | 1.00 | 21.45 |
October | 657.17 | 21.50 | 24.67 | 21.52 | 20.00 | 21.53 |
November | 716.50 | 21.56 | 28.33 | 21.53 | 28.33 | 21.50 |
December | 744.00 | 21.38 | 147.17 | 21.32 | 147.17 | 21.27 |
Annual Sum or Average | 7810.00 | 21.47 | 500.33 | 21.49 | 333.33 | 21.47 |
Minimum of Months | 538.83 | 21.25 | 0.00 | 21.32 | 0.00 | 21.27 |
Maximum of Months | 744.00 | 21.69 | 147.17 | 21.69 | 147.17 | 21.69 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.03 | 207.50 | 20.98 | 207.50 | 20.95 |
February | 672.00 | 21.32 | 131.50 | 21.27 | 131.50 | 21.23 |
March | 744.00 | 21.67 | 51.33 | 21.63 | 51.33 | 21.59 |
April | 676.33 | 21.94 | 15.67 | 22.02 | 0.00 | 22.02 |
May | 570.67 | 21.75 | 61.33 | 22.11 | 6.67 | 22.15 |
June | 465.67 | 21.55 | 109.00 | 22.13 | 15.00 | 22.24 |
July | 522.67 | 21.72 | 151.83 | 22.26 | 60.33 | 22.48 |
August | 521.17 | 21.66 | 117.17 | 22.14 | 49.50 | 22.31 |
September | 539.67 | 21.92 | 105.33 | 22.34 | 68.17 | 22.55 |
October | 697.67 | 21.93 | 52.83 | 21.98 | 41.50 | 21.99 |
November | 717.67 | 21.38 | 82.50 | 21.33 | 81.67 | 21.28 |
December | 744.00 | 20.96 | 365.67 | 20.91 | 365.67 | 20.88 |
Annual Sum or Average | 7615.50 | 21.55 | 1451.67 | 21.67 | 1078.83 | 21.67 |
Minimum of Months | 465.67 | 20.96 | 15.67 | 20.91 | 0.00 | 20.88 |
Maximum of Months | 744.00 | 21.94 | 365.67 | 22.34 | 365.67 | 22.55 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.45 | 15.83 | 21.44 | 15.83 | 21.43 |
February | 672.00 | 21.73 | 0.00 | 21.73 | 0.00 | 21.73 |
March | 744.00 | 22.01 | 0.00 | 22.01 | 0.00 | 22.01 |
April | 720.00 | 22.79 | 0.00 | 22.79 | 0.00 | 22.79 |
May | 623.33 | 23.36 | 40.50 | 23.38 | 30.00 | 23.39 |
June | 253.67 | 23.77 | 217.67 | 23.81 | 82.67 | 23.81 |
July | 458.33 | 23.78 | 655.83 | 23.80 | 458.17 | 23.79 |
August | 403.83 | 23.66 | 495.83 | 23.71 | 326.67 | 23.70 |
September | 486.67 | 23.62 | 409.67 | 23.67 | 290.00 | 23.68 |
October | 687.50 | 23.03 | 99.83 | 23.07 | 79.50 | 23.09 |
November | 720.00 | 22.21 | 0.00 | 22.21 | 0.00 | 22.21 |
December | 744.00 | 21.27 | 13.67 | 21.27 | 13.67 | 21.26 |
Annual Sum or Average | 7257.33 | 22.53 | 1948.83 | 22.78 | 1296.50 | 22.89 |
Minimum of Months | 253.67 | 21.27 | 0.00 | 21.27 | 0.00 | 21.26 |
Maximum of Months | 744.00 | 23.78 | 655.83 | 23.81 | 458.17 | 23.81 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 740.83 | 21.28 | 168.83 | 21.19 | 168.83 | 21.13 |
February | 668.50 | 21.39 | 144.33 | 21.32 | 144.33 | 21.28 |
March | 741.83 | 21.49 | 91.33 | 21.43 | 91.33 | 21.39 |
April | 674.33 | 21.57 | 29.33 | 21.58 | 19.83 | 21.57 |
May | 617.17 | 21.51 | 40.83 | 21.62 | 1.33 | 21.62 |
June | 526.50 | 21.40 | 89.33 | 21.67 | 0.83 | 21.67 |
July | 543.50 | 21.32 | 125.50 | 21.66 | 14.17 | 21.68 |
August | 552.50 | 21.34 | 120.50 | 21.64 | 16.83 | 21.64 |
September | 537.67 | 21.33 | 133.33 | 21.65 | 27.17 | 21.67 |
October | 649.50 | 21.46 | 85.17 | 21.56 | 47.50 | 21.56 |
November | 701.50 | 21.41 | 116.17 | 21.34 | 114.83 | 21.28 |
December | 744.00 | 21.25 | 281.00 | 21.15 | 281.00 | 21.10 |
Annual Sum or Average | 7697.83 | 21.40 | 1425.67 | 21.46 | 928.00 | 21.42 |
Minimum of Months | 526.50 | 21.25 | 29.33 | 21.15 | 0.83 | 21.10 |
Maximum of Months | 744.00 | 21.57 | 281.00 | 21.67 | 281.00 | 21.68 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.91 | 392.17 | 20.83 | 392.17 | 20.79 |
February | 670.00 | 21.18 | 296.67 | 21.07 | 296.67 | 21.01 |
March | 730.50 | 21.53 | 135.33 | 21.44 | 133.67 | 21.36 |
April | 669.83 | 21.82 | 36.33 | 21.86 | 19.67 | 21.84 |
May | 592.67 | 21.76 | 57.50 | 21.91 | 6.83 | 21.93 |
June | 477.83 | 21.54 | 132.50 | 21.96 | 11.83 | 21.99 |
July | 519.50 | 21.62 | 191.67 | 22.09 | 69.33 | 22.22 |
August | 540.83 | 21.65 | 162.00 | 22.02 | 63.33 | 22.13 |
September | 551.33 | 21.75 | 164.50 | 22.07 | 84.50 | 22.15 |
October | 648.33 | 21.78 | 117.17 | 21.93 | 78.83 | 21.94 |
November | 716.83 | 21.31 | 206.17 | 21.21 | 204.83 | 21.14 |
December | 744.00 | 20.84 | 561.17 | 20.79 | 561.17 | 20.77 |
Annual Sum or Average | 7605.67 | 21.44 | 2453.17 | 21.49 | 1922.83 | 21.43 |
Minimum of Months | 477.83 | 20.84 | 36.33 | 20.79 | 6.83 | 20.77 |
Maximum of Months | 744.00 | 21.82 | 561.17 | 22.09 | 561.17 | 22.22 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 697.50 | 21.48 | 23.67 | 21.46 | 23.67 | 21.44 |
February | 638.00 | 21.55 | 14.17 | 21.54 | 14.17 | 21.53 |
March | 738.17 | 21.62 | 11.83 | 21.61 | 11.83 | 21.60 |
April | 693.33 | 21.63 | 0.00 | 21.63 | 0.00 | 21.63 |
May | 699.00 | 21.62 | 0.00 | 21.62 | 0.00 | 21.62 |
June | 619.83 | 21.53 | 0.00 | 21.53 | 0.00 | 21.53 |
July | 606.83 | 21.40 | 16.67 | 21.43 | 13.33 | 21.45 |
August | 604.67 | 21.39 | 35.33 | 21.48 | 8.17 | 21.48 |
September | 562.83 | 21.34 | 95.50 | 21.62 | 10.17 | 21.63 |
October | 616.00 | 21.43 | 71.33 | 21.60 | 8.83 | 21.61 |
November | 631.83 | 21.40 | 18.17 | 21.41 | 12.17 | 21.40 |
December | 710.17 | 21.52 | 33.83 | 21.49 | 33.83 | 21.47 |
Annual Sum or Average | 7818.17 | 21.50 | 320.50 | 21.54 | 136.17 | 21.53 |
Minimum of Months | 562.83 | 21.34 | 0.00 | 21.41 | 0.00 | 21.40 |
Maximum of Months | 738.17 | 21.63 | 95.50 | 21.63 | 33.83 | 21.63 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 380.67 | 23.49 | 28.33 | 23.52 | 0.00 | 23.52 |
February | 299.00 | 23.57 | 38.17 | 23.62 | 0.00 | 23.62 |
March | 201.50 | 23.53 | 22.33 | 23.58 | 0.00 | 23.58 |
April | 33.33 | 23.61 | 218.83 | 23.94 | 0.00 | 23.94 |
May | 73.33 | 23.99 | 538.17 | 23.99 | 72.83 | 23.99 |
June | 157.33 | 24.00 | 679.33 | 23.99 | 157.33 | 24.00 |
July | 574.50 | 24.00 | 744.00 | 24.00 | 574.50 | 24.00 |
August | 441.67 | 23.99 | 744.00 | 23.99 | 441.67 | 23.99 |
September | 388.83 | 24.00 | 712.83 | 23.99 | 388.83 | 23.99 |
October | 173.17 | 23.96 | 589.83 | 23.97 | 165.83 | 23.97 |
November | 219.67 | 23.53 | 98.50 | 23.67 | 0.00 | 23.67 |
December | 456.83 | 23.50 | 0.00 | 23.50 | 0.00 | 23.50 |
Annual Sum or Average | 3399.83 | 23.77 | 4414.33 | 23.89 | 1801.00 | 23.91 |
Minimum of Months | 33.33 | 23.49 | 0.00 | 23.50 | 0.00 | 23.50 |
Maximum of Months | 574.50 | 24.00 | 744.00 | 24.00 | 574.50 | 24.00 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 154.17 | 23.50 | 100.83 | 23.69 | 0.00 | 23.69 |
February | 77.83 | 23.50 | 61.33 | 23.71 | 0.00 | 23.71 |
March | 58.83 | 23.53 | 45.50 | 23.73 | 0.00 | 23.73 |
April | 6.83 | 23.61 | 308.17 | 23.98 | 0.00 | 23.98 |
May | 64.83 | 24.00 | 592.50 | 24.00 | 64.83 | 24.00 |
June | 143.67 | 24.00 | 690.83 | 24.00 | 143.67 | 24.00 |
July | 542.33 | 24.00 | 744.00 | 24.00 | 542.33 | 24.00 |
August | 417.00 | 24.00 | 744.00 | 24.00 | 417.00 | 24.00 |
September | 374.17 | 24.00 | 720.00 | 23.99 | 374.17 | 24.00 |
October | 152.33 | 23.99 | 651.00 | 23.99 | 152.17 | 23.99 |
November | 57.50 | 23.47 | 153.67 | 23.83 | 0.00 | 23.83 |
December | 204.17 | 23.48 | 23.50 | 23.53 | 0.00 | 23.53 |
Annual Sum or Average | 2253.67 | 23.87 | 4835.33 | 23.95 | 1694.17 | 23.96 |
Minimum of Months | 6.83 | 23.47 | 23.50 | 23.53 | 0.00 | 23.53 |
Maximum of Months | 542.33 | 24.00 | 744.00 | 24.00 | 542.33 | 24.00 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 487.50 | 23.99 | 704.50 | 23.95 | 487.33 | 23.96 |
February | 449.00 | 23.99 | 638.17 | 23.96 | 448.67 | 23.97 |
March | 499.00 | 23.99 | 720.00 | 23.97 | 498.67 | 23.97 |
April | 508.50 | 23.99 | 716.00 | 23.98 | 508.50 | 23.98 |
May | 551.67 | 23.99 | 744.00 | 23.99 | 551.67 | 23.99 |
June | 593.00 | 23.99 | 720.00 | 23.99 | 593.00 | 23.99 |
July | 740.50 | 23.99 | 744.00 | 23.99 | 740.50 | 23.99 |
August | 681.00 | 23.99 | 744.00 | 23.99 | 681.00 | 23.99 |
September | 646.83 | 23.99 | 720.00 | 23.99 | 646.83 | 23.99 |
October | 564.17 | 23.99 | 744.00 | 23.98 | 564.17 | 23.98 |
November | 490.33 | 23.99 | 695.00 | 23.96 | 490.33 | 23.97 |
December | 479.83 | 23.98 | 682.50 | 23.95 | 478.50 | 23.96 |
Annual Sum or Average | 6691.33 | 23.99 | 8572.17 | 23.98 | 6689.17 | 23.98 |
Minimum of Months | 449.00 | 23.98 | 638.17 | 23.95 | 448.67 | 23.96 |
Maximum of Months | 740.50 | 23.99 | 744.00 | 23.99 | 740.50 | 23.99 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.31 | 20.17 | 21.30 | 20.17 | 21.29 |
February | 672.00 | 21.57 | 1.83 | 21.57 | 1.83 | 21.57 |
March | 744.00 | 21.83 | 6.83 | 21.83 | 6.83 | 21.82 |
April | 686.50 | 22.79 | 1.17 | 22.79 | 0.00 | 22.79 |
May | 388.33 | 23.24 | 120.17 | 23.39 | 7.17 | 23.39 |
June | 92.83 | 23.67 | 398.50 | 23.88 | 36.67 | 23.87 |
July | 333.00 | 23.81 | 741.83 | 23.87 | 333.00 | 23.86 |
August | 211.50 | 23.66 | 613.67 | 23.80 | 193.17 | 23.77 |
September | 336.33 | 23.42 | 476.17 | 23.63 | 199.33 | 23.62 |
October | 605.17 | 22.79 | 107.67 | 22.92 | 39.67 | 22.94 |
November | 720.00 | 21.88 | 0.00 | 21.88 | 0.00 | 21.88 |
December | 744.00 | 21.20 | 34.67 | 21.19 | 34.67 | 21.19 |
Annual Sum or Average | 6277.67 | 22.23 | 2522.67 | 22.68 | 872.50 | 22.75 |
Minimum of Months | 92.83 | 21.20 | 0.00 | 21.19 | 0.00 | 21.19 |
Maximum of Months | 744.00 | 23.81 | 741.83 | 23.88 | 333.00 | 23.87 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.75600 | 23.77050 | 0.16260 | 5.65990 |
February | 672.00000 | 22.96261 | 21.96856 | -0.0531 | 5.24401 |
March | 744.00000 | 22.22008 | 21.24791 | -0.2419 | 6.36954 |
April | 720.00000 | 22.32017 | 25.15534 | -0.1919 | 5.95425 |
May | 744.00000 | 22.62123 | 35.98878 | -1.0970 | 30.66455 |
June | 720.00000 | 22.92883 | 44.99795 | -0.9259 | 23.48201 |
July | 744.00000 | 23.71118 | 57.28691 | -0.5529 | 11.63452 |
August | 744.00000 | 23.91873 | 52.73596 | -0.4910 | 10.12559 |
September | 720.00000 | 23.98843 | 49.07747 | -0.4749 | 9.82938 |
October | 744.00000 | 23.99270 | 39.70579 | 0.36153 | 7.85550 |
November | 720.00000 | 23.99168 | 23.68214 | 0.24515 | 6.31483 |
December | 744.00000 | 23.95118 | 21.22283 | 0.20742 | 5.95046 |
Annual Sum or Average | 8760.00000 | 23.36748 | 34.83076 | -0.2551 | 10.79536 |
Minimum of Months | 672.00000 | 22.22008 | 21.22283 | -1.0970 | 5.24401 |
Maximum of Months | 744.00000 | 23.99270 | 57.28691 | 0.36153 | 30.66455 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.05310 | 25.18661 | -0.1924 | 7.68202 |
February | 672.00000 | 22.18758 | 22.09505 | -0.1674 | 7.30520 |
March | 744.00000 | 22.21035 | 20.54119 | -0.1686 | 7.05497 |
April | 720.00000 | 22.88002 | 23.55738 | 0.03874 | 6.36533 |
May | 744.00000 | 23.34762 | 33.69054 | -0.6978 | 16.77514 |
June | 720.00000 | 23.74011 | 42.09622 | -0.4697 | 10.16035 |
July | 744.00000 | 23.76484 | 56.37972 | -0.3606 | 8.08757 |
August | 744.00000 | 23.69831 | 52.94473 | -0.4050 | 9.13076 |
September | 720.00000 | 23.66830 | 49.81348 | -0.4244 | 9.97085 |
October | 744.00000 | 23.21562 | 41.48772 | 0.27035 | 7.91442 |
November | 720.00000 | 22.50298 | 25.58674 | -0.0471 | 7.34488 |
December | 744.00000 | 21.93260 | 23.16162 | -0.2459 | 8.09028 |
Annual Sum or Average | 8760.00000 | 22.93669 | 34.80940 | -0.2399 | 8.83994 |
Minimum of Months | 672.00000 | 21.93260 | 20.54119 | -0.6978 | 6.36533 |
Maximum of Months | 744.00000 | 23.76484 | 56.37972 | 0.27035 | 16.77514 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.91343 | 25.83289 | -0.0071 | 5.31229 |
February | 672.00000 | 23.03441 | 22.87356 | 0.00618 | 5.27635 |
March | 744.00000 | 23.11742 | 21.38253 | 0.02029 | 5.33393 |
April | 720.00000 | 23.53608 | 24.44990 | 0.15681 | 5.85275 |
May | 744.00000 | 23.74892 | 34.37072 | -0.6247 | 13.64031 |
June | 720.00000 | 23.87337 | 42.93782 | -0.5025 | 10.52922 |
July | 744.00000 | 23.88896 | 57.06340 | -0.3992 | 8.43913 |
August | 744.00000 | 23.87385 | 53.61704 | -0.4315 | 9.03644 |
September | 720.00000 | 23.88738 | 50.51809 | -0.4504 | 9.45899 |
October | 744.00000 | 23.70546 | 41.90412 | 0.32496 | 7.45504 |
November | 720.00000 | 23.30122 | 26.29844 | 0.10114 | 5.61988 |
December | 744.00000 | 22.78754 | 23.94582 | -0.0526 | 5.33763 |
Annual Sum or Average | 8760.00000 | 23.47399 | 35.52931 | -0.1560 | 7.62400 |
Minimum of Months | 672.00000 | 22.78754 | 21.38253 | -0.6247 | 5.27635 |
Maximum of Months | 744.00000 | 23.88896 | 57.06340 | 0.32496 | 13.64031 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.36044 | 20.65809 | 0.67153 | 16.47007 |
February | 672.00000 | 23.38438 | 17.86182 | 0.67194 | 16.41510 |
March | 744.00000 | 23.39015 | 16.48608 | 0.67809 | 16.61527 |
April | 720.00000 | 23.44938 | 20.13977 | 0.74926 | 18.70482 |
May | 744.00000 | 23.47388 | 30.80770 | 0.18627 | 9.57974 |
June | 720.00000 | 23.47947 | 40.07085 | 0.28137 | 10.26968 |
July | 744.00000 | 23.47679 | 54.48443 | 0.37226 | 11.20812 |
August | 744.00000 | 23.46111 | 50.94726 | 0.33690 | 10.89890 |
September | 720.00000 | 23.45510 | 47.73868 | 0.30061 | 10.43293 |
October | 744.00000 | 23.43543 | 38.19246 | 0.86324 | 22.51306 |
November | 720.00000 | 23.40940 | 21.58492 | 0.71099 | 17.59594 |
December | 744.00000 | 23.34655 | 18.71647 | 0.64876 | 15.83992 |
Annual Sum or Average | 8760.00000 | 23.42695 | 31.57596 | 0.53849 | 14.70302 |
Minimum of Months | 672.00000 | 23.34655 | 16.48608 | 0.18627 | 9.57974 |
Maximum of Months | 744.00000 | 23.47947 | 54.48443 | 0.86324 | 22.51306 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.37444 | 29.71282 | 0.18499 | 6.59792 |
February | 672.00000 | 23.48725 | 26.78123 | 0.20309 | 6.48511 |
March | 744.00000 | 23.46562 | 25.41916 | 0.18700 | 6.35342 |
April | 720.00000 | 23.66394 | 28.34905 | 0.28758 | 7.22509 |
May | 744.00000 | 23.73820 | 38.34934 | -0.4870 | 10.57094 |
June | 720.00000 | 23.83530 | 46.68929 | -0.3498 | 7.86903 |
July | 744.00000 | 23.85997 | 60.70027 | -0.2402 | 6.39344 |
August | 744.00000 | 23.85944 | 57.13322 | -0.2614 | 6.73121 |
September | 720.00000 | 23.92310 | 53.80952 | -0.2509 | 6.78413 |
October | 744.00000 | 23.81378 | 45.18849 | 0.48122 | 10.37058 |
November | 720.00000 | 23.56995 | 30.00973 | 0.27068 | 7.55513 |
December | 744.00000 | 23.28699 | 27.86973 | 0.14141 | 6.33102 |
Annual Sum or Average | 8760.00000 | 23.65689 | 39.26347 | 0.01260 | 7.44764 |
Minimum of Months | 672.00000 | 23.28699 | 25.41916 | -0.4870 | 6.33102 |
Maximum of Months | 744.00000 | 23.92310 | 60.70027 | 0.48122 | 10.57094 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.44067 | 28.37485 | 0.15206 | 5.75743 |
February | 672.00000 | 23.50718 | 25.50909 | 0.15366 | 5.72241 |
March | 744.00000 | 23.48255 | 24.09669 | 0.14167 | 5.69624 |
April | 720.00000 | 23.65622 | 27.09887 | 0.22460 | 6.31913 |
May | 744.00000 | 23.73937 | 36.99189 | -0.5758 | 12.36003 |
June | 720.00000 | 23.82820 | 45.53172 | -0.4615 | 9.73853 |
July | 744.00000 | 23.85227 | 59.61012 | -0.3539 | 7.74613 |
August | 744.00000 | 23.86011 | 56.09573 | -0.3782 | 8.12207 |
September | 720.00000 | 23.90848 | 52.92632 | -0.3856 | 8.27636 |
October | 744.00000 | 23.84253 | 44.11788 | 0.40219 | 8.58098 |
November | 720.00000 | 23.67165 | 28.77079 | 0.22803 | 6.38413 |
December | 744.00000 | 23.37033 | 26.56138 | 0.11836 | 5.57263 |
Annual Sum or Average | 8760.00000 | 23.68044 | 38.06956 | -0.0625 | 7.53609 |
Minimum of Months | 672.00000 | 23.37033 | 24.09669 | -0.5758 | 5.57263 |
Maximum of Months | 744.00000 | 23.90848 | 59.61012 | 0.40219 | 12.36003 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.37974 | 38.58423 | -0.3804 | 8.77093 |
February | 672.00000 | 21.47322 | 33.86584 | -0.3595 | 8.51631 |
March | 744.00000 | 21.55019 | 31.32679 | -0.3222 | 8.03249 |
April | 720.00000 | 21.69200 | 33.89759 | -0.2007 | 6.96383 |
May | 744.00000 | 21.78583 | 41.83889 | -1.1591 | 34.90018 |
June | 720.00000 | 21.84289 | 47.80303 | -1.0494 | 29.96881 |
July | 744.00000 | 21.78909 | 54.01173 | -1.0376 | 29.34825 |
August | 744.00000 | 21.78783 | 53.37337 | -1.0561 | 30.21356 |
September | 720.00000 | 21.78336 | 52.28784 | -1.0738 | 31.17452 |
October | 744.00000 | 21.71417 | 49.07757 | -0.0963 | 6.22798 |
November | 720.00000 | 21.53206 | 37.52766 | -0.2946 | 7.89766 |
December | 744.00000 | 21.34354 | 36.24274 | -0.4206 | 9.40496 |
Annual Sum or Average | 8760.00000 | 21.64006 | 42.55299 | -0.6226 | 17.67795 |
Minimum of Months | 672.00000 | 21.34354 | 31.32679 | -1.1591 | 6.22798 |
Maximum of Months | 744.00000 | 21.84289 | 54.01173 | -0.0963 | 34.90018 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.04580 | 39.25956 | -0.5016 | 10.60664 |
February | 672.00000 | 21.29717 | 34.11495 | -0.4452 | 9.74916 |
March | 744.00000 | 21.65658 | 31.10392 | -0.3365 | 8.34796 |
April | 720.00000 | 21.99397 | 33.45548 | -0.1588 | 6.85021 |
May | 744.00000 | 22.10367 | 41.41742 | -1.0758 | 31.32646 |
June | 720.00000 | 22.13297 | 47.85407 | -0.9637 | 26.66151 |
July | 744.00000 | 22.07944 | 54.57368 | -0.9504 | 26.12402 |
August | 744.00000 | 22.09196 | 53.73277 | -0.9789 | 27.16359 |
September | 720.00000 | 22.16372 | 52.63648 | -0.9975 | 27.95839 |
October | 744.00000 | 22.10356 | 49.02819 | -0.0543 | 6.28621 |
November | 720.00000 | 21.43245 | 37.58251 | -0.3704 | 8.69968 |
December | 744.00000 | 20.96754 | 36.99309 | -0.5513 | 11.64725 |
Annual Sum or Average | 8760.00000 | 21.75759 | 42.71354 | -0.6167 | 16.83462 |
Minimum of Months | 672.00000 | 20.96754 | 31.10392 | -1.0758 | 6.28621 |
Maximum of Months | 744.00000 | 22.16372 | 54.57368 | -0.0543 | 31.32646 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.11967 | 35.89177 | -0.4764 | 9.85724 |
February | 672.00000 | 21.25290 | 31.03197 | -0.4578 | 9.54758 |
March | 744.00000 | 21.46013 | 28.22396 | -0.4055 | 8.64576 |
April | 720.00000 | 21.77234 | 30.81455 | -0.2803 | 7.22714 |
May | 744.00000 | 21.92700 | 39.96475 | -1.2606 | 39.10106 |
June | 720.00000 | 21.97099 | 47.60772 | -1.1661 | 34.67555 |
July | 744.00000 | 21.96338 | 55.90973 | -1.1204 | 32.71337 |
August | 744.00000 | 21.95475 | 54.54231 | -1.1498 | 33.92392 |
September | 720.00000 | 21.98139 | 52.91803 | -1.1757 | 35.07423 |
October | 744.00000 | 21.82357 | 47.16796 | -0.1770 | 6.17868 |
November | 720.00000 | 21.28206 | 34.74272 | -0.4233 | 8.93849 |
December | 744.00000 | 21.07854 | 33.64666 | -0.5075 | 10.46969 |
Annual Sum or Average | 8760.00000 | 21.63404 | 41.11547 | -0.7184 | 19.75994 |
Minimum of Months | 672.00000 | 21.07854 | 28.22396 | -1.2606 | 6.17868 |
Maximum of Months | 744.00000 | 21.98139 | 55.90973 | -0.1770 | 39.10106 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.42823 | 38.52736 | -0.3730 | 8.63873 |
February | 672.00000 | 21.55841 | 33.78495 | -0.3325 | 8.23218 |
March | 744.00000 | 21.63364 | 31.30099 | -0.2991 | 7.88249 |
April | 720.00000 | 21.74697 | 33.85594 | -0.1788 | 6.85513 |
May | 744.00000 | 21.78701 | 41.90730 | -1.1498 | 34.38764 |
June | 720.00000 | 21.84439 | 47.91443 | -1.0383 | 29.45099 |
July | 744.00000 | 21.79484 | 53.94254 | -1.0275 | 28.95361 |
August | 744.00000 | 21.78395 | 53.17718 | -1.0508 | 29.97263 |
September | 720.00000 | 21.78380 | 52.09640 | -1.0707 | 31.01393 |
October | 744.00000 | 21.71239 | 49.39201 | -0.1013 | 6.26668 |
November | 720.00000 | 21.56622 | 37.51372 | -0.2897 | 7.84439 |
December | 744.00000 | 21.38192 | 36.23561 | -0.4108 | 9.20105 |
Annual Sum or Average | 8760.00000 | 21.66865 | 42.53799 | -0.6121 | 17.45157 |
Minimum of Months | 672.00000 | 21.38192 | 31.30099 | -1.1498 | 6.26668 |
Maximum of Months | 744.00000 | 21.84439 | 53.94254 | -0.1013 | 34.38764 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.02661 | 39.19407 | -0.5080 | 10.60505 |
February | 672.00000 | 21.32481 | 34.05867 | -0.4289 | 9.36338 |
March | 744.00000 | 21.67230 | 31.18221 | -0.3271 | 8.02790 |
April | 720.00000 | 22.08427 | 33.34134 | -0.1300 | 6.79970 |
May | 744.00000 | 22.27129 | 41.31141 | -1.0185 | 30.21202 |
June | 720.00000 | 22.28922 | 47.43828 | -0.9091 | 25.95334 |
July | 744.00000 | 22.21264 | 53.95797 | -0.9048 | 25.66222 |
August | 744.00000 | 22.22282 | 53.03020 | -0.9358 | 26.67175 |
September | 720.00000 | 22.32848 | 51.99384 | -0.9474 | 27.30455 |
October | 744.00000 | 22.03582 | 49.31095 | -0.0736 | 6.18631 |
November | 720.00000 | 21.39131 | 37.69859 | -0.3811 | 8.69854 |
December | 744.00000 | 20.95511 | 36.92148 | -0.5514 | 11.61042 |
Annual Sum or Average | 8760.00000 | 21.81969 | 42.52044 | -0.5943 | 16.47426 |
Minimum of Months | 672.00000 | 20.95511 | 31.18221 | -1.0185 | 6.18631 |
Maximum of Months | 744.00000 | 22.32848 | 53.95797 | -0.0736 | 30.21202 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.28386 | 39.45303 | -0.4330 | 9.79020 |
February | 672.00000 | 21.40053 | 34.48750 | -0.4042 | 9.39276 |
March | 744.00000 | 21.49434 | 31.72578 | -0.3583 | 8.72451 |
April | 720.00000 | 21.67481 | 34.06509 | -0.2132 | 7.33451 |
May | 744.00000 | 21.78928 | 42.01936 | -1.1588 | 35.21559 |
June | 720.00000 | 21.86341 | 48.11625 | -1.0301 | 29.55946 |
July | 744.00000 | 21.80141 | 54.49472 | -1.0205 | 28.94668 |
August | 744.00000 | 21.79371 | 54.04316 | -1.0451 | 30.07501 |
September | 720.00000 | 21.78264 | 53.19368 | -1.0739 | 31.56538 |
October | 744.00000 | 21.68430 | 50.24096 | -0.1129 | 6.50370 |
November | 720.00000 | 21.46164 | 38.25968 | -0.3400 | 8.71246 |
December | 744.00000 | 21.24900 | 36.99942 | -0.4747 | 10.54346 |
Annual Sum or Average | 8760.00000 | 21.60729 | 43.15879 | -0.6404 | 18.08747 |
Minimum of Months | 672.00000 | 21.24900 | 31.72578 | -1.1588 | 6.50370 |
Maximum of Months | 744.00000 | 21.86341 | 54.49472 | -0.1129 | 35.21559 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.90947 | 40.27401 | -0.5651 | 12.09677 |
February | 672.00000 | 21.19088 | 34.82943 | -0.4990 | 10.96736 |
March | 744.00000 | 21.58949 | 31.59563 | -0.3749 | 9.15915 |
April | 720.00000 | 21.96619 | 33.64294 | -0.1716 | 7.22578 |
May | 744.00000 | 22.07557 | 41.57276 | -1.0822 | 31.87600 |
June | 720.00000 | 22.12825 | 48.03131 | -0.9506 | 26.43747 |
July | 744.00000 | 22.06900 | 54.92404 | -0.9387 | 25.86130 |
August | 744.00000 | 22.06647 | 54.27815 | -0.9759 | 27.25531 |
September | 720.00000 | 22.11162 | 53.54981 | -1.0111 | 28.71508 |
October | 744.00000 | 22.05168 | 50.18746 | -0.0751 | 6.55307 |
November | 720.00000 | 21.31868 | 38.46907 | -0.4286 | 9.82254 |
December | 744.00000 | 20.83772 | 37.89322 | -0.6149 | 13.26697 |
Annual Sum or Average | 8760.00000 | 21.69498 | 43.33836 | -0.6418 | 17.48284 |
Minimum of Months | 672.00000 | 20.83772 | 31.59563 | -1.0822 | 6.55307 |
Maximum of Months | 744.00000 | 22.12825 | 54.92404 | -0.0751 | 31.87600 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.59208 | 39.27239 | -0.2767 | 7.94423 |
February | 672.00000 | 21.63572 | 34.49486 | -0.2804 | 7.96314 |
March | 744.00000 | 21.62945 | 31.74236 | -0.3000 | 8.05242 |
April | 720.00000 | 21.69173 | 34.62435 | -0.2271 | 7.30661 |
May | 744.00000 | 21.72411 | 42.97544 | -1.2473 | 38.90326 |
June | 720.00000 | 21.77801 | 48.87844 | -1.1442 | 33.97056 |
July | 744.00000 | 21.75574 | 55.03357 | -1.1119 | 32.51831 |
August | 744.00000 | 21.75304 | 54.30402 | -1.1167 | 32.86382 |
September | 720.00000 | 21.77003 | 53.35448 | -1.1052 | 32.78858 |
October | 744.00000 | 21.74565 | 49.15746 | -0.0864 | 6.48828 |
November | 720.00000 | 21.63930 | 38.04330 | -0.2326 | 7.61591 |
December | 744.00000 | 21.60104 | 37.16075 | -0.2973 | 8.22276 |
Annual Sum or Average | 8760.00000 | 21.69317 | 43.32027 | -0.6210 | 18.78960 |
Minimum of Months | 672.00000 | 21.59208 | 31.74236 | -1.2473 | 6.48828 |
Maximum of Months | 744.00000 | 21.77801 | 55.03357 | -0.0864 | 38.90326 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.72448 | 28.84799 | 0.23223 | 6.39340 |
February | 672.00000 | 23.79895 | 25.86125 | 0.24693 | 6.47738 |
March | 744.00000 | 23.85296 | 24.17111 | 0.26992 | 6.66299 |
April | 720.00000 | 23.95616 | 26.97271 | 0.36542 | 7.95989 |
May | 744.00000 | 23.98674 | 36.76750 | -0.3643 | 8.03967 |
June | 720.00000 | 23.99493 | 45.36028 | -0.2565 | 6.52505 |
July | 744.00000 | 23.99490 | 59.31709 | -0.1624 | 5.56822 |
August | 744.00000 | 23.99291 | 55.98439 | -0.2030 | 5.91935 |
September | 720.00000 | 23.98817 | 53.15102 | -0.2524 | 6.50426 |
October | 744.00000 | 23.94779 | 44.46471 | 0.47866 | 10.01292 |
November | 720.00000 | 23.82348 | 29.39064 | 0.28530 | 6.90523 |
December | 744.00000 | 23.68788 | 27.16284 | 0.20071 | 6.10727 |
Annual Sum or Average | 8760.00000 | 23.89608 | 38.21518 | 0.06897 | 6.92608 |
Minimum of Months | 672.00000 | 23.68788 | 24.17111 | -0.3643 | 5.56822 |
Maximum of Months | 744.00000 | 23.99493 | 59.31709 | 0.47866 | 10.01292 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.86177 | 27.88287 | 0.30470 | 7.09699 |
February | 672.00000 | 23.90632 | 24.97096 | 0.31092 | 7.14107 |
March | 744.00000 | 23.93913 | 23.36555 | 0.32756 | 7.31815 |
April | 720.00000 | 23.98345 | 26.37876 | 0.40389 | 8.55851 |
May | 744.00000 | 23.99365 | 36.32506 | -0.3220 | 7.41762 |
June | 720.00000 | 23.99605 | 44.99334 | -0.2197 | 6.16452 |
July | 744.00000 | 23.99587 | 58.94501 | -0.1258 | 5.35115 |
August | 744.00000 | 23.99503 | 55.59184 | -0.1653 | 5.63208 |
September | 720.00000 | 23.99388 | 52.71269 | -0.2125 | 6.10648 |
October | 744.00000 | 23.97952 | 43.85822 | 0.51607 | 10.76984 |
November | 720.00000 | 23.92019 | 28.54326 | 0.34428 | 7.60682 |
December | 744.00000 | 23.84031 | 26.18719 | 0.27763 | 6.75590 |
Annual Sum or Average | 8760.00000 | 23.95054 | 37.57495 | 0.11886 | 7.16064 |
Minimum of Months | 672.00000 | 23.84031 | 23.36555 | -0.3220 | 5.35115 |
Maximum of Months | 744.00000 | 23.99605 | 58.94501 | 0.51607 | 10.76984 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.88363 | 26.63804 | 0.94900 | 25.90079 |
February | 672.00000 | 23.90293 | 23.90591 | 0.95926 | 26.26372 |
March | 744.00000 | 23.92808 | 22.57857 | 0.98034 | 27.11252 |
April | 720.00000 | 23.97353 | 26.00555 | 1.07459 | 31.11483 |
May | 744.00000 | 23.98902 | 36.05581 | 0.64735 | 17.82611 |
June | 720.00000 | 23.99234 | 44.66407 | 0.75964 | 20.60986 |
July | 744.00000 | 23.99300 | 58.25049 | 0.84736 | 23.23963 |
August | 744.00000 | 23.99278 | 54.90210 | 0.80625 | 21.98011 |
September | 720.00000 | 23.99095 | 51.92637 | 0.76043 | 20.70864 |
October | 744.00000 | 23.97460 | 42.99776 | 1.17773 | 35.54259 |
November | 720.00000 | 23.91357 | 27.50329 | 0.99341 | 27.69558 |
December | 744.00000 | 23.86295 | 24.85390 | 0.92169 | 24.87861 |
Annual Sum or Average | 8760.00000 | 23.94997 | 36.78608 | 0.90609 | 25.23327 |
Minimum of Months | 672.00000 | 23.86295 | 22.57857 | 0.64735 | 17.82611 |
Maximum of Months | 744.00000 | 23.99300 | 58.25049 | 1.17773 | 35.54259 |
Report: OccupantComfortDataSummaryMonthly
For: STORAGE_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.35962 | 24.38570 | -0.4111 | 8.65675 |
February | 672.00000 | 21.55097 | 21.03444 | -0.3840 | 8.24689 |
March | 744.00000 | 21.77392 | 19.31026 | -0.3394 | 7.56876 |
April | 720.00000 | 22.61421 | 22.28666 | -0.1148 | 5.59640 |
May | 744.00000 | 23.35029 | 32.01648 | -0.8392 | 20.44489 |
June | 720.00000 | 23.84422 | 40.36203 | -0.6040 | 12.81067 |
July | 744.00000 | 23.87464 | 54.63891 | -0.4943 | 10.15650 |
August | 744.00000 | 23.75211 | 51.35148 | -0.5636 | 11.80126 |
September | 720.00000 | 23.53065 | 48.84329 | -0.6606 | 14.53264 |
October | 744.00000 | 22.87540 | 40.67800 | 0.06980 | 5.46544 |
November | 720.00000 | 21.95232 | 24.64042 | -0.2632 | 6.78198 |
December | 744.00000 | 21.25803 | 22.28612 | -0.4508 | 9.32723 |
Annual Sum or Average | 8760.00000 | 22.64995 | 33.58250 | -0.4217 | 10.13318 |
Minimum of Months | 672.00000 | 21.25803 | 19.31026 | -0.8392 | 5.46544 |
Maximum of Months | 744.00000 | 23.87464 | 54.63891 | 0.06980 | 20.44489 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.44559 | 27.72702 | -0.3921 | 8.34223 |
February | 672.00000 | 21.72836 | 24.32796 | -0.3423 | 7.57066 |
March | 744.00000 | 22.01132 | 22.57868 | -0.2832 | 6.82442 |
April | 720.00000 | 22.78962 | 25.68088 | -0.0729 | 5.35502 |
May | 744.00000 | 23.41168 | 35.60915 | -0.8266 | 19.90106 |
June | 720.00000 | 23.82610 | 44.01712 | -0.6202 | 13.23091 |
July | 744.00000 | 23.78913 | 58.38480 | -0.5362 | 11.07314 |
August | 744.00000 | 23.72157 | 55.03649 | -0.5844 | 12.30704 |
September | 720.00000 | 23.67016 | 52.07474 | -0.6223 | 13.37166 |
October | 744.00000 | 23.07671 | 43.85586 | 0.11775 | 5.56854 |
November | 720.00000 | 22.20778 | 27.84342 | -0.2027 | 6.23390 |
December | 744.00000 | 21.27085 | 25.71188 | -0.4480 | 9.23967 |
Annual Sum or Average | 8760.00000 | 22.74996 | 37.00188 | -0.4018 | 9.94154 |
Minimum of Months | 672.00000 | 21.27085 | 22.57868 | -0.8266 | 5.35502 |
Maximum of Months | 744.00000 | 23.82610 | 58.38480 | 0.11775 | 19.90106 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.30592 | 25.58978 | -0.4143 | 8.76354 |
February | 672.00000 | 21.57176 | 22.20187 | -0.3635 | 8.02454 |
March | 744.00000 | 21.83355 | 20.40364 | -0.3053 | 7.26267 |
April | 720.00000 | 22.83680 | 23.15775 | -0.0329 | 5.64447 |
May | 744.00000 | 23.53843 | 32.89640 | -0.7279 | 17.01521 |
June | 720.00000 | 23.89701 | 41.26675 | -0.5236 | 10.96836 |
July | 744.00000 | 23.89705 | 55.42876 | -0.4270 | 8.88089 |
August | 744.00000 | 23.81505 | 52.17174 | -0.4848 | 10.12997 |
September | 720.00000 | 23.66867 | 49.48507 | -0.5626 | 12.22429 |
October | 744.00000 | 22.97260 | 41.61358 | 0.12199 | 5.93889 |
November | 720.00000 | 21.87630 | 25.90345 | -0.2635 | 7.02221 |
December | 744.00000 | 21.20336 | 23.48409 | -0.4584 | 9.48745 |
Annual Sum or Average | 8760.00000 | 22.70662 | 34.56239 | -0.3705 | 9.29399 |
Minimum of Months | 672.00000 | 21.20336 | 20.40364 | -0.7279 | 5.64447 |
Maximum of Months | 744.00000 | 23.89705 | 55.42876 | 0.12199 | 17.01521 |
Report: OccupantComfortDataSummaryMonthly
For: MECH_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.65106 | 23.68593 | -0.3489 | 7.70550 |
February | 672.00000 | 21.83013 | 20.40550 | -0.3249 | 7.40340 |
March | 744.00000 | 22.05804 | 18.70612 | -0.2792 | 6.82570 |
April | 720.00000 | 22.87308 | 21.66006 | -0.0599 | 5.41449 |
May | 744.00000 | 23.55996 | 31.28217 | -0.7737 | 18.17777 |
June | 720.00000 | 23.91403 | 39.84057 | -0.5789 | 12.17496 |
July | 744.00000 | 23.93435 | 54.09690 | -0.4719 | 9.69233 |
August | 744.00000 | 23.86278 | 50.67142 | -0.5263 | 10.90574 |
September | 720.00000 | 23.72863 | 47.96554 | -0.5973 | 12.80706 |
October | 744.00000 | 23.14500 | 39.75071 | 0.12755 | 5.68881 |
November | 720.00000 | 22.25171 | 23.91916 | -0.1993 | 6.19651 |
December | 744.00000 | 21.51646 | 21.67684 | -0.3945 | 8.38174 |
Annual Sum or Average | 8760.00000 | 22.86527 | 32.90106 | -0.3694 | 9.29806 |
Minimum of Months | 672.00000 | 21.51646 | 18.70612 | -0.7737 | 5.41449 |
Maximum of Months | 744.00000 | 23.93435 | 54.09690 | 0.12755 | 18.17777 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.922451E+10 | 51028.58 | 03-JAN-16:02 | 561.33 | 0.428013E+11 | 0.00 | 0.520258E+11 | 3.54 | 4.72 | 11-JAN-10:00 | 0.00 | 0.00 |
February | 0.170537E+11 | 70948.84 | 22-FEB-16:01 | 573.86 | 0.761066E+11 | 0.00 | 0.931604E+11 | 3.96 | 4.72 | 04-FEB-23:30 | 0.00 | 0.00 |
March | 0.279212E+11 | 74299.98 | 14-MAR-15:02 | 698.52 | 0.122501E+12 | 0.00 | 0.150422E+12 | 4.31 | 4.72 | 26-MAR-07:27 | 0.00 | 0.00 |
April | 0.779896E+11 | 107560.28 | 28-APR-18:04 | 718.17 | 0.318776E+12 | 0.00 | 0.396765E+12 | 4.31 | 4.72 | 01-APR-00:30 | 0.00 | 0.00 |
May | 0.130294E+12 | 121998.64 | 19-MAY-18:04 | 744.00 | 0.509940E+12 | 0.00 | 0.640234E+12 | 4.07 | 4.72 | 02-MAY-03:30 | 0.00 | 0.00 |
June | 0.178680E+12 | 146739.97 | 18-JUN-18:03 | 720.00 | 0.655500E+12 | 0.00 | 0.834179E+12 | 3.79 | 4.62 | 13-JUN-05:00 | 0.00 | 0.00 |
July | 0.220511E+12 | 158737.09 | 21-JUL-21:00 | 744.00 | 0.832545E+12 | 0.00 | 0.105306E+13 | 3.83 | 4.50 | 19-JUL-03:00 | 0.00 | 0.00 |
August | 0.182337E+12 | 155967.93 | 01-AUG-21:51 | 744.00 | 0.697031E+12 | 0.00 | 0.879369E+12 | 3.92 | 4.60 | 16-AUG-21:53 | 0.00 | 0.00 |
September | 0.146513E+12 | 123258.41 | 17-SEP-18:02 | 720.00 | 0.585591E+12 | 0.00 | 0.732104E+12 | 4.12 | 4.72 | 12-SEP-06:00 | 0.00 | 0.00 |
October | 0.779270E+11 | 127956.02 | 04-OCT-18:03 | 744.00 | 0.325482E+12 | 0.00 | 0.403409E+12 | 4.40 | 4.72 | 11-OCT-08:03 | 0.00 | 0.00 |
November | 0.230263E+11 | 71027.36 | 03-NOV-15:03 | 610.59 | 0.103073E+12 | 0.00 | 0.126099E+12 | 3.92 | 4.72 | 01-NOV-00:05 | 0.00 | 0.00 |
December | 0.739712E+10 | 36926.95 | 10-DEC-16:02 | 550.19 | 0.345353E+11 | 0.00 | 0.419325E+11 | 3.47 | 4.72 | 14-DEC-18:50 | 0.00 | 0.00 |
Annual Sum or Average | 0.109888E+13 | 8128.66 | 0.430388E+13 | 0.00 | 0.540276E+13 | 3.97 | 0.00 | 0.00 | ||||
Minimum of Months | 0.739712E+10 | 36926.95 | 550.19 | 0.345353E+11 | 0.00 | 0.419325E+11 | 3.47 | 4.50 | 0.00 | 0.00 | ||
Maximum of Months | 0.220511E+12 | 158737.09 | 744.00 | 0.832545E+12 | 0.00 | 0.105306E+13 | 4.40 | 4.72 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.122684E+12 | 0.00 | 683.83 | 146802.70 | 14-JAN-16:02 | 0.00 | 35.49 | 57.66 | 0.45 | 0.00 | 0.12 | 0.38 | 14-JAN-16:02 |
February | 0.773029E+11 | 0.00 | 513.45 | 145473.42 | 01-FEB-19:03 | 0.00 | 34.16 | 53.32 | 0.30 | 0.00 | 0.08 | 0.37 | 01-FEB-19:03 |
March | 0.651360E+11 | 0.00 | 433.73 | 136917.28 | 27-MAR-08:07 | 0.00 | 31.55 | 47.12 | 0.22 | 0.00 | 0.06 | 0.35 | 27-MAR-08:07 |
April | 0.198574E+11 | 0.00 | 136.41 | 132619.43 | 11-APR-08:05 | 0.00 | 27.41 | 33.24 | 0.06 | 0.00 | 0.02 | 0.34 | 11-APR-08:05 |
May | 0.884119E+09 | 0.00 | 17.20 | 53335.98 | 02-MAY-06:00 | 0.00 | 26.78 | 27.54 | 0.00 | 0.00 | 0.00 | 0.14 | 02-MAY-06:00 |
June | 3054170.93 | 0.00 | 0.59 | 9867.48 | 29-JUN-08:05 | 0.00 | 28.32 | 28.35 | 0.00 | 0.00 | 0.00 | 0.03 | 29-JUN-08:05 |
July | 2644776.09 | 0.00 | 0.61 | 5294.51 | 19-JUL-08:07 | 0.00 | 30.83 | 30.86 | 0.00 | 0.00 | 0.00 | 0.01 | 19-JUL-08:07 |
August | 7141710.29 | 0.00 | 1.05 | 9556.84 | 14-AUG-08:06 | 0.00 | 34.51 | 34.54 | 0.00 | 0.00 | 0.00 | 0.02 | 14-AUG-08:06 |
September | 0.128263E+10 | 0.00 | 17.77 | 68429.43 | 30-SEP-06:00 | 0.00 | 36.77 | 37.58 | 0.00 | 0.00 | 0.00 | 0.18 | 30-SEP-06:00 |
October | 0.121229E+11 | 0.00 | 144.47 | 118609.01 | 25-OCT-06:05 | 0.00 | 27.35 | 33.65 | 0.03 | 0.00 | 0.01 | 0.30 | 25-OCT-06:05 |
November | 0.748704E+11 | 0.00 | 495.83 | 169412.49 | 27-NOV-19:02 | 0.00 | 34.50 | 51.84 | 0.27 | 0.00 | 0.07 | 0.43 | 27-NOV-19:02 |
December | 0.105387E+12 | 0.00 | 698.34 | 161079.26 | 28-DEC-19:02 | 0.00 | 36.98 | 58.25 | 0.40 | 0.00 | 0.10 | 0.41 | 28-DEC-19:02 |
Annual Sum or Average | 0.479540E+12 | 0.00 | 3143.28 | 0.00 | 32.04 | 41.10 | 0.15 | 0.00 | 0.04 | ||||
Minimum of Months | 2644776.09 | 0.00 | 0.59 | 5294.51 | 0.00 | 26.78 | 27.54 | 0.00 | 0.00 | 0.00 | 0.01 | ||
Maximum of Months | 0.122684E+12 | 0.00 | 698.34 | 169412.49 | 0.00 | 36.98 | 58.25 | 0.45 | 0.00 | 0.12 | 0.43 |
Report: DXReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.424271E+09 | 0.00 | 40.67 | 0.424271E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11015.35 | 03-JAN-17:00 | 11015.35 | 03-JAN-17:00 | 0.00 | 0.00 | 0.00 |
February | 0.213369E+10 | 0.00 | 104.33 | 0.213369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14201.75 | 20-FEB-16:02 | 14201.75 | 20-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.440496E+10 | 0.00 | 187.50 | 0.440496E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14771.59 | 22-MAR-15:02 | 14771.59 | 22-MAR-15:02 | 0.00 | 0.00 | 0.00 |
April | 0.144455E+11 | 0.00 | 416.17 | 0.144455E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 17662.05 | 21-APR-15:02 | 17662.05 | 21-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.238762E+11 | 0.00 | 559.50 | 0.233289E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 21571.96 | 24-MAY-13:00 | 18546.34 | 19-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.298114E+11 | 0.00 | 570.00 | 0.285666E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 24534.76 | 27-JUN-24:00 | 19661.34 | 15-JUN-15:03 | 0.00 | 0.00 | 0.00 |
July | 0.419047E+11 | 0.00 | 589.00 | 0.300733E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 39037.79 | 21-JUL-08:03 | 19659.13 | 02-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.343740E+11 | 0.00 | 589.00 | 0.282785E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 33560.00 | 01-AUG-21:51 | 19089.86 | 06-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.288701E+11 | 0.00 | 543.50 | 0.220914E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 31964.14 | 22-SEP-08:03 | 18190.96 | 19-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.136959E+11 | 0.00 | 400.67 | 0.123355E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 27787.53 | 03-OCT-20:20 | 17911.90 | 01-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.268590E+10 | 0.00 | 138.17 | 0.268590E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14433.34 | 09-NOV-16:02 | 14433.34 | 09-NOV-16:02 | 0.00 | 0.00 | 0.00 |
December | 0.217497E+09 | 0.00 | 33.00 | 0.217497E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5697.71 | 10-DEC-14:00 | 5697.71 | 10-DEC-14:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.196844E+12 | 0.00 | 4171.50 | 0.168986E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.217497E+09 | 0.00 | 33.00 | 0.217497E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5697.71 | 5697.71 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.419047E+11 | 0.00 | 589.00 | 0.300733E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 39037.79 | 19661.34 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.651804E+10 | 0.00 | 147.41 | 0.651804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 90506.65 | 03-JAN-17:00 | 90506.65 | 03-JAN-17:00 | 0.00 | 0.00 | 0.00 |
February | 0.332095E+11 | 0.00 | 223.99 | 0.332095E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 125144.89 | 21-FEB-16:13 | 125144.89 | 21-FEB-16:13 | 0.00 | 0.00 | 0.00 |
March | 0.676421E+11 | 0.00 | 332.38 | 0.676421E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 162479.49 | 14-MAR-18:10 | 162479.49 | 14-MAR-18:10 | 0.00 | 0.00 | 0.00 |
April | 0.211171E+12 | 0.00 | 552.19 | 0.211171E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 232019.11 | 19-APR-21:00 | 232019.11 | 19-APR-21:00 | 0.00 | 0.00 | 0.00 |
May | 0.349935E+12 | 0.00 | 711.00 | 0.348328E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 255163.14 | 19-MAY-19:10 | 255163.14 | 19-MAY-19:10 | 0.00 | 0.00 | 0.00 |
June | 0.451818E+12 | 0.00 | 720.00 | 0.446731E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 302704.71 | 19-JUN-18:02 | 276934.86 | 02-JUN-18:03 | 0.00 | 0.00 | 0.00 |
July | 0.605002E+12 | 0.00 | 744.00 | 0.468100E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 477291.69 | 21-JUL-21:00 | 274241.50 | 25-JUL-20:10 | 0.00 | 0.00 | 0.00 |
August | 0.491342E+12 | 0.00 | 744.00 | 0.438578E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 454220.22 | 01-AUG-20:50 | 282148.91 | 04-AUG-20:10 | 0.00 | 0.00 | 0.00 |
September | 0.401659E+12 | 0.00 | 692.17 | 0.345336E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 338086.83 | 09-SEP-20:00 | 259123.38 | 19-SEP-18:17 | 0.00 | 0.00 | 0.00 |
October | 0.198949E+12 | 0.00 | 534.75 | 0.190319E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 384591.27 | 03-OCT-19:55 | 242876.70 | 04-OCT-20:10 | 0.00 | 0.00 | 0.00 |
November | 0.412903E+11 | 0.00 | 271.89 | 0.412903E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 149267.48 | 03-NOV-15:55 | 149267.48 | 03-NOV-15:55 | 0.00 | 0.00 | 0.00 |
December | 0.381061E+10 | 0.00 | 170.68 | 0.381061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49687.19 | 09-DEC-13:00 | 49687.19 | 09-DEC-13:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.286235E+13 | 0.00 | 5844.45 | 0.260103E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.381061E+10 | 0.00 | 147.41 | 0.381061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49687.19 | 49687.19 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.605002E+12 | 0.00 | 744.00 | 0.468100E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 477291.69 | 282148.91 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.944498E+09 | 0.00 | 206.93 | 0.803344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9586.12 | 07-JAN-16:02 | 9586.12 | 07-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 0.140738E+10 | 0.00 | 271.74 | 0.138008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9586.45 | 05-FEB-16:02 | 9586.45 | 05-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.258513E+10 | 0.00 | 416.76 | 0.253391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9586.65 | 05-MAR-16:02 | 9586.65 | 05-MAR-16:02 | 0.00 | 0.00 | 0.00 |
April | 0.568009E+10 | 0.00 | 613.95 | 0.526334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9586.82 | 07-APR-15:02 | 9586.82 | 07-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.860860E+10 | 0.00 | 699.74 | 0.744741E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10658.14 | 28-MAY-08:62 | 9586.73 | 05-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.108046E+11 | 0.00 | 694.31 | 0.905665E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10566.15 | 28-JUN-08:62 | 9648.54 | 22-JUN-08:62 | 0.00 | 0.00 | 0.00 |
July | 0.113373E+11 | 0.00 | 717.03 | 0.856527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12004.69 | 19-JUL-08:62 | 9666.51 | 02-JUL-08:62 | 0.00 | 0.00 | 0.00 |
August | 0.105008E+11 | 0.00 | 710.14 | 0.794192E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10995.51 | 14-AUG-08:62 | 9657.06 | 02-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.964657E+10 | 0.00 | 687.13 | 0.724821E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11364.05 | 04-SEP-08:62 | 9640.92 | 20-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.646007E+10 | 0.00 | 669.59 | 0.482623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11215.09 | 15-OCT-08:62 | 9632.28 | 02-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.252084E+10 | 0.00 | 396.13 | 0.224860E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9886.30 | 03-NOV-08:62 | 9586.39 | 08-NOV-16:02 | 0.00 | 0.00 | 0.00 |
December | 0.589147E+09 | 0.00 | 158.73 | 0.548799E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9586.48 | 28-DEC-16:02 | 9586.48 | 28-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.710850E+11 | 0.00 | 6242.17 | 0.578638E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.589147E+09 | 0.00 | 158.73 | 0.548799E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9586.12 | 9586.12 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.113373E+11 | 0.00 | 717.03 | 0.905665E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12004.69 | 9666.51 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.168107E+09 | 0.00 | 46.83 | 0.141740E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9469.19 | 30-JAN-16:02 | 9469.19 | 30-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 0.282336E+09 | 0.00 | 93.79 | 0.275793E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9523.19 | 05-FEB-16:02 | 9523.19 | 05-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.912208E+09 | 0.00 | 224.92 | 0.884656E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9523.47 | 05-MAR-16:02 | 9523.47 | 05-MAR-16:02 | 0.00 | 0.00 | 0.00 |
April | 0.421429E+10 | 0.00 | 488.00 | 0.386895E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10621.06 | 06-APR-18:11 | 10621.06 | 06-APR-18:11 | 0.00 | 0.00 | 0.00 |
May | 0.778569E+10 | 0.00 | 591.44 | 0.678831E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11288.07 | 28-MAY-08:51 | 10277.60 | 20-MAY-08:51 | 0.00 | 0.00 | 0.00 |
June | 0.103596E+11 | 0.00 | 619.55 | 0.878158E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11409.00 | 04-JUN-08:51 | 10707.41 | 19-JUN-18:51 | 0.00 | 0.00 | 0.00 |
July | 0.107209E+11 | 0.00 | 635.36 | 0.822412E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12868.61 | 21-JUL-08:51 | 10159.40 | 11-JUL-07:52 | 0.00 | 0.00 | 0.00 |
August | 0.932209E+10 | 0.00 | 608.61 | 0.710667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12527.19 | 03-AUG-08:61 | 10175.63 | 26-AUG-08:11 | 0.00 | 0.00 | 0.00 |
September | 0.739371E+10 | 0.00 | 545.29 | 0.551709E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12185.28 | 03-SEP-08:51 | 10194.70 | 09-SEP-17:52 | 0.00 | 0.00 | 0.00 |
October | 0.349024E+10 | 0.00 | 467.22 | 0.231496E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11470.28 | 03-OCT-21:51 | 9726.75 | 03-OCT-18:21 | 0.00 | 0.00 | 0.00 |
November | 0.635540E+09 | 0.00 | 185.41 | 0.512430E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9695.21 | 02-NOV-15:02 | 9523.45 | 08-NOV-16:02 | 0.00 | 0.00 | 0.00 |
December | 72583243.19 | 0.00 | 19.52 | 67569650.79 | 0.00 | 0.00 | 0.00 | 0.00 | 9518.78 | 16-DEC-16:02 | 9518.78 | 16-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.553573E+11 | 0.00 | 4525.93 | 0.444839E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 72583243.19 | 0.00 | 19.52 | 67569650.79 | 0.00 | 0.00 | 0.00 | 0.00 | 9469.19 | 9469.19 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.107209E+11 | 0.00 | 635.36 | 0.878158E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12868.61 | 10707.41 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.209024E+11 | 0.00 | 399.43 | 0.208260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 40796.88 | 12-JAN-14:25 | 40796.88 | 12-JAN-14:25 | 0.00 | 0.00 | 0.00 |
February | 0.211718E+11 | 0.00 | 419.78 | 0.209196E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 38387.24 | 07-FEB-13:40 | 38387.24 | 07-FEB-13:40 | 0.00 | 0.00 | 0.00 |
March | 0.198286E+11 | 0.00 | 493.04 | 0.196020E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 29525.48 | 16-MAR-12:50 | 29525.48 | 16-MAR-12:50 | 0.00 | 0.00 | 0.00 |
April | 0.277315E+11 | 0.00 | 625.73 | 0.249430E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 27842.30 | 03-APR-14:00 | 27842.30 | 03-APR-14:00 | 0.00 | 0.00 | 0.00 |
May | 0.340868E+11 | 0.00 | 728.06 | 0.252926E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 26571.61 | 31-MAY-20:20 | 24084.04 | 15-MAY-20:20 | 0.00 | 0.00 | 0.00 |
June | 0.424858E+11 | 0.00 | 719.17 | 0.293507E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 29863.87 | 15-JUN-20:20 | 29863.87 | 15-JUN-20:20 | 0.00 | 0.00 | 0.00 |
July | 0.460501E+11 | 0.00 | 743.14 | 0.264990E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 30792.81 | 26-JUL-17:20 | 25822.12 | 02-JUL-20:20 | 0.00 | 0.00 | 0.00 |
August | 0.471719E+11 | 0.00 | 743.17 | 0.290244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 32132.40 | 29-AUG-13:00 | 28627.05 | 27-AUG-13:40 | 0.00 | 0.00 | 0.00 |
September | 0.518574E+11 | 0.00 | 718.33 | 0.356379E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 41253.38 | 19-SEP-13:30 | 35486.88 | 19-SEP-16:20 | 0.00 | 0.00 | 0.00 |
October | 0.463225E+11 | 0.00 | 695.56 | 0.350547E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 47180.64 | 22-OCT-13:15 | 45956.20 | 22-OCT-13:15 | 0.00 | 0.00 | 0.00 |
November | 0.323982E+11 | 0.00 | 486.69 | 0.306933E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 43923.77 | 09-NOV-13:50 | 43923.77 | 09-NOV-13:50 | 0.00 | 0.00 | 0.00 |
December | 0.178334E+11 | 0.00 | 386.83 | 0.178334E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 34169.18 | 16-DEC-13:40 | 34169.18 | 16-DEC-13:40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.407841E+12 | 0.00 | 7158.92 | 0.315677E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.178334E+11 | 0.00 | 386.83 | 0.178334E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 26571.61 | 24084.04 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.518574E+11 | 0.00 | 743.17 | 0.356379E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 47180.64 | 45956.20 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.318839E+10 | 0.00 | 178.10 | 0.260417E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61413.64 | 16-JAN-09:02 | 59423.66 | 14-JAN-09:02 | 0.00 | 0.00 | 0.00 |
February | 0.592666E+10 | 0.00 | 241.25 | 0.540099E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61991.87 | 21-FEB-21:32 | 61991.87 | 21-FEB-21:32 | 0.00 | 0.00 | 0.00 |
March | 0.120269E+11 | 0.00 | 355.53 | 0.115685E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 63124.46 | 22-MAR-20:22 | 63124.46 | 22-MAR-20:22 | 0.00 | 0.00 | 0.00 |
April | 0.296546E+11 | 0.00 | 449.24 | 0.280097E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 64518.04 | 05-APR-21:52 | 64518.04 | 05-APR-21:52 | 0.00 | 0.00 | 0.00 |
May | 0.493409E+11 | 0.00 | 529.07 | 0.437501E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 70231.53 | 23-MAY-21:51 | 65613.18 | 20-MAY-08:51 | 0.00 | 0.00 | 0.00 |
June | 0.647682E+11 | 0.00 | 579.09 | 0.551248E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 69701.08 | 19-JUN-18:51 | 67818.21 | 21-JUN-07:42 | 0.00 | 0.00 | 0.00 |
July | 0.695372E+11 | 0.00 | 588.41 | 0.528950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 81624.17 | 21-JUL-08:51 | 66937.95 | 10-JUL-07:21 | 0.00 | 0.00 | 0.00 |
August | 0.594148E+11 | 0.00 | 552.47 | 0.447913E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 77452.83 | 16-AUG-21:52 | 66322.95 | 11-AUG-07:51 | 0.00 | 0.00 | 0.00 |
September | 0.453411E+11 | 0.00 | 479.12 | 0.334338E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 77940.34 | 23-SEP-21:51 | 64108.98 | 11-SEP-21:51 | 0.00 | 0.00 | 0.00 |
October | 0.276600E+11 | 0.00 | 407.33 | 0.197657E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 75521.23 | 03-OCT-21:51 | 63646.10 | 04-OCT-18:02 | 0.00 | 0.00 | 0.00 |
November | 0.766609E+10 | 0.00 | 290.37 | 0.642419E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61618.47 | 08-NOV-22:52 | 61618.47 | 08-NOV-22:52 | 0.00 | 0.00 | 0.00 |
December | 0.222765E+10 | 0.00 | 138.67 | 0.203285E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59327.73 | 16-DEC-09:02 | 59327.73 | 16-DEC-09:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.376753E+12 | 0.00 | 4788.65 | 0.305801E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.222765E+10 | 0.00 | 138.67 | 0.203285E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59327.73 | 59327.73 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.695372E+11 | 0.00 | 588.41 | 0.551248E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 81624.17 | 67818.21 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.847653E+09 | 0.00 | 194.46 | 0.728066E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8479.77 | 31-JAN-09:02 | 8479.77 | 31-JAN-09:02 | 0.00 | 0.00 | 0.00 |
February | 0.160171E+10 | 0.00 | 307.76 | 0.153437E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8479.81 | 06-FEB-09:02 | 8479.81 | 06-FEB-09:02 | 0.00 | 0.00 | 0.00 |
March | 0.265135E+10 | 0.00 | 455.14 | 0.258131E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8480.18 | 06-MAR-09:02 | 8480.18 | 06-MAR-09:02 | 0.00 | 0.00 | 0.00 |
April | 0.598143E+10 | 0.00 | 657.28 | 0.557324E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8480.02 | 02-APR-15:02 | 8480.02 | 02-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.885063E+10 | 0.00 | 726.31 | 0.777754E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8852.73 | 28-MAY-08:62 | 8524.30 | 25-MAY-08:62 | 0.00 | 0.00 | 0.00 |
June | 0.111609E+11 | 0.00 | 708.39 | 0.963242E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9143.05 | 29-JUN-08:62 | 8506.25 | 28-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.116721E+11 | 0.00 | 729.50 | 0.915739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10635.03 | 19-JUL-08:62 | 8545.21 | 11-JUL-08:62 | 0.00 | 0.00 | 0.00 |
August | 0.108025E+11 | 0.00 | 724.83 | 0.855820E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9728.14 | 14-AUG-08:62 | 8533.76 | 21-AUG-08:62 | 0.00 | 0.00 | 0.00 |
September | 0.976021E+10 | 0.00 | 703.38 | 0.758504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9822.05 | 23-SEP-18:02 | 8539.03 | 16-SEP-08:62 | 0.00 | 0.00 | 0.00 |
October | 0.606166E+10 | 0.00 | 668.16 | 0.458335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10167.74 | 15-OCT-08:62 | 8523.40 | 05-OCT-18:02 | 0.00 | 0.00 | 0.00 |
November | 0.242236E+10 | 0.00 | 411.03 | 0.217794E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9015.87 | 03-NOV-08:62 | 8479.82 | 08-NOV-16:02 | 0.00 | 0.00 | 0.00 |
December | 0.624169E+09 | 0.00 | 151.34 | 0.547569E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8479.20 | 17-DEC-09:02 | 8479.20 | 17-DEC-09:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.724367E+11 | 0.00 | 6437.58 | 0.604364E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.624169E+09 | 0.00 | 151.34 | 0.547569E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8479.20 | 8479.20 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.116721E+11 | 0.00 | 729.50 | 0.963242E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10635.03 | 8545.21 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.115958E+09 | 0.00 | 43.38 | 78995210.48 | 0.00 | 0.00 | 0.00 | 0.00 | 8071.15 | 31-JAN-09:02 | 8071.15 | 31-JAN-09:02 | 0.00 | 0.00 | 0.00 |
February | 0.474769E+09 | 0.00 | 119.66 | 0.428971E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8419.14 | 20-FEB-09:02 | 8419.14 | 20-FEB-09:02 | 0.00 | 0.00 | 0.00 |
March | 0.117988E+10 | 0.00 | 259.86 | 0.113053E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8419.50 | 06-MAR-09:02 | 8419.50 | 06-MAR-09:02 | 0.00 | 0.00 | 0.00 |
April | 0.447723E+10 | 0.00 | 529.34 | 0.413409E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9768.45 | 27-APR-08:51 | 9768.45 | 27-APR-08:51 | 0.00 | 0.00 | 0.00 |
May | 0.773803E+10 | 0.00 | 615.43 | 0.681994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10812.56 | 28-MAY-08:51 | 10522.86 | 20-MAY-08:32 | 0.00 | 0.00 | 0.00 |
June | 0.104646E+11 | 0.00 | 633.47 | 0.909500E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11372.50 | 20-JUN-08:62 | 10787.03 | 14-JUN-07:52 | 0.00 | 0.00 | 0.00 |
July | 0.108309E+11 | 0.00 | 646.15 | 0.858516E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12149.95 | 22-JUL-08:13 | 10056.32 | 06-JUL-07:42 | 0.00 | 0.00 | 0.00 |
August | 0.939459E+10 | 0.00 | 622.49 | 0.742871E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11890.29 | 03-AUG-07:42 | 10087.96 | 04-AUG-07:42 | 0.00 | 0.00 | 0.00 |
September | 0.723374E+10 | 0.00 | 562.42 | 0.540410E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11344.86 | 03-SEP-08:51 | 9593.55 | 19-SEP-08:51 | 0.00 | 0.00 | 0.00 |
October | 0.328508E+10 | 0.00 | 477.43 | 0.222665E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10425.10 | 05-OCT-08:51 | 9435.95 | 03-OCT-08:51 | 0.00 | 0.00 | 0.00 |
November | 0.661780E+09 | 0.00 | 166.05 | 0.561226E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9060.34 | 03-NOV-08:62 | 8961.75 | 09-NOV-09:51 | 0.00 | 0.00 | 0.00 |
December | 80170993.31 | 0.00 | 30.84 | 59014865.49 | 0.00 | 0.00 | 0.00 | 0.00 | 8305.08 | 16-DEC-09:02 | 8305.08 | 16-DEC-09:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.559367E+11 | 0.00 | 4706.51 | 0.459524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 80170993.31 | 0.00 | 30.84 | 59014865.49 | 0.00 | 0.00 | 0.00 | 0.00 | 8071.15 | 8071.15 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.108309E+11 | 0.00 | 646.15 | 0.909500E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12149.95 | 10787.03 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.188614E+09 | 0.00 | 141.03 | 0.164740E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2544.68 | 29-JAN-16:02 | 2544.68 | 29-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 0.301022E+09 | 0.00 | 191.35 | 0.297271E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2544.79 | 05-FEB-16:02 | 2544.79 | 05-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.575772E+09 | 0.00 | 319.17 | 0.566345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2581.33 | 11-MAR-16:02 | 2544.92 | 27-MAR-15:02 | 0.00 | 0.00 | 0.00 |
April | 0.137459E+10 | 0.00 | 574.43 | 0.127072E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2544.81 | 02-APR-18:02 | 2544.81 | 02-APR-18:02 | 0.00 | 0.00 | 0.00 |
May | 0.214729E+10 | 0.00 | 692.10 | 0.184409E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2905.52 | 28-MAY-08:62 | 2544.95 | 06-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.279554E+10 | 0.00 | 694.46 | 0.232467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2891.07 | 28-JUN-08:62 | 2553.68 | 28-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.293616E+10 | 0.00 | 717.12 | 0.219757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3366.81 | 19-JUL-08:62 | 2565.29 | 23-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.267695E+10 | 0.00 | 709.74 | 0.200729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3067.77 | 17-AUG-08:62 | 2548.90 | 28-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.237679E+10 | 0.00 | 681.02 | 0.176478E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3166.88 | 04-SEP-08:62 | 2537.81 | 01-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.147206E+10 | 0.00 | 602.19 | 0.110013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3118.72 | 15-OCT-08:62 | 2561.54 | 08-OCT-18:02 | 0.00 | 0.00 | 0.00 |
November | 0.515732E+09 | 0.00 | 307.31 | 0.464034E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2544.77 | 08-NOV-16:02 | 2544.77 | 08-NOV-16:02 | 0.00 | 0.00 | 0.00 |
December | 0.117624E+09 | 0.00 | 101.33 | 0.111159E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2544.51 | 09-DEC-16:01 | 2544.51 | 09-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.174781E+11 | 0.00 | 5731.25 | 0.141128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.117624E+09 | 0.00 | 101.33 | 0.111159E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2544.51 | 2537.81 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.293616E+10 | 0.00 | 717.12 | 0.232467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3366.81 | 2565.29 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 28539514.53 | 0.00 | 25.74 | 23597558.61 | 0.00 | 0.00 | 0.00 | 0.00 | 2458.68 | 30-JAN-16:02 | 2458.68 | 30-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 46436936.76 | 0.00 | 53.97 | 45662147.91 | 0.00 | 0.00 | 0.00 | 0.00 | 2524.91 | 05-FEB-16:02 | 2524.91 | 05-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.172794E+09 | 0.00 | 152.86 | 0.168887E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2547.76 | 11-MAR-16:02 | 2526.84 | 26-MAR-20:12 | 0.00 | 0.00 | 0.00 |
April | 0.102601E+10 | 0.00 | 457.67 | 0.940103E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2823.85 | 06-APR-18:11 | 2823.85 | 06-APR-18:11 | 0.00 | 0.00 | 0.00 |
May | 0.197599E+10 | 0.00 | 591.26 | 0.171102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2999.59 | 28-MAY-08:51 | 2726.88 | 20-MAY-08:51 | 0.00 | 0.00 | 0.00 |
June | 0.271934E+10 | 0.00 | 621.32 | 0.229555E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3050.41 | 04-JUN-08:51 | 2832.65 | 19-JUN-18:51 | 0.00 | 0.00 | 0.00 |
July | 0.281450E+10 | 0.00 | 637.31 | 0.215129E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3478.24 | 21-JUL-08:51 | 2661.97 | 11-JUL-07:52 | 0.00 | 0.00 | 0.00 |
August | 0.241382E+10 | 0.00 | 610.09 | 0.182906E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3367.25 | 03-AUG-08:61 | 2662.34 | 26-AUG-08:11 | 0.00 | 0.00 | 0.00 |
September | 0.184544E+10 | 0.00 | 543.98 | 0.135882E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3295.65 | 03-SEP-08:51 | 2677.22 | 09-SEP-17:52 | 0.00 | 0.00 | 0.00 |
October | 0.746100E+09 | 0.00 | 399.07 | 0.501947E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3097.36 | 03-OCT-21:51 | 2568.35 | 03-OCT-18:21 | 0.00 | 0.00 | 0.00 |
November | 96235500.21 | 0.00 | 99.03 | 76362068.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2611.12 | 02-NOV-15:02 | 2524.96 | 08-NOV-16:02 | 0.00 | 0.00 | 0.00 |
December | 11706793.51 | 0.00 | 12.10 | 10876396.57 | 0.00 | 0.00 | 0.00 | 0.00 | 2516.03 | 16-DEC-16:02 | 2516.03 | 16-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.138969E+11 | 0.00 | 4204.39 | 0.111132E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 11706793.51 | 0.00 | 12.10 | 10876396.57 | 0.00 | 0.00 | 0.00 | 0.00 | 2458.68 | 2458.68 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.281450E+10 | 0.00 | 637.31 | 0.229555E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3478.24 | 2832.65 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.482286E+10 | 0.00 | 402.64 | 0.444024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11528.12 | 04-JAN-16:02 | 11528.12 | 04-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 0.479676E+10 | 0.00 | 423.02 | 0.463741E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11528.22 | 20-FEB-09:02 | 11528.22 | 20-FEB-09:02 | 0.00 | 0.00 | 0.00 |
March | 0.473158E+10 | 0.00 | 494.39 | 0.461194E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11686.55 | 11-MAR-16:02 | 11528.52 | 14-MAR-18:02 | 0.00 | 0.00 | 0.00 |
April | 0.704963E+10 | 0.00 | 612.59 | 0.647860E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11950.12 | 18-APR-18:02 | 11528.64 | 21-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.930051E+10 | 0.00 | 691.16 | 0.770628E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12785.75 | 28-MAY-08:62 | 11571.74 | 24-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.121426E+11 | 0.00 | 687.37 | 0.984571E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12698.30 | 28-JUN-08:62 | 11595.00 | 28-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.135126E+11 | 0.00 | 710.48 | 0.988595E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15293.84 | 19-JUL-08:62 | 11578.79 | 29-JUL-08:62 | 0.00 | 0.00 | 0.00 |
August | 0.132676E+11 | 0.00 | 705.68 | 0.993087E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13353.33 | 02-AUG-08:62 | 11583.39 | 05-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.134862E+11 | 0.00 | 688.03 | 0.104156E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 14035.65 | 23-SEP-18:02 | 11611.34 | 05-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.111015E+11 | 0.00 | 674.25 | 0.909328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13420.55 | 15-OCT-08:62 | 11609.15 | 17-OCT-18:02 | 0.00 | 0.00 | 0.00 |
November | 0.710518E+10 | 0.00 | 491.78 | 0.668548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12087.22 | 03-NOV-08:62 | 11528.56 | 14-NOV-16:02 | 0.00 | 0.00 | 0.00 |
December | 0.439790E+10 | 0.00 | 378.66 | 0.410623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11528.24 | 23-DEC-16:02 | 11528.24 | 23-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.105715E+12 | 0.00 | 6960.05 | 0.878376E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.439790E+10 | 0.00 | 378.66 | 0.410623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11528.12 | 11528.12 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.135126E+11 | 0.00 | 710.48 | 0.104156E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 15293.84 | 11611.34 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 706.15 | 535.07 | 171.08 | 945.40 | 499.10 | 0.00 | 0.00 | 0.00 |
February | 664.38 | 471.17 | 193.21 | 908.61 | 441.73 | 0.00 | 0.00 | 0.00 |
March | 519.74 | 294.46 | 225.28 | 735.02 | 384.44 | 0.00 | 0.00 | 0.00 |
April | 362.15 | 135.95 | 226.20 | 582.55 | 228.87 | 0.00 | 0.00 | 0.00 |
May | 257.00 | 37.69 | 219.31 | 464.69 | 129.97 | 0.00 | 0.00 | 0.00 |
June | 219.82 | 13.83 | 205.99 | 487.18 | 61.58 | 0.00 | 0.00 | 0.00 |
July | 223.23 | 19.79 | 203.44 | 494.94 | 46.23 | 0.00 | 0.00 | 0.00 |
August | 281.79 | 71.59 | 210.20 | 581.96 | 70.38 | 0.00 | 0.00 | 0.00 |
September | 446.25 | 231.85 | 214.40 | 829.07 | 153.94 | 0.00 | 0.00 | 0.00 |
October | 612.55 | 416.17 | 196.38 | 971.45 | 252.42 | 0.00 | 0.00 | 0.00 |
November | 737.24 | 563.91 | 173.33 | 1034.04 | 423.10 | 0.00 | 0.00 | 0.00 |
December | 724.95 | 544.65 | 180.31 | 951.44 | 536.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 478.50 | 276.88 | 201.63 | 747.72 | 268.18 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 219.82 | 13.83 | 171.08 | 464.69 | 46.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 737.24 | 563.91 | 226.20 | 1034.04 | 536.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1988.48 | 1506.73 | 481.75 | 2616.70 | 1532.11 | 0.00 | 0.00 | 0.00 |
February | 1870.85 | 1326.79 | 544.06 | 2509.76 | 1361.98 | 0.00 | 0.00 | 0.00 |
March | 1463.55 | 829.18 | 634.37 | 2020.09 | 1189.69 | 0.00 | 0.00 | 0.00 |
April | 1019.80 | 382.82 | 636.98 | 1605.71 | 705.21 | 0.00 | 0.00 | 0.00 |
May | 723.68 | 106.13 | 617.55 | 1287.95 | 392.29 | 0.00 | 0.00 | 0.00 |
June | 618.99 | 38.95 | 580.04 | 1365.90 | 178.79 | 0.00 | 0.00 | 0.00 |
July | 628.60 | 55.73 | 572.87 | 1386.34 | 134.89 | 0.00 | 0.00 | 0.00 |
August | 793.51 | 201.60 | 591.90 | 1627.47 | 208.33 | 0.00 | 0.00 | 0.00 |
September | 1256.61 | 652.87 | 603.74 | 2317.02 | 446.85 | 0.00 | 0.00 | 0.00 |
October | 1724.89 | 1171.91 | 552.99 | 2706.63 | 757.81 | 0.00 | 0.00 | 0.00 |
November | 2076.02 | 1587.93 | 488.09 | 2869.16 | 1285.20 | 0.00 | 0.00 | 0.00 |
December | 2041.42 | 1533.69 | 507.73 | 2628.00 | 1637.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1347.44 | 779.68 | 567.76 | 2075.27 | 816.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 618.99 | 38.95 | 481.75 | 1287.95 | 134.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2076.02 | 1587.93 | 636.98 | 2869.16 | 1637.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2583.15 | 1957.32 | 625.82 | 3471.34 | 2041.31 | 0.00 | 0.00 | 0.00 |
February | 2430.34 | 1723.58 | 706.76 | 3335.01 | 1807.45 | 0.00 | 0.00 | 0.00 |
March | 1901.24 | 1077.15 | 824.09 | 2691.31 | 1580.35 | 0.00 | 0.00 | 0.00 |
April | 1324.78 | 497.31 | 827.47 | 2149.87 | 931.53 | 0.00 | 0.00 | 0.00 |
May | 940.11 | 137.87 | 802.24 | 1729.73 | 515.83 | 0.00 | 0.00 | 0.00 |
June | 804.10 | 50.59 | 753.51 | 1840.64 | 232.53 | 0.00 | 0.00 | 0.00 |
July | 816.59 | 72.40 | 744.19 | 1866.40 | 174.20 | 0.00 | 0.00 | 0.00 |
August | 1030.81 | 261.90 | 768.91 | 2182.69 | 269.43 | 0.00 | 0.00 | 0.00 |
September | 1632.41 | 848.12 | 784.29 | 3088.37 | 578.37 | 0.00 | 0.00 | 0.00 |
October | 2240.73 | 1522.37 | 718.36 | 3590.93 | 992.43 | 0.00 | 0.00 | 0.00 |
November | 2696.87 | 2062.81 | 634.06 | 3798.64 | 1706.39 | 0.00 | 0.00 | 0.00 |
December | 2651.92 | 1992.35 | 659.58 | 3485.01 | 2186.02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1750.40 | 1012.84 | 737.56 | 2765.06 | 1081.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 804.10 | 50.59 | 625.82 | 1729.73 | 174.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2696.87 | 2062.81 | 827.47 | 3798.64 | 2186.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 139.62 | 105.79 | 33.83 | 188.09 | 102.62 | 0.00 | 0.00 | 0.00 |
February | 131.36 | 93.16 | 38.20 | 180.94 | 90.19 | 0.00 | 0.00 | 0.00 |
March | 102.76 | 58.22 | 44.54 | 145.07 | 78.44 | 0.00 | 0.00 | 0.00 |
April | 71.60 | 26.88 | 44.73 | 118.34 | 41.79 | 0.00 | 0.00 | 0.00 |
May | 50.81 | 7.45 | 43.36 | 99.83 | 19.71 | 0.00 | 0.00 | 0.00 |
June | 43.46 | 2.73 | 40.73 | 111.83 | 6.89 | 0.00 | 0.00 | 0.00 |
July | 44.14 | 3.91 | 40.22 | 113.48 | 3.87 | 0.00 | 0.00 | 0.00 |
August | 55.72 | 14.16 | 41.56 | 128.17 | 7.76 | 0.00 | 0.00 | 0.00 |
September | 88.23 | 45.84 | 42.39 | 172.56 | 22.85 | 0.00 | 0.00 | 0.00 |
October | 121.11 | 82.28 | 38.83 | 197.24 | 44.91 | 0.00 | 0.00 | 0.00 |
November | 145.77 | 111.49 | 34.27 | 207.09 | 84.27 | 0.00 | 0.00 | 0.00 |
December | 143.34 | 107.69 | 35.65 | 190.11 | 110.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 94.61 | 54.74 | 39.87 | 154.20 | 51.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 43.46 | 2.73 | 33.83 | 99.83 | 3.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 145.77 | 111.49 | 44.73 | 207.09 | 110.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 107.40 | 60.54 | 46.87 | 112.82 | 212.72 | 0.00 | 0.00 | 0.00 |
February | 120.90 | 64.15 | 56.75 | 137.98 | 186.53 | 0.00 | 0.00 | 0.00 |
March | 164.97 | 88.46 | 76.51 | 211.46 | 152.26 | 0.00 | 0.00 | 0.00 |
April | 189.31 | 102.11 | 87.19 | 293.74 | 77.19 | 0.00 | 0.00 | 0.00 |
May | 204.29 | 109.33 | 94.96 | 361.42 | 36.48 | 0.00 | 0.00 | 0.00 |
June | 198.79 | 106.74 | 92.05 | 409.09 | 12.80 | 0.00 | 0.00 | 0.00 |
July | 176.54 | 87.72 | 88.82 | 369.94 | 7.00 | 0.00 | 0.00 | 0.00 |
August | 170.94 | 87.09 | 83.85 | 339.90 | 14.39 | 0.00 | 0.00 | 0.00 |
September | 175.49 | 97.97 | 77.52 | 318.57 | 43.25 | 0.00 | 0.00 | 0.00 |
October | 151.21 | 88.52 | 62.68 | 233.17 | 88.20 | 0.00 | 0.00 | 0.00 |
November | 126.16 | 76.76 | 49.40 | 152.92 | 174.90 | 0.00 | 0.00 | 0.00 |
December | 101.75 | 55.25 | 46.51 | 100.80 | 233.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 157.45 | 85.45 | 72.00 | 254.00 | 102.91 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.75 | 55.25 | 46.51 | 100.80 | 7.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 204.29 | 109.33 | 94.96 | 409.09 | 233.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.40 | 0.00 | 20.40 | 4.00 | 115.10 | 0.00 | 0.00 | 0.00 |
February | 24.91 | 0.00 | 24.91 | 11.32 | 101.02 | 0.00 | 0.00 | 0.00 |
March | 32.60 | 0.00 | 32.60 | 22.97 | 84.03 | 0.00 | 0.00 | 0.00 |
April | 37.86 | 0.48 | 37.38 | 48.21 | 42.26 | 0.00 | 0.00 | 0.00 |
May | 44.72 | 3.30 | 41.43 | 82.03 | 19.13 | 0.00 | 0.00 | 0.00 |
June | 47.56 | 5.93 | 41.63 | 116.48 | 6.88 | 0.00 | 0.00 | 0.00 |
July | 43.94 | 4.31 | 39.63 | 109.18 | 3.99 | 0.00 | 0.00 | 0.00 |
August | 37.16 | 0.88 | 36.28 | 85.57 | 8.07 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 0.04 | 32.29 | 61.30 | 24.34 | 0.00 | 0.00 | 0.00 |
October | 26.80 | 0.00 | 26.80 | 31.78 | 49.58 | 0.00 | 0.00 | 0.00 |
November | 21.63 | 0.00 | 21.63 | 8.10 | 95.34 | 0.00 | 0.00 | 0.00 |
December | 20.24 | 0.00 | 20.24 | 2.86 | 126.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.55 | 1.25 | 31.30 | 48.85 | 56.18 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.24 | 0.00 | 20.24 | 2.86 | 3.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 47.56 | 5.93 | 41.63 | 116.48 | 126.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 107.40 | 60.54 | 46.87 | 119.15 | 206.40 | 0.00 | 0.00 | 0.00 |
February | 120.90 | 64.15 | 56.75 | 143.59 | 182.46 | 0.00 | 0.00 | 0.00 |
March | 164.97 | 88.46 | 76.51 | 214.37 | 151.94 | 0.00 | 0.00 | 0.00 |
April | 189.31 | 102.11 | 87.19 | 293.90 | 79.33 | 0.00 | 0.00 | 0.00 |
May | 204.29 | 109.33 | 94.96 | 359.29 | 38.26 | 0.00 | 0.00 | 0.00 |
June | 198.79 | 106.74 | 92.05 | 405.76 | 13.47 | 0.00 | 0.00 | 0.00 |
July | 176.54 | 87.72 | 88.82 | 366.86 | 7.66 | 0.00 | 0.00 | 0.00 |
August | 170.94 | 87.09 | 83.85 | 338.45 | 15.57 | 0.00 | 0.00 | 0.00 |
September | 175.49 | 97.97 | 77.52 | 319.35 | 45.43 | 0.00 | 0.00 | 0.00 |
October | 151.21 | 88.52 | 62.68 | 235.46 | 90.64 | 0.00 | 0.00 | 0.00 |
November | 126.16 | 76.76 | 49.40 | 158.25 | 171.30 | 0.00 | 0.00 | 0.00 |
December | 101.75 | 55.25 | 46.51 | 107.12 | 227.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 157.45 | 85.45 | 72.00 | 255.62 | 102.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.75 | 55.25 | 46.51 | 107.12 | 7.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 204.29 | 109.33 | 94.96 | 405.76 | 227.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 111.67 | 84.62 | 27.06 | 136.01 | 112.95 | 0.00 | 0.00 | 0.00 |
February | 105.07 | 74.51 | 30.55 | 129.94 | 101.98 | 0.00 | 0.00 | 0.00 |
March | 82.19 | 46.57 | 35.63 | 101.18 | 89.81 | 0.00 | 0.00 | 0.00 |
April | 57.27 | 21.50 | 35.77 | 80.16 | 56.73 | 0.00 | 0.00 | 0.00 |
May | 40.64 | 5.96 | 34.68 | 63.13 | 34.06 | 0.00 | 0.00 | 0.00 |
June | 34.76 | 2.19 | 32.58 | 68.78 | 17.71 | 0.00 | 0.00 | 0.00 |
July | 35.30 | 3.13 | 32.17 | 69.45 | 15.08 | 0.00 | 0.00 | 0.00 |
August | 44.56 | 11.32 | 33.24 | 83.39 | 21.01 | 0.00 | 0.00 | 0.00 |
September | 70.57 | 36.67 | 33.91 | 123.39 | 37.86 | 0.00 | 0.00 | 0.00 |
October | 96.87 | 65.81 | 31.06 | 143.00 | 60.00 | 0.00 | 0.00 | 0.00 |
November | 116.59 | 89.18 | 27.41 | 151.16 | 95.54 | 0.00 | 0.00 | 0.00 |
December | 114.65 | 86.13 | 28.51 | 136.84 | 118.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 75.67 | 43.79 | 31.89 | 107.03 | 63.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.76 | 2.19 | 27.06 | 63.13 | 15.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 116.59 | 89.18 | 35.77 | 151.16 | 118.82 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.32 | 0.00 | 16.32 | 3.02 | 94.50 | 0.00 | 0.00 | 0.00 |
February | 19.93 | 0.00 | 19.93 | 9.48 | 81.91 | 0.00 | 0.00 | 0.00 |
March | 26.09 | 0.00 | 26.09 | 19.94 | 66.54 | 0.00 | 0.00 | 0.00 |
April | 30.29 | 0.39 | 29.91 | 42.15 | 31.97 | 0.00 | 0.00 | 0.00 |
May | 35.78 | 2.64 | 33.15 | 71.01 | 13.78 | 0.00 | 0.00 | 0.00 |
June | 38.05 | 4.74 | 33.31 | 100.07 | 4.49 | 0.00 | 0.00 | 0.00 |
July | 35.16 | 3.45 | 31.71 | 93.64 | 2.36 | 0.00 | 0.00 | 0.00 |
August | 29.73 | 0.71 | 29.03 | 74.29 | 5.34 | 0.00 | 0.00 | 0.00 |
September | 25.87 | 0.03 | 25.84 | 53.58 | 17.32 | 0.00 | 0.00 | 0.00 |
October | 21.44 | 0.00 | 21.44 | 28.15 | 37.37 | 0.00 | 0.00 | 0.00 |
November | 17.31 | 0.00 | 17.31 | 7.24 | 76.00 | 0.00 | 0.00 | 0.00 |
December | 16.19 | 0.00 | 16.19 | 2.07 | 104.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 26.04 | 1.00 | 25.04 | 42.23 | 44.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 16.19 | 0.00 | 16.19 | 2.07 | 2.36 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 38.05 | 4.74 | 33.31 | 100.07 | 104.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.70 | 55.11 | 46.60 | 93.61 | 202.01 | 0.00 | 0.00 | 0.00 |
February | 136.50 | 77.83 | 58.67 | 151.16 | 173.40 | 0.00 | 0.00 | 0.00 |
March | 168.25 | 92.64 | 75.61 | 206.93 | 139.99 | 0.00 | 0.00 | 0.00 |
April | 202.82 | 112.49 | 90.33 | 309.90 | 69.61 | 0.00 | 0.00 | 0.00 |
May | 209.08 | 113.58 | 95.50 | 368.60 | 33.02 | 0.00 | 0.00 | 0.00 |
June | 209.17 | 116.31 | 92.86 | 427.07 | 11.89 | 0.00 | 0.00 | 0.00 |
July | 187.70 | 98.13 | 89.57 | 389.30 | 6.73 | 0.00 | 0.00 | 0.00 |
August | 178.80 | 91.56 | 87.24 | 354.35 | 13.48 | 0.00 | 0.00 | 0.00 |
September | 177.40 | 101.30 | 76.10 | 317.93 | 39.39 | 0.00 | 0.00 | 0.00 |
October | 135.78 | 73.14 | 62.64 | 200.66 | 82.34 | 0.00 | 0.00 | 0.00 |
November | 121.58 | 70.62 | 50.96 | 132.56 | 162.74 | 0.00 | 0.00 | 0.00 |
December | 101.78 | 53.93 | 47.85 | 89.50 | 221.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 160.90 | 88.01 | 72.89 | 253.83 | 96.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.70 | 53.93 | 46.60 | 89.50 | 6.73 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 209.17 | 116.31 | 95.50 | 427.07 | 221.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 139.62 | 105.79 | 33.83 | 187.34 | 102.08 | 0.00 | 0.00 | 0.00 |
February | 131.36 | 93.16 | 38.20 | 179.33 | 89.98 | 0.00 | 0.00 | 0.00 |
March | 102.76 | 58.22 | 44.54 | 143.50 | 77.97 | 0.00 | 0.00 | 0.00 |
April | 71.60 | 26.88 | 44.73 | 117.04 | 41.69 | 0.00 | 0.00 | 0.00 |
May | 50.81 | 7.45 | 43.36 | 99.19 | 19.48 | 0.00 | 0.00 | 0.00 |
June | 43.46 | 2.73 | 40.73 | 111.15 | 6.69 | 0.00 | 0.00 | 0.00 |
July | 44.14 | 3.91 | 40.22 | 112.88 | 3.72 | 0.00 | 0.00 | 0.00 |
August | 55.72 | 14.16 | 41.56 | 127.79 | 7.61 | 0.00 | 0.00 | 0.00 |
September | 88.23 | 45.84 | 42.39 | 172.10 | 22.50 | 0.00 | 0.00 | 0.00 |
October | 121.11 | 82.28 | 38.83 | 196.99 | 44.10 | 0.00 | 0.00 | 0.00 |
November | 145.77 | 111.49 | 34.27 | 206.35 | 83.62 | 0.00 | 0.00 | 0.00 |
December | 143.34 | 107.69 | 35.65 | 189.32 | 110.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 94.61 | 54.74 | 39.87 | 153.39 | 50.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 43.46 | 2.73 | 33.83 | 99.19 | 3.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 145.77 | 111.49 | 44.73 | 206.35 | 110.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.40 | 0.00 | 20.40 | 3.71 | 114.66 | 0.00 | 0.00 | 0.00 |
February | 24.91 | 0.00 | 24.91 | 10.56 | 101.22 | 0.00 | 0.00 | 0.00 |
March | 32.60 | 0.00 | 32.60 | 21.98 | 83.57 | 0.00 | 0.00 | 0.00 |
April | 37.86 | 0.48 | 37.38 | 46.44 | 41.93 | 0.00 | 0.00 | 0.00 |
May | 44.72 | 3.30 | 41.43 | 79.95 | 18.78 | 0.00 | 0.00 | 0.00 |
June | 47.56 | 5.93 | 41.63 | 114.58 | 6.73 | 0.00 | 0.00 | 0.00 |
July | 43.94 | 4.31 | 39.63 | 107.58 | 3.87 | 0.00 | 0.00 | 0.00 |
August | 37.16 | 0.88 | 36.28 | 84.10 | 7.91 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 0.04 | 32.29 | 59.76 | 24.23 | 0.00 | 0.00 | 0.00 |
October | 26.80 | 0.00 | 26.80 | 31.28 | 48.08 | 0.00 | 0.00 | 0.00 |
November | 21.63 | 0.00 | 21.63 | 7.61 | 94.35 | 0.00 | 0.00 | 0.00 |
December | 20.24 | 0.00 | 20.24 | 2.56 | 126.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.55 | 1.25 | 31.30 | 47.71 | 55.80 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.24 | 0.00 | 20.24 | 2.56 | 3.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 47.56 | 5.93 | 41.63 | 114.58 | 126.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.70 | 55.11 | 46.60 | 98.52 | 193.44 | 0.00 | 0.00 | 0.00 |
February | 136.50 | 77.83 | 58.67 | 156.46 | 168.19 | 0.00 | 0.00 | 0.00 |
March | 168.25 | 92.64 | 75.61 | 210.39 | 138.85 | 0.00 | 0.00 | 0.00 |
April | 202.82 | 112.49 | 90.33 | 309.26 | 71.42 | 0.00 | 0.00 | 0.00 |
May | 209.08 | 113.58 | 95.50 | 363.21 | 34.57 | 0.00 | 0.00 | 0.00 |
June | 209.17 | 116.31 | 92.86 | 420.61 | 12.43 | 0.00 | 0.00 | 0.00 |
July | 187.70 | 98.13 | 89.57 | 383.71 | 7.32 | 0.00 | 0.00 | 0.00 |
August | 178.80 | 91.56 | 87.24 | 350.07 | 14.42 | 0.00 | 0.00 | 0.00 |
September | 177.40 | 101.30 | 76.10 | 315.37 | 41.22 | 0.00 | 0.00 | 0.00 |
October | 135.78 | 73.14 | 62.64 | 203.10 | 83.79 | 0.00 | 0.00 | 0.00 |
November | 121.58 | 70.62 | 50.96 | 137.67 | 157.67 | 0.00 | 0.00 | 0.00 |
December | 101.78 | 53.93 | 47.85 | 93.56 | 212.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 160.90 | 88.01 | 72.89 | 253.83 | 94.28 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.70 | 53.93 | 46.60 | 93.56 | 7.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 209.17 | 116.31 | 95.50 | 420.61 | 212.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 25.83 | 0.00 | 25.83 | 4.54 | 146.59 | 0.00 | 0.00 | 0.00 |
February | 31.55 | 0.00 | 31.55 | 14.26 | 128.39 | 0.00 | 0.00 | 0.00 |
March | 41.29 | 0.00 | 41.29 | 30.77 | 105.12 | 0.00 | 0.00 | 0.00 |
April | 47.95 | 0.61 | 47.34 | 62.55 | 55.36 | 0.00 | 0.00 | 0.00 |
May | 56.64 | 4.17 | 52.47 | 102.52 | 28.43 | 0.00 | 0.00 | 0.00 |
June | 60.23 | 7.51 | 52.73 | 140.80 | 12.86 | 0.00 | 0.00 | 0.00 |
July | 55.65 | 5.46 | 50.19 | 130.61 | 9.02 | 0.00 | 0.00 | 0.00 |
August | 47.06 | 1.12 | 45.94 | 102.19 | 14.86 | 0.00 | 0.00 | 0.00 |
September | 40.94 | 0.05 | 40.89 | 74.89 | 36.63 | 0.00 | 0.00 | 0.00 |
October | 33.94 | 0.00 | 33.94 | 39.13 | 66.06 | 0.00 | 0.00 | 0.00 |
November | 27.40 | 0.00 | 27.40 | 9.46 | 124.16 | 0.00 | 0.00 | 0.00 |
December | 25.63 | 0.00 | 25.63 | 3.15 | 160.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 41.22 | 1.58 | 39.64 | 59.81 | 73.76 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.63 | 0.00 | 25.63 | 3.15 | 9.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 60.23 | 7.51 | 52.73 | 140.80 | 160.82 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 9.52 | 0.00 | 9.52 | 1.67 | 54.04 | 0.00 | 0.00 | 0.00 |
February | 11.63 | 0.00 | 11.63 | 5.26 | 47.33 | 0.00 | 0.00 | 0.00 |
March | 15.22 | 0.00 | 15.22 | 11.34 | 38.75 | 0.00 | 0.00 | 0.00 |
April | 17.68 | 0.23 | 17.45 | 23.06 | 20.41 | 0.00 | 0.00 | 0.00 |
May | 20.88 | 1.54 | 19.34 | 37.79 | 10.48 | 0.00 | 0.00 | 0.00 |
June | 22.20 | 2.77 | 19.44 | 51.91 | 4.74 | 0.00 | 0.00 | 0.00 |
July | 20.51 | 2.01 | 18.50 | 48.15 | 3.32 | 0.00 | 0.00 | 0.00 |
August | 17.35 | 0.41 | 16.94 | 37.67 | 5.48 | 0.00 | 0.00 | 0.00 |
September | 15.09 | 0.02 | 15.07 | 27.61 | 13.50 | 0.00 | 0.00 | 0.00 |
October | 12.51 | 0.00 | 12.51 | 14.42 | 24.35 | 0.00 | 0.00 | 0.00 |
November | 10.10 | 0.00 | 10.10 | 3.49 | 45.77 | 0.00 | 0.00 | 0.00 |
December | 9.45 | 0.00 | 9.45 | 1.16 | 59.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 15.20 | 0.58 | 14.61 | 22.05 | 27.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 9.45 | 0.00 | 9.45 | 1.16 | 3.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 22.20 | 2.77 | 19.44 | 51.91 | 59.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 65.15 | 49.36 | 15.78 | 89.28 | 46.91 | 0.00 | 0.00 | 0.00 |
February | 61.29 | 43.47 | 17.82 | 85.84 | 41.54 | 0.00 | 0.00 | 0.00 |
March | 47.95 | 27.17 | 20.78 | 69.13 | 36.37 | 0.00 | 0.00 | 0.00 |
April | 33.41 | 12.54 | 20.87 | 55.78 | 20.84 | 0.00 | 0.00 | 0.00 |
May | 23.71 | 3.48 | 20.23 | 45.54 | 11.27 | 0.00 | 0.00 | 0.00 |
June | 20.28 | 1.28 | 19.00 | 48.87 | 4.96 | 0.00 | 0.00 | 0.00 |
July | 20.59 | 1.83 | 18.77 | 49.34 | 3.50 | 0.00 | 0.00 | 0.00 |
August | 26.00 | 6.60 | 19.39 | 57.01 | 5.69 | 0.00 | 0.00 | 0.00 |
September | 41.17 | 21.39 | 19.78 | 79.14 | 13.34 | 0.00 | 0.00 | 0.00 |
October | 56.51 | 38.39 | 18.12 | 91.83 | 22.89 | 0.00 | 0.00 | 0.00 |
November | 68.01 | 52.02 | 15.99 | 97.49 | 39.78 | 0.00 | 0.00 | 0.00 |
December | 66.88 | 50.25 | 16.63 | 90.25 | 50.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 44.14 | 25.54 | 18.60 | 71.52 | 24.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.28 | 1.28 | 15.78 | 45.54 | 3.50 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 68.01 | 52.02 | 20.87 | 97.49 | 50.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 176.82 | 133.98 | 42.84 | 242.33 | 127.33 | 0.00 | 0.00 | 0.00 |
February | 166.36 | 117.98 | 48.38 | 232.98 | 112.76 | 0.00 | 0.00 | 0.00 |
March | 130.14 | 73.73 | 56.41 | 187.63 | 98.71 | 0.00 | 0.00 | 0.00 |
April | 90.68 | 34.04 | 56.64 | 151.39 | 56.56 | 0.00 | 0.00 | 0.00 |
May | 64.35 | 9.44 | 54.91 | 123.61 | 30.60 | 0.00 | 0.00 | 0.00 |
June | 55.04 | 3.46 | 51.58 | 132.64 | 13.47 | 0.00 | 0.00 | 0.00 |
July | 55.90 | 4.96 | 50.94 | 133.92 | 9.50 | 0.00 | 0.00 | 0.00 |
August | 70.56 | 17.93 | 52.63 | 154.74 | 15.45 | 0.00 | 0.00 | 0.00 |
September | 111.74 | 58.05 | 53.69 | 214.79 | 36.19 | 0.00 | 0.00 | 0.00 |
October | 153.38 | 104.21 | 49.17 | 249.25 | 62.12 | 0.00 | 0.00 | 0.00 |
November | 184.60 | 141.20 | 43.40 | 264.61 | 107.97 | 0.00 | 0.00 | 0.00 |
December | 181.53 | 136.38 | 45.15 | 244.97 | 136.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 119.82 | 69.33 | 50.49 | 194.13 | 67.06 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 55.04 | 3.46 | 42.84 | 123.61 | 9.50 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 184.60 | 141.20 | 56.64 | 264.61 | 136.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 139.62 | 105.79 | 33.83 | 187.01 | 101.48 | 0.00 | 0.00 | 0.00 |
February | 131.36 | 93.16 | 38.20 | 179.80 | 89.05 | 0.00 | 0.00 | 0.00 |
March | 102.76 | 58.22 | 44.54 | 143.77 | 77.41 | 0.00 | 0.00 | 0.00 |
April | 71.60 | 26.88 | 44.73 | 117.17 | 40.84 | 0.00 | 0.00 | 0.00 |
May | 50.81 | 7.45 | 43.36 | 99.29 | 18.88 | 0.00 | 0.00 | 0.00 |
June | 43.46 | 2.73 | 40.73 | 111.64 | 6.42 | 0.00 | 0.00 | 0.00 |
July | 44.14 | 3.91 | 40.22 | 113.04 | 3.55 | 0.00 | 0.00 | 0.00 |
August | 55.72 | 14.16 | 41.56 | 127.48 | 7.28 | 0.00 | 0.00 | 0.00 |
September | 88.23 | 45.84 | 42.39 | 171.22 | 22.03 | 0.00 | 0.00 | 0.00 |
October | 121.11 | 82.28 | 38.83 | 195.86 | 43.94 | 0.00 | 0.00 | 0.00 |
November | 145.77 | 111.49 | 34.27 | 206.08 | 82.91 | 0.00 | 0.00 | 0.00 |
December | 143.34 | 107.69 | 35.65 | 189.47 | 109.70 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 94.61 | 54.74 | 39.87 | 153.29 | 50.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 43.46 | 2.73 | 33.83 | 99.29 | 3.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 145.77 | 111.49 | 44.73 | 206.08 | 109.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 107.40 | 60.54 | 46.87 | 111.85 | 209.93 | 0.00 | 0.00 | 0.00 |
February | 120.90 | 64.15 | 56.75 | 136.70 | 183.74 | 0.00 | 0.00 | 0.00 |
March | 164.97 | 88.46 | 76.51 | 209.31 | 149.86 | 0.00 | 0.00 | 0.00 |
April | 189.31 | 102.11 | 87.19 | 291.10 | 75.29 | 0.00 | 0.00 | 0.00 |
May | 204.29 | 109.33 | 94.96 | 358.69 | 34.90 | 0.00 | 0.00 | 0.00 |
June | 198.79 | 106.74 | 92.05 | 406.86 | 11.99 | 0.00 | 0.00 | 0.00 |
July | 176.54 | 87.72 | 88.82 | 367.81 | 6.43 | 0.00 | 0.00 | 0.00 |
August | 170.94 | 87.09 | 83.85 | 337.88 | 13.50 | 0.00 | 0.00 | 0.00 |
September | 175.49 | 97.97 | 77.52 | 316.25 | 41.68 | 0.00 | 0.00 | 0.00 |
October | 151.21 | 88.52 | 62.68 | 231.51 | 86.02 | 0.00 | 0.00 | 0.00 |
November | 126.16 | 76.76 | 49.40 | 151.84 | 171.58 | 0.00 | 0.00 | 0.00 |
December | 101.75 | 55.25 | 46.51 | 100.31 | 230.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 157.45 | 85.45 | 72.00 | 252.18 | 100.91 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.75 | 55.25 | 46.51 | 100.31 | 6.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 204.29 | 109.33 | 94.96 | 406.86 | 230.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.40 | 0.00 | 20.40 | 4.32 | 113.31 | 0.00 | 0.00 | 0.00 |
February | 24.91 | 0.00 | 24.91 | 11.62 | 99.32 | 0.00 | 0.00 | 0.00 |
March | 32.60 | 0.00 | 32.60 | 23.12 | 82.89 | 0.00 | 0.00 | 0.00 |
April | 37.86 | 0.48 | 37.38 | 47.93 | 41.45 | 0.00 | 0.00 | 0.00 |
May | 44.72 | 3.30 | 41.43 | 81.77 | 18.41 | 0.00 | 0.00 | 0.00 |
June | 47.56 | 5.93 | 41.63 | 116.10 | 6.47 | 0.00 | 0.00 | 0.00 |
July | 43.94 | 4.31 | 39.63 | 108.72 | 3.69 | 0.00 | 0.00 | 0.00 |
August | 37.16 | 0.88 | 36.28 | 85.39 | 7.60 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 0.04 | 32.29 | 61.02 | 23.44 | 0.00 | 0.00 | 0.00 |
October | 26.80 | 0.00 | 26.80 | 31.82 | 48.57 | 0.00 | 0.00 | 0.00 |
November | 21.63 | 0.00 | 21.63 | 8.53 | 93.36 | 0.00 | 0.00 | 0.00 |
December | 20.24 | 0.00 | 20.24 | 3.13 | 124.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.55 | 1.25 | 31.30 | 48.82 | 55.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.24 | 0.00 | 20.24 | 3.13 | 3.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 47.56 | 5.93 | 41.63 | 116.10 | 124.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 107.40 | 60.54 | 46.87 | 119.10 | 203.26 | 0.00 | 0.00 | 0.00 |
February | 120.90 | 64.15 | 56.75 | 143.11 | 179.39 | 0.00 | 0.00 | 0.00 |
March | 164.97 | 88.46 | 76.51 | 212.63 | 149.66 | 0.00 | 0.00 | 0.00 |
April | 189.31 | 102.11 | 87.19 | 291.35 | 77.67 | 0.00 | 0.00 | 0.00 |
May | 204.29 | 109.33 | 94.96 | 356.67 | 36.70 | 0.00 | 0.00 | 0.00 |
June | 198.79 | 106.74 | 92.05 | 403.55 | 12.62 | 0.00 | 0.00 | 0.00 |
July | 176.54 | 87.72 | 88.82 | 364.75 | 7.06 | 0.00 | 0.00 | 0.00 |
August | 170.94 | 87.09 | 83.85 | 336.55 | 14.63 | 0.00 | 0.00 | 0.00 |
September | 175.49 | 97.97 | 77.52 | 317.38 | 43.70 | 0.00 | 0.00 | 0.00 |
October | 151.21 | 88.52 | 62.68 | 234.18 | 88.60 | 0.00 | 0.00 | 0.00 |
November | 126.16 | 76.76 | 49.40 | 158.15 | 167.47 | 0.00 | 0.00 | 0.00 |
December | 101.75 | 55.25 | 46.51 | 107.51 | 223.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 157.45 | 85.45 | 72.00 | 254.23 | 99.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.75 | 55.25 | 46.51 | 107.51 | 7.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 204.29 | 109.33 | 94.96 | 403.55 | 223.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 204.76 | 155.16 | 49.61 | 266.88 | 155.78 | 0.00 | 0.00 | 0.00 |
February | 192.65 | 136.63 | 56.02 | 257.54 | 135.84 | 0.00 | 0.00 | 0.00 |
March | 150.71 | 85.38 | 65.33 | 207.52 | 115.34 | 0.00 | 0.00 | 0.00 |
April | 105.01 | 39.42 | 65.59 | 173.32 | 58.86 | 0.00 | 0.00 | 0.00 |
May | 74.52 | 10.93 | 63.59 | 151.60 | 26.13 | 0.00 | 0.00 | 0.00 |
June | 63.74 | 4.01 | 59.73 | 171.89 | 8.37 | 0.00 | 0.00 | 0.00 |
July | 64.73 | 5.74 | 58.99 | 172.68 | 4.44 | 0.00 | 0.00 | 0.00 |
August | 81.71 | 20.76 | 60.95 | 192.26 | 9.83 | 0.00 | 0.00 | 0.00 |
September | 129.40 | 67.23 | 62.17 | 253.22 | 31.25 | 0.00 | 0.00 | 0.00 |
October | 177.62 | 120.68 | 56.94 | 285.55 | 65.18 | 0.00 | 0.00 | 0.00 |
November | 213.78 | 163.52 | 50.26 | 296.88 | 126.17 | 0.00 | 0.00 | 0.00 |
December | 210.22 | 157.93 | 52.28 | 269.53 | 168.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 138.75 | 80.29 | 58.47 | 224.65 | 75.18 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 63.74 | 4.01 | 49.61 | 151.60 | 4.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 213.78 | 163.52 | 65.59 | 296.88 | 168.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 142.78 | 0.00 | 142.78 | 10.95 | 941.09 | 0.00 | 0.00 | 0.00 |
February | 174.35 | 0.00 | 174.35 | 53.41 | 817.97 | 0.00 | 0.00 | 0.00 |
March | 228.22 | 0.01 | 228.21 | 129.21 | 667.73 | 0.00 | 0.00 | 0.00 |
April | 265.01 | 3.38 | 261.64 | 298.92 | 352.02 | 0.00 | 0.00 | 0.00 |
May | 313.05 | 23.07 | 289.98 | 524.71 | 178.68 | 0.00 | 0.00 | 0.00 |
June | 332.91 | 41.48 | 291.42 | 748.96 | 81.44 | 0.00 | 0.00 | 0.00 |
July | 307.56 | 30.17 | 277.39 | 690.02 | 61.40 | 0.00 | 0.00 | 0.00 |
August | 260.12 | 6.19 | 253.93 | 535.40 | 96.09 | 0.00 | 0.00 | 0.00 |
September | 226.30 | 0.29 | 226.02 | 391.55 | 216.69 | 0.00 | 0.00 | 0.00 |
October | 187.59 | 0.00 | 187.59 | 188.97 | 404.98 | 0.00 | 0.00 | 0.00 |
November | 151.44 | 0.00 | 151.44 | 34.76 | 770.49 | 0.00 | 0.00 | 0.00 |
December | 141.68 | 0.00 | 141.68 | 7.80 | 1024.56 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 227.84 | 8.76 | 219.09 | 302.52 | 466.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 141.68 | 0.00 | 141.68 | 7.80 | 61.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 332.91 | 41.48 | 291.42 | 748.96 | 1024.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 142.78 | 0.00 | 142.78 | 8.13 | 970.36 | 0.00 | 0.00 | 0.00 |
February | 174.35 | 0.00 | 174.35 | 47.49 | 841.30 | 0.00 | 0.00 | 0.00 |
March | 228.22 | 0.01 | 228.21 | 119.70 | 685.59 | 0.00 | 0.00 | 0.00 |
April | 265.01 | 3.38 | 261.64 | 289.72 | 362.24 | 0.00 | 0.00 | 0.00 |
May | 313.05 | 23.07 | 289.98 | 515.56 | 184.74 | 0.00 | 0.00 | 0.00 |
June | 332.91 | 41.48 | 291.42 | 739.64 | 85.02 | 0.00 | 0.00 | 0.00 |
July | 307.56 | 30.17 | 277.39 | 680.80 | 64.95 | 0.00 | 0.00 | 0.00 |
August | 260.12 | 6.19 | 253.93 | 526.67 | 100.60 | 0.00 | 0.00 | 0.00 |
September | 226.30 | 0.29 | 226.02 | 384.73 | 223.64 | 0.00 | 0.00 | 0.00 |
October | 187.59 | 0.00 | 187.59 | 181.71 | 416.30 | 0.00 | 0.00 | 0.00 |
November | 151.44 | 0.00 | 151.44 | 29.69 | 792.30 | 0.00 | 0.00 | 0.00 |
December | 141.68 | 0.00 | 141.68 | 5.92 | 1055.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 227.84 | 8.76 | 219.09 | 295.44 | 480.22 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 141.68 | 0.00 | 141.68 | 5.92 | 64.95 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 332.91 | 41.48 | 291.42 | 739.64 | 1055.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.40 | 0.00 | 20.40 | 3.62 | 123.89 | 0.00 | 0.00 | 0.00 |
February | 24.91 | 0.00 | 24.91 | 12.45 | 108.62 | 0.00 | 0.00 | 0.00 |
March | 32.60 | 0.00 | 32.60 | 25.84 | 90.48 | 0.00 | 0.00 | 0.00 |
April | 37.86 | 0.48 | 37.38 | 56.73 | 49.26 | 0.00 | 0.00 | 0.00 |
May | 44.72 | 3.30 | 41.43 | 93.06 | 27.36 | 0.00 | 0.00 | 0.00 |
June | 47.56 | 5.93 | 41.63 | 127.99 | 13.87 | 0.00 | 0.00 | 0.00 |
July | 43.94 | 4.31 | 39.63 | 120.32 | 11.01 | 0.00 | 0.00 | 0.00 |
August | 37.16 | 0.88 | 36.28 | 97.28 | 15.49 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 0.04 | 32.29 | 74.66 | 29.83 | 0.00 | 0.00 | 0.00 |
October | 26.80 | 0.00 | 26.80 | 39.25 | 53.98 | 0.00 | 0.00 | 0.00 |
November | 21.63 | 0.00 | 21.63 | 9.77 | 101.08 | 0.00 | 0.00 | 0.00 |
December | 20.24 | 0.00 | 20.24 | 2.65 | 134.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.55 | 1.25 | 31.30 | 55.52 | 63.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.24 | 0.00 | 20.24 | 2.65 | 11.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 47.56 | 5.93 | 41.63 | 127.99 | 134.00 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 203.40 | 110.21 | 93.19 | 199.83 | 423.07 | 0.00 | 0.00 | 0.00 |
February | 272.98 | 155.65 | 117.32 | 325.20 | 368.30 | 0.00 | 0.00 | 0.00 |
March | 336.47 | 185.26 | 151.21 | 441.82 | 306.97 | 0.00 | 0.00 | 0.00 |
April | 405.62 | 224.97 | 180.65 | 659.03 | 172.93 | 0.00 | 0.00 | 0.00 |
May | 418.14 | 227.15 | 190.99 | 774.16 | 101.37 | 0.00 | 0.00 | 0.00 |
June | 418.31 | 232.60 | 185.71 | 887.71 | 51.88 | 0.00 | 0.00 | 0.00 |
July | 375.38 | 196.25 | 179.13 | 810.91 | 41.67 | 0.00 | 0.00 | 0.00 |
August | 357.58 | 183.11 | 174.47 | 746.99 | 57.98 | 0.00 | 0.00 | 0.00 |
September | 354.77 | 202.59 | 152.18 | 687.86 | 107.15 | 0.00 | 0.00 | 0.00 |
October | 271.54 | 146.27 | 125.28 | 438.13 | 192.49 | 0.00 | 0.00 | 0.00 |
November | 243.14 | 141.22 | 101.92 | 287.63 | 343.23 | 0.00 | 0.00 | 0.00 |
December | 203.55 | 107.86 | 95.69 | 191.99 | 455.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 321.77 | 176.00 | 145.77 | 538.33 | 217.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 203.40 | 107.86 | 93.19 | 191.99 | 41.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 418.31 | 232.60 | 190.99 | 887.71 | 455.14 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 139.62 | 105.79 | 33.83 | 193.55 | 108.94 | 0.00 | 0.00 | 0.00 |
February | 131.36 | 93.16 | 38.20 | 186.93 | 96.76 | 0.00 | 0.00 | 0.00 |
March | 102.76 | 58.22 | 44.54 | 151.18 | 85.07 | 0.00 | 0.00 | 0.00 |
April | 71.60 | 26.88 | 44.73 | 126.52 | 50.00 | 0.00 | 0.00 | 0.00 |
May | 50.81 | 7.45 | 43.36 | 108.55 | 28.71 | 0.00 | 0.00 | 0.00 |
June | 43.46 | 2.73 | 40.73 | 120.85 | 14.10 | 0.00 | 0.00 | 0.00 |
July | 44.14 | 3.91 | 40.22 | 122.41 | 11.21 | 0.00 | 0.00 | 0.00 |
August | 55.72 | 14.16 | 41.56 | 138.65 | 15.78 | 0.00 | 0.00 | 0.00 |
September | 88.23 | 45.84 | 42.39 | 185.60 | 29.68 | 0.00 | 0.00 | 0.00 |
October | 121.11 | 82.28 | 38.83 | 207.09 | 51.53 | 0.00 | 0.00 | 0.00 |
November | 145.77 | 111.49 | 34.27 | 214.75 | 89.40 | 0.00 | 0.00 | 0.00 |
December | 143.34 | 107.69 | 35.65 | 196.07 | 115.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 94.61 | 54.74 | 39.87 | 162.49 | 57.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 43.46 | 2.73 | 33.83 | 108.55 | 11.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 145.77 | 111.49 | 44.73 | 214.75 | 115.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 25.83 | 0.00 | 25.83 | 3.62 | 148.32 | 0.00 | 0.00 | 0.00 |
February | 31.55 | 0.00 | 31.55 | 12.72 | 129.19 | 0.00 | 0.00 | 0.00 |
March | 41.29 | 0.00 | 41.29 | 28.73 | 105.29 | 0.00 | 0.00 | 0.00 |
April | 47.95 | 0.61 | 47.34 | 58.80 | 56.60 | 0.00 | 0.00 | 0.00 |
May | 56.64 | 4.17 | 52.47 | 97.76 | 29.87 | 0.00 | 0.00 | 0.00 |
June | 60.23 | 7.51 | 52.73 | 135.85 | 13.94 | 0.00 | 0.00 | 0.00 |
July | 55.65 | 5.46 | 50.19 | 125.06 | 10.36 | 0.00 | 0.00 | 0.00 |
August | 47.06 | 1.12 | 45.94 | 97.27 | 16.29 | 0.00 | 0.00 | 0.00 |
September | 40.94 | 0.05 | 40.89 | 71.24 | 37.93 | 0.00 | 0.00 | 0.00 |
October | 33.94 | 0.00 | 33.94 | 36.37 | 66.77 | 0.00 | 0.00 | 0.00 |
November | 27.40 | 0.00 | 27.40 | 8.32 | 123.23 | 0.00 | 0.00 | 0.00 |
December | 25.63 | 0.00 | 25.63 | 2.58 | 163.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 41.22 | 1.58 | 39.64 | 56.76 | 74.81 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.63 | 0.00 | 25.63 | 2.58 | 10.36 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 60.23 | 7.51 | 52.73 | 135.85 | 163.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.11 | 0.00 | 23.11 | 3.24 | 132.70 | 0.00 | 0.00 | 0.00 |
February | 28.22 | 0.00 | 28.22 | 11.38 | 115.59 | 0.00 | 0.00 | 0.00 |
March | 36.94 | 0.00 | 36.94 | 25.71 | 94.20 | 0.00 | 0.00 | 0.00 |
April | 42.90 | 0.55 | 42.35 | 52.61 | 50.64 | 0.00 | 0.00 | 0.00 |
May | 50.68 | 3.73 | 46.94 | 87.47 | 26.72 | 0.00 | 0.00 | 0.00 |
June | 53.89 | 6.72 | 47.17 | 121.55 | 12.48 | 0.00 | 0.00 | 0.00 |
July | 49.79 | 4.88 | 44.90 | 111.89 | 9.27 | 0.00 | 0.00 | 0.00 |
August | 42.11 | 1.00 | 41.11 | 87.02 | 14.57 | 0.00 | 0.00 | 0.00 |
September | 36.63 | 0.05 | 36.59 | 63.74 | 33.93 | 0.00 | 0.00 | 0.00 |
October | 30.37 | 0.00 | 30.37 | 32.54 | 59.74 | 0.00 | 0.00 | 0.00 |
November | 24.51 | 0.00 | 24.51 | 7.45 | 110.25 | 0.00 | 0.00 | 0.00 |
December | 22.93 | 0.00 | 22.93 | 2.30 | 145.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 36.88 | 1.42 | 35.46 | 50.78 | 66.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.93 | 0.00 | 22.93 | 2.30 | 9.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 53.89 | 6.72 | 47.17 | 121.55 | 145.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 521.24 | 394.96 | 126.28 | 703.31 | 377.54 | 0.00 | 0.00 | 0.00 |
February | 490.41 | 347.79 | 142.61 | 675.63 | 333.78 | 0.00 | 0.00 | 0.00 |
March | 383.64 | 217.35 | 166.29 | 541.69 | 291.44 | 0.00 | 0.00 | 0.00 |
April | 267.32 | 100.35 | 166.97 | 432.16 | 170.72 | 0.00 | 0.00 | 0.00 |
May | 189.70 | 27.82 | 161.88 | 349.72 | 94.79 | 0.00 | 0.00 | 0.00 |
June | 162.26 | 10.21 | 152.05 | 376.95 | 43.01 | 0.00 | 0.00 | 0.00 |
July | 164.78 | 14.61 | 150.17 | 378.52 | 32.26 | 0.00 | 0.00 | 0.00 |
August | 208.00 | 52.85 | 155.16 | 440.38 | 50.09 | 0.00 | 0.00 | 0.00 |
September | 329.40 | 171.14 | 158.26 | 619.55 | 110.70 | 0.00 | 0.00 | 0.00 |
October | 452.15 | 307.19 | 144.96 | 722.04 | 185.28 | 0.00 | 0.00 | 0.00 |
November | 544.19 | 416.24 | 127.94 | 771.59 | 315.23 | 0.00 | 0.00 | 0.00 |
December | 535.12 | 402.02 | 133.09 | 711.63 | 405.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 353.20 | 204.38 | 148.83 | 559.43 | 200.22 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 162.26 | 10.21 | 126.28 | 349.72 | 32.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 544.19 | 416.24 | 166.97 | 771.59 | 405.48 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.189136E+10 | 0.143314E+10 | 0.458222E+09 | 0.253215E+10 | 0.133678E+10 |
February | 0.160727E+10 | 0.113986E+10 | 0.467406E+09 | 0.219810E+10 | 0.106864E+10 |
March | 0.139207E+10 | 0.788679E+09 | 0.603391E+09 | 0.196867E+10 | 0.102970E+10 |
April | 0.938702E+09 | 0.352379E+09 | 0.586322E+09 | 0.150998E+10 | 0.593222E+09 |
May | 0.688337E+09 | 0.100947E+09 | 0.587390E+09 | 0.124461E+10 | 0.348122E+09 |
June | 0.569764E+09 | 35850177.24 | 0.533914E+09 | 0.126276E+10 | 0.159608E+09 |
July | 0.597898E+09 | 53010019.83 | 0.544888E+09 | 0.132564E+10 | 0.123827E+09 |
August | 0.754750E+09 | 0.191758E+09 | 0.562992E+09 | 0.155871E+10 | 0.188494E+09 |
September | 0.115668E+10 | 0.600953E+09 | 0.555729E+09 | 0.214894E+10 | 0.399013E+09 |
October | 0.164065E+10 | 0.111467E+10 | 0.525978E+09 | 0.260192E+10 | 0.676070E+09 |
November | 0.191093E+10 | 0.146165E+10 | 0.449279E+09 | 0.268024E+10 | 0.109668E+10 |
December | 0.194172E+10 | 0.145878E+10 | 0.482936E+09 | 0.254834E+10 | 0.143710E+10 |
Annual Sum or Average | 0.150901E+11 | 0.873168E+10 | 0.635845E+10 | 0.235801E+11 | 0.845725E+10 |
Minimum of Months | 0.569764E+09 | 35850177.24 | 0.449279E+09 | 0.124461E+10 | 0.123827E+09 |
Maximum of Months | 0.194172E+10 | 0.146165E+10 | 0.603391E+09 | 0.268024E+10 | 0.143710E+10 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.532594E+10 | 0.403562E+10 | 0.129032E+10 | 0.700856E+10 | 0.410361E+10 |
February | 0.452597E+10 | 0.320978E+10 | 0.131618E+10 | 0.607162E+10 | 0.329491E+10 |
March | 0.391998E+10 | 0.222087E+10 | 0.169911E+10 | 0.541060E+10 | 0.318646E+10 |
April | 0.264332E+10 | 0.992277E+09 | 0.165105E+10 | 0.416200E+10 | 0.182792E+10 |
May | 0.193831E+10 | 0.284261E+09 | 0.165405E+10 | 0.344964E+10 | 0.105071E+10 |
June | 0.160442E+10 | 0.100952E+09 | 0.150347E+10 | 0.354041E+10 | 0.463413E+09 |
July | 0.168364E+10 | 0.149273E+09 | 0.153437E+10 | 0.371316E+10 | 0.361294E+09 |
August | 0.212533E+10 | 0.539978E+09 | 0.158535E+10 | 0.435902E+10 | 0.557988E+09 |
September | 0.325714E+10 | 0.169224E+10 | 0.156490E+10 | 0.600572E+10 | 0.115823E+10 |
October | 0.461996E+10 | 0.313884E+10 | 0.148112E+10 | 0.724944E+10 | 0.202971E+10 |
November | 0.538106E+10 | 0.411592E+10 | 0.126514E+10 | 0.743686E+10 | 0.333124E+10 |
December | 0.546774E+10 | 0.410783E+10 | 0.135992E+10 | 0.703884E+10 | 0.438462E+10 |
Annual Sum or Average | 0.424928E+11 | 0.245878E+11 | 0.179050E+11 | 0.654459E+11 | 0.257501E+11 |
Minimum of Months | 0.160442E+10 | 0.100952E+09 | 0.126514E+10 | 0.344964E+10 | 0.361294E+09 |
Maximum of Months | 0.546774E+10 | 0.411592E+10 | 0.169911E+10 | 0.743686E+10 | 0.438462E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.691870E+10 | 0.524250E+10 | 0.167620E+10 | 0.929765E+10 | 0.546746E+10 |
February | 0.587949E+10 | 0.416969E+10 | 0.170980E+10 | 0.806806E+10 | 0.437258E+10 |
March | 0.509227E+10 | 0.288503E+10 | 0.220724E+10 | 0.720841E+10 | 0.423282E+10 |
April | 0.343383E+10 | 0.128902E+10 | 0.214480E+10 | 0.557245E+10 | 0.241451E+10 |
May | 0.251798E+10 | 0.369271E+09 | 0.214871E+10 | 0.463291E+10 | 0.138161E+10 |
June | 0.208423E+10 | 0.131142E+09 | 0.195309E+10 | 0.477095E+10 | 0.602723E+09 |
July | 0.218715E+10 | 0.193914E+09 | 0.199323E+10 | 0.499896E+10 | 0.466589E+09 |
August | 0.276092E+10 | 0.701462E+09 | 0.205946E+10 | 0.584611E+10 | 0.721632E+09 |
September | 0.423121E+10 | 0.219832E+10 | 0.203289E+10 | 0.800506E+10 | 0.149913E+10 |
October | 0.600158E+10 | 0.407753E+10 | 0.192406E+10 | 0.961796E+10 | 0.265811E+10 |
November | 0.699030E+10 | 0.534681E+10 | 0.164349E+10 | 0.984609E+10 | 0.442297E+10 |
December | 0.710291E+10 | 0.533630E+10 | 0.176661E+10 | 0.933424E+10 | 0.585502E+10 |
Annual Sum or Average | 0.552006E+11 | 0.319410E+11 | 0.232596E+11 | 0.871988E+11 | 0.340952E+11 |
Minimum of Months | 0.208423E+10 | 0.131142E+09 | 0.164349E+10 | 0.463291E+10 | 0.466589E+09 |
Maximum of Months | 0.710291E+10 | 0.534681E+10 | 0.220724E+10 | 0.984609E+10 | 0.585502E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.373955E+09 | 0.283356E+09 | 90599047.15 | 0.503770E+09 | 0.274869E+09 |
February | 0.317786E+09 | 0.225371E+09 | 92415031.30 | 0.437741E+09 | 0.218188E+09 |
March | 0.275237E+09 | 0.155935E+09 | 0.119302E+09 | 0.388559E+09 | 0.210085E+09 |
April | 0.185599E+09 | 69671463.64 | 0.115927E+09 | 0.306744E+09 | 0.108316E+09 |
May | 0.136098E+09 | 19958985.63 | 0.116139E+09 | 0.267372E+09 | 52795798.30 |
June | 0.112654E+09 | 7088195.76 | 0.105566E+09 | 0.289869E+09 | 17847877.06 |
July | 0.118216E+09 | 10480991.36 | 0.107735E+09 | 0.303943E+09 | 10354727.61 |
August | 0.149228E+09 | 37913864.16 | 0.111315E+09 | 0.343291E+09 | 20796069.39 |
September | 0.228697E+09 | 0.118819E+09 | 0.109878E+09 | 0.447280E+09 | 59217340.91 |
October | 0.324385E+09 | 0.220389E+09 | 0.103996E+09 | 0.528298E+09 | 0.120280E+09 |
November | 0.377825E+09 | 0.288994E+09 | 88830943.98 | 0.536785E+09 | 0.218427E+09 |
December | 0.383911E+09 | 0.288426E+09 | 95485408.74 | 0.509195E+09 | 0.297197E+09 |
Annual Sum or Average | 0.298359E+10 | 0.172640E+10 | 0.125719E+10 | 0.486285E+10 | 0.160837E+10 |
Minimum of Months | 0.112654E+09 | 7088195.76 | 88830943.98 | 0.267372E+09 | 10354727.61 |
Maximum of Months | 0.383911E+09 | 0.288994E+09 | 0.119302E+09 | 0.536785E+09 | 0.297197E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.287674E+09 | 0.162146E+09 | 0.125527E+09 | 0.302190E+09 | 0.569740E+09 |
February | 0.292474E+09 | 0.155192E+09 | 0.137282E+09 | 0.333801E+09 | 0.451246E+09 |
March | 0.441845E+09 | 0.236918E+09 | 0.204927E+09 | 0.566388E+09 | 0.407812E+09 |
April | 0.490686E+09 | 0.264679E+09 | 0.226007E+09 | 0.761374E+09 | 0.200070E+09 |
May | 0.547180E+09 | 0.292832E+09 | 0.254348E+09 | 0.968029E+09 | 97696556.54 |
June | 0.515254E+09 | 0.276659E+09 | 0.238595E+09 | 0.106037E+10 | 33173857.85 |
July | 0.472844E+09 | 0.234945E+09 | 0.237900E+09 | 0.990841E+09 | 18758689.50 |
August | 0.457839E+09 | 0.233254E+09 | 0.224585E+09 | 0.910400E+09 | 38538341.66 |
September | 0.454872E+09 | 0.253932E+09 | 0.200940E+09 | 0.825731E+09 | 0.112094E+09 |
October | 0.404989E+09 | 0.237094E+09 | 0.167895E+09 | 0.624519E+09 | 0.236235E+09 |
November | 0.327016E+09 | 0.198972E+09 | 0.128044E+09 | 0.396378E+09 | 0.453348E+09 |
December | 0.272539E+09 | 0.147971E+09 | 0.124568E+09 | 0.269975E+09 | 0.626643E+09 |
Annual Sum or Average | 0.496521E+10 | 0.269459E+10 | 0.227062E+10 | 0.801000E+10 | 0.324536E+10 |
Minimum of Months | 0.272539E+09 | 0.147971E+09 | 0.124568E+09 | 0.269975E+09 | 18758689.50 |
Maximum of Months | 0.547180E+09 | 0.292832E+09 | 0.254348E+09 | 0.106037E+10 | 0.626643E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54635219.79 | 0.00 | 54635219.79 | 10725338.83 | 0.308297E+09 |
February | 60259072.44 | 0.00 | 60259072.44 | 27394109.18 | 0.244386E+09 |
March | 87327152.96 | 3456.98 | 87323695.98 | 61513075.56 | 0.225065E+09 |
April | 98134921.78 | 1250183.62 | 96884738.16 | 0.124971E+09 | 0.109530E+09 |
May | 0.119788E+09 | 8827959.99 | 0.110960E+09 | 0.219697E+09 | 51236858.48 |
June | 0.123276E+09 | 15361483.16 | 0.107914E+09 | 0.301915E+09 | 17842047.20 |
July | 0.117686E+09 | 11543657.45 | 0.106142E+09 | 0.292430E+09 | 10677298.80 |
August | 99533259.29 | 2367984.07 | 97165275.22 | 0.229193E+09 | 21603709.67 |
September | 83800633.79 | 105909.72 | 83694724.07 | 0.158877E+09 | 63077760.46 |
October | 71778804.06 | 0.00 | 71778804.06 | 85122622.80 | 0.132805E+09 |
November | 56077421.72 | 0.00 | 56077421.72 | 20992895.02 | 0.247120E+09 |
December | 54212081.06 | 0.00 | 54212081.06 | 7654655.07 | 0.340051E+09 |
Annual Sum or Average | 0.102651E+10 | 39460634.99 | 0.987047E+09 | 0.154049E+10 | 0.177169E+10 |
Minimum of Months | 54212081.06 | 0.00 | 54212081.06 | 7654655.07 | 10677298.80 |
Maximum of Months | 0.123276E+09 | 15361483.16 | 0.110960E+09 | 0.301915E+09 | 0.340051E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.287674E+09 | 0.162146E+09 | 0.125527E+09 | 0.319132E+09 | 0.552828E+09 |
February | 0.292474E+09 | 0.155192E+09 | 0.137282E+09 | 0.347373E+09 | 0.441418E+09 |
March | 0.441845E+09 | 0.236918E+09 | 0.204927E+09 | 0.574159E+09 | 0.406946E+09 |
April | 0.490686E+09 | 0.264679E+09 | 0.226007E+09 | 0.761782E+09 | 0.205621E+09 |
May | 0.547180E+09 | 0.292832E+09 | 0.254348E+09 | 0.962322E+09 | 0.102469E+09 |
June | 0.515254E+09 | 0.276659E+09 | 0.238595E+09 | 0.105172E+10 | 34923308.20 |
July | 0.472844E+09 | 0.234945E+09 | 0.237900E+09 | 0.982598E+09 | 20526496.78 |
August | 0.457839E+09 | 0.233254E+09 | 0.224585E+09 | 0.906500E+09 | 41708672.67 |
September | 0.454872E+09 | 0.253932E+09 | 0.200940E+09 | 0.827759E+09 | 0.117748E+09 |
October | 0.404989E+09 | 0.237094E+09 | 0.167895E+09 | 0.630652E+09 | 0.242760E+09 |
November | 0.327016E+09 | 0.198972E+09 | 0.128044E+09 | 0.410182E+09 | 0.444000E+09 |
December | 0.272539E+09 | 0.147971E+09 | 0.124568E+09 | 0.286901E+09 | 0.608320E+09 |
Annual Sum or Average | 0.496521E+10 | 0.269459E+10 | 0.227062E+10 | 0.806108E+10 | 0.321927E+10 |
Minimum of Months | 0.272539E+09 | 0.147971E+09 | 0.124568E+09 | 0.286901E+09 | 20526496.78 |
Maximum of Months | 0.547180E+09 | 0.292832E+09 | 0.254348E+09 | 0.105172E+10 | 0.608320E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.299104E+09 | 0.226640E+09 | 72464826.42 | 0.364276E+09 | 0.302527E+09 |
February | 0.254178E+09 | 0.180261E+09 | 73917324.87 | 0.314343E+09 | 0.246708E+09 |
March | 0.220146E+09 | 0.124724E+09 | 95422629.83 | 0.270989E+09 | 0.240542E+09 |
April | 0.148450E+09 | 55726088.50 | 92723544.22 | 0.207775E+09 | 0.147052E+09 |
May | 0.108857E+09 | 15964013.69 | 92892545.85 | 0.169092E+09 | 91237476.42 |
June | 90105188.78 | 5669429.11 | 84435759.67 | 0.178277E+09 | 45903492.19 |
July | 94554156.30 | 8383125.91 | 86171030.39 | 0.186005E+09 | 40382122.88 |
August | 0.119359E+09 | 30325060.49 | 89033931.16 | 0.223362E+09 | 56265884.66 |
September | 0.182921E+09 | 95036114.58 | 87885276.20 | 0.319834E+09 | 98128226.71 |
October | 0.259457E+09 | 0.176276E+09 | 83180150.54 | 0.383009E+09 | 0.160712E+09 |
November | 0.302200E+09 | 0.231149E+09 | 71050625.13 | 0.391794E+09 | 0.247648E+09 |
December | 0.307068E+09 | 0.230695E+09 | 76373138.43 | 0.366520E+09 | 0.318244E+09 |
Annual Sum or Average | 0.238640E+10 | 0.138085E+10 | 0.100555E+10 | 0.337528E+10 | 0.199535E+10 |
Minimum of Months | 90105188.78 | 5669429.11 | 71050625.13 | 0.169092E+09 | 40382122.88 |
Maximum of Months | 0.307068E+09 | 0.231149E+09 | 95422629.83 | 0.391794E+09 | 0.318244E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 43713969.60 | 0.00 | 43713969.60 | 8095580.10 | 0.253119E+09 |
February | 48213648.10 | 0.00 | 48213648.10 | 22941600.30 | 0.198149E+09 |
March | 69870982.94 | 2765.95 | 69868216.99 | 53414226.98 | 0.178209E+09 |
April | 78518344.10 | 1000279.47 | 77518064.63 | 0.109258E+09 | 82859215.04 |
May | 95843144.60 | 7063304.15 | 88779840.45 | 0.190193E+09 | 36895010.82 |
June | 98633813.54 | 12290815.53 | 86342998.01 | 0.259390E+09 | 11649840.91 |
July | 94160895.41 | 9236150.10 | 84924745.31 | 0.250817E+09 | 6319132.76 |
August | 79637162.39 | 1894638.37 | 77742524.03 | 0.198965E+09 | 14312185.14 |
September | 67049393.63 | 84739.01 | 66964654.62 | 0.138876E+09 | 44890868.47 |
October | 57430655.00 | 0.00 | 57430655.00 | 75403720.57 | 0.100081E+09 |
November | 44867884.08 | 0.00 | 44867884.08 | 18761284.62 | 0.197004E+09 |
December | 43375413.74 | 0.00 | 43375413.74 | 5533813.66 | 0.280840E+09 |
Annual Sum or Average | 0.821315E+09 | 31572692.58 | 0.789743E+09 | 0.133165E+10 | 0.140433E+10 |
Minimum of Months | 43375413.74 | 0.00 | 43375413.74 | 5533813.66 | 6319132.76 |
Maximum of Months | 98633813.54 | 12290815.53 | 88779840.45 | 0.259390E+09 | 0.280840E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272406E+09 | 0.147604E+09 | 0.124803E+09 | 0.250725E+09 | 0.541051E+09 |
February | 0.330219E+09 | 0.188293E+09 | 0.141926E+09 | 0.365698E+09 | 0.419486E+09 |
March | 0.450634E+09 | 0.248122E+09 | 0.202511E+09 | 0.554236E+09 | 0.374947E+09 |
April | 0.525720E+09 | 0.291582E+09 | 0.234138E+09 | 0.803261E+09 | 0.180423E+09 |
May | 0.560008E+09 | 0.304221E+09 | 0.255786E+09 | 0.987263E+09 | 88440220.31 |
June | 0.542173E+09 | 0.301473E+09 | 0.240700E+09 | 0.110696E+10 | 30813274.61 |
July | 0.502747E+09 | 0.262839E+09 | 0.239908E+09 | 0.104269E+10 | 18025745.52 |
August | 0.478911E+09 | 0.245239E+09 | 0.233671E+09 | 0.949081E+09 | 36102521.92 |
September | 0.459814E+09 | 0.262571E+09 | 0.197243E+09 | 0.824074E+09 | 0.102101E+09 |
October | 0.363675E+09 | 0.195894E+09 | 0.167781E+09 | 0.537443E+09 | 0.220536E+09 |
November | 0.315129E+09 | 0.183035E+09 | 0.132093E+09 | 0.343596E+09 | 0.421832E+09 |
December | 0.272612E+09 | 0.144459E+09 | 0.128153E+09 | 0.239707E+09 | 0.593892E+09 |
Annual Sum or Average | 0.507405E+10 | 0.277533E+10 | 0.229871E+10 | 0.800474E+10 | 0.302765E+10 |
Minimum of Months | 0.272406E+09 | 0.144459E+09 | 0.124803E+09 | 0.239707E+09 | 18025745.52 |
Maximum of Months | 0.560008E+09 | 0.304221E+09 | 0.255786E+09 | 0.110696E+10 | 0.593892E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.373955E+09 | 0.283356E+09 | 90599047.15 | 0.501760E+09 | 0.273403E+09 |
February | 0.317786E+09 | 0.225371E+09 | 92415031.30 | 0.433833E+09 | 0.217684E+09 |
March | 0.275237E+09 | 0.155935E+09 | 0.119302E+09 | 0.384361E+09 | 0.208842E+09 |
April | 0.185599E+09 | 69671463.64 | 0.115927E+09 | 0.303356E+09 | 0.108050E+09 |
May | 0.136098E+09 | 19958985.63 | 0.116139E+09 | 0.265681E+09 | 52166805.81 |
June | 0.112654E+09 | 7088195.76 | 0.105566E+09 | 0.288092E+09 | 17339866.40 |
July | 0.118216E+09 | 10480991.36 | 0.107735E+09 | 0.302338E+09 | 9958567.87 |
August | 0.149228E+09 | 37913864.16 | 0.111315E+09 | 0.342269E+09 | 20384331.24 |
September | 0.228697E+09 | 0.118819E+09 | 0.109878E+09 | 0.446083E+09 | 58323313.56 |
October | 0.324385E+09 | 0.220389E+09 | 0.103996E+09 | 0.527621E+09 | 0.118114E+09 |
November | 0.377825E+09 | 0.288994E+09 | 88830943.98 | 0.534864E+09 | 0.216738E+09 |
December | 0.383911E+09 | 0.288426E+09 | 95485408.74 | 0.507078E+09 | 0.296233E+09 |
Annual Sum or Average | 0.298359E+10 | 0.172640E+10 | 0.125719E+10 | 0.483734E+10 | 0.159724E+10 |
Minimum of Months | 0.112654E+09 | 7088195.76 | 88830943.98 | 0.265681E+09 | 9958567.87 |
Maximum of Months | 0.383911E+09 | 0.288994E+09 | 0.119302E+09 | 0.534864E+09 | 0.296233E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54635219.79 | 0.00 | 54635219.79 | 9942800.87 | 0.307106E+09 |
February | 60259072.44 | 0.00 | 60259072.44 | 25554933.64 | 0.244879E+09 |
March | 87327152.96 | 3456.98 | 87323695.98 | 58857892.65 | 0.223826E+09 |
April | 98134921.78 | 1250183.62 | 96884738.16 | 0.120364E+09 | 0.108689E+09 |
May | 0.119788E+09 | 8827959.99 | 0.110960E+09 | 0.214134E+09 | 50287592.50 |
June | 0.123276E+09 | 15361483.16 | 0.107914E+09 | 0.297000E+09 | 17434787.12 |
July | 0.117686E+09 | 11543657.45 | 0.106142E+09 | 0.288153E+09 | 10362365.38 |
August | 99533259.29 | 2367984.07 | 97165275.22 | 0.225241E+09 | 21188217.47 |
September | 83800633.79 | 105909.72 | 83694724.07 | 0.154895E+09 | 62807877.55 |
October | 71778804.06 | 0.00 | 71778804.06 | 83776650.26 | 0.128780E+09 |
November | 56077421.72 | 0.00 | 56077421.72 | 19727296.32 | 0.244559E+09 |
December | 54212081.06 | 0.00 | 54212081.06 | 6845781.27 | 0.339850E+09 |
Annual Sum or Average | 0.102651E+10 | 39460634.99 | 0.987047E+09 | 0.150449E+10 | 0.175977E+10 |
Minimum of Months | 54212081.06 | 0.00 | 54212081.06 | 6845781.27 | 10362365.38 |
Maximum of Months | 0.123276E+09 | 15361483.16 | 0.110960E+09 | 0.297000E+09 | 0.339850E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272406E+09 | 0.147604E+09 | 0.124803E+09 | 0.263888E+09 | 0.518109E+09 |
February | 0.330219E+09 | 0.188293E+09 | 0.141926E+09 | 0.378508E+09 | 0.406884E+09 |
March | 0.450634E+09 | 0.248122E+09 | 0.202511E+09 | 0.563521E+09 | 0.371895E+09 |
April | 0.525720E+09 | 0.291582E+09 | 0.234138E+09 | 0.801609E+09 | 0.185120E+09 |
May | 0.560008E+09 | 0.304221E+09 | 0.255786E+09 | 0.972820E+09 | 92584815.49 |
June | 0.542173E+09 | 0.301473E+09 | 0.240700E+09 | 0.109021E+10 | 32230008.53 |
July | 0.502747E+09 | 0.262839E+09 | 0.239908E+09 | 0.102773E+10 | 19606889.19 |
August | 0.478911E+09 | 0.245239E+09 | 0.233671E+09 | 0.937634E+09 | 38632765.75 |
September | 0.459814E+09 | 0.262571E+09 | 0.197243E+09 | 0.817442E+09 | 0.106849E+09 |
October | 0.363675E+09 | 0.195894E+09 | 0.167781E+09 | 0.543977E+09 | 0.224412E+09 |
November | 0.315129E+09 | 0.183035E+09 | 0.132093E+09 | 0.356848E+09 | 0.408686E+09 |
December | 0.272612E+09 | 0.144459E+09 | 0.128153E+09 | 0.250583E+09 | 0.568133E+09 |
Annual Sum or Average | 0.507405E+10 | 0.277533E+10 | 0.229871E+10 | 0.800477E+10 | 0.297314E+10 |
Minimum of Months | 0.272406E+09 | 0.144459E+09 | 0.124803E+09 | 0.250583E+09 | 19606889.19 |
Maximum of Months | 0.560008E+09 | 0.304221E+09 | 0.255786E+09 | 0.109021E+10 | 0.568133E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 69192058.57 | 0.00 | 69192058.57 | 12166397.60 | 0.392631E+09 |
February | 76314313.11 | 0.00 | 76314313.11 | 34493928.16 | 0.310593E+09 |
March | 0.110594E+09 | 4378.05 | 0.110590E+09 | 82425494.21 | 0.281541E+09 |
April | 0.124282E+09 | 1583278.67 | 0.122698E+09 | 0.162133E+09 | 0.143502E+09 |
May | 0.151704E+09 | 11180054.31 | 0.140524E+09 | 0.274600E+09 | 76151571.27 |
June | 0.156121E+09 | 19454349.17 | 0.136667E+09 | 0.364963E+09 | 33325528.31 |
July | 0.149041E+09 | 14619313.80 | 0.134422E+09 | 0.349827E+09 | 24155085.07 |
August | 0.126053E+09 | 2998902.41 | 0.123054E+09 | 0.273703E+09 | 39791886.24 |
September | 0.106128E+09 | 134127.98 | 0.105994E+09 | 0.194123E+09 | 94943177.23 |
October | 90903326.35 | 0.00 | 90903326.35 | 0.104804E+09 | 0.176941E+09 |
November | 71018516.32 | 0.00 | 71018516.32 | 24519067.90 | 0.321813E+09 |
December | 68656180.07 | 0.00 | 68656180.07 | 8441979.50 | 0.430737E+09 |
Annual Sum or Average | 0.130001E+10 | 49974404.39 | 0.125003E+10 | 0.188620E+10 | 0.232613E+10 |
Minimum of Months | 68656180.07 | 0.00 | 68656180.07 | 8441979.50 | 24155085.07 |
Maximum of Months | 0.156121E+09 | 19454349.17 | 0.140524E+09 | 0.364963E+09 | 0.430737E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 25507057.81 | 0.00 | 25507057.81 | 4485037.93 | 0.144740E+09 |
February | 28132615.74 | 0.00 | 28132615.74 | 12715890.20 | 0.114497E+09 |
March | 40769649.09 | 1613.93 | 40768035.16 | 30385450.14 | 0.103788E+09 |
April | 45815375.73 | 583662.08 | 45231713.65 | 59768836.30 | 52900929.35 |
May | 55924379.60 | 4121430.95 | 51802948.65 | 0.101229E+09 | 28072622.36 |
June | 57552732.16 | 7171678.64 | 50381053.51 | 0.134541E+09 | 12285169.64 |
July | 54942788.87 | 5389284.40 | 49553504.47 | 0.128961E+09 | 8904564.54 |
August | 46468205.09 | 1105519.60 | 45362685.49 | 0.100898E+09 | 14668936.92 |
September | 39123254.53 | 49445.13 | 39073809.41 | 71561887.90 | 34999986.41 |
October | 33510730.10 | 0.00 | 33510730.10 | 38635217.92 | 65227666.88 |
November | 26180365.76 | 0.00 | 26180365.76 | 9038743.68 | 0.118634E+09 |
December | 25309510.80 | 0.00 | 25309510.80 | 3112063.20 | 0.158787E+09 |
Annual Sum or Average | 0.479237E+09 | 18422634.73 | 0.460814E+09 | 0.695332E+09 | 0.857506E+09 |
Minimum of Months | 25309510.80 | 0.00 | 25309510.80 | 3112063.20 | 8904564.54 |
Maximum of Months | 57552732.16 | 7171678.64 | 51802948.65 | 0.134541E+09 | 0.158787E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.174486E+09 | 0.132213E+09 | 42273150.31 | 0.239137E+09 | 0.125651E+09 |
February | 0.148278E+09 | 0.105157E+09 | 43120481.20 | 0.207655E+09 | 0.100504E+09 |
March | 0.128425E+09 | 72758842.37 | 55665836.43 | 0.185159E+09 | 97403731.55 |
April | 86599719.45 | 32508424.18 | 54091295.27 | 0.144572E+09 | 54014423.12 |
May | 63502666.49 | 9312782.27 | 54189884.22 | 0.121983E+09 | 30195376.53 |
June | 52563848.94 | 3307323.58 | 49256525.36 | 0.126666E+09 | 12867205.28 |
July | 55159202.88 | 4890388.33 | 50268814.55 | 0.132155E+09 | 9371614.69 |
August | 69629375.31 | 17690456.23 | 51938919.07 | 0.152700E+09 | 15251109.16 |
September | 0.106709E+09 | 55440358.52 | 51268838.62 | 0.205123E+09 | 34564981.34 |
October | 0.151357E+09 | 0.102833E+09 | 48524052.02 | 0.245960E+09 | 61298173.37 |
November | 0.176291E+09 | 0.134843E+09 | 41448160.50 | 0.252697E+09 | 0.103106E+09 |
December | 0.179131E+09 | 0.134578E+09 | 44553106.94 | 0.241734E+09 | 0.134935E+09 |
Annual Sum or Average | 0.139213E+10 | 0.805533E+09 | 0.586599E+09 | 0.225554E+10 | 0.779162E+09 |
Minimum of Months | 52563848.94 | 3307323.58 | 41448160.50 | 0.121983E+09 | 9371614.69 |
Maximum of Months | 0.179131E+09 | 0.134843E+09 | 55665836.43 | 0.252697E+09 | 0.134935E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.473590E+09 | 0.358852E+09 | 0.114738E+09 | 0.649066E+09 | 0.341042E+09 |
February | 0.402456E+09 | 0.285418E+09 | 0.117038E+09 | 0.563619E+09 | 0.272787E+09 |
March | 0.348571E+09 | 0.197482E+09 | 0.151088E+09 | 0.502558E+09 | 0.264374E+09 |
April | 0.235049E+09 | 88234512.68 | 0.146815E+09 | 0.392398E+09 | 0.146606E+09 |
May | 0.172359E+09 | 25276795.96 | 0.147082E+09 | 0.331087E+09 | 81956428.23 |
June | 0.142669E+09 | 8976752.69 | 0.133692E+09 | 0.343798E+09 | 34924227.07 |
July | 0.149713E+09 | 13273514.24 | 0.136440E+09 | 0.358695E+09 | 25436479.18 |
August | 0.188988E+09 | 48015516.72 | 0.140973E+09 | 0.414459E+09 | 41394629.80 |
September | 0.289631E+09 | 0.150476E+09 | 0.139154E+09 | 0.556745E+09 | 93816429.48 |
October | 0.410813E+09 | 0.279109E+09 | 0.131704E+09 | 0.667586E+09 | 0.166376E+09 |
November | 0.478491E+09 | 0.365992E+09 | 0.112499E+09 | 0.685873E+09 | 0.279850E+09 |
December | 0.486199E+09 | 0.365273E+09 | 0.120926E+09 | 0.656116E+09 | 0.366240E+09 |
Annual Sum or Average | 0.377853E+10 | 0.218638E+10 | 0.159215E+10 | 0.612200E+10 | 0.211480E+10 |
Minimum of Months | 0.142669E+09 | 8976752.69 | 0.112499E+09 | 0.331087E+09 | 25436479.18 |
Maximum of Months | 0.486199E+09 | 0.365992E+09 | 0.151088E+09 | 0.685873E+09 | 0.366240E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.373955E+09 | 0.283356E+09 | 90599047.15 | 0.500897E+09 | 0.271794E+09 |
February | 0.317786E+09 | 0.225371E+09 | 92415031.30 | 0.434978E+09 | 0.215422E+09 |
March | 0.275237E+09 | 0.155935E+09 | 0.119302E+09 | 0.385071E+09 | 0.207328E+09 |
April | 0.185599E+09 | 69671463.64 | 0.115927E+09 | 0.303692E+09 | 0.105846E+09 |
May | 0.136098E+09 | 19958985.63 | 0.116139E+09 | 0.265928E+09 | 50571532.78 |
June | 0.112654E+09 | 7088195.76 | 0.105566E+09 | 0.289361E+09 | 16639864.54 |
July | 0.118216E+09 | 10480991.36 | 0.107735E+09 | 0.302767E+09 | 9513514.37 |
August | 0.149228E+09 | 37913864.16 | 0.111315E+09 | 0.341447E+09 | 19494632.43 |
September | 0.228697E+09 | 0.118819E+09 | 0.109878E+09 | 0.443810E+09 | 57103093.60 |
October | 0.324385E+09 | 0.220389E+09 | 0.103996E+09 | 0.524593E+09 | 0.117701E+09 |
November | 0.377825E+09 | 0.288994E+09 | 88830943.98 | 0.534170E+09 | 0.214913E+09 |
December | 0.383911E+09 | 0.288426E+09 | 95485408.74 | 0.507487E+09 | 0.293831E+09 |
Annual Sum or Average | 0.298359E+10 | 0.172640E+10 | 0.125719E+10 | 0.483420E+10 | 0.158016E+10 |
Minimum of Months | 0.112654E+09 | 7088195.76 | 88830943.98 | 0.265928E+09 | 9513514.37 |
Maximum of Months | 0.383911E+09 | 0.288994E+09 | 0.119302E+09 | 0.534170E+09 | 0.293831E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.287674E+09 | 0.162146E+09 | 0.125527E+09 | 0.299574E+09 | 0.562270E+09 |
February | 0.292474E+09 | 0.155192E+09 | 0.137282E+09 | 0.330713E+09 | 0.444502E+09 |
March | 0.441845E+09 | 0.236918E+09 | 0.204927E+09 | 0.560605E+09 | 0.401385E+09 |
April | 0.490686E+09 | 0.264679E+09 | 0.226007E+09 | 0.754541E+09 | 0.195159E+09 |
May | 0.547180E+09 | 0.292832E+09 | 0.254348E+09 | 0.960719E+09 | 93464980.81 |
June | 0.515254E+09 | 0.276659E+09 | 0.238595E+09 | 0.105458E+10 | 31073515.79 |
July | 0.472844E+09 | 0.234945E+09 | 0.237900E+09 | 0.985141E+09 | 17216700.96 |
August | 0.457839E+09 | 0.233254E+09 | 0.224585E+09 | 0.904978E+09 | 36164274.82 |
September | 0.454872E+09 | 0.253932E+09 | 0.200940E+09 | 0.819721E+09 | 0.108030E+09 |
October | 0.404989E+09 | 0.237094E+09 | 0.167895E+09 | 0.620078E+09 | 0.230383E+09 |
November | 0.327016E+09 | 0.198972E+09 | 0.128044E+09 | 0.393576E+09 | 0.444745E+09 |
December | 0.272539E+09 | 0.147971E+09 | 0.124568E+09 | 0.268669E+09 | 0.617753E+09 |
Annual Sum or Average | 0.496521E+10 | 0.269459E+10 | 0.227062E+10 | 0.795290E+10 | 0.318215E+10 |
Minimum of Months | 0.272539E+09 | 0.147971E+09 | 0.124568E+09 | 0.268669E+09 | 17216700.96 |
Maximum of Months | 0.547180E+09 | 0.292832E+09 | 0.254348E+09 | 0.105458E+10 | 0.617753E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54635219.79 | 0.00 | 54635219.79 | 11568185.95 | 0.303481E+09 |
February | 60259072.44 | 0.00 | 60259072.44 | 28112071.45 | 0.240277E+09 |
March | 87327152.96 | 3456.98 | 87323695.98 | 61913861.30 | 0.222015E+09 |
April | 98134921.78 | 1250183.62 | 96884738.16 | 0.124222E+09 | 0.107431E+09 |
May | 0.119788E+09 | 8827959.99 | 0.110960E+09 | 0.219019E+09 | 49311356.60 |
June | 0.123276E+09 | 15361483.16 | 0.107914E+09 | 0.300919E+09 | 16775759.01 |
July | 0.117686E+09 | 11543657.45 | 0.106142E+09 | 0.291187E+09 | 9891704.65 |
August | 99533259.29 | 2367984.07 | 97165275.22 | 0.228710E+09 | 20359513.27 |
September | 83800633.79 | 105909.72 | 83694724.07 | 0.158153E+09 | 60746147.44 |
October | 71778804.06 | 0.00 | 71778804.06 | 85239696.44 | 0.130098E+09 |
November | 56077421.72 | 0.00 | 56077421.72 | 22107974.03 | 0.242001E+09 |
December | 54212081.06 | 0.00 | 54212081.06 | 8386068.15 | 0.334639E+09 |
Annual Sum or Average | 0.102651E+10 | 39460634.99 | 0.987047E+09 | 0.153954E+10 | 0.173702E+10 |
Minimum of Months | 54212081.06 | 0.00 | 54212081.06 | 8386068.15 | 9891704.65 |
Maximum of Months | 0.123276E+09 | 15361483.16 | 0.110960E+09 | 0.300919E+09 | 0.334639E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.287674E+09 | 0.162146E+09 | 0.125527E+09 | 0.319000E+09 | 0.544408E+09 |
February | 0.292474E+09 | 0.155192E+09 | 0.137282E+09 | 0.346200E+09 | 0.433992E+09 |
March | 0.441845E+09 | 0.236918E+09 | 0.204927E+09 | 0.569511E+09 | 0.400843E+09 |
April | 0.490686E+09 | 0.264679E+09 | 0.226007E+09 | 0.755170E+09 | 0.201310E+09 |
May | 0.547180E+09 | 0.292832E+09 | 0.254348E+09 | 0.955310E+09 | 98307994.60 |
June | 0.515254E+09 | 0.276659E+09 | 0.238595E+09 | 0.104601E+10 | 32709378.94 |
July | 0.472844E+09 | 0.234945E+09 | 0.237900E+09 | 0.976957E+09 | 18899546.82 |
August | 0.457839E+09 | 0.233254E+09 | 0.224585E+09 | 0.901426E+09 | 39184618.57 |
September | 0.454872E+09 | 0.253932E+09 | 0.200940E+09 | 0.822654E+09 | 0.113275E+09 |
October | 0.404989E+09 | 0.237094E+09 | 0.167895E+09 | 0.627225E+09 | 0.237301E+09 |
November | 0.327016E+09 | 0.198972E+09 | 0.128044E+09 | 0.409920E+09 | 0.434079E+09 |
December | 0.272539E+09 | 0.147971E+09 | 0.124568E+09 | 0.287967E+09 | 0.598900E+09 |
Annual Sum or Average | 0.496521E+10 | 0.269459E+10 | 0.227062E+10 | 0.801735E+10 | 0.315321E+10 |
Minimum of Months | 0.272539E+09 | 0.147971E+09 | 0.124568E+09 | 0.287967E+09 | 18899546.82 |
Maximum of Months | 0.547180E+09 | 0.292832E+09 | 0.254348E+09 | 0.104601E+10 | 0.598900E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.548441E+09 | 0.415568E+09 | 0.132872E+09 | 0.714811E+09 | 0.417240E+09 |
February | 0.466063E+09 | 0.330528E+09 | 0.135536E+09 | 0.623048E+09 | 0.328618E+09 |
March | 0.403662E+09 | 0.228694E+09 | 0.174968E+09 | 0.555825E+09 | 0.308932E+09 |
April | 0.272199E+09 | 0.102180E+09 | 0.170019E+09 | 0.449236E+09 | 0.152570E+09 |
May | 0.199600E+09 | 29271767.90 | 0.170329E+09 | 0.406047E+09 | 69983790.43 |
June | 0.165218E+09 | 10395519.34 | 0.154822E+09 | 0.445551E+09 | 21692857.21 |
July | 0.173375E+09 | 15371379.69 | 0.158004E+09 | 0.462513E+09 | 11898158.22 |
August | 0.218858E+09 | 55604320.39 | 0.163253E+09 | 0.514949E+09 | 26341679.02 |
September | 0.335406E+09 | 0.174259E+09 | 0.161147E+09 | 0.656355E+09 | 80995671.79 |
October | 0.475742E+09 | 0.323222E+09 | 0.152520E+09 | 0.764817E+09 | 0.174582E+09 |
November | 0.554116E+09 | 0.423837E+09 | 0.130279E+09 | 0.769516E+09 | 0.327023E+09 |
December | 0.563043E+09 | 0.423004E+09 | 0.140039E+09 | 0.721911E+09 | 0.450963E+09 |
Annual Sum or Average | 0.437572E+10 | 0.253194E+10 | 0.184379E+10 | 0.708458E+10 | 0.237084E+10 |
Minimum of Months | 0.165218E+09 | 10395519.34 | 0.130279E+09 | 0.406047E+09 | 11898158.22 |
Maximum of Months | 0.563043E+09 | 0.423837E+09 | 0.174968E+09 | 0.769516E+09 | 0.450963E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.382432E+09 | 0.00 | 0.382432E+09 | 29321346.69 | 0.252060E+10 |
February | 0.421798E+09 | 0.00 | 0.421798E+09 | 0.129204E+09 | 0.197883E+10 |
March | 0.611267E+09 | 24197.95 | 0.611243E+09 | 0.346072E+09 | 0.178844E+10 |
April | 0.686918E+09 | 8750953.90 | 0.678167E+09 | 0.774800E+09 | 0.912424E+09 |
May | 0.838485E+09 | 61793379.53 | 0.776691E+09 | 0.140538E+10 | 0.478564E+09 |
June | 0.862899E+09 | 0.107526E+09 | 0.755372E+09 | 0.194130E+10 | 0.211103E+09 |
July | 0.823767E+09 | 80802541.81 | 0.742965E+09 | 0.184816E+10 | 0.164441E+09 |
August | 0.696706E+09 | 16575260.69 | 0.680131E+09 | 0.143403E+10 | 0.257361E+09 |
September | 0.586582E+09 | 741339.97 | 0.585841E+09 | 0.101489E+10 | 0.561671E+09 |
October | 0.502433E+09 | 0.00 | 0.502433E+09 | 0.506132E+09 | 0.108471E+10 |
November | 0.392527E+09 | 0.00 | 0.392527E+09 | 90106958.35 | 0.199711E+10 |
December | 0.379470E+09 | 0.00 | 0.379470E+09 | 20887898.89 | 0.274418E+10 |
Annual Sum or Average | 0.718528E+10 | 0.276214E+09 | 0.690907E+10 | 0.954029E+10 | 0.146994E+11 |
Minimum of Months | 0.379470E+09 | 0.00 | 0.379470E+09 | 20887898.89 | 0.164441E+09 |
Maximum of Months | 0.862899E+09 | 0.107526E+09 | 0.776691E+09 | 0.194130E+10 | 0.274418E+10 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.382432E+09 | 0.00 | 0.382432E+09 | 21770516.75 | 0.259902E+10 |
February | 0.421798E+09 | 0.00 | 0.421798E+09 | 0.114897E+09 | 0.203528E+10 |
March | 0.611267E+09 | 24197.95 | 0.611243E+09 | 0.320599E+09 | 0.183628E+10 |
April | 0.686918E+09 | 8750953.90 | 0.678167E+09 | 0.750948E+09 | 0.938932E+09 |
May | 0.838485E+09 | 61793379.53 | 0.776691E+09 | 0.138086E+10 | 0.494807E+09 |
June | 0.862899E+09 | 0.107526E+09 | 0.755372E+09 | 0.191715E+10 | 0.220360E+09 |
July | 0.823767E+09 | 80802541.81 | 0.742965E+09 | 0.182345E+10 | 0.173956E+09 |
August | 0.696706E+09 | 16575260.69 | 0.680131E+09 | 0.141064E+10 | 0.269457E+09 |
September | 0.586582E+09 | 741339.97 | 0.585841E+09 | 0.997222E+09 | 0.579672E+09 |
October | 0.502433E+09 | 0.00 | 0.502433E+09 | 0.486695E+09 | 0.111502E+10 |
November | 0.392527E+09 | 0.00 | 0.392527E+09 | 76964423.64 | 0.205363E+10 |
December | 0.379470E+09 | 0.00 | 0.379470E+09 | 15868861.15 | 0.282780E+10 |
Annual Sum or Average | 0.718528E+10 | 0.276214E+09 | 0.690907E+10 | 0.931707E+10 | 0.151442E+11 |
Minimum of Months | 0.379470E+09 | 0.00 | 0.379470E+09 | 15868861.15 | 0.173956E+09 |
Maximum of Months | 0.862899E+09 | 0.107526E+09 | 0.776691E+09 | 0.191715E+10 | 0.282780E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54635219.79 | 0.00 | 54635219.79 | 9689181.94 | 0.331840E+09 |
February | 60259072.44 | 0.00 | 60259072.44 | 30116821.77 | 0.262774E+09 |
March | 87327152.96 | 3456.98 | 87323695.98 | 69203478.95 | 0.242328E+09 |
April | 98134921.78 | 1250183.62 | 96884738.16 | 0.147049E+09 | 0.127681E+09 |
May | 0.119788E+09 | 8827959.99 | 0.110960E+09 | 0.249244E+09 | 73270828.86 |
June | 0.123276E+09 | 15361483.16 | 0.107914E+09 | 0.331738E+09 | 35962611.03 |
July | 0.117686E+09 | 11543657.45 | 0.106142E+09 | 0.322257E+09 | 29480117.60 |
August | 99533259.29 | 2367984.07 | 97165275.22 | 0.260549E+09 | 41489811.22 |
September | 83800633.79 | 105909.72 | 83694724.07 | 0.193516E+09 | 77320695.38 |
October | 71778804.06 | 0.00 | 71778804.06 | 0.105124E+09 | 0.144587E+09 |
November | 56077421.72 | 0.00 | 56077421.72 | 25326068.67 | 0.261987E+09 |
December | 54212081.06 | 0.00 | 54212081.06 | 7085779.52 | 0.358896E+09 |
Annual Sum or Average | 0.102651E+10 | 39460634.99 | 0.987047E+09 | 0.175090E+10 | 0.198762E+10 |
Minimum of Months | 54212081.06 | 0.00 | 54212081.06 | 7085779.52 | 29480117.60 |
Maximum of Months | 0.123276E+09 | 15361483.16 | 0.110960E+09 | 0.331738E+09 | 0.358896E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.544774E+09 | 0.295186E+09 | 0.249587E+09 | 0.535236E+09 | 0.113316E+10 |
February | 0.660391E+09 | 0.376560E+09 | 0.283831E+09 | 0.786724E+09 | 0.891001E+09 |
March | 0.901204E+09 | 0.496210E+09 | 0.404994E+09 | 0.118338E+10 | 0.822186E+09 |
April | 0.105137E+10 | 0.583122E+09 | 0.468243E+09 | 0.170821E+10 | 0.448240E+09 |
May | 0.111994E+10 | 0.608399E+09 | 0.511536E+09 | 0.207351E+10 | 0.271521E+09 |
June | 0.108427E+10 | 0.602903E+09 | 0.481366E+09 | 0.230093E+10 | 0.134482E+09 |
July | 0.100542E+10 | 0.525641E+09 | 0.479782E+09 | 0.217194E+10 | 0.111618E+09 |
August | 0.957753E+09 | 0.490444E+09 | 0.467309E+09 | 0.200073E+10 | 0.155286E+09 |
September | 0.919563E+09 | 0.525105E+09 | 0.394458E+09 | 0.178293E+10 | 0.277731E+09 |
October | 0.727299E+09 | 0.391760E+09 | 0.335538E+09 | 0.117348E+10 | 0.515575E+09 |
November | 0.630213E+09 | 0.366045E+09 | 0.264168E+09 | 0.745547E+09 | 0.889641E+09 |
December | 0.545185E+09 | 0.288898E+09 | 0.256287E+09 | 0.514224E+09 | 0.121904E+10 |
Annual Sum or Average | 0.101474E+11 | 0.555027E+10 | 0.459710E+10 | 0.169769E+11 | 0.686948E+10 |
Minimum of Months | 0.544774E+09 | 0.288898E+09 | 0.249587E+09 | 0.514224E+09 | 0.111618E+09 |
Maximum of Months | 0.111994E+10 | 0.608399E+09 | 0.511536E+09 | 0.230093E+10 | 0.121904E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.373955E+09 | 0.283356E+09 | 90599047.15 | 0.518397E+09 | 0.291778E+09 |
February | 0.317786E+09 | 0.225371E+09 | 92415031.30 | 0.452230E+09 | 0.234077E+09 |
March | 0.275237E+09 | 0.155935E+09 | 0.119302E+09 | 0.404909E+09 | 0.227851E+09 |
April | 0.185599E+09 | 69671463.64 | 0.115927E+09 | 0.327942E+09 | 0.129608E+09 |
May | 0.136098E+09 | 19958985.63 | 0.116139E+09 | 0.290739E+09 | 76895508.76 |
June | 0.112654E+09 | 7088195.76 | 0.105566E+09 | 0.313242E+09 | 36556876.46 |
July | 0.118216E+09 | 10480991.36 | 0.107735E+09 | 0.327862E+09 | 30011672.93 |
August | 0.149228E+09 | 37913864.16 | 0.111315E+09 | 0.371360E+09 | 42254212.82 |
September | 0.228697E+09 | 0.118819E+09 | 0.109878E+09 | 0.481067E+09 | 76923248.60 |
October | 0.324385E+09 | 0.220389E+09 | 0.103996E+09 | 0.554664E+09 | 0.138028E+09 |
November | 0.377825E+09 | 0.288994E+09 | 88830943.98 | 0.556632E+09 | 0.231728E+09 |
December | 0.383911E+09 | 0.288426E+09 | 95485408.74 | 0.525147E+09 | 0.309776E+09 |
Annual Sum or Average | 0.298359E+10 | 0.172640E+10 | 0.125719E+10 | 0.512419E+10 | 0.182549E+10 |
Minimum of Months | 0.112654E+09 | 7088195.76 | 88830943.98 | 0.290739E+09 | 30011672.93 |
Maximum of Months | 0.383911E+09 | 0.288994E+09 | 0.119302E+09 | 0.556632E+09 | 0.309776E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 69192058.57 | 0.00 | 69192058.57 | 9699465.98 | 0.397251E+09 |
February | 76314313.11 | 0.00 | 76314313.11 | 30771746.78 | 0.312545E+09 |
March | 0.110594E+09 | 4378.05 | 0.110590E+09 | 76954576.49 | 0.282010E+09 |
April | 0.124282E+09 | 1583278.67 | 0.122698E+09 | 0.152408E+09 | 0.146701E+09 |
May | 0.151704E+09 | 11180054.31 | 0.140524E+09 | 0.261848E+09 | 79991853.18 |
June | 0.156121E+09 | 19454349.17 | 0.136667E+09 | 0.352130E+09 | 36141521.31 |
July | 0.149041E+09 | 14619313.80 | 0.134422E+09 | 0.334954E+09 | 27755866.77 |
August | 0.126053E+09 | 2998902.41 | 0.123054E+09 | 0.260518E+09 | 43628237.09 |
September | 0.106128E+09 | 134127.98 | 0.105994E+09 | 0.184664E+09 | 98302012.27 |
October | 90903326.35 | 0.00 | 90903326.35 | 97415802.01 | 0.178832E+09 |
November | 71018516.32 | 0.00 | 71018516.32 | 21569404.34 | 0.319411E+09 |
December | 68656180.07 | 0.00 | 68656180.07 | 6897189.17 | 0.436676E+09 |
Annual Sum or Average | 0.130001E+10 | 49974404.39 | 0.125003E+10 | 0.178983E+10 | 0.235925E+10 |
Minimum of Months | 68656180.07 | 0.00 | 68656180.07 | 6897189.17 | 27755866.77 |
Maximum of Months | 0.156121E+09 | 19454349.17 | 0.140524E+09 | 0.352130E+09 | 0.436676E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 61906396.97 | 0.00 | 61906396.97 | 8678148.96 | 0.355422E+09 |
February | 68278705.09 | 0.00 | 68278705.09 | 27531598.44 | 0.279635E+09 |
March | 98949165.36 | 3917.06 | 98945248.31 | 68851551.17 | 0.252315E+09 |
April | 0.111195E+09 | 1416565.43 | 0.109779E+09 | 0.136360E+09 | 0.131254E+09 |
May | 0.135730E+09 | 10002836.96 | 0.125727E+09 | 0.234276E+09 | 71569014.13 |
June | 0.139682E+09 | 17405879.91 | 0.122276E+09 | 0.315052E+09 | 32335956.05 |
July | 0.133348E+09 | 13079955.45 | 0.120268E+09 | 0.299684E+09 | 24833279.17 |
August | 0.112780E+09 | 2683129.35 | 0.110097E+09 | 0.233087E+09 | 39034349.04 |
September | 94953316.23 | 120004.81 | 94833311.42 | 0.165220E+09 | 87951182.85 |
October | 81331550.52 | 0.00 | 81331550.52 | 87158287.16 | 0.160001E+09 |
November | 63540535.64 | 0.00 | 63540535.64 | 19298227.79 | 0.285778E+09 |
December | 61426944.44 | 0.00 | 61426944.44 | 6170941.28 | 0.390679E+09 |
Annual Sum or Average | 0.116312E+10 | 44712288.96 | 0.111841E+10 | 0.160137E+10 | 0.211081E+10 |
Minimum of Months | 61426944.44 | 0.00 | 61426944.44 | 6170941.28 | 24833279.17 |
Maximum of Months | 0.139682E+09 | 17405879.91 | 0.125727E+09 | 0.315052E+09 | 0.390679E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.139608E+10 | 0.105785E+10 | 0.338233E+09 | 0.188374E+10 | 0.101121E+10 |
February | 0.118639E+10 | 0.841376E+09 | 0.345013E+09 | 0.163449E+10 | 0.807486E+09 |
March | 0.102754E+10 | 0.582153E+09 | 0.445390E+09 | 0.145086E+10 | 0.780581E+09 |
April | 0.692896E+09 | 0.260104E+09 | 0.432792E+09 | 0.112017E+10 | 0.442517E+09 |
May | 0.508093E+09 | 74512840.84 | 0.433581E+09 | 0.936703E+09 | 0.253873E+09 |
June | 0.420571E+09 | 26462346.95 | 0.394108E+09 | 0.977051E+09 | 0.111476E+09 |
July | 0.441336E+09 | 39128663.92 | 0.402208E+09 | 0.101383E+10 | 86406988.30 |
August | 0.557114E+09 | 0.141544E+09 | 0.415570E+09 | 0.117952E+10 | 0.134174E+09 |
September | 0.853795E+09 | 0.443586E+09 | 0.410209E+09 | 0.160587E+10 | 0.286932E+09 |
October | 0.121103E+10 | 0.822779E+09 | 0.388248E+09 | 0.193390E+10 | 0.496248E+09 |
November | 0.141053E+10 | 0.107890E+10 | 0.331632E+09 | 0.199995E+10 | 0.817072E+09 |
December | 0.143326E+10 | 0.107678E+10 | 0.356475E+09 | 0.190602E+10 | 0.108605E+10 |
Annual Sum or Average | 0.111386E+11 | 0.644518E+10 | 0.469346E+10 | 0.176421E+11 | 0.631402E+10 |
Minimum of Months | 0.420571E+09 | 26462346.95 | 0.331632E+09 | 0.936703E+09 | 86406988.30 |
Maximum of Months | 0.143326E+10 | 0.107890E+10 | 0.445390E+09 | 0.199995E+10 | 0.108605E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 945.40 | 499.10 | 706.15 | 535.07 | 171.08 | 0.00 | 0.00 |
February | 908.61 | 441.73 | 664.38 | 471.17 | 193.21 | 0.00 | 0.00 |
March | 735.02 | 384.44 | 519.74 | 294.46 | 225.28 | 0.00 | 0.00 |
April | 582.55 | 228.87 | 362.15 | 135.95 | 226.20 | 0.00 | 0.00 |
May | 464.69 | 129.97 | 257.00 | 37.69 | 219.31 | 0.00 | 0.00 |
June | 487.18 | 61.58 | 219.82 | 13.83 | 205.99 | 0.00 | 0.00 |
July | 494.94 | 46.23 | 223.23 | 19.79 | 203.44 | 0.00 | 0.00 |
August | 581.96 | 70.38 | 281.79 | 71.59 | 210.20 | 0.00 | 0.00 |
September | 829.07 | 153.94 | 446.25 | 231.85 | 214.40 | 0.00 | 0.00 |
October | 971.45 | 252.42 | 612.55 | 416.17 | 196.38 | 0.00 | 0.00 |
November | 1034.04 | 423.10 | 737.24 | 563.91 | 173.33 | 0.00 | 0.00 |
December | 951.44 | 536.55 | 724.95 | 544.65 | 180.31 | 0.00 | 0.00 |
Annual Sum or Average | 747.72 | 268.18 | 478.50 | 276.88 | 201.63 | 0.00 | 0.00 |
Minimum of Months | 464.69 | 46.23 | 219.82 | 13.83 | 171.08 | 0.00 | 0.00 |
Maximum of Months | 1034.04 | 536.55 | 737.24 | 563.91 | 226.20 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2616.70 | 1532.11 | 1988.48 | 1506.73 | 481.75 | 0.00 | 0.00 |
February | 2509.76 | 1361.98 | 1870.85 | 1326.79 | 544.06 | 0.00 | 0.00 |
March | 2020.09 | 1189.69 | 1463.55 | 829.18 | 634.37 | 0.00 | 0.00 |
April | 1605.71 | 705.21 | 1019.80 | 382.82 | 636.98 | 0.00 | 0.00 |
May | 1287.95 | 392.29 | 723.68 | 106.13 | 617.55 | 0.00 | 0.00 |
June | 1365.90 | 178.79 | 618.99 | 38.95 | 580.04 | 0.00 | 0.00 |
July | 1386.34 | 134.89 | 628.60 | 55.73 | 572.87 | 0.00 | 0.00 |
August | 1627.47 | 208.33 | 793.51 | 201.60 | 591.90 | 0.00 | 0.00 |
September | 2317.02 | 446.85 | 1256.61 | 652.87 | 603.74 | 0.00 | 0.00 |
October | 2706.63 | 757.81 | 1724.89 | 1171.91 | 552.99 | 0.00 | 0.00 |
November | 2869.16 | 1285.20 | 2076.02 | 1587.93 | 488.09 | 0.00 | 0.00 |
December | 2628.00 | 1637.03 | 2041.42 | 1533.69 | 507.73 | 0.00 | 0.00 |
Annual Sum or Average | 2075.27 | 816.53 | 1347.44 | 779.68 | 567.76 | 0.00 | 0.00 |
Minimum of Months | 1287.95 | 134.89 | 618.99 | 38.95 | 481.75 | 0.00 | 0.00 |
Maximum of Months | 2869.16 | 1637.03 | 2076.02 | 1587.93 | 636.98 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3471.34 | 2041.31 | 2583.15 | 1957.32 | 625.82 | 0.00 | 0.00 |
February | 3335.01 | 1807.45 | 2430.34 | 1723.58 | 706.76 | 0.00 | 0.00 |
March | 2691.31 | 1580.35 | 1901.24 | 1077.15 | 824.09 | 0.00 | 0.00 |
April | 2149.87 | 931.53 | 1324.78 | 497.31 | 827.47 | 0.00 | 0.00 |
May | 1729.73 | 515.83 | 940.11 | 137.87 | 802.24 | 0.00 | 0.00 |
June | 1840.64 | 232.53 | 804.10 | 50.59 | 753.51 | 0.00 | 0.00 |
July | 1866.40 | 174.20 | 816.59 | 72.40 | 744.19 | 0.00 | 0.00 |
August | 2182.69 | 269.43 | 1030.81 | 261.90 | 768.91 | 0.00 | 0.00 |
September | 3088.37 | 578.37 | 1632.41 | 848.12 | 784.29 | 0.00 | 0.00 |
October | 3590.93 | 992.43 | 2240.73 | 1522.37 | 718.36 | 0.00 | 0.00 |
November | 3798.64 | 1706.39 | 2696.87 | 2062.81 | 634.06 | 0.00 | 0.00 |
December | 3485.01 | 2186.02 | 2651.92 | 1992.35 | 659.58 | 0.00 | 0.00 |
Annual Sum or Average | 2765.06 | 1081.15 | 1750.40 | 1012.84 | 737.56 | 0.00 | 0.00 |
Minimum of Months | 1729.73 | 174.20 | 804.10 | 50.59 | 625.82 | 0.00 | 0.00 |
Maximum of Months | 3798.64 | 2186.02 | 2696.87 | 2062.81 | 827.47 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 285.42 | 299.85 | 247.02 | 166.33 | 80.69 | 0.00 | 0.00 |
February | 307.15 | 264.94 | 252.26 | 157.31 | 94.95 | 0.00 | 0.00 |
March | 351.68 | 225.84 | 267.73 | 146.67 | 121.05 | 0.00 | 0.00 |
April | 411.04 | 117.93 | 260.91 | 128.99 | 131.92 | 0.00 | 0.00 |
May | 461.17 | 56.11 | 255.11 | 116.78 | 138.32 | 0.00 | 0.00 |
June | 520.93 | 19.68 | 242.25 | 109.47 | 132.78 | 0.00 | 0.00 |
July | 483.35 | 10.80 | 220.68 | 91.63 | 129.05 | 0.00 | 0.00 |
August | 468.03 | 22.10 | 226.65 | 101.24 | 125.41 | 0.00 | 0.00 |
September | 490.89 | 65.86 | 263.72 | 143.81 | 119.91 | 0.00 | 0.00 |
October | 428.02 | 130.71 | 272.32 | 170.80 | 101.51 | 0.00 | 0.00 |
November | 348.76 | 247.92 | 271.93 | 188.26 | 83.67 | 0.00 | 0.00 |
December | 271.93 | 325.94 | 245.09 | 162.93 | 82.16 | 0.00 | 0.00 |
Annual Sum or Average | 402.70 | 148.42 | 252.05 | 140.19 | 111.87 | 0.00 | 0.00 |
Minimum of Months | 271.93 | 10.80 | 220.68 | 91.63 | 80.69 | 0.00 | 0.00 |
Maximum of Months | 520.93 | 325.94 | 272.32 | 188.26 | 138.32 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 118.51 | 316.86 | 127.80 | 60.54 | 67.26 | 0.00 | 0.00 |
February | 151.31 | 279.88 | 145.81 | 64.15 | 81.66 | 0.00 | 0.00 |
March | 234.52 | 233.15 | 197.57 | 88.46 | 109.11 | 0.00 | 0.00 |
April | 341.16 | 120.63 | 227.17 | 102.60 | 124.57 | 0.00 | 0.00 |
May | 440.52 | 56.59 | 249.02 | 112.63 | 136.39 | 0.00 | 0.00 |
June | 521.84 | 19.96 | 246.35 | 112.66 | 133.68 | 0.00 | 0.00 |
July | 475.78 | 11.39 | 220.48 | 92.03 | 128.45 | 0.00 | 0.00 |
August | 423.80 | 23.42 | 208.10 | 87.97 | 120.13 | 0.00 | 0.00 |
September | 380.59 | 69.71 | 207.82 | 98.01 | 109.81 | 0.00 | 0.00 |
October | 266.24 | 139.22 | 178.00 | 88.52 | 89.48 | 0.00 | 0.00 |
November | 162.75 | 263.04 | 147.80 | 76.76 | 71.03 | 0.00 | 0.00 |
December | 104.47 | 348.58 | 121.99 | 55.25 | 66.75 | 0.00 | 0.00 |
Annual Sum or Average | 302.48 | 156.28 | 190.00 | 86.70 | 103.30 | 0.00 | 0.00 |
Minimum of Months | 104.47 | 11.39 | 121.99 | 55.25 | 66.75 | 0.00 | 0.00 |
Maximum of Months | 521.84 | 348.58 | 249.02 | 112.66 | 136.39 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 136.01 | 112.95 | 111.67 | 84.62 | 27.06 | 0.00 | 0.00 |
February | 129.94 | 101.98 | 105.07 | 74.51 | 30.55 | 0.00 | 0.00 |
March | 101.18 | 89.81 | 82.19 | 46.57 | 35.63 | 0.00 | 0.00 |
April | 80.16 | 56.73 | 57.27 | 21.50 | 35.77 | 0.00 | 0.00 |
May | 63.13 | 34.06 | 40.64 | 5.96 | 34.68 | 0.00 | 0.00 |
June | 68.78 | 17.71 | 34.76 | 2.19 | 32.58 | 0.00 | 0.00 |
July | 69.45 | 15.08 | 35.30 | 3.13 | 32.17 | 0.00 | 0.00 |
August | 83.39 | 21.01 | 44.56 | 11.32 | 33.24 | 0.00 | 0.00 |
September | 123.39 | 37.86 | 70.57 | 36.67 | 33.91 | 0.00 | 0.00 |
October | 143.00 | 60.00 | 96.87 | 65.81 | 31.06 | 0.00 | 0.00 |
November | 151.16 | 95.54 | 116.59 | 89.18 | 27.41 | 0.00 | 0.00 |
December | 136.84 | 118.82 | 114.65 | 86.13 | 28.51 | 0.00 | 0.00 |
Annual Sum or Average | 107.03 | 63.27 | 75.67 | 43.79 | 31.89 | 0.00 | 0.00 |
Minimum of Months | 63.13 | 15.08 | 34.76 | 2.19 | 27.06 | 0.00 | 0.00 |
Maximum of Months | 151.16 | 118.82 | 116.59 | 89.18 | 35.77 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3.02 | 94.50 | 16.32 | 0.00 | 16.32 | 0.00 | 0.00 |
February | 9.48 | 81.91 | 19.93 | 0.00 | 19.93 | 0.00 | 0.00 |
March | 19.94 | 66.54 | 26.09 | 0.00 | 26.09 | 0.00 | 0.00 |
April | 42.15 | 31.97 | 30.29 | 0.39 | 29.91 | 0.00 | 0.00 |
May | 71.01 | 13.78 | 35.78 | 2.64 | 33.15 | 0.00 | 0.00 |
June | 100.07 | 4.49 | 38.05 | 4.74 | 33.31 | 0.00 | 0.00 |
July | 93.64 | 2.36 | 35.16 | 3.45 | 31.71 | 0.00 | 0.00 |
August | 74.29 | 5.34 | 29.73 | 0.71 | 29.03 | 0.00 | 0.00 |
September | 53.58 | 17.32 | 25.87 | 0.03 | 25.84 | 0.00 | 0.00 |
October | 28.15 | 37.37 | 21.44 | 0.00 | 21.44 | 0.00 | 0.00 |
November | 7.24 | 76.00 | 17.31 | 0.00 | 17.31 | 0.00 | 0.00 |
December | 2.07 | 104.85 | 16.19 | 0.00 | 16.19 | 0.00 | 0.00 |
Annual Sum or Average | 42.23 | 44.53 | 26.04 | 1.00 | 25.04 | 0.00 | 0.00 |
Minimum of Months | 2.07 | 2.36 | 16.19 | 0.00 | 16.19 | 0.00 | 0.00 |
Maximum of Months | 100.07 | 104.85 | 38.05 | 4.74 | 33.31 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 271.27 | 294.41 | 241.32 | 160.90 | 80.42 | 0.00 | 0.00 |
February | 324.32 | 257.20 | 267.86 | 170.99 | 96.87 | 0.00 | 0.00 |
March | 345.31 | 212.84 | 271.01 | 150.86 | 120.15 | 0.00 | 0.00 |
April | 422.62 | 106.98 | 274.43 | 139.37 | 135.06 | 0.00 | 0.00 |
May | 465.96 | 50.66 | 259.90 | 121.04 | 138.86 | 0.00 | 0.00 |
June | 537.90 | 18.27 | 252.63 | 119.04 | 133.59 | 0.00 | 0.00 |
July | 502.05 | 10.32 | 231.84 | 102.05 | 129.80 | 0.00 | 0.00 |
August | 481.74 | 20.69 | 234.52 | 105.72 | 128.80 | 0.00 | 0.00 |
September | 488.59 | 60.46 | 265.63 | 147.14 | 118.49 | 0.00 | 0.00 |
October | 396.67 | 125.46 | 256.89 | 155.42 | 101.47 | 0.00 | 0.00 |
November | 333.11 | 240.56 | 267.34 | 182.11 | 85.23 | 0.00 | 0.00 |
December | 265.93 | 319.45 | 245.12 | 161.62 | 83.50 | 0.00 | 0.00 |
Annual Sum or Average | 403.14 | 142.57 | 255.51 | 142.75 | 112.76 | 0.00 | 0.00 |
Minimum of Months | 265.93 | 10.32 | 231.84 | 102.05 | 80.42 | 0.00 | 0.00 |
Maximum of Months | 537.90 | 319.45 | 274.43 | 182.11 | 138.86 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 92.32 | 298.18 | 122.10 | 55.11 | 66.99 | 0.00 | 0.00 |
February | 156.42 | 258.81 | 161.41 | 77.83 | 83.58 | 0.00 | 0.00 |
March | 223.98 | 214.02 | 200.85 | 92.64 | 108.21 | 0.00 | 0.00 |
April | 351.94 | 109.59 | 240.68 | 112.98 | 127.71 | 0.00 | 0.00 |
May | 442.76 | 52.94 | 253.81 | 116.88 | 136.93 | 0.00 | 0.00 |
June | 535.17 | 19.14 | 256.73 | 122.24 | 134.50 | 0.00 | 0.00 |
July | 491.24 | 11.14 | 231.64 | 102.44 | 129.20 | 0.00 | 0.00 |
August | 434.00 | 22.17 | 215.97 | 92.45 | 123.52 | 0.00 | 0.00 |
September | 373.03 | 63.35 | 209.73 | 101.34 | 108.39 | 0.00 | 0.00 |
October | 231.25 | 128.74 | 162.58 | 73.14 | 89.44 | 0.00 | 0.00 |
November | 136.28 | 243.02 | 143.21 | 70.62 | 72.60 | 0.00 | 0.00 |
December | 84.25 | 327.14 | 122.02 | 53.93 | 68.09 | 0.00 | 0.00 |
Annual Sum or Average | 296.62 | 145.16 | 193.45 | 89.26 | 104.19 | 0.00 | 0.00 |
Minimum of Months | 84.25 | 11.14 | 122.02 | 53.93 | 66.99 | 0.00 | 0.00 |
Maximum of Months | 535.17 | 327.14 | 256.73 | 122.24 | 136.93 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 317.04 | 354.08 | 277.32 | 183.34 | 93.98 | 0.00 | 0.00 |
February | 323.32 | 315.01 | 270.83 | 161.45 | 109.38 | 0.00 | 0.00 |
March | 294.31 | 274.37 | 234.60 | 100.90 | 133.70 | 0.00 | 0.00 |
April | 292.33 | 152.73 | 189.72 | 47.42 | 142.30 | 0.00 | 0.00 |
May | 308.41 | 79.72 | 165.58 | 18.63 | 146.95 | 0.00 | 0.00 |
June | 373.65 | 35.47 | 157.76 | 15.01 | 142.75 | 0.00 | 0.00 |
July | 361.52 | 24.84 | 152.65 | 14.25 | 138.40 | 0.00 | 0.00 |
August | 351.33 | 41.20 | 160.97 | 26.06 | 134.90 | 0.00 | 0.00 |
September | 396.13 | 99.36 | 208.95 | 79.51 | 129.43 | 0.00 | 0.00 |
October | 391.59 | 172.37 | 256.34 | 142.60 | 113.74 | 0.00 | 0.00 |
November | 359.21 | 301.83 | 290.12 | 193.22 | 96.89 | 0.00 | 0.00 |
December | 313.01 | 380.70 | 283.49 | 186.62 | 96.87 | 0.00 | 0.00 |
Annual Sum or Average | 340.13 | 185.34 | 220.38 | 97.04 | 123.34 | 0.00 | 0.00 |
Minimum of Months | 292.33 | 24.84 | 152.65 | 14.25 | 93.98 | 0.00 | 0.00 |
Maximum of Months | 396.13 | 380.70 | 290.12 | 193.22 | 146.95 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 283.93 | 296.48 | 247.02 | 166.33 | 80.69 | 0.00 | 0.00 |
February | 305.18 | 261.46 | 252.26 | 157.31 | 94.95 | 0.00 | 0.00 |
March | 348.36 | 222.55 | 267.73 | 146.67 | 121.05 | 0.00 | 0.00 |
April | 407.24 | 115.09 | 260.91 | 128.99 | 131.92 | 0.00 | 0.00 |
May | 457.89 | 53.69 | 255.11 | 116.78 | 138.32 | 0.00 | 0.00 |
June | 518.49 | 18.41 | 242.25 | 109.47 | 132.78 | 0.00 | 0.00 |
July | 480.78 | 9.91 | 220.68 | 91.63 | 129.05 | 0.00 | 0.00 |
August | 465.31 | 20.73 | 226.65 | 101.24 | 125.41 | 0.00 | 0.00 |
September | 487.26 | 63.50 | 263.72 | 143.81 | 119.91 | 0.00 | 0.00 |
October | 425.19 | 127.78 | 272.32 | 170.80 | 101.51 | 0.00 | 0.00 |
November | 347.21 | 243.78 | 271.93 | 188.26 | 83.67 | 0.00 | 0.00 |
December | 271.51 | 322.08 | 245.09 | 162.93 | 82.16 | 0.00 | 0.00 |
Annual Sum or Average | 400.20 | 145.74 | 252.05 | 140.19 | 111.87 | 0.00 | 0.00 |
Minimum of Months | 271.51 | 9.91 | 220.68 | 91.63 | 80.69 | 0.00 | 0.00 |
Maximum of Months | 518.49 | 322.08 | 272.32 | 188.26 | 138.32 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 119.02 | 312.16 | 127.80 | 60.54 | 67.26 | 0.00 | 0.00 |
February | 151.26 | 275.25 | 145.81 | 64.15 | 81.66 | 0.00 | 0.00 |
March | 232.92 | 229.72 | 197.57 | 88.46 | 109.11 | 0.00 | 0.00 |
April | 338.29 | 118.13 | 227.17 | 102.60 | 124.57 | 0.00 | 0.00 |
May | 437.68 | 54.35 | 249.02 | 112.63 | 136.39 | 0.00 | 0.00 |
June | 519.30 | 18.74 | 246.35 | 112.66 | 133.68 | 0.00 | 0.00 |
July | 473.25 | 10.53 | 220.48 | 92.03 | 128.45 | 0.00 | 0.00 |
August | 421.75 | 22.04 | 208.10 | 87.97 | 120.13 | 0.00 | 0.00 |
September | 378.34 | 67.08 | 207.82 | 98.01 | 109.81 | 0.00 | 0.00 |
October | 264.98 | 136.15 | 178.00 | 88.52 | 89.48 | 0.00 | 0.00 |
November | 163.21 | 257.36 | 147.80 | 76.76 | 71.03 | 0.00 | 0.00 |
December | 105.48 | 343.38 | 121.99 | 55.25 | 66.75 | 0.00 | 0.00 |
Annual Sum or Average | 301.14 | 153.16 | 190.00 | 86.70 | 103.30 | 0.00 | 0.00 |
Minimum of Months | 105.48 | 10.53 | 121.99 | 55.25 | 66.75 | 0.00 | 0.00 |
Maximum of Months | 519.30 | 343.38 | 249.02 | 112.66 | 136.39 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 266.88 | 155.78 | 204.76 | 155.16 | 49.61 | 0.00 | 0.00 |
February | 257.54 | 135.84 | 192.65 | 136.63 | 56.02 | 0.00 | 0.00 |
March | 207.52 | 115.34 | 150.71 | 85.38 | 65.33 | 0.00 | 0.00 |
April | 173.32 | 58.86 | 105.01 | 39.42 | 65.59 | 0.00 | 0.00 |
May | 151.60 | 26.13 | 74.52 | 10.93 | 63.59 | 0.00 | 0.00 |
June | 171.89 | 8.37 | 63.74 | 4.01 | 59.73 | 0.00 | 0.00 |
July | 172.68 | 4.44 | 64.73 | 5.74 | 58.99 | 0.00 | 0.00 |
August | 192.26 | 9.83 | 81.71 | 20.76 | 60.95 | 0.00 | 0.00 |
September | 253.22 | 31.25 | 129.40 | 67.23 | 62.17 | 0.00 | 0.00 |
October | 285.55 | 65.18 | 177.62 | 120.68 | 56.94 | 0.00 | 0.00 |
November | 296.88 | 126.17 | 213.78 | 163.52 | 50.26 | 0.00 | 0.00 |
December | 269.53 | 168.37 | 210.22 | 157.93 | 52.28 | 0.00 | 0.00 |
Annual Sum or Average | 224.65 | 75.18 | 138.75 | 80.29 | 58.47 | 0.00 | 0.00 |
Minimum of Months | 151.60 | 4.44 | 63.74 | 4.01 | 49.61 | 0.00 | 0.00 |
Maximum of Months | 296.88 | 168.37 | 213.78 | 163.52 | 65.59 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 10.95 | 941.09 | 142.78 | 0.00 | 142.78 | 0.00 | 0.00 |
February | 53.41 | 817.97 | 174.35 | 0.00 | 174.35 | 0.00 | 0.00 |
March | 129.21 | 667.73 | 228.22 | 0.01 | 228.21 | 0.00 | 0.00 |
April | 298.92 | 352.02 | 265.01 | 3.38 | 261.64 | 0.00 | 0.00 |
May | 524.71 | 178.68 | 313.05 | 23.07 | 289.98 | 0.00 | 0.00 |
June | 748.96 | 81.44 | 332.91 | 41.48 | 291.42 | 0.00 | 0.00 |
July | 690.02 | 61.40 | 307.56 | 30.17 | 277.39 | 0.00 | 0.00 |
August | 535.40 | 96.09 | 260.12 | 6.19 | 253.93 | 0.00 | 0.00 |
September | 391.55 | 216.69 | 226.30 | 0.29 | 226.02 | 0.00 | 0.00 |
October | 188.97 | 404.98 | 187.59 | 0.00 | 187.59 | 0.00 | 0.00 |
November | 34.76 | 770.49 | 151.44 | 0.00 | 151.44 | 0.00 | 0.00 |
December | 7.80 | 1024.56 | 141.68 | 0.00 | 141.68 | 0.00 | 0.00 |
Annual Sum or Average | 302.52 | 466.12 | 227.84 | 8.76 | 219.09 | 0.00 | 0.00 |
Minimum of Months | 7.80 | 61.40 | 141.68 | 0.00 | 141.68 | 0.00 | 0.00 |
Maximum of Months | 748.96 | 1024.56 | 332.91 | 41.48 | 291.42 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 8.13 | 970.36 | 142.78 | 0.00 | 142.78 | 0.00 | 0.00 |
February | 47.49 | 841.30 | 174.35 | 0.00 | 174.35 | 0.00 | 0.00 |
March | 119.70 | 685.59 | 228.22 | 0.01 | 228.21 | 0.00 | 0.00 |
April | 289.72 | 362.24 | 265.01 | 3.38 | 261.64 | 0.00 | 0.00 |
May | 515.56 | 184.74 | 313.05 | 23.07 | 289.98 | 0.00 | 0.00 |
June | 739.64 | 85.02 | 332.91 | 41.48 | 291.42 | 0.00 | 0.00 |
July | 680.80 | 64.95 | 307.56 | 30.17 | 277.39 | 0.00 | 0.00 |
August | 526.67 | 100.60 | 260.12 | 6.19 | 253.93 | 0.00 | 0.00 |
September | 384.73 | 223.64 | 226.30 | 0.29 | 226.02 | 0.00 | 0.00 |
October | 181.71 | 416.30 | 187.59 | 0.00 | 187.59 | 0.00 | 0.00 |
November | 29.69 | 792.30 | 151.44 | 0.00 | 151.44 | 0.00 | 0.00 |
December | 5.92 | 1055.78 | 141.68 | 0.00 | 141.68 | 0.00 | 0.00 |
Annual Sum or Average | 295.44 | 480.22 | 227.84 | 8.76 | 219.09 | 0.00 | 0.00 |
Minimum of Months | 5.92 | 64.95 | 141.68 | 0.00 | 141.68 | 0.00 | 0.00 |
Maximum of Months | 739.64 | 1055.78 | 332.91 | 41.48 | 291.42 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 372.69 | 631.60 | 363.41 | 216.00 | 147.41 | 0.00 | 0.00 |
February | 506.20 | 555.30 | 429.25 | 248.81 | 180.43 | 0.00 | 0.00 |
March | 606.37 | 470.05 | 471.84 | 243.48 | 228.35 | 0.00 | 0.00 |
April | 835.69 | 265.60 | 515.08 | 252.33 | 262.75 | 0.00 | 0.00 |
May | 973.70 | 155.38 | 513.67 | 237.90 | 275.77 | 0.00 | 0.00 |
June | 1136.21 | 79.53 | 509.34 | 241.26 | 268.07 | 0.00 | 0.00 |
July | 1053.47 | 63.72 | 463.46 | 204.47 | 258.98 | 0.00 | 0.00 |
August | 982.48 | 88.81 | 450.46 | 198.15 | 252.31 | 0.00 | 0.00 |
September | 945.83 | 164.37 | 475.33 | 248.47 | 226.86 | 0.00 | 0.00 |
October | 681.11 | 294.65 | 419.45 | 228.55 | 190.90 | 0.00 | 0.00 |
November | 496.74 | 518.29 | 410.54 | 252.72 | 157.82 | 0.00 | 0.00 |
December | 358.89 | 672.98 | 367.13 | 215.55 | 151.58 | 0.00 | 0.00 |
Annual Sum or Average | 746.57 | 328.97 | 448.93 | 231.99 | 216.94 | 0.00 | 0.00 |
Minimum of Months | 358.89 | 63.72 | 363.41 | 198.15 | 147.41 | 0.00 | 0.00 |
Maximum of Months | 1136.21 | 672.98 | 515.08 | 252.72 | 275.77 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 678.60 | 626.99 | 570.18 | 394.96 | 175.23 | 0.00 | 0.00 |
February | 677.02 | 555.86 | 550.17 | 347.79 | 202.38 | 0.00 | 0.00 |
March | 589.01 | 483.81 | 461.88 | 217.35 | 244.52 | 0.00 | 0.00 |
April | 542.90 | 277.29 | 358.17 | 101.51 | 256.66 | 0.00 | 0.00 |
May | 533.09 | 149.50 | 297.02 | 35.73 | 261.29 | 0.00 | 0.00 |
June | 633.21 | 68.29 | 276.38 | 24.43 | 251.95 | 0.00 | 0.00 |
July | 614.45 | 50.88 | 270.21 | 24.95 | 245.26 | 0.00 | 0.00 |
August | 624.12 | 80.41 | 297.17 | 54.97 | 242.20 | 0.00 | 0.00 |
September | 754.10 | 182.12 | 406.97 | 171.23 | 235.74 | 0.00 | 0.00 |
October | 786.29 | 307.13 | 516.45 | 307.19 | 209.26 | 0.00 | 0.00 |
November | 763.98 | 525.34 | 596.10 | 416.24 | 179.86 | 0.00 | 0.00 |
December | 676.04 | 673.92 | 583.68 | 402.02 | 181.66 | 0.00 | 0.00 |
Annual Sum or Average | 655.70 | 330.70 | 431.31 | 207.38 | 223.93 | 0.00 | 0.00 |
Minimum of Months | 533.09 | 50.88 | 270.21 | 24.43 | 175.23 | 0.00 | 0.00 |
Maximum of Months | 786.29 | 673.92 | 596.10 | 416.24 | 261.29 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.253215E+10 | 0.133678E+10 | 0.189136E+10 | 0.143314E+10 | 0.458222E+09 | 0.00 | 0.00 |
February | 0.219810E+10 | 0.106864E+10 | 0.160727E+10 | 0.113986E+10 | 0.467406E+09 | 0.00 | 0.00 |
March | 0.196867E+10 | 0.102970E+10 | 0.139207E+10 | 0.788679E+09 | 0.603391E+09 | 0.00 | 0.00 |
April | 0.150998E+10 | 0.593222E+09 | 0.938702E+09 | 0.352379E+09 | 0.586322E+09 | 0.00 | 0.00 |
May | 0.124461E+10 | 0.348122E+09 | 0.688337E+09 | 0.100947E+09 | 0.587390E+09 | 0.00 | 0.00 |
June | 0.126276E+10 | 0.159608E+09 | 0.569764E+09 | 35850177.24 | 0.533914E+09 | 0.00 | 0.00 |
July | 0.132564E+10 | 0.123827E+09 | 0.597898E+09 | 53010019.83 | 0.544888E+09 | 0.00 | 0.00 |
August | 0.155871E+10 | 0.188494E+09 | 0.754750E+09 | 0.191758E+09 | 0.562992E+09 | 0.00 | 0.00 |
September | 0.214894E+10 | 0.399013E+09 | 0.115668E+10 | 0.600953E+09 | 0.555729E+09 | 0.00 | 0.00 |
October | 0.260192E+10 | 0.676070E+09 | 0.164065E+10 | 0.111467E+10 | 0.525978E+09 | 0.00 | 0.00 |
November | 0.268024E+10 | 0.109668E+10 | 0.191093E+10 | 0.146165E+10 | 0.449279E+09 | 0.00 | 0.00 |
December | 0.254834E+10 | 0.143710E+10 | 0.194172E+10 | 0.145878E+10 | 0.482936E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.235801E+11 | 0.845725E+10 | 0.150901E+11 | 0.873168E+10 | 0.635845E+10 | 0.00 | 0.00 |
Minimum of Months | 0.124461E+10 | 0.123827E+09 | 0.569764E+09 | 35850177.24 | 0.449279E+09 | 0.00 | 0.00 |
Maximum of Months | 0.268024E+10 | 0.143710E+10 | 0.194172E+10 | 0.146165E+10 | 0.603391E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.700856E+10 | 0.410361E+10 | 0.532594E+10 | 0.403562E+10 | 0.129032E+10 | 0.00 | 0.00 |
February | 0.607162E+10 | 0.329491E+10 | 0.452597E+10 | 0.320978E+10 | 0.131618E+10 | 0.00 | 0.00 |
March | 0.541060E+10 | 0.318646E+10 | 0.391998E+10 | 0.222087E+10 | 0.169911E+10 | 0.00 | 0.00 |
April | 0.416200E+10 | 0.182792E+10 | 0.264332E+10 | 0.992277E+09 | 0.165105E+10 | 0.00 | 0.00 |
May | 0.344964E+10 | 0.105071E+10 | 0.193831E+10 | 0.284261E+09 | 0.165405E+10 | 0.00 | 0.00 |
June | 0.354041E+10 | 0.463413E+09 | 0.160442E+10 | 0.100952E+09 | 0.150347E+10 | 0.00 | 0.00 |
July | 0.371316E+10 | 0.361294E+09 | 0.168364E+10 | 0.149273E+09 | 0.153437E+10 | 0.00 | 0.00 |
August | 0.435902E+10 | 0.557988E+09 | 0.212533E+10 | 0.539978E+09 | 0.158535E+10 | 0.00 | 0.00 |
September | 0.600572E+10 | 0.115823E+10 | 0.325714E+10 | 0.169224E+10 | 0.156490E+10 | 0.00 | 0.00 |
October | 0.724944E+10 | 0.202971E+10 | 0.461996E+10 | 0.313884E+10 | 0.148112E+10 | 0.00 | 0.00 |
November | 0.743686E+10 | 0.333124E+10 | 0.538106E+10 | 0.411592E+10 | 0.126514E+10 | 0.00 | 0.00 |
December | 0.703884E+10 | 0.438462E+10 | 0.546774E+10 | 0.410783E+10 | 0.135992E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.654459E+11 | 0.257501E+11 | 0.424928E+11 | 0.245878E+11 | 0.179050E+11 | 0.00 | 0.00 |
Minimum of Months | 0.344964E+10 | 0.361294E+09 | 0.160442E+10 | 0.100952E+09 | 0.126514E+10 | 0.00 | 0.00 |
Maximum of Months | 0.743686E+10 | 0.438462E+10 | 0.546774E+10 | 0.411592E+10 | 0.169911E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.929765E+10 | 0.546746E+10 | 0.691870E+10 | 0.524250E+10 | 0.167620E+10 | 0.00 | 0.00 |
February | 0.806806E+10 | 0.437258E+10 | 0.587949E+10 | 0.416969E+10 | 0.170980E+10 | 0.00 | 0.00 |
March | 0.720841E+10 | 0.423282E+10 | 0.509227E+10 | 0.288503E+10 | 0.220724E+10 | 0.00 | 0.00 |
April | 0.557245E+10 | 0.241451E+10 | 0.343383E+10 | 0.128902E+10 | 0.214480E+10 | 0.00 | 0.00 |
May | 0.463291E+10 | 0.138161E+10 | 0.251798E+10 | 0.369271E+09 | 0.214871E+10 | 0.00 | 0.00 |
June | 0.477095E+10 | 0.602723E+09 | 0.208423E+10 | 0.131142E+09 | 0.195309E+10 | 0.00 | 0.00 |
July | 0.499896E+10 | 0.466589E+09 | 0.218715E+10 | 0.193914E+09 | 0.199323E+10 | 0.00 | 0.00 |
August | 0.584611E+10 | 0.721632E+09 | 0.276092E+10 | 0.701462E+09 | 0.205946E+10 | 0.00 | 0.00 |
September | 0.800506E+10 | 0.149913E+10 | 0.423121E+10 | 0.219832E+10 | 0.203289E+10 | 0.00 | 0.00 |
October | 0.961796E+10 | 0.265811E+10 | 0.600158E+10 | 0.407753E+10 | 0.192406E+10 | 0.00 | 0.00 |
November | 0.984609E+10 | 0.442297E+10 | 0.699030E+10 | 0.534681E+10 | 0.164349E+10 | 0.00 | 0.00 |
December | 0.933424E+10 | 0.585502E+10 | 0.710291E+10 | 0.533630E+10 | 0.176661E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.871988E+11 | 0.340952E+11 | 0.552006E+11 | 0.319410E+11 | 0.232596E+11 | 0.00 | 0.00 |
Minimum of Months | 0.463291E+10 | 0.466589E+09 | 0.208423E+10 | 0.131142E+09 | 0.164349E+10 | 0.00 | 0.00 |
Maximum of Months | 0.984609E+10 | 0.585502E+10 | 0.710291E+10 | 0.534681E+10 | 0.220724E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.764461E+09 | 0.803110E+09 | 0.661628E+09 | 0.445502E+09 | 0.216126E+09 | 0.00 | 0.00 |
February | 0.743051E+09 | 0.640942E+09 | 0.610259E+09 | 0.380562E+09 | 0.229697E+09 | 0.00 | 0.00 |
March | 0.941931E+09 | 0.604882E+09 | 0.717083E+09 | 0.392853E+09 | 0.324229E+09 | 0.00 | 0.00 |
April | 0.106542E+10 | 0.305686E+09 | 0.676285E+09 | 0.334351E+09 | 0.341935E+09 | 0.00 | 0.00 |
May | 0.123519E+10 | 0.150278E+09 | 0.683278E+09 | 0.312791E+09 | 0.370487E+09 | 0.00 | 0.00 |
June | 0.135024E+10 | 51018238.40 | 0.627908E+09 | 0.283748E+09 | 0.344161E+09 | 0.00 | 0.00 |
July | 0.129460E+10 | 28926882.73 | 0.591061E+09 | 0.245426E+09 | 0.345635E+09 | 0.00 | 0.00 |
August | 0.125356E+10 | 59204246.92 | 0.607067E+09 | 0.271168E+09 | 0.335899E+09 | 0.00 | 0.00 |
September | 0.127240E+10 | 0.170700E+09 | 0.683569E+09 | 0.372750E+09 | 0.310819E+09 | 0.00 | 0.00 |
October | 0.114641E+10 | 0.350104E+09 | 0.729374E+09 | 0.457483E+09 | 0.271891E+09 | 0.00 | 0.00 |
November | 0.903990E+09 | 0.642602E+09 | 0.704840E+09 | 0.487965E+09 | 0.216875E+09 | 0.00 | 0.00 |
December | 0.728325E+09 | 0.872995E+09 | 0.656450E+09 | 0.436397E+09 | 0.220053E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.126996E+11 | 0.468045E+10 | 0.794880E+10 | 0.442100E+10 | 0.352781E+10 | 0.00 | 0.00 |
Minimum of Months | 0.728325E+09 | 28926882.73 | 0.591061E+09 | 0.245426E+09 | 0.216126E+09 | 0.00 | 0.00 |
Maximum of Months | 0.135024E+10 | 0.872995E+09 | 0.729374E+09 | 0.487965E+09 | 0.370487E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.317410E+09 | 0.848678E+09 | 0.342309E+09 | 0.162146E+09 | 0.180162E+09 | 0.00 | 0.00 |
February | 0.366053E+09 | 0.677090E+09 | 0.352733E+09 | 0.155192E+09 | 0.197541E+09 | 0.00 | 0.00 |
March | 0.628141E+09 | 0.624479E+09 | 0.529172E+09 | 0.236921E+09 | 0.292251E+09 | 0.00 | 0.00 |
April | 0.884280E+09 | 0.312677E+09 | 0.588821E+09 | 0.265930E+09 | 0.322892E+09 | 0.00 | 0.00 |
May | 0.117989E+10 | 0.151575E+09 | 0.666968E+09 | 0.301660E+09 | 0.365308E+09 | 0.00 | 0.00 |
June | 0.135260E+10 | 51731779.65 | 0.638530E+09 | 0.292021E+09 | 0.346509E+09 | 0.00 | 0.00 |
July | 0.127433E+10 | 30503366.87 | 0.590530E+09 | 0.246488E+09 | 0.344041E+09 | 0.00 | 0.00 |
August | 0.113512E+10 | 62738110.85 | 0.557372E+09 | 0.235622E+09 | 0.321750E+09 | 0.00 | 0.00 |
September | 0.986497E+09 | 0.180688E+09 | 0.538673E+09 | 0.254037E+09 | 0.284635E+09 | 0.00 | 0.00 |
October | 0.713107E+09 | 0.372897E+09 | 0.476768E+09 | 0.237094E+09 | 0.239674E+09 | 0.00 | 0.00 |
November | 0.421843E+09 | 0.681787E+09 | 0.383093E+09 | 0.198972E+09 | 0.184121E+09 | 0.00 | 0.00 |
December | 0.279810E+09 | 0.933625E+09 | 0.326751E+09 | 0.147971E+09 | 0.178780E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.953907E+10 | 0.492847E+10 | 0.599172E+10 | 0.273405E+10 | 0.325767E+10 | 0.00 | 0.00 |
Minimum of Months | 0.279810E+09 | 30503366.87 | 0.326751E+09 | 0.147971E+09 | 0.178780E+09 | 0.00 | 0.00 |
Maximum of Months | 0.135260E+10 | 0.933625E+09 | 0.666968E+09 | 0.301660E+09 | 0.365308E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.364276E+09 | 0.302527E+09 | 0.299104E+09 | 0.226640E+09 | 72464826.42 | 0.00 | 0.00 |
February | 0.314343E+09 | 0.246708E+09 | 0.254178E+09 | 0.180261E+09 | 73917324.87 | 0.00 | 0.00 |
March | 0.270989E+09 | 0.240542E+09 | 0.220146E+09 | 0.124724E+09 | 95422629.83 | 0.00 | 0.00 |
April | 0.207775E+09 | 0.147052E+09 | 0.148450E+09 | 55726088.50 | 92723544.22 | 0.00 | 0.00 |
May | 0.169092E+09 | 91237476.42 | 0.108857E+09 | 15964013.69 | 92892545.85 | 0.00 | 0.00 |
June | 0.178277E+09 | 45903492.19 | 90105188.78 | 5669429.11 | 84435759.67 | 0.00 | 0.00 |
July | 0.186005E+09 | 40382122.88 | 94554156.30 | 8383125.91 | 86171030.39 | 0.00 | 0.00 |
August | 0.223362E+09 | 56265884.66 | 0.119359E+09 | 30325060.49 | 89033931.16 | 0.00 | 0.00 |
September | 0.319834E+09 | 98128226.71 | 0.182921E+09 | 95036114.58 | 87885276.20 | 0.00 | 0.00 |
October | 0.383009E+09 | 0.160712E+09 | 0.259457E+09 | 0.176276E+09 | 83180150.54 | 0.00 | 0.00 |
November | 0.391794E+09 | 0.247648E+09 | 0.302200E+09 | 0.231149E+09 | 71050625.13 | 0.00 | 0.00 |
December | 0.366520E+09 | 0.318244E+09 | 0.307068E+09 | 0.230695E+09 | 76373138.43 | 0.00 | 0.00 |
Annual Sum or Average | 0.337528E+10 | 0.199535E+10 | 0.238640E+10 | 0.138085E+10 | 0.100555E+10 | 0.00 | 0.00 |
Minimum of Months | 0.169092E+09 | 40382122.88 | 90105188.78 | 5669429.11 | 71050625.13 | 0.00 | 0.00 |
Maximum of Months | 0.391794E+09 | 0.318244E+09 | 0.307068E+09 | 0.231149E+09 | 95422629.83 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 8095580.10 | 0.253119E+09 | 43713969.60 | 0.00 | 43713969.60 | 0.00 | 0.00 |
February | 22941600.30 | 0.198149E+09 | 48213648.10 | 0.00 | 48213648.10 | 0.00 | 0.00 |
March | 53414226.98 | 0.178209E+09 | 69870982.94 | 2765.95 | 69868216.99 | 0.00 | 0.00 |
April | 0.109258E+09 | 82859215.04 | 78518344.10 | 1000279.47 | 77518064.63 | 0.00 | 0.00 |
May | 0.190193E+09 | 36895010.82 | 95843144.60 | 7063304.15 | 88779840.45 | 0.00 | 0.00 |
June | 0.259390E+09 | 11649840.91 | 98633813.54 | 12290815.53 | 86342998.01 | 0.00 | 0.00 |
July | 0.250817E+09 | 6319132.76 | 94160895.41 | 9236150.10 | 84924745.31 | 0.00 | 0.00 |
August | 0.198965E+09 | 14312185.14 | 79637162.39 | 1894638.37 | 77742524.03 | 0.00 | 0.00 |
September | 0.138876E+09 | 44890868.47 | 67049393.63 | 84739.01 | 66964654.62 | 0.00 | 0.00 |
October | 75403720.57 | 0.100081E+09 | 57430655.00 | 0.00 | 57430655.00 | 0.00 | 0.00 |
November | 18761284.62 | 0.197004E+09 | 44867884.08 | 0.00 | 44867884.08 | 0.00 | 0.00 |
December | 5533813.66 | 0.280840E+09 | 43375413.74 | 0.00 | 43375413.74 | 0.00 | 0.00 |
Annual Sum or Average | 0.133165E+10 | 0.140433E+10 | 0.821315E+09 | 31572692.58 | 0.789743E+09 | 0.00 | 0.00 |
Minimum of Months | 5533813.66 | 6319132.76 | 43375413.74 | 0.00 | 43375413.74 | 0.00 | 0.00 |
Maximum of Months | 0.259390E+09 | 0.280840E+09 | 98633813.54 | 12290815.53 | 88779840.45 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.726566E+09 | 0.788534E+09 | 0.646361E+09 | 0.430960E+09 | 0.215402E+09 | 0.00 | 0.00 |
February | 0.784587E+09 | 0.622226E+09 | 0.648005E+09 | 0.413664E+09 | 0.234341E+09 | 0.00 | 0.00 |
March | 0.924875E+09 | 0.570067E+09 | 0.725871E+09 | 0.404058E+09 | 0.321813E+09 | 0.00 | 0.00 |
April | 0.109543E+10 | 0.277283E+09 | 0.711319E+09 | 0.361253E+09 | 0.350066E+09 | 0.00 | 0.00 |
May | 0.124804E+10 | 0.135700E+09 | 0.696105E+09 | 0.324180E+09 | 0.371925E+09 | 0.00 | 0.00 |
June | 0.139425E+10 | 47344481.51 | 0.654827E+09 | 0.308561E+09 | 0.346266E+09 | 0.00 | 0.00 |
July | 0.134469E+10 | 27645335.19 | 0.620963E+09 | 0.273320E+09 | 0.347643E+09 | 0.00 | 0.00 |
August | 0.129029E+10 | 55422129.02 | 0.628139E+09 | 0.283153E+09 | 0.344986E+09 | 0.00 | 0.00 |
September | 0.126644E+10 | 0.156703E+09 | 0.688511E+09 | 0.381390E+09 | 0.307121E+09 | 0.00 | 0.00 |
October | 0.106244E+10 | 0.336024E+09 | 0.688060E+09 | 0.416283E+09 | 0.271777E+09 | 0.00 | 0.00 |
November | 0.863425E+09 | 0.623534E+09 | 0.692953E+09 | 0.472029E+09 | 0.220924E+09 | 0.00 | 0.00 |
December | 0.712265E+09 | 0.855605E+09 | 0.656523E+09 | 0.432885E+09 | 0.223638E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.127133E+11 | 0.449609E+10 | 0.805764E+10 | 0.450174E+10 | 0.355590E+10 | 0.00 | 0.00 |
Minimum of Months | 0.712265E+09 | 27645335.19 | 0.620963E+09 | 0.273320E+09 | 0.215402E+09 | 0.00 | 0.00 |
Maximum of Months | 0.139425E+10 | 0.855605E+09 | 0.725871E+09 | 0.472029E+09 | 0.371925E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.247272E+09 | 0.798656E+09 | 0.327041E+09 | 0.147604E+09 | 0.179438E+09 | 0.00 | 0.00 |
February | 0.378418E+09 | 0.626118E+09 | 0.390478E+09 | 0.188293E+09 | 0.202185E+09 | 0.00 | 0.00 |
March | 0.599899E+09 | 0.573241E+09 | 0.537961E+09 | 0.248126E+09 | 0.289835E+09 | 0.00 | 0.00 |
April | 0.912234E+09 | 0.284069E+09 | 0.623855E+09 | 0.292832E+09 | 0.331023E+09 | 0.00 | 0.00 |
May | 0.118588E+10 | 0.141803E+09 | 0.679796E+09 | 0.313049E+09 | 0.366746E+09 | 0.00 | 0.00 |
June | 0.138715E+10 | 49603507.81 | 0.665449E+09 | 0.316834E+09 | 0.348614E+09 | 0.00 | 0.00 |
July | 0.131574E+10 | 29829026.63 | 0.620433E+09 | 0.274383E+09 | 0.346050E+09 | 0.00 | 0.00 |
August | 0.116244E+10 | 59383310.81 | 0.578444E+09 | 0.247607E+09 | 0.330837E+09 | 0.00 | 0.00 |
September | 0.966895E+09 | 0.164214E+09 | 0.543615E+09 | 0.262677E+09 | 0.280938E+09 | 0.00 | 0.00 |
October | 0.619386E+09 | 0.344824E+09 | 0.435454E+09 | 0.195894E+09 | 0.239560E+09 | 0.00 | 0.00 |
November | 0.353244E+09 | 0.629913E+09 | 0.371206E+09 | 0.183035E+09 | 0.188171E+09 | 0.00 | 0.00 |
December | 0.225651E+09 | 0.876206E+09 | 0.326824E+09 | 0.144459E+09 | 0.182365E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.935421E+10 | 0.457786E+10 | 0.610055E+10 | 0.281479E+10 | 0.328576E+10 | 0.00 | 0.00 |
Minimum of Months | 0.225651E+09 | 29829026.63 | 0.326824E+09 | 0.144459E+09 | 0.179438E+09 | 0.00 | 0.00 |
Maximum of Months | 0.138715E+10 | 0.876206E+09 | 0.679796E+09 | 0.316834E+09 | 0.366746E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.849155E+09 | 0.948366E+09 | 0.742775E+09 | 0.491065E+09 | 0.251710E+09 | 0.00 | 0.00 |
February | 0.782185E+09 | 0.762082E+09 | 0.655180E+09 | 0.390575E+09 | 0.264605E+09 | 0.00 | 0.00 |
March | 0.788283E+09 | 0.734862E+09 | 0.628360E+09 | 0.270247E+09 | 0.358112E+09 | 0.00 | 0.00 |
April | 0.757725E+09 | 0.395877E+09 | 0.491746E+09 | 0.122910E+09 | 0.368836E+09 | 0.00 | 0.00 |
May | 0.826044E+09 | 0.213520E+09 | 0.443490E+09 | 49891063.49 | 0.393599E+09 | 0.00 | 0.00 |
June | 0.968513E+09 | 91947669.64 | 0.408907E+09 | 38910104.08 | 0.369997E+09 | 0.00 | 0.00 |
July | 0.968291E+09 | 66520903.08 | 0.408857E+09 | 38172500.78 | 0.370684E+09 | 0.00 | 0.00 |
August | 0.940999E+09 | 0.110346E+09 | 0.431139E+09 | 69810394.97 | 0.361328E+09 | 0.00 | 0.00 |
September | 0.102677E+10 | 0.257547E+09 | 0.541591E+09 | 0.206100E+09 | 0.335491E+09 | 0.00 | 0.00 |
October | 0.104883E+10 | 0.461685E+09 | 0.686584E+09 | 0.381942E+09 | 0.304642E+09 | 0.00 | 0.00 |
November | 0.931064E+09 | 0.782339E+09 | 0.751982E+09 | 0.500836E+09 | 0.251146E+09 | 0.00 | 0.00 |
December | 0.838370E+09 | 0.101967E+10 | 0.759297E+09 | 0.499852E+09 | 0.259445E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.107262E+11 | 0.584476E+10 | 0.694991E+10 | 0.306031E+10 | 0.388960E+10 | 0.00 | 0.00 |
Minimum of Months | 0.757725E+09 | 66520903.08 | 0.408857E+09 | 38172500.78 | 0.251146E+09 | 0.00 | 0.00 |
Maximum of Months | 0.104883E+10 | 0.101967E+10 | 0.759297E+09 | 0.500836E+09 | 0.393599E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.760487E+09 | 0.794080E+09 | 0.661628E+09 | 0.445502E+09 | 0.216126E+09 | 0.00 | 0.00 |
February | 0.738298E+09 | 0.632531E+09 | 0.610259E+09 | 0.380562E+09 | 0.229697E+09 | 0.00 | 0.00 |
March | 0.933036E+09 | 0.596073E+09 | 0.717083E+09 | 0.392853E+09 | 0.324229E+09 | 0.00 | 0.00 |
April | 0.105555E+10 | 0.298326E+09 | 0.676285E+09 | 0.334351E+09 | 0.341935E+09 | 0.00 | 0.00 |
May | 0.122642E+10 | 0.143811E+09 | 0.683278E+09 | 0.312791E+09 | 0.370487E+09 | 0.00 | 0.00 |
June | 0.134394E+10 | 47707301.41 | 0.627908E+09 | 0.283748E+09 | 0.344161E+09 | 0.00 | 0.00 |
July | 0.128771E+10 | 26534318.94 | 0.591061E+09 | 0.245426E+09 | 0.345635E+09 | 0.00 | 0.00 |
August | 0.124629E+10 | 55523475.92 | 0.607067E+09 | 0.271168E+09 | 0.335899E+09 | 0.00 | 0.00 |
September | 0.126299E+10 | 0.164587E+09 | 0.683569E+09 | 0.372750E+09 | 0.310819E+09 | 0.00 | 0.00 |
October | 0.113884E+10 | 0.342251E+09 | 0.729374E+09 | 0.457483E+09 | 0.271891E+09 | 0.00 | 0.00 |
November | 0.899969E+09 | 0.631881E+09 | 0.704840E+09 | 0.487965E+09 | 0.216875E+09 | 0.00 | 0.00 |
December | 0.727225E+09 | 0.862654E+09 | 0.656450E+09 | 0.436397E+09 | 0.220053E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.126208E+11 | 0.459596E+10 | 0.794880E+10 | 0.442100E+10 | 0.352781E+10 | 0.00 | 0.00 |
Minimum of Months | 0.727225E+09 | 26534318.94 | 0.591061E+09 | 0.245426E+09 | 0.216126E+09 | 0.00 | 0.00 |
Maximum of Months | 0.134394E+10 | 0.862654E+09 | 0.729374E+09 | 0.487965E+09 | 0.370487E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.318775E+09 | 0.836095E+09 | 0.342309E+09 | 0.162146E+09 | 0.180162E+09 | 0.00 | 0.00 |
February | 0.365929E+09 | 0.665886E+09 | 0.352733E+09 | 0.155192E+09 | 0.197541E+09 | 0.00 | 0.00 |
March | 0.623850E+09 | 0.615283E+09 | 0.529172E+09 | 0.236921E+09 | 0.292251E+09 | 0.00 | 0.00 |
April | 0.876850E+09 | 0.306198E+09 | 0.588821E+09 | 0.265930E+09 | 0.322892E+09 | 0.00 | 0.00 |
May | 0.117227E+10 | 0.145566E+09 | 0.666968E+09 | 0.301660E+09 | 0.365308E+09 | 0.00 | 0.00 |
June | 0.134602E+10 | 48570282.31 | 0.638530E+09 | 0.292021E+09 | 0.346509E+09 | 0.00 | 0.00 |
July | 0.126756E+10 | 28204945.16 | 0.590530E+09 | 0.246488E+09 | 0.344041E+09 | 0.00 | 0.00 |
August | 0.112962E+10 | 59030982.89 | 0.557372E+09 | 0.235622E+09 | 0.321750E+09 | 0.00 | 0.00 |
September | 0.980662E+09 | 0.173875E+09 | 0.538673E+09 | 0.254037E+09 | 0.284635E+09 | 0.00 | 0.00 |
October | 0.709735E+09 | 0.364668E+09 | 0.476768E+09 | 0.237094E+09 | 0.239674E+09 | 0.00 | 0.00 |
November | 0.423036E+09 | 0.667088E+09 | 0.383093E+09 | 0.198972E+09 | 0.184121E+09 | 0.00 | 0.00 |
December | 0.282527E+09 | 0.919712E+09 | 0.326751E+09 | 0.147971E+09 | 0.178780E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.949683E+10 | 0.483018E+10 | 0.599172E+10 | 0.273405E+10 | 0.325767E+10 | 0.00 | 0.00 |
Minimum of Months | 0.282527E+09 | 28204945.16 | 0.326751E+09 | 0.147971E+09 | 0.178780E+09 | 0.00 | 0.00 |
Maximum of Months | 0.134602E+10 | 0.919712E+09 | 0.666968E+09 | 0.301660E+09 | 0.365308E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.714811E+09 | 0.417240E+09 | 0.548441E+09 | 0.415568E+09 | 0.132872E+09 | 0.00 | 0.00 |
February | 0.623048E+09 | 0.328618E+09 | 0.466063E+09 | 0.330528E+09 | 0.135536E+09 | 0.00 | 0.00 |
March | 0.555825E+09 | 0.308932E+09 | 0.403662E+09 | 0.228694E+09 | 0.174968E+09 | 0.00 | 0.00 |
April | 0.449236E+09 | 0.152570E+09 | 0.272199E+09 | 0.102180E+09 | 0.170019E+09 | 0.00 | 0.00 |
May | 0.406047E+09 | 69983790.43 | 0.199600E+09 | 29271767.90 | 0.170329E+09 | 0.00 | 0.00 |
June | 0.445551E+09 | 21692857.21 | 0.165218E+09 | 10395519.34 | 0.154822E+09 | 0.00 | 0.00 |
July | 0.462513E+09 | 11898158.22 | 0.173375E+09 | 15371379.69 | 0.158004E+09 | 0.00 | 0.00 |
August | 0.514949E+09 | 26341679.02 | 0.218858E+09 | 55604320.39 | 0.163253E+09 | 0.00 | 0.00 |
September | 0.656355E+09 | 80995671.79 | 0.335406E+09 | 0.174259E+09 | 0.161147E+09 | 0.00 | 0.00 |
October | 0.764817E+09 | 0.174582E+09 | 0.475742E+09 | 0.323222E+09 | 0.152520E+09 | 0.00 | 0.00 |
November | 0.769516E+09 | 0.327023E+09 | 0.554116E+09 | 0.423837E+09 | 0.130279E+09 | 0.00 | 0.00 |
December | 0.721911E+09 | 0.450963E+09 | 0.563043E+09 | 0.423004E+09 | 0.140039E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.708458E+10 | 0.237084E+10 | 0.437572E+10 | 0.253194E+10 | 0.184379E+10 | 0.00 | 0.00 |
Minimum of Months | 0.406047E+09 | 11898158.22 | 0.165218E+09 | 10395519.34 | 0.130279E+09 | 0.00 | 0.00 |
Maximum of Months | 0.769516E+09 | 0.450963E+09 | 0.563043E+09 | 0.423837E+09 | 0.174968E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 29321346.69 | 0.252060E+10 | 0.382432E+09 | 0.00 | 0.382432E+09 | 0.00 | 0.00 |
February | 0.129204E+09 | 0.197883E+10 | 0.421798E+09 | 0.00 | 0.421798E+09 | 0.00 | 0.00 |
March | 0.346072E+09 | 0.178844E+10 | 0.611267E+09 | 24197.95 | 0.611243E+09 | 0.00 | 0.00 |
April | 0.774800E+09 | 0.912424E+09 | 0.686918E+09 | 8750953.90 | 0.678167E+09 | 0.00 | 0.00 |
May | 0.140538E+10 | 0.478564E+09 | 0.838485E+09 | 61793379.53 | 0.776691E+09 | 0.00 | 0.00 |
June | 0.194130E+10 | 0.211103E+09 | 0.862899E+09 | 0.107526E+09 | 0.755372E+09 | 0.00 | 0.00 |
July | 0.184816E+10 | 0.164441E+09 | 0.823767E+09 | 80802541.81 | 0.742965E+09 | 0.00 | 0.00 |
August | 0.143403E+10 | 0.257361E+09 | 0.696706E+09 | 16575260.69 | 0.680131E+09 | 0.00 | 0.00 |
September | 0.101489E+10 | 0.561671E+09 | 0.586582E+09 | 741339.97 | 0.585841E+09 | 0.00 | 0.00 |
October | 0.506132E+09 | 0.108471E+10 | 0.502433E+09 | 0.00 | 0.502433E+09 | 0.00 | 0.00 |
November | 90106958.35 | 0.199711E+10 | 0.392527E+09 | 0.00 | 0.392527E+09 | 0.00 | 0.00 |
December | 20887898.89 | 0.274418E+10 | 0.379470E+09 | 0.00 | 0.379470E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.954029E+10 | 0.146994E+11 | 0.718528E+10 | 0.276214E+09 | 0.690907E+10 | 0.00 | 0.00 |
Minimum of Months | 20887898.89 | 0.164441E+09 | 0.379470E+09 | 0.00 | 0.379470E+09 | 0.00 | 0.00 |
Maximum of Months | 0.194130E+10 | 0.274418E+10 | 0.862899E+09 | 0.107526E+09 | 0.776691E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 21770516.75 | 0.259902E+10 | 0.382432E+09 | 0.00 | 0.382432E+09 | 0.00 | 0.00 |
February | 0.114897E+09 | 0.203528E+10 | 0.421798E+09 | 0.00 | 0.421798E+09 | 0.00 | 0.00 |
March | 0.320599E+09 | 0.183628E+10 | 0.611267E+09 | 24197.95 | 0.611243E+09 | 0.00 | 0.00 |
April | 0.750948E+09 | 0.938932E+09 | 0.686918E+09 | 8750953.90 | 0.678167E+09 | 0.00 | 0.00 |
May | 0.138086E+10 | 0.494807E+09 | 0.838485E+09 | 61793379.53 | 0.776691E+09 | 0.00 | 0.00 |
June | 0.191715E+10 | 0.220360E+09 | 0.862899E+09 | 0.107526E+09 | 0.755372E+09 | 0.00 | 0.00 |
July | 0.182345E+10 | 0.173956E+09 | 0.823767E+09 | 80802541.81 | 0.742965E+09 | 0.00 | 0.00 |
August | 0.141064E+10 | 0.269457E+09 | 0.696706E+09 | 16575260.69 | 0.680131E+09 | 0.00 | 0.00 |
September | 0.997222E+09 | 0.579672E+09 | 0.586582E+09 | 741339.97 | 0.585841E+09 | 0.00 | 0.00 |
October | 0.486695E+09 | 0.111502E+10 | 0.502433E+09 | 0.00 | 0.502433E+09 | 0.00 | 0.00 |
November | 76964423.64 | 0.205363E+10 | 0.392527E+09 | 0.00 | 0.392527E+09 | 0.00 | 0.00 |
December | 15868861.15 | 0.282780E+10 | 0.379470E+09 | 0.00 | 0.379470E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.931707E+10 | 0.151442E+11 | 0.718528E+10 | 0.276214E+09 | 0.690907E+10 | 0.00 | 0.00 |
Minimum of Months | 15868861.15 | 0.173956E+09 | 0.379470E+09 | 0.00 | 0.379470E+09 | 0.00 | 0.00 |
Maximum of Months | 0.191715E+10 | 0.282780E+10 | 0.862899E+09 | 0.107526E+09 | 0.776691E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.998223E+09 | 0.169168E+10 | 0.973364E+09 | 0.578542E+09 | 0.394822E+09 | 0.00 | 0.00 |
February | 0.122460E+10 | 0.134338E+10 | 0.103844E+10 | 0.601931E+09 | 0.436505E+09 | 0.00 | 0.00 |
March | 0.162411E+10 | 0.125898E+10 | 0.126377E+10 | 0.652149E+09 | 0.611620E+09 | 0.00 | 0.00 |
April | 0.216611E+10 | 0.688434E+09 | 0.133510E+10 | 0.654044E+09 | 0.681055E+09 | 0.00 | 0.00 |
May | 0.260797E+10 | 0.416157E+09 | 0.137582E+10 | 0.637186E+09 | 0.738635E+09 | 0.00 | 0.00 |
June | 0.294505E+10 | 0.206143E+09 | 0.132020E+10 | 0.625352E+09 | 0.694846E+09 | 0.00 | 0.00 |
July | 0.282162E+10 | 0.170672E+09 | 0.124132E+10 | 0.547666E+09 | 0.693659E+09 | 0.00 | 0.00 |
August | 0.263149E+10 | 0.237881E+09 | 0.120652E+10 | 0.530726E+09 | 0.675789E+09 | 0.00 | 0.00 |
September | 0.245159E+10 | 0.426048E+09 | 0.123206E+10 | 0.644030E+09 | 0.588031E+09 | 0.00 | 0.00 |
October | 0.182428E+10 | 0.789203E+09 | 0.112346E+10 | 0.612150E+09 | 0.511313E+09 | 0.00 | 0.00 |
November | 0.128755E+10 | 0.134340E+10 | 0.106411E+10 | 0.655039E+09 | 0.409076E+09 | 0.00 | 0.00 |
December | 0.961246E+09 | 0.180250E+10 | 0.983308E+09 | 0.577324E+09 | 0.405984E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.235438E+11 | 0.103745E+11 | 0.141575E+11 | 0.731614E+10 | 0.684134E+10 | 0.00 | 0.00 |
Minimum of Months | 0.961246E+09 | 0.170672E+09 | 0.973364E+09 | 0.530726E+09 | 0.394822E+09 | 0.00 | 0.00 |
Maximum of Months | 0.294505E+10 | 0.180250E+10 | 0.137582E+10 | 0.655039E+09 | 0.738635E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.181757E+10 | 0.167934E+10 | 0.152718E+10 | 0.105785E+10 | 0.469332E+09 | 0.00 | 0.00 |
February | 0.163786E+10 | 0.134473E+10 | 0.133098E+10 | 0.841376E+09 | 0.489606E+09 | 0.00 | 0.00 |
March | 0.157759E+10 | 0.129583E+10 | 0.123709E+10 | 0.582162E+09 | 0.654925E+09 | 0.00 | 0.00 |
April | 0.140719E+10 | 0.718731E+09 | 0.928373E+09 | 0.263104E+09 | 0.665269E+09 | 0.00 | 0.00 |
May | 0.142782E+10 | 0.400431E+09 | 0.795528E+09 | 95695732.11 | 0.699832E+09 | 0.00 | 0.00 |
June | 0.164128E+10 | 0.177003E+09 | 0.716374E+09 | 63322576.03 | 0.653051E+09 | 0.00 | 0.00 |
July | 0.164575E+10 | 0.136278E+09 | 0.723725E+09 | 66827933.17 | 0.656897E+09 | 0.00 | 0.00 |
August | 0.167165E+10 | 0.215362E+09 | 0.795946E+09 | 0.147226E+09 | 0.648721E+09 | 0.00 | 0.00 |
September | 0.195462E+10 | 0.472048E+09 | 0.105488E+10 | 0.443840E+09 | 0.611036E+09 | 0.00 | 0.00 |
October | 0.210600E+10 | 0.822610E+09 | 0.138326E+10 | 0.822779E+09 | 0.560482E+09 | 0.00 | 0.00 |
November | 0.198024E+10 | 0.136168E+10 | 0.154509E+10 | 0.107890E+10 | 0.466191E+09 | 0.00 | 0.00 |
December | 0.181071E+10 | 0.180502E+10 | 0.156334E+10 | 0.107678E+10 | 0.486559E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.206783E+11 | 0.104291E+11 | 0.136018E+11 | 0.653986E+10 | 0.706190E+10 | 0.00 | 0.00 |
Minimum of Months | 0.140719E+10 | 0.136278E+09 | 0.716374E+09 | 63322576.03 | 0.466191E+09 | 0.00 | 0.00 |
Maximum of Months | 0.210600E+10 | 0.180502E+10 | 0.156334E+10 | 0.107890E+10 | 0.699832E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 8.14 | 3.28 | -3.0 | 3.49 | -5.4 | 41.12 | 223.64 | 0.00 |
February | 10.27 | 3.71 | -4.6 | 3.82 | -5.0 | 51.61 | 245.22 | 0.00 |
March | 12.55 | 4.68 | -5.5 | 4.62 | -3.1 | 72.41 | 273.25 | 0.00 |
April | 19.23 | 8.50 | -2.7 | 4.72 | 3.38 | 79.21 | 314.56 | 0.00 |
May | 23.84 | 12.23 | 2.64 | 5.25 | 8.38 | 86.83 | 326.20 | 0.00 |
June | 27.86 | 15.03 | 5.88 | 4.15 | 14.09 | 80.19 | 344.14 | 0.01 |
July | 27.54 | 18.92 | 14.64 | 3.53 | 17.44 | 86.25 | 283.04 | 0.01 |
August | 26.28 | 17.11 | 12.00 | 3.28 | 15.48 | 80.55 | 269.68 | 0.02 |
September | 23.38 | 15.82 | 11.20 | 2.23 | 11.29 | 66.71 | 294.09 | 0.00 |
October | 18.30 | 12.02 | 7.27 | 3.24 | 6.21 | 54.59 | 257.93 | 0.01 |
November | 11.18 | 5.22 | -1.5 | 3.40 | -3.3 | 40.23 | 258.80 | 0.00 |
December | 6.79 | 1.84 | -4.8 | 2.82 | -8.9 | 42.65 | 217.21 | 0.00 |
Annual Sum or Average | 17.98 | 9.90 | 2.67 | 3.71 | 4.26 | 65.29 | 275.60 | 0.00 |
Minimum of Months | 6.79 | 1.84 | -5.5 | 2.23 | -8.9 | 40.23 | 217.21 | 0.00 |
Maximum of Months | 27.86 | 18.92 | 14.64 | 5.25 | 17.44 | 86.83 | 344.14 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.60 | 03-JAN-14:00 | 8.39 | -5.0 | 9.80 | 2.22 | 118.50 | 530.50 |
February | 23.30 | 20-FEB-14:00 | 8.88 | -7.8 | 4.10 | 4.10 | 55.00 | 955.00 |
March | 25.00 | 21-MAR-15:00 | 9.53 | -8.3 | 6.20 | 5.54 | 50.00 | 873.00 |
April | 32.20 | 21-APR-13:00 | 15.21 | 2.80 | 13.90 | 18.28 | 265.50 | 638.50 |
May | 35.00 | 19-MAY-13:00 | 17.23 | 6.10 | 10.30 | 21.78 | 145.00 | 874.50 |
June | 38.90 | 02-JUN-15:00 | 16.22 | -1.1 | 4.60 | 20.40 | 234.50 | 284.00 |
July | 38.30 | 01-JUL-16:00 | 19.19 | 8.90 | 3.60 | 26.81 | 165.50 | 256.50 |
August | 37.20 | 07-AUG-15:00 | 17.89 | 6.70 | 5.70 | 24.66 | 143.50 | 615.00 |
September | 33.90 | 19-SEP-13:00 | 16.85 | 6.70 | 3.10 | 17.75 | 113.00 | 912.00 |
October | 32.80 | 01-OCT-14:00 | 15.90 | 4.40 | 5.70 | 16.12 | 127.50 | 736.50 |
November | 23.90 | 03-NOV-15:00 | 13.45 | 6.10 | 5.70 | 12.22 | 48.50 | 648.50 |
December | 18.30 | 10-DEC-14:00 | 7.97 | -2.8 | 7.20 | 4.10 | 123.00 | 52.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 18.30 | 7.97 | -8.3 | 3.10 | 2.22 | 48.50 | 52.50 | |
Maximum of Months | 38.90 | 19.19 | 8.90 | 13.90 | 26.81 | 265.50 | 955.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -4.4 | 27-JAN-06:00 | -7.5 | -15.0 | 3.60 | -23.6 | 0.00 | 0.00 |
February | -5.6 | 03-FEB-06:00 | -7.5 | -11.7 | 1.50 | -23.9 | 0.00 | 0.00 |
March | -3.9 | 02-MAR-04:00 | -6.5 | -12.8 | 1.50 | -21.3 | 0.00 | 0.00 |
April | 3.30 | 12-APR-05:00 | -1.8 | -9.4 | 2.10 | -14.9 | 37.00 | 217.50 |
May | 9.40 | 02-MAY-05:00 | 3.98 | -2.2 | 3.60 | -7.6 | 51.00 | 277.50 |
June | 15.00 | 13-JUN-04:00 | 4.43 | -10.6 | 2.10 | -4.3 | 0.00 | 0.00 |
July | 17.80 | 05-JUL-05:00 | 15.98 | 15.00 | 4.10 | 4.31 | 39.00 | 249.00 |
August | 16.70 | 31-AUG-05:00 | 13.89 | 12.20 | 4.10 | 2.64 | 36.00 | 126.50 |
September | 8.30 | 30-SEP-05:00 | 5.77 | 3.30 | 1.50 | -7.3 | 0.00 | 0.00 |
October | 6.70 | 11-OCT-05:00 | 5.82 | 5.00 | 1.50 | -5.5 | 0.00 | 0.00 |
November | -0.6 | 17-NOV-03:00 | -3.1 | -6.7 | 1.50 | -18.1 | 0.00 | 0.00 |
December | -4.4 | 27-DEC-06:00 | -5.1 | -6.1 | 2.10 | -18.6 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -7.5 | -15.0 | 1.50 | -23.9 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 15.98 | 15.00 | 4.10 | 4.31 | 51.00 | 277.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.18 | 12-JAN-15:00 | 18.90 | 2.80 | 3.60 | 6.15 | 70.50 | 491.50 |
February | 11.42 | 13-FEB-16:00 | 12.80 | 10.60 | 4.10 | 6.55 | 34.00 | 18.50 |
March | 10.75 | 10-MAR-18:00 | 13.30 | 8.90 | 1.50 | 8.54 | 0.00 | 0.00 |
April | 15.74 | 29-APR-13:00 | 30.00 | 6.70 | 4.10 | 18.28 | 336.50 | 432.50 |
May | 19.12 | 24-MAY-12:00 | 27.80 | 15.00 | 5.20 | 17.57 | 188.50 | 862.00 |
June | 20.21 | 03-JUN-14:00 | 33.90 | 13.90 | 8.80 | 23.66 | 264.50 | 316.00 |
July | 22.88 | 20-JUL-15:39 | 25.53 | 21.87 | 2.93 | 18.99 | 184.00 | 15.83 |
August | 21.18 | 02-AUG-11:00 | 30.60 | 17.20 | 3.60 | 20.75 | 154.50 | 850.00 |
September | 20.65 | 14-SEP-09:00 | 25.00 | 18.90 | 2.10 | 14.47 | 126.50 | 835.50 |
October | 19.64 | 03-OCT-13:00 | 32.80 | 13.30 | 2.60 | 21.44 | 224.50 | 577.50 |
November | 13.57 | 03-NOV-14:00 | 23.30 | 7.20 | 0.00 | 10.88 | 72.50 | 802.00 |
December | 8.30 | 10-DEC-12:00 | 17.20 | -0.6 | 5.70 | 1.58 | 198.50 | 507.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 8.30 | 12.80 | -0.6 | 0.00 | 1.58 | 0.00 | 0.00 | |
Maximum of Months | 22.88 | 33.90 | 21.87 | 8.80 | 23.66 | 336.50 | 862.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.00 | 16-JAN-01:00 | 9.00 | 9.00 | 2.10 | 4.51 | 0.00 | 0.00 |
February | 10.60 | 13-FEB-13:09 | 12.20 | 11.24 | 5.53 | 5.71 | 147.33 | 0.00 |
March | 10.00 | 11-MAR-00:00 | 10.60 | 10.24 | 2.10 | 6.15 | 0.00 | 0.00 |
April | 10.60 | 17-APR-01:00 | 17.80 | 13.38 | 7.20 | 3.48 | 0.00 | 0.00 |
May | 15.00 | 24-MAY-10:00 | 25.60 | 18.41 | 7.20 | 15.39 | 171.00 | 872.50 |
June | 17.20 | 19-JUN-17:00 | 23.90 | 19.20 | 3.60 | 15.39 | 86.00 | 324.00 |
July | 22.20 | 20-JUL-14:00 | 24.40 | 22.82 | 4.60 | 17.93 | 283.00 | 59.50 |
August | 18.90 | 01-AUG-20:00 | 22.20 | 19.91 | 4.60 | 17.75 | 0.00 | 0.00 |
September | 19.40 | 22-SEP-01:00 | 20.60 | 19.76 | 1.50 | 16.30 | 0.00 | 0.00 |
October | 17.20 | 03-OCT-19:00 | 23.30 | 19.11 | 4.60 | 18.46 | 0.00 | 0.00 |
November | 10.00 | 01-NOV-09:00 | 13.30 | 11.28 | 3.10 | 8.94 | 123.50 | 0.00 |
December | 6.10 | 13-DEC-00:00 | 8.30 | 7.10 | 7.70 | 3.06 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 8.30 | 7.10 | 1.50 | 3.06 | 0.00 | 0.00 | |
Maximum of Months | 22.20 | 25.60 | 22.82 | 7.70 | 18.46 | 283.00 | 872.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 15.16 | 28.38 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 15.21 | 35.58 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 16.80 | 47.71 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 19.62 | 58.45 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 22.88 | 63.58 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 25.71 | 66.73 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 27.35 | 58.19 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 27.33 | 54.44 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 25.68 | 50.89 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 22.83 | 39.37 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 19.57 | 32.11 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 16.77 | 26.90 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 21.28 | 46.90 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 15.16 | 26.90 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 27.35 | 66.73 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH LAUNDRY G WATER HEATER
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.115228E+12 | -0.113468E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.176075E+10 | 82.17 | 0.00 | 0.00 |
February | 0.104032E+12 | -0.102420E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.161194E+10 | 82.17 | 0.00 | 0.00 |
March | 0.112496E+12 | -0.110689E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.180703E+10 | 82.17 | 0.00 | 0.00 |
April | 0.104252E+12 | -0.102506E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.174584E+10 | 82.17 | 0.00 | 0.00 |
May | 0.102192E+12 | -0.100397E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.179497E+10 | 82.17 | 0.00 | 0.00 |
June | 0.942452E+11 | -0.925171E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.172809E+10 | 82.17 | 0.00 | 0.00 |
July | 0.946002E+11 | -0.928381E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.176211E+10 | 82.17 | 0.00 | 0.00 |
August | 0.946171E+11 | -0.928612E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175586E+10 | 82.17 | 0.00 | 0.00 |
September | 0.942747E+11 | -0.925775E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.169720E+10 | 82.17 | 0.00 | 0.00 |
October | 0.102236E+12 | -0.100482E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175365E+10 | 82.17 | 0.00 | 0.00 |
November | 0.104285E+12 | -0.102588E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.169711E+10 | 82.17 | 0.00 | 0.00 |
December | 0.112505E+12 | -0.110750E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175489E+10 | 82.17 | 0.00 | 0.00 |
Annual Sum or Average | 0.123496E+13 | -0.121409E+13 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.208694E+11 | 82.17 | 0.00 | 0.00 |
Minimum of Months | 0.942452E+11 | -0.113468E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.180703E+10 | 82.17 | 0.00 | 0.00 |
Maximum of Months | 0.115228E+12 | -0.925171E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.161194E+10 | 82.17 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.804736E+10 | -0.788296E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164404602.3 | 82.17 | 0.00 | 0.00 |
February | 0.727181E+10 | -0.712336E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -148445919.6 | 82.17 | 0.00 | 0.00 |
March | 0.804584E+10 | -0.788155E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164281959.6 | 82.17 | 0.00 | 0.00 |
April | 0.779706E+10 | -0.763820E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -158862342.2 | 82.17 | 0.00 | 0.00 |
May | 0.804708E+10 | -0.788296E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164115289.2 | 82.17 | 0.00 | 0.00 |
June | 0.778857E+10 | -0.762976E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -158812236.9 | 82.17 | 0.00 | 0.00 |
July | 0.805551E+10 | -0.789140E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164104042.0 | 82.17 | 0.00 | 0.00 |
August | 0.804707E+10 | -0.788296E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164104678.9 | 82.17 | 0.00 | 0.00 |
September | 0.779842E+10 | -0.763961E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -158815967.4 | 82.17 | 0.00 | 0.00 |
October | 0.804571E+10 | -0.788155E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164155219.5 | 82.17 | 0.00 | 0.00 |
November | 0.778034E+10 | -0.762132E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -159021280.3 | 82.17 | 0.00 | 0.00 |
December | 0.805586E+10 | -0.789140E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164461320.4 | 82.17 | 0.00 | 0.00 |
Annual Sum or Average | 0.947806E+11 | -0.928471E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.193358E+10 | 82.17 | 0.00 | 0.00 |
Minimum of Months | 0.727181E+10 | -0.789140E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -164461320.4 | 82.17 | 0.00 | 0.00 |
Maximum of Months | 0.805586E+10 | -0.712336E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -148445919.6 | 82.17 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.670319E+11 | -0.655153E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.151652E+10 | 60.05 | 0.00 | 0.00 |
February | 0.605294E+11 | -0.591297E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.139970E+10 | 60.05 | 0.00 | 0.00 |
March | 0.647535E+11 | -0.631728E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.158068E+10 | 60.05 | 0.00 | 0.00 |
April | 0.586431E+11 | -0.571174E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.152567E+10 | 60.05 | 0.00 | 0.00 |
May | 0.558222E+11 | -0.542582E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.156397E+10 | 60.05 | 0.00 | 0.00 |
June | 0.500179E+11 | -0.485168E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.150108E+10 | 60.05 | 0.00 | 0.00 |
July | 0.492193E+11 | -0.477009E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.151841E+10 | 60.05 | 0.00 | 0.00 |
August | 0.492797E+11 | -0.477700E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.150975E+10 | 60.05 | 0.00 | 0.00 |
September | 0.500051E+11 | -0.485468E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.145825E+10 | 60.05 | 0.00 | 0.00 |
October | 0.558073E+11 | -0.543006E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.150668E+10 | 60.05 | 0.00 | 0.00 |
November | 0.586229E+11 | -0.571648E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.145812E+10 | 60.05 | 0.00 | 0.00 |
December | 0.646732E+11 | -0.631648E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.150840E+10 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.684405E+12 | -0.666358E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.180472E+11 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.492193E+11 | -0.655153E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.158068E+10 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.670319E+11 | -0.477009E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.139970E+10 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: LOBBY_FLR_1_DAYLCTRL
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.87 | 0.86 | 01-JAN-08:20 | 7927.13 | 38.53 | 274.50 | 280.33 | 1044.76 | 27.15 | 179.17 | 259.00 |
February | 268.33 | 0.87 | 0.86 | 01-FEB-07:49 | 6427.24 | 33.89 | 210.83 | 272.17 | 656.61 | 24.04 | 167.33 | 241.17 |
March | 351.83 | 0.88 | 0.86 | 01-MAR-07:10 | 1135.36 | 19.90 | 12.33 | 323.17 | 437.93 | 21.23 | 148.67 | 256.17 |
April | 373.83 | 0.88 | 0.86 | 01-APR-07:19 | 820.80 | 19.43 | 0.33 | 339.67 | 348.43 | 21.18 | 161.00 | 260.67 |
May | 408.83 | 0.88 | 0.86 | 01-MAY-07:19 | 686.59 | 19.07 | 0.00 | 364.17 | 296.17 | 20.82 | 134.83 | 266.50 |
June | 398.00 | 0.88 | 0.86 | 01-JUN-08:09 | 602.04 | 19.00 | 0.00 | 356.50 | 266.86 | 20.80 | 76.00 | 223.50 |
July | 400.17 | 0.88 | 0.86 | 01-JUL-08:09 | 659.82 | 18.87 | 0.00 | 362.50 | 282.78 | 20.64 | 116.83 | 217.67 |
August | 377.83 | 0.88 | 0.86 | 01-AUG-07:00 | 772.66 | 19.19 | 0.00 | 351.00 | 326.71 | 20.93 | 162.83 | 259.00 |
September | 365.83 | 0.88 | 0.86 | 01-SEP-09:39 | 887.54 | 19.30 | 0.33 | 321.17 | 375.39 | 21.09 | 153.33 | 240.67 |
October | 318.83 | 0.87 | 0.86 | 01-OCT-07:19 | 3201.31 | 26.33 | 125.67 | 314.33 | 513.35 | 22.14 | 150.50 | 279.33 |
November | 295.83 | 0.87 | 0.86 | 01-NOV-12:39 | 8202.96 | 37.69 | 288.50 | 289.67 | 800.11 | 26.02 | 160.17 | 270.67 |
December | 289.50 | 0.87 | 0.86 | 01-DEC-07:19 | 7147.65 | 38.04 | 284.67 | 278.33 | 1166.43 | 27.77 | 199.50 | 268.83 |
Annual Sum or Average | 4125.67 | 0.87 | 2797.86 | 24.68 | 1197.17 | 3853.00 | 506.35 | 22.50 | 1810.17 | 3043.17 | ||
Minimum of Months | 268.33 | 0.87 | 0.86 | 602.04 | 18.87 | 0.00 | 272.17 | 266.86 | 20.64 | 76.00 | 217.67 | |
Maximum of Months | 408.83 | 0.88 | 0.86 | 8202.96 | 38.53 | 288.50 | 364.17 | 1166.43 | 27.77 | 199.50 | 279.33 |
Report: DaylightingReportMonthly
For: CAFE_FLR_1_DAYLCTRL
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.24 | 0.22 | 01-JAN-08:09 | 8370.79 | 38.58 | 274.50 | 287.17 | 1487.42 | 26.73 | 164.67 | 273.33 |
February | 268.33 | 0.25 | 0.22 | 01-FEB-07:49 | 6825.17 | 33.88 | 211.17 | 281.67 | 1054.06 | 23.76 | 150.17 | 260.50 |
March | 351.83 | 0.27 | 0.22 | 01-MAR-06:00 | 1414.38 | 20.17 | 32.83 | 337.50 | 716.34 | 21.36 | 163.67 | 308.33 |
April | 373.83 | 0.27 | 0.22 | 01-APR-06:49 | 1012.58 | 20.00 | 33.00 | 355.00 | 539.73 | 21.54 | 213.00 | 320.83 |
May | 408.83 | 0.28 | 0.22 | 01-MAY-06:19 | 827.26 | 19.84 | 2.33 | 377.50 | 436.44 | 21.37 | 287.00 | 348.67 |
June | 398.00 | 0.27 | 0.22 | 01-JUN-06:19 | 727.88 | 19.85 | 0.17 | 372.67 | 392.34 | 21.42 | 245.83 | 340.00 |
July | 400.17 | 0.28 | 0.22 | 01-JUL-06:30 | 787.61 | 19.70 | 1.00 | 381.50 | 410.18 | 21.24 | 228.00 | 337.17 |
August | 377.83 | 0.28 | 0.22 | 01-AUG-06:30 | 932.54 | 19.90 | 18.83 | 365.17 | 486.15 | 21.42 | 236.50 | 328.50 |
September | 365.83 | 0.28 | 0.22 | 01-SEP-07:19 | 1119.40 | 19.73 | 19.50 | 337.33 | 606.74 | 21.33 | 166.50 | 303.50 |
October | 318.83 | 0.26 | 0.22 | 01-OCT-06:00 | 3552.33 | 26.35 | 131.33 | 318.00 | 863.29 | 22.04 | 151.17 | 302.67 |
November | 295.83 | 0.25 | 0.22 | 01-NOV-12:39 | 8617.22 | 37.76 | 288.67 | 295.33 | 1214.76 | 25.60 | 138.67 | 283.00 |
December | 289.50 | 0.24 | 0.22 | 01-DEC-07:10 | 7575.86 | 38.11 | 284.67 | 283.83 | 1596.63 | 27.43 | 181.33 | 276.67 |
Annual Sum or Average | 4125.67 | 0.27 | 3055.24 | 25.11 | 1298.00 | 3992.67 | 763.42 | 22.67 | 2326.50 | 3683.17 | ||
Minimum of Months | 268.33 | 0.24 | 0.22 | 727.88 | 19.70 | 0.17 | 281.67 | 392.34 | 21.24 | 138.67 | 260.50 | |
Maximum of Months | 408.83 | 0.28 | 0.22 | 8617.22 | 38.58 | 288.67 | 381.50 | 1596.63 | 27.43 | 287.00 | 348.67 |
Report: DaylightingReportMonthly
For: DINING_FLR_6_DAYLCTRL
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.70 | 0.60 | 01-JAN-09:20 | 310.75 | 14.42 | 0.00 | 237.00 | 163.68 | 18.04 | 0.00 | 60.83 |
February | 268.33 | 0.68 | 0.60 | 02-FEB-09:20 | 351.77 | 15.09 | 0.00 | 244.33 | 183.37 | 18.60 | 0.00 | 96.83 |
March | 351.83 | 0.67 | 0.60 | 01-MAR-08:30 | 421.96 | 15.88 | 0.00 | 311.33 | 206.93 | 19.20 | 0.00 | 155.00 |
April | 373.83 | 0.64 | 0.60 | 01-APR-07:30 | 508.76 | 17.00 | 0.00 | 357.50 | 243.39 | 20.25 | 25.50 | 259.33 |
May | 408.83 | 0.62 | 0.60 | 01-MAY-06:10 | 661.14 | 17.72 | 5.33 | 389.67 | 282.83 | 20.82 | 104.50 | 360.33 |
June | 398.00 | 0.61 | 0.60 | 01-JUN-06:10 | 714.89 | 20.75 | 83.67 | 386.00 | 301.97 | 21.26 | 104.83 | 361.67 |
July | 400.17 | 0.62 | 0.60 | 01-JUL-05:49 | 682.57 | 18.95 | 39.33 | 398.17 | 321.64 | 21.78 | 106.83 | 346.67 |
August | 377.83 | 0.63 | 0.60 | 01-AUG-05:00 | 562.34 | 17.19 | 0.00 | 371.17 | 267.11 | 20.44 | 53.67 | 307.33 |
September | 365.83 | 0.67 | 0.60 | 01-SEP-14:30 | 415.37 | 16.19 | 0.00 | 325.00 | 209.62 | 19.49 | 1.50 | 157.00 |
October | 318.83 | 0.68 | 0.60 | 01-OCT-14:00 | 371.36 | 15.43 | 0.00 | 290.33 | 190.53 | 18.85 | 0.00 | 108.67 |
November | 295.83 | 0.71 | 0.60 | 01-NOV-13:20 | 296.96 | 14.45 | 0.00 | 250.17 | 157.66 | 18.04 | 0.00 | 47.33 |
December | 289.50 | 0.70 | 0.60 | 01-DEC-10:39 | 318.84 | 14.44 | 0.00 | 240.33 | 165.80 | 18.03 | 0.00 | 61.00 |
Annual Sum or Average | 4125.67 | 0.66 | 487.20 | 16.69 | 128.33 | 3801.00 | 231.68 | 19.73 | 396.83 | 2322.00 | ||
Minimum of Months | 268.33 | 0.61 | 0.60 | 296.96 | 14.42 | 0.00 | 237.00 | 157.66 | 18.03 | 0.00 | 47.33 | |
Maximum of Months | 408.83 | 0.71 | 0.60 | 714.89 | 20.75 | 83.67 | 398.17 | 321.64 | 21.78 | 106.83 | 361.67 |
Report: DaylightingReportMonthly
For: BANQUET_FLR_6_DAYLCTRL
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.70 | 0.60 | 01-JAN-09:20 | 310.75 | 14.42 | 0.00 | 237.00 | 163.68 | 18.04 | 0.00 | 60.83 |
February | 268.33 | 0.68 | 0.60 | 02-FEB-09:20 | 351.77 | 15.09 | 0.00 | 244.33 | 183.37 | 18.60 | 0.00 | 96.83 |
March | 351.83 | 0.67 | 0.60 | 01-MAR-08:30 | 421.96 | 15.88 | 0.00 | 311.33 | 206.93 | 19.20 | 0.00 | 155.00 |
April | 373.83 | 0.64 | 0.60 | 01-APR-07:30 | 508.76 | 17.00 | 0.00 | 357.50 | 243.39 | 20.25 | 25.50 | 259.33 |
May | 408.83 | 0.62 | 0.60 | 01-MAY-06:10 | 661.14 | 17.72 | 5.33 | 389.67 | 282.83 | 20.82 | 104.50 | 360.33 |
June | 398.00 | 0.61 | 0.60 | 01-JUN-06:10 | 714.89 | 20.75 | 83.67 | 386.00 | 301.97 | 21.26 | 104.83 | 361.67 |
July | 400.17 | 0.62 | 0.60 | 01-JUL-05:49 | 682.57 | 18.95 | 39.33 | 398.17 | 321.64 | 21.78 | 106.83 | 346.67 |
August | 377.83 | 0.63 | 0.60 | 01-AUG-05:00 | 562.34 | 17.19 | 0.00 | 371.17 | 267.11 | 20.44 | 53.67 | 307.33 |
September | 365.83 | 0.67 | 0.60 | 01-SEP-14:30 | 415.37 | 16.19 | 0.00 | 325.00 | 209.62 | 19.49 | 1.50 | 157.00 |
October | 318.83 | 0.68 | 0.60 | 01-OCT-14:00 | 371.36 | 15.43 | 0.00 | 290.33 | 190.53 | 18.85 | 0.00 | 108.67 |
November | 295.83 | 0.71 | 0.60 | 01-NOV-13:20 | 296.96 | 14.45 | 0.00 | 250.17 | 157.66 | 18.04 | 0.00 | 47.33 |
December | 289.50 | 0.70 | 0.60 | 01-DEC-10:39 | 318.84 | 14.44 | 0.00 | 240.33 | 165.80 | 18.03 | 0.00 | 61.00 |
Annual Sum or Average | 4125.67 | 0.66 | 487.20 | 16.69 | 128.33 | 3801.00 | 231.68 | 19.73 | 396.83 | 2322.00 | ||
Minimum of Months | 268.33 | 0.61 | 0.60 | 296.96 | 14.42 | 0.00 | 237.00 | 157.66 | 18.03 | 0.00 | 47.33 | |
Maximum of Months | 408.83 | 0.71 | 0.60 | 714.89 | 20.75 | 83.67 | 398.17 | 321.64 | 21.78 | 106.83 | 361.67 |
Report: CoilReportMonthly
For: FLR_3_DOAS HEATING COIL
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 28411761.06 | 1322.22 | 27-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 49814462.23 | 1785.09 | 03-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 15218592.06 | 1130.78 | 02-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 24133.11 | 0.37 | 06-APR-03:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 30554.25 | 0.37 | 26-MAY-23:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 21128.86 | 0.38 | 23-JUN-01:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 21755.18 | 0.38 | 13-JUL-24:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 19998.12 | 0.38 | 25-AUG-22:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 23349.97 | 0.38 | 21-SEP-01:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 19032.16 | 0.37 | 04-OCT-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6725.13 | 0.36 | 08-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 91444079.72 | 1328.41 | 27-DEC-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.185056E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 6725.13 | 0.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 91444079.72 | 1785.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.108575E+12 | 135561.20 | 26-JAN-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.694059E+11 | 132126.11 | 01-FEB-19:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.617196E+11 | 125975.52 | 25-MAR-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.196843E+11 | 118256.14 | 07-APR-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.874521E+09 | 53530.87 | 02-MAY-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.129368E+10 | 68170.13 | 30-SEP-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.121077E+11 | 113164.26 | 25-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.689018E+11 | 138588.19 | 27-NOV-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.846997E+11 | 133112.56 | 28-DEC-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.427262E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.108575E+12 | 138588.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.337921E+09 | 1078.55 | 27-JAN-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.191471E+09 | 1028.61 | 03-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.136511E+09 | 981.76 | 02-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 9864479.48 | 402.73 | 12-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 98515.57 | 165.31 | 14-OCT-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.160921E+09 | 1044.09 | 28-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.471022E+09 | 1520.42 | 27-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.130781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.471022E+09 | 1520.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 1523004.17 | 210.33 | 28-JAN-11:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 374994.51 | 180.75 | 03-FEB-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 150493.61 | 164.41 | 02-MAR-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 423745.89 | 154.03 | 28-NOV-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 28021934.73 | 369.71 | 28-DEC-11:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 30494172.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28021934.73 | 369.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 16291809.22 | 242.18 | 28-JAN-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 9386685.16 | 182.65 | 03-FEB-08:18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 4736785.46 | 192.13 | 02-MAR-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 7201817.55 | 173.98 | 28-NOV-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 76959555.18 | 306.35 | 27-DEC-11:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.114577E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 76959555.18 | 306.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 23645991.62 | 1372.91 | 15-JAN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1873544.52 | 506.02 | 13-FEB-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 80543.84 | 134.24 | 24-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16274175.22 | 1590.35 | 27-NOV-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 22108945.29 | 1710.48 | 26-DEC-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 63983200.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23645991.62 | 1710.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.248413E+09 | 3091.01 | 17-JAN-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16159902.49 | 1978.26 | 03-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 9135190.59 | 1375.97 | 02-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 84802016.50 | 2032.71 | 28-NOV-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.581835E+09 | 4285.62 | 27-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.940345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.581835E+09 | 4285.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.719020E+09 | 2643.17 | 27-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.319565E+09 | 2764.57 | 03-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.136615E+09 | 2372.78 | 02-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.266635E+09 | 2063.24 | 28-NOV-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.125945E+10 | 3144.30 | 27-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.270128E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.125945E+10 | 3144.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.120917E+10 | 5394.80 | 15-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.729353E+09 | 5343.30 | 02-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.377337E+09 | 5378.43 | 02-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 30428378.44 | 2576.09 | 13-APR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1564670.79 | 2468.34 | 08-MAY-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 114336.16 | 1143.36 | 29-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 38904.49 | 389.04 | 19-JUL-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 748122.99 | 1464.39 | 14-AUG-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 710212.90 | 2057.64 | 28-SEP-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4464583.54 | 2668.56 | 14-OCT-18:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.549698E+09 | 5397.36 | 28-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.163709E+10 | 5509.16 | 26-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.454072E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 38904.49 | 389.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.163709E+10 | 5509.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.207854E+10 | 5497.17 | 27-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.123496E+10 | 5480.71 | 02-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.546921E+09 | 5427.63 | 02-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 32231566.23 | 2780.11 | 13-APR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1574912.97 | 2245.11 | 04-MAY-06:44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 84049.65 | 519.74 | 13-JUN-08:36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 100351.69 | 627.73 | 08-AUG-06:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 881527.85 | 1698.54 | 29-SEP-06:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6849374.05 | 2712.37 | 11-OCT-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.909844E+09 | 5436.89 | 28-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.273023E+10 | 5497.95 | 27-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.754222E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.273023E+10 | 5497.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.458756E+10 | 31318.53 | 27-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.258566E+10 | 31217.92 | 02-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.738949E+09 | 30519.47 | 29-MAR-15:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 32131323.94 | 30681.37 | 11-APR-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5052134.02 | 21478.41 | 01-MAY-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 104042.00 | 915.44 | 01-JUN-08:38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 619232.29 | 3223.34 | 24-AUG-08:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5007093.34 | 11018.07 | 20-SEP-08:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16107546.88 | 18096.66 | 25-OCT-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.166209E+10 | 31030.31 | 27-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.715217E+10 | 31461.34 | 27-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.167854E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.715217E+10 | 31461.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.128710E+10 | 5277.98 | 15-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.698367E+09 | 4377.51 | 13-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.393794E+09 | 5168.24 | 02-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 28938247.97 | 1377.19 | 22-APR-18:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 81741.62 | 681.18 | 03-MAY-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 82054.97 | 820.55 | 19-JUL-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 287041.90 | 1289.69 | 17-AUG-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 9610842.50 | 2229.11 | 15-OCT-18:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.608246E+09 | 5257.80 | 28-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.167309E+10 | 5372.92 | 26-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.469959E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.167309E+10 | 5372.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.213107E+10 | 5287.33 | 15-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.111491E+10 | 5228.21 | 02-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.568549E+09 | 5215.38 | 02-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 34180637.83 | 3980.17 | 11-APR-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 242394.12 | 785.36 | 04-MAY-21:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 24573.91 | 163.83 | 17-AUG-08:58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 611.13 | 8.15 | 08-SEP-21:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 20738753.85 | 2592.61 | 07-OCT-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.963092E+09 | 5305.79 | 27-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.269918E+10 | 5360.35 | 26-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.753199E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.269918E+10 | 5360.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.569494E+09 | 1661.56 | 15-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.375347E+09 | 1650.23 | 02-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.235029E+09 | 1655.94 | 02-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 34259932.76 | 1604.81 | 11-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1370475.22 | 624.84 | 26-MAY-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 135093.63 | 513.84 | 29-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 389895.10 | 551.35 | 16-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 559262.34 | 565.70 | 26-SEP-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16382491.36 | 595.38 | 06-OCT-18:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.307022E+09 | 1660.77 | 28-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.722370E+09 | 1664.56 | 26-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.226236E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.722370E+09 | 1664.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.876696E+09 | 1661.94 | 15-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.559225E+09 | 1661.11 | 01-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.300129E+09 | 1660.95 | 02-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 33977105.40 | 1604.31 | 11-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 490412.07 | 746.72 | 01-MAY-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 55689.24 | 249.94 | 11-JUN-08:36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 42326.71 | 153.21 | 29-JUL-06:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 61870.24 | 284.97 | 30-AUG-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 429058.36 | 501.41 | 25-SEP-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 20840971.34 | 807.01 | 25-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.470928E+09 | 1661.34 | 28-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.108672E+10 | 1661.47 | 04-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.334960E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 42326.71 | 153.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.108672E+10 | 1661.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.907935E+09 | 7717.50 | 15-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.592584E+09 | 2829.95 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.436188E+09 | 7607.07 | 02-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 74736529.01 | 3091.50 | 13-APR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 4700241.42 | 2767.43 | 10-MAY-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 391674.94 | 2882.86 | 29-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 461632.69 | 739.29 | 17-JUL-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 477453.10 | 1588.64 | 14-AUG-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 646375.16 | 1247.88 | 24-SEP-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5378971.65 | 3211.87 | 07-OCT-18:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.508364E+09 | 7650.31 | 27-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.127437E+10 | 7759.61 | 26-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.380624E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 391674.94 | 739.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.127437E+10 | 7759.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.424271E+09 | 0.424271E+09 | 11015.35 | 03-JAN-17:00 | 11015.35 | 0.00 |
February | 0.00 | 0.00 | 0.213369E+10 | 0.213369E+10 | 14201.75 | 20-FEB-16:02 | 14201.75 | 0.00 |
March | 0.00 | 0.00 | 0.440496E+10 | 0.440496E+10 | 14771.59 | 22-MAR-15:02 | 14771.59 | 0.00 |
April | 0.00 | 0.00 | 0.144455E+11 | 0.144455E+11 | 17662.05 | 21-APR-15:02 | 17662.05 | 0.09 |
May | 0.00 | 0.00 | 0.238762E+11 | 0.233289E+11 | 21571.96 | 24-MAY-13:00 | 16231.94 | 0.31 |
June | 0.00 | 0.00 | 0.298114E+11 | 0.285666E+11 | 24534.76 | 27-JUN-24:00 | 12151.89 | 0.58 |
July | 0.00 | 0.00 | 0.419047E+11 | 0.300733E+11 | 39037.79 | 21-JUL-08:03 | 13821.47 | 0.79 |
August | 0.00 | 0.00 | 0.343740E+11 | 0.282785E+11 | 33560.00 | 01-AUG-21:51 | 14428.59 | 0.79 |
September | 0.00 | 0.00 | 0.288701E+11 | 0.220914E+11 | 31964.14 | 22-SEP-08:03 | 14826.78 | 0.68 |
October | 0.00 | 0.00 | 0.136959E+11 | 0.123355E+11 | 27787.53 | 03-OCT-20:20 | 14079.21 | 0.35 |
November | 0.00 | 0.00 | 0.268590E+10 | 0.268590E+10 | 14433.34 | 09-NOV-16:02 | 14433.34 | 0.02 |
December | 0.00 | 0.00 | 0.217497E+09 | 0.217497E+09 | 5697.71 | 10-DEC-14:00 | 5697.71 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.196844E+12 | 0.168986E+12 | 0.30 | |||
Minimum of Months | 0.00 | 0.00 | 0.217497E+09 | 0.217497E+09 | 5697.71 | 5697.71 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.419047E+11 | 0.300733E+11 | 39037.79 | 17662.05 | 0.79 |
Report: CoilReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.651804E+10 | 0.651804E+10 | 90506.65 | 03-JAN-17:00 | 90506.65 | 0.00 |
February | 0.00 | 0.00 | 0.332095E+11 | 0.332095E+11 | 125144.89 | 21-FEB-16:13 | 125144.89 | 0.00 |
March | 0.00 | 0.00 | 0.676421E+11 | 0.676421E+11 | 162479.49 | 14-MAR-18:10 | 162479.49 | 0.00 |
April | 0.00 | 0.00 | 0.211171E+12 | 0.211171E+12 | 232019.11 | 19-APR-21:00 | 232019.11 | 0.10 |
May | 0.00 | 0.00 | 0.349935E+12 | 0.348328E+12 | 255163.14 | 19-MAY-19:10 | 255163.14 | 0.36 |
June | 0.00 | 0.00 | 0.451818E+12 | 0.446731E+12 | 302704.71 | 19-JUN-18:02 | 203429.95 | 0.69 |
July | 0.00 | 0.00 | 0.605002E+12 | 0.468100E+12 | 477291.69 | 21-JUL-21:00 | 220594.90 | 1.00 |
August | 0.00 | 0.00 | 0.491342E+12 | 0.438578E+12 | 454220.22 | 01-AUG-20:50 | 212333.67 | 0.98 |
September | 0.00 | 0.00 | 0.401659E+12 | 0.345336E+12 | 338086.83 | 09-SEP-20:00 | 186057.70 | 0.85 |
October | 0.00 | 0.00 | 0.198949E+12 | 0.190319E+12 | 384591.27 | 03-OCT-19:55 | 210205.48 | 0.44 |
November | 0.00 | 0.00 | 0.412903E+11 | 0.412903E+11 | 149267.48 | 03-NOV-15:55 | 149267.48 | 0.03 |
December | 0.00 | 0.00 | 0.381061E+10 | 0.381061E+10 | 49687.19 | 09-DEC-13:00 | 49687.19 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.286235E+13 | 0.260103E+13 | 0.37 | |||
Minimum of Months | 0.00 | 0.00 | 0.381061E+10 | 0.381061E+10 | 49687.19 | 49687.19 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.605002E+12 | 0.468100E+12 | 477291.69 | 255163.14 | 1.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.944498E+09 | 0.803344E+09 | 9586.12 | 07-JAN-16:02 | 9586.12 | 0.11 |
February | 0.00 | 0.00 | 0.140738E+10 | 0.138008E+10 | 9586.45 | 05-FEB-16:02 | 9586.45 | 0.03 |
March | 0.00 | 0.00 | 0.258513E+10 | 0.253391E+10 | 9586.65 | 05-MAR-16:02 | 9586.65 | 0.05 |
April | 0.00 | 0.00 | 0.568009E+10 | 0.526334E+10 | 9586.82 | 07-APR-15:02 | 9586.82 | 0.27 |
May | 0.00 | 0.00 | 0.860860E+10 | 0.744741E+10 | 10658.14 | 28-MAY-08:62 | 8887.56 | 0.64 |
June | 0.00 | 0.00 | 0.108046E+11 | 0.905665E+10 | 10566.15 | 28-JUN-08:62 | 8947.21 | 0.86 |
July | 0.00 | 0.00 | 0.113373E+11 | 0.856527E+10 | 12004.69 | 19-JUL-08:62 | 7996.21 | 0.96 |
August | 0.00 | 0.00 | 0.105008E+11 | 0.794192E+10 | 10995.51 | 14-AUG-08:62 | 8440.88 | 0.95 |
September | 0.00 | 0.00 | 0.964657E+10 | 0.724821E+10 | 11364.05 | 04-SEP-08:62 | 8424.68 | 0.95 |
October | 0.00 | 0.00 | 0.646007E+10 | 0.482623E+10 | 11215.09 | 15-OCT-08:62 | 7874.22 | 0.80 |
November | 0.00 | 0.00 | 0.252084E+10 | 0.224860E+10 | 9886.30 | 03-NOV-08:62 | 8346.85 | 0.20 |
December | 0.00 | 0.00 | 0.589147E+09 | 0.548799E+09 | 9586.48 | 28-DEC-16:02 | 9586.48 | 0.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.710850E+11 | 0.578638E+11 | 0.49 | |||
Minimum of Months | 0.00 | 0.00 | 0.589147E+09 | 0.548799E+09 | 9586.12 | 7874.22 | 0.03 | |
Maximum of Months | 0.00 | 0.00 | 0.113373E+11 | 0.905665E+10 | 12004.69 | 9586.82 | 0.96 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.168107E+09 | 0.141740E+09 | 9469.19 | 30-JAN-16:02 | 9469.19 | 0.03 |
February | 0.00 | 0.00 | 0.282336E+09 | 0.275793E+09 | 9523.19 | 05-FEB-16:02 | 9523.19 | 0.01 |
March | 0.00 | 0.00 | 0.912208E+09 | 0.884656E+09 | 9523.47 | 05-MAR-16:02 | 9523.47 | 0.02 |
April | 0.00 | 0.00 | 0.421429E+10 | 0.386895E+10 | 10621.06 | 06-APR-18:11 | 10621.06 | 0.23 |
May | 0.00 | 0.00 | 0.778569E+10 | 0.678831E+10 | 11288.07 | 28-MAY-08:51 | 9001.37 | 0.57 |
June | 0.00 | 0.00 | 0.103596E+11 | 0.878158E+10 | 11409.00 | 04-JUN-08:51 | 9239.31 | 0.78 |
July | 0.00 | 0.00 | 0.107209E+11 | 0.822412E+10 | 12868.61 | 21-JUL-08:51 | 7741.59 | 0.85 |
August | 0.00 | 0.00 | 0.932209E+10 | 0.710667E+10 | 12527.19 | 03-AUG-08:61 | 8937.31 | 0.82 |
September | 0.00 | 0.00 | 0.739371E+10 | 0.551709E+10 | 12185.28 | 03-SEP-08:51 | 8644.03 | 0.75 |
October | 0.00 | 0.00 | 0.349024E+10 | 0.231496E+10 | 11470.28 | 03-OCT-21:51 | 8629.68 | 0.58 |
November | 0.00 | 0.00 | 0.635540E+09 | 0.512430E+09 | 9695.21 | 02-NOV-15:02 | 9401.35 | 0.10 |
December | 0.00 | 0.00 | 72583243.19 | 67569650.79 | 9518.78 | 16-DEC-16:02 | 9518.78 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.553573E+11 | 0.444839E+11 | 0.40 | |||
Minimum of Months | 0.00 | 0.00 | 72583243.19 | 67569650.79 | 9469.19 | 7741.59 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.107209E+11 | 0.878158E+10 | 12868.61 | 10621.06 | 0.85 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.209024E+11 | 0.208260E+11 | 40796.88 | 12-JAN-14:25 | 40796.88 | 0.01 |
February | 0.00 | 0.00 | 0.211718E+11 | 0.209196E+11 | 38387.24 | 07-FEB-13:40 | 38387.24 | 0.03 |
March | 0.00 | 0.00 | 0.198286E+11 | 0.196020E+11 | 29525.48 | 16-MAR-12:50 | 29525.48 | 0.02 |
April | 0.00 | 0.00 | 0.277315E+11 | 0.249430E+11 | 27842.30 | 03-APR-14:00 | 27842.30 | 0.20 |
May | 0.00 | 0.00 | 0.340868E+11 | 0.252926E+11 | 26571.61 | 31-MAY-20:20 | 21981.27 | 0.56 |
June | 0.00 | 0.00 | 0.424858E+11 | 0.293507E+11 | 29863.87 | 15-JUN-20:20 | 29863.87 | 0.80 |
July | 0.00 | 0.00 | 0.460501E+11 | 0.264990E+11 | 30792.81 | 26-JUL-17:20 | 25198.57 | 1.00 |
August | 0.00 | 0.00 | 0.471719E+11 | 0.290244E+11 | 32132.40 | 29-AUG-13:00 | 25982.83 | 1.00 |
September | 0.00 | 0.00 | 0.518574E+11 | 0.356379E+11 | 41253.38 | 19-SEP-13:30 | 33941.25 | 1.00 |
October | 0.00 | 0.00 | 0.463225E+11 | 0.350547E+11 | 47180.64 | 22-OCT-13:15 | 45956.20 | 0.79 |
November | 0.00 | 0.00 | 0.323982E+11 | 0.306933E+11 | 43923.77 | 09-NOV-13:50 | 43923.77 | 0.14 |
December | 0.00 | 0.00 | 0.178334E+11 | 0.178334E+11 | 34169.18 | 16-DEC-13:40 | 34169.18 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.407841E+12 | 0.315677E+12 | 0.46 | |||
Minimum of Months | 0.00 | 0.00 | 0.178334E+11 | 0.178334E+11 | 26571.61 | 21981.27 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.518574E+11 | 0.356379E+11 | 47180.64 | 45956.20 | 1.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.318839E+10 | 0.260417E+10 | 61413.64 | 16-JAN-09:02 | 57353.25 | 0.08 |
February | 0.00 | 0.00 | 0.592666E+10 | 0.540099E+10 | 61991.87 | 21-FEB-21:32 | 61991.87 | 0.07 |
March | 0.00 | 0.00 | 0.120269E+11 | 0.115685E+11 | 63124.46 | 22-MAR-20:22 | 63124.46 | 0.05 |
April | 0.00 | 0.00 | 0.296546E+11 | 0.280097E+11 | 64518.04 | 05-APR-21:52 | 64518.04 | 0.17 |
May | 0.00 | 0.00 | 0.493409E+11 | 0.437501E+11 | 70231.53 | 23-MAY-21:51 | 62107.27 | 0.46 |
June | 0.00 | 0.00 | 0.647682E+11 | 0.551248E+11 | 69701.08 | 19-JUN-18:51 | 64577.10 | 0.68 |
July | 0.00 | 0.00 | 0.695372E+11 | 0.528950E+11 | 81624.17 | 21-JUL-08:51 | 51920.34 | 0.79 |
August | 0.00 | 0.00 | 0.594148E+11 | 0.447913E+11 | 77452.83 | 16-AUG-21:52 | 55902.80 | 0.74 |
September | 0.00 | 0.00 | 0.453411E+11 | 0.334338E+11 | 77940.34 | 23-SEP-21:51 | 56995.85 | 0.65 |
October | 0.00 | 0.00 | 0.276600E+11 | 0.197657E+11 | 75521.23 | 03-OCT-21:51 | 57231.27 | 0.49 |
November | 0.00 | 0.00 | 0.766609E+10 | 0.642419E+10 | 61618.47 | 08-NOV-22:52 | 61618.47 | 0.14 |
December | 0.00 | 0.00 | 0.222765E+10 | 0.203285E+10 | 59327.73 | 16-DEC-09:02 | 59327.73 | 0.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.376753E+12 | 0.305801E+12 | 0.36 | |||
Minimum of Months | 0.00 | 0.00 | 0.222765E+10 | 0.203285E+10 | 59327.73 | 51920.34 | 0.04 | |
Maximum of Months | 0.00 | 0.00 | 0.695372E+11 | 0.551248E+11 | 81624.17 | 64577.10 | 0.79 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.847653E+09 | 0.728066E+09 | 8479.77 | 31-JAN-09:02 | 8479.77 | 0.11 |
February | 0.00 | 0.00 | 0.160171E+10 | 0.153437E+10 | 8479.81 | 06-FEB-09:02 | 8479.81 | 0.07 |
March | 0.00 | 0.00 | 0.265135E+10 | 0.258131E+10 | 8480.18 | 06-MAR-09:02 | 8480.18 | 0.07 |
April | 0.00 | 0.00 | 0.598143E+10 | 0.557324E+10 | 8480.02 | 02-APR-15:02 | 8480.02 | 0.29 |
May | 0.00 | 0.00 | 0.885063E+10 | 0.777754E+10 | 8852.73 | 28-MAY-08:62 | 8230.96 | 0.65 |
June | 0.00 | 0.00 | 0.111609E+11 | 0.963242E+10 | 9143.05 | 29-JUN-08:62 | 7923.53 | 0.88 |
July | 0.00 | 0.00 | 0.116721E+11 | 0.915739E+10 | 10635.03 | 19-JUL-08:62 | 7061.52 | 0.98 |
August | 0.00 | 0.00 | 0.108025E+11 | 0.855820E+10 | 9728.14 | 14-AUG-08:62 | 7451.26 | 0.97 |
September | 0.00 | 0.00 | 0.976021E+10 | 0.758504E+10 | 9822.05 | 23-SEP-18:02 | 7602.33 | 0.97 |
October | 0.00 | 0.00 | 0.606166E+10 | 0.458335E+10 | 10167.74 | 15-OCT-08:62 | 7375.04 | 0.80 |
November | 0.00 | 0.00 | 0.242236E+10 | 0.217794E+10 | 9015.87 | 03-NOV-08:62 | 8125.42 | 0.21 |
December | 0.00 | 0.00 | 0.624169E+09 | 0.547569E+09 | 8479.20 | 17-DEC-09:02 | 8479.20 | 0.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.724367E+11 | 0.604364E+11 | 0.51 | |||
Minimum of Months | 0.00 | 0.00 | 0.624169E+09 | 0.547569E+09 | 8479.20 | 7061.52 | 0.07 | |
Maximum of Months | 0.00 | 0.00 | 0.116721E+11 | 0.963242E+10 | 10635.03 | 8480.18 | 0.98 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.115958E+09 | 78995210.48 | 8071.15 | 31-JAN-09:02 | 8071.15 | 0.03 |
February | 0.00 | 0.00 | 0.474769E+09 | 0.428971E+09 | 8419.14 | 20-FEB-09:02 | 8419.14 | 0.04 |
March | 0.00 | 0.00 | 0.117988E+10 | 0.113053E+10 | 8419.50 | 06-MAR-09:02 | 8419.50 | 0.05 |
April | 0.00 | 0.00 | 0.447723E+10 | 0.413409E+10 | 9768.45 | 27-APR-08:51 | 9768.45 | 0.25 |
May | 0.00 | 0.00 | 0.773803E+10 | 0.681994E+10 | 10812.56 | 28-MAY-08:51 | 9053.77 | 0.59 |
June | 0.00 | 0.00 | 0.104646E+11 | 0.909500E+10 | 11372.50 | 20-JUN-08:62 | 10313.26 | 0.81 |
July | 0.00 | 0.00 | 0.108309E+11 | 0.858516E+10 | 12149.95 | 22-JUL-08:13 | 8825.91 | 0.87 |
August | 0.00 | 0.00 | 0.939459E+10 | 0.742871E+10 | 11890.29 | 03-AUG-07:42 | 9362.57 | 0.84 |
September | 0.00 | 0.00 | 0.723374E+10 | 0.540410E+10 | 11344.86 | 03-SEP-08:51 | 8694.26 | 0.78 |
October | 0.00 | 0.00 | 0.328508E+10 | 0.222665E+10 | 10425.10 | 05-OCT-08:51 | 9311.13 | 0.59 |
November | 0.00 | 0.00 | 0.661780E+09 | 0.561226E+09 | 9060.34 | 03-NOV-08:62 | 7997.51 | 0.09 |
December | 0.00 | 0.00 | 80170993.31 | 59014865.49 | 8305.08 | 16-DEC-09:02 | 8305.08 | 0.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.559367E+11 | 0.459524E+11 | 0.42 | |||
Minimum of Months | 0.00 | 0.00 | 80170993.31 | 59014865.49 | 8071.15 | 7997.51 | 0.02 | |
Maximum of Months | 0.00 | 0.00 | 0.108309E+11 | 0.909500E+10 | 12149.95 | 10313.26 | 0.87 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.188614E+09 | 0.164740E+09 | 2544.68 | 29-JAN-16:02 | 2544.68 | 0.08 |
February | 0.00 | 0.00 | 0.301022E+09 | 0.297271E+09 | 2544.79 | 05-FEB-16:02 | 2544.79 | 0.02 |
March | 0.00 | 0.00 | 0.575772E+09 | 0.566345E+09 | 2581.33 | 11-MAR-16:02 | 2518.03 | 0.03 |
April | 0.00 | 0.00 | 0.137459E+10 | 0.127072E+10 | 2544.81 | 02-APR-18:02 | 2544.81 | 0.26 |
May | 0.00 | 0.00 | 0.214729E+10 | 0.184409E+10 | 2905.52 | 28-MAY-08:62 | 2309.54 | 0.63 |
June | 0.00 | 0.00 | 0.279554E+10 | 0.232467E+10 | 2891.07 | 28-JUN-08:62 | 2275.41 | 0.86 |
July | 0.00 | 0.00 | 0.293616E+10 | 0.219757E+10 | 3366.81 | 19-JUL-08:62 | 1969.71 | 0.96 |
August | 0.00 | 0.00 | 0.267695E+10 | 0.200729E+10 | 3067.77 | 17-AUG-08:62 | 1924.83 | 0.95 |
September | 0.00 | 0.00 | 0.237679E+10 | 0.176478E+10 | 3166.88 | 04-SEP-08:62 | 2136.47 | 0.94 |
October | 0.00 | 0.00 | 0.147206E+10 | 0.110013E+10 | 3118.72 | 15-OCT-08:62 | 1861.01 | 0.71 |
November | 0.00 | 0.00 | 0.515732E+09 | 0.464034E+09 | 2544.77 | 08-NOV-16:02 | 2544.77 | 0.15 |
December | 0.00 | 0.00 | 0.117624E+09 | 0.111159E+09 | 2544.51 | 09-DEC-16:01 | 2544.51 | 0.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.174781E+11 | 0.141128E+11 | 0.47 | |||
Minimum of Months | 0.00 | 0.00 | 0.117624E+09 | 0.111159E+09 | 2544.51 | 1861.01 | 0.02 | |
Maximum of Months | 0.00 | 0.00 | 0.293616E+10 | 0.232467E+10 | 3366.81 | 2544.81 | 0.96 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 28539514.53 | 23597558.61 | 2458.68 | 30-JAN-16:02 | 2458.68 | 0.02 |
February | 0.00 | 0.00 | 46436936.76 | 45662147.91 | 2524.91 | 05-FEB-16:02 | 2524.91 | 0.00 |
March | 0.00 | 0.00 | 0.172794E+09 | 0.168887E+09 | 2547.76 | 11-MAR-16:02 | 2481.37 | 0.02 |
April | 0.00 | 0.00 | 0.102601E+10 | 0.940103E+09 | 2823.85 | 06-APR-18:11 | 2823.85 | 0.22 |
May | 0.00 | 0.00 | 0.197599E+10 | 0.171102E+10 | 2999.59 | 28-MAY-08:51 | 2354.37 | 0.56 |
June | 0.00 | 0.00 | 0.271934E+10 | 0.229555E+10 | 3050.41 | 04-JUN-08:51 | 2434.36 | 0.78 |
July | 0.00 | 0.00 | 0.281450E+10 | 0.215129E+10 | 3478.24 | 21-JUL-08:51 | 2016.74 | 0.86 |
August | 0.00 | 0.00 | 0.241382E+10 | 0.182906E+10 | 3367.25 | 03-AUG-08:61 | 2298.72 | 0.82 |
September | 0.00 | 0.00 | 0.184544E+10 | 0.135882E+10 | 3295.65 | 03-SEP-08:51 | 2223.65 | 0.75 |
October | 0.00 | 0.00 | 0.746100E+09 | 0.501947E+09 | 3097.36 | 03-OCT-21:51 | 2211.77 | 0.50 |
November | 0.00 | 0.00 | 96235500.21 | 76362068.13 | 2611.12 | 02-NOV-15:02 | 2466.98 | 0.06 |
December | 0.00 | 0.00 | 11706793.51 | 10876396.57 | 2516.03 | 16-DEC-16:02 | 2516.03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.138969E+11 | 0.111132E+11 | 0.38 | |||
Minimum of Months | 0.00 | 0.00 | 11706793.51 | 10876396.57 | 2458.68 | 2016.74 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.281450E+10 | 0.229555E+10 | 3478.24 | 2823.85 | 0.86 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.482286E+10 | 0.444024E+10 | 11528.12 | 04-JAN-16:02 | 11528.12 | 0.25 |
February | 0.00 | 0.00 | 0.479676E+10 | 0.463741E+10 | 11528.22 | 20-FEB-09:02 | 11528.22 | 0.11 |
March | 0.00 | 0.00 | 0.473158E+10 | 0.461194E+10 | 11686.55 | 11-MAR-16:02 | 11391.92 | 0.07 |
April | 0.00 | 0.00 | 0.704963E+10 | 0.647860E+10 | 11950.12 | 18-APR-18:02 | 11228.10 | 0.31 |
May | 0.00 | 0.00 | 0.930051E+10 | 0.770628E+10 | 12785.75 | 28-MAY-08:62 | 10695.90 | 0.66 |
June | 0.00 | 0.00 | 0.121426E+11 | 0.984571E+10 | 12698.30 | 28-JUN-08:62 | 10163.39 | 0.88 |
July | 0.00 | 0.00 | 0.135126E+11 | 0.988595E+10 | 15293.84 | 19-JUL-08:62 | 8820.49 | 0.95 |
August | 0.00 | 0.00 | 0.132676E+11 | 0.993087E+10 | 13353.33 | 02-AUG-08:62 | 10328.94 | 0.95 |
September | 0.00 | 0.00 | 0.134862E+11 | 0.104156E+11 | 14035.65 | 23-SEP-18:02 | 9881.06 | 0.94 |
October | 0.00 | 0.00 | 0.111015E+11 | 0.909328E+10 | 13420.55 | 15-OCT-08:62 | 9843.03 | 0.81 |
November | 0.00 | 0.00 | 0.710518E+10 | 0.668548E+10 | 12087.22 | 03-NOV-08:62 | 10795.58 | 0.27 |
December | 0.00 | 0.00 | 0.439790E+10 | 0.410623E+10 | 11528.24 | 23-DEC-16:02 | 11528.24 | 0.20 |
Annual Sum or Average | 0.00 | 0.00 | 0.105715E+12 | 0.878376E+11 | 0.54 | |||
Minimum of Months | 0.00 | 0.00 | 0.439790E+10 | 0.410623E+10 | 11528.12 | 8820.49 | 0.07 | |
Maximum of Months | 0.00 | 0.00 | 0.135126E+11 | 0.104156E+11 | 15293.84 | 11528.24 | 0.95 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 45804.94 | 146802.70 | 14-JAN-16:02 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 31953.93 | 145473.42 | 01-FEB-19:03 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 24318.99 | 136917.28 | 27-MAR-08:07 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7661.06 | 132619.43 | 11-APR-08:05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 330.10 | 53335.98 | 02-MAY-06:00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 1.18 | 9867.48 | 29-JUN-08:05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.99 | 5294.51 | 19-JUL-08:07 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 2.67 | 9556.84 | 14-AUG-08:06 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 494.85 | 68429.43 | 30-SEP-06:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 4526.18 | 118609.01 | 25-OCT-06:05 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 28885.18 | 169412.49 | 27-NOV-19:02 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 39347.06 | 161079.26 | 28-DEC-19:02 |
Annual Sum or Average | 0.00 | 15206.13 | ||||
Minimum of Months | 0.00 | 0.00 | 0.99 | 5294.51 | ||
Maximum of Months | 0.00 | 0.00 | 45804.94 | 169412.49 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 15980.17 | 220904.14 | 03-JAN-16:02 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 31459.42 | 302884.31 | 22-FEB-16:01 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 45736.45 | 309357.55 | 14-MAR-15:02 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 122984.48 | 402166.98 | 28-APR-18:04 | 0.00 | 0.00 | 01-APR-00:10 |
May | 190389.69 | 414378.20 | 12-MAY-18:06 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 252893.34 | 462906.25 | 19-JUN-18:51 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 310836.60 | 613091.07 | 20-JUL-21:51 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 260241.74 | 604206.44 | 01-AUG-21:51 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 225922.40 | 460083.39 | 03-SEP-21:51 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 121521.23 | 479164.98 | 03-OCT-19:30 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 39765.83 | 299112.13 | 03-NOV-15:03 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 12894.02 | 166504.20 | 10-DEC-16:02 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 136475.18 | 0.00 | ||||
Minimum of Months | 12894.02 | 166504.20 | 0.00 | 0.00 | ||
Maximum of Months | 310836.60 | 613091.07 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 24354.76 | 51173.10 | 30-JAN-08:00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 24335.99 | 51167.95 | 01-FEB-07:50 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 23481.45 | 50214.12 | 01-MAR-07:40 |
April | 0.00 | 0.00 | 01-APR-00:10 | 21933.68 | 47296.41 | 03-APR-06:25 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 20157.81 | 43944.27 | 01-MAY-06:15 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 18620.16 | 40265.66 | 01-JUN-06:45 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 17713.04 | 37550.87 | 03-JUL-06:20 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17738.79 | 37701.55 | 31-AUG-06:40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18631.73 | 40210.87 | 29-SEP-06:22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 20173.61 | 44003.88 | 31-OCT-06:20 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 21951.94 | 47566.19 | 30-NOV-07:30 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23478.45 | 50117.98 | 29-DEC-07:15 |
Annual Sum or Average | 0.00 | 21028.95 | ||||
Minimum of Months | 0.00 | 0.00 | 17713.04 | 37550.87 | ||
Maximum of Months | 0.00 | 0.00 | 24354.76 | 51173.10 |
Report: FanReportMonthly
For: FLR_3_DOAS FAN
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.271000E+10 | 0.80 | 1299.30 | 26-JAN-16:03 | 1.01 |
February | 0.244774E+10 | 0.80 | 1299.30 | 07-FEB-09:03 | 1.01 |
March | 0.271000E+10 | 0.80 | 1299.30 | 12-MAR-15:03 | 1.01 |
April | 0.262258E+10 | 0.80 | 1299.30 | 13-APR-08:03 | 1.01 |
May | 0.271000E+10 | 0.80 | 1299.30 | 03-MAY-15:25 | 1.01 |
June | 0.262258E+10 | 0.80 | 1299.30 | 02-JUN-22:10 | 1.01 |
July | 0.271000E+10 | 0.79 | 1299.30 | 08-JUL-19:30 | 1.00 |
August | 0.271000E+10 | 0.79 | 1299.30 | 01-AUG-08:30 | 1.00 |
September | 0.262258E+10 | 0.79 | 1299.30 | 01-SEP-09:04 | 1.00 |
October | 0.271000E+10 | 0.80 | 1299.30 | 23-OCT-08:13 | 1.01 |
November | 0.262258E+10 | 0.80 | 1299.30 | 09-NOV-09:53 | 1.01 |
December | 0.271000E+10 | 0.80 | 1299.30 | 04-DEC-10:40 | 1.01 |
Annual Sum or Average | 0.319080E+11 | 0.80 | |||
Minimum of Months | 0.244774E+10 | 0.79 | 1299.30 | 1.00 | |
Maximum of Months | 0.271000E+10 | 0.80 | 1299.30 | 1.01 |
Report: FanReportMonthly
For: VAV WITH REHEAT FAN
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.337103E+11 | 0.87 | 25540.99 | 03-JAN-22:10 | 1.30 |
February | 0.307046E+11 | 0.87 | 25905.18 | 06-FEB-22:10 | 1.32 |
March | 0.347742E+11 | 0.88 | 26677.24 | 15-MAR-21:10 | 1.34 |
April | 0.364910E+11 | 0.92 | 30229.33 | 21-APR-21:10 | 1.44 |
May | 0.403779E+11 | 0.95 | 32618.73 | 31-MAY-21:10 | 1.50 |
June | 0.423750E+11 | 0.99 | 35705.64 | 15-JUN-21:10 | 1.60 |
July | 0.439387E+11 | 0.99 | 37047.15 | 26-JUL-21:10 | 1.62 |
August | 0.449149E+11 | 1.00 | 39594.21 | 07-AUG-21:10 | 1.69 |
September | 0.433448E+11 | 1.00 | 39834.17 | 22-SEP-21:10 | 1.69 |
October | 0.417116E+11 | 0.96 | 38888.62 | 05-OCT-21:10 | 1.67 |
November | 0.363643E+11 | 0.92 | 33949.30 | 09-NOV-22:10 | 1.55 |
December | 0.341441E+11 | 0.87 | 26209.39 | 15-DEC-22:10 | 1.33 |
Annual Sum or Average | 0.462851E+12 | 0.93 | |||
Minimum of Months | 0.307046E+11 | 0.87 | 25540.99 | 1.30 | |
Maximum of Months | 0.449149E+11 | 1.00 | 39834.17 | 1.69 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205205E+09 | 0.31 | 76.61 | 01-JAN-00:10 | 0.31 |
February | 0.185347E+09 | 0.31 | 76.61 | 01-FEB-00:10 | 0.31 |
March | 0.205205E+09 | 0.31 | 76.61 | 01-MAR-00:10 | 0.31 |
April | 0.198586E+09 | 0.31 | 76.61 | 01-APR-00:10 | 0.31 |
May | 0.205205E+09 | 0.31 | 76.61 | 01-MAY-00:05 | 0.31 |
June | 0.198586E+09 | 0.30 | 76.61 | 01-JUN-00:05 | 0.31 |
July | 0.205205E+09 | 0.30 | 76.61 | 01-JUL-00:10 | 0.30 |
August | 0.205205E+09 | 0.30 | 76.61 | 01-AUG-00:05 | 0.30 |
September | 0.198586E+09 | 0.30 | 76.61 | 01-SEP-00:05 | 0.30 |
October | 0.205205E+09 | 0.30 | 76.61 | 01-OCT-00:10 | 0.31 |
November | 0.198586E+09 | 0.31 | 76.61 | 01-NOV-00:05 | 0.31 |
December | 0.205205E+09 | 0.31 | 76.61 | 01-DEC-00:10 | 0.31 |
Annual Sum or Average | 0.241613E+10 | 0.31 | |||
Minimum of Months | 0.185347E+09 | 0.30 | 76.61 | 0.30 | |
Maximum of Months | 0.205205E+09 | 0.31 | 76.61 | 0.31 |
Report: FanReportMonthly
For: LOBBY_FLR_1 EXHAUST FAN
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | -0.0 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | -0.0 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:10 | -0.0 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 EXHAUST FAN
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 EXHAUST FAN
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116283E+10 | 0.22 | 612.92 | 01-JAN-07:10 | 0.31 |
February | 0.105030E+10 | 0.22 | 612.92 | 01-FEB-07:05 | 0.31 |
March | 0.116283E+10 | 0.22 | 612.92 | 01-MAR-07:05 | 0.31 |
April | 0.112532E+10 | 0.22 | 612.92 | 01-APR-06:05 | 0.31 |
May | 0.116283E+10 | 0.22 | 612.92 | 01-MAY-06:05 | 0.31 |
June | 0.112532E+10 | 0.22 | 612.92 | 01-JUN-06:05 | 0.31 |
July | 0.116283E+10 | 0.21 | 612.92 | 01-JUL-06:10 | 0.30 |
August | 0.116283E+10 | 0.21 | 612.92 | 01-AUG-06:10 | 0.30 |
September | 0.112532E+10 | 0.21 | 612.92 | 01-SEP-06:05 | 0.30 |
October | 0.116283E+10 | 0.22 | 612.92 | 01-OCT-06:10 | 0.31 |
November | 0.112532E+10 | 0.22 | 612.92 | 01-NOV-06:05 | 0.30 |
December | 0.116283E+10 | 0.22 | 612.92 | 01-DEC-07:05 | 0.31 |
Annual Sum or Average | 0.136914E+11 | 0.22 | |||
Minimum of Months | 0.105030E+10 | 0.21 | 612.92 | 0.30 | |
Maximum of Months | 0.116283E+10 | 0.22 | 612.92 | 0.31 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.229283E+09 | 0.51 | 820.57 | 01-JAN-16:02 | 0.66 |
February | 0.215400E+09 | 0.53 | 820.57 | 01-FEB-09:02 | 0.66 |
March | 0.286659E+09 | 0.55 | 820.57 | 01-MAR-16:02 | 0.66 |
April | 0.507336E+09 | 0.59 | 820.57 | 01-APR-08:62 | 0.66 |
May | 0.756469E+09 | 0.62 | 820.57 | 01-MAY-08:62 | 0.66 |
June | 0.923297E+09 | 0.64 | 820.57 | 01-JUN-08:62 | 0.66 |
July | 0.876726E+09 | 0.63 | 820.57 | 01-JUL-08:62 | 0.66 |
August | 0.816050E+09 | 0.63 | 820.57 | 01-AUG-08:62 | 0.66 |
September | 0.752233E+09 | 0.63 | 820.57 | 01-SEP-08:62 | 0.66 |
October | 0.539621E+09 | 0.60 | 820.57 | 01-OCT-08:62 | 0.66 |
November | 0.291649E+09 | 0.56 | 820.57 | 01-NOV-15:02 | 0.66 |
December | 0.230166E+09 | 0.50 | 820.57 | 01-DEC-16:02 | 0.66 |
Annual Sum or Average | 0.642489E+10 | 0.58 | |||
Minimum of Months | 0.215400E+09 | 0.50 | 820.57 | 0.66 | |
Maximum of Months | 0.923297E+09 | 0.64 | 820.57 | 0.66 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.230389E+09 | 0.46 | 815.10 | 01-JAN-16:02 | 0.66 |
February | 0.163154E+09 | 0.43 | 815.10 | 01-FEB-09:02 | 0.66 |
March | 0.159996E+09 | 0.42 | 815.10 | 01-MAR-09:02 | 0.66 |
April | 0.384522E+09 | 0.48 | 815.10 | 01-APR-08:51 | 0.66 |
May | 0.693381E+09 | 0.53 | 815.10 | 01-MAY-08:51 | 0.66 |
June | 0.902098E+09 | 0.57 | 815.10 | 01-JUN-08:31 | 0.66 |
July | 0.844611E+09 | 0.56 | 815.10 | 01-JUL-08:62 | 0.66 |
August | 0.733985E+09 | 0.54 | 815.10 | 01-AUG-07:51 | 0.66 |
September | 0.580254E+09 | 0.50 | 815.10 | 01-SEP-08:51 | 0.65 |
October | 0.295303E+09 | 0.42 | 815.10 | 01-OCT-08:51 | 0.66 |
November | 0.169760E+09 | 0.45 | 815.10 | 01-NOV-15:02 | 0.66 |
December | 0.267829E+09 | 0.46 | 815.10 | 01-DEC-09:02 | 0.66 |
Annual Sum or Average | 0.542528E+10 | 0.49 | |||
Minimum of Months | 0.159996E+09 | 0.42 | 815.10 | 0.65 | |
Maximum of Months | 0.902098E+09 | 0.57 | 815.10 | 0.66 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.118694E+10 | 0.36 | 2894.27 | 02-JAN-14:00 | 0.66 |
February | 0.119704E+10 | 0.42 | 2351.10 | 07-FEB-13:40 | 0.66 |
March | 0.119551E+10 | 0.44 | 1381.64 | 16-MAR-12:50 | 0.66 |
April | 0.165075E+10 | 0.58 | 1322.99 | 03-APR-14:00 | 0.66 |
May | 0.198569E+10 | 0.65 | 1328.91 | 31-MAY-20:20 | 0.66 |
June | 0.228966E+10 | 0.66 | 1476.91 | 17-JUN-17:13 | 0.66 |
July | 0.229490E+10 | 0.66 | 1382.40 | 02-JUL-20:20 | 0.66 |
August | 0.237802E+10 | 0.66 | 1445.20 | 27-AUG-13:50 | 0.66 |
September | 0.262271E+10 | 0.66 | 2643.37 | 19-SEP-13:30 | 0.66 |
October | 0.263827E+10 | 0.62 | 3129.46 | 22-OCT-13:15 | 0.66 |
November | 0.181464E+10 | 0.45 | 3013.12 | 10-NOV-12:00 | 0.66 |
December | 0.102616E+10 | 0.35 | 1539.25 | 16-DEC-13:40 | 0.66 |
Annual Sum or Average | 0.222803E+11 | 0.54 | |||
Minimum of Months | 0.102616E+10 | 0.35 | 1322.99 | 0.66 | |
Maximum of Months | 0.263827E+10 | 0.66 | 3129.46 | 0.66 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.975707E+09 | 0.46 | 5282.72 | 01-JAN-09:02 | 0.66 |
February | 0.927137E+09 | 0.42 | 5282.72 | 01-FEB-16:02 | 0.66 |
March | 0.119963E+10 | 0.39 | 5282.72 | 03-MAR-16:02 | 0.66 |
April | 0.250128E+10 | 0.42 | 5282.72 | 01-APR-08:51 | 0.66 |
May | 0.436565E+10 | 0.47 | 5282.72 | 01-MAY-08:51 | 0.67 |
June | 0.566100E+10 | 0.53 | 5282.72 | 01-JUN-08:31 | 0.66 |
July | 0.556475E+10 | 0.52 | 5282.72 | 01-JUL-08:62 | 0.66 |
August | 0.468918E+10 | 0.49 | 5282.72 | 01-AUG-07:51 | 0.66 |
September | 0.341583E+10 | 0.44 | 5282.72 | 01-SEP-08:51 | 0.66 |
October | 0.213403E+10 | 0.36 | 5282.72 | 01-OCT-08:51 | 0.66 |
November | 0.989704E+09 | 0.42 | 5282.72 | 01-NOV-08:62 | 0.66 |
December | 0.112483E+10 | 0.46 | 5282.72 | 01-DEC-09:02 | 0.66 |
Annual Sum or Average | 0.335487E+11 | 0.45 | |||
Minimum of Months | 0.927137E+09 | 0.36 | 5282.72 | 0.66 | |
Maximum of Months | 0.566100E+10 | 0.53 | 5282.72 | 0.67 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.210122E+09 | 0.50 | 724.66 | 01-JAN-09:02 | 0.66 |
February | 0.222085E+09 | 0.54 | 724.66 | 01-FEB-09:02 | 0.66 |
March | 0.290229E+09 | 0.57 | 724.66 | 01-MAR-09:02 | 0.66 |
April | 0.525975E+09 | 0.63 | 724.66 | 01-APR-08:62 | 0.66 |
May | 0.770151E+09 | 0.65 | 724.66 | 01-MAY-08:62 | 0.66 |
June | 0.967590E+09 | 0.65 | 724.66 | 01-JUN-08:62 | 0.66 |
July | 0.921009E+09 | 0.65 | 724.66 | 01-JUL-08:62 | 0.66 |
August | 0.852371E+09 | 0.64 | 724.66 | 01-AUG-08:62 | 0.66 |
September | 0.764842E+09 | 0.64 | 724.66 | 01-SEP-08:62 | 0.66 |
October | 0.506357E+09 | 0.61 | 724.66 | 01-OCT-08:62 | 0.66 |
November | 0.289484E+09 | 0.57 | 724.66 | 01-NOV-15:02 | 0.66 |
December | 0.216923E+09 | 0.48 | 724.66 | 01-DEC-09:02 | 0.66 |
Annual Sum or Average | 0.653714E+10 | 0.59 | |||
Minimum of Months | 0.210122E+09 | 0.48 | 724.66 | 0.66 | |
Maximum of Months | 0.967590E+09 | 0.65 | 724.66 | 0.66 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.208571E+09 | 0.46 | 719.42 | 02-JAN-09:02 | 0.66 |
February | 0.155267E+09 | 0.43 | 719.42 | 01-FEB-16:02 | 0.66 |
March | 0.177194E+09 | 0.43 | 719.42 | 01-MAR-09:02 | 0.66 |
April | 0.401263E+09 | 0.52 | 719.42 | 01-APR-08:51 | 0.66 |
May | 0.671168E+09 | 0.55 | 719.42 | 01-MAY-08:51 | 0.66 |
June | 0.914414E+09 | 0.58 | 719.42 | 01-JUN-08:12 | 0.66 |
July | 0.858263E+09 | 0.57 | 719.42 | 01-JUL-08:62 | 0.66 |
August | 0.736085E+09 | 0.55 | 719.42 | 01-AUG-07:51 | 0.66 |
September | 0.551060E+09 | 0.51 | 719.42 | 01-SEP-08:51 | 0.65 |
October | 0.277031E+09 | 0.45 | 719.42 | 01-OCT-08:51 | 0.66 |
November | 0.161992E+09 | 0.43 | 719.42 | 02-NOV-15:02 | 0.66 |
December | 0.241252E+09 | 0.46 | 719.42 | 01-DEC-09:02 | 0.66 |
Annual Sum or Average | 0.535356E+10 | 0.49 | |||
Minimum of Months | 0.155267E+09 | 0.43 | 719.42 | 0.65 | |
Maximum of Months | 0.914414E+09 | 0.58 | 719.42 | 0.66 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 70183286.87 | 0.51 | 217.99 | 01-JAN-16:02 | 0.66 |
February | 63170233.47 | 0.52 | 217.99 | 01-FEB-09:02 | 0.66 |
March | 77200938.78 | 0.54 | 217.99 | 01-MAR-09:02 | 0.66 |
April | 0.127655E+09 | 0.59 | 217.99 | 01-APR-15:02 | 0.66 |
May | 0.191111E+09 | 0.62 | 217.99 | 01-MAY-15:02 | 0.66 |
June | 0.238610E+09 | 0.64 | 217.99 | 01-JUN-08:62 | 0.66 |
July | 0.226938E+09 | 0.63 | 217.99 | 01-JUL-08:62 | 0.66 |
August | 0.208094E+09 | 0.63 | 217.99 | 01-AUG-08:62 | 0.66 |
September | 0.186159E+09 | 0.63 | 217.99 | 01-SEP-08:62 | 0.66 |
October | 0.126937E+09 | 0.59 | 217.99 | 01-OCT-08:62 | 0.66 |
November | 76601996.49 | 0.55 | 217.99 | 02-NOV-15:02 | 0.66 |
December | 73858790.17 | 0.50 | 217.99 | 01-DEC-16:02 | 0.66 |
Annual Sum or Average | 0.166652E+10 | 0.58 | |||
Minimum of Months | 63170233.47 | 0.50 | 217.99 | 0.66 | |
Maximum of Months | 0.238610E+09 | 0.64 | 217.99 | 0.66 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 76693345.92 | 0.47 | 216.27 | 01-JAN-16:02 | 0.66 |
February | 54275204.02 | 0.44 | 216.27 | 01-FEB-09:02 | 0.66 |
March | 47239713.72 | 0.42 | 216.27 | 01-MAR-09:02 | 0.66 |
April | 97845267.58 | 0.48 | 216.27 | 01-APR-15:02 | 0.66 |
May | 0.177948E+09 | 0.53 | 216.27 | 01-MAY-08:51 | 0.66 |
June | 0.235758E+09 | 0.57 | 216.27 | 01-JUN-08:31 | 0.66 |
July | 0.221192E+09 | 0.56 | 216.27 | 01-JUL-08:62 | 0.66 |
August | 0.190193E+09 | 0.54 | 216.27 | 01-AUG-07:51 | 0.66 |
September | 0.147042E+09 | 0.50 | 216.27 | 01-SEP-08:51 | 0.65 |
October | 67074722.12 | 0.42 | 216.27 | 01-OCT-08:51 | 0.66 |
November | 53665808.82 | 0.45 | 216.27 | 02-NOV-15:02 | 0.66 |
December | 88196858.71 | 0.48 | 216.27 | 01-DEC-09:02 | 0.66 |
Annual Sum or Average | 0.145712E+10 | 0.49 | |||
Minimum of Months | 47239713.72 | 0.42 | 216.27 | 0.65 | |
Maximum of Months | 0.235758E+09 | 0.57 | 216.27 | 0.66 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.511014E+09 | 0.58 | 973.03 | 01-JAN-09:02 | 0.66 |
February | 0.467697E+09 | 0.59 | 973.03 | 01-FEB-09:02 | 0.66 |
March | 0.451392E+09 | 0.58 | 973.03 | 01-MAR-16:02 | 0.66 |
April | 0.625070E+09 | 0.60 | 973.03 | 01-APR-08:62 | 0.66 |
May | 0.793109E+09 | 0.62 | 973.03 | 01-MAY-15:02 | 0.66 |
June | 0.100535E+10 | 0.63 | 973.03 | 01-JUN-08:62 | 0.66 |
July | 0.101653E+10 | 0.63 | 973.03 | 01-JUL-08:62 | 0.66 |
August | 0.101678E+10 | 0.62 | 973.03 | 01-AUG-08:62 | 0.66 |
September | 0.105225E+10 | 0.63 | 973.03 | 01-SEP-08:62 | 0.66 |
October | 0.938072E+09 | 0.61 | 973.03 | 01-OCT-08:62 | 0.66 |
November | 0.676825E+09 | 0.59 | 973.03 | 01-NOV-08:62 | 0.66 |
December | 0.498163E+09 | 0.58 | 973.03 | 01-DEC-09:02 | 0.66 |
Annual Sum or Average | 0.905225E+10 | 0.60 | |||
Minimum of Months | 0.451392E+09 | 0.58 | 973.03 | 0.66 | |
Maximum of Months | 0.105225E+10 | 0.63 | 973.03 | 0.66 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.848159E+09 | 0.763343E+09 | 747.85 | 06-JAN-10:50 | 673.07 | 673.07 | 40.26 | 1.50 |
February | 0.543028E+09 | 0.488726E+09 | 741.13 | 01-FEB-19:03 | 667.01 | 667.01 | 36.22 | 1.46 |
March | 0.439532E+09 | 0.395578E+09 | 745.14 | 25-MAR-06:20 | 670.62 | 670.62 | 40.45 | 1.49 |
April | 0.126646E+09 | 0.113982E+09 | 717.41 | 11-APR-08:05 | 645.67 | 645.67 | 36.29 | 1.34 |
May | 5711640.18 | 5140476.16 | 334.51 | 02-MAY-06:00 | 301.06 | 301.06 | 28.68 | 0.41 |
June | 22622.57 | 20360.31 | 73.27 | 29-JUN-08:05 | 65.94 | 65.94 | 29.38 | 0.08 |
July | 21378.11 | 19240.30 | 42.28 | 19-JUL-08:07 | 38.05 | 38.05 | 31.10 | 0.04 |
August | 65814.92 | 59233.43 | 81.04 | 14-AUG-08:06 | 72.93 | 72.93 | 33.26 | 0.09 |
September | 8165003.27 | 7348502.94 | 424.52 | 30-SEP-06:00 | 382.07 | 382.07 | 30.32 | 0.55 |
October | 77125413.15 | 69412871.83 | 669.15 | 25-OCT-06:05 | 602.24 | 602.24 | 35.08 | 1.14 |
November | 0.512338E+09 | 0.461104E+09 | 773.48 | 27-NOV-19:02 | 696.13 | 696.13 | 35.97 | 1.69 |
December | 0.782087E+09 | 0.703878E+09 | 773.58 | 28-DEC-19:02 | 696.23 | 696.23 | 37.15 | 1.69 |
Annual Sum or Average | 0.334290E+10 | 0.300861E+10 | ||||||
Minimum of Months | 21378.11 | 19240.30 | 42.28 | 38.05 | 38.05 | 28.68 | 0.04 | |
Maximum of Months | 0.848159E+09 | 0.763343E+09 | 773.58 | 696.23 | 696.23 | 40.45 | 1.69 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 25444710.50 | 22900239.45 | 232.00 | 03-JAN-16:02 | 208.80 | 208.80 | 6.72 | 6.99 |
February | 46537142.68 | 41883428.42 | 314.77 | 20-FEB-16:03 | 283.29 | 283.29 | 6.72 | 8.04 |
March | 76096944.62 | 68487250.16 | 326.61 | 14-MAR-15:03 | 293.95 | 293.95 | 6.72 | 8.17 |
April | 0.292429E+09 | 0.263186E+09 | 1114.51 | 28-APR-18:06 | 1003.06 | 1003.06 | 6.72 | 13.88 |
May | 0.628283E+09 | 0.565455E+09 | 1266.43 | 19-MAY-20:20 | 1139.79 | 1139.79 | 6.72 | 14.64 |
June | 0.958828E+09 | 0.862945E+09 | 1477.59 | 16-JUN-20:30 | 1329.83 | 1329.83 | 6.72 | 15.60 |
July | 0.114140E+10 | 0.102726E+10 | 1336.60 | 21-JUL-21:00 | 1202.94 | 1202.94 | 6.72 | 14.97 |
August | 0.996857E+09 | 0.897171E+09 | 1404.25 | 22-AUG-20:00 | 1263.83 | 1263.83 | 6.72 | 15.28 |
September | 0.788706E+09 | 0.709836E+09 | 1209.23 | 17-SEP-18:03 | 1088.31 | 1088.31 | 6.72 | 14.36 |
October | 0.348271E+09 | 0.313444E+09 | 1121.12 | 01-OCT-19:10 | 1009.01 | 1009.01 | 6.72 | 13.92 |
November | 73187971.33 | 65869174.19 | 648.48 | 03-NOV-15:02 | 583.64 | 583.64 | 6.72 | 11.04 |
December | 19300106.63 | 17370095.97 | 151.77 | 09-DEC-16:01 | 136.60 | 136.60 | 6.72 | 5.73 |
Annual Sum or Average | 0.539535E+10 | 0.485581E+10 | ||||||
Minimum of Months | 19300106.63 | 17370095.97 | 151.77 | 136.60 | 136.60 | 6.72 | 5.73 | |
Maximum of Months | 0.114140E+10 | 0.102726E+10 | 1477.59 | 1329.83 | 1329.83 | 6.72 | 15.60 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.514796E+10 | 0.463316E+10 | 2547.52 | 01-JAN-00:10 | 2292.77 | 2292.77 | 6.77 | 22.53 |
February | 0.526295E+10 | 0.473666E+10 | 2547.52 | 01-FEB-01:30 | 2292.77 | 2292.77 | 6.72 | 22.53 |
March | 0.640616E+10 | 0.576554E+10 | 2547.52 | 01-MAR-00:10 | 2292.77 | 2292.77 | 6.75 | 22.53 |
April | 0.658637E+10 | 0.592773E+10 | 2547.52 | 01-APR-00:10 | 2292.77 | 2292.77 | 6.80 | 22.53 |
May | 0.682329E+10 | 0.614096E+10 | 2547.52 | 01-MAY-00:05 | 2292.77 | 2292.77 | 8.21 | 22.53 |
June | 0.660318E+10 | 0.594286E+10 | 2547.52 | 01-JUN-00:05 | 2292.77 | 2292.77 | 9.14 | 22.53 |
July | 0.682329E+10 | 0.614096E+10 | 2547.52 | 01-JUL-00:10 | 2292.77 | 2292.77 | 9.27 | 22.53 |
August | 0.682329E+10 | 0.614096E+10 | 2547.52 | 01-AUG-00:05 | 2292.77 | 2292.77 | 9.77 | 22.53 |
September | 0.660318E+10 | 0.594286E+10 | 2547.52 | 01-SEP-00:05 | 2292.77 | 2292.77 | 8.88 | 22.53 |
October | 0.682329E+10 | 0.614096E+10 | 2547.52 | 01-OCT-00:10 | 2292.77 | 2292.77 | 7.40 | 22.53 |
November | 0.559976E+10 | 0.503979E+10 | 2547.52 | 01-NOV-00:05 | 2292.77 | 2292.77 | 6.92 | 22.53 |
December | 0.504588E+10 | 0.454129E+10 | 2547.52 | 01-DEC-00:10 | 2292.77 | 2292.77 | 6.74 | 22.53 |
Annual Sum or Average | 0.745486E+11 | 0.670937E+11 | ||||||
Minimum of Months | 0.504588E+10 | 0.454129E+10 | 2547.52 | 2292.77 | 2292.77 | 6.72 | 22.53 | |
Maximum of Months | 0.682329E+10 | 0.614096E+10 | 2547.52 | 2292.77 | 2292.77 | 9.77 | 22.53 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:10 | 14.37 | 14.37 | 50.03 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:10 | 14.37 | 14.37 | 50.82 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:10 | 14.37 | 14.37 | 50.99 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 53.57 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:05 | 14.37 | 14.37 | 53.86 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:05 | 14.37 | 14.37 | 54.38 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 54.91 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:05 | 14.37 | 14.37 | 54.88 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:05 | 14.37 | 14.37 | 54.74 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:10 | 14.37 | 14.37 | 53.87 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:05 | 14.37 | 14.37 | 53.84 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:10 | 14.37 | 14.37 | 51.45 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 50.03 | 0.37 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 54.91 | 0.37 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 34.37 | 60.00 | 45804.94 | 146802.70 | 14-JAN-16:02 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 33.61 | 60.00 | 31953.93 | 145473.42 | 01-FEB-19:03 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 34.00 | 60.00 | 24318.99 | 136917.28 | 27-MAR-08:07 |
April | 0.00 | 0.00 | 01-APR-00:10 | 25.02 | 60.00 | 7661.06 | 132619.43 | 11-APR-08:05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.27 | 26.27 | 330.10 | 53335.98 | 02-MAY-06:00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 27.23 | 27.23 | 1.18 | 9867.48 | 29-JUN-08:05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 29.79 | 29.79 | 0.99 | 5294.51 | 19-JUL-08:07 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 32.16 | 32.16 | 2.67 | 9556.84 | 14-AUG-08:06 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 37.40 | 37.40 | 494.85 | 68429.43 | 30-SEP-06:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.39 | 25.39 | 4526.18 | 118609.01 | 25-OCT-06:05 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 25.16 | 60.00 | 28885.18 | 169412.49 | 27-NOV-19:02 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 31.99 | 60.00 | 39347.06 | 161079.26 | 28-DEC-19:02 |
Annual Sum or Average | 0.00 | 15206.13 | ||||||
Minimum of Months | 0.00 | 0.00 | 25.02 | 25.39 | 0.99 | 5294.51 | ||
Maximum of Months | 0.00 | 0.00 | 37.40 | 60.00 | 45804.94 | 169412.49 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 15980.17 | 220904.14 | 03-JAN-16:02 | 9.04 | 6.70 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 31459.42 | 302884.31 | 22-FEB-16:01 | 9.91 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 45736.45 | 309357.55 | 14-MAR-15:02 | 9.98 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 122984.48 | 402166.98 | 28-APR-18:04 | 10.96 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 190389.69 | 414378.20 | 12-MAY-18:06 | 11.09 | 6.70 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 252893.34 | 462906.25 | 19-JUN-18:51 | 11.60 | 6.70 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 310836.60 | 613091.07 | 20-JUL-21:51 | 13.20 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 260241.74 | 604206.44 | 01-AUG-21:51 | 13.10 | 6.70 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 225922.40 | 460083.39 | 03-SEP-21:51 | 11.57 | 6.70 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 121521.23 | 479164.98 | 03-OCT-19:30 | 11.78 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 39765.83 | 299112.13 | 03-NOV-15:03 | 9.87 | 6.70 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 12894.02 | 166504.20 | 10-DEC-16:02 | 8.46 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 136475.18 | 0.00 | ||||||
Minimum of Months | 12894.02 | 166504.20 | 8.46 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 310836.60 | 613091.07 | 13.20 | 6.70 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 50.03 | 60.05 | 24354.76 | 51173.10 | 30-JAN-08:00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 50.82 | 60.05 | 24335.99 | 51167.95 | 01-FEB-07:50 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 50.99 | 60.05 | 23481.45 | 50214.12 | 01-MAR-07:40 |
April | 0.00 | 0.00 | 01-APR-00:10 | 53.57 | 60.05 | 21933.68 | 47296.41 | 03-APR-06:25 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 53.86 | 60.05 | 20157.81 | 43944.27 | 01-MAY-06:15 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 54.38 | 60.05 | 18620.16 | 40265.66 | 01-JUN-06:45 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 54.91 | 60.05 | 17713.04 | 37550.87 | 03-JUL-06:20 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 54.88 | 60.05 | 17738.79 | 37701.55 | 31-AUG-06:40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 54.74 | 60.05 | 18631.73 | 40210.87 | 29-SEP-06:22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 53.87 | 60.05 | 20173.61 | 44003.88 | 31-OCT-06:20 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 53.84 | 60.05 | 21951.94 | 47566.19 | 30-NOV-07:30 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 51.45 | 60.05 | 23478.45 | 50117.98 | 29-DEC-07:15 |
Annual Sum or Average | 0.00 | 21028.95 | ||||||
Minimum of Months | 0.00 | 0.00 | 50.03 | 60.05 | 17713.04 | 37550.87 | ||
Maximum of Months | 0.00 | 0.00 | 54.91 | 60.05 | 24354.76 | 51173.10 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 28411761.06 | 0.00 | 0.424271E+09 | 0.271000E+10 | 0.00 | 0.00 |
February | 49814462.23 | 0.00 | 0.213369E+10 | 0.244774E+10 | 0.00 | 0.00 |
March | 15218592.06 | 0.00 | 0.440496E+10 | 0.271000E+10 | 0.00 | 0.00 |
April | 24133.11 | 0.00 | 0.144455E+11 | 0.262258E+10 | 0.00 | 0.00 |
May | 30554.25 | 0.00 | 0.238762E+11 | 0.271000E+10 | 0.00 | 0.00 |
June | 21128.86 | 0.00 | 0.298114E+11 | 0.262258E+10 | 0.00 | 0.00 |
July | 21755.18 | 0.00 | 0.419047E+11 | 0.271000E+10 | 0.00 | 0.00 |
August | 19998.12 | 0.00 | 0.343740E+11 | 0.271000E+10 | 0.00 | 0.00 |
September | 23349.97 | 0.00 | 0.288701E+11 | 0.262258E+10 | 0.00 | 0.00 |
October | 19032.16 | 0.00 | 0.136959E+11 | 0.271000E+10 | 0.00 | 0.00 |
November | 6725.13 | 0.00 | 0.268590E+10 | 0.262258E+10 | 0.00 | 0.00 |
December | 91444079.72 | 0.00 | 0.217497E+09 | 0.271000E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.185056E+09 | 0.00 | 0.196844E+12 | 0.319080E+11 | 0.00 | 0.00 |
Minimum of Months | 6725.13 | 0.00 | 0.217497E+09 | 0.244774E+10 | 0.00 | 0.00 |
Maximum of Months | 91444079.72 | 0.00 | 0.419047E+11 | 0.271000E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.109922E+12 | 0.00 | 0.651804E+10 | 0.337103E+11 | 0.00 | 0.00 |
February | 0.699447E+11 | 0.00 | 0.332095E+11 | 0.307046E+11 | 0.00 | 0.00 |
March | 0.620069E+11 | 0.00 | 0.676421E+11 | 0.347742E+11 | 0.00 | 0.00 |
April | 0.196942E+11 | 0.00 | 0.211171E+12 | 0.364910E+11 | 0.00 | 0.00 |
May | 0.874521E+09 | 0.00 | 0.349935E+12 | 0.403779E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.451818E+12 | 0.423750E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.605002E+12 | 0.439387E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.491342E+12 | 0.449149E+11 | 0.00 | 0.00 |
September | 0.129368E+10 | 0.00 | 0.401659E+12 | 0.433448E+11 | 0.00 | 0.00 |
October | 0.121078E+11 | 0.00 | 0.198949E+12 | 0.417116E+11 | 0.00 | 0.00 |
November | 0.694380E+11 | 0.00 | 0.412903E+11 | 0.363643E+11 | 0.00 | 0.00 |
December | 0.871391E+11 | 0.00 | 0.381061E+10 | 0.341441E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.432421E+12 | 0.00 | 0.286235E+13 | 0.462851E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.381061E+10 | 0.307046E+11 | 0.00 | 0.00 |
Maximum of Months | 0.109922E+12 | 0.00 | 0.605002E+12 | 0.449149E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.271000E+10 | 0.424271E+09 | 28411761.06 | 0.275172E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244774E+10 | 0.213369E+10 | 49814462.23 | 0.195612E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.271000E+10 | 0.440496E+10 | 15218592.06 | 0.155900E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.262258E+10 | 0.144455E+11 | 24133.11 | 0.518223E+10 | 0.289450E+09 | 0.00 | 0.00 | 0.00 |
May | 0.271000E+10 | 0.238762E+11 | 30554.25 | 0.242118E+10 | 0.209771E+10 | 0.00 | 0.00 | 0.00 |
June | 0.262258E+10 | 0.298114E+11 | 21128.86 | 0.952145E+09 | 0.510602E+10 | 0.00 | 0.00 | 0.00 |
July | 0.271000E+10 | 0.419047E+11 | 21755.18 | 624317.73 | 0.163652E+11 | 0.00 | 0.00 | 0.00 |
August | 0.271000E+10 | 0.343740E+11 | 19998.12 | 0.213171E+09 | 0.893725E+10 | 0.00 | 0.00 | 0.00 |
September | 0.262258E+10 | 0.288701E+11 | 23349.97 | 0.925135E+09 | 0.465669E+10 | 0.00 | 0.00 | 0.00 |
October | 0.271000E+10 | 0.136959E+11 | 19032.16 | 0.349469E+10 | 0.958486E+09 | 0.00 | 0.00 | 0.00 |
November | 0.262258E+10 | 0.268590E+10 | 6725.13 | 0.181593E+11 | 4348571.35 | 0.00 | 0.00 | 0.00 |
December | 0.271000E+10 | 0.217497E+09 | 91444079.72 | 0.322499E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319080E+11 | 0.196844E+12 | 0.185056E+09 | 0.126267E+12 | 0.384152E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244774E+10 | 0.217497E+09 | 6725.13 | 624317.73 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.271000E+10 | 0.419047E+11 | 91444079.72 | 0.322499E+11 | 0.163652E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.337103E+11 | 0.651804E+10 | 0.109922E+12 | 0.127273E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.307046E+11 | 0.332095E+11 | 0.699447E+11 | 0.940462E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.347742E+11 | 0.676421E+11 | 0.620069E+11 | 0.569617E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.364910E+11 | 0.211171E+12 | 0.196942E+11 | 0.111963E+11 | 0.432627E+10 | 0.00 | 0.00 | 0.00 |
May | 0.403779E+11 | 0.349935E+12 | 0.874521E+09 | 0.187967E+11 | 0.190363E+11 | 0.00 | 0.00 | 0.00 |
June | 0.423750E+11 | 0.451818E+12 | 0.00 | 0.247130E+11 | 0.442066E+11 | 0.00 | 0.00 | 0.00 |
July | 0.439387E+11 | 0.605002E+12 | 0.00 | 0.959240E+10 | 0.761290E+11 | 0.00 | 0.00 | 0.00 |
August | 0.449149E+11 | 0.491342E+12 | 0.00 | 0.115338E+11 | 0.365310E+11 | 0.00 | 0.00 | 0.00 |
September | 0.433448E+11 | 0.401659E+12 | 0.129368E+10 | 0.698437E+10 | 0.209700E+11 | 0.00 | 0.00 | 0.00 |
October | 0.417116E+11 | 0.198949E+12 | 0.121078E+11 | 0.501813E+10 | 0.385478E+10 | 0.00 | 0.00 | 0.00 |
November | 0.363643E+11 | 0.412903E+11 | 0.694380E+11 | 0.739866E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.341441E+11 | 0.381061E+10 | 0.871391E+11 | 0.222334E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.462851E+12 | 0.286235E+13 | 0.432421E+12 | 0.662436E+12 | 0.205054E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.307046E+11 | 0.381061E+10 | 0.00 | 0.501813E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.449149E+11 | 0.605002E+12 | 0.109922E+12 | 0.222334E+12 | 0.761290E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.271000E+10 | 28411761.06 | 0.424271E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244774E+10 | 49814462.23 | 0.213369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.271000E+10 | 15218592.06 | 0.440496E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.262258E+10 | 24133.11 | 0.144455E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.271000E+10 | 30554.25 | 0.238762E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.262258E+10 | 21128.86 | 0.298114E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.271000E+10 | 21755.18 | 0.419047E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.271000E+10 | 19998.12 | 0.343740E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.262258E+10 | 23349.97 | 0.288701E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.271000E+10 | 19032.16 | 0.136959E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.262258E+10 | 6725.13 | 0.268590E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.271000E+10 | 91444079.72 | 0.217497E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319080E+11 | 0.185056E+09 | 0.196844E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244774E+10 | 6725.13 | 0.217497E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.271000E+10 | 91444079.72 | 0.419047E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.337103E+11 | 0.109922E+12 | 0.651804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.307046E+11 | 0.699447E+11 | 0.332095E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.347742E+11 | 0.620069E+11 | 0.676421E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.364910E+11 | 0.196942E+11 | 0.211171E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.403779E+11 | 0.874521E+09 | 0.349935E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.423750E+11 | 0.00 | 0.451818E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.439387E+11 | 0.00 | 0.605002E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.449149E+11 | 0.00 | 0.491342E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.433448E+11 | 0.129368E+10 | 0.401659E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.417116E+11 | 0.121078E+11 | 0.198949E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.363643E+11 | 0.694380E+11 | 0.412903E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.341441E+11 | 0.871391E+11 | 0.381061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.462851E+12 | 0.432421E+12 | 0.286235E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.307046E+11 | 0.00 | 0.381061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.449149E+11 | 0.109922E+12 | 0.605002E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.133797E+11 | 0.00 | 0.00 | 33810109.69 | 0.00 | 0.00 | 0.443033E+11 | 0.00 | 1.00 |
February | 0.404441E+11 | 0.00 | 0.00 | 1630035.81 | 0.00 | 0.00 | 0.406150E+10 | 0.00 | 0.96 |
March | 0.448000E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.96 |
April | 0.274293E+11 | 0.00 | 0.00 | 0.00 | 95320083.08 | 0.00 | 0.00 | 0.00 | 0.96 |
May | 0.161160E+11 | 0.00 | 0.00 | 0.00 | 0.546273E+09 | 0.00 | 0.00 | 0.00 | 0.94 |
June | 0.809193E+10 | 3976883.25 | 0.00 | 590114.29 | 0.156315E+10 | 0.00 | 0.281513E+09 | 0.00 | 0.86 |
July | 0.215073E+09 | 0.447244E+10 | 0.00 | 16289980.44 | 0.292657E+10 | 0.00 | 0.200883E+10 | 0.00 | 0.88 |
August | 16003844.86 | 0.199029E+10 | 0.00 | 59536977.42 | 0.161897E+09 | 0.00 | 0.884166E+10 | 0.00 | 1.03 |
September | 96179.02 | 0.146489E+10 | 0.00 | 86106636.02 | 4409510.31 | 0.00 | 0.179445E+11 | 0.00 | 1.23 |
October | 0.00 | 0.243045E+09 | 0.00 | 0.103705E+09 | 0.00 | 0.00 | 0.417675E+11 | 0.00 | 1.27 |
November | 0.00 | 0.00 | 0.00 | 92411990.71 | 0.00 | 0.00 | 0.613698E+11 | 0.00 | 1.22 |
December | 0.356051E+09 | 0.00 | 0.00 | 73971085.06 | 0.00 | 0.00 | 0.616953E+11 | 0.00 | 1.12 |
Annual Sum or Average | 0.150848E+12 | 0.817464E+10 | 0.00 | 0.468052E+09 | 0.529762E+10 | 0.00 | 0.242274E+12 | 0.00 | 1.04 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.86 |
Maximum of Months | 0.448000E+11 | 0.447244E+10 | 0.00 | 0.103705E+09 | 0.292657E+10 | 0.00 | 0.616953E+11 | 0.00 | 1.27 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.559384E+10 | 0.00 | 0.00 | 1905874.07 | 0.00 | 15831185.90 | 0.144349E+10 | 0.00 | 2.25 |
February | 0.458002E+10 | 0.00 | 0.00 | 1926081.09 | 0.00 | 9775083.80 | 0.103026E+10 | 0.00 | 2.26 |
March | 0.490321E+10 | 0.00 | 0.00 | 1351809.82 | 0.00 | 4407182.37 | 0.659258E+09 | 0.00 | 2.20 |
April | 0.278090E+10 | 14044382.21 | 0.00 | 2359532.90 | 68974.61 | 0.00 | 0.615010E+09 | 0.00 | 2.21 |
May | 0.131307E+10 | 71845230.44 | 0.00 | 2931983.93 | 2335828.77 | 0.00 | 0.690348E+09 | 0.00 | 2.18 |
June | 0.338417E+09 | 0.233337E+09 | 0.00 | 3602619.51 | 1318498.25 | 0.00 | 0.716829E+09 | 0.00 | 2.10 |
July | 54812273.43 | 0.814952E+09 | 0.00 | 1745964.60 | 0.141196E+09 | 0.00 | 0.222795E+09 | 0.00 | 2.09 |
August | 0.344597E+09 | 0.268604E+09 | 0.00 | 4105124.26 | 21756158.75 | 0.00 | 0.590621E+09 | 0.00 | 2.24 |
September | 0.720051E+09 | 0.203395E+09 | 0.00 | 5703293.68 | 6844359.55 | 0.00 | 0.932339E+09 | 0.00 | 2.52 |
October | 0.233983E+10 | 38028068.55 | 0.00 | 6487956.08 | 585403.80 | 0.00 | 0.165429E+10 | 0.00 | 2.55 |
November | 0.432092E+10 | 0.00 | 0.00 | 3971870.53 | 0.00 | 22658510.74 | 0.188655E+10 | 0.00 | 2.42 |
December | 0.521442E+10 | 0.00 | 0.00 | 1537518.49 | 0.00 | 0.157971E+09 | 0.131428E+10 | 0.00 | 2.22 |
Annual Sum or Average | 0.325041E+11 | 0.164421E+10 | 0.00 | 37629628.97 | 0.174105E+09 | 0.210643E+09 | 0.117561E+11 | 0.00 | 2.27 |
Minimum of Months | 54812273.43 | 0.00 | 0.00 | 1351809.82 | 0.00 | 0.00 | 0.222795E+09 | 0.00 | 2.09 |
Maximum of Months | 0.559384E+10 | 0.814952E+09 | 0.00 | 6487956.08 | 0.141196E+09 | 0.157971E+09 | 0.188655E+10 | 0.00 | 2.55 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.399940E+10 | 0.00 | 0.00 | 592891.30 | 0.00 | 0.00 | 0.114431E+10 | 0.00 | 1.40 |
February | 0.289975E+10 | 0.00 | 0.00 | 778424.25 | 0.00 | 0.00 | 0.125107E+10 | 0.00 | 1.41 |
March | 0.259093E+10 | 0.00 | 0.00 | 1206651.34 | 0.00 | 0.00 | 0.161189E+10 | 0.00 | 1.42 |
April | 0.755220E+09 | 3500768.17 | 0.00 | 3191789.45 | 5352159.93 | 0.00 | 0.190077E+10 | 0.00 | 1.49 |
May | 0.138941E+09 | 38153923.85 | 0.00 | 5162733.77 | 12639408.22 | 0.00 | 0.152494E+10 | 0.00 | 1.54 |
June | 13516290.11 | 0.143257E+09 | 0.00 | 5434052.14 | 7839836.21 | 0.00 | 0.922414E+09 | 0.00 | 1.47 |
July | 337607.50 | 0.686076E+09 | 0.00 | 2782786.26 | 57472117.95 | 0.00 | 0.250546E+09 | 0.00 | 1.45 |
August | 27782140.18 | 0.188328E+09 | 0.00 | 5101397.87 | 15314541.27 | 0.00 | 0.780898E+09 | 0.00 | 1.52 |
September | 34037361.20 | 0.118189E+09 | 0.00 | 5764004.10 | 11056834.95 | 0.00 | 0.137550E+10 | 0.00 | 1.62 |
October | 0.507408E+09 | 19174573.52 | 0.00 | 4369268.68 | 2120222.31 | 0.00 | 0.257019E+10 | 0.00 | 1.54 |
November | 0.228058E+10 | 0.00 | 0.00 | 1606358.63 | 0.00 | 0.00 | 0.219126E+10 | 0.00 | 1.43 |
December | 0.404494E+10 | 0.00 | 0.00 | 391333.26 | 0.00 | 0.00 | 0.849920E+09 | 0.00 | 1.40 |
Annual Sum or Average | 0.172928E+11 | 0.119668E+10 | 0.00 | 36381691.04 | 0.111795E+09 | 0.00 | 0.163737E+11 | 0.00 | 1.47 |
Minimum of Months | 337607.50 | 0.00 | 0.00 | 391333.26 | 0.00 | 0.00 | 0.250546E+09 | 0.00 | 1.40 |
Maximum of Months | 0.404494E+10 | 0.686076E+09 | 0.00 | 5764004.10 | 57472117.95 | 0.00 | 0.257019E+10 | 0.00 | 1.62 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.445651E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 |
February | 0.358749E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 |
March | 0.361364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
April | 0.217568E+10 | 0.00 | 0.00 | 55336.41 | 7688687.22 | 0.00 | 36824953.65 | 0.00 | 0.58 |
May | 0.835056E+09 | 4940171.55 | 0.00 | 1416121.30 | 39125918.47 | 0.00 | 0.486481E+09 | 0.00 | 0.58 |
June | 61128179.88 | 0.123765E+09 | 0.00 | 4126485.15 | 8419472.25 | 0.00 | 0.683213E+09 | 0.00 | 0.58 |
July | 2869721.34 | 0.527502E+09 | 0.00 | 2201311.91 | 97356692.23 | 0.00 | 0.198852E+09 | 0.00 | 0.57 |
August | 0.128742E+09 | 0.151336E+09 | 0.00 | 3133774.32 | 20365046.08 | 0.00 | 0.503610E+09 | 0.00 | 0.58 |
September | 0.482226E+09 | 49086847.79 | 0.00 | 1831570.46 | 57819074.49 | 0.00 | 0.583055E+09 | 0.00 | 0.59 |
October | 0.232484E+10 | 6015164.07 | 0.00 | 289866.98 | 11303258.72 | 0.00 | 0.162280E+09 | 0.00 | 0.58 |
November | 0.379995E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 |
December | 0.425058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 |
Annual Sum or Average | 0.257187E+11 | 0.862646E+09 | 0.00 | 13054466.53 | 0.242078E+09 | 0.00 | 0.265432E+10 | 0.00 | 0.58 |
Minimum of Months | 2869721.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 |
Maximum of Months | 0.445651E+10 | 0.527502E+09 | 0.00 | 4126485.15 | 97356692.23 | 0.00 | 0.683213E+09 | 0.00 | 0.59 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.268516E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
February | 0.216155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
March | 0.217731E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
April | 0.133308E+10 | 0.00 | 0.00 | 0.00 | 4632616.76 | 0.00 | 0.00 | 0.00 | 0.60 |
May | 0.693666E+09 | 1311017.32 | 0.00 | 211672.25 | 25238212.81 | 0.00 | 89793485.90 | 0.00 | 0.59 |
June | 0.118222E+09 | 67507731.47 | 0.00 | 1459980.44 | 10300759.64 | 0.00 | 0.298621E+09 | 0.00 | 0.56 |
July | 13333978.82 | 0.233155E+09 | 0.00 | 938158.24 | 0.120364E+09 | 0.00 | 96947517.38 | 0.00 | 0.55 |
August | 0.185341E+09 | 71658393.07 | 0.00 | 908090.11 | 25627178.11 | 0.00 | 0.178666E+09 | 0.00 | 0.57 |
September | 0.539535E+09 | 16292588.33 | 0.00 | 270452.56 | 46666737.98 | 0.00 | 88927248.65 | 0.00 | 0.59 |
October | 0.148385E+10 | 1627248.95 | 0.00 | 32411.70 | 8194215.71 | 0.00 | 12769902.05 | 0.00 | 0.61 |
November | 0.228956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
December | 0.256108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
Annual Sum or Average | 0.162417E+11 | 0.391552E+09 | 0.00 | 3820765.30 | 0.241023E+09 | 0.00 | 0.765726E+09 | 0.00 | 0.59 |
Minimum of Months | 13333978.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.55 |
Maximum of Months | 0.268516E+10 | 0.233155E+09 | 0.00 | 1459980.44 | 0.120364E+09 | 0.00 | 0.298621E+09 | 0.00 | 0.61 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 22381769.27 | 0.00 | 0.00 | 0.101548E+09 | 0.00 | 0.00 | 0.883155E+11 | 0.00 | 23.68 |
February | 38373172.13 | 0.00 | 0.00 | 94334966.74 | 0.00 | 0.00 | 0.715249E+11 | 0.00 | 23.91 |
March | 5420242.67 | 0.00 | 0.00 | 0.111845E+09 | 0.00 | 0.00 | 0.722571E+11 | 0.00 | 24.21 |
April | 0.00 | 0.124028E+09 | 0.00 | 0.123623E+09 | 0.00 | 0.00 | 0.433913E+11 | 0.00 | 24.11 |
May | 0.00 | 0.716840E+09 | 0.00 | 0.121772E+09 | 0.00 | 0.00 | 0.251418E+11 | 0.00 | 23.47 |
June | 0.00 | 0.220298E+10 | 0.00 | 88939911.58 | 0.00 | 0.00 | 0.125220E+11 | 0.00 | 20.96 |
July | 0.00 | 0.112212E+11 | 0.00 | 34160924.08 | 0.00 | 0.00 | 0.318794E+10 | 0.00 | 20.61 |
August | 0.00 | 0.308588E+10 | 0.00 | 85576818.43 | 0.00 | 0.00 | 0.111951E+11 | 0.00 | 21.83 |
September | 0.00 | 0.191580E+10 | 0.00 | 0.100104E+09 | 0.00 | 0.00 | 0.203750E+11 | 0.00 | 23.58 |
October | 0.00 | 0.341007E+09 | 0.00 | 0.117297E+09 | 0.00 | 0.00 | 0.492534E+11 | 0.00 | 24.36 |
November | 13883454.79 | 0.00 | 0.00 | 0.105382E+09 | 0.00 | 0.00 | 0.760629E+11 | 0.00 | 23.83 |
December | 78888410.79 | 0.00 | 0.00 | 0.100564E+09 | 0.00 | 0.00 | 0.841195E+11 | 0.00 | 23.74 |
Annual Sum or Average | 0.158947E+09 | 0.196077E+11 | 0.00 | 0.118515E+10 | 0.00 | 0.00 | 0.557346E+12 | 0.00 | 23.19 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 34160924.08 | 0.00 | 0.00 | 0.318794E+10 | 0.00 | 20.61 |
Maximum of Months | 78888410.79 | 0.112212E+11 | 0.00 | 0.123623E+09 | 0.00 | 0.00 | 0.883155E+11 | 0.00 | 24.36 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.538666E+10 | 0.00 | 0.00 | 24802765.00 | 0.00 | 0.00 | 0.261868E+11 | 0.00 | 3.58 |
February | 0.333782E+10 | 0.00 | 0.00 | 25255710.28 | 0.00 | 0.00 | 0.219473E+11 | 0.00 | 3.62 |
March | 0.448414E+10 | 0.00 | 0.00 | 26808539.90 | 0.00 | 0.00 | 0.206661E+11 | 0.00 | 3.55 |
April | 0.209101E+10 | 57164432.81 | 0.00 | 32073110.03 | 111498.23 | 0.00 | 0.139585E+11 | 0.00 | 3.71 |
May | 0.734675E+09 | 0.293094E+09 | 0.00 | 32291498.30 | 8522901.94 | 0.00 | 0.936696E+10 | 0.00 | 3.74 |
June | 0.128243E+09 | 0.893272E+09 | 0.00 | 29341474.47 | 14537053.94 | 0.00 | 0.555381E+10 | 0.00 | 3.57 |
July | 5360421.70 | 0.412083E+10 | 0.00 | 15442845.88 | 0.236715E+09 | 0.00 | 0.154508E+10 | 0.00 | 3.54 |
August | 0.193899E+09 | 0.119304E+10 | 0.00 | 30137523.15 | 37270917.63 | 0.00 | 0.479867E+10 | 0.00 | 3.78 |
September | 0.193429E+09 | 0.832321E+09 | 0.00 | 37902972.68 | 15920953.71 | 0.00 | 0.836720E+10 | 0.00 | 4.16 |
October | 0.129892E+10 | 0.148629E+09 | 0.00 | 45431742.81 | 1869046.55 | 0.00 | 0.179578E+11 | 0.00 | 4.17 |
November | 0.325441E+10 | 0.00 | 0.00 | 35472098.11 | 0.00 | 0.00 | 0.250621E+11 | 0.00 | 3.86 |
December | 0.580164E+10 | 0.00 | 0.00 | 21625768.89 | 0.00 | 0.00 | 0.240331E+11 | 0.00 | 3.54 |
Annual Sum or Average | 0.269102E+11 | 0.753836E+10 | 0.00 | 0.356586E+09 | 0.314947E+09 | 0.00 | 0.179443E+12 | 0.00 | 3.74 |
Minimum of Months | 5360421.70 | 0.00 | 0.00 | 15442845.88 | 0.00 | 0.00 | 0.154508E+10 | 0.00 | 3.54 |
Maximum of Months | 0.580164E+10 | 0.412083E+10 | 0.00 | 45431742.81 | 0.236715E+09 | 0.00 | 0.261868E+11 | 0.00 | 4.17 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.335153E+11 | 0.00 | 0.00 | 50169772.89 | 0.00 | 0.00 | 0.721005E+11 | 0.00 | 1.71 |
February | 0.245136E+11 | 0.00 | 0.00 | 52343407.31 | 0.00 | 0.00 | 0.611239E+11 | 0.00 | 1.73 |
March | 0.246335E+11 | 0.00 | 0.00 | 61342969.38 | 0.00 | 0.00 | 0.625910E+11 | 0.00 | 1.75 |
April | 0.829434E+10 | 0.154736E+09 | 0.00 | 89032840.68 | 22900385.32 | 0.00 | 0.483153E+11 | 0.00 | 1.85 |
May | 0.221326E+10 | 0.836013E+09 | 0.00 | 0.111897E+09 | 0.182611E+09 | 0.00 | 0.340386E+11 | 0.00 | 1.91 |
June | 0.327169E+09 | 0.279809E+10 | 0.00 | 0.108957E+09 | 0.192699E+09 | 0.00 | 0.199710E+11 | 0.00 | 1.80 |
July | 4132632.65 | 0.140741E+11 | 0.00 | 57580439.38 | 0.112791E+10 | 0.00 | 0.549629E+10 | 0.00 | 1.78 |
August | 0.491069E+09 | 0.379180E+10 | 0.00 | 0.106057E+09 | 0.316474E+09 | 0.00 | 0.172110E+11 | 0.00 | 1.87 |
September | 0.406358E+09 | 0.242416E+10 | 0.00 | 0.124220E+09 | 0.188881E+09 | 0.00 | 0.301120E+11 | 0.00 | 2.00 |
October | 0.454069E+10 | 0.408174E+09 | 0.00 | 0.129087E+09 | 20621178.23 | 0.00 | 0.620771E+11 | 0.00 | 1.95 |
November | 0.137261E+11 | 0.00 | 0.00 | 87518976.06 | 0.00 | 0.00 | 0.803334E+11 | 0.00 | 1.78 |
December | 0.381481E+11 | 0.00 | 0.00 | 42365456.06 | 0.00 | 0.00 | 0.616574E+11 | 0.00 | 1.70 |
Annual Sum or Average | 0.150814E+12 | 0.244870E+11 | 0.00 | 0.102057E+10 | 0.205209E+10 | 0.00 | 0.555028E+12 | 0.00 | 1.82 |
Minimum of Months | 4132632.65 | 0.00 | 0.00 | 42365456.06 | 0.00 | 0.00 | 0.549629E+10 | 0.00 | 1.70 |
Maximum of Months | 0.381481E+11 | 0.140741E+11 | 0.00 | 0.129087E+09 | 0.112791E+10 | 0.00 | 0.803334E+11 | 0.00 | 2.00 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 66064732.08 | 0.00 | 0.00 | 3486971.12 | 0.00 | 0.772125E+09 | 0.567526E+09 | 0.00 | 0.35 |
February | 42192987.06 | 0.00 | 0.00 | 4798966.20 | 0.00 | 0.489161E+09 | 0.655493E+09 | 0.00 | 0.35 |
March | 46570025.05 | 0.00 | 0.00 | 8453409.18 | 0.00 | 0.298434E+09 | 0.896923E+09 | 0.00 | 0.35 |
April | 12831010.71 | 3324559.25 | 0.00 | 15714285.45 | 0.00 | 26410331.61 | 0.812976E+09 | 0.00 | 0.35 |
May | 110116.53 | 24255715.84 | 0.00 | 15679062.89 | 0.00 | 495712.32 | 0.511300E+09 | 0.00 | 0.36 |
June | 0.00 | 51737319.13 | 0.00 | 12643934.00 | 0.00 | 28145.76 | 0.156856E+09 | 0.00 | 0.36 |
July | 0.00 | 0.517041E+09 | 0.00 | 624739.75 | 0.00 | 0.00 | 1625535.31 | 0.00 | 0.36 |
August | 0.00 | 0.226850E+09 | 0.00 | 6020130.28 | 0.00 | 144648.75 | 62686857.18 | 0.00 | 0.35 |
September | 0.00 | 0.224352E+09 | 0.00 | 9739484.82 | 0.00 | 177028.37 | 0.262476E+09 | 0.00 | 0.36 |
October | 6304058.79 | 29881135.09 | 0.00 | 14733419.53 | 0.00 | 2098854.28 | 0.814202E+09 | 0.00 | 0.36 |
November | 17531388.04 | 64379.95 | 0.00 | 7595295.99 | 0.00 | 0.386316E+09 | 0.860202E+09 | 0.00 | 0.35 |
December | 69159206.75 | 0.00 | 0.00 | 2536886.29 | 0.00 | 0.883492E+09 | 0.463555E+09 | 0.00 | 0.35 |
Annual Sum or Average | 0.260764E+09 | 0.107751E+10 | 0.00 | 0.102027E+09 | 0.00 | 0.285888E+10 | 0.606582E+10 | 0.00 | 0.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 624739.75 | 0.00 | 0.00 | 1625535.31 | 0.00 | 0.35 |
Maximum of Months | 69159206.75 | 0.517041E+09 | 0.00 | 15714285.45 | 0.00 | 0.883492E+09 | 0.896923E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.105399E+09 | 0.00 | 0.00 | 1177391.25 | 0.00 | 0.109352E+10 | 0.208940E+09 | 0.00 | 0.35 |
February | 0.150523E+09 | 0.00 | 0.00 | 1580799.73 | 0.00 | 0.700449E+09 | 0.338954E+09 | 0.00 | 0.35 |
March | 0.193376E+09 | 0.00 | 0.00 | 3808034.44 | 0.00 | 0.409955E+09 | 0.643096E+09 | 0.00 | 0.35 |
April | 0.152051E+09 | 3206048.28 | 0.00 | 12682040.82 | 118121.45 | 29418171.24 | 0.673679E+09 | 0.00 | 0.35 |
May | 98492492.23 | 23151806.70 | 8591.95 | 13270063.40 | 1091251.53 | 479762.23 | 0.415281E+09 | 1223.74 | 0.36 |
June | 39157012.78 | 50447231.65 | 2943.30 | 10267301.23 | 1281031.82 | 3442.39 | 0.120080E+09 | 50.57 | 0.36 |
July | 929564.86 | 0.442766E+09 | 0.00 | 518321.63 | 74214160.52 | 0.00 | 802124.92 | 0.00 | 0.36 |
August | 27876682.94 | 0.199868E+09 | 10459.91 | 4469499.64 | 26944798.25 | 2031.08 | 36495355.57 | 159.53 | 0.36 |
September | 85628163.84 | 0.195013E+09 | 17637.88 | 6907821.13 | 29294507.26 | 151427.59 | 0.179674E+09 | 484.06 | 0.36 |
October | 0.174005E+09 | 26600082.25 | 0.00 | 7774180.67 | 3277551.83 | 2352803.16 | 0.653108E+09 | 0.00 | 0.36 |
November | 0.150678E+09 | 58248.29 | 0.00 | 2726581.79 | 6124.12 | 0.599400E+09 | 0.518691E+09 | 0.00 | 0.35 |
December | 0.105205E+09 | 0.00 | 0.00 | 678026.68 | 0.00 | 0.119625E+10 | 0.116440E+09 | 0.00 | 0.35 |
Annual Sum or Average | 0.128332E+10 | 0.941111E+09 | 39633.05 | 65860062.43 | 0.136228E+09 | 0.403199E+10 | 0.390524E+10 | 1917.90 | 0.36 |
Minimum of Months | 929564.86 | 0.00 | 0.00 | 518321.63 | 0.00 | 0.00 | 802124.92 | 0.00 | 0.35 |
Maximum of Months | 0.193376E+09 | 0.442766E+09 | 17637.88 | 13270063.40 | 74214160.52 | 0.119625E+10 | 0.673679E+09 | 1223.74 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.286202E+09 | 0.00 | 0.00 | 3294826.37 | 0.00 | 0.00 | 0.120634E+10 | 0.00 | 0.02 |
February | 0.160178E+09 | 0.00 | 0.00 | 2868804.00 | 0.00 | 0.00 | 0.103850E+10 | 0.00 | 0.02 |
March | 92214858.59 | 0.00 | 0.00 | 2925079.14 | 0.00 | 0.00 | 0.108574E+10 | 0.00 | 0.02 |
April | 0.00 | 1343754.81 | 0.00 | 2949525.68 | 0.00 | 0.00 | 0.534246E+09 | 0.00 | 0.02 |
May | 0.00 | 22942709.98 | 0.00 | 2346743.93 | 0.00 | 0.00 | 0.199061E+09 | 0.00 | 0.02 |
June | 0.00 | 30826955.80 | 0.00 | 1940098.92 | 0.00 | 0.00 | 70588457.47 | 0.00 | 0.02 |
July | 0.00 | 0.310183E+09 | 0.00 | 216453.52 | 0.00 | 0.00 | 7749312.08 | 0.00 | 0.02 |
August | 0.00 | 0.118367E+09 | 0.00 | 1386813.06 | 0.00 | 0.00 | 38848220.51 | 0.00 | 0.02 |
September | 0.00 | 0.118952E+09 | 0.00 | 2130253.54 | 0.00 | 0.00 | 0.102164E+09 | 0.00 | 0.02 |
October | 18618334.64 | 32148456.20 | 0.00 | 4225924.64 | 0.00 | 0.00 | 0.655180E+09 | 0.00 | 0.02 |
November | 0.214663E+09 | 0.00 | 0.00 | 4191611.88 | 0.00 | 0.00 | 0.958520E+09 | 0.00 | 0.02 |
December | 0.299206E+09 | 0.00 | 0.00 | 2676292.13 | 0.00 | 0.00 | 0.122816E+10 | 0.00 | 0.02 |
Annual Sum or Average | 0.107108E+10 | 0.634764E+09 | 0.00 | 31152426.81 | 0.00 | 0.00 | 0.712511E+10 | 0.00 | 0.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 216453.52 | 0.00 | 0.00 | 7749312.08 | 0.00 | 0.02 |
Maximum of Months | 0.299206E+09 | 0.310183E+09 | 0.00 | 4225924.64 | 0.00 | 0.00 | 0.122816E+10 | 0.00 | 0.02 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.142968E+10 | 0.00 | 0.00 | 19604445.74 | 0.00 | 0.410650E+10 | 0.135570E+11 | 0.00 | 0.40 |
February | 0.204175E+10 | 0.00 | 0.00 | 29690580.54 | 0.00 | 0.237205E+10 | 0.117186E+11 | 0.00 | 0.40 |
March | 0.262033E+10 | 0.00 | 0.00 | 55741885.84 | 0.00 | 0.421684E+09 | 0.138609E+11 | 0.00 | 0.40 |
April | 0.213100E+10 | 37118906.93 | 0.00 | 0.121471E+09 | 7971461.25 | 11970413.44 | 0.950715E+10 | 0.00 | 0.40 |
May | 0.138899E+10 | 0.297619E+09 | 0.00 | 0.121960E+09 | 31356302.72 | 1013906.16 | 0.564357E+10 | 0.00 | 0.40 |
June | 0.531141E+09 | 0.678489E+09 | 0.00 | 92652055.18 | 23214220.58 | 0.00 | 0.167548E+10 | 0.00 | 0.40 |
July | 12608989.66 | 0.598804E+10 | 0.00 | 4167501.42 | 0.102450E+10 | 0.00 | 13743563.91 | 0.00 | 0.40 |
August | 0.378249E+09 | 0.268169E+10 | 0.00 | 40908305.73 | 0.395037E+09 | 0.00 | 0.514664E+09 | 0.00 | 0.40 |
September | 0.121915E+10 | 0.258314E+10 | 98408.39 | 61562882.06 | 0.459603E+09 | 1035908.71 | 0.241267E+10 | 4632.49 | 0.40 |
October | 0.241525E+10 | 0.336391E+09 | 0.00 | 87755713.15 | 68881072.02 | 6510102.07 | 0.884714E+10 | 0.00 | 0.40 |
November | 0.207498E+10 | 98457.21 | 0.00 | 36779990.60 | 774715.92 | 0.923596E+09 | 0.142117E+11 | 0.00 | 0.40 |
December | 0.142704E+10 | 0.00 | 0.00 | 14914533.28 | 0.00 | 0.689564E+10 | 0.109045E+11 | 0.00 | 0.40 |
Annual Sum or Average | 0.176702E+11 | 0.126026E+11 | 98408.39 | 0.687209E+09 | 0.201133E+10 | 0.147400E+11 | 0.928671E+11 | 4632.49 | 0.40 |
Minimum of Months | 12608989.66 | 0.00 | 0.00 | 4167501.42 | 0.00 | 0.00 | 13743563.91 | 0.00 | 0.40 |
Maximum of Months | 0.262033E+10 | 0.598804E+10 | 98408.39 | 0.121960E+09 | 0.102450E+10 | 0.689564E+10 | 0.142117E+11 | 4632.49 | 0.40 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 69696701.62 | 0.00 | 0.00 | 3557420.63 | 0.00 | 0.793988E+09 | 0.541960E+09 | 0.00 | 0.35 |
February | 37969069.35 | 0.00 | 0.00 | 5579976.72 | 0.00 | 0.463810E+09 | 0.684288E+09 | 0.00 | 0.35 |
March | 24416890.19 | 0.00 | 0.00 | 8623130.11 | 0.00 | 0.313124E+09 | 0.904216E+09 | 0.00 | 0.35 |
April | 2728433.31 | 3324559.25 | 0.00 | 16981367.00 | 0.00 | 26372858.66 | 0.821849E+09 | 0.00 | 0.35 |
May | 0.00 | 24255715.84 | 0.00 | 17618017.38 | 0.00 | 29432.99 | 0.509937E+09 | 0.00 | 0.36 |
June | 0.00 | 51737319.13 | 0.00 | 14191053.54 | 0.00 | 0.00 | 0.155337E+09 | 0.00 | 0.36 |
July | 0.00 | 0.517016E+09 | 24835.26 | 596189.40 | 0.00 | 0.00 | 1654085.66 | 368.08 | 0.36 |
August | 0.00 | 0.226850E+09 | 0.00 | 6673851.19 | 0.00 | 70112.45 | 62107672.57 | 0.00 | 0.35 |
September | 0.00 | 0.224352E+09 | 0.00 | 10408820.88 | 0.00 | 0.00 | 0.261984E+09 | 0.00 | 0.36 |
October | 7044941.73 | 29881135.09 | 0.00 | 13501608.54 | 0.00 | 6257692.76 | 0.810534E+09 | 0.00 | 0.36 |
November | 18635972.04 | 64379.95 | 0.00 | 7937595.80 | 0.00 | 0.415363E+09 | 0.829708E+09 | 0.00 | 0.35 |
December | 75331204.31 | 0.00 | 0.00 | 2837086.35 | 0.00 | 0.852911E+09 | 0.487663E+09 | 0.00 | 0.35 |
Annual Sum or Average | 0.235823E+09 | 0.107748E+10 | 24835.26 | 0.108506E+09 | 0.00 | 0.287193E+10 | 0.607124E+10 | 368.08 | 0.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 596189.40 | 0.00 | 0.00 | 1654085.66 | 0.00 | 0.35 |
Maximum of Months | 75331204.31 | 0.517016E+09 | 24835.26 | 17618017.38 | 0.00 | 0.852911E+09 | 0.904216E+09 | 368.08 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.105824E+09 | 0.00 | 0.00 | 684023.90 | 0.00 | 0.108586E+10 | 0.216673E+09 | 0.00 | 0.35 |
February | 0.150512E+09 | 0.00 | 0.00 | 2232843.07 | 0.00 | 0.621459E+09 | 0.417304E+09 | 0.00 | 0.35 |
March | 0.187415E+09 | 0.00 | 0.00 | 4655238.47 | 0.00 | 0.405066E+09 | 0.653098E+09 | 0.00 | 0.35 |
April | 0.136282E+09 | 3206048.28 | 0.00 | 13995902.96 | 118121.45 | 30751012.55 | 0.686801E+09 | 0.00 | 0.35 |
May | 94263437.95 | 23197502.07 | 0.00 | 14210009.28 | 1055371.85 | 114076.78 | 0.418936E+09 | 0.00 | 0.36 |
June | 38171493.92 | 50352097.78 | 0.00 | 10860325.21 | 1379159.56 | 0.00 | 0.120476E+09 | 0.00 | 0.36 |
July | 929564.86 | 0.444836E+09 | 0.00 | 455286.76 | 72144699.63 | 0.00 | 865159.79 | 0.00 | 0.36 |
August | 27253324.37 | 0.200416E+09 | 0.00 | 4489767.99 | 26407017.43 | 0.00 | 37100476.87 | 0.00 | 0.36 |
September | 83876342.92 | 0.196351E+09 | 0.00 | 7063986.61 | 27974756.40 | 0.00 | 0.181421E+09 | 0.00 | 0.36 |
October | 0.164583E+09 | 26647191.28 | 6227.74 | 7994900.32 | 3224162.71 | 14980611.66 | 0.649682E+09 | 52.36 | 0.36 |
November | 0.152202E+09 | 23265.86 | 0.00 | 3231938.53 | 41106.55 | 0.572658E+09 | 0.543403E+09 | 0.00 | 0.35 |
December | 0.104207E+09 | 0.00 | 0.00 | 550372.02 | 0.00 | 0.114472E+10 | 0.169097E+09 | 0.00 | 0.35 |
Annual Sum or Average | 0.124552E+10 | 0.945029E+09 | 6227.74 | 70424595.11 | 0.132344E+09 | 0.387561E+10 | 0.409486E+10 | 52.36 | 0.36 |
Minimum of Months | 929564.86 | 0.00 | 0.00 | 455286.76 | 0.00 | 0.00 | 865159.79 | 0.00 | 0.35 |
Maximum of Months | 0.187415E+09 | 0.444836E+09 | 6227.74 | 14210009.28 | 72144699.63 | 0.114472E+10 | 0.686801E+09 | 52.36 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.329464E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
February | 0.265218E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
March | 0.267152E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
April | 0.163567E+11 | 0.00 | 0.00 | 0.00 | 56841405.75 | 0.00 | 0.00 | 0.00 | 0.59 |
May | 0.836169E+10 | 14845792.68 | 0.00 | 2582503.46 | 0.310909E+09 | 0.00 | 0.124843E+10 | 0.00 | 0.57 |
June | 0.158763E+10 | 0.742571E+09 | 0.00 | 14007509.77 | 0.201343E+09 | 0.00 | 0.349973E+10 | 0.00 | 0.54 |
July | 0.289409E+09 | 0.186662E+10 | 0.00 | 6688824.15 | 0.240694E+10 | 0.00 | 0.103582E+10 | 0.00 | 0.53 |
August | 0.242856E+10 | 0.756318E+09 | 0.00 | 8551251.88 | 0.425487E+09 | 0.00 | 0.202413E+10 | 0.00 | 0.55 |
September | 0.545335E+10 | 0.281239E+09 | 0.00 | 6148954.88 | 0.491722E+09 | 0.00 | 0.227564E+10 | 0.00 | 0.58 |
October | 0.180461E+11 | 28355268.47 | 0.00 | 672391.49 | 92152402.69 | 0.00 | 0.319645E+09 | 0.00 | 0.59 |
November | 0.280925E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
December | 0.314240E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
Annual Sum or Average | 0.198223E+12 | 0.368995E+10 | 0.00 | 38651435.63 | 0.398539E+10 | 0.00 | 0.104034E+11 | 0.00 | 0.57 |
Minimum of Months | 0.289409E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
Maximum of Months | 0.329464E+11 | 0.186662E+10 | 0.00 | 14007509.77 | 0.240694E+10 | 0.00 | 0.349973E+10 | 0.00 | 0.59 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 17758770.14 | 0.00 | 0.00 | 714550.85 | 0.00 | 0.243556E+09 | 90270994.48 | 0.00 | 0.35 |
February | 11786748.78 | 0.00 | 0.00 | 1017629.63 | 0.00 | 0.179300E+09 | 0.105807E+09 | 0.00 | 0.35 |
March | 11764375.45 | 0.00 | 0.00 | 1888785.46 | 0.00 | 0.142293E+09 | 0.156649E+09 | 0.00 | 0.35 |
April | 3561590.18 | 831139.81 | 0.00 | 3750710.23 | 0.00 | 27095926.77 | 0.182575E+09 | 0.00 | 0.35 |
May | 0.00 | 6063866.82 | 0.00 | 3728322.36 | 0.00 | 637712.37 | 0.127530E+09 | 62.14 | 0.36 |
June | 0.00 | 12934329.78 | 0.00 | 3082715.49 | 0.00 | 20310.19 | 39278876.24 | 0.00 | 0.36 |
July | 0.00 | 0.129260E+09 | 0.00 | 160126.83 | 0.00 | 0.00 | 402441.94 | 0.00 | 0.36 |
August | 0.00 | 56705033.91 | 7040.52 | 1441530.92 | 0.00 | 33450.59 | 15737927.54 | 396.19 | 0.36 |
September | 0.00 | 56088053.91 | 0.00 | 2276235.67 | 0.00 | 91014.84 | 65730964.78 | 0.00 | 0.36 |
October | 2149147.57 | 7470283.77 | 0.00 | 3290575.51 | 0.00 | 15782756.89 | 0.188112E+09 | 0.00 | 0.36 |
November | 5780490.01 | 16094.99 | 0.00 | 1555809.81 | 0.00 | 0.151661E+09 | 0.158914E+09 | 0.00 | 0.35 |
December | 19190058.19 | 0.00 | 0.00 | 515757.65 | 0.00 | 0.263580E+09 | 71399702.01 | 0.00 | 0.35 |
Annual Sum or Average | 71991180.30 | 0.269369E+09 | 7040.52 | 23422750.41 | 0.00 | 0.102405E+10 | 0.120241E+10 | 458.33 | 0.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 160126.83 | 0.00 | 0.00 | 402441.94 | 0.00 | 0.35 |
Maximum of Months | 19190058.19 | 0.129260E+09 | 7040.52 | 3750710.23 | 0.00 | 0.263580E+09 | 0.188112E+09 | 396.19 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 26038202.32 | 0.00 | 0.00 | 203010.59 | 0.00 | 0.298803E+09 | 27215222.29 | 0.00 | 0.35 |
February | 37630723.64 | 0.00 | 0.00 | 281706.69 | 0.00 | 0.221116E+09 | 38848859.21 | 0.00 | 0.35 |
March | 48393879.87 | 0.00 | 0.00 | 767217.68 | 0.00 | 0.166274E+09 | 97123419.73 | 0.00 | 0.35 |
April | 37934111.25 | 801512.07 | 0.00 | 3033918.63 | 29530.36 | 26838633.78 | 0.149151E+09 | 0.00 | 0.35 |
May | 24623123.06 | 5788393.33 | 1990.59 | 3199602.68 | 272812.88 | 109991.92 | 0.103948E+09 | 21.68 | 0.36 |
June | 9789253.19 | 12626929.88 | 350.65 | 2576085.22 | 305377.16 | 345.81 | 30011252.03 | 156.65 | 0.36 |
July | 232391.21 | 0.110684E+09 | 7787.73 | 137693.45 | 18553540.13 | 0.00 | 192418.19 | 47.58 | 0.36 |
August | 6969170.73 | 49969626.36 | 0.00 | 1099246.87 | 6736199.56 | 613.31 | 9141861.39 | 0.00 | 0.36 |
September | 21407040.96 | 48750469.87 | 6891.64 | 1614620.21 | 7323626.82 | 49052.28 | 45019523.15 | 494.05 | 0.36 |
October | 43682063.45 | 6679027.75 | 3730.10 | 1578649.88 | 786595.55 | 20564155.12 | 0.143485E+09 | 55.12 | 0.36 |
November | 38048942.46 | 13026.40 | 0.00 | 478860.28 | 3066.70 | 0.212518E+09 | 66827671.44 | 0.00 | 0.35 |
December | 25666433.04 | 0.00 | 0.00 | 109238.80 | 0.00 | 0.314093E+09 | 14775479.38 | 0.00 | 0.35 |
Annual Sum or Average | 0.320415E+09 | 0.235313E+09 | 20750.71 | 15079850.98 | 34010749.17 | 0.126037E+10 | 0.725740E+09 | 775.07 | 0.36 |
Minimum of Months | 232391.21 | 0.00 | 0.00 | 109238.80 | 0.00 | 0.00 | 192418.19 | 0.00 | 0.35 |
Maximum of Months | 48393879.87 | 0.110684E+09 | 7787.73 | 3199602.68 | 18553540.13 | 0.314093E+09 | 0.149151E+09 | 494.05 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 24089488.57 | 0.00 | 0.00 | 12821097.12 | 0.00 | 0.735117E+09 | 0.149132E+10 | 0.00 | 0.40 |
February | 12145452.51 | 0.00 | 0.00 | 13132298.06 | 0.00 | 0.473426E+09 | 0.141523E+10 | 0.00 | 0.40 |
March | 16611529.98 | 0.00 | 0.00 | 14419986.32 | 0.00 | 0.352546E+09 | 0.162469E+10 | 0.00 | 0.40 |
April | 4419765.78 | 5339648.86 | 0.00 | 20477000.97 | 0.00 | 60571375.37 | 0.130854E+10 | 0.00 | 0.40 |
May | 0.00 | 38957646.97 | 0.00 | 18245370.58 | 0.00 | 3783165.80 | 0.825337E+09 | 0.00 | 0.40 |
June | 0.00 | 83096463.83 | 0.00 | 15585273.61 | 0.00 | 45205.54 | 0.256652E+09 | 0.00 | 0.40 |
July | 0.00 | 0.830431E+09 | 0.00 | 754408.51 | 0.00 | 0.00 | 2859808.52 | 0.00 | 0.40 |
August | 0.00 | 0.364349E+09 | 0.00 | 8124469.60 | 0.00 | 112609.17 | 0.102347E+09 | 0.00 | 0.40 |
September | 0.00 | 0.360337E+09 | 0.00 | 13757715.57 | 0.00 | 274851.26 | 0.423464E+09 | 0.00 | 0.40 |
October | 9120932.95 | 47992758.49 | 0.00 | 24746095.56 | 0.00 | 849770.73 | 0.131015E+10 | 0.00 | 0.40 |
November | 22527439.14 | 103402.08 | 0.00 | 18654242.16 | 0.00 | 0.385934E+09 | 0.161530E+10 | 0.00 | 0.40 |
December | 26619844.83 | 0.00 | 0.00 | 11996125.63 | 0.00 | 0.881665E+09 | 0.135839E+10 | 0.00 | 0.40 |
Annual Sum or Average | 0.115534E+09 | 0.173061E+10 | 0.00 | 0.172714E+09 | 0.00 | 0.289433E+10 | 0.117343E+11 | 0.00 | 0.40 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 754408.51 | 0.00 | 0.00 | 2859808.52 | 0.00 | 0.40 |
Maximum of Months | 26619844.83 | 0.830431E+09 | 0.00 | 24746095.56 | 0.00 | 0.881665E+09 | 0.162469E+10 | 0.00 | 0.40 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.136510E+10 | 0.00 | 0.00 | 57127652.96 | 0.00 | 0.00 | 0.547436E+11 | 0.00 | 4.59 |
February | 0.770415E+09 | 0.00 | 0.00 | 57939596.20 | 0.00 | 0.00 | 0.458458E+11 | 0.00 | 4.73 |
March | 0.400158E+09 | 0.00 | 0.00 | 73625201.89 | 0.00 | 0.00 | 0.487274E+11 | 0.00 | 4.93 |
April | 42060514.40 | 93999385.96 | 0.00 | 91950982.49 | 0.00 | 0.00 | 0.329126E+11 | 0.00 | 5.40 |
May | 0.00 | 0.571876E+09 | 0.00 | 95359337.85 | 0.00 | 0.00 | 0.212929E+11 | 0.00 | 5.63 |
June | 0.00 | 0.176205E+10 | 0.00 | 76999623.14 | 0.00 | 0.00 | 0.116969E+11 | 0.00 | 5.32 |
July | 0.00 | 0.868050E+10 | 0.00 | 34303759.07 | 0.00 | 0.00 | 0.313214E+10 | 0.00 | 5.22 |
August | 0.00 | 0.229888E+10 | 0.00 | 72886664.68 | 0.00 | 0.00 | 0.100040E+11 | 0.00 | 5.39 |
September | 0.00 | 0.140396E+10 | 0.00 | 79319587.58 | 0.00 | 0.00 | 0.168608E+11 | 0.00 | 5.60 |
October | 9344634.32 | 0.223135E+09 | 0.00 | 87949976.14 | 0.00 | 0.00 | 0.364186E+11 | 0.00 | 5.35 |
November | 0.555457E+09 | 0.00 | 0.00 | 65732574.38 | 0.00 | 0.00 | 0.495088E+11 | 0.00 | 4.77 |
December | 0.153944E+10 | 0.00 | 0.00 | 54169763.33 | 0.00 | 0.00 | 0.509124E+11 | 0.00 | 4.53 |
Annual Sum or Average | 0.468197E+10 | 0.150344E+11 | 0.00 | 0.847365E+09 | 0.00 | 0.00 | 0.382056E+12 | 0.00 | 5.12 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 34303759.07 | 0.00 | 0.00 | 0.313214E+10 | 0.00 | 4.53 |
Maximum of Months | 0.153944E+10 | 0.868050E+10 | 0.00 | 95359337.85 | 0.00 | 0.00 | 0.547436E+11 | 0.00 | 5.63 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.260046E+09 | 0.00 | 0.00 | 71417259.10 | 0.00 | 0.00 | 0.614346E+11 | 0.00 | 5.03 |
February | 0.143973E+09 | 0.00 | 0.00 | 70399838.92 | 0.00 | 0.00 | 0.510535E+11 | 0.00 | 5.18 |
March | 10849774.84 | 0.00 | 0.00 | 86823878.75 | 0.00 | 0.00 | 0.537271E+11 | 0.00 | 5.40 |
April | 0.00 | 0.103459E+09 | 0.00 | 0.102251E+09 | 0.00 | 0.00 | 0.355005E+11 | 0.00 | 5.84 |
May | 0.00 | 0.619219E+09 | 0.00 | 0.102689E+09 | 0.00 | 0.00 | 0.225990E+11 | 0.00 | 6.01 |
June | 0.00 | 0.188920E+10 | 0.00 | 81598513.02 | 0.00 | 0.00 | 0.122926E+11 | 0.00 | 5.64 |
July | 0.00 | 0.925340E+10 | 0.00 | 36091096.15 | 0.00 | 0.00 | 0.328179E+10 | 0.00 | 5.53 |
August | 0.00 | 0.245571E+10 | 0.00 | 77560099.14 | 0.00 | 0.00 | 0.105510E+11 | 0.00 | 5.73 |
September | 0.00 | 0.150882E+10 | 0.00 | 85221993.85 | 0.00 | 0.00 | 0.178651E+11 | 0.00 | 5.96 |
October | 0.00 | 0.239513E+09 | 0.00 | 97746395.07 | 0.00 | 0.00 | 0.391796E+11 | 0.00 | 5.76 |
November | 70192191.83 | 0.00 | 0.00 | 78721044.33 | 0.00 | 0.00 | 0.546422E+11 | 0.00 | 5.20 |
December | 0.379262E+09 | 0.00 | 0.00 | 68873177.57 | 0.00 | 0.00 | 0.572727E+11 | 0.00 | 4.97 |
Annual Sum or Average | 0.864323E+09 | 0.160693E+11 | 0.00 | 0.959394E+09 | 0.00 | 0.00 | 0.419400E+12 | 0.00 | 5.52 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 36091096.15 | 0.00 | 0.00 | 0.328179E+10 | 0.00 | 4.97 |
Maximum of Months | 0.379262E+09 | 0.925340E+10 | 0.00 | 0.102689E+09 | 0.00 | 0.00 | 0.614346E+11 | 0.00 | 6.01 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.115123E+09 | 0.00 | 0.00 | 0.835424E+11 | 0.00 | 22.91 |
February | 0.00 | 0.00 | 0.00 | 0.108494E+09 | 0.00 | 0.00 | 0.669422E+11 | 0.00 | 23.33 |
March | 0.00 | 0.00 | 0.00 | 0.127797E+09 | 0.00 | 0.00 | 0.664055E+11 | 0.00 | 23.72 |
April | 0.00 | 0.181011E+09 | 0.00 | 0.141270E+09 | 0.00 | 0.00 | 0.395743E+11 | 0.00 | 24.05 |
May | 0.00 | 0.103829E+10 | 0.00 | 0.132427E+09 | 0.00 | 0.00 | 0.223299E+11 | 0.00 | 23.80 |
June | 0.00 | 0.297932E+10 | 0.00 | 96860745.87 | 0.00 | 0.00 | 0.113346E+11 | 0.00 | 21.92 |
July | 0.00 | 0.124804E+11 | 0.00 | 36134397.76 | 0.00 | 0.00 | 0.282515E+10 | 0.00 | 21.64 |
August | 0.00 | 0.353766E+10 | 0.00 | 95529679.52 | 0.00 | 0.00 | 0.102315E+11 | 0.00 | 22.46 |
September | 0.00 | 0.237785E+10 | 0.00 | 0.108840E+09 | 0.00 | 0.00 | 0.180132E+11 | 0.00 | 23.74 |
October | 0.00 | 0.380183E+09 | 0.00 | 0.136131E+09 | 0.00 | 0.00 | 0.452491E+11 | 0.00 | 24.16 |
November | 0.00 | 0.00 | 0.00 | 0.120292E+09 | 0.00 | 0.00 | 0.710281E+11 | 0.00 | 23.26 |
December | 0.00 | 0.00 | 0.00 | 0.113880E+09 | 0.00 | 0.00 | 0.803442E+11 | 0.00 | 22.87 |
Annual Sum or Average | 0.00 | 0.229747E+11 | 0.00 | 0.133278E+10 | 0.00 | 0.00 | 0.517820E+12 | 0.00 | 23.15 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 36134397.76 | 0.00 | 0.00 | 0.282515E+10 | 0.00 | 21.64 |
Maximum of Months | 0.00 | 0.124804E+11 | 0.00 | 0.141270E+09 | 0.00 | 0.00 | 0.835424E+11 | 0.00 | 24.16 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.167628E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 40255356.56 | 0.00 | 0.00 | 1.11 |
February | 0.134745E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 51915508.32 | 0.00 | 0.00 | 1.12 |
March | 0.136212E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3805705.34 | 0.00 | 0.00 | 1.12 |
April | 0.806364E+10 | 17343210.26 | 0.00 | 898346.04 | 11652649.03 | 0.00 | 0.277837E+09 | 0.00 | 1.13 |
May | 0.356894E+10 | 0.170759E+09 | 0.00 | 6336017.28 | 14560657.85 | 0.00 | 0.134415E+10 | 0.00 | 1.13 |
June | 0.680472E+09 | 0.622627E+09 | 0.00 | 10922858.30 | 1243751.32 | 0.00 | 0.193292E+10 | 0.00 | 1.14 |
July | 0.122799E+09 | 0.212661E+10 | 0.00 | 4735468.26 | 0.283895E+09 | 0.00 | 0.564262E+09 | 0.00 | 1.11 |
August | 0.965617E+09 | 0.650932E+09 | 0.00 | 8898715.28 | 50922114.04 | 0.00 | 0.132002E+10 | 0.00 | 1.13 |
September | 0.258841E+10 | 0.393197E+09 | 0.00 | 7350978.75 | 46456082.39 | 0.00 | 0.135382E+10 | 0.00 | 1.17 |
October | 0.877956E+10 | 63144562.64 | 0.00 | 2138374.49 | 5381575.64 | 0.00 | 0.586955E+09 | 0.00 | 1.14 |
November | 0.143275E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.11 |
December | 0.157870E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239527E+09 | 0.00 | 0.00 | 1.12 |
Annual Sum or Average | 0.987424E+11 | 0.404461E+10 | 0.00 | 41280758.40 | 0.414112E+09 | 0.335504E+09 | 0.737996E+10 | 0.00 | 1.13 |
Minimum of Months | 0.122799E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.11 |
Maximum of Months | 0.167628E+11 | 0.212661E+10 | 0.00 | 10922858.30 | 0.283895E+09 | 0.239527E+09 | 0.193292E+10 | 0.00 | 1.17 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:22:03
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.190110E+12 | 0.591755E+10 | 0.161607E+12 | 0.685413E+12 | 0.134801E+12 |
February | 0.197747E+12 | 0.492068E+10 | 0.126000E+12 | 0.546019E+12 | 0.149763E+12 |
March | 0.317784E+12 | 0.485604E+10 | 0.118309E+12 | 0.517144E+12 | 0.201514E+12 |
April | 0.330547E+12 | 0.282280E+10 | 0.637420E+11 | 0.297169E+12 | 0.422670E+12 |
May | 0.363307E+12 | 0.154993E+10 | 0.316860E+11 | 0.170302E+12 | 0.658224E+12 |
June | 0.346004E+12 | 0.432733E+09 | 0.337406E+10 | 0.559300E+11 | 0.851095E+12 |
July | 0.334895E+12 | -0.143048E+10 | -0.370143E+11 | -0.136834E+12 | 0.107076E+13 |
August | 0.304569E+12 | -19640695.2 | 0.227691E+10 | 0.216813E+11 | 0.896977E+12 |
September | 0.260372E+12 | 0.743208E+09 | 0.189031E+11 | 0.107594E+12 | 0.750302E+12 |
October | 0.244102E+12 | 0.285385E+10 | 0.700917E+11 | 0.332316E+12 | 0.425889E+12 |
November | 0.187345E+12 | 0.494553E+10 | 0.128584E+12 | 0.571716E+12 | 0.182043E+12 |
December | 0.153711E+12 | 0.645066E+10 | 0.175239E+12 | 0.758929E+12 | 0.115198E+12 |
Annual Sum or Average | 0.323049E+13 | 0.340429E+11 | 0.862799E+12 | 0.392738E+13 | 0.585924E+13 |
Minimum of Months | 0.153711E+12 | -0.143048E+10 | -0.370143E+11 | -0.136834E+12 | 0.115198E+12 |
Maximum of Months | 0.363307E+12 | 0.645066E+10 | 0.175239E+12 | 0.758929E+12 | 0.107076E+13 |