Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:24
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695
Simulation Timestamp: 2024-07-03 12:25:04
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:04
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 10790.29 | 951.08 | 951.08 |
Net Site Energy | 10790.29 | 951.08 | 951.08 |
Total Source Energy | 22141.18 | 1951.57 | 1951.57 |
Net Source Energy | 22141.18 | 1951.57 | 1951.57 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1229.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 588.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 781.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 193.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1658.18 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 813.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 586.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 71.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 164.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 94.78 | 2757.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | 61.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 5014.16 | 5776.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 1229.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 588.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 781.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 193.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 872.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 14.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 8.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 21.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 789.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 2.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 586.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 71.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 164.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 94.78 | 2757.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5742.51 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.69 | |
Refrigeration | General | 7.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 20.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 33.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1229.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 588.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 781.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 193.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 1658.18 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 813.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 586.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 71.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 164.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 94.78 | 2757.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | Unassigned | 61.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 85.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 118.21 | 351.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 237.76 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 441.96 | 509.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 85.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 118.21 | 351.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 237.76 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 441.96 | 509.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 5014.162 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 5014.162 | 100.00 |
Total On-Site and Utility Electric Sources | 5014.162 | 100.00 |
Total Electricity End Uses | 5014.162 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 63.50 | 1.81 |
Air to Air Heat Recovery for Heating | 3436.79 | 98.19 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 3500.29 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9857.19 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9857.19 | 100.00 |
Total Water End Uses | 9857.19 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 6.00 |
Time Setpoint Not Met During Occupied Cooling | 510.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 7444.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5B
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CO_DENVER
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER1 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| FLR_3_DOAS COOLING COIL | VAV WITH REHEAT COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH LAUNDRY G WATER HEATER | SWH BOOSTER E WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |CoilReportMonthly
| FLR_3_DOAS HEATING COIL | VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | FLR_3_DOAS COOLING COIL | VAV WITH REHEAT COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |FanReportMonthly
| FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL_FANCOILFAN | ROOM_2_FLR_3 FAN COIL_FANCOILFAN | ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | ROOM_5_FLR_3 FAN COIL_FANCOILFAN | ROOM_6_FLR_3 FAN COIL_FANCOILFAN | ROOM_1_FLR_6 FAN COIL_FANCOILFAN | ROOM_2_FLR_6 FAN COIL_FANCOILFAN | ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| FLR_3_DOAS | VAV WITH REHEAT |AirLoopSystemComponentLoadsMonthly
| FLR_3_DOAS | VAV WITH REHEAT |AirLoopSystemComponentEnergyUseMonthly
| FLR_3_DOAS | VAV WITH REHEAT |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:04
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:24 |
RunPeriod | RUNPERIOD 1 |
Weather File | Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 |
Latitude [deg] | 39.72 |
Longitude [deg] | -104.8 |
Elevation [m] | 1726.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 8.8143 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.26 | 23.26 | 11.3140 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 11.3140 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 4.6285 | 61.93 | 5.3800 |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 5.7199 | 46.45 | 2.6900 |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 4.6285 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.50 | 65.50 | 10.0104 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.08 | 85.08 | 10.7639 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 8.2882 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 8.2882 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 7.1042 | 18.58 | 0.0000 |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.74 | 6.74 | 8.2882 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 10.0104 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 10.0104 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.37 | 26.37 | 11.4097 | 4.65 | 2934.4875 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.20 | 28.20 | 7.1042 | 18.58 | 0.0000 |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 8.5566 | 7.07 | 41.0709 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 8.5566 | 7.07 | 41.0709 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 1978.83 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 8.8143 | 18.58 | 5.3800 | |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 1.00 | RETAIL_1_FLR_1 | GENERAL | RETAIL_1_FLR_1 | 11.3140 | 6.19 | 10.7600 | |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 1.00 | RETAIL_2_FLR_1 | GENERAL | RETAIL_2_FLR_1 | 11.3140 | 6.19 | 10.7600 | |
MECH_FLR_1 | 164.24 | Yes | Yes | 1.00 | MECH_FLR_1 | GENERAL | MECH_FLR_1 | 4.6285 | 61.93 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 1.00 | STORAGE_FLR_1 | GENERAL | STORAGE_FLR_1 | 5.7199 | 46.45 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 1.00 | LAUNDRY_FLR_1 | GENERAL | LAUNDRY_FLR_1 | 4.6285 | 9.29 | 597.5300 | |
CAFE_FLR_1 | 188.86 | Yes | Yes | 1.00 | CAFE_FLR_1 | GENERAL | CAFE_FLR_1 | 10.0104 | 1.33 | 5.3800 | |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 1.00 | LOBBY_FLR_1 | GENERAL | LOBBY_FLR_1 | 10.7639 | 3.10 | 8.0700 | |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_1_FLR_3 | GENERAL | ROOM_1_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_2_FLR_3 | GENERAL | ROOM_2_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 76.00 | ROOM_3_MULT19_FLR_3 | GENERAL | ROOM_3_MULT19_FLR_3 | 8.2882 | 16.35 | 10.5200 | |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 76.00 | ROOM_4_MULT19_FLR_3 | GENERAL | ROOM_4_MULT19_FLR_3 | 8.2882 | 16.35 | 10.5200 | |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_5_FLR_3 | GENERAL | ROOM_5_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_6_FLR_3 | GENERAL | ROOM_6_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 4.00 | CORRIDOR_FLR_3 | GENERAL | CORRIDOR_FLR_3 | 7.1042 | 18.58 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_1_FLR_6 | GENERAL | ROOM_1_FLR_6 | 8.2882 | 26.01 | 6.7500 | |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_2_FLR_6 | GENERAL | ROOM_2_FLR_6 | 8.2882 | 26.01 | 6.7500 | |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 9.00 | ROOM_3_MULT9_FLR_6 | GENERAL | ROOM_3_MULT9_FLR_6 | 8.2882 | 16.35 | 10.5200 | |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1.00 | BANQUET_FLR_6 | GENERAL | BANQUET_FLR_6 | 10.0104 | 1.33 | 67.8200 | |
DINING_FLR_6 | 331.66 | Yes | Yes | 1.00 | DINING_FLR_6 | GENERAL | DINING_FLR_6 | 10.0104 | 1.33 | 67.8200 | |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 1.00 | KITCHEN_FLR_6 | GENERAL | KITCHEN_FLR_6 | 11.4097 | 4.65 | 2934.4875 | |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1.00 | CORRIDOR_FLR_6 | GENERAL | CORRIDOR_FLR_6 | 7.1042 | 18.58 | 0.0000 | |
Total | 11345.29 | 8.5566 | 3.54 | 41.0709 | |||||||
Conditioned Total | 11345.29 | 8.5566 | 3.54 | 41.0709 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 11345.29 | 11345.29 | 0.00 | 0.00 | 4.6520 | 8.82 | 37.1989 |
Total | 11345.29 | 11345.29 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:04
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 26-JUN-19:30 | 21-DEC-19:30 | - | - | - | - | - | - | - | - | - | - | 19-APR-20:49 |
Heating | 0.00 | 276927.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 129595.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 64632.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 12338.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 86439.81 | 87619.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 10999.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 41509.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 3960.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 3980.01 | 242962.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 2355.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 365749.68 | 607509.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 276927.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 129595.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 64632.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 12338.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 56456.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 49984.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 37635.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1249.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 9600.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 150.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 41509.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 3960.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 3980.01 | 242962.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 1056.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1057.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:04
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1332.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1863.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2475.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 613.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5251.45 | 1939.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2577.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1858.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 224.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 519.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 300.17 | 2989.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 194.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 15879.85 | 6261.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 117.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 164.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 218.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 54.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 462.88 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 227.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 163.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 19.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 45.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 26.46 | 263.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1399.69 | 551.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 117.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 164.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 218.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 54.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 462.88 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 227.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 163.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 19.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 45.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 26.46 | 263.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1399.69 | 551.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:04
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
BASEMENT VAV BOX COMPONENT | 2.96 | 0.509091 | 0.432000 | 1.28 | 1.00 | 0.500000 | 0.000748 | 0.000048 | 1.28 | 16.70 | 0.008000 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.445010 | 0.114848 | 0.432000 | 0.192244 | 0.432000 | 0.500000 | 0.003317 | 0.000034 | 0.192244 | 16.70 | 0.008000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.279114 | 0.212041 | 0.432000 | 0.120577 | 0.565443 | 0.500000 | 0.001797 | 0.000013 | 0.120577 | 16.70 | 0.008000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.220436 | 0.567754 | 0.432000 | 0.095228 | 1.00 | 0.500000 | 0.000671 | 0.000019 | 0.095228 | 16.70 | 0.008000 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.133102 | 0.542489 | 0.432000 | 0.057500 | 1.00 | 0.500000 | 0.000702 | 0.000013 | 0.064486 | 16.70 | 0.008000 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 4.00 | 0.014851 | 0.432000 | 1.73 | 0.432000 | 0.500000 | 0.025655 | 0.000085 | 1.73 | 16.70 | 0.008000 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.87 | 0.076847 | 0.432000 | 0.809009 | 0.432000 | 0.500000 | 0.004958 | 0.000098 | 0.809009 | 16.70 | 0.008000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 5.93 | 0.168167 | 0.432000 | 2.56 | 0.448446 | 0.500000 | 0.002266 | 0.000249 | 2.56 | 16.70 | 0.008000 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.88 | 0.632063 | 0.432000 | 0.811221 | 1.00 | 0.500000 | 0.000603 | 0.000123 | 0.811221 | 16.70 | 0.008000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.68 | 0.094411 | 0.432000 | 1.16 | 0.432000 | 0.500000 | 0.004036 | 0.000104 | 1.16 | 16.70 | 0.008000 |
DINING_FLR_6 VAV BOX COMPONENT | 2.80 | 0.090117 | 0.432000 | 1.21 | 0.432000 | 0.500000 | 0.004228 | 0.000108 | 1.21 | 16.70 | 0.008000 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.78 | 0.050882 | 0.432000 | 1.20 | 0.432000 | 0.500000 | 0.013468 | 0.000067 | 1.20 | 16.70 | 0.008000 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 0.980005 | 0.320446 | 0.432000 | 0.423362 | 0.854524 | 0.500000 | 0.001189 | 0.000080 | 0.423362 | 16.70 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
BASEMENT VAV BOX REHEAT COIL | 5483.86 | 0.000048 | 114.36 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 3855.72 | 0.000034 | 99.92 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1487.83 | 0.000013 | 34.41 |
MECH_FLR_1 VAV BOX REHEAT COIL | 2118.41 | 0.000019 | 56.88 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 1497.44 | 0.000013 | 40.87 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 9698.03 | 0.000085 | 205.52 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 11218.54 | 0.000098 | 265.07 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 28416.19 | 0.000249 | 646.26 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | 6651.82 | 0.000058 | 190.06 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | 6656.73 | 0.000058 | 190.20 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 38221.42 | 0.000334 | 1092.08 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 38328.32 | 0.000335 | 1095.13 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | 6651.82 | 0.000058 | 190.06 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | 6656.73 | 0.000058 | 190.20 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 14095.13 | 0.000123 | 350.47 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | 2063.99 | 0.000018 | 58.97 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | 2063.90 | 0.000018 | 58.97 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 9931.79 | 0.000087 | 283.77 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 11926.07 | 0.000104 | 268.40 |
DINING_FLR_6 VAV BOX REHEAT COIL | 12312.38 | 0.000108 | 276.55 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 7679.28 | 0.000067 | 164.33 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 9196.36 | 0.000080 | 244.79 |
FLR_3_DOAS HEATING COIL | 20913.38 | 0.000183 | 324.43 |
VAV WITH REHEAT HEATING COIL | 273341.93 | 0.002391 | 4240.38 |
Design Size Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 0.061735 |
ROOM_2_FLR_3 DIRECT AIR | 0.061728 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 0.837072 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 0.837300 |
ROOM_5_FLR_3 DIRECT AIR | 0.061735 |
ROOM_6_FLR_3 DIRECT AIR | 0.061728 |
ROOM_1_FLR_6 DIRECT AIR | 0.015434 |
ROOM_2_FLR_6 DIRECT AIR | 0.015432 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 0.099154 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Hot Water Flow [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 1.45 | 0.000058 | 0.000378 |
ROOM_2_FLR_3 FAN COIL | 1.42 | 0.000058 | 0.000369 |
ROOM_3_MULT19_FLR_3 FAN COIL | 8.29 | 0.000334 | 0.002132 |
ROOM_4_MULT19_FLR_3 FAN COIL | 7.50 | 0.000335 | 0.002039 |
ROOM_5_FLR_3 FAN COIL | 1.28 | 0.000058 | 0.000333 |
ROOM_6_FLR_3 FAN COIL | 1.25 | 0.000058 | 0.000326 |
ROOM_1_FLR_6 FAN COIL | 0.385667 | 0.000018 | 0.000100 |
ROOM_2_FLR_6 FAN COIL | 0.376018 | 0.000018 | 0.000098 |
ROOM_3_MULT9_FLR_6 FAN COIL | 1.69 | 0.000087 | 0.000446 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COIL_FANCOILFAN | 1.45 |
ROOM_2_FLR_3 FAN COIL_FANCOILFAN | 1.42 |
ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | 8.29 |
ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | 7.50 |
ROOM_5_FLR_3 FAN COIL_FANCOILFAN | 1.28 |
ROOM_6_FLR_3 FAN COIL_FANCOILFAN | 1.25 |
ROOM_1_FLR_6 FAN COIL_FANCOILFAN | 0.385667 |
ROOM_2_FLR_6 FAN COIL_FANCOILFAN | 0.376018 |
ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN | 1.69 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Coil Load [W] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | 21.82 | 6.70 | 0.008542 | 12.80 | 0.008500 | 0.000378 | 1.45 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | 21.82 | 6.70 | 0.008543 | 12.80 | 0.008500 | 0.000369 | 1.42 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 21.82 | 6.70 | 0.008481 | 12.80 | 0.008481 | 0.002132 | 8.29 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 21.82 | 6.70 | 0.008709 | 12.80 | 0.008500 | 0.002039 | 7.50 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | 21.82 | 6.70 | 0.008547 | 12.80 | 0.008500 | 0.000333 | 1.28 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | 21.82 | 6.70 | 0.008548 | 12.80 | 0.008500 | 0.000326 | 1.25 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | 21.82 | 6.70 | 0.008540 | 12.80 | 0.008500 | 0.000100 | 0.385667 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | 21.82 | 6.70 | 0.008541 | 12.80 | 0.008500 | 0.000098 | 0.376018 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 21.82 | 6.70 | 0.008601 | 12.80 | 0.008500 | 0.000446 | 1.69 | |
FLR_3_DOAS COOLING COIL | 33.90 | 6.70 | 0.005475 | 11.72 | 0.005475 | 0.001291 | 2.05 | 45136.60 |
VAV WITH REHEAT COOLING COIL | 28.30 | 6.70 | 0.007825 | 10.55 | 0.007825 | 0.013561 | 26.81 | 474160.83 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
VAV WITH REHEAT | 13.48 | 11.65 | 26.97 | 11.65 | 26.81 | 26.81 | 0.300000 | 0.434491 | 26.81 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
VAV WITH REHEAT_OA_CONTROLLER | 26.81 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
FLR_3_DOAS OA HEAT RECOVERY | 2.05 |
VAV WITH REHEAT OA HEAT RECOVERY | 11.66 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS FAN | 2.05 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.001291 | 0.000369 |
FLR_3_DOAS_HEATC_CONTROLLER | 0.000183 | |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.013561 | 0.000035 |
VAV WITH REHEAT_HEATC_CONTROLLER | 0.002391 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT FAN | 26.81 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.021074 | 3440.75 | |
HEATSYS1 PUMP | 0.004641 | 1397.59 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.004641 | 0.556891 |
COOLSYS1 | 0.021074 | 2.53 |
SWHSYS1 | 0.000375 | 0.045004 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 530467.11 | 530467.11 | 0.004641 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.021074 | 2382.15 |
SWHSYS1 PUMP | 0.000375 | 47.91 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.021074 | 736858.95 | 737566.70 | 84.08 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000375 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:04
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:04
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:04
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 7.10 | 3.00 | -1.00 | 0.80 | -0.20 | 4.80 | 6.10 | 13.70 | 22.20 | 22.70 | 21.70 | 18.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 | 39.72 | -104.75 | -7.00 | 1726.00 | 82237 | 0.9774 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 9.95 | 23.70 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.58 | 23.26 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.72 | 65.50 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.80 | 85.08 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.70 | 6.74 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.96 | 26.37 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.27 | 28.20 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 8.814 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 14.194 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 11.314 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 22.074 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 11.314 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 22.074 | No |
4 | MECH_FLR_1 | 164.24 | 2.7 | 61.932 | 1.615E-002 | 4.628 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 10.008 | No |
5 | STORAGE_FLR_1 | 94.76 | 2.0 | 46.451 | 2.153E-002 | 5.720 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 8.410 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 4.628 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 602.158 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 10.010 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 15.390 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 10.764 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.834 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 8.288 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 18.808 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 8.288 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 18.808 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 21.0 | 18.581 | 5.382E-002 | 7.104 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.104 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 8.288 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 18.808 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 10.010 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 77.830 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 10.010 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 77.830 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 11.410 | 515.227 | 2419.260 | 0.000 | 0.000 | 0.000 | 2945.897 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 22.2 | 18.581 | 5.382E-002 | 7.104 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.104 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | STORAGE_FLR_1 PEOPLE | BLDG_OCC_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.0 | 2.153E-002 | 46.451 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | CORRIDOR_FLR_3 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 21.0 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 21 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
21 | CORRIDOR_FLR_6 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 22.2 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
22 | MECH_FLR_1 PEOPLE | BLDG_OCC_SCH | MECH_FLR_1 | 164.24 | 2.7 | 2.7 | 1.615E-002 | 61.932 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 3 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_BASEMENT | BASEMENT | 1978.83 | 106.5 | 17441.963 | 8.814 | 163.776 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 17441.963 |
2 | RETAIL_1_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_1_FLR_1 | 67.07 | 10.8 | 758.849 | 11.314 | 70.076 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 758.849 |
3 | RETAIL_2_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_2_FLR_1 | 77.67 | 12.5 | 878.750 | 11.314 | 70.076 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 878.750 |
4 | MECH_FLR_1_LIGHTS | LTG_SCH_MECHANIC | MECH_FLR_1 | 164.24 | 2.7 | 760.196 | 4.628 | 286.650 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 760.196 |
5 | STORAGE_FLR_1_LIGHTS | LTG_SCH_STORAGE | STORAGE_FLR_1 | 94.76 | 2.0 | 542.017 | 5.720 | 265.695 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 542.017 |
6 | LAUNDRY_FLR_1_LIGHTS | LTG_SCH_LAUNDRY | LAUNDRY_FLR_1 | 78.04 | 8.4 | 361.204 | 4.628 | 43.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 361.204 |
7 | CAFE_FLR_1_LIGHTS | LTG_SCH_DINING | CAFE_FLR_1 | 188.86 | 142.3 | 1890.589 | 10.010 | 13.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1890.589 |
8 | LOBBY_FLR_1_LIGHTS | LTG_SCH_LOBBY | LOBBY_FLR_1 | 1308.19 | 422.4 | 14081.185 | 10.764 | 33.333 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14081.185 |
9 | ROOM_1_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_3 | 39.02 | 1.5 | 323.422 | 8.288 | 215.615 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.422 |
10 | ROOM_2_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_3 | 39.02 | 1.5 | 323.384 | 8.288 | 215.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.384 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 203.259 | 8.288 | 135.506 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 203.259 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 203.314 | 8.288 | 135.543 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 203.314 |
13 | ROOM_5_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_5_FLR_3 | 39.02 | 1.5 | 323.422 | 8.288 | 215.615 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.422 |
14 | ROOM_6_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_6_FLR_3 | 39.02 | 1.5 | 323.384 | 8.288 | 215.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.384 |
15 | CORRIDOR_FLR_3_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2766.397 | 7.104 | 132.003 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2766.397 |
16 | ROOM_1_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_6 | 39.02 | 1.5 | 323.422 | 8.288 | 215.615 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.422 |
17 | ROOM_2_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_6 | 39.02 | 1.5 | 323.384 | 8.288 | 215.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.384 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 203.314 | 8.288 | 135.543 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 203.314 |
19 | BANQUET_FLR_6_LIGHTS | LTG_SCH_DINING | BANQUET_FLR_6 | 331.66 | 249.9 | 3320.034 | 10.010 | 13.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3320.034 |
20 | DINING_FLR_6_LIGHTS | LTG_SCH_DINING | DINING_FLR_6 | 331.66 | 249.9 | 3320.034 | 10.010 | 13.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3320.034 |
21 | KITCHEN_FLR_6_LIGHTS | LTG_SCH_KITCHEN | KITCHEN_FLR_6 | 103.30 | 22.2 | 1178.676 | 11.410 | 53.003 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1178.676 |
22 | CORRIDOR_FLR_6_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_6 | 412.12 | 22.2 | 2927.804 | 7.104 | 132.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2927.804 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 2.7 | 883.628 | 5.380 | 333.193 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 254.902 | 2.690 | 124.952 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 457.500 | 4.429 | 20.573 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 457.500 | 457.500 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 285.000 | 2.759 | 12.816 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 285.000 | 285.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 2.390 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
6 | RES_ROOF | 19 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
7 | NONRES_EXT_WALL_GRD | 21 | 3 | 9 | 0.167 | 0.7214 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | NONRES_EXT_WALL_MID | 22 | 3 | 9 | 0.167 | 0.9169 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | NONRES_EXT_WALL_TOP | 23 | 3 | 9 | 0.167 | 0.9299 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | RES_EXT_WALL_MID | 25 | 3 | 9 | 0.167 | 0.8441 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | RES_EXT_WALL_TOP | 26 | 3 | 9 | 0.167 | 0.8569 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | NONRES_FLOOR | 30 | 3 | 7 | 0.167 | 0.2277 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
13 | NONRES_FLOOR_CEILING | 33 | 3 | 7 | 0.167 | 0.2277 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
14 | BASEMENT_FLOOR | 36 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
15 | BASEMENT_WALL_NORTH_CFACTOR | 39 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | BASEMENT_WALL_EAST_CFACTOR | 40 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | BASEMENT_WALL_SOUTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
18 | BASEMENT_WALL_WEST_CFACTOR | 42 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4184 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
10 | RES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
11 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
12 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.219 |
14 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9233 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9080 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | RES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.017 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
25 | RES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9996 |
26 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
27 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.131 |
28 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
29 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
30 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
31 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
32 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.131 |
33 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
34 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
35 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
39 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
40 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
41 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
42 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 2.3900722 | 2.3900722 | 2.3900722 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
21 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
22 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
23 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
24 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
25 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
26 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
27 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
28 | 9 | -0.17110984E-14 | 0.24103936E-16 | -0.15943139E-09 | 0.44685538E-16 |
29 | 8 | 0.23237837E-07 | 0.98082464E-13 | 0.39196772E-03 | -0.26422217E-09 |
30 | 7 | -0.12664044E-01 | 0.50206963E-08 | -0.23693971E-01 | 0.14399480E-03 |
31 | 6 | 0.41682950 | 0.17394333E-05 | 0.48185553 | -0.48830741E-02 |
32 | 5 | -5.3025782 | 0.64717486E-04 | -4.5162048 | 0.64572787E-01 |
33 | 4 | 33.498276 | 0.52771084E-03 | 21.733161 | -0.42870077 |
34 | 3 | -112.28016 | 0.11468200E-02 | -56.202879 | 1.5304215 |
35 | 2 | 198.17562 | 0.64344368E-03 | 78.405936 | -2.9173034 |
36 | 1 | -171.55028 | 0.68528185E-04 | -55.409506 | 2.7523484 |
37 | 0 | 57.057407 | 0.38903588E-06 | 15.533392 | |
38 | 9 | -0.29206544E-14 | 0.31488305E-16 | -0.15031727E-09 | 0.48064473E-16 |
39 | 8 | 0.21958778E-07 | 0.12356532E-12 | 0.37867817E-03 | -0.24967887E-09 |
40 | 7 | -0.12267989E-01 | 0.64094198E-08 | -0.23123879E-01 | 0.13949151E-03 |
41 | 6 | 0.40606866 | 0.22324768E-05 | 0.47270315 | -0.47562292E-02 |
42 | 5 | -5.1975737 | 0.83445227E-04 | -4.4459647 | 0.63270770E-01 |
43 | 4 | 33.033866 | 0.68326082E-03 | 21.458733 | -0.42253461 |
44 | 3 | -111.29222 | 0.14903991E-02 | -55.660391 | 1.5161481 |
45 | 2 | 197.19665 | 0.83899866E-03 | 77.908180 | -2.9017570 |
46 | 1 | -171.18874 | 0.89630080E-04 | -55.264364 | 2.7460119 |
47 | 0 | 57.057407 | 0.51068186E-06 | 15.557036 | |
48 | 9 | -0.29497736E-14 | 0.32939851E-16 | -0.14970570E-09 | 0.45584202E-16 |
49 | 8 | 0.21872815E-07 | 0.12523736E-12 | 0.37777579E-03 | -0.24870145E-09 |
50 | 7 | -0.12241065E-01 | 0.65023057E-08 | -0.23085114E-01 | 0.13918537E-03 |
51 | 6 | 0.40533708 | 0.22656711E-05 | 0.47208016 | -0.47476058E-02 |
52 | 5 | -5.1904345 | 0.84713026E-04 | -4.4411801 | 0.63182247E-01 |
53 | 4 | 33.002288 | 0.69384191E-03 | 21.440032 | -0.42211534 |
54 | 3 | -111.22504 | 0.15138688E-02 | -55.623419 | 1.5151774 |
55 | 2 | 197.13007 | 0.85240592E-03 | 77.874271 | -2.9006996 |
56 | 1 | -171.16415 | 0.91081681E-04 | -55.254501 | 2.7455809 |
57 | 0 | 57.057407 | 0.51907125E-06 | 15.558664 | |
58 | 9 | -0.24257523E-14 | 0.33690592E-16 | -0.15372093E-09 | 0.39666009E-16 |
59 | 8 | 0.22436951E-07 | 0.11417013E-12 | 0.38367618E-03 | -0.25511586E-09 |
60 | 7 | -0.12417040E-01 | 0.58916776E-08 | -0.23338459E-01 | 0.14118628E-03 |
61 | 6 | 0.41011853 | 0.20479623E-05 | 0.47615013 | -0.48039676E-02 |
62 | 5 | -5.2370942 | 0.76414309E-04 | -4.4724296 | 0.63760808E-01 |
63 | 4 | 33.208666 | 0.62469949E-03 | 21.562156 | -0.42485549 |
64 | 3 | -111.66410 | 0.13607335E-02 | -55.864850 | 1.5215209 |
65 | 2 | 197.56520 | 0.76503996E-03 | 78.095736 | -2.9076095 |
66 | 1 | -171.32486 | 0.81633884E-04 | -55.318971 | 2.7483976 |
67 | 0 | 57.057407 | 0.46449959E-06 | 15.548073 | |
68 | 9 | -0.24053431E-14 | 0.30582108E-16 | -0.15312349E-09 | 0.40258954E-16 |
69 | 8 | 0.22353057E-07 | 0.11582316E-12 | 0.38280191E-03 | -0.25416195E-09 |
70 | 7 | -0.12390977E-01 | 0.59826426E-08 | -0.23300939E-01 | 0.14088992E-03 |
71 | 6 | 0.40941037 | 0.20803184E-05 | 0.47554760 | -0.47956200E-02 |
72 | 5 | -5.2301838 | 0.77645268E-04 | -4.4678046 | 0.63675121E-01 |
73 | 4 | 33.178102 | 0.63493787E-03 | 21.544084 | -0.42444968 |
74 | 3 | -111.59908 | 0.13833754E-02 | -55.829123 | 1.5205815 |
75 | 2 | 197.50076 | 0.77794062E-03 | 78.062960 | -2.9065863 |
76 | 1 | -171.30107 | 0.83027327E-04 | -55.309421 | 2.7479805 |
77 | 0 | 57.057407 | 0.47253235E-06 | 15.549635 | |
78 | 7 | -0.14139450E-14 | -0.18802902E-16 | -0.22311785E-13 | 0.54375338E-15 |
79 | 6 | 0.16999971E-10 | 0.27590984E-11 | 0.52267399E-09 | -0.18616555E-10 |
80 | 5 | -0.63950587E-07 | 0.13451749E-07 | -0.21905428E-05 | 0.17144787E-06 |
81 | 4 | 0.72477507E-04 | 0.50724086E-05 | 0.17668371E-02 | -0.28223350E-03 |
82 | 3 | -0.10573811E-01 | 0.17927531E-03 | -0.21549182 | 0.43318087E-01 |
83 | 2 | 0.15010112 | 0.77388015E-03 | 2.8998331 | -0.61891034 |
84 | 1 | -0.37982851 | 0.49528818E-03 | -7.1368477 | 1.5694772 |
85 | 0 | 0.24168561 | 0.34021171E-05 | 4.4521969 | |
86 | 7 | -0.22311785E-13 | -0.18802902E-16 | -0.14139450E-14 | 0.54375338E-15 |
87 | 6 | 0.52267399E-09 | 0.27590984E-11 | 0.16999971E-10 | -0.18616555E-10 |
88 | 5 | -0.21905428E-05 | 0.13451749E-07 | -0.63950587E-07 | 0.17144787E-06 |
89 | 4 | 0.17668371E-02 | 0.50724086E-05 | 0.72477507E-04 | -0.28223350E-03 |
90 | 3 | -0.21549182 | 0.17927531E-03 | -0.10573811E-01 | 0.43318087E-01 |
91 | 2 | 2.8998331 | 0.77388015E-03 | 0.15010112 | -0.61891034 |
92 | 1 | -7.1368477 | 0.49528818E-03 | -0.37982851 | 1.5694772 |
93 | 0 | 4.4521969 | 0.34021171E-05 | 0.24168561 | |
94 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
95 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
96 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
97 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
98 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
99 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
100 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
101 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
102 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
103 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
104 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
105 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
106 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
107 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
108 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
109 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
110 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
111 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
112 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
113 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
114 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
115 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
116 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
117 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
118 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
119 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
120 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
121 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
122 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
123 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
124 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
125 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
126 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
127 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
128 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
129 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
130 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
131 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
132 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
133 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.38_SHGC_0.38 | 37 | 1 | VerySmooth | 2.159 | 2.159 | 1.000 | 0.381 | ||
2 | RESWINDOW_U_0.38_SHGC_0.38 | 38 | 1 | VerySmooth | 2.159 | 2.159 | 1.000 | 0.381 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 3.45900E-002 | 0.29373 | 0.49855 | 0.49855 | 0.41800 | 0.13582 | 0.17513 | 0.00000 | 0.84000 | 0.84000 | 0.11893 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 3.45900E-002 | 0.29373 | 0.49855 | 0.49855 | 0.41800 | 0.13582 | 0.17513 | 0.00000 | 0.84000 | 0.84000 | 0.11893 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | CAFE_FLR_1 | 1 | 0 |
2 | LOBBY_FLR_1 | 1 | 0 |
3 | BANQUET_FLR_6 | 1 | 0 |
4 | DINING_FLR_6 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | CAFE_FLR_1 | 0 | |
2 | LOBBY_FLR_1 | 0 | |
3 | BANQUET_FLR_6 | 0 | |
4 | DINING_FLR_6 | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH LAUNDRY G WATER HEATER | 1.1356 | 163316.0 | 11.511 | 0.4388 |
2 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.219 | 1.1187 |
3 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 2.2712 | 175842.6 | 5.775 | 0.3748 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 1.764E-002 | 2.631E-004 | 1.298E-004 | 0.239 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.811E-003 | 8.769E-005 | 2.388E-004 | 7.967E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 2.7 | 1.610E-002 | 9.800E-005 | 2.563E-004 | 8.904E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 9.287E-003 | 9.800E-005 | 2.127E-004 | 8.904E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 2.198E-002 | 2.816E-004 | 2.506E-004 | 0.256 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 3.900E-002 | 2.065E-004 | 1.137E-004 | 0.188 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 0.111 | 8.519E-005 | 1.629E-004 | 7.740E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 2.563E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 2.563E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 2.857E-003 | 1.165E-004 | 2.563E-004 | 0.138 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 2.858E-003 | 1.165E-004 | 2.563E-004 | 0.138 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 2.563E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 2.563E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 1.238E-002 | 3.180E-005 | 2.563E-004 | 3.755E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 1.297E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 1.297E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 5.239E-003 | 2.136E-004 | 1.165E-004 | 0.252 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 2.500E-002 | 7.539E-005 | 5.825E-005 | 8.904E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 2.500E-002 | 7.539E-005 | 5.825E-005 | 8.904E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 2.238E-002 | 2.167E-004 | 1.174E-004 | 0.256 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 2.191E-002 | 5.316E-005 | 4.403E-005 | 6.278E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1527 |
2 | Clear Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 7.9324E-002 |
3 | Clear Turbid Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1717 |
4 | Clear Turbid Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 8.9683E-002 |
5 | Intermediate Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1091 |
6 | Intermediate Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 4.2955E-002 |
7 | Overcast Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 4.3971E-002 |
8 | Overcast Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 1.4607E-002 |
9 | Clear Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1739 |
10 | Clear Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 9.5745E-002 |
11 | Clear Turbid Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1963 |
12 | Clear Turbid Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 0.1080 |
13 | Intermediate Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1208 |
14 | Intermediate Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 5.3719E-002 |
15 | Overcast Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 4.9373E-002 |
16 | Overcast Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 1.9973E-002 |
17 | Clear Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 3.7455E-002 |
18 | Clear Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 2.1621E-002 |
19 | Clear Turbid Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.8716E-002 |
20 | Clear Turbid Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.6274E-002 |
21 | Intermediate Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.7733E-002 |
22 | Intermediate Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.1091E-002 |
23 | Overcast Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 4.3283E-002 |
24 | Overcast Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.5348E-002 |
25 | Clear Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 3.7455E-002 |
26 | Clear Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 2.1621E-002 |
27 | Clear Turbid Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.8716E-002 |
28 | Clear Turbid Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.6274E-002 |
29 | Intermediate Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.7733E-002 |
30 | Intermediate Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.1091E-002 |
31 | Overcast Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 4.3283E-002 |
32 | Overcast Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.5348E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 33088.99922 | 33088.99922 | 2.96188 | 2.96188 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:40:00 | 27.04267 | 5.46480E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 0.85446 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
3 | RETAIL_1_FLR_1 | Cooling | 4971.06520 | 4971.06520 | 0.44501 | 0.44501 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 33.40667 | 5.47451E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 3032.21408 | 3032.21408 | 0.16011 | 0.16011 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 3117.78202 | 3117.78202 | 0.27911 | 0.27911 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | 33.01200 | 5.47390E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 971.32158 | 971.32158 | 5.12906E-002 | 9.17347E-002 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 2462.92784 | 2462.92784 | 0.22044 | 0.22044 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 29.23800 | 5.46812E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 1710.55543 | 1710.55543 | 9.03256E-002 | 9.03256E-002 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 1487.13955 | 1487.13955 | 0.13310 | 0.13310 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 30.34800 | 5.46981E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 1221.21619 | 1221.21619 | 6.44862E-002 | 6.44862E-002 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 44734.42632 | 44734.42632 | 4.00417 | 4.00417 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 33.90000 | 5.47527E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 2290.04758 | 2290.04758 | 0.12092 | 0.12092 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 20900.29394 | 20900.29394 | 1.87271 | 1.87271 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 33.40667 | 5.47451E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 7752.78508 | 7752.78508 | 0.40938 | 0.67639 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 66193.15111 | 66193.15111 | 5.92766 | 5.92766 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 33.53000 | 5.47470E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 17446.48062 | 17446.48062 | 0.92126 | 1.89399 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 12038.82685 | 12038.82685 | 1.45205 | 1.45205 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 32.02533 | 5.47238E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 6651.86290 | 6651.86290 | 0.35331 | 0.35331 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 11760.29393 | 11760.29393 | 1.41846 | 1.41846 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 31.82800 | 5.47208E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 6656.77814 | 6656.77814 | 0.35357 | 0.35357 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 68726.59126 | 68726.59126 | 8.28908 | 8.28908 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 33.53000 | 5.47470E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 38221.54412 | 38221.54412 | 2.03014 | 2.03014 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 62140.58408 | 62140.58408 | 7.49538 | 7.49538 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | 29.60800 | 5.46868E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 38328.44382 | 38328.44382 | 2.03581 | 2.03581 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 10605.70983 | 10605.70983 | 1.27920 | 1.27920 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 27.43733 | 5.46540E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 6651.86290 | 6651.86290 | 0.35331 | 0.35331 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 10375.81521 | 10375.81521 | 1.25147 | 1.25147 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 26.17933 | 5.46350E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 6656.77814 | 6656.77814 | 0.35357 | 0.35357 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 20979.01563 | 20979.01563 | 1.87783 | 1.87783 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 33.90000 | 5.47527E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 10619.55135 | 10619.55135 | 0.56077 | 0.56077 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 3197.52215 | 3197.52215 | 0.38567 | 0.38567 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 32.02533 | 5.47238E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 2064.00223 | 2064.00223 | 0.10963 | 0.10963 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 3117.52143 | 3117.52143 | 0.37602 | 0.37602 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 32.02533 | 5.47238E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 2063.90932 | 2063.90932 | 0.10962 | 0.10962 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 13986.32396 | 13986.32396 | 1.68700 | 1.68700 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 33.53000 | 5.47470E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 9931.84271 | 9931.84271 | 0.52752 | 0.52752 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 29864.79534 | 29864.79534 | 2.67683 | 2.67683 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 33.90000 | 5.47527E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 6971.42437 | 6971.42437 | 0.36813 | 1.18780 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 31288.62138 | 31288.62138 | 2.80440 | 2.80440 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 33.90000 | 5.47527E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
40 | DINING_FLR_6 | Heating | 7121.59542 | 7121.59542 | 0.37605 | 1.18780 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -17.90000 | 9.55238E-004 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 30999.64412 | 30999.64412 | 2.78260 | 2.78260 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 32.56800 | 5.47322E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 2536.59692 | 2536.59692 | 0.13393 | 0.36735 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | -17.90000 | 9.55238E-004 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
43 | CORRIDOR_FLR_6 | Cooling | 10948.70719 | 10948.70719 | 0.98001 | 0.98001 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 33.90000 | 5.47527E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 7382.33085 | 7382.33085 | 0.38982 | 0.38982 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -17.90000 | 9.55238E-004 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | FLR_3_DOAS | Cooling | Sensible | 42510.28 | 22.13328 | 2.05125 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | FLR_3_DOAS | Heating | Sensible | 69708.81 | 6.22647 | 2.05125 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
3 | VAV WITH REHEAT | Cooling | Sensible | 408068.14 | 26.81112 | 26.81112 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | VAV WITH REHEAT | Heating | Sensible | 259836.89 | 7.64594 | 7.64594 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.96188 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.50909 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.43200 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.27953 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 7.48393E-004 |
8 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.79752E-005 |
9 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.27953 |
10 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 5483.86332 |
13 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.79752E-005 |
14 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 114.35652 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.44501 |
16 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11485 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.43200 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.19224 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43200 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.31744E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.37315E-005 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.19224 |
24 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3855.71999 |
27 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.37315E-005 |
28 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 99.91531 |
29 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.27911 |
30 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21204 |
31 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.43200 |
32 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.12058 |
33 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.56544 |
34 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.79682E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.30162E-005 |
37 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.12058 |
38 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1487.82898 |
41 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.30162E-005 |
42 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 34.41407 |
43 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.22044 |
44 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.56775 |
45 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.43200 |
46 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 9.52282E-002 |
47 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.71065E-004 |
50 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.85328E-005 |
51 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 9.52282E-002 |
52 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2118.41198 |
55 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.85328E-005 |
56 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 56.87799 |
57 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.13310 |
58 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.54249 |
59 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.43200 |
60 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 5.75003E-002 |
61 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 7.02319E-004 |
64 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.31002E-005 |
65 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 6.44862E-002 |
66 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1497.43843 |
69 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.31002E-005 |
70 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 40.86765 |
71 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 4.00417 |
72 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 1.48510E-002 |
73 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.43200 |
74 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.72980 |
75 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43200 |
76 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.56548E-002 |
78 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.48426E-005 |
79 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.72980 |
80 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9698.02639 |
83 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.48426E-005 |
84 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 205.52287 |
85 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.87271 |
86 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.68475E-002 |
87 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.43200 |
88 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.80901 |
89 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43200 |
90 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.95787E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.81447E-005 |
93 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.80901 |
94 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11218.54494 |
97 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.81447E-005 |
98 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 265.07331 |
99 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.92766 |
100 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16817 |
101 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.43200 |
102 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.56075 |
103 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.44845 |
104 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
105 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.26560E-003 |
106 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.48597E-004 |
107 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.56075 |
108 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
110 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 28416.19386 |
111 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.48597E-004 |
112 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 646.26302 |
113 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
114 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.45205 |
115 | Fan:OnOff | ROOM_1_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 1.45205 |
116 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.81930E-005 |
117 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.77874E-004 |
118 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.81600 |
119 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
120 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.54220E-003 |
121 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
122 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
123 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.77874E-004 |
124 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.45205 |
125 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 6651.81942 |
126 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.81930E-005 |
127 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 190.05973 |
128 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
129 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.41846 |
130 | Fan:OnOff | ROOM_2_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 1.41846 |
131 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.82360E-005 |
132 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.69224E-004 |
133 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.81599 |
134 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
135 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.54312E-003 |
136 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
137 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
138 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.69224E-004 |
139 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.41846 |
140 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 6656.73464 |
141 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.82360E-005 |
142 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 190.20015 |
143 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83707 |
144 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 8.28908 |
145 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 8.28908 |
146 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 3.34378E-004 |
147 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.13227E-003 |
148 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.81641 |
149 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
150 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.48134E-003 |
151 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
152 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.48134E-003 |
153 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.13227E-003 |
154 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 8.28908 |
155 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 38221.42454 |
156 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.34378E-004 |
157 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1092.07806 |
158 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83730 |
159 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 7.49538 |
160 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 7.49538 |
161 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 3.35313E-004 |
162 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.03913E-003 |
163 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.81541 |
164 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
165 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.70878E-003 |
166 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
167 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
168 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.03913E-003 |
169 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 7.49538 |
170 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 38328.32395 |
171 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.35313E-004 |
172 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1095.13210 |
173 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
174 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.27920 |
175 | Fan:OnOff | ROOM_5_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 1.27920 |
176 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.81930E-005 |
177 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.33367E-004 |
178 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.81599 |
179 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
180 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.54744E-003 |
181 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
182 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
183 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.33367E-004 |
184 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.27920 |
185 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 6651.81942 |
186 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.81930E-005 |
187 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 190.05973 |
188 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
189 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.25147 |
190 | Fan:OnOff | ROOM_6_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 1.25147 |
191 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.82360E-005 |
192 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.26216E-004 |
193 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.81599 |
194 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
195 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.54828E-003 |
196 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
197 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
198 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.26216E-004 |
199 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.25147 |
200 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 6656.73464 |
201 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.82360E-005 |
202 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 190.20015 |
203 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.87783 |
204 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.63206 |
205 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.43200 |
206 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.81122 |
207 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.02788E-004 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.23310E-004 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.81122 |
212 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
213 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
214 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14095.13261 |
215 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.23310E-004 |
216 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 350.47330 |
217 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54338E-002 |
218 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.38567 |
219 | Fan:OnOff | ROOM_1_FLR_6 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 0.38567 |
220 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.80567E-005 |
221 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.00297E-004 |
222 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.81600 |
223 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
224 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.53978E-003 |
225 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
226 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
227 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.00297E-004 |
228 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.38567 |
229 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 2063.98935 |
230 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.80567E-005 |
231 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 58.97205 |
232 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54319E-002 |
233 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.37602 |
234 | Fan:OnOff | ROOM_2_FLR_6 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 0.37602 |
235 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.80559E-005 |
236 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 9.78130E-005 |
237 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.81600 |
238 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
239 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.54071E-003 |
240 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
241 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
242 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 9.78130E-005 |
243 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.37602 |
244 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 2063.89644 |
245 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.80559E-005 |
246 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 58.96940 |
247 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 9.91540E-002 |
248 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.68700 |
249 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 1.68700 |
250 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 8.68877E-005 |
251 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.46035E-004 |
252 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.81566 |
253 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
254 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.60090E-003 |
255 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
256 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
257 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.46035E-004 |
258 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.68700 |
259 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 9931.79376 |
260 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.68877E-005 |
261 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 283.76905 |
262 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.67683 |
263 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.44114E-002 |
264 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.43200 |
265 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.15639 |
266 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43200 |
267 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
268 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.03553E-003 |
269 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.04334E-004 |
270 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.15639 |
271 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
272 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
273 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11926.06892 |
274 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.04334E-004 |
275 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 268.40477 |
276 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.80440 |
277 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.01167E-002 |
278 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.43200 |
279 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.21150 |
280 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43200 |
281 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
282 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.22785E-003 |
283 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.07714E-004 |
284 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.21150 |
285 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
286 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
287 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12312.38489 |
288 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.07714E-004 |
289 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 276.54726 |
290 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.78260 |
291 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 5.08820E-002 |
292 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.43200 |
293 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.20208 |
294 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43200 |
295 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
296 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.34680E-002 |
297 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.71817E-005 |
298 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.20208 |
299 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
300 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
301 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7679.28468 |
302 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.71817E-005 |
303 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 164.32776 |
304 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.98001 |
305 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.32045 |
306 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.43200 |
307 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.42336 |
308 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.85452 |
309 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
310 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.18897E-003 |
311 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.04538E-005 |
312 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.42336 |
313 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
314 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
315 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9196.36098 |
316 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.04538E-005 |
317 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 244.79478 |
318 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05132 |
319 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05132 |
320 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05132 |
321 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05132 |
322 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05132 |
323 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05132 |
324 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
325 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
326 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 13.48287 |
327 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 11.64920 |
328 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 26.96574 |
329 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 11.64920 |
330 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 26.81112 |
331 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 26.81112 |
332 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
333 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.43449 |
334 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05132 |
335 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 26.81112 |
336 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05132 |
337 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05125 |
338 | HeatExchanger:AirToAir:SensibleAndLatent | FLR_3_DOAS OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.05125 |
339 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 33.90000 |
340 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
341 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.72145 |
342 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 5.47527E-003 |
343 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 5.47527E-003 |
344 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Coil Load [W] | 45136.60304 |
345 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.29090E-003 |
346 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 2.05132 |
347 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Rated Capacity [W] | 20913.37763 |
348 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.82959E-004 |
349 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 324.43145 |
350 | Fan:ConstantVolume | FLR_3_DOAS FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05125 |
351 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.29090E-003 |
352 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 3.68882E-004 |
353 | Controller:WaterCoil | FLR_3_DOAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.82959E-004 |
354 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 26.81112 |
355 | HeatExchanger:AirToAir:SensibleAndLatent | VAV WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 11.66146 |
356 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 28.30059 |
357 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
358 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.55124 |
359 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.82538E-003 |
360 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.82538E-003 |
361 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 474160.82913 |
362 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.35609E-002 |
363 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 26.81112 |
364 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 273341.93176 |
365 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.39131E-003 |
366 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 4240.38249 |
367 | Fan:VariableVolume | VAV WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 26.81112 |
368 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.35609E-002 |
369 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 3.51149E-005 |
370 | Controller:WaterCoil | VAV WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.39131E-003 |
371 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 2.10741E-002 |
372 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 3440.75212 |
373 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 4.64076E-003 |
374 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.55689 |
375 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 4.64076E-003 |
376 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 1397.59241 |
377 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
378 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 530467.10552 |
379 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 530467.11000 |
380 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 4.64076E-003 |
381 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 2.10741E-002 |
382 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 2.52889 |
383 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 2.10741E-002 |
384 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 2382.14874 |
385 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 2.10741E-002 |
386 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 736858.95141 |
387 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 737566.70000 |
388 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 84.08260 |
389 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
390 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
391 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
392 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
393 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | 5512.71 |
2 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 3872.91 |
3 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1495.10 |
4 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | 2127.66 |
5 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | 1503.92 |
6 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 9748.56 |
7 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | 11272.74 |
8 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | 28556.40 |
9 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | 7167.29 |
10 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | 7172.59 |
11 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 41183.29 |
12 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 41298.47 |
13 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | 7167.29 |
14 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | 7172.59 |
15 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 14160.30 |
16 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | 2223.90 |
17 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | 2223.80 |
18 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 10701.28 |
19 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | 11985.29 |
20 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | 12373.60 |
21 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | 7719.09 |
22 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 9236.71 |
23 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | 13769.91 |
24 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | 179975.45 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | 15367.32 | 11887.61 | 3479.70 | 0.77 | 1330.35 | 13.49 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | 15015.06 | 11614.53 | 3400.53 | 0.77 | 1299.90 | 13.18 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 92468.85 | 72593.44 | 19875.40 | 0.79 | 8891.94 | 90.19 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 82435.93 | 63194.66 | 19241.27 | 0.77 | 7180.44 | 72.83 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | 13554.79 | 10482.48 | 3072.31 | 0.77 | 1173.67 | 11.90 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | 13263.62 | 10256.83 | 3006.79 | 0.77 | 1148.49 | 11.65 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | 4079.23 | 3155.97 | 923.26 | 0.77 | 353.11 | 3.58 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | 3978.05 | 3077.53 | 900.52 | 0.77 | 344.36 | 3.49 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 18101.50 | 13957.76 | 4143.73 | 0.77 | 1570.45 | 15.93 |
10 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | 44280.81 | 27957.13 | 16323.69 | 0.63 | 4887.02 | 49.57 |
11 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | 485019.81 | 323497.23 | 161522.58 | 0.67 | 47804.04 | 484.86 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 4.09 | 13.95 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.419 | 0.394 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.419 | 0.394 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.721 | 0.651 | 22.63 | 45.89 | 22.63 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 23.26 | 23.26 | 23.26 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.721 | 0.651 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.721 | 0.651 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.721 | 0.651 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.721 | 0.651 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 2.390 | 2.390 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.721 | 0.651 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.721 | 0.651 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.721 | 0.651 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.721 | 0.651 | 63.73 | 129.23 | 63.73 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 65.50 | 65.50 | 65.50 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.721 | 0.651 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.721 | 0.651 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.721 | 0.651 | 82.79 | 167.88 | 82.79 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 85.08 | 85.08 | 85.08 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.721 | 0.651 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.844 | 0.749 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.844 | 0.749 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.844 | 0.749 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.844 | 0.749 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.844 | 0.749 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.844 | 0.749 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.844 | 0.749 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.844 | 0.749 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.844 | 0.749 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.844 | 0.749 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.917 | 0.806 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.917 | 0.806 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.917 | 0.806 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.917 | 0.806 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.857 | 0.759 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.857 | 0.759 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.857 | 0.759 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.857 | 0.759 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.857 | 0.759 | 13.70 | 20.44 | 13.70 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 6.74 | 6.74 | 6.74 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.930 | 0.816 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.930 | 0.816 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.930 | 0.816 | 16.77 | 21.37 | 16.77 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.930 | 0.816 | 34.86 | 52.03 | 34.86 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 17.17 | 17.17 | 17.17 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.930 | 0.816 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.930 | 0.816 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.930 | 0.816 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.930 | 0.816 | 34.86 | 52.03 | 34.86 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 17.17 | 17.17 | 17.17 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 1.1198367466E-002 | 2.0974458292E-002 | Pass | Pass | 1.2292820117E-002 | 2.9555611200E-002 | Pass | Pass |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.7822504192E-002 | 9.6223134156E-002 | Pass | Pass | 3.3059670387E-002 | 3.8323686713E-002 | Pass | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.7018165878E-002 | 2.8966316442E-002 | Pass | Pass | 8.0611653154E-003 | 1.7929643084E-002 | Pass | Pass |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.3629461888E-002 | 1.3908668550E-002 | Pass | Pass | 8.7864273170E-003 | 2.2533731393E-002 | Pass | Pass |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.1912836556E-002 | 1.0075997020E-002 | Pass | Pass | 9.4079093634E-003 | 2.3336669447E-002 | Pass | Pass |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 3.1727540708E-002 | 0.1052566263 | Pass | Pass | 1.9950058832E-002 | 5.5199677199E-002 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.0927511875E-002 | 7.5112649089E-002 | Pass | Pass | 1.8443616217E-002 | 2.7090468523E-002 | Pass | Pass |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.1702204165E-002 | 3.8419125995E-002 | Pass | Pass | 1.1738974991E-002 | 2.1918050386E-002 | Pass | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.9602382171E-002 | 0.1899767942 | Pass | Pass | 0.1577135309 | 0.3627889568 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 7.4379658313E-002 | 0.1962445210 | Pass | Pass | 0.2297080150 | 0.9719903887 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 1.2662313229E-002 | 3.0251506731E-002 | Pass | Pass | 0.1085152145 | 0.4175073703 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 2.2701697360E-002 | 7.4214760710E-002 | Pass | Pass | 0.4663241311 | 2.6850246143 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 6.5108663316E-002 | 0.2594454965 | Pass | Pass | 0.3291206315 | 1.6415252216 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 6.1691872442E-002 | 0.1927587469 | Pass | Pass | 0.1139289893 | 0.3634701479 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 1.5176132766E-002 | 1.4360497046E-002 | Pass | Pass | 8.8938385681E-003 | 2.0936775525E-002 | Pass | Pass |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 4.3465169872E-002 | 0.1693995009 | Pass | Pass | 0.1529402447 | 0.6104678415 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.6686599033E-002 | 0.2575513102 | Pass | Pass | 0.1686312346 | 0.8831992029 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.5277555341E-002 | 0.2436970760 | Pass | Pass | 0.5477284927 | 4.6645780206 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 2.0837789137E-002 | 5.2426776272E-002 | Pass | Pass | 1.7315948230E-002 | 4.8253618035E-002 | Pass | Pass |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 1.2985675473E-002 | 3.8875688024E-002 | Pass | Pass | 1.6346018012E-002 | 4.5325270602E-002 | Pass | Pass |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 1.4024105515E-002 | 4.4108163028E-002 | Pass | Pass | 2.2109479079E-002 | 4.3499149486E-002 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 2.1189321791E-002 | 2.5074265556E-002 | Pass | Pass | 2.3192061144E-002 | 3.0725980029E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:04
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 4756.71 | 63.84 | 1646.21 | 8144.06 | 3599.92 | 18210.75 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:04
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | -17.90 | 0.00 | -17.90 | Wetbulb [C] | 2.50 | 180.00 |
DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 33.90 | 14.80 | 15.00 | Wetbulb [C] | 3.60 | 30.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 11.00 | 10 | |||
Feb | 15.00 | 16 | |||
Mar | 88.00 | 32 | |||
Apr | 159.00 | 54 | |||
May | 30.00 | 24 | |||
Jun | 11.00 | 4 | |||
Jul | 167.00 | 26 | |||
Aug | 33.00 | 24 | |||
Sep | 8.00 | 8 | |||
Oct | 13.00 | 10 | |||
Nov | 12.00 | 22 | |||
Dec | 11.00 | 18 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:04
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 211.13 | 211.13 | 0.00 | 90.00 | N |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.399 | 0.419 | 55.76 | 55.76 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 211.13 | 211.13 | 180.00 | 90.00 | S |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.399 | 0.419 | 55.76 | 55.76 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.651 | 0.721 | 45.89 | 22.63 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.651 | 0.721 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.651 | 0.721 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.651 | 0.721 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.651 | 0.721 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.651 | 0.721 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.651 | 0.721 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.651 | 0.721 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.651 | 0.721 | 129.23 | 63.73 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.651 | 0.721 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.651 | 0.721 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.651 | 0.721 | 167.88 | 82.79 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.651 | 0.721 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.749 | 0.844 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.749 | 0.844 | 104.06 | 69.72 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.749 | 0.844 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.749 | 0.844 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.749 | 0.844 | 847.14 | 567.58 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.749 | 0.844 | 847.37 | 567.71 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.749 | 0.844 | 104.06 | 69.72 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.749 | 0.844 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.749 | 0.844 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.749 | 0.844 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.917 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.917 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.917 | 26.02 | 17.43 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.917 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.759 | 0.857 | 13.94 | 9.34 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.759 | 0.857 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | RES_ROOF | 0.23 | 0.182 | 0.186 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | RES_EXT_WALL_TOP | 0.30 | 0.759 | 0.857 | 13.94 | 9.34 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.759 | 0.857 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | RES_ROOF | 0.23 | 0.182 | 0.186 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.759 | 0.857 | 183.96 | 123.26 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | RES_ROOF | 0.23 | 0.182 | 0.186 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.816 | 0.930 | 97.55 | 65.36 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.816 | 0.930 | 97.55 | 65.36 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.816 | 0.930 | 21.37 | 16.77 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.816 | 0.930 | 52.03 | 34.86 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.816 | 0.930 | 13.94 | 9.34 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.816 | 0.930 | 17.65 | 11.83 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.816 | 0.930 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.816 | 0.930 | 52.03 | 34.86 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 167.42 | 167.42 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_FLOOR | BASEMENT_FLOOR | 0.30 | 1.441 | 2.705 | 1978.83 | 1978.83 | 0.00 | 180.00 | |
BASEMENT_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 67.07 | 67.07 | 180.00 | 0.00 | |
BASEMENT_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 77.67 | 77.67 | 180.00 | 0.00 | |
BASEMENT_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 164.24 | 164.24 | 180.00 | 0.00 | |
BASEMENT_CEILING_4 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 94.76 | 94.76 | 180.00 | 0.00 | |
BASEMENT_CEILING_5 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 78.04 | 78.04 | 180.00 | 0.00 | |
BASEMENT_CEILING_6 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 188.86 | 188.86 | 180.00 | 0.00 | |
BASEMENT_CEILING_7 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 1088.56 | 1088.56 | 180.00 | 0.00 | |
BASEMENT_CEILING_8 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 219.63 | 219.63 | 90.00 | 0.00 | |
RETAIL_1_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_1_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
RETAIL_1_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 67.07 | 67.07 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
RETAIL_2_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_2_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 90.00 | 90.00 | E |
RETAIL_2_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 77.67 | 77.67 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 77.67 | 77.67 | 180.00 | 0.00 | |
MECH_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
MECH_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 180.00 | 90.00 | S |
MECH_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
MECH_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 164.24 | 164.24 | 0.00 | 180.00 | |
MECH_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 164.24 | 164.24 | 180.00 | 0.00 | |
STORAGE_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
STORAGE_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 180.00 | 90.00 | S |
STORAGE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
STORAGE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 94.76 | 94.76 | 0.00 | 180.00 | |
STORAGE_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 94.76 | 94.76 | 180.00 | 0.00 | |
LAUNDRY_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 180.00 | 90.00 | S |
LAUNDRY_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 270.00 | 90.00 | W |
LAUNDRY_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 78.04 | 78.04 | 0.00 | 180.00 | |
LAUNDRY_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 78.04 | 78.04 | 180.00 | 0.00 | |
CAFE_FLR_1_WALL_1_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_2_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
CAFE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 188.86 | 188.86 | 0.00 | 180.00 | |
LOBBY_FLR_1_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 90.00 | 90.00 | E |
LOBBY_FLR_1_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 1088.56 | 1088.56 | 180.00 | 180.00 | |
LOBBY_FLR_1_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 219.63 | 219.63 | 90.00 | 180.00 | |
LOBBY_FLR_1_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 1062.83 | 1062.83 | 270.00 | 0.00 | |
ROOM_1_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_1_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
ROOM_1_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_1_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_2_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
ROOM_2_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_2_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_2_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 156.07 | 156.07 | 180.00 | 0.00 | |
ROOM_3_MULT19_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.14 | 847.14 | 0.00 | 90.00 | N |
ROOM_3_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_3_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 1863.81 | 1863.81 | 0.00 | 180.00 | |
ROOM_3_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 1863.81 | 1863.81 | 180.00 | 0.00 | |
ROOM_4_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_4_MULT19_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.37 | 847.37 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_4_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 1864.32 | 1864.32 | 0.00 | 180.00 | |
ROOM_4_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 1864.32 | 1864.32 | 180.00 | 0.00 | |
ROOM_5_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
ROOM_5_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_5_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_6_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
ROOM_6_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_6_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 156.07 | 156.07 | 180.00 | 0.00 | |
CORRIDOR_FLR_3_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.28 | 847.28 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_4_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.27 | 847.27 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 297.29 | 297.29 | 180.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 963.06 | 963.06 | 270.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_3 | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 297.26 | 297.26 | 90.00 | 180.00 | |
CORRIDOR_FLR_3_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 297.29 | 297.29 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 963.06 | 963.06 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 297.26 | 297.26 | 90.00 | 0.00 | |
ROOM_1_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 0.00 | 90.00 | N |
ROOM_1_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_1_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_2_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_2_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 180.00 | 90.00 | S |
ROOM_2_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_3_MULT9_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.96 | 183.96 | 0.00 | 90.00 | N |
ROOM_3_MULT9_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 90.00 | 90.00 | E |
ROOM_3_MULT9_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 270.00 | 90.00 | W |
ROOM_3_MULT9_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 220.77 | 220.77 | 0.00 | 180.00 | |
BANQUET_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
BANQUET_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
BANQUET_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
BANQUET_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 331.66 | 331.66 | 0.00 | 180.00 | |
DINING_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
DINING_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
DINING_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
DINING_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 331.66 | 331.66 | 0.00 | 180.00 | |
KITCHEN_FLR_6_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 7.43 | 7.43 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 103.30 | 103.30 | 180.00 | 180.00 | |
CORRIDOR_FLR_6_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 104.98 | 104.98 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_1_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.95 | 183.95 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 11.15 | 11.15 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 40.88 | 40.88 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 412.12 | 412.12 | 180.00 | 180.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3957.66 | 0.00 | 90.00 | N | ||
RETAIL_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 134.14 | 0.00 | 90.00 | N | ||
RETAIL_2_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 155.34 | 0.00 | 90.00 | N | ||
MECH_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 328.49 | 0.00 | 90.00 | N | ||
STORAGE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 189.52 | 0.00 | 90.00 | N | ||
LAUNDRY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 156.08 | 0.00 | 90.00 | N | ||
CAFE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 377.72 | 0.00 | 90.00 | N | ||
LOBBY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 2616.37 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3727.63 | 0.00 | 90.00 | N | ||
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3728.64 | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3115.24 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.04 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.03 | 0.00 | 90.00 | N | ||
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 441.55 | 0.00 | 90.00 | N | ||
BANQUET_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
DINING_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 206.61 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 824.25 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.38 | 23.26 | 0.00 | 0.00 | 23.26 | 23.26 | 2.159 | 0.381 | 0.420 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.38 | 65.50 | 0.00 | 0.00 | 65.50 | 65.50 | 2.159 | 0.381 | 0.420 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.38 | 85.08 | 0.00 | 0.00 | 85.08 | 85.08 | 2.159 | 0.381 | 0.420 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.38_SHGC_0.38 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.159 | 0.381 | 0.420 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.38_SHGC_0.38 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.159 | 0.381 | 0.420 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.38_SHGC_0.38 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.159 | 0.381 | 0.420 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.38_SHGC_0.38 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.159 | 0.381 | 0.420 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.38_SHGC_0.38 | 3.68 | 0.00 | 0.00 | 3.68 | 279.56 | 2.159 | 0.381 | 0.420 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.38_SHGC_0.38 | 3.68 | 0.00 | 0.00 | 3.68 | 279.65 | 2.159 | 0.381 | 0.420 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.38_SHGC_0.38 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.159 | 0.381 | 0.420 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.38_SHGC_0.38 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.159 | 0.381 | 0.420 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.38_SHGC_0.38 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.159 | 0.381 | 0.420 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.38_SHGC_0.38 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.159 | 0.381 | 0.420 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.38 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.159 | 0.381 | 0.420 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.38 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 2.159 | 0.381 | 0.420 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.38 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 2.159 | 0.381 | 0.420 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.38 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.159 | 0.381 | 0.420 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.38_SHGC_0.38 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.159 | 0.381 | 0.420 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.38_SHGC_0.38 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.159 | 0.381 | 0.420 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.38_SHGC_0.38 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.159 | 0.381 | 0.420 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.38_SHGC_0.38 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.159 | 0.381 | 0.420 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.38_SHGC_0.38 | 6.74 | 0.00 | 0.00 | 6.74 | 60.70 | 2.159 | 0.381 | 0.420 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.38 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.159 | 0.381 | 0.420 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.38 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.159 | 0.381 | 0.420 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.38 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.159 | 0.381 | 0.420 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.38 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.159 | 0.381 | 0.420 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | |||||||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.38 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.159 | 0.381 | 0.420 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.38 | 5.82 | 0.00 | 0.00 | 5.82 | 5.82 | 2.159 | 0.381 | 0.420 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.38 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 2.159 | 0.381 | 0.420 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.38 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.159 | 0.381 | 0.420 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 1213.79 | 2.159 | 0.381 | 0.420 | |||||||||||||||||
North Total or Average | 432.95 | 2.159 | 0.381 | 0.420 | |||||||||||||||||
Non-North Total or Average | 780.84 | 2.159 | 0.381 | 0.420 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 1.760 | 2.390 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:04
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:04
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 8.8143 | 1978.83 | 17441.96 | LightsWired | LTG_SCH_BASEMENT | 49.32 | 168.00 | 49.26 | 0.0000 | Y | 161.29 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | RETAIL_1_FLR_1 | GENERAL | 11.3140 | 67.07 | 758.85 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 7.31 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | RETAIL_2_FLR_1 | GENERAL | 11.3140 | 77.67 | 878.75 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 8.46 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | MECH_FLR_1 | GENERAL | 4.6285 | 164.24 | 760.20 | LightsWired | LTG_SCH_MECHANIC | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 8.37 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | STORAGE_FLR_1 | GENERAL | 5.7199 | 94.76 | 542.02 | LightsWired | LTG_SCH_STORAGE | 30.30 | 168.00 | 30.27 | 0.0000 | Y | 3.08 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | LAUNDRY_FLR_1 | GENERAL | 4.6285 | 78.04 | 361.20 | LightsWired | LTG_SCH_LAUNDRY | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 3.98 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | CAFE_FLR_1 | GENERAL | 10.0104 | 188.86 | 1890.59 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 39.52 | 0.0000 | Y | 14.03 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | LOBBY_FLR_1 | GENERAL | 10.7639 | 1308.19 | 14081.18 | LightsWired | LTG_SCH_LOBBY | 44.02 | 168.00 | 41.54 | 0.0000 | Y | 109.80 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | ROOM_1_FLR_3 | GENERAL | 8.2882 | 156.09 | 1293.69 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | ROOM_2_FLR_3 | GENERAL | 8.2882 | 156.07 | 1293.54 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | GENERAL | 8.2882 | 1863.81 | 15447.65 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 110.38 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | GENERAL | 8.2882 | 1864.32 | 15451.87 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 110.41 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | ROOM_5_FLR_3 | GENERAL | 8.2882 | 156.09 | 1293.69 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | ROOM_6_FLR_3 | GENERAL | 8.2882 | 156.07 | 1293.54 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | CORRIDOR_FLR_3 | GENERAL | 7.1042 | 1557.62 | 11065.59 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 91.33 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | ROOM_1_FLR_6 | GENERAL | 8.2882 | 39.02 | 323.42 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 2.31 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | ROOM_2_FLR_6 | GENERAL | 8.2882 | 39.02 | 323.38 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 2.31 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | GENERAL | 8.2882 | 220.77 | 1829.83 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 13.08 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | BANQUET_FLR_6 | GENERAL | 10.0104 | 331.66 | 3320.03 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 49.34 | 0.0000 | Y | 30.75 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | DINING_FLR_6 | GENERAL | 10.0104 | 331.66 | 3320.03 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 49.34 | 0.0000 | Y | 30.75 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | KITCHEN_FLR_6 | GENERAL | 11.4097 | 103.30 | 1178.68 | LightsWired | LTG_SCH_KITCHEN | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 12.97 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | CORRIDOR_FLR_6 | GENERAL | 7.1042 | 412.12 | 2927.80 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 24.17 |
Interior Lighting Total | 8.5566 | 11345.29 | 97077.49 | 456.00 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
LOBBY_FLR_1_DAYLREFPT1 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.07 | 14081.18 | 985.68 |
LOBBY_FLR_1_DAYLREFPT2 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.07 | 14081.18 | 985.68 |
CAFE_FLR_1_DAYLREFPT1 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1890.59 | 737.33 |
CAFE_FLR_1_DAYLREFPT2 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1890.59 | 737.33 |
DINING_FLR_6_DAYLREFPT1 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
DINING_FLR_6_DAYLREFPT2 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
BANQUET_FLR_6_DAYLREFPT1 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
BANQUET_FLR_6_DAYLREFPT2 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 12338.45 | AstronomicalClock | - | 83.67 | 83.67 | 193.79 | |
Exterior Lighting Total | 12338.45 | 193.79 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:04
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 530467.11 | 0.80 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 737566.70 | 2.96 | 737566.70 | 2.96 | 4.09 | 13.95 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 13212.68 | 15367.32 | 11887.61 | 3479.70 | 0.77 | - | 1330.35 | 13.49 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 12910.24 | 15015.06 | 11614.53 | 3400.53 | 0.77 | - | 1299.90 | 13.18 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 74556.75 | 92468.85 | 72593.44 | 19875.40 | 0.79 | - | 8891.94 | 90.19 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 71299.96 | 82435.93 | 63194.66 | 19241.27 | 0.77 | - | 7180.44 | 72.83 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 11656.46 | 13554.79 | 10482.48 | 3072.31 | 0.77 | - | 1173.67 | 11.90 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 11406.41 | 13263.62 | 10256.83 | 3006.79 | 0.77 | - | 1148.49 | 11.65 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3506.98 | 4079.23 | 3155.97 | 923.26 | 0.77 | - | 353.11 | 3.58 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3420.11 | 3978.05 | 3077.53 | 900.52 | 0.77 | - | 344.36 | 3.49 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 15595.99 | 18101.50 | 13957.76 | 4143.73 | 0.77 | - | 1570.45 | 15.93 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | 45136.60 | 44280.81 | 27957.13 | 16323.69 | 0.63 | - | 4887.02 | 49.57 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | 474160.83 | 485019.81 | 323497.23 | 161522.58 | 0.67 | - | 47804.04 | 484.86 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 5483.86 | 5512.71 | - |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 3855.72 | 3872.91 | - |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1487.83 | 1495.10 | - |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2118.41 | 2127.66 | - |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1497.44 | 1503.92 | - |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 9698.03 | 9748.56 | - |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 11218.54 | 11272.74 | - |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 28416.19 | 28556.40 | - |
ROOM_1_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 6651.82 | 7167.29 | - |
ROOM_2_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 6656.73 | 7172.59 | - |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 38221.42 | 41183.29 | - |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 38328.32 | 41298.47 | - |
ROOM_5_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 6651.82 | 7167.29 | - |
ROOM_6_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 6656.73 | 7172.59 | - |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 14095.13 | 14160.30 | - |
ROOM_1_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 2063.99 | 2223.90 | - |
ROOM_2_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 2063.90 | 2223.80 | - |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 9931.79 | 10701.28 | - |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 11926.07 | 11985.29 | - |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 12312.38 | 12373.60 | - |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 7679.28 | 7719.09 | - |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 9196.36 | 9236.71 | - |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | 20913.38 | 13769.91 | - |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | 273341.93 | 179975.45 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 0.24 | 76.61 | 324.68 | 1.00 | 2.78 | General | ||
LOBBY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.24 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
ROOM_1_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 1.45 | 1021.72 | 703.64 | 1.00 | 1.12 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 |
ROOM_2_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 1.42 | 998.08 | 703.64 | 1.00 | 1.12 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 8.29 | 5832.50 | 703.64 | 1.00 | 0.94 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 |
ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 7.50 | 5274.02 | 703.64 | 1.00 | 0.95 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 |
ROOM_5_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 1.28 | 900.09 | 703.64 | 1.00 | 1.14 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 |
ROOM_6_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 1.25 | 880.58 | 703.64 | 1.00 | 1.15 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 |
ROOM_1_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 0.39 | 271.37 | 703.64 | 1.00 | 1.56 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 |
ROOM_2_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 0.38 | 264.58 | 703.64 | 1.00 | 1.57 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 |
ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 1.69 | 1187.04 | 703.64 | 1.00 | 1.09 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 |
BANQUET_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
DINING_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 1.89 | 612.92 | 324.68 | 1.00 | 1.48 | General | ||
FLR_3_DOAS FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.93 | 1070.05 | 1.00 | 1.30 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
VAV WITH REHEAT FAN | Fan:VariableVolume | 0.62 | 1389.42 | 26.81 | 60074.02 | 2240.64 | 1.00 | 1.11 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.021074 | 3440.75 | 163269.44 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.004641 | 1397.59 | 301156.09 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.021074 | 2382.15 | 113036.94 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH LAUNDRY G WATER HEATER | WaterHeater:Mixed | 1.14 | 163316.00 | 0.80 | 11.51 | 0.44 |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.22 | 1.12 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.60 | 0.80 | 5.78 | 0.37 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:04
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 33089.00 | 33089.00 | 16.72 | 2.962 | 2.962 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:40:00 | 24.00 | 24.00 | 0.00923 | 27.04 | 0.00546 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 4971.07 | 4971.07 | 74.12 | 0.445 | 0.445 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 24.00 | 0.00896 | 33.41 | 0.00547 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 3117.78 | 3117.78 | 40.14 | 0.279 | 0.279 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | 24.00 | 24.00 | 0.00939 | 33.01 | 0.00547 | 0.092 | 0.00 |
MECH_FLR_1 | 2462.93 | 2462.93 | 15.00 | 0.220 | 0.220 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 24.00 | 24.00 | 0.00869 | 29.24 | 0.00547 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1487.14 | 1487.14 | 15.69 | 0.133 | 0.133 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 24.00 | 24.00 | 0.00876 | 30.35 | 0.00547 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 44734.43 | 44734.43 | 573.23 | 4.004 | 4.004 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00854 | 33.90 | 0.00548 | 0.000 | 0.00 |
CAFE_FLR_1 | 20900.29 | 20900.29 | 110.66 | 1.873 | 1.873 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 23.99 | 0.01002 | 33.41 | 0.00547 | 0.676 | 0.00 |
LOBBY_FLR_1 | 66193.15 | 66193.15 | 50.60 | 5.928 | 5.928 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 23.99 | 0.00992 | 33.53 | 0.00547 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 12038.83 | 12038.83 | 308.51 | 1.452 | 1.452 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 21.11 | 21.11 | 0.00854 | 32.03 | 0.00547 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 11760.29 | 11760.29 | 301.41 | 1.418 | 1.418 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 21.11 | 21.11 | 0.00854 | 31.83 | 0.00547 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 68726.59 | 68726.59 | 2802.44 | 8.289 | 8.289 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 21.11 | 21.11 | 0.00848 | 33.53 | 0.00547 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 62140.58 | 62140.58 | 2533.19 | 7.495 | 7.495 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | 21.11 | 21.11 | 0.00871 | 29.61 | 0.00547 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 10605.71 | 10605.71 | 271.79 | 1.279 | 1.279 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 21.11 | 21.11 | 0.00855 | 27.44 | 0.00547 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 10375.82 | 10375.82 | 265.93 | 1.251 | 1.251 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 21.11 | 21.11 | 0.00855 | 26.18 | 0.00546 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 20979.02 | 20979.02 | 53.87 | 1.878 | 1.878 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00938 | 33.90 | 0.00548 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 3197.52 | 3197.52 | 81.94 | 0.386 | 0.386 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 21.11 | 21.11 | 0.00854 | 32.03 | 0.00547 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 3117.52 | 3117.52 | 79.90 | 0.376 | 0.376 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 21.11 | 21.11 | 0.00854 | 32.03 | 0.00547 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 13986.32 | 13986.32 | 570.16 | 1.687 | 1.687 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 21.11 | 21.11 | 0.00860 | 33.53 | 0.00547 | 0.099 | 0.00 |
BANQUET_FLR_6 | 29864.80 | 29864.80 | 90.05 | 2.677 | 2.677 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 23.98 | 0.01038 | 33.90 | 0.00548 | 1.188 | 0.00 |
DINING_FLR_6 | 31288.62 | 31288.62 | 94.34 | 2.804 | 2.804 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 23.98 | 0.01029 | 33.90 | 0.00548 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 30999.64 | 30999.64 | 300.08 | 2.783 | 2.783 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 24.00 | 23.97 | 0.01007 | 32.57 | 0.00547 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 10948.71 | 10948.71 | 26.57 | 0.980 | 0.980 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 24.00 | 0.00894 | 33.90 | 0.00548 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 0.854 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 22.36 | 0.00096 | -17.90 | 0.00096 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 3032.21 | 3032.21 | 45.21 | 0.160 | 0.160 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00778 | -17.90 | 0.00096 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 971.32 | 971.32 | 12.51 | 0.051 | 0.092 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00774 | -17.90 | 0.00096 | 0.092 | 0.00 |
MECH_FLR_1 | 1710.56 | 1710.56 | 10.41 | 0.090 | 0.090 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00766 | -17.90 | 0.00096 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1221.22 | 1221.22 | 12.89 | 0.064 | 0.064 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00772 | -17.90 | 0.00096 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 2290.05 | 2290.05 | 29.34 | 0.121 | 0.121 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00765 | -17.90 | 0.00096 | 0.000 | 0.00 |
CAFE_FLR_1 | 7752.79 | 7752.79 | 41.05 | 0.409 | 0.676 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00781 | -17.90 | 0.00096 | 0.676 | 0.00 |
LOBBY_FLR_1 | 17446.48 | 17446.48 | 13.34 | 0.921 | 1.894 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00776 | -17.90 | 0.00096 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 6651.86 | 6651.86 | 170.46 | 0.353 | 0.353 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00777 | -17.90 | 0.00096 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 6656.78 | 6656.78 | 170.61 | 0.354 | 0.354 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00777 | -17.90 | 0.00096 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 38221.54 | 38221.54 | 1558.55 | 2.030 | 2.030 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00779 | -17.90 | 0.00096 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 38328.44 | 38328.44 | 1562.48 | 2.036 | 2.036 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00779 | -17.90 | 0.00096 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 6651.86 | 6651.86 | 170.46 | 0.353 | 0.353 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00777 | -17.90 | 0.00096 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 6656.78 | 6656.78 | 170.61 | 0.354 | 0.354 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00777 | -17.90 | 0.00096 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 10619.55 | 10619.55 | 27.27 | 0.561 | 0.561 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00783 | -17.90 | 0.00096 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 2064.00 | 2064.00 | 52.89 | 0.110 | 0.110 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00782 | -17.90 | 0.00096 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2063.91 | 2063.91 | 52.90 | 0.110 | 0.110 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00782 | -17.90 | 0.00096 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 9931.84 | 9931.84 | 404.88 | 0.528 | 0.528 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00782 | -17.90 | 0.00096 | 0.099 | 0.00 |
BANQUET_FLR_6 | 6971.42 | 6971.42 | 21.02 | 0.368 | 1.188 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00787 | -17.90 | 0.00096 | 1.188 | 0.00 |
DINING_FLR_6 | 7121.60 | 7121.60 | 21.47 | 0.376 | 1.188 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00787 | -17.90 | 0.00096 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 2536.60 | 2536.60 | 24.55 | 0.134 | 0.367 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 21.00 | 21.00 | 0.00728 | -17.90 | 0.00096 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 7382.33 | 7382.33 | 17.91 | 0.390 | 0.390 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00789 | -17.90 | 0.00096 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
FLR_3_DOAS | 22.13 | 2.05 | 6.23 | 2.05 | 2.0513 | 2.0513 | 2.0513 | 1.0000 | 0.3000 |
VAV WITH REHEAT | 26.81 | 26.81 | 7.65 | 7.65 | 26.8111 | 11.6492 | 26.8111 | 0.4345 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 5483.863 | 5483.863 | 1.279534 | 0.00004798 | 114.357 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 5483.86 | 5483.86 | 1.279534 | 16.70 | 11.24 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00800000 | 41.9796 | 0.00 | 0.00 | 5514.68 | 5514.68 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 3855.720 | 3855.720 | 0.192244 | 0.00003373 | 99.915 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3855.72 | 3855.72 | 0.192244 | 16.70 | 11.24 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00778426 | 40.8628 | 3032.21 | 0.00 | 3875.15 | 3875.15 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 1487.829 | 1487.829 | 0.120577 | 0.00001302 | 34.414 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1487.83 | 1487.83 | 0.120577 | 16.70 | 11.24 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00774162 | 40.6409 | 971.32 | 0.00 | 1495.79 | 1495.79 |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 2118.412 | 2118.412 | 0.095228 | 0.00001853 | 56.878 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 2118.41 | 2118.41 | 0.095228 | 16.70 | 11.24 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00765751 | 40.2048 | 1710.56 | 0.00 | 2128.96 | 2128.96 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 1497.438 | 1497.438 | 0.064486 | 0.00001310 | 40.868 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1497.44 | 1497.44 | 0.064486 | 16.70 | 11.24 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00772064 | 40.5322 | 1221.22 | 0.00 | 1504.86 | 1504.86 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 9698.026 | 9698.026 | 1.729802 | 0.00008484 | 205.523 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 9698.03 | 9698.03 | 1.729802 | 16.70 | 11.24 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00765109 | 40.1724 | 2290.05 | 0.00 | 9752.23 | 9752.23 |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 11218.545 | 11218.545 | 0.809009 | 0.00009814 | 265.073 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 11218.54 | 11218.54 | 0.809009 | 16.70 | 11.24 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00781270 | 41.0100 | 7752.79 | 0.00 | 11278.23 | 11278.23 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 28416.194 | 28416.194 | 2.560748 | 0.00024860 | 646.263 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 28416.19 | 28416.19 | 2.560748 | 16.70 | 11.24 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00776385 | 40.7562 | 17446.48 | 0.00 | 28569.20 | 28569.20 |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 13212.683 | -999.000 | 1.452055 | 0.00037787 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | 7/21 16:50:00 | 13212.68 | 13109.36 | 1.452055 | 21.82 | 13.55 | 0.00854220 | 12.80 | 10.21 | 0.00850000 | 32.03 | 0.00547238 | 14.46 | 0.0000 | 21.11 | 0.00854220 | 44.4826 | 12038.83 | 0.00 | 9941.95 | 9941.95 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 6651.819 | 6651.819 | 0.353306 | 0.00005819 | 190.060 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 6651.82 | 6651.82 | 0.353306 | 21.11 | 12.65 | 0.00777336 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.11 | 0.00777336 | 40.5292 | 6651.86 | 0.00 | 7170.83 | 7170.83 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 12910.239 | -999.000 | 1.418460 | 0.00036922 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | 7/21 17:00:00 | 12910.24 | 12807.10 | 1.418460 | 21.82 | 13.55 | 0.00854312 | 12.80 | 10.21 | 0.00850000 | 31.83 | 0.00547208 | 14.39 | 0.0000 | 21.11 | 0.00854312 | 44.4873 | 11760.29 | 0.00 | 9714.86 | 9714.86 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 6656.735 | 6656.735 | 0.353567 | 0.00005824 | 190.200 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 6656.73 | 6656.73 | 0.353567 | 21.11 | 12.65 | 0.00777354 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.11 | 0.00777354 | 40.5301 | 6656.78 | 0.00 | 7176.13 | 7176.13 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 74556.746 | -999.000 | 8.289077 | 0.00213227 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | unknown | 7/21 13:30:00 | 74556.75 | 74556.74 | 8.289077 | 21.82 | 13.49 | 0.00848134 | 12.80 | 10.20 | 0.00848134 | 33.53 | 0.00547470 | 14.95 | 0.0000 | 21.11 | 0.00848134 | 44.1690 | 68726.59 | 0.00 | 59838.74 | 59838.74 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 38221.425 | 38221.425 | 2.030136 | 0.00033438 | 1092.078 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 38221.42 | 38221.42 | 2.030136 | 21.11 | 12.66 | 0.00779038 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.11 | 0.00779038 | 40.6161 | 38221.54 | 0.00 | 41203.89 | 41203.89 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 71299.957 | -999.000 | 7.495381 | 0.00203913 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | unknown | 7/21 18:20:00 | 71299.96 | 68623.91 | 7.495381 | 21.82 | 13.68 | 0.00870878 | 12.80 | 10.21 | 0.00850000 | 29.61 | 0.00546868 | 13.64 | 0.0000 | 21.11 | 0.00870878 | 45.3391 | 62140.58 | 0.00 | 54133.45 | 53189.31 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 38328.324 | 38328.324 | 2.035814 | 0.00033531 | 1095.132 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 38328.32 | 38328.32 | 2.035814 | 21.11 | 12.66 | 0.00779090 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.11 | 0.00779090 | 40.6187 | 38328.44 | 0.00 | 41319.13 | 41319.13 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 11656.461 | -999.000 | 1.279200 | 0.00033337 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | unknown | 7/21 09:40:00 | 11656.46 | 11554.10 | 1.279200 | 21.82 | 13.55 | 0.00854744 | 12.80 | 10.21 | 0.00850000 | 27.44 | 0.00546540 | 12.88 | 0.0000 | 21.11 | 0.00854744 | 44.5095 | 10605.71 | 0.00 | 8773.47 | 8773.47 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 6651.819 | 6651.819 | 0.353306 | 0.00005819 | 190.060 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 6651.82 | 6651.82 | 0.353306 | 21.11 | 12.65 | 0.00777336 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.11 | 0.00777336 | 40.5292 | 6651.86 | 0.00 | 7170.83 | 7170.83 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 11406.414 | -999.000 | 1.251472 | 0.00032622 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | unknown | 7/21 09:10:00 | 11406.41 | 11304.48 | 1.251472 | 21.82 | 13.55 | 0.00854828 | 12.80 | 10.21 | 0.00850000 | 26.18 | 0.00546350 | 12.44 | 0.0000 | 21.11 | 0.00854828 | 44.5138 | 10375.82 | 0.00 | 8585.67 | 8585.67 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 6656.735 | 6656.735 | 0.353567 | 0.00005824 | 190.200 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 6656.73 | 6656.73 | 0.353567 | 21.11 | 12.65 | 0.00777354 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.11 | 0.00777354 | 40.5301 | 6656.78 | 0.00 | 7176.13 | 7176.13 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 14095.133 | 14095.133 | 0.811221 | 0.00012331 | 350.473 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 14095.13 | 14095.13 | 0.811221 | 16.70 | 11.24 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00782597 | 41.0780 | 10619.55 | 0.00 | 14167.91 | 14167.91 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 3506.981 | -999.000 | 0.385667 | 0.00010030 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | 7/21 16:50:00 | 3506.98 | 3481.12 | 0.385667 | 21.82 | 13.54 | 0.00853978 | 12.80 | 10.21 | 0.00850000 | 32.03 | 0.00547238 | 14.46 | 0.0000 | 21.11 | 0.00853978 | 44.4701 | 3197.52 | 0.00 | 2638.50 | 2638.50 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 2063.989 | 2063.989 | 0.109627 | 0.00001806 | 58.972 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 2063.99 | 2063.99 | 0.109627 | 21.11 | 12.68 | 0.00781621 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.11 | 0.00781621 | 40.7498 | 2064.00 | 0.00 | 2225.03 | 2225.03 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 3420.113 | -999.000 | 0.376018 | 0.00009781 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | 7/21 16:50:00 | 3420.11 | 3394.30 | 0.376018 | 21.82 | 13.54 | 0.00854071 | 12.80 | 10.21 | 0.00850000 | 32.03 | 0.00547238 | 14.46 | 0.0000 | 21.11 | 0.00854071 | 44.4750 | 3117.52 | 0.00 | 2573.27 | 2573.27 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 2063.896 | 2063.896 | 0.109622 | 0.00001806 | 58.969 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 2063.90 | 2063.90 | 0.109622 | 21.11 | 12.68 | 0.00781622 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.11 | 0.00781622 | 40.7498 | 2063.91 | 0.00 | 2224.93 | 2224.93 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 15595.987 | -999.000 | 1.687004 | 0.00044603 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | unknown | 7/21 13:30:00 | 15595.99 | 15307.51 | 1.687004 | 21.82 | 13.59 | 0.00860090 | 12.80 | 10.21 | 0.00850000 | 33.53 | 0.00547470 | 14.95 | 0.0000 | 21.11 | 0.00860090 | 44.7848 | 13986.32 | 0.00 | 11772.84 | 11772.84 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 9931.794 | 9931.794 | 0.527523 | 0.00008689 | 283.769 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 9931.79 | 9931.79 | 0.527523 | 21.11 | 12.69 | 0.00782393 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.11 | 0.00782393 | 40.7892 | 9931.84 | 0.00 | 10706.75 | 10706.75 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 11926.069 | 11926.069 | 1.156390 | 0.00010433 | 268.405 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 11926.07 | 11926.07 | 1.156390 | 16.70 | 11.24 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00786540 | 41.2826 | 6971.42 | 0.00 | 11990.53 | 11990.53 |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 12312.385 | 12312.385 | 1.211499 | 0.00010771 | 276.547 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 12312.38 | 12312.38 | 1.211499 | 16.70 | 11.24 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00786818 | 41.2971 | 7121.60 | 0.00 | 12378.99 | 12378.99 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 7679.285 | 7679.285 | 1.202083 | 0.00006718 | 164.328 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 7679.28 | 7679.28 | 1.202083 | 16.70 | 11.24 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00727697 | 38.2343 | 2536.60 | 0.00 | 7722.07 | 7722.07 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 9196.361 | 9196.361 | 0.423362 | 0.00008045 | 244.795 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 9196.36 | 9196.36 | 0.423362 | 16.70 | 11.24 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00788825 | 41.4010 | 7382.33 | 0.00 | 9242.27 | 9242.27 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 45136.603 | -999.000 | 2.051317 | 0.00129090 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 45136.60 | 45136.60 | 2.051317 | 33.90 | 15.07 | 0.00547527 | 11.72 | 6.72 | 0.00547527 | 33.90 | 0.00547527 | 15.07 | 99.9965 | 21.11 | 0.00859063 | 44.7314 | 183503.95 | 0.00 | 45178.78 | 45178.78 |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | FLR_3_DOAS | 20913.378 | 20913.378 | 0.615395 | 0.00018296 | 324.431 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 20913.38 | 20913.38 | 0.615395 | -17.90 | -17.90 | 0.00095524 | 16.70 | 11.24 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 333.3216 | 21.11 | 0.00779085 | 40.6185 | 117227.02 | 0.00 | 16640.75 | 16640.75 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 474160.829 | -999.000 | 26.811117 | 0.01356094 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 474160.83 | 474160.83 | 26.811117 | 28.30 | 15.12 | 0.00782538 | 10.55 | 8.66 | 0.00782538 | 33.90 | 0.00547527 | 15.07 | 43.4949 | 23.99 | 0.00959187 | 41.8597 | 299228.01 | 0.00 | 375841.57 | 375841.57 |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV WITH REHEAT | 273341.932 | 273341.932 | 8.043335 | 0.00239131 | 4240.382 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 273341.93 | 273341.93 | 8.043335 | -17.90 | -17.90 | 0.00095524 | 16.70 | 11.24 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 144.9829 | 21.21 | 0.00681381 | 35.3737 | 68680.05 | 0.00 | 217497.84 | 217497.84 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:25:04
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | Yes | Yes | No | 5483.863 | 5483.863 | 1.279534 | 0.00004798 | 114.357 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.64028424 | 54.44 | 82.22 | 27.78 | 541142.97 | 1.0134 | 1.033780 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 5483.86 | 5483.86 | 1.0000 | 1.25066445 | 1.279534 | 16.70 | 11.24 | 0.00800000 | 37036.7 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.04797033 | 60.00 | 32.22 | 27.78 | 0.000 | 5483.86 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 41.9796 | 0.00 | 0.00 | 5514.68 | 5514.68 | 1.25066445 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 20.92 | 14.82 | 0.00800000 | 41344.1 | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3855.720 | 3855.720 | 0.192244 | 0.00003373 | 99.915 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.64028424 | 54.44 | 82.22 | 27.78 | 541142.97 | 0.7125 | 0.726854 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 3855.72 | 3855.72 | 1.0000 | 0.18790690 | 0.192244 | 16.70 | 11.24 | 0.00800000 | 37036.7 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.03372808 | 60.00 | 32.22 | 27.78 | 0.000 | 3855.72 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00778426 | 21.00 | 0.00778426 | 40.8628 | 3032.21 | 0.00 | 3875.15 | 3875.15 | 0.18790690 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 36.82 | 20.22 | 0.00800000 | 57557.4 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1487.829 | 1487.829 | 0.120577 | 0.00001302 | 34.414 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.64028424 | 54.44 | 82.22 | 27.78 | 541142.97 | 0.2749 | 0.280475 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1487.83 | 1487.83 | 1.0000 | 0.11785673 | 0.120577 | 16.70 | 11.24 | 0.00800000 | 37036.7 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.01301485 | 60.00 | 32.22 | 27.78 | 0.000 | 1487.83 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00774162 | 21.00 | 0.00774162 | 40.6409 | 971.32 | 0.00 | 1495.79 | 1495.79 | 0.11785673 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 29.05 | 17.72 | 0.00800000 | 49626.4 | |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2118.412 | 2118.412 | 0.095228 | 0.00001853 | 56.878 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.64028424 | 54.44 | 82.22 | 27.78 | 541142.97 | 0.3915 | 0.399348 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 2118.41 | 2118.41 | 1.0000 | 0.09307965 | 0.095228 | 16.70 | 11.24 | 0.00800000 | 37036.7 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.01853090 | 60.00 | 32.22 | 27.78 | 0.000 | 2118.41 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00765751 | 21.00 | 0.00765751 | 40.2048 | 1710.56 | 0.00 | 2128.96 | 2128.96 | 0.09307965 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 39.03 | 20.89 | 0.00800000 | 59807.2 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1497.438 | 1497.438 | 0.064486 | 0.00001310 | 40.868 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.64028424 | 54.44 | 82.22 | 27.78 | 541142.97 | 0.2767 | 0.282287 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1497.44 | 1497.44 | 1.0000 | 0.06303119 | 0.064486 | 16.70 | 11.24 | 0.00800000 | 37036.7 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.01309891 | 60.00 | 32.22 | 27.78 | 0.000 | 1497.44 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00772064 | 21.00 | 0.00772064 | 40.5322 | 1221.22 | 0.00 | 1504.86 | 1504.86 | 0.06303119 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 40.01 | 21.19 | 0.00800000 | 60809.6 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9698.026 | 9698.026 | 1.729802 | 0.00008484 | 205.523 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.64028424 | 54.44 | 82.22 | 27.78 | 541142.97 | 1.7921 | 1.828205 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 9698.03 | 9698.03 | 1.0000 | 1.69077382 | 1.729802 | 16.70 | 11.24 | 0.00800000 | 37036.7 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.08483391 | 60.00 | 32.22 | 27.78 | 0.000 | 9698.03 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00765109 | 21.00 | 0.00765109 | 40.1724 | 2290.05 | 0.00 | 9752.23 | 9752.23 | 1.69077382 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 22.26 | 15.32 | 0.00800000 | 42702.6 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11218.545 | 11218.545 | 0.809009 | 0.00009814 | 265.073 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.64028424 | 54.44 | 82.22 | 27.78 | 541142.97 | 2.0731 | 2.114843 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 11218.54 | 11218.54 | 1.0000 | 0.79075575 | 0.809009 | 16.70 | 11.24 | 0.00800000 | 37036.7 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.09813471 | 60.00 | 32.22 | 27.78 | 0.000 | 11218.54 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00781270 | 21.00 | 0.00781270 | 41.0100 | 7752.79 | 0.00 | 11278.23 | 11278.23 | 0.79075575 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 30.59 | 18.23 | 0.00800000 | 51197.3 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 28416.194 | 28416.194 | 2.560748 | 0.00024860 | 646.263 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.64028424 | 54.44 | 82.22 | 27.78 | 541142.97 | 5.2511 | 5.356825 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 28416.19 | 28416.19 | 1.0000 | 2.50297141 | 2.560748 | 16.70 | 11.24 | 0.00800000 | 37036.7 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.24857190 | 60.00 | 32.22 | 27.78 | 0.000 | 28416.19 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00776385 | 21.00 | 0.00776385 | 40.7562 | 17446.48 | 0.00 | 28569.20 | 28569.20 | 2.50297141 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 27.79 | 17.29 | 0.00800000 | 48348.8 | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13212.683 | -999.000 | 1.452055 | 0.00037787 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7195 | 1004.8586 | 0.9774 | ROOM_1_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.452055 | 1.41929290 | 4197.9300 | 999.8980 | 21.07192296 | 15.03 | 6.70 | 8.33 | 736858.95 | 1.7931 | 1.793075 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | unknown | unknown | 7/21 16:50:00 | Sensible | 13212.68 | 13109.36 | 1.0000 | 1.41929290 | 1.452055 | 21.82 | 13.55 | 0.00854220 | 43631.5 | 12.80 | 10.21 | 0.00850000 | 34322.2 | 0.37783545 | 6.70 | 15.03 | 8.33 | 0.000 | 13212.68 | 32.03 | 0.00547238 | 14.46 | 0.00000000 | 0.0000 | 21.11 | 0.00854220 | 21.11 | 0.00854220 | 44.4826 | 12038.83 | 0.00 | 9941.95 | 9941.95 | 1.41929290 | 21.82 | 15.64 | 0.00854220 | 43631.5 | 14.95 | 13.02 | 0.00854220 | 36626.7 | |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6651.819 | 6651.819 | 0.353306 | 0.00005819 | 190.060 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | ROOM_1_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.452055 | 1.41929290 | 4197.9300 | 999.8980 | 4.64028424 | 54.44 | 82.22 | 27.78 | 541142.97 | 1.2292 | 1.253955 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 6651.82 | 6651.82 | 1.0000 | 0.34533492 | 0.353306 | 21.11 | 12.65 | 0.00777336 | 40958.3 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.05818708 | 60.00 | 32.22 | 27.78 | 0.000 | 6651.82 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.11 | 0.00777336 | 21.11 | 0.00777336 | 40.5292 | 6651.86 | 0.00 | 7170.83 | 7170.83 | 0.34533492 | 16.60 | 12.93 | 0.00777336 | 36360.9 | 36.97 | 20.10 | 0.00777336 | 57125.8 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12910.239 | -999.000 | 1.418460 | 0.00036922 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7212 | 1004.8586 | 0.9774 | ROOM_2_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.418460 | 1.38645605 | 4197.9300 | 999.8980 | 21.07192296 | 15.03 | 6.70 | 8.33 | 736858.95 | 1.7521 | 1.752031 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | unknown | unknown | 7/21 17:00:00 | Sensible | 12910.24 | 12807.10 | 1.0000 | 1.38645605 | 1.418460 | 21.82 | 13.55 | 0.00854312 | 43633.9 | 12.80 | 10.21 | 0.00850000 | 34322.2 | 0.36918664 | 6.70 | 15.03 | 8.33 | 0.000 | 12910.24 | 31.83 | 0.00547208 | 14.39 | 0.00000000 | 0.0000 | 21.11 | 0.00854312 | 21.11 | 0.00854312 | 44.4873 | 11760.29 | 0.00 | 9714.86 | 9714.86 | 1.38645605 | 21.82 | 15.64 | 0.00854312 | 43633.9 | 14.95 | 13.02 | 0.00854312 | 36626.9 | |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6656.735 | 6656.735 | 0.353567 | 0.00005824 | 190.200 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | ROOM_2_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.418460 | 1.38645605 | 4197.9300 | 999.8980 | 4.64028424 | 54.44 | 82.22 | 27.78 | 541142.97 | 1.2301 | 1.254882 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 6656.73 | 6656.73 | 1.0000 | 0.34559010 | 0.353567 | 21.11 | 12.65 | 0.00777354 | 40958.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.05823008 | 60.00 | 32.22 | 27.78 | 0.000 | 6656.73 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.11 | 0.00777354 | 21.11 | 0.00777354 | 40.5301 | 6656.78 | 0.00 | 7176.13 | 7176.13 | 0.34559010 | 16.60 | 12.93 | 0.00777354 | 36361.4 | 36.97 | 20.10 | 0.00777354 | 57126.2 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 74556.746 | -999.000 | 8.289077 | 0.00213227 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6064 | 1004.8586 | 0.9774 | ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 8.289077 | 8.10205589 | 4197.9300 | 999.8980 | 21.07192296 | 15.03 | 6.70 | 8.33 | 736858.95 | 10.1182 | 10.117995 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | unknown | unknown | unknown | 7/21 13:30:00 | Sensible | 74556.75 | 74556.74 | 1.0000 | 8.10205589 | 8.289077 | 21.82 | 13.49 | 0.00848134 | 43477.3 | 12.80 | 10.20 | 0.00848134 | 34275.1 | 2.13205618 | 6.70 | 15.03 | 8.33 | 0.000 | 74556.75 | 33.53 | 0.00547470 | 14.95 | 0.00000000 | 0.0000 | 21.11 | 0.00848134 | 21.11 | 0.00848134 | 44.1690 | 68726.59 | 0.00 | 59838.74 | 59838.74 | 8.10205589 | 21.82 | 15.59 | 0.00848134 | 43477.3 | 14.58 | 12.81 | 0.00848134 | 36091.7 | |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 38221.425 | 38221.425 | 2.030136 | 0.00033438 | 1092.078 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 8.289077 | 8.10205589 | 4197.9300 | 999.8980 | 4.64028424 | 54.44 | 82.22 | 27.78 | 541142.97 | 7.0631 | 7.205239 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 38221.42 | 38221.42 | 1.0000 | 1.98433111 | 2.030136 | 21.11 | 12.66 | 0.00779038 | 41001.9 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.33434359 | 60.00 | 32.22 | 27.78 | 0.000 | 38221.42 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.11 | 0.00779038 | 21.11 | 0.00779038 | 40.6161 | 38221.54 | 0.00 | 41203.89 | 41203.89 | 1.98433111 | 16.60 | 12.95 | 0.00779038 | 36404.0 | 36.97 | 20.11 | 0.00779038 | 57168.6 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 71299.957 | -999.000 | 7.495381 | 0.00203913 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0292 | 1004.8586 | 0.9774 | ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 7.495381 | 7.32626708 | 4197.9300 | 999.8980 | 21.07192296 | 15.03 | 6.70 | 8.33 | 736858.95 | 9.6762 | 9.676021 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | unknown | unknown | unknown | 7/21 18:20:00 | Sensible | 71299.96 | 68623.91 | 1.0000 | 7.32626708 | 7.495381 | 21.82 | 13.68 | 0.00870878 | 44054.3 | 12.80 | 10.21 | 0.00850000 | 34322.2 | 2.03892366 | 6.70 | 15.03 | 8.33 | 0.000 | 71299.96 | 29.61 | 0.00546868 | 13.64 | 0.00000000 | 0.0000 | 21.11 | 0.00870878 | 21.11 | 0.00870878 | 45.3391 | 62140.58 | 0.00 | 54133.45 | 53189.31 | 7.32626708 | 21.82 | 15.79 | 0.00870878 | 44054.3 | 14.70 | 13.03 | 0.00865780 | 36665.3 | |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 38328.324 | 38328.324 | 2.035814 | 0.00033531 | 1095.132 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 7.495381 | 7.32626708 | 4197.9300 | 999.8980 | 4.64028424 | 54.44 | 82.22 | 27.78 | 541142.97 | 7.0828 | 7.225391 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 38328.32 | 38328.32 | 1.0000 | 1.98988098 | 2.035814 | 21.11 | 12.66 | 0.00779090 | 41003.2 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.33527869 | 60.00 | 32.22 | 27.78 | 0.000 | 38328.32 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.11 | 0.00779090 | 21.11 | 0.00779090 | 40.6187 | 38328.44 | 0.00 | 41319.13 | 41319.13 | 1.98988098 | 16.60 | 12.95 | 0.00779090 | 36405.3 | 36.97 | 20.11 | 0.00779090 | 57169.9 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11656.461 | -999.000 | 1.279200 | 0.00033337 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7293 | 1004.8586 | 0.9774 | ROOM_5_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.279200 | 1.25033849 | 4197.9300 | 999.8980 | 21.07192296 | 15.03 | 6.70 | 8.33 | 736858.95 | 1.5819 | 1.581883 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | unknown | unknown | unknown | 7/21 09:40:00 | Sensible | 11656.46 | 11554.10 | 1.0000 | 1.25033849 | 1.279200 | 21.82 | 13.55 | 0.00854744 | 43644.8 | 12.80 | 10.21 | 0.00850000 | 34322.2 | 0.33333309 | 6.70 | 15.03 | 8.33 | 0.000 | 11656.46 | 27.44 | 0.00546540 | 12.88 | 0.00000000 | 0.0000 | 21.11 | 0.00854744 | 21.11 | 0.00854744 | 44.5095 | 10605.71 | 0.00 | 8773.47 | 8773.47 | 1.25033849 | 21.82 | 15.64 | 0.00854744 | 43644.8 | 14.94 | 13.02 | 0.00854744 | 36628.0 | |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6651.819 | 6651.819 | 0.353306 | 0.00005819 | 190.060 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | ROOM_5_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.279200 | 1.25033849 | 4197.9300 | 999.8980 | 4.64028424 | 54.44 | 82.22 | 27.78 | 541142.97 | 1.2292 | 1.253955 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 6651.82 | 6651.82 | 1.0000 | 0.34533492 | 0.353306 | 21.11 | 12.65 | 0.00777336 | 40958.3 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.05818708 | 60.00 | 32.22 | 27.78 | 0.000 | 6651.82 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.11 | 0.00777336 | 21.11 | 0.00777336 | 40.5292 | 6651.86 | 0.00 | 7170.83 | 7170.83 | 0.34533492 | 16.60 | 12.93 | 0.00777336 | 36360.9 | 36.97 | 20.10 | 0.00777336 | 57125.8 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11406.414 | -999.000 | 1.251472 | 0.00032622 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7308 | 1004.8586 | 0.9774 | ROOM_6_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.251472 | 1.22323571 | 4197.9300 | 999.8980 | 21.07192296 | 15.03 | 6.70 | 8.33 | 736858.95 | 1.5480 | 1.547949 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | unknown | unknown | unknown | 7/21 09:10:00 | Sensible | 11406.41 | 11304.48 | 1.0000 | 1.22323571 | 1.251472 | 21.82 | 13.55 | 0.00854828 | 43647.0 | 12.80 | 10.21 | 0.00850000 | 34322.2 | 0.32618262 | 6.70 | 15.03 | 8.33 | 0.000 | 11406.41 | 26.18 | 0.00546350 | 12.44 | 0.00000000 | 0.0000 | 21.11 | 0.00854828 | 21.11 | 0.00854828 | 44.5138 | 10375.82 | 0.00 | 8585.67 | 8585.67 | 1.22323571 | 21.82 | 15.65 | 0.00854828 | 43647.0 | 14.94 | 13.02 | 0.00854828 | 36628.2 | |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6656.735 | 6656.735 | 0.353567 | 0.00005824 | 190.200 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | ROOM_6_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.251472 | 1.22323571 | 4197.9300 | 999.8980 | 4.64028424 | 54.44 | 82.22 | 27.78 | 541142.97 | 1.2301 | 1.254882 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 6656.73 | 6656.73 | 1.0000 | 0.34559010 | 0.353567 | 21.11 | 12.65 | 0.00777354 | 40958.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.05823008 | 60.00 | 32.22 | 27.78 | 0.000 | 6656.73 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.11 | 0.00777354 | 21.11 | 0.00777354 | 40.5301 | 6656.78 | 0.00 | 7176.13 | 7176.13 | 0.34559010 | 16.60 | 12.93 | 0.00777354 | 36361.4 | 36.97 | 20.10 | 0.00777354 | 57126.2 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14095.133 | 14095.133 | 0.811221 | 0.00012331 | 350.473 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.64028424 | 54.44 | 82.22 | 27.78 | 541142.97 | 2.6047 | 2.657117 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 14095.13 | 14095.13 | 1.0000 | 0.79291814 | 0.811221 | 16.70 | 11.24 | 0.00800000 | 37036.7 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.12329779 | 60.00 | 32.22 | 27.78 | 0.000 | 14095.13 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00782597 | 21.00 | 0.00782597 | 41.0780 | 10619.55 | 0.00 | 14167.91 | 14167.91 | 0.79291814 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 34.12 | 19.38 | 0.00800000 | 54802.8 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3506.981 | -999.000 | 0.385667 | 0.00010030 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7150 | 1004.8586 | 0.9774 | ROOM_1_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.385667 | 0.37696519 | 4197.9300 | 999.8980 | 21.07192296 | 15.03 | 6.70 | 8.33 | 736858.95 | 0.4759 | 0.475928 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | unknown | unknown | 7/21 16:50:00 | Sensible | 3506.98 | 3481.12 | 1.0000 | 0.37696519 | 0.385667 | 21.82 | 13.54 | 0.00853978 | 43625.4 | 12.80 | 10.21 | 0.00850000 | 34322.2 | 0.10028712 | 6.70 | 15.03 | 8.33 | 0.000 | 3506.98 | 32.03 | 0.00547238 | 14.46 | 0.00000000 | 0.0000 | 21.11 | 0.00853978 | 21.11 | 0.00853978 | 44.4701 | 3197.52 | 0.00 | 2638.50 | 2638.50 | 0.37696519 | 21.82 | 15.64 | 0.00853978 | 43625.4 | 14.96 | 13.02 | 0.00853978 | 36626.1 | |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2063.989 | 2063.989 | 0.109627 | 0.00001806 | 58.972 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | ROOM_1_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.385667 | 0.37696519 | 4197.9300 | 999.8980 | 4.64028424 | 54.44 | 82.22 | 27.78 | 541142.97 | 0.3814 | 0.389089 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 2063.99 | 2063.99 | 1.0000 | 0.10715387 | 0.109627 | 21.11 | 12.68 | 0.00781621 | 41067.2 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.01805484 | 60.00 | 32.22 | 27.78 | 0.000 | 2063.99 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.11 | 0.00781621 | 21.11 | 0.00781621 | 40.7498 | 2064.00 | 0.00 | 2225.03 | 2225.03 | 0.10715387 | 16.60 | 12.97 | 0.00781621 | 36469.4 | 36.97 | 20.13 | 0.00781621 | 57234.3 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3420.113 | -999.000 | 0.376018 | 0.00009781 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7168 | 1004.8586 | 0.9774 | ROOM_2_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.376018 | 0.36753379 | 4197.9300 | 999.8980 | 21.07192296 | 15.03 | 6.70 | 8.33 | 736858.95 | 0.4641 | 0.464139 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | unknown | unknown | 7/21 16:50:00 | Sensible | 3420.11 | 3394.30 | 1.0000 | 0.36753379 | 0.376018 | 21.82 | 13.54 | 0.00854071 | 43627.8 | 12.80 | 10.21 | 0.00850000 | 34322.2 | 0.09780299 | 6.70 | 15.03 | 8.33 | 0.000 | 3420.11 | 32.03 | 0.00547238 | 14.46 | 0.00000000 | 0.0000 | 21.11 | 0.00854071 | 21.11 | 0.00854071 | 44.4750 | 3117.52 | 0.00 | 2573.27 | 2573.27 | 0.36753379 | 21.82 | 15.64 | 0.00854071 | 43627.8 | 14.96 | 13.02 | 0.00854071 | 36626.3 | |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2063.896 | 2063.896 | 0.109622 | 0.00001806 | 58.969 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | ROOM_2_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.376018 | 0.36753379 | 4197.9300 | 999.8980 | 4.64028424 | 54.44 | 82.22 | 27.78 | 541142.97 | 0.3814 | 0.389072 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 2063.90 | 2063.90 | 1.0000 | 0.10714904 | 0.109622 | 21.11 | 12.68 | 0.00781622 | 41067.2 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.01805402 | 60.00 | 32.22 | 27.78 | 0.000 | 2063.90 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.11 | 0.00781622 | 21.11 | 0.00781622 | 40.7498 | 2063.91 | 0.00 | 2224.93 | 2224.93 | 0.10714904 | 16.60 | 12.97 | 0.00781622 | 36469.4 | 36.97 | 20.13 | 0.00781622 | 57234.3 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15595.987 | -999.000 | 1.687004 | 0.00044603 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8286 | 1004.8586 | 0.9774 | ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 1.687004 | 1.64894081 | 4197.9300 | 999.8980 | 21.07192296 | 15.03 | 6.70 | 8.33 | 736858.95 | 2.1165 | 2.116510 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | unknown | unknown | unknown | 7/21 13:30:00 | Sensible | 15595.99 | 15307.51 | 1.0000 | 1.64894081 | 1.687004 | 21.82 | 13.59 | 0.00860090 | 43780.4 | 12.80 | 10.21 | 0.00850000 | 34322.2 | 0.44598942 | 6.70 | 15.03 | 8.33 | 0.000 | 15595.99 | 33.53 | 0.00547470 | 14.95 | 0.00000000 | 0.0000 | 21.11 | 0.00860090 | 21.11 | 0.00860090 | 44.7848 | 13986.32 | 0.00 | 11772.84 | 11772.84 | 1.64894081 | 21.82 | 15.69 | 0.00860090 | 43780.4 | 14.82 | 13.02 | 0.00860090 | 36640.7 | |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9931.794 | 9931.794 | 0.527523 | 0.00008689 | 283.769 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 1.687004 | 1.64894081 | 4197.9300 | 999.8980 | 4.64028424 | 54.44 | 82.22 | 27.78 | 541142.97 | 1.8353 | 1.872273 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 9931.79 | 9931.79 | 1.0000 | 0.51562104 | 0.527523 | 21.11 | 12.69 | 0.00782393 | 41086.9 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.08687880 | 60.00 | 32.22 | 27.78 | 0.000 | 9931.79 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.11 | 0.00782393 | 21.11 | 0.00782393 | 40.7892 | 9931.84 | 0.00 | 10706.75 | 10706.75 | 0.51562104 | 16.60 | 12.98 | 0.00782393 | 36489.0 | 36.97 | 20.14 | 0.00782393 | 57253.7 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11926.069 | 11926.069 | 1.156390 | 0.00010433 | 268.405 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.64028424 | 54.44 | 82.22 | 27.78 | 541142.97 | 2.2039 | 2.248220 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 11926.07 | 11926.07 | 1.0000 | 1.13029874 | 1.156390 | 16.70 | 11.24 | 0.00800000 | 37036.7 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.10432381 | 60.00 | 32.22 | 27.78 | 0.000 | 11926.07 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00786540 | 21.00 | 0.00786540 | 41.2826 | 6971.42 | 0.00 | 11990.53 | 11990.53 | 1.13029874 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 27.00 | 17.02 | 0.00800000 | 47543.0 | |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12312.385 | 12312.385 | 1.211499 | 0.00010771 | 276.547 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.64028424 | 54.44 | 82.22 | 27.78 | 541142.97 | 2.2753 | 2.321046 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 12312.38 | 12312.38 | 1.0000 | 1.18416509 | 1.211499 | 16.70 | 11.24 | 0.00800000 | 37036.7 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.10770313 | 60.00 | 32.22 | 27.78 | 0.000 | 12312.38 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00786818 | 21.00 | 0.00786818 | 41.2971 | 7121.60 | 0.00 | 12378.99 | 12378.99 | 1.18416509 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 26.85 | 16.96 | 0.00800000 | 47388.5 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7679.285 | 7679.285 | 1.202083 | 0.00006718 | 164.328 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.64028424 | 54.44 | 82.22 | 27.78 | 541142.97 | 1.4191 | 1.447646 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | Sensible | 7679.28 | 7679.28 | 1.0000 | 1.17496123 | 1.202083 | 16.70 | 11.24 | 0.00800000 | 37036.7 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.06717488 | 60.00 | 32.22 | 27.78 | 0.000 | 7679.28 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.60 | 0.00727697 | 21.00 | 0.00727697 | 38.2343 | 2536.60 | 0.00 | 7722.07 | 7722.07 | 1.17496123 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 23.05 | 15.61 | 0.00800000 | 43506.9 | |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9196.361 | 9196.361 | 0.423362 | 0.00008045 | 244.795 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.64028424 | 54.44 | 82.22 | 27.78 | 541142.97 | 1.6994 | 1.733635 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 9196.36 | 9196.36 | 1.0000 | 0.41381012 | 0.423362 | 16.70 | 11.24 | 0.00800000 | 37036.7 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.08044557 | 60.00 | 32.22 | 27.78 | 0.000 | 9196.36 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00788825 | 21.00 | 0.00788825 | 41.4010 | 7382.33 | 0.00 | 9242.27 | 9242.27 | 0.41381012 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 38.50 | 20.73 | 0.00800000 | 59269.3 | |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 45136.603 | -999.000 | 2.051317 | 0.00129090 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1015.0183 | 1004.8586 | 0.9774 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.00496413 | 4197.9300 | 999.8980 | 21.07192296 | 15.03 | 6.70 | 8.33 | 736858.95 | 6.1255 | 6.125542 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | Sensible | 45136.60 | 45136.60 | 1.0000 | 2.00503462 | 2.051317 | 33.90 | 15.07 | 0.00547527 | 48102.5 | 11.72 | 6.72 | 0.00547527 | 25590.8 | 1.29076945 | 6.70 | 15.03 | 8.33 | 2195.006 | 42941.60 | 33.90 | 0.00547527 | 15.07 | 2.05124512 | 99.9965 | 21.11 | 0.00858397 | 21.11 | 0.00859063 | 44.7314 | 183503.95 | 0.00 | 45178.78 | 45178.78 | 2.00503462 | 33.90 | 17.27 | 0.00547527 | 48102.5 | 11.70 | 8.38 | 0.00547527 | 25569.8 | |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 20913.378 | 20913.378 | 0.615395 | 0.00018296 | 324.431 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.00496413 | 4197.9300 | 999.8980 | 4.64028424 | 54.44 | 82.22 | 27.78 | 541142.97 | 3.8647 | 3.942446 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 20913.38 | 20913.38 | 1.0000 | 0.60151039 | 0.615395 | -17.90 | -17.90 | 0.00095524 | -15629.4 | 16.70 | 11.24 | 0.00800000 | 37036.7 | 0.18294069 | 60.00 | 32.22 | 27.78 | 0.000 | 20913.38 | -17.90 | 0.00095524 | -17.90 | 2.05124512 | 333.3216 | 21.11 | 0.00779046 | 21.11 | 0.00779085 | 40.6185 | 117227.02 | 0.00 | 16640.75 | 16640.75 | 0.60151039 | 2.80 | -2.86 | 0.00095524 | 5207.5 | 30.28 | 11.67 | 0.00095524 | 32872.5 | |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 474160.829 | -999.000 | 26.811117 | 0.01356094 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.3870 | 1004.8586 | 0.9774 | VAV WITH REHEAT FAN | Fan:VariableVolume | 26.811117 | 26.20619430 | 4197.9300 | 999.8980 | 21.07192296 | 15.03 | 6.70 | 8.33 | 736858.95 | 64.3489 | 64.348927 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | Sensible | 474160.83 | 474160.83 | 1.0000 | 26.20619430 | 26.811117 | 28.30 | 15.12 | 0.00782538 | 48420.1 | 10.55 | 8.66 | 0.00782538 | 30326.6 | 13.55955633 | 6.70 | 15.03 | 8.33 | 60074.024 | 414086.81 | 33.90 | 0.00547527 | 15.07 | 11.66146000 | 43.4949 | 23.99 | 0.00963529 | 23.99 | 0.00959187 | 41.8597 | 299228.01 | 0.00 | 375841.57 | 375841.57 | 26.20619430 | 28.30 | 17.32 | 0.00782538 | 48420.1 | 14.23 | 12.02 | 0.00782538 | 34078.4 | |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 273341.932 | 273341.932 | 8.043335 | 0.00239131 | 4240.382 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | VAV WITH REHEAT FAN | Fan:VariableVolume | 26.811117 | 26.20619430 | 4197.9300 | 999.8980 | 4.64028424 | 54.44 | 82.22 | 27.78 | 541142.97 | 50.5120 | 51.528536 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 273341.93 | 273341.93 | 1.0000 | 7.86185829 | 8.043335 | -17.90 | -17.90 | 0.00095524 | -15629.4 | 16.70 | 11.24 | 0.00800000 | 37036.7 | 2.39107052 | 60.00 | 32.22 | 27.78 | 0.000 | 273341.93 | -17.90 | 0.00095524 | -17.90 | 11.66146000 | 144.9829 | 18.63 | 0.00702403 | 21.21 | 0.00681381 | 35.3737 | 68680.05 | 0.00 | 217497.84 | 217497.84 | 7.86185829 | 2.80 | -2.86 | 0.00095524 | 5207.5 | 30.28 | 11.67 | 0.00095524 | 32872.5 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:04
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - | |||
VAV WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 26.81 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | VAV WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000610 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LAUNDRY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CAFE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001448 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_3 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
KITCHEN_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003556 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 593.33 | 6502.50 | 301.33 |
RETAIL_1_FLR_1 | 2734.67 | 5978.67 | 1007.00 |
RETAIL_2_FLR_1 | 1223.67 | 5910.00 | 375.17 |
MECH_FLR_1 | 868.33 | 7242.83 | 472.67 |
STORAGE_FLR_1 | 901.83 | 7694.33 | 672.50 |
LAUNDRY_FLR_1 | 7998.00 | 3150.17 | 2942.67 |
CAFE_FLR_1 | 3897.83 | 3653.33 | 702.67 |
LOBBY_FLR_1 | 1956.83 | 3597.67 | 476.00 |
ROOM_1_FLR_3 | 1311.17 | 7926.17 | 1051.50 |
ROOM_2_FLR_3 | 2226.67 | 7758.33 | 1781.67 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 948.67 | 8707.33 | 929.83 |
ROOM_5_FLR_3 | 1326.83 | 7864.83 | 1049.67 |
ROOM_6_FLR_3 | 2295.33 | 7696.67 | 1821.67 |
CORRIDOR_FLR_3 | 848.83 | 7595.17 | 632.00 |
ROOM_1_FLR_6 | 2095.00 | 7799.33 | 1684.83 |
ROOM_2_FLR_6 | 3140.83 | 7670.33 | 2573.33 |
ROOM_3_MULT9_FLR_6 | 1288.83 | 7563.83 | 782.00 |
BANQUET_FLR_6 | 3404.50 | 2421.83 | 485.17 |
DINING_FLR_6 | 4223.17 | 1357.83 | 467.83 |
KITCHEN_FLR_6 | 8566.83 | 6233.67 | 6186.00 |
CORRIDOR_FLR_6 | 1201.50 | 7010.67 | 694.33 |
Facility | 8760.00 | 8760.00 | 7444.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.17 | 0.00 | 0.17 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 6.17 | 0.00 | 6.17 |
CAFE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 1.00 | 141.33 | 1.00 | 141.33 |
ROOM_2_FLR_3 | 2.17 | 139.00 | 2.17 | 139.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4.17 | 144.00 | 4.17 | 144.00 |
ROOM_5_FLR_3 | 1.50 | 158.67 | 1.50 | 158.67 |
ROOM_6_FLR_3 | 3.67 | 160.67 | 3.67 | 160.67 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 1.83 | 157.67 | 1.83 | 157.67 |
ROOM_2_FLR_6 | 3.50 | 155.50 | 3.50 | 155.50 |
ROOM_3_MULT9_FLR_6 | 1.17 | 161.83 | 1.17 | 161.83 |
BANQUET_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 6.83 | 0.00 | 6.83 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 6.00 | 510.50 | 6.00 | 510.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:04
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.79 | 106.50 | 4826.41 | 1.092 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 2.935 | 0.063 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.28 | 12.54 | 307.76 | 1.538 | 0.021 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.549 | 0.023 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.558 | 0.023 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 26.195 | 0.067 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.56 | 142.30 | 748.35 | 4.539 | 0.049 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.09 | 422.44 | 5183.56 | 2.032 | 0.020 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.354 | 0.081 | 0.000 | 0.053 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.355 | 0.081 | 0.000 | 0.050 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.402 | 0.036 | 0.000 | 0.087 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.354 | 0.081 | 0.000 | 0.053 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.355 | 0.081 | 0.000 | 0.052 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 0.626 | 0.010 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.354 | 0.081 | 0.000 | 0.063 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.355 | 0.081 | 0.000 | 0.055 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.402 | 0.066 | 0.000 | 0.101 |
BANQUET_FLR_6 | 144.99 | 249.90 | 1010.89 | 5.652 | 0.023 | 0.000 | 0.000 |
DINING_FLR_6 | 144.99 | 249.90 | 1010.89 | 6.145 | 0.023 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 26.399 | 0.067 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 1.254 | 0.016 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.79 | 106.50 | 4826.41 | 0.497 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 1.460 | 0.001 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.28 | 12.54 | 307.76 | 0.996 | 0.000 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.438 | 0.000 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.398 | 0.000 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 14.203 | 0.001 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.56 | 142.30 | 748.35 | 2.463 | 0.001 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.09 | 422.44 | 5183.56 | 1.272 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 0.368 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.000 | 0.001 | 0.000 | 0.000 |
BANQUET_FLR_6 | 144.99 | 249.90 | 1010.89 | 3.438 | 0.000 | 0.000 | 0.000 |
DINING_FLR_6 | 144.99 | 249.90 | 1010.89 | 3.602 | 0.000 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 11.526 | 0.001 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 0.755 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:25:04
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | VAV WITH REHEAT | 61.79 | 106.50 | 4826.41 | 1978.83 | 0.0000 | 0.854 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 6.28 | 10.83 | 265.76 | 67.07 | 0.0000 | 0.079 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 7.28 | 12.54 | 307.76 | 77.67 | 0.0000 | 0.092 |
MECH_FLR_1 | VAV WITH REHEAT | 1.54 | 2.65 | 650.80 | 164.24 | 0.0000 | 0.000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 1.18 | 2.04 | 375.47 | 94.76 | 0.0000 | 0.058 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 4.87 | 8.40 | 309.22 | 78.04 | 0.0000 | 0.000 |
CAFE_FLR_1 | VAV WITH REHEAT | 82.56 | 142.30 | 748.35 | 188.86 | 0.0000 | 0.676 |
LOBBY_FLR_1 | VAV WITH REHEAT | 245.09 | 422.44 | 5183.56 | 1308.19 | 0.0000 | 1.894 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 1.50 | 74.75 | 24.52 | 0.0000 | 0.837 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.837 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 12.16 | 20.96 | 1186.91 | 389.40 | 0.0000 | 0.475 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.015 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.015 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.099 |
BANQUET_FLR_6 | VAV WITH REHEAT | 144.99 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
DINING_FLR_6 | VAV WITH REHEAT | 144.99 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 12.90 | 22.24 | 314.87 | 103.30 | 0.0000 | 0.367 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 12.87 | 22.18 | 1256.16 | 412.12 | 0.0000 | 0.126 |
Total Facility | 873.25 | 1604.23 | 35184.81 | 11345.29 | 0.0000 | 137.584 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 45417807.19 | 0.00 | 45417807.19 | 0.00 | 45417807.19 | 26946214.98 | 32.55 | 4.56 | 8722.89 | 0.00 |
RETAIL_1_FLR_1 | 6755427.83 | 0.00 | 6755427.83 | 143971.56 | 6899399.39 | 2498216.28 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_2_FLR_1 | 4084024.93 | 0.00 | 4084024.93 | 55573.20 | 4139598.14 | 2892943.94 | 3.17 | 1.00 | 8755.83 | 0.00 |
MECH_FLR_1 | 3094560.01 | 0.00 | 3094560.01 | 131342.04 | 3225902.05 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
STORAGE_FLR_1 | 1816568.90 | 0.00 | 1816568.90 | 75777.12 | 1892346.02 | 1821682.01 | 501.59 | 7990.87 | 267.54 | 0.00 |
LAUNDRY_FLR_1 | 69911939.59 | 0.00 | 69911939.59 | 179340.85 | 70091280.44 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
CAFE_FLR_1 | 29280005.16 | 0.00 | 29280005.16 | 318257.28 | 29598262.44 | 21330615.53 | 64.60 | 6.22 | 8689.18 | 0.00 |
LOBBY_FLR_1 | 90687295.23 | 0.00 | 90687295.23 | 909333.75 | 91596628.99 | 59728886.00 | 1.50 | 1.50 | 8757.00 | 0.00 |
ROOM_1_FLR_3 | 1460156.71 | 55037.97 | 1515194.69 | 83565.56 | 1598760.25 | 1946875.62 | 2189.00 | 5988.83 | 582.17 | 0.00 |
ROOM_2_FLR_3 | 1459985.63 | 51486.17 | 1511471.80 | 83559.19 | 1595030.99 | 1946647.51 | 2190.00 | 6053.71 | 516.29 | 0.00 |
ROOM_3_MULT19_FLR_3 | 1099911.97 | 0.00 | 1099911.97 | 23315.73 | 1123227.70 | 26397887.27 | 8395.00 | 365.00 | 0.00 | 365.00 |
ROOM_4_MULT19_FLR_3 | 19803829.30 | 56389.70 | 19860218.99 | 23322.11 | 19883541.10 | 26405105.73 | 2190.00 | 5994.81 | 575.19 | 0.00 |
ROOM_5_FLR_3 | 1460156.71 | 55157.16 | 1515313.87 | 83565.56 | 1598879.44 | 1946875.62 | 2189.00 | 5988.83 | 582.17 | 0.00 |
ROOM_6_FLR_3 | 1459985.63 | 53126.23 | 1513111.87 | 83559.19 | 1596671.06 | 1946647.51 | 2190.00 | 6010.22 | 559.78 | 0.00 |
CORRIDOR_FLR_3 | 25706280.92 | 0.00 | 25706280.92 | 101047.58 | 25807328.50 | 14972100.18 | 0.00 | 0.00 | 8760.00 | 0.00 |
ROOM_1_FLR_6 | 365039.18 | 65685.92 | 430725.10 | 83583.17 | 514308.26 | 486718.90 | 2038.86 | 5990.78 | 730.36 | 0.00 |
ROOM_2_FLR_6 | 364996.41 | 56907.16 | 421903.57 | 83576.79 | 505480.36 | 486661.88 | 2066.88 | 6081.00 | 612.12 | 0.00 |
ROOM_3_MULT9_FLR_6 | 2345190.31 | 65716.79 | 2410907.10 | 42764.07 | 2453671.17 | 3126920.42 | 2190.00 | 5989.50 | 580.50 | 0.00 |
BANQUET_FLR_6 | 49149418.23 | 0.00 | 49149418.23 | 204089.08 | 49353507.31 | 37458366.31 | 1877.46 | 142.61 | 6739.93 | 0.00 |
DINING_FLR_6 | 53432840.10 | 0.00 | 53432840.10 | 204089.08 | 53636929.18 | 37458366.31 | 8.67 | 5.42 | 8745.92 | 0.00 |
KITCHEN_FLR_6 | 71593097.76 | 0.00 | 71593097.76 | 182707.05 | 71775804.81 | 11584760.86 | 0.00 | 0.00 | 8760.00 | 0.00 |
CORRIDOR_FLR_6 | 13646306.80 | 0.00 | 13646306.80 | 178823.46 | 13825130.26 | 3961413.96 | 0.00 | 0.00 | 8760.00 | 0.00 |
Total Facility | 0.22E+10 | 5858891.47 | 0.22E+10 | 8421004.90 | 0.22E+10 | 0.43E+10 | 8760.00 | 8632.08 | 8760.00 | 365.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 1.4402 | 0.0000 | 1.4402 | 0.0000 | 1.4402 | 0.8545 | 32.55 | 4.56 | 8722.89 |
RETAIL_1_FLR_1 | 0.2142 | 0.0000 | 0.2142 | 0.0046 | 0.2188 | 0.0792 | 0.00 | 0.00 | 8760.00 |
RETAIL_2_FLR_1 | 0.1295 | 0.0000 | 0.1295 | 0.0018 | 0.1313 | 0.0917 | 3.17 | 1.00 | 8755.83 |
MECH_FLR_1 | 0.0981 | 0.0000 | 0.0981 | 0.0042 | 0.1023 | 0.0000 | 0.00 | 0.00 | 8760.00 |
STORAGE_FLR_1 | 0.0576 | 0.0000 | 0.0576 | 0.0024 | 0.0600 | 0.0578 | 501.59 | 7990.87 | 267.54 |
LAUNDRY_FLR_1 | 2.2169 | 0.0000 | 2.2169 | 0.0057 | 2.2226 | 0.0000 | 0.00 | 0.00 | 8760.00 |
CAFE_FLR_1 | 0.9285 | 0.0000 | 0.9285 | 0.0101 | 0.9386 | 0.6764 | 64.60 | 6.22 | 8689.18 |
LOBBY_FLR_1 | 2.8757 | 0.0000 | 2.8757 | 0.0288 | 2.9045 | 1.8940 | 1.50 | 1.50 | 8757.00 |
ROOM_1_FLR_3 | 0.0463 | 0.0017 | 0.0480 | 0.0026 | 0.0507 | 0.0617 | 2189.00 | 5988.83 | 582.17 |
ROOM_2_FLR_3 | 0.0463 | 0.0016 | 0.0479 | 0.0026 | 0.0506 | 0.0617 | 2190.00 | 6053.71 | 516.29 |
ROOM_4_MULT19_FLR_3 | 0.6280 | 0.0018 | 0.6298 | 0.0007 | 0.6305 | 0.8373 | 2190.00 | 5994.81 | 575.19 |
ROOM_5_FLR_3 | 0.0463 | 0.0017 | 0.0481 | 0.0026 | 0.0507 | 0.0617 | 2189.00 | 5988.83 | 582.17 |
ROOM_6_FLR_3 | 0.0463 | 0.0017 | 0.0480 | 0.0026 | 0.0506 | 0.0617 | 2190.00 | 6010.22 | 559.78 |
CORRIDOR_FLR_3 | 0.8151 | 0.0000 | 0.8151 | 0.0032 | 0.8183 | 0.4748 | 0.00 | 0.00 | 8760.00 |
ROOM_1_FLR_6 | 0.0116 | 0.0021 | 0.0137 | 0.0027 | 0.0163 | 0.0154 | 2038.86 | 5990.78 | 730.36 |
ROOM_2_FLR_6 | 0.0116 | 0.0018 | 0.0134 | 0.0027 | 0.0160 | 0.0154 | 2066.88 | 6081.00 | 612.12 |
ROOM_3_MULT9_FLR_6 | 0.0744 | 0.0021 | 0.0764 | 0.0014 | 0.0778 | 0.0992 | 2190.00 | 5989.50 | 580.50 |
BANQUET_FLR_6 | 1.5585 | 0.0000 | 1.5585 | 0.0065 | 1.5650 | 1.1878 | 1877.46 | 142.61 | 6739.93 |
DINING_FLR_6 | 1.6943 | 0.0000 | 1.6943 | 0.0065 | 1.7008 | 1.1878 | 8.67 | 5.42 | 8745.92 |
KITCHEN_FLR_6 | 2.2702 | 0.0000 | 2.2702 | 0.0058 | 2.2760 | 0.3674 | 0.00 | 0.00 | 8760.00 |
CORRIDOR_FLR_6 | 0.4327 | 0.0000 | 0.4327 | 0.0057 | 0.4384 | 0.1256 | 0.00 | 0.00 | 8760.00 |
Total Facility | 66.3364 | 0.1858 | 66.5221 | 0.2108 | 66.7330 | 73.9670 | 8760.00 | 8632.08 | 8760.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
FLR_3_DOAS | 28488844.65 | 459507.09 | 28948351.74 | 64690340.46 | 8760.00 | 0.00 | 0.00 | 0.00 |
VAV WITH REHEAT | 0.44E+09 | 0.00 | 0.44E+09 | 0.22E+09 | 0.00 | 0.00 | 8760.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
FLR_3_DOAS | 0.9034 | 0.0146 | 0.9179 | 2.0513 | 8760.00 | 0.00 | 0.00 |
VAV WITH REHEAT | 14.0743 | 0.0000 | 14.0743 | 6.9969 | 0.00 | 0.00 | 8760.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
FLR_3_DOAS | 0.00 | 0.00 | 0.00 | 0.00 | 6935.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
VAV WITH REHEAT | 0.00 | 0.00 | 4054.54 | 0.00 | 0.00 | 0.00 | 4705.46 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
FLR_3_DOAS | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.1411 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
VAV WITH REHEAT | 0.0000 | 0.0000 | 14.5905 | 0.0000 | 0.0000 | 0.0000 | 13.6326 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:04
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1333 |
Defaulted Fields | 1182 |
Fields with Defaults | 4000 |
Autosized Fields | 349 |
Autosizable Fields | 402 |
Autocalculated Fields | 280 |
Autocalculatable Fields | 539 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:25:04
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 5014.16 | 65523.65 | 20-MAY-04:50 | 365749.68 | 26-JUN-19:30 |
Electricity:Building | 2447.03 | 31112.40 | 27-MAY-05:00 | 151313.73 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 304.40 | 3493.55 | 02-JAN-02:10 | 22822.84 | 02-JAN-20:10 |
Electricity:SpaceType:GENERAL | 2439.94 | 30971.25 | 27-MAY-05:00 | 151072.40 | 02-JAN-20:10 |
InteriorLights:Electricity | 781.76 | 6769.28 | 27-MAY-05:00 | 64632.59 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 161.29 | 1465.65 | 02-JAN-02:10 | 13190.31 | 02-JAN-20:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 781.76 | 6769.28 | 27-MAY-05:00 | 64632.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 781.76 | 6769.28 | 27-MAY-05:00 | 64632.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 161.29 | 1465.65 | 02-JAN-02:10 | 13190.31 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 781.76 | 6769.28 | 27-MAY-05:00 | 64632.59 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 17.49 | 210.74 | 02-JAN-02:10 | 1283.20 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 7.31 | 66.40 | 02-JAN-02:10 | 597.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 7.31 | 66.40 | 02-JAN-02:10 | 597.59 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 20.26 | 244.03 | 02-JAN-02:10 | 1485.95 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 8.46 | 76.89 | 02-JAN-02:10 | 692.02 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 8.46 | 76.89 | 02-JAN-02:10 | 692.02 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 20.84 | 252.75 | 02-JAN-02:10 | 1523.62 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.37 | 76.02 | 02-JAN-02:10 | 684.18 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.37 | 76.02 | 02-JAN-02:10 | 684.18 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 6.68 | 78.96 | 02-JAN-02:10 | 493.99 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 3.08 | 27.98 | 02-JAN-02:10 | 251.84 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 3.08 | 27.98 | 02-JAN-02:10 | 251.84 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 71.91 | 998.82 | 02-JAN-02:10 | 4897.88 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 3.98 | 36.12 | 02-JAN-02:10 | 325.08 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 3.98 | 36.12 | 02-JAN-02:10 | 325.08 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 28.37 | 318.54 | 20-MAY-05:00 | 2666.80 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 14.03 | 83.19 | 01-JAN-13:10 | 1701.53 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 | 14.03 | 83.19 | 01-JAN-13:10 | 1701.53 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 258.81 | 3118.22 | 27-MAY-05:00 | 19534.01 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 109.81 | 1006.80 | 27-MAY-05:00 | 9504.80 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 109.81 | 1006.80 | 27-MAY-05:00 | 9504.80 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 19.72 | 257.38 | 01-JAN-02:10 | 1438.51 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 19.72 | 257.35 | 01-JAN-02:10 | 1438.34 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 305.38 | 4267.82 | 01-JAN-02:10 | 22404.45 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 110.39 | 934.58 | 01-JAN-02:10 | 8496.21 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 110.39 | 934.58 | 01-JAN-02:10 | 8496.21 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 305.47 | 4268.99 | 01-JAN-02:10 | 22410.58 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 110.42 | 934.84 | 01-JAN-02:10 | 8498.53 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 110.42 | 934.84 | 01-JAN-02:10 | 8498.53 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 19.72 | 257.38 | 01-JAN-02:10 | 1438.51 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 19.72 | 257.35 | 01-JAN-02:10 | 1438.34 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 4.93 | 64.34 | 01-JAN-02:10 | 359.63 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 2.31 | 19.57 | 01-JAN-02:10 | 177.88 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 2.31 | 19.57 | 01-JAN-02:10 | 177.88 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 4.93 | 64.34 | 01-JAN-02:10 | 359.59 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 2.31 | 19.56 | 01-JAN-02:10 | 177.86 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 2.31 | 19.56 | 01-JAN-02:10 | 177.86 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 36.17 | 505.54 | 01-JAN-02:10 | 2653.88 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 13.08 | 110.70 | 01-JAN-02:10 | 1006.40 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 13.08 | 110.70 | 01-JAN-02:10 | 1006.40 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 206.60 | 2448.50 | 27-MAY-05:00 | 9735.93 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 30.75 | 199.20 | 27-MAY-05:00 | 2988.03 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 30.75 | 199.20 | 27-MAY-05:00 | 2988.03 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 206.60 | 2448.50 | 27-MAY-05:00 | 9735.93 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 30.75 | 199.20 | 27-MAY-05:00 | 2988.03 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 | 30.75 | 199.20 | 27-MAY-05:00 | 2988.03 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 453.81 | 6249.79 | 02-JAN-02:10 | 18934.39 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 12.97 | 117.87 | 02-JAN-02:10 | 1060.81 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 12.97 | 117.87 | 02-JAN-02:10 | 1060.81 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1658.18 | 24201.97 | 02-JAN-02:10 | 89171.45 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 1658.18 | 24201.97 | 02-JAN-02:10 | 89171.45 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 433.74 | 5990.78 | 01-JAN-00:10 | 16487.34 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 410.33 | 5248.28 | 01-JAN-00:10 | 15744.84 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
Refrigeration:Electricity | 61.36 | 1114.43 | 15-JUL-22:30 | 3259.72 | 28-JUL-06:20 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
Electricity:Plant | 808.48 | 2769.51 | 12-APR-02:20 | 158880.00 | 26-JUN-18:10 |
LowTempRefrigeration:Refrigeration:Electricity | 20.44 | 0.00 | 01-JAN-11:10 | 1894.61 | 05-AUG-10:50 |
MedTempRefrigeration:Refrigeration:Electricity | 33.82 | 954.48 | 22-DEC-04:10 | 1197.02 | 28-JUL-13:10 |
Fans:Electricity | 586.97 | 10647.24 | 19-DEC-11:10 | 60628.05 | 27-JUN-19:10 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 772.86 | 11274.11 | 30-APR-14:00 | 71808.09 | 27-JUN-19:10 |
ExteriorEquipment:Electricity | 813.77 | 9999.82 | 02-JAN-02:20 | 49607.07 | 02-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 21.77 | 380.98 | 10-JUN-05:00 | 1291.59 | 02-JAN-21:10 |
ElectricityPurchased:Facility | 5014.16 | 65523.65 | 20-MAY-04:50 | 365749.68 | 26-JUN-19:30 |
ElectricityPurchased:Plant | 5014.16 | 65523.65 | 20-MAY-04:50 | 365749.68 | 26-JUN-19:30 |
Cogeneration:ElectricityPurchased | 5014.16 | 65523.65 | 20-MAY-04:50 | 365749.68 | 26-JUN-19:30 |
General:Cogeneration:ElectricityPurchased | 5014.16 | 65523.65 | 20-MAY-04:50 | 365749.68 | 26-JUN-19:30 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 5014.16 | 65523.65 | 20-MAY-04:50 | 365749.68 | 26-JUN-19:30 |
ElectricityNet:Plant | 5014.16 | 65523.65 | 20-MAY-04:50 | 365749.68 | 26-JUN-19:30 |
Cogeneration:ElectricityNet | 5014.16 | 65523.65 | 20-MAY-04:50 | 365749.68 | 26-JUN-19:30 |
General:Cogeneration:ElectricityNet | 5014.16 | 65523.65 | 20-MAY-04:50 | 365749.68 | 26-JUN-19:30 |
General:Fans:Electricity | 586.97 | 10647.24 | 19-DEC-11:10 | 60628.05 | 27-JUN-19:10 |
ExteriorLights:Electricity | 193.79 | 0.00 | 01-JAN-07:30 | 12338.45 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 193.79 | 0.00 | 01-JAN-07:30 | 12338.45 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 789.09 | 9600.00 | 01-JAN-00:10 | 48128.80 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 2.91 | 18.80 | 01-JAN-00:10 | 188.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 164.13 | 0.00 | 01-JAN-11:40 | 9938.94 | 14-JUN-07:00 |
General:HeatRecovery:Electricity | 164.13 | 0.00 | 01-JAN-11:40 | 9938.94 | 14-JUN-07:00 |
WaterSystems:Electricity | 94.78 | 1222.48 | 12-JUL-01:30 | 4751.13 | 22-FEB-07:40 |
Water Heater:WaterSystems:Electricity | 94.78 | 1222.48 | 12-JUL-01:30 | 4751.13 | 22-FEB-07:40 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 588.43 | 0.00 | 01-JAN-03:10 | 147665.61 | 26-JUN-18:10 |
General:Cooling:Electricity | 588.43 | 0.00 | 01-JAN-03:10 | 147665.61 | 26-JUN-18:10 |
Pumps:Electricity | 71.00 | 47.91 | 30-JAN-15:20 | 5537.81 | 10-JUL-18:10 |
General:Pumps:Electricity | 71.00 | 47.91 | 30-JAN-15:20 | 5537.81 | 10-JUL-18:10 |
WIRED_LTG_ELECTRICITY | 27.52 | 0.00 | 01-JAN-00:10 | 2275.07 | 02-JAN-20:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 5776.13 | 25724.80 | 16-AUG-02:20 | 607509.47 | 21-DEC-19:30 |
NaturalGas:Building | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Laundry:InteriorEquipment:NaturalGas | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
NaturalGas:Plant | 3987.29 | 12362.90 | 16-AUG-02:20 | 519889.70 | 21-DEC-19:30 |
WaterSystems:NaturalGas | 2757.84 | 12362.90 | 16-AUG-02:20 | 262642.43 | 13-FEB-21:20 |
Water Heater:WaterSystems:NaturalGas | 2757.84 | 12362.90 | 16-AUG-02:20 | 262642.43 | 13-FEB-21:20 |
Heating:NaturalGas | 1229.45 | 0.00 | 01-JAN-09:00 | 293095.06 | 21-DEC-09:20 |
Boiler:Heating:NaturalGas | 1229.45 | 0.00 | 01-JAN-09:00 | 293095.06 | 21-DEC-09:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 2368.05 | 0.00 | 01-JAN-03:10 | 428614.54 | 26-JUN-18:10 |
PlantLoopCoolingDemand:HVAC | 2368.05 | 0.00 | 01-JAN-03:10 | 428614.54 | 26-JUN-18:10 |
CoolingCoils:PlantLoopCoolingDemand | 2368.05 | 0.00 | 01-JAN-03:10 | 428614.54 | 26-JUN-18:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 19-APR-20:50 |
Water:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 19-APR-20:50 |
WaterSystems:Water | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 19-APR-20:50 |
Water Heater:WaterSystems:Water | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:20 |
MainsWater:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 19-APR-20:50 |
MainsWater:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 19-APR-20:50 |
WaterSystems:MainsWater | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 19-APR-20:50 |
Water Heater:WaterSystems:MainsWater | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:20 |
WaterUse:WaterSystems:Water | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 16-MAY-07:00 |
WaterUse:WaterSystems:MainsWater | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 16-MAY-07:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 19015.67 | 139077.92 | 01-MAY-14:50 | 1856847.85 | 26-JUN-18:10 |
EnergyTransfer:Building | 5150.09 | 77282.76 | 06-FEB-11:10 | 332646.78 | 26-JUN-18:20 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 723.01 | 9469.29 | 22-DEC-04:00 | 36666.15 | 05-AUG-10:50 |
Refrigeration:EnergyTransfer | 179.73 | 4016.10 | 15-JUL-22:30 | 10348.21 | 28-JUL-06:20 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 89.87 | 2008.05 | 15-JUL-22:30 | 5174.11 | 28-JUL-06:20 |
General:Refrigeration:EnergyTransfer | 89.87 | 2008.05 | 15-JUL-22:30 | 5174.11 | 28-JUL-06:20 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 89.87 | 2008.05 | 15-JUL-22:30 | 5174.11 | 28-JUL-06:20 |
EnergyTransfer:Plant | 7159.37 | 16109.20 | 13-OCT-01:20 | 1044924.47 | 26-JUN-18:10 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 21.51 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 68.36 | 1813.43 | 22-DEC-04:10 | 2541.06 | 28-JUL-13:10 |
EnergyTransfer:Zone:BASEMENT | 389.08 | 9153.74 | 26-MAR-15:00 | 22662.71 | 20-OCT-21:00 |
Heating:EnergyTransfer | 128.63 | 0.00 | 01-JAN-08:10 | 88087.43 | 21-DEC-09:20 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 128.63 | 0.00 | 01-JAN-08:10 | 88087.43 | 21-DEC-09:20 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 4931.59 | 62656.54 | 20-DEC-15:00 | 329161.57 | 26-JUN-18:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 389.08 | 9153.74 | 26-MAR-15:00 | 22662.71 | 20-OCT-21:00 |
General:Cooling:EnergyTransfer | 4931.59 | 62656.54 | 20-DEC-15:00 | 329161.57 | 26-JUN-18:20 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 389.08 | 9153.74 | 26-MAR-15:00 | 22662.71 | 20-OCT-21:00 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 46.73 | 0.08 | 08-JAN-03:40 | 5013.20 | 07-NOV-12:40 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 1.09 | 0.00 | 01-JAN-00:10 | 1649.47 | 21-DEC-08:10 |
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 1.09 | 0.00 | 01-JAN-00:10 | 1649.47 | 21-DEC-08:10 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 45.64 | 0.00 | 03-JAN-07:10 | 5013.20 | 07-NOV-12:40 |
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 45.64 | 0.00 | 03-JAN-07:10 | 5013.20 | 07-NOV-12:40 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 33.55 | 174.73 | 21-DEC-10:10 | 2214.96 | 26-JUN-20:10 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 33.55 | 174.73 | 21-DEC-10:10 | 2214.96 | 26-JUN-20:10 |
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 33.55 | 174.73 | 21-DEC-10:10 | 2214.96 | 26-JUN-20:10 |
EnergyTransfer:Zone:MECH_FLR_1 | 22.64 | 0.49 | 07-FEB-01:10 | 1862.70 | 17-JUL-19:50 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.14 | 0.00 | 01-JAN-00:10 | 604.10 | 22-DEC-05:00 |
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.14 | 0.00 | 01-JAN-00:10 | 604.10 | 22-DEC-05:00 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 22.50 | 0.00 | 05-JAN-10:10 | 1862.70 | 17-JUL-19:50 |
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 22.50 | 0.00 | 05-JAN-10:10 | 1862.70 | 17-JUL-19:50 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 12.35 | 0.01 | 19-DEC-22:50 | 913.71 | 26-JUN-19:10 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.30 | 0.00 | 01-JAN-00:10 | 625.08 | 21-DEC-11:00 |
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.30 | 0.00 | 01-JAN-00:10 | 625.08 | 21-DEC-11:00 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 12.05 | 0.00 | 04-JAN-12:10 | 913.71 | 26-JUN-19:10 |
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 12.05 | 0.00 | 04-JAN-12:10 | 913.71 | 26-JUN-19:10 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 596.12 | 8953.83 | 22-DEC-05:00 | 39234.98 | 26-JUN-20:00 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 596.12 | 8953.83 | 22-DEC-05:00 | 39234.98 | 26-JUN-20:00 |
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 596.12 | 8953.83 | 22-DEC-05:00 | 39234.98 | 26-JUN-20:00 |
EnergyTransfer:Zone:CAFE_FLR_1 | 241.24 | 3.12 | 31-OCT-10:40 | 17898.41 | 18-FEB-13:10 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.04 | 0.00 | 01-JAN-00:10 | 2441.05 | 21-DEC-09:30 |
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.04 | 0.00 | 01-JAN-00:10 | 2441.05 | 21-DEC-09:30 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 241.20 | 0.00 | 05-JAN-09:10 | 17898.41 | 18-FEB-13:10 |
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 241.20 | 0.00 | 05-JAN-09:10 | 17898.41 | 18-FEB-13:10 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 770.39 | 7977.23 | 21-DEC-09:30 | 42505.03 | 16-AUG-20:10 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 770.39 | 7977.23 | 21-DEC-09:30 | 42505.03 | 16-AUG-20:10 |
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 770.39 | 7977.23 | 21-DEC-09:30 | 42505.03 | 16-AUG-20:10 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 68.48 | 0.00 | 01-JAN-08:10 | 10404.62 | 28-SEP-15:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 12.46 | 0.00 | 01-JAN-08:10 | 6818.29 | 21-DEC-09:20 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 12.46 | 0.00 | 01-JAN-08:10 | 6818.29 | 21-DEC-09:20 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 56.02 | 0.00 | 01-JAN-00:10 | 10404.62 | 28-SEP-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 56.02 | 0.00 | 01-JAN-00:10 | 10404.62 | 28-SEP-15:10 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 55.53 | 0.00 | 01-JAN-08:10 | 10235.90 | 01-JUL-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 17.55 | 0.00 | 01-JAN-08:10 | 6800.49 | 20-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 17.55 | 0.00 | 01-JAN-08:10 | 6800.49 | 20-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 37.98 | 0.00 | 01-JAN-00:10 | 10235.90 | 01-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 37.98 | 0.00 | 01-JAN-00:10 | 10235.90 | 01-JUL-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 388.21 | 0.00 | 01-JAN-00:50 | 65434.73 | 20-JAN-12:40 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 388.21 | 0.00 | 01-JAN-00:50 | 65434.73 | 20-JAN-12:40 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 388.21 | 0.00 | 01-JAN-00:50 | 65434.73 | 20-JAN-12:40 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 354.62 | 0.00 | 01-JAN-08:10 | 61876.98 | 01-JUL-08:10 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 39.09 | 0.00 | 01-JAN-08:10 | 37237.49 | 21-DEC-16:30 |
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 39.09 | 0.00 | 01-JAN-08:10 | 37237.49 | 21-DEC-16:30 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 315.52 | 0.00 | 01-JAN-00:10 | 61876.98 | 01-JUL-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 315.52 | 0.00 | 01-JAN-00:10 | 61876.98 | 01-JUL-08:10 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 72.52 | 0.00 | 01-JAN-08:10 | 9408.47 | 01-JUL-08:10 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 12.84 | 0.00 | 01-JAN-07:50 | 6621.38 | 20-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 12.84 | 0.00 | 01-JAN-07:50 | 6621.38 | 20-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 59.68 | 0.00 | 01-JAN-00:10 | 9408.47 | 01-JUL-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 59.68 | 0.00 | 01-JAN-00:10 | 9408.47 | 01-JUL-08:10 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 59.30 | 0.00 | 01-JAN-08:10 | 10223.48 | 01-JUL-08:10 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 17.93 | 0.00 | 01-JAN-08:10 | 6714.80 | 21-DEC-16:30 |
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 17.93 | 0.00 | 01-JAN-08:10 | 6714.80 | 21-DEC-16:30 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 41.37 | 0.00 | 01-JAN-00:10 | 10223.48 | 01-JUL-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 41.37 | 0.00 | 01-JAN-00:10 | 10223.48 | 01-JUL-08:10 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 180.70 | 2.39 | 12-FEB-05:40 | 13059.39 | 26-JUN-18:30 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.75 | 0.00 | 01-JAN-00:10 | 4826.27 | 21-DEC-09:20 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.75 | 0.00 | 01-JAN-00:10 | 4826.27 | 21-DEC-09:20 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 179.95 | 0.00 | 05-JAN-07:10 | 13059.39 | 26-JUN-18:30 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 179.95 | 0.00 | 05-JAN-07:10 | 13059.39 | 26-JUN-18:30 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 18.82 | 0.00 | 01-JAN-08:10 | 2774.09 | 28-SEP-15:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 5.28 | 0.00 | 01-JAN-08:10 | 2073.20 | 21-DEC-09:20 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 5.28 | 0.00 | 01-JAN-08:10 | 2073.20 | 21-DEC-09:20 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 13.54 | 0.00 | 01-JAN-00:10 | 2774.09 | 28-SEP-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 13.54 | 0.00 | 01-JAN-00:10 | 2774.09 | 28-SEP-15:10 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 16.43 | 0.00 | 01-JAN-08:10 | 2732.65 | 27-JUN-16:30 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 7.10 | 0.00 | 01-JAN-08:10 | 2067.89 | 20-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 7.10 | 0.00 | 01-JAN-08:10 | 2067.89 | 20-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 9.33 | 0.00 | 01-JAN-00:10 | 2732.65 | 27-JUN-16:30 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 9.33 | 0.00 | 01-JAN-00:10 | 2732.65 | 27-JUN-16:30 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 112.11 | 0.00 | 01-JAN-08:10 | 13605.02 | 18-FEB-13:40 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 12.53 | 0.00 | 01-JAN-00:10 | 9577.50 | 20-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 12.53 | 0.00 | 01-JAN-00:10 | 9577.50 | 20-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 99.57 | 0.00 | 01-JAN-02:40 | 13605.02 | 18-FEB-13:40 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 99.57 | 0.00 | 01-JAN-02:40 | 13605.02 | 18-FEB-13:40 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 428.53 | 6742.88 | 20-DEC-15:00 | 23350.14 | 26-JUN-21:20 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 428.53 | 6742.88 | 20-DEC-15:00 | 23350.14 | 26-JUN-21:20 |
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 428.53 | 6742.88 | 20-DEC-15:00 | 23350.14 | 26-JUN-21:20 |
EnergyTransfer:Zone:DINING_FLR_6 | 468.17 | 7628.45 | 20-DEC-15:00 | 24545.07 | 26-JUN-21:20 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 468.17 | 7628.45 | 20-DEC-15:00 | 24545.07 | 26-JUN-21:20 |
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 468.17 | 7628.45 | 20-DEC-15:00 | 24545.07 | 26-JUN-21:20 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 633.14 | 7413.13 | 22-DEC-04:00 | 31621.31 | 05-AUG-10:50 |
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 633.14 | 7413.13 | 22-DEC-04:00 | 31621.31 | 05-AUG-10:50 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 91.57 | 0.02 | 11-FEB-23:10 | 7201.49 | 16-AUG-15:10 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 1.53 | 0.00 | 01-JAN-00:10 | 3463.45 | 22-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 1.53 | 0.00 | 01-JAN-00:10 | 3463.45 | 22-DEC-07:10 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 90.05 | 0.00 | 03-JAN-07:10 | 7201.49 | 16-AUG-15:10 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 90.05 | 0.00 | 03-JAN-07:10 | 7201.49 | 16-AUG-15:10 |
PlantLoopHeatingDemand:Facility | 1641.34 | 9706.06 | 15-AUG-00:20 | 270745.27 | 21-DEC-09:10 |
PlantLoopHeatingDemand:Plant | 803.47 | 9706.06 | 15-AUG-00:20 | 59313.31 | 13-FEB-07:10 |
WaterSystems:PlantLoopHeatingDemand | 803.47 | 9706.06 | 15-AUG-00:20 | 59313.31 | 13-FEB-07:10 |
General:WaterSystems:PlantLoopHeatingDemand | 803.47 | 9706.06 | 15-AUG-00:20 | 59313.31 | 13-FEB-07:10 |
EnergyTransfer:HVAC | 6706.21 | 1501.18 | 01-MAY-14:50 | 737952.87 | 21-DEC-20:00 |
HeatingCoils:EnergyTransfer | 837.87 | 0.00 | 01-JAN-09:00 | 237958.96 | 21-DEC-09:10 |
PlantLoopHeatingDemand:HVAC | 837.87 | 0.00 | 01-JAN-09:00 | 237958.96 | 21-DEC-09:10 |
HeatingCoils:PlantLoopHeatingDemand | 837.87 | 0.00 | 01-JAN-09:00 | 237958.96 | 21-DEC-09:10 |
CoolingCoils:EnergyTransfer | 2368.05 | 0.00 | 01-JAN-03:10 | 428614.54 | 26-JUN-18:10 |
HeatRecoveryForHeating:EnergyTransfer | 3436.79 | 0.00 | 01-JAN-11:40 | 518612.32 | 21-DEC-20:10 |
HeatRecoveryForCooling:EnergyTransfer | 63.50 | 0.00 | 01-JAN-00:10 | 150150.65 | 16-AUG-14:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 803.47 | 9706.06 | 15-AUG-00:20 | 59313.31 | 13-FEB-07:10 |
WaterUse:WaterSystems:EnergyTransfer | 803.47 | 9706.06 | 15-AUG-00:20 | 59313.31 | 13-FEB-07:10 |
Boilers:EnergyTransfer | 831.19 | 0.00 | 01-JAN-09:00 | 235805.85 | 21-DEC-09:20 |
Chillers:EnergyTransfer | 2423.20 | 0.00 | 01-JAN-03:10 | 430836.17 | 26-JUN-18:10 |
HeatRejection:EnergyTransfer | 3011.63 | 0.00 | 01-JAN-03:10 | 578501.78 | 26-JUN-18:10 |
General:HeatRejection:EnergyTransfer | 3011.63 | 0.00 | 01-JAN-03:10 | 578501.78 | 26-JUN-18:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:04
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -389.081 | 0.000 | 0.000 | 135.366 | 161.294 | 143.105 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -50.684 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 1.089 | -45.642 | 0.000 | 0.000 | 15.070 | 7.307 | 10.186 | 34.432 | 0.000 | 0.072 | 0.001 | 0.000 | -13.098 | 0.000 | -1.906 | -7.510 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.000 | -33.554 | 0.000 | 0.000 | 16.313 | 8.462 | 11.795 | 0.000 | 0.000 | 0.028 | 0.000 | 0.000 | 0.000 | 0.000 | -0.783 | -2.261 |
MECH_FLR_1 | 0.000 | 0.000 | 0.137 | -22.499 | 0.000 | 0.000 | 3.611 | 8.366 | 12.471 | 0.000 | 0.000 | 0.067 | 0.000 | 0.000 | 0.000 | 0.000 | -1.758 | -0.395 |
STORAGE_FLR_1 | 0.000 | 0.000 | 0.301 | -12.048 | 0.000 | 0.000 | 2.824 | 3.079 | 3.598 | 0.000 | 0.000 | 0.039 | 3.201 | 0.000 | 0.000 | 0.000 | -0.995 | -0.000 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.000 | -596.126 | 0.000 | 0.000 | 10.888 | 3.975 | 658.131 | 0.000 | 0.000 | 0.092 | 0.000 | 0.000 | 0.000 | 0.000 | -2.577 | -74.383 |
CAFE_FLR_1 | 0.000 | 0.000 | 0.036 | -241.204 | 0.000 | 0.000 | 184.762 | 14.027 | 14.341 | 95.905 | 0.000 | 0.158 | 0.001 | 0.000 | -39.026 | 0.000 | -4.502 | -24.498 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.000 | -770.393 | 0.000 | 0.000 | 539.451 | 109.807 | 148.998 | 126.805 | 0.000 | 0.456 | 0.000 | 0.000 | -52.317 | 0.000 | -13.084 | -89.724 |
ROOM_1_FLR_3 | 15.252 | -49.632 | 0.000 | -9.173 | 0.000 | 0.000 | 9.681 | 9.244 | 10.478 | 61.070 | 0.000 | 0.289 | 0.000 | 0.000 | -28.825 | 0.000 | -4.730 | -13.655 |
ROOM_2_FLR_3 | 20.998 | -31.816 | 0.000 | -9.606 | 0.000 | 0.000 | 9.559 | 9.243 | 10.477 | 40.033 | 0.000 | 0.229 | 0.000 | 0.000 | -29.834 | 0.000 | -5.114 | -14.168 |
ROOM_3_MULT19_FLR_3 | 0.000 | -375.443 | 0.000 | -12.759 | 0.000 | 0.000 | 0.000 | 110.385 | 194.997 | 395.572 | 0.000 | 0.434 | 0.018 | 0.000 | -199.254 | 0.000 | -29.075 | -84.857 |
ROOM_4_MULT19_FLR_3 | 69.434 | -218.403 | 0.000 | -127.455 | 0.000 | 0.000 | 182.807 | 110.415 | 195.050 | 97.063 | 0.000 | 1.445 | 0.000 | 0.000 | -164.882 | 0.000 | -37.224 | -108.251 |
ROOM_5_FLR_3 | 15.617 | -53.284 | 0.000 | -9.178 | 0.000 | 0.000 | 9.676 | 9.244 | 10.478 | 64.073 | 0.000 | 0.292 | 0.001 | 0.000 | -28.391 | 0.000 | -4.750 | -13.778 |
ROOM_6_FLR_3 | 21.310 | -35.136 | 0.000 | -9.613 | 0.000 | 0.000 | 9.565 | 9.243 | 10.477 | 42.741 | 0.000 | 0.228 | 0.000 | 0.000 | -29.143 | 0.000 | -5.159 | -14.513 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 0.749 | -179.950 | 0.000 | 0.000 | 115.225 | 91.336 | 0.000 | 57.074 | 0.000 | 0.204 | 0.002 | 0.000 | -37.733 | 0.000 | -5.370 | -41.535 |
ROOM_1_FLR_6 | 6.128 | -12.094 | 0.000 | -2.293 | 0.000 | 0.000 | 2.423 | 2.311 | 2.620 | 15.193 | 0.000 | 0.074 | 0.000 | 0.000 | -7.154 | 0.000 | -1.206 | -6.001 |
ROOM_2_FLR_6 | 8.063 | -7.890 | 0.000 | -2.402 | 0.000 | 0.000 | 2.391 | 2.311 | 2.619 | 9.964 | 0.000 | 0.057 | 0.000 | 0.000 | -7.407 | 0.000 | -1.293 | -6.413 |
ROOM_3_MULT9_FLR_6 | 15.912 | -88.170 | 0.000 | -14.778 | 0.000 | 0.000 | 21.737 | 13.076 | 23.098 | 90.418 | 0.000 | 0.422 | 0.000 | 0.000 | -33.594 | 0.000 | -6.310 | -21.811 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.000 | -428.531 | 0.000 | 0.000 | 315.102 | 30.748 | 175.857 | 9.851 | 0.000 | 0.098 | 0.000 | 0.000 | -22.264 | 0.000 | -3.000 | -77.861 |
DINING_FLR_6 | 0.000 | 0.000 | 0.000 | -468.172 | 0.000 | 0.000 | 314.478 | 30.748 | 175.857 | 9.680 | 0.000 | 0.098 | 0.000 | 0.000 | -22.743 | 0.000 | -3.013 | -36.933 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.000 | -633.127 | 0.000 | 0.000 | 28.061 | 12.972 | 550.372 | 29.009 | 0.000 | 0.087 | 30.654 | 0.000 | -15.330 | 0.000 | -2.699 | -0.000 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 1.526 | -90.049 | 0.000 | 0.000 | 30.793 | 24.166 | 0.000 | 28.469 | 0.000 | 0.086 | 24.166 | 0.000 | -16.794 | 0.000 | -2.364 | -0.000 |
Total Facility | 172.713 | -871.867 | 3.838 | -4107.637 | 0.000 | 0.000 | 1959.782 | 781.761 | 2365.005 | 1207.353 | 0.000 | 4.957 | 58.045 | 0.000 | -747.788 | 0.000 | -136.910 | -689.228 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 20-OCT-21:00 | 0.00 | 0.00 | 0.00 | -22662.48 | 0.00 | 0.00 | 5924.48 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4112.21 |
RETAIL_1_FLR_1 | 07-NOV-12:40 | 0.00 | 0.00 | 0.00 | -5012.39 | 0.00 | 0.00 | 148.49 | 166.00 | 252.59 | 7607.08 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -18.56 | -3143.22 |
RETAIL_2_FLR_1 | 26-JUN-20:10 | 0.00 | 0.00 | 0.00 | -2215.24 | 0.00 | 0.00 | 697.60 | 615.12 | 752.15 | 0.00 | 0.00 | 13.09 | 137.28 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 17-JUL-19:50 | 0.00 | 0.00 | 0.00 | -1863.07 | 0.00 | 0.00 | 128.84 | 684.18 | 839.45 | 0.00 | 0.00 | 23.90 | 186.70 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 26-JUN-19:10 | 0.00 | 0.00 | 0.00 | -913.82 | 0.00 | 0.00 | 99.29 | 251.84 | 242.16 | 0.00 | 0.00 | 24.25 | 296.27 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 26-JUN-20:00 | 0.00 | 0.00 | 0.00 | -39238.52 | 0.00 | 0.00 | 408.86 | 325.08 | 44299.38 | 0.00 | 0.00 | 45.56 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5840.35 |
CAFE_FLR_1 | 18-FEB-13:10 | 0.00 | 0.00 | 0.00 | -17898.46 | 0.00 | 0.00 | 2968.78 | 103.98 | 355.63 | 20996.65 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -38.78 | -6487.80 |
LOBBY_FLR_1 | 16-AUG-21:10 | 0.00 | 0.00 | 0.00 | -42508.64 | 0.00 | 0.00 | 26440.63 | 6336.53 | 7389.94 | 0.00 | 0.00 | 45.21 | 2464.02 | 0.00 | -167.70 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 28-SEP-15:02 | 0.00 | -10163.52 | 0.00 | -628.41 | 0.00 | 0.00 | 235.27 | 199.23 | 200.18 | 12747.79 | 0.00 | 63.43 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2653.98 |
ROOM_2_FLR_3 | 08-APR-18:01 | 0.00 | -11090.88 | 0.00 | -595.32 | 0.00 | 0.00 | 233.87 | 711.45 | 484.60 | 1942.42 | 0.00 | 0.00 | 8435.34 | 0.00 | -0.00 | 0.00 | -121.47 | 0.00 |
ROOM_3_MULT19_FLR_3 | 20-JAN-12:40 | 0.00 | -65434.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2378.94 | 2352.88 | 96501.47 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -325.60 | -35473.49 |
ROOM_4_MULT19_FLR_3 | 01-JUL-08:61 | 0.00 | -59991.32 | 0.00 | -9820.35 | 0.00 | 0.00 | 2207.40 | 4759.18 | 12159.85 | 9097.50 | 0.00 | 69.15 | 41518.60 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 01-JUL-08:61 | 0.00 | -9127.15 | 0.00 | -635.76 | 0.00 | 0.00 | 130.71 | 398.46 | 653.23 | 11297.63 | 0.00 | 27.58 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2744.71 |
ROOM_6_FLR_3 | 27-JUN-08:32 | 0.00 | -10737.64 | 0.00 | -873.21 | 0.00 | 0.00 | 58.86 | 313.04 | 452.99 | 9516.47 | 0.00 | 0.00 | 1294.26 | 0.00 | -0.00 | 0.00 | -24.79 | 0.00 |
CORRIDOR_FLR_3 | 26-JUN-18:30 | 0.00 | 0.00 | 0.00 | -13060.08 | 0.00 | 0.00 | 4080.25 | 6639.35 | 0.00 | 3470.27 | 0.00 | 146.61 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1276.40 |
ROOM_1_FLR_6 | 28-SEP-15:02 | 0.00 | -2707.02 | 0.00 | -157.46 | 0.00 | 0.00 | 58.82 | 49.81 | 50.05 | 3172.67 | 0.00 | 15.66 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -482.52 |
ROOM_2_FLR_6 | 08-APR-17:42 | 0.00 | -3120.79 | 0.00 | 0.00 | 0.00 | 0.00 | 39.76 | 151.18 | 126.42 | 1229.74 | 0.00 | 0.00 | 1605.98 | 0.00 | -0.00 | 0.00 | -32.29 | 0.00 |
ROOM_3_MULT9_FLR_6 | 18-FEB-13:33 | 0.00 | -12799.19 | 0.00 | -1076.63 | 0.00 | 0.00 | 269.82 | 332.11 | 301.93 | 18084.47 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -50.37 | -5062.13 |
BANQUET_FLR_6 | 26-JUN-21:20 | 0.00 | 0.00 | 0.00 | -23352.42 | 0.00 | 0.00 | 15610.38 | 1992.02 | 6747.90 | 1.28 | 0.00 | 20.70 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1019.86 |
DINING_FLR_6 | 26-JUN-21:20 | 0.00 | 0.00 | 0.00 | -24547.62 | 0.00 | 0.00 | 15600.16 | 1992.02 | 6747.90 | 0.00 | 0.00 | 20.68 | 197.87 | 0.00 | -11.01 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 05-AUG-10:40 | 0.00 | 0.00 | 0.00 | -31627.24 | 0.00 | 0.00 | 464.26 | 294.67 | 24259.91 | 3749.69 | 0.00 | 25.97 | 2832.75 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 16-AUG-15:02 | 0.00 | 0.00 | 0.00 | -7205.19 | 0.00 | 0.00 | 771.11 | 548.96 | 0.00 | 2361.64 | 0.00 | 62.40 | 3461.07 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 24-JUL-18:02 | 0.00 | -128401.61 | 0.00 | -202721.15 | 0.00 | 0.00 | 73774.73 | 53578.21 | 120482.43 | 37074.40 | 0.00 | 1467.48 | 44745.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 21-DEC-08:10 | 0.00 | 0.00 | 1657.01 | 0.00 | 0.00 | 0.00 | 366.74 | 265.60 | 360.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1981.38 | 0.00 | -201.99 | -466.82 |
RETAIL_2_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 22-DEC-05:00 | 0.00 | 0.00 | 604.13 | 0.00 | 0.00 | 0.00 | 197.30 | 76.02 | 176.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -192.95 | -861.21 |
STORAGE_FLR_1 | 21-DEC-11:00 | 0.00 | 0.00 | 625.03 | 0.00 | 0.00 | 0.00 | 33.72 | 69.95 | 89.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -102.28 | -715.64 |
LAUNDRY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 21-DEC-09:25 | 0.00 | 0.00 | 2440.99 | 0.00 | 0.00 | 0.00 | 2352.03 | 264.68 | 508.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3965.19 | 0.00 | -454.36 | -1146.18 |
LOBBY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 21-DEC-09:13 | 7039.34 | 297.48 | 0.00 | -297.48 | 0.00 | 0.00 | 99.53 | 313.07 | 453.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3279.78 | 0.00 | -470.08 | -4155.13 |
ROOM_2_FLR_3 | 20-DEC-16:13 | 7016.11 | 296.48 | 0.00 | -296.48 | 0.00 | 0.00 | 268.60 | 199.20 | 200.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3278.86 | 0.00 | -433.11 | -3972.10 |
ROOM_3_MULT19_FLR_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 21-DEC-16:13 | 38110.45 | 3746.59 | 0.00 | -3746.59 | 0.00 | 0.00 | 5175.23 | 2379.59 | 3726.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -19066.10 | 0.00 | -2388.79 | -27936.78 |
ROOM_5_FLR_3 | 20-DEC-16:13 | 6815.64 | 292.44 | 0.00 | -292.44 | 0.00 | 0.00 | 269.94 | 199.23 | 200.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3433.34 | 0.00 | -432.38 | -3619.27 |
ROOM_6_FLR_3 | 21-DEC-16:13 | 6835.28 | 284.98 | 0.00 | -284.98 | 0.00 | 0.00 | 271.54 | 199.20 | 200.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3521.35 | 0.00 | -452.06 | -3532.78 |
CORRIDOR_FLR_3 | 21-DEC-09:13 | 0.00 | 0.00 | 4826.51 | 0.00 | 0.00 | 0.00 | 1385.78 | 3319.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4207.24 | 0.00 | -577.51 | -4747.21 |
ROOM_1_FLR_6 | 21-DEC-09:13 | 2123.89 | 71.98 | 0.00 | -71.98 | 0.00 | 0.00 | 25.16 | 78.27 | 113.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -817.94 | 0.00 | -117.26 | -1405.38 |
ROOM_2_FLR_6 | 21-DEC-19:13 | 2115.51 | 72.22 | 0.00 | -72.22 | 0.00 | 0.00 | 96.47 | 158.30 | 121.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1010.19 | 0.00 | -119.11 | -1362.13 |
ROOM_3_MULT9_FLR_6 | 20-DEC-16:13 | 9830.86 | 470.47 | 0.00 | -470.47 | 0.00 | 0.00 | 605.76 | 281.79 | 441.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3851.99 | 0.00 | -498.72 | -6808.99 |
BANQUET_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 21-DEC-08:02 | 0.00 | 0.00 | 3485.56 | 0.00 | 0.00 | 0.00 | 733.24 | 878.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2542.44 | 0.00 | -255.26 | -2299.44 |
Total Facility | 21-DEC-09:13 | 9651.10 | 74824.89 | 13291.24 | -74824.89 | 0.00 | 0.00 | 23817.49 | 27037.32 | 88178.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -76703.60 | 0.00 | -11827.69 | -73444.78 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:04
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV WITH REHEAT | 26.9657 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 26.8111 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV WITH REHEAT | 13.4829 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 11.6492 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.6520 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.0400 | 0.000610 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.000000 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.000000 | 142.3000 | 0.003581 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.000000 | 422.4350 | 0.001448 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 83.8280 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003556 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.1800 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 | |
VAV WITH REHEAT | 0.00 | 0.001045 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.9619 | 2.9619 | 1.2795 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4450 | 0.4450 | 0.1922 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2791 | 0.2791 | 0.1206 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2204 | 0.2204 | 0.0952 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1331 | 0.1331 | 0.0575 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.0042 | 4.0042 | 1.7298 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8727 | 1.8727 | 0.8090 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.9277 | 5.9277 | 2.5607 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8778 | 1.8778 | 0.8112 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6768 | 2.6768 | 1.1564 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8044 | 2.8044 | 1.2115 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.7826 | 2.7826 | 1.2021 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9800 | 0.9800 | 0.4234 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
VAV WITH REHEAT | 26.9657 | 26.8111 | 26.9657 | 11.6492 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4809 | 1.4809 | 1.2795 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2225 | 0.2225 | 0.1922 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1396 | 0.1396 | 0.1206 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1102 | 0.1102 | 0.0952 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0666 | 0.0666 | 0.0575 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.0021 | 2.0021 | 1.7298 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9364 | 0.9364 | 0.8090 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.9638 | 2.9638 | 2.5607 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9389 | 0.9389 | 0.8112 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3384 | 1.3384 | 1.1564 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4022 | 1.4022 | 1.2115 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3913 | 1.3913 | 1.2021 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4900 | 0.4900 | 0.4234 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
VAV WITH REHEAT | 13.4829 | 11.6492 | 11.6492 | 11.6492 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:04
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 168.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 168.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 6.00 |
Number of hours cooling loads not met | 510.50 |
Number of hours not met | 516.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 1229.45 | 293095.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 588.43 | 147665.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 781.76 | 64632.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 193.79 | 12338.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 872.72 | 59188.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 14.43 | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 8.99 | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.20 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 21.77 | 1291.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 789.09 | 48128.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 2.91 | 188.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 586.97 | 60628.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 71.00 | 5537.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 164.13 | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 94.78 | 4751.13 | 2757.84 | 262642.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.09 | 2093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 20.44 | 1894.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 33.82 | 1197.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1719.53 | 5014.16 |
Natural Gas | 1788.84 | 5776.13 |
Additional | 0.00 | 0.00 |
Total | 3508.37 | 10790.29 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 68.91 |
Space Heating | 0.00 |
Space Cooling | 51.87 |
Fans (All) | 51.74 |
Service Water Heating | 8.35 |
Receptacle Equipment | 146.16 |
Miscellaneous (All) | 441.96 |
Subtotal | 441.96 |
Natural Gas [MJ/m2] | |
Space Heating | 108.37 |
Service Water Heating | 243.08 |
Miscellaneous (All) | 509.12 |
Subtotal | 509.12 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 7.25 |
Space Heating | 11.39 |
Space Cooling | 5.45 |
Fans (All) | 5.44 |
Service Water Heating | 26.44 |
Receptacle Equipment | 31.95 |
Miscellaneous | 12.09 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 486. | 5110. |
ELEVATOR_STANDBY_SCH | 7671. | 8760. |
LTG_SCH_KITCHEN | 3061. | 8760. |
LTG_SCH_DINING | 3061. | 8760. |
LTG_SCH_BASEMENT | 2572. | 8760. |
LTG_SCH_LOBBY | 2295. | 8760. |
LTG_SCH_STORAGE | 1580. | 8760. |
LTG_SCH_MECHANIC | 3061. | 8760. |
LTG_SCH_LAUNDRY | 3061. | 8760. |
LTG_SCH_GUESTROOM | 1980. | 8760. |
LTG_SCH_CORRIDOR | 2295. | 8760. |
LTG_SCH_RETAIL | 2678. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 1591. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3737. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 5740. | 6205. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 8760. | 8760. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 26.67 | 365 | 26.67 | 365 |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
HTGSETP_SCH | BASEMENT DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:04
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8741.17 | 18.83 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8579.17 | 180.83 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8702.33 | 57.67 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8719.67 | 40.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8579.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 180.83 | 0.00 | 0.00 | 0.00 |
Average | 8746.47 | 13.53 | 0.00 | 0.00 | 0.00 |
Sum | 192422.33 | 297.67 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4151.17 | 2.83 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4144.50 | 9.50 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108269.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 9.50 | 0.00 | 0.00 | 0.00 |
Average | 288886.48 | 0.56 | 0.00 | 0.00 | 0.00 |
Sum | 6355502.67 | 12.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8686.00 | 74.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8719.67 | 40.33 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8720.67 | 39.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8435.67 | 324.33 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8758.83 | 1.17 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8684.17 | 75.83 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8704.83 | 55.17 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8713.67 | 46.33 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8725.67 | 34.33 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8759.83 | 0.17 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8435.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 324.33 | 0.00 | 0.00 | 0.00 |
Average | 8728.59 | 31.41 | 0.00 | 0.00 | 0.00 |
Sum | 192029.00 | 691.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 701407.67 | 9009.33 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2100782.17 | 14646.83 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4138.50 | 15.50 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4153.83 | 0.17 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4144.50 | 9.50 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4128.00 | 26.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1235686.33 | 10028.67 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1238324.33 | 7390.67 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108268.33 | 0.67 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2100782.17 | 14646.83 | 0.00 | 0.00 | 0.00 |
Average | 287017.62 | 1869.42 | 0.00 | 0.00 | 0.00 |
Sum | 6314387.67 | 41127.33 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:04
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:04
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 1592.73 | 0.00 | 0.00 |
Sum | 0.00 | 35040.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 710417.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 2115429.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 2115429.00 | 0.00 | 0.00 |
Average | 0.00 | 241694.36 | 0.00 | 0.00 |
Sum | 0.00 | 5317276.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5B
For: Environment
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Environment
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CO_DENVER
For: Environment
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.310629E+11 | 17984.69 | 26-JAN-22:00 | 4.00 | 2.09 | 0.815770E+10 | 4837.05 | 18-JAN-22:19 | 4.00 | 2.09 |
February | 0.262661E+11 | 16525.81 | 01-FEB-22:00 | -8.0 | -8.0 | 0.727643E+10 | 4836.97 | 22-FEB-22:19 | 2.67 | 2.34 |
March | 0.277399E+11 | 15086.89 | 01-MAR-22:00 | -4.0 | -4.0 | 0.791706E+10 | 4837.07 | 14-MAR-21:10 | 13.00 | 3.83 |
April | 0.270887E+11 | 14111.67 | 14-APR-21:00 | 1.00 | -0.9 | 0.768304E+10 | 4837.03 | 20-APR-21:10 | 14.00 | 7.96 |
May | 0.283405E+11 | 13526.39 | 19-MAY-21:00 | 10.00 | 6.74 | 0.791185E+10 | 4837.12 | 30-MAY-21:10 | 14.00 | 11.46 |
June | 0.299299E+11 | 16458.28 | 16-JUN-21:00 | 21.60 | 14.78 | 0.782882E+10 | 4837.45 | 07-JUN-21:10 | 21.60 | 14.78 |
July | 0.315460E+11 | 17198.72 | 28-JUL-21:00 | 16.00 | 15.35 | 0.810797E+10 | 4837.13 | 15-JUL-00:10 | 16.00 | 15.35 |
August | 0.353670E+11 | 19909.34 | 18-AUG-21:00 | 19.00 | 9.02 | 0.822566E+10 | 4837.47 | 24-AUG-02:09 | 18.67 | 15.36 |
September | 0.383930E+11 | 22598.79 | 15-SEP-21:00 | 12.20 | 6.07 | 0.797104E+10 | 4837.69 | 01-SEP-01:10 | 12.20 | 6.07 |
October | 0.394564E+11 | 22662.71 | 20-OCT-21:00 | 10.00 | 1.41 | 0.823277E+10 | 4837.21 | 27-OCT-01:10 | 5.00 | 5.00 |
November | 0.374352E+11 | 22342.52 | 09-NOV-22:00 | 8.00 | 6.33 | 0.795982E+10 | 4837.11 | 09-NOV-02:20 | 8.00 | 6.33 |
December | 0.364530E+11 | 21442.92 | 05-DEC-22:00 | -4.0 | -4.0 | 0.822360E+10 | 4837.07 | 29-DEC-02:20 | 5.00 | 0.56 |
Annual Sum or Average | 0.389079E+12 | 0.954958E+11 | ||||||||
Minimum of Months | 0.262661E+11 | 13526.39 | -8.0 | -8.0 | 0.727643E+10 | 4836.97 | 2.67 | 0.56 | ||
Maximum of Months | 0.394564E+11 | 22662.71 | 21.60 | 15.35 | 0.823277E+10 | 4837.69 | 21.60 | 15.36 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.360316E+10 | 4982.72 | 20-JAN-13:10 | 21.00 | 6.97 | 0.671431E+09 | 460.95 | 20-JAN-22:19 | 7.67 | 1.92 |
February | 0.296759E+10 | 4964.26 | 18-FEB-13:20 | 20.00 | 7.74 | 0.606411E+09 | 449.18 | 17-FEB-22:30 | 20.00 | 7.74 |
March | 0.316948E+10 | 4646.75 | 14-MAR-12:40 | 23.33 | 7.71 | 0.683454E+09 | 487.46 | 15-MAR-21:30 | 12.50 | 3.03 |
April | 0.247357E+10 | 3310.75 | 07-APR-12:30 | 20.50 | 8.13 | 0.640620E+09 | 464.25 | 07-APR-21:30 | 11.50 | 6.33 |
May | 0.359507E+10 | 2422.70 | 05-MAY-13:00 | 22.00 | 10.96 | 0.699766E+09 | 473.94 | 31-MAY-21:30 | 17.65 | 11.72 |
June | 0.451655E+10 | 3000.77 | 26-JUN-12:40 | 36.43 | 15.33 | 0.759752E+09 | 491.88 | 07-JUN-21:10 | 36.43 | 15.33 |
July | 0.471897E+10 | 3267.25 | 23-JUL-12:00 | 32.00 | 15.97 | 0.784862E+09 | 491.84 | 12-JUL-22:10 | 32.00 | 15.97 |
August | 0.509176E+10 | 3998.05 | 31-AUG-12:40 | 30.00 | 12.25 | 0.789148E+09 | 491.87 | 25-AUG-22:10 | 30.00 | 12.25 |
September | 0.496429E+10 | 4883.46 | 28-SEP-12:50 | 30.42 | 11.32 | 0.749733E+09 | 491.84 | 08-SEP-22:10 | 30.42 | 11.32 |
October | 0.398309E+10 | 4932.14 | 10-OCT-12:40 | 23.67 | 7.92 | 0.703594E+09 | 491.82 | 10-OCT-21:40 | 13.33 | 4.26 |
November | 0.364188E+10 | 5013.20 | 07-NOV-12:40 | 20.00 | 7.20 | 0.658098E+09 | 463.72 | 07-NOV-22:30 | 7.00 | 2.01 |
December | 0.291673E+10 | 4711.96 | 17-DEC-13:00 | 18.00 | 5.78 | 0.657381E+09 | 429.75 | 01-DEC-22:30 | 18.00 | 5.78 |
Annual Sum or Average | 0.456421E+11 | 0.840425E+10 | ||||||||
Minimum of Months | 0.247357E+10 | 2422.70 | 18.00 | 5.78 | 0.606411E+09 | 429.75 | 7.00 | 1.92 | ||
Maximum of Months | 0.509176E+10 | 5013.20 | 36.43 | 15.97 | 0.789148E+09 | 491.88 | 36.43 | 15.97 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.249774E+10 | 1579.27 | 20-JAN-22:00 | 8.00 | 2.08 | 0.898270E+09 | 569.52 | 18-JAN-22:30 | 8.00 | 2.08 |
February | 0.218234E+10 | 1482.77 | 27-FEB-21:10 | 3.67 | 0.22 | 0.798219E+09 | 569.52 | 22-FEB-22:19 | 3.67 | 0.22 |
March | 0.256436E+10 | 1841.18 | 15-MAR-21:00 | 13.00 | 3.08 | 0.899697E+09 | 569.55 | 14-MAR-21:10 | 13.00 | 3.08 |
April | 0.240852E+10 | 1638.06 | 07-APR-21:00 | 12.00 | 6.33 | 0.864938E+09 | 569.53 | 20-APR-21:10 | 14.00 | 7.96 |
May | 0.282652E+10 | 1806.19 | 31-MAY-21:00 | 18.00 | 12.50 | 0.940094E+09 | 569.55 | 30-MAY-21:10 | 18.00 | 12.50 |
June | 0.337006E+10 | 2214.96 | 26-JUN-20:10 | 32.05 | 13.25 | 0.937614E+09 | 569.60 | 07-JUN-21:10 | 32.05 | 13.25 |
July | 0.345558E+10 | 2125.14 | 17-JUL-21:00 | 29.00 | 13.54 | 0.965545E+09 | 569.55 | 12-JUL-22:10 | 29.00 | 13.54 |
August | 0.347698E+10 | 2211.07 | 16-AUG-20:10 | 28.50 | 11.68 | 0.969871E+09 | 569.59 | 24-AUG-02:09 | 18.67 | 15.36 |
September | 0.321962E+10 | 2087.29 | 12-SEP-20:04 | 23.72 | 13.29 | 0.933052E+09 | 569.63 | 01-SEP-01:10 | 23.72 | 13.29 |
October | 0.275517E+10 | 1902.87 | 11-OCT-20:10 | 10.83 | 5.03 | 0.922733E+09 | 569.53 | 11-OCT-00:20 | 10.83 | 5.03 |
November | 0.247566E+10 | 1679.02 | 07-NOV-21:10 | 7.00 | 1.69 | 0.873796E+09 | 569.53 | 09-NOV-01:00 | 6.00 | 3.51 |
December | 0.232120E+10 | 1428.04 | 04-DEC-22:00 | 7.00 | 0.68 | 0.866939E+09 | 569.52 | 14-DEC-23:30 | 1.00 | -2.1 |
Annual Sum or Average | 0.335538E+11 | 0.108708E+11 | ||||||||
Minimum of Months | 0.218234E+10 | 1428.04 | 3.67 | 0.22 | 0.798219E+09 | 569.52 | 1.00 | -2.1 | ||
Maximum of Months | 0.347698E+10 | 2214.96 | 32.05 | 13.54 | 0.969871E+09 | 569.63 | 32.05 | 15.36 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.151011E+10 | 868.78 | 20-JAN-13:50 | 21.00 | 6.96 | 0.164970E+09 | 110.18 | 24-JAN-22:10 | 3.00 | 0.25 |
February | 0.119967E+10 | 863.18 | 18-FEB-13:45 | 20.00 | 7.73 | 0.146611E+09 | 110.59 | 27-FEB-22:10 | 2.00 | -0.8 |
March | 0.162700E+10 | 936.25 | 15-MAR-10:33 | 15.67 | 4.43 | 0.169580E+09 | 118.29 | 15-MAR-21:19 | 12.67 | 3.04 |
April | 0.160303E+10 | 892.99 | 21-APR-10:33 | 13.33 | 5.84 | 0.164924E+09 | 114.24 | 21-APR-21:10 | 6.00 | 4.11 |
May | 0.200031E+10 | 1136.41 | 17-MAY-21:00 | 17.00 | 8.20 | 0.189163E+09 | 120.45 | 16-MAY-21:10 | 17.00 | 8.20 |
June | 0.252273E+10 | 1862.96 | 27-JUN-20:25 | 24.95 | 12.03 | 0.197362E+09 | 120.46 | 07-JUN-21:10 | 24.95 | 12.03 |
July | 0.266388E+10 | 1862.70 | 17-JUL-19:50 | 30.17 | 13.94 | 0.203833E+09 | 120.46 | 15-JUL-00:10 | 30.17 | 13.94 |
August | 0.252102E+10 | 1715.91 | 16-AUG-20:00 | 29.00 | 11.91 | 0.203945E+09 | 120.46 | 10-AUG-21:10 | 29.00 | 11.91 |
September | 0.224361E+10 | 1577.40 | 11-SEP-20:00 | 19.40 | 11.27 | 0.193174E+09 | 120.46 | 01-SEP-00:40 | 19.40 | 11.27 |
October | 0.180345E+10 | 966.40 | 01-OCT-10:35 | 14.67 | 8.01 | 0.179517E+09 | 120.45 | 11-OCT-21:19 | 9.33 | 4.48 |
November | 0.153538E+10 | 906.22 | 07-NOV-13:50 | 21.67 | 7.30 | 0.163236E+09 | 115.49 | 09-NOV-22:10 | 8.00 | 6.42 |
December | 0.126898E+10 | 818.27 | 03-DEC-13:00 | 17.20 | 6.28 | 0.161584E+09 | 110.19 | 04-DEC-22:10 | 7.17 | 0.72 |
Annual Sum or Average | 0.224992E+11 | 0.213790E+10 | ||||||||
Minimum of Months | 0.119967E+10 | 818.27 | 13.33 | 4.43 | 0.146611E+09 | 110.18 | 2.00 | -0.8 | ||
Maximum of Months | 0.266388E+10 | 1862.96 | 30.17 | 13.94 | 0.203945E+09 | 120.46 | 30.17 | 13.94 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.778729E+09 | 518.71 | 20-JAN-13:50 | 21.00 | 6.96 | 0.122224E+09 | 79.77 | 20-JAN-22:30 | 7.50 | 1.84 |
February | 0.560295E+09 | 516.84 | 18-FEB-13:45 | 20.00 | 7.73 | 0.109661E+09 | 79.78 | 27-FEB-22:30 | 2.00 | -0.8 |
March | 0.838923E+09 | 550.02 | 15-MAR-10:33 | 15.67 | 4.43 | 0.125758E+09 | 86.23 | 15-MAR-21:40 | 12.33 | 3.01 |
April | 0.858022E+09 | 524.34 | 21-APR-10:33 | 13.33 | 5.84 | 0.122057E+09 | 83.75 | 20-APR-22:10 | 13.33 | 5.84 |
May | 0.115258E+10 | 578.52 | 18-MAY-10:33 | 22.00 | 11.41 | 0.140233E+09 | 90.54 | 17-MAY-22:10 | 22.00 | 11.41 |
June | 0.136930E+10 | 913.71 | 26-JUN-19:10 | 35.03 | 14.34 | 0.149858E+09 | 92.66 | 07-JUN-21:10 | 35.03 | 14.34 |
July | 0.143512E+10 | 880.22 | 17-JUL-19:10 | 30.83 | 14.16 | 0.155215E+09 | 92.66 | 15-JUL-00:10 | 30.83 | 14.16 |
August | 0.137096E+10 | 797.05 | 16-AUG-20:00 | 29.00 | 11.91 | 0.154586E+09 | 92.66 | 10-AUG-21:10 | 29.00 | 11.91 |
September | 0.124436E+10 | 676.91 | 12-SEP-21:00 | 23.30 | 12.99 | 0.144951E+09 | 92.66 | 08-SEP-21:00 | 23.30 | 12.99 |
October | 0.990011E+09 | 574.03 | 11-OCT-12:50 | 25.83 | 9.40 | 0.132585E+09 | 87.93 | 11-OCT-21:30 | 9.00 | 4.40 |
November | 0.818815E+09 | 539.86 | 07-NOV-13:50 | 21.67 | 7.30 | 0.120677E+09 | 83.87 | 09-NOV-22:40 | 8.00 | 6.69 |
December | 0.630500E+09 | 484.39 | 03-DEC-13:00 | 17.20 | 6.28 | 0.120624E+09 | 80.02 | 04-DEC-23:10 | 7.83 | 0.81 |
Annual Sum or Average | 0.120476E+11 | 0.159843E+10 | ||||||||
Minimum of Months | 0.560295E+09 | 484.39 | 13.33 | 4.43 | 0.109661E+09 | 79.77 | 2.00 | -0.8 | ||
Maximum of Months | 0.143512E+10 | 913.71 | 35.03 | 14.34 | 0.155215E+09 | 92.66 | 35.03 | 14.34 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.490462E+11 | 37770.69 | 20-JAN-21:00 | 7.00 | 1.60 | 0.617240E+09 | 381.81 | 09-JAN-22:10 | 7.00 | 1.60 |
February | 0.440646E+11 | 37778.38 | 27-FEB-21:00 | 4.00 | 0.39 | 0.556600E+09 | 381.75 | 27-FEB-22:10 | 2.00 | -0.8 |
March | 0.497152E+11 | 38341.82 | 14-MAR-20:00 | 16.00 | 5.00 | 0.620350E+09 | 381.80 | 16-MAR-21:10 | 10.00 | 4.14 |
April | 0.480079E+11 | 38370.50 | 20-APR-19:55 | 15.00 | 7.97 | 0.599907E+09 | 381.80 | 07-APR-21:10 | 15.00 | 7.97 |
May | 0.513190E+11 | 38668.04 | 16-MAY-20:00 | 19.00 | 9.69 | 0.624132E+09 | 381.83 | 16-MAY-21:10 | 16.83 | 10.08 |
June | 0.513740E+11 | 39234.98 | 26-JUN-20:00 | 32.70 | 13.66 | 0.608768E+09 | 396.35 | 14-JUN-21:10 | 32.70 | 13.66 |
July | 0.528567E+11 | 39242.77 | 07-JUL-19:30 | 24.00 | 12.33 | 0.627443E+09 | 386.58 | 17-JUL-21:10 | 28.50 | 13.44 |
August | 0.529793E+11 | 39161.31 | 16-AUG-20:00 | 29.00 | 11.91 | 0.628337E+09 | 382.03 | 25-AUG-21:10 | 24.00 | 14.43 |
September | 0.505081E+11 | 38879.95 | 12-SEP-20:00 | 23.80 | 13.35 | 0.605985E+09 | 381.90 | 08-SEP-21:10 | 23.80 | 13.35 |
October | 0.501388E+11 | 38277.07 | 11-OCT-20:00 | 11.00 | 5.10 | 0.620006E+09 | 381.84 | 04-OCT-21:10 | 11.00 | 5.10 |
November | 0.478429E+11 | 37955.15 | 09-NOV-21:00 | 9.00 | 7.27 | 0.597617E+09 | 381.80 | 07-NOV-22:10 | 9.00 | 7.27 |
December | 0.482701E+11 | 37590.95 | 04-DEC-21:00 | 7.00 | 0.68 | 0.614620E+09 | 381.75 | 04-DEC-22:10 | 7.17 | 0.72 |
Annual Sum or Average | 0.596123E+12 | 0.732100E+10 | ||||||||
Minimum of Months | 0.440646E+11 | 37590.95 | 4.00 | 0.39 | 0.556600E+09 | 381.75 | 2.00 | -0.8 | ||
Maximum of Months | 0.529793E+11 | 39242.77 | 32.70 | 13.66 | 0.628337E+09 | 396.35 | 32.70 | 14.43 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.200187E+11 | 17469.88 | 20-JAN-13:00 | 21.00 | 6.97 | 0.103215E+11 | 6461.77 | 21-JAN-02:20 | 6.00 | 0.98 |
February | 0.172552E+11 | 17898.41 | 18-FEB-13:10 | 20.00 | 7.74 | 0.917993E+10 | 6461.75 | 18-FEB-02:20 | 20.00 | 7.74 |
March | 0.188591E+11 | 16468.65 | 11-MAR-13:00 | 17.00 | 5.47 | 0.102390E+11 | 6462.59 | 14-MAR-21:10 | 13.00 | 3.83 |
April | 0.162163E+11 | 12258.25 | 07-APR-12:30 | 20.50 | 8.13 | 0.977219E+10 | 6461.88 | 01-APR-01:19 | 20.50 | 8.13 |
May | 0.188404E+11 | 10085.81 | 10-MAY-21:10 | 20.33 | 7.92 | 0.106791E+11 | 6462.64 | 15-MAY-21:40 | 13.33 | 9.13 |
June | 0.216407E+11 | 11718.45 | 26-JUN-21:10 | 28.17 | 11.17 | 0.106117E+11 | 6462.71 | 06-JUN-22:10 | 28.17 | 11.17 |
July | 0.225842E+11 | 11796.49 | 17-JUL-21:10 | 28.50 | 13.44 | 0.109297E+11 | 6462.69 | 03-JUL-22:10 | 28.50 | 13.44 |
August | 0.238849E+11 | 13720.55 | 26-AUG-12:40 | 31.67 | 13.33 | 0.109846E+11 | 6462.67 | 11-AUG-22:10 | 31.67 | 13.33 |
September | 0.232415E+11 | 16069.13 | 28-SEP-12:50 | 30.42 | 11.32 | 0.105676E+11 | 6462.70 | 01-SEP-00:49 | 30.42 | 11.32 |
October | 0.208140E+11 | 16511.83 | 08-OCT-12:00 | 21.00 | 8.76 | 0.104467E+11 | 6462.04 | 06-OCT-04:19 | 21.00 | 8.76 |
November | 0.198028E+11 | 17885.37 | 05-NOV-12:00 | 20.00 | 5.63 | 0.100020E+11 | 6461.84 | 18-NOV-02:20 | 5.33 | 2.19 |
December | 0.180442E+11 | 17225.74 | 17-DEC-12:50 | 17.67 | 5.69 | 0.997209E+10 | 6461.90 | 18-DEC-05:19 | 2.00 | -2.3 |
Annual Sum or Average | 0.241202E+12 | 0.123706E+12 | ||||||||
Minimum of Months | 0.162163E+11 | 10085.81 | 17.00 | 5.47 | 0.917993E+10 | 6461.75 | 2.00 | -2.3 | ||
Maximum of Months | 0.238849E+11 | 17898.41 | 31.67 | 13.44 | 0.109846E+11 | 6462.71 | 31.67 | 13.44 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.594527E+11 | 35484.69 | 20-JAN-22:10 | 7.83 | 2.00 | 0.317488E+11 | 19184.92 | 21-JAN-02:20 | 6.00 | 0.98 |
February | 0.520304E+11 | 33964.35 | 17-FEB-22:10 | 7.00 | 3.16 | 0.282844E+11 | 19184.97 | 25-FEB-02:20 | -0.3 | -1.6 |
March | 0.598458E+11 | 37765.83 | 15-MAR-21:10 | 12.83 | 3.06 | 0.315667E+11 | 19185.99 | 14-MAR-21:10 | 12.83 | 3.06 |
April | 0.557335E+11 | 34932.84 | 07-APR-21:10 | 11.83 | 6.33 | 0.303558E+11 | 19185.41 | 13-APR-04:19 | 5.00 | 2.00 |
May | 0.650556E+11 | 37126.36 | 17-MAY-21:10 | 17.17 | 8.37 | 0.322626E+11 | 19186.05 | 15-MAY-21:40 | 17.17 | 8.37 |
June | 0.730880E+11 | 42230.58 | 26-JUN-20:10 | 32.05 | 13.25 | 0.316010E+11 | 19186.52 | 01-JUN-01:10 | 32.05 | 13.25 |
July | 0.758798E+11 | 42199.73 | 17-JUL-21:10 | 28.50 | 13.44 | 0.325524E+11 | 19186.15 | 12-JUL-22:10 | 28.50 | 13.44 |
August | 0.769167E+11 | 42505.03 | 16-AUG-20:10 | 28.50 | 11.68 | 0.327144E+11 | 19186.64 | 24-AUG-02:09 | 18.67 | 15.36 |
September | 0.727434E+11 | 41333.84 | 12-SEP-21:10 | 22.93 | 12.81 | 0.315640E+11 | 19188.11 | 01-SEP-01:10 | 22.93 | 12.81 |
October | 0.647160E+11 | 38629.80 | 10-OCT-21:10 | 13.83 | 4.11 | 0.319467E+11 | 19185.37 | 06-OCT-04:19 | 13.83 | 4.11 |
November | 0.590395E+11 | 36092.64 | 07-NOV-22:10 | 7.00 | 2.01 | 0.307353E+11 | 19185.11 | 09-NOV-02:20 | 6.33 | 3.81 |
December | 0.558839E+11 | 33289.81 | 04-DEC-22:10 | 7.17 | 0.72 | 0.309425E+11 | 19185.27 | 18-DEC-05:19 | 2.00 | -2.3 |
Annual Sum or Average | 0.770385E+12 | 0.376275E+12 | ||||||||
Minimum of Months | 0.520304E+11 | 33289.81 | 7.00 | 0.72 | 0.282844E+11 | 19184.92 | -0.3 | -2.3 | ||
Maximum of Months | 0.769167E+11 | 42505.03 | 32.05 | 13.44 | 0.327144E+11 | 19188.11 | 32.05 | 15.36 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.387619E+09 | 2556.65 | 23-JAN-16:02 | 18.17 | 6.14 | 96920456.04 | 56.69 | 20-JAN-22:30 | 18.17 | 6.14 |
February | 0.400998E+09 | 2557.20 | 17-FEB-16:02 | 13.83 | 6.79 | 87217756.12 | 56.69 | 08-FEB-05:19 | 13.83 | 6.79 |
March | 0.728698E+09 | 2663.74 | 13-MAR-15:02 | 23.00 | 6.97 | 96874634.03 | 56.69 | 14-MAR-21:40 | 13.00 | 3.96 |
April | 0.521632E+09 | 2615.95 | 07-APR-15:02 | 21.00 | 7.80 | 93433311.98 | 56.69 | 07-APR-21:10 | 11.83 | 6.33 |
May | 0.121172E+10 | 2590.73 | 09-MAY-15:02 | 21.17 | 8.58 | 98713259.72 | 56.69 | 05-MAY-21:10 | 21.17 | 8.58 |
June | 0.237781E+10 | 2662.38 | 14-JUN-15:02 | 36.00 | 13.52 | 96587573.43 | 56.70 | 19-JUN-21:30 | 17.45 | 14.20 |
July | 0.231681E+10 | 2683.39 | 01-JUL-18:02 | 27.67 | 10.47 | 99411856.79 | 56.70 | 24-JUL-21:10 | 23.33 | 16.45 |
August | 0.234305E+10 | 2674.91 | 17-AUG-15:02 | 31.00 | 12.21 | 99673580.34 | 56.70 | 26-AUG-00:20 | 21.67 | 15.93 |
September | 0.196211E+10 | 2698.00 | 28-SEP-15:02 | 29.50 | 11.04 | 95965363.98 | 56.70 | 01-SEP-21:49 | 29.50 | 11.04 |
October | 0.995430E+09 | 2684.28 | 11-OCT-15:02 | 25.67 | 9.32 | 97410004.13 | 56.69 | 11-OCT-21:30 | 9.00 | 4.40 |
November | 0.512841E+09 | 2617.88 | 05-NOV-15:02 | 20.67 | 6.59 | 93984350.04 | 56.69 | 06-NOV-22:10 | 7.83 | 1.71 |
December | 0.246059E+09 | 2506.20 | 02-DEC-16:01 | 17.33 | 5.85 | 95867975.26 | 56.69 | 22-DEC-04:19 | -21.7 | -21.7 |
Annual Sum or Average | 0.140048E+11 | 0.115206E+10 | ||||||||
Minimum of Months | 0.246059E+09 | 2506.20 | 13.83 | 5.85 | 87217756.12 | 56.69 | -21.7 | -21.7 | ||
Maximum of Months | 0.237781E+10 | 2698.00 | 36.00 | 13.52 | 99673580.34 | 56.70 | 29.50 | 16.45 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 78639737.09 | 2419.30 | 23-JAN-16:02 | 18.17 | 6.14 | 94991415.62 | 56.69 | 06-JAN-04:19 | 18.17 | 6.14 |
February | 0.109861E+09 | 2417.84 | 26-FEB-16:02 | 17.67 | 5.08 | 85746019.86 | 56.69 | 08-FEB-05:19 | 17.67 | 5.08 |
March | 0.331773E+09 | 2824.48 | 08-MAR-17:11 | 14.33 | 3.92 | 97658309.83 | 75.80 | 13-MAR-18:10 | 17.33 | 4.68 |
April | 0.297013E+09 | 2921.57 | 08-APR-18:01 | 13.50 | 4.30 | 94581868.02 | 79.70 | 07-APR-18:10 | 13.50 | 4.30 |
May | 0.904028E+09 | 2846.38 | 27-MAY-16:11 | 14.33 | 8.19 | 0.103667E+09 | 82.86 | 09-MAY-18:10 | 14.33 | 8.19 |
June | 0.206714E+10 | 2815.99 | 18-JUN-21:51 | 18.80 | 12.91 | 0.103860E+09 | 86.87 | 22-JUN-21:10 | 16.18 | 13.70 |
July | 0.195692E+10 | 2908.00 | 01-JUL-08:61 | 26.00 | 9.47 | 0.106898E+09 | 88.94 | 03-JUL-21:10 | 16.00 | 9.77 |
August | 0.182864E+10 | 2759.93 | 11-AUG-21:51 | 23.00 | 9.59 | 0.106957E+09 | 82.91 | 03-AUG-21:10 | 23.00 | 9.59 |
September | 0.130650E+10 | 2711.15 | 15-SEP-19:51 | 12.70 | 6.10 | 0.102828E+09 | 79.19 | 12-SEP-21:19 | 12.70 | 6.10 |
October | 0.445477E+09 | 2768.21 | 14-OCT-16:11 | 14.00 | 3.81 | 98465459.82 | 65.15 | 10-OCT-20:40 | 14.00 | 3.81 |
November | 0.127746E+09 | 2493.24 | 07-NOV-16:01 | 20.00 | 7.03 | 92616108.16 | 56.69 | 01-NOV-04:19 | 20.00 | 7.03 |
December | 40694443.05 | 2396.70 | 02-DEC-16:01 | 17.33 | 5.85 | 94263793.64 | 56.69 | 22-DEC-05:19 | -21.0 | -21.0 |
Annual Sum or Average | 0.949442E+10 | 0.118253E+10 | ||||||||
Minimum of Months | 40694443.05 | 2396.70 | 12.70 | 3.81 | 85746019.86 | 56.69 | -21.0 | -21.0 | ||
Maximum of Months | 0.206714E+10 | 2921.57 | 26.00 | 12.91 | 0.106957E+09 | 88.94 | 23.00 | 13.70 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.439993E+09 | 860.98 | 20-JAN-12:40 | 20.67 | 7.18 | 0.00 | 0.00 | 01-JAN-00:10 | 20.67 | 7.18 |
February | 0.314188E+09 | 819.27 | 18-FEB-13:00 | 20.00 | 7.74 | 0.00 | 0.00 | 01-FEB-00:10 | 20.00 | 7.74 |
March | 0.316937E+09 | 737.15 | 14-MAR-12:40 | 23.33 | 7.71 | 0.00 | 0.00 | 01-MAR-00:10 | 23.33 | 7.71 |
April | 0.129817E+09 | 457.27 | 08-APR-13:00 | 16.00 | 5.15 | 0.00 | 0.00 | 01-APR-00:10 | 16.00 | 5.15 |
May | 0.291262E+09 | 358.78 | 05-MAY-13:00 | 22.00 | 10.96 | 0.00 | 0.00 | 01-MAY-00:10 | 22.00 | 10.96 |
June | 0.530781E+09 | 422.27 | 14-JUN-13:30 | 34.95 | 13.21 | 0.00 | 0.00 | 01-JUN-00:10 | 34.95 | 13.21 |
July | 0.577780E+09 | 457.58 | 23-JUL-13:00 | 34.00 | 16.01 | 0.00 | 0.00 | 01-JUL-00:10 | 34.00 | 16.01 |
August | 0.656467E+09 | 590.40 | 31-AUG-12:40 | 30.00 | 12.25 | 0.00 | 0.00 | 01-AUG-00:10 | 30.00 | 12.25 |
September | 0.666208E+09 | 762.05 | 28-SEP-13:00 | 30.50 | 11.31 | 0.00 | 0.00 | 01-SEP-00:10 | 30.50 | 11.31 |
October | 0.493718E+09 | 794.90 | 10-OCT-12:30 | 23.50 | 7.91 | 0.00 | 0.00 | 01-OCT-00:10 | 23.50 | 7.91 |
November | 0.414800E+09 | 854.36 | 07-NOV-12:10 | 20.00 | 7.48 | 0.00 | 0.00 | 01-NOV-00:10 | 20.00 | 7.48 |
December | 0.276054E+09 | 776.08 | 17-DEC-12:30 | 17.00 | 5.51 | 0.00 | 0.00 | 01-DEC-00:10 | 17.00 | 5.51 |
Annual Sum or Average | 0.510800E+10 | 0.00 | ||||||||
Minimum of Months | 0.129817E+09 | 358.78 | 16.00 | 5.15 | 0.00 | 0.00 | 16.00 | 5.15 | ||
Maximum of Months | 0.666208E+09 | 860.98 | 34.95 | 16.01 | 0.00 | 0.00 | 34.95 | 16.01 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 67109855.31 | 726.64 | 21-JAN-09:02 | 13.00 | 3.75 | 95176597.50 | 56.69 | 24-JAN-22:10 | 3.00 | 0.25 |
February | 55998211.64 | 728.58 | 19-FEB-09:02 | 5.17 | 2.82 | 85890444.06 | 56.69 | 27-FEB-22:00 | 2.00 | -0.8 |
March | 0.163164E+09 | 798.48 | 14-MAR-20:51 | 13.00 | 3.78 | 96519324.99 | 64.18 | 14-MAR-20:49 | 13.00 | 3.78 |
April | 0.215121E+09 | 810.81 | 20-APR-20:31 | 14.33 | 7.97 | 93893305.41 | 65.30 | 20-APR-20:40 | 14.33 | 7.97 |
May | 0.488320E+09 | 838.12 | 17-MAY-21:51 | 18.00 | 9.24 | 0.101181E+09 | 76.24 | 30-MAY-21:10 | 14.00 | 11.46 |
June | 0.762764E+09 | 871.83 | 12-JUN-08:61 | 26.97 | 12.63 | 0.101336E+09 | 79.74 | 22-JUN-21:49 | 16.52 | 14.01 |
July | 0.785800E+09 | 918.59 | 01-JUL-08:61 | 26.00 | 9.47 | 0.104952E+09 | 81.15 | 05-JUL-21:10 | 14.50 | 9.06 |
August | 0.695756E+09 | 881.88 | 01-AUG-21:51 | 21.00 | 10.09 | 0.104004E+09 | 78.75 | 03-AUG-21:19 | 21.33 | 15.95 |
September | 0.537245E+09 | 849.71 | 08-SEP-21:51 | 21.60 | 11.21 | 99663103.68 | 76.48 | 11-SEP-21:49 | 17.20 | 10.39 |
October | 0.231684E+09 | 803.34 | 11-OCT-15:02 | 25.67 | 9.32 | 96952491.80 | 63.25 | 10-OCT-20:40 | 25.67 | 9.32 |
November | 97392108.87 | 740.03 | 09-NOV-19:02 | 11.67 | 7.20 | 92565968.60 | 56.69 | 09-NOV-23:10 | 8.00 | 6.96 |
December | 51238620.97 | 714.19 | 03-DEC-09:02 | 9.50 | 2.25 | 94751740.51 | 56.69 | 04-DEC-22:19 | 7.33 | 0.76 |
Annual Sum or Average | 0.415159E+10 | 0.116689E+10 | ||||||||
Minimum of Months | 51238620.97 | 714.19 | 5.17 | 2.25 | 85890444.06 | 56.69 | 2.00 | -0.8 | ||
Maximum of Months | 0.785800E+09 | 918.59 | 26.97 | 12.63 | 0.104952E+09 | 81.15 | 25.67 | 15.95 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.374872E+09 | 2249.13 | 20-JAN-09:02 | 10.67 | 3.20 | 97152795.19 | 56.69 | 06-JAN-05:19 | 10.67 | 3.20 |
February | 0.437104E+09 | 2284.80 | 27-FEB-09:02 | 9.17 | 2.67 | 87458196.24 | 56.69 | 08-FEB-05:19 | 9.17 | 2.67 |
March | 0.773634E+09 | 2319.71 | 10-MAR-09:01 | 12.33 | 2.54 | 97182056.12 | 56.69 | 13-MAR-21:19 | 10.67 | 1.98 |
April | 0.600382E+09 | 2271.10 | 07-APR-08:62 | 11.67 | 4.90 | 93835978.83 | 56.69 | 20-APR-21:19 | 14.00 | 7.96 |
May | 0.130628E+10 | 2285.44 | 13-MAY-08:62 | 20.33 | 9.00 | 98979852.99 | 56.69 | 31-MAY-21:19 | 17.77 | 11.98 |
June | 0.251820E+10 | 2379.88 | 27-JUN-08:62 | 24.00 | 9.68 | 96280093.00 | 56.69 | 19-JUN-22:40 | 24.00 | 9.68 |
July | 0.256774E+10 | 2440.75 | 01-JUL-08:61 | 26.00 | 9.47 | 99344440.39 | 56.70 | 21-JUL-21:10 | 23.83 | 14.71 |
August | 0.257922E+10 | 2397.00 | 05-AUG-08:62 | 22.33 | 16.17 | 99419474.73 | 56.70 | 03-AUG-23:10 | 22.33 | 16.17 |
September | 0.205813E+10 | 2355.58 | 28-SEP-08:62 | 20.78 | 8.57 | 96004375.59 | 56.69 | 08-SEP-21:10 | 20.78 | 8.57 |
October | 0.959078E+09 | 2310.59 | 11-OCT-15:02 | 25.67 | 9.32 | 97560312.38 | 56.69 | 10-OCT-22:10 | 25.67 | 9.32 |
November | 0.493937E+09 | 2295.20 | 07-NOV-09:02 | 14.00 | 4.09 | 94038381.75 | 56.69 | 06-NOV-22:10 | 14.00 | 4.09 |
December | 0.251657E+09 | 2220.28 | 03-DEC-09:02 | 9.50 | 2.25 | 96005755.39 | 56.69 | 27-DEC-05:19 | -1.0 | -3.9 |
Annual Sum or Average | 0.149202E+11 | 0.115326E+10 | ||||||||
Minimum of Months | 0.251657E+09 | 2220.28 | 9.17 | 2.25 | 87458196.24 | 56.69 | -1.0 | -3.9 | ||
Maximum of Months | 0.257922E+10 | 2440.75 | 26.00 | 16.17 | 99419474.73 | 56.70 | 25.67 | 16.17 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 86148080.08 | 2131.61 | 24-JAN-09:02 | 7.67 | 1.43 | 94764297.19 | 56.69 | 06-JAN-05:19 | 7.67 | 1.43 |
February | 0.144631E+09 | 2191.48 | 27-FEB-09:02 | 9.17 | 2.67 | 85845846.80 | 56.69 | 13-FEB-05:19 | 9.17 | 2.67 |
March | 0.389061E+09 | 2264.80 | 15-MAR-18:31 | 13.00 | 3.03 | 97107411.98 | 65.99 | 14-MAR-20:40 | 13.00 | 3.03 |
April | 0.393977E+09 | 2239.01 | 20-APR-20:31 | 14.33 | 7.97 | 94312472.63 | 65.80 | 20-APR-20:30 | 14.33 | 7.97 |
May | 0.102476E+10 | 2659.11 | 04-MAY-08:51 | 21.00 | 8.58 | 0.102888E+09 | 76.97 | 16-MAY-21:40 | 16.33 | 9.88 |
June | 0.213093E+10 | 2902.73 | 27-JUN-08:32 | 24.60 | 10.38 | 0.104616E+09 | 82.28 | 22-JUN-21:40 | 24.60 | 10.38 |
July | 0.213983E+10 | 2819.87 | 01-JUL-07:32 | 25.00 | 9.48 | 0.107810E+09 | 83.83 | 05-JUL-21:10 | 14.50 | 9.06 |
August | 0.199686E+10 | 2849.55 | 06-AUG-08:32 | 24.00 | 15.32 | 0.107459E+09 | 82.12 | 03-AUG-21:19 | 24.00 | 15.32 |
September | 0.140519E+10 | 2681.90 | 18-SEP-08:51 | 22.70 | 10.68 | 0.102113E+09 | 78.83 | 08-SEP-21:19 | 22.70 | 10.68 |
October | 0.438810E+09 | 2620.24 | 11-OCT-08:51 | 20.20 | 7.65 | 97815410.33 | 63.92 | 10-OCT-20:40 | 20.20 | 7.65 |
November | 0.140895E+09 | 2184.43 | 07-NOV-09:02 | 14.00 | 4.09 | 92313705.49 | 56.69 | 01-NOV-04:19 | 14.00 | 4.09 |
December | 52018160.59 | 2113.38 | 03-DEC-09:02 | 9.50 | 2.25 | 94058956.73 | 56.69 | 05-DEC-05:19 | -1.7 | -3.8 |
Annual Sum or Average | 0.103431E+11 | 0.118111E+10 | ||||||||
Minimum of Months | 52018160.59 | 2113.38 | 7.67 | 1.43 | 85845846.80 | 56.69 | -1.7 | -3.8 | ||
Maximum of Months | 0.213983E+10 | 2902.73 | 25.00 | 15.32 | 0.107810E+09 | 83.83 | 24.60 | 15.32 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.315491E+10 | 1872.47 | 20-JAN-13:50 | 21.00 | 6.96 | 0.128098E+10 | 837.07 | 24-JAN-22:40 | 3.00 | 0.25 |
February | 0.248273E+10 | 1925.72 | 18-FEB-13:45 | 20.00 | 7.73 | 0.114959E+10 | 838.41 | 27-FEB-22:40 | 2.00 | -0.8 |
March | 0.328639E+10 | 2042.61 | 15-MAR-10:33 | 15.67 | 4.43 | 0.132228E+10 | 925.50 | 15-MAR-21:40 | 12.33 | 3.01 |
April | 0.316181E+10 | 1835.80 | 21-APR-10:33 | 13.33 | 5.84 | 0.125673E+10 | 846.27 | 12-APR-21:40 | 13.33 | 5.84 |
May | 0.405257E+10 | 2020.87 | 18-MAY-10:33 | 22.00 | 11.41 | 0.143676E+10 | 918.18 | 17-MAY-22:10 | 22.00 | 11.41 |
June | 0.485648E+10 | 3264.92 | 26-JUN-18:25 | 36.60 | 14.84 | 0.154349E+10 | 951.90 | 07-JUN-21:10 | 36.60 | 14.84 |
July | 0.508449E+10 | 2946.09 | 01-JUL-18:40 | 26.67 | 10.19 | 0.160202E+10 | 951.86 | 15-JUL-00:10 | 21.83 | 14.36 |
August | 0.500755E+10 | 3012.43 | 11-AUG-18:30 | 30.00 | 11.17 | 0.160485E+10 | 951.88 | 10-AUG-21:19 | 30.00 | 11.17 |
September | 0.458435E+10 | 2697.84 | 12-SEP-18:03 | 27.33 | 13.46 | 0.152166E+10 | 951.86 | 01-SEP-00:30 | 27.33 | 13.46 |
October | 0.371628E+10 | 2134.00 | 11-OCT-12:50 | 25.83 | 9.40 | 0.140501E+10 | 932.48 | 11-OCT-21:40 | 8.67 | 4.30 |
November | 0.312026E+10 | 1975.61 | 07-NOV-13:50 | 21.67 | 7.30 | 0.125929E+10 | 861.60 | 09-NOV-22:40 | 8.00 | 6.69 |
December | 0.247946E+10 | 1770.41 | 17-DEC-13:00 | 18.00 | 5.78 | 0.124019E+10 | 804.56 | 04-DEC-22:49 | 18.00 | 5.78 |
Annual Sum or Average | 0.449873E+11 | 0.166228E+11 | ||||||||
Minimum of Months | 0.247946E+10 | 1770.41 | 13.33 | 4.43 | 0.114959E+10 | 804.56 | 2.00 | -0.8 | ||
Maximum of Months | 0.508449E+10 | 3264.92 | 36.60 | 14.84 | 0.160485E+10 | 951.90 | 36.60 | 14.84 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.336220E+09 | 2712.48 | 20-JAN-16:02 | 17.00 | 7.18 | 96423636.92 | 56.69 | 06-JAN-04:19 | 17.00 | 7.18 |
February | 0.363928E+09 | 2714.58 | 17-FEB-16:02 | 13.83 | 6.79 | 86884678.17 | 56.69 | 13-FEB-05:19 | 13.83 | 6.79 |
March | 0.692197E+09 | 2827.80 | 13-MAR-15:02 | 23.00 | 6.97 | 96549575.44 | 56.70 | 17-MAR-00:00 | 8.00 | 4.06 |
April | 0.511255E+09 | 2768.26 | 07-APR-15:02 | 21.00 | 7.80 | 93086225.92 | 56.69 | 20-APR-01:19 | 9.00 | 4.68 |
May | 0.115458E+10 | 2733.90 | 04-MAY-15:02 | 24.83 | 10.09 | 98591482.16 | 56.69 | 31-MAY-04:49 | 11.83 | 9.63 |
June | 0.240846E+10 | 2831.01 | 14-JUN-15:02 | 36.00 | 13.52 | 96686986.90 | 56.70 | 07-JUN-21:40 | 36.00 | 13.52 |
July | 0.230416E+10 | 2848.77 | 01-JUL-18:02 | 27.67 | 10.47 | 99443661.73 | 56.70 | 21-JUL-21:00 | 23.00 | 15.78 |
August | 0.233684E+10 | 2840.54 | 14-AUG-15:02 | 33.83 | 12.96 | 99738982.97 | 58.98 | 11-AUG-18:10 | 33.83 | 12.96 |
September | 0.186494E+10 | 2864.50 | 28-SEP-15:02 | 29.50 | 11.04 | 95861248.59 | 56.69 | 08-SEP-21:49 | 29.50 | 11.04 |
October | 0.894821E+09 | 2842.89 | 11-OCT-15:02 | 25.67 | 9.32 | 97104688.67 | 56.70 | 19-OCT-00:30 | 5.50 | -0.4 |
November | 0.457629E+09 | 2782.51 | 05-NOV-15:02 | 20.67 | 6.59 | 93598122.36 | 56.69 | 07-NOV-22:10 | 7.00 | 2.01 |
December | 0.215967E+09 | 2660.51 | 02-DEC-16:01 | 17.33 | 5.85 | 95354849.36 | 56.69 | 19-DEC-05:19 | -16.5 | -16.6 |
Annual Sum or Average | 0.135410E+11 | 0.114932E+10 | ||||||||
Minimum of Months | 0.215967E+09 | 2660.51 | 13.83 | 5.85 | 86884678.17 | 56.69 | -16.5 | -16.6 | ||
Maximum of Months | 0.240846E+10 | 2864.50 | 36.00 | 13.52 | 99738982.97 | 58.98 | 36.00 | 15.78 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 59760206.80 | 2539.73 | 23-JAN-16:02 | 18.17 | 6.14 | 94365669.79 | 56.69 | 06-JAN-04:19 | 18.17 | 6.14 |
February | 89976638.34 | 2537.25 | 17-FEB-16:02 | 13.83 | 6.79 | 85365942.32 | 56.69 | 02-FEB-05:19 | 13.83 | 6.79 |
March | 0.298463E+09 | 3049.41 | 08-MAR-17:11 | 14.33 | 3.92 | 97527267.66 | 83.72 | 31-MAR-18:10 | 14.33 | 7.61 |
April | 0.281998E+09 | 3120.79 | 08-APR-17:42 | 14.33 | 4.60 | 94516593.04 | 87.31 | 07-APR-18:10 | 14.33 | 4.60 |
May | 0.855040E+09 | 3044.83 | 27-MAY-16:11 | 14.33 | 8.19 | 0.104142E+09 | 90.22 | 09-MAY-18:10 | 14.33 | 8.19 |
June | 0.214482E+10 | 3042.66 | 18-JUN-21:51 | 18.80 | 12.91 | 0.104093E+09 | 90.10 | 22-JUN-21:10 | 16.18 | 13.70 |
July | 0.199633E+10 | 3036.34 | 01-JUL-08:61 | 26.00 | 9.47 | 0.106931E+09 | 93.58 | 03-JUL-21:10 | 16.00 | 9.77 |
August | 0.186529E+10 | 2913.20 | 11-AUG-21:51 | 23.00 | 9.59 | 0.107088E+09 | 87.36 | 03-AUG-21:10 | 23.00 | 9.59 |
September | 0.124227E+10 | 2914.99 | 15-SEP-19:51 | 12.70 | 6.10 | 0.102813E+09 | 79.66 | 15-SEP-18:10 | 12.70 | 6.10 |
October | 0.361654E+09 | 3000.13 | 08-OCT-18:11 | 13.33 | 7.54 | 98349507.05 | 67.13 | 05-OCT-18:10 | 13.33 | 7.54 |
November | 0.102111E+09 | 2631.89 | 07-NOV-16:01 | 20.00 | 7.03 | 92146616.02 | 56.69 | 30-NOV-05:19 | -12.7 | -13.3 |
December | 31094855.24 | 2523.31 | 02-DEC-16:01 | 17.33 | 5.85 | 93753716.51 | 56.69 | 22-DEC-04:19 | -21.7 | -21.7 |
Annual Sum or Average | 0.932881E+10 | 0.118109E+10 | ||||||||
Minimum of Months | 31094855.24 | 2523.31 | 12.70 | 3.92 | 85365942.32 | 56.69 | -21.7 | -21.7 | ||
Maximum of Months | 0.214482E+10 | 3120.79 | 26.00 | 12.91 | 0.107088E+09 | 93.58 | 23.00 | 13.70 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.838960E+09 | 1508.83 | 20-JAN-13:15 | 21.00 | 6.97 | 98216898.24 | 56.69 | 26-JAN-22:10 | 4.00 | 2.01 |
February | 0.681696E+09 | 1541.82 | 18-FEB-13:33 | 20.00 | 7.73 | 88253580.66 | 56.69 | 23-FEB-22:10 | 1.00 | 0.92 |
March | 0.712590E+09 | 1460.06 | 13-MAR-15:02 | 23.00 | 6.97 | 97358004.47 | 56.69 | 13-MAR-21:19 | 10.67 | 1.98 |
April | 0.400716E+09 | 1401.19 | 07-APR-15:02 | 21.00 | 7.80 | 93686139.66 | 56.69 | 07-APR-21:40 | 11.33 | 6.32 |
May | 0.689006E+09 | 1391.08 | 04-MAY-15:02 | 24.83 | 10.09 | 98602767.14 | 56.69 | 16-MAY-21:10 | 16.83 | 10.08 |
June | 0.121045E+10 | 1389.08 | 07-JUN-15:02 | 31.83 | 11.89 | 95971690.76 | 56.69 | 20-JUN-21:30 | 16.60 | 15.15 |
July | 0.129145E+10 | 1396.71 | 01-JUL-08:61 | 26.00 | 9.47 | 99066710.87 | 56.70 | 21-JUL-22:00 | 22.00 | 16.07 |
August | 0.142092E+10 | 1422.42 | 17-AUG-15:02 | 31.00 | 12.21 | 99275244.13 | 56.70 | 26-AUG-00:20 | 21.67 | 15.93 |
September | 0.135720E+10 | 1462.21 | 28-SEP-15:02 | 29.50 | 11.04 | 96002039.47 | 56.69 | 08-SEP-21:00 | 29.50 | 11.04 |
October | 0.972523E+09 | 1464.23 | 11-OCT-15:02 | 25.67 | 9.32 | 97958066.14 | 56.69 | 11-OCT-21:30 | 9.00 | 4.40 |
November | 0.868126E+09 | 1495.14 | 07-NOV-13:15 | 20.67 | 7.14 | 95103029.17 | 56.69 | 06-NOV-23:10 | 20.67 | 7.14 |
December | 0.619990E+09 | 1400.68 | 29-DEC-13:55 | 10.00 | 3.87 | 97497799.22 | 56.69 | 01-DEC-23:10 | 10.00 | 3.87 |
Annual Sum or Average | 0.110636E+11 | 0.115699E+10 | ||||||||
Minimum of Months | 0.400716E+09 | 1389.08 | 10.00 | 3.87 | 88253580.66 | 56.69 | 1.00 | 0.92 | ||
Maximum of Months | 0.142092E+10 | 1541.82 | 31.83 | 12.21 | 99275244.13 | 56.70 | 29.50 | 16.07 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.308838E+11 | 18540.13 | 20-JAN-22:10 | 7.83 | 2.00 | 0.191227E+11 | 11347.44 | 06-JAN-04:19 | 7.83 | 2.00 |
February | 0.276940E+11 | 18313.66 | 27-FEB-22:10 | 2.00 | -0.8 | 0.172763E+11 | 11346.89 | 25-FEB-02:20 | 2.00 | -0.8 |
March | 0.332993E+11 | 20365.98 | 14-MAR-21:03 | 13.00 | 3.83 | 0.192816E+11 | 11348.77 | 14-MAR-21:10 | 13.00 | 3.83 |
April | 0.329115E+11 | 20457.39 | 20-APR-21:10 | 14.00 | 7.96 | 0.186430E+11 | 11347.62 | 13-APR-04:19 | 14.00 | 7.96 |
May | 0.389362E+11 | 21562.02 | 31-MAY-21:10 | 17.88 | 12.24 | 0.193428E+11 | 11348.89 | 15-MAY-21:40 | 17.88 | 12.24 |
June | 0.427307E+11 | 23350.14 | 26-JUN-21:20 | 27.53 | 11.08 | 0.187619E+11 | 11393.54 | 30-JUN-21:19 | 26.13 | 11.13 |
July | 0.440304E+11 | 23198.89 | 17-JUL-21:10 | 28.50 | 13.44 | 0.193104E+11 | 11387.33 | 07-JUL-21:19 | 28.50 | 13.44 |
August | 0.432921E+11 | 23033.81 | 16-AUG-21:20 | 25.33 | 11.70 | 0.193917E+11 | 11418.12 | 16-AUG-21:49 | 24.33 | 13.24 |
September | 0.395479E+11 | 22220.17 | 12-SEP-21:20 | 22.57 | 12.63 | 0.187074E+11 | 11372.76 | 08-SEP-21:19 | 22.57 | 12.63 |
October | 0.346148E+11 | 20422.12 | 10-OCT-21:10 | 13.83 | 4.11 | 0.192298E+11 | 11347.60 | 06-OCT-04:19 | 13.83 | 4.11 |
November | 0.309557E+11 | 19414.54 | 09-NOV-23:00 | 8.00 | 6.87 | 0.185436E+11 | 11347.00 | 18-NOV-02:20 | 5.33 | 2.19 |
December | 0.296295E+11 | 18567.21 | 04-DEC-23:00 | 8.00 | 0.89 | 0.189945E+11 | 11347.10 | 18-DEC-05:19 | 2.00 | -2.3 |
Annual Sum or Average | 0.428526E+12 | 0.226606E+12 | ||||||||
Minimum of Months | 0.276940E+11 | 18313.66 | 2.00 | -0.8 | 0.172763E+11 | 11346.89 | 2.00 | -2.3 | ||
Maximum of Months | 0.440304E+11 | 23350.14 | 28.50 | 13.44 | 0.193917E+11 | 11418.12 | 28.50 | 13.44 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.345187E+11 | 20173.63 | 20-JAN-22:10 | 7.83 | 2.00 | 0.192314E+11 | 11347.53 | 06-JAN-04:19 | 7.83 | 2.00 |
February | 0.309793E+11 | 19899.58 | 27-FEB-22:10 | 2.00 | -0.8 | 0.173765E+11 | 11346.98 | 11-FEB-02:20 | 2.00 | -0.8 |
March | 0.369680E+11 | 21686.08 | 14-MAR-21:03 | 13.00 | 3.83 | 0.193575E+11 | 11348.78 | 14-MAR-21:10 | 13.00 | 3.83 |
April | 0.366195E+11 | 21948.18 | 20-APR-21:10 | 14.00 | 7.96 | 0.186966E+11 | 11347.70 | 13-APR-04:19 | 14.00 | 7.96 |
May | 0.424180E+11 | 22865.98 | 31-MAY-21:10 | 17.88 | 12.24 | 0.193495E+11 | 11348.90 | 15-MAY-21:40 | 17.88 | 12.24 |
June | 0.455322E+11 | 24545.07 | 26-JUN-21:20 | 27.53 | 11.08 | 0.187625E+11 | 11404.76 | 30-JUN-21:19 | 26.13 | 11.13 |
July | 0.468836E+11 | 24426.75 | 17-JUL-21:20 | 28.00 | 13.33 | 0.193109E+11 | 11402.23 | 07-JUL-21:19 | 28.00 | 13.33 |
August | 0.461422E+11 | 24219.91 | 16-AUG-21:20 | 25.33 | 11.70 | 0.193924E+11 | 11430.54 | 16-AUG-21:49 | 24.33 | 13.24 |
September | 0.424160E+11 | 23403.40 | 12-SEP-21:20 | 22.57 | 12.63 | 0.187103E+11 | 11390.93 | 08-SEP-21:19 | 22.57 | 12.63 |
October | 0.380064E+11 | 21708.80 | 10-OCT-21:10 | 13.83 | 4.11 | 0.192798E+11 | 11347.67 | 06-OCT-04:19 | 13.83 | 4.11 |
November | 0.344577E+11 | 20847.85 | 09-NOV-22:10 | 8.00 | 6.42 | 0.186186E+11 | 11347.05 | 18-NOV-02:20 | 5.33 | 2.19 |
December | 0.332256E+11 | 20217.07 | 04-DEC-23:00 | 8.00 | 0.89 | 0.191432E+11 | 11347.17 | 18-DEC-05:19 | 2.00 | -2.3 |
Annual Sum or Average | 0.468167E+12 | 0.227229E+12 | ||||||||
Minimum of Months | 0.309793E+11 | 19899.58 | 2.00 | -0.8 | 0.173765E+11 | 11346.98 | 2.00 | -2.3 | ||
Maximum of Months | 0.468836E+11 | 24545.07 | 28.00 | 13.33 | 0.193924E+11 | 11430.54 | 28.00 | 13.33 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.502805E+11 | 28644.16 | 20-JAN-11:40 | 19.33 | 7.26 | 0.188494E+11 | 11319.77 | 21-JAN-18:19 | 7.33 | 3.18 |
February | 0.453016E+11 | 29171.69 | 18-FEB-11:40 | 17.67 | 6.73 | 0.170230E+11 | 11319.62 | 25-FEB-18:19 | 7.67 | 3.07 |
March | 0.518676E+11 | 30252.37 | 12-MAR-10:40 | 15.67 | 5.64 | 0.188629E+11 | 11319.58 | 25-MAR-17:19 | 7.00 | 4.43 |
April | 0.504274E+11 | 29941.66 | 20-APR-10:33 | 19.33 | 8.37 | 0.182521E+11 | 11319.64 | 08-APR-17:19 | 19.33 | 8.37 |
May | 0.553439E+11 | 30506.58 | 16-MAY-10:33 | 24.67 | 11.32 | 0.188696E+11 | 11319.63 | 06-MAY-17:19 | 24.67 | 11.32 |
June | 0.570350E+11 | 31319.46 | 26-JUN-10:40 | 32.70 | 15.62 | 0.182669E+11 | 11319.64 | 17-JUN-17:19 | 32.70 | 15.62 |
July | 0.587077E+11 | 31550.38 | 23-JUL-10:40 | 29.67 | 15.92 | 0.188696E+11 | 11319.64 | 22-JUL-17:19 | 29.67 | 15.92 |
August | 0.585841E+11 | 31636.54 | 05-AUG-10:40 | 29.00 | 17.63 | 0.188761E+11 | 11319.65 | 05-AUG-17:19 | 21.33 | 16.54 |
September | 0.549891E+11 | 31096.77 | 04-SEP-10:40 | 26.83 | 13.23 | 0.182610E+11 | 11319.62 | 23-SEP-17:19 | 19.80 | 9.24 |
October | 0.524713E+11 | 30241.70 | 07-OCT-10:33 | 20.33 | 9.02 | 0.188605E+11 | 11319.68 | 21-OCT-17:10 | 11.67 | 4.94 |
November | 0.492422E+11 | 29455.26 | 05-NOV-10:40 | 18.00 | 5.62 | 0.182430E+11 | 11319.53 | 04-NOV-17:19 | 18.00 | 5.62 |
December | 0.488920E+11 | 28399.67 | 02-DEC-11:50 | 19.50 | 6.90 | 0.188404E+11 | 11319.73 | 02-DEC-18:19 | 13.00 | 4.03 |
Annual Sum or Average | 0.633142E+12 | 0.222075E+12 | ||||||||
Minimum of Months | 0.453016E+11 | 28399.67 | 15.67 | 5.62 | 0.170230E+11 | 11319.53 | 7.00 | 3.07 | ||
Maximum of Months | 0.587077E+11 | 31636.54 | 32.70 | 17.63 | 0.188761E+11 | 11319.77 | 32.70 | 16.54 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.544178E+10 | 4248.15 | 20-JAN-13:50 | 21.00 | 6.96 | 0.131623E+10 | 862.79 | 20-JAN-22:30 | 7.50 | 1.84 |
February | 0.441479E+10 | 4300.52 | 18-FEB-13:45 | 20.00 | 7.73 | 0.119289E+10 | 848.13 | 27-FEB-22:30 | 2.00 | -0.8 |
March | 0.604105E+10 | 5020.55 | 15-MAR-14:10 | 20.83 | 6.19 | 0.137366E+10 | 961.25 | 15-MAR-21:30 | 12.50 | 3.03 |
April | 0.609670E+10 | 4065.82 | 21-APR-10:33 | 13.33 | 5.84 | 0.131903E+10 | 915.52 | 20-APR-21:30 | 13.33 | 5.84 |
May | 0.846588E+10 | 4373.85 | 18-MAY-10:33 | 22.00 | 11.41 | 0.151112E+10 | 977.60 | 17-MAY-21:30 | 22.00 | 11.41 |
June | 0.107067E+11 | 6945.48 | 26-JUN-14:10 | 37.98 | 15.29 | 0.162288E+10 | 1007.48 | 07-JUN-21:10 | 37.98 | 15.29 |
July | 0.110896E+11 | 6913.73 | 23-JUL-12:50 | 33.67 | 16.02 | 0.167592E+10 | 1007.41 | 14-JUL-23:49 | 33.67 | 16.02 |
August | 0.110241E+11 | 7205.10 | 16-AUG-15:02 | 36.17 | 16.19 | 0.167513E+10 | 1007.45 | 25-AUG-22:10 | 23.67 | 16.10 |
September | 0.963646E+10 | 6830.79 | 09-SEP-12:50 | 32.62 | 13.01 | 0.156842E+10 | 1007.41 | 08-SEP-21:00 | 32.62 | 13.01 |
October | 0.705622E+10 | 5127.33 | 11-OCT-14:10 | 26.83 | 9.68 | 0.143338E+10 | 967.82 | 10-OCT-21:30 | 26.83 | 9.68 |
November | 0.578114E+10 | 4445.91 | 07-NOV-13:40 | 21.33 | 7.25 | 0.129993E+10 | 896.87 | 09-NOV-22:30 | 8.00 | 6.60 |
December | 0.429428E+10 | 3858.08 | 03-DEC-13:00 | 17.20 | 6.28 | 0.129865E+10 | 836.68 | 04-DEC-22:40 | 7.67 | 0.83 |
Annual Sum or Average | 0.900487E+11 | 0.172872E+11 | ||||||||
Minimum of Months | 0.429428E+10 | 3858.08 | 13.33 | 5.84 | 0.119289E+10 | 836.68 | 2.00 | -0.8 | ||
Maximum of Months | 0.110896E+11 | 7205.10 | 37.98 | 16.19 | 0.167592E+10 | 1007.48 | 37.98 | 16.10 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.50 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -5.3 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 10.30 |
November | 0.00 | 0.00 | 01-NOV-00:05 | -5.7 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 2.77 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -5.7 | |
Maximum of Months | 0.00 | 0.00 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 93775867.91 | 1198.20 | 05-JAN-09:10 | -17.0 |
February | 0.229730E+09 | 1053.51 | 05-FEB-17:00 | -7.0 |
March | 0.112888E+09 | 1152.33 | 19-MAR-08:10 | -13.0 |
April | 75212896.67 | 658.63 | 03-APR-08:03 | -4.8 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 0.131357E+09 | 974.48 | 31-OCT-15:00 | -8.0 |
November | 91969591.66 | 874.59 | 30-NOV-07:10 | -11.3 |
December | 0.353862E+09 | 1657.05 | 21-DEC-08:10 | -20.0 |
Annual Sum or Average | 0.108879E+10 | |||
Minimum of Months | 0.00 | 0.00 | -20.0 | |
Maximum of Months | 0.353862E+09 | 1657.05 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.50 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -5.3 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 10.30 |
November | 0.00 | 0.00 | 01-NOV-00:05 | -5.7 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 2.77 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -5.7 | |
Maximum of Months | 0.00 | 0.00 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 6056184.52 | 191.11 | 06-JAN-04:03 | -11.3 |
February | 10649589.92 | 179.32 | 06-FEB-14:00 | -3.0 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 1719760.96 | 96.50 | 31-OCT-13:50 | -7.0 |
November | 155347.28 | 41.35 | 30-NOV-05:00 | -13.0 |
December | 0.118168E+09 | 604.10 | 22-DEC-05:00 | -21.0 |
Annual Sum or Average | 0.136748E+09 | |||
Minimum of Months | 0.00 | 0.00 | -21.0 | |
Maximum of Months | 0.118168E+09 | 604.10 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 28283203.06 | 337.44 | 05-JAN-18:00 | -18.0 |
February | 53185228.58 | 282.70 | 06-FEB-18:00 | -7.0 |
March | 5698669.99 | 134.75 | 19-MAR-15:00 | 0.00 |
April | 1205337.65 | 73.75 | 03-APR-09:20 | -3.7 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 14051323.45 | 260.86 | 31-OCT-15:00 | -8.0 |
November | 16661927.92 | 203.92 | 30-NOV-04:50 | -13.2 |
December | 0.182001E+09 | 625.08 | 21-DEC-11:00 | -18.0 |
Annual Sum or Average | 0.301087E+09 | |||
Minimum of Months | 0.00 | 0.00 | -18.0 | |
Maximum of Months | 0.182001E+09 | 625.08 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.50 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -5.3 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 10.30 |
November | 0.00 | 0.00 | 01-NOV-00:05 | -5.7 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 2.77 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -5.7 | |
Maximum of Months | 0.00 | 0.00 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 897611.68 | 550.55 | 05-JAN-09:04 | -17.0 |
February | 2125765.49 | 377.95 | 05-FEB-16:00 | -6.0 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 1748928.25 | 275.81 | 31-OCT-14:00 | -7.0 |
November | 0.00 | 0.00 | 01-NOV-00:05 | -5.7 |
December | 31635929.54 | 2441.12 | 21-DEC-09:25 | -20.0 |
Annual Sum or Average | 36408234.96 | |||
Minimum of Months | 0.00 | 0.00 | -20.0 | |
Maximum of Months | 31635929.54 | 2441.12 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.50 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -5.3 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 10.30 |
November | 0.00 | 0.00 | 01-NOV-00:05 | -5.7 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 2.77 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -5.7 | |
Maximum of Months | 0.00 | 0.00 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.415627E+09 | 1705.80 | 05-JAN-09:13 | -17.0 |
February | 0.528049E+09 | 1706.94 | 05-FEB-16:13 | -6.3 |
March | 0.394614E+09 | 1685.43 | 19-MAR-08:62 | -13.0 |
April | 0.311313E+09 | 1647.64 | 03-APR-08:62 | -4.8 |
May | 20533975.27 | 1063.28 | 02-MAY-08:62 | 3.35 |
June | 414689.87 | 483.61 | 01-JUN-08:05 | 18.77 |
July | 373076.13 | 436.43 | 31-JUL-08:05 | 21.17 |
August | 540179.24 | 536.87 | 24-AUG-08:05 | 15.00 |
September | 7843852.32 | 1162.46 | 22-SEP-08:62 | 2.57 |
October | 0.277142E+09 | 1712.90 | 31-OCT-15:13 | -8.0 |
November | 0.360712E+09 | 1667.19 | 29-NOV-09:02 | -9.0 |
December | 0.799015E+09 | 1759.86 | 21-DEC-09:13 | -20.0 |
Annual Sum or Average | 0.311618E+10 | |||
Minimum of Months | 373076.13 | 436.43 | -20.0 | |
Maximum of Months | 0.799015E+09 | 1759.86 | 21.17 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.732510E+09 | 1705.87 | 05-JAN-19:13 | -18.3 |
February | 0.759508E+09 | 1702.24 | 05-FEB-16:13 | -6.3 |
March | 0.487209E+09 | 1679.11 | 19-MAR-08:62 | -13.0 |
April | 0.339369E+09 | 1642.14 | 02-APR-15:02 | -4.0 |
May | 22472476.13 | 1112.26 | 02-MAY-08:62 | 3.35 |
June | 67559.30 | 291.75 | 03-JUN-08:54 | 19.40 |
July | 86639.57 | 354.76 | 03-JUL-08:05 | 13.33 |
August | 289403.28 | 538.65 | 24-AUG-08:05 | 15.00 |
September | 9422025.40 | 1330.28 | 22-SEP-08:62 | 2.57 |
October | 0.324707E+09 | 1706.01 | 31-OCT-15:13 | -8.0 |
November | 0.566067E+09 | 1680.98 | 30-NOV-09:01 | -5.5 |
December | 0.114655E+10 | 1754.05 | 20-DEC-16:13 | -17.3 |
Annual Sum or Average | 0.438826E+10 | |||
Minimum of Months | 67559.30 | 291.75 | -18.3 | |
Maximum of Months | 0.114655E+10 | 1754.05 | 19.40 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.50 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -5.3 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 10.30 |
November | 0.00 | 0.00 | 01-NOV-00:05 | -5.7 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 2.77 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -5.7 | |
Maximum of Months | 0.00 | 0.00 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 96725082.40 | 495.31 | 05-JAN-16:02 | -15.2 |
February | 0.110639E+09 | 488.74 | 12-FEB-16:02 | -6.2 |
March | 34819170.09 | 475.63 | 19-MAR-15:02 | 0.00 |
April | 13330798.06 | 467.51 | 02-APR-15:02 | -4.0 |
May | 140052.22 | 362.84 | 03-MAY-15:04 | 16.17 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 2628.08 | 39.42 | 17-AUG-08:56 | 18.00 |
September | 78297.66 | 217.96 | 22-SEP-15:05 | 16.18 |
October | 25282546.93 | 483.55 | 31-OCT-15:13 | -8.0 |
November | 57143924.90 | 486.43 | 29-NOV-16:02 | -9.3 |
December | 0.176235E+09 | 501.45 | 21-DEC-16:13 | -18.7 |
Annual Sum or Average | 0.514396E+09 | |||
Minimum of Months | 0.00 | 0.00 | -18.7 | |
Maximum of Months | 0.176235E+09 | 501.45 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.444050E+09 | 1657.41 | 05-JAN-19:13 | -18.3 |
February | 0.563092E+09 | 1656.40 | 05-FEB-16:13 | -6.3 |
March | 0.390889E+09 | 1641.46 | 19-MAR-08:62 | -13.0 |
April | 0.300158E+09 | 1608.76 | 02-APR-15:02 | -4.0 |
May | 19697687.21 | 758.19 | 01-MAY-18:03 | 9.67 |
June | 20189.91 | 201.90 | 17-JUN-08:05 | 17.28 |
July | 42350.63 | 423.51 | 28-JUL-08:05 | 18.00 |
August | 42424.17 | 397.82 | 27-AUG-08:05 | 17.17 |
September | 6457713.59 | 454.90 | 22-SEP-08:62 | 2.57 |
October | 0.278033E+09 | 1659.66 | 31-OCT-15:13 | -8.0 |
November | 0.388927E+09 | 1627.04 | 28-NOV-16:02 | -7.2 |
December | 0.817419E+09 | 1703.93 | 20-DEC-16:13 | -17.3 |
Annual Sum or Average | 0.320883E+10 | |||
Minimum of Months | 20189.91 | 201.90 | -18.3 | |
Maximum of Months | 0.817419E+09 | 1703.93 | 18.00 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.765493E+09 | 1674.71 | 05-JAN-16:13 | -15.3 |
February | 0.788363E+09 | 1651.47 | 05-FEB-16:13 | -6.3 |
March | 0.470385E+09 | 1635.15 | 19-MAR-08:62 | -13.0 |
April | 0.333261E+09 | 1603.65 | 02-APR-15:02 | -4.0 |
May | 21639631.41 | 779.03 | 01-MAY-18:03 | 9.67 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 15.88 |
July | 3903.19 | 45.54 | 28-JUL-21:56 | 16.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.93 |
September | 8140724.90 | 639.35 | 22-SEP-08:62 | 2.57 |
October | 0.330340E+09 | 1652.76 | 31-OCT-15:13 | -8.0 |
November | 0.610025E+09 | 1643.65 | 29-NOV-16:13 | -9.7 |
December | 0.115540E+10 | 1708.84 | 21-DEC-16:13 | -18.7 |
Annual Sum or Average | 0.448305E+10 | |||
Minimum of Months | 0.00 | 0.00 | -18.7 | |
Maximum of Months | 0.115540E+10 | 1708.84 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 6969888.50 | 511.76 | 05-JAN-09:04 | -17.0 |
February | 51503580.88 | 728.06 | 05-FEB-16:00 | -6.0 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 |
April | 924666.18 | 146.78 | 03-APR-08:03 | -4.8 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 25037835.85 | 669.00 | 31-OCT-13:50 | -7.0 |
November | 6016801.39 | 442.40 | 01-NOV-08:03 | -2.0 |
December | 96813703.02 | 1206.66 | 21-DEC-09:13 | -20.0 |
Annual Sum or Average | 0.187266E+09 | |||
Minimum of Months | 0.00 | 0.00 | -20.0 | |
Maximum of Months | 96813703.02 | 1206.66 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.761079E+09 | 2072.01 | 05-JAN-09:13 | -17.0 |
February | 0.853580E+09 | 2066.02 | 05-FEB-16:13 | -6.3 |
March | 0.660736E+09 | 2027.56 | 19-MAR-08:62 | -13.0 |
April | 0.538704E+09 | 1979.68 | 02-APR-15:02 | -4.0 |
May | 56367250.67 | 1724.22 | 02-MAY-08:62 | 3.35 |
June | 615774.64 | 535.28 | 09-JUN-08:04 | 14.77 |
July | 496964.84 | 412.85 | 21-JUL-08:05 | 23.17 |
August | 872386.21 | 584.82 | 13-AUG-08:04 | 15.17 |
September | 24582343.91 | 1842.42 | 22-SEP-08:62 | 2.57 |
October | 0.492875E+09 | 2071.75 | 31-OCT-15:13 | -8.0 |
November | 0.643870E+09 | 2006.44 | 28-NOV-16:02 | -7.2 |
December | 0.124827E+10 | 2123.94 | 21-DEC-09:13 | -20.0 |
Annual Sum or Average | 0.528205E+10 | |||
Minimum of Months | 496964.84 | 412.85 | -20.0 | |
Maximum of Months | 0.124827E+10 | 2123.94 | 23.17 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.121137E+10 | 2073.08 | 05-JAN-19:13 | -18.3 |
February | 0.117514E+10 | 2057.08 | 05-FEB-16:13 | -6.3 |
March | 0.795556E+09 | 2017.54 | 19-MAR-08:62 | -13.0 |
April | 0.578554E+09 | 1970.43 | 02-APR-15:02 | -4.0 |
May | 56308779.88 | 1759.67 | 02-MAY-08:62 | 3.35 |
June | 81992.83 | 416.08 | 16-JUN-08:05 | 15.78 |
July | 103660.25 | 454.20 | 03-JUL-08:05 | 13.33 |
August | 322828.23 | 459.44 | 15-AUG-08:05 | 14.17 |
September | 28649194.52 | 1840.30 | 22-SEP-08:62 | 2.57 |
October | 0.590276E+09 | 2060.69 | 31-OCT-15:13 | -8.0 |
November | 0.960454E+09 | 2012.41 | 30-NOV-09:01 | -5.5 |
December | 0.170242E+10 | 2115.53 | 21-DEC-19:13 | -20.3 |
Annual Sum or Average | 0.709923E+10 | |||
Minimum of Months | 81992.83 | 416.08 | -20.3 | |
Maximum of Months | 0.170242E+10 | 2115.53 | 15.78 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.140213E+09 | 1059.82 | 05-JAN-09:13 | -17.0 |
February | 0.236546E+09 | 1069.71 | 06-FEB-16:13 | -3.3 |
March | 0.209736E+09 | 1041.03 | 19-MAR-08:62 | -13.0 |
April | 0.177791E+09 | 1031.25 | 02-APR-15:02 | -4.0 |
May | 12908334.52 | 488.76 | 02-MAY-08:62 | 3.35 |
June | 219925.24 | 208.63 | 21-JUN-08:05 | 19.68 |
July | 80678.13 | 181.31 | 03-JUL-08:05 | 13.33 |
August | 80472.57 | 198.15 | 02-AUG-08:05 | 20.00 |
September | 4094640.89 | 609.99 | 22-SEP-08:62 | 2.57 |
October | 0.152573E+09 | 1073.60 | 31-OCT-15:13 | -8.0 |
November | 0.142328E+09 | 1036.13 | 28-NOV-16:02 | -7.2 |
December | 0.316146E+09 | 1092.32 | 20-DEC-16:13 | -17.3 |
Annual Sum or Average | 0.139272E+10 | |||
Minimum of Months | 80472.57 | 181.31 | -17.3 | |
Maximum of Months | 0.316146E+09 | 1092.32 | 20.00 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.50 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -5.3 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 10.30 |
November | 0.00 | 0.00 | 01-NOV-00:05 | -5.7 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 2.77 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -5.7 | |
Maximum of Months | 0.00 | 0.00 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.50 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -5.3 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 10.30 |
November | 0.00 | 0.00 | 01-NOV-00:05 | -5.7 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 2.77 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -5.7 | |
Maximum of Months | 0.00 | 0.00 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.50 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -5.3 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 10.30 |
November | 0.00 | 0.00 | 01-NOV-00:05 | -5.7 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 2.77 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -5.7 | |
Maximum of Months | 0.00 | 0.00 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.182525E+09 | 2225.34 | 05-JAN-09:06 | -17.0 |
February | 0.266565E+09 | 1930.89 | 12-FEB-05:40 | -19.3 |
March | 41168180.79 | 1029.23 | 05-MAR-06:00 | -12.0 |
April | 16097593.32 | 684.68 | 03-APR-06:05 | -7.7 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 0.100210E+09 | 1293.35 | 31-OCT-14:00 | -7.0 |
November | 0.105631E+09 | 1653.32 | 30-NOV-07:10 | -11.3 |
December | 0.813981E+09 | 3485.67 | 21-DEC-08:02 | -20.0 |
Annual Sum or Average | 0.152618E+10 | |||
Minimum of Months | 0.00 | 0.00 | -20.0 | |
Maximum of Months | 0.813981E+09 | 3485.67 | 22.27 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.136942E+11 | 13190.31 | 02-JAN-20:10 | 0.121516E+11 | 9632.53 | 02-JAN-20:10 |
February | 0.123646E+11 | 13190.31 | 01-FEB-20:10 | 0.109726E+11 | 9632.53 | 01-FEB-20:10 |
March | 0.137364E+11 | 13190.31 | 01-MAR-20:10 | 0.121771E+11 | 9632.53 | 01-MAR-20:10 |
April | 0.132299E+11 | 13190.31 | 03-APR-19:10 | 0.117446E+11 | 9632.53 | 03-APR-19:10 |
May | 0.137180E+11 | 13190.31 | 01-MAY-19:10 | 0.121662E+11 | 9632.53 | 01-MAY-19:10 |
June | 0.132906E+11 | 13190.31 | 01-JUN-19:10 | 0.117829E+11 | 9632.53 | 01-JUN-19:10 |
July | 0.136573E+11 | 13190.31 | 03-JUL-19:10 | 0.121279E+11 | 9632.53 | 03-JUL-19:10 |
August | 0.137417E+11 | 13190.31 | 01-AUG-19:10 | 0.121808E+11 | 9632.53 | 01-AUG-19:10 |
September | 0.132352E+11 | 13190.31 | 01-SEP-19:10 | 0.117482E+11 | 9632.53 | 01-SEP-19:10 |
October | 0.136889E+11 | 13190.31 | 02-OCT-19:10 | 0.121479E+11 | 9632.53 | 02-OCT-19:10 |
November | 0.132800E+11 | 13190.31 | 01-NOV-19:10 | 0.117774E+11 | 9632.53 | 01-NOV-19:10 |
December | 0.136573E+11 | 13190.31 | 01-DEC-20:10 | 0.121279E+11 | 9632.53 | 01-DEC-20:10 |
Annual Sum or Average | 0.161294E+12 | 0.143105E+12 | ||||
Minimum of Months | 0.123646E+11 | 13190.31 | 0.109726E+11 | 9632.53 | ||
Maximum of Months | 0.137417E+11 | 13190.31 | 0.121808E+11 | 9632.53 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.620421E+09 | 597.59 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.560184E+09 | 597.59 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.622334E+09 | 597.59 | 01-MAR-20:10 | 0.866718E+09 | 685.60 | 01-MAR-20:10 |
April | 0.599386E+09 | 597.59 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.621497E+09 | 597.59 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.602135E+09 | 597.59 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.618748E+09 | 597.59 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.622573E+09 | 597.59 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.599625E+09 | 597.59 | 01-SEP-19:10 | 0.836191E+09 | 685.60 | 01-SEP-19:10 |
October | 0.620182E+09 | 597.59 | 02-OCT-19:10 | 0.864640E+09 | 685.60 | 02-OCT-19:10 |
November | 0.601657E+09 | 597.59 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.618748E+09 | 597.59 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.730749E+10 | 0.101856E+11 | ||||
Minimum of Months | 0.560184E+09 | 597.59 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.622573E+09 | 597.59 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.718450E+09 | 692.02 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.648695E+09 | 692.02 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.720665E+09 | 692.02 | 01-MAR-20:10 | 0.100366E+10 | 793.93 | 01-MAR-20:10 |
April | 0.694091E+09 | 692.02 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.719696E+09 | 692.02 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.697275E+09 | 692.02 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.716513E+09 | 692.02 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.720942E+09 | 692.02 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.694368E+09 | 692.02 | 01-SEP-19:10 | 0.968312E+09 | 793.93 | 01-SEP-19:10 |
October | 0.718174E+09 | 692.02 | 02-OCT-19:10 | 0.100126E+10 | 793.93 | 02-OCT-19:10 |
November | 0.696721E+09 | 692.02 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.716513E+09 | 692.02 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.846210E+10 | 0.117950E+11 | ||||
Minimum of Months | 0.648695E+09 | 692.02 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.720942E+09 | 692.02 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.710312E+09 | 684.18 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.641347E+09 | 684.18 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.712502E+09 | 684.18 | 01-MAR-20:10 | 0.106120E+10 | 839.45 | 01-MAR-20:10 |
April | 0.686229E+09 | 684.18 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.711544E+09 | 684.18 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.689376E+09 | 684.18 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.708397E+09 | 684.18 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.712775E+09 | 684.18 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.686503E+09 | 684.18 | 01-SEP-19:10 | 0.102382E+10 | 839.45 | 01-SEP-19:10 |
October | 0.710039E+09 | 684.18 | 02-OCT-19:10 | 0.105866E+10 | 839.45 | 02-OCT-19:10 |
November | 0.688829E+09 | 684.18 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.708397E+09 | 684.18 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.836625E+10 | 0.124712E+11 | ||||
Minimum of Months | 0.641347E+09 | 684.18 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.712775E+09 | 684.18 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.261454E+09 | 251.84 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.236069E+09 | 251.84 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.262260E+09 | 251.84 | 01-MAR-20:10 | 0.306128E+09 | 242.16 | 01-MAR-20:10 |
April | 0.252589E+09 | 251.84 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.261907E+09 | 251.84 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.253748E+09 | 251.84 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.260749E+09 | 251.84 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.262360E+09 | 251.84 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.252690E+09 | 251.84 | 01-SEP-19:10 | 0.295345E+09 | 242.16 | 01-SEP-19:10 |
October | 0.261353E+09 | 251.84 | 02-OCT-19:10 | 0.305393E+09 | 242.16 | 02-OCT-19:10 |
November | 0.253546E+09 | 251.84 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.260749E+09 | 251.84 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.307947E+10 | 0.359760E+10 | ||||
Minimum of Months | 0.236069E+09 | 251.84 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.262360E+09 | 251.84 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.337502E+09 | 325.08 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.304733E+09 | 325.08 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.338542E+09 | 325.08 | 01-MAR-20:10 | 0.578079E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.326059E+09 | 325.08 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.338087E+09 | 325.08 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.327554E+09 | 325.08 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.336592E+09 | 325.08 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.338672E+09 | 325.08 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.326189E+09 | 325.08 | 01-SEP-19:10 | 0.557718E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.337372E+09 | 325.08 | 02-OCT-19:10 | 0.576693E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.327294E+09 | 325.08 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.336592E+09 | 325.08 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.397519E+10 | 0.679355E+11 | ||||
Minimum of Months | 0.304733E+09 | 325.08 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.338672E+09 | 325.08 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.133720E+10 | 1701.53 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.117038E+10 | 1701.53 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.122572E+10 | 1701.53 | 01-MAR-20:10 | 0.122027E+10 | 965.27 | 01-MAR-20:10 |
April | 0.111406E+10 | 1701.53 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.104558E+10 | 1701.53 | 01-MAY-19:10 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.955454E+09 | 1701.53 | 01-JUN-19:19 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.100549E+10 | 1701.53 | 03-JUL-19:19 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.110602E+10 | 1701.53 | 01-AUG-19:10 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.114071E+10 | 1701.53 | 01-SEP-19:10 | 0.117729E+10 | 965.27 | 01-SEP-19:10 |
October | 0.129645E+10 | 1701.53 | 02-OCT-19:10 | 0.121734E+10 | 965.27 | 02-OCT-19:10 |
November | 0.128057E+10 | 1701.53 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.134932E+10 | 1701.53 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.140270E+11 | 0.143405E+11 | ||||
Minimum of Months | 0.955454E+09 | 1701.53 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.134932E+10 | 1701.53 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.944630E+10 | 9504.80 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.849836E+10 | 9504.80 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.938141E+10 | 9504.80 | 01-MAR-20:10 | 0.126786E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.898075E+10 | 9504.80 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.920653E+10 | 9504.80 | 01-MAY-19:10 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.887437E+10 | 9504.80 | 01-JUN-19:19 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.913916E+10 | 9504.80 | 03-JUL-19:19 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.927475E+10 | 9504.80 | 01-AUG-19:10 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.900291E+10 | 9504.80 | 01-SEP-19:10 | 0.122320E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.941533E+10 | 9504.80 | 02-OCT-19:10 | 0.126482E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.914999E+10 | 9504.80 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.943694E+10 | 9504.80 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.109807E+12 | 0.148998E+12 | ||||
Minimum of Months | 0.849836E+10 | 9504.80 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.944630E+10 | 9504.80 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196602E+09 | 177.88 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.177551E+09 | 177.88 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.195039E+09 | 177.88 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.190486E+09 | 177.88 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.195821E+09 | 177.88 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.188975E+09 | 177.88 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.197358E+09 | 177.88 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.195039E+09 | 177.88 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.190538E+09 | 177.88 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.196576E+09 | 177.88 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.189731E+09 | 177.88 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.197383E+09 | 177.88 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.231110E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.177551E+09 | 177.88 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.197383E+09 | 177.88 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196579E+09 | 177.86 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.177530E+09 | 177.86 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.195017E+09 | 177.86 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.190464E+09 | 177.86 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.195798E+09 | 177.86 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.188953E+09 | 177.86 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.197334E+09 | 177.86 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.195017E+09 | 177.86 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.190515E+09 | 177.86 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.196553E+09 | 177.86 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.189708E+09 | 177.86 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.197360E+09 | 177.86 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.231083E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.177530E+09 | 177.86 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.197360E+09 | 177.86 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123557E+09 | 111.79 | 01-JAN-19:10 | 0.217935E+09 | 232.19 | 01-JAN-08:09 |
February | 0.111584E+09 | 111.79 | 01-FEB-20:10 | 0.196843E+09 | 232.19 | 01-FEB-07:10 |
March | 0.122575E+09 | 111.79 | 01-MAR-20:10 | 0.217824E+09 | 232.19 | 01-MAR-07:10 |
April | 0.119713E+09 | 111.79 | 01-APR-18:10 | 0.210923E+09 | 232.19 | 01-APR-07:10 |
May | 0.123066E+09 | 111.79 | 01-MAY-19:10 | 0.217879E+09 | 232.19 | 01-MAY-06:10 |
June | 0.118764E+09 | 111.79 | 01-JUN-19:10 | 0.210812E+09 | 232.19 | 01-JUN-06:10 |
July | 0.124032E+09 | 111.79 | 01-JUL-18:10 | 0.217991E+09 | 232.19 | 01-JUL-07:10 |
August | 0.122575E+09 | 111.79 | 01-AUG-19:10 | 0.217824E+09 | 232.19 | 01-AUG-06:10 |
September | 0.119746E+09 | 111.79 | 01-SEP-19:10 | 0.210923E+09 | 232.19 | 01-SEP-06:10 |
October | 0.123541E+09 | 111.79 | 01-OCT-18:10 | 0.217935E+09 | 232.19 | 01-OCT-07:10 |
November | 0.119238E+09 | 111.79 | 01-NOV-19:10 | 0.210867E+09 | 232.19 | 01-NOV-06:10 |
December | 0.124048E+09 | 111.79 | 01-DEC-20:10 | 0.217991E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.145244E+10 | 0.256575E+10 | ||||
Minimum of Months | 0.111584E+09 | 111.79 | 0.196843E+09 | 232.19 | ||
Maximum of Months | 0.124048E+09 | 111.79 | 0.217991E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123591E+09 | 111.82 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 0.111614E+09 | 111.82 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 0.122608E+09 | 111.82 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 0.119746E+09 | 111.82 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 0.123099E+09 | 111.82 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 0.118796E+09 | 111.82 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 0.124066E+09 | 111.82 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 0.122608E+09 | 111.82 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 0.119778E+09 | 111.82 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 0.123574E+09 | 111.82 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 0.119271E+09 | 111.82 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 0.124082E+09 | 111.82 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.145283E+10 | 0.256645E+10 | ||||
Minimum of Months | 0.111614E+09 | 111.82 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 0.124082E+09 | 111.82 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196602E+09 | 177.88 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.177551E+09 | 177.88 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.195039E+09 | 177.88 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.190486E+09 | 177.88 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.195821E+09 | 177.88 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.188975E+09 | 177.88 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.197358E+09 | 177.88 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.195039E+09 | 177.88 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.190538E+09 | 177.88 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.196576E+09 | 177.88 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.189731E+09 | 177.88 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.197383E+09 | 177.88 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.231110E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.177551E+09 | 177.88 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.197383E+09 | 177.88 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196579E+09 | 177.86 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.177530E+09 | 177.86 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.195017E+09 | 177.86 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.190464E+09 | 177.86 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.195798E+09 | 177.86 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.188953E+09 | 177.86 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.197334E+09 | 177.86 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.195017E+09 | 177.86 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.190515E+09 | 177.86 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.196553E+09 | 177.86 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.189708E+09 | 177.86 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.197360E+09 | 177.86 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.231083E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.177530E+09 | 177.86 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.197360E+09 | 177.86 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.193865E+10 | 1867.32 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.175042E+10 | 1867.32 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.194462E+10 | 1867.32 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.187292E+10 | 1867.32 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.194201E+10 | 1867.32 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.188151E+10 | 1867.32 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.193342E+10 | 1867.32 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.194537E+10 | 1867.32 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.187367E+10 | 1867.32 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.193790E+10 | 1867.32 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.188002E+10 | 1867.32 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.193342E+10 | 1867.32 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.228339E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.175042E+10 | 1867.32 | 0.00 | 0.00 | |
Maximum of Months | 0.194537E+10 | 1867.32 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196602E+09 | 177.88 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.177551E+09 | 177.88 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.195039E+09 | 177.88 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.190486E+09 | 177.88 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.195821E+09 | 177.88 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.188975E+09 | 177.88 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.197358E+09 | 177.88 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.195039E+09 | 177.88 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.190538E+09 | 177.88 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.196576E+09 | 177.88 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.189731E+09 | 177.88 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.197383E+09 | 177.88 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.231110E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.177551E+09 | 177.88 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.197383E+09 | 177.88 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196579E+09 | 177.86 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.177530E+09 | 177.86 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.195017E+09 | 177.86 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.190464E+09 | 177.86 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.195798E+09 | 177.86 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.188953E+09 | 177.86 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.197334E+09 | 177.86 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.195017E+09 | 177.86 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.190515E+09 | 177.86 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.196553E+09 | 177.86 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.189708E+09 | 177.86 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.197360E+09 | 177.86 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.231083E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.177530E+09 | 177.86 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.197360E+09 | 177.86 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123591E+09 | 111.82 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 0.111614E+09 | 111.82 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 0.122608E+09 | 111.82 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 0.119746E+09 | 111.82 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 0.123099E+09 | 111.82 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 0.118796E+09 | 111.82 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 0.124066E+09 | 111.82 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 0.122608E+09 | 111.82 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 0.119778E+09 | 111.82 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 0.123574E+09 | 111.82 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 0.119271E+09 | 111.82 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 0.124082E+09 | 111.82 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.145283E+10 | 0.256645E+10 | ||||
Minimum of Months | 0.111614E+09 | 111.82 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 0.124082E+09 | 111.82 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.280433E+10 | 2988.03 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.247269E+10 | 2988.03 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.265069E+10 | 2988.03 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.247185E+10 | 2988.03 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.244435E+10 | 2988.03 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.229353E+10 | 2988.03 | 01-JUN-19:19 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.238660E+10 | 2988.03 | 03-JUL-19:30 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.250716E+10 | 2988.03 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.251260E+10 | 2988.03 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.271903E+10 | 2988.03 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.268606E+10 | 2988.03 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.279887E+10 | 2988.03 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.307478E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.229353E+10 | 2988.03 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.280433E+10 | 2988.03 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.280433E+10 | 2988.03 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.247269E+10 | 2988.03 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.265069E+10 | 2988.03 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.247185E+10 | 2988.03 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.244435E+10 | 2988.03 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.229353E+10 | 2988.03 | 01-JUN-19:19 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.238660E+10 | 2988.03 | 03-JUL-19:30 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.250716E+10 | 2988.03 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.251260E+10 | 2988.03 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.271903E+10 | 2988.03 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.268606E+10 | 2988.03 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.279887E+10 | 2988.03 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.307478E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.229353E+10 | 2988.03 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.280433E+10 | 2988.03 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.110133E+10 | 1060.81 | 02-JAN-20:10 | 0.368383E+11 | 16487.34 | 01-JAN-07:10 |
February | 0.994402E+09 | 1060.81 | 01-FEB-20:10 | 0.332733E+11 | 16487.34 | 01-FEB-07:10 |
March | 0.110473E+10 | 1060.81 | 01-MAR-20:10 | 0.368383E+11 | 16487.34 | 01-MAR-07:10 |
April | 0.106399E+10 | 1060.81 | 03-APR-19:10 | 0.356500E+11 | 16487.34 | 01-APR-06:10 |
May | 0.110324E+10 | 1060.81 | 01-MAY-19:10 | 0.368383E+11 | 16487.34 | 01-MAY-06:10 |
June | 0.106887E+10 | 1060.81 | 01-JUN-19:10 | 0.356500E+11 | 16487.34 | 01-JUN-06:10 |
July | 0.109836E+10 | 1060.81 | 03-JUL-19:10 | 0.368383E+11 | 16487.34 | 01-JUL-06:10 |
August | 0.110515E+10 | 1060.81 | 01-AUG-19:10 | 0.368383E+11 | 16487.34 | 01-AUG-06:10 |
September | 0.106442E+10 | 1060.81 | 01-SEP-19:10 | 0.356500E+11 | 16487.34 | 01-SEP-06:10 |
October | 0.110091E+10 | 1060.81 | 02-OCT-19:10 | 0.368383E+11 | 16487.34 | 01-OCT-06:10 |
November | 0.106802E+10 | 1060.81 | 01-NOV-19:10 | 0.356500E+11 | 16487.34 | 01-NOV-06:10 |
December | 0.109836E+10 | 1060.81 | 01-DEC-20:10 | 0.368383E+11 | 16487.34 | 01-DEC-07:10 |
Annual Sum or Average | 0.129718E+11 | 0.433742E+12 | ||||
Minimum of Months | 0.994402E+09 | 1060.81 | 0.332733E+11 | 16487.34 | ||
Maximum of Months | 0.110515E+10 | 1060.81 | 0.368383E+11 | 16487.34 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.205176E+10 | 1976.27 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.185255E+10 | 1976.27 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.205809E+10 | 1976.27 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.198220E+10 | 1976.27 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.205532E+10 | 1976.27 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.199129E+10 | 1976.27 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.204623E+10 | 1976.27 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.205888E+10 | 1976.27 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.198299E+10 | 1976.27 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.205097E+10 | 1976.27 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.198971E+10 | 1976.27 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.204623E+10 | 1976.27 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.241662E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.185255E+10 | 1976.27 | 0.00 | 0.00 | |
Maximum of Months | 0.205888E+10 | 1976.27 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.136942E+11 | 0.121516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.123646E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196682E+11 | 0.137364E+11 | 0.121771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.132299E+11 | 0.117446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.137180E+11 | 0.121662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.132906E+11 | 0.117829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.136573E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.137417E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189689E+11 | 0.132352E+11 | 0.117482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195854E+11 | 0.136889E+11 | 0.121479E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.132800E+11 | 0.117774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.136573E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230861E+12 | 0.161294E+12 | 0.143105E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.176991E+11 | 0.123646E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196682E+11 | 0.137417E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.620421E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265385E+09 |
February | 0.179968E+10 | 0.560184E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253404E+09 |
March | 0.199990E+10 | 0.622334E+09 | 0.866718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213313E+09 |
April | 0.192973E+10 | 0.599386E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186632E+09 |
May | 0.199475E+10 | 0.621497E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1438638.89 | 0.104971E+09 |
June | 0.193394E+10 | 0.602135E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21180280.90 | 36168882.98 |
July | 0.199054E+10 | 0.618748E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22502549.43 | 31871046.99 |
August | 0.199896E+10 | 0.622573E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17924238.22 | 38897679.61 |
September | 0.192879E+10 | 0.599625E+09 | 0.836191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8795334.98 | 64859186.92 |
October | 0.199148E+10 | 0.620182E+09 | 0.864640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 178137.56 | 0.188977E+09 |
November | 0.192552E+10 | 0.601657E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230466E+09 |
December | 0.199054E+10 | 0.618748E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291220E+09 |
Annual Sum or Average | 0.234744E+11 | 0.730749E+10 | 0.101856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 72019179.98 | 0.190617E+10 |
Minimum of Months | 0.179968E+10 | 0.560184E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31871046.99 |
Maximum of Months | 0.199990E+10 | 0.622573E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22502549.43 | 0.291220E+09 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.718450E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107288E+09 |
February | 0.208403E+10 | 0.648695E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101468E+09 |
March | 0.231589E+10 | 0.720665E+09 | 0.100366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 906.73 | 86805755.82 |
April | 0.223463E+10 | 0.694091E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77608233.94 |
May | 0.230993E+10 | 0.719696E+09 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 614194.46 | 46320111.80 |
June | 0.223950E+10 | 0.697275E+09 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8213967.75 | 16332515.07 |
July | 0.230505E+10 | 0.716513E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8725463.84 | 14642462.54 |
August | 0.231480E+10 | 0.720942E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7033369.11 | 17359055.51 |
September | 0.223354E+10 | 0.694368E+09 | 0.968312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3484339.48 | 27753231.61 |
October | 0.230614E+10 | 0.718174E+09 | 0.100126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79901.14 | 77602553.46 |
November | 0.222975E+10 | 0.696721E+09 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93438049.24 |
December | 0.230505E+10 | 0.716513E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116652E+09 |
Annual Sum or Average | 0.271834E+11 | 0.846210E+10 | 0.117950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 28152142.51 | 0.783270E+09 |
Minimum of Months | 0.208403E+10 | 0.648695E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14642462.54 |
Maximum of Months | 0.231589E+10 | 0.720942E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8725463.84 | 0.116652E+09 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.487480E+09 | 0.710312E+09 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238377E+09 |
February | 0.440737E+09 | 0.641347E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226337E+09 |
March | 0.489771E+09 | 0.712502E+09 | 0.106120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21163.67 | 0.193154E+09 |
April | 0.472586E+09 | 0.686229E+09 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173359E+09 |
May | 0.488511E+09 | 0.711544E+09 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1764223.49 | 0.104840E+09 |
June | 0.473617E+09 | 0.689376E+09 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19338144.43 | 38290360.33 |
July | 0.487480E+09 | 0.708397E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20365325.54 | 34435923.30 |
August | 0.489542E+09 | 0.712775E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16693379.35 | 40642473.96 |
September | 0.472357E+09 | 0.686503E+09 | 0.102382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8624919.33 | 63657749.89 |
October | 0.487709E+09 | 0.710039E+09 | 0.105866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 295786.56 | 0.174608E+09 |
November | 0.471555E+09 | 0.688829E+09 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207955E+09 |
December | 0.487480E+09 | 0.708397E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5909.63 | 0.262528E+09 |
Annual Sum or Average | 0.574883E+10 | 0.836625E+10 | 0.124712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 67108852.01 | 0.175819E+10 |
Minimum of Months | 0.440737E+09 | 0.641347E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34435923.30 |
Maximum of Months | 0.489771E+09 | 0.712775E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20365325.54 | 0.262528E+09 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.374985E+09 | 0.261454E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135403E+09 |
February | 0.339028E+09 | 0.236069E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129220E+09 |
March | 0.376747E+09 | 0.262260E+09 | 0.306128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17520.08 | 0.109407E+09 |
April | 0.363528E+09 | 0.252589E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 112.05 | 97884199.27 |
May | 0.375778E+09 | 0.261907E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1088320.55 | 58389030.39 |
June | 0.364321E+09 | 0.253748E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11325445.84 | 21446722.68 |
July | 0.374985E+09 | 0.260749E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11870717.72 | 19334149.47 |
August | 0.376571E+09 | 0.262360E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9819120.93 | 22659107.52 |
September | 0.363352E+09 | 0.252690E+09 | 0.295345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5137479.59 | 35371679.31 |
October | 0.375161E+09 | 0.261353E+09 | 0.305393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 186879.05 | 98355268.65 |
November | 0.362735E+09 | 0.253546E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117778E+09 |
December | 0.374985E+09 | 0.260749E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3134.55 | 0.149804E+09 |
Annual Sum or Average | 0.442217E+10 | 0.307947E+10 | 0.359760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39448730.37 | 0.995052E+09 |
Minimum of Months | 0.339028E+09 | 0.236069E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19334149.47 |
Maximum of Months | 0.376747E+09 | 0.262360E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11870717.72 | 0.149804E+09 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.337502E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.353809E+09 |
February | 0.139600E+10 | 0.304733E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.336750E+09 |
March | 0.155131E+10 | 0.338542E+09 | 0.578079E+10 | 0.502211E+11 | 0.00 | 0.00 | 0.00 | 12635.48 | 0.288804E+09 |
April | 0.149688E+10 | 0.326059E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260066E+09 |
May | 0.154732E+10 | 0.338087E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 1674457.13 | 0.151196E+09 |
June | 0.150015E+10 | 0.327554E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 26704382.34 | 49890283.08 |
July | 0.154405E+10 | 0.336592E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 28481106.00 | 44395318.31 |
August | 0.155059E+10 | 0.338672E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 23069755.51 | 52871904.62 |
September | 0.149615E+10 | 0.326189E+09 | 0.557718E+10 | 0.484522E+11 | 0.00 | 0.00 | 0.00 | 11836673.58 | 87149434.08 |
October | 0.154478E+10 | 0.337372E+09 | 0.576693E+10 | 0.501006E+11 | 0.00 | 0.00 | 0.00 | 402551.94 | 0.254330E+09 |
November | 0.149361E+10 | 0.327294E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.307919E+09 |
December | 0.154405E+10 | 0.336592E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.389436E+09 |
Annual Sum or Average | 0.182090E+11 | 0.397519E+10 | 0.679355E+11 | 0.590196E+12 | 0.00 | 0.00 | 0.00 | 92181561.99 | 0.257662E+10 |
Minimum of Months | 0.139600E+10 | 0.304733E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 44395318.31 |
Maximum of Months | 0.155131E+10 | 0.338672E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 28481106.00 | 0.389436E+09 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.133720E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.620134E+09 |
February | 0.236489E+11 | 0.117038E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.586976E+09 |
March | 0.262800E+11 | 0.122572E+10 | 0.122027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.498770E+09 |
April | 0.253579E+11 | 0.111406E+10 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.442764E+09 |
May | 0.262123E+11 | 0.104558E+10 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2810490.49 | 0.264714E+09 |
June | 0.254132E+11 | 0.955454E+09 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46512512.33 | 92132527.21 |
July | 0.261570E+11 | 0.100549E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49528599.02 | 82599831.73 |
August | 0.262677E+11 | 0.110602E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39366264.58 | 98196519.59 |
September | 0.253456E+11 | 0.114071E+10 | 0.117729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19403622.09 | 0.158211E+09 |
October | 0.261693E+11 | 0.129645E+10 | 0.121734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 394550.76 | 0.443705E+09 |
November | 0.253025E+11 | 0.128057E+10 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.539360E+09 |
December | 0.261570E+11 | 0.134932E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.674403E+09 |
Annual Sum or Average | 0.308468E+12 | 0.140270E+11 | 0.143405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158016E+09 | 0.450196E+10 |
Minimum of Months | 0.236489E+11 | 0.955454E+09 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82599831.73 |
Maximum of Months | 0.262800E+11 | 0.134932E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49528599.02 | 0.674403E+09 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.944630E+10 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179668E+10 |
February | 0.702046E+11 | 0.849836E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169872E+10 |
March | 0.780153E+11 | 0.938141E+10 | 0.126786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145301E+10 |
April | 0.752779E+11 | 0.898075E+10 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130019E+10 |
May | 0.778146E+11 | 0.920653E+10 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 9096763.09 | 0.772145E+09 |
June | 0.754422E+11 | 0.887437E+10 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134200E+09 | 0.267385E+09 |
July | 0.776503E+11 | 0.913916E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142323E+09 | 0.240024E+09 |
August | 0.779788E+11 | 0.927475E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113459E+09 | 0.284588E+09 |
September | 0.752414E+11 | 0.900291E+10 | 0.122320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 55877296.25 | 0.457767E+09 |
October | 0.776868E+11 | 0.941533E+10 | 0.126482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1126692.76 | 0.129262E+10 |
November | 0.751137E+11 | 0.914999E+10 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156464E+10 |
December | 0.776503E+11 | 0.943694E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195579E+10 |
Annual Sum or Average | 0.915726E+12 | 0.109807E+12 | 0.148998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.456083E+09 | 0.130835E+11 |
Minimum of Months | 0.702046E+11 | 0.849836E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240024E+09 |
Maximum of Months | 0.780153E+11 | 0.944630E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142323E+09 | 0.195579E+10 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196602E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149538E+09 |
February | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142638E+09 |
March | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35763.24 | 0.118928E+09 |
April | 0.293479E+09 | 0.190486E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105699E+09 |
May | 0.303504E+09 | 0.195821E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1437627.40 | 57574393.09 |
June | 0.293842E+09 | 0.188975E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16253318.82 | 14988525.53 |
July | 0.303141E+09 | 0.197358E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17633776.54 | 12311806.43 |
August | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14229030.68 | 15574369.00 |
September | 0.293479E+09 | 0.190538E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7490978.90 | 30033912.10 |
October | 0.303322E+09 | 0.196576E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 237049.54 | 0.103515E+09 |
November | 0.293661E+09 | 0.189731E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128809E+09 |
December | 0.303141E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164833E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231110E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57317545.13 | 0.104444E+10 |
Minimum of Months | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12311806.43 |
Maximum of Months | 0.303685E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17633776.54 | 0.164833E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196579E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146677E+09 |
February | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140362E+09 |
March | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7086.42 | 0.118638E+09 |
April | 0.293479E+09 | 0.190464E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105972E+09 |
May | 0.303504E+09 | 0.195798E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1315405.96 | 60295982.87 |
June | 0.293842E+09 | 0.188953E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15367819.06 | 18283072.08 |
July | 0.303141E+09 | 0.197334E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16813249.42 | 16000751.36 |
August | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13614575.15 | 19174872.38 |
September | 0.293479E+09 | 0.190515E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7116555.66 | 33487283.55 |
October | 0.303322E+09 | 0.196553E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 235652.03 | 0.103680E+09 |
November | 0.293661E+09 | 0.189708E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126759E+09 |
December | 0.303141E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162452E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231083E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54470343.71 | 0.105178E+10 |
Minimum of Months | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16000751.36 |
Maximum of Months | 0.303685E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16813249.42 | 0.162452E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.123557E+09 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51217394.26 |
February | 0.00 | 0.111584E+09 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46548934.95 |
March | 0.00 | 0.122575E+09 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40288091.36 |
April | 0.00 | 0.119713E+09 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37298135.68 |
May | 0.00 | 0.123066E+09 | 0.217879E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 28992.49 | 25090710.37 |
June | 0.00 | 0.118764E+09 | 0.210812E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1825012.40 | 10372128.49 |
July | 0.00 | 0.124032E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1895649.96 | 9674856.63 |
August | 0.00 | 0.122575E+09 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1421087.19 | 11061785.35 |
September | 0.00 | 0.119746E+09 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 545078.56 | 15931543.09 |
October | 0.00 | 0.123541E+09 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 218.73 | 37697549.54 |
November | 0.00 | 0.119238E+09 | 0.210867E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44478878.13 |
December | 0.00 | 0.124048E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52899399.56 |
Annual Sum or Average | 0.00 | 0.145244E+10 | 0.256575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5716039.32 | 0.382559E+09 |
Minimum of Months | 0.00 | 0.111584E+09 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9674856.63 |
Maximum of Months | 0.00 | 0.124048E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1895649.96 | 52899399.56 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.123591E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40968639.73 |
February | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39205254.50 |
March | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9987.79 | 32969157.25 |
April | 0.293479E+09 | 0.119746E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29547854.48 |
May | 0.303504E+09 | 0.123099E+09 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 396685.82 | 16388694.42 |
June | 0.293842E+09 | 0.118796E+09 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4398069.61 | 4786623.55 |
July | 0.303141E+09 | 0.124066E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4708345.98 | 4151330.75 |
August | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3920920.00 | 4957428.25 |
September | 0.293479E+09 | 0.119778E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2076505.94 | 8850622.06 |
October | 0.303322E+09 | 0.123574E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 85890.57 | 28663112.14 |
November | 0.293661E+09 | 0.119271E+09 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1550.87 | 35339460.54 |
December | 0.303141E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3111.72 | 45479628.77 |
Annual Sum or Average | 0.357224E+10 | 0.145283E+10 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15601068.29 | 0.291308E+09 |
Minimum of Months | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4151330.75 |
Maximum of Months | 0.303685E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4708345.98 | 45479628.77 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196602E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149788E+09 |
February | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142942E+09 |
March | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 43245.90 | 0.119442E+09 |
April | 0.293479E+09 | 0.190486E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106336E+09 |
May | 0.303504E+09 | 0.195821E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1424527.75 | 57962486.34 |
June | 0.293842E+09 | 0.188975E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16413149.81 | 15177542.64 |
July | 0.303141E+09 | 0.197358E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17542209.83 | 12392631.20 |
August | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14364916.50 | 15762042.87 |
September | 0.293479E+09 | 0.190538E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7551822.54 | 30288537.32 |
October | 0.303322E+09 | 0.196576E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 261804.48 | 0.103766E+09 |
November | 0.293661E+09 | 0.189731E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128889E+09 |
December | 0.303141E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164951E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231110E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57601676.80 | 0.104770E+10 |
Minimum of Months | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12392631.20 |
Maximum of Months | 0.303685E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17542209.83 | 0.164951E+09 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196579E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146393E+09 |
February | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140498E+09 |
March | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7717.99 | 0.118792E+09 |
April | 0.293479E+09 | 0.190464E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106367E+09 |
May | 0.303504E+09 | 0.195798E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1284093.90 | 60275176.65 |
June | 0.293842E+09 | 0.188953E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15408745.88 | 19639619.00 |
July | 0.303141E+09 | 0.197334E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16549946.70 | 16977880.06 |
August | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13555021.67 | 20261215.92 |
September | 0.293479E+09 | 0.190515E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7062025.41 | 33556047.90 |
October | 0.303322E+09 | 0.196553E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 236847.19 | 0.103616E+09 |
November | 0.293661E+09 | 0.189708E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126397E+09 |
December | 0.303141E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5345.70 | 0.162132E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231083E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54109744.43 | 0.105491E+10 |
Minimum of Months | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16977880.06 |
Maximum of Months | 0.303685E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16549946.70 | 0.162132E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.385223E+10 | 0.193865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182707E+09 |
February | 0.348285E+10 | 0.175042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174254E+09 |
March | 0.387034E+10 | 0.194462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3496.20 | 0.148180E+09 |
April | 0.373454E+10 | 0.187292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131064E+09 |
May | 0.386038E+10 | 0.194201E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1460204.69 | 77951208.62 |
June | 0.374269E+10 | 0.188151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14903651.11 | 28932043.83 |
July | 0.385223E+10 | 0.193342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15580667.77 | 26271131.79 |
August | 0.386853E+10 | 0.194537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12605319.11 | 31055189.19 |
September | 0.373273E+10 | 0.187367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6344220.00 | 48915270.07 |
October | 0.385404E+10 | 0.193790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168688.17 | 0.134095E+09 |
November | 0.372639E+10 | 0.188002E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158783E+09 |
December | 0.385223E+10 | 0.193342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1540.17 | 0.200320E+09 |
Annual Sum or Average | 0.454292E+11 | 0.228339E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51067787.23 | 0.134253E+10 |
Minimum of Months | 0.348285E+10 | 0.175042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26271131.79 |
Maximum of Months | 0.387034E+10 | 0.194537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15580667.77 | 0.200320E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196602E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149416E+09 |
February | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142652E+09 |
March | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30645.06 | 0.118946E+09 |
April | 0.293479E+09 | 0.190486E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105685E+09 |
May | 0.303504E+09 | 0.195821E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1386497.93 | 57813904.70 |
June | 0.293842E+09 | 0.188975E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15981246.86 | 15163587.88 |
July | 0.303141E+09 | 0.197358E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17384904.55 | 12481338.19 |
August | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13978739.02 | 15754522.66 |
September | 0.293479E+09 | 0.190538E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7355239.72 | 30185786.47 |
October | 0.303322E+09 | 0.196576E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 225731.40 | 0.103582E+09 |
November | 0.293661E+09 | 0.189731E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128786E+09 |
December | 0.303141E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164642E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231110E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56343004.54 | 0.104511E+10 |
Minimum of Months | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12481338.19 |
Maximum of Months | 0.303685E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17384904.55 | 0.164642E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196579E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146290E+09 |
February | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140261E+09 |
March | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6374.48 | 0.118721E+09 |
April | 0.293479E+09 | 0.190464E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106119E+09 |
May | 0.303504E+09 | 0.195798E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1268986.80 | 60854735.47 |
June | 0.293842E+09 | 0.188953E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15117370.99 | 18485216.42 |
July | 0.303141E+09 | 0.197334E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16592638.17 | 16118716.34 |
August | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13397298.25 | 19340841.52 |
September | 0.293479E+09 | 0.190515E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7019251.43 | 33651956.78 |
October | 0.303322E+09 | 0.196553E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 230159.12 | 0.103787E+09 |
November | 0.293661E+09 | 0.189708E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126584E+09 |
December | 0.303141E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162221E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231083E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53632079.25 | 0.105243E+10 |
Minimum of Months | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16118716.34 |
Maximum of Months | 0.303685E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16592638.17 | 0.162221E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.123591E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77513254.27 |
February | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73822261.41 |
March | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13072.63 | 61412652.13 |
April | 0.293479E+09 | 0.119746E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54525175.57 |
May | 0.303504E+09 | 0.123099E+09 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 717793.43 | 29643785.49 |
June | 0.293842E+09 | 0.118796E+09 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8416731.99 | 7745891.39 |
July | 0.303141E+09 | 0.124066E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9021703.79 | 6377218.71 |
August | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7301561.52 | 8061718.40 |
September | 0.293479E+09 | 0.119778E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3763063.89 | 15536268.04 |
October | 0.303322E+09 | 0.123574E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 81934.05 | 53472767.67 |
November | 0.293661E+09 | 0.119271E+09 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66856842.07 |
December | 0.303141E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85678989.80 |
Annual Sum or Average | 0.357224E+10 | 0.145283E+10 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29315861.30 | 0.540647E+09 |
Minimum of Months | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6377218.71 |
Maximum of Months | 0.303685E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9021703.79 | 85678989.80 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.280433E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.407904E+09 |
February | 0.415303E+11 | 0.247269E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.388128E+09 |
March | 0.461508E+11 | 0.265069E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.335170E+09 |
April | 0.445315E+11 | 0.247185E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302726E+09 |
May | 0.460320E+11 | 0.244435E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1594247.69 | 0.179213E+09 |
June | 0.446286E+11 | 0.229353E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 28655200.77 | 61677182.67 |
July | 0.459349E+11 | 0.238660E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 30490565.06 | 55326289.65 |
August | 0.461292E+11 | 0.250716E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 24508960.49 | 65513259.39 |
September | 0.445099E+11 | 0.251260E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 12077361.63 | 0.104647E+09 |
October | 0.459565E+11 | 0.271903E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 256490.77 | 0.296022E+09 |
November | 0.444343E+11 | 0.268606E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.356270E+09 |
December | 0.459349E+11 | 0.279887E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.447199E+09 |
Annual Sum or Average | 0.541708E+12 | 0.307478E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 97582826.41 | 0.299980E+10 |
Minimum of Months | 0.415303E+11 | 0.229353E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55326289.65 |
Maximum of Months | 0.461508E+11 | 0.280433E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 30490565.06 | 0.447199E+09 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.280433E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.410105E+09 |
February | 0.415303E+11 | 0.247269E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.390181E+09 |
March | 0.461508E+11 | 0.265069E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.336800E+09 |
April | 0.445315E+11 | 0.247185E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.303944E+09 |
May | 0.460320E+11 | 0.244435E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1592213.20 | 0.179387E+09 |
June | 0.446286E+11 | 0.229353E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 28653357.06 | 61681302.20 |
July | 0.459349E+11 | 0.238660E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 30489161.83 | 55330894.34 |
August | 0.461292E+11 | 0.250716E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 24505196.63 | 65519911.00 |
September | 0.445099E+11 | 0.251260E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 12068339.39 | 0.104707E+09 |
October | 0.459565E+11 | 0.271903E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 240930.38 | 0.297158E+09 |
November | 0.444343E+11 | 0.268606E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357933E+09 |
December | 0.459349E+11 | 0.279887E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.449926E+09 |
Annual Sum or Average | 0.541708E+12 | 0.307478E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 97549198.49 | 0.301267E+10 |
Minimum of Months | 0.415303E+11 | 0.229353E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55330894.34 |
Maximum of Months | 0.461508E+11 | 0.280433E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 30489161.83 | 0.449926E+09 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.110133E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.367469E+09 |
February | 0.369574E+10 | 0.994402E+09 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.349488E+09 |
March | 0.410691E+10 | 0.110473E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.301460E+09 |
April | 0.396281E+10 | 0.106399E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.271848E+09 |
May | 0.409635E+10 | 0.110324E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 1432868.72 | 0.160414E+09 |
June | 0.397146E+10 | 0.106887E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 25650619.54 | 55205190.38 |
July | 0.408770E+10 | 0.109836E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 27243878.96 | 49517057.66 |
August | 0.410499E+10 | 0.110515E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 21939300.17 | 58634523.44 |
September | 0.396089E+10 | 0.106442E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 10822171.70 | 93668286.58 |
October | 0.408962E+10 | 0.110091E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 211040.38 | 0.266290E+09 |
November | 0.395417E+10 | 0.106802E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.320686E+09 |
December | 0.408770E+10 | 0.109836E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.403915E+09 |
Annual Sum or Average | 0.482060E+11 | 0.129718E+11 | 0.392709E+12 | 0.359593E+12 | 0.00 | 0.00 | 0.00 | 87299879.48 | 0.269859E+10 |
Minimum of Months | 0.369574E+10 | 0.994402E+09 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 49517057.66 |
Maximum of Months | 0.410691E+10 | 0.110515E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 27243878.96 | 0.403915E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.407704E+10 | 0.205176E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.321299E+09 |
February | 0.368610E+10 | 0.185255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.307768E+09 |
March | 0.409620E+10 | 0.205809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261620E+09 |
April | 0.395248E+10 | 0.198220E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232576E+09 |
May | 0.408566E+10 | 0.205532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1780470.93 | 0.138402E+09 |
June | 0.396110E+10 | 0.199129E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25266442.80 | 50768879.35 |
July | 0.407704E+10 | 0.204623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26857321.25 | 45499191.97 |
August | 0.409429E+10 | 0.205888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21605741.74 | 53709952.99 |
September | 0.395056E+10 | 0.198299E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10732746.08 | 83829950.46 |
October | 0.407896E+10 | 0.205097E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 212315.57 | 0.233920E+09 |
November | 0.394385E+10 | 0.198971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279707E+09 |
December | 0.407704E+10 | 0.204623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.354778E+09 |
Annual Sum or Average | 0.480803E+11 | 0.241662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86455038.37 | 0.236388E+10 |
Minimum of Months | 0.368610E+10 | 0.185255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45499191.97 |
Maximum of Months | 0.409620E+10 | 0.205888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26857321.25 | 0.354778E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 13190.31 | 02-JAN-20:10 | 9632.53 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 13190.31 | 01-FEB-20:10 | 9632.53 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 13190.31 | 01-MAR-20:10 | 9632.53 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 13190.31 | 03-APR-19:10 | 9632.53 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 13190.31 | 01-MAY-19:10 | 9632.53 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 13190.31 | 01-JUN-19:10 | 9632.53 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 13190.31 | 03-JUL-19:10 | 9632.53 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 13190.31 | 01-AUG-19:10 | 9632.53 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 13190.31 | 01-SEP-19:10 | 9632.53 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 01-OCT-23:10 | 13190.31 | 02-OCT-19:10 | 9632.53 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 13190.31 | 01-NOV-19:10 | 9632.53 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 13190.31 | 01-DEC-20:10 | 9632.53 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 11501.89 | 13190.31 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 13190.31 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 597.59 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 197.69 | 05-JAN-19:00 |
February | 1169.53 | 01-FEB-00:10 | 597.59 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 206.43 | 12-FEB-07:00 |
March | 1169.53 | 01-MAR-00:10 | 597.59 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 180.28 | 19-MAR-07:00 |
April | 1169.53 | 01-APR-00:10 | 597.59 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 140.14 | 17-APR-03:00 |
May | 1169.53 | 01-MAY-00:10 | 597.59 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.27 | 17-MAY-13:00 | 103.10 | 03-MAY-02:00 |
June | 1169.53 | 01-JUN-00:10 | 597.59 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 63.59 | 26-JUN-15:00 | 70.73 | 09-JUN-04:10 |
July | 1169.53 | 01-JUL-00:10 | 597.59 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.35 | 16-JUL-13:00 | 59.65 | 02-JUL-05:00 |
August | 1169.53 | 01-AUG-00:10 | 597.59 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.05 | 16-AUG-16:00 | 54.40 | 12-AUG-23:00 |
September | 1169.53 | 01-SEP-00:10 | 597.59 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.74 | 09-SEP-13:00 | 107.43 | 22-SEP-05:05 |
October | 1169.53 | 01-OCT-23:10 | 597.59 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.77 | 11-OCT-14:00 | 150.39 | 30-OCT-06:40 |
November | 1169.53 | 01-NOV-00:10 | 597.59 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 176.47 | 29-NOV-21:00 |
December | 1169.53 | 01-DEC-00:10 | 597.59 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 223.32 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1169.53 | 597.59 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.40 | |||||
Maximum of Months | 1169.53 | 597.59 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 63.59 | 223.32 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 692.02 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 77.48 | 05-JAN-19:00 |
February | 1354.32 | 01-FEB-00:10 | 692.02 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 81.89 | 12-FEB-05:00 |
March | 1354.32 | 01-MAR-00:10 | 692.02 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.74 | 14-MAR-13:00 | 71.34 | 19-MAR-07:00 |
April | 1354.32 | 01-APR-00:10 | 692.02 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 56.05 | 17-APR-06:00 |
May | 1354.32 | 01-MAY-00:10 | 692.02 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.09 | 17-MAY-13:00 | 43.50 | 03-MAY-02:00 |
June | 1354.32 | 01-JUN-00:10 | 692.02 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.54 | 26-JUN-15:00 | 30.85 | 09-JUN-04:07 |
July | 1354.32 | 01-JUL-00:10 | 692.02 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.09 | 16-JUL-13:00 | 26.30 | 02-JUL-05:00 |
August | 1354.32 | 01-AUG-00:10 | 692.02 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.86 | 16-AUG-16:00 | 22.76 | 12-AUG-24:00 |
September | 1354.32 | 01-SEP-00:10 | 692.02 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.21 | 10-SEP-13:00 | 45.67 | 22-SEP-06:00 |
October | 1354.32 | 01-OCT-23:10 | 692.02 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.31 | 11-OCT-14:00 | 60.36 | 30-OCT-06:00 |
November | 1354.32 | 01-NOV-00:10 | 692.02 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 71.20 | 29-NOV-21:00 |
December | 1354.32 | 01-DEC-00:10 | 692.02 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 86.35 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1354.32 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.76 | |||||
Maximum of Months | 1354.32 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 24.54 | 86.35 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 286.42 | 02-JAN-00:10 | 684.18 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 180.33 | 05-JAN-19:00 |
February | 286.42 | 01-FEB-00:10 | 684.18 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 188.31 | 12-FEB-07:00 |
March | 286.42 | 01-MAR-00:10 | 684.18 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.75 | 14-MAR-13:00 | 164.86 | 19-MAR-07:00 |
April | 286.42 | 01-APR-00:10 | 684.18 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 127.83 | 17-APR-03:00 |
May | 286.42 | 01-MAY-00:10 | 684.18 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.93 | 17-MAY-13:00 | 97.95 | 03-MAY-02:00 |
June | 286.42 | 01-JUN-00:10 | 684.18 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.01 | 26-JUN-15:00 | 72.02 | 09-JUN-04:40 |
July | 286.42 | 01-JUL-00:10 | 684.18 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.58 | 16-JUL-13:00 | 62.00 | 02-JUL-05:00 |
August | 286.42 | 01-AUG-00:10 | 684.18 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.31 | 16-AUG-16:00 | 53.79 | 12-AUG-24:00 |
September | 286.42 | 01-SEP-00:10 | 684.18 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.92 | 09-SEP-13:00 | 105.90 | 22-SEP-05:50 |
October | 286.42 | 01-OCT-23:10 | 684.18 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.86 | 11-OCT-14:00 | 138.03 | 30-OCT-06:40 |
November | 286.42 | 01-NOV-00:10 | 684.18 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 161.80 | 29-NOV-21:00 |
December | 286.42 | 01-DEC-00:10 | 684.18 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.53 | 01-DEC-14:00 | 203.75 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 286.42 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.79 | |||||
Maximum of Months | 286.42 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 58.01 | 203.75 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 220.32 | 02-JAN-00:10 | 251.84 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 104.04 | 05-JAN-19:00 |
February | 220.32 | 01-FEB-00:10 | 251.84 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 108.64 | 12-FEB-05:00 |
March | 220.32 | 01-MAR-00:10 | 251.84 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.01 | 14-MAR-13:00 | 94.88 | 19-MAR-07:00 |
April | 220.32 | 01-APR-00:10 | 251.84 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.11 | 19-APR-13:00 | 73.75 | 17-APR-03:00 |
May | 220.32 | 01-MAY-00:10 | 251.84 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.84 | 17-MAY-13:00 | 55.44 | 03-MAY-02:00 |
June | 220.32 | 01-JUN-00:10 | 251.84 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.47 | 26-JUN-15:00 | 40.75 | 09-JUN-05:00 |
July | 220.32 | 01-JUL-00:10 | 251.84 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.61 | 16-JUL-13:00 | 35.09 | 02-JUL-05:00 |
August | 220.32 | 01-AUG-00:10 | 251.84 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.45 | 16-AUG-14:00 | 30.41 | 12-AUG-23:00 |
September | 220.32 | 01-SEP-00:10 | 251.84 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.60 | 09-SEP-13:00 | 59.62 | 22-SEP-05:30 |
October | 220.32 | 01-OCT-23:10 | 251.84 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 11-OCT-14:00 | 79.14 | 30-OCT-08:00 |
November | 220.32 | 01-NOV-00:10 | 251.84 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 92.88 | 29-NOV-21:00 |
December | 220.32 | 01-DEC-00:10 | 251.84 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.40 | 01-DEC-14:00 | 117.55 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 220.32 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.41 | |||||
Maximum of Months | 220.32 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 33.47 | 117.55 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 325.08 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 264.69 | 05-JAN-19:00 |
February | 907.20 | 01-FEB-00:10 | 325.08 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 275.88 | 12-FEB-07:00 |
March | 907.20 | 01-MAR-00:10 | 325.08 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 5.57 | 14-MAR-13:00 | 242.93 | 19-MAR-07:00 |
April | 907.20 | 01-APR-00:10 | 325.08 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 192.57 | 17-APR-06:00 |
May | 907.20 | 01-MAY-00:10 | 325.08 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 26.58 | 17-MAY-13:00 | 138.64 | 02-MAY-24:00 |
June | 907.20 | 01-JUN-00:10 | 325.08 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 80.10 | 26-JUN-15:20 | 96.35 | 09-JUN-05:00 |
July | 907.20 | 01-JUL-00:10 | 325.08 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 70.75 | 16-JUL-13:00 | 83.72 | 02-JUL-05:00 |
August | 907.20 | 01-AUG-00:10 | 325.08 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 70.28 | 16-AUG-16:00 | 73.45 | 12-AUG-24:00 |
September | 907.20 | 01-SEP-00:10 | 325.08 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 49.59 | 10-SEP-13:00 | 151.45 | 22-SEP-06:00 |
October | 907.20 | 01-OCT-23:10 | 325.08 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 21.64 | 11-OCT-14:00 | 205.43 | 30-OCT-07:20 |
November | 907.20 | 01-NOV-00:10 | 325.08 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 238.12 | 29-NOV-21:00 |
December | 907.20 | 01-DEC-00:10 | 325.08 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 290.05 | 23-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 907.20 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 73.45 | ||||||
Maximum of Months | 907.20 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 80.10 | 290.05 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 1701.53 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 437.01 | 05-JAN-19:00 |
February | 15368.40 | 01-FEB-00:10 | 1701.53 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 458.36 | 12-FEB-07:00 |
March | 15368.40 | 01-MAR-00:10 | 1701.53 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 398.52 | 19-MAR-07:00 |
April | 15368.40 | 01-APR-00:10 | 1701.53 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 320.82 | 17-APR-03:00 |
May | 15368.40 | 01-MAY-00:10 | 1701.53 | 01-MAY-19:10 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.03 | 17-MAY-13:00 | 250.97 | 03-MAY-02:00 |
June | 15368.40 | 01-JUN-00:10 | 1701.53 | 01-JUN-19:19 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 140.57 | 26-JUN-15:00 | 176.66 | 09-JUN-04:07 |
July | 15368.40 | 01-JUL-00:10 | 1701.53 | 03-JUL-19:19 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 120.15 | 16-JUL-13:00 | 147.50 | 02-JUL-05:00 |
August | 15368.40 | 01-AUG-00:10 | 1701.53 | 01-AUG-19:10 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 119.50 | 16-AUG-16:00 | 130.30 | 12-AUG-24:00 |
September | 15368.40 | 01-SEP-00:10 | 1701.53 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.24 | 10-SEP-13:00 | 260.78 | 22-SEP-05:00 |
October | 15368.40 | 01-OCT-23:10 | 1701.53 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.25 | 11-OCT-14:00 | 343.97 | 30-OCT-05:00 |
November | 15368.40 | 01-NOV-00:10 | 1701.53 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 396.98 | 29-NOV-21:10 |
December | 15368.40 | 01-DEC-00:10 | 1701.53 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 493.74 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 15368.40 | 1701.53 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.30 | |||||
Maximum of Months | 15368.40 | 1701.53 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 140.57 | 493.74 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 9504.80 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1282.14 | 05-JAN-19:10 |
February | 45622.98 | 01-FEB-00:10 | 9504.80 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1358.37 | 12-FEB-07:00 |
March | 45622.98 | 01-MAR-00:10 | 9504.80 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1188.09 | 19-MAR-07:00 |
April | 45622.98 | 01-APR-00:10 | 9504.80 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 946.93 | 17-APR-05:00 |
May | 45622.98 | 01-MAY-00:10 | 9504.80 | 01-MAY-19:10 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 146.57 | 17-MAY-13:00 | 735.31 | 03-MAY-02:00 |
June | 45622.98 | 01-JUN-00:10 | 9504.80 | 01-JUN-19:19 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 401.62 | 26-JUN-15:00 | 504.81 | 09-JUN-04:07 |
July | 45622.98 | 01-JUL-00:10 | 9504.80 | 03-JUL-19:19 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 347.67 | 16-JUL-13:00 | 430.31 | 02-JUL-05:00 |
August | 45622.98 | 01-AUG-00:10 | 9504.80 | 01-AUG-19:10 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 341.40 | 16-AUG-16:00 | 372.37 | 12-AUG-24:00 |
September | 45622.98 | 01-SEP-00:10 | 9504.80 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 232.11 | 10-SEP-13:00 | 768.05 | 22-SEP-05:00 |
October | 45622.98 | 01-OCT-23:10 | 9504.80 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.70 | 11-OCT-14:00 | 1016.49 | 30-OCT-05:00 |
November | 45622.98 | 01-NOV-00:10 | 9504.80 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 1180.52 | 29-NOV-21:00 |
December | 45622.98 | 01-DEC-00:10 | 9504.80 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1446.90 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 45622.98 | 9504.80 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 372.37 | |||||
Maximum of Months | 45622.98 | 9504.80 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 401.62 | 1446.90 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.88 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 114.09 | 05-JAN-19:10 |
February | 180.00 | 01-FEB-00:10 | 177.88 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 120.26 | 12-FEB-05:00 |
March | 180.00 | 01-MAR-00:10 | 177.88 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.20 | 14-MAR-15:10 | 105.06 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 177.88 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 81.76 | 17-APR-03:00 |
May | 180.00 | 01-MAY-00:10 | 177.88 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.05 | 31-MAY-16:00 | 60.26 | 03-MAY-02:00 |
June | 180.00 | 01-JUN-00:10 | 177.88 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.82 | 26-JUN-15:10 | 38.80 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 177.88 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.53 | 16-JUL-15:10 | 32.05 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 177.88 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.88 | 16-AUG-14:00 | 26.73 | 12-AUG-24:00 |
September | 180.00 | 01-SEP-00:10 | 177.88 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.49 | 06-SEP-15:10 | 62.77 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 177.88 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.61 | 10-OCT-16:30 | 87.71 | 30-OCT-06:10 |
November | 180.00 | 01-NOV-00:10 | 177.88 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 102.86 | 29-NOV-21:00 |
December | 180.00 | 01-DEC-00:10 | 177.88 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 130.09 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.73 | |||||
Maximum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 39.82 | 130.09 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.86 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 114.09 | 05-JAN-19:10 |
February | 180.00 | 01-FEB-00:10 | 177.86 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 120.25 | 12-FEB-05:00 |
March | 180.00 | 01-MAR-00:10 | 177.86 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.65 | 13-MAR-15:10 | 105.05 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 177.86 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 81.75 | 17-APR-03:00 |
May | 180.00 | 01-MAY-00:10 | 177.86 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.96 | 31-MAY-16:00 | 60.25 | 03-MAY-02:00 |
June | 180.00 | 01-JUN-00:10 | 177.86 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.85 | 26-JUN-15:10 | 38.80 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 177.86 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.41 | 16-JUL-15:10 | 32.04 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 177.86 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.20 | 16-AUG-16:00 | 29.32 | 12-AUG-20:00 |
September | 180.00 | 01-SEP-00:10 | 177.86 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.97 | 06-SEP-15:10 | 62.77 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 177.86 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 11-OCT-15:10 | 87.70 | 30-OCT-06:10 |
November | 180.00 | 01-NOV-00:10 | 177.86 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 102.85 | 29-NOV-21:00 |
December | 180.00 | 01-DEC-00:10 | 177.86 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 130.08 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.32 | |||||
Maximum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 39.85 | 130.08 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 111.79 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 33.53 | 05-JAN-19:00 |
February | 0.00 | 01-FEB-00:10 | 111.79 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 34.98 | 12-FEB-05:00 |
March | 0.00 | 01-MAR-00:10 | 111.79 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 30.07 | 19-MAR-07:00 |
April | 0.00 | 01-APR-00:10 | 111.79 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 23.42 | 17-APR-06:00 |
May | 0.00 | 01-MAY-00:10 | 111.79 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.58 | 17-MAY-13:00 | 19.60 | 03-MAY-02:00 |
June | 0.00 | 01-JUN-00:10 | 111.79 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.49 | 26-JUN-15:00 | 14.89 | 09-JUN-04:20 |
July | 0.00 | 01-JUL-00:10 | 111.79 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.97 | 16-JUL-13:00 | 13.03 | 02-JUL-05:00 |
August | 0.00 | 01-AUG-00:10 | 111.79 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.93 | 16-AUG-14:00 | 11.54 | 12-AUG-24:00 |
September | 0.00 | 01-SEP-00:10 | 111.79 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.10 | 10-SEP-13:00 | 21.01 | 22-SEP-06:00 |
October | 0.00 | 01-OCT-00:10 | 111.79 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.20 | 11-OCT-14:00 | 26.42 | 30-OCT-07:00 |
November | 0.00 | 01-NOV-00:10 | 111.79 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 30.64 | 29-NOV-21:00 |
December | 0.00 | 01-DEC-00:10 | 111.79 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 34.33 | 21-DEC-17:20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 0.00 | 111.79 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.54 | |||||
Maximum of Months | 0.00 | 111.79 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 8.49 | 34.98 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 111.82 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 31.84 | 05-JAN-19:10 |
February | 180.00 | 01-FEB-00:10 | 111.82 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 33.56 | 12-FEB-05:00 |
March | 180.00 | 01-MAR-00:10 | 111.82 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.41 | 14-MAR-13:00 | 29.32 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 111.82 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 22.82 | 17-APR-03:00 |
May | 180.00 | 01-MAY-00:10 | 111.82 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.77 | 31-MAY-15:10 | 16.82 | 03-MAY-02:00 |
June | 180.00 | 01-JUN-00:10 | 111.82 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.60 | 26-JUN-15:30 | 10.83 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 111.82 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.35 | 16-JUL-15:10 | 8.94 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 111.82 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.40 | 16-AUG-16:00 | 7.46 | 12-AUG-24:00 |
September | 180.00 | 01-SEP-00:10 | 111.82 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.41 | 10-SEP-16:00 | 17.52 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 111.82 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.13 | 11-OCT-15:10 | 24.48 | 30-OCT-06:10 |
November | 180.00 | 01-NOV-00:10 | 111.82 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 | 07-NOV-14:00 | 28.71 | 29-NOV-21:00 |
December | 180.00 | 01-DEC-00:10 | 111.82 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.97 | 01-DEC-14:00 | 36.31 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.46 | |||||
Maximum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 11.60 | 36.31 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.88 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 114.09 | 05-JAN-19:10 |
February | 180.00 | 01-FEB-00:10 | 177.88 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 120.26 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 177.88 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.65 | 13-MAR-16:00 | 105.06 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 177.88 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 81.76 | 17-APR-03:00 |
May | 180.00 | 01-MAY-00:10 | 177.88 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.08 | 31-MAY-15:10 | 60.25 | 03-MAY-02:00 |
June | 180.00 | 01-JUN-00:10 | 177.88 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.93 | 26-JUN-15:30 | 38.80 | 09-JUN-04:50 |
July | 180.00 | 01-JUL-00:10 | 177.88 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.87 | 16-JUL-15:10 | 32.05 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 177.88 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.33 | 16-AUG-16:00 | 28.49 | 13-AUG-07:09 |
September | 180.00 | 01-SEP-00:10 | 177.88 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.02 | 10-SEP-16:00 | 62.77 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 177.88 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.21 | 11-OCT-15:10 | 87.71 | 30-OCT-06:10 |
November | 180.00 | 01-NOV-00:10 | 177.88 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 102.86 | 29-NOV-21:00 |
December | 180.00 | 01-DEC-00:10 | 177.88 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 130.09 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.49 | |||||
Maximum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 41.93 | 130.09 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.86 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 114.08 | 05-JAN-19:10 |
February | 180.00 | 01-FEB-00:10 | 177.86 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 120.25 | 12-FEB-05:00 |
March | 180.00 | 01-MAR-00:10 | 177.86 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.65 | 13-MAR-15:10 | 105.05 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 177.86 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 81.75 | 17-APR-03:00 |
May | 180.00 | 01-MAY-00:10 | 177.86 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.07 | 31-MAY-15:10 | 60.25 | 03-MAY-02:00 |
June | 180.00 | 01-JUN-00:10 | 177.86 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.64 | 26-JUN-15:30 | 38.80 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 177.86 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.66 | 16-JUL-15:10 | 32.04 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 177.86 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.89 | 16-AUG-16:00 | 28.76 | 12-AUG-08:00 |
September | 180.00 | 01-SEP-00:10 | 177.86 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.06 | 10-SEP-16:00 | 62.77 | 22-SEP-05:50 |
October | 180.00 | 01-OCT-00:10 | 177.86 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.21 | 11-OCT-15:10 | 87.70 | 30-OCT-06:10 |
November | 180.00 | 01-NOV-00:10 | 177.86 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 102.85 | 29-NOV-21:00 |
December | 180.00 | 01-DEC-00:10 | 177.86 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.32 | 01-DEC-14:00 | 130.08 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.76 | |||||
Maximum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 41.64 | 130.08 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2263.36 | 02-JAN-00:10 | 1867.32 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 138.89 | 05-JAN-19:00 |
February | 2263.36 | 01-FEB-00:10 | 1867.32 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 145.03 | 12-FEB-05:00 |
March | 2263.36 | 01-MAR-00:10 | 1867.32 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 14-MAR-13:00 | 126.66 | 19-MAR-07:00 |
April | 2263.36 | 01-APR-00:10 | 1867.32 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 98.49 | 17-APR-03:00 |
May | 2263.36 | 01-MAY-00:10 | 1867.32 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.15 | 17-MAY-13:00 | 74.04 | 03-MAY-02:00 |
June | 2263.36 | 01-JUN-00:10 | 1867.32 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.50 | 26-JUN-15:00 | 55.03 | 09-JUN-04:10 |
July | 2263.36 | 01-JUL-00:10 | 1867.32 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.02 | 16-JUL-13:00 | 47.04 | 02-JUL-05:00 |
August | 2263.36 | 01-AUG-00:10 | 1867.32 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.81 | 16-AUG-16:00 | 41.18 | 12-AUG-23:00 |
September | 2263.36 | 01-SEP-00:10 | 1867.32 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.66 | 10-SEP-13:00 | 81.18 | 22-SEP-05:00 |
October | 2263.36 | 01-OCT-23:10 | 1867.32 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.01 | 11-OCT-14:00 | 105.69 | 30-OCT-06:30 |
November | 2263.36 | 01-NOV-00:10 | 1867.32 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 124.00 | 29-NOV-21:00 |
December | 2263.36 | 01-DEC-00:10 | 1867.32 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.11 | 01-DEC-14:00 | 156.91 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.18 | ||||
Maximum of Months | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.50 | 156.91 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.88 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 114.29 | 05-JAN-19:10 |
February | 180.00 | 01-FEB-00:10 | 177.88 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 120.46 | 12-FEB-05:00 |
March | 180.00 | 01-MAR-00:10 | 177.88 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.05 | 14-MAR-15:10 | 105.26 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 177.88 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 81.94 | 17-APR-03:00 |
May | 180.00 | 01-MAY-00:10 | 177.88 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.32 | 31-MAY-16:00 | 60.43 | 03-MAY-02:00 |
June | 180.00 | 01-JUN-00:10 | 177.88 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.05 | 26-JUN-15:10 | 38.97 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 177.88 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.09 | 16-JUL-15:10 | 32.21 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 177.88 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.74 | 16-AUG-14:00 | 26.89 | 12-AUG-24:00 |
September | 180.00 | 01-SEP-00:10 | 177.88 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.22 | 06-SEP-15:10 | 62.95 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 177.88 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.46 | 10-OCT-16:30 | 87.90 | 30-OCT-06:10 |
November | 180.00 | 01-NOV-00:10 | 177.88 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 103.05 | 29-NOV-21:00 |
December | 180.00 | 01-DEC-00:10 | 177.88 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 130.29 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.89 | |||||
Maximum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 39.05 | 130.29 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.86 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 114.28 | 05-JAN-19:10 |
February | 180.00 | 01-FEB-00:10 | 177.86 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 120.45 | 12-FEB-05:00 |
March | 180.00 | 01-MAR-00:10 | 177.86 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 13-MAR-15:10 | 105.25 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 177.86 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 81.94 | 17-APR-03:00 |
May | 180.00 | 01-MAY-00:10 | 177.86 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.18 | 31-MAY-16:00 | 60.43 | 03-MAY-02:00 |
June | 180.00 | 01-JUN-00:10 | 177.86 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.09 | 26-JUN-15:10 | 38.97 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 177.86 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.93 | 16-JUL-15:10 | 32.21 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 177.86 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.74 | 16-AUG-14:00 | 30.43 | 12-AUG-20:00 |
September | 180.00 | 01-SEP-00:10 | 177.86 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.69 | 06-SEP-15:10 | 62.94 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 177.86 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.04 | 11-OCT-15:10 | 87.89 | 30-OCT-06:10 |
November | 180.00 | 01-NOV-00:10 | 177.86 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 103.04 | 29-NOV-21:00 |
December | 180.00 | 01-DEC-00:10 | 177.86 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 130.28 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.43 | |||||
Maximum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 39.09 | 130.28 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 111.82 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 58.48 | 05-JAN-19:10 |
February | 180.00 | 01-FEB-00:10 | 111.82 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 61.63 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 111.82 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.71 | 14-MAR-15:10 | 53.85 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 111.82 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 41.92 | 17-APR-03:00 |
May | 180.00 | 01-MAY-00:10 | 111.82 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.66 | 31-MAY-15:10 | 30.92 | 03-MAY-02:00 |
June | 180.00 | 01-JUN-00:10 | 111.82 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.19 | 26-JUN-16:00 | 19.94 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 111.82 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.45 | 16-JUL-15:10 | 16.48 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 111.82 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.21 | 16-AUG-16:00 | 13.76 | 12-AUG-24:00 |
September | 180.00 | 01-SEP-00:10 | 111.82 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.38 | 10-SEP-16:00 | 32.21 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 111.82 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.60 | 10-OCT-17:00 | 44.97 | 30-OCT-06:10 |
November | 180.00 | 01-NOV-00:10 | 111.82 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 52.72 | 29-NOV-21:00 |
December | 180.00 | 01-DEC-00:10 | 111.82 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 66.66 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.76 | |||||
Maximum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 21.19 | 66.66 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2988.03 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 299.28 | 05-JAN-19:10 |
February | 26988.77 | 01-FEB-00:10 | 2988.03 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 313.94 | 12-FEB-07:00 |
March | 26988.77 | 01-MAR-00:10 | 2988.03 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 277.14 | 19-MAR-07:00 |
April | 26988.77 | 01-APR-00:10 | 2988.03 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 219.82 | 17-APR-03:00 |
May | 26988.77 | 01-MAY-00:10 | 2988.03 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.54 | 17-MAY-13:00 | 166.70 | 03-MAY-02:00 |
June | 26988.77 | 01-JUN-00:10 | 2988.03 | 01-JUN-19:19 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.55 | 26-JUN-15:00 | 113.95 | 09-JUN-04:07 |
July | 26988.77 | 01-JUL-00:10 | 2988.03 | 03-JUL-19:30 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.44 | 16-JUL-13:00 | 97.22 | 02-JUL-05:00 |
August | 26988.77 | 01-AUG-00:10 | 2988.03 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.03 | 16-AUG-16:00 | 84.21 | 12-AUG-24:00 |
September | 26988.77 | 01-SEP-00:10 | 2988.03 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.49 | 10-SEP-13:00 | 173.06 | 22-SEP-05:10 |
October | 26988.77 | 01-OCT-23:10 | 2988.03 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.11 | 11-OCT-14:00 | 234.44 | 30-OCT-06:00 |
November | 26988.77 | 01-NOV-00:10 | 2988.03 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 271.66 | 29-NOV-21:00 |
December | 26988.77 | 01-DEC-00:10 | 2988.03 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 336.92 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.21 | |||||
Maximum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 89.55 | 336.92 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2988.03 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 300.16 | 05-JAN-19:00 |
February | 26988.77 | 01-FEB-00:10 | 2988.03 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 314.71 | 12-FEB-07:00 |
March | 26988.77 | 01-MAR-00:10 | 2988.03 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 277.14 | 19-MAR-07:00 |
April | 26988.77 | 01-APR-00:10 | 2988.03 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 219.83 | 17-APR-03:00 |
May | 26988.77 | 01-MAY-00:10 | 2988.03 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.54 | 17-MAY-13:00 | 166.70 | 03-MAY-02:00 |
June | 26988.77 | 01-JUN-00:10 | 2988.03 | 01-JUN-19:19 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.55 | 26-JUN-15:00 | 113.95 | 09-JUN-04:07 |
July | 26988.77 | 01-JUL-00:10 | 2988.03 | 03-JUL-19:30 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.44 | 16-JUL-13:00 | 97.22 | 02-JUL-05:00 |
August | 26988.77 | 01-AUG-00:10 | 2988.03 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.03 | 16-AUG-16:00 | 84.21 | 12-AUG-24:00 |
September | 26988.77 | 01-SEP-00:10 | 2988.03 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.49 | 10-SEP-13:00 | 173.06 | 22-SEP-05:10 |
October | 26988.77 | 01-OCT-23:10 | 2988.03 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.51 | 11-OCT-14:00 | 234.44 | 30-OCT-06:00 |
November | 26988.77 | 01-NOV-00:10 | 2988.03 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 271.66 | 29-NOV-21:00 |
December | 26988.77 | 01-DEC-00:10 | 2988.03 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 338.71 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.21 | |||||
Maximum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 89.55 | 338.71 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 1060.81 | 02-JAN-20:10 | 14912.86 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 270.22 | 05-JAN-19:00 |
February | 2401.70 | 01-FEB-00:10 | 1060.81 | 01-FEB-20:10 | 14912.86 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 281.70 | 12-FEB-07:00 |
March | 2401.70 | 01-MAR-00:10 | 1060.81 | 01-MAR-20:10 | 14912.86 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 248.06 | 19-MAR-07:00 |
April | 2401.70 | 01-APR-00:10 | 1060.81 | 03-APR-19:10 | 14912.86 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 196.76 | 17-APR-06:00 |
May | 2401.70 | 01-MAY-00:10 | 1060.81 | 01-MAY-19:10 | 14912.86 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 26.51 | 17-MAY-13:00 | 146.32 | 03-MAY-02:00 |
June | 2401.70 | 01-JUN-00:10 | 1060.81 | 01-JUN-19:10 | 14912.86 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 80.22 | 26-JUN-15:00 | 102.01 | 09-JUN-04:03 |
July | 2401.70 | 01-JUL-00:10 | 1060.81 | 03-JUL-19:10 | 14912.86 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 68.49 | 16-JUL-13:00 | 87.03 | 02-JUL-05:00 |
August | 2401.70 | 01-AUG-00:10 | 1060.81 | 01-AUG-19:10 | 14912.86 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 68.14 | 16-AUG-16:00 | 75.39 | 12-AUG-24:00 |
September | 2401.70 | 01-SEP-00:10 | 1060.81 | 01-SEP-19:10 | 14912.86 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 46.16 | 10-SEP-13:00 | 154.91 | 22-SEP-05:05 |
October | 2401.70 | 01-OCT-23:10 | 1060.81 | 02-OCT-19:10 | 14912.86 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 15.73 | 11-OCT-14:00 | 209.89 | 30-OCT-07:07 |
November | 2401.70 | 01-NOV-00:10 | 1060.81 | 01-NOV-19:10 | 14912.86 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 243.15 | 29-NOV-21:00 |
December | 2401.70 | 01-DEC-00:10 | 1060.81 | 01-DEC-20:10 | 14912.86 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 297.28 | 23-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2401.70 | 1060.81 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 0.00 | 75.39 | ||||||
Maximum of Months | 2401.70 | 1060.81 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 80.22 | 297.28 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2395.44 | 02-JAN-00:10 | 1976.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 246.17 | 05-JAN-19:00 |
February | 2395.44 | 01-FEB-00:10 | 1976.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 257.04 | 12-FEB-07:00 |
March | 2395.44 | 01-MAR-00:10 | 1976.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 224.53 | 19-MAR-07:00 |
April | 2395.44 | 01-APR-00:10 | 1976.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 174.66 | 17-APR-03:00 |
May | 2395.44 | 01-MAY-00:10 | 1976.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.94 | 17-MAY-13:00 | 128.65 | 03-MAY-02:00 |
June | 2395.44 | 01-JUN-00:10 | 1976.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.45 | 26-JUN-15:00 | 94.58 | 09-JUN-04:00 |
July | 2395.44 | 01-JUL-00:10 | 1976.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.97 | 16-JUL-13:00 | 80.28 | 02-JUL-05:00 |
August | 2395.44 | 01-AUG-00:10 | 1976.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.60 | 16-AUG-16:00 | 71.50 | 12-AUG-23:00 |
September | 2395.44 | 01-SEP-00:10 | 1976.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.11 | 10-SEP-13:00 | 136.88 | 22-SEP-05:00 |
October | 2395.44 | 01-OCT-23:10 | 1976.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.33 | 11-OCT-14:00 | 187.40 | 30-OCT-06:40 |
November | 2395.44 | 01-NOV-00:10 | 1976.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 219.81 | 29-NOV-21:00 |
December | 2395.44 | 01-DEC-00:10 | 1976.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 278.08 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.50 | ||||
Maximum of Months | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.45 | 278.08 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17984.69 | 26-JAN-22:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16525.81 | 01-FEB-22:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 15086.89 | 01-MAR-22:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 14111.67 | 14-APR-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 13526.39 | 19-MAY-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16458.28 | 16-JUN-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17198.72 | 28-JUL-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 19909.34 | 18-AUG-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 22598.79 | 15-SEP-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 22662.71 | 20-OCT-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 22342.52 | 09-NOV-22:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 21442.92 | 05-DEC-22:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 13526.39 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22662.71 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4982.72 | 20-JAN-13:10 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.79 |
February | 4964.26 | 18-FEB-13:20 | 389.84 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.94 |
March | 4646.75 | 14-MAR-12:40 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.89 |
April | 3310.75 | 07-APR-12:30 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.29 |
May | 2422.70 | 05-MAY-13:00 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.79 |
June | 3000.77 | 26-JUN-12:40 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 51.84 | 0.00 |
July | 3267.25 | 23-JUL-12:00 | 389.84 | 199.20 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 33.94 | 0.00 |
August | 3998.05 | 31-AUG-12:40 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 25.67 | 0.00 |
September | 4883.46 | 28-SEP-12:50 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 27.33 | 0.00 |
October | 4932.14 | 10-OCT-12:40 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.64 |
November | 5013.20 | 07-NOV-12:40 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.56 |
December | 4711.96 | 17-DEC-13:00 | 389.84 | 199.20 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.44 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2422.70 | 259.90 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5013.20 | 389.84 | 199.20 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 51.84 | 26.44 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1579.27 | 20-JAN-22:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.91 |
February | 1482.77 | 27-FEB-21:10 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.88 |
March | 1841.18 | 15-MAR-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.78 |
April | 1638.06 | 07-APR-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.50 |
May | 1806.19 | 31-MAY-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.22 |
June | 2214.96 | 26-JUN-20:10 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 13.09 | 0.00 |
July | 2125.14 | 17-JUL-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 8.23 | 0.00 |
August | 2211.07 | 16-AUG-20:10 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 7.39 | 0.00 |
September | 2087.29 | 12-SEP-20:04 | 6019.20 | 3075.62 | 3760.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.48 |
October | 1902.87 | 11-OCT-20:10 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.91 |
November | 1679.02 | 07-NOV-21:10 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.98 |
December | 1428.04 | 04-DEC-22:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.58 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1428.04 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2214.96 | 6019.20 | 3075.62 | 3760.73 | 0.00 | 0.00 | 0.00 | 0.00 | 13.09 | 35.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 868.78 | 20-JAN-13:50 | 63.65 | 190.05 | 309.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.16 |
February | 863.18 | 18-FEB-13:45 | 190.94 | 380.10 | 618.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.88 |
March | 936.25 | 15-MAR-10:33 | 190.94 | 570.15 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.33 |
April | 892.99 | 21-APR-10:33 | 190.94 | 570.15 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.36 |
May | 1136.41 | 17-MAY-21:00 | 254.59 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.05 |
June | 1862.96 | 27-JUN-20:25 | 509.18 | 1216.31 | 1590.53 | 0.00 | 0.00 | 0.00 | 0.00 | 3.74 | 0.00 |
July | 1862.70 | 17-JUL-19:50 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 23.90 | 0.00 |
August | 1715.91 | 16-AUG-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 19.38 | 0.00 |
September | 1577.40 | 11-SEP-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.45 |
October | 966.40 | 01-OCT-10:35 | 190.94 | 456.12 | 706.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.48 |
November | 906.22 | 07-NOV-13:50 | 63.65 | 190.05 | 309.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.10 |
December | 818.27 | 03-DEC-13:00 | 95.47 | 228.06 | 353.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 818.27 | 63.65 | 190.05 | 309.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1862.96 | 509.18 | 1216.31 | 1590.53 | 0.00 | 0.00 | 0.00 | 0.00 | 23.90 | 37.36 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 518.71 | 20-JAN-13:50 | 48.96 | 69.95 | 89.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.16 |
February | 516.84 | 18-FEB-13:45 | 146.88 | 139.91 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.37 |
March | 550.02 | 15-MAR-10:33 | 146.88 | 209.86 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.29 |
April | 524.34 | 21-APR-10:33 | 146.88 | 209.86 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.95 |
May | 578.52 | 18-MAY-10:33 | 146.88 | 209.86 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.90 |
June | 913.71 | 26-JUN-19:10 | 171.36 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 24.25 | 0.00 |
July | 880.22 | 17-JUL-19:10 | 171.36 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 15.25 | 0.00 |
August | 797.05 | 16-AUG-20:00 | 171.36 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 11.18 | 0.00 |
September | 676.91 | 12-SEP-21:00 | 195.84 | 223.85 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.60 |
October | 574.03 | 11-OCT-12:50 | 48.96 | 69.95 | 89.22 | 0.00 | 0.00 | 0.00 | 0.00 | 6.40 | 0.00 |
November | 539.86 | 07-NOV-13:50 | 48.96 | 69.95 | 89.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.49 |
December | 484.39 | 03-DEC-13:00 | 73.44 | 83.94 | 101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.16 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 484.39 | 48.96 | 69.95 | 89.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 913.71 | 195.84 | 251.84 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 24.25 | 20.95 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 37770.69 | 20-JAN-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 96.16 |
February | 37778.38 | 27-FEB-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 113.82 |
March | 38341.82 | 14-MAR-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 43.79 |
April | 38370.50 | 20-APR-19:55 | 1411.20 | 650.17 | 9145.60 | 79453.15 | 0.00 | 0.00 | 0.00 | 0.00 | 49.42 |
May | 38668.04 | 16-MAY-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 27.45 |
June | 39234.98 | 26-JUN-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 45.56 | 0.00 |
July | 39242.77 | 07-JUL-19:30 | 1411.20 | 650.17 | 9145.60 | 79453.15 | 0.00 | 0.00 | 0.00 | 0.00 | 1.37 |
August | 39161.31 | 16-AUG-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 26.47 | 0.00 |
September | 38879.95 | 12-SEP-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 1.16 |
October | 38277.07 | 11-OCT-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 72.97 |
November | 37955.15 | 09-NOV-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 83.74 |
December | 37590.95 | 04-DEC-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 95.34 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 37590.95 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 39242.77 | 1411.20 | 650.17 | 9145.60 | 79453.15 | 0.00 | 0.00 | 0.00 | 45.56 | 113.82 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 17469.88 | 20-JAN-13:00 | 3415.20 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.99 |
February | 17898.41 | 18-FEB-13:10 | 5122.80 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.78 |
March | 16468.65 | 11-MAR-13:00 | 5122.80 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.91 |
April | 12258.25 | 07-APR-12:30 | 3415.20 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.80 |
May | 10085.81 | 10-MAY-21:10 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.51 |
June | 11718.45 | 26-JUN-21:10 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 39.22 | 0.00 |
July | 11796.49 | 17-JUL-21:10 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 42.53 | 0.00 |
August | 13720.55 | 26-AUG-12:40 | 5122.80 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 71.85 | 0.00 |
September | 16069.13 | 28-SEP-12:50 | 3415.20 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 60.43 | 0.00 |
October | 16511.83 | 08-OCT-12:00 | 5122.80 | 124.78 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.04 |
November | 17885.37 | 05-NOV-12:00 | 5122.80 | 124.78 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.87 |
December | 17225.74 | 17-DEC-12:50 | 5122.80 | 124.78 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.76 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10085.81 | 3415.20 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17898.41 | 15368.40 | 1134.35 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 71.85 | 67.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 35484.69 | 20-JAN-22:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 461.51 |
February | 33964.35 | 17-FEB-22:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 492.90 |
March | 37765.83 | 15-MAR-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 312.03 |
April | 34932.84 | 07-APR-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 340.13 |
May | 37126.36 | 17-MAY-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 189.47 |
June | 42230.58 | 26-JUN-20:10 | 40553.76 | 8448.71 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 214.14 | 0.00 |
July | 42199.73 | 17-JUL-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 121.44 | 0.00 |
August | 42505.03 | 16-AUG-20:10 | 40553.76 | 8448.71 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 121.01 | 0.00 |
September | 41333.84 | 12-SEP-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.26 |
October | 38629.80 | 10-OCT-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 285.56 |
November | 36092.64 | 07-NOV-22:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 490.53 |
December | 33289.81 | 04-DEC-22:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 478.86 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 33289.81 | 40553.76 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 42505.03 | 45622.98 | 8448.71 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 214.14 | 492.90 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2556.65 | 23-JAN-16:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.78 |
February | 2557.20 | 17-FEB-16:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.52 |
March | 2663.74 | 13-MAR-15:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
April | 2615.95 | 07-APR-15:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.73 |
May | 2590.73 | 09-MAY-15:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.20 |
June | 2662.38 | 14-JUN-15:02 | 486.00 | 249.04 | 250.23 | 0.00 | 0.00 | 0.00 | 0.00 | 31.11 | 0.00 |
July | 2683.39 | 01-JUL-18:02 | 702.00 | 1067.29 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 11.43 | 0.00 |
August | 2674.91 | 17-AUG-15:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 19.62 | 0.00 |
September | 2698.00 | 28-SEP-15:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 15.86 | 0.00 |
October | 2684.28 | 11-OCT-15:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 6.48 | 0.00 |
November | 2617.88 | 05-NOV-15:02 | 324.00 | 352.21 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.65 |
December | 2506.20 | 02-DEC-16:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.56 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2506.20 | 324.00 | 249.04 | 250.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2698.00 | 702.00 | 1067.29 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 31.11 | 23.52 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2419.30 | 23-JAN-16:02 | 583.20 | 298.81 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.21 |
February | 2417.84 | 26-FEB-16:02 | 324.00 | 352.17 | 331.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.41 |
March | 2824.48 | 08-MAR-17:11 | 972.00 | 498.01 | 1264.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.91 |
April | 2921.57 | 08-APR-18:01 | 1170.00 | 1778.61 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.37 |
May | 2846.38 | 27-MAY-16:11 | 954.00 | 586.94 | 1053.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.41 |
June | 2815.99 | 18-JUN-21:51 | 1386.00 | 1511.82 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.43 |
July | 2908.00 | 01-JUL-08:61 | 540.00 | 996.02 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 2.39 | 0.00 |
August | 2759.93 | 11-AUG-21:51 | 1620.00 | 1072.50 | 805.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.05 |
September | 2711.15 | 15-SEP-19:51 | 1386.00 | 1778.61 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.84 |
October | 2768.21 | 14-OCT-16:11 | 954.00 | 586.94 | 1053.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.17 |
November | 2493.24 | 07-NOV-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.94 |
December | 2396.70 | 02-DEC-16:01 | 378.00 | 410.86 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.18 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2396.70 | 324.00 | 298.81 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2921.57 | 1620.00 | 1778.61 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 2.39 | 30.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 860.98 | 20-JAN-12:40 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.28 |
February | 819.27 | 18-FEB-13:00 | 0.00 | 36.89 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.77 |
March | 737.15 | 14-MAR-12:40 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.36 |
April | 457.27 | 08-APR-13:00 | 0.00 | 36.89 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.60 |
May | 358.78 | 05-MAY-13:00 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.35 |
June | 422.27 | 14-JUN-13:30 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 5.52 | 0.00 |
July | 457.58 | 23-JUL-13:00 | 0.00 | 36.89 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 4.97 | 0.00 |
August | 590.40 | 31-AUG-12:40 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 2.28 | 0.00 |
September | 762.05 | 28-SEP-13:00 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 2.61 | 0.00 |
October | 794.90 | 10-OCT-12:30 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.25 |
November | 854.36 | 07-NOV-12:10 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.79 |
December | 776.08 | 17-DEC-12:30 | 0.00 | 36.89 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.96 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 358.78 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 860.98 | 0.00 | 36.89 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 5.52 | 7.60 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 726.64 | 21-JAN-09:02 | 324.00 | 375.72 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.52 |
February | 728.58 | 19-FEB-09:02 | 324.00 | 375.72 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.42 |
March | 798.48 | 14-MAR-20:51 | 1281.60 | 796.18 | 1424.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.29 |
April | 810.81 | 20-APR-20:31 | 1281.60 | 796.18 | 1424.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.44 |
May | 838.12 | 17-MAY-21:51 | 1440.00 | 599.37 | 701.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.97 |
June | 871.83 | 12-JUN-08:61 | 288.00 | 393.62 | 887.73 | 0.00 | 0.00 | 0.00 | 0.00 | 2.11 | 0.00 |
July | 918.59 | 01-JUL-08:61 | 540.00 | 626.21 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.91 | 0.00 |
August | 881.88 | 01-AUG-21:51 | 1620.00 | 674.29 | 789.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.16 |
September | 849.71 | 08-SEP-21:51 | 1620.00 | 674.29 | 789.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 |
October | 803.34 | 11-OCT-15:02 | 583.20 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 1.95 | 0.00 |
November | 740.03 | 09-NOV-19:02 | 831.60 | 597.13 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.61 |
December | 714.19 | 03-DEC-09:02 | 324.00 | 375.72 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 714.19 | 288.00 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 918.59 | 1620.00 | 796.18 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 2.11 | 12.42 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2249.13 | 20-JAN-09:02 | 216.00 | 469.61 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.72 |
February | 2284.80 | 27-FEB-09:02 | 216.00 | 469.61 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.81 |
March | 2319.71 | 10-MAR-09:01 | 252.00 | 547.88 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.68 |
April | 2271.10 | 07-APR-08:62 | 216.00 | 469.61 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.15 |
May | 2285.44 | 13-MAY-08:62 | 324.00 | 597.68 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 |
June | 2379.88 | 27-JUN-08:62 | 216.00 | 469.61 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 2.41 | 0.00 |
July | 2440.75 | 01-JUL-08:61 | 540.00 | 996.14 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 6.90 | 0.00 |
August | 2397.00 | 05-AUG-08:62 | 324.00 | 597.68 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.90 |
September | 2355.58 | 28-SEP-08:62 | 216.00 | 469.61 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.59 |
October | 2310.59 | 11-OCT-15:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 7.04 | 0.00 |
November | 2295.20 | 07-NOV-09:02 | 216.00 | 469.61 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.18 |
December | 2220.28 | 03-DEC-09:02 | 324.00 | 597.68 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2220.28 | 216.00 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2440.75 | 583.20 | 996.14 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 7.04 | 35.81 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2131.61 | 24-JAN-09:02 | 216.00 | 469.55 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.32 |
February | 2191.48 | 27-FEB-09:02 | 216.00 | 469.55 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.44 |
March | 2264.80 | 15-MAR-18:31 | 1386.00 | 1582.97 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.03 |
April | 2239.01 | 20-APR-20:31 | 1281.60 | 1266.37 | 1453.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.42 |
May | 2659.11 | 04-MAY-08:51 | 360.00 | 782.59 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 |
June | 2902.73 | 27-JUN-08:32 | 216.00 | 469.55 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.20 |
July | 2819.87 | 01-JUL-07:32 | 477.00 | 498.01 | 1185.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.35 |
August | 2849.55 | 06-AUG-08:32 | 324.00 | 597.61 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.82 |
September | 2681.90 | 18-SEP-08:51 | 324.00 | 704.33 | 1019.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.95 |
October | 2620.24 | 11-OCT-08:51 | 360.00 | 782.59 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.46 |
November | 2184.43 | 07-NOV-09:02 | 216.00 | 469.55 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.67 |
December | 2113.38 | 03-DEC-09:02 | 324.00 | 597.61 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2113.38 | 216.00 | 469.55 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.20 | |
Maximum of Months | 2902.73 | 1386.00 | 1582.97 | 1453.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.32 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1872.47 | 20-JAN-13:50 | 502.97 | 518.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.66 |
February | 1925.72 | 18-FEB-13:45 | 1508.90 | 1037.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.51 |
March | 2042.61 | 15-MAR-10:33 | 1508.90 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.43 |
April | 1835.80 | 21-APR-10:33 | 1508.90 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.84 |
May | 2020.87 | 18-MAY-10:33 | 1508.90 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.68 |
June | 3264.92 | 26-JUN-18:25 | 3520.78 | 3319.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.65 | 0.00 |
July | 2946.09 | 01-JUL-18:40 | 1508.90 | 1452.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.89 | 0.00 |
August | 3012.43 | 11-AUG-18:30 | 3520.78 | 3319.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.73 | 0.00 |
September | 2697.84 | 12-SEP-18:03 | 10562.33 | 9959.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.88 | 0.00 |
October | 2134.00 | 11-OCT-12:50 | 502.97 | 518.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.79 | 0.00 |
November | 1975.61 | 07-NOV-13:50 | 502.97 | 518.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.20 |
December | 1770.41 | 17-DEC-13:00 | 754.45 | 622.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.81 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 1770.41 | 502.97 | 518.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3264.92 | 10562.33 | 9959.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.65 | 27.84 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2712.48 | 20-JAN-16:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.05 |
February | 2714.58 | 17-FEB-16:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.72 |
March | 2827.80 | 13-MAR-15:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.23 |
April | 2768.26 | 07-APR-15:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.89 |
May | 2733.90 | 04-MAY-15:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 4.97 | 0.00 |
June | 2831.01 | 14-JUN-15:02 | 486.00 | 249.04 | 250.23 | 0.00 | 0.00 | 0.00 | 0.00 | 30.89 | 0.00 |
July | 2848.77 | 01-JUL-18:02 | 702.00 | 1067.29 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 11.23 | 0.00 |
August | 2840.54 | 14-AUG-15:02 | 486.00 | 249.04 | 250.23 | 0.00 | 0.00 | 0.00 | 0.00 | 26.03 | 0.00 |
September | 2864.50 | 28-SEP-15:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 15.66 | 0.00 |
October | 2842.89 | 11-OCT-15:02 | 583.20 | 298.84 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 6.31 | 0.00 |
November | 2782.51 | 05-NOV-15:02 | 324.00 | 352.21 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.88 |
December | 2660.51 | 02-DEC-16:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.76 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2660.51 | 324.00 | 249.04 | 250.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2864.50 | 702.00 | 1067.29 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 30.89 | 23.72 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2539.73 | 23-JAN-16:02 | 583.20 | 298.81 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.26 |
February | 2537.25 | 17-FEB-16:02 | 583.20 | 298.81 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.96 |
March | 3049.41 | 08-MAR-17:11 | 972.00 | 498.01 | 1264.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.05 |
April | 3120.79 | 08-APR-17:42 | 583.20 | 907.09 | 758.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.29 |
May | 3044.83 | 27-MAY-16:11 | 954.00 | 586.94 | 1053.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.19 |
June | 3042.66 | 18-JUN-21:51 | 1386.00 | 1511.82 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.69 |
July | 3036.34 | 01-JUL-08:61 | 540.00 | 996.02 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 2.59 | 0.00 |
August | 2913.20 | 11-AUG-21:51 | 1620.00 | 1072.50 | 805.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.29 |
September | 2914.99 | 15-SEP-19:51 | 1386.00 | 1778.61 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.83 |
October | 3000.13 | 08-OCT-18:11 | 1170.00 | 1778.61 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.25 |
November | 2631.89 | 07-NOV-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.08 |
December | 2523.31 | 02-DEC-16:01 | 378.00 | 410.86 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.28 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2523.31 | 378.00 | 298.81 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3120.79 | 1620.00 | 1778.61 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 2.59 | 32.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1508.83 | 20-JAN-13:15 | 72.00 | 62.62 | 61.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 |
February | 1541.82 | 18-FEB-13:33 | 162.00 | 110.70 | 100.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.60 |
March | 1460.06 | 13-MAR-15:02 | 583.20 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.32 |
April | 1401.19 | 07-APR-15:02 | 583.20 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.51 |
May | 1391.08 | 04-MAY-15:02 | 583.20 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 2.49 | 0.00 |
June | 1389.08 | 07-JUN-15:02 | 486.00 | 156.55 | 245.16 | 0.00 | 0.00 | 0.00 | 0.00 | 11.15 | 0.00 |
July | 1396.71 | 01-JUL-08:61 | 540.00 | 626.21 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 3.91 | 0.00 |
August | 1422.42 | 17-AUG-15:02 | 583.20 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 10.02 | 0.00 |
September | 1462.21 | 28-SEP-15:02 | 583.20 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 7.92 | 0.00 |
October | 1464.23 | 11-OCT-15:02 | 583.20 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 3.06 | 0.00 |
November | 1495.14 | 07-NOV-13:15 | 72.00 | 62.62 | 61.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.65 |
December | 1400.68 | 29-DEC-13:55 | 72.00 | 62.62 | 61.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.25 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1389.08 | 72.00 | 62.62 | 61.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1541.82 | 583.20 | 626.21 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 11.15 | 18.25 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18540.13 | 20-JAN-22:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.21 |
February | 18313.66 | 27-FEB-22:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.74 |
March | 20365.98 | 14-MAR-21:03 | 80966.30 | 5976.06 | 20243.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.76 |
April | 20457.39 | 20-APR-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.21 |
May | 21562.02 | 31-MAY-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.88 |
June | 23350.14 | 26-JUN-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 20.70 | 0.00 |
July | 23198.89 | 17-JUL-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 26.65 | 0.00 |
August | 23033.81 | 16-AUG-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 7.45 | 0.00 |
September | 22220.17 | 12-SEP-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.49 |
October | 20422.12 | 10-OCT-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.71 |
November | 19414.54 | 09-NOV-23:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.60 |
December | 18567.21 | 04-DEC-23:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.47 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 18313.66 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23350.14 | 80966.30 | 5976.06 | 20243.71 | 0.00 | 0.00 | 0.00 | 0.00 | 26.65 | 143.74 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 20173.63 | 20-JAN-22:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.21 |
February | 19899.58 | 27-FEB-22:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.75 |
March | 21686.08 | 14-MAR-21:03 | 80966.30 | 5976.06 | 20243.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.76 |
April | 21948.18 | 20-APR-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.22 |
May | 22865.98 | 31-MAY-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.88 |
June | 24545.07 | 26-JUN-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 20.68 | 0.00 |
July | 24426.75 | 17-JUL-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 23.63 | 0.00 |
August | 24219.91 | 16-AUG-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 7.43 | 0.00 |
September | 23403.40 | 12-SEP-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.52 |
October | 21708.80 | 10-OCT-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.71 |
November | 20847.85 | 09-NOV-22:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.59 |
December | 20217.07 | 04-DEC-23:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.47 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 19899.58 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24545.07 | 80966.30 | 5976.06 | 20243.71 | 0.00 | 0.00 | 0.00 | 0.00 | 23.63 | 143.75 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 28644.16 | 20-JAN-11:40 | 533.71 | 294.67 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 26.51 |
February | 29171.69 | 18-FEB-11:40 | 800.57 | 294.67 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 36.02 |
March | 30252.37 | 12-MAR-10:40 | 1601.14 | 707.21 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 47.25 |
April | 29941.66 | 20-APR-10:33 | 1601.14 | 884.01 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 26.40 |
May | 30506.58 | 16-MAY-10:33 | 1601.14 | 884.01 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 3.16 | 0.00 |
June | 31319.46 | 26-JUN-10:40 | 1601.14 | 884.01 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 45.70 | 0.00 |
July | 31550.38 | 23-JUL-10:40 | 1601.14 | 707.21 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 29.57 | 0.00 |
August | 31636.54 | 05-AUG-10:40 | 2401.70 | 884.01 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 25.97 | 0.00 |
September | 31096.77 | 04-SEP-10:40 | 1601.14 | 707.21 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 14.96 | 0.00 |
October | 30241.70 | 07-OCT-10:33 | 2401.70 | 884.01 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 20.98 |
November | 29455.26 | 05-NOV-10:40 | 1601.14 | 707.21 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 34.17 |
December | 28399.67 | 02-DEC-11:50 | 800.57 | 294.67 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 25.43 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 28399.67 | 533.71 | 294.67 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31636.54 | 2401.70 | 884.01 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 45.70 | 47.25 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4248.15 | 20-JAN-13:50 | 532.32 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.25 |
February | 4300.52 | 18-FEB-13:45 | 1596.96 | 1097.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.30 |
March | 5020.55 | 15-MAR-14:10 | 798.48 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.57 |
April | 4065.82 | 21-APR-10:33 | 1596.96 | 1646.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.70 |
May | 4373.85 | 18-MAY-10:33 | 1596.96 | 1646.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.85 |
June | 6945.48 | 26-JUN-14:10 | 798.48 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.51 | 0.00 |
July | 6913.73 | 23-JUL-12:50 | 532.32 | 439.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.12 | 0.00 |
August | 7205.10 | 16-AUG-15:02 | 5323.20 | 2195.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.40 | 0.00 |
September | 6830.79 | 09-SEP-12:50 | 798.48 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.68 | 0.00 |
October | 5127.33 | 11-OCT-14:10 | 798.48 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.45 | 0.00 |
November | 4445.91 | 07-NOV-13:40 | 532.32 | 548.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.03 |
December | 3858.08 | 03-DEC-13:00 | 798.48 | 658.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.70 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 3858.08 | 532.32 | 439.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7205.10 | 5323.20 | 2195.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.51 | 52.70 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.391909E+12 | 231959.89 | 24-JAN-19:30 | 0.565204E+12 | 577852.69 | 05-JAN-19:10 |
February | 0.350011E+12 | 229104.81 | 17-FEB-19:30 | 0.532719E+12 | 579133.59 | 24-FEB-18:30 |
March | 0.386739E+12 | 241133.86 | 14-MAR-18:10 | 0.548523E+12 | 568795.42 | 02-MAR-18:49 |
April | 0.366178E+12 | 236730.61 | 20-APR-20:40 | 0.517241E+12 | 560066.16 | 04-APR-17:30 |
May | 0.403722E+12 | 295339.60 | 31-MAY-18:19 | 0.489651E+12 | 513405.25 | 01-MAY-20:10 |
June | 0.483802E+12 | 365749.68 | 26-JUN-19:30 | 0.369791E+12 | 337142.95 | 01-JUN-17:30 |
July | 0.509408E+12 | 360506.78 | 17-JUL-19:30 | 0.373318E+12 | 330552.48 | 05-JUL-21:00 |
August | 0.499178E+12 | 358172.03 | 10-AUG-19:10 | 0.371156E+12 | 324453.97 | 12-AUG-21:00 |
September | 0.451369E+12 | 348701.87 | 12-SEP-18:30 | 0.394611E+12 | 443235.46 | 22-SEP-20:00 |
October | 0.401436E+12 | 251834.70 | 10-OCT-18:10 | 0.494611E+12 | 528350.57 | 27-OCT-17:00 |
November | 0.381928E+12 | 237517.70 | 07-NOV-19:30 | 0.499942E+12 | 548353.02 | 22-NOV-18:19 |
December | 0.388480E+12 | 228409.64 | 14-DEC-19:10 | 0.619363E+12 | 607509.47 | 21-DEC-19:30 |
Annual Sum or Average | 0.501416E+13 | 0.577613E+13 | ||||
Minimum of Months | 0.350011E+12 | 228409.64 | 0.369791E+12 | 324453.97 | ||
Maximum of Months | 0.509408E+12 | 365749.68 | 0.619363E+12 | 607509.47 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.670763E+11 | 0.199069E+11 | 0.140828E+12 | 0.691145E+11 | 0.439974E+11 | 0.519647E+10 | 0.00 | 0.122475E+11 | 0.00 | 0.00 | 0.203052E+11 | 0.804729E+10 | 0.00 |
February | 0.603817E+11 | 0.167606E+11 | 0.127191E+12 | 0.624260E+11 | 0.390968E+11 | 0.421531E+10 | 0.00 | 0.919242E+10 | 0.00 | 0.00 | 0.187992E+11 | 0.727183E+10 | 0.00 |
March | 0.664904E+11 | 0.168346E+11 | 0.140882E+12 | 0.691168E+11 | 0.438101E+11 | 0.505011E+10 | 0.00 | 0.155019E+11 | 0.00 | 0.00 | 0.158228E+11 | 0.804583E+10 | 0.00 |
April | 0.640698E+11 | 0.145470E+11 | 0.136245E+12 | 0.668843E+11 | 0.405968E+11 | 0.495507E+10 | 0.00 | 0.119584E+11 | 0.00 | 0.00 | 0.141002E+11 | 0.779713E+10 | 0.00 |
May | 0.657791E+11 | 0.135180E+11 | 0.140860E+12 | 0.691151E+11 | 0.476910E+11 | 0.698789E+10 | 0.00 | 0.405990E+11 | 0.00 | 0.00 | 0.590142E+10 | 0.804710E+10 | 0.00 |
June | 0.633888E+11 | 0.122817E+11 | 0.136336E+12 | 0.668863E+11 | 0.575686E+11 | 0.729214E+10 | 0.00 | 0.117435E+12 | 0.00 | 0.00 | 0.972781E+10 | 0.778856E+10 | 0.00 |
July | 0.656186E+11 | 0.130516E+11 | 0.140770E+12 | 0.691125E+11 | 0.594989E+11 | 0.767953E+10 | 0.00 | 0.130027E+12 | 0.00 | 0.00 | 0.103429E+11 | 0.805549E+10 | 0.00 |
August | 0.659875E+11 | 0.143620E+11 | 0.140892E+12 | 0.691165E+11 | 0.599667E+11 | 0.760997E+10 | 0.00 | 0.118951E+12 | 0.00 | 0.00 | 0.897141E+10 | 0.804706E+10 | 0.00 |
September | 0.642168E+11 | 0.155316E+11 | 0.136256E+12 | 0.668845E+11 | 0.564465E+11 | 0.703694E+10 | 0.00 | 0.850756E+11 | 0.00 | 0.00 | 0.706635E+10 | 0.779843E+10 | 0.00 |
October | 0.668205E+11 | 0.178488E+11 | 0.140818E+12 | 0.691144E+11 | 0.490946E+11 | 0.557109E+10 | 0.00 | 0.246267E+11 | 0.00 | 0.00 | 0.143009E+11 | 0.804575E+10 | 0.00 |
November | 0.648437E+11 | 0.188112E+11 | 0.136330E+12 | 0.668857E+11 | 0.447165E+11 | 0.502310E+10 | 0.00 | 0.139228E+11 | 0.00 | 0.00 | 0.185946E+11 | 0.778032E+10 | 0.00 |
December | 0.670878E+11 | 0.203362E+11 | 0.140770E+12 | 0.691134E+11 | 0.444824E+11 | 0.438319E+10 | 0.00 | 0.889412E+10 | 0.00 | 0.00 | 0.201943E+11 | 0.805584E+10 | 0.00 |
Annual Sum or Average | 0.781761E+12 | 0.193790E+12 | 0.165818E+13 | 0.813770E+12 | 0.586966E+12 | 0.710008E+11 | 0.00 | 0.588431E+12 | 0.00 | 0.00 | 0.164127E+12 | 0.947806E+11 | 0.00 |
Minimum of Months | 0.603817E+11 | 0.122817E+11 | 0.127191E+12 | 0.624260E+11 | 0.390968E+11 | 0.421531E+10 | 0.00 | 0.889412E+10 | 0.00 | 0.00 | 0.590142E+10 | 0.727183E+10 | 0.00 |
Maximum of Months | 0.670878E+11 | 0.203362E+11 | 0.140892E+12 | 0.691168E+11 | 0.599667E+11 | 0.767953E+10 | 0.00 | 0.130027E+12 | 0.00 | 0.00 | 0.203052E+11 | 0.805584E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.151918E+12 | 0.00 | 0.160393E+12 | 0.00 | 0.252893E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.164843E+12 | 0.00 | 0.230673E+12 | 0.00 | 0.00 |
March | 0.152024E+12 | 0.00 | 0.143983E+12 | 0.00 | 0.252516E+12 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.133529E+12 | 0.00 | 0.236757E+12 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.103629E+12 | 0.00 | 0.234044E+12 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 0.639068E+10 | 0.00 | 0.216287E+12 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 0.572249E+10 | 0.00 | 0.215775E+12 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 0.596063E+10 | 0.00 | 0.213156E+12 | 0.00 | 0.00 |
September | 0.146971E+12 | 0.00 | 0.384319E+11 | 0.00 | 0.209209E+12 | 0.00 | 0.00 |
October | 0.151903E+12 | 0.00 | 0.118610E+12 | 0.00 | 0.224098E+12 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.125672E+12 | 0.00 | 0.227179E+12 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.222291E+12 | 0.00 | 0.245252E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178884E+13 | 0.00 | 0.122945E+13 | 0.00 | 0.275784E+13 | 0.00 | 0.00 |
Minimum of Months | 0.137204E+12 | 0.00 | 0.572249E+10 | 0.00 | 0.209209E+12 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.222291E+12 | 0.00 | 0.252893E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 64632.59 | 02-JAN-20:10 | 12338.45 | 01-JAN-00:10 | 89171.45 | 02-JAN-07:10 | 49607.07 | 02-JAN-07:19 | 33171.39 | 20-JAN-22:10 | 3370.30 | 01-JAN-16:10 | 0.00 | 01-JAN-00:10 |
February | 64632.59 | 01-FEB-20:10 | 12338.45 | 01-FEB-00:10 | 89171.45 | 01-FEB-07:10 | 49607.07 | 01-FEB-07:19 | 30315.30 | 17-FEB-22:10 | 3354.54 | 14-FEB-16:30 | 0.00 | 01-FEB-00:10 |
March | 64632.59 | 01-MAR-20:10 | 12338.45 | 01-MAR-00:10 | 89171.45 | 01-MAR-07:10 | 49607.07 | 13-MAR-06:19 | 37840.62 | 14-MAR-21:10 | 3314.69 | 05-MAR-16:10 | 0.00 | 01-MAR-00:10 |
April | 64632.59 | 03-APR-19:10 | 12338.45 | 01-APR-00:10 | 89171.45 | 03-APR-06:10 | 49606.78 | 03-APR-06:19 | 36192.17 | 20-APR-21:10 | 3273.62 | 04-APR-09:00 | 0.00 | 01-APR-00:10 |
May | 64632.59 | 01-MAY-19:10 | 12338.45 | 01-MAY-00:10 | 89171.45 | 01-MAY-06:10 | 49605.38 | 19-MAY-06:19 | 38309.12 | 16-MAY-21:00 | 4173.18 | 31-MAY-18:49 | 0.00 | 01-MAY-00:10 |
June | 64632.59 | 01-JUN-19:19 | 12338.45 | 01-JUN-00:10 | 89171.45 | 01-JUN-06:10 | 49605.49 | 16-JUN-06:19 | 60628.05 | 27-JUN-19:10 | 5458.62 | 15-JUN-18:10 | 0.00 | 01-JUN-00:10 |
July | 64632.59 | 03-JUL-19:30 | 12338.45 | 01-JUL-00:10 | 89171.45 | 03-JUL-06:10 | 49605.49 | 28-JUL-06:19 | 58307.50 | 17-JUL-18:49 | 5537.81 | 10-JUL-18:10 | 0.00 | 01-JUL-00:10 |
August | 64632.59 | 01-AUG-19:10 | 12338.45 | 01-AUG-00:10 | 89171.45 | 01-AUG-06:10 | 49605.59 | 18-AUG-06:19 | 55156.49 | 10-AUG-19:10 | 5456.18 | 10-AUG-19:10 | 0.00 | 01-AUG-00:10 |
September | 64632.59 | 01-SEP-19:10 | 12338.45 | 01-SEP-00:10 | 89171.45 | 01-SEP-06:10 | 49606.57 | 19-SEP-06:19 | 53656.60 | 12-SEP-18:30 | 5475.69 | 12-SEP-18:30 | 0.00 | 01-SEP-00:10 |
October | 64632.59 | 02-OCT-19:10 | 12338.45 | 01-OCT-00:10 | 89171.45 | 02-OCT-06:10 | 49607.07 | 02-OCT-06:19 | 44238.15 | 10-OCT-21:10 | 3303.36 | 21-OCT-08:00 | 0.00 | 01-OCT-00:10 |
November | 64632.59 | 01-NOV-19:10 | 12338.45 | 01-NOV-00:10 | 89171.45 | 01-NOV-06:10 | 49607.07 | 01-NOV-06:19 | 36309.50 | 07-NOV-22:10 | 3324.01 | 12-NOV-16:30 | 0.00 | 01-NOV-00:10 |
December | 64632.59 | 01-DEC-20:10 | 12338.45 | 01-DEC-00:10 | 89171.45 | 01-DEC-07:10 | 49607.07 | 01-DEC-07:19 | 32486.75 | 04-DEC-22:10 | 3376.09 | 22-DEC-09:30 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 64632.59 | 12338.45 | 89171.45 | 49605.38 | 30315.30 | 3273.62 | 0.00 | |||||||
Maximum of Months | 64632.59 | 12338.45 | 89171.45 | 49607.07 | 60628.05 | 5537.81 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 52069.06 | 20-JAN-13:20 | 0.00 | 0.00 | 9938.94 | 01-JAN-00:10 | 4751.13 | 30-JAN-07:49 | 0.00 |
February | 48086.17 | 18-FEB-13:39 | 0.00 | 0.00 | 9938.94 | 01-FEB-00:10 | 4751.13 | 22-FEB-07:40 | 0.00 |
March | 71292.44 | 13-MAR-15:09 | 0.00 | 0.00 | 9938.94 | 01-MAR-00:10 | 4751.13 | 03-MAR-07:40 | 0.00 |
April | 52571.52 | 07-APR-15:09 | 0.00 | 0.00 | 9938.94 | 01-APR-00:10 | 4751.13 | 26-APR-06:30 | 0.00 |
May | 83152.48 | 31-MAY-18:19 | 0.00 | 0.00 | 9938.94 | 01-MAY-05:10 | 4751.13 | 30-MAY-06:30 | 0.00 |
June | 147665.61 | 26-JUN-18:10 | 0.00 | 0.00 | 9938.94 | 14-JUN-06:00 | 4751.10 | 20-JUN-18:00 | 0.00 |
July | 115914.49 | 15-JUL-18:10 | 0.00 | 0.00 | 9938.94 | 01-JUL-08:09 | 4751.13 | 11-JUL-06:00 | 0.00 |
August | 131451.37 | 16-AUG-15:20 | 0.00 | 0.00 | 9938.94 | 02-AUG-09:00 | 4751.12 | 28-AUG-06:30 | 0.00 |
September | 102663.92 | 28-SEP-15:20 | 0.00 | 0.00 | 9938.94 | 29-SEP-08:00 | 4751.13 | 22-SEP-06:40 | 0.00 |
October | 87665.46 | 11-OCT-15:09 | 0.00 | 0.00 | 9938.94 | 01-OCT-20:10 | 4751.13 | 10-OCT-06:30 | 0.00 |
November | 55127.95 | 07-NOV-13:00 | 0.00 | 0.00 | 9938.94 | 01-NOV-00:10 | 4751.13 | 30-NOV-07:00 | 0.00 |
December | 47279.43 | 02-DEC-13:20 | 0.00 | 0.00 | 9938.94 | 01-DEC-00:10 | 4751.12 | 15-DEC-07:40 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 47279.43 | 0.00 | 0.00 | 9938.94 | 4751.10 | 0.00 | |||
Maximum of Months | 147665.61 | 0.00 | 0.00 | 9938.94 | 4751.13 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 231959.89 | 24-JAN-19:30 | 57474.69 | 77573.37 | 12338.45 | 28169.74 | 27791.54 | 2483.38 | 0.00 | 9643.39 | 0.00 |
February | 229104.81 | 17-FEB-19:30 | 57474.69 | 77573.37 | 12338.45 | 28169.74 | 26307.30 | 2473.84 | 0.00 | 8275.54 | 0.00 |
March | 241133.86 | 14-MAR-18:10 | 57474.69 | 77573.37 | 12338.45 | 28159.60 | 26211.07 | 2556.10 | 0.00 | 30288.85 | 0.00 |
April | 236730.61 | 20-APR-20:40 | 57474.69 | 88218.55 | 12338.45 | 10998.34 | 33545.80 | 2565.56 | 0.00 | 23608.21 | 0.00 |
May | 295339.60 | 31-MAY-18:19 | 53381.59 | 77573.37 | 0.00 | 28166.69 | 32024.30 | 3958.13 | 0.00 | 83152.48 | 0.00 |
June | 365749.68 | 26-JUN-19:30 | 64632.59 | 86439.81 | 12338.45 | 10999.44 | 41509.18 | 3960.74 | 0.00 | 129595.41 | 0.00 |
July | 360506.78 | 17-JUL-19:30 | 64632.59 | 86439.81 | 12338.45 | 10999.44 | 53362.51 | 5286.18 | 0.00 | 111076.79 | 0.00 |
August | 358172.03 | 10-AUG-19:10 | 64632.59 | 86439.81 | 12338.45 | 10993.88 | 55156.49 | 5456.18 | 0.00 | 106895.49 | 0.00 |
September | 348701.87 | 12-SEP-18:30 | 57474.69 | 77573.37 | 12338.45 | 28169.74 | 53656.60 | 5475.69 | 0.00 | 97469.10 | 0.00 |
October | 251834.70 | 10-OCT-18:10 | 57474.69 | 77573.37 | 12338.45 | 28159.60 | 29184.66 | 2607.96 | 0.00 | 37966.91 | 0.00 |
November | 237517.70 | 07-NOV-19:30 | 57474.69 | 77573.37 | 12338.45 | 28169.74 | 30907.43 | 2512.23 | 0.00 | 12060.33 | 0.00 |
December | 228409.64 | 14-DEC-19:10 | 57474.69 | 77573.37 | 12338.45 | 28159.60 | 24586.54 | 2558.56 | 0.00 | 8683.98 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 228409.64 | 53381.59 | 77573.37 | 0.00 | 10993.88 | 24586.54 | 2473.84 | 0.00 | 8275.54 | 0.00 | |
Maximum of Months | 365749.68 | 64632.59 | 88218.55 | 12338.45 | 28169.74 | 55156.49 | 5475.69 | 0.00 | 129595.41 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 245298.47 | 05-JAN-09:09 | 0.00 | 262534.03 | 27-JAN-21:30 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 238240.46 | 12-FEB-07:10 | 0.00 | 262642.43 | 13-FEB-21:19 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 239778.60 | 05-MAR-11:50 | 0.00 | 262523.43 | 03-MAR-21:19 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 207636.66 | 17-APR-10:50 | 0.00 | 255195.87 | 03-APR-20:49 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 205070.11 | 01-MAY-00:10 | 0.00 | 246802.23 | 02-MAY-20:40 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 177184.29 | 09-JUN-03:39 | 0.00 | 236264.61 | 01-JUN-20:40 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 95314.11 | 02-JUL-04:00 | 0.00 | 226022.36 | 03-JUL-20:00 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 85377.15 | 23-AUG-04:00 | 0.00 | 222216.96 | 29-AUG-20:40 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 214811.30 | 21-SEP-14:20 | 0.00 | 226665.75 | 29-SEP-20:30 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 223069.37 | 09-OCT-05:10 | 0.00 | 236743.92 | 31-OCT-20:30 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 237870.04 | 02-NOV-10:39 | 0.00 | 247963.87 | 29-NOV-21:00 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 293095.06 | 21-DEC-09:20 | 0.00 | 255286.57 | 29-DEC-21:19 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 104248.32 | 0.00 | 85377.15 | 0.00 | 222216.96 | 0.00 | |||
Maximum of Months | 104248.32 | 0.00 | 293095.06 | 0.00 | 262642.43 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 20.44 | 0.17 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
Annual Sum or Average | 0.17 | 20.44 | 0.17 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 20.44 | 0.17 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 25.25 | 2.50 | 25.25 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 25.01 | 2.83 | 25.01 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.88 | 0.67 | 24.88 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.66 | 0.17 | 24.66 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 6.17 | 25.08 | 6.17 | 25.08 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 25.25 | 2.83 | 25.25 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.83 | 0.33 | 21.83 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 22.03 | 1.67 | 22.03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 21.88 | 2.00 | 21.88 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.75 | 0.50 | 21.75 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 21.91 | 3.33 | 21.91 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 42.83 | 22.28 | 42.83 | 22.28 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 28.83 | 22.17 | 28.83 | 22.17 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 34.33 | 22.43 | 34.33 | 22.43 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 20.00 | 22.27 | 20.00 | 22.27 |
October | 0.17 | 20.55 | 0.17 | 20.55 | 6.83 | 22.11 | 6.83 | 22.15 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.87 | 0.67 | 21.87 |
December | 0.83 | 20.38 | 0.83 | 20.38 | 0.00 | 20.38 | 0.00 | 20.38 |
Annual Sum or Average | 1.00 | 20.41 | 1.00 | 20.41 | 141.33 | 22.24 | 141.33 | 22.25 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.38 | 0.00 | 20.38 |
Maximum of Months | 0.83 | 20.55 | 0.83 | 20.55 | 42.83 | 22.43 | 42.83 | 22.43 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 20.54 | 0.17 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 |
February | 0.17 | 20.55 | 0.17 | 20.55 | 0.17 | 20.96 | 0.17 | 21.16 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.82 | 0.83 | 21.82 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.95 | 0.50 | 21.95 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 21.88 | 3.67 | 21.88 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 52.67 | 22.29 | 52.67 | 22.29 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 33.17 | 22.15 | 33.17 | 22.15 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 30.50 | 22.32 | 30.50 | 22.32 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 15.83 | 22.05 | 15.83 | 22.05 |
October | 0.17 | 20.54 | 0.17 | 20.54 | 1.67 | 21.69 | 1.67 | 21.80 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.67 | 20.39 | 1.67 | 20.39 | 0.00 | 20.39 | 0.00 | 20.39 |
Annual Sum or Average | 2.17 | 20.43 | 2.17 | 20.43 | 139.00 | 22.16 | 139.00 | 22.19 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.67 | 20.55 | 1.67 | 20.55 | 52.67 | 22.32 | 52.67 | 22.32 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 20.35 | 0.33 | 20.35 | 0.00 | 20.35 | 0.00 | 20.35 |
February | 0.50 | 20.46 | 0.50 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.76 | 0.17 | 21.76 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.83 | 0.33 | 21.83 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 21.94 | 8.83 | 21.94 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 50.17 | 21.94 | 50.17 | 21.94 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 49.50 | 21.96 | 49.50 | 21.96 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 21.67 | 21.88 | 21.67 | 21.88 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 21.89 | 13.00 | 21.89 |
October | 0.17 | 20.37 | 0.17 | 20.37 | 0.33 | 21.05 | 0.33 | 21.28 |
November | 0.17 | 20.50 | 0.17 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
December | 3.00 | 20.30 | 3.00 | 20.30 | 0.00 | 20.30 | 0.00 | 20.30 |
Annual Sum or Average | 4.17 | 20.34 | 4.17 | 20.34 | 144.00 | 21.85 | 144.00 | 21.89 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.30 | 0.00 | 20.30 |
Maximum of Months | 3.00 | 20.50 | 3.00 | 20.50 | 50.17 | 21.96 | 50.17 | 21.96 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.78 | 0.33 | 21.78 |
February | 0.33 | 20.54 | 0.33 | 20.54 | 4.17 | 21.80 | 4.17 | 21.90 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 21.82 | 2.83 | 21.82 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 21.94 | 7.50 | 21.94 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 22.05 | 7.17 | 22.05 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 36.33 | 22.08 | 36.33 | 22.08 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 34.17 | 22.12 | 34.17 | 22.12 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 32.17 | 22.01 | 32.17 | 22.01 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 25.83 | 22.04 | 25.83 | 22.04 |
October | 0.17 | 20.53 | 0.17 | 20.53 | 6.50 | 21.81 | 6.50 | 21.84 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.80 | 1.17 | 21.80 |
December | 1.00 | 20.34 | 1.00 | 20.34 | 0.50 | 20.62 | 0.50 | 20.81 |
Annual Sum or Average | 1.50 | 20.41 | 1.50 | 20.41 | 158.67 | 22.01 | 158.67 | 22.03 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 20.62 | 0.33 | 20.81 |
Maximum of Months | 1.00 | 20.54 | 1.00 | 20.54 | 36.33 | 22.12 | 36.33 | 22.12 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 20.47 | 0.50 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
February | 0.33 | 20.53 | 0.33 | 20.53 | 0.33 | 20.95 | 0.33 | 21.16 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.71 | 0.50 | 21.71 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 22.06 | 3.17 | 22.06 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 22.26 | 6.67 | 22.26 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 51.33 | 22.40 | 51.33 | 22.40 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 44.83 | 22.48 | 44.83 | 22.48 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 33.00 | 22.51 | 33.00 | 22.51 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 19.50 | 22.29 | 19.50 | 22.29 |
October | 0.17 | 20.52 | 0.17 | 20.52 | 1.17 | 21.58 | 1.17 | 21.71 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.80 | 0.17 | 21.80 |
December | 2.67 | 20.34 | 2.67 | 20.34 | 0.00 | 20.34 | 0.00 | 20.34 |
Annual Sum or Average | 3.67 | 20.38 | 3.67 | 20.38 | 160.67 | 22.32 | 160.67 | 22.37 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.34 | 0.00 | 20.34 |
Maximum of Months | 2.67 | 20.53 | 2.67 | 20.53 | 51.33 | 22.51 | 51.33 | 22.51 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 20.52 | 0.17 | 20.52 | 0.17 | 21.05 | 0.17 | 21.31 |
February | 0.17 | 20.54 | 0.17 | 20.54 | 2.00 | 21.81 | 2.00 | 21.91 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 21.85 | 4.33 | 21.85 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.77 | 0.67 | 21.77 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 21.95 | 5.00 | 21.95 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 47.83 | 22.35 | 47.83 | 22.35 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 31.67 | 22.26 | 31.67 | 22.26 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 22.61 | 37.50 | 22.61 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 20.83 | 22.33 | 20.83 | 22.33 |
October | 0.17 | 20.52 | 0.17 | 20.52 | 6.67 | 22.15 | 6.67 | 22.19 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.89 | 1.00 | 21.89 |
December | 1.33 | 20.36 | 1.33 | 20.36 | 0.00 | 20.36 | 0.00 | 20.36 |
Annual Sum or Average | 1.83 | 20.41 | 1.83 | 20.41 | 157.67 | 22.31 | 157.67 | 22.33 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.36 | 0.00 | 20.36 |
Maximum of Months | 1.33 | 20.54 | 1.33 | 20.54 | 47.83 | 22.61 | 47.83 | 22.61 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 20.50 | 0.33 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
February | 0.33 | 20.54 | 0.33 | 20.54 | 0.17 | 20.77 | 0.17 | 20.92 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.94 | 1.00 | 21.94 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.98 | 1.00 | 21.98 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 21.91 | 6.67 | 21.91 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 57.83 | 22.40 | 57.83 | 22.40 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 36.83 | 22.23 | 36.83 | 22.23 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 34.33 | 22.50 | 34.33 | 22.50 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 16.00 | 22.12 | 16.00 | 22.12 |
October | 0.17 | 20.51 | 0.17 | 20.51 | 1.67 | 21.68 | 1.67 | 21.79 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.67 | 20.35 | 2.67 | 20.35 | 0.00 | 20.35 | 0.00 | 20.35 |
Annual Sum or Average | 3.50 | 20.39 | 3.50 | 20.39 | 155.50 | 22.24 | 155.50 | 22.28 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.67 | 20.54 | 2.67 | 20.54 | 57.83 | 22.50 | 57.83 | 22.50 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 17.83 | 22.32 | 17.83 | 22.32 |
February | 0.33 | 20.53 | 0.33 | 20.53 | 12.83 | 22.38 | 12.83 | 22.43 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 22.05 | 6.17 | 22.05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.82 | 0.83 | 21.82 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 21.89 | 3.17 | 21.89 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 21.93 | 9.67 | 21.93 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 21.91 | 9.67 | 21.91 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 18.33 | 22.07 | 18.33 | 22.07 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 22.83 | 22.15 | 22.83 | 22.15 |
October | 0.17 | 20.50 | 0.17 | 20.50 | 24.67 | 22.98 | 24.67 | 23.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 26.67 | 22.47 | 26.67 | 22.47 |
December | 0.67 | 20.36 | 0.67 | 20.36 | 9.17 | 22.07 | 9.17 | 22.19 |
Annual Sum or Average | 1.17 | 20.43 | 1.17 | 20.43 | 161.83 | 22.31 | 161.83 | 22.33 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.82 | 0.83 | 21.82 |
Maximum of Months | 0.67 | 20.53 | 0.67 | 20.53 | 26.67 | 22.98 | 26.67 | 23.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 25.08 | 2.17 | 25.08 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 25.13 | 3.33 | 25.13 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.96 | 1.00 | 24.96 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.88 | 0.33 | 24.88 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 6.83 | 25.08 | 6.83 | 25.08 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 25.13 | 3.33 | 25.13 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 623.00 | 23.81 | 0.00 | 23.81 | 0.00 | 23.81 |
February | 657.17 | 23.67 | 0.00 | 23.67 | 0.00 | 23.67 |
March | 740.83 | 23.42 | 0.00 | 23.42 | 0.00 | 23.42 |
April | 702.17 | 23.48 | 0.00 | 23.48 | 0.00 | 23.48 |
May | 703.50 | 23.42 | 0.00 | 23.42 | 0.00 | 23.42 |
June | 490.33 | 23.60 | 110.33 | 23.64 | 64.83 | 23.66 |
July | 488.50 | 23.68 | 197.17 | 23.74 | 147.00 | 23.76 |
August | 319.83 | 23.85 | 248.17 | 23.90 | 89.50 | 23.91 |
September | 293.83 | 23.97 | 37.67 | 23.98 | 0.00 | 23.98 |
October | 437.00 | 23.98 | 0.00 | 23.98 | 0.00 | 23.98 |
November | 361.83 | 23.97 | 0.00 | 23.97 | 0.00 | 23.97 |
December | 684.50 | 23.97 | 0.00 | 23.97 | 0.00 | 23.97 |
Annual Sum or Average | 6502.50 | 23.70 | 593.33 | 23.71 | 301.33 | 23.72 |
Minimum of Months | 293.83 | 23.42 | 0.00 | 23.42 | 0.00 | 23.42 |
Maximum of Months | 740.83 | 23.98 | 248.17 | 23.98 | 147.00 | 23.98 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 576.17 | 21.53 | 183.33 | 21.83 | 74.83 | 21.75 |
February | 526.83 | 21.53 | 223.17 | 21.69 | 144.00 | 21.58 |
March | 607.83 | 21.65 | 141.17 | 21.75 | 85.33 | 21.68 |
April | 655.00 | 21.52 | 120.00 | 21.49 | 105.33 | 21.43 |
May | 642.17 | 22.05 | 30.67 | 22.10 | 8.00 | 22.09 |
June | 302.17 | 22.76 | 325.83 | 23.29 | 43.33 | 23.28 |
July | 315.83 | 22.85 | 412.17 | 23.30 | 111.33 | 23.25 |
August | 293.00 | 22.81 | 405.17 | 23.35 | 77.67 | 23.32 |
September | 331.33 | 22.58 | 236.33 | 23.16 | 0.83 | 23.16 |
October | 545.67 | 21.80 | 211.83 | 22.06 | 90.67 | 21.94 |
November | 555.50 | 21.65 | 177.17 | 21.96 | 62.67 | 21.89 |
December | 627.17 | 21.44 | 267.83 | 21.52 | 203.00 | 21.42 |
Annual Sum or Average | 5978.67 | 21.88 | 2734.67 | 22.24 | 1007.00 | 22.16 |
Minimum of Months | 293.00 | 21.44 | 30.67 | 21.49 | 0.83 | 21.42 |
Maximum of Months | 655.00 | 22.85 | 412.17 | 23.35 | 203.00 | 23.32 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 694.17 | 23.02 | 0.50 | 23.02 | 0.50 | 23.01 |
February | 631.67 | 22.82 | 9.33 | 22.80 | 9.33 | 22.77 |
March | 717.17 | 22.97 | 0.00 | 22.97 | 0.00 | 22.97 |
April | 662.50 | 22.85 | 0.00 | 22.85 | 0.00 | 22.85 |
May | 493.50 | 23.31 | 38.50 | 23.36 | 0.00 | 23.36 |
June | 147.67 | 23.80 | 290.50 | 23.89 | 76.83 | 23.90 |
July | 205.17 | 23.83 | 346.50 | 23.88 | 154.17 | 23.88 |
August | 163.17 | 23.85 | 394.50 | 23.93 | 107.00 | 23.93 |
September | 200.67 | 23.66 | 116.67 | 23.78 | 1.67 | 23.79 |
October | 604.83 | 23.21 | 1.00 | 23.21 | 0.00 | 23.21 |
November | 650.83 | 23.05 | 0.50 | 23.06 | 0.00 | 23.06 |
December | 738.67 | 22.70 | 25.67 | 22.64 | 25.67 | 22.59 |
Annual Sum or Average | 5910.00 | 23.07 | 1223.67 | 23.21 | 375.17 | 23.23 |
Minimum of Months | 147.67 | 22.70 | 0.00 | 22.64 | 0.00 | 22.59 |
Maximum of Months | 738.67 | 23.85 | 394.50 | 23.93 | 154.17 | 23.93 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.74 | 26.00 | 21.71 | 26.00 | 21.69 |
February | 672.00 | 21.58 | 93.83 | 21.51 | 93.83 | 21.46 |
March | 744.00 | 21.94 | 6.50 | 21.93 | 6.50 | 21.92 |
April | 720.00 | 22.01 | 6.33 | 22.00 | 6.33 | 21.99 |
May | 736.83 | 23.05 | 0.00 | 23.05 | 0.00 | 23.05 |
June | 310.17 | 23.82 | 131.33 | 23.85 | 14.67 | 23.85 |
July | 274.67 | 23.86 | 220.17 | 23.88 | 77.67 | 23.87 |
August | 296.50 | 23.81 | 178.67 | 23.86 | 42.17 | 23.86 |
September | 536.83 | 23.57 | 0.00 | 23.57 | 0.00 | 23.57 |
October | 743.83 | 22.55 | 15.17 | 22.52 | 15.17 | 22.49 |
November | 720.00 | 21.96 | 23.17 | 21.93 | 23.17 | 21.90 |
December | 744.00 | 21.55 | 167.17 | 21.45 | 167.17 | 21.38 |
Annual Sum or Average | 7242.83 | 22.38 | 868.33 | 22.42 | 472.67 | 22.39 |
Minimum of Months | 274.67 | 21.55 | 0.00 | 21.45 | 0.00 | 21.38 |
Maximum of Months | 744.00 | 23.86 | 220.17 | 23.88 | 167.17 | 23.87 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.41 | 58.50 | 21.38 | 58.50 | 21.36 |
February | 672.00 | 21.35 | 137.33 | 21.29 | 137.33 | 21.25 |
March | 744.00 | 21.62 | 24.67 | 21.60 | 24.67 | 21.58 |
April | 720.00 | 21.67 | 13.50 | 21.65 | 13.50 | 21.64 |
May | 744.00 | 22.72 | 0.00 | 22.72 | 0.00 | 22.72 |
June | 426.67 | 23.67 | 81.00 | 23.70 | 21.83 | 23.70 |
July | 369.33 | 23.73 | 189.33 | 23.74 | 88.50 | 23.72 |
August | 423.33 | 23.65 | 121.17 | 23.68 | 51.83 | 23.68 |
September | 643.00 | 23.36 | 0.00 | 23.36 | 0.00 | 23.36 |
October | 744.00 | 22.18 | 25.83 | 22.14 | 25.83 | 22.10 |
November | 720.00 | 21.61 | 43.67 | 21.58 | 43.67 | 21.54 |
December | 744.00 | 21.30 | 206.83 | 21.23 | 206.83 | 21.19 |
Annual Sum or Average | 7694.33 | 22.18 | 901.83 | 22.18 | 672.50 | 22.14 |
Minimum of Months | 369.33 | 21.30 | 0.00 | 21.23 | 0.00 | 21.19 |
Maximum of Months | 744.00 | 23.73 | 206.83 | 23.74 | 206.83 | 23.72 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 200.67 | 23.65 | 654.00 | 23.75 | 171.17 | 23.79 |
February | 186.67 | 23.53 | 579.33 | 23.73 | 149.83 | 23.78 |
March | 192.83 | 23.71 | 648.00 | 23.77 | 168.67 | 23.81 |
April | 205.17 | 23.81 | 642.67 | 23.78 | 188.33 | 23.82 |
May | 268.17 | 23.96 | 698.00 | 23.81 | 263.17 | 23.85 |
June | 369.67 | 23.98 | 711.33 | 23.80 | 369.67 | 23.84 |
July | 419.00 | 23.94 | 740.50 | 23.79 | 419.00 | 23.83 |
August | 409.17 | 23.93 | 734.00 | 23.78 | 409.17 | 23.82 |
September | 282.67 | 23.98 | 686.67 | 23.81 | 280.50 | 23.86 |
October | 213.50 | 23.85 | 672.17 | 23.78 | 199.83 | 23.82 |
November | 202.33 | 23.71 | 637.33 | 23.76 | 177.83 | 23.80 |
December | 200.33 | 23.35 | 594.00 | 23.71 | 145.50 | 23.76 |
Annual Sum or Average | 3150.17 | 23.82 | 7998.00 | 23.77 | 2942.67 | 23.82 |
Minimum of Months | 186.67 | 23.35 | 579.33 | 23.71 | 145.50 | 23.76 |
Maximum of Months | 419.00 | 23.98 | 740.50 | 23.81 | 419.00 | 23.86 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 399.17 | 22.74 | 191.83 | 23.07 | 14.83 | 23.02 |
February | 374.50 | 22.48 | 191.00 | 22.79 | 37.67 | 22.68 |
March | 428.17 | 22.42 | 135.17 | 22.75 | 10.50 | 22.71 |
April | 469.17 | 22.35 | 100.67 | 22.60 | 6.17 | 22.59 |
May | 243.00 | 22.98 | 230.00 | 23.43 | 11.00 | 23.45 |
June | 158.00 | 23.86 | 618.83 | 23.89 | 150.67 | 23.90 |
July | 200.00 | 23.82 | 669.17 | 23.89 | 193.83 | 23.88 |
August | 181.00 | 23.89 | 652.00 | 23.92 | 174.83 | 23.92 |
September | 69.50 | 23.20 | 486.17 | 23.88 | 4.33 | 23.88 |
October | 289.17 | 22.34 | 247.00 | 22.97 | 23.67 | 22.89 |
November | 331.50 | 22.58 | 197.83 | 23.07 | 7.50 | 23.04 |
December | 510.17 | 22.48 | 178.17 | 22.58 | 67.67 | 22.44 |
Annual Sum or Average | 3653.33 | 22.73 | 3897.83 | 23.29 | 702.67 | 23.29 |
Minimum of Months | 69.50 | 22.34 | 100.67 | 22.58 | 4.33 | 22.44 |
Maximum of Months | 510.17 | 23.89 | 669.17 | 23.92 | 193.83 | 23.92 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 364.17 | 23.24 | 4.33 | 23.25 | 0.00 | 23.25 |
February | 397.33 | 23.06 | 0.67 | 23.06 | 0.00 | 23.06 |
March | 487.83 | 23.14 | 3.00 | 23.14 | 0.00 | 23.14 |
April | 480.50 | 23.04 | 31.33 | 23.10 | 0.00 | 23.10 |
May | 254.83 | 23.35 | 146.83 | 23.58 | 4.33 | 23.59 |
June | 137.67 | 23.91 | 439.00 | 23.93 | 129.67 | 23.93 |
July | 182.67 | 23.92 | 499.83 | 23.94 | 182.50 | 23.93 |
August | 159.17 | 23.96 | 521.67 | 23.95 | 153.00 | 23.96 |
September | 35.67 | 23.52 | 257.17 | 23.92 | 2.50 | 23.92 |
October | 239.50 | 22.96 | 34.00 | 23.09 | 0.00 | 23.09 |
November | 313.83 | 23.16 | 15.00 | 23.20 | 0.00 | 23.20 |
December | 544.50 | 23.05 | 4.00 | 23.03 | 4.00 | 23.02 |
Annual Sum or Average | 3597.67 | 23.23 | 1956.83 | 23.48 | 476.00 | 23.52 |
Minimum of Months | 35.67 | 22.96 | 0.67 | 23.03 | 0.00 | 23.02 |
Maximum of Months | 544.50 | 23.96 | 521.67 | 23.95 | 182.50 | 23.96 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 723.00 | 21.35 | 105.50 | 21.27 | 105.50 | 21.22 |
February | 650.50 | 21.27 | 192.67 | 21.14 | 192.00 | 21.06 |
March | 721.33 | 21.27 | 115.50 | 21.15 | 115.00 | 21.05 |
April | 710.67 | 21.27 | 110.17 | 21.18 | 110.17 | 21.10 |
May | 701.50 | 21.56 | 8.50 | 21.58 | 3.33 | 21.57 |
June | 553.33 | 21.41 | 76.00 | 21.62 | 4.83 | 21.62 |
July | 583.50 | 21.38 | 88.17 | 21.57 | 28.67 | 21.57 |
August | 568.33 | 21.36 | 83.33 | 21.57 | 9.67 | 21.57 |
September | 602.00 | 21.46 | 35.67 | 21.56 | 0.00 | 21.56 |
October | 693.00 | 21.30 | 104.33 | 21.22 | 92.50 | 21.13 |
November | 684.33 | 21.32 | 88.83 | 21.24 | 87.33 | 21.17 |
December | 734.67 | 21.19 | 302.50 | 21.05 | 302.50 | 20.98 |
Annual Sum or Average | 7926.17 | 21.34 | 1311.17 | 21.32 | 1051.50 | 21.25 |
Minimum of Months | 553.33 | 21.19 | 8.50 | 21.05 | 0.00 | 20.98 |
Maximum of Months | 734.67 | 21.56 | 302.50 | 21.62 | 302.50 | 21.62 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.00 | 262.17 | 20.89 | 262.17 | 20.82 |
February | 672.00 | 20.98 | 319.83 | 20.86 | 319.83 | 20.80 |
March | 720.33 | 21.16 | 185.00 | 21.10 | 170.00 | 20.99 |
April | 705.67 | 21.25 | 133.83 | 21.21 | 123.33 | 21.12 |
May | 646.67 | 21.76 | 45.17 | 21.95 | 5.67 | 21.97 |
June | 474.83 | 21.83 | 161.17 | 22.39 | 38.50 | 22.51 |
July | 524.50 | 21.93 | 168.67 | 22.44 | 74.33 | 22.60 |
August | 529.50 | 21.91 | 136.33 | 22.38 | 46.33 | 22.52 |
September | 569.33 | 21.86 | 61.33 | 22.15 | 1.50 | 22.17 |
October | 708.00 | 21.30 | 111.50 | 21.26 | 98.33 | 21.16 |
November | 719.50 | 21.12 | 173.33 | 21.00 | 173.33 | 20.92 |
December | 744.00 | 20.88 | 468.33 | 20.78 | 468.33 | 20.74 |
Annual Sum or Average | 7758.33 | 21.37 | 2226.67 | 21.42 | 1781.67 | 21.34 |
Minimum of Months | 474.83 | 20.88 | 45.17 | 20.78 | 1.50 | 20.74 |
Maximum of Months | 744.00 | 21.93 | 468.33 | 22.44 | 468.33 | 22.60 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.02 | 172.50 | 20.95 | 172.50 | 20.90 |
February | 672.00 | 21.00 | 188.33 | 20.91 | 188.33 | 20.85 |
March | 744.00 | 21.22 | 46.17 | 21.18 | 46.17 | 21.15 |
April | 720.00 | 21.32 | 13.50 | 21.30 | 13.50 | 21.29 |
May | 743.83 | 21.83 | 0.00 | 21.83 | 0.00 | 21.83 |
June | 700.00 | 22.16 | 31.33 | 22.22 | 24.00 | 22.26 |
July | 725.83 | 22.22 | 63.67 | 22.32 | 59.17 | 22.40 |
August | 730.50 | 22.10 | 32.33 | 22.16 | 25.33 | 22.20 |
September | 719.17 | 22.01 | 0.00 | 22.01 | 0.00 | 22.01 |
October | 744.00 | 21.30 | 35.67 | 21.26 | 35.67 | 21.22 |
November | 720.00 | 21.09 | 77.17 | 21.03 | 77.17 | 20.98 |
December | 744.00 | 20.94 | 288.00 | 20.86 | 288.00 | 20.81 |
Annual Sum or Average | 8707.33 | 21.52 | 948.67 | 21.46 | 929.83 | 21.42 |
Minimum of Months | 672.00 | 20.94 | 0.00 | 20.86 | 0.00 | 20.81 |
Maximum of Months | 744.00 | 22.22 | 288.00 | 22.32 | 288.00 | 22.40 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 743.83 | 21.44 | 105.33 | 21.35 | 105.33 | 21.29 |
February | 664.33 | 21.36 | 205.83 | 21.21 | 205.83 | 21.12 |
March | 723.17 | 21.35 | 111.00 | 21.21 | 111.00 | 21.11 |
April | 703.83 | 21.35 | 102.50 | 21.25 | 102.00 | 21.18 |
May | 689.83 | 21.60 | 4.50 | 21.59 | 4.33 | 21.59 |
June | 520.33 | 21.26 | 62.83 | 21.48 | 1.00 | 21.48 |
July | 544.33 | 21.27 | 103.17 | 21.55 | 19.17 | 21.56 |
August | 535.17 | 21.26 | 103.83 | 21.58 | 1.83 | 21.58 |
September | 581.50 | 21.41 | 26.67 | 21.50 | 0.00 | 21.50 |
October | 699.67 | 21.35 | 93.50 | 21.24 | 91.50 | 21.15 |
November | 714.83 | 21.41 | 99.50 | 21.32 | 99.50 | 21.24 |
December | 744.00 | 21.23 | 308.17 | 21.09 | 308.17 | 21.02 |
Annual Sum or Average | 7864.83 | 21.36 | 1326.83 | 21.34 | 1049.67 | 21.27 |
Minimum of Months | 520.33 | 21.23 | 4.50 | 21.09 | 0.00 | 21.02 |
Maximum of Months | 744.00 | 21.60 | 308.17 | 21.59 | 308.17 | 21.59 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.96 | 272.33 | 20.86 | 272.33 | 20.80 |
February | 672.00 | 21.00 | 312.33 | 20.88 | 312.33 | 20.81 |
March | 743.33 | 21.32 | 149.17 | 21.18 | 149.17 | 21.08 |
April | 714.17 | 21.38 | 118.83 | 21.27 | 117.33 | 21.19 |
May | 683.17 | 21.92 | 16.33 | 21.98 | 6.17 | 21.98 |
June | 440.83 | 21.95 | 198.17 | 22.78 | 57.67 | 23.03 |
July | 464.17 | 21.95 | 242.00 | 22.74 | 82.17 | 22.96 |
August | 462.83 | 21.89 | 175.50 | 22.61 | 53.50 | 22.85 |
September | 567.33 | 21.92 | 40.00 | 22.13 | 1.17 | 22.14 |
October | 741.00 | 21.44 | 97.67 | 21.32 | 96.83 | 21.22 |
November | 719.83 | 21.07 | 194.50 | 20.95 | 194.50 | 20.88 |
December | 744.00 | 20.83 | 478.50 | 20.76 | 478.50 | 20.72 |
Annual Sum or Average | 7696.67 | 21.41 | 2295.33 | 21.48 | 1821.67 | 21.42 |
Minimum of Months | 440.83 | 20.83 | 16.33 | 20.76 | 1.17 | 20.72 |
Maximum of Months | 744.00 | 21.95 | 478.50 | 22.78 | 478.50 | 23.03 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.62 | 23.50 | 21.60 | 23.50 | 21.58 |
February | 672.00 | 21.56 | 55.50 | 21.52 | 55.50 | 21.48 |
March | 744.00 | 21.85 | 0.00 | 21.85 | 0.00 | 21.85 |
April | 720.00 | 21.69 | 1.17 | 21.69 | 1.17 | 21.69 |
May | 744.00 | 22.68 | 0.00 | 22.68 | 0.00 | 22.68 |
June | 460.50 | 23.69 | 134.83 | 23.72 | 89.00 | 23.73 |
July | 412.17 | 23.80 | 250.00 | 23.80 | 157.50 | 23.79 |
August | 357.33 | 23.80 | 186.00 | 23.81 | 110.17 | 23.81 |
September | 533.17 | 23.56 | 2.67 | 23.56 | 0.00 | 23.56 |
October | 744.00 | 22.49 | 21.50 | 22.45 | 21.50 | 22.41 |
November | 720.00 | 21.77 | 15.67 | 21.76 | 15.67 | 21.74 |
December | 744.00 | 21.32 | 158.00 | 21.26 | 158.00 | 21.22 |
Annual Sum or Average | 7595.17 | 22.30 | 848.83 | 22.36 | 632.00 | 22.38 |
Minimum of Months | 357.33 | 21.32 | 0.00 | 21.26 | 0.00 | 21.22 |
Maximum of Months | 744.00 | 23.80 | 250.00 | 23.81 | 158.00 | 23.81 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 720.50 | 21.26 | 200.00 | 21.16 | 200.00 | 21.09 |
February | 648.17 | 21.19 | 255.17 | 21.07 | 253.00 | 21.00 |
March | 714.00 | 21.19 | 215.67 | 21.05 | 214.17 | 20.97 |
April | 700.50 | 21.18 | 173.33 | 21.04 | 173.33 | 20.95 |
May | 679.50 | 21.49 | 30.00 | 21.53 | 14.67 | 21.52 |
June | 528.17 | 21.34 | 123.50 | 21.65 | 18.33 | 21.64 |
July | 566.33 | 21.34 | 148.50 | 21.61 | 54.00 | 21.60 |
August | 555.67 | 21.32 | 160.67 | 21.63 | 46.00 | 21.62 |
September | 590.83 | 21.41 | 56.50 | 21.56 | 1.67 | 21.56 |
October | 688.17 | 21.23 | 146.33 | 21.15 | 128.50 | 21.06 |
November | 679.00 | 21.23 | 171.50 | 21.13 | 167.33 | 21.05 |
December | 728.50 | 21.07 | 413.83 | 20.95 | 413.83 | 20.89 |
Annual Sum or Average | 7799.33 | 21.27 | 2095.00 | 21.26 | 1684.83 | 21.18 |
Minimum of Months | 528.17 | 21.07 | 30.00 | 20.95 | 1.67 | 20.89 |
Maximum of Months | 728.50 | 21.49 | 413.83 | 21.65 | 413.83 | 21.64 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.89 | 402.00 | 20.78 | 402.00 | 20.73 |
February | 672.00 | 20.90 | 380.83 | 20.79 | 380.83 | 20.74 |
March | 721.17 | 21.11 | 322.00 | 21.05 | 308.00 | 20.96 |
April | 701.83 | 21.20 | 207.33 | 21.13 | 197.33 | 21.04 |
May | 624.50 | 21.71 | 79.17 | 22.00 | 20.50 | 22.03 |
June | 452.83 | 21.81 | 198.17 | 22.45 | 43.50 | 22.57 |
July | 516.00 | 21.93 | 221.50 | 22.46 | 96.17 | 22.60 |
August | 514.50 | 21.89 | 186.00 | 22.39 | 71.00 | 22.52 |
September | 560.00 | 21.82 | 78.00 | 22.17 | 7.33 | 22.20 |
October | 700.67 | 21.20 | 183.67 | 21.17 | 164.50 | 21.06 |
November | 718.83 | 21.03 | 288.67 | 20.90 | 288.67 | 20.83 |
December | 744.00 | 20.78 | 593.50 | 20.71 | 593.50 | 20.69 |
Annual Sum or Average | 7670.33 | 21.30 | 3140.83 | 21.35 | 2573.33 | 21.27 |
Minimum of Months | 452.83 | 20.78 | 78.00 | 20.71 | 7.33 | 20.69 |
Maximum of Months | 744.00 | 21.93 | 593.50 | 22.46 | 593.50 | 22.60 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 628.83 | 21.29 | 130.17 | 21.44 | 62.33 | 21.38 |
February | 579.33 | 21.23 | 169.83 | 21.25 | 129.50 | 21.16 |
March | 673.83 | 21.23 | 109.00 | 21.16 | 93.67 | 21.06 |
April | 684.67 | 21.26 | 105.33 | 21.17 | 105.33 | 21.10 |
May | 695.00 | 21.54 | 9.33 | 21.54 | 9.33 | 21.53 |
June | 599.17 | 21.42 | 26.17 | 21.48 | 9.00 | 21.48 |
July | 611.50 | 21.40 | 79.83 | 21.52 | 43.50 | 21.52 |
August | 592.00 | 21.36 | 103.83 | 21.61 | 16.83 | 21.60 |
September | 590.50 | 21.42 | 69.00 | 21.62 | 0.00 | 21.62 |
October | 634.00 | 21.20 | 158.00 | 21.31 | 88.67 | 21.22 |
November | 605.33 | 21.29 | 133.00 | 21.44 | 64.67 | 21.38 |
December | 669.67 | 21.30 | 195.33 | 21.30 | 159.17 | 21.23 |
Annual Sum or Average | 7563.83 | 21.33 | 1288.83 | 21.39 | 782.00 | 21.34 |
Minimum of Months | 579.33 | 21.20 | 9.33 | 21.16 | 0.00 | 21.06 |
Maximum of Months | 695.00 | 21.54 | 195.33 | 21.62 | 159.17 | 21.62 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 353.33 | 23.52 | 27.67 | 23.55 | 0.00 | 23.55 |
February | 341.67 | 23.53 | 22.50 | 23.56 | 0.00 | 23.56 |
March | 223.83 | 23.52 | 32.00 | 23.58 | 0.00 | 23.58 |
April | 149.83 | 23.56 | 153.00 | 23.78 | 0.00 | 23.78 |
May | 18.17 | 23.66 | 464.50 | 23.98 | 2.83 | 23.98 |
June | 131.83 | 24.00 | 681.33 | 24.00 | 131.83 | 24.00 |
July | 189.00 | 24.00 | 724.83 | 24.00 | 189.00 | 24.00 |
August | 158.67 | 24.00 | 703.00 | 24.00 | 158.67 | 24.00 |
September | 7.83 | 23.73 | 442.67 | 23.99 | 2.83 | 23.99 |
October | 141.17 | 23.44 | 113.67 | 23.69 | 0.00 | 23.69 |
November | 231.67 | 23.45 | 39.33 | 23.52 | 0.00 | 23.52 |
December | 474.83 | 23.45 | 0.00 | 23.45 | 0.00 | 23.45 |
Annual Sum or Average | 2421.83 | 23.60 | 3404.50 | 23.83 | 485.17 | 23.84 |
Minimum of Months | 7.83 | 23.44 | 0.00 | 23.45 | 0.00 | 23.45 |
Maximum of Months | 474.83 | 24.00 | 724.83 | 24.00 | 189.00 | 24.00 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 165.17 | 23.62 | 133.17 | 23.79 | 0.00 | 23.79 |
February | 173.50 | 23.58 | 78.33 | 23.71 | 0.00 | 23.71 |
March | 87.67 | 23.62 | 108.00 | 23.83 | 0.00 | 23.83 |
April | 31.67 | 23.52 | 265.00 | 23.94 | 0.00 | 23.94 |
May | 3.00 | 23.94 | 547.83 | 24.00 | 2.50 | 24.00 |
June | 127.33 | 24.00 | 705.83 | 24.00 | 127.33 | 24.00 |
July | 184.00 | 24.00 | 732.33 | 24.00 | 184.00 | 24.00 |
August | 151.17 | 24.00 | 729.33 | 24.00 | 151.17 | 24.00 |
September | 2.83 | 23.99 | 541.33 | 24.00 | 2.83 | 24.00 |
October | 48.33 | 23.34 | 228.67 | 23.88 | 0.00 | 23.88 |
November | 94.67 | 23.50 | 152.00 | 23.80 | 0.00 | 23.80 |
December | 288.50 | 23.51 | 1.33 | 23.51 | 0.00 | 23.51 |
Annual Sum or Average | 1357.83 | 23.70 | 4223.17 | 23.92 | 467.83 | 23.93 |
Minimum of Months | 2.83 | 23.34 | 1.33 | 23.51 | 0.00 | 23.51 |
Maximum of Months | 288.50 | 24.00 | 732.33 | 24.00 | 184.00 | 24.00 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 495.50 | 23.97 | 712.00 | 23.96 | 489.83 | 23.97 |
February | 443.00 | 23.96 | 629.83 | 23.95 | 434.17 | 23.96 |
March | 501.00 | 23.98 | 727.83 | 23.96 | 498.50 | 23.97 |
April | 495.17 | 23.99 | 709.00 | 23.97 | 495.17 | 23.98 |
May | 539.17 | 23.99 | 744.00 | 23.99 | 539.17 | 23.99 |
June | 560.67 | 24.00 | 720.00 | 24.00 | 560.67 | 24.00 |
July | 603.50 | 24.00 | 744.00 | 24.00 | 603.50 | 24.00 |
August | 606.83 | 24.00 | 744.00 | 24.00 | 606.83 | 24.00 |
September | 522.67 | 23.99 | 720.00 | 23.99 | 522.67 | 23.99 |
October | 504.17 | 23.99 | 737.00 | 23.97 | 503.67 | 23.98 |
November | 487.00 | 23.98 | 700.33 | 23.96 | 483.67 | 23.97 |
December | 475.00 | 23.91 | 678.83 | 23.94 | 448.17 | 23.95 |
Annual Sum or Average | 6233.67 | 23.98 | 8566.83 | 23.97 | 6186.00 | 23.98 |
Minimum of Months | 443.00 | 23.91 | 629.83 | 23.94 | 434.17 | 23.95 |
Maximum of Months | 606.83 | 24.00 | 744.00 | 24.00 | 606.83 | 24.00 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.43 | 62.50 | 21.40 | 62.50 | 21.37 |
February | 672.00 | 21.46 | 98.00 | 21.40 | 98.00 | 21.35 |
March | 744.00 | 21.75 | 29.83 | 21.72 | 29.83 | 21.70 |
April | 720.00 | 21.68 | 9.67 | 21.67 | 9.67 | 21.66 |
May | 724.33 | 22.68 | 0.00 | 22.68 | 0.00 | 22.68 |
June | 234.00 | 23.46 | 173.33 | 23.63 | 37.17 | 23.63 |
July | 255.33 | 23.52 | 292.00 | 23.66 | 110.67 | 23.64 |
August | 255.00 | 23.46 | 245.67 | 23.64 | 74.17 | 23.63 |
September | 463.33 | 23.17 | 18.17 | 23.20 | 0.00 | 23.20 |
October | 734.67 | 22.19 | 36.33 | 22.14 | 36.33 | 22.09 |
November | 720.00 | 21.63 | 39.50 | 21.60 | 39.50 | 21.57 |
December | 744.00 | 21.28 | 196.50 | 21.22 | 196.50 | 21.18 |
Annual Sum or Average | 7010.67 | 22.04 | 1201.50 | 22.14 | 694.33 | 22.11 |
Minimum of Months | 234.00 | 21.28 | 0.00 | 21.22 | 0.00 | 21.18 |
Maximum of Months | 744.00 | 23.52 | 292.00 | 23.66 | 196.50 | 23.64 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.83755 | 23.94456 | 0.17604 | 5.74697 |
February | 672.00000 | 23.67259 | 22.64593 | 0.12138 | 5.44803 |
March | 744.00000 | 23.42735 | 22.18972 | 0.05513 | 5.23571 |
April | 720.00000 | 23.49589 | 26.23129 | 0.09835 | 5.38892 |
May | 744.00000 | 23.44900 | 30.22590 | -0.8587 | 20.81977 |
June | 720.00000 | 23.67342 | 37.78551 | -0.7197 | 16.20074 |
July | 744.00000 | 23.74996 | 40.11293 | -0.6745 | 14.85837 |
August | 744.00000 | 23.89520 | 39.07772 | -0.6143 | 13.14128 |
September | 720.00000 | 23.98147 | 27.91527 | -0.6423 | 13.76756 |
October | 744.00000 | 23.98852 | 23.22787 | 0.23360 | 6.18962 |
November | 720.00000 | 23.98667 | 24.22409 | 0.23779 | 6.22343 |
December | 744.00000 | 23.97268 | 18.13957 | 0.18579 | 5.75720 |
Annual Sum or Average | 8760.00000 | 23.76133 | 28.00887 | -0.2022 | 9.92926 |
Minimum of Months | 672.00000 | 23.42735 | 18.13957 | -0.8587 | 5.23571 |
Maximum of Months | 744.00000 | 23.98852 | 40.11293 | 0.23779 | 20.81977 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.07914 | 24.86608 | -0.1681 | 8.75900 |
February | 672.00000 | 22.06185 | 23.04822 | -0.2077 | 9.34365 |
March | 744.00000 | 22.07796 | 22.43005 | -0.2072 | 8.73907 |
April | 720.00000 | 21.73238 | 27.30489 | -0.2827 | 8.60530 |
May | 744.00000 | 22.28149 | 30.66463 | -1.1120 | 33.03202 |
June | 720.00000 | 23.37298 | 37.09090 | -0.6307 | 14.76157 |
July | 744.00000 | 23.40939 | 39.65065 | -0.5980 | 13.87941 |
August | 744.00000 | 23.42795 | 39.08516 | -0.5762 | 13.54526 |
September | 720.00000 | 23.30021 | 28.33897 | -0.6907 | 17.86712 |
October | 744.00000 | 22.37706 | 24.82526 | -0.0832 | 8.38867 |
November | 720.00000 | 22.18190 | 26.07830 | -0.1301 | 8.57093 |
December | 744.00000 | 21.83706 | 19.32204 | -0.3035 | 10.12343 |
Annual Sum or Average | 8760.00000 | 22.51383 | 28.59151 | -0.4174 | 13.00340 |
Minimum of Months | 672.00000 | 21.73238 | 19.32204 | -1.1120 | 8.38867 |
Maximum of Months | 744.00000 | 23.42795 | 39.65065 | -0.0832 | 33.03202 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.08107 | 25.85571 | 0.02668 | 5.56630 |
February | 672.00000 | 22.89315 | 24.32829 | -0.0325 | 5.93711 |
March | 744.00000 | 23.01102 | 23.53885 | -0.0047 | 5.67443 |
April | 720.00000 | 22.94197 | 27.78124 | 0.00265 | 5.72991 |
May | 744.00000 | 23.51000 | 30.82686 | -0.7721 | 18.16641 |
June | 720.00000 | 23.89781 | 37.56762 | -0.5531 | 11.59575 |
July | 744.00000 | 23.91036 | 40.10184 | -0.5327 | 11.11095 |
August | 744.00000 | 23.91191 | 39.70845 | -0.5336 | 11.15963 |
September | 720.00000 | 23.88172 | 29.30599 | -0.6229 | 13.43511 |
October | 744.00000 | 23.34718 | 25.72500 | 0.10137 | 5.93765 |
November | 720.00000 | 23.14216 | 27.05077 | 0.05168 | 5.69038 |
December | 744.00000 | 22.70919 | 20.80139 | -0.1034 | 6.24623 |
Annual Sum or Average | 8760.00000 | 23.35567 | 29.41277 | -0.2491 | 8.87530 |
Minimum of Months | 672.00000 | 22.70919 | 20.80139 | -0.7721 | 5.56630 |
Maximum of Months | 744.00000 | 23.91191 | 40.10184 | 0.10137 | 18.16641 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.56691 | 20.63332 | 0.71406 | 17.46095 |
February | 672.00000 | 23.54853 | 18.99151 | 0.69219 | 16.90876 |
March | 744.00000 | 23.57085 | 18.14526 | 0.71158 | 17.34825 |
April | 720.00000 | 23.58984 | 22.25083 | 0.74256 | 18.34883 |
May | 744.00000 | 23.64942 | 25.98706 | 0.15726 | 8.79591 |
June | 720.00000 | 23.68685 | 33.89791 | 0.28098 | 9.82598 |
July | 744.00000 | 23.69403 | 36.50484 | 0.29696 | 9.88380 |
August | 744.00000 | 23.67315 | 36.05171 | 0.28670 | 9.80366 |
September | 720.00000 | 23.67182 | 25.41405 | 0.19278 | 8.87797 |
October | 744.00000 | 23.58419 | 20.76542 | 0.74459 | 18.30937 |
November | 720.00000 | 23.56466 | 21.84424 | 0.72979 | 17.95170 |
December | 744.00000 | 23.52443 | 15.44803 | 0.65092 | 15.79966 |
Annual Sum or Average | 8760.00000 | 23.61070 | 24.69474 | 0.51559 | 14.09049 |
Minimum of Months | 672.00000 | 23.52443 | 15.44803 | 0.15726 | 8.79591 |
Maximum of Months | 744.00000 | 23.69403 | 36.50484 | 0.74459 | 18.34883 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.29553 | 28.70629 | 0.19094 | 7.69505 |
February | 672.00000 | 23.13270 | 27.20571 | 0.12241 | 8.07057 |
March | 744.00000 | 23.07685 | 26.62732 | 0.10290 | 7.42345 |
April | 720.00000 | 22.88549 | 31.24411 | 0.05665 | 6.94690 |
May | 744.00000 | 23.51833 | 34.26163 | -0.6366 | 14.52726 |
June | 720.00000 | 23.86420 | 40.82091 | -0.3850 | 8.44732 |
July | 744.00000 | 23.88004 | 43.29928 | -0.3566 | 8.04289 |
August | 744.00000 | 23.90174 | 42.56483 | -0.3293 | 7.74818 |
September | 720.00000 | 23.87691 | 32.19549 | -0.4108 | 9.54720 |
October | 744.00000 | 23.32995 | 28.70848 | 0.21333 | 8.31832 |
November | 720.00000 | 23.30751 | 29.87758 | 0.20829 | 7.97283 |
December | 744.00000 | 22.94400 | 23.79432 | 0.03694 | 7.80302 |
Annual Sum or Average | 8760.00000 | 23.41939 | 32.47323 | -0.1004 | 8.55262 |
Minimum of Months | 672.00000 | 22.88549 | 23.79432 | -0.6366 | 6.94690 |
Maximum of Months | 744.00000 | 23.90174 | 43.29928 | 0.21333 | 14.52726 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.60542 | 27.90032 | 0.19283 | 6.25141 |
February | 672.00000 | 23.42955 | 26.47245 | 0.13331 | 6.23130 |
March | 744.00000 | 23.42971 | 25.67243 | 0.13332 | 5.95184 |
April | 720.00000 | 23.34531 | 29.93409 | 0.13411 | 6.00649 |
May | 744.00000 | 23.70968 | 32.87149 | -0.6476 | 14.21918 |
June | 720.00000 | 23.90260 | 39.72383 | -0.4876 | 10.13043 |
July | 744.00000 | 23.92231 | 42.19391 | -0.4616 | 9.61450 |
August | 744.00000 | 23.94160 | 41.69476 | -0.4545 | 9.46197 |
September | 720.00000 | 23.94742 | 31.30660 | -0.5304 | 11.07480 |
October | 744.00000 | 23.64318 | 27.71632 | 0.21741 | 6.63282 |
November | 720.00000 | 23.61346 | 29.02013 | 0.20697 | 6.39549 |
December | 744.00000 | 23.30030 | 23.05561 | 0.07375 | 6.10527 |
Annual Sum or Average | 8760.00000 | 23.65044 | 31.49320 | -0.1258 | 8.18641 |
Minimum of Months | 672.00000 | 23.30030 | 23.05561 | -0.6476 | 5.95184 |
Maximum of Months | 744.00000 | 23.94742 | 42.19391 | 0.21741 | 14.21918 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.40519 | 38.48686 | -0.3760 | 9.32764 |
February | 672.00000 | 21.33192 | 36.87075 | -0.4118 | 10.23448 |
March | 744.00000 | 21.33216 | 35.90402 | -0.3819 | 9.49734 |
April | 720.00000 | 21.30016 | 40.14236 | -0.3748 | 9.16590 |
May | 744.00000 | 21.66489 | 42.09447 | -1.3028 | 41.71406 |
June | 720.00000 | 21.81138 | 46.21525 | -1.0907 | 32.10457 |
July | 744.00000 | 21.78179 | 47.61542 | -1.1050 | 32.58272 |
August | 744.00000 | 21.79533 | 47.73476 | -1.0980 | 32.48408 |
September | 720.00000 | 21.74995 | 39.76218 | -1.1942 | 36.94230 |
October | 744.00000 | 21.43574 | 38.54119 | -0.3056 | 8.77021 |
November | 720.00000 | 21.41606 | 40.05284 | -0.3485 | 9.04590 |
December | 744.00000 | 21.21200 | 33.26439 | -0.4965 | 11.69016 |
Annual Sum or Average | 8760.00000 | 21.52071 | 40.57653 | -0.7091 | 20.36268 |
Minimum of Months | 672.00000 | 21.21200 | 33.26439 | -1.3028 | 8.77021 |
Maximum of Months | 744.00000 | 21.81138 | 47.73476 | -0.3056 | 41.71406 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.00493 | 39.29342 | -0.5299 | 11.60495 |
February | 672.00000 | 20.98354 | 37.47297 | -0.5473 | 12.26791 |
March | 744.00000 | 21.30167 | 36.02484 | -0.4328 | 10.58023 |
April | 720.00000 | 21.34501 | 40.15427 | -0.3878 | 9.64172 |
May | 744.00000 | 22.08084 | 41.22944 | -1.2024 | 37.99621 |
June | 720.00000 | 22.44556 | 45.11392 | -0.9179 | 26.04851 |
July | 744.00000 | 22.44157 | 46.86737 | -0.9263 | 26.40360 |
August | 744.00000 | 22.41193 | 47.00319 | -0.9500 | 27.43765 |
September | 720.00000 | 22.32773 | 38.83702 | -1.0815 | 32.77527 |
October | 744.00000 | 21.46384 | 38.29845 | -0.3523 | 9.39191 |
November | 720.00000 | 21.11973 | 40.56028 | -0.4772 | 10.65956 |
December | 744.00000 | 20.88137 | 33.86825 | -0.6260 | 14.08797 |
Annual Sum or Average | 8760.00000 | 21.65439 | 40.40915 | -0.7037 | 19.12282 |
Minimum of Months | 672.00000 | 20.88137 | 33.86825 | -1.2024 | 9.39191 |
Maximum of Months | 744.00000 | 22.44556 | 47.00319 | -0.3523 | 37.99621 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.01580 | 36.38249 | -0.5164 | 10.77331 |
February | 672.00000 | 20.99520 | 34.70526 | -0.5341 | 11.20877 |
March | 744.00000 | 21.21535 | 32.90865 | -0.4631 | 9.64882 |
April | 720.00000 | 21.32077 | 37.21286 | -0.3984 | 8.60191 |
May | 744.00000 | 21.83463 | 38.72984 | -1.3462 | 43.29339 |
June | 720.00000 | 22.21294 | 44.01469 | -1.1289 | 33.17660 |
July | 744.00000 | 22.26827 | 45.71857 | -1.0989 | 31.95220 |
August | 744.00000 | 22.13972 | 45.96329 | -1.1599 | 34.51852 |
September | 720.00000 | 22.00970 | 36.60861 | -1.2878 | 40.49193 |
October | 744.00000 | 21.30434 | 35.49024 | -0.4122 | 8.83025 |
November | 720.00000 | 21.09275 | 37.75826 | -0.4794 | 9.97747 |
December | 744.00000 | 20.94424 | 30.82327 | -0.5772 | 12.29964 |
Annual Sum or Average | 8760.00000 | 21.53245 | 38.04407 | -0.7851 | 21.29338 |
Minimum of Months | 672.00000 | 20.94424 | 30.82327 | -1.3462 | 8.60191 |
Maximum of Months | 744.00000 | 22.26827 | 45.96329 | -0.3984 | 43.29339 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.43975 | 38.56572 | -0.3708 | 9.23470 |
February | 672.00000 | 21.37860 | 36.88994 | -0.3996 | 10.16631 |
March | 744.00000 | 21.40256 | 35.94887 | -0.3591 | 9.33247 |
April | 720.00000 | 21.39296 | 40.04045 | -0.3432 | 8.94192 |
May | 744.00000 | 21.72233 | 41.87625 | -1.2709 | 40.23147 |
June | 720.00000 | 21.81440 | 46.28843 | -1.0722 | 31.22464 |
July | 744.00000 | 21.80697 | 47.49176 | -1.0706 | 31.18803 |
August | 744.00000 | 21.80142 | 47.57997 | -1.0712 | 31.35272 |
September | 720.00000 | 21.77822 | 39.75547 | -1.1728 | 35.97278 |
October | 744.00000 | 21.46735 | 38.55529 | -0.2993 | 8.74868 |
November | 720.00000 | 21.42755 | 40.12044 | -0.3497 | 9.03230 |
December | 744.00000 | 21.22815 | 33.31454 | -0.4931 | 11.55862 |
Annual Sum or Average | 8760.00000 | 21.55594 | 40.55443 | -0.6913 | 19.81056 |
Minimum of Months | 672.00000 | 21.22815 | 33.31454 | -1.2709 | 8.74868 |
Maximum of Months | 744.00000 | 21.81440 | 47.57997 | -0.2993 | 40.23147 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.96333 | 39.37680 | -0.5409 | 11.69103 |
February | 672.00000 | 21.00428 | 37.40914 | -0.5401 | 12.17261 |
March | 744.00000 | 21.31953 | 35.91150 | -0.4208 | 9.91173 |
April | 720.00000 | 21.40100 | 39.98883 | -0.3644 | 9.14738 |
May | 744.00000 | 22.08151 | 41.13568 | -1.1871 | 36.76666 |
June | 720.00000 | 22.64405 | 45.15334 | -0.8407 | 25.25042 |
July | 744.00000 | 22.62419 | 46.51214 | -0.8451 | 24.77627 |
August | 744.00000 | 22.57850 | 46.54243 | -0.8751 | 26.05801 |
September | 720.00000 | 22.34621 | 38.80151 | -1.0615 | 31.73458 |
October | 744.00000 | 21.45229 | 38.27726 | -0.3557 | 9.05069 |
November | 720.00000 | 21.06585 | 40.68843 | -0.4920 | 10.83230 |
December | 744.00000 | 20.83388 | 33.90617 | -0.6360 | 14.20524 |
Annual Sum or Average | 8760.00000 | 21.69667 | 40.32312 | -0.6810 | 18.50965 |
Minimum of Months | 672.00000 | 20.83388 | 33.90617 | -1.1871 | 9.05069 |
Maximum of Months | 744.00000 | 22.64405 | 46.54243 | -0.3557 | 36.76666 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.32407 | 39.25684 | -0.4298 | 10.45561 |
February | 672.00000 | 21.26990 | 37.58213 | -0.4593 | 11.35188 |
March | 744.00000 | 21.27276 | 36.65221 | -0.4213 | 10.47387 |
April | 720.00000 | 21.23616 | 41.02434 | -0.4099 | 10.09631 |
May | 744.00000 | 21.64571 | 42.67320 | -1.3228 | 42.96081 |
June | 720.00000 | 21.82064 | 46.61454 | -1.0832 | 32.22529 |
July | 744.00000 | 21.78444 | 48.13365 | -1.1036 | 32.86900 |
August | 744.00000 | 21.79961 | 48.50953 | -1.0945 | 32.78946 |
September | 720.00000 | 21.73350 | 40.11414 | -1.2153 | 38.29568 |
October | 744.00000 | 21.38463 | 39.26393 | -0.3459 | 9.67410 |
November | 720.00000 | 21.34965 | 40.86686 | -0.3945 | 10.05650 |
December | 744.00000 | 21.12099 | 33.88110 | -0.5557 | 13.22688 |
Annual Sum or Average | 8760.00000 | 21.47960 | 41.23392 | -0.7382 | 21.27125 |
Minimum of Months | 672.00000 | 21.12099 | 33.88110 | -1.3228 | 9.67410 |
Maximum of Months | 744.00000 | 21.82064 | 48.50953 | -0.3459 | 42.96081 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.88608 | 40.23615 | -0.5961 | 13.26466 |
February | 672.00000 | 20.90337 | 38.27686 | -0.6028 | 13.70258 |
March | 744.00000 | 21.25123 | 36.80042 | -0.4721 | 11.80825 |
April | 720.00000 | 21.30528 | 41.04884 | -0.4178 | 10.67857 |
May | 744.00000 | 22.10735 | 41.75153 | -1.2044 | 38.86647 |
June | 720.00000 | 22.45555 | 45.34147 | -0.9046 | 26.17025 |
July | 744.00000 | 22.43236 | 47.16692 | -0.9235 | 26.85386 |
August | 744.00000 | 22.40922 | 47.62181 | -0.9438 | 27.91497 |
September | 720.00000 | 22.30710 | 39.22680 | -1.0996 | 34.19945 |
October | 744.00000 | 21.41788 | 39.15356 | -0.3937 | 10.50551 |
November | 720.00000 | 21.03078 | 41.48918 | -0.5329 | 11.98875 |
December | 744.00000 | 20.78344 | 34.57276 | -0.6898 | 15.94072 |
Annual Sum or Average | 8760.00000 | 21.61142 | 41.07216 | -0.7327 | 20.20430 |
Minimum of Months | 672.00000 | 20.78344 | 34.57276 | -1.2044 | 10.50551 |
Maximum of Months | 744.00000 | 22.45555 | 47.62181 | -0.3937 | 38.86647 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.61464 | 39.51158 | -0.2478 | 8.58326 |
February | 672.00000 | 21.51980 | 38.14417 | -0.3038 | 9.53000 |
March | 744.00000 | 21.42532 | 36.79766 | -0.3360 | 9.32557 |
April | 720.00000 | 21.36429 | 40.63719 | -0.3612 | 9.17951 |
May | 744.00000 | 21.66103 | 42.41282 | -1.3443 | 43.84693 |
June | 720.00000 | 21.74353 | 47.08913 | -1.1859 | 36.24111 |
July | 744.00000 | 21.74453 | 48.35090 | -1.1712 | 35.59817 |
August | 744.00000 | 21.75560 | 48.46972 | -1.1470 | 34.78866 |
September | 720.00000 | 21.76005 | 40.12011 | -1.2019 | 37.67797 |
October | 744.00000 | 21.52612 | 39.20821 | -0.2568 | 8.87114 |
November | 720.00000 | 21.62151 | 40.94452 | -0.2318 | 8.50028 |
December | 744.00000 | 21.50627 | 34.46646 | -0.3513 | 9.94562 |
Annual Sum or Average | 8760.00000 | 21.60404 | 41.36302 | -0.6806 | 21.08095 |
Minimum of Months | 672.00000 | 21.36429 | 34.46646 | -1.3443 | 8.50028 |
Maximum of Months | 744.00000 | 21.76005 | 48.46972 | -0.2318 | 43.84693 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.76283 | 28.78985 | 0.22437 | 6.33928 |
February | 672.00000 | 23.75050 | 27.23022 | 0.20798 | 6.24445 |
March | 744.00000 | 23.84353 | 25.84992 | 0.25438 | 6.52553 |
April | 720.00000 | 23.88983 | 29.68932 | 0.30135 | 7.10547 |
May | 744.00000 | 23.98421 | 32.53006 | -0.4568 | 9.52656 |
June | 720.00000 | 23.99670 | 39.66037 | -0.3203 | 7.26081 |
July | 744.00000 | 23.99638 | 42.21548 | -0.3037 | 7.05683 |
August | 744.00000 | 23.99603 | 41.84724 | -0.3189 | 7.24497 |
September | 720.00000 | 23.99095 | 31.77993 | -0.4277 | 8.99624 |
October | 744.00000 | 23.87439 | 28.18614 | 0.29583 | 7.06174 |
November | 720.00000 | 23.80672 | 29.75645 | 0.25661 | 6.62817 |
December | 744.00000 | 23.64913 | 24.02581 | 0.14699 | 6.01876 |
Annual Sum or Average | 8760.00000 | 23.87902 | 31.82413 | -0.0131 | 7.17137 |
Minimum of Months | 672.00000 | 23.64913 | 24.02581 | -0.4568 | 6.01876 |
Maximum of Months | 744.00000 | 23.99670 | 42.21548 | 0.30135 | 9.52656 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.88835 | 27.83695 | 0.29470 | 6.97941 |
February | 672.00000 | 23.87880 | 26.28215 | 0.27930 | 6.81843 |
March | 744.00000 | 23.93693 | 24.99306 | 0.31570 | 7.16477 |
April | 720.00000 | 23.96192 | 28.84260 | 0.35854 | 7.81340 |
May | 744.00000 | 23.99456 | 31.94495 | -0.4038 | 8.53535 |
June | 720.00000 | 23.99707 | 39.27288 | -0.2815 | 6.78002 |
July | 744.00000 | 23.99674 | 41.83260 | -0.2654 | 6.60971 |
August | 744.00000 | 23.99666 | 41.44659 | -0.2803 | 6.76475 |
September | 720.00000 | 23.99510 | 31.31349 | -0.3852 | 8.25578 |
October | 744.00000 | 23.94002 | 27.43708 | 0.34653 | 7.64666 |
November | 720.00000 | 23.90491 | 28.84548 | 0.31921 | 7.26830 |
December | 744.00000 | 23.80126 | 23.08115 | 0.22486 | 6.42474 |
Annual Sum or Average | 8760.00000 | 23.94128 | 31.12295 | 0.04206 | 7.25569 |
Minimum of Months | 672.00000 | 23.80126 | 23.08115 | -0.4038 | 6.42474 |
Maximum of Months | 744.00000 | 23.99707 | 41.83260 | 0.35854 | 8.53535 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.91070 | 26.46025 | 0.95095 | 25.98355 |
February | 672.00000 | 23.89347 | 24.91605 | 0.93320 | 25.41618 |
March | 744.00000 | 23.93415 | 23.96141 | 0.97381 | 26.81121 |
April | 720.00000 | 23.94560 | 27.87310 | 1.00785 | 28.19830 |
May | 744.00000 | 23.98247 | 31.39376 | 0.55184 | 15.28239 |
June | 720.00000 | 23.99616 | 38.98189 | 0.71274 | 19.57168 |
July | 744.00000 | 23.99914 | 41.46181 | 0.72525 | 19.92434 |
August | 744.00000 | 23.99515 | 40.98498 | 0.71476 | 19.43970 |
September | 720.00000 | 23.98923 | 30.91364 | 0.59575 | 16.37519 |
October | 744.00000 | 23.95654 | 26.50904 | 1.00961 | 28.17761 |
November | 720.00000 | 23.92263 | 27.61248 | 0.97520 | 26.89945 |
December | 744.00000 | 23.87158 | 21.69209 | 0.87888 | 23.46941 |
Annual Sum or Average | 8760.00000 | 23.95005 | 30.26150 | 0.83516 | 22.94446 |
Minimum of Months | 672.00000 | 23.87158 | 21.69209 | 0.55184 | 15.28239 |
Maximum of Months | 744.00000 | 23.99914 | 41.46181 | 1.00961 | 28.19830 |
Report: OccupantComfortDataSummaryMonthly
For: STORAGE_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.41336 | 24.60290 | -0.4097 | 8.79676 |
February | 672.00000 | 21.35277 | 22.73402 | -0.4441 | 9.45213 |
March | 744.00000 | 21.62090 | 21.79188 | -0.3759 | 8.37724 |
April | 720.00000 | 21.66651 | 26.18149 | -0.3372 | 7.80053 |
May | 744.00000 | 22.71703 | 28.81783 | -1.0970 | 30.85501 |
June | 720.00000 | 23.74063 | 35.28271 | -0.6935 | 15.27554 |
July | 744.00000 | 23.81417 | 37.64296 | -0.6511 | 14.04836 |
August | 744.00000 | 23.71261 | 37.57720 | -0.6898 | 15.19958 |
September | 720.00000 | 23.41187 | 27.15406 | -0.8650 | 21.43926 |
October | 744.00000 | 22.17620 | 24.01693 | -0.2240 | 6.58571 |
November | 720.00000 | 21.61022 | 25.76333 | -0.3534 | 7.96595 |
December | 744.00000 | 21.29821 | 18.76073 | -0.4852 | 10.21590 |
Annual Sum or Average | 8760.00000 | 22.38378 | 27.55486 | -0.5529 | 13.02886 |
Minimum of Months | 672.00000 | 21.29821 | 18.76073 | -1.0970 | 6.58571 |
Maximum of Months | 744.00000 | 23.81417 | 37.64296 | -0.2240 | 30.85501 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.61807 | 27.60449 | -0.3534 | 7.92893 |
February | 672.00000 | 21.55795 | 25.78120 | -0.3853 | 8.56351 |
March | 744.00000 | 21.84906 | 24.86977 | -0.3150 | 7.68151 |
April | 720.00000 | 21.68806 | 29.43993 | -0.3266 | 7.60569 |
May | 744.00000 | 22.68399 | 32.17660 | -1.1075 | 31.37327 |
June | 720.00000 | 23.76484 | 38.57467 | -0.6834 | 14.99539 |
July | 744.00000 | 23.86113 | 40.84171 | -0.6337 | 13.54755 |
August | 744.00000 | 23.83151 | 40.68245 | -0.6462 | 13.90494 |
September | 720.00000 | 23.64894 | 30.22510 | -0.7818 | 18.36106 |
October | 744.00000 | 22.48822 | 27.01492 | -0.1437 | 6.24691 |
November | 720.00000 | 21.77473 | 28.81667 | -0.3084 | 7.40376 |
December | 744.00000 | 21.31916 | 22.01931 | -0.4680 | 9.81537 |
Annual Sum or Average | 8760.00000 | 22.51262 | 30.69877 | -0.5137 | 12.31838 |
Minimum of Months | 672.00000 | 21.31916 | 22.01931 | -1.1075 | 6.24691 |
Maximum of Months | 744.00000 | 23.86113 | 40.84171 | -0.1437 | 31.37327 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.42832 | 25.59126 | -0.3936 | 8.65777 |
February | 672.00000 | 21.45535 | 23.63635 | -0.4059 | 8.96787 |
March | 744.00000 | 21.75319 | 22.63249 | -0.3274 | 8.05005 |
April | 720.00000 | 21.67711 | 27.14775 | -0.3154 | 7.68871 |
May | 744.00000 | 22.71434 | 29.72973 | -1.0524 | 29.25587 |
June | 720.00000 | 23.75627 | 36.06330 | -0.6217 | 13.43633 |
July | 744.00000 | 23.78501 | 38.55875 | -0.5946 | 12.71015 |
August | 744.00000 | 23.73730 | 38.25414 | -0.6143 | 13.24161 |
September | 720.00000 | 23.43769 | 28.01550 | -0.7982 | 19.50393 |
October | 744.00000 | 22.21608 | 24.94888 | -0.1926 | 6.78267 |
November | 720.00000 | 21.63205 | 26.74245 | -0.3321 | 7.91898 |
December | 744.00000 | 21.27934 | 19.76929 | -0.4817 | 10.24181 |
Annual Sum or Average | 8760.00000 | 22.41141 | 28.45180 | -0.5116 | 12.23199 |
Minimum of Months | 672.00000 | 21.27934 | 19.76929 | -1.0524 | 6.78267 |
Maximum of Months | 744.00000 | 23.78501 | 38.55875 | -0.1926 | 29.25587 |
Report: OccupantComfortDataSummaryMonthly
For: MECH_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.73954 | 23.79287 | -0.3366 | 7.77888 |
February | 672.00000 | 21.58427 | 22.07595 | -0.3888 | 8.66431 |
March | 744.00000 | 21.93655 | 21.08117 | -0.3054 | 7.46445 |
April | 720.00000 | 22.00840 | 25.32474 | -0.2622 | 6.94280 |
May | 744.00000 | 23.05944 | 27.91333 | -0.9923 | 26.39287 |
June | 720.00000 | 23.87598 | 34.57550 | -0.6486 | 13.98186 |
July | 744.00000 | 23.91932 | 36.96590 | -0.6154 | 13.07570 |
August | 744.00000 | 23.86981 | 36.87668 | -0.6381 | 13.73527 |
September | 720.00000 | 23.66104 | 26.39919 | -0.7863 | 18.57216 |
October | 744.00000 | 22.54841 | 23.16783 | -0.1420 | 6.03413 |
November | 720.00000 | 21.95995 | 24.89468 | -0.2760 | 7.05183 |
December | 744.00000 | 21.55155 | 18.13733 | -0.4251 | 9.22134 |
Annual Sum or Average | 8760.00000 | 22.64900 | 26.79435 | -0.4854 | 11.59957 |
Minimum of Months | 672.00000 | 21.55155 | 18.13733 | -0.9923 | 6.03413 |
Maximum of Months | 744.00000 | 23.91932 | 36.96590 | -0.1420 | 26.39287 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.122475E+11 | 52101.27 | 20-JAN-13:15 | 486.13 | 0.569769E+11 | 0.00 | 0.692244E+11 | 3.07 | 4.72 | 01-JAN-16:15 | 0.00 | 0.00 |
February | 0.919242E+10 | 48183.02 | 18-FEB-13:37 | 372.77 | 0.429506E+11 | 0.00 | 0.521430E+11 | 2.61 | 4.72 | 01-FEB-12:00 | 0.00 | 0.00 |
March | 0.155019E+11 | 79887.62 | 13-MAR-15:03 | 478.52 | 0.704132E+11 | 0.00 | 0.859151E+11 | 3.00 | 4.72 | 01-MAR-07:30 | 0.00 | 0.00 |
April | 0.119584E+11 | 60656.34 | 07-APR-15:03 | 479.68 | 0.542705E+11 | 0.00 | 0.662289E+11 | 3.11 | 4.72 | 01-APR-05:10 | 0.00 | 0.00 |
May | 0.405990E+11 | 89291.21 | 31-MAY-18:03 | 719.56 | 0.176221E+12 | 0.00 | 0.216820E+12 | 4.41 | 4.72 | 01-MAY-18:09 | 0.00 | 0.00 |
June | 0.117435E+12 | 148590.42 | 26-JUN-18:05 | 720.00 | 0.462704E+12 | 0.00 | 0.580138E+12 | 4.17 | 4.72 | 09-JUN-02:20 | 0.00 | 0.00 |
July | 0.130027E+12 | 126473.16 | 17-JUL-18:42 | 744.00 | 0.516396E+12 | 0.00 | 0.646424E+12 | 4.15 | 4.72 | 02-JUL-04:10 | 0.00 | 0.00 |
August | 0.118951E+12 | 132020.51 | 16-AUG-15:13 | 744.00 | 0.476898E+12 | 0.00 | 0.595848E+12 | 4.21 | 4.72 | 13-AUG-05:30 | 0.00 | 0.00 |
September | 0.850756E+11 | 111331.57 | 13-SEP-15:04 | 714.02 | 0.351147E+12 | 0.00 | 0.436222E+12 | 4.32 | 4.72 | 01-SEP-04:20 | 0.00 | 0.00 |
October | 0.246267E+11 | 94672.77 | 11-OCT-15:03 | 551.95 | 0.110365E+12 | 0.00 | 0.134992E+12 | 3.44 | 4.72 | 01-OCT-03:40 | 0.00 | 0.00 |
November | 0.139228E+11 | 63783.93 | 05-NOV-15:02 | 485.02 | 0.639814E+11 | 0.00 | 0.779042E+11 | 3.16 | 4.72 | 02-NOV-10:33 | 0.00 | 0.00 |
December | 0.889412E+10 | 47301.91 | 02-DEC-13:15 | 364.39 | 0.408802E+11 | 0.00 | 0.497743E+11 | 2.30 | 4.72 | 01-DEC-09:20 | 0.00 | 0.00 |
Annual Sum or Average | 0.588431E+12 | 6860.04 | 0.242320E+13 | 0.00 | 0.301163E+13 | 3.50 | 0.00 | 0.00 | ||||
Minimum of Months | 0.889412E+10 | 47301.91 | 364.39 | 0.408802E+11 | 0.00 | 0.497743E+11 | 2.30 | 4.72 | 0.00 | 0.00 | ||
Maximum of Months | 0.130027E+12 | 148590.42 | 744.00 | 0.516396E+12 | 0.00 | 0.646424E+12 | 4.41 | 4.72 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.106047E+12 | 0.00 | 690.26 | 209447.12 | 05-JAN-19:05 | 0.00 | 39.31 | 58.34 | 0.41 | 0.00 | 0.07 | 0.39 | 05-JAN-19:05 |
February | 0.109590E+12 | 0.00 | 634.44 | 196265.22 | 07-FEB-16:03 | 0.00 | 38.39 | 58.54 | 0.46 | 0.00 | 0.09 | 0.37 | 07-FEB-16:03 |
March | 0.952768E+11 | 0.00 | 632.18 | 185402.32 | 21-MAR-15:02 | 0.00 | 35.89 | 55.00 | 0.35 | 0.00 | 0.07 | 0.35 | 21-MAR-15:02 |
April | 0.877765E+11 | 0.00 | 601.60 | 136872.06 | 10-APR-08:05 | 0.00 | 35.30 | 54.59 | 0.32 | 0.00 | 0.06 | 0.26 | 10-APR-08:05 |
May | 0.730129E+11 | 0.00 | 427.99 | 131917.38 | 02-MAY-18:04 | 0.00 | 27.87 | 45.31 | 0.22 | 0.00 | 0.05 | 0.25 | 02-MAY-18:04 |
June | 0.507827E+10 | 0.00 | 60.89 | 110306.14 | 09-JUN-03:40 | 0.00 | 24.05 | 27.03 | 0.01 | 0.00 | 0.00 | 0.21 | 09-JUN-03:40 |
July | 0.455946E+10 | 0.00 | 43.31 | 76251.29 | 02-JUL-05:00 | 0.00 | 25.62 | 27.63 | 0.01 | 0.00 | 0.00 | 0.14 | 02-JUL-05:00 |
August | 0.464505E+10 | 0.00 | 56.93 | 57000.48 | 12-AUG-23:00 | 0.00 | 26.21 | 28.89 | 0.01 | 0.00 | 0.00 | 0.11 | 12-AUG-23:00 |
September | 0.282008E+11 | 0.00 | 195.92 | 133730.84 | 21-SEP-14:20 | 0.00 | 26.11 | 34.74 | 0.09 | 0.00 | 0.02 | 0.25 | 21-SEP-14:20 |
October | 0.804593E+11 | 0.00 | 558.36 | 158252.24 | 30-OCT-08:62 | 0.00 | 33.99 | 51.86 | 0.28 | 0.00 | 0.06 | 0.30 | 30-OCT-08:62 |
November | 0.824514E+11 | 0.00 | 634.20 | 172065.05 | 24-NOV-16:03 | 0.00 | 38.90 | 56.75 | 0.33 | 0.00 | 0.06 | 0.32 | 24-NOV-16:03 |
December | 0.154098E+12 | 0.00 | 697.18 | 238212.65 | 21-DEC-09:05 | 0.00 | 38.42 | 58.59 | 0.58 | 0.00 | 0.11 | 0.45 | 21-DEC-09:05 |
Annual Sum or Average | 0.831195E+12 | 0.00 | 5233.26 | 0.00 | 32.47 | 46.37 | 0.26 | 0.00 | 0.05 | ||||
Minimum of Months | 0.455946E+10 | 0.00 | 43.31 | 57000.48 | 0.00 | 24.05 | 27.03 | 0.01 | 0.00 | 0.00 | 0.11 | ||
Maximum of Months | 0.154098E+12 | 0.00 | 697.18 | 238212.65 | 0.00 | 39.31 | 58.59 | 0.58 | 0.00 | 0.11 | 0.45 |
Report: DXReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.192282E+09 | 0.00 | 14.67 | 0.192282E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11112.29 | 20-JAN-14:00 | 11112.29 | 20-JAN-14:00 | 0.00 | 0.00 | 0.00 |
February | 0.123483E+09 | 0.00 | 9.33 | 0.123483E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9344.67 | 18-FEB-14:00 | 9344.67 | 18-FEB-14:00 | 0.00 | 0.00 | 0.00 |
March | 0.894175E+09 | 0.00 | 49.33 | 0.894175E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13447.39 | 13-MAR-15:02 | 13447.39 | 13-MAR-15:02 | 0.00 | 0.00 | 0.00 |
April | 0.105845E+10 | 0.00 | 59.33 | 0.105845E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12344.03 | 20-APR-13:00 | 12344.03 | 20-APR-13:00 | 0.00 | 0.00 | 0.00 |
May | 0.512689E+10 | 0.00 | 201.17 | 0.512689E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15634.50 | 17-MAY-13:00 | 15634.50 | 17-MAY-13:00 | 0.00 | 0.00 | 0.00 |
June | 0.173293E+11 | 0.00 | 514.67 | 0.168247E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 21371.02 | 18-JUN-12:05 | 18844.67 | 26-JUN-15:03 | 0.00 | 0.00 | 0.00 |
July | 0.210710E+11 | 0.00 | 551.83 | 0.191669E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 25905.13 | 30-JUL-15:37 | 18133.97 | 16-JUL-13:00 | 0.00 | 0.00 | 0.00 |
August | 0.182586E+11 | 0.00 | 538.50 | 0.171944E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 21036.31 | 05-AUG-15:02 | 17908.65 | 16-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.117438E+11 | 0.00 | 387.83 | 0.117438E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 16830.58 | 10-SEP-13:00 | 16830.58 | 10-SEP-13:00 | 0.00 | 0.00 | 0.00 |
October | 0.173362E+10 | 0.00 | 82.00 | 0.173362E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14656.79 | 11-OCT-15:02 | 14656.79 | 11-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.497130E+09 | 0.00 | 28.33 | 0.497130E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12330.11 | 06-NOV-13:50 | 12330.11 | 06-NOV-13:50 | 0.00 | 0.00 | 0.00 |
December | 0.275091E+09 | 0.00 | 17.83 | 0.275091E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11661.97 | 01-DEC-14:00 | 11661.97 | 01-DEC-14:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.783038E+11 | 0.00 | 2454.83 | 0.748311E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.123483E+09 | 0.00 | 9.33 | 0.123483E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9344.67 | 9344.67 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.210710E+11 | 0.00 | 551.83 | 0.191669E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 25905.13 | 18844.67 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.527522E+10 | 0.00 | 49.82 | 0.527522E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 123745.19 | 20-JAN-13:00 | 123745.19 | 20-JAN-13:00 | 0.00 | 0.00 | 0.00 |
February | 0.295321E+10 | 0.00 | 22.53 | 0.295321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 112634.92 | 18-FEB-13:00 | 112634.92 | 18-FEB-13:00 | 0.00 | 0.00 | 0.00 |
March | 0.182652E+11 | 0.00 | 119.76 | 0.182652E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 153222.08 | 14-MAR-13:00 | 153222.08 | 14-MAR-13:00 | 0.00 | 0.00 | 0.00 |
April | 0.191272E+11 | 0.00 | 124.60 | 0.191272E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 108415.72 | 19-APR-10:50 | 108415.72 | 19-APR-10:50 | 0.00 | 0.00 | 0.00 |
May | 0.890894E+11 | 0.00 | 308.17 | 0.890894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 202844.21 | 31-MAY-18:07 | 202844.21 | 31-MAY-18:07 | 0.00 | 0.00 | 0.00 |
June | 0.292388E+12 | 0.00 | 659.17 | 0.287438E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 278121.23 | 26-JUN-18:20 | 278121.23 | 26-JUN-18:20 | 0.00 | 0.00 | 0.00 |
July | 0.336345E+12 | 0.00 | 703.17 | 0.316784E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 284410.40 | 30-JUL-10:40 | 264624.47 | 17-JUL-20:10 | 0.00 | 0.00 | 0.00 |
August | 0.300331E+12 | 0.00 | 688.83 | 0.292772E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 267745.35 | 16-AUG-18:05 | 267745.35 | 16-AUG-18:05 | 0.00 | 0.00 | 0.00 |
September | 0.206989E+12 | 0.00 | 524.00 | 0.206989E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 241681.96 | 12-SEP-18:30 | 241681.96 | 12-SEP-18:30 | 0.00 | 0.00 | 0.00 |
October | 0.338864E+11 | 0.00 | 146.33 | 0.338864E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 179083.54 | 11-OCT-15:10 | 179083.54 | 11-OCT-15:10 | 0.00 | 0.00 | 0.00 |
November | 0.107359E+11 | 0.00 | 65.60 | 0.107359E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 136540.05 | 06-NOV-13:00 | 136540.05 | 06-NOV-13:00 | 0.00 | 0.00 | 0.00 |
December | 0.717379E+10 | 0.00 | 43.69 | 0.717379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 116626.29 | 02-DEC-13:00 | 116626.29 | 02-DEC-13:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.132256E+13 | 0.00 | 3455.66 | 0.129049E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.295321E+10 | 0.00 | 22.53 | 0.295321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 108415.72 | 108415.72 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.336345E+12 | 0.00 | 703.17 | 0.316784E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 284410.40 | 278121.23 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.144698E+10 | 0.00 | 225.85 | 0.123723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11596.59 | 26-JAN-16:01 | 11596.59 | 26-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.152996E+10 | 0.00 | 205.84 | 0.135759E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11596.53 | 11-FEB-16:02 | 11596.53 | 11-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.283996E+10 | 0.00 | 305.40 | 0.279293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11596.86 | 11-MAR-09:02 | 11596.86 | 11-MAR-09:02 | 0.00 | 0.00 | 0.00 |
April | 0.195075E+10 | 0.00 | 269.23 | 0.174762E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11595.89 | 20-APR-15:01 | 11595.89 | 20-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.463948E+10 | 0.00 | 593.31 | 0.366884E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12001.89 | 22-MAY-08:62 | 11643.94 | 22-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.983319E+10 | 0.00 | 688.19 | 0.795145E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13043.76 | 18-JUN-08:62 | 11639.92 | 21-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.960901E+10 | 0.00 | 712.56 | 0.732713E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13053.69 | 27-JUL-18:02 | 11594.04 | 01-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.970440E+10 | 0.00 | 711.11 | 0.756203E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13085.46 | 05-AUG-08:62 | 11598.59 | 04-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.782648E+10 | 0.00 | 656.90 | 0.676298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11597.03 | 30-SEP-15:02 | 11597.03 | 30-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.389606E+10 | 0.00 | 422.72 | 0.353908E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11597.65 | 21-OCT-15:02 | 11597.65 | 21-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.193375E+10 | 0.00 | 276.41 | 0.158968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11597.29 | 24-NOV-16:02 | 11597.29 | 24-NOV-16:02 | 0.00 | 0.00 | 0.00 |
December | 0.902789E+09 | 0.00 | 151.32 | 0.873902E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11596.28 | 29-DEC-16:01 | 11596.28 | 29-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.561128E+11 | 0.00 | 5218.84 | 0.464105E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.902789E+09 | 0.00 | 151.32 | 0.873902E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11595.89 | 11594.04 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.983319E+10 | 0.00 | 712.56 | 0.795145E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13085.46 | 11643.94 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.243005E+09 | 0.00 | 54.57 | 0.220946E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11330.27 | 26-JAN-16:01 | 11330.27 | 26-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.368664E+09 | 0.00 | 70.65 | 0.339265E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11329.29 | 15-FEB-16:02 | 11329.29 | 15-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.114976E+10 | 0.00 | 186.14 | 0.113346E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12789.66 | 15-MAR-18:31 | 12789.66 | 15-MAR-18:31 | 0.00 | 0.00 | 0.00 |
April | 0.976966E+09 | 0.00 | 181.07 | 0.831245E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14349.27 | 08-APR-17:42 | 14349.27 | 08-APR-17:42 | 0.00 | 0.00 | 0.00 |
May | 0.321651E+10 | 0.00 | 468.73 | 0.236863E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12825.99 | 27-MAY-16:11 | 12825.99 | 27-MAY-16:11 | 0.00 | 0.00 | 0.00 |
June | 0.835991E+10 | 0.00 | 544.16 | 0.691083E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14417.29 | 22-JUN-21:51 | 12582.18 | 18-JUN-21:51 | 0.00 | 0.00 | 0.00 |
July | 0.784155E+10 | 0.00 | 546.06 | 0.611751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14339.25 | 31-JUL-21:51 | 12975.24 | 01-JUL-08:61 | 0.00 | 0.00 | 0.00 |
August | 0.730169E+10 | 0.00 | 544.70 | 0.565164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13850.72 | 05-AUG-21:51 | 12402.67 | 11-AUG-21:51 | 0.00 | 0.00 | 0.00 |
September | 0.486065E+10 | 0.00 | 480.15 | 0.402541E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12277.07 | 15-SEP-19:51 | 12277.07 | 15-SEP-19:51 | 0.00 | 0.00 | 0.00 |
October | 0.153039E+10 | 0.00 | 253.26 | 0.135672E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12501.60 | 14-OCT-16:11 | 12501.60 | 14-OCT-16:11 | 0.00 | 0.00 | 0.00 |
November | 0.401145E+09 | 0.00 | 89.61 | 0.343888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11330.69 | 16-NOV-16:02 | 11330.69 | 16-NOV-16:02 | 0.00 | 0.00 | 0.00 |
December | 0.111940E+09 | 0.00 | 32.22 | 0.110919E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11329.93 | 29-DEC-16:01 | 11329.93 | 29-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.363622E+11 | 0.00 | 3451.32 | 0.294105E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.111940E+09 | 0.00 | 32.22 | 0.110919E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11329.29 | 11329.29 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.835991E+10 | 0.00 | 546.06 | 0.691083E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14417.29 | 14349.27 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.345404E+11 | 0.00 | 422.42 | 0.345404E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 70513.89 | 20-JAN-12:40 | 70513.89 | 20-JAN-12:40 | 0.00 | 0.00 | 0.00 |
February | 0.245262E+11 | 0.00 | 308.19 | 0.245262E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 66077.74 | 18-FEB-13:00 | 66077.74 | 18-FEB-13:00 | 0.00 | 0.00 | 0.00 |
March | 0.246526E+11 | 0.00 | 333.68 | 0.246526E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 59562.53 | 14-MAR-12:40 | 59562.53 | 14-MAR-12:40 | 0.00 | 0.00 | 0.00 |
April | 0.954113E+10 | 0.00 | 215.33 | 0.922836E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36527.05 | 08-APR-13:00 | 36527.05 | 08-APR-13:00 | 0.00 | 0.00 | 0.00 |
May | 0.224943E+11 | 0.00 | 543.42 | 0.168771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 28756.62 | 05-MAY-13:00 | 28756.62 | 05-MAY-13:00 | 0.00 | 0.00 | 0.00 |
June | 0.418490E+11 | 0.00 | 712.92 | 0.276164E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 33766.55 | 14-JUN-13:30 | 33766.55 | 14-JUN-13:30 | 0.00 | 0.00 | 0.00 |
July | 0.457377E+11 | 0.00 | 741.50 | 0.306108E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 37722.40 | 23-JUL-12:40 | 33782.69 | 23-JUL-13:00 | 0.00 | 0.00 | 0.00 |
August | 0.521340E+11 | 0.00 | 742.42 | 0.371679E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 48184.61 | 31-AUG-12:40 | 42989.23 | 19-AUG-13:00 | 0.00 | 0.00 | 0.00 |
September | 0.526855E+11 | 0.00 | 691.58 | 0.456288E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 61537.33 | 28-SEP-13:00 | 61537.33 | 28-SEP-13:00 | 0.00 | 0.00 | 0.00 |
October | 0.389010E+11 | 0.00 | 464.47 | 0.382515E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 64142.50 | 10-OCT-12:30 | 64142.50 | 10-OCT-12:30 | 0.00 | 0.00 | 0.00 |
November | 0.325280E+11 | 0.00 | 397.69 | 0.325280E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 69984.40 | 07-NOV-12:10 | 69984.40 | 07-NOV-12:10 | 0.00 | 0.00 | 0.00 |
December | 0.213818E+11 | 0.00 | 270.83 | 0.213818E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 62651.42 | 17-DEC-12:30 | 62651.42 | 17-DEC-12:30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.400972E+12 | 0.00 | 5844.45 | 0.343010E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.954113E+10 | 0.00 | 215.33 | 0.922836E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28756.62 | 28756.62 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.526855E+11 | 0.00 | 742.42 | 0.456288E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 70513.89 | 70513.89 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.182467E+10 | 0.00 | 109.53 | 0.152873E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58901.55 | 21-JAN-09:02 | 58901.55 | 21-JAN-09:02 | 0.00 | 0.00 | 0.00 |
February | 0.171594E+10 | 0.00 | 91.26 | 0.145369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59058.33 | 19-FEB-09:02 | 59058.33 | 19-FEB-09:02 | 0.00 | 0.00 | 0.00 |
March | 0.715555E+10 | 0.00 | 233.62 | 0.678060E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62361.41 | 14-MAR-20:51 | 62361.41 | 14-MAR-20:51 | 0.00 | 0.00 | 0.00 |
April | 0.101214E+11 | 0.00 | 309.92 | 0.825466E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63167.59 | 20-APR-20:31 | 63167.59 | 20-APR-20:31 | 0.00 | 0.00 | 0.00 |
May | 0.296050E+11 | 0.00 | 453.25 | 0.254838E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 64335.72 | 07-MAY-19:31 | 64335.72 | 07-MAY-19:31 | 0.00 | 0.00 | 0.00 |
June | 0.522944E+11 | 0.00 | 508.11 | 0.459800E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 75274.61 | 20-JUN-21:51 | 66931.30 | 30-JUN-07:42 | 0.00 | 0.00 | 0.00 |
July | 0.538972E+11 | 0.00 | 518.71 | 0.463559E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 76883.12 | 31-JUL-21:51 | 68198.37 | 01-JUL-08:61 | 0.00 | 0.00 | 0.00 |
August | 0.467124E+11 | 0.00 | 492.11 | 0.388396E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 73460.78 | 29-AUG-21:51 | 65656.58 | 01-AUG-21:51 | 0.00 | 0.00 | 0.00 |
September | 0.325014E+11 | 0.00 | 432.16 | 0.293916E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 64208.35 | 09-SEP-21:51 | 64208.35 | 09-SEP-21:51 | 0.00 | 0.00 | 0.00 |
October | 0.108115E+11 | 0.00 | 327.64 | 0.942864E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61946.17 | 01-OCT-18:01 | 61946.17 | 01-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.338537E+10 | 0.00 | 162.27 | 0.268795E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59513.18 | 09-NOV-19:02 | 59513.18 | 09-NOV-19:02 | 0.00 | 0.00 | 0.00 |
December | 0.130705E+10 | 0.00 | 82.88 | 0.130376E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58039.40 | 03-DEC-09:02 | 58039.40 | 03-DEC-09:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.251332E+12 | 0.00 | 3721.45 | 0.217489E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.130705E+10 | 0.00 | 82.88 | 0.130376E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58039.40 | 58039.40 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.538972E+11 | 0.00 | 518.71 | 0.463559E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 76883.12 | 68198.37 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.141149E+10 | 0.00 | 218.49 | 0.124810E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10228.32 | 20-JAN-09:02 | 10228.32 | 20-JAN-09:02 | 0.00 | 0.00 | 0.00 |
February | 0.169043E+10 | 0.00 | 222.60 | 0.151465E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10227.54 | 14-FEB-09:01 | 10227.54 | 14-FEB-09:01 | 0.00 | 0.00 | 0.00 |
March | 0.303469E+10 | 0.00 | 330.64 | 0.294009E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10227.68 | 03-MAR-09:02 | 10227.68 | 03-MAR-09:02 | 0.00 | 0.00 | 0.00 |
April | 0.229133E+10 | 0.00 | 302.53 | 0.202915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10227.77 | 20-APR-15:01 | 10227.77 | 20-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.506218E+10 | 0.00 | 631.10 | 0.407105E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10419.71 | 22-MAY-15:02 | 10249.20 | 22-MAY-08:62 | 0.00 | 0.00 | 0.00 |
June | 0.104562E+11 | 0.00 | 708.53 | 0.871874E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11237.35 | 17-JUN-08:62 | 10227.42 | 14-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.107362E+11 | 0.00 | 729.23 | 0.870390E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11545.37 | 27-JUL-18:02 | 10250.86 | 30-JUL-08:62 | 0.00 | 0.00 | 0.00 |
August | 0.107633E+11 | 0.00 | 729.29 | 0.881384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10594.57 | 21-AUG-18:02 | 10240.03 | 05-AUG-08:62 | 0.00 | 0.00 | 0.00 |
September | 0.824907E+10 | 0.00 | 674.98 | 0.733039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10227.65 | 30-SEP-15:02 | 10227.65 | 30-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.374673E+10 | 0.00 | 417.09 | 0.340716E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10227.84 | 21-OCT-08:62 | 10227.84 | 21-OCT-08:62 | 0.00 | 0.00 | 0.00 |
November | 0.186883E+10 | 0.00 | 270.31 | 0.156530E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10226.43 | 07-NOV-09:02 | 10226.43 | 07-NOV-09:02 | 0.00 | 0.00 | 0.00 |
December | 0.933840E+09 | 0.00 | 150.39 | 0.905711E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10228.12 | 05-DEC-09:02 | 10228.12 | 05-DEC-09:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.602443E+11 | 0.00 | 5385.18 | 0.512481E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.933840E+09 | 0.00 | 150.39 | 0.905711E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10226.43 | 10226.43 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.107633E+11 | 0.00 | 729.29 | 0.881384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11545.37 | 10250.86 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.261454E+09 | 0.00 | 50.24 | 0.214576E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10005.96 | 24-JAN-09:02 | 10005.96 | 24-JAN-09:02 | 0.00 | 0.00 | 0.00 |
February | 0.501540E+09 | 0.00 | 79.77 | 0.434481E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10007.19 | 27-FEB-09:02 | 10007.19 | 27-FEB-09:02 | 0.00 | 0.00 | 0.00 |
March | 0.140263E+10 | 0.00 | 210.15 | 0.134537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10226.99 | 14-MAR-20:51 | 10226.99 | 14-MAR-20:51 | 0.00 | 0.00 | 0.00 |
April | 0.141354E+10 | 0.00 | 223.53 | 0.120727E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10253.21 | 20-APR-20:31 | 10253.21 | 20-APR-20:31 | 0.00 | 0.00 | 0.00 |
May | 0.376833E+10 | 0.00 | 511.68 | 0.292198E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11550.36 | 04-MAY-08:51 | 11550.36 | 04-MAY-08:51 | 0.00 | 0.00 | 0.00 |
June | 0.864264E+10 | 0.00 | 561.92 | 0.728142E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13798.72 | 21-JUN-08:32 | 12819.82 | 28-JUN-08:32 | 0.00 | 0.00 | 0.00 |
July | 0.867945E+10 | 0.00 | 561.66 | 0.718449E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13784.68 | 01-JUL-07:32 | 13784.68 | 01-JUL-07:32 | 0.00 | 0.00 | 0.00 |
August | 0.806730E+10 | 0.00 | 566.09 | 0.648062E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14080.95 | 04-AUG-08:32 | 12550.83 | 06-AUG-08:32 | 0.00 | 0.00 | 0.00 |
September | 0.531302E+10 | 0.00 | 509.44 | 0.450128E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11603.79 | 18-SEP-08:51 | 11603.79 | 18-SEP-08:51 | 0.00 | 0.00 | 0.00 |
October | 0.153693E+10 | 0.00 | 263.07 | 0.134379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11430.55 | 11-OCT-08:51 | 11430.55 | 11-OCT-08:51 | 0.00 | 0.00 | 0.00 |
November | 0.453192E+09 | 0.00 | 86.85 | 0.365717E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10006.71 | 07-NOV-09:02 | 10006.71 | 07-NOV-09:02 | 0.00 | 0.00 | 0.00 |
December | 0.149660E+09 | 0.00 | 29.78 | 0.135136E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10005.67 | 03-DEC-09:02 | 10005.67 | 03-DEC-09:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.401897E+11 | 0.00 | 3654.18 | 0.334161E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.149660E+09 | 0.00 | 29.78 | 0.135136E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10005.67 | 10005.67 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.867945E+10 | 0.00 | 566.09 | 0.728142E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14080.95 | 13784.68 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.324472E+09 | 0.00 | 168.13 | 0.283974E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3078.54 | 26-JAN-16:01 | 3078.54 | 26-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.357022E+09 | 0.00 | 159.70 | 0.321950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3078.48 | 11-FEB-16:02 | 3078.48 | 11-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.687480E+09 | 0.00 | 253.44 | 0.676948E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3078.34 | 30-MAR-18:01 | 3078.34 | 30-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.494616E+09 | 0.00 | 229.46 | 0.446387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3078.39 | 20-APR-15:01 | 3078.39 | 20-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.111928E+10 | 0.00 | 516.84 | 0.906796E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3402.02 | 22-MAY-08:62 | 3089.76 | 29-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.249057E+10 | 0.00 | 685.88 | 0.201914E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3557.15 | 18-JUN-08:62 | 3078.63 | 14-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.238692E+10 | 0.00 | 708.94 | 0.181813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3634.15 | 30-JUL-08:62 | 3081.30 | 27-JUL-08:62 | 0.00 | 0.00 | 0.00 |
August | 0.241388E+10 | 0.00 | 704.47 | 0.188709E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3603.88 | 05-AUG-08:62 | 3078.68 | 14-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.185810E+10 | 0.00 | 634.13 | 0.159675E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3078.63 | 30-SEP-15:02 | 3078.63 | 30-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.892751E+09 | 0.00 | 335.20 | 0.819245E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3078.59 | 13-OCT-15:01 | 3078.59 | 13-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.444616E+09 | 0.00 | 212.45 | 0.376299E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3078.65 | 25-NOV-16:01 | 3078.65 | 25-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.203662E+09 | 0.00 | 120.96 | 0.197785E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3078.40 | 29-DEC-16:01 | 3078.40 | 29-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.136734E+11 | 0.00 | 4729.58 | 0.113505E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.203662E+09 | 0.00 | 120.96 | 0.197785E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3078.34 | 3078.34 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.249057E+10 | 0.00 | 708.94 | 0.201914E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3634.15 | 3089.76 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 47773945.46 | 0.00 | 35.89 | 43357941.68 | 0.00 | 0.00 | 0.00 | 0.00 | 3001.22 | 21-JAN-16:02 | 3001.22 | 21-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 79419403.88 | 0.00 | 47.73 | 72973140.09 | 0.00 | 0.00 | 0.00 | 0.00 | 3001.84 | 15-FEB-16:02 | 3001.84 | 15-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.264847E+09 | 0.00 | 149.57 | 0.261135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3459.81 | 15-MAR-18:31 | 3459.81 | 15-MAR-18:31 | 0.00 | 0.00 | 0.00 |
April | 0.242401E+09 | 0.00 | 152.32 | 0.209958E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3840.77 | 08-APR-17:42 | 3840.77 | 08-APR-17:42 | 0.00 | 0.00 | 0.00 |
May | 0.765504E+09 | 0.00 | 420.16 | 0.576996E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3450.95 | 27-MAY-16:11 | 3450.95 | 27-MAY-16:11 | 0.00 | 0.00 | 0.00 |
June | 0.217451E+10 | 0.00 | 545.61 | 0.179549E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3921.18 | 22-JUN-21:51 | 3416.31 | 18-JUN-21:51 | 0.00 | 0.00 | 0.00 |
July | 0.200444E+10 | 0.00 | 546.85 | 0.156166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3885.01 | 31-JUL-21:51 | 3418.52 | 01-JUL-08:61 | 0.00 | 0.00 | 0.00 |
August | 0.186248E+10 | 0.00 | 544.09 | 0.144328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3774.56 | 05-AUG-21:51 | 3300.68 | 11-AUG-21:51 | 0.00 | 0.00 | 0.00 |
September | 0.115014E+10 | 0.00 | 465.08 | 0.942971E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3321.24 | 15-SEP-19:51 | 3321.24 | 15-SEP-19:51 | 0.00 | 0.00 | 0.00 |
October | 0.316246E+09 | 0.00 | 184.08 | 0.286084E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3412.93 | 08-OCT-18:11 | 3412.93 | 08-OCT-18:11 | 0.00 | 0.00 | 0.00 |
November | 84525646.34 | 0.00 | 64.32 | 75192812.88 | 0.00 | 0.00 | 0.00 | 0.00 | 3002.16 | 16-NOV-16:02 | 3002.16 | 16-NOV-16:02 | 0.00 | 0.00 | 0.00 |
December | 23013948.59 | 0.00 | 19.90 | 22723102.67 | 0.00 | 0.00 | 0.00 | 0.00 | 3001.23 | 02-DEC-16:01 | 3001.23 | 02-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.901529E+10 | 0.00 | 3175.60 | 0.729183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 23013948.59 | 0.00 | 19.90 | 22723102.67 | 0.00 | 0.00 | 0.00 | 0.00 | 3001.22 | 3001.22 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.217451E+10 | 0.00 | 546.85 | 0.179549E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3921.18 | 3840.77 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.763478E+10 | 0.00 | 412.08 | 0.717995E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13850.72 | 20-JAN-13:10 | 13850.72 | 20-JAN-13:10 | 0.00 | 0.00 | 0.00 |
February | 0.620988E+10 | 0.00 | 338.76 | 0.583577E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14682.57 | 18-FEB-13:33 | 14682.57 | 18-FEB-13:33 | 0.00 | 0.00 | 0.00 |
March | 0.633898E+10 | 0.00 | 392.50 | 0.616882E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13641.96 | 05-MAR-16:02 | 13641.96 | 05-MAR-16:02 | 0.00 | 0.00 | 0.00 |
April | 0.332150E+10 | 0.00 | 314.80 | 0.296901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13640.81 | 06-APR-15:01 | 13640.81 | 06-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.567413E+10 | 0.00 | 577.37 | 0.449465E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14506.49 | 22-MAY-15:02 | 13640.09 | 04-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.108673E+11 | 0.00 | 680.31 | 0.851895E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15512.89 | 18-JUN-08:62 | 13641.39 | 27-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.117701E+11 | 0.00 | 705.15 | 0.897273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16097.67 | 30-JUL-18:02 | 13639.99 | 01-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.130418E+11 | 0.00 | 707.66 | 0.103645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 15290.29 | 04-AUG-08:62 | 13640.37 | 18-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.121654E+11 | 0.00 | 662.74 | 0.109438E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 13640.59 | 10-SEP-08:62 | 13640.59 | 10-SEP-08:62 | 0.00 | 0.00 | 0.00 |
October | 0.879661E+10 | 0.00 | 481.82 | 0.832951E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13718.90 | 08-OCT-15:18 | 13718.90 | 08-OCT-15:18 | 0.00 | 0.00 | 0.00 |
November | 0.787811E+10 | 0.00 | 437.19 | 0.720891E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13798.52 | 05-NOV-13:40 | 13798.52 | 05-NOV-13:40 | 0.00 | 0.00 | 0.00 |
December | 0.559171E+10 | 0.00 | 317.30 | 0.548810E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13778.44 | 29-DEC-13:55 | 13778.44 | 29-DEC-13:55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.992903E+11 | 0.00 | 6027.69 | 0.864747E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.332150E+10 | 0.00 | 314.80 | 0.296901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13640.59 | 13639.99 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.130418E+11 | 0.00 | 707.66 | 0.109438E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 16097.67 | 14682.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1327.33 | 1092.65 | 234.67 | 1515.10 | 624.54 | 0.00 | 0.00 | 0.00 |
February | 1255.98 | 998.64 | 257.34 | 1420.30 | 654.39 | 0.00 | 0.00 | 0.00 |
March | 943.45 | 623.53 | 319.92 | 1079.14 | 520.35 | 0.00 | 0.00 | 0.00 |
April | 617.77 | 255.57 | 362.20 | 647.81 | 465.51 | 0.00 | 0.00 | 0.00 |
May | 561.37 | 107.95 | 453.41 | 654.59 | 268.96 | 0.00 | 0.00 | 0.00 |
June | 510.38 | 92.13 | 418.25 | 742.78 | 144.99 | 0.00 | 0.00 | 0.00 |
July | 527.16 | 89.81 | 437.35 | 771.00 | 129.49 | 0.00 | 0.00 | 0.00 |
August | 670.74 | 275.95 | 394.79 | 979.64 | 151.41 | 0.00 | 0.00 | 0.00 |
September | 881.07 | 495.25 | 385.82 | 1200.90 | 237.99 | 0.00 | 0.00 | 0.00 |
October | 1040.04 | 736.90 | 303.14 | 1260.40 | 505.43 | 0.00 | 0.00 | 0.00 |
November | 1274.79 | 1016.81 | 257.98 | 1494.51 | 585.69 | 0.00 | 0.00 | 0.00 |
December | 1216.57 | 984.85 | 231.72 | 1358.54 | 711.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 900.20 | 561.69 | 338.52 | 1091.83 | 415.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 510.38 | 89.81 | 231.72 | 647.81 | 129.49 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1327.33 | 1092.65 | 453.41 | 1515.10 | 711.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3737.67 | 3076.84 | 660.83 | 4227.89 | 1857.40 | 0.00 | 0.00 | 0.00 |
February | 3536.75 | 2812.11 | 724.64 | 3962.44 | 1932.03 | 0.00 | 0.00 | 0.00 |
March | 2656.69 | 1755.81 | 900.88 | 3005.47 | 1548.85 | 0.00 | 0.00 | 0.00 |
April | 1739.60 | 719.67 | 1019.93 | 1789.35 | 1408.40 | 0.00 | 0.00 | 0.00 |
May | 1580.77 | 303.98 | 1276.78 | 1792.48 | 835.14 | 0.00 | 0.00 | 0.00 |
June | 1437.19 | 259.44 | 1177.75 | 2064.93 | 430.35 | 0.00 | 0.00 | 0.00 |
July | 1484.44 | 252.89 | 1231.56 | 2144.48 | 386.87 | 0.00 | 0.00 | 0.00 |
August | 1888.76 | 777.06 | 1111.70 | 2732.03 | 450.38 | 0.00 | 0.00 | 0.00 |
September | 2481.05 | 1394.59 | 1086.46 | 3354.71 | 705.16 | 0.00 | 0.00 | 0.00 |
October | 2928.68 | 2075.07 | 853.61 | 3520.66 | 1500.77 | 0.00 | 0.00 | 0.00 |
November | 3589.72 | 2863.26 | 726.46 | 4173.61 | 1741.57 | 0.00 | 0.00 | 0.00 |
December | 3425.79 | 2773.28 | 652.52 | 3789.52 | 2098.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2534.91 | 1581.67 | 953.24 | 3041.14 | 1237.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1437.19 | 252.89 | 652.52 | 1789.35 | 386.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3737.67 | 3076.84 | 1276.78 | 4227.89 | 2098.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 4855.45 | 3996.99 | 858.45 | 5573.24 | 2480.94 | 0.00 | 0.00 | 0.00 |
February | 4594.44 | 3653.09 | 941.35 | 5231.39 | 2590.44 | 0.00 | 0.00 | 0.00 |
March | 3451.19 | 2280.90 | 1170.29 | 3970.85 | 2095.73 | 0.00 | 0.00 | 0.00 |
April | 2259.84 | 934.90 | 1324.95 | 2364.78 | 1926.38 | 0.00 | 0.00 | 0.00 |
May | 2053.51 | 394.89 | 1658.62 | 2375.70 | 1121.05 | 0.00 | 0.00 | 0.00 |
June | 1866.99 | 337.03 | 1529.97 | 2751.15 | 567.07 | 0.00 | 0.00 | 0.00 |
July | 1928.38 | 328.51 | 1599.86 | 2854.95 | 508.80 | 0.00 | 0.00 | 0.00 |
August | 2453.61 | 1009.44 | 1444.17 | 3627.68 | 588.03 | 0.00 | 0.00 | 0.00 |
September | 3223.02 | 1811.65 | 1411.37 | 4441.32 | 924.65 | 0.00 | 0.00 | 0.00 |
October | 3804.52 | 2695.63 | 1108.89 | 4645.48 | 2015.82 | 0.00 | 0.00 | 0.00 |
November | 4663.25 | 3719.54 | 943.71 | 5504.41 | 2332.11 | 0.00 | 0.00 | 0.00 |
December | 4450.30 | 3602.64 | 847.66 | 4994.74 | 2818.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3292.99 | 2054.68 | 1238.31 | 4020.96 | 1658.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1866.99 | 328.51 | 847.66 | 2364.78 | 508.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4855.45 | 3996.99 | 1658.62 | 5573.24 | 2818.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 262.44 | 216.04 | 46.40 | 304.20 | 122.04 | 0.00 | 0.00 | 0.00 |
February | 248.33 | 197.45 | 50.88 | 284.03 | 129.67 | 0.00 | 0.00 | 0.00 |
March | 186.54 | 123.28 | 63.25 | 215.74 | 102.45 | 0.00 | 0.00 | 0.00 |
April | 122.14 | 50.53 | 71.61 | 129.04 | 92.83 | 0.00 | 0.00 | 0.00 |
May | 110.99 | 21.34 | 89.65 | 130.82 | 51.64 | 0.00 | 0.00 | 0.00 |
June | 100.91 | 18.22 | 82.70 | 152.32 | 22.91 | 0.00 | 0.00 | 0.00 |
July | 104.23 | 17.76 | 86.47 | 158.83 | 19.50 | 0.00 | 0.00 | 0.00 |
August | 132.62 | 54.56 | 78.06 | 199.33 | 23.26 | 0.00 | 0.00 | 0.00 |
September | 174.20 | 97.92 | 76.28 | 242.68 | 40.39 | 0.00 | 0.00 | 0.00 |
October | 205.63 | 145.70 | 59.94 | 252.81 | 97.47 | 0.00 | 0.00 | 0.00 |
November | 252.05 | 201.04 | 51.01 | 299.85 | 114.28 | 0.00 | 0.00 | 0.00 |
December | 240.54 | 194.72 | 45.82 | 271.50 | 141.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 177.99 | 111.06 | 66.93 | 219.72 | 79.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 100.91 | 17.76 | 45.82 | 129.04 | 19.50 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 262.44 | 216.04 | 89.65 | 304.20 | 141.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 169.84 | 107.64 | 62.20 | 158.08 | 251.93 | 0.00 | 0.00 | 0.00 |
February | 205.18 | 127.28 | 77.90 | 188.53 | 259.17 | 0.00 | 0.00 | 0.00 |
March | 239.27 | 131.80 | 107.47 | 238.19 | 194.34 | 0.00 | 0.00 | 0.00 |
April | 225.68 | 95.60 | 130.08 | 216.38 | 169.40 | 0.00 | 0.00 | 0.00 |
May | 275.93 | 97.45 | 178.48 | 321.62 | 93.75 | 0.00 | 0.00 | 0.00 |
June | 336.87 | 161.95 | 174.92 | 473.40 | 42.53 | 0.00 | 0.00 | 0.00 |
July | 274.17 | 100.11 | 174.07 | 390.85 | 36.26 | 0.00 | 0.00 | 0.00 |
August | 287.10 | 141.88 | 145.22 | 398.49 | 42.84 | 0.00 | 0.00 | 0.00 |
September | 255.45 | 122.90 | 132.55 | 336.76 | 76.02 | 0.00 | 0.00 | 0.00 |
October | 213.91 | 122.27 | 91.65 | 232.13 | 187.18 | 0.00 | 0.00 | 0.00 |
November | 175.65 | 106.68 | 68.97 | 169.39 | 226.74 | 0.00 | 0.00 | 0.00 |
December | 141.66 | 83.65 | 58.01 | 118.93 | 288.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 233.46 | 116.46 | 117.01 | 270.59 | 155.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 141.66 | 83.65 | 58.01 | 118.93 | 36.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 336.87 | 161.95 | 178.48 | 473.40 | 288.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.28 | 0.00 | 27.28 | 5.49 | 139.62 | 0.00 | 0.00 | 0.00 |
February | 34.29 | 0.00 | 34.29 | 6.50 | 144.37 | 0.00 | 0.00 | 0.00 |
March | 46.67 | 0.00 | 46.67 | 21.08 | 108.14 | 0.00 | 0.00 | 0.00 |
April | 58.67 | 0.38 | 58.29 | 32.47 | 92.15 | 0.00 | 0.00 | 0.00 |
May | 80.15 | 2.69 | 77.46 | 75.24 | 49.07 | 0.00 | 0.00 | 0.00 |
June | 87.88 | 9.83 | 78.05 | 122.66 | 22.94 | 0.00 | 0.00 | 0.00 |
July | 83.35 | 5.69 | 77.66 | 118.97 | 20.18 | 0.00 | 0.00 | 0.00 |
August | 66.36 | 1.80 | 64.56 | 90.06 | 24.39 | 0.00 | 0.00 | 0.00 |
September | 55.56 | 0.04 | 55.52 | 66.48 | 43.10 | 0.00 | 0.00 | 0.00 |
October | 39.75 | 0.00 | 39.75 | 22.86 | 101.60 | 0.00 | 0.00 | 0.00 |
November | 30.18 | 0.00 | 30.18 | 8.82 | 124.47 | 0.00 | 0.00 | 0.00 |
December | 25.53 | 0.00 | 25.53 | 4.57 | 160.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 53.07 | 1.71 | 51.36 | 48.17 | 85.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.53 | 0.00 | 25.53 | 4.57 | 20.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 87.88 | 9.83 | 78.05 | 122.66 | 160.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 169.84 | 107.64 | 62.20 | 164.67 | 246.04 | 0.00 | 0.00 | 0.00 |
February | 205.18 | 127.28 | 77.90 | 195.38 | 254.19 | 0.00 | 0.00 | 0.00 |
March | 239.27 | 131.80 | 107.47 | 242.25 | 192.62 | 0.00 | 0.00 | 0.00 |
April | 225.68 | 95.60 | 130.08 | 218.17 | 169.08 | 0.00 | 0.00 | 0.00 |
May | 275.93 | 97.45 | 178.48 | 319.97 | 95.91 | 0.00 | 0.00 | 0.00 |
June | 336.87 | 161.95 | 174.92 | 470.06 | 46.04 | 0.00 | 0.00 | 0.00 |
July | 274.17 | 100.11 | 174.07 | 387.18 | 39.51 | 0.00 | 0.00 | 0.00 |
August | 287.10 | 141.88 | 145.22 | 397.10 | 46.31 | 0.00 | 0.00 | 0.00 |
September | 255.45 | 122.90 | 132.55 | 337.47 | 79.43 | 0.00 | 0.00 | 0.00 |
October | 213.91 | 122.27 | 91.65 | 235.96 | 185.60 | 0.00 | 0.00 | 0.00 |
November | 175.65 | 106.68 | 68.97 | 175.77 | 222.03 | 0.00 | 0.00 | 0.00 |
December | 141.66 | 83.65 | 58.01 | 124.56 | 283.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 233.46 | 116.46 | 117.01 | 272.71 | 154.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 141.66 | 83.65 | 58.01 | 124.56 | 39.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 336.87 | 161.95 | 178.48 | 470.06 | 283.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 209.91 | 172.79 | 37.11 | 231.67 | 122.11 | 0.00 | 0.00 | 0.00 |
February | 198.62 | 157.93 | 40.70 | 217.19 | 123.33 | 0.00 | 0.00 | 0.00 |
March | 149.20 | 98.61 | 50.59 | 164.09 | 100.26 | 0.00 | 0.00 | 0.00 |
April | 97.70 | 40.42 | 57.28 | 95.28 | 96.18 | 0.00 | 0.00 | 0.00 |
May | 88.78 | 17.07 | 71.70 | 92.59 | 60.01 | 0.00 | 0.00 | 0.00 |
June | 80.71 | 14.57 | 66.14 | 109.06 | 33.06 | 0.00 | 0.00 | 0.00 |
July | 83.37 | 14.20 | 69.16 | 113.55 | 30.58 | 0.00 | 0.00 | 0.00 |
August | 106.07 | 43.64 | 62.43 | 147.15 | 34.79 | 0.00 | 0.00 | 0.00 |
September | 139.34 | 78.32 | 61.02 | 182.34 | 50.98 | 0.00 | 0.00 | 0.00 |
October | 164.47 | 116.54 | 47.94 | 192.95 | 100.86 | 0.00 | 0.00 | 0.00 |
November | 201.60 | 160.80 | 40.80 | 229.91 | 114.71 | 0.00 | 0.00 | 0.00 |
December | 192.39 | 155.75 | 36.65 | 208.42 | 133.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 142.36 | 88.83 | 53.53 | 165.05 | 83.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 80.71 | 14.20 | 36.65 | 92.59 | 30.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 209.91 | 172.79 | 71.70 | 231.67 | 133.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 21.83 | 0.00 | 21.83 | 4.34 | 114.06 | 0.00 | 0.00 | 0.00 |
February | 27.44 | 0.00 | 27.44 | 5.38 | 117.48 | 0.00 | 0.00 | 0.00 |
March | 37.34 | 0.00 | 37.34 | 17.82 | 87.13 | 0.00 | 0.00 | 0.00 |
April | 46.94 | 0.31 | 46.64 | 26.99 | 74.88 | 0.00 | 0.00 | 0.00 |
May | 64.13 | 2.15 | 61.98 | 63.21 | 38.58 | 0.00 | 0.00 | 0.00 |
June | 70.31 | 7.86 | 62.45 | 103.00 | 16.74 | 0.00 | 0.00 | 0.00 |
July | 66.69 | 4.55 | 62.14 | 99.26 | 14.84 | 0.00 | 0.00 | 0.00 |
August | 53.10 | 1.44 | 51.66 | 76.45 | 17.68 | 0.00 | 0.00 | 0.00 |
September | 44.46 | 0.04 | 44.42 | 56.65 | 32.33 | 0.00 | 0.00 | 0.00 |
October | 31.81 | 0.00 | 31.81 | 19.76 | 81.39 | 0.00 | 0.00 | 0.00 |
November | 24.15 | 0.00 | 24.15 | 7.23 | 101.33 | 0.00 | 0.00 | 0.00 |
December | 20.42 | 0.00 | 20.42 | 3.51 | 132.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 42.46 | 1.37 | 41.10 | 40.50 | 68.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.42 | 0.00 | 20.42 | 3.51 | 14.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 70.31 | 7.86 | 62.45 | 103.00 | 132.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 159.00 | 97.25 | 61.75 | 138.35 | 247.73 | 0.00 | 0.00 | 0.00 |
February | 213.16 | 134.91 | 78.25 | 197.53 | 258.24 | 0.00 | 0.00 | 0.00 |
March | 256.77 | 149.88 | 106.89 | 257.87 | 190.67 | 0.00 | 0.00 | 0.00 |
April | 262.12 | 127.66 | 134.45 | 260.61 | 165.76 | 0.00 | 0.00 | 0.00 |
May | 307.29 | 128.64 | 178.65 | 357.12 | 88.35 | 0.00 | 0.00 | 0.00 |
June | 373.91 | 196.24 | 177.67 | 519.93 | 38.66 | 0.00 | 0.00 | 0.00 |
July | 339.39 | 161.28 | 178.12 | 478.35 | 34.09 | 0.00 | 0.00 | 0.00 |
August | 343.18 | 189.07 | 154.10 | 475.68 | 41.26 | 0.00 | 0.00 | 0.00 |
September | 286.01 | 155.47 | 130.54 | 373.74 | 71.92 | 0.00 | 0.00 | 0.00 |
October | 206.97 | 113.51 | 93.46 | 218.32 | 183.38 | 0.00 | 0.00 | 0.00 |
November | 160.61 | 90.51 | 70.10 | 148.28 | 225.33 | 0.00 | 0.00 | 0.00 |
December | 139.29 | 80.27 | 59.02 | 113.97 | 286.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 254.13 | 135.32 | 118.81 | 295.44 | 152.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 139.29 | 80.27 | 59.02 | 113.97 | 34.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 373.91 | 196.24 | 178.65 | 519.93 | 286.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 262.44 | 216.04 | 46.40 | 303.65 | 121.53 | 0.00 | 0.00 | 0.00 |
February | 248.33 | 197.45 | 50.88 | 283.02 | 129.09 | 0.00 | 0.00 | 0.00 |
March | 186.54 | 123.28 | 63.25 | 214.29 | 101.95 | 0.00 | 0.00 | 0.00 |
April | 122.14 | 50.53 | 71.61 | 127.48 | 92.72 | 0.00 | 0.00 | 0.00 |
May | 110.99 | 21.34 | 89.65 | 129.57 | 51.46 | 0.00 | 0.00 | 0.00 |
June | 100.91 | 18.22 | 82.70 | 151.16 | 22.44 | 0.00 | 0.00 | 0.00 |
July | 104.23 | 17.76 | 86.47 | 157.33 | 19.32 | 0.00 | 0.00 | 0.00 |
August | 132.62 | 54.56 | 78.06 | 198.00 | 23.06 | 0.00 | 0.00 | 0.00 |
September | 174.20 | 97.92 | 76.28 | 241.66 | 40.10 | 0.00 | 0.00 | 0.00 |
October | 205.63 | 145.70 | 59.94 | 252.20 | 96.99 | 0.00 | 0.00 | 0.00 |
November | 252.05 | 201.04 | 51.01 | 299.48 | 113.70 | 0.00 | 0.00 | 0.00 |
December | 240.54 | 194.72 | 45.82 | 271.01 | 140.87 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 177.99 | 111.06 | 66.93 | 218.70 | 79.16 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 100.91 | 17.76 | 45.82 | 127.48 | 19.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 262.44 | 216.04 | 89.65 | 303.65 | 140.87 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.28 | 0.00 | 27.28 | 5.17 | 138.99 | 0.00 | 0.00 | 0.00 |
February | 34.29 | 0.00 | 34.29 | 5.71 | 143.96 | 0.00 | 0.00 | 0.00 |
March | 46.67 | 0.00 | 46.67 | 19.87 | 107.65 | 0.00 | 0.00 | 0.00 |
April | 58.67 | 0.38 | 58.29 | 31.02 | 91.92 | 0.00 | 0.00 | 0.00 |
May | 80.15 | 2.69 | 77.46 | 74.01 | 48.57 | 0.00 | 0.00 | 0.00 |
June | 87.88 | 9.83 | 78.05 | 120.10 | 22.45 | 0.00 | 0.00 | 0.00 |
July | 83.35 | 5.69 | 77.66 | 116.31 | 20.01 | 0.00 | 0.00 | 0.00 |
August | 66.36 | 1.80 | 64.56 | 87.49 | 24.10 | 0.00 | 0.00 | 0.00 |
September | 55.56 | 0.04 | 55.52 | 65.03 | 42.43 | 0.00 | 0.00 | 0.00 |
October | 39.75 | 0.00 | 39.75 | 22.04 | 100.62 | 0.00 | 0.00 | 0.00 |
November | 30.18 | 0.00 | 30.18 | 8.24 | 123.56 | 0.00 | 0.00 | 0.00 |
December | 25.53 | 0.00 | 25.53 | 4.23 | 159.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 53.07 | 1.71 | 51.36 | 46.83 | 85.04 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.53 | 0.00 | 25.53 | 4.23 | 20.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 87.88 | 9.83 | 78.05 | 120.10 | 159.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 159.00 | 97.25 | 61.75 | 142.89 | 238.84 | 0.00 | 0.00 | 0.00 |
February | 213.16 | 134.91 | 78.25 | 202.11 | 250.65 | 0.00 | 0.00 | 0.00 |
March | 256.77 | 149.88 | 106.89 | 261.96 | 188.23 | 0.00 | 0.00 | 0.00 |
April | 262.12 | 127.66 | 134.45 | 262.69 | 165.05 | 0.00 | 0.00 | 0.00 |
May | 307.29 | 128.64 | 178.65 | 356.12 | 90.30 | 0.00 | 0.00 | 0.00 |
June | 373.91 | 196.24 | 177.67 | 513.80 | 42.27 | 0.00 | 0.00 | 0.00 |
July | 339.39 | 161.28 | 178.12 | 472.42 | 37.46 | 0.00 | 0.00 | 0.00 |
August | 343.18 | 189.07 | 154.10 | 471.99 | 44.81 | 0.00 | 0.00 | 0.00 |
September | 286.01 | 155.47 | 130.54 | 373.81 | 74.74 | 0.00 | 0.00 | 0.00 |
October | 206.97 | 113.51 | 93.46 | 222.41 | 181.16 | 0.00 | 0.00 | 0.00 |
November | 160.61 | 90.51 | 70.10 | 153.01 | 218.25 | 0.00 | 0.00 | 0.00 |
December | 139.29 | 80.27 | 59.02 | 117.95 | 279.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 254.13 | 135.32 | 118.81 | 296.37 | 150.37 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 139.29 | 80.27 | 59.02 | 117.95 | 37.46 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 373.91 | 196.24 | 178.65 | 513.80 | 279.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.55 | 0.00 | 34.55 | 5.56 | 191.19 | 0.00 | 0.00 | 0.00 |
February | 43.43 | 0.00 | 43.43 | 6.65 | 195.49 | 0.00 | 0.00 | 0.00 |
March | 59.11 | 0.00 | 59.11 | 25.55 | 146.08 | 0.00 | 0.00 | 0.00 |
April | 74.31 | 0.49 | 73.82 | 41.42 | 123.91 | 0.00 | 0.00 | 0.00 |
May | 101.51 | 3.40 | 98.10 | 96.73 | 67.06 | 0.00 | 0.00 | 0.00 |
June | 111.29 | 12.45 | 98.84 | 155.26 | 33.72 | 0.00 | 0.00 | 0.00 |
July | 105.56 | 7.21 | 98.35 | 149.33 | 31.27 | 0.00 | 0.00 | 0.00 |
August | 84.04 | 2.27 | 81.77 | 112.93 | 37.34 | 0.00 | 0.00 | 0.00 |
September | 70.37 | 0.06 | 70.31 | 82.66 | 62.45 | 0.00 | 0.00 | 0.00 |
October | 50.34 | 0.00 | 50.34 | 27.14 | 140.82 | 0.00 | 0.00 | 0.00 |
November | 38.22 | 0.00 | 38.22 | 9.46 | 170.57 | 0.00 | 0.00 | 0.00 |
December | 32.33 | 0.00 | 32.33 | 4.67 | 218.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 67.21 | 2.16 | 65.05 | 60.08 | 117.76 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 32.33 | 0.00 | 32.33 | 4.67 | 31.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 111.29 | 12.45 | 98.84 | 155.26 | 218.10 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 12.74 | 0.00 | 12.74 | 2.05 | 70.48 | 0.00 | 0.00 | 0.00 |
February | 16.01 | 0.00 | 16.01 | 2.45 | 72.07 | 0.00 | 0.00 | 0.00 |
March | 21.79 | 0.00 | 21.79 | 9.42 | 53.85 | 0.00 | 0.00 | 0.00 |
April | 27.39 | 0.18 | 27.21 | 15.27 | 45.68 | 0.00 | 0.00 | 0.00 |
May | 37.42 | 1.25 | 36.16 | 35.66 | 24.72 | 0.00 | 0.00 | 0.00 |
June | 41.03 | 4.59 | 36.44 | 57.23 | 12.43 | 0.00 | 0.00 | 0.00 |
July | 38.91 | 2.66 | 36.26 | 55.05 | 11.53 | 0.00 | 0.00 | 0.00 |
August | 30.98 | 0.84 | 30.14 | 41.63 | 13.76 | 0.00 | 0.00 | 0.00 |
September | 25.94 | 0.02 | 25.92 | 30.47 | 23.02 | 0.00 | 0.00 | 0.00 |
October | 18.56 | 0.00 | 18.56 | 10.00 | 51.91 | 0.00 | 0.00 | 0.00 |
November | 14.09 | 0.00 | 14.09 | 3.49 | 62.88 | 0.00 | 0.00 | 0.00 |
December | 11.92 | 0.00 | 11.92 | 1.72 | 80.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 24.78 | 0.80 | 23.98 | 22.15 | 43.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 11.92 | 0.00 | 11.92 | 1.72 | 11.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 41.03 | 4.59 | 36.44 | 57.23 | 80.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 122.45 | 100.80 | 21.65 | 142.69 | 59.40 | 0.00 | 0.00 | 0.00 |
February | 115.87 | 92.13 | 23.74 | 133.36 | 63.14 | 0.00 | 0.00 | 0.00 |
March | 87.04 | 57.52 | 29.51 | 101.23 | 50.68 | 0.00 | 0.00 | 0.00 |
April | 56.99 | 23.58 | 33.41 | 60.74 | 45.89 | 0.00 | 0.00 | 0.00 |
May | 51.79 | 9.96 | 41.83 | 61.37 | 26.70 | 0.00 | 0.00 | 0.00 |
June | 47.08 | 8.50 | 38.59 | 70.43 | 13.68 | 0.00 | 0.00 | 0.00 |
July | 48.63 | 8.28 | 40.35 | 72.90 | 12.33 | 0.00 | 0.00 | 0.00 |
August | 61.88 | 25.46 | 36.42 | 92.29 | 14.27 | 0.00 | 0.00 | 0.00 |
September | 81.28 | 45.69 | 35.59 | 112.75 | 22.64 | 0.00 | 0.00 | 0.00 |
October | 95.95 | 67.98 | 27.97 | 118.20 | 49.36 | 0.00 | 0.00 | 0.00 |
November | 117.60 | 93.80 | 23.80 | 140.69 | 56.04 | 0.00 | 0.00 | 0.00 |
December | 112.23 | 90.86 | 21.38 | 127.18 | 68.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 83.05 | 51.82 | 31.23 | 102.64 | 40.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 47.08 | 8.28 | 21.38 | 60.74 | 12.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 122.45 | 100.80 | 41.83 | 142.69 | 68.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 332.36 | 273.60 | 58.76 | 387.30 | 161.23 | 0.00 | 0.00 | 0.00 |
February | 314.49 | 250.06 | 64.44 | 361.96 | 171.39 | 0.00 | 0.00 | 0.00 |
March | 236.24 | 156.13 | 80.11 | 274.75 | 137.55 | 0.00 | 0.00 | 0.00 |
April | 154.69 | 63.99 | 90.69 | 164.86 | 124.55 | 0.00 | 0.00 | 0.00 |
May | 140.56 | 27.03 | 113.53 | 166.57 | 72.48 | 0.00 | 0.00 | 0.00 |
June | 127.80 | 23.07 | 104.73 | 191.17 | 37.14 | 0.00 | 0.00 | 0.00 |
July | 132.00 | 22.49 | 109.51 | 197.87 | 33.48 | 0.00 | 0.00 | 0.00 |
August | 167.95 | 69.10 | 98.86 | 250.48 | 38.73 | 0.00 | 0.00 | 0.00 |
September | 220.62 | 124.01 | 96.61 | 306.02 | 61.45 | 0.00 | 0.00 | 0.00 |
October | 260.42 | 184.52 | 75.90 | 320.82 | 133.99 | 0.00 | 0.00 | 0.00 |
November | 319.20 | 254.60 | 64.60 | 381.87 | 152.11 | 0.00 | 0.00 | 0.00 |
December | 304.63 | 246.60 | 58.02 | 345.20 | 186.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 225.41 | 140.64 | 84.76 | 278.59 | 108.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 127.80 | 22.49 | 58.02 | 164.86 | 33.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 332.36 | 273.60 | 113.53 | 387.30 | 186.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 262.44 | 216.04 | 46.40 | 303.45 | 121.28 | 0.00 | 0.00 | 0.00 |
February | 248.33 | 197.45 | 50.88 | 282.63 | 129.54 | 0.00 | 0.00 | 0.00 |
March | 186.54 | 123.28 | 63.25 | 214.59 | 102.00 | 0.00 | 0.00 | 0.00 |
April | 122.14 | 50.53 | 71.61 | 128.14 | 92.42 | 0.00 | 0.00 | 0.00 |
May | 110.99 | 21.34 | 89.65 | 129.84 | 51.32 | 0.00 | 0.00 | 0.00 |
June | 100.91 | 18.22 | 82.70 | 151.29 | 22.37 | 0.00 | 0.00 | 0.00 |
July | 104.23 | 17.76 | 86.47 | 158.01 | 18.91 | 0.00 | 0.00 | 0.00 |
August | 132.62 | 54.56 | 78.06 | 198.12 | 22.66 | 0.00 | 0.00 | 0.00 |
September | 174.20 | 97.92 | 76.28 | 241.60 | 39.58 | 0.00 | 0.00 | 0.00 |
October | 205.63 | 145.70 | 59.94 | 251.86 | 96.68 | 0.00 | 0.00 | 0.00 |
November | 252.05 | 201.04 | 51.01 | 298.77 | 113.69 | 0.00 | 0.00 | 0.00 |
December | 240.54 | 194.72 | 45.82 | 270.45 | 141.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 177.99 | 111.06 | 66.93 | 218.70 | 79.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 100.91 | 17.76 | 45.82 | 128.14 | 18.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 262.44 | 216.04 | 89.65 | 303.45 | 141.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 169.84 | 107.64 | 62.20 | 157.44 | 249.74 | 0.00 | 0.00 | 0.00 |
February | 205.18 | 127.28 | 77.90 | 187.26 | 258.40 | 0.00 | 0.00 | 0.00 |
March | 239.27 | 131.80 | 107.47 | 236.66 | 193.22 | 0.00 | 0.00 | 0.00 |
April | 225.68 | 95.60 | 130.08 | 214.82 | 168.43 | 0.00 | 0.00 | 0.00 |
May | 275.93 | 97.45 | 178.48 | 319.42 | 92.99 | 0.00 | 0.00 | 0.00 |
June | 336.87 | 161.95 | 174.92 | 470.88 | 41.55 | 0.00 | 0.00 | 0.00 |
July | 274.17 | 100.11 | 174.07 | 388.97 | 35.17 | 0.00 | 0.00 | 0.00 |
August | 287.10 | 141.88 | 145.22 | 396.35 | 41.74 | 0.00 | 0.00 | 0.00 |
September | 255.45 | 122.90 | 132.55 | 335.39 | 74.42 | 0.00 | 0.00 | 0.00 |
October | 213.91 | 122.27 | 91.65 | 231.03 | 185.38 | 0.00 | 0.00 | 0.00 |
November | 175.65 | 106.68 | 68.97 | 168.45 | 225.14 | 0.00 | 0.00 | 0.00 |
December | 141.66 | 83.65 | 58.01 | 118.43 | 287.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 233.46 | 116.46 | 117.01 | 269.11 | 153.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 141.66 | 83.65 | 58.01 | 118.43 | 35.17 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 336.87 | 161.95 | 178.48 | 470.88 | 287.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.28 | 0.00 | 27.28 | 5.74 | 138.04 | 0.00 | 0.00 | 0.00 |
February | 34.29 | 0.00 | 34.29 | 6.59 | 143.63 | 0.00 | 0.00 | 0.00 |
March | 46.67 | 0.00 | 46.67 | 21.06 | 107.66 | 0.00 | 0.00 | 0.00 |
April | 58.67 | 0.38 | 58.29 | 32.11 | 91.85 | 0.00 | 0.00 | 0.00 |
May | 80.15 | 2.69 | 77.46 | 74.33 | 49.10 | 0.00 | 0.00 | 0.00 |
June | 87.88 | 9.83 | 78.05 | 121.81 | 22.81 | 0.00 | 0.00 | 0.00 |
July | 83.35 | 5.69 | 77.66 | 118.38 | 19.94 | 0.00 | 0.00 | 0.00 |
August | 66.36 | 1.80 | 64.56 | 89.46 | 24.13 | 0.00 | 0.00 | 0.00 |
September | 55.56 | 0.04 | 55.52 | 66.42 | 42.59 | 0.00 | 0.00 | 0.00 |
October | 39.75 | 0.00 | 39.75 | 23.00 | 100.84 | 0.00 | 0.00 | 0.00 |
November | 30.18 | 0.00 | 30.18 | 8.97 | 123.29 | 0.00 | 0.00 | 0.00 |
December | 25.53 | 0.00 | 25.53 | 4.76 | 159.65 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 53.07 | 1.71 | 51.36 | 47.95 | 84.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.53 | 0.00 | 25.53 | 4.76 | 19.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 87.88 | 9.83 | 78.05 | 121.81 | 159.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 169.84 | 107.64 | 62.20 | 164.99 | 243.60 | 0.00 | 0.00 | 0.00 |
February | 205.18 | 127.28 | 77.90 | 194.87 | 253.26 | 0.00 | 0.00 | 0.00 |
March | 239.27 | 131.80 | 107.47 | 241.04 | 191.65 | 0.00 | 0.00 | 0.00 |
April | 225.68 | 95.60 | 130.08 | 216.58 | 168.36 | 0.00 | 0.00 | 0.00 |
May | 275.93 | 97.45 | 178.48 | 317.34 | 95.81 | 0.00 | 0.00 | 0.00 |
June | 336.87 | 161.95 | 174.92 | 467.38 | 45.61 | 0.00 | 0.00 | 0.00 |
July | 274.17 | 100.11 | 174.07 | 385.23 | 38.87 | 0.00 | 0.00 | 0.00 |
August | 287.10 | 141.88 | 145.22 | 394.93 | 45.69 | 0.00 | 0.00 | 0.00 |
September | 255.45 | 122.90 | 132.55 | 336.23 | 78.35 | 0.00 | 0.00 | 0.00 |
October | 213.91 | 122.27 | 91.65 | 235.30 | 183.90 | 0.00 | 0.00 | 0.00 |
November | 175.65 | 106.68 | 68.97 | 175.59 | 220.15 | 0.00 | 0.00 | 0.00 |
December | 141.66 | 83.65 | 58.01 | 124.67 | 281.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 233.46 | 116.46 | 117.01 | 271.50 | 153.39 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 141.66 | 83.65 | 58.01 | 124.67 | 38.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 336.87 | 161.95 | 178.48 | 467.38 | 281.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 384.89 | 316.84 | 68.05 | 437.52 | 184.29 | 0.00 | 0.00 | 0.00 |
February | 364.20 | 289.58 | 74.62 | 408.05 | 195.71 | 0.00 | 0.00 | 0.00 |
March | 273.57 | 180.80 | 92.77 | 311.10 | 152.72 | 0.00 | 0.00 | 0.00 |
April | 179.14 | 74.11 | 105.03 | 186.09 | 137.62 | 0.00 | 0.00 | 0.00 |
May | 162.78 | 31.30 | 131.48 | 191.43 | 74.82 | 0.00 | 0.00 | 0.00 |
June | 148.00 | 26.72 | 121.28 | 226.57 | 30.96 | 0.00 | 0.00 | 0.00 |
July | 152.86 | 26.04 | 126.82 | 235.04 | 26.49 | 0.00 | 0.00 | 0.00 |
August | 194.50 | 80.02 | 114.48 | 292.91 | 32.04 | 0.00 | 0.00 | 0.00 |
September | 255.49 | 143.61 | 111.88 | 353.95 | 57.91 | 0.00 | 0.00 | 0.00 |
October | 301.58 | 213.68 | 87.90 | 365.99 | 145.39 | 0.00 | 0.00 | 0.00 |
November | 369.65 | 294.84 | 74.81 | 431.71 | 172.74 | 0.00 | 0.00 | 0.00 |
December | 352.77 | 285.58 | 67.19 | 388.69 | 214.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 261.03 | 162.87 | 98.16 | 318.57 | 118.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 148.00 | 26.04 | 67.19 | 186.09 | 26.49 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 384.89 | 316.84 | 131.48 | 437.52 | 214.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 190.98 | 0.00 | 190.98 | 22.17 | 1142.73 | 0.00 | 0.00 | 0.00 |
February | 240.04 | 0.00 | 240.04 | 27.23 | 1181.05 | 0.00 | 0.00 | 0.00 |
March | 326.71 | 0.02 | 326.69 | 116.17 | 890.78 | 0.00 | 0.00 | 0.00 |
April | 410.70 | 2.69 | 408.01 | 189.17 | 774.59 | 0.00 | 0.00 | 0.00 |
May | 561.03 | 18.82 | 542.22 | 484.46 | 404.62 | 0.00 | 0.00 | 0.00 |
June | 615.11 | 68.79 | 546.32 | 836.30 | 192.20 | 0.00 | 0.00 | 0.00 |
July | 583.42 | 39.82 | 543.59 | 808.10 | 177.77 | 0.00 | 0.00 | 0.00 |
August | 464.51 | 12.57 | 451.94 | 608.83 | 210.50 | 0.00 | 0.00 | 0.00 |
September | 388.93 | 0.31 | 388.62 | 442.97 | 352.89 | 0.00 | 0.00 | 0.00 |
October | 278.26 | 0.00 | 278.26 | 134.23 | 832.37 | 0.00 | 0.00 | 0.00 |
November | 211.23 | 0.00 | 211.23 | 41.56 | 1028.08 | 0.00 | 0.00 | 0.00 |
December | 178.68 | 0.00 | 178.68 | 18.01 | 1314.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 371.48 | 11.95 | 359.53 | 312.37 | 705.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 178.68 | 0.00 | 178.68 | 18.01 | 177.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 615.11 | 68.79 | 546.32 | 836.30 | 1314.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 190.98 | 0.00 | 190.98 | 19.48 | 1166.96 | 0.00 | 0.00 | 0.00 |
February | 240.04 | 0.00 | 240.04 | 24.80 | 1206.61 | 0.00 | 0.00 | 0.00 |
March | 326.71 | 0.02 | 326.69 | 110.12 | 910.03 | 0.00 | 0.00 | 0.00 |
April | 410.70 | 2.69 | 408.01 | 181.67 | 791.62 | 0.00 | 0.00 | 0.00 |
May | 561.03 | 18.82 | 542.22 | 475.56 | 412.52 | 0.00 | 0.00 | 0.00 |
June | 615.11 | 68.79 | 546.32 | 828.88 | 196.94 | 0.00 | 0.00 | 0.00 |
July | 583.42 | 39.82 | 543.59 | 800.90 | 182.67 | 0.00 | 0.00 | 0.00 |
August | 464.51 | 12.57 | 451.94 | 602.26 | 216.13 | 0.00 | 0.00 | 0.00 |
September | 388.93 | 0.31 | 388.62 | 437.00 | 360.40 | 0.00 | 0.00 | 0.00 |
October | 278.26 | 0.00 | 278.26 | 129.06 | 848.28 | 0.00 | 0.00 | 0.00 |
November | 211.23 | 0.00 | 211.23 | 38.76 | 1050.17 | 0.00 | 0.00 | 0.00 |
December | 178.68 | 0.00 | 178.68 | 16.11 | 1343.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 371.48 | 11.95 | 359.53 | 306.96 | 721.18 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 178.68 | 0.00 | 178.68 | 16.11 | 182.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 615.11 | 68.79 | 546.32 | 828.88 | 1343.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.28 | 0.00 | 27.28 | 7.25 | 142.46 | 0.00 | 0.00 | 0.00 |
February | 34.29 | 0.00 | 34.29 | 8.02 | 150.41 | 0.00 | 0.00 | 0.00 |
March | 46.67 | 0.00 | 46.67 | 25.32 | 114.25 | 0.00 | 0.00 | 0.00 |
April | 58.67 | 0.38 | 58.29 | 38.28 | 100.10 | 0.00 | 0.00 | 0.00 |
May | 80.15 | 2.69 | 77.46 | 91.53 | 54.88 | 0.00 | 0.00 | 0.00 |
June | 87.88 | 9.83 | 78.05 | 146.14 | 27.29 | 0.00 | 0.00 | 0.00 |
July | 83.35 | 5.69 | 77.66 | 141.83 | 25.16 | 0.00 | 0.00 | 0.00 |
August | 66.36 | 1.80 | 64.56 | 111.88 | 28.43 | 0.00 | 0.00 | 0.00 |
September | 55.56 | 0.04 | 55.52 | 83.94 | 45.40 | 0.00 | 0.00 | 0.00 |
October | 39.75 | 0.00 | 39.75 | 29.50 | 105.40 | 0.00 | 0.00 | 0.00 |
November | 30.18 | 0.00 | 30.18 | 11.60 | 128.14 | 0.00 | 0.00 | 0.00 |
December | 25.53 | 0.00 | 25.53 | 5.42 | 168.02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 53.07 | 1.71 | 51.36 | 58.68 | 90.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.53 | 0.00 | 25.53 | 5.42 | 25.16 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 87.88 | 9.83 | 78.05 | 146.14 | 168.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 317.98 | 194.49 | 123.49 | 301.45 | 495.18 | 0.00 | 0.00 | 0.00 |
February | 426.28 | 269.79 | 156.49 | 419.21 | 530.23 | 0.00 | 0.00 | 0.00 |
March | 513.51 | 299.74 | 213.77 | 550.52 | 404.67 | 0.00 | 0.00 | 0.00 |
April | 524.20 | 255.31 | 268.89 | 555.55 | 363.62 | 0.00 | 0.00 | 0.00 |
May | 614.54 | 257.27 | 357.27 | 777.99 | 203.76 | 0.00 | 0.00 | 0.00 |
June | 747.77 | 392.46 | 355.32 | 1124.03 | 102.26 | 0.00 | 0.00 | 0.00 |
July | 678.74 | 322.53 | 356.21 | 1040.08 | 94.30 | 0.00 | 0.00 | 0.00 |
August | 686.30 | 378.12 | 308.19 | 1035.68 | 105.90 | 0.00 | 0.00 | 0.00 |
September | 571.97 | 310.91 | 261.06 | 822.53 | 164.02 | 0.00 | 0.00 | 0.00 |
October | 413.90 | 227.00 | 186.90 | 478.72 | 383.15 | 0.00 | 0.00 | 0.00 |
November | 321.19 | 181.00 | 140.18 | 324.14 | 456.95 | 0.00 | 0.00 | 0.00 |
December | 278.56 | 160.52 | 118.04 | 244.87 | 592.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 508.22 | 270.61 | 237.60 | 640.64 | 323.59 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 278.56 | 160.52 | 118.04 | 244.87 | 94.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 747.77 | 392.46 | 357.27 | 1124.03 | 592.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 262.44 | 216.04 | 46.40 | 315.26 | 124.43 | 0.00 | 0.00 | 0.00 |
February | 248.33 | 197.45 | 50.88 | 293.20 | 135.09 | 0.00 | 0.00 | 0.00 |
March | 186.54 | 123.28 | 63.25 | 225.04 | 108.66 | 0.00 | 0.00 | 0.00 |
April | 122.14 | 50.53 | 71.61 | 136.87 | 100.72 | 0.00 | 0.00 | 0.00 |
May | 110.99 | 21.34 | 89.65 | 146.72 | 58.49 | 0.00 | 0.00 | 0.00 |
June | 100.91 | 18.22 | 82.70 | 173.79 | 29.30 | 0.00 | 0.00 | 0.00 |
July | 104.23 | 17.76 | 86.47 | 179.65 | 26.34 | 0.00 | 0.00 | 0.00 |
August | 132.62 | 54.56 | 78.06 | 220.48 | 29.09 | 0.00 | 0.00 | 0.00 |
September | 174.20 | 97.92 | 76.28 | 261.57 | 45.26 | 0.00 | 0.00 | 0.00 |
October | 205.63 | 145.70 | 59.94 | 265.08 | 101.59 | 0.00 | 0.00 | 0.00 |
November | 252.05 | 201.04 | 51.01 | 310.66 | 117.33 | 0.00 | 0.00 | 0.00 |
December | 240.54 | 194.72 | 45.82 | 278.45 | 147.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 177.99 | 111.06 | 66.93 | 233.55 | 85.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 100.91 | 17.76 | 45.82 | 136.87 | 26.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 262.44 | 216.04 | 89.65 | 315.26 | 147.10 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.55 | 0.00 | 34.55 | 4.84 | 192.19 | 0.00 | 0.00 | 0.00 |
February | 43.43 | 0.00 | 43.43 | 5.64 | 197.96 | 0.00 | 0.00 | 0.00 |
March | 59.11 | 0.00 | 59.11 | 23.28 | 147.26 | 0.00 | 0.00 | 0.00 |
April | 74.31 | 0.49 | 73.82 | 38.59 | 125.75 | 0.00 | 0.00 | 0.00 |
May | 101.51 | 3.40 | 98.10 | 92.60 | 68.37 | 0.00 | 0.00 | 0.00 |
June | 111.29 | 12.45 | 98.84 | 151.37 | 34.77 | 0.00 | 0.00 | 0.00 |
July | 105.56 | 7.21 | 98.35 | 146.05 | 32.16 | 0.00 | 0.00 | 0.00 |
August | 84.04 | 2.27 | 81.77 | 109.77 | 38.17 | 0.00 | 0.00 | 0.00 |
September | 70.37 | 0.06 | 70.31 | 80.33 | 62.37 | 0.00 | 0.00 | 0.00 |
October | 50.34 | 0.00 | 50.34 | 25.34 | 140.68 | 0.00 | 0.00 | 0.00 |
November | 38.22 | 0.00 | 38.22 | 8.20 | 172.08 | 0.00 | 0.00 | 0.00 |
December | 32.33 | 0.00 | 32.33 | 3.91 | 221.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 67.21 | 2.16 | 65.05 | 57.79 | 118.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 32.33 | 0.00 | 32.33 | 3.91 | 32.16 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 111.29 | 12.45 | 98.84 | 151.37 | 221.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.91 | 0.00 | 30.91 | 4.33 | 171.93 | 0.00 | 0.00 | 0.00 |
February | 38.86 | 0.00 | 38.86 | 5.05 | 177.12 | 0.00 | 0.00 | 0.00 |
March | 52.89 | 0.00 | 52.88 | 20.82 | 131.75 | 0.00 | 0.00 | 0.00 |
April | 66.48 | 0.44 | 66.05 | 34.52 | 112.51 | 0.00 | 0.00 | 0.00 |
May | 90.82 | 3.05 | 87.77 | 82.85 | 61.17 | 0.00 | 0.00 | 0.00 |
June | 99.57 | 11.13 | 88.44 | 135.43 | 31.11 | 0.00 | 0.00 | 0.00 |
July | 94.44 | 6.45 | 87.99 | 130.67 | 28.78 | 0.00 | 0.00 | 0.00 |
August | 75.19 | 2.03 | 73.16 | 98.21 | 34.15 | 0.00 | 0.00 | 0.00 |
September | 62.96 | 0.05 | 62.91 | 71.87 | 55.81 | 0.00 | 0.00 | 0.00 |
October | 45.04 | 0.00 | 45.04 | 22.67 | 125.87 | 0.00 | 0.00 | 0.00 |
November | 34.19 | 0.00 | 34.19 | 7.34 | 153.96 | 0.00 | 0.00 | 0.00 |
December | 28.92 | 0.00 | 28.92 | 3.50 | 197.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 60.13 | 1.93 | 58.20 | 51.70 | 106.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 28.92 | 0.00 | 28.92 | 3.50 | 28.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 99.57 | 11.13 | 88.44 | 135.43 | 197.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 979.75 | 806.53 | 173.22 | 1131.74 | 475.59 | 0.00 | 0.00 | 0.00 |
February | 927.09 | 737.13 | 189.95 | 1054.54 | 509.83 | 0.00 | 0.00 | 0.00 |
March | 696.40 | 460.25 | 236.15 | 798.40 | 408.87 | 0.00 | 0.00 | 0.00 |
April | 456.00 | 188.65 | 267.36 | 475.33 | 373.38 | 0.00 | 0.00 | 0.00 |
May | 414.37 | 79.68 | 334.68 | 478.13 | 218.56 | 0.00 | 0.00 | 0.00 |
June | 376.73 | 68.01 | 308.73 | 551.47 | 112.95 | 0.00 | 0.00 | 0.00 |
July | 389.12 | 66.29 | 322.83 | 572.83 | 101.56 | 0.00 | 0.00 | 0.00 |
August | 495.10 | 203.69 | 291.41 | 727.11 | 116.83 | 0.00 | 0.00 | 0.00 |
September | 650.36 | 365.56 | 284.79 | 892.12 | 181.46 | 0.00 | 0.00 | 0.00 |
October | 767.69 | 543.93 | 223.76 | 936.90 | 394.71 | 0.00 | 0.00 | 0.00 |
November | 940.97 | 750.54 | 190.43 | 1114.34 | 450.77 | 0.00 | 0.00 | 0.00 |
December | 898.00 | 726.96 | 171.04 | 1005.94 | 555.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 664.48 | 414.60 | 249.87 | 810.16 | 323.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 376.73 | 66.29 | 171.04 | 475.33 | 101.56 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 979.75 | 806.53 | 334.68 | 1131.74 | 555.63 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.355512E+10 | 0.292657E+10 | 0.628553E+09 | 0.405805E+10 | 0.167278E+10 |
February | 0.303846E+10 | 0.241591E+10 | 0.622550E+09 | 0.343598E+10 | 0.158310E+10 |
March | 0.252694E+10 | 0.167006E+10 | 0.856880E+09 | 0.289037E+10 | 0.139370E+10 |
April | 0.160126E+10 | 0.662442E+09 | 0.938820E+09 | 0.167913E+10 | 0.120661E+10 |
May | 0.150356E+10 | 0.289137E+09 | 0.121442E+10 | 0.175326E+10 | 0.720374E+09 |
June | 0.132290E+10 | 0.238808E+09 | 0.108409E+10 | 0.192528E+10 | 0.375821E+09 |
July | 0.141194E+10 | 0.240535E+09 | 0.117141E+10 | 0.206505E+10 | 0.346820E+09 |
August | 0.179651E+10 | 0.739105E+09 | 0.105741E+10 | 0.262387E+10 | 0.405524E+09 |
September | 0.228374E+10 | 0.128369E+10 | 0.100006E+10 | 0.311273E+10 | 0.616868E+09 |
October | 0.278564E+10 | 0.197372E+10 | 0.811921E+09 | 0.337587E+10 | 0.135373E+10 |
November | 0.330425E+10 | 0.263556E+10 | 0.668687E+09 | 0.387376E+10 | 0.151812E+10 |
December | 0.325847E+10 | 0.263783E+10 | 0.620648E+09 | 0.363872E+10 | 0.190452E+10 |
Annual Sum or Average | 0.283888E+11 | 0.177134E+11 | 0.106754E+11 | 0.344321E+11 | 0.130980E+11 |
Minimum of Months | 0.132290E+10 | 0.238808E+09 | 0.620648E+09 | 0.167913E+10 | 0.346820E+09 |
Maximum of Months | 0.355512E+10 | 0.292657E+10 | 0.121442E+10 | 0.405805E+10 | 0.190452E+10 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.100110E+11 | 0.824102E+10 | 0.176996E+10 | 0.113240E+11 | 0.497485E+10 |
February | 0.855611E+10 | 0.680305E+10 | 0.175306E+10 | 0.958594E+10 | 0.467396E+10 |
March | 0.711568E+10 | 0.470277E+10 | 0.241292E+10 | 0.804984E+10 | 0.414843E+10 |
April | 0.450905E+10 | 0.186539E+10 | 0.264366E+10 | 0.463799E+10 | 0.365058E+10 |
May | 0.423393E+10 | 0.814191E+09 | 0.341974E+10 | 0.480097E+10 | 0.223683E+10 |
June | 0.372520E+10 | 0.672467E+09 | 0.305273E+10 | 0.535229E+10 | 0.111548E+10 |
July | 0.397593E+10 | 0.677330E+09 | 0.329860E+10 | 0.574379E+10 | 0.103618E+10 |
August | 0.505886E+10 | 0.208127E+10 | 0.297759E+10 | 0.731748E+10 | 0.120630E+10 |
September | 0.643087E+10 | 0.361478E+10 | 0.281609E+10 | 0.869540E+10 | 0.182778E+10 |
October | 0.784417E+10 | 0.555786E+10 | 0.228632E+10 | 0.942975E+10 | 0.401965E+10 |
November | 0.930455E+10 | 0.742157E+10 | 0.188298E+10 | 0.108180E+11 | 0.451415E+10 |
December | 0.917565E+10 | 0.742794E+10 | 0.174770E+10 | 0.101498E+11 | 0.562156E+10 |
Annual Sum or Average | 0.799410E+11 | 0.498796E+11 | 0.300613E+11 | 0.959053E+11 | 0.390257E+11 |
Minimum of Months | 0.372520E+10 | 0.672467E+09 | 0.174770E+10 | 0.463799E+10 | 0.103618E+10 |
Maximum of Months | 0.100110E+11 | 0.824102E+10 | 0.341974E+10 | 0.113240E+11 | 0.562156E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.130048E+11 | 0.107055E+11 | 0.229928E+10 | 0.149274E+11 | 0.664494E+10 |
February | 0.111149E+11 | 0.883755E+10 | 0.227732E+10 | 0.126558E+11 | 0.626678E+10 |
March | 0.924368E+10 | 0.610916E+10 | 0.313452E+10 | 0.106355E+11 | 0.561320E+10 |
April | 0.585751E+10 | 0.242325E+10 | 0.343426E+10 | 0.612951E+10 | 0.499317E+10 |
May | 0.550012E+10 | 0.105768E+10 | 0.444243E+10 | 0.636307E+10 | 0.300262E+10 |
June | 0.483925E+10 | 0.873573E+09 | 0.396567E+10 | 0.713098E+10 | 0.146985E+10 |
July | 0.516496E+10 | 0.879891E+09 | 0.428507E+10 | 0.764669E+10 | 0.136277E+10 |
August | 0.657175E+10 | 0.270369E+10 | 0.386806E+10 | 0.971638E+10 | 0.157497E+10 |
September | 0.835407E+10 | 0.469580E+10 | 0.365826E+10 | 0.115119E+11 | 0.239671E+10 |
October | 0.101900E+11 | 0.721997E+10 | 0.297005E+10 | 0.124425E+11 | 0.539917E+10 |
November | 0.120871E+11 | 0.964104E+10 | 0.244610E+10 | 0.142674E+11 | 0.604483E+10 |
December | 0.119197E+11 | 0.964932E+10 | 0.227037E+10 | 0.133779E+11 | 0.754776E+10 |
Annual Sum or Average | 0.103848E+12 | 0.647965E+11 | 0.390514E+11 | 0.126805E+12 | 0.523168E+11 |
Minimum of Months | 0.483925E+10 | 0.873573E+09 | 0.227037E+10 | 0.612951E+10 | 0.136277E+10 |
Maximum of Months | 0.130048E+11 | 0.107055E+11 | 0.444243E+10 | 0.149274E+11 | 0.754776E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.702909E+09 | 0.578632E+09 | 0.124277E+09 | 0.814759E+09 | 0.326860E+09 |
February | 0.600757E+09 | 0.477667E+09 | 0.123090E+09 | 0.687114E+09 | 0.313697E+09 |
March | 0.499620E+09 | 0.330199E+09 | 0.169422E+09 | 0.577846E+09 | 0.274409E+09 |
April | 0.316599E+09 | 0.130976E+09 | 0.185623E+09 | 0.334474E+09 | 0.240627E+09 |
May | 0.297282E+09 | 57167386.18 | 0.240115E+09 | 0.350375E+09 | 0.138317E+09 |
June | 0.261563E+09 | 47216418.44 | 0.214346E+09 | 0.394805E+09 | 59370837.89 |
July | 0.279167E+09 | 47557874.28 | 0.231609E+09 | 0.425404E+09 | 52226647.90 |
August | 0.355204E+09 | 0.146134E+09 | 0.209070E+09 | 0.533874E+09 | 62286368.78 |
September | 0.451537E+09 | 0.253807E+09 | 0.197730E+09 | 0.629036E+09 | 0.104700E+09 |
October | 0.550770E+09 | 0.390238E+09 | 0.160532E+09 | 0.677117E+09 | 0.261069E+09 |
November | 0.653308E+09 | 0.521096E+09 | 0.132212E+09 | 0.777211E+09 | 0.296204E+09 |
December | 0.644257E+09 | 0.521543E+09 | 0.122714E+09 | 0.727194E+09 | 0.378427E+09 |
Annual Sum or Average | 0.561297E+10 | 0.350223E+10 | 0.211074E+10 | 0.692921E+10 | 0.250819E+10 |
Minimum of Months | 0.261563E+09 | 47216418.44 | 0.122714E+09 | 0.334474E+09 | 52226647.90 |
Maximum of Months | 0.702909E+09 | 0.578632E+09 | 0.240115E+09 | 0.814759E+09 | 0.378427E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.454908E+09 | 0.288304E+09 | 0.166604E+09 | 0.423404E+09 | 0.674757E+09 |
February | 0.496369E+09 | 0.307906E+09 | 0.188463E+09 | 0.456103E+09 | 0.626996E+09 |
March | 0.640872E+09 | 0.353023E+09 | 0.287849E+09 | 0.637961E+09 | 0.520510E+09 |
April | 0.584971E+09 | 0.247796E+09 | 0.337175E+09 | 0.560855E+09 | 0.439095E+09 |
May | 0.739057E+09 | 0.261015E+09 | 0.478041E+09 | 0.861427E+09 | 0.251107E+09 |
June | 0.873178E+09 | 0.419781E+09 | 0.453397E+09 | 0.122705E+10 | 0.110243E+09 |
July | 0.734347E+09 | 0.268122E+09 | 0.466225E+09 | 0.104686E+10 | 97122393.98 |
August | 0.768972E+09 | 0.380005E+09 | 0.388968E+09 | 0.106733E+10 | 0.114753E+09 |
September | 0.662115E+09 | 0.318550E+09 | 0.343565E+09 | 0.872889E+09 | 0.197033E+09 |
October | 0.572943E+09 | 0.327477E+09 | 0.245466E+09 | 0.621737E+09 | 0.501336E+09 |
November | 0.455288E+09 | 0.276523E+09 | 0.178766E+09 | 0.439050E+09 | 0.587705E+09 |
December | 0.379433E+09 | 0.224048E+09 | 0.155385E+09 | 0.318537E+09 | 0.772144E+09 |
Annual Sum or Average | 0.736245E+10 | 0.367255E+10 | 0.368990E+10 | 0.853320E+10 | 0.489280E+10 |
Minimum of Months | 0.379433E+09 | 0.224048E+09 | 0.155385E+09 | 0.318537E+09 | 97122393.98 |
Maximum of Months | 0.873178E+09 | 0.419781E+09 | 0.478041E+09 | 0.122705E+10 | 0.772144E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 73076084.28 | 0.00 | 73076084.28 | 14716036.27 | 0.373968E+09 |
February | 82959434.63 | 0.00 | 82959434.63 | 15716445.35 | 0.349252E+09 |
March | 0.125014E+09 | 6450.90 | 0.125007E+09 | 56456570.60 | 0.289639E+09 |
April | 0.152081E+09 | 996427.49 | 0.151084E+09 | 84150967.05 | 0.238858E+09 |
May | 0.214675E+09 | 7199804.69 | 0.207475E+09 | 0.201525E+09 | 0.131423E+09 |
June | 0.227774E+09 | 25471614.68 | 0.202303E+09 | 0.317937E+09 | 59457540.56 |
July | 0.223240E+09 | 15238426.74 | 0.208001E+09 | 0.318637E+09 | 54041867.70 |
August | 0.177740E+09 | 4810033.59 | 0.172930E+09 | 0.241223E+09 | 65317737.01 |
September | 0.144022E+09 | 115022.61 | 0.143907E+09 | 0.172322E+09 | 0.111712E+09 |
October | 0.106474E+09 | 0.00 | 0.106474E+09 | 61239277.49 | 0.272133E+09 |
November | 78220106.15 | 0.00 | 78220106.15 | 22865655.78 | 0.322633E+09 |
December | 68371746.70 | 0.00 | 68371746.70 | 12235579.14 | 0.430088E+09 |
Annual Sum or Average | 0.167365E+10 | 53837780.70 | 0.161981E+10 | 0.151903E+10 | 0.269852E+10 |
Minimum of Months | 68371746.70 | 0.00 | 68371746.70 | 12235579.14 | 54041867.70 |
Maximum of Months | 0.227774E+09 | 25471614.68 | 0.208001E+09 | 0.318637E+09 | 0.430088E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.454908E+09 | 0.288304E+09 | 0.166604E+09 | 0.441065E+09 | 0.658982E+09 |
February | 0.496369E+09 | 0.307906E+09 | 0.188463E+09 | 0.472670E+09 | 0.614932E+09 |
March | 0.640872E+09 | 0.353023E+09 | 0.287849E+09 | 0.648845E+09 | 0.515916E+09 |
April | 0.584971E+09 | 0.247796E+09 | 0.337175E+09 | 0.565505E+09 | 0.438259E+09 |
May | 0.739057E+09 | 0.261015E+09 | 0.478041E+09 | 0.857011E+09 | 0.256886E+09 |
June | 0.873178E+09 | 0.419781E+09 | 0.453397E+09 | 0.121840E+10 | 0.119324E+09 |
July | 0.734347E+09 | 0.268122E+09 | 0.466225E+09 | 0.103703E+10 | 0.105826E+09 |
August | 0.768972E+09 | 0.380005E+09 | 0.388968E+09 | 0.106359E+10 | 0.124041E+09 |
September | 0.662115E+09 | 0.318550E+09 | 0.343565E+09 | 0.874710E+09 | 0.205889E+09 |
October | 0.572943E+09 | 0.327477E+09 | 0.245466E+09 | 0.632008E+09 | 0.497101E+09 |
November | 0.455288E+09 | 0.276523E+09 | 0.178766E+09 | 0.455605E+09 | 0.575493E+09 |
December | 0.379433E+09 | 0.224048E+09 | 0.155385E+09 | 0.333631E+09 | 0.758238E+09 |
Annual Sum or Average | 0.736245E+10 | 0.367255E+10 | 0.368990E+10 | 0.860008E+10 | 0.487089E+10 |
Minimum of Months | 0.379433E+09 | 0.224048E+09 | 0.155385E+09 | 0.333631E+09 | 0.105826E+09 |
Maximum of Months | 0.873178E+09 | 0.419781E+09 | 0.478041E+09 | 0.121840E+10 | 0.758238E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.562215E+09 | 0.462814E+09 | 99401584.82 | 0.620502E+09 | 0.327059E+09 |
February | 0.480510E+09 | 0.382058E+09 | 98452499.34 | 0.525424E+09 | 0.298348E+09 |
March | 0.399617E+09 | 0.264106E+09 | 0.135510E+09 | 0.439496E+09 | 0.268534E+09 |
April | 0.253229E+09 | 0.104760E+09 | 0.148469E+09 | 0.246968E+09 | 0.249296E+09 |
May | 0.237778E+09 | 45724815.51 | 0.192054E+09 | 0.247982E+09 | 0.160735E+09 |
June | 0.209209E+09 | 37765624.19 | 0.171443E+09 | 0.282689E+09 | 85696620.97 |
July | 0.223289E+09 | 38038734.55 | 0.185251E+09 | 0.304139E+09 | 81894133.48 |
August | 0.284106E+09 | 0.116884E+09 | 0.167223E+09 | 0.394124E+09 | 93190664.96 |
September | 0.361158E+09 | 0.203005E+09 | 0.158153E+09 | 0.472621E+09 | 0.132148E+09 |
October | 0.440528E+09 | 0.312128E+09 | 0.128400E+09 | 0.516796E+09 | 0.270149E+09 |
November | 0.522542E+09 | 0.416794E+09 | 0.105749E+09 | 0.595917E+09 | 0.297322E+09 |
December | 0.515303E+09 | 0.417152E+09 | 98151340.49 | 0.558236E+09 | 0.357393E+09 |
Annual Sum or Average | 0.448949E+10 | 0.280123E+10 | 0.168826E+10 | 0.520489E+10 | 0.262177E+10 |
Minimum of Months | 0.209209E+09 | 37765624.19 | 98151340.49 | 0.246968E+09 | 81894133.48 |
Maximum of Months | 0.562215E+09 | 0.462814E+09 | 0.192054E+09 | 0.620502E+09 | 0.357393E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 58468616.74 | 0.00 | 58468616.74 | 11622669.06 | 0.305501E+09 |
February | 66376345.10 | 0.00 | 66376345.10 | 13025188.21 | 0.284206E+09 |
March | 0.100024E+09 | 5161.40 | 0.100019E+09 | 47730092.75 | 0.233372E+09 |
April | 0.121681E+09 | 797247.66 | 0.120884E+09 | 69946737.03 | 0.194096E+09 |
May | 0.171763E+09 | 5760607.25 | 0.166002E+09 | 0.169309E+09 | 0.103323E+09 |
June | 0.182244E+09 | 20379992.87 | 0.161864E+09 | 0.266974E+09 | 43401683.53 |
July | 0.178615E+09 | 12192357.35 | 0.166423E+09 | 0.265865E+09 | 39756717.33 |
August | 0.142211E+09 | 3848536.95 | 0.138363E+09 | 0.204775E+09 | 47345454.72 |
September | 0.115233E+09 | 92030.28 | 0.115141E+09 | 0.146826E+09 | 83790069.39 |
October | 85190674.52 | 0.00 | 85190674.52 | 52924065.09 | 0.217997E+09 |
November | 62584379.74 | 0.00 | 62584379.74 | 18745486.29 | 0.262637E+09 |
December | 54704647.81 | 0.00 | 54704647.81 | 9406108.45 | 0.354071E+09 |
Annual Sum or Average | 0.133910E+10 | 43075933.76 | 0.129602E+10 | 0.127715E+10 | 0.216950E+10 |
Minimum of Months | 54704647.81 | 0.00 | 54704647.81 | 9406108.45 | 39756717.33 |
Maximum of Months | 0.182244E+09 | 20379992.87 | 0.166423E+09 | 0.266974E+09 | 0.354071E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.425875E+09 | 0.260481E+09 | 0.165394E+09 | 0.370563E+09 | 0.663514E+09 |
February | 0.515669E+09 | 0.326363E+09 | 0.189306E+09 | 0.477872E+09 | 0.624728E+09 |
March | 0.687736E+09 | 0.401434E+09 | 0.286302E+09 | 0.690688E+09 | 0.510686E+09 |
April | 0.679412E+09 | 0.330906E+09 | 0.348505E+09 | 0.675503E+09 | 0.429661E+09 |
May | 0.823047E+09 | 0.344559E+09 | 0.478488E+09 | 0.956513E+09 | 0.236646E+09 |
June | 0.969184E+09 | 0.508660E+09 | 0.460524E+09 | 0.134766E+10 | 0.100200E+09 |
July | 0.909035E+09 | 0.431962E+09 | 0.477073E+09 | 0.128120E+10 | 91310450.37 |
August | 0.919162E+09 | 0.506410E+09 | 0.412753E+09 | 0.127407E+10 | 0.110508E+09 |
September | 0.741328E+09 | 0.402965E+09 | 0.338362E+09 | 0.968729E+09 | 0.186425E+09 |
October | 0.554336E+09 | 0.304019E+09 | 0.250317E+09 | 0.584736E+09 | 0.491155E+09 |
November | 0.416289E+09 | 0.234599E+09 | 0.181690E+09 | 0.384334E+09 | 0.584044E+09 |
December | 0.373075E+09 | 0.214985E+09 | 0.158090E+09 | 0.305246E+09 | 0.768291E+09 |
Annual Sum or Average | 0.801415E+10 | 0.426734E+10 | 0.374681E+10 | 0.931712E+10 | 0.479717E+10 |
Minimum of Months | 0.373075E+09 | 0.214985E+09 | 0.158090E+09 | 0.305246E+09 | 91310450.37 |
Maximum of Months | 0.969184E+09 | 0.508660E+09 | 0.478488E+09 | 0.134766E+10 | 0.768291E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.702909E+09 | 0.578632E+09 | 0.124277E+09 | 0.813284E+09 | 0.325499E+09 |
February | 0.600757E+09 | 0.477667E+09 | 0.123090E+09 | 0.684689E+09 | 0.312292E+09 |
March | 0.499620E+09 | 0.330199E+09 | 0.169422E+09 | 0.573956E+09 | 0.273062E+09 |
April | 0.316599E+09 | 0.130976E+09 | 0.185623E+09 | 0.330436E+09 | 0.240326E+09 |
May | 0.297282E+09 | 57167386.18 | 0.240115E+09 | 0.347038E+09 | 0.137818E+09 |
June | 0.261563E+09 | 47216418.44 | 0.214346E+09 | 0.391804E+09 | 58152596.80 |
July | 0.279167E+09 | 47557874.28 | 0.231609E+09 | 0.421402E+09 | 51751314.61 |
August | 0.355204E+09 | 0.146134E+09 | 0.209070E+09 | 0.530322E+09 | 61773504.09 |
September | 0.451537E+09 | 0.253807E+09 | 0.197730E+09 | 0.626382E+09 | 0.103933E+09 |
October | 0.550770E+09 | 0.390238E+09 | 0.160532E+09 | 0.675487E+09 | 0.259791E+09 |
November | 0.653308E+09 | 0.521096E+09 | 0.132212E+09 | 0.776257E+09 | 0.294698E+09 |
December | 0.644257E+09 | 0.521543E+09 | 0.122714E+09 | 0.725861E+09 | 0.377297E+09 |
Annual Sum or Average | 0.561297E+10 | 0.350223E+10 | 0.211074E+10 | 0.689692E+10 | 0.249639E+10 |
Minimum of Months | 0.261563E+09 | 47216418.44 | 0.122714E+09 | 0.330436E+09 | 51751314.61 |
Maximum of Months | 0.702909E+09 | 0.578632E+09 | 0.240115E+09 | 0.813284E+09 | 0.377297E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 73076084.28 | 0.00 | 73076084.28 | 13848110.63 | 0.372284E+09 |
February | 82959434.63 | 0.00 | 82959434.63 | 13806962.52 | 0.348261E+09 |
March | 0.125014E+09 | 6450.90 | 0.125007E+09 | 53207462.89 | 0.288319E+09 |
April | 0.152081E+09 | 996427.49 | 0.151084E+09 | 80392319.69 | 0.238249E+09 |
May | 0.214675E+09 | 7199804.69 | 0.207475E+09 | 0.198217E+09 | 0.130098E+09 |
June | 0.227774E+09 | 25471614.68 | 0.202303E+09 | 0.311304E+09 | 58192183.09 |
July | 0.223240E+09 | 15238426.74 | 0.208001E+09 | 0.311522E+09 | 53583450.21 |
August | 0.177740E+09 | 4810033.59 | 0.172930E+09 | 0.234333E+09 | 64552652.47 |
September | 0.144022E+09 | 115022.61 | 0.143907E+09 | 0.168545E+09 | 0.109990E+09 |
October | 0.106474E+09 | 0.00 | 0.106474E+09 | 59026969.43 | 0.269503E+09 |
November | 78220106.15 | 0.00 | 78220106.15 | 21366420.22 | 0.320269E+09 |
December | 68371746.70 | 0.00 | 68371746.70 | 11325576.53 | 0.428510E+09 |
Annual Sum or Average | 0.167365E+10 | 53837780.70 | 0.161981E+10 | 0.147690E+10 | 0.268181E+10 |
Minimum of Months | 68371746.70 | 0.00 | 68371746.70 | 11325576.53 | 53583450.21 |
Maximum of Months | 0.227774E+09 | 25471614.68 | 0.208001E+09 | 0.311522E+09 | 0.428510E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.425875E+09 | 0.260481E+09 | 0.165394E+09 | 0.382722E+09 | 0.639714E+09 |
February | 0.515669E+09 | 0.326363E+09 | 0.189306E+09 | 0.488950E+09 | 0.606379E+09 |
March | 0.687736E+09 | 0.401434E+09 | 0.286302E+09 | 0.701632E+09 | 0.504143E+09 |
April | 0.679412E+09 | 0.330906E+09 | 0.348505E+09 | 0.680883E+09 | 0.427801E+09 |
May | 0.823047E+09 | 0.344559E+09 | 0.478488E+09 | 0.953830E+09 | 0.241850E+09 |
June | 0.969184E+09 | 0.508660E+09 | 0.460524E+09 | 0.133177E+10 | 0.109571E+09 |
July | 0.909035E+09 | 0.431962E+09 | 0.477073E+09 | 0.126533E+10 | 0.100344E+09 |
August | 0.919162E+09 | 0.506410E+09 | 0.412753E+09 | 0.126417E+10 | 0.120006E+09 |
September | 0.741328E+09 | 0.402965E+09 | 0.338362E+09 | 0.968922E+09 | 0.193713E+09 |
October | 0.554336E+09 | 0.304019E+09 | 0.250317E+09 | 0.595709E+09 | 0.485231E+09 |
November | 0.416289E+09 | 0.234599E+09 | 0.181690E+09 | 0.396613E+09 | 0.565693E+09 |
December | 0.373075E+09 | 0.214985E+09 | 0.158090E+09 | 0.315927E+09 | 0.747760E+09 |
Annual Sum or Average | 0.801415E+10 | 0.426734E+10 | 0.374681E+10 | 0.934646E+10 | 0.474221E+10 |
Minimum of Months | 0.373075E+09 | 0.214985E+09 | 0.158090E+09 | 0.315927E+09 | 0.100344E+09 |
Maximum of Months | 0.969184E+09 | 0.508660E+09 | 0.478488E+09 | 0.133177E+10 | 0.747760E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 92546249.89 | 0.00 | 92546249.89 | 14891112.53 | 0.512083E+09 |
February | 0.105063E+09 | 0.00 | 0.105063E+09 | 16081804.41 | 0.472934E+09 |
March | 0.158322E+09 | 8169.66 | 0.158314E+09 | 68433766.45 | 0.391253E+09 |
April | 0.192601E+09 | 1261912.55 | 0.191339E+09 | 0.107369E+09 | 0.321187E+09 |
May | 0.271873E+09 | 9118098.35 | 0.262755E+09 | 0.259077E+09 | 0.179614E+09 |
June | 0.288462E+09 | 32258192.82 | 0.256204E+09 | 0.402427E+09 | 87410383.58 |
July | 0.282719E+09 | 19298505.98 | 0.263421E+09 | 0.399977E+09 | 83761663.57 |
August | 0.225097E+09 | 6091604.04 | 0.219005E+09 | 0.302465E+09 | 0.100001E+09 |
September | 0.182395E+09 | 145668.87 | 0.182249E+09 | 0.214258E+09 | 0.161861E+09 |
October | 0.134843E+09 | 0.00 | 0.134843E+09 | 72686316.01 | 0.377165E+09 |
November | 99060829.03 | 0.00 | 99060829.03 | 24531770.82 | 0.442126E+09 |
December | 86588503.18 | 0.00 | 86588503.18 | 12513237.52 | 0.584155E+09 |
Annual Sum or Average | 0.211957E+10 | 68182152.28 | 0.205139E+10 | 0.189471E+10 | 0.371355E+10 |
Minimum of Months | 86588503.18 | 0.00 | 86588503.18 | 12513237.52 | 83761663.57 |
Maximum of Months | 0.288462E+09 | 32258192.82 | 0.263421E+09 | 0.402427E+09 | 0.584155E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 34116379.75 | 0.00 | 34116379.75 | 5489480.67 | 0.188775E+09 |
February | 38730531.38 | 0.00 | 38730531.38 | 5928419.00 | 0.174344E+09 |
March | 58364136.20 | 3011.67 | 58361124.52 | 25227519.93 | 0.144232E+09 |
April | 71000608.82 | 465193.22 | 70535415.60 | 39580476.94 | 0.118403E+09 |
May | 0.100224E+09 | 3361308.60 | 96862221.74 | 95506599.09 | 66213256.15 |
June | 0.106339E+09 | 11891705.58 | 94447236.21 | 0.148351E+09 | 32223086.77 |
July | 0.104222E+09 | 7114228.39 | 97107710.86 | 0.147448E+09 | 30878017.49 |
August | 82980016.94 | 2245617.48 | 80734399.46 | 0.111501E+09 | 36864655.67 |
September | 67238296.50 | 53699.58 | 67184596.92 | 78984364.28 | 59668750.23 |
October | 49708673.90 | 0.00 | 49708673.90 | 26795185.78 | 0.139038E+09 |
November | 36517923.36 | 0.00 | 36517923.36 | 9043426.50 | 0.162986E+09 |
December | 31920107.62 | 0.00 | 31920107.62 | 4612897.48 | 0.215344E+09 |
Annual Sum or Average | 0.781361E+09 | 25134764.53 | 0.756226E+09 | 0.698469E+09 | 0.136897E+10 |
Minimum of Months | 31920107.62 | 0.00 | 31920107.62 | 4612897.48 | 30878017.49 |
Maximum of Months | 0.106339E+09 | 11891705.58 | 97107710.86 | 0.148351E+09 | 0.215344E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.327974E+09 | 0.269987E+09 | 57987003.41 | 0.382193E+09 | 0.159106E+09 |
February | 0.280311E+09 | 0.222878E+09 | 57433344.00 | 0.322620E+09 | 0.152759E+09 |
March | 0.233121E+09 | 0.154069E+09 | 79051433.12 | 0.271124E+09 | 0.135731E+09 |
April | 0.147724E+09 | 61112968.53 | 86610767.13 | 0.157441E+09 | 0.118941E+09 |
May | 0.138711E+09 | 26674072.02 | 0.112037E+09 | 0.164377E+09 | 71525247.85 |
June | 0.122044E+09 | 22030990.58 | 0.100013E+09 | 0.182561E+09 | 35466651.50 |
July | 0.130258E+09 | 22190312.50 | 0.108068E+09 | 0.195261E+09 | 33037882.13 |
August | 0.165737E+09 | 68185376.53 | 97551239.88 | 0.247179E+09 | 38216529.49 |
September | 0.210685E+09 | 0.118425E+09 | 92260125.35 | 0.292239E+09 | 58685280.81 |
October | 0.256987E+09 | 0.182083E+09 | 74903651.52 | 0.316588E+09 | 0.132218E+09 |
November | 0.304831E+09 | 0.243141E+09 | 61689551.46 | 0.364673E+09 | 0.145266E+09 |
December | 0.300608E+09 | 0.243350E+09 | 57257659.68 | 0.340648E+09 | 0.183921E+09 |
Annual Sum or Average | 0.261899E+10 | 0.163413E+10 | 0.984863E+09 | 0.323690E+10 | 0.126487E+10 |
Minimum of Months | 0.122044E+09 | 22030990.58 | 57257659.68 | 0.157441E+09 | 33037882.13 |
Maximum of Months | 0.327974E+09 | 0.269987E+09 | 0.112037E+09 | 0.382193E+09 | 0.183921E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.890190E+09 | 0.732801E+09 | 0.157389E+09 | 0.103735E+10 | 0.431846E+09 |
February | 0.760821E+09 | 0.604935E+09 | 0.155886E+09 | 0.875658E+09 | 0.414619E+09 |
March | 0.632738E+09 | 0.418176E+09 | 0.214562E+09 | 0.735885E+09 | 0.368402E+09 |
April | 0.400952E+09 | 0.165873E+09 | 0.235079E+09 | 0.427327E+09 | 0.322830E+09 |
May | 0.376489E+09 | 72398887.53 | 0.304090E+09 | 0.446154E+09 | 0.194134E+09 |
June | 0.331253E+09 | 59796614.77 | 0.271456E+09 | 0.495507E+09 | 96263746.71 |
July | 0.353548E+09 | 60229047.04 | 0.293319E+09 | 0.529979E+09 | 89671569.86 |
August | 0.449843E+09 | 0.185069E+09 | 0.264774E+09 | 0.670893E+09 | 0.103727E+09 |
September | 0.571844E+09 | 0.321431E+09 | 0.250413E+09 | 0.793197E+09 | 0.159284E+09 |
October | 0.697515E+09 | 0.494211E+09 | 0.203304E+09 | 0.859283E+09 | 0.358866E+09 |
November | 0.827373E+09 | 0.659935E+09 | 0.167438E+09 | 0.989797E+09 | 0.394281E+09 |
December | 0.815911E+09 | 0.660502E+09 | 0.155409E+09 | 0.924588E+09 | 0.499198E+09 |
Annual Sum or Average | 0.710848E+10 | 0.443536E+10 | 0.267312E+10 | 0.878562E+10 | 0.343312E+10 |
Minimum of Months | 0.331253E+09 | 59796614.77 | 0.155409E+09 | 0.427327E+09 | 89671569.86 |
Maximum of Months | 0.890190E+09 | 0.732801E+09 | 0.304090E+09 | 0.103735E+10 | 0.499198E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.702909E+09 | 0.578632E+09 | 0.124277E+09 | 0.812768E+09 | 0.324846E+09 |
February | 0.600757E+09 | 0.477667E+09 | 0.123090E+09 | 0.683737E+09 | 0.313392E+09 |
March | 0.499620E+09 | 0.330199E+09 | 0.169422E+09 | 0.574752E+09 | 0.273208E+09 |
April | 0.316599E+09 | 0.130976E+09 | 0.185623E+09 | 0.332142E+09 | 0.239541E+09 |
May | 0.297282E+09 | 57167386.18 | 0.240115E+09 | 0.347776E+09 | 0.137443E+09 |
June | 0.261563E+09 | 47216418.44 | 0.214346E+09 | 0.392155E+09 | 57977169.61 |
July | 0.279167E+09 | 47557874.28 | 0.231609E+09 | 0.423207E+09 | 50646406.83 |
August | 0.355204E+09 | 0.146134E+09 | 0.209070E+09 | 0.530648E+09 | 60689837.23 |
September | 0.451537E+09 | 0.253807E+09 | 0.197730E+09 | 0.626231E+09 | 0.102591E+09 |
October | 0.550770E+09 | 0.390238E+09 | 0.160532E+09 | 0.674592E+09 | 0.258943E+09 |
November | 0.653308E+09 | 0.521096E+09 | 0.132212E+09 | 0.774404E+09 | 0.294672E+09 |
December | 0.644257E+09 | 0.521543E+09 | 0.122714E+09 | 0.724361E+09 | 0.377797E+09 |
Annual Sum or Average | 0.561297E+10 | 0.350223E+10 | 0.211074E+10 | 0.689677E+10 | 0.249175E+10 |
Minimum of Months | 0.261563E+09 | 47216418.44 | 0.122714E+09 | 0.332142E+09 | 50646406.83 |
Maximum of Months | 0.702909E+09 | 0.578632E+09 | 0.240115E+09 | 0.812768E+09 | 0.377797E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.454908E+09 | 0.288304E+09 | 0.166604E+09 | 0.421677E+09 | 0.668897E+09 |
February | 0.496369E+09 | 0.307906E+09 | 0.188463E+09 | 0.453014E+09 | 0.625129E+09 |
March | 0.640872E+09 | 0.353023E+09 | 0.287849E+09 | 0.633868E+09 | 0.517523E+09 |
April | 0.584971E+09 | 0.247796E+09 | 0.337175E+09 | 0.556809E+09 | 0.436574E+09 |
May | 0.739057E+09 | 0.261015E+09 | 0.478041E+09 | 0.855545E+09 | 0.249070E+09 |
June | 0.873178E+09 | 0.419781E+09 | 0.453397E+09 | 0.122052E+10 | 0.107701E+09 |
July | 0.734347E+09 | 0.268122E+09 | 0.466225E+09 | 0.104182E+10 | 94197131.55 |
August | 0.768972E+09 | 0.380005E+09 | 0.388968E+09 | 0.106157E+10 | 0.111794E+09 |
September | 0.662115E+09 | 0.318550E+09 | 0.343565E+09 | 0.869331E+09 | 0.192906E+09 |
October | 0.572943E+09 | 0.327477E+09 | 0.245466E+09 | 0.618787E+09 | 0.496511E+09 |
November | 0.455288E+09 | 0.276523E+09 | 0.178766E+09 | 0.436622E+09 | 0.583572E+09 |
December | 0.379433E+09 | 0.224048E+09 | 0.155385E+09 | 0.317199E+09 | 0.769049E+09 |
Annual Sum or Average | 0.736245E+10 | 0.367255E+10 | 0.368990E+10 | 0.848676E+10 | 0.485292E+10 |
Minimum of Months | 0.379433E+09 | 0.224048E+09 | 0.155385E+09 | 0.317199E+09 | 94197131.55 |
Maximum of Months | 0.873178E+09 | 0.419781E+09 | 0.478041E+09 | 0.122052E+10 | 0.769049E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 73076084.28 | 0.00 | 73076084.28 | 15386959.94 | 0.369721E+09 |
February | 82959434.63 | 0.00 | 82959434.63 | 15947027.94 | 0.347470E+09 |
March | 0.125014E+09 | 6450.90 | 0.125007E+09 | 56395033.60 | 0.288349E+09 |
April | 0.152081E+09 | 996427.49 | 0.151084E+09 | 83232901.07 | 0.238074E+09 |
May | 0.214675E+09 | 7199804.69 | 0.207475E+09 | 0.199089E+09 | 0.131515E+09 |
June | 0.227774E+09 | 25471614.68 | 0.202303E+09 | 0.315739E+09 | 59120021.06 |
July | 0.223240E+09 | 15238426.74 | 0.208001E+09 | 0.317072E+09 | 53418866.82 |
August | 0.177740E+09 | 4810033.59 | 0.172930E+09 | 0.239609E+09 | 64632243.48 |
September | 0.144022E+09 | 115022.61 | 0.143907E+09 | 0.172163E+09 | 0.110385E+09 |
October | 0.106474E+09 | 0.00 | 0.106474E+09 | 61603257.74 | 0.270100E+09 |
November | 78220106.15 | 0.00 | 78220106.15 | 23262368.08 | 0.319556E+09 |
December | 68371746.70 | 0.00 | 68371746.70 | 12758138.17 | 0.427610E+09 |
Annual Sum or Average | 0.167365E+10 | 53837780.70 | 0.161981E+10 | 0.151226E+10 | 0.267995E+10 |
Minimum of Months | 68371746.70 | 0.00 | 68371746.70 | 12758138.17 | 53418866.82 |
Maximum of Months | 0.227774E+09 | 25471614.68 | 0.208001E+09 | 0.317072E+09 | 0.427610E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.454908E+09 | 0.288304E+09 | 0.166604E+09 | 0.441903E+09 | 0.652447E+09 |
February | 0.496369E+09 | 0.307906E+09 | 0.188463E+09 | 0.471433E+09 | 0.612679E+09 |
March | 0.640872E+09 | 0.353023E+09 | 0.287849E+09 | 0.645590E+09 | 0.513315E+09 |
April | 0.584971E+09 | 0.247796E+09 | 0.337175E+09 | 0.561377E+09 | 0.436392E+09 |
May | 0.739057E+09 | 0.261015E+09 | 0.478041E+09 | 0.849971E+09 | 0.256630E+09 |
June | 0.873178E+09 | 0.419781E+09 | 0.453397E+09 | 0.121146E+10 | 0.118223E+09 |
July | 0.734347E+09 | 0.268122E+09 | 0.466225E+09 | 0.103179E+10 | 0.104108E+09 |
August | 0.768972E+09 | 0.380005E+09 | 0.388968E+09 | 0.105778E+10 | 0.122381E+09 |
September | 0.662115E+09 | 0.318550E+09 | 0.343565E+09 | 0.871513E+09 | 0.203083E+09 |
October | 0.572943E+09 | 0.327477E+09 | 0.245466E+09 | 0.630237E+09 | 0.492546E+09 |
November | 0.455288E+09 | 0.276523E+09 | 0.178766E+09 | 0.455120E+09 | 0.570633E+09 |
December | 0.379433E+09 | 0.224048E+09 | 0.155385E+09 | 0.333906E+09 | 0.754875E+09 |
Annual Sum or Average | 0.736245E+10 | 0.367255E+10 | 0.368990E+10 | 0.856209E+10 | 0.483731E+10 |
Minimum of Months | 0.379433E+09 | 0.224048E+09 | 0.155385E+09 | 0.333906E+09 | 0.104108E+09 |
Maximum of Months | 0.873178E+09 | 0.419781E+09 | 0.478041E+09 | 0.121146E+10 | 0.754875E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.103088E+10 | 0.848620E+09 | 0.182264E+09 | 0.117185E+10 | 0.493607E+09 |
February | 0.881068E+09 | 0.700545E+09 | 0.180523E+09 | 0.987151E+09 | 0.473450E+09 |
March | 0.732741E+09 | 0.484268E+09 | 0.248473E+09 | 0.833250E+09 | 0.409056E+09 |
April | 0.464323E+09 | 0.192089E+09 | 0.272233E+09 | 0.482349E+09 | 0.356723E+09 |
May | 0.435993E+09 | 83841458.20 | 0.352151E+09 | 0.512720E+09 | 0.200388E+09 |
June | 0.383607E+09 | 69247409.02 | 0.314360E+09 | 0.587281E+09 | 80244136.68 |
July | 0.409426E+09 | 69748186.78 | 0.339677E+09 | 0.629538E+09 | 70944136.28 |
August | 0.520940E+09 | 0.214319E+09 | 0.306621E+09 | 0.784519E+09 | 85826584.49 |
September | 0.662223E+09 | 0.372232E+09 | 0.289990E+09 | 0.917435E+09 | 0.150111E+09 |
October | 0.807757E+09 | 0.572321E+09 | 0.235436E+09 | 0.980278E+09 | 0.389421E+09 |
November | 0.958139E+09 | 0.764237E+09 | 0.193901E+09 | 0.111898E+10 | 0.447740E+09 |
December | 0.944865E+09 | 0.764893E+09 | 0.179971E+09 | 0.104105E+10 | 0.575112E+09 |
Annual Sum or Average | 0.823196E+10 | 0.513636E+10 | 0.309560E+10 | 0.100464E+11 | 0.373262E+10 |
Minimum of Months | 0.383607E+09 | 69247409.02 | 0.179971E+09 | 0.482349E+09 | 70944136.28 |
Maximum of Months | 0.103088E+10 | 0.848620E+09 | 0.352151E+09 | 0.117185E+10 | 0.575112E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.511513E+09 | 0.00 | 0.511513E+09 | 59369378.76 | 0.306069E+10 |
February | 0.580694E+09 | 0.00 | 0.580694E+09 | 65881959.91 | 0.285720E+10 |
March | 0.875064E+09 | 45154.60 | 0.875019E+09 | 0.311163E+09 | 0.238585E+10 |
April | 0.106453E+10 | 6974728.30 | 0.105755E+10 | 0.490326E+09 | 0.200773E+10 |
May | 0.150267E+10 | 50396724.07 | 0.145227E+10 | 0.129758E+10 | 0.108373E+10 |
June | 0.159436E+10 | 0.178295E+09 | 0.141606E+10 | 0.216770E+10 | 0.498188E+09 |
July | 0.156262E+10 | 0.106665E+09 | 0.145595E+10 | 0.216442E+10 | 0.476148E+09 |
August | 0.124413E+10 | 33668959.93 | 0.121047E+10 | 0.163068E+10 | 0.563809E+09 |
September | 0.100812E+10 | 805127.75 | 0.100731E+10 | 0.114817E+10 | 0.914697E+09 |
October | 0.745291E+09 | 0.00 | 0.745291E+09 | 0.359529E+09 | 0.222943E+10 |
November | 0.547520E+09 | 0.00 | 0.547520E+09 | 0.107711E+09 | 0.266477E+10 |
December | 0.478584E+09 | 0.00 | 0.478584E+09 | 48239046.27 | 0.352150E+10 |
Annual Sum or Average | 0.117151E+11 | 0.376850E+09 | 0.113382E+11 | 0.985076E+10 | 0.222637E+11 |
Minimum of Months | 0.478584E+09 | 0.00 | 0.478584E+09 | 48239046.27 | 0.476148E+09 |
Maximum of Months | 0.159436E+10 | 0.178295E+09 | 0.145595E+10 | 0.216770E+10 | 0.352150E+10 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.511513E+09 | 0.00 | 0.511513E+09 | 52170166.25 | 0.312558E+10 |
February | 0.580694E+09 | 0.00 | 0.580694E+09 | 59997134.30 | 0.291904E+10 |
March | 0.875064E+09 | 45154.60 | 0.875019E+09 | 0.294959E+09 | 0.243743E+10 |
April | 0.106453E+10 | 6974728.30 | 0.105755E+10 | 0.470890E+09 | 0.205189E+10 |
May | 0.150267E+10 | 50396724.07 | 0.145227E+10 | 0.127374E+10 | 0.110489E+10 |
June | 0.159436E+10 | 0.178295E+09 | 0.141606E+10 | 0.214846E+10 | 0.510469E+09 |
July | 0.156262E+10 | 0.106665E+09 | 0.145595E+10 | 0.214514E+10 | 0.489266E+09 |
August | 0.124413E+10 | 33668959.93 | 0.121047E+10 | 0.161309E+10 | 0.578878E+09 |
September | 0.100812E+10 | 805127.75 | 0.100731E+10 | 0.113271E+10 | 0.934152E+09 |
October | 0.745291E+09 | 0.00 | 0.745291E+09 | 0.345670E+09 | 0.227203E+10 |
November | 0.547520E+09 | 0.00 | 0.547520E+09 | 0.100473E+09 | 0.272204E+10 |
December | 0.478584E+09 | 0.00 | 0.478584E+09 | 43138521.77 | 0.359761E+10 |
Annual Sum or Average | 0.117151E+11 | 0.376850E+09 | 0.113382E+11 | 0.968045E+10 | 0.227433E+11 |
Minimum of Months | 0.478584E+09 | 0.00 | 0.478584E+09 | 43138521.77 | 0.489266E+09 |
Maximum of Months | 0.159436E+10 | 0.178295E+09 | 0.145595E+10 | 0.214846E+10 | 0.359761E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 73076084.28 | 0.00 | 73076084.28 | 19425271.00 | 0.381566E+09 |
February | 82959434.63 | 0.00 | 82959434.63 | 19404499.69 | 0.363882E+09 |
March | 0.125014E+09 | 6450.90 | 0.125007E+09 | 67820730.52 | 0.306014E+09 |
April | 0.152081E+09 | 996427.49 | 0.151084E+09 | 99222185.04 | 0.259453E+09 |
May | 0.214675E+09 | 7199804.69 | 0.207475E+09 | 0.245162E+09 | 0.146979E+09 |
June | 0.227774E+09 | 25471614.68 | 0.202303E+09 | 0.378797E+09 | 70747443.83 |
July | 0.223240E+09 | 15238426.74 | 0.208001E+09 | 0.379884E+09 | 67394552.71 |
August | 0.177740E+09 | 4810033.59 | 0.172930E+09 | 0.299649E+09 | 76139009.71 |
September | 0.144022E+09 | 115022.61 | 0.143907E+09 | 0.217581E+09 | 0.117688E+09 |
October | 0.106474E+09 | 0.00 | 0.106474E+09 | 79008702.47 | 0.282292E+09 |
November | 78220106.15 | 0.00 | 78220106.15 | 30076813.91 | 0.332138E+09 |
December | 68371746.70 | 0.00 | 68371746.70 | 14527890.35 | 0.450012E+09 |
Annual Sum or Average | 0.167365E+10 | 53837780.70 | 0.161981E+10 | 0.185056E+10 | 0.285430E+10 |
Minimum of Months | 68371746.70 | 0.00 | 68371746.70 | 14527890.35 | 67394552.71 |
Maximum of Months | 0.227774E+09 | 25471614.68 | 0.208001E+09 | 0.379884E+09 | 0.450012E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.851689E+09 | 0.520925E+09 | 0.330764E+09 | 0.807409E+09 | 0.132629E+10 |
February | 0.103127E+10 | 0.652680E+09 | 0.378585E+09 | 0.101415E+10 | 0.128272E+10 |
March | 0.137538E+10 | 0.802812E+09 | 0.572564E+09 | 0.147452E+10 | 0.108386E+10 |
April | 0.135873E+10 | 0.661766E+09 | 0.696961E+09 | 0.143999E+10 | 0.942513E+09 |
May | 0.164598E+10 | 0.689069E+09 | 0.956909E+09 | 0.208378E+10 | 0.545759E+09 |
June | 0.193823E+10 | 0.101725E+10 | 0.920982E+09 | 0.291348E+10 | 0.265057E+09 |
July | 0.181794E+10 | 0.863862E+09 | 0.954079E+09 | 0.278575E+10 | 0.252561E+09 |
August | 0.183819E+10 | 0.101275E+10 | 0.825447E+09 | 0.277397E+10 | 0.283645E+09 |
September | 0.148255E+10 | 0.805873E+09 | 0.676677E+09 | 0.213200E+10 | 0.425146E+09 |
October | 0.110859E+10 | 0.607994E+09 | 0.500598E+09 | 0.128220E+10 | 0.102623E+10 |
November | 0.832518E+09 | 0.469164E+09 | 0.363353E+09 | 0.840165E+09 | 0.118441E+10 |
December | 0.746097E+09 | 0.429939E+09 | 0.316158E+09 | 0.655867E+09 | 0.158643E+10 |
Annual Sum or Average | 0.160272E+11 | 0.853408E+10 | 0.749308E+10 | 0.202033E+11 | 0.102046E+11 |
Minimum of Months | 0.746097E+09 | 0.429939E+09 | 0.316158E+09 | 0.655867E+09 | 0.252561E+09 |
Maximum of Months | 0.193823E+10 | 0.101725E+10 | 0.956909E+09 | 0.291348E+10 | 0.158643E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.702909E+09 | 0.578632E+09 | 0.124277E+09 | 0.844405E+09 | 0.333272E+09 |
February | 0.600757E+09 | 0.477667E+09 | 0.123090E+09 | 0.709310E+09 | 0.326820E+09 |
March | 0.499620E+09 | 0.330199E+09 | 0.169422E+09 | 0.602739E+09 | 0.291030E+09 |
April | 0.316599E+09 | 0.130976E+09 | 0.185623E+09 | 0.354762E+09 | 0.261073E+09 |
May | 0.297282E+09 | 57167386.18 | 0.240115E+09 | 0.392965E+09 | 0.156659E+09 |
June | 0.261563E+09 | 47216418.44 | 0.214346E+09 | 0.450459E+09 | 75952646.66 |
July | 0.279167E+09 | 47557874.28 | 0.231609E+09 | 0.481162E+09 | 70548811.03 |
August | 0.355204E+09 | 0.146134E+09 | 0.209070E+09 | 0.590521E+09 | 77903518.64 |
September | 0.451537E+09 | 0.253807E+09 | 0.197730E+09 | 0.677998E+09 | 0.117307E+09 |
October | 0.550770E+09 | 0.390238E+09 | 0.160532E+09 | 0.709981E+09 | 0.272096E+09 |
November | 0.653308E+09 | 0.521096E+09 | 0.132212E+09 | 0.805219E+09 | 0.304115E+09 |
December | 0.644257E+09 | 0.521543E+09 | 0.122714E+09 | 0.745796E+09 | 0.393998E+09 |
Annual Sum or Average | 0.561297E+10 | 0.350223E+10 | 0.211074E+10 | 0.736532E+10 | 0.268078E+10 |
Minimum of Months | 0.261563E+09 | 47216418.44 | 0.122714E+09 | 0.354762E+09 | 70548811.03 |
Maximum of Months | 0.702909E+09 | 0.578632E+09 | 0.240115E+09 | 0.844405E+09 | 0.393998E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 92546249.89 | 0.00 | 92546249.89 | 12975334.88 | 0.514765E+09 |
February | 0.105063E+09 | 0.00 | 0.105063E+09 | 13650233.14 | 0.478908E+09 |
March | 0.158322E+09 | 8169.66 | 0.158314E+09 | 62340576.58 | 0.394416E+09 |
April | 0.192601E+09 | 1261912.55 | 0.191339E+09 | 0.100018E+09 | 0.325949E+09 |
May | 0.271873E+09 | 9118098.35 | 0.262755E+09 | 0.248014E+09 | 0.183113E+09 |
June | 0.288462E+09 | 32258192.82 | 0.256204E+09 | 0.392345E+09 | 90128961.34 |
July | 0.282719E+09 | 19298505.98 | 0.263421E+09 | 0.391189E+09 | 86147637.87 |
August | 0.225097E+09 | 6091604.04 | 0.219005E+09 | 0.294010E+09 | 0.102229E+09 |
September | 0.182395E+09 | 145668.87 | 0.182249E+09 | 0.208208E+09 | 0.161670E+09 |
October | 0.134843E+09 | 0.00 | 0.134843E+09 | 67858588.91 | 0.376804E+09 |
November | 99060829.03 | 0.00 | 99060829.03 | 21254759.40 | 0.446037E+09 |
December | 86588503.18 | 0.00 | 86588503.18 | 10466563.11 | 0.592124E+09 |
Annual Sum or Average | 0.211957E+10 | 68182152.28 | 0.205139E+10 | 0.182233E+10 | 0.375229E+10 |
Minimum of Months | 86588503.18 | 0.00 | 86588503.18 | 10466563.11 | 86147637.87 |
Maximum of Months | 0.288462E+09 | 32258192.82 | 0.263421E+09 | 0.392345E+09 | 0.592124E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 82801480.44 | 0.00 | 82801480.44 | 11609081.28 | 0.460490E+09 |
February | 94000165.32 | 0.00 | 94000165.32 | 12212915.31 | 0.428485E+09 |
March | 0.141652E+09 | 7309.43 | 0.141644E+09 | 55776350.08 | 0.352885E+09 |
April | 0.172321E+09 | 1129037.94 | 0.171192E+09 | 89486726.47 | 0.291628E+09 |
May | 0.243246E+09 | 8157997.15 | 0.235088E+09 | 0.221899E+09 | 0.163832E+09 |
June | 0.258088E+09 | 28861527.34 | 0.229226E+09 | 0.351033E+09 | 80638723.20 |
July | 0.252950E+09 | 17266446.42 | 0.235683E+09 | 0.349999E+09 | 77076618.01 |
August | 0.201395E+09 | 5450181.22 | 0.195945E+09 | 0.263052E+09 | 91464668.42 |
September | 0.163189E+09 | 130330.49 | 0.163059E+09 | 0.186285E+09 | 0.144647E+09 |
October | 0.120644E+09 | 0.00 | 0.120644E+09 | 60713336.62 | 0.337128E+09 |
November | 88630099.07 | 0.00 | 88630099.07 | 19016713.77 | 0.399060E+09 |
December | 77471061.88 | 0.00 | 77471061.88 | 9364473.67 | 0.529732E+09 |
Annual Sum or Average | 0.189639E+10 | 61002829.99 | 0.183538E+10 | 0.163045E+10 | 0.335707E+10 |
Minimum of Months | 77471061.88 | 0.00 | 77471061.88 | 9364473.67 | 77076618.01 |
Maximum of Months | 0.258088E+09 | 28861527.34 | 0.235683E+09 | 0.351033E+09 | 0.529732E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.262417E+10 | 0.216021E+10 | 0.463962E+09 | 0.303125E+10 | 0.127383E+10 |
February | 0.224281E+10 | 0.178327E+10 | 0.459532E+09 | 0.255115E+10 | 0.123338E+10 |
March | 0.186523E+10 | 0.123273E+10 | 0.632501E+09 | 0.213843E+10 | 0.109512E+10 |
April | 0.118196E+10 | 0.488973E+09 | 0.692985E+09 | 0.123205E+10 | 0.967794E+09 |
May | 0.110984E+10 | 0.213423E+09 | 0.896420E+09 | 0.128061E+10 | 0.585390E+09 |
June | 0.976492E+09 | 0.176273E+09 | 0.800219E+09 | 0.142940E+10 | 0.292766E+09 |
July | 0.104221E+10 | 0.177548E+09 | 0.864667E+09 | 0.153427E+10 | 0.272018E+09 |
August | 0.132608E+10 | 0.545560E+09 | 0.780521E+09 | 0.194750E+10 | 0.312924E+09 |
September | 0.168572E+10 | 0.947538E+09 | 0.738186E+09 | 0.231236E+10 | 0.470340E+09 |
October | 0.205619E+10 | 0.145687E+10 | 0.599314E+09 | 0.250940E+10 | 0.105720E+10 |
November | 0.243899E+10 | 0.194541E+10 | 0.493587E+09 | 0.288836E+10 | 0.116840E+10 |
December | 0.240520E+10 | 0.194708E+10 | 0.458126E+09 | 0.269430E+10 | 0.148820E+10 |
Annual Sum or Average | 0.209549E+11 | 0.130749E+11 | 0.788002E+10 | 0.255491E+11 | 0.102174E+11 |
Minimum of Months | 0.976492E+09 | 0.176273E+09 | 0.458126E+09 | 0.123205E+10 | 0.272018E+09 |
Maximum of Months | 0.262417E+10 | 0.216021E+10 | 0.896420E+09 | 0.303125E+10 | 0.148820E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1515.10 | 624.54 | 1327.33 | 1092.65 | 234.67 | 0.00 | 0.00 |
February | 1420.30 | 654.39 | 1255.98 | 998.64 | 257.34 | 0.00 | 0.00 |
March | 1079.14 | 520.35 | 943.45 | 623.53 | 319.92 | 0.00 | 0.00 |
April | 647.81 | 465.51 | 617.77 | 255.57 | 362.20 | 0.00 | 0.00 |
May | 654.59 | 268.96 | 561.37 | 107.95 | 453.41 | 0.00 | 0.00 |
June | 742.78 | 144.99 | 510.38 | 92.13 | 418.25 | 0.00 | 0.00 |
July | 771.00 | 129.49 | 527.16 | 89.81 | 437.35 | 0.00 | 0.00 |
August | 979.64 | 151.41 | 670.74 | 275.95 | 394.79 | 0.00 | 0.00 |
September | 1200.90 | 237.99 | 881.07 | 495.25 | 385.82 | 0.00 | 0.00 |
October | 1260.40 | 505.43 | 1040.04 | 736.90 | 303.14 | 0.00 | 0.00 |
November | 1494.51 | 585.69 | 1274.79 | 1016.81 | 257.98 | 0.00 | 0.00 |
December | 1358.54 | 711.06 | 1216.57 | 984.85 | 231.72 | 0.00 | 0.00 |
Annual Sum or Average | 1091.83 | 415.33 | 900.20 | 561.69 | 338.52 | 0.00 | 0.00 |
Minimum of Months | 647.81 | 129.49 | 510.38 | 89.81 | 231.72 | 0.00 | 0.00 |
Maximum of Months | 1515.10 | 711.06 | 1327.33 | 1092.65 | 453.41 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4227.89 | 1857.40 | 3737.67 | 3076.84 | 660.83 | 0.00 | 0.00 |
February | 3962.44 | 1932.03 | 3536.75 | 2812.11 | 724.64 | 0.00 | 0.00 |
March | 3005.47 | 1548.85 | 2656.69 | 1755.81 | 900.88 | 0.00 | 0.00 |
April | 1789.35 | 1408.40 | 1739.60 | 719.67 | 1019.93 | 0.00 | 0.00 |
May | 1792.48 | 835.14 | 1580.77 | 303.98 | 1276.78 | 0.00 | 0.00 |
June | 2064.93 | 430.35 | 1437.19 | 259.44 | 1177.75 | 0.00 | 0.00 |
July | 2144.48 | 386.87 | 1484.44 | 252.89 | 1231.56 | 0.00 | 0.00 |
August | 2732.03 | 450.38 | 1888.76 | 777.06 | 1111.70 | 0.00 | 0.00 |
September | 3354.71 | 705.16 | 2481.05 | 1394.59 | 1086.46 | 0.00 | 0.00 |
October | 3520.66 | 1500.77 | 2928.68 | 2075.07 | 853.61 | 0.00 | 0.00 |
November | 4173.61 | 1741.57 | 3589.72 | 2863.26 | 726.46 | 0.00 | 0.00 |
December | 3789.52 | 2098.85 | 3425.79 | 2773.28 | 652.52 | 0.00 | 0.00 |
Annual Sum or Average | 3041.14 | 1237.50 | 2534.91 | 1581.67 | 953.24 | 0.00 | 0.00 |
Minimum of Months | 1789.35 | 386.87 | 1437.19 | 252.89 | 652.52 | 0.00 | 0.00 |
Maximum of Months | 4227.89 | 2098.85 | 3737.67 | 3076.84 | 1276.78 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 5573.24 | 2480.94 | 4855.45 | 3996.99 | 858.45 | 0.00 | 0.00 |
February | 5231.39 | 2590.44 | 4594.44 | 3653.09 | 941.35 | 0.00 | 0.00 |
March | 3970.85 | 2095.73 | 3451.19 | 2280.90 | 1170.29 | 0.00 | 0.00 |
April | 2364.78 | 1926.38 | 2259.84 | 934.90 | 1324.95 | 0.00 | 0.00 |
May | 2375.70 | 1121.05 | 2053.51 | 394.89 | 1658.62 | 0.00 | 0.00 |
June | 2751.15 | 567.07 | 1866.99 | 337.03 | 1529.97 | 0.00 | 0.00 |
July | 2854.95 | 508.80 | 1928.38 | 328.51 | 1599.86 | 0.00 | 0.00 |
August | 3627.68 | 588.03 | 2453.61 | 1009.44 | 1444.17 | 0.00 | 0.00 |
September | 4441.32 | 924.65 | 3223.02 | 1811.65 | 1411.37 | 0.00 | 0.00 |
October | 4645.48 | 2015.82 | 3804.52 | 2695.63 | 1108.89 | 0.00 | 0.00 |
November | 5504.41 | 2332.11 | 4663.25 | 3719.54 | 943.71 | 0.00 | 0.00 |
December | 4994.74 | 2818.01 | 4450.30 | 3602.64 | 847.66 | 0.00 | 0.00 |
Annual Sum or Average | 4020.96 | 1658.95 | 3292.99 | 2054.68 | 1238.31 | 0.00 | 0.00 |
Minimum of Months | 2364.78 | 508.80 | 1866.99 | 328.51 | 847.66 | 0.00 | 0.00 |
Maximum of Months | 5573.24 | 2818.01 | 4855.45 | 3996.99 | 1658.62 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 444.12 | 355.80 | 432.28 | 323.68 | 108.60 | 0.00 | 0.00 |
February | 458.54 | 374.83 | 453.51 | 324.72 | 128.78 | 0.00 | 0.00 |
March | 448.17 | 291.03 | 425.81 | 255.09 | 170.73 | 0.00 | 0.00 |
April | 342.70 | 259.52 | 347.83 | 146.13 | 201.70 | 0.00 | 0.00 |
May | 451.36 | 144.32 | 386.92 | 118.80 | 268.13 | 0.00 | 0.00 |
June | 625.57 | 65.29 | 437.79 | 180.17 | 257.62 | 0.00 | 0.00 |
July | 549.58 | 55.66 | 378.40 | 117.86 | 260.54 | 0.00 | 0.00 |
August | 597.49 | 65.77 | 419.72 | 196.44 | 223.28 | 0.00 | 0.00 |
September | 578.73 | 115.69 | 429.65 | 220.82 | 208.83 | 0.00 | 0.00 |
October | 481.77 | 281.48 | 419.55 | 267.96 | 151.58 | 0.00 | 0.00 |
November | 459.52 | 331.29 | 427.70 | 307.72 | 119.98 | 0.00 | 0.00 |
December | 371.82 | 410.97 | 382.20 | 278.37 | 103.83 | 0.00 | 0.00 |
Annual Sum or Average | 484.13 | 228.51 | 411.45 | 227.51 | 183.94 | 0.00 | 0.00 |
Minimum of Months | 342.70 | 55.66 | 347.83 | 117.86 | 103.83 | 0.00 | 0.00 |
Maximum of Months | 625.57 | 410.97 | 453.51 | 324.72 | 268.13 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 162.54 | 378.03 | 197.13 | 107.64 | 89.49 | 0.00 | 0.00 |
February | 193.81 | 390.48 | 239.47 | 127.28 | 112.20 | 0.00 | 0.00 |
March | 259.12 | 296.55 | 285.95 | 131.81 | 154.14 | 0.00 | 0.00 |
April | 248.53 | 259.12 | 284.36 | 95.98 | 188.37 | 0.00 | 0.00 |
May | 393.63 | 143.40 | 356.08 | 100.14 | 255.94 | 0.00 | 0.00 |
June | 590.73 | 66.98 | 424.75 | 171.78 | 252.97 | 0.00 | 0.00 |
July | 504.86 | 58.40 | 357.52 | 105.79 | 251.73 | 0.00 | 0.00 |
August | 486.59 | 70.13 | 353.46 | 143.67 | 209.79 | 0.00 | 0.00 |
September | 403.31 | 121.90 | 311.01 | 122.94 | 188.07 | 0.00 | 0.00 |
October | 256.77 | 285.14 | 253.67 | 122.27 | 131.40 | 0.00 | 0.00 |
November | 179.51 | 341.42 | 205.83 | 106.68 | 99.15 | 0.00 | 0.00 |
December | 121.91 | 436.45 | 167.19 | 83.65 | 83.54 | 0.00 | 0.00 |
Annual Sum or Average | 317.36 | 236.51 | 286.53 | 118.16 | 168.37 | 0.00 | 0.00 |
Minimum of Months | 121.91 | 58.40 | 167.19 | 83.65 | 83.54 | 0.00 | 0.00 |
Maximum of Months | 590.73 | 436.45 | 424.75 | 171.78 | 255.94 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 231.67 | 122.11 | 209.91 | 172.79 | 37.11 | 0.00 | 0.00 |
February | 217.19 | 123.33 | 198.62 | 157.93 | 40.70 | 0.00 | 0.00 |
March | 164.09 | 100.26 | 149.20 | 98.61 | 50.59 | 0.00 | 0.00 |
April | 95.28 | 96.18 | 97.70 | 40.42 | 57.28 | 0.00 | 0.00 |
May | 92.59 | 60.01 | 88.78 | 17.07 | 71.70 | 0.00 | 0.00 |
June | 109.06 | 33.06 | 80.71 | 14.57 | 66.14 | 0.00 | 0.00 |
July | 113.55 | 30.58 | 83.37 | 14.20 | 69.16 | 0.00 | 0.00 |
August | 147.15 | 34.79 | 106.07 | 43.64 | 62.43 | 0.00 | 0.00 |
September | 182.34 | 50.98 | 139.34 | 78.32 | 61.02 | 0.00 | 0.00 |
October | 192.95 | 100.86 | 164.47 | 116.54 | 47.94 | 0.00 | 0.00 |
November | 229.91 | 114.71 | 201.60 | 160.80 | 40.80 | 0.00 | 0.00 |
December | 208.42 | 133.44 | 192.39 | 155.75 | 36.65 | 0.00 | 0.00 |
Annual Sum or Average | 165.05 | 83.14 | 142.36 | 88.83 | 53.53 | 0.00 | 0.00 |
Minimum of Months | 92.59 | 30.58 | 80.71 | 14.20 | 36.65 | 0.00 | 0.00 |
Maximum of Months | 231.67 | 133.44 | 209.91 | 172.79 | 71.70 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4.34 | 114.06 | 21.83 | 0.00 | 21.83 | 0.00 | 0.00 |
February | 5.38 | 117.48 | 27.44 | 0.00 | 27.44 | 0.00 | 0.00 |
March | 17.82 | 87.13 | 37.34 | 0.00 | 37.34 | 0.00 | 0.00 |
April | 26.99 | 74.88 | 46.94 | 0.31 | 46.64 | 0.00 | 0.00 |
May | 63.21 | 38.58 | 64.13 | 2.15 | 61.98 | 0.00 | 0.00 |
June | 103.00 | 16.74 | 70.31 | 7.86 | 62.45 | 0.00 | 0.00 |
July | 99.26 | 14.84 | 66.69 | 4.55 | 62.14 | 0.00 | 0.00 |
August | 76.45 | 17.68 | 53.10 | 1.44 | 51.66 | 0.00 | 0.00 |
September | 56.65 | 32.33 | 44.46 | 0.04 | 44.42 | 0.00 | 0.00 |
October | 19.76 | 81.39 | 31.81 | 0.00 | 31.81 | 0.00 | 0.00 |
November | 7.23 | 101.33 | 24.15 | 0.00 | 24.15 | 0.00 | 0.00 |
December | 3.51 | 132.20 | 20.42 | 0.00 | 20.42 | 0.00 | 0.00 |
Annual Sum or Average | 40.50 | 68.79 | 42.46 | 1.37 | 41.10 | 0.00 | 0.00 |
Minimum of Months | 3.51 | 14.84 | 20.42 | 0.00 | 20.42 | 0.00 | 0.00 |
Maximum of Months | 103.00 | 132.20 | 70.31 | 7.86 | 62.45 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 424.91 | 352.17 | 421.44 | 313.29 | 108.15 | 0.00 | 0.00 |
February | 466.68 | 373.45 | 461.49 | 332.35 | 129.13 | 0.00 | 0.00 |
March | 468.48 | 288.93 | 443.31 | 273.16 | 170.15 | 0.00 | 0.00 |
April | 384.32 | 254.71 | 384.26 | 178.20 | 206.07 | 0.00 | 0.00 |
May | 483.14 | 136.26 | 418.28 | 149.99 | 268.30 | 0.00 | 0.00 |
June | 669.42 | 59.42 | 474.83 | 214.46 | 260.37 | 0.00 | 0.00 |
July | 634.66 | 52.40 | 443.62 | 179.03 | 264.59 | 0.00 | 0.00 |
August | 672.72 | 63.37 | 475.79 | 243.63 | 232.16 | 0.00 | 0.00 |
September | 613.86 | 110.49 | 460.21 | 253.38 | 206.83 | 0.00 | 0.00 |
October | 468.63 | 278.48 | 412.60 | 259.21 | 153.39 | 0.00 | 0.00 |
November | 437.94 | 329.21 | 412.65 | 291.55 | 121.10 | 0.00 | 0.00 |
December | 368.82 | 411.56 | 379.83 | 274.99 | 104.84 | 0.00 | 0.00 |
Annual Sum or Average | 507.93 | 225.07 | 432.11 | 246.37 | 185.74 | 0.00 | 0.00 |
Minimum of Months | 368.82 | 52.40 | 379.83 | 149.99 | 104.84 | 0.00 | 0.00 |
Maximum of Months | 672.72 | 411.56 | 475.79 | 332.35 | 268.30 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 137.75 | 367.53 | 186.29 | 97.25 | 89.03 | 0.00 | 0.00 |
February | 198.38 | 385.17 | 247.45 | 134.91 | 112.54 | 0.00 | 0.00 |
March | 275.53 | 289.58 | 303.45 | 149.88 | 153.57 | 0.00 | 0.00 |
April | 290.18 | 253.44 | 320.79 | 128.05 | 192.74 | 0.00 | 0.00 |
May | 428.98 | 137.73 | 387.44 | 131.33 | 256.11 | 0.00 | 0.00 |
June | 633.62 | 64.44 | 461.79 | 206.07 | 255.72 | 0.00 | 0.00 |
July | 588.56 | 57.30 | 422.74 | 166.97 | 255.78 | 0.00 | 0.00 |
August | 559.02 | 68.45 | 409.54 | 190.87 | 218.67 | 0.00 | 0.00 |
September | 436.72 | 115.05 | 341.57 | 155.51 | 186.06 | 0.00 | 0.00 |
October | 241.02 | 278.36 | 246.72 | 113.51 | 133.21 | 0.00 | 0.00 |
November | 155.13 | 335.68 | 190.78 | 90.51 | 100.27 | 0.00 | 0.00 |
December | 112.58 | 429.57 | 164.82 | 80.27 | 84.55 | 0.00 | 0.00 |
Annual Sum or Average | 338.82 | 231.03 | 307.20 | 137.02 | 170.17 | 0.00 | 0.00 |
Minimum of Months | 112.58 | 57.30 | 164.82 | 80.27 | 84.55 | 0.00 | 0.00 |
Maximum of Months | 633.62 | 429.57 | 461.79 | 206.07 | 256.11 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 503.55 | 448.25 | 502.10 | 374.40 | 127.70 | 0.00 | 0.00 |
February | 478.65 | 476.32 | 489.80 | 342.18 | 147.62 | 0.00 | 0.00 |
March | 405.17 | 382.37 | 404.18 | 213.66 | 190.52 | 0.00 | 0.00 |
April | 281.85 | 339.58 | 313.38 | 88.24 | 225.14 | 0.00 | 0.00 |
May | 358.48 | 189.11 | 331.28 | 41.65 | 289.63 | 0.00 | 0.00 |
June | 470.98 | 93.86 | 327.20 | 48.60 | 278.60 | 0.00 | 0.00 |
July | 473.17 | 86.63 | 325.10 | 40.63 | 284.47 | 0.00 | 0.00 |
August | 496.71 | 103.48 | 344.85 | 97.67 | 247.19 | 0.00 | 0.00 |
September | 531.33 | 168.99 | 398.21 | 169.77 | 228.44 | 0.00 | 0.00 |
October | 471.05 | 370.96 | 425.27 | 252.50 | 172.77 | 0.00 | 0.00 |
November | 515.93 | 422.03 | 489.11 | 348.41 | 140.70 | 0.00 | 0.00 |
December | 444.79 | 519.55 | 461.11 | 337.46 | 123.65 | 0.00 | 0.00 |
Annual Sum or Average | 452.45 | 299.13 | 400.44 | 195.42 | 205.02 | 0.00 | 0.00 |
Minimum of Months | 281.85 | 86.63 | 313.38 | 40.63 | 123.65 | 0.00 | 0.00 |
Maximum of Months | 531.33 | 519.55 | 502.10 | 374.40 | 289.63 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 443.29 | 353.42 | 432.28 | 323.68 | 108.60 | 0.00 | 0.00 |
February | 456.14 | 374.20 | 453.51 | 324.72 | 128.78 | 0.00 | 0.00 |
March | 445.54 | 289.52 | 425.81 | 255.09 | 170.73 | 0.00 | 0.00 |
April | 340.20 | 258.09 | 347.83 | 146.13 | 201.70 | 0.00 | 0.00 |
May | 448.16 | 143.20 | 386.92 | 118.80 | 268.13 | 0.00 | 0.00 |
June | 622.02 | 63.76 | 437.79 | 180.17 | 257.62 | 0.00 | 0.00 |
July | 546.87 | 53.97 | 378.40 | 117.86 | 260.54 | 0.00 | 0.00 |
August | 594.13 | 64.06 | 419.72 | 196.44 | 223.28 | 0.00 | 0.00 |
September | 576.29 | 113.31 | 429.65 | 220.82 | 208.83 | 0.00 | 0.00 |
October | 479.90 | 279.06 | 419.55 | 267.96 | 151.58 | 0.00 | 0.00 |
November | 457.76 | 329.37 | 427.70 | 307.72 | 119.98 | 0.00 | 0.00 |
December | 370.63 | 409.94 | 382.20 | 278.37 | 103.83 | 0.00 | 0.00 |
Annual Sum or Average | 481.76 | 226.85 | 411.45 | 227.51 | 183.94 | 0.00 | 0.00 |
Minimum of Months | 340.20 | 53.97 | 347.83 | 117.86 | 103.83 | 0.00 | 0.00 |
Maximum of Months | 622.02 | 409.94 | 453.51 | 324.72 | 268.13 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 163.31 | 374.21 | 197.13 | 107.64 | 89.49 | 0.00 | 0.00 |
February | 193.42 | 388.84 | 239.47 | 127.28 | 112.20 | 0.00 | 0.00 |
March | 257.76 | 294.98 | 285.95 | 131.81 | 154.14 | 0.00 | 0.00 |
April | 246.49 | 258.01 | 284.36 | 95.98 | 188.37 | 0.00 | 0.00 |
May | 390.05 | 143.29 | 356.08 | 100.14 | 255.94 | 0.00 | 0.00 |
June | 587.28 | 66.50 | 424.75 | 171.78 | 252.97 | 0.00 | 0.00 |
July | 502.38 | 57.59 | 357.52 | 105.79 | 251.73 | 0.00 | 0.00 |
August | 483.82 | 69.25 | 353.46 | 143.67 | 209.79 | 0.00 | 0.00 |
September | 401.96 | 120.25 | 311.01 | 122.94 | 188.07 | 0.00 | 0.00 |
October | 256.16 | 282.60 | 253.67 | 122.27 | 131.40 | 0.00 | 0.00 |
November | 179.55 | 338.42 | 205.83 | 106.68 | 99.15 | 0.00 | 0.00 |
December | 122.39 | 434.45 | 167.19 | 83.65 | 83.54 | 0.00 | 0.00 |
Annual Sum or Average | 315.96 | 234.88 | 286.53 | 118.16 | 168.37 | 0.00 | 0.00 |
Minimum of Months | 122.39 | 57.59 | 167.19 | 83.65 | 83.54 | 0.00 | 0.00 |
Maximum of Months | 587.28 | 434.45 | 424.75 | 171.78 | 255.94 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 437.52 | 184.29 | 384.89 | 316.84 | 68.05 | 0.00 | 0.00 |
February | 408.05 | 195.71 | 364.20 | 289.58 | 74.62 | 0.00 | 0.00 |
March | 311.10 | 152.72 | 273.57 | 180.80 | 92.77 | 0.00 | 0.00 |
April | 186.09 | 137.62 | 179.14 | 74.11 | 105.03 | 0.00 | 0.00 |
May | 191.43 | 74.82 | 162.78 | 31.30 | 131.48 | 0.00 | 0.00 |
June | 226.57 | 30.96 | 148.00 | 26.72 | 121.28 | 0.00 | 0.00 |
July | 235.04 | 26.49 | 152.86 | 26.04 | 126.82 | 0.00 | 0.00 |
August | 292.91 | 32.04 | 194.50 | 80.02 | 114.48 | 0.00 | 0.00 |
September | 353.95 | 57.91 | 255.49 | 143.61 | 111.88 | 0.00 | 0.00 |
October | 365.99 | 145.39 | 301.58 | 213.68 | 87.90 | 0.00 | 0.00 |
November | 431.71 | 172.74 | 369.65 | 294.84 | 74.81 | 0.00 | 0.00 |
December | 388.69 | 214.72 | 352.77 | 285.58 | 67.19 | 0.00 | 0.00 |
Annual Sum or Average | 318.57 | 118.36 | 261.03 | 162.87 | 98.16 | 0.00 | 0.00 |
Minimum of Months | 186.09 | 26.49 | 148.00 | 26.04 | 67.19 | 0.00 | 0.00 |
Maximum of Months | 437.52 | 214.72 | 384.89 | 316.84 | 131.48 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 22.17 | 1142.73 | 190.98 | 0.00 | 190.98 | 0.00 | 0.00 |
February | 27.23 | 1181.05 | 240.04 | 0.00 | 240.04 | 0.00 | 0.00 |
March | 116.17 | 890.78 | 326.71 | 0.02 | 326.69 | 0.00 | 0.00 |
April | 189.17 | 774.59 | 410.70 | 2.69 | 408.01 | 0.00 | 0.00 |
May | 484.46 | 404.62 | 561.03 | 18.82 | 542.22 | 0.00 | 0.00 |
June | 836.30 | 192.20 | 615.11 | 68.79 | 546.32 | 0.00 | 0.00 |
July | 808.10 | 177.77 | 583.42 | 39.82 | 543.59 | 0.00 | 0.00 |
August | 608.83 | 210.50 | 464.51 | 12.57 | 451.94 | 0.00 | 0.00 |
September | 442.97 | 352.89 | 388.93 | 0.31 | 388.62 | 0.00 | 0.00 |
October | 134.23 | 832.37 | 278.26 | 0.00 | 278.26 | 0.00 | 0.00 |
November | 41.56 | 1028.08 | 211.23 | 0.00 | 211.23 | 0.00 | 0.00 |
December | 18.01 | 1314.78 | 178.68 | 0.00 | 178.68 | 0.00 | 0.00 |
Annual Sum or Average | 312.37 | 705.98 | 371.48 | 11.95 | 359.53 | 0.00 | 0.00 |
Minimum of Months | 18.01 | 177.77 | 178.68 | 0.00 | 178.68 | 0.00 | 0.00 |
Maximum of Months | 836.30 | 1314.78 | 615.11 | 68.79 | 546.32 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 19.48 | 1166.96 | 190.98 | 0.00 | 190.98 | 0.00 | 0.00 |
February | 24.80 | 1206.61 | 240.04 | 0.00 | 240.04 | 0.00 | 0.00 |
March | 110.12 | 910.03 | 326.71 | 0.02 | 326.69 | 0.00 | 0.00 |
April | 181.67 | 791.62 | 410.70 | 2.69 | 408.01 | 0.00 | 0.00 |
May | 475.56 | 412.52 | 561.03 | 18.82 | 542.22 | 0.00 | 0.00 |
June | 828.88 | 196.94 | 615.11 | 68.79 | 546.32 | 0.00 | 0.00 |
July | 800.90 | 182.67 | 583.42 | 39.82 | 543.59 | 0.00 | 0.00 |
August | 602.26 | 216.13 | 464.51 | 12.57 | 451.94 | 0.00 | 0.00 |
September | 437.00 | 360.40 | 388.93 | 0.31 | 388.62 | 0.00 | 0.00 |
October | 129.06 | 848.28 | 278.26 | 0.00 | 278.26 | 0.00 | 0.00 |
November | 38.76 | 1050.17 | 211.23 | 0.00 | 211.23 | 0.00 | 0.00 |
December | 16.11 | 1343.19 | 178.68 | 0.00 | 178.68 | 0.00 | 0.00 |
Annual Sum or Average | 306.96 | 721.18 | 371.48 | 11.95 | 359.53 | 0.00 | 0.00 |
Minimum of Months | 16.11 | 182.67 | 178.68 | 0.00 | 178.68 | 0.00 | 0.00 |
Maximum of Months | 828.88 | 1343.19 | 615.11 | 68.79 | 546.32 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 587.56 | 725.66 | 607.70 | 410.53 | 197.18 | 0.00 | 0.00 |
February | 689.95 | 785.25 | 708.90 | 467.24 | 241.66 | 0.00 | 0.00 |
March | 791.88 | 618.57 | 746.72 | 423.02 | 323.70 | 0.00 | 0.00 |
April | 724.15 | 557.89 | 705.02 | 306.23 | 398.79 | 0.00 | 0.00 |
May | 1011.91 | 312.79 | 805.68 | 281.30 | 524.38 | 0.00 | 0.00 |
June | 1441.88 | 156.78 | 936.56 | 420.50 | 516.06 | 0.00 | 0.00 |
July | 1360.37 | 144.61 | 866.32 | 345.97 | 520.34 | 0.00 | 0.00 |
August | 1366.91 | 162.29 | 885.28 | 434.47 | 450.81 | 0.00 | 0.00 |
September | 1165.29 | 251.92 | 801.74 | 408.87 | 392.87 | 0.00 | 0.00 |
October | 768.89 | 585.74 | 659.29 | 372.70 | 286.59 | 0.00 | 0.00 |
November | 626.62 | 682.63 | 603.41 | 382.04 | 221.37 | 0.00 | 0.00 |
December | 489.78 | 868.46 | 544.63 | 355.24 | 189.38 | 0.00 | 0.00 |
Annual Sum or Average | 919.87 | 486.10 | 739.28 | 383.38 | 355.90 | 0.00 | 0.00 |
Minimum of Months | 489.78 | 144.61 | 544.63 | 281.30 | 189.38 | 0.00 | 0.00 |
Maximum of Months | 1441.88 | 868.46 | 936.56 | 467.24 | 524.38 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1090.03 | 788.82 | 1045.22 | 806.53 | 238.69 | 0.00 | 0.00 |
February | 1025.67 | 845.35 | 1009.37 | 737.13 | 272.24 | 0.00 | 0.00 |
March | 833.43 | 678.81 | 808.39 | 460.25 | 348.14 | 0.00 | 0.00 |
April | 547.69 | 610.90 | 596.79 | 189.57 | 407.22 | 0.00 | 0.00 |
May | 650.49 | 345.01 | 606.69 | 86.13 | 520.56 | 0.00 | 0.00 |
June | 832.23 | 172.80 | 587.59 | 91.59 | 496.01 | 0.00 | 0.00 |
July | 845.75 | 158.69 | 589.11 | 79.94 | 509.17 | 0.00 | 0.00 |
August | 933.94 | 187.99 | 654.34 | 208.00 | 446.34 | 0.00 | 0.00 |
September | 1043.48 | 298.81 | 783.68 | 365.67 | 418.01 | 0.00 | 0.00 |
October | 977.25 | 653.61 | 863.08 | 543.93 | 319.15 | 0.00 | 0.00 |
November | 1099.84 | 746.78 | 1013.38 | 750.54 | 262.84 | 0.00 | 0.00 |
December | 962.25 | 923.39 | 959.25 | 726.96 | 232.30 | 0.00 | 0.00 |
Annual Sum or Average | 902.75 | 532.53 | 791.82 | 418.70 | 373.12 | 0.00 | 0.00 |
Minimum of Months | 547.69 | 158.69 | 587.59 | 79.94 | 232.30 | 0.00 | 0.00 |
Maximum of Months | 1099.84 | 923.39 | 1045.22 | 806.53 | 520.56 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.405805E+10 | 0.167278E+10 | 0.355512E+10 | 0.292657E+10 | 0.628553E+09 | 0.00 | 0.00 |
February | 0.343598E+10 | 0.158310E+10 | 0.303846E+10 | 0.241591E+10 | 0.622550E+09 | 0.00 | 0.00 |
March | 0.289037E+10 | 0.139370E+10 | 0.252694E+10 | 0.167006E+10 | 0.856880E+09 | 0.00 | 0.00 |
April | 0.167913E+10 | 0.120661E+10 | 0.160126E+10 | 0.662442E+09 | 0.938820E+09 | 0.00 | 0.00 |
May | 0.175326E+10 | 0.720374E+09 | 0.150356E+10 | 0.289137E+09 | 0.121442E+10 | 0.00 | 0.00 |
June | 0.192528E+10 | 0.375821E+09 | 0.132290E+10 | 0.238808E+09 | 0.108409E+10 | 0.00 | 0.00 |
July | 0.206505E+10 | 0.346820E+09 | 0.141194E+10 | 0.240535E+09 | 0.117141E+10 | 0.00 | 0.00 |
August | 0.262387E+10 | 0.405524E+09 | 0.179651E+10 | 0.739105E+09 | 0.105741E+10 | 0.00 | 0.00 |
September | 0.311273E+10 | 0.616868E+09 | 0.228374E+10 | 0.128369E+10 | 0.100006E+10 | 0.00 | 0.00 |
October | 0.337587E+10 | 0.135373E+10 | 0.278564E+10 | 0.197372E+10 | 0.811921E+09 | 0.00 | 0.00 |
November | 0.387376E+10 | 0.151812E+10 | 0.330425E+10 | 0.263556E+10 | 0.668687E+09 | 0.00 | 0.00 |
December | 0.363872E+10 | 0.190452E+10 | 0.325847E+10 | 0.263783E+10 | 0.620648E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.344321E+11 | 0.130980E+11 | 0.283888E+11 | 0.177134E+11 | 0.106754E+11 | 0.00 | 0.00 |
Minimum of Months | 0.167913E+10 | 0.346820E+09 | 0.132290E+10 | 0.238808E+09 | 0.620648E+09 | 0.00 | 0.00 |
Maximum of Months | 0.405805E+10 | 0.190452E+10 | 0.355512E+10 | 0.292657E+10 | 0.121442E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.113240E+11 | 0.497485E+10 | 0.100110E+11 | 0.824102E+10 | 0.176996E+10 | 0.00 | 0.00 |
February | 0.958594E+10 | 0.467396E+10 | 0.855611E+10 | 0.680305E+10 | 0.175306E+10 | 0.00 | 0.00 |
March | 0.804984E+10 | 0.414843E+10 | 0.711568E+10 | 0.470277E+10 | 0.241292E+10 | 0.00 | 0.00 |
April | 0.463799E+10 | 0.365058E+10 | 0.450905E+10 | 0.186539E+10 | 0.264366E+10 | 0.00 | 0.00 |
May | 0.480097E+10 | 0.223683E+10 | 0.423393E+10 | 0.814191E+09 | 0.341974E+10 | 0.00 | 0.00 |
June | 0.535229E+10 | 0.111548E+10 | 0.372520E+10 | 0.672467E+09 | 0.305273E+10 | 0.00 | 0.00 |
July | 0.574379E+10 | 0.103618E+10 | 0.397593E+10 | 0.677330E+09 | 0.329860E+10 | 0.00 | 0.00 |
August | 0.731748E+10 | 0.120630E+10 | 0.505886E+10 | 0.208127E+10 | 0.297759E+10 | 0.00 | 0.00 |
September | 0.869540E+10 | 0.182778E+10 | 0.643087E+10 | 0.361478E+10 | 0.281609E+10 | 0.00 | 0.00 |
October | 0.942975E+10 | 0.401965E+10 | 0.784417E+10 | 0.555786E+10 | 0.228632E+10 | 0.00 | 0.00 |
November | 0.108180E+11 | 0.451415E+10 | 0.930455E+10 | 0.742157E+10 | 0.188298E+10 | 0.00 | 0.00 |
December | 0.101498E+11 | 0.562156E+10 | 0.917565E+10 | 0.742794E+10 | 0.174770E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.959053E+11 | 0.390257E+11 | 0.799410E+11 | 0.498796E+11 | 0.300613E+11 | 0.00 | 0.00 |
Minimum of Months | 0.463799E+10 | 0.103618E+10 | 0.372520E+10 | 0.672467E+09 | 0.174770E+10 | 0.00 | 0.00 |
Maximum of Months | 0.113240E+11 | 0.562156E+10 | 0.100110E+11 | 0.824102E+10 | 0.341974E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.149274E+11 | 0.664494E+10 | 0.130048E+11 | 0.107055E+11 | 0.229928E+10 | 0.00 | 0.00 |
February | 0.126558E+11 | 0.626678E+10 | 0.111149E+11 | 0.883755E+10 | 0.227732E+10 | 0.00 | 0.00 |
March | 0.106355E+11 | 0.561320E+10 | 0.924368E+10 | 0.610916E+10 | 0.313452E+10 | 0.00 | 0.00 |
April | 0.612951E+10 | 0.499317E+10 | 0.585751E+10 | 0.242325E+10 | 0.343426E+10 | 0.00 | 0.00 |
May | 0.636307E+10 | 0.300262E+10 | 0.550012E+10 | 0.105768E+10 | 0.444243E+10 | 0.00 | 0.00 |
June | 0.713098E+10 | 0.146985E+10 | 0.483925E+10 | 0.873573E+09 | 0.396567E+10 | 0.00 | 0.00 |
July | 0.764669E+10 | 0.136277E+10 | 0.516496E+10 | 0.879891E+09 | 0.428507E+10 | 0.00 | 0.00 |
August | 0.971638E+10 | 0.157497E+10 | 0.657175E+10 | 0.270369E+10 | 0.386806E+10 | 0.00 | 0.00 |
September | 0.115119E+11 | 0.239671E+10 | 0.835407E+10 | 0.469580E+10 | 0.365826E+10 | 0.00 | 0.00 |
October | 0.124425E+11 | 0.539917E+10 | 0.101900E+11 | 0.721997E+10 | 0.297005E+10 | 0.00 | 0.00 |
November | 0.142674E+11 | 0.604483E+10 | 0.120871E+11 | 0.964104E+10 | 0.244610E+10 | 0.00 | 0.00 |
December | 0.133779E+11 | 0.754776E+10 | 0.119197E+11 | 0.964932E+10 | 0.227037E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.126805E+12 | 0.523168E+11 | 0.103848E+12 | 0.647965E+11 | 0.390514E+11 | 0.00 | 0.00 |
Minimum of Months | 0.612951E+10 | 0.136277E+10 | 0.483925E+10 | 0.873573E+09 | 0.227037E+10 | 0.00 | 0.00 |
Maximum of Months | 0.149274E+11 | 0.754776E+10 | 0.130048E+11 | 0.107055E+11 | 0.444243E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.118952E+10 | 0.952976E+09 | 0.115782E+10 | 0.866936E+09 | 0.290881E+09 | 0.00 | 0.00 |
February | 0.110931E+10 | 0.906784E+09 | 0.109713E+10 | 0.785573E+09 | 0.311553E+09 | 0.00 | 0.00 |
March | 0.120037E+10 | 0.779483E+09 | 0.114049E+10 | 0.683221E+09 | 0.457271E+09 | 0.00 | 0.00 |
April | 0.888290E+09 | 0.672683E+09 | 0.901570E+09 | 0.378772E+09 | 0.522798E+09 | 0.00 | 0.00 |
May | 0.120891E+10 | 0.386534E+09 | 0.103634E+10 | 0.318183E+09 | 0.718156E+09 | 0.00 | 0.00 |
June | 0.162147E+10 | 0.169228E+09 | 0.113474E+10 | 0.466997E+09 | 0.667743E+09 | 0.00 | 0.00 |
July | 0.147199E+10 | 0.149076E+09 | 0.101351E+10 | 0.315680E+09 | 0.697834E+09 | 0.00 | 0.00 |
August | 0.160031E+10 | 0.176154E+09 | 0.112418E+10 | 0.526138E+09 | 0.598038E+09 | 0.00 | 0.00 |
September | 0.150006E+10 | 0.299873E+09 | 0.111365E+10 | 0.572357E+09 | 0.541296E+09 | 0.00 | 0.00 |
October | 0.129036E+10 | 0.753912E+09 | 0.112371E+10 | 0.717715E+09 | 0.405998E+09 | 0.00 | 0.00 |
November | 0.119107E+10 | 0.858716E+09 | 0.110860E+10 | 0.797619E+09 | 0.310977E+09 | 0.00 | 0.00 |
December | 0.995892E+09 | 0.110073E+10 | 0.102369E+10 | 0.745592E+09 | 0.278098E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.152676E+11 | 0.720615E+10 | 0.129754E+11 | 0.717478E+10 | 0.580064E+10 | 0.00 | 0.00 |
Minimum of Months | 0.888290E+09 | 0.149076E+09 | 0.901570E+09 | 0.315680E+09 | 0.278098E+09 | 0.00 | 0.00 |
Maximum of Months | 0.162147E+10 | 0.110073E+10 | 0.115782E+10 | 0.866936E+09 | 0.718156E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.435340E+09 | 0.101251E+10 | 0.527984E+09 | 0.288304E+09 | 0.239680E+09 | 0.00 | 0.00 |
February | 0.468856E+09 | 0.944654E+09 | 0.579329E+09 | 0.307906E+09 | 0.271423E+09 | 0.00 | 0.00 |
March | 0.694014E+09 | 0.794268E+09 | 0.765886E+09 | 0.353029E+09 | 0.412856E+09 | 0.00 | 0.00 |
April | 0.644184E+09 | 0.671645E+09 | 0.737052E+09 | 0.248792E+09 | 0.488260E+09 | 0.00 | 0.00 |
May | 0.105431E+10 | 0.384080E+09 | 0.953732E+09 | 0.268215E+09 | 0.685517E+09 | 0.00 | 0.00 |
June | 0.153118E+10 | 0.173618E+09 | 0.110095E+10 | 0.445253E+09 | 0.655699E+09 | 0.00 | 0.00 |
July | 0.135223E+10 | 0.156427E+09 | 0.957587E+09 | 0.283361E+09 | 0.674226E+09 | 0.00 | 0.00 |
August | 0.130328E+10 | 0.187826E+09 | 0.946712E+09 | 0.384815E+09 | 0.561898E+09 | 0.00 | 0.00 |
September | 0.104539E+10 | 0.315956E+09 | 0.806137E+09 | 0.318665E+09 | 0.487473E+09 | 0.00 | 0.00 |
October | 0.687720E+09 | 0.763706E+09 | 0.679417E+09 | 0.327477E+09 | 0.351940E+09 | 0.00 | 0.00 |
November | 0.465293E+09 | 0.884948E+09 | 0.533508E+09 | 0.276523E+09 | 0.256986E+09 | 0.00 | 0.00 |
December | 0.326523E+09 | 0.116898E+10 | 0.447805E+09 | 0.224048E+09 | 0.223756E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.100083E+11 | 0.745862E+10 | 0.903610E+10 | 0.372639E+10 | 0.530971E+10 | 0.00 | 0.00 |
Minimum of Months | 0.326523E+09 | 0.156427E+09 | 0.447805E+09 | 0.224048E+09 | 0.223756E+09 | 0.00 | 0.00 |
Maximum of Months | 0.153118E+10 | 0.116898E+10 | 0.110095E+10 | 0.445253E+09 | 0.685517E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.620502E+09 | 0.327059E+09 | 0.562215E+09 | 0.462814E+09 | 99401584.82 | 0.00 | 0.00 |
February | 0.525424E+09 | 0.298348E+09 | 0.480510E+09 | 0.382058E+09 | 98452499.34 | 0.00 | 0.00 |
March | 0.439496E+09 | 0.268534E+09 | 0.399617E+09 | 0.264106E+09 | 0.135510E+09 | 0.00 | 0.00 |
April | 0.246968E+09 | 0.249296E+09 | 0.253229E+09 | 0.104760E+09 | 0.148469E+09 | 0.00 | 0.00 |
May | 0.247982E+09 | 0.160735E+09 | 0.237778E+09 | 45724815.51 | 0.192054E+09 | 0.00 | 0.00 |
June | 0.282689E+09 | 85696620.97 | 0.209209E+09 | 37765624.19 | 0.171443E+09 | 0.00 | 0.00 |
July | 0.304139E+09 | 81894133.48 | 0.223289E+09 | 38038734.55 | 0.185251E+09 | 0.00 | 0.00 |
August | 0.394124E+09 | 93190664.96 | 0.284106E+09 | 0.116884E+09 | 0.167223E+09 | 0.00 | 0.00 |
September | 0.472621E+09 | 0.132148E+09 | 0.361158E+09 | 0.203005E+09 | 0.158153E+09 | 0.00 | 0.00 |
October | 0.516796E+09 | 0.270149E+09 | 0.440528E+09 | 0.312128E+09 | 0.128400E+09 | 0.00 | 0.00 |
November | 0.595917E+09 | 0.297322E+09 | 0.522542E+09 | 0.416794E+09 | 0.105749E+09 | 0.00 | 0.00 |
December | 0.558236E+09 | 0.357393E+09 | 0.515303E+09 | 0.417152E+09 | 98151340.49 | 0.00 | 0.00 |
Annual Sum or Average | 0.520489E+10 | 0.262177E+10 | 0.448949E+10 | 0.280123E+10 | 0.168826E+10 | 0.00 | 0.00 |
Minimum of Months | 0.246968E+09 | 81894133.48 | 0.209209E+09 | 37765624.19 | 98151340.49 | 0.00 | 0.00 |
Maximum of Months | 0.620502E+09 | 0.357393E+09 | 0.562215E+09 | 0.462814E+09 | 0.192054E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 11622669.06 | 0.305501E+09 | 58468616.74 | 0.00 | 58468616.74 | 0.00 | 0.00 |
February | 13025188.21 | 0.284206E+09 | 66376345.10 | 0.00 | 66376345.10 | 0.00 | 0.00 |
March | 47730092.75 | 0.233372E+09 | 0.100024E+09 | 5161.40 | 0.100019E+09 | 0.00 | 0.00 |
April | 69946737.03 | 0.194096E+09 | 0.121681E+09 | 797247.66 | 0.120884E+09 | 0.00 | 0.00 |
May | 0.169309E+09 | 0.103323E+09 | 0.171763E+09 | 5760607.25 | 0.166002E+09 | 0.00 | 0.00 |
June | 0.266974E+09 | 43401683.53 | 0.182244E+09 | 20379992.87 | 0.161864E+09 | 0.00 | 0.00 |
July | 0.265865E+09 | 39756717.33 | 0.178615E+09 | 12192357.35 | 0.166423E+09 | 0.00 | 0.00 |
August | 0.204775E+09 | 47345454.72 | 0.142211E+09 | 3848536.95 | 0.138363E+09 | 0.00 | 0.00 |
September | 0.146826E+09 | 83790069.39 | 0.115233E+09 | 92030.28 | 0.115141E+09 | 0.00 | 0.00 |
October | 52924065.09 | 0.217997E+09 | 85190674.52 | 0.00 | 85190674.52 | 0.00 | 0.00 |
November | 18745486.29 | 0.262637E+09 | 62584379.74 | 0.00 | 62584379.74 | 0.00 | 0.00 |
December | 9406108.45 | 0.354071E+09 | 54704647.81 | 0.00 | 54704647.81 | 0.00 | 0.00 |
Annual Sum or Average | 0.127715E+10 | 0.216950E+10 | 0.133910E+10 | 43075933.76 | 0.129602E+10 | 0.00 | 0.00 |
Minimum of Months | 9406108.45 | 39756717.33 | 54704647.81 | 0.00 | 54704647.81 | 0.00 | 0.00 |
Maximum of Months | 0.266974E+09 | 0.354071E+09 | 0.182244E+09 | 20379992.87 | 0.166423E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.113808E+10 | 0.943250E+09 | 0.112878E+10 | 0.839113E+09 | 0.289670E+09 | 0.00 | 0.00 |
February | 0.112899E+10 | 0.903448E+09 | 0.111643E+10 | 0.804030E+09 | 0.312396E+09 | 0.00 | 0.00 |
March | 0.125477E+10 | 0.773879E+09 | 0.118736E+10 | 0.731633E+09 | 0.455724E+09 | 0.00 | 0.00 |
April | 0.996150E+09 | 0.660196E+09 | 0.996011E+09 | 0.461883E+09 | 0.534128E+09 | 0.00 | 0.00 |
May | 0.129405E+10 | 0.364965E+09 | 0.112033E+10 | 0.401726E+09 | 0.718603E+09 | 0.00 | 0.00 |
June | 0.173513E+10 | 0.154013E+09 | 0.123075E+10 | 0.555877E+09 | 0.674870E+09 | 0.00 | 0.00 |
July | 0.169988E+10 | 0.140338E+09 | 0.118820E+10 | 0.479520E+09 | 0.708683E+09 | 0.00 | 0.00 |
August | 0.180183E+10 | 0.169718E+09 | 0.127437E+10 | 0.652543E+09 | 0.621823E+09 | 0.00 | 0.00 |
September | 0.159113E+10 | 0.286381E+09 | 0.119287E+10 | 0.656772E+09 | 0.536093E+09 | 0.00 | 0.00 |
October | 0.125517E+10 | 0.745889E+09 | 0.110511E+10 | 0.694257E+09 | 0.410849E+09 | 0.00 | 0.00 |
November | 0.113515E+10 | 0.853302E+09 | 0.106960E+10 | 0.755695E+09 | 0.313902E+09 | 0.00 | 0.00 |
December | 0.987835E+09 | 0.110232E+10 | 0.101733E+10 | 0.736528E+09 | 0.280804E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.160182E+11 | 0.709770E+10 | 0.136271E+11 | 0.776958E+10 | 0.585754E+10 | 0.00 | 0.00 |
Minimum of Months | 0.987835E+09 | 0.140338E+09 | 0.996011E+09 | 0.401726E+09 | 0.280804E+09 | 0.00 | 0.00 |
Maximum of Months | 0.180183E+10 | 0.110232E+10 | 0.127437E+10 | 0.839113E+09 | 0.718603E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.368961E+09 | 0.984388E+09 | 0.498951E+09 | 0.260481E+09 | 0.238470E+09 | 0.00 | 0.00 |
February | 0.479928E+09 | 0.931811E+09 | 0.598629E+09 | 0.326363E+09 | 0.272266E+09 | 0.00 | 0.00 |
March | 0.737987E+09 | 0.775609E+09 | 0.812750E+09 | 0.401441E+09 | 0.411310E+09 | 0.00 | 0.00 |
April | 0.752145E+09 | 0.656920E+09 | 0.831493E+09 | 0.331903E+09 | 0.499590E+09 | 0.00 | 0.00 |
May | 0.114899E+10 | 0.368892E+09 | 0.103772E+10 | 0.351759E+09 | 0.685964E+09 | 0.00 | 0.00 |
June | 0.164234E+10 | 0.167030E+09 | 0.119696E+10 | 0.534132E+09 | 0.662827E+09 | 0.00 | 0.00 |
July | 0.157639E+10 | 0.153461E+09 | 0.113227E+10 | 0.447200E+09 | 0.685075E+09 | 0.00 | 0.00 |
August | 0.149728E+10 | 0.183335E+09 | 0.109690E+10 | 0.511220E+09 | 0.585683E+09 | 0.00 | 0.00 |
September | 0.113197E+10 | 0.298203E+09 | 0.885350E+09 | 0.403080E+09 | 0.482270E+09 | 0.00 | 0.00 |
October | 0.645559E+09 | 0.745557E+09 | 0.660810E+09 | 0.304019E+09 | 0.356791E+09 | 0.00 | 0.00 |
November | 0.402102E+09 | 0.870085E+09 | 0.494509E+09 | 0.234599E+09 | 0.259910E+09 | 0.00 | 0.00 |
December | 0.301537E+09 | 0.115055E+10 | 0.441447E+09 | 0.214985E+09 | 0.226462E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.106852E+11 | 0.728585E+10 | 0.968780E+10 | 0.432118E+10 | 0.536662E+10 | 0.00 | 0.00 |
Minimum of Months | 0.301537E+09 | 0.153461E+09 | 0.441447E+09 | 0.214985E+09 | 0.226462E+09 | 0.00 | 0.00 |
Maximum of Months | 0.164234E+10 | 0.115055E+10 | 0.119696E+10 | 0.534132E+09 | 0.685964E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.134871E+10 | 0.120060E+10 | 0.134483E+10 | 0.100279E+10 | 0.342038E+09 | 0.00 | 0.00 |
February | 0.115795E+10 | 0.115232E+10 | 0.118493E+10 | 0.827813E+09 | 0.357113E+09 | 0.00 | 0.00 |
March | 0.108520E+10 | 0.102415E+10 | 0.108254E+10 | 0.572256E+09 | 0.510288E+09 | 0.00 | 0.00 |
April | 0.730544E+09 | 0.880188E+09 | 0.812278E+09 | 0.228713E+09 | 0.583564E+09 | 0.00 | 0.00 |
May | 0.960151E+09 | 0.506523E+09 | 0.887296E+09 | 0.111552E+09 | 0.775744E+09 | 0.00 | 0.00 |
June | 0.122078E+10 | 0.243297E+09 | 0.848098E+09 | 0.125978E+09 | 0.722120E+09 | 0.00 | 0.00 |
July | 0.126734E+10 | 0.232023E+09 | 0.870747E+09 | 0.108832E+09 | 0.761915E+09 | 0.00 | 0.00 |
August | 0.133040E+10 | 0.277168E+09 | 0.923657E+09 | 0.261592E+09 | 0.662065E+09 | 0.00 | 0.00 |
September | 0.137721E+10 | 0.438032E+09 | 0.103216E+10 | 0.440055E+09 | 0.592107E+09 | 0.00 | 0.00 |
October | 0.126165E+10 | 0.993586E+09 | 0.113905E+10 | 0.676295E+09 | 0.462759E+09 | 0.00 | 0.00 |
November | 0.133729E+10 | 0.109390E+10 | 0.126778E+10 | 0.903077E+09 | 0.364706E+09 | 0.00 | 0.00 |
December | 0.119131E+10 | 0.139157E+10 | 0.123503E+10 | 0.903852E+09 | 0.331175E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.142685E+11 | 0.943335E+10 | 0.126284E+11 | 0.616280E+10 | 0.646559E+10 | 0.00 | 0.00 |
Minimum of Months | 0.730544E+09 | 0.232023E+09 | 0.812278E+09 | 0.108832E+09 | 0.331175E+09 | 0.00 | 0.00 |
Maximum of Months | 0.137721E+10 | 0.139157E+10 | 0.134483E+10 | 0.100279E+10 | 0.775744E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.118730E+10 | 0.946597E+09 | 0.115782E+10 | 0.866936E+09 | 0.290881E+09 | 0.00 | 0.00 |
February | 0.110349E+10 | 0.905258E+09 | 0.109713E+10 | 0.785573E+09 | 0.311553E+09 | 0.00 | 0.00 |
March | 0.119334E+10 | 0.775447E+09 | 0.114049E+10 | 0.683221E+09 | 0.457271E+09 | 0.00 | 0.00 |
April | 0.881806E+09 | 0.668969E+09 | 0.901570E+09 | 0.378772E+09 | 0.522798E+09 | 0.00 | 0.00 |
May | 0.120035E+10 | 0.383541E+09 | 0.103634E+10 | 0.318183E+09 | 0.718156E+09 | 0.00 | 0.00 |
June | 0.161227E+10 | 0.165272E+09 | 0.113474E+10 | 0.466997E+09 | 0.667743E+09 | 0.00 | 0.00 |
July | 0.146474E+10 | 0.144553E+09 | 0.101351E+10 | 0.315680E+09 | 0.697834E+09 | 0.00 | 0.00 |
August | 0.159131E+10 | 0.171571E+09 | 0.112418E+10 | 0.526138E+09 | 0.598038E+09 | 0.00 | 0.00 |
September | 0.149375E+10 | 0.293691E+09 | 0.111365E+10 | 0.572357E+09 | 0.541296E+09 | 0.00 | 0.00 |
October | 0.128537E+10 | 0.747447E+09 | 0.112371E+10 | 0.717715E+09 | 0.405998E+09 | 0.00 | 0.00 |
November | 0.118651E+10 | 0.853732E+09 | 0.110860E+10 | 0.797619E+09 | 0.310977E+09 | 0.00 | 0.00 |
December | 0.992705E+09 | 0.109799E+10 | 0.102369E+10 | 0.745592E+09 | 0.278098E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.151929E+11 | 0.715407E+10 | 0.129754E+11 | 0.717478E+10 | 0.580064E+10 | 0.00 | 0.00 |
Minimum of Months | 0.881806E+09 | 0.144553E+09 | 0.901570E+09 | 0.315680E+09 | 0.278098E+09 | 0.00 | 0.00 |
Maximum of Months | 0.161227E+10 | 0.109799E+10 | 0.115782E+10 | 0.866936E+09 | 0.718156E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.437418E+09 | 0.100230E+10 | 0.527984E+09 | 0.288304E+09 | 0.239680E+09 | 0.00 | 0.00 |
February | 0.467922E+09 | 0.940691E+09 | 0.579329E+09 | 0.307906E+09 | 0.271423E+09 | 0.00 | 0.00 |
March | 0.690392E+09 | 0.790072E+09 | 0.765886E+09 | 0.353029E+09 | 0.412856E+09 | 0.00 | 0.00 |
April | 0.638899E+09 | 0.668755E+09 | 0.737052E+09 | 0.248792E+09 | 0.488260E+09 | 0.00 | 0.00 |
May | 0.104471E+10 | 0.383797E+09 | 0.953732E+09 | 0.268215E+09 | 0.685517E+09 | 0.00 | 0.00 |
June | 0.152222E+10 | 0.172361E+09 | 0.110095E+10 | 0.445253E+09 | 0.655699E+09 | 0.00 | 0.00 |
July | 0.134558E+10 | 0.154242E+09 | 0.957587E+09 | 0.283361E+09 | 0.674226E+09 | 0.00 | 0.00 |
August | 0.129587E+10 | 0.185490E+09 | 0.946712E+09 | 0.384815E+09 | 0.561898E+09 | 0.00 | 0.00 |
September | 0.104189E+10 | 0.311681E+09 | 0.806137E+09 | 0.318665E+09 | 0.487473E+09 | 0.00 | 0.00 |
October | 0.686106E+09 | 0.756912E+09 | 0.679417E+09 | 0.327477E+09 | 0.351940E+09 | 0.00 | 0.00 |
November | 0.465384E+09 | 0.877191E+09 | 0.533508E+09 | 0.276523E+09 | 0.256986E+09 | 0.00 | 0.00 |
December | 0.327819E+09 | 0.116364E+10 | 0.447805E+09 | 0.224048E+09 | 0.223756E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.996421E+10 | 0.740713E+10 | 0.903610E+10 | 0.372639E+10 | 0.530971E+10 | 0.00 | 0.00 |
Minimum of Months | 0.327819E+09 | 0.154242E+09 | 0.447805E+09 | 0.224048E+09 | 0.223756E+09 | 0.00 | 0.00 |
Maximum of Months | 0.152222E+10 | 0.116364E+10 | 0.110095E+10 | 0.445253E+09 | 0.685517E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.117185E+10 | 0.493607E+09 | 0.103088E+10 | 0.848620E+09 | 0.182264E+09 | 0.00 | 0.00 |
February | 0.987151E+09 | 0.473450E+09 | 0.881068E+09 | 0.700545E+09 | 0.180523E+09 | 0.00 | 0.00 |
March | 0.833250E+09 | 0.409056E+09 | 0.732741E+09 | 0.484268E+09 | 0.248473E+09 | 0.00 | 0.00 |
April | 0.482349E+09 | 0.356723E+09 | 0.464323E+09 | 0.192089E+09 | 0.272233E+09 | 0.00 | 0.00 |
May | 0.512720E+09 | 0.200388E+09 | 0.435993E+09 | 83841458.20 | 0.352151E+09 | 0.00 | 0.00 |
June | 0.587281E+09 | 80244136.68 | 0.383607E+09 | 69247409.02 | 0.314360E+09 | 0.00 | 0.00 |
July | 0.629538E+09 | 70944136.28 | 0.409426E+09 | 69748186.78 | 0.339677E+09 | 0.00 | 0.00 |
August | 0.784519E+09 | 85826584.49 | 0.520940E+09 | 0.214319E+09 | 0.306621E+09 | 0.00 | 0.00 |
September | 0.917435E+09 | 0.150111E+09 | 0.662223E+09 | 0.372232E+09 | 0.289990E+09 | 0.00 | 0.00 |
October | 0.980278E+09 | 0.389421E+09 | 0.807757E+09 | 0.572321E+09 | 0.235436E+09 | 0.00 | 0.00 |
November | 0.111898E+10 | 0.447740E+09 | 0.958139E+09 | 0.764237E+09 | 0.193901E+09 | 0.00 | 0.00 |
December | 0.104105E+10 | 0.575112E+09 | 0.944865E+09 | 0.764893E+09 | 0.179971E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.100464E+11 | 0.373262E+10 | 0.823196E+10 | 0.513636E+10 | 0.309560E+10 | 0.00 | 0.00 |
Minimum of Months | 0.482349E+09 | 70944136.28 | 0.383607E+09 | 69247409.02 | 0.179971E+09 | 0.00 | 0.00 |
Maximum of Months | 0.117185E+10 | 0.575112E+09 | 0.103088E+10 | 0.848620E+09 | 0.352151E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 59369378.76 | 0.306069E+10 | 0.511513E+09 | 0.00 | 0.511513E+09 | 0.00 | 0.00 |
February | 65881959.91 | 0.285720E+10 | 0.580694E+09 | 0.00 | 0.580694E+09 | 0.00 | 0.00 |
March | 0.311163E+09 | 0.238585E+10 | 0.875064E+09 | 45154.60 | 0.875019E+09 | 0.00 | 0.00 |
April | 0.490326E+09 | 0.200773E+10 | 0.106453E+10 | 6974728.30 | 0.105755E+10 | 0.00 | 0.00 |
May | 0.129758E+10 | 0.108373E+10 | 0.150267E+10 | 50396724.07 | 0.145227E+10 | 0.00 | 0.00 |
June | 0.216770E+10 | 0.498188E+09 | 0.159436E+10 | 0.178295E+09 | 0.141606E+10 | 0.00 | 0.00 |
July | 0.216442E+10 | 0.476148E+09 | 0.156262E+10 | 0.106665E+09 | 0.145595E+10 | 0.00 | 0.00 |
August | 0.163068E+10 | 0.563809E+09 | 0.124413E+10 | 33668959.93 | 0.121047E+10 | 0.00 | 0.00 |
September | 0.114817E+10 | 0.914697E+09 | 0.100812E+10 | 805127.75 | 0.100731E+10 | 0.00 | 0.00 |
October | 0.359529E+09 | 0.222943E+10 | 0.745291E+09 | 0.00 | 0.745291E+09 | 0.00 | 0.00 |
November | 0.107711E+09 | 0.266477E+10 | 0.547520E+09 | 0.00 | 0.547520E+09 | 0.00 | 0.00 |
December | 48239046.27 | 0.352150E+10 | 0.478584E+09 | 0.00 | 0.478584E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.985076E+10 | 0.222637E+11 | 0.117151E+11 | 0.376850E+09 | 0.113382E+11 | 0.00 | 0.00 |
Minimum of Months | 48239046.27 | 0.476148E+09 | 0.478584E+09 | 0.00 | 0.478584E+09 | 0.00 | 0.00 |
Maximum of Months | 0.216770E+10 | 0.352150E+10 | 0.159436E+10 | 0.178295E+09 | 0.145595E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 52170166.25 | 0.312558E+10 | 0.511513E+09 | 0.00 | 0.511513E+09 | 0.00 | 0.00 |
February | 59997134.30 | 0.291904E+10 | 0.580694E+09 | 0.00 | 0.580694E+09 | 0.00 | 0.00 |
March | 0.294959E+09 | 0.243743E+10 | 0.875064E+09 | 45154.60 | 0.875019E+09 | 0.00 | 0.00 |
April | 0.470890E+09 | 0.205189E+10 | 0.106453E+10 | 6974728.30 | 0.105755E+10 | 0.00 | 0.00 |
May | 0.127374E+10 | 0.110489E+10 | 0.150267E+10 | 50396724.07 | 0.145227E+10 | 0.00 | 0.00 |
June | 0.214846E+10 | 0.510469E+09 | 0.159436E+10 | 0.178295E+09 | 0.141606E+10 | 0.00 | 0.00 |
July | 0.214514E+10 | 0.489266E+09 | 0.156262E+10 | 0.106665E+09 | 0.145595E+10 | 0.00 | 0.00 |
August | 0.161309E+10 | 0.578878E+09 | 0.124413E+10 | 33668959.93 | 0.121047E+10 | 0.00 | 0.00 |
September | 0.113271E+10 | 0.934152E+09 | 0.100812E+10 | 805127.75 | 0.100731E+10 | 0.00 | 0.00 |
October | 0.345670E+09 | 0.227203E+10 | 0.745291E+09 | 0.00 | 0.745291E+09 | 0.00 | 0.00 |
November | 0.100473E+09 | 0.272204E+10 | 0.547520E+09 | 0.00 | 0.547520E+09 | 0.00 | 0.00 |
December | 43138521.77 | 0.359761E+10 | 0.478584E+09 | 0.00 | 0.478584E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.968045E+10 | 0.227433E+11 | 0.117151E+11 | 0.376850E+09 | 0.113382E+11 | 0.00 | 0.00 |
Minimum of Months | 43138521.77 | 0.489266E+09 | 0.478584E+09 | 0.00 | 0.478584E+09 | 0.00 | 0.00 |
Maximum of Months | 0.214846E+10 | 0.359761E+10 | 0.159436E+10 | 0.178295E+09 | 0.145595E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.157373E+10 | 0.194362E+10 | 0.162767E+10 | 0.109956E+10 | 0.528117E+09 | 0.00 | 0.00 |
February | 0.166912E+10 | 0.189968E+10 | 0.171498E+10 | 0.113035E+10 | 0.584635E+09 | 0.00 | 0.00 |
March | 0.212096E+10 | 0.165678E+10 | 0.200001E+10 | 0.113302E+10 | 0.866993E+09 | 0.00 | 0.00 |
April | 0.187699E+10 | 0.144605E+10 | 0.182741E+10 | 0.793739E+09 | 0.103367E+10 | 0.00 | 0.00 |
May | 0.271029E+10 | 0.837782E+09 | 0.215794E+10 | 0.753436E+09 | 0.140450E+10 | 0.00 | 0.00 |
June | 0.373734E+10 | 0.406364E+09 | 0.242757E+10 | 0.108994E+10 | 0.133763E+10 | 0.00 | 0.00 |
July | 0.364362E+10 | 0.387325E+09 | 0.232035E+10 | 0.926658E+09 | 0.139369E+10 | 0.00 | 0.00 |
August | 0.366114E+10 | 0.434686E+09 | 0.237114E+10 | 0.116369E+10 | 0.120745E+10 | 0.00 | 0.00 |
September | 0.302042E+10 | 0.652988E+09 | 0.207811E+10 | 0.105980E+10 | 0.101831E+10 | 0.00 | 0.00 |
October | 0.205940E+10 | 0.156883E+10 | 0.176584E+10 | 0.998232E+09 | 0.767605E+09 | 0.00 | 0.00 |
November | 0.162419E+10 | 0.176939E+10 | 0.156405E+10 | 0.990260E+09 | 0.573786E+09 | 0.00 | 0.00 |
December | 0.131182E+10 | 0.232607E+10 | 0.145873E+10 | 0.951482E+09 | 0.507244E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.290090E+11 | 0.153296E+11 | 0.233138E+11 | 0.120902E+11 | 0.112236E+11 | 0.00 | 0.00 |
Minimum of Months | 0.131182E+10 | 0.387325E+09 | 0.145873E+10 | 0.753436E+09 | 0.507244E+09 | 0.00 | 0.00 |
Maximum of Months | 0.373734E+10 | 0.232607E+10 | 0.242757E+10 | 0.116369E+10 | 0.140450E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.291953E+10 | 0.211279E+10 | 0.279952E+10 | 0.216021E+10 | 0.639310E+09 | 0.00 | 0.00 |
February | 0.248131E+10 | 0.204507E+10 | 0.244187E+10 | 0.178327E+10 | 0.658595E+09 | 0.00 | 0.00 |
March | 0.223226E+10 | 0.181812E+10 | 0.216521E+10 | 0.123275E+10 | 0.932460E+09 | 0.00 | 0.00 |
April | 0.141963E+10 | 0.158344E+10 | 0.154688E+10 | 0.491364E+09 | 0.105551E+10 | 0.00 | 0.00 |
May | 0.174226E+10 | 0.924071E+09 | 0.162496E+10 | 0.230699E+09 | 0.139426E+10 | 0.00 | 0.00 |
June | 0.215714E+10 | 0.447892E+09 | 0.152304E+10 | 0.237393E+09 | 0.128565E+10 | 0.00 | 0.00 |
July | 0.226525E+10 | 0.425033E+09 | 0.157788E+10 | 0.214113E+09 | 0.136377E+10 | 0.00 | 0.00 |
August | 0.250146E+10 | 0.503514E+09 | 0.175257E+10 | 0.557102E+09 | 0.119547E+10 | 0.00 | 0.00 |
September | 0.270471E+10 | 0.774512E+09 | 0.203131E+10 | 0.947814E+09 | 0.108349E+10 | 0.00 | 0.00 |
October | 0.261746E+10 | 0.175062E+10 | 0.231168E+10 | 0.145687E+10 | 0.854802E+09 | 0.00 | 0.00 |
November | 0.285079E+10 | 0.193566E+10 | 0.262668E+10 | 0.194541E+10 | 0.681277E+09 | 0.00 | 0.00 |
December | 0.257730E+10 | 0.247322E+10 | 0.256926E+10 | 0.194708E+10 | 0.622186E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.284691E+11 | 0.167939E+11 | 0.249709E+11 | 0.132041E+11 | 0.117668E+11 | 0.00 | 0.00 |
Minimum of Months | 0.141963E+10 | 0.425033E+09 | 0.152304E+10 | 0.214113E+09 | 0.622186E+09 | 0.00 | 0.00 |
Maximum of Months | 0.291953E+10 | 0.247322E+10 | 0.279952E+10 | 0.216021E+10 | 0.139426E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 0.85 | -1.5 | -4.5 | 2.30 | -12.1 | 27.63 | 226.20 | 0.01 |
February | -0.2 | -2.7 | -6.1 | 3.74 | -13.6 | 32.55 | 253.27 | 0.01 |
March | 4.82 | 0.36 | -5.5 | 4.48 | -7.8 | 54.65 | 233.06 | 0.03 |
April | 6.08 | 2.29 | -2.0 | 5.23 | -4.9 | 81.86 | 179.11 | 0.05 |
May | 13.74 | 7.52 | 1.82 | 4.10 | 2.75 | 117.64 | 180.87 | 0.01 |
June | 22.16 | 12.46 | 5.10 | 4.19 | 9.76 | 95.26 | 290.95 | 0.00 |
July | 22.71 | 13.25 | 6.43 | 4.25 | 12.01 | 110.54 | 215.12 | 0.03 |
August | 21.74 | 12.79 | 6.20 | 3.81 | 10.76 | 77.72 | 272.61 | 0.02 |
September | 18.54 | 9.35 | 1.35 | 4.13 | 5.52 | 70.51 | 233.03 | 0.01 |
October | 7.12 | 2.51 | -2.7 | 3.54 | -5.8 | 44.60 | 216.74 | 0.01 |
November | 3.03 | 0.31 | -2.9 | 2.79 | -8.8 | 30.71 | 220.86 | 0.01 |
December | -1.0 | -4.5 | -9.5 | 4.43 | -15.4 | 27.45 | 194.75 | 0.01 |
Annual Sum or Average | 10.02 | 4.37 | -1.0 | 3.91 | -2.2 | 64.46 | 226.11 | 0.02 |
Minimum of Months | -1.0 | -4.5 | -9.5 | 2.30 | -15.4 | 27.45 | 179.11 | 0.00 |
Maximum of Months | 22.71 | 13.25 | 6.43 | 5.23 | 12.01 | 117.64 | 290.95 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.00 | 20-JAN-12:00 | 6.97 | -11.0 | 0.50 | 6.55 | 41.00 | 961.00 |
February | 20.00 | 18-FEB-12:00 | 7.74 | -5.0 | 3.60 | 6.35 | 56.00 | 998.00 |
March | 24.00 | 14-MAR-12:00 | 7.90 | -12.0 | 3.10 | 11.65 | 160.00 | 837.50 |
April | 22.00 | 19-APR-13:09 | 8.49 | -5.7 | 5.52 | 11.55 | 235.67 | 789.67 |
May | 29.00 | 17-MAY-12:00 | 11.92 | -3.0 | 5.10 | 18.99 | 432.50 | 162.00 |
June | 39.40 | 26-JUN-14:00 | 15.63 | -2.8 | 4.60 | 21.96 | 136.50 | 752.00 |
July | 37.00 | 16-JUL-12:00 | 14.90 | -3.0 | 3.10 | 26.65 | 319.50 | 109.50 |
August | 37.00 | 16-AUG-13:00 | 16.36 | 3.00 | 3.60 | 28.27 | 90.00 | 895.00 |
September | 32.70 | 09-SEP-12:00 | 13.05 | -3.9 | 3.00 | 16.30 | 270.50 | 562.00 |
October | 27.00 | 11-OCT-13:00 | 9.73 | -9.0 | 4.60 | 12.03 | 89.50 | 844.00 |
November | 22.00 | 06-NOV-13:09 | 7.10 | -13.0 | 2.60 | 4.92 | 88.67 | 883.33 |
December | 22.00 | 01-DEC-13:00 | 7.94 | -8.0 | 2.60 | 5.13 | 49.00 | 862.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.00 | 6.97 | -13.0 | 0.50 | 4.92 | 41.00 | 109.50 | |
Maximum of Months | 39.40 | 16.36 | 3.00 | 5.52 | 28.27 | 432.50 | 998.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -19.0 | 05-JAN-18:00 | -19.0 | -19.0 | 1.50 | -37.1 | 0.00 | 0.00 |
February | -20.0 | 12-FEB-04:00 | -20.0 | -20.0 | 3.60 | -39.1 | 0.00 | 0.00 |
March | -15.6 | 19-MAR-06:00 | -15.6 | -15.6 | 10.80 | -25.3 | 24.00 | 0.00 |
April | -8.0 | 03-APR-02:00 | -8.0 | -8.0 | 3.10 | -22.2 | 0.00 | 0.00 |
May | -1.0 | 03-MAY-01:00 | -2.4 | -4.0 | 4.10 | -15.7 | 0.00 | 0.00 |
June | 6.60 | 09-JUN-03:00 | 3.45 | 0.00 | 3.60 | -6.9 | 0.00 | 0.00 |
July | 9.00 | 02-JUL-04:00 | 3.30 | -3.0 | 3.60 | -5.3 | 20.00 | 184.50 |
August | 11.00 | 12-AUG-22:00 | 7.22 | 4.00 | 4.10 | 5.13 | 0.00 | 0.00 |
September | -1.7 | 22-SEP-05:10 | -2.9 | -4.3 | 3.60 | -15.8 | 0.00 | 0.00 |
October | -10.0 | 30-OCT-03:00 | -10.0 | -10.0 | 2.60 | -18.6 | 0.00 | 0.00 |
November | -15.0 | 29-NOV-20:00 | -15.0 | -15.0 | 3.10 | -33.5 | 0.00 | 0.00 |
December | -23.0 | 22-DEC-02:00 | -23.0 | -23.0 | 3.60 | -42.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -23.0 | -23.0 | -23.0 | 1.50 | -42.7 | 0.00 | 0.00 | |
Maximum of Months | 11.00 | 7.22 | 4.00 | 10.80 | 5.13 | 24.00 | 184.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 7.55 | 20-JAN-11:00 | 20.00 | -6.0 | 2.60 | 7.95 | 43.00 | 971.50 |
February | 7.98 | 18-FEB-14:00 | 19.00 | -3.0 | 3.60 | 5.94 | 151.00 | 410.00 |
March | 8.00 | 31-MAR-17:00 | 15.00 | 2.00 | 2.60 | 1.58 | 19.50 | 261.00 |
April | 12.50 | 28-APR-13:00 | 18.00 | 9.00 | 9.80 | 9.72 | 335.00 | 196.50 |
May | 14.87 | 31-MAY-13:00 | 28.00 | 7.00 | 4.60 | 14.47 | 157.50 | 830.50 |
June | 19.65 | 18-JUN-11:00 | 29.40 | 15.50 | 6.10 | 16.85 | 272.50 | 596.00 |
July | 19.75 | 30-JUL-13:00 | 29.00 | 16.00 | 3.60 | 18.99 | 217.50 | 412.00 |
August | 18.80 | 05-AUG-14:09 | 25.83 | 15.33 | 6.62 | 20.54 | 196.33 | 4.00 |
September | 14.95 | 01-SEP-11:00 | 24.40 | 9.40 | 3.00 | 10.69 | 193.50 | 684.00 |
October | 9.73 | 11-OCT-13:00 | 27.00 | -9.0 | 4.60 | 12.03 | 89.50 | 844.00 |
November | 9.33 | 09-NOV-10:00 | 20.00 | 0.00 | 1.50 | 11.07 | 112.00 | 860.50 |
December | 7.94 | 01-DEC-13:00 | 22.00 | -8.0 | 2.60 | 5.13 | 49.00 | 862.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.55 | 15.00 | -9.0 | 1.50 | 1.58 | 19.50 | 4.00 | |
Maximum of Months | 19.75 | 29.40 | 16.00 | 9.80 | 20.54 | 335.00 | 971.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.00 | 28-JAN-10:00 | 5.00 | 5.00 | 1.00 | -6.2 | 207.00 | 309.00 |
February | 5.00 | 19-FEB-14:30 | 5.00 | 5.00 | 1.80 | -0.4 | 188.00 | 467.00 |
March | 7.00 | 17-MAR-14:00 | 8.00 | 7.39 | 8.20 | 1.16 | 121.50 | 3.00 |
April | 9.00 | 28-APR-13:00 | 18.00 | 12.50 | 9.80 | 9.72 | 335.00 | 196.50 |
May | 11.00 | 21-MAY-21:10 | 12.83 | 11.73 | 2.68 | 6.78 | 0.00 | 0.00 |
June | 15.50 | 18-JUN-11:00 | 29.40 | 19.65 | 6.10 | 16.85 | 272.50 | 596.00 |
July | 17.00 | 28-JUL-16:00 | 20.00 | 17.92 | 5.70 | 15.02 | 155.00 | 32.00 |
August | 18.00 | 04-AUG-01:00 | 18.00 | 18.00 | 2.60 | 8.74 | 0.00 | 0.00 |
September | 12.20 | 30-SEP-14:00 | 17.20 | 13.90 | 5.10 | 9.72 | 209.00 | 82.50 |
October | 6.00 | 01-OCT-19:00 | 9.00 | 7.28 | 3.10 | 3.69 | 0.00 | 0.00 |
November | 7.00 | 09-NOV-23:00 | 8.00 | 7.40 | 4.10 | 3.06 | 0.00 | 0.00 |
December | 1.00 | 30-DEC-14:00 | 7.00 | 4.06 | 9.80 | -1.2 | 101.00 | 91.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.00 | 5.00 | 4.06 | 1.00 | -6.2 | 0.00 | 0.00 | |
Maximum of Months | 18.00 | 29.40 | 19.65 | 9.80 | 16.85 | 335.00 | 596.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 8.52 | 21.53 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 7.90 | 29.36 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 8.65 | 35.75 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 10.64 | 38.62 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 13.34 | 48.35 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 16.03 | 59.81 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.97 | 52.29 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 18.66 | 51.98 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.88 | 41.73 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 15.85 | 30.82 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 13.14 | 23.90 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 10.46 | 18.59 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 13.28 | 37.76 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 7.90 | 18.59 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 18.66 | 59.81 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH LAUNDRY G WATER HEATER
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.126470E+12 | -0.124712E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175830E+10 | 82.17 | 0.00 | 0.00 |
February | 0.115194E+12 | -0.113602E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.159263E+10 | 82.17 | 0.00 | 0.00 |
March | 0.126268E+12 | -0.124497E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.177064E+10 | 82.17 | 0.00 | 0.00 |
April | 0.118934E+12 | -0.117223E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.171153E+10 | 82.17 | 0.00 | 0.00 |
May | 0.118322E+12 | -0.116552E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.177000E+10 | 82.17 | 0.00 | 0.00 |
June | 0.110093E+12 | -0.108387E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.170638E+10 | 82.17 | 0.00 | 0.00 |
July | 0.110467E+12 | -0.108706E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.176095E+10 | 82.17 | 0.00 | 0.00 |
August | 0.109306E+12 | -0.107549E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175658E+10 | 82.17 | 0.00 | 0.00 |
September | 0.107060E+12 | -0.105363E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.169741E+10 | 82.17 | 0.00 | 0.00 |
October | 0.114058E+12 | -0.112304E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175377E+10 | 82.17 | 0.00 | 0.00 |
November | 0.114824E+12 | -0.113127E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.169726E+10 | 82.17 | 0.00 | 0.00 |
December | 0.123179E+12 | -0.121425E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175425E+10 | 82.17 | 0.00 | 0.00 |
Annual Sum or Average | 0.139418E+13 | -0.137345E+13 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.207297E+11 | 82.17 | 0.00 | 0.00 |
Minimum of Months | 0.107060E+12 | -0.124712E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.177064E+10 | 82.17 | 0.00 | 0.00 |
Maximum of Months | 0.126470E+12 | -0.105363E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.159263E+10 | 82.17 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.804729E+10 | -0.788296E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164330000.4 | 82.17 | 0.00 | 0.00 |
February | 0.727183E+10 | -0.712336E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -148469970.5 | 82.17 | 0.00 | 0.00 |
March | 0.804582E+10 | -0.788155E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164266230.0 | 82.17 | 0.00 | 0.00 |
April | 0.779714E+10 | -0.763820E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -158937015.7 | 82.17 | 0.00 | 0.00 |
May | 0.804710E+10 | -0.788296E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164133366.9 | 82.17 | 0.00 | 0.00 |
June | 0.778856E+10 | -0.762976E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -158800782.0 | 82.17 | 0.00 | 0.00 |
July | 0.805549E+10 | -0.789140E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164084249.9 | 82.17 | 0.00 | 0.00 |
August | 0.804706E+10 | -0.788296E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164097129.8 | 82.17 | 0.00 | 0.00 |
September | 0.779843E+10 | -0.763961E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -158820376.5 | 82.17 | 0.00 | 0.00 |
October | 0.804576E+10 | -0.788155E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164204242.3 | 82.17 | 0.00 | 0.00 |
November | 0.778032E+10 | -0.762132E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -158997483.3 | 82.17 | 0.00 | 0.00 |
December | 0.805584E+10 | -0.789140E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164439146.2 | 82.17 | 0.00 | 0.00 |
Annual Sum or Average | 0.947806E+11 | -0.928470E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.193358E+10 | 82.17 | 0.00 | 0.00 |
Minimum of Months | 0.727183E+10 | -0.789140E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -164439146.2 | 82.17 | 0.00 | 0.00 |
Maximum of Months | 0.805584E+10 | -0.712336E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -148469970.5 | 82.17 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.767362E+11 | -0.752230E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.151312E+10 | 60.05 | 0.00 | 0.00 |
February | 0.701569E+11 | -0.687840E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.137291E+10 | 60.05 | 0.00 | 0.00 |
March | 0.766350E+11 | -0.751048E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.153024E+10 | 60.05 | 0.00 | 0.00 |
April | 0.713061E+11 | -0.698280E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.147811E+10 | 60.05 | 0.00 | 0.00 |
May | 0.697415E+11 | -0.682122E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.152935E+10 | 60.05 | 0.00 | 0.00 |
June | 0.637019E+11 | -0.622309E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.147098E+10 | 60.05 | 0.00 | 0.00 |
July | 0.629172E+11 | -0.614004E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.151681E+10 | 60.05 | 0.00 | 0.00 |
August | 0.619746E+11 | -0.604639E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.151075E+10 | 60.05 | 0.00 | 0.00 |
September | 0.610483E+11 | -0.595897E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.145854E+10 | 60.05 | 0.00 | 0.00 |
October | 0.660134E+11 | -0.645065E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.150686E+10 | 60.05 | 0.00 | 0.00 |
November | 0.677222E+11 | -0.662639E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.145833E+10 | 60.05 | 0.00 | 0.00 |
December | 0.738877E+11 | -0.723802E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.150751E+10 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.821841E+12 | -0.803987E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.178535E+11 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.610483E+11 | -0.752230E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.153024E+10 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.767362E+11 | -0.595897E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.137291E+10 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: LOBBY_FLR_1_DAYLCTRL
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.87 | 0.86 | 01-JAN-07:49 | 9411.76 | 39.82 | 274.00 | 270.83 | 3585.01 | 33.84 | 232.83 | 260.17 |
February | 245.50 | 0.86 | 0.86 | 01-FEB-10:39 | 12828.02 | 39.21 | 238.17 | 266.17 | 1087.62 | 26.11 | 174.83 | 234.00 |
March | 296.17 | 0.87 | 0.86 | 01-MAR-06:00 | 4576.51 | 25.81 | 135.17 | 332.33 | 660.30 | 22.47 | 239.83 | 275.83 |
April | 296.67 | 0.87 | 0.86 | 03-APR-09:39 | 1458.46 | 20.50 | 95.33 | 344.83 | 585.86 | 22.21 | 220.17 | 280.33 |
May | 415.33 | 0.87 | 0.86 | 01-MAY-06:30 | 1377.33 | 20.13 | 131.50 | 396.00 | 539.74 | 21.85 | 296.33 | 338.83 |
June | 421.50 | 0.87 | 0.86 | 01-JUN-06:10 | 1061.34 | 20.19 | 63.83 | 396.00 | 446.53 | 21.95 | 311.00 | 326.33 |
July | 430.33 | 0.88 | 0.86 | 01-JUL-08:30 | 1233.07 | 20.02 | 104.50 | 401.83 | 492.88 | 21.76 | 290.00 | 334.17 |
August | 394.50 | 0.87 | 0.86 | 01-AUG-06:30 | 1230.92 | 20.26 | 99.83 | 374.33 | 513.94 | 22.00 | 296.33 | 320.33 |
September | 354.00 | 0.87 | 0.86 | 01-SEP-07:10 | 1525.41 | 20.51 | 102.00 | 336.67 | 627.01 | 22.29 | 275.50 | 291.67 |
October | 262.67 | 0.87 | 0.86 | 01-OCT-06:49 | 10055.37 | 35.15 | 226.00 | 302.50 | 839.89 | 24.13 | 237.67 | 258.00 |
November | 257.67 | 0.87 | 0.86 | 01-NOV-08:39 | 10866.39 | 39.70 | 254.00 | 267.83 | 1980.07 | 30.31 | 213.50 | 240.17 |
December | 251.17 | 0.86 | 0.86 | 01-DEC-07:40 | 8723.34 | 40.23 | 250.83 | 260.17 | 5340.79 | 38.34 | 239.50 | 244.17 |
Annual Sum or Average | 3902.00 | 0.87 | 4548.30 | 26.83 | 1975.17 | 3949.50 | 1217.08 | 24.87 | 3027.50 | 3404.00 | ||
Minimum of Months | 245.50 | 0.86 | 0.86 | 1061.34 | 20.02 | 63.83 | 260.17 | 446.53 | 21.76 | 174.83 | 234.00 | |
Maximum of Months | 430.33 | 0.88 | 0.86 | 12828.02 | 40.23 | 274.00 | 401.83 | 5340.79 | 38.34 | 311.00 | 338.83 |
Report: DaylightingReportMonthly
For: CAFE_FLR_1_DAYLCTRL
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.25 | 0.22 | 01-JAN-07:40 | 10066.27 | 39.88 | 274.17 | 276.83 | 4238.88 | 33.43 | 225.33 | 268.50 |
February | 245.50 | 0.24 | 0.22 | 01-FEB-10:39 | 13482.96 | 39.28 | 238.17 | 272.67 | 1741.22 | 25.34 | 128.83 | 257.00 |
March | 296.17 | 0.25 | 0.22 | 01-MAR-06:00 | 5049.29 | 25.80 | 138.00 | 340.83 | 1131.61 | 22.21 | 185.83 | 312.17 |
April | 296.67 | 0.26 | 0.22 | 03-APR-09:39 | 1771.78 | 20.81 | 110.50 | 355.17 | 898.25 | 22.36 | 221.83 | 323.67 |
May | 415.33 | 0.27 | 0.22 | 01-MAY-05:00 | 1609.16 | 20.70 | 185.00 | 406.17 | 770.74 | 22.23 | 322.50 | 378.17 |
June | 421.50 | 0.27 | 0.22 | 01-JUN-05:40 | 1270.76 | 20.76 | 144.50 | 412.00 | 655.35 | 22.33 | 332.17 | 376.00 |
July | 430.33 | 0.27 | 0.22 | 01-JUL-06:10 | 1448.41 | 20.62 | 171.67 | 417.83 | 707.48 | 22.17 | 327.50 | 379.50 |
August | 394.50 | 0.27 | 0.22 | 01-AUG-06:10 | 1515.31 | 20.61 | 124.33 | 383.50 | 797.61 | 22.18 | 295.17 | 356.67 |
September | 354.00 | 0.26 | 0.22 | 01-SEP-06:19 | 1906.43 | 20.61 | 122.17 | 347.00 | 1007.06 | 22.25 | 251.17 | 321.33 |
October | 262.67 | 0.24 | 0.22 | 01-OCT-06:40 | 10632.89 | 35.12 | 219.00 | 311.83 | 1415.64 | 23.67 | 184.00 | 289.17 |
November | 257.67 | 0.25 | 0.22 | 01-NOV-08:39 | 11539.98 | 39.76 | 254.00 | 274.83 | 2651.00 | 29.65 | 176.83 | 258.83 |
December | 251.17 | 0.24 | 0.22 | 01-DEC-07:40 | 9384.62 | 40.28 | 250.83 | 264.17 | 6000.30 | 38.20 | 231.83 | 257.33 |
Annual Sum or Average | 3902.00 | 0.26 | 4955.88 | 27.09 | 2232.33 | 4062.83 | 1623.55 | 24.84 | 2883.00 | 3778.33 | ||
Minimum of Months | 245.50 | 0.24 | 0.22 | 1270.76 | 20.61 | 110.50 | 264.17 | 655.35 | 22.17 | 128.83 | 257.00 | |
Maximum of Months | 430.33 | 0.27 | 0.22 | 13482.96 | 40.28 | 274.17 | 417.83 | 6000.30 | 38.20 | 332.17 | 379.50 |
Report: DaylightingReportMonthly
For: DINING_FLR_6_DAYLCTRL
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.70 | 0.60 | 01-JAN-10:30 | 349.18 | 14.29 | 0.00 | 225.33 | 184.13 | 17.98 | 0.00 | 91.50 |
February | 245.50 | 0.66 | 0.60 | 01-FEB-10:50 | 394.86 | 15.63 | 0.00 | 252.00 | 213.84 | 19.23 | 1.67 | 118.67 |
March | 296.17 | 0.63 | 0.60 | 01-MAR-07:30 | 544.95 | 16.88 | 0.00 | 328.33 | 272.52 | 20.23 | 25.83 | 263.33 |
April | 296.67 | 0.62 | 0.60 | 03-APR-09:39 | 771.22 | 18.01 | 0.00 | 355.50 | 351.23 | 21.19 | 115.83 | 304.50 |
May | 415.33 | 0.62 | 0.60 | 01-MAY-06:10 | 983.57 | 18.34 | 0.00 | 413.83 | 415.77 | 21.99 | 260.83 | 386.33 |
June | 421.50 | 0.61 | 0.60 | 01-JUN-04:00 | 1044.39 | 19.03 | 11.00 | 422.33 | 447.39 | 24.27 | 294.00 | 409.17 |
July | 430.33 | 0.62 | 0.60 | 01-JUL-04:00 | 1015.92 | 18.49 | 1.83 | 427.83 | 428.61 | 22.86 | 280.83 | 401.17 |
August | 394.50 | 0.62 | 0.60 | 01-AUG-05:00 | 764.19 | 18.01 | 0.00 | 389.83 | 346.53 | 21.25 | 166.17 | 351.00 |
September | 354.00 | 0.63 | 0.60 | 01-SEP-06:30 | 611.02 | 17.28 | 0.00 | 339.33 | 297.57 | 20.56 | 61.50 | 282.33 |
October | 262.67 | 0.64 | 0.60 | 01-OCT-06:00 | 495.96 | 16.66 | 0.00 | 293.50 | 264.36 | 20.11 | 4.00 | 212.33 |
November | 257.67 | 0.68 | 0.60 | 01-NOV-08:00 | 385.02 | 15.09 | 0.00 | 244.00 | 209.50 | 18.74 | 0.17 | 112.17 |
December | 251.17 | 0.69 | 0.60 | 01-DEC-08:00 | 365.96 | 14.71 | 0.00 | 229.17 | 195.18 | 18.40 | 0.00 | 90.83 |
Annual Sum or Average | 3902.00 | 0.64 | 694.20 | 17.15 | 12.83 | 3921.00 | 319.97 | 20.90 | 1210.83 | 3023.33 | ||
Minimum of Months | 245.50 | 0.61 | 0.60 | 349.18 | 14.29 | 0.00 | 225.33 | 184.13 | 17.98 | 0.00 | 90.83 | |
Maximum of Months | 430.33 | 0.70 | 0.60 | 1044.39 | 19.03 | 11.00 | 427.83 | 447.39 | 24.27 | 294.00 | 409.17 |
Report: DaylightingReportMonthly
For: BANQUET_FLR_6_DAYLCTRL
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.70 | 0.60 | 01-JAN-10:30 | 349.18 | 14.29 | 0.00 | 225.33 | 184.13 | 17.98 | 0.00 | 91.50 |
February | 245.50 | 0.66 | 0.60 | 01-FEB-10:50 | 394.86 | 15.63 | 0.00 | 252.00 | 213.84 | 19.23 | 1.67 | 118.67 |
March | 296.17 | 0.63 | 0.60 | 01-MAR-07:30 | 544.95 | 16.88 | 0.00 | 328.33 | 272.52 | 20.23 | 25.83 | 263.33 |
April | 296.67 | 0.62 | 0.60 | 03-APR-09:39 | 771.22 | 18.01 | 0.00 | 355.50 | 351.23 | 21.19 | 115.83 | 304.50 |
May | 415.33 | 0.62 | 0.60 | 01-MAY-06:10 | 983.57 | 18.34 | 0.00 | 413.83 | 415.77 | 21.99 | 260.83 | 386.33 |
June | 421.50 | 0.61 | 0.60 | 01-JUN-04:00 | 1044.39 | 19.03 | 11.00 | 422.33 | 447.39 | 24.27 | 294.00 | 409.17 |
July | 430.33 | 0.62 | 0.60 | 01-JUL-04:00 | 1015.92 | 18.49 | 1.83 | 427.83 | 428.61 | 22.86 | 280.83 | 401.17 |
August | 394.50 | 0.62 | 0.60 | 01-AUG-05:00 | 764.19 | 18.01 | 0.00 | 389.83 | 346.53 | 21.25 | 166.17 | 351.00 |
September | 354.00 | 0.63 | 0.60 | 01-SEP-06:30 | 611.02 | 17.28 | 0.00 | 339.33 | 297.57 | 20.56 | 61.50 | 282.33 |
October | 262.67 | 0.64 | 0.60 | 01-OCT-06:00 | 495.96 | 16.66 | 0.00 | 293.50 | 264.36 | 20.11 | 4.00 | 212.33 |
November | 257.67 | 0.68 | 0.60 | 01-NOV-08:00 | 385.02 | 15.09 | 0.00 | 244.00 | 209.50 | 18.74 | 0.17 | 112.17 |
December | 251.17 | 0.69 | 0.60 | 01-DEC-08:00 | 365.96 | 14.71 | 0.00 | 229.17 | 195.18 | 18.40 | 0.00 | 90.83 |
Annual Sum or Average | 3902.00 | 0.64 | 694.20 | 17.15 | 12.83 | 3921.00 | 319.97 | 20.90 | 1210.83 | 3023.33 | ||
Minimum of Months | 245.50 | 0.61 | 0.60 | 349.18 | 14.29 | 0.00 | 225.33 | 184.13 | 17.98 | 0.00 | 90.83 | |
Maximum of Months | 430.33 | 0.70 | 0.60 | 1044.39 | 19.03 | 11.00 | 427.83 | 447.39 | 24.27 | 294.00 | 409.17 |
Report: CoilReportMonthly
For: FLR_3_DOAS HEATING COIL
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.164443E+10 | 8308.18 | 05-JAN-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176228E+10 | 6771.11 | 12-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.704855E+09 | 5495.11 | 04-MAR-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.320535E+09 | 2460.81 | 03-APR-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 15734.47 | 0.44 | 24-MAY-19:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 31347.18 | 0.45 | 21-JUN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 40835.88 | 0.45 | 08-JUL-02:70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 32874.84 | 0.45 | 23-AUG-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 947394.74 | 187.75 | 22-SEP-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.507572E+09 | 5168.31 | 30-OCT-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.821371E+09 | 5467.81 | 29-NOV-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.309429E+10 | 8851.47 | 20-DEC-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.885640E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 15734.47 | 0.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.309429E+10 | 8851.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.757998E+11 | 150847.87 | 15-JAN-11:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.737422E+11 | 146764.31 | 24-FEB-08:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.745891E+11 | 153427.71 | 05-MAR-11:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.736044E+11 | 131939.77 | 17-APR-10:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.725147E+11 | 127008.13 | 19-MAY-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.510729E+10 | 110678.66 | 09-JUN-03:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.457452E+10 | 76388.84 | 02-JUL-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.467773E+10 | 56993.40 | 12-AUG-23:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.280264E+11 | 133312.69 | 21-SEP-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.660362E+11 | 138512.20 | 09-OCT-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.591552E+11 | 149340.71 | 02-NOV-10:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.102798E+12 | 150045.60 | 25-DEC-11:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.640626E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.457452E+10 | 56993.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.102798E+12 | 153427.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.655474E+09 | 2221.11 | 05-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.956246E+09 | 2079.57 | 05-FEB-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.927326E+09 | 2176.37 | 19-MAR-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.868374E+09 | 1684.75 | 03-APR-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 76400946.37 | 777.34 | 01-MAY-03:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 20489881.25 | 732.01 | 22-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.651236E+09 | 1999.93 | 31-OCT-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.627465E+09 | 1899.19 | 30-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.127092E+10 | 2711.64 | 20-DEC-18:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.605393E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.127092E+10 | 2711.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 617565.22 | 85.33 | 05-JAN-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 14050755.45 | 305.81 | 06-FEB-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2707690.82 | 189.84 | 19-MAR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 21663.00 | 36.11 | 03-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4459762.00 | 250.11 | 31-OCT-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 62652.50 | 65.03 | 01-NOV-09:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 19572499.64 | 469.19 | 21-DEC-10:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 41492588.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19572499.64 | 469.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 94409443.32 | 701.05 | 06-JAN-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.217272E+09 | 687.84 | 06-FEB-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 44723314.15 | 462.22 | 19-MAR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 27970284.32 | 441.36 | 03-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 40198207.73 | 604.52 | 31-OCT-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 79463870.97 | 550.18 | 30-NOV-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.388278E+09 | 1112.33 | 22-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.892315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.388278E+09 | 1112.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.164965E+09 | 643.48 | 05-JAN-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.310099E+09 | 589.68 | 06-FEB-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.128117E+09 | 442.66 | 19-MAR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 77531369.88 | 399.26 | 03-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 79426945.93 | 567.45 | 31-OCT-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.121171E+09 | 511.20 | 30-NOV-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.442205E+09 | 942.21 | 21-DEC-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.132352E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.442205E+09 | 942.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1399469.80 | 283.03 | 23-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1399469.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1399469.80 | 283.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.157033E+09 | 4858.35 | 05-JAN-09:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.449419E+09 | 4700.02 | 05-FEB-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.393884E+09 | 3831.36 | 19-MAR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.280169E+09 | 3592.38 | 03-APR-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 106873.87 | 285.75 | 02-MAY-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.422485E+09 | 4590.20 | 31-OCT-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.161985E+09 | 3830.73 | 29-NOV-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.461755E+09 | 6744.17 | 21-DEC-09:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.232684E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.461755E+09 | 6744.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.107142E+09 | 4065.25 | 06-FEB-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6134195.82 | 1547.34 | 19-MAR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 30719521.42 | 3069.04 | 31-OCT-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 88933025.58 | 6257.09 | 21-DEC-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.232929E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.107142E+09 | 6257.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.779311E+09 | 6361.31 | 05-JAN-09:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.221582E+10 | 7239.48 | 05-FEB-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.923969E+09 | 4508.25 | 21-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.598135E+09 | 4917.82 | 03-APR-08:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.815075E+09 | 7002.42 | 31-OCT-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.927619E+09 | 6106.89 | 01-NOV-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.309269E+10 | 9129.85 | 21-DEC-09:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.935262E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.309269E+10 | 9129.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.149821E+10 | 4477.02 | 05-JAN-09:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.197357E+10 | 4186.88 | 12-FEB-05:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.123955E+10 | 3290.18 | 05-MAR-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.811595E+09 | 2947.60 | 03-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 22773319.69 | 656.72 | 02-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.876576E+09 | 3551.48 | 31-OCT-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.114734E+10 | 3908.26 | 30-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.305709E+10 | 5732.49 | 21-DEC-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.106267E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.305709E+10 | 5732.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.191440E+10 | 6707.35 | 04-JAN-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.229648E+10 | 6708.11 | 01-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.176204E+10 | 6709.16 | 18-MAR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.144286E+10 | 6707.90 | 03-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.124776E+09 | 4561.18 | 02-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2092225.03 | 2153.36 | 01-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1905399.67 | 2021.95 | 31-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2911535.58 | 2251.54 | 24-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 46094178.32 | 4873.04 | 22-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.123134E+10 | 6708.76 | 24-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.164807E+10 | 6708.42 | 01-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.336372E+10 | 6706.46 | 20-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.138367E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1905399.67 | 2021.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.336372E+10 | 6709.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.320845E+10 | 6682.65 | 04-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.325246E+10 | 6682.64 | 01-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.216223E+10 | 6683.72 | 18-MAR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.157362E+10 | 6682.43 | 03-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.133509E+09 | 4750.05 | 02-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 431174.85 | 1456.96 | 03-JUN-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 602592.22 | 1560.68 | 03-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1632483.64 | 2261.03 | 24-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 54854860.91 | 5605.58 | 22-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.147394E+10 | 6683.30 | 24-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.253694E+10 | 6683.09 | 28-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.472792E+10 | 6682.34 | 07-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.191266E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 431174.85 | 1456.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.472792E+10 | 6683.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.120160E+11 | 37817.00 | 05-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.128793E+11 | 37603.94 | 06-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.561203E+10 | 37089.19 | 19-MAR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.275217E+10 | 36749.07 | 02-APR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 62891764.74 | 29007.56 | 03-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 22936.67 | 267.59 | 23-JUN-08:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 39611.28 | 346.88 | 14-JUL-08:58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1252456.00 | 7850.01 | 17-AUG-08:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 30792096.25 | 20007.02 | 22-SEP-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.340355E+10 | 37696.10 | 31-OCT-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.821008E+10 | 37563.23 | 29-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.181152E+11 | 37818.52 | 24-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.630833E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 22936.67 | 267.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.181152E+11 | 37818.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.203719E+10 | 6542.75 | 04-JAN-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.243930E+10 | 6543.58 | 01-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.175367E+10 | 6544.71 | 18-MAR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.140713E+10 | 6543.36 | 03-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.117900E+09 | 3104.91 | 01-MAY-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 104793.28 | 1047.93 | 17-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 191343.58 | 1913.44 | 28-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 226145.83 | 1788.52 | 27-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 41073931.77 | 2043.14 | 22-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.125790E+10 | 6544.29 | 24-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.177257E+10 | 6543.93 | 01-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.345187E+10 | 6541.82 | 20-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.142791E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 104793.28 | 1047.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.345187E+10 | 6544.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.333991E+10 | 6518.43 | 31-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.336617E+10 | 6517.72 | 04-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.210515E+10 | 6518.84 | 18-MAR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.155961E+10 | 6517.46 | 03-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.126511E+09 | 3193.81 | 01-MAY-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11679.49 | 136.26 | 17-JUN-08:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 60478.28 | 464.26 | 28-JUL-21:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 60091.95 | 326.54 | 28-AUG-21:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 50978517.63 | 2782.96 | 22-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.151598E+10 | 6518.41 | 24-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.270933E+10 | 6518.04 | 01-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.477776E+10 | 6517.77 | 31-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.195515E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 11679.49 | 136.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.477776E+10 | 6518.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.816055E+09 | 2018.85 | 30-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.891636E+09 | 2018.37 | 01-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.704730E+09 | 2018.90 | 21-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.589858E+09 | 2018.51 | 23-APR-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 80865336.81 | 1924.08 | 02-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 912199.91 | 561.19 | 09-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 765546.66 | 487.51 | 21-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1305631.19 | 605.85 | 13-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 31123113.72 | 1986.80 | 22-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.533051E+09 | 2018.61 | 24-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.695811E+09 | 2018.80 | 10-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.126833E+10 | 2018.15 | 09-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.561445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 765546.66 | 487.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.126833E+10 | 2018.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.125947E+10 | 2007.94 | 30-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121077E+10 | 2007.54 | 04-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.842988E+09 | 2008.00 | 21-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.631547E+09 | 2007.61 | 23-APR-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 77064470.47 | 1963.93 | 02-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 124679.74 | 454.40 | 16-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 181546.85 | 488.28 | 03-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 598774.75 | 493.01 | 15-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 34969358.58 | 1980.18 | 22-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.638867E+09 | 2007.77 | 25-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.101525E+10 | 2007.90 | 10-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.170502E+10 | 2007.64 | 31-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.741684E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 124679.74 | 454.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.170502E+10 | 2008.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.157086E+10 | 9510.71 | 04-JAN-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.241357E+10 | 9510.90 | 05-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.218141E+10 | 9513.38 | 18-MAR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.193829E+10 | 9511.41 | 03-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.205478E+09 | 4839.98 | 02-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4045788.27 | 2395.10 | 21-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 2203842.98 | 1963.30 | 03-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1326998.06 | 2322.70 | 02-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 59673563.28 | 5918.55 | 22-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.155935E+10 | 9512.51 | 29-OCT-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.153320E+10 | 9512.29 | 01-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.315365E+10 | 9508.92 | 20-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.146231E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1326998.06 | 1963.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.315365E+10 | 9513.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.192282E+09 | 0.192282E+09 | 11112.29 | 20-JAN-14:00 | 11112.29 | 0.00 |
February | 0.00 | 0.00 | 0.123483E+09 | 0.123483E+09 | 9344.67 | 18-FEB-14:00 | 9344.67 | 0.00 |
March | 0.00 | 0.00 | 0.894175E+09 | 0.894175E+09 | 13447.39 | 13-MAR-15:02 | 13447.39 | 0.00 |
April | 0.00 | 0.00 | 0.105845E+10 | 0.105845E+10 | 12344.03 | 20-APR-13:00 | 12344.03 | 0.00 |
May | 0.00 | 0.00 | 0.512689E+10 | 0.512689E+10 | 15634.50 | 17-MAY-13:00 | 15634.50 | 0.06 |
June | 0.00 | 0.00 | 0.173293E+11 | 0.168247E+11 | 21371.02 | 18-JUN-12:05 | 15865.72 | 0.37 |
July | 0.00 | 0.00 | 0.210710E+11 | 0.191669E+11 | 25905.13 | 30-JUL-15:37 | 13390.78 | 0.43 |
August | 0.00 | 0.00 | 0.182586E+11 | 0.171944E+11 | 21036.31 | 05-AUG-15:02 | 9826.56 | 0.49 |
September | 0.00 | 0.00 | 0.117438E+11 | 0.117438E+11 | 16830.58 | 10-SEP-13:00 | 16830.58 | 0.14 |
October | 0.00 | 0.00 | 0.173362E+10 | 0.173362E+10 | 14656.79 | 11-OCT-15:02 | 14656.79 | 0.00 |
November | 0.00 | 0.00 | 0.497130E+09 | 0.497130E+09 | 12330.11 | 06-NOV-13:50 | 12330.11 | 0.00 |
December | 0.00 | 0.00 | 0.275091E+09 | 0.275091E+09 | 11661.97 | 01-DEC-14:00 | 11661.97 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.783038E+11 | 0.748311E+11 | 0.13 | |||
Minimum of Months | 0.00 | 0.00 | 0.123483E+09 | 0.123483E+09 | 9344.67 | 9344.67 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.210710E+11 | 0.191669E+11 | 25905.13 | 16830.58 | 0.49 |
Report: CoilReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.527522E+10 | 0.527522E+10 | 123745.19 | 20-JAN-13:00 | 123745.19 | 0.00 |
February | 0.00 | 0.00 | 0.295321E+10 | 0.295321E+10 | 112634.92 | 18-FEB-13:00 | 112634.92 | 0.00 |
March | 0.00 | 0.00 | 0.182652E+11 | 0.182652E+11 | 153222.08 | 14-MAR-13:00 | 153222.08 | 0.00 |
April | 0.00 | 0.00 | 0.191272E+11 | 0.191272E+11 | 108415.72 | 19-APR-10:50 | 108415.72 | 0.01 |
May | 0.00 | 0.00 | 0.890894E+11 | 0.890894E+11 | 202844.21 | 31-MAY-18:07 | 202844.21 | 0.08 |
June | 0.00 | 0.00 | 0.292388E+12 | 0.287438E+12 | 278121.23 | 26-JUN-18:20 | 278121.23 | 0.42 |
July | 0.00 | 0.00 | 0.336345E+12 | 0.316784E+12 | 284410.40 | 30-JUL-10:40 | 157327.46 | 0.49 |
August | 0.00 | 0.00 | 0.300331E+12 | 0.292772E+12 | 267745.35 | 16-AUG-18:05 | 267745.35 | 0.55 |
September | 0.00 | 0.00 | 0.206989E+12 | 0.206989E+12 | 241681.96 | 12-SEP-18:30 | 241681.96 | 0.15 |
October | 0.00 | 0.00 | 0.338864E+11 | 0.338864E+11 | 179083.54 | 11-OCT-15:10 | 179083.54 | 0.00 |
November | 0.00 | 0.00 | 0.107359E+11 | 0.107359E+11 | 136540.05 | 06-NOV-13:00 | 136540.05 | 0.00 |
December | 0.00 | 0.00 | 0.717379E+10 | 0.717379E+10 | 116626.29 | 02-DEC-13:00 | 116626.29 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.132256E+13 | 0.129049E+13 | 0.14 | |||
Minimum of Months | 0.00 | 0.00 | 0.295321E+10 | 0.295321E+10 | 108415.72 | 108415.72 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.336345E+12 | 0.316784E+12 | 284410.40 | 278121.23 | 0.55 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.144698E+10 | 0.123723E+10 | 11596.59 | 26-JAN-16:01 | 11596.59 | 0.14 |
February | 0.00 | 0.00 | 0.152996E+10 | 0.135759E+10 | 11596.53 | 11-FEB-16:02 | 11596.53 | 0.13 |
March | 0.00 | 0.00 | 0.283996E+10 | 0.279293E+10 | 11596.86 | 11-MAR-09:02 | 11596.86 | 0.04 |
April | 0.00 | 0.00 | 0.195075E+10 | 0.174762E+10 | 11595.89 | 20-APR-15:01 | 11595.89 | 0.14 |
May | 0.00 | 0.00 | 0.463948E+10 | 0.366884E+10 | 12001.89 | 22-MAY-08:62 | 10498.55 | 0.53 |
June | 0.00 | 0.00 | 0.983319E+10 | 0.795145E+10 | 13043.76 | 18-JUN-08:62 | 10549.11 | 0.83 |
July | 0.00 | 0.00 | 0.960901E+10 | 0.732713E+10 | 13053.69 | 27-JUL-18:02 | 10543.26 | 0.90 |
August | 0.00 | 0.00 | 0.970440E+10 | 0.756203E+10 | 13085.46 | 05-AUG-08:62 | 10522.28 | 0.81 |
September | 0.00 | 0.00 | 0.782648E+10 | 0.676298E+10 | 11597.03 | 30-SEP-15:02 | 11597.03 | 0.54 |
October | 0.00 | 0.00 | 0.389606E+10 | 0.353908E+10 | 11597.65 | 21-OCT-15:02 | 11597.65 | 0.22 |
November | 0.00 | 0.00 | 0.193375E+10 | 0.158968E+10 | 11597.29 | 24-NOV-16:02 | 11597.29 | 0.22 |
December | 0.00 | 0.00 | 0.902789E+09 | 0.873902E+09 | 11596.28 | 29-DEC-16:01 | 11596.28 | 0.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.561128E+11 | 0.464105E+11 | 0.38 | |||
Minimum of Months | 0.00 | 0.00 | 0.902789E+09 | 0.873902E+09 | 11595.89 | 10498.55 | 0.02 | |
Maximum of Months | 0.00 | 0.00 | 0.983319E+10 | 0.795145E+10 | 13085.46 | 11597.65 | 0.90 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.243005E+09 | 0.220946E+09 | 11330.27 | 26-JAN-16:01 | 11330.27 | 0.02 |
February | 0.00 | 0.00 | 0.368664E+09 | 0.339265E+09 | 11329.29 | 15-FEB-16:02 | 11329.29 | 0.03 |
March | 0.00 | 0.00 | 0.114976E+10 | 0.113346E+10 | 12789.66 | 15-MAR-18:31 | 12789.66 | 0.02 |
April | 0.00 | 0.00 | 0.976966E+09 | 0.831245E+09 | 14349.27 | 08-APR-17:42 | 14349.27 | 0.10 |
May | 0.00 | 0.00 | 0.321651E+10 | 0.236863E+10 | 12825.99 | 27-MAY-16:11 | 12825.99 | 0.45 |
June | 0.00 | 0.00 | 0.835991E+10 | 0.691083E+10 | 14417.29 | 22-JUN-21:51 | 11138.83 | 0.67 |
July | 0.00 | 0.00 | 0.784155E+10 | 0.611751E+10 | 14339.25 | 31-JUL-21:51 | 10281.20 | 0.69 |
August | 0.00 | 0.00 | 0.730169E+10 | 0.565164E+10 | 13850.72 | 05-AUG-21:51 | 11913.01 | 0.63 |
September | 0.00 | 0.00 | 0.486065E+10 | 0.402541E+10 | 12277.07 | 15-SEP-19:51 | 12277.07 | 0.42 |
October | 0.00 | 0.00 | 0.153039E+10 | 0.135672E+10 | 12501.60 | 14-OCT-16:11 | 12501.60 | 0.13 |
November | 0.00 | 0.00 | 0.401145E+09 | 0.343888E+09 | 11330.69 | 16-NOV-16:02 | 11330.69 | 0.05 |
December | 0.00 | 0.00 | 0.111940E+09 | 0.110919E+09 | 11329.93 | 29-DEC-16:01 | 11329.93 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.363622E+11 | 0.294105E+11 | 0.27 | |||
Minimum of Months | 0.00 | 0.00 | 0.111940E+09 | 0.110919E+09 | 11329.29 | 10281.20 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.835991E+10 | 0.691083E+10 | 14417.29 | 14349.27 | 0.69 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.345404E+11 | 0.345404E+11 | 70513.89 | 20-JAN-12:40 | 70513.89 | 0.00 |
February | 0.00 | 0.00 | 0.245262E+11 | 0.245262E+11 | 66077.74 | 18-FEB-13:00 | 66077.74 | 0.00 |
March | 0.00 | 0.00 | 0.246526E+11 | 0.246526E+11 | 59562.53 | 14-MAR-12:40 | 59562.53 | 0.00 |
April | 0.00 | 0.00 | 0.954113E+10 | 0.922836E+10 | 36527.05 | 08-APR-13:00 | 36527.05 | 0.03 |
May | 0.00 | 0.00 | 0.224943E+11 | 0.168771E+11 | 28756.62 | 05-MAY-13:00 | 28756.62 | 0.37 |
June | 0.00 | 0.00 | 0.418490E+11 | 0.276164E+11 | 33766.55 | 14-JUN-13:30 | 33766.55 | 0.87 |
July | 0.00 | 0.00 | 0.457377E+11 | 0.306108E+11 | 37722.40 | 23-JUL-12:40 | 33463.66 | 0.87 |
August | 0.00 | 0.00 | 0.521340E+11 | 0.371679E+11 | 48184.61 | 31-AUG-12:40 | 41480.83 | 0.89 |
September | 0.00 | 0.00 | 0.526855E+11 | 0.456288E+11 | 61537.33 | 28-SEP-13:00 | 61537.33 | 0.49 |
October | 0.00 | 0.00 | 0.389010E+11 | 0.382515E+11 | 64142.50 | 10-OCT-12:30 | 64142.50 | 0.06 |
November | 0.00 | 0.00 | 0.325280E+11 | 0.325280E+11 | 69984.40 | 07-NOV-12:10 | 69984.40 | 0.00 |
December | 0.00 | 0.00 | 0.213818E+11 | 0.213818E+11 | 62651.42 | 17-DEC-12:30 | 62651.42 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.400972E+12 | 0.343010E+12 | 0.30 | |||
Minimum of Months | 0.00 | 0.00 | 0.954113E+10 | 0.922836E+10 | 28756.62 | 28756.62 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.526855E+11 | 0.456288E+11 | 70513.89 | 70513.89 | 0.89 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.182467E+10 | 0.152873E+10 | 58901.55 | 21-JAN-09:02 | 58901.55 | 0.05 |
February | 0.00 | 0.00 | 0.171594E+10 | 0.145369E+10 | 59058.33 | 19-FEB-09:02 | 59058.33 | 0.04 |
March | 0.00 | 0.00 | 0.715555E+10 | 0.678060E+10 | 62361.41 | 14-MAR-20:51 | 62361.41 | 0.05 |
April | 0.00 | 0.00 | 0.101214E+11 | 0.825466E+10 | 63167.59 | 20-APR-20:31 | 63167.59 | 0.22 |
May | 0.00 | 0.00 | 0.296050E+11 | 0.254838E+11 | 64335.72 | 07-MAY-19:31 | 64335.72 | 0.36 |
June | 0.00 | 0.00 | 0.522944E+11 | 0.459800E+11 | 75274.61 | 20-JUN-21:51 | 57538.52 | 0.55 |
July | 0.00 | 0.00 | 0.538972E+11 | 0.463559E+11 | 76883.12 | 31-JUL-21:51 | 56667.57 | 0.61 |
August | 0.00 | 0.00 | 0.467124E+11 | 0.388396E+11 | 73460.78 | 29-AUG-21:51 | 56370.96 | 0.53 |
September | 0.00 | 0.00 | 0.325014E+11 | 0.293916E+11 | 64208.35 | 09-SEP-21:51 | 64208.35 | 0.33 |
October | 0.00 | 0.00 | 0.108115E+11 | 0.942864E+10 | 61946.17 | 01-OCT-18:01 | 61946.17 | 0.16 |
November | 0.00 | 0.00 | 0.338537E+10 | 0.268795E+10 | 59513.18 | 09-NOV-19:02 | 59513.18 | 0.11 |
December | 0.00 | 0.00 | 0.130705E+10 | 0.130376E+10 | 58039.40 | 03-DEC-09:02 | 58039.40 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.251332E+12 | 0.217489E+12 | 0.25 | |||
Minimum of Months | 0.00 | 0.00 | 0.130705E+10 | 0.130376E+10 | 58039.40 | 56370.96 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.538972E+11 | 0.463559E+11 | 76883.12 | 64335.72 | 0.61 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.141149E+10 | 0.124810E+10 | 10228.32 | 20-JAN-09:02 | 10228.32 | 0.14 |
February | 0.00 | 0.00 | 0.169043E+10 | 0.151465E+10 | 10227.54 | 14-FEB-09:01 | 10227.54 | 0.15 |
March | 0.00 | 0.00 | 0.303469E+10 | 0.294009E+10 | 10227.68 | 03-MAR-09:02 | 10227.68 | 0.07 |
April | 0.00 | 0.00 | 0.229133E+10 | 0.202915E+10 | 10227.77 | 20-APR-15:01 | 10227.77 | 0.20 |
May | 0.00 | 0.00 | 0.506218E+10 | 0.407105E+10 | 10419.71 | 22-MAY-15:02 | 10008.56 | 0.58 |
June | 0.00 | 0.00 | 0.104562E+11 | 0.871874E+10 | 11237.35 | 17-JUN-08:62 | 9476.95 | 0.87 |
July | 0.00 | 0.00 | 0.107362E+11 | 0.870390E+10 | 11545.37 | 27-JUL-18:02 | 9276.20 | 0.92 |
August | 0.00 | 0.00 | 0.107633E+11 | 0.881384E+10 | 10594.57 | 21-AUG-18:02 | 9896.85 | 0.84 |
September | 0.00 | 0.00 | 0.824907E+10 | 0.733039E+10 | 10227.65 | 30-SEP-15:02 | 10227.65 | 0.57 |
October | 0.00 | 0.00 | 0.374673E+10 | 0.340716E+10 | 10227.84 | 21-OCT-08:62 | 10227.84 | 0.25 |
November | 0.00 | 0.00 | 0.186883E+10 | 0.156530E+10 | 10226.43 | 07-NOV-09:02 | 10226.43 | 0.23 |
December | 0.00 | 0.00 | 0.933840E+09 | 0.905711E+09 | 10228.12 | 05-DEC-09:02 | 10228.12 | 0.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.602443E+11 | 0.512481E+11 | 0.40 | |||
Minimum of Months | 0.00 | 0.00 | 0.933840E+09 | 0.905711E+09 | 10226.43 | 9276.20 | 0.03 | |
Maximum of Months | 0.00 | 0.00 | 0.107633E+11 | 0.881384E+10 | 11545.37 | 10228.32 | 0.92 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.261454E+09 | 0.214576E+09 | 10005.96 | 24-JAN-09:02 | 10005.96 | 0.03 |
February | 0.00 | 0.00 | 0.501540E+09 | 0.434481E+09 | 10007.19 | 27-FEB-09:02 | 10007.19 | 0.05 |
March | 0.00 | 0.00 | 0.140263E+10 | 0.134537E+10 | 10226.99 | 14-MAR-20:51 | 10226.99 | 0.04 |
April | 0.00 | 0.00 | 0.141354E+10 | 0.120727E+10 | 10253.21 | 20-APR-20:31 | 10253.21 | 0.16 |
May | 0.00 | 0.00 | 0.376833E+10 | 0.292198E+10 | 11550.36 | 04-MAY-08:51 | 11550.36 | 0.49 |
June | 0.00 | 0.00 | 0.864264E+10 | 0.728142E+10 | 13798.72 | 21-JUN-08:32 | 11638.17 | 0.70 |
July | 0.00 | 0.00 | 0.867945E+10 | 0.718449E+10 | 13784.68 | 01-JUL-07:32 | 13784.68 | 0.71 |
August | 0.00 | 0.00 | 0.806730E+10 | 0.648062E+10 | 14080.95 | 04-AUG-08:32 | 11813.02 | 0.67 |
September | 0.00 | 0.00 | 0.531302E+10 | 0.450128E+10 | 11603.79 | 18-SEP-08:51 | 11603.79 | 0.46 |
October | 0.00 | 0.00 | 0.153693E+10 | 0.134379E+10 | 11430.55 | 11-OCT-08:51 | 11430.55 | 0.16 |
November | 0.00 | 0.00 | 0.453192E+09 | 0.365717E+09 | 10006.71 | 07-NOV-09:02 | 10006.71 | 0.07 |
December | 0.00 | 0.00 | 0.149660E+09 | 0.135136E+09 | 10005.67 | 03-DEC-09:02 | 10005.67 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.401897E+11 | 0.334161E+11 | 0.30 | |||
Minimum of Months | 0.00 | 0.00 | 0.149660E+09 | 0.135136E+09 | 10005.67 | 10005.67 | 0.01 | |
Maximum of Months | 0.00 | 0.00 | 0.867945E+10 | 0.728142E+10 | 14080.95 | 13784.68 | 0.71 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.324472E+09 | 0.283974E+09 | 3078.54 | 26-JAN-16:01 | 3078.54 | 0.09 |
February | 0.00 | 0.00 | 0.357022E+09 | 0.321950E+09 | 3078.48 | 11-FEB-16:02 | 3078.48 | 0.10 |
March | 0.00 | 0.00 | 0.687480E+09 | 0.676948E+09 | 3078.34 | 30-MAR-18:01 | 3078.34 | 0.03 |
April | 0.00 | 0.00 | 0.494616E+09 | 0.446387E+09 | 3078.39 | 20-APR-15:01 | 3078.39 | 0.12 |
May | 0.00 | 0.00 | 0.111928E+10 | 0.906796E+09 | 3402.02 | 22-MAY-08:62 | 2536.00 | 0.46 |
June | 0.00 | 0.00 | 0.249057E+10 | 0.201914E+10 | 3557.15 | 18-JUN-08:62 | 2737.74 | 0.83 |
July | 0.00 | 0.00 | 0.238692E+10 | 0.181813E+10 | 3634.15 | 30-JUL-08:62 | 2686.51 | 0.89 |
August | 0.00 | 0.00 | 0.241388E+10 | 0.188709E+10 | 3603.88 | 05-AUG-08:62 | 2706.70 | 0.80 |
September | 0.00 | 0.00 | 0.185810E+10 | 0.159675E+10 | 3078.63 | 30-SEP-15:02 | 3078.63 | 0.53 |
October | 0.00 | 0.00 | 0.892751E+09 | 0.819245E+09 | 3078.59 | 13-OCT-15:01 | 3078.59 | 0.17 |
November | 0.00 | 0.00 | 0.444616E+09 | 0.376299E+09 | 3078.65 | 25-NOV-16:01 | 3078.65 | 0.16 |
December | 0.00 | 0.00 | 0.203662E+09 | 0.197785E+09 | 3078.40 | 29-DEC-16:01 | 3078.40 | 0.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.136734E+11 | 0.113505E+11 | 0.35 | |||
Minimum of Months | 0.00 | 0.00 | 0.203662E+09 | 0.197785E+09 | 3078.34 | 2536.00 | 0.02 | |
Maximum of Months | 0.00 | 0.00 | 0.249057E+10 | 0.201914E+10 | 3634.15 | 3078.65 | 0.89 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 47773945.46 | 43357941.68 | 3001.22 | 21-JAN-16:02 | 3001.22 | 0.01 |
February | 0.00 | 0.00 | 79419403.88 | 72973140.09 | 3001.84 | 15-FEB-16:02 | 3001.84 | 0.02 |
March | 0.00 | 0.00 | 0.264847E+09 | 0.261135E+09 | 3459.81 | 15-MAR-18:31 | 3459.81 | 0.01 |
April | 0.00 | 0.00 | 0.242401E+09 | 0.209958E+09 | 3840.77 | 08-APR-17:42 | 3840.77 | 0.09 |
May | 0.00 | 0.00 | 0.765504E+09 | 0.576996E+09 | 3450.95 | 27-MAY-16:11 | 3450.95 | 0.41 |
June | 0.00 | 0.00 | 0.217451E+10 | 0.179549E+10 | 3921.18 | 22-JUN-21:51 | 2974.86 | 0.67 |
July | 0.00 | 0.00 | 0.200444E+10 | 0.156166E+10 | 3885.01 | 31-JUL-21:51 | 2717.83 | 0.69 |
August | 0.00 | 0.00 | 0.186248E+10 | 0.144328E+10 | 3774.56 | 05-AUG-21:51 | 3234.68 | 0.63 |
September | 0.00 | 0.00 | 0.115014E+10 | 0.942971E+09 | 3321.24 | 15-SEP-19:51 | 3321.24 | 0.42 |
October | 0.00 | 0.00 | 0.316246E+09 | 0.286084E+09 | 3412.93 | 08-OCT-18:11 | 3412.93 | 0.08 |
November | 0.00 | 0.00 | 84525646.34 | 75192812.88 | 3002.16 | 16-NOV-16:02 | 3002.16 | 0.03 |
December | 0.00 | 0.00 | 23013948.59 | 22723102.67 | 3001.23 | 02-DEC-16:01 | 3001.23 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.901529E+10 | 0.729183E+10 | 0.26 | |||
Minimum of Months | 0.00 | 0.00 | 23013948.59 | 22723102.67 | 3001.22 | 2717.83 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.217451E+10 | 0.179549E+10 | 3921.18 | 3840.77 | 0.69 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.763478E+10 | 0.717995E+10 | 13850.72 | 20-JAN-13:10 | 13850.72 | 0.31 |
February | 0.00 | 0.00 | 0.620988E+10 | 0.583577E+10 | 14682.57 | 18-FEB-13:33 | 14682.57 | 0.26 |
March | 0.00 | 0.00 | 0.633898E+10 | 0.616882E+10 | 13641.96 | 05-MAR-16:02 | 13641.96 | 0.10 |
April | 0.00 | 0.00 | 0.332150E+10 | 0.296901E+10 | 13640.81 | 06-APR-15:01 | 13640.81 | 0.20 |
May | 0.00 | 0.00 | 0.567413E+10 | 0.449465E+10 | 14506.49 | 22-MAY-15:02 | 12940.81 | 0.54 |
June | 0.00 | 0.00 | 0.108673E+11 | 0.851895E+10 | 15512.89 | 18-JUN-08:62 | 12287.20 | 0.83 |
July | 0.00 | 0.00 | 0.117701E+11 | 0.897273E+10 | 16097.67 | 30-JUL-18:02 | 11900.95 | 0.88 |
August | 0.00 | 0.00 | 0.130418E+11 | 0.103645E+11 | 15290.29 | 04-AUG-08:62 | 12434.43 | 0.83 |
September | 0.00 | 0.00 | 0.121654E+11 | 0.109438E+11 | 13640.59 | 10-SEP-08:62 | 13640.59 | 0.58 |
October | 0.00 | 0.00 | 0.879661E+10 | 0.832951E+10 | 13718.90 | 08-OCT-15:18 | 13718.90 | 0.32 |
November | 0.00 | 0.00 | 0.787811E+10 | 0.720891E+10 | 13798.52 | 05-NOV-13:40 | 13798.52 | 0.43 |
December | 0.00 | 0.00 | 0.559171E+10 | 0.548810E+10 | 13778.44 | 29-DEC-13:55 | 13778.44 | 0.08 |
Annual Sum or Average | 0.00 | 0.00 | 0.992903E+11 | 0.864747E+11 | 0.45 | |||
Minimum of Months | 0.00 | 0.00 | 0.332150E+10 | 0.296901E+10 | 13640.59 | 11900.95 | 0.08 | |
Maximum of Months | 0.00 | 0.00 | 0.130418E+11 | 0.109438E+11 | 16097.67 | 14682.57 | 0.88 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 39593.28 | 209447.12 | 05-JAN-19:05 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 45300.08 | 196265.22 | 07-FEB-16:03 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 35572.28 | 185402.32 | 21-MAR-15:02 |
April | 0.00 | 0.00 | 01-APR-00:10 | 33864.41 | 136872.06 | 10-APR-08:05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 27259.92 | 131917.38 | 02-MAY-18:04 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 1959.22 | 110306.14 | 09-JUN-03:40 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1702.32 | 76251.29 | 02-JUL-05:00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 1734.27 | 57000.48 | 12-AUG-23:00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 10879.95 | 133730.84 | 21-SEP-14:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 30040.07 | 158252.24 | 30-OCT-08:62 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 31809.96 | 172065.05 | 24-NOV-16:03 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57533.42 | 238212.65 | 21-DEC-09:05 |
Annual Sum or Average | 0.00 | 26357.02 | ||||
Minimum of Months | 0.00 | 0.00 | 1702.32 | 57000.48 | ||
Maximum of Months | 0.00 | 0.00 | 57533.42 | 238212.65 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 21272.74 | 225662.05 | 20-JAN-13:15 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 17754.05 | 209418.44 | 18-FEB-13:37 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 26289.27 | 335252.26 | 13-MAR-15:03 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 20937.69 | 265968.71 | 07-APR-15:03 | 0.00 | 0.00 | 01-APR-00:10 |
May | 65793.30 | 354920.70 | 31-MAY-18:03 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 178512.21 | 437228.03 | 27-JUN-18:52 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 192800.31 | 430418.79 | 17-JUL-18:42 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 178053.15 | 422304.12 | 25-AUG-18:15 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 135473.21 | 408343.42 | 13-SEP-15:04 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 41205.63 | 372559.50 | 11-OCT-15:03 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 24684.18 | 281283.13 | 05-NOV-15:02 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 15262.90 | 201701.22 | 02-DEC-13:15 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 76839.25 | 0.00 | ||||
Minimum of Months | 15262.90 | 201701.22 | 0.00 | 0.00 | ||
Maximum of Months | 192800.31 | 437228.03 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 27974.26 | 59065.78 | 31-JAN-07:40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 28321.34 | 59222.68 | 13-FEB-08:00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 27930.19 | 58991.42 | 01-MAR-07:50 |
April | 0.00 | 0.00 | 01-APR-00:10 | 26830.37 | 57149.89 | 03-APR-06:20 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 25360.12 | 54536.01 | 01-MAY-06:30 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 23903.64 | 51281.59 | 01-JUN-06:57 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22820.66 | 48438.34 | 03-JUL-06:15 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 22471.55 | 47091.05 | 31-AUG-06:45 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22886.16 | 48636.47 | 29-SEP-06:45 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 23978.68 | 51558.90 | 31-OCT-07:00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 25457.24 | 54711.25 | 30-NOV-07:40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 26914.09 | 57361.34 | 29-DEC-07:15 |
Annual Sum or Average | 0.00 | 25387.00 | ||||
Minimum of Months | 0.00 | 0.00 | 22471.55 | 47091.05 | ||
Maximum of Months | 0.00 | 0.00 | 28321.34 | 59222.68 |
Report: FanReportMonthly
For: FLR_3_DOAS FAN
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.271000E+10 | 0.85 | 1299.30 | 07-JAN-19:03 | 1.08 |
February | 0.244774E+10 | 0.85 | 1299.30 | 02-FEB-09:20 | 1.08 |
March | 0.271000E+10 | 0.85 | 1299.30 | 27-MAR-08:62 | 1.08 |
April | 0.262258E+10 | 0.85 | 1299.30 | 10-APR-08:03 | 1.08 |
May | 0.271000E+10 | 0.85 | 1299.30 | 09-MAY-20:38 | 1.08 |
June | 0.262258E+10 | 0.85 | 1299.30 | 13-JUN-16:20 | 1.08 |
July | 0.271000E+10 | 0.85 | 1299.30 | 02-JUL-15:08 | 1.08 |
August | 0.271000E+10 | 0.85 | 1299.30 | 05-AUG-22:50 | 1.07 |
September | 0.262258E+10 | 0.85 | 1299.30 | 04-SEP-09:08 | 1.07 |
October | 0.271000E+10 | 0.85 | 1299.30 | 01-OCT-01:00 | 1.08 |
November | 0.262258E+10 | 0.85 | 1299.30 | 01-NOV-09:20 | 1.08 |
December | 0.271000E+10 | 0.86 | 1299.30 | 02-DEC-17:23 | 1.08 |
Annual Sum or Average | 0.319080E+11 | 0.85 | |||
Minimum of Months | 0.244774E+10 | 0.85 | 1299.30 | 1.07 | |
Maximum of Months | 0.271000E+10 | 0.86 | 1299.30 | 1.08 |
Report: FanReportMonthly
For: VAV WITH REHEAT FAN
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.339364E+11 | 0.89 | 28614.10 | 20-JAN-22:10 | 1.42 |
February | 0.300766E+11 | 0.88 | 26241.03 | 17-FEB-22:10 | 1.35 |
March | 0.344417E+11 | 0.90 | 30474.15 | 15-MAR-21:10 | 1.48 |
April | 0.328592E+11 | 0.89 | 28799.23 | 20-APR-21:10 | 1.42 |
May | 0.371047E+11 | 0.93 | 31298.07 | 17-MAY-21:10 | 1.50 |
June | 0.415571E+11 | 1.00 | 46843.08 | 27-JUN-19:05 | 1.92 |
July | 0.431439E+11 | 1.00 | 45788.50 | 17-JUL-18:43 | 1.89 |
August | 0.442910E+11 | 1.02 | 44187.95 | 25-AUG-18:10 | 1.85 |
September | 0.425323E+11 | 1.02 | 42543.94 | 12-SEP-21:10 | 1.81 |
October | 0.384708E+11 | 0.95 | 36638.17 | 10-OCT-21:10 | 1.66 |
November | 0.351799E+11 | 0.92 | 31458.38 | 07-NOV-22:10 | 1.51 |
December | 0.340459E+11 | 0.89 | 28445.76 | 04-DEC-22:10 | 1.42 |
Annual Sum or Average | 0.447639E+12 | 0.94 | |||
Minimum of Months | 0.300766E+11 | 0.88 | 26241.03 | 1.35 | |
Maximum of Months | 0.442910E+11 | 1.02 | 46843.08 | 1.92 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205205E+09 | 0.33 | 76.61 | 01-JAN-00:10 | 0.33 |
February | 0.185347E+09 | 0.33 | 76.61 | 01-FEB-00:10 | 0.33 |
March | 0.205205E+09 | 0.33 | 76.61 | 01-MAR-00:10 | 0.33 |
April | 0.198586E+09 | 0.33 | 76.61 | 01-APR-00:10 | 0.33 |
May | 0.205205E+09 | 0.33 | 76.61 | 01-MAY-00:05 | 0.33 |
June | 0.198586E+09 | 0.33 | 76.61 | 01-JUN-00:05 | 0.33 |
July | 0.205205E+09 | 0.33 | 76.61 | 01-JUL-00:10 | 0.33 |
August | 0.205205E+09 | 0.33 | 76.61 | 01-AUG-00:05 | 0.32 |
September | 0.198586E+09 | 0.33 | 76.61 | 01-SEP-00:10 | 0.33 |
October | 0.205205E+09 | 0.33 | 76.61 | 01-OCT-00:10 | 0.33 |
November | 0.198586E+09 | 0.33 | 76.61 | 01-NOV-00:05 | 0.33 |
December | 0.205205E+09 | 0.33 | 76.61 | 01-DEC-00:10 | 0.33 |
Annual Sum or Average | 0.241613E+10 | 0.33 | |||
Minimum of Months | 0.185347E+09 | 0.33 | 76.61 | 0.32 | |
Maximum of Months | 0.205205E+09 | 0.33 | 76.61 | 0.33 |
Report: FanReportMonthly
For: LOBBY_FLR_1 EXHAUST FAN
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | -0.0 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | -0.0 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:10 | -0.0 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | -0.0 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 EXHAUST FAN
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 EXHAUST FAN
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116283E+10 | 0.23 | 612.92 | 01-JAN-07:10 | 0.33 |
February | 0.105030E+10 | 0.23 | 612.92 | 01-FEB-07:05 | 0.33 |
March | 0.116283E+10 | 0.23 | 612.92 | 01-MAR-07:05 | 0.33 |
April | 0.112532E+10 | 0.23 | 612.92 | 01-APR-06:05 | 0.33 |
May | 0.116283E+10 | 0.23 | 612.92 | 01-MAY-06:05 | 0.33 |
June | 0.112532E+10 | 0.23 | 612.92 | 01-JUN-06:05 | 0.32 |
July | 0.116283E+10 | 0.23 | 612.92 | 01-JUL-06:03 | 0.33 |
August | 0.116283E+10 | 0.23 | 612.92 | 01-AUG-06:05 | 0.33 |
September | 0.112532E+10 | 0.23 | 612.92 | 01-SEP-06:05 | 0.32 |
October | 0.116283E+10 | 0.23 | 612.92 | 01-OCT-06:10 | 0.33 |
November | 0.112532E+10 | 0.23 | 612.92 | 01-NOV-06:05 | 0.33 |
December | 0.116283E+10 | 0.23 | 612.92 | 01-DEC-07:05 | 0.33 |
Annual Sum or Average | 0.136914E+11 | 0.23 | |||
Minimum of Months | 0.105030E+10 | 0.23 | 612.92 | 0.32 | |
Maximum of Months | 0.116283E+10 | 0.23 | 612.92 | 0.33 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.338590E+09 | 0.59 | 1021.72 | 01-JAN-09:02 | 0.71 |
February | 0.368373E+09 | 0.60 | 1021.72 | 01-FEB-09:02 | 0.71 |
March | 0.437223E+09 | 0.59 | 1021.72 | 01-MAR-16:02 | 0.71 |
April | 0.342497E+09 | 0.57 | 1021.72 | 02-APR-08:62 | 0.71 |
May | 0.454909E+09 | 0.62 | 1021.72 | 01-MAY-15:02 | 0.71 |
June | 0.877700E+09 | 0.67 | 1021.72 | 01-JUN-08:62 | 0.70 |
July | 0.822884E+09 | 0.67 | 1021.72 | 01-JUL-08:61 | 0.71 |
August | 0.821286E+09 | 0.67 | 1021.72 | 01-AUG-08:62 | 0.71 |
September | 0.706296E+09 | 0.66 | 1021.72 | 01-SEP-08:62 | 0.70 |
October | 0.489870E+09 | 0.63 | 1021.72 | 01-OCT-08:61 | 0.70 |
November | 0.349923E+09 | 0.59 | 1021.72 | 01-NOV-08:62 | 0.71 |
December | 0.450161E+09 | 0.58 | 1021.72 | 01-DEC-16:01 | 0.71 |
Annual Sum or Average | 0.645971E+10 | 0.62 | |||
Minimum of Months | 0.338590E+09 | 0.57 | 1021.72 | 0.70 | |
Maximum of Months | 0.877700E+09 | 0.67 | 1021.72 | 0.71 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.345140E+09 | 0.53 | 998.08 | 01-JAN-09:02 | 0.71 |
February | 0.343374E+09 | 0.55 | 998.08 | 01-FEB-09:02 | 0.71 |
March | 0.323725E+09 | 0.53 | 998.08 | 01-MAR-09:02 | 0.71 |
April | 0.264237E+09 | 0.51 | 998.08 | 02-APR-08:62 | 0.71 |
May | 0.321429E+09 | 0.50 | 998.08 | 01-MAY-15:02 | 0.71 |
June | 0.754497E+09 | 0.53 | 998.08 | 01-JUN-08:51 | 0.70 |
July | 0.678466E+09 | 0.52 | 998.08 | 01-JUL-08:61 | 0.71 |
August | 0.624703E+09 | 0.52 | 998.08 | 01-AUG-08:52 | 0.71 |
September | 0.448884E+09 | 0.49 | 998.08 | 01-SEP-08:51 | 0.70 |
October | 0.302785E+09 | 0.53 | 998.08 | 01-OCT-08:61 | 0.70 |
November | 0.296119E+09 | 0.54 | 998.08 | 01-NOV-08:62 | 0.71 |
December | 0.508730E+09 | 0.56 | 998.08 | 01-DEC-09:02 | 0.71 |
Annual Sum or Average | 0.521209E+10 | 0.52 | |||
Minimum of Months | 0.264237E+09 | 0.49 | 998.08 | 0.70 | |
Maximum of Months | 0.754497E+09 | 0.56 | 998.08 | 0.71 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.211284E+10 | 0.40 | 5079.15 | 20-JAN-12:40 | 0.71 |
February | 0.147704E+10 | 0.33 | 3813.38 | 18-FEB-13:00 | 0.71 |
March | 0.148805E+10 | 0.32 | 3538.55 | 14-MAR-12:40 | 0.71 |
April | 0.613548E+09 | 0.21 | 1774.78 | 08-APR-13:00 | 0.71 |
May | 0.152919E+10 | 0.52 | 1580.74 | 16-MAY-13:20 | 0.71 |
June | 0.253359E+10 | 0.70 | 1759.12 | 26-JUN-17:15 | 0.71 |
July | 0.271758E+10 | 0.70 | 1893.67 | 17-JUL-13:30 | 0.71 |
August | 0.307593E+10 | 0.70 | 3316.96 | 31-AUG-12:50 | 0.70 |
September | 0.322310E+10 | 0.68 | 5311.17 | 09-SEP-12:30 | 0.71 |
October | 0.240392E+10 | 0.44 | 5832.50 | 09-OCT-11:20 | 0.71 |
November | 0.197896E+10 | 0.39 | 5053.34 | 07-NOV-12:10 | 0.71 |
December | 0.130442E+10 | 0.26 | 3669.54 | 17-DEC-12:30 | 0.71 |
Annual Sum or Average | 0.244582E+11 | 0.47 | |||
Minimum of Months | 0.613548E+09 | 0.21 | 1580.74 | 0.70 | |
Maximum of Months | 0.322310E+10 | 0.70 | 5832.50 | 0.71 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.140345E+10 | 0.50 | 5274.02 | 01-JAN-16:02 | 0.71 |
February | 0.141653E+10 | 0.50 | 5274.02 | 01-FEB-09:02 | 0.71 |
March | 0.129473E+10 | 0.48 | 5274.02 | 02-MAR-16:01 | 0.71 |
April | 0.127134E+10 | 0.47 | 5274.02 | 01-APR-08:62 | 0.71 |
May | 0.261453E+10 | 0.44 | 5274.02 | 01-MAY-08:63 | 0.71 |
June | 0.486378E+10 | 0.50 | 5274.02 | 01-JUN-08:51 | 0.70 |
July | 0.501463E+10 | 0.49 | 5274.02 | 01-JUL-08:61 | 0.71 |
August | 0.401837E+10 | 0.47 | 5274.02 | 01-AUG-08:52 | 0.71 |
September | 0.293072E+10 | 0.43 | 5274.02 | 01-SEP-08:51 | 0.70 |
October | 0.138321E+10 | 0.47 | 5274.02 | 01-OCT-08:61 | 0.71 |
November | 0.122219E+10 | 0.49 | 5274.02 | 01-NOV-08:62 | 0.71 |
December | 0.203931E+10 | 0.52 | 5274.02 | 01-DEC-19:02 | 0.71 |
Annual Sum or Average | 0.294728E+11 | 0.48 | |||
Minimum of Months | 0.122219E+10 | 0.43 | 5274.02 | 0.70 | |
Maximum of Months | 0.501463E+10 | 0.52 | 5274.02 | 0.71 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.342883E+09 | 0.59 | 900.09 | 01-JAN-09:02 | 0.71 |
February | 0.379940E+09 | 0.61 | 900.09 | 01-FEB-09:02 | 0.71 |
March | 0.443541E+09 | 0.61 | 900.09 | 01-MAR-09:02 | 0.71 |
April | 0.357030E+09 | 0.59 | 900.09 | 02-APR-08:62 | 0.71 |
May | 0.486824E+09 | 0.65 | 900.09 | 01-MAY-15:02 | 0.71 |
June | 0.931096E+09 | 0.69 | 900.09 | 01-JUN-08:62 | 0.70 |
July | 0.937524E+09 | 0.69 | 900.09 | 01-JUL-06:35 | 0.71 |
August | 0.914566E+09 | 0.69 | 900.09 | 01-AUG-08:62 | 0.71 |
September | 0.744808E+09 | 0.68 | 900.09 | 01-SEP-08:62 | 0.70 |
October | 0.464090E+09 | 0.64 | 900.09 | 01-OCT-08:61 | 0.70 |
November | 0.348555E+09 | 0.59 | 900.09 | 01-NOV-08:62 | 0.71 |
December | 0.440942E+09 | 0.57 | 900.09 | 01-DEC-09:02 | 0.71 |
Annual Sum or Average | 0.679180E+10 | 0.63 | |||
Minimum of Months | 0.342883E+09 | 0.57 | 900.09 | 0.70 | |
Maximum of Months | 0.937524E+09 | 0.69 | 900.09 | 0.71 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.332080E+09 | 0.51 | 880.58 | 01-JAN-09:02 | 0.71 |
February | 0.335494E+09 | 0.55 | 880.58 | 01-FEB-09:02 | 0.71 |
March | 0.328015E+09 | 0.54 | 880.58 | 01-MAR-09:02 | 0.70 |
April | 0.293776E+09 | 0.54 | 880.58 | 01-APR-15:02 | 0.71 |
May | 0.368755E+09 | 0.54 | 880.58 | 01-MAY-15:02 | 0.71 |
June | 0.758738E+09 | 0.55 | 880.58 | 01-JUN-08:51 | 0.70 |
July | 0.743810E+09 | 0.53 | 880.58 | 01-JUL-07:32 | 0.71 |
August | 0.668977E+09 | 0.54 | 880.58 | 01-AUG-08:32 | 0.71 |
September | 0.491400E+09 | 0.52 | 880.58 | 01-SEP-08:51 | 0.70 |
October | 0.298847E+09 | 0.55 | 880.58 | 01-OCT-08:61 | 0.70 |
November | 0.294593E+09 | 0.52 | 880.58 | 01-NOV-08:62 | 0.71 |
December | 0.483100E+09 | 0.55 | 880.58 | 01-DEC-09:02 | 0.71 |
Annual Sum or Average | 0.539758E+10 | 0.54 | |||
Minimum of Months | 0.293776E+09 | 0.51 | 880.58 | 0.70 | |
Maximum of Months | 0.758738E+09 | 0.55 | 880.58 | 0.71 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.107444E+09 | 0.58 | 271.37 | 01-JAN-16:02 | 0.71 |
February | 0.112375E+09 | 0.59 | 271.37 | 01-FEB-09:02 | 0.71 |
March | 0.125765E+09 | 0.60 | 271.37 | 01-MAR-19:02 | 0.71 |
April | 0.101694E+09 | 0.59 | 271.37 | 01-APR-15:02 | 0.71 |
May | 0.116439E+09 | 0.62 | 271.37 | 01-MAY-15:02 | 0.71 |
June | 0.225619E+09 | 0.67 | 271.37 | 01-JUN-08:62 | 0.70 |
July | 0.208095E+09 | 0.67 | 271.37 | 01-JUL-08:61 | 0.71 |
August | 0.208139E+09 | 0.67 | 271.37 | 01-AUG-08:62 | 0.71 |
September | 0.174313E+09 | 0.66 | 271.37 | 01-SEP-08:62 | 0.70 |
October | 0.133125E+09 | 0.63 | 271.37 | 01-OCT-08:61 | 0.70 |
November | 0.104064E+09 | 0.60 | 271.37 | 01-NOV-08:62 | 0.71 |
December | 0.143298E+09 | 0.59 | 271.37 | 01-DEC-16:01 | 0.71 |
Annual Sum or Average | 0.176037E+10 | 0.62 | |||
Minimum of Months | 0.101694E+09 | 0.58 | 271.37 | 0.70 | |
Maximum of Months | 0.225619E+09 | 0.67 | 271.37 | 0.71 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.114658E+09 | 0.54 | 264.58 | 01-JAN-09:02 | 0.71 |
February | 0.111558E+09 | 0.57 | 264.58 | 01-FEB-09:02 | 0.71 |
March | 98443317.38 | 0.55 | 264.58 | 01-MAR-09:02 | 0.70 |
April | 81263706.12 | 0.52 | 264.58 | 01-APR-15:02 | 0.71 |
May | 81569665.94 | 0.51 | 264.58 | 01-MAY-15:02 | 0.71 |
June | 0.198802E+09 | 0.53 | 264.58 | 01-JUN-08:51 | 0.70 |
July | 0.175977E+09 | 0.52 | 264.58 | 01-JUL-08:61 | 0.71 |
August | 0.162333E+09 | 0.52 | 264.58 | 01-AUG-08:52 | 0.71 |
September | 0.110929E+09 | 0.49 | 264.58 | 01-SEP-08:51 | 0.70 |
October | 89173511.63 | 0.54 | 264.58 | 01-OCT-08:61 | 0.70 |
November | 98097850.84 | 0.55 | 264.58 | 01-NOV-08:62 | 0.71 |
December | 0.165672E+09 | 0.58 | 264.58 | 01-DEC-09:02 | 0.71 |
Annual Sum or Average | 0.148848E+10 | 0.53 | |||
Minimum of Months | 81263706.12 | 0.49 | 264.58 | 0.70 | |
Maximum of Months | 0.198802E+09 | 0.58 | 264.58 | 0.71 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.885893E+09 | 0.63 | 1187.04 | 01-JAN-09:02 | 0.71 |
February | 0.792135E+09 | 0.64 | 1187.04 | 01-FEB-09:02 | 0.71 |
March | 0.750908E+09 | 0.62 | 1187.04 | 01-MAR-09:02 | 0.70 |
April | 0.465742E+09 | 0.59 | 1187.04 | 02-APR-08:62 | 0.71 |
May | 0.534586E+09 | 0.63 | 1187.04 | 01-MAY-15:02 | 0.71 |
June | 0.921235E+09 | 0.67 | 1187.04 | 01-JUN-08:62 | 0.70 |
July | 0.977978E+09 | 0.67 | 1187.04 | 01-JUL-08:61 | 0.71 |
August | 0.110338E+10 | 0.67 | 1187.04 | 01-AUG-08:62 | 0.71 |
September | 0.113731E+10 | 0.67 | 1187.04 | 01-SEP-08:62 | 0.70 |
October | 0.980799E+09 | 0.64 | 1187.04 | 01-OCT-08:61 | 0.70 |
November | 0.897689E+09 | 0.64 | 1187.04 | 01-NOV-08:62 | 0.71 |
December | 0.822841E+09 | 0.62 | 1187.04 | 01-DEC-09:02 | 0.71 |
Annual Sum or Average | 0.102705E+11 | 0.64 | |||
Minimum of Months | 0.465742E+09 | 0.59 | 1187.04 | 0.70 | |
Maximum of Months | 0.113731E+10 | 0.67 | 1187.04 | 0.71 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.860789E+09 | 0.774710E+09 | 984.37 | 05-JAN-19:03 | 885.94 | 885.94 | 33.19 | 1.86 |
February | 0.871377E+09 | 0.784239E+09 | 969.15 | 12-FEB-07:10 | 872.24 | 872.24 | 35.80 | 1.79 |
March | 0.751293E+09 | 0.676164E+09 | 938.63 | 21-MAR-15:02 | 844.77 | 844.77 | 33.21 | 1.66 |
April | 0.670942E+09 | 0.603848E+09 | 842.21 | 04-APR-10:00 | 757.99 | 757.99 | 39.18 | 1.33 |
May | 0.472695E+09 | 0.425425E+09 | 810.22 | 01-MAY-00:10 | 729.20 | 729.20 | 35.36 | 1.24 |
June | 31980204.24 | 28782183.81 | 680.86 | 09-JUN-03:40 | 612.78 | 612.78 | 32.02 | 0.94 |
July | 28937857.49 | 26044071.74 | 484.94 | 02-JUL-05:00 | 436.45 | 436.45 | 29.56 | 0.60 |
August | 29421666.28 | 26479499.65 | 358.29 | 12-AUG-23:00 | 322.46 | 322.46 | 27.31 | 0.42 |
September | 0.182300E+09 | 0.164070E+09 | 806.56 | 22-SEP-09:20 | 725.91 | 725.91 | 39.59 | 1.23 |
October | 0.592970E+09 | 0.533673E+09 | 871.73 | 27-OCT-10:00 | 784.56 | 784.56 | 36.65 | 1.42 |
November | 0.688128E+09 | 0.619315E+09 | 928.10 | 24-NOV-16:03 | 835.29 | 835.29 | 34.49 | 1.61 |
December | 0.110272E+10 | 0.992447E+09 | 1046.35 | 21-DEC-09:05 | 941.71 | 941.71 | 34.60 | 2.24 |
Annual Sum or Average | 0.628355E+10 | 0.565520E+10 | ||||||
Minimum of Months | 28937857.49 | 26044071.74 | 358.29 | 322.46 | 322.46 | 27.31 | 0.42 | |
Maximum of Months | 0.110272E+10 | 0.992447E+09 | 1046.35 | 941.71 | 941.71 | 39.59 | 2.24 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 38458203.68 | 34612383.31 | 280.51 | 23-JAN-16:02 | 252.46 | 252.46 | 6.72 | 7.35 |
February | 31272610.18 | 28145349.17 | 281.97 | 18-FEB-16:01 | 253.77 | 253.77 | 6.72 | 7.37 |
March | 66836522.86 | 60152870.57 | 575.72 | 13-MAR-15:03 | 518.15 | 518.15 | 6.72 | 10.10 |
April | 46337508.41 | 41703757.57 | 404.83 | 07-APR-15:03 | 364.35 | 364.35 | 6.72 | 8.66 |
May | 0.216163E+09 | 0.194547E+09 | 1743.13 | 31-MAY-18:50 | 1568.81 | 1568.81 | 6.72 | 16.03 |
June | 0.961454E+09 | 0.865309E+09 | 3064.89 | 15-JUN-18:02 | 2758.40 | 2758.40 | 6.72 | 20.09 |
July | 0.114193E+10 | 0.102774E+10 | 3147.61 | 10-JUL-18:02 | 2832.85 | 2832.85 | 6.72 | 20.30 |
August | 0.107189E+10 | 0.964698E+09 | 3043.81 | 10-AUG-19:03 | 2739.43 | 2739.43 | 6.72 | 20.03 |
September | 0.607204E+09 | 0.546483E+09 | 3086.87 | 12-SEP-18:20 | 2778.18 | 2778.18 | 6.72 | 20.14 |
October | 0.116389E+09 | 0.104750E+09 | 685.62 | 11-OCT-15:13 | 617.06 | 617.06 | 6.72 | 10.88 |
November | 51395818.39 | 46256236.55 | 386.79 | 06-NOV-16:02 | 348.11 | 348.11 | 6.72 | 8.49 |
December | 27232712.52 | 24509441.27 | 248.22 | 02-DEC-16:01 | 223.40 | 223.40 | 6.72 | 6.96 |
Annual Sum or Average | 0.437656E+10 | 0.393891E+10 | ||||||
Minimum of Months | 27232712.52 | 24509441.27 | 248.22 | 223.40 | 223.40 | 6.72 | 6.96 | |
Maximum of Months | 0.114193E+10 | 0.102774E+10 | 3147.61 | 2832.85 | 2832.85 | 6.72 | 20.30 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.416891E+10 | 0.375202E+10 | 2382.15 | 01-JAN-00:10 | 2143.93 | 2143.93 | 6.75 | 21.07 |
February | 0.319677E+10 | 0.287709E+10 | 2382.15 | 01-FEB-11:50 | 2143.93 | 2143.93 | 6.73 | 21.07 |
March | 0.410367E+10 | 0.369330E+10 | 2382.15 | 01-MAR-07:05 | 2143.93 | 2143.93 | 6.73 | 21.07 |
April | 0.411362E+10 | 0.370226E+10 | 2382.15 | 01-APR-00:10 | 2143.93 | 2143.93 | 6.82 | 21.07 |
May | 0.617072E+10 | 0.555365E+10 | 2382.15 | 01-MAY-00:05 | 2143.93 | 2143.93 | 6.73 | 21.07 |
June | 0.617453E+10 | 0.555708E+10 | 2382.15 | 01-JUN-00:05 | 2143.93 | 2143.93 | 7.50 | 21.07 |
July | 0.638035E+10 | 0.574231E+10 | 2382.15 | 01-JUL-00:10 | 2143.93 | 2143.93 | 9.00 | 21.07 |
August | 0.638035E+10 | 0.574231E+10 | 2382.15 | 01-AUG-00:05 | 2143.93 | 2143.93 | 8.27 | 21.07 |
September | 0.612327E+10 | 0.551094E+10 | 2382.15 | 01-SEP-00:10 | 2143.93 | 2143.93 | 8.12 | 21.07 |
October | 0.473342E+10 | 0.426008E+10 | 2382.15 | 01-OCT-00:10 | 2143.93 | 2143.93 | 7.00 | 21.07 |
November | 0.415940E+10 | 0.374346E+10 | 2382.15 | 01-NOV-03:05 | 2143.93 | 2143.93 | 6.72 | 21.07 |
December | 0.312492E+10 | 0.281243E+10 | 2382.15 | 01-DEC-07:15 | 2143.93 | 2143.93 | 6.74 | 21.07 |
Annual Sum or Average | 0.588299E+11 | 0.529469E+11 | ||||||
Minimum of Months | 0.312492E+10 | 0.281243E+10 | 2382.15 | 2143.93 | 2143.93 | 6.72 | 21.07 | |
Maximum of Months | 0.638035E+10 | 0.574231E+10 | 2382.15 | 2143.93 | 2143.93 | 9.00 | 21.07 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:10 | 14.37 | 14.37 | 48.58 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:10 | 14.37 | 14.37 | 49.39 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:10 | 14.37 | 14.37 | 49.41 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 52.23 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:05 | 14.37 | 14.37 | 52.37 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:05 | 14.37 | 14.37 | 52.83 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 53.42 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:05 | 14.37 | 14.37 | 53.43 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:10 | 14.37 | 14.37 | 53.62 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:10 | 14.37 | 14.37 | 52.59 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:05 | 14.37 | 14.37 | 52.78 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:10 | 14.37 | 14.37 | 50.16 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 48.58 | 0.37 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 53.62 | 0.37 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 45.74 | 60.00 | 39593.28 | 209447.12 | 05-JAN-19:05 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 40.28 | 60.00 | 45300.08 | 196265.22 | 07-FEB-16:03 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 45.99 | 60.00 | 35572.28 | 185402.32 | 21-MAR-15:02 |
April | 0.00 | 0.00 | 01-APR-00:10 | 32.05 | 60.00 | 33864.41 | 136872.06 | 10-APR-08:05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 35.39 | 60.00 | 27259.92 | 131917.38 | 02-MAY-18:04 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 24.93 | 24.93 | 1959.22 | 110306.14 | 09-JUN-03:40 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 23.78 | 23.78 | 1702.32 | 76251.29 | 02-JUL-05:00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.26 | 33.26 | 1734.27 | 57000.48 | 12-AUG-23:00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 25.33 | 25.33 | 10879.95 | 133730.84 | 21-SEP-14:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.27 | 60.00 | 30040.07 | 158252.24 | 30-OCT-08:62 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 40.33 | 60.00 | 31809.96 | 172065.05 | 24-NOV-16:03 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 46.40 | 60.00 | 57533.42 | 238212.65 | 21-DEC-09:05 |
Annual Sum or Average | 0.00 | 26357.02 | ||||||
Minimum of Months | 0.00 | 0.00 | 23.78 | 23.78 | 1702.32 | 57000.48 | ||
Maximum of Months | 0.00 | 0.00 | 46.40 | 60.00 | 57533.42 | 238212.65 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 21272.74 | 225662.05 | 20-JAN-13:15 | 9.25 | 6.70 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 17754.05 | 209418.44 | 18-FEB-13:37 | 9.07 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 26289.27 | 335252.26 | 13-MAR-15:03 | 10.50 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 20937.69 | 265968.71 | 07-APR-15:03 | 9.71 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 65793.30 | 354920.70 | 31-MAY-18:03 | 10.72 | 6.70 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 178512.21 | 437228.03 | 27-JUN-18:52 | 11.65 | 6.70 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 192800.31 | 430418.79 | 17-JUL-18:42 | 11.58 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 178053.15 | 422304.12 | 25-AUG-18:15 | 11.48 | 6.70 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 135473.21 | 408343.42 | 13-SEP-15:04 | 11.33 | 6.70 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 41205.63 | 372559.50 | 11-OCT-15:03 | 10.92 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 24684.18 | 281283.13 | 05-NOV-15:02 | 9.88 | 6.70 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 15262.90 | 201701.22 | 02-DEC-13:15 | 8.98 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 76839.25 | 0.00 | ||||||
Minimum of Months | 15262.90 | 201701.22 | 8.98 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 192800.31 | 437228.03 | 11.65 | 6.70 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 48.58 | 60.05 | 27974.26 | 59065.78 | 31-JAN-07:40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 49.39 | 60.05 | 28321.34 | 59222.68 | 13-FEB-08:00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 49.41 | 60.05 | 27930.19 | 58991.42 | 01-MAR-07:50 |
April | 0.00 | 0.00 | 01-APR-00:10 | 52.23 | 60.05 | 26830.37 | 57149.89 | 03-APR-06:20 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 52.37 | 60.05 | 25360.12 | 54536.01 | 01-MAY-06:30 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 52.83 | 60.05 | 23903.64 | 51281.59 | 01-JUN-06:57 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 53.42 | 60.05 | 22820.66 | 48438.34 | 03-JUL-06:15 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 53.43 | 60.05 | 22471.55 | 47091.05 | 31-AUG-06:45 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 53.62 | 60.05 | 22886.16 | 48636.47 | 29-SEP-06:45 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 52.59 | 60.05 | 23978.68 | 51558.90 | 31-OCT-07:00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 52.78 | 60.05 | 25457.24 | 54711.25 | 30-NOV-07:40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 50.16 | 60.05 | 26914.09 | 57361.34 | 29-DEC-07:15 |
Annual Sum or Average | 0.00 | 25387.00 | ||||||
Minimum of Months | 0.00 | 0.00 | 48.58 | 60.05 | 22471.55 | 47091.05 | ||
Maximum of Months | 0.00 | 0.00 | 53.62 | 60.05 | 28321.34 | 59222.68 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.164443E+10 | 0.00 | 0.192282E+09 | 0.271000E+10 | 0.00 | 0.00 |
February | 0.176228E+10 | 0.00 | 0.123483E+09 | 0.244774E+10 | 0.00 | 0.00 |
March | 0.704855E+09 | 0.00 | 0.894175E+09 | 0.271000E+10 | 0.00 | 0.00 |
April | 0.320535E+09 | 0.00 | 0.105845E+10 | 0.262258E+10 | 0.00 | 0.00 |
May | 15734.47 | 0.00 | 0.512689E+10 | 0.271000E+10 | 0.00 | 0.00 |
June | 31347.18 | 0.00 | 0.173293E+11 | 0.262258E+10 | 0.00 | 0.00 |
July | 40835.88 | 0.00 | 0.210710E+11 | 0.271000E+10 | 0.00 | 0.00 |
August | 32874.84 | 0.00 | 0.182586E+11 | 0.271000E+10 | 0.00 | 0.00 |
September | 947394.74 | 0.00 | 0.117438E+11 | 0.262258E+10 | 0.00 | 0.00 |
October | 0.507572E+09 | 0.00 | 0.173362E+10 | 0.271000E+10 | 0.00 | 0.00 |
November | 0.821371E+09 | 0.00 | 0.497130E+09 | 0.262258E+10 | 0.00 | 0.00 |
December | 0.309429E+10 | 0.00 | 0.275091E+09 | 0.271000E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.885640E+10 | 0.00 | 0.783038E+11 | 0.319080E+11 | 0.00 | 0.00 |
Minimum of Months | 15734.47 | 0.00 | 0.123483E+09 | 0.244774E+10 | 0.00 | 0.00 |
Maximum of Months | 0.309429E+10 | 0.00 | 0.210710E+11 | 0.271000E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.791499E+11 | 0.00 | 0.527522E+10 | 0.339364E+11 | 0.00 | 0.00 |
February | 0.799859E+11 | 0.00 | 0.295321E+10 | 0.300766E+11 | 0.00 | 0.00 |
March | 0.782555E+11 | 0.00 | 0.182652E+11 | 0.344417E+11 | 0.00 | 0.00 |
April | 0.762682E+11 | 0.00 | 0.191272E+11 | 0.328592E+11 | 0.00 | 0.00 |
May | 0.726140E+11 | 0.00 | 0.890894E+11 | 0.371047E+11 | 0.00 | 0.00 |
June | 0.510729E+10 | 0.00 | 0.292388E+12 | 0.415571E+11 | 0.00 | 0.00 |
July | 0.457452E+10 | 0.00 | 0.336345E+12 | 0.431439E+11 | 0.00 | 0.00 |
August | 0.467773E+10 | 0.00 | 0.300331E+12 | 0.442910E+11 | 0.00 | 0.00 |
September | 0.280469E+11 | 0.00 | 0.206989E+12 | 0.425323E+11 | 0.00 | 0.00 |
October | 0.689564E+11 | 0.00 | 0.338864E+11 | 0.384708E+11 | 0.00 | 0.00 |
November | 0.622203E+11 | 0.00 | 0.107359E+11 | 0.351799E+11 | 0.00 | 0.00 |
December | 0.111621E+12 | 0.00 | 0.717379E+10 | 0.340459E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.671477E+12 | 0.00 | 0.132256E+13 | 0.447639E+12 | 0.00 | 0.00 |
Minimum of Months | 0.457452E+10 | 0.00 | 0.295321E+10 | 0.300766E+11 | 0.00 | 0.00 |
Maximum of Months | 0.111621E+12 | 0.00 | 0.336345E+12 | 0.442910E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.271000E+10 | 0.192282E+09 | 0.164443E+10 | 0.474162E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244774E+10 | 0.123483E+09 | 0.176228E+10 | 0.453602E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.271000E+10 | 0.894175E+09 | 0.704855E+09 | 0.363527E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.262258E+10 | 0.105845E+10 | 0.320535E+09 | 0.317220E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.271000E+10 | 0.512689E+10 | 15734.47 | 0.126772E+11 | 11395912.11 | 0.00 | 0.00 | 0.00 |
June | 0.262258E+10 | 0.173293E+11 | 31347.18 | 0.165137E+10 | 0.906471E+09 | 0.00 | 0.00 | 0.00 |
July | 0.271000E+10 | 0.210710E+11 | 40835.88 | 0.131115E+10 | 0.108106E+10 | 0.00 | 0.00 | 0.00 |
August | 0.271000E+10 | 0.182586E+11 | 32874.84 | 0.142542E+10 | 0.621930E+09 | 0.00 | 0.00 | 0.00 |
September | 0.262258E+10 | 0.117438E+11 | 947394.74 | 0.531306E+10 | 0.175369E+09 | 0.00 | 0.00 | 0.00 |
October | 0.271000E+10 | 0.173362E+10 | 0.507572E+09 | 0.297810E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.262258E+10 | 0.497130E+09 | 0.821371E+09 | 0.406997E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.271000E+10 | 0.275091E+09 | 0.309429E+10 | 0.506643E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319080E+11 | 0.783038E+11 | 0.885640E+10 | 0.304374E+12 | 0.279622E+10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244774E+10 | 0.123483E+09 | 15734.47 | 0.131115E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.271000E+10 | 0.210710E+11 | 0.309429E+10 | 0.506643E+11 | 0.108106E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.339364E+11 | 0.527522E+10 | 0.791499E+11 | 0.530029E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.300766E+11 | 0.295321E+10 | 0.799859E+11 | 0.508591E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.344417E+11 | 0.182652E+11 | 0.782555E+11 | 0.365225E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.328592E+11 | 0.191272E+11 | 0.762682E+11 | 0.301740E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.371047E+11 | 0.890894E+11 | 0.726140E+11 | 0.507118E+11 | 0.412755E+09 | 0.00 | 0.00 | 0.00 |
June | 0.415571E+11 | 0.292388E+12 | 0.510729E+10 | 0.698887E+10 | 0.186845E+11 | 0.00 | 0.00 | 0.00 |
July | 0.431439E+11 | 0.336345E+12 | 0.457452E+10 | 0.659988E+10 | 0.201311E+11 | 0.00 | 0.00 | 0.00 |
August | 0.442910E+11 | 0.300331E+12 | 0.467773E+10 | 0.633136E+10 | 0.155755E+11 | 0.00 | 0.00 | 0.00 |
September | 0.425323E+11 | 0.206989E+12 | 0.280469E+11 | 0.236802E+11 | 0.588904E+10 | 0.00 | 0.00 | 0.00 |
October | 0.384708E+11 | 0.338864E+11 | 0.689564E+11 | 0.302231E+12 | 11644223.12 | 0.00 | 0.00 | 0.00 |
November | 0.351799E+11 | 0.107359E+11 | 0.622203E+11 | 0.457844E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.340459E+11 | 0.717379E+10 | 0.111621E+12 | 0.572440E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.447639E+12 | 0.132256E+13 | 0.671477E+12 | 0.313241E+13 | 0.607045E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.300766E+11 | 0.295321E+10 | 0.457452E+10 | 0.633136E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.442910E+11 | 0.336345E+12 | 0.111621E+12 | 0.572440E+12 | 0.201311E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.271000E+10 | 0.164443E+10 | 0.192282E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244774E+10 | 0.176228E+10 | 0.123483E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.271000E+10 | 0.704855E+09 | 0.894175E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.262258E+10 | 0.320535E+09 | 0.105845E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.271000E+10 | 15734.47 | 0.512689E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.262258E+10 | 31347.18 | 0.173293E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.271000E+10 | 40835.88 | 0.210710E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.271000E+10 | 32874.84 | 0.182586E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.262258E+10 | 947394.74 | 0.117438E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.271000E+10 | 0.507572E+09 | 0.173362E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.262258E+10 | 0.821371E+09 | 0.497130E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.271000E+10 | 0.309429E+10 | 0.275091E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319080E+11 | 0.885640E+10 | 0.783038E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244774E+10 | 15734.47 | 0.123483E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.271000E+10 | 0.309429E+10 | 0.210710E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.339364E+11 | 0.791499E+11 | 0.527522E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.300766E+11 | 0.799859E+11 | 0.295321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.344417E+11 | 0.782555E+11 | 0.182652E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.328592E+11 | 0.762682E+11 | 0.191272E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.371047E+11 | 0.726140E+11 | 0.890894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.415571E+11 | 0.510729E+10 | 0.292388E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.431439E+11 | 0.457452E+10 | 0.336345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.442910E+11 | 0.467773E+10 | 0.300331E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.425323E+11 | 0.280469E+11 | 0.206989E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.384708E+11 | 0.689564E+11 | 0.338864E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.351799E+11 | 0.622203E+11 | 0.107359E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.340459E+11 | 0.111621E+12 | 0.717379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.447639E+12 | 0.671477E+12 | 0.132256E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.300766E+11 | 0.457452E+10 | 0.295321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.442910E+11 | 0.111621E+12 | 0.336345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.773575E+10 | 0.00 | 0.00 | 42464971.80 | 0.00 | 0.00 | 0.432068E+11 | 0.00 | 1.05 |
February | 0.168991E+11 | 0.00 | 0.00 | 19651025.74 | 0.00 | 0.00 | 0.275252E+11 | 0.00 | 1.00 |
March | 0.305424E+11 | 0.00 | 0.00 | 9268909.93 | 0.00 | 0.00 | 0.157009E+11 | 0.00 | 0.98 |
April | 0.253975E+11 | 0.00 | 0.00 | 11063847.92 | 0.00 | 0.00 | 0.192557E+11 | 0.00 | 0.98 |
May | 0.241967E+11 | 0.00 | 0.00 | 10792220.43 | 2964611.47 | 0.00 | 0.168698E+11 | 0.00 | 0.97 |
June | 0.291700E+10 | 12643720.27 | 0.00 | 31622010.61 | 0.430355E+09 | 0.00 | 0.170462E+11 | 0.00 | 0.97 |
July | 0.117879E+10 | 46666344.19 | 0.00 | 39041764.12 | 0.555960E+09 | 0.00 | 0.168340E+11 | 0.00 | 0.98 |
August | 0.544618E+09 | 0.319930E+09 | 0.00 | 70615100.06 | 30928349.33 | 0.00 | 0.236957E+11 | 0.00 | 1.10 |
September | 13662305.74 | 75793323.90 | 0.00 | 95811843.24 | 0.00 | 0.00 | 0.380864E+11 | 0.00 | 1.26 |
October | 4288070.64 | 0.00 | 0.00 | 91730140.94 | 0.00 | 0.00 | 0.600111E+11 | 0.00 | 1.29 |
November | 33862496.79 | 0.00 | 0.00 | 83198067.72 | 0.00 | 0.00 | 0.579075E+11 | 0.00 | 1.28 |
December | 0.122082E+09 | 0.00 | 0.00 | 78280688.18 | 0.00 | 0.00 | 0.613341E+11 | 0.00 | 1.22 |
Annual Sum or Average | 0.109586E+12 | 0.455033E+09 | 0.00 | 0.583541E+09 | 0.102021E+10 | 0.00 | 0.397474E+12 | 0.00 | 1.09 |
Minimum of Months | 4288070.64 | 0.00 | 0.00 | 9268909.93 | 0.00 | 0.00 | 0.157009E+11 | 0.00 | 0.97 |
Maximum of Months | 0.305424E+11 | 0.319930E+09 | 0.00 | 95811843.24 | 0.555960E+09 | 0.00 | 0.613341E+11 | 0.00 | 1.29 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.467130E+10 | 0.00 | 0.00 | 4307351.53 | 0.00 | 0.641714E+09 | 0.284539E+10 | 0.00 | 3.09 |
February | 0.351494E+10 | 0.00 | 0.00 | 3825969.10 | 0.00 | 0.124651E+10 | 0.269883E+10 | 0.00 | 3.04 |
March | 0.431511E+10 | 0.00 | 0.00 | 4041785.61 | 0.00 | 0.962948E+09 | 0.216019E+10 | 0.00 | 2.94 |
April | 0.521647E+10 | 0.00 | 0.00 | 1176581.50 | 0.00 | 0.751082E+09 | 0.779746E+09 | 0.00 | 2.70 |
May | 0.551082E+10 | 518000.04 | 0.00 | 1152542.47 | 0.00 | 0.00 | 0.627855E+09 | 0.00 | 2.65 |
June | 0.179848E+10 | 91309308.45 | 0.00 | 4383292.10 | 314955.84 | 0.00 | 0.112281E+10 | 0.00 | 2.74 |
July | 0.151749E+10 | 0.113455E+09 | 0.00 | 4309975.81 | 3538208.54 | 0.00 | 0.108031E+10 | 0.00 | 2.74 |
August | 0.170983E+10 | 84925175.54 | 0.00 | 6421493.17 | 0.00 | 0.00 | 0.143271E+10 | 0.00 | 3.01 |
September | 0.244012E+10 | 20696454.39 | 0.00 | 8019955.24 | 0.00 | 0.00 | 0.184832E+10 | 0.00 | 3.13 |
October | 0.378199E+10 | 0.00 | 0.00 | 5881693.93 | 0.00 | 0.820951E+09 | 0.286957E+10 | 0.00 | 3.11 |
November | 0.417684E+10 | 0.00 | 0.00 | 4594676.61 | 0.00 | 0.584488E+09 | 0.290831E+10 | 0.00 | 3.11 |
December | 0.453635E+10 | 0.00 | 0.00 | 3195280.22 | 0.00 | 0.161338E+10 | 0.197844E+10 | 0.00 | 2.96 |
Annual Sum or Average | 0.431897E+11 | 0.310904E+09 | 0.00 | 51310597.31 | 3853164.38 | 0.662108E+10 | 0.223525E+11 | 0.00 | 2.93 |
Minimum of Months | 0.151749E+10 | 0.00 | 0.00 | 1152542.47 | 0.00 | 0.00 | 0.627855E+09 | 0.00 | 2.65 |
Maximum of Months | 0.551082E+10 | 0.113455E+09 | 0.00 | 8019955.24 | 3538208.54 | 0.161338E+10 | 0.290831E+10 | 0.00 | 3.13 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.301459E+10 | 0.00 | 0.00 | 962375.95 | 0.00 | 0.00 | 0.149124E+10 | 0.00 | 1.46 |
February | 0.284536E+10 | 0.00 | 0.00 | 813656.68 | 0.00 | 0.00 | 0.125880E+10 | 0.00 | 1.45 |
March | 0.263302E+10 | 0.00 | 0.00 | 1886986.85 | 0.00 | 0.00 | 0.186486E+10 | 0.00 | 1.49 |
April | 0.277963E+10 | 0.00 | 0.00 | 1087726.91 | 0.00 | 0.00 | 0.147033E+10 | 0.00 | 1.46 |
May | 0.122585E+10 | 279371.03 | 0.00 | 2806508.26 | 0.00 | 0.00 | 0.282245E+10 | 0.00 | 1.51 |
June | 55350711.98 | 43206154.71 | 0.00 | 6759853.19 | 567669.00 | 0.00 | 0.218272E+10 | 0.00 | 1.67 |
July | 24446201.42 | 53713708.43 | 0.00 | 6807953.16 | 4210041.42 | 0.00 | 0.196761E+10 | 0.00 | 1.64 |
August | 71710507.58 | 35553719.65 | 0.00 | 7029649.36 | 157610.75 | 0.00 | 0.225640E+10 | 0.00 | 1.70 |
September | 0.205431E+09 | 7412384.02 | 0.00 | 6573285.87 | 0.00 | 0.00 | 0.284236E+10 | 0.00 | 1.67 |
October | 0.174645E+10 | 0.00 | 0.00 | 3026230.43 | 0.00 | 0.00 | 0.269090E+10 | 0.00 | 1.51 |
November | 0.244807E+10 | 0.00 | 0.00 | 1308959.04 | 0.00 | 0.00 | 0.177798E+10 | 0.00 | 1.47 |
December | 0.362804E+10 | 0.00 | 0.00 | 589996.59 | 0.00 | 0.00 | 0.100067E+10 | 0.00 | 1.44 |
Annual Sum or Average | 0.206780E+11 | 0.140165E+09 | 0.00 | 39653182.29 | 4935321.16 | 0.00 | 0.236263E+11 | 0.00 | 1.54 |
Minimum of Months | 24446201.42 | 0.00 | 0.00 | 589996.59 | 0.00 | 0.00 | 0.100067E+10 | 0.00 | 1.44 |
Maximum of Months | 0.362804E+10 | 53713708.43 | 0.00 | 7029649.36 | 4210041.42 | 0.00 | 0.284236E+10 | 0.00 | 1.70 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.343307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77556162.22 | 0.00 | 0.00 | 0.53 |
February | 0.304546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154842E+09 | 0.00 | 0.00 | 0.53 |
March | 0.339929E+10 | 0.00 | 0.00 | 3797.33 | 0.00 | 0.00 | 22090790.39 | 0.00 | 0.53 |
April | 0.329504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
May | 0.286788E+10 | 0.00 | 0.00 | 145358.06 | 220638.72 | 0.00 | 0.175696E+09 | 0.00 | 0.53 |
June | 0.318426E+09 | 33608569.22 | 0.00 | 4035326.24 | 1400266.82 | 0.00 | 0.129701E+10 | 0.00 | 0.59 |
July | 0.147232E+09 | 34407242.13 | 0.00 | 4813936.51 | 12247113.67 | 0.00 | 0.132602E+10 | 0.00 | 0.60 |
August | 0.344162E+09 | 23837478.42 | 0.00 | 3769931.49 | 2610654.74 | 0.00 | 0.131687E+10 | 0.00 | 0.58 |
September | 0.108670E+10 | 4121969.51 | 0.00 | 2229951.17 | 1457708.55 | 0.00 | 0.105157E+10 | 0.00 | 0.56 |
October | 0.321628E+10 | 0.00 | 0.00 | 29049.75 | 0.00 | 35301612.74 | 52842294.82 | 0.00 | 0.53 |
November | 0.325757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8657618.86 | 0.00 | 0.00 | 0.53 |
December | 0.304316E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.591172E+09 | 0.00 | 0.00 | 0.53 |
Annual Sum or Average | 0.274543E+11 | 95975259.28 | 0.00 | 15027350.55 | 17936382.49 | 0.867530E+09 | 0.524211E+10 | 0.00 | 0.55 |
Minimum of Months | 0.147232E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
Maximum of Months | 0.343307E+10 | 34407242.13 | 0.00 | 4813936.51 | 12247113.67 | 0.591172E+09 | 0.132602E+10 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.194603E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173741E+09 | 0.00 | 0.00 | 0.56 |
February | 0.156098E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.371413E+09 | 0.00 | 0.00 | 0.56 |
March | 0.199333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72553352.33 | 0.00 | 0.00 | 0.56 |
April | 0.195590E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33692369.41 | 0.00 | 0.00 | 0.56 |
May | 0.183115E+10 | 0.00 | 0.00 | 262.09 | 133225.02 | 0.00 | 2895387.20 | 0.00 | 0.56 |
June | 0.503061E+09 | 19444609.71 | 0.00 | 1154204.88 | 1661982.16 | 0.00 | 0.385826E+09 | 0.00 | 0.56 |
July | 0.328165E+09 | 19840626.37 | 0.00 | 1448526.16 | 8489779.42 | 0.00 | 0.469278E+09 | 0.00 | 0.56 |
August | 0.586719E+09 | 13015590.81 | 0.00 | 763724.83 | 2797779.29 | 0.00 | 0.340764E+09 | 0.00 | 0.56 |
September | 0.104589E+10 | 2323421.50 | 0.00 | 339200.58 | 1043047.80 | 0.00 | 0.187233E+09 | 0.00 | 0.56 |
October | 0.190048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 94693295.19 | 0.00 | 0.00 | 0.56 |
November | 0.179860E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173591E+09 | 0.00 | 0.00 | 0.56 |
December | 0.166184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.532652E+09 | 0.00 | 0.00 | 0.55 |
Annual Sum or Average | 0.171122E+11 | 54624248.39 | 0.00 | 3705918.54 | 14125813.69 | 0.145234E+10 | 0.138600E+10 | 0.00 | 0.56 |
Minimum of Months | 0.328165E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.55 |
Maximum of Months | 0.199333E+10 | 19840626.37 | 0.00 | 1448526.16 | 8489779.42 | 0.532652E+09 | 0.469278E+09 | 0.00 | 0.56 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 14666214.30 | 0.00 | 0.00 | 0.108950E+09 | 0.00 | 0.00 | 0.822417E+11 | 0.00 | 26.48 |
February | 13877391.11 | 0.00 | 0.00 | 98047850.76 | 0.00 | 0.00 | 0.745715E+11 | 0.00 | 26.34 |
March | 0.00 | 0.00 | 0.00 | 0.113739E+09 | 0.00 | 0.00 | 0.807216E+11 | 0.00 | 26.50 |
April | 0.00 | 0.00 | 0.00 | 0.107317E+09 | 0.00 | 0.00 | 0.772021E+11 | 0.00 | 26.42 |
May | 0.00 | 4182546.72 | 0.00 | 0.129193E+09 | 0.00 | 0.00 | 0.721592E+11 | 0.00 | 26.49 |
June | 0.00 | 0.626544E+09 | 0.00 | 0.134823E+09 | 0.00 | 0.00 | 0.331235E+11 | 0.00 | 25.46 |
July | 0.00 | 0.857603E+09 | 0.00 | 0.127824E+09 | 0.00 | 0.00 | 0.294586E+11 | 0.00 | 25.19 |
August | 0.00 | 0.495644E+09 | 0.00 | 0.138899E+09 | 0.00 | 0.00 | 0.353721E+11 | 0.00 | 26.03 |
September | 0.00 | 0.104570E+09 | 0.00 | 0.133269E+09 | 0.00 | 0.00 | 0.485481E+11 | 0.00 | 26.36 |
October | 14223273.07 | 0.00 | 0.00 | 0.117397E+09 | 0.00 | 0.00 | 0.784131E+11 | 0.00 | 26.41 |
November | 0.00 | 0.00 | 0.00 | 0.106389E+09 | 0.00 | 0.00 | 0.766097E+11 | 0.00 | 26.49 |
December | 22388562.69 | 0.00 | 0.00 | 0.107356E+09 | 0.00 | 0.00 | 0.847111E+11 | 0.00 | 26.20 |
Annual Sum or Average | 65155441.17 | 0.208854E+10 | 0.00 | 0.142320E+10 | 0.00 | 0.00 | 0.773132E+12 | 0.00 | 26.20 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 98047850.76 | 0.00 | 0.00 | 0.294586E+11 | 0.00 | 25.19 |
Maximum of Months | 22388562.69 | 0.857603E+09 | 0.00 | 0.138899E+09 | 0.00 | 0.00 | 0.847111E+11 | 0.00 | 26.50 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.647307E+10 | 0.00 | 0.00 | 32845247.39 | 0.00 | 27549260.69 | 0.279868E+11 | 0.00 | 4.64 |
February | 0.710343E+10 | 0.00 | 0.00 | 28026836.99 | 0.00 | 0.125506E+09 | 0.242830E+11 | 0.00 | 4.59 |
March | 0.820082E+10 | 0.00 | 0.00 | 31115720.61 | 0.00 | 0.00 | 0.239911E+11 | 0.00 | 4.49 |
April | 0.100914E+11 | 0.00 | 0.00 | 19579967.14 | 0.00 | 0.00 | 0.188302E+11 | 0.00 | 4.13 |
May | 0.334345E+10 | 2156982.86 | 0.00 | 29267708.32 | 0.00 | 0.00 | 0.234566E+11 | 0.00 | 4.13 |
June | 0.471997E+09 | 0.339753E+09 | 0.00 | 41287262.84 | 149971.04 | 0.00 | 0.138398E+11 | 0.00 | 4.44 |
July | 0.221141E+09 | 0.448175E+09 | 0.00 | 41476839.60 | 173599.19 | 0.00 | 0.126198E+11 | 0.00 | 4.46 |
August | 0.426727E+09 | 0.311284E+09 | 0.00 | 48972579.00 | 0.00 | 0.00 | 0.148814E+11 | 0.00 | 4.81 |
September | 0.629574E+09 | 72859900.63 | 0.00 | 53160367.14 | 0.00 | 0.00 | 0.197893E+11 | 0.00 | 4.94 |
October | 0.633193E+10 | 0.00 | 0.00 | 40628422.78 | 0.00 | 0.139956E+09 | 0.259252E+11 | 0.00 | 4.73 |
November | 0.574667E+10 | 0.00 | 0.00 | 33906067.40 | 0.00 | 0.00 | 0.268076E+11 | 0.00 | 4.69 |
December | 0.105924E+11 | 0.00 | 0.00 | 25124605.05 | 0.00 | 0.522628E+09 | 0.230514E+11 | 0.00 | 4.44 |
Annual Sum or Average | 0.596326E+11 | 0.117423E+10 | 0.00 | 0.425392E+09 | 323570.23 | 0.815639E+09 | 0.255462E+12 | 0.00 | 4.54 |
Minimum of Months | 0.221141E+09 | 0.00 | 0.00 | 19579967.14 | 0.00 | 0.00 | 0.126198E+11 | 0.00 | 4.13 |
Maximum of Months | 0.105924E+11 | 0.448175E+09 | 0.00 | 53160367.14 | 173599.19 | 0.522628E+09 | 0.279868E+11 | 0.00 | 4.94 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.210421E+11 | 0.00 | 0.00 | 82656779.23 | 0.00 | 0.00 | 0.788361E+11 | 0.00 | 1.93 |
February | 0.253127E+11 | 0.00 | 0.00 | 65030418.57 | 0.00 | 0.00 | 0.651943E+11 | 0.00 | 1.91 |
March | 0.285105E+11 | 0.00 | 0.00 | 81402614.23 | 0.00 | 0.00 | 0.709754E+11 | 0.00 | 1.95 |
April | 0.315239E+11 | 0.00 | 0.00 | 56481568.50 | 0.00 | 0.00 | 0.620881E+11 | 0.00 | 1.91 |
May | 0.118785E+11 | 5933116.37 | 0.00 | 98697705.48 | 0.00 | 0.00 | 0.808560E+11 | 0.00 | 2.01 |
June | 0.909830E+09 | 0.912606E+09 | 0.00 | 0.150438E+09 | 7266943.27 | 0.00 | 0.503079E+11 | 0.00 | 2.16 |
July | 0.383559E+09 | 0.121226E+10 | 0.00 | 0.153116E+09 | 25869485.42 | 0.00 | 0.456642E+11 | 0.00 | 2.16 |
August | 0.752507E+09 | 0.775531E+09 | 0.00 | 0.163411E+09 | 1308133.78 | 0.00 | 0.527587E+11 | 0.00 | 2.23 |
September | 0.133239E+10 | 0.169023E+09 | 0.00 | 0.168113E+09 | 0.00 | 0.00 | 0.687045E+11 | 0.00 | 2.23 |
October | 0.165887E+11 | 0.00 | 0.00 | 0.116924E+09 | 0.00 | 0.00 | 0.836024E+11 | 0.00 | 2.04 |
November | 0.186720E+11 | 0.00 | 0.00 | 89682738.57 | 0.00 | 0.00 | 0.761147E+11 | 0.00 | 1.96 |
December | 0.402370E+11 | 0.00 | 0.00 | 61171607.94 | 0.00 | 0.00 | 0.613069E+11 | 0.00 | 1.88 |
Annual Sum or Average | 0.197144E+12 | 0.307535E+10 | 0.00 | 0.128713E+10 | 34444562.47 | 0.00 | 0.796409E+12 | 0.00 | 2.03 |
Minimum of Months | 0.383559E+09 | 0.00 | 0.00 | 56481568.50 | 0.00 | 0.00 | 0.456642E+11 | 0.00 | 1.88 |
Maximum of Months | 0.402370E+11 | 0.121226E+10 | 0.00 | 0.168113E+09 | 25869485.42 | 0.00 | 0.836024E+11 | 0.00 | 2.23 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 24673510.60 | 0.00 | 0.00 | 4213524.28 | 0.00 | 0.923857E+09 | 0.482033E+09 | 0.00 | 0.36 |
February | 20711116.88 | 0.00 | 0.00 | 4311825.35 | 0.00 | 0.827403E+09 | 0.453445E+09 | 0.00 | 0.36 |
March | 34933167.79 | 0.00 | 0.00 | 8799482.60 | 0.00 | 0.700326E+09 | 0.631031E+09 | 0.00 | 0.36 |
April | 38402312.31 | 0.00 | 0.00 | 6283086.28 | 0.00 | 0.634351E+09 | 0.615343E+09 | 0.00 | 0.36 |
May | 17392621.31 | 0.00 | 0.00 | 14414968.48 | 0.00 | 90412004.70 | 0.106491E+10 | 0.00 | 0.35 |
June | 0.00 | 5883868.82 | 0.00 | 22635256.40 | 0.00 | 403228.99 | 0.619829E+09 | 0.00 | 0.35 |
July | 0.00 | 16701646.46 | 0.00 | 19713049.16 | 0.00 | 396038.20 | 0.502187E+09 | 358.13 | 0.35 |
August | 0.00 | 22575587.93 | 0.00 | 22295749.16 | 0.00 | 971517.60 | 0.578056E+09 | 0.00 | 0.35 |
September | 4117269.11 | 499175.23 | 0.00 | 20748655.00 | 0.00 | 33867243.15 | 0.840485E+09 | 0.00 | 0.35 |
October | 13745526.49 | 0.00 | 0.00 | 12211017.69 | 0.00 | 0.448949E+09 | 0.861205E+09 | 0.00 | 0.35 |
November | 20780365.07 | 0.00 | 0.00 | 5346207.33 | 0.00 | 0.710363E+09 | 0.609798E+09 | 0.00 | 0.36 |
December | 38675231.43 | 0.00 | 0.00 | 2479128.48 | 0.00 | 0.114461E+10 | 0.315226E+09 | 0.00 | 0.35 |
Annual Sum or Average | 0.213431E+09 | 45660278.44 | 0.00 | 0.143452E+09 | 0.00 | 0.551590E+10 | 0.757354E+10 | 358.13 | 0.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 2479128.48 | 0.00 | 396038.20 | 0.315226E+09 | 0.00 | 0.35 |
Maximum of Months | 38675231.43 | 22575587.93 | 0.00 | 22635256.40 | 0.00 | 0.114461E+10 | 0.106491E+10 | 358.13 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 76971892.40 | 0.00 | 0.00 | 1308889.69 | 0.00 | 0.121131E+10 | 0.145020E+09 | 0.00 | 0.36 |
February | 65551269.40 | 0.00 | 0.00 | 1588420.95 | 0.00 | 0.105420E+10 | 0.184377E+09 | 0.00 | 0.36 |
March | 0.100752E+09 | 0.00 | 0.00 | 4505408.15 | 0.00 | 0.829437E+09 | 0.440233E+09 | 0.00 | 0.36 |
April | 0.117972E+09 | 0.00 | 0.00 | 4037730.26 | 0.00 | 0.697158E+09 | 0.475060E+09 | 0.00 | 0.36 |
May | 0.186744E+09 | 0.00 | 0.00 | 10668399.11 | 0.00 | 0.103018E+09 | 0.886555E+09 | 0.00 | 0.35 |
June | 0.148767E+09 | 5294587.35 | 0.00 | 19436244.18 | 588592.09 | 109341.70 | 0.474480E+09 | 0.00 | 0.35 |
July | 0.145298E+09 | 12570648.72 | 770.68 | 15787628.94 | 4128512.61 | 120836.02 | 0.361029E+09 | 115.69 | 0.35 |
August | 0.167163E+09 | 21091167.25 | 8502.54 | 16728175.38 | 1473167.74 | 397676.52 | 0.416963E+09 | 105.34 | 0.35 |
September | 0.201151E+09 | 392416.14 | 0.00 | 13755696.35 | 106700.60 | 42736363.29 | 0.641470E+09 | 0.00 | 0.35 |
October | 0.126980E+09 | 0.00 | 0.00 | 5670031.02 | 0.00 | 0.583314E+09 | 0.619990E+09 | 0.00 | 0.35 |
November | 76616906.13 | 0.00 | 0.00 | 1808899.57 | 0.00 | 0.993157E+09 | 0.274547E+09 | 0.00 | 0.36 |
December | 63290173.68 | 0.00 | 0.00 | 687964.19 | 0.00 | 0.134928E+10 | 87555323.63 | 0.00 | 0.35 |
Annual Sum or Average | 0.147726E+10 | 39348819.46 | 9273.22 | 95983487.79 | 6296973.05 | 0.686424E+10 | 0.500728E+10 | 221.03 | 0.35 |
Minimum of Months | 63290173.68 | 0.00 | 0.00 | 687964.19 | 0.00 | 109341.70 | 87555323.63 | 0.00 | 0.35 |
Maximum of Months | 0.201151E+09 | 21091167.25 | 8502.54 | 19436244.18 | 4128512.61 | 0.134928E+10 | 0.886555E+09 | 115.69 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.194945E+09 | 0.00 | 0.00 | 5610623.94 | 0.00 | 0.00 | 0.119221E+10 | 0.00 | 0.02 |
February | 0.230513E+09 | 0.00 | 0.00 | 3675214.61 | 0.00 | 0.00 | 0.947521E+09 | 0.00 | 0.02 |
March | 0.363383E+09 | 0.00 | 0.00 | 3581207.20 | 0.00 | 0.00 | 0.860913E+09 | 0.00 | 0.02 |
April | 0.641972E+09 | 0.00 | 0.00 | 1408555.62 | 0.00 | 0.00 | 0.535296E+09 | 0.00 | 0.02 |
May | 0.107090E+09 | 0.00 | 0.00 | 2729493.60 | 0.00 | 0.00 | 0.953839E+09 | 0.00 | 0.02 |
June | 0.00 | 3597154.78 | 0.00 | 3920397.84 | 0.00 | 0.00 | 0.295789E+09 | 0.00 | 0.02 |
July | 0.00 | 37937161.66 | 0.00 | 3741757.80 | 0.00 | 0.00 | 0.189765E+09 | 0.00 | 0.02 |
August | 0.00 | 32880485.28 | 0.00 | 4747008.37 | 0.00 | 0.00 | 0.308137E+09 | 0.00 | 0.02 |
September | 0.00 | 528999.69 | 0.00 | 6123639.89 | 0.00 | 0.00 | 0.595540E+09 | 0.00 | 0.02 |
October | 0.334179E+09 | 0.00 | 0.00 | 5635984.49 | 0.00 | 0.00 | 0.974985E+09 | 0.00 | 0.02 |
November | 0.238345E+09 | 0.00 | 0.00 | 4414953.46 | 0.00 | 0.00 | 0.106328E+10 | 0.00 | 0.02 |
December | 0.423046E+09 | 0.00 | 0.00 | 3501970.98 | 0.00 | 0.00 | 0.873013E+09 | 0.00 | 0.02 |
Annual Sum or Average | 0.253347E+10 | 74943801.42 | 0.00 | 49090807.79 | 0.00 | 0.00 | 0.879029E+10 | 0.00 | 0.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 1408555.62 | 0.00 | 0.00 | 0.189765E+09 | 0.00 | 0.02 |
Maximum of Months | 0.641972E+09 | 37937161.66 | 0.00 | 6123639.89 | 0.00 | 0.00 | 0.119221E+10 | 0.00 | 0.02 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.111734E+10 | 0.00 | 0.00 | 11742903.42 | 0.00 | 0.993149E+10 | 0.839904E+10 | 0.00 | 0.40 |
February | 0.104424E+10 | 0.00 | 0.00 | 10410050.55 | 0.00 | 0.106526E+11 | 0.600402E+10 | 0.00 | 0.40 |
March | 0.160131E+10 | 0.00 | 0.00 | 36926441.21 | 0.00 | 0.550417E+10 | 0.115077E+11 | 0.00 | 0.40 |
April | 0.168422E+10 | 0.00 | 0.00 | 48986549.88 | 0.00 | 0.269753E+10 | 0.131247E+11 | 0.00 | 0.40 |
May | 0.291802E+10 | 0.00 | 0.00 | 0.136999E+09 | 0.00 | 9830661.36 | 0.130359E+11 | 0.00 | 0.40 |
June | 0.205031E+10 | 71380555.93 | 0.00 | 0.201864E+09 | 8421243.85 | 0.00 | 0.646692E+10 | 0.00 | 0.40 |
July | 0.199116E+10 | 0.158025E+09 | 0.00 | 0.178668E+09 | 68500952.88 | 0.00 | 0.491398E+10 | 0.00 | 0.40 |
August | 0.240366E+10 | 0.285843E+09 | 0.00 | 0.163738E+09 | 20345507.03 | 516127.51 | 0.558772E+10 | 0.00 | 0.40 |
September | 0.291225E+10 | 4966845.06 | 349901.66 | 0.144921E+09 | 1447329.68 | 4685010.41 | 0.913408E+10 | 6142.85 | 0.40 |
October | 0.198587E+10 | 0.00 | 0.00 | 52777196.68 | 0.00 | 0.272496E+10 | 0.133578E+11 | 0.00 | 0.40 |
November | 0.123168E+10 | 0.00 | 0.00 | 19113251.50 | 0.00 | 0.750099E+10 | 0.950766E+10 | 0.00 | 0.40 |
December | 0.979993E+09 | 0.00 | 0.00 | 8803748.96 | 0.00 | 0.129971E+11 | 0.637167E+10 | 0.00 | 0.40 |
Annual Sum or Average | 0.219200E+11 | 0.520215E+09 | 349901.66 | 0.101495E+10 | 98715033.45 | 0.520239E+11 | 0.107411E+12 | 6142.85 | 0.40 |
Minimum of Months | 0.979993E+09 | 0.00 | 0.00 | 8803748.96 | 0.00 | 0.00 | 0.491398E+10 | 0.00 | 0.40 |
Maximum of Months | 0.291802E+10 | 0.285843E+09 | 349901.66 | 0.201864E+09 | 68500952.88 | 0.129971E+11 | 0.133578E+11 | 6142.85 | 0.40 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 28500419.78 | 0.00 | 0.00 | 4590899.95 | 0.00 | 0.931861E+09 | 0.469825E+09 | 0.00 | 0.36 |
February | 21821785.70 | 0.00 | 0.00 | 5188611.12 | 0.00 | 0.824226E+09 | 0.454635E+09 | 0.00 | 0.36 |
March | 30792515.61 | 0.00 | 0.00 | 8664703.16 | 0.00 | 0.683461E+09 | 0.652171E+09 | 0.00 | 0.36 |
April | 32376207.72 | 0.00 | 0.00 | 6936098.78 | 0.00 | 0.635774E+09 | 0.619293E+09 | 0.00 | 0.36 |
May | 8806876.48 | 0.00 | 0.00 | 15421049.76 | 0.00 | 79367299.49 | 0.108353E+10 | 0.00 | 0.35 |
June | 0.00 | 5883868.82 | 0.00 | 25817016.46 | 0.00 | 33667.41 | 0.617017E+09 | 0.00 | 0.35 |
July | 0.00 | 16702004.59 | 0.00 | 22289178.19 | 0.00 | 27161.98 | 0.499980E+09 | 0.00 | 0.35 |
August | 0.00 | 22575587.93 | 0.00 | 26026673.70 | 0.00 | 73567.67 | 0.575223E+09 | 0.00 | 0.35 |
September | 3152932.11 | 499175.23 | 0.00 | 21986970.42 | 0.00 | 35466788.82 | 0.838612E+09 | 0.00 | 0.35 |
October | 13230689.18 | 0.00 | 0.00 | 10809484.58 | 0.00 | 0.470601E+09 | 0.841469E+09 | 0.00 | 0.35 |
November | 24107829.58 | 0.00 | 0.00 | 5635429.22 | 0.00 | 0.741338E+09 | 0.575207E+09 | 0.00 | 0.36 |
December | 39357287.47 | 0.00 | 0.00 | 3060681.98 | 0.00 | 0.113092E+10 | 0.327649E+09 | 0.00 | 0.35 |
Annual Sum or Average | 0.202147E+09 | 45660636.57 | 0.00 | 0.156427E+09 | 0.00 | 0.553315E+10 | 0.755461E+10 | 0.00 | 0.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 3060681.98 | 0.00 | 27161.98 | 0.327649E+09 | 0.00 | 0.35 |
Maximum of Months | 39357287.47 | 22575587.93 | 0.00 | 26026673.70 | 0.00 | 0.113092E+10 | 0.108353E+10 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 75398715.34 | 0.00 | 0.00 | 1228303.61 | 0.00 | 0.116568E+10 | 0.192306E+09 | 0.00 | 0.36 |
February | 63120035.07 | 0.00 | 0.00 | 2013145.53 | 0.00 | 0.101088E+10 | 0.229701E+09 | 0.00 | 0.36 |
March | 94277643.03 | 0.00 | 0.00 | 4747178.12 | 0.00 | 0.801284E+09 | 0.474619E+09 | 0.00 | 0.36 |
April | 0.100275E+09 | 0.00 | 0.00 | 4937263.09 | 0.00 | 0.697459E+09 | 0.491556E+09 | 0.00 | 0.36 |
May | 0.170005E+09 | 0.00 | 0.00 | 12077299.75 | 0.00 | 84723714.03 | 0.920180E+09 | 0.00 | 0.35 |
June | 0.142094E+09 | 5295198.99 | 0.00 | 20814374.25 | 587980.45 | 0.00 | 0.479884E+09 | 0.00 | 0.35 |
July | 0.142216E+09 | 12571535.09 | 0.00 | 17056537.48 | 4128512.61 | 36469.98 | 0.362926E+09 | 0.00 | 0.35 |
August | 0.158514E+09 | 21099775.13 | 0.00 | 19495661.75 | 1473167.74 | 0.00 | 0.423243E+09 | 0.00 | 0.35 |
September | 0.194435E+09 | 392416.14 | 0.00 | 15231865.56 | 106700.60 | 39971636.49 | 0.649475E+09 | 0.00 | 0.35 |
October | 0.119636E+09 | 0.00 | 0.00 | 5620427.23 | 0.00 | 0.613380E+09 | 0.597316E+09 | 0.00 | 0.35 |
November | 79494551.59 | 0.00 | 0.00 | 1980914.51 | 0.00 | 0.100782E+10 | 0.256834E+09 | 0.00 | 0.36 |
December | 62398268.27 | 0.00 | 0.00 | 749580.48 | 0.00 | 0.131121E+10 | 0.126455E+09 | 0.00 | 0.35 |
Annual Sum or Average | 0.140187E+10 | 39358925.35 | 0.00 | 0.105953E+09 | 6296361.40 | 0.673244E+10 | 0.520450E+10 | 0.00 | 0.35 |
Minimum of Months | 62398268.27 | 0.00 | 0.00 | 749580.48 | 0.00 | 0.00 | 0.126455E+09 | 0.00 | 0.35 |
Maximum of Months | 0.194435E+09 | 21099775.13 | 0.00 | 20814374.25 | 4128512.61 | 0.131121E+10 | 0.920180E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.293789E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.527146E+09 | 0.00 | 0.00 | 0.62 |
February | 0.256825E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157996E+10 | 0.00 | 0.00 | 0.62 |
March | 0.291458E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.62 |
April | 0.279696E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 99818086.75 | 0.00 | 0.00 | 0.62 |
May | 0.258750E+11 | 0.00 | 0.00 | 0.00 | 1879556.27 | 0.00 | 0.00 | 0.00 | 0.62 |
June | 0.540855E+10 | 0.284235E+09 | 0.00 | 17219262.67 | 16867001.68 | 0.00 | 0.718095E+10 | 0.00 | 0.63 |
July | 0.304370E+10 | 0.292385E+09 | 0.00 | 22304468.77 | 0.107499E+09 | 0.00 | 0.824067E+10 | 0.00 | 0.63 |
August | 0.507566E+10 | 0.235106E+09 | 0.00 | 19314387.25 | 5971318.71 | 0.00 | 0.815372E+10 | 0.00 | 0.64 |
September | 0.105720E+11 | 49883990.29 | 0.00 | 14033913.99 | 1735459.58 | 0.00 | 0.696310E+10 | 0.00 | 0.63 |
October | 0.270923E+11 | 0.00 | 0.00 | 33433.15 | 0.00 | 0.889018E+09 | 0.166765E+09 | 0.00 | 0.62 |
November | 0.273492E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.474805E+09 | 0.00 | 0.00 | 0.62 |
December | 0.272499E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.370984E+10 | 0.00 | 0.00 | 0.62 |
Annual Sum or Average | 0.243843E+12 | 0.861610E+09 | 0.00 | 72905465.83 | 0.133953E+09 | 0.728058E+10 | 0.307052E+11 | 0.00 | 0.63 |
Minimum of Months | 0.304370E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.62 |
Maximum of Months | 0.293789E+11 | 0.292385E+09 | 0.00 | 22304468.77 | 0.107499E+09 | 0.370984E+10 | 0.824067E+10 | 0.00 | 0.64 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 7573530.02 | 0.00 | 0.00 | 944401.92 | 0.00 | 0.269270E+09 | 80906638.76 | 0.00 | 0.36 |
February | 5764951.14 | 0.00 | 0.00 | 979552.72 | 0.00 | 0.239485E+09 | 80238649.00 | 0.00 | 0.36 |
March | 6891016.23 | 0.00 | 0.00 | 2152134.18 | 0.00 | 0.206733E+09 | 0.127996E+09 | 0.00 | 0.36 |
April | 8268588.03 | 0.00 | 0.00 | 1555241.91 | 0.00 | 0.199654E+09 | 0.114117E+09 | 0.00 | 0.36 |
May | 4310623.33 | 0.00 | 0.00 | 3478316.07 | 0.00 | 55621403.95 | 0.233371E+09 | 0.00 | 0.35 |
June | 0.00 | 1470967.21 | 0.00 | 5583392.21 | 0.00 | 326180.45 | 0.154807E+09 | 0.00 | 0.35 |
July | 0.00 | 4175411.62 | 0.00 | 4740743.81 | 0.00 | 134239.67 | 0.125699E+09 | 89.53 | 0.35 |
August | 0.00 | 5643896.98 | 0.00 | 5461852.15 | 0.00 | 287261.59 | 0.144582E+09 | 0.00 | 0.35 |
September | 1149003.07 | 124793.81 | 0.00 | 4897433.33 | 0.00 | 17281227.39 | 0.201477E+09 | 0.00 | 0.35 |
October | 3275018.32 | 0.00 | 0.00 | 2850189.83 | 0.00 | 0.165975E+09 | 0.161927E+09 | 0.00 | 0.35 |
November | 4377073.34 | 0.00 | 0.00 | 1201183.01 | 0.00 | 0.225134E+09 | 0.105860E+09 | 0.00 | 0.36 |
December | 7715872.54 | 0.00 | 0.00 | 543442.14 | 0.00 | 0.311046E+09 | 55940953.29 | 0.00 | 0.35 |
Annual Sum or Average | 49325676.04 | 11415069.61 | 0.00 | 34387883.29 | 0.00 | 0.169095E+10 | 0.158692E+10 | 89.53 | 0.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 543442.14 | 0.00 | 134239.67 | 55940953.29 | 0.00 | 0.35 |
Maximum of Months | 8268588.03 | 5643896.98 | 0.00 | 5583392.21 | 0.00 | 0.311046E+09 | 0.233371E+09 | 89.53 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 18043583.86 | 0.00 | 0.00 | 263560.01 | 0.00 | 0.319176E+09 | 21169131.66 | 0.00 | 0.36 |
February | 15056623.60 | 0.00 | 0.00 | 337053.50 | 0.00 | 0.282206E+09 | 28830222.36 | 0.00 | 0.36 |
March | 22863610.27 | 0.00 | 0.00 | 1080279.74 | 0.00 | 0.235287E+09 | 84501558.74 | 0.00 | 0.36 |
April | 26269026.94 | 0.00 | 0.00 | 1021134.15 | 0.00 | 0.209014E+09 | 87252414.81 | 0.00 | 0.36 |
May | 45911955.49 | 0.00 | 0.00 | 2582224.21 | 0.00 | 50151046.82 | 0.198101E+09 | 0.00 | 0.35 |
June | 37052012.75 | 1323646.84 | 0.00 | 4909913.80 | 147148.02 | 43271.58 | 0.118693E+09 | 0.00 | 0.35 |
July | 36126087.89 | 3142673.41 | 203.04 | 3908428.46 | 1032128.15 | 30655.22 | 90493607.47 | 7.32 | 0.35 |
August | 41453195.57 | 5274943.78 | 0.00 | 4182833.45 | 368291.94 | 136833.60 | 0.104540E+09 | 0.00 | 0.35 |
September | 50359228.61 | 98092.05 | 0.00 | 3221713.83 | 26675.15 | 18149538.52 | 0.153048E+09 | 11.99 | 0.35 |
October | 31625153.21 | 0.00 | 0.00 | 1246714.81 | 0.00 | 0.201873E+09 | 99243577.16 | 0.00 | 0.35 |
November | 17935526.76 | 0.00 | 0.00 | 382396.07 | 0.00 | 0.283490E+09 | 34724322.38 | 0.00 | 0.36 |
December | 13865646.60 | 0.00 | 0.00 | 142235.71 | 0.00 | 0.349607E+09 | 11587618.91 | 0.00 | 0.35 |
Annual Sum or Average | 0.356562E+09 | 9839356.08 | 203.04 | 23278487.74 | 1574243.26 | 0.194916E+10 | 0.103218E+10 | 19.31 | 0.35 |
Minimum of Months | 13865646.60 | 0.00 | 0.00 | 142235.71 | 0.00 | 30655.22 | 11587618.91 | 0.00 | 0.35 |
Maximum of Months | 50359228.61 | 5274943.78 | 203.04 | 4909913.80 | 1032128.15 | 0.349607E+09 | 0.198101E+09 | 11.99 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 10124662.90 | 0.00 | 0.00 | 17521288.77 | 0.00 | 0.904732E+09 | 0.137205E+10 | 0.00 | 0.41 |
February | 7418159.13 | 0.00 | 0.00 | 13995265.24 | 0.00 | 0.100801E+10 | 0.106797E+10 | 0.00 | 0.40 |
March | 28755347.23 | 0.00 | 0.00 | 16593257.93 | 0.00 | 0.937069E+09 | 0.122614E+10 | 0.00 | 0.40 |
April | 39354720.44 | 0.00 | 0.00 | 9476756.70 | 0.00 | 0.941158E+09 | 0.108894E+10 | 0.00 | 0.40 |
May | 11713600.39 | 0.00 | 0.00 | 18131290.99 | 0.00 | 0.147761E+09 | 0.172906E+10 | 0.00 | 0.40 |
June | 0.00 | 9450213.13 | 0.00 | 25787625.67 | 0.00 | 1942749.86 | 0.100479E+10 | 0.00 | 0.40 |
July | 0.00 | 26825462.62 | 0.00 | 24308247.89 | 0.00 | 592725.86 | 0.813971E+09 | 0.00 | 0.40 |
August | 0.00 | 36259156.01 | 0.00 | 28989335.62 | 0.00 | 586756.45 | 0.936223E+09 | 0.00 | 0.40 |
September | 876691.76 | 801736.49 | 0.00 | 31358432.15 | 0.00 | 48753311.24 | 0.136327E+10 | 0.00 | 0.40 |
October | 18511820.00 | 0.00 | 0.00 | 24879591.71 | 0.00 | 0.584087E+09 | 0.151848E+10 | 0.00 | 0.40 |
November | 16989260.16 | 0.00 | 0.00 | 18368471.24 | 0.00 | 0.742649E+09 | 0.138430E+10 | 0.00 | 0.40 |
December | 28622542.19 | 0.00 | 0.00 | 11939797.34 | 0.00 | 0.131116E+10 | 0.105905E+10 | 0.00 | 0.40 |
Annual Sum or Average | 0.162367E+09 | 73336568.25 | 0.00 | 0.241349E+09 | 0.00 | 0.662849E+10 | 0.145642E+11 | 0.00 | 0.40 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 9476756.70 | 0.00 | 586756.45 | 0.813971E+09 | 0.00 | 0.40 |
Maximum of Months | 39354720.44 | 36259156.01 | 0.00 | 31358432.15 | 0.00 | 0.131116E+10 | 0.172906E+10 | 0.00 | 0.41 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.146208E+10 | 0.00 | 0.00 | 58080088.82 | 0.00 | 0.00 | 0.494309E+11 | 0.00 | 5.04 |
February | 0.156842E+10 | 0.00 | 0.00 | 51515697.12 | 0.00 | 0.00 | 0.446433E+11 | 0.00 | 5.00 |
March | 0.478941E+09 | 0.00 | 0.00 | 69918620.93 | 0.00 | 0.00 | 0.525702E+11 | 0.00 | 5.33 |
April | 0.165411E+09 | 0.00 | 0.00 | 69682336.88 | 0.00 | 0.00 | 0.520829E+11 | 0.00 | 5.42 |
May | 0.00 | 3657183.78 | 0.00 | 96747261.42 | 0.00 | 0.00 | 0.545407E+11 | 0.00 | 6.02 |
June | 0.00 | 0.560662E+09 | 0.00 | 0.106715E+09 | 0.00 | 0.00 | 0.296331E+11 | 0.00 | 6.44 |
July | 0.00 | 0.737393E+09 | 0.00 | 0.102460E+09 | 0.00 | 0.00 | 0.264726E+11 | 0.00 | 6.39 |
August | 0.00 | 0.443648E+09 | 0.00 | 0.108495E+09 | 0.00 | 0.00 | 0.302163E+11 | 0.00 | 6.43 |
September | 0.00 | 88963857.08 | 0.00 | 0.100703E+09 | 0.00 | 0.00 | 0.387005E+11 | 0.00 | 6.21 |
October | 0.862888E+09 | 0.00 | 0.00 | 76245439.95 | 0.00 | 0.00 | 0.519161E+11 | 0.00 | 5.46 |
November | 0.102081E+10 | 0.00 | 0.00 | 60763426.79 | 0.00 | 0.00 | 0.476484E+11 | 0.00 | 5.16 |
December | 0.410359E+10 | 0.00 | 0.00 | 52016305.30 | 0.00 | 0.00 | 0.471327E+11 | 0.00 | 4.89 |
Annual Sum or Average | 0.966214E+10 | 0.183432E+10 | 0.00 | 0.953342E+09 | 0.00 | 0.00 | 0.524988E+12 | 0.00 | 5.65 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 51515697.12 | 0.00 | 0.00 | 0.264726E+11 | 0.00 | 4.89 |
Maximum of Months | 0.410359E+10 | 0.737393E+09 | 0.00 | 0.108495E+09 | 0.00 | 0.00 | 0.545407E+11 | 0.00 | 6.44 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.272991E+09 | 0.00 | 0.00 | 72314996.53 | 0.00 | 0.00 | 0.559199E+11 | 0.00 | 5.56 |
February | 0.270432E+09 | 0.00 | 0.00 | 64458033.25 | 0.00 | 0.00 | 0.507214E+11 | 0.00 | 5.52 |
March | 52722327.36 | 0.00 | 0.00 | 83104544.41 | 0.00 | 0.00 | 0.583014E+11 | 0.00 | 5.86 |
April | 45273253.26 | 0.00 | 0.00 | 81784227.29 | 0.00 | 0.00 | 0.576190E+11 | 0.00 | 5.99 |
May | 0.00 | 3985458.23 | 0.00 | 0.106235E+09 | 0.00 | 0.00 | 0.591600E+11 | 0.00 | 6.55 |
June | 0.00 | 0.602566E+09 | 0.00 | 0.113909E+09 | 0.00 | 0.00 | 0.313487E+11 | 0.00 | 6.86 |
July | 0.00 | 0.795133E+09 | 0.00 | 0.109214E+09 | 0.00 | 0.00 | 0.279607E+11 | 0.00 | 6.80 |
August | 0.00 | 0.476202E+09 | 0.00 | 0.115999E+09 | 0.00 | 0.00 | 0.320166E+11 | 0.00 | 6.85 |
September | 0.00 | 95851561.46 | 0.00 | 0.108571E+09 | 0.00 | 0.00 | 0.413396E+11 | 0.00 | 6.65 |
October | 0.139410E+09 | 0.00 | 0.00 | 87781712.56 | 0.00 | 0.00 | 0.574364E+11 | 0.00 | 5.96 |
November | 0.171387E+09 | 0.00 | 0.00 | 73308383.05 | 0.00 | 0.00 | 0.534797E+11 | 0.00 | 5.69 |
December | 0.209696E+10 | 0.00 | 0.00 | 66056409.67 | 0.00 | 0.00 | 0.543804E+11 | 0.00 | 5.40 |
Annual Sum or Average | 0.304918E+10 | 0.197374E+10 | 0.00 | 0.108274E+10 | 0.00 | 0.00 | 0.579684E+12 | 0.00 | 6.14 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 64458033.25 | 0.00 | 0.00 | 0.279607E+11 | 0.00 | 5.40 |
Maximum of Months | 0.209696E+10 | 0.795133E+09 | 0.00 | 0.115999E+09 | 0.00 | 0.00 | 0.591600E+11 | 0.00 | 6.86 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.121086E+09 | 0.00 | 0.00 | 0.812106E+11 | 0.00 | 25.79 |
February | 0.00 | 0.00 | 0.00 | 0.109677E+09 | 0.00 | 0.00 | 0.739815E+11 | 0.00 | 25.70 |
March | 0.00 | 0.00 | 0.00 | 0.128319E+09 | 0.00 | 0.00 | 0.792475E+11 | 0.00 | 26.18 |
April | 0.00 | 0.00 | 0.00 | 0.120961E+09 | 0.00 | 0.00 | 0.760610E+11 | 0.00 | 26.33 |
May | 0.00 | 6439497.59 | 0.00 | 0.147349E+09 | 0.00 | 0.00 | 0.689440E+11 | 0.00 | 27.15 |
June | 0.00 | 0.961766E+09 | 0.00 | 0.147402E+09 | 0.00 | 0.00 | 0.307090E+11 | 0.00 | 27.06 |
July | 0.00 | 0.130714E+10 | 0.00 | 0.139392E+09 | 0.00 | 0.00 | 0.267901E+11 | 0.00 | 26.79 |
August | 0.00 | 0.755859E+09 | 0.00 | 0.155535E+09 | 0.00 | 0.00 | 0.332653E+11 | 0.00 | 27.43 |
September | 0.00 | 0.159473E+09 | 0.00 | 0.149505E+09 | 0.00 | 0.00 | 0.447549E+11 | 0.00 | 27.24 |
October | 0.00 | 0.00 | 0.00 | 0.133432E+09 | 0.00 | 0.00 | 0.764818E+11 | 0.00 | 26.11 |
November | 0.00 | 0.00 | 0.00 | 0.118706E+09 | 0.00 | 0.00 | 0.755269E+11 | 0.00 | 25.84 |
December | 0.00 | 0.00 | 0.00 | 0.117869E+09 | 0.00 | 0.00 | 0.820887E+11 | 0.00 | 25.15 |
Annual Sum or Average | 0.00 | 0.319068E+10 | 0.00 | 0.158923E+10 | 0.00 | 0.00 | 0.749061E+12 | 0.00 | 26.40 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.109677E+09 | 0.00 | 0.00 | 0.267901E+11 | 0.00 | 25.15 |
Maximum of Months | 0.00 | 0.130714E+10 | 0.00 | 0.155535E+09 | 0.00 | 0.00 | 0.820887E+11 | 0.00 | 27.43 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.139726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163487E+10 | 0.00 | 0.00 | 1.23 |
February | 0.117727E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245514E+10 | 0.00 | 0.00 | 1.22 |
March | 0.143570E+11 | 0.00 | 0.00 | 682794.24 | 0.00 | 0.517547E+09 | 0.341135E+09 | 0.00 | 1.23 |
April | 0.143274E+11 | 0.00 | 0.00 | 4527.46 | 0.00 | 0.298442E+09 | 23150950.50 | 0.00 | 1.23 |
May | 0.131419E+11 | 980961.34 | 0.00 | 646421.30 | 0.00 | 0.00 | 0.361808E+09 | 0.00 | 1.23 |
June | 0.308370E+10 | 0.213580E+09 | 0.00 | 13290681.61 | 269189.75 | 0.00 | 0.340547E+10 | 0.00 | 1.31 |
July | 0.238640E+10 | 0.260102E+09 | 0.00 | 12955760.91 | 2656288.09 | 0.00 | 0.338843E+10 | 0.00 | 1.30 |
August | 0.335117E+10 | 0.172095E+09 | 0.00 | 13709422.04 | 0.00 | 0.00 | 0.349790E+10 | 0.00 | 1.34 |
September | 0.638963E+10 | 35406632.03 | 0.00 | 8946227.81 | 0.00 | 0.00 | 0.270148E+10 | 0.00 | 1.28 |
October | 0.131879E+11 | 0.00 | 0.00 | 1034913.17 | 0.00 | 0.893932E+09 | 0.610523E+09 | 0.00 | 1.23 |
November | 0.133475E+11 | 0.00 | 0.00 | 25535.08 | 0.00 | 0.111358E+10 | 59714300.33 | 0.00 | 1.23 |
December | 0.123628E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.379457E+10 | 0.00 | 0.00 | 1.22 |
Annual Sum or Average | 0.121681E+12 | 0.682165E+09 | 0.00 | 51296283.62 | 2925477.84 | 0.107081E+11 | 0.143896E+11 | 0.00 | 1.25 |
Minimum of Months | 0.238640E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.22 |
Maximum of Months | 0.143570E+11 | 0.260102E+09 | 0.00 | 13709422.04 | 2656288.09 | 0.379457E+10 | 0.349790E+10 | 0.00 | 1.34 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:25:04
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.230602E+12 | 0.817018E+10 | 0.223507E+12 | 0.105024E+13 | 0.138462E+12 |
February | 0.315755E+12 | 0.774742E+10 | 0.210043E+12 | 0.979759E+12 | 0.120882E+12 |
March | 0.421469E+12 | 0.685509E+10 | 0.185348E+12 | 0.879545E+12 | 0.149702E+12 |
April | 0.472597E+12 | 0.625190E+10 | 0.168091E+12 | 0.794240E+12 | 0.126253E+12 |
May | 0.531383E+12 | 0.427169E+10 | 0.990443E+11 | 0.526714E+12 | 0.263696E+12 |
June | 0.575758E+12 | 0.183065E+10 | 0.329837E+11 | 0.224639E+12 | 0.599662E+12 |
July | 0.549912E+12 | 0.158561E+10 | 0.278461E+11 | 0.193138E+12 | 0.665626E+12 |
August | 0.512306E+12 | 0.196008E+10 | 0.388891E+11 | 0.240408E+12 | 0.615584E+12 |
September | 0.384267E+12 | 0.297055E+10 | 0.614464E+11 | 0.361827E+12 | 0.463158E+12 |
October | 0.315324E+12 | 0.621021E+10 | 0.163313E+12 | 0.824618E+12 | 0.188549E+12 |
November | 0.248887E+12 | 0.720692E+10 | 0.197046E+12 | 0.959273E+12 | 0.135499E+12 |
December | 0.198448E+12 | 0.877999E+10 | 0.238657E+12 | 0.110941E+13 | 0.132839E+12 |
Annual Sum or Average | 0.475671E+13 | 0.638403E+11 | 0.164621E+13 | 0.814382E+13 | 0.359991E+13 |
Minimum of Months | 0.198448E+12 | 0.158561E+10 | 0.278461E+11 | 0.193138E+12 | 0.120882E+12 |
Maximum of Months | 0.575758E+12 | 0.877999E+10 | 0.238657E+12 | 0.110941E+13 | 0.665626E+12 |