Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930
Simulation Timestamp: 2024-07-03 12:21:35
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:35
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 10436.55 | 919.90 | 919.90 |
Net Site Energy | 10436.55 | 919.90 | 919.90 |
Total Source Energy | 20909.00 | 1842.97 | 1842.97 |
Net Source Energy | 20909.00 | 1842.97 | 1842.97 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1341.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 316.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 782.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 193.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1658.18 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 813.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 499.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 65.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 120.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 94.78 | 2699.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | 61.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 4606.71 | 5829.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 1341.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 316.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 782.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 193.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 872.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 14.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 8.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 21.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 789.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 2.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 499.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 65.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 120.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 94.78 | 2699.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5742.51 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.69 | |
Refrigeration | General | 7.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 20.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 34.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1341.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 316.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 782.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 193.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 1658.18 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 813.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 499.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 65.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 120.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 94.78 | 2699.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | Unassigned | 61.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 86.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 86.00 | 356.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 233.99 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 406.05 | 513.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 86.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 86.00 | 356.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 233.99 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 406.05 | 513.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 4606.710 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 4606.710 | 100.00 |
Total On-Site and Utility Electric Sources | 4606.710 | 100.00 |
Total Electricity End Uses | 4606.710 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 14.43 | 0.68 |
Air to Air Heat Recovery for Heating | 2118.81 | 99.32 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 2133.24 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9857.19 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9857.19 | 100.00 |
Total Water End Uses | 9857.19 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 18.83 |
Time Setpoint Not Met During Occupied Cooling | 30.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 7073.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER1 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| FLR_3_DOAS COOLING COIL | VAV WITH REHEAT COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH LAUNDRY G WATER HEATER | SWH BOOSTER E WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |CoilReportMonthly
| FLR_3_DOAS HEATING COIL | VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | FLR_3_DOAS COOLING COIL | VAV WITH REHEAT COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |FanReportMonthly
| FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL_FANCOILFAN | ROOM_2_FLR_3 FAN COIL_FANCOILFAN | ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | ROOM_5_FLR_3 FAN COIL_FANCOILFAN | ROOM_6_FLR_3 FAN COIL_FANCOILFAN | ROOM_1_FLR_6 FAN COIL_FANCOILFAN | ROOM_2_FLR_6 FAN COIL_FANCOILFAN | ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| FLR_3_DOAS | VAV WITH REHEAT |AirLoopSystemComponentLoadsMonthly
| FLR_3_DOAS | VAV WITH REHEAT |AirLoopSystemComponentEnergyUseMonthly
| FLR_3_DOAS | VAV WITH REHEAT |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:35
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21 |
RunPeriod | RUNPERIOD 1 |
Weather File | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Latitude [deg] | 47.47 |
Longitude [deg] | -122.3 |
Elevation [m] | 122.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 8.8143 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.26 | 23.26 | 11.3140 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 11.3140 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 4.6285 | 61.93 | 5.3800 |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 5.7199 | 46.45 | 2.6900 |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 4.6285 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.50 | 65.50 | 10.0104 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.08 | 85.08 | 10.7639 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 8.2882 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 8.2882 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 7.1042 | 18.58 | 0.0000 |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.74 | 6.74 | 8.2882 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 10.0104 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 10.0104 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.37 | 26.37 | 11.4097 | 4.65 | 2934.4875 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.20 | 28.20 | 7.1042 | 18.58 | 0.0000 |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 8.5566 | 7.07 | 41.0709 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 8.5566 | 7.07 | 41.0709 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 1978.83 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 8.8143 | 18.58 | 5.3800 | |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 1.00 | RETAIL_1_FLR_1 | GENERAL | RETAIL_1_FLR_1 | 11.3140 | 6.19 | 10.7600 | |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 1.00 | RETAIL_2_FLR_1 | GENERAL | RETAIL_2_FLR_1 | 11.3140 | 6.19 | 10.7600 | |
MECH_FLR_1 | 164.24 | Yes | Yes | 1.00 | MECH_FLR_1 | GENERAL | MECH_FLR_1 | 4.6285 | 61.93 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 1.00 | STORAGE_FLR_1 | GENERAL | STORAGE_FLR_1 | 5.7199 | 46.45 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 1.00 | LAUNDRY_FLR_1 | GENERAL | LAUNDRY_FLR_1 | 4.6285 | 9.29 | 597.5300 | |
CAFE_FLR_1 | 188.86 | Yes | Yes | 1.00 | CAFE_FLR_1 | GENERAL | CAFE_FLR_1 | 10.0104 | 1.33 | 5.3800 | |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 1.00 | LOBBY_FLR_1 | GENERAL | LOBBY_FLR_1 | 10.7639 | 3.10 | 8.0700 | |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_1_FLR_3 | GENERAL | ROOM_1_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_2_FLR_3 | GENERAL | ROOM_2_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 76.00 | ROOM_3_MULT19_FLR_3 | GENERAL | ROOM_3_MULT19_FLR_3 | 8.2882 | 16.35 | 10.5200 | |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 76.00 | ROOM_4_MULT19_FLR_3 | GENERAL | ROOM_4_MULT19_FLR_3 | 8.2882 | 16.35 | 10.5200 | |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_5_FLR_3 | GENERAL | ROOM_5_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_6_FLR_3 | GENERAL | ROOM_6_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 4.00 | CORRIDOR_FLR_3 | GENERAL | CORRIDOR_FLR_3 | 7.1042 | 18.58 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_1_FLR_6 | GENERAL | ROOM_1_FLR_6 | 8.2882 | 26.01 | 6.7500 | |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_2_FLR_6 | GENERAL | ROOM_2_FLR_6 | 8.2882 | 26.01 | 6.7500 | |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 9.00 | ROOM_3_MULT9_FLR_6 | GENERAL | ROOM_3_MULT9_FLR_6 | 8.2882 | 16.35 | 10.5200 | |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1.00 | BANQUET_FLR_6 | GENERAL | BANQUET_FLR_6 | 10.0104 | 1.33 | 67.8200 | |
DINING_FLR_6 | 331.66 | Yes | Yes | 1.00 | DINING_FLR_6 | GENERAL | DINING_FLR_6 | 10.0104 | 1.33 | 67.8200 | |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 1.00 | KITCHEN_FLR_6 | GENERAL | KITCHEN_FLR_6 | 11.4097 | 4.65 | 2934.4875 | |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1.00 | CORRIDOR_FLR_6 | GENERAL | CORRIDOR_FLR_6 | 7.1042 | 18.58 | 0.0000 | |
Total | 11345.29 | 8.5566 | 3.54 | 41.0709 | |||||||
Conditioned Total | 11345.29 | 8.5566 | 3.54 | 41.0709 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 11345.29 | 11345.29 | 0.00 | 0.00 | 4.6520 | 8.82 | 37.1989 |
Total | 11345.29 | 11345.29 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:35
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 10-AUG-18:10 | 22-MAR-17:40 | - | - | - | - | - | - | - | - | - | - | 08-MAY-20:10 |
Heating | 0.00 | 192332.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 130336.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 53578.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 77573.37 | 104248.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 28157.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 25257.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 3389.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 4751.03 | 243401.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 2416.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 335399.91 | 539983.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 192332.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 130336.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 53578.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 47590.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 29272.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1038.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 26968.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 150.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 25257.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 3389.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 4751.03 | 243401.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 228.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 1093.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1093.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:35
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1453.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1002.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2479.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 612.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5251.45 | 1939.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2577.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1580.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 206.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 382.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 300.18 | 2926.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 196.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 14589.45 | 6319.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 88.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 218.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 54.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 462.88 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 227.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 139.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 18.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 33.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 26.46 | 257.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1285.95 | 557.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 88.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 218.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 54.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 462.88 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 227.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 139.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 18.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 33.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 26.46 | 257.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1285.95 | 557.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:35
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
BASEMENT VAV BOX COMPONENT | 2.55 | 0.591906 | 0.513000 | 1.31 | 1.00 | 0.500000 | 0.000644 | 0.000060 | 1.31 | 16.70 | 0.008000 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.442493 | 0.115501 | 0.513000 | 0.226999 | 0.513000 | 0.500000 | 0.003299 | 0.000029 | 0.226999 | 16.70 | 0.008000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.232046 | 0.255052 | 0.513000 | 0.119040 | 0.680138 | 0.500000 | 0.001494 | 0.000012 | 0.119040 | 16.70 | 0.008000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.174022 | 0.719179 | 0.513000 | 0.089274 | 1.00 | 0.500000 | 0.000530 | 0.000015 | 0.089274 | 16.70 | 0.008000 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.103423 | 0.698170 | 0.513000 | 0.053056 | 1.00 | 0.500000 | 0.000546 | 0.000010 | 0.053056 | 16.70 | 0.008000 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 3.29 | 0.018088 | 0.513000 | 1.69 | 0.513000 | 0.500000 | 0.021063 | 0.000091 | 1.69 | 16.70 | 0.008000 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.77 | 0.081450 | 0.513000 | 0.906411 | 0.513000 | 0.500000 | 0.004678 | 0.000088 | 0.906411 | 16.70 | 0.008000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 5.14 | 0.193875 | 0.513000 | 2.64 | 0.517000 | 0.500000 | 0.001965 | 0.000229 | 2.64 | 16.70 | 0.008000 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.61 | 0.738384 | 0.513000 | 0.824615 | 1.00 | 0.500000 | 0.000516 | 0.000104 | 0.824615 | 16.70 | 0.008000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.12 | 0.119360 | 0.513000 | 1.09 | 0.513000 | 0.500000 | 0.003192 | 0.000091 | 1.09 | 16.70 | 0.008000 |
DINING_FLR_6 VAV BOX COMPONENT | 2.22 | 0.113953 | 0.513000 | 1.14 | 0.513000 | 0.500000 | 0.003343 | 0.000095 | 1.14 | 16.70 | 0.008000 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.27 | 0.062335 | 0.513000 | 1.17 | 0.513000 | 0.500000 | 0.010993 | 0.000062 | 1.17 | 16.70 | 0.008000 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 0.804123 | 0.390536 | 0.513000 | 0.412515 | 1.00 | 0.500000 | 0.000976 | 0.000063 | 0.412515 | 16.70 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
BASEMENT VAV BOX REHEAT COIL | 6801.76 | 0.000060 | 141.84 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 3305.38 | 0.000029 | 76.09 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1331.70 | 0.000012 | 29.54 |
MECH_FLR_1 VAV BOX REHEAT COIL | 1731.54 | 0.000015 | 42.17 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 1153.85 | 0.000010 | 28.92 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 10449.05 | 0.000091 | 220.07 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 10115.52 | 0.000088 | 224.32 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 26217.27 | 0.000229 | 573.93 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | 4651.52 | 0.000041 | 132.91 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | 4654.79 | 0.000041 | 133.00 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 26893.42 | 0.000235 | 768.43 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 26967.92 | 0.000236 | 770.56 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | 4658.62 | 0.000041 | 133.11 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | 4661.89 | 0.000041 | 133.21 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 11871.41 | 0.000104 | 272.78 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | 1427.71 | 0.000012 | 40.79 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | 1429.36 | 0.000013 | 40.84 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 6868.36 | 0.000060 | 196.25 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 10447.66 | 0.000091 | 227.94 |
DINING_FLR_6 VAV BOX REHEAT COIL | 10820.47 | 0.000095 | 235.80 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 7057.59 | 0.000062 | 148.43 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 7206.92 | 0.000063 | 171.55 |
FLR_3_DOAS HEATING COIL | 15340.96 | 0.000134 | 261.90 |
VAV WITH REHEAT HEATING COIL | 168952.24 | 0.001478 | 2884.39 |
Design Size Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 0.061735 |
ROOM_2_FLR_3 DIRECT AIR | 0.061728 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 0.837072 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 0.837300 |
ROOM_5_FLR_3 DIRECT AIR | 0.061735 |
ROOM_6_FLR_3 DIRECT AIR | 0.061728 |
ROOM_1_FLR_6 DIRECT AIR | 0.015434 |
ROOM_2_FLR_6 DIRECT AIR | 0.015432 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 0.099154 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Hot Water Flow [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 1.18 | 0.000041 | 0.000369 |
ROOM_2_FLR_3 FAN COIL | 1.07 | 0.000041 | 0.000335 |
ROOM_3_MULT19_FLR_3 FAN COIL | 8.31 | 0.000235 | 0.002562 |
ROOM_4_MULT19_FLR_3 FAN COIL | 5.57 | 0.000236 | 0.001838 |
ROOM_5_FLR_3 FAN COIL | 1.06 | 0.000041 | 0.000334 |
ROOM_6_FLR_3 FAN COIL | 0.970524 | 0.000041 | 0.000306 |
ROOM_1_FLR_6 FAN COIL | 0.306756 | 0.000012 | 0.000096 |
ROOM_2_FLR_6 FAN COIL | 0.275957 | 0.000013 | 0.000087 |
ROOM_3_MULT9_FLR_6 FAN COIL | 1.68 | 0.000060 | 0.000532 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COIL_FANCOILFAN | 1.18 |
ROOM_2_FLR_3 FAN COIL_FANCOILFAN | 1.07 |
ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | 8.31 |
ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | 5.57 |
ROOM_5_FLR_3 FAN COIL_FANCOILFAN | 1.06 |
ROOM_6_FLR_3 FAN COIL_FANCOILFAN | 0.970524 |
ROOM_1_FLR_6 FAN COIL_FANCOILFAN | 0.306756 |
ROOM_2_FLR_6 FAN COIL_FANCOILFAN | 0.275957 |
ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN | 1.68 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Coil Load [W] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008566 | 12.80 | 0.008500 | 0.000369 | 1.18 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008572 | 12.80 | 0.008500 | 0.000335 | 1.07 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008502 | 12.80 | 0.008500 | 0.002562 | 8.31 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008757 | 12.80 | 0.008500 | 0.001838 | 5.57 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008573 | 12.80 | 0.008500 | 0.000334 | 1.06 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008580 | 12.80 | 0.008500 | 0.000306 | 0.970524 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008563 | 12.80 | 0.008500 | 0.000096 | 0.306756 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008570 | 12.80 | 0.008500 | 0.000087 | 0.275957 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008602 | 12.80 | 0.008500 | 0.000532 | 1.68 | |
FLR_3_DOAS COOLING COIL | 29.40 | 6.70 | 0.008822 | 11.92 | 0.008500 | 0.001300 | 2.05 | 45447.84 |
VAV WITH REHEAT COOLING COIL | 26.78 | 6.70 | 0.009207 | 10.95 | 0.008500 | 0.013775 | 22.59 | 481649.27 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
VAV WITH REHEAT | 11.65 | 11.65 | 22.71 | 11.65 | 22.59 | 22.59 | 0.300000 | 0.515772 | 22.59 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
VAV WITH REHEAT_OA_CONTROLLER | 22.59 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
FLR_3_DOAS OA HEAT RECOVERY | 2.05 |
VAV WITH REHEAT OA HEAT RECOVERY | 11.66 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS FAN | 2.05 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.001300 | 0.000366 |
FLR_3_DOAS_HEATC_CONTROLLER | 0.000134 | |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.013775 | 0.000035 |
VAV WITH REHEAT_HEATC_CONTROLLER | 0.001478 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT FAN | 22.59 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.021534 | 3515.82 | |
HEATSYS1 PUMP | 0.003281 | 988.04 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.003281 | 0.393697 |
COOLSYS1 | 0.021534 | 2.58 |
SWHSYS1 | 0.000375 | 0.045004 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 375016.92 | 375016.92 | 0.003281 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.021534 | 2434.12 |
SWHSYS1 PUMP | 0.000375 | 47.91 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.021534 | 752935.70 | 753560.40 | 85.91 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000375 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:35
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:35
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:35
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 11.40 | 8.10 | 5.40 | 4.50 | 5.80 | 8.30 | 10.90 | 13.00 | 15.60 | 17.70 | 18.80 | 15.10 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 | 47.47 | -122.32 | -8.00 | 122.00 | 99868 | 1.1870 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 11.22 | 14.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.58 | 23.26 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.72 | 65.50 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.80 | 85.08 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.70 | 6.74 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.96 | 26.37 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.27 | 28.20 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 8.814 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 14.194 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 11.314 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 22.074 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 11.314 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 22.074 | No |
4 | MECH_FLR_1 | 164.24 | 2.7 | 61.932 | 1.615E-002 | 4.628 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 10.008 | No |
5 | STORAGE_FLR_1 | 94.76 | 2.0 | 46.451 | 2.153E-002 | 5.720 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 8.410 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 4.628 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 602.158 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 10.010 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 15.390 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 10.764 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.834 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 8.288 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 18.808 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 8.288 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 18.808 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 21.0 | 18.581 | 5.382E-002 | 7.104 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.104 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 8.288 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 18.808 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 10.010 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 77.830 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 10.010 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 77.830 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 11.410 | 515.227 | 2419.260 | 0.000 | 0.000 | 0.000 | 2945.897 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 22.2 | 18.581 | 5.382E-002 | 7.104 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.104 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | STORAGE_FLR_1 PEOPLE | BLDG_OCC_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.0 | 2.153E-002 | 46.451 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | CORRIDOR_FLR_3 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 21.0 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 21 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
21 | CORRIDOR_FLR_6 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 22.2 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
22 | MECH_FLR_1 PEOPLE | BLDG_OCC_SCH | MECH_FLR_1 | 164.24 | 2.7 | 2.7 | 1.615E-002 | 61.932 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 3 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_BASEMENT | BASEMENT | 1978.83 | 106.5 | 17441.963 | 8.814 | 163.776 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 17441.963 |
2 | RETAIL_1_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_1_FLR_1 | 67.07 | 10.8 | 758.849 | 11.314 | 70.076 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 758.849 |
3 | RETAIL_2_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_2_FLR_1 | 77.67 | 12.5 | 878.750 | 11.314 | 70.076 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 878.750 |
4 | MECH_FLR_1_LIGHTS | LTG_SCH_MECHANIC | MECH_FLR_1 | 164.24 | 2.7 | 760.196 | 4.628 | 286.650 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 760.196 |
5 | STORAGE_FLR_1_LIGHTS | LTG_SCH_STORAGE | STORAGE_FLR_1 | 94.76 | 2.0 | 542.017 | 5.720 | 265.695 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 542.017 |
6 | LAUNDRY_FLR_1_LIGHTS | LTG_SCH_LAUNDRY | LAUNDRY_FLR_1 | 78.04 | 8.4 | 361.204 | 4.628 | 43.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 361.204 |
7 | CAFE_FLR_1_LIGHTS | LTG_SCH_DINING | CAFE_FLR_1 | 188.86 | 142.3 | 1890.589 | 10.010 | 13.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1890.589 |
8 | LOBBY_FLR_1_LIGHTS | LTG_SCH_LOBBY | LOBBY_FLR_1 | 1308.19 | 422.4 | 14081.185 | 10.764 | 33.333 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14081.185 |
9 | ROOM_1_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_3 | 39.02 | 1.5 | 323.422 | 8.288 | 215.615 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.422 |
10 | ROOM_2_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_3 | 39.02 | 1.5 | 323.384 | 8.288 | 215.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.384 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 203.259 | 8.288 | 135.506 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 203.259 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 203.314 | 8.288 | 135.543 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 203.314 |
13 | ROOM_5_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_5_FLR_3 | 39.02 | 1.5 | 323.422 | 8.288 | 215.615 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.422 |
14 | ROOM_6_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_6_FLR_3 | 39.02 | 1.5 | 323.384 | 8.288 | 215.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.384 |
15 | CORRIDOR_FLR_3_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2766.397 | 7.104 | 132.003 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2766.397 |
16 | ROOM_1_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_6 | 39.02 | 1.5 | 323.422 | 8.288 | 215.615 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.422 |
17 | ROOM_2_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_6 | 39.02 | 1.5 | 323.384 | 8.288 | 215.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.384 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 203.314 | 8.288 | 135.543 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 203.314 |
19 | BANQUET_FLR_6_LIGHTS | LTG_SCH_DINING | BANQUET_FLR_6 | 331.66 | 249.9 | 3320.034 | 10.010 | 13.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3320.034 |
20 | DINING_FLR_6_LIGHTS | LTG_SCH_DINING | DINING_FLR_6 | 331.66 | 249.9 | 3320.034 | 10.010 | 13.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3320.034 |
21 | KITCHEN_FLR_6_LIGHTS | LTG_SCH_KITCHEN | KITCHEN_FLR_6 | 103.30 | 22.2 | 1178.676 | 11.410 | 53.003 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1178.676 |
22 | CORRIDOR_FLR_6_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_6 | 412.12 | 22.2 | 2927.804 | 7.104 | 132.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2927.804 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 2.7 | 883.628 | 5.380 | 333.193 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 254.902 | 2.690 | 124.952 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 457.500 | 4.429 | 20.573 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 457.500 | 457.500 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 285.000 | 2.759 | 12.816 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 285.000 | 285.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 2.390 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
6 | RES_ROOF | 19 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
7 | NONRES_EXT_WALL_GRD | 21 | 3 | 9 | 0.167 | 0.8203 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | NONRES_EXT_WALL_MID | 22 | 3 | 9 | 0.167 | 1.021 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | NONRES_EXT_WALL_TOP | 23 | 3 | 9 | 0.167 | 1.034 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | RES_EXT_WALL_MID | 25 | 3 | 9 | 0.167 | 0.9169 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | RES_EXT_WALL_TOP | 26 | 3 | 9 | 0.167 | 0.9299 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | NONRES_FLOOR | 30 | 3 | 7 | 0.167 | 0.2277 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
13 | NONRES_FLOOR_CEILING | 33 | 3 | 7 | 0.167 | 0.2277 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
14 | BASEMENT_FLOOR | 36 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
15 | BASEMENT_WALL_NORTH_CFACTOR | 39 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | BASEMENT_WALL_EAST_CFACTOR | 40 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | BASEMENT_WALL_SOUTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
18 | BASEMENT_WALL_WEST_CFACTOR | 42 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4184 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
10 | RES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
11 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
12 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.052 |
14 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8120 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7993 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | RES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9233 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
25 | RES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9080 |
26 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
27 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.131 |
28 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
29 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
30 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
31 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
32 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.131 |
33 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
34 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
35 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
39 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
40 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
41 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
42 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 2.3900722 | 2.3900722 | 2.3900722 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
21 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
22 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
23 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
24 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
25 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
26 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
27 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
28 | 9 | -0.15703352E-14 | 0.29012323E-16 | -0.15483104E-09 | 0.40370831E-16 |
29 | 8 | 0.22592825E-07 | 0.11106548E-12 | 0.38529762E-03 | -0.25688817E-09 |
30 | 7 | -0.12465369E-01 | 0.57225352E-08 | -0.23408026E-01 | 0.14173579E-03 |
31 | 6 | 0.41143163 | 0.19878644E-05 | 0.47726710 | -0.48194459E-02 |
32 | 5 | -5.2499075 | 0.74130146E-04 | -4.4810026 | 0.63919688E-01 |
33 | 4 | 33.265337 | 0.60571720E-03 | 21.595652 | -0.42560793 |
34 | 3 | -111.78466 | 0.13187857E-02 | -55.931065 | 1.5232626 |
35 | 2 | 197.68466 | 0.74115454E-03 | 78.156489 | -2.9095067 |
36 | 1 | -171.36898 | 0.79055603E-04 | -55.336681 | 2.7491709 |
37 | 0 | 57.057407 | 0.44959794E-06 | 15.545184 | |
38 | 9 | 0.14302076E-15 | 0.35792568E-16 | -0.14541430E-09 | -0.27421543E-17 |
39 | 8 | 0.21269444E-07 | 0.13686051E-12 | 0.37140784E-03 | -0.24184090E-09 |
40 | 7 | -0.12050952E-01 | 0.71525680E-08 | -0.22811354E-01 | 0.13702371E-03 |
41 | 6 | 0.40017121 | 0.24988627E-05 | 0.46767819 | -0.46867126E-02 |
42 | 5 | -5.1400200 | 0.93645327E-04 | -4.4073602 | 0.62557131E-01 |
43 | 4 | 32.779281 | 0.76858103E-03 | 21.307814 | -0.41915444 |
44 | 3 | -110.75053 | 0.16800125E-02 | -55.362013 | 1.5083221 |
45 | 2 | 196.65975 | 0.94749847E-03 | 77.634567 | -2.8932310 |
46 | 1 | -170.99041 | 0.10139533E-03 | -55.184883 | 2.7425359 |
47 | 0 | 57.057407 | 0.57877233E-06 | 15.570231 | |
48 | 9 | 0.33566835E-16 | 0.35384250E-16 | -0.14478218E-09 | -0.87565041E-18 |
49 | 8 | 0.21180494E-07 | 0.13854999E-12 | 0.37046393E-03 | -0.24082951E-09 |
50 | 7 | -0.12022754E-01 | 0.72481687E-08 | -0.22770744E-01 | 0.13670309E-03 |
51 | 6 | 0.39940498 | 0.25332696E-05 | 0.46702484 | -0.46776806E-02 |
52 | 5 | -5.1325420 | 0.94967185E-04 | -4.4023386 | 0.62464408E-01 |
53 | 4 | 32.746200 | 0.77967008E-03 | 21.288178 | -0.41871522 |
54 | 3 | -110.68014 | 0.17047184E-02 | -55.323188 | 1.5073051 |
55 | 2 | 196.58997 | 0.96166638E-03 | 77.598974 | -2.8921229 |
56 | 1 | -170.96463 | 0.10293464E-03 | -55.174560 | 2.7420841 |
57 | 0 | 57.057407 | 0.58770932E-06 | 15.571958 | |
58 | 9 | -0.29206544E-14 | 0.31488305E-16 | -0.15031727E-09 | 0.48064473E-16 |
59 | 8 | 0.21958778E-07 | 0.12356532E-12 | 0.37867817E-03 | -0.24967887E-09 |
60 | 7 | -0.12267989E-01 | 0.64094198E-08 | -0.23123879E-01 | 0.13949151E-03 |
61 | 6 | 0.40606866 | 0.22324768E-05 | 0.47270315 | -0.47562292E-02 |
62 | 5 | -5.1975737 | 0.83445227E-04 | -4.4459647 | 0.63270770E-01 |
63 | 4 | 33.033866 | 0.68326082E-03 | 21.458733 | -0.42253461 |
64 | 3 | -111.29222 | 0.14903991E-02 | -55.660391 | 1.5161481 |
65 | 2 | 197.19665 | 0.83899866E-03 | 77.908180 | -2.9017570 |
66 | 1 | -171.18874 | 0.89630080E-04 | -55.264364 | 2.7460119 |
67 | 0 | 57.057407 | 0.51068186E-06 | 15.557036 | |
68 | 9 | -0.29497736E-14 | 0.32939851E-16 | -0.14970570E-09 | 0.45584202E-16 |
69 | 8 | 0.21872815E-07 | 0.12523736E-12 | 0.37777579E-03 | -0.24870145E-09 |
70 | 7 | -0.12241065E-01 | 0.65023057E-08 | -0.23085114E-01 | 0.13918537E-03 |
71 | 6 | 0.40533708 | 0.22656711E-05 | 0.47208016 | -0.47476058E-02 |
72 | 5 | -5.1904345 | 0.84713026E-04 | -4.4411801 | 0.63182247E-01 |
73 | 4 | 33.002288 | 0.69384191E-03 | 21.440032 | -0.42211534 |
74 | 3 | -111.22504 | 0.15138688E-02 | -55.623419 | 1.5151774 |
75 | 2 | 197.13007 | 0.85240592E-03 | 77.874271 | -2.9006996 |
76 | 1 | -171.16415 | 0.91081681E-04 | -55.254501 | 2.7455809 |
77 | 0 | 57.057407 | 0.51907125E-06 | 15.558664 | |
78 | 7 | -0.14139450E-14 | -0.18802902E-16 | -0.22311785E-13 | 0.54375338E-15 |
79 | 6 | 0.16999971E-10 | 0.27590984E-11 | 0.52267399E-09 | -0.18616555E-10 |
80 | 5 | -0.63950587E-07 | 0.13451749E-07 | -0.21905428E-05 | 0.17144787E-06 |
81 | 4 | 0.72477507E-04 | 0.50724086E-05 | 0.17668371E-02 | -0.28223350E-03 |
82 | 3 | -0.10573811E-01 | 0.17927531E-03 | -0.21549182 | 0.43318087E-01 |
83 | 2 | 0.15010112 | 0.77388015E-03 | 2.8998331 | -0.61891034 |
84 | 1 | -0.37982851 | 0.49528818E-03 | -7.1368477 | 1.5694772 |
85 | 0 | 0.24168561 | 0.34021171E-05 | 4.4521969 | |
86 | 7 | -0.22311785E-13 | -0.18802902E-16 | -0.14139450E-14 | 0.54375338E-15 |
87 | 6 | 0.52267399E-09 | 0.27590984E-11 | 0.16999971E-10 | -0.18616555E-10 |
88 | 5 | -0.21905428E-05 | 0.13451749E-07 | -0.63950587E-07 | 0.17144787E-06 |
89 | 4 | 0.17668371E-02 | 0.50724086E-05 | 0.72477507E-04 | -0.28223350E-03 |
90 | 3 | -0.21549182 | 0.17927531E-03 | -0.10573811E-01 | 0.43318087E-01 |
91 | 2 | 2.8998331 | 0.77388015E-03 | 0.15010112 | -0.61891034 |
92 | 1 | -7.1368477 | 0.49528818E-03 | -0.37982851 | 1.5694772 |
93 | 0 | 4.4521969 | 0.34021171E-05 | 0.24168561 | |
94 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
95 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
96 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
97 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
98 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
99 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
100 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
101 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
102 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
103 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
104 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
105 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
106 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
107 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
108 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
109 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
110 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
111 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
112 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
113 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
114 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
115 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
116 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
117 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
118 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
119 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
120 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
121 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
122 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
123 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
124 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
125 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
126 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
127 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
128 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
129 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
130 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
131 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
132 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
133 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.38_SHGC_0.36 | 37 | 1 | VerySmooth | 2.159 | 2.159 | 1.000 | 0.361 | ||
2 | RESWINDOW_U_0.38_SHGC_0.36 | 38 | 1 | VerySmooth | 2.159 | 2.159 | 1.000 | 0.361 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 3.45900E-002 | 0.27318 | 0.51781 | 0.51781 | 0.39600 | 0.13802 | 0.18068 | 0.00000 | 0.84000 | 0.84000 | 0.11893 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 3.45900E-002 | 0.27318 | 0.51781 | 0.51781 | 0.39600 | 0.13802 | 0.18068 | 0.00000 | 0.84000 | 0.84000 | 0.11893 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | CAFE_FLR_1 | 1 | 0 |
2 | LOBBY_FLR_1 | 1 | 0 |
3 | BANQUET_FLR_6 | 1 | 0 |
4 | DINING_FLR_6 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | CAFE_FLR_1 | 0 | |
2 | LOBBY_FLR_1 | 0 | |
3 | BANQUET_FLR_6 | 0 | |
4 | DINING_FLR_6 | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH LAUNDRY G WATER HEATER | 1.1356 | 163316.0 | 11.511 | 0.4388 |
2 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.219 | 1.1187 |
3 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 2.2712 | 175842.6 | 5.775 | 0.3748 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 1.764E-002 | 2.631E-004 | 1.298E-004 | 0.239 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.811E-003 | 8.769E-005 | 2.388E-004 | 7.967E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 2.7 | 1.610E-002 | 9.800E-005 | 2.563E-004 | 8.904E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 9.287E-003 | 9.800E-005 | 2.127E-004 | 8.904E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 2.198E-002 | 2.816E-004 | 2.506E-004 | 0.256 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 3.900E-002 | 2.065E-004 | 1.137E-004 | 0.188 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 0.111 | 8.519E-005 | 1.629E-004 | 7.740E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 2.563E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 2.563E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 2.857E-003 | 1.165E-004 | 2.563E-004 | 0.138 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 2.858E-003 | 1.165E-004 | 2.563E-004 | 0.138 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 2.563E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 2.563E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 1.238E-002 | 3.180E-005 | 2.563E-004 | 3.755E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 1.297E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 1.297E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 5.239E-003 | 2.136E-004 | 1.165E-004 | 0.252 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 2.500E-002 | 7.539E-005 | 5.825E-005 | 8.904E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 2.500E-002 | 7.539E-005 | 5.825E-005 | 8.904E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 2.238E-002 | 2.167E-004 | 1.174E-004 | 0.256 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 2.191E-002 | 5.316E-005 | 4.403E-005 | 6.278E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1490 |
2 | Clear Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 8.8401E-002 |
3 | Clear Turbid Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1700 |
4 | Clear Turbid Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 0.1033 |
5 | Intermediate Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 9.9040E-002 |
6 | Intermediate Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 4.0567E-002 |
7 | Overcast Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 4.1657E-002 |
8 | Overcast Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 1.3839E-002 |
9 | Clear Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1708 |
10 | Clear Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 0.1058 |
11 | Clear Turbid Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1958 |
12 | Clear Turbid Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 0.1233 |
13 | Intermediate Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1096 |
14 | Intermediate Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 5.0553E-002 |
15 | Overcast Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 4.6776E-002 |
16 | Overcast Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 1.8924E-002 |
17 | Clear Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 3.9132E-002 |
18 | Clear Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 2.2626E-002 |
19 | Clear Turbid Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 3.0128E-002 |
20 | Clear Turbid Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.7133E-002 |
21 | Intermediate Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.8567E-002 |
22 | Intermediate Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.1374E-002 |
23 | Overcast Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 4.1005E-002 |
24 | Overcast Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.4540E-002 |
25 | Clear Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 3.9132E-002 |
26 | Clear Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 2.2626E-002 |
27 | Clear Turbid Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 3.0128E-002 |
28 | Clear Turbid Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.7133E-002 |
29 | Intermediate Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.8567E-002 |
30 | Intermediate Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.1374E-002 |
31 | Overcast Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 4.1005E-002 |
32 | Overcast Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.4540E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 34561.46706 | 34561.46706 | 2.54748 | 2.54748 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 25.86400 | 8.81585E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 0.85446 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
3 | RETAIL_1_FLR_1 | Cooling | 6002.75136 | 6002.75136 | 0.44249 | 0.44249 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 29.05333 | 8.82094E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 2124.55339 | 2124.55339 | 9.23803E-002 | 9.23803E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 3147.79599 | 3147.79599 | 0.23205 | 0.23205 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:40:00 | 28.98400 | 8.82083E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 712.48325 | 712.48325 | 3.09808E-002 | 9.17347E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 2361.19338 | 2361.19338 | 0.17402 | 0.17402 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:40:00 | 28.98400 | 8.82083E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 1267.24394 | 1267.24394 | 5.51033E-002 | 5.51033E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 1403.26081 | 1403.26081 | 0.10342 | 0.10342 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 29.40000 | 8.82150E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 877.88084 | 877.88084 | 3.81727E-002 | 5.77652E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 44601.96818 | 44601.96818 | 3.28752 | 3.28752 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 29.40000 | 8.82150E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 1678.32187 | 1678.32187 | 7.29771E-002 | 7.29771E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 23949.81398 | 23949.81398 | 1.76688 | 1.76688 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 29.05333 | 8.82094E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 5400.13062 | 5400.13062 | 0.23481 | 0.67639 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 69729.68513 | 69729.68513 | 5.14165 | 5.14165 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 29.22667 | 8.82122E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 12496.35959 | 12496.35959 | 0.54338 | 1.89399 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 11843.53612 | 11843.53612 | 1.17633 | 1.17633 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 28.36000 | 8.81983E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 4651.57260 | 4651.57260 | 0.20345 | 0.20345 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 10733.21187 | 10733.21187 | 1.06605 | 1.06605 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | 28.08267 | 8.81938E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 4654.84776 | 4654.84776 | 0.20359 | 0.20359 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 83692.74210 | 83692.74210 | 8.31217 | 8.31217 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 29.14000 | 8.82108E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 26893.56477 | 26893.56477 | 1.17628 | 1.17628 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 56028.34518 | 56028.34518 | 5.56504 | 5.56504 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 29.40000 | 8.82150E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 26968.06721 | 26968.06721 | 1.17953 | 1.17953 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 10693.38554 | 10693.38554 | 1.06209 | 1.06209 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 25.44800 | 8.81519E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 4658.67236 | 4658.67236 | 0.20376 | 0.20376 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 9771.45290 | 9771.45290 | 0.97052 | 0.97052 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 23.68000 | 8.81240E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 4661.94656 | 4661.94656 | 0.20390 | 0.20390 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 21808.50071 | 21808.50071 | 1.60744 | 1.60744 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 29.40000 | 8.82150E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 7581.23420 | 7581.23420 | 0.32966 | 0.47476 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 3088.49743 | 3088.49743 | 0.30676 | 0.30676 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 28.36000 | 8.81983E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 1427.72104 | 1427.72104 | 6.24451E-002 | 6.24451E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 2778.40158 | 2778.40158 | 0.27596 | 0.27596 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 27.94400 | 8.81916E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 1429.37229 | 1429.37229 | 6.25173E-002 | 6.25173E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 16913.12864 | 16913.12864 | 1.67989 | 1.67989 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 29.22667 | 8.82122E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 6868.42325 | 6868.42325 | 0.30041 | 0.30041 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 28690.49121 | 28690.49121 | 2.11732 | 2.11732 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 29.40000 | 8.82150E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 4796.25938 | 4796.25938 | 0.20855 | 1.18780 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 30052.14742 | 30052.14742 | 2.21778 | 2.21778 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 29.40000 | 8.82150E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
40 | DINING_FLR_6 | Heating | 4901.05272 | 4901.05272 | 0.21311 | 1.18780 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:10:00 | -4.20000 | 2.69032E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 30735.29545 | 30735.29545 | 2.27133 | 2.27133 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 28.46400 | 8.82000E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 1026.39523 | 1026.39523 | 4.46249E-002 | 0.36735 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | -4.20000 | 2.69032E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
43 | CORRIDOR_FLR_6 | Cooling | 10909.82741 | 10909.82741 | 0.80412 | 0.80412 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 29.40000 | 8.82150E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 5060.53477 | 5060.53477 | 0.22005 | 0.22005 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:10:00 | -4.20000 | 2.69032E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | FLR_3_DOAS | Cooling | Sensible | 40614.20 | 19.16137 | 2.05125 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
2 | FLR_3_DOAS | Heating | Sensible | 51134.75 | 3.59588 | 2.05125 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
3 | VAV WITH REHEAT | Cooling | Sensible | 376643.77 | 22.59145 | 22.59145 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | VAV WITH REHEAT | Heating | Sensible | 180294.09 | 7.23241 | 7.23241 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:30:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.54748 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.59191 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.51300 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.30686 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.43684E-004 |
8 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.95048E-005 |
9 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.30686 |
10 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6801.76349 |
13 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.95048E-005 |
14 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 141.83905 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.44249 |
16 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11550 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.51300 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.22700 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51300 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.29868E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.89169E-005 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.22700 |
24 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3305.37991 |
27 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.89169E-005 |
28 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 76.09021 |
29 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.23205 |
30 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25505 |
31 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.51300 |
32 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.11904 |
33 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.68014 |
34 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.49382E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.16503E-005 |
37 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.11904 |
38 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1331.69539 |
41 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.16503E-005 |
42 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 29.53949 |
43 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.17402 |
44 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.71918 |
45 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.51300 |
46 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.92735E-002 |
47 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.29771E-004 |
50 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.51483E-005 |
51 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 8.92735E-002 |
52 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1731.54259 |
55 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.51483E-005 |
56 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 42.16644 |
57 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.10342 |
58 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.69817 |
59 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.51300 |
60 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 5.30558E-002 |
61 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.45713E-004 |
64 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.00944E-005 |
65 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.30558E-002 |
66 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1153.84735 |
69 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.00944E-005 |
70 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 28.92258 |
71 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.28752 |
72 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 1.80884E-002 |
73 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.51300 |
74 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.68650 |
75 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51300 |
76 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.10632E-002 |
78 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.14128E-005 |
79 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.68650 |
80 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10449.05013 |
83 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.14128E-005 |
84 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 220.07044 |
85 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.76688 |
86 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.14501E-002 |
87 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.51300 |
88 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.90641 |
89 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51300 |
90 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.67771E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.84950E-005 |
93 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.90641 |
94 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10115.52116 |
97 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.84950E-005 |
98 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 224.31602 |
99 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.14165 |
100 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19388 |
101 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.51300 |
102 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.63767 |
103 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51700 |
104 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
105 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.96518E-003 |
106 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.29360E-004 |
107 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.63767 |
108 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
110 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 26217.26750 |
111 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.29360E-004 |
112 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 573.92818 |
113 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
114 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.17633 |
115 | Fan:OnOff | ROOM_1_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 1.17633 |
116 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.06935E-005 |
117 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.69063E-004 |
118 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69135 |
119 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
120 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.56579E-003 |
121 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
122 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
123 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.69063E-004 |
124 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.17633 |
125 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 4651.51968 |
126 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.06935E-005 |
127 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 132.91021 |
128 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
129 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.06605 |
130 | Fan:OnOff | ROOM_2_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 1.06605 |
131 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.07222E-005 |
132 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.35067E-004 |
133 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69134 |
134 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
135 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.57235E-003 |
136 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
137 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
138 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.35067E-004 |
139 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.06605 |
140 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 4654.79481 |
141 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.07222E-005 |
142 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 133.00378 |
143 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83707 |
144 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 8.31217 |
145 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 8.31217 |
146 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.35275E-004 |
147 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.56225E-003 |
148 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69179 |
149 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
150 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50199E-003 |
151 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
152 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
153 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.56225E-003 |
154 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 8.31217 |
155 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 26893.41674 |
156 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.35275E-004 |
157 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 768.43062 |
158 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83730 |
159 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 5.56504 |
160 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 5.56504 |
161 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.35927E-004 |
162 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.83786E-003 |
163 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69087 |
164 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
165 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.75736E-003 |
166 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
167 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
168 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.83786E-003 |
169 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.56504 |
170 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 26967.91880 |
171 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.35927E-004 |
172 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 770.55911 |
173 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
174 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.06209 |
175 | Fan:OnOff | ROOM_5_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 1.06209 |
176 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.07556E-005 |
177 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.33881E-004 |
178 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69134 |
179 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
180 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.57298E-003 |
181 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
182 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
183 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.33881E-004 |
184 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.06209 |
185 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 4658.61937 |
186 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.07556E-005 |
187 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 133.11304 |
188 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
189 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.97052 |
190 | Fan:OnOff | ROOM_6_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 0.97052 |
191 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.07843E-005 |
192 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.05665E-004 |
193 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69133 |
194 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
195 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.57979E-003 |
196 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
197 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
198 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.05665E-004 |
199 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.97052 |
200 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 4661.89354 |
201 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.07843E-005 |
202 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 133.20658 |
203 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.60744 |
204 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.73838 |
205 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.51300 |
206 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.82461 |
207 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.15992E-004 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.03856E-004 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.82461 |
212 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
213 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
214 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11871.41494 |
215 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.03856E-004 |
216 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 272.77522 |
217 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54338E-002 |
218 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.30676 |
219 | Fan:OnOff | ROOM_1_FLR_6 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 0.30676 |
220 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.24902E-005 |
221 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 9.61715E-005 |
222 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69136 |
223 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
224 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.56311E-003 |
225 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
226 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
227 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 9.61715E-005 |
228 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.30676 |
229 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1427.70541 |
230 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.24902E-005 |
231 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 40.79337 |
232 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54319E-002 |
233 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.27596 |
234 | Fan:OnOff | ROOM_2_FLR_6 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 0.27596 |
235 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.25046E-005 |
236 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 8.66871E-005 |
237 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69135 |
238 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
239 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.57032E-003 |
240 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
241 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
242 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 8.66871E-005 |
243 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.27596 |
244 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1429.35664 |
245 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.25046E-005 |
246 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 40.84055 |
247 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 9.91540E-002 |
248 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.67989 |
249 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 1.67989 |
250 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 6.00874E-005 |
251 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 5.32302E-004 |
252 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69112 |
253 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
254 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.60211E-003 |
255 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
256 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
257 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.32302E-004 |
258 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.67989 |
259 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 6868.36292 |
260 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.00874E-005 |
261 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 196.24659 |
262 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.11732 |
263 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11936 |
264 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.51300 |
265 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.08619 |
266 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51300 |
267 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
268 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.19203E-003 |
269 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.14007E-005 |
270 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.08619 |
271 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
272 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
273 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10447.65910 |
274 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.14007E-005 |
275 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 227.93863 |
276 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.21778 |
277 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11395 |
278 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.51300 |
279 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.13772 |
280 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51300 |
281 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
282 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.34348E-003 |
283 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.46622E-005 |
284 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.13772 |
285 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
286 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
287 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10820.47004 |
288 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.46622E-005 |
289 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 235.80412 |
290 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.27133 |
291 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 6.23354E-002 |
292 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.51300 |
293 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.16519 |
294 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51300 |
295 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
296 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.09934E-002 |
297 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.17429E-005 |
298 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.16519 |
299 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
300 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
301 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7057.59388 |
302 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.17429E-005 |
303 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 148.43458 |
304 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.80412 |
305 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.39054 |
306 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.51300 |
307 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.41252 |
308 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
309 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
310 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 9.75582E-004 |
311 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.30493E-005 |
312 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.41252 |
313 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
314 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
315 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7206.92457 |
316 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.30493E-005 |
317 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 171.54597 |
318 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05132 |
319 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05132 |
320 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05132 |
321 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05132 |
322 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05132 |
323 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05132 |
324 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
325 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
326 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 11.65203 |
327 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 11.65203 |
328 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 22.71351 |
329 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 11.65203 |
330 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 22.59145 |
331 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 22.59145 |
332 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
333 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.51577 |
334 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05132 |
335 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 22.59145 |
336 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05132 |
337 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05125 |
338 | HeatExchanger:AirToAir:SensibleAndLatent | FLR_3_DOAS OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.05125 |
339 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 29.40000 |
340 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
341 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.91727 |
342 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.82150E-003 |
343 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
344 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Coil Load [W] | 45447.83718 |
345 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.29980E-003 |
346 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 2.05132 |
347 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Rated Capacity [W] | 15340.96456 |
348 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.34209E-004 |
349 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 261.90442 |
350 | Fan:ConstantVolume | FLR_3_DOAS FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05125 |
351 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.29980E-003 |
352 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 3.66356E-004 |
353 | Controller:WaterCoil | FLR_3_DOAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.34209E-004 |
354 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 22.59145 |
355 | HeatExchanger:AirToAir:SensibleAndLatent | VAV WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 11.66146 |
356 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.78336 |
357 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
358 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.95289 |
359 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 9.20731E-003 |
360 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
361 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 481649.26568 |
362 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.37751E-002 |
363 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 22.59145 |
364 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 168952.24094 |
365 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.47807E-003 |
366 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 2884.39088 |
367 | Fan:VariableVolume | VAV WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 22.59145 |
368 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.37751E-002 |
369 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 3.45689E-005 |
370 | Controller:WaterCoil | VAV WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.47807E-003 |
371 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 2.15339E-002 |
372 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 3515.82228 |
373 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 3.28081E-003 |
374 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.39370 |
375 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 3.28081E-003 |
376 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 988.03639 |
377 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
378 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 375016.92346 |
379 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 375016.92000 |
380 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 3.28081E-003 |
381 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 2.15339E-002 |
382 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 2.58406 |
383 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 2.15339E-002 |
384 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 2434.12235 |
385 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 2.15339E-002 |
386 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 752935.70441 |
387 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 753560.40000 |
388 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 85.90589 |
389 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
390 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
391 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
392 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
393 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | 6836.93 |
2 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 3320.71 |
3 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1338.11 |
4 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | 1739.03 |
5 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | 1158.69 |
6 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 10502.58 |
7 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | 10164.23 |
8 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | 26347.03 |
9 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | 5009.85 |
10 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | 5013.38 |
11 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 28965.01 |
12 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 29045.25 |
13 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | 5017.50 |
14 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | 5021.02 |
15 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 11926.58 |
16 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | 1537.66 |
17 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | 1539.44 |
18 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 7397.33 |
19 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | 10499.52 |
20 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | 10874.23 |
21 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | 7093.79 |
22 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 7239.34 |
23 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | 11685.10 |
24 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | 128689.70 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | 19173.09 | 16554.96 | 2618.14 | 0.86 | 3802.76 | 38.57 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | 17397.01 | 15010.27 | 2386.74 | 0.86 | 3444.30 | 34.93 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 133833.60 | 116412.11 | 17421.49 | 0.87 | 27003.90 | 273.89 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 93929.54 | 79454.82 | 14474.72 | 0.85 | 17795.61 | 180.49 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | 17334.49 | 14955.26 | 2379.23 | 0.86 | 3431.33 | 34.80 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | 15860.14 | 13672.81 | 2187.33 | 0.86 | 3133.69 | 31.78 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | 4997.35 | 4316.26 | 681.09 | 0.86 | 991.90 | 10.06 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | 4501.68 | 3884.97 | 616.71 | 0.86 | 891.75 | 9.04 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 27566.19 | 23705.54 | 3860.65 | 0.86 | 5414.39 | 54.92 |
10 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | 49570.73 | 35167.84 | 14402.90 | 0.71 | 6912.11 | 70.11 |
11 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | 559090.64 | 394703.21 | 164387.43 | 0.71 | 88515.67 | 897.78 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 4.09 | 13.95 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.419 | 0.394 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.419 | 0.394 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.820 | 0.731 | 22.63 | 45.89 | 22.63 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 23.26 | 23.26 | 23.26 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.820 | 0.731 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.820 | 0.731 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.820 | 0.731 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.820 | 0.731 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 2.390 | 2.390 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.820 | 0.731 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.820 | 0.731 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.820 | 0.731 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.820 | 0.731 | 63.73 | 129.23 | 63.73 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 65.50 | 65.50 | 65.50 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.820 | 0.731 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.820 | 0.731 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.820 | 0.731 | 82.79 | 167.88 | 82.79 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 85.08 | 85.08 | 85.08 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.820 | 0.731 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.917 | 0.806 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.917 | 0.806 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.917 | 0.806 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.917 | 0.806 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.917 | 0.806 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.917 | 0.806 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.917 | 0.806 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.917 | 0.806 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.917 | 0.806 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.917 | 0.806 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.021 | 0.886 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.021 | 0.886 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.021 | 0.886 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.021 | 0.886 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.930 | 0.816 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.930 | 0.816 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.930 | 0.816 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.930 | 0.816 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.930 | 0.816 | 13.70 | 20.44 | 13.70 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 6.74 | 6.74 | 6.74 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.034 | 0.896 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.034 | 0.896 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.034 | 0.896 | 16.77 | 21.37 | 16.77 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.034 | 0.896 | 34.86 | 52.03 | 34.86 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 17.17 | 17.17 | 17.17 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.034 | 0.896 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.034 | 0.896 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.034 | 0.896 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.034 | 0.896 | 34.86 | 52.03 | 34.86 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 17.17 | 17.17 | 17.17 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 1.8488594988E-002 | 2.2974074959E-002 | Pass | Pass | 4.9569037922E-003 | 1.4977626802E-002 | Pass | Pass |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.8887459915E-003 | 1.4578722389E-003 | Pass | Pass | 0.3353849653 | 0.9544137540 | Pass | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.1100874448E-002 | 2.9470838200E-002 | Pass | Pass | 1.2823253019E-002 | 3.3016054019E-002 | Pass | Pass |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 3.9650809377E-003 | 9.7986082554E-003 | Pass | Pass | 2.6637532891E-002 | 6.1267690089E-002 | Pass | Pass |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 3.3711051241E-004 | 2.7846206786E-004 | Pass | Pass | 0.2171921824 | 1.3485721334 | Pass | Pass |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 6.9118705310E-002 | 0.2042853969 | Pass | Pass | 1.9430974578E-002 | 5.2395281092E-002 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.3071775497E-002 | 4.2760540289E-002 | Pass | Pass | 2.5584843043E-002 | 7.9956799351E-002 | Pass | Pass |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.9769615282E-002 | 4.7731752855E-002 | Pass | Pass | 1.3400404218E-002 | 3.6622174781E-002 | Pass | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 6.9897292769E-002 | 0.2088997344 | Pass | Pass | 8.5628166182E-002 | 0.3346990275 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 7.0277517597E-002 | 0.2094129695 | Pass | Pass | 8.6546415946E-002 | 0.3391737901 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 3.8141918404E-002 | 3.6404111060E-002 | Pass | Pass | 7.3022170539E-003 | 6.6639791027E-002 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 2.7992803800E-002 | 8.7225029039E-002 | Pass | Pass | 0.2000083775 | 0.6415293123 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 6.9468167277E-002 | 0.2072746925 | Pass | Pass | 8.7529242391E-002 | 0.3436611285 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 6.9808207792E-002 | 0.2077777308 | Pass | Pass | 8.9590965285E-002 | 0.3525749450 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.4281993367E-004 | 3.3088679879E-004 | Pass | Pass | 0.1231482578 | 0.4735711270 | Pass | Pass |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 8.3260952093E-002 | 0.2586722274 | Pass | Pass | 6.7631424739E-002 | 0.2174486788 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 8.3505029892E-002 | 0.2585725913 | Pass | Pass | 7.0578586520E-002 | 0.2292271660 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 5.4520699784E-002 | 0.1749875913 | Pass | Pass | 7.3085334011E-002 | 0.2270344001 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 2.7935332518E-002 | 6.6740056639E-002 | Pass | Pass | 1.3571226362E-002 | 4.1274763372E-002 | Pass | Pass |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 1.9074654504E-002 | 4.8127803758E-002 | Pass | Pass | 1.3740882676E-002 | 3.9961070806E-002 | Pass | Pass |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 2.1440819553E-002 | 6.0450003670E-002 | Pass | Pass | 2.1027794326E-002 | 4.2458882834E-002 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 7.1941917326E-004 | 5.1317068149E-004 | Pass | Pass | 2.6713901822E-002 | 3.7285758752E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:35
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3532.16 | 61.40 | 1821.26 | 7450.52 | 2337.33 | 15202.68 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:35
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00 | -4.20 | Wetbulb [C] | 4.30 | 20.00 |
SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 29.40 | 10.40 | 18.30 | Wetbulb [C] | 4.20 | 350.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 22.00 | 23 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 16.00 | 20 | |||
Jul | 0.00 | 0 | |||
Aug | 24.00 | 18 | |||
Sep | 12.00 | 15 | |||
Oct | 61.00 | 41 | |||
Nov | 0.00 | 0 | |||
Dec | 45.00 | 41 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:35
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 211.13 | 211.13 | 0.00 | 90.00 | N |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.399 | 0.419 | 55.76 | 55.76 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 211.13 | 211.13 | 180.00 | 90.00 | S |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.399 | 0.419 | 55.76 | 55.76 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.731 | 0.820 | 45.89 | 22.63 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.731 | 0.820 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.731 | 0.820 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.731 | 0.820 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.731 | 0.820 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.731 | 0.820 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.731 | 0.820 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.731 | 0.820 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.731 | 0.820 | 129.23 | 63.73 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.731 | 0.820 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.731 | 0.820 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.731 | 0.820 | 167.88 | 82.79 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.731 | 0.820 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.806 | 0.917 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.806 | 0.917 | 104.06 | 69.72 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.806 | 0.917 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.806 | 0.917 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.806 | 0.917 | 847.14 | 567.58 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.806 | 0.917 | 847.37 | 567.71 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.806 | 0.917 | 104.06 | 69.72 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.806 | 0.917 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.806 | 0.917 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.806 | 0.917 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 26.02 | 17.43 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.886 | 1.021 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.816 | 0.930 | 13.94 | 9.34 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.816 | 0.930 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | RES_ROOF | 0.23 | 0.182 | 0.186 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | RES_EXT_WALL_TOP | 0.30 | 0.816 | 0.930 | 13.94 | 9.34 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.816 | 0.930 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | RES_ROOF | 0.23 | 0.182 | 0.186 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.816 | 0.930 | 183.96 | 123.26 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | RES_ROOF | 0.23 | 0.182 | 0.186 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 97.55 | 65.36 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 97.55 | 65.36 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 21.37 | 16.77 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 52.03 | 34.86 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 13.94 | 9.34 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 17.65 | 11.83 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.896 | 1.034 | 52.03 | 34.86 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 167.42 | 167.42 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_FLOOR | BASEMENT_FLOOR | 0.30 | 1.441 | 2.705 | 1978.83 | 1978.83 | 0.00 | 180.00 | |
BASEMENT_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 67.07 | 67.07 | 180.00 | 0.00 | |
BASEMENT_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 77.67 | 77.67 | 180.00 | 0.00 | |
BASEMENT_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 164.24 | 164.24 | 180.00 | 0.00 | |
BASEMENT_CEILING_4 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 94.76 | 94.76 | 180.00 | 0.00 | |
BASEMENT_CEILING_5 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 78.04 | 78.04 | 180.00 | 0.00 | |
BASEMENT_CEILING_6 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 188.86 | 188.86 | 180.00 | 0.00 | |
BASEMENT_CEILING_7 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 1088.56 | 1088.56 | 180.00 | 0.00 | |
BASEMENT_CEILING_8 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 219.63 | 219.63 | 90.00 | 0.00 | |
RETAIL_1_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_1_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
RETAIL_1_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 67.07 | 67.07 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
RETAIL_2_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_2_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 90.00 | 90.00 | E |
RETAIL_2_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 77.67 | 77.67 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 77.67 | 77.67 | 180.00 | 0.00 | |
MECH_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
MECH_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 180.00 | 90.00 | S |
MECH_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
MECH_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 164.24 | 164.24 | 0.00 | 180.00 | |
MECH_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 164.24 | 164.24 | 180.00 | 0.00 | |
STORAGE_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
STORAGE_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 180.00 | 90.00 | S |
STORAGE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
STORAGE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 94.76 | 94.76 | 0.00 | 180.00 | |
STORAGE_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 94.76 | 94.76 | 180.00 | 0.00 | |
LAUNDRY_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 180.00 | 90.00 | S |
LAUNDRY_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 270.00 | 90.00 | W |
LAUNDRY_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 78.04 | 78.04 | 0.00 | 180.00 | |
LAUNDRY_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 78.04 | 78.04 | 180.00 | 0.00 | |
CAFE_FLR_1_WALL_1_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_2_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
CAFE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 188.86 | 188.86 | 0.00 | 180.00 | |
LOBBY_FLR_1_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 90.00 | 90.00 | E |
LOBBY_FLR_1_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 1088.56 | 1088.56 | 180.00 | 180.00 | |
LOBBY_FLR_1_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 219.63 | 219.63 | 90.00 | 180.00 | |
LOBBY_FLR_1_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 1062.83 | 1062.83 | 270.00 | 0.00 | |
ROOM_1_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_1_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
ROOM_1_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_1_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_2_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
ROOM_2_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_2_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_2_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 156.07 | 156.07 | 180.00 | 0.00 | |
ROOM_3_MULT19_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.14 | 847.14 | 0.00 | 90.00 | N |
ROOM_3_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_3_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 1863.81 | 1863.81 | 0.00 | 180.00 | |
ROOM_3_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 1863.81 | 1863.81 | 180.00 | 0.00 | |
ROOM_4_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_4_MULT19_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.37 | 847.37 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_4_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 1864.32 | 1864.32 | 0.00 | 180.00 | |
ROOM_4_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 1864.32 | 1864.32 | 180.00 | 0.00 | |
ROOM_5_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
ROOM_5_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_5_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_6_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
ROOM_6_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_6_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 156.07 | 156.07 | 180.00 | 0.00 | |
CORRIDOR_FLR_3_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.28 | 847.28 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_4_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.27 | 847.27 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 297.29 | 297.29 | 180.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 963.06 | 963.06 | 270.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_3 | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 297.26 | 297.26 | 90.00 | 180.00 | |
CORRIDOR_FLR_3_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 297.29 | 297.29 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 963.06 | 963.06 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 297.26 | 297.26 | 90.00 | 0.00 | |
ROOM_1_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 0.00 | 90.00 | N |
ROOM_1_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_1_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_2_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_2_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 180.00 | 90.00 | S |
ROOM_2_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_3_MULT9_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.96 | 183.96 | 0.00 | 90.00 | N |
ROOM_3_MULT9_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 90.00 | 90.00 | E |
ROOM_3_MULT9_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 270.00 | 90.00 | W |
ROOM_3_MULT9_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 220.77 | 220.77 | 0.00 | 180.00 | |
BANQUET_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
BANQUET_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
BANQUET_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
BANQUET_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 331.66 | 331.66 | 0.00 | 180.00 | |
DINING_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
DINING_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
DINING_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
DINING_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 331.66 | 331.66 | 0.00 | 180.00 | |
KITCHEN_FLR_6_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 7.43 | 7.43 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 103.30 | 103.30 | 180.00 | 180.00 | |
CORRIDOR_FLR_6_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 104.98 | 104.98 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_1_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.95 | 183.95 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 11.15 | 11.15 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 40.88 | 40.88 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 412.12 | 412.12 | 180.00 | 180.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3957.66 | 0.00 | 90.00 | N | ||
RETAIL_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 134.14 | 0.00 | 90.00 | N | ||
RETAIL_2_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 155.34 | 0.00 | 90.00 | N | ||
MECH_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 328.49 | 0.00 | 90.00 | N | ||
STORAGE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 189.52 | 0.00 | 90.00 | N | ||
LAUNDRY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 156.08 | 0.00 | 90.00 | N | ||
CAFE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 377.72 | 0.00 | 90.00 | N | ||
LOBBY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 2616.37 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3727.63 | 0.00 | 90.00 | N | ||
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3728.64 | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3115.24 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.04 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.03 | 0.00 | 90.00 | N | ||
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 441.55 | 0.00 | 90.00 | N | ||
BANQUET_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
DINING_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 206.61 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 824.25 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.36 | 23.26 | 0.00 | 0.00 | 23.26 | 23.26 | 2.159 | 0.361 | 0.397 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.36 | 65.50 | 0.00 | 0.00 | 65.50 | 65.50 | 2.159 | 0.361 | 0.397 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.36 | 85.08 | 0.00 | 0.00 | 85.08 | 85.08 | 2.159 | 0.361 | 0.397 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.38_SHGC_0.36 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.159 | 0.361 | 0.397 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.38_SHGC_0.36 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.159 | 0.361 | 0.397 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.38_SHGC_0.36 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.159 | 0.361 | 0.397 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.38_SHGC_0.36 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.159 | 0.361 | 0.397 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.38_SHGC_0.36 | 3.68 | 0.00 | 0.00 | 3.68 | 279.56 | 2.159 | 0.361 | 0.397 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.38_SHGC_0.36 | 3.68 | 0.00 | 0.00 | 3.68 | 279.65 | 2.159 | 0.361 | 0.397 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.38_SHGC_0.36 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.159 | 0.361 | 0.397 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.38_SHGC_0.36 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.159 | 0.361 | 0.397 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.38_SHGC_0.36 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.159 | 0.361 | 0.397 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.38_SHGC_0.36 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.159 | 0.361 | 0.397 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.36 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.159 | 0.361 | 0.397 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.36 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 2.159 | 0.361 | 0.397 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.36 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 2.159 | 0.361 | 0.397 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.36 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.159 | 0.361 | 0.397 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.38_SHGC_0.36 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.159 | 0.361 | 0.397 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.38_SHGC_0.36 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.159 | 0.361 | 0.397 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.38_SHGC_0.36 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.159 | 0.361 | 0.397 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.38_SHGC_0.36 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.159 | 0.361 | 0.397 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.38_SHGC_0.36 | 6.74 | 0.00 | 0.00 | 6.74 | 60.70 | 2.159 | 0.361 | 0.397 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.36 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.159 | 0.361 | 0.397 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.36 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.159 | 0.361 | 0.397 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.36 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.159 | 0.361 | 0.397 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.36 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.159 | 0.361 | 0.397 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | |||||||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.36 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.159 | 0.361 | 0.397 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.36 | 5.82 | 0.00 | 0.00 | 5.82 | 5.82 | 2.159 | 0.361 | 0.397 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.36 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 2.159 | 0.361 | 0.397 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.36 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.159 | 0.361 | 0.397 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 1213.79 | 2.159 | 0.361 | 0.397 | |||||||||||||||||
North Total or Average | 432.95 | 2.159 | 0.361 | 0.397 | |||||||||||||||||
Non-North Total or Average | 780.84 | 2.159 | 0.361 | 0.397 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 1.760 | 2.390 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:35
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:35
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 8.8143 | 1978.83 | 17441.96 | LightsWired | LTG_SCH_BASEMENT | 49.32 | 168.00 | 49.26 | 0.0000 | Y | 161.29 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | RETAIL_1_FLR_1 | GENERAL | 11.3140 | 67.07 | 758.85 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 7.31 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | RETAIL_2_FLR_1 | GENERAL | 11.3140 | 77.67 | 878.75 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 8.46 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | MECH_FLR_1 | GENERAL | 4.6285 | 164.24 | 760.20 | LightsWired | LTG_SCH_MECHANIC | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 8.37 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | STORAGE_FLR_1 | GENERAL | 5.7199 | 94.76 | 542.02 | LightsWired | LTG_SCH_STORAGE | 30.30 | 168.00 | 30.27 | 0.0000 | Y | 3.08 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | LAUNDRY_FLR_1 | GENERAL | 4.6285 | 78.04 | 361.20 | LightsWired | LTG_SCH_LAUNDRY | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 3.98 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | CAFE_FLR_1 | GENERAL | 10.0104 | 188.86 | 1890.59 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 40.13 | 0.0000 | Y | 14.24 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | LOBBY_FLR_1 | GENERAL | 10.7639 | 1308.19 | 14081.18 | LightsWired | LTG_SCH_LOBBY | 44.02 | 168.00 | 41.68 | 0.0000 | Y | 110.17 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | ROOM_1_FLR_3 | GENERAL | 8.2882 | 156.09 | 1293.69 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | ROOM_2_FLR_3 | GENERAL | 8.2882 | 156.07 | 1293.54 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | GENERAL | 8.2882 | 1863.81 | 15447.65 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 110.38 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | GENERAL | 8.2882 | 1864.32 | 15451.87 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 110.41 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | ROOM_5_FLR_3 | GENERAL | 8.2882 | 156.09 | 1293.69 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | ROOM_6_FLR_3 | GENERAL | 8.2882 | 156.07 | 1293.54 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | CORRIDOR_FLR_3 | GENERAL | 7.1042 | 1557.62 | 11065.59 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 91.33 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | ROOM_1_FLR_6 | GENERAL | 8.2882 | 39.02 | 323.42 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 2.31 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | ROOM_2_FLR_6 | GENERAL | 8.2882 | 39.02 | 323.38 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 2.31 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | GENERAL | 8.2882 | 220.77 | 1829.83 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 13.08 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | BANQUET_FLR_6 | GENERAL | 10.0104 | 331.66 | 3320.03 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 49.75 | 0.0000 | Y | 31.01 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | DINING_FLR_6 | GENERAL | 10.0104 | 331.66 | 3320.03 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 49.75 | 0.0000 | Y | 31.01 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | KITCHEN_FLR_6 | GENERAL | 11.4097 | 103.30 | 1178.68 | LightsWired | LTG_SCH_KITCHEN | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 12.97 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | CORRIDOR_FLR_6 | GENERAL | 7.1042 | 412.12 | 2927.80 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 24.17 |
Interior Lighting Total | 8.5566 | 11345.29 | 97077.49 | 457.10 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
LOBBY_FLR_1_DAYLREFPT1 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.07 | 14081.18 | 985.68 |
LOBBY_FLR_1_DAYLREFPT2 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.07 | 14081.18 | 985.68 |
CAFE_FLR_1_DAYLREFPT1 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1890.59 | 737.33 |
CAFE_FLR_1_DAYLREFPT2 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1890.59 | 737.33 |
DINING_FLR_6_DAYLREFPT1 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
DINING_FLR_6_DAYLREFPT2 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
BANQUET_FLR_6_DAYLREFPT1 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
BANQUET_FLR_6_DAYLREFPT2 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 12338.45 | AstronomicalClock | - | 83.55 | 83.55 | 193.50 | |
Exterior Lighting Total | 12338.45 | 193.50 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:35
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 375016.92 | 0.80 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 753560.40 | 2.96 | 753560.40 | 2.96 | 4.09 | 13.95 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 12904.59 | 19173.09 | 16554.96 | 2618.14 | 0.86 | - | 3802.76 | 38.57 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 11715.90 | 17397.01 | 15010.27 | 2386.74 | 0.86 | - | 3444.30 | 34.93 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 89591.38 | 133833.60 | 116412.11 | 17421.49 | 0.87 | - | 27003.90 | 273.89 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 64262.48 | 93929.54 | 79454.82 | 14474.72 | 0.85 | - | 17795.61 | 180.49 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 11674.44 | 17334.49 | 14955.26 | 2379.23 | 0.86 | - | 3431.33 | 34.80 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 10687.84 | 15860.14 | 13672.81 | 2187.33 | 0.86 | - | 3133.69 | 31.78 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3362.72 | 4997.35 | 4316.26 | 681.09 | 0.86 | - | 991.90 | 10.06 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3031.09 | 4501.68 | 3884.97 | 616.71 | 0.86 | - | 891.75 | 9.04 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 18612.38 | 27566.19 | 23705.54 | 3860.65 | 0.86 | - | 5414.39 | 54.92 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | 45447.84 | 49570.73 | 35167.84 | 14402.90 | 0.71 | - | 6912.11 | 70.11 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | 481649.27 | 559090.64 | 394703.21 | 164387.43 | 0.71 | - | 88515.67 | 897.78 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 6801.76 | 6836.93 | - |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 3305.38 | 3320.71 | - |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1331.70 | 1338.11 | - |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1731.54 | 1739.03 | - |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1153.85 | 1158.69 | - |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 10449.05 | 10502.58 | - |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 10115.52 | 10164.23 | - |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 26217.27 | 26347.03 | - |
ROOM_1_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 4651.52 | 5009.85 | - |
ROOM_2_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 4654.79 | 5013.38 | - |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 26893.42 | 28965.01 | - |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 26967.92 | 29045.25 | - |
ROOM_5_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 4658.62 | 5017.50 | - |
ROOM_6_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 4661.89 | 5021.02 | - |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 11871.41 | 11926.58 | - |
ROOM_1_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 1427.71 | 1537.66 | - |
ROOM_2_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 1429.36 | 1539.44 | - |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 6868.36 | 7397.33 | - |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 10447.66 | 10499.52 | - |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 10820.47 | 10874.23 | - |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 7057.59 | 7093.79 | - |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 7206.92 | 7239.34 | - |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | 15340.96 | 11685.10 | - |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | 168952.24 | 128689.70 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 0.24 | 76.61 | 324.68 | 1.00 | 2.78 | General | ||
LOBBY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.24 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
ROOM_1_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 1.18 | 827.71 | 703.64 | 1.00 | 1.16 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 |
ROOM_2_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 1.07 | 750.11 | 703.64 | 1.00 | 1.18 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 |
ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 8.31 | 5848.75 | 703.64 | 1.00 | 0.94 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 |
ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 5.57 | 3915.77 | 703.64 | 1.00 | 0.96 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 |
ROOM_5_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 1.06 | 747.33 | 703.64 | 1.00 | 1.18 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 |
ROOM_6_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 0.97 | 682.90 | 703.64 | 1.00 | 1.20 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 |
ROOM_1_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 0.31 | 215.84 | 703.64 | 1.00 | 1.70 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 |
ROOM_2_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 0.28 | 194.17 | 703.64 | 1.00 | 1.77 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 |
ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 1.68 | 1182.03 | 703.64 | 1.00 | 1.09 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 |
BANQUET_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
DINING_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 1.89 | 612.92 | 324.68 | 1.00 | 1.48 | General | ||
FLR_3_DOAS FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.93 | 1070.05 | 1.00 | 1.30 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
VAV WITH REHEAT FAN | Fan:VariableVolume | 0.62 | 1389.42 | 22.59 | 50619.28 | 2240.64 | 1.00 | 1.11 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.021534 | 3515.82 | 163269.44 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.003281 | 988.04 | 301156.09 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.021534 | 2434.12 | 113036.94 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH LAUNDRY G WATER HEATER | WaterHeater:Mixed | 1.14 | 163316.00 | 0.80 | 11.51 | 0.44 |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.22 | 1.12 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.60 | 0.80 | 5.78 | 0.37 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:35
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 34561.47 | 34561.47 | 17.47 | 2.547 | 2.547 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 24.00 | 24.00 | 0.00920 | 25.86 | 0.00882 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 6002.75 | 6002.75 | 89.50 | 0.442 | 0.442 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 24.00 | 24.00 | 0.00891 | 29.05 | 0.00882 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 3147.80 | 3147.80 | 40.53 | 0.232 | 0.232 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:40:00 | 24.00 | 24.00 | 0.00940 | 28.98 | 0.00882 | 0.092 | 0.00 |
MECH_FLR_1 | 2361.19 | 2361.19 | 14.38 | 0.174 | 0.174 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:40:00 | 24.00 | 24.00 | 0.00876 | 28.98 | 0.00882 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1403.26 | 1403.26 | 14.81 | 0.103 | 0.103 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 24.00 | 24.00 | 0.00883 | 29.40 | 0.00882 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 44601.97 | 44601.97 | 571.53 | 3.288 | 3.288 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 24.00 | 24.00 | 0.00854 | 29.40 | 0.00882 | 0.000 | 0.00 |
CAFE_FLR_1 | 23949.81 | 23949.81 | 126.81 | 1.767 | 1.767 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 24.00 | 23.99 | 0.00984 | 29.05 | 0.00882 | 0.676 | 0.00 |
LOBBY_FLR_1 | 69729.69 | 69729.69 | 53.30 | 5.142 | 5.142 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 24.00 | 23.99 | 0.00987 | 29.23 | 0.00882 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 11843.54 | 11843.54 | 303.51 | 1.176 | 1.176 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 21.11 | 21.11 | 0.00857 | 28.36 | 0.00882 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 10733.21 | 10733.21 | 275.09 | 1.066 | 1.066 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | 21.11 | 21.11 | 0.00857 | 28.08 | 0.00882 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 83692.74 | 83692.74 | 3412.71 | 8.312 | 8.312 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 21.11 | 21.11 | 0.00850 | 29.14 | 0.00882 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 56028.35 | 56028.35 | 2284.02 | 5.565 | 5.565 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 21.11 | 21.11 | 0.00876 | 29.40 | 0.00882 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 10693.39 | 10693.39 | 274.03 | 1.062 | 1.062 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 21.11 | 21.11 | 0.00857 | 25.45 | 0.00882 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 9771.45 | 9771.45 | 250.44 | 0.971 | 0.971 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 21.11 | 21.11 | 0.00858 | 23.68 | 0.00881 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 21808.50 | 21808.50 | 56.00 | 1.607 | 1.607 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 24.00 | 24.00 | 0.00937 | 29.40 | 0.00882 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 3088.50 | 3088.50 | 79.15 | 0.307 | 0.307 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 21.11 | 21.11 | 0.00856 | 28.36 | 0.00882 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2778.40 | 2778.40 | 71.21 | 0.276 | 0.276 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 21.11 | 21.11 | 0.00857 | 27.94 | 0.00882 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 16913.13 | 16913.13 | 689.47 | 1.680 | 1.680 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 21.11 | 21.11 | 0.00860 | 29.23 | 0.00882 | 0.099 | 0.00 |
BANQUET_FLR_6 | 28690.49 | 28690.49 | 86.51 | 2.117 | 2.117 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 24.00 | 23.98 | 0.01046 | 29.40 | 0.00882 | 1.188 | 0.00 |
DINING_FLR_6 | 30052.15 | 30052.15 | 90.61 | 2.218 | 2.218 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 24.00 | 23.99 | 0.01037 | 29.40 | 0.00882 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 30735.30 | 30735.30 | 297.52 | 2.271 | 2.271 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 24.00 | 23.97 | 0.01008 | 28.46 | 0.00882 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 10909.83 | 10909.83 | 26.47 | 0.804 | 0.804 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 24.00 | 24.00 | 0.00896 | 29.40 | 0.00882 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 0.854 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.89 | 0.00269 | -4.20 | 0.00269 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 2124.55 | 2124.55 | 31.68 | 0.092 | 0.092 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00774 | -4.20 | 0.00269 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 712.48 | 712.48 | 9.17 | 0.031 | 0.092 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00770 | -4.20 | 0.00269 | 0.092 | 0.00 |
MECH_FLR_1 | 1267.24 | 1267.24 | 7.72 | 0.055 | 0.055 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00761 | -4.20 | 0.00269 | 0.000 | 0.00 |
STORAGE_FLR_1 | 877.88 | 877.88 | 9.26 | 0.038 | 0.058 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00767 | -4.20 | 0.00269 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 1678.32 | 1678.32 | 21.51 | 0.073 | 0.073 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00760 | -4.20 | 0.00269 | 0.000 | 0.00 |
CAFE_FLR_1 | 5400.13 | 5400.13 | 28.59 | 0.235 | 0.676 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00777 | -4.20 | 0.00269 | 0.676 | 0.00 |
LOBBY_FLR_1 | 12496.36 | 12496.36 | 9.55 | 0.543 | 1.894 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00772 | -4.20 | 0.00269 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 4651.57 | 4651.57 | 119.20 | 0.203 | 0.203 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00772 | -4.20 | 0.00269 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 4654.85 | 4654.85 | 119.30 | 0.204 | 0.204 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00773 | -4.20 | 0.00269 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 26893.56 | 26893.56 | 1096.63 | 1.176 | 1.176 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00775 | -4.20 | 0.00269 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 26968.07 | 26968.07 | 1099.37 | 1.180 | 1.180 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00775 | -4.20 | 0.00269 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 4658.67 | 4658.67 | 119.39 | 0.204 | 0.204 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00773 | -4.20 | 0.00269 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 4661.95 | 4661.95 | 119.48 | 0.204 | 0.204 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00773 | -4.20 | 0.00269 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 7581.23 | 7581.23 | 19.47 | 0.330 | 0.475 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00779 | -4.20 | 0.00269 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 1427.72 | 1427.72 | 36.59 | 0.062 | 0.062 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00777 | -4.20 | 0.00269 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 1429.37 | 1429.37 | 36.63 | 0.063 | 0.063 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00777 | -4.20 | 0.00269 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 6868.42 | 6868.42 | 279.99 | 0.300 | 0.300 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00778 | -4.20 | 0.00269 | 0.099 | 0.00 |
BANQUET_FLR_6 | 4796.26 | 4796.26 | 14.46 | 0.209 | 1.188 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00783 | -4.20 | 0.00269 | 1.188 | 0.00 |
DINING_FLR_6 | 4901.05 | 4901.05 | 14.78 | 0.213 | 1.188 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:10:00 | 21.00 | 21.00 | 0.00784 | -4.20 | 0.00269 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 1026.40 | 1026.40 | 9.94 | 0.045 | 0.367 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 21.00 | 21.00 | 0.00541 | -4.20 | 0.00269 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 5060.53 | 5060.53 | 12.28 | 0.220 | 0.220 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:10:00 | 21.00 | 21.00 | 0.00786 | -4.20 | 0.00269 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
FLR_3_DOAS | 19.16 | 2.05 | 3.60 | 2.05 | 2.0513 | 2.0513 | 2.0513 | 1.0000 | 0.3000 |
VAV WITH REHEAT | 22.59 | 22.59 | 7.23 | 7.23 | 22.5915 | 11.6520 | 22.5915 | 0.5158 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 6801.763 | 6801.763 | 1.306858 | 0.00005950 | 141.839 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 6801.76 | 6801.76 | 1.306858 | 16.70 | 13.06 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00800000 | 50.9797 | 0.00 | 0.00 | 6839.99 | 6839.99 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 3305.380 | 3305.380 | 0.226999 | 0.00002892 | 76.090 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3305.38 | 3305.38 | 0.226999 | 16.70 | 13.06 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00773838 | 49.3337 | 2124.55 | 0.00 | 3323.10 | 3323.10 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 1331.695 | 1331.695 | 0.119040 | 0.00001165 | 29.539 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1331.70 | 1331.70 | 0.119040 | 16.70 | 13.06 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00770095 | 49.0975 | 712.48 | 0.00 | 1338.93 | 1338.93 |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 1731.543 | 1731.543 | 0.089274 | 0.00001515 | 42.166 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1731.54 | 1731.54 | 0.089274 | 16.70 | 13.06 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00760975 | 48.5232 | 1267.24 | 0.00 | 1740.55 | 1740.55 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 1153.847 | 1153.847 | 0.053056 | 0.00001009 | 28.923 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1153.85 | 1153.85 | 0.053056 | 16.70 | 13.06 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00767103 | 48.9091 | 877.88 | 0.00 | 1159.79 | 1159.79 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 10449.050 | 10449.050 | 1.686497 | 0.00009141 | 220.070 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 10449.05 | 10449.05 | 1.686497 | 16.70 | 13.06 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00759883 | 48.4548 | 1678.32 | 0.00 | 10507.57 | 10507.57 |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 10115.521 | 10115.521 | 0.906411 | 0.00008849 | 224.316 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 10115.52 | 10115.52 | 0.906411 | 16.70 | 13.06 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00777100 | 49.5390 | 5400.13 | 0.00 | 10170.51 | 10170.51 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 26217.268 | 26217.268 | 2.637666 | 0.00022936 | 573.928 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 26217.27 | 26217.27 | 2.637666 | 16.70 | 13.06 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00771996 | 49.2173 | 12496.36 | 0.00 | 26362.38 | 26362.38 |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 12904.592 | -999.000 | 1.176326 | 0.00036906 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | unknown | 8/21 16:30:00 | 12904.59 | 12702.77 | 1.176326 | 21.69 | 15.47 | 0.00856579 | 12.80 | 11.97 | 0.00850000 | 28.36 | 0.00881983 | 18.00 | 0.0000 | 21.11 | 0.00856579 | 54.1668 | 11843.54 | 0.00 | 13095.37 | 13095.37 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 4651.520 | 4651.520 | 0.203448 | 0.00004069 | 132.910 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 4651.52 | 4651.52 | 0.203448 | 21.11 | 14.50 | 0.00772493 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.11 | 0.00772493 | 48.9145 | 4651.57 | 0.00 | 5014.48 | 5014.48 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 11715.903 | -999.000 | 1.066047 | 0.00033507 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | unknown | 8/21 16:50:00 | 11715.90 | 11514.70 | 1.066047 | 21.69 | 15.48 | 0.00857235 | 12.80 | 11.97 | 0.00850000 | 28.08 | 0.00881938 | 17.91 | 0.0000 | 21.11 | 0.00857235 | 54.2077 | 10733.21 | 0.00 | 11888.82 | 11888.82 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 4654.795 | 4654.795 | 0.203592 | 0.00004072 | 133.004 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 4654.79 | 4654.79 | 0.203592 | 21.11 | 14.50 | 0.00772514 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.11 | 0.00772514 | 48.9158 | 4654.85 | 0.00 | 5018.01 | 5018.01 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 89591.379 | -999.000 | 8.312172 | 0.00256225 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | unknown | 8/21 13:30:00 | 89591.38 | 89548.33 | 8.312172 | 21.69 | 15.42 | 0.00850199 | 12.80 | 11.97 | 0.00850000 | 29.14 | 0.00882108 | 18.26 | 0.0000 | 21.11 | 0.00850199 | 53.7675 | 83692.74 | 0.00 | 90923.28 | 90923.28 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 26893.417 | 26893.417 | 1.176276 | 0.00023528 | 768.431 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 26893.42 | 26893.42 | 1.176276 | 21.11 | 14.52 | 0.00774669 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.11 | 0.00774669 | 49.0501 | 26893.56 | 0.00 | 28992.01 | 28992.01 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 64262.482 | -999.000 | 5.565044 | 0.00183786 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | unknown | 8/21 15:00:00 | 64262.48 | 60501.94 | 5.565044 | 21.69 | 15.64 | 0.00875736 | 12.80 | 11.97 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 0.0000 | 21.11 | 0.00875736 | 55.3623 | 56028.35 | 0.00 | 65190.74 | 63826.20 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 26967.919 | 26967.919 | 1.179535 | 0.00023593 | 770.559 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 26967.92 | 26967.92 | 1.179535 | 21.11 | 14.52 | 0.00774729 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.11 | 0.00774729 | 49.0538 | 26968.07 | 0.00 | 29072.33 | 29072.33 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 11674.441 | -999.000 | 1.062091 | 0.00033388 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | unknown | 8/21 10:00:00 | 11674.44 | 11472.23 | 1.062091 | 21.69 | 15.48 | 0.00857298 | 12.80 | 11.97 | 0.00850000 | 25.45 | 0.00881519 | 17.01 | 0.0000 | 21.11 | 0.00857298 | 54.2117 | 10693.39 | 0.00 | 11846.72 | 11846.72 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 4658.619 | 4658.619 | 0.203759 | 0.00004076 | 133.113 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 4658.62 | 4658.62 | 0.203759 | 21.11 | 14.50 | 0.00772533 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.11 | 0.00772533 | 48.9170 | 4658.67 | 0.00 | 5022.14 | 5022.14 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 10687.837 | -999.000 | 0.970524 | 0.00030567 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | unknown | 8/21 09:00:00 | 10687.84 | 10485.79 | 0.970524 | 21.69 | 15.48 | 0.00857979 | 12.80 | 11.97 | 0.00850000 | 23.68 | 0.00881240 | 16.40 | 0.0000 | 21.11 | 0.00857979 | 54.2541 | 9771.45 | 0.00 | 10845.28 | 10845.28 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 4661.894 | 4661.894 | 0.203902 | 0.00004078 | 133.207 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 4661.89 | 4661.89 | 0.203902 | 21.11 | 14.50 | 0.00772554 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.11 | 0.00772554 | 48.9182 | 4661.95 | 0.00 | 5025.67 | 5025.67 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 11871.415 | 11871.415 | 0.824615 | 0.00010386 | 272.775 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 11871.41 | 11871.41 | 0.824615 | 16.70 | 13.06 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00779186 | 49.6699 | 7581.23 | 0.00 | 11935.11 | 11935.11 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 3362.718 | -999.000 | 0.306756 | 0.00009617 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | unknown | 8/21 16:30:00 | 3362.72 | 3312.23 | 0.306756 | 21.69 | 15.47 | 0.00856311 | 12.80 | 11.97 | 0.00850000 | 28.36 | 0.00881983 | 18.00 | 0.0000 | 21.11 | 0.00856311 | 54.1500 | 3088.50 | 0.00 | 3412.47 | 3412.47 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 1427.705 | 1427.705 | 0.062445 | 0.00001249 | 40.793 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1427.71 | 1427.71 | 0.062445 | 21.11 | 14.55 | 0.00777374 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.11 | 0.00777374 | 49.2197 | 1427.72 | 0.00 | 1539.11 | 1539.11 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 3031.088 | -999.000 | 0.275957 | 0.00008669 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | unknown | 8/21 17:00:00 | 3031.09 | 2980.47 | 0.275957 | 21.69 | 15.48 | 0.00857032 | 12.80 | 11.97 | 0.00850000 | 27.94 | 0.00881916 | 17.86 | 0.0000 | 21.11 | 0.00857032 | 54.1950 | 2778.40 | 0.00 | 3075.85 | 3075.85 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 1429.357 | 1429.357 | 0.062517 | 0.00001250 | 40.841 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1429.36 | 1429.36 | 0.062517 | 21.11 | 14.55 | 0.00777401 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.11 | 0.00777401 | 49.2214 | 1429.37 | 0.00 | 1540.89 | 1540.89 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 18612.379 | -999.000 | 1.679889 | 0.00053230 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | unknown | 8/21 13:40:00 | 18612.38 | 18164.43 | 1.679889 | 21.69 | 15.50 | 0.00860211 | 12.80 | 11.97 | 0.00850000 | 29.23 | 0.00882122 | 18.29 | 0.0000 | 21.11 | 0.00860211 | 54.3940 | 16913.13 | 0.00 | 18885.04 | 18885.04 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 6868.363 | 6868.363 | 0.300410 | 0.00006009 | 196.247 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 6868.36 | 6868.36 | 0.300410 | 21.11 | 14.55 | 0.00778303 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.11 | 0.00778303 | 49.2776 | 6868.42 | 0.00 | 7404.31 | 7404.31 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 10447.659 | 10447.659 | 1.086187 | 0.00009140 | 227.939 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 10447.66 | 10447.66 | 1.086187 | 16.70 | 13.06 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00783265 | 49.9268 | 4796.26 | 0.00 | 10505.54 | 10505.54 |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 10820.470 | 10820.470 | 1.137720 | 0.00009466 | 235.804 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:10:00 | 10820.47 | 10820.47 | 1.137720 | 16.70 | 13.06 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00783610 | 49.9488 | 4901.05 | 0.00 | 10880.43 | 10880.43 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 7057.594 | 7057.594 | 1.165192 | 0.00006174 | 148.435 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 7057.59 | 7057.59 | 1.165192 | 16.70 | 13.06 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00540943 | 34.6207 | 1026.40 | 0.00 | 7097.14 | 7097.14 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 7206.925 | 7206.925 | 0.412515 | 0.00006305 | 171.546 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:10:00 | 7206.92 | 7206.92 | 0.412515 | 16.70 | 13.06 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00786026 | 50.1007 | 5060.53 | 0.00 | 7245.20 | 7245.20 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 45447.837 | -999.000 | 2.051317 | 0.00129980 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 45447.84 | 43504.21 | 2.051317 | 29.40 | 18.34 | 0.00882150 | 11.92 | 11.61 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 99.9965 | 21.11 | 0.00860544 | 54.4137 | 192922.69 | 0.00 | 45917.97 | 43441.59 |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | FLR_3_DOAS | 15340.965 | 15340.965 | 0.615395 | 0.00013421 | 261.904 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 15340.96 | 15340.96 | 0.615395 | -4.20 | -4.20 | 0.00269032 | 16.70 | 13.06 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 333.3216 | 21.11 | 0.00774716 | 49.0530 | 82214.19 | 0.00 | 14133.30 | 14133.30 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 481649.266 | -999.000 | 22.591451 | 0.01377511 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 481649.27 | 432061.98 | 22.591451 | 26.78 | 17.79 | 0.00920731 | 10.95 | 10.95 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 51.6189 | 23.99 | 0.00957604 | 50.7488 | 306177.77 | 0.00 | 487018.06 | 422262.48 |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV WITH REHEAT | 168952.241 | 168952.241 | 6.777435 | 0.00147807 | 2884.391 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:30:00 | 168952.24 | 168952.24 | 6.777435 | -4.20 | -4.20 | 0.00269032 | 16.70 | 13.06 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 172.0630 | 21.21 | 0.00661006 | 41.6679 | 47220.32 | 0.00 | 155652.07 | 155652.07 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:35
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | Yes | Yes | No | 6801.763 | 6801.763 | 1.306858 | 0.00005950 | 141.839 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.28047697 | 54.44 | 82.22 | 27.78 | 382564.29 | 1.7779 | 1.813722 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 6801.76 | 6801.76 | 1.0000 | 1.55122827 | 1.306858 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.05949872 | 60.00 | 32.22 | 27.78 | 0.000 | 6801.76 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 50.9797 | 0.00 | 0.00 | 6839.99 | 6839.99 | 1.55122827 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 20.92 | 14.82 | 0.00800000 | 41344.1 | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3305.380 | 3305.380 | 0.226999 | 0.00002892 | 76.090 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.28047697 | 54.44 | 82.22 | 27.78 | 382564.29 | 0.8640 | 0.881395 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 3305.38 | 3305.38 | 1.0000 | 0.26944582 | 0.226999 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.02891396 | 60.00 | 32.22 | 27.78 | 0.000 | 3305.38 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00773838 | 21.00 | 0.00773838 | 49.3337 | 2124.55 | 0.00 | 3323.10 | 3323.10 | 0.26944582 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 28.69 | 17.60 | 0.00800000 | 49267.8 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1331.695 | 1331.695 | 0.119040 | 0.00001165 | 29.539 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.28047697 | 54.44 | 82.22 | 27.78 | 382564.29 | 0.3481 | 0.355103 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1331.70 | 1331.70 | 1.0000 | 0.14129891 | 0.119040 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.01164906 | 60.00 | 32.22 | 27.78 | 0.000 | 1331.70 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00770095 | 21.00 | 0.00770095 | 49.0975 | 712.48 | 0.00 | 1338.93 | 1338.93 | 0.14129891 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 25.89 | 16.63 | 0.00800000 | 46410.6 | |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1731.543 | 1731.543 | 0.089274 | 0.00001515 | 42.166 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.28047697 | 54.44 | 82.22 | 27.78 | 382564.29 | 0.4526 | 0.461724 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1731.54 | 1731.54 | 1.0000 | 0.10596684 | 0.089274 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.01514674 | 60.00 | 32.22 | 27.78 | 0.000 | 1731.54 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00760975 | 21.00 | 0.00760975 | 48.5232 | 1267.24 | 0.00 | 1740.55 | 1740.55 | 0.10596684 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 32.71 | 18.93 | 0.00800000 | 53360.1 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1153.847 | 1153.847 | 0.053056 | 0.00001009 | 28.923 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.28047697 | 54.44 | 82.22 | 27.78 | 382564.29 | 0.3016 | 0.307679 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1153.85 | 1153.85 | 1.0000 | 0.06297677 | 0.053056 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.01009333 | 60.00 | 32.22 | 27.78 | 0.000 | 1153.85 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00767103 | 21.00 | 0.00767103 | 48.9091 | 877.88 | 0.00 | 1159.79 | 1159.79 | 0.06297677 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 34.66 | 19.55 | 0.00800000 | 55350.9 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10449.050 | 10449.050 | 1.686497 | 0.00009141 | 220.070 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.28047697 | 54.44 | 82.22 | 27.78 | 382564.29 | 2.7313 | 2.786288 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 10449.05 | 10449.05 | 1.0000 | 2.00185598 | 1.686497 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.09140352 | 60.00 | 32.22 | 27.78 | 0.000 | 10449.05 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00759883 | 21.00 | 0.00759883 | 48.4548 | 1678.32 | 0.00 | 10507.57 | 10507.57 | 2.00185598 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.75 | 15.13 | 0.00800000 | 42183.6 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10115.521 | 10115.521 | 0.906411 | 0.00008849 | 224.316 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.28047697 | 54.44 | 82.22 | 27.78 | 382564.29 | 2.6441 | 2.697351 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 10115.52 | 10115.52 | 1.0000 | 1.07590121 | 0.906411 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.08848596 | 60.00 | 32.22 | 27.78 | 0.000 | 10115.52 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00777100 | 21.00 | 0.00777100 | 49.5390 | 5400.13 | 0.00 | 10170.51 | 10170.51 | 1.07590121 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 25.87 | 16.62 | 0.00800000 | 46387.8 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 26217.268 | 26217.268 | 2.637666 | 0.00022936 | 573.928 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.28047697 | 54.44 | 82.22 | 27.78 | 382564.29 | 6.8530 | 6.990956 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 26217.27 | 26217.27 | 1.0000 | 3.13088476 | 2.637666 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.22933670 | 60.00 | 32.22 | 27.78 | 0.000 | 26217.27 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00771996 | 21.00 | 0.00771996 | 49.2173 | 12496.36 | 0.00 | 26362.38 | 26362.38 | 3.13088476 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 24.86 | 16.26 | 0.00800000 | 45354.8 | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12904.592 | -999.000 | 1.176326 | 0.00036906 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7634 | 1004.8586 | 1.1870 | ROOM_1_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.176326 | 1.39628853 | 4197.9300 | 999.8980 | 21.53166916 | 15.03 | 6.70 | 8.33 | 752935.70 | 1.7139 | 1.713872 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | unknown | unknown | unknown | 8/21 16:30:00 | Sensible | 12904.59 | 12702.77 | 1.0000 | 1.39628853 | 1.176326 | 21.69 | 15.47 | 0.00856579 | 43564.3 | 12.80 | 11.97 | 0.00850000 | 34322.2 | 0.36902517 | 6.70 | 15.03 | 8.33 | 0.000 | 12904.59 | 28.36 | 0.00881983 | 18.00 | 0.00000000 | 0.0000 | 21.11 | 0.00856579 | 21.11 | 0.00856579 | 54.1668 | 11843.54 | 0.00 | 13095.37 | 13095.37 | 1.39628853 | 21.69 | 15.62 | 0.00856579 | 43564.3 | 12.50 | 12.04 | 0.00856579 | 34185.6 | |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4651.520 | 4651.520 | 0.203448 | 0.00004069 | 132.910 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | ROOM_1_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.176326 | 1.39628853 | 4197.9300 | 999.8980 | 3.28047697 | 54.44 | 82.22 | 27.78 | 382564.29 | 1.2159 | 1.240349 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 4651.52 | 4651.52 | 1.0000 | 0.24149148 | 0.203448 | 21.11 | 14.50 | 0.00772493 | 40835.6 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.04068937 | 60.00 | 32.22 | 27.78 | 0.000 | 4651.52 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.11 | 0.00772493 | 21.11 | 0.00772493 | 48.9145 | 4651.57 | 0.00 | 5014.48 | 5014.48 | 0.24149148 | 16.60 | 12.88 | 0.00772493 | 36238.3 | 36.97 | 20.06 | 0.00772493 | 57003.0 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11715.903 | -999.000 | 1.066047 | 0.00033507 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7756 | 1004.8586 | 1.1870 | ROOM_2_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.066047 | 1.26538853 | 4197.9300 | 999.8980 | 21.53166916 | 15.03 | 6.70 | 8.33 | 752935.70 | 1.5560 | 1.556001 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | unknown | unknown | unknown | 8/21 16:50:00 | Sensible | 11715.90 | 11514.70 | 1.0000 | 1.26538853 | 1.066047 | 21.69 | 15.48 | 0.00857235 | 43580.9 | 12.80 | 11.97 | 0.00850000 | 34322.2 | 0.33503291 | 6.70 | 15.03 | 8.33 | 0.000 | 11715.90 | 28.08 | 0.00881938 | 17.91 | 0.00000000 | 0.0000 | 21.11 | 0.00857235 | 21.11 | 0.00857235 | 54.2077 | 10733.21 | 0.00 | 11888.82 | 11888.82 | 1.26538853 | 21.69 | 15.62 | 0.00857235 | 43580.9 | 12.49 | 12.04 | 0.00857235 | 34185.5 | |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4654.795 | 4654.795 | 0.203592 | 0.00004072 | 133.004 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | ROOM_2_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.066047 | 1.26538853 | 4197.9300 | 999.8980 | 3.28047697 | 54.44 | 82.22 | 27.78 | 382564.29 | 1.2167 | 1.241223 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 4654.79 | 4654.79 | 1.0000 | 0.24166151 | 0.203592 | 21.11 | 14.50 | 0.00772514 | 40836.2 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.04071802 | 60.00 | 32.22 | 27.78 | 0.000 | 4654.79 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.11 | 0.00772514 | 21.11 | 0.00772514 | 48.9158 | 4654.85 | 0.00 | 5018.01 | 5018.01 | 0.24166151 | 16.60 | 12.88 | 0.00772514 | 36238.8 | 36.97 | 20.06 | 0.00772514 | 57003.5 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 89591.379 | -999.000 | 8.312172 | 0.00256225 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6448 | 1004.8586 | 1.1870 | ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 8.312172 | 9.86647102 | 4197.9300 | 999.8980 | 21.53166916 | 15.03 | 6.70 | 8.33 | 752935.70 | 11.8989 | 11.898719 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | unknown | unknown | unknown | 8/21 13:30:00 | Sensible | 89591.38 | 89548.33 | 1.0000 | 9.86647102 | 8.312172 | 21.69 | 15.42 | 0.00850199 | 43402.6 | 12.80 | 11.97 | 0.00850000 | 34322.2 | 2.56199287 | 6.70 | 15.03 | 8.33 | 0.000 | 89591.38 | 29.14 | 0.00882108 | 18.26 | 0.00000000 | 0.0000 | 21.11 | 0.00850199 | 21.11 | 0.00850199 | 53.7675 | 83692.74 | 0.00 | 90923.28 | 90923.28 | 9.86647102 | 21.69 | 15.56 | 0.00850199 | 43402.6 | 12.66 | 12.05 | 0.00850199 | 34187.2 | |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 26893.417 | 26893.417 | 1.176276 | 0.00023528 | 768.431 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 8.312172 | 9.86647102 | 4197.9300 | 999.8980 | 3.28047697 | 54.44 | 82.22 | 27.78 | 382564.29 | 7.0298 | 7.171254 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 26893.42 | 26893.42 | 1.0000 | 1.39622878 | 1.176276 | 21.11 | 14.52 | 0.00774669 | 40891.1 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.23525134 | 60.00 | 32.22 | 27.78 | 0.000 | 26893.42 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.11 | 0.00774669 | 21.11 | 0.00774669 | 49.0501 | 26893.56 | 0.00 | 28992.01 | 28992.01 | 1.39622878 | 16.60 | 12.90 | 0.00774669 | 36293.4 | 36.97 | 20.08 | 0.00774669 | 57057.9 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 64262.482 | -999.000 | 5.565044 | 0.00183786 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1195 | 1004.8586 | 1.1870 | ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 5.565044 | 6.60565594 | 4197.9300 | 999.8980 | 21.53166916 | 15.03 | 6.70 | 8.33 | 752935.70 | 8.5349 | 8.534764 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | unknown | unknown | unknown | 8/21 15:00:00 | Sensible | 64262.48 | 60501.94 | 1.0000 | 6.60565594 | 5.565044 | 21.69 | 15.64 | 0.00875736 | 44050.6 | 12.80 | 11.97 | 0.00850000 | 34322.2 | 1.83767706 | 6.70 | 15.03 | 8.33 | 0.000 | 64262.48 | 29.40 | 0.00882150 | 18.34 | 0.00000000 | 0.0000 | 21.11 | 0.00875736 | 21.11 | 0.00875736 | 55.3623 | 56028.35 | 0.00 | 65190.74 | 63826.20 | 6.60565594 | 21.69 | 15.78 | 0.00875736 | 44050.6 | 12.23 | 12.04 | 0.00867550 | 34181.7 | |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 26967.919 | 26967.919 | 1.179535 | 0.00023593 | 770.559 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 5.565044 | 6.60565594 | 4197.9300 | 999.8980 | 3.28047697 | 54.44 | 82.22 | 27.78 | 382564.29 | 7.0493 | 7.191120 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 26967.92 | 26967.92 | 1.0000 | 1.40009672 | 1.179535 | 21.11 | 14.52 | 0.00774729 | 40892.6 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.23590305 | 60.00 | 32.22 | 27.78 | 0.000 | 26967.92 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.11 | 0.00774729 | 21.11 | 0.00774729 | 49.0538 | 26968.07 | 0.00 | 29072.33 | 29072.33 | 1.40009672 | 16.60 | 12.90 | 0.00774729 | 36294.9 | 36.97 | 20.08 | 0.00774729 | 57059.4 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11674.441 | -999.000 | 1.062091 | 0.00033388 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7768 | 1004.8586 | 1.1870 | ROOM_5_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.062091 | 1.26069220 | 4197.9300 | 999.8980 | 21.53166916 | 15.03 | 6.70 | 8.33 | 752935.70 | 1.5505 | 1.550494 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | unknown | unknown | unknown | 8/21 10:00:00 | Sensible | 11674.44 | 11472.23 | 1.0000 | 1.26069220 | 1.062091 | 21.69 | 15.48 | 0.00857298 | 43582.5 | 12.80 | 11.97 | 0.00850000 | 34322.2 | 0.33384723 | 6.70 | 15.03 | 8.33 | 0.000 | 11674.44 | 25.45 | 0.00881519 | 17.01 | 0.00000000 | 0.0000 | 21.11 | 0.00857298 | 21.11 | 0.00857298 | 54.2117 | 10693.39 | 0.00 | 11846.72 | 11846.72 | 1.26069220 | 21.69 | 15.62 | 0.00857298 | 43582.5 | 12.49 | 12.04 | 0.00857298 | 34185.5 | |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4658.619 | 4658.619 | 0.203759 | 0.00004076 | 133.113 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | ROOM_5_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.062091 | 1.26069220 | 4197.9300 | 999.8980 | 3.28047697 | 54.44 | 82.22 | 27.78 | 382564.29 | 1.2177 | 1.242242 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 4658.62 | 4658.62 | 1.0000 | 0.24186007 | 0.203759 | 21.11 | 14.50 | 0.00772533 | 40836.6 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.04075148 | 60.00 | 32.22 | 27.78 | 0.000 | 4658.62 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.11 | 0.00772533 | 21.11 | 0.00772533 | 48.9170 | 4658.67 | 0.00 | 5022.14 | 5022.14 | 0.24186007 | 16.60 | 12.88 | 0.00772533 | 36239.3 | 36.97 | 20.06 | 0.00772533 | 57004.0 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10687.837 | -999.000 | 0.970524 | 0.00030567 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7894 | 1004.8586 | 1.1870 | ROOM_6_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.970524 | 1.15200247 | 4197.9300 | 999.8980 | 21.53166916 | 15.03 | 6.70 | 8.33 | 752935.70 | 1.4195 | 1.419462 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | unknown | unknown | unknown | 8/21 09:00:00 | Sensible | 10687.84 | 10485.79 | 1.0000 | 1.15200247 | 0.970524 | 21.69 | 15.48 | 0.00857979 | 43599.8 | 12.80 | 11.97 | 0.00850000 | 34322.2 | 0.30563389 | 6.70 | 15.03 | 8.33 | 0.000 | 10687.84 | 23.68 | 0.00881240 | 16.40 | 0.00000000 | 0.0000 | 21.11 | 0.00857979 | 21.11 | 0.00857979 | 54.2541 | 9771.45 | 0.00 | 10845.28 | 10845.28 | 1.15200247 | 21.69 | 15.63 | 0.00857979 | 43599.8 | 12.47 | 12.04 | 0.00857979 | 34185.5 | |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4661.894 | 4661.894 | 0.203902 | 0.00004078 | 133.207 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | ROOM_6_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.970524 | 1.15200247 | 4197.9300 | 999.8980 | 3.28047697 | 54.44 | 82.22 | 27.78 | 382564.29 | 1.2186 | 1.243116 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 4661.89 | 4661.89 | 1.0000 | 0.24203006 | 0.203902 | 21.11 | 14.50 | 0.00772554 | 40837.2 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.04078012 | 60.00 | 32.22 | 27.78 | 0.000 | 4661.89 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.11 | 0.00772554 | 21.11 | 0.00772554 | 48.9182 | 4661.95 | 0.00 | 5025.67 | 5025.67 | 0.24203006 | 16.60 | 12.88 | 0.00772554 | 36239.8 | 36.97 | 20.06 | 0.00772554 | 57004.5 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11871.415 | 11871.415 | 0.824615 | 0.00010386 | 272.775 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.28047697 | 54.44 | 82.22 | 27.78 | 382564.29 | 3.1031 | 3.165568 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 11871.41 | 11871.41 | 1.0000 | 0.97881036 | 0.824615 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.10384572 | 60.00 | 32.22 | 27.78 | 0.000 | 11871.41 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00779186 | 21.00 | 0.00779186 | 49.6699 | 7581.23 | 0.00 | 11935.11 | 11935.11 | 0.97881036 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 28.56 | 17.55 | 0.00800000 | 49128.2 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3362.718 | -999.000 | 0.306756 | 0.00009617 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7584 | 1004.8586 | 1.1870 | ROOM_1_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.306756 | 0.36411693 | 4197.9300 | 999.8980 | 21.53166916 | 15.03 | 6.70 | 8.33 | 752935.70 | 0.4466 | 0.446606 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | unknown | unknown | unknown | 8/21 16:30:00 | Sensible | 3362.72 | 3312.23 | 1.0000 | 0.36411693 | 0.306756 | 21.69 | 15.47 | 0.00856311 | 43557.5 | 12.80 | 11.97 | 0.00850000 | 34322.2 | 0.09616169 | 6.70 | 15.03 | 8.33 | 0.000 | 3362.72 | 28.36 | 0.00881983 | 18.00 | 0.00000000 | 0.0000 | 21.11 | 0.00856311 | 21.11 | 0.00856311 | 54.1500 | 3088.50 | 0.00 | 3412.47 | 3412.47 | 0.36411693 | 21.69 | 15.61 | 0.00856311 | 43557.5 | 12.51 | 12.04 | 0.00856311 | 34185.6 | |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1427.705 | 1427.705 | 0.062445 | 0.00001249 | 40.793 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | ROOM_1_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.306756 | 0.36411693 | 4197.9300 | 999.8980 | 3.28047697 | 54.44 | 82.22 | 27.78 | 382564.29 | 0.3732 | 0.380704 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1427.71 | 1427.71 | 1.0000 | 0.07412174 | 0.062445 | 21.11 | 14.55 | 0.00777374 | 40959.6 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.01248892 | 60.00 | 32.22 | 27.78 | 0.000 | 1427.71 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.11 | 0.00777374 | 21.11 | 0.00777374 | 49.2197 | 1427.72 | 0.00 | 1539.11 | 1539.11 | 0.07412174 | 16.60 | 12.93 | 0.00777374 | 36361.9 | 36.97 | 20.10 | 0.00777374 | 57126.5 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3031.088 | -999.000 | 0.275957 | 0.00008669 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7718 | 1004.8586 | 1.1870 | ROOM_2_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.275957 | 0.32755854 | 4197.9300 | 999.8980 | 21.53166916 | 15.03 | 6.70 | 8.33 | 752935.70 | 0.4026 | 0.402562 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | unknown | unknown | unknown | 8/21 17:00:00 | Sensible | 3031.09 | 2980.47 | 1.0000 | 0.32755854 | 0.275957 | 21.69 | 15.48 | 0.00857032 | 43575.8 | 12.80 | 11.97 | 0.00850000 | 34322.2 | 0.08667827 | 6.70 | 15.03 | 8.33 | 0.000 | 3031.09 | 27.94 | 0.00881916 | 17.86 | 0.00000000 | 0.0000 | 21.11 | 0.00857032 | 21.11 | 0.00857032 | 54.1950 | 2778.40 | 0.00 | 3075.85 | 3075.85 | 0.32755854 | 21.69 | 15.62 | 0.00857032 | 43575.8 | 12.49 | 12.04 | 0.00857032 | 34185.6 | |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1429.357 | 1429.357 | 0.062517 | 0.00001250 | 40.841 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | ROOM_2_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.275957 | 0.32755854 | 4197.9300 | 999.8980 | 3.28047697 | 54.44 | 82.22 | 27.78 | 382564.29 | 0.3736 | 0.381145 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1429.36 | 1429.36 | 1.0000 | 0.07420746 | 0.062517 | 21.11 | 14.55 | 0.00777401 | 40960.3 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.01250336 | 60.00 | 32.22 | 27.78 | 0.000 | 1429.36 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.11 | 0.00777401 | 21.11 | 0.00777401 | 49.2214 | 1429.37 | 0.00 | 1540.89 | 1540.89 | 0.07420746 | 16.60 | 12.93 | 0.00777401 | 36362.6 | 36.97 | 20.10 | 0.00777401 | 57127.2 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 18612.379 | -999.000 | 1.679889 | 0.00053230 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8309 | 1004.8586 | 1.1870 | ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 1.679889 | 1.99401223 | 4197.9300 | 999.8980 | 21.53166916 | 15.03 | 6.70 | 8.33 | 752935.70 | 2.4720 | 2.471928 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | unknown | unknown | unknown | 8/21 13:40:00 | Sensible | 18612.38 | 18164.43 | 1.0000 | 1.99401223 | 1.679889 | 21.69 | 15.50 | 0.00860211 | 43656.3 | 12.80 | 11.97 | 0.00850000 | 34322.2 | 0.53224744 | 6.70 | 15.03 | 8.33 | 0.000 | 18612.38 | 29.23 | 0.00882122 | 18.29 | 0.00000000 | 0.0000 | 21.11 | 0.00860211 | 21.11 | 0.00860211 | 54.3940 | 16913.13 | 0.00 | 18885.04 | 18885.04 | 1.99401223 | 21.69 | 15.65 | 0.00860211 | 43656.3 | 12.41 | 12.04 | 0.00860211 | 34185.5 | |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6868.363 | 6868.363 | 0.300410 | 0.00006009 | 196.247 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 1.679889 | 1.99401223 | 4197.9300 | 999.8980 | 3.28047697 | 54.44 | 82.22 | 27.78 | 382564.29 | 1.7953 | 1.831481 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 6868.36 | 6868.36 | 1.0000 | 0.35658369 | 0.300410 | 21.11 | 14.55 | 0.00778303 | 40983.3 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.06008131 | 60.00 | 32.22 | 27.78 | 0.000 | 6868.36 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.11 | 0.00778303 | 21.11 | 0.00778303 | 49.2776 | 6868.42 | 0.00 | 7404.31 | 7404.31 | 0.35658369 | 16.60 | 12.94 | 0.00778303 | 36385.4 | 36.97 | 20.11 | 0.00778303 | 57150.0 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10447.659 | 10447.659 | 1.086187 | 0.00009140 | 227.939 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.28047697 | 54.44 | 82.22 | 27.78 | 382564.29 | 2.7310 | 2.785917 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 10447.66 | 10447.66 | 1.0000 | 1.28929405 | 1.086187 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.09139136 | 60.00 | 32.22 | 27.78 | 0.000 | 10447.66 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00783265 | 21.00 | 0.00783265 | 49.9268 | 4796.26 | 0.00 | 10505.54 | 10505.54 | 1.28929405 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 24.59 | 16.17 | 0.00800000 | 45083.0 | |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10820.470 | 10820.470 | 1.137720 | 0.00009466 | 235.804 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.28047697 | 54.44 | 82.22 | 27.78 | 382564.29 | 2.8284 | 2.885328 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:10:00 | Sensible | 10820.47 | 10820.47 | 1.0000 | 1.35046356 | 1.137720 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.09465254 | 60.00 | 32.22 | 27.78 | 0.000 | 10820.47 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00783610 | 21.00 | 0.00783610 | 49.9488 | 4901.05 | 0.00 | 10880.43 | 10880.43 | 1.35046356 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 24.50 | 16.14 | 0.00800000 | 44991.5 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7057.594 | 7057.594 | 1.165192 | 0.00006174 | 148.435 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.28047697 | 54.44 | 82.22 | 27.78 | 382564.29 | 1.8448 | 1.881940 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | Sensible | 7057.59 | 7057.59 | 1.0000 | 1.38307250 | 1.165192 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.06173661 | 60.00 | 32.22 | 27.78 | 0.000 | 7057.59 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 19.93 | 0.00540943 | 21.00 | 0.00540943 | 34.6207 | 1026.40 | 0.00 | 7097.14 | 7097.14 | 1.38307250 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.63 | 15.09 | 0.00800000 | 42066.2 | |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7206.925 | 7206.925 | 0.412515 | 0.00006305 | 171.546 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.28047697 | 54.44 | 82.22 | 27.78 | 382564.29 | 1.8838 | 1.921760 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:10:00 | Sensible | 7206.92 | 7206.92 | 1.0000 | 0.48965162 | 0.412515 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.06304289 | 60.00 | 32.22 | 27.78 | 0.000 | 7206.92 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00786026 | 21.00 | 0.00786026 | 50.1007 | 5060.53 | 0.00 | 7245.20 | 7245.20 | 0.48965162 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 31.11 | 18.41 | 0.00800000 | 51731.4 | |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 45447.837 | -999.000 | 2.051317 | 0.00129980 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2387 | 1004.8586 | 1.1870 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.43480905 | 4197.9300 | 999.8980 | 21.53166916 | 15.03 | 6.70 | 8.33 | 752935.70 | 6.0361 | 6.036085 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | Sensible | 45447.84 | 43504.21 | 1.0000 | 2.43489466 | 2.051317 | 29.40 | 18.34 | 0.00882150 | 52086.5 | 11.92 | 11.61 | 0.00850000 | 33421.2 | 1.29966980 | 6.70 | 15.03 | 8.33 | 2195.006 | 43252.83 | 29.40 | 0.00882150 | 18.34 | 2.05124512 | 99.9965 | 21.11 | 0.00860263 | 21.11 | 0.00860544 | 54.4137 | 192922.69 | 0.00 | 45917.97 | 43441.59 | 2.43489466 | 29.40 | 18.50 | 0.00882150 | 52086.5 | 11.93 | 11.66 | 0.00841841 | 33228.2 | |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 15340.965 | 15340.965 | 0.615395 | 0.00013421 | 261.904 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.43480905 | 4197.9300 | 999.8980 | 3.28047697 | 54.44 | 82.22 | 27.78 | 382564.29 | 4.0100 | 4.090739 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 15340.96 | 15340.96 | 1.0000 | 0.73046840 | 0.615395 | -4.20 | -4.20 | 0.00269032 | 2487.0 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 0.13419576 | 60.00 | 32.22 | 27.78 | 0.000 | 15340.96 | -4.20 | 0.00269032 | -4.20 | 2.05124512 | 333.3216 | 21.11 | 0.00774601 | 21.11 | 0.00774716 | 49.0530 | 82214.19 | 0.00 | 14133.30 | 14133.30 | 0.73046840 | 2.80 | 0.07 | 0.00269032 | 9555.9 | 21.96 | 9.93 | 0.00269032 | 28904.2 | |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 481649.266 | -999.000 | 22.591451 | 0.01377511 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.9559 | 1004.8586 | 1.1870 | VAV WITH REHEAT FAN | Fan:VariableVolume | 22.591451 | 26.81584376 | 4197.9300 | 999.8980 | 21.53166916 | 15.03 | 6.70 | 8.33 | 752935.70 | 63.9695 | 63.969508 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | Sensible | 481649.27 | 432061.98 | 1.0000 | 26.81584376 | 22.591451 | 26.78 | 17.79 | 0.00920731 | 50398.3 | 10.95 | 10.95 | 0.00850000 | 32437.0 | 13.77370282 | 6.70 | 15.03 | 8.33 | 50619.277 | 431029.99 | 29.40 | 0.00882150 | 18.34 | 11.66146000 | 51.6189 | 23.99 | 0.00961928 | 23.99 | 0.00957604 | 50.7488 | 306177.77 | 0.00 | 487018.06 | 422262.48 | 26.81584376 | 26.78 | 17.94 | 0.00920731 | 50398.3 | 11.37 | 11.25 | 0.00824983 | 32236.8 | |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 168952.241 | 168952.241 | 6.777435 | 0.00147807 | 2884.391 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | VAV WITH REHEAT FAN | Fan:VariableVolume | 22.591451 | 26.81584376 | 4197.9300 | 999.8980 | 3.28047697 | 54.44 | 82.22 | 27.78 | 382564.29 | 44.1631 | 45.051898 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:30:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:30:00 | Sensible | 168952.24 | 168952.24 | 1.0000 | 8.04475313 | 6.777435 | -4.20 | -4.20 | 0.00269032 | 2487.0 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 1.47791713 | 60.00 | 32.22 | 27.78 | 0.000 | 168952.24 | -4.20 | 0.00269032 | -4.20 | 11.66146000 | 172.0630 | 18.45 | 0.00706731 | 21.21 | 0.00661006 | 41.6679 | 47220.32 | 0.00 | 155652.07 | 155652.07 | 8.04475313 | 2.80 | 0.07 | 0.00269032 | 9555.9 | 21.96 | 9.93 | 0.00269032 | 28904.2 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:35
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - | |||
VAV WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 22.59 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | VAV WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000610 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LAUNDRY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CAFE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001448 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_3 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
KITCHEN_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003556 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 56.33 | 7634.83 | 0.00 |
RETAIL_1_FLR_1 | 967.17 | 8035.83 | 538.33 |
RETAIL_2_FLR_1 | 368.17 | 7658.83 | 0.00 |
MECH_FLR_1 | 39.17 | 8596.00 | 35.67 |
STORAGE_FLR_1 | 119.50 | 8735.50 | 119.50 |
LAUNDRY_FLR_1 | 7308.83 | 3229.33 | 2579.83 |
CAFE_FLR_1 | 1138.83 | 6900.00 | 44.50 |
LOBBY_FLR_1 | 1043.67 | 6487.50 | 32.67 |
ROOM_1_FLR_3 | 1008.50 | 8433.50 | 974.33 |
ROOM_2_FLR_3 | 1775.33 | 8169.83 | 1479.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 201.50 | 8747.17 | 201.33 |
ROOM_5_FLR_3 | 980.67 | 8443.33 | 977.83 |
ROOM_6_FLR_3 | 1533.17 | 8408.67 | 1449.50 |
CORRIDOR_FLR_3 | 24.17 | 8755.33 | 24.17 |
ROOM_1_FLR_6 | 1827.67 | 8320.33 | 1741.17 |
ROOM_2_FLR_6 | 2663.83 | 8089.00 | 2323.00 |
ROOM_3_MULT9_FLR_6 | 596.33 | 8214.67 | 523.00 |
BANQUET_FLR_6 | 4423.17 | 1732.00 | 39.50 |
DINING_FLR_6 | 5855.83 | 765.83 | 21.33 |
KITCHEN_FLR_6 | 8532.33 | 6234.83 | 6218.83 |
CORRIDOR_FLR_6 | 165.83 | 8345.00 | 45.50 |
Facility | 8757.00 | 8760.00 | 7073.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4.50 | 3.17 | 4.50 | 3.17 |
ROOM_2_FLR_3 | 9.00 | 6.83 | 9.00 | 6.83 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 12.17 | 0.00 | 12.17 |
ROOM_5_FLR_3 | 5.17 | 0.00 | 5.17 | 0.00 |
ROOM_6_FLR_3 | 12.17 | 7.33 | 12.17 | 7.33 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 7.33 | 6.67 | 7.33 | 6.67 |
ROOM_2_FLR_6 | 16.00 | 13.33 | 16.00 | 13.33 |
ROOM_3_MULT9_FLR_6 | 1.83 | 1.67 | 1.83 | 1.67 |
BANQUET_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 18.83 | 30.00 | 18.83 | 30.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:35
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.76 | 106.50 | 4826.41 | 1.001 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 3.130 | 0.062 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 1.424 | 0.021 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.501 | 0.023 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.516 | 0.023 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 23.331 | 0.067 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.52 | 142.30 | 748.35 | 4.453 | 0.049 | 0.000 | 0.000 |
LOBBY_FLR_1 | 244.96 | 422.44 | 5183.56 | 1.880 | 0.020 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.355 | 0.080 | 0.000 | 0.042 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.356 | 0.081 | 0.000 | 0.040 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.403 | 0.036 | 0.000 | 0.075 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.355 | 0.080 | 0.000 | 0.042 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.355 | 0.080 | 0.000 | 0.048 |
CORRIDOR_FLR_3 | 12.15 | 20.96 | 1186.91 | 0.634 | 0.010 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.355 | 0.080 | 0.000 | 0.049 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.356 | 0.081 | 0.000 | 0.042 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.403 | 0.066 | 0.000 | 0.079 |
BANQUET_FLR_6 | 144.91 | 249.90 | 1010.89 | 4.756 | 0.023 | 0.000 | 0.000 |
DINING_FLR_6 | 144.91 | 249.90 | 1010.89 | 5.184 | 0.023 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 22.117 | 0.067 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.86 | 22.18 | 1256.16 | 1.199 | 0.016 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.76 | 106.50 | 4826.41 | 0.966 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 3.027 | 0.001 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 1.373 | 0.000 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.486 | 0.000 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.501 | 0.000 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 19.394 | 0.001 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.52 | 142.30 | 748.35 | 4.294 | 0.001 | 0.000 | 0.000 |
LOBBY_FLR_1 | 244.96 | 422.44 | 5183.56 | 1.806 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
CORRIDOR_FLR_3 | 12.15 | 20.96 | 1186.91 | 0.616 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.000 | 0.001 | 0.000 | 0.000 |
BANQUET_FLR_6 | 144.91 | 249.90 | 1010.89 | 3.832 | 0.000 | 0.000 | 0.000 |
DINING_FLR_6 | 144.91 | 249.90 | 1010.89 | 4.019 | 0.000 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 13.231 | 0.001 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.86 | 22.18 | 1256.16 | 1.164 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:35
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | VAV WITH REHEAT | 61.76 | 106.50 | 4826.41 | 1978.83 | 0.0000 | 0.854 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 6.28 | 10.83 | 265.76 | 67.07 | 0.0000 | 0.079 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 7.27 | 12.54 | 307.76 | 77.67 | 0.0000 | 0.092 |
MECH_FLR_1 | VAV WITH REHEAT | 1.54 | 2.65 | 650.80 | 164.24 | 0.0000 | 0.000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 1.18 | 2.04 | 375.47 | 94.76 | 0.0000 | 0.058 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 4.87 | 8.40 | 309.22 | 78.04 | 0.0000 | 0.000 |
CAFE_FLR_1 | VAV WITH REHEAT | 82.52 | 142.30 | 748.35 | 188.86 | 0.0000 | 0.676 |
LOBBY_FLR_1 | VAV WITH REHEAT | 244.96 | 422.44 | 5183.56 | 1308.19 | 0.0000 | 1.894 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 1.50 | 74.75 | 24.52 | 0.0000 | 0.837 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.837 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 12.15 | 20.96 | 1186.91 | 389.40 | 0.0000 | 0.475 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.015 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.015 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.099 |
BANQUET_FLR_6 | VAV WITH REHEAT | 144.91 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
DINING_FLR_6 | VAV WITH REHEAT | 144.91 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 12.90 | 22.24 | 314.87 | 103.30 | 0.0000 | 0.367 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 12.86 | 22.18 | 1256.16 | 412.12 | 0.0000 | 0.126 |
Total Facility | 872.83 | 1604.23 | 35184.81 | 11345.29 | 0.0000 | 137.584 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 41514557.94 | 0.00 | 41514557.94 | 0.00 | 41514557.94 | 26946214.98 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_1_FLR_1 | 7195756.99 | 0.00 | 7195756.99 | 142406.96 | 7338163.95 | 2498216.28 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_2_FLR_1 | 3774271.31 | 0.00 | 3774271.31 | 54969.27 | 3829240.58 | 2892943.94 | 0.00 | 0.00 | 8760.00 | 0.00 |
MECH_FLR_1 | 2815957.39 | 0.00 | 2815957.39 | 129914.69 | 2945872.08 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
STORAGE_FLR_1 | 1673168.38 | 0.00 | 1673168.38 | 74953.62 | 1748122.00 | 1821682.01 | 8760.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 62066829.84 | 0.00 | 62066829.84 | 177391.88 | 62244221.72 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
CAFE_FLR_1 | 28706709.60 | 0.00 | 28706709.60 | 314798.65 | 29021508.25 | 21330615.53 | 0.00 | 0.00 | 8760.00 | 0.00 |
LOBBY_FLR_1 | 83783214.31 | 0.00 | 83783214.31 | 899451.65 | 84682665.96 | 59728886.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
ROOM_1_FLR_3 | 1460156.71 | 43586.13 | 1503742.85 | 82657.34 | 1586400.19 | 1946875.62 | 2190.00 | 6018.50 | 551.50 | 0.00 |
ROOM_2_FLR_3 | 1459985.63 | 41153.94 | 1501139.58 | 82651.04 | 1583790.62 | 1946647.51 | 2190.00 | 6122.98 | 447.02 | 0.00 |
ROOM_3_MULT19_FLR_3 | 1099911.97 | 66.61 | 1099978.58 | 23062.33 | 1123040.90 | 26397887.27 | 8395.00 | 365.00 | 0.00 | 365.83 |
ROOM_4_MULT19_FLR_3 | 19803829.30 | 48066.93 | 19851896.23 | 23068.63 | 19874964.86 | 26405105.73 | 2190.00 | 6028.17 | 541.83 | 0.00 |
ROOM_5_FLR_3 | 1460156.71 | 43546.31 | 1503703.03 | 82657.34 | 1586360.37 | 1946875.62 | 2190.00 | 6018.50 | 551.50 | 0.00 |
ROOM_6_FLR_3 | 1459985.63 | 48793.52 | 1508779.15 | 82651.04 | 1591430.19 | 1946647.51 | 2190.00 | 6019.17 | 550.83 | 0.00 |
CORRIDOR_FLR_3 | 26005057.44 | 0.00 | 26005057.44 | 99949.36 | 26105006.80 | 14972100.18 | 0.00 | 0.00 | 8760.00 | 0.00 |
ROOM_1_FLR_6 | 365039.18 | 50872.72 | 415911.90 | 82674.64 | 498586.54 | 486718.90 | 2074.00 | 6019.43 | 666.58 | 0.00 |
ROOM_2_FLR_6 | 364996.41 | 42956.52 | 407952.93 | 82668.33 | 490621.26 | 486661.88 | 2105.15 | 6165.50 | 489.35 | 0.00 |
ROOM_3_MULT9_FLR_6 | 2345190.31 | 50798.26 | 2395988.57 | 42299.24 | 2438287.81 | 3126920.42 | 2190.00 | 6017.83 | 552.17 | 0.00 |
BANQUET_FLR_6 | 41157191.91 | 0.00 | 41157191.91 | 201870.69 | 41359062.60 | 37458366.31 | 3745.91 | 166.68 | 4847.41 | 0.00 |
DINING_FLR_6 | 44855404.40 | 0.00 | 44855404.40 | 201870.69 | 45057275.09 | 37458366.31 | 2490.13 | 208.01 | 6061.86 | 0.00 |
KITCHEN_FLR_6 | 59648498.48 | 0.00 | 59648498.48 | 180721.07 | 59829219.55 | 11584760.86 | 0.00 | 0.00 | 8760.00 | 0.00 |
CORRIDOR_FLR_6 | 13013445.54 | 0.00 | 13013445.54 | 176879.70 | 13190325.25 | 3961413.96 | 0.00 | 0.00 | 8760.00 | 0.00 |
Total Facility | 0.21E+10 | 4917482.31 | 0.21E+10 | 8329482.29 | 0.21E+10 | 0.43E+10 | 8760.00 | 6685.45 | 8760.00 | 365.83 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 1.3164 | 0.0000 | 1.3164 | 0.0000 | 1.3164 | 0.8545 | 0.00 | 0.00 | 8760.00 |
RETAIL_1_FLR_1 | 0.2282 | 0.0000 | 0.2282 | 0.0045 | 0.2327 | 0.0792 | 0.00 | 0.00 | 8760.00 |
RETAIL_2_FLR_1 | 0.1197 | 0.0000 | 0.1197 | 0.0017 | 0.1214 | 0.0917 | 0.00 | 0.00 | 8760.00 |
MECH_FLR_1 | 0.0893 | 0.0000 | 0.0893 | 0.0041 | 0.0934 | 0.0000 | 0.00 | 0.00 | 8760.00 |
STORAGE_FLR_1 | 0.0531 | 0.0000 | 0.0531 | 0.0024 | 0.0554 | 0.0578 | 8760.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 1.9681 | 0.0000 | 1.9681 | 0.0056 | 1.9738 | 0.0000 | 0.00 | 0.00 | 8760.00 |
CAFE_FLR_1 | 0.9103 | 0.0000 | 0.9103 | 0.0100 | 0.9203 | 0.6764 | 0.00 | 0.00 | 8760.00 |
LOBBY_FLR_1 | 2.6567 | 0.0000 | 2.6567 | 0.0285 | 2.6853 | 1.8940 | 0.00 | 0.00 | 8760.00 |
ROOM_1_FLR_3 | 0.0463 | 0.0014 | 0.0477 | 0.0026 | 0.0503 | 0.0617 | 2190.00 | 6018.50 | 551.50 |
ROOM_2_FLR_3 | 0.0463 | 0.0013 | 0.0476 | 0.0026 | 0.0502 | 0.0617 | 2190.00 | 6122.98 | 447.02 |
ROOM_4_MULT19_FLR_3 | 0.6280 | 0.0015 | 0.6295 | 0.0007 | 0.6302 | 0.8373 | 2190.00 | 6028.17 | 541.83 |
ROOM_5_FLR_3 | 0.0463 | 0.0014 | 0.0477 | 0.0026 | 0.0503 | 0.0617 | 2190.00 | 6018.50 | 551.50 |
ROOM_6_FLR_3 | 0.0463 | 0.0015 | 0.0478 | 0.0026 | 0.0505 | 0.0617 | 2190.00 | 6019.17 | 550.83 |
CORRIDOR_FLR_3 | 0.8246 | 0.0000 | 0.8246 | 0.0032 | 0.8278 | 0.4748 | 0.00 | 0.00 | 8760.00 |
ROOM_1_FLR_6 | 0.0116 | 0.0016 | 0.0132 | 0.0026 | 0.0158 | 0.0154 | 2074.00 | 6019.43 | 666.58 |
ROOM_2_FLR_6 | 0.0116 | 0.0014 | 0.0129 | 0.0026 | 0.0156 | 0.0154 | 2105.15 | 6165.50 | 489.35 |
ROOM_3_MULT9_FLR_6 | 0.0744 | 0.0016 | 0.0760 | 0.0013 | 0.0773 | 0.0992 | 2190.00 | 6017.83 | 552.17 |
BANQUET_FLR_6 | 1.3051 | 0.0000 | 1.3051 | 0.0064 | 1.3115 | 1.1878 | 3745.91 | 166.68 | 4847.41 |
DINING_FLR_6 | 1.4224 | 0.0000 | 1.4224 | 0.0064 | 1.4288 | 1.1878 | 2490.13 | 208.01 | 6061.86 |
KITCHEN_FLR_6 | 1.8914 | 0.0000 | 1.8914 | 0.0057 | 1.8972 | 0.3674 | 0.00 | 0.00 | 8760.00 |
CORRIDOR_FLR_6 | 0.4127 | 0.0000 | 0.4127 | 0.0056 | 0.4183 | 0.1256 | 0.00 | 0.00 | 8760.00 |
Total Facility | 64.8311 | 0.1558 | 64.9869 | 0.2085 | 65.1954 | 73.9670 | 8760.00 | 6685.45 | 8760.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
FLR_3_DOAS | 42013749.02 | 369840.95 | 42383589.97 | 64690340.46 | 8754.17 | 4.95 | 0.88 | 0.00 |
VAV WITH REHEAT | 0.59E+09 | 0.00 | 0.59E+09 | 0.22E+09 | 0.00 | 0.00 | 8760.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
FLR_3_DOAS | 1.3322 | 0.0117 | 1.3440 | 2.0513 | 8754.17 | 4.95 | 0.88 |
VAV WITH REHEAT | 18.5952 | 0.0000 | 18.5952 | 6.9969 | 0.00 | 0.00 | 8760.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
FLR_3_DOAS | 0.00 | 0.00 | 0.00 | 0.00 | 6935.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
VAV WITH REHEAT | 0.00 | 0.00 | 5342.21 | 0.00 | 0.00 | 0.00 | 3417.79 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
FLR_3_DOAS | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.6828 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
VAV WITH REHEAT | 0.0000 | 0.0000 | 18.7453 | 0.0000 | 0.0000 | 0.0000 | 18.3659 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:35
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1333 |
Defaulted Fields | 1182 |
Fields with Defaults | 4000 |
Autosized Fields | 349 |
Autosizable Fields | 402 |
Autocalculated Fields | 280 |
Autocalculatable Fields | 539 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:21:35
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 4606.71 | 66637.43 | 05-AUG-05:00 | 335399.91 | 10-AUG-18:10 |
Electricity:Building | 2448.13 | 31038.54 | 01-JUL-05:00 | 151313.73 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 304.40 | 3493.55 | 02-JAN-02:10 | 22822.84 | 02-JAN-20:10 |
Electricity:SpaceType:GENERAL | 2441.03 | 30897.39 | 01-JUL-05:00 | 151072.40 | 02-JAN-20:10 |
InteriorLights:Electricity | 782.86 | 6695.42 | 01-JUL-05:00 | 64632.59 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 161.29 | 1465.65 | 02-JAN-02:10 | 13190.31 | 02-JAN-20:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 782.86 | 6695.42 | 01-JUL-05:00 | 64632.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 782.86 | 6695.42 | 01-JUL-05:00 | 64632.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 161.29 | 1465.65 | 02-JAN-02:10 | 13190.31 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 782.86 | 6695.42 | 01-JUL-05:00 | 64632.59 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 17.49 | 210.74 | 02-JAN-02:10 | 1283.20 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 7.31 | 66.40 | 02-JAN-02:10 | 597.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 7.31 | 66.40 | 02-JAN-02:10 | 597.59 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 20.26 | 244.03 | 02-JAN-02:10 | 1485.95 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 8.46 | 76.89 | 02-JAN-02:10 | 692.02 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 8.46 | 76.89 | 02-JAN-02:10 | 692.02 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 20.84 | 252.75 | 02-JAN-02:10 | 1523.62 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.37 | 76.02 | 02-JAN-02:10 | 684.18 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.37 | 76.02 | 02-JAN-02:10 | 684.18 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 6.68 | 78.96 | 02-JAN-02:10 | 493.99 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 3.08 | 27.98 | 02-JAN-02:10 | 251.84 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 3.08 | 27.98 | 02-JAN-02:10 | 251.84 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 71.91 | 998.82 | 02-JAN-02:10 | 4897.88 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 3.98 | 36.12 | 02-JAN-02:10 | 325.08 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 3.98 | 36.12 | 02-JAN-02:10 | 325.08 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 28.58 | 293.96 | 03-JUN-05:00 | 2666.80 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 14.24 | 83.19 | 01-JAN-13:10 | 1701.53 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 | 14.24 | 83.19 | 01-JAN-13:10 | 1701.53 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 259.17 | 3068.93 | 01-JUL-05:00 | 19534.01 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 110.17 | 957.52 | 01-JUL-05:00 | 9504.80 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 110.17 | 957.52 | 01-JUL-05:00 | 9504.80 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 19.72 | 257.38 | 01-JAN-02:10 | 1438.51 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 19.72 | 257.35 | 01-JAN-02:10 | 1438.34 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 305.38 | 4267.82 | 01-JAN-02:10 | 22404.45 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 110.39 | 934.58 | 01-JAN-02:10 | 8496.21 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 110.39 | 934.58 | 01-JAN-02:10 | 8496.21 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 305.47 | 4268.99 | 01-JAN-02:10 | 22410.58 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 110.42 | 934.84 | 01-JAN-02:10 | 8498.53 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 110.42 | 934.84 | 01-JAN-02:10 | 8498.53 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 19.72 | 257.38 | 01-JAN-02:10 | 1438.51 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 19.72 | 257.35 | 01-JAN-02:10 | 1438.34 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 4.93 | 64.34 | 01-JAN-02:10 | 359.63 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 2.31 | 19.57 | 01-JAN-02:10 | 177.88 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 2.31 | 19.57 | 01-JAN-02:10 | 177.88 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 4.93 | 64.34 | 01-JAN-02:10 | 359.59 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 2.31 | 19.56 | 01-JAN-02:10 | 177.86 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 2.31 | 19.56 | 01-JAN-02:10 | 177.86 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 36.17 | 505.54 | 01-JAN-02:10 | 2653.88 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 13.08 | 110.70 | 01-JAN-02:10 | 1006.40 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 13.08 | 110.70 | 01-JAN-02:10 | 1006.40 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 206.86 | 2448.50 | 10-JUN-05:00 | 9735.93 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 31.01 | 199.20 | 10-JUN-05:00 | 2988.03 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 31.01 | 199.20 | 10-JUN-05:00 | 2988.03 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 206.86 | 2448.50 | 10-JUN-05:00 | 9735.93 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 31.01 | 199.20 | 10-JUN-05:00 | 2988.03 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 | 31.01 | 199.20 | 10-JUN-05:00 | 2988.03 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 453.81 | 6249.79 | 02-JAN-02:10 | 18934.39 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 12.97 | 117.87 | 02-JAN-02:10 | 1060.81 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 12.97 | 117.87 | 02-JAN-02:10 | 1060.81 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1658.18 | 24201.97 | 02-JAN-02:10 | 89171.45 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 1658.18 | 24201.97 | 02-JAN-02:10 | 89171.45 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 433.74 | 5990.78 | 01-JAN-00:10 | 16487.34 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 410.33 | 5248.28 | 01-JAN-00:10 | 15744.84 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
Refrigeration:Electricity | 61.96 | 1115.58 | 11-FEB-23:30 | 3259.19 | 29-AUG-06:50 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
Electricity:Plant | 531.51 | 2756.46 | 17-OCT-02:20 | 140664.97 | 10-AUG-18:10 |
LowTempRefrigeration:Refrigeration:Electricity | 20.46 | 0.00 | 01-JAN-11:10 | 1891.74 | 13-AUG-10:50 |
MedTempRefrigeration:Refrigeration:Electricity | 34.41 | 978.20 | 12-FEB-04:10 | 1201.92 | 30-AUG-13:30 |
Fans:Electricity | 499.01 | 11724.09 | 07-JAN-08:10 | 31141.22 | 24-AUG-22:00 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 641.57 | 12480.70 | 22-JAN-15:00 | 40518.36 | 10-AUG-20:30 |
ExteriorEquipment:Electricity | 813.77 | 9999.82 | 02-JAN-02:20 | 49607.07 | 02-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 21.77 | 380.96 | 17-JUN-05:00 | 1291.59 | 02-JAN-21:10 |
ElectricityPurchased:Facility | 4606.71 | 66637.43 | 05-AUG-05:00 | 335399.91 | 10-AUG-18:10 |
ElectricityPurchased:Plant | 4606.71 | 66637.43 | 05-AUG-05:00 | 335399.91 | 10-AUG-18:10 |
Cogeneration:ElectricityPurchased | 4606.71 | 66637.43 | 05-AUG-05:00 | 335399.91 | 10-AUG-18:10 |
General:Cogeneration:ElectricityPurchased | 4606.71 | 66637.43 | 05-AUG-05:00 | 335399.91 | 10-AUG-18:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 4606.71 | 66637.43 | 05-AUG-05:00 | 335399.91 | 10-AUG-18:10 |
ElectricityNet:Plant | 4606.71 | 66637.43 | 05-AUG-05:00 | 335399.91 | 10-AUG-18:10 |
Cogeneration:ElectricityNet | 4606.71 | 66637.43 | 05-AUG-05:00 | 335399.91 | 10-AUG-18:10 |
General:Cogeneration:ElectricityNet | 4606.71 | 66637.43 | 05-AUG-05:00 | 335399.91 | 10-AUG-18:10 |
General:Fans:Electricity | 499.01 | 11724.09 | 07-JAN-08:10 | 31141.22 | 24-AUG-22:00 |
ExteriorLights:Electricity | 193.50 | 0.00 | 01-JAN-08:10 | 12338.45 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 193.50 | 0.00 | 01-JAN-08:10 | 12338.45 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 789.09 | 9600.00 | 01-JAN-00:10 | 48128.80 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 2.91 | 18.80 | 01-JAN-00:10 | 188.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 120.79 | 0.00 | 01-JAN-08:40 | 9938.94 | 22-JUN-16:30 |
General:HeatRecovery:Electricity | 120.79 | 0.00 | 01-JAN-08:40 | 9938.94 | 22-JUN-16:30 |
WaterSystems:Electricity | 94.78 | 1222.48 | 25-AUG-01:00 | 4751.13 | 15-NOV-19:50 |
Water Heater:WaterSystems:Electricity | 94.78 | 1222.48 | 25-AUG-01:00 | 4751.13 | 15-NOV-19:50 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 316.58 | 0.00 | 01-JAN-00:10 | 130336.53 | 10-AUG-18:10 |
General:Cooling:Electricity | 316.58 | 0.00 | 01-JAN-00:10 | 130336.53 | 10-AUG-18:10 |
Pumps:Electricity | 65.28 | 50.09 | 21-OCT-13:50 | 3389.68 | 10-AUG-18:10 |
General:Pumps:Electricity | 65.28 | 50.09 | 21-OCT-13:50 | 3389.68 | 10-AUG-18:10 |
WIRED_LTG_ELECTRICITY | 27.56 | 0.00 | 01-JAN-00:10 | 2275.07 | 02-JAN-20:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 5829.84 | 25738.07 | 11-AUG-01:20 | 539983.04 | 22-MAR-17:40 |
NaturalGas:Building | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Laundry:InteriorEquipment:NaturalGas | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
NaturalGas:Plant | 4041.00 | 12376.17 | 11-AUG-01:20 | 435734.72 | 22-MAR-17:40 |
WaterSystems:NaturalGas | 2699.81 | 12376.17 | 11-AUG-01:20 | 250435.74 | 07-FEB-21:30 |
Water Heater:WaterSystems:NaturalGas | 2699.81 | 12376.17 | 11-AUG-01:20 | 250435.74 | 07-FEB-21:30 |
Heating:NaturalGas | 1341.19 | 0.00 | 27-FEB-11:20 | 210727.42 | 11-NOV-11:50 |
Boiler:Heating:NaturalGas | 1341.19 | 0.00 | 27-FEB-11:20 | 210727.42 | 11-NOV-11:50 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 1327.72 | 0.00 | 01-JAN-00:10 | 445234.04 | 10-AUG-18:10 |
PlantLoopCoolingDemand:HVAC | 1327.72 | 0.00 | 01-JAN-00:10 | 445234.04 | 10-AUG-18:10 |
CoolingCoils:PlantLoopCoolingDemand | 1327.72 | 0.00 | 01-JAN-00:10 | 445234.04 | 10-AUG-18:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 9857.19 | 0.00 | 02-JAN-01:20 | 0.00 | 08-MAY-20:10 |
Water:Plant | 9857.19 | 0.00 | 02-JAN-01:20 | 0.00 | 08-MAY-20:10 |
WaterSystems:Water | 9857.19 | 0.00 | 02-JAN-01:20 | 0.00 | 08-MAY-20:10 |
Water Heater:WaterSystems:Water | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:10 |
MainsWater:Facility | 9857.19 | 0.00 | 02-JAN-01:20 | 0.00 | 08-MAY-20:10 |
MainsWater:Plant | 9857.19 | 0.00 | 02-JAN-01:20 | 0.00 | 08-MAY-20:10 |
WaterSystems:MainsWater | 9857.19 | 0.00 | 02-JAN-01:20 | 0.00 | 08-MAY-20:10 |
Water Heater:WaterSystems:MainsWater | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:10 |
WaterUse:WaterSystems:Water | 4114.69 | 0.00 | 02-JAN-01:20 | 0.00 | 28-JUN-07:00 |
WaterUse:WaterSystems:MainsWater | 4114.69 | 0.00 | 02-JAN-01:20 | 0.00 | 28-JUN-07:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 13946.26 | 131951.85 | 09-MAR-14:20 | 1913920.56 | 10-AUG-18:10 |
EnergyTransfer:Building | 4761.08 | 80996.85 | 26-DEC-11:10 | 335491.49 | 10-AUG-18:20 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 717.13 | 11295.25 | 19-FEB-04:00 | 36165.76 | 13-AUG-10:40 |
Refrigeration:EnergyTransfer | 183.45 | 4022.28 | 11-FEB-23:20 | 10345.15 | 29-AUG-06:50 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 91.73 | 2011.14 | 11-FEB-23:20 | 5172.57 | 29-AUG-06:50 |
General:Refrigeration:EnergyTransfer | 91.73 | 2011.14 | 11-FEB-23:20 | 5172.57 | 29-AUG-06:50 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 91.73 | 2011.14 | 11-FEB-23:20 | 5172.57 | 29-AUG-06:50 |
EnergyTransfer:Plant | 4832.63 | 17380.95 | 17-OCT-03:00 | 1061397.10 | 10-AUG-18:10 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 21.61 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 70.11 | 1884.59 | 12-FEB-04:10 | 2555.76 | 30-AUG-13:30 |
EnergyTransfer:Zone:BASEMENT | 398.99 | 10528.77 | 23-APR-15:00 | 18924.04 | 06-OCT-21:00 |
Heating:EnergyTransfer | 74.62 | 0.00 | 01-JAN-08:10 | 47369.38 | 26-DEC-16:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 74.62 | 0.00 | 01-JAN-08:10 | 47369.38 | 26-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 4594.74 | 73209.95 | 26-DEC-15:00 | 331881.08 | 10-AUG-18:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 398.99 | 10528.77 | 23-APR-15:00 | 18924.04 | 06-OCT-21:00 |
General:Cooling:EnergyTransfer | 4594.74 | 73209.95 | 26-DEC-15:00 | 331881.08 | 10-AUG-18:20 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 398.99 | 10528.77 | 23-APR-15:00 | 18924.04 | 06-OCT-21:00 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 38.40 | 0.44 | 22-DEC-05:30 | 4006.98 | 04-OCT-12:50 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.21 | 0.00 | 01-JAN-00:10 | 623.77 | 26-DEC-12:00 |
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.21 | 0.00 | 01-JAN-00:10 | 623.77 | 26-DEC-12:00 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 38.20 | 0.00 | 01-JAN-02:40 | 4006.98 | 04-OCT-12:50 |
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 38.20 | 0.00 | 01-JAN-02:40 | 4006.98 | 04-OCT-12:50 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 32.87 | 403.92 | 16-JAN-16:00 | 2008.30 | 10-AUG-21:00 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 32.87 | 403.92 | 16-JAN-16:00 | 2008.30 | 10-AUG-21:00 |
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 32.87 | 403.92 | 16-JAN-16:00 | 2008.30 | 10-AUG-21:00 |
EnergyTransfer:Zone:MECH_FLR_1 | 21.70 | 0.59 | 26-DEC-11:30 | 1298.48 | 10-AUG-21:00 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 71.89 | 16-JAN-15:50 |
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 71.89 | 16-JAN-15:50 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 21.69 | 0.00 | 15-JAN-15:30 | 1298.48 | 10-AUG-21:00 |
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 21.69 | 0.00 | 15-JAN-15:30 | 1298.48 | 10-AUG-21:00 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 11.43 | 0.01 | 25-DEC-05:30 | 663.76 | 10-AUG-18:10 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.04 | 0.00 | 01-JAN-00:10 | 167.68 | 16-JAN-16:00 |
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.04 | 0.00 | 01-JAN-00:10 | 167.68 | 16-JAN-16:00 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 11.39 | 0.00 | 01-JAN-14:40 | 663.76 | 10-AUG-18:10 |
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 11.39 | 0.00 | 01-JAN-14:40 | 663.76 | 10-AUG-18:10 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 591.64 | 9749.25 | 17-JAN-05:00 | 38660.34 | 10-AUG-20:00 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 591.64 | 9749.25 | 17-JAN-05:00 | 38660.34 | 10-AUG-20:00 |
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 591.64 | 9749.25 | 17-JAN-05:00 | 38660.34 | 10-AUG-20:00 |
EnergyTransfer:Zone:CAFE_FLR_1 | 231.61 | 618.95 | 26-DEC-12:30 | 14123.84 | 04-OCT-12:50 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 231.61 | 618.95 | 26-DEC-12:30 | 14123.84 | 04-OCT-12:50 |
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 231.61 | 618.95 | 26-DEC-12:30 | 14123.84 | 04-OCT-12:50 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 761.03 | 10472.79 | 26-DEC-15:00 | 39328.61 | 10-AUG-21:10 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 761.03 | 10472.79 | 26-DEC-15:00 | 39328.61 | 10-AUG-21:10 |
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 761.03 | 10472.79 | 26-DEC-15:00 | 39328.61 | 10-AUG-21:10 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 47.06 | 0.00 | 01-JAN-08:10 | 11634.61 | 10-AUG-18:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 10.59 | 0.00 | 01-JAN-08:10 | 4432.66 | 26-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 10.59 | 0.00 | 01-JAN-08:10 | 4432.66 | 26-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 36.47 | 0.00 | 01-JAN-00:10 | 11634.61 | 10-AUG-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 36.47 | 0.00 | 01-JAN-00:10 | 11634.61 | 10-AUG-18:10 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 37.22 | 0.00 | 01-JAN-08:10 | 11935.41 | 14-JUL-16:40 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 13.25 | 0.00 | 01-JAN-08:10 | 4499.91 | 26-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 13.25 | 0.00 | 01-JAN-08:10 | 4499.91 | 26-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 23.97 | 0.00 | 01-JAN-00:10 | 11935.41 | 14-JUL-16:40 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 23.97 | 0.00 | 01-JAN-00:10 | 11935.41 | 14-JUL-16:40 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 231.86 | 0.00 | 01-JAN-00:10 | 53212.93 | 04-OCT-12:40 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 231.86 | 0.00 | 01-JAN-00:10 | 53212.93 | 04-OCT-12:40 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 231.86 | 0.00 | 01-JAN-00:10 | 53212.93 | 04-OCT-12:40 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 301.45 | 0.00 | 01-JAN-08:10 | 64148.23 | 11-JUL-20:50 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 7.93 | 0.00 | 01-JAN-00:10 | 20265.46 | 26-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 7.93 | 0.00 | 01-JAN-00:10 | 20265.46 | 26-DEC-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 293.51 | 0.00 | 01-JAN-08:10 | 64148.23 | 11-JUL-20:50 |
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 293.51 | 0.00 | 01-JAN-08:10 | 64148.23 | 11-JUL-20:50 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 45.35 | 0.00 | 01-JAN-08:10 | 10560.76 | 10-AUG-08:10 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 10.64 | 0.00 | 01-JAN-08:10 | 4432.87 | 26-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 10.64 | 0.00 | 01-JAN-08:10 | 4432.87 | 26-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 34.70 | 0.00 | 01-JAN-00:10 | 10560.76 | 10-AUG-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 34.70 | 0.00 | 01-JAN-00:10 | 10560.76 | 10-AUG-08:10 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 36.77 | 0.00 | 01-JAN-08:10 | 11606.00 | 13-AUG-09:00 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 13.21 | 0.00 | 01-JAN-08:10 | 4479.39 | 26-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 13.21 | 0.00 | 01-JAN-08:10 | 4479.39 | 26-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 23.56 | 0.00 | 01-JAN-00:10 | 11606.00 | 13-AUG-09:00 |
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 23.56 | 0.00 | 01-JAN-00:10 | 11606.00 | 13-AUG-09:00 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 179.23 | 1.38 | 22-DEC-13:50 | 10288.06 | 13-AUG-10:40 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.05 | 0.00 | 01-JAN-00:10 | 1361.76 | 26-DEC-15:00 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.05 | 0.00 | 01-JAN-00:10 | 1361.76 | 26-DEC-15:00 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 179.18 | 0.00 | 01-JAN-15:00 | 10288.06 | 13-AUG-10:40 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 179.18 | 0.00 | 01-JAN-15:00 | 10288.06 | 13-AUG-10:40 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 13.42 | 0.00 | 01-JAN-08:10 | 3245.17 | 10-AUG-18:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 4.48 | 0.00 | 01-JAN-08:10 | 1453.49 | 26-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 4.48 | 0.00 | 01-JAN-08:10 | 1453.49 | 26-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 8.95 | 0.00 | 01-JAN-00:10 | 3245.17 | 10-AUG-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 8.95 | 0.00 | 01-JAN-00:10 | 3245.17 | 10-AUG-18:10 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 11.28 | 0.00 | 01-JAN-08:10 | 3186.23 | 14-JUL-16:30 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 5.38 | 0.00 | 01-JAN-08:10 | 1424.93 | 26-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 5.38 | 0.00 | 01-JAN-08:10 | 1424.93 | 26-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 5.89 | 0.00 | 01-JAN-00:10 | 3186.23 | 14-JUL-16:30 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 5.89 | 0.00 | 01-JAN-00:10 | 3186.23 | 14-JUL-16:30 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 71.45 | 0.00 | 01-JAN-08:10 | 17253.39 | 14-SEP-15:10 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 8.82 | 0.00 | 01-JAN-08:10 | 6941.43 | 26-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 8.82 | 0.00 | 01-JAN-08:10 | 6941.43 | 26-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 62.62 | 0.00 | 01-JAN-00:10 | 17253.39 | 14-SEP-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 62.62 | 0.00 | 01-JAN-00:10 | 17253.39 | 14-SEP-15:10 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 423.96 | 8520.76 | 26-DEC-15:00 | 22260.17 | 24-JUL-21:10 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 423.96 | 8520.76 | 26-DEC-15:00 | 22260.17 | 24-JUL-21:10 |
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 423.96 | 8520.76 | 26-DEC-15:00 | 22260.17 | 24-JUL-21:10 |
EnergyTransfer:Zone:DINING_FLR_6 | 466.99 | 9543.87 | 26-DEC-15:00 | 23521.14 | 24-JUL-21:20 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 466.99 | 9543.87 | 26-DEC-15:00 | 23521.14 | 24-JUL-21:20 |
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 466.99 | 9543.87 | 26-DEC-15:00 | 23521.14 | 24-JUL-21:20 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 625.41 | 9157.89 | 19-FEB-04:00 | 31074.49 | 13-AUG-10:40 |
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 625.41 | 9157.89 | 19-FEB-04:00 | 31074.49 | 13-AUG-10:40 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 90.26 | 1.05 | 16-JAN-16:40 | 6157.07 | 10-AUG-15:10 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.01 | 0.00 | 01-JAN-00:10 | 484.13 | 19-FEB-06:00 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.01 | 0.00 | 01-JAN-00:10 | 484.13 | 19-FEB-06:00 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 90.25 | 0.00 | 06-JAN-07:50 | 6157.07 | 10-AUG-15:10 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 90.25 | 0.00 | 06-JAN-07:50 | 6157.07 | 10-AUG-15:10 |
PlantLoopHeatingDemand:Facility | 1673.27 | 9877.26 | 12-AUG-00:10 | 183670.94 | 03-JAN-07:20 |
PlantLoopHeatingDemand:Plant | 781.70 | 9877.26 | 12-AUG-00:10 | 55604.03 | 10-FEB-07:30 |
WaterSystems:PlantLoopHeatingDemand | 781.70 | 9877.26 | 12-AUG-00:10 | 55604.03 | 10-FEB-07:30 |
General:WaterSystems:PlantLoopHeatingDemand | 781.70 | 9877.26 | 12-AUG-00:10 | 55604.03 | 10-FEB-07:30 |
EnergyTransfer:HVAC | 4352.54 | 403.15 | 21-OCT-13:50 | 524924.78 | 10-AUG-18:10 |
HeatingCoils:EnergyTransfer | 891.58 | 0.00 | 27-FEB-11:20 | 148590.34 | 16-DEC-16:20 |
PlantLoopHeatingDemand:HVAC | 891.58 | 0.00 | 27-FEB-11:20 | 148590.34 | 16-DEC-16:20 |
HeatingCoils:PlantLoopHeatingDemand | 891.58 | 0.00 | 27-FEB-11:20 | 148590.34 | 16-DEC-16:20 |
CoolingCoils:EnergyTransfer | 1327.72 | 0.00 | 01-JAN-00:10 | 445234.04 | 10-AUG-18:10 |
HeatRecoveryForHeating:EnergyTransfer | 2118.81 | 0.00 | 01-JAN-08:40 | 377584.14 | 19-FEB-06:40 |
HeatRecoveryForCooling:EnergyTransfer | 14.43 | 0.00 | 01-JAN-00:10 | 84238.76 | 29-AUG-13:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 781.70 | 9877.26 | 12-AUG-00:10 | 55604.03 | 10-FEB-07:30 |
WaterUse:WaterSystems:EnergyTransfer | 781.70 | 9877.26 | 12-AUG-00:10 | 55604.03 | 10-FEB-07:30 |
Boilers:EnergyTransfer | 884.95 | 0.00 | 27-FEB-11:20 | 148984.30 | 16-DEC-16:10 |
Chillers:EnergyTransfer | 1378.84 | 0.00 | 01-JAN-00:10 | 448092.67 | 10-AUG-18:10 |
HeatRejection:EnergyTransfer | 1695.42 | 0.00 | 01-JAN-00:10 | 578429.20 | 10-AUG-18:10 |
General:HeatRejection:EnergyTransfer | 1695.42 | 0.00 | 01-JAN-00:10 | 578429.20 | 10-AUG-18:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:35
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -398.990 | 0.000 | 0.000 | 139.547 | 161.294 | 143.105 | 0.000 | 0.000 | 0.000 | 0.001 | 0.000 | 0.000 | 0.000 | 0.000 | -44.957 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 0.206 | -38.199 | 0.000 | 0.000 | 15.892 | 7.307 | 10.186 | 20.671 | 0.000 | 0.013 | 0.000 | 0.000 | -9.995 | 0.000 | -1.786 | -4.296 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.000 | -32.867 | 0.000 | 0.000 | 17.086 | 8.462 | 11.795 | 0.000 | 0.000 | 0.005 | 0.000 | 0.000 | 0.000 | 0.000 | -0.761 | -3.720 |
MECH_FLR_1 | 0.000 | 0.000 | 0.001 | -21.694 | 0.000 | 0.000 | 3.738 | 8.366 | 12.471 | 0.000 | 0.000 | 0.013 | 0.000 | 0.000 | 0.000 | 0.000 | -1.723 | -1.173 |
STORAGE_FLR_1 | 0.000 | 0.000 | 0.037 | -11.390 | 0.000 | 0.000 | 2.917 | 3.079 | 3.598 | 0.000 | 0.000 | 0.008 | 2.723 | 0.000 | 0.000 | 0.000 | -0.973 | -0.000 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.000 | -591.643 | 0.000 | 0.000 | 11.245 | 3.975 | 658.131 | 0.000 | 0.000 | 0.019 | 0.000 | 0.000 | 0.000 | 0.000 | -2.571 | -79.157 |
CAFE_FLR_1 | 0.000 | 0.000 | 0.000 | -231.611 | 0.000 | 0.000 | 197.346 | 14.244 | 14.341 | 57.359 | 0.000 | 0.027 | 0.000 | 0.000 | -30.039 | 0.000 | -4.243 | -17.423 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.000 | -761.038 | 0.000 | 0.000 | 563.295 | 110.169 | 148.998 | 75.381 | 0.000 | 0.083 | 0.000 | 0.000 | -41.713 | 0.000 | -12.774 | -82.402 |
ROOM_1_FLR_3 | 14.833 | -30.217 | 0.000 | -10.495 | 0.000 | 0.000 | 9.725 | 9.244 | 10.478 | 38.939 | 0.000 | 0.096 | 0.000 | 0.000 | -22.896 | 0.000 | -4.770 | -14.938 |
ROOM_2_FLR_3 | 17.887 | -17.615 | 0.000 | -10.985 | 0.000 | 0.000 | 9.596 | 9.243 | 10.477 | 26.904 | 0.000 | 0.047 | 0.000 | 0.000 | -23.520 | 0.000 | -5.208 | -16.826 |
ROOM_3_MULT19_FLR_3 | 0.000 | -217.704 | 0.000 | -14.148 | 0.000 | 0.000 | 0.000 | 110.385 | 194.997 | 225.700 | 0.000 | 0.030 | 0.003 | 0.000 | -167.239 | 0.000 | -30.494 | -101.526 |
ROOM_4_MULT19_FLR_3 | 31.574 | -171.405 | 0.000 | -145.738 | 0.000 | 0.000 | 183.307 | 110.415 | 195.050 | 64.829 | 0.000 | 0.481 | 0.000 | 0.000 | -130.696 | 0.000 | -39.060 | -98.757 |
ROOM_5_FLR_3 | 14.883 | -28.445 | 0.000 | -10.497 | 0.000 | 0.000 | 9.721 | 9.244 | 10.478 | 37.127 | 0.000 | 0.097 | 0.000 | 0.000 | -22.424 | 0.000 | -4.771 | -15.414 |
ROOM_6_FLR_3 | 17.843 | -17.358 | 0.000 | -10.834 | 0.000 | 0.000 | 9.647 | 9.243 | 10.477 | 25.086 | 0.000 | 0.049 | 0.000 | 0.000 | -22.832 | 0.000 | -5.191 | -16.129 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 0.049 | -179.177 | 0.000 | 0.000 | 120.331 | 91.336 | 0.000 | 35.066 | 0.000 | 0.042 | 0.000 | 0.000 | -29.498 | 0.000 | -5.177 | -32.971 |
ROOM_1_FLR_6 | 5.691 | -7.542 | 0.000 | -2.620 | 0.000 | 0.000 | 2.435 | 2.311 | 2.620 | 9.663 | 0.000 | 0.026 | 0.000 | 0.000 | -5.676 | 0.000 | -1.217 | -5.690 |
ROOM_2_FLR_6 | 6.673 | -4.421 | 0.000 | -2.760 | 0.000 | 0.000 | 2.397 | 2.311 | 2.619 | 6.658 | 0.000 | 0.012 | 0.000 | 0.000 | -5.844 | 0.000 | -1.318 | -6.326 |
ROOM_3_MULT9_FLR_6 | 14.084 | -50.949 | 0.000 | -16.934 | 0.000 | 0.000 | 21.821 | 13.076 | 23.098 | 53.040 | 0.000 | 0.182 | 0.000 | 0.000 | -26.770 | 0.000 | -6.444 | -24.205 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.000 | -423.962 | 0.000 | 0.000 | 316.003 | 31.006 | 175.857 | 6.311 | 0.000 | 0.013 | 0.000 | 0.000 | -18.266 | 0.000 | -3.123 | -83.839 |
DINING_FLR_6 | 0.000 | 0.000 | 0.000 | -466.991 | 0.000 | 0.000 | 314.906 | 31.006 | 175.857 | 6.104 | 0.000 | 0.013 | 0.000 | 0.000 | -18.833 | 0.000 | -3.149 | -38.913 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.000 | -625.391 | 0.000 | 0.000 | 28.294 | 12.972 | 550.372 | 17.565 | 0.000 | 0.012 | 31.224 | 0.000 | -12.233 | 0.000 | -2.814 | -0.000 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 0.013 | -90.251 | 0.000 | 0.000 | 31.810 | 24.166 | 0.000 | 17.089 | 0.000 | 0.014 | 32.866 | 0.000 | -13.396 | 0.000 | -2.311 | 0.000 |
Total Facility | 123.468 | -545.655 | 0.306 | -4098.214 | 0.000 | 0.000 | 2011.057 | 782.856 | 2365.005 | 723.492 | 0.000 | 1.281 | 66.817 | 0.000 | -601.870 | 0.000 | -139.879 | -688.661 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 06-OCT-21:00 | 0.00 | 0.00 | 0.00 | -18924.24 | 0.00 | 0.00 | 5924.44 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -7850.42 |
RETAIL_1_FLR_1 | 04-OCT-12:50 | 0.00 | 0.00 | 0.00 | -4006.54 | 0.00 | 0.00 | 150.60 | 166.00 | 252.59 | 6353.19 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -17.84 | -2898.00 |
RETAIL_2_FLR_1 | 10-AUG-20:55 | 0.00 | 0.00 | 0.00 | -2008.49 | 0.00 | 0.00 | 697.58 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -2.01 | -54.34 |
MECH_FLR_1 | 10-AUG-20:57 | 0.00 | 0.00 | 0.00 | -1298.51 | 0.00 | 0.00 | 147.52 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -4.75 | -247.69 |
STORAGE_FLR_1 | 10-AUG-18:10 | 0.00 | 0.00 | 0.00 | -665.62 | 0.00 | 0.00 | 102.91 | 223.85 | 229.41 | 0.00 | 0.00 | 18.76 | 90.67 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 10-AUG-20:00 | 0.00 | 0.00 | 0.00 | -38661.54 | 0.00 | 0.00 | 408.86 | 325.08 | 44299.38 | 0.00 | 0.00 | 10.23 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -6382.01 |
CAFE_FLR_1 | 04-OCT-12:50 | 0.00 | 0.00 | 0.00 | -14122.26 | 0.00 | 0.00 | 1979.10 | 103.98 | 355.63 | 17817.44 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -39.44 | -6094.46 |
LOBBY_FLR_1 | 10-AUG-21:05 | 0.00 | 0.00 | 0.00 | -39344.91 | 0.00 | 0.00 | 26437.38 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -673.42 | 0.00 | -35.58 | -109.95 |
ROOM_1_FLR_3 | 14-MAY-18:01 | 0.00 | -14897.60 | 0.00 | -725.79 | 0.00 | 0.00 | 283.21 | 711.53 | 484.65 | 6185.16 | 0.00 | 0.00 | 8015.54 | 0.00 | -0.00 | 0.00 | -56.71 | 0.00 |
ROOM_2_FLR_3 | 25-APR-17:41 | 0.00 | -15572.86 | 0.00 | 0.00 | 0.00 | 0.00 | 193.47 | 476.67 | 505.67 | 5885.14 | 0.00 | 0.00 | 8642.35 | 0.00 | -0.00 | 0.00 | -130.44 | 0.00 |
ROOM_3_MULT19_FLR_3 | 04-OCT-12:40 | 0.00 | -53212.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2378.94 | 2352.88 | 76152.85 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -394.67 | -27277.07 |
ROOM_4_MULT19_FLR_3 | 14-MAY-21:51 | 0.00 | -74923.83 | 0.00 | -8216.81 | 0.00 | 0.00 | 6347.31 | 7223.75 | 6668.31 | 0.00 | 0.00 | 0.00 | 67867.39 | 0.00 | -4546.73 | 0.00 | -419.38 | 0.00 |
ROOM_5_FLR_3 | 14-MAY-18:01 | 0.00 | -13252.22 | 0.00 | -713.69 | 0.00 | 0.00 | 283.21 | 711.53 | 484.65 | 343.86 | 0.00 | 0.00 | 12187.34 | 0.00 | -0.00 | 0.00 | -44.68 | 0.00 |
ROOM_6_FLR_3 | 24-JUL-08:32 | 0.00 | -13596.91 | 0.00 | -1051.05 | 0.00 | 0.00 | 58.85 | 313.04 | 452.99 | 9318.08 | 0.00 | 0.00 | 4549.48 | 0.00 | -0.00 | 0.00 | -44.48 | 0.00 |
CORRIDOR_FLR_3 | 13-AUG-10:33 | 0.00 | 0.00 | 0.00 | -10313.74 | 0.00 | 0.00 | 1850.29 | 2489.76 | 0.00 | 7053.07 | 0.00 | 14.96 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1094.34 |
ROOM_1_FLR_6 | 14-MAY-18:01 | 0.00 | -3890.01 | 0.00 | -181.71 | 0.00 | 0.00 | 70.80 | 177.88 | 121.16 | 1531.43 | 0.00 | 0.00 | 2188.44 | 0.00 | -0.00 | 0.00 | -18.01 | 0.00 |
ROOM_2_FLR_6 | 25-APR-17:41 | 0.00 | -4036.24 | 0.00 | 0.00 | 0.00 | 0.00 | 48.37 | 119.17 | 126.42 | 1450.07 | 0.00 | 0.00 | 2325.09 | 0.00 | -0.00 | 0.00 | -32.86 | 0.00 |
ROOM_3_MULT9_FLR_6 | 25-MAR-15:01 | 0.00 | -21222.02 | 0.00 | -835.64 | 0.00 | 0.00 | 294.09 | 332.11 | 487.74 | 7016.73 | 0.00 | 0.00 | 14086.52 | 0.00 | -0.00 | 0.00 | -159.53 | 0.00 |
BANQUET_FLR_6 | 24-JUL-21:10 | 0.00 | 0.00 | 0.00 | -22261.32 | 0.00 | 0.00 | 15644.05 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -217.44 | 0.00 | -12.36 | -1892.86 |
DINING_FLR_6 | 24-JUL-21:20 | 0.00 | 0.00 | 0.00 | -23522.51 | 0.00 | 0.00 | 15629.92 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -254.33 | 0.00 | -15.12 | -577.88 |
KITCHEN_FLR_6 | 13-AUG-10:40 | 0.00 | 0.00 | 0.00 | -31081.50 | 0.00 | 0.00 | 464.20 | 353.60 | 24259.91 | 3650.54 | 0.00 | 0.02 | 2353.23 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 10-AUG-15:03 | 0.00 | 0.00 | 0.00 | -6159.30 | 0.00 | 0.00 | 771.14 | 548.96 | 0.00 | 2449.02 | 0.00 | 39.42 | 2350.75 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 10-AUG-18:02 | 0.00 | -163454.81 | 0.00 | -201969.72 | 0.00 | 0.00 | 75199.71 | 53578.21 | 120482.43 | 47564.63 | 0.00 | 1961.29 | 66638.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 26-DEC-12:00 | 0.00 | 0.00 | 623.76 | 0.00 | 0.00 | 0.00 | 179.27 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -554.01 | 0.00 | -118.80 | -548.80 |
RETAIL_2_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 16-JAN-15:50 | 0.00 | 0.00 | 71.89 | 0.00 | 0.00 | 0.00 | 43.84 | 152.04 | 265.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -97.71 | -435.14 |
STORAGE_FLR_1 | 16-JAN-16:00 | 0.00 | 0.00 | 167.67 | 0.00 | 0.00 | 0.00 | 33.72 | 55.96 | 76.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -56.38 | -277.45 |
LAUNDRY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 18-APR-15:04 | 5220.88 | 419.38 | 0.00 | -419.38 | 0.00 | 0.00 | 235.75 | 199.23 | 200.18 | 2176.12 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -152.05 | -7880.11 |
ROOM_2_FLR_3 | 24-MAR-15:03 | 5109.14 | 416.25 | 0.00 | -416.25 | 0.00 | 0.00 | 252.31 | 199.20 | 200.16 | 2771.48 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -151.04 | -8381.26 |
ROOM_3_MULT19_FLR_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 07-JAN-16:01 | 25357.18 | 4669.59 | 0.00 | -4669.59 | 0.00 | 0.00 | 2968.12 | 2804.51 | 4118.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -8405.24 | 0.00 | -1214.47 | -25628.76 |
ROOM_5_FLR_3 | 01-OCT-15:04 | 5064.74 | 465.73 | 0.00 | -465.73 | 0.00 | 0.00 | 130.71 | 234.80 | 221.25 | 2083.19 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -530.12 | -7204.59 |
ROOM_6_FLR_3 | 29-MAY-15:04 | 4976.47 | 426.09 | 0.00 | -426.09 | 0.00 | 0.00 | 130.71 | 234.78 | 221.23 | 2658.43 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -718.71 | -7502.92 |
CORRIDOR_FLR_3 | 26-DEC-15:00 | 0.00 | 0.00 | 1361.76 | 0.00 | 0.00 | 0.00 | 1385.83 | 2074.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1796.77 | 0.00 | -299.43 | -2726.19 |
ROOM_1_FLR_6 | 26-DEC-16:13 | 1520.00 | 90.71 | 0.00 | -90.71 | 0.00 | 0.00 | 67.02 | 49.81 | 50.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -401.86 | 0.00 | -54.60 | -1230.42 |
ROOM_2_FLR_6 | 26-DEC-16:13 | 1484.92 | 89.67 | 0.00 | -89.67 | 0.00 | 0.00 | 67.26 | 49.80 | 50.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -398.62 | 0.00 | -54.42 | -1198.97 |
ROOM_3_MULT9_FLR_6 | 26-DEC-16:13 | 7417.28 | 590.81 | 0.00 | -590.81 | 0.00 | 0.00 | 600.58 | 281.79 | 441.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1897.97 | 0.00 | -252.47 | -6590.49 |
BANQUET_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 19-FEB-06:00 | 0.00 | 0.00 | 484.11 | 0.00 | 0.00 | 0.00 | 1283.30 | 439.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1511.06 | 0.00 | -190.23 | -505.30 |
Total Facility | 16-JAN-16:13 | -25057.65 | 87179.53 | 1150.23 | -87179.53 | 0.00 | 0.00 | 35481.86 | 16549.49 | 71286.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -37120.36 | 0.00 | -6346.92 | -55942.93 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:35
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV WITH REHEAT | 22.7135 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 22.5915 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV WITH REHEAT | 11.6520 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 11.6520 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.6520 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.0400 | 0.000610 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.000000 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.000000 | 142.3000 | 0.003581 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.000000 | 422.4350 | 0.001448 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 83.8280 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003556 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.1800 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 | |
VAV WITH REHEAT | 0.00 | 0.001045 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.5475 | 2.5475 | 1.3069 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4425 | 0.4425 | 0.2270 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2320 | 0.2320 | 0.1190 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1740 | 0.1740 | 0.0893 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1034 | 0.1034 | 0.0531 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.2875 | 3.2875 | 1.6865 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7669 | 1.7669 | 0.9064 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.1416 | 5.1416 | 2.6377 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6074 | 1.6074 | 0.8246 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1173 | 2.1173 | 1.0862 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2178 | 2.2178 | 1.1377 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2713 | 2.2713 | 1.1652 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8041 | 0.8041 | 0.4125 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
VAV WITH REHEAT | 22.7135 | 22.5915 | 22.7135 | 11.6520 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3069 | 1.3069 | 1.3069 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2270 | 0.2270 | 0.2270 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1190 | 0.1190 | 0.1190 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0893 | 0.0893 | 0.0893 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0531 | 0.0531 | 0.0531 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6865 | 1.6865 | 1.6865 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9064 | 0.9064 | 0.9064 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6377 | 2.6377 | 2.6377 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8246 | 0.8246 | 0.8246 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0862 | 1.0862 | 1.0862 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1377 | 1.1377 | 1.1377 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1652 | 1.1652 | 1.1652 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4125 | 0.4125 | 0.4125 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
VAV WITH REHEAT | 11.6520 | 11.6520 | 11.6520 | 11.6520 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:35
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 168.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 168.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 18.83 |
Number of hours cooling loads not met | 30.00 |
Number of hours not met | 48.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 1341.19 | 210727.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 316.58 | 130336.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 782.86 | 64632.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 193.50 | 12338.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 872.72 | 59188.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 14.43 | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 8.99 | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.20 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 21.77 | 1291.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 789.09 | 48128.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 2.91 | 188.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 499.01 | 31141.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 65.28 | 3389.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 120.79 | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 94.78 | 4751.13 | 2699.81 | 250435.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.09 | 2093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 20.46 | 1891.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 34.41 | 1201.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1720.14 | 4606.71 |
Natural Gas | 1788.84 | 5829.84 |
Additional | 0.00 | 0.00 |
Total | 3508.98 | 10436.55 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 69.00 |
Space Heating | 0.00 |
Space Cooling | 27.90 |
Fans (All) | 43.98 |
Service Water Heating | 8.35 |
Receptacle Equipment | 146.16 |
Miscellaneous (All) | 406.05 |
Subtotal | 406.05 |
Natural Gas [MJ/m2] | |
Space Heating | 118.22 |
Service Water Heating | 237.97 |
Miscellaneous (All) | 513.86 |
Subtotal | 513.86 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 7.50 |
Space Heating | 12.85 |
Space Cooling | 3.03 |
Fans (All) | 4.78 |
Service Water Heating | 26.78 |
Receptacle Equipment | 33.03 |
Miscellaneous | 12.03 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 486. | 5110. |
ELEVATOR_STANDBY_SCH | 7671. | 8760. |
LTG_SCH_KITCHEN | 3061. | 8760. |
LTG_SCH_DINING | 3061. | 8760. |
LTG_SCH_BASEMENT | 2572. | 8760. |
LTG_SCH_LOBBY | 2295. | 8760. |
LTG_SCH_STORAGE | 1580. | 8760. |
LTG_SCH_MECHANIC | 3061. | 8760. |
LTG_SCH_LAUNDRY | 3061. | 8760. |
LTG_SCH_GUESTROOM | 1980. | 8760. |
LTG_SCH_CORRIDOR | 2295. | 8760. |
LTG_SCH_RETAIL | 2678. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 1591. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3737. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 5740. | 6205. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 8760. | 8760. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 26.67 | 365 | 26.67 | 365 |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
HTGSETP_SCH | BASEMENT DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:35
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8697.50 | 62.50 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8546.17 | 213.83 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8748.83 | 11.17 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8646.17 | 113.83 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8546.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 213.83 | 0.00 | 0.00 | 0.00 |
Average | 8741.76 | 18.24 | 0.00 | 0.00 | 0.00 |
Sum | 192318.67 | 401.33 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4135.17 | 18.83 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4113.33 | 40.67 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108269.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 40.67 | 0.00 | 0.00 | 0.00 |
Average | 288884.34 | 2.70 | 0.00 | 0.00 | 0.00 |
Sum | 6355455.50 | 59.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8741.33 | 18.67 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8733.67 | 26.33 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8681.50 | 78.50 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8206.00 | 554.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8739.00 | 21.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8622.00 | 138.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8719.83 | 40.17 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8739.33 | 20.67 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8753.00 | 7.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8206.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 554.00 | 0.00 | 0.00 | 0.00 |
Average | 8718.89 | 41.11 | 0.00 | 0.00 | 0.00 |
Sum | 191815.67 | 904.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 708027.67 | 2389.33 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2105606.50 | 9822.50 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4119.17 | 34.83 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4087.33 | 66.67 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1236917.67 | 8797.33 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1241185.67 | 4529.33 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108225.50 | 43.50 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2105606.50 | 9822.50 | 0.00 | 0.00 | 0.00 |
Average | 287719.61 | 1167.43 | 0.00 | 0.00 | 0.00 |
Sum | 6329831.50 | 25683.50 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:35
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:35
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 1592.73 | 0.00 | 0.00 |
Sum | 0.00 | 35040.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 710417.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 2115429.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 2115429.00 | 0.00 | 0.00 |
Average | 0.00 | 241694.36 | 0.00 | 0.00 |
Sum | 0.00 | 5317276.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
For: Environment
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Environment
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
For: Environment
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.326644E+11 | 14368.56 | 11-JAN-21:00 | 11.10 | 10.22 | 0.773642E+10 | 4833.51 | 13-JAN-22:10 | 0.60 | 0.60 |
February | 0.289740E+11 | 14221.27 | 01-FEB-21:00 | 6.70 | 5.41 | 0.687705E+10 | 4775.28 | 01-FEB-22:10 | 6.60 | 5.31 |
March | 0.315923E+11 | 14304.51 | 25-MAR-10:33 | 8.87 | 1.80 | 0.750406E+10 | 4688.90 | 03-MAR-22:10 | 8.87 | 1.80 |
April | 0.305699E+11 | 14725.32 | 27-APR-10:33 | 20.37 | 13.53 | 0.716308E+10 | 4590.96 | 14-APR-21:10 | 20.37 | 13.53 |
May | 0.322970E+11 | 15190.50 | 14-MAY-10:33 | 20.03 | 12.68 | 0.746710E+10 | 4641.22 | 18-MAY-21:10 | 8.90 | 7.04 |
June | 0.322909E+11 | 15590.92 | 25-JUN-10:33 | 18.87 | 13.09 | 0.735829E+10 | 4723.74 | 23-JUN-22:10 | 18.87 | 13.09 |
July | 0.345298E+11 | 16122.79 | 30-JUL-10:33 | 23.33 | 16.24 | 0.772981E+10 | 4817.66 | 28-JUL-22:10 | 23.33 | 16.24 |
August | 0.354496E+11 | 16354.47 | 13-AUG-10:33 | 24.17 | 17.28 | 0.789715E+10 | 4837.10 | 15-AUG-22:10 | 18.18 | 14.52 |
September | 0.349199E+11 | 17575.13 | 15-SEP-21:00 | 16.10 | 14.33 | 0.774164E+10 | 4837.09 | 11-SEP-22:10 | 16.10 | 14.33 |
October | 0.363529E+11 | 18924.04 | 06-OCT-21:00 | 12.80 | 10.62 | 0.807085E+10 | 4837.08 | 04-OCT-21:30 | 12.80 | 10.62 |
November | 0.349908E+11 | 18782.45 | 08-NOV-22:00 | 8.90 | 7.25 | 0.781563E+10 | 4837.03 | 16-NOV-22:19 | 5.20 | 4.52 |
December | 0.343574E+11 | 17689.75 | 01-DEC-22:00 | 5.00 | 4.72 | 0.795294E+10 | 4837.04 | 22-DEC-22:19 | 1.90 | 1.47 |
Annual Sum or Average | 0.398989E+12 | 0.913140E+11 | ||||||||
Minimum of Months | 0.289740E+11 | 14221.27 | 5.00 | 1.80 | 0.687705E+10 | 4590.96 | 0.60 | 0.60 | ||
Maximum of Months | 0.363529E+11 | 18924.04 | 24.17 | 17.28 | 0.807085E+10 | 4837.10 | 23.33 | 16.24 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.984917E+09 | 2277.79 | 20-JAN-11:50 | 5.60 | 3.57 | 0.620875E+09 | 364.22 | 03-JAN-01:00 | 5.60 | 3.57 |
February | 0.175555E+10 | 2779.69 | 08-FEB-13:30 | 6.40 | 3.77 | 0.565344E+09 | 389.72 | 27-FEB-22:40 | 12.20 | 10.25 |
March | 0.274675E+10 | 3427.10 | 02-MAR-13:20 | 12.57 | 7.60 | 0.633106E+09 | 407.24 | 14-MAR-21:30 | 12.50 | 8.53 |
April | 0.344856E+10 | 3203.26 | 27-APR-13:05 | 26.10 | 16.37 | 0.618882E+09 | 437.30 | 27-APR-21:30 | 15.80 | 11.30 |
May | 0.405073E+10 | 3094.00 | 04-MAY-13:20 | 22.77 | 15.31 | 0.645538E+09 | 434.51 | 04-MAY-21:30 | 18.35 | 12.20 |
June | 0.428329E+10 | 2568.56 | 28-JUN-10:33 | 21.50 | 14.65 | 0.630437E+09 | 431.62 | 28-JUN-21:30 | 17.50 | 13.87 |
July | 0.495267E+10 | 3026.55 | 31-JUL-13:20 | 27.57 | 18.47 | 0.673585E+09 | 452.37 | 24-JUL-21:30 | 27.57 | 18.47 |
August | 0.513441E+10 | 3845.17 | 24-AUG-13:10 | 28.93 | 19.36 | 0.687116E+09 | 465.74 | 10-AUG-21:19 | 28.93 | 19.36 |
September | 0.446400E+10 | 3980.43 | 14-SEP-13:15 | 23.17 | 17.52 | 0.644288E+09 | 452.15 | 12-SEP-21:30 | 23.17 | 17.52 |
October | 0.341285E+10 | 4006.98 | 04-OCT-12:50 | 20.60 | 11.27 | 0.638269E+09 | 434.52 | 04-OCT-21:30 | 15.00 | 9.56 |
November | 0.175265E+10 | 3260.01 | 04-NOV-13:30 | 20.85 | 16.00 | 0.602579E+09 | 364.86 | 02-NOV-21:30 | 20.85 | 16.00 |
December | 0.121249E+10 | 2544.74 | 05-DEC-12:20 | 10.20 | 6.11 | 0.622325E+09 | 364.21 | 13-DEC-23:49 | 7.80 | 2.39 |
Annual Sum or Average | 0.381989E+11 | 0.758234E+10 | ||||||||
Minimum of Months | 0.984917E+09 | 2277.79 | 5.60 | 3.57 | 0.565344E+09 | 364.21 | 5.60 | 2.39 | ||
Maximum of Months | 0.513441E+10 | 4006.98 | 28.93 | 19.36 | 0.687116E+09 | 465.74 | 28.93 | 19.36 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.231627E+10 | 1141.51 | 11-JAN-21:00 | 11.10 | 10.22 | 0.781287E+09 | 516.13 | 11-JAN-23:10 | 9.22 | 8.15 |
February | 0.222765E+10 | 1252.97 | 27-FEB-21:00 | 12.20 | 10.06 | 0.727077E+09 | 548.68 | 27-FEB-23:10 | 12.20 | 10.40 |
March | 0.264279E+10 | 1279.22 | 02-MAR-21:00 | 6.70 | 5.56 | 0.838631E+09 | 556.41 | 02-MAR-23:10 | 7.12 | 6.08 |
April | 0.271605E+10 | 1621.11 | 27-APR-21:00 | 17.20 | 11.44 | 0.833733E+09 | 569.55 | 27-APR-22:10 | 14.40 | 11.00 |
May | 0.294909E+10 | 1594.67 | 04-MAY-21:00 | 17.80 | 12.21 | 0.885801E+09 | 569.55 | 15-MAY-21:30 | 13.35 | 11.02 |
June | 0.295066E+10 | 1670.87 | 28-JUN-21:00 | 16.70 | 13.67 | 0.871739E+09 | 569.55 | 27-JUN-22:10 | 16.70 | 13.67 |
July | 0.322471E+10 | 1860.11 | 31-JUL-21:00 | 21.70 | 16.73 | 0.920404E+09 | 569.55 | 21-JUL-22:10 | 21.70 | 16.73 |
August | 0.327705E+10 | 2008.44 | 10-AUG-20:55 | 23.00 | 16.96 | 0.927504E+09 | 569.55 | 15-AUG-22:10 | 18.18 | 14.52 |
September | 0.298204E+10 | 1806.55 | 14-SEP-21:00 | 18.30 | 14.89 | 0.875204E+09 | 569.55 | 11-SEP-22:10 | 18.30 | 14.89 |
October | 0.278407E+10 | 1572.60 | 04-OCT-21:00 | 13.90 | 9.05 | 0.860617E+09 | 569.55 | 04-OCT-21:30 | 15.00 | 9.56 |
November | 0.243269E+10 | 1268.63 | 04-NOV-18:10 | 15.00 | 13.34 | 0.785468E+09 | 535.10 | 06-NOV-23:10 | 15.40 | 14.28 |
December | 0.236396E+10 | 1190.31 | 05-DEC-21:00 | 5.60 | 1.73 | 0.789881E+09 | 529.32 | 05-DEC-23:10 | 4.03 | 2.13 |
Annual Sum or Average | 0.328670E+11 | 0.100973E+11 | ||||||||
Minimum of Months | 0.222765E+10 | 1141.51 | 5.60 | 1.73 | 0.727077E+09 | 516.13 | 4.03 | 2.13 | ||
Maximum of Months | 0.327705E+10 | 2008.44 | 23.00 | 16.96 | 0.927504E+09 | 569.55 | 21.70 | 16.73 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.111144E+10 | 747.74 | 11-JAN-21:00 | 11.10 | 10.22 | 0.153160E+09 | 96.97 | 11-JAN-22:10 | 10.82 | 10.11 |
February | 0.123654E+10 | 827.99 | 27-FEB-19:10 | 15.73 | 11.89 | 0.140610E+09 | 103.19 | 28-FEB-22:10 | 8.12 | 7.00 |
March | 0.174533E+10 | 837.55 | 18-MAR-10:33 | 11.27 | 7.86 | 0.161741E+09 | 102.61 | 10-MAR-22:10 | 11.27 | 7.86 |
April | 0.184448E+10 | 988.56 | 27-APR-18:10 | 25.55 | 15.86 | 0.162966E+09 | 111.65 | 28-APR-21:10 | 12.20 | 10.91 |
May | 0.207876E+10 | 1047.32 | 06-MAY-10:33 | 20.93 | 16.16 | 0.177567E+09 | 114.98 | 05-MAY-21:19 | 20.93 | 16.16 |
June | 0.213079E+10 | 1068.69 | 28-JUN-10:33 | 21.50 | 14.65 | 0.178039E+09 | 117.98 | 28-JUN-22:10 | 17.75 | 13.83 |
July | 0.232496E+10 | 1173.92 | 24-JUL-21:00 | 22.80 | 16.50 | 0.189815E+09 | 120.45 | 31-JUL-21:19 | 21.23 | 16.56 |
August | 0.236299E+10 | 1298.48 | 10-AUG-20:57 | 23.00 | 16.96 | 0.192461E+09 | 120.45 | 24-AUG-21:19 | 23.10 | 17.55 |
September | 0.211011E+10 | 1077.25 | 14-SEP-10:33 | 19.43 | 16.41 | 0.177219E+09 | 118.65 | 14-SEP-21:19 | 17.93 | 14.75 |
October | 0.192234E+10 | 972.37 | 04-OCT-10:33 | 18.33 | 11.02 | 0.170239E+09 | 112.03 | 04-OCT-21:19 | 14.63 | 9.40 |
November | 0.155742E+10 | 887.41 | 04-NOV-10:33 | 17.23 | 14.47 | 0.153625E+09 | 104.54 | 06-NOV-22:10 | 15.10 | 14.35 |
December | 0.126876E+10 | 762.28 | 03-DEC-11:33 | 11.33 | 5.78 | 0.153652E+09 | 96.72 | 05-DEC-22:10 | 4.90 | 1.99 |
Annual Sum or Average | 0.216939E+11 | 0.201110E+10 | ||||||||
Minimum of Months | 0.111144E+10 | 747.74 | 11.10 | 5.78 | 0.140610E+09 | 96.72 | 4.90 | 1.99 | ||
Maximum of Months | 0.236299E+10 | 1298.48 | 25.55 | 16.96 | 0.192461E+09 | 120.45 | 23.10 | 17.55 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.342734E+09 | 419.11 | 11-JAN-19:10 | 12.30 | 9.41 | 0.116774E+09 | 71.44 | 11-JAN-23:10 | 9.22 | 8.15 |
February | 0.515433E+09 | 471.39 | 28-FEB-11:33 | 11.50 | 10.37 | 0.106393E+09 | 75.50 | 27-FEB-23:10 | 11.50 | 10.37 |
March | 0.932782E+09 | 481.99 | 18-MAR-10:33 | 11.27 | 7.86 | 0.120257E+09 | 75.12 | 10-MAR-23:10 | 11.27 | 7.86 |
April | 0.104112E+10 | 573.39 | 29-APR-10:33 | 15.03 | 12.68 | 0.121031E+09 | 82.40 | 27-APR-21:40 | 15.03 | 12.68 |
May | 0.118269E+10 | 613.64 | 06-MAY-10:33 | 20.93 | 16.16 | 0.132048E+09 | 84.92 | 05-MAY-22:10 | 20.93 | 16.16 |
June | 0.121846E+10 | 623.03 | 28-JUN-10:33 | 21.50 | 14.65 | 0.132777E+09 | 87.13 | 28-JUN-22:10 | 17.75 | 13.83 |
July | 0.133292E+10 | 657.57 | 24-JUL-18:10 | 28.72 | 17.86 | 0.141767E+09 | 90.21 | 24-JUL-21:40 | 21.33 | 16.04 |
August | 0.135276E+10 | 665.62 | 10-AUG-18:10 | 30.57 | 19.31 | 0.143784E+09 | 91.33 | 10-AUG-22:10 | 21.82 | 15.74 |
September | 0.120237E+10 | 626.42 | 14-SEP-10:33 | 19.43 | 16.41 | 0.131915E+09 | 87.35 | 14-SEP-21:40 | 17.57 | 14.62 |
October | 0.108233E+10 | 564.00 | 04-OCT-10:33 | 18.33 | 11.02 | 0.126202E+09 | 82.48 | 04-OCT-22:10 | 15.73 | 10.00 |
November | 0.734010E+09 | 512.21 | 04-NOV-10:33 | 17.23 | 14.47 | 0.115235E+09 | 76.68 | 06-NOV-23:10 | 15.40 | 14.28 |
December | 0.451987E+09 | 441.51 | 03-DEC-11:33 | 11.33 | 5.78 | 0.116817E+09 | 70.59 | 05-DEC-23:10 | 4.03 | 2.13 |
Annual Sum or Average | 0.113896E+11 | 0.150500E+10 | ||||||||
Minimum of Months | 0.342734E+09 | 419.11 | 11.27 | 5.78 | 0.106393E+09 | 70.59 | 4.03 | 2.13 | ||
Maximum of Months | 0.135276E+10 | 665.62 | 30.57 | 19.31 | 0.143784E+09 | 91.33 | 21.82 | 16.16 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.481530E+11 | 36766.16 | 11-JAN-21:00 | 11.10 | 10.22 | 0.585811E+09 | 381.60 | 10-JAN-23:10 | 11.10 | 10.22 |
February | 0.440086E+11 | 37231.64 | 27-FEB-21:00 | 12.20 | 10.06 | 0.530816E+09 | 381.61 | 03-FEB-22:10 | 12.20 | 10.06 |
March | 0.496540E+11 | 37364.02 | 14-MAR-20:00 | 14.40 | 9.49 | 0.590910E+09 | 381.68 | 28-MAR-21:10 | 7.70 | 4.73 |
April | 0.487177E+11 | 38175.36 | 27-APR-20:00 | 19.40 | 13.66 | 0.572546E+09 | 381.68 | 28-APR-21:10 | 12.20 | 10.91 |
May | 0.510485E+11 | 38115.47 | 15-MAY-20:00 | 17.20 | 11.19 | 0.593025E+09 | 381.67 | 10-MAY-21:10 | 17.20 | 11.19 |
June | 0.500723E+11 | 38322.53 | 28-JUN-19:55 | 21.70 | 15.30 | 0.575889E+09 | 381.71 | 26-JUN-21:10 | 21.70 | 15.30 |
July | 0.519930E+11 | 38591.13 | 24-JUL-20:00 | 23.90 | 16.63 | 0.595000E+09 | 381.65 | 12-JUL-21:10 | 23.90 | 16.63 |
August | 0.524004E+11 | 38660.34 | 10-AUG-20:00 | 25.60 | 17.66 | 0.596887E+09 | 381.69 | 08-AUG-21:10 | 25.60 | 17.66 |
September | 0.496787E+11 | 38250.48 | 14-SEP-20:00 | 18.90 | 14.81 | 0.574817E+09 | 381.70 | 05-SEP-21:10 | 18.90 | 14.81 |
October | 0.501330E+11 | 37858.86 | 04-OCT-20:00 | 17.20 | 10.66 | 0.591919E+09 | 381.68 | 06-OCT-21:10 | 12.70 | 10.58 |
November | 0.475180E+11 | 37111.38 | 02-NOV-20:00 | 12.80 | 10.42 | 0.569820E+09 | 381.63 | 16-NOV-22:10 | 5.40 | 4.66 |
December | 0.482648E+11 | 36691.63 | 05-DEC-21:00 | 5.60 | 1.73 | 0.586425E+09 | 381.64 | 22-DEC-22:10 | 2.10 | 1.63 |
Annual Sum or Average | 0.591642E+12 | 0.696387E+10 | ||||||||
Minimum of Months | 0.440086E+11 | 36691.63 | 5.60 | 1.73 | 0.530816E+09 | 381.60 | 2.10 | 1.63 | ||
Maximum of Months | 0.524004E+11 | 38660.34 | 25.60 | 17.66 | 0.596887E+09 | 381.71 | 25.60 | 17.66 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.149792E+11 | 9465.09 | 08-JAN-11:35 | 1.33 | 0.94 | 0.866360E+10 | 5749.24 | 11-JAN-22:40 | 9.97 | 8.97 |
February | 0.155555E+11 | 10937.42 | 08-FEB-13:30 | 6.40 | 3.77 | 0.808642E+10 | 6213.71 | 27-FEB-22:40 | 12.20 | 10.25 |
March | 0.188479E+11 | 12724.48 | 02-MAR-13:20 | 12.57 | 7.60 | 0.928564E+10 | 6368.41 | 14-MAR-21:40 | 12.40 | 8.44 |
April | 0.197376E+11 | 11668.75 | 27-APR-14:10 | 26.28 | 16.91 | 0.918430E+10 | 6462.70 | 27-APR-22:10 | 14.40 | 11.00 |
May | 0.211454E+11 | 11381.55 | 04-MAY-14:10 | 23.98 | 15.25 | 0.965283E+10 | 6462.75 | 04-MAY-22:10 | 18.43 | 12.09 |
June | 0.211148E+11 | 10668.45 | 10-JUN-10:33 | 20.20 | 14.80 | 0.950875E+10 | 6462.71 | 28-JUN-22:10 | 17.75 | 13.83 |
July | 0.229289E+11 | 11382.64 | 30-JUL-10:33 | 23.33 | 16.24 | 0.100424E+11 | 6462.74 | 20-JUL-22:10 | 23.33 | 16.24 |
August | 0.236026E+11 | 13252.01 | 24-AUG-15:03 | 29.62 | 19.18 | 0.102012E+11 | 6462.78 | 11-AUG-22:10 | 29.62 | 19.18 |
September | 0.218611E+11 | 14068.15 | 23-SEP-13:15 | 22.57 | 17.43 | 0.962877E+10 | 6462.78 | 11-SEP-22:10 | 22.57 | 17.43 |
October | 0.201613E+11 | 14123.84 | 04-OCT-12:50 | 20.60 | 11.27 | 0.949663E+10 | 6462.61 | 04-OCT-21:30 | 15.00 | 9.56 |
November | 0.162247E+11 | 12716.09 | 04-NOV-13:30 | 20.85 | 16.00 | 0.863797E+10 | 5968.02 | 02-NOV-21:40 | 20.85 | 16.00 |
December | 0.154505E+11 | 10447.00 | 02-DEC-11:33 | 11.83 | 6.03 | 0.873422E+10 | 5890.99 | 05-DEC-22:40 | 4.60 | 2.18 |
Annual Sum or Average | 0.231609E+12 | 0.111123E+12 | ||||||||
Minimum of Months | 0.149792E+11 | 9465.09 | 1.33 | 0.94 | 0.808642E+10 | 5749.24 | 4.60 | 2.18 | ||
Maximum of Months | 0.236026E+11 | 14123.84 | 29.62 | 19.18 | 0.102012E+11 | 6462.78 | 29.62 | 19.18 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.553353E+11 | 26379.15 | 11-JAN-22:00 | 11.10 | 10.49 | 0.277647E+11 | 18393.91 | 11-JAN-23:10 | 9.22 | 8.15 |
February | 0.528331E+11 | 28454.18 | 27-FEB-21:00 | 12.20 | 10.06 | 0.257770E+11 | 19183.09 | 27-FEB-22:00 | 12.20 | 10.35 |
March | 0.618554E+11 | 29204.60 | 14-MAR-21:20 | 12.60 | 8.62 | 0.295573E+11 | 19183.19 | 02-MAR-22:49 | 12.60 | 8.62 |
April | 0.628565E+11 | 34277.33 | 27-APR-21:10 | 16.73 | 11.41 | 0.291297E+11 | 19186.16 | 27-APR-22:10 | 14.40 | 11.00 |
May | 0.675360E+11 | 34319.19 | 04-MAY-21:52 | 18.90 | 12.17 | 0.306917E+11 | 19186.32 | 15-MAY-21:30 | 13.35 | 11.02 |
June | 0.674263E+11 | 35106.36 | 28-JUN-21:52 | 18.30 | 14.03 | 0.301400E+11 | 19186.27 | 27-JUN-22:10 | 18.30 | 14.03 |
July | 0.726260E+11 | 37863.37 | 24-JUL-21:10 | 22.43 | 16.40 | 0.314640E+11 | 19186.25 | 21-JUL-22:10 | 22.43 | 16.40 |
August | 0.740916E+11 | 39345.61 | 10-AUG-21:05 | 22.92 | 16.74 | 0.317183E+11 | 19186.24 | 31-AUG-22:10 | 16.50 | 13.64 |
September | 0.681526E+11 | 37737.92 | 14-SEP-21:10 | 18.12 | 14.82 | 0.302020E+11 | 19186.25 | 11-SEP-22:10 | 18.12 | 14.82 |
October | 0.648630E+11 | 35229.85 | 04-OCT-21:10 | 14.27 | 9.23 | 0.301794E+11 | 19186.00 | 04-OCT-21:30 | 15.00 | 9.56 |
November | 0.571879E+11 | 29161.79 | 04-NOV-10:33 | 17.23 | 14.47 | 0.277876E+11 | 18960.42 | 06-NOV-23:10 | 15.40 | 14.28 |
December | 0.562701E+11 | 27573.83 | 03-DEC-11:33 | 11.33 | 5.78 | 0.280199E+11 | 18758.20 | 05-DEC-22:49 | 4.50 | 2.23 |
Annual Sum or Average | 0.761034E+12 | 0.352432E+12 | ||||||||
Minimum of Months | 0.528331E+11 | 26379.15 | 11.10 | 5.78 | 0.257770E+11 | 18393.91 | 4.50 | 2.23 | ||
Maximum of Months | 0.740916E+11 | 39345.61 | 22.92 | 16.74 | 0.317183E+11 | 19186.32 | 22.43 | 16.40 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 11832991.99 | 2782.23 | 05-JAN-16:01 | 5.73 | 4.38 | 93899893.71 | 56.69 | 17-JAN-04:19 | 1.70 | -0.1 |
February | 84029528.17 | 3739.23 | 12-FEB-16:01 | 6.52 | 1.59 | 86018417.81 | 56.69 | 27-FEB-22:19 | 12.20 | 10.16 |
March | 0.254152E+09 | 3783.66 | 25-MAR-15:01 | 11.70 | 3.86 | 96555957.90 | 56.69 | 18-MAR-23:40 | 11.70 | 3.86 |
April | 0.658433E+09 | 3769.96 | 13-APR-18:01 | 16.52 | 9.25 | 94556866.54 | 56.69 | 27-APR-21:30 | 15.80 | 11.30 |
May | 0.114736E+10 | 3905.88 | 14-MAY-18:01 | 21.83 | 11.88 | 98433889.40 | 56.69 | 15-MAY-21:19 | 13.53 | 10.95 |
June | 0.132749E+10 | 3398.63 | 23-JUN-15:01 | 16.88 | 12.55 | 95569783.84 | 56.70 | 28-JUN-21:00 | 18.30 | 14.03 |
July | 0.193539E+10 | 3403.01 | 25-JUL-08:61 | 15.18 | 13.46 | 98822502.00 | 56.70 | 31-JUL-22:49 | 19.05 | 15.07 |
August | 0.186452E+10 | 3457.93 | 18-AUG-15:01 | 20.62 | 14.05 | 98892538.93 | 56.70 | 24-AUG-22:00 | 20.20 | 16.47 |
September | 0.129315E+10 | 3421.22 | 22-SEP-18:01 | 20.40 | 16.20 | 95169088.32 | 56.70 | 13-SEP-21:30 | 20.40 | 16.20 |
October | 0.455714E+09 | 3737.16 | 03-OCT-18:01 | 16.02 | 9.78 | 96996174.87 | 56.69 | 06-OCT-21:10 | 12.70 | 10.58 |
November | 66261091.04 | 3240.64 | 04-NOV-15:01 | 20.92 | 15.94 | 91949862.42 | 56.69 | 04-NOV-23:10 | 13.30 | 12.93 |
December | 18808888.64 | 3143.59 | 10-DEC-16:01 | 9.72 | 8.43 | 94195360.83 | 56.69 | 12-DEC-04:19 | 1.33 | 1.33 |
Annual Sum or Average | 0.911714E+10 | 0.114106E+10 | ||||||||
Minimum of Months | 11832991.99 | 2782.23 | 5.73 | 1.59 | 86018417.81 | 56.69 | 1.33 | -0.1 | ||
Maximum of Months | 0.193539E+10 | 3905.88 | 21.83 | 16.20 | 98892538.93 | 56.70 | 20.40 | 16.47 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 6659749.85 | 442.14 | 20-JAN-16:03 | 5.40 | 3.78 | 93227159.84 | 56.69 | 17-JAN-04:19 | 5.40 | 3.78 |
February | 29528734.82 | 3116.07 | 12-FEB-16:01 | 6.52 | 1.59 | 85150177.36 | 56.69 | 14-FEB-04:19 | 0.93 | -0.1 |
March | 0.107994E+09 | 3382.76 | 25-MAR-15:01 | 11.70 | 3.86 | 95837623.01 | 57.40 | 14-MAR-18:10 | 11.70 | 3.86 |
April | 0.406250E+09 | 3893.21 | 25-APR-17:41 | 14.60 | 8.96 | 95253795.41 | 73.61 | 27-APR-21:40 | 15.33 | 11.23 |
May | 0.771572E+09 | 3461.03 | 29-MAY-19:41 | 13.27 | 10.89 | 0.103462E+09 | 83.84 | 31-MAY-18:10 | 20.40 | 14.89 |
June | 0.958500E+09 | 3485.39 | 18-JUN-20:11 | 14.63 | 11.86 | 0.102402E+09 | 86.52 | 19-JUN-18:10 | 19.22 | 12.49 |
July | 0.138303E+10 | 3648.35 | 25-JUL-16:51 | 25.60 | 18.36 | 0.109588E+09 | 90.53 | 21-JUL-18:10 | 25.60 | 18.36 |
August | 0.133998E+10 | 3526.86 | 02-AUG-18:11 | 14.53 | 12.84 | 0.105846E+09 | 80.09 | 08-AUG-21:10 | 24.15 | 15.61 |
September | 0.745010E+09 | 3542.28 | 22-SEP-16:11 | 24.43 | 17.44 | 0.100734E+09 | 79.63 | 08-SEP-18:10 | 24.43 | 17.44 |
October | 0.207370E+09 | 3159.30 | 06-OCT-15:01 | 17.30 | 12.22 | 96848665.10 | 70.84 | 04-OCT-21:10 | 17.30 | 12.22 |
November | 28875508.34 | 2923.63 | 04-NOV-15:01 | 20.92 | 15.94 | 91377782.64 | 56.69 | 04-NOV-23:10 | 13.30 | 12.93 |
December | 6988074.06 | 1063.82 | 02-DEC-16:01 | 10.40 | 4.47 | 93418721.21 | 56.69 | 26-DEC-04:19 | -0.9 | -0.9 |
Annual Sum or Average | 0.599176E+10 | 0.117315E+10 | ||||||||
Minimum of Months | 6659749.85 | 442.14 | 5.40 | 1.59 | 85150177.36 | 56.69 | -0.9 | -0.9 | ||
Maximum of Months | 0.138303E+10 | 3893.21 | 25.60 | 18.36 | 0.109588E+09 | 90.53 | 25.60 | 18.36 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8738062.53 | 129.71 | 08-JAN-15:15 | 5.20 | 2.41 | 0.00 | 0.00 | 01-JAN-00:10 | 5.20 | 2.41 |
February | 61914643.11 | 475.70 | 08-FEB-13:40 | 6.50 | 3.79 | 0.00 | 0.00 | 01-FEB-00:10 | 6.50 | 3.79 |
March | 0.165703E+09 | 605.89 | 02-MAR-13:00 | 12.20 | 7.34 | 0.00 | 0.00 | 01-MAR-00:10 | 12.20 | 7.34 |
April | 0.260067E+09 | 550.05 | 27-APR-13:05 | 26.10 | 16.37 | 0.00 | 0.00 | 01-APR-00:10 | 26.10 | 16.37 |
May | 0.325207E+09 | 530.52 | 04-MAY-13:20 | 22.77 | 15.31 | 0.00 | 0.00 | 01-MAY-00:10 | 22.77 | 15.31 |
June | 0.359694E+09 | 399.86 | 28-JUN-13:05 | 24.50 | 15.71 | 0.00 | 0.00 | 01-JUN-00:10 | 24.50 | 15.71 |
July | 0.485950E+09 | 499.21 | 31-JUL-13:20 | 27.57 | 18.47 | 0.00 | 0.00 | 01-JUL-00:10 | 27.57 | 18.47 |
August | 0.547027E+09 | 626.10 | 24-AUG-13:05 | 28.93 | 19.36 | 0.00 | 0.00 | 01-AUG-00:10 | 28.93 | 19.36 |
September | 0.467400E+09 | 670.75 | 14-SEP-13:30 | 23.35 | 17.43 | 0.00 | 0.00 | 01-SEP-00:10 | 23.35 | 17.43 |
October | 0.279338E+09 | 700.17 | 04-OCT-12:40 | 20.60 | 11.32 | 0.00 | 0.00 | 01-OCT-00:10 | 20.60 | 11.32 |
November | 57323539.07 | 542.82 | 04-NOV-13:30 | 20.85 | 16.00 | 0.00 | 0.00 | 01-NOV-00:10 | 20.85 | 16.00 |
December | 32369909.92 | 432.40 | 05-DEC-12:30 | 10.30 | 6.13 | 0.00 | 0.00 | 01-DEC-00:10 | 10.30 | 6.13 |
Annual Sum or Average | 0.305073E+10 | 0.00 | ||||||||
Minimum of Months | 8738062.53 | 129.71 | 5.20 | 2.41 | 0.00 | 0.00 | 5.20 | 2.41 | ||
Maximum of Months | 0.547027E+09 | 700.17 | 28.93 | 19.36 | 0.00 | 0.00 | 28.93 | 19.36 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 74977347.93 | 808.46 | 01-JAN-09:02 | 7.80 | 6.49 | 95175589.53 | 56.69 | 11-JAN-22:10 | 10.82 | 10.11 |
February | 0.111168E+09 | 909.70 | 26-FEB-09:02 | 9.60 | 8.77 | 86418366.02 | 56.69 | 27-FEB-22:10 | 12.20 | 10.11 |
March | 0.226056E+09 | 992.67 | 28-MAR-18:01 | 10.92 | 4.32 | 96579252.53 | 56.69 | 09-MAR-22:10 | 10.92 | 4.32 |
April | 0.339639E+09 | 1029.71 | 01-APR-21:52 | 20.60 | 9.92 | 94678050.56 | 70.01 | 27-APR-21:00 | 14.40 | 11.03 |
May | 0.461595E+09 | 1093.96 | 14-MAY-21:51 | 16.70 | 9.76 | 99968129.83 | 75.73 | 15-MAY-21:10 | 13.72 | 10.88 |
June | 0.521547E+09 | 1010.03 | 22-JUN-21:51 | 15.60 | 12.67 | 98887542.96 | 74.38 | 22-JUN-21:49 | 15.60 | 12.67 |
July | 0.590220E+09 | 1017.51 | 25-JUL-15:02 | 22.98 | 16.69 | 0.103564E+09 | 76.31 | 26-JUL-21:10 | 20.68 | 16.76 |
August | 0.578615E+09 | 1015.09 | 08-AUG-21:31 | 23.70 | 15.01 | 0.102709E+09 | 73.93 | 18-AUG-21:10 | 15.13 | 12.34 |
September | 0.426144E+09 | 1008.00 | 11-SEP-15:01 | 23.30 | 15.89 | 97242937.74 | 72.33 | 13-SEP-21:49 | 18.30 | 14.68 |
October | 0.291501E+09 | 1016.02 | 02-OCT-18:01 | 14.32 | 8.97 | 96949203.91 | 68.33 | 04-OCT-21:10 | 14.27 | 9.23 |
November | 0.163895E+09 | 901.27 | 05-NOV-08:62 | 12.88 | 12.19 | 92910215.64 | 56.69 | 06-NOV-23:30 | 15.00 | 13.69 |
December | 76656931.62 | 941.01 | 03-DEC-09:02 | 7.98 | 3.60 | 95225712.45 | 56.69 | 12-DEC-04:19 | 1.33 | 1.33 |
Annual Sum or Average | 0.386202E+10 | 0.116031E+10 | ||||||||
Minimum of Months | 74977347.93 | 808.46 | 7.80 | 3.60 | 86418366.02 | 56.69 | 1.33 | 1.33 | ||
Maximum of Months | 0.590220E+09 | 1093.96 | 23.70 | 16.69 | 0.103564E+09 | 76.31 | 20.68 | 16.76 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 12165589.78 | 471.52 | 20-JAN-16:02 | 5.40 | 3.78 | 93820006.30 | 56.69 | 17-JAN-04:19 | 5.40 | 3.78 |
February | 78663920.26 | 3222.62 | 12-FEB-16:01 | 6.52 | 1.59 | 86069873.27 | 56.69 | 19-FEB-02:20 | -4.0 | -4.7 |
March | 0.249291E+09 | 3438.76 | 25-MAR-08:61 | 4.78 | 0.26 | 96767147.90 | 56.69 | 18-MAR-23:19 | 4.78 | 0.26 |
April | 0.674947E+09 | 3319.40 | 13-APR-18:01 | 16.52 | 9.25 | 94898051.54 | 56.69 | 29-APR-23:00 | 15.00 | 12.75 |
May | 0.101000E+10 | 3491.51 | 14-MAY-18:01 | 21.83 | 11.88 | 98495565.58 | 56.69 | 15-MAY-21:10 | 13.72 | 10.88 |
June | 0.139221E+10 | 3120.84 | 18-JUN-08:62 | 12.57 | 10.53 | 95738974.97 | 56.70 | 28-JUN-21:30 | 17.50 | 13.87 |
July | 0.169940E+10 | 3138.89 | 11-JUL-15:01 | 21.88 | 17.19 | 98894271.43 | 56.70 | 24-JUL-22:49 | 19.60 | 15.45 |
August | 0.183390E+10 | 3191.38 | 25-AUG-08:61 | 19.83 | 16.44 | 99014203.29 | 56.70 | 25-AUG-21:30 | 21.25 | 16.32 |
September | 0.117965E+10 | 3168.61 | 23-SEP-08:61 | 14.27 | 13.74 | 95140588.47 | 56.70 | 12-SEP-21:40 | 14.27 | 13.74 |
October | 0.447314E+09 | 3281.83 | 03-OCT-18:01 | 16.02 | 9.78 | 97115979.28 | 56.69 | 04-OCT-23:40 | 13.50 | 9.95 |
November | 71102019.48 | 3167.07 | 04-NOV-15:01 | 20.92 | 15.94 | 91923667.38 | 56.69 | 04-NOV-23:10 | 13.30 | 12.93 |
December | 27289292.31 | 2377.31 | 02-DEC-09:02 | 8.58 | 4.35 | 94115969.73 | 56.69 | 26-DEC-04:19 | -0.9 | -0.9 |
Annual Sum or Average | 0.867593E+10 | 0.114199E+10 | ||||||||
Minimum of Months | 12165589.78 | 471.52 | 4.78 | 0.26 | 86069873.27 | 56.69 | -4.0 | -4.7 | ||
Maximum of Months | 0.183390E+10 | 3491.51 | 21.88 | 17.19 | 99014203.29 | 56.70 | 21.25 | 16.32 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5902699.24 | 354.13 | 27-JAN-19:06 | 8.30 | 5.90 | 93158393.40 | 56.69 | 17-JAN-04:19 | 8.30 | 5.90 |
February | 25640873.50 | 2509.90 | 27-FEB-16:01 | 19.32 | 12.38 | 85089899.06 | 56.69 | 14-FEB-04:19 | 19.32 | 12.38 |
March | 0.100108E+09 | 3157.57 | 25-MAR-08:61 | 4.78 | 0.26 | 95879193.53 | 56.69 | 19-MAR-01:19 | 4.78 | 0.26 |
April | 0.430995E+09 | 3130.84 | 25-APR-18:01 | 13.95 | 8.77 | 95203236.98 | 71.11 | 27-APR-21:40 | 15.33 | 11.23 |
May | 0.719269E+09 | 3387.43 | 06-MAY-08:51 | 19.40 | 15.38 | 0.100907E+09 | 75.83 | 15-MAY-21:10 | 13.72 | 10.88 |
June | 0.106713E+10 | 3205.99 | 10-JUN-08:51 | 18.30 | 14.28 | 0.100536E+09 | 74.47 | 21-JUN-21:40 | 16.33 | 12.50 |
July | 0.125029E+10 | 3662.15 | 24-JUL-08:32 | 23.17 | 16.50 | 0.105464E+09 | 77.58 | 24-JUL-21:19 | 22.07 | 16.28 |
August | 0.132918E+10 | 3578.19 | 10-AUG-08:32 | 22.00 | 17.03 | 0.104789E+09 | 77.44 | 08-AUG-21:10 | 22.00 | 17.03 |
September | 0.714696E+09 | 3324.97 | 13-SEP-08:51 | 18.30 | 15.25 | 98265335.46 | 74.44 | 13-SEP-21:40 | 18.30 | 14.73 |
October | 0.208233E+09 | 2803.02 | 07-OCT-08:61 | 10.18 | 9.20 | 96627653.04 | 67.19 | 04-OCT-21:10 | 10.18 | 9.20 |
November | 30221871.52 | 2465.33 | 04-NOV-15:01 | 20.92 | 15.94 | 91280826.95 | 56.69 | 12-NOV-02:20 | 2.80 | 2.46 |
December | 7783159.08 | 812.59 | 02-DEC-09:02 | 8.58 | 4.35 | 93326230.91 | 56.69 | 26-DEC-04:19 | -0.9 | -0.9 |
Annual Sum or Average | 0.588945E+10 | 0.116053E+10 | ||||||||
Minimum of Months | 5902699.24 | 354.13 | 4.78 | 0.26 | 85089899.06 | 56.69 | -0.9 | -0.9 | ||
Maximum of Months | 0.132918E+10 | 3662.15 | 23.17 | 17.03 | 0.105464E+09 | 77.58 | 22.07 | 17.03 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.189700E+10 | 1574.00 | 11-JAN-21:00 | 11.10 | 10.22 | 0.119930E+10 | 722.26 | 11-JAN-22:49 | 9.68 | 8.60 |
February | 0.241833E+10 | 1788.66 | 27-FEB-19:10 | 15.73 | 11.89 | 0.109023E+10 | 756.31 | 27-FEB-23:10 | 12.20 | 10.40 |
March | 0.357212E+10 | 1900.42 | 25-MAR-10:33 | 8.87 | 1.80 | 0.123326E+10 | 768.66 | 02-MAR-22:49 | 8.87 | 1.80 |
April | 0.401413E+10 | 2241.77 | 27-APR-18:10 | 25.55 | 15.86 | 0.123744E+10 | 840.83 | 27-APR-21:40 | 15.33 | 11.23 |
May | 0.458348E+10 | 2340.16 | 06-MAY-10:33 | 20.93 | 16.16 | 0.135294E+10 | 861.72 | 15-MAY-21:40 | 13.17 | 11.09 |
June | 0.466864E+10 | 2398.50 | 28-JUN-10:33 | 21.50 | 14.65 | 0.134908E+10 | 880.83 | 28-JUN-22:10 | 17.75 | 13.83 |
July | 0.510409E+10 | 2532.57 | 24-JUL-18:10 | 28.72 | 17.86 | 0.143913E+10 | 908.53 | 24-JUL-21:40 | 21.33 | 16.04 |
August | 0.518568E+10 | 2578.50 | 13-AUG-10:33 | 24.17 | 17.28 | 0.145998E+10 | 920.07 | 10-AUG-21:40 | 24.17 | 17.28 |
September | 0.462786E+10 | 2480.27 | 14-SEP-10:33 | 19.43 | 16.41 | 0.134484E+10 | 904.20 | 14-SEP-21:40 | 17.57 | 14.62 |
October | 0.396640E+10 | 2202.16 | 04-OCT-10:33 | 18.33 | 11.02 | 0.127185E+10 | 839.57 | 04-OCT-22:10 | 15.73 | 10.00 |
November | 0.266014E+10 | 1910.63 | 04-NOV-10:33 | 17.23 | 14.47 | 0.116846E+10 | 745.94 | 05-NOV-23:19 | 11.10 | 9.49 |
December | 0.209622E+10 | 1736.49 | 03-DEC-11:33 | 11.33 | 5.78 | 0.120002E+10 | 725.63 | 05-DEC-22:49 | 4.50 | 2.23 |
Annual Sum or Average | 0.447941E+11 | 0.153465E+11 | ||||||||
Minimum of Months | 0.189700E+10 | 1574.00 | 8.87 | 1.80 | 0.109023E+10 | 722.26 | 4.50 | 1.80 | ||
Maximum of Months | 0.518568E+10 | 2578.50 | 28.72 | 17.86 | 0.145998E+10 | 920.07 | 24.17 | 17.28 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8214409.01 | 2846.45 | 05-JAN-16:01 | 5.73 | 4.38 | 93258913.14 | 56.69 | 17-JAN-04:19 | 1.70 | -0.1 |
February | 71413914.50 | 3880.23 | 12-FEB-16:01 | 6.52 | 1.59 | 85527114.74 | 56.69 | 17-FEB-04:19 | 1.50 | -0.2 |
March | 0.236488E+09 | 3937.58 | 25-MAR-15:01 | 11.70 | 3.86 | 96180250.91 | 56.69 | 19-MAR-00:30 | 11.70 | 3.86 |
April | 0.639447E+09 | 3924.50 | 13-APR-18:01 | 16.52 | 9.25 | 94359577.84 | 56.69 | 28-APR-00:00 | 14.40 | 12.20 |
May | 0.113078E+10 | 4071.74 | 14-MAY-18:01 | 21.83 | 11.88 | 98306593.21 | 56.69 | 26-MAY-22:19 | 10.73 | 10.73 |
June | 0.132558E+10 | 3537.66 | 23-JUN-15:01 | 16.88 | 12.55 | 95496303.66 | 56.70 | 22-JUN-21:00 | 16.88 | 12.55 |
July | 0.197377E+10 | 3436.55 | 24-JUL-08:61 | 22.07 | 16.26 | 98747575.79 | 56.70 | 27-JUL-21:30 | 18.35 | 14.93 |
August | 0.185966E+10 | 3586.09 | 18-AUG-15:01 | 20.62 | 14.05 | 98805029.62 | 56.70 | 24-AUG-22:30 | 21.05 | 16.84 |
September | 0.124308E+10 | 3549.10 | 22-SEP-18:01 | 20.40 | 16.20 | 94992808.72 | 56.69 | 22-SEP-22:49 | 15.78 | 14.24 |
October | 0.390621E+09 | 3919.09 | 04-OCT-18:01 | 17.52 | 10.01 | 96644800.63 | 56.69 | 16-OCT-21:30 | 9.70 | 8.39 |
November | 55918450.57 | 3356.65 | 04-NOV-18:01 | 15.00 | 13.34 | 91429214.06 | 56.69 | 05-NOV-02:30 | 13.05 | 12.26 |
December | 12699577.90 | 3220.79 | 10-DEC-16:01 | 9.72 | 8.43 | 93652902.22 | 56.69 | 22-DEC-04:19 | 0.20 | -0.9 |
Annual Sum or Average | 0.894768E+10 | 0.113740E+10 | ||||||||
Minimum of Months | 8214409.01 | 2846.45 | 5.73 | 1.59 | 85527114.74 | 56.69 | 0.20 | -0.9 | ||
Maximum of Months | 0.197377E+10 | 4071.74 | 22.07 | 16.26 | 98805029.62 | 56.70 | 21.05 | 16.84 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1996174.39 | 432.48 | 20-JAN-16:05 | 5.40 | 3.78 | 92708419.71 | 56.69 | 16-JAN-02:20 | 5.40 | 3.78 |
February | 20440061.53 | 3052.08 | 26-FEB-16:01 | 14.40 | 10.25 | 84651624.81 | 56.69 | 14-FEB-04:19 | 14.40 | 10.25 |
March | 90684292.42 | 3471.91 | 25-MAR-15:01 | 11.70 | 3.86 | 95441348.91 | 60.83 | 14-MAR-18:10 | 11.70 | 3.86 |
April | 0.381677E+09 | 4036.24 | 25-APR-17:41 | 14.60 | 8.96 | 95258835.56 | 75.79 | 26-APR-21:19 | 14.67 | 10.66 |
May | 0.755337E+09 | 4031.89 | 21-MAY-17:41 | 15.60 | 9.45 | 0.104445E+09 | 90.41 | 31-MAY-18:10 | 20.40 | 14.89 |
June | 0.970660E+09 | 3674.11 | 19-JUN-21:51 | 16.70 | 12.03 | 0.103518E+09 | 94.03 | 19-JUN-21:10 | 16.70 | 12.03 |
July | 0.145249E+10 | 3788.39 | 19-JUL-21:51 | 16.70 | 12.02 | 0.111287E+09 | 97.08 | 21-JUL-21:10 | 17.12 | 12.73 |
August | 0.135485E+10 | 3715.74 | 06-AUG-21:51 | 17.90 | 14.41 | 0.106358E+09 | 83.64 | 11-AUG-18:10 | 20.88 | 15.38 |
September | 0.691410E+09 | 3656.96 | 22-SEP-16:11 | 24.43 | 17.44 | 0.101584E+09 | 86.85 | 08-SEP-18:10 | 24.43 | 17.44 |
October | 0.151049E+09 | 3267.18 | 07-OCT-15:01 | 18.03 | 12.32 | 96485916.51 | 71.48 | 04-OCT-21:10 | 18.03 | 12.32 |
November | 19288948.37 | 3004.83 | 04-NOV-15:01 | 20.92 | 15.94 | 90838958.26 | 56.69 | 29-NOV-00:20 | 8.00 | 7.36 |
December | 3466904.39 | 359.90 | 29-DEC-19:06 | 9.32 | 7.90 | 92884539.99 | 56.69 | 12-DEC-04:19 | 9.32 | 7.90 |
Annual Sum or Average | 0.589335E+10 | 0.117546E+10 | ||||||||
Minimum of Months | 1996174.39 | 359.90 | 5.40 | 3.78 | 84651624.81 | 56.69 | 5.40 | 3.78 | ||
Maximum of Months | 0.145249E+10 | 4036.24 | 24.43 | 17.44 | 0.111287E+09 | 97.08 | 24.43 | 17.44 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 68836498.76 | 1976.31 | 05-JAN-16:01 | 5.73 | 4.38 | 95187880.77 | 56.69 | 20-JAN-04:19 | -0.4 | -0.8 |
February | 0.229836E+09 | 2126.45 | 26-FEB-16:01 | 14.40 | 10.25 | 87134909.51 | 56.69 | 27-FEB-23:10 | 12.20 | 10.40 |
March | 0.399456E+09 | 2450.94 | 25-MAR-15:01 | 11.70 | 3.86 | 97421529.59 | 56.69 | 18-MAR-23:40 | 11.70 | 3.86 |
April | 0.591384E+09 | 2360.62 | 13-APR-18:01 | 16.52 | 9.25 | 94999841.17 | 56.69 | 27-APR-21:10 | 16.73 | 11.41 |
May | 0.735303E+09 | 2438.96 | 14-MAY-18:01 | 21.83 | 11.88 | 98484010.23 | 56.69 | 06-MAY-23:49 | 21.83 | 11.88 |
June | 0.818758E+09 | 2170.71 | 25-JUN-08:61 | 15.78 | 11.63 | 95559299.48 | 56.69 | 08-JUN-21:30 | 15.78 | 11.63 |
July | 0.107508E+10 | 2184.61 | 11-JUL-15:01 | 21.88 | 17.19 | 98727263.04 | 56.70 | 24-JUL-21:00 | 20.60 | 15.77 |
August | 0.117383E+10 | 2211.69 | 18-AUG-15:01 | 20.62 | 14.05 | 98825093.88 | 56.70 | 29-AUG-21:00 | 19.90 | 15.56 |
September | 0.978858E+09 | 2224.92 | 22-SEP-18:01 | 20.40 | 16.20 | 95255869.11 | 56.70 | 14-SEP-21:00 | 20.40 | 16.20 |
October | 0.584753E+09 | 2412.00 | 04-OCT-18:01 | 17.52 | 10.01 | 97732182.76 | 56.69 | 04-OCT-21:10 | 14.27 | 9.23 |
November | 0.171239E+09 | 2143.39 | 02-NOV-15:01 | 13.30 | 11.14 | 92987808.11 | 56.69 | 04-NOV-23:10 | 13.30 | 12.93 |
December | 0.130980E+09 | 2123.83 | 10-DEC-16:01 | 9.72 | 8.43 | 95361021.54 | 56.69 | 04-DEC-00:20 | 9.72 | 8.43 |
Annual Sum or Average | 0.695831E+10 | 0.114768E+10 | ||||||||
Minimum of Months | 68836498.76 | 1976.31 | 5.73 | 3.86 | 87134909.51 | 56.69 | -0.4 | -0.8 | ||
Maximum of Months | 0.117383E+10 | 2450.94 | 21.88 | 17.19 | 98825093.88 | 56.70 | 21.83 | 16.20 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.314696E+11 | 18024.62 | 11-JAN-23:00 | 9.40 | 8.23 | 0.189072E+11 | 11347.93 | 20-JAN-04:19 | -0.4 | -0.8 |
February | 0.292260E+11 | 19050.19 | 27-FEB-23:00 | 12.20 | 10.35 | 0.171628E+11 | 11347.91 | 10-FEB-04:19 | 12.20 | 10.35 |
March | 0.341390E+11 | 18939.41 | 10-MAR-23:00 | 11.10 | 10.84 | 0.192030E+11 | 11347.94 | 30-MAR-23:19 | 7.60 | 4.67 |
April | 0.348895E+11 | 20763.65 | 27-APR-21:10 | 16.73 | 11.41 | 0.186076E+11 | 11349.01 | 27-APR-22:10 | 14.40 | 11.00 |
May | 0.381110E+11 | 21101.62 | 05-MAY-21:53 | 17.80 | 12.72 | 0.192908E+11 | 11349.23 | 15-MAY-21:30 | 13.35 | 11.02 |
June | 0.384357E+11 | 21541.59 | 28-JUN-21:52 | 18.30 | 14.03 | 0.187215E+11 | 11349.22 | 27-JUN-22:10 | 18.30 | 14.03 |
July | 0.408682E+11 | 22260.17 | 24-JUL-21:10 | 22.43 | 16.40 | 0.192853E+11 | 11349.21 | 21-JUL-22:10 | 22.43 | 16.40 |
August | 0.408698E+11 | 22252.06 | 10-AUG-21:52 | 22.50 | 15.63 | 0.193584E+11 | 11349.20 | 11-AUG-22:10 | 15.85 | 13.74 |
September | 0.370639E+11 | 20993.24 | 12-SEP-21:52 | 18.30 | 14.27 | 0.186448E+11 | 11349.20 | 11-SEP-22:10 | 18.30 | 14.27 |
October | 0.351800E+11 | 19842.50 | 04-OCT-22:00 | 16.10 | 10.03 | 0.191637E+11 | 11348.80 | 04-OCT-21:30 | 16.10 | 10.03 |
November | 0.320508E+11 | 18994.71 | 06-NOV-23:00 | 15.60 | 14.58 | 0.184121E+11 | 11347.85 | 09-NOV-00:20 | 7.97 | 6.86 |
December | 0.316566E+11 | 17779.87 | 29-DEC-23:00 | 8.90 | 7.76 | 0.189473E+11 | 11348.12 | 04-DEC-00:20 | 8.90 | 7.76 |
Annual Sum or Average | 0.423960E+12 | 0.225705E+12 | ||||||||
Minimum of Months | 0.292260E+11 | 17779.87 | 8.90 | 7.76 | 0.171628E+11 | 11347.85 | -0.4 | -0.8 | ||
Maximum of Months | 0.408698E+11 | 22260.17 | 22.50 | 16.40 | 0.193584E+11 | 11349.23 | 22.43 | 16.40 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.352262E+11 | 20072.51 | 11-JAN-22:10 | 10.82 | 10.11 | 0.191075E+11 | 11347.97 | 17-JAN-04:19 | 1.70 | -0.1 |
February | 0.326637E+11 | 20862.22 | 27-FEB-23:00 | 12.20 | 10.35 | 0.173173E+11 | 11347.95 | 10-FEB-04:19 | 12.20 | 10.35 |
March | 0.380223E+11 | 20842.23 | 08-MAR-23:00 | 13.90 | 9.29 | 0.193135E+11 | 11347.96 | 30-MAR-23:19 | 7.60 | 4.67 |
April | 0.385910E+11 | 22275.99 | 27-APR-21:10 | 16.73 | 11.41 | 0.186777E+11 | 11349.01 | 27-APR-22:10 | 14.40 | 11.00 |
May | 0.417513E+11 | 22607.98 | 05-MAY-21:20 | 18.53 | 12.90 | 0.193306E+11 | 11368.65 | 05-MAY-21:19 | 18.53 | 12.90 |
June | 0.418089E+11 | 22890.50 | 28-JUN-21:20 | 17.23 | 13.81 | 0.187492E+11 | 11369.48 | 27-JUN-21:19 | 17.23 | 13.81 |
July | 0.441611E+11 | 23521.14 | 24-JUL-21:20 | 22.07 | 16.28 | 0.193037E+11 | 11369.62 | 21-JUL-21:19 | 22.07 | 16.28 |
August | 0.441035E+11 | 23456.67 | 10-AUG-21:05 | 22.92 | 16.74 | 0.193817E+11 | 11369.88 | 23-AUG-21:19 | 21.47 | 16.20 |
September | 0.404221E+11 | 22321.33 | 12-SEP-21:20 | 19.03 | 14.58 | 0.186851E+11 | 11349.28 | 12-SEP-21:19 | 19.03 | 14.58 |
October | 0.389836E+11 | 21367.20 | 04-OCT-22:00 | 16.10 | 10.03 | 0.192501E+11 | 11348.81 | 04-OCT-21:30 | 16.10 | 10.03 |
November | 0.358041E+11 | 20857.51 | 06-NOV-23:00 | 15.60 | 14.58 | 0.185546E+11 | 11347.86 | 09-NOV-00:20 | 7.97 | 6.86 |
December | 0.354504E+11 | 19809.67 | 29-DEC-23:00 | 8.90 | 7.76 | 0.191308E+11 | 11348.18 | 04-DEC-00:20 | 8.90 | 7.76 |
Annual Sum or Average | 0.466988E+12 | 0.226802E+12 | ||||||||
Minimum of Months | 0.326637E+11 | 19809.67 | 8.90 | 7.76 | 0.173173E+11 | 11347.86 | 1.70 | -0.1 | ||
Maximum of Months | 0.441611E+11 | 23521.14 | 22.92 | 16.74 | 0.193817E+11 | 11369.88 | 22.07 | 16.28 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.492109E+11 | 26602.78 | 30-JAN-11:33 | 8.13 | 6.36 | 0.188193E+11 | 11319.62 | 21-JAN-18:19 | 8.13 | 6.36 |
February | 0.454186E+11 | 27755.78 | 27-FEB-11:45 | 16.23 | 10.66 | 0.170028E+11 | 11319.62 | 18-FEB-18:19 | 16.23 | 10.66 |
March | 0.517697E+11 | 28894.50 | 14-MAR-10:45 | 11.42 | 8.58 | 0.188394E+11 | 11319.62 | 18-MAR-17:19 | 19.03 | 9.50 |
April | 0.518344E+11 | 30227.01 | 27-APR-10:33 | 20.37 | 13.53 | 0.182339E+11 | 11319.65 | 29-APR-17:19 | 20.57 | 14.52 |
May | 0.547707E+11 | 30342.60 | 14-MAY-10:33 | 20.03 | 12.68 | 0.188485E+11 | 11319.65 | 20-MAY-17:19 | 16.87 | 9.98 |
June | 0.542583E+11 | 30623.93 | 10-JUN-10:33 | 20.20 | 14.80 | 0.182502E+11 | 11319.65 | 24-JUN-17:19 | 19.23 | 11.83 |
July | 0.567124E+11 | 31021.13 | 24-JUL-10:37 | 25.93 | 17.48 | 0.188559E+11 | 11319.69 | 29-JUL-17:19 | 23.17 | 15.48 |
August | 0.569796E+11 | 31091.67 | 13-AUG-10:40 | 24.17 | 17.28 | 0.188647E+11 | 11319.68 | 12-AUG-17:19 | 24.17 | 17.28 |
September | 0.533915E+11 | 30544.84 | 10-SEP-10:33 | 18.33 | 13.89 | 0.182450E+11 | 11319.66 | 23-SEP-17:19 | 21.67 | 16.65 |
October | 0.526095E+11 | 29366.68 | 07-OCT-10:33 | 14.63 | 10.97 | 0.188401E+11 | 11319.60 | 28-OCT-17:19 | 10.73 | 7.68 |
November | 0.489733E+11 | 28888.15 | 04-NOV-10:45 | 17.52 | 14.63 | 0.182212E+11 | 11319.64 | 25-NOV-18:19 | 7.40 | 6.48 |
December | 0.494769E+11 | 27114.85 | 03-DEC-11:50 | 11.52 | 5.93 | 0.188208E+11 | 11319.61 | 23-DEC-18:19 | 5.60 | 4.96 |
Annual Sum or Average | 0.625406E+12 | 0.221842E+12 | ||||||||
Minimum of Months | 0.454186E+11 | 26602.78 | 8.13 | 5.93 | 0.170028E+11 | 11319.60 | 5.60 | 4.96 | ||
Maximum of Months | 0.569796E+11 | 31091.67 | 25.93 | 17.48 | 0.188647E+11 | 11319.69 | 24.17 | 17.28 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.373648E+10 | 3346.98 | 30-JAN-11:33 | 8.13 | 6.36 | 0.126910E+10 | 765.10 | 11-JAN-22:40 | 8.13 | 6.36 |
February | 0.469627E+10 | 3751.87 | 27-FEB-11:45 | 16.23 | 10.66 | 0.115471E+10 | 819.49 | 27-FEB-22:40 | 12.20 | 10.25 |
March | 0.710433E+10 | 3974.38 | 02-MAR-11:33 | 9.63 | 6.30 | 0.130596E+10 | 833.22 | 14-MAR-21:40 | 12.40 | 8.44 |
April | 0.807847E+10 | 4787.93 | 27-APR-18:10 | 25.55 | 15.86 | 0.131557E+10 | 920.31 | 27-APR-21:30 | 15.80 | 11.30 |
May | 0.926972E+10 | 4945.36 | 06-MAY-10:33 | 20.93 | 16.16 | 0.143164E+10 | 926.78 | 15-MAY-21:30 | 13.35 | 11.02 |
June | 0.956570E+10 | 5090.45 | 28-JUN-18:10 | 25.40 | 16.48 | 0.144202E+10 | 959.19 | 28-JUN-21:30 | 17.50 | 13.87 |
July | 0.104578E+11 | 5360.37 | 24-JUL-18:10 | 28.72 | 17.86 | 0.153889E+10 | 993.07 | 24-JUL-21:30 | 21.70 | 16.16 |
August | 0.105609E+11 | 6159.39 | 10-AUG-15:03 | 30.37 | 18.88 | 0.155244E+10 | 1005.53 | 10-AUG-21:30 | 22.75 | 16.30 |
September | 0.926779E+10 | 5093.60 | 14-SEP-10:33 | 19.43 | 16.41 | 0.141498E+10 | 958.02 | 14-SEP-21:30 | 17.75 | 14.69 |
October | 0.793499E+10 | 4562.15 | 04-OCT-10:33 | 18.33 | 11.02 | 0.133658E+10 | 888.01 | 04-OCT-22:10 | 15.73 | 10.00 |
November | 0.548544E+10 | 4044.72 | 04-NOV-10:50 | 17.52 | 14.63 | 0.123876E+10 | 803.16 | 05-NOV-23:19 | 11.10 | 9.49 |
December | 0.409284E+10 | 3610.45 | 03-DEC-11:33 | 11.33 | 5.78 | 0.126979E+10 | 753.05 | 29-DEC-22:40 | 8.90 | 7.67 |
Annual Sum or Average | 0.902506E+11 | 0.162704E+11 | ||||||||
Minimum of Months | 0.373648E+10 | 3346.98 | 8.13 | 5.78 | 0.115471E+10 | 753.05 | 8.13 | 6.36 | ||
Maximum of Months | 0.105609E+11 | 6159.39 | 30.37 | 18.88 | 0.155244E+10 | 1005.53 | 22.75 | 16.30 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 78654395.50 | 458.93 | 16-JAN-17:00 | 1.70 |
February | 32662351.08 | 611.45 | 19-FEB-06:00 | -5.6 |
March | 107098.37 | 51.02 | 05-MAR-18:00 | 5.60 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 10118138.99 | 276.13 | 30-NOV-16:00 | 4.40 |
December | 84523361.88 | 623.77 | 26-DEC-12:00 | 0.20 |
Annual Sum or Average | 0.206065E+09 | |||
Minimum of Months | 0.00 | 0.00 | -5.6 | |
Maximum of Months | 84523361.88 | 623.77 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1069286.70 | 71.89 | 16-JAN-15:50 | 2.20 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 9.22 |
December | 285259.28 | 31.35 | 26-DEC-14:50 | 2.03 |
Annual Sum or Average | 1354545.98 | |||
Minimum of Months | 0.00 | 0.00 | 2.03 | |
Maximum of Months | 1069286.70 | 71.89 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 18034691.49 | 167.68 | 16-JAN-16:00 | 2.20 |
February | 8841903.90 | 134.33 | 19-FEB-06:00 | -5.6 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 14611.92 | 7.85 | 30-NOV-16:00 | 4.40 |
December | 9837511.69 | 153.51 | 26-DEC-14:50 | 2.03 |
Annual Sum or Average | 36728719.00 | |||
Minimum of Months | 0.00 | 0.00 | -5.6 | |
Maximum of Months | 18034691.49 | 167.68 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.767817E+09 | 1249.63 | 16-JAN-16:13 | 2.03 |
February | 0.433986E+09 | 1229.95 | 03-FEB-16:03 | 8.90 |
March | 0.186791E+09 | 1265.46 | 15-MAR-18:04 | 10.40 |
April | 59653728.50 | 1305.25 | 18-APR-15:04 | 9.22 |
May | 10167926.45 | 1176.34 | 12-MAY-08:03 | 10.97 |
June | 3210512.53 | 1237.30 | 13-JUN-18:04 | 11.02 |
July | 2066511.49 | 1010.49 | 17-JUL-18:04 | 17.02 |
August | 2719924.70 | 1038.10 | 08-AUG-08:04 | 20.10 |
September | 6043860.88 | 1147.74 | 27-SEP-15:03 | 13.30 |
October | 80192812.60 | 1137.58 | 27-OCT-15:02 | 10.82 |
November | 0.395929E+09 | 1240.26 | 30-NOV-16:13 | 4.60 |
December | 0.698665E+09 | 1259.72 | 26-DEC-16:13 | 3.73 |
Annual Sum or Average | 0.264724E+10 | |||
Minimum of Months | 2066511.49 | 1010.49 | 2.03 | |
Maximum of Months | 0.767817E+09 | 1305.25 | 20.10 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.905368E+09 | 1232.79 | 16-JAN-16:13 | 2.03 |
February | 0.574247E+09 | 1274.49 | 12-FEB-16:03 | 6.52 |
March | 0.267388E+09 | 1277.32 | 24-MAR-15:03 | 9.32 |
April | 80668188.67 | 1218.64 | 13-APR-19:44 | 14.60 |
May | 10961189.40 | 1109.09 | 11-MAY-18:04 | 12.12 |
June | 3706664.78 | 1241.36 | 06-JUN-18:04 | 10.78 |
July | 2007242.40 | 1065.92 | 25-JUL-08:04 | 15.18 |
August | 2426101.03 | 1183.06 | 23-AUG-08:53 | 21.20 |
September | 6787206.93 | 1198.14 | 21-SEP-15:04 | 17.30 |
October | 0.123336E+09 | 1259.66 | 14-OCT-15:03 | 11.60 |
November | 0.497003E+09 | 1216.40 | 30-NOV-16:13 | 4.60 |
December | 0.839424E+09 | 1234.43 | 26-DEC-16:13 | 3.73 |
Annual Sum or Average | 0.331332E+10 | |||
Minimum of Months | 2007242.40 | 1065.92 | 2.03 | |
Maximum of Months | 0.905368E+09 | 1277.32 | 21.20 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 42434475.01 | 333.65 | 07-JAN-16:01 | 2.70 |
February | 23066497.40 | 330.64 | 12-FEB-09:04 | 1.97 |
March | 2049874.50 | 330.56 | 01-MAR-16:03 | 12.20 |
April | 750255.28 | 327.37 | 06-APR-08:04 | 9.18 |
May | 509902.24 | 329.02 | 21-MAY-15:06 | 16.10 |
June | 149264.96 | 325.46 | 04-JUN-15:06 | 17.12 |
July | 130507.35 | 330.69 | 03-JUL-15:06 | 16.42 |
August | 242848.02 | 305.63 | 02-AUG-15:06 | 18.37 |
September | 582828.01 | 328.07 | 28-SEP-08:04 | 10.28 |
October | 1599597.82 | 316.70 | 12-OCT-15:04 | 14.90 |
November | 6327095.30 | 318.20 | 12-NOV-16:01 | 4.72 |
December | 26563743.94 | 328.64 | 23-DEC-09:04 | 4.40 |
Annual Sum or Average | 0.104407E+09 | |||
Minimum of Months | 130507.35 | 305.63 | 1.97 | |
Maximum of Months | 42434475.01 | 333.65 | 18.37 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.772918E+09 | 1224.38 | 16-JAN-16:13 | 2.03 |
February | 0.435703E+09 | 1190.12 | 16-FEB-16:13 | 2.80 |
March | 0.180806E+09 | 1220.50 | 21-MAR-15:04 | 13.12 |
April | 55734651.33 | 1244.85 | 09-APR-15:04 | 14.32 |
May | 12483556.27 | 1160.59 | 16-MAY-18:04 | 13.72 |
June | 2565958.95 | 1209.36 | 14-JUN-15:04 | 14.40 |
July | 2334988.76 | 1235.28 | 16-JUL-15:04 | 17.80 |
August | 2341762.62 | 1173.33 | 17-AUG-18:04 | 18.58 |
September | 7856641.27 | 1247.22 | 21-SEP-15:04 | 17.30 |
October | 83163885.72 | 1266.50 | 01-OCT-15:04 | 16.70 |
November | 0.399783E+09 | 1214.51 | 30-NOV-16:13 | 4.60 |
December | 0.705275E+09 | 1232.91 | 26-DEC-16:13 | 3.73 |
Annual Sum or Average | 0.266097E+10 | |||
Minimum of Months | 2334988.76 | 1160.59 | 2.03 | |
Maximum of Months | 0.772918E+09 | 1266.50 | 18.58 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.912474E+09 | 1215.59 | 07-JAN-16:01 | 2.70 |
February | 0.573288E+09 | 1197.74 | 19-FEB-16:01 | 2.62 |
March | 0.251474E+09 | 1222.28 | 26-MAR-15:03 | 10.60 |
April | 75095212.37 | 1115.55 | 23-APR-15:04 | 18.30 |
May | 14167422.78 | 1244.34 | 29-MAY-15:04 | 15.68 |
June | 2742851.09 | 1218.14 | 07-JUN-15:04 | 15.92 |
July | 1976161.31 | 1164.11 | 01-JUL-08:04 | 15.10 |
August | 1481090.85 | 1122.65 | 03-AUG-15:04 | 19.30 |
September | 9194612.56 | 1227.75 | 06-SEP-15:04 | 16.02 |
October | 0.124952E+09 | 1224.36 | 07-OCT-15:04 | 18.03 |
November | 0.494287E+09 | 1199.85 | 12-NOV-16:01 | 4.72 |
December | 0.840844E+09 | 1209.31 | 26-DEC-16:13 | 3.73 |
Annual Sum or Average | 0.330198E+10 | |||
Minimum of Months | 1481090.85 | 1115.55 | 2.62 | |
Maximum of Months | 0.912474E+09 | 1244.34 | 19.30 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3271975.39 | 238.36 | 16-JAN-16:00 | 2.20 |
February | 72909.29 | 32.00 | 17-FEB-10:30 | 1.15 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 313353.26 | 66.58 | 30-NOV-15:00 | 5.00 |
December | 8645497.41 | 340.44 | 26-DEC-15:00 | 2.20 |
Annual Sum or Average | 12303735.35 | |||
Minimum of Months | 0.00 | 0.00 | 1.15 | |
Maximum of Months | 8645497.41 | 340.44 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.118808E+10 | 1510.83 | 16-JAN-16:13 | 2.03 |
February | 0.719073E+09 | 1471.18 | 18-FEB-19:13 | -1.0 |
March | 0.379837E+09 | 1420.62 | 05-MAR-16:02 | 6.02 |
April | 0.144463E+09 | 1381.26 | 19-APR-08:62 | 5.87 |
May | 39657593.47 | 1313.87 | 18-MAY-08:62 | 6.28 |
June | 7116457.20 | 1081.29 | 13-JUN-18:04 | 11.02 |
July | 2172658.71 | 1200.21 | 04-JUL-08:03 | 12.98 |
August | 2526357.13 | 957.65 | 17-AUG-18:04 | 18.58 |
September | 16563319.61 | 1170.40 | 27-SEP-15:03 | 13.30 |
October | 0.196270E+09 | 1385.29 | 28-OCT-15:03 | 12.20 |
November | 0.683396E+09 | 1499.97 | 30-NOV-16:13 | 4.60 |
December | 0.109685E+10 | 1520.02 | 26-DEC-16:13 | 3.73 |
Annual Sum or Average | 0.447601E+10 | |||
Minimum of Months | 2172658.71 | 957.65 | -1.0 | |
Maximum of Months | 0.118808E+10 | 1520.02 | 18.58 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.135980E+10 | 1483.42 | 16-JAN-16:13 | 2.03 |
February | 0.902900E+09 | 1466.53 | 19-FEB-09:13 | -2.9 |
March | 0.499092E+09 | 1408.37 | 25-MAR-08:61 | 4.78 |
April | 0.184263E+09 | 1374.23 | 19-APR-08:62 | 5.87 |
May | 41518572.90 | 1293.41 | 18-MAY-08:62 | 6.28 |
June | 7318532.11 | 1229.88 | 27-JUN-08:53 | 17.80 |
July | 1674670.91 | 1020.09 | 19-JUL-08:04 | 15.97 |
August | 2119085.17 | 1034.82 | 23-AUG-08:53 | 21.20 |
September | 19177370.51 | 1355.46 | 28-SEP-08:61 | 10.28 |
October | 0.279049E+09 | 1371.49 | 25-OCT-08:61 | 9.37 |
November | 0.812166E+09 | 1466.55 | 30-NOV-16:13 | 4.60 |
December | 0.127547E+10 | 1484.93 | 26-DEC-16:13 | 3.73 |
Annual Sum or Average | 0.538454E+10 | |||
Minimum of Months | 1674670.91 | 1020.09 | -2.9 | |
Maximum of Months | 0.135980E+10 | 1484.93 | 21.20 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.309239E+09 | 799.46 | 26-JAN-16:13 | 6.67 |
February | 0.152636E+09 | 770.33 | 16-FEB-16:13 | 2.80 |
March | 48458992.43 | 773.61 | 08-MAR-16:04 | 16.02 |
April | 18181168.33 | 695.28 | 09-APR-08:03 | 8.40 |
May | 5222828.87 | 711.09 | 24-MAY-18:04 | 12.70 |
June | 2033182.20 | 672.45 | 07-JUN-08:03 | 11.88 |
July | 1437003.81 | 711.72 | 12-JUL-08:03 | 12.80 |
August | 1660698.20 | 628.82 | 17-AUG-18:04 | 18.58 |
September | 3218845.76 | 675.58 | 28-SEP-08:03 | 10.28 |
October | 14788303.03 | 676.10 | 29-OCT-18:04 | 9.82 |
November | 0.131533E+09 | 811.24 | 30-NOV-16:13 | 4.60 |
December | 0.292093E+09 | 824.14 | 26-DEC-16:13 | 3.73 |
Annual Sum or Average | 0.980501E+09 | |||
Minimum of Months | 1437003.81 | 628.82 | 2.80 | |
Maximum of Months | 0.309239E+09 | 824.14 | 18.58 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1652666.73 | 128.87 | 16-JAN-05:20 | -2.2 |
February | 5346550.83 | 484.13 | 19-FEB-06:00 | -5.6 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 9.22 |
December | 5820300.43 | 293.73 | 26-DEC-11:05 | 0.12 |
Annual Sum or Average | 12819517.98 | |||
Minimum of Months | 0.00 | 0.00 | -5.6 | |
Maximum of Months | 5820300.43 | 484.13 | 17.17 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.136942E+11 | 13190.31 | 02-JAN-20:10 | 0.121516E+11 | 9632.53 | 02-JAN-20:10 |
February | 0.123646E+11 | 13190.31 | 01-FEB-20:10 | 0.109726E+11 | 9632.53 | 01-FEB-20:10 |
March | 0.137364E+11 | 13190.31 | 01-MAR-20:10 | 0.121771E+11 | 9632.53 | 01-MAR-20:10 |
April | 0.132299E+11 | 13190.31 | 03-APR-19:10 | 0.117446E+11 | 9632.53 | 03-APR-19:10 |
May | 0.137180E+11 | 13190.31 | 01-MAY-19:10 | 0.121662E+11 | 9632.53 | 01-MAY-19:10 |
June | 0.132906E+11 | 13190.31 | 01-JUN-19:10 | 0.117829E+11 | 9632.53 | 01-JUN-19:10 |
July | 0.136573E+11 | 13190.31 | 03-JUL-19:10 | 0.121279E+11 | 9632.53 | 03-JUL-19:10 |
August | 0.137417E+11 | 13190.31 | 01-AUG-19:10 | 0.121808E+11 | 9632.53 | 01-AUG-19:10 |
September | 0.132352E+11 | 13190.31 | 01-SEP-19:10 | 0.117482E+11 | 9632.53 | 01-SEP-19:10 |
October | 0.136889E+11 | 13190.31 | 02-OCT-19:10 | 0.121479E+11 | 9632.53 | 02-OCT-19:10 |
November | 0.132800E+11 | 13190.31 | 01-NOV-19:10 | 0.117774E+11 | 9632.53 | 01-NOV-19:10 |
December | 0.136573E+11 | 13190.31 | 01-DEC-20:10 | 0.121279E+11 | 9632.53 | 01-DEC-20:10 |
Annual Sum or Average | 0.161294E+12 | 0.143105E+12 | ||||
Minimum of Months | 0.123646E+11 | 13190.31 | 0.109726E+11 | 9632.53 | ||
Maximum of Months | 0.137417E+11 | 13190.31 | 0.121808E+11 | 9632.53 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.620421E+09 | 597.59 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.560184E+09 | 597.59 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.622334E+09 | 597.59 | 01-MAR-20:10 | 0.866718E+09 | 685.60 | 01-MAR-20:10 |
April | 0.599386E+09 | 597.59 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.621497E+09 | 597.59 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.602135E+09 | 597.59 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.618748E+09 | 597.59 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.622573E+09 | 597.59 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.599625E+09 | 597.59 | 01-SEP-19:10 | 0.836191E+09 | 685.60 | 01-SEP-19:10 |
October | 0.620182E+09 | 597.59 | 02-OCT-19:10 | 0.864640E+09 | 685.60 | 02-OCT-19:10 |
November | 0.601657E+09 | 597.59 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.618748E+09 | 597.59 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.730749E+10 | 0.101856E+11 | ||||
Minimum of Months | 0.560184E+09 | 597.59 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.622573E+09 | 597.59 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.718450E+09 | 692.02 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.648695E+09 | 692.02 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.720665E+09 | 692.02 | 01-MAR-20:10 | 0.100366E+10 | 793.93 | 01-MAR-20:10 |
April | 0.694091E+09 | 692.02 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.719696E+09 | 692.02 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.697275E+09 | 692.02 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.716513E+09 | 692.02 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.720942E+09 | 692.02 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.694368E+09 | 692.02 | 01-SEP-19:10 | 0.968312E+09 | 793.93 | 01-SEP-19:10 |
October | 0.718174E+09 | 692.02 | 02-OCT-19:10 | 0.100126E+10 | 793.93 | 02-OCT-19:10 |
November | 0.696721E+09 | 692.02 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.716513E+09 | 692.02 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.846210E+10 | 0.117950E+11 | ||||
Minimum of Months | 0.648695E+09 | 692.02 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.720942E+09 | 692.02 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.710312E+09 | 684.18 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.641347E+09 | 684.18 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.712502E+09 | 684.18 | 01-MAR-20:10 | 0.106120E+10 | 839.45 | 01-MAR-20:10 |
April | 0.686229E+09 | 684.18 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.711544E+09 | 684.18 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.689376E+09 | 684.18 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.708397E+09 | 684.18 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.712775E+09 | 684.18 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.686503E+09 | 684.18 | 01-SEP-19:10 | 0.102382E+10 | 839.45 | 01-SEP-19:10 |
October | 0.710039E+09 | 684.18 | 02-OCT-19:10 | 0.105866E+10 | 839.45 | 02-OCT-19:10 |
November | 0.688829E+09 | 684.18 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.708397E+09 | 684.18 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.836625E+10 | 0.124712E+11 | ||||
Minimum of Months | 0.641347E+09 | 684.18 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.712775E+09 | 684.18 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.261454E+09 | 251.84 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.236069E+09 | 251.84 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.262260E+09 | 251.84 | 01-MAR-20:10 | 0.306128E+09 | 242.16 | 01-MAR-20:10 |
April | 0.252589E+09 | 251.84 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.261907E+09 | 251.84 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.253748E+09 | 251.84 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.260749E+09 | 251.84 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.262360E+09 | 251.84 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.252690E+09 | 251.84 | 01-SEP-19:10 | 0.295345E+09 | 242.16 | 01-SEP-19:10 |
October | 0.261353E+09 | 251.84 | 02-OCT-19:10 | 0.305393E+09 | 242.16 | 02-OCT-19:10 |
November | 0.253546E+09 | 251.84 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.260749E+09 | 251.84 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.307947E+10 | 0.359760E+10 | ||||
Minimum of Months | 0.236069E+09 | 251.84 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.262360E+09 | 251.84 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.337502E+09 | 325.08 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.304733E+09 | 325.08 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.338542E+09 | 325.08 | 01-MAR-20:10 | 0.578079E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.326059E+09 | 325.08 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.338087E+09 | 325.08 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.327554E+09 | 325.08 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.336592E+09 | 325.08 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.338672E+09 | 325.08 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.326189E+09 | 325.08 | 01-SEP-19:10 | 0.557718E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.337372E+09 | 325.08 | 02-OCT-19:10 | 0.576693E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.327294E+09 | 325.08 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.336592E+09 | 325.08 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.397519E+10 | 0.679355E+11 | ||||
Minimum of Months | 0.304733E+09 | 325.08 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.338672E+09 | 325.08 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.141930E+10 | 1701.53 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.120632E+10 | 1701.53 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.125166E+10 | 1701.53 | 01-MAR-20:10 | 0.122027E+10 | 965.27 | 01-MAR-20:10 |
April | 0.108886E+10 | 1701.53 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.103943E+10 | 1701.53 | 01-MAY-19:10 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.922157E+09 | 1701.53 | 01-JUN-19:40 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.985607E+09 | 1701.53 | 03-JUL-19:00 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.106554E+10 | 1701.53 | 01-AUG-19:19 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.117377E+10 | 1701.53 | 01-SEP-19:10 | 0.117729E+10 | 965.27 | 01-SEP-19:10 |
October | 0.132050E+10 | 1701.53 | 02-OCT-19:10 | 0.121734E+10 | 965.27 | 02-OCT-19:10 |
November | 0.134594E+10 | 1701.53 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.142460E+10 | 1701.53 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.142437E+11 | 0.143405E+11 | ||||
Minimum of Months | 0.922157E+09 | 1701.53 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.142460E+10 | 1701.53 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.954301E+10 | 9504.80 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.853979E+10 | 9504.80 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.941463E+10 | 9504.80 | 01-MAR-20:10 | 0.126786E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.896188E+10 | 9504.80 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.921214E+10 | 9504.80 | 01-MAY-19:10 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.885814E+10 | 9504.80 | 01-JUN-19:30 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.914681E+10 | 9504.80 | 03-JUL-19:40 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.925746E+10 | 9504.80 | 01-AUG-19:19 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.903708E+10 | 9504.80 | 01-SEP-19:10 | 0.122320E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.944307E+10 | 9504.80 | 02-OCT-19:10 | 0.126482E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.922463E+10 | 9504.80 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.953034E+10 | 9504.80 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.110169E+12 | 0.148998E+12 | ||||
Minimum of Months | 0.853979E+10 | 9504.80 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.954301E+10 | 9504.80 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196602E+09 | 177.88 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.177551E+09 | 177.88 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.195039E+09 | 177.88 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.190486E+09 | 177.88 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.195821E+09 | 177.88 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.188975E+09 | 177.88 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.197358E+09 | 177.88 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.195039E+09 | 177.88 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.190538E+09 | 177.88 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.196576E+09 | 177.88 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.189731E+09 | 177.88 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.197383E+09 | 177.88 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.231110E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.177551E+09 | 177.88 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.197383E+09 | 177.88 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196579E+09 | 177.86 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.177530E+09 | 177.86 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.195017E+09 | 177.86 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.190464E+09 | 177.86 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.195798E+09 | 177.86 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.188953E+09 | 177.86 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.197334E+09 | 177.86 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.195017E+09 | 177.86 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.190515E+09 | 177.86 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.196553E+09 | 177.86 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.189708E+09 | 177.86 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.197360E+09 | 177.86 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.231083E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.177530E+09 | 177.86 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.197360E+09 | 177.86 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123557E+09 | 111.79 | 01-JAN-19:10 | 0.217935E+09 | 232.19 | 01-JAN-08:09 |
February | 0.111584E+09 | 111.79 | 01-FEB-20:10 | 0.196843E+09 | 232.19 | 01-FEB-07:10 |
March | 0.122575E+09 | 111.79 | 01-MAR-20:10 | 0.217824E+09 | 232.19 | 01-MAR-07:10 |
April | 0.119713E+09 | 111.79 | 01-APR-18:10 | 0.210923E+09 | 232.19 | 01-APR-07:10 |
May | 0.123066E+09 | 111.79 | 01-MAY-19:10 | 0.217879E+09 | 232.19 | 01-MAY-06:10 |
June | 0.118764E+09 | 111.79 | 01-JUN-19:10 | 0.210812E+09 | 232.19 | 01-JUN-06:10 |
July | 0.124032E+09 | 111.79 | 01-JUL-18:10 | 0.217991E+09 | 232.19 | 01-JUL-07:10 |
August | 0.122575E+09 | 111.79 | 01-AUG-19:10 | 0.217824E+09 | 232.19 | 01-AUG-06:10 |
September | 0.119746E+09 | 111.79 | 01-SEP-19:10 | 0.210923E+09 | 232.19 | 01-SEP-06:10 |
October | 0.123541E+09 | 111.79 | 01-OCT-18:10 | 0.217935E+09 | 232.19 | 01-OCT-07:10 |
November | 0.119238E+09 | 111.79 | 01-NOV-19:10 | 0.210867E+09 | 232.19 | 01-NOV-06:10 |
December | 0.124048E+09 | 111.79 | 01-DEC-20:10 | 0.217991E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.145244E+10 | 0.256575E+10 | ||||
Minimum of Months | 0.111584E+09 | 111.79 | 0.196843E+09 | 232.19 | ||
Maximum of Months | 0.124048E+09 | 111.79 | 0.217991E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123591E+09 | 111.82 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 0.111614E+09 | 111.82 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 0.122608E+09 | 111.82 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 0.119746E+09 | 111.82 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 0.123099E+09 | 111.82 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 0.118796E+09 | 111.82 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 0.124066E+09 | 111.82 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 0.122608E+09 | 111.82 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 0.119778E+09 | 111.82 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 0.123574E+09 | 111.82 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 0.119271E+09 | 111.82 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 0.124082E+09 | 111.82 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.145283E+10 | 0.256645E+10 | ||||
Minimum of Months | 0.111614E+09 | 111.82 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 0.124082E+09 | 111.82 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196602E+09 | 177.88 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.177551E+09 | 177.88 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.195039E+09 | 177.88 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.190486E+09 | 177.88 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.195821E+09 | 177.88 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.188975E+09 | 177.88 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.197358E+09 | 177.88 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.195039E+09 | 177.88 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.190538E+09 | 177.88 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.196576E+09 | 177.88 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.189731E+09 | 177.88 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.197383E+09 | 177.88 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.231110E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.177551E+09 | 177.88 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.197383E+09 | 177.88 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196579E+09 | 177.86 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.177530E+09 | 177.86 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.195017E+09 | 177.86 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.190464E+09 | 177.86 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.195798E+09 | 177.86 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.188953E+09 | 177.86 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.197334E+09 | 177.86 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.195017E+09 | 177.86 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.190515E+09 | 177.86 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.196553E+09 | 177.86 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.189708E+09 | 177.86 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.197360E+09 | 177.86 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.231083E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.177530E+09 | 177.86 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.197360E+09 | 177.86 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.193865E+10 | 1867.32 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.175042E+10 | 1867.32 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.194462E+10 | 1867.32 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.187292E+10 | 1867.32 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.194201E+10 | 1867.32 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.188151E+10 | 1867.32 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.193342E+10 | 1867.32 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.194537E+10 | 1867.32 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.187367E+10 | 1867.32 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.193790E+10 | 1867.32 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.188002E+10 | 1867.32 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.193342E+10 | 1867.32 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.228339E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.175042E+10 | 1867.32 | 0.00 | 0.00 | |
Maximum of Months | 0.194537E+10 | 1867.32 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196602E+09 | 177.88 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.177551E+09 | 177.88 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.195039E+09 | 177.88 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.190486E+09 | 177.88 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.195821E+09 | 177.88 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.188975E+09 | 177.88 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.197358E+09 | 177.88 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.195039E+09 | 177.88 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.190538E+09 | 177.88 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.196576E+09 | 177.88 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.189731E+09 | 177.88 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.197383E+09 | 177.88 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.231110E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.177551E+09 | 177.88 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.197383E+09 | 177.88 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196579E+09 | 177.86 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.177530E+09 | 177.86 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.195017E+09 | 177.86 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.190464E+09 | 177.86 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.195798E+09 | 177.86 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.188953E+09 | 177.86 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.197334E+09 | 177.86 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.195017E+09 | 177.86 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.190515E+09 | 177.86 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.196553E+09 | 177.86 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.189708E+09 | 177.86 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.197360E+09 | 177.86 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.231083E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.177530E+09 | 177.86 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.197360E+09 | 177.86 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123591E+09 | 111.82 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 0.111614E+09 | 111.82 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 0.122608E+09 | 111.82 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 0.119746E+09 | 111.82 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 0.123099E+09 | 111.82 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 0.118796E+09 | 111.82 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 0.124066E+09 | 111.82 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 0.122608E+09 | 111.82 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 0.119778E+09 | 111.82 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 0.123574E+09 | 111.82 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 0.119271E+09 | 111.82 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 0.124082E+09 | 111.82 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.145283E+10 | 0.256645E+10 | ||||
Minimum of Months | 0.111614E+09 | 111.82 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 0.124082E+09 | 111.82 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.287054E+10 | 2988.03 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.250957E+10 | 2988.03 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.268827E+10 | 2988.03 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.245393E+10 | 2988.03 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.244131E+10 | 2988.03 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.226940E+10 | 2988.03 | 01-JUN-19:40 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.235884E+10 | 2988.03 | 10-JUL-19:30 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.247234E+10 | 2988.03 | 01-AUG-19:19 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.254653E+10 | 2988.03 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.275942E+10 | 2988.03 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.275372E+10 | 2988.03 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.288189E+10 | 2988.03 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.310058E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.226940E+10 | 2988.03 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.288189E+10 | 2988.03 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.287054E+10 | 2988.03 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.250957E+10 | 2988.03 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.268827E+10 | 2988.03 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.245393E+10 | 2988.03 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.244131E+10 | 2988.03 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.226940E+10 | 2988.03 | 01-JUN-19:40 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.235884E+10 | 2988.03 | 10-JUL-19:30 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.247234E+10 | 2988.03 | 01-AUG-19:19 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.254653E+10 | 2988.03 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.275942E+10 | 2988.03 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.275372E+10 | 2988.03 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.288189E+10 | 2988.03 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.310058E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.226940E+10 | 2988.03 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.288189E+10 | 2988.03 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.110133E+10 | 1060.81 | 02-JAN-20:10 | 0.368383E+11 | 16487.34 | 01-JAN-07:10 |
February | 0.994402E+09 | 1060.81 | 01-FEB-20:10 | 0.332733E+11 | 16487.34 | 01-FEB-07:10 |
March | 0.110473E+10 | 1060.81 | 01-MAR-20:10 | 0.368383E+11 | 16487.34 | 01-MAR-07:10 |
April | 0.106399E+10 | 1060.81 | 03-APR-19:10 | 0.356500E+11 | 16487.34 | 01-APR-06:10 |
May | 0.110324E+10 | 1060.81 | 01-MAY-19:10 | 0.368383E+11 | 16487.34 | 01-MAY-06:10 |
June | 0.106887E+10 | 1060.81 | 01-JUN-19:10 | 0.356500E+11 | 16487.34 | 01-JUN-06:10 |
July | 0.109836E+10 | 1060.81 | 03-JUL-19:10 | 0.368383E+11 | 16487.34 | 01-JUL-06:10 |
August | 0.110515E+10 | 1060.81 | 01-AUG-19:10 | 0.368383E+11 | 16487.34 | 01-AUG-06:10 |
September | 0.106442E+10 | 1060.81 | 01-SEP-19:10 | 0.356500E+11 | 16487.34 | 01-SEP-06:10 |
October | 0.110091E+10 | 1060.81 | 02-OCT-19:10 | 0.368383E+11 | 16487.34 | 01-OCT-06:10 |
November | 0.106802E+10 | 1060.81 | 01-NOV-19:10 | 0.356500E+11 | 16487.34 | 01-NOV-06:10 |
December | 0.109836E+10 | 1060.81 | 01-DEC-20:10 | 0.368383E+11 | 16487.34 | 01-DEC-07:10 |
Annual Sum or Average | 0.129718E+11 | 0.433742E+12 | ||||
Minimum of Months | 0.994402E+09 | 1060.81 | 0.332733E+11 | 16487.34 | ||
Maximum of Months | 0.110515E+10 | 1060.81 | 0.368383E+11 | 16487.34 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.205176E+10 | 1976.27 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.185255E+10 | 1976.27 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.205809E+10 | 1976.27 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.198220E+10 | 1976.27 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.205532E+10 | 1976.27 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.199129E+10 | 1976.27 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.204623E+10 | 1976.27 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.205888E+10 | 1976.27 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.198299E+10 | 1976.27 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.205097E+10 | 1976.27 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.198971E+10 | 1976.27 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.204623E+10 | 1976.27 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.241662E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.185255E+10 | 1976.27 | 0.00 | 0.00 | |
Maximum of Months | 0.205888E+10 | 1976.27 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.136942E+11 | 0.121516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.123646E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196682E+11 | 0.137364E+11 | 0.121771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.132299E+11 | 0.117446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.137180E+11 | 0.121662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.132906E+11 | 0.117829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.136573E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.137417E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189689E+11 | 0.132352E+11 | 0.117482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195854E+11 | 0.136889E+11 | 0.121479E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.132800E+11 | 0.117774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.136573E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230861E+12 | 0.161294E+12 | 0.143105E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.176991E+11 | 0.123646E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196682E+11 | 0.137417E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.620421E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248298E+09 |
February | 0.179968E+10 | 0.560184E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205951E+09 |
March | 0.199990E+10 | 0.622334E+09 | 0.866718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191216E+09 |
April | 0.192973E+10 | 0.599386E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 697441.60 | 0.150712E+09 |
May | 0.199475E+10 | 0.621497E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 270607.17 | 0.124507E+09 |
June | 0.193394E+10 | 0.602135E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 945786.84 | 84165592.83 |
July | 0.199054E+10 | 0.618748E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3984501.58 | 65336397.95 |
August | 0.199896E+10 | 0.622573E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7508999.52 | 54494129.69 |
September | 0.192879E+10 | 0.599625E+09 | 0.836191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 84018.04 | 94093706.70 |
October | 0.199148E+10 | 0.620182E+09 | 0.864640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145672E+09 |
November | 0.192552E+10 | 0.601657E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187063E+09 |
December | 0.199054E+10 | 0.618748E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234487E+09 |
Annual Sum or Average | 0.234744E+11 | 0.730749E+10 | 0.101856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 13491354.74 | 0.178600E+10 |
Minimum of Months | 0.179968E+10 | 0.560184E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54494129.69 |
Maximum of Months | 0.199990E+10 | 0.622573E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7508999.52 | 0.248298E+09 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.718450E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99202772.06 |
February | 0.208403E+10 | 0.648695E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83285371.76 |
March | 0.231589E+10 | 0.720665E+09 | 0.100366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79508782.89 |
April | 0.223463E+10 | 0.694091E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 328914.92 | 64662309.50 |
May | 0.230993E+10 | 0.719696E+09 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 102259.50 | 55710400.06 |
June | 0.223950E+10 | 0.697275E+09 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 280650.50 | 40300655.14 |
July | 0.230505E+10 | 0.716513E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1443537.39 | 32707525.08 |
August | 0.231480E+10 | 0.720942E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2946616.27 | 28119096.70 |
September | 0.223354E+10 | 0.694368E+09 | 0.968312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 58874.67 | 43315852.06 |
October | 0.230614E+10 | 0.718174E+09 | 0.100126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62820575.56 |
November | 0.222975E+10 | 0.696721E+09 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77167078.51 |
December | 0.230505E+10 | 0.716513E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94268533.07 |
Annual Sum or Average | 0.271834E+11 | 0.846210E+10 | 0.117950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5160853.25 | 0.761069E+09 |
Minimum of Months | 0.208403E+10 | 0.648695E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28119096.70 |
Maximum of Months | 0.231589E+10 | 0.720942E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2946616.27 | 99202772.06 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.487480E+09 | 0.710312E+09 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226745E+09 |
February | 0.440737E+09 | 0.641347E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188036E+09 |
March | 0.489771E+09 | 0.712502E+09 | 0.106120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177444E+09 |
April | 0.472586E+09 | 0.686229E+09 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1062476.49 | 0.144460E+09 |
May | 0.488511E+09 | 0.711544E+09 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 393684.19 | 0.126110E+09 |
June | 0.473617E+09 | 0.689376E+09 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 798430.97 | 92307336.49 |
July | 0.487480E+09 | 0.708397E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3540572.80 | 75328989.61 |
August | 0.489542E+09 | 0.712775E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7155313.81 | 65314584.07 |
September | 0.472357E+09 | 0.686503E+09 | 0.102382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 314248.22 | 98200125.24 |
October | 0.487709E+09 | 0.710039E+09 | 0.105866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141079E+09 |
November | 0.471555E+09 | 0.688829E+09 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174219E+09 |
December | 0.487480E+09 | 0.708397E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213866E+09 |
Annual Sum or Average | 0.574883E+10 | 0.836625E+10 | 0.124712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 13264726.48 | 0.172311E+10 |
Minimum of Months | 0.440737E+09 | 0.641347E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65314584.07 |
Maximum of Months | 0.489771E+09 | 0.712775E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7155313.81 | 0.226745E+09 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.374985E+09 | 0.261454E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130349E+09 |
February | 0.339028E+09 | 0.236069E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107599E+09 |
March | 0.376747E+09 | 0.262260E+09 | 0.306128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100115E+09 |
April | 0.363528E+09 | 0.252589E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 635308.76 | 81025668.27 |
May | 0.375778E+09 | 0.261907E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 255097.56 | 70428975.64 |
June | 0.364321E+09 | 0.253748E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 518624.24 | 51195989.92 |
July | 0.374985E+09 | 0.260749E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2182677.56 | 41486868.41 |
August | 0.376571E+09 | 0.262360E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4352519.60 | 35799172.34 |
September | 0.363352E+09 | 0.252690E+09 | 0.295345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 211643.90 | 54398615.37 |
October | 0.375161E+09 | 0.261353E+09 | 0.305393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78777839.98 |
November | 0.362735E+09 | 0.253546E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98960670.71 |
December | 0.374985E+09 | 0.260749E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122735E+09 |
Annual Sum or Average | 0.442217E+10 | 0.307947E+10 | 0.359760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8155871.62 | 0.972871E+09 |
Minimum of Months | 0.339028E+09 | 0.236069E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35799172.34 |
Maximum of Months | 0.376747E+09 | 0.262360E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4352519.60 | 0.130349E+09 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.337502E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344874E+09 |
February | 0.139600E+10 | 0.304733E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286704E+09 |
March | 0.155131E+10 | 0.338542E+09 | 0.578079E+10 | 0.502211E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270322E+09 |
April | 0.149688E+10 | 0.326059E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 1027275.66 | 0.216946E+09 |
May | 0.154732E+10 | 0.338087E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 529623.49 | 0.183680E+09 |
June | 0.150015E+10 | 0.327554E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 1062666.69 | 0.131408E+09 |
July | 0.154405E+10 | 0.336592E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 5421278.94 | 0.102915E+09 |
August | 0.155059E+10 | 0.338672E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 10724756.11 | 87895629.60 |
September | 0.149615E+10 | 0.326189E+09 | 0.557718E+10 | 0.484522E+11 | 0.00 | 0.00 | 0.00 | 629233.68 | 0.140179E+09 |
October | 0.154478E+10 | 0.337372E+09 | 0.576693E+10 | 0.501006E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211482E+09 |
November | 0.149361E+10 | 0.327294E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.267216E+09 |
December | 0.154405E+10 | 0.336592E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327015E+09 |
Annual Sum or Average | 0.182090E+11 | 0.397519E+10 | 0.679355E+11 | 0.590196E+12 | 0.00 | 0.00 | 0.00 | 19394834.57 | 0.257064E+10 |
Minimum of Months | 0.139600E+10 | 0.304733E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 87895629.60 |
Maximum of Months | 0.155131E+10 | 0.338672E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 10724756.11 | 0.344874E+09 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.141930E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.561785E+09 |
February | 0.236489E+11 | 0.120632E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.472556E+09 |
March | 0.262800E+11 | 0.125166E+10 | 0.122027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.447975E+09 |
April | 0.253579E+11 | 0.108886E+10 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1346093.19 | 0.360980E+09 |
May | 0.262123E+11 | 0.103943E+10 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 435635.88 | 0.305741E+09 |
June | 0.254132E+11 | 0.922157E+09 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1594857.16 | 0.217451E+09 |
July | 0.261570E+11 | 0.985607E+09 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8185229.68 | 0.174184E+09 |
August | 0.262677E+11 | 0.106554E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15708901.99 | 0.148842E+09 |
September | 0.253456E+11 | 0.117377E+10 | 0.117729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 140025.66 | 0.237779E+09 |
October | 0.261693E+11 | 0.132050E+10 | 0.121734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.351019E+09 |
November | 0.253025E+11 | 0.134594E+10 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.431960E+09 |
December | 0.261570E+11 | 0.142460E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.532936E+09 |
Annual Sum or Average | 0.308468E+12 | 0.142437E+11 | 0.143405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 27410743.57 | 0.424321E+10 |
Minimum of Months | 0.236489E+11 | 0.922157E+09 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148842E+09 |
Maximum of Months | 0.262800E+11 | 0.142460E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15708901.99 | 0.561785E+09 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.954301E+10 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166245E+10 |
February | 0.702046E+11 | 0.853979E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139862E+10 |
March | 0.780153E+11 | 0.941463E+10 | 0.126786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133624E+10 |
April | 0.752779E+11 | 0.896188E+10 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4905056.93 | 0.108550E+10 |
May | 0.778146E+11 | 0.921214E+10 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1553859.53 | 0.932743E+09 |
June | 0.754422E+11 | 0.885814E+10 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4481867.44 | 0.677855E+09 |
July | 0.776503E+11 | 0.914681E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 23858516.81 | 0.545646E+09 |
August | 0.779788E+11 | 0.925746E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 47355506.97 | 0.470096E+09 |
September | 0.752414E+11 | 0.903708E+10 | 0.122320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 742508.54 | 0.726877E+09 |
October | 0.776868E+11 | 0.944307E+10 | 0.126482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105973E+10 |
November | 0.751137E+11 | 0.922463E+10 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129769E+10 |
December | 0.776503E+11 | 0.953034E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158068E+10 |
Annual Sum or Average | 0.915726E+12 | 0.110169E+12 | 0.148998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 82897316.21 | 0.127741E+11 |
Minimum of Months | 0.702046E+11 | 0.853979E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.470096E+09 |
Maximum of Months | 0.780153E+11 | 0.954301E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 47355506.97 | 0.166245E+10 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196602E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142321E+09 |
February | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118997E+09 |
March | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111452E+09 |
April | 0.293479E+09 | 0.190486E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 597426.59 | 88934045.10 |
May | 0.303504E+09 | 0.195821E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 352854.22 | 74023709.27 |
June | 0.293842E+09 | 0.188975E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 824966.41 | 50615456.29 |
July | 0.303141E+09 | 0.197358E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3277386.45 | 37571271.16 |
August | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6211225.21 | 31052132.02 |
September | 0.293479E+09 | 0.190538E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 478508.93 | 53959081.43 |
October | 0.303322E+09 | 0.196576E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1628.93 | 84701795.03 |
November | 0.293661E+09 | 0.189731E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108122E+09 |
December | 0.303141E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134483E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231110E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11743996.74 | 0.103623E+10 |
Minimum of Months | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31052132.02 |
Maximum of Months | 0.303685E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6211225.21 | 0.142321E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196579E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140985E+09 |
February | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117333E+09 |
March | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109945E+09 |
April | 0.293479E+09 | 0.190464E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 578001.80 | 88758633.60 |
May | 0.303504E+09 | 0.195798E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 148209.76 | 77094664.25 |
June | 0.293842E+09 | 0.188953E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 543719.35 | 54732624.10 |
July | 0.303141E+09 | 0.197334E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2668594.70 | 43905696.15 |
August | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5601238.23 | 35088353.68 |
September | 0.293479E+09 | 0.190515E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 189461.16 | 57334693.90 |
October | 0.303322E+09 | 0.196553E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 556.66 | 83790586.09 |
November | 0.293661E+09 | 0.189708E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106994E+09 |
December | 0.303141E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133018E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231083E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9729781.67 | 0.104898E+10 |
Minimum of Months | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35088353.68 |
Maximum of Months | 0.303685E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5601238.23 | 0.140985E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.123557E+09 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41376624.36 |
February | 0.00 | 0.111584E+09 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39937816.36 |
March | 0.00 | 0.122575E+09 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42621200.95 |
April | 0.00 | 0.119713E+09 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3171.21 | 36056513.21 |
May | 0.00 | 0.123066E+09 | 0.217879E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32210537.44 |
June | 0.00 | 0.118764E+09 | 0.210812E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25101676.50 |
July | 0.00 | 0.124032E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 84303.61 | 21151862.03 |
August | 0.00 | 0.122575E+09 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 301721.72 | 18674521.19 |
September | 0.00 | 0.119746E+09 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26271561.60 |
October | 0.00 | 0.123541E+09 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35552933.05 |
November | 0.00 | 0.119238E+09 | 0.210867E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39532263.00 |
December | 0.00 | 0.124048E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42051853.08 |
Annual Sum or Average | 0.00 | 0.145244E+10 | 0.256575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 389196.54 | 0.400539E+09 |
Minimum of Months | 0.00 | 0.111584E+09 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18674521.19 |
Maximum of Months | 0.00 | 0.124048E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 301721.72 | 42621200.95 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.123591E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40239154.93 |
February | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33297128.30 |
March | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31051531.67 |
April | 0.293479E+09 | 0.119746E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 180326.08 | 24711107.28 |
May | 0.303504E+09 | 0.123099E+09 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 56529.59 | 20788098.31 |
June | 0.293842E+09 | 0.118796E+09 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 170250.22 | 14582810.60 |
July | 0.303141E+09 | 0.124066E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 793767.26 | 11153706.77 |
August | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1638370.21 | 9190111.12 |
September | 0.293479E+09 | 0.119778E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 83796.14 | 15269855.22 |
October | 0.303322E+09 | 0.123574E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 159.46 | 23520410.01 |
November | 0.293661E+09 | 0.119271E+09 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30535866.70 |
December | 0.303141E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37934563.63 |
Annual Sum or Average | 0.357224E+10 | 0.145283E+10 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2923198.96 | 0.292274E+09 |
Minimum of Months | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9190111.12 |
Maximum of Months | 0.303685E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1638370.21 | 40239154.93 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196602E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142202E+09 |
February | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119105E+09 |
March | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111939E+09 |
April | 0.293479E+09 | 0.190486E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 604270.99 | 89556754.99 |
May | 0.303504E+09 | 0.195821E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 357806.11 | 74174626.43 |
June | 0.293842E+09 | 0.188975E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 833715.66 | 50907679.10 |
July | 0.303141E+09 | 0.197358E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3301250.67 | 37704961.91 |
August | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6224065.74 | 31232828.71 |
September | 0.293479E+09 | 0.190538E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 486420.77 | 53990008.04 |
October | 0.303322E+09 | 0.196576E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1942.68 | 84948308.12 |
November | 0.293661E+09 | 0.189731E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108083E+09 |
December | 0.303141E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134341E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231110E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11809472.62 | 0.103819E+10 |
Minimum of Months | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31232828.71 |
Maximum of Months | 0.303685E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6224065.74 | 0.142202E+09 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196579E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140868E+09 |
February | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117293E+09 |
March | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110384E+09 |
April | 0.293479E+09 | 0.190464E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 581019.21 | 89348129.38 |
May | 0.303504E+09 | 0.195798E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 159219.00 | 75615333.93 |
June | 0.293842E+09 | 0.188953E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 566385.36 | 53974101.99 |
July | 0.303141E+09 | 0.197334E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2700752.80 | 41820581.45 |
August | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5585582.28 | 34983173.44 |
September | 0.293479E+09 | 0.190515E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 225612.00 | 55789547.92 |
October | 0.303322E+09 | 0.196553E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 579.36 | 83896101.74 |
November | 0.293661E+09 | 0.189708E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106869E+09 |
December | 0.303141E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132833E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231083E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9819150.02 | 0.104367E+10 |
Minimum of Months | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34983173.44 |
Maximum of Months | 0.303685E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5585582.28 | 0.140868E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.385223E+10 | 0.193865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174249E+09 |
February | 0.348285E+10 | 0.175042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143694E+09 |
March | 0.387034E+10 | 0.194462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133845E+09 |
April | 0.373454E+10 | 0.187292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 800480.91 | 0.108017E+09 |
May | 0.386038E+10 | 0.194201E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 300972.84 | 94060993.45 |
June | 0.374269E+10 | 0.188151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 673404.30 | 67602661.72 |
July | 0.385223E+10 | 0.193342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2870769.95 | 54501061.45 |
August | 0.386853E+10 | 0.194537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5769819.08 | 46996171.92 |
September | 0.373273E+10 | 0.187367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 203403.47 | 72133494.35 |
October | 0.385404E+10 | 0.193790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103714E+09 |
November | 0.372639E+10 | 0.188002E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131301E+09 |
December | 0.385223E+10 | 0.193342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164123E+09 |
Annual Sum or Average | 0.454292E+11 | 0.228339E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10618850.55 | 0.129424E+10 |
Minimum of Months | 0.348285E+10 | 0.175042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46996171.92 |
Maximum of Months | 0.387034E+10 | 0.194537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5769819.08 | 0.174249E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196602E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141764E+09 |
February | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118672E+09 |
March | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111370E+09 |
April | 0.293479E+09 | 0.190486E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 582992.96 | 89143246.32 |
May | 0.303504E+09 | 0.195821E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 333241.03 | 74353278.16 |
June | 0.293842E+09 | 0.188975E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 795572.78 | 50991321.58 |
July | 0.303141E+09 | 0.197358E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3198964.50 | 37916062.77 |
August | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6079392.52 | 31311934.55 |
September | 0.293479E+09 | 0.190538E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 457419.79 | 54182208.79 |
October | 0.303322E+09 | 0.196576E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1068.49 | 84679020.10 |
November | 0.293661E+09 | 0.189731E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107777E+09 |
December | 0.303141E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134140E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231110E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11448652.08 | 0.103630E+10 |
Minimum of Months | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31311934.55 |
Maximum of Months | 0.303685E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6079392.52 | 0.141764E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196579E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140655E+09 |
February | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116980E+09 |
March | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109785E+09 |
April | 0.293479E+09 | 0.190464E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 561706.76 | 89096206.07 |
May | 0.303504E+09 | 0.195798E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 138463.43 | 78129164.28 |
June | 0.293842E+09 | 0.188953E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 521705.02 | 55852501.24 |
July | 0.303141E+09 | 0.197334E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2610774.61 | 45256877.88 |
August | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5484367.75 | 35693854.71 |
September | 0.293479E+09 | 0.190515E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 180390.14 | 58243871.25 |
October | 0.303322E+09 | 0.196553E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 479.78 | 83680163.15 |
November | 0.293661E+09 | 0.189708E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106595E+09 |
December | 0.303141E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132679E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231083E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9497887.49 | 0.105265E+10 |
Minimum of Months | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35693854.71 |
Maximum of Months | 0.303685E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5484367.75 | 0.140655E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.123591E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74238325.48 |
February | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62049279.96 |
March | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58016743.92 |
April | 0.293479E+09 | 0.119746E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 300041.45 | 46130600.09 |
May | 0.303504E+09 | 0.123099E+09 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 174141.01 | 38185101.26 |
June | 0.293842E+09 | 0.118796E+09 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 412000.11 | 26151505.26 |
July | 0.303141E+09 | 0.124066E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1650749.97 | 19396933.35 |
August | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3122624.53 | 16050956.37 |
September | 0.293479E+09 | 0.119778E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 236818.25 | 27940198.16 |
October | 0.303322E+09 | 0.123574E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 256.90 | 44166789.61 |
November | 0.293661E+09 | 0.119271E+09 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56473571.21 |
December | 0.303141E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70083267.08 |
Annual Sum or Average | 0.357224E+10 | 0.145283E+10 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5896632.22 | 0.538883E+09 |
Minimum of Months | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16050956.37 |
Maximum of Months | 0.303685E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3122624.53 | 74238325.48 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.287054E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.406953E+09 |
February | 0.415303E+11 | 0.250957E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340082E+09 |
March | 0.461508E+11 | 0.268827E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.324840E+09 |
April | 0.445315E+11 | 0.245393E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 654518.87 | 0.264382E+09 |
May | 0.460320E+11 | 0.244131E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 37725.73 | 0.228245E+09 |
June | 0.446286E+11 | 0.226940E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 345116.17 | 0.167884E+09 |
July | 0.459349E+11 | 0.235884E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3671746.80 | 0.134446E+09 |
August | 0.461292E+11 | 0.247234E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 8264911.93 | 0.115539E+09 |
September | 0.445099E+11 | 0.254653E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 52147.93 | 0.177124E+09 |
October | 0.459565E+11 | 0.275942E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257720E+09 |
November | 0.444343E+11 | 0.275372E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319132E+09 |
December | 0.459349E+11 | 0.288189E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.386994E+09 |
Annual Sum or Average | 0.541708E+12 | 0.310058E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 13026167.42 | 0.312334E+10 |
Minimum of Months | 0.415303E+11 | 0.226940E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115539E+09 |
Maximum of Months | 0.461508E+11 | 0.288189E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 8264911.93 | 0.406953E+09 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.287054E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.411118E+09 |
February | 0.415303E+11 | 0.250957E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.343388E+09 |
March | 0.461508E+11 | 0.268827E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327629E+09 |
April | 0.445315E+11 | 0.245393E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 642433.48 | 0.266269E+09 |
May | 0.460320E+11 | 0.244131E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 37721.86 | 0.229436E+09 |
June | 0.446286E+11 | 0.226940E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 345099.80 | 0.168745E+09 |
July | 0.459349E+11 | 0.235884E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3648544.48 | 0.134990E+09 |
August | 0.461292E+11 | 0.247234E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 8172960.64 | 0.116158E+09 |
September | 0.445099E+11 | 0.254653E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 52142.56 | 0.178297E+09 |
October | 0.459565E+11 | 0.275942E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259977E+09 |
November | 0.444343E+11 | 0.275372E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322338E+09 |
December | 0.459349E+11 | 0.288189E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.390904E+09 |
Annual Sum or Average | 0.541708E+12 | 0.310058E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 12898902.82 | 0.314925E+10 |
Minimum of Months | 0.415303E+11 | 0.226940E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116158E+09 |
Maximum of Months | 0.461508E+11 | 0.288189E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 8172960.64 | 0.411118E+09 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.110133E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.368825E+09 |
February | 0.369574E+10 | 0.994402E+09 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.307441E+09 |
March | 0.410691E+10 | 0.110473E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292690E+09 |
April | 0.396281E+10 | 0.106399E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 577689.95 | 0.237231E+09 |
May | 0.409635E+10 | 0.110324E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 34626.32 | 0.204071E+09 |
June | 0.397146E+10 | 0.106887E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 312372.15 | 0.150112E+09 |
July | 0.408770E+10 | 0.109836E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 3269096.17 | 0.120001E+09 |
August | 0.410499E+10 | 0.110515E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 7299946.39 | 0.103367E+09 |
September | 0.396089E+10 | 0.106442E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 47823.15 | 0.158984E+09 |
October | 0.408962E+10 | 0.110091E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232246E+09 |
November | 0.395417E+10 | 0.106802E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288711E+09 |
December | 0.408770E+10 | 0.109836E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.350509E+09 |
Annual Sum or Average | 0.482060E+11 | 0.129718E+11 | 0.392709E+12 | 0.359593E+12 | 0.00 | 0.00 | 0.00 | 11541554.14 | 0.281419E+10 |
Minimum of Months | 0.369574E+10 | 0.994402E+09 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103367E+09 |
Maximum of Months | 0.410691E+10 | 0.110515E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 7299946.39 | 0.368825E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.407704E+10 | 0.205176E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309491E+09 |
February | 0.368610E+10 | 0.185255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255765E+09 |
March | 0.409620E+10 | 0.205809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238926E+09 |
April | 0.395248E+10 | 0.198220E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1008670.73 | 0.193666E+09 |
May | 0.408566E+10 | 0.205532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167512.78 | 0.168498E+09 |
June | 0.396110E+10 | 0.199129E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 547631.48 | 0.123035E+09 |
July | 0.407704E+10 | 0.204623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3719428.63 | 99331755.95 |
August | 0.409429E+10 | 0.205888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8083414.52 | 83988436.88 |
September | 0.395056E+10 | 0.198299E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103184.25 | 0.128546E+09 |
October | 0.407896E+10 | 0.205097E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184308E+09 |
November | 0.394385E+10 | 0.198971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233951E+09 |
December | 0.407704E+10 | 0.204623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291675E+09 |
Annual Sum or Average | 0.480803E+11 | 0.241662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13629842.39 | 0.231118E+10 |
Minimum of Months | 0.368610E+10 | 0.185255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83988436.88 |
Maximum of Months | 0.409620E+10 | 0.205888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8083414.52 | 0.309491E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 13190.31 | 02-JAN-20:10 | 9632.53 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 13190.31 | 01-FEB-20:10 | 9632.53 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 13190.31 | 01-MAR-20:10 | 9632.53 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 13190.31 | 03-APR-19:10 | 9632.53 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 13190.31 | 01-MAY-19:10 | 9632.53 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 13190.31 | 01-JUN-19:10 | 9632.53 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 13190.31 | 03-JUL-19:10 | 9632.53 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 13190.31 | 01-AUG-19:10 | 9632.53 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 13190.31 | 01-SEP-19:10 | 9632.53 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 01-OCT-23:10 | 13190.31 | 02-OCT-19:10 | 9632.53 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 13190.31 | 01-NOV-19:10 | 9632.53 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 13190.31 | 01-DEC-20:10 | 9632.53 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 11501.89 | 13190.31 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 13190.31 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 597.59 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 145.51 | 15-JAN-08:00 |
February | 1169.53 | 01-FEB-00:10 | 597.59 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 152.57 | 19-FEB-06:00 |
March | 1169.53 | 01-MAR-00:10 | 597.59 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 123.98 | 01-MAR-07:00 |
April | 1169.53 | 01-APR-00:10 | 597.59 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.67 | 01-APR-17:00 | 109.76 | 19-APR-05:00 |
May | 1169.53 | 01-MAY-00:10 | 597.59 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.86 | 05-MAY-16:00 | 92.79 | 11-MAY-03:50 |
June | 1169.53 | 01-JUN-00:10 | 597.59 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.07 | 28-JUN-17:00 | 69.77 | 15-JUN-03:50 |
July | 1169.53 | 01-JUL-00:10 | 597.59 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.55 | 24-JUL-15:00 | 54.22 | 07-JUL-05:00 |
August | 1169.53 | 01-AUG-00:10 | 597.59 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.62 | 10-AUG-17:00 | 55.83 | 01-AUG-06:00 |
September | 1169.53 | 01-SEP-00:10 | 597.59 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.55 | 14-SEP-17:00 | 76.47 | 27-SEP-05:00 |
October | 1169.53 | 01-OCT-23:10 | 597.59 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 85.63 | 13-OCT-05:00 |
November | 1169.53 | 01-NOV-00:10 | 597.59 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 119.24 | 11-NOV-07:30 |
December | 1169.53 | 01-DEC-00:10 | 597.59 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 131.10 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1169.53 | 597.59 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.22 | |||||
Maximum of Months | 1169.53 | 597.59 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 42.62 | 152.57 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 692.02 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 57.51 | 15-JAN-08:00 |
February | 1354.32 | 01-FEB-00:10 | 692.02 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 59.31 | 19-FEB-05:00 |
March | 1354.32 | 01-MAR-00:10 | 692.02 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 51.14 | 01-MAR-07:00 |
April | 1354.32 | 01-APR-00:10 | 692.02 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.73 | 01-APR-16:00 | 45.19 | 19-APR-05:00 |
May | 1354.32 | 01-MAY-00:10 | 692.02 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.12 | 05-MAY-16:00 | 39.57 | 11-MAY-03:00 |
June | 1354.32 | 01-JUN-00:10 | 692.02 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.24 | 28-JUN-17:00 | 30.61 | 15-JUN-03:00 |
July | 1354.32 | 01-JUL-00:10 | 692.02 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.21 | 24-JUL-15:00 | 26.02 | 07-JUL-05:00 |
August | 1354.32 | 01-AUG-00:10 | 692.02 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.17 | 29-AUG-16:00 | 26.31 | 01-AUG-06:00 |
September | 1354.32 | 01-SEP-00:10 | 692.02 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.80 | 22-SEP-16:00 | 33.01 | 27-SEP-05:00 |
October | 1354.32 | 01-OCT-23:10 | 692.02 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 37.16 | 13-OCT-05:00 |
November | 1354.32 | 01-NOV-00:10 | 692.02 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 48.51 | 11-NOV-08:00 |
December | 1354.32 | 01-DEC-00:10 | 692.02 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 51.72 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1354.32 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.02 | |||||
Maximum of Months | 1354.32 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 16.17 | 59.31 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 286.42 | 02-JAN-00:10 | 684.18 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 132.73 | 15-JAN-08:00 |
February | 286.42 | 01-FEB-00:10 | 684.18 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 139.18 | 19-FEB-06:00 |
March | 286.42 | 01-MAR-00:10 | 684.18 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 116.94 | 01-MAR-07:00 |
April | 286.42 | 01-APR-00:10 | 684.18 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.97 | 01-APR-16:00 | 101.84 | 19-APR-05:00 |
May | 286.42 | 01-MAY-00:10 | 684.18 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.26 | 05-MAY-16:00 | 90.74 | 11-MAY-03:00 |
June | 286.42 | 01-JUN-00:10 | 684.18 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.08 | 28-JUN-17:00 | 69.98 | 15-JUN-03:00 |
July | 286.42 | 01-JUL-00:10 | 684.18 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.00 | 24-JUL-15:00 | 59.05 | 19-JUL-05:00 |
August | 286.42 | 01-AUG-00:10 | 684.18 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.70 | 29-AUG-16:00 | 60.64 | 01-AUG-06:00 |
September | 286.42 | 01-SEP-00:10 | 684.18 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.74 | 22-SEP-16:00 | 75.16 | 27-SEP-05:00 |
October | 286.42 | 01-OCT-23:10 | 684.18 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 83.40 | 13-OCT-05:00 |
November | 286.42 | 01-NOV-00:10 | 684.18 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 110.12 | 11-NOV-08:00 |
December | 286.42 | 01-DEC-00:10 | 684.18 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 119.58 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 286.42 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.05 | |||||
Maximum of Months | 286.42 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 38.70 | 139.18 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 220.32 | 02-JAN-00:10 | 251.84 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 76.57 | 15-JAN-08:00 |
February | 220.32 | 01-FEB-00:10 | 251.84 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 80.30 | 19-FEB-06:00 |
March | 220.32 | 01-MAR-00:10 | 251.84 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 66.00 | 01-MAR-07:00 |
April | 220.32 | 01-APR-00:10 | 251.84 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.62 | 01-APR-16:00 | 57.77 | 19-APR-05:00 |
May | 220.32 | 01-MAY-00:10 | 251.84 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.75 | 05-MAY-16:00 | 51.28 | 11-MAY-03:00 |
June | 220.32 | 01-JUN-00:10 | 251.84 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.69 | 28-JUN-17:00 | 39.47 | 15-JUN-03:00 |
July | 220.32 | 01-JUL-00:10 | 251.84 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.74 | 24-JUL-15:00 | 33.39 | 19-JUL-05:00 |
August | 220.32 | 01-AUG-00:10 | 251.84 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.48 | 10-AUG-17:00 | 34.04 | 01-AUG-06:00 |
September | 220.32 | 01-SEP-00:10 | 251.84 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.06 | 22-SEP-16:00 | 42.36 | 27-SEP-05:00 |
October | 220.32 | 01-OCT-23:10 | 251.84 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 47.14 | 13-OCT-05:00 |
November | 220.32 | 01-NOV-00:10 | 251.84 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 62.75 | 11-NOV-08:00 |
December | 220.32 | 01-DEC-00:10 | 251.84 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 68.99 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 220.32 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.39 | |||||
Maximum of Months | 220.32 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 22.48 | 80.30 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 325.08 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 203.03 | 15-JAN-08:00 |
February | 907.20 | 01-FEB-00:10 | 325.08 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 206.90 | 19-FEB-08:00 |
March | 907.20 | 01-MAR-00:10 | 325.08 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 175.81 | 01-MAR-07:00 |
April | 907.20 | 01-APR-00:10 | 325.08 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 32.15 | 01-APR-16:00 | 156.59 | 19-APR-05:10 |
May | 907.20 | 01-MAY-00:10 | 325.08 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 17.60 | 05-MAY-16:00 | 130.93 | 11-MAY-05:10 |
June | 907.20 | 01-JUN-00:10 | 325.08 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 30.33 | 28-JUN-17:00 | 102.31 | 15-JUN-05:10 |
July | 907.20 | 01-JUL-00:10 | 325.08 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 49.38 | 24-JUL-15:00 | 84.82 | 07-JUL-05:10 |
August | 907.20 | 01-AUG-00:10 | 325.08 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 61.63 | 10-AUG-17:00 | 86.67 | 21-AUG-05:10 |
September | 907.20 | 01-SEP-00:10 | 325.08 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 18.85 | 14-SEP-17:00 | 114.21 | 27-SEP-05:10 |
October | 907.20 | 01-OCT-23:10 | 325.08 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 125.74 | 13-OCT-05:10 |
November | 907.20 | 01-NOV-00:10 | 325.08 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 169.68 | 11-NOV-08:00 |
December | 907.20 | 01-DEC-00:10 | 325.08 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 184.71 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 907.20 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 84.82 | ||||||
Maximum of Months | 907.20 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 61.63 | 206.90 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 1701.53 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 321.67 | 15-JAN-08:00 |
February | 15368.40 | 01-FEB-00:10 | 1701.53 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 337.33 | 19-FEB-06:00 |
March | 15368.40 | 01-MAR-00:10 | 1701.53 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 281.68 | 01-MAR-07:00 |
April | 15368.40 | 01-APR-00:10 | 1701.53 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.84 | 01-APR-16:00 | 257.25 | 19-APR-05:00 |
May | 15368.40 | 01-MAY-00:10 | 1701.53 | 01-MAY-19:10 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.35 | 05-MAY-16:00 | 223.49 | 11-MAY-03:00 |
June | 15368.40 | 01-JUN-00:10 | 1701.53 | 01-JUN-19:40 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.20 | 28-JUN-17:00 | 172.97 | 15-JUN-03:00 |
July | 15368.40 | 01-JUL-00:10 | 1701.53 | 03-JUL-19:00 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.59 | 24-JUL-15:00 | 146.78 | 19-JUL-05:00 |
August | 15368.40 | 01-AUG-00:10 | 1701.53 | 01-AUG-19:19 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 92.90 | 10-AUG-17:00 | 146.67 | 01-AUG-05:00 |
September | 15368.40 | 01-SEP-00:10 | 1701.53 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.52 | 14-SEP-17:00 | 186.10 | 27-SEP-05:00 |
October | 15368.40 | 01-OCT-23:10 | 1701.53 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 211.82 | 13-OCT-05:00 |
November | 15368.40 | 01-NOV-00:10 | 1701.53 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 269.73 | 11-NOV-08:00 |
December | 15368.40 | 01-DEC-00:10 | 1701.53 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 289.80 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 15368.40 | 1701.53 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.67 | |||||
Maximum of Months | 15368.40 | 1701.53 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 92.90 | 337.33 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 9504.80 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 961.25 | 15-JAN-08:00 |
February | 45622.98 | 01-FEB-00:10 | 9504.80 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 991.36 | 19-FEB-05:00 |
March | 45622.98 | 01-MAR-00:10 | 9504.80 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 852.43 | 01-MAR-07:00 |
April | 45622.98 | 01-APR-00:10 | 9504.80 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 151.42 | 01-APR-16:00 | 766.02 | 19-APR-05:00 |
May | 45622.98 | 01-MAY-00:10 | 9504.80 | 01-MAY-19:10 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.38 | 05-MAY-16:00 | 669.10 | 11-MAY-03:00 |
June | 45622.98 | 01-JUN-00:10 | 9504.80 | 01-JUN-19:30 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.77 | 28-JUN-17:00 | 522.98 | 15-JUN-03:00 |
July | 45622.98 | 01-JUL-00:10 | 9504.80 | 03-JUL-19:40 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 234.42 | 24-JUL-15:00 | 441.51 | 19-JUL-05:00 |
August | 45622.98 | 01-AUG-00:10 | 9504.80 | 01-AUG-19:19 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 268.24 | 10-AUG-17:00 | 437.28 | 21-AUG-05:00 |
September | 45622.98 | 01-SEP-00:10 | 9504.80 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.21 | 22-SEP-16:00 | 563.48 | 27-SEP-05:00 |
October | 45622.98 | 01-OCT-23:10 | 9504.80 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 630.45 | 13-OCT-05:00 |
November | 45622.98 | 01-NOV-00:10 | 9504.80 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 812.40 | 11-NOV-08:00 |
December | 45622.98 | 01-DEC-00:10 | 9504.80 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 867.95 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 45622.98 | 9504.80 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 437.28 | |||||
Maximum of Months | 45622.98 | 9504.80 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 268.24 | 991.36 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.88 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 84.96 | 15-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 177.88 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 89.06 | 19-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 177.88 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 72.46 | 01-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 177.88 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.02 | 27-APR-15:10 | 64.21 | 19-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 177.88 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.58 | 05-MAY-16:00 | 54.34 | 11-MAY-03:10 |
June | 180.00 | 01-JUN-00:10 | 177.88 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.64 | 28-JUN-17:00 | 40.97 | 15-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 177.88 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.06 | 24-JUL-15:10 | 32.52 | 04-JUL-07:20 |
August | 180.00 | 01-AUG-00:10 | 177.88 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.13 | 10-AUG-17:00 | 36.53 | 01-AUG-08:00 |
September | 180.00 | 01-SEP-00:10 | 177.88 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.60 | 14-SEP-17:00 | 44.87 | 27-SEP-05:00 |
October | 180.00 | 01-OCT-00:10 | 177.88 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.34 | 04-OCT-15:10 | 50.18 | 13-OCT-05:00 |
November | 180.00 | 01-NOV-00:10 | 177.88 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 69.70 | 11-NOV-07:10 |
December | 180.00 | 01-DEC-00:10 | 177.88 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 76.59 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.52 | |||||
Maximum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 31.13 | 89.06 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.86 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 84.96 | 15-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 177.86 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 89.06 | 19-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 177.86 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 72.46 | 01-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 177.86 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.02 | 27-APR-15:10 | 64.21 | 19-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 177.86 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.58 | 05-MAY-16:00 | 54.34 | 11-MAY-03:10 |
June | 180.00 | 01-JUN-00:10 | 177.86 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.63 | 28-JUN-17:00 | 40.97 | 15-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 177.86 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.06 | 24-JUL-15:10 | 36.43 | 11-JUL-19:55 |
August | 180.00 | 01-AUG-00:10 | 177.86 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.13 | 10-AUG-17:00 | 36.52 | 01-AUG-08:00 |
September | 180.00 | 01-SEP-00:10 | 177.86 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.60 | 14-SEP-17:00 | 44.86 | 27-SEP-05:00 |
October | 180.00 | 01-OCT-00:10 | 177.86 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.34 | 04-OCT-15:10 | 50.18 | 13-OCT-05:00 |
November | 180.00 | 01-NOV-00:10 | 177.86 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 69.69 | 11-NOV-07:10 |
December | 180.00 | 01-DEC-00:10 | 177.86 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 76.59 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.43 | |||||
Maximum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 31.13 | 89.06 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 111.79 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 24.44 | 15-JAN-08:10 |
February | 0.00 | 01-FEB-00:10 | 111.79 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 25.67 | 09-FEB-08:00 |
March | 0.00 | 01-MAR-00:10 | 111.79 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 24.44 | 01-MAR-07:00 |
April | 0.00 | 01-APR-00:10 | 111.79 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 | 27-APR-15:00 | 21.73 | 19-APR-05:10 |
May | 0.00 | 01-MAY-00:10 | 111.79 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 19.49 | 11-MAY-03:00 |
June | 0.00 | 01-JUN-00:10 | 111.79 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 15.86 | 01-JUN-04:40 |
July | 0.00 | 01-JUL-00:10 | 111.79 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.20 | 24-JUL-15:00 | 13.84 | 07-JUL-05:00 |
August | 0.00 | 01-AUG-00:10 | 111.79 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.15 | 10-AUG-17:00 | 13.91 | 06-AUG-05:00 |
September | 0.00 | 01-SEP-00:10 | 111.79 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 16.55 | 27-SEP-05:10 |
October | 0.00 | 01-OCT-00:10 | 111.79 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 18.75 | 13-OCT-05:10 |
November | 0.00 | 01-NOV-00:10 | 111.79 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 23.54 | 11-NOV-23:00 |
December | 0.00 | 01-DEC-00:10 | 111.79 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 23.92 | 06-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 0.00 | 111.79 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.84 | |||||
Maximum of Months | 0.00 | 111.79 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 4.15 | 25.67 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 111.82 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 23.71 | 15-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 111.82 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 24.86 | 19-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 111.82 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 20.22 | 01-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 111.82 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.03 | 27-APR-15:10 | 17.92 | 19-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 111.82 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.23 | 05-MAY-16:00 | 15.17 | 11-MAY-03:10 |
June | 180.00 | 01-JUN-00:10 | 111.82 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.64 | 28-JUN-17:00 | 11.43 | 15-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 111.82 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.55 | 24-JUL-15:10 | 9.53 | 04-JUL-07:20 |
August | 180.00 | 01-AUG-00:10 | 111.82 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.69 | 10-AUG-17:00 | 10.03 | 01-AUG-08:00 |
September | 180.00 | 01-SEP-00:10 | 111.82 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.24 | 14-SEP-17:00 | 12.52 | 27-SEP-05:00 |
October | 180.00 | 01-OCT-00:10 | 111.82 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 | 04-OCT-15:09 | 14.15 | 29-OCT-08:00 |
November | 180.00 | 01-NOV-00:10 | 111.82 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 19.75 | 11-NOV-08:20 |
December | 180.00 | 01-DEC-00:10 | 111.82 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 21.38 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.53 | |||||
Maximum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 8.69 | 24.86 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.88 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 84.96 | 15-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 177.88 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 89.06 | 19-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 177.88 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 72.46 | 01-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 177.88 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.02 | 27-APR-15:10 | 64.21 | 19-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 177.88 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.58 | 05-MAY-16:00 | 54.34 | 11-MAY-03:10 |
June | 180.00 | 01-JUN-00:10 | 177.88 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.64 | 28-JUN-17:00 | 40.97 | 15-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 177.88 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.06 | 24-JUL-15:10 | 32.46 | 04-JUL-07:20 |
August | 180.00 | 01-AUG-00:10 | 177.88 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.13 | 10-AUG-17:00 | 37.41 | 01-AUG-07:20 |
September | 180.00 | 01-SEP-00:10 | 177.88 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.60 | 14-SEP-17:00 | 44.87 | 27-SEP-05:00 |
October | 180.00 | 01-OCT-00:10 | 177.88 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.34 | 04-OCT-15:10 | 50.18 | 13-OCT-05:00 |
November | 180.00 | 01-NOV-00:10 | 177.88 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 69.70 | 11-NOV-07:10 |
December | 180.00 | 01-DEC-00:10 | 177.88 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 76.60 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.46 | |||||
Maximum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 31.13 | 89.06 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.86 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 84.96 | 15-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 177.86 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 89.06 | 19-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 177.86 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 72.46 | 01-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 177.86 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.02 | 27-APR-15:10 | 64.21 | 19-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 177.86 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.58 | 05-MAY-16:00 | 54.34 | 11-MAY-03:10 |
June | 180.00 | 01-JUN-00:10 | 177.86 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.63 | 28-JUN-17:00 | 40.97 | 15-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 177.86 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.06 | 24-JUL-15:10 | 32.61 | 04-JUL-07:20 |
August | 180.00 | 01-AUG-00:10 | 177.86 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.13 | 10-AUG-17:00 | 37.41 | 01-AUG-07:20 |
September | 180.00 | 01-SEP-00:10 | 177.86 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.60 | 14-SEP-17:00 | 44.86 | 27-SEP-05:00 |
October | 180.00 | 01-OCT-00:10 | 177.86 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.34 | 04-OCT-15:09 | 50.18 | 13-OCT-05:00 |
November | 180.00 | 01-NOV-00:10 | 177.86 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 69.69 | 11-NOV-07:20 |
December | 180.00 | 01-DEC-00:10 | 177.86 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 76.59 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.61 | |||||
Maximum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 31.13 | 89.06 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2263.36 | 02-JAN-00:10 | 1867.32 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 102.29 | 15-JAN-08:00 |
February | 2263.36 | 01-FEB-00:10 | 1867.32 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 107.25 | 19-FEB-06:00 |
March | 2263.36 | 01-MAR-00:10 | 1867.32 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 87.35 | 01-MAR-07:00 |
April | 2263.36 | 01-APR-00:10 | 1867.32 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.38 | 01-APR-16:00 | 77.32 | 19-APR-05:00 |
May | 2263.36 | 01-MAY-00:10 | 1867.32 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.09 | 05-MAY-16:00 | 68.98 | 11-MAY-03:00 |
June | 2263.36 | 01-JUN-00:10 | 1867.32 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.22 | 28-JUN-17:00 | 52.72 | 15-JUN-03:00 |
July | 2263.36 | 01-JUL-00:10 | 1867.32 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.20 | 24-JUL-15:00 | 44.15 | 19-JUL-05:00 |
August | 2263.36 | 01-AUG-00:10 | 1867.32 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.26 | 29-AUG-16:00 | 44.94 | 01-AUG-06:00 |
September | 2263.36 | 01-SEP-00:10 | 1867.32 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.20 | 22-SEP-16:00 | 56.12 | 27-SEP-05:00 |
October | 2263.36 | 01-OCT-23:10 | 1867.32 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 62.99 | 13-OCT-05:00 |
November | 2263.36 | 01-NOV-00:10 | 1867.32 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 83.84 | 11-NOV-07:30 |
December | 2263.36 | 01-DEC-00:10 | 1867.32 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 92.18 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.15 | ||||
Maximum of Months | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.26 | 107.25 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.88 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 85.18 | 15-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 177.88 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 89.28 | 19-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 177.88 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 72.67 | 01-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 177.88 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.84 | 27-APR-15:50 | 64.42 | 19-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 177.88 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.40 | 05-MAY-16:00 | 54.55 | 11-MAY-03:00 |
June | 180.00 | 01-JUN-00:10 | 177.88 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.46 | 28-JUN-17:00 | 41.17 | 15-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 177.88 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.89 | 24-JUL-15:10 | 32.15 | 07-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 177.88 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.96 | 10-AUG-17:00 | 35.98 | 01-AUG-08:00 |
September | 180.00 | 01-SEP-00:10 | 177.88 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.42 | 14-SEP-17:00 | 45.07 | 27-SEP-05:00 |
October | 180.00 | 01-OCT-00:10 | 177.88 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.16 | 04-OCT-15:10 | 50.39 | 13-OCT-05:00 |
November | 180.00 | 01-NOV-00:10 | 177.88 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 69.91 | 11-NOV-07:30 |
December | 180.00 | 01-DEC-00:10 | 177.88 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 76.81 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.15 | |||||
Maximum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 30.96 | 89.28 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.86 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 85.18 | 15-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 177.86 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 89.27 | 19-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 177.86 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 72.67 | 01-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 177.86 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.84 | 27-APR-15:10 | 64.42 | 19-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 177.86 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.40 | 05-MAY-16:00 | 54.54 | 11-MAY-03:10 |
June | 180.00 | 01-JUN-00:10 | 177.86 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.46 | 28-JUN-17:00 | 41.16 | 15-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 177.86 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.88 | 24-JUL-15:10 | 40.48 | 11-JUL-19:55 |
August | 180.00 | 01-AUG-00:10 | 177.86 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.96 | 10-AUG-17:00 | 36.19 | 01-AUG-08:00 |
September | 180.00 | 01-SEP-00:10 | 177.86 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.42 | 14-SEP-17:00 | 45.06 | 27-SEP-05:00 |
October | 180.00 | 01-OCT-00:10 | 177.86 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.16 | 04-OCT-15:10 | 50.38 | 13-OCT-05:00 |
November | 180.00 | 01-NOV-00:10 | 177.86 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 69.91 | 11-NOV-07:10 |
December | 180.00 | 01-DEC-00:10 | 177.86 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 76.80 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.19 | |||||
Maximum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 30.96 | 89.27 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 111.82 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 43.58 | 15-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 111.82 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 45.68 | 19-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 111.82 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 37.18 | 01-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 111.82 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.13 | 27-APR-15:10 | 32.96 | 19-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 111.82 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 05-MAY-16:00 | 27.91 | 11-MAY-03:10 |
June | 180.00 | 01-JUN-00:10 | 111.82 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.42 | 28-JUN-17:00 | 21.06 | 15-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 111.82 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.76 | 24-JUL-15:10 | 16.82 | 04-JUL-07:20 |
August | 180.00 | 01-AUG-00:10 | 111.82 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.84 | 10-AUG-17:00 | 18.54 | 01-AUG-08:00 |
September | 180.00 | 01-SEP-00:10 | 111.82 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.84 | 14-SEP-17:00 | 23.06 | 27-SEP-05:00 |
October | 180.00 | 01-OCT-00:10 | 111.82 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 | 04-OCT-15:10 | 25.78 | 13-OCT-05:00 |
November | 180.00 | 01-NOV-00:10 | 111.82 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 35.77 | 11-NOV-07:10 |
December | 180.00 | 01-DEC-00:10 | 111.82 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 39.30 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.82 | |||||
Maximum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 15.84 | 45.68 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2988.03 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 231.89 | 15-JAN-08:00 |
February | 26988.77 | 01-FEB-00:10 | 2988.03 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 239.08 | 19-FEB-06:10 |
March | 26988.77 | 01-MAR-00:10 | 2988.03 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 200.92 | 01-MAR-07:00 |
April | 26988.77 | 01-APR-00:10 | 2988.03 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.31 | 01-APR-16:00 | 180.55 | 19-APR-05:00 |
May | 26988.77 | 01-MAY-00:10 | 2988.03 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.61 | 05-MAY-16:00 | 156.05 | 11-MAY-03:10 |
June | 26988.77 | 01-JUN-00:10 | 2988.03 | 01-JUN-19:40 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.04 | 28-JUN-17:00 | 122.97 | 15-JUN-03:10 |
July | 26988.77 | 01-JUL-00:10 | 2988.03 | 10-JUL-19:30 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.83 | 24-JUL-15:00 | 100.89 | 07-JUL-05:00 |
August | 26988.77 | 01-AUG-00:10 | 2988.03 | 01-AUG-19:19 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.99 | 10-AUG-17:00 | 101.72 | 21-AUG-05:00 |
September | 26988.77 | 01-SEP-00:10 | 2988.03 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.62 | 14-SEP-17:00 | 132.68 | 27-SEP-05:00 |
October | 26988.77 | 01-OCT-23:10 | 2988.03 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 145.75 | 13-OCT-05:00 |
November | 26988.77 | 01-NOV-00:10 | 2988.03 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 193.92 | 11-NOV-07:10 |
December | 26988.77 | 01-DEC-00:10 | 2988.03 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 211.16 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.89 | |||||
Maximum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 54.99 | 239.08 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2988.03 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 231.89 | 15-JAN-08:00 |
February | 26988.77 | 01-FEB-00:10 | 2988.03 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 240.50 | 19-FEB-06:10 |
March | 26988.77 | 01-MAR-00:10 | 2988.03 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 200.92 | 01-MAR-07:00 |
April | 26988.77 | 01-APR-00:10 | 2988.03 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.56 | 27-APR-16:00 | 180.55 | 19-APR-05:00 |
May | 26988.77 | 01-MAY-00:10 | 2988.03 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.61 | 05-MAY-16:00 | 156.05 | 11-MAY-03:10 |
June | 26988.77 | 01-JUN-00:10 | 2988.03 | 01-JUN-19:40 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.04 | 28-JUN-17:00 | 122.97 | 15-JUN-03:10 |
July | 26988.77 | 01-JUL-00:10 | 2988.03 | 10-JUL-19:30 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.83 | 24-JUL-15:00 | 100.89 | 07-JUL-05:00 |
August | 26988.77 | 01-AUG-00:10 | 2988.03 | 01-AUG-19:19 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.99 | 10-AUG-17:00 | 101.72 | 21-AUG-05:00 |
September | 26988.77 | 01-SEP-00:10 | 2988.03 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.62 | 14-SEP-17:00 | 132.68 | 27-SEP-05:00 |
October | 26988.77 | 01-OCT-23:10 | 2988.03 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 145.75 | 13-OCT-05:00 |
November | 26988.77 | 01-NOV-00:10 | 2988.03 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 193.92 | 11-NOV-07:10 |
December | 26988.77 | 01-DEC-00:10 | 2988.03 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 211.16 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.89 | |||||
Maximum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 54.99 | 240.50 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 1060.81 | 02-JAN-20:10 | 14912.86 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 207.55 | 15-JAN-08:00 |
February | 2401.70 | 01-FEB-00:10 | 1060.81 | 01-FEB-20:10 | 14912.86 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 215.09 | 19-FEB-06:10 |
March | 2401.70 | 01-MAR-00:10 | 1060.81 | 01-MAR-20:10 | 14912.86 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 179.83 | 01-MAR-07:00 |
April | 2401.70 | 01-APR-00:10 | 1060.81 | 03-APR-19:10 | 14912.86 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 20.28 | 27-APR-15:40 | 161.02 | 19-APR-05:10 |
May | 2401.70 | 01-MAY-00:10 | 1060.81 | 01-MAY-19:10 | 14912.86 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 5.99 | 05-MAY-16:00 | 135.58 | 11-MAY-03:30 |
June | 2401.70 | 01-JUN-00:10 | 1060.81 | 01-JUN-19:10 | 14912.86 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 17.12 | 28-JUN-17:00 | 106.95 | 15-JUN-03:30 |
July | 2401.70 | 01-JUL-00:10 | 1060.81 | 03-JUL-19:10 | 14912.86 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 41.98 | 24-JUL-15:00 | 90.32 | 07-JUL-05:00 |
August | 2401.70 | 01-AUG-00:10 | 1060.81 | 01-AUG-19:10 | 14912.86 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 49.30 | 10-AUG-17:00 | 91.06 | 21-AUG-05:00 |
September | 2401.70 | 01-SEP-00:10 | 1060.81 | 01-SEP-19:10 | 14912.86 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 6.01 | 14-SEP-17:00 | 117.43 | 27-SEP-05:10 |
October | 2401.70 | 01-OCT-23:10 | 1060.81 | 02-OCT-19:10 | 14912.86 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 130.48 | 13-OCT-05:00 |
November | 2401.70 | 01-NOV-00:10 | 1060.81 | 01-NOV-19:10 | 14912.86 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 173.58 | 11-NOV-07:10 |
December | 2401.70 | 01-DEC-00:10 | 1060.81 | 01-DEC-20:10 | 14912.86 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 189.01 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2401.70 | 1060.81 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 0.00 | 90.32 | ||||||
Maximum of Months | 2401.70 | 1060.81 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 49.30 | 215.09 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2395.44 | 02-JAN-00:10 | 1976.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 181.46 | 15-JAN-08:00 |
February | 2395.44 | 01-FEB-00:10 | 1976.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 190.23 | 19-FEB-06:00 |
March | 2395.44 | 01-MAR-00:10 | 1976.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 154.70 | 01-MAR-07:00 |
April | 2395.44 | 01-APR-00:10 | 1976.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.19 | 01-APR-16:00 | 137.06 | 19-APR-05:00 |
May | 2395.44 | 01-MAY-00:10 | 1976.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.72 | 05-MAY-16:00 | 118.89 | 11-MAY-03:00 |
June | 2395.44 | 01-JUN-00:10 | 1976.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.73 | 28-JUN-17:00 | 91.09 | 15-JUN-03:00 |
July | 2395.44 | 01-JUL-00:10 | 1976.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.02 | 24-JUL-15:00 | 77.45 | 19-JUL-05:00 |
August | 2395.44 | 01-AUG-00:10 | 1976.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.16 | 10-AUG-17:00 | 78.79 | 01-AUG-06:00 |
September | 2395.44 | 01-SEP-00:10 | 1976.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.16 | 22-SEP-16:00 | 96.47 | 27-SEP-04:03 |
October | 2395.44 | 01-OCT-23:10 | 1976.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 108.66 | 13-OCT-05:00 |
November | 2395.44 | 01-NOV-00:10 | 1976.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 148.80 | 11-NOV-08:00 |
December | 2395.44 | 01-DEC-00:10 | 1976.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 163.55 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.45 | ||||
Maximum of Months | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.16 | 190.23 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 14368.56 | 11-JAN-21:00 | 8945.92 | 13190.31 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 14221.27 | 01-FEB-21:00 | 8945.92 | 13190.31 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 14304.51 | 25-MAR-10:33 | 11501.89 | 10992.10 | 10646.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 14725.32 | 27-APR-10:33 | 7667.93 | 10992.10 | 10646.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 15190.50 | 14-MAY-10:33 | 11501.89 | 13190.31 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 15590.92 | 25-JUN-10:33 | 11501.89 | 13190.31 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16122.79 | 30-JUL-10:33 | 11501.89 | 13190.31 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16354.47 | 13-AUG-10:33 | 11501.89 | 13190.31 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17575.13 | 15-SEP-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 18924.04 | 06-OCT-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 18782.45 | 08-NOV-22:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17689.75 | 01-DEC-22:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 14221.27 | 7667.93 | 10992.10 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18924.04 | 11501.89 | 13190.31 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2277.79 | 20-JAN-11:50 | 519.79 | 332.00 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.76 |
February | 2779.69 | 08-FEB-13:30 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.87 |
March | 3427.10 | 02-MAR-13:20 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.05 |
April | 3203.26 | 27-APR-13:05 | 519.79 | 332.00 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 10.82 | 0.00 |
May | 3094.00 | 04-MAY-13:20 | 519.79 | 332.00 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.49 |
June | 2568.56 | 28-JUN-10:33 | 779.69 | 497.99 | 757.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.02 |
July | 3026.55 | 31-JUL-13:20 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 18.42 | 0.00 |
August | 3845.17 | 24-AUG-13:10 | 519.79 | 332.00 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 25.24 | 0.00 |
September | 3980.43 | 14-SEP-13:15 | 519.79 | 332.00 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.38 |
October | 4006.98 | 04-OCT-12:50 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.84 |
November | 3260.01 | 04-NOV-13:30 | 779.69 | 332.00 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.65 |
December | 2544.74 | 05-DEC-12:20 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.89 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2277.79 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4006.98 | 779.69 | 497.99 | 757.77 | 0.00 | 0.00 | 0.00 | 0.00 | 25.24 | 97.87 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1141.51 | 11-JAN-21:00 | 1053.36 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.27 |
February | 1252.97 | 27-FEB-21:00 | 1053.36 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.34 |
March | 1279.22 | 02-MAR-21:00 | 1053.36 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.80 |
April | 1621.11 | 27-APR-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.92 |
May | 1594.67 | 04-MAY-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.75 |
June | 1670.87 | 28-JUN-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.08 |
July | 1860.11 | 31-JUL-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.68 |
August | 2008.44 | 10-AUG-20:55 | 4815.36 | 2460.50 | 3008.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.01 |
September | 1806.55 | 14-SEP-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.70 |
October | 1572.60 | 04-OCT-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.86 |
November | 1268.63 | 04-NOV-18:10 | 6320.16 | 3767.64 | 4680.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.48 |
December | 1190.31 | 05-DEC-21:00 | 1053.36 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.97 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1141.51 | 1053.36 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.01 | |
Maximum of Months | 2008.44 | 6320.16 | 3767.64 | 4680.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.97 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 747.74 | 11-JAN-21:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.47 |
February | 827.99 | 27-FEB-19:10 | 1113.84 | 3040.79 | 3976.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.87 |
March | 837.55 | 18-MAR-10:33 | 286.42 | 570.15 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.19 |
April | 988.56 | 27-APR-18:10 | 1336.61 | 3648.94 | 4771.59 | 0.00 | 0.00 | 0.00 | 0.00 | 13.77 | 0.00 |
May | 1047.32 | 06-MAY-10:33 | 286.42 | 570.15 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.59 |
June | 1068.69 | 28-JUN-10:33 | 190.94 | 570.15 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.28 |
July | 1173.92 | 24-JUL-21:00 | 254.59 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.73 |
August | 1298.48 | 10-AUG-20:57 | 1018.37 | 2432.63 | 3181.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.75 |
September | 1077.25 | 14-SEP-10:33 | 190.94 | 570.15 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.00 |
October | 972.37 | 04-OCT-10:33 | 190.94 | 570.15 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.26 |
November | 887.41 | 04-NOV-10:33 | 286.42 | 570.15 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.03 |
December | 762.28 | 03-DEC-11:33 | 286.42 | 684.18 | 1060.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.80 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 747.74 | 190.94 | 570.15 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1298.48 | 1336.61 | 3648.94 | 4771.59 | 0.00 | 0.00 | 0.00 | 0.00 | 13.77 | 52.47 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 419.11 | 11-JAN-19:10 | 514.08 | 671.56 | 688.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.77 |
February | 471.39 | 28-FEB-11:33 | 146.88 | 209.86 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.45 |
March | 481.99 | 18-MAR-10:33 | 220.32 | 209.86 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.25 |
April | 573.39 | 29-APR-10:33 | 220.32 | 209.86 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.01 |
May | 613.64 | 06-MAY-10:33 | 220.32 | 209.86 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.57 |
June | 623.03 | 28-JUN-10:33 | 146.88 | 209.86 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.10 |
July | 657.57 | 24-JUL-18:10 | 1028.16 | 1343.12 | 1376.47 | 0.00 | 0.00 | 0.00 | 0.00 | 14.43 | 0.00 |
August | 665.62 | 10-AUG-18:10 | 1028.16 | 1343.12 | 1376.47 | 0.00 | 0.00 | 0.00 | 0.00 | 18.76 | 0.00 |
September | 626.42 | 14-SEP-10:33 | 146.88 | 209.86 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.21 |
October | 564.00 | 04-OCT-10:33 | 146.88 | 209.86 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.51 |
November | 512.21 | 04-NOV-10:33 | 220.32 | 209.86 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.04 |
December | 441.51 | 03-DEC-11:33 | 220.32 | 251.83 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.64 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 419.11 | 146.88 | 209.86 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 665.62 | 1028.16 | 1343.12 | 1376.47 | 0.00 | 0.00 | 0.00 | 0.00 | 18.76 | 28.45 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 36766.16 | 11-JAN-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 87.32 |
February | 37231.64 | 27-FEB-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 79.94 |
March | 37364.02 | 14-MAR-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 64.47 |
April | 38175.36 | 27-APR-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 30.16 |
May | 38115.47 | 15-MAY-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 45.00 |
June | 38322.53 | 28-JUN-19:55 | 1411.20 | 650.17 | 9145.60 | 79453.15 | 0.00 | 0.00 | 0.00 | 0.00 | 15.08 |
July | 38591.13 | 24-JUL-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 |
August | 38660.34 | 10-AUG-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 10.23 | 0.00 |
September | 38250.48 | 14-SEP-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 33.72 |
October | 37858.86 | 04-OCT-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 44.83 |
November | 37111.38 | 02-NOV-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 75.95 |
December | 36691.63 | 05-DEC-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 126.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 36691.63 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 38660.34 | 1411.20 | 650.17 | 9145.60 | 79453.15 | 0.00 | 0.00 | 0.00 | 10.23 | 126.07 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9465.09 | 08-JAN-11:35 | 10245.60 | 249.56 | 812.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 272.98 |
February | 10937.42 | 08-FEB-13:30 | 3415.20 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.35 |
March | 12724.48 | 02-MAR-13:20 | 3415.20 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.15 |
April | 11668.75 | 27-APR-14:10 | 5122.80 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 26.00 | 0.00 |
May | 11381.55 | 04-MAY-14:10 | 5122.80 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.22 |
June | 10668.45 | 10-JUN-10:33 | 15368.40 | 311.95 | 1066.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.90 |
July | 11382.64 | 30-JUL-10:33 | 15368.40 | 374.34 | 1219.29 | 0.00 | 0.00 | 0.00 | 0.00 | 2.23 | 0.00 |
August | 13252.01 | 24-AUG-15:03 | 51228.00 | 623.89 | 2133.76 | 0.00 | 0.00 | 0.00 | 0.00 | 63.26 | 0.00 |
September | 14068.15 | 23-SEP-13:15 | 10245.60 | 207.96 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.56 |
October | 14123.84 | 04-OCT-12:50 | 3415.20 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.44 |
November | 12716.09 | 04-NOV-13:30 | 10245.60 | 207.96 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.80 |
December | 10447.00 | 02-DEC-11:33 | 15368.40 | 311.95 | 1066.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.86 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9465.09 | 3415.20 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14123.84 | 51228.00 | 623.89 | 2133.76 | 0.00 | 0.00 | 0.00 | 0.00 | 63.26 | 272.98 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 26379.15 | 11-JAN-22:00 | 40553.76 | 8448.71 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 418.63 |
February | 28454.18 | 27-FEB-21:00 | 35484.54 | 9504.80 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 389.05 |
March | 29204.60 | 14-MAR-21:20 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 390.82 |
April | 34277.33 | 27-APR-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 243.72 |
May | 34319.19 | 04-MAY-21:52 | 456229.80 | 63365.33 | 73899.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.85 |
June | 35106.36 | 28-JUN-21:52 | 410606.82 | 57028.80 | 66509.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 191.63 |
July | 37863.37 | 24-JUL-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.80 |
August | 39345.61 | 10-AUG-21:05 | 91245.96 | 12673.07 | 14779.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.58 |
September | 37737.92 | 14-SEP-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.64 |
October | 35229.85 | 04-OCT-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 328.47 |
November | 29161.79 | 04-NOV-10:33 | 45622.98 | 6811.77 | 11084.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.13 |
December | 27573.83 | 03-DEC-11:33 | 45622.98 | 8174.13 | 12668.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 392.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 26379.15 | 35484.54 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.58 | |
Maximum of Months | 39345.61 | 456229.80 | 63365.33 | 73899.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 418.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2782.23 | 05-JAN-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.82 |
February | 3739.23 | 12-FEB-16:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.06 |
March | 3783.66 | 25-MAR-15:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.04 |
April | 3769.96 | 13-APR-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.03 |
May | 3905.88 | 14-MAY-18:01 | 819.00 | 1245.18 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.31 |
June | 3398.63 | 23-JUN-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.17 |
July | 3403.01 | 25-JUL-08:61 | 252.00 | 547.88 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.30 |
August | 3457.93 | 18-AUG-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.78 |
September | 3421.22 | 22-SEP-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.20 |
October | 3737.16 | 03-OCT-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.41 |
November | 3240.64 | 04-NOV-15:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.30 |
December | 3143.59 | 10-DEC-16:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.48 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2782.23 | 252.00 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.31 | |
Maximum of Months | 3905.88 | 970.20 | 1245.18 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.82 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 442.14 | 20-JAN-16:03 | 583.20 | 298.81 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.30 |
February | 3116.07 | 12-FEB-16:01 | 378.00 | 410.86 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.80 |
March | 3382.76 | 25-MAR-15:01 | 378.00 | 410.86 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.31 |
April | 3893.21 | 25-APR-17:41 | 777.60 | 953.34 | 1011.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.61 |
May | 3461.03 | 29-MAY-19:41 | 1170.00 | 1778.61 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.18 |
June | 3485.39 | 18-JUN-20:11 | 1386.00 | 1778.61 | 1817.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.42 |
July | 3648.35 | 25-JUL-16:51 | 972.00 | 498.01 | 1264.17 | 0.00 | 0.00 | 0.00 | 0.00 | 1.04 | 0.00 |
August | 3526.86 | 02-AUG-18:11 | 1386.00 | 1582.97 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.65 |
September | 3542.28 | 22-SEP-16:11 | 972.00 | 498.01 | 1264.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.65 |
October | 3159.30 | 06-OCT-15:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.91 |
November | 2923.63 | 04-NOV-15:01 | 378.00 | 410.86 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.04 |
December | 1063.82 | 02-DEC-16:01 | 378.00 | 410.86 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.89 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 442.14 | 378.00 | 298.81 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3893.21 | 1386.00 | 1778.61 | 1817.24 | 0.00 | 0.00 | 0.00 | 0.00 | 1.04 | 51.30 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 129.71 | 08-JAN-15:15 | 0.00 | 73.78 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.26 |
February | 475.70 | 08-FEB-13:40 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.19 |
March | 605.89 | 02-MAR-13:00 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.77 |
April | 550.05 | 27-APR-13:05 | 0.00 | 62.60 | 61.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.51 |
May | 530.52 | 04-MAY-13:20 | 0.00 | 62.60 | 61.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.35 |
June | 399.86 | 28-JUN-13:05 | 0.00 | 62.60 | 61.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.87 |
July | 499.21 | 31-JUL-13:20 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.71 | 0.00 |
August | 626.10 | 24-AUG-13:05 | 0.00 | 62.60 | 61.92 | 0.00 | 0.00 | 0.00 | 0.00 | 1.84 | 0.00 |
September | 670.75 | 14-SEP-13:30 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.85 |
October | 700.17 | 04-OCT-12:40 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.19 |
November | 542.82 | 04-NOV-13:30 | 0.00 | 73.78 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.01 |
December | 432.40 | 05-DEC-12:30 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.42 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 129.71 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 700.17 | 0.00 | 73.78 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 1.84 | 18.26 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 808.46 | 01-JAN-09:02 | 270.00 | 313.10 | 799.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.04 |
February | 909.70 | 26-FEB-09:02 | 270.00 | 313.10 | 799.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.13 |
March | 992.67 | 28-MAR-18:01 | 970.20 | 696.66 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.64 |
April | 1029.71 | 01-APR-21:52 | 693.00 | 475.25 | 438.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.21 |
May | 1093.96 | 14-MAY-21:51 | 1386.00 | 950.49 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.52 |
June | 1010.03 | 22-JUN-21:51 | 1800.00 | 749.21 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.88 |
July | 1017.51 | 25-JUL-15:02 | 583.20 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.11 | 0.00 |
August | 1015.09 | 08-AUG-21:31 | 1620.00 | 674.29 | 789.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 | 0.00 |
September | 1008.00 | 11-SEP-15:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 | 0.00 |
October | 1016.02 | 02-OCT-18:01 | 970.20 | 696.66 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.91 |
November | 901.27 | 05-NOV-08:62 | 324.00 | 375.72 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.30 |
December | 941.01 | 03-DEC-09:02 | 216.00 | 250.48 | 639.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.87 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 808.46 | 216.00 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1093.96 | 1800.00 | 950.49 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 | 12.04 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 471.52 | 20-JAN-16:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.32 |
February | 3222.62 | 12-FEB-16:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.77 |
March | 3438.76 | 25-MAR-08:61 | 378.00 | 697.30 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.72 |
April | 3319.40 | 13-APR-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.75 |
May | 3491.51 | 14-MAY-18:01 | 819.00 | 1245.18 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.82 |
June | 3120.84 | 18-JUN-08:62 | 324.00 | 597.68 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.24 |
July | 3138.89 | 11-JUL-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 |
August | 3191.38 | 25-AUG-08:61 | 252.00 | 547.88 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.65 |
September | 3168.61 | 23-SEP-08:61 | 378.00 | 697.30 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.14 |
October | 3281.83 | 03-OCT-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.89 |
November | 3167.07 | 04-NOV-15:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 |
December | 2377.31 | 02-DEC-09:02 | 270.00 | 498.07 | 816.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.36 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 471.52 | 252.00 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.82 | |
Maximum of Months | 3491.51 | 970.20 | 1245.18 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.72 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 354.13 | 27-JAN-19:06 | 693.00 | 791.48 | 605.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.25 |
February | 2509.90 | 27-FEB-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.68 |
March | 3157.57 | 25-MAR-08:61 | 378.00 | 697.22 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.74 |
April | 3130.84 | 25-APR-18:01 | 970.20 | 1108.08 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.33 |
May | 3387.43 | 06-MAY-08:51 | 540.00 | 996.02 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.41 |
June | 3205.99 | 10-JUN-08:51 | 540.00 | 996.02 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.04 |
July | 3662.15 | 24-JUL-08:32 | 216.00 | 469.55 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.12 |
August | 3578.19 | 10-AUG-08:32 | 216.00 | 469.55 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.78 |
September | 3324.97 | 13-SEP-08:51 | 360.00 | 782.59 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.82 |
October | 2803.02 | 07-OCT-08:61 | 378.00 | 697.22 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.75 |
November | 2465.33 | 04-NOV-15:01 | 378.00 | 410.86 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.53 |
December | 812.59 | 02-DEC-09:02 | 270.00 | 498.01 | 816.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.95 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 354.13 | 216.00 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.53 | |
Maximum of Months | 3662.15 | 970.20 | 1108.08 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.74 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1574.00 | 11-JAN-21:00 | 1760.39 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.16 |
February | 1788.66 | 27-FEB-19:10 | 8801.94 | 8299.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.25 |
March | 1900.42 | 25-MAR-10:33 | 2263.36 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.88 |
April | 2241.77 | 27-APR-18:10 | 10562.33 | 9959.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.07 | 0.00 |
May | 2340.16 | 06-MAY-10:33 | 2263.36 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.57 |
June | 2398.50 | 28-JUN-10:33 | 1508.90 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.94 |
July | 2532.57 | 24-JUL-18:10 | 10562.33 | 9959.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.44 | 0.00 |
August | 2578.50 | 13-AUG-10:33 | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.74 | 0.00 |
September | 2480.27 | 14-SEP-10:33 | 1508.90 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.10 |
October | 2202.16 | 04-OCT-10:33 | 1508.90 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.32 |
November | 1910.63 | 04-NOV-10:33 | 2263.36 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.01 |
December | 1736.49 | 03-DEC-11:33 | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.32 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 1574.00 | 1508.90 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2578.50 | 10562.33 | 9959.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.44 | 47.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2846.45 | 05-JAN-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.12 |
February | 3880.23 | 12-FEB-16:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.14 |
March | 3937.58 | 25-MAR-15:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.21 |
April | 3924.50 | 13-APR-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.21 |
May | 4071.74 | 14-MAY-18:01 | 819.00 | 1245.18 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.54 |
June | 3537.66 | 23-JUN-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.27 |
July | 3436.55 | 24-JUL-08:61 | 252.00 | 547.88 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.09 |
August | 3586.09 | 18-AUG-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.91 |
September | 3549.10 | 22-SEP-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.37 |
October | 3919.09 | 04-OCT-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.84 |
November | 3356.65 | 04-NOV-18:01 | 819.00 | 1245.18 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.43 |
December | 3220.79 | 10-DEC-16:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.82 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2846.45 | 252.00 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.09 | |
Maximum of Months | 4071.74 | 970.20 | 1245.18 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 432.48 | 20-JAN-16:05 | 583.20 | 298.81 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.51 |
February | 3052.08 | 26-FEB-16:01 | 378.00 | 410.86 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.61 |
March | 3471.91 | 25-MAR-15:01 | 378.00 | 410.86 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.21 |
April | 4036.24 | 25-APR-17:41 | 777.60 | 953.34 | 1011.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.86 |
May | 4031.89 | 21-MAY-17:41 | 777.60 | 1209.46 | 1011.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.40 |
June | 3674.11 | 19-JUN-21:51 | 1800.00 | 1191.67 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.75 |
July | 3788.39 | 19-JUL-21:51 | 1800.00 | 1191.67 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.61 |
August | 3715.74 | 06-AUG-21:51 | 1386.00 | 1511.82 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.48 |
September | 3656.96 | 22-SEP-16:11 | 972.00 | 498.01 | 1264.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.84 |
October | 3267.18 | 07-OCT-15:01 | 378.00 | 410.86 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.95 |
November | 3004.83 | 04-NOV-15:01 | 378.00 | 410.86 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.22 |
December | 359.90 | 29-DEC-19:06 | 693.00 | 791.48 | 605.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.16 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 359.90 | 378.00 | 298.81 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.84 | |
Maximum of Months | 4036.24 | 1800.00 | 1511.82 | 1264.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.51 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1976.31 | 05-JAN-16:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.60 |
February | 2126.45 | 26-FEB-16:01 | 378.00 | 258.31 | 379.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.97 |
March | 2450.94 | 25-MAR-15:01 | 378.00 | 258.31 | 379.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.73 |
April | 2360.62 | 13-APR-18:01 | 970.20 | 696.66 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.92 |
May | 2438.96 | 14-MAY-18:01 | 819.00 | 782.76 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
June | 2170.71 | 25-JUN-08:61 | 378.00 | 438.35 | 1119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.53 |
July | 2184.61 | 11-JUL-15:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.09 |
August | 2211.69 | 18-AUG-15:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.98 |
September | 2224.92 | 22-SEP-18:01 | 970.20 | 696.66 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.28 |
October | 2412.00 | 04-OCT-18:01 | 970.20 | 696.66 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.62 |
November | 2143.39 | 02-NOV-15:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.79 |
December | 2123.83 | 10-DEC-16:01 | 378.00 | 258.31 | 379.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1976.31 | 378.00 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 | |
Maximum of Months | 2450.94 | 970.20 | 782.76 | 1119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.60 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18024.62 | 11-JAN-23:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.60 |
February | 19050.19 | 27-FEB-23:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.73 |
March | 18939.41 | 10-MAR-23:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.21 |
April | 20763.65 | 27-APR-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.44 |
May | 21101.62 | 05-MAY-21:53 | 188921.38 | 13944.14 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.56 |
June | 21541.59 | 28-JUN-21:52 | 242898.91 | 17928.18 | 60731.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.77 |
July | 22260.17 | 24-JUL-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.36 |
August | 22252.06 | 10-AUG-21:52 | 242898.91 | 17928.18 | 60731.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.81 |
September | 20993.24 | 12-SEP-21:52 | 215910.14 | 15936.16 | 53983.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.56 |
October | 19842.50 | 04-OCT-22:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.20 |
November | 18994.71 | 06-NOV-23:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.44 |
December | 17779.87 | 29-DEC-23:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.21 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 17779.87 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.81 | |
Maximum of Months | 22260.17 | 242898.91 | 17928.18 | 60731.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.21 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 20072.51 | 11-JAN-22:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.18 |
February | 20862.22 | 27-FEB-23:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.73 |
March | 20842.23 | 08-MAR-23:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.97 |
April | 22275.99 | 27-APR-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.44 |
May | 22607.98 | 05-MAY-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.94 |
June | 22890.50 | 28-JUN-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.01 |
July | 23521.14 | 24-JUL-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.12 |
August | 23456.67 | 10-AUG-21:05 | 53977.54 | 3984.04 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.72 |
September | 22321.33 | 12-SEP-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.99 |
October | 21367.20 | 04-OCT-22:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.20 |
November | 20857.51 | 06-NOV-23:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.44 |
December | 19809.67 | 29-DEC-23:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.22 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 19809.67 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.72 | |
Maximum of Months | 23521.14 | 53977.54 | 3984.04 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.22 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 26602.78 | 30-JAN-11:33 | 1601.14 | 884.01 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 111.15 |
February | 27755.78 | 27-FEB-11:45 | 1067.42 | 589.34 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 53.42 |
March | 28894.50 | 14-MAR-10:45 | 1067.42 | 589.34 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 88.05 |
April | 30227.01 | 27-APR-10:33 | 1601.14 | 884.01 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 24.93 |
May | 30342.60 | 14-MAY-10:33 | 2401.70 | 1060.81 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 27.16 |
June | 30623.93 | 10-JUN-10:33 | 2401.70 | 884.01 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 26.18 |
July | 31021.13 | 24-JUL-10:37 | 1601.14 | 884.01 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 11.85 | 0.00 |
August | 31091.67 | 13-AUG-10:40 | 2401.70 | 1060.81 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.02 | 0.00 |
September | 30544.84 | 10-SEP-10:33 | 2401.70 | 1060.81 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 38.83 |
October | 29366.68 | 07-OCT-10:33 | 2401.70 | 884.01 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 65.01 |
November | 28888.15 | 04-NOV-10:45 | 1601.14 | 589.34 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 |
December | 27114.85 | 03-DEC-11:50 | 800.57 | 353.60 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 86.52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 26602.78 | 800.57 | 353.60 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31091.67 | 2401.70 | 1060.81 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 11.85 | 111.15 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3346.98 | 30-JAN-11:33 | 1596.96 | 1646.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.50 |
February | 3751.87 | 27-FEB-11:45 | 1064.64 | 1097.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.13 |
March | 3974.38 | 02-MAR-11:33 | 1596.96 | 1646.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.67 |
April | 4787.93 | 27-APR-18:10 | 11178.72 | 10540.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.32 | 0.00 |
May | 4945.36 | 06-MAY-10:33 | 2395.44 | 1646.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.69 |
June | 5090.45 | 28-JUN-18:10 | 11178.72 | 10540.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.49 | 0.00 |
July | 5360.37 | 24-JUL-18:10 | 11178.72 | 10540.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.28 | 0.00 |
August | 6159.39 | 10-AUG-15:03 | 7984.80 | 3293.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.42 | 0.00 |
September | 5093.60 | 14-SEP-10:33 | 1596.96 | 1646.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.31 |
October | 4562.15 | 04-OCT-10:33 | 1596.96 | 1646.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.82 |
November | 4044.72 | 04-NOV-10:50 | 1596.96 | 1097.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.88 |
December | 3610.45 | 03-DEC-11:33 | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.32 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 3346.98 | 1064.64 | 1097.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6159.39 | 11178.72 | 10540.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.42 | 88.50 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.377150E+12 | 225168.97 | 03-JAN-07:00 | 0.528473E+12 | 534395.30 | 25-JAN-18:00 |
February | 0.338418E+12 | 224903.63 | 03-FEB-07:30 | 0.489094E+12 | 520464.05 | 04-FEB-18:49 |
March | 0.373716E+12 | 225168.46 | 15-MAR-06:19 | 0.546422E+12 | 539983.04 | 22-MAR-17:40 |
April | 0.368700E+12 | 290829.02 | 27-APR-18:10 | 0.517596E+12 | 514456.73 | 18-APR-17:10 |
May | 0.387440E+12 | 253628.26 | 04-MAY-19:19 | 0.503159E+12 | 490823.92 | 17-MAY-19:10 |
June | 0.387473E+12 | 290728.86 | 28-JUN-18:10 | 0.423889E+12 | 415098.34 | 13-JUN-21:10 |
July | 0.426366E+12 | 317190.60 | 24-JUL-18:10 | 0.390639E+12 | 331885.62 | 04-JUL-20:00 |
August | 0.445270E+12 | 335399.91 | 10-AUG-18:10 | 0.385314E+12 | 325648.33 | 31-AUG-17:30 |
September | 0.387915E+12 | 260000.28 | 13-SEP-18:30 | 0.424512E+12 | 421489.01 | 27-SEP-20:00 |
October | 0.375568E+12 | 235734.73 | 04-OCT-18:10 | 0.560542E+12 | 476974.58 | 31-OCT-18:10 |
November | 0.361588E+12 | 226976.26 | 04-NOV-17:10 | 0.528066E+12 | 532987.96 | 21-NOV-18:40 |
December | 0.377107E+12 | 224660.91 | 15-DEC-07:49 | 0.532137E+12 | 536781.22 | 14-DEC-18:30 |
Annual Sum or Average | 0.460671E+13 | 0.582984E+13 | ||||
Minimum of Months | 0.338418E+12 | 224660.91 | 0.385314E+12 | 325648.33 | ||
Maximum of Months | 0.445270E+12 | 335399.91 | 0.560542E+12 | 539983.04 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.673876E+11 | 0.210395E+11 | 0.140828E+12 | 0.691147E+11 | 0.401416E+11 | 0.226579E+10 | 0.00 | 0.638853E+09 | 0.00 | 0.00 | 0.224671E+11 | 0.804765E+10 | 0.00 |
February | 0.605329E+11 | 0.173454E+11 | 0.127191E+12 | 0.624261E+11 | 0.362981E+11 | 0.326451E+10 | 0.00 | 0.296017E+10 | 0.00 | 0.00 | 0.164118E+11 | 0.727208E+10 | 0.00 |
March | 0.666248E+11 | 0.169308E+11 | 0.140882E+12 | 0.691169E+11 | 0.405808E+11 | 0.527534E+10 | 0.00 | 0.715482E+10 | 0.00 | 0.00 | 0.138738E+11 | 0.804609E+10 | 0.00 |
April | 0.639899E+11 | 0.141028E+11 | 0.136245E+12 | 0.668843E+11 | 0.404336E+11 | 0.658909E+10 | 0.00 | 0.188866E+11 | 0.00 | 0.00 | 0.870059E+10 | 0.779734E+10 | 0.00 |
May | 0.657725E+11 | 0.125260E+11 | 0.140860E+12 | 0.691150E+11 | 0.431287E+11 | 0.719885E+10 | 0.00 | 0.304821E+11 | 0.00 | 0.00 | 0.503699E+10 | 0.804734E+10 | 0.00 |
June | 0.632910E+11 | 0.110232E+11 | 0.136336E+12 | 0.668862E+11 | 0.429155E+11 | 0.687712E+10 | 0.00 | 0.445722E+11 | 0.00 | 0.00 | 0.266012E+10 | 0.778876E+10 | 0.00 |
July | 0.655509E+11 | 0.118967E+11 | 0.140770E+12 | 0.691124E+11 | 0.457350E+11 | 0.703271E+10 | 0.00 | 0.692126E+11 | 0.00 | 0.00 | 0.371227E+10 | 0.805564E+10 | 0.00 |
August | 0.658601E+11 | 0.136587E+11 | 0.140892E+12 | 0.691164E+11 | 0.462702E+11 | 0.708239E+10 | 0.00 | 0.836526E+11 | 0.00 | 0.00 | 0.535483E+10 | 0.804720E+10 | 0.00 |
September | 0.643518E+11 | 0.153910E+11 | 0.136256E+12 | 0.668846E+11 | 0.426069E+11 | 0.680215E+10 | 0.00 | 0.402850E+11 | 0.00 | 0.00 | 0.239300E+10 | 0.779861E+10 | 0.00 |
October | 0.669530E+11 | 0.182634E+11 | 0.140818E+12 | 0.691144E+11 | 0.415576E+11 | 0.652036E+10 | 0.00 | 0.138221E+11 | 0.00 | 0.00 | 0.520904E+10 | 0.804600E+10 | 0.00 |
November | 0.651190E+11 | 0.197440E+11 | 0.136330E+12 | 0.668859E+11 | 0.391317E+11 | 0.380209E+10 | 0.00 | 0.374244E+10 | 0.00 | 0.00 | 0.139786E+11 | 0.778058E+10 | 0.00 |
December | 0.674225E+11 | 0.215799E+11 | 0.140770E+12 | 0.691136E+11 | 0.402105E+11 | 0.256519E+10 | 0.00 | 0.117132E+10 | 0.00 | 0.00 | 0.209916E+11 | 0.805607E+10 | 0.00 |
Annual Sum or Average | 0.782856E+12 | 0.193501E+12 | 0.165818E+13 | 0.813771E+12 | 0.499010E+12 | 0.652756E+11 | 0.00 | 0.316581E+12 | 0.00 | 0.00 | 0.120790E+12 | 0.947834E+11 | 0.00 |
Minimum of Months | 0.605329E+11 | 0.110232E+11 | 0.127191E+12 | 0.624261E+11 | 0.362981E+11 | 0.226579E+10 | 0.00 | 0.638853E+09 | 0.00 | 0.00 | 0.239300E+10 | 0.727208E+10 | 0.00 |
Maximum of Months | 0.674225E+11 | 0.215799E+11 | 0.140892E+12 | 0.691169E+11 | 0.462702E+11 | 0.719885E+10 | 0.00 | 0.836526E+11 | 0.00 | 0.00 | 0.224671E+11 | 0.805607E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.151918E+12 | 0.00 | 0.135205E+12 | 0.00 | 0.241350E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.132691E+12 | 0.00 | 0.219199E+12 | 0.00 | 0.00 |
March | 0.152024E+12 | 0.00 | 0.153760E+12 | 0.00 | 0.240638E+12 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.142770E+12 | 0.00 | 0.227870E+12 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.122498E+12 | 0.00 | 0.228682E+12 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 0.618497E+11 | 0.00 | 0.214925E+12 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 0.214627E+11 | 0.00 | 0.217355E+12 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 0.172866E+11 | 0.00 | 0.215989E+12 | 0.00 | 0.00 |
September | 0.146971E+12 | 0.00 | 0.664399E+11 | 0.00 | 0.211101E+12 | 0.00 | 0.00 |
October | 0.151903E+12 | 0.00 | 0.185329E+12 | 0.00 | 0.223310E+12 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.158282E+12 | 0.00 | 0.222692E+12 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.143619E+12 | 0.00 | 0.236697E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178884E+13 | 0.00 | 0.134119E+13 | 0.00 | 0.269981E+13 | 0.00 | 0.00 |
Minimum of Months | 0.137204E+12 | 0.00 | 0.172866E+11 | 0.00 | 0.211101E+12 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.185329E+12 | 0.00 | 0.241350E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 64632.59 | 02-JAN-20:10 | 12338.45 | 01-JAN-00:10 | 89171.45 | 02-JAN-07:10 | 49607.07 | 02-JAN-07:19 | 21469.47 | 13-JAN-19:10 | 3173.91 | 03-JAN-07:19 | 0.00 | 01-JAN-00:10 |
February | 64632.59 | 01-FEB-20:10 | 12338.45 | 01-FEB-00:10 | 89171.45 | 01-FEB-07:10 | 49607.07 | 01-FEB-07:19 | 22361.17 | 27-FEB-21:19 | 3206.97 | 08-FEB-11:39 | 0.00 | 01-FEB-00:10 |
March | 64632.59 | 01-MAR-20:10 | 12338.45 | 01-MAR-00:10 | 89171.45 | 01-MAR-07:10 | 49607.07 | 13-MAR-06:19 | 23429.51 | 18-MAR-20:49 | 3203.68 | 02-MAR-10:09 | 0.00 | 01-MAR-00:10 |
April | 64632.59 | 03-APR-19:10 | 12338.45 | 01-APR-00:10 | 89171.45 | 03-APR-06:10 | 49606.78 | 04-APR-06:19 | 28197.80 | 27-APR-21:00 | 3164.10 | 06-APR-06:10 | 0.00 | 01-APR-00:10 |
May | 64632.59 | 01-MAY-19:10 | 12338.45 | 01-MAY-00:10 | 89171.45 | 01-MAY-06:10 | 49606.67 | 01-MAY-06:19 | 29769.36 | 15-MAY-21:30 | 3153.14 | 18-MAY-09:09 | 0.00 | 01-MAY-00:10 |
June | 64632.59 | 01-JUN-19:40 | 12338.45 | 01-JUN-00:10 | 89171.45 | 01-JUN-06:10 | 49605.70 | 22-JUN-06:19 | 29254.20 | 28-JUN-21:00 | 3093.47 | 20-JUN-18:19 | 0.00 | 01-JUN-00:10 |
July | 64632.59 | 10-JUL-19:30 | 12338.45 | 01-JUL-00:10 | 89171.45 | 03-JUL-06:10 | 49605.70 | 10-JUL-06:19 | 30160.05 | 31-JUL-21:00 | 3272.05 | 31-JUL-18:10 | 0.00 | 01-JUL-00:10 |
August | 64632.59 | 01-AUG-19:19 | 12338.45 | 01-AUG-00:10 | 89171.45 | 01-AUG-06:10 | 49606.38 | 16-AUG-06:19 | 31141.22 | 24-AUG-21:00 | 3389.68 | 10-AUG-18:10 | 0.00 | 01-AUG-00:10 |
September | 64632.59 | 01-SEP-19:10 | 12338.45 | 01-SEP-00:10 | 89171.45 | 01-SEP-06:10 | 49607.07 | 06-SEP-06:19 | 31062.20 | 13-SEP-21:00 | 3131.00 | 08-SEP-15:09 | 0.00 | 01-SEP-00:10 |
October | 64632.59 | 02-OCT-19:10 | 12338.45 | 01-OCT-00:10 | 89171.45 | 02-OCT-06:10 | 49607.07 | 02-OCT-06:19 | 30123.55 | 04-OCT-21:19 | 3187.66 | 30-OCT-08:09 | 0.00 | 01-OCT-00:10 |
November | 64632.59 | 01-NOV-19:10 | 12338.45 | 01-NOV-00:10 | 89171.45 | 01-NOV-06:10 | 49607.07 | 01-NOV-06:19 | 23100.74 | 06-NOV-21:00 | 3212.26 | 11-NOV-11:39 | 0.00 | 01-NOV-00:10 |
December | 64632.59 | 01-DEC-20:10 | 12338.45 | 01-DEC-00:10 | 89171.45 | 01-DEC-07:10 | 49607.07 | 01-DEC-07:19 | 21727.64 | 26-DEC-19:10 | 3189.41 | 05-DEC-10:20 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 64632.59 | 12338.45 | 89171.45 | 49605.70 | 21469.47 | 3093.47 | 0.00 | |||||||
Maximum of Months | 64632.59 | 12338.45 | 89171.45 | 49607.07 | 31141.22 | 3389.68 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 4290.45 | 11-JAN-19:10 | 0.00 | 0.00 | 9938.94 | 01-JAN-00:10 | 4751.13 | 17-JAN-07:10 | 0.00 |
February | 36346.04 | 27-FEB-16:10 | 0.00 | 0.00 | 9938.94 | 01-FEB-00:20 | 4751.13 | 14-FEB-19:49 | 0.00 |
March | 45617.27 | 18-MAR-15:09 | 0.00 | 0.00 | 9938.94 | 01-MAR-00:20 | 4751.12 | 14-MAR-06:19 | 0.00 |
April | 87825.73 | 27-APR-15:09 | 0.00 | 0.00 | 9938.94 | 01-APR-00:10 | 4751.13 | 07-APR-18:49 | 0.00 |
May | 76868.64 | 04-MAY-15:09 | 0.00 | 0.00 | 9938.94 | 03-MAY-03:49 | 4751.13 | 24-MAY-06:40 | 0.00 |
June | 87343.71 | 28-JUN-18:10 | 0.00 | 0.00 | 9938.94 | 22-JUN-16:30 | 4751.13 | 21-JUN-06:30 | 0.00 |
July | 112626.72 | 24-JUL-18:10 | 0.00 | 0.00 | 9938.94 | 14-JUL-16:30 | 4751.13 | 27-JUL-06:19 | 0.00 |
August | 130336.53 | 10-AUG-18:10 | 0.00 | 0.00 | 9938.94 | 06-AUG-15:09 | 4751.13 | 04-AUG-06:00 | 0.00 |
September | 87303.51 | 14-SEP-15:20 | 0.00 | 0.00 | 9938.94 | 22-SEP-16:19 | 4751.12 | 13-SEP-06:49 | 0.00 |
October | 62129.49 | 04-OCT-15:09 | 0.00 | 0.00 | 9938.94 | 03-OCT-04:00 | 4751.13 | 24-OCT-06:40 | 0.00 |
November | 54436.94 | 04-NOV-15:09 | 0.00 | 0.00 | 9938.94 | 08-NOV-22:10 | 4751.13 | 15-NOV-19:49 | 0.00 |
December | 9332.83 | 05-DEC-12:30 | 0.00 | 0.00 | 9938.94 | 01-DEC-00:20 | 4751.13 | 06-DEC-07:30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 4290.45 | 0.00 | 0.00 | 9938.94 | 4751.12 | 0.00 | |||
Maximum of Months | 130336.53 | 0.00 | 0.00 | 9938.94 | 4751.13 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 225168.97 | 03-JAN-07:00 | 36001.17 | 89171.45 | 12338.45 | 49607.07 | 16017.06 | 2676.25 | 0.00 | 1445.88 | 0.00 |
February | 224903.63 | 03-FEB-07:30 | 36001.17 | 89171.45 | 12338.45 | 49607.07 | 15805.86 | 2629.10 | 0.00 | 1436.61 | 0.00 |
March | 225168.46 | 15-MAR-06:19 | 36001.17 | 89171.45 | 12338.45 | 49607.07 | 15303.49 | 2526.77 | 0.00 | 3676.09 | 0.00 |
April | 290829.02 | 27-APR-18:10 | 53578.21 | 77573.37 | 0.00 | 28157.33 | 24205.38 | 3096.27 | 0.00 | 87119.71 | 0.00 |
May | 253628.26 | 04-MAY-19:19 | 64632.59 | 86439.81 | 12338.45 | 10999.77 | 21859.35 | 2789.58 | 0.00 | 48210.23 | 0.00 |
June | 290728.86 | 28-JUN-18:10 | 53184.46 | 77573.37 | 0.00 | 28157.23 | 24299.68 | 3064.38 | 0.00 | 87343.71 | 0.00 |
July | 317190.60 | 24-JUL-18:10 | 52987.32 | 77573.37 | 0.00 | 28157.23 | 25485.57 | 3254.16 | 0.00 | 112626.72 | 0.00 |
August | 335399.91 | 10-AUG-18:10 | 53578.21 | 77573.37 | 0.00 | 28157.73 | 25257.88 | 3389.68 | 0.00 | 130336.53 | 0.00 |
September | 260000.28 | 13-SEP-18:30 | 57474.69 | 77573.37 | 12338.45 | 28169.74 | 20895.81 | 2731.35 | 0.00 | 53646.98 | 0.00 |
October | 235734.73 | 04-OCT-18:10 | 57474.69 | 77573.37 | 12338.45 | 28159.60 | 20228.88 | 2576.43 | 0.00 | 30261.37 | 0.00 |
November | 226976.26 | 04-NOV-17:10 | 46975.58 | 72654.62 | 12338.45 | 49247.41 | 15176.94 | 2534.00 | 0.00 | 21862.67 | 0.00 |
December | 224660.91 | 15-DEC-07:49 | 36001.17 | 89171.45 | 12338.45 | 49607.07 | 15890.90 | 2656.25 | 0.00 | 1097.88 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 224660.91 | 36001.17 | 72654.62 | 0.00 | 10999.77 | 15176.94 | 2526.77 | 0.00 | 1097.88 | 0.00 | |
Maximum of Months | 335399.91 | 64632.59 | 89171.45 | 12338.45 | 49607.07 | 25485.57 | 3389.68 | 0.00 | 130336.53 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 198238.14 | 20-JAN-11:50 | 0.00 | 250400.13 | 30-JAN-21:40 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 201745.73 | 08-FEB-11:50 | 0.00 | 250435.74 | 07-FEB-21:30 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 200552.63 | 03-MAR-11:50 | 0.00 | 249312.41 | 03-MAR-21:40 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 187313.49 | 24-APR-22:40 | 0.00 | 245699.11 | 03-APR-20:19 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 183508.26 | 18-MAY-09:20 | 0.00 | 239024.97 | 01-MAY-20:40 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 154150.82 | 15-JUN-04:30 | 0.00 | 233032.45 | 01-JUN-20:30 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 91284.20 | 03-JUL-03:00 | 0.00 | 226631.85 | 03-JUL-20:19 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 94384.82 | 21-AUG-04:00 | 0.00 | 223915.36 | 30-AUG-20:30 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 169813.55 | 27-SEP-03:09 | 0.00 | 226909.21 | 29-SEP-20:19 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 195368.30 | 30-OCT-08:09 | 0.00 | 233988.33 | 31-OCT-20:00 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 210727.42 | 11-NOV-11:50 | 0.00 | 240294.52 | 30-NOV-21:49 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 203987.69 | 12-DEC-11:50 | 0.00 | 246841.34 | 29-DEC-21:40 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 104248.32 | 0.00 | 91284.20 | 0.00 | 223915.36 | 0.00 | |||
Maximum of Months | 104248.32 | 0.00 | 210727.42 | 0.00 | 250435.74 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.67 | 20.47 | 1.67 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
February | 0.17 | 20.50 | 0.17 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.71 | 0.33 | 21.71 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.69 | 0.50 | 21.69 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.78 | 1.50 | 21.78 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.74 | 0.83 | 21.74 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.67 | 20.49 | 0.67 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 |
December | 2.00 | 20.44 | 2.00 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
Annual Sum or Average | 4.50 | 20.46 | 4.50 | 20.46 | 3.17 | 20.80 | 3.17 | 20.99 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.00 | 20.50 | 2.00 | 20.50 | 1.50 | 21.78 | 1.50 | 21.78 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.00 | 20.46 | 4.00 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 |
February | 1.17 | 20.46 | 1.17 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.96 | 1.67 | 21.96 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.94 | 0.83 | 21.94 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 21.90 | 2.50 | 21.90 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.72 | 1.67 | 21.72 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 22.02 | 0.17 | 22.02 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.67 | 20.45 | 0.67 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 |
December | 3.17 | 20.43 | 3.17 | 20.43 | 0.00 | 20.43 | 0.00 | 20.43 |
Annual Sum or Average | 9.00 | 20.45 | 9.00 | 20.45 | 6.83 | 20.84 | 6.83 | 21.06 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.00 | 20.46 | 4.00 | 20.46 | 2.50 | 22.02 | 2.50 | 22.02 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.78 | 0.17 | 21.78 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 21.76 | 2.17 | 21.76 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 21.82 | 3.17 | 21.82 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 21.84 | 4.67 | 21.84 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.76 | 1.50 | 21.76 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.71 | 0.50 | 21.71 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 12.17 | 21.80 | 12.17 | 21.80 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 21.84 | 4.67 | 21.84 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.67 | 20.46 | 1.67 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 |
February | 0.17 | 20.47 | 0.17 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.67 | 20.47 | 0.67 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
December | 2.67 | 20.45 | 2.67 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 |
Annual Sum or Average | 5.17 | 20.46 | 5.17 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.67 | 20.47 | 2.67 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.33 | 20.45 | 5.33 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 |
February | 1.83 | 20.49 | 1.83 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 22.33 | 0.17 | 22.33 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.95 | 0.33 | 21.95 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 22.45 | 0.67 | 22.45 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 22.33 | 2.50 | 22.33 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 22.31 | 3.33 | 22.31 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 22.26 | 0.33 | 22.26 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.00 | 20.46 | 1.00 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 |
December | 4.00 | 20.44 | 4.00 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
Annual Sum or Average | 12.17 | 20.45 | 12.17 | 20.45 | 7.33 | 20.88 | 7.33 | 21.15 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5.33 | 20.49 | 5.33 | 20.49 | 3.33 | 22.45 | 3.33 | 22.45 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.17 | 20.51 | 3.17 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
February | 0.33 | 20.54 | 0.33 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.74 | 0.17 | 21.74 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.86 | 0.50 | 21.86 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.70 | 0.17 | 21.70 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.73 | 1.50 | 21.73 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 21.79 | 3.33 | 21.79 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.86 | 1.00 | 21.86 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.83 | 20.51 | 0.83 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
December | 3.00 | 20.48 | 3.00 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 |
Annual Sum or Average | 7.33 | 20.50 | 7.33 | 20.50 | 6.67 | 20.90 | 6.67 | 21.11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.17 | 20.54 | 3.17 | 20.54 | 3.33 | 21.86 | 3.33 | 21.86 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.50 | 20.49 | 6.50 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 |
February | 2.83 | 20.52 | 2.83 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 22.02 | 2.67 | 22.02 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 21.94 | 2.17 | 21.94 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 21.92 | 4.83 | 21.92 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 21.79 | 3.33 | 21.79 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.94 | 0.33 | 21.94 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.33 | 20.51 | 1.33 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
December | 5.33 | 20.48 | 5.33 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 |
Annual Sum or Average | 16.00 | 20.50 | 16.00 | 20.50 | 13.33 | 20.91 | 13.33 | 21.14 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6.50 | 20.52 | 6.50 | 20.52 | 4.83 | 22.02 | 4.83 | 22.02 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 20.51 | 0.67 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.70 | 0.67 | 21.70 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.71 | 0.83 | 21.71 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.84 | 0.17 | 21.84 |
November | 0.17 | 20.48 | 0.17 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 |
December | 1.00 | 20.46 | 1.00 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 |
Annual Sum or Average | 1.83 | 20.48 | 1.83 | 20.48 | 1.67 | 20.87 | 1.67 | 21.07 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.00 | 20.51 | 1.00 | 20.51 | 0.83 | 21.84 | 0.83 | 21.84 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 742.33 | 23.24 | 0.00 | 23.24 | 0.00 | 23.24 |
February | 672.00 | 23.07 | 0.00 | 23.07 | 0.00 | 23.07 |
March | 744.00 | 22.88 | 0.00 | 22.88 | 0.00 | 22.88 |
April | 720.00 | 22.76 | 0.00 | 22.76 | 0.00 | 22.76 |
May | 744.00 | 22.85 | 0.00 | 22.85 | 0.00 | 22.85 |
June | 719.67 | 23.01 | 0.00 | 23.01 | 0.00 | 23.01 |
July | 686.50 | 23.18 | 0.67 | 23.18 | 0.00 | 23.18 |
August | 513.17 | 23.26 | 13.50 | 23.28 | 0.00 | 23.28 |
September | 390.33 | 23.40 | 30.67 | 23.44 | 0.00 | 23.44 |
October | 473.83 | 23.59 | 0.00 | 23.59 | 0.00 | 23.59 |
November | 510.50 | 23.65 | 11.50 | 23.65 | 0.00 | 23.65 |
December | 718.50 | 23.53 | 0.00 | 23.53 | 0.00 | 23.53 |
Annual Sum or Average | 7634.83 | 23.16 | 56.33 | 23.17 | 0.00 | 23.17 |
Minimum of Months | 390.33 | 22.76 | 0.00 | 22.76 | 0.00 | 22.76 |
Maximum of Months | 744.00 | 23.65 | 30.67 | 23.65 | 0.00 | 23.65 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 740.50 | 21.04 | 209.33 | 21.03 | 209.33 | 21.02 |
February | 652.00 | 21.10 | 129.33 | 21.11 | 121.67 | 21.10 |
March | 713.17 | 21.16 | 24.00 | 21.21 | 9.00 | 21.21 |
April | 678.83 | 21.26 | 22.83 | 21.35 | 0.00 | 21.35 |
May | 689.50 | 21.33 | 29.33 | 21.43 | 0.00 | 21.43 |
June | 676.50 | 21.42 | 15.00 | 21.47 | 0.00 | 21.47 |
July | 616.00 | 21.62 | 76.33 | 21.83 | 0.00 | 21.83 |
August | 560.67 | 21.59 | 122.33 | 21.96 | 0.00 | 21.96 |
September | 585.17 | 21.38 | 94.33 | 21.72 | 0.00 | 21.72 |
October | 682.50 | 21.20 | 37.67 | 21.35 | 0.00 | 21.35 |
November | 706.83 | 21.05 | 35.17 | 21.08 | 27.67 | 21.07 |
December | 734.17 | 21.06 | 171.50 | 21.05 | 170.67 | 21.05 |
Annual Sum or Average | 8035.83 | 21.26 | 967.17 | 21.36 | 538.33 | 21.34 |
Minimum of Months | 560.67 | 21.04 | 15.00 | 21.03 | 0.00 | 21.02 |
Maximum of Months | 740.50 | 21.62 | 209.33 | 21.96 | 209.33 | 21.96 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.63 | 0.00 | 21.63 | 0.00 | 21.63 |
February | 672.00 | 21.91 | 0.00 | 21.91 | 0.00 | 21.91 |
March | 744.00 | 22.26 | 0.00 | 22.26 | 0.00 | 22.26 |
April | 694.67 | 22.52 | 1.83 | 22.53 | 0.00 | 22.53 |
May | 686.17 | 22.76 | 6.67 | 22.77 | 0.00 | 22.77 |
June | 605.83 | 22.84 | 14.33 | 22.87 | 0.00 | 22.87 |
July | 453.67 | 22.97 | 105.67 | 23.15 | 0.00 | 23.15 |
August | 361.33 | 22.88 | 172.67 | 23.21 | 0.00 | 23.21 |
September | 511.17 | 22.82 | 67.00 | 22.94 | 0.00 | 22.94 |
October | 723.50 | 22.54 | 0.00 | 22.54 | 0.00 | 22.54 |
November | 718.50 | 22.00 | 0.00 | 22.00 | 0.00 | 22.00 |
December | 744.00 | 21.75 | 0.00 | 21.75 | 0.00 | 21.75 |
Annual Sum or Average | 7658.83 | 22.34 | 368.17 | 22.42 | 0.00 | 22.42 |
Minimum of Months | 361.33 | 21.63 | 0.00 | 21.63 | 0.00 | 21.63 |
Maximum of Months | 744.00 | 22.97 | 172.67 | 23.21 | 0.00 | 23.21 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.06 | 16.33 | 21.06 | 16.33 | 21.06 |
February | 672.00 | 21.19 | 18.17 | 21.19 | 18.17 | 21.18 |
March | 744.00 | 21.49 | 1.17 | 21.48 | 1.17 | 21.48 |
April | 720.00 | 21.90 | 0.00 | 21.90 | 0.00 | 21.90 |
May | 744.00 | 22.41 | 0.00 | 22.41 | 0.00 | 22.41 |
June | 718.50 | 22.75 | 0.00 | 22.75 | 0.00 | 22.75 |
July | 700.17 | 23.07 | 0.00 | 23.07 | 0.00 | 23.07 |
August | 635.33 | 23.11 | 3.50 | 23.12 | 0.00 | 23.12 |
September | 710.00 | 22.72 | 0.00 | 22.72 | 0.00 | 22.72 |
October | 744.00 | 22.02 | 0.00 | 22.02 | 0.00 | 22.02 |
November | 720.00 | 21.38 | 0.00 | 21.38 | 0.00 | 21.38 |
December | 744.00 | 21.09 | 0.00 | 21.09 | 0.00 | 21.09 |
Annual Sum or Average | 8596.00 | 22.00 | 39.17 | 22.00 | 35.67 | 21.99 |
Minimum of Months | 635.33 | 21.06 | 0.00 | 21.06 | 0.00 | 21.06 |
Maximum of Months | 744.00 | 23.11 | 18.17 | 23.12 | 18.17 | 23.12 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.00 | 51.83 | 21.00 | 51.83 | 21.00 |
February | 672.00 | 21.07 | 51.00 | 21.06 | 51.00 | 21.06 |
March | 744.00 | 21.19 | 12.17 | 21.19 | 12.17 | 21.19 |
April | 720.00 | 21.58 | 0.00 | 21.58 | 0.00 | 21.58 |
May | 744.00 | 22.10 | 0.00 | 22.10 | 0.00 | 22.10 |
June | 720.00 | 22.46 | 0.00 | 22.46 | 0.00 | 22.46 |
July | 737.00 | 22.82 | 0.00 | 22.82 | 0.00 | 22.82 |
August | 726.50 | 22.91 | 0.00 | 22.91 | 0.00 | 22.91 |
September | 720.00 | 22.42 | 0.00 | 22.42 | 0.00 | 22.42 |
October | 744.00 | 21.68 | 0.00 | 21.68 | 0.00 | 21.68 |
November | 720.00 | 21.17 | 0.00 | 21.17 | 0.00 | 21.17 |
December | 744.00 | 21.01 | 4.50 | 21.01 | 4.50 | 21.01 |
Annual Sum or Average | 8735.50 | 21.79 | 119.50 | 21.78 | 119.50 | 21.77 |
Minimum of Months | 672.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
Maximum of Months | 744.00 | 22.91 | 51.83 | 22.91 | 51.83 | 22.91 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 245.33 | 22.87 | 531.00 | 23.27 | 146.33 | 23.38 |
February | 225.50 | 23.00 | 492.83 | 23.30 | 145.67 | 23.42 |
March | 249.83 | 23.11 | 588.33 | 23.31 | 173.00 | 23.43 |
April | 257.50 | 23.33 | 604.00 | 23.34 | 198.00 | 23.46 |
May | 291.67 | 23.54 | 645.33 | 23.37 | 244.33 | 23.50 |
June | 292.83 | 23.74 | 638.33 | 23.42 | 265.83 | 23.55 |
July | 297.67 | 23.87 | 678.83 | 23.44 | 284.83 | 23.56 |
August | 307.00 | 23.92 | 696.33 | 23.42 | 299.50 | 23.55 |
September | 297.50 | 23.77 | 650.17 | 23.42 | 274.00 | 23.55 |
October | 277.50 | 23.41 | 635.83 | 23.36 | 220.50 | 23.48 |
November | 251.17 | 23.19 | 585.50 | 23.32 | 181.33 | 23.44 |
December | 235.83 | 22.92 | 562.33 | 23.26 | 146.50 | 23.38 |
Annual Sum or Average | 3229.33 | 23.42 | 7308.83 | 23.36 | 2579.83 | 23.48 |
Minimum of Months | 225.50 | 22.87 | 492.83 | 23.26 | 145.67 | 23.38 |
Maximum of Months | 307.00 | 23.92 | 696.33 | 23.44 | 299.50 | 23.56 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 735.00 | 21.41 | 10.50 | 21.42 | 7.17 | 21.42 |
February | 634.67 | 21.66 | 17.50 | 21.72 | 0.00 | 21.72 |
March | 688.00 | 21.91 | 27.33 | 21.99 | 0.00 | 21.99 |
April | 613.67 | 22.10 | 49.50 | 22.21 | 0.00 | 22.21 |
May | 592.33 | 22.21 | 69.83 | 22.35 | 0.00 | 22.35 |
June | 517.17 | 22.30 | 73.67 | 22.44 | 0.00 | 22.44 |
July | 338.50 | 22.33 | 243.00 | 22.81 | 2.17 | 22.81 |
August | 336.17 | 22.35 | 327.83 | 22.99 | 26.50 | 23.02 |
September | 408.17 | 22.16 | 221.83 | 22.70 | 0.33 | 22.70 |
October | 614.33 | 22.05 | 68.33 | 22.22 | 0.00 | 22.22 |
November | 697.50 | 21.63 | 15.17 | 21.67 | 1.33 | 21.67 |
December | 724.50 | 21.49 | 14.33 | 21.50 | 7.00 | 21.50 |
Annual Sum or Average | 6900.00 | 21.90 | 1138.83 | 22.14 | 44.50 | 22.14 |
Minimum of Months | 336.17 | 21.41 | 10.50 | 21.42 | 0.00 | 21.42 |
Maximum of Months | 735.00 | 22.35 | 327.83 | 22.99 | 26.50 | 23.02 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 22.04 | 0.00 | 22.04 | 0.00 | 22.04 |
February | 665.17 | 22.32 | 0.00 | 22.32 | 0.00 | 22.32 |
March | 725.83 | 22.61 | 0.00 | 22.61 | 0.00 | 22.61 |
April | 616.50 | 22.74 | 16.67 | 22.77 | 0.00 | 22.77 |
May | 535.00 | 22.82 | 44.83 | 22.90 | 0.00 | 22.90 |
June | 404.50 | 22.76 | 109.33 | 23.01 | 0.00 | 23.01 |
July | 263.17 | 22.84 | 253.33 | 23.35 | 2.67 | 23.35 |
August | 207.00 | 22.86 | 376.00 | 23.49 | 26.00 | 23.51 |
September | 287.00 | 22.70 | 224.67 | 23.20 | 2.33 | 23.21 |
October | 601.83 | 22.73 | 13.00 | 22.75 | 0.00 | 22.75 |
November | 693.50 | 22.34 | 5.83 | 22.36 | 1.67 | 22.36 |
December | 744.00 | 22.15 | 0.00 | 22.15 | 0.00 | 22.15 |
Annual Sum or Average | 6487.50 | 22.51 | 1043.67 | 22.69 | 32.67 | 22.70 |
Minimum of Months | 207.00 | 22.04 | 0.00 | 22.04 | 0.00 | 22.04 |
Maximum of Months | 744.00 | 22.86 | 376.00 | 23.49 | 26.00 | 23.51 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.80 | 369.50 | 20.69 | 369.50 | 20.63 |
February | 670.50 | 21.06 | 190.17 | 20.96 | 190.17 | 20.90 |
March | 740.67 | 21.27 | 19.17 | 21.25 | 19.17 | 21.23 |
April | 704.33 | 21.46 | 1.00 | 21.46 | 0.67 | 21.46 |
May | 706.17 | 21.53 | 1.33 | 21.54 | 0.00 | 21.54 |
June | 682.83 | 21.58 | 0.83 | 21.58 | 0.00 | 21.58 |
July | 662.67 | 21.50 | 11.17 | 21.53 | 0.00 | 21.53 |
August | 665.00 | 21.51 | 15.17 | 21.55 | 0.00 | 21.55 |
September | 663.00 | 21.46 | 5.33 | 21.48 | 0.00 | 21.48 |
October | 732.33 | 21.35 | 0.00 | 21.35 | 0.00 | 21.35 |
November | 718.00 | 20.99 | 110.33 | 20.89 | 110.33 | 20.81 |
December | 744.00 | 20.87 | 284.50 | 20.73 | 284.50 | 20.65 |
Annual Sum or Average | 8433.50 | 21.27 | 1008.50 | 21.20 | 974.33 | 21.13 |
Minimum of Months | 662.67 | 20.80 | 0.00 | 20.69 | 0.00 | 20.63 |
Maximum of Months | 744.00 | 21.58 | 369.50 | 21.58 | 369.50 | 21.58 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.64 | 477.83 | 20.55 | 477.83 | 20.51 |
February | 672.00 | 20.85 | 297.00 | 20.75 | 297.00 | 20.69 |
March | 743.50 | 21.10 | 59.50 | 21.05 | 59.50 | 21.01 |
April | 702.00 | 21.42 | 7.00 | 21.45 | 1.50 | 21.45 |
May | 664.83 | 21.69 | 54.00 | 22.02 | 9.50 | 22.09 |
June | 623.67 | 21.84 | 56.00 | 22.16 | 4.83 | 22.19 |
July | 584.17 | 22.03 | 112.33 | 22.63 | 24.00 | 22.80 |
August | 621.00 | 21.90 | 56.17 | 22.17 | 5.50 | 22.21 |
September | 611.00 | 21.66 | 58.00 | 21.97 | 3.67 | 22.00 |
October | 739.67 | 21.26 | 2.67 | 21.26 | 0.83 | 21.26 |
November | 720.00 | 20.87 | 181.17 | 20.73 | 181.17 | 20.65 |
December | 744.00 | 20.70 | 413.67 | 20.58 | 413.67 | 20.53 |
Annual Sum or Average | 8169.83 | 21.30 | 1775.33 | 21.31 | 1479.00 | 21.23 |
Minimum of Months | 584.17 | 20.64 | 2.67 | 20.55 | 0.83 | 20.51 |
Maximum of Months | 744.00 | 22.03 | 477.83 | 22.63 | 477.83 | 22.80 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.01 | 81.67 | 20.95 | 81.67 | 20.90 |
February | 672.00 | 21.11 | 54.83 | 21.07 | 54.83 | 21.03 |
March | 744.00 | 21.25 | 0.00 | 21.25 | 0.00 | 21.25 |
April | 720.00 | 21.45 | 0.00 | 21.45 | 0.00 | 21.45 |
May | 743.83 | 21.70 | 0.00 | 21.70 | 0.00 | 21.70 |
June | 719.50 | 21.90 | 0.00 | 21.90 | 0.00 | 21.90 |
July | 732.50 | 22.01 | 0.17 | 22.01 | 0.00 | 22.01 |
August | 743.33 | 21.96 | 0.00 | 21.96 | 0.00 | 21.96 |
September | 720.00 | 21.73 | 0.00 | 21.73 | 0.00 | 21.73 |
October | 744.00 | 21.33 | 0.00 | 21.33 | 0.00 | 21.33 |
November | 720.00 | 21.16 | 12.50 | 21.14 | 12.50 | 21.13 |
December | 744.00 | 21.03 | 52.33 | 20.98 | 52.33 | 20.94 |
Annual Sum or Average | 8747.17 | 21.47 | 201.50 | 21.45 | 201.33 | 21.42 |
Minimum of Months | 672.00 | 21.01 | 0.00 | 20.95 | 0.00 | 20.90 |
Maximum of Months | 744.00 | 22.01 | 81.67 | 22.01 | 81.67 | 22.01 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.78 | 377.33 | 20.68 | 377.33 | 20.63 |
February | 672.00 | 21.08 | 180.83 | 20.99 | 180.83 | 20.93 |
March | 744.00 | 21.33 | 15.00 | 21.32 | 15.00 | 21.30 |
April | 709.33 | 21.55 | 0.50 | 21.55 | 0.50 | 21.55 |
May | 713.33 | 21.57 | 0.00 | 21.57 | 0.00 | 21.57 |
June | 673.67 | 21.59 | 0.00 | 21.59 | 0.00 | 21.59 |
July | 669.33 | 21.54 | 1.00 | 21.54 | 0.00 | 21.54 |
August | 652.83 | 21.49 | 1.83 | 21.50 | 0.00 | 21.50 |
September | 663.33 | 21.46 | 0.00 | 21.46 | 0.00 | 21.46 |
October | 737.50 | 21.39 | 0.00 | 21.39 | 0.00 | 21.39 |
November | 720.00 | 21.00 | 112.67 | 20.89 | 112.67 | 20.81 |
December | 744.00 | 20.85 | 291.50 | 20.72 | 291.50 | 20.65 |
Annual Sum or Average | 8443.33 | 21.30 | 980.67 | 21.21 | 977.83 | 21.14 |
Minimum of Months | 652.83 | 20.78 | 0.00 | 20.68 | 0.00 | 20.63 |
Maximum of Months | 744.00 | 21.59 | 377.33 | 21.59 | 377.33 | 21.59 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.63 | 472.00 | 20.53 | 472.00 | 20.48 |
February | 672.00 | 20.85 | 294.17 | 20.75 | 294.17 | 20.70 |
March | 744.00 | 21.15 | 36.50 | 21.12 | 36.50 | 21.08 |
April | 718.33 | 21.55 | 1.50 | 21.56 | 0.67 | 21.56 |
May | 722.83 | 21.78 | 2.33 | 21.79 | 0.00 | 21.79 |
June | 659.67 | 21.94 | 13.00 | 22.00 | 0.00 | 22.00 |
July | 626.50 | 21.98 | 35.50 | 22.14 | 4.33 | 22.18 |
August | 623.50 | 21.93 | 34.17 | 22.11 | 5.00 | 22.15 |
September | 689.83 | 21.78 | 7.17 | 21.81 | 0.00 | 21.81 |
October | 744.00 | 21.29 | 1.33 | 21.28 | 1.33 | 21.28 |
November | 720.00 | 20.85 | 194.50 | 20.72 | 194.50 | 20.64 |
December | 744.00 | 20.67 | 441.00 | 20.57 | 441.00 | 20.52 |
Annual Sum or Average | 8408.67 | 21.35 | 1533.17 | 21.24 | 1449.50 | 21.14 |
Minimum of Months | 623.50 | 20.63 | 1.33 | 20.53 | 0.00 | 20.48 |
Maximum of Months | 744.00 | 21.98 | 472.00 | 22.14 | 472.00 | 22.18 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.00 | 13.83 | 21.00 | 13.83 | 21.00 |
February | 672.00 | 21.05 | 10.00 | 21.04 | 10.00 | 21.04 |
March | 744.00 | 21.18 | 0.00 | 21.18 | 0.00 | 21.18 |
April | 720.00 | 21.54 | 0.00 | 21.54 | 0.00 | 21.54 |
May | 744.00 | 22.08 | 0.00 | 22.08 | 0.00 | 22.08 |
June | 720.00 | 22.35 | 0.00 | 22.35 | 0.00 | 22.35 |
July | 744.00 | 22.71 | 0.00 | 22.71 | 0.00 | 22.71 |
August | 739.33 | 22.81 | 0.00 | 22.81 | 0.00 | 22.81 |
September | 720.00 | 22.35 | 0.00 | 22.35 | 0.00 | 22.35 |
October | 744.00 | 21.51 | 0.00 | 21.51 | 0.00 | 21.51 |
November | 720.00 | 21.06 | 0.00 | 21.06 | 0.00 | 21.06 |
December | 744.00 | 21.01 | 0.33 | 21.01 | 0.33 | 21.01 |
Annual Sum or Average | 8755.33 | 21.72 | 24.17 | 21.72 | 24.17 | 21.72 |
Minimum of Months | 672.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
Maximum of Months | 744.00 | 22.81 | 13.83 | 22.81 | 13.83 | 22.81 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.67 | 569.33 | 20.61 | 569.33 | 20.59 |
February | 670.00 | 20.95 | 300.33 | 20.84 | 300.33 | 20.78 |
March | 738.33 | 21.19 | 96.00 | 21.11 | 96.00 | 21.04 |
April | 696.17 | 21.41 | 9.00 | 21.41 | 5.67 | 21.40 |
May | 689.67 | 21.47 | 8.67 | 21.49 | 0.00 | 21.49 |
June | 661.00 | 21.51 | 5.00 | 21.52 | 0.00 | 21.52 |
July | 634.83 | 21.42 | 23.50 | 21.49 | 0.00 | 21.49 |
August | 644.67 | 21.44 | 29.67 | 21.52 | 0.17 | 21.52 |
September | 652.33 | 21.40 | 17.50 | 21.45 | 1.67 | 21.45 |
October | 727.83 | 21.27 | 10.50 | 21.26 | 9.83 | 21.24 |
November | 717.50 | 20.89 | 263.83 | 20.78 | 263.83 | 20.72 |
December | 744.00 | 20.76 | 494.33 | 20.67 | 494.33 | 20.63 |
Annual Sum or Average | 8320.33 | 21.19 | 1827.67 | 21.09 | 1741.17 | 21.01 |
Minimum of Months | 634.83 | 20.67 | 5.00 | 20.61 | 0.00 | 20.59 |
Maximum of Months | 744.00 | 21.51 | 569.33 | 21.52 | 569.33 | 21.52 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.54 | 640.67 | 20.50 | 640.67 | 20.48 |
February | 672.00 | 20.74 | 412.67 | 20.65 | 412.67 | 20.61 |
March | 742.00 | 21.01 | 166.83 | 20.92 | 166.83 | 20.86 |
April | 689.67 | 21.35 | 16.17 | 21.38 | 9.00 | 21.38 |
May | 663.67 | 21.78 | 67.67 | 22.21 | 23.83 | 22.39 |
June | 606.33 | 21.89 | 76.00 | 22.33 | 15.33 | 22.45 |
July | 567.00 | 22.15 | 132.33 | 22.88 | 40.50 | 23.18 |
August | 606.17 | 21.89 | 75.17 | 22.26 | 13.17 | 22.35 |
September | 596.67 | 21.63 | 84.00 | 22.10 | 11.33 | 22.18 |
October | 737.83 | 21.17 | 26.00 | 21.15 | 23.33 | 21.11 |
November | 719.67 | 20.76 | 337.50 | 20.65 | 337.50 | 20.59 |
December | 744.00 | 20.59 | 628.83 | 20.55 | 628.83 | 20.54 |
Annual Sum or Average | 8089.00 | 21.25 | 2663.83 | 21.28 | 2323.00 | 21.19 |
Minimum of Months | 567.00 | 20.54 | 16.17 | 20.50 | 9.00 | 20.48 |
Maximum of Months | 744.00 | 22.15 | 640.67 | 22.88 | 640.67 | 23.18 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 737.33 | 21.03 | 209.33 | 20.93 | 209.33 | 20.86 |
February | 649.17 | 21.23 | 106.33 | 21.17 | 106.33 | 21.12 |
March | 717.50 | 21.37 | 9.83 | 21.37 | 7.83 | 21.36 |
April | 677.17 | 21.48 | 2.33 | 21.49 | 0.00 | 21.49 |
May | 688.00 | 21.50 | 1.33 | 21.50 | 0.00 | 21.50 |
June | 664.00 | 21.53 | 0.00 | 21.53 | 0.00 | 21.53 |
July | 649.83 | 21.45 | 0.83 | 21.45 | 0.00 | 21.45 |
August | 655.33 | 21.47 | 24.00 | 21.53 | 0.00 | 21.53 |
September | 645.00 | 21.43 | 32.50 | 21.53 | 0.00 | 21.53 |
October | 692.00 | 21.38 | 7.67 | 21.40 | 0.00 | 21.40 |
November | 707.33 | 21.17 | 41.00 | 21.12 | 38.33 | 21.07 |
December | 732.00 | 21.05 | 161.17 | 20.93 | 161.17 | 20.84 |
Annual Sum or Average | 8214.67 | 21.34 | 596.33 | 21.30 | 523.00 | 21.26 |
Minimum of Months | 645.00 | 21.03 | 0.00 | 20.93 | 0.00 | 20.84 |
Maximum of Months | 737.33 | 21.53 | 209.33 | 21.53 | 209.33 | 21.53 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 385.33 | 23.14 | 26.67 | 23.20 | 0.00 | 23.20 |
February | 288.83 | 23.18 | 97.83 | 23.39 | 0.00 | 23.39 |
March | 208.67 | 23.20 | 129.83 | 23.50 | 0.00 | 23.50 |
April | 85.17 | 23.20 | 270.67 | 23.79 | 0.00 | 23.79 |
May | 6.83 | 23.17 | 561.17 | 23.97 | 0.00 | 23.97 |
June | 0.50 | 23.06 | 651.17 | 23.97 | 0.00 | 23.97 |
July | 2.33 | 23.99 | 730.00 | 23.96 | 2.33 | 23.96 |
August | 26.67 | 23.99 | 741.50 | 23.95 | 26.67 | 23.95 |
September | 12.83 | 23.70 | 646.50 | 23.94 | 8.50 | 23.94 |
October | 130.50 | 23.13 | 354.33 | 23.75 | 0.00 | 23.75 |
November | 244.33 | 23.10 | 182.83 | 23.47 | 2.00 | 23.47 |
December | 340.00 | 23.09 | 30.67 | 23.17 | 0.00 | 23.17 |
Annual Sum or Average | 1732.00 | 23.16 | 4423.17 | 23.74 | 39.50 | 23.74 |
Minimum of Months | 0.50 | 23.06 | 26.67 | 23.17 | 0.00 | 23.17 |
Maximum of Months | 385.33 | 23.99 | 741.50 | 23.97 | 26.67 | 23.97 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 223.50 | 23.21 | 149.50 | 23.52 | 0.00 | 23.52 |
February | 154.00 | 23.28 | 208.67 | 23.68 | 0.00 | 23.68 |
March | 70.83 | 23.32 | 341.50 | 23.87 | 0.00 | 23.87 |
April | 4.83 | 23.27 | 498.33 | 23.98 | 0.00 | 23.98 |
May | 0.00 | 0.00 | 702.67 | 23.98 | 0.00 | 23.98 |
June | 0.00 | 0.00 | 712.00 | 23.98 | 0.00 | 23.98 |
July | 0.00 | 0.00 | 743.00 | 23.99 | 0.00 | 23.99 |
August | 18.33 | 23.99 | 744.00 | 23.98 | 18.33 | 23.98 |
September | 1.83 | 24.00 | 706.67 | 23.96 | 1.83 | 23.96 |
October | 4.33 | 23.25 | 543.17 | 23.98 | 0.00 | 23.98 |
November | 103.83 | 23.20 | 336.17 | 23.80 | 1.17 | 23.80 |
December | 184.33 | 23.17 | 170.17 | 23.57 | 0.00 | 23.57 |
Annual Sum or Average | 765.83 | 23.24 | 5855.83 | 23.90 | 21.33 | 23.90 |
Minimum of Months | 0.00 | 0.00 | 149.50 | 23.52 | 0.00 | 23.52 |
Maximum of Months | 223.50 | 24.00 | 744.00 | 23.99 | 18.33 | 23.99 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 499.83 | 23.96 | 676.17 | 23.92 | 491.00 | 23.94 |
February | 458.83 | 23.97 | 621.17 | 23.92 | 451.83 | 23.94 |
March | 519.00 | 23.99 | 725.17 | 23.91 | 519.00 | 23.94 |
April | 512.33 | 23.99 | 716.50 | 23.92 | 512.33 | 23.94 |
May | 537.00 | 23.99 | 744.00 | 23.93 | 537.00 | 23.95 |
June | 531.67 | 23.99 | 720.00 | 23.95 | 531.67 | 23.96 |
July | 557.00 | 23.99 | 744.00 | 23.96 | 557.00 | 23.97 |
August | 565.17 | 23.99 | 744.00 | 23.97 | 565.17 | 23.97 |
September | 530.17 | 23.99 | 720.00 | 23.95 | 530.17 | 23.96 |
October | 527.67 | 23.99 | 744.00 | 23.92 | 527.67 | 23.94 |
November | 498.83 | 23.99 | 692.33 | 23.92 | 498.83 | 23.94 |
December | 497.33 | 23.99 | 685.00 | 23.92 | 497.17 | 23.94 |
Annual Sum or Average | 6234.83 | 23.99 | 8532.33 | 23.93 | 6218.83 | 23.95 |
Minimum of Months | 458.83 | 23.96 | 621.17 | 23.91 | 451.83 | 23.94 |
Maximum of Months | 565.17 | 23.99 | 744.00 | 23.97 | 565.17 | 23.97 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.00 | 23.00 | 21.00 | 23.00 | 21.00 |
February | 672.00 | 21.07 | 22.50 | 21.07 | 22.50 | 21.07 |
March | 744.00 | 21.24 | 0.00 | 21.24 | 0.00 | 21.24 |
April | 717.83 | 21.65 | 0.00 | 21.65 | 0.00 | 21.65 |
May | 735.33 | 22.14 | 0.00 | 22.14 | 0.00 | 22.14 |
June | 695.17 | 22.49 | 0.00 | 22.49 | 0.00 | 22.49 |
July | 602.50 | 22.73 | 32.50 | 22.79 | 0.00 | 22.79 |
August | 564.67 | 22.69 | 71.17 | 22.83 | 0.00 | 22.83 |
September | 661.50 | 22.25 | 16.67 | 22.29 | 0.00 | 22.29 |
October | 744.00 | 21.49 | 0.00 | 21.49 | 0.00 | 21.49 |
November | 720.00 | 21.09 | 0.00 | 21.09 | 0.00 | 21.09 |
December | 744.00 | 21.02 | 0.00 | 21.02 | 0.00 | 21.02 |
Annual Sum or Average | 8345.00 | 21.70 | 165.83 | 21.73 | 45.50 | 21.72 |
Minimum of Months | 564.67 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
Maximum of Months | 744.00 | 22.73 | 71.17 | 22.83 | 23.00 | 22.83 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.24269 | 32.94383 | 0.09747 | 5.31959 |
February | 672.00000 | 23.06586 | 34.09152 | 0.05984 | 5.22691 |
March | 744.00000 | 22.87548 | 34.80752 | 0.01653 | 5.16977 |
April | 720.00000 | 22.76470 | 38.35291 | 0.01106 | 5.16733 |
May | 744.00000 | 22.84714 | 42.39340 | -0.9671 | 24.94524 |
June | 720.00000 | 23.01157 | 44.92684 | -0.8891 | 21.91839 |
July | 744.00000 | 23.22544 | 48.95740 | -0.7831 | 18.16156 |
August | 744.00000 | 23.40461 | 52.67330 | -0.6923 | 15.27202 |
September | 720.00000 | 23.58798 | 48.62677 | -0.6510 | 14.11057 |
October | 744.00000 | 23.70499 | 39.49527 | 0.26714 | 6.57449 |
November | 720.00000 | 23.72572 | 37.79159 | 0.25991 | 6.50221 |
December | 744.00000 | 23.54299 | 33.81569 | 0.18234 | 5.79689 |
Annual Sum or Average | 8760.00000 | 23.25120 | 40.77585 | -0.2593 | 11.22119 |
Minimum of Months | 672.00000 | 22.76470 | 32.94383 | -0.9671 | 5.16733 |
Maximum of Months | 744.00000 | 23.72572 | 52.67330 | 0.26714 | 24.94524 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.04717 | 35.01496 | -0.4860 | 10.21497 |
February | 672.00000 | 21.17912 | 35.81060 | -0.3944 | 9.12940 |
March | 744.00000 | 21.26476 | 36.15953 | -0.3275 | 8.16325 |
April | 720.00000 | 21.39649 | 39.51773 | -0.2340 | 7.34520 |
May | 744.00000 | 21.48354 | 43.89713 | -1.2749 | 40.55277 |
June | 720.00000 | 21.52742 | 47.00136 | -1.2163 | 37.24238 |
July | 744.00000 | 21.90750 | 50.80971 | -1.0293 | 29.67655 |
August | 744.00000 | 22.04095 | 55.00152 | -0.9496 | 27.17094 |
September | 720.00000 | 21.79166 | 51.92714 | -1.0875 | 33.45715 |
October | 744.00000 | 21.40827 | 43.05752 | -0.2196 | 7.32445 |
November | 720.00000 | 21.09832 | 41.70471 | -0.3858 | 8.71928 |
December | 744.00000 | 21.09590 | 36.59222 | -0.4546 | 9.80498 |
Annual Sum or Average | 8760.00000 | 21.43869 | 43.07873 | -0.6732 | 19.11970 |
Minimum of Months | 672.00000 | 21.04717 | 35.01496 | -1.2749 | 7.32445 |
Maximum of Months | 744.00000 | 22.04095 | 55.00152 | -0.2196 | 40.55277 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.62984 | 36.62558 | -0.2684 | 6.78557 |
February | 672.00000 | 21.91229 | 37.03545 | -0.1891 | 6.21281 |
March | 744.00000 | 22.26306 | 36.94471 | -0.0959 | 5.56571 |
April | 720.00000 | 22.56735 | 39.75960 | 0.00420 | 5.49282 |
May | 744.00000 | 22.84239 | 43.47289 | -0.9088 | 23.11917 |
June | 720.00000 | 22.99107 | 46.04526 | -0.8347 | 20.35171 |
July | 744.00000 | 23.27131 | 49.82839 | -0.7011 | 15.97230 |
August | 744.00000 | 23.31094 | 53.90572 | -0.6581 | 14.75776 |
September | 720.00000 | 23.07760 | 51.03873 | -0.7684 | 18.30290 |
October | 744.00000 | 22.57778 | 43.06032 | 0.02699 | 5.41786 |
November | 720.00000 | 21.99868 | 42.37182 | -0.1335 | 5.82877 |
December | 744.00000 | 21.74699 | 38.04821 | -0.2294 | 6.38409 |
Annual Sum or Average | 8760.00000 | 22.51917 | 43.21073 | -0.3976 | 11.20910 |
Minimum of Months | 672.00000 | 21.62984 | 36.62558 | -0.9088 | 5.41786 |
Maximum of Months | 744.00000 | 23.31094 | 53.90572 | 0.02699 | 23.11917 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.95842 | 29.66178 | 0.60339 | 15.25362 |
February | 672.00000 | 22.99023 | 30.48108 | 0.63080 | 15.98976 |
March | 744.00000 | 23.01348 | 30.85184 | 0.65949 | 16.69801 |
April | 720.00000 | 23.03883 | 34.11992 | 0.70494 | 17.95228 |
May | 744.00000 | 23.04752 | 38.23984 | 0.02448 | 10.09580 |
June | 720.00000 | 23.06193 | 41.10070 | 0.07014 | 10.16980 |
July | 744.00000 | 23.08156 | 45.62210 | 0.11807 | 10.14799 |
August | 744.00000 | 23.08156 | 49.85891 | 0.15466 | 10.39218 |
September | 720.00000 | 23.07365 | 46.31808 | 0.09837 | 10.20114 |
October | 744.00000 | 23.06023 | 37.20534 | 0.72540 | 18.51299 |
November | 720.00000 | 23.01746 | 35.55514 | 0.67819 | 17.25920 |
December | 744.00000 | 22.97334 | 31.09712 | 0.62028 | 15.65262 |
Annual Sum or Average | 8760.00000 | 23.03337 | 37.54775 | 0.42271 | 14.01243 |
Minimum of Months | 672.00000 | 22.95842 | 29.66178 | 0.02448 | 10.09580 |
Maximum of Months | 744.00000 | 23.08156 | 49.85891 | 0.72540 | 18.51299 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.43835 | 39.31669 | -0.2905 | 7.26939 |
February | 672.00000 | 21.76354 | 39.71695 | -0.1642 | 6.68437 |
March | 744.00000 | 22.03884 | 39.83186 | -0.0638 | 6.11845 |
April | 720.00000 | 22.28955 | 42.81879 | 0.04680 | 6.09265 |
May | 744.00000 | 22.43515 | 46.88212 | -0.8853 | 23.15689 |
June | 720.00000 | 22.55923 | 49.61156 | -0.8066 | 19.82757 |
July | 744.00000 | 22.86154 | 53.48393 | -0.6477 | 15.24721 |
August | 744.00000 | 22.96450 | 57.47639 | -0.5728 | 13.94684 |
September | 720.00000 | 22.75437 | 54.40511 | -0.6925 | 18.08089 |
October | 744.00000 | 22.30779 | 46.10423 | 0.06619 | 6.36706 |
November | 720.00000 | 21.68333 | 45.42610 | -0.1570 | 6.44384 |
December | 744.00000 | 21.53833 | 40.81822 | -0.2495 | 6.98403 |
Annual Sum or Average | 8760.00000 | 22.22217 | 46.35956 | -0.3694 | 11.37616 |
Minimum of Months | 672.00000 | 21.43835 | 39.31669 | -0.8853 | 6.09265 |
Maximum of Months | 744.00000 | 22.96450 | 57.47639 | 0.06619 | 23.15689 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.04435 | 38.54332 | -0.1404 | 5.92114 |
February | 672.00000 | 22.33601 | 38.93666 | -0.0539 | 5.69710 |
March | 744.00000 | 22.64109 | 38.96496 | 0.03373 | 5.54719 |
April | 720.00000 | 22.87832 | 41.85826 | 0.12212 | 5.82016 |
May | 744.00000 | 23.07297 | 45.66192 | -0.7722 | 18.30420 |
June | 720.00000 | 23.20063 | 48.22967 | -0.7008 | 16.04074 |
July | 744.00000 | 23.38316 | 52.19258 | -0.5965 | 13.03846 |
August | 744.00000 | 23.43043 | 56.13113 | -0.5484 | 11.88524 |
September | 720.00000 | 23.28480 | 53.12532 | -0.6345 | 14.35161 |
October | 744.00000 | 22.92304 | 44.98153 | 0.15356 | 6.00329 |
November | 720.00000 | 22.38577 | 44.23529 | -0.0063 | 5.67933 |
December | 744.00000 | 22.15151 | 39.95922 | -0.1023 | 5.74003 |
Annual Sum or Average | 8760.00000 | 22.81353 | 45.26892 | -0.2719 | 9.52301 |
Minimum of Months | 672.00000 | 22.04435 | 38.54332 | -0.7722 | 5.54719 |
Maximum of Months | 744.00000 | 23.43043 | 56.13113 | 0.15356 | 18.30420 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.79627 | 48.32192 | -0.5446 | 11.51091 |
February | 672.00000 | 21.06623 | 48.36796 | -0.4421 | 9.74109 |
March | 744.00000 | 21.27618 | 48.29712 | -0.3481 | 8.12232 |
April | 720.00000 | 21.50514 | 49.64707 | -0.2310 | 6.97532 |
May | 744.00000 | 21.62415 | 51.18464 | -1.2697 | 40.01787 |
June | 720.00000 | 21.66798 | 51.66749 | -1.2222 | 37.63047 |
July | 744.00000 | 21.70246 | 51.41641 | -1.1509 | 34.47814 |
August | 744.00000 | 21.69741 | 53.65248 | -1.1484 | 34.34939 |
September | 720.00000 | 21.60924 | 55.08930 | -1.2292 | 38.04771 |
October | 744.00000 | 21.38192 | 53.93312 | -0.2599 | 7.09509 |
November | 720.00000 | 21.00148 | 53.84453 | -0.4272 | 9.31468 |
December | 744.00000 | 20.86527 | 49.69810 | -0.5133 | 10.99417 |
Annual Sum or Average | 8760.00000 | 21.35075 | 51.26951 | -0.7341 | 20.75452 |
Minimum of Months | 672.00000 | 20.79627 | 48.29712 | -1.2697 | 6.97532 |
Maximum of Months | 744.00000 | 21.70246 | 55.08930 | -0.2310 | 40.01787 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.64397 | 48.74846 | -0.5917 | 12.66930 |
February | 672.00000 | 20.85263 | 48.99948 | -0.5128 | 10.98008 |
March | 744.00000 | 21.10033 | 48.81545 | -0.4122 | 8.87680 |
April | 720.00000 | 21.48960 | 49.93264 | -0.2588 | 7.30124 |
May | 744.00000 | 22.02232 | 50.73967 | -1.1788 | 38.00824 |
June | 720.00000 | 22.21950 | 50.56942 | -1.0824 | 33.19017 |
July | 744.00000 | 22.54578 | 50.16792 | -0.9280 | 28.68615 |
August | 744.00000 | 22.26295 | 53.63300 | -1.0108 | 29.61750 |
September | 720.00000 | 22.06982 | 55.42138 | -1.1313 | 35.21202 |
October | 744.00000 | 21.27542 | 54.68990 | -0.3109 | 7.52488 |
November | 720.00000 | 20.86677 | 54.44301 | -0.4720 | 10.06749 |
December | 744.00000 | 20.69565 | 50.18528 | -0.5672 | 12.05400 |
Annual Sum or Average | 8760.00000 | 21.50735 | 51.36808 | -0.7060 | 19.56469 |
Minimum of Months | 672.00000 | 20.64397 | 48.74846 | -1.1788 | 7.30124 |
Maximum of Months | 744.00000 | 22.54578 | 55.42138 | -0.2588 | 38.00824 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.01234 | 45.02492 | -0.4594 | 9.51165 |
February | 672.00000 | 21.10664 | 45.37316 | -0.4226 | 8.92393 |
March | 744.00000 | 21.25260 | 45.33044 | -0.3629 | 7.83909 |
April | 720.00000 | 21.45075 | 46.99155 | -0.2853 | 6.98024 |
May | 744.00000 | 21.69858 | 48.41708 | -1.3372 | 42.76095 |
June | 720.00000 | 21.89961 | 48.44609 | -1.2508 | 38.57474 |
July | 744.00000 | 22.04499 | 50.24406 | -1.1791 | 35.33643 |
August | 744.00000 | 21.96652 | 53.21770 | -1.1923 | 35.74253 |
September | 720.00000 | 21.72598 | 53.49246 | -1.3005 | 40.85307 |
October | 744.00000 | 21.33022 | 50.99498 | -0.2995 | 6.97055 |
November | 720.00000 | 21.15709 | 50.23631 | -0.3712 | 8.02525 |
December | 744.00000 | 21.03065 | 46.49852 | -0.4448 | 9.21125 |
Annual Sum or Average | 8760.00000 | 21.47507 | 48.70411 | -0.7441 | 20.96278 |
Minimum of Months | 672.00000 | 21.01234 | 45.02492 | -1.3372 | 6.97055 |
Maximum of Months | 744.00000 | 22.04499 | 53.49246 | -0.2853 | 42.76095 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.78249 | 48.33350 | -0.5479 | 11.54944 |
February | 672.00000 | 21.07979 | 48.32156 | -0.4398 | 9.63043 |
March | 744.00000 | 21.33292 | 48.08354 | -0.3345 | 7.97228 |
April | 720.00000 | 21.57961 | 48.99231 | -0.2125 | 6.88692 |
May | 744.00000 | 21.64126 | 50.88001 | -1.2793 | 40.47573 |
June | 720.00000 | 21.70290 | 50.73105 | -1.2058 | 36.93066 |
July | 744.00000 | 21.71553 | 51.35689 | -1.1686 | 35.28822 |
August | 744.00000 | 21.71747 | 53.03675 | -1.1457 | 34.26328 |
September | 720.00000 | 21.61188 | 55.19932 | -1.2406 | 38.60030 |
October | 744.00000 | 21.41093 | 53.60217 | -0.2553 | 7.08228 |
November | 720.00000 | 20.99678 | 53.79210 | -0.4282 | 9.30160 |
December | 744.00000 | 20.84863 | 49.73329 | -0.5169 | 11.00369 |
Annual Sum or Average | 8760.00000 | 21.36958 | 51.01441 | -0.7332 | 20.81622 |
Minimum of Months | 672.00000 | 20.78249 | 48.08354 | -1.2793 | 6.88692 |
Maximum of Months | 744.00000 | 21.71747 | 55.19932 | -0.2125 | 40.47573 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.63029 | 48.77063 | -0.5954 | 12.79265 |
February | 672.00000 | 20.84675 | 48.98373 | -0.5145 | 10.93075 |
March | 744.00000 | 21.15074 | 48.60205 | -0.4001 | 8.57896 |
April | 720.00000 | 21.55960 | 49.35872 | -0.2408 | 6.99947 |
May | 744.00000 | 21.84098 | 50.79108 | -1.2461 | 38.98467 |
June | 720.00000 | 22.12090 | 50.01297 | -1.1044 | 32.75560 |
July | 744.00000 | 22.28785 | 50.98026 | -1.0232 | 29.86490 |
August | 744.00000 | 22.25145 | 53.11496 | -1.0164 | 29.61401 |
September | 720.00000 | 21.87122 | 56.13929 | -1.2016 | 36.87027 |
October | 744.00000 | 21.28719 | 54.33151 | -0.3108 | 7.41691 |
November | 720.00000 | 20.85141 | 54.44083 | -0.4750 | 10.10630 |
December | 744.00000 | 20.67402 | 50.22211 | -0.5719 | 12.17674 |
Annual Sum or Average | 8760.00000 | 21.45096 | 51.31860 | -0.7264 | 19.80905 |
Minimum of Months | 672.00000 | 20.63029 | 48.60205 | -1.2461 | 6.99947 |
Maximum of Months | 744.00000 | 22.28785 | 56.13929 | -0.2408 | 38.98467 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.66872 | 49.87038 | -0.6025 | 13.01039 |
February | 672.00000 | 20.96133 | 49.84877 | -0.4897 | 10.83710 |
March | 744.00000 | 21.20439 | 49.71101 | -0.3808 | 8.76963 |
April | 720.00000 | 21.47082 | 50.84021 | -0.2469 | 7.31451 |
May | 744.00000 | 21.60450 | 52.22835 | -1.2826 | 40.91481 |
June | 720.00000 | 21.65757 | 52.58358 | -1.2251 | 38.00401 |
July | 744.00000 | 21.69330 | 52.34170 | -1.1475 | 34.58704 |
August | 744.00000 | 21.68501 | 54.97492 | -1.1490 | 34.61851 |
September | 720.00000 | 21.57884 | 56.83226 | -1.2437 | 38.98461 |
October | 744.00000 | 21.31773 | 55.60464 | -0.2881 | 7.53973 |
November | 720.00000 | 20.89769 | 55.66205 | -0.4715 | 10.29401 |
December | 744.00000 | 20.76249 | 51.26169 | -0.5648 | 12.25382 |
Annual Sum or Average | 8760.00000 | 21.29338 | 52.65502 | -0.7595 | 21.49004 |
Minimum of Months | 672.00000 | 20.66872 | 49.71101 | -1.2826 | 7.31451 |
Maximum of Months | 744.00000 | 21.69330 | 56.83226 | -0.2469 | 40.91481 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.54229 | 50.25582 | -0.6459 | 14.19461 |
February | 672.00000 | 20.74413 | 50.54479 | -0.5630 | 12.25948 |
March | 744.00000 | 21.01930 | 50.29823 | -0.4489 | 9.65713 |
April | 720.00000 | 21.47172 | 51.12129 | -0.2724 | 7.71586 |
May | 744.00000 | 22.08661 | 51.58936 | -1.1631 | 38.78741 |
June | 720.00000 | 22.30116 | 51.10215 | -1.0526 | 33.15850 |
July | 744.00000 | 22.65600 | 50.41636 | -0.8819 | 28.88503 |
August | 744.00000 | 22.29068 | 54.55166 | -0.9961 | 29.82625 |
September | 720.00000 | 22.12370 | 56.80080 | -1.1185 | 35.85051 |
October | 744.00000 | 21.20083 | 56.47985 | -0.3432 | 8.09676 |
November | 720.00000 | 20.75648 | 56.31886 | -0.5186 | 11.18902 |
December | 744.00000 | 20.59329 | 51.79531 | -0.6198 | 13.45752 |
Annual Sum or Average | 8760.00000 | 21.48626 | 52.60968 | -0.7197 | 20.30336 |
Minimum of Months | 672.00000 | 20.54229 | 50.25582 | -1.1631 | 7.71586 |
Maximum of Months | 744.00000 | 22.65600 | 56.80080 | -0.2724 | 38.78741 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.05332 | 48.20491 | -0.4622 | 10.11918 |
February | 672.00000 | 21.29776 | 48.06825 | -0.3554 | 8.70386 |
March | 744.00000 | 21.44202 | 47.98464 | -0.2834 | 7.66236 |
April | 720.00000 | 21.59442 | 49.31854 | -0.2028 | 6.98032 |
May | 744.00000 | 21.63663 | 51.19208 | -1.2911 | 41.25952 |
June | 720.00000 | 21.67137 | 51.74264 | -1.2506 | 39.16228 |
July | 744.00000 | 21.68931 | 52.09413 | -1.2026 | 37.02810 |
August | 744.00000 | 21.68916 | 53.90001 | -1.1789 | 35.94996 |
September | 720.00000 | 21.63058 | 54.45776 | -1.2290 | 38.38805 |
October | 744.00000 | 21.51275 | 52.59759 | -0.2088 | 6.89929 |
November | 720.00000 | 21.21073 | 52.90877 | -0.3585 | 8.43480 |
December | 744.00000 | 21.09139 | 49.47318 | -0.4343 | 9.86835 |
Annual Sum or Average | 8760.00000 | 21.46055 | 51.00708 | -0.7071 | 20.94537 |
Minimum of Months | 672.00000 | 21.05332 | 47.98464 | -1.2911 | 6.89929 |
Maximum of Months | 744.00000 | 21.68931 | 54.45776 | -0.2028 | 41.25952 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.54003 | 38.37685 | 0.24226 | 6.67089 |
February | 672.00000 | 23.61734 | 38.88250 | 0.27690 | 7.05560 |
March | 744.00000 | 23.73376 | 38.81755 | 0.32831 | 7.52803 |
April | 720.00000 | 23.83444 | 41.49543 | 0.39568 | 8.46821 |
May | 744.00000 | 23.90657 | 44.91075 | -0.4111 | 8.70316 |
June | 720.00000 | 23.93325 | 47.32748 | -0.3587 | 7.81083 |
July | 744.00000 | 23.95787 | 51.39058 | -0.3023 | 7.03082 |
August | 744.00000 | 23.94473 | 55.43465 | -0.2811 | 6.74982 |
September | 720.00000 | 23.89542 | 52.59917 | -0.3583 | 7.88519 |
October | 744.00000 | 23.78436 | 44.66721 | 0.39461 | 8.44963 |
November | 720.00000 | 23.65804 | 43.62549 | 0.32915 | 7.65944 |
December | 744.00000 | 23.57177 | 39.74023 | 0.26168 | 6.83478 |
Annual Sum or Average | 8760.00000 | 23.78228 | 44.80441 | 0.04163 | 7.57054 |
Minimum of Months | 672.00000 | 23.54003 | 38.37685 | -0.4111 | 6.67089 |
Maximum of Months | 744.00000 | 23.95787 | 55.43465 | 0.39568 | 8.70316 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.73668 | 37.17943 | 0.33059 | 7.54871 |
February | 672.00000 | 23.79226 | 37.72372 | 0.35951 | 7.98826 |
March | 744.00000 | 23.86775 | 37.71889 | 0.39994 | 8.50023 |
April | 720.00000 | 23.92946 | 40.49760 | 0.45605 | 9.46792 |
May | 744.00000 | 23.96467 | 44.05847 | -0.3399 | 7.51825 |
June | 720.00000 | 23.97698 | 46.57604 | -0.2957 | 6.90118 |
July | 744.00000 | 23.98594 | 50.72452 | -0.2480 | 6.38529 |
August | 744.00000 | 23.98007 | 54.75175 | -0.2249 | 6.12652 |
September | 720.00000 | 23.95479 | 51.75808 | -0.2893 | 6.87005 |
October | 744.00000 | 23.89417 | 43.60285 | 0.45888 | 9.50719 |
November | 720.00000 | 23.81612 | 42.43373 | 0.40773 | 8.71705 |
December | 744.00000 | 23.75704 | 38.51822 | 0.34731 | 7.75775 |
Annual Sum or Average | 8760.00000 | 23.88844 | 43.82851 | 0.11198 | 7.76992 |
Minimum of Months | 672.00000 | 23.73668 | 37.17943 | -0.3399 | 6.12652 |
Maximum of Months | 744.00000 | 23.98594 | 54.75175 | 0.45888 | 9.50719 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.77940 | 35.56519 | 0.95820 | 26.49878 |
February | 672.00000 | 23.79580 | 36.18374 | 0.98914 | 27.82027 |
March | 744.00000 | 23.83658 | 36.40091 | 1.03190 | 29.35986 |
April | 720.00000 | 23.86733 | 39.36040 | 1.09599 | 32.21725 |
May | 744.00000 | 23.89380 | 43.14740 | 0.57855 | 16.55779 |
June | 720.00000 | 23.92354 | 45.73706 | 0.64362 | 17.91770 |
July | 744.00000 | 23.93977 | 49.93568 | 0.69746 | 19.49293 |
August | 744.00000 | 23.94717 | 53.77770 | 0.72968 | 20.26482 |
September | 720.00000 | 23.91963 | 50.60708 | 0.64722 | 17.98962 |
October | 744.00000 | 23.86863 | 42.28509 | 1.09601 | 32.05763 |
November | 720.00000 | 23.82486 | 40.91337 | 1.03487 | 29.54745 |
December | 744.00000 | 23.78813 | 36.88328 | 0.97431 | 27.09472 |
Annual Sum or Average | 8760.00000 | 23.86576 | 42.60146 | 0.87232 | 24.71301 |
Minimum of Months | 672.00000 | 23.77940 | 35.56519 | 0.57855 | 16.55779 |
Maximum of Months | 744.00000 | 23.94717 | 53.77770 | 1.09601 | 32.21725 |
Report: OccupantComfortDataSummaryMonthly
For: STORAGE_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.00451 | 34.53376 | -0.4714 | 9.67927 |
February | 672.00000 | 21.06535 | 35.42810 | -0.4402 | 9.18855 |
March | 744.00000 | 21.19416 | 35.68449 | -0.3908 | 8.29731 |
April | 720.00000 | 21.58389 | 38.49154 | -0.2749 | 6.88910 |
May | 744.00000 | 22.10412 | 41.83539 | -1.2192 | 36.44847 |
June | 720.00000 | 22.46130 | 44.04654 | -1.0798 | 29.83164 |
July | 744.00000 | 22.83089 | 47.73136 | -0.9254 | 23.37047 |
August | 744.00000 | 22.92799 | 51.80719 | -0.8652 | 21.12018 |
September | 720.00000 | 22.42482 | 49.59959 | -1.0573 | 28.97177 |
October | 744.00000 | 21.68047 | 41.89870 | -0.2302 | 6.32283 |
November | 720.00000 | 21.16738 | 40.99928 | -0.3739 | 8.14842 |
December | 744.00000 | 21.00720 | 36.18316 | -0.4556 | 9.35924 |
Annual Sum or Average | 8760.00000 | 21.79228 | 41.55066 | -0.6499 | 16.50695 |
Minimum of Months | 672.00000 | 21.00451 | 34.53376 | -1.2192 | 6.32283 |
Maximum of Months | 744.00000 | 22.92799 | 51.80719 | -0.2302 | 36.44847 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.00284 | 37.56582 | -0.4610 | 9.46498 |
February | 672.00000 | 21.04500 | 38.48075 | -0.4343 | 9.02174 |
March | 744.00000 | 21.18482 | 38.73267 | -0.3874 | 8.20291 |
April | 720.00000 | 21.54333 | 41.58990 | -0.2774 | 6.88938 |
May | 744.00000 | 22.08004 | 44.93655 | -1.2236 | 36.61879 |
June | 720.00000 | 22.35279 | 47.36419 | -1.1117 | 31.25975 |
July | 744.00000 | 22.71123 | 51.12900 | -0.9601 | 24.78015 |
August | 744.00000 | 22.81508 | 55.23530 | -0.8971 | 22.30088 |
September | 720.00000 | 22.35001 | 52.82646 | -1.0775 | 30.03509 |
October | 744.00000 | 21.50762 | 45.25560 | -0.2658 | 6.73799 |
November | 720.00000 | 21.05685 | 44.25685 | -0.3974 | 8.39896 |
December | 744.00000 | 21.00835 | 39.20138 | -0.4480 | 9.21168 |
Annual Sum or Average | 8760.00000 | 21.72592 | 44.74611 | -0.6630 | 16.95053 |
Minimum of Months | 672.00000 | 21.00284 | 37.56582 | -1.2236 | 6.73799 |
Maximum of Months | 744.00000 | 22.81508 | 55.23530 | -0.2658 | 36.61879 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.00381 | 35.42398 | -0.4547 | 9.35082 |
February | 672.00000 | 21.07480 | 36.26979 | -0.4163 | 8.77209 |
March | 744.00000 | 21.23949 | 36.47529 | -0.3552 | 7.77457 |
April | 720.00000 | 21.65373 | 39.18475 | -0.2260 | 6.54851 |
May | 744.00000 | 22.15813 | 42.51704 | -1.1490 | 33.42985 |
June | 720.00000 | 22.53078 | 44.67522 | -0.9993 | 26.64867 |
July | 744.00000 | 22.89467 | 48.34275 | -0.8423 | 20.73574 |
August | 744.00000 | 22.92728 | 52.58840 | -0.8032 | 19.45151 |
September | 720.00000 | 22.36012 | 50.54905 | -1.0246 | 28.18234 |
October | 744.00000 | 21.49184 | 43.10105 | -0.2460 | 6.58354 |
November | 720.00000 | 21.08757 | 42.01464 | -0.3750 | 8.12535 |
December | 744.00000 | 21.01529 | 37.05031 | -0.4391 | 9.05493 |
Annual Sum or Average | 8760.00000 | 21.79097 | 42.38008 | -0.6120 | 15.42075 |
Minimum of Months | 672.00000 | 21.00381 | 35.42398 | -1.1490 | 6.54851 |
Maximum of Months | 744.00000 | 22.92728 | 52.58840 | -0.2260 | 33.42985 |
Report: OccupantComfortDataSummaryMonthly
For: MECH_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.06476 | 34.02497 | -0.4492 | 9.27384 |
February | 672.00000 | 21.19209 | 34.76497 | -0.4069 | 8.67150 |
March | 744.00000 | 21.48529 | 34.71348 | -0.3269 | 7.38528 |
April | 720.00000 | 21.89766 | 37.42342 | -0.2077 | 6.22362 |
May | 744.00000 | 22.41206 | 40.71774 | -1.1250 | 31.99903 |
June | 720.00000 | 22.75009 | 42.92619 | -0.9913 | 26.06110 |
July | 744.00000 | 23.11117 | 46.57135 | -0.8390 | 20.19235 |
August | 744.00000 | 23.20881 | 50.57200 | -0.7785 | 18.12779 |
September | 720.00000 | 22.73586 | 48.32640 | -0.9616 | 24.96557 |
October | 744.00000 | 22.02178 | 40.70433 | -0.1565 | 5.73776 |
November | 720.00000 | 21.37508 | 40.11030 | -0.3247 | 7.52241 |
December | 744.00000 | 21.09077 | 35.63587 | -0.4294 | 8.89099 |
Annual Sum or Average | 8760.00000 | 22.03390 | 40.57025 | -0.5841 | 14.61863 |
Minimum of Months | 672.00000 | 21.06476 | 34.02497 | -1.1250 | 5.73776 |
Maximum of Months | 744.00000 | 23.20881 | 50.57200 | -0.1565 | 31.99903 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.638853E+09 | 7287.92 | 11-JAN-19:03 | 159.36 | 0.301303E+10 | 0.00 | 0.365188E+10 | 1.01 | 4.72 | 01-JAN-19:02 | 0.00 | 0.00 |
February | 0.296017E+10 | 49318.38 | 27-FEB-16:03 | 284.24 | 0.137947E+11 | 0.00 | 0.167549E+11 | 1.99 | 4.72 | 01-FEB-06:08 | 0.00 | 0.00 |
March | 0.715482E+10 | 59775.06 | 18-MAR-15:01 | 508.55 | 0.333749E+11 | 0.00 | 0.405297E+11 | 3.22 | 4.72 | 01-MAR-01:10 | 0.00 | 0.00 |
April | 0.188866E+11 | 99116.90 | 27-APR-18:03 | 660.85 | 0.841844E+11 | 0.00 | 0.103071E+12 | 4.28 | 4.72 | 01-APR-06:05 | 0.00 | 0.00 |
May | 0.304821E+11 | 86909.36 | 04-MAY-15:03 | 734.68 | 0.135987E+12 | 0.00 | 0.166469E+12 | 4.57 | 4.72 | 01-MAY-02:40 | 0.00 | 0.00 |
June | 0.445722E+11 | 99608.13 | 28-JUN-18:03 | 719.39 | 0.196308E+12 | 0.00 | 0.240880E+12 | 4.55 | 4.72 | 01-JUN-05:50 | 0.00 | 0.00 |
July | 0.692126E+11 | 123540.98 | 24-JUL-18:03 | 744.00 | 0.296681E+12 | 0.00 | 0.365893E+12 | 4.46 | 4.72 | 02-JUL-03:05 | 0.00 | 0.00 |
August | 0.836526E+11 | 143742.81 | 10-AUG-18:03 | 744.00 | 0.350563E+12 | 0.00 | 0.434215E+12 | 4.39 | 4.72 | 01-AUG-03:20 | 0.00 | 0.00 |
September | 0.402850E+11 | 96231.89 | 14-SEP-15:03 | 712.08 | 0.178598E+12 | 0.00 | 0.218883E+12 | 4.53 | 4.72 | 02-SEP-06:30 | 0.00 | 0.00 |
October | 0.138221E+11 | 71743.49 | 04-OCT-15:03 | 638.89 | 0.635698E+11 | 0.00 | 0.773918E+11 | 4.02 | 4.72 | 01-OCT-22:10 | 0.00 | 0.00 |
November | 0.374244E+10 | 68779.82 | 04-NOV-15:03 | 336.78 | 0.172429E+11 | 0.00 | 0.209853E+11 | 2.20 | 4.72 | 01-NOV-03:40 | 0.00 | 0.00 |
December | 0.117132E+10 | 9716.22 | 02-DEC-09:02 | 193.72 | 0.552444E+10 | 0.00 | 0.669576E+10 | 1.23 | 4.72 | 01-DEC-14:00 | 0.00 | 0.00 |
Annual Sum or Average | 0.316581E+12 | 6436.54 | 0.137884E+13 | 0.00 | 0.169542E+13 | 3.38 | 0.00 | 0.00 | ||||
Minimum of Months | 0.638853E+09 | 7287.92 | 159.36 | 0.301303E+10 | 0.00 | 0.365188E+10 | 1.01 | 4.72 | 0.00 | 0.00 | ||
Maximum of Months | 0.836526E+11 | 143742.81 | 744.00 | 0.350563E+12 | 0.00 | 0.434215E+12 | 4.57 | 4.72 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.896645E+11 | 0.00 | 744.00 | 163121.08 | 02-JAN-16:02 | 0.00 | 39.08 | 60.00 | 0.36 | 0.00 | 0.09 | 0.43 | 02-JAN-16:02 |
February | 0.855076E+11 | 0.00 | 663.30 | 158030.82 | 22-FEB-09:04 | 0.00 | 37.91 | 59.58 | 0.36 | 0.00 | 0.09 | 0.42 | 22-FEB-09:04 |
March | 0.981709E+11 | 0.00 | 723.71 | 144112.30 | 15-MAR-08:07 | 0.00 | 36.72 | 59.06 | 0.34 | 0.00 | 0.10 | 0.38 | 15-MAR-08:07 |
April | 0.950044E+11 | 0.00 | 605.01 | 129681.18 | 18-APR-15:04 | 0.00 | 32.61 | 54.63 | 0.32 | 0.00 | 0.10 | 0.35 | 18-APR-15:04 |
May | 0.850980E+11 | 0.00 | 515.35 | 120978.54 | 28-MAY-08:03 | 0.00 | 29.07 | 49.40 | 0.27 | 0.00 | 0.08 | 0.32 | 28-MAY-08:03 |
June | 0.434233E+11 | 0.00 | 361.22 | 100869.71 | 15-JUN-04:00 | 0.00 | 25.82 | 42.59 | 0.13 | 0.00 | 0.04 | 0.27 | 15-JUN-04:00 |
July | 0.162345E+11 | 0.00 | 236.04 | 58593.92 | 19-JUL-05:00 | 0.00 | 25.16 | 36.26 | 0.04 | 0.00 | 0.02 | 0.16 | 19-JUL-05:00 |
August | 0.124870E+11 | 0.00 | 190.94 | 65555.32 | 01-AUG-08:04 | 0.00 | 27.29 | 36.08 | 0.03 | 0.00 | 0.01 | 0.17 | 01-AUG-08:04 |
September | 0.455968E+11 | 0.00 | 410.15 | 106483.59 | 28-SEP-08:04 | 0.00 | 26.64 | 45.50 | 0.14 | 0.00 | 0.05 | 0.28 | 28-SEP-08:04 |
October | 0.119684E+12 | 0.00 | 646.84 | 153595.98 | 30-OCT-08:05 | 0.00 | 31.28 | 55.71 | 0.39 | 0.00 | 0.12 | 0.41 | 30-OCT-08:05 |
November | 0.100789E+12 | 0.00 | 705.96 | 168464.52 | 17-NOV-09:04 | 0.00 | 36.21 | 59.44 | 0.37 | 0.00 | 0.10 | 0.45 | 17-NOV-09:04 |
December | 0.932875E+11 | 0.00 | 744.00 | 167650.85 | 16-DEC-19:04 | 0.00 | 38.59 | 60.00 | 0.37 | 0.00 | 0.09 | 0.45 | 16-DEC-19:04 |
Annual Sum or Average | 0.884948E+12 | 0.00 | 6546.53 | 0.00 | 32.17 | 51.47 | 0.26 | 0.00 | 0.07 | ||||
Minimum of Months | 0.124870E+11 | 0.00 | 190.94 | 58593.92 | 0.00 | 25.16 | 36.08 | 0.03 | 0.00 | 0.01 | 0.16 | ||
Maximum of Months | 0.119684E+12 | 0.00 | 744.00 | 168464.52 | 0.00 | 39.08 | 60.00 | 0.39 | 0.00 | 0.12 | 0.45 |
Report: DXReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 |
February | 0.108438E+09 | 0.00 | 5.00 | 0.108438E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9635.08 | 27-FEB-16:09 | 9635.08 | 27-FEB-16:09 | 0.00 | 0.00 | 0.00 |
March | 0.232884E+09 | 0.00 | 18.50 | 0.232884E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12388.66 | 18-MAR-16:00 | 12388.66 | 18-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.179842E+10 | 0.00 | 73.00 | 0.179842E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18212.60 | 27-APR-15:02 | 18212.60 | 27-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.355559E+10 | 0.00 | 145.50 | 0.343568E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20677.56 | 05-MAY-18:03 | 17245.92 | 05-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.630895E+10 | 0.00 | 267.83 | 0.630895E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17791.40 | 28-JUN-15:02 | 17791.40 | 28-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.116585E+11 | 0.00 | 399.17 | 0.109079E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 23708.15 | 15-JUL-18:03 | 19376.32 | 24-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.152262E+11 | 0.00 | 453.17 | 0.141063E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 24768.28 | 30-AUG-12:40 | 19655.88 | 29-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.544189E+10 | 0.00 | 235.33 | 0.511333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22992.79 | 14-SEP-12:50 | 17201.20 | 12-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.903800E+09 | 0.00 | 70.67 | 0.903800E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14148.91 | 04-OCT-15:01 | 14148.91 | 04-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.218215E+09 | 0.00 | 15.50 | 0.196313E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15659.16 | 04-NOV-15:01 | 13199.77 | 04-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.454529E+11 | 0.00 | 1683.67 | 0.431120E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.152262E+11 | 0.00 | 453.17 | 0.141063E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 24768.28 | 19655.88 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 |
February | 0.177965E+10 | 0.00 | 10.83 | 0.177965E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78982.59 | 27-FEB-15:00 | 78982.59 | 27-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.394681E+10 | 0.00 | 33.33 | 0.394681E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 104148.08 | 18-MAR-16:10 | 104148.08 | 18-MAR-16:10 | 0.00 | 0.00 | 0.00 |
April | 0.284700E+11 | 0.00 | 121.33 | 0.284700E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 204755.85 | 27-APR-18:10 | 204755.85 | 27-APR-18:10 | 0.00 | 0.00 | 0.00 |
May | 0.551595E+11 | 0.00 | 242.23 | 0.548024E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 206707.51 | 05-MAY-18:00 | 176797.98 | 04-MAY-18:03 | 0.00 | 0.00 | 0.00 |
June | 0.986138E+11 | 0.00 | 390.00 | 0.985076E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 209018.02 | 28-JUN-18:10 | 209018.02 | 28-JUN-18:10 | 0.00 | 0.00 | 0.00 |
July | 0.166404E+12 | 0.00 | 537.50 | 0.161479E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 264497.45 | 27-JUL-18:03 | 235021.89 | 24-JUL-18:10 | 0.00 | 0.00 | 0.00 |
August | 0.209638E+12 | 0.00 | 589.83 | 0.201849E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 286685.50 | 10-AUG-18:10 | 249248.48 | 10-AUG-18:50 | 0.00 | 0.00 | 0.00 |
September | 0.803282E+11 | 0.00 | 342.83 | 0.784403E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 198570.87 | 14-SEP-17:15 | 180590.89 | 14-SEP-17:04 | 0.00 | 0.00 | 0.00 |
October | 0.149889E+11 | 0.00 | 120.00 | 0.149718E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 124339.99 | 04-OCT-15:15 | 124339.99 | 04-OCT-15:15 | 0.00 | 0.00 | 0.00 |
November | 0.341840E+10 | 0.00 | 26.00 | 0.341840E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 102902.96 | 04-NOV-14:30 | 102902.96 | 04-NOV-14:30 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.662748E+12 | 0.00 | 2413.90 | 0.647665E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.209638E+12 | 0.00 | 589.83 | 0.201849E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 286685.50 | 249248.48 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 10367649.58 | 0.00 | 2.16 | 6049164.85 | 0.00 | 0.00 | 0.00 | 0.00 | 12746.79 | 05-JAN-16:01 | 12746.79 | 05-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.220335E+09 | 0.00 | 56.06 | 0.104331E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16838.06 | 12-FEB-16:01 | 16838.06 | 12-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.784666E+09 | 0.00 | 155.67 | 0.485889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16838.93 | 28-MAR-15:01 | 16838.93 | 28-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.228306E+10 | 0.00 | 354.28 | 0.125430E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16833.78 | 13-APR-18:01 | 16833.78 | 13-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.426025E+10 | 0.00 | 539.17 | 0.233314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16840.09 | 20-MAY-18:01 | 16840.09 | 20-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.502958E+10 | 0.00 | 608.42 | 0.254741E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16995.33 | 12-JUN-15:01 | 15353.49 | 24-JUN-08:61 | 0.00 | 0.00 | 0.00 |
July | 0.783209E+10 | 0.00 | 679.68 | 0.437955E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16525.47 | 16-JUL-15:01 | 15453.84 | 25-JUL-08:61 | 0.00 | 0.00 | 0.00 |
August | 0.764520E+10 | 0.00 | 672.54 | 0.419540E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17228.09 | 30-AUG-08:62 | 15246.36 | 16-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.511176E+10 | 0.00 | 568.63 | 0.261404E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16527.19 | 23-SEP-08:61 | 15333.88 | 06-SEP-15:01 | 0.00 | 0.00 | 0.00 |
October | 0.149068E+10 | 0.00 | 283.68 | 0.699597E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16839.66 | 03-OCT-18:01 | 16839.66 | 03-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.173443E+09 | 0.00 | 47.42 | 66535432.22 | 0.00 | 0.00 | 0.00 | 0.00 | 17054.25 | 05-NOV-15:01 | 14601.79 | 04-NOV-18:01 | 0.00 | 0.00 | 0.00 |
December | 24451951.66 | 0.00 | 10.59 | 13301003.62 | 0.00 | 0.00 | 0.00 | 0.00 | 14991.55 | 10-DEC-16:01 | 14329.93 | 10-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.348659E+11 | 0.00 | 3978.29 | 0.186996E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 10367649.58 | 0.00 | 2.16 | 6049164.85 | 0.00 | 0.00 | 0.00 | 0.00 | 12746.79 | 12746.79 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.783209E+10 | 0.00 | 679.68 | 0.437955E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17228.09 | 16840.09 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 1356388.22 | 0.00 | 0.65 | 251363.27 | 0.00 | 0.00 | 0.00 | 0.00 | 1421.33 | 20-JAN-16:03 | 444.61 | 20-JAN-16:03 | 0.00 | 0.00 | 0.00 |
February | 47358347.19 | 0.00 | 16.09 | 20279881.12 | 0.00 | 0.00 | 0.00 | 0.00 | 14008.45 | 12-FEB-16:01 | 14008.45 | 12-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.257554E+09 | 0.00 | 68.74 | 0.146797E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15102.86 | 25-MAR-15:01 | 15102.86 | 25-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.125531E+10 | 0.00 | 240.46 | 0.635699E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17674.76 | 25-APR-17:41 | 17674.76 | 25-APR-17:41 | 0.00 | 0.00 | 0.00 |
May | 0.255917E+10 | 0.00 | 419.77 | 0.118639E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15667.62 | 08-MAY-20:01 | 14890.85 | 29-MAY-19:41 | 0.00 | 0.00 | 0.00 |
June | 0.334869E+10 | 0.00 | 453.52 | 0.157633E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16133.74 | 22-JUN-21:51 | 14966.44 | 18-JUN-20:11 | 0.00 | 0.00 | 0.00 |
July | 0.526460E+10 | 0.00 | 501.26 | 0.283200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17448.54 | 15-JUL-21:51 | 15405.46 | 25-JUL-16:51 | 0.00 | 0.00 | 0.00 |
August | 0.515946E+10 | 0.00 | 491.78 | 0.278664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16059.82 | 26-AUG-21:51 | 15170.31 | 02-AUG-18:11 | 0.00 | 0.00 | 0.00 |
September | 0.256435E+10 | 0.00 | 403.50 | 0.102994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16037.85 | 24-SEP-18:11 | 14948.38 | 22-SEP-16:11 | 0.00 | 0.00 | 0.00 |
October | 0.501741E+09 | 0.00 | 157.13 | 0.183897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15584.61 | 01-OCT-15:01 | 14039.66 | 06-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 37433914.07 | 0.00 | 13.99 | 12256786.94 | 0.00 | 0.00 | 0.00 | 0.00 | 15313.45 | 05-NOV-15:01 | 12777.90 | 04-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 2600525.61 | 0.00 | 0.86 | 912733.46 | 0.00 | 0.00 | 0.00 | 0.00 | 4251.77 | 10-DEC-16:01 | 3184.94 | 02-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209996E+11 | 0.00 | 2767.76 | 0.104114E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1356388.22 | 0.00 | 0.65 | 251363.27 | 0.00 | 0.00 | 0.00 | 0.00 | 1421.33 | 444.61 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.526460E+10 | 0.00 | 501.26 | 0.283200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17674.76 | 17674.76 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 |
February | 0.398136E+10 | 0.00 | 96.44 | 0.345728E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37380.75 | 08-FEB-13:40 | 37380.75 | 08-FEB-13:40 | 0.00 | 0.00 | 0.00 |
March | 0.119107E+11 | 0.00 | 274.68 | 0.843996E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47719.56 | 02-MAR-13:00 | 41340.91 | 02-MAR-13:00 | 0.00 | 0.00 | 0.00 |
April | 0.193943E+11 | 0.00 | 479.09 | 0.909172E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43942.81 | 27-APR-13:00 | 31555.47 | 27-APR-13:05 | 0.00 | 0.00 | 0.00 |
May | 0.246056E+11 | 0.00 | 566.96 | 0.854564E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43083.26 | 04-MAY-13:00 | 29645.07 | 04-MAY-13:15 | 0.00 | 0.00 | 0.00 |
June | 0.272618E+11 | 0.00 | 627.10 | 0.873149E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32629.85 | 28-JUN-13:00 | 17352.10 | 28-JUN-13:05 | 0.00 | 0.00 | 0.00 |
July | 0.377326E+11 | 0.00 | 716.26 | 0.136682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 41194.86 | 31-JUL-12:50 | 26469.83 | 31-JUL-13:05 | 0.00 | 0.00 | 0.00 |
August | 0.428340E+11 | 0.00 | 707.19 | 0.177077E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 51050.96 | 24-AUG-13:00 | 40492.40 | 24-AUG-13:00 | 0.00 | 0.00 | 0.00 |
September | 0.363342E+11 | 0.00 | 632.23 | 0.165338E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 54044.42 | 14-SEP-13:15 | 46102.34 | 14-SEP-13:30 | 0.00 | 0.00 | 0.00 |
October | 0.209240E+11 | 0.00 | 444.83 | 0.923041E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54983.46 | 04-OCT-12:40 | 50437.90 | 04-OCT-12:40 | 0.00 | 0.00 | 0.00 |
November | 0.357538E+10 | 0.00 | 105.23 | 0.131882E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44767.79 | 04-NOV-13:25 | 30918.43 | 04-NOV-13:25 | 0.00 | 0.00 | 0.00 |
December | 0.174235E+10 | 0.00 | 46.38 | 0.163441E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33996.75 | 05-DEC-12:30 | 33996.75 | 05-DEC-12:30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230296E+12 | 0.00 | 4696.40 | 0.983594E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.428340E+11 | 0.00 | 716.26 | 0.177077E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 54983.46 | 50437.90 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.127853E+10 | 0.00 | 102.79 | 0.414090E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 63145.74 | 01-JAN-09:02 | 63145.74 | 01-JAN-09:02 | 0.00 | 0.00 | 0.00 |
February | 0.336465E+10 | 0.00 | 161.59 | 0.126126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76049.44 | 25-FEB-09:02 | 70591.02 | 26-FEB-09:02 | 0.00 | 0.00 | 0.00 |
March | 0.797714E+10 | 0.00 | 333.27 | 0.395410E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76739.66 | 18-MAR-20:42 | 76739.66 | 18-MAR-20:42 | 0.00 | 0.00 | 0.00 |
April | 0.164513E+11 | 0.00 | 437.14 | 0.886768E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78093.30 | 20-APR-18:01 | 78093.30 | 20-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.261891E+11 | 0.00 | 462.54 | 0.154526E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 81551.40 | 06-MAY-21:51 | 81217.16 | 14-MAY-21:51 | 0.00 | 0.00 | 0.00 |
June | 0.318460E+11 | 0.00 | 422.08 | 0.199549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 80341.17 | 12-JUN-18:01 | 75063.48 | 11-JUN-21:31 | 0.00 | 0.00 | 0.00 |
July | 0.373715E+11 | 0.00 | 432.08 | 0.239237E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 85347.82 | 26-JUL-21:51 | 75447.95 | 28-JUL-21:51 | 0.00 | 0.00 | 0.00 |
August | 0.374883E+11 | 0.00 | 428.70 | 0.223534E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 85952.31 | 26-AUG-21:51 | 74794.77 | 01-AUG-20:41 | 0.00 | 0.00 | 0.00 |
September | 0.255177E+11 | 0.00 | 401.77 | 0.131501E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 82815.27 | 15-SEP-21:51 | 74164.88 | 02-SEP-15:01 | 0.00 | 0.00 | 0.00 |
October | 0.125895E+11 | 0.00 | 437.93 | 0.533314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80385.17 | 01-OCT-15:01 | 77582.05 | 02-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.565920E+10 | 0.00 | 254.20 | 0.198128E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76211.58 | 04-NOV-15:01 | 69519.29 | 05-NOV-18:42 | 0.00 | 0.00 | 0.00 |
December | 0.119099E+10 | 0.00 | 110.92 | 0.461661E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 74807.91 | 03-DEC-09:02 | 74807.91 | 03-DEC-09:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.206924E+12 | 0.00 | 3985.00 | 0.117108E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.119099E+10 | 0.00 | 102.79 | 0.414090E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 63145.74 | 63145.74 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.374883E+11 | 0.00 | 462.54 | 0.239237E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 85952.31 | 81217.16 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 6761682.63 | 0.00 | 4.39 | 1184824.20 | 0.00 | 0.00 | 0.00 | 0.00 | 1572.81 | 20-JAN-16:02 | 523.43 | 20-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 0.198050E+09 | 0.00 | 47.73 | 85848414.78 | 0.00 | 0.00 | 0.00 | 0.00 | 14498.98 | 12-FEB-16:01 | 14498.98 | 12-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.751570E+09 | 0.00 | 172.28 | 0.441640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15212.93 | 28-MAR-15:01 | 15212.93 | 28-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.236585E+10 | 0.00 | 386.37 | 0.121383E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15022.04 | 30-APR-15:01 | 14826.17 | 13-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.370808E+10 | 0.00 | 530.63 | 0.185995E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15211.59 | 14-MAY-18:01 | 15211.59 | 14-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.535543E+10 | 0.00 | 633.46 | 0.276254E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14704.87 | 12-JUN-15:01 | 13888.10 | 18-JUN-08:62 | 0.00 | 0.00 | 0.00 |
July | 0.683111E+10 | 0.00 | 693.08 | 0.360811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15530.27 | 16-JUL-15:01 | 13892.49 | 25-JUL-08:61 | 0.00 | 0.00 | 0.00 |
August | 0.755454E+10 | 0.00 | 690.69 | 0.412684E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15640.78 | 30-AUG-08:62 | 13737.05 | 25-AUG-08:61 | 0.00 | 0.00 | 0.00 |
September | 0.461389E+10 | 0.00 | 564.63 | 0.232205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15480.96 | 24-SEP-15:01 | 13882.77 | 06-SEP-15:01 | 0.00 | 0.00 | 0.00 |
October | 0.147376E+10 | 0.00 | 299.98 | 0.676987E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15958.36 | 01-OCT-15:01 | 14663.00 | 03-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.183456E+09 | 0.00 | 51.90 | 57312453.87 | 0.00 | 0.00 | 0.00 | 0.00 | 15264.12 | 05-NOV-15:01 | 13837.43 | 04-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 55759226.55 | 0.00 | 14.45 | 20551316.70 | 0.00 | 0.00 | 0.00 | 0.00 | 11053.03 | 02-DEC-09:02 | 10740.82 | 02-DEC-09:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.330983E+11 | 0.00 | 4089.58 | 0.171769E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 6761682.63 | 0.00 | 4.39 | 1184824.20 | 0.00 | 0.00 | 0.00 | 0.00 | 1572.81 | 523.43 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.755454E+10 | 0.00 | 693.08 | 0.412684E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15958.36 | 15212.93 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 1167286.50 | 0.00 | 0.51 | 218781.49 | 0.00 | 0.00 | 0.00 | 0.00 | 1156.48 | 27-JAN-19:06 | 267.81 | 27-JAN-19:06 | 0.00 | 0.00 | 0.00 |
February | 26962366.04 | 0.00 | 16.72 | 9705940.86 | 0.00 | 0.00 | 0.00 | 0.00 | 11063.55 | 27-FEB-16:01 | 11063.55 | 27-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.206922E+09 | 0.00 | 66.78 | 0.117763E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13905.82 | 25-MAR-08:61 | 13905.82 | 25-MAR-08:61 | 0.00 | 0.00 | 0.00 |
April | 0.135549E+10 | 0.00 | 270.87 | 0.663145E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13837.86 | 25-APR-18:01 | 13837.86 | 25-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.239386E+10 | 0.00 | 414.66 | 0.115738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14551.90 | 06-MAY-08:51 | 14196.97 | 06-MAY-08:51 | 0.00 | 0.00 | 0.00 |
June | 0.386189E+10 | 0.00 | 494.40 | 0.200963E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14030.75 | 12-JUN-18:01 | 13395.89 | 10-JUN-08:51 | 0.00 | 0.00 | 0.00 |
July | 0.469090E+10 | 0.00 | 521.80 | 0.245401E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16658.91 | 31-JUL-08:32 | 15704.15 | 24-JUL-08:32 | 0.00 | 0.00 | 0.00 |
August | 0.516350E+10 | 0.00 | 519.84 | 0.274949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16865.73 | 10-AUG-08:32 | 15328.57 | 13-AUG-08:32 | 0.00 | 0.00 | 0.00 |
September | 0.243866E+10 | 0.00 | 399.68 | 0.110653E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14461.35 | 24-SEP-15:01 | 13943.95 | 13-SEP-08:51 | 0.00 | 0.00 | 0.00 |
October | 0.532710E+09 | 0.00 | 145.58 | 0.237209E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14522.44 | 01-OCT-15:01 | 12282.14 | 06-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 37320501.03 | 0.00 | 16.44 | 10998431.23 | 0.00 | 0.00 | 0.00 | 0.00 | 13568.60 | 05-NOV-15:01 | 10782.68 | 04-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 2546414.82 | 0.00 | 1.52 | 686184.57 | 0.00 | 0.00 | 0.00 | 0.00 | 3338.17 | 02-DEC-09:02 | 1868.21 | 02-DEC-09:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.207119E+11 | 0.00 | 2868.80 | 0.105168E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1167286.50 | 0.00 | 0.51 | 218781.49 | 0.00 | 0.00 | 0.00 | 0.00 | 1156.48 | 267.81 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.516350E+10 | 0.00 | 521.80 | 0.274949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16865.73 | 15704.15 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 2192228.88 | 0.00 | 1.63 | 1408926.32 | 0.00 | 0.00 | 0.00 | 0.00 | 3274.88 | 05-JAN-16:01 | 3261.03 | 20-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 54066503.67 | 0.00 | 38.91 | 27452591.81 | 0.00 | 0.00 | 0.00 | 0.00 | 4390.20 | 12-FEB-16:01 | 4390.20 | 12-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.196455E+09 | 0.00 | 121.93 | 0.128358E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4390.60 | 28-MAR-15:01 | 4390.60 | 28-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.575201E+09 | 0.00 | 292.90 | 0.340481E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4486.10 | 30-APR-08:61 | 4388.60 | 23-APR-18:02 | 0.00 | 0.00 | 0.00 |
May | 0.107673E+10 | 0.00 | 471.18 | 0.637987E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4390.24 | 20-MAY-18:01 | 4390.24 | 20-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.126726E+10 | 0.00 | 569.16 | 0.683854E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4408.03 | 12-JUN-15:01 | 3990.02 | 23-JUN-15:01 | 0.00 | 0.00 | 0.00 |
July | 0.199780E+10 | 0.00 | 672.27 | 0.117562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4418.73 | 15-JUL-08:61 | 3886.86 | 23-JUL-08:62 | 0.00 | 0.00 | 0.00 |
August | 0.190064E+10 | 0.00 | 654.63 | 0.109123E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4592.38 | 20-AUG-08:61 | 3978.60 | 09-AUG-08:61 | 0.00 | 0.00 | 0.00 |
September | 0.123509E+10 | 0.00 | 516.75 | 0.677452E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4564.86 | 23-SEP-08:61 | 3987.38 | 06-SEP-15:01 | 0.00 | 0.00 | 0.00 |
October | 0.336503E+09 | 0.00 | 212.19 | 0.174360E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4544.38 | 01-OCT-08:62 | 4390.84 | 04-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 41900589.23 | 0.00 | 32.41 | 18045904.95 | 0.00 | 0.00 | 0.00 | 0.00 | 4487.39 | 05-NOV-15:01 | 3842.84 | 04-NOV-18:01 | 0.00 | 0.00 | 0.00 |
December | 5255959.83 | 0.00 | 6.88 | 2943633.72 | 0.00 | 0.00 | 0.00 | 0.00 | 4001.85 | 10-DEC-16:01 | 3688.94 | 10-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.868909E+10 | 0.00 | 3590.86 | 0.495920E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2192228.88 | 0.00 | 1.63 | 1408926.32 | 0.00 | 0.00 | 0.00 | 0.00 | 3274.88 | 3261.03 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.199780E+10 | 0.00 | 672.27 | 0.117562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4592.38 | 4390.84 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 177959.83 | 0.00 | 0.31 | 32661.36 | 0.00 | 0.00 | 0.00 | 0.00 | 346.08 | 20-JAN-16:05 | 102.42 | 20-JAN-16:05 | 0.00 | 0.00 | 0.00 |
February | 9398724.44 | 0.00 | 11.79 | 3815606.67 | 0.00 | 0.00 | 0.00 | 0.00 | 3618.99 | 26-FEB-16:01 | 3439.78 | 26-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 58883214.72 | 0.00 | 49.22 | 34430336.28 | 0.00 | 0.00 | 0.00 | 0.00 | 3893.02 | 25-MAR-15:01 | 3893.02 | 25-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.310058E+09 | 0.00 | 188.86 | 0.170709E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4574.65 | 25-APR-17:41 | 4574.65 | 25-APR-17:41 | 0.00 | 0.00 | 0.00 |
May | 0.649119E+09 | 0.00 | 366.16 | 0.326146E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4575.60 | 21-MAY-17:41 | 4575.60 | 21-MAY-17:41 | 0.00 | 0.00 | 0.00 |
June | 0.860962E+09 | 0.00 | 435.16 | 0.428483E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4342.25 | 22-JUN-21:51 | 3939.29 | 19-JUN-21:51 | 0.00 | 0.00 | 0.00 |
July | 0.139279E+10 | 0.00 | 510.12 | 0.772536E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4626.26 | 26-JUL-21:51 | 4064.16 | 19-JUL-21:51 | 0.00 | 0.00 | 0.00 |
August | 0.130159E+10 | 0.00 | 488.65 | 0.735660E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4300.23 | 11-AUG-21:51 | 3969.00 | 06-AUG-21:51 | 0.00 | 0.00 | 0.00 |
September | 0.595839E+09 | 0.00 | 361.45 | 0.253485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4240.37 | 13-SEP-21:51 | 3861.63 | 22-SEP-16:11 | 0.00 | 0.00 | 0.00 |
October | 93671335.49 | 0.00 | 98.22 | 37543185.37 | 0.00 | 0.00 | 0.00 | 0.00 | 4088.31 | 01-OCT-08:62 | 3612.76 | 07-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 7750853.19 | 0.00 | 8.06 | 2571218.02 | 0.00 | 0.00 | 0.00 | 0.00 | 4046.14 | 05-NOV-15:01 | 3291.75 | 04-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 187484.93 | 0.00 | 0.31 | 67757.81 | 0.00 | 0.00 | 0.00 | 0.00 | 323.64 | 29-DEC-19:06 | 244.15 | 02-DEC-19:06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.528043E+10 | 0.00 | 2518.31 | 0.276548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 177959.83 | 0.00 | 0.31 | 32661.36 | 0.00 | 0.00 | 0.00 | 0.00 | 323.64 | 102.42 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.139279E+10 | 0.00 | 510.12 | 0.772536E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4626.26 | 4575.60 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.455824E+09 | 0.00 | 63.71 | 0.203203E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20036.61 | 05-JAN-16:01 | 20036.61 | 05-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.176052E+10 | 0.00 | 179.71 | 0.961059E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22633.93 | 28-FEB-16:01 | 21449.79 | 26-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.302958E+10 | 0.00 | 307.79 | 0.191849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24114.24 | 25-MAR-15:01 | 24114.24 | 25-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.469085E+10 | 0.00 | 450.04 | 0.245489E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24464.34 | 30-APR-15:01 | 23870.08 | 13-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.599950E+10 | 0.00 | 555.03 | 0.298076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24109.44 | 14-MAY-18:01 | 24109.44 | 14-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.681200E+10 | 0.00 | 618.41 | 0.311330E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24208.15 | 12-JUN-15:01 | 22043.94 | 05-JUN-15:01 | 0.00 | 0.00 | 0.00 |
July | 0.956897E+10 | 0.00 | 675.13 | 0.472205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24540.83 | 16-JUL-15:01 | 21998.97 | 25-JUL-08:61 | 0.00 | 0.00 | 0.00 |
August | 0.107165E+11 | 0.00 | 672.83 | 0.568579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23877.42 | 29-AUG-08:62 | 21932.84 | 02-AUG-18:01 | 0.00 | 0.00 | 0.00 |
September | 0.874662E+10 | 0.00 | 588.70 | 0.487032E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23675.97 | 16-SEP-15:01 | 22012.09 | 22-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.467255E+10 | 0.00 | 441.23 | 0.253512E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24114.70 | 04-OCT-18:01 | 24114.70 | 04-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.123165E+10 | 0.00 | 152.88 | 0.559186E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23020.96 | 05-NOV-08:62 | 21653.30 | 02-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 0.971341E+09 | 0.00 | 104.50 | 0.512672E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21524.65 | 10-DEC-16:01 | 21524.65 | 10-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.586559E+11 | 0.00 | 4809.96 | 0.305168E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.455824E+09 | 0.00 | 63.71 | 0.203203E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20036.61 | 20036.61 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.107165E+11 | 0.00 | 675.13 | 0.568579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24540.83 | 24114.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 381.12 | 226.72 | 154.40 | 337.78 | 510.06 | 0.00 | 0.00 | 0.00 |
February | 586.49 | 363.88 | 222.60 | 596.42 | 447.88 | 0.00 | 0.00 | 0.00 |
March | 622.14 | 328.93 | 293.21 | 670.22 | 372.79 | 0.00 | 0.00 | 0.00 |
April | 657.40 | 282.14 | 375.26 | 757.86 | 299.99 | 0.00 | 0.00 | 0.00 |
May | 612.50 | 186.73 | 425.76 | 725.14 | 238.83 | 0.00 | 0.00 | 0.00 |
June | 554.17 | 148.32 | 405.85 | 678.90 | 176.85 | 0.00 | 0.00 | 0.00 |
July | 602.08 | 218.62 | 383.46 | 803.01 | 156.93 | 0.00 | 0.00 | 0.00 |
August | 641.87 | 294.94 | 346.93 | 876.28 | 151.61 | 0.00 | 0.00 | 0.00 |
September | 711.91 | 389.37 | 322.54 | 903.95 | 224.72 | 0.00 | 0.00 | 0.00 |
October | 643.99 | 394.27 | 249.72 | 744.27 | 315.16 | 0.00 | 0.00 | 0.00 |
November | 385.41 | 220.61 | 164.80 | 373.43 | 403.85 | 0.00 | 0.00 | 0.00 |
December | 403.36 | 260.85 | 142.51 | 395.63 | 512.02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 566.59 | 275.74 | 290.86 | 655.47 | 316.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 381.12 | 148.32 | 142.51 | 337.78 | 151.61 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 711.91 | 394.27 | 425.76 | 903.95 | 512.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1073.21 | 638.43 | 434.78 | 936.50 | 1482.97 | 0.00 | 0.00 | 0.00 |
February | 1651.51 | 1024.67 | 626.84 | 1656.80 | 1315.40 | 0.00 | 0.00 | 0.00 |
March | 1751.91 | 926.24 | 825.67 | 1862.36 | 1116.51 | 0.00 | 0.00 | 0.00 |
April | 1851.19 | 794.48 | 1056.71 | 2102.59 | 910.80 | 0.00 | 0.00 | 0.00 |
May | 1724.75 | 525.83 | 1198.93 | 2007.99 | 735.25 | 0.00 | 0.00 | 0.00 |
June | 1560.51 | 417.65 | 1142.85 | 1871.57 | 560.95 | 0.00 | 0.00 | 0.00 |
July | 1695.42 | 615.61 | 1079.81 | 2226.63 | 497.33 | 0.00 | 0.00 | 0.00 |
August | 1807.46 | 830.52 | 976.94 | 2435.47 | 484.34 | 0.00 | 0.00 | 0.00 |
September | 2004.70 | 1096.43 | 908.26 | 2516.26 | 697.80 | 0.00 | 0.00 | 0.00 |
October | 1813.42 | 1110.24 | 703.18 | 2068.81 | 961.74 | 0.00 | 0.00 | 0.00 |
November | 1085.28 | 621.22 | 464.06 | 1034.07 | 1194.93 | 0.00 | 0.00 | 0.00 |
December | 1135.85 | 734.54 | 401.31 | 1099.33 | 1493.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1595.49 | 776.46 | 819.03 | 1818.84 | 952.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1073.21 | 417.65 | 401.31 | 936.50 | 484.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2004.70 | 1110.24 | 1198.93 | 2516.26 | 1493.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1394.16 | 829.35 | 564.80 | 1224.42 | 2057.81 | 0.00 | 0.00 | 0.00 |
February | 2145.41 | 1331.11 | 814.30 | 2176.56 | 1814.82 | 0.00 | 0.00 | 0.00 |
March | 2275.84 | 1203.24 | 1072.60 | 2450.89 | 1546.67 | 0.00 | 0.00 | 0.00 |
April | 2404.80 | 1032.08 | 1372.72 | 2768.32 | 1260.23 | 0.00 | 0.00 | 0.00 |
May | 2240.55 | 683.08 | 1557.47 | 2639.00 | 1026.63 | 0.00 | 0.00 | 0.00 |
June | 2027.19 | 542.56 | 1484.63 | 2453.89 | 786.67 | 0.00 | 0.00 | 0.00 |
July | 2202.45 | 799.71 | 1402.74 | 2931.38 | 692.15 | 0.00 | 0.00 | 0.00 |
August | 2348.00 | 1078.89 | 1269.10 | 3208.13 | 668.38 | 0.00 | 0.00 | 0.00 |
September | 2604.21 | 1424.33 | 1179.88 | 3312.20 | 964.49 | 0.00 | 0.00 | 0.00 |
October | 2355.74 | 1442.27 | 913.47 | 2719.76 | 1336.74 | 0.00 | 0.00 | 0.00 |
November | 1409.84 | 807.00 | 602.84 | 1349.03 | 1673.41 | 0.00 | 0.00 | 0.00 |
December | 1475.53 | 954.20 | 521.33 | 1440.04 | 2072.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2072.64 | 1008.67 | 1063.97 | 2390.33 | 1322.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1394.16 | 542.56 | 521.33 | 1224.42 | 668.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2604.21 | 1442.27 | 1557.47 | 3312.20 | 2072.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.35 | 44.83 | 30.53 | 67.51 | 102.46 | 0.00 | 0.00 | 0.00 |
February | 115.96 | 71.95 | 44.01 | 118.59 | 89.93 | 0.00 | 0.00 | 0.00 |
March | 123.01 | 65.03 | 57.97 | 132.83 | 75.03 | 0.00 | 0.00 | 0.00 |
April | 129.98 | 55.78 | 74.20 | 148.89 | 60.84 | 0.00 | 0.00 | 0.00 |
May | 121.10 | 36.92 | 84.18 | 141.36 | 48.41 | 0.00 | 0.00 | 0.00 |
June | 109.57 | 29.33 | 80.24 | 132.14 | 35.17 | 0.00 | 0.00 | 0.00 |
July | 119.04 | 43.22 | 75.82 | 157.94 | 30.07 | 0.00 | 0.00 | 0.00 |
August | 126.91 | 58.31 | 68.60 | 173.72 | 27.95 | 0.00 | 0.00 | 0.00 |
September | 140.76 | 76.98 | 63.77 | 179.81 | 43.58 | 0.00 | 0.00 | 0.00 |
October | 127.33 | 77.95 | 49.37 | 147.73 | 62.34 | 0.00 | 0.00 | 0.00 |
November | 76.20 | 43.62 | 32.58 | 74.55 | 80.54 | 0.00 | 0.00 | 0.00 |
December | 79.75 | 51.57 | 28.18 | 79.12 | 101.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 112.03 | 54.52 | 57.51 | 129.56 | 63.06 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 75.35 | 29.33 | 28.18 | 67.51 | 27.95 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.76 | 77.95 | 84.18 | 179.81 | 102.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 54.10 | 16.09 | 38.01 | 22.20 | 207.29 | 0.00 | 0.00 | 0.00 |
February | 96.50 | 36.23 | 60.27 | 65.55 | 179.62 | 0.00 | 0.00 | 0.00 |
March | 135.19 | 45.71 | 89.48 | 113.71 | 142.95 | 0.00 | 0.00 | 0.00 |
April | 205.42 | 78.44 | 126.98 | 211.05 | 110.90 | 0.00 | 0.00 | 0.00 |
May | 264.84 | 107.82 | 157.02 | 300.78 | 87.51 | 0.00 | 0.00 | 0.00 |
June | 254.15 | 98.49 | 155.66 | 297.94 | 63.59 | 0.00 | 0.00 | 0.00 |
July | 314.18 | 165.10 | 149.08 | 402.41 | 54.51 | 0.00 | 0.00 | 0.00 |
August | 260.02 | 132.62 | 127.39 | 338.12 | 51.38 | 0.00 | 0.00 | 0.00 |
September | 212.43 | 102.19 | 110.24 | 253.46 | 81.31 | 0.00 | 0.00 | 0.00 |
October | 121.48 | 49.94 | 71.54 | 113.95 | 120.27 | 0.00 | 0.00 | 0.00 |
November | 60.16 | 17.10 | 43.06 | 33.73 | 159.56 | 0.00 | 0.00 | 0.00 |
December | 50.78 | 17.63 | 33.15 | 26.78 | 205.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 169.55 | 72.56 | 96.99 | 182.40 | 121.72 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 50.78 | 16.09 | 33.15 | 22.20 | 51.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 314.18 | 165.10 | 157.02 | 402.41 | 207.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.99 | 0.00 | 16.99 | 0.54 | 114.61 | 0.00 | 0.00 | 0.00 |
February | 26.44 | 0.00 | 26.44 | 5.16 | 99.24 | 0.00 | 0.00 | 0.00 |
March | 38.96 | 0.00 | 38.96 | 17.23 | 77.79 | 0.00 | 0.00 | 0.00 |
April | 55.32 | 0.34 | 54.98 | 37.42 | 59.68 | 0.00 | 0.00 | 0.00 |
May | 70.97 | 2.13 | 68.84 | 58.98 | 46.56 | 0.00 | 0.00 | 0.00 |
June | 74.69 | 5.00 | 69.70 | 70.07 | 33.86 | 0.00 | 0.00 | 0.00 |
July | 71.09 | 5.72 | 65.37 | 74.63 | 30.01 | 0.00 | 0.00 | 0.00 |
August | 57.63 | 1.73 | 55.90 | 63.57 | 27.93 | 0.00 | 0.00 | 0.00 |
September | 44.60 | 0.03 | 44.57 | 36.53 | 45.71 | 0.00 | 0.00 | 0.00 |
October | 30.54 | 0.00 | 30.54 | 15.28 | 65.17 | 0.00 | 0.00 | 0.00 |
November | 19.24 | 0.00 | 19.24 | 3.13 | 87.04 | 0.00 | 0.00 | 0.00 |
December | 14.44 | 0.00 | 14.44 | 0.28 | 111.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 43.49 | 1.26 | 42.24 | 32.07 | 66.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.44 | 0.00 | 14.44 | 0.28 | 27.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.69 | 5.72 | 69.70 | 74.63 | 114.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 54.10 | 16.09 | 38.01 | 23.74 | 205.23 | 0.00 | 0.00 | 0.00 |
February | 96.50 | 36.23 | 60.27 | 68.60 | 176.86 | 0.00 | 0.00 | 0.00 |
March | 135.19 | 45.71 | 89.48 | 117.42 | 141.00 | 0.00 | 0.00 | 0.00 |
April | 205.42 | 78.44 | 126.98 | 213.83 | 110.35 | 0.00 | 0.00 | 0.00 |
May | 264.84 | 107.82 | 157.02 | 299.30 | 89.13 | 0.00 | 0.00 | 0.00 |
June | 254.15 | 98.49 | 155.66 | 295.12 | 66.33 | 0.00 | 0.00 | 0.00 |
July | 314.18 | 165.10 | 149.08 | 397.77 | 58.84 | 0.00 | 0.00 | 0.00 |
August | 260.02 | 132.62 | 127.39 | 336.89 | 54.55 | 0.00 | 0.00 | 0.00 |
September | 212.43 | 102.19 | 110.24 | 253.41 | 83.59 | 0.00 | 0.00 | 0.00 |
October | 121.48 | 49.94 | 71.54 | 117.29 | 118.61 | 0.00 | 0.00 | 0.00 |
November | 60.16 | 17.10 | 43.06 | 35.50 | 157.67 | 0.00 | 0.00 | 0.00 |
December | 50.78 | 17.63 | 33.15 | 28.54 | 202.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 169.55 | 72.56 | 96.99 | 183.03 | 121.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 50.78 | 16.09 | 33.15 | 23.74 | 54.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 314.18 | 165.10 | 157.02 | 397.77 | 205.23 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.27 | 35.85 | 24.42 | 51.65 | 88.32 | 0.00 | 0.00 | 0.00 |
February | 92.75 | 57.55 | 35.20 | 87.86 | 89.57 | 0.00 | 0.00 | 0.00 |
March | 98.39 | 52.02 | 46.37 | 96.33 | 85.78 | 0.00 | 0.00 | 0.00 |
April | 103.96 | 44.62 | 59.34 | 107.18 | 71.55 | 0.00 | 0.00 | 0.00 |
May | 96.86 | 29.53 | 67.33 | 101.17 | 59.09 | 0.00 | 0.00 | 0.00 |
June | 87.64 | 23.46 | 64.18 | 92.49 | 46.63 | 0.00 | 0.00 | 0.00 |
July | 95.22 | 34.57 | 60.64 | 113.99 | 41.67 | 0.00 | 0.00 | 0.00 |
August | 101.51 | 46.64 | 54.87 | 126.47 | 40.53 | 0.00 | 0.00 | 0.00 |
September | 112.58 | 61.58 | 51.01 | 132.81 | 55.81 | 0.00 | 0.00 | 0.00 |
October | 101.84 | 62.35 | 39.49 | 107.77 | 76.20 | 0.00 | 0.00 | 0.00 |
November | 60.95 | 34.89 | 26.06 | 52.58 | 88.67 | 0.00 | 0.00 | 0.00 |
December | 63.79 | 41.25 | 22.54 | 59.39 | 94.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.60 | 43.61 | 46.00 | 94.17 | 69.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.27 | 23.46 | 22.54 | 51.65 | 40.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 112.58 | 62.35 | 67.33 | 132.81 | 94.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.60 | 0.00 | 13.60 | 0.26 | 97.33 | 0.00 | 0.00 | 0.00 |
February | 21.15 | 0.00 | 21.15 | 3.57 | 83.18 | 0.00 | 0.00 | 0.00 |
March | 31.17 | 0.00 | 31.17 | 13.35 | 64.37 | 0.00 | 0.00 | 0.00 |
April | 44.26 | 0.27 | 43.99 | 30.89 | 48.17 | 0.00 | 0.00 | 0.00 |
May | 56.79 | 1.71 | 55.08 | 50.28 | 36.54 | 0.00 | 0.00 | 0.00 |
June | 59.76 | 4.00 | 55.77 | 59.42 | 26.22 | 0.00 | 0.00 | 0.00 |
July | 56.88 | 4.58 | 52.30 | 64.59 | 22.19 | 0.00 | 0.00 | 0.00 |
August | 46.11 | 1.38 | 44.72 | 54.50 | 20.82 | 0.00 | 0.00 | 0.00 |
September | 35.69 | 0.03 | 35.66 | 31.56 | 34.99 | 0.00 | 0.00 | 0.00 |
October | 24.44 | 0.00 | 24.44 | 12.20 | 53.47 | 0.00 | 0.00 | 0.00 |
November | 15.39 | 0.00 | 15.39 | 2.09 | 73.94 | 0.00 | 0.00 | 0.00 |
December | 11.55 | 0.00 | 11.55 | 0.11 | 94.80 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 34.80 | 1.00 | 33.80 | 27.05 | 54.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 11.55 | 0.00 | 11.55 | 0.11 | 20.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 59.76 | 4.58 | 55.77 | 64.59 | 97.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 50.77 | 12.72 | 38.05 | 16.37 | 205.38 | 0.00 | 0.00 | 0.00 |
February | 93.53 | 33.13 | 60.40 | 58.26 | 176.16 | 0.00 | 0.00 | 0.00 |
March | 140.17 | 50.83 | 89.34 | 115.57 | 138.21 | 0.00 | 0.00 | 0.00 |
April | 216.49 | 89.84 | 126.65 | 221.30 | 106.50 | 0.00 | 0.00 | 0.00 |
May | 230.51 | 80.26 | 150.25 | 251.80 | 84.87 | 0.00 | 0.00 | 0.00 |
June | 275.89 | 120.08 | 155.81 | 326.46 | 60.99 | 0.00 | 0.00 | 0.00 |
July | 257.29 | 115.68 | 141.62 | 320.87 | 50.05 | 0.00 | 0.00 | 0.00 |
August | 252.57 | 126.34 | 126.23 | 324.71 | 47.89 | 0.00 | 0.00 | 0.00 |
September | 187.04 | 86.42 | 100.63 | 213.79 | 77.72 | 0.00 | 0.00 | 0.00 |
October | 122.30 | 52.26 | 70.05 | 112.51 | 117.06 | 0.00 | 0.00 | 0.00 |
November | 59.85 | 16.95 | 42.90 | 31.53 | 157.34 | 0.00 | 0.00 | 0.00 |
December | 48.96 | 15.74 | 33.22 | 21.46 | 201.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 161.58 | 66.83 | 94.75 | 168.46 | 118.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 48.96 | 12.72 | 33.22 | 16.37 | 47.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 275.89 | 126.34 | 155.81 | 326.46 | 205.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.35 | 44.83 | 30.53 | 67.48 | 102.32 | 0.00 | 0.00 | 0.00 |
February | 115.96 | 71.95 | 44.01 | 118.31 | 89.72 | 0.00 | 0.00 | 0.00 |
March | 123.01 | 65.03 | 57.97 | 132.09 | 74.83 | 0.00 | 0.00 | 0.00 |
April | 129.98 | 55.78 | 74.20 | 147.78 | 60.63 | 0.00 | 0.00 | 0.00 |
May | 121.10 | 36.92 | 84.18 | 141.24 | 47.78 | 0.00 | 0.00 | 0.00 |
June | 109.57 | 29.33 | 80.24 | 131.09 | 34.87 | 0.00 | 0.00 | 0.00 |
July | 119.04 | 43.22 | 75.82 | 157.99 | 29.26 | 0.00 | 0.00 | 0.00 |
August | 126.91 | 58.31 | 68.60 | 173.21 | 27.54 | 0.00 | 0.00 | 0.00 |
September | 140.76 | 76.98 | 63.77 | 179.67 | 42.85 | 0.00 | 0.00 | 0.00 |
October | 127.33 | 77.95 | 49.37 | 147.25 | 62.05 | 0.00 | 0.00 | 0.00 |
November | 76.20 | 43.62 | 32.58 | 74.42 | 80.41 | 0.00 | 0.00 | 0.00 |
December | 79.75 | 51.57 | 28.18 | 79.08 | 101.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 112.03 | 54.52 | 57.51 | 129.18 | 62.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 75.35 | 29.33 | 28.18 | 67.48 | 27.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.76 | 77.95 | 84.18 | 179.67 | 102.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.99 | 0.00 | 16.99 | 0.52 | 114.51 | 0.00 | 0.00 | 0.00 |
February | 26.44 | 0.00 | 26.44 | 5.05 | 99.09 | 0.00 | 0.00 | 0.00 |
March | 38.96 | 0.00 | 38.96 | 16.59 | 77.64 | 0.00 | 0.00 | 0.00 |
April | 55.32 | 0.34 | 54.98 | 36.41 | 59.56 | 0.00 | 0.00 | 0.00 |
May | 70.97 | 2.13 | 68.84 | 59.73 | 45.48 | 0.00 | 0.00 | 0.00 |
June | 74.69 | 5.00 | 69.70 | 69.56 | 33.19 | 0.00 | 0.00 | 0.00 |
July | 71.09 | 5.72 | 65.37 | 75.78 | 28.34 | 0.00 | 0.00 | 0.00 |
August | 57.63 | 1.73 | 55.90 | 62.79 | 27.10 | 0.00 | 0.00 | 0.00 |
September | 44.60 | 0.03 | 44.57 | 36.86 | 44.12 | 0.00 | 0.00 | 0.00 |
October | 30.54 | 0.00 | 30.54 | 14.80 | 64.70 | 0.00 | 0.00 | 0.00 |
November | 19.24 | 0.00 | 19.24 | 3.01 | 86.84 | 0.00 | 0.00 | 0.00 |
December | 14.44 | 0.00 | 14.44 | 0.25 | 111.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 43.49 | 1.26 | 42.24 | 31.95 | 65.85 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.44 | 0.00 | 14.44 | 0.25 | 27.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.69 | 5.72 | 69.70 | 75.78 | 114.51 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 50.77 | 12.72 | 38.05 | 16.98 | 202.39 | 0.00 | 0.00 | 0.00 |
February | 93.53 | 33.13 | 60.40 | 60.28 | 172.08 | 0.00 | 0.00 | 0.00 |
March | 140.17 | 50.83 | 89.34 | 119.08 | 135.89 | 0.00 | 0.00 | 0.00 |
April | 216.49 | 89.84 | 126.65 | 224.03 | 105.71 | 0.00 | 0.00 | 0.00 |
May | 230.51 | 80.26 | 150.25 | 252.49 | 85.73 | 0.00 | 0.00 | 0.00 |
June | 275.89 | 120.08 | 155.81 | 325.40 | 63.40 | 0.00 | 0.00 | 0.00 |
July | 257.29 | 115.68 | 141.62 | 318.99 | 53.13 | 0.00 | 0.00 | 0.00 |
August | 252.57 | 126.34 | 126.23 | 323.33 | 50.50 | 0.00 | 0.00 | 0.00 |
September | 187.04 | 86.42 | 100.63 | 215.38 | 78.72 | 0.00 | 0.00 | 0.00 |
October | 122.30 | 52.26 | 70.05 | 115.85 | 114.97 | 0.00 | 0.00 | 0.00 |
November | 59.85 | 16.95 | 42.90 | 32.71 | 154.67 | 0.00 | 0.00 | 0.00 |
December | 48.96 | 15.74 | 33.22 | 22.24 | 198.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 161.58 | 66.83 | 94.75 | 169.45 | 117.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 48.96 | 12.72 | 33.22 | 16.98 | 50.50 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 275.89 | 126.34 | 155.81 | 325.40 | 202.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 21.52 | 0.00 | 21.52 | 0.39 | 157.32 | 0.00 | 0.00 | 0.00 |
February | 33.48 | 0.00 | 33.48 | 5.60 | 134.39 | 0.00 | 0.00 | 0.00 |
March | 49.34 | 0.00 | 49.34 | 21.09 | 103.68 | 0.00 | 0.00 | 0.00 |
April | 70.06 | 0.43 | 69.63 | 48.84 | 78.89 | 0.00 | 0.00 | 0.00 |
May | 89.88 | 2.70 | 87.19 | 78.78 | 62.00 | 0.00 | 0.00 | 0.00 |
June | 94.60 | 6.33 | 88.27 | 92.79 | 45.25 | 0.00 | 0.00 | 0.00 |
July | 90.04 | 7.25 | 82.79 | 99.72 | 39.69 | 0.00 | 0.00 | 0.00 |
August | 72.98 | 2.19 | 70.79 | 82.61 | 38.75 | 0.00 | 0.00 | 0.00 |
September | 56.49 | 0.04 | 56.45 | 47.88 | 61.20 | 0.00 | 0.00 | 0.00 |
October | 38.68 | 0.00 | 38.68 | 18.57 | 88.10 | 0.00 | 0.00 | 0.00 |
November | 24.36 | 0.00 | 24.36 | 3.37 | 118.73 | 0.00 | 0.00 | 0.00 |
December | 18.29 | 0.00 | 18.29 | 0.15 | 153.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.08 | 1.59 | 53.49 | 41.87 | 89.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.29 | 0.00 | 18.29 | 0.15 | 38.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 94.60 | 7.25 | 88.27 | 99.72 | 157.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 7.93 | 0.00 | 7.93 | 0.14 | 57.99 | 0.00 | 0.00 | 0.00 |
February | 12.34 | 0.00 | 12.34 | 2.06 | 49.54 | 0.00 | 0.00 | 0.00 |
March | 18.19 | 0.00 | 18.19 | 7.77 | 38.22 | 0.00 | 0.00 | 0.00 |
April | 25.83 | 0.16 | 25.67 | 18.01 | 29.08 | 0.00 | 0.00 | 0.00 |
May | 33.14 | 0.99 | 32.14 | 29.04 | 22.86 | 0.00 | 0.00 | 0.00 |
June | 34.87 | 2.33 | 32.54 | 34.21 | 16.68 | 0.00 | 0.00 | 0.00 |
July | 33.19 | 2.67 | 30.52 | 36.76 | 14.63 | 0.00 | 0.00 | 0.00 |
August | 26.90 | 0.81 | 26.10 | 30.45 | 14.28 | 0.00 | 0.00 | 0.00 |
September | 20.82 | 0.02 | 20.81 | 17.65 | 22.56 | 0.00 | 0.00 | 0.00 |
October | 14.26 | 0.00 | 14.26 | 6.85 | 32.48 | 0.00 | 0.00 | 0.00 |
November | 8.98 | 0.00 | 8.98 | 1.24 | 43.77 | 0.00 | 0.00 | 0.00 |
December | 6.74 | 0.00 | 6.74 | 0.05 | 56.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 20.31 | 0.59 | 19.72 | 15.44 | 33.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 6.74 | 0.00 | 6.74 | 0.05 | 14.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 34.87 | 2.67 | 32.54 | 36.76 | 57.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.16 | 20.92 | 14.24 | 30.98 | 50.76 | 0.00 | 0.00 | 0.00 |
February | 54.11 | 33.57 | 20.54 | 55.39 | 43.88 | 0.00 | 0.00 | 0.00 |
March | 57.40 | 30.35 | 27.05 | 62.59 | 36.32 | 0.00 | 0.00 | 0.00 |
April | 60.65 | 26.03 | 34.62 | 70.65 | 29.45 | 0.00 | 0.00 | 0.00 |
May | 56.51 | 17.23 | 39.28 | 67.15 | 24.18 | 0.00 | 0.00 | 0.00 |
June | 51.12 | 13.68 | 37.44 | 62.57 | 18.16 | 0.00 | 0.00 | 0.00 |
July | 55.54 | 20.17 | 35.38 | 74.60 | 15.96 | 0.00 | 0.00 | 0.00 |
August | 59.22 | 27.21 | 32.01 | 81.62 | 15.26 | 0.00 | 0.00 | 0.00 |
September | 65.68 | 35.92 | 29.76 | 84.59 | 22.23 | 0.00 | 0.00 | 0.00 |
October | 59.41 | 36.37 | 23.04 | 69.53 | 30.63 | 0.00 | 0.00 | 0.00 |
November | 35.56 | 20.35 | 15.20 | 34.68 | 39.75 | 0.00 | 0.00 | 0.00 |
December | 37.21 | 24.06 | 13.15 | 36.74 | 50.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 52.27 | 25.44 | 26.83 | 60.95 | 31.37 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 35.16 | 13.68 | 13.15 | 30.98 | 15.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.68 | 36.37 | 39.28 | 84.59 | 50.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 95.43 | 56.77 | 38.66 | 84.08 | 137.77 | 0.00 | 0.00 | 0.00 |
February | 146.85 | 91.12 | 55.74 | 150.33 | 119.09 | 0.00 | 0.00 | 0.00 |
March | 155.78 | 82.36 | 73.42 | 169.89 | 98.58 | 0.00 | 0.00 | 0.00 |
April | 164.61 | 70.65 | 93.96 | 191.76 | 79.94 | 0.00 | 0.00 | 0.00 |
May | 153.37 | 46.76 | 106.61 | 182.26 | 65.62 | 0.00 | 0.00 | 0.00 |
June | 138.76 | 37.14 | 101.62 | 169.83 | 49.30 | 0.00 | 0.00 | 0.00 |
July | 150.76 | 54.74 | 96.02 | 202.49 | 43.33 | 0.00 | 0.00 | 0.00 |
August | 160.72 | 73.85 | 86.87 | 221.54 | 41.41 | 0.00 | 0.00 | 0.00 |
September | 178.26 | 97.50 | 80.76 | 229.60 | 60.34 | 0.00 | 0.00 | 0.00 |
October | 161.25 | 98.72 | 62.53 | 188.71 | 83.14 | 0.00 | 0.00 | 0.00 |
November | 96.50 | 55.24 | 41.26 | 94.12 | 107.88 | 0.00 | 0.00 | 0.00 |
December | 101.00 | 65.32 | 35.69 | 99.73 | 137.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 141.87 | 69.04 | 72.83 | 165.42 | 85.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 95.43 | 37.14 | 35.69 | 84.08 | 41.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 178.26 | 98.72 | 106.61 | 229.60 | 137.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.35 | 44.83 | 30.53 | 67.61 | 101.75 | 0.00 | 0.00 | 0.00 |
February | 115.96 | 71.95 | 44.01 | 118.30 | 89.37 | 0.00 | 0.00 | 0.00 |
March | 123.01 | 65.03 | 57.97 | 132.14 | 74.63 | 0.00 | 0.00 | 0.00 |
April | 129.98 | 55.78 | 74.20 | 147.59 | 60.76 | 0.00 | 0.00 | 0.00 |
May | 121.10 | 36.92 | 84.18 | 139.84 | 48.28 | 0.00 | 0.00 | 0.00 |
June | 109.57 | 29.33 | 80.24 | 130.59 | 35.01 | 0.00 | 0.00 | 0.00 |
July | 119.04 | 43.22 | 75.82 | 156.33 | 29.91 | 0.00 | 0.00 | 0.00 |
August | 126.91 | 58.31 | 68.60 | 172.42 | 27.60 | 0.00 | 0.00 | 0.00 |
September | 140.76 | 76.98 | 63.77 | 178.89 | 43.11 | 0.00 | 0.00 | 0.00 |
October | 127.33 | 77.95 | 49.37 | 147.05 | 61.73 | 0.00 | 0.00 | 0.00 |
November | 76.20 | 43.62 | 32.58 | 74.50 | 79.80 | 0.00 | 0.00 | 0.00 |
December | 79.75 | 51.57 | 28.18 | 79.14 | 101.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 112.03 | 54.52 | 57.51 | 128.74 | 62.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 75.35 | 29.33 | 28.18 | 67.61 | 27.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.76 | 77.95 | 84.18 | 178.89 | 101.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 54.10 | 16.09 | 38.01 | 22.48 | 205.41 | 0.00 | 0.00 | 0.00 |
February | 96.50 | 36.23 | 60.27 | 65.33 | 178.10 | 0.00 | 0.00 | 0.00 |
March | 135.19 | 45.71 | 89.48 | 112.83 | 141.86 | 0.00 | 0.00 | 0.00 |
April | 205.42 | 78.44 | 126.98 | 208.69 | 110.57 | 0.00 | 0.00 | 0.00 |
May | 264.84 | 107.82 | 157.02 | 297.56 | 87.12 | 0.00 | 0.00 | 0.00 |
June | 254.15 | 98.49 | 155.66 | 294.65 | 63.16 | 0.00 | 0.00 | 0.00 |
July | 314.18 | 165.10 | 149.08 | 398.76 | 54.06 | 0.00 | 0.00 | 0.00 |
August | 260.02 | 132.62 | 127.39 | 335.51 | 50.61 | 0.00 | 0.00 | 0.00 |
September | 212.43 | 102.19 | 110.24 | 251.74 | 80.27 | 0.00 | 0.00 | 0.00 |
October | 121.48 | 49.94 | 71.54 | 113.18 | 118.80 | 0.00 | 0.00 | 0.00 |
November | 60.16 | 17.10 | 43.06 | 33.84 | 157.66 | 0.00 | 0.00 | 0.00 |
December | 50.78 | 17.63 | 33.15 | 26.91 | 202.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 169.55 | 72.56 | 96.99 | 180.88 | 120.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 50.78 | 16.09 | 33.15 | 22.48 | 50.61 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 314.18 | 165.10 | 157.02 | 398.76 | 205.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.99 | 0.00 | 16.99 | 0.61 | 113.36 | 0.00 | 0.00 | 0.00 |
February | 26.44 | 0.00 | 26.44 | 5.30 | 98.34 | 0.00 | 0.00 | 0.00 |
March | 38.96 | 0.00 | 38.96 | 17.28 | 77.17 | 0.00 | 0.00 | 0.00 |
April | 55.32 | 0.34 | 54.98 | 36.94 | 59.53 | 0.00 | 0.00 | 0.00 |
May | 70.97 | 2.13 | 68.84 | 57.70 | 46.81 | 0.00 | 0.00 | 0.00 |
June | 74.69 | 5.00 | 69.70 | 68.57 | 34.19 | 0.00 | 0.00 | 0.00 |
July | 71.09 | 5.72 | 65.37 | 73.02 | 30.59 | 0.00 | 0.00 | 0.00 |
August | 57.63 | 1.73 | 55.90 | 62.83 | 27.97 | 0.00 | 0.00 | 0.00 |
September | 44.60 | 0.03 | 44.57 | 36.00 | 45.85 | 0.00 | 0.00 | 0.00 |
October | 30.54 | 0.00 | 30.54 | 15.48 | 64.28 | 0.00 | 0.00 | 0.00 |
November | 19.24 | 0.00 | 19.24 | 3.25 | 85.82 | 0.00 | 0.00 | 0.00 |
December | 14.44 | 0.00 | 14.44 | 0.33 | 110.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 43.49 | 1.26 | 42.24 | 31.61 | 66.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.44 | 0.00 | 14.44 | 0.33 | 27.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.69 | 5.72 | 69.70 | 73.02 | 113.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 54.10 | 16.09 | 38.01 | 24.07 | 203.51 | 0.00 | 0.00 | 0.00 |
February | 96.50 | 36.23 | 60.27 | 68.73 | 175.34 | 0.00 | 0.00 | 0.00 |
March | 135.19 | 45.71 | 89.48 | 116.89 | 139.79 | 0.00 | 0.00 | 0.00 |
April | 205.42 | 78.44 | 126.98 | 211.57 | 110.14 | 0.00 | 0.00 | 0.00 |
May | 264.84 | 107.82 | 157.02 | 295.36 | 89.59 | 0.00 | 0.00 | 0.00 |
June | 254.15 | 98.49 | 155.66 | 290.88 | 66.93 | 0.00 | 0.00 | 0.00 |
July | 314.18 | 165.10 | 149.08 | 392.93 | 59.87 | 0.00 | 0.00 | 0.00 |
August | 260.02 | 132.62 | 127.39 | 333.93 | 54.54 | 0.00 | 0.00 | 0.00 |
September | 212.43 | 102.19 | 110.24 | 251.24 | 83.56 | 0.00 | 0.00 | 0.00 |
October | 121.48 | 49.94 | 71.54 | 116.91 | 117.01 | 0.00 | 0.00 | 0.00 |
November | 60.16 | 17.10 | 43.06 | 35.81 | 155.71 | 0.00 | 0.00 | 0.00 |
December | 50.78 | 17.63 | 33.15 | 28.88 | 200.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 169.55 | 72.56 | 96.99 | 181.34 | 121.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 50.78 | 16.09 | 33.15 | 24.07 | 54.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 314.18 | 165.10 | 157.02 | 392.93 | 203.51 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 110.51 | 65.74 | 44.77 | 94.98 | 155.59 | 0.00 | 0.00 | 0.00 |
February | 170.06 | 105.52 | 64.55 | 168.51 | 136.58 | 0.00 | 0.00 | 0.00 |
March | 180.40 | 95.38 | 85.02 | 189.89 | 113.49 | 0.00 | 0.00 | 0.00 |
April | 190.63 | 81.81 | 108.82 | 214.12 | 90.67 | 0.00 | 0.00 | 0.00 |
May | 177.61 | 54.15 | 123.46 | 205.24 | 70.60 | 0.00 | 0.00 | 0.00 |
June | 160.69 | 43.01 | 117.69 | 192.34 | 50.74 | 0.00 | 0.00 | 0.00 |
July | 174.59 | 63.39 | 111.20 | 231.30 | 42.37 | 0.00 | 0.00 | 0.00 |
August | 186.12 | 85.52 | 100.60 | 253.83 | 39.54 | 0.00 | 0.00 | 0.00 |
September | 206.43 | 112.91 | 93.53 | 261.36 | 63.37 | 0.00 | 0.00 | 0.00 |
October | 186.74 | 114.33 | 72.41 | 211.95 | 94.08 | 0.00 | 0.00 | 0.00 |
November | 111.76 | 63.97 | 47.79 | 105.73 | 122.62 | 0.00 | 0.00 | 0.00 |
December | 116.96 | 75.64 | 41.33 | 112.33 | 154.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 164.30 | 79.96 | 84.34 | 186.88 | 94.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 110.51 | 43.01 | 41.33 | 94.98 | 39.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 206.43 | 114.33 | 123.46 | 261.36 | 155.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 118.94 | 0.00 | 118.94 | 0.51 | 1002.39 | 0.00 | 0.00 | 0.00 |
February | 185.07 | 0.00 | 185.07 | 18.70 | 868.16 | 0.00 | 0.00 | 0.00 |
March | 272.70 | 0.00 | 272.70 | 83.59 | 679.19 | 0.00 | 0.00 | 0.00 |
April | 387.23 | 2.38 | 384.85 | 219.62 | 515.73 | 0.00 | 0.00 | 0.00 |
May | 496.80 | 14.92 | 481.88 | 378.21 | 393.01 | 0.00 | 0.00 | 0.00 |
June | 522.84 | 34.98 | 487.86 | 452.63 | 287.79 | 0.00 | 0.00 | 0.00 |
July | 497.64 | 40.06 | 457.58 | 502.37 | 248.59 | 0.00 | 0.00 | 0.00 |
August | 403.39 | 12.11 | 391.28 | 416.97 | 242.72 | 0.00 | 0.00 | 0.00 |
September | 312.22 | 0.23 | 311.99 | 230.69 | 382.98 | 0.00 | 0.00 | 0.00 |
October | 213.77 | 0.00 | 213.77 | 74.74 | 582.09 | 0.00 | 0.00 | 0.00 |
November | 134.66 | 0.00 | 134.66 | 9.37 | 785.31 | 0.00 | 0.00 | 0.00 |
December | 101.07 | 0.00 | 101.07 | 0.13 | 979.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 304.45 | 8.79 | 295.66 | 200.12 | 579.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.07 | 0.00 | 101.07 | 0.13 | 242.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 522.84 | 40.06 | 487.86 | 502.37 | 1002.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 118.94 | 0.00 | 118.94 | 0.26 | 1034.72 | 0.00 | 0.00 | 0.00 |
February | 185.07 | 0.00 | 185.07 | 16.38 | 896.97 | 0.00 | 0.00 | 0.00 |
March | 272.70 | 0.00 | 272.70 | 75.82 | 699.37 | 0.00 | 0.00 | 0.00 |
April | 387.23 | 2.38 | 384.85 | 208.97 | 529.62 | 0.00 | 0.00 | 0.00 |
May | 496.80 | 14.92 | 481.88 | 367.27 | 402.57 | 0.00 | 0.00 | 0.00 |
June | 522.84 | 34.98 | 487.86 | 441.43 | 295.19 | 0.00 | 0.00 | 0.00 |
July | 497.64 | 40.06 | 457.58 | 492.82 | 255.34 | 0.00 | 0.00 | 0.00 |
August | 403.39 | 12.11 | 391.28 | 407.71 | 250.12 | 0.00 | 0.00 | 0.00 |
September | 312.22 | 0.23 | 311.99 | 222.41 | 394.00 | 0.00 | 0.00 | 0.00 |
October | 213.77 | 0.00 | 213.77 | 67.90 | 601.10 | 0.00 | 0.00 | 0.00 |
November | 134.66 | 0.00 | 134.66 | 7.82 | 813.57 | 0.00 | 0.00 | 0.00 |
December | 101.07 | 0.00 | 101.07 | 0.07 | 1011.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 304.45 | 8.79 | 295.66 | 193.55 | 597.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.07 | 0.00 | 101.07 | 0.07 | 250.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 522.84 | 40.06 | 487.86 | 492.82 | 1034.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.99 | 0.00 | 16.99 | 0.94 | 119.74 | 0.00 | 0.00 | 0.00 |
February | 26.44 | 0.00 | 26.44 | 7.08 | 104.38 | 0.00 | 0.00 | 0.00 |
March | 38.96 | 0.00 | 38.96 | 21.96 | 82.52 | 0.00 | 0.00 | 0.00 |
April | 55.32 | 0.34 | 54.98 | 47.63 | 64.69 | 0.00 | 0.00 | 0.00 |
May | 70.97 | 2.13 | 68.84 | 75.94 | 50.95 | 0.00 | 0.00 | 0.00 |
June | 74.69 | 5.00 | 69.70 | 89.47 | 38.89 | 0.00 | 0.00 | 0.00 |
July | 71.09 | 5.72 | 65.37 | 97.63 | 33.32 | 0.00 | 0.00 | 0.00 |
August | 57.63 | 1.73 | 55.90 | 84.06 | 31.86 | 0.00 | 0.00 | 0.00 |
September | 44.60 | 0.03 | 44.57 | 52.22 | 45.69 | 0.00 | 0.00 | 0.00 |
October | 30.54 | 0.00 | 30.54 | 21.10 | 69.12 | 0.00 | 0.00 | 0.00 |
November | 19.24 | 0.00 | 19.24 | 5.25 | 91.04 | 0.00 | 0.00 | 0.00 |
December | 14.44 | 0.00 | 14.44 | 0.73 | 116.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 43.49 | 1.26 | 42.24 | 42.21 | 70.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.44 | 0.00 | 14.44 | 0.73 | 31.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.69 | 5.72 | 69.70 | 97.63 | 119.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.53 | 25.44 | 76.09 | 38.47 | 429.51 | 0.00 | 0.00 | 0.00 |
February | 187.04 | 66.25 | 120.79 | 132.36 | 368.69 | 0.00 | 0.00 | 0.00 |
March | 280.32 | 101.65 | 178.67 | 262.35 | 294.12 | 0.00 | 0.00 | 0.00 |
April | 432.94 | 179.66 | 253.29 | 494.93 | 233.94 | 0.00 | 0.00 | 0.00 |
May | 460.98 | 160.51 | 300.48 | 565.99 | 191.35 | 0.00 | 0.00 | 0.00 |
June | 551.74 | 240.14 | 311.60 | 724.31 | 146.60 | 0.00 | 0.00 | 0.00 |
July | 514.55 | 231.34 | 283.21 | 718.71 | 123.55 | 0.00 | 0.00 | 0.00 |
August | 505.11 | 252.66 | 252.44 | 727.43 | 118.95 | 0.00 | 0.00 | 0.00 |
September | 374.06 | 172.82 | 201.24 | 492.31 | 167.01 | 0.00 | 0.00 | 0.00 |
October | 244.59 | 104.51 | 140.08 | 260.20 | 250.70 | 0.00 | 0.00 | 0.00 |
November | 119.70 | 33.90 | 85.80 | 76.78 | 330.81 | 0.00 | 0.00 | 0.00 |
December | 97.92 | 31.47 | 66.44 | 50.51 | 420.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 323.14 | 133.66 | 189.48 | 379.97 | 255.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 97.92 | 25.44 | 66.44 | 38.47 | 118.95 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 551.74 | 252.66 | 311.60 | 727.43 | 429.51 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.35 | 44.83 | 30.53 | 70.32 | 108.30 | 0.00 | 0.00 | 0.00 |
February | 115.96 | 71.95 | 44.01 | 124.62 | 95.13 | 0.00 | 0.00 | 0.00 |
March | 123.01 | 65.03 | 57.97 | 141.48 | 79.74 | 0.00 | 0.00 | 0.00 |
April | 129.98 | 55.78 | 74.20 | 161.31 | 66.06 | 0.00 | 0.00 | 0.00 |
May | 121.10 | 36.92 | 84.18 | 157.37 | 53.25 | 0.00 | 0.00 | 0.00 |
June | 109.57 | 29.33 | 80.24 | 149.69 | 41.41 | 0.00 | 0.00 | 0.00 |
July | 119.04 | 43.22 | 75.82 | 178.04 | 35.16 | 0.00 | 0.00 | 0.00 |
August | 126.91 | 58.31 | 68.60 | 193.56 | 33.22 | 0.00 | 0.00 | 0.00 |
September | 140.76 | 76.98 | 63.77 | 197.18 | 45.40 | 0.00 | 0.00 | 0.00 |
October | 127.33 | 77.95 | 49.37 | 157.82 | 67.09 | 0.00 | 0.00 | 0.00 |
November | 76.20 | 43.62 | 32.58 | 79.35 | 85.51 | 0.00 | 0.00 | 0.00 |
December | 79.75 | 51.57 | 28.18 | 83.01 | 107.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 112.03 | 54.52 | 57.51 | 141.22 | 68.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 75.35 | 29.33 | 28.18 | 70.32 | 33.22 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.76 | 77.95 | 84.18 | 197.18 | 108.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 21.52 | 0.00 | 21.52 | 0.30 | 161.04 | 0.00 | 0.00 | 0.00 |
February | 33.48 | 0.00 | 33.48 | 4.83 | 138.21 | 0.00 | 0.00 | 0.00 |
March | 49.34 | 0.00 | 49.34 | 18.88 | 106.64 | 0.00 | 0.00 | 0.00 |
April | 70.06 | 0.43 | 69.63 | 45.23 | 81.42 | 0.00 | 0.00 | 0.00 |
May | 89.88 | 2.70 | 87.19 | 74.43 | 63.69 | 0.00 | 0.00 | 0.00 |
June | 94.60 | 6.33 | 88.27 | 87.56 | 47.18 | 0.00 | 0.00 | 0.00 |
July | 90.04 | 7.25 | 82.79 | 94.48 | 41.54 | 0.00 | 0.00 | 0.00 |
August | 72.98 | 2.19 | 70.79 | 78.34 | 40.44 | 0.00 | 0.00 | 0.00 |
September | 56.49 | 0.04 | 56.45 | 44.78 | 62.62 | 0.00 | 0.00 | 0.00 |
October | 38.68 | 0.00 | 38.68 | 16.66 | 90.32 | 0.00 | 0.00 | 0.00 |
November | 24.36 | 0.00 | 24.36 | 2.79 | 122.46 | 0.00 | 0.00 | 0.00 |
December | 18.29 | 0.00 | 18.29 | 0.10 | 156.70 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.08 | 1.59 | 53.49 | 39.25 | 92.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.29 | 0.00 | 18.29 | 0.10 | 40.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 94.60 | 7.25 | 88.27 | 94.48 | 161.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.25 | 0.00 | 19.25 | 0.27 | 144.07 | 0.00 | 0.00 | 0.00 |
February | 29.96 | 0.00 | 29.96 | 4.32 | 123.66 | 0.00 | 0.00 | 0.00 |
March | 44.14 | 0.00 | 44.14 | 16.89 | 95.41 | 0.00 | 0.00 | 0.00 |
April | 62.68 | 0.39 | 62.30 | 40.47 | 72.85 | 0.00 | 0.00 | 0.00 |
May | 80.42 | 2.41 | 78.01 | 66.59 | 56.99 | 0.00 | 0.00 | 0.00 |
June | 84.63 | 5.66 | 78.97 | 78.34 | 42.21 | 0.00 | 0.00 | 0.00 |
July | 80.56 | 6.48 | 74.07 | 84.53 | 37.17 | 0.00 | 0.00 | 0.00 |
August | 65.30 | 1.96 | 63.34 | 70.09 | 36.19 | 0.00 | 0.00 | 0.00 |
September | 50.54 | 0.04 | 50.50 | 40.06 | 56.03 | 0.00 | 0.00 | 0.00 |
October | 34.60 | 0.00 | 34.60 | 14.91 | 80.81 | 0.00 | 0.00 | 0.00 |
November | 21.80 | 0.00 | 21.80 | 2.50 | 109.57 | 0.00 | 0.00 | 0.00 |
December | 16.36 | 0.00 | 16.36 | 0.09 | 140.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 49.28 | 1.42 | 47.86 | 35.11 | 82.73 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 16.36 | 0.00 | 16.36 | 0.09 | 36.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 84.63 | 6.48 | 78.97 | 84.53 | 144.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 281.32 | 167.35 | 113.97 | 243.32 | 416.30 | 0.00 | 0.00 | 0.00 |
February | 432.91 | 268.60 | 164.31 | 435.06 | 359.84 | 0.00 | 0.00 | 0.00 |
March | 459.23 | 242.79 | 216.43 | 490.74 | 299.40 | 0.00 | 0.00 | 0.00 |
April | 485.25 | 208.26 | 277.00 | 551.38 | 244.07 | 0.00 | 0.00 | 0.00 |
May | 452.11 | 137.83 | 314.28 | 522.46 | 199.70 | 0.00 | 0.00 | 0.00 |
June | 409.06 | 109.48 | 299.58 | 483.85 | 152.46 | 0.00 | 0.00 | 0.00 |
July | 444.42 | 161.37 | 283.05 | 579.78 | 134.48 | 0.00 | 0.00 | 0.00 |
August | 473.79 | 217.70 | 256.09 | 638.22 | 127.98 | 0.00 | 0.00 | 0.00 |
September | 525.49 | 287.41 | 238.08 | 665.52 | 182.46 | 0.00 | 0.00 | 0.00 |
October | 475.35 | 291.03 | 184.33 | 546.64 | 251.77 | 0.00 | 0.00 | 0.00 |
November | 284.48 | 162.84 | 121.64 | 271.66 | 328.12 | 0.00 | 0.00 | 0.00 |
December | 297.74 | 192.54 | 105.20 | 289.60 | 413.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 418.23 | 203.53 | 214.69 | 476.68 | 258.72 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 281.32 | 109.48 | 105.20 | 243.32 | 127.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 525.49 | 291.03 | 314.28 | 665.52 | 416.30 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102079E+10 | 0.607247E+09 | 0.413543E+09 | 0.904710E+09 | 0.136614E+10 |
February | 0.141883E+10 | 0.880309E+09 | 0.538522E+09 | 0.144286E+10 | 0.108351E+10 |
March | 0.166635E+10 | 0.881003E+09 | 0.785345E+09 | 0.179511E+10 | 0.998468E+09 |
April | 0.170398E+10 | 0.731303E+09 | 0.972674E+09 | 0.196437E+10 | 0.777568E+09 |
May | 0.164051E+10 | 0.500145E+09 | 0.114037E+10 | 0.194222E+10 | 0.639693E+09 |
June | 0.143641E+10 | 0.384441E+09 | 0.105197E+10 | 0.175971E+10 | 0.458393E+09 |
July | 0.161261E+10 | 0.585540E+09 | 0.102707E+10 | 0.215079E+10 | 0.420315E+09 |
August | 0.171918E+10 | 0.789956E+09 | 0.929228E+09 | 0.234704E+10 | 0.406070E+09 |
September | 0.184527E+10 | 0.100924E+10 | 0.836033E+09 | 0.234305E+10 | 0.582473E+09 |
October | 0.172485E+10 | 0.105602E+10 | 0.668837E+09 | 0.199345E+10 | 0.844130E+09 |
November | 0.998973E+09 | 0.571820E+09 | 0.427153E+09 | 0.967933E+09 | 0.104679E+10 |
December | 0.108037E+10 | 0.698661E+09 | 0.381712E+09 | 0.105965E+10 | 0.137139E+10 |
Annual Sum or Average | 0.178681E+11 | 0.869568E+10 | 0.917246E+10 | 0.206709E+11 | 0.999494E+10 |
Minimum of Months | 0.998973E+09 | 0.384441E+09 | 0.381712E+09 | 0.904710E+09 | 0.406070E+09 |
Maximum of Months | 0.184527E+10 | 0.105602E+10 | 0.114037E+10 | 0.234704E+10 | 0.137139E+10 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.287448E+10 | 0.170997E+10 | 0.116451E+10 | 0.250833E+10 | 0.397198E+10 |
February | 0.399533E+10 | 0.247889E+10 | 0.151644E+10 | 0.400813E+10 | 0.318222E+10 |
March | 0.469233E+10 | 0.248085E+10 | 0.221148E+10 | 0.498816E+10 | 0.299046E+10 |
April | 0.479829E+10 | 0.205930E+10 | 0.273898E+10 | 0.544990E+10 | 0.236078E+10 |
May | 0.461958E+10 | 0.140838E+10 | 0.321120E+10 | 0.537820E+10 | 0.196930E+10 |
June | 0.404484E+10 | 0.108256E+10 | 0.296227E+10 | 0.485112E+10 | 0.145398E+10 |
July | 0.454101E+10 | 0.164884E+10 | 0.289217E+10 | 0.596381E+10 | 0.133206E+10 |
August | 0.484111E+10 | 0.222446E+10 | 0.261664E+10 | 0.652316E+10 | 0.129727E+10 |
September | 0.519617E+10 | 0.284196E+10 | 0.235421E+10 | 0.652216E+10 | 0.180869E+10 |
October | 0.485707E+10 | 0.297367E+10 | 0.188340E+10 | 0.554110E+10 | 0.257592E+10 |
November | 0.281304E+10 | 0.161021E+10 | 0.120283E+10 | 0.268032E+10 | 0.309726E+10 |
December | 0.304226E+10 | 0.196738E+10 | 0.107488E+10 | 0.294443E+10 | 0.399904E+10 |
Annual Sum or Average | 0.503155E+11 | 0.244865E+11 | 0.258290E+11 | 0.573588E+11 | 0.300390E+11 |
Minimum of Months | 0.281304E+10 | 0.108256E+10 | 0.107488E+10 | 0.250833E+10 | 0.129727E+10 |
Maximum of Months | 0.519617E+10 | 0.297367E+10 | 0.321120E+10 | 0.652316E+10 | 0.399904E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.373411E+10 | 0.222134E+10 | 0.151276E+10 | 0.327949E+10 | 0.551163E+10 |
February | 0.519017E+10 | 0.322022E+10 | 0.196994E+10 | 0.526553E+10 | 0.439041E+10 |
March | 0.609560E+10 | 0.322276E+10 | 0.287284E+10 | 0.656445E+10 | 0.414259E+10 |
April | 0.623325E+10 | 0.267515E+10 | 0.355810E+10 | 0.717549E+10 | 0.326652E+10 |
May | 0.600109E+10 | 0.182956E+10 | 0.417153E+10 | 0.706830E+10 | 0.274973E+10 |
June | 0.525447E+10 | 0.140631E+10 | 0.384816E+10 | 0.636049E+10 | 0.203906E+10 |
July | 0.589903E+10 | 0.214194E+10 | 0.375709E+10 | 0.785141E+10 | 0.185386E+10 |
August | 0.628888E+10 | 0.288971E+10 | 0.339917E+10 | 0.859266E+10 | 0.179019E+10 |
September | 0.675012E+10 | 0.369187E+10 | 0.305826E+10 | 0.858522E+10 | 0.249996E+10 |
October | 0.630961E+10 | 0.386297E+10 | 0.244665E+10 | 0.728462E+10 | 0.358031E+10 |
November | 0.365430E+10 | 0.209175E+10 | 0.156255E+10 | 0.349668E+10 | 0.433748E+10 |
December | 0.395207E+10 | 0.255574E+10 | 0.139632E+10 | 0.385700E+10 | 0.555093E+10 |
Annual Sum or Average | 0.653627E+11 | 0.318093E+11 | 0.335534E+11 | 0.753813E+11 | 0.417127E+11 |
Minimum of Months | 0.365430E+10 | 0.140631E+10 | 0.139632E+10 | 0.327949E+10 | 0.179019E+10 |
Maximum of Months | 0.675012E+10 | 0.386297E+10 | 0.417153E+10 | 0.859266E+10 | 0.555093E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201828E+09 | 0.120063E+09 | 81764855.83 | 0.180826E+09 | 0.274427E+09 |
February | 0.280528E+09 | 0.174052E+09 | 0.106476E+09 | 0.286897E+09 | 0.217552E+09 |
March | 0.329467E+09 | 0.174190E+09 | 0.155277E+09 | 0.355781E+09 | 0.200952E+09 |
April | 0.336907E+09 | 0.144591E+09 | 0.192316E+09 | 0.385917E+09 | 0.157701E+09 |
May | 0.324360E+09 | 98887279.29 | 0.225472E+09 | 0.378616E+09 | 0.129649E+09 |
June | 0.284005E+09 | 76010646.67 | 0.207994E+09 | 0.342499E+09 | 91166134.92 |
July | 0.318843E+09 | 0.115771E+09 | 0.203072E+09 | 0.423025E+09 | 80530755.24 |
August | 0.339914E+09 | 0.156188E+09 | 0.183726E+09 | 0.465284E+09 | 74866181.28 |
September | 0.364844E+09 | 0.199544E+09 | 0.165299E+09 | 0.466055E+09 | 0.112948E+09 |
October | 0.341034E+09 | 0.208792E+09 | 0.132241E+09 | 0.395688E+09 | 0.166977E+09 |
November | 0.197514E+09 | 0.113059E+09 | 84455881.64 | 0.193228E+09 | 0.208759E+09 |
December | 0.213609E+09 | 0.138137E+09 | 75471285.47 | 0.211915E+09 | 0.273144E+09 |
Annual Sum or Average | 0.353285E+10 | 0.171929E+10 | 0.181357E+10 | 0.408573E+10 | 0.198867E+10 |
Minimum of Months | 0.197514E+09 | 76010646.67 | 75471285.47 | 0.180826E+09 | 74866181.28 |
Maximum of Months | 0.364844E+09 | 0.208792E+09 | 0.225472E+09 | 0.466055E+09 | 0.274427E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.144896E+09 | 43103720.32 | 0.101793E+09 | 59455203.86 | 0.555206E+09 |
February | 0.233458E+09 | 87642964.17 | 0.145815E+09 | 0.158573E+09 | 0.434529E+09 |
March | 0.362082E+09 | 0.122417E+09 | 0.239665E+09 | 0.304565E+09 | 0.382883E+09 |
April | 0.532452E+09 | 0.203310E+09 | 0.329141E+09 | 0.547038E+09 | 0.287444E+09 |
May | 0.709342E+09 | 0.288786E+09 | 0.420557E+09 | 0.805614E+09 | 0.234381E+09 |
June | 0.658756E+09 | 0.255289E+09 | 0.403468E+09 | 0.772255E+09 | 0.164835E+09 |
July | 0.841502E+09 | 0.442194E+09 | 0.399308E+09 | 0.107781E+10 | 0.145988E+09 |
August | 0.696429E+09 | 0.355219E+09 | 0.341210E+09 | 0.905615E+09 | 0.137607E+09 |
September | 0.550628E+09 | 0.264873E+09 | 0.285755E+09 | 0.656978E+09 | 0.210751E+09 |
October | 0.325383E+09 | 0.133761E+09 | 0.191622E+09 | 0.305214E+09 | 0.322140E+09 |
November | 0.155943E+09 | 44331374.38 | 0.111611E+09 | 87424008.34 | 0.413590E+09 |
December | 0.136017E+09 | 47217705.85 | 88798972.09 | 71732635.66 | 0.549304E+09 |
Annual Sum or Average | 0.534689E+10 | 0.228814E+10 | 0.305874E+10 | 0.575228E+10 | 0.383866E+10 |
Minimum of Months | 0.136017E+09 | 43103720.32 | 88798972.09 | 59455203.86 | 0.137607E+09 |
Maximum of Months | 0.841502E+09 | 0.442194E+09 | 0.420557E+09 | 0.107781E+10 | 0.555206E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 45510498.67 | 0.00 | 45510498.67 | 1452376.70 | 0.306961E+09 |
February | 63962484.45 | 0.00 | 63962484.45 | 12474701.33 | 0.240092E+09 |
March | 0.104345E+09 | 340.22 | 0.104345E+09 | 46141517.03 | 0.208351E+09 |
April | 0.143391E+09 | 882204.25 | 0.142509E+09 | 96990988.13 | 0.154702E+09 |
May | 0.190097E+09 | 5707817.87 | 0.184389E+09 | 0.157972E+09 | 0.124705E+09 |
June | 0.193607E+09 | 12952148.54 | 0.180655E+09 | 0.181633E+09 | 87765174.34 |
July | 0.190420E+09 | 15329272.49 | 0.175090E+09 | 0.199882E+09 | 80378884.59 |
August | 0.154354E+09 | 4635653.25 | 0.149719E+09 | 0.170254E+09 | 74812507.59 |
September | 0.115615E+09 | 86607.59 | 0.115529E+09 | 94685137.33 | 0.118473E+09 |
October | 81798730.60 | 0.00 | 81798730.60 | 40937941.19 | 0.174544E+09 |
November | 49862977.19 | 0.00 | 49862977.19 | 8111109.51 | 0.225608E+09 |
December | 38672190.66 | 0.00 | 38672190.66 | 741217.46 | 0.299162E+09 |
Annual Sum or Average | 0.137164E+10 | 39594044.20 | 0.133204E+10 | 0.101128E+10 | 0.209555E+10 |
Minimum of Months | 38672190.66 | 0.00 | 38672190.66 | 741217.46 | 74812507.59 |
Maximum of Months | 0.193607E+09 | 15329272.49 | 0.184389E+09 | 0.199882E+09 | 0.306961E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.144896E+09 | 43103720.32 | 0.101793E+09 | 63592030.41 | 0.549699E+09 |
February | 0.233458E+09 | 87642964.17 | 0.145815E+09 | 0.165957E+09 | 0.427855E+09 |
March | 0.362082E+09 | 0.122417E+09 | 0.239665E+09 | 0.314510E+09 | 0.377649E+09 |
April | 0.532452E+09 | 0.203310E+09 | 0.329141E+09 | 0.554255E+09 | 0.286020E+09 |
May | 0.709342E+09 | 0.288786E+09 | 0.420557E+09 | 0.801658E+09 | 0.238731E+09 |
June | 0.658756E+09 | 0.255289E+09 | 0.403468E+09 | 0.764950E+09 | 0.171931E+09 |
July | 0.841502E+09 | 0.442194E+09 | 0.399308E+09 | 0.106539E+10 | 0.157603E+09 |
August | 0.696429E+09 | 0.355219E+09 | 0.341210E+09 | 0.902334E+09 | 0.146097E+09 |
September | 0.550628E+09 | 0.264873E+09 | 0.285755E+09 | 0.656826E+09 | 0.216668E+09 |
October | 0.325383E+09 | 0.133761E+09 | 0.191622E+09 | 0.314147E+09 | 0.317688E+09 |
November | 0.155943E+09 | 44331374.38 | 0.111611E+09 | 92020331.23 | 0.408690E+09 |
December | 0.136017E+09 | 47217705.85 | 88798972.09 | 76445599.53 | 0.543139E+09 |
Annual Sum or Average | 0.534689E+10 | 0.228814E+10 | 0.305874E+10 | 0.577208E+10 | 0.384177E+10 |
Minimum of Months | 0.136017E+09 | 43103720.32 | 88798972.09 | 63592030.41 | 0.146097E+09 |
Maximum of Months | 0.841502E+09 | 0.442194E+09 | 0.420557E+09 | 0.106539E+10 | 0.549699E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.161430E+09 | 96031370.32 | 65398878.59 | 0.138345E+09 | 0.236559E+09 |
February | 0.224378E+09 | 0.139214E+09 | 85163535.41 | 0.212559E+09 | 0.216680E+09 |
March | 0.263521E+09 | 0.139324E+09 | 0.124197E+09 | 0.258003E+09 | 0.229742E+09 |
April | 0.269472E+09 | 0.115650E+09 | 0.153822E+09 | 0.277818E+09 | 0.185456E+09 |
May | 0.259436E+09 | 79094093.75 | 0.180342E+09 | 0.270975E+09 | 0.158277E+09 |
June | 0.227159E+09 | 60796426.56 | 0.166362E+09 | 0.239743E+09 | 0.120867E+09 |
July | 0.255024E+09 | 92598617.16 | 0.162425E+09 | 0.305305E+09 | 0.111608E+09 |
August | 0.271877E+09 | 0.124925E+09 | 0.146952E+09 | 0.338731E+09 | 0.108565E+09 |
September | 0.291817E+09 | 0.159604E+09 | 0.132213E+09 | 0.344240E+09 | 0.144658E+09 |
October | 0.272773E+09 | 0.167001E+09 | 0.105772E+09 | 0.288663E+09 | 0.204107E+09 |
November | 0.157980E+09 | 90428875.66 | 67551271.18 | 0.136284E+09 | 0.229820E+09 |
December | 0.170853E+09 | 0.110488E+09 | 60365023.40 | 0.159073E+09 | 0.254175E+09 |
Annual Sum or Average | 0.282572E+10 | 0.137516E+10 | 0.145056E+10 | 0.296974E+10 | 0.220052E+10 |
Minimum of Months | 0.157980E+09 | 60796426.56 | 60365023.40 | 0.136284E+09 | 0.108565E+09 |
Maximum of Months | 0.291817E+09 | 0.167001E+09 | 0.180342E+09 | 0.344240E+09 | 0.254175E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 36413225.08 | 0.00 | 36413225.08 | 701082.84 | 0.260699E+09 |
February | 51176770.43 | 0.00 | 51176770.43 | 8639307.11 | 0.201232E+09 |
March | 83487367.90 | 272.21 | 83487095.69 | 35761776.39 | 0.172401E+09 |
April | 0.114728E+09 | 705856.95 | 0.114022E+09 | 80075429.18 | 0.124862E+09 |
May | 0.152098E+09 | 4566859.58 | 0.147531E+09 | 0.134657E+09 | 97864401.29 |
June | 0.154906E+09 | 10363092.34 | 0.144543E+09 | 0.154022E+09 | 67958831.48 |
July | 0.152356E+09 | 12265043.58 | 0.140091E+09 | 0.172989E+09 | 59434891.13 |
August | 0.123500E+09 | 3709014.18 | 0.119791E+09 | 0.145977E+09 | 55768778.77 |
September | 92504439.09 | 69295.25 | 92435143.84 | 81808772.32 | 90686870.81 |
October | 65447658.79 | 0.00 | 65447658.79 | 32680784.65 | 0.143225E+09 |
November | 39895669.45 | 0.00 | 39895669.45 | 5412035.22 | 0.191644E+09 |
December | 30941853.50 | 0.00 | 30941853.50 | 287529.25 | 0.253911E+09 |
Annual Sum or Average | 0.109745E+10 | 31679434.09 | 0.106578E+10 | 0.853012E+09 | 0.171969E+10 |
Minimum of Months | 30941853.50 | 0.00 | 30941853.50 | 287529.25 | 55768778.77 |
Maximum of Months | 0.154906E+09 | 12265043.58 | 0.147531E+09 | 0.172989E+09 | 0.260699E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.135983E+09 | 34077660.85 | 0.101905E+09 | 43858507.90 | 0.550094E+09 |
February | 0.226258E+09 | 80141237.88 | 0.146117E+09 | 0.140954E+09 | 0.426173E+09 |
March | 0.375425E+09 | 0.136136E+09 | 0.239289E+09 | 0.309548E+09 | 0.370193E+09 |
April | 0.561134E+09 | 0.232853E+09 | 0.328282E+09 | 0.573603E+09 | 0.276050E+09 |
May | 0.617389E+09 | 0.214964E+09 | 0.402426E+09 | 0.674425E+09 | 0.227318E+09 |
June | 0.715100E+09 | 0.311241E+09 | 0.403858E+09 | 0.846192E+09 | 0.158077E+09 |
July | 0.689138E+09 | 0.309834E+09 | 0.379304E+09 | 0.859429E+09 | 0.134054E+09 |
August | 0.676486E+09 | 0.338392E+09 | 0.338094E+09 | 0.869704E+09 | 0.128268E+09 |
September | 0.484815E+09 | 0.223992E+09 | 0.260822E+09 | 0.554145E+09 | 0.201457E+09 |
October | 0.327581E+09 | 0.139970E+09 | 0.187611E+09 | 0.301337E+09 | 0.313530E+09 |
November | 0.155138E+09 | 43931896.31 | 0.111207E+09 | 81730010.20 | 0.407831E+09 |
December | 0.131139E+09 | 42150042.10 | 88988570.02 | 57488559.01 | 0.539606E+09 |
Annual Sum or Average | 0.509559E+10 | 0.210768E+10 | 0.298790E+10 | 0.531241E+10 | 0.373265E+10 |
Minimum of Months | 0.131139E+09 | 34077660.85 | 88988570.02 | 43858507.90 | 0.128268E+09 |
Maximum of Months | 0.715100E+09 | 0.338392E+09 | 0.403858E+09 | 0.869704E+09 | 0.550094E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201828E+09 | 0.120063E+09 | 81764855.83 | 0.180747E+09 | 0.274048E+09 |
February | 0.280528E+09 | 0.174052E+09 | 0.106476E+09 | 0.286224E+09 | 0.217042E+09 |
March | 0.329467E+09 | 0.174190E+09 | 0.155277E+09 | 0.353781E+09 | 0.200425E+09 |
April | 0.336907E+09 | 0.144591E+09 | 0.192316E+09 | 0.383050E+09 | 0.157159E+09 |
May | 0.324360E+09 | 98887279.29 | 0.225472E+09 | 0.378285E+09 | 0.127986E+09 |
June | 0.284005E+09 | 76010646.67 | 0.207994E+09 | 0.339783E+09 | 90383887.47 |
July | 0.318843E+09 | 0.115771E+09 | 0.203072E+09 | 0.423153E+09 | 78376875.04 |
August | 0.339914E+09 | 0.156188E+09 | 0.183726E+09 | 0.463936E+09 | 73770782.17 |
September | 0.364844E+09 | 0.199544E+09 | 0.165299E+09 | 0.465693E+09 | 0.111071E+09 |
October | 0.341034E+09 | 0.208792E+09 | 0.132241E+09 | 0.394395E+09 | 0.166207E+09 |
November | 0.197514E+09 | 0.113059E+09 | 84455881.64 | 0.192897E+09 | 0.208417E+09 |
December | 0.213609E+09 | 0.138137E+09 | 75471285.47 | 0.211809E+09 | 0.272707E+09 |
Annual Sum or Average | 0.353285E+10 | 0.171929E+10 | 0.181357E+10 | 0.407375E+10 | 0.197759E+10 |
Minimum of Months | 0.197514E+09 | 76010646.67 | 75471285.47 | 0.180747E+09 | 73770782.17 |
Maximum of Months | 0.364844E+09 | 0.208792E+09 | 0.225472E+09 | 0.465693E+09 | 0.274048E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 45510498.67 | 0.00 | 45510498.67 | 1395287.77 | 0.306713E+09 |
February | 63962484.45 | 0.00 | 63962484.45 | 12209123.12 | 0.239712E+09 |
March | 0.104345E+09 | 340.22 | 0.104345E+09 | 44437029.24 | 0.207955E+09 |
April | 0.143391E+09 | 882204.25 | 0.142509E+09 | 94374985.47 | 0.154391E+09 |
May | 0.190097E+09 | 5707817.87 | 0.184389E+09 | 0.159993E+09 | 0.121826E+09 |
June | 0.193607E+09 | 12952148.54 | 0.180655E+09 | 0.180312E+09 | 86035048.78 |
July | 0.190420E+09 | 15329272.49 | 0.175090E+09 | 0.202962E+09 | 75903204.53 |
August | 0.154354E+09 | 4635653.25 | 0.149719E+09 | 0.168181E+09 | 72579364.49 |
September | 0.115615E+09 | 86607.59 | 0.115529E+09 | 95541387.06 | 0.114357E+09 |
October | 81798730.60 | 0.00 | 81798730.60 | 39632118.00 | 0.173303E+09 |
November | 49862977.19 | 0.00 | 49862977.19 | 7799821.04 | 0.225091E+09 |
December | 38672190.66 | 0.00 | 38672190.66 | 656315.62 | 0.298762E+09 |
Annual Sum or Average | 0.137164E+10 | 39594044.20 | 0.133204E+10 | 0.100749E+10 | 0.207663E+10 |
Minimum of Months | 38672190.66 | 0.00 | 38672190.66 | 656315.62 | 72579364.49 |
Maximum of Months | 0.193607E+09 | 15329272.49 | 0.184389E+09 | 0.202962E+09 | 0.306713E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.135983E+09 | 34077660.85 | 0.101905E+09 | 45486514.44 | 0.542091E+09 |
February | 0.226258E+09 | 80141237.88 | 0.146117E+09 | 0.145838E+09 | 0.416307E+09 |
March | 0.375425E+09 | 0.136136E+09 | 0.239289E+09 | 0.318933E+09 | 0.363977E+09 |
April | 0.561134E+09 | 0.232853E+09 | 0.328282E+09 | 0.580678E+09 | 0.274010E+09 |
May | 0.617389E+09 | 0.214964E+09 | 0.402426E+09 | 0.676260E+09 | 0.229624E+09 |
June | 0.715100E+09 | 0.311241E+09 | 0.403858E+09 | 0.843434E+09 | 0.164324E+09 |
July | 0.689138E+09 | 0.309834E+09 | 0.379304E+09 | 0.854382E+09 | 0.142311E+09 |
August | 0.676486E+09 | 0.338392E+09 | 0.338094E+09 | 0.865999E+09 | 0.135251E+09 |
September | 0.484815E+09 | 0.223992E+09 | 0.260822E+09 | 0.558255E+09 | 0.204031E+09 |
October | 0.327581E+09 | 0.139970E+09 | 0.187611E+09 | 0.310303E+09 | 0.307941E+09 |
November | 0.155138E+09 | 43931896.31 | 0.111207E+09 | 84775710.01 | 0.400916E+09 |
December | 0.131139E+09 | 42150042.10 | 88988570.02 | 59563543.34 | 0.530559E+09 |
Annual Sum or Average | 0.509559E+10 | 0.210768E+10 | 0.298790E+10 | 0.534391E+10 | 0.371134E+10 |
Minimum of Months | 0.131139E+09 | 34077660.85 | 88988570.02 | 45486514.44 | 0.135251E+09 |
Maximum of Months | 0.715100E+09 | 0.338392E+09 | 0.403858E+09 | 0.865999E+09 | 0.542091E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 57636175.01 | 0.00 | 57636175.01 | 1031262.33 | 0.421357E+09 |
February | 81004450.75 | 0.00 | 81004450.75 | 13548855.00 | 0.325125E+09 |
March | 0.132147E+09 | 430.86 | 0.132146E+09 | 56480410.04 | 0.277698E+09 |
April | 0.181596E+09 | 1117256.01 | 0.180479E+09 | 0.126600E+09 | 0.204484E+09 |
May | 0.240746E+09 | 7228591.19 | 0.233517E+09 | 0.211014E+09 | 0.166062E+09 |
June | 0.245191E+09 | 16403078.89 | 0.228788E+09 | 0.240512E+09 | 0.117293E+09 |
July | 0.241154E+09 | 19413556.39 | 0.221741E+09 | 0.267092E+09 | 0.106303E+09 |
August | 0.195480E+09 | 5870762.35 | 0.189609E+09 | 0.221266E+09 | 0.103782E+09 |
September | 0.146419E+09 | 109683.05 | 0.146310E+09 | 0.124094E+09 | 0.158625E+09 |
October | 0.103593E+09 | 0.00 | 0.103593E+09 | 49747864.10 | 0.235976E+09 |
November | 63148314.43 | 0.00 | 63148314.43 | 8732723.81 | 0.307755E+09 |
December | 48975889.39 | 0.00 | 48975889.39 | 390958.80 | 0.410534E+09 |
Annual Sum or Average | 0.173709E+10 | 50143358.74 | 0.168695E+10 | 0.132051E+10 | 0.283499E+10 |
Minimum of Months | 48975889.39 | 0.00 | 48975889.39 | 390958.80 | 0.103782E+09 |
Maximum of Months | 0.245191E+09 | 19413556.39 | 0.233517E+09 | 0.267092E+09 | 0.421357E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 21247080.64 | 0.00 | 21247080.64 | 380166.00 | 0.155329E+09 |
February | 29861594.68 | 0.00 | 29861594.68 | 4994668.97 | 0.119854E+09 |
March | 48714796.18 | 158.83 | 48714637.34 | 20821017.81 | 0.102371E+09 |
April | 66943790.08 | 411866.83 | 66531923.25 | 46670115.43 | 75381419.73 |
May | 88748888.58 | 2664758.02 | 86084130.55 | 77788626.88 | 61217350.19 |
June | 90387603.67 | 6046854.08 | 84340749.59 | 88662846.77 | 43239141.08 |
July | 88899508.73 | 7156640.74 | 81742867.99 | 98461108.64 | 39187619.84 |
August | 72062069.48 | 2164206.09 | 69897863.39 | 81567732.36 | 38258417.46 |
September | 53976248.26 | 40433.71 | 53935814.54 | 45746164.56 | 58475571.00 |
October | 38188643.85 | 0.00 | 38188643.85 | 18339122.60 | 86990582.86 |
November | 23279083.47 | 0.00 | 23279083.47 | 3219243.59 | 0.113451E+09 |
December | 18054540.76 | 0.00 | 18054540.76 | 144123.60 | 0.151340E+09 |
Annual Sum or Average | 0.640364E+09 | 18484918.30 | 0.621879E+09 | 0.486795E+09 | 0.104510E+10 |
Minimum of Months | 18054540.76 | 0.00 | 18054540.76 | 144123.60 | 38258417.46 |
Maximum of Months | 90387603.67 | 7156640.74 | 86084130.55 | 98461108.64 | 0.155329E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 94172104.10 | 56020951.86 | 38151152.24 | 82969963.84 | 0.135950E+09 |
February | 0.130893E+09 | 81212052.17 | 49681081.31 | 0.133994E+09 | 0.106146E+09 |
March | 0.153728E+09 | 81276128.21 | 72451757.76 | 0.167647E+09 | 97280864.31 |
April | 0.157199E+09 | 67465641.93 | 89733781.59 | 0.183123E+09 | 76336329.34 |
May | 0.151345E+09 | 46140406.03 | 0.105205E+09 | 0.179854E+09 | 64754229.76 |
June | 0.132516E+09 | 35466261.44 | 97049331.00 | 0.162181E+09 | 47076418.22 |
July | 0.148771E+09 | 54018417.70 | 94752617.30 | 0.199819E+09 | 42754374.86 |
August | 0.158603E+09 | 72876646.06 | 85725869.59 | 0.218619E+09 | 40863103.35 |
September | 0.170235E+09 | 93106622.21 | 77128015.79 | 0.219262E+09 | 57619923.80 |
October | 0.159125E+09 | 97421719.72 | 61703299.94 | 0.186222E+09 | 82044615.43 |
November | 92159449.27 | 52752675.23 | 39406774.04 | 89881046.14 | 0.103022E+09 |
December | 99668866.61 | 64454268.94 | 35214597.67 | 98413784.82 | 0.135349E+09 |
Annual Sum or Average | 0.164841E+10 | 0.802212E+09 | 0.846203E+09 | 0.192199E+10 | 0.989197E+09 |
Minimum of Months | 92159449.27 | 35466261.44 | 35214597.67 | 82969963.84 | 40863103.35 |
Maximum of Months | 0.170235E+09 | 97421719.72 | 0.105205E+09 | 0.219262E+09 | 0.135950E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.255602E+09 | 0.152052E+09 | 0.103550E+09 | 0.225197E+09 | 0.368995E+09 |
February | 0.355271E+09 | 0.220426E+09 | 0.134845E+09 | 0.363688E+09 | 0.288102E+09 |
March | 0.417249E+09 | 0.220600E+09 | 0.196649E+09 | 0.455029E+09 | 0.264040E+09 |
April | 0.426671E+09 | 0.183116E+09 | 0.243556E+09 | 0.497034E+09 | 0.207192E+09 |
May | 0.410781E+09 | 0.125234E+09 | 0.285547E+09 | 0.488159E+09 | 0.175756E+09 |
June | 0.359674E+09 | 96262688.00 | 0.263412E+09 | 0.440191E+09 | 0.127775E+09 |
July | 0.403795E+09 | 0.146617E+09 | 0.257178E+09 | 0.542349E+09 | 0.116044E+09 |
August | 0.430480E+09 | 0.197802E+09 | 0.232678E+09 | 0.593377E+09 | 0.110911E+09 |
September | 0.462052E+09 | 0.252710E+09 | 0.209341E+09 | 0.595121E+09 | 0.156392E+09 |
October | 0.431898E+09 | 0.264422E+09 | 0.167475E+09 | 0.505446E+09 | 0.222686E+09 |
November | 0.250140E+09 | 0.143182E+09 | 0.106958E+09 | 0.243956E+09 | 0.279623E+09 |
December | 0.270522E+09 | 0.174942E+09 | 95579621.07 | 0.267115E+09 | 0.367365E+09 |
Annual Sum or Average | 0.447413E+10 | 0.217737E+10 | 0.229677E+10 | 0.521666E+10 | 0.268488E+10 |
Minimum of Months | 0.250140E+09 | 96262688.00 | 95579621.07 | 0.225197E+09 | 0.110911E+09 |
Maximum of Months | 0.462052E+09 | 0.264422E+09 | 0.285547E+09 | 0.595121E+09 | 0.368995E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201828E+09 | 0.120063E+09 | 81764855.83 | 0.181089E+09 | 0.272537E+09 |
February | 0.280528E+09 | 0.174052E+09 | 0.106476E+09 | 0.286185E+09 | 0.216203E+09 |
March | 0.329467E+09 | 0.174190E+09 | 0.155277E+09 | 0.353937E+09 | 0.199889E+09 |
April | 0.336907E+09 | 0.144591E+09 | 0.192316E+09 | 0.382554E+09 | 0.157493E+09 |
May | 0.324360E+09 | 98887279.29 | 0.225472E+09 | 0.374555E+09 | 0.129310E+09 |
June | 0.284005E+09 | 76010646.67 | 0.207994E+09 | 0.338478E+09 | 90750241.79 |
July | 0.318843E+09 | 0.115771E+09 | 0.203072E+09 | 0.418702E+09 | 80099182.56 |
August | 0.339914E+09 | 0.156188E+09 | 0.183726E+09 | 0.461797E+09 | 73910658.32 |
September | 0.364844E+09 | 0.199544E+09 | 0.165299E+09 | 0.463678E+09 | 0.111746E+09 |
October | 0.341034E+09 | 0.208792E+09 | 0.132241E+09 | 0.393847E+09 | 0.165337E+09 |
November | 0.197514E+09 | 0.113059E+09 | 84455881.64 | 0.193097E+09 | 0.206832E+09 |
December | 0.213609E+09 | 0.138137E+09 | 75471285.47 | 0.211958E+09 | 0.270736E+09 |
Annual Sum or Average | 0.353285E+10 | 0.171929E+10 | 0.181357E+10 | 0.405988E+10 | 0.197484E+10 |
Minimum of Months | 0.197514E+09 | 76010646.67 | 75471285.47 | 0.181089E+09 | 73910658.32 |
Maximum of Months | 0.364844E+09 | 0.208792E+09 | 0.225472E+09 | 0.463678E+09 | 0.272537E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.144896E+09 | 43103720.32 | 0.101793E+09 | 60215619.82 | 0.550169E+09 |
February | 0.233458E+09 | 87642964.17 | 0.145815E+09 | 0.158041E+09 | 0.430862E+09 |
March | 0.362082E+09 | 0.122417E+09 | 0.239665E+09 | 0.302199E+09 | 0.379971E+09 |
April | 0.532452E+09 | 0.203310E+09 | 0.329141E+09 | 0.540932E+09 | 0.286606E+09 |
May | 0.709342E+09 | 0.288786E+09 | 0.420557E+09 | 0.796978E+09 | 0.233346E+09 |
June | 0.658756E+09 | 0.255289E+09 | 0.403468E+09 | 0.763724E+09 | 0.163715E+09 |
July | 0.841502E+09 | 0.442194E+09 | 0.399308E+09 | 0.106805E+10 | 0.144792E+09 |
August | 0.696429E+09 | 0.355219E+09 | 0.341210E+09 | 0.898639E+09 | 0.135551E+09 |
September | 0.550628E+09 | 0.264873E+09 | 0.285755E+09 | 0.652520E+09 | 0.208047E+09 |
October | 0.325383E+09 | 0.133761E+09 | 0.191622E+09 | 0.303150E+09 | 0.318185E+09 |
November | 0.155943E+09 | 44331374.38 | 0.111611E+09 | 87718535.82 | 0.408651E+09 |
December | 0.136017E+09 | 47217705.85 | 88798972.09 | 72066364.35 | 0.542753E+09 |
Annual Sum or Average | 0.534689E+10 | 0.228814E+10 | 0.305874E+10 | 0.570423E+10 | 0.380265E+10 |
Minimum of Months | 0.136017E+09 | 43103720.32 | 88798972.09 | 60215619.82 | 0.135551E+09 |
Maximum of Months | 0.841502E+09 | 0.442194E+09 | 0.420557E+09 | 0.106805E+10 | 0.550169E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 45510498.67 | 0.00 | 45510498.67 | 1629391.18 | 0.303629E+09 |
February | 63962484.45 | 0.00 | 63962484.45 | 12829938.37 | 0.237893E+09 |
March | 0.104345E+09 | 340.22 | 0.104345E+09 | 46273675.64 | 0.206679E+09 |
April | 0.143391E+09 | 882204.25 | 0.142509E+09 | 95738927.06 | 0.154307E+09 |
May | 0.190097E+09 | 5707817.87 | 0.184389E+09 | 0.154550E+09 | 0.125374E+09 |
June | 0.193607E+09 | 12952148.54 | 0.180655E+09 | 0.177730E+09 | 88632382.24 |
July | 0.190420E+09 | 15329272.49 | 0.175090E+09 | 0.195577E+09 | 81925499.00 |
August | 0.154354E+09 | 4635653.25 | 0.149719E+09 | 0.168291E+09 | 74923397.51 |
September | 0.115615E+09 | 86607.59 | 0.115529E+09 | 93319055.98 | 0.118830E+09 |
October | 81798730.60 | 0.00 | 81798730.60 | 41452060.73 | 0.172169E+09 |
November | 49862977.19 | 0.00 | 49862977.19 | 8433231.91 | 0.222441E+09 |
December | 38672190.66 | 0.00 | 38672190.66 | 890728.17 | 0.294983E+09 |
Annual Sum or Average | 0.137164E+10 | 39594044.20 | 0.133204E+10 | 0.996714E+09 | 0.208179E+10 |
Minimum of Months | 38672190.66 | 0.00 | 38672190.66 | 890728.17 | 74923397.51 |
Maximum of Months | 0.193607E+09 | 15329272.49 | 0.184389E+09 | 0.195577E+09 | 0.303629E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.144896E+09 | 43103720.32 | 0.101793E+09 | 64457562.17 | 0.545087E+09 |
February | 0.233458E+09 | 87642964.17 | 0.145815E+09 | 0.166264E+09 | 0.424190E+09 |
March | 0.362082E+09 | 0.122417E+09 | 0.239665E+09 | 0.313073E+09 | 0.374405E+09 |
April | 0.532452E+09 | 0.203310E+09 | 0.329141E+09 | 0.548393E+09 | 0.285484E+09 |
May | 0.709342E+09 | 0.288786E+09 | 0.420557E+09 | 0.791104E+09 | 0.239960E+09 |
June | 0.658756E+09 | 0.255289E+09 | 0.403468E+09 | 0.753963E+09 | 0.173482E+09 |
July | 0.841502E+09 | 0.442194E+09 | 0.399308E+09 | 0.105243E+10 | 0.160359E+09 |
August | 0.696429E+09 | 0.355219E+09 | 0.341210E+09 | 0.894403E+09 | 0.146084E+09 |
September | 0.550628E+09 | 0.264873E+09 | 0.285755E+09 | 0.651211E+09 | 0.216586E+09 |
October | 0.325383E+09 | 0.133761E+09 | 0.191622E+09 | 0.313119E+09 | 0.313405E+09 |
November | 0.155943E+09 | 44331374.38 | 0.111611E+09 | 92822645.68 | 0.403601E+09 |
December | 0.136017E+09 | 47217705.85 | 88798972.09 | 77346950.85 | 0.536642E+09 |
Annual Sum or Average | 0.534689E+10 | 0.228814E+10 | 0.305874E+10 | 0.571858E+10 | 0.381928E+10 |
Minimum of Months | 0.136017E+09 | 43103720.32 | 88798972.09 | 64457562.17 | 0.146084E+09 |
Maximum of Months | 0.841502E+09 | 0.442194E+09 | 0.420557E+09 | 0.105243E+10 | 0.545087E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.296000E+09 | 0.176084E+09 | 0.119916E+09 | 0.254400E+09 | 0.416722E+09 |
February | 0.411421E+09 | 0.255264E+09 | 0.156157E+09 | 0.407661E+09 | 0.330418E+09 |
March | 0.483195E+09 | 0.255466E+09 | 0.227729E+09 | 0.508610E+09 | 0.303974E+09 |
April | 0.494106E+09 | 0.212057E+09 | 0.282050E+09 | 0.554993E+09 | 0.235024E+09 |
May | 0.475705E+09 | 0.145028E+09 | 0.330677E+09 | 0.549720E+09 | 0.189092E+09 |
June | 0.416521E+09 | 0.111477E+09 | 0.305044E+09 | 0.498545E+09 | 0.131527E+09 |
July | 0.467614E+09 | 0.169790E+09 | 0.297825E+09 | 0.619527E+09 | 0.113496E+09 |
August | 0.498517E+09 | 0.229065E+09 | 0.269452E+09 | 0.679845E+09 | 0.105908E+09 |
September | 0.535078E+09 | 0.292651E+09 | 0.242427E+09 | 0.677455E+09 | 0.164260E+09 |
October | 0.500159E+09 | 0.306214E+09 | 0.193945E+09 | 0.567688E+09 | 0.251990E+09 |
November | 0.289674E+09 | 0.165811E+09 | 0.123863E+09 | 0.274059E+09 | 0.317840E+09 |
December | 0.313277E+09 | 0.202591E+09 | 0.110686E+09 | 0.300873E+09 | 0.414172E+09 |
Annual Sum or Average | 0.518127E+10 | 0.252150E+10 | 0.265977E+10 | 0.589338E+10 | 0.297442E+10 |
Minimum of Months | 0.289674E+09 | 0.111477E+09 | 0.110686E+09 | 0.254400E+09 | 0.105908E+09 |
Maximum of Months | 0.535078E+09 | 0.306214E+09 | 0.330677E+09 | 0.679845E+09 | 0.416722E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.318561E+09 | 0.00 | 0.318561E+09 | 1369555.18 | 0.268481E+10 |
February | 0.447720E+09 | 0.00 | 0.447720E+09 | 45237698.48 | 0.210024E+10 |
March | 0.730390E+09 | 2381.43 | 0.730388E+09 | 0.223900E+09 | 0.181915E+10 |
April | 0.100370E+10 | 6175195.84 | 0.997525E+09 | 0.569268E+09 | 0.133676E+10 |
May | 0.133063E+10 | 39953211.88 | 0.129068E+10 | 0.101299E+10 | 0.105264E+10 |
June | 0.135520E+10 | 90661606.03 | 0.126454E+10 | 0.117320E+10 | 0.745944E+09 |
July | 0.133289E+10 | 0.107301E+09 | 0.122559E+10 | 0.134554E+10 | 0.665837E+09 |
August | 0.108044E+10 | 32448343.77 | 0.104799E+10 | 0.111680E+10 | 0.650114E+09 |
September | 0.809276E+09 | 606230.16 | 0.808670E+09 | 0.597949E+09 | 0.992684E+09 |
October | 0.572569E+09 | 0.00 | 0.572569E+09 | 0.200195E+09 | 0.155908E+10 |
November | 0.349028E+09 | 0.00 | 0.349028E+09 | 24289375.55 | 0.203553E+10 |
December | 0.270695E+09 | 0.00 | 0.270695E+09 | 359972.49 | 0.262315E+10 |
Annual Sum or Average | 0.960109E+10 | 0.277148E+09 | 0.932395E+10 | 0.631110E+10 | 0.182659E+11 |
Minimum of Months | 0.270695E+09 | 0.00 | 0.270695E+09 | 359972.49 | 0.650114E+09 |
Maximum of Months | 0.135520E+10 | 0.107301E+09 | 0.129068E+10 | 0.134554E+10 | 0.268481E+10 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.318561E+09 | 0.00 | 0.318561E+09 | 687444.12 | 0.277140E+10 |
February | 0.447720E+09 | 0.00 | 0.447720E+09 | 39623527.95 | 0.216995E+10 |
March | 0.730390E+09 | 2381.43 | 0.730388E+09 | 0.203067E+09 | 0.187318E+10 |
April | 0.100370E+10 | 6175195.84 | 0.997525E+09 | 0.541639E+09 | 0.137277E+10 |
May | 0.133063E+10 | 39953211.88 | 0.129068E+10 | 0.983699E+09 | 0.107824E+10 |
June | 0.135520E+10 | 90661606.03 | 0.126454E+10 | 0.114418E+10 | 0.765134E+09 |
July | 0.133289E+10 | 0.107301E+09 | 0.122559E+10 | 0.131997E+10 | 0.683892E+09 |
August | 0.108044E+10 | 32448343.77 | 0.104799E+10 | 0.109201E+10 | 0.669926E+09 |
September | 0.809276E+09 | 606230.16 | 0.808670E+09 | 0.576484E+09 | 0.102126E+10 |
October | 0.572569E+09 | 0.00 | 0.572569E+09 | 0.181873E+09 | 0.160999E+10 |
November | 0.349028E+09 | 0.00 | 0.349028E+09 | 20281496.21 | 0.210877E+10 |
December | 0.270695E+09 | 0.00 | 0.270695E+09 | 193458.55 | 0.270839E+10 |
Annual Sum or Average | 0.960109E+10 | 0.277148E+09 | 0.932395E+10 | 0.610372E+10 | 0.188329E+11 |
Minimum of Months | 0.270695E+09 | 0.00 | 0.270695E+09 | 193458.55 | 0.669926E+09 |
Maximum of Months | 0.135520E+10 | 0.107301E+09 | 0.129068E+10 | 0.131997E+10 | 0.277140E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 45510498.67 | 0.00 | 45510498.67 | 2507640.87 | 0.320722E+09 |
February | 63962484.45 | 0.00 | 63962484.45 | 17132774.31 | 0.252514E+09 |
March | 0.104345E+09 | 340.22 | 0.104345E+09 | 58807777.14 | 0.221013E+09 |
April | 0.143391E+09 | 882204.25 | 0.142509E+09 | 0.123450E+09 | 0.167674E+09 |
May | 0.190097E+09 | 5707817.87 | 0.184389E+09 | 0.203393E+09 | 0.136458E+09 |
June | 0.193607E+09 | 12952148.54 | 0.180655E+09 | 0.231902E+09 | 0.100798E+09 |
July | 0.190420E+09 | 15329272.49 | 0.175090E+09 | 0.261490E+09 | 89233609.95 |
August | 0.154354E+09 | 4635653.25 | 0.149719E+09 | 0.225152E+09 | 85341355.16 |
September | 0.115615E+09 | 86607.59 | 0.115529E+09 | 0.135354E+09 | 0.118432E+09 |
October | 81798730.60 | 0.00 | 81798730.60 | 56512198.14 | 0.185134E+09 |
November | 49862977.19 | 0.00 | 49862977.19 | 13614318.76 | 0.235982E+09 |
December | 38672190.66 | 0.00 | 38672190.66 | 1943138.12 | 0.311286E+09 |
Annual Sum or Average | 0.137164E+10 | 39594044.20 | 0.133204E+10 | 0.133126E+10 | 0.222459E+10 |
Minimum of Months | 38672190.66 | 0.00 | 38672190.66 | 1943138.12 | 85341355.16 |
Maximum of Months | 0.193607E+09 | 15329272.49 | 0.184389E+09 | 0.261490E+09 | 0.320722E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.271947E+09 | 68150481.81 | 0.203796E+09 | 0.103027E+09 | 0.115039E+10 |
February | 0.452484E+09 | 0.160271E+09 | 0.292213E+09 | 0.320194E+09 | 0.891940E+09 |
March | 0.750798E+09 | 0.272253E+09 | 0.478545E+09 | 0.702691E+09 | 0.787783E+09 |
April | 0.112219E+10 | 0.465673E+09 | 0.656516E+09 | 0.128285E+10 | 0.606372E+09 |
May | 0.123469E+10 | 0.429897E+09 | 0.804794E+09 | 0.151594E+10 | 0.512501E+09 |
June | 0.143010E+10 | 0.622438E+09 | 0.807660E+09 | 0.187742E+10 | 0.379979E+09 |
July | 0.137818E+10 | 0.619625E+09 | 0.758553E+09 | 0.192500E+10 | 0.330905E+09 |
August | 0.135288E+10 | 0.676736E+09 | 0.676140E+09 | 0.194835E+10 | 0.318585E+09 |
September | 0.969561E+09 | 0.447953E+09 | 0.521608E+09 | 0.127606E+10 | 0.432884E+09 |
October | 0.655116E+09 | 0.279920E+09 | 0.375195E+09 | 0.696927E+09 | 0.671488E+09 |
November | 0.310255E+09 | 87857553.18 | 0.222397E+09 | 0.199002E+09 | 0.857463E+09 |
December | 0.262259E+09 | 84294097.83 | 0.177965E+09 | 0.135277E+09 | 0.112552E+10 |
Annual Sum or Average | 0.101905E+11 | 0.421507E+10 | 0.597538E+10 | 0.119827E+11 | 0.806581E+10 |
Minimum of Months | 0.262259E+09 | 68150481.81 | 0.177965E+09 | 0.103027E+09 | 0.318585E+09 |
Maximum of Months | 0.143010E+10 | 0.676736E+09 | 0.807660E+09 | 0.194835E+10 | 0.115039E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201828E+09 | 0.120063E+09 | 81764855.83 | 0.188349E+09 | 0.290058E+09 |
February | 0.280528E+09 | 0.174052E+09 | 0.106476E+09 | 0.301485E+09 | 0.230128E+09 |
March | 0.329467E+09 | 0.174190E+09 | 0.155277E+09 | 0.378934E+09 | 0.213583E+09 |
April | 0.336907E+09 | 0.144591E+09 | 0.192316E+09 | 0.418115E+09 | 0.171216E+09 |
May | 0.324360E+09 | 98887279.29 | 0.225472E+09 | 0.421488E+09 | 0.142618E+09 |
June | 0.284005E+09 | 76010646.67 | 0.207994E+09 | 0.388009E+09 | 0.107347E+09 |
July | 0.318843E+09 | 0.115771E+09 | 0.203072E+09 | 0.476860E+09 | 94169567.48 |
August | 0.339914E+09 | 0.156188E+09 | 0.183726E+09 | 0.518424E+09 | 88985745.85 |
September | 0.364844E+09 | 0.199544E+09 | 0.165299E+09 | 0.511085E+09 | 0.117669E+09 |
October | 0.341034E+09 | 0.208792E+09 | 0.132241E+09 | 0.422692E+09 | 0.179698E+09 |
November | 0.197514E+09 | 0.113059E+09 | 84455881.64 | 0.205664E+09 | 0.221653E+09 |
December | 0.213609E+09 | 0.138137E+09 | 75471285.47 | 0.222329E+09 | 0.288424E+09 |
Annual Sum or Average | 0.353285E+10 | 0.171929E+10 | 0.181357E+10 | 0.445343E+10 | 0.214555E+10 |
Minimum of Months | 0.197514E+09 | 76010646.67 | 75471285.47 | 0.188349E+09 | 88985745.85 |
Maximum of Months | 0.364844E+09 | 0.208792E+09 | 0.225472E+09 | 0.518424E+09 | 0.290058E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 57636175.01 | 0.00 | 57636175.01 | 796179.67 | 0.431326E+09 |
February | 81004450.75 | 0.00 | 81004450.75 | 11673527.02 | 0.334357E+09 |
March | 0.132147E+09 | 430.86 | 0.132146E+09 | 50569662.86 | 0.285620E+09 |
April | 0.181596E+09 | 1117256.01 | 0.180479E+09 | 0.117248E+09 | 0.211042E+09 |
May | 0.240746E+09 | 7228591.19 | 0.233517E+09 | 0.199357E+09 | 0.170594E+09 |
June | 0.245191E+09 | 16403078.89 | 0.228788E+09 | 0.226958E+09 | 0.122283E+09 |
July | 0.241154E+09 | 19413556.39 | 0.221741E+09 | 0.253043E+09 | 0.111274E+09 |
August | 0.195480E+09 | 5870762.35 | 0.189609E+09 | 0.209836E+09 | 0.108325E+09 |
September | 0.146419E+09 | 109683.05 | 0.146310E+09 | 0.116070E+09 | 0.162308E+09 |
October | 0.103593E+09 | 0.00 | 0.103593E+09 | 44631873.54 | 0.241921E+09 |
November | 63148314.43 | 0.00 | 63148314.43 | 7235445.82 | 0.317427E+09 |
December | 48975889.39 | 0.00 | 48975889.39 | 271103.97 | 0.419713E+09 |
Annual Sum or Average | 0.173709E+10 | 50143358.74 | 0.168695E+10 | 0.123769E+10 | 0.291619E+10 |
Minimum of Months | 48975889.39 | 0.00 | 48975889.39 | 271103.97 | 0.108325E+09 |
Maximum of Months | 0.245191E+09 | 19413556.39 | 0.233517E+09 | 0.253043E+09 | 0.431326E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51567304.17 | 0.00 | 51567304.17 | 712344.96 | 0.385888E+09 |
February | 72474989.01 | 0.00 | 72474989.01 | 10444348.86 | 0.299149E+09 |
March | 0.118232E+09 | 385.50 | 0.118232E+09 | 45244868.97 | 0.255545E+09 |
April | 0.162475E+09 | 999613.19 | 0.161475E+09 | 0.104902E+09 | 0.188820E+09 |
May | 0.215396E+09 | 6467447.92 | 0.208929E+09 | 0.178365E+09 | 0.152631E+09 |
June | 0.219373E+09 | 14675896.84 | 0.204698E+09 | 0.203061E+09 | 0.109407E+09 |
July | 0.215762E+09 | 17369382.46 | 0.198392E+09 | 0.226398E+09 | 99557049.18 |
August | 0.174897E+09 | 5252593.31 | 0.169644E+09 | 0.187741E+09 | 96918732.83 |
September | 0.131002E+09 | 98133.84 | 0.130904E+09 | 0.103848E+09 | 0.145217E+09 |
October | 92684987.96 | 0.00 | 92684987.96 | 39932306.37 | 0.216448E+09 |
November | 56499036.19 | 0.00 | 56499036.19 | 6473580.79 | 0.283994E+09 |
December | 43818913.81 | 0.00 | 43818913.81 | 242557.75 | 0.375475E+09 |
Annual Sum or Average | 0.155418E+10 | 44863453.06 | 0.150932E+10 | 0.110737E+10 | 0.260905E+10 |
Minimum of Months | 43818913.81 | 0.00 | 43818913.81 | 242557.75 | 96918732.83 |
Maximum of Months | 0.219373E+09 | 17369382.46 | 0.208929E+09 | 0.226398E+09 | 0.385888E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.753484E+09 | 0.448231E+09 | 0.305253E+09 | 0.651712E+09 | 0.111501E+10 |
February | 0.104729E+10 | 0.649789E+09 | 0.397505E+09 | 0.105250E+10 | 0.870523E+09 |
March | 0.123000E+10 | 0.650301E+09 | 0.579696E+09 | 0.131439E+10 | 0.801901E+09 |
April | 0.125777E+10 | 0.539802E+09 | 0.717972E+09 | 0.142918E+10 | 0.632623E+09 |
May | 0.121093E+10 | 0.369176E+09 | 0.841756E+09 | 0.139936E+10 | 0.534887E+09 |
June | 0.106028E+10 | 0.283770E+09 | 0.776505E+09 | 0.125413E+10 | 0.395177E+09 |
July | 0.119034E+10 | 0.432209E+09 | 0.758129E+09 | 0.155287E+10 | 0.360193E+09 |
August | 0.126900E+10 | 0.583096E+09 | 0.685904E+09 | 0.170941E+10 | 0.342791E+09 |
September | 0.136207E+10 | 0.744959E+09 | 0.617112E+09 | 0.172503E+10 | 0.472949E+09 |
October | 0.127318E+10 | 0.779484E+09 | 0.493697E+09 | 0.146411E+10 | 0.674332E+09 |
November | 0.737380E+09 | 0.422081E+09 | 0.315299E+09 | 0.704131E+09 | 0.850493E+09 |
December | 0.797464E+09 | 0.515707E+09 | 0.281757E+09 | 0.775652E+09 | 0.110799E+10 |
Annual Sum or Average | 0.131892E+11 | 0.641861E+10 | 0.677058E+10 | 0.150325E+11 | 0.815888E+10 |
Minimum of Months | 0.737380E+09 | 0.283770E+09 | 0.281757E+09 | 0.651712E+09 | 0.342791E+09 |
Maximum of Months | 0.136207E+10 | 0.779484E+09 | 0.841756E+09 | 0.172503E+10 | 0.111501E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 337.78 | 510.06 | 381.12 | 226.72 | 154.40 | 0.00 | 0.00 |
February | 596.42 | 447.88 | 586.49 | 363.88 | 222.60 | 0.00 | 0.00 |
March | 670.22 | 372.79 | 622.14 | 328.93 | 293.21 | 0.00 | 0.00 |
April | 757.86 | 299.99 | 657.40 | 282.14 | 375.26 | 0.00 | 0.00 |
May | 725.14 | 238.83 | 612.50 | 186.73 | 425.76 | 0.00 | 0.00 |
June | 678.90 | 176.85 | 554.17 | 148.32 | 405.85 | 0.00 | 0.00 |
July | 803.01 | 156.93 | 602.08 | 218.62 | 383.46 | 0.00 | 0.00 |
August | 876.28 | 151.61 | 641.87 | 294.94 | 346.93 | 0.00 | 0.00 |
September | 903.95 | 224.72 | 711.91 | 389.37 | 322.54 | 0.00 | 0.00 |
October | 744.27 | 315.16 | 643.99 | 394.27 | 249.72 | 0.00 | 0.00 |
November | 373.43 | 403.85 | 385.41 | 220.61 | 164.80 | 0.00 | 0.00 |
December | 395.63 | 512.02 | 403.36 | 260.85 | 142.51 | 0.00 | 0.00 |
Annual Sum or Average | 655.47 | 316.94 | 566.59 | 275.74 | 290.86 | 0.00 | 0.00 |
Minimum of Months | 337.78 | 151.61 | 381.12 | 148.32 | 142.51 | 0.00 | 0.00 |
Maximum of Months | 903.95 | 512.02 | 711.91 | 394.27 | 425.76 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 936.50 | 1482.97 | 1073.21 | 638.43 | 434.78 | 0.00 | 0.00 |
February | 1656.80 | 1315.40 | 1651.51 | 1024.67 | 626.84 | 0.00 | 0.00 |
March | 1862.36 | 1116.51 | 1751.91 | 926.24 | 825.67 | 0.00 | 0.00 |
April | 2102.59 | 910.80 | 1851.19 | 794.48 | 1056.71 | 0.00 | 0.00 |
May | 2007.99 | 735.25 | 1724.75 | 525.83 | 1198.93 | 0.00 | 0.00 |
June | 1871.57 | 560.95 | 1560.51 | 417.65 | 1142.85 | 0.00 | 0.00 |
July | 2226.63 | 497.33 | 1695.42 | 615.61 | 1079.81 | 0.00 | 0.00 |
August | 2435.47 | 484.34 | 1807.46 | 830.52 | 976.94 | 0.00 | 0.00 |
September | 2516.26 | 697.80 | 2004.70 | 1096.43 | 908.26 | 0.00 | 0.00 |
October | 2068.81 | 961.74 | 1813.42 | 1110.24 | 703.18 | 0.00 | 0.00 |
November | 1034.07 | 1194.93 | 1085.28 | 621.22 | 464.06 | 0.00 | 0.00 |
December | 1099.33 | 1493.07 | 1135.85 | 734.54 | 401.31 | 0.00 | 0.00 |
Annual Sum or Average | 1818.84 | 952.53 | 1595.49 | 776.46 | 819.03 | 0.00 | 0.00 |
Minimum of Months | 936.50 | 484.34 | 1073.21 | 417.65 | 401.31 | 0.00 | 0.00 |
Maximum of Months | 2516.26 | 1493.07 | 2004.70 | 1110.24 | 1198.93 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1224.42 | 2057.81 | 1394.16 | 829.35 | 564.80 | 0.00 | 0.00 |
February | 2176.56 | 1814.82 | 2145.41 | 1331.11 | 814.30 | 0.00 | 0.00 |
March | 2450.89 | 1546.67 | 2275.84 | 1203.24 | 1072.60 | 0.00 | 0.00 |
April | 2768.32 | 1260.23 | 2404.80 | 1032.08 | 1372.72 | 0.00 | 0.00 |
May | 2639.00 | 1026.63 | 2240.55 | 683.08 | 1557.47 | 0.00 | 0.00 |
June | 2453.89 | 786.67 | 2027.19 | 542.56 | 1484.63 | 0.00 | 0.00 |
July | 2931.38 | 692.15 | 2202.45 | 799.71 | 1402.74 | 0.00 | 0.00 |
August | 3208.13 | 668.38 | 2348.00 | 1078.89 | 1269.10 | 0.00 | 0.00 |
September | 3312.20 | 964.49 | 2604.21 | 1424.33 | 1179.88 | 0.00 | 0.00 |
October | 2719.76 | 1336.74 | 2355.74 | 1442.27 | 913.47 | 0.00 | 0.00 |
November | 1349.03 | 1673.41 | 1409.84 | 807.00 | 602.84 | 0.00 | 0.00 |
December | 1440.04 | 2072.48 | 1475.53 | 954.20 | 521.33 | 0.00 | 0.00 |
Annual Sum or Average | 2390.33 | 1322.70 | 2072.64 | 1008.67 | 1063.97 | 0.00 | 0.00 |
Minimum of Months | 1224.42 | 668.38 | 1394.16 | 542.56 | 521.33 | 0.00 | 0.00 |
Maximum of Months | 3312.20 | 2072.48 | 2604.21 | 1442.27 | 1557.47 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 81.08 | 301.12 | 129.45 | 60.92 | 68.53 | 0.00 | 0.00 |
February | 176.40 | 261.81 | 212.46 | 108.17 | 104.29 | 0.00 | 0.00 |
March | 243.72 | 215.16 | 258.19 | 110.74 | 147.45 | 0.00 | 0.00 |
April | 358.27 | 170.08 | 335.40 | 134.22 | 201.18 | 0.00 | 0.00 |
May | 441.01 | 134.78 | 385.94 | 144.74 | 241.20 | 0.00 | 0.00 |
June | 429.32 | 98.01 | 363.72 | 127.82 | 235.90 | 0.00 | 0.00 |
July | 559.68 | 83.91 | 433.22 | 208.32 | 224.90 | 0.00 | 0.00 |
August | 511.44 | 78.94 | 386.93 | 190.94 | 195.99 | 0.00 | 0.00 |
September | 432.29 | 123.91 | 353.19 | 179.17 | 174.02 | 0.00 | 0.00 |
October | 259.23 | 180.16 | 248.81 | 127.89 | 120.92 | 0.00 | 0.00 |
November | 103.77 | 235.59 | 136.36 | 60.72 | 75.64 | 0.00 | 0.00 |
December | 98.08 | 299.24 | 130.54 | 69.20 | 61.33 | 0.00 | 0.00 |
Annual Sum or Average | 308.69 | 181.51 | 281.57 | 127.07 | 154.50 | 0.00 | 0.00 |
Minimum of Months | 81.08 | 78.94 | 129.45 | 60.72 | 61.33 | 0.00 | 0.00 |
Maximum of Months | 559.68 | 301.12 | 433.22 | 208.32 | 241.20 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 20.97 | 316.52 | 71.09 | 16.09 | 55.00 | 0.00 | 0.00 |
February | 70.33 | 272.68 | 122.94 | 36.23 | 86.71 | 0.00 | 0.00 |
March | 132.78 | 216.92 | 174.14 | 45.71 | 128.44 | 0.00 | 0.00 |
April | 250.21 | 168.99 | 260.74 | 78.78 | 181.96 | 0.00 | 0.00 |
May | 357.21 | 134.61 | 335.81 | 109.95 | 225.86 | 0.00 | 0.00 |
June | 363.50 | 98.49 | 328.84 | 103.49 | 225.36 | 0.00 | 0.00 |
July | 470.96 | 87.42 | 385.28 | 170.82 | 214.46 | 0.00 | 0.00 |
August | 399.59 | 81.61 | 317.65 | 134.35 | 183.29 | 0.00 | 0.00 |
September | 288.97 | 128.33 | 257.04 | 102.22 | 154.82 | 0.00 | 0.00 |
October | 131.09 | 182.29 | 152.02 | 49.94 | 102.08 | 0.00 | 0.00 |
November | 36.66 | 242.74 | 79.40 | 17.10 | 62.30 | 0.00 | 0.00 |
December | 26.02 | 311.68 | 65.22 | 17.63 | 47.59 | 0.00 | 0.00 |
Annual Sum or Average | 213.28 | 186.45 | 213.04 | 73.81 | 139.23 | 0.00 | 0.00 |
Minimum of Months | 20.97 | 81.61 | 65.22 | 16.09 | 47.59 | 0.00 | 0.00 |
Maximum of Months | 470.96 | 316.52 | 385.28 | 170.82 | 225.86 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 51.65 | 88.32 | 60.27 | 35.85 | 24.42 | 0.00 | 0.00 |
February | 87.86 | 89.57 | 92.75 | 57.55 | 35.20 | 0.00 | 0.00 |
March | 96.33 | 85.78 | 98.39 | 52.02 | 46.37 | 0.00 | 0.00 |
April | 107.18 | 71.55 | 103.96 | 44.62 | 59.34 | 0.00 | 0.00 |
May | 101.17 | 59.09 | 96.86 | 29.53 | 67.33 | 0.00 | 0.00 |
June | 92.49 | 46.63 | 87.64 | 23.46 | 64.18 | 0.00 | 0.00 |
July | 113.99 | 41.67 | 95.22 | 34.57 | 60.64 | 0.00 | 0.00 |
August | 126.47 | 40.53 | 101.51 | 46.64 | 54.87 | 0.00 | 0.00 |
September | 132.81 | 55.81 | 112.58 | 61.58 | 51.01 | 0.00 | 0.00 |
October | 107.77 | 76.20 | 101.84 | 62.35 | 39.49 | 0.00 | 0.00 |
November | 52.58 | 88.67 | 60.95 | 34.89 | 26.06 | 0.00 | 0.00 |
December | 59.39 | 94.90 | 63.79 | 41.25 | 22.54 | 0.00 | 0.00 |
Annual Sum or Average | 94.17 | 69.78 | 89.60 | 43.61 | 46.00 | 0.00 | 0.00 |
Minimum of Months | 51.65 | 40.53 | 60.27 | 23.46 | 22.54 | 0.00 | 0.00 |
Maximum of Months | 132.81 | 94.90 | 112.58 | 62.35 | 67.33 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.26 | 97.33 | 13.60 | 0.00 | 13.60 | 0.00 | 0.00 |
February | 3.57 | 83.18 | 21.15 | 0.00 | 21.15 | 0.00 | 0.00 |
March | 13.35 | 64.37 | 31.17 | 0.00 | 31.17 | 0.00 | 0.00 |
April | 30.89 | 48.17 | 44.26 | 0.27 | 43.99 | 0.00 | 0.00 |
May | 50.28 | 36.54 | 56.79 | 1.71 | 55.08 | 0.00 | 0.00 |
June | 59.42 | 26.22 | 59.76 | 4.00 | 55.77 | 0.00 | 0.00 |
July | 64.59 | 22.19 | 56.88 | 4.58 | 52.30 | 0.00 | 0.00 |
August | 54.50 | 20.82 | 46.11 | 1.38 | 44.72 | 0.00 | 0.00 |
September | 31.56 | 34.99 | 35.69 | 0.03 | 35.66 | 0.00 | 0.00 |
October | 12.20 | 53.47 | 24.44 | 0.00 | 24.44 | 0.00 | 0.00 |
November | 2.09 | 73.94 | 15.39 | 0.00 | 15.39 | 0.00 | 0.00 |
December | 0.11 | 94.80 | 11.55 | 0.00 | 11.55 | 0.00 | 0.00 |
Annual Sum or Average | 27.05 | 54.53 | 34.80 | 1.00 | 33.80 | 0.00 | 0.00 |
Minimum of Months | 0.11 | 20.82 | 11.55 | 0.00 | 11.55 | 0.00 | 0.00 |
Maximum of Months | 64.59 | 97.33 | 59.76 | 4.58 | 55.77 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 75.83 | 299.67 | 126.12 | 57.55 | 68.57 | 0.00 | 0.00 |
February | 170.32 | 259.63 | 209.48 | 105.07 | 104.41 | 0.00 | 0.00 |
March | 245.45 | 210.83 | 263.18 | 115.86 | 147.31 | 0.00 | 0.00 |
April | 366.17 | 164.22 | 346.47 | 145.62 | 200.85 | 0.00 | 0.00 |
May | 391.32 | 130.93 | 351.61 | 117.18 | 234.43 | 0.00 | 0.00 |
June | 455.95 | 94.25 | 385.46 | 149.40 | 236.05 | 0.00 | 0.00 |
July | 477.36 | 77.81 | 376.34 | 158.90 | 217.43 | 0.00 | 0.00 |
August | 496.21 | 73.71 | 379.48 | 184.65 | 194.83 | 0.00 | 0.00 |
September | 391.97 | 119.09 | 327.80 | 163.40 | 164.40 | 0.00 | 0.00 |
October | 258.16 | 177.51 | 249.63 | 130.21 | 119.42 | 0.00 | 0.00 |
November | 102.06 | 233.85 | 136.05 | 60.57 | 75.49 | 0.00 | 0.00 |
December | 93.61 | 296.35 | 128.71 | 67.31 | 61.40 | 0.00 | 0.00 |
Annual Sum or Average | 294.33 | 177.76 | 273.61 | 121.35 | 152.25 | 0.00 | 0.00 |
Minimum of Months | 75.83 | 73.71 | 126.12 | 57.55 | 61.40 | 0.00 | 0.00 |
Maximum of Months | 496.21 | 299.67 | 385.46 | 184.65 | 236.05 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 13.70 | 313.10 | 67.76 | 12.72 | 55.04 | 0.00 | 0.00 |
February | 60.22 | 266.06 | 119.97 | 33.13 | 86.84 | 0.00 | 0.00 |
March | 131.81 | 209.68 | 179.13 | 50.83 | 128.30 | 0.00 | 0.00 |
April | 257.58 | 162.42 | 271.81 | 90.18 | 181.63 | 0.00 | 0.00 |
May | 311.23 | 130.23 | 301.48 | 82.39 | 219.09 | 0.00 | 0.00 |
June | 394.12 | 95.74 | 350.58 | 125.07 | 225.51 | 0.00 | 0.00 |
July | 393.54 | 80.24 | 328.39 | 121.40 | 206.99 | 0.00 | 0.00 |
August | 385.54 | 77.02 | 310.20 | 128.07 | 182.13 | 0.00 | 0.00 |
September | 250.25 | 120.84 | 231.65 | 86.45 | 145.20 | 0.00 | 0.00 |
October | 127.84 | 176.86 | 152.84 | 52.26 | 100.59 | 0.00 | 0.00 |
November | 33.04 | 238.83 | 79.09 | 16.95 | 62.14 | 0.00 | 0.00 |
December | 18.63 | 305.78 | 63.40 | 15.74 | 47.66 | 0.00 | 0.00 |
Annual Sum or Average | 198.87 | 181.00 | 205.07 | 68.09 | 136.98 | 0.00 | 0.00 |
Minimum of Months | 13.70 | 77.02 | 63.40 | 12.72 | 47.66 | 0.00 | 0.00 |
Maximum of Months | 394.12 | 313.10 | 350.58 | 128.07 | 225.51 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 99.21 | 387.46 | 160.04 | 77.69 | 82.36 | 0.00 | 0.00 |
February | 200.21 | 333.72 | 246.79 | 124.69 | 122.10 | 0.00 | 0.00 |
March | 258.42 | 273.88 | 280.70 | 112.71 | 168.00 | 0.00 | 0.00 |
April | 328.78 | 216.89 | 321.15 | 97.26 | 223.88 | 0.00 | 0.00 |
May | 355.45 | 172.87 | 332.89 | 67.68 | 265.22 | 0.00 | 0.00 |
June | 356.73 | 126.73 | 319.36 | 59.48 | 259.87 | 0.00 | 0.00 |
July | 410.89 | 110.93 | 329.53 | 84.83 | 244.70 | 0.00 | 0.00 |
August | 415.04 | 108.51 | 319.83 | 104.06 | 215.77 | 0.00 | 0.00 |
September | 379.19 | 165.80 | 321.25 | 133.47 | 187.78 | 0.00 | 0.00 |
October | 280.12 | 230.81 | 273.60 | 135.10 | 138.50 | 0.00 | 0.00 |
November | 124.79 | 301.52 | 165.40 | 75.59 | 89.81 | 0.00 | 0.00 |
December | 121.90 | 382.70 | 163.24 | 89.38 | 73.86 | 0.00 | 0.00 |
Annual Sum or Average | 277.98 | 233.85 | 269.53 | 96.66 | 172.88 | 0.00 | 0.00 |
Minimum of Months | 99.21 | 108.51 | 160.04 | 59.48 | 73.86 | 0.00 | 0.00 |
Maximum of Months | 415.04 | 387.46 | 332.89 | 135.10 | 265.22 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 81.65 | 298.72 | 129.45 | 60.92 | 68.53 | 0.00 | 0.00 |
February | 176.08 | 259.93 | 212.46 | 108.17 | 104.29 | 0.00 | 0.00 |
March | 242.21 | 213.73 | 258.19 | 110.74 | 147.45 | 0.00 | 0.00 |
April | 354.60 | 169.66 | 335.40 | 134.22 | 201.18 | 0.00 | 0.00 |
May | 436.22 | 134.22 | 385.94 | 144.74 | 241.20 | 0.00 | 0.00 |
June | 424.43 | 97.38 | 363.72 | 127.82 | 235.90 | 0.00 | 0.00 |
July | 554.38 | 83.26 | 433.22 | 208.32 | 224.90 | 0.00 | 0.00 |
August | 507.51 | 77.79 | 386.93 | 190.94 | 195.99 | 0.00 | 0.00 |
September | 429.65 | 122.40 | 353.19 | 179.17 | 174.02 | 0.00 | 0.00 |
October | 257.86 | 178.16 | 248.81 | 127.89 | 120.92 | 0.00 | 0.00 |
November | 103.97 | 233.09 | 136.36 | 60.72 | 75.64 | 0.00 | 0.00 |
December | 98.46 | 296.14 | 130.54 | 69.20 | 61.33 | 0.00 | 0.00 |
Annual Sum or Average | 306.40 | 179.99 | 281.57 | 127.07 | 154.50 | 0.00 | 0.00 |
Minimum of Months | 81.65 | 77.79 | 129.45 | 60.72 | 61.33 | 0.00 | 0.00 |
Maximum of Months | 554.38 | 298.72 | 433.22 | 208.32 | 241.20 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 21.46 | 313.66 | 71.09 | 16.09 | 55.00 | 0.00 | 0.00 |
February | 70.74 | 270.39 | 122.94 | 36.23 | 86.71 | 0.00 | 0.00 |
March | 132.26 | 215.05 | 174.14 | 45.71 | 128.44 | 0.00 | 0.00 |
April | 247.42 | 168.58 | 260.74 | 78.78 | 181.96 | 0.00 | 0.00 |
May | 351.95 | 135.29 | 335.81 | 109.95 | 225.86 | 0.00 | 0.00 |
June | 357.75 | 99.42 | 328.84 | 103.49 | 225.36 | 0.00 | 0.00 |
July | 464.53 | 89.04 | 385.28 | 170.82 | 214.46 | 0.00 | 0.00 |
August | 395.87 | 81.62 | 317.65 | 134.35 | 183.29 | 0.00 | 0.00 |
September | 286.14 | 128.30 | 257.04 | 102.22 | 154.82 | 0.00 | 0.00 |
October | 130.88 | 179.79 | 152.02 | 49.94 | 102.08 | 0.00 | 0.00 |
November | 37.19 | 239.65 | 79.40 | 17.10 | 62.30 | 0.00 | 0.00 |
December | 26.58 | 307.86 | 65.22 | 17.63 | 47.59 | 0.00 | 0.00 |
Annual Sum or Average | 211.14 | 185.32 | 213.04 | 73.81 | 139.23 | 0.00 | 0.00 |
Minimum of Months | 21.46 | 81.62 | 65.22 | 16.09 | 47.59 | 0.00 | 0.00 |
Maximum of Months | 464.53 | 313.66 | 385.28 | 170.82 | 225.86 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 94.98 | 155.59 | 110.51 | 65.74 | 44.77 | 0.00 | 0.00 |
February | 168.51 | 136.58 | 170.06 | 105.52 | 64.55 | 0.00 | 0.00 |
March | 189.89 | 113.49 | 180.40 | 95.38 | 85.02 | 0.00 | 0.00 |
April | 214.12 | 90.67 | 190.63 | 81.81 | 108.82 | 0.00 | 0.00 |
May | 205.24 | 70.60 | 177.61 | 54.15 | 123.46 | 0.00 | 0.00 |
June | 192.34 | 50.74 | 160.69 | 43.01 | 117.69 | 0.00 | 0.00 |
July | 231.30 | 42.37 | 174.59 | 63.39 | 111.20 | 0.00 | 0.00 |
August | 253.83 | 39.54 | 186.12 | 85.52 | 100.60 | 0.00 | 0.00 |
September | 261.36 | 63.37 | 206.43 | 112.91 | 93.53 | 0.00 | 0.00 |
October | 211.95 | 94.08 | 186.74 | 114.33 | 72.41 | 0.00 | 0.00 |
November | 105.73 | 122.62 | 111.76 | 63.97 | 47.79 | 0.00 | 0.00 |
December | 112.33 | 154.63 | 116.96 | 75.64 | 41.33 | 0.00 | 0.00 |
Annual Sum or Average | 186.88 | 94.32 | 164.30 | 79.96 | 84.34 | 0.00 | 0.00 |
Minimum of Months | 94.98 | 39.54 | 110.51 | 43.01 | 41.33 | 0.00 | 0.00 |
Maximum of Months | 261.36 | 155.59 | 206.43 | 114.33 | 123.46 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.51 | 1002.39 | 118.94 | 0.00 | 118.94 | 0.00 | 0.00 |
February | 18.70 | 868.16 | 185.07 | 0.00 | 185.07 | 0.00 | 0.00 |
March | 83.59 | 679.19 | 272.70 | 0.00 | 272.70 | 0.00 | 0.00 |
April | 219.62 | 515.73 | 387.23 | 2.38 | 384.85 | 0.00 | 0.00 |
May | 378.21 | 393.01 | 496.80 | 14.92 | 481.88 | 0.00 | 0.00 |
June | 452.63 | 287.79 | 522.84 | 34.98 | 487.86 | 0.00 | 0.00 |
July | 502.37 | 248.59 | 497.64 | 40.06 | 457.58 | 0.00 | 0.00 |
August | 416.97 | 242.72 | 403.39 | 12.11 | 391.28 | 0.00 | 0.00 |
September | 230.69 | 382.98 | 312.22 | 0.23 | 311.99 | 0.00 | 0.00 |
October | 74.74 | 582.09 | 213.77 | 0.00 | 213.77 | 0.00 | 0.00 |
November | 9.37 | 785.31 | 134.66 | 0.00 | 134.66 | 0.00 | 0.00 |
December | 0.13 | 979.37 | 101.07 | 0.00 | 101.07 | 0.00 | 0.00 |
Annual Sum or Average | 200.12 | 579.21 | 304.45 | 8.79 | 295.66 | 0.00 | 0.00 |
Minimum of Months | 0.13 | 242.72 | 101.07 | 0.00 | 101.07 | 0.00 | 0.00 |
Maximum of Months | 502.37 | 1002.39 | 522.84 | 40.06 | 487.86 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.26 | 1034.72 | 118.94 | 0.00 | 118.94 | 0.00 | 0.00 |
February | 16.38 | 896.97 | 185.07 | 0.00 | 185.07 | 0.00 | 0.00 |
March | 75.82 | 699.37 | 272.70 | 0.00 | 272.70 | 0.00 | 0.00 |
April | 208.97 | 529.62 | 387.23 | 2.38 | 384.85 | 0.00 | 0.00 |
May | 367.27 | 402.57 | 496.80 | 14.92 | 481.88 | 0.00 | 0.00 |
June | 441.43 | 295.19 | 522.84 | 34.98 | 487.86 | 0.00 | 0.00 |
July | 492.82 | 255.34 | 497.64 | 40.06 | 457.58 | 0.00 | 0.00 |
August | 407.71 | 250.12 | 403.39 | 12.11 | 391.28 | 0.00 | 0.00 |
September | 222.41 | 394.00 | 312.22 | 0.23 | 311.99 | 0.00 | 0.00 |
October | 67.90 | 601.10 | 213.77 | 0.00 | 213.77 | 0.00 | 0.00 |
November | 7.82 | 813.57 | 134.66 | 0.00 | 134.66 | 0.00 | 0.00 |
December | 0.07 | 1011.20 | 101.07 | 0.00 | 101.07 | 0.00 | 0.00 |
Annual Sum or Average | 193.55 | 597.19 | 304.45 | 8.79 | 295.66 | 0.00 | 0.00 |
Minimum of Months | 0.07 | 250.12 | 101.07 | 0.00 | 101.07 | 0.00 | 0.00 |
Maximum of Months | 492.82 | 1034.72 | 522.84 | 40.06 | 487.86 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 91.67 | 639.49 | 193.88 | 70.27 | 123.61 | 0.00 | 0.00 |
February | 249.51 | 553.65 | 329.44 | 138.20 | 191.24 | 0.00 | 0.00 |
March | 420.76 | 451.35 | 442.28 | 166.68 | 275.60 | 0.00 | 0.00 |
April | 699.24 | 360.06 | 618.24 | 235.78 | 382.46 | 0.00 | 0.00 |
May | 796.99 | 293.23 | 653.06 | 199.56 | 453.50 | 0.00 | 0.00 |
June | 961.33 | 224.75 | 736.00 | 274.46 | 461.54 | 0.00 | 0.00 |
July | 992.38 | 190.02 | 704.69 | 280.29 | 424.40 | 0.00 | 0.00 |
August | 1003.33 | 182.31 | 689.64 | 312.71 | 376.94 | 0.00 | 0.00 |
September | 739.45 | 255.84 | 559.42 | 249.84 | 309.58 | 0.00 | 0.00 |
October | 435.87 | 383.67 | 402.46 | 182.46 | 220.00 | 0.00 | 0.00 |
November | 153.92 | 499.91 | 215.14 | 77.51 | 137.62 | 0.00 | 0.00 |
December | 120.10 | 629.98 | 192.11 | 83.05 | 109.06 | 0.00 | 0.00 |
Annual Sum or Average | 556.98 | 387.92 | 478.66 | 189.43 | 289.22 | 0.00 | 0.00 |
Minimum of Months | 91.67 | 182.31 | 192.11 | 70.27 | 109.06 | 0.00 | 0.00 |
Maximum of Months | 1003.33 | 639.49 | 736.00 | 312.71 | 461.54 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 219.11 | 696.63 | 322.09 | 167.35 | 154.74 | 0.00 | 0.00 |
February | 423.45 | 600.95 | 496.35 | 268.60 | 227.75 | 0.00 | 0.00 |
March | 521.84 | 496.77 | 552.71 | 242.80 | 309.91 | 0.00 | 0.00 |
April | 636.31 | 397.56 | 618.00 | 209.07 | 408.92 | 0.00 | 0.00 |
May | 660.28 | 317.18 | 622.41 | 142.95 | 479.47 | 0.00 | 0.00 |
June | 644.30 | 236.39 | 588.29 | 121.47 | 466.82 | 0.00 | 0.00 |
July | 753.15 | 207.57 | 615.01 | 175.10 | 439.91 | 0.00 | 0.00 |
August | 784.58 | 202.53 | 612.07 | 221.86 | 390.22 | 0.00 | 0.00 |
September | 749.54 | 300.28 | 632.52 | 287.49 | 345.03 | 0.00 | 0.00 |
October | 572.56 | 417.26 | 548.63 | 291.03 | 257.61 | 0.00 | 0.00 |
November | 263.20 | 546.41 | 330.64 | 162.84 | 167.80 | 0.00 | 0.00 |
December | 266.94 | 687.72 | 332.38 | 192.54 | 139.84 | 0.00 | 0.00 |
Annual Sum or Average | 541.89 | 424.77 | 522.59 | 206.55 | 316.05 | 0.00 | 0.00 |
Minimum of Months | 219.11 | 202.53 | 322.09 | 121.47 | 139.84 | 0.00 | 0.00 |
Maximum of Months | 784.58 | 696.63 | 632.52 | 291.03 | 479.47 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.904710E+09 | 0.136614E+10 | 0.102079E+10 | 0.607247E+09 | 0.413543E+09 | 0.00 | 0.00 |
February | 0.144286E+10 | 0.108351E+10 | 0.141883E+10 | 0.880309E+09 | 0.538522E+09 | 0.00 | 0.00 |
March | 0.179511E+10 | 0.998468E+09 | 0.166635E+10 | 0.881003E+09 | 0.785345E+09 | 0.00 | 0.00 |
April | 0.196437E+10 | 0.777568E+09 | 0.170398E+10 | 0.731303E+09 | 0.972674E+09 | 0.00 | 0.00 |
May | 0.194222E+10 | 0.639693E+09 | 0.164051E+10 | 0.500145E+09 | 0.114037E+10 | 0.00 | 0.00 |
June | 0.175971E+10 | 0.458393E+09 | 0.143641E+10 | 0.384441E+09 | 0.105197E+10 | 0.00 | 0.00 |
July | 0.215079E+10 | 0.420315E+09 | 0.161261E+10 | 0.585540E+09 | 0.102707E+10 | 0.00 | 0.00 |
August | 0.234704E+10 | 0.406070E+09 | 0.171918E+10 | 0.789956E+09 | 0.929228E+09 | 0.00 | 0.00 |
September | 0.234305E+10 | 0.582473E+09 | 0.184527E+10 | 0.100924E+10 | 0.836033E+09 | 0.00 | 0.00 |
October | 0.199345E+10 | 0.844130E+09 | 0.172485E+10 | 0.105602E+10 | 0.668837E+09 | 0.00 | 0.00 |
November | 0.967933E+09 | 0.104679E+10 | 0.998973E+09 | 0.571820E+09 | 0.427153E+09 | 0.00 | 0.00 |
December | 0.105965E+10 | 0.137139E+10 | 0.108037E+10 | 0.698661E+09 | 0.381712E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.206709E+11 | 0.999494E+10 | 0.178681E+11 | 0.869568E+10 | 0.917246E+10 | 0.00 | 0.00 |
Minimum of Months | 0.904710E+09 | 0.406070E+09 | 0.998973E+09 | 0.384441E+09 | 0.381712E+09 | 0.00 | 0.00 |
Maximum of Months | 0.234704E+10 | 0.137139E+10 | 0.184527E+10 | 0.105602E+10 | 0.114037E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.250833E+10 | 0.397198E+10 | 0.287448E+10 | 0.170997E+10 | 0.116451E+10 | 0.00 | 0.00 |
February | 0.400813E+10 | 0.318222E+10 | 0.399533E+10 | 0.247889E+10 | 0.151644E+10 | 0.00 | 0.00 |
March | 0.498816E+10 | 0.299046E+10 | 0.469233E+10 | 0.248085E+10 | 0.221148E+10 | 0.00 | 0.00 |
April | 0.544990E+10 | 0.236078E+10 | 0.479829E+10 | 0.205930E+10 | 0.273898E+10 | 0.00 | 0.00 |
May | 0.537820E+10 | 0.196930E+10 | 0.461958E+10 | 0.140838E+10 | 0.321120E+10 | 0.00 | 0.00 |
June | 0.485112E+10 | 0.145398E+10 | 0.404484E+10 | 0.108256E+10 | 0.296227E+10 | 0.00 | 0.00 |
July | 0.596381E+10 | 0.133206E+10 | 0.454101E+10 | 0.164884E+10 | 0.289217E+10 | 0.00 | 0.00 |
August | 0.652316E+10 | 0.129727E+10 | 0.484111E+10 | 0.222446E+10 | 0.261664E+10 | 0.00 | 0.00 |
September | 0.652216E+10 | 0.180869E+10 | 0.519617E+10 | 0.284196E+10 | 0.235421E+10 | 0.00 | 0.00 |
October | 0.554110E+10 | 0.257592E+10 | 0.485707E+10 | 0.297367E+10 | 0.188340E+10 | 0.00 | 0.00 |
November | 0.268032E+10 | 0.309726E+10 | 0.281304E+10 | 0.161021E+10 | 0.120283E+10 | 0.00 | 0.00 |
December | 0.294443E+10 | 0.399904E+10 | 0.304226E+10 | 0.196738E+10 | 0.107488E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.573588E+11 | 0.300390E+11 | 0.503155E+11 | 0.244865E+11 | 0.258290E+11 | 0.00 | 0.00 |
Minimum of Months | 0.250833E+10 | 0.129727E+10 | 0.281304E+10 | 0.108256E+10 | 0.107488E+10 | 0.00 | 0.00 |
Maximum of Months | 0.652316E+10 | 0.399904E+10 | 0.519617E+10 | 0.297367E+10 | 0.321120E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.327949E+10 | 0.551163E+10 | 0.373411E+10 | 0.222134E+10 | 0.151276E+10 | 0.00 | 0.00 |
February | 0.526553E+10 | 0.439041E+10 | 0.519017E+10 | 0.322022E+10 | 0.196994E+10 | 0.00 | 0.00 |
March | 0.656445E+10 | 0.414259E+10 | 0.609560E+10 | 0.322276E+10 | 0.287284E+10 | 0.00 | 0.00 |
April | 0.717549E+10 | 0.326652E+10 | 0.623325E+10 | 0.267515E+10 | 0.355810E+10 | 0.00 | 0.00 |
May | 0.706830E+10 | 0.274973E+10 | 0.600109E+10 | 0.182956E+10 | 0.417153E+10 | 0.00 | 0.00 |
June | 0.636049E+10 | 0.203906E+10 | 0.525447E+10 | 0.140631E+10 | 0.384816E+10 | 0.00 | 0.00 |
July | 0.785141E+10 | 0.185386E+10 | 0.589903E+10 | 0.214194E+10 | 0.375709E+10 | 0.00 | 0.00 |
August | 0.859266E+10 | 0.179019E+10 | 0.628888E+10 | 0.288971E+10 | 0.339917E+10 | 0.00 | 0.00 |
September | 0.858522E+10 | 0.249996E+10 | 0.675012E+10 | 0.369187E+10 | 0.305826E+10 | 0.00 | 0.00 |
October | 0.728462E+10 | 0.358031E+10 | 0.630961E+10 | 0.386297E+10 | 0.244665E+10 | 0.00 | 0.00 |
November | 0.349668E+10 | 0.433748E+10 | 0.365430E+10 | 0.209175E+10 | 0.156255E+10 | 0.00 | 0.00 |
December | 0.385700E+10 | 0.555093E+10 | 0.395207E+10 | 0.255574E+10 | 0.139632E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.753813E+11 | 0.417127E+11 | 0.653627E+11 | 0.318093E+11 | 0.335534E+11 | 0.00 | 0.00 |
Minimum of Months | 0.327949E+10 | 0.179019E+10 | 0.365430E+10 | 0.140631E+10 | 0.139632E+10 | 0.00 | 0.00 |
Maximum of Months | 0.859266E+10 | 0.555093E+10 | 0.675012E+10 | 0.386297E+10 | 0.417153E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.217174E+09 | 0.806526E+09 | 0.346724E+09 | 0.163167E+09 | 0.183558E+09 | 0.00 | 0.00 |
February | 0.426757E+09 | 0.633368E+09 | 0.513985E+09 | 0.261695E+09 | 0.252290E+09 | 0.00 | 0.00 |
March | 0.652789E+09 | 0.576278E+09 | 0.691549E+09 | 0.296606E+09 | 0.394943E+09 | 0.00 | 0.00 |
April | 0.928647E+09 | 0.440838E+09 | 0.869359E+09 | 0.347902E+09 | 0.521457E+09 | 0.00 | 0.00 |
May | 0.118119E+10 | 0.360991E+09 | 0.103370E+10 | 0.387673E+09 | 0.646029E+09 | 0.00 | 0.00 |
June | 0.111279E+10 | 0.254035E+09 | 0.942761E+09 | 0.331299E+09 | 0.611462E+09 | 0.00 | 0.00 |
July | 0.149905E+10 | 0.224737E+09 | 0.116035E+10 | 0.557965E+09 | 0.602380E+09 | 0.00 | 0.00 |
August | 0.136985E+10 | 0.211427E+09 | 0.103634E+10 | 0.511407E+09 | 0.524936E+09 | 0.00 | 0.00 |
September | 0.112050E+10 | 0.321169E+09 | 0.915471E+09 | 0.464417E+09 | 0.451054E+09 | 0.00 | 0.00 |
October | 0.694317E+09 | 0.482531E+09 | 0.666417E+09 | 0.342553E+09 | 0.323863E+09 | 0.00 | 0.00 |
November | 0.268962E+09 | 0.610660E+09 | 0.353457E+09 | 0.157390E+09 | 0.196067E+09 | 0.00 | 0.00 |
December | 0.262693E+09 | 0.801494E+09 | 0.349625E+09 | 0.185355E+09 | 0.164270E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.973473E+10 | 0.572405E+10 | 0.887974E+10 | 0.400743E+10 | 0.487231E+10 | 0.00 | 0.00 |
Minimum of Months | 0.217174E+09 | 0.211427E+09 | 0.346724E+09 | 0.157390E+09 | 0.164270E+09 | 0.00 | 0.00 |
Maximum of Months | 0.149905E+10 | 0.806526E+09 | 0.116035E+10 | 0.557965E+09 | 0.646029E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 56159025.65 | 0.847775E+09 | 0.190407E+09 | 43103720.32 | 0.147303E+09 | 0.00 | 0.00 |
February | 0.170151E+09 | 0.659667E+09 | 0.297420E+09 | 87642964.17 | 0.209777E+09 | 0.00 | 0.00 |
March | 0.355645E+09 | 0.580994E+09 | 0.466427E+09 | 0.122417E+09 | 0.344011E+09 | 0.00 | 0.00 |
April | 0.648551E+09 | 0.438026E+09 | 0.675843E+09 | 0.204193E+09 | 0.471650E+09 | 0.00 | 0.00 |
May | 0.956747E+09 | 0.360552E+09 | 0.899439E+09 | 0.294493E+09 | 0.604946E+09 | 0.00 | 0.00 |
June | 0.942179E+09 | 0.255293E+09 | 0.852363E+09 | 0.268241E+09 | 0.584122E+09 | 0.00 | 0.00 |
July | 0.126142E+10 | 0.234136E+09 | 0.103192E+10 | 0.457523E+09 | 0.574398E+09 | 0.00 | 0.00 |
August | 0.107027E+10 | 0.218594E+09 | 0.850783E+09 | 0.359854E+09 | 0.490929E+09 | 0.00 | 0.00 |
September | 0.749014E+09 | 0.332644E+09 | 0.666243E+09 | 0.264960E+09 | 0.401283E+09 | 0.00 | 0.00 |
October | 0.351109E+09 | 0.488257E+09 | 0.407182E+09 | 0.133761E+09 | 0.273421E+09 | 0.00 | 0.00 |
November | 95028185.43 | 0.629195E+09 | 0.205806E+09 | 44331374.38 | 0.161474E+09 | 0.00 | 0.00 |
December | 69682752.85 | 0.834797E+09 | 0.174689E+09 | 47217705.85 | 0.127471E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.672596E+10 | 0.587993E+10 | 0.671852E+10 | 0.232774E+10 | 0.439079E+10 | 0.00 | 0.00 |
Minimum of Months | 56159025.65 | 0.218594E+09 | 0.174689E+09 | 43103720.32 | 0.127471E+09 | 0.00 | 0.00 |
Maximum of Months | 0.126142E+10 | 0.847775E+09 | 0.103192E+10 | 0.457523E+09 | 0.604946E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.138345E+09 | 0.236559E+09 | 0.161430E+09 | 96031370.32 | 65398878.59 | 0.00 | 0.00 |
February | 0.212559E+09 | 0.216680E+09 | 0.224378E+09 | 0.139214E+09 | 85163535.41 | 0.00 | 0.00 |
March | 0.258003E+09 | 0.229742E+09 | 0.263521E+09 | 0.139324E+09 | 0.124197E+09 | 0.00 | 0.00 |
April | 0.277818E+09 | 0.185456E+09 | 0.269472E+09 | 0.115650E+09 | 0.153822E+09 | 0.00 | 0.00 |
May | 0.270975E+09 | 0.158277E+09 | 0.259436E+09 | 79094093.75 | 0.180342E+09 | 0.00 | 0.00 |
June | 0.239743E+09 | 0.120867E+09 | 0.227159E+09 | 60796426.56 | 0.166362E+09 | 0.00 | 0.00 |
July | 0.305305E+09 | 0.111608E+09 | 0.255024E+09 | 92598617.16 | 0.162425E+09 | 0.00 | 0.00 |
August | 0.338731E+09 | 0.108565E+09 | 0.271877E+09 | 0.124925E+09 | 0.146952E+09 | 0.00 | 0.00 |
September | 0.344240E+09 | 0.144658E+09 | 0.291817E+09 | 0.159604E+09 | 0.132213E+09 | 0.00 | 0.00 |
October | 0.288663E+09 | 0.204107E+09 | 0.272773E+09 | 0.167001E+09 | 0.105772E+09 | 0.00 | 0.00 |
November | 0.136284E+09 | 0.229820E+09 | 0.157980E+09 | 90428875.66 | 67551271.18 | 0.00 | 0.00 |
December | 0.159073E+09 | 0.254175E+09 | 0.170853E+09 | 0.110488E+09 | 60365023.40 | 0.00 | 0.00 |
Annual Sum or Average | 0.296974E+10 | 0.220052E+10 | 0.282572E+10 | 0.137516E+10 | 0.145056E+10 | 0.00 | 0.00 |
Minimum of Months | 0.136284E+09 | 0.108565E+09 | 0.157980E+09 | 60796426.56 | 60365023.40 | 0.00 | 0.00 |
Maximum of Months | 0.344240E+09 | 0.254175E+09 | 0.291817E+09 | 0.167001E+09 | 0.180342E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 701082.84 | 0.260699E+09 | 36413225.08 | 0.00 | 36413225.08 | 0.00 | 0.00 |
February | 8639307.11 | 0.201232E+09 | 51176770.43 | 0.00 | 51176770.43 | 0.00 | 0.00 |
March | 35761776.39 | 0.172401E+09 | 83487367.90 | 272.21 | 83487095.69 | 0.00 | 0.00 |
April | 80075429.18 | 0.124862E+09 | 0.114728E+09 | 705856.95 | 0.114022E+09 | 0.00 | 0.00 |
May | 0.134657E+09 | 97864401.29 | 0.152098E+09 | 4566859.58 | 0.147531E+09 | 0.00 | 0.00 |
June | 0.154022E+09 | 67958831.48 | 0.154906E+09 | 10363092.34 | 0.144543E+09 | 0.00 | 0.00 |
July | 0.172989E+09 | 59434891.13 | 0.152356E+09 | 12265043.58 | 0.140091E+09 | 0.00 | 0.00 |
August | 0.145977E+09 | 55768778.77 | 0.123500E+09 | 3709014.18 | 0.119791E+09 | 0.00 | 0.00 |
September | 81808772.32 | 90686870.81 | 92504439.09 | 69295.25 | 92435143.84 | 0.00 | 0.00 |
October | 32680784.65 | 0.143225E+09 | 65447658.79 | 0.00 | 65447658.79 | 0.00 | 0.00 |
November | 5412035.22 | 0.191644E+09 | 39895669.45 | 0.00 | 39895669.45 | 0.00 | 0.00 |
December | 287529.25 | 0.253911E+09 | 30941853.50 | 0.00 | 30941853.50 | 0.00 | 0.00 |
Annual Sum or Average | 0.853012E+09 | 0.171969E+10 | 0.109745E+10 | 31679434.09 | 0.106578E+10 | 0.00 | 0.00 |
Minimum of Months | 287529.25 | 55768778.77 | 30941853.50 | 0.00 | 30941853.50 | 0.00 | 0.00 |
Maximum of Months | 0.172989E+09 | 0.260699E+09 | 0.154906E+09 | 12265043.58 | 0.147531E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.203109E+09 | 0.802646E+09 | 0.337811E+09 | 0.154141E+09 | 0.183670E+09 | 0.00 | 0.00 |
February | 0.412048E+09 | 0.628085E+09 | 0.506786E+09 | 0.254193E+09 | 0.252592E+09 | 0.00 | 0.00 |
March | 0.657400E+09 | 0.564688E+09 | 0.704892E+09 | 0.310326E+09 | 0.394567E+09 | 0.00 | 0.00 |
April | 0.949108E+09 | 0.425665E+09 | 0.898041E+09 | 0.377444E+09 | 0.520597E+09 | 0.00 | 0.00 |
May | 0.104810E+10 | 0.350693E+09 | 0.941749E+09 | 0.313851E+09 | 0.627898E+09 | 0.00 | 0.00 |
June | 0.118182E+10 | 0.244304E+09 | 0.999105E+09 | 0.387252E+09 | 0.611853E+09 | 0.00 | 0.00 |
July | 0.127857E+10 | 0.208414E+09 | 0.100798E+10 | 0.425606E+09 | 0.582376E+09 | 0.00 | 0.00 |
August | 0.132904E+10 | 0.197437E+09 | 0.101640E+10 | 0.494580E+09 | 0.521820E+09 | 0.00 | 0.00 |
September | 0.101599E+10 | 0.308677E+09 | 0.849659E+09 | 0.423537E+09 | 0.426122E+09 | 0.00 | 0.00 |
October | 0.691449E+09 | 0.475455E+09 | 0.668615E+09 | 0.348763E+09 | 0.319852E+09 | 0.00 | 0.00 |
November | 0.264530E+09 | 0.606151E+09 | 0.352653E+09 | 0.156990E+09 | 0.195662E+09 | 0.00 | 0.00 |
December | 0.250718E+09 | 0.793733E+09 | 0.344747E+09 | 0.180287E+09 | 0.164460E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.928187E+10 | 0.560595E+10 | 0.862844E+10 | 0.382697E+10 | 0.480147E+10 | 0.00 | 0.00 |
Minimum of Months | 0.203109E+09 | 0.197437E+09 | 0.337811E+09 | 0.154141E+09 | 0.164460E+09 | 0.00 | 0.00 |
Maximum of Months | 0.132904E+10 | 0.802646E+09 | 0.101640E+10 | 0.494580E+09 | 0.627898E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 36688979.34 | 0.838610E+09 | 0.181494E+09 | 34077660.85 | 0.147416E+09 | 0.00 | 0.00 |
February | 0.145687E+09 | 0.643659E+09 | 0.290220E+09 | 80141237.88 | 0.210079E+09 | 0.00 | 0.00 |
March | 0.353037E+09 | 0.561600E+09 | 0.479771E+09 | 0.136136E+09 | 0.343635E+09 | 0.00 | 0.00 |
April | 0.667648E+09 | 0.420996E+09 | 0.704526E+09 | 0.233735E+09 | 0.470791E+09 | 0.00 | 0.00 |
May | 0.833604E+09 | 0.348802E+09 | 0.807486E+09 | 0.220672E+09 | 0.586815E+09 | 0.00 | 0.00 |
June | 0.102155E+10 | 0.248166E+09 | 0.908707E+09 | 0.324193E+09 | 0.584513E+09 | 0.00 | 0.00 |
July | 0.105405E+10 | 0.214921E+09 | 0.879557E+09 | 0.325164E+09 | 0.554394E+09 | 0.00 | 0.00 |
August | 0.103264E+10 | 0.206286E+09 | 0.830840E+09 | 0.343027E+09 | 0.487813E+09 | 0.00 | 0.00 |
September | 0.648638E+09 | 0.313229E+09 | 0.600430E+09 | 0.224079E+09 | 0.376351E+09 | 0.00 | 0.00 |
October | 0.342399E+09 | 0.473707E+09 | 0.409380E+09 | 0.139970E+09 | 0.269410E+09 | 0.00 | 0.00 |
November | 85627052.90 | 0.619059E+09 | 0.205001E+09 | 43931896.31 | 0.161070E+09 | 0.00 | 0.00 |
December | 49911332.63 | 0.819012E+09 | 0.169811E+09 | 42150042.10 | 0.127661E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.627148E+10 | 0.570805E+10 | 0.646722E+10 | 0.214728E+10 | 0.431995E+10 | 0.00 | 0.00 |
Minimum of Months | 36688979.34 | 0.206286E+09 | 0.169811E+09 | 34077660.85 | 0.127661E+09 | 0.00 | 0.00 |
Maximum of Months | 0.105405E+10 | 0.838610E+09 | 0.908707E+09 | 0.343027E+09 | 0.586815E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.265727E+09 | 0.103778E+10 | 0.428658E+09 | 0.208073E+09 | 0.220584E+09 | 0.00 | 0.00 |
February | 0.484337E+09 | 0.807338E+09 | 0.597030E+09 | 0.301638E+09 | 0.295392E+09 | 0.00 | 0.00 |
March | 0.692152E+09 | 0.733564E+09 | 0.751838E+09 | 0.301877E+09 | 0.449962E+09 | 0.00 | 0.00 |
April | 0.852204E+09 | 0.562171E+09 | 0.832411E+09 | 0.252110E+09 | 0.580300E+09 | 0.00 | 0.00 |
May | 0.952029E+09 | 0.463003E+09 | 0.891621E+09 | 0.181268E+09 | 0.710352E+09 | 0.00 | 0.00 |
June | 0.924653E+09 | 0.328490E+09 | 0.827769E+09 | 0.154179E+09 | 0.673590E+09 | 0.00 | 0.00 |
July | 0.110053E+10 | 0.297102E+09 | 0.882620E+09 | 0.227206E+09 | 0.655414E+09 | 0.00 | 0.00 |
August | 0.111165E+10 | 0.290638E+09 | 0.856624E+09 | 0.278714E+09 | 0.577911E+09 | 0.00 | 0.00 |
September | 0.982862E+09 | 0.429751E+09 | 0.832682E+09 | 0.345967E+09 | 0.486715E+09 | 0.00 | 0.00 |
October | 0.750268E+09 | 0.618209E+09 | 0.732804E+09 | 0.361844E+09 | 0.370960E+09 | 0.00 | 0.00 |
November | 0.323464E+09 | 0.781527E+09 | 0.428726E+09 | 0.195934E+09 | 0.232792E+09 | 0.00 | 0.00 |
December | 0.326492E+09 | 0.102502E+10 | 0.437221E+09 | 0.239396E+09 | 0.197825E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.876638E+10 | 0.737459E+10 | 0.850000E+10 | 0.304821E+10 | 0.545180E+10 | 0.00 | 0.00 |
Minimum of Months | 0.265727E+09 | 0.290638E+09 | 0.428658E+09 | 0.154179E+09 | 0.197825E+09 | 0.00 | 0.00 |
Maximum of Months | 0.111165E+10 | 0.103778E+10 | 0.891621E+09 | 0.361844E+09 | 0.710352E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.218697E+09 | 0.800099E+09 | 0.346724E+09 | 0.163167E+09 | 0.183558E+09 | 0.00 | 0.00 |
February | 0.425974E+09 | 0.628813E+09 | 0.513985E+09 | 0.261695E+09 | 0.252290E+09 | 0.00 | 0.00 |
March | 0.648728E+09 | 0.572452E+09 | 0.691549E+09 | 0.296606E+09 | 0.394943E+09 | 0.00 | 0.00 |
April | 0.919133E+09 | 0.439746E+09 | 0.869359E+09 | 0.347902E+09 | 0.521457E+09 | 0.00 | 0.00 |
May | 0.116836E+10 | 0.359483E+09 | 0.103370E+10 | 0.387673E+09 | 0.646029E+09 | 0.00 | 0.00 |
June | 0.110014E+10 | 0.252399E+09 | 0.942761E+09 | 0.331299E+09 | 0.611462E+09 | 0.00 | 0.00 |
July | 0.148485E+10 | 0.222992E+09 | 0.116035E+10 | 0.557965E+09 | 0.602380E+09 | 0.00 | 0.00 |
August | 0.135932E+10 | 0.208347E+09 | 0.103634E+10 | 0.511407E+09 | 0.524936E+09 | 0.00 | 0.00 |
September | 0.111366E+10 | 0.317253E+09 | 0.915471E+09 | 0.464417E+09 | 0.451054E+09 | 0.00 | 0.00 |
October | 0.690650E+09 | 0.477175E+09 | 0.666417E+09 | 0.342553E+09 | 0.323863E+09 | 0.00 | 0.00 |
November | 0.269492E+09 | 0.604160E+09 | 0.353457E+09 | 0.157390E+09 | 0.196067E+09 | 0.00 | 0.00 |
December | 0.263728E+09 | 0.793193E+09 | 0.349625E+09 | 0.185355E+09 | 0.164270E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.966273E+10 | 0.567611E+10 | 0.887974E+10 | 0.400743E+10 | 0.487231E+10 | 0.00 | 0.00 |
Minimum of Months | 0.218697E+09 | 0.208347E+09 | 0.346724E+09 | 0.157390E+09 | 0.164270E+09 | 0.00 | 0.00 |
Maximum of Months | 0.148485E+10 | 0.800099E+09 | 0.116035E+10 | 0.557965E+09 | 0.646029E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 57484275.48 | 0.840113E+09 | 0.190407E+09 | 43103720.32 | 0.147303E+09 | 0.00 | 0.00 |
February | 0.171144E+09 | 0.654133E+09 | 0.297420E+09 | 87642964.17 | 0.209777E+09 | 0.00 | 0.00 |
March | 0.354251E+09 | 0.575987E+09 | 0.466427E+09 | 0.122417E+09 | 0.344011E+09 | 0.00 | 0.00 |
April | 0.641302E+09 | 0.436961E+09 | 0.675843E+09 | 0.204193E+09 | 0.471650E+09 | 0.00 | 0.00 |
May | 0.942672E+09 | 0.362352E+09 | 0.899439E+09 | 0.294493E+09 | 0.604946E+09 | 0.00 | 0.00 |
June | 0.927286E+09 | 0.257708E+09 | 0.852363E+09 | 0.268241E+09 | 0.584122E+09 | 0.00 | 0.00 |
July | 0.124420E+10 | 0.238482E+09 | 0.103192E+10 | 0.457523E+09 | 0.574398E+09 | 0.00 | 0.00 |
August | 0.106030E+10 | 0.218613E+09 | 0.850783E+09 | 0.359854E+09 | 0.490929E+09 | 0.00 | 0.00 |
September | 0.741678E+09 | 0.332564E+09 | 0.666243E+09 | 0.264960E+09 | 0.401283E+09 | 0.00 | 0.00 |
October | 0.350540E+09 | 0.481543E+09 | 0.407182E+09 | 0.133761E+09 | 0.273421E+09 | 0.00 | 0.00 |
November | 96389717.12 | 0.621176E+09 | 0.205806E+09 | 44331374.38 | 0.161474E+09 | 0.00 | 0.00 |
December | 71190792.17 | 0.824578E+09 | 0.174689E+09 | 47217705.85 | 0.127471E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.665844E+10 | 0.584421E+10 | 0.671852E+10 | 0.232774E+10 | 0.439079E+10 | 0.00 | 0.00 |
Minimum of Months | 57484275.48 | 0.218613E+09 | 0.174689E+09 | 43103720.32 | 0.127471E+09 | 0.00 | 0.00 |
Maximum of Months | 0.124420E+10 | 0.840113E+09 | 0.103192E+10 | 0.457523E+09 | 0.604946E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.254400E+09 | 0.416722E+09 | 0.296000E+09 | 0.176084E+09 | 0.119916E+09 | 0.00 | 0.00 |
February | 0.407661E+09 | 0.330418E+09 | 0.411421E+09 | 0.255264E+09 | 0.156157E+09 | 0.00 | 0.00 |
March | 0.508610E+09 | 0.303974E+09 | 0.483195E+09 | 0.255466E+09 | 0.227729E+09 | 0.00 | 0.00 |
April | 0.554993E+09 | 0.235024E+09 | 0.494106E+09 | 0.212057E+09 | 0.282050E+09 | 0.00 | 0.00 |
May | 0.549720E+09 | 0.189092E+09 | 0.475705E+09 | 0.145028E+09 | 0.330677E+09 | 0.00 | 0.00 |
June | 0.498545E+09 | 0.131527E+09 | 0.416521E+09 | 0.111477E+09 | 0.305044E+09 | 0.00 | 0.00 |
July | 0.619527E+09 | 0.113496E+09 | 0.467614E+09 | 0.169790E+09 | 0.297825E+09 | 0.00 | 0.00 |
August | 0.679845E+09 | 0.105908E+09 | 0.498517E+09 | 0.229065E+09 | 0.269452E+09 | 0.00 | 0.00 |
September | 0.677455E+09 | 0.164260E+09 | 0.535078E+09 | 0.292651E+09 | 0.242427E+09 | 0.00 | 0.00 |
October | 0.567688E+09 | 0.251990E+09 | 0.500159E+09 | 0.306214E+09 | 0.193945E+09 | 0.00 | 0.00 |
November | 0.274059E+09 | 0.317840E+09 | 0.289674E+09 | 0.165811E+09 | 0.123863E+09 | 0.00 | 0.00 |
December | 0.300873E+09 | 0.414172E+09 | 0.313277E+09 | 0.202591E+09 | 0.110686E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.589338E+10 | 0.297442E+10 | 0.518127E+10 | 0.252150E+10 | 0.265977E+10 | 0.00 | 0.00 |
Minimum of Months | 0.254400E+09 | 0.105908E+09 | 0.289674E+09 | 0.111477E+09 | 0.110686E+09 | 0.00 | 0.00 |
Maximum of Months | 0.679845E+09 | 0.416722E+09 | 0.535078E+09 | 0.306214E+09 | 0.330677E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 1369555.18 | 0.268481E+10 | 0.318561E+09 | 0.00 | 0.318561E+09 | 0.00 | 0.00 |
February | 45237698.48 | 0.210024E+10 | 0.447720E+09 | 0.00 | 0.447720E+09 | 0.00 | 0.00 |
March | 0.223900E+09 | 0.181915E+10 | 0.730390E+09 | 2381.43 | 0.730388E+09 | 0.00 | 0.00 |
April | 0.569268E+09 | 0.133676E+10 | 0.100370E+10 | 6175195.84 | 0.997525E+09 | 0.00 | 0.00 |
May | 0.101299E+10 | 0.105264E+10 | 0.133063E+10 | 39953211.88 | 0.129068E+10 | 0.00 | 0.00 |
June | 0.117320E+10 | 0.745944E+09 | 0.135520E+10 | 90661606.03 | 0.126454E+10 | 0.00 | 0.00 |
July | 0.134554E+10 | 0.665837E+09 | 0.133289E+10 | 0.107301E+09 | 0.122559E+10 | 0.00 | 0.00 |
August | 0.111680E+10 | 0.650114E+09 | 0.108044E+10 | 32448343.77 | 0.104799E+10 | 0.00 | 0.00 |
September | 0.597949E+09 | 0.992684E+09 | 0.809276E+09 | 606230.16 | 0.808670E+09 | 0.00 | 0.00 |
October | 0.200195E+09 | 0.155908E+10 | 0.572569E+09 | 0.00 | 0.572569E+09 | 0.00 | 0.00 |
November | 24289375.55 | 0.203553E+10 | 0.349028E+09 | 0.00 | 0.349028E+09 | 0.00 | 0.00 |
December | 359972.49 | 0.262315E+10 | 0.270695E+09 | 0.00 | 0.270695E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.631110E+10 | 0.182659E+11 | 0.960109E+10 | 0.277148E+09 | 0.932395E+10 | 0.00 | 0.00 |
Minimum of Months | 359972.49 | 0.650114E+09 | 0.270695E+09 | 0.00 | 0.270695E+09 | 0.00 | 0.00 |
Maximum of Months | 0.134554E+10 | 0.268481E+10 | 0.135520E+10 | 0.107301E+09 | 0.129068E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 687444.12 | 0.277140E+10 | 0.318561E+09 | 0.00 | 0.318561E+09 | 0.00 | 0.00 |
February | 39623527.95 | 0.216995E+10 | 0.447720E+09 | 0.00 | 0.447720E+09 | 0.00 | 0.00 |
March | 0.203067E+09 | 0.187318E+10 | 0.730390E+09 | 2381.43 | 0.730388E+09 | 0.00 | 0.00 |
April | 0.541639E+09 | 0.137277E+10 | 0.100370E+10 | 6175195.84 | 0.997525E+09 | 0.00 | 0.00 |
May | 0.983699E+09 | 0.107824E+10 | 0.133063E+10 | 39953211.88 | 0.129068E+10 | 0.00 | 0.00 |
June | 0.114418E+10 | 0.765134E+09 | 0.135520E+10 | 90661606.03 | 0.126454E+10 | 0.00 | 0.00 |
July | 0.131997E+10 | 0.683892E+09 | 0.133289E+10 | 0.107301E+09 | 0.122559E+10 | 0.00 | 0.00 |
August | 0.109201E+10 | 0.669926E+09 | 0.108044E+10 | 32448343.77 | 0.104799E+10 | 0.00 | 0.00 |
September | 0.576484E+09 | 0.102126E+10 | 0.809276E+09 | 606230.16 | 0.808670E+09 | 0.00 | 0.00 |
October | 0.181873E+09 | 0.160999E+10 | 0.572569E+09 | 0.00 | 0.572569E+09 | 0.00 | 0.00 |
November | 20281496.21 | 0.210877E+10 | 0.349028E+09 | 0.00 | 0.349028E+09 | 0.00 | 0.00 |
December | 193458.55 | 0.270839E+10 | 0.270695E+09 | 0.00 | 0.270695E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.610372E+10 | 0.188329E+11 | 0.960109E+10 | 0.277148E+09 | 0.932395E+10 | 0.00 | 0.00 |
Minimum of Months | 193458.55 | 0.669926E+09 | 0.270695E+09 | 0.00 | 0.270695E+09 | 0.00 | 0.00 |
Maximum of Months | 0.131997E+10 | 0.277140E+10 | 0.135520E+10 | 0.107301E+09 | 0.129068E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.245539E+09 | 0.171282E+10 | 0.519285E+09 | 0.188214E+09 | 0.331072E+09 | 0.00 | 0.00 |
February | 0.603611E+09 | 0.133938E+10 | 0.796974E+09 | 0.334323E+09 | 0.462651E+09 | 0.00 | 0.00 |
March | 0.112696E+10 | 0.120891E+10 | 0.118461E+10 | 0.446443E+09 | 0.738167E+09 | 0.00 | 0.00 |
April | 0.181243E+10 | 0.933283E+09 | 0.160249E+10 | 0.611146E+09 | 0.991341E+09 | 0.00 | 0.00 |
May | 0.213465E+10 | 0.785399E+09 | 0.174915E+10 | 0.534492E+09 | 0.121466E+10 | 0.00 | 0.00 |
June | 0.249176E+10 | 0.582554E+09 | 0.190771E+10 | 0.711401E+09 | 0.119631E+10 | 0.00 | 0.00 |
July | 0.265799E+10 | 0.508952E+09 | 0.188744E+10 | 0.750725E+09 | 0.113672E+10 | 0.00 | 0.00 |
August | 0.268733E+10 | 0.488312E+09 | 0.184714E+10 | 0.837559E+09 | 0.100959E+10 | 0.00 | 0.00 |
September | 0.191664E+10 | 0.663130E+09 | 0.145002E+10 | 0.647584E+09 | 0.802436E+09 | 0.00 | 0.00 |
October | 0.116744E+10 | 0.102763E+10 | 0.107795E+10 | 0.488713E+09 | 0.589235E+09 | 0.00 | 0.00 |
November | 0.398955E+09 | 0.129577E+10 | 0.557632E+09 | 0.200916E+09 | 0.356716E+09 | 0.00 | 0.00 |
December | 0.321668E+09 | 0.168735E+10 | 0.514539E+09 | 0.222431E+09 | 0.292108E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.175650E+11 | 0.122335E+11 | 0.150949E+11 | 0.597395E+10 | 0.912099E+10 | 0.00 | 0.00 |
Minimum of Months | 0.245539E+09 | 0.488312E+09 | 0.514539E+09 | 0.188214E+09 | 0.292108E+09 | 0.00 | 0.00 |
Maximum of Months | 0.268733E+10 | 0.171282E+10 | 0.190771E+10 | 0.837559E+09 | 0.121466E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.586857E+09 | 0.186586E+10 | 0.862687E+09 | 0.448231E+09 | 0.414456E+09 | 0.00 | 0.00 |
February | 0.102441E+10 | 0.145382E+10 | 0.120077E+10 | 0.649789E+09 | 0.550985E+09 | 0.00 | 0.00 |
March | 0.139770E+10 | 0.133056E+10 | 0.148038E+10 | 0.650302E+09 | 0.830075E+09 | 0.00 | 0.00 |
April | 0.164931E+10 | 0.103047E+10 | 0.160184E+10 | 0.541919E+09 | 0.105993E+10 | 0.00 | 0.00 |
May | 0.176850E+10 | 0.849532E+09 | 0.166707E+10 | 0.382872E+09 | 0.128420E+10 | 0.00 | 0.00 |
June | 0.167001E+10 | 0.612729E+09 | 0.152484E+10 | 0.314849E+09 | 0.120999E+10 | 0.00 | 0.00 |
July | 0.201724E+10 | 0.555947E+09 | 0.164725E+10 | 0.468992E+09 | 0.117826E+10 | 0.00 | 0.00 |
August | 0.210142E+10 | 0.542462E+09 | 0.163938E+10 | 0.594219E+09 | 0.104516E+10 | 0.00 | 0.00 |
September | 0.194281E+10 | 0.778331E+09 | 0.163949E+10 | 0.745167E+09 | 0.894325E+09 | 0.00 | 0.00 |
October | 0.153355E+10 | 0.111758E+10 | 0.146946E+10 | 0.779484E+09 | 0.689974E+09 | 0.00 | 0.00 |
November | 0.682215E+09 | 0.141629E+10 | 0.857028E+09 | 0.422081E+09 | 0.434946E+09 | 0.00 | 0.00 |
December | 0.714980E+09 | 0.184200E+10 | 0.890259E+09 | 0.515707E+09 | 0.374552E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.170890E+11 | 0.133956E+11 | 0.164805E+11 | 0.651361E+10 | 0.996685E+10 | 0.00 | 0.00 |
Minimum of Months | 0.586857E+09 | 0.542462E+09 | 0.857028E+09 | 0.314849E+09 | 0.374552E+09 | 0.00 | 0.00 |
Maximum of Months | 0.210142E+10 | 0.186586E+10 | 0.166707E+10 | 0.779484E+09 | 0.128420E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 4.50 | 3.10 | 1.22 | 3.91 | -4.2 | 29.50 | 44.23 | 0.00 |
February | 5.82 | 4.07 | 1.77 | 3.94 | -3.8 | 43.80 | 82.64 | 0.00 |
March | 8.33 | 5.86 | 2.94 | 3.85 | -1.4 | 65.55 | 100.60 | 0.02 |
April | 10.85 | 8.04 | 5.25 | 4.23 | 1.22 | 89.73 | 150.02 | 0.00 |
May | 12.97 | 10.02 | 7.49 | 3.85 | 3.75 | 114.98 | 168.60 | 0.00 |
June | 15.59 | 11.80 | 8.88 | 4.02 | 5.93 | 107.53 | 199.74 | 0.01 |
July | 17.66 | 13.41 | 10.38 | 3.76 | 8.02 | 92.25 | 247.81 | 0.00 |
August | 18.80 | 14.57 | 11.86 | 3.84 | 8.90 | 79.20 | 215.47 | 0.01 |
September | 15.09 | 12.55 | 10.74 | 2.23 | 5.47 | 68.06 | 162.11 | 0.01 |
October | 11.43 | 9.19 | 7.19 | 4.02 | 2.10 | 48.18 | 106.36 | 0.04 |
November | 8.07 | 6.72 | 5.29 | 3.86 | 0.13 | 33.26 | 46.10 | 0.00 |
December | 5.42 | 4.09 | 2.46 | 3.51 | -3.8 | 24.03 | 50.49 | 0.04 |
Annual Sum or Average | 11.24 | 8.64 | 6.31 | 3.75 | 1.89 | 66.43 | 131.49 | 0.01 |
Minimum of Months | 4.50 | 3.10 | 1.22 | 2.23 | -4.2 | 24.03 | 44.23 | 0.00 |
Maximum of Months | 18.80 | 14.57 | 11.86 | 4.23 | 8.90 | 114.98 | 247.81 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.40 | 11-JAN-14:20 | 10.49 | 7.20 | 8.40 | 3.89 | 99.17 | 130.33 |
February | 20.00 | 27-FEB-14:00 | 12.17 | 5.60 | 2.60 | 5.54 | 87.00 | 691.00 |
March | 20.60 | 18-MAR-15:00 | 10.43 | 0.00 | 6.20 | 6.55 | 111.50 | 465.50 |
April | 27.20 | 27-APR-15:09 | 17.22 | 11.02 | 4.10 | 12.63 | 151.33 | 598.33 |
May | 25.00 | 05-MAY-15:00 | 17.36 | 12.80 | 2.60 | 18.99 | 208.50 | 29.50 |
June | 26.70 | 28-JUN-16:00 | 16.74 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 30.60 | 24-JUL-14:00 | 18.78 | 12.20 | 3.10 | 20.75 | 267.00 | 383.50 |
August | 31.80 | 10-AUG-16:00 | 18.70 | 11.10 | 2.60 | 16.85 | 50.50 | 750.50 |
September | 25.00 | 14-SEP-16:00 | 16.69 | 11.70 | 3.10 | 13.54 | 100.50 | 235.00 |
October | 21.70 | 04-OCT-14:00 | 11.49 | 1.70 | 5.20 | 4.92 | 56.50 | 783.50 |
November | 21.10 | 04-NOV-13:00 | 15.94 | 12.80 | 0.00 | 6.95 | 52.50 | 729.00 |
December | 13.30 | 14-DEC-11:00 | 8.44 | 3.60 | 13.90 | 5.33 | 127.50 | 85.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.30 | 8.44 | 0.00 | 0.00 | 3.89 | 50.50 | 29.50 | |
Maximum of Months | 31.80 | 18.78 | 12.80 | 13.90 | 20.75 | 267.00 | 783.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -3.9 | 07-JAN-07:00 | -3.9 | -3.9 | 2.10 | -14.4 | 0.00 | 0.00 |
February | -5.6 | 19-FEB-05:10 | -6.1 | -7.3 | 3.77 | -22.8 | 0.00 | 0.00 |
March | -0.6 | 01-MAR-06:00 | -2.0 | -3.9 | 1.50 | -17.3 | 16.50 | 102.00 |
April | 1.70 | 19-APR-04:00 | 1.21 | 0.60 | 3.10 | -11.9 | 0.00 | 0.00 |
May | 4.40 | 11-MAY-02:00 | 3.92 | 3.30 | 3.10 | -10.9 | 0.00 | 0.00 |
June | 8.30 | 15-JUN-02:00 | 7.50 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
July | 11.10 | 03-JUL-03:00 | 8.19 | 5.00 | 2.60 | 5.54 | 0.00 | 0.00 |
August | 11.00 | 06-AUG-04:00 | 10.57 | 10.20 | 2.60 | -3.2 | 11.00 | 135.50 |
September | 7.20 | 27-SEP-04:49 | 6.72 | 6.20 | 0.25 | -4.0 | 0.00 | 0.00 |
October | 5.60 | 13-OCT-04:00 | 4.51 | 3.30 | 2.10 | -8.5 | 0.00 | 0.00 |
November | 0.00 | 11-NOV-06:00 | -0.2 | -0.6 | 2.10 | -16.0 | 0.00 | 0.00 |
December | -1.7 | 26-DEC-06:00 | -1.7 | -1.7 | 2.10 | -15.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -6.1 | -7.3 | 0.25 | -22.8 | 0.00 | 0.00 | |
Maximum of Months | 11.10 | 10.57 | 10.20 | 3.77 | 5.54 | 16.50 | 135.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.49 | 11-JAN-13:00 | 14.40 | 7.20 | 8.20 | 2.85 | 105.50 | 249.00 |
February | 12.42 | 27-FEB-15:00 | 19.40 | 6.70 | 2.60 | 6.35 | 88.00 | 342.50 |
March | 12.45 | 09-MAR-11:00 | 17.20 | 8.90 | 2.10 | 12.41 | 178.00 | 40.00 |
April | 17.29 | 27-APR-14:00 | 27.20 | 11.10 | 4.10 | 12.41 | 147.50 | 646.00 |
May | 17.58 | 06-MAY-12:00 | 23.90 | 13.90 | 5.20 | 15.57 | 365.50 | 282.50 |
June | 16.74 | 28-JUN-16:00 | 26.70 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 19.18 | 31-JUL-15:00 | 28.90 | 13.90 | 4.10 | 14.65 | 45.00 | 848.50 |
August | 20.13 | 29-AUG-12:00 | 28.90 | 15.70 | 2.60 | 17.39 | 136.50 | 655.00 |
September | 17.97 | 23-SEP-13:00 | 23.30 | 15.00 | 2.10 | 9.72 | 148.00 | 670.50 |
October | 15.15 | 01-OCT-11:00 | 17.20 | 13.90 | 4.60 | 13.73 | 236.50 | 63.50 |
November | 16.05 | 04-NOV-12:00 | 20.60 | 13.30 | 0.00 | 7.95 | 62.00 | 746.50 |
December | 10.71 | 16-DEC-11:00 | 11.70 | 10.00 | 6.70 | 7.35 | 89.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.49 | 11.70 | 6.70 | 0.00 | 2.85 | 45.00 | 0.00 | |
Maximum of Months | 20.13 | 28.90 | 15.70 | 8.20 | 17.39 | 365.50 | 848.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.00 | 11-JAN-21:00 | 11.10 | 10.49 | 4.60 | 6.75 | 0.00 | 0.00 |
February | 11.70 | 24-FEB-00:00 | 12.80 | 12.15 | 4.10 | 8.74 | 0.00 | 0.00 |
March | 11.70 | 09-MAR-16:00 | 12.80 | 12.15 | 2.10 | 8.74 | 37.50 | 0.00 |
April | 12.80 | 28-APR-12:00 | 16.70 | 14.35 | 4.10 | 8.35 | 265.50 | 596.00 |
May | 13.90 | 05-MAY-16:00 | 22.80 | 17.10 | 2.60 | 19.17 | 111.50 | 27.50 |
June | 13.90 | 12-JUN-12:00 | 16.70 | 15.00 | 3.60 | 13.16 | 263.50 | 0.00 |
July | 15.00 | 11-JUL-09:20 | 16.13 | 15.49 | 4.60 | 12.91 | 204.17 | 28.17 |
August | 16.40 | 30-AUG-07:00 | 17.40 | 16.77 | 5.20 | 12.41 | 168.50 | 34.50 |
September | 15.00 | 14-SEP-11:20 | 20.37 | 16.93 | 2.10 | 6.89 | 152.83 | 748.17 |
October | 13.90 | 01-OCT-10:00 | 16.70 | 15.01 | 4.10 | 13.16 | 184.50 | 0.00 |
November | 13.90 | 03-NOV-19:00 | 15.00 | 14.31 | 4.60 | 11.46 | 0.00 | 0.00 |
December | 10.00 | 16-DEC-10:00 | 11.10 | 10.48 | 7.70 | 6.75 | 81.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.00 | 11.10 | 10.48 | 2.10 | 6.75 | 0.00 | 0.00 | |
Maximum of Months | 16.40 | 22.80 | 17.10 | 7.70 | 19.17 | 265.50 | 748.17 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 11.48 | 8.35 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 11.14 | 14.81 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 11.69 | 23.26 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 12.99 | 36.00 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 14.72 | 45.46 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 16.40 | 49.26 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.58 | 51.50 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 17.95 | 42.11 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.39 | 30.76 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 16.06 | 18.91 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 14.32 | 9.65 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 12.65 | 7.39 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 14.55 | 28.19 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 11.14 | 7.39 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 17.95 | 51.50 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH LAUNDRY G WATER HEATER
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.121488E+12 | -0.119712E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.177623E+10 | 82.17 | 0.00 | 0.00 |
February | 0.110243E+12 | -0.108633E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.160915E+10 | 82.17 | 0.00 | 0.00 |
March | 0.121144E+12 | -0.119356E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.178730E+10 | 82.17 | 0.00 | 0.00 |
April | 0.115098E+12 | -0.113365E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.173287E+10 | 82.17 | 0.00 | 0.00 |
May | 0.116005E+12 | -0.114217E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.178815E+10 | 82.17 | 0.00 | 0.00 |
June | 0.109501E+12 | -0.107775E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.172568E+10 | 82.17 | 0.00 | 0.00 |
July | 0.111144E+12 | -0.109368E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.177677E+10 | 82.17 | 0.00 | 0.00 |
August | 0.110523E+12 | -0.108751E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.177135E+10 | 82.17 | 0.00 | 0.00 |
September | 0.107873E+12 | -0.106164E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.170886E+10 | 82.17 | 0.00 | 0.00 |
October | 0.113716E+12 | -0.111954E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.176229E+10 | 82.17 | 0.00 | 0.00 |
November | 0.112887E+12 | -0.111182E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.170485E+10 | 82.17 | 0.00 | 0.00 |
December | 0.119487E+12 | -0.117720E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.176718E+10 | 82.17 | 0.00 | 0.00 |
Annual Sum or Average | 0.136911E+13 | -0.134820E+13 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.209107E+11 | 82.17 | 0.00 | 0.00 |
Minimum of Months | 0.107873E+12 | -0.119712E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.178815E+10 | 82.17 | 0.00 | 0.00 |
Maximum of Months | 0.121488E+12 | -0.106164E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.160915E+10 | 82.17 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.804766E+10 | -0.788296E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164694608.6 | 82.17 | 0.00 | 0.00 |
February | 0.727208E+10 | -0.712336E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -148715182.0 | 82.17 | 0.00 | 0.00 |
March | 0.804609E+10 | -0.788155E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164534156.8 | 82.17 | 0.00 | 0.00 |
April | 0.779735E+10 | -0.763820E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -159144973.2 | 82.17 | 0.00 | 0.00 |
May | 0.804734E+10 | -0.788296E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164377361.4 | 82.17 | 0.00 | 0.00 |
June | 0.778876E+10 | -0.762976E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -158994786.4 | 82.17 | 0.00 | 0.00 |
July | 0.805565E+10 | -0.789140E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164249807.4 | 82.17 | 0.00 | 0.00 |
August | 0.804719E+10 | -0.788296E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164230507.4 | 82.17 | 0.00 | 0.00 |
September | 0.779861E+10 | -0.763961E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -159005414.6 | 82.17 | 0.00 | 0.00 |
October | 0.804600E+10 | -0.788155E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164446023.7 | 82.17 | 0.00 | 0.00 |
November | 0.778058E+10 | -0.762132E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -159259857.2 | 82.17 | 0.00 | 0.00 |
December | 0.805607E+10 | -0.789140E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164670320.7 | 82.17 | 0.00 | 0.00 |
Annual Sum or Average | 0.947834E+11 | -0.928470E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.193632E+10 | 82.17 | 0.00 | 0.00 |
Minimum of Months | 0.727208E+10 | -0.789140E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -164694608.6 | 82.17 | 0.00 | 0.00 |
Maximum of Months | 0.805607E+10 | -0.712336E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -148715182.0 | 82.17 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.724447E+11 | -0.709067E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.153799E+10 | 60.05 | 0.00 | 0.00 |
February | 0.658905E+11 | -0.644947E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.139583E+10 | 60.05 | 0.00 | 0.00 |
March | 0.722161E+11 | -0.706628E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.155333E+10 | 60.05 | 0.00 | 0.00 |
April | 0.680036E+11 | -0.664959E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.150770E+10 | 60.05 | 0.00 | 0.00 |
May | 0.677494E+11 | -0.661949E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.155452E+10 | 60.05 | 0.00 | 0.00 |
June | 0.632001E+11 | -0.617024E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.149773E+10 | 60.05 | 0.00 | 0.00 |
July | 0.635103E+11 | -0.619716E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.153873E+10 | 60.05 | 0.00 | 0.00 |
August | 0.630338E+11 | -0.615025E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.153123E+10 | 60.05 | 0.00 | 0.00 |
September | 0.617559E+11 | -0.602815E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.147441E+10 | 60.05 | 0.00 | 0.00 |
October | 0.657225E+11 | -0.642038E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.151867E+10 | 60.05 | 0.00 | 0.00 |
November | 0.660540E+11 | -0.645851E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.146885E+10 | 60.05 | 0.00 | 0.00 |
December | 0.707072E+11 | -0.691817E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.152543E+10 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.800288E+12 | -0.782184E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.181044E+11 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.617559E+11 | -0.709067E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.155452E+10 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.724447E+11 | -0.602815E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.139583E+10 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: LOBBY_FLR_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.88 | 0.86 | 01-JAN-10:09 | 2313.90 | 32.52 | 223.50 | 221.83 | 1753.65 | 33.48 | 226.67 | 177.67 |
February | 259.50 | 0.87 | 0.86 | 01-FEB-08:39 | 4072.80 | 33.17 | 241.00 | 245.50 | 1755.64 | 29.18 | 209.67 | 212.83 |
March | 247.00 | 0.87 | 0.86 | 01-MAR-07:30 | 5992.21 | 30.52 | 183.83 | 315.50 | 753.73 | 22.30 | 170.50 | 254.00 |
April | 379.50 | 0.87 | 0.86 | 01-APR-07:19 | 1564.44 | 19.76 | 106.17 | 349.67 | 605.54 | 21.50 | 244.67 | 288.17 |
May | 427.83 | 0.88 | 0.86 | 01-MAY-07:30 | 1442.36 | 19.59 | 108.50 | 389.00 | 552.25 | 21.29 | 259.83 | 317.00 |
June | 375.17 | 0.88 | 0.86 | 01-JUN-06:00 | 1222.26 | 19.58 | 57.67 | 399.50 | 490.02 | 21.32 | 256.17 | 318.00 |
July | 471.00 | 0.89 | 0.86 | 01-JUL-09:00 | 1053.37 | 18.55 | 68.33 | 397.83 | 422.07 | 20.31 | 212.17 | 289.67 |
August | 366.67 | 0.88 | 0.86 | 01-AUG-06:30 | 1218.12 | 19.63 | 53.33 | 377.83 | 495.75 | 21.37 | 240.50 | 301.50 |
September | 301.17 | 0.87 | 0.86 | 01-SEP-07:00 | 3413.00 | 24.83 | 149.17 | 322.33 | 683.10 | 22.35 | 226.00 | 269.17 |
October | 245.33 | 0.87 | 0.86 | 01-OCT-08:09 | 6361.65 | 34.77 | 221.33 | 287.33 | 913.20 | 24.24 | 188.67 | 244.33 |
November | 242.67 | 0.87 | 0.86 | 01-NOV-08:30 | 2612.59 | 32.24 | 226.33 | 228.50 | 1732.70 | 32.54 | 224.67 | 185.67 |
December | 160.33 | 0.87 | 0.86 | 01-DEC-09:39 | 3101.92 | 35.76 | 150.33 | 211.17 | 2530.32 | 36.82 | 150.33 | 154.17 |
Annual Sum or Average | 3714.00 | 0.88 | 2536.17 | 24.93 | 1789.50 | 3746.00 | 900.71 | 24.28 | 2609.83 | 3012.17 | ||
Minimum of Months | 160.33 | 0.87 | 0.86 | 1053.37 | 18.55 | 53.33 | 211.17 | 422.07 | 20.31 | 150.33 | 154.17 | |
Maximum of Months | 471.00 | 0.89 | 0.86 | 6361.65 | 35.76 | 241.00 | 399.50 | 2530.32 | 36.82 | 259.83 | 318.00 |
Report: DaylightingReportMonthly
For: CAFE_FLR_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.27 | 0.22 | 01-JAN-09:39 | 2537.74 | 32.63 | 224.33 | 233.83 | 1975.68 | 33.57 | 227.50 | 206.33 |
February | 259.50 | 0.26 | 0.22 | 01-FEB-08:30 | 4378.38 | 33.29 | 242.33 | 254.33 | 2058.85 | 29.30 | 217.33 | 232.50 |
March | 247.00 | 0.26 | 0.22 | 01-MAR-07:19 | 6368.42 | 30.77 | 184.33 | 328.67 | 1127.58 | 22.39 | 175.33 | 290.50 |
April | 379.50 | 0.27 | 0.22 | 01-APR-06:00 | 1850.55 | 20.23 | 114.17 | 362.00 | 890.56 | 21.80 | 256.17 | 327.50 |
May | 427.83 | 0.27 | 0.22 | 01-MAY-07:10 | 1692.12 | 20.16 | 134.67 | 404.33 | 801.02 | 21.68 | 288.83 | 366.17 |
June | 375.17 | 0.28 | 0.22 | 01-JUN-05:49 | 1453.91 | 20.13 | 114.00 | 418.17 | 720.93 | 21.70 | 291.83 | 371.00 |
July | 471.00 | 0.31 | 0.22 | 01-JUL-05:30 | 1274.56 | 19.13 | 103.00 | 418.67 | 642.62 | 20.71 | 233.50 | 366.67 |
August | 366.67 | 0.28 | 0.22 | 01-AUG-05:00 | 1497.50 | 19.98 | 84.83 | 394.00 | 774.37 | 21.56 | 246.00 | 352.17 |
September | 301.17 | 0.26 | 0.22 | 01-SEP-07:40 | 3775.30 | 25.02 | 157.50 | 332.00 | 1044.42 | 22.44 | 225.00 | 304.17 |
October | 245.33 | 0.27 | 0.22 | 01-OCT-07:49 | 6743.61 | 34.93 | 221.33 | 299.67 | 1295.45 | 24.23 | 186.00 | 269.83 |
November | 242.67 | 0.26 | 0.22 | 01-NOV-07:00 | 2836.08 | 32.35 | 227.67 | 239.83 | 1955.13 | 32.63 | 224.83 | 213.67 |
December | 160.33 | 0.26 | 0.22 | 01-DEC-09:39 | 3407.81 | 35.90 | 150.33 | 223.67 | 2834.37 | 36.92 | 150.33 | 192.33 |
Annual Sum or Average | 3714.00 | 0.27 | 2816.34 | 25.28 | 1958.50 | 3909.17 | 1179.77 | 24.50 | 2722.67 | 3492.83 | ||
Minimum of Months | 160.33 | 0.26 | 0.22 | 1274.56 | 19.13 | 84.83 | 223.67 | 642.62 | 20.71 | 150.33 | 192.33 | |
Maximum of Months | 471.00 | 0.31 | 0.22 | 6743.61 | 35.90 | 242.33 | 418.67 | 2834.37 | 36.92 | 291.83 | 371.00 |
Report: DaylightingReportMonthly
For: DINING_FLR_6_DAYLCTRL
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.71 | 0.60 | 03-JAN-10:30 | 350.19 | 13.75 | 0.00 | 199.67 | 149.72 | 16.99 | 0.00 | 36.17 |
February | 259.50 | 0.68 | 0.60 | 01-FEB-11:09 | 434.41 | 15.01 | 0.00 | 231.83 | 192.00 | 18.30 | 0.00 | 111.67 |
March | 247.00 | 0.65 | 0.60 | 01-MAR-09:09 | 563.11 | 16.39 | 0.00 | 315.00 | 259.94 | 19.64 | 2.33 | 206.67 |
April | 379.50 | 0.63 | 0.60 | 01-APR-07:19 | 674.58 | 17.16 | 0.00 | 360.67 | 301.35 | 20.33 | 50.50 | 304.83 |
May | 427.83 | 0.62 | 0.60 | 01-MAY-07:19 | 843.04 | 18.34 | 17.67 | 409.00 | 373.09 | 21.95 | 192.33 | 366.83 |
June | 375.17 | 0.62 | 0.60 | 01-JUN-05:30 | 876.37 | 19.62 | 40.17 | 427.00 | 408.72 | 23.56 | 225.17 | 391.33 |
July | 471.00 | 0.64 | 0.60 | 01-JUL-04:00 | 735.34 | 18.60 | 48.00 | 435.17 | 344.16 | 22.67 | 207.67 | 340.17 |
August | 366.67 | 0.63 | 0.60 | 01-AUG-05:40 | 627.16 | 17.86 | 13.17 | 400.00 | 293.70 | 21.05 | 83.33 | 332.33 |
September | 301.17 | 0.63 | 0.60 | 01-SEP-07:49 | 600.90 | 17.20 | 0.00 | 325.00 | 285.74 | 20.41 | 25.33 | 254.17 |
October | 245.33 | 0.67 | 0.60 | 01-OCT-08:50 | 451.85 | 15.60 | 0.00 | 276.00 | 215.84 | 18.93 | 0.17 | 145.83 |
November | 242.67 | 0.70 | 0.60 | 01-NOV-11:39 | 378.80 | 14.21 | 0.00 | 212.00 | 160.91 | 17.43 | 0.00 | 51.33 |
December | 160.33 | 0.72 | 0.60 | 01-DEC-10:20 | 316.81 | 13.88 | 0.00 | 179.33 | 149.55 | 17.36 | 0.00 | 27.00 |
Annual Sum or Average | 3714.00 | 0.65 | 616.97 | 16.94 | 119.00 | 3770.67 | 282.39 | 20.41 | 786.83 | 2568.33 | ||
Minimum of Months | 160.33 | 0.62 | 0.60 | 316.81 | 13.75 | 0.00 | 179.33 | 149.55 | 16.99 | 0.00 | 27.00 | |
Maximum of Months | 471.00 | 0.72 | 0.60 | 876.37 | 19.62 | 48.00 | 435.17 | 408.72 | 23.56 | 225.17 | 391.33 |
Report: DaylightingReportMonthly
For: BANQUET_FLR_6_DAYLCTRL
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.71 | 0.60 | 03-JAN-10:30 | 350.19 | 13.75 | 0.00 | 199.67 | 149.72 | 16.99 | 0.00 | 36.17 |
February | 259.50 | 0.68 | 0.60 | 01-FEB-11:09 | 434.41 | 15.01 | 0.00 | 231.83 | 192.00 | 18.30 | 0.00 | 111.67 |
March | 247.00 | 0.65 | 0.60 | 01-MAR-09:09 | 563.11 | 16.39 | 0.00 | 315.00 | 259.94 | 19.64 | 2.33 | 206.67 |
April | 379.50 | 0.63 | 0.60 | 01-APR-07:19 | 674.58 | 17.16 | 0.00 | 360.67 | 301.35 | 20.33 | 50.50 | 304.83 |
May | 427.83 | 0.62 | 0.60 | 01-MAY-07:19 | 843.04 | 18.34 | 17.67 | 409.00 | 373.09 | 21.95 | 192.33 | 366.83 |
June | 375.17 | 0.62 | 0.60 | 01-JUN-05:30 | 876.37 | 19.62 | 40.17 | 427.00 | 408.72 | 23.56 | 225.17 | 391.33 |
July | 471.00 | 0.64 | 0.60 | 01-JUL-04:00 | 735.34 | 18.60 | 48.00 | 435.17 | 344.16 | 22.67 | 207.67 | 340.17 |
August | 366.67 | 0.63 | 0.60 | 01-AUG-05:40 | 627.16 | 17.86 | 13.17 | 400.00 | 293.70 | 21.05 | 83.33 | 332.33 |
September | 301.17 | 0.63 | 0.60 | 01-SEP-07:49 | 600.90 | 17.20 | 0.00 | 325.00 | 285.74 | 20.41 | 25.33 | 254.17 |
October | 245.33 | 0.67 | 0.60 | 01-OCT-08:50 | 451.85 | 15.60 | 0.00 | 276.00 | 215.84 | 18.93 | 0.17 | 145.83 |
November | 242.67 | 0.70 | 0.60 | 01-NOV-11:39 | 378.80 | 14.21 | 0.00 | 212.00 | 160.91 | 17.43 | 0.00 | 51.33 |
December | 160.33 | 0.72 | 0.60 | 01-DEC-10:20 | 316.81 | 13.88 | 0.00 | 179.33 | 149.55 | 17.36 | 0.00 | 27.00 |
Annual Sum or Average | 3714.00 | 0.65 | 616.97 | 16.94 | 119.00 | 3770.67 | 282.39 | 20.41 | 786.83 | 2568.33 | ||
Minimum of Months | 160.33 | 0.62 | 0.60 | 316.81 | 13.75 | 0.00 | 179.33 | 149.55 | 16.99 | 0.00 | 27.00 | |
Maximum of Months | 471.00 | 0.72 | 0.60 | 876.37 | 19.62 | 48.00 | 435.17 | 408.72 | 23.56 | 225.17 | 391.33 |
Report: CoilReportMonthly
For: FLR_3_DOAS HEATING COIL
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.107885E+09 | 1467.73 | 07-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 94116059.72 | 2209.45 | 19-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 14570.92 | 21.20 | 01-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5374.59 | 0.53 | 26-APR-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 7907.92 | 0.53 | 05-MAY-08:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 24976.93 | 0.53 | 21-JUN-22:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 25196.21 | 0.54 | 30-JUL-03:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 28778.06 | 0.53 | 26-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 21135.78 | 0.54 | 23-SEP-22:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4594.50 | 0.53 | 05-OCT-12:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 134237.44 | 221.09 | 30-NOV-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 14198385.80 | 2203.07 | 26-DEC-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.216466E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 4594.50 | 0.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.107885E+09 | 2209.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.416026E+11 | 121549.82 | 20-JAN-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.568448E+11 | 133958.02 | 08-FEB-11:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.858799E+11 | 119564.07 | 03-MAR-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.911593E+11 | 118060.58 | 25-APR-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.840791E+11 | 112555.94 | 21-MAY-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.432190E+11 | 98195.93 | 15-JUN-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.161707E+11 | 58196.05 | 07-JUL-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.123476E+11 | 58254.14 | 21-AUG-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.448933E+11 | 101700.08 | 28-SEP-05:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.113700E+12 | 119477.12 | 12-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.757441E+11 | 137305.51 | 11-NOV-11:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.497012E+11 | 127591.54 | 21-DEC-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.715342E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.123476E+11 | 58196.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.113700E+12 | 137305.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.315281E+10 | 1928.68 | 16-JAN-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.206333E+10 | 2083.77 | 19-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.158188E+10 | 1588.95 | 05-MAR-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.899391E+09 | 1294.56 | 18-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.562584E+09 | 1071.65 | 18-MAY-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.265343E+09 | 903.65 | 14-JUN-10:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 83400762.73 | 693.60 | 12-JUL-10:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.111127E+09 | 616.01 | 22-AUG-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.381780E+09 | 1245.85 | 26-SEP-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.108124E+10 | 1374.75 | 27-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.226794E+10 | 1878.27 | 30-NOV-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.297329E+10 | 2182.06 | 26-DEC-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.154241E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 83400762.73 | 616.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.315281E+10 | 2182.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 39341566.01 | 374.38 | 17-JAN-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11392824.72 | 290.94 | 17-FEB-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 90030.76 | 46.69 | 05-MAR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5203445.79 | 174.09 | 26-NOV-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 39914865.79 | 402.81 | 26-DEC-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95942733.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 39914865.79 | 402.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.491234E+09 | 650.14 | 16-JAN-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.253128E+09 | 552.05 | 20-FEB-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 10164493.56 | 257.67 | 05-MAR-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 94564333.79 | 376.83 | 26-NOV-17:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.343038E+09 | 645.44 | 26-DEC-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.119213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.491234E+09 | 650.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.616756E+09 | 511.30 | 16-JAN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.359086E+09 | 478.44 | 19-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 60730578.57 | 308.55 | 05-MAR-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3115063.43 | 157.07 | 19-APR-10:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1662944.99 | 93.11 | 31-OCT-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.213314E+09 | 364.22 | 30-NOV-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.501229E+09 | 519.74 | 26-DEC-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.175589E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.616756E+09 | 519.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.104559E+09 | 1202.40 | 17-JAN-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 66522406.29 | 1202.38 | 18-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 31958224.03 | 800.03 | 06-MAR-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 12687994.15 | 640.52 | 01-APR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1770397.43 | 245.97 | 18-MAY-03:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 38391.82 | 63.99 | 14-JUN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 566747.78 | 186.45 | 27-SEP-03:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 12952952.97 | 586.18 | 28-OCT-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 46087017.98 | 954.64 | 13-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 99469170.08 | 1202.40 | 26-DEC-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.376613E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.104559E+09 | 1202.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.240613E+10 | 4843.10 | 26-JAN-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.114386E+10 | 4839.17 | 17-FEB-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.741264E+09 | 3725.91 | 22-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.187395E+09 | 2797.42 | 10-APR-10:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 96782293.64 | 2544.97 | 17-MAY-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 20549157.80 | 2239.81 | 14-JUN-10:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 8935077.15 | 1867.88 | 12-JUL-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 3362755.39 | 1322.07 | 01-AUG-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.129895E+09 | 3267.01 | 26-SEP-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.430158E+09 | 3563.98 | 27-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.148737E+10 | 4960.52 | 30-NOV-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.225888E+10 | 5823.91 | 26-DEC-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.891458E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 3362755.39 | 1322.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.240613E+10 | 5823.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.445884E+09 | 6102.42 | 16-JAN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 95286855.88 | 4748.54 | 17-FEB-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2077552.31 | 1061.23 | 05-MAR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 84357083.75 | 3589.84 | 30-NOV-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.498001E+09 | 7293.09 | 26-DEC-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.112561E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.498001E+09 | 7293.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.706121E+10 | 6294.52 | 16-JAN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.374174E+10 | 5984.06 | 17-FEB-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.114026E+10 | 4296.93 | 05-MAR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 82676080.48 | 2450.28 | 11-APR-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.534489E+09 | 3782.73 | 31-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.380769E+10 | 5859.66 | 30-NOV-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.632350E+10 | 6862.05 | 26-DEC-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.226916E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.706121E+10 | 6862.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.358555E+10 | 2807.22 | 16-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.205237E+10 | 3159.85 | 19-FEB-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.681739E+09 | 1607.75 | 25-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.132265E+09 | 1299.11 | 18-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 229608.56 | 245.86 | 28-SEP-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.242731E+09 | 1249.44 | 31-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.177788E+10 | 2416.27 | 30-NOV-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.325980E+10 | 3195.10 | 26-DEC-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.117326E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.358555E+10 | 3195.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.354306E+10 | 4974.52 | 01-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.214739E+10 | 4971.45 | 16-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.116247E+10 | 4903.72 | 05-MAR-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453309E+09 | 4813.54 | 18-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.117062E+09 | 4333.59 | 28-MAY-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 25739043.85 | 4470.30 | 13-JUN-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 8899479.02 | 3970.44 | 31-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 12814736.56 | 4149.02 | 08-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 58511823.03 | 4366.60 | 27-SEP-15:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.607686E+09 | 4814.56 | 27-OCT-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.205874E+10 | 4974.29 | 29-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.327082E+10 | 4975.09 | 16-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.134665E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 8899479.02 | 3970.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.354306E+10 | 4975.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.409125E+10 | 4905.86 | 01-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.273652E+10 | 4905.15 | 16-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.155086E+10 | 4857.35 | 05-MAR-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.594429E+09 | 4752.05 | 18-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.129242E+09 | 4265.55 | 11-MAY-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 29059818.44 | 4548.24 | 06-JUN-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 8627019.47 | 4137.06 | 25-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11531299.13 | 4535.28 | 23-AUG-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 67127199.61 | 4457.04 | 21-SEP-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.864522E+09 | 4767.13 | 31-OCT-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.248247E+10 | 4905.65 | 26-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.384123E+10 | 4906.47 | 16-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.164069E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 8627019.47 | 4137.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.409125E+10 | 4906.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.912973E+10 | 27233.78 | 07-JAN-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.589629E+10 | 27120.88 | 19-FEB-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.142802E+10 | 26439.57 | 24-MAR-15:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.288920E+09 | 26442.70 | 06-APR-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 72645115.45 | 26452.03 | 24-MAY-15:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 28560525.17 | 26438.64 | 04-JUN-15:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 28433221.01 | 26395.39 | 16-JUL-15:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 41985644.09 | 25904.61 | 02-AUG-15:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 85405480.62 | 26444.06 | 24-SEP-15:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.437799E+09 | 25760.62 | 12-OCT-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.337516E+10 | 26979.66 | 30-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.780201E+10 | 27317.85 | 26-DEC-16:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.286149E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 28433221.01 | 25760.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.912973E+10 | 27317.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.358143E+10 | 4906.47 | 01-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.217007E+10 | 4905.76 | 16-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.113883E+10 | 4828.45 | 05-MAR-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.431036E+09 | 4738.87 | 18-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.148381E+09 | 4248.35 | 29-MAY-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 27431613.53 | 4441.28 | 14-JUN-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 10015896.80 | 4580.56 | 16-JUL-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 10465886.00 | 4422.63 | 17-AUG-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 69889737.55 | 4635.47 | 21-SEP-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.631880E+09 | 4754.06 | 31-OCT-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.207858E+10 | 4906.21 | 29-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.331342E+10 | 4907.07 | 16-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.136114E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 10015896.80 | 4248.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.358143E+10 | 4907.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.414015E+10 | 4839.17 | 01-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.274455E+10 | 4838.41 | 16-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.148778E+10 | 4783.05 | 05-MAR-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.555022E+09 | 4678.80 | 18-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.168757E+09 | 4574.39 | 29-MAY-19:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 29787337.83 | 4502.38 | 07-JUN-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 8558190.61 | 4297.37 | 01-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7121109.56 | 4281.13 | 03-AUG-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 87005936.91 | 4572.89 | 06-SEP-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.883392E+09 | 4709.53 | 31-OCT-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.248155E+10 | 4838.94 | 26-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.386294E+10 | 4839.81 | 16-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.164566E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 7121109.56 | 4281.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.414015E+10 | 4839.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.129035E+10 | 1489.69 | 01-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.818187E+09 | 1489.64 | 15-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.488679E+09 | 1489.51 | 05-MAR-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.213699E+09 | 1461.08 | 18-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 79528028.83 | 1443.03 | 18-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 19695306.03 | 1052.89 | 06-JUN-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 2564776.76 | 1142.32 | 04-JUL-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 4457550.77 | 1012.14 | 17-AUG-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 37910622.00 | 1122.06 | 27-SEP-15:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.288386E+09 | 1461.68 | 27-OCT-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.796144E+09 | 1489.61 | 26-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.120228E+10 | 1489.90 | 16-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.524188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 2564776.76 | 1012.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.129035E+10 | 1489.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.146052E+10 | 1464.74 | 01-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.100395E+10 | 1464.69 | 15-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.619387E+09 | 1464.55 | 05-MAR-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.265903E+09 | 1437.96 | 18-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 81232644.94 | 1417.13 | 18-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 18650450.34 | 1216.97 | 27-JUN-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1888546.12 | 1005.76 | 19-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 3066654.88 | 1066.17 | 23-AUG-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 42687168.82 | 1405.21 | 28-SEP-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.387822E+09 | 1443.24 | 31-OCT-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.929411E+09 | 1464.73 | 17-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.138096E+10 | 1464.97 | 16-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.619548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1888546.12 | 1005.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.146052E+10 | 1464.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.358716E+10 | 7309.67 | 26-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.195500E+10 | 7232.13 | 16-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.899887E+09 | 7114.12 | 05-MAR-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.394923E+09 | 6534.10 | 18-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.147748E+09 | 6194.94 | 24-MAY-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 37001244.38 | 5855.58 | 07-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 15327838.75 | 6152.42 | 12-JUL-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 18601738.41 | 5723.35 | 18-AUG-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 63873192.97 | 5913.03 | 28-SEP-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.397906E+09 | 6287.76 | 27-OCT-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.182137E+10 | 7309.43 | 30-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.337676E+10 | 7309.89 | 17-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.127156E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 15327838.75 | 5723.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.358716E+10 | 7309.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.108438E+09 | 0.108438E+09 | 9635.08 | 27-FEB-16:09 | 9635.08 | 0.00 |
March | 0.00 | 0.00 | 0.232884E+09 | 0.232884E+09 | 12388.66 | 18-MAR-16:00 | 12388.66 | 0.01 |
April | 0.00 | 0.00 | 0.179842E+10 | 0.179842E+10 | 18212.60 | 27-APR-15:02 | 18212.60 | 0.04 |
May | 0.00 | 0.00 | 0.355559E+10 | 0.343568E+10 | 20677.56 | 05-MAY-18:03 | 16125.17 | 0.14 |
June | 0.00 | 0.00 | 0.630895E+10 | 0.630895E+10 | 17791.40 | 28-JUN-15:02 | 17791.40 | 0.32 |
July | 0.00 | 0.00 | 0.116585E+11 | 0.109079E+11 | 23708.15 | 15-JUL-18:03 | 15807.51 | 0.51 |
August | 0.00 | 0.00 | 0.152262E+11 | 0.141063E+11 | 24768.28 | 30-AUG-12:40 | 15889.63 | 0.61 |
September | 0.00 | 0.00 | 0.544189E+10 | 0.511333E+10 | 22992.79 | 14-SEP-12:50 | 15654.77 | 0.32 |
October | 0.00 | 0.00 | 0.903800E+09 | 0.903800E+09 | 14148.91 | 04-OCT-15:01 | 14148.91 | 0.06 |
November | 0.00 | 0.00 | 0.218215E+09 | 0.196313E+09 | 15659.16 | 04-NOV-15:01 | 13199.77 | 0.02 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.454529E+11 | 0.431120E+11 | 0.17 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.152262E+11 | 0.141063E+11 | 24768.28 | 18212.60 | 0.61 |
Report: CoilReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.177965E+10 | 0.177965E+10 | 78982.59 | 27-FEB-15:00 | 78982.59 | 0.01 |
March | 0.00 | 0.00 | 0.394681E+10 | 0.394681E+10 | 104148.08 | 18-MAR-16:10 | 104148.08 | 0.02 |
April | 0.00 | 0.00 | 0.284700E+11 | 0.284700E+11 | 204755.85 | 27-APR-18:10 | 204755.85 | 0.07 |
May | 0.00 | 0.00 | 0.551595E+11 | 0.548024E+11 | 206707.51 | 05-MAY-18:00 | 171305.65 | 0.21 |
June | 0.00 | 0.00 | 0.986138E+11 | 0.985076E+11 | 209018.02 | 28-JUN-18:10 | 209018.02 | 0.46 |
July | 0.00 | 0.00 | 0.166404E+12 | 0.161479E+12 | 264497.45 | 27-JUL-18:03 | 202410.67 | 0.68 |
August | 0.00 | 0.00 | 0.209638E+12 | 0.201849E+12 | 286685.50 | 10-AUG-18:10 | 248114.84 | 0.79 |
September | 0.00 | 0.00 | 0.803282E+11 | 0.784403E+11 | 198570.87 | 14-SEP-17:15 | 179635.18 | 0.47 |
October | 0.00 | 0.00 | 0.149889E+11 | 0.149718E+11 | 124339.99 | 04-OCT-15:15 | 124339.99 | 0.10 |
November | 0.00 | 0.00 | 0.341840E+10 | 0.341840E+10 | 102902.96 | 04-NOV-14:30 | 102902.96 | 0.04 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.662748E+12 | 0.647665E+12 | 0.24 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.209638E+12 | 0.201849E+12 | 286685.50 | 248114.84 | 0.79 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 10367649.58 | 6049164.85 | 12746.79 | 05-JAN-16:01 | 12746.79 | 0.00 |
February | 0.00 | 0.00 | 0.220335E+09 | 0.104331E+09 | 16838.06 | 12-FEB-16:01 | 16838.06 | 0.08 |
March | 0.00 | 0.00 | 0.784666E+09 | 0.485889E+09 | 16838.93 | 28-MAR-15:01 | 16838.93 | 0.16 |
April | 0.00 | 0.00 | 0.228306E+10 | 0.125430E+10 | 16833.78 | 13-APR-18:01 | 16833.78 | 0.47 |
May | 0.00 | 0.00 | 0.426025E+10 | 0.233314E+10 | 16840.09 | 20-MAY-18:01 | 16840.09 | 0.71 |
June | 0.00 | 0.00 | 0.502958E+10 | 0.254741E+10 | 16995.33 | 12-JUN-15:01 | 13917.39 | 0.85 |
July | 0.00 | 0.00 | 0.783209E+10 | 0.437955E+10 | 16525.47 | 16-JUL-15:01 | 14305.75 | 0.91 |
August | 0.00 | 0.00 | 0.764520E+10 | 0.419540E+10 | 17228.09 | 30-AUG-08:62 | 12555.05 | 0.90 |
September | 0.00 | 0.00 | 0.511176E+10 | 0.261404E+10 | 16527.19 | 23-SEP-08:61 | 14296.41 | 0.79 |
October | 0.00 | 0.00 | 0.149068E+10 | 0.699597E+09 | 16839.66 | 03-OCT-18:01 | 16839.66 | 0.37 |
November | 0.00 | 0.00 | 0.173443E+09 | 66535432.22 | 17054.25 | 05-NOV-15:01 | 13878.91 | 0.07 |
December | 0.00 | 0.00 | 24451951.66 | 13301003.62 | 14991.55 | 10-DEC-16:01 | 14329.93 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.348659E+11 | 0.186996E+11 | 0.45 | |||
Minimum of Months | 0.00 | 0.00 | 10367649.58 | 6049164.85 | 12746.79 | 12555.05 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.783209E+10 | 0.437955E+10 | 17228.09 | 16840.09 | 0.91 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 1356388.22 | 251363.27 | 1421.33 | 20-JAN-16:03 | 444.61 | 0.00 |
February | 0.00 | 0.00 | 47358347.19 | 20279881.12 | 14008.45 | 12-FEB-16:01 | 14008.45 | 0.02 |
March | 0.00 | 0.00 | 0.257554E+09 | 0.146797E+09 | 15102.86 | 25-MAR-15:01 | 15102.86 | 0.07 |
April | 0.00 | 0.00 | 0.125531E+10 | 0.635699E+09 | 17674.76 | 25-APR-17:41 | 17674.76 | 0.32 |
May | 0.00 | 0.00 | 0.255917E+10 | 0.118639E+10 | 15667.62 | 08-MAY-20:01 | 14250.55 | 0.56 |
June | 0.00 | 0.00 | 0.334869E+10 | 0.157633E+10 | 16133.74 | 22-JUN-21:51 | 14277.23 | 0.63 |
July | 0.00 | 0.00 | 0.526460E+10 | 0.283200E+10 | 17448.54 | 15-JUL-21:51 | 14126.48 | 0.67 |
August | 0.00 | 0.00 | 0.515946E+10 | 0.278664E+10 | 16059.82 | 26-AUG-21:51 | 12212.93 | 0.66 |
September | 0.00 | 0.00 | 0.256435E+10 | 0.102994E+10 | 16037.85 | 24-SEP-18:11 | 13032.72 | 0.56 |
October | 0.00 | 0.00 | 0.501741E+09 | 0.183897E+09 | 15584.61 | 01-OCT-15:01 | 12506.07 | 0.21 |
November | 0.00 | 0.00 | 37433914.07 | 12256786.94 | 15313.45 | 05-NOV-15:01 | 11847.75 | 0.02 |
December | 0.00 | 0.00 | 2600525.61 | 912733.46 | 4251.77 | 10-DEC-16:01 | 1859.79 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.209996E+11 | 0.104114E+11 | 0.31 | |||
Minimum of Months | 0.00 | 0.00 | 1356388.22 | 251363.27 | 1421.33 | 444.61 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.526460E+10 | 0.283200E+10 | 17674.76 | 17674.76 | 0.67 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.398136E+10 | 0.345728E+10 | 37380.75 | 08-FEB-13:40 | 37380.75 | 0.04 |
March | 0.00 | 0.00 | 0.119107E+11 | 0.843996E+10 | 47719.56 | 02-MAR-13:00 | 41340.91 | 0.19 |
April | 0.00 | 0.00 | 0.193943E+11 | 0.909172E+10 | 43942.81 | 27-APR-13:00 | 31540.88 | 0.56 |
May | 0.00 | 0.00 | 0.246056E+11 | 0.854564E+10 | 43083.26 | 04-MAY-13:00 | 29481.49 | 0.76 |
June | 0.00 | 0.00 | 0.272618E+11 | 0.873149E+10 | 32629.85 | 28-JUN-13:00 | 17271.06 | 0.87 |
July | 0.00 | 0.00 | 0.377326E+11 | 0.136682E+11 | 41194.86 | 31-JUL-12:50 | 26151.68 | 0.96 |
August | 0.00 | 0.00 | 0.428340E+11 | 0.177077E+11 | 51050.96 | 24-AUG-13:00 | 40492.40 | 0.95 |
September | 0.00 | 0.00 | 0.363342E+11 | 0.165338E+11 | 54044.42 | 14-SEP-13:15 | 46053.25 | 0.88 |
October | 0.00 | 0.00 | 0.209240E+11 | 0.923041E+10 | 54983.46 | 04-OCT-12:40 | 50437.90 | 0.60 |
November | 0.00 | 0.00 | 0.357538E+10 | 0.131882E+10 | 44767.79 | 04-NOV-13:25 | 30918.43 | 0.14 |
December | 0.00 | 0.00 | 0.174235E+10 | 0.163441E+10 | 33996.75 | 05-DEC-12:30 | 33996.75 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.230296E+12 | 0.983594E+11 | 0.50 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.428340E+11 | 0.177077E+11 | 54983.46 | 50437.90 | 0.96 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.127853E+10 | 0.414090E+09 | 63145.74 | 01-JAN-09:02 | 63145.74 | 0.13 |
February | 0.00 | 0.00 | 0.336465E+10 | 0.126126E+10 | 76049.44 | 25-FEB-09:02 | 67722.04 | 0.23 |
March | 0.00 | 0.00 | 0.797714E+10 | 0.395410E+10 | 76739.66 | 18-MAR-20:42 | 76739.66 | 0.39 |
April | 0.00 | 0.00 | 0.164513E+11 | 0.886768E+10 | 78093.30 | 20-APR-18:01 | 78093.30 | 0.57 |
May | 0.00 | 0.00 | 0.261891E+11 | 0.154526E+11 | 81551.40 | 06-MAY-21:51 | 68988.80 | 0.61 |
June | 0.00 | 0.00 | 0.318460E+11 | 0.199549E+11 | 80341.17 | 12-JUN-18:01 | 68987.45 | 0.59 |
July | 0.00 | 0.00 | 0.373715E+11 | 0.239237E+11 | 85347.82 | 26-JUL-21:51 | 69811.36 | 0.58 |
August | 0.00 | 0.00 | 0.374883E+11 | 0.223534E+11 | 85952.31 | 26-AUG-21:51 | 67398.15 | 0.58 |
September | 0.00 | 0.00 | 0.255177E+11 | 0.131501E+11 | 82815.27 | 15-SEP-21:51 | 68190.29 | 0.56 |
October | 0.00 | 0.00 | 0.125895E+11 | 0.533314E+10 | 80385.17 | 01-OCT-15:01 | 65454.31 | 0.58 |
November | 0.00 | 0.00 | 0.565920E+10 | 0.198128E+10 | 76211.58 | 04-NOV-15:01 | 64929.41 | 0.35 |
December | 0.00 | 0.00 | 0.119099E+10 | 0.461661E+09 | 74807.91 | 03-DEC-09:02 | 74807.91 | 0.13 |
Annual Sum or Average | 0.00 | 0.00 | 0.206924E+12 | 0.117108E+12 | 0.44 | |||
Minimum of Months | 0.00 | 0.00 | 0.119099E+10 | 0.414090E+09 | 63145.74 | 63145.74 | 0.13 | |
Maximum of Months | 0.00 | 0.00 | 0.374883E+11 | 0.239237E+11 | 85952.31 | 78093.30 | 0.61 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 6761682.63 | 1184824.20 | 1572.81 | 20-JAN-16:02 | 523.43 | 0.01 |
February | 0.00 | 0.00 | 0.198050E+09 | 85848414.78 | 14498.98 | 12-FEB-16:01 | 14498.98 | 0.07 |
March | 0.00 | 0.00 | 0.751570E+09 | 0.441640E+09 | 15212.93 | 28-MAR-15:01 | 15212.93 | 0.18 |
April | 0.00 | 0.00 | 0.236585E+10 | 0.121383E+10 | 15022.04 | 30-APR-15:01 | 12378.49 | 0.51 |
May | 0.00 | 0.00 | 0.370808E+10 | 0.185995E+10 | 15211.59 | 14-MAY-18:01 | 15211.59 | 0.70 |
June | 0.00 | 0.00 | 0.535543E+10 | 0.276254E+10 | 14704.87 | 12-JUN-15:01 | 13085.65 | 0.88 |
July | 0.00 | 0.00 | 0.683111E+10 | 0.360811E+10 | 15530.27 | 16-JUL-15:01 | 12463.75 | 0.93 |
August | 0.00 | 0.00 | 0.755454E+10 | 0.412684E+10 | 15640.78 | 30-AUG-08:62 | 11552.11 | 0.93 |
September | 0.00 | 0.00 | 0.461389E+10 | 0.232205E+10 | 15480.96 | 24-SEP-15:01 | 12496.89 | 0.78 |
October | 0.00 | 0.00 | 0.147376E+10 | 0.676987E+09 | 15958.36 | 01-OCT-15:01 | 12120.08 | 0.40 |
November | 0.00 | 0.00 | 0.183456E+09 | 57312453.87 | 15264.12 | 05-NOV-15:01 | 12229.82 | 0.07 |
December | 0.00 | 0.00 | 55759226.55 | 20551316.70 | 11053.03 | 02-DEC-09:02 | 10740.82 | 0.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.330983E+11 | 0.171769E+11 | 0.46 | |||
Minimum of Months | 0.00 | 0.00 | 6761682.63 | 1184824.20 | 1572.81 | 523.43 | 0.01 | |
Maximum of Months | 0.00 | 0.00 | 0.755454E+10 | 0.412684E+10 | 15958.36 | 15212.93 | 0.93 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 1167286.50 | 218781.49 | 1156.48 | 27-JAN-19:06 | 267.81 | 0.00 |
February | 0.00 | 0.00 | 26962366.04 | 9705940.86 | 11063.55 | 27-FEB-16:01 | 11063.55 | 0.02 |
March | 0.00 | 0.00 | 0.206922E+09 | 0.117763E+09 | 13905.82 | 25-MAR-08:61 | 13905.82 | 0.07 |
April | 0.00 | 0.00 | 0.135549E+10 | 0.663145E+09 | 13837.86 | 25-APR-18:01 | 13837.86 | 0.36 |
May | 0.00 | 0.00 | 0.239386E+10 | 0.115738E+10 | 14551.90 | 06-MAY-08:51 | 14196.97 | 0.56 |
June | 0.00 | 0.00 | 0.386189E+10 | 0.200963E+10 | 14030.75 | 12-JUN-18:01 | 11443.19 | 0.69 |
July | 0.00 | 0.00 | 0.469090E+10 | 0.245401E+10 | 16658.91 | 31-JUL-08:32 | 15278.55 | 0.70 |
August | 0.00 | 0.00 | 0.516350E+10 | 0.274949E+10 | 16865.73 | 10-AUG-08:32 | 15325.50 | 0.70 |
September | 0.00 | 0.00 | 0.243866E+10 | 0.110653E+10 | 14461.35 | 24-SEP-15:01 | 11111.16 | 0.56 |
October | 0.00 | 0.00 | 0.532710E+09 | 0.237209E+09 | 14522.44 | 01-OCT-15:01 | 10340.90 | 0.20 |
November | 0.00 | 0.00 | 37320501.03 | 10998431.23 | 13568.60 | 05-NOV-15:01 | 10191.58 | 0.02 |
December | 0.00 | 0.00 | 2546414.82 | 686184.57 | 3338.17 | 02-DEC-09:02 | 1868.21 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.207119E+11 | 0.105168E+11 | 0.32 | |||
Minimum of Months | 0.00 | 0.00 | 1167286.50 | 218781.49 | 1156.48 | 267.81 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.516350E+10 | 0.274949E+10 | 16865.73 | 15325.50 | 0.70 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 2192228.88 | 1408926.32 | 3274.88 | 05-JAN-16:01 | 3237.78 | 0.00 |
February | 0.00 | 0.00 | 54066503.67 | 27452591.81 | 4390.20 | 12-FEB-16:01 | 4390.20 | 0.05 |
March | 0.00 | 0.00 | 0.196455E+09 | 0.128358E+09 | 4390.60 | 28-MAR-15:01 | 4390.60 | 0.12 |
April | 0.00 | 0.00 | 0.575201E+09 | 0.340481E+09 | 4486.10 | 30-APR-08:61 | 3365.09 | 0.38 |
May | 0.00 | 0.00 | 0.107673E+10 | 0.637987E+09 | 4390.24 | 20-MAY-18:01 | 4390.24 | 0.62 |
June | 0.00 | 0.00 | 0.126726E+10 | 0.683854E+09 | 4408.03 | 12-JUN-15:01 | 3645.54 | 0.79 |
July | 0.00 | 0.00 | 0.199780E+10 | 0.117562E+10 | 4418.73 | 15-JUL-08:61 | 3613.21 | 0.90 |
August | 0.00 | 0.00 | 0.190064E+10 | 0.109123E+10 | 4592.38 | 20-AUG-08:61 | 3225.65 | 0.88 |
September | 0.00 | 0.00 | 0.123509E+10 | 0.677452E+09 | 4564.86 | 23-SEP-08:61 | 3391.54 | 0.72 |
October | 0.00 | 0.00 | 0.336503E+09 | 0.174360E+09 | 4544.38 | 01-OCT-08:62 | 3179.33 | 0.28 |
November | 0.00 | 0.00 | 41900589.23 | 18045904.95 | 4487.39 | 05-NOV-15:01 | 3585.16 | 0.05 |
December | 0.00 | 0.00 | 5255959.83 | 2943633.72 | 4001.85 | 10-DEC-16:01 | 3688.94 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.868909E+10 | 0.495920E+10 | 0.40 | |||
Minimum of Months | 0.00 | 0.00 | 2192228.88 | 1408926.32 | 3274.88 | 3179.33 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.199780E+10 | 0.117562E+10 | 4592.38 | 4390.60 | 0.90 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 177959.83 | 32661.36 | 346.08 | 20-JAN-16:05 | 102.42 | 0.00 |
February | 0.00 | 0.00 | 9398724.44 | 3815606.67 | 3618.99 | 26-FEB-16:01 | 3439.78 | 0.02 |
March | 0.00 | 0.00 | 58883214.72 | 34430336.28 | 3893.02 | 25-MAR-15:01 | 3893.02 | 0.05 |
April | 0.00 | 0.00 | 0.310058E+09 | 0.170709E+09 | 4574.65 | 25-APR-17:41 | 4574.65 | 0.25 |
May | 0.00 | 0.00 | 0.649119E+09 | 0.326146E+09 | 4575.60 | 21-MAY-17:41 | 4575.60 | 0.49 |
June | 0.00 | 0.00 | 0.860962E+09 | 0.428483E+09 | 4342.25 | 22-JUN-21:51 | 3806.88 | 0.60 |
July | 0.00 | 0.00 | 0.139279E+10 | 0.772536E+09 | 4626.26 | 26-JUL-21:51 | 3677.71 | 0.69 |
August | 0.00 | 0.00 | 0.130159E+10 | 0.735660E+09 | 4300.23 | 11-AUG-21:51 | 3570.57 | 0.66 |
September | 0.00 | 0.00 | 0.595839E+09 | 0.253485E+09 | 4240.37 | 13-SEP-21:51 | 3487.10 | 0.50 |
October | 0.00 | 0.00 | 93671335.49 | 37543185.37 | 4088.31 | 01-OCT-08:62 | 2843.18 | 0.13 |
November | 0.00 | 0.00 | 7750853.19 | 2571218.02 | 4046.14 | 05-NOV-15:01 | 3000.41 | 0.01 |
December | 0.00 | 0.00 | 187484.93 | 67757.81 | 323.64 | 29-DEC-19:06 | 64.48 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.528043E+10 | 0.276548E+10 | 0.29 | |||
Minimum of Months | 0.00 | 0.00 | 177959.83 | 32661.36 | 323.64 | 64.48 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.139279E+10 | 0.772536E+09 | 4626.26 | 4575.60 | 0.69 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.455824E+09 | 0.203203E+09 | 20036.61 | 05-JAN-16:01 | 20036.61 | 0.08 |
February | 0.00 | 0.00 | 0.176052E+10 | 0.961059E+09 | 22633.93 | 28-FEB-16:01 | 21333.92 | 0.25 |
March | 0.00 | 0.00 | 0.302958E+10 | 0.191849E+10 | 24114.24 | 25-MAR-15:01 | 24114.24 | 0.35 |
April | 0.00 | 0.00 | 0.469085E+10 | 0.245489E+10 | 24464.34 | 30-APR-15:01 | 19903.15 | 0.60 |
May | 0.00 | 0.00 | 0.599950E+10 | 0.298076E+10 | 24109.44 | 14-MAY-18:01 | 24109.44 | 0.73 |
June | 0.00 | 0.00 | 0.681200E+10 | 0.311330E+10 | 24208.15 | 12-JUN-15:01 | 20109.43 | 0.86 |
July | 0.00 | 0.00 | 0.956897E+10 | 0.472205E+10 | 24540.83 | 16-JUL-15:01 | 19882.51 | 0.91 |
August | 0.00 | 0.00 | 0.107165E+11 | 0.568579E+10 | 23877.42 | 29-AUG-08:62 | 20086.02 | 0.90 |
September | 0.00 | 0.00 | 0.874662E+10 | 0.487032E+10 | 23675.97 | 16-SEP-15:01 | 20551.07 | 0.82 |
October | 0.00 | 0.00 | 0.467255E+10 | 0.253512E+10 | 24114.70 | 04-OCT-18:01 | 24114.70 | 0.58 |
November | 0.00 | 0.00 | 0.123165E+10 | 0.559186E+09 | 23020.96 | 05-NOV-08:62 | 20204.29 | 0.21 |
December | 0.00 | 0.00 | 0.971341E+09 | 0.512672E+09 | 21524.65 | 10-DEC-16:01 | 21524.65 | 0.12 |
Annual Sum or Average | 0.00 | 0.00 | 0.586559E+11 | 0.305168E+11 | 0.54 | |||
Minimum of Months | 0.00 | 0.00 | 0.455824E+09 | 0.203203E+09 | 20036.61 | 19882.51 | 0.08 | |
Maximum of Months | 0.00 | 0.00 | 0.107165E+11 | 0.568579E+10 | 24540.83 | 24114.70 | 0.91 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 33476.87 | 163121.08 | 02-JAN-16:02 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 35345.41 | 158030.82 | 22-FEB-09:04 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 36652.82 | 144112.30 | 15-MAR-08:07 |
April | 0.00 | 0.00 | 01-APR-00:10 | 36652.92 | 129681.18 | 18-APR-15:04 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 31771.97 | 120978.54 | 28-MAY-08:03 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 16752.82 | 100869.71 | 15-JUN-04:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 6061.27 | 58593.92 | 19-JUL-05:00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 4662.11 | 65555.32 | 01-AUG-08:04 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 17591.35 | 106483.59 | 28-SEP-08:04 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 44685.06 | 153595.98 | 30-OCT-08:05 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 38884.56 | 168464.52 | 17-NOV-09:04 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 34829.55 | 167650.85 | 16-DEC-19:04 |
Annual Sum or Average | 0.00 | 28061.51 | ||||
Minimum of Months | 0.00 | 0.00 | 4662.11 | 58593.92 | ||
Maximum of Months | 0.00 | 0.00 | 44685.06 | 168464.52 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 1124.94 | 34372.80 | 11-JAN-19:03 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 5702.19 | 216998.28 | 27-FEB-16:03 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 12460.75 | 265608.87 | 18-MAR-15:01 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 32478.55 | 389617.12 | 27-APR-18:03 | 0.00 | 0.00 | 01-APR-00:10 |
May | 50771.85 | 354540.72 | 04-MAY-15:03 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 75736.02 | 392319.47 | 28-JUN-18:03 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 110767.84 | 455087.94 | 27-JUL-18:03 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 130885.15 | 487055.67 | 10-AUG-18:03 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 68903.44 | 390036.38 | 14-SEP-15:03 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 23734.24 | 310852.05 | 04-OCT-15:03 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 6652.34 | 301776.38 | 04-NOV-15:03 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 2062.59 | 45825.67 | 02-DEC-09:02 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 43722.74 | 0.00 | ||||
Minimum of Months | 1124.94 | 34372.80 | 0.00 | 0.00 | ||
Maximum of Months | 130885.15 | 487055.67 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 26364.65 | 55433.29 | 31-JAN-08:00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26550.39 | 55500.92 | 10-FEB-07:15 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 26273.73 | 55310.08 | 01-MAR-07:20 |
April | 0.00 | 0.00 | 01-APR-00:10 | 25546.60 | 54075.96 | 03-APR-06:30 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 24608.09 | 52394.42 | 01-MAY-06:50 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 23700.05 | 50335.89 | 01-JUN-06:40 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 23033.61 | 48581.04 | 03-JUL-07:00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 22858.77 | 47874.14 | 31-AUG-06:20 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 23152.66 | 48916.89 | 29-SEP-07:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 23865.82 | 50808.06 | 31-OCT-06:40 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 24810.55 | 52801.40 | 30-NOV-07:20 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 25721.57 | 54432.65 | 29-DEC-07:50 |
Annual Sum or Average | 0.00 | 24696.49 | ||||
Minimum of Months | 0.00 | 0.00 | 22858.77 | 47874.14 | ||
Maximum of Months | 0.00 | 0.00 | 26550.39 | 55500.92 |
Report: FanReportMonthly
For: FLR_3_DOAS FAN
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.271000E+10 | 0.70 | 1299.30 | 17-JAN-09:13 | 0.89 |
February | 0.244774E+10 | 0.70 | 1299.30 | 01-FEB-00:03 | 0.89 |
March | 0.271000E+10 | 0.70 | 1299.30 | 02-MAR-19:04 | 0.89 |
April | 0.262258E+10 | 0.70 | 1299.30 | 01-APR-18:09 | 0.89 |
May | 0.271000E+10 | 0.70 | 1299.30 | 05-MAY-22:20 | 0.89 |
June | 0.262258E+10 | 0.70 | 1299.30 | 01-JUN-21:20 | 0.89 |
July | 0.271000E+10 | 0.70 | 1299.30 | 04-JUL-18:40 | 0.89 |
August | 0.271000E+10 | 0.70 | 1299.30 | 01-AUG-21:20 | 0.88 |
September | 0.262258E+10 | 0.70 | 1299.30 | 02-SEP-18:03 | 0.88 |
October | 0.271000E+10 | 0.70 | 1299.30 | 20-OCT-08:07 | 0.88 |
November | 0.262258E+10 | 0.70 | 1299.30 | 21-NOV-09:07 | 0.88 |
December | 0.271000E+10 | 0.70 | 1299.30 | 03-DEC-09:05 | 0.89 |
Annual Sum or Average | 0.319080E+11 | 0.70 | |||
Minimum of Months | 0.244774E+10 | 0.70 | 1299.30 | 0.88 | |
Maximum of Months | 0.271000E+10 | 0.70 | 1299.30 | 0.89 |
Report: FanReportMonthly
For: VAV WITH REHEAT FAN
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.331375E+11 | 0.79 | 18388.37 | 11-JAN-21:10 | 0.99 |
February | 0.302954E+11 | 0.80 | 19120.75 | 27-FEB-22:10 | 1.01 |
March | 0.342830E+11 | 0.81 | 19480.63 | 14-MAR-21:10 | 1.03 |
April | 0.338123E+11 | 0.82 | 23921.22 | 27-APR-21:10 | 1.16 |
May | 0.357228E+11 | 0.82 | 23806.57 | 04-MAY-21:10 | 1.16 |
June | 0.352161E+11 | 0.83 | 23754.36 | 28-JUN-21:10 | 1.15 |
July | 0.369387E+11 | 0.84 | 24789.83 | 31-JUL-21:10 | 1.18 |
August | 0.373513E+11 | 0.84 | 25849.35 | 24-AUG-21:10 | 1.21 |
September | 0.350692E+11 | 0.83 | 26784.71 | 14-SEP-21:10 | 1.24 |
October | 0.350156E+11 | 0.81 | 24970.38 | 04-OCT-21:10 | 1.19 |
November | 0.330394E+11 | 0.80 | 19959.55 | 03-NOV-21:10 | 1.04 |
December | 0.332969E+11 | 0.79 | 18519.20 | 28-DEC-21:10 | 1.00 |
Annual Sum or Average | 0.413178E+12 | 0.82 | |||
Minimum of Months | 0.302954E+11 | 0.79 | 18388.37 | 0.99 | |
Maximum of Months | 0.373513E+11 | 0.84 | 26784.71 | 1.24 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205205E+09 | 0.27 | 76.61 | 01-JAN-00:10 | 0.27 |
February | 0.185347E+09 | 0.27 | 76.61 | 01-FEB-00:03 | 0.27 |
March | 0.205205E+09 | 0.27 | 76.61 | 01-MAR-00:03 | 0.27 |
April | 0.198586E+09 | 0.27 | 76.61 | 01-APR-00:10 | 0.27 |
May | 0.205205E+09 | 0.27 | 76.61 | 01-MAY-00:05 | 0.27 |
June | 0.198586E+09 | 0.27 | 76.61 | 01-JUN-00:05 | 0.27 |
July | 0.205205E+09 | 0.27 | 76.61 | 01-JUL-00:10 | 0.27 |
August | 0.205205E+09 | 0.27 | 76.61 | 01-AUG-00:05 | 0.27 |
September | 0.198586E+09 | 0.27 | 76.61 | 01-SEP-00:05 | 0.27 |
October | 0.205205E+09 | 0.27 | 76.61 | 01-OCT-00:10 | 0.27 |
November | 0.198586E+09 | 0.27 | 76.61 | 01-NOV-00:05 | 0.27 |
December | 0.205205E+09 | 0.27 | 76.61 | 01-DEC-00:03 | 0.27 |
Annual Sum or Average | 0.241613E+10 | 0.27 | |||
Minimum of Months | 0.185347E+09 | 0.27 | 76.61 | 0.27 | |
Maximum of Months | 0.205205E+09 | 0.27 | 76.61 | 0.27 |
Report: FanReportMonthly
For: LOBBY_FLR_1 EXHAUST FAN
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:03 | -0.0 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | -0.0 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:05 | -0.0 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:05 | -0.0 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | -0.0 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 EXHAUST FAN
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 EXHAUST FAN
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116283E+10 | 0.19 | 612.92 | 01-JAN-07:05 | 0.27 |
February | 0.105030E+10 | 0.19 | 612.92 | 01-FEB-07:05 | 0.27 |
March | 0.116283E+10 | 0.19 | 612.92 | 01-MAR-07:05 | 0.27 |
April | 0.112532E+10 | 0.19 | 612.92 | 01-APR-06:05 | 0.27 |
May | 0.116283E+10 | 0.19 | 612.92 | 01-MAY-06:05 | 0.27 |
June | 0.112532E+10 | 0.19 | 612.92 | 01-JUN-06:05 | 0.27 |
July | 0.116283E+10 | 0.19 | 612.92 | 01-JUL-06:10 | 0.27 |
August | 0.116283E+10 | 0.19 | 612.92 | 01-AUG-06:05 | 0.27 |
September | 0.112532E+10 | 0.19 | 612.92 | 01-SEP-06:05 | 0.27 |
October | 0.116283E+10 | 0.19 | 612.92 | 01-OCT-06:10 | 0.27 |
November | 0.112532E+10 | 0.19 | 612.92 | 01-NOV-06:05 | 0.27 |
December | 0.116283E+10 | 0.19 | 612.92 | 01-DEC-07:10 | 0.27 |
Annual Sum or Average | 0.136914E+11 | 0.19 | |||
Minimum of Months | 0.105030E+10 | 0.19 | 612.92 | 0.27 | |
Maximum of Months | 0.116283E+10 | 0.19 | 612.92 | 0.27 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.341884E+09 | 0.42 | 827.71 | 01-JAN-09:02 | 0.58 |
February | 0.232939E+09 | 0.42 | 827.71 | 01-FEB-09:02 | 0.58 |
March | 0.185276E+09 | 0.43 | 827.71 | 01-MAR-16:01 | 0.58 |
April | 0.178359E+09 | 0.46 | 827.71 | 01-APR-15:01 | 0.58 |
May | 0.229611E+09 | 0.50 | 827.71 | 01-MAY-15:01 | 0.58 |
June | 0.243942E+09 | 0.51 | 827.71 | 01-JUN-08:62 | 0.58 |
July | 0.359229E+09 | 0.53 | 827.71 | 01-JUL-08:61 | 0.58 |
August | 0.344609E+09 | 0.53 | 827.71 | 01-AUG-08:61 | 0.58 |
September | 0.243123E+09 | 0.49 | 827.71 | 01-SEP-15:01 | 0.58 |
October | 0.160174E+09 | 0.45 | 827.71 | 01-OCT-08:62 | 0.58 |
November | 0.231100E+09 | 0.42 | 827.71 | 02-NOV-15:01 | 0.58 |
December | 0.323708E+09 | 0.43 | 827.71 | 01-DEC-09:02 | 0.58 |
Annual Sum or Average | 0.307395E+10 | 0.47 | |||
Minimum of Months | 0.160174E+09 | 0.42 | 827.71 | 0.58 | |
Maximum of Months | 0.359229E+09 | 0.53 | 827.71 | 0.58 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.354437E+09 | 0.43 | 750.11 | 01-JAN-09:02 | 0.58 |
February | 0.251731E+09 | 0.42 | 750.11 | 01-FEB-09:02 | 0.58 |
March | 0.182537E+09 | 0.41 | 750.11 | 01-MAR-09:02 | 0.58 |
April | 0.138178E+09 | 0.41 | 750.11 | 01-APR-15:01 | 0.58 |
May | 0.143622E+09 | 0.41 | 750.11 | 01-MAY-15:01 | 0.58 |
June | 0.160076E+09 | 0.39 | 750.11 | 01-JUN-08:62 | 0.58 |
July | 0.235579E+09 | 0.39 | 750.11 | 01-JUL-08:61 | 0.58 |
August | 0.231315E+09 | 0.39 | 750.11 | 01-AUG-08:61 | 0.58 |
September | 0.125685E+09 | 0.37 | 750.11 | 01-SEP-08:52 | 0.58 |
October | 0.132986E+09 | 0.40 | 750.11 | 01-OCT-08:62 | 0.58 |
November | 0.240920E+09 | 0.41 | 750.11 | 02-NOV-08:62 | 0.58 |
December | 0.340181E+09 | 0.44 | 750.11 | 01-DEC-09:02 | 0.58 |
Annual Sum or Average | 0.253725E+10 | 0.40 | |||
Minimum of Months | 0.125685E+09 | 0.37 | 750.11 | 0.58 | |
Maximum of Months | 0.354437E+09 | 0.44 | 750.11 | 0.58 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.163863E+09 | 0.08 | 1227.72 | 08-FEB-13:40 | 0.58 |
March | 0.499837E+09 | 0.22 | 1672.09 | 02-MAR-13:00 | 0.58 |
April | 0.824221E+09 | 0.39 | 1409.40 | 27-APR-13:05 | 0.58 |
May | 0.100274E+10 | 0.44 | 1372.39 | 04-MAY-13:15 | 0.58 |
June | 0.108427E+10 | 0.51 | 1064.74 | 28-JUN-13:05 | 0.58 |
July | 0.140880E+10 | 0.56 | 1302.11 | 31-JUL-13:05 | 0.58 |
August | 0.154074E+10 | 0.55 | 1589.48 | 24-AUG-13:00 | 0.58 |
September | 0.132419E+10 | 0.51 | 1689.54 | 14-SEP-13:30 | 0.58 |
October | 0.836219E+09 | 0.35 | 1770.52 | 04-OCT-12:40 | 0.58 |
November | 0.149590E+09 | 0.08 | 1399.22 | 04-NOV-13:25 | 0.58 |
December | 73571056.28 | 0.04 | 1134.24 | 05-DEC-12:30 | 0.58 |
Annual Sum or Average | 0.890804E+10 | 0.31 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.154074E+10 | 0.56 | 1770.52 | 0.58 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.972966E+09 | 0.41 | 3915.77 | 01-JAN-09:02 | 0.58 |
February | 0.770033E+09 | 0.41 | 3915.77 | 01-FEB-19:03 | 0.58 |
March | 0.632848E+09 | 0.41 | 3915.77 | 01-MAR-09:02 | 0.58 |
April | 0.852512E+09 | 0.39 | 3915.77 | 01-APR-08:62 | 0.58 |
May | 0.120590E+10 | 0.36 | 3915.77 | 01-MAY-08:62 | 0.58 |
June | 0.140697E+10 | 0.34 | 3915.77 | 01-JUN-08:62 | 0.58 |
July | 0.162607E+10 | 0.34 | 3915.77 | 01-JUL-08:61 | 0.58 |
August | 0.156183E+10 | 0.34 | 3915.77 | 01-AUG-08:61 | 0.58 |
September | 0.106685E+10 | 0.33 | 3915.77 | 01-SEP-08:52 | 0.58 |
October | 0.681758E+09 | 0.39 | 3915.77 | 01-OCT-08:62 | 0.58 |
November | 0.666940E+09 | 0.41 | 3915.77 | 01-NOV-18:03 | 0.58 |
December | 0.878430E+09 | 0.41 | 3915.77 | 01-DEC-16:01 | 0.58 |
Annual Sum or Average | 0.123231E+11 | 0.38 | |||
Minimum of Months | 0.632848E+09 | 0.33 | 3915.77 | 0.58 | |
Maximum of Months | 0.162607E+10 | 0.41 | 3915.77 | 0.58 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.317256E+09 | 0.42 | 747.33 | 01-JAN-09:02 | 0.58 |
February | 0.215978E+09 | 0.42 | 747.33 | 02-FEB-09:02 | 0.58 |
March | 0.169681E+09 | 0.44 | 747.33 | 01-MAR-09:02 | 0.58 |
April | 0.171617E+09 | 0.48 | 747.33 | 01-APR-08:62 | 0.58 |
May | 0.197928E+09 | 0.51 | 747.33 | 01-MAY-15:01 | 0.58 |
June | 0.250538E+09 | 0.53 | 747.33 | 01-JUN-08:62 | 0.58 |
July | 0.302719E+09 | 0.54 | 747.33 | 01-JUL-08:61 | 0.58 |
August | 0.328686E+09 | 0.54 | 747.33 | 01-AUG-08:61 | 0.58 |
September | 0.216918E+09 | 0.50 | 747.33 | 01-SEP-15:01 | 0.58 |
October | 0.153795E+09 | 0.46 | 747.33 | 01-OCT-08:62 | 0.58 |
November | 0.214761E+09 | 0.42 | 747.33 | 02-NOV-15:01 | 0.58 |
December | 0.302901E+09 | 0.43 | 747.33 | 01-DEC-09:02 | 0.58 |
Annual Sum or Average | 0.284278E+10 | 0.47 | |||
Minimum of Months | 0.153795E+09 | 0.42 | 747.33 | 0.58 | |
Maximum of Months | 0.328686E+09 | 0.54 | 747.33 | 0.58 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.335412E+09 | 0.44 | 682.90 | 01-JAN-09:02 | 0.58 |
February | 0.234330E+09 | 0.42 | 682.90 | 01-FEB-09:02 | 0.58 |
March | 0.162067E+09 | 0.41 | 682.90 | 01-MAR-09:02 | 0.58 |
April | 0.131633E+09 | 0.42 | 682.90 | 01-APR-08:62 | 0.58 |
May | 0.139758E+09 | 0.42 | 682.90 | 01-MAY-15:01 | 0.58 |
June | 0.182664E+09 | 0.42 | 682.90 | 01-JUN-08:62 | 0.58 |
July | 0.209855E+09 | 0.41 | 682.90 | 01-JUL-08:61 | 0.58 |
August | 0.225122E+09 | 0.41 | 682.90 | 01-AUG-08:61 | 0.58 |
September | 0.124411E+09 | 0.38 | 682.90 | 01-SEP-08:52 | 0.58 |
October | 0.127086E+09 | 0.40 | 682.90 | 01-OCT-08:62 | 0.58 |
November | 0.224072E+09 | 0.41 | 682.90 | 04-NOV-15:01 | 0.58 |
December | 0.318756E+09 | 0.44 | 682.90 | 01-DEC-09:02 | 0.58 |
Annual Sum or Average | 0.241517E+10 | 0.41 | |||
Minimum of Months | 0.124411E+09 | 0.38 | 682.90 | 0.58 | |
Maximum of Months | 0.335412E+09 | 0.44 | 682.90 | 0.58 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.106591E+09 | 0.45 | 215.84 | 01-JAN-09:02 | 0.58 |
February | 74410254.75 | 0.44 | 215.84 | 01-FEB-09:02 | 0.58 |
March | 59272872.60 | 0.43 | 215.84 | 01-MAR-09:02 | 0.58 |
April | 53010064.80 | 0.46 | 215.84 | 01-APR-15:01 | 0.58 |
May | 63565013.81 | 0.50 | 215.84 | 01-MAY-15:01 | 0.58 |
June | 63559627.24 | 0.51 | 215.84 | 01-JUN-08:62 | 0.58 |
July | 93192412.10 | 0.53 | 215.84 | 01-JUL-08:61 | 0.58 |
August | 88027134.37 | 0.52 | 215.84 | 01-AUG-08:61 | 0.58 |
September | 62572246.80 | 0.49 | 215.84 | 01-SEP-15:01 | 0.58 |
October | 49212153.99 | 0.45 | 215.84 | 01-OCT-08:62 | 0.58 |
November | 74126543.93 | 0.43 | 215.84 | 02-NOV-15:01 | 0.58 |
December | 0.101665E+09 | 0.46 | 215.84 | 01-DEC-09:02 | 0.58 |
Annual Sum or Average | 0.889205E+09 | 0.47 | |||
Minimum of Months | 49212153.99 | 0.43 | 215.84 | 0.58 | |
Maximum of Months | 0.106591E+09 | 0.53 | 215.84 | 0.58 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.111865E+09 | 0.49 | 194.17 | 01-JAN-09:02 | 0.58 |
February | 79673051.76 | 0.44 | 194.17 | 01-FEB-09:02 | 0.58 |
March | 58030435.18 | 0.41 | 194.17 | 01-MAR-09:02 | 0.58 |
April | 42388950.15 | 0.41 | 194.17 | 01-APR-08:62 | 0.58 |
May | 40767717.20 | 0.41 | 194.17 | 01-MAY-15:01 | 0.58 |
June | 42529916.48 | 0.39 | 194.17 | 01-JUN-08:62 | 0.58 |
July | 64028254.68 | 0.40 | 194.17 | 01-JUL-08:61 | 0.58 |
August | 60396341.19 | 0.39 | 194.17 | 01-AUG-08:61 | 0.58 |
September | 32159721.99 | 0.37 | 194.17 | 01-SEP-08:52 | 0.58 |
October | 43274928.85 | 0.40 | 194.17 | 01-OCT-08:62 | 0.58 |
November | 76095652.56 | 0.43 | 194.17 | 02-NOV-08:62 | 0.58 |
December | 0.105402E+09 | 0.48 | 194.17 | 01-DEC-09:02 | 0.58 |
Annual Sum or Average | 0.756611E+09 | 0.42 | |||
Minimum of Months | 32159721.99 | 0.37 | 194.17 | 0.58 | |
Maximum of Months | 0.111865E+09 | 0.49 | 194.17 | 0.58 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.385665E+09 | 0.43 | 1182.03 | 01-JAN-16:02 | 0.58 |
February | 0.296326E+09 | 0.46 | 1182.03 | 01-FEB-16:01 | 0.58 |
March | 0.270178E+09 | 0.47 | 1182.03 | 01-MAR-09:02 | 0.58 |
April | 0.282841E+09 | 0.49 | 1182.03 | 01-APR-15:01 | 0.58 |
May | 0.303912E+09 | 0.51 | 1182.03 | 01-MAY-15:01 | 0.58 |
June | 0.318349E+09 | 0.51 | 1182.03 | 01-JUN-08:62 | 0.58 |
July | 0.418812E+09 | 0.53 | 1182.03 | 01-JUL-08:61 | 0.58 |
August | 0.460139E+09 | 0.53 | 1182.03 | 01-AUG-08:61 | 0.58 |
September | 0.395380E+09 | 0.50 | 1182.03 | 01-SEP-15:01 | 0.58 |
October | 0.279458E+09 | 0.48 | 1182.03 | 01-OCT-08:62 | 0.58 |
November | 0.268140E+09 | 0.44 | 1182.03 | 02-NOV-15:01 | 0.58 |
December | 0.390953E+09 | 0.45 | 1182.03 | 01-DEC-09:02 | 0.58 |
Annual Sum or Average | 0.407015E+10 | 0.48 | |||
Minimum of Months | 0.268140E+09 | 0.43 | 1182.03 | 0.58 | |
Maximum of Months | 0.460139E+09 | 0.53 | 1182.03 | 0.58 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.740369E+09 | 0.666332E+09 | 731.08 | 02-JAN-16:02 | 657.97 | 657.97 | 34.37 | 1.52 |
February | 0.652426E+09 | 0.587184E+09 | 736.43 | 22-FEB-09:04 | 662.79 | 662.79 | 35.77 | 1.56 |
March | 0.674883E+09 | 0.607395E+09 | 719.71 | 15-MAR-08:07 | 647.74 | 647.74 | 36.17 | 1.45 |
April | 0.609781E+09 | 0.548803E+09 | 679.31 | 06-APR-06:05 | 611.38 | 611.38 | 41.48 | 1.23 |
May | 0.529553E+09 | 0.476598E+09 | 670.41 | 18-MAY-09:05 | 603.37 | 603.37 | 40.10 | 1.20 |
June | 0.270481E+09 | 0.243433E+09 | 607.61 | 15-JUN-04:00 | 546.85 | 546.85 | 35.26 | 0.98 |
July | 0.101293E+09 | 91164052.07 | 361.76 | 07-JUL-05:00 | 325.59 | 325.59 | 29.18 | 0.45 |
August | 78219101.83 | 70397191.65 | 386.32 | 01-AUG-08:04 | 347.69 | 347.69 | 28.21 | 0.49 |
September | 0.286539E+09 | 0.257885E+09 | 627.05 | 27-SEP-03:10 | 564.35 | 564.35 | 35.65 | 1.04 |
October | 0.755932E+09 | 0.680339E+09 | 726.15 | 30-OCT-08:05 | 653.54 | 653.54 | 35.32 | 1.49 |
November | 0.719245E+09 | 0.647321E+09 | 738.12 | 17-NOV-09:04 | 664.31 | 664.31 | 34.39 | 1.57 |
December | 0.737784E+09 | 0.664005E+09 | 734.90 | 16-DEC-19:04 | 661.41 | 661.41 | 34.13 | 1.55 |
Annual Sum or Average | 0.615651E+10 | 0.554086E+10 | ||||||
Minimum of Months | 78219101.83 | 70397191.65 | 361.76 | 325.59 | 325.59 | 28.21 | 0.45 | |
Maximum of Months | 0.755932E+09 | 0.680339E+09 | 738.12 | 664.31 | 664.31 | 41.48 | 1.57 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 659685.07 | 593716.57 | 22.09 | 11-JAN-19:03 | 19.88 | 19.88 | 6.72 | 2.07 |
February | 5444300.74 | 4899870.67 | 361.58 | 27-FEB-16:01 | 325.42 | 325.42 | 6.72 | 8.34 |
March | 15777559.41 | 14199803.47 | 277.50 | 18-MAR-15:01 | 249.75 | 249.75 | 6.72 | 7.40 |
April | 64238926.13 | 57815033.51 | 725.67 | 26-APR-15:01 | 653.11 | 653.11 | 6.72 | 11.29 |
May | 0.103096E+09 | 92786404.14 | 654.30 | 04-MAY-15:02 | 588.87 | 588.87 | 6.72 | 10.80 |
June | 0.178575E+09 | 0.160717E+09 | 709.91 | 20-JUN-18:02 | 638.92 | 638.92 | 6.72 | 11.18 |
July | 0.283550E+09 | 0.255195E+09 | 868.95 | 31-JUL-18:02 | 782.06 | 782.06 | 6.72 | 12.18 |
August | 0.356300E+09 | 0.320670E+09 | 1005.08 | 10-AUG-18:03 | 904.57 | 904.57 | 6.72 | 12.95 |
September | 0.151563E+09 | 0.136407E+09 | 749.09 | 08-SEP-15:01 | 674.18 | 674.18 | 6.72 | 11.44 |
October | 37587938.52 | 33829144.66 | 385.70 | 04-OCT-15:03 | 347.13 | 347.13 | 6.72 | 8.58 |
November | 7561695.62 | 6805526.06 | 394.54 | 04-NOV-15:01 | 355.09 | 355.09 | 6.72 | 8.67 |
December | 1593814.34 | 1434432.90 | 40.32 | 02-DEC-09:02 | 36.29 | 36.29 | 6.72 | 2.88 |
Annual Sum or Average | 0.120595E+10 | 0.108535E+10 | ||||||
Minimum of Months | 659685.07 | 593716.57 | 22.09 | 19.88 | 19.88 | 6.72 | 2.07 | |
Maximum of Months | 0.356300E+09 | 0.320670E+09 | 1005.08 | 904.57 | 904.57 | 6.72 | 12.95 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.139645E+10 | 0.125681E+10 | 2434.12 | 01-JAN-09:02 | 2190.71 | 2190.71 | 6.99 | 21.53 |
February | 0.249074E+10 | 0.224167E+10 | 2434.12 | 01-FEB-06:03 | 2190.71 | 2190.71 | 6.74 | 21.53 |
March | 0.445637E+10 | 0.401073E+10 | 2434.12 | 01-MAR-00:03 | 2190.71 | 2190.71 | 6.76 | 21.53 |
April | 0.579090E+10 | 0.521181E+10 | 2434.12 | 01-APR-00:10 | 2190.71 | 2190.71 | 6.73 | 21.53 |
May | 0.643789E+10 | 0.579410E+10 | 2434.12 | 01-MAY-00:05 | 2190.71 | 2190.71 | 6.83 | 21.53 |
June | 0.630389E+10 | 0.567350E+10 | 2434.12 | 01-JUN-00:05 | 2190.71 | 2190.71 | 7.15 | 21.53 |
July | 0.651955E+10 | 0.586760E+10 | 2434.12 | 01-JUL-00:10 | 2190.71 | 2190.71 | 7.33 | 21.53 |
August | 0.651955E+10 | 0.586760E+10 | 2434.12 | 01-AUG-00:05 | 2190.71 | 2190.71 | 7.84 | 21.53 |
September | 0.623987E+10 | 0.561589E+10 | 2434.12 | 01-SEP-00:05 | 2190.71 | 2190.71 | 7.47 | 21.53 |
October | 0.559853E+10 | 0.503868E+10 | 2434.12 | 01-OCT-00:10 | 2190.71 | 2190.71 | 6.91 | 21.53 |
November | 0.295111E+10 | 0.265600E+10 | 2434.12 | 01-NOV-00:05 | 2190.71 | 2190.71 | 6.73 | 21.53 |
December | 0.169749E+10 | 0.152774E+10 | 2434.12 | 01-DEC-07:10 | 2190.71 | 2190.71 | 6.73 | 21.53 |
Annual Sum or Average | 0.564023E+11 | 0.507621E+11 | ||||||
Minimum of Months | 0.139645E+10 | 0.125681E+10 | 2434.12 | 2190.71 | 2190.71 | 6.73 | 21.53 | |
Maximum of Months | 0.651955E+10 | 0.586760E+10 | 2434.12 | 2190.71 | 2190.71 | 7.84 | 21.53 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:10 | 14.37 | 14.37 | 49.18 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:03 | 14.37 | 14.37 | 49.58 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:03 | 14.37 | 14.37 | 49.61 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 52.66 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:05 | 14.37 | 14.37 | 52.67 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:05 | 14.37 | 14.37 | 52.96 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 53.41 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:05 | 14.37 | 14.37 | 53.33 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:05 | 14.37 | 14.37 | 53.31 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:10 | 14.37 | 14.37 | 52.56 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:05 | 14.37 | 14.37 | 52.89 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:03 | 14.37 | 14.37 | 50.07 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 49.18 | 0.37 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 53.41 | 0.37 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 42.74 | 60.00 | 33476.87 | 163121.08 | 02-JAN-16:02 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 44.52 | 60.00 | 35345.41 | 158030.82 | 22-FEB-09:04 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 45.77 | 60.00 | 36652.82 | 144112.30 | 15-MAR-08:07 |
April | 0.00 | 0.00 | 01-APR-00:10 | 37.38 | 60.00 | 36652.92 | 129681.18 | 18-APR-15:04 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 31.16 | 60.00 | 31771.97 | 120978.54 | 28-MAY-08:03 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.25 | 60.00 | 16752.82 | 100869.71 | 15-JUN-04:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.84 | 26.84 | 6061.27 | 58593.92 | 19-JUL-05:00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.02 | 27.02 | 4662.11 | 65555.32 | 01-AUG-08:04 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 29.32 | 29.32 | 17591.35 | 106483.59 | 28-SEP-08:04 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 23.60 | 60.00 | 44685.06 | 153595.98 | 30-OCT-08:05 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 34.49 | 60.00 | 38884.56 | 168464.52 | 17-NOV-09:04 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 42.40 | 60.00 | 34829.55 | 167650.85 | 16-DEC-19:04 |
Annual Sum or Average | 0.00 | 28061.51 | ||||||
Minimum of Months | 0.00 | 0.00 | 23.60 | 26.84 | 4662.11 | 58593.92 | ||
Maximum of Months | 0.00 | 0.00 | 45.77 | 60.00 | 44685.06 | 168464.52 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 1124.94 | 34372.80 | 11-JAN-19:03 | 7.08 | 6.70 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 5702.19 | 216998.28 | 27-FEB-16:03 | 9.10 | 6.70 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 12460.75 | 265608.87 | 18-MAR-15:01 | 9.64 | 6.70 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 32478.55 | 389617.12 | 27-APR-18:03 | 11.02 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 50771.85 | 354540.72 | 04-MAY-15:03 | 10.63 | 6.70 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 75736.02 | 392319.47 | 28-JUN-18:03 | 11.05 | 6.70 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 110767.84 | 455087.94 | 27-JUL-18:03 | 11.75 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 130885.15 | 487055.67 | 10-AUG-18:03 | 12.10 | 6.70 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 68903.44 | 390036.38 | 14-SEP-15:03 | 11.02 | 6.70 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 23734.24 | 310852.05 | 04-OCT-15:03 | 10.14 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 6652.34 | 301776.38 | 04-NOV-15:03 | 10.04 | 6.70 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 2062.59 | 45825.67 | 02-DEC-09:02 | 7.21 | 6.70 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 43722.74 | 0.00 | ||||||
Minimum of Months | 1124.94 | 34372.80 | 7.08 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 130885.15 | 487055.67 | 12.10 | 6.70 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 49.18 | 60.05 | 26364.65 | 55433.29 | 31-JAN-08:00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 49.58 | 60.05 | 26550.39 | 55500.92 | 10-FEB-07:15 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 49.61 | 60.05 | 26273.73 | 55310.08 | 01-MAR-07:20 |
April | 0.00 | 0.00 | 01-APR-00:10 | 52.66 | 60.05 | 25546.60 | 54075.96 | 03-APR-06:30 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 52.67 | 60.05 | 24608.09 | 52394.42 | 01-MAY-06:50 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 52.96 | 60.05 | 23700.05 | 50335.89 | 01-JUN-06:40 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 53.41 | 60.05 | 23033.61 | 48581.04 | 03-JUL-07:00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 53.33 | 60.05 | 22858.77 | 47874.14 | 31-AUG-06:20 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 53.31 | 60.05 | 23152.66 | 48916.89 | 29-SEP-07:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 52.56 | 60.05 | 23865.82 | 50808.06 | 31-OCT-06:40 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 52.89 | 60.05 | 24810.55 | 52801.40 | 30-NOV-07:20 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 50.07 | 60.05 | 25721.57 | 54432.65 | 29-DEC-07:50 |
Annual Sum or Average | 0.00 | 24696.49 | ||||||
Minimum of Months | 0.00 | 0.00 | 49.18 | 60.05 | 22858.77 | 47874.14 | ||
Maximum of Months | 0.00 | 0.00 | 53.41 | 60.05 | 26550.39 | 55500.92 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.107885E+09 | 0.00 | 0.00 | 0.271000E+10 | 0.00 | 0.00 |
February | 94116059.72 | 0.00 | 0.108438E+09 | 0.244774E+10 | 0.00 | 0.00 |
March | 14570.92 | 0.00 | 0.232884E+09 | 0.271000E+10 | 0.00 | 0.00 |
April | 5374.59 | 0.00 | 0.179842E+10 | 0.262258E+10 | 0.00 | 0.00 |
May | 7907.92 | 0.00 | 0.355559E+10 | 0.271000E+10 | 0.00 | 0.00 |
June | 24976.93 | 0.00 | 0.630895E+10 | 0.262258E+10 | 0.00 | 0.00 |
July | 25196.21 | 0.00 | 0.116585E+11 | 0.271000E+10 | 0.00 | 0.00 |
August | 28778.06 | 0.00 | 0.152262E+11 | 0.271000E+10 | 0.00 | 0.00 |
September | 21135.78 | 0.00 | 0.544189E+10 | 0.262258E+10 | 0.00 | 0.00 |
October | 4594.50 | 0.00 | 0.903800E+09 | 0.271000E+10 | 0.00 | 0.00 |
November | 134237.44 | 0.00 | 0.218215E+09 | 0.262258E+10 | 0.00 | 0.00 |
December | 14198385.80 | 0.00 | 0.00 | 0.271000E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.216466E+09 | 0.00 | 0.454529E+11 | 0.319080E+11 | 0.00 | 0.00 |
Minimum of Months | 4594.50 | 0.00 | 0.00 | 0.244774E+10 | 0.00 | 0.00 |
Maximum of Months | 0.107885E+09 | 0.00 | 0.152262E+11 | 0.271000E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.595061E+11 | 0.00 | 0.00 | 0.331375E+11 | 0.00 | 0.00 |
February | 0.666315E+11 | 0.00 | 0.177965E+10 | 0.302954E+11 | 0.00 | 0.00 |
March | 0.901301E+11 | 0.00 | 0.394681E+10 | 0.342830E+11 | 0.00 | 0.00 |
April | 0.924768E+11 | 0.00 | 0.284700E+11 | 0.338123E+11 | 0.00 | 0.00 |
May | 0.847403E+11 | 0.00 | 0.551595E+11 | 0.357228E+11 | 0.00 | 0.00 |
June | 0.435050E+11 | 0.00 | 0.986138E+11 | 0.352161E+11 | 0.00 | 0.00 |
July | 0.162630E+11 | 0.00 | 0.166404E+12 | 0.369387E+11 | 0.00 | 0.00 |
August | 0.124621E+11 | 0.00 | 0.209638E+12 | 0.373513E+11 | 0.00 | 0.00 |
September | 0.454058E+11 | 0.00 | 0.803282E+11 | 0.350692E+11 | 0.00 | 0.00 |
October | 0.116004E+12 | 0.00 | 0.149889E+11 | 0.350156E+11 | 0.00 | 0.00 |
November | 0.855285E+11 | 0.00 | 0.341840E+10 | 0.330394E+11 | 0.00 | 0.00 |
December | 0.659983E+11 | 0.00 | 0.00 | 0.332969E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.778651E+12 | 0.00 | 0.662748E+12 | 0.413178E+12 | 0.00 | 0.00 |
Minimum of Months | 0.124621E+11 | 0.00 | 0.00 | 0.302954E+11 | 0.00 | 0.00 |
Maximum of Months | 0.116004E+12 | 0.00 | 0.209638E+12 | 0.373513E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.271000E+10 | 0.00 | 0.107885E+09 | 0.428279E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244774E+10 | 0.108438E+09 | 94116059.72 | 0.342462E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.271000E+10 | 0.232884E+09 | 14570.92 | 0.285506E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.262258E+10 | 0.179842E+10 | 5374.59 | 0.195564E+11 | 66000322.98 | 0.00 | 0.00 | 0.00 |
May | 0.271000E+10 | 0.355559E+10 | 7907.92 | 0.126563E+11 | 47890353.55 | 0.00 | 0.00 | 0.00 |
June | 0.262258E+10 | 0.630895E+10 | 24976.93 | 0.461220E+10 | 70261490.73 | 0.00 | 0.00 | 0.00 |
July | 0.271000E+10 | 0.116585E+11 | 25196.21 | 0.166400E+10 | 0.805621E+09 | 0.00 | 0.00 | 0.00 |
August | 0.271000E+10 | 0.152262E+11 | 28778.06 | 0.112849E+10 | 0.177236E+10 | 0.00 | 0.00 | 0.00 |
September | 0.262258E+10 | 0.544189E+10 | 21135.78 | 0.468909E+10 | 0.122063E+09 | 0.00 | 0.00 | 0.00 |
October | 0.271000E+10 | 0.903800E+09 | 4594.50 | 0.160422E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.262258E+10 | 0.218215E+09 | 134237.44 | 0.277552E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.271000E+10 | 0.00 | 14198385.80 | 0.396913E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319080E+11 | 0.454529E+11 | 0.216466E+09 | 0.233420E+12 | 0.288419E+10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244774E+10 | 0.00 | 4594.50 | 0.112849E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.271000E+10 | 0.152262E+11 | 0.107885E+09 | 0.428279E+11 | 0.177236E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.331375E+11 | 0.00 | 0.595061E+11 | 0.465655E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.302954E+11 | 0.177965E+10 | 0.666315E+11 | 0.339163E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.342830E+11 | 0.394681E+10 | 0.901301E+11 | 0.227734E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.338123E+11 | 0.284700E+11 | 0.924768E+11 | 0.110523E+12 | 0.277059E+09 | 0.00 | 0.00 | 0.00 |
May | 0.357228E+11 | 0.551595E+11 | 0.847403E+11 | 0.390086E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.352161E+11 | 0.986138E+11 | 0.435050E+11 | 0.197899E+10 | 24945550.41 | 0.00 | 0.00 | 0.00 |
July | 0.369387E+11 | 0.166404E+12 | 0.162630E+11 | 0.176997E+10 | 0.302243E+10 | 0.00 | 0.00 | 0.00 |
August | 0.373513E+11 | 0.209638E+12 | 0.124621E+11 | 0.292313E+10 | 0.822426E+10 | 0.00 | 0.00 | 0.00 |
September | 0.350692E+11 | 0.803282E+11 | 0.454058E+11 | 0.234667E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.350156E+11 | 0.149889E+11 | 0.116004E+12 | 0.419041E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.330394E+11 | 0.341840E+10 | 0.855285E+11 | 0.239018E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.332969E+11 | 0.00 | 0.659983E+11 | 0.413367E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.413178E+12 | 0.662748E+12 | 0.778651E+12 | 0.188539E+13 | 0.115487E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.302954E+11 | 0.00 | 0.124621E+11 | 0.176997E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.373513E+11 | 0.209638E+12 | 0.116004E+12 | 0.465655E+12 | 0.822426E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.271000E+10 | 0.107885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244774E+10 | 94116059.72 | 0.108438E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.271000E+10 | 14570.92 | 0.232884E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.262258E+10 | 5374.59 | 0.179842E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.271000E+10 | 7907.92 | 0.355559E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.262258E+10 | 24976.93 | 0.630895E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.271000E+10 | 25196.21 | 0.116585E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.271000E+10 | 28778.06 | 0.152262E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.262258E+10 | 21135.78 | 0.544189E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.271000E+10 | 4594.50 | 0.903800E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.262258E+10 | 134237.44 | 0.218215E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.271000E+10 | 14198385.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319080E+11 | 0.216466E+09 | 0.454529E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244774E+10 | 4594.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.271000E+10 | 0.107885E+09 | 0.152262E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.331375E+11 | 0.595061E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.302954E+11 | 0.666315E+11 | 0.177965E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.342830E+11 | 0.901301E+11 | 0.394681E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.338123E+11 | 0.924768E+11 | 0.284700E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.357228E+11 | 0.847403E+11 | 0.551595E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.352161E+11 | 0.435050E+11 | 0.986138E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.369387E+11 | 0.162630E+11 | 0.166404E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.373513E+11 | 0.124621E+11 | 0.209638E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.350692E+11 | 0.454058E+11 | 0.803282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.350156E+11 | 0.116004E+12 | 0.149889E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.330394E+11 | 0.855285E+11 | 0.341840E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.332969E+11 | 0.659983E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.413178E+12 | 0.778651E+12 | 0.662748E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.302954E+11 | 0.124621E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.373513E+11 | 0.116004E+12 | 0.209638E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.394109E+11 | 0.00 | 0.00 | 5018573.52 | 0.00 | 0.00 | 0.875337E+10 | 0.00 | 0.99 |
February | 0.407849E+11 | 0.00 | 0.00 | 1760336.82 | 0.00 | 0.00 | 0.508241E+10 | 0.00 | 1.00 |
March | 0.521809E+11 | 0.00 | 0.00 | 218736.30 | 0.00 | 0.00 | 0.154945E+10 | 0.00 | 0.99 |
April | 0.513941E+11 | 0.00 | 0.00 | 0.00 | 8470882.52 | 0.00 | 0.00 | 0.00 | 0.99 |
May | 0.489624E+11 | 0.00 | 0.00 | 113524.82 | 0.00 | 0.00 | 0.172215E+10 | 0.00 | 0.99 |
June | 0.382172E+11 | 0.00 | 0.00 | 1247766.69 | 0.00 | 0.00 | 0.363330E+10 | 0.00 | 0.99 |
July | 0.294207E+11 | 101091.57 | 0.00 | 4294909.06 | 0.101677E+09 | 0.00 | 0.591071E+10 | 0.00 | 0.99 |
August | 0.182740E+11 | 8094467.32 | 0.00 | 12809667.94 | 0.334449E+09 | 0.00 | 0.132622E+11 | 0.00 | 1.00 |
September | 0.141177E+11 | 0.00 | 0.00 | 22396631.10 | 0.00 | 0.00 | 0.304614E+11 | 0.00 | 1.01 |
October | 0.162106E+11 | 0.00 | 0.00 | 30687910.12 | 0.00 | 0.00 | 0.421910E+11 | 0.00 | 1.03 |
November | 0.154419E+11 | 0.00 | 0.00 | 30999760.89 | 0.00 | 0.00 | 0.371761E+11 | 0.00 | 1.03 |
December | 0.251917E+11 | 0.00 | 0.00 | 15494494.54 | 0.00 | 0.00 | 0.247539E+11 | 0.00 | 1.00 |
Annual Sum or Average | 0.389607E+12 | 8195558.89 | 0.00 | 0.125042E+09 | 0.444596E+09 | 0.00 | 0.174496E+12 | 0.00 | 1.00 |
Minimum of Months | 0.141177E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.99 |
Maximum of Months | 0.521809E+11 | 8094467.32 | 0.00 | 30999760.89 | 0.334449E+09 | 0.00 | 0.421910E+11 | 0.00 | 1.03 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.664260E+10 | 0.00 | 0.00 | 32688.22 | 0.00 | 0.167620E+10 | 48091152.50 | 0.00 | 3.10 |
February | 0.708180E+10 | 0.00 | 0.00 | 271764.43 | 0.00 | 0.606146E+09 | 0.288097E+09 | 0.00 | 3.13 |
March | 0.886546E+10 | 0.00 | 0.00 | 534561.09 | 0.00 | 9914772.38 | 0.490043E+09 | 0.00 | 3.12 |
April | 0.862716E+10 | 1856810.51 | 0.00 | 461666.17 | 0.00 | 0.00 | 0.301517E+09 | 0.00 | 3.12 |
May | 0.854185E+10 | 0.00 | 0.00 | 512660.94 | 0.00 | 0.00 | 0.263704E+09 | 0.00 | 3.12 |
June | 0.713178E+10 | 0.00 | 0.00 | 228686.88 | 0.00 | 0.00 | 0.137562E+09 | 0.00 | 3.12 |
July | 0.589663E+10 | 13847473.75 | 0.00 | 702932.10 | 4452895.31 | 0.00 | 0.240673E+09 | 0.00 | 3.13 |
August | 0.516028E+10 | 62453403.41 | 0.00 | 1034735.91 | 5612654.10 | 0.00 | 0.307379E+09 | 0.00 | 3.18 |
September | 0.702296E+10 | 0.00 | 0.00 | 2354472.66 | 0.00 | 0.00 | 0.659063E+09 | 0.00 | 3.20 |
October | 0.927922E+10 | 0.00 | 0.00 | 980056.67 | 0.00 | 0.00 | 0.615785E+09 | 0.00 | 3.15 |
November | 0.848948E+10 | 0.00 | 0.00 | 183291.84 | 0.00 | 0.231917E+09 | 0.136874E+09 | 0.00 | 3.11 |
December | 0.681010E+10 | 0.00 | 0.00 | 103870.96 | 0.00 | 0.158084E+10 | 0.197107E+09 | 0.00 | 3.10 |
Annual Sum or Average | 0.895493E+11 | 78157687.67 | 0.00 | 7401387.86 | 10065549.41 | 0.410501E+10 | 0.368589E+10 | 0.00 | 3.13 |
Minimum of Months | 0.516028E+10 | 0.00 | 0.00 | 32688.22 | 0.00 | 0.00 | 48091152.50 | 0.00 | 3.10 |
Maximum of Months | 0.927922E+10 | 62453403.41 | 0.00 | 2354472.66 | 5612654.10 | 0.167620E+10 | 0.659063E+09 | 0.00 | 3.20 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.438766E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.41 |
February | 0.413352E+10 | 0.00 | 0.00 | 7767.22 | 0.00 | 0.00 | 44614847.83 | 0.00 | 1.42 |
March | 0.472667E+10 | 0.00 | 0.00 | 46120.04 | 0.00 | 0.00 | 0.167514E+09 | 0.00 | 1.41 |
April | 0.414505E+10 | 0.00 | 0.00 | 282970.49 | 771599.16 | 0.00 | 0.541113E+09 | 0.00 | 1.42 |
May | 0.359988E+10 | 0.00 | 0.00 | 687771.67 | 0.00 | 0.00 | 0.102523E+10 | 0.00 | 1.42 |
June | 0.269677E+10 | 0.00 | 0.00 | 995744.73 | 0.00 | 0.00 | 0.113031E+10 | 0.00 | 1.43 |
July | 0.158769E+10 | 4087266.98 | 0.00 | 2091588.82 | 5194776.34 | 0.00 | 0.168055E+10 | 0.00 | 1.45 |
August | 0.141266E+10 | 11993599.22 | 0.00 | 2407492.73 | 19390471.78 | 0.00 | 0.150506E+10 | 0.00 | 1.46 |
September | 0.268373E+10 | 0.00 | 0.00 | 1262347.81 | 0.00 | 0.00 | 0.135573E+10 | 0.00 | 1.44 |
October | 0.462031E+10 | 0.00 | 0.00 | 278619.18 | 0.00 | 0.00 | 0.550522E+09 | 0.00 | 1.42 |
November | 0.461992E+10 | 0.00 | 0.00 | 3759.25 | 0.00 | 0.00 | 23680068.49 | 0.00 | 1.41 |
December | 0.450331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.41 |
Annual Sum or Average | 0.431172E+11 | 16080866.20 | 0.00 | 8064181.94 | 25356847.28 | 0.00 | 0.802433E+10 | 0.00 | 1.42 |
Minimum of Months | 0.141266E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.41 |
Maximum of Months | 0.472667E+10 | 11993599.22 | 0.00 | 2407492.73 | 19390471.78 | 0.00 | 0.168055E+10 | 0.00 | 1.46 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.326111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29406343.75 | 0.00 | 0.00 | 0.50 |
February | 0.313339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 |
March | 0.367042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 |
April | 0.351081E+10 | 0.00 | 0.00 | 0.00 | 578659.27 | 0.00 | 0.00 | 0.00 | 0.50 |
May | 0.346235E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 |
June | 0.285327E+10 | 0.00 | 0.00 | 1645.31 | 0.00 | 0.00 | 5686695.99 | 0.00 | 0.50 |
July | 0.234001E+10 | 6905.72 | 0.00 | 124341.29 | 6945695.72 | 0.00 | 74461155.65 | 0.00 | 0.50 |
August | 0.200643E+10 | 412682.95 | 0.00 | 318406.42 | 22990706.03 | 0.00 | 0.145184E+09 | 0.00 | 0.51 |
September | 0.297806E+10 | 0.00 | 0.00 | 8948.50 | 0.00 | 0.00 | 24242396.08 | 0.00 | 0.50 |
October | 0.387483E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 |
November | 0.348246E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 |
December | 0.335973E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17523053.71 | 0.00 | 0.00 | 0.50 |
Annual Sum or Average | 0.379329E+11 | 419588.67 | 0.00 | 453341.52 | 30515061.03 | 46929397.46 | 0.249574E+09 | 0.00 | 0.50 |
Minimum of Months | 0.200643E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 |
Maximum of Months | 0.387483E+10 | 412682.95 | 0.00 | 318406.42 | 22990706.03 | 29406343.75 | 0.145184E+09 | 0.00 | 0.51 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.167120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284380E+09 | 0.00 | 0.00 | 0.51 |
February | 0.168750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174694E+09 | 0.00 | 0.00 | 0.52 |
March | 0.218135E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.51 |
April | 0.208650E+10 | 0.00 | 0.00 | 0.00 | 343900.92 | 0.00 | 0.00 | 0.00 | 0.51 |
May | 0.205769E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
June | 0.169910E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
July | 0.143456E+10 | 0.00 | 0.00 | 0.00 | 4131975.63 | 0.00 | 0.00 | 0.00 | 0.52 |
August | 0.127481E+10 | 53155.03 | 0.00 | 2190.66 | 13853417.67 | 0.00 | 2490723.33 | 0.00 | 0.52 |
September | 0.178429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
October | 0.230284E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
November | 0.206767E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1977705.45 | 0.00 | 0.00 | 0.51 |
December | 0.186359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143531E+09 | 0.00 | 0.00 | 0.51 |
Annual Sum or Average | 0.221111E+11 | 53155.03 | 0.00 | 2190.66 | 18329294.22 | 0.604583E+09 | 2490723.33 | 0.00 | 0.52 |
Minimum of Months | 0.127481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.51 |
Maximum of Months | 0.230284E+10 | 53155.03 | 0.00 | 2190.66 | 13853417.67 | 0.284380E+09 | 2490723.33 | 0.00 | 0.52 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.232474E+09 | 0.00 | 0.00 | 90961917.37 | 0.00 | 0.00 | 0.723315E+11 | 0.00 | 23.18 |
February | 0.173710E+09 | 0.00 | 0.00 | 81701675.73 | 0.00 | 0.00 | 0.690093E+11 | 0.00 | 23.37 |
March | 0.187004E+09 | 0.00 | 0.00 | 92226189.49 | 0.00 | 0.00 | 0.814107E+11 | 0.00 | 23.36 |
April | 0.145553E+09 | 10931651.48 | 0.00 | 98072671.49 | 0.00 | 0.00 | 0.777161E+11 | 0.00 | 23.31 |
May | 0.123989E+09 | 0.00 | 0.00 | 0.109907E+09 | 0.00 | 0.00 | 0.766896E+11 | 0.00 | 23.36 |
June | 51581703.23 | 0.00 | 0.00 | 0.113773E+09 | 0.00 | 0.00 | 0.628713E+11 | 0.00 | 23.41 |
July | 62371327.44 | 0.140808E+09 | 0.00 | 0.122164E+09 | 1363971.10 | 0.00 | 0.526559E+11 | 0.00 | 23.30 |
August | 30268309.92 | 0.464923E+09 | 0.00 | 0.117637E+09 | 1174711.21 | 0.00 | 0.471168E+11 | 0.00 | 23.49 |
September | 83595808.41 | 0.00 | 0.00 | 0.108929E+09 | 0.00 | 0.00 | 0.661075E+11 | 0.00 | 23.39 |
October | 0.176398E+09 | 0.00 | 0.00 | 95751670.66 | 0.00 | 0.00 | 0.857428E+11 | 0.00 | 23.41 |
November | 0.174567E+09 | 0.00 | 0.00 | 87874487.92 | 0.00 | 0.00 | 0.765544E+11 | 0.00 | 23.27 |
December | 0.245849E+09 | 0.00 | 0.00 | 90183309.78 | 0.00 | 0.00 | 0.738642E+11 | 0.00 | 23.13 |
Annual Sum or Average | 0.168736E+10 | 0.616663E+09 | 0.00 | 0.120918E+10 | 2538682.31 | 0.00 | 0.842070E+12 | 0.00 | 23.33 |
Minimum of Months | 30268309.92 | 0.00 | 0.00 | 81701675.73 | 0.00 | 0.00 | 0.471168E+11 | 0.00 | 23.13 |
Maximum of Months | 0.245849E+09 | 0.464923E+09 | 0.00 | 0.122164E+09 | 1363971.10 | 0.00 | 0.857428E+11 | 0.00 | 23.49 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.302231E+11 | 0.00 | 0.00 | 605389.46 | 0.00 | 0.00 | 0.318556E+10 | 0.00 | 4.41 |
February | 0.231926E+11 | 0.00 | 0.00 | 3142265.32 | 0.00 | 0.00 | 0.865969E+10 | 0.00 | 4.45 |
March | 0.216878E+11 | 0.00 | 0.00 | 6326835.90 | 0.00 | 0.00 | 0.157080E+11 | 0.00 | 4.44 |
April | 0.184814E+11 | 6828949.27 | 0.00 | 8308747.94 | 0.00 | 0.00 | 0.171669E+11 | 0.00 | 4.44 |
May | 0.156057E+11 | 0.00 | 0.00 | 10692154.86 | 0.00 | 0.00 | 0.195478E+11 | 0.00 | 4.44 |
June | 0.104044E+11 | 0.00 | 0.00 | 11503290.09 | 0.00 | 0.00 | 0.186124E+11 | 0.00 | 4.44 |
July | 0.698125E+10 | 63045211.02 | 0.00 | 17414047.70 | 8406344.56 | 0.00 | 0.175224E+11 | 0.00 | 4.45 |
August | 0.628784E+10 | 0.244694E+09 | 0.00 | 20218663.99 | 12271951.28 | 0.00 | 0.155861E+11 | 0.00 | 4.52 |
September | 0.107564E+11 | 0.00 | 0.00 | 21943302.27 | 0.00 | 0.00 | 0.198929E+11 | 0.00 | 4.53 |
October | 0.191299E+11 | 0.00 | 0.00 | 11082126.71 | 0.00 | 0.00 | 0.203561E+11 | 0.00 | 4.48 |
November | 0.262074E+11 | 0.00 | 0.00 | 2567355.16 | 0.00 | 0.00 | 0.916737E+10 | 0.00 | 4.42 |
December | 0.295322E+11 | 0.00 | 0.00 | 1308175.36 | 0.00 | 0.00 | 0.476726E+10 | 0.00 | 4.41 |
Annual Sum or Average | 0.218490E+12 | 0.314569E+09 | 0.00 | 0.115112E+09 | 20678295.84 | 0.00 | 0.170173E+12 | 0.00 | 4.45 |
Minimum of Months | 0.628784E+10 | 0.00 | 0.00 | 605389.46 | 0.00 | 0.00 | 0.318556E+10 | 0.00 | 4.41 |
Maximum of Months | 0.302231E+11 | 0.244694E+09 | 0.00 | 21943302.27 | 12271951.28 | 0.00 | 0.203561E+11 | 0.00 | 4.53 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.919761E+11 | 0.00 | 0.00 | 872886.30 | 0.00 | 0.00 | 0.524433E+10 | 0.00 | 1.86 |
February | 0.780481E+11 | 0.00 | 0.00 | 4436689.95 | 0.00 | 0.00 | 0.145305E+11 | 0.00 | 1.87 |
March | 0.756936E+11 | 0.00 | 0.00 | 12141342.07 | 0.00 | 0.00 | 0.327604E+11 | 0.00 | 1.86 |
April | 0.596440E+11 | 12277206.61 | 0.00 | 22837466.76 | 4819798.04 | 0.00 | 0.442614E+11 | 0.00 | 1.87 |
May | 0.470872E+11 | 0.00 | 0.00 | 38493724.75 | 0.00 | 0.00 | 0.556230E+11 | 0.00 | 1.88 |
June | 0.309905E+11 | 0.00 | 0.00 | 51711886.82 | 0.00 | 0.00 | 0.541570E+11 | 0.00 | 1.89 |
July | 0.194638E+11 | 0.124214E+09 | 0.00 | 71376851.07 | 81212615.79 | 0.00 | 0.533741E+11 | 0.00 | 1.91 |
August | 0.167586E+11 | 0.505511E+09 | 0.00 | 77564490.46 | 0.186964E+09 | 0.00 | 0.487426E+11 | 0.00 | 1.94 |
September | 0.313030E+11 | 0.00 | 0.00 | 57439718.74 | 0.00 | 0.00 | 0.586917E+11 | 0.00 | 1.90 |
October | 0.616485E+11 | 0.00 | 0.00 | 26992166.29 | 0.00 | 0.00 | 0.531660E+11 | 0.00 | 1.88 |
November | 0.817943E+11 | 0.00 | 0.00 | 6033702.08 | 0.00 | 0.00 | 0.210921E+11 | 0.00 | 1.86 |
December | 0.923654E+11 | 0.00 | 0.00 | 1735465.02 | 0.00 | 0.00 | 0.741677E+10 | 0.00 | 1.85 |
Annual Sum or Average | 0.686773E+12 | 0.642002E+09 | 0.00 | 0.371636E+09 | 0.272996E+09 | 0.00 | 0.449060E+12 | 0.00 | 1.88 |
Minimum of Months | 0.167586E+11 | 0.00 | 0.00 | 872886.30 | 0.00 | 0.00 | 0.524433E+10 | 0.00 | 1.85 |
Maximum of Months | 0.923654E+11 | 0.505511E+09 | 0.00 | 77564490.46 | 0.186964E+09 | 0.00 | 0.586917E+11 | 0.00 | 1.94 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 68403761.98 | 0.00 | 0.00 | 128465.52 | 0.00 | 0.141156E+10 | 13714524.41 | 0.00 | 0.35 |
February | 66722030.63 | 0.00 | 0.00 | 994159.62 | 0.00 | 0.104871E+10 | 0.228604E+09 | 0.00 | 0.36 |
March | 77146645.11 | 0.00 | 0.00 | 3088707.12 | 0.00 | 0.883506E+09 | 0.527672E+09 | 0.00 | 0.35 |
April | 59200699.32 | 858256.74 | 0.00 | 7111786.94 | 0.00 | 0.389178E+09 | 0.900227E+09 | 0.00 | 0.36 |
May | 31047599.14 | 1597998.20 | 0.00 | 13323598.21 | 0.00 | 96926486.06 | 0.114448E+10 | 0.00 | 0.36 |
June | 18608644.35 | 747072.97 | 0.00 | 14397816.67 | 0.00 | 3553347.52 | 0.103028E+10 | 0.00 | 0.36 |
July | 1724771.82 | 16706797.76 | 0.00 | 16411734.10 | 0.00 | 1937548.82 | 0.838442E+09 | 0.00 | 0.35 |
August | 4437375.15 | 40381902.49 | 10172.30 | 12325083.20 | 0.00 | 2048132.98 | 0.626796E+09 | 2999.06 | 0.36 |
September | 28450022.80 | 4684449.21 | 0.00 | 12663294.19 | 0.00 | 37303473.60 | 0.953266E+09 | 0.00 | 0.36 |
October | 56344842.23 | 0.00 | 0.00 | 5067060.89 | 0.00 | 0.528813E+09 | 0.837423E+09 | 0.00 | 0.36 |
November | 67058600.87 | 0.00 | 0.00 | 740950.87 | 0.00 | 0.116373E+10 | 0.187370E+09 | 0.00 | 0.35 |
December | 62266434.61 | 0.00 | 0.00 | 261736.81 | 0.00 | 0.135848E+10 | 69605271.47 | 0.00 | 0.35 |
Annual Sum or Average | 0.541411E+09 | 64976477.37 | 10172.30 | 86514394.12 | 0.00 | 0.692575E+10 | 0.735788E+10 | 2999.06 | 0.36 |
Minimum of Months | 1724771.82 | 0.00 | 0.00 | 128465.52 | 0.00 | 1937548.82 | 13714524.41 | 0.00 | 0.35 |
Maximum of Months | 77146645.11 | 40381902.49 | 10172.30 | 16411734.10 | 0.00 | 0.141156E+10 | 0.114448E+10 | 2999.06 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 60770912.60 | 0.00 | 0.00 | 20410.64 | 0.00 | 0.142991E+10 | 2932581.59 | 0.00 | 0.35 |
February | 73636550.31 | 0.00 | 0.00 | 367461.73 | 0.00 | 0.116057E+10 | 0.110307E+09 | 0.00 | 0.36 |
March | 0.101445E+09 | 0.00 | 0.00 | 1537154.62 | 0.00 | 0.106763E+10 | 0.320627E+09 | 0.00 | 0.35 |
April | 0.128823E+09 | 854305.23 | 0.00 | 4737735.57 | 3850.95 | 0.510868E+09 | 0.711129E+09 | 0.00 | 0.36 |
May | 0.184511E+09 | 1292544.00 | 5507.35 | 9834728.19 | 299478.36 | 0.109506E+09 | 0.981776E+09 | 281.26 | 0.36 |
June | 0.216492E+09 | 664909.83 | 0.00 | 10849495.77 | 82075.61 | 3942571.41 | 0.835435E+09 | 0.00 | 0.36 |
July | 0.201059E+09 | 14100928.02 | 1822.36 | 12541632.19 | 2600894.93 | 1905040.28 | 0.642909E+09 | 1195.00 | 0.36 |
August | 0.175839E+09 | 37579307.81 | 15475.45 | 8226436.51 | 2788288.26 | 1996311.88 | 0.459469E+09 | 7269.46 | 0.36 |
September | 0.206294E+09 | 3492917.03 | 0.00 | 7895336.33 | 1190983.32 | 45002564.70 | 0.772371E+09 | 0.00 | 0.36 |
October | 0.127747E+09 | 0.00 | 0.00 | 2510676.28 | 0.00 | 0.703774E+09 | 0.593449E+09 | 0.00 | 0.36 |
November | 75411052.59 | 0.00 | 0.00 | 284278.71 | 0.00 | 0.123794E+10 | 0.105099E+09 | 0.00 | 0.35 |
December | 57325342.92 | 0.00 | 0.00 | 36929.69 | 0.00 | 0.142903E+10 | 4040467.90 | 0.00 | 0.35 |
Annual Sum or Average | 0.160935E+10 | 57984911.92 | 22805.15 | 58842276.25 | 6965571.43 | 0.770207E+10 | 0.553954E+10 | 8745.73 | 0.36 |
Minimum of Months | 57325342.92 | 0.00 | 0.00 | 20410.64 | 0.00 | 1905040.28 | 2932581.59 | 0.00 | 0.35 |
Maximum of Months | 0.216492E+09 | 37579307.81 | 15475.45 | 12541632.19 | 2788288.26 | 0.142991E+10 | 0.981776E+09 | 7269.46 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.918003E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
February | 0.792905E+09 | 0.00 | 0.00 | 841226.40 | 0.00 | 0.00 | 0.371290E+09 | 0.00 | 0.02 |
March | 0.606650E+09 | 0.00 | 0.00 | 2127187.21 | 0.00 | 0.00 | 0.979089E+09 | 0.00 | 0.02 |
April | 0.277566E+09 | 5060235.45 | 0.00 | 2545844.74 | 0.00 | 0.00 | 0.112225E+10 | 0.00 | 0.02 |
May | 0.237708E+09 | 1532831.23 | 0.00 | 2988066.47 | 0.00 | 0.00 | 0.105785E+10 | 0.00 | 0.02 |
June | 29227501.74 | 0.00 | 0.00 | 3021112.13 | 0.00 | 0.00 | 0.106238E+10 | 0.00 | 0.02 |
July | 0.00 | 36374494.43 | 0.00 | 3104297.25 | 0.00 | 0.00 | 0.519147E+09 | 0.00 | 0.02 |
August | 0.00 | 99871961.16 | 0.00 | 2057983.88 | 0.00 | 0.00 | 0.385587E+09 | 0.00 | 0.02 |
September | 0.225604E+09 | 40128408.89 | 0.00 | 3062867.92 | 0.00 | 0.00 | 0.644725E+09 | 0.00 | 0.02 |
October | 0.591607E+09 | 0.00 | 0.00 | 2845216.53 | 0.00 | 0.00 | 0.917565E+09 | 0.00 | 0.02 |
November | 0.101224E+10 | 0.00 | 0.00 | 535348.08 | 0.00 | 0.00 | 0.248257E+09 | 0.00 | 0.02 |
December | 0.917282E+09 | 0.00 | 0.00 | 244769.91 | 0.00 | 0.00 | 0.162099E+09 | 0.00 | 0.02 |
Annual Sum or Average | 0.560879E+10 | 0.182968E+09 | 0.00 | 23373920.51 | 0.00 | 0.00 | 0.747024E+10 | 0.00 | 0.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
Maximum of Months | 0.101224E+10 | 99871961.16 | 0.00 | 3104297.25 | 0.00 | 0.00 | 0.112225E+10 | 0.00 | 0.02 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.964134E+09 | 0.00 | 0.00 | 11870559.74 | 0.00 | 0.781185E+10 | 0.114724E+11 | 0.00 | 0.40 |
February | 0.100373E+10 | 0.00 | 0.00 | 19240675.20 | 0.00 | 0.554214E+10 | 0.116773E+11 | 0.00 | 0.40 |
March | 0.137604E+10 | 0.00 | 0.00 | 43749863.33 | 0.00 | 0.333718E+09 | 0.184743E+11 | 0.00 | 0.40 |
April | 0.175887E+10 | 10725927.44 | 0.00 | 80489611.27 | 914446.35 | 80194428.51 | 0.164678E+11 | 0.00 | 0.40 |
May | 0.268835E+10 | 12554324.33 | 80680.62 | 0.126202E+09 | 9025277.20 | 32545796.98 | 0.145917E+11 | 13065.14 | 0.40 |
June | 0.321302E+10 | 9019102.98 | 0.00 | 0.145984E+09 | 1113306.42 | 11763011.33 | 0.110986E+11 | 0.00 | 0.40 |
July | 0.306358E+10 | 0.167088E+09 | 113157.21 | 0.151480E+09 | 59382752.81 | 6256510.81 | 0.842257E+10 | 6894.25 | 0.40 |
August | 0.248127E+10 | 0.436107E+09 | 1033835.43 | 0.104690E+09 | 0.110682E+09 | 7527060.05 | 0.616276E+10 | 48560.15 | 0.40 |
September | 0.285584E+10 | 25648321.65 | 0.00 | 0.103346E+09 | 37885976.82 | 32800039.41 | 0.110005E+11 | 0.00 | 0.40 |
October | 0.172490E+10 | 0.00 | 0.00 | 58868462.99 | 0.00 | 0.188383E+09 | 0.173908E+11 | 0.00 | 0.40 |
November | 0.105005E+10 | 0.00 | 0.00 | 28531071.35 | 0.00 | 0.208131E+10 | 0.160844E+11 | 0.00 | 0.40 |
December | 0.985779E+09 | 0.00 | 0.00 | 12219422.01 | 0.00 | 0.732099E+10 | 0.118979E+11 | 0.00 | 0.40 |
Annual Sum or Average | 0.231656E+11 | 0.661143E+09 | 1227673.26 | 0.886672E+09 | 0.219003E+09 | 0.234495E+11 | 0.154741E+12 | 68519.54 | 0.40 |
Minimum of Months | 0.964134E+09 | 0.00 | 0.00 | 11870559.74 | 0.00 | 6256510.81 | 0.616276E+10 | 0.00 | 0.40 |
Maximum of Months | 0.321302E+10 | 0.436107E+09 | 1033835.43 | 0.151480E+09 | 0.110682E+09 | 0.781185E+10 | 0.184743E+11 | 48560.15 | 0.40 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 68166545.25 | 0.00 | 0.00 | 62002.82 | 0.00 | 0.140136E+10 | 24220602.01 | 0.00 | 0.35 |
February | 67125714.25 | 0.00 | 0.00 | 872420.44 | 0.00 | 0.105473E+10 | 0.222304E+09 | 0.00 | 0.36 |
March | 67599448.08 | 0.00 | 0.00 | 2944221.46 | 0.00 | 0.860600E+09 | 0.560271E+09 | 0.00 | 0.35 |
April | 36091451.62 | 858256.74 | 0.00 | 7516405.82 | 0.00 | 0.364884E+09 | 0.947225E+09 | 0.00 | 0.36 |
May | 26687209.21 | 1592208.91 | 5183.40 | 11331154.81 | 0.00 | 0.123708E+09 | 0.112405E+10 | 605.89 | 0.36 |
June | 15026102.53 | 746980.05 | 0.00 | 15043445.97 | 0.00 | 12309863.72 | 0.102446E+10 | 92.92 | 0.36 |
July | 2825036.38 | 16706797.76 | 0.00 | 15594575.24 | 0.00 | 1814247.35 | 0.838282E+09 | 0.00 | 0.35 |
August | 4353342.60 | 40382558.80 | 10168.02 | 13372148.05 | 0.00 | 1629750.41 | 0.626251E+09 | 2347.03 | 0.36 |
September | 28685131.58 | 4684449.21 | 0.00 | 11584300.80 | 0.00 | 46595899.65 | 0.944818E+09 | 0.00 | 0.36 |
October | 46470362.68 | 0.00 | 0.00 | 4909739.44 | 0.00 | 0.538407E+09 | 0.837860E+09 | 0.00 | 0.36 |
November | 66567349.10 | 0.00 | 0.00 | 714868.15 | 0.00 | 0.115163E+10 | 0.199990E+09 | 0.00 | 0.35 |
December | 63303489.23 | 0.00 | 0.00 | 229708.11 | 0.00 | 0.136676E+10 | 60314315.83 | 0.00 | 0.35 |
Annual Sum or Average | 0.492901E+09 | 64971251.46 | 15351.42 | 84174991.10 | 0.00 | 0.692443E+10 | 0.741005E+10 | 3045.85 | 0.36 |
Minimum of Months | 2825036.38 | 0.00 | 0.00 | 62002.82 | 0.00 | 1629750.41 | 24220602.01 | 0.00 | 0.35 |
Maximum of Months | 68166545.25 | 40382558.80 | 10168.02 | 15594575.24 | 0.00 | 0.140136E+10 | 0.112405E+10 | 2347.03 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 53669069.99 | 0.00 | 0.00 | 18733.92 | 0.00 | 0.143591E+10 | 4039181.44 | 0.00 | 0.35 |
February | 73997413.53 | 0.00 | 0.00 | 212869.01 | 0.00 | 0.114684E+10 | 0.123825E+09 | 0.00 | 0.36 |
March | 0.101885E+09 | 0.00 | 0.00 | 1180170.60 | 0.00 | 0.101262E+10 | 0.375549E+09 | 0.00 | 0.35 |
April | 0.125615E+09 | 854305.23 | 0.00 | 5297983.03 | 3850.95 | 0.465048E+09 | 0.759597E+09 | 0.00 | 0.36 |
May | 0.169491E+09 | 1292544.00 | 4497.61 | 8516054.30 | 299478.36 | 0.147849E+09 | 0.959772E+09 | 1291.00 | 0.36 |
June | 0.203913E+09 | 664909.83 | 0.00 | 12017119.79 | 82075.61 | 14331507.43 | 0.836458E+09 | 0.00 | 0.36 |
July | 0.200171E+09 | 13958550.13 | 8335.50 | 11969126.34 | 2736936.93 | 1869929.85 | 0.644406E+09 | 1017.75 | 0.36 |
August | 0.167982E+09 | 37739445.03 | 0.00 | 8873110.39 | 2650895.95 | 1569197.23 | 0.467106E+09 | 0.00 | 0.36 |
September | 0.200060E+09 | 3577079.18 | 3085.28 | 7441917.59 | 1102158.45 | 50352936.67 | 0.773708E+09 | 1577.45 | 0.36 |
October | 0.126467E+09 | 0.00 | 0.00 | 2431231.63 | 0.00 | 0.713693E+09 | 0.584889E+09 | 0.00 | 0.36 |
November | 75121967.12 | 0.00 | 0.00 | 266495.12 | 0.00 | 0.121317E+10 | 0.130171E+09 | 0.00 | 0.35 |
December | 57295511.87 | 0.00 | 0.00 | 38276.01 | 0.00 | 0.141316E+10 | 19943282.17 | 0.00 | 0.35 |
Annual Sum or Average | 0.155567E+10 | 58086833.40 | 15918.39 | 58263087.72 | 6875396.25 | 0.761642E+10 | 0.567946E+10 | 3886.20 | 0.36 |
Minimum of Months | 53669069.99 | 0.00 | 0.00 | 18733.92 | 0.00 | 1569197.23 | 4039181.44 | 0.00 | 0.35 |
Maximum of Months | 0.203913E+09 | 37739445.03 | 8335.50 | 12017119.79 | 2736936.93 | 0.143591E+10 | 0.959772E+09 | 1577.45 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.299521E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.442231E+09 | 0.00 | 0.00 | 0.63 |
February | 0.289117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 31263798.71 | 0.00 | 0.00 | 0.63 |
March | 0.339035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.63 |
April | 0.324292E+11 | 0.00 | 0.00 | 0.00 | 5345046.71 | 0.00 | 0.00 | 0.00 | 0.63 |
May | 0.319815E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.63 |
June | 0.264080E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.64 |
July | 0.222965E+11 | 0.00 | 0.00 | 0.00 | 64220831.00 | 0.00 | 0.00 | 0.00 | 0.64 |
August | 0.198523E+11 | 0.00 | 0.00 | 0.00 | 0.216142E+09 | 0.00 | 0.00 | 0.00 | 0.64 |
September | 0.277322E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.64 |
October | 0.357916E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.64 |
November | 0.321009E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 66451785.15 | 0.00 | 0.00 | 0.63 |
December | 0.304928E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.702680E+09 | 0.00 | 0.00 | 0.63 |
Annual Sum or Average | 0.351852E+12 | 0.00 | 0.00 | 0.00 | 0.285707E+09 | 0.124263E+10 | 0.00 | 0.00 | 0.63 |
Minimum of Months | 0.198523E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.63 |
Maximum of Months | 0.357916E+11 | 0.00 | 0.00 | 0.00 | 0.216142E+09 | 0.702680E+09 | 0.00 | 0.00 | 0.64 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 12056630.35 | 0.00 | 0.00 | 24863.14 | 0.00 | 0.359833E+09 | 1537609.79 | 0.00 | 0.35 |
February | 15232758.92 | 0.00 | 0.00 | 222985.74 | 0.00 | 0.289376E+09 | 31426872.35 | 0.00 | 0.36 |
March | 19226978.74 | 0.00 | 0.00 | 730881.51 | 0.00 | 0.262293E+09 | 90602264.56 | 0.00 | 0.35 |
April | 14787032.92 | 214564.18 | 0.00 | 1696734.66 | 0.00 | 0.141321E+09 | 0.181124E+09 | 0.00 | 0.36 |
May | 6707205.34 | 399499.55 | 0.00 | 3291801.15 | 0.00 | 65689820.37 | 0.245756E+09 | 0.00 | 0.36 |
June | 4432323.48 | 186768.24 | 0.00 | 3535079.69 | 0.00 | 15049669.67 | 0.243694E+09 | 0.00 | 0.36 |
July | 704816.80 | 4176699.44 | 0.00 | 4005202.52 | 0.00 | 472471.92 | 0.209447E+09 | 0.00 | 0.35 |
August | 1449583.24 | 10095475.62 | 2623.78 | 2860691.98 | 0.00 | 692409.88 | 0.156399E+09 | 669.06 | 0.36 |
September | 7264195.36 | 1171112.30 | 0.00 | 2987055.31 | 0.00 | 28074915.00 | 0.219595E+09 | 0.00 | 0.36 |
October | 14591982.81 | 0.00 | 0.00 | 1112663.18 | 0.00 | 0.191105E+09 | 0.150102E+09 | 0.00 | 0.36 |
November | 15673781.22 | 0.00 | 0.00 | 164652.30 | 0.00 | 0.313235E+09 | 25650535.09 | 0.00 | 0.35 |
December | 11646286.77 | 0.00 | 0.00 | 58448.56 | 0.00 | 0.354705E+09 | 6243155.62 | 0.00 | 0.35 |
Annual Sum or Average | 0.123774E+09 | 16244119.34 | 2623.78 | 20691059.76 | 0.00 | 0.202185E+10 | 0.156158E+10 | 669.06 | 0.36 |
Minimum of Months | 704816.80 | 0.00 | 0.00 | 24863.14 | 0.00 | 472471.92 | 1537609.79 | 0.00 | 0.35 |
Maximum of Months | 19226978.74 | 10095475.62 | 2623.78 | 4005202.52 | 0.00 | 0.359833E+09 | 0.245756E+09 | 669.06 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 6184098.78 | 0.00 | 0.00 | 2394.50 | 0.00 | 0.366913E+09 | 308922.05 | 0.00 | 0.35 |
February | 14098736.38 | 0.00 | 0.00 | 66309.59 | 0.00 | 0.309283E+09 | 12771095.81 | 0.00 | 0.36 |
March | 25361256.84 | 0.00 | 0.00 | 335999.44 | 0.00 | 0.295214E+09 | 51898859.03 | 0.00 | 0.35 |
April | 32017831.04 | 213576.31 | 0.00 | 1110985.99 | 962.74 | 0.166683E+09 | 0.139078E+09 | 0.00 | 0.36 |
May | 44249068.65 | 324583.15 | 0.00 | 2485021.31 | 74869.59 | 66073266.00 | 0.208600E+09 | 0.00 | 0.36 |
June | 51045093.24 | 166227.46 | 0.00 | 2745123.92 | 20518.90 | 15747631.22 | 0.197142E+09 | 0.00 | 0.36 |
July | 49301437.21 | 3525232.01 | 371.20 | 3240010.62 | 650223.73 | 427150.07 | 0.161635E+09 | 383.14 | 0.36 |
August | 43460176.42 | 9395672.00 | 4026.32 | 1932354.81 | 695713.75 | 558016.38 | 0.115432E+09 | 2173.16 | 0.36 |
September | 50941792.61 | 911738.89 | 0.00 | 1838941.89 | 259236.20 | 33456407.30 | 0.171653E+09 | 0.00 | 0.36 |
October | 31896029.56 | 0.00 | 0.00 | 488951.71 | 0.00 | 0.231735E+09 | 92750303.21 | 0.00 | 0.36 |
November | 16758789.99 | 0.00 | 0.00 | 47846.11 | 0.00 | 0.326808E+09 | 11068150.87 | 0.00 | 0.35 |
December | 7997274.88 | 0.00 | 0.00 | 2948.27 | 0.00 | 0.364123E+09 | 485729.07 | 0.00 | 0.35 |
Annual Sum or Average | 0.373312E+09 | 14537029.81 | 4397.53 | 14296888.16 | 1701524.92 | 0.217702E+10 | 0.116282E+10 | 2556.30 | 0.36 |
Minimum of Months | 6184098.78 | 0.00 | 0.00 | 2394.50 | 0.00 | 427150.07 | 308922.05 | 0.00 | 0.35 |
Maximum of Months | 51045093.24 | 9395672.00 | 4026.32 | 3240010.62 | 695713.75 | 0.366913E+09 | 0.208600E+09 | 2173.16 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 93815361.42 | 0.00 | 0.00 | 1351301.31 | 0.00 | 0.198764E+10 | 0.316436E+09 | 0.00 | 0.40 |
February | 61537797.27 | 0.00 | 0.00 | 4362123.11 | 0.00 | 0.126791E+10 | 0.826476E+09 | 0.00 | 0.41 |
March | 57662379.15 | 0.00 | 0.00 | 8347436.36 | 0.00 | 0.788050E+09 | 0.154133E+10 | 0.00 | 0.40 |
April | 34019696.06 | 1378465.32 | 0.00 | 12717150.51 | 0.00 | 0.336229E+09 | 0.179448E+10 | 0.00 | 0.40 |
May | 22291445.98 | 2566580.60 | 0.00 | 17547701.16 | 0.00 | 97800746.44 | 0.192748E+10 | 0.00 | 0.40 |
June | 25452081.02 | 1199890.59 | 0.00 | 19311051.36 | 0.00 | 7716356.25 | 0.166100E+10 | 0.00 | 0.40 |
July | 4337333.69 | 26833161.04 | 0.00 | 20261650.82 | 0.00 | 3593320.02 | 0.135069E+10 | 0.00 | 0.40 |
August | 8138262.67 | 64858275.54 | 17149.94 | 16747829.45 | 0.00 | 3259070.26 | 0.100878E+10 | 4004.88 | 0.40 |
September | 40111077.65 | 7523798.50 | 0.00 | 19603427.52 | 0.00 | 39941547.30 | 0.155735E+10 | 0.00 | 0.40 |
October | 53058018.78 | 0.00 | 0.00 | 12126920.48 | 0.00 | 0.379010E+09 | 0.184878E+10 | 0.00 | 0.40 |
November | 81969571.04 | 0.00 | 0.00 | 3257188.19 | 0.00 | 0.130558E+10 | 0.888119E+09 | 0.00 | 0.40 |
December | 78096544.35 | 0.00 | 0.00 | 2357021.90 | 0.00 | 0.183648E+10 | 0.477167E+09 | 0.00 | 0.40 |
Annual Sum or Average | 0.560490E+09 | 0.104360E+09 | 17149.94 | 0.137991E+09 | 0.00 | 0.805321E+10 | 0.151981E+11 | 4004.88 | 0.40 |
Minimum of Months | 4337333.69 | 0.00 | 0.00 | 1351301.31 | 0.00 | 3259070.26 | 0.316436E+09 | 0.00 | 0.40 |
Maximum of Months | 93815361.42 | 64858275.54 | 17149.94 | 20261650.82 | 0.00 | 0.198764E+10 | 0.192748E+10 | 4004.88 | 0.41 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.328151E+10 | 0.00 | 0.00 | 47548009.07 | 0.00 | 0.00 | 0.412942E+11 | 0.00 | 4.37 |
February | 0.196989E+10 | 0.00 | 0.00 | 46745410.93 | 0.00 | 0.00 | 0.410869E+11 | 0.00 | 4.46 |
March | 0.134454E+10 | 0.00 | 0.00 | 60705090.89 | 0.00 | 0.00 | 0.505022E+11 | 0.00 | 4.58 |
April | 0.603019E+09 | 7505081.69 | 0.00 | 70737738.21 | 0.00 | 0.00 | 0.511415E+11 | 0.00 | 4.74 |
May | 0.115496E+09 | 0.00 | 0.00 | 89176420.31 | 0.00 | 0.00 | 0.534597E+11 | 0.00 | 4.93 |
June | 18129426.03 | 0.00 | 0.00 | 94484161.64 | 0.00 | 0.00 | 0.460188E+11 | 0.00 | 5.08 |
July | 1151911.26 | 99868009.36 | 0.00 | 0.104579E+09 | 0.00 | 0.00 | 0.400587E+11 | 0.00 | 5.18 |
August | 8957291.87 | 0.322050E+09 | 0.00 | 94899341.84 | 235232.18 | 0.00 | 0.357586E+11 | 0.00 | 5.19 |
September | 0.133956E+09 | 0.00 | 0.00 | 86513737.92 | 0.00 | 0.00 | 0.466697E+11 | 0.00 | 4.95 |
October | 0.767161E+09 | 0.00 | 0.00 | 66386138.63 | 0.00 | 0.00 | 0.557966E+11 | 0.00 | 4.69 |
November | 0.163607E+10 | 0.00 | 0.00 | 53169469.23 | 0.00 | 0.00 | 0.471244E+11 | 0.00 | 4.51 |
December | 0.301828E+10 | 0.00 | 0.00 | 48895945.10 | 0.00 | 0.00 | 0.426731E+11 | 0.00 | 4.37 |
Annual Sum or Average | 0.128981E+11 | 0.429423E+09 | 0.00 | 0.863840E+09 | 235232.18 | 0.00 | 0.551584E+12 | 0.00 | 4.76 |
Minimum of Months | 1151911.26 | 0.00 | 0.00 | 46745410.93 | 0.00 | 0.00 | 0.357586E+11 | 0.00 | 4.37 |
Maximum of Months | 0.328151E+10 | 0.322050E+09 | 0.00 | 0.104579E+09 | 235232.18 | 0.00 | 0.557966E+11 | 0.00 | 5.19 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.959513E+09 | 0.00 | 0.00 | 63406127.66 | 0.00 | 0.00 | 0.478863E+11 | 0.00 | 4.78 |
February | 0.496122E+09 | 0.00 | 0.00 | 60770025.25 | 0.00 | 0.00 | 0.467460E+11 | 0.00 | 4.89 |
March | 0.126282E+09 | 0.00 | 0.00 | 75263758.38 | 0.00 | 0.00 | 0.568264E+11 | 0.00 | 5.03 |
April | 20703152.94 | 8381410.40 | 0.00 | 84472171.08 | 0.00 | 0.00 | 0.566766E+11 | 0.00 | 5.19 |
May | 0.00 | 0.00 | 0.00 | 0.102094E+09 | 0.00 | 0.00 | 0.583317E+11 | 0.00 | 5.37 |
June | 0.00 | 0.00 | 0.00 | 0.106697E+09 | 0.00 | 0.00 | 0.497730E+11 | 0.00 | 5.50 |
July | 0.00 | 0.107679E+09 | 0.00 | 0.116293E+09 | 0.00 | 0.00 | 0.430523E+11 | 0.00 | 5.59 |
August | 0.00 | 0.348551E+09 | 0.00 | 0.106292E+09 | 0.00 | 0.00 | 0.383896E+11 | 0.00 | 5.59 |
September | 0.00 | 0.00 | 0.00 | 98887492.30 | 0.00 | 0.00 | 0.507418E+11 | 0.00 | 5.37 |
October | 50307921.29 | 0.00 | 0.00 | 80317833.41 | 0.00 | 0.00 | 0.620069E+11 | 0.00 | 5.14 |
November | 0.259240E+09 | 0.00 | 0.00 | 67818991.25 | 0.00 | 0.00 | 0.533331E+11 | 0.00 | 4.95 |
December | 0.783239E+09 | 0.00 | 0.00 | 64450373.09 | 0.00 | 0.00 | 0.493622E+11 | 0.00 | 4.79 |
Annual Sum or Average | 0.269541E+10 | 0.464611E+09 | 0.00 | 0.102676E+10 | 0.00 | 0.00 | 0.613126E+12 | 0.00 | 5.18 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 60770025.25 | 0.00 | 0.00 | 0.383896E+11 | 0.00 | 4.78 |
Maximum of Months | 0.959513E+09 | 0.348551E+09 | 0.00 | 0.116293E+09 | 0.00 | 0.00 | 0.620069E+11 | 0.00 | 5.59 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.109457E+09 | 0.00 | 0.00 | 0.666394E+11 | 0.00 | 21.20 |
February | 0.00 | 0.00 | 0.00 | 99250984.69 | 0.00 | 0.00 | 0.643201E+11 | 0.00 | 21.64 |
March | 0.00 | 0.00 | 0.00 | 0.113192E+09 | 0.00 | 0.00 | 0.771594E+11 | 0.00 | 21.87 |
April | 0.00 | 14704966.42 | 0.00 | 0.122741E+09 | 0.00 | 0.00 | 0.733371E+11 | 0.00 | 22.26 |
May | 0.00 | 0.00 | 0.00 | 0.142612E+09 | 0.00 | 0.00 | 0.711455E+11 | 0.00 | 22.48 |
June | 0.00 | 0.00 | 0.00 | 0.146852E+09 | 0.00 | 0.00 | 0.579744E+11 | 0.00 | 22.74 |
July | 0.00 | 0.176641E+09 | 0.00 | 0.156961E+09 | 0.00 | 0.00 | 0.479466E+11 | 0.00 | 22.79 |
August | 0.00 | 0.594586E+09 | 0.00 | 0.143310E+09 | 0.00 | 0.00 | 0.424723E+11 | 0.00 | 22.90 |
September | 0.00 | 0.00 | 0.00 | 0.140517E+09 | 0.00 | 0.00 | 0.611349E+11 | 0.00 | 22.56 |
October | 0.00 | 0.00 | 0.00 | 0.118543E+09 | 0.00 | 0.00 | 0.798501E+11 | 0.00 | 22.13 |
November | 0.00 | 0.00 | 0.00 | 0.105682E+09 | 0.00 | 0.00 | 0.711622E+11 | 0.00 | 21.57 |
December | 0.00 | 0.00 | 0.00 | 0.109120E+09 | 0.00 | 0.00 | 0.685733E+11 | 0.00 | 21.24 |
Annual Sum or Average | 0.00 | 0.785932E+09 | 0.00 | 0.150824E+10 | 0.00 | 0.00 | 0.781715E+12 | 0.00 | 22.12 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 99250984.69 | 0.00 | 0.00 | 0.424723E+11 | 0.00 | 21.20 |
Maximum of Months | 0.00 | 0.594586E+09 | 0.00 | 0.156961E+09 | 0.00 | 0.00 | 0.798501E+11 | 0.00 | 22.90 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.150802E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124608E+09 | 0.00 | 0.00 | 1.19 |
February | 0.143494E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129317E+09 | 0.00 | 0.00 | 1.20 |
March | 0.169603E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.19 |
April | 0.162227E+11 | 1583434.89 | 0.00 | 137.32 | 1090434.21 | 0.00 | 87700.98 | 0.00 | 1.20 |
May | 0.159853E+11 | 0.00 | 0.00 | 24343.23 | 0.00 | 0.00 | 13515139.90 | 0.00 | 1.20 |
June | 0.131390E+11 | 0.00 | 0.00 | 116472.86 | 0.00 | 0.00 | 71571229.40 | 0.00 | 1.20 |
July | 0.107642E+11 | 25505185.93 | 0.00 | 654695.13 | 7147271.69 | 0.00 | 0.389041E+09 | 0.00 | 1.20 |
August | 0.944094E+10 | 91364250.86 | 0.00 | 1059812.15 | 20357592.76 | 0.00 | 0.489436E+09 | 0.00 | 1.21 |
September | 0.137171E+11 | 0.00 | 0.00 | 565097.34 | 0.00 | 0.00 | 0.155566E+09 | 0.00 | 1.20 |
October | 0.179048E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.20 |
November | 0.160918E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.19 |
December | 0.154459E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159739E+09 | 0.00 | 0.00 | 1.19 |
Annual Sum or Average | 0.175101E+12 | 0.118453E+09 | 0.00 | 2420558.02 | 28595298.66 | 0.413664E+09 | 0.111922E+10 | 0.00 | 1.20 |
Minimum of Months | 0.944094E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.19 |
Maximum of Months | 0.179048E+11 | 91364250.86 | 0.00 | 1059812.15 | 20357592.76 | 0.159739E+09 | 0.489436E+09 | 0.00 | 1.21 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:21:35
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.604553E+11 | 0.772854E+10 | 0.235430E+12 | 0.935829E+12 | 0.637284E+11 |
February | 0.132335E+12 | 0.647635E+10 | 0.196149E+12 | 0.791883E+12 | 0.768838E+11 |
March | 0.251618E+12 | 0.624868E+10 | 0.185092E+12 | 0.767380E+12 | 0.110401E+12 |
April | 0.405045E+12 | 0.515783E+10 | 0.149777E+12 | 0.629969E+12 | 0.165672E+12 |
May | 0.531481E+12 | 0.459325E+10 | 0.130677E+12 | 0.552870E+12 | 0.220408E+12 |
June | 0.547216E+12 | 0.367741E+10 | 0.101461E+12 | 0.425358E+12 | 0.275958E+12 |
July | 0.569419E+12 | 0.298194E+10 | 0.821845E+11 | 0.351256E+12 | 0.389411E+12 |
August | 0.448963E+12 | 0.255185E+10 | 0.706203E+11 | 0.301879E+12 | 0.457216E+12 |
September | 0.285569E+12 | 0.364896E+10 | 0.107394E+12 | 0.440631E+12 | 0.256092E+12 |
October | 0.190393E+12 | 0.497931E+10 | 0.150228E+12 | 0.612924E+12 | 0.157792E+12 |
November | 0.708633E+11 | 0.600515E+10 | 0.187910E+12 | 0.743304E+12 | 0.922716E+11 |
December | 0.388054E+11 | 0.735080E+10 | 0.224337E+12 | 0.897030E+12 | 0.714876E+11 |
Annual Sum or Average | 0.353216E+13 | 0.614001E+11 | 0.182126E+13 | 0.745031E+13 | 0.233732E+13 |
Minimum of Months | 0.388054E+11 | 0.255185E+10 | 0.706203E+11 | 0.301879E+12 | 0.637284E+11 |
Maximum of Months | 0.569419E+12 | 0.772854E+10 | 0.235430E+12 | 0.935829E+12 | 0.457216E+12 |