Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:25
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** William R Fairchild WA USA TMY3 WMO#=727885
Simulation Timestamp: 2024-07-03 12:25:19
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:19
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 10583.01 | 932.81 | 932.81 |
Net Site Energy | 10583.01 | 932.81 | 932.81 |
Total Source Energy | 20921.13 | 1844.04 | 1844.04 |
Net Source Energy | 20921.13 | 1844.04 | 1844.04 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1466.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 215.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 782.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 193.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1658.18 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 813.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 495.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 74.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 146.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 94.78 | 2791.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | 61.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 4536.32 | 6046.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 1466.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 215.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 782.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 193.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 872.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 14.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 8.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 21.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 789.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 2.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 495.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 74.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 146.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 94.78 | 2791.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5742.51 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.69 | |
Refrigeration | General | 7.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 20.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 34.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1466.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 215.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 782.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 193.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 1658.18 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 813.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 495.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 74.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 146.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 94.78 | 2791.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | Unassigned | 61.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 85.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 77.60 | 375.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 236.25 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 399.84 | 532.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 85.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 77.60 | 375.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 236.25 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 399.84 | 532.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 4536.316 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 4536.316 | 100.00 |
Total On-Site and Utility Electric Sources | 4536.316 | 100.00 |
Total Electricity End Uses | 4536.316 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 1.13 | 0.04 |
Air to Air Heat Recovery for Heating | 2929.91 | 99.96 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 2931.04 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9857.19 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9857.19 | 100.00 |
Total Water End Uses | 9857.19 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 20.83 |
Time Setpoint Not Met During Occupied Cooling | 27.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 7067.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5C
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_PORTANGELES
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER1 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| FLR_3_DOAS COOLING COIL | VAV WITH REHEAT COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH LAUNDRY G WATER HEATER | SWH BOOSTER E WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |CoilReportMonthly
| FLR_3_DOAS HEATING COIL | VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | FLR_3_DOAS COOLING COIL | VAV WITH REHEAT COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |FanReportMonthly
| FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL_FANCOILFAN | ROOM_2_FLR_3 FAN COIL_FANCOILFAN | ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | ROOM_5_FLR_3 FAN COIL_FANCOILFAN | ROOM_6_FLR_3 FAN COIL_FANCOILFAN | ROOM_1_FLR_6 FAN COIL_FANCOILFAN | ROOM_2_FLR_6 FAN COIL_FANCOILFAN | ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| FLR_3_DOAS | VAV WITH REHEAT |AirLoopSystemComponentLoadsMonthly
| FLR_3_DOAS | VAV WITH REHEAT |AirLoopSystemComponentEnergyUseMonthly
| FLR_3_DOAS | VAV WITH REHEAT |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:19
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:25 |
RunPeriod | RUNPERIOD 1 |
Weather File | William R Fairchild WA USA TMY3 WMO#=727885 |
Latitude [deg] | 48.12 |
Longitude [deg] | -123.5 |
Elevation [m] | 91.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 8.8143 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.26 | 23.26 | 11.3140 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 11.3140 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 4.6285 | 61.93 | 5.3800 |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 5.7199 | 46.45 | 2.6900 |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 4.6285 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.50 | 65.50 | 10.0104 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.08 | 85.08 | 10.7639 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 8.2882 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 8.2882 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 7.1042 | 18.58 | 0.0000 |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.74 | 6.74 | 8.2882 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 10.0104 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 10.0104 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.37 | 26.37 | 11.4097 | 4.65 | 2934.4875 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.20 | 28.20 | 7.1042 | 18.58 | 0.0000 |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 8.5566 | 7.07 | 41.0709 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 8.5566 | 7.07 | 41.0709 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 1978.83 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 8.8143 | 18.58 | 5.3800 | |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 1.00 | RETAIL_1_FLR_1 | GENERAL | RETAIL_1_FLR_1 | 11.3140 | 6.19 | 10.7600 | |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 1.00 | RETAIL_2_FLR_1 | GENERAL | RETAIL_2_FLR_1 | 11.3140 | 6.19 | 10.7600 | |
MECH_FLR_1 | 164.24 | Yes | Yes | 1.00 | MECH_FLR_1 | GENERAL | MECH_FLR_1 | 4.6285 | 61.93 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 1.00 | STORAGE_FLR_1 | GENERAL | STORAGE_FLR_1 | 5.7199 | 46.45 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 1.00 | LAUNDRY_FLR_1 | GENERAL | LAUNDRY_FLR_1 | 4.6285 | 9.29 | 597.5300 | |
CAFE_FLR_1 | 188.86 | Yes | Yes | 1.00 | CAFE_FLR_1 | GENERAL | CAFE_FLR_1 | 10.0104 | 1.33 | 5.3800 | |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 1.00 | LOBBY_FLR_1 | GENERAL | LOBBY_FLR_1 | 10.7639 | 3.10 | 8.0700 | |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_1_FLR_3 | GENERAL | ROOM_1_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_2_FLR_3 | GENERAL | ROOM_2_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 76.00 | ROOM_3_MULT19_FLR_3 | GENERAL | ROOM_3_MULT19_FLR_3 | 8.2882 | 16.35 | 10.5200 | |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 76.00 | ROOM_4_MULT19_FLR_3 | GENERAL | ROOM_4_MULT19_FLR_3 | 8.2882 | 16.35 | 10.5200 | |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_5_FLR_3 | GENERAL | ROOM_5_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_6_FLR_3 | GENERAL | ROOM_6_FLR_3 | 8.2882 | 26.01 | 6.7500 | |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 4.00 | CORRIDOR_FLR_3 | GENERAL | CORRIDOR_FLR_3 | 7.1042 | 18.58 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_1_FLR_6 | GENERAL | ROOM_1_FLR_6 | 8.2882 | 26.01 | 6.7500 | |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_2_FLR_6 | GENERAL | ROOM_2_FLR_6 | 8.2882 | 26.01 | 6.7500 | |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 9.00 | ROOM_3_MULT9_FLR_6 | GENERAL | ROOM_3_MULT9_FLR_6 | 8.2882 | 16.35 | 10.5200 | |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1.00 | BANQUET_FLR_6 | GENERAL | BANQUET_FLR_6 | 10.0104 | 1.33 | 67.8200 | |
DINING_FLR_6 | 331.66 | Yes | Yes | 1.00 | DINING_FLR_6 | GENERAL | DINING_FLR_6 | 10.0104 | 1.33 | 67.8200 | |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 1.00 | KITCHEN_FLR_6 | GENERAL | KITCHEN_FLR_6 | 11.4097 | 4.65 | 2934.4875 | |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1.00 | CORRIDOR_FLR_6 | GENERAL | CORRIDOR_FLR_6 | 7.1042 | 18.58 | 0.0000 | |
Total | 11345.29 | 8.5566 | 3.54 | 41.0709 | |||||||
Conditioned Total | 11345.29 | 8.5566 | 3.54 | 41.0709 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 11345.29 | 11345.29 | 0.00 | 0.00 | 4.6520 | 8.82 | 37.1989 |
Total | 11345.29 | 11345.29 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:19
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 22-JUL-18:19 | 26-JAN-18:40 | - | - | - | - | - | - | - | - | - | - | 27-APR-20:10 |
Heating | 0.00 | 190758.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 112941.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 51055.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 74651.16 | 104248.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 28107.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 25912.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 4801.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 4363.65 | 249929.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 2382.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 314153.84 | 544936.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 190758.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 112941.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 51055.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 44668.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 29272.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 988.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 26968.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 150.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 25912.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 4801.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 4363.65 | 249929.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 216.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 1088.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1077.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:19
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1589.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 683.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2476.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 612.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5251.45 | 1939.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2577.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1568.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 235.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 463.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 300.18 | 3026.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 196.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 14366.51 | 6554.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 140.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 60.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 218.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 54.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 462.88 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 227.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 138.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 20.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 40.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 26.46 | 266.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1266.30 | 577.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 140.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 60.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 218.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 54.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 462.88 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 227.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 138.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 20.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 40.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 26.46 | 266.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1266.30 | 577.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:19
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
BASEMENT VAV BOX COMPONENT | 2.49 | 0.604888 | 0.515000 | 1.28 | 1.00 | 0.500000 | 0.000630 | 0.000072 | 1.28 | 16.70 | 0.008000 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.448222 | 0.114025 | 0.515000 | 0.230834 | 0.515000 | 0.500000 | 0.003341 | 0.000029 | 0.230834 | 16.70 | 0.008000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.229436 | 0.257953 | 0.515000 | 0.118159 | 0.687875 | 0.500000 | 0.001477 | 0.000011 | 0.118159 | 16.70 | 0.008000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.168015 | 0.744895 | 0.515000 | 0.086528 | 1.00 | 0.500000 | 0.000511 | 0.000015 | 0.086528 | 16.70 | 0.008000 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.099259 | 0.727456 | 0.515000 | 0.051118 | 1.00 | 0.500000 | 0.000524 | 0.000010 | 0.051118 | 16.70 | 0.008000 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 3.27 | 0.018164 | 0.515000 | 1.69 | 0.515000 | 0.500000 | 0.020975 | 0.000091 | 1.69 | 16.70 | 0.008000 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.78 | 0.080624 | 0.515000 | 0.919270 | 0.515000 | 0.500000 | 0.004726 | 0.000089 | 0.919270 | 16.70 | 0.008000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 5.13 | 0.194152 | 0.515000 | 2.64 | 0.517740 | 0.500000 | 0.001962 | 0.000228 | 2.64 | 16.70 | 0.008000 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.59 | 0.744945 | 0.515000 | 0.820539 | 1.00 | 0.500000 | 0.000511 | 0.000101 | 0.820539 | 16.70 | 0.008000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.11 | 0.119768 | 0.515000 | 1.09 | 0.515000 | 0.500000 | 0.003181 | 0.000092 | 1.09 | 16.70 | 0.008000 |
DINING_FLR_6 VAV BOX COMPONENT | 2.21 | 0.114354 | 0.515000 | 1.14 | 0.515000 | 0.500000 | 0.003332 | 0.000095 | 1.14 | 16.70 | 0.008000 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.27 | 0.062357 | 0.515000 | 1.17 | 0.515000 | 0.500000 | 0.010990 | 0.000061 | 1.17 | 16.70 | 0.008000 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 0.817359 | 0.384212 | 0.515000 | 0.420940 | 1.00 | 0.500000 | 0.000992 | 0.000065 | 0.420940 | 16.70 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
BASEMENT VAV BOX REHEAT COIL | 8182.48 | 0.000072 | 172.60 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 3290.41 | 0.000029 | 75.44 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1307.26 | 0.000011 | 28.95 |
MECH_FLR_1 VAV BOX REHEAT COIL | 1663.35 | 0.000015 | 40.39 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 1118.32 | 0.000010 | 28.05 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 10377.69 | 0.000091 | 218.43 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 10150.21 | 0.000089 | 224.70 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 26107.80 | 0.000228 | 570.91 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | 4459.56 | 0.000039 | 127.43 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | 4464.17 | 0.000039 | 127.56 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 25697.99 | 0.000225 | 734.28 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 25797.55 | 0.000226 | 737.12 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | 4449.81 | 0.000039 | 127.15 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | 4454.42 | 0.000039 | 127.28 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 11498.45 | 0.000101 | 262.92 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | 1401.50 | 0.000012 | 40.04 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | 1402.63 | 0.000012 | 40.08 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 6755.46 | 0.000059 | 193.02 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 10519.18 | 0.000092 | 229.56 |
DINING_FLR_6 VAV BOX REHEAT COIL | 10886.97 | 0.000095 | 237.30 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 6988.14 | 0.000061 | 146.82 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 7377.31 | 0.000065 | 175.58 |
FLR_3_DOAS HEATING COIL | 15471.26 | 0.000135 | 263.98 |
VAV WITH REHEAT HEATING COIL | 169771.45 | 0.001485 | 2896.78 |
Design Size Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 0.061735 |
ROOM_2_FLR_3 DIRECT AIR | 0.061728 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 0.837072 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 0.837300 |
ROOM_5_FLR_3 DIRECT AIR | 0.061735 |
ROOM_6_FLR_3 DIRECT AIR | 0.061728 |
ROOM_1_FLR_6 DIRECT AIR | 0.015434 |
ROOM_2_FLR_6 DIRECT AIR | 0.015432 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 0.099154 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Hot Water Flow [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 1.17 | 0.000039 | 0.000369 |
ROOM_2_FLR_3 FAN COIL | 1.05 | 0.000039 | 0.000331 |
ROOM_3_MULT19_FLR_3 FAN COIL | 8.40 | 0.000225 | 0.002597 |
ROOM_4_MULT19_FLR_3 FAN COIL | 5.34 | 0.000226 | 0.001774 |
ROOM_5_FLR_3 FAN COIL | 1.07 | 0.000039 | 0.000338 |
ROOM_6_FLR_3 FAN COIL | 0.968492 | 0.000039 | 0.000306 |
ROOM_1_FLR_6 FAN COIL | 0.308770 | 0.000012 | 0.000097 |
ROOM_2_FLR_6 FAN COIL | 0.274515 | 0.000012 | 0.000086 |
ROOM_3_MULT9_FLR_6 FAN COIL | 1.71 | 0.000059 | 0.000544 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COIL_FANCOILFAN | 1.17 |
ROOM_2_FLR_3 FAN COIL_FANCOILFAN | 1.05 |
ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | 8.40 |
ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | 5.34 |
ROOM_5_FLR_3 FAN COIL_FANCOILFAN | 1.07 |
ROOM_6_FLR_3 FAN COIL_FANCOILFAN | 0.968492 |
ROOM_1_FLR_6 FAN COIL_FANCOILFAN | 0.308770 |
ROOM_2_FLR_6 FAN COIL_FANCOILFAN | 0.274515 |
ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN | 1.71 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Coil Load [W] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008562 | 12.80 | 0.008500 | 0.000369 | 1.17 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008570 | 12.80 | 0.008500 | 0.000331 | 1.05 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008499 | 12.80 | 0.008499 | 0.002597 | 8.40 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008763 | 12.80 | 0.008500 | 0.001774 | 5.34 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008568 | 12.80 | 0.008500 | 0.000338 | 1.07 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008575 | 12.80 | 0.008500 | 0.000306 | 0.968492 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008559 | 12.80 | 0.008500 | 0.000097 | 0.308770 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008567 | 12.80 | 0.008500 | 0.000086 | 0.274515 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008597 | 12.80 | 0.008500 | 0.000544 | 1.71 | |
FLR_3_DOAS COOLING COIL | 26.40 | 6.70 | 0.008407 | 11.92 | 0.008407 | 0.001033 | 2.05 | 36112.10 |
VAV WITH REHEAT COOLING COIL | 25.24 | 6.70 | 0.008990 | 10.96 | 0.008500 | 0.012136 | 22.51 | 424344.37 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
VAV WITH REHEAT | 11.66 | 11.66 | 22.63 | 11.66 | 22.51 | 22.51 | 0.300000 | 0.517798 | 22.51 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
VAV WITH REHEAT_OA_CONTROLLER | 22.51 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
FLR_3_DOAS OA HEAT RECOVERY | 2.05 |
VAV WITH REHEAT OA HEAT RECOVERY | 11.66 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS FAN | 2.05 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.001033 | 0.000461 |
FLR_3_DOAS_HEATC_CONTROLLER | 0.000135 | |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.012136 | 0.000039 |
VAV WITH REHEAT_HEATC_CONTROLLER | 0.001485 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT FAN | 22.51 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.019611 | 3201.84 | |
HEATSYS1 PUMP | 0.003268 | 984.29 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.003268 | 0.392203 |
COOLSYS1 | 0.019611 | 2.35 |
SWHSYS1 | 0.000375 | 0.045004 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 373593.38 | 373593.38 | 0.003268 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.019611 | 2216.74 |
SWHSYS1 PUMP | 0.000375 | 47.91 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.019611 | 685693.67 | 686317.06 | 78.24 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000375 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:19
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:19
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:19
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 9.30 | 6.70 | 4.10 | 4.20 | 4.20 | 5.90 | 9.00 | 10.00 | 13.30 | 15.00 | 15.70 | 13.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | William R Fairchild WA USA TMY3 WMO#=727885 | 48.12 | -123.50 | -8.00 | 91.00 | 100237 | 1.1914 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 9.23 | 11.60 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.58 | 23.26 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.72 | 65.50 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.80 | 85.08 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.70 | 6.74 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.96 | 26.37 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.27 | 28.20 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 8.814 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 14.194 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 11.314 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 22.074 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 11.314 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 22.074 | No |
4 | MECH_FLR_1 | 164.24 | 2.7 | 61.932 | 1.615E-002 | 4.628 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 10.008 | No |
5 | STORAGE_FLR_1 | 94.76 | 2.0 | 46.451 | 2.153E-002 | 5.720 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 8.410 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 4.628 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 602.158 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 10.010 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 15.390 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 10.764 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.834 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 8.288 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 18.808 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 8.288 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 18.808 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 21.0 | 18.581 | 5.382E-002 | 7.104 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.104 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 8.288 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 18.808 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 10.010 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 77.830 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 10.010 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 77.830 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 11.410 | 515.227 | 2419.260 | 0.000 | 0.000 | 0.000 | 2945.897 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 22.2 | 18.581 | 5.382E-002 | 7.104 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.104 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | STORAGE_FLR_1 PEOPLE | BLDG_OCC_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.0 | 2.153E-002 | 46.451 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | CORRIDOR_FLR_3 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 21.0 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 21 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
21 | CORRIDOR_FLR_6 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 22.2 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
22 | MECH_FLR_1 PEOPLE | BLDG_OCC_SCH | MECH_FLR_1 | 164.24 | 2.7 | 2.7 | 1.615E-002 | 61.932 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 3 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_BASEMENT | BASEMENT | 1978.83 | 106.5 | 17441.963 | 8.814 | 163.776 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 17441.963 |
2 | RETAIL_1_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_1_FLR_1 | 67.07 | 10.8 | 758.849 | 11.314 | 70.076 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 758.849 |
3 | RETAIL_2_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_2_FLR_1 | 77.67 | 12.5 | 878.750 | 11.314 | 70.076 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 878.750 |
4 | MECH_FLR_1_LIGHTS | LTG_SCH_MECHANIC | MECH_FLR_1 | 164.24 | 2.7 | 760.196 | 4.628 | 286.650 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 760.196 |
5 | STORAGE_FLR_1_LIGHTS | LTG_SCH_STORAGE | STORAGE_FLR_1 | 94.76 | 2.0 | 542.017 | 5.720 | 265.695 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 542.017 |
6 | LAUNDRY_FLR_1_LIGHTS | LTG_SCH_LAUNDRY | LAUNDRY_FLR_1 | 78.04 | 8.4 | 361.204 | 4.628 | 43.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 361.204 |
7 | CAFE_FLR_1_LIGHTS | LTG_SCH_DINING | CAFE_FLR_1 | 188.86 | 142.3 | 1890.589 | 10.010 | 13.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1890.589 |
8 | LOBBY_FLR_1_LIGHTS | LTG_SCH_LOBBY | LOBBY_FLR_1 | 1308.19 | 422.4 | 14081.185 | 10.764 | 33.333 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14081.185 |
9 | ROOM_1_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_3 | 39.02 | 1.5 | 323.422 | 8.288 | 215.615 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.422 |
10 | ROOM_2_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_3 | 39.02 | 1.5 | 323.384 | 8.288 | 215.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.384 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 203.259 | 8.288 | 135.506 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 203.259 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 203.314 | 8.288 | 135.543 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 203.314 |
13 | ROOM_5_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_5_FLR_3 | 39.02 | 1.5 | 323.422 | 8.288 | 215.615 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.422 |
14 | ROOM_6_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_6_FLR_3 | 39.02 | 1.5 | 323.384 | 8.288 | 215.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.384 |
15 | CORRIDOR_FLR_3_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2766.397 | 7.104 | 132.003 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2766.397 |
16 | ROOM_1_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_6 | 39.02 | 1.5 | 323.422 | 8.288 | 215.615 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.422 |
17 | ROOM_2_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_6 | 39.02 | 1.5 | 323.384 | 8.288 | 215.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.384 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 203.314 | 8.288 | 135.543 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 203.314 |
19 | BANQUET_FLR_6_LIGHTS | LTG_SCH_DINING | BANQUET_FLR_6 | 331.66 | 249.9 | 3320.034 | 10.010 | 13.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3320.034 |
20 | DINING_FLR_6_LIGHTS | LTG_SCH_DINING | DINING_FLR_6 | 331.66 | 249.9 | 3320.034 | 10.010 | 13.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3320.034 |
21 | KITCHEN_FLR_6_LIGHTS | LTG_SCH_KITCHEN | KITCHEN_FLR_6 | 103.30 | 22.2 | 1178.676 | 11.410 | 53.003 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1178.676 |
22 | CORRIDOR_FLR_6_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_6 | 412.12 | 22.2 | 2927.804 | 7.104 | 132.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2927.804 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 2.7 | 883.628 | 5.380 | 333.193 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 254.902 | 2.690 | 124.952 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 457.500 | 4.429 | 20.573 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 457.500 | 457.500 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 285.000 | 2.759 | 12.816 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 285.000 | 285.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 2.390 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
6 | RES_ROOF | 19 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
7 | NONRES_EXT_WALL_GRD | 21 | 3 | 9 | 0.167 | 0.7214 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | NONRES_EXT_WALL_MID | 22 | 3 | 9 | 0.167 | 0.9169 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | NONRES_EXT_WALL_TOP | 23 | 3 | 9 | 0.167 | 0.9299 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | RES_EXT_WALL_MID | 25 | 3 | 9 | 0.167 | 0.8441 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | RES_EXT_WALL_TOP | 26 | 3 | 9 | 0.167 | 0.8569 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | NONRES_FLOOR | 30 | 3 | 7 | 0.167 | 0.2277 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
13 | NONRES_FLOOR_CEILING | 33 | 3 | 7 | 0.167 | 0.2277 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
14 | BASEMENT_FLOOR | 36 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
15 | BASEMENT_WALL_NORTH_CFACTOR | 39 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | BASEMENT_WALL_EAST_CFACTOR | 40 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | BASEMENT_WALL_SOUTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
18 | BASEMENT_WALL_WEST_CFACTOR | 42 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4184 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
10 | RES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
11 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
12 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.219 |
14 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9233 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9080 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | RES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.017 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
25 | RES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9996 |
26 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
27 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.131 |
28 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
29 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
30 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
31 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
32 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.131 |
33 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
34 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
35 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
39 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
40 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
41 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
42 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 2.3900722 | 2.3900722 | 2.3900722 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
21 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
22 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
23 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
24 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
25 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
26 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
27 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
28 | 9 | -0.17110984E-14 | 0.24103936E-16 | -0.15943139E-09 | 0.44685538E-16 |
29 | 8 | 0.23237837E-07 | 0.98082464E-13 | 0.39196772E-03 | -0.26422217E-09 |
30 | 7 | -0.12664044E-01 | 0.50206963E-08 | -0.23693971E-01 | 0.14399480E-03 |
31 | 6 | 0.41682950 | 0.17394333E-05 | 0.48185553 | -0.48830741E-02 |
32 | 5 | -5.3025782 | 0.64717486E-04 | -4.5162048 | 0.64572787E-01 |
33 | 4 | 33.498276 | 0.52771084E-03 | 21.733161 | -0.42870077 |
34 | 3 | -112.28016 | 0.11468200E-02 | -56.202879 | 1.5304215 |
35 | 2 | 198.17562 | 0.64344368E-03 | 78.405936 | -2.9173034 |
36 | 1 | -171.55028 | 0.68528185E-04 | -55.409506 | 2.7523484 |
37 | 0 | 57.057407 | 0.38903588E-06 | 15.533392 | |
38 | 9 | -0.29206544E-14 | 0.31488305E-16 | -0.15031727E-09 | 0.48064473E-16 |
39 | 8 | 0.21958778E-07 | 0.12356532E-12 | 0.37867817E-03 | -0.24967887E-09 |
40 | 7 | -0.12267989E-01 | 0.64094198E-08 | -0.23123879E-01 | 0.13949151E-03 |
41 | 6 | 0.40606866 | 0.22324768E-05 | 0.47270315 | -0.47562292E-02 |
42 | 5 | -5.1975737 | 0.83445227E-04 | -4.4459647 | 0.63270770E-01 |
43 | 4 | 33.033866 | 0.68326082E-03 | 21.458733 | -0.42253461 |
44 | 3 | -111.29222 | 0.14903991E-02 | -55.660391 | 1.5161481 |
45 | 2 | 197.19665 | 0.83899866E-03 | 77.908180 | -2.9017570 |
46 | 1 | -171.18874 | 0.89630080E-04 | -55.264364 | 2.7460119 |
47 | 0 | 57.057407 | 0.51068186E-06 | 15.557036 | |
48 | 9 | -0.29497736E-14 | 0.32939851E-16 | -0.14970570E-09 | 0.45584202E-16 |
49 | 8 | 0.21872815E-07 | 0.12523736E-12 | 0.37777579E-03 | -0.24870145E-09 |
50 | 7 | -0.12241065E-01 | 0.65023057E-08 | -0.23085114E-01 | 0.13918537E-03 |
51 | 6 | 0.40533708 | 0.22656711E-05 | 0.47208016 | -0.47476058E-02 |
52 | 5 | -5.1904345 | 0.84713026E-04 | -4.4411801 | 0.63182247E-01 |
53 | 4 | 33.002288 | 0.69384191E-03 | 21.440032 | -0.42211534 |
54 | 3 | -111.22504 | 0.15138688E-02 | -55.623419 | 1.5151774 |
55 | 2 | 197.13007 | 0.85240592E-03 | 77.874271 | -2.9006996 |
56 | 1 | -171.16415 | 0.91081681E-04 | -55.254501 | 2.7455809 |
57 | 0 | 57.057407 | 0.51907125E-06 | 15.558664 | |
58 | 9 | -0.24257523E-14 | 0.33690592E-16 | -0.15372093E-09 | 0.39666009E-16 |
59 | 8 | 0.22436951E-07 | 0.11417013E-12 | 0.38367618E-03 | -0.25511586E-09 |
60 | 7 | -0.12417040E-01 | 0.58916776E-08 | -0.23338459E-01 | 0.14118628E-03 |
61 | 6 | 0.41011853 | 0.20479623E-05 | 0.47615013 | -0.48039676E-02 |
62 | 5 | -5.2370942 | 0.76414309E-04 | -4.4724296 | 0.63760808E-01 |
63 | 4 | 33.208666 | 0.62469949E-03 | 21.562156 | -0.42485549 |
64 | 3 | -111.66410 | 0.13607335E-02 | -55.864850 | 1.5215209 |
65 | 2 | 197.56520 | 0.76503996E-03 | 78.095736 | -2.9076095 |
66 | 1 | -171.32486 | 0.81633884E-04 | -55.318971 | 2.7483976 |
67 | 0 | 57.057407 | 0.46449959E-06 | 15.548073 | |
68 | 9 | -0.24053431E-14 | 0.30582108E-16 | -0.15312349E-09 | 0.40258954E-16 |
69 | 8 | 0.22353057E-07 | 0.11582316E-12 | 0.38280191E-03 | -0.25416195E-09 |
70 | 7 | -0.12390977E-01 | 0.59826426E-08 | -0.23300939E-01 | 0.14088992E-03 |
71 | 6 | 0.40941037 | 0.20803184E-05 | 0.47554760 | -0.47956200E-02 |
72 | 5 | -5.2301838 | 0.77645268E-04 | -4.4678046 | 0.63675121E-01 |
73 | 4 | 33.178102 | 0.63493787E-03 | 21.544084 | -0.42444968 |
74 | 3 | -111.59908 | 0.13833754E-02 | -55.829123 | 1.5205815 |
75 | 2 | 197.50076 | 0.77794062E-03 | 78.062960 | -2.9065863 |
76 | 1 | -171.30107 | 0.83027327E-04 | -55.309421 | 2.7479805 |
77 | 0 | 57.057407 | 0.47253235E-06 | 15.549635 | |
78 | 7 | -0.14139450E-14 | -0.18802902E-16 | -0.22311785E-13 | 0.54375338E-15 |
79 | 6 | 0.16999971E-10 | 0.27590984E-11 | 0.52267399E-09 | -0.18616555E-10 |
80 | 5 | -0.63950587E-07 | 0.13451749E-07 | -0.21905428E-05 | 0.17144787E-06 |
81 | 4 | 0.72477507E-04 | 0.50724086E-05 | 0.17668371E-02 | -0.28223350E-03 |
82 | 3 | -0.10573811E-01 | 0.17927531E-03 | -0.21549182 | 0.43318087E-01 |
83 | 2 | 0.15010112 | 0.77388015E-03 | 2.8998331 | -0.61891034 |
84 | 1 | -0.37982851 | 0.49528818E-03 | -7.1368477 | 1.5694772 |
85 | 0 | 0.24168561 | 0.34021171E-05 | 4.4521969 | |
86 | 7 | -0.22311785E-13 | -0.18802902E-16 | -0.14139450E-14 | 0.54375338E-15 |
87 | 6 | 0.52267399E-09 | 0.27590984E-11 | 0.16999971E-10 | -0.18616555E-10 |
88 | 5 | -0.21905428E-05 | 0.13451749E-07 | -0.63950587E-07 | 0.17144787E-06 |
89 | 4 | 0.17668371E-02 | 0.50724086E-05 | 0.72477507E-04 | -0.28223350E-03 |
90 | 3 | -0.21549182 | 0.17927531E-03 | -0.10573811E-01 | 0.43318087E-01 |
91 | 2 | 2.8998331 | 0.77388015E-03 | 0.15010112 | -0.61891034 |
92 | 1 | -7.1368477 | 0.49528818E-03 | -0.37982851 | 1.5694772 |
93 | 0 | 4.4521969 | 0.34021171E-05 | 0.24168561 | |
94 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
95 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
96 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
97 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
98 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
99 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
100 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
101 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
102 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
103 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
104 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
105 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
106 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
107 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
108 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
109 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
110 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
111 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
112 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
113 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
114 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
115 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
116 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
117 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
118 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
119 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
120 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
121 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
122 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
123 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
124 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
125 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
126 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
127 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
128 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
129 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
130 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
131 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
132 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
133 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.38_SHGC_0.38 | 37 | 1 | VerySmooth | 2.159 | 2.159 | 1.000 | 0.381 | ||
2 | RESWINDOW_U_0.38_SHGC_0.38 | 38 | 1 | VerySmooth | 2.159 | 2.159 | 1.000 | 0.381 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 3.45900E-002 | 0.29373 | 0.49855 | 0.49855 | 0.41800 | 0.13582 | 0.17513 | 0.00000 | 0.84000 | 0.84000 | 0.11893 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 3.45900E-002 | 0.29373 | 0.49855 | 0.49855 | 0.41800 | 0.13582 | 0.17513 | 0.00000 | 0.84000 | 0.84000 | 0.11893 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | CAFE_FLR_1 | 1 | 0 |
2 | LOBBY_FLR_1 | 1 | 0 |
3 | BANQUET_FLR_6 | 1 | 0 |
4 | DINING_FLR_6 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | CAFE_FLR_1 | 0 | |
2 | LOBBY_FLR_1 | 0 | |
3 | BANQUET_FLR_6 | 0 | |
4 | DINING_FLR_6 | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH LAUNDRY G WATER HEATER | 1.1356 | 163316.0 | 11.511 | 0.4388 |
2 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.219 | 1.1187 |
3 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 2.2712 | 175842.6 | 5.775 | 0.3748 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 1.764E-002 | 2.631E-004 | 1.298E-004 | 0.239 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.811E-003 | 8.769E-005 | 2.388E-004 | 7.967E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 2.7 | 1.610E-002 | 9.800E-005 | 2.563E-004 | 8.904E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 9.287E-003 | 9.800E-005 | 2.127E-004 | 8.904E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 2.198E-002 | 2.816E-004 | 2.506E-004 | 0.256 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 3.900E-002 | 2.065E-004 | 1.137E-004 | 0.188 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 0.111 | 8.519E-005 | 1.629E-004 | 7.740E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 2.563E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 2.563E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 2.857E-003 | 1.165E-004 | 2.563E-004 | 0.138 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 2.858E-003 | 1.165E-004 | 2.563E-004 | 0.138 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 2.563E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 2.563E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 1.238E-002 | 3.180E-005 | 2.563E-004 | 3.755E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 1.297E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.024E-002 | 2.624E-004 | 1.297E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 5.239E-003 | 2.136E-004 | 1.165E-004 | 0.252 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 2.500E-002 | 7.539E-005 | 5.825E-005 | 8.904E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 2.500E-002 | 7.539E-005 | 5.825E-005 | 8.904E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 2.238E-002 | 2.167E-004 | 1.174E-004 | 0.256 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 2.191E-002 | 5.316E-005 | 4.403E-005 | 6.278E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1603 |
2 | Clear Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 9.1706E-002 |
3 | Clear Turbid Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1831 |
4 | Clear Turbid Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 0.1067 |
5 | Intermediate Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1066 |
6 | Intermediate Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 4.3266E-002 |
7 | Overcast Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 4.3971E-002 |
8 | Overcast Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 1.4607E-002 |
9 | Clear Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1825 |
10 | Clear Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 0.1094 |
11 | Clear Turbid Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.2092 |
12 | Clear Turbid Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 0.1269 |
13 | Intermediate Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1179 |
14 | Intermediate Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 5.3891E-002 |
15 | Overcast Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 4.9373E-002 |
16 | Overcast Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 1.9973E-002 |
17 | Clear Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 4.0209E-002 |
18 | Clear Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 2.3231E-002 |
19 | Clear Turbid Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 3.0980E-002 |
20 | Clear Turbid Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.7593E-002 |
21 | Intermediate Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.9478E-002 |
22 | Intermediate Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.1762E-002 |
23 | Overcast Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 4.3283E-002 |
24 | Overcast Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.5348E-002 |
25 | Clear Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 4.0209E-002 |
26 | Clear Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 2.3231E-002 |
27 | Clear Turbid Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 3.0980E-002 |
28 | Clear Turbid Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.7593E-002 |
29 | Intermediate Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.9478E-002 |
30 | Intermediate Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.1762E-002 |
31 | Overcast Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 4.3283E-002 |
32 | Overcast Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.5348E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 33944.50175 | 33944.50175 | 2.49281 | 2.49281 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 23.30600 | 8.40224E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
2 | BASEMENT | Heating | 1476.51611 | 1476.51611 | 6.39676E-002 | 0.85446 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -4.30000 | 2.65759E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
3 | RETAIL_1_FLR_1 | Cooling | 6102.92983 | 6102.92983 | 0.44822 | 0.44822 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 26.17250 | 8.40672E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 2085.24712 | 2085.24712 | 9.03383E-002 | 9.03383E-002 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | -4.30000 | 2.65759E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 3123.87978 | 3123.87978 | 0.22944 | 0.22944 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | 26.12700 | 8.40665E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 690.37355 | 690.37355 | 2.99090E-002 | 9.17347E-002 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -4.30000 | 2.65759E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 2288.09365 | 2288.09365 | 0.16801 | 0.16801 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 26.21800 | 8.40679E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 1211.68769 | 1211.68769 | 5.24938E-002 | 5.24938E-002 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -4.30000 | 2.65759E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 1351.74054 | 1351.74054 | 9.92591E-002 | 9.92591E-002 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 26.40000 | 8.40708E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 851.45706 | 851.45706 | 3.68876E-002 | 5.77652E-002 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -4.30000 | 2.65759E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 44579.66296 | 44579.66296 | 3.27378 | 3.27378 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 26.40000 | 8.40708E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 1577.85197 | 1577.85197 | 6.83565E-002 | 6.83565E-002 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | -4.30000 | 2.65759E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 24284.77752 | 24284.77752 | 1.78499 | 1.78499 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 26.17250 | 8.40672E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 5350.31170 | 5350.31170 | 0.23179 | 0.67639 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -4.30000 | 2.65759E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 69887.25935 | 69887.25935 | 5.13431 | 5.13431 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 26.24833 | 8.40684E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 12302.47174 | 12302.47174 | 0.53298 | 1.89399 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -4.30000 | 2.65759E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 11854.77259 | 11854.77259 | 1.17311 | 1.17311 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | 25.36867 | 8.40546E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 4459.56055 | 4459.56055 | 0.19433 | 0.19433 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | -4.30000 | 2.65759E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 10621.01836 | 10621.01836 | 1.05102 | 1.05102 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 25.12600 | 8.40508E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 4464.16998 | 4464.16998 | 0.19454 | 0.19454 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | -4.30000 | 2.65759E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 84884.45991 | 84884.45991 | 8.39952 | 8.39952 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 26.17250 | 8.40672E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 25697.97721 | 25697.97721 | 1.11985 | 1.11985 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | -4.30000 | 2.65759E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 54006.84376 | 54006.84376 | 5.34453 | 5.34453 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 26.40000 | 8.40708E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 25797.54391 | 25797.54391 | 1.12419 | 1.12419 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | -4.30000 | 2.65759E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 10828.63816 | 10828.63816 | 1.07157 | 1.07157 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 22.94200 | 8.40167E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 4449.80399 | 4449.80399 | 0.19391 | 0.19391 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | -4.30000 | 2.65759E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 9787.01652 | 9787.01652 | 0.96849 | 0.96849 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | 21.65283 | 8.39969E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 4454.41530 | 4454.41530 | 0.19411 | 0.19411 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | -4.30000 | 2.65759E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 21696.21541 | 21696.21541 | 1.59328 | 1.59328 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 26.40000 | 8.40708E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 7213.81363 | 7213.81363 | 0.31253 | 0.47476 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -4.30000 | 2.65759E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 3120.25118 | 3120.25118 | 0.30877 | 0.30877 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 25.49000 | 8.40565E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 1401.49568 | 1401.49568 | 6.10730E-002 | 6.10730E-002 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | -4.30000 | 2.65759E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 2774.09113 | 2774.09113 | 0.27452 | 0.27452 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 25.12600 | 8.40508E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 1402.63054 | 1402.63054 | 6.11225E-002 | 6.11225E-002 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | -4.30000 | 2.65759E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 17325.43549 | 17325.43549 | 1.71451 | 1.71451 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 26.24833 | 8.40684E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 6755.45468 | 6755.45468 | 0.29438 | 0.29438 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | -4.30000 | 2.65759E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 28698.23154 | 28698.23154 | 2.11010 | 2.11010 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 26.40000 | 8.40708E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 4844.29100 | 4844.29100 | 0.20987 | 1.18780 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | -4.30000 | 2.65759E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 30057.40018 | 30057.40018 | 2.21000 | 2.21000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 26.40000 | 8.40708E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
40 | DINING_FLR_6 | Heating | 4943.39242 | 4943.39242 | 0.21416 | 1.18780 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 19:20:00 | -4.30000 | 2.65759E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 30838.24119 | 30838.24119 | 2.27053 | 2.27053 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 25.58100 | 8.40579E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 916.02783 | 916.02783 | 3.96801E-002 | 0.36735 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | -4.30000 | 2.65759E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
43 | CORRIDOR_FLR_6 | Cooling | 11130.34034 | 11130.34034 | 0.81736 | 0.81736 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 26.40000 | 8.40708E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 5178.97712 | 5178.97712 | 0.22437 | 0.22437 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 19:20:00 | -4.30000 | 2.65759E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | FLR_3_DOAS | Cooling | Sensible | 33397.10 | 18.97147 | 2.05125 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
2 | FLR_3_DOAS | Heating | Sensible | 51569.06 | 3.43751 | 2.05125 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 |
3 | VAV WITH REHEAT | Cooling | Sensible | 335075.76 | 22.50981 | 22.50981 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | VAV WITH REHEAT | Heating | Sensible | 181704.13 | 7.22758 | 7.22758 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 19:20:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.49281 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.60489 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.51500 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.28379 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.29868E-004 |
8 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.15839E-005 |
9 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.28379 |
10 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8182.48143 |
13 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.15839E-005 |
14 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 172.60240 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.44822 |
16 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11402 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.51500 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23083 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51500 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.34138E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.87860E-005 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.23083 |
24 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3290.41275 |
27 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.87860E-005 |
28 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 75.44087 |
29 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.22944 |
30 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25795 |
31 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.51500 |
32 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.11816 |
33 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.68787 |
34 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.47701E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.14365E-005 |
37 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.11816 |
38 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1307.26266 |
41 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.14365E-005 |
42 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 28.94650 |
43 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.16801 |
44 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.74490 |
45 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.51500 |
46 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.65275E-002 |
47 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.11481E-004 |
50 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.45517E-005 |
51 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 8.65275E-002 |
52 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1663.34912 |
55 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.45517E-005 |
56 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 40.38726 |
57 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 9.92591E-002 |
58 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.72746 |
59 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.51500 |
60 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 5.11184E-002 |
61 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.23743E-004 |
64 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.78356E-006 |
65 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.11184E-002 |
66 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1118.32145 |
69 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.78356E-006 |
70 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 28.04923 |
71 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.27378 |
72 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 1.81643E-002 |
73 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.51500 |
74 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.68600 |
75 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51500 |
76 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.09752E-002 |
78 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.07886E-005 |
79 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.68600 |
80 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10377.69453 |
83 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.07886E-005 |
84 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 218.42865 |
85 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.78499 |
86 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.06238E-002 |
87 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.51500 |
88 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.91927 |
89 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51500 |
90 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.72565E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.87985E-005 |
93 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.91927 |
94 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10150.21339 |
97 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.87985E-005 |
98 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 224.70184 |
99 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.13431 |
100 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19415 |
101 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.51500 |
102 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.64417 |
103 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51774 |
104 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
105 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.96238E-003 |
106 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.28402E-004 |
107 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.64417 |
108 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
110 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 26107.79559 |
111 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.28402E-004 |
112 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 570.91486 |
113 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
114 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.17311 |
115 | Fan:OnOff | ROOM_1_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 1.17311 |
116 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 3.90142E-005 |
117 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.68976E-004 |
118 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68924 |
119 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
120 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.56234E-003 |
121 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
122 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
123 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.68976E-004 |
124 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.17311 |
125 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 4459.56444 |
126 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.90142E-005 |
127 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 127.42628 |
128 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
129 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.05102 |
130 | Fan:OnOff | ROOM_2_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 1.05102 |
131 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 3.90545E-005 |
132 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.31229E-004 |
133 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68923 |
134 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
135 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.56953E-003 |
136 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
137 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
138 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.31229E-004 |
139 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.05102 |
140 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 4464.17388 |
141 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.90545E-005 |
142 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 127.55796 |
143 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83707 |
144 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 8.39952 |
145 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 8.39952 |
146 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.24817E-004 |
147 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.59666E-003 |
148 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68967 |
149 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
150 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.49942E-003 |
151 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
152 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.49942E-003 |
153 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.59666E-003 |
154 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 8.39952 |
155 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 25697.98715 |
156 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.24817E-004 |
157 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 734.27894 |
158 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83730 |
159 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 5.34453 |
160 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 5.34453 |
161 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.25688E-004 |
162 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.77371E-003 |
163 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68874 |
164 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
165 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.76288E-003 |
166 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
167 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
168 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.77371E-003 |
169 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.34453 |
170 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 25797.55390 |
171 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.25688E-004 |
172 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 737.12351 |
173 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
174 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.07157 |
175 | Fan:OnOff | ROOM_5_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 1.07157 |
176 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 3.89289E-005 |
177 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.37596E-004 |
178 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68923 |
179 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
180 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.56836E-003 |
181 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
182 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
183 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.37596E-004 |
184 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.07157 |
185 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 4449.80787 |
186 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.89289E-005 |
187 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 127.14754 |
188 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
189 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.96849 |
190 | Fan:OnOff | ROOM_6_FLR_3 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 0.96849 |
191 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 3.89692E-005 |
192 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.05716E-004 |
193 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68922 |
194 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
195 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.57545E-003 |
196 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
197 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
198 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.05716E-004 |
199 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.96849 |
200 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 4454.41919 |
201 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.89692E-005 |
202 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 127.27928 |
203 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.59328 |
204 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.74495 |
205 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.51500 |
206 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.82054 |
207 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.11447E-004 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.00593E-004 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.82054 |
212 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
213 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
214 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11498.44720 |
215 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.00593E-004 |
216 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 262.92339 |
217 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54338E-002 |
218 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.30877 |
219 | Fan:OnOff | ROOM_1_FLR_6 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 0.30877 |
220 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.22609E-005 |
221 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 9.70335E-005 |
222 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68925 |
223 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
224 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.55923E-003 |
225 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
226 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
227 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 9.70335E-005 |
228 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.30877 |
229 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1401.49693 |
230 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.22609E-005 |
231 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 40.04463 |
232 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54319E-002 |
233 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.27452 |
234 | Fan:OnOff | ROOM_2_FLR_6 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 0.27452 |
235 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.22708E-005 |
236 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 8.64445E-005 |
237 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68924 |
238 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
239 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.56663E-003 |
240 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
241 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
242 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 8.64445E-005 |
243 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.27452 |
244 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1402.63179 |
245 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.22708E-005 |
246 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 40.07705 |
247 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 9.91540E-002 |
248 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.71451 |
249 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN | Design Size Maximum Flow Rate [m3/s] | 1.71451 |
250 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.90997E-005 |
251 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 5.44384E-004 |
252 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68901 |
253 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
254 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.59694E-003 |
255 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
256 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
257 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.44384E-004 |
258 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.71451 |
259 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 6755.45977 |
260 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.90997E-005 |
261 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 193.02112 |
262 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.11010 |
263 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11977 |
264 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.51500 |
265 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.08670 |
266 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51500 |
267 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
268 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.18114E-003 |
269 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.20264E-005 |
270 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.08670 |
271 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
272 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
273 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10519.17950 |
274 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.20264E-005 |
275 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 229.56108 |
276 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.21000 |
277 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11435 |
278 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.51500 |
279 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.13815 |
280 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51500 |
281 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
282 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.33175E-003 |
283 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.52439E-005 |
284 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.13815 |
285 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
286 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
287 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10886.96523 |
288 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.52439E-005 |
289 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 237.30226 |
290 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.27053 |
291 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 6.23573E-002 |
292 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.51500 |
293 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.16932 |
294 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51500 |
295 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
296 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.09895E-002 |
297 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.11353E-005 |
298 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.16932 |
299 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
300 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
301 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6988.14353 |
302 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.11353E-005 |
303 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 146.82213 |
304 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.81736 |
305 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.38421 |
306 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.51500 |
307 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.42094 |
308 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
309 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
310 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 9.91640E-004 |
311 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.45399E-005 |
312 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.42094 |
313 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
314 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
315 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7377.30806 |
316 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.45399E-005 |
317 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 175.58236 |
318 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05132 |
319 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05132 |
320 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05132 |
321 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05132 |
322 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05132 |
323 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05132 |
324 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
325 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
326 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 11.65552 |
327 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 11.65552 |
328 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 22.63209 |
329 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 11.65552 |
330 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 22.50981 |
331 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 22.50981 |
332 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
333 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.51780 |
334 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05132 |
335 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 22.50981 |
336 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05132 |
337 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05125 |
338 | HeatExchanger:AirToAir:SensibleAndLatent | FLR_3_DOAS OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.05125 |
339 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.40000 |
340 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
341 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.91985 |
342 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.40708E-003 |
343 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.40708E-003 |
344 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Coil Load [W] | 36112.10278 |
345 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.03280E-003 |
346 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 2.05132 |
347 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Rated Capacity [W] | 15471.26131 |
348 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.35349E-004 |
349 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 263.98335 |
350 | Fan:ConstantVolume | FLR_3_DOAS FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05125 |
351 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.03280E-003 |
352 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 4.61067E-004 |
353 | Controller:WaterCoil | FLR_3_DOAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.35349E-004 |
354 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 22.50981 |
355 | HeatExchanger:AirToAir:SensibleAndLatent | VAV WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 11.66146 |
356 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.23861 |
357 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
358 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.95896 |
359 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.99021E-003 |
360 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
361 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 424344.37130 |
362 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.21362E-002 |
363 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 22.50981 |
364 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 169771.44777 |
365 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.48523E-003 |
366 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 2896.77974 |
367 | Fan:VariableVolume | VAV WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 22.50981 |
368 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.21362E-002 |
369 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 3.92372E-005 |
370 | Controller:WaterCoil | VAV WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.48523E-003 |
371 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 1.96108E-002 |
372 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 3201.83658 |
373 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 3.26836E-003 |
374 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.39220 |
375 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 3.26836E-003 |
376 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 984.28585 |
377 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
378 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 373593.37842 |
379 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 373593.38000 |
380 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 3.26836E-003 |
381 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 1.96108E-002 |
382 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 2.35329 |
383 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 1.96108E-002 |
384 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 2216.73946 |
385 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 1.96108E-002 |
386 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 685693.66917 |
387 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 686317.06000 |
388 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 78.24014 |
389 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
390 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
391 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
392 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
393 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | 8224.32 |
2 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 3305.72 |
3 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1313.56 |
4 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | 1670.56 |
5 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | 1123.01 |
6 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 10430.87 |
7 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | 10199.14 |
8 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | 26237.05 |
9 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | 4803.09 |
10 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | 4808.05 |
11 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 27677.40 |
12 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 27784.62 |
13 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | 4792.58 |
14 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | 4797.54 |
15 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 11552.09 |
16 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | 1509.43 |
17 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | 1510.65 |
18 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 7275.68 |
19 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | 10571.35 |
20 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | 10941.02 |
21 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | 7024.01 |
22 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 7410.45 |
23 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | 11770.74 |
24 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | 129164.38 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | 19107.52 | 16532.13 | 2575.39 | 0.87 | 3722.28 | 37.75 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | 17142.03 | 14819.58 | 2322.45 | 0.86 | 3333.13 | 33.81 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 135183.72 | 117803.16 | 17380.56 | 0.87 | 26757.99 | 271.39 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 90291.55 | 76471.89 | 13819.65 | 0.85 | 16806.86 | 170.46 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | 17473.30 | 15107.94 | 2365.36 | 0.86 | 3398.57 | 34.47 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | 15813.46 | 13661.95 | 2151.52 | 0.86 | 3070.08 | 31.14 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | 5026.28 | 4350.35 | 675.93 | 0.87 | 979.96 | 9.94 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | 4474.88 | 3869.87 | 605.01 | 0.86 | 870.76 | 8.83 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 28106.12 | 24224.41 | 3881.71 | 0.86 | 5426.92 | 55.04 |
10 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | 44891.31 | 33390.37 | 11500.94 | 0.74 | 6895.25 | 69.94 |
11 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | 527223.94 | 382337.85 | 144886.09 | 0.73 | 88175.92 | 894.33 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 4.09 | 13.95 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.419 | 0.394 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.419 | 0.394 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.721 | 0.651 | 22.63 | 45.89 | 22.63 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 23.26 | 23.26 | 23.26 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.721 | 0.651 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.721 | 0.651 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.721 | 0.651 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.721 | 0.651 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 2.390 | 2.390 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.721 | 0.651 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.721 | 0.651 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.721 | 0.651 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.721 | 0.651 | 63.73 | 129.23 | 63.73 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 65.50 | 65.50 | 65.50 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.721 | 0.651 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.721 | 0.651 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.721 | 0.651 | 82.79 | 167.88 | 82.79 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 85.08 | 85.08 | 85.08 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.721 | 0.651 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.844 | 0.749 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.844 | 0.749 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.844 | 0.749 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.844 | 0.749 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.844 | 0.749 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.844 | 0.749 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.844 | 0.749 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.844 | 0.749 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.844 | 0.749 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.844 | 0.749 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.917 | 0.806 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.917 | 0.806 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.917 | 0.806 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.917 | 0.806 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.857 | 0.759 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.857 | 0.759 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.857 | 0.759 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.857 | 0.759 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.857 | 0.759 | 13.70 | 20.44 | 13.70 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 6.74 | 6.74 | 6.74 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.930 | 0.816 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.930 | 0.816 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.930 | 0.816 | 16.77 | 21.37 | 16.77 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.930 | 0.816 | 34.86 | 52.03 | 34.86 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 17.17 | 17.17 | 17.17 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.930 | 0.816 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.930 | 0.816 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.930 | 0.816 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.930 | 0.816 | 34.86 | 52.03 | 34.86 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 17.17 | 17.17 | 17.17 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 1.8530054023E-002 | 2.3216869611E-002 | Pass | Pass | 5.9151476338E-003 | 1.8474587798E-002 | Pass | Pass |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.6570277059E-002 | 4.7588688609E-002 | Pass | Pass | 4.3848754992E-002 | 6.8454769190E-002 | Pass | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.6966834619E-002 | 2.8046410198E-002 | Pass | Pass | 7.5713437834E-003 | 2.0304223416E-002 | Pass | Pass |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 8.2718540538E-003 | 1.2319226466E-002 | Pass | Pass | 1.4895538460E-002 | 3.4468279039E-002 | Pass | Pass |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 3.0827551156E-004 | 2.3148493337E-004 | Pass | Pass | 3.1718256099E-002 | 5.2647455179E-002 | Pass | Pass |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 7.1378316648E-002 | 0.2037861393 | Pass | Pass | 1.9497061052E-002 | 5.1942302408E-002 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 5.3336015243E-002 | 7.3391495797E-002 | Pass | Pass | 1.4995679577E-002 | 2.9866389852E-002 | Pass | Pass |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 3.6553840603E-002 | 4.1638240274E-002 | Pass | Pass | 8.1374770559E-003 | 1.9149301338E-002 | Pass | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 3.5317792551E-002 | 9.7623885096E-002 | Pass | Pass | 0.2995334943 | 1.2793574684 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 6.1134865973E-002 | 0.1640471513 | Pass | Pass | 0.1126660689 | 0.5391468152 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 1.6038497864E-002 | 3.3179638735E-002 | Pass | Pass | 0.1207788485 | 0.4780182327 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 2.4503683129E-002 | 7.8088008087E-002 | Pass | Pass | 0.4302303300 | 1.4385651547 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.2127452202E-002 | 0.1031426385 | Pass | Pass | 0.1303730672 | 0.8574976547 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 5.3398269706E-002 | 0.1659781401 | Pass | Pass | 0.1621535035 | 0.6663552443 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 2.4145007903E-003 | 5.5432864350E-003 | Pass | Pass | 2.6332397170E-002 | 4.4702995700E-002 | Pass | Pass |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 4.5990593724E-002 | 0.1443280248 | Pass | Pass | 0.1190219232 | 0.4114281860 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 8.6743533022E-002 | 0.2422970747 | Pass | Pass | 7.4215405570E-002 | 0.2655317264 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 5.7240160321E-002 | 0.2387866717 | Pass | Pass | 0.1789201090 | 0.4005455059 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 3.0959602080E-002 | 6.8752269461E-002 | Pass | Pass | 1.3211834956E-002 | 4.1109630121E-002 | Pass | Pass |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 2.0984902217E-002 | 5.5081062147E-002 | Pass | Pass | 1.4018201003E-002 | 4.0693495044E-002 | Pass | Pass |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 2.0774196755E-002 | 5.9401851431E-002 | Pass | Pass | 2.0751196548E-002 | 4.2010936821E-002 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 5.6828791656E-003 | 1.3957586345E-002 | Pass | Pass | 2.6257396324E-002 | 3.5810148290E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:19
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3451.48 | 70.21 | 2076.81 | 8578.83 | 1867.26 | 16044.59 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:19
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | -4.30 | 0.00 | -4.30 | Wetbulb [C] | 1.20 | 110.00 |
WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 26.40 | 9.10 | 17.00 | Wetbulb [C] | 2.10 | 90.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 42.00 | 35 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 40.00 | 22 | |||
Jun | 4.00 | 8 | |||
Jul | 5.00 | 4 | |||
Aug | 7.00 | 8 | |||
Sep | 17.00 | 10 | |||
Oct | 50.00 | 49 | |||
Nov | 69.00 | 59 | |||
Dec | 95.00 | 53 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:19
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 211.13 | 211.13 | 0.00 | 90.00 | N |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.399 | 0.419 | 55.76 | 55.76 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 211.13 | 211.13 | 180.00 | 90.00 | S |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.399 | 0.419 | 55.76 | 55.76 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.651 | 0.721 | 45.89 | 22.63 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.651 | 0.721 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.651 | 0.721 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.651 | 0.721 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.651 | 0.721 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.651 | 0.721 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.651 | 0.721 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.651 | 0.721 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.651 | 0.721 | 129.23 | 63.73 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.651 | 0.721 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.651 | 0.721 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.651 | 0.721 | 167.88 | 82.79 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.651 | 0.721 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.749 | 0.844 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.749 | 0.844 | 104.06 | 69.72 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.749 | 0.844 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.749 | 0.844 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.749 | 0.844 | 847.14 | 567.58 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.749 | 0.844 | 847.37 | 567.71 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.749 | 0.844 | 104.06 | 69.72 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.749 | 0.844 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.749 | 0.844 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.749 | 0.844 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.917 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.917 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.917 | 26.02 | 17.43 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.917 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.759 | 0.857 | 13.94 | 9.34 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.759 | 0.857 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | RES_ROOF | 0.23 | 0.182 | 0.186 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | RES_EXT_WALL_TOP | 0.30 | 0.759 | 0.857 | 13.94 | 9.34 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.759 | 0.857 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | RES_ROOF | 0.23 | 0.182 | 0.186 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.759 | 0.857 | 183.96 | 123.26 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | RES_ROOF | 0.23 | 0.182 | 0.186 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.816 | 0.930 | 97.55 | 65.36 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.816 | 0.930 | 97.55 | 65.36 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.816 | 0.930 | 21.37 | 16.77 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.816 | 0.930 | 52.03 | 34.86 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.816 | 0.930 | 13.94 | 9.34 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.816 | 0.930 | 17.65 | 11.83 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.816 | 0.930 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.816 | 0.930 | 52.03 | 34.86 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 167.42 | 167.42 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_FLOOR | BASEMENT_FLOOR | 0.30 | 1.441 | 2.705 | 1978.83 | 1978.83 | 0.00 | 180.00 | |
BASEMENT_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 67.07 | 67.07 | 180.00 | 0.00 | |
BASEMENT_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 77.67 | 77.67 | 180.00 | 0.00 | |
BASEMENT_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 164.24 | 164.24 | 180.00 | 0.00 | |
BASEMENT_CEILING_4 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 94.76 | 94.76 | 180.00 | 0.00 | |
BASEMENT_CEILING_5 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 78.04 | 78.04 | 180.00 | 0.00 | |
BASEMENT_CEILING_6 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 188.86 | 188.86 | 180.00 | 0.00 | |
BASEMENT_CEILING_7 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 1088.56 | 1088.56 | 180.00 | 0.00 | |
BASEMENT_CEILING_8 | NONRES_FLOOR_CEILING | 0.30 | 0.215 | 0.228 | 219.63 | 219.63 | 90.00 | 0.00 | |
RETAIL_1_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_1_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
RETAIL_1_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 67.07 | 67.07 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
RETAIL_2_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_2_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 90.00 | 90.00 | E |
RETAIL_2_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 77.67 | 77.67 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 77.67 | 77.67 | 180.00 | 0.00 | |
MECH_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
MECH_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 180.00 | 90.00 | S |
MECH_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
MECH_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 164.24 | 164.24 | 0.00 | 180.00 | |
MECH_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 164.24 | 164.24 | 180.00 | 0.00 | |
STORAGE_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
STORAGE_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 180.00 | 90.00 | S |
STORAGE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
STORAGE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 94.76 | 94.76 | 0.00 | 180.00 | |
STORAGE_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 94.76 | 94.76 | 180.00 | 0.00 | |
LAUNDRY_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 180.00 | 90.00 | S |
LAUNDRY_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 270.00 | 90.00 | W |
LAUNDRY_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 78.04 | 78.04 | 0.00 | 180.00 | |
LAUNDRY_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 78.04 | 78.04 | 180.00 | 0.00 | |
CAFE_FLR_1_WALL_1_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_2_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
CAFE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 188.86 | 188.86 | 0.00 | 180.00 | |
LOBBY_FLR_1_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 90.00 | 90.00 | E |
LOBBY_FLR_1_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 1088.56 | 1088.56 | 180.00 | 180.00 | |
LOBBY_FLR_1_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.215 | 0.228 | 219.63 | 219.63 | 90.00 | 180.00 | |
LOBBY_FLR_1_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 1062.83 | 1062.83 | 270.00 | 0.00 | |
ROOM_1_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_1_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
ROOM_1_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_1_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_2_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
ROOM_2_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_2_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_2_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 156.07 | 156.07 | 180.00 | 0.00 | |
ROOM_3_MULT19_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.14 | 847.14 | 0.00 | 90.00 | N |
ROOM_3_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_3_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 1863.81 | 1863.81 | 0.00 | 180.00 | |
ROOM_3_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 1863.81 | 1863.81 | 180.00 | 0.00 | |
ROOM_4_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_4_MULT19_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.37 | 847.37 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_4_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 1864.32 | 1864.32 | 0.00 | 180.00 | |
ROOM_4_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 1864.32 | 1864.32 | 180.00 | 0.00 | |
ROOM_5_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
ROOM_5_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_5_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_6_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
ROOM_6_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_6_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 156.07 | 156.07 | 180.00 | 0.00 | |
CORRIDOR_FLR_3_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.28 | 847.28 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_4_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.27 | 847.27 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 297.29 | 297.29 | 180.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 963.06 | 963.06 | 270.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_3 | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 297.26 | 297.26 | 90.00 | 180.00 | |
CORRIDOR_FLR_3_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 297.29 | 297.29 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 963.06 | 963.06 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.217 | 0.228 | 297.26 | 297.26 | 90.00 | 0.00 | |
ROOM_1_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 0.00 | 90.00 | N |
ROOM_1_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_1_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_2_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_2_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 180.00 | 90.00 | S |
ROOM_2_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_3_MULT9_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.96 | 183.96 | 0.00 | 90.00 | N |
ROOM_3_MULT9_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 90.00 | 90.00 | E |
ROOM_3_MULT9_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 270.00 | 90.00 | W |
ROOM_3_MULT9_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 220.77 | 220.77 | 0.00 | 180.00 | |
BANQUET_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
BANQUET_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
BANQUET_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
BANQUET_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 331.66 | 331.66 | 0.00 | 180.00 | |
DINING_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
DINING_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
DINING_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
DINING_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 331.66 | 331.66 | 0.00 | 180.00 | |
KITCHEN_FLR_6_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 7.43 | 7.43 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 103.30 | 103.30 | 180.00 | 180.00 | |
CORRIDOR_FLR_6_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 104.98 | 104.98 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_1_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.95 | 183.95 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 11.15 | 11.15 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 40.88 | 40.88 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.212 | 0.228 | 412.12 | 412.12 | 180.00 | 180.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3957.66 | 0.00 | 90.00 | N | ||
RETAIL_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 134.14 | 0.00 | 90.00 | N | ||
RETAIL_2_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 155.34 | 0.00 | 90.00 | N | ||
MECH_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 328.49 | 0.00 | 90.00 | N | ||
STORAGE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 189.52 | 0.00 | 90.00 | N | ||
LAUNDRY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 156.08 | 0.00 | 90.00 | N | ||
CAFE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 377.72 | 0.00 | 90.00 | N | ||
LOBBY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 2616.37 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3727.63 | 0.00 | 90.00 | N | ||
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3728.64 | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3115.24 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.04 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.03 | 0.00 | 90.00 | N | ||
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 441.55 | 0.00 | 90.00 | N | ||
BANQUET_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
DINING_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 206.61 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 824.25 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.38 | 23.26 | 0.00 | 0.00 | 23.26 | 23.26 | 2.159 | 0.381 | 0.420 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.38 | 65.50 | 0.00 | 0.00 | 65.50 | 65.50 | 2.159 | 0.381 | 0.420 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.38 | 85.08 | 0.00 | 0.00 | 85.08 | 85.08 | 2.159 | 0.381 | 0.420 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.38_SHGC_0.38 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.159 | 0.381 | 0.420 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.38_SHGC_0.38 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.159 | 0.381 | 0.420 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.38_SHGC_0.38 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.159 | 0.381 | 0.420 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.38_SHGC_0.38 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.159 | 0.381 | 0.420 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.38_SHGC_0.38 | 3.68 | 0.00 | 0.00 | 3.68 | 279.56 | 2.159 | 0.381 | 0.420 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.38_SHGC_0.38 | 3.68 | 0.00 | 0.00 | 3.68 | 279.65 | 2.159 | 0.381 | 0.420 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.38_SHGC_0.38 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.159 | 0.381 | 0.420 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.38_SHGC_0.38 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.159 | 0.381 | 0.420 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.38_SHGC_0.38 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.159 | 0.381 | 0.420 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.38_SHGC_0.38 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.159 | 0.381 | 0.420 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.38 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.159 | 0.381 | 0.420 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.38 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 2.159 | 0.381 | 0.420 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.38 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 2.159 | 0.381 | 0.420 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.38 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.159 | 0.381 | 0.420 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.38_SHGC_0.38 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.159 | 0.381 | 0.420 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.38_SHGC_0.38 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.159 | 0.381 | 0.420 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.38_SHGC_0.38 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.159 | 0.381 | 0.420 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.38_SHGC_0.38 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.159 | 0.381 | 0.420 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.38_SHGC_0.38 | 6.74 | 0.00 | 0.00 | 6.74 | 60.70 | 2.159 | 0.381 | 0.420 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.38 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.159 | 0.381 | 0.420 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.38 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.159 | 0.381 | 0.420 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.38 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.159 | 0.381 | 0.420 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.38 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.159 | 0.381 | 0.420 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | |||||||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.38 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.159 | 0.381 | 0.420 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.38 | 5.82 | 0.00 | 0.00 | 5.82 | 5.82 | 2.159 | 0.381 | 0.420 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.38 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 2.159 | 0.381 | 0.420 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.38 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.159 | 0.381 | 0.420 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 1213.79 | 2.159 | 0.381 | 0.420 | |||||||||||||||||
North Total or Average | 432.95 | 2.159 | 0.381 | 0.420 | |||||||||||||||||
Non-North Total or Average | 780.84 | 2.159 | 0.381 | 0.420 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 1.760 | 2.390 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:19
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:19
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 8.8143 | 1978.83 | 17441.96 | LightsWired | LTG_SCH_BASEMENT | 49.32 | 168.00 | 49.26 | 0.0000 | Y | 161.29 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | RETAIL_1_FLR_1 | GENERAL | 11.3140 | 67.07 | 758.85 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 7.31 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | RETAIL_2_FLR_1 | GENERAL | 11.3140 | 77.67 | 878.75 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 8.46 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | MECH_FLR_1 | GENERAL | 4.6285 | 164.24 | 760.20 | LightsWired | LTG_SCH_MECHANIC | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 8.37 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | STORAGE_FLR_1 | GENERAL | 5.7199 | 94.76 | 542.02 | LightsWired | LTG_SCH_STORAGE | 30.30 | 168.00 | 30.27 | 0.0000 | Y | 3.08 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | LAUNDRY_FLR_1 | GENERAL | 4.6285 | 78.04 | 361.20 | LightsWired | LTG_SCH_LAUNDRY | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 3.98 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | CAFE_FLR_1 | GENERAL | 10.0104 | 188.86 | 1890.59 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 39.73 | 0.0000 | Y | 14.10 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | LOBBY_FLR_1 | GENERAL | 10.7639 | 1308.19 | 14081.18 | LightsWired | LTG_SCH_LOBBY | 44.02 | 168.00 | 41.58 | 0.0000 | Y | 109.92 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | ROOM_1_FLR_3 | GENERAL | 8.2882 | 156.09 | 1293.69 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | ROOM_2_FLR_3 | GENERAL | 8.2882 | 156.07 | 1293.54 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | GENERAL | 8.2882 | 1863.81 | 15447.65 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 110.38 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | GENERAL | 8.2882 | 1864.32 | 15451.87 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 110.41 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | ROOM_5_FLR_3 | GENERAL | 8.2882 | 156.09 | 1293.69 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | ROOM_6_FLR_3 | GENERAL | 8.2882 | 156.07 | 1293.54 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 9.24 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | CORRIDOR_FLR_3 | GENERAL | 7.1042 | 1557.62 | 11065.59 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 91.33 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | ROOM_1_FLR_6 | GENERAL | 8.2882 | 39.02 | 323.42 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 2.31 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | ROOM_2_FLR_6 | GENERAL | 8.2882 | 39.02 | 323.38 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 2.31 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | GENERAL | 8.2882 | 220.77 | 1829.83 | LightsWired | LTG_SCH_GUESTROOM | 37.96 | 168.00 | 38.07 | 0.0000 | Y | 13.08 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | BANQUET_FLR_6 | GENERAL | 10.0104 | 331.66 | 3320.03 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 49.45 | 0.0000 | Y | 30.82 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | DINING_FLR_6 | GENERAL | 10.0104 | 331.66 | 3320.03 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 49.45 | 0.0000 | Y | 30.82 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | KITCHEN_FLR_6 | GENERAL | 11.4097 | 103.30 | 1178.68 | LightsWired | LTG_SCH_KITCHEN | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 12.97 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | CORRIDOR_FLR_6 | GENERAL | 7.1042 | 412.12 | 2927.80 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 24.17 |
Interior Lighting Total | 8.5566 | 11345.29 | 97077.49 | 456.33 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
LOBBY_FLR_1_DAYLREFPT1 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.07 | 14081.18 | 985.68 |
LOBBY_FLR_1_DAYLREFPT2 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.07 | 14081.18 | 985.68 |
CAFE_FLR_1_DAYLREFPT1 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1890.59 | 737.33 |
CAFE_FLR_1_DAYLREFPT2 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1890.59 | 737.33 |
DINING_FLR_6_DAYLREFPT1 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
DINING_FLR_6_DAYLREFPT2 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
BANQUET_FLR_6_DAYLREFPT1 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
BANQUET_FLR_6_DAYLREFPT2 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3320.03 | 664.01 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 12338.45 | AstronomicalClock | - | 83.54 | 83.54 | 193.49 | |
Exterior Lighting Total | 12338.45 | 193.49 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:19
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 373593.38 | 0.80 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 686317.06 | 2.96 | 686317.06 | 2.96 | 4.09 | 13.95 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 12901.55 | 19107.52 | 16532.13 | 2575.39 | 0.87 | - | 3722.28 | 37.75 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 11581.71 | 17142.03 | 14819.58 | 2322.45 | 0.86 | - | 3333.13 | 33.81 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 90794.58 | 135183.72 | 117803.16 | 17380.56 | 0.87 | - | 26757.99 | 271.39 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 62019.31 | 90291.55 | 76471.89 | 13819.65 | 0.85 | - | 16806.86 | 170.46 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 11804.33 | 17473.30 | 15107.94 | 2365.36 | 0.86 | - | 3398.57 | 34.47 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 10689.63 | 15813.46 | 13661.95 | 2151.52 | 0.86 | - | 3070.08 | 31.14 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3392.86 | 5026.28 | 4350.35 | 675.93 | 0.87 | - | 979.96 | 9.94 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3022.61 | 4474.88 | 3869.87 | 605.01 | 0.86 | - | 870.76 | 8.83 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 19034.83 | 28106.12 | 24224.41 | 3881.71 | 0.86 | - | 5426.92 | 55.04 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | 36112.10 | 44891.31 | 33390.37 | 11500.94 | 0.74 | - | 6895.25 | 69.94 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | 424344.37 | 527223.94 | 382337.85 | 144886.09 | 0.73 | - | 88175.92 | 894.33 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 8182.48 | 8224.32 | - |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 3290.41 | 3305.72 | - |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1307.26 | 1313.56 | - |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1663.35 | 1670.56 | - |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1118.32 | 1123.01 | - |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 10377.69 | 10430.87 | - |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 10150.21 | 10199.14 | - |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 26107.80 | 26237.05 | - |
ROOM_1_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 4459.56 | 4803.09 | - |
ROOM_2_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 4464.17 | 4808.05 | - |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 25697.99 | 27677.40 | - |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 25797.55 | 27784.62 | - |
ROOM_5_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 4449.81 | 4792.58 | - |
ROOM_6_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 4454.42 | 4797.54 | - |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 11498.45 | 11552.09 | - |
ROOM_1_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 1401.50 | 1509.43 | - |
ROOM_2_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 1402.63 | 1510.65 | - |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 6755.46 | 7275.68 | - |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 10519.18 | 10571.35 | - |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 10886.97 | 10941.02 | - |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 6988.14 | 7024.01 | - |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 7377.31 | 7410.45 | - |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | 15471.26 | 11770.74 | - |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | 169771.45 | 129164.38 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 0.24 | 76.61 | 324.68 | 1.00 | 2.78 | General | ||
LOBBY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.24 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
ROOM_1_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 1.17 | 825.44 | 703.64 | 1.00 | 1.16 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 |
ROOM_2_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 1.05 | 739.54 | 703.64 | 1.00 | 1.18 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 |
ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 8.40 | 5910.21 | 703.64 | 1.00 | 0.94 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 |
ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 5.34 | 3760.60 | 703.64 | 1.00 | 0.97 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 |
ROOM_5_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 1.07 | 753.99 | 703.64 | 1.00 | 1.18 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 |
ROOM_6_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 0.97 | 681.47 | 703.64 | 1.00 | 1.20 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 |
ROOM_1_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 0.31 | 217.26 | 703.64 | 1.00 | 1.69 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 |
ROOM_2_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 0.27 | 193.16 | 703.64 | 1.00 | 1.78 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 |
ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.39 | 270.90 | 1.71 | 1206.39 | 703.64 | 1.00 | 1.09 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 |
BANQUET_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
DINING_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 1.89 | 612.92 | 324.68 | 1.00 | 1.48 | General | ||
FLR_3_DOAS FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.93 | 1070.05 | 1.00 | 1.30 | General | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 |
VAV WITH REHEAT FAN | Fan:VariableVolume | 0.62 | 1389.42 | 22.51 | 50436.34 | 2240.64 | 1.00 | 1.11 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.019611 | 3201.84 | 163269.44 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.003268 | 984.29 | 301156.09 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.019611 | 2216.74 | 113036.94 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH LAUNDRY G WATER HEATER | WaterHeater:Mixed | 1.14 | 163316.00 | 0.80 | 11.51 | 0.44 |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.22 | 1.12 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.60 | 0.80 | 5.78 | 0.37 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:19
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 33944.50 | 33944.50 | 17.15 | 2.493 | 2.493 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 24.00 | 24.00 | 0.00921 | 23.31 | 0.00840 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 6102.93 | 6102.93 | 90.99 | 0.448 | 0.448 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 24.00 | 24.00 | 0.00890 | 26.17 | 0.00841 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 3123.88 | 3123.88 | 40.22 | 0.229 | 0.229 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | 24.00 | 24.00 | 0.00940 | 26.13 | 0.00841 | 0.092 | 0.00 |
MECH_FLR_1 | 2288.09 | 2288.09 | 13.93 | 0.168 | 0.168 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 24.00 | 24.00 | 0.00876 | 26.22 | 0.00841 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1351.74 | 1351.74 | 14.26 | 0.099 | 0.099 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 24.00 | 24.00 | 0.00884 | 26.40 | 0.00841 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 44579.66 | 44579.66 | 571.25 | 3.274 | 3.274 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 24.00 | 24.00 | 0.00854 | 26.40 | 0.00841 | 0.000 | 0.00 |
CAFE_FLR_1 | 24284.78 | 24284.78 | 128.58 | 1.785 | 1.785 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 24.00 | 23.99 | 0.00982 | 26.17 | 0.00841 | 0.676 | 0.00 |
LOBBY_FLR_1 | 69887.26 | 69887.26 | 53.42 | 5.134 | 5.134 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 24.00 | 23.99 | 0.00986 | 26.25 | 0.00841 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 11854.77 | 11854.77 | 303.80 | 1.173 | 1.173 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | 21.11 | 21.11 | 0.00856 | 25.37 | 0.00841 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 10621.02 | 10621.02 | 272.21 | 1.051 | 1.051 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 21.11 | 21.11 | 0.00857 | 25.13 | 0.00841 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 84884.46 | 84884.46 | 3461.30 | 8.400 | 8.400 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 21.11 | 21.11 | 0.00850 | 26.17 | 0.00841 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 54006.84 | 54006.84 | 2201.62 | 5.345 | 5.345 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 21.11 | 21.11 | 0.00876 | 26.40 | 0.00841 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 10828.64 | 10828.64 | 277.50 | 1.072 | 1.072 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 21.11 | 21.11 | 0.00857 | 22.94 | 0.00840 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 9787.02 | 9787.02 | 250.84 | 0.968 | 0.968 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | 21.11 | 21.11 | 0.00858 | 21.65 | 0.00840 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 21696.22 | 21696.22 | 55.72 | 1.593 | 1.593 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 24.00 | 24.00 | 0.00938 | 26.40 | 0.00841 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 3120.25 | 3120.25 | 79.96 | 0.309 | 0.309 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 21.11 | 21.11 | 0.00856 | 25.49 | 0.00841 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2774.09 | 2774.09 | 71.10 | 0.275 | 0.275 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 21.11 | 21.11 | 0.00857 | 25.13 | 0.00841 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 17325.44 | 17325.44 | 706.28 | 1.715 | 1.715 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 21.11 | 21.11 | 0.00860 | 26.25 | 0.00841 | 0.099 | 0.00 |
BANQUET_FLR_6 | 28698.23 | 28698.23 | 86.53 | 2.110 | 2.110 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 24.00 | 23.98 | 0.01046 | 26.40 | 0.00841 | 1.188 | 0.00 |
DINING_FLR_6 | 30057.40 | 30057.40 | 90.63 | 2.210 | 2.210 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 24.00 | 23.99 | 0.01037 | 26.40 | 0.00841 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 30838.24 | 30838.24 | 298.52 | 2.271 | 2.271 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 24.00 | 23.97 | 0.01008 | 25.58 | 0.00841 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 11130.34 | 11130.34 | 27.01 | 0.817 | 0.817 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 24.00 | 24.00 | 0.00895 | 26.40 | 0.00841 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 1476.52 | 1476.52 | 0.75 | 0.064 | 0.854 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00797 | -4.30 | 0.00266 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 2085.25 | 2085.25 | 31.09 | 0.090 | 0.090 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 21.00 | 21.00 | 0.00773 | -4.30 | 0.00266 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 690.37 | 690.37 | 8.89 | 0.030 | 0.092 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00769 | -4.30 | 0.00266 | 0.092 | 0.00 |
MECH_FLR_1 | 1211.69 | 1211.69 | 7.38 | 0.052 | 0.052 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00759 | -4.30 | 0.00266 | 0.000 | 0.00 |
STORAGE_FLR_1 | 851.46 | 851.46 | 8.99 | 0.037 | 0.058 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00766 | -4.30 | 0.00266 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 1577.85 | 1577.85 | 20.22 | 0.068 | 0.068 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 21.00 | 21.00 | 0.00757 | -4.30 | 0.00266 | 0.000 | 0.00 |
CAFE_FLR_1 | 5350.31 | 5350.31 | 28.33 | 0.232 | 0.676 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00777 | -4.30 | 0.00266 | 0.676 | 0.00 |
LOBBY_FLR_1 | 12302.47 | 12302.47 | 9.40 | 0.533 | 1.894 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00771 | -4.30 | 0.00266 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 4459.56 | 4459.56 | 114.28 | 0.194 | 0.194 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 21.11 | 21.11 | 0.00771 | -4.30 | 0.00266 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 4464.17 | 4464.17 | 114.41 | 0.195 | 0.195 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 21.11 | 21.11 | 0.00771 | -4.30 | 0.00266 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 25697.98 | 25697.98 | 1047.88 | 1.120 | 1.120 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 21.11 | 21.11 | 0.00773 | -4.30 | 0.00266 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 25797.54 | 25797.54 | 1051.65 | 1.124 | 1.124 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 21.11 | 21.11 | 0.00773 | -4.30 | 0.00266 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 4449.80 | 4449.80 | 114.03 | 0.194 | 0.194 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 21.11 | 21.11 | 0.00771 | -4.30 | 0.00266 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 4454.42 | 4454.42 | 114.16 | 0.194 | 0.194 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 21.11 | 21.11 | 0.00771 | -4.30 | 0.00266 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 7213.81 | 7213.81 | 18.53 | 0.313 | 0.475 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00778 | -4.30 | 0.00266 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 1401.50 | 1401.50 | 35.92 | 0.061 | 0.061 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 21.11 | 21.11 | 0.00777 | -4.30 | 0.00266 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 1402.63 | 1402.63 | 35.95 | 0.061 | 0.061 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 21.11 | 21.11 | 0.00777 | -4.30 | 0.00266 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 6755.45 | 6755.45 | 275.39 | 0.294 | 0.294 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 21.11 | 21.11 | 0.00778 | -4.30 | 0.00266 | 0.099 | 0.00 |
BANQUET_FLR_6 | 4844.29 | 4844.29 | 14.61 | 0.210 | 1.188 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 21.00 | 21.00 | 0.00783 | -4.30 | 0.00266 | 1.188 | 0.00 |
DINING_FLR_6 | 4943.39 | 4943.39 | 14.91 | 0.214 | 1.188 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 19:20:00 | 21.00 | 21.00 | 0.00784 | -4.30 | 0.00266 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 916.03 | 916.03 | 8.87 | 0.040 | 0.367 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 21.00 | 21.00 | 0.00516 | -4.30 | 0.00266 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 5178.98 | 5178.98 | 12.57 | 0.224 | 0.224 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 19:20:00 | 21.00 | 21.00 | 0.00786 | -4.30 | 0.00266 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
FLR_3_DOAS | 18.97 | 2.05 | 3.44 | 2.05 | 2.0513 | 2.0513 | 2.0513 | 1.0000 | 0.3000 |
VAV WITH REHEAT | 22.51 | 22.51 | 7.23 | 7.23 | 22.5098 | 11.6555 | 22.5098 | 0.5178 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 8182.481 | 8182.481 | 1.283795 | 0.00007158 | 172.602 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 8182.48 | 8182.48 | 1.283795 | 16.70 | 13.09 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00796550 | 50.9500 | 1476.52 | 0.00 | 8228.28 | 8228.28 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 3290.413 | 3290.413 | 0.230834 | 0.00002879 | 75.441 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 3290.41 | 3290.41 | 0.230834 | 16.70 | 13.09 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00773101 | 49.4695 | 2085.25 | 0.00 | 3308.08 | 3308.08 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 1307.263 | 1307.263 | 0.118159 | 0.00001144 | 28.947 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 1307.26 | 1307.26 | 0.118159 | 16.70 | 13.09 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00768898 | 49.2031 | 690.37 | 0.00 | 1314.37 | 1314.37 |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 1663.349 | 1663.349 | 0.086528 | 0.00001455 | 40.387 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 1663.35 | 1663.35 | 0.086528 | 16.70 | 13.09 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00758946 | 48.5740 | 1211.69 | 0.00 | 1672.01 | 1672.01 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 1118.321 | 1118.321 | 0.051118 | 0.00000978 | 28.049 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 1118.32 | 1118.32 | 0.051118 | 16.70 | 13.09 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00765824 | 49.0088 | 851.46 | 0.00 | 1124.08 | 1124.08 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 10377.695 | 10377.695 | 1.685998 | 0.00009079 | 218.429 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 10377.69 | 10377.69 | 1.685998 | 16.70 | 13.09 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00757111 | 48.4588 | 1577.85 | 0.00 | 10435.83 | 10435.83 |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 10150.213 | 10150.213 | 0.919270 | 0.00008880 | 224.702 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 10150.21 | 10150.21 | 0.919270 | 16.70 | 13.09 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00776663 | 49.6942 | 5350.31 | 0.00 | 10205.43 | 10205.43 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 26107.796 | 26107.796 | 2.644167 | 0.00022840 | 570.915 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 26107.80 | 26107.80 | 2.644167 | 16.70 | 13.09 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00771305 | 49.3552 | 12302.47 | 0.00 | 26252.34 | 26252.34 |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 12901.550 | -999.000 | 1.173109 | 0.00036898 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | unknown | 8/21 16:40:00 | 12901.55 | 12709.12 | 1.173109 | 21.69 | 15.50 | 0.00856234 | 12.80 | 12.00 | 0.00850000 | 25.37 | 0.00840546 | 16.68 | 0.0000 | 21.11 | 0.00856234 | 54.3450 | 11854.77 | 0.00 | 13046.83 | 13046.83 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 4459.564 | 4459.564 | 0.194334 | 0.00003901 | 127.426 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 4459.56 | 4459.56 | 0.194334 | 21.11 | 14.52 | 0.00771084 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.11 | 0.00771084 | 49.0069 | 4459.56 | 0.00 | 4807.54 | 4807.54 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 11581.714 | -999.000 | 1.051022 | 0.00033123 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | unknown | 8/21 17:00:00 | 11581.71 | 11389.40 | 1.051022 | 21.69 | 15.51 | 0.00856953 | 12.80 | 12.00 | 0.00850000 | 25.13 | 0.00840508 | 16.59 | 0.0000 | 21.11 | 0.00856953 | 54.3900 | 10621.02 | 0.00 | 11711.85 | 11711.85 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 4464.174 | 4464.174 | 0.194535 | 0.00003905 | 127.558 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 4464.17 | 4464.17 | 0.194535 | 21.11 | 14.52 | 0.00771114 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.11 | 0.00771114 | 49.0088 | 4464.17 | 0.00 | 4812.51 | 4812.51 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 90794.576 | -999.000 | 8.399518 | 0.00259666 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | unknown | 8/21 13:30:00 | 90794.58 | 90794.57 | 8.399518 | 21.69 | 15.45 | 0.00849942 | 12.80 | 12.00 | 0.00849942 | 26.17 | 0.00840672 | 16.96 | 0.0000 | 21.11 | 0.00849942 | 53.9499 | 84884.46 | 0.00 | 91816.62 | 91816.62 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 25697.987 | 25697.987 | 1.119853 | 0.00022482 | 734.279 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 25697.99 | 25697.99 | 1.119853 | 21.11 | 14.54 | 0.00773283 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.11 | 0.00773283 | 49.1442 | 25697.98 | 0.00 | 27703.27 | 27703.27 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 62019.310 | -999.000 | 5.344525 | 0.00177371 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | unknown | 8/21 15:00:00 | 62019.31 | 58297.22 | 5.344525 | 21.69 | 15.68 | 0.00876288 | 12.80 | 12.00 | 0.00850000 | 26.40 | 0.00840708 | 17.04 | 0.0000 | 21.11 | 0.00876288 | 55.6012 | 54006.84 | 0.00 | 62701.90 | 61339.07 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 25797.554 | 25797.554 | 1.124192 | 0.00022569 | 737.124 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 25797.55 | 25797.55 | 1.124192 | 21.11 | 14.55 | 0.00773374 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.11 | 0.00773374 | 49.1500 | 25797.54 | 0.00 | 27810.61 | 27810.61 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 11804.328 | -999.000 | 1.071567 | 0.00033760 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | unknown | 8/21 10:00:00 | 11804.33 | 11611.54 | 1.071567 | 21.69 | 15.51 | 0.00856836 | 12.80 | 12.00 | 0.00850000 | 22.94 | 0.00840167 | 15.82 | 0.0000 | 21.11 | 0.00856836 | 54.3827 | 10828.64 | 0.00 | 11937.01 | 11937.01 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 4449.808 | 4449.808 | 0.193909 | 0.00003893 | 127.148 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 4449.81 | 4449.81 | 0.193909 | 21.11 | 14.52 | 0.00771024 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.11 | 0.00771024 | 49.0031 | 4449.80 | 0.00 | 4797.02 | 4797.02 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 10689.629 | -999.000 | 0.968492 | 0.00030572 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | unknown | 8/21 09:10:00 | 10689.63 | 10497.28 | 0.968492 | 21.69 | 15.52 | 0.00857545 | 12.80 | 12.00 | 0.00850000 | 21.65 | 0.00839969 | 15.35 | 0.0000 | 21.11 | 0.00857545 | 54.4271 | 9787.02 | 0.00 | 10809.53 | 10809.53 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 4454.419 | 4454.419 | 0.194110 | 0.00003897 | 127.279 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 4454.42 | 4454.42 | 0.194110 | 21.11 | 14.52 | 0.00771055 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.11 | 0.00771055 | 49.0050 | 4454.42 | 0.00 | 4801.99 | 4801.99 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 11498.447 | 11498.447 | 0.820539 | 0.00010059 | 262.923 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 11498.45 | 11498.45 | 0.820539 | 16.70 | 13.09 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00777962 | 49.7758 | 7213.81 | 0.00 | 11560.24 | 11560.24 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 3392.857 | -999.000 | 0.308770 | 0.00009703 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | unknown | 8/21 16:30:00 | 3392.86 | 3344.75 | 0.308770 | 21.69 | 15.50 | 0.00855923 | 12.80 | 12.00 | 0.00850000 | 25.49 | 0.00840565 | 16.72 | 0.0000 | 21.11 | 0.00855923 | 54.3255 | 3120.25 | 0.00 | 3431.10 | 3431.10 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 1401.497 | 1401.497 | 0.061073 | 0.00001226 | 40.045 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 1401.50 | 1401.50 | 0.061073 | 21.11 | 14.58 | 0.00776735 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.11 | 0.00776735 | 49.3616 | 1401.50 | 0.00 | 1510.85 | 1510.85 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 3022.605 | -999.000 | 0.274515 | 0.00008644 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | unknown | 8/21 17:00:00 | 3022.61 | 2974.47 | 0.274515 | 21.69 | 15.51 | 0.00856663 | 12.80 | 12.00 | 0.00850000 | 25.13 | 0.00840508 | 16.59 | 0.0000 | 21.11 | 0.00856663 | 54.3719 | 2774.09 | 0.00 | 3056.60 | 3056.60 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 1402.632 | 1402.632 | 0.061122 | 0.00001227 | 40.077 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 1402.63 | 1402.63 | 0.061122 | 21.11 | 14.58 | 0.00776755 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.11 | 0.00776755 | 49.3629 | 1402.63 | 0.00 | 1512.08 | 1512.08 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 19034.832 | -999.000 | 1.714509 | 0.00054438 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | unknown | 8/21 13:40:00 | 19034.83 | 18596.98 | 1.714509 | 21.69 | 15.53 | 0.00859694 | 12.80 | 12.00 | 0.00850000 | 26.25 | 0.00840684 | 16.99 | 0.0000 | 21.11 | 0.00859694 | 54.5623 | 17325.44 | 0.00 | 19247.01 | 19247.01 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 6755.460 | 6755.460 | 0.294384 | 0.00005910 | 193.021 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 6755.46 | 6755.46 | 0.294384 | 21.11 | 14.59 | 0.00777732 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.11 | 0.00777732 | 49.4239 | 6755.45 | 0.00 | 7282.59 | 7282.59 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 10519.179 | 10519.179 | 1.086700 | 0.00009203 | 229.561 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 10519.18 | 10519.18 | 1.086700 | 16.70 | 13.09 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00783258 | 50.1107 | 4844.29 | 0.00 | 10577.45 | 10577.45 |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 10886.965 | 10886.965 | 1.138151 | 0.00009524 | 237.302 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 19:20:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 19:20:00 | 10886.97 | 10886.97 | 1.138151 | 16.70 | 13.09 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00783581 | 50.1312 | 4943.39 | 0.00 | 10947.29 | 10947.29 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 6988.144 | 6988.144 | 1.169324 | 0.00006114 | 146.822 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 6988.14 | 6988.14 | 1.169324 | 16.70 | 13.09 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00516107 | 33.1663 | 916.03 | 0.00 | 7027.31 | 7027.31 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 7377.308 | 7377.308 | 0.420940 | 0.00006454 | 175.582 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 19:20:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 19:20:00 | 7377.31 | 7377.31 | 0.420940 | 16.70 | 13.09 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00786199 | 50.2965 | 5178.98 | 0.00 | 7416.49 | 7416.49 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 36112.103 | -999.000 | 2.051317 | 0.00103280 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 36112.10 | 36112.10 | 2.051317 | 26.40 | 17.04 | 0.00840708 | 11.92 | 11.55 | 0.00840708 | 26.40 | 0.00840708 | 17.04 | 99.9965 | 21.11 | 0.00860283 | 54.5982 | 191716.15 | 0.00 | 36442.34 | 36442.34 |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | FLR_3_DOAS | 15471.261 | 15471.261 | 0.615395 | 0.00013535 | 263.983 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 15471.26 | 15471.26 | 0.615395 | -4.30 | -4.30 | 0.00265759 | 16.70 | 13.09 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 333.3216 | 21.11 | 0.00773357 | 49.1489 | 78883.05 | 0.00 | 14236.78 | 14236.78 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 424344.371 | -999.000 | 22.509806 | 0.01213620 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 424344.37 | 389783.97 | 22.509806 | 25.24 | 17.13 | 0.00899021 | 10.96 | 10.96 | 0.00850000 | 26.40 | 0.00840708 | 17.04 | 51.8061 | 23.99 | 0.00957506 | 50.9310 | 306214.64 | 0.00 | 428205.71 | 379322.03 |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV WITH REHEAT | 169771.448 | 169771.448 | 6.752942 | 0.00148523 | 2896.780 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 19:20:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 19:20:00 | 169771.45 | 169771.45 | 6.752942 | -4.30 | -4.30 | 0.00265759 | 16.70 | 13.09 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 172.6871 | 21.00 | 0.00775870 | 49.6337 | 48136.30 | 0.00 | 156225.06 | 156225.06 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:25:19
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | Yes | Yes | No | 8182.481 | 8182.481 | 1.283795 | 0.00007158 | 172.602 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.26802444 | 54.44 | 82.22 | 27.78 | 381112.09 | 2.1470 | 2.190211 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 8182.48 | 8182.48 | 1.0000 | 1.52947694 | 1.283795 | 16.70 | 13.09 | 0.00800000 | 37036.7 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.07157661 | 60.00 | 32.22 | 27.78 | 0.000 | 8182.48 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.00 | 0.00796550 | 21.00 | 0.00796550 | 50.9500 | 1476.52 | 0.00 | 8228.28 | 8228.28 | 1.52947694 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.88 | 15.18 | 0.00800000 | 42314.5 | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3290.413 | 3290.413 | 0.230834 | 0.00002879 | 75.441 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.26802444 | 54.44 | 82.22 | 27.78 | 381112.09 | 0.8634 | 0.880747 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | Sensible | 3290.41 | 3290.41 | 1.0000 | 0.27500951 | 0.230834 | 16.70 | 13.09 | 0.00800000 | 37036.7 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.02878303 | 60.00 | 32.22 | 27.78 | 0.000 | 3290.41 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.00 | 0.00773101 | 21.00 | 0.00773101 | 49.4695 | 2085.25 | 0.00 | 3308.08 | 3308.08 | 0.27500951 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 28.40 | 17.50 | 0.00800000 | 48963.7 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1307.263 | 1307.263 | 0.118159 | 0.00001144 | 28.947 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.26802444 | 54.44 | 82.22 | 27.78 | 381112.09 | 0.3430 | 0.349916 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 1307.26 | 1307.26 | 1.0000 | 0.14077190 | 0.118159 | 16.70 | 13.09 | 0.00800000 | 37036.7 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.01143534 | 60.00 | 32.22 | 27.78 | 0.000 | 1307.26 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.00 | 0.00768898 | 21.00 | 0.00768898 | 49.2031 | 690.37 | 0.00 | 1314.37 | 1314.37 | 0.14077190 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 25.76 | 16.58 | 0.00800000 | 46271.6 | |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1663.349 | 1663.349 | 0.086528 | 0.00001455 | 40.387 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.26802444 | 54.44 | 82.22 | 27.78 | 381112.09 | 0.4364 | 0.445230 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 1663.35 | 1663.35 | 1.0000 | 0.10308647 | 0.086528 | 16.70 | 13.09 | 0.00800000 | 37036.7 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.01455022 | 60.00 | 32.22 | 27.78 | 0.000 | 1663.35 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.00 | 0.00758946 | 21.00 | 0.00758946 | 48.5740 | 1211.69 | 0.00 | 1672.01 | 1672.01 | 0.10308647 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 32.51 | 18.86 | 0.00800000 | 53154.2 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1118.321 | 1118.321 | 0.051118 | 0.00000978 | 28.049 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.26802444 | 54.44 | 82.22 | 27.78 | 381112.09 | 0.2934 | 0.299342 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 1118.32 | 1118.32 | 1.0000 | 0.06090106 | 0.051118 | 16.70 | 13.09 | 0.00800000 | 37036.7 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.00978257 | 60.00 | 32.22 | 27.78 | 0.000 | 1118.32 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.00 | 0.00765824 | 21.00 | 0.00765824 | 49.0088 | 851.46 | 0.00 | 1124.08 | 1124.08 | 0.06090106 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 34.70 | 19.56 | 0.00800000 | 55392.2 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10377.695 | 10377.695 | 1.685998 | 0.00009079 | 218.429 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.26802444 | 54.44 | 82.22 | 27.78 | 381112.09 | 2.7230 | 2.777805 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | Sensible | 10377.69 | 10377.69 | 1.0000 | 2.00865134 | 1.685998 | 16.70 | 13.09 | 0.00800000 | 37036.7 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.09077934 | 60.00 | 32.22 | 27.78 | 0.000 | 10377.69 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.00 | 0.00757111 | 21.00 | 0.00757111 | 48.4588 | 1577.85 | 0.00 | 10435.83 | 10435.83 | 2.00865134 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.70 | 15.11 | 0.00800000 | 42130.2 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10150.213 | 10150.213 | 0.919270 | 0.00008880 | 224.702 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.26802444 | 54.44 | 82.22 | 27.78 | 381112.09 | 2.6633 | 2.716915 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 10150.21 | 10150.21 | 1.0000 | 1.09519298 | 0.919270 | 16.70 | 13.09 | 0.00800000 | 37036.7 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.08878944 | 60.00 | 32.22 | 27.78 | 0.000 | 10150.21 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.00 | 0.00776663 | 21.00 | 0.00776663 | 49.6942 | 5350.31 | 0.00 | 10205.43 | 10205.43 | 1.09519298 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 25.74 | 16.57 | 0.00800000 | 46253.1 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 26107.796 | 26107.796 | 2.644167 | 0.00022840 | 570.915 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.26802444 | 54.44 | 82.22 | 27.78 | 381112.09 | 6.8504 | 6.988292 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 26107.80 | 26107.80 | 1.0000 | 3.15018711 | 2.644167 | 16.70 | 13.09 | 0.00800000 | 37036.7 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.22837909 | 60.00 | 32.22 | 27.78 | 0.000 | 26107.80 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.00 | 0.00771305 | 21.00 | 0.00771305 | 49.3552 | 12302.47 | 0.00 | 26252.34 | 26252.34 | 3.15018711 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 24.77 | 16.23 | 0.00800000 | 45268.3 | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12901.550 | -999.000 | 1.173109 | 0.00036898 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7570 | 1004.8586 | 1.1914 | ROOM_1_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.173109 | 1.39760946 | 4197.9300 | 999.8980 | 19.60875164 | 15.03 | 6.70 | 8.33 | 685693.67 | 1.8815 | 1.881497 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | unknown | unknown | unknown | 8/21 16:40:00 | Sensible | 12901.55 | 12709.12 | 1.0000 | 1.39760946 | 1.173109 | 21.69 | 15.50 | 0.00856234 | 43553.4 | 12.80 | 12.00 | 0.00850000 | 34322.2 | 0.36893815 | 6.70 | 15.03 | 8.33 | 0.000 | 12901.55 | 25.37 | 0.00840546 | 16.68 | 0.00000000 | 0.0000 | 21.11 | 0.00856234 | 21.11 | 0.00856234 | 54.3450 | 11854.77 | 0.00 | 13046.83 | 13046.83 | 1.39760946 | 21.69 | 15.61 | 0.00856234 | 43553.4 | 12.54 | 12.06 | 0.00856234 | 34218.2 | |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4459.564 | 4459.564 | 0.194334 | 0.00003901 | 127.426 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | ROOM_1_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.173109 | 1.39760946 | 4197.9300 | 999.8980 | 3.26802444 | 54.44 | 82.22 | 27.78 | 381112.09 | 1.1701 | 1.193695 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | Sensible | 4459.56 | 4459.56 | 1.0000 | 0.23152442 | 0.194334 | 21.11 | 14.52 | 0.00771084 | 40799.7 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.03901024 | 60.00 | 32.22 | 27.78 | 0.000 | 4459.56 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.11 | 0.00771084 | 21.11 | 0.00771084 | 49.0069 | 4459.56 | 0.00 | 4807.54 | 4807.54 | 0.23152442 | 16.60 | 12.87 | 0.00771084 | 36202.6 | 36.97 | 20.05 | 0.00771084 | 56967.4 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11581.714 | -999.000 | 1.051022 | 0.00033123 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7703 | 1004.8586 | 1.1914 | ROOM_2_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.051022 | 1.25215807 | 4197.9300 | 999.8980 | 19.60875164 | 15.03 | 6.70 | 8.33 | 685693.67 | 1.6891 | 1.689019 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | unknown | unknown | unknown | 8/21 17:00:00 | Sensible | 11581.71 | 11389.40 | 1.0000 | 1.25215807 | 1.051022 | 21.69 | 15.51 | 0.00856953 | 43571.6 | 12.80 | 12.00 | 0.00850000 | 34322.2 | 0.33119559 | 6.70 | 15.03 | 8.33 | 0.000 | 11581.71 | 25.13 | 0.00840508 | 16.59 | 0.00000000 | 0.0000 | 21.11 | 0.00856953 | 21.11 | 0.00856953 | 54.3900 | 10621.02 | 0.00 | 11711.85 | 11711.85 | 1.25215807 | 21.69 | 15.62 | 0.00856953 | 43571.6 | 12.53 | 12.06 | 0.00856953 | 34218.3 | |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4464.174 | 4464.174 | 0.194535 | 0.00003905 | 127.558 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | ROOM_2_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.051022 | 1.25215807 | 4197.9300 | 999.8980 | 3.26802444 | 54.44 | 82.22 | 27.78 | 381112.09 | 1.1714 | 1.194929 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | Sensible | 4464.17 | 4464.17 | 1.0000 | 0.23176373 | 0.194535 | 21.11 | 14.52 | 0.00771114 | 40800.5 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.03905056 | 60.00 | 32.22 | 27.78 | 0.000 | 4464.17 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.11 | 0.00771114 | 21.11 | 0.00771114 | 49.0088 | 4464.17 | 0.00 | 4812.51 | 4812.51 | 0.23176373 | 16.60 | 12.87 | 0.00771114 | 36203.4 | 36.97 | 20.05 | 0.00771114 | 56968.1 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 90794.576 | -999.000 | 8.399518 | 0.00259666 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6400 | 1004.8586 | 1.1914 | ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 8.399518 | 10.00695057 | 4197.9300 | 999.8980 | 19.60875164 | 15.03 | 6.70 | 8.33 | 685693.67 | 13.2413 | 13.241027 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | unknown | unknown | unknown | 8/21 13:30:00 | Sensible | 90794.58 | 90794.57 | 1.0000 | 10.00695057 | 8.399518 | 21.69 | 15.45 | 0.00849942 | 43393.9 | 12.80 | 12.00 | 0.00849942 | 34320.7 | 2.59640000 | 6.70 | 15.03 | 8.33 | 0.000 | 90794.58 | 26.17 | 0.00840672 | 16.96 | 0.00000000 | 0.0000 | 21.11 | 0.00849942 | 21.11 | 0.00849942 | 53.9499 | 84884.46 | 0.00 | 91816.62 | 91816.62 | 10.00695057 | 21.69 | 15.56 | 0.00849942 | 43393.9 | 12.70 | 12.06 | 0.00849942 | 34218.6 | |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 25697.987 | 25697.987 | 1.119853 | 0.00022482 | 734.279 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 8.399518 | 10.00695057 | 4197.9300 | 999.8980 | 3.26802444 | 54.44 | 82.22 | 27.78 | 381112.09 | 6.7429 | 6.878598 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | Sensible | 25697.99 | 25697.99 | 1.0000 | 1.33416173 | 1.119853 | 21.11 | 14.54 | 0.00773283 | 40855.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.22479427 | 60.00 | 32.22 | 27.78 | 0.000 | 25697.99 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.11 | 0.00773283 | 21.11 | 0.00773283 | 49.1442 | 25697.98 | 0.00 | 27703.27 | 27703.27 | 1.33416173 | 16.60 | 12.89 | 0.00773283 | 36258.3 | 36.97 | 20.07 | 0.00773283 | 57022.9 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 62019.310 | -999.000 | 5.344525 | 0.00177371 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1298 | 1004.8586 | 1.1914 | ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 5.344525 | 6.36731758 | 4197.9300 | 999.8980 | 19.60875164 | 15.03 | 6.70 | 8.33 | 685693.67 | 9.0448 | 9.044586 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | unknown | unknown | unknown | 8/21 15:00:00 | Sensible | 62019.31 | 58297.22 | 1.0000 | 6.36731758 | 5.344525 | 21.69 | 15.68 | 0.00876288 | 44062.5 | 12.80 | 12.00 | 0.00850000 | 34322.2 | 1.77353036 | 6.70 | 15.03 | 8.33 | 0.000 | 62019.31 | 26.40 | 0.00840708 | 17.04 | 0.00000000 | 0.0000 | 21.11 | 0.00876288 | 21.11 | 0.00876288 | 55.6012 | 54006.84 | 0.00 | 62701.90 | 61339.07 | 6.36731758 | 21.69 | 15.79 | 0.00876288 | 44062.5 | 12.25 | 12.05 | 0.00867807 | 34215.0 | |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 25797.554 | 25797.554 | 1.124192 | 0.00022569 | 737.124 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 5.344525 | 6.36731758 | 4197.9300 | 999.8980 | 3.26802444 | 54.44 | 82.22 | 27.78 | 381112.09 | 6.7690 | 6.905249 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | Sensible | 25797.55 | 25797.55 | 1.0000 | 1.33933093 | 1.124192 | 21.11 | 14.55 | 0.00773374 | 40858.1 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.22566523 | 60.00 | 32.22 | 27.78 | 0.000 | 25797.55 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.11 | 0.00773374 | 21.11 | 0.00773374 | 49.1500 | 25797.54 | 0.00 | 27810.61 | 27810.61 | 1.33933093 | 16.60 | 12.89 | 0.00773374 | 36260.6 | 36.97 | 20.07 | 0.00773374 | 57025.2 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11804.328 | -999.000 | 1.071567 | 0.00033760 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7682 | 1004.8586 | 1.1914 | ROOM_5_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.071567 | 1.27663447 | 4197.9300 | 999.8980 | 19.60875164 | 15.03 | 6.70 | 8.33 | 685693.67 | 1.7215 | 1.721484 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | unknown | unknown | unknown | 8/21 10:00:00 | Sensible | 11804.33 | 11611.54 | 1.0000 | 1.27663447 | 1.071567 | 21.69 | 15.51 | 0.00856836 | 43568.6 | 12.80 | 12.00 | 0.00850000 | 34322.2 | 0.33756154 | 6.70 | 15.03 | 8.33 | 0.000 | 11804.33 | 22.94 | 0.00840167 | 15.82 | 0.00000000 | 0.0000 | 21.11 | 0.00856836 | 21.11 | 0.00856836 | 54.3827 | 10828.64 | 0.00 | 11937.01 | 11937.01 | 1.27663447 | 21.69 | 15.62 | 0.00856836 | 43568.6 | 12.53 | 12.06 | 0.00856836 | 34218.3 | |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4449.808 | 4449.808 | 0.193909 | 0.00003893 | 127.148 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | ROOM_5_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 1.071567 | 1.27663447 | 4197.9300 | 999.8980 | 3.26802444 | 54.44 | 82.22 | 27.78 | 381112.09 | 1.1676 | 1.191083 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | Sensible | 4449.81 | 4449.81 | 1.0000 | 0.23101790 | 0.193909 | 21.11 | 14.52 | 0.00771024 | 40798.2 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.03892489 | 60.00 | 32.22 | 27.78 | 0.000 | 4449.81 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.11 | 0.00771024 | 21.11 | 0.00771024 | 49.0031 | 4449.80 | 0.00 | 4797.02 | 4797.02 | 0.23101790 | 16.60 | 12.87 | 0.00771024 | 36201.1 | 36.97 | 20.05 | 0.00771024 | 56965.8 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10689.629 | -999.000 | 0.968492 | 0.00030572 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7813 | 1004.8586 | 1.1914 | ROOM_6_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.968492 | 1.15383418 | 4197.9300 | 999.8980 | 19.60875164 | 15.03 | 6.70 | 8.33 | 685693.67 | 1.5590 | 1.558922 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | unknown | unknown | unknown | 8/21 09:10:00 | Sensible | 10689.63 | 10497.28 | 1.0000 | 1.15383418 | 0.968492 | 21.69 | 15.52 | 0.00857545 | 43586.6 | 12.80 | 12.00 | 0.00850000 | 34322.2 | 0.30568514 | 6.70 | 15.03 | 8.33 | 0.000 | 10689.63 | 21.65 | 0.00839969 | 15.35 | 0.00000000 | 0.0000 | 21.11 | 0.00857545 | 21.11 | 0.00857545 | 54.4271 | 9787.02 | 0.00 | 10809.53 | 10809.53 | 1.15383418 | 21.69 | 15.62 | 0.00857545 | 43586.6 | 12.51 | 12.06 | 0.00857545 | 34218.3 | |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4454.419 | 4454.419 | 0.194110 | 0.00003897 | 127.279 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | ROOM_6_FLR_3 FAN COIL_FANCOILFAN | Fan:OnOff | 0.968492 | 1.15383418 | 4197.9300 | 999.8980 | 3.26802444 | 54.44 | 82.22 | 27.78 | 381112.09 | 1.1688 | 1.192317 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | Sensible | 4454.42 | 4454.42 | 1.0000 | 0.23125730 | 0.194110 | 21.11 | 14.52 | 0.00771055 | 40799.0 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.03896523 | 60.00 | 32.22 | 27.78 | 0.000 | 4454.42 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.11 | 0.00771055 | 21.11 | 0.00771055 | 49.0050 | 4454.42 | 0.00 | 4801.99 | 4801.99 | 0.23125730 | 16.60 | 12.87 | 0.00771055 | 36201.9 | 36.97 | 20.05 | 0.00771055 | 56966.6 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11498.447 | 11498.447 | 0.820539 | 0.00010059 | 262.923 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.26802444 | 54.44 | 82.22 | 27.78 | 381112.09 | 3.0171 | 3.077797 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 11498.45 | 11498.45 | 1.0000 | 0.97756664 | 0.820539 | 16.70 | 13.09 | 0.00800000 | 37036.7 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.10058317 | 60.00 | 32.22 | 27.78 | 0.000 | 11498.45 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.00 | 0.00777962 | 21.00 | 0.00777962 | 49.7758 | 7213.81 | 0.00 | 11560.24 | 11560.24 | 0.97756664 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 28.20 | 17.43 | 0.00800000 | 48760.3 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3392.857 | -999.000 | 0.308770 | 0.00009703 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7512 | 1004.8586 | 1.1914 | ROOM_1_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.308770 | 0.36785959 | 4197.9300 | 999.8980 | 19.60875164 | 15.03 | 6.70 | 8.33 | 685693.67 | 0.4948 | 0.494797 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | unknown | unknown | unknown | 8/21 16:30:00 | Sensible | 3392.86 | 3344.75 | 1.0000 | 0.36785959 | 0.308770 | 21.69 | 15.50 | 0.00855923 | 43545.4 | 12.80 | 12.00 | 0.00850000 | 34322.2 | 0.09702358 | 6.70 | 15.03 | 8.33 | 0.000 | 3392.86 | 25.49 | 0.00840565 | 16.72 | 0.00000000 | 0.0000 | 21.11 | 0.00855923 | 21.11 | 0.00855923 | 54.3255 | 3120.25 | 0.00 | 3431.10 | 3431.10 | 0.36785959 | 21.69 | 15.61 | 0.00855923 | 43545.4 | 12.55 | 12.06 | 0.00855923 | 34218.2 | |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1401.497 | 1401.497 | 0.061073 | 0.00001226 | 40.045 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | ROOM_1_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.308770 | 0.36785959 | 4197.9300 | 999.8980 | 3.26802444 | 54.44 | 82.22 | 27.78 | 381112.09 | 0.3677 | 0.375140 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | Sensible | 1401.50 | 1401.50 | 1.0000 | 0.07276066 | 0.061073 | 21.11 | 14.58 | 0.00776735 | 40943.3 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.01225966 | 60.00 | 32.22 | 27.78 | 0.000 | 1401.50 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.11 | 0.00776735 | 21.11 | 0.00776735 | 49.3616 | 1401.50 | 0.00 | 1510.85 | 1510.85 | 0.07276066 | 16.60 | 12.92 | 0.00776735 | 36345.7 | 36.97 | 20.09 | 0.00776735 | 57110.4 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3022.605 | -999.000 | 0.274515 | 0.00008644 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7649 | 1004.8586 | 1.1914 | ROOM_2_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.274515 | 0.32704956 | 4197.9300 | 999.8980 | 19.60875164 | 15.03 | 6.70 | 8.33 | 685693.67 | 0.4408 | 0.440802 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | unknown | unknown | unknown | 8/21 17:00:00 | Sensible | 3022.61 | 2974.47 | 1.0000 | 0.32704956 | 0.274515 | 21.69 | 15.51 | 0.00856663 | 43564.2 | 12.80 | 12.00 | 0.00850000 | 34322.2 | 0.08643570 | 6.70 | 15.03 | 8.33 | 0.000 | 3022.61 | 25.13 | 0.00840508 | 16.59 | 0.00000000 | 0.0000 | 21.11 | 0.00856663 | 21.11 | 0.00856663 | 54.3719 | 2774.09 | 0.00 | 3056.60 | 3056.60 | 0.32704956 | 21.69 | 15.62 | 0.00856663 | 43564.2 | 12.53 | 12.06 | 0.00856663 | 34218.3 | |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1402.632 | 1402.632 | 0.061122 | 0.00001227 | 40.077 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | ROOM_2_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 0.274515 | 0.32704956 | 4197.9300 | 999.8980 | 3.26802444 | 54.44 | 82.22 | 27.78 | 381112.09 | 0.3680 | 0.375443 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | Sensible | 1402.63 | 1402.63 | 1.0000 | 0.07281958 | 0.061122 | 21.11 | 14.58 | 0.00776755 | 40943.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.01226958 | 60.00 | 32.22 | 27.78 | 0.000 | 1402.63 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.11 | 0.00776755 | 21.11 | 0.00776755 | 49.3629 | 1402.63 | 0.00 | 1512.08 | 1512.08 | 0.07281958 | 16.60 | 12.92 | 0.00776755 | 36346.2 | 36.97 | 20.10 | 0.00776755 | 57110.9 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 19034.832 | -999.000 | 1.714509 | 0.00054438 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8213 | 1004.8586 | 1.1914 | ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 1.714509 | 2.04261751 | 4197.9300 | 999.8980 | 19.60875164 | 15.03 | 6.70 | 8.33 | 685693.67 | 2.7760 | 2.775945 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | unknown | unknown | unknown | 8/21 13:40:00 | Sensible | 19034.83 | 18596.98 | 1.0000 | 2.04261751 | 1.714509 | 21.69 | 15.53 | 0.00859694 | 43641.0 | 12.80 | 12.00 | 0.00850000 | 34322.2 | 0.54432807 | 6.70 | 15.03 | 8.33 | 0.000 | 19034.83 | 26.25 | 0.00840684 | 16.99 | 0.00000000 | 0.0000 | 21.11 | 0.00859694 | 21.11 | 0.00859694 | 54.5623 | 17325.44 | 0.00 | 19247.01 | 19247.01 | 2.04261751 | 21.69 | 15.64 | 0.00859694 | 43641.0 | 12.46 | 12.06 | 0.00859694 | 34218.3 | |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6755.460 | 6755.460 | 0.294384 | 0.00005910 | 193.021 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN | Fan:OnOff | 1.714509 | 2.04261751 | 4197.9300 | 999.8980 | 3.26802444 | 54.44 | 82.22 | 27.78 | 381112.09 | 1.7726 | 1.808239 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | Sensible | 6755.46 | 6755.46 | 1.0000 | 0.35072048 | 0.294384 | 21.11 | 14.59 | 0.00777732 | 40968.7 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.05909368 | 60.00 | 32.22 | 27.78 | 0.000 | 6755.46 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.11 | 0.00777732 | 21.11 | 0.00777732 | 49.4239 | 6755.45 | 0.00 | 7282.59 | 7282.59 | 0.35072048 | 16.60 | 12.93 | 0.00777732 | 36371.0 | 36.97 | 20.10 | 0.00777732 | 57135.6 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10519.179 | 10519.179 | 1.086700 | 0.00009203 | 229.561 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.26802444 | 54.44 | 82.22 | 27.78 | 381112.09 | 2.7601 | 2.815676 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | Sensible | 10519.18 | 10519.18 | 1.0000 | 1.29466451 | 1.086700 | 16.70 | 13.09 | 0.00800000 | 37036.7 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.09201698 | 60.00 | 32.22 | 27.78 | 0.000 | 10519.18 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.00 | 0.00783258 | 21.00 | 0.00783258 | 50.1107 | 4844.29 | 0.00 | 10577.45 | 10577.45 | 1.29466451 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 24.61 | 16.18 | 0.00800000 | 45104.8 | |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10886.965 | 10886.965 | 1.138151 | 0.00009524 | 237.302 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.26802444 | 54.44 | 82.22 | 27.78 | 381112.09 | 2.8566 | 2.914122 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 19:20:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 19:20:00 | Sensible | 10886.97 | 10886.97 | 1.0000 | 1.35596084 | 1.138151 | 16.70 | 13.09 | 0.00800000 | 37036.7 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.09523421 | 60.00 | 32.22 | 27.78 | 0.000 | 10886.97 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.00 | 0.00783581 | 21.00 | 0.00783581 | 50.1312 | 4943.39 | 0.00 | 10947.29 | 10947.29 | 1.35596084 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 24.52 | 16.14 | 0.00800000 | 45008.2 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6988.144 | 6988.144 | 1.169324 | 0.00006114 | 146.822 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.26802444 | 54.44 | 82.22 | 27.78 | 381112.09 | 1.8336 | 1.870521 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | Sensible | 6988.14 | 6988.14 | 1.0000 | 1.39310037 | 1.169324 | 16.70 | 13.09 | 0.00800000 | 37036.7 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.06112909 | 60.00 | 32.22 | 27.78 | 0.000 | 6988.14 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 19.76 | 0.00516107 | 21.00 | 0.00516107 | 33.1663 | 916.03 | 0.00 | 7027.31 | 7027.31 | 1.39310037 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.55 | 15.06 | 0.00800000 | 41979.1 | |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7377.308 | 7377.308 | 0.420940 | 0.00006454 | 175.582 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.26802444 | 54.44 | 82.22 | 27.78 | 381112.09 | 1.9357 | 1.974689 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 19:20:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 19:20:00 | Sensible | 7377.31 | 7377.31 | 1.0000 | 0.50149570 | 0.420940 | 16.70 | 13.09 | 0.00800000 | 37036.7 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.06453333 | 60.00 | 32.22 | 27.78 | 0.000 | 7377.31 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.00 | 0.00786199 | 21.00 | 0.00786199 | 50.2965 | 5178.98 | 0.00 | 7416.49 | 7416.49 | 0.50149570 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 31.10 | 18.40 | 0.00800000 | 51723.5 | |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 36112.103 | -999.000 | 2.051317 | 0.00103280 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.4683 | 1004.8586 | 1.1914 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.44379602 | 4197.9300 | 999.8980 | 19.60875164 | 15.03 | 6.70 | 8.33 | 685693.67 | 5.2665 | 5.266507 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | Sensible | 36112.10 | 36112.10 | 1.0000 | 2.44388195 | 2.051317 | 26.40 | 17.04 | 0.00840708 | 47966.0 | 11.92 | 11.55 | 0.00840708 | 33189.4 | 1.03269621 | 6.70 | 15.03 | 8.33 | 2195.006 | 33917.10 | 26.40 | 0.00840708 | 17.04 | 2.05124512 | 99.9965 | 21.11 | 0.00859981 | 21.11 | 0.00860283 | 54.5982 | 191716.15 | 0.00 | 36442.34 | 36442.34 | 2.44388195 | 26.40 | 17.15 | 0.00840708 | 47966.0 | 11.79 | 11.58 | 0.00840708 | 33054.3 | |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 15471.261 | 15471.261 | 0.615395 | 0.00013535 | 263.983 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.44379602 | 4197.9300 | 999.8980 | 3.26802444 | 54.44 | 82.22 | 27.78 | 381112.09 | 4.0595 | 4.141203 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | Sensible | 15471.26 | 15471.26 | 1.0000 | 0.73316458 | 0.615395 | -4.30 | -4.30 | 0.00265759 | 2304.4 | 16.70 | 13.09 | 0.00800000 | 37036.7 | 0.13533554 | 60.00 | 32.22 | 27.78 | 0.000 | 15471.26 | -4.30 | 0.00265759 | -4.30 | 2.05124512 | 333.3216 | 21.11 | 0.00773316 | 21.11 | 0.00773357 | 49.1489 | 78883.05 | 0.00 | 14236.78 | 14236.78 | 0.73316458 | 2.80 | 0.02 | 0.00265759 | 9473.9 | 22.03 | 9.93 | 0.00265759 | 28892.1 | |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 424344.371 | -999.000 | 22.509806 | 0.01213620 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.5523 | 1004.8586 | 1.1914 | VAV WITH REHEAT FAN | Fan:VariableVolume | 22.509806 | 26.81755337 | 4197.9300 | 999.8980 | 19.60875164 | 15.03 | 6.70 | 8.33 | 685693.67 | 61.8854 | 61.885415 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 424344.37 | 389783.97 | 1.0000 | 26.81755337 | 22.509806 | 25.24 | 17.13 | 0.00899021 | 48266.5 | 10.96 | 10.96 | 0.00850000 | 32443.2 | 12.13495729 | 6.70 | 15.03 | 8.33 | 50436.341 | 373908.03 | 26.40 | 0.00840708 | 17.04 | 11.66146000 | 51.8061 | 23.99 | 0.00961750 | 23.99 | 0.00957506 | 50.9310 | 306214.64 | 0.00 | 428205.71 | 379322.03 | 26.81755337 | 25.24 | 17.24 | 0.00899021 | 48266.5 | 11.39 | 11.27 | 0.00826747 | 32299.2 | |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 169771.448 | 169771.448 | 6.752942 | 0.00148523 | 2896.780 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | VAV WITH REHEAT FAN | Fan:VariableVolume | 22.509806 | 26.81755337 | 4197.9300 | 999.8980 | 3.26802444 | 54.44 | 82.22 | 27.78 | 381112.09 | 44.5463 | 45.442842 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 19:20:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 19:20:00 | Sensible | 169771.45 | 169771.45 | 1.0000 | 8.04526601 | 6.752942 | -4.30 | -4.30 | 0.00265759 | 2304.4 | 16.70 | 13.09 | 0.00800000 | 37036.7 | 1.48508318 | 60.00 | 32.22 | 27.78 | 0.000 | 169771.45 | -4.30 | 0.00265759 | -4.30 | 11.66146000 | 172.6871 | 20.92 | 0.00767716 | 21.00 | 0.00775870 | 49.6337 | 48136.30 | 0.00 | 156225.06 | 156225.06 | 8.04526601 | 2.80 | 0.02 | 0.00265759 | 9473.9 | 22.03 | 9.93 | 0.00265759 | 28892.1 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:19
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - | |||
VAV WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 22.51 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | VAV WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000610 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LAUNDRY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CAFE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001448 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_3 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
KITCHEN_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003556 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 3.17 | 8265.00 | 0.00 |
RETAIL_1_FLR_1 | 857.33 | 8091.33 | 456.33 |
RETAIL_2_FLR_1 | 186.50 | 8015.50 | 0.00 |
MECH_FLR_1 | 37.50 | 8732.00 | 37.50 |
STORAGE_FLR_1 | 82.17 | 8760.00 | 82.17 |
LAUNDRY_FLR_1 | 7305.83 | 3178.83 | 2502.83 |
CAFE_FLR_1 | 897.50 | 7151.00 | 18.67 |
LOBBY_FLR_1 | 667.83 | 6956.50 | 9.33 |
ROOM_1_FLR_3 | 885.33 | 8432.50 | 866.17 |
ROOM_2_FLR_3 | 1714.17 | 8298.67 | 1454.67 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 188.67 | 8750.33 | 188.17 |
ROOM_5_FLR_3 | 841.00 | 8383.33 | 840.50 |
ROOM_6_FLR_3 | 1423.17 | 8488.83 | 1336.17 |
CORRIDOR_FLR_3 | 34.50 | 8760.00 | 34.50 |
ROOM_1_FLR_6 | 1790.33 | 8333.83 | 1715.17 |
ROOM_2_FLR_6 | 2719.33 | 8267.67 | 2475.33 |
ROOM_3_MULT9_FLR_6 | 472.33 | 8175.50 | 406.50 |
BANQUET_FLR_6 | 3926.67 | 1789.67 | 7.67 |
DINING_FLR_6 | 5631.17 | 692.50 | 7.17 |
KITCHEN_FLR_6 | 8533.50 | 6204.83 | 6195.83 |
CORRIDOR_FLR_6 | 71.83 | 8610.67 | 51.83 |
Facility | 8756.83 | 8760.00 | 7067.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4.00 | 1.00 | 4.00 | 1.00 |
ROOM_2_FLR_3 | 9.67 | 8.83 | 9.67 | 8.83 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.50 | 14.17 | 0.50 | 14.17 |
ROOM_5_FLR_3 | 4.17 | 0.00 | 4.17 | 0.00 |
ROOM_6_FLR_3 | 10.00 | 7.50 | 10.00 | 7.50 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8.67 | 2.83 | 8.67 | 2.83 |
ROOM_2_FLR_6 | 19.67 | 13.33 | 19.67 | 13.33 |
ROOM_3_MULT9_FLR_6 | 2.17 | 1.00 | 2.17 | 1.00 |
BANQUET_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 20.83 | 27.67 | 20.83 | 27.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:19
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.78 | 106.50 | 4826.41 | 0.978 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 3.173 | 0.062 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 1.406 | 0.021 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.484 | 0.023 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.496 | 0.023 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 23.250 | 0.067 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.55 | 142.30 | 748.35 | 4.499 | 0.049 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.05 | 422.44 | 5183.56 | 1.874 | 0.020 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.354 | 0.081 | 0.000 | 0.027 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.355 | 0.081 | 0.000 | 0.021 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.402 | 0.036 | 0.000 | 0.046 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.354 | 0.081 | 0.000 | 0.027 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.355 | 0.081 | 0.000 | 0.030 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 0.630 | 0.010 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.355 | 0.081 | 0.000 | 0.031 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.355 | 0.081 | 0.000 | 0.020 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.403 | 0.066 | 0.000 | 0.049 |
BANQUET_FLR_6 | 144.96 | 249.90 | 1010.89 | 4.667 | 0.023 | 0.000 | 0.000 |
DINING_FLR_6 | 144.96 | 249.90 | 1010.89 | 5.098 | 0.023 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 22.039 | 0.067 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 1.220 | 0.016 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.78 | 106.50 | 4826.41 | 0.941 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 3.050 | 0.001 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 1.355 | 0.000 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.467 | 0.000 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.478 | 0.000 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 19.256 | 0.001 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.55 | 142.30 | 748.35 | 4.333 | 0.001 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.05 | 422.44 | 5183.56 | 1.805 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 0.607 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.000 | 0.001 | 0.000 | 0.000 |
BANQUET_FLR_6 | 144.96 | 249.90 | 1010.89 | 3.831 | 0.000 | 0.000 | 0.000 |
DINING_FLR_6 | 144.96 | 249.90 | 1010.89 | 4.018 | 0.000 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 13.169 | 0.001 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 1.177 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:25:19
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | VAV WITH REHEAT | 61.78 | 106.50 | 4826.41 | 1978.83 | 0.0000 | 0.854 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 6.28 | 10.83 | 265.76 | 67.07 | 0.0000 | 0.079 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 7.27 | 12.54 | 307.76 | 77.67 | 0.0000 | 0.092 |
MECH_FLR_1 | VAV WITH REHEAT | 1.54 | 2.65 | 650.80 | 164.24 | 0.0000 | 0.000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 1.18 | 2.04 | 375.47 | 94.76 | 0.0000 | 0.058 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 4.87 | 8.40 | 309.22 | 78.04 | 0.0000 | 0.000 |
CAFE_FLR_1 | VAV WITH REHEAT | 82.55 | 142.30 | 748.35 | 188.86 | 0.0000 | 0.676 |
LOBBY_FLR_1 | VAV WITH REHEAT | 245.05 | 422.44 | 5183.56 | 1308.19 | 0.0000 | 1.894 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 1.50 | 74.75 | 24.52 | 0.0000 | 0.837 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.837 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 12.16 | 20.96 | 1186.91 | 389.40 | 0.0000 | 0.475 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.015 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.015 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.099 |
BANQUET_FLR_6 | VAV WITH REHEAT | 144.96 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
DINING_FLR_6 | VAV WITH REHEAT | 144.96 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 12.90 | 22.24 | 314.87 | 103.30 | 0.0000 | 0.367 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 12.87 | 22.18 | 1256.16 | 412.12 | 0.0000 | 0.126 |
Total Facility | 873.11 | 1604.23 | 35184.81 | 11345.29 | 0.0000 | 137.584 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 40655445.00 | 0.00 | 40655445.00 | 0.00 | 40655445.00 | 26946214.98 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_1_FLR_1 | 7310112.33 | 0.00 | 7310112.33 | 143731.35 | 7453843.68 | 2498216.28 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_2_FLR_1 | 3736260.03 | 0.00 | 3736260.03 | 55480.48 | 3791740.51 | 2892943.94 | 0.00 | 0.00 | 8760.00 | 0.00 |
MECH_FLR_1 | 2728732.39 | 0.00 | 2728732.39 | 131122.90 | 2859855.30 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
STORAGE_FLR_1 | 1612070.50 | 0.00 | 1612070.50 | 75650.69 | 1687721.19 | 1821682.01 | 8760.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 61988391.18 | 0.00 | 61988391.18 | 179041.63 | 62167432.81 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
CAFE_FLR_1 | 29082666.31 | 0.00 | 29082666.31 | 317726.29 | 29400392.60 | 21330615.53 | 0.00 | 0.00 | 8760.00 | 0.00 |
LOBBY_FLR_1 | 83720620.53 | 0.00 | 83720620.53 | 907816.58 | 84628437.11 | 59728886.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
ROOM_1_FLR_3 | 1460156.71 | 28030.93 | 1488187.65 | 83426.14 | 1571613.79 | 1946875.62 | 2190.00 | 6236.00 | 334.00 | 0.00 |
ROOM_2_FLR_3 | 1459985.63 | 21279.24 | 1481264.87 | 83419.78 | 1564684.65 | 1946647.51 | 2190.00 | 6339.69 | 230.31 | 0.00 |
ROOM_3_MULT19_FLR_3 | 1099911.97 | 12.95 | 1099924.92 | 23276.83 | 1123201.75 | 26397887.27 | 8395.00 | 365.00 | 0.00 | 365.17 |
ROOM_4_MULT19_FLR_3 | 19803829.30 | 29806.66 | 19833635.95 | 23283.19 | 19856919.15 | 26405105.73 | 2190.00 | 6240.72 | 329.28 | 0.00 |
ROOM_5_FLR_3 | 1460156.71 | 28006.37 | 1488163.08 | 83426.14 | 1571589.23 | 1946875.62 | 2190.00 | 6236.00 | 334.00 | 0.00 |
ROOM_6_FLR_3 | 1459985.63 | 30965.98 | 1490951.61 | 83419.78 | 1574371.39 | 1946647.51 | 2190.00 | 6237.08 | 332.92 | 0.00 |
CORRIDOR_FLR_3 | 25876503.19 | 0.00 | 25876503.19 | 100878.99 | 25977382.19 | 14972100.18 | 0.00 | 0.00 | 8760.00 | 0.00 |
ROOM_1_FLR_6 | 365039.18 | 31780.42 | 396819.60 | 83443.72 | 480263.32 | 486718.90 | 2086.56 | 6238.14 | 435.30 | 0.00 |
ROOM_2_FLR_6 | 364996.41 | 20329.68 | 385326.08 | 83437.36 | 468763.44 | 486661.88 | 2134.97 | 6371.19 | 253.84 | 0.00 |
ROOM_3_MULT9_FLR_6 | 2345190.31 | 31705.65 | 2376895.96 | 42692.73 | 2419588.69 | 3126920.42 | 2190.00 | 6236.17 | 333.83 | 0.00 |
BANQUET_FLR_6 | 40474385.28 | 0.00 | 40474385.28 | 203748.60 | 40678133.88 | 37458366.31 | 3953.72 | 181.59 | 4624.69 | 0.00 |
DINING_FLR_6 | 44213166.41 | 0.00 | 44213166.41 | 203748.60 | 44416915.01 | 37458366.31 | 2593.24 | 224.20 | 5942.56 | 0.00 |
KITCHEN_FLR_6 | 59569834.16 | 0.00 | 59569834.16 | 182402.23 | 59752236.39 | 11584760.86 | 0.00 | 0.00 | 8760.00 | 0.00 |
CORRIDOR_FLR_6 | 13274877.42 | 0.00 | 13274877.42 | 178525.13 | 13453402.54 | 3961413.96 | 0.00 | 0.00 | 8760.00 | 0.00 |
Total Facility | 0.21E+10 | 3036881.21 | 0.21E+10 | 8406955.38 | 0.21E+10 | 0.43E+10 | 8760.00 | 6874.36 | 8760.00 | 365.17 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 1.2892 | 0.0000 | 1.2892 | 0.0000 | 1.2892 | 0.8545 | 0.00 | 0.00 | 8760.00 |
RETAIL_1_FLR_1 | 0.2318 | 0.0000 | 0.2318 | 0.0046 | 0.2364 | 0.0792 | 0.00 | 0.00 | 8760.00 |
RETAIL_2_FLR_1 | 0.1185 | 0.0000 | 0.1185 | 0.0018 | 0.1202 | 0.0917 | 0.00 | 0.00 | 8760.00 |
MECH_FLR_1 | 0.0865 | 0.0000 | 0.0865 | 0.0042 | 0.0907 | 0.0000 | 0.00 | 0.00 | 8760.00 |
STORAGE_FLR_1 | 0.0511 | 0.0000 | 0.0511 | 0.0024 | 0.0535 | 0.0578 | 8760.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 1.9656 | 0.0000 | 1.9656 | 0.0057 | 1.9713 | 0.0000 | 0.00 | 0.00 | 8760.00 |
CAFE_FLR_1 | 0.9222 | 0.0000 | 0.9222 | 0.0101 | 0.9323 | 0.6764 | 0.00 | 0.00 | 8760.00 |
LOBBY_FLR_1 | 2.6548 | 0.0000 | 2.6548 | 0.0288 | 2.6836 | 1.8940 | 0.00 | 0.00 | 8760.00 |
ROOM_1_FLR_3 | 0.0463 | 0.0009 | 0.0472 | 0.0026 | 0.0498 | 0.0617 | 2190.00 | 6236.00 | 334.00 |
ROOM_2_FLR_3 | 0.0463 | 0.0007 | 0.0470 | 0.0026 | 0.0496 | 0.0617 | 2190.00 | 6339.69 | 230.31 |
ROOM_4_MULT19_FLR_3 | 0.6280 | 0.0009 | 0.6289 | 0.0007 | 0.6297 | 0.8373 | 2190.00 | 6240.72 | 329.28 |
ROOM_5_FLR_3 | 0.0463 | 0.0009 | 0.0472 | 0.0026 | 0.0498 | 0.0617 | 2190.00 | 6236.00 | 334.00 |
ROOM_6_FLR_3 | 0.0463 | 0.0010 | 0.0473 | 0.0026 | 0.0499 | 0.0617 | 2190.00 | 6237.08 | 332.92 |
CORRIDOR_FLR_3 | 0.8205 | 0.0000 | 0.8205 | 0.0032 | 0.8237 | 0.4748 | 0.00 | 0.00 | 8760.00 |
ROOM_1_FLR_6 | 0.0116 | 0.0010 | 0.0126 | 0.0026 | 0.0152 | 0.0154 | 2086.56 | 6238.14 | 435.30 |
ROOM_2_FLR_6 | 0.0116 | 0.0006 | 0.0122 | 0.0026 | 0.0149 | 0.0154 | 2134.97 | 6371.19 | 253.84 |
ROOM_3_MULT9_FLR_6 | 0.0744 | 0.0010 | 0.0754 | 0.0014 | 0.0767 | 0.0992 | 2190.00 | 6236.17 | 333.83 |
BANQUET_FLR_6 | 1.2834 | 0.0000 | 1.2834 | 0.0065 | 1.2899 | 1.1878 | 3953.72 | 181.59 | 4624.69 |
DINING_FLR_6 | 1.4020 | 0.0000 | 1.4020 | 0.0065 | 1.4085 | 1.1878 | 2593.24 | 224.20 | 5942.56 |
KITCHEN_FLR_6 | 1.8889 | 0.0000 | 1.8889 | 0.0058 | 1.8947 | 0.3674 | 0.00 | 0.00 | 8760.00 |
CORRIDOR_FLR_6 | 0.4209 | 0.0000 | 0.4209 | 0.0057 | 0.4266 | 0.1256 | 0.00 | 0.00 | 8760.00 |
Total Facility | 64.7565 | 0.0963 | 64.8528 | 0.2105 | 65.0633 | 73.9670 | 8760.00 | 6874.36 | 8760.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
FLR_3_DOAS | 42324470.08 | 221917.87 | 42546387.95 | 64690340.46 | 8759.83 | 0.17 | 0.00 | 0.00 |
VAV WITH REHEAT | 0.59E+09 | 0.00 | 0.59E+09 | 0.22E+09 | 0.00 | 0.00 | 8760.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
FLR_3_DOAS | 1.3421 | 0.0070 | 1.3491 | 2.0513 | 8759.83 | 0.17 | 0.00 |
VAV WITH REHEAT | 18.6442 | 0.0000 | 18.6442 | 6.9969 | 0.00 | 0.00 | 8760.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
FLR_3_DOAS | 0.00 | 0.00 | 0.00 | 0.00 | 6935.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
VAV WITH REHEAT | 0.00 | 0.00 | 4441.86 | 0.00 | 0.00 | 0.00 | 4318.14 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
FLR_3_DOAS | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.6953 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
VAV WITH REHEAT | 0.0000 | 0.0000 | 18.7844 | 0.0000 | 0.0000 | 0.0000 | 18.5043 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:19
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1333 |
Defaulted Fields | 1182 |
Fields with Defaults | 4000 |
Autosized Fields | 349 |
Autosizable Fields | 402 |
Autocalculated Fields | 280 |
Autocalculatable Fields | 539 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:25:19
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 4536.32 | 64575.35 | 13-MAY-04:50 | 314153.84 | 22-JUL-18:20 |
Electricity:Building | 2447.36 | 31087.76 | 01-JUL-05:00 | 151313.73 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 304.40 | 3493.55 | 02-JAN-02:10 | 22822.84 | 02-JAN-20:10 |
Electricity:SpaceType:GENERAL | 2440.27 | 30946.61 | 01-JUL-05:00 | 151072.40 | 02-JAN-20:10 |
InteriorLights:Electricity | 782.09 | 6744.64 | 01-JUL-05:00 | 64632.59 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 161.29 | 1465.65 | 02-JAN-02:10 | 13190.31 | 02-JAN-20:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 782.09 | 6744.64 | 01-JUL-05:00 | 64632.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 782.09 | 6744.64 | 01-JUL-05:00 | 64632.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 161.29 | 1465.65 | 02-JAN-02:10 | 13190.31 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 782.09 | 6744.64 | 01-JUL-05:00 | 64632.59 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 17.49 | 210.74 | 02-JAN-02:10 | 1283.20 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 7.31 | 66.40 | 02-JAN-02:10 | 597.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 7.31 | 66.40 | 02-JAN-02:10 | 597.59 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 20.26 | 244.03 | 02-JAN-02:10 | 1485.95 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 8.46 | 76.89 | 02-JAN-02:10 | 692.02 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 8.46 | 76.89 | 02-JAN-02:10 | 692.02 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 20.84 | 252.75 | 02-JAN-02:10 | 1523.62 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.37 | 76.02 | 02-JAN-02:10 | 684.18 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.37 | 76.02 | 02-JAN-02:10 | 684.18 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 6.68 | 78.96 | 02-JAN-02:10 | 493.99 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 3.08 | 27.98 | 02-JAN-02:10 | 251.84 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 3.08 | 27.98 | 02-JAN-02:10 | 251.84 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 71.91 | 998.82 | 02-JAN-02:10 | 4897.88 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 3.98 | 36.12 | 02-JAN-02:10 | 325.08 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 3.98 | 36.12 | 02-JAN-02:10 | 325.08 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 28.44 | 293.96 | 10-JUN-05:00 | 2666.80 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 14.10 | 83.19 | 01-JAN-13:10 | 1701.53 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 | 14.10 | 83.19 | 01-JAN-13:10 | 1701.53 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 258.92 | 3093.58 | 01-JUL-05:00 | 19534.01 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 109.92 | 982.16 | 01-JUL-05:00 | 9504.80 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 109.92 | 982.16 | 01-JUL-05:00 | 9504.80 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 19.72 | 257.38 | 01-JAN-02:10 | 1438.51 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 19.72 | 257.35 | 01-JAN-02:10 | 1438.34 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 305.38 | 4267.82 | 01-JAN-02:10 | 22404.45 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 110.39 | 934.58 | 01-JAN-02:10 | 8496.21 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 110.39 | 934.58 | 01-JAN-02:10 | 8496.21 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 305.47 | 4268.99 | 01-JAN-02:10 | 22410.58 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 110.42 | 934.84 | 01-JAN-02:10 | 8498.53 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 110.42 | 934.84 | 01-JAN-02:10 | 8498.53 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 19.72 | 257.38 | 01-JAN-02:10 | 1438.51 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 9.24 | 78.27 | 01-JAN-02:10 | 711.53 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 19.72 | 257.35 | 01-JAN-02:10 | 1438.34 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 9.24 | 78.26 | 01-JAN-02:10 | 711.45 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 91.34 | 829.92 | 02-JAN-02:10 | 7469.27 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 4.93 | 64.34 | 01-JAN-02:10 | 359.63 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 2.31 | 19.57 | 01-JAN-02:10 | 177.88 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 2.31 | 19.57 | 01-JAN-02:10 | 177.88 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 4.93 | 64.34 | 01-JAN-02:10 | 359.59 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 2.31 | 19.56 | 01-JAN-02:10 | 177.86 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 2.31 | 19.56 | 01-JAN-02:10 | 177.86 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 36.17 | 505.54 | 01-JAN-02:10 | 2653.88 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 13.08 | 110.70 | 01-JAN-02:10 | 1006.40 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 13.08 | 110.70 | 01-JAN-02:10 | 1006.40 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 206.68 | 2448.50 | 20-MAY-05:00 | 9735.93 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 30.82 | 199.20 | 20-MAY-05:00 | 2988.03 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 30.82 | 199.20 | 20-MAY-05:00 | 2988.03 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 206.68 | 2448.50 | 20-MAY-05:00 | 9735.93 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 30.82 | 199.20 | 20-MAY-05:00 | 2988.03 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 | 30.82 | 199.20 | 20-MAY-05:00 | 2988.03 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 453.81 | 6249.79 | 02-JAN-02:10 | 18934.39 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 12.97 | 117.87 | 02-JAN-02:10 | 1060.81 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 12.97 | 117.87 | 02-JAN-02:10 | 1060.81 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 24.17 | 219.59 | 02-JAN-02:10 | 1976.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1658.18 | 24201.97 | 02-JAN-02:10 | 89171.45 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 1658.18 | 24201.97 | 02-JAN-02:10 | 89171.45 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 433.74 | 5990.78 | 01-JAN-00:10 | 16487.34 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 410.33 | 5248.28 | 01-JAN-00:10 | 15744.84 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
Refrigeration:Electricity | 61.91 | 1114.65 | 10-JAN-23:30 | 3264.88 | 27-JUN-06:20 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
Electricity:Plant | 439.85 | 2727.27 | 15-APR-02:50 | 124272.39 | 22-JUL-18:20 |
LowTempRefrigeration:Refrigeration:Electricity | 20.45 | 0.00 | 01-JAN-11:10 | 1894.38 | 23-JUL-10:50 |
MedTempRefrigeration:Refrigeration:Electricity | 34.36 | 975.26 | 11-JAN-04:10 | 1202.65 | 08-AUG-13:10 |
Fans:Electricity | 495.37 | 11775.86 | 30-DEC-08:10 | 30864.56 | 26-JUN-21:10 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 663.62 | 12546.53 | 06-NOV-15:00 | 36839.87 | 22-JUL-18:20 |
ExteriorEquipment:Electricity | 813.77 | 9999.82 | 02-JAN-02:20 | 49607.07 | 02-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 21.77 | 380.96 | 01-JUL-05:00 | 1291.59 | 02-JAN-21:10 |
ElectricityPurchased:Facility | 4536.32 | 64575.35 | 13-MAY-04:50 | 314153.84 | 22-JUL-18:20 |
ElectricityPurchased:Plant | 4536.32 | 64575.35 | 13-MAY-04:50 | 314153.84 | 22-JUL-18:20 |
Cogeneration:ElectricityPurchased | 4536.32 | 64575.35 | 13-MAY-04:50 | 314153.84 | 22-JUL-18:20 |
General:Cogeneration:ElectricityPurchased | 4536.32 | 64575.35 | 13-MAY-04:50 | 314153.84 | 22-JUL-18:20 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 4536.32 | 64575.35 | 13-MAY-04:50 | 314153.84 | 22-JUL-18:20 |
ElectricityNet:Plant | 4536.32 | 64575.35 | 13-MAY-04:50 | 314153.84 | 22-JUL-18:20 |
Cogeneration:ElectricityNet | 4536.32 | 64575.35 | 13-MAY-04:50 | 314153.84 | 22-JUL-18:20 |
General:Cogeneration:ElectricityNet | 4536.32 | 64575.35 | 13-MAY-04:50 | 314153.84 | 22-JUL-18:20 |
General:Fans:Electricity | 495.37 | 11775.86 | 30-DEC-08:10 | 30864.56 | 26-JUN-21:10 |
ExteriorLights:Electricity | 193.49 | 0.00 | 01-JAN-08:20 | 12338.45 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 193.49 | 0.00 | 01-JAN-08:20 | 12338.45 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 789.09 | 9600.00 | 01-JAN-00:10 | 48128.80 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 2.91 | 18.80 | 01-JAN-00:10 | 188.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 146.48 | 0.00 | 06-JAN-11:40 | 9938.94 | 01-JAN-00:10 |
General:HeatRecovery:Electricity | 146.48 | 0.00 | 06-JAN-11:40 | 9938.94 | 01-JAN-00:10 |
WaterSystems:Electricity | 94.78 | 1222.49 | 21-AUG-00:20 | 4751.13 | 13-JAN-08:00 |
Water Heater:WaterSystems:Electricity | 94.78 | 1222.49 | 21-AUG-00:20 | 4751.13 | 13-JAN-08:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 215.86 | 0.00 | 01-JAN-00:10 | 112941.32 | 22-JUL-18:20 |
General:Cooling:Electricity | 215.86 | 0.00 | 01-JAN-00:10 | 112941.32 | 22-JUL-18:20 |
Pumps:Electricity | 74.39 | 54.18 | 06-MAY-07:10 | 4842.51 | 14-AUG-18:30 |
General:Pumps:Electricity | 74.39 | 54.18 | 06-MAY-07:10 | 4842.51 | 14-AUG-18:30 |
WIRED_LTG_ELECTRICITY | 27.53 | 0.00 | 01-JAN-00:10 | 2275.07 | 02-JAN-20:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 6046.70 | 25792.95 | 22-JUL-02:10 | 544936.28 | 26-JAN-18:40 |
NaturalGas:Building | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Laundry:InteriorEquipment:NaturalGas | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
NaturalGas:Plant | 4257.86 | 12430.88 | 22-JUL-01:00 | 440687.96 | 26-JAN-18:40 |
WaterSystems:NaturalGas | 2791.64 | 12426.78 | 12-AUG-02:30 | 254045.25 | 15-FEB-21:20 |
Water Heater:WaterSystems:NaturalGas | 2791.64 | 12426.78 | 12-AUG-02:30 | 254045.25 | 15-FEB-21:20 |
Heating:NaturalGas | 1466.22 | 0.00 | 04-FEB-16:00 | 204998.76 | 19-FEB-11:50 |
Boiler:Heating:NaturalGas | 1466.22 | 0.00 | 04-FEB-16:00 | 204998.76 | 19-FEB-11:50 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 915.12 | 0.00 | 01-JAN-00:10 | 422229.91 | 25-JUN-18:10 |
PlantLoopCoolingDemand:HVAC | 915.12 | 0.00 | 01-JAN-00:10 | 422229.91 | 25-JUN-18:10 |
CoolingCoils:PlantLoopCoolingDemand | 915.12 | 0.00 | 01-JAN-00:10 | 422229.91 | 25-JUN-18:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 9857.19 | 0.00 | 02-JAN-01:20 | 0.00 | 27-APR-20:10 |
Water:Plant | 9857.19 | 0.00 | 02-JAN-01:20 | 0.00 | 27-APR-20:10 |
WaterSystems:Water | 9857.19 | 0.00 | 02-JAN-01:20 | 0.00 | 27-APR-20:10 |
Water Heater:WaterSystems:Water | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:10 |
MainsWater:Facility | 9857.19 | 0.00 | 02-JAN-01:20 | 0.00 | 27-APR-20:10 |
MainsWater:Plant | 9857.19 | 0.00 | 02-JAN-01:20 | 0.00 | 27-APR-20:10 |
WaterSystems:MainsWater | 9857.19 | 0.00 | 02-JAN-01:20 | 0.00 | 27-APR-20:10 |
Water Heater:WaterSystems:MainsWater | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:10 |
WaterUse:WaterSystems:Water | 4114.69 | 0.00 | 02-JAN-01:20 | 0.00 | 22-MAY-07:00 |
WaterUse:WaterSystems:MainsWater | 4114.69 | 0.00 | 02-JAN-01:20 | 0.00 | 22-MAY-07:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 13554.90 | 135734.56 | 17-OCT-13:20 | 1703210.80 | 22-JUL-18:20 |
EnergyTransfer:Building | 4680.42 | 83277.84 | 10-DEC-15:00 | 331459.21 | 22-JUL-18:20 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 717.26 | 11419.11 | 11-JAN-04:00 | 36407.74 | 23-JUL-10:40 |
Refrigeration:EnergyTransfer | 183.16 | 4017.18 | 10-JAN-23:10 | 10378.94 | 27-JUN-06:20 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 91.58 | 2008.59 | 10-JAN-23:10 | 5189.47 | 27-JUN-06:20 |
General:Refrigeration:EnergyTransfer | 91.58 | 2008.59 | 10-JAN-23:10 | 5189.47 | 27-JUN-06:20 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 91.58 | 2008.59 | 10-JAN-23:10 | 5189.47 | 27-JUN-06:20 |
EnergyTransfer:Plant | 4046.37 | 16053.58 | 14-APR-02:20 | 985374.44 | 25-JUN-18:10 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 21.61 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 69.98 | 1875.77 | 11-JAN-04:10 | 2557.95 | 08-AUG-13:10 |
EnergyTransfer:Zone:BASEMENT | 387.79 | 10326.65 | 20-MAR-14:00 | 17846.80 | 06-OCT-21:00 |
Heating:EnergyTransfer | 77.94 | 0.00 | 01-JAN-08:10 | 44584.80 | 12-JAN-16:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 77.94 | 0.00 | 01-JAN-08:10 | 44584.80 | 12-JAN-16:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 4510.90 | 77527.15 | 27-DEC-15:00 | 327894.92 | 22-JUL-18:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 387.79 | 10326.65 | 20-MAR-14:00 | 17846.80 | 06-OCT-21:00 |
General:Cooling:EnergyTransfer | 4510.90 | 77527.15 | 27-DEC-15:00 | 327894.92 | 22-JUL-18:20 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 387.79 | 10326.65 | 20-MAR-14:00 | 17846.80 | 06-OCT-21:00 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 36.84 | 0.01 | 04-DEC-08:00 | 3973.35 | 27-SEP-13:20 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.16 | 0.00 | 01-JAN-00:10 | 472.50 | 10-JAN-08:00 |
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.16 | 0.00 | 01-JAN-00:10 | 472.50 | 10-JAN-08:00 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 36.68 | 0.00 | 03-JAN-07:10 | 3973.35 | 27-SEP-13:20 |
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 36.68 | 0.00 | 03-JAN-07:10 | 3973.35 | 27-SEP-13:20 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 32.41 | 501.15 | 10-DEC-16:00 | 1702.79 | 21-JUL-21:00 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 32.41 | 501.15 | 10-DEC-16:00 | 1702.79 | 21-JUL-21:00 |
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 32.41 | 501.15 | 10-DEC-16:00 | 1702.79 | 21-JUL-21:00 |
EnergyTransfer:Zone:MECH_FLR_1 | 21.12 | 11.07 | 12-JAN-14:30 | 1106.88 | 23-JUL-10:40 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 21.12 | 11.07 | 12-JAN-14:30 | 1106.88 | 23-JUL-10:40 |
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 21.12 | 11.07 | 12-JAN-14:30 | 1106.88 | 23-JUL-10:40 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 10.86 | 0.10 | 09-JAN-09:40 | 641.87 | 23-JUL-10:40 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.02 | 0.00 | 01-JAN-00:10 | 125.52 | 12-JAN-15:00 |
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.02 | 0.00 | 01-JAN-00:10 | 125.52 | 12-JAN-15:00 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 10.85 | 0.00 | 03-JAN-11:50 | 641.87 | 23-JUL-10:40 |
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 10.85 | 0.00 | 03-JAN-11:50 | 641.87 | 23-JUL-10:40 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 591.71 | 9805.91 | 30-DEC-06:00 | 38354.92 | 13-JUN-20:00 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 591.71 | 9805.91 | 30-DEC-06:00 | 38354.92 | 13-JUN-20:00 |
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 591.71 | 9805.91 | 30-DEC-06:00 | 38354.92 | 13-JUN-20:00 |
EnergyTransfer:Zone:CAFE_FLR_1 | 230.52 | 1020.36 | 10-DEC-16:00 | 13962.76 | 23-SEP-12:30 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 230.52 | 1020.36 | 10-DEC-16:00 | 13962.76 | 23-SEP-12:30 |
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 230.52 | 1020.36 | 10-DEC-16:00 | 13962.76 | 23-SEP-12:30 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 755.87 | 12091.37 | 10-DEC-16:00 | 35847.30 | 12-SEP-21:10 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 755.87 | 12091.37 | 10-DEC-16:00 | 35847.30 | 12-SEP-21:10 |
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 755.87 | 12091.37 | 10-DEC-16:00 | 35847.30 | 12-SEP-21:10 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 44.50 | 0.00 | 01-JAN-08:10 | 11200.66 | 13-JUN-18:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 11.14 | 0.00 | 01-JAN-08:10 | 4058.08 | 27-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 11.14 | 0.00 | 01-JAN-08:10 | 4058.08 | 27-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 33.35 | 0.00 | 01-JAN-00:10 | 11200.66 | 13-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 33.35 | 0.00 | 01-JAN-00:10 | 11200.66 | 13-JUN-18:10 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 36.22 | 0.00 | 01-JAN-08:10 | 11639.83 | 15-JUN-18:30 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 14.34 | 0.00 | 01-JAN-08:10 | 4342.41 | 27-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 14.34 | 0.00 | 01-JAN-08:10 | 4342.41 | 27-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 21.88 | 0.00 | 01-JAN-00:10 | 11639.83 | 15-JUN-18:30 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 21.88 | 0.00 | 01-JAN-00:10 | 11639.83 | 15-JUN-18:30 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 221.70 | 0.00 | 01-JAN-00:10 | 52903.14 | 27-SEP-13:20 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 221.70 | 0.00 | 01-JAN-00:10 | 52903.14 | 27-SEP-13:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 221.70 | 0.00 | 01-JAN-00:10 | 52903.14 | 27-SEP-13:20 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 276.81 | 0.00 | 01-JAN-08:10 | 64627.23 | 06-JUL-20:50 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 7.14 | 0.00 | 01-JAN-00:10 | 23188.82 | 11-JAN-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 7.14 | 0.00 | 01-JAN-00:10 | 23188.82 | 11-JAN-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 269.67 | 0.00 | 01-JAN-08:10 | 64627.23 | 06-JUL-20:50 |
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 269.67 | 0.00 | 01-JAN-08:10 | 64627.23 | 06-JUL-20:50 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 44.85 | 0.00 | 01-JAN-08:10 | 10505.08 | 23-JUL-08:10 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 11.15 | 0.00 | 01-JAN-08:10 | 4080.45 | 30-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 11.15 | 0.00 | 01-JAN-08:10 | 4080.45 | 30-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 33.70 | 0.00 | 01-JAN-00:10 | 10505.08 | 23-JUL-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 33.70 | 0.00 | 01-JAN-00:10 | 10505.08 | 23-JUL-08:10 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 37.26 | 0.00 | 01-JAN-08:10 | 11682.40 | 22-JUL-08:50 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 14.23 | 0.00 | 01-JAN-08:10 | 4388.28 | 12-JAN-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 14.23 | 0.00 | 01-JAN-08:10 | 4388.28 | 12-JAN-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 23.03 | 0.00 | 01-JAN-00:10 | 11682.40 | 22-JUL-08:50 |
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 23.03 | 0.00 | 01-JAN-00:10 | 11682.40 | 22-JUL-08:50 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 176.07 | 0.12 | 15-DEC-10:30 | 10184.01 | 23-JUL-10:40 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.02 | 0.00 | 01-JAN-00:10 | 698.73 | 10-DEC-16:00 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.02 | 0.00 | 01-JAN-00:10 | 698.73 | 10-DEC-16:00 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 176.05 | 0.00 | 03-JAN-14:00 | 10184.01 | 23-JUL-10:40 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 176.05 | 0.00 | 03-JAN-14:00 | 10184.01 | 23-JUL-10:40 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 13.02 | 0.00 | 01-JAN-08:10 | 3035.99 | 13-JUN-18:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 4.87 | 0.00 | 01-JAN-08:10 | 1385.93 | 27-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 4.87 | 0.00 | 01-JAN-08:10 | 1385.93 | 27-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 8.15 | 0.00 | 01-JAN-00:10 | 3035.99 | 13-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 8.15 | 0.00 | 01-JAN-00:10 | 3035.99 | 13-JUN-18:10 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 11.28 | 0.00 | 01-JAN-08:10 | 3196.36 | 15-JUN-18:20 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 5.96 | 0.00 | 01-JAN-08:10 | 1403.97 | 27-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 5.96 | 0.00 | 01-JAN-08:10 | 1403.97 | 27-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 5.32 | 0.00 | 01-JAN-00:10 | 3196.36 | 15-JUN-18:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 5.32 | 0.00 | 01-JAN-00:10 | 3196.36 | 15-JUN-18:20 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 67.85 | 0.00 | 01-JAN-08:10 | 16771.13 | 12-SEP-15:10 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 8.92 | 0.00 | 01-JAN-08:10 | 6022.71 | 10-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 8.92 | 0.00 | 01-JAN-08:10 | 6022.71 | 10-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 58.93 | 0.00 | 01-JAN-00:10 | 16771.13 | 12-SEP-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 58.93 | 0.00 | 01-JAN-00:10 | 16771.13 | 12-SEP-15:10 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 417.43 | 8533.47 | 12-JAN-15:00 | 21365.07 | 21-JUL-21:10 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 417.43 | 8533.47 | 12-JAN-15:00 | 21365.07 | 21-JUL-21:10 |
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 417.43 | 8533.47 | 12-JAN-15:00 | 21365.07 | 21-JUL-21:10 |
EnergyTransfer:Zone:DINING_FLR_6 | 461.35 | 9548.16 | 12-JAN-15:00 | 22774.28 | 21-JUL-21:20 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 461.35 | 9548.16 | 12-JAN-15:00 | 22774.28 | 21-JUL-21:20 |
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 461.35 | 9548.16 | 12-JAN-15:00 | 22774.28 | 21-JUL-21:20 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 625.68 | 9298.93 | 11-JAN-04:00 | 31325.05 | 23-JUL-10:40 |
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 625.68 | 9298.93 | 11-JAN-04:00 | 31325.05 | 23-JUL-10:40 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 87.70 | 0.51 | 12-JAN-07:20 | 5432.49 | 23-JUL-10:50 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 359.90 | 10-JAN-08:00 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 359.90 | 10-JAN-08:00 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 87.70 | 0.00 | 09-JAN-07:10 | 5432.49 | 23-JUL-10:50 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 87.70 | 0.00 | 09-JAN-07:10 | 5432.49 | 23-JUL-10:50 |
PlantLoopHeatingDemand:Facility | 1797.76 | 10547.60 | 21-AUG-02:00 | 180283.07 | 22-NOV-07:30 |
PlantLoopHeatingDemand:Plant | 815.81 | 10545.29 | 16-AUG-00:20 | 56884.51 | 14-FEB-07:20 |
WaterSystems:PlantLoopHeatingDemand | 815.81 | 10545.29 | 16-AUG-00:20 | 56884.51 | 14-FEB-07:20 |
General:WaterSystems:PlantLoopHeatingDemand | 815.81 | 10545.29 | 16-AUG-00:20 | 56884.51 | 14-FEB-07:20 |
EnergyTransfer:HVAC | 4828.11 | 493.04 | 08-SEP-14:50 | 453638.29 | 10-JAN-22:10 |
HeatingCoils:EnergyTransfer | 981.94 | 0.00 | 04-FEB-16:00 | 158590.48 | 16-DEC-16:10 |
PlantLoopHeatingDemand:HVAC | 981.94 | 0.00 | 04-FEB-16:00 | 158590.48 | 16-DEC-16:10 |
HeatingCoils:PlantLoopHeatingDemand | 981.94 | 0.00 | 04-FEB-16:00 | 158590.48 | 16-DEC-16:10 |
CoolingCoils:EnergyTransfer | 915.12 | 0.00 | 01-JAN-00:10 | 422229.91 | 25-JUN-18:10 |
HeatRecoveryForHeating:EnergyTransfer | 2929.91 | 0.00 | 06-JAN-11:40 | 401694.60 | 17-FEB-07:00 |
HeatRecoveryForCooling:EnergyTransfer | 1.13 | 0.00 | 01-JAN-00:10 | 31600.62 | 22-JUL-15:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 815.81 | 10545.29 | 16-AUG-00:20 | 56884.51 | 14-FEB-07:20 |
WaterUse:WaterSystems:EnergyTransfer | 815.81 | 10545.29 | 16-AUG-00:20 | 56884.51 | 14-FEB-07:20 |
Boilers:EnergyTransfer | 974.65 | 0.00 | 04-FEB-16:00 | 158724.28 | 16-DEC-16:10 |
Chillers:EnergyTransfer | 974.23 | 0.00 | 01-JAN-00:10 | 423615.47 | 25-JUN-18:10 |
HeatRejection:EnergyTransfer | 1190.10 | 0.00 | 01-JAN-00:10 | 526718.11 | 25-JUN-18:10 |
General:HeatRejection:EnergyTransfer | 1190.10 | 0.00 | 01-JAN-00:10 | 526718.11 | 25-JUN-18:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:19
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -387.795 | 0.000 | 0.000 | 140.229 | 161.294 | 143.105 | 0.000 | 0.000 | 0.000 | 0.001 | 0.000 | 0.000 | 0.000 | 0.000 | -56.834 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 0.157 | -36.679 | 0.000 | 0.000 | 15.946 | 7.307 | 10.186 | 22.094 | 0.000 | 0.002 | 0.000 | 0.000 | -11.457 | 0.000 | -2.129 | -5.427 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.000 | -32.407 | 0.000 | 0.000 | 17.145 | 8.462 | 11.795 | 0.000 | 0.000 | 0.001 | 0.000 | 0.000 | 0.000 | 0.000 | -0.894 | -4.102 |
MECH_FLR_1 | 0.000 | 0.000 | 0.000 | -21.118 | 0.000 | 0.000 | 3.759 | 8.366 | 12.471 | 0.000 | 0.000 | 0.002 | 0.000 | 0.000 | 0.000 | 0.000 | -2.029 | -1.452 |
STORAGE_FLR_1 | 0.000 | 0.000 | 0.015 | -10.849 | 0.000 | 0.000 | 2.936 | 3.079 | 3.598 | 0.000 | 0.000 | 0.002 | 2.366 | 0.000 | 0.000 | 0.000 | -1.147 | -0.000 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.000 | -591.711 | 0.000 | 0.000 | 11.253 | 3.975 | 658.131 | 0.000 | 0.000 | 0.004 | 0.000 | 0.000 | 0.000 | 0.000 | -3.008 | -78.644 |
CAFE_FLR_1 | 0.000 | 0.000 | 0.000 | -230.525 | 0.000 | 0.000 | 198.923 | 14.100 | 14.341 | 61.382 | 0.000 | 0.005 | 0.000 | 0.000 | -33.962 | 0.000 | -4.985 | -19.280 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.000 | -755.870 | 0.000 | 0.000 | 565.752 | 109.921 | 148.998 | 80.719 | 0.000 | 0.015 | 0.000 | 0.000 | -47.100 | 0.000 | -14.942 | -87.494 |
ROOM_1_FLR_3 | 15.825 | -27.801 | 0.000 | -10.234 | 0.000 | 0.000 | 9.728 | 9.244 | 10.478 | 41.179 | 0.000 | 0.015 | 0.000 | 0.000 | -26.020 | 0.000 | -5.484 | -16.930 |
ROOM_2_FLR_3 | 19.422 | -16.367 | 0.000 | -10.587 | 0.000 | 0.000 | 9.640 | 9.243 | 10.477 | 28.104 | 0.000 | 0.008 | 0.000 | 0.000 | -26.433 | 0.000 | -5.609 | -17.899 |
ROOM_3_MULT19_FLR_3 | 0.000 | -207.677 | 0.000 | -14.016 | 0.000 | 0.000 | 0.000 | 110.385 | 194.997 | 243.082 | 0.000 | 0.004 | 0.018 | 0.000 | -187.165 | 0.000 | -35.510 | -104.100 |
ROOM_4_MULT19_FLR_3 | 32.620 | -154.554 | 0.000 | -140.590 | 0.000 | 0.000 | 184.056 | 110.415 | 195.050 | 66.331 | 0.000 | 0.073 | 0.000 | 0.000 | -145.956 | 0.000 | -39.249 | -108.196 |
ROOM_5_FLR_3 | 15.772 | -28.078 | 0.000 | -10.241 | 0.000 | 0.000 | 9.721 | 9.244 | 10.478 | 41.608 | 0.000 | 0.016 | 0.000 | 0.000 | -25.559 | 0.000 | -5.494 | -17.466 |
ROOM_6_FLR_3 | 19.232 | -17.563 | 0.000 | -10.471 | 0.000 | 0.000 | 9.680 | 9.243 | 10.477 | 28.439 | 0.000 | 0.008 | 0.000 | 0.000 | -25.708 | 0.000 | -5.795 | -17.542 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 0.020 | -176.055 | 0.000 | 0.000 | 120.730 | 91.336 | 0.000 | 37.287 | 0.000 | 0.008 | 0.000 | 0.000 | -33.250 | 0.000 | -6.137 | -33.938 |
ROOM_1_FLR_6 | 6.206 | -6.931 | 0.000 | -2.555 | 0.000 | 0.000 | 2.436 | 2.311 | 2.620 | 10.232 | 0.000 | 0.004 | 0.000 | 0.000 | -6.435 | 0.000 | -1.389 | -6.498 |
ROOM_2_FLR_6 | 7.368 | -4.072 | 0.000 | -2.657 | 0.000 | 0.000 | 2.409 | 2.311 | 2.619 | 6.960 | 0.000 | 0.002 | 0.000 | 0.000 | -6.544 | 0.000 | -1.398 | -6.997 |
ROOM_3_MULT9_FLR_6 | 14.779 | -48.263 | 0.000 | -16.523 | 0.000 | 0.000 | 21.822 | 13.076 | 23.098 | 56.986 | 0.000 | 0.026 | 0.000 | 0.000 | -30.500 | 0.000 | -7.131 | -27.370 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.000 | -417.436 | 0.000 | 0.000 | 316.144 | 30.820 | 175.857 | 6.410 | 0.000 | 0.002 | 0.000 | 0.000 | -19.812 | 0.000 | -3.630 | -88.355 |
DINING_FLR_6 | 0.000 | 0.000 | 0.000 | -461.356 | 0.000 | 0.000 | 314.953 | 30.820 | 175.857 | 6.181 | 0.000 | 0.002 | 0.000 | 0.000 | -20.369 | 0.000 | -3.658 | -42.430 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.000 | -625.664 | 0.000 | 0.000 | 28.339 | 12.972 | 550.372 | 19.658 | 0.000 | 0.002 | 30.955 | 0.000 | -13.368 | 0.000 | -3.268 | -0.000 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 0.003 | -87.700 | 0.000 | 0.000 | 32.083 | 24.166 | 0.000 | 18.334 | 0.000 | 0.002 | 30.740 | 0.000 | -14.909 | 0.000 | -2.721 | -0.001 |
Total Facility | 131.224 | -511.306 | 0.195 | -4053.041 | 0.000 | 0.000 | 2017.684 | 782.094 | 2365.005 | 774.985 | 0.000 | 0.205 | 64.081 | 0.000 | -674.545 | 0.000 | -155.606 | -740.955 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 06-OCT-21:00 | 0.00 | 0.00 | 0.00 | -17847.76 | 0.00 | 0.00 | 5924.41 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -8926.86 |
RETAIL_1_FLR_1 | 27-SEP-13:20 | 0.00 | 0.00 | 0.00 | -3973.40 | 0.00 | 0.00 | 150.60 | 166.00 | 252.59 | 6001.52 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -14.07 | -2583.23 |
RETAIL_2_FLR_1 | 21-JUL-21:00 | 0.00 | 0.00 | 0.00 | -1702.99 | 0.00 | 0.00 | 697.60 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -14.49 | -347.39 |
MECH_FLR_1 | 23-JUL-10:33 | 0.00 | 0.00 | 0.00 | -1109.59 | 0.00 | 0.00 | 57.71 | 228.06 | 353.45 | 0.00 | 0.00 | 0.00 | 481.63 | 0.00 | -0.00 | 0.00 | -11.26 | 0.00 |
STORAGE_FLR_1 | 23-JUL-10:33 | 0.00 | 0.00 | 0.00 | -643.43 | 0.00 | 0.00 | 44.94 | 83.94 | 101.96 | 0.00 | 0.00 | 0.00 | 418.54 | 0.00 | -0.00 | 0.00 | -5.95 | 0.00 |
LAUNDRY_FLR_1 | 13-JUN-20:00 | 0.00 | 0.00 | 0.00 | -38351.36 | 0.00 | 0.00 | 408.82 | 325.08 | 44299.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -46.63 | -6635.29 |
CAFE_FLR_1 | 23-SEP-12:30 | 0.00 | 0.00 | 0.00 | -13962.63 | 0.00 | 0.00 | 2968.60 | 103.98 | 355.63 | 16719.68 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -59.13 | -6126.13 |
LOBBY_FLR_1 | 12-SEP-21:10 | 0.00 | 0.00 | 0.00 | -35847.76 | 0.00 | 0.00 | 26439.84 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1723.97 | 0.00 | -301.06 | -2293.53 |
ROOM_1_FLR_3 | 11-MAY-18:03 | 0.00 | -13464.27 | 0.00 | -483.50 | 0.00 | 0.00 | 335.50 | 633.26 | 484.65 | 1378.02 | 0.00 | 0.00 | 11612.88 | 0.00 | -0.00 | 0.00 | -496.53 | 0.00 |
ROOM_2_FLR_3 | 28-JUL-17:52 | 0.00 | -14535.80 | 0.00 | 0.00 | 0.00 | 0.00 | 163.95 | 476.67 | 505.67 | 5072.84 | 0.00 | 0.00 | 8474.13 | 0.00 | -0.00 | 0.00 | -157.45 | 0.00 |
ROOM_3_MULT19_FLR_3 | 27-SEP-13:20 | 0.00 | -52927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2378.94 | 2352.88 | 71141.33 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -349.02 | -22596.31 |
ROOM_4_MULT19_FLR_3 | 08-JUN-19:11 | 0.00 | -70860.87 | 0.00 | -7429.70 | 0.00 | 0.00 | 6433.29 | 8498.53 | 12159.85 | 3074.10 | 0.00 | 0.00 | 48720.41 | 0.00 | -0.00 | 0.00 | -595.61 | 0.00 |
ROOM_5_FLR_3 | 11-MAY-18:01 | 0.00 | -13236.12 | 0.00 | -552.16 | 0.00 | 0.00 | 335.50 | 633.26 | 484.65 | 122.15 | 0.00 | 0.00 | 12829.55 | 0.00 | -0.00 | 0.00 | -616.83 | 0.00 |
ROOM_6_FLR_3 | 23-JUL-08:32 | 0.00 | -13750.21 | 0.00 | -1001.26 | 0.00 | 0.00 | 88.64 | 398.41 | 653.15 | 9177.61 | 0.00 | 0.00 | 4521.46 | 0.00 | -0.00 | 0.00 | -87.80 | 0.00 |
CORRIDOR_FLR_3 | 23-JUL-10:33 | 0.00 | 0.00 | 0.00 | -10209.50 | 0.00 | 0.00 | 1860.90 | 2489.76 | 0.00 | 6308.09 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -30.45 | -418.79 |
ROOM_1_FLR_6 | 11-MAY-18:01 | 0.00 | -3795.22 | 0.00 | -137.26 | 0.00 | 0.00 | 83.87 | 158.32 | 121.16 | 337.19 | 0.00 | 0.00 | 3395.16 | 0.00 | -0.00 | 0.00 | -163.21 | 0.00 |
ROOM_2_FLR_6 | 11-JUL-18:52 | 0.00 | -3837.70 | 0.00 | -209.01 | 0.00 | 0.00 | 57.55 | 158.30 | 121.15 | 663.01 | 0.00 | 0.00 | 3086.78 | 0.00 | -0.00 | 0.00 | -40.07 | 0.00 |
ROOM_3_MULT9_FLR_6 | 11-MAY-18:01 | 0.00 | -20993.71 | 0.00 | -872.65 | 0.00 | 0.00 | 754.87 | 895.70 | 1068.37 | 133.41 | 0.00 | 0.00 | 20387.33 | 0.00 | -0.00 | 0.00 | -1373.32 | 0.00 |
BANQUET_FLR_6 | 21-JUL-21:10 | 0.00 | 0.00 | 0.00 | -21363.59 | 0.00 | 0.00 | 15643.99 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -527.96 | 0.00 | -53.95 | -2438.42 |
DINING_FLR_6 | 13-JUN-21:11 | 0.00 | 0.00 | 0.00 | -23233.26 | 0.00 | 0.00 | 15618.46 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -728.26 | 0.00 | -77.44 | -319.41 |
KITCHEN_FLR_6 | 23-JUL-10:40 | 0.00 | 0.00 | 0.00 | -31371.78 | 0.00 | 0.00 | 464.23 | 353.60 | 24259.91 | 3781.32 | 0.00 | 0.00 | 2534.40 | 0.00 | -0.00 | 0.00 | -21.67 | 0.00 |
CORRIDOR_FLR_6 | 23-JUL-10:33 | 0.00 | 0.00 | 0.00 | -5443.48 | 0.00 | 0.00 | 479.44 | 658.76 | 0.00 | 3087.47 | 0.00 | 0.00 | 1234.34 | 0.00 | -0.00 | 0.00 | -16.52 | 0.00 |
Total Facility | 22-JUL-18:02 | 0.00 | -154937.76 | 0.00 | -196431.57 | 0.00 | 0.00 | 64369.16 | 51055.14 | 113378.48 | 61182.57 | 0.00 | 1759.19 | 59624.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 10-JAN-08:00 | 0.00 | 0.00 | 472.38 | 0.00 | 0.00 | 0.00 | 358.03 | 332.00 | 433.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1097.93 | 0.00 | -156.05 | -341.45 |
RETAIL_2_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 12-JAN-15:00 | 0.00 | 0.00 | 125.52 | 0.00 | 0.00 | 0.00 | 33.72 | 69.95 | 89.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -66.17 | -252.24 |
LAUNDRY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 18-APR-08:03 | 5103.84 | 420.94 | 0.00 | -420.94 | 0.00 | 0.00 | 93.27 | 313.07 | 453.05 | 658.89 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -144.43 | -6477.69 |
ROOM_2_FLR_3 | 08-MAY-08:03 | 4897.62 | 421.53 | 0.00 | -421.53 | 0.00 | 0.00 | 93.84 | 313.04 | 452.99 | 672.72 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -156.98 | -6273.23 |
ROOM_3_MULT19_FLR_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 11-JAN-16:02 | 24434.81 | 4357.01 | 0.00 | -4357.01 | 0.00 | 0.00 | 5422.25 | 2379.59 | 3726.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -9760.84 | 0.00 | -1544.41 | -24657.80 |
ROOM_5_FLR_3 | 22-OCT-15:03 | 4895.88 | 421.88 | 0.00 | -421.88 | 0.00 | 0.00 | 140.93 | 234.80 | 221.25 | 1229.89 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -157.46 | -6565.30 |
ROOM_6_FLR_3 | 05-SEP-18:04 | 4821.57 | 420.26 | 0.00 | -420.26 | 0.00 | 0.00 | 335.52 | 633.19 | 484.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -660.50 | 0.00 | -94.29 | -5520.09 |
CORRIDOR_FLR_3 | 10-DEC-16:00 | 0.00 | 0.00 | 698.71 | 0.00 | 0.00 | 0.00 | 1385.80 | 1659.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1930.44 | 0.00 | -266.98 | -1546.93 |
ROOM_1_FLR_6 | 27-DEC-16:13 | 1496.98 | 92.70 | 0.00 | -92.70 | 0.00 | 0.00 | 66.66 | 49.81 | 50.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -417.32 | 0.00 | -57.34 | -1188.84 |
ROOM_2_FLR_6 | 27-DEC-16:13 | 1464.20 | 90.36 | 0.00 | -90.36 | 0.00 | 0.00 | 67.00 | 49.80 | 50.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -412.91 | 0.00 | -56.93 | -1161.21 |
ROOM_3_MULT9_FLR_6 | 10-DEC-16:13 | 7258.79 | 613.88 | 0.00 | -613.88 | 0.00 | 0.00 | 332.96 | 332.11 | 487.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1690.18 | 0.00 | -249.07 | -6472.35 |
BANQUET_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 10-JAN-08:00 | 0.00 | 0.00 | 359.80 | 0.00 | 0.00 | 0.00 | 733.29 | 1097.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1388.80 | 0.00 | -194.53 | -607.68 |
Total Facility | 30-DEC-16:13 | -32710.63 | 92942.07 | 687.52 | -92942.07 | 0.00 | 0.00 | 35266.15 | 19060.81 | 74838.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -38588.15 | 0.00 | -6358.46 | -52195.50 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:19
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV WITH REHEAT | 22.6321 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 22.5098 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV WITH REHEAT | 11.6555 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 11.6555 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.6520 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.0400 | 0.000610 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.000000 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.000000 | 142.3000 | 0.003581 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.000000 | 422.4350 | 0.001448 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 83.8280 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003556 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.1800 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 | |
VAV WITH REHEAT | 0.00 | 0.001045 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.4928 | 2.4928 | 1.2838 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4482 | 0.4482 | 0.2308 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2294 | 0.2294 | 0.1182 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1680 | 0.1680 | 0.0865 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0993 | 0.0993 | 0.0511 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.2738 | 3.2738 | 1.6860 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7850 | 1.7850 | 0.9193 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.1343 | 5.1343 | 2.6442 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5933 | 1.5933 | 0.8205 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1101 | 2.1101 | 1.0867 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2100 | 2.2100 | 1.1382 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2705 | 2.2705 | 1.1693 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8174 | 0.8174 | 0.4209 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
VAV WITH REHEAT | 22.6321 | 22.5098 | 22.6321 | 11.6555 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2838 | 1.2838 | 1.2838 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2308 | 0.2308 | 0.2308 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1182 | 0.1182 | 0.1182 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0865 | 0.0865 | 0.0865 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0511 | 0.0511 | 0.0511 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6860 | 1.6860 | 1.6860 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9193 | 0.9193 | 0.9193 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6442 | 2.6442 | 2.6442 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8205 | 0.8205 | 0.8205 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0867 | 1.0867 | 1.0867 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1382 | 1.1382 | 1.1382 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1693 | 1.1693 | 1.1693 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4209 | 0.4209 | 0.4209 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
VAV WITH REHEAT | 11.6555 | 11.6555 | 11.6555 | 11.6555 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:19
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** William R Fairchild WA USA TMY3 WMO#=727885 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 168.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 168.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 20.83 |
Number of hours cooling loads not met | 27.67 |
Number of hours not met | 48.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 1466.22 | 204998.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 215.86 | 112941.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 782.09 | 64632.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 193.49 | 12338.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 872.72 | 59188.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 14.43 | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 8.99 | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.20 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 21.77 | 1291.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 789.09 | 48128.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 2.91 | 188.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 495.37 | 30864.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 74.39 | 4842.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 146.48 | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 94.78 | 4751.13 | 2791.64 | 254045.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.09 | 2093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 20.45 | 1894.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 34.36 | 1202.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1720.08 | 4536.32 |
Natural Gas | 1788.84 | 6046.70 |
Additional | 0.00 | 0.00 |
Total | 3508.92 | 10583.01 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 68.94 |
Space Heating | 0.00 |
Space Cooling | 19.03 |
Fans (All) | 43.66 |
Service Water Heating | 8.35 |
Receptacle Equipment | 146.16 |
Miscellaneous (All) | 399.84 |
Subtotal | 399.84 |
Natural Gas [MJ/m2] | |
Space Heating | 129.24 |
Service Water Heating | 246.06 |
Miscellaneous (All) | 532.97 |
Subtotal | 532.97 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 7.39 |
Space Heating | 13.85 |
Space Cooling | 2.04 |
Fans (All) | 4.68 |
Service Water Heating | 27.27 |
Receptacle Equipment | 32.57 |
Miscellaneous | 12.19 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 486. | 5110. |
ELEVATOR_STANDBY_SCH | 7671. | 8760. |
LTG_SCH_KITCHEN | 3061. | 8760. |
LTG_SCH_DINING | 3061. | 8760. |
LTG_SCH_BASEMENT | 2572. | 8760. |
LTG_SCH_LOBBY | 2295. | 8760. |
LTG_SCH_STORAGE | 1580. | 8760. |
LTG_SCH_MECHANIC | 3061. | 8760. |
LTG_SCH_LAUNDRY | 3061. | 8760. |
LTG_SCH_GUESTROOM | 1980. | 8760. |
LTG_SCH_CORRIDOR | 2295. | 8760. |
LTG_SCH_RETAIL | 2678. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 1591. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3737. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 5740. | 6205. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 8760. | 8760. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 26.67 | 365 | 26.67 | 365 |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
HTGSETP_SCH | BASEMENT DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:19
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8666.83 | 93.17 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8531.83 | 228.17 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8753.67 | 6.33 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8612.67 | 147.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8531.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 228.17 | 0.00 | 0.00 | 0.00 |
Average | 8738.41 | 21.59 | 0.00 | 0.00 | 0.00 |
Sum | 192245.00 | 475.00 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4127.67 | 26.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4106.67 | 47.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108269.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 47.33 | 0.00 | 0.00 | 0.00 |
Average | 288883.70 | 3.35 | 0.00 | 0.00 | 0.00 |
Sum | 6355441.33 | 73.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8756.67 | 3.33 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8748.00 | 12.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8627.17 | 132.83 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8223.50 | 536.50 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8746.00 | 14.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8575.00 | 185.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8747.83 | 12.17 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8752.17 | 7.83 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8758.33 | 1.67 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8223.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 536.50 | 0.00 | 0.00 | 0.00 |
Average | 8718.85 | 41.15 | 0.00 | 0.00 | 0.00 |
Sum | 191814.67 | 905.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 709990.33 | 426.67 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2110954.00 | 4475.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4097.50 | 56.50 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4152.67 | 1.33 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4073.33 | 80.67 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1243135.50 | 2579.50 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1244052.00 | 1663.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108254.83 | 14.17 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2110954.00 | 4475.00 | 0.00 | 0.00 | 0.00 |
Average | 288464.46 | 422.58 | 0.00 | 0.00 | 0.00 |
Sum | 6346218.17 | 9296.83 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:19
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:19
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 1592.73 | 0.00 | 0.00 |
Sum | 0.00 | 35040.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 710417.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 2115429.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 2115429.00 | 0.00 | 0.00 |
Average | 0.00 | 241694.36 | 0.00 | 0.00 |
Sum | 0.00 | 5317276.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5C
For: Environment
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Environment
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_PORTANGELES
For: Environment
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.320868E+11 | 14141.82 | 20-JAN-21:00 | 1.00 | 0.17 | 0.769615E+10 | 4798.34 | 12-JAN-22:10 | 1.00 | 0.17 |
February | 0.284038E+11 | 13866.90 | 12-FEB-11:33 | 6.00 | 3.75 | 0.684380E+10 | 4733.76 | 01-FEB-22:10 | 6.00 | 3.75 |
March | 0.305852E+11 | 13723.23 | 25-MAR-10:33 | 11.33 | 8.27 | 0.743130E+10 | 4653.07 | 01-MAR-22:10 | 11.33 | 8.27 |
April | 0.304335E+11 | 15032.55 | 30-APR-10:33 | 19.33 | 11.65 | 0.717516E+10 | 4602.41 | 21-APR-22:10 | 19.33 | 11.65 |
May | 0.314605E+11 | 14662.97 | 21-MAY-10:33 | 13.67 | 10.30 | 0.741351E+10 | 4613.93 | 04-MAY-21:10 | 13.67 | 10.30 |
June | 0.313007E+11 | 15262.50 | 25-JUN-10:33 | 20.00 | 13.96 | 0.726882E+10 | 4671.10 | 16-JUN-22:10 | 20.00 | 13.96 |
July | 0.335132E+11 | 15664.44 | 23-JUL-10:33 | 21.00 | 15.99 | 0.765492E+10 | 4787.28 | 28-JUL-22:10 | 12.00 | 11.46 |
August | 0.341096E+11 | 15742.60 | 19-AUG-10:33 | 18.00 | 14.38 | 0.779202E+10 | 4827.52 | 25-AUG-22:10 | 14.83 | 13.13 |
September | 0.339375E+11 | 17084.64 | 29-SEP-21:00 | 12.00 | 7.58 | 0.768848E+10 | 4837.08 | 11-SEP-21:19 | 12.00 | 7.58 |
October | 0.349521E+11 | 17846.80 | 06-OCT-21:00 | 6.00 | 4.60 | 0.800561E+10 | 4837.01 | 27-OCT-21:19 | 8.00 | 8.00 |
November | 0.335936E+11 | 17416.61 | 17-NOV-22:00 | 6.00 | 5.05 | 0.775133E+10 | 4837.02 | 01-NOV-22:10 | 6.00 | 5.05 |
December | 0.334173E+11 | 16511.61 | 01-DEC-22:00 | 4.00 | 3.53 | 0.791097E+10 | 4836.97 | 04-DEC-22:19 | 7.00 | 7.00 |
Annual Sum or Average | 0.387794E+12 | 0.906321E+11 | ||||||||
Minimum of Months | 0.284038E+11 | 13723.23 | 1.00 | 0.17 | 0.684380E+10 | 4602.41 | 1.00 | 0.17 | ||
Maximum of Months | 0.349521E+11 | 17846.80 | 21.00 | 15.99 | 0.800561E+10 | 4837.08 | 20.00 | 13.96 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.157162E+10 | 2626.98 | 21-JAN-11:33 | 6.33 | 5.22 | 0.623323E+09 | 364.15 | 05-JAN-04:49 | 6.33 | 5.22 |
February | 0.176644E+10 | 3075.05 | 04-FEB-13:30 | 9.00 | 6.13 | 0.565256E+09 | 364.16 | 15-FEB-04:00 | 6.00 | 2.58 |
March | 0.164577E+10 | 2138.10 | 25-MAR-10:33 | 11.33 | 8.27 | 0.623054E+09 | 364.21 | 18-MAR-02:09 | 11.33 | 8.27 |
April | 0.371917E+10 | 3244.01 | 29-APR-13:10 | 19.17 | 12.73 | 0.623453E+09 | 418.70 | 28-APR-21:30 | 19.17 | 12.73 |
May | 0.373639E+10 | 2677.52 | 23-MAY-10:33 | 20.00 | 14.59 | 0.638250E+09 | 418.75 | 22-MAY-21:30 | 20.00 | 14.59 |
June | 0.418701E+10 | 2702.82 | 13-JUN-10:33 | 22.00 | 15.85 | 0.624948E+09 | 427.93 | 13-JUN-21:30 | 14.00 | 12.84 |
July | 0.468282E+10 | 3138.06 | 22-JUL-13:30 | 28.00 | 16.51 | 0.657925E+09 | 433.97 | 21-JUL-21:30 | 28.00 | 16.51 |
August | 0.500524E+10 | 3218.65 | 19-AUG-13:10 | 20.67 | 15.34 | 0.669911E+09 | 435.94 | 14-AUG-21:30 | 20.67 | 15.34 |
September | 0.474508E+10 | 3973.57 | 27-SEP-13:20 | 21.33 | 13.25 | 0.644879E+09 | 435.90 | 12-SEP-21:30 | 21.33 | 13.25 |
October | 0.297286E+10 | 3625.13 | 07-OCT-13:10 | 17.00 | 9.32 | 0.634159E+09 | 399.37 | 03-OCT-21:30 | 17.00 | 9.32 |
November | 0.173863E+10 | 2589.50 | 11-NOV-11:33 | 9.00 | 6.87 | 0.602477E+09 | 364.23 | 18-NOV-01:10 | 7.67 | 5.84 |
December | 0.908379E+09 | 2349.27 | 08-DEC-11:33 | 6.67 | 4.51 | 0.620857E+09 | 364.17 | 22-DEC-05:40 | 3.33 | 2.88 |
Annual Sum or Average | 0.366794E+11 | 0.752849E+10 | ||||||||
Minimum of Months | 0.908379E+09 | 2138.10 | 6.33 | 4.51 | 0.565256E+09 | 364.15 | 3.33 | 2.58 | ||
Maximum of Months | 0.500524E+10 | 3973.57 | 28.00 | 16.51 | 0.669911E+09 | 435.94 | 28.00 | 16.51 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.244096E+10 | 1179.64 | 20-JAN-21:00 | 1.00 | 0.17 | 0.800434E+09 | 525.70 | 20-JAN-22:40 | 0.33 | 0.07 |
February | 0.224670E+10 | 1161.67 | 27-FEB-21:00 | 6.00 | 6.00 | 0.730550E+09 | 522.51 | 09-FEB-23:10 | 6.00 | 6.00 |
March | 0.248821E+10 | 1178.08 | 20-MAR-20:00 | 7.00 | 4.68 | 0.810970E+09 | 526.18 | 23-MAR-22:10 | 3.98 | 3.51 |
April | 0.275863E+10 | 1486.69 | 28-APR-21:00 | 12.00 | 8.90 | 0.840339E+09 | 569.52 | 27-APR-21:30 | 12.00 | 8.90 |
May | 0.286877E+10 | 1516.22 | 23-MAY-21:00 | 12.00 | 9.78 | 0.872552E+09 | 569.55 | 22-MAY-21:49 | 12.00 | 9.78 |
June | 0.291881E+10 | 1680.17 | 13-JUN-21:00 | 14.00 | 12.84 | 0.868325E+09 | 569.55 | 26-JUN-21:19 | 14.00 | 14.00 |
July | 0.310811E+10 | 1702.79 | 21-JUL-21:00 | 17.00 | 13.95 | 0.905323E+09 | 569.55 | 19-JUL-21:19 | 17.00 | 13.95 |
August | 0.314830E+10 | 1636.51 | 14-AUG-21:00 | 18.20 | 11.89 | 0.918034E+09 | 569.55 | 07-AUG-21:49 | 18.20 | 11.89 |
September | 0.296841E+10 | 1651.73 | 13-SEP-21:00 | 12.00 | 10.35 | 0.875303E+09 | 569.55 | 11-SEP-21:19 | 12.00 | 10.35 |
October | 0.270802E+10 | 1336.49 | 01-OCT-10:33 | 13.67 | 9.65 | 0.848153E+09 | 569.51 | 03-OCT-21:30 | 8.00 | 6.49 |
November | 0.242331E+10 | 1188.15 | 10-NOV-21:00 | 4.00 | 4.00 | 0.785480E+09 | 528.56 | 03-NOV-22:10 | 4.00 | 4.00 |
December | 0.232879E+10 | 1127.44 | 21-DEC-21:00 | 2.00 | 2.00 | 0.782761E+09 | 512.46 | 21-DEC-23:10 | 3.17 | 3.09 |
Annual Sum or Average | 0.324070E+11 | 0.100382E+11 | ||||||||
Minimum of Months | 0.224670E+10 | 1127.44 | 1.00 | 0.17 | 0.730550E+09 | 512.46 | 0.33 | 0.07 | ||
Maximum of Months | 0.314830E+10 | 1702.79 | 18.20 | 13.95 | 0.918034E+09 | 569.55 | 18.20 | 14.00 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.136694E+10 | 759.35 | 21-JAN-11:33 | 6.33 | 5.22 | 0.154934E+09 | 98.50 | 19-JAN-22:10 | 6.33 | 5.22 |
February | 0.131980E+10 | 757.16 | 22-FEB-11:33 | 10.00 | 8.60 | 0.140016E+09 | 97.19 | 22-FEB-22:10 | 4.17 | 3.62 |
March | 0.157275E+10 | 788.19 | 25-MAR-10:33 | 11.33 | 8.27 | 0.157683E+09 | 99.30 | 20-MAR-21:10 | 11.33 | 8.27 |
April | 0.183123E+10 | 1016.98 | 30-APR-10:33 | 19.33 | 11.65 | 0.164221E+09 | 110.33 | 28-APR-21:19 | 19.33 | 11.65 |
May | 0.194836E+10 | 992.78 | 23-MAY-10:33 | 20.00 | 14.59 | 0.173165E+09 | 112.83 | 23-MAY-21:19 | 12.00 | 9.78 |
June | 0.204871E+10 | 1040.49 | 13-JUN-10:33 | 22.00 | 15.85 | 0.176555E+09 | 117.55 | 13-JUN-21:19 | 14.00 | 12.84 |
July | 0.219446E+10 | 1109.61 | 23-JUL-10:33 | 21.00 | 15.99 | 0.185943E+09 | 119.45 | 24-JUL-21:19 | 13.67 | 13.29 |
August | 0.220936E+10 | 1055.17 | 19-AUG-10:33 | 18.00 | 14.38 | 0.187557E+09 | 117.72 | 18-AUG-21:19 | 18.00 | 14.38 |
September | 0.204201E+10 | 1012.79 | 13-SEP-10:33 | 19.67 | 15.19 | 0.176300E+09 | 115.98 | 13-SEP-21:19 | 12.00 | 10.35 |
October | 0.182003E+10 | 941.92 | 01-OCT-10:33 | 13.67 | 9.65 | 0.167377E+09 | 109.25 | 02-OCT-21:10 | 8.00 | 6.98 |
November | 0.154222E+10 | 791.97 | 11-NOV-11:33 | 9.00 | 6.87 | 0.152885E+09 | 100.65 | 10-NOV-22:10 | 9.00 | 6.87 |
December | 0.122255E+10 | 713.74 | 21-DEC-21:00 | 2.00 | 2.00 | 0.153344E+09 | 95.58 | 21-DEC-22:10 | 3.00 | 3.00 |
Annual Sum or Average | 0.211184E+11 | 0.198998E+10 | ||||||||
Minimum of Months | 0.122255E+10 | 713.74 | 2.00 | 2.00 | 0.140016E+09 | 95.58 | 3.00 | 3.00 | ||
Maximum of Months | 0.220936E+10 | 1109.61 | 22.00 | 15.99 | 0.187557E+09 | 119.45 | 19.33 | 14.38 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.532272E+09 | 406.22 | 18-JAN-21:00 | 8.00 | 6.97 | 0.117054E+09 | 71.75 | 18-JAN-23:10 | 7.80 | 7.23 |
February | 0.533025E+09 | 402.05 | 22-FEB-21:00 | 5.00 | 4.08 | 0.105749E+09 | 70.99 | 22-FEB-23:10 | 4.83 | 3.99 |
March | 0.728877E+09 | 422.13 | 19-MAR-10:33 | 12.00 | 11.46 | 0.118032E+09 | 72.10 | 20-MAR-22:10 | 4.30 | 3.44 |
April | 0.102669E+10 | 589.83 | 30-APR-10:33 | 19.33 | 11.65 | 0.121644E+09 | 81.93 | 30-APR-23:10 | 11.87 | 8.94 |
May | 0.109585E+10 | 576.20 | 23-MAY-10:33 | 20.00 | 14.59 | 0.128365E+09 | 82.82 | 23-MAY-22:10 | 11.83 | 9.72 |
June | 0.116130E+10 | 604.98 | 13-JUN-10:33 | 22.00 | 15.85 | 0.131372E+09 | 86.50 | 13-JUN-22:10 | 13.83 | 12.78 |
July | 0.124728E+10 | 643.44 | 23-JUL-10:33 | 21.00 | 15.99 | 0.138544E+09 | 87.51 | 24-JUL-21:49 | 13.17 | 13.07 |
August | 0.125521E+10 | 609.62 | 19-AUG-10:33 | 18.00 | 14.38 | 0.139678E+09 | 86.39 | 18-AUG-21:30 | 18.00 | 14.38 |
September | 0.115417E+10 | 586.18 | 13-SEP-10:33 | 19.67 | 15.19 | 0.130940E+09 | 84.97 | 13-SEP-21:49 | 12.00 | 10.35 |
October | 0.100755E+10 | 539.29 | 01-OCT-10:33 | 13.67 | 9.65 | 0.123619E+09 | 79.44 | 02-OCT-22:10 | 8.00 | 6.98 |
November | 0.730884E+09 | 448.31 | 11-NOV-11:33 | 9.00 | 6.87 | 0.114056E+09 | 72.95 | 08-NOV-23:10 | 9.00 | 6.87 |
December | 0.375857E+09 | 390.24 | 20-DEC-21:00 | 7.00 | 6.47 | 0.116728E+09 | 69.77 | 21-DEC-23:10 | 3.17 | 3.09 |
Annual Sum or Average | 0.108490E+11 | 0.148578E+10 | ||||||||
Minimum of Months | 0.375857E+09 | 390.24 | 5.00 | 4.08 | 0.105749E+09 | 69.77 | 3.17 | 3.09 | ||
Maximum of Months | 0.125521E+10 | 643.44 | 22.00 | 15.99 | 0.139678E+09 | 87.51 | 18.00 | 14.38 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.487683E+11 | 36869.21 | 23-JAN-21:00 | 9.00 | 7.43 | 0.587498E+09 | 381.66 | 23-JAN-22:10 | 8.00 | 7.45 |
February | 0.441776E+11 | 36863.66 | 22-FEB-21:00 | 5.00 | 4.08 | 0.530847E+09 | 381.60 | 06-FEB-22:10 | 5.00 | 4.08 |
March | 0.493158E+11 | 36970.50 | 30-MAR-20:00 | 7.00 | 4.67 | 0.589480E+09 | 381.61 | 20-MAR-21:10 | 7.00 | 4.67 |
April | 0.490747E+11 | 37972.37 | 28-APR-20:00 | 13.00 | 9.28 | 0.572227E+09 | 381.63 | 28-APR-21:10 | 11.83 | 8.82 |
May | 0.508594E+11 | 38077.22 | 23-MAY-20:00 | 14.00 | 10.69 | 0.591825E+09 | 381.64 | 11-MAY-21:10 | 14.00 | 10.69 |
June | 0.499421E+11 | 38354.92 | 13-JUN-20:00 | 17.00 | 13.95 | 0.574735E+09 | 381.64 | 08-JUN-21:10 | 17.00 | 13.95 |
July | 0.517374E+11 | 38335.63 | 21-JUL-20:00 | 21.00 | 15.02 | 0.593317E+09 | 381.66 | 21-JUL-21:10 | 17.00 | 13.87 |
August | 0.521026E+11 | 38224.98 | 14-AUG-20:00 | 20.70 | 12.26 | 0.594919E+09 | 381.68 | 14-AUG-21:10 | 17.83 | 11.86 |
September | 0.498118E+11 | 38104.51 | 13-SEP-20:00 | 15.00 | 12.66 | 0.574284E+09 | 381.75 | 21-SEP-21:10 | 8.00 | 7.37 |
October | 0.499979E+11 | 37522.58 | 06-OCT-20:00 | 8.00 | 6.07 | 0.590750E+09 | 381.71 | 02-OCT-21:10 | 8.00 | 6.07 |
November | 0.475846E+11 | 36972.61 | 10-NOV-21:00 | 4.00 | 4.00 | 0.569737E+09 | 381.64 | 21-NOV-22:19 | 8.67 | 7.78 |
December | 0.483386E+11 | 36652.95 | 20-DEC-21:00 | 7.00 | 6.47 | 0.586195E+09 | 381.60 | 11-DEC-22:10 | 7.00 | 6.47 |
Annual Sum or Average | 0.591711E+12 | 0.695581E+10 | ||||||||
Minimum of Months | 0.441776E+11 | 36652.95 | 4.00 | 4.00 | 0.530847E+09 | 381.60 | 5.00 | 4.08 | ||
Maximum of Months | 0.521026E+11 | 38354.92 | 21.00 | 15.02 | 0.594919E+09 | 381.75 | 17.83 | 13.95 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.165008E+11 | 10876.69 | 21-JAN-11:33 | 6.33 | 5.22 | 0.877523E+10 | 5788.08 | 17-JAN-22:40 | 6.33 | 5.22 |
February | 0.157323E+11 | 12365.53 | 04-FEB-13:30 | 9.00 | 6.13 | 0.802078E+10 | 5792.92 | 27-FEB-22:40 | 4.33 | 4.33 |
March | 0.165018E+11 | 9092.99 | 25-MAR-10:33 | 11.33 | 8.27 | 0.881157E+10 | 5764.23 | 20-MAR-21:40 | 11.33 | 8.27 |
April | 0.205823E+11 | 12459.24 | 29-APR-13:00 | 19.00 | 12.80 | 0.920153E+10 | 6398.22 | 28-APR-21:40 | 19.00 | 12.80 |
May | 0.207119E+11 | 10669.33 | 23-MAY-10:33 | 20.00 | 14.59 | 0.942931E+10 | 6375.31 | 22-MAY-21:40 | 20.00 | 14.59 |
June | 0.210056E+11 | 11001.85 | 25-JUN-10:33 | 20.00 | 13.96 | 0.935061E+10 | 6411.51 | 13-JUN-22:10 | 20.00 | 13.96 |
July | 0.225521E+11 | 11737.42 | 22-JUL-13:30 | 28.00 | 16.51 | 0.980169E+10 | 6462.75 | 21-JUL-22:10 | 28.00 | 16.51 |
August | 0.234683E+11 | 12401.92 | 28-AUG-15:03 | 24.00 | 15.59 | 0.100619E+11 | 6462.70 | 21-AUG-21:19 | 24.00 | 15.59 |
September | 0.228687E+11 | 13962.76 | 23-SEP-12:30 | 19.00 | 14.78 | 0.966005E+10 | 6462.72 | 11-SEP-21:19 | 19.00 | 14.78 |
October | 0.194017E+11 | 13803.47 | 07-OCT-13:00 | 17.00 | 9.21 | 0.926990E+10 | 6278.66 | 03-OCT-21:40 | 17.00 | 9.21 |
November | 0.163460E+11 | 10856.72 | 11-NOV-11:33 | 9.00 | 6.87 | 0.857313E+10 | 5813.69 | 03-NOV-21:40 | 9.00 | 6.87 |
December | 0.148528E+11 | 9542.01 | 08-DEC-11:33 | 6.67 | 4.51 | 0.858937E+10 | 5590.23 | 21-DEC-22:40 | 3.00 | 3.00 |
Annual Sum or Average | 0.230524E+12 | 0.109545E+12 | ||||||||
Minimum of Months | 0.148528E+11 | 9092.99 | 6.33 | 4.51 | 0.802078E+10 | 5590.23 | 3.00 | 3.00 | ||
Maximum of Months | 0.234683E+11 | 13962.76 | 28.00 | 16.51 | 0.100619E+11 | 6462.75 | 28.00 | 16.51 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.579378E+11 | 28164.13 | 21-JAN-11:33 | 6.33 | 5.22 | 0.282693E+11 | 18558.95 | 17-JAN-23:10 | 6.33 | 5.22 |
February | 0.532515E+11 | 27773.39 | 04-FEB-11:33 | 7.67 | 5.05 | 0.257574E+11 | 18429.64 | 09-FEB-23:10 | 2.17 | 2.17 |
March | 0.586257E+11 | 27009.95 | 20-MAR-20:00 | 7.00 | 4.68 | 0.285558E+11 | 18523.59 | 20-MAR-22:10 | 4.30 | 3.44 |
April | 0.640978E+11 | 32901.58 | 30-APR-10:33 | 19.33 | 11.65 | 0.292093E+11 | 19184.69 | 28-APR-23:19 | 19.33 | 11.65 |
May | 0.662391E+11 | 32826.11 | 23-MAY-20:14 | 13.33 | 10.40 | 0.302216E+11 | 19186.23 | 22-MAY-21:49 | 13.33 | 10.40 |
June | 0.669060E+11 | 34665.07 | 13-JUN-21:12 | 14.00 | 12.84 | 0.299142E+11 | 19186.27 | 26-JUN-21:19 | 14.00 | 14.00 |
July | 0.710224E+11 | 35456.98 | 21-JUL-21:10 | 17.00 | 13.87 | 0.310878E+11 | 19186.23 | 19-JUL-21:19 | 17.00 | 13.87 |
August | 0.723566E+11 | 35311.30 | 18-AUG-21:10 | 15.50 | 12.88 | 0.315512E+11 | 19186.23 | 02-AUG-21:30 | 15.50 | 12.88 |
September | 0.689121E+11 | 35847.30 | 12-SEP-21:10 | 15.17 | 13.86 | 0.302708E+11 | 19186.12 | 11-SEP-21:19 | 15.17 | 13.86 |
October | 0.635411E+11 | 31515.98 | 03-OCT-21:10 | 8.00 | 6.49 | 0.297099E+11 | 19183.77 | 02-OCT-21:10 | 8.00 | 6.49 |
November | 0.572913E+11 | 28669.19 | 11-NOV-11:33 | 9.00 | 6.87 | 0.277019E+11 | 18672.68 | 03-NOV-22:10 | 9.00 | 6.87 |
December | 0.556854E+11 | 26079.01 | 21-DEC-21:00 | 2.00 | 2.00 | 0.277246E+11 | 18194.23 | 21-DEC-23:10 | 3.17 | 3.09 |
Annual Sum or Average | 0.755867E+12 | 0.349974E+12 | ||||||||
Minimum of Months | 0.532515E+11 | 26079.01 | 2.00 | 2.00 | 0.257574E+11 | 18194.23 | 2.17 | 2.17 | ||
Maximum of Months | 0.723566E+11 | 35847.30 | 19.33 | 13.87 | 0.315512E+11 | 19186.27 | 19.33 | 14.00 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 28786724.51 | 3152.51 | 19-JAN-16:01 | 7.67 | 7.22 | 94747723.77 | 56.69 | 10-JAN-04:19 | 7.67 | 7.22 |
February | 87278720.26 | 3210.69 | 27-FEB-16:01 | 8.00 | 6.56 | 86210478.79 | 56.69 | 14-FEB-04:19 | 8.00 | 6.56 |
March | 60847379.34 | 2945.96 | 23-MAR-18:01 | 7.67 | 5.83 | 95371999.55 | 56.69 | 18-MAR-01:19 | 7.67 | 5.83 |
April | 0.836657E+09 | 3312.10 | 29-APR-08:61 | 15.17 | 11.12 | 94934106.26 | 56.69 | 29-APR-23:30 | 10.65 | 8.89 |
May | 0.996654E+09 | 3487.01 | 11-MAY-18:03 | 16.67 | 9.33 | 98181632.50 | 56.70 | 22-MAY-21:30 | 14.50 | 12.46 |
June | 0.140052E+10 | 3454.14 | 05-JUN-15:01 | 14.00 | 11.65 | 95575282.09 | 56.70 | 13-JUN-22:10 | 13.83 | 12.78 |
July | 0.169033E+10 | 3433.57 | 18-JUL-18:01 | 16.00 | 14.13 | 98746345.18 | 56.70 | 10-JUL-21:49 | 16.00 | 14.13 |
August | 0.162581E+10 | 3410.10 | 15-AUG-18:01 | 16.83 | 14.37 | 98869760.30 | 56.70 | 02-AUG-21:10 | 16.83 | 14.37 |
September | 0.123313E+10 | 3453.84 | 10-SEP-18:01 | 18.67 | 15.77 | 95387054.17 | 56.69 | 14-SEP-23:40 | 13.67 | 12.71 |
October | 0.336374E+09 | 3371.46 | 10-OCT-15:01 | 12.83 | 11.71 | 96533514.49 | 56.69 | 05-OCT-21:19 | 12.83 | 11.71 |
November | 33955766.57 | 3249.30 | 10-NOV-16:01 | 10.33 | 8.12 | 91983529.41 | 56.69 | 17-NOV-04:19 | 3.00 | 2.03 |
December | 8171949.58 | 412.63 | 19-DEC-19:05 | 7.00 | 6.01 | 93636387.93 | 56.69 | 19-DEC-04:19 | 7.00 | 6.01 |
Annual Sum or Average | 0.833852E+10 | 0.114018E+10 | ||||||||
Minimum of Months | 8171949.58 | 412.63 | 7.00 | 5.83 | 86210478.79 | 56.69 | 3.00 | 2.03 | ||
Maximum of Months | 0.169033E+10 | 3487.01 | 18.67 | 15.77 | 98869760.30 | 56.70 | 16.83 | 14.37 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 10339750.02 | 2720.63 | 19-JAN-16:01 | 7.67 | 7.22 | 93743952.36 | 56.69 | 13-JAN-04:19 | 7.67 | 7.22 |
February | 31948214.60 | 2952.18 | 27-FEB-16:01 | 8.00 | 6.56 | 85228787.33 | 56.69 | 17-FEB-04:19 | 8.00 | 6.56 |
March | 35955541.24 | 2706.72 | 23-MAR-18:01 | 7.67 | 5.83 | 94881986.30 | 56.69 | 03-MAR-04:19 | 7.67 | 5.83 |
April | 0.517906E+09 | 3323.82 | 28-APR-19:01 | 13.83 | 10.09 | 95480373.96 | 81.02 | 28-APR-18:10 | 13.83 | 10.09 |
May | 0.734261E+09 | 3564.35 | 11-MAY-19:31 | 13.67 | 8.80 | 0.100171E+09 | 87.58 | 23-MAY-18:10 | 17.67 | 12.17 |
June | 0.112120E+10 | 3574.82 | 22-JUN-19:01 | 13.67 | 11.71 | 99837675.15 | 90.63 | 26-JUN-18:10 | 18.00 | 16.13 |
July | 0.119616E+10 | 3633.96 | 28-JUL-17:52 | 14.00 | 12.84 | 0.107771E+09 | 89.16 | 12-JUL-18:10 | 14.00 | 12.84 |
August | 0.999523E+09 | 3572.23 | 01-AUG-19:31 | 14.33 | 11.35 | 0.107021E+09 | 84.10 | 17-AUG-18:10 | 20.50 | 15.86 |
September | 0.661817E+09 | 3611.44 | 14-SEP-18:01 | 14.00 | 12.84 | 98177597.93 | 76.23 | 12-SEP-18:10 | 14.00 | 12.84 |
October | 0.141440E+09 | 3348.14 | 06-OCT-18:01 | 11.33 | 7.72 | 95877664.40 | 56.69 | 08-OCT-01:19 | 10.00 | 8.75 |
November | 13358724.43 | 2816.26 | 10-NOV-16:01 | 10.33 | 8.12 | 91137910.67 | 56.69 | 01-NOV-04:19 | 10.33 | 8.12 |
December | 5083621.31 | 207.16 | 20-DEC-19:06 | 7.67 | 7.21 | 93021535.01 | 56.69 | 26-DEC-04:19 | 2.00 | 0.60 |
Annual Sum or Average | 0.546900E+10 | 0.116235E+10 | ||||||||
Minimum of Months | 5083621.31 | 207.16 | 7.67 | 5.83 | 85228787.33 | 56.69 | 2.00 | 0.60 | ||
Maximum of Months | 0.119616E+10 | 3633.96 | 14.33 | 12.84 | 0.107771E+09 | 90.63 | 20.50 | 16.13 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 63674258.87 | 455.06 | 21-JAN-11:25 | 6.00 | 5.05 | 0.00 | 0.00 | 01-JAN-00:10 | 6.00 | 5.05 |
February | 63411979.59 | 392.28 | 19-FEB-14:05 | 6.00 | 4.14 | 0.00 | 0.00 | 01-FEB-00:10 | 6.00 | 4.14 |
March | 13970260.51 | 145.95 | 25-MAR-14:05 | 11.83 | 9.32 | 0.00 | 0.00 | 01-MAR-00:10 | 11.83 | 9.32 |
April | 0.339011E+09 | 572.93 | 30-APR-12:50 | 22.00 | 13.22 | 0.00 | 0.00 | 01-APR-00:10 | 22.00 | 13.22 |
May | 0.278494E+09 | 447.24 | 22-MAY-13:05 | 22.17 | 14.96 | 0.00 | 0.00 | 01-MAY-00:10 | 22.17 | 14.96 |
June | 0.342388E+09 | 447.53 | 13-JUN-13:20 | 24.37 | 17.19 | 0.00 | 0.00 | 01-JUN-00:10 | 24.37 | 17.19 |
July | 0.440942E+09 | 517.18 | 22-JUL-13:30 | 28.00 | 16.51 | 0.00 | 0.00 | 01-JUL-00:10 | 28.00 | 16.51 |
August | 0.539190E+09 | 559.64 | 20-AUG-13:00 | 23.00 | 14.82 | 0.00 | 0.00 | 01-AUG-00:10 | 23.00 | 14.82 |
September | 0.550274E+09 | 696.41 | 27-SEP-13:20 | 21.33 | 13.25 | 0.00 | 0.00 | 01-SEP-00:10 | 21.33 | 13.25 |
October | 0.224791E+09 | 647.88 | 07-OCT-13:00 | 17.00 | 9.21 | 0.00 | 0.00 | 01-OCT-00:10 | 17.00 | 9.21 |
November | 51809400.65 | 416.04 | 11-NOV-13:30 | 9.00 | 7.22 | 0.00 | 0.00 | 01-NOV-00:10 | 9.00 | 7.22 |
December | 9090948.90 | 136.28 | 26-DEC-15:05 | 5.50 | 3.13 | 0.00 | 0.00 | 01-DEC-00:10 | 5.50 | 3.13 |
Annual Sum or Average | 0.291705E+10 | 0.00 | ||||||||
Minimum of Months | 9090948.90 | 136.28 | 5.50 | 3.13 | 0.00 | 0.00 | 5.50 | 3.13 | ||
Maximum of Months | 0.550274E+09 | 696.41 | 28.00 | 17.19 | 0.00 | 0.00 | 28.00 | 17.19 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 93413881.78 | 836.09 | 29-JAN-09:02 | 11.00 | 8.46 | 95403708.69 | 56.69 | 29-JAN-02:20 | 11.00 | 8.46 |
February | 89791342.93 | 783.12 | 27-FEB-19:02 | 5.17 | 5.17 | 86361749.66 | 56.69 | 27-FEB-00:20 | 5.17 | 5.17 |
March | 0.191530E+09 | 858.49 | 19-MAR-08:62 | 11.00 | 9.96 | 96364295.97 | 56.69 | 19-MAR-23:19 | 8.17 | 7.67 |
April | 0.339394E+09 | 962.04 | 14-APR-15:02 | 12.17 | 8.09 | 94517356.97 | 61.11 | 27-APR-20:10 | 11.50 | 8.67 |
May | 0.423037E+09 | 1021.40 | 11-MAY-19:31 | 13.67 | 8.80 | 98319558.21 | 74.27 | 22-MAY-21:19 | 14.67 | 12.52 |
June | 0.532420E+09 | 1030.14 | 08-JUN-19:11 | 14.00 | 9.33 | 96575124.55 | 77.95 | 26-JUN-21:10 | 14.00 | 14.00 |
July | 0.551654E+09 | 1016.57 | 10-JUL-21:51 | 17.00 | 13.49 | 0.101438E+09 | 75.81 | 19-JUL-21:10 | 14.00 | 12.84 |
August | 0.484547E+09 | 981.65 | 28-AUG-15:01 | 24.00 | 15.59 | 0.101526E+09 | 75.31 | 17-AUG-21:10 | 24.00 | 15.59 |
September | 0.397678E+09 | 952.09 | 13-SEP-19:31 | 15.00 | 12.66 | 95541036.43 | 72.89 | 11-SEP-21:10 | 15.00 | 12.66 |
October | 0.250198E+09 | 973.73 | 07-OCT-18:01 | 10.67 | 8.16 | 96603329.97 | 56.69 | 07-OCT-23:30 | 10.50 | 9.16 |
November | 0.135399E+09 | 854.03 | 23-NOV-09:02 | 8.00 | 7.45 | 92724845.52 | 56.69 | 08-NOV-22:40 | 8.00 | 7.45 |
December | 59273500.39 | 794.32 | 02-DEC-09:02 | 7.00 | 6.47 | 95075256.54 | 56.69 | 05-DEC-00:20 | 7.00 | 7.00 |
Annual Sum or Average | 0.354834E+10 | 0.115045E+10 | ||||||||
Minimum of Months | 59273500.39 | 783.12 | 5.17 | 5.17 | 86361749.66 | 56.69 | 5.17 | 5.17 | ||
Maximum of Months | 0.551654E+09 | 1030.14 | 24.00 | 15.59 | 0.101526E+09 | 77.95 | 24.00 | 15.59 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 44172531.89 | 2732.93 | 19-JAN-16:01 | 7.67 | 7.22 | 94720354.64 | 56.69 | 10-JAN-04:19 | 7.67 | 7.22 |
February | 66501038.07 | 2878.82 | 27-FEB-16:01 | 8.00 | 6.56 | 86193921.51 | 56.69 | 17-FEB-04:19 | 8.00 | 6.56 |
March | 55180552.96 | 2829.54 | 25-MAR-15:01 | 11.00 | 9.40 | 95451369.55 | 56.69 | 31-MAR-03:20 | 3.50 | 2.46 |
April | 0.933311E+09 | 3001.25 | 21-APR-08:62 | 11.83 | 10.02 | 95361204.71 | 56.69 | 29-APR-23:10 | 10.88 | 9.05 |
May | 0.995184E+09 | 3447.12 | 11-MAY-18:01 | 16.67 | 9.33 | 98558059.78 | 56.69 | 11-MAY-21:10 | 11.50 | 9.00 |
June | 0.130786E+10 | 3144.11 | 16-JUN-15:01 | 14.00 | 11.22 | 95730782.08 | 56.69 | 13-JUN-21:19 | 14.00 | 11.22 |
July | 0.158641E+10 | 3168.02 | 26-JUL-08:61 | 14.00 | 13.33 | 98936361.72 | 56.70 | 21-JUL-21:30 | 14.00 | 13.33 |
August | 0.166943E+10 | 3191.52 | 06-AUG-08:61 | 14.17 | 12.90 | 99014227.31 | 56.70 | 21-AUG-21:10 | 14.17 | 12.31 |
September | 0.134860E+10 | 3161.22 | 09-SEP-08:62 | 13.33 | 12.02 | 95663915.87 | 56.69 | 13-SEP-01:10 | 14.33 | 12.86 |
October | 0.356104E+09 | 3379.19 | 06-OCT-18:01 | 11.33 | 7.72 | 96705977.40 | 56.69 | 08-OCT-01:19 | 10.00 | 8.75 |
November | 43657188.94 | 2813.42 | 10-NOV-16:01 | 10.33 | 8.12 | 91974715.72 | 56.69 | 28-NOV-04:19 | 1.67 | 0.43 |
December | 18354433.01 | 483.93 | 26-DEC-09:04 | 2.17 | 0.41 | 93718308.12 | 56.69 | 19-DEC-04:19 | 2.17 | 0.41 |
Annual Sum or Average | 0.842477E+10 | 0.114203E+10 | ||||||||
Minimum of Months | 18354433.01 | 483.93 | 2.17 | 0.41 | 86193921.51 | 56.69 | 1.67 | 0.41 | ||
Maximum of Months | 0.166943E+10 | 3447.12 | 16.67 | 13.33 | 99014227.31 | 56.70 | 14.33 | 13.33 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 12491517.78 | 441.19 | 21-JAN-09:02 | 3.35 | 3.02 | 93719943.35 | 56.69 | 13-JAN-04:19 | 3.35 | 3.02 |
February | 23524707.10 | 2455.53 | 23-FEB-09:02 | 5.33 | 3.83 | 85079230.21 | 56.69 | 01-FEB-01:19 | 5.33 | 3.83 |
March | 27762054.69 | 2211.03 | 25-MAR-15:01 | 11.00 | 9.40 | 94967560.86 | 56.69 | 03-MAR-04:19 | 11.00 | 9.40 |
April | 0.603482E+09 | 3139.46 | 28-APR-08:51 | 16.00 | 11.54 | 95632667.64 | 62.26 | 27-APR-20:10 | 16.00 | 11.54 |
May | 0.750808E+09 | 3280.43 | 23-MAY-08:51 | 19.00 | 14.78 | 99503784.89 | 75.30 | 22-MAY-21:10 | 19.00 | 14.78 |
June | 0.106344E+10 | 3500.91 | 13-JUN-08:32 | 21.40 | 15.97 | 98115385.48 | 78.60 | 26-JUN-21:10 | 14.00 | 14.00 |
July | 0.119124E+10 | 3687.85 | 23-JUL-08:32 | 19.67 | 15.53 | 0.103676E+09 | 77.38 | 10-JUL-21:40 | 19.67 | 15.53 |
August | 0.111463E+10 | 3426.69 | 17-AUG-08:51 | 19.00 | 15.90 | 0.103992E+09 | 75.26 | 17-AUG-21:10 | 14.83 | 13.13 |
September | 0.795816E+09 | 3406.68 | 11-SEP-08:51 | 19.00 | 15.28 | 97390672.35 | 72.73 | 11-SEP-21:10 | 13.83 | 12.58 |
October | 0.153521E+09 | 2984.61 | 06-OCT-18:01 | 11.33 | 7.72 | 96061205.84 | 56.69 | 08-OCT-01:19 | 10.00 | 8.75 |
November | 15762716.72 | 1996.28 | 11-NOV-09:02 | 6.50 | 5.33 | 91104778.29 | 56.69 | 28-NOV-04:19 | 1.67 | 0.43 |
December | 5700843.83 | 335.72 | 20-DEC-09:06 | 5.50 | 5.00 | 93102635.23 | 56.69 | 26-DEC-04:19 | 2.00 | 0.60 |
Annual Sum or Average | 0.575817E+10 | 0.115235E+10 | ||||||||
Minimum of Months | 5700843.83 | 335.72 | 3.35 | 3.02 | 85079230.21 | 56.69 | 1.67 | 0.43 | ||
Maximum of Months | 0.119124E+10 | 3687.85 | 21.40 | 15.97 | 0.103992E+09 | 78.60 | 19.67 | 15.53 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.246154E+10 | 1794.21 | 21-JAN-11:33 | 6.33 | 5.22 | 0.120129E+10 | 726.77 | 17-JAN-23:10 | 6.33 | 5.22 |
February | 0.252472E+10 | 1780.99 | 04-FEB-11:33 | 7.67 | 5.05 | 0.108737E+10 | 727.27 | 27-FEB-22:49 | 4.17 | 4.17 |
March | 0.289013E+10 | 1694.42 | 20-MAR-18:10 | 7.83 | 5.10 | 0.121002E+10 | 733.79 | 20-MAR-21:49 | 4.50 | 3.61 |
April | 0.416521E+10 | 2403.88 | 30-APR-10:33 | 19.33 | 11.65 | 0.125798E+10 | 846.37 | 30-APR-23:19 | 11.63 | 8.77 |
May | 0.446077E+10 | 2311.76 | 23-MAY-10:33 | 20.00 | 14.59 | 0.133044E+10 | 851.45 | 23-MAY-21:40 | 12.00 | 9.78 |
June | 0.463926E+10 | 2404.28 | 13-JUN-10:33 | 22.00 | 15.85 | 0.134427E+10 | 882.04 | 26-JUN-21:19 | 14.00 | 14.00 |
July | 0.497491E+10 | 2552.44 | 23-JUL-10:33 | 21.00 | 15.99 | 0.141579E+10 | 899.82 | 24-JUL-21:40 | 13.33 | 13.15 |
August | 0.503346E+10 | 2461.25 | 19-AUG-10:33 | 18.00 | 14.38 | 0.143248E+10 | 885.41 | 21-AUG-21:00 | 15.00 | 12.66 |
September | 0.464669E+10 | 2364.32 | 13-SEP-10:33 | 19.67 | 15.19 | 0.134569E+10 | 872.17 | 13-SEP-21:40 | 12.00 | 10.35 |
October | 0.373202E+10 | 2220.35 | 01-OCT-10:33 | 13.67 | 9.65 | 0.125864E+10 | 823.24 | 03-OCT-21:40 | 8.00 | 6.49 |
November | 0.263745E+10 | 1798.69 | 11-NOV-11:33 | 9.00 | 6.87 | 0.116364E+10 | 726.79 | 03-NOV-21:49 | 9.00 | 6.87 |
December | 0.184734E+10 | 1484.70 | 21-DEC-22:00 | 3.00 | 3.00 | 0.119904E+10 | 713.93 | 21-DEC-22:49 | 3.00 | 3.00 |
Annual Sum or Average | 0.440135E+11 | 0.152467E+11 | ||||||||
Minimum of Months | 0.184734E+10 | 1484.70 | 3.00 | 3.00 | 0.108737E+10 | 713.93 | 3.00 | 3.00 | ||
Maximum of Months | 0.503346E+10 | 2552.44 | 22.00 | 15.99 | 0.143248E+10 | 899.82 | 15.00 | 14.00 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 22537485.86 | 3347.47 | 19-JAN-16:01 | 7.67 | 7.22 | 94129711.40 | 56.69 | 13-JAN-04:19 | 7.67 | 7.22 |
February | 84179768.37 | 3342.58 | 27-FEB-16:01 | 8.00 | 6.56 | 85720255.72 | 56.69 | 17-FEB-04:19 | 8.00 | 6.56 |
March | 51121622.37 | 3234.01 | 25-MAR-15:01 | 11.00 | 9.40 | 94918991.17 | 56.69 | 14-MAR-03:20 | 11.00 | 9.40 |
April | 0.845030E+09 | 3455.42 | 29-APR-08:61 | 15.17 | 11.12 | 94805739.01 | 56.69 | 23-APR-01:39 | 15.17 | 11.12 |
May | 0.980613E+09 | 3932.54 | 11-MAY-18:01 | 16.67 | 9.33 | 98034155.07 | 56.70 | 22-MAY-21:30 | 14.50 | 12.46 |
June | 0.139563E+10 | 3552.29 | 26-JUN-08:61 | 18.17 | 13.96 | 95499402.60 | 56.70 | 15-JUN-02:00 | 18.17 | 13.96 |
July | 0.170751E+10 | 3629.14 | 17-JUL-18:01 | 17.83 | 15.39 | 98676083.62 | 56.70 | 21-JUL-21:00 | 17.00 | 13.49 |
August | 0.159624E+10 | 3583.65 | 15-AUG-18:01 | 16.83 | 14.37 | 98780402.06 | 56.70 | 17-AUG-21:10 | 14.83 | 13.13 |
September | 0.114827E+10 | 3619.24 | 10-SEP-18:01 | 18.67 | 15.77 | 95232781.16 | 56.69 | 27-SEP-01:00 | 9.00 | 8.43 |
October | 0.285340E+09 | 3579.56 | 10-OCT-15:01 | 12.83 | 11.71 | 96119002.58 | 56.69 | 08-OCT-00:40 | 12.83 | 11.71 |
November | 27519087.03 | 3455.27 | 10-NOV-16:01 | 10.33 | 8.12 | 91415868.24 | 56.69 | 01-NOV-04:19 | 10.33 | 8.12 |
December | 5083736.12 | 329.48 | 18-DEC-16:03 | 5.17 | 3.90 | 93078550.60 | 56.69 | 15-DEC-04:19 | 5.17 | 3.90 |
Annual Sum or Average | 0.814908E+10 | 0.113641E+10 | ||||||||
Minimum of Months | 5083736.12 | 329.48 | 5.17 | 3.90 | 85720255.72 | 56.69 | 5.17 | 3.90 | ||
Maximum of Months | 0.170751E+10 | 3932.54 | 18.67 | 15.77 | 98780402.06 | 56.70 | 18.17 | 13.96 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5909874.60 | 2829.28 | 19-JAN-16:01 | 7.67 | 7.22 | 93160005.59 | 56.69 | 03-JAN-04:19 | 7.67 | 7.22 |
February | 26141856.17 | 3106.84 | 27-FEB-16:01 | 8.00 | 6.56 | 84664099.53 | 56.69 | 24-FEB-04:19 | 8.00 | 6.56 |
March | 30181570.92 | 2842.28 | 23-MAR-18:01 | 7.67 | 5.83 | 94394478.31 | 56.69 | 17-MAR-03:20 | 7.67 | 5.83 |
April | 0.514249E+09 | 3476.97 | 28-APR-19:01 | 13.83 | 10.09 | 95629967.21 | 88.73 | 28-APR-18:10 | 13.83 | 10.09 |
May | 0.710628E+09 | 3845.84 | 23-MAY-19:42 | 14.33 | 10.77 | 0.100534E+09 | 95.05 | 22-MAY-18:10 | 14.33 | 10.77 |
June | 0.112208E+10 | 3896.20 | 22-JUN-18:42 | 14.33 | 11.96 | 0.100523E+09 | 97.24 | 21-JUN-18:10 | 14.33 | 11.96 |
July | 0.123554E+10 | 4046.72 | 11-JUL-18:52 | 14.00 | 12.24 | 0.109308E+09 | 95.92 | 12-JUL-18:10 | 19.00 | 13.74 |
August | 0.985080E+09 | 3780.63 | 31-AUG-19:01 | 13.83 | 11.16 | 0.108262E+09 | 90.00 | 17-AUG-18:10 | 13.83 | 11.16 |
September | 0.569436E+09 | 3760.48 | 14-SEP-18:01 | 14.00 | 12.84 | 98615292.61 | 82.13 | 12-SEP-18:10 | 14.00 | 12.84 |
October | 0.107593E+09 | 3488.12 | 06-OCT-18:01 | 11.33 | 7.72 | 95397081.63 | 56.69 | 06-OCT-04:19 | 11.33 | 7.72 |
November | 9702341.78 | 2951.92 | 10-NOV-16:01 | 10.33 | 8.12 | 90528672.20 | 56.69 | 28-NOV-04:19 | 1.67 | 0.43 |
December | 2001088.19 | 73.74 | 21-DEC-14:00 | 8.00 | 6.98 | 92537903.31 | 56.69 | 19-DEC-04:19 | 8.00 | 6.98 |
Annual Sum or Average | 0.531854E+10 | 0.116355E+10 | ||||||||
Minimum of Months | 2001088.19 | 73.74 | 7.67 | 5.83 | 84664099.53 | 56.69 | 1.67 | 0.43 | ||
Maximum of Months | 0.123554E+10 | 4046.72 | 14.33 | 12.84 | 0.109308E+09 | 97.24 | 19.00 | 13.74 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.190818E+09 | 2172.65 | 23-JAN-16:01 | 10.83 | 9.28 | 96128063.97 | 56.69 | 13-JAN-04:19 | 10.83 | 9.28 |
February | 0.229866E+09 | 2039.26 | 10-FEB-16:01 | 6.83 | 5.06 | 87321611.32 | 56.69 | 21-FEB-00:20 | 6.00 | 4.59 |
March | 0.111191E+09 | 2162.32 | 25-MAR-15:01 | 11.00 | 9.40 | 96350815.72 | 56.69 | 20-MAR-23:19 | 11.00 | 9.40 |
April | 0.734515E+09 | 2146.48 | 29-APR-08:61 | 15.17 | 11.12 | 95280250.12 | 56.69 | 26-APR-21:10 | 15.17 | 11.12 |
May | 0.637928E+09 | 2429.63 | 11-MAY-18:01 | 16.67 | 9.33 | 98366993.03 | 56.69 | 11-MAY-21:19 | 11.00 | 8.70 |
June | 0.781330E+09 | 2272.35 | 08-JUN-18:02 | 15.83 | 9.50 | 95548033.45 | 56.70 | 13-JUN-21:10 | 14.00 | 12.84 |
July | 0.959841E+09 | 2235.94 | 28-JUL-15:01 | 17.00 | 14.43 | 98720460.75 | 56.69 | 24-JUL-00:40 | 17.00 | 14.43 |
August | 0.109927E+10 | 2184.74 | 12-AUG-18:01 | 17.83 | 14.24 | 98801159.68 | 56.69 | 15-AUG-23:49 | 14.00 | 12.84 |
September | 0.109011E+10 | 2221.79 | 14-SEP-18:01 | 14.00 | 12.84 | 95547336.00 | 56.70 | 13-SEP-21:10 | 14.00 | 12.84 |
October | 0.480828E+09 | 2427.12 | 06-OCT-18:01 | 11.33 | 7.72 | 97348822.38 | 56.69 | 10-OCT-21:10 | 8.83 | 8.83 |
November | 0.165921E+09 | 2076.13 | 10-NOV-16:01 | 10.33 | 8.12 | 93198611.14 | 56.69 | 05-NOV-23:19 | 10.33 | 8.12 |
December | 65864720.01 | 2033.95 | 21-DEC-16:02 | 6.83 | 6.31 | 95011197.24 | 56.69 | 05-DEC-00:20 | 6.83 | 6.31 |
Annual Sum or Average | 0.654749E+10 | 0.114762E+10 | ||||||||
Minimum of Months | 65864720.01 | 2033.95 | 6.83 | 5.06 | 87321611.32 | 56.69 | 6.00 | 4.59 | ||
Maximum of Months | 0.109927E+10 | 2429.63 | 17.83 | 14.43 | 98801159.68 | 56.70 | 17.00 | 14.43 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.317618E+11 | 17834.46 | 18-JAN-23:00 | 7.80 | 7.26 | 0.189483E+11 | 11347.99 | 26-JAN-00:20 | 7.97 | 7.26 |
February | 0.290548E+11 | 17661.57 | 07-FEB-23:00 | 7.00 | 7.00 | 0.171659E+11 | 11347.92 | 17-FEB-04:19 | -2.0 | -2.3 |
March | 0.333306E+11 | 18013.98 | 20-MAR-21:10 | 4.90 | 3.99 | 0.191632E+11 | 11347.93 | 17-MAR-23:19 | 4.90 | 3.99 |
April | 0.350521E+11 | 20026.80 | 28-APR-21:10 | 11.83 | 8.82 | 0.186124E+11 | 11348.14 | 23-APR-23:19 | 11.83 | 8.82 |
May | 0.370314E+11 | 20730.19 | 22-MAY-21:32 | 14.33 | 12.38 | 0.192663E+11 | 11349.19 | 22-MAY-21:49 | 14.17 | 12.31 |
June | 0.380085E+11 | 21361.25 | 13-JUN-21:12 | 14.00 | 12.84 | 0.187166E+11 | 11349.22 | 26-JUN-21:19 | 14.00 | 14.00 |
July | 0.399282E+11 | 21365.07 | 21-JUL-21:10 | 17.00 | 13.87 | 0.192778E+11 | 11349.24 | 05-JUL-21:10 | 17.00 | 13.87 |
August | 0.395851E+11 | 20932.40 | 14-AUG-21:10 | 17.83 | 11.86 | 0.193470E+11 | 11349.19 | 17-AUG-21:30 | 14.50 | 13.02 |
September | 0.363552E+11 | 20308.46 | 12-SEP-22:00 | 16.00 | 14.13 | 0.186361E+11 | 11349.04 | 11-SEP-21:19 | 16.00 | 14.13 |
October | 0.343620E+11 | 18712.45 | 02-OCT-22:00 | 8.00 | 6.98 | 0.191285E+11 | 11348.29 | 15-OCT-23:19 | 8.00 | 7.63 |
November | 0.316099E+11 | 18350.68 | 08-NOV-23:00 | 11.00 | 11.00 | 0.183914E+11 | 11348.25 | 05-NOV-23:19 | 11.00 | 11.00 |
December | 0.313552E+11 | 17174.05 | 04-DEC-23:00 | 7.00 | 7.00 | 0.189102E+11 | 11347.91 | 08-DEC-04:19 | 3.00 | 2.51 |
Annual Sum or Average | 0.417435E+12 | 0.225564E+12 | ||||||||
Minimum of Months | 0.290548E+11 | 17174.05 | 4.90 | 3.99 | 0.171659E+11 | 11347.91 | -2.0 | -2.3 | ||
Maximum of Months | 0.399282E+11 | 21365.07 | 17.83 | 14.13 | 0.193470E+11 | 11349.24 | 17.00 | 14.13 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.355664E+11 | 19848.01 | 18-JAN-23:00 | 7.80 | 7.26 | 0.191286E+11 | 11348.03 | 26-JAN-00:20 | 7.97 | 7.26 |
February | 0.325018E+11 | 19688.96 | 07-FEB-23:00 | 7.00 | 7.00 | 0.173267E+11 | 11347.97 | 17-FEB-04:19 | -2.0 | -2.3 |
March | 0.373239E+11 | 20001.87 | 30-MAR-21:10 | 5.92 | 4.10 | 0.192991E+11 | 11347.96 | 17-MAR-23:19 | 5.92 | 4.10 |
April | 0.387529E+11 | 21590.32 | 28-APR-21:10 | 11.83 | 8.82 | 0.186824E+11 | 11348.18 | 23-APR-23:19 | 11.83 | 8.82 |
May | 0.408073E+11 | 22267.43 | 22-MAY-21:10 | 14.83 | 12.59 | 0.193201E+11 | 11349.19 | 22-MAY-21:49 | 14.17 | 12.31 |
June | 0.414767E+11 | 23233.26 | 13-JUN-21:11 | 14.00 | 12.84 | 0.187478E+11 | 11370.31 | 13-JUN-21:19 | 14.00 | 12.84 |
July | 0.433947E+11 | 22774.28 | 21-JUL-21:20 | 17.00 | 13.80 | 0.193023E+11 | 11369.61 | 21-JUL-21:19 | 17.00 | 13.80 |
August | 0.430048E+11 | 22362.62 | 14-AUG-21:20 | 17.47 | 11.81 | 0.193761E+11 | 11357.32 | 14-AUG-21:19 | 17.47 | 11.81 |
September | 0.397892E+11 | 21753.94 | 12-SEP-22:00 | 16.00 | 14.13 | 0.186819E+11 | 11349.05 | 11-SEP-21:19 | 16.00 | 14.13 |
October | 0.382411E+11 | 20547.54 | 12-OCT-22:00 | 12.00 | 10.91 | 0.192359E+11 | 11348.37 | 15-OCT-23:19 | 8.00 | 7.63 |
November | 0.353668E+11 | 20360.89 | 08-NOV-23:00 | 11.00 | 11.00 | 0.185431E+11 | 11348.33 | 05-NOV-23:19 | 11.00 | 11.00 |
December | 0.351291E+11 | 19218.20 | 04-DEC-23:00 | 7.00 | 7.00 | 0.191104E+11 | 11347.96 | 08-DEC-04:19 | 3.00 | 2.51 |
Annual Sum or Average | 0.461355E+12 | 0.226754E+12 | ||||||||
Minimum of Months | 0.325018E+11 | 19218.20 | 5.92 | 4.10 | 0.173267E+11 | 11347.96 | -2.0 | -2.3 | ||
Maximum of Months | 0.433947E+11 | 23233.26 | 17.47 | 14.13 | 0.193761E+11 | 11370.31 | 17.47 | 14.13 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.500681E+11 | 27665.45 | 21-JAN-11:33 | 6.33 | 5.22 | 0.188213E+11 | 11319.57 | 14-JAN-18:19 | 6.33 | 5.22 |
February | 0.456331E+11 | 27826.48 | 22-FEB-11:33 | 10.00 | 8.60 | 0.170009E+11 | 11319.54 | 11-FEB-18:19 | 10.00 | 8.60 |
March | 0.511509E+11 | 28575.37 | 25-MAR-10:45 | 11.42 | 8.36 | 0.188343E+11 | 11319.61 | 18-MAR-17:19 | 11.42 | 8.36 |
April | 0.526214E+11 | 30830.75 | 30-APR-10:33 | 19.33 | 11.65 | 0.182312E+11 | 11319.69 | 15-APR-17:19 | 19.33 | 11.65 |
May | 0.546516E+11 | 30625.33 | 23-MAY-10:33 | 20.00 | 14.59 | 0.188431E+11 | 11319.69 | 20-MAY-17:19 | 20.00 | 14.59 |
June | 0.541863E+11 | 30951.71 | 25-JUN-10:37 | 20.00 | 13.96 | 0.182464E+11 | 11319.67 | 10-JUN-17:19 | 20.00 | 13.96 |
July | 0.565289E+11 | 31380.43 | 23-JUL-10:40 | 21.00 | 15.99 | 0.188507E+11 | 11319.68 | 15-JUL-17:19 | 21.00 | 15.99 |
August | 0.565634E+11 | 30813.11 | 19-AUG-10:33 | 18.00 | 14.38 | 0.188585E+11 | 11319.69 | 19-AUG-17:19 | 18.00 | 14.38 |
September | 0.536262E+11 | 30394.97 | 10-SEP-10:33 | 18.67 | 14.65 | 0.182400E+11 | 11319.66 | 09-SEP-17:19 | 18.67 | 14.65 |
October | 0.523360E+11 | 29445.94 | 07-OCT-10:33 | 14.67 | 10.10 | 0.188345E+11 | 11319.63 | 21-OCT-17:19 | 8.67 | 7.29 |
November | 0.489240E+11 | 27559.67 | 11-NOV-11:50 | 9.00 | 6.94 | 0.182176E+11 | 11319.65 | 04-NOV-17:19 | 9.00 | 6.94 |
December | 0.493890E+11 | 26773.03 | 03-DEC-11:50 | 6.83 | 4.26 | 0.188183E+11 | 11319.62 | 30-DEC-18:19 | 0.00 | -0.9 |
Annual Sum or Average | 0.625679E+12 | 0.221797E+12 | ||||||||
Minimum of Months | 0.456331E+11 | 26773.03 | 6.33 | 4.26 | 0.170009E+11 | 11319.54 | 0.00 | -0.9 | ||
Maximum of Months | 0.565634E+11 | 31380.43 | 21.00 | 15.99 | 0.188585E+11 | 11319.69 | 21.00 | 15.99 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.441934E+10 | 3791.53 | 21-JAN-11:33 | 6.33 | 5.22 | 0.127038E+10 | 761.19 | 23-JAN-22:40 | 8.00 | 7.45 |
February | 0.465970E+10 | 3828.29 | 22-FEB-11:33 | 10.00 | 8.60 | 0.114988E+10 | 764.15 | 27-FEB-22:40 | 4.33 | 4.33 |
March | 0.578599E+10 | 3863.11 | 25-MAR-10:33 | 11.33 | 8.27 | 0.127836E+10 | 772.58 | 20-MAR-21:40 | 11.33 | 8.27 |
April | 0.839463E+10 | 5092.23 | 30-APR-10:33 | 19.33 | 11.65 | 0.131878E+10 | 897.91 | 30-APR-23:10 | 11.87 | 8.94 |
May | 0.902450E+10 | 5012.13 | 23-MAY-10:33 | 20.00 | 14.59 | 0.138545E+10 | 912.27 | 23-MAY-21:30 | 12.00 | 9.78 |
June | 0.955554E+10 | 5215.73 | 13-JUN-10:33 | 22.00 | 15.85 | 0.141513E+10 | 949.54 | 13-JUN-21:30 | 14.00 | 12.84 |
July | 0.102594E+11 | 5443.74 | 23-JUL-10:33 | 21.00 | 15.99 | 0.149144E+10 | 952.40 | 21-JUL-21:30 | 21.00 | 15.99 |
August | 0.102619E+11 | 5159.05 | 19-AUG-10:33 | 18.00 | 14.38 | 0.149608E+10 | 931.61 | 14-AUG-21:30 | 18.00 | 14.38 |
September | 0.929761E+10 | 4977.19 | 13-SEP-10:33 | 19.67 | 15.19 | 0.138749E+10 | 911.06 | 12-SEP-21:40 | 19.67 | 15.19 |
October | 0.735837E+10 | 4464.97 | 01-OCT-10:33 | 13.67 | 9.65 | 0.130560E+10 | 831.23 | 02-OCT-21:40 | 8.00 | 6.98 |
November | 0.519541E+10 | 3815.17 | 11-NOV-11:33 | 9.00 | 6.87 | 0.122956E+10 | 765.83 | 08-NOV-23:10 | 9.00 | 6.87 |
December | 0.348697E+10 | 3485.35 | 03-DEC-11:33 | 6.67 | 4.17 | 0.126899E+10 | 745.62 | 29-DEC-04:00 | 3.00 | 0.54 |
Annual Sum or Average | 0.876994E+11 | 0.159972E+11 | ||||||||
Minimum of Months | 0.348697E+10 | 3485.35 | 6.33 | 4.17 | 0.114988E+10 | 745.62 | 3.00 | 0.54 | ||
Maximum of Months | 0.102619E+11 | 5443.74 | 22.00 | 15.99 | 0.149608E+10 | 952.40 | 21.00 | 15.99 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 1.92 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.00 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.92 | |
Maximum of Months | 0.00 | 0.00 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 33435021.18 | 472.50 | 10-JAN-08:00 | -6.0 |
February | 9361204.17 | 318.54 | 17-FEB-07:20 | -3.7 |
March | 2164541.92 | 132.69 | 16-MAR-06:20 | 1.33 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 9845739.43 | 215.83 | 29-NOV-16:00 | 4.00 |
December | 0.102217E+09 | 431.48 | 10-DEC-16:00 | 4.00 |
Annual Sum or Average | 0.157023E+09 | |||
Minimum of Months | 0.00 | 0.00 | -6.0 | |
Maximum of Months | 0.102217E+09 | 472.50 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 1.92 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.00 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.92 | |
Maximum of Months | 0.00 | 0.00 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 1.92 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.00 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.92 | |
Maximum of Months | 0.00 | 0.00 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 7901974.69 | 125.52 | 12-JAN-15:00 | -1.0 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 393832.86 | 37.46 | 29-NOV-16:00 | 4.00 |
December | 6946150.09 | 105.22 | 30-DEC-17:00 | 1.00 |
Annual Sum or Average | 15241957.65 | |||
Minimum of Months | 0.00 | 0.00 | -1.0 | |
Maximum of Months | 7901974.69 | 125.52 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 1.92 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.00 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.92 | |
Maximum of Months | 0.00 | 0.00 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 1.92 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.00 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.92 | |
Maximum of Months | 0.00 | 0.00 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 1.92 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.00 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.92 | |
Maximum of Months | 0.00 | 0.00 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.565212E+09 | 1243.85 | 10-JAN-16:03 | -3.0 |
February | 0.390545E+09 | 1196.80 | 20-FEB-16:04 | 8.83 |
March | 0.350968E+09 | 1269.24 | 25-MAR-15:03 | 11.00 |
April | 40119210.07 | 1275.98 | 18-APR-08:03 | 9.83 |
May | 23194481.98 | 1200.87 | 08-MAY-08:03 | 9.00 |
June | 3214401.92 | 1216.67 | 06-JUN-08:03 | 12.17 |
July | 3058796.84 | 1229.96 | 02-JUL-18:04 | 13.00 |
August | 2186791.79 | 1142.66 | 08-AUG-15:04 | 17.17 |
September | 4683239.68 | 1207.08 | 19-SEP-18:04 | 13.00 |
October | 0.144031E+09 | 1209.08 | 02-OCT-08:03 | 11.17 |
November | 0.418849E+09 | 1202.02 | 29-NOV-16:13 | 3.67 |
December | 0.839622E+09 | 1211.66 | 27-DEC-16:13 | 3.00 |
Annual Sum or Average | 0.278568E+10 | |||
Minimum of Months | 2186791.79 | 1142.66 | -3.0 | |
Maximum of Months | 0.839622E+09 | 1275.98 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.764171E+09 | 1186.56 | 12-JAN-16:13 | -1.0 |
February | 0.547763E+09 | 1136.44 | 17-FEB-09:13 | 1.67 |
March | 0.420622E+09 | 1136.56 | 15-MAR-15:02 | 3.00 |
April | 65138580.07 | 1164.96 | 21-APR-08:03 | 11.83 |
May | 27397950.47 | 1224.44 | 08-MAY-08:03 | 9.00 |
June | 2680737.67 | 1174.51 | 04-JUN-18:04 | 12.83 |
July | 2948645.10 | 1195.82 | 02-JUL-18:04 | 13.00 |
August | 2162213.50 | 1090.14 | 13-AUG-08:04 | 14.17 |
September | 6792347.57 | 1198.49 | 20-SEP-18:04 | 12.33 |
October | 0.205777E+09 | 1126.18 | 01-OCT-18:04 | 11.00 |
November | 0.560616E+09 | 1184.61 | 29-NOV-16:13 | 3.67 |
December | 0.979578E+09 | 1191.06 | 27-DEC-16:13 | 3.00 |
Annual Sum or Average | 0.358565E+10 | |||
Minimum of Months | 2162213.50 | 1090.14 | -1.0 | |
Maximum of Months | 0.979578E+09 | 1224.44 | 14.17 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 1.92 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.00 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.92 | |
Maximum of Months | 0.00 | 0.00 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 33250100.36 | 321.51 | 11-JAN-16:02 | -2.2 |
February | 10369841.93 | 299.81 | 17-FEB-16:02 | 5.83 |
March | 2101683.99 | 312.85 | 25-MAR-15:04 | 11.00 |
April | 537475.22 | 310.17 | 11-APR-08:04 | 7.17 |
May | 308638.54 | 311.93 | 26-MAY-15:06 | 15.67 |
June | 175007.23 | 241.21 | 15-JUN-15:06 | 16.00 |
July | 75264.53 | 194.19 | 11-JUL-15:06 | 18.00 |
August | 214148.21 | 299.69 | 23-AUG-15:06 | 17.17 |
September | 531111.67 | 308.77 | 04-SEP-15:06 | 16.00 |
October | 1496875.00 | 316.85 | 17-OCT-15:05 | 15.67 |
November | 8339820.35 | 310.70 | 02-NOV-08:04 | 8.13 |
December | 36558756.82 | 312.44 | 27-DEC-16:02 | 3.00 |
Annual Sum or Average | 93958723.86 | |||
Minimum of Months | 75264.53 | 194.19 | -2.2 | |
Maximum of Months | 36558756.82 | 321.51 | 18.00 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.572229E+09 | 1177.80 | 04-JAN-16:13 | 3.83 |
February | 0.417404E+09 | 1125.65 | 01-FEB-16:02 | 7.00 |
March | 0.354922E+09 | 1131.04 | 15-MAR-15:02 | 3.00 |
April | 36696953.27 | 1183.33 | 01-APR-15:04 | 11.17 |
May | 23875077.10 | 1120.60 | 09-MAY-18:04 | 8.83 |
June | 4101783.46 | 1162.51 | 27-JUN-18:04 | 11.95 |
July | 2453984.26 | 1151.20 | 29-JUL-15:04 | 16.83 |
August | 1846756.57 | 1217.54 | 08-AUG-15:04 | 17.17 |
September | 3542698.83 | 1185.54 | 30-SEP-18:04 | 10.33 |
October | 0.143492E+09 | 1223.99 | 22-OCT-15:03 | 9.00 |
November | 0.422811E+09 | 1175.59 | 29-NOV-16:13 | 3.67 |
December | 0.804270E+09 | 1188.16 | 30-DEC-16:13 | 1.67 |
Annual Sum or Average | 0.278765E+10 | |||
Minimum of Months | 1846756.57 | 1120.60 | 1.67 | |
Maximum of Months | 0.804270E+09 | 1223.99 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.758123E+09 | 1169.52 | 12-JAN-16:13 | -1.0 |
February | 0.586201E+09 | 1144.34 | 16-FEB-16:01 | 6.00 |
March | 0.422762E+09 | 1118.23 | 15-MAR-15:02 | 3.00 |
April | 60683826.14 | 1146.58 | 24-APR-18:04 | 9.83 |
May | 29551399.88 | 1136.04 | 13-MAY-15:04 | 11.80 |
June | 3605989.66 | 1146.85 | 27-JUN-18:04 | 11.95 |
July | 1565279.35 | 1163.90 | 13-JUL-08:04 | 14.50 |
August | 1291612.03 | 1180.28 | 08-AUG-15:04 | 17.17 |
September | 5012755.03 | 1205.34 | 05-SEP-18:04 | 13.67 |
October | 0.202390E+09 | 1086.61 | 27-OCT-15:02 | 9.00 |
November | 0.557035E+09 | 1159.66 | 29-NOV-16:13 | 3.67 |
December | 0.928940E+09 | 1167.44 | 30-DEC-16:13 | 1.67 |
Annual Sum or Average | 0.355716E+10 | |||
Minimum of Months | 1291612.03 | 1086.61 | -1.0 | |
Maximum of Months | 0.928940E+09 | 1205.34 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 874669.46 | 81.31 | 04-JAN-14:50 | 4.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 124932.03 | 34.20 | 30-NOV-15:00 | 6.00 |
December | 3877576.62 | 174.68 | 10-DEC-16:00 | 4.00 |
Annual Sum or Average | 4877178.11 | |||
Minimum of Months | 0.00 | 0.00 | 3.80 | |
Maximum of Months | 3877576.62 | 174.68 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.953830E+09 | 1483.79 | 03-JAN-16:13 | 3.67 |
February | 0.681832E+09 | 1402.84 | 25-FEB-16:02 | 5.00 |
March | 0.632168E+09 | 1407.70 | 15-MAR-15:02 | 3.00 |
April | 0.122869E+09 | 1364.22 | 11-APR-08:61 | 7.17 |
May | 79299763.86 | 1346.57 | 05-MAY-08:62 | 8.17 |
June | 6730681.81 | 1231.70 | 01-JUN-08:03 | 12.17 |
July | 8247408.91 | 1152.20 | 01-JUL-08:03 | 13.17 |
August | 2488124.92 | 1161.71 | 08-AUG-15:04 | 17.17 |
September | 23569434.41 | 1223.06 | 30-SEP-08:03 | 11.00 |
October | 0.326462E+09 | 1375.30 | 27-OCT-15:02 | 9.00 |
November | 0.735582E+09 | 1486.81 | 29-NOV-16:13 | 3.67 |
December | 0.129553E+10 | 1497.00 | 27-DEC-16:13 | 3.00 |
Annual Sum or Average | 0.486861E+10 | |||
Minimum of Months | 2488124.92 | 1152.20 | 3.00 | |
Maximum of Months | 0.129553E+10 | 1497.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.120600E+10 | 1459.12 | 11-JAN-09:13 | -3.7 |
February | 0.883494E+09 | 1409.56 | 17-FEB-09:13 | 1.67 |
March | 0.727073E+09 | 1384.11 | 15-MAR-15:02 | 3.00 |
April | 0.173599E+09 | 1348.28 | 11-APR-08:61 | 7.17 |
May | 91843359.04 | 1324.63 | 05-MAY-08:62 | 8.17 |
June | 6214323.47 | 1195.81 | 04-JUN-18:04 | 12.83 |
July | 8008068.99 | 1243.81 | 02-JUL-18:04 | 13.00 |
August | 2183004.78 | 1187.71 | 21-AUG-08:53 | 17.00 |
September | 34876749.16 | 1056.45 | 30-SEP-18:04 | 10.33 |
October | 0.442135E+09 | 1357.63 | 11-OCT-08:61 | 9.83 |
November | 0.916584E+09 | 1456.87 | 29-NOV-16:13 | 3.67 |
December | 0.146516E+10 | 1464.21 | 27-DEC-16:13 | 3.00 |
Annual Sum or Average | 0.595718E+10 | |||
Minimum of Months | 2183004.78 | 1056.45 | -3.7 | |
Maximum of Months | 0.146516E+10 | 1464.21 | 17.00 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.193526E+09 | 798.45 | 04-JAN-16:13 | 3.83 |
February | 0.130155E+09 | 738.59 | 02-FEB-09:02 | 4.33 |
March | 0.131653E+09 | 748.04 | 15-MAR-15:02 | 3.00 |
April | 12013971.01 | 717.64 | 26-APR-08:03 | 11.83 |
May | 10845992.39 | 726.75 | 29-MAY-18:04 | 11.00 |
June | 2810724.15 | 681.92 | 06-JUN-18:04 | 11.83 |
July | 1872456.99 | 742.68 | 29-JUL-15:04 | 16.83 |
August | 1547733.35 | 658.57 | 08-AUG-15:04 | 17.17 |
September | 1759430.61 | 675.84 | 07-SEP-08:03 | 12.33 |
October | 37051813.36 | 728.60 | 27-OCT-15:02 | 9.00 |
November | 0.124709E+09 | 796.54 | 30-NOV-16:13 | 6.00 |
December | 0.343002E+09 | 806.53 | 10-DEC-16:13 | 4.00 |
Annual Sum or Average | 0.990948E+09 | |||
Minimum of Months | 1547733.35 | 658.57 | 3.00 | |
Maximum of Months | 0.343002E+09 | 806.53 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 1.92 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.00 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.92 | |
Maximum of Months | 0.00 | 0.00 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 1.92 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.00 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.92 | |
Maximum of Months | 0.00 | 0.00 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 1.92 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.00 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.92 | |
Maximum of Months | 0.00 | 0.00 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2154065.96 | 359.90 | 10-JAN-08:00 | -6.0 |
February | 282657.55 | 173.25 | 17-FEB-07:20 | -3.7 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 6.57 |
December | 577224.71 | 129.95 | 27-DEC-09:20 | -0.3 |
Annual Sum or Average | 3013948.22 | |||
Minimum of Months | 0.00 | 0.00 | -6.0 | |
Maximum of Months | 2154065.96 | 359.90 | 12.43 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.136942E+11 | 13190.31 | 02-JAN-20:10 | 0.121516E+11 | 9632.53 | 02-JAN-20:10 |
February | 0.123646E+11 | 13190.31 | 01-FEB-20:10 | 0.109726E+11 | 9632.53 | 01-FEB-20:10 |
March | 0.137364E+11 | 13190.31 | 01-MAR-20:10 | 0.121771E+11 | 9632.53 | 01-MAR-20:10 |
April | 0.132299E+11 | 13190.31 | 03-APR-19:10 | 0.117446E+11 | 9632.53 | 03-APR-19:10 |
May | 0.137180E+11 | 13190.31 | 01-MAY-19:10 | 0.121662E+11 | 9632.53 | 01-MAY-19:10 |
June | 0.132906E+11 | 13190.31 | 01-JUN-19:10 | 0.117829E+11 | 9632.53 | 01-JUN-19:10 |
July | 0.136573E+11 | 13190.31 | 03-JUL-19:10 | 0.121279E+11 | 9632.53 | 03-JUL-19:10 |
August | 0.137417E+11 | 13190.31 | 01-AUG-19:10 | 0.121808E+11 | 9632.53 | 01-AUG-19:10 |
September | 0.132352E+11 | 13190.31 | 01-SEP-19:10 | 0.117482E+11 | 9632.53 | 01-SEP-19:10 |
October | 0.136889E+11 | 13190.31 | 02-OCT-19:10 | 0.121479E+11 | 9632.53 | 02-OCT-19:10 |
November | 0.132800E+11 | 13190.31 | 01-NOV-19:10 | 0.117774E+11 | 9632.53 | 01-NOV-19:10 |
December | 0.136573E+11 | 13190.31 | 01-DEC-20:10 | 0.121279E+11 | 9632.53 | 01-DEC-20:10 |
Annual Sum or Average | 0.161294E+12 | 0.143105E+12 | ||||
Minimum of Months | 0.123646E+11 | 13190.31 | 0.109726E+11 | 9632.53 | ||
Maximum of Months | 0.137417E+11 | 13190.31 | 0.121808E+11 | 9632.53 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.620421E+09 | 597.59 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.560184E+09 | 597.59 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.622334E+09 | 597.59 | 01-MAR-20:10 | 0.866718E+09 | 685.60 | 01-MAR-20:10 |
April | 0.599386E+09 | 597.59 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.621497E+09 | 597.59 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.602135E+09 | 597.59 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.618748E+09 | 597.59 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.622573E+09 | 597.59 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.599625E+09 | 597.59 | 01-SEP-19:10 | 0.836191E+09 | 685.60 | 01-SEP-19:10 |
October | 0.620182E+09 | 597.59 | 02-OCT-19:10 | 0.864640E+09 | 685.60 | 02-OCT-19:10 |
November | 0.601657E+09 | 597.59 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.618748E+09 | 597.59 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.730749E+10 | 0.101856E+11 | ||||
Minimum of Months | 0.560184E+09 | 597.59 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.622573E+09 | 597.59 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.718450E+09 | 692.02 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.648695E+09 | 692.02 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.720665E+09 | 692.02 | 01-MAR-20:10 | 0.100366E+10 | 793.93 | 01-MAR-20:10 |
April | 0.694091E+09 | 692.02 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.719696E+09 | 692.02 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.697275E+09 | 692.02 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.716513E+09 | 692.02 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.720942E+09 | 692.02 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.694368E+09 | 692.02 | 01-SEP-19:10 | 0.968312E+09 | 793.93 | 01-SEP-19:10 |
October | 0.718174E+09 | 692.02 | 02-OCT-19:10 | 0.100126E+10 | 793.93 | 02-OCT-19:10 |
November | 0.696721E+09 | 692.02 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.716513E+09 | 692.02 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.846210E+10 | 0.117950E+11 | ||||
Minimum of Months | 0.648695E+09 | 692.02 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.720942E+09 | 692.02 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.710312E+09 | 684.18 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.641347E+09 | 684.18 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.712502E+09 | 684.18 | 01-MAR-20:10 | 0.106120E+10 | 839.45 | 01-MAR-20:10 |
April | 0.686229E+09 | 684.18 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.711544E+09 | 684.18 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.689376E+09 | 684.18 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.708397E+09 | 684.18 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.712775E+09 | 684.18 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.686503E+09 | 684.18 | 01-SEP-19:10 | 0.102382E+10 | 839.45 | 01-SEP-19:10 |
October | 0.710039E+09 | 684.18 | 02-OCT-19:10 | 0.105866E+10 | 839.45 | 02-OCT-19:10 |
November | 0.688829E+09 | 684.18 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.708397E+09 | 684.18 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.836625E+10 | 0.124712E+11 | ||||
Minimum of Months | 0.641347E+09 | 684.18 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.712775E+09 | 684.18 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.261454E+09 | 251.84 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.236069E+09 | 251.84 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.262260E+09 | 251.84 | 01-MAR-20:10 | 0.306128E+09 | 242.16 | 01-MAR-20:10 |
April | 0.252589E+09 | 251.84 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.261907E+09 | 251.84 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.253748E+09 | 251.84 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.260749E+09 | 251.84 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.262360E+09 | 251.84 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.252690E+09 | 251.84 | 01-SEP-19:10 | 0.295345E+09 | 242.16 | 01-SEP-19:10 |
October | 0.261353E+09 | 251.84 | 02-OCT-19:10 | 0.305393E+09 | 242.16 | 02-OCT-19:10 |
November | 0.253546E+09 | 251.84 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.260749E+09 | 251.84 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.307947E+10 | 0.359760E+10 | ||||
Minimum of Months | 0.236069E+09 | 251.84 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.262360E+09 | 251.84 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.337502E+09 | 325.08 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.304733E+09 | 325.08 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.338542E+09 | 325.08 | 01-MAR-20:10 | 0.578079E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.326059E+09 | 325.08 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.338087E+09 | 325.08 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.327554E+09 | 325.08 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.336592E+09 | 325.08 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.338672E+09 | 325.08 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.326189E+09 | 325.08 | 01-SEP-19:10 | 0.557718E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.337372E+09 | 325.08 | 02-OCT-19:10 | 0.576693E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.327294E+09 | 325.08 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.336592E+09 | 325.08 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.397519E+10 | 0.679355E+11 | ||||
Minimum of Months | 0.304733E+09 | 325.08 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.338672E+09 | 325.08 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.141974E+10 | 1701.53 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.120913E+10 | 1701.53 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.125940E+10 | 1701.53 | 01-MAR-20:10 | 0.122027E+10 | 965.27 | 01-MAR-20:10 |
April | 0.106959E+10 | 1701.53 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.968984E+09 | 1701.53 | 01-MAY-19:19 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.871045E+09 | 1701.53 | 01-JUN-19:30 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.918775E+09 | 1701.53 | 17-JUL-19:30 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.105931E+10 | 1701.53 | 01-AUG-19:30 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.115330E+10 | 1701.53 | 01-SEP-19:10 | 0.117729E+10 | 965.27 | 01-SEP-19:10 |
October | 0.133573E+10 | 1701.53 | 02-OCT-19:10 | 0.121734E+10 | 965.27 | 02-OCT-19:10 |
November | 0.136582E+10 | 1701.53 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.146961E+10 | 1701.53 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.141004E+11 | 0.143405E+11 | ||||
Minimum of Months | 0.871045E+09 | 1701.53 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.146961E+10 | 1701.53 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.954008E+10 | 9504.80 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.854159E+10 | 9504.80 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.942203E+10 | 9504.80 | 01-MAR-20:10 | 0.126786E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.892724E+10 | 9504.80 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.913316E+10 | 9504.80 | 01-MAY-19:19 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.878766E+10 | 9504.80 | 01-JUN-19:19 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.904831E+10 | 9504.80 | 17-JUL-19:19 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.923041E+10 | 9504.80 | 01-AUG-19:30 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.901095E+10 | 9504.80 | 01-SEP-19:10 | 0.122320E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.945687E+10 | 9504.80 | 02-OCT-19:10 | 0.126482E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.924772E+10 | 9504.80 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.957456E+10 | 9504.80 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.109921E+12 | 0.148998E+12 | ||||
Minimum of Months | 0.854159E+10 | 9504.80 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.957456E+10 | 9504.80 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196602E+09 | 177.88 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.177551E+09 | 177.88 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.195039E+09 | 177.88 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.190486E+09 | 177.88 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.195821E+09 | 177.88 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.188975E+09 | 177.88 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.197358E+09 | 177.88 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.195039E+09 | 177.88 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.190538E+09 | 177.88 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.196576E+09 | 177.88 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.189731E+09 | 177.88 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.197383E+09 | 177.88 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.231110E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.177551E+09 | 177.88 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.197383E+09 | 177.88 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196579E+09 | 177.86 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.177530E+09 | 177.86 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.195017E+09 | 177.86 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.190464E+09 | 177.86 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.195798E+09 | 177.86 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.188953E+09 | 177.86 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.197334E+09 | 177.86 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.195017E+09 | 177.86 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.190515E+09 | 177.86 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.196553E+09 | 177.86 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.189708E+09 | 177.86 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.197360E+09 | 177.86 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.231083E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.177530E+09 | 177.86 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.197360E+09 | 177.86 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123557E+09 | 111.79 | 01-JAN-19:10 | 0.217935E+09 | 232.19 | 01-JAN-08:09 |
February | 0.111584E+09 | 111.79 | 01-FEB-20:10 | 0.196843E+09 | 232.19 | 01-FEB-07:10 |
March | 0.122575E+09 | 111.79 | 01-MAR-20:10 | 0.217824E+09 | 232.19 | 01-MAR-07:10 |
April | 0.119713E+09 | 111.79 | 01-APR-18:10 | 0.210923E+09 | 232.19 | 01-APR-07:10 |
May | 0.123066E+09 | 111.79 | 01-MAY-19:10 | 0.217879E+09 | 232.19 | 01-MAY-06:10 |
June | 0.118764E+09 | 111.79 | 01-JUN-19:10 | 0.210812E+09 | 232.19 | 01-JUN-06:10 |
July | 0.124032E+09 | 111.79 | 01-JUL-18:10 | 0.217991E+09 | 232.19 | 01-JUL-07:10 |
August | 0.122575E+09 | 111.79 | 01-AUG-19:10 | 0.217824E+09 | 232.19 | 01-AUG-06:10 |
September | 0.119746E+09 | 111.79 | 01-SEP-19:10 | 0.210923E+09 | 232.19 | 01-SEP-06:10 |
October | 0.123541E+09 | 111.79 | 01-OCT-18:10 | 0.217935E+09 | 232.19 | 01-OCT-07:10 |
November | 0.119238E+09 | 111.79 | 01-NOV-19:10 | 0.210867E+09 | 232.19 | 01-NOV-06:10 |
December | 0.124048E+09 | 111.79 | 01-DEC-20:10 | 0.217991E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.145244E+10 | 0.256575E+10 | ||||
Minimum of Months | 0.111584E+09 | 111.79 | 0.196843E+09 | 232.19 | ||
Maximum of Months | 0.124048E+09 | 111.79 | 0.217991E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123591E+09 | 111.82 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 0.111614E+09 | 111.82 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 0.122608E+09 | 111.82 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 0.119746E+09 | 111.82 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 0.123099E+09 | 111.82 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 0.118796E+09 | 111.82 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 0.124066E+09 | 111.82 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 0.122608E+09 | 111.82 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 0.119778E+09 | 111.82 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 0.123574E+09 | 111.82 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 0.119271E+09 | 111.82 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 0.124082E+09 | 111.82 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.145283E+10 | 0.256645E+10 | ||||
Minimum of Months | 0.111614E+09 | 111.82 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 0.124082E+09 | 111.82 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196602E+09 | 177.88 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.177551E+09 | 177.88 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.195039E+09 | 177.88 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.190486E+09 | 177.88 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.195821E+09 | 177.88 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.188975E+09 | 177.88 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.197358E+09 | 177.88 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.195039E+09 | 177.88 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.190538E+09 | 177.88 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.196576E+09 | 177.88 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.189731E+09 | 177.88 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.197383E+09 | 177.88 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.231110E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.177551E+09 | 177.88 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.197383E+09 | 177.88 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196579E+09 | 177.86 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.177530E+09 | 177.86 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.195017E+09 | 177.86 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.190464E+09 | 177.86 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.195798E+09 | 177.86 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.188953E+09 | 177.86 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.197334E+09 | 177.86 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.195017E+09 | 177.86 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.190515E+09 | 177.86 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.196553E+09 | 177.86 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.189708E+09 | 177.86 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.197360E+09 | 177.86 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.231083E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.177530E+09 | 177.86 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.197360E+09 | 177.86 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.193865E+10 | 1867.32 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.175042E+10 | 1867.32 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.194462E+10 | 1867.32 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.187292E+10 | 1867.32 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.194201E+10 | 1867.32 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.188151E+10 | 1867.32 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.193342E+10 | 1867.32 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.194537E+10 | 1867.32 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.187367E+10 | 1867.32 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.193790E+10 | 1867.32 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.188002E+10 | 1867.32 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.193342E+10 | 1867.32 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.228339E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.175042E+10 | 1867.32 | 0.00 | 0.00 | |
Maximum of Months | 0.194537E+10 | 1867.32 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196602E+09 | 177.88 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.177551E+09 | 177.88 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.195039E+09 | 177.88 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.190486E+09 | 177.88 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.195821E+09 | 177.88 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.188975E+09 | 177.88 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.197358E+09 | 177.88 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.195039E+09 | 177.88 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.190538E+09 | 177.88 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.196576E+09 | 177.88 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.189731E+09 | 177.88 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.197383E+09 | 177.88 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.231110E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.177551E+09 | 177.88 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.197383E+09 | 177.88 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196579E+09 | 177.86 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.177530E+09 | 177.86 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.195017E+09 | 177.86 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.190464E+09 | 177.86 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.195798E+09 | 177.86 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.188953E+09 | 177.86 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.197334E+09 | 177.86 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.195017E+09 | 177.86 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.190515E+09 | 177.86 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.196553E+09 | 177.86 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.189708E+09 | 177.86 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.197360E+09 | 177.86 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.231083E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.177530E+09 | 177.86 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.197360E+09 | 177.86 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123591E+09 | 111.82 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 0.111614E+09 | 111.82 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 0.122608E+09 | 111.82 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 0.119746E+09 | 111.82 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 0.123099E+09 | 111.82 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 0.118796E+09 | 111.82 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 0.124066E+09 | 111.82 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 0.122608E+09 | 111.82 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 0.119778E+09 | 111.82 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 0.123574E+09 | 111.82 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 0.119271E+09 | 111.82 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 0.124082E+09 | 111.82 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.145283E+10 | 0.256645E+10 | ||||
Minimum of Months | 0.111614E+09 | 111.82 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 0.124082E+09 | 111.82 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.286423E+10 | 2988.03 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.250408E+10 | 2988.03 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.268933E+10 | 2988.03 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.243034E+10 | 2988.03 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.236847E+10 | 2988.03 | 01-MAY-19:19 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.223314E+10 | 2988.03 | 01-JUN-19:30 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.231335E+10 | 2988.03 | 17-JUL-19:30 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.246665E+10 | 2988.03 | 01-AUG-19:40 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.252321E+10 | 2988.03 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.276186E+10 | 2988.03 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.276225E+10 | 2988.03 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.290344E+10 | 2988.03 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.308203E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.223314E+10 | 2988.03 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.290344E+10 | 2988.03 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.286423E+10 | 2988.03 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.250408E+10 | 2988.03 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.268933E+10 | 2988.03 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.243034E+10 | 2988.03 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.236847E+10 | 2988.03 | 01-MAY-19:19 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.223314E+10 | 2988.03 | 01-JUN-19:30 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.231335E+10 | 2988.03 | 17-JUL-19:30 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.246665E+10 | 2988.03 | 01-AUG-19:40 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.252321E+10 | 2988.03 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.276186E+10 | 2988.03 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.276225E+10 | 2988.03 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.290344E+10 | 2988.03 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.308203E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.223314E+10 | 2988.03 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.290344E+10 | 2988.03 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.110133E+10 | 1060.81 | 02-JAN-20:10 | 0.368383E+11 | 16487.34 | 01-JAN-07:10 |
February | 0.994402E+09 | 1060.81 | 01-FEB-20:10 | 0.332733E+11 | 16487.34 | 01-FEB-07:10 |
March | 0.110473E+10 | 1060.81 | 01-MAR-20:10 | 0.368383E+11 | 16487.34 | 01-MAR-07:10 |
April | 0.106399E+10 | 1060.81 | 03-APR-19:10 | 0.356500E+11 | 16487.34 | 01-APR-06:10 |
May | 0.110324E+10 | 1060.81 | 01-MAY-19:10 | 0.368383E+11 | 16487.34 | 01-MAY-06:10 |
June | 0.106887E+10 | 1060.81 | 01-JUN-19:10 | 0.356500E+11 | 16487.34 | 01-JUN-06:10 |
July | 0.109836E+10 | 1060.81 | 03-JUL-19:10 | 0.368383E+11 | 16487.34 | 01-JUL-06:10 |
August | 0.110515E+10 | 1060.81 | 01-AUG-19:10 | 0.368383E+11 | 16487.34 | 01-AUG-06:10 |
September | 0.106442E+10 | 1060.81 | 01-SEP-19:10 | 0.356500E+11 | 16487.34 | 01-SEP-06:10 |
October | 0.110091E+10 | 1060.81 | 02-OCT-19:10 | 0.368383E+11 | 16487.34 | 01-OCT-06:10 |
November | 0.106802E+10 | 1060.81 | 01-NOV-19:10 | 0.356500E+11 | 16487.34 | 01-NOV-06:10 |
December | 0.109836E+10 | 1060.81 | 01-DEC-20:10 | 0.368383E+11 | 16487.34 | 01-DEC-07:10 |
Annual Sum or Average | 0.129718E+11 | 0.433742E+12 | ||||
Minimum of Months | 0.994402E+09 | 1060.81 | 0.332733E+11 | 16487.34 | ||
Maximum of Months | 0.110515E+10 | 1060.81 | 0.368383E+11 | 16487.34 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.205176E+10 | 1976.27 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.185255E+10 | 1976.27 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.205809E+10 | 1976.27 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.198220E+10 | 1976.27 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.205532E+10 | 1976.27 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.199129E+10 | 1976.27 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.204623E+10 | 1976.27 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.205888E+10 | 1976.27 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.198299E+10 | 1976.27 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.205097E+10 | 1976.27 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.198971E+10 | 1976.27 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.204623E+10 | 1976.27 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.241662E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.185255E+10 | 1976.27 | 0.00 | 0.00 | |
Maximum of Months | 0.205888E+10 | 1976.27 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.136942E+11 | 0.121516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.123646E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196682E+11 | 0.137364E+11 | 0.121771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.132299E+11 | 0.117446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.137180E+11 | 0.121662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.132906E+11 | 0.117829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.136573E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.137417E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189689E+11 | 0.132352E+11 | 0.117482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195854E+11 | 0.136889E+11 | 0.121479E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.132800E+11 | 0.117774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.136573E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230861E+12 | 0.161294E+12 | 0.143105E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.176991E+11 | 0.123646E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196682E+11 | 0.137417E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.620421E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255834E+09 |
February | 0.179968E+10 | 0.560184E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229573E+09 |
March | 0.199990E+10 | 0.622334E+09 | 0.866718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226615E+09 |
April | 0.192973E+10 | 0.599386E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 77633.73 | 0.180271E+09 |
May | 0.199475E+10 | 0.621497E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3147.92 | 0.168985E+09 |
June | 0.193394E+10 | 0.602135E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 499811.78 | 0.115995E+09 |
July | 0.199054E+10 | 0.618748E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1609732.54 | 99173311.89 |
August | 0.199896E+10 | 0.622573E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 235762.75 | 90936257.41 |
September | 0.192879E+10 | 0.599625E+09 | 0.836191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119879E+09 |
October | 0.199148E+10 | 0.620182E+09 | 0.864640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177658E+09 |
November | 0.192552E+10 | 0.601657E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209895E+09 |
December | 0.199054E+10 | 0.618748E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254138E+09 |
Annual Sum or Average | 0.234744E+11 | 0.730749E+10 | 0.101856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2426088.72 | 0.212895E+10 |
Minimum of Months | 0.179968E+10 | 0.560184E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90936257.41 |
Maximum of Months | 0.199990E+10 | 0.622573E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1609732.54 | 0.255834E+09 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.718450E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103112E+09 |
February | 0.208403E+10 | 0.648695E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92721385.02 |
March | 0.231589E+10 | 0.720665E+09 | 0.100366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92716707.77 |
April | 0.223463E+10 | 0.694091E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 27441.07 | 75898180.48 |
May | 0.230993E+10 | 0.719696E+09 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9229.76 | 72737267.56 |
June | 0.223950E+10 | 0.697275E+09 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 199166.15 | 52974155.76 |
July | 0.230505E+10 | 0.716513E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 593854.00 | 46163472.59 |
August | 0.231480E+10 | 0.720942E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 115479.94 | 42502624.35 |
September | 0.223354E+10 | 0.694368E+09 | 0.968312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52789743.53 |
October | 0.230614E+10 | 0.718174E+09 | 0.100126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74804686.85 |
November | 0.222975E+10 | 0.696721E+09 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86027847.30 |
December | 0.230505E+10 | 0.716513E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101607E+09 |
Annual Sum or Average | 0.271834E+11 | 0.846210E+10 | 0.117950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 945170.93 | 0.894055E+09 |
Minimum of Months | 0.208403E+10 | 0.648695E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42502624.35 |
Maximum of Months | 0.231589E+10 | 0.720942E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 593854.00 | 0.103112E+09 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.487480E+09 | 0.710312E+09 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233847E+09 |
February | 0.440737E+09 | 0.641347E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209082E+09 |
March | 0.489771E+09 | 0.712502E+09 | 0.106120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209970E+09 |
April | 0.472586E+09 | 0.686229E+09 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 115212.68 | 0.170546E+09 |
May | 0.488511E+09 | 0.711544E+09 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49199.54 | 0.164883E+09 |
June | 0.473617E+09 | 0.689376E+09 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 540556.36 | 0.121596E+09 |
July | 0.487480E+09 | 0.708397E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1425527.85 | 0.106529E+09 |
August | 0.489542E+09 | 0.712775E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 346138.43 | 97172828.41 |
September | 0.472357E+09 | 0.686503E+09 | 0.102382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11352.22 | 0.119533E+09 |
October | 0.487709E+09 | 0.710039E+09 | 0.105866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169082E+09 |
November | 0.471555E+09 | 0.688829E+09 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194362E+09 |
December | 0.487480E+09 | 0.708397E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232147E+09 |
Annual Sum or Average | 0.574883E+10 | 0.836625E+10 | 0.124712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2487987.08 | 0.202875E+10 |
Minimum of Months | 0.440737E+09 | 0.641347E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97172828.41 |
Maximum of Months | 0.489771E+09 | 0.712775E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1425527.85 | 0.233847E+09 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.374985E+09 | 0.261454E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133837E+09 |
February | 0.339028E+09 | 0.236069E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119684E+09 |
March | 0.376747E+09 | 0.262260E+09 | 0.306128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119467E+09 |
April | 0.363528E+09 | 0.252589E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 72408.85 | 95879328.32 |
May | 0.375778E+09 | 0.261907E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 31009.56 | 92532144.10 |
June | 0.364321E+09 | 0.253748E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 330513.50 | 67898791.37 |
July | 0.374985E+09 | 0.260749E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 856751.49 | 59226279.76 |
August | 0.376571E+09 | 0.262360E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 218117.14 | 53781629.39 |
September | 0.363352E+09 | 0.252690E+09 | 0.295345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11640.51 | 66550905.05 |
October | 0.375161E+09 | 0.261353E+09 | 0.305393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94684029.82 |
November | 0.362735E+09 | 0.253546E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110201E+09 |
December | 0.374985E+09 | 0.260749E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133377E+09 |
Annual Sum or Average | 0.442217E+10 | 0.307947E+10 | 0.359760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1520441.06 | 0.114712E+10 |
Minimum of Months | 0.339028E+09 | 0.236069E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53781629.39 |
Maximum of Months | 0.376747E+09 | 0.262360E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 856751.49 | 0.133837E+09 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.337502E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.353788E+09 |
February | 0.139600E+10 | 0.304733E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.316574E+09 |
March | 0.155131E+10 | 0.338542E+09 | 0.578079E+10 | 0.502211E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318961E+09 |
April | 0.149688E+10 | 0.326059E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 151640.56 | 0.251549E+09 |
May | 0.154732E+10 | 0.338087E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 43008.21 | 0.240997E+09 |
June | 0.150015E+10 | 0.327554E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 768463.73 | 0.172625E+09 |
July | 0.154405E+10 | 0.336592E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 2112257.86 | 0.148396E+09 |
August | 0.155059E+10 | 0.338672E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 538497.90 | 0.134496E+09 |
September | 0.149615E+10 | 0.326189E+09 | 0.557718E+10 | 0.484522E+11 | 0.00 | 0.00 | 0.00 | 57423.48 | 0.169767E+09 |
October | 0.154478E+10 | 0.337372E+09 | 0.576693E+10 | 0.501006E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.252538E+09 |
November | 0.149361E+10 | 0.327294E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295925E+09 |
December | 0.154405E+10 | 0.336592E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.352343E+09 |
Annual Sum or Average | 0.182090E+11 | 0.397519E+10 | 0.679355E+11 | 0.590196E+12 | 0.00 | 0.00 | 0.00 | 3671291.74 | 0.300796E+10 |
Minimum of Months | 0.139600E+10 | 0.304733E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134496E+09 |
Maximum of Months | 0.155131E+10 | 0.338672E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 2112257.86 | 0.353788E+09 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.141974E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.581216E+09 |
February | 0.236489E+11 | 0.120913E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.523493E+09 |
March | 0.262800E+11 | 0.125940E+10 | 0.122027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.517030E+09 |
April | 0.253579E+11 | 0.106959E+10 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 155642.12 | 0.425525E+09 |
May | 0.262123E+11 | 0.968984E+09 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3167.03 | 0.401407E+09 |
June | 0.254132E+11 | 0.871045E+09 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1009281.29 | 0.286280E+09 |
July | 0.261570E+11 | 0.918775E+09 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3309138.83 | 0.249205E+09 |
August | 0.262677E+11 | 0.105931E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 470276.74 | 0.233231E+09 |
September | 0.253456E+11 | 0.115330E+10 | 0.117729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295834E+09 |
October | 0.261693E+11 | 0.133573E+10 | 0.121734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.417329E+09 |
November | 0.253025E+11 | 0.136582E+10 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.481347E+09 |
December | 0.261570E+11 | 0.146961E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.572833E+09 |
Annual Sum or Average | 0.308468E+12 | 0.141004E+11 | 0.143405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4947506.00 | 0.498473E+10 |
Minimum of Months | 0.236489E+11 | 0.871045E+09 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233231E+09 |
Maximum of Months | 0.262800E+11 | 0.146961E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3309138.83 | 0.581216E+09 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.954008E+10 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172300E+10 |
February | 0.702046E+11 | 0.854159E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154923E+10 |
March | 0.780153E+11 | 0.942203E+10 | 0.126786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154903E+10 |
April | 0.752779E+11 | 0.892724E+10 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 513976.09 | 0.126658E+10 |
May | 0.778146E+11 | 0.913316E+10 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 119577.28 | 0.121127E+10 |
June | 0.754422E+11 | 0.878766E+10 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3232942.14 | 0.882125E+09 |
July | 0.776503E+11 | 0.904831E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 9628617.35 | 0.769463E+09 |
August | 0.779788E+11 | 0.923041E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1736616.26 | 0.711005E+09 |
September | 0.752414E+11 | 0.901095E+10 | 0.122320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.885893E+09 |
October | 0.776868E+11 | 0.945687E+10 | 0.126482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125435E+10 |
November | 0.751137E+11 | 0.924772E+10 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144080E+10 |
December | 0.776503E+11 | 0.957456E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169905E+10 |
Annual Sum or Average | 0.915726E+12 | 0.109921E+12 | 0.148998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 15231729.13 | 0.149418E+11 |
Minimum of Months | 0.702046E+11 | 0.854159E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.711005E+09 |
Maximum of Months | 0.780153E+11 | 0.957456E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 9628617.35 | 0.172300E+10 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196602E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147496E+09 |
February | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132983E+09 |
March | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132140E+09 |
April | 0.293479E+09 | 0.190486E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 104711.00 | 0.105504E+09 |
May | 0.303504E+09 | 0.195821E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 29554.17 | 0.100142E+09 |
June | 0.293842E+09 | 0.188975E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 436180.75 | 69594840.02 |
July | 0.303141E+09 | 0.197358E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1153887.33 | 58143789.33 |
August | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 327400.69 | 51671206.08 |
September | 0.293479E+09 | 0.190538E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 112235.72 | 68037477.14 |
October | 0.303322E+09 | 0.196576E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103077E+09 |
November | 0.293661E+09 | 0.189731E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121391E+09 |
December | 0.303141E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145387E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231110E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2163969.64 | 0.123557E+10 |
Minimum of Months | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51671206.08 |
Maximum of Months | 0.303685E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1153887.33 | 0.147496E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196579E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145599E+09 |
February | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131206E+09 |
March | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131222E+09 |
April | 0.293479E+09 | 0.190464E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 103971.55 | 0.105220E+09 |
May | 0.303504E+09 | 0.195798E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7471.52 | 0.101102E+09 |
June | 0.293842E+09 | 0.188953E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 391020.56 | 72422803.76 |
July | 0.303141E+09 | 0.197334E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1042292.30 | 64222738.25 |
August | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 261580.02 | 57420182.76 |
September | 0.293479E+09 | 0.190515E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9313.33 | 69748848.01 |
October | 0.303322E+09 | 0.196553E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101766E+09 |
November | 0.293661E+09 | 0.189708E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119826E+09 |
December | 0.303141E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144123E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231083E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1815649.28 | 0.124388E+10 |
Minimum of Months | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57420182.76 |
Maximum of Months | 0.303685E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1042292.30 | 0.145599E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.123557E+09 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51350214.15 |
February | 0.00 | 0.111584E+09 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46533710.47 |
March | 0.00 | 0.122575E+09 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45970808.07 |
April | 0.00 | 0.119713E+09 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40873656.87 |
May | 0.00 | 0.123066E+09 | 0.217879E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39769997.31 |
June | 0.00 | 0.118764E+09 | 0.210812E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 326.19 | 30630010.10 |
July | 0.00 | 0.124032E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 54662.58 | 27600073.32 |
August | 0.00 | 0.122575E+09 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1073.36 | 25985260.81 |
September | 0.00 | 0.119746E+09 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30330051.59 |
October | 0.00 | 0.123541E+09 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40482644.14 |
November | 0.00 | 0.119238E+09 | 0.210867E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44301787.06 |
December | 0.00 | 0.124048E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43265810.31 |
Annual Sum or Average | 0.00 | 0.145244E+10 | 0.256575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56062.12 | 0.467094E+09 |
Minimum of Months | 0.00 | 0.111584E+09 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25985260.81 |
Maximum of Months | 0.00 | 0.124048E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 54662.58 | 51350214.15 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.123591E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41378633.40 |
February | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37112960.16 |
March | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37286294.50 |
April | 0.293479E+09 | 0.119746E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30159.11 | 29161292.66 |
May | 0.303504E+09 | 0.123099E+09 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4046.71 | 27827295.59 |
June | 0.293842E+09 | 0.118796E+09 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 115556.90 | 19507813.76 |
July | 0.303141E+09 | 0.124066E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 300559.42 | 16661033.65 |
August | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 81082.97 | 14824195.60 |
September | 0.293479E+09 | 0.119778E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6248.66 | 18797485.57 |
October | 0.303322E+09 | 0.123574E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28735953.81 |
November | 0.293661E+09 | 0.119271E+09 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34142299.04 |
December | 0.303141E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41158187.88 |
Annual Sum or Average | 0.357224E+10 | 0.145283E+10 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 537653.76 | 0.346593E+09 |
Minimum of Months | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14824195.60 |
Maximum of Months | 0.303685E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 300559.42 | 41378633.40 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196602E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147483E+09 |
February | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132999E+09 |
March | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132407E+09 |
April | 0.293479E+09 | 0.190486E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 106849.19 | 0.106232E+09 |
May | 0.303504E+09 | 0.195821E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 29889.33 | 0.100740E+09 |
June | 0.293842E+09 | 0.188975E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 440547.12 | 69842563.75 |
July | 0.303141E+09 | 0.197358E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1150174.64 | 58406366.70 |
August | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 330173.83 | 51886146.12 |
September | 0.293479E+09 | 0.190538E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 114746.43 | 68426227.63 |
October | 0.303322E+09 | 0.196576E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103406E+09 |
November | 0.293661E+09 | 0.189731E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121377E+09 |
December | 0.303141E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145531E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231110E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2172380.55 | 0.123874E+10 |
Minimum of Months | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51886146.12 |
Maximum of Months | 0.303685E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1150174.64 | 0.147483E+09 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196579E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145588E+09 |
February | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131006E+09 |
March | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131518E+09 |
April | 0.293479E+09 | 0.190464E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 106422.02 | 0.106202E+09 |
May | 0.303504E+09 | 0.195798E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9203.03 | 0.101354E+09 |
June | 0.293842E+09 | 0.188953E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 394630.63 | 71726057.80 |
July | 0.303141E+09 | 0.197334E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1030786.71 | 61960198.35 |
August | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 265965.54 | 55826325.26 |
September | 0.293479E+09 | 0.190515E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10923.89 | 69833347.40 |
October | 0.303322E+09 | 0.196553E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102296E+09 |
November | 0.293661E+09 | 0.189708E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119770E+09 |
December | 0.303141E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144274E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231083E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1817931.82 | 0.124135E+10 |
Minimum of Months | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55826325.26 |
Maximum of Months | 0.303685E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1030786.71 | 0.145588E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.385223E+10 | 0.193865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178872E+09 |
February | 0.348285E+10 | 0.175042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160103E+09 |
March | 0.387034E+10 | 0.194462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159605E+09 |
April | 0.373454E+10 | 0.187292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79352.64 | 0.128966E+09 |
May | 0.386038E+10 | 0.194201E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34501.49 | 0.124747E+09 |
June | 0.374269E+10 | 0.188151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 425954.96 | 90560417.56 |
July | 0.385223E+10 | 0.193342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1143706.53 | 78875294.58 |
August | 0.386853E+10 | 0.194537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 255999.25 | 71982988.17 |
September | 0.373273E+10 | 0.187367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3000.36 | 89311210.77 |
October | 0.385404E+10 | 0.193790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125977E+09 |
November | 0.372639E+10 | 0.188002E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146892E+09 |
December | 0.385223E+10 | 0.193342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178298E+09 |
Annual Sum or Average | 0.454292E+11 | 0.228339E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1942515.22 | 0.153419E+10 |
Minimum of Months | 0.348285E+10 | 0.175042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71982988.17 |
Maximum of Months | 0.387034E+10 | 0.194537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1143706.53 | 0.178872E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196602E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147014E+09 |
February | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132656E+09 |
March | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131919E+09 |
April | 0.293479E+09 | 0.190486E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 99785.66 | 0.105858E+09 |
May | 0.303504E+09 | 0.195821E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 27895.68 | 0.100473E+09 |
June | 0.293842E+09 | 0.188975E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 420655.87 | 69989747.81 |
July | 0.303141E+09 | 0.197358E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1127056.45 | 58562585.95 |
August | 0.303685E+09 | 0.195039E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 316498.25 | 52070898.95 |
September | 0.293479E+09 | 0.190538E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 104677.55 | 68345366.12 |
October | 0.303322E+09 | 0.196576E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102955E+09 |
November | 0.293661E+09 | 0.189731E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120977E+09 |
December | 0.303141E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145015E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231110E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2096569.45 | 0.123583E+10 |
Minimum of Months | 0.273974E+09 | 0.177551E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52070898.95 |
Maximum of Months | 0.303685E+09 | 0.197383E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1127056.45 | 0.147014E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.196579E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145167E+09 |
February | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130731E+09 |
March | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130931E+09 |
April | 0.293479E+09 | 0.190464E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 99480.73 | 0.105779E+09 |
May | 0.303504E+09 | 0.195798E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6436.80 | 0.101770E+09 |
June | 0.293842E+09 | 0.188953E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 377346.35 | 73314782.58 |
July | 0.303141E+09 | 0.197334E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1019147.77 | 65611629.42 |
August | 0.303685E+09 | 0.195017E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 253732.61 | 58654240.60 |
September | 0.293479E+09 | 0.190515E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8417.96 | 70441292.99 |
October | 0.303322E+09 | 0.196553E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101503E+09 |
November | 0.293661E+09 | 0.189708E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119308E+09 |
December | 0.303141E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143871E+09 |
Annual Sum or Average | 0.357224E+10 | 0.231083E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1764562.22 | 0.124708E+10 |
Minimum of Months | 0.273974E+09 | 0.177530E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58654240.60 |
Maximum of Months | 0.303685E+09 | 0.197360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1019147.77 | 0.145167E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.123591E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76938487.82 |
February | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69207109.32 |
March | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68744073.80 |
April | 0.293479E+09 | 0.119746E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 52618.48 | 54547738.06 |
May | 0.303504E+09 | 0.123099E+09 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14585.22 | 51671025.95 |
June | 0.293842E+09 | 0.118796E+09 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 218289.23 | 35843407.80 |
July | 0.303141E+09 | 0.124066E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 579262.46 | 29991511.69 |
August | 0.303685E+09 | 0.122608E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 163296.28 | 26668108.21 |
September | 0.293479E+09 | 0.119778E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 53339.67 | 35190176.44 |
October | 0.303322E+09 | 0.123574E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53641679.60 |
November | 0.293661E+09 | 0.119271E+09 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63393330.58 |
December | 0.303141E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75885500.81 |
Annual Sum or Average | 0.357224E+10 | 0.145283E+10 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1081391.35 | 0.641722E+09 |
Minimum of Months | 0.273974E+09 | 0.111614E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26668108.21 |
Maximum of Months | 0.303685E+09 | 0.124082E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 579262.46 | 76938487.82 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.286423E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.417179E+09 |
February | 0.415303E+11 | 0.250408E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.374310E+09 |
March | 0.461508E+11 | 0.268933E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.380081E+09 |
April | 0.445315E+11 | 0.243034E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.304817E+09 |
May | 0.460320E+11 | 0.236847E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.294060E+09 |
June | 0.446286E+11 | 0.223314E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 299372.04 | 0.215605E+09 |
July | 0.459349E+11 | 0.231335E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1589759.00 | 0.188554E+09 |
August | 0.461292E+11 | 0.246665E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 224616.42 | 0.172819E+09 |
September | 0.445099E+11 | 0.252321E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211651E+09 |
October | 0.459565E+11 | 0.276186E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.304313E+09 |
November | 0.444343E+11 | 0.276225E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.351520E+09 |
December | 0.459349E+11 | 0.290344E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.415265E+09 |
Annual Sum or Average | 0.541708E+12 | 0.308203E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2113747.46 | 0.363017E+10 |
Minimum of Months | 0.415303E+11 | 0.223314E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172819E+09 |
Maximum of Months | 0.461508E+11 | 0.290344E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1589759.00 | 0.417179E+09 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.286423E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421094E+09 |
February | 0.415303E+11 | 0.250408E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.377758E+09 |
March | 0.461508E+11 | 0.268933E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383386E+09 |
April | 0.445315E+11 | 0.243034E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306698E+09 |
May | 0.460320E+11 | 0.236847E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295620E+09 |
June | 0.446286E+11 | 0.223314E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 299363.23 | 0.216575E+09 |
July | 0.459349E+11 | 0.231335E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1565052.78 | 0.189265E+09 |
August | 0.461292E+11 | 0.246665E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 224491.03 | 0.173726E+09 |
September | 0.445099E+11 | 0.252321E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212952E+09 |
October | 0.459565E+11 | 0.276186E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306998E+09 |
November | 0.444343E+11 | 0.276225E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.354950E+09 |
December | 0.459349E+11 | 0.290344E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.419424E+09 |
Annual Sum or Average | 0.541708E+12 | 0.308203E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2088907.04 | 0.365845E+10 |
Minimum of Months | 0.415303E+11 | 0.223314E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173726E+09 |
Maximum of Months | 0.461508E+11 | 0.290344E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1565052.78 | 0.421094E+09 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.110133E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.377589E+09 |
February | 0.369574E+10 | 0.994402E+09 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.337902E+09 |
March | 0.410691E+10 | 0.110473E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.342537E+09 |
April | 0.396281E+10 | 0.106399E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273040E+09 |
May | 0.409635E+10 | 0.110324E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263143E+09 |
June | 0.397146E+10 | 0.106887E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 270004.44 | 0.192656E+09 |
July | 0.408770E+10 | 0.109836E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 1398983.56 | 0.168191E+09 |
August | 0.410499E+10 | 0.110515E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 202058.41 | 0.154581E+09 |
September | 0.396089E+10 | 0.106442E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189665E+09 |
October | 0.408962E+10 | 0.110091E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274234E+09 |
November | 0.395417E+10 | 0.106802E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.317863E+09 |
December | 0.408770E+10 | 0.109836E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.376199E+09 |
Annual Sum or Average | 0.482060E+11 | 0.129718E+11 | 0.392709E+12 | 0.359593E+12 | 0.00 | 0.00 | 0.00 | 1871046.41 | 0.326760E+10 |
Minimum of Months | 0.369574E+10 | 0.994402E+09 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154581E+09 |
Maximum of Months | 0.410691E+10 | 0.110515E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 1398983.56 | 0.377589E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.407704E+10 | 0.205176E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.317782E+09 |
February | 0.368610E+10 | 0.185255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284608E+09 |
March | 0.409620E+10 | 0.205809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283576E+09 |
April | 0.395248E+10 | 0.198220E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50437.77 | 0.229143E+09 |
May | 0.408566E+10 | 0.205532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8078.49 | 0.220395E+09 |
June | 0.396110E+10 | 0.199129E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 413326.15 | 0.161462E+09 |
July | 0.407704E+10 | 0.204623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1640207.18 | 0.140952E+09 |
August | 0.409429E+10 | 0.205888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 294683.53 | 0.127464E+09 |
September | 0.395056E+10 | 0.198299E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155982E+09 |
October | 0.407896E+10 | 0.205097E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221547E+09 |
November | 0.394385E+10 | 0.198971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261082E+09 |
December | 0.407704E+10 | 0.204623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.316699E+09 |
Annual Sum or Average | 0.480803E+11 | 0.241662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2406733.12 | 0.272069E+10 |
Minimum of Months | 0.368610E+10 | 0.185255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127464E+09 |
Maximum of Months | 0.409620E+10 | 0.205888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1640207.18 | 0.317782E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 13190.31 | 02-JAN-20:10 | 9632.53 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 13190.31 | 01-FEB-20:10 | 9632.53 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 13190.31 | 01-MAR-20:10 | 9632.53 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 13190.31 | 03-APR-19:10 | 9632.53 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 13190.31 | 01-MAY-19:10 | 9632.53 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 13190.31 | 01-JUN-19:10 | 9632.53 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 13190.31 | 03-JUL-19:10 | 9632.53 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 13190.31 | 01-AUG-19:10 | 9632.53 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 13190.31 | 01-SEP-19:10 | 9632.53 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 01-OCT-23:10 | 13190.31 | 02-OCT-19:10 | 9632.53 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 13190.31 | 01-NOV-19:10 | 9632.53 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 13190.31 | 01-DEC-20:10 | 9632.53 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 11501.89 | 13190.31 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 13190.31 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 597.59 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 156.64 | 11-JAN-24:00 |
February | 1169.53 | 01-FEB-00:10 | 597.59 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 145.14 | 17-FEB-07:00 |
March | 1169.53 | 01-MAR-00:10 | 597.59 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 125.83 | 08-MAR-07:00 |
April | 1169.53 | 01-APR-00:10 | 597.59 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.07 | 30-APR-18:00 | 119.43 | 08-APR-06:00 |
May | 1169.53 | 01-MAY-00:10 | 597.59 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.52 | 22-MAY-15:00 | 108.37 | 06-MAY-05:00 |
June | 1169.53 | 01-JUN-00:10 | 597.59 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.57 | 13-JUN-17:00 | 84.10 | 07-JUN-05:00 |
July | 1169.53 | 01-JUL-00:10 | 597.59 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.85 | 22-JUL-18:00 | 78.21 | 31-JUL-05:00 |
August | 1169.53 | 01-AUG-00:10 | 597.59 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.46 | 14-AUG-18:00 | 72.25 | 20-AUG-05:00 |
September | 1169.53 | 01-SEP-00:10 | 597.59 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 90.29 | 21-SEP-06:00 |
October | 1169.53 | 01-OCT-23:10 | 597.59 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 107.63 | 15-OCT-04:00 |
November | 1169.53 | 01-NOV-00:10 | 597.59 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 133.88 | 29-NOV-02:00 |
December | 1169.53 | 01-DEC-00:10 | 597.59 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 138.11 | 29-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1169.53 | 597.59 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.25 | |||||
Maximum of Months | 1169.53 | 597.59 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 35.85 | 156.64 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 692.02 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 63.52 | 11-JAN-24:00 |
February | 1354.32 | 01-FEB-00:10 | 692.02 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 58.02 | 17-FEB-07:00 |
March | 1354.32 | 01-MAR-00:10 | 692.02 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 50.93 | 08-MAR-07:00 |
April | 1354.32 | 01-APR-00:10 | 692.02 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.11 | 30-APR-17:00 | 49.48 | 08-APR-05:02 |
May | 1354.32 | 01-MAY-00:10 | 692.02 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.27 | 22-MAY-15:00 | 44.99 | 06-MAY-05:00 |
June | 1354.32 | 01-JUN-00:10 | 692.02 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.71 | 13-JUN-17:00 | 36.57 | 07-JUN-05:00 |
July | 1354.32 | 01-JUL-00:10 | 692.02 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.24 | 22-JUL-18:00 | 34.65 | 31-JUL-05:00 |
August | 1354.32 | 01-AUG-00:10 | 692.02 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.70 | 14-AUG-17:00 | 32.61 | 23-AUG-04:00 |
September | 1354.32 | 01-SEP-00:10 | 692.02 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 39.92 | 20-SEP-24:00 |
October | 1354.32 | 01-OCT-23:10 | 692.02 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 45.61 | 07-OCT-04:00 |
November | 1354.32 | 01-NOV-00:10 | 692.02 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 54.11 | 29-NOV-02:00 |
December | 1354.32 | 01-DEC-00:10 | 692.02 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 56.62 | 29-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1354.32 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.61 | |||||
Maximum of Months | 1354.32 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 12.24 | 63.52 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 286.42 | 02-JAN-00:10 | 684.18 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 142.89 | 11-JAN-24:00 |
February | 286.42 | 01-FEB-00:10 | 684.18 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 132.41 | 17-FEB-07:00 |
March | 286.42 | 01-MAR-00:10 | 684.18 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 115.69 | 08-MAR-07:00 |
April | 286.42 | 01-APR-00:10 | 684.18 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.40 | 30-APR-17:00 | 112.66 | 08-APR-06:00 |
May | 286.42 | 01-MAY-00:10 | 684.18 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.24 | 22-MAY-15:00 | 102.46 | 07-MAY-05:00 |
June | 286.42 | 01-JUN-00:10 | 684.18 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.73 | 13-JUN-17:00 | 83.09 | 07-JUN-05:00 |
July | 286.42 | 01-JUL-00:10 | 684.18 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.56 | 22-JUL-18:00 | 79.55 | 31-JUL-05:00 |
August | 286.42 | 01-AUG-00:10 | 684.18 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.22 | 14-AUG-17:00 | 75.65 | 20-AUG-05:00 |
September | 286.42 | 01-SEP-00:10 | 684.18 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.04 | 11-SEP-17:00 | 90.49 | 20-SEP-24:00 |
October | 286.42 | 01-OCT-23:10 | 684.18 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 103.48 | 07-OCT-04:00 |
November | 286.42 | 01-NOV-00:10 | 684.18 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 122.13 | 29-NOV-02:00 |
December | 286.42 | 01-DEC-00:10 | 684.18 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 127.47 | 29-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 286.42 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.65 | |||||
Maximum of Months | 286.42 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 30.56 | 142.89 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 220.32 | 02-JAN-00:10 | 251.84 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 82.44 | 11-JAN-24:00 |
February | 220.32 | 01-FEB-00:10 | 251.84 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 76.39 | 17-FEB-07:00 |
March | 220.32 | 01-MAR-00:10 | 251.84 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 66.23 | 08-MAR-07:00 |
April | 220.32 | 01-APR-00:10 | 251.84 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.45 | 30-APR-17:00 | 63.69 | 08-APR-06:00 |
May | 220.32 | 01-MAY-00:10 | 251.84 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.96 | 22-MAY-15:00 | 57.93 | 07-MAY-05:00 |
June | 220.32 | 01-JUN-00:10 | 251.84 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.54 | 13-JUN-17:00 | 46.90 | 01-JUN-05:00 |
July | 220.32 | 01-JUL-00:10 | 251.84 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.99 | 22-JUL-18:00 | 44.88 | 31-JUL-05:00 |
August | 220.32 | 01-AUG-00:10 | 251.84 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.88 | 14-AUG-17:00 | 42.53 | 20-AUG-05:00 |
September | 220.32 | 01-SEP-00:10 | 251.84 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.49 | 11-SEP-17:00 | 51.03 | 20-SEP-24:00 |
October | 220.32 | 01-OCT-23:10 | 251.84 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 58.68 | 07-OCT-04:00 |
November | 220.32 | 01-NOV-00:10 | 251.84 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 70.46 | 29-NOV-02:00 |
December | 220.32 | 01-DEC-00:10 | 251.84 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 72.70 | 29-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 220.32 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.53 | |||||
Maximum of Months | 220.32 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 17.99 | 82.44 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 325.08 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 216.54 | 11-JAN-24:00 |
February | 907.20 | 01-FEB-00:10 | 325.08 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 202.40 | 17-FEB-07:00 |
March | 907.20 | 01-MAR-00:10 | 325.08 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 178.05 | 08-MAR-07:00 |
April | 907.20 | 01-APR-00:10 | 325.08 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 17.57 | 30-APR-17:00 | 164.38 | 08-APR-06:00 |
May | 907.20 | 01-MAY-00:10 | 325.08 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 8.35 | 22-MAY-15:18 | 148.52 | 07-MAY-05:10 |
June | 907.20 | 01-JUN-00:10 | 325.08 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 32.73 | 13-JUN-17:00 | 124.05 | 08-JUN-05:10 |
July | 907.20 | 01-JUL-00:10 | 325.08 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 45.56 | 21-JUL-17:00 | 115.50 | 05-JUL-05:10 |
August | 907.20 | 01-AUG-00:10 | 325.08 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 32.48 | 14-AUG-17:00 | 110.73 | 24-AUG-06:00 |
September | 907.20 | 01-SEP-00:10 | 325.08 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 6.11 | 11-SEP-17:00 | 133.53 | 21-SEP-06:00 |
October | 907.20 | 01-OCT-23:10 | 325.08 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 148.35 | 04-OCT-06:00 |
November | 907.20 | 01-NOV-00:10 | 325.08 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 180.77 | 28-NOV-23:10 |
December | 907.20 | 01-DEC-00:10 | 325.08 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 193.54 | 29-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 907.20 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 110.73 | ||||||
Maximum of Months | 907.20 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 45.56 | 216.54 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 1701.53 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 360.95 | 11-JAN-24:00 |
February | 15368.40 | 01-FEB-00:10 | 1701.53 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 324.24 | 18-FEB-02:00 |
March | 15368.40 | 01-MAR-00:10 | 1701.53 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 281.90 | 08-MAR-07:00 |
April | 15368.40 | 01-APR-00:10 | 1701.53 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.77 | 30-APR-18:00 | 279.31 | 08-APR-05:00 |
May | 15368.40 | 01-MAY-00:10 | 1701.53 | 01-MAY-19:19 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.79 | 22-MAY-15:00 | 254.52 | 06-MAY-05:00 |
June | 15368.40 | 01-JUN-00:10 | 1701.53 | 01-JUN-19:30 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.43 | 13-JUN-17:00 | 205.47 | 01-JUN-05:00 |
July | 15368.40 | 01-JUL-00:10 | 1701.53 | 17-JUL-19:30 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.29 | 22-JUL-18:00 | 194.53 | 31-JUL-05:00 |
August | 15368.40 | 01-AUG-00:10 | 1701.53 | 01-AUG-19:30 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.72 | 14-AUG-18:00 | 182.87 | 23-AUG-04:00 |
September | 15368.40 | 01-SEP-00:10 | 1701.53 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 225.93 | 20-SEP-24:00 |
October | 15368.40 | 01-OCT-23:10 | 1701.53 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 258.29 | 07-OCT-04:00 |
November | 15368.40 | 01-NOV-00:10 | 1701.53 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 307.68 | 29-NOV-02:00 |
December | 15368.40 | 01-DEC-00:10 | 1701.53 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 316.73 | 29-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 15368.40 | 1701.53 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.87 | |||||
Maximum of Months | 15368.40 | 1701.53 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 76.29 | 360.95 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 9504.80 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1062.09 | 11-JAN-24:00 |
February | 45622.98 | 01-FEB-00:10 | 9504.80 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 965.45 | 17-FEB-07:00 |
March | 45622.98 | 01-MAR-00:10 | 9504.80 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 850.85 | 08-MAR-07:00 |
April | 45622.98 | 01-APR-00:10 | 9504.80 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.68 | 30-APR-17:00 | 830.38 | 08-APR-05:00 |
May | 45622.98 | 01-MAY-00:10 | 9504.80 | 01-MAY-19:19 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.06 | 22-MAY-15:00 | 759.00 | 06-MAY-05:00 |
June | 45622.98 | 01-JUN-00:10 | 9504.80 | 01-JUN-19:19 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 131.24 | 13-JUN-17:00 | 617.73 | 07-JUN-05:00 |
July | 45622.98 | 01-JUL-00:10 | 9504.80 | 17-JUL-19:19 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 206.92 | 22-JUL-18:00 | 585.76 | 31-JUL-05:00 |
August | 45622.98 | 01-AUG-00:10 | 9504.80 | 01-AUG-19:30 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 127.87 | 14-AUG-17:00 | 550.21 | 23-AUG-04:00 |
September | 45622.98 | 01-SEP-00:10 | 9504.80 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 669.68 | 20-SEP-24:00 |
October | 45622.98 | 01-OCT-23:10 | 9504.80 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 766.29 | 07-OCT-04:00 |
November | 45622.98 | 01-NOV-00:10 | 9504.80 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 911.74 | 29-NOV-02:00 |
December | 45622.98 | 01-DEC-00:10 | 9504.80 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 946.28 | 29-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 45622.98 | 9504.80 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 550.21 | |||||
Maximum of Months | 45622.98 | 9504.80 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 206.92 | 1062.09 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.88 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 91.43 | 11-JAN-24:00 |
February | 180.00 | 01-FEB-00:10 | 177.88 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 84.76 | 17-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 177.88 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 73.55 | 08-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 177.88 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.64 | 30-APR-19:00 | 69.83 | 08-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 177.88 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.13 | 22-MAY-15:10 | 63.41 | 06-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 177.88 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.54 | 13-JUN-17:00 | 49.31 | 07-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 177.88 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.71 | 22-JUL-18:10 | 45.89 | 31-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 177.88 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.58 | 14-AUG-17:00 | 42.43 | 20-AUG-05:00 |
September | 180.00 | 01-SEP-00:10 | 177.88 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.61 | 11-SEP-17:00 | 52.91 | 21-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 177.88 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 62.97 | 15-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 177.88 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 78.22 | 29-NOV-02:00 |
December | 180.00 | 01-DEC-00:10 | 177.88 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 80.68 | 29-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.43 | |||||
Maximum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 25.71 | 91.43 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.86 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 91.42 | 11-JAN-24:00 |
February | 180.00 | 01-FEB-00:10 | 177.86 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 84.75 | 17-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 177.86 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 73.54 | 08-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 177.86 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.64 | 30-APR-18:50 | 69.82 | 08-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 177.86 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.13 | 22-MAY-15:10 | 63.40 | 06-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 177.86 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.54 | 13-JUN-17:00 | 49.30 | 07-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 177.86 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.44 | 22-JUL-18:10 | 45.89 | 31-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 177.86 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.58 | 14-AUG-17:00 | 42.43 | 20-AUG-05:00 |
September | 180.00 | 01-SEP-00:10 | 177.86 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.61 | 13-SEP-15:10 | 52.91 | 21-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 177.86 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 62.97 | 15-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 177.86 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 78.22 | 29-NOV-02:00 |
December | 180.00 | 01-DEC-00:10 | 177.86 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 80.67 | 29-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.43 | |||||
Maximum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 25.44 | 91.42 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 111.79 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 29.47 | 11-JAN-24:00 |
February | 0.00 | 01-FEB-00:10 | 111.79 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 27.87 | 17-FEB-21:00 |
March | 0.00 | 01-MAR-00:10 | 111.79 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 23.65 | 14-MAR-21:00 |
April | 0.00 | 01-APR-00:10 | 111.79 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 23.83 | 08-APR-06:00 |
May | 0.00 | 01-MAY-00:10 | 111.79 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 22.01 | 07-MAY-05:00 |
June | 0.00 | 01-JUN-00:10 | 111.79 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.24 | 13-JUN-17:00 | 18.33 | 01-JUN-04:20 |
July | 0.00 | 01-JUL-00:10 | 111.79 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.72 | 22-JUL-18:00 | 17.57 | 31-JUL-05:00 |
August | 0.00 | 01-AUG-00:10 | 111.79 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.24 | 14-AUG-17:04 | 16.84 | 20-AUG-05:00 |
September | 0.00 | 01-SEP-00:10 | 111.79 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 19.84 | 21-SEP-06:00 |
October | 0.00 | 01-OCT-00:10 | 111.79 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 22.31 | 07-OCT-04:00 |
November | 0.00 | 01-NOV-00:10 | 111.79 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 25.24 | 28-NOV-21:00 |
December | 0.00 | 01-DEC-00:10 | 111.79 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 24.32 | 26-DEC-20:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 0.00 | 111.79 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.84 | |||||
Maximum of Months | 0.00 | 111.79 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 2.72 | 29.47 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 111.82 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 25.52 | 11-JAN-24:00 |
February | 180.00 | 01-FEB-00:10 | 111.82 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 23.66 | 17-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 111.82 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 20.53 | 08-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 111.82 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.41 | 30-APR-19:00 | 19.49 | 08-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 111.82 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.27 | 22-MAY-15:10 | 17.70 | 06-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 111.82 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.90 | 13-JUN-17:00 | 13.76 | 07-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 111.82 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.18 | 22-JUL-18:10 | 12.81 | 31-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 111.82 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.91 | 14-AUG-17:00 | 11.84 | 20-AUG-05:00 |
September | 180.00 | 01-SEP-00:10 | 111.82 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.57 | 13-SEP-15:10 | 14.77 | 21-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 111.82 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 17.58 | 15-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 111.82 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 21.83 | 29-NOV-02:00 |
December | 180.00 | 01-DEC-00:10 | 111.82 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 22.52 | 29-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.84 | |||||
Maximum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 7.18 | 25.52 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.88 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 91.43 | 11-JAN-24:00 |
February | 180.00 | 01-FEB-00:10 | 177.88 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 84.76 | 17-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 177.88 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 73.55 | 08-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 177.88 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.64 | 30-APR-19:00 | 69.83 | 08-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 177.88 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.13 | 22-MAY-15:10 | 63.41 | 06-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 177.88 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.54 | 13-JUN-17:00 | 49.31 | 07-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 177.88 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.71 | 22-JUL-18:10 | 45.89 | 31-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 177.88 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.58 | 14-AUG-17:00 | 42.43 | 20-AUG-05:00 |
September | 180.00 | 01-SEP-00:10 | 177.88 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.61 | 11-SEP-17:00 | 52.91 | 21-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 177.88 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 62.97 | 15-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 177.88 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 78.22 | 29-NOV-02:00 |
December | 180.00 | 01-DEC-00:10 | 177.88 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 80.68 | 29-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.43 | |||||
Maximum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 25.71 | 91.43 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.86 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 91.42 | 11-JAN-24:00 |
February | 180.00 | 01-FEB-00:10 | 177.86 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 84.75 | 17-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 177.86 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 73.54 | 08-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 177.86 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.64 | 30-APR-19:00 | 69.82 | 08-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 177.86 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.13 | 22-MAY-15:10 | 63.40 | 06-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 177.86 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.54 | 13-JUN-17:00 | 49.30 | 07-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 177.86 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.71 | 22-JUL-18:10 | 45.89 | 31-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 177.86 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.58 | 14-AUG-17:00 | 42.43 | 20-AUG-05:00 |
September | 180.00 | 01-SEP-00:10 | 177.86 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.61 | 13-SEP-15:09 | 52.91 | 21-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 177.86 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 62.97 | 15-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 177.86 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 78.22 | 29-NOV-02:00 |
December | 180.00 | 01-DEC-00:10 | 177.86 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 80.67 | 29-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.43 | |||||
Maximum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 25.71 | 91.42 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2263.36 | 02-JAN-00:10 | 1867.32 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 110.11 | 11-JAN-24:00 |
February | 2263.36 | 01-FEB-00:10 | 1867.32 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 102.05 | 17-FEB-07:00 |
March | 2263.36 | 01-MAR-00:10 | 1867.32 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 88.49 | 08-MAR-07:00 |
April | 2263.36 | 01-APR-00:10 | 1867.32 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.12 | 30-APR-17:00 | 85.45 | 08-APR-05:00 |
May | 2263.36 | 01-MAY-00:10 | 1867.32 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.05 | 22-MAY-15:00 | 78.27 | 06-MAY-05:00 |
June | 2263.36 | 01-JUN-00:10 | 1867.32 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.42 | 13-JUN-17:00 | 62.85 | 07-JUN-05:00 |
July | 2263.36 | 01-JUL-00:10 | 1867.32 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.28 | 22-JUL-18:00 | 60.21 | 31-JUL-05:00 |
August | 2263.36 | 01-AUG-00:10 | 1867.32 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.48 | 14-AUG-17:00 | 56.97 | 23-AUG-04:00 |
September | 2263.36 | 01-SEP-00:10 | 1867.32 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.40 | 11-SEP-17:00 | 68.42 | 20-SEP-24:00 |
October | 2263.36 | 01-OCT-23:10 | 1867.32 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 79.28 | 07-OCT-04:00 |
November | 2263.36 | 01-NOV-00:10 | 1867.32 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 94.13 | 29-NOV-02:00 |
December | 2263.36 | 01-DEC-00:10 | 1867.32 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 97.11 | 29-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.97 | ||||
Maximum of Months | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.28 | 110.11 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.88 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 91.65 | 11-JAN-24:00 |
February | 180.00 | 01-FEB-00:10 | 177.88 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 84.98 | 17-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 177.88 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 73.76 | 08-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 177.88 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.46 | 30-APR-18:50 | 70.04 | 08-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 177.88 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.90 | 22-MAY-15:10 | 63.62 | 06-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 177.88 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.36 | 13-JUN-17:00 | 49.51 | 07-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 177.88 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.49 | 22-JUL-18:10 | 46.09 | 31-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 177.88 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.40 | 14-AUG-17:00 | 42.63 | 20-AUG-05:00 |
September | 180.00 | 01-SEP-00:10 | 177.88 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.43 | 11-SEP-17:00 | 53.12 | 21-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 177.88 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 63.18 | 15-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 177.88 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 78.44 | 29-NOV-02:00 |
December | 180.00 | 01-DEC-00:10 | 177.88 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 80.89 | 29-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.63 | |||||
Maximum of Months | 180.00 | 177.88 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 25.49 | 91.65 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 177.86 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 91.64 | 11-JAN-24:00 |
February | 180.00 | 01-FEB-00:10 | 177.86 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 84.97 | 17-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 177.86 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 73.75 | 08-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 177.86 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.46 | 30-APR-19:00 | 70.03 | 08-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 177.86 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.90 | 22-MAY-15:10 | 63.61 | 06-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 177.86 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.36 | 13-JUN-17:00 | 49.51 | 07-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 177.86 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.72 | 22-JUL-18:10 | 46.09 | 31-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 177.86 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.40 | 14-AUG-17:00 | 42.63 | 20-AUG-05:00 |
September | 180.00 | 01-SEP-00:10 | 177.86 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.43 | 13-SEP-15:10 | 53.11 | 21-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 177.86 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 63.18 | 15-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 177.86 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 78.43 | 29-NOV-02:00 |
December | 180.00 | 01-DEC-00:10 | 177.86 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 80.88 | 29-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.63 | |||||
Maximum of Months | 180.00 | 177.86 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 24.72 | 91.64 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 111.82 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 46.89 | 11-JAN-24:00 |
February | 180.00 | 01-FEB-00:10 | 111.82 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 43.48 | 17-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 111.82 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 37.74 | 08-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 111.82 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 30-APR-19:00 | 35.83 | 08-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 111.82 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.07 | 22-MAY-15:10 | 32.55 | 06-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 111.82 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.88 | 13-JUN-17:00 | 25.33 | 07-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 111.82 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.07 | 22-JUL-18:10 | 23.58 | 31-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 111.82 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.90 | 14-AUG-17:00 | 21.81 | 20-AUG-05:00 |
September | 180.00 | 01-SEP-00:10 | 111.82 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.78 | 11-SEP-17:00 | 27.18 | 21-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 111.82 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 32.33 | 15-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 111.82 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 40.13 | 29-NOV-02:00 |
December | 180.00 | 01-DEC-00:10 | 111.82 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 41.39 | 29-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.81 | |||||
Maximum of Months | 180.00 | 111.82 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 13.07 | 46.89 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2988.03 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 247.49 | 11-JAN-24:00 |
February | 26988.77 | 01-FEB-00:10 | 2988.03 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 231.23 | 17-FEB-07:00 |
March | 26988.77 | 01-MAR-00:10 | 2988.03 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 203.49 | 08-MAR-07:00 |
April | 26988.77 | 01-APR-00:10 | 2988.03 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 194.26 | 08-APR-06:00 |
May | 26988.77 | 01-MAY-00:10 | 2988.03 | 01-MAY-19:19 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 178.65 | 06-MAY-05:00 |
June | 26988.77 | 01-JUN-00:10 | 2988.03 | 01-JUN-19:30 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.25 | 13-JUN-17:00 | 143.80 | 07-JUN-05:00 |
July | 26988.77 | 01-JUL-00:10 | 2988.03 | 17-JUL-19:30 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.67 | 22-JUL-18:00 | 135.39 | 31-JUL-05:00 |
August | 26988.77 | 01-AUG-00:10 | 2988.03 | 01-AUG-19:40 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.30 | 14-AUG-17:00 | 126.81 | 20-AUG-05:00 |
September | 26988.77 | 01-SEP-00:10 | 2988.03 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 152.77 | 21-SEP-06:00 |
October | 26988.77 | 01-OCT-23:10 | 2988.03 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 176.90 | 07-OCT-04:00 |
November | 26988.77 | 01-NOV-00:10 | 2988.03 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 215.32 | 29-NOV-02:00 |
December | 26988.77 | 01-DEC-00:10 | 2988.03 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 221.05 | 29-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.81 | |||||
Maximum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 42.67 | 247.49 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2988.03 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 247.49 | 11-JAN-24:00 |
February | 26988.77 | 01-FEB-00:10 | 2988.03 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 231.23 | 17-FEB-07:00 |
March | 26988.77 | 01-MAR-00:10 | 2988.03 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 203.49 | 08-MAR-07:00 |
April | 26988.77 | 01-APR-00:10 | 2988.03 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 194.27 | 08-APR-06:00 |
May | 26988.77 | 01-MAY-00:10 | 2988.03 | 01-MAY-19:19 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 178.65 | 06-MAY-05:00 |
June | 26988.77 | 01-JUN-00:10 | 2988.03 | 01-JUN-19:30 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.25 | 13-JUN-17:00 | 143.80 | 07-JUN-05:00 |
July | 26988.77 | 01-JUL-00:10 | 2988.03 | 17-JUL-19:30 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.67 | 22-JUL-18:00 | 135.39 | 31-JUL-05:00 |
August | 26988.77 | 01-AUG-00:10 | 2988.03 | 01-AUG-19:40 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.30 | 14-AUG-17:00 | 126.82 | 20-AUG-05:00 |
September | 26988.77 | 01-SEP-00:10 | 2988.03 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 152.78 | 21-SEP-06:00 |
October | 26988.77 | 01-OCT-23:10 | 2988.03 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 177.44 | 15-OCT-04:00 |
November | 26988.77 | 01-NOV-00:10 | 2988.03 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 215.32 | 29-NOV-02:00 |
December | 26988.77 | 01-DEC-00:10 | 2988.03 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 221.05 | 29-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.82 | |||||
Maximum of Months | 26988.77 | 2988.03 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 42.67 | 247.49 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 1060.81 | 02-JAN-20:10 | 14912.86 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 221.55 | 11-JAN-24:00 |
February | 2401.70 | 01-FEB-00:10 | 1060.81 | 01-FEB-20:10 | 14912.86 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 206.97 | 17-FEB-07:00 |
March | 2401.70 | 01-MAR-00:10 | 1060.81 | 01-MAR-20:10 | 14912.86 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 182.13 | 08-MAR-07:00 |
April | 2401.70 | 01-APR-00:10 | 1060.81 | 03-APR-19:10 | 14912.86 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 173.88 | 08-APR-06:00 |
May | 2401.70 | 01-MAY-00:10 | 1060.81 | 01-MAY-19:10 | 14912.86 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 158.65 | 06-MAY-05:10 |
June | 2401.70 | 01-JUN-00:10 | 1060.81 | 01-JUN-19:10 | 14912.86 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 19.10 | 13-JUN-17:00 | 128.12 | 08-JUN-05:00 |
July | 2401.70 | 01-JUL-00:10 | 1060.81 | 03-JUL-19:10 | 14912.86 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 38.28 | 22-JUL-18:00 | 120.92 | 05-JUL-05:00 |
August | 2401.70 | 01-AUG-00:10 | 1060.81 | 01-AUG-19:10 | 14912.86 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 19.16 | 14-AUG-17:00 | 113.49 | 24-AUG-06:00 |
September | 2401.70 | 01-SEP-00:10 | 1060.81 | 01-SEP-19:10 | 14912.86 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 136.74 | 21-SEP-06:00 |
October | 2401.70 | 01-OCT-23:10 | 1060.81 | 02-OCT-19:10 | 14912.86 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 153.51 | 07-OCT-04:00 |
November | 2401.70 | 01-NOV-00:10 | 1060.81 | 01-NOV-19:10 | 14912.86 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 184.90 | 29-NOV-00:10 |
December | 2401.70 | 01-DEC-00:10 | 1060.81 | 01-DEC-20:10 | 14912.86 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 197.83 | 29-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2401.70 | 1060.81 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 0.00 | 113.49 | ||||||
Maximum of Months | 2401.70 | 1060.81 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 38.28 | 221.55 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2395.44 | 02-JAN-00:10 | 1976.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 195.29 | 11-JAN-24:00 |
February | 2395.44 | 01-FEB-00:10 | 1976.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 181.02 | 17-FEB-07:00 |
March | 2395.44 | 01-MAR-00:10 | 1976.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 157.02 | 08-MAR-07:00 |
April | 2395.44 | 01-APR-00:10 | 1976.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.49 | 30-APR-18:00 | 149.06 | 08-APR-06:00 |
May | 2395.44 | 01-MAY-00:10 | 1976.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.72 | 22-MAY-15:00 | 135.33 | 06-MAY-05:00 |
June | 2395.44 | 01-JUN-00:10 | 1976.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.53 | 13-JUN-17:00 | 108.78 | 01-JUN-04:00 |
July | 2395.44 | 01-JUL-00:10 | 1976.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.66 | 22-JUL-18:00 | 103.08 | 31-JUL-05:00 |
August | 2395.44 | 01-AUG-00:10 | 1976.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.72 | 14-AUG-18:00 | 97.31 | 20-AUG-05:00 |
September | 2395.44 | 01-SEP-00:10 | 1976.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 117.91 | 20-SEP-24:00 |
October | 2395.44 | 01-OCT-23:10 | 1976.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 134.52 | 07-OCT-04:00 |
November | 2395.44 | 01-NOV-00:10 | 1976.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 167.02 | 29-NOV-02:00 |
December | 2395.44 | 01-DEC-00:10 | 1976.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 172.29 | 29-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.31 | ||||
Maximum of Months | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.66 | 195.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 14141.82 | 20-JAN-21:00 | 8945.92 | 13190.31 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 13866.90 | 12-FEB-11:33 | 11501.89 | 13190.31 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 13723.23 | 25-MAR-10:33 | 11501.89 | 10992.10 | 10646.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 15032.55 | 30-APR-10:33 | 11501.89 | 13190.31 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 14662.97 | 21-MAY-10:33 | 11501.89 | 13190.31 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 15262.50 | 25-JUN-10:33 | 11501.89 | 13190.31 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 15664.44 | 23-JUL-10:33 | 11501.89 | 13190.31 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 15742.60 | 19-AUG-10:33 | 11501.89 | 10992.10 | 10646.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17084.64 | 29-SEP-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17846.80 | 06-OCT-21:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17416.61 | 17-NOV-22:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16511.61 | 01-DEC-22:00 | 10223.90 | 11724.66 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 13723.23 | 8945.92 | 10992.10 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17846.80 | 11501.89 | 13190.31 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2626.98 | 21-JAN-11:33 | 1169.53 | 497.99 | 757.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.91 |
February | 3075.05 | 04-FEB-13:30 | 389.84 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.71 |
March | 2138.10 | 25-MAR-10:33 | 1169.53 | 497.99 | 757.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.26 |
April | 3244.01 | 29-APR-13:10 | 389.84 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.62 |
May | 2677.52 | 23-MAY-10:33 | 779.69 | 497.99 | 757.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.01 |
June | 2702.82 | 13-JUN-10:33 | 779.69 | 497.99 | 757.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.40 |
July | 3138.06 | 22-JUL-13:30 | 389.84 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 20.59 | 0.00 |
August | 3218.65 | 19-AUG-13:10 | 779.69 | 332.00 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.70 |
September | 3973.57 | 27-SEP-13:20 | 519.79 | 332.00 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.07 |
October | 3625.13 | 07-OCT-13:10 | 779.69 | 332.00 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.49 |
November | 2589.50 | 11-NOV-11:33 | 1169.53 | 597.59 | 866.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.09 |
December | 2349.27 | 08-DEC-11:33 | 779.69 | 497.99 | 757.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.72 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2138.10 | 389.84 | 166.00 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3973.57 | 1169.53 | 597.59 | 866.03 | 0.00 | 0.00 | 0.00 | 0.00 | 20.59 | 94.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1179.64 | 20-JAN-21:00 | 1053.36 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.08 |
February | 1161.67 | 27-FEB-21:00 | 1053.36 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.94 |
March | 1178.08 | 20-MAR-20:00 | 1053.36 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.30 |
April | 1486.69 | 28-APR-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.20 |
May | 1516.22 | 23-MAY-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.28 |
June | 1680.17 | 13-JUN-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.87 |
July | 1702.79 | 21-JUL-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.49 |
August | 1636.51 | 14-AUG-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.96 |
September | 1651.73 | 13-SEP-21:00 | 1203.84 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.16 |
October | 1336.49 | 01-OCT-10:33 | 1354.32 | 692.02 | 1002.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.01 |
November | 1188.15 | 10-NOV-21:00 | 1053.36 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.29 |
December | 1127.44 | 21-DEC-21:00 | 1053.36 | 692.02 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.36 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1127.44 | 1053.36 | 615.12 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.96 | |
Maximum of Months | 1702.79 | 1354.32 | 692.02 | 1002.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.08 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 759.35 | 21-JAN-11:33 | 286.42 | 570.15 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.63 |
February | 757.16 | 22-FEB-11:33 | 190.94 | 570.15 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.92 |
March | 788.19 | 25-MAR-10:33 | 286.42 | 570.15 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.88 |
April | 1016.98 | 30-APR-10:33 | 286.42 | 684.18 | 1060.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.23 |
May | 992.78 | 23-MAY-10:33 | 190.94 | 570.15 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.38 |
June | 1040.49 | 13-JUN-10:33 | 190.94 | 570.15 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.45 |
July | 1109.61 | 23-JUL-10:33 | 286.42 | 684.18 | 1060.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.26 |
August | 1055.17 | 19-AUG-10:33 | 286.42 | 570.15 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.82 |
September | 1012.79 | 13-SEP-10:33 | 190.94 | 570.15 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.77 |
October | 941.92 | 01-OCT-10:33 | 286.42 | 684.18 | 1060.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.22 |
November | 791.97 | 11-NOV-11:33 | 286.42 | 684.18 | 1060.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.51 |
December | 713.74 | 21-DEC-21:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.71 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 713.74 | 190.94 | 570.15 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.45 | |
Maximum of Months | 1109.61 | 286.42 | 684.18 | 1060.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.71 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 406.22 | 18-JAN-21:00 | 171.36 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.79 |
February | 402.05 | 22-FEB-21:00 | 171.36 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.23 |
March | 422.13 | 19-MAR-10:33 | 220.32 | 251.83 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.16 |
April | 589.83 | 30-APR-10:33 | 220.32 | 251.83 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.29 |
May | 576.20 | 23-MAY-10:33 | 146.88 | 209.86 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.10 |
June | 604.98 | 13-JUN-10:33 | 146.88 | 209.86 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.56 |
July | 643.44 | 23-JUL-10:33 | 220.32 | 251.83 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.95 |
August | 609.62 | 19-AUG-10:33 | 220.32 | 209.86 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.12 |
September | 586.18 | 13-SEP-10:33 | 146.88 | 209.86 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.97 |
October | 539.29 | 01-OCT-10:33 | 220.32 | 251.83 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.14 |
November | 448.31 | 11-NOV-11:33 | 220.32 | 251.83 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.71 |
December | 390.24 | 20-DEC-21:00 | 171.36 | 251.84 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 390.24 | 146.88 | 209.86 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.56 | |
Maximum of Months | 643.44 | 220.32 | 251.84 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.23 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 36869.21 | 23-JAN-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 102.54 |
February | 36863.66 | 22-FEB-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 131.19 |
March | 36970.50 | 30-MAR-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 118.05 |
April | 37972.37 | 28-APR-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 74.29 |
May | 38077.22 | 23-MAY-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 67.46 |
June | 38354.92 | 13-JUN-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 46.63 |
July | 38335.63 | 21-JUL-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 19.80 |
August | 38224.98 | 14-AUG-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 21.78 |
September | 38104.51 | 13-SEP-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 60.29 |
October | 37522.58 | 06-OCT-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 110.07 |
November | 36972.61 | 10-NOV-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 140.54 |
December | 36652.95 | 20-DEC-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 117.51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 36652.95 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 19.80 | |
Maximum of Months | 38354.92 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 140.54 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10876.69 | 21-JAN-11:33 | 15368.40 | 311.95 | 1066.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 214.30 |
February | 12365.53 | 04-FEB-13:30 | 5122.80 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.81 |
March | 9092.99 | 25-MAR-10:33 | 15368.40 | 311.95 | 1066.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.11 |
April | 12459.24 | 29-APR-13:00 | 5122.80 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.60 |
May | 10669.33 | 23-MAY-10:33 | 10245.60 | 311.95 | 1066.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.78 |
June | 11001.85 | 25-JUN-10:33 | 15368.40 | 374.34 | 1219.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.18 |
July | 11737.42 | 22-JUL-13:30 | 5122.80 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 45.52 | 0.00 |
August | 12401.92 | 28-AUG-15:03 | 59766.00 | 727.88 | 2489.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.03 |
September | 13962.76 | 23-SEP-12:30 | 5122.80 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.13 |
October | 13803.47 | 07-OCT-13:00 | 5122.80 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.86 |
November | 10856.72 | 11-NOV-11:33 | 15368.40 | 374.34 | 1219.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.69 |
December | 9542.01 | 08-DEC-11:33 | 10245.60 | 311.95 | 1066.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.34 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9092.99 | 5122.80 | 103.98 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13962.76 | 59766.00 | 727.88 | 2489.39 | 0.00 | 0.00 | 0.00 | 0.00 | 45.52 | 214.30 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 28164.13 | 21-JAN-11:33 | 45622.98 | 6811.77 | 11084.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 577.97 |
February | 27773.39 | 04-FEB-11:33 | 45622.98 | 6811.77 | 11084.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 522.93 |
March | 27009.95 | 20-MAR-20:00 | 35484.54 | 9504.80 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 567.98 |
April | 32901.58 | 30-APR-10:33 | 45622.98 | 8174.13 | 12668.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.06 |
May | 32826.11 | 23-MAY-20:14 | 202768.80 | 42243.55 | 47506.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 365.80 |
June | 34665.07 | 13-JUN-21:12 | 456229.80 | 63365.33 | 73899.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 341.53 |
July | 35456.98 | 21-JUL-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 237.03 |
August | 35311.30 | 18-AUG-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 289.57 |
September | 35847.30 | 12-SEP-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 301.06 |
October | 31515.98 | 03-OCT-21:10 | 45622.98 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 562.64 |
November | 28669.19 | 11-NOV-11:33 | 45622.98 | 8174.13 | 12668.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 488.22 |
December | 26079.01 | 21-DEC-21:00 | 35484.54 | 9504.80 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 751.46 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 26079.01 | 35484.54 | 6336.53 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.06 | |
Maximum of Months | 35847.30 | 456229.80 | 63365.33 | 73899.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 751.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3152.51 | 19-JAN-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.73 |
February | 3210.69 | 27-FEB-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.28 |
March | 2945.96 | 23-MAR-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.57 |
April | 3312.10 | 29-APR-08:61 | 378.00 | 697.30 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.32 |
May | 3487.01 | 11-MAY-18:03 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.81 |
June | 3454.14 | 05-JUN-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.95 |
July | 3433.57 | 18-JUL-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.08 |
August | 3410.10 | 15-AUG-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.50 |
September | 3453.84 | 10-SEP-18:01 | 819.00 | 1245.18 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.60 |
October | 3371.46 | 10-OCT-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.27 |
November | 3249.30 | 10-NOV-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.52 |
December | 412.63 | 19-DEC-19:05 | 831.60 | 949.89 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.26 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 412.63 | 378.00 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.60 | |
Maximum of Months | 3487.01 | 970.20 | 1245.18 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.73 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2720.63 | 19-JAN-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.92 |
February | 2952.18 | 27-FEB-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.09 |
March | 2706.72 | 23-MAR-18:01 | 970.20 | 1108.08 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.67 |
April | 3323.82 | 28-APR-19:01 | 1386.00 | 1778.61 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.15 |
May | 3564.35 | 11-MAY-19:31 | 1247.40 | 1600.75 | 1469.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.51 |
June | 3574.82 | 22-JUN-19:01 | 1386.00 | 1778.61 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.62 |
July | 3633.96 | 28-JUL-17:52 | 583.20 | 715.00 | 758.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.36 |
August | 3572.23 | 01-AUG-19:31 | 1386.00 | 1778.61 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.48 |
September | 3611.44 | 14-SEP-18:01 | 1386.00 | 1582.97 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.95 |
October | 3348.14 | 06-OCT-18:01 | 970.20 | 1108.08 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.63 |
November | 2816.26 | 10-NOV-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.92 |
December | 207.16 | 20-DEC-19:06 | 693.00 | 791.48 | 605.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 207.16 | 583.20 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.51 | |
Maximum of Months | 3633.96 | 1386.00 | 1778.61 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.67 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 455.06 | 21-JAN-11:25 | 0.00 | 73.78 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.75 |
February | 392.28 | 19-FEB-14:05 | 0.00 | 73.78 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.69 |
March | 145.95 | 25-MAR-14:05 | 0.00 | 73.78 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.93 |
April | 572.93 | 30-APR-12:50 | 0.00 | 36.89 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 |
May | 447.24 | 22-MAY-13:05 | 0.00 | 62.60 | 61.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.88 |
June | 447.53 | 13-JUN-13:20 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.99 |
July | 517.18 | 22-JUL-13:30 | 0.00 | 36.89 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 1.07 | 0.00 |
August | 559.64 | 20-AUG-13:00 | 0.00 | 36.89 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 |
September | 696.41 | 27-SEP-13:20 | 0.00 | 62.60 | 61.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.59 |
October | 647.88 | 07-OCT-13:00 | 0.00 | 36.89 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.42 |
November | 416.04 | 11-NOV-13:30 | 0.00 | 36.89 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.89 |
December | 136.28 | 26-DEC-15:05 | 0.00 | 62.60 | 61.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.36 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 136.28 | 0.00 | 31.30 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 696.41 | 0.00 | 73.78 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 1.07 | 18.75 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 836.09 | 29-JAN-09:02 | 216.00 | 250.48 | 639.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.47 |
February | 783.12 | 27-FEB-19:02 | 693.00 | 497.61 | 593.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.47 |
March | 858.49 | 19-MAR-08:62 | 270.00 | 313.10 | 799.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.87 |
April | 962.04 | 14-APR-15:02 | 583.20 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.75 |
May | 1021.40 | 11-MAY-19:31 | 1247.40 | 1006.40 | 1439.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.96 |
June | 1030.14 | 08-JUN-19:11 | 1247.40 | 1006.40 | 1439.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.84 |
July | 1016.57 | 10-JUL-21:51 | 1800.00 | 749.21 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.84 |
August | 981.65 | 28-AUG-15:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.92 | 0.00 |
September | 952.09 | 13-SEP-19:31 | 1386.00 | 1118.23 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.15 |
October | 973.73 | 07-OCT-18:01 | 819.00 | 782.76 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.18 |
November | 854.03 | 23-NOV-09:02 | 216.00 | 250.48 | 639.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.22 |
December | 794.32 | 02-DEC-09:02 | 270.00 | 313.10 | 799.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 783.12 | 216.00 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1030.14 | 1800.00 | 1118.23 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.92 | 14.47 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2732.93 | 19-JAN-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.33 |
February | 2878.82 | 27-FEB-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.46 |
March | 2829.54 | 25-MAR-15:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.68 |
April | 3001.25 | 21-APR-08:62 | 216.00 | 469.61 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.00 |
May | 3447.12 | 11-MAY-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.67 |
June | 3144.11 | 16-JUN-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.66 |
July | 3168.02 | 26-JUL-08:61 | 252.00 | 547.88 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.76 |
August | 3191.52 | 06-AUG-08:61 | 378.00 | 697.30 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.36 |
September | 3161.22 | 09-SEP-08:62 | 324.00 | 597.68 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.05 |
October | 3379.19 | 06-OCT-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.25 |
November | 2813.42 | 10-NOV-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.48 |
December | 483.93 | 26-DEC-09:04 | 180.00 | 391.34 | 566.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.37 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 483.93 | 180.00 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.67 | |
Maximum of Months | 3447.12 | 970.20 | 1108.21 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 441.19 | 21-JAN-09:02 | 270.00 | 498.01 | 816.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.22 |
February | 2455.53 | 23-FEB-09:02 | 216.00 | 469.55 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.68 |
March | 2211.03 | 25-MAR-15:01 | 378.00 | 410.86 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.41 |
April | 3139.46 | 28-APR-08:51 | 360.00 | 782.59 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.54 |
May | 3280.43 | 23-MAY-08:51 | 360.00 | 782.59 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.86 |
June | 3500.91 | 13-JUN-08:32 | 180.00 | 391.30 | 566.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.79 |
July | 3687.85 | 23-JUL-08:32 | 324.00 | 597.61 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.95 |
August | 3426.69 | 17-AUG-08:51 | 360.00 | 782.59 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.78 |
September | 3406.68 | 11-SEP-08:51 | 360.00 | 782.59 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.52 |
October | 2984.61 | 06-OCT-18:01 | 970.20 | 1108.08 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.90 |
November | 1996.28 | 11-NOV-09:02 | 270.00 | 498.01 | 816.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.83 |
December | 335.72 | 20-DEC-09:06 | 180.00 | 391.30 | 566.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 335.72 | 180.00 | 391.30 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.79 | |
Maximum of Months | 3687.85 | 970.20 | 1108.08 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.22 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1794.21 | 21-JAN-11:33 | 2263.36 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.24 |
February | 1780.99 | 04-FEB-11:33 | 2263.36 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.41 |
March | 1694.42 | 20-MAR-18:10 | 12322.72 | 11618.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.32 |
April | 2403.88 | 30-APR-10:33 | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.74 |
May | 2311.76 | 23-MAY-10:33 | 1508.90 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.26 |
June | 2404.28 | 13-JUN-10:33 | 1508.90 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.86 |
July | 2552.44 | 23-JUL-10:33 | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.61 |
August | 2461.25 | 19-AUG-10:33 | 2263.36 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.85 |
September | 2364.32 | 13-SEP-10:33 | 1508.90 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.95 |
October | 2220.35 | 01-OCT-10:33 | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.19 |
November | 1798.69 | 11-NOV-11:33 | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.77 |
December | 1484.70 | 21-DEC-22:00 | 2011.87 | 1659.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.13 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 1484.70 | 1508.90 | 1556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.86 | |
Maximum of Months | 2552.44 | 12322.72 | 11618.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.13 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3347.47 | 19-JAN-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.82 |
February | 3342.58 | 27-FEB-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.50 |
March | 3234.01 | 25-MAR-15:01 | 378.00 | 410.91 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.90 |
April | 3455.42 | 29-APR-08:61 | 378.00 | 697.30 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.02 |
May | 3932.54 | 11-MAY-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.73 |
June | 3552.29 | 26-JUN-08:61 | 252.00 | 547.88 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.85 |
July | 3629.14 | 17-JUL-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.47 |
August | 3583.65 | 15-AUG-18:01 | 970.20 | 1108.21 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.54 |
September | 3619.24 | 10-SEP-18:01 | 819.00 | 1245.18 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.71 |
October | 3579.56 | 10-OCT-15:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.36 |
November | 3455.27 | 10-NOV-16:01 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.59 |
December | 329.48 | 18-DEC-16:03 | 680.40 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.22 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 329.48 | 252.00 | 348.65 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.71 | |
Maximum of Months | 3932.54 | 970.20 | 1245.18 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.22 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2829.28 | 19-JAN-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.25 |
February | 3106.84 | 27-FEB-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.17 |
March | 2842.28 | 23-MAR-18:01 | 970.20 | 1108.08 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.91 |
April | 3476.97 | 28-APR-19:01 | 1386.00 | 1778.61 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.36 |
May | 3845.84 | 23-MAY-19:42 | 831.60 | 1067.17 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.92 |
June | 3896.20 | 22-JUN-18:42 | 831.60 | 949.78 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.96 |
July | 4046.72 | 11-JUL-18:52 | 831.60 | 949.78 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.07 |
August | 3780.63 | 31-AUG-19:01 | 1386.00 | 1778.61 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.31 |
September | 3760.48 | 14-SEP-18:01 | 1386.00 | 1582.97 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.79 |
October | 3488.12 | 06-OCT-18:01 | 970.20 | 1108.08 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.83 |
November | 2951.92 | 10-NOV-16:01 | 680.40 | 348.61 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.46 |
December | 73.74 | 21-DEC-14:00 | 36.00 | 49.80 | 31.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.33 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 73.74 | 36.00 | 49.80 | 31.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.79 | |
Maximum of Months | 4046.72 | 1386.00 | 1778.61 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2172.65 | 23-JAN-16:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.75 |
February | 2039.26 | 10-FEB-16:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.87 |
March | 2162.32 | 25-MAR-15:01 | 378.00 | 258.31 | 379.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.48 |
April | 2146.48 | 29-APR-08:61 | 378.00 | 438.35 | 1119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.53 |
May | 2429.63 | 11-MAY-18:01 | 970.20 | 696.66 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.95 |
June | 2272.35 | 08-JUN-18:02 | 831.60 | 597.13 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.06 |
July | 2235.94 | 28-JUL-15:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.80 |
August | 2184.74 | 12-AUG-18:01 | 819.00 | 782.76 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.36 |
September | 2221.79 | 14-SEP-18:01 | 1386.00 | 995.22 | 1187.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.06 |
October | 2427.12 | 06-OCT-18:01 | 970.20 | 696.66 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.82 |
November | 2076.13 | 10-NOV-16:01 | 680.40 | 219.17 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.98 |
December | 2033.95 | 21-DEC-16:02 | 583.20 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.28 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2033.95 | 378.00 | 187.86 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.36 | |
Maximum of Months | 2429.63 | 1386.00 | 995.22 | 1187.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.87 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 17834.46 | 18-JAN-23:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.47 |
February | 17661.57 | 07-FEB-23:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.03 |
March | 18013.98 | 20-MAR-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.46 |
April | 20026.80 | 28-APR-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.65 |
May | 20730.19 | 22-MAY-21:32 | 269887.68 | 19920.20 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.78 |
June | 21361.25 | 13-JUN-21:12 | 269887.68 | 19920.20 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.43 |
July | 21365.07 | 21-JUL-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.95 |
August | 20932.40 | 14-AUG-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.50 |
September | 20308.46 | 12-SEP-22:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.77 |
October | 18712.45 | 02-OCT-22:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.17 |
November | 18350.68 | 08-NOV-23:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.43 |
December | 17174.05 | 04-DEC-23:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.89 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 17174.05 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.50 | |
Maximum of Months | 21365.07 | 269887.68 | 19920.20 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19848.01 | 18-JAN-23:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.47 |
February | 19688.96 | 07-FEB-23:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.03 |
March | 20001.87 | 30-MAR-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.22 |
April | 21590.32 | 28-APR-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.65 |
May | 22267.43 | 22-MAY-21:10 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.80 |
June | 23233.26 | 13-JUN-21:11 | 269887.68 | 19920.20 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.44 |
July | 22774.28 | 21-JUL-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.00 |
August | 22362.62 | 14-AUG-21:20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.37 |
September | 21753.94 | 12-SEP-22:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.77 |
October | 20547.54 | 12-OCT-22:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.00 |
November | 20360.89 | 08-NOV-23:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.43 |
December | 19218.20 | 04-DEC-23:00 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.89 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 19218.20 | 26988.77 | 1992.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.37 | |
Maximum of Months | 23233.26 | 269887.68 | 19920.20 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.22 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 27665.45 | 21-JAN-11:33 | 2401.70 | 884.01 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 125.82 |
February | 27826.48 | 22-FEB-11:33 | 1601.14 | 884.01 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 96.90 |
March | 28575.37 | 25-MAR-10:45 | 1601.14 | 589.34 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 87.60 |
April | 30830.75 | 30-APR-10:33 | 2401.70 | 1060.81 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 31.86 |
May | 30625.33 | 23-MAY-10:33 | 1601.14 | 884.01 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 27.57 |
June | 30951.71 | 25-JUN-10:37 | 2401.70 | 1060.81 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 27.69 |
July | 31380.43 | 23-JUL-10:40 | 2401.70 | 1060.81 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 21.67 |
August | 30813.11 | 19-AUG-10:33 | 2401.70 | 884.01 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 41.40 |
September | 30394.97 | 10-SEP-10:33 | 2401.70 | 1060.81 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 36.83 |
October | 29445.94 | 07-OCT-10:33 | 2401.70 | 884.01 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 64.68 |
November | 27559.67 | 11-NOV-11:50 | 800.57 | 353.60 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 106.24 |
December | 26773.03 | 03-DEC-11:50 | 800.57 | 353.60 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 122.99 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 26773.03 | 800.57 | 353.60 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 21.67 | |
Maximum of Months | 31380.43 | 2401.70 | 1060.81 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 125.82 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3791.53 | 21-JAN-11:33 | 2395.44 | 1646.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.00 |
February | 3828.29 | 22-FEB-11:33 | 1596.96 | 1646.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.37 |
March | 3863.11 | 25-MAR-10:33 | 2395.44 | 1646.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.62 |
April | 5092.23 | 30-APR-10:33 | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.27 |
May | 5012.13 | 23-MAY-10:33 | 1596.96 | 1646.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.49 |
June | 5215.73 | 13-JUN-10:33 | 1596.96 | 1646.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.30 |
July | 5443.74 | 23-JUL-10:33 | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.52 |
August | 5159.05 | 19-AUG-10:33 | 2395.44 | 1646.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.42 |
September | 4977.19 | 13-SEP-10:33 | 1596.96 | 1646.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.38 |
October | 4464.97 | 01-OCT-10:33 | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.98 |
November | 3815.17 | 11-NOV-11:33 | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.66 |
December | 3485.35 | 03-DEC-11:33 | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.41 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 3485.35 | 1596.96 | 1646.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.30 | |
Maximum of Months | 5443.74 | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.378753E+12 | 225184.61 | 24-JAN-07:49 | 0.537991E+12 | 544936.28 | 26-JAN-18:40 |
February | 0.342036E+12 | 224511.61 | 07-FEB-07:40 | 0.450938E+12 | 544249.64 | 22-FEB-18:19 |
March | 0.371763E+12 | 224841.14 | 17-MAR-06:19 | 0.536614E+12 | 542592.79 | 09-MAR-18:19 |
April | 0.372536E+12 | 278432.86 | 30-APR-18:10 | 0.506380E+12 | 519817.93 | 11-APR-17:00 |
May | 0.380449E+12 | 233146.13 | 22-MAY-19:49 | 0.539364E+12 | 499073.05 | 02-MAY-20:10 |
June | 0.378898E+12 | 307149.40 | 12-JUN-18:10 | 0.477330E+12 | 484068.49 | 06-JUN-20:49 |
July | 0.403452E+12 | 314153.84 | 22-JUL-18:19 | 0.451054E+12 | 459186.64 | 03-JUL-20:00 |
August | 0.408382E+12 | 297221.09 | 14-AUG-18:10 | 0.429199E+12 | 367278.88 | 27-AUG-20:00 |
September | 0.384561E+12 | 250809.11 | 11-SEP-18:40 | 0.473569E+12 | 498434.16 | 30-SEP-18:00 |
October | 0.375003E+12 | 227598.61 | 03-OCT-18:10 | 0.564546E+12 | 525224.96 | 30-OCT-17:00 |
November | 0.361696E+12 | 224961.61 | 10-NOV-07:10 | 0.563063E+12 | 539692.39 | 21-NOV-18:30 |
December | 0.378787E+12 | 224549.06 | 05-DEC-07:40 | 0.516650E+12 | 538827.56 | 19-DEC-18:00 |
Annual Sum or Average | 0.453632E+13 | 0.604670E+13 | ||||
Minimum of Months | 0.342036E+12 | 224511.61 | 0.429199E+12 | 367278.88 | ||
Maximum of Months | 0.408382E+12 | 314153.84 | 0.564546E+12 | 544936.28 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.673725E+11 | 0.211506E+11 | 0.140828E+12 | 0.691147E+11 | 0.402288E+11 | 0.318919E+10 | 0.00 | 0.201157E+10 | 0.00 | 0.00 | 0.215829E+11 | 0.804762E+10 | 0.00 |
February | 0.605265E+11 | 0.174046E+11 | 0.127191E+12 | 0.624261E+11 | 0.361965E+11 | 0.312943E+10 | 0.00 | 0.218906E+10 | 0.00 | 0.00 | 0.209779E+11 | 0.727209E+10 | 0.00 |
March | 0.666420E+11 | 0.169382E+11 | 0.140882E+12 | 0.691169E+11 | 0.399753E+11 | 0.360902E+10 | 0.00 | 0.201937E+10 | 0.00 | 0.00 | 0.193038E+11 | 0.804615E+10 | 0.00 |
April | 0.638888E+11 | 0.140362E+11 | 0.136245E+12 | 0.668842E+11 | 0.409501E+11 | 0.764983E+10 | 0.00 | 0.176654E+11 | 0.00 | 0.00 | 0.123640E+11 | 0.779737E+10 | 0.00 |
May | 0.654774E+11 | 0.124372E+11 | 0.140860E+12 | 0.691148E+11 | 0.425460E+11 | 0.823671E+10 | 0.00 | 0.186935E+11 | 0.00 | 0.00 | 0.977589E+10 | 0.804741E+10 | 0.00 |
June | 0.630969E+11 | 0.109343E+11 | 0.136336E+12 | 0.668861E+11 | 0.428231E+11 | 0.882805E+10 | 0.00 | 0.330699E+11 | 0.00 | 0.00 | 0.400239E+10 | 0.778879E+10 | 0.00 |
July | 0.652946E+11 | 0.117857E+11 | 0.140770E+12 | 0.691122E+11 | 0.449176E+11 | 0.949077E+10 | 0.00 | 0.457432E+11 | 0.00 | 0.00 | 0.299589E+10 | 0.805572E+10 | 0.00 |
August | 0.658154E+11 | 0.135846E+11 | 0.140892E+12 | 0.691164E+11 | 0.448764E+11 | 0.964760E+10 | 0.00 | 0.490709E+11 | 0.00 | 0.00 | 0.201686E+10 | 0.804726E+10 | 0.00 |
September | 0.642586E+11 | 0.153688E+11 | 0.136256E+12 | 0.668845E+11 | 0.425719E+11 | 0.891288E+10 | 0.00 | 0.339915E+11 | 0.00 | 0.00 | 0.339388E+10 | 0.779867E+10 | 0.00 |
October | 0.669869E+11 | 0.183004E+11 | 0.140818E+12 | 0.691145E+11 | 0.409940E+11 | 0.617723E+10 | 0.00 | 0.878565E+10 | 0.00 | 0.00 | 0.105169E+11 | 0.804607E+10 | 0.00 |
November | 0.651790E+11 | 0.198254E+11 | 0.136330E+12 | 0.668859E+11 | 0.389629E+11 | 0.358162E+10 | 0.00 | 0.215861E+10 | 0.00 | 0.00 | 0.159260E+11 | 0.778062E+10 | 0.00 |
December | 0.675549E+11 | 0.217206E+11 | 0.140770E+12 | 0.691137E+11 | 0.403294E+11 | 0.193668E+10 | 0.00 | 0.462468E+09 | 0.00 | 0.00 | 0.236192E+11 | 0.805610E+10 | 0.00 |
Annual Sum or Average | 0.782094E+12 | 0.193487E+12 | 0.165818E+13 | 0.813770E+12 | 0.495372E+12 | 0.743890E+11 | 0.00 | 0.215861E+12 | 0.00 | 0.00 | 0.146476E+12 | 0.947839E+11 | 0.00 |
Minimum of Months | 0.605265E+11 | 0.109343E+11 | 0.127191E+12 | 0.624261E+11 | 0.361965E+11 | 0.193668E+10 | 0.00 | 0.462468E+09 | 0.00 | 0.00 | 0.201686E+10 | 0.727209E+10 | 0.00 |
Maximum of Months | 0.675549E+11 | 0.217206E+11 | 0.140892E+12 | 0.691169E+11 | 0.449176E+11 | 0.964760E+10 | 0.00 | 0.490709E+11 | 0.00 | 0.00 | 0.236192E+11 | 0.805610E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.151918E+12 | 0.00 | 0.140215E+12 | 0.00 | 0.245858E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.904843E+11 | 0.00 | 0.223250E+12 | 0.00 | 0.00 |
March | 0.152024E+12 | 0.00 | 0.138634E+12 | 0.00 | 0.245957E+12 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.124968E+12 | 0.00 | 0.234457E+12 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.150122E+12 | 0.00 | 0.237264E+12 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 0.105473E+12 | 0.00 | 0.224743E+12 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 0.708157E+11 | 0.00 | 0.228418E+12 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 0.500617E+11 | 0.00 | 0.227098E+12 | 0.00 | 0.00 |
September | 0.146971E+12 | 0.00 | 0.105582E+12 | 0.00 | 0.221016E+12 | 0.00 | 0.00 |
October | 0.151903E+12 | 0.00 | 0.180607E+12 | 0.00 | 0.232036E+12 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.186543E+12 | 0.00 | 0.229428E+12 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.122716E+12 | 0.00 | 0.242114E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178884E+13 | 0.00 | 0.146622E+13 | 0.00 | 0.279164E+13 | 0.00 | 0.00 |
Minimum of Months | 0.137204E+12 | 0.00 | 0.500617E+11 | 0.00 | 0.221016E+12 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.186543E+12 | 0.00 | 0.245957E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 64632.59 | 02-JAN-20:10 | 12338.45 | 01-JAN-00:10 | 89171.45 | 02-JAN-07:10 | 49607.07 | 02-JAN-07:19 | 22218.44 | 10-JAN-19:10 | 3777.78 | 19-JAN-16:10 | 0.00 | 01-JAN-00:10 |
February | 64632.59 | 01-FEB-20:10 | 12338.45 | 01-FEB-00:10 | 89171.45 | 01-FEB-07:10 | 49607.07 | 01-FEB-07:19 | 21099.06 | 21-FEB-19:10 | 3868.08 | 27-FEB-16:10 | 0.00 | 01-FEB-00:10 |
March | 64632.59 | 01-MAR-20:10 | 12338.45 | 01-MAR-00:10 | 89171.45 | 01-MAR-07:10 | 49607.07 | 01-MAR-07:19 | 21353.71 | 31-MAR-18:10 | 3703.77 | 20-MAR-18:10 | 0.00 | 01-MAR-00:10 |
April | 64632.59 | 03-APR-19:10 | 12338.45 | 01-APR-00:10 | 89171.45 | 03-APR-06:10 | 49607.07 | 10-APR-06:19 | 26772.11 | 28-APR-21:10 | 4673.87 | 29-APR-15:09 | 0.00 | 01-APR-00:10 |
May | 64632.59 | 01-MAY-19:19 | 12338.45 | 01-MAY-00:10 | 89171.45 | 01-MAY-06:10 | 49605.88 | 01-MAY-06:19 | 28362.88 | 22-MAY-21:49 | 4628.20 | 22-MAY-15:09 | 0.00 | 01-MAY-00:10 |
June | 64632.59 | 01-JUN-19:30 | 12338.45 | 01-JUN-00:10 | 89171.45 | 01-JUN-06:10 | 49605.38 | 15-JUN-06:19 | 30864.56 | 26-JUN-21:10 | 4754.32 | 25-JUN-18:10 | 0.00 | 01-JUN-00:10 |
July | 64632.59 | 17-JUL-19:30 | 12338.45 | 01-JUL-00:10 | 89171.45 | 03-JUL-06:10 | 49605.49 | 25-JUL-06:19 | 29628.98 | 19-JUL-21:10 | 4802.72 | 22-JUL-18:10 | 0.00 | 01-JUL-00:10 |
August | 64632.59 | 01-AUG-19:40 | 12338.45 | 01-AUG-00:10 | 89171.45 | 01-AUG-06:10 | 49606.78 | 15-AUG-06:19 | 29896.92 | 17-AUG-21:30 | 4842.51 | 14-AUG-18:30 | 0.00 | 01-AUG-00:10 |
September | 64632.59 | 01-SEP-19:10 | 12338.45 | 01-SEP-00:10 | 89171.45 | 01-SEP-06:10 | 49607.07 | 18-SEP-06:19 | 30011.47 | 11-SEP-21:10 | 4736.26 | 25-SEP-15:09 | 0.00 | 01-SEP-00:10 |
October | 64632.59 | 02-OCT-19:10 | 12338.45 | 01-OCT-00:10 | 89171.45 | 02-OCT-06:10 | 49607.07 | 02-OCT-06:19 | 24933.09 | 03-OCT-21:10 | 4258.12 | 07-OCT-15:09 | 0.00 | 01-OCT-00:10 |
November | 64632.59 | 01-NOV-19:10 | 12338.45 | 01-NOV-00:10 | 89171.45 | 01-NOV-06:10 | 49607.07 | 01-NOV-06:19 | 22117.75 | 08-NOV-21:10 | 3766.50 | 11-NOV-09:00 | 0.00 | 01-NOV-00:10 |
December | 64632.59 | 01-DEC-20:10 | 12338.45 | 01-DEC-00:10 | 89171.45 | 01-DEC-07:10 | 49607.07 | 01-DEC-07:19 | 22109.07 | 29-DEC-19:10 | 3169.60 | 20-DEC-19:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 64632.59 | 12338.45 | 89171.45 | 49605.38 | 21099.06 | 3169.60 | 0.00 | |||||||
Maximum of Months | 64632.59 | 12338.45 | 89171.45 | 49607.07 | 30864.56 | 4842.51 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 10018.53 | 21-JAN-10:00 | 0.00 | 0.00 | 9938.94 | 01-JAN-00:10 | 4751.13 | 13-JAN-07:00 | 0.00 |
February | 10922.99 | 19-FEB-16:10 | 0.00 | 0.00 | 9938.94 | 01-FEB-00:20 | 4751.12 | 09-FEB-07:49 | 0.00 |
March | 9305.30 | 20-MAR-18:10 | 0.00 | 0.00 | 9938.94 | 01-MAR-00:20 | 4751.13 | 20-MAR-18:49 | 0.00 |
April | 79997.97 | 30-APR-18:10 | 0.00 | 0.00 | 9938.94 | 01-APR-00:10 | 4751.13 | 03-APR-06:40 | 0.00 |
May | 74633.46 | 22-MAY-15:09 | 0.00 | 0.00 | 9938.94 | 01-MAY-01:00 | 4751.13 | 22-MAY-18:00 | 0.00 |
June | 103102.64 | 25-JUN-18:10 | 0.00 | 0.00 | 9938.94 | 01-JUN-01:30 | 4751.13 | 27-JUN-06:00 | 0.00 |
July | 112941.32 | 22-JUL-18:19 | 0.00 | 0.00 | 9938.94 | 03-JUL-21:10 | 4751.13 | 18-JUL-06:00 | 0.00 |
August | 92252.05 | 14-AUG-18:10 | 0.00 | 0.00 | 9938.94 | 14-AUG-12:39 | 4751.13 | 31-AUG-06:49 | 0.00 |
September | 78724.70 | 13-SEP-15:09 | 0.00 | 0.00 | 9938.94 | 04-SEP-05:19 | 4751.12 | 28-SEP-06:49 | 0.00 |
October | 43613.14 | 07-OCT-15:09 | 0.00 | 0.00 | 9938.94 | 01-OCT-02:09 | 4751.13 | 25-OCT-18:40 | 0.00 |
November | 9637.37 | 05-NOV-15:09 | 0.00 | 0.00 | 9938.94 | 01-NOV-00:10 | 4751.08 | 22-NOV-19:00 | 0.00 |
December | 2314.74 | 02-DEC-09:09 | 0.00 | 0.00 | 9938.94 | 01-DEC-00:20 | 4751.13 | 18-DEC-19:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 2314.74 | 0.00 | 0.00 | 9938.94 | 4751.08 | 0.00 | |||
Maximum of Months | 112941.32 | 0.00 | 0.00 | 9938.94 | 4751.13 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 225184.61 | 24-JAN-07:49 | 36001.17 | 89171.45 | 12338.45 | 49607.07 | 15932.47 | 2598.10 | 0.00 | 1622.10 | 0.00 |
February | 224511.61 | 07-FEB-07:40 | 36001.17 | 89171.45 | 12338.45 | 49607.07 | 15813.67 | 2570.61 | 0.00 | 1095.35 | 0.00 |
March | 224841.14 | 17-MAR-06:19 | 36001.17 | 89171.45 | 12338.45 | 49607.07 | 15756.41 | 2619.13 | 0.00 | 1432.21 | 0.00 |
April | 278432.86 | 30-APR-18:10 | 51055.14 | 74651.16 | 0.00 | 28099.95 | 23747.58 | 4622.19 | 0.00 | 79997.97 | 0.00 |
May | 233146.13 | 22-MAY-19:49 | 64632.59 | 86439.81 | 12338.45 | 10999.77 | 21905.44 | 3999.80 | 0.00 | 26470.52 | 0.00 |
June | 307149.40 | 12-JUN-18:10 | 52987.32 | 77573.37 | 0.00 | 28157.23 | 24654.27 | 4744.45 | 0.00 | 101925.36 | 0.00 |
July | 314153.84 | 22-JUL-18:19 | 51055.14 | 74651.16 | 0.00 | 28107.81 | 25912.11 | 4801.62 | 0.00 | 112941.32 | 0.00 |
August | 297221.09 | 14-AUG-18:10 | 53184.46 | 77573.37 | 0.00 | 28157.33 | 24341.84 | 4635.62 | 0.00 | 92252.05 | 0.00 |
September | 250809.11 | 11-SEP-18:40 | 57474.69 | 77573.37 | 12338.45 | 28169.74 | 20675.96 | 4278.19 | 0.00 | 43134.49 | 0.00 |
October | 227598.61 | 03-OCT-18:10 | 57474.69 | 77573.37 | 12338.45 | 28159.60 | 23175.83 | 4091.72 | 0.00 | 16691.56 | 0.00 |
November | 224961.61 | 10-NOV-07:10 | 36001.17 | 89171.45 | 12338.45 | 49600.84 | 15577.10 | 2619.39 | 0.00 | 1737.34 | 0.00 |
December | 224549.06 | 05-DEC-07:40 | 36001.17 | 89171.45 | 12338.45 | 49607.07 | 15848.51 | 2588.41 | 0.00 | 1077.41 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 224511.61 | 36001.17 | 74651.16 | 0.00 | 10999.77 | 15577.10 | 2570.61 | 0.00 | 1077.41 | 0.00 | |
Maximum of Months | 314153.84 | 64632.59 | 89171.45 | 12338.45 | 49607.07 | 25912.11 | 4801.62 | 0.00 | 112941.32 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 194229.07 | 31-JAN-11:39 | 0.00 | 254004.27 | 31-JAN-21:49 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 204998.76 | 19-FEB-11:50 | 0.00 | 254045.25 | 15-FEB-21:19 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 194208.29 | 04-MAR-11:50 | 0.00 | 253624.41 | 02-MAR-21:49 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 185850.29 | 23-APR-22:40 | 0.00 | 250643.72 | 03-APR-20:49 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 192091.28 | 27-MAY-22:40 | 0.00 | 247467.06 | 01-MAY-20:30 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 180989.44 | 07-JUN-10:20 | 0.00 | 241488.55 | 01-JUN-20:00 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 166886.96 | 31-JUL-04:30 | 0.00 | 237536.49 | 05-JUL-20:19 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 162138.29 | 20-AUG-05:10 | 0.00 | 235027.52 | 01-AUG-20:30 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 196861.17 | 28-SEP-06:10 | 0.00 | 237480.06 | 29-SEP-20:00 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 193473.81 | 31-OCT-08:09 | 0.00 | 241378.48 | 31-OCT-20:19 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 203552.84 | 12-NOV-11:50 | 0.00 | 247542.21 | 30-NOV-21:30 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 203749.14 | 16-DEC-16:10 | 0.00 | 250605.00 | 29-DEC-21:40 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 104248.32 | 0.00 | 162138.29 | 0.00 | 235027.52 | 0.00 | |||
Maximum of Months | 104248.32 | 0.00 | 204998.76 | 0.00 | 254045.25 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.00 | 20.47 | 1.00 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.73 | 0.17 | 21.73 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.70 | 0.50 | 21.70 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.68 | 0.17 | 21.68 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.72 | 0.17 | 21.72 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.33 | 20.41 | 0.33 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 |
December | 2.67 | 20.43 | 2.67 | 20.43 | 0.00 | 20.43 | 0.00 | 20.43 |
Annual Sum or Average | 4.00 | 20.44 | 4.00 | 20.44 | 1.00 | 20.58 | 1.00 | 20.69 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.67 | 20.47 | 2.67 | 20.47 | 0.50 | 21.73 | 0.50 | 21.73 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.67 | 20.41 | 2.67 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.17 | 20.52 | 0.17 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.92 | 0.50 | 21.92 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.87 | 0.50 | 21.87 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 22.08 | 1.67 | 22.08 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 21.96 | 3.67 | 21.96 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.76 | 1.83 | 21.76 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.85 | 0.67 | 21.85 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.83 | 20.41 | 0.83 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 |
December | 6.00 | 20.43 | 6.00 | 20.43 | 0.00 | 20.43 | 0.00 | 20.43 |
Annual Sum or Average | 9.67 | 20.42 | 9.67 | 20.42 | 8.83 | 20.89 | 8.83 | 21.14 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6.00 | 20.52 | 6.00 | 20.52 | 3.67 | 22.08 | 3.67 | 22.08 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 20.47 | 0.50 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.78 | 0.67 | 21.78 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.76 | 1.17 | 21.76 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 21.82 | 3.33 | 21.82 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 21.86 | 4.67 | 21.86 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 21.75 | 3.67 | 21.75 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.72 | 0.67 | 21.72 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.50 | 20.47 | 0.50 | 20.47 | 14.17 | 21.72 | 14.17 | 21.76 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 20.47 | 0.50 | 20.47 | 4.67 | 21.86 | 4.67 | 21.86 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.83 | 20.44 | 0.83 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.33 | 20.40 | 0.33 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 |
December | 3.00 | 20.44 | 3.00 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
Annual Sum or Average | 4.17 | 20.43 | 4.17 | 20.43 | 0.00 | 20.43 | 0.00 | 20.43 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.00 | 20.44 | 3.00 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.17 | 20.41 | 3.17 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 |
February | 0.17 | 20.55 | 0.17 | 20.55 | 0.00 | 20.55 | 0.00 | 20.55 |
March | 0.17 | 20.53 | 0.17 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 22.40 | 0.33 | 22.40 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 22.47 | 0.33 | 22.47 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 22.30 | 1.33 | 22.30 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 22.22 | 2.17 | 22.22 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 22.24 | 2.00 | 22.24 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 22.08 | 1.33 | 22.08 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.67 | 20.41 | 0.67 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 |
December | 5.83 | 20.42 | 5.83 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 |
Annual Sum or Average | 10.00 | 20.42 | 10.00 | 20.42 | 7.50 | 20.92 | 7.50 | 21.20 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5.83 | 20.55 | 5.83 | 20.55 | 2.17 | 22.47 | 2.17 | 22.47 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.67 | 20.51 | 2.67 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.17 | 20.55 | 0.17 | 20.55 | 0.00 | 20.55 | 0.00 | 20.55 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.82 | 0.50 | 21.82 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.80 | 0.17 | 21.80 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.72 | 0.67 | 21.72 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.84 | 0.50 | 21.84 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.73 | 0.67 | 21.73 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.75 | 0.33 | 21.75 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.00 | 20.50 | 1.00 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
December | 4.83 | 20.48 | 4.83 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 |
Annual Sum or Average | 8.67 | 20.50 | 8.67 | 20.50 | 2.83 | 20.67 | 2.83 | 20.81 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.83 | 20.55 | 4.83 | 20.55 | 0.67 | 21.84 | 0.67 | 21.84 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.83 | 20.46 | 4.83 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 |
February | 1.17 | 20.53 | 1.17 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 |
March | 0.17 | 20.54 | 0.17 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.94 | 1.00 | 21.94 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 22.00 | 1.00 | 22.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 22.08 | 3.00 | 22.08 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 22.07 | 4.50 | 22.07 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 21.88 | 2.83 | 21.88 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.84 | 1.00 | 21.84 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2.67 | 20.50 | 2.67 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
December | 10.83 | 20.48 | 10.83 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 |
Annual Sum or Average | 19.67 | 20.48 | 19.67 | 20.48 | 13.33 | 20.87 | 13.33 | 21.10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 10.83 | 20.54 | 10.83 | 20.54 | 4.50 | 22.08 | 4.50 | 22.08 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 20.50 | 0.33 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.70 | 1.00 | 21.70 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 20.48 | 0.17 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 |
December | 1.67 | 20.48 | 1.67 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 |
Annual Sum or Average | 2.17 | 20.48 | 2.17 | 20.48 | 1.00 | 20.71 | 1.00 | 20.86 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.67 | 20.50 | 1.67 | 20.50 | 1.00 | 21.70 | 1.00 | 21.70 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 23.19 | 0.00 | 23.19 | 0.00 | 23.19 |
February | 672.00 | 23.02 | 0.00 | 23.02 | 0.00 | 23.02 |
March | 744.00 | 22.78 | 0.00 | 22.78 | 0.00 | 22.78 |
April | 720.00 | 22.78 | 0.00 | 22.78 | 0.00 | 22.78 |
May | 744.00 | 22.77 | 0.00 | 22.77 | 0.00 | 22.77 |
June | 720.00 | 22.89 | 0.00 | 22.89 | 0.00 | 22.89 |
July | 713.67 | 23.10 | 0.00 | 23.10 | 0.00 | 23.10 |
August | 677.83 | 23.21 | 0.67 | 23.21 | 0.00 | 23.21 |
September | 573.67 | 23.41 | 2.50 | 23.42 | 0.00 | 23.42 |
October | 598.00 | 23.53 | 0.00 | 23.53 | 0.00 | 23.53 |
November | 625.50 | 23.58 | 0.00 | 23.58 | 0.00 | 23.58 |
December | 732.33 | 23.47 | 0.00 | 23.47 | 0.00 | 23.47 |
Annual Sum or Average | 8265.00 | 23.13 | 3.17 | 23.13 | 0.00 | 23.13 |
Minimum of Months | 573.67 | 22.77 | 0.00 | 22.77 | 0.00 | 22.77 |
Maximum of Months | 744.00 | 23.58 | 2.50 | 23.58 | 0.00 | 23.58 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 731.67 | 21.08 | 139.83 | 21.08 | 138.50 | 21.07 |
February | 650.67 | 21.10 | 33.50 | 21.12 | 27.83 | 21.11 |
March | 744.00 | 21.02 | 32.00 | 21.02 | 32.00 | 21.02 |
April | 654.33 | 21.31 | 32.83 | 21.43 | 0.00 | 21.43 |
May | 698.83 | 21.25 | 15.00 | 21.30 | 0.00 | 21.30 |
June | 663.50 | 21.31 | 20.83 | 21.38 | 0.00 | 21.38 |
July | 638.50 | 21.43 | 66.00 | 21.62 | 0.00 | 21.62 |
August | 602.83 | 21.51 | 105.50 | 21.84 | 0.00 | 21.84 |
September | 567.33 | 21.44 | 119.00 | 21.85 | 0.00 | 21.85 |
October | 686.83 | 21.15 | 33.00 | 21.28 | 0.00 | 21.28 |
November | 711.17 | 21.08 | 26.50 | 21.09 | 24.67 | 21.08 |
December | 741.67 | 21.04 | 233.33 | 21.03 | 233.33 | 21.03 |
Annual Sum or Average | 8091.33 | 21.22 | 857.33 | 21.32 | 456.33 | 21.30 |
Minimum of Months | 567.33 | 21.02 | 15.00 | 21.02 | 0.00 | 21.02 |
Maximum of Months | 744.00 | 21.51 | 233.33 | 21.85 | 233.33 | 21.85 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.87 | 0.00 | 21.87 | 0.00 | 21.87 |
February | 672.00 | 21.96 | 0.00 | 21.96 | 0.00 | 21.96 |
March | 744.00 | 21.93 | 0.00 | 21.93 | 0.00 | 21.93 |
April | 700.00 | 22.62 | 0.00 | 22.62 | 0.00 | 22.62 |
May | 709.00 | 22.63 | 2.17 | 22.63 | 0.00 | 22.63 |
June | 611.33 | 22.81 | 25.00 | 22.85 | 0.00 | 22.85 |
July | 530.83 | 22.84 | 71.83 | 22.97 | 0.00 | 22.97 |
August | 529.83 | 22.97 | 55.00 | 23.07 | 0.00 | 23.07 |
September | 577.00 | 22.93 | 32.50 | 22.98 | 0.00 | 22.98 |
October | 733.50 | 22.41 | 0.00 | 22.41 | 0.00 | 22.41 |
November | 720.00 | 22.00 | 0.00 | 22.00 | 0.00 | 22.00 |
December | 744.00 | 21.66 | 0.00 | 21.66 | 0.00 | 21.66 |
Annual Sum or Average | 8015.50 | 22.34 | 186.50 | 22.38 | 0.00 | 22.38 |
Minimum of Months | 529.83 | 21.66 | 0.00 | 21.66 | 0.00 | 21.66 |
Maximum of Months | 744.00 | 22.97 | 71.83 | 23.07 | 0.00 | 23.07 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.16 | 27.17 | 21.15 | 27.17 | 21.15 |
February | 672.00 | 21.15 | 0.00 | 21.15 | 0.00 | 21.15 |
March | 744.00 | 21.26 | 0.00 | 21.26 | 0.00 | 21.26 |
April | 720.00 | 21.97 | 0.00 | 21.97 | 0.00 | 21.97 |
May | 744.00 | 22.17 | 0.00 | 22.17 | 0.00 | 22.17 |
June | 716.00 | 22.66 | 0.00 | 22.66 | 0.00 | 22.66 |
July | 724.50 | 22.88 | 0.00 | 22.88 | 0.00 | 22.88 |
August | 739.50 | 22.94 | 0.00 | 22.94 | 0.00 | 22.94 |
September | 720.00 | 22.69 | 0.00 | 22.69 | 0.00 | 22.69 |
October | 744.00 | 21.86 | 0.00 | 21.86 | 0.00 | 21.86 |
November | 720.00 | 21.33 | 0.00 | 21.33 | 0.00 | 21.33 |
December | 744.00 | 21.07 | 10.33 | 21.07 | 10.33 | 21.07 |
Annual Sum or Average | 8732.00 | 21.93 | 37.50 | 21.92 | 37.50 | 21.92 |
Minimum of Months | 672.00 | 21.07 | 0.00 | 21.07 | 0.00 | 21.07 |
Maximum of Months | 744.00 | 22.94 | 27.17 | 22.94 | 27.17 | 22.94 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.02 | 60.50 | 21.02 | 60.50 | 21.02 |
February | 672.00 | 21.01 | 0.00 | 21.01 | 0.00 | 21.01 |
March | 744.00 | 21.04 | 0.00 | 21.04 | 0.00 | 21.04 |
April | 720.00 | 21.64 | 0.00 | 21.64 | 0.00 | 21.64 |
May | 744.00 | 21.83 | 0.00 | 21.83 | 0.00 | 21.83 |
June | 720.00 | 22.36 | 0.00 | 22.36 | 0.00 | 22.36 |
July | 744.00 | 22.61 | 0.00 | 22.61 | 0.00 | 22.61 |
August | 744.00 | 22.65 | 0.00 | 22.65 | 0.00 | 22.65 |
September | 720.00 | 22.36 | 0.00 | 22.36 | 0.00 | 22.36 |
October | 744.00 | 21.49 | 0.00 | 21.49 | 0.00 | 21.49 |
November | 720.00 | 21.07 | 0.00 | 21.07 | 0.00 | 21.07 |
December | 744.00 | 21.00 | 21.67 | 21.00 | 21.67 | 21.00 |
Annual Sum or Average | 8760.00 | 21.68 | 82.17 | 21.67 | 82.17 | 21.67 |
Minimum of Months | 672.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
Maximum of Months | 744.00 | 22.65 | 60.50 | 22.65 | 60.50 | 22.65 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 238.00 | 22.99 | 562.00 | 23.29 | 154.50 | 23.40 |
February | 217.50 | 23.04 | 536.50 | 23.27 | 145.83 | 23.39 |
March | 246.17 | 23.03 | 587.83 | 23.28 | 164.00 | 23.40 |
April | 255.83 | 23.31 | 596.50 | 23.33 | 193.83 | 23.45 |
May | 273.17 | 23.44 | 633.83 | 23.35 | 220.67 | 23.48 |
June | 299.17 | 23.67 | 640.17 | 23.39 | 265.33 | 23.52 |
July | 303.00 | 23.80 | 673.00 | 23.41 | 282.17 | 23.54 |
August | 302.67 | 23.83 | 670.83 | 23.42 | 285.17 | 23.55 |
September | 289.17 | 23.68 | 636.00 | 23.40 | 256.33 | 23.53 |
October | 279.00 | 23.36 | 634.50 | 23.33 | 217.33 | 23.46 |
November | 240.50 | 23.14 | 581.50 | 23.31 | 169.33 | 23.43 |
December | 234.67 | 22.94 | 553.17 | 23.27 | 148.33 | 23.39 |
Annual Sum or Average | 3178.83 | 23.38 | 7305.83 | 23.34 | 2502.83 | 23.47 |
Minimum of Months | 217.50 | 22.94 | 536.50 | 23.27 | 145.83 | 23.39 |
Maximum of Months | 303.00 | 23.83 | 673.00 | 23.42 | 285.17 | 23.55 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 717.17 | 21.53 | 10.33 | 21.56 | 0.50 | 21.56 |
February | 633.33 | 21.61 | 19.17 | 21.67 | 0.00 | 21.67 |
March | 744.00 | 21.51 | 0.00 | 21.51 | 0.00 | 21.51 |
April | 592.33 | 22.14 | 59.17 | 22.28 | 0.00 | 22.28 |
May | 642.50 | 22.07 | 43.83 | 22.16 | 0.00 | 22.16 |
June | 574.00 | 22.23 | 81.33 | 22.37 | 9.00 | 22.38 |
July | 430.83 | 22.19 | 172.00 | 22.54 | 0.67 | 22.54 |
August | 351.00 | 22.37 | 222.50 | 22.84 | 2.33 | 22.84 |
September | 376.67 | 22.34 | 218.83 | 22.83 | 0.00 | 22.83 |
October | 655.33 | 21.90 | 56.83 | 22.05 | 0.00 | 22.05 |
November | 698.00 | 21.60 | 6.00 | 21.62 | 0.00 | 21.62 |
December | 735.83 | 21.36 | 7.50 | 21.37 | 6.17 | 21.36 |
Annual Sum or Average | 7151.00 | 21.84 | 897.50 | 22.03 | 18.67 | 22.03 |
Minimum of Months | 351.00 | 21.36 | 0.00 | 21.37 | 0.00 | 21.36 |
Maximum of Months | 744.00 | 22.37 | 222.50 | 22.84 | 9.00 | 22.84 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 22.25 | 0.00 | 22.25 | 0.00 | 22.25 |
February | 672.00 | 22.33 | 0.00 | 22.33 | 0.00 | 22.33 |
March | 744.00 | 22.26 | 0.00 | 22.26 | 0.00 | 22.26 |
April | 641.83 | 22.82 | 1.33 | 22.82 | 0.00 | 22.82 |
May | 630.00 | 22.76 | 13.00 | 22.78 | 0.00 | 22.78 |
June | 440.33 | 22.76 | 83.17 | 22.95 | 8.17 | 22.96 |
July | 363.83 | 22.79 | 205.67 | 23.19 | 0.00 | 23.19 |
August | 250.33 | 22.81 | 218.00 | 23.31 | 1.17 | 23.32 |
September | 330.50 | 22.93 | 146.67 | 23.22 | 0.00 | 23.22 |
October | 676.33 | 22.65 | 0.00 | 22.65 | 0.00 | 22.65 |
November | 719.33 | 22.36 | 0.00 | 22.36 | 0.00 | 22.36 |
December | 744.00 | 22.04 | 0.00 | 22.04 | 0.00 | 22.04 |
Annual Sum or Average | 6956.50 | 22.50 | 667.83 | 22.62 | 9.33 | 22.62 |
Minimum of Months | 250.33 | 22.04 | 0.00 | 22.04 | 0.00 | 22.04 |
Maximum of Months | 744.00 | 22.93 | 218.00 | 23.31 | 8.17 | 23.32 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.97 | 222.33 | 20.85 | 222.33 | 20.78 |
February | 672.00 | 21.10 | 87.33 | 21.01 | 87.33 | 20.95 |
March | 744.00 | 21.05 | 68.00 | 20.99 | 68.00 | 20.94 |
April | 694.33 | 21.51 | 1.50 | 21.51 | 0.00 | 21.51 |
May | 712.83 | 21.50 | 1.33 | 21.50 | 0.00 | 21.50 |
June | 667.50 | 21.54 | 5.50 | 21.55 | 0.00 | 21.55 |
July | 671.00 | 21.51 | 6.67 | 21.53 | 0.00 | 21.53 |
August | 665.67 | 21.50 | 2.83 | 21.51 | 0.00 | 21.51 |
September | 664.50 | 21.52 | 1.33 | 21.52 | 0.00 | 21.52 |
October | 732.67 | 21.26 | 9.67 | 21.24 | 9.67 | 21.23 |
November | 720.00 | 21.01 | 115.50 | 20.92 | 115.50 | 20.85 |
December | 744.00 | 20.76 | 363.33 | 20.64 | 363.33 | 20.58 |
Annual Sum or Average | 8432.50 | 21.26 | 885.33 | 21.18 | 866.17 | 21.12 |
Minimum of Months | 664.50 | 20.76 | 1.33 | 20.64 | 0.00 | 20.58 |
Maximum of Months | 744.00 | 21.54 | 363.33 | 21.55 | 363.33 | 21.55 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.75 | 340.50 | 20.64 | 340.50 | 20.58 |
February | 672.00 | 20.87 | 192.33 | 20.75 | 192.33 | 20.68 |
March | 744.00 | 20.94 | 110.00 | 20.87 | 110.00 | 20.81 |
April | 699.33 | 21.44 | 12.33 | 21.52 | 1.67 | 21.53 |
May | 710.00 | 21.55 | 28.50 | 21.72 | 7.67 | 21.79 |
June | 650.50 | 21.77 | 51.00 | 22.09 | 15.67 | 22.21 |
July | 618.00 | 21.99 | 107.50 | 22.61 | 33.33 | 22.83 |
August | 606.50 | 21.90 | 91.33 | 22.39 | 13.17 | 22.49 |
September | 646.33 | 21.59 | 40.67 | 21.80 | 0.33 | 21.80 |
October | 744.00 | 21.14 | 16.67 | 21.11 | 16.67 | 21.09 |
November | 720.00 | 20.83 | 208.83 | 20.71 | 208.83 | 20.64 |
December | 744.00 | 20.62 | 514.50 | 20.53 | 514.50 | 20.49 |
Annual Sum or Average | 8298.67 | 21.26 | 1714.17 | 21.29 | 1454.67 | 21.22 |
Minimum of Months | 606.50 | 20.62 | 12.33 | 20.53 | 0.33 | 20.49 |
Maximum of Months | 744.00 | 21.99 | 514.50 | 22.61 | 514.50 | 22.83 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.05 | 90.33 | 21.01 | 90.33 | 20.97 |
February | 672.00 | 21.10 | 6.50 | 21.09 | 6.50 | 21.09 |
March | 744.00 | 21.22 | 0.67 | 21.22 | 0.67 | 21.22 |
April | 720.00 | 21.45 | 0.00 | 21.45 | 0.00 | 21.45 |
May | 744.00 | 21.52 | 0.00 | 21.52 | 0.00 | 21.52 |
June | 715.50 | 21.70 | 0.50 | 21.70 | 0.00 | 21.70 |
July | 738.83 | 21.87 | 0.00 | 21.87 | 0.00 | 21.87 |
August | 744.00 | 21.87 | 0.00 | 21.87 | 0.00 | 21.87 |
September | 720.00 | 21.58 | 0.00 | 21.58 | 0.00 | 21.58 |
October | 744.00 | 21.28 | 0.00 | 21.28 | 0.00 | 21.28 |
November | 720.00 | 21.13 | 12.00 | 21.11 | 12.00 | 21.10 |
December | 744.00 | 21.00 | 78.67 | 20.94 | 78.67 | 20.89 |
Annual Sum or Average | 8750.33 | 21.40 | 188.67 | 21.38 | 188.17 | 21.36 |
Minimum of Months | 672.00 | 21.00 | 0.00 | 20.94 | 0.00 | 20.89 |
Maximum of Months | 744.00 | 21.87 | 90.33 | 21.87 | 90.33 | 21.87 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.96 | 222.67 | 20.85 | 222.67 | 20.78 |
February | 672.00 | 21.10 | 91.67 | 21.02 | 91.67 | 20.96 |
March | 744.00 | 21.08 | 60.67 | 21.03 | 60.67 | 20.99 |
April | 690.67 | 21.59 | 0.00 | 21.59 | 0.00 | 21.59 |
May | 720.50 | 21.59 | 0.00 | 21.59 | 0.00 | 21.59 |
June | 663.33 | 21.56 | 0.00 | 21.56 | 0.00 | 21.56 |
July | 665.00 | 21.53 | 0.50 | 21.53 | 0.00 | 21.53 |
August | 629.83 | 21.42 | 0.00 | 21.42 | 0.00 | 21.42 |
September | 646.00 | 21.52 | 0.00 | 21.52 | 0.00 | 21.52 |
October | 744.00 | 21.33 | 11.33 | 21.31 | 11.33 | 21.29 |
November | 720.00 | 21.01 | 107.33 | 20.92 | 107.33 | 20.85 |
December | 744.00 | 20.78 | 346.83 | 20.66 | 346.83 | 20.60 |
Annual Sum or Average | 8383.33 | 21.28 | 841.00 | 21.20 | 840.50 | 21.13 |
Minimum of Months | 629.83 | 20.78 | 0.00 | 20.66 | 0.00 | 20.60 |
Maximum of Months | 744.00 | 21.59 | 346.83 | 21.59 | 346.83 | 21.59 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.75 | 322.67 | 20.63 | 322.67 | 20.57 |
February | 672.00 | 20.85 | 209.17 | 20.74 | 209.17 | 20.67 |
March | 744.00 | 20.98 | 100.67 | 20.91 | 100.67 | 20.86 |
April | 711.83 | 21.63 | 2.83 | 21.64 | 0.00 | 21.64 |
May | 724.33 | 21.66 | 6.17 | 21.68 | 0.00 | 21.68 |
June | 654.83 | 21.73 | 26.33 | 21.86 | 1.17 | 21.87 |
July | 650.33 | 21.90 | 30.83 | 22.05 | 4.17 | 22.08 |
August | 677.67 | 22.02 | 17.83 | 22.09 | 0.00 | 22.09 |
September | 701.83 | 21.83 | 8.33 | 21.87 | 0.00 | 21.87 |
October | 744.00 | 21.20 | 14.00 | 21.18 | 14.00 | 21.15 |
November | 720.00 | 20.82 | 205.17 | 20.71 | 205.17 | 20.64 |
December | 744.00 | 20.63 | 479.17 | 20.54 | 479.17 | 20.49 |
Annual Sum or Average | 8488.83 | 21.32 | 1423.17 | 21.23 | 1336.17 | 21.13 |
Minimum of Months | 650.33 | 20.63 | 2.83 | 20.54 | 0.00 | 20.49 |
Maximum of Months | 744.00 | 22.02 | 479.17 | 22.09 | 479.17 | 22.09 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.02 | 20.33 | 21.01 | 20.33 | 21.01 |
February | 672.00 | 21.03 | 0.00 | 21.03 | 0.00 | 21.03 |
March | 744.00 | 21.03 | 0.00 | 21.03 | 0.00 | 21.03 |
April | 720.00 | 21.71 | 0.00 | 21.71 | 0.00 | 21.71 |
May | 744.00 | 21.92 | 0.00 | 21.92 | 0.00 | 21.92 |
June | 720.00 | 22.32 | 0.00 | 22.32 | 0.00 | 22.32 |
July | 744.00 | 22.55 | 0.00 | 22.55 | 0.00 | 22.55 |
August | 744.00 | 22.64 | 0.00 | 22.64 | 0.00 | 22.64 |
September | 720.00 | 22.38 | 0.00 | 22.38 | 0.00 | 22.38 |
October | 744.00 | 21.42 | 0.00 | 21.42 | 0.00 | 21.42 |
November | 720.00 | 21.02 | 0.00 | 21.02 | 0.00 | 21.02 |
December | 744.00 | 21.00 | 14.17 | 21.00 | 14.17 | 21.00 |
Annual Sum or Average | 8760.00 | 21.67 | 34.50 | 21.67 | 34.50 | 21.67 |
Minimum of Months | 672.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
Maximum of Months | 744.00 | 22.64 | 20.33 | 22.64 | 20.33 | 22.64 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.85 | 387.67 | 20.74 | 387.67 | 20.69 |
February | 671.00 | 20.99 | 237.67 | 20.88 | 237.67 | 20.82 |
March | 744.00 | 20.96 | 208.00 | 20.88 | 208.00 | 20.84 |
April | 682.67 | 21.46 | 14.17 | 21.46 | 8.67 | 21.45 |
May | 699.33 | 21.44 | 6.17 | 21.45 | 0.00 | 21.45 |
June | 651.50 | 21.49 | 13.67 | 21.52 | 0.00 | 21.52 |
July | 651.17 | 21.45 | 23.17 | 21.51 | 0.00 | 21.51 |
August | 642.33 | 21.42 | 14.67 | 21.46 | 0.00 | 21.46 |
September | 653.00 | 21.46 | 12.50 | 21.50 | 0.50 | 21.50 |
October | 730.83 | 21.18 | 34.83 | 21.12 | 34.83 | 21.07 |
November | 720.00 | 20.90 | 239.17 | 20.78 | 239.17 | 20.71 |
December | 744.00 | 20.66 | 598.67 | 20.61 | 598.67 | 20.59 |
Annual Sum or Average | 8333.83 | 21.17 | 1790.33 | 21.08 | 1715.17 | 21.00 |
Minimum of Months | 642.33 | 20.66 | 6.17 | 20.61 | 0.00 | 20.59 |
Maximum of Months | 744.00 | 21.49 | 598.67 | 21.52 | 598.67 | 21.52 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.64 | 518.33 | 20.56 | 518.33 | 20.53 |
February | 672.00 | 20.75 | 386.67 | 20.65 | 386.67 | 20.61 |
March | 744.00 | 20.85 | 304.83 | 20.77 | 304.83 | 20.72 |
April | 697.50 | 21.45 | 34.00 | 21.55 | 24.17 | 21.58 |
May | 706.67 | 21.58 | 31.67 | 21.80 | 14.83 | 21.92 |
June | 641.00 | 21.83 | 57.50 | 22.21 | 25.33 | 22.42 |
July | 619.83 | 22.18 | 118.50 | 22.89 | 54.00 | 23.25 |
August | 598.00 | 22.00 | 105.83 | 22.60 | 30.00 | 22.82 |
September | 636.67 | 21.57 | 52.17 | 21.86 | 7.33 | 21.90 |
October | 744.00 | 21.05 | 52.67 | 20.97 | 52.67 | 20.90 |
November | 720.00 | 20.70 | 365.83 | 20.59 | 365.83 | 20.53 |
December | 744.00 | 20.52 | 691.33 | 20.50 | 691.33 | 20.50 |
Annual Sum or Average | 8267.67 | 21.23 | 2719.33 | 21.24 | 2475.33 | 21.17 |
Minimum of Months | 598.00 | 20.52 | 31.67 | 20.50 | 7.33 | 20.50 |
Maximum of Months | 744.00 | 22.18 | 691.33 | 22.89 | 691.33 | 23.25 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 725.17 | 21.18 | 112.00 | 21.10 | 112.00 | 21.03 |
February | 645.67 | 21.25 | 31.33 | 21.22 | 29.83 | 21.18 |
March | 744.00 | 21.24 | 27.67 | 21.21 | 27.67 | 21.18 |
April | 654.00 | 21.47 | 7.00 | 21.49 | 0.00 | 21.49 |
May | 688.67 | 21.47 | 0.00 | 21.47 | 0.00 | 21.47 |
June | 660.00 | 21.51 | 0.00 | 21.51 | 0.00 | 21.51 |
July | 660.00 | 21.48 | 1.83 | 21.48 | 0.00 | 21.48 |
August | 638.83 | 21.41 | 15.00 | 21.46 | 0.00 | 21.46 |
September | 621.33 | 21.43 | 36.33 | 21.53 | 0.00 | 21.53 |
October | 695.50 | 21.31 | 9.17 | 21.31 | 5.00 | 21.30 |
November | 702.67 | 21.20 | 32.17 | 21.15 | 32.17 | 21.10 |
December | 739.67 | 21.02 | 199.83 | 20.89 | 199.83 | 20.80 |
Annual Sum or Average | 8175.50 | 21.33 | 472.33 | 21.30 | 406.50 | 21.26 |
Minimum of Months | 621.33 | 21.02 | 0.00 | 20.89 | 0.00 | 20.80 |
Maximum of Months | 744.00 | 21.51 | 199.83 | 21.53 | 199.83 | 21.53 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 345.50 | 23.13 | 45.33 | 23.23 | 0.00 | 23.23 |
February | 276.17 | 23.14 | 51.00 | 23.27 | 0.00 | 23.27 |
March | 233.50 | 23.13 | 63.50 | 23.32 | 0.00 | 23.32 |
April | 91.00 | 23.26 | 213.00 | 23.77 | 0.00 | 23.77 |
May | 44.83 | 23.22 | 447.83 | 23.91 | 0.00 | 23.91 |
June | 10.33 | 23.76 | 654.17 | 23.95 | 7.33 | 23.95 |
July | 0.00 | 0.00 | 717.50 | 23.96 | 0.00 | 23.96 |
August | 0.33 | 23.99 | 718.17 | 23.94 | 0.33 | 23.94 |
September | 10.67 | 23.17 | 571.00 | 23.93 | 0.00 | 23.93 |
October | 147.17 | 23.08 | 295.67 | 23.69 | 0.00 | 23.69 |
November | 265.67 | 23.08 | 134.50 | 23.39 | 0.00 | 23.39 |
December | 364.50 | 23.09 | 15.00 | 23.12 | 0.00 | 23.12 |
Annual Sum or Average | 1789.67 | 23.12 | 3926.67 | 23.70 | 7.67 | 23.70 |
Minimum of Months | 0.00 | 0.00 | 15.00 | 23.12 | 0.00 | 23.12 |
Maximum of Months | 364.50 | 23.99 | 718.17 | 23.96 | 7.33 | 23.96 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 162.67 | 23.17 | 213.00 | 23.64 | 0.00 | 23.64 |
February | 116.33 | 23.24 | 208.17 | 23.72 | 0.00 | 23.72 |
March | 84.83 | 23.30 | 301.50 | 23.84 | 0.00 | 23.84 |
April | 4.50 | 23.27 | 440.17 | 23.98 | 0.00 | 23.98 |
May | 0.33 | 23.14 | 630.83 | 23.98 | 0.00 | 23.98 |
June | 7.17 | 24.00 | 705.17 | 23.98 | 7.17 | 23.98 |
July | 0.00 | 0.00 | 741.50 | 23.98 | 0.00 | 23.98 |
August | 0.00 | 0.00 | 740.50 | 23.97 | 0.00 | 23.97 |
September | 0.00 | 0.00 | 673.50 | 23.96 | 0.00 | 23.96 |
October | 10.00 | 23.21 | 512.67 | 23.96 | 0.00 | 23.96 |
November | 105.17 | 23.20 | 300.83 | 23.79 | 0.00 | 23.79 |
December | 201.50 | 23.15 | 163.33 | 23.53 | 0.00 | 23.53 |
Annual Sum or Average | 692.50 | 23.21 | 5631.17 | 23.90 | 7.17 | 23.90 |
Minimum of Months | 0.00 | 0.00 | 163.33 | 23.53 | 0.00 | 23.53 |
Maximum of Months | 201.50 | 24.00 | 741.50 | 23.98 | 7.17 | 23.98 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 508.00 | 23.97 | 694.50 | 23.91 | 501.50 | 23.93 |
February | 460.33 | 23.99 | 624.00 | 23.92 | 459.67 | 23.94 |
March | 516.33 | 23.99 | 716.17 | 23.91 | 516.33 | 23.93 |
April | 511.00 | 23.99 | 714.00 | 23.92 | 511.00 | 23.94 |
May | 535.83 | 23.99 | 743.50 | 23.92 | 535.83 | 23.94 |
June | 532.67 | 23.99 | 720.00 | 23.94 | 532.67 | 23.96 |
July | 554.67 | 23.99 | 744.00 | 23.95 | 554.67 | 23.96 |
August | 550.00 | 23.99 | 744.00 | 23.95 | 550.00 | 23.96 |
September | 516.50 | 23.99 | 720.00 | 23.94 | 516.50 | 23.95 |
October | 526.17 | 23.99 | 742.17 | 23.91 | 526.17 | 23.93 |
November | 496.67 | 23.99 | 689.50 | 23.91 | 496.50 | 23.93 |
December | 496.67 | 23.98 | 681.67 | 23.92 | 495.00 | 23.94 |
Annual Sum or Average | 6204.83 | 23.99 | 8533.50 | 23.92 | 6195.83 | 23.94 |
Minimum of Months | 460.33 | 23.97 | 624.00 | 23.91 | 459.67 | 23.93 |
Maximum of Months | 554.67 | 23.99 | 744.00 | 23.95 | 554.67 | 23.96 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.02 | 37.17 | 21.02 | 37.17 | 21.02 |
February | 672.00 | 21.04 | 0.00 | 21.04 | 0.00 | 21.04 |
March | 744.00 | 21.03 | 0.00 | 21.03 | 0.00 | 21.03 |
April | 720.00 | 21.71 | 0.00 | 21.71 | 0.00 | 21.71 |
May | 741.00 | 21.84 | 0.00 | 21.84 | 0.00 | 21.84 |
June | 695.50 | 22.32 | 4.67 | 22.33 | 0.00 | 22.33 |
July | 673.33 | 22.49 | 12.17 | 22.52 | 0.00 | 22.52 |
August | 704.83 | 22.54 | 3.17 | 22.55 | 0.00 | 22.55 |
September | 708.00 | 22.18 | 0.00 | 22.18 | 0.00 | 22.18 |
October | 744.00 | 21.29 | 0.00 | 21.29 | 0.00 | 21.29 |
November | 720.00 | 21.03 | 0.00 | 21.03 | 0.00 | 21.03 |
December | 744.00 | 21.00 | 14.67 | 21.00 | 14.67 | 21.00 |
Annual Sum or Average | 8610.67 | 21.61 | 71.83 | 21.62 | 51.83 | 21.61 |
Minimum of Months | 672.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
Maximum of Months | 744.00 | 22.54 | 37.17 | 22.55 | 37.17 | 22.55 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.18798 | 34.66280 | 0.09353 | 5.31092 |
February | 672.00000 | 23.01607 | 36.00130 | 0.05817 | 5.18638 |
March | 744.00000 | 22.77663 | 35.57429 | -0.0060 | 5.13285 |
April | 720.00000 | 22.77830 | 35.15392 | -0.0065 | 5.16527 |
May | 744.00000 | 22.77285 | 40.60437 | -1.0077 | 26.64058 |
June | 720.00000 | 22.88558 | 47.91377 | -0.9180 | 22.99266 |
July | 744.00000 | 23.12301 | 49.45685 | -0.8199 | 19.41467 |
August | 744.00000 | 23.25983 | 49.45601 | -0.7701 | 17.70581 |
September | 720.00000 | 23.50704 | 44.80047 | -0.7096 | 15.81068 |
October | 744.00000 | 23.60927 | 40.17919 | 0.24358 | 6.33320 |
November | 720.00000 | 23.62768 | 36.75332 | 0.22419 | 6.14858 |
December | 744.00000 | 23.48280 | 33.83022 | 0.16467 | 5.67729 |
Annual Sum or Average | 8760.00000 | 23.16984 | 40.39276 | -0.2899 | 11.83948 |
Minimum of Months | 672.00000 | 22.77285 | 33.83022 | -1.0077 | 5.13285 |
Maximum of Months | 744.00000 | 23.62768 | 49.45685 | 0.24358 | 26.64058 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.12355 | 36.62003 | -0.4216 | 9.33622 |
February | 672.00000 | 21.17767 | 37.71982 | -0.3795 | 8.79970 |
March | 744.00000 | 21.02048 | 37.03496 | -0.4360 | 9.09397 |
April | 720.00000 | 21.51773 | 35.72767 | -0.2133 | 7.46271 |
May | 744.00000 | 21.37902 | 41.85776 | -1.3428 | 43.78515 |
June | 720.00000 | 21.45409 | 49.90880 | -1.2292 | 38.09592 |
July | 744.00000 | 21.69231 | 51.59292 | -1.1155 | 33.43133 |
August | 744.00000 | 21.88976 | 51.43990 | -1.0310 | 30.44499 |
September | 720.00000 | 21.90707 | 46.96171 | -1.0605 | 32.66126 |
October | 744.00000 | 21.34235 | 43.62667 | -0.2546 | 7.60197 |
November | 720.00000 | 21.10973 | 40.10605 | -0.3922 | 8.68245 |
December | 744.00000 | 21.05103 | 36.39636 | -0.4831 | 10.19108 |
Annual Sum or Average | 8760.00000 | 21.38928 | 42.44632 | -0.6989 | 20.03805 |
Minimum of Months | 672.00000 | 21.02048 | 35.72767 | -1.3428 | 7.46271 |
Maximum of Months | 744.00000 | 21.90707 | 51.59292 | -0.2133 | 43.78515 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.87174 | 37.92709 | -0.1948 | 6.11670 |
February | 672.00000 | 21.96013 | 38.91468 | -0.1648 | 5.82360 |
March | 744.00000 | 21.92636 | 38.06917 | -0.1786 | 5.97841 |
April | 720.00000 | 22.65400 | 36.36388 | 0.00694 | 5.44367 |
May | 744.00000 | 22.68839 | 41.78682 | -0.9772 | 25.87506 |
June | 720.00000 | 22.95228 | 48.78165 | -0.8318 | 20.21710 |
July | 744.00000 | 23.09652 | 50.50872 | -0.7642 | 18.07427 |
August | 744.00000 | 23.20165 | 50.65495 | -0.7249 | 16.51884 |
September | 720.00000 | 23.09500 | 46.82329 | -0.7905 | 18.80718 |
October | 744.00000 | 22.43055 | 43.85448 | -0.0082 | 5.38333 |
November | 720.00000 | 22.00359 | 40.96329 | -0.1414 | 5.71396 |
December | 744.00000 | 21.65678 | 37.97326 | -0.2530 | 6.60201 |
Annual Sum or Average | 8760.00000 | 22.46318 | 42.74406 | -0.4204 | 11.75213 |
Minimum of Months | 672.00000 | 21.65678 | 36.36388 | -0.9772 | 5.38333 |
Maximum of Months | 744.00000 | 23.20165 | 50.65495 | 0.00694 | 25.87506 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.99332 | 31.18733 | 0.63789 | 16.09982 |
February | 672.00000 | 22.99116 | 32.25771 | 0.64814 | 16.36970 |
March | 744.00000 | 22.98985 | 31.36355 | 0.64973 | 16.49021 |
April | 720.00000 | 23.02346 | 30.93857 | 0.69054 | 17.57012 |
May | 744.00000 | 23.02954 | 36.26018 | 0.00035 | 10.13348 |
June | 720.00000 | 23.04157 | 43.68958 | 0.07672 | 10.30262 |
July | 744.00000 | 23.05392 | 45.84701 | 0.10274 | 10.24196 |
August | 744.00000 | 23.04698 | 46.20203 | 0.11056 | 10.35494 |
September | 720.00000 | 23.05895 | 42.07501 | 0.07147 | 10.15961 |
October | 744.00000 | 23.03917 | 37.66453 | 0.72067 | 18.40670 |
November | 720.00000 | 23.01815 | 34.16490 | 0.67163 | 17.03999 |
December | 744.00000 | 22.96930 | 30.92226 | 0.62061 | 15.65983 |
Annual Sum or Average | 8760.00000 | 23.02137 | 36.90989 | 0.41528 | 14.05347 |
Minimum of Months | 672.00000 | 22.96930 | 30.92226 | 0.00035 | 10.13348 |
Maximum of Months | 744.00000 | 23.05895 | 46.20203 | 0.72067 | 18.40670 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.59355 | 40.69634 | -0.2141 | 6.73041 |
February | 672.00000 | 21.71131 | 41.65163 | -0.1615 | 6.40105 |
March | 744.00000 | 21.50506 | 41.08794 | -0.2309 | 6.43667 |
April | 720.00000 | 22.36895 | 39.20063 | 0.05864 | 6.21785 |
May | 744.00000 | 22.22833 | 45.05753 | -0.9805 | 26.80027 |
June | 720.00000 | 22.41021 | 52.50958 | -0.8443 | 21.22973 |
July | 744.00000 | 22.62917 | 54.14220 | -0.7358 | 18.01067 |
August | 744.00000 | 22.89213 | 53.87858 | -0.6267 | 14.97967 |
September | 720.00000 | 22.89091 | 49.65443 | -0.6535 | 16.64652 |
October | 744.00000 | 22.09313 | 46.94822 | 0.00228 | 6.22965 |
November | 720.00000 | 21.65115 | 43.94945 | -0.1722 | 6.27843 |
December | 744.00000 | 21.38380 | 40.67067 | -0.2998 | 7.36543 |
Annual Sum or Average | 8760.00000 | 22.11406 | 45.81533 | -0.4069 | 11.98230 |
Minimum of Months | 672.00000 | 21.38380 | 39.20063 | -0.9805 | 6.21785 |
Maximum of Months | 744.00000 | 22.89213 | 54.14220 | 0.05864 | 26.80027 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.24739 | 39.85461 | -0.0719 | 5.62366 |
February | 672.00000 | 22.33445 | 40.81666 | -0.0406 | 5.44924 |
March | 744.00000 | 22.26321 | 40.06478 | -0.0644 | 5.59527 |
April | 720.00000 | 22.92518 | 38.52774 | 0.11748 | 5.74302 |
May | 744.00000 | 22.91338 | 43.95787 | -0.8446 | 20.82259 |
June | 720.00000 | 23.12328 | 51.00681 | -0.7118 | 16.32397 |
July | 744.00000 | 23.24981 | 52.73995 | -0.6466 | 14.47325 |
August | 744.00000 | 23.37258 | 52.80612 | -0.5981 | 12.95394 |
September | 720.00000 | 23.34279 | 48.83413 | -0.6389 | 14.15978 |
October | 744.00000 | 22.75558 | 45.77118 | 0.11181 | 5.76590 |
November | 720.00000 | 22.36504 | 42.86686 | -0.0196 | 5.50632 |
December | 744.00000 | 22.04164 | 39.83176 | -0.1318 | 5.86516 |
Annual Sum or Average | 8760.00000 | 22.74577 | 44.78287 | -0.2968 | 9.88675 |
Minimum of Months | 672.00000 | 22.04164 | 38.52774 | -0.8446 | 5.44924 |
Maximum of Months | 744.00000 | 23.37258 | 52.80612 | 0.11748 | 20.82259 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.96644 | 49.35234 | -0.4748 | 10.19986 |
February | 672.00000 | 21.09984 | 49.87267 | -0.4188 | 9.19518 |
March | 744.00000 | 21.04800 | 49.45596 | -0.4331 | 9.14065 |
April | 720.00000 | 21.57022 | 46.96798 | -0.2105 | 6.95423 |
May | 744.00000 | 21.57236 | 50.81158 | -1.3087 | 41.89648 |
June | 720.00000 | 21.66938 | 53.09196 | -1.2049 | 36.93616 |
July | 744.00000 | 21.68965 | 52.93900 | -1.1716 | 35.45065 |
August | 744.00000 | 21.69054 | 53.15817 | -1.1726 | 35.51526 |
September | 720.00000 | 21.65819 | 52.82243 | -1.2292 | 38.21041 |
October | 744.00000 | 21.29371 | 54.93825 | -0.2942 | 7.46961 |
November | 720.00000 | 21.01458 | 52.99912 | -0.4331 | 9.31684 |
December | 744.00000 | 20.76181 | 49.60146 | -0.5518 | 11.72833 |
Annual Sum or Average | 8760.00000 | 21.33661 | 51.34476 | -0.7443 | 21.07786 |
Minimum of Months | 672.00000 | 20.76181 | 46.96798 | -1.3087 | 6.95423 |
Maximum of Months | 744.00000 | 21.69054 | 54.93825 | -0.2105 | 41.89648 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.74957 | 49.99532 | -0.5459 | 11.59580 |
February | 672.00000 | 20.87306 | 50.59444 | -0.4953 | 10.37088 |
March | 744.00000 | 20.94240 | 49.75971 | -0.4681 | 9.73048 |
April | 720.00000 | 21.53968 | 47.24838 | -0.2485 | 7.46037 |
May | 744.00000 | 21.69335 | 50.77474 | -1.2989 | 42.69239 |
June | 720.00000 | 22.02716 | 52.50989 | -1.1173 | 35.36301 |
July | 744.00000 | 22.43339 | 51.80867 | -0.9780 | 31.60122 |
August | 744.00000 | 22.38875 | 52.71637 | -1.0049 | 30.93933 |
September | 720.00000 | 21.88509 | 53.82784 | -1.2135 | 38.40912 |
October | 744.00000 | 21.14072 | 55.63690 | -0.3546 | 7.98131 |
November | 720.00000 | 20.82875 | 53.57010 | -0.4933 | 10.33481 |
December | 744.00000 | 20.61707 | 50.03531 | -0.5973 | 12.82500 |
Annual Sum or Average | 8760.00000 | 21.42956 | 51.54484 | -0.7362 | 20.83763 |
Minimum of Months | 672.00000 | 20.61707 | 47.24838 | -1.2989 | 7.46037 |
Maximum of Months | 744.00000 | 22.43339 | 55.63690 | -0.2485 | 42.69239 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.05430 | 46.50339 | -0.4349 | 9.09980 |
February | 672.00000 | 21.09873 | 47.41067 | -0.4142 | 8.61667 |
March | 744.00000 | 21.21666 | 46.23230 | -0.3722 | 7.95256 |
April | 720.00000 | 21.44614 | 44.79055 | -0.2993 | 7.12149 |
May | 744.00000 | 21.52404 | 48.46181 | -1.4055 | 46.09121 |
June | 720.00000 | 21.71061 | 51.18997 | -1.2986 | 40.88451 |
July | 744.00000 | 21.88557 | 51.85110 | -1.2304 | 37.67768 |
August | 744.00000 | 21.86766 | 52.29590 | -1.2440 | 38.13042 |
September | 720.00000 | 21.58470 | 51.85279 | -1.3655 | 44.03348 |
October | 744.00000 | 21.27974 | 51.88838 | -0.3142 | 7.12713 |
November | 720.00000 | 21.12696 | 49.78208 | -0.3863 | 8.19469 |
December | 744.00000 | 21.00357 | 46.29285 | -0.4566 | 9.43569 |
Annual Sum or Average | 8760.00000 | 21.40163 | 49.05550 | -0.7706 | 22.10751 |
Minimum of Months | 672.00000 | 21.00357 | 44.79055 | -1.4055 | 7.12149 |
Maximum of Months | 744.00000 | 21.88557 | 52.29590 | -0.2993 | 46.09121 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.96478 | 49.30946 | -0.4745 | 10.16245 |
February | 672.00000 | 21.10182 | 49.85685 | -0.4235 | 9.17320 |
March | 744.00000 | 21.07904 | 49.35110 | -0.4268 | 9.05207 |
April | 720.00000 | 21.65783 | 46.47845 | -0.1807 | 6.83900 |
May | 744.00000 | 21.64221 | 50.02509 | -1.2861 | 40.85543 |
June | 720.00000 | 21.69909 | 52.62717 | -1.2053 | 36.97918 |
July | 744.00000 | 21.72110 | 52.43797 | -1.1702 | 35.39580 |
August | 744.00000 | 21.71573 | 52.43494 | -1.1612 | 35.05105 |
September | 720.00000 | 21.70537 | 51.97985 | -1.2017 | 36.99490 |
October | 744.00000 | 21.33220 | 54.48544 | -0.2849 | 7.40025 |
November | 720.00000 | 21.01245 | 52.95703 | -0.4332 | 9.27032 |
December | 744.00000 | 20.77846 | 49.52067 | -0.5433 | 11.54266 |
Annual Sum or Average | 8760.00000 | 21.36803 | 50.96376 | -0.7349 | 20.80165 |
Minimum of Months | 672.00000 | 20.77846 | 46.47845 | -1.2861 | 6.83900 |
Maximum of Months | 744.00000 | 21.72110 | 54.48544 | -0.1807 | 40.85543 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.74807 | 49.98016 | -0.5452 | 11.57272 |
February | 672.00000 | 20.84727 | 50.66392 | -0.5057 | 10.52977 |
March | 744.00000 | 20.97690 | 49.62670 | -0.4612 | 9.59481 |
April | 720.00000 | 21.65714 | 46.60176 | -0.2128 | 6.98706 |
May | 744.00000 | 21.72013 | 50.12143 | -1.2889 | 41.08485 |
June | 720.00000 | 21.93960 | 52.58904 | -1.1509 | 35.18655 |
July | 744.00000 | 22.16326 | 52.41219 | -1.0609 | 31.48965 |
August | 744.00000 | 22.19643 | 52.74760 | -1.0543 | 30.73396 |
September | 720.00000 | 21.89382 | 52.87246 | -1.1979 | 36.79875 |
October | 744.00000 | 21.20281 | 55.21256 | -0.3398 | 7.79082 |
November | 720.00000 | 20.82166 | 53.55490 | -0.4942 | 10.32995 |
December | 744.00000 | 20.63447 | 49.94396 | -0.5888 | 12.62477 |
Annual Sum or Average | 8760.00000 | 21.40273 | 51.36580 | -0.7434 | 20.45354 |
Minimum of Months | 672.00000 | 20.63447 | 46.60176 | -1.2889 | 6.98706 |
Maximum of Months | 744.00000 | 22.19643 | 55.21256 | -0.2128 | 41.08485 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.84764 | 50.93151 | -0.5302 | 11.48187 |
February | 672.00000 | 20.99455 | 51.39419 | -0.4667 | 10.20832 |
March | 744.00000 | 20.95950 | 51.00822 | -0.4739 | 9.99918 |
April | 720.00000 | 21.55155 | 47.83906 | -0.2225 | 7.32757 |
May | 744.00000 | 21.54925 | 51.86336 | -1.3269 | 43.05550 |
June | 720.00000 | 21.65839 | 54.13283 | -1.2093 | 37.41631 |
July | 744.00000 | 21.68179 | 53.96200 | -1.1715 | 35.72148 |
August | 744.00000 | 21.67875 | 54.40257 | -1.1773 | 36.00026 |
September | 720.00000 | 21.63564 | 54.28656 | -1.2491 | 39.42352 |
October | 744.00000 | 21.21715 | 56.76737 | -0.3291 | 8.06323 |
November | 720.00000 | 20.90233 | 54.82659 | -0.4816 | 10.34700 |
December | 744.00000 | 20.65542 | 51.14576 | -0.6073 | 13.16140 |
Annual Sum or Average | 8760.00000 | 21.27825 | 52.72354 | -0.7727 | 21.92667 |
Minimum of Months | 672.00000 | 20.65542 | 47.83906 | -1.3269 | 7.32757 |
Maximum of Months | 744.00000 | 21.68179 | 56.76737 | -0.2225 | 43.05550 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.63642 | 51.63763 | -0.6017 | 13.04547 |
February | 672.00000 | 20.74881 | 52.23503 | -0.5489 | 11.64057 |
March | 744.00000 | 20.84577 | 51.36271 | -0.5114 | 10.69836 |
April | 720.00000 | 21.54635 | 48.13052 | -0.2571 | 7.99328 |
May | 744.00000 | 21.71061 | 51.77495 | -1.3050 | 43.95906 |
June | 720.00000 | 22.07750 | 53.30209 | -1.1002 | 35.94109 |
July | 744.00000 | 22.54124 | 52.20631 | -0.9380 | 32.22159 |
August | 744.00000 | 22.47647 | 53.46080 | -0.9748 | 31.29974 |
September | 720.00000 | 21.90949 | 55.19966 | -1.2201 | 39.57707 |
October | 744.00000 | 21.04760 | 57.55835 | -0.3955 | 8.71539 |
November | 720.00000 | 20.70416 | 55.49078 | -0.5454 | 11.58304 |
December | 744.00000 | 20.52459 | 51.56902 | -0.6512 | 14.34381 |
Annual Sum or Average | 8760.00000 | 21.40097 | 52.82996 | -0.7555 | 21.81248 |
Minimum of Months | 672.00000 | 20.52459 | 48.13052 | -1.3050 | 7.99328 |
Maximum of Months | 744.00000 | 22.54124 | 57.55835 | -0.2571 | 43.95906 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.23399 | 48.92137 | -0.3781 | 9.00376 |
February | 672.00000 | 21.32923 | 49.53273 | -0.3337 | 8.29486 |
March | 744.00000 | 21.24271 | 49.27735 | -0.3772 | 8.43360 |
April | 720.00000 | 21.64243 | 47.09418 | -0.1838 | 7.03945 |
May | 744.00000 | 21.60979 | 50.92692 | -1.3216 | 42.76148 |
June | 720.00000 | 21.66569 | 53.64399 | -1.2500 | 39.19553 |
July | 744.00000 | 21.68768 | 53.52409 | -1.2138 | 37.56840 |
August | 744.00000 | 21.68460 | 52.96884 | -1.1925 | 36.74588 |
September | 720.00000 | 21.68889 | 51.64795 | -1.2043 | 37.52631 |
October | 744.00000 | 21.43886 | 53.80275 | -0.2393 | 7.19503 |
November | 720.00000 | 21.25118 | 52.42488 | -0.3495 | 8.35349 |
December | 744.00000 | 21.03748 | 49.36217 | -0.4635 | 10.30768 |
Annual Sum or Average | 8760.00000 | 21.45932 | 51.10557 | -0.7116 | 21.11833 |
Minimum of Months | 672.00000 | 21.03748 | 47.09418 | -1.3216 | 7.03945 |
Maximum of Months | 744.00000 | 21.68889 | 53.80275 | -0.1838 | 42.76148 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.57307 | 39.87303 | 0.26454 | 6.91949 |
February | 672.00000 | 23.61985 | 40.74769 | 0.28764 | 7.01892 |
March | 744.00000 | 23.69237 | 39.57468 | 0.31276 | 7.31707 |
April | 720.00000 | 23.84406 | 38.52118 | 0.38020 | 8.18125 |
May | 744.00000 | 23.87412 | 43.35599 | -0.4511 | 9.46357 |
June | 720.00000 | 23.92624 | 49.88605 | -0.3504 | 7.71366 |
July | 744.00000 | 23.94806 | 51.80508 | -0.3177 | 7.22728 |
August | 744.00000 | 23.92717 | 52.23468 | -0.3294 | 7.37086 |
September | 720.00000 | 23.88403 | 48.80259 | -0.4006 | 8.54777 |
October | 744.00000 | 23.74554 | 45.37845 | 0.37941 | 8.20405 |
November | 720.00000 | 23.63409 | 42.52061 | 0.30987 | 7.35495 |
December | 744.00000 | 23.53958 | 39.64007 | 0.24909 | 6.73243 |
Annual Sum or Average | 8760.00000 | 23.76796 | 44.38512 | 0.02620 | 7.67325 |
Minimum of Months | 672.00000 | 23.53958 | 38.52118 | -0.4511 | 6.73243 |
Maximum of Months | 744.00000 | 23.94806 | 52.23468 | 0.38020 | 9.46357 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.75697 | 38.64906 | 0.34999 | 7.84873 |
February | 672.00000 | 23.80055 | 39.53371 | 0.37197 | 8.04309 |
March | 744.00000 | 23.84905 | 38.38696 | 0.39194 | 8.35135 |
April | 720.00000 | 23.93740 | 37.54603 | 0.44011 | 9.13718 |
May | 744.00000 | 23.94887 | 42.41093 | -0.3714 | 7.99081 |
June | 720.00000 | 23.97489 | 49.07822 | -0.2841 | 6.78634 |
July | 744.00000 | 23.98398 | 51.05898 | -0.2578 | 6.47974 |
August | 744.00000 | 23.97173 | 51.46551 | -0.2672 | 6.56740 |
September | 720.00000 | 23.94981 | 47.91169 | -0.3278 | 7.37899 |
October | 744.00000 | 23.87480 | 44.22554 | 0.44978 | 9.33021 |
November | 720.00000 | 23.80157 | 41.29710 | 0.39113 | 8.39769 |
December | 744.00000 | 23.73628 | 38.41369 | 0.33778 | 7.64163 |
Annual Sum or Average | 8760.00000 | 23.88246 | 43.35580 | 0.10034 | 7.82663 |
Minimum of Months | 672.00000 | 23.73628 | 37.54603 | -0.3714 | 6.47974 |
Maximum of Months | 744.00000 | 23.98398 | 51.46551 | 0.44978 | 9.33021 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.79043 | 36.95126 | 0.98847 | 27.72875 |
February | 672.00000 | 23.78728 | 37.86505 | 1.00308 | 28.38893 |
March | 744.00000 | 23.81525 | 36.93983 | 1.01763 | 28.82488 |
April | 720.00000 | 23.85535 | 36.43679 | 1.09089 | 32.13089 |
May | 744.00000 | 23.86991 | 41.33975 | 0.55487 | 16.18926 |
June | 720.00000 | 23.90699 | 48.14125 | 0.65086 | 18.55259 |
July | 744.00000 | 23.91747 | 50.16240 | 0.68536 | 19.47654 |
August | 744.00000 | 23.92120 | 50.46887 | 0.68674 | 19.51496 |
September | 720.00000 | 23.89669 | 46.72720 | 0.62059 | 17.91377 |
October | 744.00000 | 23.84465 | 42.74884 | 1.08708 | 31.80362 |
November | 720.00000 | 23.80874 | 39.69505 | 1.02179 | 29.01939 |
December | 744.00000 | 23.77629 | 36.74104 | 0.96866 | 26.89412 |
Annual Sum or Average | 8760.00000 | 23.84950 | 42.04423 | 0.86373 | 24.67612 |
Minimum of Months | 672.00000 | 23.77629 | 36.43679 | 0.55487 | 16.18926 |
Maximum of Months | 744.00000 | 23.92120 | 50.46887 | 1.09089 | 32.13089 |
Report: OccupantComfortDataSummaryMonthly
For: STORAGE_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.01989 | 36.31260 | -0.4469 | 9.22901 |
February | 672.00000 | 21.01494 | 37.50834 | -0.4379 | 9.02093 |
March | 744.00000 | 21.04446 | 36.55730 | -0.4305 | 8.90408 |
April | 720.00000 | 21.63987 | 34.95432 | -0.2827 | 6.88529 |
May | 744.00000 | 21.83320 | 40.36972 | -1.3244 | 41.71210 |
June | 720.00000 | 22.36272 | 47.00032 | -1.0975 | 30.65178 |
July | 744.00000 | 22.60504 | 48.58569 | -1.0018 | 26.56828 |
August | 744.00000 | 22.64748 | 48.85737 | -0.9862 | 25.64301 |
September | 720.00000 | 22.36266 | 45.39565 | -1.1078 | 31.09597 |
October | 744.00000 | 21.49024 | 42.78246 | -0.2741 | 6.72280 |
November | 720.00000 | 21.07351 | 39.70876 | -0.4040 | 8.46600 |
December | 744.00000 | 21.00212 | 36.04036 | -0.4605 | 9.45065 |
Annual Sum or Average | 8760.00000 | 21.67807 | 41.19637 | -0.6895 | 17.91969 |
Minimum of Months | 672.00000 | 21.00212 | 34.95432 | -1.3244 | 6.72280 |
Maximum of Months | 744.00000 | 22.64748 | 48.85737 | -0.2741 | 41.71210 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.01534 | 39.33713 | -0.4392 | 9.07015 |
February | 672.00000 | 21.02558 | 40.50037 | -0.4251 | 8.78618 |
March | 744.00000 | 21.03027 | 39.57594 | -0.4284 | 8.85508 |
April | 720.00000 | 21.71065 | 37.84320 | -0.2570 | 6.64166 |
May | 744.00000 | 21.92212 | 43.20094 | -1.2892 | 39.91800 |
June | 720.00000 | 22.32370 | 50.12593 | -1.1043 | 30.93553 |
July | 744.00000 | 22.55270 | 51.74033 | -1.0123 | 27.04967 |
August | 744.00000 | 22.63503 | 51.93872 | -0.9827 | 25.51173 |
September | 720.00000 | 22.37944 | 48.35780 | -1.0951 | 30.54819 |
October | 744.00000 | 21.42049 | 45.91741 | -0.2862 | 6.96865 |
November | 720.00000 | 21.02469 | 42.78126 | -0.4138 | 8.60401 |
December | 744.00000 | 21.00155 | 39.03232 | -0.4538 | 9.32029 |
Annual Sum or Average | 8760.00000 | 21.67335 | 44.21995 | -0.6840 | 17.74081 |
Minimum of Months | 672.00000 | 21.00155 | 37.84320 | -1.2892 | 6.64166 |
Maximum of Months | 744.00000 | 22.63503 | 51.93872 | -0.2570 | 39.91800 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.02191 | 37.11284 | -0.4331 | 8.98563 |
February | 672.00000 | 21.04235 | 38.27267 | -0.4129 | 8.59978 |
March | 744.00000 | 21.03161 | 37.33638 | -0.4143 | 8.61477 |
April | 720.00000 | 21.71144 | 35.59803 | -0.2304 | 6.60231 |
May | 744.00000 | 21.84903 | 41.05219 | -1.2667 | 39.12913 |
June | 720.00000 | 22.35564 | 47.67056 | -1.0401 | 28.53057 |
July | 744.00000 | 22.59407 | 49.26444 | -0.9426 | 24.64606 |
August | 744.00000 | 22.59172 | 49.68616 | -0.9419 | 24.30551 |
September | 720.00000 | 22.20528 | 46.42643 | -1.1033 | 31.34371 |
October | 744.00000 | 21.28641 | 43.98798 | -0.2977 | 7.05154 |
November | 720.00000 | 21.02810 | 40.56113 | -0.4015 | 8.40841 |
December | 744.00000 | 21.00476 | 36.81312 | -0.4495 | 9.24434 |
Annual Sum or Average | 8760.00000 | 21.64648 | 42.00593 | -0.6629 | 17.17433 |
Minimum of Months | 672.00000 | 21.00476 | 35.59803 | -1.2667 | 6.60231 |
Maximum of Months | 744.00000 | 22.59407 | 49.68616 | -0.2304 | 39.12913 |
Report: OccupantComfortDataSummaryMonthly
For: MECH_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.15629 | 35.61120 | -0.4101 | 8.61823 |
February | 672.00000 | 21.14727 | 36.82349 | -0.4026 | 8.43667 |
March | 744.00000 | 21.25687 | 35.71162 | -0.3801 | 8.10244 |
April | 720.00000 | 21.97426 | 33.88674 | -0.2107 | 6.16360 |
May | 744.00000 | 22.16664 | 39.19826 | -1.2222 | 36.60060 |
June | 720.00000 | 22.66826 | 45.76868 | -1.0035 | 26.58673 |
July | 744.00000 | 22.90134 | 47.35046 | -0.9104 | 22.94107 |
August | 744.00000 | 22.94898 | 47.59956 | -0.8931 | 22.00739 |
September | 720.00000 | 22.68804 | 44.14605 | -1.0075 | 26.71885 |
October | 744.00000 | 21.85900 | 41.48214 | -0.1939 | 5.96139 |
November | 720.00000 | 21.32750 | 38.72558 | -0.3449 | 7.59632 |
December | 744.00000 | 21.07301 | 35.49245 | -0.4352 | 8.99567 |
Annual Sum or Average | 8760.00000 | 21.93450 | 40.17174 | -0.6193 | 15.77595 |
Minimum of Months | 672.00000 | 21.07301 | 33.88674 | -1.2222 | 5.96139 |
Maximum of Months | 744.00000 | 22.94898 | 47.59956 | -0.1939 | 36.60060 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.201157E+10 | 15470.53 | 19-JAN-16:01 | 261.36 | 0.948729E+10 | 0.00 | 0.114989E+11 | 1.66 | 4.72 | 01-JAN-08:40 | 0.00 | 0.00 |
February | 0.218906E+10 | 16086.11 | 27-FEB-16:01 | 282.04 | 0.103245E+11 | 0.00 | 0.125136E+11 | 1.98 | 4.72 | 01-FEB-06:05 | 0.00 | 0.00 |
March | 0.201937E+10 | 15461.79 | 20-MAR-15:01 | 321.59 | 0.952407E+10 | 0.00 | 0.115434E+11 | 2.04 | 4.72 | 01-MAR-06:05 | 0.00 | 0.00 |
April | 0.176654E+11 | 88888.60 | 30-APR-18:03 | 665.46 | 0.811516E+11 | 0.00 | 0.988170E+11 | 4.34 | 4.72 | 01-APR-06:30 | 0.00 | 0.00 |
May | 0.186935E+11 | 84594.04 | 22-MAY-15:03 | 709.13 | 0.863390E+11 | 0.00 | 0.105032E+12 | 4.47 | 4.72 | 01-MAY-00:20 | 0.00 | 0.00 |
June | 0.330699E+11 | 114203.66 | 12-JUN-18:03 | 717.83 | 0.148802E+12 | 0.00 | 0.181872E+12 | 4.62 | 4.72 | 01-JUN-00:10 | 0.00 | 0.00 |
July | 0.457432E+11 | 122332.14 | 22-JUL-18:03 | 743.50 | 0.202751E+12 | 0.00 | 0.248494E+12 | 4.58 | 4.72 | 01-JUL-00:40 | 0.00 | 0.00 |
August | 0.490709E+11 | 104967.75 | 14-AUG-18:03 | 744.00 | 0.218990E+12 | 0.00 | 0.268061E+12 | 4.56 | 4.72 | 01-AUG-00:05 | 0.00 | 0.00 |
September | 0.339915E+11 | 87813.17 | 13-SEP-15:03 | 718.44 | 0.153388E+12 | 0.00 | 0.187379E+12 | 4.62 | 4.72 | 01-SEP-00:10 | 0.00 | 0.00 |
October | 0.878565E+10 | 55551.31 | 07-OCT-15:03 | 546.55 | 0.411170E+11 | 0.00 | 0.499027E+11 | 3.46 | 4.72 | 01-OCT-00:20 | 0.00 | 0.00 |
November | 0.215861E+10 | 18015.24 | 05-NOV-15:01 | 297.94 | 0.101793E+11 | 0.00 | 0.123380E+11 | 1.95 | 4.72 | 01-NOV-05:50 | 0.00 | 0.00 |
December | 0.462468E+09 | 6182.08 | 21-DEC-19:02 | 134.62 | 0.218119E+10 | 0.00 | 0.264366E+10 | 0.85 | 4.72 | 01-DEC-07:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.215861E+12 | 6142.47 | 0.974235E+12 | 0.00 | 0.119010E+13 | 3.26 | 0.00 | 0.00 | ||||
Minimum of Months | 0.462468E+09 | 6182.08 | 134.62 | 0.218119E+10 | 0.00 | 0.264366E+10 | 0.85 | 4.72 | 0.00 | 0.00 | ||
Maximum of Months | 0.490709E+11 | 122332.14 | 744.00 | 0.218990E+12 | 0.00 | 0.268061E+12 | 4.62 | 4.72 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.916581E+11 | 0.00 | 744.00 | 163151.32 | 28-JAN-19:04 | 0.00 | 39.58 | 60.00 | 0.36 | 0.00 | 0.09 | 0.44 | 28-JAN-19:04 |
February | 0.574853E+11 | 0.00 | 671.83 | 157637.56 | 26-FEB-19:04 | 0.00 | 40.42 | 59.99 | 0.26 | 0.00 | 0.06 | 0.42 | 26-FEB-19:04 |
March | 0.873712E+11 | 0.00 | 744.00 | 141981.40 | 17-MAR-15:04 | 0.00 | 39.56 | 60.00 | 0.33 | 0.00 | 0.09 | 0.38 | 17-MAR-15:04 |
April | 0.807021E+11 | 0.00 | 627.41 | 132127.96 | 05-APR-08:05 | 0.00 | 35.73 | 55.91 | 0.27 | 0.00 | 0.08 | 0.35 | 05-APR-08:05 |
May | 0.103239E+12 | 0.00 | 642.53 | 130764.86 | 05-MAY-08:05 | 0.00 | 32.50 | 55.39 | 0.33 | 0.00 | 0.10 | 0.35 | 05-MAY-08:05 |
June | 0.750394E+11 | 0.00 | 508.97 | 113930.99 | 07-JUN-10:15 | 0.00 | 27.27 | 49.72 | 0.23 | 0.00 | 0.08 | 0.30 | 07-JUN-10:15 |
July | 0.510280E+11 | 0.00 | 401.44 | 103895.53 | 31-JUL-04:30 | 0.00 | 26.02 | 43.80 | 0.15 | 0.00 | 0.05 | 0.28 | 31-JUL-04:30 |
August | 0.380206E+11 | 0.00 | 354.16 | 101170.58 | 20-AUG-05:07 | 0.00 | 26.26 | 42.28 | 0.11 | 0.00 | 0.04 | 0.27 | 20-AUG-05:07 |
September | 0.735277E+11 | 0.00 | 456.33 | 123538.24 | 28-SEP-06:05 | 0.00 | 28.33 | 47.84 | 0.23 | 0.00 | 0.08 | 0.33 | 28-SEP-06:05 |
October | 0.116704E+12 | 0.00 | 707.92 | 164474.96 | 19-OCT-08:04 | 0.00 | 34.63 | 58.48 | 0.39 | 0.00 | 0.12 | 0.44 | 19-OCT-08:04 |
November | 0.118920E+12 | 0.00 | 720.00 | 164512.21 | 21-NOV-16:02 | 0.00 | 38.01 | 60.00 | 0.45 | 0.00 | 0.12 | 0.44 | 21-NOV-16:02 |
December | 0.809499E+11 | 0.00 | 744.00 | 172812.60 | 16-DEC-16:04 | 0.00 | 38.68 | 60.00 | 0.33 | 0.00 | 0.08 | 0.46 | 16-DEC-16:04 |
Annual Sum or Average | 0.974645E+12 | 0.00 | 7322.59 | 0.00 | 33.88 | 54.42 | 0.29 | 0.00 | 0.08 | ||||
Minimum of Months | 0.380206E+11 | 0.00 | 354.16 | 101170.58 | 0.00 | 26.02 | 42.28 | 0.11 | 0.00 | 0.04 | 0.27 | ||
Maximum of Months | 0.118920E+12 | 0.00 | 744.00 | 172812.60 | 0.00 | 40.42 | 60.00 | 0.45 | 0.00 | 0.12 | 0.46 |
Report: DXReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 |
April | 0.871154E+09 | 0.00 | 37.50 | 0.871154E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17047.43 | 30-APR-15:02 | 17047.43 | 30-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.908508E+09 | 0.00 | 48.17 | 0.908508E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17029.33 | 22-MAY-15:02 | 17029.33 | 22-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.290652E+10 | 0.00 | 130.50 | 0.269898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31376.35 | 25-JUN-18:03 | 17887.51 | 13-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.528296E+10 | 0.00 | 236.67 | 0.509039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20042.47 | 23-JUL-16:00 | 19223.45 | 22-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.612201E+10 | 0.00 | 286.00 | 0.589890E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19239.53 | 17-AUG-15:02 | 17963.67 | 14-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.309486E+10 | 0.00 | 152.83 | 0.300021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18537.15 | 10-SEP-15:55 | 16368.41 | 13-SEP-15:01 | 0.00 | 0.00 | 0.00 |
October | 0.156128E+09 | 0.00 | 16.67 | 0.156128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8578.33 | 07-OCT-15:01 | 8578.33 | 07-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.193421E+11 | 0.00 | 908.33 | 0.186243E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.612201E+10 | 0.00 | 286.00 | 0.589890E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31376.35 | 19223.45 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 |
April | 0.152719E+11 | 0.00 | 66.33 | 0.152564E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 186075.45 | 30-APR-18:10 | 186075.45 | 30-APR-18:10 | 0.00 | 0.00 | 0.00 |
May | 0.154628E+11 | 0.00 | 84.50 | 0.154628E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 160089.16 | 22-MAY-15:21 | 160089.16 | 22-MAY-15:21 | 0.00 | 0.00 | 0.00 |
June | 0.494767E+11 | 0.00 | 226.67 | 0.471619E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 335438.29 | 25-JUN-18:00 | 210234.17 | 12-JUN-18:10 | 0.00 | 0.00 | 0.00 |
July | 0.853833E+11 | 0.00 | 374.75 | 0.842582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 234725.63 | 22-JUL-18:10 | 234725.63 | 22-JUL-18:10 | 0.00 | 0.00 | 0.00 |
August | 0.994403E+11 | 0.00 | 435.33 | 0.983440E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 213132.70 | 14-AUG-18:10 | 213132.70 | 14-AUG-18:10 | 0.00 | 0.00 | 0.00 |
September | 0.513385E+11 | 0.00 | 276.69 | 0.509601E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 160440.29 | 11-SEP-17:04 | 160440.29 | 11-SEP-17:04 | 0.00 | 0.00 | 0.00 |
October | 0.269335E+10 | 0.00 | 31.83 | 0.269335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72291.81 | 07-OCT-15:03 | 72291.81 | 07-OCT-15:03 | 0.00 | 0.00 | 0.00 |
November | 50951902.96 | 0.00 | 1.00 | 50951902.96 | 0.00 | 0.00 | 0.00 | 0.00 | 29307.42 | 24-NOV-11:50 | 29307.42 | 24-NOV-11:50 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319118E+12 | 0.00 | 1497.11 | 0.314188E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.994403E+11 | 0.00 | 435.33 | 0.983440E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 335438.29 | 234725.63 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 51301204.30 | 0.00 | 16.29 | 24176778.07 | 0.00 | 0.00 | 0.00 | 0.00 | 14329.17 | 25-JAN-16:01 | 14329.17 | 25-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.267690E+09 | 0.00 | 51.45 | 0.122381E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14321.86 | 27-FEB-16:01 | 14321.86 | 27-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.136805E+09 | 0.00 | 35.50 | 64419913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 13372.37 | 23-MAR-18:01 | 13372.37 | 23-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.297280E+10 | 0.00 | 407.22 | 0.169866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15022.46 | 29-APR-08:61 | 15022.46 | 29-APR-08:61 | 0.00 | 0.00 | 0.00 |
May | 0.365411E+10 | 0.00 | 467.72 | 0.202237E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16095.71 | 11-MAY-18:03 | 16095.71 | 11-MAY-18:03 | 0.00 | 0.00 | 0.00 |
June | 0.551328E+10 | 0.00 | 619.71 | 0.292119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16617.84 | 04-JUN-15:01 | 15337.10 | 05-JUN-15:01 | 0.00 | 0.00 | 0.00 |
July | 0.687527E+10 | 0.00 | 640.61 | 0.373584E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16784.67 | 08-JUL-15:02 | 15397.53 | 18-JUL-18:01 | 0.00 | 0.00 | 0.00 |
August | 0.654508E+10 | 0.00 | 676.15 | 0.332817E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17223.13 | 08-AUG-15:01 | 15245.02 | 15-AUG-18:01 | 0.00 | 0.00 | 0.00 |
September | 0.474899E+10 | 0.00 | 576.40 | 0.241152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17390.20 | 16-SEP-15:02 | 15391.03 | 10-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.110413E+10 | 0.00 | 187.79 | 0.569643E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15692.55 | 20-OCT-15:02 | 15076.48 | 10-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 62283202.18 | 0.00 | 20.52 | 25088704.41 | 0.00 | 0.00 | 0.00 | 0.00 | 14752.56 | 10-NOV-16:01 | 14752.56 | 10-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 1576399.79 | 0.00 | 0.74 | 267849.47 | 0.00 | 0.00 | 0.00 | 0.00 | 1306.84 | 19-DEC-19:05 | 328.83 | 19-DEC-19:05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319333E+11 | 0.00 | 3700.09 | 0.169237E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1576399.79 | 0.00 | 0.74 | 267849.47 | 0.00 | 0.00 | 0.00 | 0.00 | 1306.84 | 328.83 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.687527E+10 | 0.00 | 676.15 | 0.373584E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17390.20 | 16095.71 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 9182999.48 | 0.00 | 2.81 | 4368965.92 | 0.00 | 0.00 | 0.00 | 0.00 | 12235.11 | 19-JAN-16:01 | 12235.11 | 19-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 74485642.64 | 0.00 | 17.05 | 32922333.27 | 0.00 | 0.00 | 0.00 | 0.00 | 13161.17 | 27-FEB-16:01 | 13161.17 | 27-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 68443678.22 | 0.00 | 19.30 | 29393248.13 | 0.00 | 0.00 | 0.00 | 0.00 | 12112.55 | 23-MAR-18:01 | 12112.55 | 23-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.168838E+10 | 0.00 | 280.72 | 0.937418E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14217.14 | 28-APR-19:01 | 14217.14 | 28-APR-19:01 | 0.00 | 0.00 | 0.00 |
May | 0.253859E+10 | 0.00 | 375.34 | 0.134510E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15911.35 | 22-MAY-21:31 | 15533.38 | 25-MAY-17:01 | 0.00 | 0.00 | 0.00 |
June | 0.425720E+10 | 0.00 | 529.12 | 0.217510E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17800.86 | 26-JUN-21:01 | 15685.48 | 15-JUN-17:52 | 0.00 | 0.00 | 0.00 |
July | 0.460792E+10 | 0.00 | 492.44 | 0.232771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17067.85 | 23-JUL-21:31 | 16962.87 | 28-JUL-17:52 | 0.00 | 0.00 | 0.00 |
August | 0.362882E+10 | 0.00 | 472.26 | 0.158575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16360.89 | 11-AUG-19:11 | 15248.66 | 01-AUG-19:31 | 0.00 | 0.00 | 0.00 |
September | 0.219606E+10 | 0.00 | 403.24 | 0.887288E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15941.74 | 14-SEP-18:01 | 15504.46 | 14-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.394722E+09 | 0.00 | 84.97 | 0.197025E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14968.61 | 10-OCT-15:01 | 14956.34 | 06-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 13621625.42 | 0.00 | 4.47 | 6002426.06 | 0.00 | 0.00 | 0.00 | 0.00 | 12667.67 | 10-NOV-16:01 | 12667.67 | 10-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 243614.34 | 0.00 | 0.26 | 26528.82 | 0.00 | 0.00 | 0.00 | 0.00 | 429.73 | 20-DEC-19:06 | 51.99 | 04-DEC-19:07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.194777E+11 | 0.00 | 2681.97 | 0.952810E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 243614.34 | 0.00 | 0.26 | 26528.82 | 0.00 | 0.00 | 0.00 | 0.00 | 429.73 | 51.99 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.460792E+10 | 0.00 | 529.12 | 0.232771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17800.86 | 16962.87 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.394761E+10 | 0.00 | 128.25 | 0.189095E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35886.74 | 21-JAN-11:25 | 23953.51 | 21-JAN-11:25 | 0.00 | 0.00 | 0.00 |
February | 0.398019E+10 | 0.00 | 143.16 | 0.289050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30865.47 | 19-FEB-14:05 | 30865.47 | 19-FEB-14:05 | 0.00 | 0.00 | 0.00 |
March | 47762257.21 | 0.00 | 6.42 | 10693330.22 | 0.00 | 0.00 | 0.00 | 0.00 | 6000.37 | 25-MAR-11:40 | 2222.61 | 31-MAR-16:20 | 0.00 | 0.00 | 0.00 |
April | 0.256087E+11 | 0.00 | 502.17 | 0.153080E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 45894.97 | 30-APR-12:40 | 38646.79 | 13-APR-13:25 | 0.00 | 0.00 | 0.00 |
May | 0.208791E+11 | 0.00 | 494.77 | 0.718796E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36255.13 | 23-MAY-12:50 | 28189.03 | 11-MAY-15:03 | 0.00 | 0.00 | 0.00 |
June | 0.261936E+11 | 0.00 | 584.23 | 0.829697E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36616.08 | 13-JUN-13:05 | 21336.39 | 13-JUN-13:20 | 0.00 | 0.00 | 0.00 |
July | 0.342655E+11 | 0.00 | 663.01 | 0.121558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 41443.53 | 22-JUL-13:20 | 27832.78 | 22-JUL-13:30 | 0.00 | 0.00 | 0.00 |
August | 0.421380E+11 | 0.00 | 711.26 | 0.174399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 45363.19 | 20-AUG-12:50 | 32421.44 | 20-AUG-13:00 | 0.00 | 0.00 | 0.00 |
September | 0.428309E+11 | 0.00 | 649.53 | 0.210656E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 55493.77 | 27-SEP-12:40 | 48936.77 | 27-SEP-12:50 | 0.00 | 0.00 | 0.00 |
October | 0.166187E+11 | 0.00 | 335.99 | 0.827341E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50960.88 | 07-OCT-13:00 | 44985.52 | 07-OCT-13:05 | 0.00 | 0.00 | 0.00 |
November | 0.302281E+10 | 0.00 | 105.45 | 0.117926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32757.79 | 11-NOV-13:30 | 19114.48 | 11-NOV-13:30 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.219533E+12 | 0.00 | 4324.24 | 0.956989E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.428309E+11 | 0.00 | 711.26 | 0.210656E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 55493.77 | 48936.77 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.181507E+10 | 0.00 | 124.25 | 0.611418E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 65510.60 | 29-JAN-09:02 | 65510.60 | 29-JAN-09:02 | 0.00 | 0.00 | 0.00 |
February | 0.167638E+10 | 0.00 | 133.00 | 0.544600E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 61040.26 | 07-FEB-19:03 | 60997.92 | 21-FEB-19:03 | 0.00 | 0.00 | 0.00 |
March | 0.592048E+10 | 0.00 | 282.11 | 0.238330E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70529.77 | 18-MAR-08:62 | 66101.82 | 19-MAR-08:62 | 0.00 | 0.00 | 0.00 |
April | 0.158708E+11 | 0.00 | 448.07 | 0.892478E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73729.71 | 14-APR-15:02 | 73729.71 | 14-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.231723E+11 | 0.00 | 491.66 | 0.133436E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 76394.84 | 11-MAY-19:31 | 76394.84 | 11-MAY-19:31 | 0.00 | 0.00 | 0.00 |
June | 0.347151E+11 | 0.00 | 478.41 | 0.211936E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 84153.70 | 26-JUN-21:01 | 76910.69 | 08-JUN-19:11 | 0.00 | 0.00 | 0.00 |
July | 0.357201E+11 | 0.00 | 447.76 | 0.221109E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 81578.74 | 17-JUL-21:51 | 74061.86 | 26-JUL-19:51 | 0.00 | 0.00 | 0.00 |
August | 0.295380E+11 | 0.00 | 405.71 | 0.170171E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 81706.17 | 16-AUG-21:51 | 72426.97 | 02-AUG-21:11 | 0.00 | 0.00 | 0.00 |
September | 0.223708E+11 | 0.00 | 436.76 | 0.115628E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 79653.13 | 10-SEP-20:31 | 71070.52 | 02-SEP-08:61 | 0.00 | 0.00 | 0.00 |
October | 0.959484E+10 | 0.00 | 385.67 | 0.384256E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74082.66 | 07-OCT-18:01 | 74082.66 | 07-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.336541E+10 | 0.00 | 188.25 | 0.112300E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70649.98 | 24-NOV-19:03 | 67071.00 | 23-NOV-09:02 | 0.00 | 0.00 | 0.00 |
December | 0.703315E+09 | 0.00 | 78.89 | 0.208613E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 61638.38 | 02-DEC-09:02 | 61638.38 | 02-DEC-09:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.184463E+12 | 0.00 | 3900.56 | 0.102866E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.703315E+09 | 0.00 | 78.89 | 0.208613E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 61040.26 | 60997.92 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.357201E+11 | 0.00 | 491.66 | 0.221109E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 84153.70 | 76910.69 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.104612E+09 | 0.00 | 23.14 | 43357193.32 | 0.00 | 0.00 | 0.00 | 0.00 | 12362.60 | 19-JAN-16:01 | 12362.60 | 19-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.178615E+09 | 0.00 | 37.54 | 78354270.97 | 0.00 | 0.00 | 0.00 | 0.00 | 12991.43 | 27-FEB-16:01 | 12991.43 | 27-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.108401E+09 | 0.00 | 34.90 | 38429825.12 | 0.00 | 0.00 | 0.00 | 0.00 | 12768.87 | 25-MAR-15:01 | 12768.87 | 25-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.338206E+10 | 0.00 | 455.74 | 0.186974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13392.28 | 23-APR-08:62 | 13392.28 | 23-APR-08:62 | 0.00 | 0.00 | 0.00 |
May | 0.368391E+10 | 0.00 | 504.26 | 0.190641E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15311.06 | 11-MAY-18:01 | 15311.06 | 11-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.515798E+10 | 0.00 | 629.96 | 0.260888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15313.07 | 04-JUN-08:61 | 14024.02 | 10-JUN-08:61 | 0.00 | 0.00 | 0.00 |
July | 0.645088E+10 | 0.00 | 675.13 | 0.334470E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15260.65 | 08-JUL-15:02 | 14082.49 | 26-JUL-08:61 | 0.00 | 0.00 | 0.00 |
August | 0.677143E+10 | 0.00 | 690.93 | 0.349908E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15731.65 | 08-AUG-15:01 | 14068.38 | 06-AUG-08:61 | 0.00 | 0.00 | 0.00 |
September | 0.527751E+10 | 0.00 | 616.17 | 0.272717E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15785.24 | 16-SEP-15:02 | 14038.73 | 09-SEP-08:62 | 0.00 | 0.00 | 0.00 |
October | 0.120399E+10 | 0.00 | 199.57 | 0.622291E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15156.71 | 06-OCT-18:01 | 15156.71 | 06-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 97128641.75 | 0.00 | 23.80 | 36903024.98 | 0.00 | 0.00 | 0.00 | 0.00 | 12791.77 | 13-NOV-09:02 | 12791.77 | 13-NOV-09:02 | 0.00 | 0.00 | 0.00 |
December | 25067528.06 | 0.00 | 11.30 | 5134149.76 | 0.00 | 0.00 | 0.00 | 0.00 | 1596.37 | 26-DEC-09:04 | 547.48 | 26-DEC-09:04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.324416E+11 | 0.00 | 3902.45 | 0.167805E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 25067528.06 | 0.00 | 11.30 | 5134149.76 | 0.00 | 0.00 | 0.00 | 0.00 | 1596.37 | 547.48 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.677143E+10 | 0.00 | 690.93 | 0.349908E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15785.24 | 15311.06 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 7049034.75 | 0.00 | 6.24 | 1055450.49 | 0.00 | 0.00 | 0.00 | 0.00 | 1498.71 | 21-JAN-09:02 | 467.65 | 21-JAN-09:02 | 0.00 | 0.00 | 0.00 |
February | 34739019.46 | 0.00 | 15.86 | 10617830.30 | 0.00 | 0.00 | 0.00 | 0.00 | 11087.66 | 23-FEB-09:02 | 11087.66 | 23-FEB-09:02 | 0.00 | 0.00 | 0.00 |
March | 33719428.96 | 0.00 | 16.98 | 11296331.06 | 0.00 | 0.00 | 0.00 | 0.00 | 9728.15 | 25-MAR-15:01 | 8547.89 | 25-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.202740E+10 | 0.00 | 342.32 | 0.111087E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13262.88 | 28-APR-08:51 | 13262.88 | 28-APR-08:51 | 0.00 | 0.00 | 0.00 |
May | 0.263414E+10 | 0.00 | 421.44 | 0.136711E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13866.95 | 11-MAY-19:31 | 13866.95 | 11-MAY-19:31 | 0.00 | 0.00 | 0.00 |
June | 0.403037E+10 | 0.00 | 548.23 | 0.203983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15697.98 | 13-JUN-08:32 | 15116.41 | 13-JUN-08:32 | 0.00 | 0.00 | 0.00 |
July | 0.456528E+10 | 0.00 | 542.63 | 0.233571E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15864.06 | 23-JUL-08:32 | 15864.06 | 23-JUL-08:32 | 0.00 | 0.00 | 0.00 |
August | 0.414508E+10 | 0.00 | 527.71 | 0.201063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14370.36 | 16-AUG-21:51 | 14325.70 | 17-AUG-08:51 | 0.00 | 0.00 | 0.00 |
September | 0.281112E+10 | 0.00 | 474.73 | 0.132741E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14348.68 | 16-SEP-15:02 | 14271.21 | 11-SEP-08:51 | 0.00 | 0.00 | 0.00 |
October | 0.437467E+09 | 0.00 | 94.51 | 0.213068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13256.91 | 06-OCT-18:01 | 13256.91 | 06-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 14213564.12 | 0.00 | 7.98 | 4248721.46 | 0.00 | 0.00 | 0.00 | 0.00 | 9289.70 | 11-NOV-09:02 | 8284.32 | 11-NOV-09:02 | 0.00 | 0.00 | 0.00 |
December | 969215.70 | 0.00 | 0.58 | 180396.52 | 0.00 | 0.00 | 0.00 | 0.00 | 1061.52 | 20-DEC-09:06 | 244.87 | 26-DEC-09:06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.207416E+11 | 0.00 | 2999.19 | 0.104320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 969215.70 | 0.00 | 0.58 | 180396.52 | 0.00 | 0.00 | 0.00 | 0.00 | 1061.52 | 244.87 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.456528E+10 | 0.00 | 548.23 | 0.233571E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15864.06 | 15864.06 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 11713349.36 | 0.00 | 12.26 | 5410342.78 | 0.00 | 0.00 | 0.00 | 0.00 | 3808.85 | 19-JAN-16:01 | 3808.85 | 19-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 69595899.22 | 0.00 | 42.30 | 33369110.32 | 0.00 | 0.00 | 0.00 | 0.00 | 3739.48 | 05-FEB-16:01 | 3739.48 | 05-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 31795384.41 | 0.00 | 26.90 | 14739470.75 | 0.00 | 0.00 | 0.00 | 0.00 | 3722.57 | 25-MAR-15:01 | 3722.57 | 25-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.783035E+09 | 0.00 | 342.44 | 0.483139E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4016.75 | 29-APR-08:61 | 3954.98 | 29-APR-08:61 | 0.00 | 0.00 | 0.00 |
May | 0.930446E+09 | 0.00 | 391.47 | 0.555617E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4408.60 | 11-MAY-18:01 | 4408.60 | 11-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.138935E+10 | 0.00 | 554.77 | 0.788248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4606.83 | 04-JUN-08:61 | 4027.87 | 26-JUN-08:61 | 0.00 | 0.00 | 0.00 |
July | 0.174835E+10 | 0.00 | 609.56 | 0.998428E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4531.50 | 08-JUL-08:61 | 4051.82 | 17-JUL-18:01 | 0.00 | 0.00 | 0.00 |
August | 0.160326E+10 | 0.00 | 648.91 | 0.864533E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4591.36 | 08-AUG-15:01 | 4032.71 | 15-AUG-18:01 | 0.00 | 0.00 | 0.00 |
September | 0.112056E+10 | 0.00 | 496.52 | 0.605945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4616.08 | 16-SEP-15:02 | 4051.23 | 10-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.252248E+09 | 0.00 | 140.35 | 0.140343E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4136.85 | 20-OCT-15:02 | 4017.61 | 10-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 15194359.33 | 0.00 | 16.99 | 6235827.28 | 0.00 | 0.00 | 0.00 | 0.00 | 3940.81 | 10-NOV-16:01 | 3940.81 | 10-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 56891.15 | 0.00 | 0.11 | 8867.47 | 0.00 | 0.00 | 0.00 | 0.00 | 238.75 | 18-DEC-16:03 | 49.02 | 18-DEC-16:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.795560E+10 | 0.00 | 3282.59 | 0.449602E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 56891.15 | 0.00 | 0.11 | 8867.47 | 0.00 | 0.00 | 0.00 | 0.00 | 238.75 | 49.02 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.174835E+10 | 0.00 | 648.91 | 0.998428E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4616.08 | 4408.60 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 1105633.47 | 0.00 | 1.07 | 561051.42 | 0.00 | 0.00 | 0.00 | 0.00 | 3202.31 | 19-JAN-16:01 | 3202.31 | 19-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 15042191.12 | 0.00 | 15.77 | 6315946.95 | 0.00 | 0.00 | 0.00 | 0.00 | 3479.08 | 27-FEB-16:01 | 3479.08 | 27-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 15021111.02 | 0.00 | 16.20 | 6184510.37 | 0.00 | 0.00 | 0.00 | 0.00 | 3190.41 | 23-MAR-18:01 | 3190.41 | 23-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.446686E+09 | 0.00 | 228.58 | 0.270382E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3706.14 | 28-APR-19:01 | 3706.14 | 28-APR-19:01 | 0.00 | 0.00 | 0.00 |
May | 0.643740E+09 | 0.00 | 309.00 | 0.364547E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4320.77 | 22-MAY-21:31 | 4263.15 | 23-MAY-19:42 | 0.00 | 0.00 | 0.00 |
June | 0.108078E+10 | 0.00 | 483.12 | 0.590705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4550.24 | 26-JUN-21:01 | 4327.57 | 22-JUN-18:42 | 0.00 | 0.00 | 0.00 |
July | 0.120839E+10 | 0.00 | 475.04 | 0.637018E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4676.12 | 25-JUL-19:42 | 4482.40 | 28-JUL-17:52 | 0.00 | 0.00 | 0.00 |
August | 0.892487E+09 | 0.00 | 472.41 | 0.408173E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4430.89 | 17-AUG-21:11 | 4066.28 | 31-AUG-19:01 | 0.00 | 0.00 | 0.00 |
September | 0.480145E+09 | 0.00 | 322.94 | 0.208054E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4320.93 | 12-SEP-20:11 | 4048.89 | 14-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 81962808.60 | 0.00 | 55.02 | 43985052.96 | 0.00 | 0.00 | 0.00 | 0.00 | 3971.78 | 10-OCT-15:01 | 3913.86 | 06-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 1680082.60 | 0.00 | 2.82 | 800439.55 | 0.00 | 0.00 | 0.00 | 0.00 | 3339.88 | 10-NOV-16:01 | 3339.88 | 10-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.486704E+10 | 0.00 | 2381.97 | 0.253673E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.120839E+10 | 0.00 | 483.12 | 0.637018E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4676.12 | 4482.40 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.144429E+10 | 0.00 | 158.80 | 0.738488E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22080.44 | 23-JAN-16:01 | 22080.44 | 23-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.176265E+10 | 0.00 | 182.94 | 0.881979E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21922.98 | 07-FEB-16:02 | 21084.63 | 07-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.614545E+09 | 0.00 | 124.58 | 0.224230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22060.67 | 25-MAR-15:01 | 22060.67 | 25-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.596451E+10 | 0.00 | 488.88 | 0.338419E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21819.03 | 29-APR-08:61 | 21819.03 | 29-APR-08:61 | 0.00 | 0.00 | 0.00 |
May | 0.513390E+10 | 0.00 | 492.64 | 0.249404E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24548.77 | 11-MAY-18:01 | 24548.77 | 11-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.672918E+10 | 0.00 | 606.62 | 0.305790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24732.13 | 26-JUN-18:02 | 23450.17 | 08-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.859779E+10 | 0.00 | 641.30 | 0.411271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24865.11 | 08-JUL-15:02 | 22550.58 | 04-JUL-15:01 | 0.00 | 0.00 | 0.00 |
August | 0.990920E+10 | 0.00 | 673.13 | 0.514283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25480.11 | 08-AUG-15:01 | 22038.84 | 30-AUG-18:01 | 0.00 | 0.00 | 0.00 |
September | 0.967862E+10 | 0.00 | 623.64 | 0.568334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25638.54 | 16-SEP-15:02 | 22099.70 | 27-SEP-08:62 | 0.00 | 0.00 | 0.00 |
October | 0.381664E+10 | 0.00 | 345.15 | 0.213403E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24552.76 | 06-OCT-18:01 | 24552.76 | 06-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.116186E+10 | 0.00 | 151.49 | 0.497231E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20942.85 | 10-NOV-16:01 | 20942.85 | 10-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.439658E+09 | 0.00 | 58.25 | 0.186951E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21101.94 | 21-DEC-16:02 | 21101.94 | 21-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.552529E+11 | 0.00 | 4547.41 | 0.285379E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.439658E+09 | 0.00 | 58.25 | 0.186951E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20942.85 | 20942.85 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.990920E+10 | 0.00 | 673.13 | 0.568334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25638.54 | 24552.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 526.65 | 341.04 | 185.61 | 525.59 | 509.43 | 0.00 | 0.00 | 0.00 |
February | 639.06 | 389.50 | 249.57 | 654.63 | 492.25 | 0.00 | 0.00 | 0.00 |
March | 394.43 | 114.02 | 280.42 | 329.91 | 410.27 | 0.00 | 0.00 | 0.00 |
April | 808.56 | 358.28 | 450.29 | 933.13 | 340.48 | 0.00 | 0.00 | 0.00 |
May | 677.84 | 219.58 | 458.26 | 732.11 | 289.81 | 0.00 | 0.00 | 0.00 |
June | 625.72 | 151.33 | 474.39 | 712.59 | 212.84 | 0.00 | 0.00 | 0.00 |
July | 674.45 | 208.66 | 465.80 | 821.65 | 195.78 | 0.00 | 0.00 | 0.00 |
August | 792.15 | 354.92 | 437.23 | 1006.80 | 215.95 | 0.00 | 0.00 | 0.00 |
September | 949.31 | 560.29 | 389.02 | 1185.15 | 283.97 | 0.00 | 0.00 | 0.00 |
October | 633.43 | 365.19 | 268.24 | 704.76 | 378.27 | 0.00 | 0.00 | 0.00 |
November | 457.43 | 278.17 | 179.26 | 460.38 | 463.24 | 0.00 | 0.00 | 0.00 |
December | 362.99 | 232.76 | 130.23 | 351.60 | 574.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 627.52 | 296.63 | 330.89 | 700.58 | 363.28 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 362.99 | 114.02 | 130.23 | 329.91 | 195.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 949.31 | 560.29 | 474.39 | 1185.15 | 574.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1483.01 | 960.34 | 522.67 | 1462.75 | 1478.82 | 0.00 | 0.00 | 0.00 |
February | 1799.56 | 1096.79 | 702.77 | 1823.01 | 1433.90 | 0.00 | 0.00 | 0.00 |
March | 1110.70 | 321.07 | 789.63 | 910.42 | 1196.85 | 0.00 | 0.00 | 0.00 |
April | 2276.87 | 1008.88 | 1267.98 | 2596.17 | 1016.82 | 0.00 | 0.00 | 0.00 |
May | 1908.76 | 618.33 | 1290.43 | 2028.25 | 872.74 | 0.00 | 0.00 | 0.00 |
June | 1761.98 | 426.13 | 1335.85 | 1968.42 | 655.26 | 0.00 | 0.00 | 0.00 |
July | 1899.22 | 587.57 | 1311.65 | 2275.56 | 604.51 | 0.00 | 0.00 | 0.00 |
August | 2230.66 | 999.44 | 1231.21 | 2799.27 | 670.65 | 0.00 | 0.00 | 0.00 |
September | 2673.19 | 1577.74 | 1095.45 | 3303.77 | 867.18 | 0.00 | 0.00 | 0.00 |
October | 1783.71 | 1028.36 | 755.35 | 1962.18 | 1127.88 | 0.00 | 0.00 | 0.00 |
November | 1288.09 | 783.31 | 504.77 | 1280.41 | 1358.51 | 0.00 | 0.00 | 0.00 |
December | 1022.16 | 655.44 | 366.72 | 978.76 | 1661.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1767.06 | 835.28 | 931.77 | 1946.41 | 1076.91 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1022.16 | 321.07 | 366.72 | 910.42 | 604.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2673.19 | 1577.74 | 1335.85 | 3303.77 | 1661.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1926.52 | 1247.54 | 678.98 | 1919.41 | 2047.87 | 0.00 | 0.00 | 0.00 |
February | 2337.73 | 1424.80 | 912.94 | 2395.96 | 1977.32 | 0.00 | 0.00 | 0.00 |
March | 1442.86 | 417.08 | 1025.78 | 1182.49 | 1675.90 | 0.00 | 0.00 | 0.00 |
April | 2957.78 | 1310.59 | 1647.18 | 3427.46 | 1398.59 | 0.00 | 0.00 | 0.00 |
May | 2479.59 | 803.25 | 1676.34 | 2666.08 | 1215.43 | 0.00 | 0.00 | 0.00 |
June | 2288.91 | 553.57 | 1735.34 | 2579.53 | 918.46 | 0.00 | 0.00 | 0.00 |
July | 2467.19 | 763.28 | 1703.91 | 2991.37 | 843.12 | 0.00 | 0.00 | 0.00 |
August | 2897.75 | 1298.33 | 1599.42 | 3694.76 | 921.87 | 0.00 | 0.00 | 0.00 |
September | 3472.62 | 2049.57 | 1423.05 | 4361.90 | 1183.09 | 0.00 | 0.00 | 0.00 |
October | 2317.14 | 1335.90 | 981.24 | 2581.57 | 1570.23 | 0.00 | 0.00 | 0.00 |
November | 1673.30 | 1017.57 | 655.73 | 1677.25 | 1893.95 | 0.00 | 0.00 | 0.00 |
December | 1327.84 | 851.45 | 476.39 | 1279.53 | 2304.51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2295.51 | 1085.08 | 1210.43 | 2559.57 | 1493.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1327.84 | 417.08 | 476.39 | 1182.49 | 843.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3472.62 | 2049.57 | 1735.34 | 4361.90 | 2304.51 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 104.13 | 67.43 | 36.70 | 105.65 | 100.52 | 0.00 | 0.00 | 0.00 |
February | 126.35 | 77.01 | 49.34 | 130.81 | 98.02 | 0.00 | 0.00 | 0.00 |
March | 77.99 | 22.54 | 55.44 | 65.67 | 81.73 | 0.00 | 0.00 | 0.00 |
April | 159.87 | 70.84 | 89.03 | 185.03 | 68.38 | 0.00 | 0.00 | 0.00 |
May | 134.02 | 43.42 | 90.61 | 143.12 | 59.29 | 0.00 | 0.00 | 0.00 |
June | 123.72 | 29.92 | 93.80 | 138.52 | 43.22 | 0.00 | 0.00 | 0.00 |
July | 133.35 | 41.26 | 92.10 | 161.31 | 38.92 | 0.00 | 0.00 | 0.00 |
August | 156.62 | 70.17 | 86.45 | 199.84 | 41.93 | 0.00 | 0.00 | 0.00 |
September | 187.69 | 110.78 | 76.92 | 236.37 | 55.48 | 0.00 | 0.00 | 0.00 |
October | 125.24 | 72.20 | 53.04 | 140.89 | 74.79 | 0.00 | 0.00 | 0.00 |
November | 90.44 | 55.00 | 35.44 | 92.14 | 91.42 | 0.00 | 0.00 | 0.00 |
December | 71.77 | 46.02 | 25.75 | 70.64 | 113.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 124.07 | 58.65 | 65.42 | 138.97 | 72.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 71.77 | 22.54 | 25.75 | 65.67 | 38.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 187.69 | 110.78 | 93.80 | 236.37 | 113.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.26 | 22.37 | 45.89 | 40.69 | 202.82 | 0.00 | 0.00 | 0.00 |
February | 120.75 | 51.40 | 69.35 | 94.44 | 192.43 | 0.00 | 0.00 | 0.00 |
March | 108.62 | 20.89 | 87.74 | 69.04 | 153.14 | 0.00 | 0.00 | 0.00 |
April | 255.82 | 101.43 | 154.39 | 268.08 | 124.23 | 0.00 | 0.00 | 0.00 |
May | 300.20 | 122.08 | 178.12 | 313.04 | 105.07 | 0.00 | 0.00 | 0.00 |
June | 324.11 | 133.43 | 190.68 | 367.81 | 77.29 | 0.00 | 0.00 | 0.00 |
July | 329.88 | 145.31 | 184.57 | 391.65 | 69.88 | 0.00 | 0.00 | 0.00 |
August | 277.60 | 120.26 | 157.34 | 331.59 | 76.46 | 0.00 | 0.00 | 0.00 |
September | 224.32 | 101.40 | 122.93 | 254.17 | 103.53 | 0.00 | 0.00 | 0.00 |
October | 119.58 | 43.43 | 76.15 | 105.89 | 143.13 | 0.00 | 0.00 | 0.00 |
November | 64.51 | 19.04 | 45.48 | 39.15 | 180.02 | 0.00 | 0.00 | 0.00 |
December | 35.97 | 7.31 | 28.66 | 12.38 | 226.71 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 185.99 | 74.05 | 111.94 | 191.00 | 137.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 35.97 | 7.31 | 28.66 | 12.38 | 69.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 329.88 | 145.31 | 190.68 | 391.65 | 226.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 18.24 | 0.00 | 18.24 | 1.74 | 111.77 | 0.00 | 0.00 | 0.00 |
February | 28.49 | 0.00 | 28.49 | 4.92 | 105.37 | 0.00 | 0.00 | 0.00 |
March | 39.43 | 0.00 | 39.43 | 15.05 | 84.54 | 0.00 | 0.00 | 0.00 |
April | 64.43 | 0.43 | 64.00 | 43.76 | 66.75 | 0.00 | 0.00 | 0.00 |
May | 80.55 | 4.11 | 76.44 | 54.55 | 53.52 | 0.00 | 0.00 | 0.00 |
June | 88.74 | 5.55 | 83.19 | 77.08 | 40.07 | 0.00 | 0.00 | 0.00 |
July | 84.37 | 4.96 | 79.41 | 77.26 | 36.97 | 0.00 | 0.00 | 0.00 |
August | 66.43 | 1.24 | 65.19 | 59.89 | 41.57 | 0.00 | 0.00 | 0.00 |
September | 50.39 | 0.03 | 50.36 | 39.87 | 56.91 | 0.00 | 0.00 | 0.00 |
October | 32.26 | 0.00 | 32.26 | 15.24 | 77.26 | 0.00 | 0.00 | 0.00 |
November | 19.38 | 0.00 | 19.38 | 2.76 | 97.24 | 0.00 | 0.00 | 0.00 |
December | 13.20 | 0.00 | 13.20 | 0.15 | 121.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 48.92 | 1.37 | 47.55 | 32.83 | 74.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.20 | 0.00 | 13.20 | 0.15 | 36.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.74 | 5.55 | 83.19 | 77.26 | 121.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.26 | 22.37 | 45.89 | 43.30 | 200.31 | 0.00 | 0.00 | 0.00 |
February | 120.75 | 51.40 | 69.35 | 98.00 | 189.88 | 0.00 | 0.00 | 0.00 |
March | 108.62 | 20.89 | 87.74 | 70.87 | 152.09 | 0.00 | 0.00 | 0.00 |
April | 255.82 | 101.43 | 154.39 | 271.40 | 123.33 | 0.00 | 0.00 | 0.00 |
May | 300.20 | 122.08 | 178.12 | 313.76 | 105.15 | 0.00 | 0.00 | 0.00 |
June | 324.11 | 133.43 | 190.68 | 365.69 | 78.45 | 0.00 | 0.00 | 0.00 |
July | 329.88 | 145.31 | 184.57 | 386.44 | 72.39 | 0.00 | 0.00 | 0.00 |
August | 277.60 | 120.26 | 157.34 | 328.83 | 79.36 | 0.00 | 0.00 | 0.00 |
September | 224.32 | 101.40 | 122.93 | 256.12 | 103.59 | 0.00 | 0.00 | 0.00 |
October | 119.58 | 43.43 | 76.15 | 109.32 | 141.26 | 0.00 | 0.00 | 0.00 |
November | 64.51 | 19.04 | 45.48 | 41.55 | 177.79 | 0.00 | 0.00 | 0.00 |
December | 35.97 | 7.31 | 28.66 | 13.52 | 224.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 185.99 | 74.05 | 111.94 | 191.87 | 137.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 35.97 | 7.31 | 28.66 | 13.52 | 72.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 329.88 | 145.31 | 190.68 | 386.44 | 224.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.29 | 53.93 | 29.35 | 76.90 | 104.44 | 0.00 | 0.00 | 0.00 |
February | 101.06 | 61.60 | 39.47 | 96.36 | 102.13 | 0.00 | 0.00 | 0.00 |
March | 62.38 | 18.03 | 44.35 | 44.68 | 84.67 | 0.00 | 0.00 | 0.00 |
April | 127.87 | 56.66 | 71.21 | 136.06 | 75.45 | 0.00 | 0.00 | 0.00 |
May | 107.20 | 34.73 | 72.47 | 102.21 | 67.81 | 0.00 | 0.00 | 0.00 |
June | 98.95 | 23.93 | 75.02 | 97.76 | 52.34 | 0.00 | 0.00 | 0.00 |
July | 106.66 | 33.00 | 73.66 | 115.94 | 48.34 | 0.00 | 0.00 | 0.00 |
August | 125.27 | 56.13 | 69.15 | 147.47 | 52.16 | 0.00 | 0.00 | 0.00 |
September | 150.13 | 88.61 | 61.52 | 177.03 | 65.22 | 0.00 | 0.00 | 0.00 |
October | 100.17 | 57.75 | 42.42 | 103.33 | 85.43 | 0.00 | 0.00 | 0.00 |
November | 72.34 | 43.99 | 28.35 | 66.87 | 100.04 | 0.00 | 0.00 | 0.00 |
December | 57.40 | 36.81 | 20.60 | 54.28 | 100.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 99.24 | 46.91 | 52.33 | 101.42 | 78.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 57.40 | 18.03 | 20.60 | 44.68 | 48.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 150.13 | 88.61 | 75.02 | 177.03 | 104.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.60 | 0.00 | 14.60 | 1.04 | 93.98 | 0.00 | 0.00 | 0.00 |
February | 22.79 | 0.00 | 22.79 | 3.26 | 87.52 | 0.00 | 0.00 | 0.00 |
March | 31.55 | 0.00 | 31.55 | 11.00 | 70.57 | 0.00 | 0.00 | 0.00 |
April | 51.55 | 0.34 | 51.21 | 36.57 | 53.36 | 0.00 | 0.00 | 0.00 |
May | 64.45 | 3.29 | 61.16 | 46.18 | 42.57 | 0.00 | 0.00 | 0.00 |
June | 71.00 | 4.44 | 66.56 | 65.65 | 31.12 | 0.00 | 0.00 | 0.00 |
July | 67.51 | 3.97 | 63.54 | 66.84 | 28.16 | 0.00 | 0.00 | 0.00 |
August | 53.15 | 0.99 | 52.16 | 52.07 | 31.42 | 0.00 | 0.00 | 0.00 |
September | 40.31 | 0.02 | 40.29 | 34.23 | 44.27 | 0.00 | 0.00 | 0.00 |
October | 25.81 | 0.00 | 25.81 | 12.02 | 63.90 | 0.00 | 0.00 | 0.00 |
November | 15.51 | 0.00 | 15.51 | 1.74 | 82.10 | 0.00 | 0.00 | 0.00 |
December | 10.56 | 0.00 | 10.56 | 0.03 | 103.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 39.14 | 1.10 | 38.04 | 27.68 | 60.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 10.56 | 0.00 | 10.56 | 0.03 | 28.16 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.00 | 4.44 | 66.56 | 66.84 | 103.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.24 | 27.58 | 41.66 | 39.57 | 199.90 | 0.00 | 0.00 | 0.00 |
February | 104.56 | 38.96 | 65.60 | 67.63 | 188.50 | 0.00 | 0.00 | 0.00 |
March | 108.63 | 21.43 | 87.21 | 67.81 | 151.63 | 0.00 | 0.00 | 0.00 |
April | 291.02 | 136.45 | 154.57 | 309.38 | 118.92 | 0.00 | 0.00 | 0.00 |
May | 306.41 | 133.65 | 172.76 | 317.71 | 101.77 | 0.00 | 0.00 | 0.00 |
June | 303.21 | 121.13 | 182.08 | 337.89 | 74.89 | 0.00 | 0.00 | 0.00 |
July | 309.46 | 131.45 | 178.01 | 361.12 | 67.24 | 0.00 | 0.00 | 0.00 |
August | 293.97 | 140.73 | 153.24 | 351.33 | 72.87 | 0.00 | 0.00 | 0.00 |
September | 263.92 | 140.24 | 123.69 | 302.92 | 99.36 | 0.00 | 0.00 | 0.00 |
October | 128.37 | 53.68 | 74.69 | 115.12 | 140.45 | 0.00 | 0.00 | 0.00 |
November | 66.44 | 22.61 | 43.83 | 37.72 | 176.01 | 0.00 | 0.00 | 0.00 |
December | 49.42 | 18.49 | 30.92 | 24.22 | 220.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 191.50 | 82.30 | 109.19 | 194.83 | 134.05 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 49.42 | 18.49 | 30.92 | 24.22 | 67.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 309.46 | 140.73 | 182.08 | 361.12 | 220.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 104.13 | 67.43 | 36.70 | 105.45 | 100.37 | 0.00 | 0.00 | 0.00 |
February | 126.35 | 77.01 | 49.34 | 130.70 | 97.62 | 0.00 | 0.00 | 0.00 |
March | 77.99 | 22.54 | 55.44 | 65.27 | 81.55 | 0.00 | 0.00 | 0.00 |
April | 159.87 | 70.84 | 89.03 | 183.43 | 68.20 | 0.00 | 0.00 | 0.00 |
May | 134.02 | 43.42 | 90.61 | 141.93 | 58.82 | 0.00 | 0.00 | 0.00 |
June | 123.72 | 29.92 | 93.80 | 138.01 | 42.49 | 0.00 | 0.00 | 0.00 |
July | 133.35 | 41.26 | 92.10 | 160.73 | 38.25 | 0.00 | 0.00 | 0.00 |
August | 156.62 | 70.17 | 86.45 | 198.99 | 41.52 | 0.00 | 0.00 | 0.00 |
September | 187.69 | 110.78 | 76.92 | 235.10 | 55.32 | 0.00 | 0.00 | 0.00 |
October | 125.24 | 72.20 | 53.04 | 140.26 | 74.62 | 0.00 | 0.00 | 0.00 |
November | 90.44 | 55.00 | 35.44 | 91.95 | 91.27 | 0.00 | 0.00 | 0.00 |
December | 71.77 | 46.02 | 25.75 | 70.34 | 114.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 124.07 | 58.65 | 65.42 | 138.32 | 71.88 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 71.77 | 22.54 | 25.75 | 65.27 | 38.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 187.69 | 110.78 | 93.80 | 235.10 | 114.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 18.24 | 0.00 | 18.24 | 1.58 | 111.55 | 0.00 | 0.00 | 0.00 |
February | 28.49 | 0.00 | 28.49 | 4.62 | 104.71 | 0.00 | 0.00 | 0.00 |
March | 39.43 | 0.00 | 39.43 | 14.65 | 84.38 | 0.00 | 0.00 | 0.00 |
April | 64.43 | 0.43 | 64.00 | 41.96 | 66.68 | 0.00 | 0.00 | 0.00 |
May | 80.55 | 4.11 | 76.44 | 53.56 | 53.03 | 0.00 | 0.00 | 0.00 |
June | 88.74 | 5.55 | 83.19 | 77.18 | 39.20 | 0.00 | 0.00 | 0.00 |
July | 84.37 | 4.96 | 79.41 | 78.02 | 35.70 | 0.00 | 0.00 | 0.00 |
August | 66.43 | 1.24 | 65.19 | 59.59 | 40.35 | 0.00 | 0.00 | 0.00 |
September | 50.39 | 0.03 | 50.36 | 38.44 | 56.42 | 0.00 | 0.00 | 0.00 |
October | 32.26 | 0.00 | 32.26 | 14.51 | 77.11 | 0.00 | 0.00 | 0.00 |
November | 19.38 | 0.00 | 19.38 | 2.59 | 96.98 | 0.00 | 0.00 | 0.00 |
December | 13.20 | 0.00 | 13.20 | 0.11 | 121.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 48.92 | 1.37 | 47.55 | 32.38 | 73.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.20 | 0.00 | 13.20 | 0.11 | 35.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.74 | 5.55 | 83.19 | 78.02 | 121.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.24 | 27.58 | 41.66 | 41.19 | 196.21 | 0.00 | 0.00 | 0.00 |
February | 104.56 | 38.96 | 65.60 | 70.25 | 184.77 | 0.00 | 0.00 | 0.00 |
March | 108.63 | 21.43 | 87.21 | 69.46 | 150.44 | 0.00 | 0.00 | 0.00 |
April | 291.02 | 136.45 | 154.57 | 312.27 | 117.88 | 0.00 | 0.00 | 0.00 |
May | 306.41 | 133.65 | 172.76 | 318.98 | 101.59 | 0.00 | 0.00 | 0.00 |
June | 303.21 | 121.13 | 182.08 | 337.23 | 75.66 | 0.00 | 0.00 | 0.00 |
July | 309.46 | 131.45 | 178.01 | 359.46 | 68.99 | 0.00 | 0.00 | 0.00 |
August | 293.97 | 140.73 | 153.24 | 350.75 | 74.90 | 0.00 | 0.00 | 0.00 |
September | 263.92 | 140.24 | 123.69 | 305.11 | 98.94 | 0.00 | 0.00 | 0.00 |
October | 128.37 | 53.68 | 74.69 | 118.18 | 138.39 | 0.00 | 0.00 | 0.00 |
November | 66.44 | 22.61 | 43.83 | 39.48 | 172.96 | 0.00 | 0.00 | 0.00 |
December | 49.42 | 18.49 | 30.92 | 24.98 | 217.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 191.50 | 82.30 | 109.19 | 196.06 | 132.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 49.42 | 18.49 | 30.92 | 24.98 | 68.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 309.46 | 140.73 | 182.08 | 359.46 | 217.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.11 | 0.00 | 23.11 | 1.51 | 151.79 | 0.00 | 0.00 | 0.00 |
February | 36.08 | 0.00 | 36.08 | 4.75 | 140.94 | 0.00 | 0.00 | 0.00 |
March | 49.93 | 0.00 | 49.93 | 17.77 | 112.33 | 0.00 | 0.00 | 0.00 |
April | 81.59 | 0.54 | 81.05 | 56.96 | 88.11 | 0.00 | 0.00 | 0.00 |
May | 102.01 | 5.20 | 96.81 | 71.76 | 71.47 | 0.00 | 0.00 | 0.00 |
June | 112.38 | 7.03 | 105.35 | 101.98 | 54.00 | 0.00 | 0.00 | 0.00 |
July | 106.85 | 6.28 | 100.57 | 103.41 | 49.43 | 0.00 | 0.00 | 0.00 |
August | 84.13 | 1.57 | 82.56 | 79.55 | 55.74 | 0.00 | 0.00 | 0.00 |
September | 63.81 | 0.04 | 63.77 | 51.27 | 77.40 | 0.00 | 0.00 | 0.00 |
October | 40.86 | 0.00 | 40.86 | 18.17 | 104.31 | 0.00 | 0.00 | 0.00 |
November | 24.55 | 0.00 | 24.55 | 2.62 | 131.77 | 0.00 | 0.00 | 0.00 |
December | 16.72 | 0.00 | 16.72 | 0.04 | 166.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 61.95 | 1.73 | 60.22 | 42.67 | 100.16 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 16.72 | 0.00 | 16.72 | 0.04 | 49.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 112.38 | 7.03 | 105.35 | 103.41 | 166.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 8.52 | 0.00 | 8.52 | 0.56 | 55.95 | 0.00 | 0.00 | 0.00 |
February | 13.30 | 0.00 | 13.30 | 1.75 | 51.95 | 0.00 | 0.00 | 0.00 |
March | 18.41 | 0.00 | 18.41 | 6.55 | 41.41 | 0.00 | 0.00 | 0.00 |
April | 30.08 | 0.20 | 29.88 | 21.00 | 32.48 | 0.00 | 0.00 | 0.00 |
May | 37.61 | 1.92 | 35.69 | 26.45 | 26.35 | 0.00 | 0.00 | 0.00 |
June | 41.43 | 2.59 | 38.84 | 37.59 | 19.91 | 0.00 | 0.00 | 0.00 |
July | 39.39 | 2.32 | 37.07 | 38.12 | 18.22 | 0.00 | 0.00 | 0.00 |
August | 31.01 | 0.58 | 30.43 | 29.33 | 20.55 | 0.00 | 0.00 | 0.00 |
September | 23.52 | 0.01 | 23.51 | 18.90 | 28.53 | 0.00 | 0.00 | 0.00 |
October | 15.06 | 0.00 | 15.06 | 6.70 | 38.45 | 0.00 | 0.00 | 0.00 |
November | 9.05 | 0.00 | 9.05 | 0.97 | 48.58 | 0.00 | 0.00 | 0.00 |
December | 6.16 | 0.00 | 6.16 | 0.01 | 61.56 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 22.84 | 0.64 | 22.20 | 15.73 | 36.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 6.16 | 0.00 | 6.16 | 0.01 | 18.22 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 41.43 | 2.59 | 38.84 | 38.12 | 61.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 48.59 | 31.46 | 17.12 | 49.18 | 49.11 | 0.00 | 0.00 | 0.00 |
February | 58.96 | 35.93 | 23.02 | 61.30 | 47.43 | 0.00 | 0.00 | 0.00 |
March | 36.39 | 10.52 | 25.87 | 30.51 | 39.67 | 0.00 | 0.00 | 0.00 |
April | 74.59 | 33.05 | 41.54 | 87.68 | 32.99 | 0.00 | 0.00 | 0.00 |
May | 62.53 | 20.26 | 42.28 | 67.93 | 29.12 | 0.00 | 0.00 | 0.00 |
June | 57.73 | 13.96 | 43.76 | 65.80 | 21.80 | 0.00 | 0.00 | 0.00 |
July | 62.22 | 19.25 | 42.97 | 76.24 | 20.00 | 0.00 | 0.00 | 0.00 |
August | 73.08 | 32.74 | 40.34 | 94.10 | 21.66 | 0.00 | 0.00 | 0.00 |
September | 87.58 | 51.69 | 35.89 | 111.12 | 27.93 | 0.00 | 0.00 | 0.00 |
October | 58.44 | 33.69 | 24.75 | 66.18 | 36.67 | 0.00 | 0.00 | 0.00 |
November | 42.20 | 25.66 | 16.54 | 43.02 | 44.81 | 0.00 | 0.00 | 0.00 |
December | 33.49 | 21.47 | 12.01 | 32.64 | 56.51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 57.89 | 27.37 | 30.53 | 65.38 | 35.59 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 33.49 | 10.52 | 12.01 | 30.51 | 20.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 87.58 | 51.69 | 43.76 | 111.12 | 56.51 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 131.87 | 85.39 | 46.48 | 133.48 | 133.29 | 0.00 | 0.00 | 0.00 |
February | 160.02 | 97.53 | 62.49 | 166.37 | 128.74 | 0.00 | 0.00 | 0.00 |
March | 98.77 | 28.55 | 70.22 | 82.81 | 107.69 | 0.00 | 0.00 | 0.00 |
April | 202.46 | 89.71 | 112.75 | 237.98 | 89.55 | 0.00 | 0.00 | 0.00 |
May | 169.73 | 54.98 | 114.75 | 184.37 | 79.04 | 0.00 | 0.00 | 0.00 |
June | 156.68 | 37.89 | 118.79 | 178.60 | 59.16 | 0.00 | 0.00 | 0.00 |
July | 168.88 | 52.25 | 116.63 | 206.94 | 54.29 | 0.00 | 0.00 | 0.00 |
August | 198.35 | 88.87 | 109.48 | 255.41 | 58.79 | 0.00 | 0.00 | 0.00 |
September | 237.70 | 140.29 | 97.41 | 301.61 | 75.80 | 0.00 | 0.00 | 0.00 |
October | 158.61 | 91.44 | 67.17 | 179.63 | 99.52 | 0.00 | 0.00 | 0.00 |
November | 114.54 | 69.65 | 44.89 | 116.78 | 121.62 | 0.00 | 0.00 | 0.00 |
December | 90.89 | 58.28 | 32.61 | 88.60 | 153.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 157.13 | 74.27 | 82.86 | 177.47 | 96.59 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 90.89 | 28.55 | 32.61 | 82.81 | 54.29 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 237.70 | 140.29 | 118.79 | 301.61 | 153.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 104.13 | 67.43 | 36.70 | 105.90 | 99.12 | 0.00 | 0.00 | 0.00 |
February | 126.35 | 77.01 | 49.34 | 130.77 | 97.14 | 0.00 | 0.00 | 0.00 |
March | 77.99 | 22.54 | 55.44 | 65.73 | 80.69 | 0.00 | 0.00 | 0.00 |
April | 159.87 | 70.84 | 89.03 | 183.79 | 67.94 | 0.00 | 0.00 | 0.00 |
May | 134.02 | 43.42 | 90.61 | 141.84 | 59.15 | 0.00 | 0.00 | 0.00 |
June | 123.72 | 29.92 | 93.80 | 137.14 | 43.09 | 0.00 | 0.00 | 0.00 |
July | 133.35 | 41.26 | 92.10 | 159.88 | 38.77 | 0.00 | 0.00 | 0.00 |
August | 156.62 | 70.17 | 86.45 | 198.54 | 41.53 | 0.00 | 0.00 | 0.00 |
September | 187.69 | 110.78 | 76.92 | 235.26 | 54.94 | 0.00 | 0.00 | 0.00 |
October | 125.24 | 72.20 | 53.04 | 140.65 | 73.80 | 0.00 | 0.00 | 0.00 |
November | 90.44 | 55.00 | 35.44 | 92.20 | 90.24 | 0.00 | 0.00 | 0.00 |
December | 71.77 | 46.02 | 25.75 | 70.78 | 112.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 124.07 | 58.65 | 65.42 | 138.35 | 71.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 71.77 | 22.54 | 25.75 | 65.73 | 38.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 187.69 | 110.78 | 93.80 | 235.26 | 112.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.26 | 22.37 | 45.89 | 41.03 | 199.66 | 0.00 | 0.00 | 0.00 |
February | 120.75 | 51.40 | 69.35 | 94.50 | 190.34 | 0.00 | 0.00 | 0.00 |
March | 108.62 | 20.89 | 87.74 | 69.11 | 151.06 | 0.00 | 0.00 | 0.00 |
April | 255.82 | 101.43 | 154.39 | 265.53 | 123.18 | 0.00 | 0.00 | 0.00 |
May | 300.20 | 122.08 | 178.12 | 309.85 | 104.67 | 0.00 | 0.00 | 0.00 |
June | 324.11 | 133.43 | 190.68 | 364.06 | 76.96 | 0.00 | 0.00 | 0.00 |
July | 329.88 | 145.31 | 184.57 | 388.04 | 69.48 | 0.00 | 0.00 | 0.00 |
August | 277.60 | 120.26 | 157.34 | 328.73 | 75.62 | 0.00 | 0.00 | 0.00 |
September | 224.32 | 101.40 | 122.93 | 252.46 | 102.33 | 0.00 | 0.00 | 0.00 |
October | 119.58 | 43.43 | 76.15 | 105.60 | 141.00 | 0.00 | 0.00 | 0.00 |
November | 64.51 | 19.04 | 45.48 | 39.41 | 177.46 | 0.00 | 0.00 | 0.00 |
December | 35.97 | 7.31 | 28.66 | 12.60 | 224.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 185.99 | 74.05 | 111.94 | 189.57 | 136.05 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 35.97 | 7.31 | 28.66 | 12.60 | 69.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 329.88 | 145.31 | 190.68 | 388.04 | 224.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 18.24 | 0.00 | 18.24 | 1.90 | 109.92 | 0.00 | 0.00 | 0.00 |
February | 28.49 | 0.00 | 28.49 | 5.14 | 104.02 | 0.00 | 0.00 | 0.00 |
March | 39.43 | 0.00 | 39.43 | 15.27 | 83.34 | 0.00 | 0.00 | 0.00 |
April | 64.43 | 0.43 | 64.00 | 42.86 | 66.31 | 0.00 | 0.00 | 0.00 |
May | 80.55 | 4.11 | 76.44 | 53.27 | 53.44 | 0.00 | 0.00 | 0.00 |
June | 88.74 | 5.55 | 83.19 | 75.37 | 40.19 | 0.00 | 0.00 | 0.00 |
July | 84.37 | 4.96 | 79.41 | 75.36 | 37.40 | 0.00 | 0.00 | 0.00 |
August | 66.43 | 1.24 | 65.19 | 58.67 | 41.92 | 0.00 | 0.00 | 0.00 |
September | 50.39 | 0.03 | 50.36 | 39.50 | 56.63 | 0.00 | 0.00 | 0.00 |
October | 32.26 | 0.00 | 32.26 | 15.47 | 75.97 | 0.00 | 0.00 | 0.00 |
November | 19.38 | 0.00 | 19.38 | 2.96 | 95.57 | 0.00 | 0.00 | 0.00 |
December | 13.20 | 0.00 | 13.20 | 0.19 | 120.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 48.92 | 1.37 | 47.55 | 32.30 | 73.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.20 | 0.00 | 13.20 | 0.19 | 37.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.74 | 5.55 | 83.19 | 75.37 | 120.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.26 | 22.37 | 45.89 | 43.84 | 197.21 | 0.00 | 0.00 | 0.00 |
February | 120.75 | 51.40 | 69.35 | 98.42 | 187.64 | 0.00 | 0.00 | 0.00 |
March | 108.62 | 20.89 | 87.74 | 71.11 | 149.96 | 0.00 | 0.00 | 0.00 |
April | 255.82 | 101.43 | 154.39 | 268.89 | 122.35 | 0.00 | 0.00 | 0.00 |
May | 300.20 | 122.08 | 178.12 | 310.27 | 105.00 | 0.00 | 0.00 | 0.00 |
June | 324.11 | 133.43 | 190.68 | 361.22 | 78.66 | 0.00 | 0.00 | 0.00 |
July | 329.88 | 145.31 | 184.57 | 381.47 | 73.04 | 0.00 | 0.00 | 0.00 |
August | 277.60 | 120.26 | 157.34 | 325.06 | 79.70 | 0.00 | 0.00 | 0.00 |
September | 224.32 | 101.40 | 122.93 | 254.35 | 102.89 | 0.00 | 0.00 | 0.00 |
October | 119.58 | 43.43 | 76.15 | 109.44 | 138.95 | 0.00 | 0.00 | 0.00 |
November | 64.51 | 19.04 | 45.48 | 42.05 | 175.12 | 0.00 | 0.00 | 0.00 |
December | 35.97 | 7.31 | 28.66 | 13.82 | 222.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 185.99 | 74.05 | 111.94 | 190.29 | 135.81 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 35.97 | 7.31 | 28.66 | 13.82 | 73.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 329.88 | 145.31 | 190.68 | 381.47 | 222.14 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 152.71 | 98.89 | 53.82 | 150.28 | 151.47 | 0.00 | 0.00 | 0.00 |
February | 185.31 | 112.94 | 72.37 | 187.26 | 147.93 | 0.00 | 0.00 | 0.00 |
March | 114.37 | 33.06 | 81.31 | 92.92 | 121.95 | 0.00 | 0.00 | 0.00 |
April | 234.46 | 103.89 | 130.57 | 267.42 | 100.59 | 0.00 | 0.00 | 0.00 |
May | 196.56 | 63.67 | 132.88 | 207.57 | 86.70 | 0.00 | 0.00 | 0.00 |
June | 181.44 | 43.88 | 137.56 | 202.65 | 62.22 | 0.00 | 0.00 | 0.00 |
July | 195.57 | 60.50 | 135.07 | 236.06 | 55.78 | 0.00 | 0.00 | 0.00 |
August | 229.70 | 102.92 | 126.79 | 291.32 | 60.35 | 0.00 | 0.00 | 0.00 |
September | 275.27 | 162.47 | 112.81 | 342.80 | 81.60 | 0.00 | 0.00 | 0.00 |
October | 183.68 | 105.90 | 77.78 | 202.64 | 112.23 | 0.00 | 0.00 | 0.00 |
November | 132.64 | 80.66 | 51.98 | 131.26 | 138.54 | 0.00 | 0.00 | 0.00 |
December | 105.26 | 67.49 | 37.76 | 100.40 | 172.56 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 181.96 | 86.01 | 95.95 | 200.78 | 107.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 105.26 | 33.06 | 37.76 | 92.92 | 55.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 275.27 | 162.47 | 137.56 | 342.80 | 172.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 127.71 | 0.00 | 127.71 | 3.53 | 948.56 | 0.00 | 0.00 | 0.00 |
February | 199.42 | 0.00 | 199.42 | 13.27 | 890.18 | 0.00 | 0.00 | 0.00 |
March | 275.99 | 0.00 | 275.99 | 68.47 | 718.55 | 0.00 | 0.00 | 0.00 |
April | 450.98 | 3.00 | 447.98 | 265.83 | 545.57 | 0.00 | 0.00 | 0.00 |
May | 563.83 | 28.75 | 535.08 | 332.80 | 445.35 | 0.00 | 0.00 | 0.00 |
June | 621.15 | 38.85 | 582.30 | 500.19 | 333.74 | 0.00 | 0.00 | 0.00 |
July | 590.59 | 34.74 | 555.86 | 514.66 | 302.26 | 0.00 | 0.00 | 0.00 |
August | 464.99 | 8.70 | 456.29 | 396.41 | 337.15 | 0.00 | 0.00 | 0.00 |
September | 352.69 | 0.21 | 352.48 | 249.93 | 469.27 | 0.00 | 0.00 | 0.00 |
October | 225.82 | 0.00 | 225.82 | 75.97 | 665.47 | 0.00 | 0.00 | 0.00 |
November | 135.69 | 0.00 | 135.69 | 6.33 | 848.80 | 0.00 | 0.00 | 0.00 |
December | 92.40 | 0.00 | 92.40 | 0.00 | 1049.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 342.41 | 9.59 | 332.82 | 203.25 | 628.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 92.40 | 0.00 | 92.40 | 0.00 | 302.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 621.15 | 38.85 | 582.30 | 514.66 | 1049.27 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 127.71 | 0.00 | 127.71 | 2.48 | 977.76 | 0.00 | 0.00 | 0.00 |
February | 199.42 | 0.00 | 199.42 | 10.42 | 917.69 | 0.00 | 0.00 | 0.00 |
March | 275.99 | 0.00 | 275.99 | 60.82 | 739.70 | 0.00 | 0.00 | 0.00 |
April | 450.98 | 3.00 | 447.98 | 254.95 | 557.91 | 0.00 | 0.00 | 0.00 |
May | 563.83 | 28.75 | 535.08 | 319.94 | 455.01 | 0.00 | 0.00 | 0.00 |
June | 621.15 | 38.85 | 582.30 | 488.09 | 340.94 | 0.00 | 0.00 | 0.00 |
July | 590.59 | 34.74 | 555.86 | 503.52 | 308.80 | 0.00 | 0.00 | 0.00 |
August | 464.99 | 8.70 | 456.29 | 386.38 | 345.11 | 0.00 | 0.00 | 0.00 |
September | 352.69 | 0.21 | 352.48 | 240.55 | 480.19 | 0.00 | 0.00 | 0.00 |
October | 225.82 | 0.00 | 225.82 | 68.88 | 685.08 | 0.00 | 0.00 | 0.00 |
November | 135.69 | 0.00 | 135.69 | 4.57 | 876.94 | 0.00 | 0.00 | 0.00 |
December | 92.40 | 0.00 | 92.40 | 0.00 | 1081.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 342.41 | 9.59 | 332.82 | 196.00 | 645.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 92.40 | 0.00 | 92.40 | 0.00 | 308.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 621.15 | 38.85 | 582.30 | 503.52 | 1081.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 18.24 | 0.00 | 18.24 | 3.10 | 110.57 | 0.00 | 0.00 | 0.00 |
February | 28.49 | 0.00 | 28.49 | 6.95 | 105.68 | 0.00 | 0.00 | 0.00 |
March | 39.43 | 0.00 | 39.43 | 20.18 | 85.17 | 0.00 | 0.00 | 0.00 |
April | 64.43 | 0.43 | 64.00 | 56.44 | 68.72 | 0.00 | 0.00 | 0.00 |
May | 80.55 | 4.11 | 76.44 | 69.17 | 59.45 | 0.00 | 0.00 | 0.00 |
June | 88.74 | 5.55 | 83.19 | 96.54 | 45.43 | 0.00 | 0.00 | 0.00 |
July | 84.37 | 4.96 | 79.41 | 99.86 | 41.64 | 0.00 | 0.00 | 0.00 |
August | 66.43 | 1.24 | 65.19 | 79.96 | 44.13 | 0.00 | 0.00 | 0.00 |
September | 50.39 | 0.03 | 50.36 | 53.51 | 58.20 | 0.00 | 0.00 | 0.00 |
October | 32.26 | 0.00 | 32.26 | 21.22 | 78.89 | 0.00 | 0.00 | 0.00 |
November | 19.38 | 0.00 | 19.38 | 4.59 | 98.63 | 0.00 | 0.00 | 0.00 |
December | 13.20 | 0.00 | 13.20 | 0.58 | 124.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 48.92 | 1.37 | 47.55 | 42.86 | 76.64 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.20 | 0.00 | 13.20 | 0.58 | 41.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.74 | 5.55 | 83.19 | 99.86 | 124.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 138.47 | 55.15 | 83.32 | 93.80 | 393.94 | 0.00 | 0.00 | 0.00 |
February | 209.10 | 77.91 | 131.19 | 154.17 | 377.36 | 0.00 | 0.00 | 0.00 |
March | 217.25 | 42.85 | 174.40 | 163.37 | 307.75 | 0.00 | 0.00 | 0.00 |
April | 582.00 | 272.88 | 309.12 | 686.03 | 248.13 | 0.00 | 0.00 | 0.00 |
May | 612.78 | 267.28 | 345.50 | 698.24 | 225.34 | 0.00 | 0.00 | 0.00 |
June | 606.38 | 242.24 | 364.14 | 748.03 | 172.48 | 0.00 | 0.00 | 0.00 |
July | 618.87 | 262.88 | 355.99 | 800.41 | 157.10 | 0.00 | 0.00 | 0.00 |
August | 587.90 | 281.45 | 306.45 | 780.78 | 164.13 | 0.00 | 0.00 | 0.00 |
September | 527.81 | 280.46 | 247.35 | 674.54 | 209.45 | 0.00 | 0.00 | 0.00 |
October | 256.72 | 107.36 | 149.36 | 266.76 | 287.12 | 0.00 | 0.00 | 0.00 |
November | 132.86 | 45.21 | 87.65 | 90.00 | 355.39 | 0.00 | 0.00 | 0.00 |
December | 98.82 | 36.98 | 61.84 | 56.20 | 449.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 382.96 | 164.59 | 218.37 | 435.40 | 278.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 98.82 | 36.98 | 61.84 | 56.20 | 157.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 618.87 | 281.45 | 364.14 | 800.41 | 449.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 104.13 | 67.43 | 36.70 | 111.77 | 100.08 | 0.00 | 0.00 | 0.00 |
February | 126.35 | 77.01 | 49.34 | 138.45 | 99.10 | 0.00 | 0.00 | 0.00 |
March | 77.99 | 22.54 | 55.44 | 73.48 | 83.04 | 0.00 | 0.00 | 0.00 |
April | 159.87 | 70.84 | 89.03 | 201.10 | 70.00 | 0.00 | 0.00 | 0.00 |
May | 134.02 | 43.42 | 90.61 | 158.74 | 64.42 | 0.00 | 0.00 | 0.00 |
June | 123.72 | 29.92 | 93.80 | 157.40 | 48.58 | 0.00 | 0.00 | 0.00 |
July | 133.35 | 41.26 | 92.10 | 181.67 | 44.28 | 0.00 | 0.00 | 0.00 |
August | 156.62 | 70.17 | 86.45 | 219.59 | 45.83 | 0.00 | 0.00 | 0.00 |
September | 187.69 | 110.78 | 76.92 | 253.70 | 57.78 | 0.00 | 0.00 | 0.00 |
October | 125.24 | 72.20 | 53.04 | 151.36 | 76.77 | 0.00 | 0.00 | 0.00 |
November | 90.44 | 55.00 | 35.44 | 97.49 | 93.21 | 0.00 | 0.00 | 0.00 |
December | 71.77 | 46.02 | 25.75 | 73.63 | 117.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 124.07 | 58.65 | 65.42 | 151.36 | 74.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 71.77 | 22.54 | 25.75 | 73.48 | 44.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 187.69 | 110.78 | 93.80 | 253.70 | 117.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.11 | 0.00 | 23.11 | 1.18 | 154.11 | 0.00 | 0.00 | 0.00 |
February | 36.08 | 0.00 | 36.08 | 3.84 | 143.53 | 0.00 | 0.00 | 0.00 |
March | 49.93 | 0.00 | 49.93 | 16.33 | 114.10 | 0.00 | 0.00 | 0.00 |
April | 81.59 | 0.54 | 81.05 | 53.22 | 88.98 | 0.00 | 0.00 | 0.00 |
May | 102.01 | 5.20 | 96.81 | 67.75 | 72.17 | 0.00 | 0.00 | 0.00 |
June | 112.38 | 7.03 | 105.35 | 97.13 | 55.17 | 0.00 | 0.00 | 0.00 |
July | 106.85 | 6.28 | 100.57 | 98.53 | 50.50 | 0.00 | 0.00 | 0.00 |
August | 84.13 | 1.57 | 82.56 | 75.72 | 56.42 | 0.00 | 0.00 | 0.00 |
September | 63.81 | 0.04 | 63.77 | 48.63 | 77.45 | 0.00 | 0.00 | 0.00 |
October | 40.86 | 0.00 | 40.86 | 16.78 | 105.20 | 0.00 | 0.00 | 0.00 |
November | 24.55 | 0.00 | 24.55 | 2.10 | 134.49 | 0.00 | 0.00 | 0.00 |
December | 16.72 | 0.00 | 16.72 | 0.01 | 169.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 61.95 | 1.73 | 60.22 | 40.29 | 101.64 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 16.72 | 0.00 | 16.72 | 0.01 | 50.50 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 112.38 | 7.03 | 105.35 | 98.53 | 169.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.67 | 0.00 | 20.67 | 1.05 | 137.85 | 0.00 | 0.00 | 0.00 |
February | 32.28 | 0.00 | 32.28 | 3.44 | 128.42 | 0.00 | 0.00 | 0.00 |
March | 44.68 | 0.00 | 44.68 | 14.61 | 102.09 | 0.00 | 0.00 | 0.00 |
April | 73.00 | 0.49 | 72.52 | 47.61 | 79.61 | 0.00 | 0.00 | 0.00 |
May | 91.27 | 4.65 | 86.62 | 60.62 | 64.57 | 0.00 | 0.00 | 0.00 |
June | 100.55 | 6.29 | 94.26 | 86.91 | 49.36 | 0.00 | 0.00 | 0.00 |
July | 95.60 | 5.62 | 89.98 | 88.16 | 45.18 | 0.00 | 0.00 | 0.00 |
August | 75.27 | 1.41 | 73.86 | 67.75 | 50.48 | 0.00 | 0.00 | 0.00 |
September | 57.09 | 0.03 | 57.06 | 43.51 | 69.29 | 0.00 | 0.00 | 0.00 |
October | 36.56 | 0.00 | 36.56 | 15.02 | 94.12 | 0.00 | 0.00 | 0.00 |
November | 21.96 | 0.00 | 21.96 | 1.88 | 120.32 | 0.00 | 0.00 | 0.00 |
December | 14.96 | 0.00 | 14.96 | 0.01 | 152.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.43 | 1.55 | 53.88 | 36.05 | 90.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.96 | 0.00 | 14.96 | 0.01 | 45.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 100.55 | 6.29 | 94.26 | 88.16 | 152.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 388.74 | 251.73 | 137.01 | 388.70 | 398.07 | 0.00 | 0.00 | 0.00 |
February | 471.72 | 287.50 | 184.22 | 483.81 | 385.89 | 0.00 | 0.00 | 0.00 |
March | 291.15 | 84.16 | 206.99 | 237.96 | 322.66 | 0.00 | 0.00 | 0.00 |
April | 596.83 | 264.46 | 332.38 | 689.00 | 267.10 | 0.00 | 0.00 | 0.00 |
May | 500.34 | 162.08 | 338.26 | 531.29 | 236.24 | 0.00 | 0.00 | 0.00 |
June | 461.87 | 111.70 | 350.17 | 512.31 | 178.88 | 0.00 | 0.00 | 0.00 |
July | 497.84 | 154.02 | 343.83 | 595.37 | 164.19 | 0.00 | 0.00 | 0.00 |
August | 584.72 | 261.98 | 322.74 | 740.16 | 175.86 | 0.00 | 0.00 | 0.00 |
September | 700.72 | 413.57 | 287.15 | 878.75 | 224.22 | 0.00 | 0.00 | 0.00 |
October | 467.56 | 269.56 | 198.00 | 523.35 | 296.54 | 0.00 | 0.00 | 0.00 |
November | 337.65 | 205.33 | 132.32 | 339.38 | 365.95 | 0.00 | 0.00 | 0.00 |
December | 267.94 | 171.81 | 96.13 | 257.98 | 460.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 463.20 | 218.95 | 244.25 | 514.11 | 289.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 267.94 | 84.16 | 96.13 | 237.96 | 164.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 700.72 | 413.57 | 350.17 | 878.75 | 460.79 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.141058E+10 | 0.913437E+09 | 0.497142E+09 | 0.140774E+10 | 0.136446E+10 |
February | 0.154602E+10 | 0.942266E+09 | 0.603757E+09 | 0.158368E+10 | 0.119085E+10 |
March | 0.105645E+10 | 0.305385E+09 | 0.751065E+09 | 0.883634E+09 | 0.109888E+10 |
April | 0.209580E+10 | 0.928651E+09 | 0.116715E+10 | 0.241868E+10 | 0.882537E+09 |
May | 0.181553E+10 | 0.588130E+09 | 0.122740E+10 | 0.196088E+10 | 0.776220E+09 |
June | 0.162186E+10 | 0.392246E+09 | 0.122962E+10 | 0.184704E+10 | 0.551681E+09 |
July | 0.180646E+10 | 0.558869E+09 | 0.124759E+10 | 0.220070E+10 | 0.524384E+09 |
August | 0.212171E+10 | 0.950629E+09 | 0.117108E+10 | 0.269660E+10 | 0.578409E+09 |
September | 0.246060E+10 | 0.145227E+10 | 0.100834E+10 | 0.307191E+10 | 0.736044E+09 |
October | 0.169659E+10 | 0.978133E+09 | 0.718459E+09 | 0.188764E+10 | 0.101315E+10 |
November | 0.118565E+10 | 0.721021E+09 | 0.464633E+09 | 0.119330E+10 | 0.120072E+10 |
December | 0.972235E+09 | 0.623425E+09 | 0.348810E+09 | 0.941729E+09 | 0.153921E+10 |
Annual Sum or Average | 0.197895E+11 | 0.935446E+10 | 0.104350E+11 | 0.220935E+11 | 0.114566E+11 |
Minimum of Months | 0.972235E+09 | 0.305385E+09 | 0.348810E+09 | 0.883634E+09 | 0.524384E+09 |
Maximum of Months | 0.246060E+10 | 0.145227E+10 | 0.124759E+10 | 0.307191E+10 | 0.153921E+10 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.397210E+10 | 0.257218E+10 | 0.139992E+10 | 0.391784E+10 | 0.396088E+10 |
February | 0.435350E+10 | 0.265336E+10 | 0.170014E+10 | 0.441022E+10 | 0.346888E+10 |
March | 0.297490E+10 | 0.859945E+09 | 0.211495E+10 | 0.243847E+10 | 0.320565E+10 |
April | 0.590163E+10 | 0.261502E+10 | 0.328662E+10 | 0.672926E+10 | 0.263559E+10 |
May | 0.511242E+10 | 0.165614E+10 | 0.345628E+10 | 0.543245E+10 | 0.233754E+10 |
June | 0.456706E+10 | 0.110454E+10 | 0.346252E+10 | 0.510214E+10 | 0.169843E+10 |
July | 0.508687E+10 | 0.157374E+10 | 0.351313E+10 | 0.609487E+10 | 0.161912E+10 |
August | 0.597459E+10 | 0.267691E+10 | 0.329768E+10 | 0.749758E+10 | 0.179626E+10 |
September | 0.692890E+10 | 0.408949E+10 | 0.283941E+10 | 0.856338E+10 | 0.224773E+10 |
October | 0.477749E+10 | 0.275436E+10 | 0.202313E+10 | 0.525550E+10 | 0.302090E+10 |
November | 0.333872E+10 | 0.203035E+10 | 0.130838E+10 | 0.331881E+10 | 0.352127E+10 |
December | 0.273775E+10 | 0.175552E+10 | 0.982227E+09 | 0.262152E+10 | 0.444928E+10 |
Annual Sum or Average | 0.557259E+11 | 0.263415E+11 | 0.293844E+11 | 0.613820E+11 | 0.339615E+11 |
Minimum of Months | 0.273775E+10 | 0.859945E+09 | 0.982227E+09 | 0.243847E+10 | 0.161912E+10 |
Maximum of Months | 0.692890E+10 | 0.408949E+10 | 0.351313E+10 | 0.856338E+10 | 0.444928E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.515998E+10 | 0.334141E+10 | 0.181858E+10 | 0.514095E+10 | 0.548500E+10 |
February | 0.565545E+10 | 0.344687E+10 | 0.220858E+10 | 0.579629E+10 | 0.478352E+10 |
March | 0.386456E+10 | 0.111712E+10 | 0.274744E+10 | 0.316719E+10 | 0.448874E+10 |
April | 0.766656E+10 | 0.339706E+10 | 0.426950E+10 | 0.888398E+10 | 0.362514E+10 |
May | 0.664133E+10 | 0.215142E+10 | 0.448991E+10 | 0.714082E+10 | 0.325542E+10 |
June | 0.593287E+10 | 0.143486E+10 | 0.449801E+10 | 0.668614E+10 | 0.238064E+10 |
July | 0.660813E+10 | 0.204438E+10 | 0.456376E+10 | 0.801208E+10 | 0.225822E+10 |
August | 0.776133E+10 | 0.347745E+10 | 0.428388E+10 | 0.989604E+10 | 0.246915E+10 |
September | 0.900103E+10 | 0.531248E+10 | 0.368855E+10 | 0.113060E+11 | 0.306658E+10 |
October | 0.620623E+10 | 0.357807E+10 | 0.262816E+10 | 0.691448E+10 | 0.420570E+10 |
November | 0.433719E+10 | 0.263754E+10 | 0.169966E+10 | 0.434744E+10 | 0.490913E+10 |
December | 0.355649E+10 | 0.228052E+10 | 0.127597E+10 | 0.342708E+10 | 0.617239E+10 |
Annual Sum or Average | 0.723912E+11 | 0.342192E+11 | 0.381720E+11 | 0.807185E+11 | 0.470996E+11 |
Minimum of Months | 0.355649E+10 | 0.111712E+10 | 0.127597E+10 | 0.316719E+10 | 0.225822E+10 |
Maximum of Months | 0.900103E+10 | 0.531248E+10 | 0.456376E+10 | 0.113060E+11 | 0.617239E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.278896E+09 | 0.180602E+09 | 98293958.39 | 0.282974E+09 | 0.269226E+09 |
February | 0.305676E+09 | 0.186302E+09 | 0.119374E+09 | 0.316452E+09 | 0.237142E+09 |
March | 0.208879E+09 | 60379947.61 | 0.148499E+09 | 0.175893E+09 | 0.218894E+09 |
April | 0.414378E+09 | 0.183610E+09 | 0.230767E+09 | 0.479587E+09 | 0.177246E+09 |
May | 0.358964E+09 | 0.116283E+09 | 0.242681E+09 | 0.383324E+09 | 0.158813E+09 |
June | 0.320672E+09 | 77553725.01 | 0.243119E+09 | 0.359046E+09 | 0.112020E+09 |
July | 0.357170E+09 | 0.110498E+09 | 0.246672E+09 | 0.432054E+09 | 0.104255E+09 |
August | 0.419500E+09 | 0.187956E+09 | 0.231545E+09 | 0.535240E+09 | 0.112294E+09 |
September | 0.486505E+09 | 0.287138E+09 | 0.199367E+09 | 0.612678E+09 | 0.143811E+09 |
October | 0.335446E+09 | 0.193394E+09 | 0.142052E+09 | 0.377370E+09 | 0.200305E+09 |
November | 0.234425E+09 | 0.142558E+09 | 91866383.63 | 0.238815E+09 | 0.236973E+09 |
December | 0.192228E+09 | 0.123262E+09 | 68966069.76 | 0.189211E+09 | 0.305042E+09 |
Annual Sum or Average | 0.391274E+10 | 0.184954E+10 | 0.206320E+10 | 0.438265E+10 | 0.227602E+10 |
Minimum of Months | 0.192228E+09 | 60379947.61 | 68966069.76 | 0.175893E+09 | 0.104255E+09 |
Maximum of Months | 0.486505E+09 | 0.287138E+09 | 0.246672E+09 | 0.612678E+09 | 0.305042E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182828E+09 | 59922886.42 | 0.122905E+09 | 0.108973E+09 | 0.543240E+09 |
February | 0.292111E+09 | 0.124345E+09 | 0.167766E+09 | 0.228479E+09 | 0.465532E+09 |
March | 0.290934E+09 | 55944156.98 | 0.234990E+09 | 0.184924E+09 | 0.410159E+09 |
April | 0.663093E+09 | 0.262902E+09 | 0.400191E+09 | 0.694852E+09 | 0.322001E+09 |
May | 0.804054E+09 | 0.326982E+09 | 0.477072E+09 | 0.838457E+09 | 0.281419E+09 |
June | 0.840081E+09 | 0.345850E+09 | 0.494232E+09 | 0.953371E+09 | 0.200349E+09 |
July | 0.883552E+09 | 0.389198E+09 | 0.494354E+09 | 0.104900E+10 | 0.187163E+09 |
August | 0.743526E+09 | 0.322103E+09 | 0.421423E+09 | 0.888120E+09 | 0.204782E+09 |
September | 0.581449E+09 | 0.262824E+09 | 0.318624E+09 | 0.658808E+09 | 0.268338E+09 |
October | 0.320274E+09 | 0.116318E+09 | 0.203956E+09 | 0.283613E+09 | 0.383365E+09 |
November | 0.167220E+09 | 49338807.43 | 0.117881E+09 | 0.101482E+09 | 0.466620E+09 |
December | 96331508.60 | 19581694.53 | 76749814.07 | 33145948.67 | 0.607209E+09 |
Annual Sum or Average | 0.586545E+10 | 0.233531E+10 | 0.353014E+10 | 0.602322E+10 | 0.434018E+10 |
Minimum of Months | 96331508.60 | 19581694.53 | 76749814.07 | 33145948.67 | 0.187163E+09 |
Maximum of Months | 0.883552E+09 | 0.389198E+09 | 0.494354E+09 | 0.104900E+10 | 0.607209E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 48866192.30 | 0.00 | 48866192.30 | 4672302.02 | 0.299374E+09 |
February | 68922124.97 | 0.00 | 68922124.97 | 11891278.27 | 0.254903E+09 |
March | 0.105605E+09 | 713.77 | 0.105604E+09 | 40317869.92 | 0.226432E+09 |
April | 0.166996E+09 | 1109896.04 | 0.165887E+09 | 0.113431E+09 | 0.173022E+09 |
May | 0.215746E+09 | 11001825.72 | 0.204744E+09 | 0.146097E+09 | 0.143345E+09 |
June | 0.230011E+09 | 14387406.61 | 0.215624E+09 | 0.199779E+09 | 0.103857E+09 |
July | 0.225987E+09 | 13291530.21 | 0.212695E+09 | 0.206925E+09 | 99013385.20 |
August | 0.177924E+09 | 3327374.37 | 0.174597E+09 | 0.160406E+09 | 0.111349E+09 |
September | 0.130601E+09 | 77189.67 | 0.130524E+09 | 0.103351E+09 | 0.147512E+09 |
October | 86410212.49 | 0.00 | 86410212.49 | 40808337.79 | 0.206928E+09 |
November | 50244830.41 | 0.00 | 50244830.41 | 7147569.57 | 0.252034E+09 |
December | 35357147.73 | 0.00 | 35357147.73 | 389447.29 | 0.326586E+09 |
Annual Sum or Average | 0.154267E+10 | 43195936.38 | 0.149948E+10 | 0.103522E+10 | 0.234436E+10 |
Minimum of Months | 35357147.73 | 0.00 | 35357147.73 | 389447.29 | 99013385.20 |
Maximum of Months | 0.230011E+09 | 14387406.61 | 0.215624E+09 | 0.206925E+09 | 0.326586E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182828E+09 | 59922886.42 | 0.122905E+09 | 0.115962E+09 | 0.536520E+09 |
February | 0.292111E+09 | 0.124345E+09 | 0.167766E+09 | 0.237070E+09 | 0.459346E+09 |
March | 0.290934E+09 | 55944156.98 | 0.234990E+09 | 0.189807E+09 | 0.407359E+09 |
April | 0.663093E+09 | 0.262902E+09 | 0.400191E+09 | 0.703459E+09 | 0.319661E+09 |
May | 0.804054E+09 | 0.326982E+09 | 0.477072E+09 | 0.840379E+09 | 0.281641E+09 |
June | 0.840081E+09 | 0.345850E+09 | 0.494232E+09 | 0.947875E+09 | 0.203340E+09 |
July | 0.883552E+09 | 0.389198E+09 | 0.494354E+09 | 0.103504E+10 | 0.193891E+09 |
August | 0.743526E+09 | 0.322103E+09 | 0.421423E+09 | 0.880736E+09 | 0.212565E+09 |
September | 0.581449E+09 | 0.262824E+09 | 0.318624E+09 | 0.663852E+09 | 0.268509E+09 |
October | 0.320274E+09 | 0.116318E+09 | 0.203956E+09 | 0.292807E+09 | 0.378353E+09 |
November | 0.167220E+09 | 49338807.43 | 0.117881E+09 | 0.107700E+09 | 0.460826E+09 |
December | 96331508.60 | 19581694.53 | 76749814.07 | 36221900.06 | 0.601882E+09 |
Annual Sum or Average | 0.586545E+10 | 0.233531E+10 | 0.353014E+10 | 0.605091E+10 | 0.432389E+10 |
Minimum of Months | 96331508.60 | 19581694.53 | 76749814.07 | 36221900.06 | 0.193891E+09 |
Maximum of Months | 0.883552E+09 | 0.389198E+09 | 0.494354E+09 | 0.103504E+10 | 0.601882E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.223073E+09 | 0.144453E+09 | 78619531.41 | 0.205972E+09 | 0.279727E+09 |
February | 0.244492E+09 | 0.149012E+09 | 95480078.80 | 0.233118E+09 | 0.247081E+09 |
March | 0.167070E+09 | 48294353.64 | 0.118776E+09 | 0.119672E+09 | 0.226785E+09 |
April | 0.331436E+09 | 0.146859E+09 | 0.184577E+09 | 0.352676E+09 | 0.195556E+09 |
May | 0.287114E+09 | 93008268.71 | 0.194106E+09 | 0.273757E+09 | 0.181615E+09 |
June | 0.256487E+09 | 62030643.78 | 0.194456E+09 | 0.253399E+09 | 0.135652E+09 |
July | 0.285680E+09 | 88380901.82 | 0.197299E+09 | 0.310529E+09 | 0.129480E+09 |
August | 0.335533E+09 | 0.150335E+09 | 0.185199E+09 | 0.394981E+09 | 0.139695E+09 |
September | 0.389127E+09 | 0.229665E+09 | 0.159462E+09 | 0.458874E+09 | 0.169042E+09 |
October | 0.268304E+09 | 0.154684E+09 | 0.113619E+09 | 0.276760E+09 | 0.228820E+09 |
November | 0.187502E+09 | 0.114024E+09 | 73478494.01 | 0.173335E+09 | 0.259297E+09 |
December | 0.153752E+09 | 98589840.04 | 55161885.59 | 0.145374E+09 | 0.269941E+09 |
Annual Sum or Average | 0.312957E+10 | 0.147934E+10 | 0.165023E+10 | 0.319845E+10 | 0.246269E+10 |
Minimum of Months | 0.153752E+09 | 48294353.64 | 55161885.59 | 0.119672E+09 | 0.129480E+09 |
Maximum of Months | 0.389127E+09 | 0.229665E+09 | 0.197299E+09 | 0.458874E+09 | 0.279727E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 39098135.84 | 0.00 | 39098135.84 | 2774005.79 | 0.251704E+09 |
February | 55145008.79 | 0.00 | 55145008.79 | 7888634.42 | 0.211729E+09 |
March | 84495288.28 | 571.09 | 84494717.18 | 29449612.23 | 0.189019E+09 |
April | 0.133615E+09 | 888034.53 | 0.132727E+09 | 94787862.61 | 0.138307E+09 |
May | 0.172620E+09 | 8802627.26 | 0.163817E+09 | 0.123700E+09 | 0.114015E+09 |
June | 0.184033E+09 | 11511450.99 | 0.172522E+09 | 0.170159E+09 | 80671637.53 |
July | 0.180813E+09 | 10634633.66 | 0.170179E+09 | 0.179029E+09 | 75413515.97 |
August | 0.142358E+09 | 2662252.34 | 0.139696E+09 | 0.139475E+09 | 84157925.23 |
September | 0.104495E+09 | 61759.92 | 0.104433E+09 | 88720360.48 | 0.114756E+09 |
October | 69137333.33 | 0.00 | 69137333.33 | 32202247.28 | 0.171156E+09 |
November | 40201192.52 | 0.00 | 40201192.52 | 4498810.37 | 0.212799E+09 |
December | 28289467.61 | 0.00 | 28289467.61 | 86338.12 | 0.276745E+09 |
Annual Sum or Average | 0.123430E+10 | 34561329.80 | 0.119974E+10 | 0.872771E+09 | 0.192047E+10 |
Minimum of Months | 28289467.61 | 0.00 | 28289467.61 | 86338.12 | 75413515.97 |
Maximum of Months | 0.184033E+09 | 11511450.99 | 0.172522E+09 | 0.179029E+09 | 0.276745E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.185446E+09 | 73858251.45 | 0.111587E+09 | 0.105976E+09 | 0.535417E+09 |
February | 0.252944E+09 | 94250751.19 | 0.158693E+09 | 0.163616E+09 | 0.456011E+09 |
March | 0.290958E+09 | 57386715.51 | 0.233571E+09 | 0.181621E+09 | 0.406120E+09 |
April | 0.754324E+09 | 0.353674E+09 | 0.400650E+09 | 0.801925E+09 | 0.308249E+09 |
May | 0.820699E+09 | 0.357967E+09 | 0.462732E+09 | 0.850945E+09 | 0.272575E+09 |
June | 0.785919E+09 | 0.313959E+09 | 0.471960E+09 | 0.875819E+09 | 0.194124E+09 |
July | 0.828856E+09 | 0.352075E+09 | 0.476782E+09 | 0.967224E+09 | 0.180098E+09 |
August | 0.787372E+09 | 0.376942E+09 | 0.410430E+09 | 0.940998E+09 | 0.195177E+09 |
September | 0.684094E+09 | 0.363500E+09 | 0.320594E+09 | 0.785173E+09 | 0.257538E+09 |
October | 0.343823E+09 | 0.143781E+09 | 0.200042E+09 | 0.308328E+09 | 0.376184E+09 |
November | 0.172200E+09 | 58593481.72 | 0.113606E+09 | 97771378.58 | 0.456206E+09 |
December | 0.132354E+09 | 49526930.11 | 82827209.84 | 64875204.49 | 0.589547E+09 |
Annual Sum or Average | 0.603899E+10 | 0.259551E+10 | 0.344347E+10 | 0.614427E+10 | 0.422725E+10 |
Minimum of Months | 0.132354E+09 | 49526930.11 | 82827209.84 | 64875204.49 | 0.180098E+09 |
Maximum of Months | 0.828856E+09 | 0.376942E+09 | 0.476782E+09 | 0.967224E+09 | 0.589547E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.278896E+09 | 0.180602E+09 | 98293958.39 | 0.282426E+09 | 0.268840E+09 |
February | 0.305676E+09 | 0.186302E+09 | 0.119374E+09 | 0.316189E+09 | 0.236158E+09 |
March | 0.208879E+09 | 60379947.61 | 0.148499E+09 | 0.174814E+09 | 0.218417E+09 |
April | 0.414378E+09 | 0.183610E+09 | 0.230767E+09 | 0.475460E+09 | 0.176786E+09 |
May | 0.358964E+09 | 0.116283E+09 | 0.242681E+09 | 0.380144E+09 | 0.157550E+09 |
June | 0.320672E+09 | 77553725.01 | 0.243119E+09 | 0.357725E+09 | 0.110130E+09 |
July | 0.357170E+09 | 0.110498E+09 | 0.246672E+09 | 0.430510E+09 | 0.102462E+09 |
August | 0.419500E+09 | 0.187956E+09 | 0.231545E+09 | 0.532986E+09 | 0.111209E+09 |
September | 0.486505E+09 | 0.287138E+09 | 0.199367E+09 | 0.609384E+09 | 0.143385E+09 |
October | 0.335446E+09 | 0.193394E+09 | 0.142052E+09 | 0.375672E+09 | 0.199869E+09 |
November | 0.234425E+09 | 0.142558E+09 | 91866383.63 | 0.238336E+09 | 0.236584E+09 |
December | 0.192228E+09 | 0.123262E+09 | 68966069.76 | 0.188407E+09 | 0.305433E+09 |
Annual Sum or Average | 0.391274E+10 | 0.184954E+10 | 0.206320E+10 | 0.436205E+10 | 0.226682E+10 |
Minimum of Months | 0.192228E+09 | 60379947.61 | 68966069.76 | 0.174814E+09 | 0.102462E+09 |
Maximum of Months | 0.486505E+09 | 0.287138E+09 | 0.246672E+09 | 0.609384E+09 | 0.305433E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 48866192.30 | 0.00 | 48866192.30 | 4241694.41 | 0.298762E+09 |
February | 68922124.97 | 0.00 | 68922124.97 | 11176578.88 | 0.253319E+09 |
March | 0.105605E+09 | 713.77 | 0.105604E+09 | 39236074.01 | 0.226009E+09 |
April | 0.166996E+09 | 1109896.04 | 0.165887E+09 | 0.108767E+09 | 0.172822E+09 |
May | 0.215746E+09 | 11001825.72 | 0.204744E+09 | 0.143455E+09 | 0.142033E+09 |
June | 0.230011E+09 | 14387406.61 | 0.215624E+09 | 0.200045E+09 | 0.101604E+09 |
July | 0.225987E+09 | 13291530.21 | 0.212695E+09 | 0.208964E+09 | 95618051.12 |
August | 0.177924E+09 | 3327374.37 | 0.174597E+09 | 0.159598E+09 | 0.108070E+09 |
September | 0.130601E+09 | 77189.67 | 0.130524E+09 | 99642139.17 | 0.146246E+09 |
October | 86410212.49 | 0.00 | 86410212.49 | 38868404.63 | 0.206543E+09 |
November | 50244830.41 | 0.00 | 50244830.41 | 6712402.88 | 0.251365E+09 |
December | 35357147.73 | 0.00 | 35357147.73 | 306298.23 | 0.326725E+09 |
Annual Sum or Average | 0.154267E+10 | 43195936.38 | 0.149948E+10 | 0.102101E+10 | 0.232912E+10 |
Minimum of Months | 35357147.73 | 0.00 | 35357147.73 | 306298.23 | 95618051.12 |
Maximum of Months | 0.230011E+09 | 14387406.61 | 0.215624E+09 | 0.208964E+09 | 0.326725E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.185446E+09 | 73858251.45 | 0.111587E+09 | 0.110331E+09 | 0.525526E+09 |
February | 0.252944E+09 | 94250751.19 | 0.158693E+09 | 0.169961E+09 | 0.446993E+09 |
March | 0.290958E+09 | 57386715.51 | 0.233571E+09 | 0.186040E+09 | 0.402930E+09 |
April | 0.754324E+09 | 0.353674E+09 | 0.400650E+09 | 0.809410E+09 | 0.305551E+09 |
May | 0.820699E+09 | 0.357967E+09 | 0.462732E+09 | 0.854352E+09 | 0.272108E+09 |
June | 0.785919E+09 | 0.313959E+09 | 0.471960E+09 | 0.874099E+09 | 0.196117E+09 |
July | 0.828856E+09 | 0.352075E+09 | 0.476782E+09 | 0.962765E+09 | 0.184785E+09 |
August | 0.787372E+09 | 0.376942E+09 | 0.410430E+09 | 0.939457E+09 | 0.200615E+09 |
September | 0.684094E+09 | 0.363500E+09 | 0.320594E+09 | 0.790849E+09 | 0.256452E+09 |
October | 0.343823E+09 | 0.143781E+09 | 0.200042E+09 | 0.316530E+09 | 0.370673E+09 |
November | 0.172200E+09 | 58593481.72 | 0.113606E+09 | 0.102322E+09 | 0.448304E+09 |
December | 0.132354E+09 | 49526930.11 | 82827209.84 | 66896082.10 | 0.582002E+09 |
Annual Sum or Average | 0.603899E+10 | 0.259551E+10 | 0.344347E+10 | 0.618301E+10 | 0.419206E+10 |
Minimum of Months | 0.132354E+09 | 49526930.11 | 82827209.84 | 66896082.10 | 0.184785E+09 |
Maximum of Months | 0.828856E+09 | 0.376942E+09 | 0.476782E+09 | 0.962765E+09 | 0.582002E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 61885949.27 | 0.00 | 61885949.27 | 4039613.80 | 0.406543E+09 |
February | 87285522.53 | 0.00 | 87285522.53 | 11482499.86 | 0.340952E+09 |
March | 0.133742E+09 | 903.95 | 0.133741E+09 | 47601159.40 | 0.300855E+09 |
April | 0.211490E+09 | 1405613.30 | 0.210085E+09 | 0.147635E+09 | 0.228377E+09 |
May | 0.273229E+09 | 13933118.10 | 0.259296E+09 | 0.192194E+09 | 0.191424E+09 |
June | 0.291295E+09 | 18220742.68 | 0.273074E+09 | 0.264338E+09 | 0.139973E+09 |
July | 0.286198E+09 | 16832884.36 | 0.269365E+09 | 0.276968E+09 | 0.132405E+09 |
August | 0.225330E+09 | 4213909.69 | 0.221116E+09 | 0.213066E+09 | 0.149293E+09 |
September | 0.165399E+09 | 97755.85 | 0.165301E+09 | 0.132882E+09 | 0.200622E+09 |
October | 0.109433E+09 | 0.00 | 0.109433E+09 | 48677050.10 | 0.279378E+09 |
November | 63631907.44 | 0.00 | 63631907.44 | 6794641.58 | 0.341560E+09 |
December | 44777596.68 | 0.00 | 44777596.68 | 95379.25 | 0.447269E+09 |
Annual Sum or Average | 0.195370E+10 | 54704927.91 | 0.189899E+10 | 0.134577E+10 | 0.315865E+10 |
Minimum of Months | 44777596.68 | 0.00 | 44777596.68 | 95379.25 | 0.132405E+09 |
Maximum of Months | 0.291295E+09 | 18220742.68 | 0.273074E+09 | 0.276968E+09 | 0.447269E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 22813723.39 | 0.00 | 22813723.39 | 1489168.91 | 0.149869E+09 |
February | 32177057.81 | 0.00 | 32177057.81 | 4232924.90 | 0.125689E+09 |
March | 49302916.72 | 333.23 | 49302583.49 | 17547758.36 | 0.110908E+09 |
April | 77964135.71 | 518167.26 | 77445968.45 | 54424265.17 | 84189169.08 |
May | 0.100723E+09 | 5136324.26 | 95587169.75 | 70850614.81 | 70566636.21 |
June | 0.107383E+09 | 6716920.21 | 0.100666E+09 | 97445972.38 | 51599832.69 |
July | 0.105504E+09 | 6205298.17 | 99299092.38 | 0.102102E+09 | 48809909.25 |
August | 83065992.48 | 1553421.60 | 81512570.89 | 78545032.64 | 55035568.06 |
September | 60972753.66 | 36036.85 | 60936716.80 | 48985921.61 | 73957671.74 |
October | 40341565.27 | 0.00 | 40341565.27 | 17944376.23 | 0.102990E+09 |
November | 23457355.87 | 0.00 | 23457355.87 | 2504786.23 | 0.125913E+09 |
December | 16506876.23 | 0.00 | 16506876.23 | 35160.74 | 0.164882E+09 |
Annual Sum or Average | 0.720213E+09 | 20166501.58 | 0.700047E+09 | 0.496108E+09 | 0.116441E+10 |
Minimum of Months | 16506876.23 | 0.00 | 16506876.23 | 35160.74 | 48809909.25 |
Maximum of Months | 0.107383E+09 | 6716920.21 | 0.100666E+09 | 0.102102E+09 | 0.164882E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.130132E+09 | 84268280.43 | 45863564.89 | 0.131722E+09 | 0.131534E+09 |
February | 0.142627E+09 | 86927885.14 | 55699349.91 | 0.148286E+09 | 0.114751E+09 |
March | 97462209.09 | 28173040.24 | 69289168.85 | 81715551.93 | 0.106265E+09 |
April | 0.193347E+09 | 85671773.91 | 0.107675E+09 | 0.227264E+09 | 85517748.21 |
May | 0.167491E+09 | 54257392.42 | 0.113234E+09 | 0.181941E+09 | 77993661.15 |
June | 0.149624E+09 | 36186255.57 | 0.113438E+09 | 0.170563E+09 | 56496732.13 |
July | 0.166654E+09 | 51557967.26 | 0.115096E+09 | 0.204212E+09 | 53570600.74 |
August | 0.195737E+09 | 87699320.48 | 0.108038E+09 | 0.252038E+09 | 58014249.49 |
September | 0.227001E+09 | 0.133978E+09 | 93023788.67 | 0.288026E+09 | 72383581.85 |
October | 0.156518E+09 | 90236746.51 | 66281111.23 | 0.177259E+09 | 98211325.70 |
November | 0.109382E+09 | 66517073.52 | 42864484.41 | 0.111518E+09 | 0.116147E+09 |
December | 89692753.44 | 57513463.20 | 32179290.24 | 87432658.59 | 0.151363E+09 |
Annual Sum or Average | 0.182567E+10 | 0.862987E+09 | 0.962682E+09 | 0.206198E+10 | 0.112225E+10 |
Minimum of Months | 89692753.44 | 28173040.24 | 32179290.24 | 81715551.93 | 53570600.74 |
Maximum of Months | 0.227001E+09 | 0.133978E+09 | 0.115096E+09 | 0.288026E+09 | 0.151363E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.353204E+09 | 0.228721E+09 | 0.124483E+09 | 0.357520E+09 | 0.357009E+09 |
February | 0.387119E+09 | 0.235940E+09 | 0.151179E+09 | 0.402479E+09 | 0.311458E+09 |
March | 0.264532E+09 | 76467393.88 | 0.188065E+09 | 0.221793E+09 | 0.288426E+09 |
April | 0.524783E+09 | 0.232531E+09 | 0.292252E+09 | 0.616840E+09 | 0.232113E+09 |
May | 0.454606E+09 | 0.147266E+09 | 0.307340E+09 | 0.493826E+09 | 0.211691E+09 |
June | 0.406111E+09 | 98216899.36 | 0.307894E+09 | 0.462942E+09 | 0.153344E+09 |
July | 0.452334E+09 | 0.139939E+09 | 0.312395E+09 | 0.554274E+09 | 0.145402E+09 |
August | 0.531270E+09 | 0.238034E+09 | 0.293237E+09 | 0.684083E+09 | 0.157463E+09 |
September | 0.616128E+09 | 0.363643E+09 | 0.252486E+09 | 0.781762E+09 | 0.196464E+09 |
October | 0.424821E+09 | 0.244921E+09 | 0.179900E+09 | 0.481116E+09 | 0.266566E+09 |
November | 0.296884E+09 | 0.180541E+09 | 0.116343E+09 | 0.302683E+09 | 0.315246E+09 |
December | 0.243444E+09 | 0.156103E+09 | 87341175.83 | 0.237310E+09 | 0.410829E+09 |
Annual Sum or Average | 0.495524E+10 | 0.234232E+10 | 0.261292E+10 | 0.559663E+10 | 0.304601E+10 |
Minimum of Months | 0.243444E+09 | 76467393.88 | 87341175.83 | 0.221793E+09 | 0.145402E+09 |
Maximum of Months | 0.616128E+09 | 0.363643E+09 | 0.312395E+09 | 0.781762E+09 | 0.410829E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.278896E+09 | 0.180602E+09 | 98293958.39 | 0.283642E+09 | 0.265494E+09 |
February | 0.305676E+09 | 0.186302E+09 | 0.119374E+09 | 0.316360E+09 | 0.234999E+09 |
March | 0.208879E+09 | 60379947.61 | 0.148499E+09 | 0.176046E+09 | 0.216126E+09 |
April | 0.414378E+09 | 0.183610E+09 | 0.230767E+09 | 0.476387E+09 | 0.176100E+09 |
May | 0.358964E+09 | 0.116283E+09 | 0.242681E+09 | 0.379905E+09 | 0.158432E+09 |
June | 0.320672E+09 | 77553725.01 | 0.243119E+09 | 0.355465E+09 | 0.111702E+09 |
July | 0.357170E+09 | 0.110498E+09 | 0.246672E+09 | 0.428231E+09 | 0.103841E+09 |
August | 0.419500E+09 | 0.187956E+09 | 0.231545E+09 | 0.531780E+09 | 0.111238E+09 |
September | 0.486505E+09 | 0.287138E+09 | 0.199367E+09 | 0.609792E+09 | 0.142403E+09 |
October | 0.335446E+09 | 0.193394E+09 | 0.142052E+09 | 0.376717E+09 | 0.197669E+09 |
November | 0.234425E+09 | 0.142558E+09 | 91866383.63 | 0.238976E+09 | 0.233896E+09 |
December | 0.192228E+09 | 0.123262E+09 | 68966069.76 | 0.189578E+09 | 0.301954E+09 |
Annual Sum or Average | 0.391274E+10 | 0.184954E+10 | 0.206320E+10 | 0.436288E+10 | 0.225385E+10 |
Minimum of Months | 0.192228E+09 | 60379947.61 | 68966069.76 | 0.176046E+09 | 0.103841E+09 |
Maximum of Months | 0.486505E+09 | 0.287138E+09 | 0.246672E+09 | 0.609792E+09 | 0.301954E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182828E+09 | 59922886.42 | 0.122905E+09 | 0.109890E+09 | 0.534765E+09 |
February | 0.292111E+09 | 0.124345E+09 | 0.167766E+09 | 0.228619E+09 | 0.460479E+09 |
March | 0.290934E+09 | 55944156.98 | 0.234990E+09 | 0.185113E+09 | 0.404606E+09 |
April | 0.663093E+09 | 0.262902E+09 | 0.400191E+09 | 0.688258E+09 | 0.319281E+09 |
May | 0.804054E+09 | 0.326982E+09 | 0.477072E+09 | 0.829895E+09 | 0.280340E+09 |
June | 0.840081E+09 | 0.345850E+09 | 0.494232E+09 | 0.943636E+09 | 0.199491E+09 |
July | 0.883552E+09 | 0.389198E+09 | 0.494354E+09 | 0.103933E+10 | 0.186095E+09 |
August | 0.743526E+09 | 0.322103E+09 | 0.421423E+09 | 0.880482E+09 | 0.202551E+09 |
September | 0.581449E+09 | 0.262824E+09 | 0.318624E+09 | 0.654374E+09 | 0.265241E+09 |
October | 0.320274E+09 | 0.116318E+09 | 0.203956E+09 | 0.282837E+09 | 0.377653E+09 |
November | 0.167220E+09 | 49338807.43 | 0.117881E+09 | 0.102147E+09 | 0.459979E+09 |
December | 96331508.60 | 19581694.53 | 76749814.07 | 33748008.84 | 0.600056E+09 |
Annual Sum or Average | 0.586545E+10 | 0.233531E+10 | 0.353014E+10 | 0.597833E+10 | 0.429054E+10 |
Minimum of Months | 96331508.60 | 19581694.53 | 76749814.07 | 33748008.84 | 0.186095E+09 |
Maximum of Months | 0.883552E+09 | 0.389198E+09 | 0.494354E+09 | 0.103933E+10 | 0.600056E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 48866192.30 | 0.00 | 48866192.30 | 5085476.97 | 0.294422E+09 |
February | 68922124.97 | 0.00 | 68922124.97 | 12431540.03 | 0.251645E+09 |
March | 0.105605E+09 | 713.77 | 0.105604E+09 | 40902531.18 | 0.223217E+09 |
April | 0.166996E+09 | 1109896.04 | 0.165887E+09 | 0.111105E+09 | 0.171868E+09 |
May | 0.215746E+09 | 11001825.72 | 0.204744E+09 | 0.142688E+09 | 0.143131E+09 |
June | 0.230011E+09 | 14387406.61 | 0.215624E+09 | 0.195348E+09 | 0.104175E+09 |
July | 0.225987E+09 | 13291530.21 | 0.212695E+09 | 0.201852E+09 | 0.100164E+09 |
August | 0.177924E+09 | 3327374.37 | 0.174597E+09 | 0.157142E+09 | 0.112278E+09 |
September | 0.130601E+09 | 77189.67 | 0.130524E+09 | 0.102383E+09 | 0.146777E+09 |
October | 86410212.49 | 0.00 | 86410212.49 | 41440993.53 | 0.203472E+09 |
November | 50244830.41 | 0.00 | 50244830.41 | 7683003.60 | 0.247716E+09 |
December | 35357147.73 | 0.00 | 35357147.73 | 521467.57 | 0.322076E+09 |
Annual Sum or Average | 0.154267E+10 | 43195936.38 | 0.149948E+10 | 0.101858E+10 | 0.232094E+10 |
Minimum of Months | 35357147.73 | 0.00 | 35357147.73 | 521467.57 | 0.100164E+09 |
Maximum of Months | 0.230011E+09 | 14387406.61 | 0.215624E+09 | 0.201852E+09 | 0.322076E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182828E+09 | 59922886.42 | 0.122905E+09 | 0.117427E+09 | 0.528219E+09 |
February | 0.292111E+09 | 0.124345E+09 | 0.167766E+09 | 0.238098E+09 | 0.453938E+09 |
March | 0.290934E+09 | 55944156.98 | 0.234990E+09 | 0.190471E+09 | 0.401665E+09 |
April | 0.663093E+09 | 0.262902E+09 | 0.400191E+09 | 0.696960E+09 | 0.317136E+09 |
May | 0.804054E+09 | 0.326982E+09 | 0.477072E+09 | 0.831019E+09 | 0.281235E+09 |
June | 0.840081E+09 | 0.345850E+09 | 0.494232E+09 | 0.936270E+09 | 0.203891E+09 |
July | 0.883552E+09 | 0.389198E+09 | 0.494354E+09 | 0.102172E+10 | 0.195625E+09 |
August | 0.743526E+09 | 0.322103E+09 | 0.421423E+09 | 0.870645E+09 | 0.213477E+09 |
September | 0.581449E+09 | 0.262824E+09 | 0.318624E+09 | 0.659267E+09 | 0.266682E+09 |
October | 0.320274E+09 | 0.116318E+09 | 0.203956E+09 | 0.293119E+09 | 0.372152E+09 |
November | 0.167220E+09 | 49338807.43 | 0.117881E+09 | 0.108995E+09 | 0.453918E+09 |
December | 96331508.60 | 19581694.53 | 76749814.07 | 37025410.85 | 0.594971E+09 |
Annual Sum or Average | 0.586545E+10 | 0.233531E+10 | 0.353014E+10 | 0.600102E+10 | 0.428291E+10 |
Minimum of Months | 96331508.60 | 19581694.53 | 76749814.07 | 37025410.85 | 0.195625E+09 |
Maximum of Months | 0.883552E+09 | 0.389198E+09 | 0.494354E+09 | 0.102172E+10 | 0.594971E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.409028E+09 | 0.264871E+09 | 0.144158E+09 | 0.402514E+09 | 0.405693E+09 |
February | 0.448303E+09 | 0.273230E+09 | 0.175073E+09 | 0.453023E+09 | 0.357875E+09 |
March | 0.306341E+09 | 88552987.85 | 0.217788E+09 | 0.248877E+09 | 0.326635E+09 |
April | 0.607724E+09 | 0.269282E+09 | 0.338442E+09 | 0.693158E+09 | 0.260722E+09 |
May | 0.526456E+09 | 0.170541E+09 | 0.355915E+09 | 0.555950E+09 | 0.232219E+09 |
June | 0.470297E+09 | 0.113740E+09 | 0.356557E+09 | 0.525275E+09 | 0.161286E+09 |
July | 0.523825E+09 | 0.162056E+09 | 0.361769E+09 | 0.632254E+09 | 0.149391E+09 |
August | 0.615237E+09 | 0.275655E+09 | 0.339582E+09 | 0.780280E+09 | 0.161652E+09 |
September | 0.713507E+09 | 0.421116E+09 | 0.292391E+09 | 0.888543E+09 | 0.211513E+09 |
October | 0.491964E+09 | 0.283631E+09 | 0.208334E+09 | 0.542757E+09 | 0.300588E+09 |
November | 0.343806E+09 | 0.209075E+09 | 0.134731E+09 | 0.340233E+09 | 0.359103E+09 |
December | 0.281921E+09 | 0.180775E+09 | 0.101145E+09 | 0.268908E+09 | 0.462182E+09 |
Annual Sum or Average | 0.573841E+10 | 0.271252E+10 | 0.302588E+10 | 0.633177E+10 | 0.338886E+10 |
Minimum of Months | 0.281921E+09 | 88552987.85 | 0.101145E+09 | 0.248877E+09 | 0.149391E+09 |
Maximum of Months | 0.713507E+09 | 0.421116E+09 | 0.361769E+09 | 0.888543E+09 | 0.462182E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.342050E+09 | 0.00 | 0.342050E+09 | 9455874.25 | 0.254062E+10 |
February | 0.482437E+09 | 0.00 | 0.482437E+09 | 32102311.62 | 0.215352E+10 |
March | 0.739208E+09 | 4996.21 | 0.739203E+09 | 0.183398E+09 | 0.192456E+10 |
April | 0.116893E+10 | 7768978.00 | 0.116116E+10 | 0.689040E+09 | 0.141412E+10 |
May | 0.151017E+10 | 77009863.32 | 0.143316E+10 | 0.891381E+09 | 0.119282E+10 |
June | 0.161002E+10 | 0.100708E+09 | 0.150931E+10 | 0.129650E+10 | 0.865057E+09 |
July | 0.158185E+10 | 93037187.73 | 0.148881E+10 | 0.137846E+10 | 0.809572E+09 |
August | 0.124542E+10 | 23290738.43 | 0.122213E+10 | 0.106174E+10 | 0.903023E+09 |
September | 0.914176E+09 | 540307.24 | 0.913636E+09 | 0.647813E+09 | 0.121635E+10 |
October | 0.604849E+09 | 0.00 | 0.604849E+09 | 0.203490E+09 | 0.178238E+10 |
November | 0.351700E+09 | 0.00 | 0.351700E+09 | 16402434.74 | 0.220008E+10 |
December | 0.247491E+09 | 0.00 | 0.247491E+09 | 0.00 | 0.281037E+10 |
Annual Sum or Average | 0.107983E+11 | 0.302360E+09 | 0.104959E+11 | 0.640978E+10 | 0.198125E+11 |
Minimum of Months | 0.247491E+09 | 0.00 | 0.247491E+09 | 0.00 | 0.809572E+09 |
Maximum of Months | 0.161002E+10 | 0.100708E+09 | 0.150931E+10 | 0.137846E+10 | 0.281037E+10 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.342050E+09 | 0.00 | 0.342050E+09 | 6637175.98 | 0.261884E+10 |
February | 0.482437E+09 | 0.00 | 0.482437E+09 | 25198717.88 | 0.222008E+10 |
March | 0.739208E+09 | 4996.21 | 0.739203E+09 | 0.162898E+09 | 0.198122E+10 |
April | 0.116893E+10 | 7768978.00 | 0.116116E+10 | 0.660832E+09 | 0.144609E+10 |
May | 0.151017E+10 | 77009863.32 | 0.143316E+10 | 0.856919E+09 | 0.121871E+10 |
June | 0.161002E+10 | 0.100708E+09 | 0.150931E+10 | 0.126514E+10 | 0.883707E+09 |
July | 0.158185E+10 | 93037187.73 | 0.148881E+10 | 0.134863E+10 | 0.827098E+09 |
August | 0.124542E+10 | 23290738.43 | 0.122213E+10 | 0.103488E+10 | 0.924340E+09 |
September | 0.914176E+09 | 540307.24 | 0.913636E+09 | 0.623499E+09 | 0.124466E+10 |
October | 0.604849E+09 | 0.00 | 0.604849E+09 | 0.184490E+09 | 0.183492E+10 |
November | 0.351700E+09 | 0.00 | 0.351700E+09 | 11836012.33 | 0.227304E+10 |
December | 0.247491E+09 | 0.00 | 0.247491E+09 | 0.00 | 0.289640E+10 |
Annual Sum or Average | 0.107983E+11 | 0.302360E+09 | 0.104959E+11 | 0.618096E+10 | 0.203691E+11 |
Minimum of Months | 0.247491E+09 | 0.00 | 0.247491E+09 | 0.00 | 0.827098E+09 |
Maximum of Months | 0.161002E+10 | 0.100708E+09 | 0.150931E+10 | 0.134863E+10 | 0.289640E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 48866192.30 | 0.00 | 48866192.30 | 8311211.82 | 0.296162E+09 |
February | 68922124.97 | 0.00 | 68922124.97 | 16823124.82 | 0.255657E+09 |
March | 0.105605E+09 | 713.77 | 0.105604E+09 | 54051200.24 | 0.228114E+09 |
April | 0.166996E+09 | 1109896.04 | 0.165887E+09 | 0.146283E+09 | 0.178125E+09 |
May | 0.215746E+09 | 11001825.72 | 0.204744E+09 | 0.185253E+09 | 0.159230E+09 |
June | 0.230011E+09 | 14387406.61 | 0.215624E+09 | 0.250239E+09 | 0.117745E+09 |
July | 0.225987E+09 | 13291530.21 | 0.212695E+09 | 0.267465E+09 | 0.111540E+09 |
August | 0.177924E+09 | 3327374.37 | 0.174597E+09 | 0.214157E+09 | 0.118208E+09 |
September | 0.130601E+09 | 77189.67 | 0.130524E+09 | 0.138708E+09 | 0.150848E+09 |
October | 86410212.49 | 0.00 | 86410212.49 | 56841928.86 | 0.211311E+09 |
November | 50244830.41 | 0.00 | 50244830.41 | 11891271.83 | 0.255647E+09 |
December | 35357147.73 | 0.00 | 35357147.73 | 1562969.38 | 0.334214E+09 |
Annual Sum or Average | 0.154267E+10 | 43195936.38 | 0.149948E+10 | 0.135159E+10 | 0.241680E+10 |
Minimum of Months | 35357147.73 | 0.00 | 35357147.73 | 1562969.38 | 0.111540E+09 |
Maximum of Months | 0.230011E+09 | 14387406.61 | 0.215624E+09 | 0.267465E+09 | 0.334214E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.370865E+09 | 0.147706E+09 | 0.223159E+09 | 0.251236E+09 | 0.105514E+10 |
February | 0.505852E+09 | 0.188488E+09 | 0.317364E+09 | 0.372970E+09 | 0.912906E+09 |
March | 0.581875E+09 | 0.114765E+09 | 0.467109E+09 | 0.437581E+09 | 0.824283E+09 |
April | 0.150854E+10 | 0.707297E+09 | 0.801243E+09 | 0.177819E+10 | 0.643153E+09 |
May | 0.164128E+10 | 0.715884E+09 | 0.925398E+09 | 0.187016E+10 | 0.603549E+09 |
June | 0.157173E+10 | 0.627874E+09 | 0.943852E+09 | 0.193889E+10 | 0.447081E+09 |
July | 0.165759E+10 | 0.704099E+09 | 0.953495E+09 | 0.214381E+10 | 0.420774E+09 |
August | 0.157463E+10 | 0.753831E+09 | 0.820802E+09 | 0.209125E+10 | 0.439609E+09 |
September | 0.136809E+10 | 0.726948E+09 | 0.641142E+09 | 0.174842E+10 | 0.542898E+09 |
October | 0.687597E+09 | 0.287541E+09 | 0.400056E+09 | 0.714477E+09 | 0.769024E+09 |
November | 0.344375E+09 | 0.117179E+09 | 0.227196E+09 | 0.233284E+09 | 0.921160E+09 |
December | 0.264689E+09 | 99046826.15 | 0.165643E+09 | 0.150517E+09 | 0.120526E+10 |
Annual Sum or Average | 0.120771E+11 | 0.519066E+10 | 0.688646E+10 | 0.137308E+11 | 0.878484E+10 |
Minimum of Months | 0.264689E+09 | 99046826.15 | 0.165643E+09 | 0.150517E+09 | 0.420774E+09 |
Maximum of Months | 0.165759E+10 | 0.753831E+09 | 0.953495E+09 | 0.214381E+10 | 0.120526E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.278896E+09 | 0.180602E+09 | 98293958.39 | 0.299353E+09 | 0.268048E+09 |
February | 0.305676E+09 | 0.186302E+09 | 0.119374E+09 | 0.334940E+09 | 0.239750E+09 |
March | 0.208879E+09 | 60379947.61 | 0.148499E+09 | 0.196814E+09 | 0.222423E+09 |
April | 0.414378E+09 | 0.183610E+09 | 0.230767E+09 | 0.521263E+09 | 0.181435E+09 |
May | 0.358964E+09 | 0.116283E+09 | 0.242681E+09 | 0.425178E+09 | 0.172534E+09 |
June | 0.320672E+09 | 77553725.01 | 0.243119E+09 | 0.407979E+09 | 0.125914E+09 |
July | 0.357170E+09 | 0.110498E+09 | 0.246672E+09 | 0.486596E+09 | 0.118587E+09 |
August | 0.419500E+09 | 0.187956E+09 | 0.231545E+09 | 0.588161E+09 | 0.122762E+09 |
September | 0.486505E+09 | 0.287138E+09 | 0.199367E+09 | 0.657588E+09 | 0.149761E+09 |
October | 0.335446E+09 | 0.193394E+09 | 0.142052E+09 | 0.405403E+09 | 0.205620E+09 |
November | 0.234425E+09 | 0.142558E+09 | 91866383.63 | 0.252683E+09 | 0.241589E+09 |
December | 0.192228E+09 | 0.123262E+09 | 68966069.76 | 0.197219E+09 | 0.314553E+09 |
Annual Sum or Average | 0.391274E+10 | 0.184954E+10 | 0.206320E+10 | 0.477318E+10 | 0.236298E+10 |
Minimum of Months | 0.192228E+09 | 60379947.61 | 68966069.76 | 0.196814E+09 | 0.118587E+09 |
Maximum of Months | 0.486505E+09 | 0.287138E+09 | 0.246672E+09 | 0.657588E+09 | 0.314553E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 61885949.27 | 0.00 | 61885949.27 | 3157321.19 | 0.412756E+09 |
February | 87285522.53 | 0.00 | 87285522.53 | 9295599.55 | 0.347227E+09 |
March | 0.133742E+09 | 903.95 | 0.133741E+09 | 43747420.13 | 0.305615E+09 |
April | 0.211490E+09 | 1405613.30 | 0.210085E+09 | 0.137940E+09 | 0.230631E+09 |
May | 0.273229E+09 | 13933118.10 | 0.259296E+09 | 0.181461E+09 | 0.193297E+09 |
June | 0.291295E+09 | 18220742.68 | 0.273074E+09 | 0.251769E+09 | 0.143002E+09 |
July | 0.286198E+09 | 16832884.36 | 0.269365E+09 | 0.263903E+09 | 0.135265E+09 |
August | 0.225330E+09 | 4213909.69 | 0.221116E+09 | 0.202814E+09 | 0.151127E+09 |
September | 0.165399E+09 | 97755.85 | 0.165301E+09 | 0.126042E+09 | 0.200745E+09 |
October | 0.109433E+09 | 0.00 | 0.109433E+09 | 44953029.39 | 0.281755E+09 |
November | 63631907.44 | 0.00 | 63631907.44 | 5452523.21 | 0.348598E+09 |
December | 44777596.68 | 0.00 | 44777596.68 | 32609.58 | 0.455290E+09 |
Annual Sum or Average | 0.195370E+10 | 54704927.91 | 0.189899E+10 | 0.127057E+10 | 0.320531E+10 |
Minimum of Months | 44777596.68 | 0.00 | 44777596.68 | 32609.58 | 0.135265E+09 |
Maximum of Months | 0.291295E+09 | 18220742.68 | 0.273074E+09 | 0.263903E+09 | 0.455290E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 55369593.29 | 0.00 | 55369593.29 | 2824867.23 | 0.369226E+09 |
February | 78094687.73 | 0.00 | 78094687.73 | 8316808.14 | 0.310664E+09 |
March | 0.119660E+09 | 808.76 | 0.119659E+09 | 39140982.55 | 0.273435E+09 |
April | 0.189221E+09 | 1257607.54 | 0.187964E+09 | 0.123415E+09 | 0.206346E+09 |
May | 0.244459E+09 | 12466013.55 | 0.231993E+09 | 0.162354E+09 | 0.172943E+09 |
June | 0.260622E+09 | 16302167.51 | 0.244320E+09 | 0.225258E+09 | 0.127945E+09 |
July | 0.256062E+09 | 15060445.42 | 0.241002E+09 | 0.236115E+09 | 0.121022E+09 |
August | 0.201604E+09 | 3770200.96 | 0.197833E+09 | 0.181459E+09 | 0.135214E+09 |
September | 0.147983E+09 | 87462.53 | 0.147895E+09 | 0.112770E+09 | 0.179607E+09 |
October | 97910193.05 | 0.00 | 97910193.05 | 40219645.72 | 0.252087E+09 |
November | 56931708.69 | 0.00 | 56931708.69 | 4878393.17 | 0.311873E+09 |
December | 40062685.41 | 0.00 | 40062685.41 | 29175.92 | 0.407303E+09 |
Annual Sum or Average | 0.174798E+10 | 48944706.28 | 0.169904E+10 | 0.113678E+10 | 0.286767E+10 |
Minimum of Months | 40062685.41 | 0.00 | 40062685.41 | 29175.92 | 0.121022E+09 |
Maximum of Months | 0.260622E+09 | 16302167.51 | 0.244320E+09 | 0.236115E+09 | 0.407303E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.104120E+10 | 0.674242E+09 | 0.366961E+09 | 0.104109E+10 | 0.106619E+10 |
February | 0.114118E+10 | 0.695522E+09 | 0.445658E+09 | 0.117043E+10 | 0.933543E+09 |
March | 0.779808E+09 | 0.225416E+09 | 0.554392E+09 | 0.637340E+09 | 0.864212E+09 |
April | 0.154699E+10 | 0.685472E+09 | 0.861523E+09 | 0.178589E+10 | 0.692314E+09 |
May | 0.134012E+10 | 0.434121E+09 | 0.906000E+09 | 0.142300E+10 | 0.632741E+09 |
June | 0.119717E+10 | 0.289531E+09 | 0.907634E+09 | 0.132790E+10 | 0.463668E+09 |
July | 0.133342E+10 | 0.412522E+09 | 0.920901E+09 | 0.159465E+10 | 0.439760E+09 |
August | 0.156612E+10 | 0.701694E+09 | 0.864425E+09 | 0.198245E+10 | 0.471028E+09 |
September | 0.181627E+10 | 0.107197E+10 | 0.744296E+09 | 0.227772E+10 | 0.581188E+09 |
October | 0.125232E+10 | 0.721997E+09 | 0.530324E+09 | 0.140175E+10 | 0.794254E+09 |
November | 0.875177E+09 | 0.532212E+09 | 0.342965E+09 | 0.879679E+09 | 0.948537E+09 |
December | 0.717644E+09 | 0.460173E+09 | 0.257471E+09 | 0.690961E+09 | 0.123418E+10 |
Annual Sum or Average | 0.146074E+11 | 0.690488E+10 | 0.770255E+10 | 0.162129E+11 | 0.912161E+10 |
Minimum of Months | 0.717644E+09 | 0.225416E+09 | 0.257471E+09 | 0.637340E+09 | 0.439760E+09 |
Maximum of Months | 0.181627E+10 | 0.107197E+10 | 0.920901E+09 | 0.227772E+10 | 0.123418E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 525.59 | 509.43 | 526.65 | 341.04 | 185.61 | 0.00 | 0.00 |
February | 654.63 | 492.25 | 639.06 | 389.50 | 249.57 | 0.00 | 0.00 |
March | 329.91 | 410.27 | 394.43 | 114.02 | 280.42 | 0.00 | 0.00 |
April | 933.13 | 340.48 | 808.56 | 358.28 | 450.29 | 0.00 | 0.00 |
May | 732.11 | 289.81 | 677.84 | 219.58 | 458.26 | 0.00 | 0.00 |
June | 712.59 | 212.84 | 625.72 | 151.33 | 474.39 | 0.00 | 0.00 |
July | 821.65 | 195.78 | 674.45 | 208.66 | 465.80 | 0.00 | 0.00 |
August | 1006.80 | 215.95 | 792.15 | 354.92 | 437.23 | 0.00 | 0.00 |
September | 1185.15 | 283.97 | 949.31 | 560.29 | 389.02 | 0.00 | 0.00 |
October | 704.76 | 378.27 | 633.43 | 365.19 | 268.24 | 0.00 | 0.00 |
November | 460.38 | 463.24 | 457.43 | 278.17 | 179.26 | 0.00 | 0.00 |
December | 351.60 | 574.67 | 362.99 | 232.76 | 130.23 | 0.00 | 0.00 |
Annual Sum or Average | 700.58 | 363.28 | 627.52 | 296.63 | 330.89 | 0.00 | 0.00 |
Minimum of Months | 329.91 | 195.78 | 362.99 | 114.02 | 130.23 | 0.00 | 0.00 |
Maximum of Months | 1185.15 | 574.67 | 949.31 | 560.29 | 474.39 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1462.75 | 1478.82 | 1483.01 | 960.34 | 522.67 | 0.00 | 0.00 |
February | 1823.01 | 1433.90 | 1799.56 | 1096.79 | 702.77 | 0.00 | 0.00 |
March | 910.42 | 1196.85 | 1110.70 | 321.07 | 789.63 | 0.00 | 0.00 |
April | 2596.17 | 1016.82 | 2276.87 | 1008.88 | 1267.98 | 0.00 | 0.00 |
May | 2028.25 | 872.74 | 1908.76 | 618.33 | 1290.43 | 0.00 | 0.00 |
June | 1968.42 | 655.26 | 1761.98 | 426.13 | 1335.85 | 0.00 | 0.00 |
July | 2275.56 | 604.51 | 1899.22 | 587.57 | 1311.65 | 0.00 | 0.00 |
August | 2799.27 | 670.65 | 2230.66 | 999.44 | 1231.21 | 0.00 | 0.00 |
September | 3303.77 | 867.18 | 2673.19 | 1577.74 | 1095.45 | 0.00 | 0.00 |
October | 1962.18 | 1127.88 | 1783.71 | 1028.36 | 755.35 | 0.00 | 0.00 |
November | 1280.41 | 1358.51 | 1288.09 | 783.31 | 504.77 | 0.00 | 0.00 |
December | 978.76 | 1661.17 | 1022.16 | 655.44 | 366.72 | 0.00 | 0.00 |
Annual Sum or Average | 1946.41 | 1076.91 | 1767.06 | 835.28 | 931.77 | 0.00 | 0.00 |
Minimum of Months | 910.42 | 604.51 | 1022.16 | 321.07 | 366.72 | 0.00 | 0.00 |
Maximum of Months | 3303.77 | 1661.17 | 2673.19 | 1577.74 | 1335.85 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1919.41 | 2047.87 | 1926.52 | 1247.54 | 678.98 | 0.00 | 0.00 |
February | 2395.96 | 1977.32 | 2337.73 | 1424.80 | 912.94 | 0.00 | 0.00 |
March | 1182.49 | 1675.90 | 1442.86 | 417.08 | 1025.78 | 0.00 | 0.00 |
April | 3427.46 | 1398.59 | 2957.78 | 1310.59 | 1647.18 | 0.00 | 0.00 |
May | 2666.08 | 1215.43 | 2479.59 | 803.25 | 1676.34 | 0.00 | 0.00 |
June | 2579.53 | 918.46 | 2288.91 | 553.57 | 1735.34 | 0.00 | 0.00 |
July | 2991.37 | 843.12 | 2467.19 | 763.28 | 1703.91 | 0.00 | 0.00 |
August | 3694.76 | 921.87 | 2897.75 | 1298.33 | 1599.42 | 0.00 | 0.00 |
September | 4361.90 | 1183.09 | 3472.62 | 2049.57 | 1423.05 | 0.00 | 0.00 |
October | 2581.57 | 1570.23 | 2317.14 | 1335.90 | 981.24 | 0.00 | 0.00 |
November | 1677.25 | 1893.95 | 1673.30 | 1017.57 | 655.73 | 0.00 | 0.00 |
December | 1279.53 | 2304.51 | 1327.84 | 851.45 | 476.39 | 0.00 | 0.00 |
Annual Sum or Average | 2559.57 | 1493.52 | 2295.51 | 1085.08 | 1210.43 | 0.00 | 0.00 |
Minimum of Months | 1182.49 | 843.12 | 1327.84 | 417.08 | 476.39 | 0.00 | 0.00 |
Maximum of Months | 4361.90 | 2304.51 | 3472.62 | 2049.57 | 1735.34 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 136.78 | 293.78 | 172.39 | 89.80 | 82.59 | 0.00 | 0.00 |
February | 220.37 | 285.57 | 247.10 | 128.41 | 118.69 | 0.00 | 0.00 |
March | 132.75 | 232.89 | 186.61 | 43.43 | 143.18 | 0.00 | 0.00 |
April | 450.98 | 190.49 | 415.69 | 172.27 | 243.43 | 0.00 | 0.00 |
May | 453.58 | 161.78 | 434.22 | 165.50 | 268.72 | 0.00 | 0.00 |
June | 505.13 | 119.31 | 447.82 | 163.35 | 284.47 | 0.00 | 0.00 |
July | 551.70 | 107.54 | 463.23 | 186.57 | 276.67 | 0.00 | 0.00 |
August | 530.51 | 117.47 | 434.22 | 190.43 | 243.79 | 0.00 | 0.00 |
September | 489.01 | 157.47 | 412.02 | 212.18 | 199.84 | 0.00 | 0.00 |
October | 244.37 | 215.50 | 244.82 | 115.63 | 129.18 | 0.00 | 0.00 |
November | 125.94 | 266.10 | 154.96 | 74.03 | 80.92 | 0.00 | 0.00 |
December | 74.53 | 332.11 | 107.74 | 53.33 | 54.40 | 0.00 | 0.00 |
Annual Sum or Average | 326.45 | 206.28 | 310.06 | 132.70 | 177.36 | 0.00 | 0.00 |
Minimum of Months | 74.53 | 107.54 | 107.74 | 43.43 | 54.40 | 0.00 | 0.00 |
Maximum of Months | 551.70 | 332.11 | 463.23 | 212.18 | 284.47 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 41.24 | 308.29 | 86.50 | 22.37 | 64.13 | 0.00 | 0.00 |
February | 99.93 | 292.26 | 149.24 | 51.40 | 97.84 | 0.00 | 0.00 |
March | 83.87 | 234.58 | 148.05 | 20.89 | 127.16 | 0.00 | 0.00 |
April | 313.49 | 188.41 | 320.25 | 101.86 | 218.39 | 0.00 | 0.00 |
May | 366.40 | 156.77 | 380.75 | 126.19 | 254.56 | 0.00 | 0.00 |
June | 440.80 | 116.55 | 412.84 | 138.98 | 273.86 | 0.00 | 0.00 |
July | 461.93 | 107.59 | 414.25 | 150.27 | 263.98 | 0.00 | 0.00 |
August | 387.60 | 119.82 | 344.03 | 121.50 | 222.53 | 0.00 | 0.00 |
September | 294.63 | 159.15 | 274.71 | 101.43 | 173.28 | 0.00 | 0.00 |
October | 123.21 | 217.17 | 151.84 | 43.43 | 108.41 | 0.00 | 0.00 |
November | 42.62 | 273.33 | 83.90 | 19.04 | 64.86 | 0.00 | 0.00 |
December | 12.40 | 345.38 | 49.17 | 7.31 | 41.86 | 0.00 | 0.00 |
Annual Sum or Average | 222.80 | 209.55 | 234.91 | 75.42 | 159.49 | 0.00 | 0.00 |
Minimum of Months | 12.40 | 107.59 | 49.17 | 7.31 | 41.86 | 0.00 | 0.00 |
Maximum of Months | 461.93 | 345.38 | 414.25 | 150.27 | 273.86 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 76.90 | 104.44 | 83.29 | 53.93 | 29.35 | 0.00 | 0.00 |
February | 96.36 | 102.13 | 101.06 | 61.60 | 39.47 | 0.00 | 0.00 |
March | 44.68 | 84.67 | 62.38 | 18.03 | 44.35 | 0.00 | 0.00 |
April | 136.06 | 75.45 | 127.87 | 56.66 | 71.21 | 0.00 | 0.00 |
May | 102.21 | 67.81 | 107.20 | 34.73 | 72.47 | 0.00 | 0.00 |
June | 97.76 | 52.34 | 98.95 | 23.93 | 75.02 | 0.00 | 0.00 |
July | 115.94 | 48.34 | 106.66 | 33.00 | 73.66 | 0.00 | 0.00 |
August | 147.47 | 52.16 | 125.27 | 56.13 | 69.15 | 0.00 | 0.00 |
September | 177.03 | 65.22 | 150.13 | 88.61 | 61.52 | 0.00 | 0.00 |
October | 103.33 | 85.43 | 100.17 | 57.75 | 42.42 | 0.00 | 0.00 |
November | 66.87 | 100.04 | 72.34 | 43.99 | 28.35 | 0.00 | 0.00 |
December | 54.28 | 100.78 | 57.40 | 36.81 | 20.60 | 0.00 | 0.00 |
Annual Sum or Average | 101.42 | 78.09 | 99.24 | 46.91 | 52.33 | 0.00 | 0.00 |
Minimum of Months | 44.68 | 48.34 | 57.40 | 18.03 | 20.60 | 0.00 | 0.00 |
Maximum of Months | 177.03 | 104.44 | 150.13 | 88.61 | 75.02 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1.04 | 93.98 | 14.60 | 0.00 | 14.60 | 0.00 | 0.00 |
February | 3.26 | 87.52 | 22.79 | 0.00 | 22.79 | 0.00 | 0.00 |
March | 11.00 | 70.57 | 31.55 | 0.00 | 31.55 | 0.00 | 0.00 |
April | 36.57 | 53.36 | 51.55 | 0.34 | 51.21 | 0.00 | 0.00 |
May | 46.18 | 42.57 | 64.45 | 3.29 | 61.16 | 0.00 | 0.00 |
June | 65.65 | 31.12 | 71.00 | 4.44 | 66.56 | 0.00 | 0.00 |
July | 66.84 | 28.16 | 67.51 | 3.97 | 63.54 | 0.00 | 0.00 |
August | 52.07 | 31.42 | 53.15 | 0.99 | 52.16 | 0.00 | 0.00 |
September | 34.23 | 44.27 | 40.31 | 0.02 | 40.29 | 0.00 | 0.00 |
October | 12.02 | 63.90 | 25.81 | 0.00 | 25.81 | 0.00 | 0.00 |
November | 1.74 | 82.10 | 15.51 | 0.00 | 15.51 | 0.00 | 0.00 |
December | 0.03 | 103.32 | 10.56 | 0.00 | 10.56 | 0.00 | 0.00 |
Annual Sum or Average | 27.68 | 60.90 | 39.14 | 1.10 | 38.04 | 0.00 | 0.00 |
Minimum of Months | 0.03 | 28.16 | 10.56 | 0.00 | 10.56 | 0.00 | 0.00 |
Maximum of Months | 66.84 | 103.32 | 71.00 | 4.44 | 66.56 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 136.99 | 292.25 | 173.37 | 95.00 | 78.36 | 0.00 | 0.00 |
February | 193.63 | 281.41 | 230.91 | 115.97 | 114.94 | 0.00 | 0.00 |
March | 131.33 | 231.43 | 186.62 | 43.97 | 142.65 | 0.00 | 0.00 |
April | 488.63 | 182.94 | 450.89 | 207.29 | 243.60 | 0.00 | 0.00 |
May | 455.85 | 156.80 | 440.44 | 177.06 | 263.37 | 0.00 | 0.00 |
June | 473.92 | 115.40 | 426.93 | 151.05 | 275.88 | 0.00 | 0.00 |
July | 520.00 | 103.64 | 442.81 | 172.70 | 270.11 | 0.00 | 0.00 |
August | 548.04 | 112.11 | 450.59 | 210.91 | 239.69 | 0.00 | 0.00 |
September | 535.40 | 152.06 | 451.62 | 251.02 | 200.60 | 0.00 | 0.00 |
October | 253.95 | 213.65 | 253.61 | 125.89 | 127.72 | 0.00 | 0.00 |
November | 126.46 | 264.07 | 156.88 | 77.60 | 79.27 | 0.00 | 0.00 |
December | 90.55 | 330.14 | 121.19 | 64.51 | 56.67 | 0.00 | 0.00 |
Annual Sum or Average | 329.84 | 202.61 | 315.57 | 140.95 | 174.62 | 0.00 | 0.00 |
Minimum of Months | 90.55 | 103.64 | 121.19 | 43.97 | 56.67 | 0.00 | 0.00 |
Maximum of Months | 548.04 | 330.14 | 451.62 | 251.02 | 275.88 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 37.44 | 302.42 | 87.48 | 27.58 | 59.91 | 0.00 | 0.00 |
February | 70.35 | 284.96 | 133.05 | 38.96 | 94.09 | 0.00 | 0.00 |
March | 81.82 | 232.53 | 148.06 | 21.43 | 126.63 | 0.00 | 0.00 |
April | 350.63 | 180.95 | 355.45 | 136.88 | 218.57 | 0.00 | 0.00 |
May | 370.41 | 152.49 | 386.96 | 137.76 | 249.21 | 0.00 | 0.00 |
June | 413.17 | 113.63 | 391.95 | 126.68 | 265.27 | 0.00 | 0.00 |
July | 436.27 | 103.49 | 393.83 | 136.41 | 257.42 | 0.00 | 0.00 |
August | 409.29 | 114.20 | 360.40 | 141.98 | 218.42 | 0.00 | 0.00 |
September | 340.05 | 151.86 | 314.31 | 140.27 | 174.04 | 0.00 | 0.00 |
October | 129.90 | 212.72 | 160.63 | 53.68 | 106.95 | 0.00 | 0.00 |
November | 38.50 | 266.36 | 85.82 | 22.61 | 63.21 | 0.00 | 0.00 |
December | 20.34 | 334.53 | 62.62 | 18.49 | 44.12 | 0.00 | 0.00 |
Annual Sum or Average | 225.45 | 203.80 | 240.41 | 83.67 | 156.74 | 0.00 | 0.00 |
Minimum of Months | 20.34 | 103.49 | 62.62 | 18.49 | 44.12 | 0.00 | 0.00 |
Maximum of Months | 436.27 | 334.53 | 393.83 | 141.98 | 265.27 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 166.91 | 372.33 | 212.08 | 116.86 | 95.22 | 0.00 | 0.00 |
February | 224.76 | 359.67 | 268.36 | 133.46 | 134.90 | 0.00 | 0.00 |
March | 135.32 | 298.78 | 203.49 | 39.07 | 164.43 | 0.00 | 0.00 |
April | 403.22 | 242.74 | 388.73 | 123.51 | 265.22 | 0.00 | 0.00 |
May | 346.67 | 202.13 | 371.88 | 82.36 | 289.52 | 0.00 | 0.00 |
June | 380.28 | 151.16 | 368.22 | 61.47 | 306.74 | 0.00 | 0.00 |
July | 421.40 | 138.63 | 377.35 | 80.10 | 297.25 | 0.00 | 0.00 |
August | 457.36 | 155.71 | 386.58 | 123.77 | 262.81 | 0.00 | 0.00 |
September | 481.90 | 208.66 | 412.62 | 192.03 | 220.58 | 0.00 | 0.00 |
October | 267.50 | 275.77 | 272.97 | 125.13 | 147.83 | 0.00 | 0.00 |
November | 154.46 | 337.86 | 190.34 | 95.32 | 95.02 | 0.00 | 0.00 |
December | 108.11 | 425.26 | 147.26 | 79.76 | 67.50 | 0.00 | 0.00 |
Annual Sum or Average | 295.59 | 263.59 | 299.81 | 104.01 | 195.80 | 0.00 | 0.00 |
Minimum of Months | 108.11 | 138.63 | 147.26 | 39.07 | 67.50 | 0.00 | 0.00 |
Maximum of Months | 481.90 | 425.26 | 412.62 | 192.03 | 306.74 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 137.61 | 289.46 | 172.39 | 89.80 | 82.59 | 0.00 | 0.00 |
February | 220.57 | 282.78 | 247.10 | 128.41 | 118.69 | 0.00 | 0.00 |
March | 132.90 | 229.81 | 186.61 | 43.43 | 143.18 | 0.00 | 0.00 |
April | 447.16 | 188.95 | 415.69 | 172.27 | 243.43 | 0.00 | 0.00 |
May | 449.02 | 161.15 | 434.22 | 165.50 | 268.72 | 0.00 | 0.00 |
June | 499.93 | 118.79 | 447.82 | 163.35 | 284.47 | 0.00 | 0.00 |
July | 546.60 | 106.92 | 463.23 | 186.57 | 276.67 | 0.00 | 0.00 |
August | 526.31 | 116.19 | 434.22 | 190.43 | 243.79 | 0.00 | 0.00 |
September | 486.22 | 155.77 | 412.02 | 212.18 | 199.84 | 0.00 | 0.00 |
October | 243.94 | 212.49 | 244.82 | 115.63 | 129.18 | 0.00 | 0.00 |
November | 126.43 | 262.52 | 154.96 | 74.03 | 80.92 | 0.00 | 0.00 |
December | 75.13 | 328.52 | 107.74 | 53.33 | 54.40 | 0.00 | 0.00 |
Annual Sum or Average | 324.45 | 204.05 | 310.06 | 132.70 | 177.36 | 0.00 | 0.00 |
Minimum of Months | 75.13 | 106.92 | 107.74 | 43.43 | 54.40 | 0.00 | 0.00 |
Maximum of Months | 546.60 | 328.52 | 463.23 | 212.18 | 284.47 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 42.08 | 303.48 | 86.50 | 22.37 | 64.13 | 0.00 | 0.00 |
February | 100.65 | 288.75 | 149.24 | 51.40 | 97.84 | 0.00 | 0.00 |
March | 84.35 | 231.27 | 148.05 | 20.89 | 127.16 | 0.00 | 0.00 |
April | 310.01 | 186.91 | 320.25 | 101.86 | 218.39 | 0.00 | 0.00 |
May | 361.61 | 156.51 | 380.75 | 126.19 | 254.56 | 0.00 | 0.00 |
June | 434.62 | 116.89 | 412.84 | 138.98 | 273.86 | 0.00 | 0.00 |
July | 455.06 | 108.66 | 414.25 | 150.27 | 263.98 | 0.00 | 0.00 |
August | 382.49 | 120.38 | 344.03 | 121.50 | 222.53 | 0.00 | 0.00 |
September | 292.38 | 158.05 | 274.71 | 101.43 | 173.28 | 0.00 | 0.00 |
October | 123.56 | 213.56 | 151.84 | 43.43 | 108.41 | 0.00 | 0.00 |
November | 43.43 | 269.10 | 83.90 | 19.04 | 64.86 | 0.00 | 0.00 |
December | 12.84 | 341.21 | 49.17 | 7.31 | 41.86 | 0.00 | 0.00 |
Annual Sum or Average | 220.69 | 207.51 | 234.91 | 75.42 | 159.49 | 0.00 | 0.00 |
Minimum of Months | 12.84 | 108.66 | 49.17 | 7.31 | 41.86 | 0.00 | 0.00 |
Maximum of Months | 455.06 | 341.21 | 414.25 | 150.27 | 273.86 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 150.28 | 151.47 | 152.71 | 98.89 | 53.82 | 0.00 | 0.00 |
February | 187.26 | 147.93 | 185.31 | 112.94 | 72.37 | 0.00 | 0.00 |
March | 92.92 | 121.95 | 114.37 | 33.06 | 81.31 | 0.00 | 0.00 |
April | 267.42 | 100.59 | 234.46 | 103.89 | 130.57 | 0.00 | 0.00 |
May | 207.57 | 86.70 | 196.56 | 63.67 | 132.88 | 0.00 | 0.00 |
June | 202.65 | 62.22 | 181.44 | 43.88 | 137.56 | 0.00 | 0.00 |
July | 236.06 | 55.78 | 195.57 | 60.50 | 135.07 | 0.00 | 0.00 |
August | 291.32 | 60.35 | 229.70 | 102.92 | 126.79 | 0.00 | 0.00 |
September | 342.80 | 81.60 | 275.27 | 162.47 | 112.81 | 0.00 | 0.00 |
October | 202.64 | 112.23 | 183.68 | 105.90 | 77.78 | 0.00 | 0.00 |
November | 131.26 | 138.54 | 132.64 | 80.66 | 51.98 | 0.00 | 0.00 |
December | 100.40 | 172.56 | 105.26 | 67.49 | 37.76 | 0.00 | 0.00 |
Annual Sum or Average | 200.78 | 107.46 | 181.96 | 86.01 | 95.95 | 0.00 | 0.00 |
Minimum of Months | 92.92 | 55.78 | 105.26 | 33.06 | 37.76 | 0.00 | 0.00 |
Maximum of Months | 342.80 | 172.56 | 275.27 | 162.47 | 137.56 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3.53 | 948.56 | 127.71 | 0.00 | 127.71 | 0.00 | 0.00 |
February | 13.27 | 890.18 | 199.42 | 0.00 | 199.42 | 0.00 | 0.00 |
March | 68.47 | 718.55 | 275.99 | 0.00 | 275.99 | 0.00 | 0.00 |
April | 265.83 | 545.57 | 450.98 | 3.00 | 447.98 | 0.00 | 0.00 |
May | 332.80 | 445.35 | 563.83 | 28.75 | 535.08 | 0.00 | 0.00 |
June | 500.19 | 333.74 | 621.15 | 38.85 | 582.30 | 0.00 | 0.00 |
July | 514.66 | 302.26 | 590.59 | 34.74 | 555.86 | 0.00 | 0.00 |
August | 396.41 | 337.15 | 464.99 | 8.70 | 456.29 | 0.00 | 0.00 |
September | 249.93 | 469.27 | 352.69 | 0.21 | 352.48 | 0.00 | 0.00 |
October | 75.97 | 665.47 | 225.82 | 0.00 | 225.82 | 0.00 | 0.00 |
November | 6.33 | 848.80 | 135.69 | 0.00 | 135.69 | 0.00 | 0.00 |
December | 0.00 | 1049.27 | 92.40 | 0.00 | 92.40 | 0.00 | 0.00 |
Annual Sum or Average | 203.25 | 628.25 | 342.41 | 9.59 | 332.82 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 302.26 | 92.40 | 0.00 | 92.40 | 0.00 | 0.00 |
Maximum of Months | 514.66 | 1049.27 | 621.15 | 38.85 | 582.30 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2.48 | 977.76 | 127.71 | 0.00 | 127.71 | 0.00 | 0.00 |
February | 10.42 | 917.69 | 199.42 | 0.00 | 199.42 | 0.00 | 0.00 |
March | 60.82 | 739.70 | 275.99 | 0.00 | 275.99 | 0.00 | 0.00 |
April | 254.95 | 557.91 | 450.98 | 3.00 | 447.98 | 0.00 | 0.00 |
May | 319.94 | 455.01 | 563.83 | 28.75 | 535.08 | 0.00 | 0.00 |
June | 488.09 | 340.94 | 621.15 | 38.85 | 582.30 | 0.00 | 0.00 |
July | 503.52 | 308.80 | 590.59 | 34.74 | 555.86 | 0.00 | 0.00 |
August | 386.38 | 345.11 | 464.99 | 8.70 | 456.29 | 0.00 | 0.00 |
September | 240.55 | 480.19 | 352.69 | 0.21 | 352.48 | 0.00 | 0.00 |
October | 68.88 | 685.08 | 225.82 | 0.00 | 225.82 | 0.00 | 0.00 |
November | 4.57 | 876.94 | 135.69 | 0.00 | 135.69 | 0.00 | 0.00 |
December | 0.00 | 1081.39 | 92.40 | 0.00 | 92.40 | 0.00 | 0.00 |
Annual Sum or Average | 196.00 | 645.90 | 342.41 | 9.59 | 332.82 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 308.80 | 92.40 | 0.00 | 92.40 | 0.00 | 0.00 |
Maximum of Months | 503.52 | 1081.39 | 621.15 | 38.85 | 582.30 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 190.60 | 586.53 | 260.84 | 122.58 | 138.26 | 0.00 | 0.00 |
February | 290.49 | 573.05 | 363.94 | 154.92 | 209.02 | 0.00 | 0.00 |
March | 253.66 | 472.59 | 334.66 | 65.39 | 269.27 | 0.00 | 0.00 |
April | 937.77 | 381.05 | 806.29 | 344.14 | 462.15 | 0.00 | 0.00 |
May | 920.57 | 343.63 | 827.36 | 314.80 | 512.55 | 0.00 | 0.00 |
June | 998.74 | 263.26 | 818.83 | 277.71 | 541.12 | 0.00 | 0.00 |
July | 1079.07 | 240.15 | 836.60 | 309.10 | 527.50 | 0.00 | 0.00 |
August | 1077.85 | 251.62 | 810.95 | 352.86 | 458.09 | 0.00 | 0.00 |
September | 977.56 | 321.23 | 765.89 | 391.27 | 374.63 | 0.00 | 0.00 |
October | 436.19 | 439.64 | 414.22 | 179.56 | 234.66 | 0.00 | 0.00 |
November | 184.91 | 540.05 | 242.69 | 100.21 | 142.48 | 0.00 | 0.00 |
December | 120.27 | 682.08 | 183.79 | 83.00 | 100.79 | 0.00 | 0.00 |
Annual Sum or Average | 623.36 | 423.88 | 555.95 | 224.61 | 331.34 | 0.00 | 0.00 |
Minimum of Months | 120.27 | 240.15 | 183.79 | 65.39 | 100.79 | 0.00 | 0.00 |
Maximum of Months | 1079.07 | 682.08 | 836.60 | 391.27 | 541.12 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 363.69 | 662.78 | 432.52 | 251.73 | 180.79 | 0.00 | 0.00 |
February | 476.08 | 642.83 | 540.08 | 287.50 | 252.58 | 0.00 | 0.00 |
March | 265.10 | 535.05 | 385.76 | 84.16 | 301.60 | 0.00 | 0.00 |
April | 789.17 | 435.02 | 751.43 | 265.48 | 485.95 | 0.00 | 0.00 |
May | 653.00 | 366.33 | 693.63 | 171.94 | 521.69 | 0.00 | 0.00 |
June | 689.27 | 276.35 | 674.80 | 125.02 | 549.78 | 0.00 | 0.00 |
July | 775.78 | 253.59 | 700.30 | 165.93 | 534.37 | 0.00 | 0.00 |
August | 881.88 | 281.02 | 744.12 | 264.96 | 479.16 | 0.00 | 0.00 |
September | 969.40 | 369.48 | 821.62 | 413.64 | 407.98 | 0.00 | 0.00 |
October | 550.20 | 490.90 | 544.98 | 269.56 | 275.41 | 0.00 | 0.00 |
November | 329.47 | 606.86 | 384.16 | 205.33 | 178.83 | 0.00 | 0.00 |
December | 237.81 | 762.65 | 299.61 | 171.81 | 127.80 | 0.00 | 0.00 |
Annual Sum or Average | 581.37 | 472.75 | 580.58 | 222.24 | 358.34 | 0.00 | 0.00 |
Minimum of Months | 237.81 | 253.59 | 299.61 | 84.16 | 127.80 | 0.00 | 0.00 |
Maximum of Months | 969.40 | 762.65 | 821.62 | 413.64 | 549.78 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.140774E+10 | 0.136446E+10 | 0.141058E+10 | 0.913437E+09 | 0.497142E+09 | 0.00 | 0.00 |
February | 0.158368E+10 | 0.119085E+10 | 0.154602E+10 | 0.942266E+09 | 0.603757E+09 | 0.00 | 0.00 |
March | 0.883634E+09 | 0.109888E+10 | 0.105645E+10 | 0.305385E+09 | 0.751065E+09 | 0.00 | 0.00 |
April | 0.241868E+10 | 0.882537E+09 | 0.209580E+10 | 0.928651E+09 | 0.116715E+10 | 0.00 | 0.00 |
May | 0.196088E+10 | 0.776220E+09 | 0.181553E+10 | 0.588130E+09 | 0.122740E+10 | 0.00 | 0.00 |
June | 0.184704E+10 | 0.551681E+09 | 0.162186E+10 | 0.392246E+09 | 0.122962E+10 | 0.00 | 0.00 |
July | 0.220070E+10 | 0.524384E+09 | 0.180646E+10 | 0.558869E+09 | 0.124759E+10 | 0.00 | 0.00 |
August | 0.269660E+10 | 0.578409E+09 | 0.212171E+10 | 0.950629E+09 | 0.117108E+10 | 0.00 | 0.00 |
September | 0.307191E+10 | 0.736044E+09 | 0.246060E+10 | 0.145227E+10 | 0.100834E+10 | 0.00 | 0.00 |
October | 0.188764E+10 | 0.101315E+10 | 0.169659E+10 | 0.978133E+09 | 0.718459E+09 | 0.00 | 0.00 |
November | 0.119330E+10 | 0.120072E+10 | 0.118565E+10 | 0.721021E+09 | 0.464633E+09 | 0.00 | 0.00 |
December | 0.941729E+09 | 0.153921E+10 | 0.972235E+09 | 0.623425E+09 | 0.348810E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.220935E+11 | 0.114566E+11 | 0.197895E+11 | 0.935446E+10 | 0.104350E+11 | 0.00 | 0.00 |
Minimum of Months | 0.883634E+09 | 0.524384E+09 | 0.972235E+09 | 0.305385E+09 | 0.348810E+09 | 0.00 | 0.00 |
Maximum of Months | 0.307191E+10 | 0.153921E+10 | 0.246060E+10 | 0.145227E+10 | 0.124759E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.391784E+10 | 0.396088E+10 | 0.397210E+10 | 0.257218E+10 | 0.139992E+10 | 0.00 | 0.00 |
February | 0.441022E+10 | 0.346888E+10 | 0.435350E+10 | 0.265336E+10 | 0.170014E+10 | 0.00 | 0.00 |
March | 0.243847E+10 | 0.320565E+10 | 0.297490E+10 | 0.859945E+09 | 0.211495E+10 | 0.00 | 0.00 |
April | 0.672926E+10 | 0.263559E+10 | 0.590163E+10 | 0.261502E+10 | 0.328662E+10 | 0.00 | 0.00 |
May | 0.543245E+10 | 0.233754E+10 | 0.511242E+10 | 0.165614E+10 | 0.345628E+10 | 0.00 | 0.00 |
June | 0.510214E+10 | 0.169843E+10 | 0.456706E+10 | 0.110454E+10 | 0.346252E+10 | 0.00 | 0.00 |
July | 0.609487E+10 | 0.161912E+10 | 0.508687E+10 | 0.157374E+10 | 0.351313E+10 | 0.00 | 0.00 |
August | 0.749758E+10 | 0.179626E+10 | 0.597459E+10 | 0.267691E+10 | 0.329768E+10 | 0.00 | 0.00 |
September | 0.856338E+10 | 0.224773E+10 | 0.692890E+10 | 0.408949E+10 | 0.283941E+10 | 0.00 | 0.00 |
October | 0.525550E+10 | 0.302090E+10 | 0.477749E+10 | 0.275436E+10 | 0.202313E+10 | 0.00 | 0.00 |
November | 0.331881E+10 | 0.352127E+10 | 0.333872E+10 | 0.203035E+10 | 0.130838E+10 | 0.00 | 0.00 |
December | 0.262152E+10 | 0.444928E+10 | 0.273775E+10 | 0.175552E+10 | 0.982227E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.613820E+11 | 0.339615E+11 | 0.557259E+11 | 0.263415E+11 | 0.293844E+11 | 0.00 | 0.00 |
Minimum of Months | 0.243847E+10 | 0.161912E+10 | 0.273775E+10 | 0.859945E+09 | 0.982227E+09 | 0.00 | 0.00 |
Maximum of Months | 0.856338E+10 | 0.444928E+10 | 0.692890E+10 | 0.408949E+10 | 0.351313E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.514095E+10 | 0.548500E+10 | 0.515998E+10 | 0.334141E+10 | 0.181858E+10 | 0.00 | 0.00 |
February | 0.579629E+10 | 0.478352E+10 | 0.565545E+10 | 0.344687E+10 | 0.220858E+10 | 0.00 | 0.00 |
March | 0.316719E+10 | 0.448874E+10 | 0.386456E+10 | 0.111712E+10 | 0.274744E+10 | 0.00 | 0.00 |
April | 0.888398E+10 | 0.362514E+10 | 0.766656E+10 | 0.339706E+10 | 0.426950E+10 | 0.00 | 0.00 |
May | 0.714082E+10 | 0.325542E+10 | 0.664133E+10 | 0.215142E+10 | 0.448991E+10 | 0.00 | 0.00 |
June | 0.668614E+10 | 0.238064E+10 | 0.593287E+10 | 0.143486E+10 | 0.449801E+10 | 0.00 | 0.00 |
July | 0.801208E+10 | 0.225822E+10 | 0.660813E+10 | 0.204438E+10 | 0.456376E+10 | 0.00 | 0.00 |
August | 0.989604E+10 | 0.246915E+10 | 0.776133E+10 | 0.347745E+10 | 0.428388E+10 | 0.00 | 0.00 |
September | 0.113060E+11 | 0.306658E+10 | 0.900103E+10 | 0.531248E+10 | 0.368855E+10 | 0.00 | 0.00 |
October | 0.691448E+10 | 0.420570E+10 | 0.620623E+10 | 0.357807E+10 | 0.262816E+10 | 0.00 | 0.00 |
November | 0.434744E+10 | 0.490913E+10 | 0.433719E+10 | 0.263754E+10 | 0.169966E+10 | 0.00 | 0.00 |
December | 0.342708E+10 | 0.617239E+10 | 0.355649E+10 | 0.228052E+10 | 0.127597E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.807185E+11 | 0.470996E+11 | 0.723912E+11 | 0.342192E+11 | 0.381720E+11 | 0.00 | 0.00 |
Minimum of Months | 0.316719E+10 | 0.225822E+10 | 0.355649E+10 | 0.111712E+10 | 0.127597E+10 | 0.00 | 0.00 |
Maximum of Months | 0.113060E+11 | 0.617239E+10 | 0.900103E+10 | 0.531248E+10 | 0.456376E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.366353E+09 | 0.786873E+09 | 0.461724E+09 | 0.240525E+09 | 0.221199E+09 | 0.00 | 0.00 |
February | 0.533111E+09 | 0.690852E+09 | 0.597787E+09 | 0.310648E+09 | 0.287140E+09 | 0.00 | 0.00 |
March | 0.355548E+09 | 0.623782E+09 | 0.499814E+09 | 0.116324E+09 | 0.383489E+09 | 0.00 | 0.00 |
April | 0.116894E+10 | 0.493745E+09 | 0.107747E+10 | 0.446512E+09 | 0.630959E+09 | 0.00 | 0.00 |
May | 0.121486E+10 | 0.433314E+09 | 0.116302E+10 | 0.443266E+09 | 0.719753E+09 | 0.00 | 0.00 |
June | 0.130929E+10 | 0.309241E+09 | 0.116075E+10 | 0.423404E+09 | 0.737350E+09 | 0.00 | 0.00 |
July | 0.147767E+10 | 0.288042E+09 | 0.124072E+10 | 0.499696E+09 | 0.741026E+09 | 0.00 | 0.00 |
August | 0.142091E+10 | 0.314623E+09 | 0.116303E+10 | 0.510058E+09 | 0.652968E+09 | 0.00 | 0.00 |
September | 0.126750E+10 | 0.408166E+09 | 0.106795E+10 | 0.549963E+09 | 0.517991E+09 | 0.00 | 0.00 |
October | 0.654512E+09 | 0.577199E+09 | 0.655720E+09 | 0.309712E+09 | 0.346008E+09 | 0.00 | 0.00 |
November | 0.326448E+09 | 0.689743E+09 | 0.401645E+09 | 0.191897E+09 | 0.209748E+09 | 0.00 | 0.00 |
December | 0.199625E+09 | 0.889519E+09 | 0.288559E+09 | 0.142844E+09 | 0.145716E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.102948E+11 | 0.650510E+10 | 0.977819E+10 | 0.418485E+10 | 0.559335E+10 | 0.00 | 0.00 |
Minimum of Months | 0.199625E+09 | 0.288042E+09 | 0.288559E+09 | 0.116324E+09 | 0.145716E+09 | 0.00 | 0.00 |
Maximum of Months | 0.147767E+10 | 0.889519E+09 | 0.124072E+10 | 0.549963E+09 | 0.741026E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.110463E+09 | 0.825723E+09 | 0.231694E+09 | 59922886.42 | 0.171771E+09 | 0.00 | 0.00 |
February | 0.241751E+09 | 0.707039E+09 | 0.361033E+09 | 0.124345E+09 | 0.236688E+09 | 0.00 | 0.00 |
March | 0.224638E+09 | 0.628304E+09 | 0.396539E+09 | 55944870.75 | 0.340595E+09 | 0.00 | 0.00 |
April | 0.812576E+09 | 0.488369E+09 | 0.830090E+09 | 0.264012E+09 | 0.566078E+09 | 0.00 | 0.00 |
May | 0.981378E+09 | 0.419888E+09 | 0.101980E+10 | 0.337984E+09 | 0.681816E+09 | 0.00 | 0.00 |
June | 0.114254E+10 | 0.302086E+09 | 0.107009E+10 | 0.360237E+09 | 0.709855E+09 | 0.00 | 0.00 |
July | 0.123723E+10 | 0.288175E+09 | 0.110954E+10 | 0.402490E+09 | 0.707049E+09 | 0.00 | 0.00 |
August | 0.103816E+10 | 0.320932E+09 | 0.921450E+09 | 0.325430E+09 | 0.596020E+09 | 0.00 | 0.00 |
September | 0.763687E+09 | 0.412506E+09 | 0.712050E+09 | 0.262902E+09 | 0.449148E+09 | 0.00 | 0.00 |
October | 0.330007E+09 | 0.581673E+09 | 0.406684E+09 | 0.116318E+09 | 0.290366E+09 | 0.00 | 0.00 |
November | 0.110466E+09 | 0.708479E+09 | 0.217465E+09 | 49338807.43 | 0.168126E+09 | 0.00 | 0.00 |
December | 33216580.07 | 0.925072E+09 | 0.131689E+09 | 19581694.53 | 0.112107E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.702612E+10 | 0.660824E+10 | 0.740813E+10 | 0.237851E+10 | 0.502962E+10 | 0.00 | 0.00 |
Minimum of Months | 33216580.07 | 0.288175E+09 | 0.131689E+09 | 19581694.53 | 0.112107E+09 | 0.00 | 0.00 |
Maximum of Months | 0.123723E+10 | 0.925072E+09 | 0.110954E+10 | 0.402490E+09 | 0.709855E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.205972E+09 | 0.279727E+09 | 0.223073E+09 | 0.144453E+09 | 78619531.41 | 0.00 | 0.00 |
February | 0.233118E+09 | 0.247081E+09 | 0.244492E+09 | 0.149012E+09 | 95480078.80 | 0.00 | 0.00 |
March | 0.119672E+09 | 0.226785E+09 | 0.167070E+09 | 48294353.64 | 0.118776E+09 | 0.00 | 0.00 |
April | 0.352676E+09 | 0.195556E+09 | 0.331436E+09 | 0.146859E+09 | 0.184577E+09 | 0.00 | 0.00 |
May | 0.273757E+09 | 0.181615E+09 | 0.287114E+09 | 93008268.71 | 0.194106E+09 | 0.00 | 0.00 |
June | 0.253399E+09 | 0.135652E+09 | 0.256487E+09 | 62030643.78 | 0.194456E+09 | 0.00 | 0.00 |
July | 0.310529E+09 | 0.129480E+09 | 0.285680E+09 | 88380901.82 | 0.197299E+09 | 0.00 | 0.00 |
August | 0.394981E+09 | 0.139695E+09 | 0.335533E+09 | 0.150335E+09 | 0.185199E+09 | 0.00 | 0.00 |
September | 0.458874E+09 | 0.169042E+09 | 0.389127E+09 | 0.229665E+09 | 0.159462E+09 | 0.00 | 0.00 |
October | 0.276760E+09 | 0.228820E+09 | 0.268304E+09 | 0.154684E+09 | 0.113619E+09 | 0.00 | 0.00 |
November | 0.173335E+09 | 0.259297E+09 | 0.187502E+09 | 0.114024E+09 | 73478494.01 | 0.00 | 0.00 |
December | 0.145374E+09 | 0.269941E+09 | 0.153752E+09 | 98589840.04 | 55161885.59 | 0.00 | 0.00 |
Annual Sum or Average | 0.319845E+10 | 0.246269E+10 | 0.312957E+10 | 0.147934E+10 | 0.165023E+10 | 0.00 | 0.00 |
Minimum of Months | 0.119672E+09 | 0.129480E+09 | 0.153752E+09 | 48294353.64 | 55161885.59 | 0.00 | 0.00 |
Maximum of Months | 0.458874E+09 | 0.279727E+09 | 0.389127E+09 | 0.229665E+09 | 0.197299E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 2774005.79 | 0.251704E+09 | 39098135.84 | 0.00 | 39098135.84 | 0.00 | 0.00 |
February | 7888634.42 | 0.211729E+09 | 55145008.79 | 0.00 | 55145008.79 | 0.00 | 0.00 |
March | 29449612.23 | 0.189019E+09 | 84495288.28 | 571.09 | 84494717.18 | 0.00 | 0.00 |
April | 94787862.61 | 0.138307E+09 | 0.133615E+09 | 888034.53 | 0.132727E+09 | 0.00 | 0.00 |
May | 0.123700E+09 | 0.114015E+09 | 0.172620E+09 | 8802627.26 | 0.163817E+09 | 0.00 | 0.00 |
June | 0.170159E+09 | 80671637.53 | 0.184033E+09 | 11511450.99 | 0.172522E+09 | 0.00 | 0.00 |
July | 0.179029E+09 | 75413515.97 | 0.180813E+09 | 10634633.66 | 0.170179E+09 | 0.00 | 0.00 |
August | 0.139475E+09 | 84157925.23 | 0.142358E+09 | 2662252.34 | 0.139696E+09 | 0.00 | 0.00 |
September | 88720360.48 | 0.114756E+09 | 0.104495E+09 | 61759.92 | 0.104433E+09 | 0.00 | 0.00 |
October | 32202247.28 | 0.171156E+09 | 69137333.33 | 0.00 | 69137333.33 | 0.00 | 0.00 |
November | 4498810.37 | 0.212799E+09 | 40201192.52 | 0.00 | 40201192.52 | 0.00 | 0.00 |
December | 86338.12 | 0.276745E+09 | 28289467.61 | 0.00 | 28289467.61 | 0.00 | 0.00 |
Annual Sum or Average | 0.872771E+09 | 0.192047E+10 | 0.123430E+10 | 34561329.80 | 0.119974E+10 | 0.00 | 0.00 |
Minimum of Months | 86338.12 | 75413515.97 | 28289467.61 | 0.00 | 28289467.61 | 0.00 | 0.00 |
Maximum of Months | 0.179029E+09 | 0.276745E+09 | 0.184033E+09 | 11511450.99 | 0.172522E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.366919E+09 | 0.782775E+09 | 0.464342E+09 | 0.254460E+09 | 0.209881E+09 | 0.00 | 0.00 |
February | 0.468436E+09 | 0.680799E+09 | 0.558620E+09 | 0.280553E+09 | 0.278067E+09 | 0.00 | 0.00 |
March | 0.351748E+09 | 0.619850E+09 | 0.499837E+09 | 0.117767E+09 | 0.382070E+09 | 0.00 | 0.00 |
April | 0.126652E+10 | 0.474172E+09 | 0.116870E+10 | 0.537284E+09 | 0.631418E+09 | 0.00 | 0.00 |
May | 0.122095E+10 | 0.419983E+09 | 0.117966E+10 | 0.474251E+09 | 0.705413E+09 | 0.00 | 0.00 |
June | 0.122841E+10 | 0.299118E+09 | 0.110659E+10 | 0.391513E+09 | 0.715078E+09 | 0.00 | 0.00 |
July | 0.139277E+10 | 0.277591E+09 | 0.118603E+10 | 0.462573E+09 | 0.723454E+09 | 0.00 | 0.00 |
August | 0.146786E+10 | 0.300265E+09 | 0.120687E+10 | 0.564898E+09 | 0.641975E+09 | 0.00 | 0.00 |
September | 0.138777E+10 | 0.394132E+09 | 0.117060E+10 | 0.650638E+09 | 0.519960E+09 | 0.00 | 0.00 |
October | 0.680192E+09 | 0.572245E+09 | 0.679269E+09 | 0.337174E+09 | 0.342095E+09 | 0.00 | 0.00 |
November | 0.327774E+09 | 0.684457E+09 | 0.406624E+09 | 0.201152E+09 | 0.205473E+09 | 0.00 | 0.00 |
December | 0.242542E+09 | 0.884239E+09 | 0.324582E+09 | 0.172789E+09 | 0.151793E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.104019E+11 | 0.638963E+10 | 0.995173E+10 | 0.444505E+10 | 0.550668E+10 | 0.00 | 0.00 |
Minimum of Months | 0.242542E+09 | 0.277591E+09 | 0.324582E+09 | 0.117767E+09 | 0.151793E+09 | 0.00 | 0.00 |
Maximum of Months | 0.146786E+10 | 0.884239E+09 | 0.120687E+10 | 0.650638E+09 | 0.723454E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.100280E+09 | 0.809996E+09 | 0.234312E+09 | 73858251.45 | 0.160454E+09 | 0.00 | 0.00 |
February | 0.170194E+09 | 0.689370E+09 | 0.321866E+09 | 94250751.19 | 0.227615E+09 | 0.00 | 0.00 |
March | 0.219158E+09 | 0.622819E+09 | 0.396563E+09 | 57387429.28 | 0.339176E+09 | 0.00 | 0.00 |
April | 0.908822E+09 | 0.469020E+09 | 0.921320E+09 | 0.354784E+09 | 0.566537E+09 | 0.00 | 0.00 |
May | 0.992102E+09 | 0.408436E+09 | 0.103645E+10 | 0.368969E+09 | 0.667476E+09 | 0.00 | 0.00 |
June | 0.107095E+10 | 0.294526E+09 | 0.101593E+10 | 0.328347E+09 | 0.687583E+09 | 0.00 | 0.00 |
July | 0.116851E+10 | 0.277188E+09 | 0.105484E+10 | 0.365366E+09 | 0.689477E+09 | 0.00 | 0.00 |
August | 0.109625E+10 | 0.305878E+09 | 0.965296E+09 | 0.380269E+09 | 0.585027E+09 | 0.00 | 0.00 |
September | 0.881418E+09 | 0.393624E+09 | 0.814695E+09 | 0.363577E+09 | 0.451118E+09 | 0.00 | 0.00 |
October | 0.347934E+09 | 0.569753E+09 | 0.430233E+09 | 0.143781E+09 | 0.286452E+09 | 0.00 | 0.00 |
November | 99781043.98 | 0.690416E+09 | 0.222445E+09 | 58593481.72 | 0.163851E+09 | 0.00 | 0.00 |
December | 54471137.40 | 0.895995E+09 | 0.167711E+09 | 49526930.11 | 0.118184E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.710987E+10 | 0.642702E+10 | 0.758166E+10 | 0.263871E+10 | 0.494295E+10 | 0.00 | 0.00 |
Minimum of Months | 54471137.40 | 0.277188E+09 | 0.167711E+09 | 49526930.11 | 0.118184E+09 | 0.00 | 0.00 |
Maximum of Months | 0.116851E+10 | 0.895995E+09 | 0.105484E+10 | 0.380269E+09 | 0.689477E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.447065E+09 | 0.997248E+09 | 0.568036E+09 | 0.312990E+09 | 0.255046E+09 | 0.00 | 0.00 |
February | 0.543744E+09 | 0.870114E+09 | 0.649209E+09 | 0.322868E+09 | 0.326341E+09 | 0.00 | 0.00 |
March | 0.362449E+09 | 0.800246E+09 | 0.545040E+09 | 0.104642E+09 | 0.440398E+09 | 0.00 | 0.00 |
April | 0.104515E+10 | 0.629188E+09 | 0.100758E+10 | 0.320126E+09 | 0.687458E+09 | 0.00 | 0.00 |
May | 0.928530E+09 | 0.541394E+09 | 0.996049E+09 | 0.220592E+09 | 0.775457E+09 | 0.00 | 0.00 |
June | 0.985674E+09 | 0.391799E+09 | 0.954413E+09 | 0.159341E+09 | 0.795073E+09 | 0.00 | 0.00 |
July | 0.112867E+10 | 0.371296E+09 | 0.101069E+10 | 0.214535E+09 | 0.796155E+09 | 0.00 | 0.00 |
August | 0.122499E+10 | 0.417059E+09 | 0.103540E+10 | 0.331501E+09 | 0.703903E+09 | 0.00 | 0.00 |
September | 0.124908E+10 | 0.540849E+09 | 0.106950E+10 | 0.497754E+09 | 0.571747E+09 | 0.00 | 0.00 |
October | 0.716462E+09 | 0.738611E+09 | 0.731114E+09 | 0.335158E+09 | 0.395956E+09 | 0.00 | 0.00 |
November | 0.400356E+09 | 0.875721E+09 | 0.493355E+09 | 0.247058E+09 | 0.246297E+09 | 0.00 | 0.00 |
December | 0.289555E+09 | 0.113902E+10 | 0.394422E+09 | 0.213617E+09 | 0.180805E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.932172E+10 | 0.831255E+10 | 0.945482E+10 | 0.328018E+10 | 0.617464E+10 | 0.00 | 0.00 |
Minimum of Months | 0.289555E+09 | 0.371296E+09 | 0.394422E+09 | 0.104642E+09 | 0.180805E+09 | 0.00 | 0.00 |
Maximum of Months | 0.124908E+10 | 0.113902E+10 | 0.106950E+10 | 0.497754E+09 | 0.796155E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.368575E+09 | 0.775301E+09 | 0.461724E+09 | 0.240525E+09 | 0.221199E+09 | 0.00 | 0.00 |
February | 0.533599E+09 | 0.684099E+09 | 0.597787E+09 | 0.310648E+09 | 0.287140E+09 | 0.00 | 0.00 |
March | 0.355948E+09 | 0.615520E+09 | 0.499814E+09 | 0.116324E+09 | 0.383489E+09 | 0.00 | 0.00 |
April | 0.115903E+10 | 0.489771E+09 | 0.107747E+10 | 0.446512E+09 | 0.630959E+09 | 0.00 | 0.00 |
May | 0.120265E+10 | 0.431621E+09 | 0.116302E+10 | 0.443266E+09 | 0.719753E+09 | 0.00 | 0.00 |
June | 0.129581E+10 | 0.307903E+09 | 0.116075E+10 | 0.423404E+09 | 0.737350E+09 | 0.00 | 0.00 |
July | 0.146401E+10 | 0.286385E+09 | 0.124072E+10 | 0.499696E+09 | 0.741026E+09 | 0.00 | 0.00 |
August | 0.140968E+10 | 0.311208E+09 | 0.116303E+10 | 0.510058E+09 | 0.652968E+09 | 0.00 | 0.00 |
September | 0.126028E+10 | 0.403754E+09 | 0.106795E+10 | 0.549963E+09 | 0.517991E+09 | 0.00 | 0.00 |
October | 0.653367E+09 | 0.569134E+09 | 0.655720E+09 | 0.309712E+09 | 0.346008E+09 | 0.00 | 0.00 |
November | 0.327697E+09 | 0.680449E+09 | 0.401645E+09 | 0.191897E+09 | 0.209748E+09 | 0.00 | 0.00 |
December | 0.201226E+09 | 0.879910E+09 | 0.288559E+09 | 0.142844E+09 | 0.145716E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.102319E+11 | 0.643505E+10 | 0.977819E+10 | 0.418485E+10 | 0.559335E+10 | 0.00 | 0.00 |
Minimum of Months | 0.201226E+09 | 0.286385E+09 | 0.288559E+09 | 0.116324E+09 | 0.145716E+09 | 0.00 | 0.00 |
Maximum of Months | 0.146401E+10 | 0.879910E+09 | 0.124072E+10 | 0.549963E+09 | 0.741026E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.112707E+09 | 0.812835E+09 | 0.231694E+09 | 59922886.42 | 0.171771E+09 | 0.00 | 0.00 |
February | 0.243480E+09 | 0.698534E+09 | 0.361033E+09 | 0.124345E+09 | 0.236688E+09 | 0.00 | 0.00 |
March | 0.225920E+09 | 0.619429E+09 | 0.396539E+09 | 55944870.75 | 0.340595E+09 | 0.00 | 0.00 |
April | 0.803539E+09 | 0.484478E+09 | 0.830090E+09 | 0.264012E+09 | 0.566078E+09 | 0.00 | 0.00 |
May | 0.968535E+09 | 0.419194E+09 | 0.101980E+10 | 0.337984E+09 | 0.681816E+09 | 0.00 | 0.00 |
June | 0.112654E+10 | 0.302989E+09 | 0.107009E+10 | 0.360237E+09 | 0.709855E+09 | 0.00 | 0.00 |
July | 0.121882E+10 | 0.291040E+09 | 0.110954E+10 | 0.402490E+09 | 0.707049E+09 | 0.00 | 0.00 |
August | 0.102446E+10 | 0.322423E+09 | 0.921450E+09 | 0.325430E+09 | 0.596020E+09 | 0.00 | 0.00 |
September | 0.757860E+09 | 0.409668E+09 | 0.712050E+09 | 0.262902E+09 | 0.449148E+09 | 0.00 | 0.00 |
October | 0.330937E+09 | 0.572001E+09 | 0.406684E+09 | 0.116318E+09 | 0.290366E+09 | 0.00 | 0.00 |
November | 0.112563E+09 | 0.697519E+09 | 0.217465E+09 | 49338807.43 | 0.168126E+09 | 0.00 | 0.00 |
December | 34400141.06 | 0.913900E+09 | 0.131689E+09 | 19581694.53 | 0.112107E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.695976E+10 | 0.654401E+10 | 0.740813E+10 | 0.237851E+10 | 0.502962E+10 | 0.00 | 0.00 |
Minimum of Months | 34400141.06 | 0.291040E+09 | 0.131689E+09 | 19581694.53 | 0.112107E+09 | 0.00 | 0.00 |
Maximum of Months | 0.121882E+10 | 0.913900E+09 | 0.110954E+10 | 0.402490E+09 | 0.709855E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.402514E+09 | 0.405693E+09 | 0.409028E+09 | 0.264871E+09 | 0.144158E+09 | 0.00 | 0.00 |
February | 0.453023E+09 | 0.357875E+09 | 0.448303E+09 | 0.273230E+09 | 0.175073E+09 | 0.00 | 0.00 |
March | 0.248877E+09 | 0.326635E+09 | 0.306341E+09 | 88552987.85 | 0.217788E+09 | 0.00 | 0.00 |
April | 0.693158E+09 | 0.260722E+09 | 0.607724E+09 | 0.269282E+09 | 0.338442E+09 | 0.00 | 0.00 |
May | 0.555950E+09 | 0.232219E+09 | 0.526456E+09 | 0.170541E+09 | 0.355915E+09 | 0.00 | 0.00 |
June | 0.525275E+09 | 0.161286E+09 | 0.470297E+09 | 0.113740E+09 | 0.356557E+09 | 0.00 | 0.00 |
July | 0.632254E+09 | 0.149391E+09 | 0.523825E+09 | 0.162056E+09 | 0.361769E+09 | 0.00 | 0.00 |
August | 0.780280E+09 | 0.161652E+09 | 0.615237E+09 | 0.275655E+09 | 0.339582E+09 | 0.00 | 0.00 |
September | 0.888543E+09 | 0.211513E+09 | 0.713507E+09 | 0.421116E+09 | 0.292391E+09 | 0.00 | 0.00 |
October | 0.542757E+09 | 0.300588E+09 | 0.491964E+09 | 0.283631E+09 | 0.208334E+09 | 0.00 | 0.00 |
November | 0.340233E+09 | 0.359103E+09 | 0.343806E+09 | 0.209075E+09 | 0.134731E+09 | 0.00 | 0.00 |
December | 0.268908E+09 | 0.462182E+09 | 0.281921E+09 | 0.180775E+09 | 0.101145E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.633177E+10 | 0.338886E+10 | 0.573841E+10 | 0.271252E+10 | 0.302588E+10 | 0.00 | 0.00 |
Minimum of Months | 0.248877E+09 | 0.149391E+09 | 0.281921E+09 | 88552987.85 | 0.101145E+09 | 0.00 | 0.00 |
Maximum of Months | 0.888543E+09 | 0.462182E+09 | 0.713507E+09 | 0.421116E+09 | 0.361769E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 9455874.25 | 0.254062E+10 | 0.342050E+09 | 0.00 | 0.342050E+09 | 0.00 | 0.00 |
February | 32102311.62 | 0.215352E+10 | 0.482437E+09 | 0.00 | 0.482437E+09 | 0.00 | 0.00 |
March | 0.183398E+09 | 0.192456E+10 | 0.739208E+09 | 4996.21 | 0.739203E+09 | 0.00 | 0.00 |
April | 0.689040E+09 | 0.141412E+10 | 0.116893E+10 | 7768978.00 | 0.116116E+10 | 0.00 | 0.00 |
May | 0.891381E+09 | 0.119282E+10 | 0.151017E+10 | 77009863.32 | 0.143316E+10 | 0.00 | 0.00 |
June | 0.129650E+10 | 0.865057E+09 | 0.161002E+10 | 0.100708E+09 | 0.150931E+10 | 0.00 | 0.00 |
July | 0.137846E+10 | 0.809572E+09 | 0.158185E+10 | 93037187.73 | 0.148881E+10 | 0.00 | 0.00 |
August | 0.106174E+10 | 0.903023E+09 | 0.124542E+10 | 23290738.43 | 0.122213E+10 | 0.00 | 0.00 |
September | 0.647813E+09 | 0.121635E+10 | 0.914176E+09 | 540307.24 | 0.913636E+09 | 0.00 | 0.00 |
October | 0.203490E+09 | 0.178238E+10 | 0.604849E+09 | 0.00 | 0.604849E+09 | 0.00 | 0.00 |
November | 16402434.74 | 0.220008E+10 | 0.351700E+09 | 0.00 | 0.351700E+09 | 0.00 | 0.00 |
December | 0.00 | 0.281037E+10 | 0.247491E+09 | 0.00 | 0.247491E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.640978E+10 | 0.198125E+11 | 0.107983E+11 | 0.302360E+09 | 0.104959E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.809572E+09 | 0.247491E+09 | 0.00 | 0.247491E+09 | 0.00 | 0.00 |
Maximum of Months | 0.137846E+10 | 0.281037E+10 | 0.161002E+10 | 0.100708E+09 | 0.150931E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 6637175.98 | 0.261884E+10 | 0.342050E+09 | 0.00 | 0.342050E+09 | 0.00 | 0.00 |
February | 25198717.88 | 0.222008E+10 | 0.482437E+09 | 0.00 | 0.482437E+09 | 0.00 | 0.00 |
March | 0.162898E+09 | 0.198122E+10 | 0.739208E+09 | 4996.21 | 0.739203E+09 | 0.00 | 0.00 |
April | 0.660832E+09 | 0.144609E+10 | 0.116893E+10 | 7768978.00 | 0.116116E+10 | 0.00 | 0.00 |
May | 0.856919E+09 | 0.121871E+10 | 0.151017E+10 | 77009863.32 | 0.143316E+10 | 0.00 | 0.00 |
June | 0.126514E+10 | 0.883707E+09 | 0.161002E+10 | 0.100708E+09 | 0.150931E+10 | 0.00 | 0.00 |
July | 0.134863E+10 | 0.827098E+09 | 0.158185E+10 | 93037187.73 | 0.148881E+10 | 0.00 | 0.00 |
August | 0.103488E+10 | 0.924340E+09 | 0.124542E+10 | 23290738.43 | 0.122213E+10 | 0.00 | 0.00 |
September | 0.623499E+09 | 0.124466E+10 | 0.914176E+09 | 540307.24 | 0.913636E+09 | 0.00 | 0.00 |
October | 0.184490E+09 | 0.183492E+10 | 0.604849E+09 | 0.00 | 0.604849E+09 | 0.00 | 0.00 |
November | 11836012.33 | 0.227304E+10 | 0.351700E+09 | 0.00 | 0.351700E+09 | 0.00 | 0.00 |
December | 0.00 | 0.289640E+10 | 0.247491E+09 | 0.00 | 0.247491E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.618096E+10 | 0.203691E+11 | 0.107983E+11 | 0.302360E+09 | 0.104959E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.827098E+09 | 0.247491E+09 | 0.00 | 0.247491E+09 | 0.00 | 0.00 |
Maximum of Months | 0.134863E+10 | 0.289640E+10 | 0.161002E+10 | 0.100708E+09 | 0.150931E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.510514E+09 | 0.157096E+10 | 0.698627E+09 | 0.328308E+09 | 0.370319E+09 | 0.00 | 0.00 |
February | 0.702748E+09 | 0.138633E+10 | 0.880450E+09 | 0.374790E+09 | 0.505660E+09 | 0.00 | 0.00 |
March | 0.679414E+09 | 0.126579E+10 | 0.896359E+09 | 0.175146E+09 | 0.721213E+09 | 0.00 | 0.00 |
April | 0.243071E+10 | 0.987689E+09 | 0.208991E+10 | 0.892017E+09 | 0.119790E+10 | 0.00 | 0.00 |
May | 0.246565E+10 | 0.920375E+09 | 0.221599E+10 | 0.843169E+09 | 0.137282E+10 | 0.00 | 0.00 |
June | 0.258875E+10 | 0.682380E+09 | 0.212241E+10 | 0.719815E+09 | 0.140259E+10 | 0.00 | 0.00 |
July | 0.289019E+10 | 0.643214E+09 | 0.224075E+10 | 0.827889E+09 | 0.141286E+10 | 0.00 | 0.00 |
August | 0.288692E+10 | 0.673939E+09 | 0.217206E+10 | 0.945114E+09 | 0.122694E+10 | 0.00 | 0.00 |
September | 0.253383E+10 | 0.832615E+09 | 0.198520E+10 | 0.101416E+10 | 0.971033E+09 | 0.00 | 0.00 |
October | 0.116830E+10 | 0.117754E+10 | 0.110945E+10 | 0.480935E+09 | 0.628519E+09 | 0.00 | 0.00 |
November | 0.479275E+09 | 0.139981E+10 | 0.629044E+09 | 0.259737E+09 | 0.369308E+09 | 0.00 | 0.00 |
December | 0.322144E+09 | 0.182688E+10 | 0.492275E+09 | 0.222309E+09 | 0.269966E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.196584E+11 | 0.133675E+11 | 0.175325E+11 | 0.708339E+10 | 0.104491E+11 | 0.00 | 0.00 |
Minimum of Months | 0.322144E+09 | 0.643214E+09 | 0.492275E+09 | 0.175146E+09 | 0.269966E+09 | 0.00 | 0.00 |
Maximum of Months | 0.289019E+10 | 0.182688E+10 | 0.224075E+10 | 0.101416E+10 | 0.141286E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.974103E+09 | 0.177520E+10 | 0.115846E+10 | 0.674242E+09 | 0.484216E+09 | 0.00 | 0.00 |
February | 0.115173E+10 | 0.155513E+10 | 0.130656E+10 | 0.695522E+09 | 0.611038E+09 | 0.00 | 0.00 |
March | 0.710033E+09 | 0.143307E+10 | 0.103321E+10 | 0.225418E+09 | 0.807792E+09 | 0.00 | 0.00 |
April | 0.204553E+10 | 0.112758E+10 | 0.194771E+10 | 0.688135E+09 | 0.125957E+10 | 0.00 | 0.00 |
May | 0.174900E+10 | 0.981171E+09 | 0.185781E+10 | 0.460520E+09 | 0.139729E+10 | 0.00 | 0.00 |
June | 0.178660E+10 | 0.716288E+09 | 0.174908E+10 | 0.324054E+09 | 0.142503E+10 | 0.00 | 0.00 |
July | 0.207785E+10 | 0.679228E+09 | 0.187568E+10 | 0.444416E+09 | 0.143127E+10 | 0.00 | 0.00 |
August | 0.236204E+10 | 0.752686E+09 | 0.199305E+10 | 0.709678E+09 | 0.128337E+10 | 0.00 | 0.00 |
September | 0.251270E+10 | 0.957700E+09 | 0.212965E+10 | 0.107216E+10 | 0.105749E+10 | 0.00 | 0.00 |
October | 0.147365E+10 | 0.131482E+10 | 0.145966E+10 | 0.721997E+09 | 0.737667E+09 | 0.00 | 0.00 |
November | 0.853992E+09 | 0.157299E+10 | 0.995740E+09 | 0.532212E+09 | 0.463528E+09 | 0.00 | 0.00 |
December | 0.636938E+09 | 0.204268E+10 | 0.802484E+09 | 0.460173E+09 | 0.342311E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.183342E+11 | 0.149085E+11 | 0.183091E+11 | 0.700852E+10 | 0.113006E+11 | 0.00 | 0.00 |
Minimum of Months | 0.636938E+09 | 0.679228E+09 | 0.802484E+09 | 0.225418E+09 | 0.342311E+09 | 0.00 | 0.00 |
Maximum of Months | 0.251270E+10 | 0.204268E+10 | 0.212965E+10 | 0.107216E+10 | 0.143127E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 4.18 | 3.23 | 2.03 | 1.05 | -4.0 | 28.28 | 62.93 | 0.00 |
February | 4.25 | 3.55 | 2.74 | 1.60 | -5.0 | 43.80 | 86.73 | 0.02 |
March | 5.90 | 4.45 | 2.76 | 1.18 | -1.9 | 68.95 | 35.00 | 0.00 |
April | 8.96 | 6.24 | 3.38 | 1.56 | -0.7 | 96.13 | 186.12 | 0.00 |
May | 9.99 | 8.07 | 6.28 | 3.35 | -0.9 | 110.92 | 199.68 | 0.02 |
June | 13.31 | 11.27 | 9.70 | 3.33 | 3.35 | 121.69 | 199.28 | 0.00 |
July | 15.02 | 12.39 | 10.49 | 3.21 | 4.49 | 111.91 | 220.83 | 0.00 |
August | 15.65 | 12.75 | 10.65 | 2.92 | 3.95 | 91.47 | 211.91 | 0.00 |
September | 13.43 | 11.01 | 9.10 | 2.64 | 1.43 | 68.72 | 198.32 | 0.01 |
October | 9.33 | 8.03 | 6.81 | 1.97 | -1.0 | 48.92 | 91.86 | 0.04 |
November | 6.66 | 5.66 | 4.54 | 2.05 | -2.3 | 30.27 | 53.24 | 0.04 |
December | 4.10 | 3.14 | 1.95 | 2.36 | -5.1 | 20.52 | 40.74 | 0.04 |
Annual Sum or Average | 9.26 | 7.50 | 5.89 | 2.27 | -0.6 | 70.25 | 132.30 | 0.02 |
Minimum of Months | 4.10 | 3.14 | 1.95 | 1.05 | -5.1 | 20.52 | 35.00 | 0.00 |
Maximum of Months | 15.65 | 12.75 | 10.65 | 3.35 | 4.49 | 121.69 | 220.83 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.00 | 29-JAN-05:00 | 9.37 | 5.00 | 3.60 | 8.35 | 0.00 | 0.00 |
February | 11.00 | 07-FEB-14:00 | 9.86 | 9.00 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 14.00 | 25-MAR-12:00 | 11.22 | 9.00 | 2.60 | 7.35 | 287.00 | 93.00 |
April | 24.00 | 30-APR-14:00 | 13.13 | 4.00 | 1.50 | 7.75 | 167.50 | 716.00 |
May | 24.00 | 22-MAY-14:00 | 16.08 | 11.00 | 2.60 | 9.33 | 159.00 | 769.00 |
June | 27.00 | 13-JUN-16:00 | 17.53 | 12.00 | 3.10 | 12.41 | 141.50 | 652.50 |
July | 30.00 | 22-JUL-17:00 | 16.80 | 8.00 | 0.00 | 14.28 | 122.00 | 407.00 |
August | 27.00 | 14-AUG-17:19 | 14.18 | 3.33 | 2.60 | 10.37 | 133.00 | 358.83 |
September | 23.00 | 11-SEP-16:00 | 16.22 | 12.00 | 2.60 | 8.74 | 108.00 | 325.50 |
October | 19.00 | 07-OCT-14:00 | 10.10 | 1.00 | 1.50 | 2.22 | 131.00 | 540.50 |
November | 16.00 | 24-NOV-11:00 | 12.01 | 9.00 | 4.10 | 9.33 | 61.50 | 0.00 |
December | 13.00 | 23-DEC-10:00 | 7.64 | 2.00 | 7.70 | 6.75 | 70.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 11.00 | 7.64 | 1.00 | 0.00 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 30.00 | 17.53 | 12.00 | 7.70 | 14.28 | 287.00 | 769.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -6.0 | 10-JAN-07:00 | -7.0 | -9.0 | 0.00 | -20.0 | 0.00 | 0.00 |
February | -4.0 | 17-FEB-06:00 | -4.0 | -4.0 | 0.00 | -20.5 | 0.00 | 0.00 |
March | -1.0 | 08-MAR-06:00 | -1.4 | -2.0 | 0.00 | -14.4 | 17.50 | 184.50 |
April | 0.00 | 08-APR-04:00 | -0.9 | -2.0 | 0.00 | -12.7 | 0.00 | 0.00 |
May | 2.00 | 06-MAY-04:00 | 1.57 | 1.00 | 3.60 | -13.7 | 12.50 | 117.00 |
June | 6.00 | 01-JUN-03:00 | 5.05 | 4.00 | 0.00 | -9.2 | 0.00 | 0.00 |
July | 7.00 | 05-JUL-04:00 | 6.47 | 6.00 | 3.10 | -7.8 | 28.00 | 155.00 |
August | 8.00 | 20-AUG-04:00 | 7.45 | 7.00 | 0.00 | -6.6 | 0.00 | 0.00 |
September | 5.00 | 20-SEP-03:00 | 5.00 | 5.00 | 2.60 | -10.0 | 0.00 | 0.00 |
October | 2.00 | 07-OCT-03:00 | 2.00 | 2.00 | 0.00 | -13.4 | 0.00 | 0.00 |
November | -2.0 | 29-NOV-01:00 | -2.0 | -2.0 | 3.10 | -10.7 | 0.00 | 0.00 |
December | -3.0 | 29-DEC-20:00 | -4.5 | -7.0 | 3.60 | -20.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -6.0 | -7.0 | -9.0 | 0.00 | -20.5 | 0.00 | 0.00 | |
Maximum of Months | 8.00 | 7.45 | 7.00 | 3.60 | -6.6 | 28.00 | 184.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.44 | 29-JAN-04:00 | 13.00 | 12.00 | 0.00 | 9.13 | 0.00 | 0.00 |
February | 9.86 | 07-FEB-14:00 | 11.00 | 9.00 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 12.00 | 19-MAR-11:00 | 12.00 | 12.00 | 2.60 | 8.15 | 131.00 | 0.00 |
April | 15.39 | 28-APR-07:00 | 16.00 | 15.00 | 0.00 | 5.54 | 119.50 | 626.00 |
May | 16.08 | 22-MAY-14:00 | 24.00 | 11.00 | 2.60 | 9.33 | 159.00 | 769.00 |
June | 19.93 | 25-JUN-17:00 | 22.00 | 19.00 | 0.00 | 15.94 | 136.50 | 360.50 |
July | 17.31 | 22-JUL-09:00 | 26.00 | 12.00 | 4.60 | 11.46 | 224.50 | 619.50 |
August | 17.06 | 14-AUG-12:00 | 24.00 | 13.00 | 2.60 | 9.91 | 205.50 | 669.50 |
September | 16.54 | 10-SEP-15:00 | 21.00 | 14.00 | 3.60 | 8.54 | 160.50 | 483.00 |
October | 13.58 | 17-OCT-14:00 | 16.00 | 12.00 | 0.00 | 12.03 | 144.00 | 44.50 |
November | 12.01 | 24-NOV-11:00 | 16.00 | 9.00 | 4.10 | 9.33 | 61.50 | 0.00 |
December | 7.93 | 02-DEC-12:00 | 9.00 | 7.00 | 0.00 | 2.01 | 135.50 | 84.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.93 | 9.00 | 7.00 | 0.00 | 2.01 | 0.00 | 0.00 | |
Maximum of Months | 19.93 | 26.00 | 19.00 | 4.60 | 15.94 | 224.50 | 769.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.00 | 29-JAN-04:00 | 13.00 | 12.44 | 0.00 | 9.13 | 0.00 | 0.00 |
February | 9.00 | 07-FEB-14:00 | 11.00 | 9.86 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 12.00 | 19-MAR-11:00 | 12.00 | 12.00 | 2.60 | 8.15 | 131.00 | 0.00 |
April | 15.00 | 28-APR-07:00 | 16.00 | 15.39 | 0.00 | 5.54 | 119.50 | 626.00 |
May | 12.00 | 23-MAY-07:00 | 17.00 | 13.95 | 3.10 | 5.13 | 112.00 | 719.50 |
June | 19.00 | 25-JUN-17:00 | 22.00 | 19.93 | 0.00 | 15.94 | 136.50 | 360.50 |
July | 14.00 | 17-JUL-17:00 | 18.00 | 15.45 | 3.60 | 9.91 | 120.00 | 0.00 |
August | 16.00 | 08-AUG-12:00 | 18.00 | 16.70 | 1.50 | 11.46 | 154.00 | 0.00 |
September | 14.00 | 10-SEP-15:00 | 21.00 | 16.54 | 3.60 | 8.54 | 160.50 | 483.00 |
October | 13.00 | 17-OCT-18:00 | 13.00 | 13.00 | 2.60 | 9.33 | 0.00 | 0.00 |
November | 12.00 | 08-NOV-14:00 | 12.00 | 12.00 | 0.00 | 8.15 | 93.00 | 106.00 |
December | 7.00 | 02-DEC-11:00 | 8.00 | 7.45 | 3.10 | 1.16 | 144.50 | 146.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.00 | 8.00 | 7.45 | 0.00 | 1.16 | 0.00 | 0.00 | |
Maximum of Months | 19.00 | 22.00 | 19.93 | 3.60 | 15.94 | 160.50 | 719.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 10.33 | 8.85 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 10.00 | 14.79 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 10.33 | 17.09 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 11.26 | 40.86 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 12.54 | 47.73 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 13.82 | 50.98 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 14.77 | 51.67 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 15.12 | 44.67 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 14.78 | 34.25 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.84 | 17.71 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 12.55 | 9.34 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 11.27 | 6.14 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 12.57 | 28.73 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 10.00 | 6.14 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 15.12 | 51.67 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH LAUNDRY G WATER HEATER
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.123431E+12 | -0.121653E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.177788E+10 | 82.17 | 0.00 | 0.00 |
February | 0.111989E+12 | -0.110378E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.161051E+10 | 82.17 | 0.00 | 0.00 |
March | 0.123435E+12 | -0.121645E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.179029E+10 | 82.17 | 0.00 | 0.00 |
April | 0.117937E+12 | -0.116205E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.173248E+10 | 82.17 | 0.00 | 0.00 |
May | 0.119704E+12 | -0.117913E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.179040E+10 | 82.17 | 0.00 | 0.00 |
June | 0.113731E+12 | -0.112002E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.172935E+10 | 82.17 | 0.00 | 0.00 |
July | 0.115913E+12 | -0.114133E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.177984E+10 | 82.17 | 0.00 | 0.00 |
August | 0.115309E+12 | -0.113534E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.177571E+10 | 82.17 | 0.00 | 0.00 |
September | 0.112146E+12 | -0.110435E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.171122E+10 | 82.17 | 0.00 | 0.00 |
October | 0.117478E+12 | -0.115713E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.176519E+10 | 82.17 | 0.00 | 0.00 |
November | 0.115791E+12 | -0.114083E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.170771E+10 | 82.17 | 0.00 | 0.00 |
December | 0.121822E+12 | -0.120053E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.176899E+10 | 82.17 | 0.00 | 0.00 |
Annual Sum or Average | 0.140869E+13 | -0.138775E+13 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.209396E+11 | 82.17 | 0.00 | 0.00 |
Minimum of Months | 0.111989E+12 | -0.121653E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.179040E+10 | 82.17 | 0.00 | 0.00 |
Maximum of Months | 0.123435E+12 | -0.110378E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.161051E+10 | 82.17 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.804762E+10 | -0.788296E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164663813.9 | 82.17 | 0.00 | 0.00 |
February | 0.727210E+10 | -0.712336E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -148736354.8 | 82.17 | 0.00 | 0.00 |
March | 0.804615E+10 | -0.788155E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164593666.1 | 82.17 | 0.00 | 0.00 |
April | 0.779738E+10 | -0.763820E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -159177336.6 | 82.17 | 0.00 | 0.00 |
May | 0.804740E+10 | -0.788296E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164443072.9 | 82.17 | 0.00 | 0.00 |
June | 0.778880E+10 | -0.762976E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -159039644.4 | 82.17 | 0.00 | 0.00 |
July | 0.805571E+10 | -0.789140E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164312201.1 | 82.17 | 0.00 | 0.00 |
August | 0.804726E+10 | -0.788296E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164301135.1 | 82.17 | 0.00 | 0.00 |
September | 0.779867E+10 | -0.763961E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -159066821.9 | 82.17 | 0.00 | 0.00 |
October | 0.804607E+10 | -0.788155E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164512050.1 | 82.17 | 0.00 | 0.00 |
November | 0.778062E+10 | -0.762132E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -159302735.2 | 82.17 | 0.00 | 0.00 |
December | 0.805610E+10 | -0.789140E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164703427.2 | 82.17 | 0.00 | 0.00 |
Annual Sum or Average | 0.947839E+11 | -0.928470E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.193685E+10 | 82.17 | 0.00 | 0.00 |
Minimum of Months | 0.727210E+10 | -0.789140E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -164703427.2 | 82.17 | 0.00 | 0.00 |
Maximum of Months | 0.805610E+10 | -0.712336E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -148736354.8 | 82.17 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.741228E+11 | -0.725825E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.154028E+10 | 60.05 | 0.00 | 0.00 |
February | 0.673992E+11 | -0.660015E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.139771E+10 | 60.05 | 0.00 | 0.00 |
March | 0.741976E+11 | -0.726401E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.155747E+10 | 60.05 | 0.00 | 0.00 |
April | 0.704560E+11 | -0.689489E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.150715E+10 | 60.05 | 0.00 | 0.00 |
May | 0.709453E+11 | -0.693876E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.155762E+10 | 60.05 | 0.00 | 0.00 |
June | 0.668576E+11 | -0.653548E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.150281E+10 | 60.05 | 0.00 | 0.00 |
July | 0.676288E+11 | -0.660858E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.154299E+10 | 60.05 | 0.00 | 0.00 |
August | 0.671729E+11 | -0.656356E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.153726E+10 | 60.05 | 0.00 | 0.00 |
September | 0.654481E+11 | -0.639704E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.147768E+10 | 60.05 | 0.00 | 0.00 |
October | 0.689716E+11 | -0.674489E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.152268E+10 | 60.05 | 0.00 | 0.00 |
November | 0.685621E+11 | -0.670893E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.147281E+10 | 60.05 | 0.00 | 0.00 |
December | 0.727242E+11 | -0.711963E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.152794E+10 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.834486E+12 | -0.816342E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.181444E+11 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.654481E+11 | -0.726401E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.155762E+10 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.741976E+11 | -0.639704E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.139771E+10 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: LOBBY_FLR_1_DAYLCTRL
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.87 | 0.86 | 01-JAN-08:39 | 3370.77 | 36.53 | 191.67 | 226.00 | 2715.88 | 37.48 | 192.00 | 187.00 |
February | 217.00 | 0.87 | 0.86 | 01-FEB-11:39 | 4958.33 | 35.87 | 212.00 | 247.67 | 2174.54 | 31.92 | 194.67 | 210.67 |
March | 215.50 | 0.87 | 0.86 | 01-MAR-11:39 | 3215.22 | 29.59 | 161.50 | 313.83 | 667.82 | 21.68 | 136.00 | 251.67 |
April | 359.67 | 0.87 | 0.86 | 01-APR-07:19 | 1866.57 | 20.90 | 192.17 | 360.17 | 735.92 | 22.61 | 281.33 | 316.67 |
May | 417.17 | 0.87 | 0.86 | 01-MAY-07:10 | 1497.46 | 20.41 | 155.50 | 413.17 | 589.00 | 22.12 | 297.00 | 350.67 |
June | 410.67 | 0.87 | 0.86 | 01-JUN-06:19 | 1467.33 | 20.63 | 154.33 | 415.83 | 574.85 | 22.32 | 299.50 | 353.83 |
July | 429.00 | 0.87 | 0.86 | 01-JUL-06:30 | 1434.35 | 20.49 | 162.83 | 424.00 | 572.45 | 22.20 | 313.83 | 365.33 |
August | 396.33 | 0.87 | 0.86 | 01-AUG-06:40 | 1632.91 | 20.60 | 188.50 | 385.17 | 655.47 | 22.33 | 299.00 | 333.83 |
September | 337.67 | 0.87 | 0.86 | 01-SEP-07:00 | 5617.92 | 27.26 | 219.17 | 332.33 | 786.17 | 22.74 | 265.00 | 290.83 |
October | 234.00 | 0.87 | 0.86 | 01-OCT-06:00 | 6323.09 | 35.14 | 217.00 | 282.67 | 1095.65 | 25.41 | 193.00 | 230.67 |
November | 171.33 | 0.87 | 0.86 | 01-NOV-11:50 | 3930.05 | 36.25 | 167.33 | 221.83 | 2868.44 | 36.50 | 165.67 | 164.33 |
December | 131.67 | 0.87 | 0.86 | 02-DEC-08:50 | 3233.30 | 37.32 | 128.50 | 186.67 | 2601.23 | 38.27 | 128.67 | 125.17 |
Annual Sum or Average | 3515.67 | 0.87 | 2862.95 | 25.97 | 2150.50 | 3809.33 | 1068.03 | 25.24 | 2765.67 | 3180.67 | ||
Minimum of Months | 131.67 | 0.87 | 0.86 | 1434.35 | 20.41 | 128.50 | 186.67 | 572.45 | 21.68 | 128.67 | 125.17 | |
Maximum of Months | 429.00 | 0.87 | 0.86 | 6323.09 | 37.32 | 219.17 | 424.00 | 2868.44 | 38.27 | 313.83 | 365.33 |
Report: DaylightingReportMonthly
For: CAFE_FLR_1_DAYLCTRL
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.27 | 0.22 | 01-JAN-08:39 | 3702.74 | 36.60 | 191.67 | 234.83 | 3047.32 | 37.53 | 192.00 | 212.33 |
February | 217.00 | 0.25 | 0.22 | 01-FEB-11:39 | 5335.82 | 35.95 | 212.17 | 254.83 | 2547.96 | 31.94 | 200.50 | 234.67 |
March | 215.50 | 0.27 | 0.22 | 01-MAR-11:39 | 3464.58 | 29.86 | 162.50 | 325.17 | 916.26 | 22.11 | 186.50 | 288.17 |
April | 359.67 | 0.26 | 0.22 | 01-APR-06:00 | 2221.91 | 21.17 | 187.17 | 368.33 | 1090.14 | 22.73 | 298.00 | 344.83 |
May | 417.17 | 0.26 | 0.22 | 01-MAY-06:49 | 1770.13 | 20.87 | 181.33 | 425.00 | 860.73 | 22.41 | 326.83 | 394.17 |
June | 410.67 | 0.25 | 0.22 | 01-JUN-05:40 | 1720.23 | 21.14 | 189.17 | 430.33 | 826.83 | 22.66 | 326.00 | 390.83 |
July | 429.00 | 0.26 | 0.22 | 01-JUL-05:40 | 1700.67 | 20.95 | 195.83 | 436.50 | 837.89 | 22.49 | 343.00 | 405.83 |
August | 396.33 | 0.26 | 0.22 | 01-AUG-05:00 | 1962.64 | 20.92 | 176.83 | 395.17 | 984.19 | 22.49 | 316.33 | 365.50 |
September | 337.67 | 0.26 | 0.22 | 01-SEP-07:40 | 6043.77 | 27.49 | 212.33 | 340.33 | 1211.06 | 22.72 | 270.67 | 318.67 |
October | 234.00 | 0.25 | 0.22 | 01-OCT-06:49 | 6721.29 | 35.27 | 217.33 | 291.83 | 1493.77 | 25.45 | 207.17 | 264.50 |
November | 171.33 | 0.26 | 0.22 | 01-NOV-11:39 | 4271.67 | 36.32 | 167.50 | 233.00 | 3209.29 | 36.55 | 166.17 | 195.00 |
December | 131.67 | 0.26 | 0.22 | 02-DEC-08:39 | 3566.45 | 37.39 | 128.67 | 198.83 | 2933.06 | 38.32 | 128.67 | 155.17 |
Annual Sum or Average | 3515.67 | 0.26 | 3184.46 | 26.27 | 2222.50 | 3934.17 | 1388.46 | 25.42 | 2961.83 | 3569.67 | ||
Minimum of Months | 131.67 | 0.25 | 0.22 | 1700.67 | 20.87 | 128.67 | 198.83 | 826.83 | 22.11 | 128.67 | 155.17 | |
Maximum of Months | 429.00 | 0.27 | 0.22 | 6721.29 | 37.39 | 217.33 | 436.50 | 3209.29 | 38.32 | 343.00 | 405.83 |
Report: DaylightingReportMonthly
For: DINING_FLR_6_DAYLCTRL
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.70 | 0.60 | 01-JAN-10:50 | 368.78 | 14.16 | 0.00 | 205.67 | 171.61 | 17.56 | 0.00 | 65.17 |
February | 217.00 | 0.66 | 0.60 | 01-FEB-12:09 | 480.84 | 15.69 | 0.00 | 236.33 | 222.48 | 18.98 | 0.00 | 137.67 |
March | 215.50 | 0.65 | 0.60 | 01-MAR-11:39 | 616.26 | 16.23 | 0.00 | 313.83 | 257.71 | 19.33 | 3.17 | 216.67 |
April | 359.67 | 0.62 | 0.60 | 01-APR-07:19 | 772.32 | 18.16 | 0.00 | 367.67 | 356.91 | 21.35 | 164.83 | 332.67 |
May | 417.17 | 0.61 | 0.60 | 01-MAY-06:00 | 936.67 | 19.61 | 30.00 | 433.00 | 424.85 | 23.55 | 273.17 | 407.67 |
June | 410.67 | 0.61 | 0.60 | 01-JUN-04:00 | 1070.80 | 20.54 | 49.50 | 436.83 | 488.67 | 24.00 | 292.00 | 408.50 |
July | 429.00 | 0.61 | 0.60 | 01-JUL-04:49 | 985.44 | 20.68 | 61.33 | 445.50 | 457.35 | 23.65 | 295.00 | 419.17 |
August | 396.33 | 0.62 | 0.60 | 01-AUG-05:40 | 777.05 | 18.45 | 6.83 | 399.50 | 366.76 | 21.64 | 194.00 | 363.67 |
September | 337.67 | 0.63 | 0.60 | 01-SEP-07:00 | 607.50 | 17.37 | 0.00 | 333.83 | 300.80 | 20.61 | 38.17 | 284.67 |
October | 234.00 | 0.64 | 0.60 | 01-OCT-07:49 | 533.87 | 16.34 | 0.00 | 274.83 | 252.12 | 19.60 | 0.17 | 174.83 |
November | 171.33 | 0.68 | 0.60 | 01-NOV-12:20 | 404.55 | 14.79 | 0.00 | 204.50 | 188.83 | 18.14 | 0.00 | 74.00 |
December | 131.67 | 0.71 | 0.60 | 02-DEC-11:09 | 340.63 | 13.99 | 0.00 | 165.50 | 161.99 | 17.43 | 0.00 | 34.83 |
Annual Sum or Average | 3515.67 | 0.63 | 737.42 | 17.94 | 147.67 | 3817.00 | 341.18 | 21.26 | 1260.50 | 2919.50 | ||
Minimum of Months | 131.67 | 0.61 | 0.60 | 340.63 | 13.99 | 0.00 | 165.50 | 161.99 | 17.43 | 0.00 | 34.83 | |
Maximum of Months | 429.00 | 0.71 | 0.60 | 1070.80 | 20.68 | 61.33 | 445.50 | 488.67 | 24.00 | 295.00 | 419.17 |
Report: DaylightingReportMonthly
For: BANQUET_FLR_6_DAYLCTRL
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.70 | 0.60 | 01-JAN-10:50 | 368.78 | 14.16 | 0.00 | 205.67 | 171.61 | 17.56 | 0.00 | 65.17 |
February | 217.00 | 0.66 | 0.60 | 01-FEB-12:09 | 480.84 | 15.69 | 0.00 | 236.33 | 222.48 | 18.98 | 0.00 | 137.67 |
March | 215.50 | 0.65 | 0.60 | 01-MAR-11:39 | 616.26 | 16.23 | 0.00 | 313.83 | 257.71 | 19.33 | 3.17 | 216.67 |
April | 359.67 | 0.62 | 0.60 | 01-APR-07:19 | 772.32 | 18.16 | 0.00 | 367.67 | 356.91 | 21.35 | 164.83 | 332.67 |
May | 417.17 | 0.61 | 0.60 | 01-MAY-06:00 | 936.67 | 19.61 | 30.00 | 433.00 | 424.85 | 23.55 | 273.17 | 407.67 |
June | 410.67 | 0.61 | 0.60 | 01-JUN-04:00 | 1070.80 | 20.54 | 49.50 | 436.83 | 488.67 | 24.00 | 292.00 | 408.50 |
July | 429.00 | 0.61 | 0.60 | 01-JUL-04:49 | 985.44 | 20.68 | 61.33 | 445.50 | 457.35 | 23.65 | 295.00 | 419.17 |
August | 396.33 | 0.62 | 0.60 | 01-AUG-05:40 | 777.05 | 18.45 | 6.83 | 399.50 | 366.76 | 21.64 | 194.00 | 363.67 |
September | 337.67 | 0.63 | 0.60 | 01-SEP-07:00 | 607.50 | 17.37 | 0.00 | 333.83 | 300.80 | 20.61 | 38.17 | 284.67 |
October | 234.00 | 0.64 | 0.60 | 01-OCT-07:49 | 533.87 | 16.34 | 0.00 | 274.83 | 252.12 | 19.60 | 0.17 | 174.83 |
November | 171.33 | 0.68 | 0.60 | 01-NOV-12:20 | 404.55 | 14.79 | 0.00 | 204.50 | 188.83 | 18.14 | 0.00 | 74.00 |
December | 131.67 | 0.71 | 0.60 | 02-DEC-11:09 | 340.63 | 13.99 | 0.00 | 165.50 | 161.99 | 17.43 | 0.00 | 34.83 |
Annual Sum or Average | 3515.67 | 0.63 | 737.42 | 17.94 | 147.67 | 3817.00 | 341.18 | 21.26 | 1260.50 | 2919.50 | ||
Minimum of Months | 131.67 | 0.61 | 0.60 | 340.63 | 13.99 | 0.00 | 165.50 | 161.99 | 17.43 | 0.00 | 34.83 | |
Maximum of Months | 429.00 | 0.71 | 0.60 | 1070.80 | 20.68 | 61.33 | 445.50 | 488.67 | 24.00 | 295.00 | 419.17 |
Report: CoilReportMonthly
For: FLR_3_DOAS HEATING COIL
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.252471E+09 | 2923.67 | 12-JAN-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 83318550.81 | 1522.43 | 17-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1307150.44 | 1292.80 | 15-MAR-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7319.02 | 0.63 | 28-APR-12:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6352.33 | 0.63 | 27-MAY-12:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 12223.26 | 0.67 | 24-JUN-18:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 25817.97 | 0.68 | 12-JUL-19:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 24076.45 | 0.66 | 18-AUG-16:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 12826.79 | 0.67 | 17-SEP-16:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3041.39 | 0.64 | 07-OCT-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6792423.90 | 642.47 | 29-NOV-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 46266835.84 | 1561.82 | 27-DEC-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.390248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 3041.39 | 0.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.252471E+09 | 2923.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.537322E+11 | 119496.51 | 06-JAN-11:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.303488E+11 | 129214.75 | 19-FEB-11:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.644217E+11 | 120014.34 | 10-MAR-18:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.773795E+11 | 117680.91 | 10-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.101127E+12 | 118810.89 | 27-MAY-22:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.748573E+11 | 115605.44 | 08-JUN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.509107E+11 | 102991.13 | 31-JUL-04:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.380216E+11 | 101574.32 | 20-AUG-05:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.731374E+11 | 121668.72 | 28-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.106296E+12 | 123870.44 | 03-OCT-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.922363E+11 | 123556.55 | 28-NOV-11:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.306237E+11 | 126275.86 | 26-DEC-11:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.793093E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.303488E+11 | 101574.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.106296E+12 | 129214.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.268071E+10 | 2037.10 | 04-JAN-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.210794E+10 | 1828.96 | 16-FEB-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.253638E+10 | 1787.63 | 15-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.865974E+09 | 1463.52 | 10-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.871756E+09 | 1338.91 | 05-MAY-07:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.396800E+09 | 1096.09 | 07-JUN-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.272229E+09 | 871.70 | 09-JUL-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.147317E+09 | 783.33 | 09-AUG-10:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.321374E+09 | 1035.12 | 17-SEP-04:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.153395E+10 | 1536.63 | 16-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.235747E+10 | 1871.22 | 30-NOV-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.334066E+10 | 1967.67 | 15-DEC-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.174326E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.147317E+09 | 783.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.334066E+10 | 2037.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 8352320.08 | 231.51 | 04-JAN-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2376873.95 | 199.88 | 27-FEB-11:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1611011.54 | 181.35 | 16-MAR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 3049987.62 | 185.83 | 30-NOV-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 29079027.66 | 270.47 | 10-DEC-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 44469220.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29079027.66 | 270.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.223904E+09 | 570.05 | 12-JAN-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.119259E+09 | 379.61 | 16-FEB-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 60602775.68 | 372.71 | 16-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 48878609.33 | 414.18 | 29-NOV-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.338327E+09 | 513.07 | 30-DEC-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.790971E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.338327E+09 | 570.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.392841E+09 | 461.81 | 12-JAN-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.297320E+09 | 357.26 | 16-FEB-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.200903E+09 | 327.45 | 15-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1672662.45 | 123.07 | 01-APR-10:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6584238.75 | 99.17 | 25-OCT-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.168780E+09 | 386.50 | 29-NOV-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.541399E+09 | 437.98 | 30-DEC-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160950E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.541399E+09 | 461.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 81493572.82 | 1096.96 | 09-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 65421849.31 | 897.29 | 17-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 53684681.29 | 846.11 | 04-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8542135.53 | 582.08 | 01-APR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 7646433.71 | 472.30 | 15-MAY-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 76253.42 | 63.54 | 08-JUN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 114376.40 | 63.54 | 03-JUL-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 151253.87 | 125.00 | 09-SEP-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 19479912.77 | 582.09 | 28-OCT-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 52109053.10 | 897.29 | 27-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 99211322.12 | 1193.94 | 30-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.387931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 99211322.12 | 1193.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.173694E+10 | 5429.58 | 04-JAN-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.113191E+10 | 4941.71 | 16-FEB-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.162236E+10 | 4780.43 | 15-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.145765E+09 | 3918.48 | 10-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.210956E+09 | 3022.15 | 17-MAY-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 53014865.90 | 2951.45 | 07-JUN-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 3539678.67 | 1423.08 | 08-JUL-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 14653791.36 | 2110.30 | 09-AUG-10:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 26005762.85 | 2442.30 | 08-SEP-10:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.805088E+09 | 4179.63 | 16-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.152574E+10 | 5022.98 | 30-NOV-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.268515E+10 | 5326.91 | 15-DEC-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.996112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 3539678.67 | 1423.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.268515E+10 | 5429.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.149355E+09 | 4934.09 | 04-JAN-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 29587418.10 | 3816.88 | 16-FEB-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 36888497.13 | 3217.77 | 15-MAR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 62815454.57 | 3933.67 | 30-NOV-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.432746E+09 | 5176.03 | 10-DEC-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.711392E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.432746E+09 | 5176.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.487724E+10 | 6099.59 | 04-JAN-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.326453E+10 | 5585.09 | 16-FEB-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.333628E+10 | 5091.28 | 15-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 43091240.20 | 2000.60 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.117682E+10 | 4316.60 | 20-OCT-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.376837E+10 | 5813.62 | 30-NOV-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.724417E+10 | 6065.26 | 15-DEC-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.237105E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.724417E+10 | 6099.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.313917E+10 | 3095.45 | 10-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.221283E+10 | 2911.97 | 17-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.185369E+10 | 2250.08 | 16-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.169394E+09 | 1703.03 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 22731917.03 | 733.15 | 06-MAY-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.714724E+09 | 1674.65 | 23-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.215009E+10 | 2730.01 | 29-NOV-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.401412E+10 | 2891.95 | 27-DEC-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.142767E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.401412E+10 | 3095.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.275631E+10 | 4797.57 | 04-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.200654E+10 | 4740.35 | 01-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.191360E+10 | 4767.95 | 15-MAR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.351372E+09 | 4529.19 | 25-APR-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.228567E+09 | 4270.04 | 28-MAY-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 21265741.78 | 4322.37 | 06-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 27473487.86 | 4431.25 | 02-JUL-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 9848116.00 | 4167.80 | 08-AUG-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 60062618.14 | 4353.38 | 19-SEP-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.957237E+09 | 4692.27 | 27-OCT-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.217801E+10 | 4797.81 | 30-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.381528E+10 | 4798.20 | 16-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.143256E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 9848116.00 | 4167.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.381528E+10 | 4798.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.355195E+10 | 4727.10 | 13-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.264759E+10 | 4695.34 | 25-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.222087E+10 | 4712.07 | 15-MAR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.516494E+09 | 4558.52 | 10-APR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.270845E+09 | 4464.59 | 08-MAY-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 19965341.04 | 4279.23 | 04-JUN-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 27360336.90 | 4347.59 | 02-JUL-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 9569156.84 | 4063.85 | 06-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 94266372.65 | 4343.89 | 20-SEP-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.130422E+10 | 4631.50 | 27-OCT-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.275758E+10 | 4727.25 | 30-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.437507E+10 | 4727.66 | 16-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.177958E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 9569156.84 | 4063.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.437507E+10 | 4727.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.769072E+10 | 26300.65 | 11-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.522608E+10 | 25645.59 | 17-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.213380E+10 | 25575.32 | 15-MAR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.244237E+09 | 25333.06 | 11-APR-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 90810051.21 | 25324.67 | 26-MAY-15:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 38019370.77 | 21509.36 | 15-JUN-15:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 23284615.45 | 18979.72 | 11-JUL-15:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 37609820.66 | 25321.99 | 23-AUG-15:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 85398985.88 | 25328.08 | 03-SEP-15:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.715665E+09 | 25317.48 | 24-OCT-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.385475E+10 | 26005.11 | 29-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.936348E+10 | 26140.30 | 27-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.295039E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 23284615.45 | 18979.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.936348E+10 | 26300.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.278959E+10 | 4727.57 | 04-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.212237E+10 | 4684.65 | 01-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.194021E+10 | 4695.60 | 15-MAR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.331290E+09 | 4274.01 | 01-APR-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.235806E+09 | 4069.69 | 08-MAY-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 35431301.54 | 4245.20 | 27-JUN-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 18866934.64 | 4231.26 | 29-JUL-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8818659.07 | 4463.60 | 08-AUG-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 42929869.11 | 4270.45 | 30-SEP-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.961901E+09 | 4627.75 | 27-OCT-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.220053E+10 | 4727.82 | 30-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.368697E+10 | 4728.23 | 16-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.143747E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 8818659.07 | 4069.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.368697E+10 | 4728.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.353640E+10 | 4659.15 | 05-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.280530E+10 | 4638.27 | 01-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.224300E+10 | 4641.60 | 15-MAR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.471994E+09 | 4267.92 | 24-APR-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.284044E+09 | 4196.76 | 13-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 36506904.98 | 4205.02 | 27-JUN-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 15989538.61 | 4284.80 | 13-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6391740.76 | 4341.20 | 08-AUG-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 76839595.51 | 4398.06 | 18-SEP-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.128578E+10 | 4568.75 | 27-OCT-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.274975E+10 | 4659.27 | 30-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.419937E+10 | 4659.70 | 16-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.177114E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 6391740.76 | 4196.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.419937E+10 | 4659.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.106418E+10 | 1469.22 | 28-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.783883E+09 | 1469.20 | 01-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.752430E+09 | 1468.93 | 15-MAR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.188704E+09 | 1427.81 | 10-APR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.135707E+09 | 1410.50 | 05-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 21045809.72 | 1168.12 | 01-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 21948174.27 | 1100.14 | 01-JUL-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6137347.40 | 1134.63 | 08-AUG-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 54996508.41 | 1169.85 | 30-SEP-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.436581E+09 | 1459.63 | 27-OCT-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.851290E+09 | 1469.05 | 21-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.139216E+10 | 1469.19 | 02-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.570906E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 6137347.40 | 1100.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.139216E+10 | 1469.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.131087E+10 | 1441.87 | 28-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.986358E+09 | 1441.84 | 01-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.851915E+09 | 1441.56 | 15-MAR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.253805E+09 | 1409.27 | 10-APR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.155750E+09 | 1387.18 | 05-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 19477794.68 | 1163.17 | 04-JUN-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 19908965.18 | 1206.94 | 02-JUL-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 4331896.58 | 1171.37 | 21-AUG-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 76847742.57 | 1024.34 | 25-SEP-08:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.566494E+09 | 1435.23 | 27-OCT-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.103231E+10 | 1441.90 | 23-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.156075E+10 | 1441.83 | 02-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.683881E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 4331896.58 | 1024.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.156075E+10 | 1441.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.244826E+10 | 7231.34 | 04-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.175800E+10 | 7046.80 | 02-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.188154E+10 | 7123.68 | 15-MAR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.323796E+09 | 6202.59 | 26-APR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.300906E+09 | 6310.88 | 29-MAY-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 53547568.83 | 5952.43 | 06-JUN-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 36410915.29 | 6205.46 | 29-JUL-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17225136.20 | 5874.57 | 08-AUG-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 45555245.18 | 5862.62 | 07-SEP-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.734519E+09 | 7027.70 | 27-OCT-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.179807E+10 | 7231.66 | 30-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.388003E+10 | 7232.21 | 16-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.132778E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 17225136.20 | 5862.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.388003E+10 | 7232.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.871154E+09 | 0.871154E+09 | 17047.43 | 30-APR-15:02 | 17047.43 | 0.02 |
May | 0.00 | 0.00 | 0.908508E+09 | 0.908508E+09 | 17029.33 | 22-MAY-15:02 | 17029.33 | 0.05 |
June | 0.00 | 0.00 | 0.290652E+10 | 0.269898E+10 | 31376.35 | 25-JUN-18:03 | 14441.62 | 0.18 |
July | 0.00 | 0.00 | 0.528296E+10 | 0.509039E+10 | 20042.47 | 23-JUL-16:00 | 14923.03 | 0.31 |
August | 0.00 | 0.00 | 0.612201E+10 | 0.589890E+10 | 19239.53 | 17-AUG-15:02 | 14671.97 | 0.37 |
September | 0.00 | 0.00 | 0.309486E+10 | 0.300021E+10 | 18537.15 | 10-SEP-15:55 | 13442.60 | 0.20 |
October | 0.00 | 0.00 | 0.156128E+09 | 0.156128E+09 | 8578.33 | 07-OCT-15:01 | 8578.33 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.193421E+11 | 0.186243E+11 | 0.10 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.612201E+10 | 0.589890E+10 | 31376.35 | 17047.43 | 0.37 |
Report: CoilReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.152719E+11 | 0.152564E+11 | 186075.45 | 30-APR-18:10 | 186075.45 | 0.03 |
May | 0.00 | 0.00 | 0.154628E+11 | 0.154628E+11 | 160089.16 | 22-MAY-15:21 | 160089.16 | 0.09 |
June | 0.00 | 0.00 | 0.494767E+11 | 0.471619E+11 | 335438.29 | 25-JUN-18:00 | 149312.93 | 0.31 |
July | 0.00 | 0.00 | 0.853833E+11 | 0.842582E+11 | 234725.63 | 22-JUL-18:10 | 234725.63 | 0.49 |
August | 0.00 | 0.00 | 0.994403E+11 | 0.983440E+11 | 213132.70 | 14-AUG-18:10 | 213132.70 | 0.56 |
September | 0.00 | 0.00 | 0.513385E+11 | 0.509601E+11 | 160440.29 | 11-SEP-17:04 | 160440.29 | 0.36 |
October | 0.00 | 0.00 | 0.269335E+10 | 0.269335E+10 | 72291.81 | 07-OCT-15:03 | 72291.81 | 0.01 |
November | 0.00 | 0.00 | 50951902.96 | 50951902.96 | 29307.42 | 24-NOV-11:50 | 29307.42 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.319118E+12 | 0.314188E+12 | 0.16 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.994403E+11 | 0.983440E+11 | 335438.29 | 234725.63 | 0.56 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 51301204.30 | 24176778.07 | 14329.17 | 25-JAN-16:01 | 14329.17 | 0.02 |
February | 0.00 | 0.00 | 0.267690E+09 | 0.122381E+09 | 14321.86 | 27-FEB-16:01 | 14321.86 | 0.08 |
March | 0.00 | 0.00 | 0.136805E+09 | 64419913.66 | 13372.37 | 23-MAR-18:01 | 13372.37 | 0.05 |
April | 0.00 | 0.00 | 0.297280E+10 | 0.169866E+10 | 15022.46 | 29-APR-08:61 | 15022.46 | 0.56 |
May | 0.00 | 0.00 | 0.365411E+10 | 0.202237E+10 | 16095.71 | 11-MAY-18:03 | 16095.71 | 0.63 |
June | 0.00 | 0.00 | 0.551328E+10 | 0.292119E+10 | 16617.84 | 04-JUN-15:01 | 14120.83 | 0.86 |
July | 0.00 | 0.00 | 0.687527E+10 | 0.373584E+10 | 16784.67 | 08-JUL-15:02 | 13713.98 | 0.86 |
August | 0.00 | 0.00 | 0.654508E+10 | 0.332817E+10 | 17223.13 | 08-AUG-15:01 | 13600.48 | 0.91 |
September | 0.00 | 0.00 | 0.474899E+10 | 0.241152E+10 | 17390.20 | 16-SEP-15:02 | 12449.89 | 0.80 |
October | 0.00 | 0.00 | 0.110413E+10 | 0.569643E+09 | 15692.55 | 20-OCT-15:02 | 14082.74 | 0.25 |
November | 0.00 | 0.00 | 62283202.18 | 25088704.41 | 14752.56 | 10-NOV-16:01 | 14752.56 | 0.03 |
December | 0.00 | 0.00 | 1576399.79 | 267849.47 | 1306.84 | 19-DEC-19:05 | 328.83 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.319333E+11 | 0.169237E+11 | 0.42 | |||
Minimum of Months | 0.00 | 0.00 | 1576399.79 | 267849.47 | 1306.84 | 328.83 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.687527E+10 | 0.373584E+10 | 17390.20 | 16095.71 | 0.91 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 9182999.48 | 4368965.92 | 12235.11 | 19-JAN-16:01 | 12235.11 | 0.00 |
February | 0.00 | 0.00 | 74485642.64 | 32922333.27 | 13161.17 | 27-FEB-16:01 | 13161.17 | 0.03 |
March | 0.00 | 0.00 | 68443678.22 | 29393248.13 | 12112.55 | 23-MAR-18:01 | 12112.55 | 0.03 |
April | 0.00 | 0.00 | 0.168838E+10 | 0.937418E+09 | 14217.14 | 28-APR-19:01 | 14217.14 | 0.39 |
May | 0.00 | 0.00 | 0.253859E+10 | 0.134510E+10 | 15911.35 | 22-MAY-21:31 | 14231.01 | 0.50 |
June | 0.00 | 0.00 | 0.425720E+10 | 0.217510E+10 | 17800.86 | 26-JUN-21:01 | 13823.26 | 0.73 |
July | 0.00 | 0.00 | 0.460792E+10 | 0.232771E+10 | 17067.85 | 23-JUL-21:31 | 13848.14 | 0.66 |
August | 0.00 | 0.00 | 0.362882E+10 | 0.158575E+10 | 16360.89 | 11-AUG-19:11 | 13012.82 | 0.63 |
September | 0.00 | 0.00 | 0.219606E+10 | 0.887288E+09 | 15941.74 | 14-SEP-18:01 | 15504.46 | 0.56 |
October | 0.00 | 0.00 | 0.394722E+09 | 0.197025E+09 | 14968.61 | 10-OCT-15:01 | 12641.41 | 0.11 |
November | 0.00 | 0.00 | 13621625.42 | 6002426.06 | 12667.67 | 10-NOV-16:01 | 12667.67 | 0.01 |
December | 0.00 | 0.00 | 243614.34 | 26528.82 | 429.73 | 20-DEC-19:06 | 51.95 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.194777E+11 | 0.952810E+10 | 0.31 | |||
Minimum of Months | 0.00 | 0.00 | 243614.34 | 26528.82 | 429.73 | 51.95 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.460792E+10 | 0.232771E+10 | 17800.86 | 15504.46 | 0.73 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.394761E+10 | 0.189095E+10 | 35886.74 | 21-JAN-11:25 | 23953.51 | 0.13 |
February | 0.00 | 0.00 | 0.398019E+10 | 0.289050E+10 | 30865.47 | 19-FEB-14:05 | 30865.47 | 0.10 |
March | 0.00 | 0.00 | 47762257.21 | 10693330.22 | 6000.37 | 25-MAR-11:40 | 1050.00 | 0.01 |
April | 0.00 | 0.00 | 0.256087E+11 | 0.153080E+11 | 45894.97 | 30-APR-12:40 | 33681.49 | 0.49 |
May | 0.00 | 0.00 | 0.208791E+11 | 0.718796E+10 | 36255.13 | 23-MAY-12:50 | 20509.43 | 0.66 |
June | 0.00 | 0.00 | 0.261936E+11 | 0.829697E+10 | 36616.08 | 13-JUN-13:05 | 21312.41 | 0.81 |
July | 0.00 | 0.00 | 0.342655E+11 | 0.121558E+11 | 41443.53 | 22-JUL-13:20 | 27796.73 | 0.89 |
August | 0.00 | 0.00 | 0.421380E+11 | 0.174399E+11 | 45363.19 | 20-AUG-12:50 | 32255.61 | 0.96 |
September | 0.00 | 0.00 | 0.428309E+11 | 0.210656E+11 | 55493.77 | 27-SEP-12:40 | 48768.42 | 0.90 |
October | 0.00 | 0.00 | 0.166187E+11 | 0.827341E+10 | 50960.88 | 07-OCT-13:00 | 44984.58 | 0.43 |
November | 0.00 | 0.00 | 0.302281E+10 | 0.117926E+10 | 32757.79 | 11-NOV-13:30 | 19114.48 | 0.12 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.219533E+12 | 0.956989E+11 | 0.46 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.428309E+11 | 0.210656E+11 | 55493.77 | 48768.42 | 0.96 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.181507E+10 | 0.611418E+09 | 65510.60 | 29-JAN-09:02 | 65510.60 | 0.17 |
February | 0.00 | 0.00 | 0.167638E+10 | 0.544600E+09 | 61040.26 | 07-FEB-19:03 | 58970.97 | 0.20 |
March | 0.00 | 0.00 | 0.592048E+10 | 0.238330E+10 | 70529.77 | 18-MAR-08:62 | 64870.03 | 0.38 |
April | 0.00 | 0.00 | 0.158708E+11 | 0.892478E+10 | 73729.71 | 14-APR-15:02 | 73729.71 | 0.61 |
May | 0.00 | 0.00 | 0.231723E+11 | 0.133436E+11 | 76394.84 | 11-MAY-19:31 | 76394.84 | 0.66 |
June | 0.00 | 0.00 | 0.347151E+11 | 0.211936E+11 | 84153.70 | 26-JUN-21:01 | 68341.81 | 0.66 |
July | 0.00 | 0.00 | 0.357201E+11 | 0.221109E+11 | 81578.74 | 17-JUL-21:51 | 64277.34 | 0.60 |
August | 0.00 | 0.00 | 0.295380E+11 | 0.170171E+11 | 81706.17 | 16-AUG-21:51 | 63726.45 | 0.55 |
September | 0.00 | 0.00 | 0.223708E+11 | 0.115628E+11 | 79653.13 | 10-SEP-20:31 | 63514.69 | 0.61 |
October | 0.00 | 0.00 | 0.959484E+10 | 0.384256E+10 | 74082.66 | 07-OCT-18:01 | 74082.66 | 0.51 |
November | 0.00 | 0.00 | 0.336541E+10 | 0.112300E+10 | 70649.98 | 24-NOV-19:03 | 61257.54 | 0.26 |
December | 0.00 | 0.00 | 0.703315E+09 | 0.208613E+09 | 61638.38 | 02-DEC-09:02 | 61638.38 | 0.11 |
Annual Sum or Average | 0.00 | 0.00 | 0.184463E+12 | 0.102866E+12 | 0.44 | |||
Minimum of Months | 0.00 | 0.00 | 0.703315E+09 | 0.208613E+09 | 61040.26 | 58970.97 | 0.11 | |
Maximum of Months | 0.00 | 0.00 | 0.357201E+11 | 0.221109E+11 | 84153.70 | 76394.84 | 0.66 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.104612E+09 | 43357193.32 | 12362.60 | 19-JAN-16:01 | 12362.60 | 0.03 |
February | 0.00 | 0.00 | 0.178615E+09 | 78354270.97 | 12991.43 | 27-FEB-16:01 | 12991.43 | 0.06 |
March | 0.00 | 0.00 | 0.108401E+09 | 38429825.12 | 12768.87 | 25-MAR-15:01 | 12768.87 | 0.05 |
April | 0.00 | 0.00 | 0.338206E+10 | 0.186974E+10 | 13392.28 | 23-APR-08:62 | 13392.28 | 0.63 |
May | 0.00 | 0.00 | 0.368391E+10 | 0.190641E+10 | 15311.06 | 11-MAY-18:01 | 15311.06 | 0.67 |
June | 0.00 | 0.00 | 0.515798E+10 | 0.260888E+10 | 15313.07 | 04-JUN-08:61 | 12768.73 | 0.87 |
July | 0.00 | 0.00 | 0.645088E+10 | 0.334470E+10 | 15260.65 | 08-JUL-15:02 | 12645.20 | 0.91 |
August | 0.00 | 0.00 | 0.677143E+10 | 0.349908E+10 | 15731.65 | 08-AUG-15:01 | 12396.81 | 0.93 |
September | 0.00 | 0.00 | 0.527751E+10 | 0.272717E+10 | 15785.24 | 16-SEP-15:02 | 11700.60 | 0.86 |
October | 0.00 | 0.00 | 0.120399E+10 | 0.622291E+09 | 15156.71 | 06-OCT-18:01 | 15156.71 | 0.27 |
November | 0.00 | 0.00 | 97128641.75 | 36903024.98 | 12791.77 | 13-NOV-09:02 | 12791.77 | 0.03 |
December | 0.00 | 0.00 | 25067528.06 | 5134149.76 | 1596.37 | 26-DEC-09:04 | 547.48 | 0.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.324416E+11 | 0.167805E+11 | 0.44 | |||
Minimum of Months | 0.00 | 0.00 | 25067528.06 | 5134149.76 | 1596.37 | 547.48 | 0.02 | |
Maximum of Months | 0.00 | 0.00 | 0.677143E+10 | 0.349908E+10 | 15785.24 | 15311.06 | 0.93 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 7049034.75 | 1055450.49 | 1498.71 | 21-JAN-09:02 | 467.65 | 0.01 |
February | 0.00 | 0.00 | 34739019.46 | 10617830.30 | 11087.66 | 23-FEB-09:02 | 11087.66 | 0.02 |
March | 0.00 | 0.00 | 33719428.96 | 11296331.06 | 9728.15 | 25-MAR-15:01 | 8547.89 | 0.02 |
April | 0.00 | 0.00 | 0.202740E+10 | 0.111087E+10 | 13262.88 | 28-APR-08:51 | 13262.88 | 0.47 |
May | 0.00 | 0.00 | 0.263414E+10 | 0.136711E+10 | 13866.95 | 11-MAY-19:31 | 13866.95 | 0.57 |
June | 0.00 | 0.00 | 0.403037E+10 | 0.203983E+10 | 15697.98 | 13-JUN-08:32 | 15116.41 | 0.76 |
July | 0.00 | 0.00 | 0.456528E+10 | 0.233571E+10 | 15864.06 | 23-JUL-08:32 | 15864.06 | 0.73 |
August | 0.00 | 0.00 | 0.414508E+10 | 0.201063E+10 | 14370.36 | 16-AUG-21:51 | 10891.54 | 0.71 |
September | 0.00 | 0.00 | 0.281112E+10 | 0.132741E+10 | 14348.68 | 16-SEP-15:02 | 10457.39 | 0.66 |
October | 0.00 | 0.00 | 0.437467E+09 | 0.213068E+09 | 13256.91 | 06-OCT-18:01 | 13256.91 | 0.13 |
November | 0.00 | 0.00 | 14213564.12 | 4248721.46 | 9289.70 | 11-NOV-09:02 | 8284.32 | 0.01 |
December | 0.00 | 0.00 | 969215.70 | 180396.52 | 1061.52 | 20-DEC-09:06 | 233.16 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.207416E+11 | 0.104320E+11 | 0.34 | |||
Minimum of Months | 0.00 | 0.00 | 969215.70 | 180396.52 | 1061.52 | 233.16 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.456528E+10 | 0.233571E+10 | 15864.06 | 15864.06 | 0.76 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 11713349.36 | 5410342.78 | 3808.85 | 19-JAN-16:01 | 3808.85 | 0.02 |
February | 0.00 | 0.00 | 69595899.22 | 33369110.32 | 3739.48 | 05-FEB-16:01 | 3739.48 | 0.06 |
March | 0.00 | 0.00 | 31795384.41 | 14739470.75 | 3722.57 | 25-MAR-15:01 | 3722.57 | 0.04 |
April | 0.00 | 0.00 | 0.783035E+09 | 0.483139E+09 | 4016.75 | 29-APR-08:61 | 3954.98 | 0.48 |
May | 0.00 | 0.00 | 0.930446E+09 | 0.555617E+09 | 4408.60 | 11-MAY-18:01 | 4408.60 | 0.52 |
June | 0.00 | 0.00 | 0.138935E+10 | 0.788248E+09 | 4606.83 | 04-JUN-08:61 | 3352.47 | 0.77 |
July | 0.00 | 0.00 | 0.174835E+10 | 0.998428E+09 | 4531.50 | 08-JUL-08:61 | 3366.35 | 0.82 |
August | 0.00 | 0.00 | 0.160326E+10 | 0.864533E+09 | 4591.36 | 08-AUG-15:01 | 3530.97 | 0.87 |
September | 0.00 | 0.00 | 0.112056E+10 | 0.605945E+09 | 4616.08 | 16-SEP-15:02 | 3126.56 | 0.69 |
October | 0.00 | 0.00 | 0.252248E+09 | 0.140343E+09 | 4136.85 | 20-OCT-15:02 | 3536.34 | 0.19 |
November | 0.00 | 0.00 | 15194359.33 | 6235827.28 | 3940.81 | 10-NOV-16:01 | 3940.81 | 0.02 |
December | 0.00 | 0.00 | 56891.15 | 8867.47 | 238.75 | 18-DEC-16:03 | 49.02 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.795560E+10 | 0.449602E+10 | 0.37 | |||
Minimum of Months | 0.00 | 0.00 | 56891.15 | 8867.47 | 238.75 | 49.02 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.174835E+10 | 0.998428E+09 | 4616.08 | 4408.60 | 0.87 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 1105633.47 | 561051.42 | 3202.31 | 19-JAN-16:01 | 3202.31 | 0.00 |
February | 0.00 | 0.00 | 15042191.12 | 6315946.95 | 3479.08 | 27-FEB-16:01 | 3479.08 | 0.02 |
March | 0.00 | 0.00 | 15021111.02 | 6184510.37 | 3190.41 | 23-MAR-18:01 | 3190.41 | 0.02 |
April | 0.00 | 0.00 | 0.446686E+09 | 0.270382E+09 | 3706.14 | 28-APR-19:01 | 3706.14 | 0.32 |
May | 0.00 | 0.00 | 0.643740E+09 | 0.364547E+09 | 4320.77 | 22-MAY-21:31 | 3906.14 | 0.41 |
June | 0.00 | 0.00 | 0.108078E+10 | 0.590705E+09 | 4550.24 | 26-JUN-21:01 | 3699.50 | 0.67 |
July | 0.00 | 0.00 | 0.120839E+10 | 0.637018E+09 | 4676.12 | 25-JUL-19:42 | 4316.39 | 0.64 |
August | 0.00 | 0.00 | 0.892487E+09 | 0.408173E+09 | 4430.89 | 17-AUG-21:11 | 3636.15 | 0.63 |
September | 0.00 | 0.00 | 0.480145E+09 | 0.208054E+09 | 4320.93 | 12-SEP-20:11 | 3557.67 | 0.45 |
October | 0.00 | 0.00 | 81962808.60 | 43985052.96 | 3971.78 | 10-OCT-15:01 | 3250.83 | 0.07 |
November | 0.00 | 0.00 | 1680082.60 | 800439.55 | 3339.88 | 10-NOV-16:01 | 3339.88 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.486704E+10 | 0.253673E+10 | 0.27 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.120839E+10 | 0.637018E+09 | 4676.12 | 4316.39 | 0.67 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.144429E+10 | 0.738488E+09 | 22080.44 | 23-JAN-16:01 | 22080.44 | 0.20 |
February | 0.00 | 0.00 | 0.176265E+10 | 0.881979E+09 | 21922.98 | 07-FEB-16:02 | 21084.63 | 0.27 |
March | 0.00 | 0.00 | 0.614545E+09 | 0.224230E+09 | 22060.67 | 25-MAR-15:01 | 22060.67 | 0.17 |
April | 0.00 | 0.00 | 0.596451E+10 | 0.338419E+10 | 21819.03 | 29-APR-08:61 | 21819.03 | 0.68 |
May | 0.00 | 0.00 | 0.513390E+10 | 0.249404E+10 | 24548.77 | 11-MAY-18:01 | 24548.77 | 0.66 |
June | 0.00 | 0.00 | 0.672918E+10 | 0.305790E+10 | 24732.13 | 26-JUN-18:02 | 20527.74 | 0.84 |
July | 0.00 | 0.00 | 0.859779E+10 | 0.411271E+10 | 24865.11 | 08-JUL-15:02 | 20207.61 | 0.86 |
August | 0.00 | 0.00 | 0.990920E+10 | 0.514283E+10 | 25480.11 | 08-AUG-15:01 | 19637.82 | 0.90 |
September | 0.00 | 0.00 | 0.967862E+10 | 0.568334E+10 | 25638.54 | 16-SEP-15:02 | 18789.32 | 0.87 |
October | 0.00 | 0.00 | 0.381664E+10 | 0.213403E+10 | 24552.76 | 06-OCT-18:01 | 24552.76 | 0.46 |
November | 0.00 | 0.00 | 0.116186E+10 | 0.497231E+09 | 20942.85 | 10-NOV-16:01 | 20942.85 | 0.21 |
December | 0.00 | 0.00 | 0.439658E+09 | 0.186951E+09 | 21101.94 | 21-DEC-16:02 | 21101.94 | 0.08 |
Annual Sum or Average | 0.00 | 0.00 | 0.552529E+11 | 0.285379E+11 | 0.52 | |||
Minimum of Months | 0.00 | 0.00 | 0.439658E+09 | 0.186951E+09 | 20942.85 | 18789.32 | 0.08 | |
Maximum of Months | 0.00 | 0.00 | 0.990920E+10 | 0.568334E+10 | 25638.54 | 24552.76 | 0.90 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 34221.23 | 163151.32 | 28-JAN-19:04 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 23762.13 | 157637.56 | 26-FEB-19:04 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 32620.67 | 141981.40 | 17-MAR-15:04 |
April | 0.00 | 0.00 | 01-APR-00:10 | 31135.07 | 132127.96 | 05-APR-08:05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 38544.88 | 130764.86 | 05-MAY-08:05 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 28950.39 | 113930.99 | 07-JUN-10:15 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19051.67 | 103895.53 | 31-JUL-04:30 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 14195.26 | 101170.58 | 20-AUG-05:07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 28367.17 | 123538.24 | 28-SEP-06:05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 43572.34 | 164474.96 | 19-OCT-08:04 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 45879.68 | 164512.21 | 21-NOV-16:02 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 30223.21 | 172812.60 | 16-DEC-16:04 |
Annual Sum or Average | 0.00 | 30905.80 | ||||
Minimum of Months | 0.00 | 0.00 | 14195.26 | 101170.58 | ||
Maximum of Months | 0.00 | 0.00 | 45879.68 | 172812.60 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 3542.15 | 72965.36 | 19-JAN-16:01 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 4267.74 | 75868.68 | 27-FEB-16:01 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 3555.88 | 72924.13 | 20-MAR-15:01 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 31308.48 | 359507.68 | 30-APR-18:03 | 0.00 | 0.00 | 01-APR-00:10 |
May | 32235.28 | 345268.94 | 22-MAY-15:03 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 57408.37 | 440543.18 | 25-JUN-18:03 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 75698.38 | 424902.94 | 22-JUL-18:03 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 81761.45 | 397274.00 | 14-AUG-18:03 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 59177.37 | 361557.07 | 13-SEP-15:03 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 15351.33 | 251755.50 | 07-OCT-15:03 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 3927.22 | 84967.26 | 05-NOV-15:01 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 814.36 | 29157.22 | 21-DEC-19:02 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 30892.78 | 0.00 | ||||
Minimum of Months | 814.36 | 29157.22 | 0.00 | 0.00 | ||
Maximum of Months | 81761.45 | 440543.18 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 26989.55 | 56695.31 | 31-JAN-07:20 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 27172.48 | 56785.25 | 14-FEB-07:50 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 27011.04 | 56692.35 | 01-MAR-07:40 |
April | 0.00 | 0.00 | 01-APR-00:10 | 26491.61 | 55848.28 | 03-APR-07:00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 25798.33 | 54620.10 | 01-MAY-06:20 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25107.04 | 53071.03 | 01-JUN-06:40 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 24567.41 | 51700.90 | 03-JUL-06:15 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 24399.59 | 50998.77 | 31-AUG-06:20 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 24573.74 | 51705.28 | 29-SEP-06:40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25075.58 | 53077.30 | 31-OCT-07:00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 25775.23 | 54577.56 | 30-NOV-07:50 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 26472.62 | 55853.03 | 29-DEC-07:40 |
Annual Sum or Average | 0.00 | 25778.07 | ||||
Minimum of Months | 0.00 | 0.00 | 24399.59 | 50998.77 | ||
Maximum of Months | 0.00 | 0.00 | 27172.48 | 56785.25 |
Report: FanReportMonthly
For: FLR_3_DOAS FAN
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.271000E+10 | 0.70 | 1299.30 | 04-JAN-09:13 | 0.88 |
February | 0.244774E+10 | 0.70 | 1299.30 | 01-FEB-09:04 | 0.88 |
March | 0.271000E+10 | 0.70 | 1299.30 | 01-MAR-09:02 | 0.88 |
April | 0.262258E+10 | 0.70 | 1299.30 | 04-APR-18:07 | 0.88 |
May | 0.271000E+10 | 0.70 | 1299.30 | 01-MAY-15:09 | 0.88 |
June | 0.262258E+10 | 0.70 | 1299.30 | 01-JUN-15:18 | 0.88 |
July | 0.271000E+10 | 0.70 | 1299.30 | 01-JUL-18:09 | 0.88 |
August | 0.271000E+10 | 0.70 | 1299.30 | 01-AUG-15:16 | 0.88 |
September | 0.262258E+10 | 0.70 | 1299.30 | 02-SEP-18:30 | 0.88 |
October | 0.271000E+10 | 0.70 | 1299.30 | 01-OCT-15:15 | 0.88 |
November | 0.262258E+10 | 0.70 | 1299.30 | 03-NOV-15:03 | 0.89 |
December | 0.271000E+10 | 0.70 | 1299.30 | 04-DEC-19:02 | 0.88 |
Annual Sum or Average | 0.319080E+11 | 0.70 | |||
Minimum of Months | 0.244774E+10 | 0.70 | 1299.30 | 0.88 | |
Maximum of Months | 0.271000E+10 | 0.70 | 1299.30 | 0.89 |
Report: FanReportMonthly
For: VAV WITH REHEAT FAN
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.333673E+11 | 0.79 | 18171.38 | 18-JAN-22:10 | 0.98 |
February | 0.302781E+11 | 0.80 | 18119.86 | 27-FEB-21:10 | 0.98 |
March | 0.339936E+11 | 0.80 | 18403.04 | 20-MAR-21:10 | 0.99 |
April | 0.338956E+11 | 0.82 | 22368.44 | 28-APR-21:10 | 1.11 |
May | 0.353337E+11 | 0.82 | 22687.55 | 23-MAY-21:10 | 1.12 |
June | 0.350132E+11 | 0.83 | 23874.90 | 13-JUN-21:10 | 1.15 |
July | 0.364633E+11 | 0.83 | 24085.81 | 21-JUL-21:10 | 1.16 |
August | 0.365072E+11 | 0.83 | 24270.18 | 14-AUG-21:10 | 1.17 |
September | 0.347985E+11 | 0.82 | 24348.70 | 12-SEP-21:10 | 1.17 |
October | 0.345802E+11 | 0.81 | 21500.81 | 03-OCT-21:10 | 1.09 |
November | 0.328207E+11 | 0.80 | 19266.60 | 08-NOV-22:10 | 1.01 |
December | 0.331984E+11 | 0.79 | 18194.94 | 20-DEC-21:10 | 0.98 |
Annual Sum or Average | 0.410250E+12 | 0.81 | |||
Minimum of Months | 0.302781E+11 | 0.79 | 18119.86 | 0.98 | |
Maximum of Months | 0.365072E+11 | 0.83 | 24348.70 | 1.17 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205205E+09 | 0.27 | 76.61 | 01-JAN-00:10 | 0.27 |
February | 0.185347E+09 | 0.27 | 76.61 | 01-FEB-00:03 | 0.27 |
March | 0.205205E+09 | 0.27 | 76.61 | 01-MAR-00:03 | 0.27 |
April | 0.198586E+09 | 0.27 | 76.61 | 01-APR-00:10 | 0.27 |
May | 0.205205E+09 | 0.27 | 76.61 | 01-MAY-00:05 | 0.27 |
June | 0.198586E+09 | 0.27 | 76.61 | 01-JUN-00:05 | 0.27 |
July | 0.205205E+09 | 0.27 | 76.61 | 01-JUL-00:10 | 0.27 |
August | 0.205205E+09 | 0.27 | 76.61 | 01-AUG-00:05 | 0.27 |
September | 0.198586E+09 | 0.27 | 76.61 | 01-SEP-00:05 | 0.27 |
October | 0.205205E+09 | 0.27 | 76.61 | 01-OCT-00:10 | 0.27 |
November | 0.198586E+09 | 0.27 | 76.61 | 01-NOV-00:05 | 0.27 |
December | 0.205205E+09 | 0.27 | 76.61 | 01-DEC-00:03 | 0.27 |
Annual Sum or Average | 0.241613E+10 | 0.27 | |||
Minimum of Months | 0.185347E+09 | 0.27 | 76.61 | 0.27 | |
Maximum of Months | 0.205205E+09 | 0.27 | 76.61 | 0.27 |
Report: FanReportMonthly
For: LOBBY_FLR_1 EXHAUST FAN
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:10 | -0.0 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:03 | -0.0 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | -0.0 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 EXHAUST FAN
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 EXHAUST FAN
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116283E+10 | 0.19 | 612.92 | 01-JAN-07:05 | 0.27 |
February | 0.105030E+10 | 0.19 | 612.92 | 01-FEB-07:05 | 0.27 |
March | 0.116283E+10 | 0.19 | 612.92 | 01-MAR-07:05 | 0.27 |
April | 0.112532E+10 | 0.19 | 612.92 | 01-APR-06:05 | 0.27 |
May | 0.116283E+10 | 0.19 | 612.92 | 01-MAY-06:05 | 0.27 |
June | 0.112532E+10 | 0.19 | 612.92 | 01-JUN-06:05 | 0.27 |
July | 0.116283E+10 | 0.19 | 612.92 | 01-JUL-06:10 | 0.27 |
August | 0.116283E+10 | 0.19 | 612.92 | 01-AUG-06:05 | 0.27 |
September | 0.112532E+10 | 0.19 | 612.92 | 01-SEP-06:05 | 0.27 |
October | 0.116283E+10 | 0.19 | 612.92 | 01-OCT-06:10 | 0.27 |
November | 0.112532E+10 | 0.19 | 612.92 | 01-NOV-06:05 | 0.27 |
December | 0.116283E+10 | 0.19 | 612.92 | 01-DEC-07:10 | 0.27 |
Annual Sum or Average | 0.136914E+11 | 0.19 | |||
Minimum of Months | 0.105030E+10 | 0.19 | 612.92 | 0.27 | |
Maximum of Months | 0.116283E+10 | 0.19 | 612.92 | 0.27 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.289087E+09 | 0.42 | 825.44 | 01-JAN-19:02 | 0.58 |
February | 0.230509E+09 | 0.43 | 825.44 | 01-FEB-09:02 | 0.58 |
March | 0.225613E+09 | 0.41 | 825.44 | 01-MAR-09:02 | 0.58 |
April | 0.208220E+09 | 0.48 | 825.44 | 01-APR-15:01 | 0.58 |
May | 0.217234E+09 | 0.48 | 825.44 | 01-MAY-08:62 | 0.58 |
June | 0.261951E+09 | 0.51 | 825.44 | 01-JUN-08:62 | 0.58 |
July | 0.319976E+09 | 0.52 | 825.44 | 01-JUL-08:62 | 0.58 |
August | 0.299413E+09 | 0.53 | 825.44 | 01-AUG-08:62 | 0.58 |
September | 0.235645E+09 | 0.51 | 825.44 | 01-SEP-15:01 | 0.58 |
October | 0.181019E+09 | 0.44 | 825.44 | 01-OCT-08:62 | 0.58 |
November | 0.244147E+09 | 0.42 | 825.44 | 01-NOV-08:62 | 0.58 |
December | 0.370969E+09 | 0.44 | 825.44 | 01-DEC-09:02 | 0.58 |
Annual Sum or Average | 0.308378E+10 | 0.47 | |||
Minimum of Months | 0.181019E+09 | 0.41 | 825.44 | 0.58 | |
Maximum of Months | 0.370969E+09 | 0.53 | 825.44 | 0.58 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.321481E+09 | 0.43 | 739.54 | 01-JAN-09:02 | 0.58 |
February | 0.250583E+09 | 0.41 | 739.54 | 01-FEB-09:02 | 0.58 |
March | 0.227972E+09 | 0.41 | 739.54 | 01-MAR-09:02 | 0.58 |
April | 0.155998E+09 | 0.43 | 739.54 | 01-APR-15:01 | 0.58 |
May | 0.161903E+09 | 0.43 | 739.54 | 01-MAY-08:62 | 0.58 |
June | 0.199206E+09 | 0.44 | 739.54 | 01-JUN-08:62 | 0.58 |
July | 0.207870E+09 | 0.40 | 739.54 | 01-JUL-08:62 | 0.58 |
August | 0.162010E+09 | 0.37 | 739.54 | 01-AUG-08:51 | 0.58 |
September | 0.119137E+09 | 0.39 | 739.54 | 01-SEP-15:01 | 0.58 |
October | 0.169929E+09 | 0.41 | 739.54 | 01-OCT-15:02 | 0.58 |
November | 0.264797E+09 | 0.42 | 739.54 | 01-NOV-08:62 | 0.58 |
December | 0.381643E+09 | 0.45 | 739.54 | 01-DEC-09:02 | 0.58 |
Annual Sum or Average | 0.262253E+10 | 0.42 | |||
Minimum of Months | 0.119137E+09 | 0.37 | 739.54 | 0.58 | |
Maximum of Months | 0.381643E+09 | 0.45 | 739.54 | 0.58 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.184417E+09 | 0.10 | 1301.82 | 21-JAN-11:25 | 0.58 |
February | 0.185457E+09 | 0.12 | 1052.22 | 19-FEB-14:05 | 0.58 |
March | 3613137.80 | 0.01 | 341.29 | 25-MAR-11:40 | 0.58 |
April | 0.105400E+10 | 0.41 | 1518.54 | 15-APR-13:15 | 0.58 |
May | 0.878798E+09 | 0.39 | 1178.78 | 22-MAY-13:05 | 0.58 |
June | 0.101743E+10 | 0.47 | 1182.40 | 13-JUN-13:20 | 0.58 |
July | 0.128296E+10 | 0.52 | 1335.69 | 22-JUL-13:30 | 0.58 |
August | 0.153620E+10 | 0.55 | 1438.10 | 20-AUG-13:00 | 0.58 |
September | 0.155354E+10 | 0.52 | 1750.14 | 27-SEP-12:50 | 0.58 |
October | 0.664535E+09 | 0.26 | 1722.02 | 07-OCT-13:05 | 0.58 |
November | 0.143671E+09 | 0.09 | 1138.06 | 11-NOV-13:30 | 0.58 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.850462E+10 | 0.29 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.155354E+10 | 0.55 | 1750.14 | 0.58 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.876264E+09 | 0.41 | 3760.60 | 01-JAN-09:02 | 0.58 |
February | 0.669740E+09 | 0.41 | 3760.60 | 01-FEB-16:02 | 0.58 |
March | 0.617938E+09 | 0.41 | 3760.60 | 01-MAR-19:02 | 0.58 |
April | 0.864804E+09 | 0.40 | 3760.60 | 01-APR-08:62 | 0.58 |
May | 0.110159E+10 | 0.39 | 3760.60 | 01-MAY-08:62 | 0.58 |
June | 0.152368E+10 | 0.39 | 3760.60 | 01-JUN-08:62 | 0.58 |
July | 0.154915E+10 | 0.35 | 3760.60 | 01-JUL-08:62 | 0.58 |
August | 0.125611E+10 | 0.32 | 3760.60 | 01-AUG-08:51 | 0.58 |
September | 0.991894E+09 | 0.35 | 3760.60 | 01-SEP-08:53 | 0.58 |
October | 0.588501E+09 | 0.40 | 3760.60 | 01-OCT-08:62 | 0.58 |
November | 0.630307E+09 | 0.41 | 3760.60 | 01-NOV-08:62 | 0.58 |
December | 0.963825E+09 | 0.41 | 3760.60 | 01-DEC-16:02 | 0.58 |
Annual Sum or Average | 0.116338E+11 | 0.39 | |||
Minimum of Months | 0.588501E+09 | 0.32 | 3760.60 | 0.58 | |
Maximum of Months | 0.154915E+10 | 0.41 | 3760.60 | 0.58 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.273076E+09 | 0.42 | 753.99 | 01-JAN-19:02 | 0.58 |
February | 0.218889E+09 | 0.41 | 753.99 | 01-FEB-09:02 | 0.58 |
March | 0.210845E+09 | 0.41 | 753.99 | 01-MAR-09:02 | 0.58 |
April | 0.214368E+09 | 0.51 | 753.99 | 01-APR-15:01 | 0.58 |
May | 0.210150E+09 | 0.51 | 753.99 | 01-MAY-08:62 | 0.58 |
June | 0.239482E+09 | 0.53 | 753.99 | 01-JUN-08:62 | 0.58 |
July | 0.288126E+09 | 0.54 | 753.99 | 01-JUL-08:62 | 0.58 |
August | 0.302190E+09 | 0.54 | 753.99 | 01-AUG-08:62 | 0.58 |
September | 0.249027E+09 | 0.53 | 753.99 | 01-SEP-15:01 | 0.58 |
October | 0.175153E+09 | 0.45 | 753.99 | 01-OCT-08:62 | 0.58 |
November | 0.229873E+09 | 0.41 | 753.99 | 01-NOV-08:62 | 0.58 |
December | 0.336395E+09 | 0.43 | 753.99 | 01-DEC-09:02 | 0.58 |
Annual Sum or Average | 0.294757E+10 | 0.48 | |||
Minimum of Months | 0.175153E+09 | 0.41 | 753.99 | 0.58 | |
Maximum of Months | 0.336395E+09 | 0.54 | 753.99 | 0.58 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.302070E+09 | 0.43 | 681.47 | 01-JAN-16:01 | 0.58 |
February | 0.243417E+09 | 0.41 | 681.47 | 01-FEB-09:02 | 0.58 |
March | 0.213814E+09 | 0.41 | 681.47 | 01-MAR-09:02 | 0.58 |
April | 0.159829E+09 | 0.46 | 681.47 | 01-APR-15:01 | 0.58 |
May | 0.164854E+09 | 0.46 | 681.47 | 01-MAY-08:62 | 0.58 |
June | 0.190090E+09 | 0.47 | 681.47 | 01-JUN-08:62 | 0.58 |
July | 0.206969E+09 | 0.44 | 681.47 | 01-JUL-08:62 | 0.58 |
August | 0.188616E+09 | 0.41 | 681.47 | 01-AUG-08:51 | 0.58 |
September | 0.145151E+09 | 0.45 | 681.47 | 01-SEP-15:01 | 0.58 |
October | 0.159515E+09 | 0.41 | 681.47 | 01-OCT-08:62 | 0.58 |
November | 0.247994E+09 | 0.42 | 681.47 | 01-NOV-08:62 | 0.58 |
December | 0.348179E+09 | 0.45 | 681.47 | 01-DEC-09:02 | 0.58 |
Annual Sum or Average | 0.257050E+10 | 0.43 | |||
Minimum of Months | 0.145151E+09 | 0.41 | 681.47 | 0.58 | |
Maximum of Months | 0.348179E+09 | 0.47 | 681.47 | 0.58 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 92479957.82 | 0.44 | 217.26 | 01-JAN-09:02 | 0.58 |
February | 73220684.04 | 0.43 | 217.26 | 01-FEB-09:02 | 0.58 |
March | 71833209.85 | 0.41 | 217.26 | 01-MAR-09:02 | 0.58 |
April | 62987098.71 | 0.49 | 217.26 | 01-APR-15:01 | 0.58 |
May | 62844292.63 | 0.48 | 217.26 | 01-MAY-15:01 | 0.58 |
June | 68889949.20 | 0.51 | 217.26 | 01-JUN-15:01 | 0.58 |
July | 84398571.15 | 0.52 | 217.26 | 01-JUL-15:01 | 0.58 |
August | 74742446.59 | 0.53 | 217.26 | 01-AUG-15:01 | 0.58 |
September | 61014366.69 | 0.51 | 217.26 | 01-SEP-15:01 | 0.58 |
October | 58506876.37 | 0.44 | 217.26 | 01-OCT-15:02 | 0.58 |
November | 78318229.95 | 0.42 | 217.26 | 01-NOV-08:62 | 0.58 |
December | 0.115776E+09 | 0.46 | 217.26 | 01-DEC-09:02 | 0.58 |
Annual Sum or Average | 0.905012E+09 | 0.47 | |||
Minimum of Months | 58506876.37 | 0.41 | 217.26 | 0.58 | |
Maximum of Months | 0.115776E+09 | 0.53 | 217.26 | 0.58 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.104338E+09 | 0.46 | 193.16 | 01-JAN-09:02 | 0.58 |
February | 77327554.13 | 0.42 | 193.16 | 01-FEB-09:02 | 0.58 |
March | 71405114.69 | 0.41 | 193.16 | 01-MAR-09:02 | 0.58 |
April | 49117547.35 | 0.44 | 193.16 | 01-APR-08:62 | 0.58 |
May | 48445392.11 | 0.43 | 193.16 | 01-MAY-15:01 | 0.58 |
June | 53015035.00 | 0.45 | 193.16 | 01-JUN-08:62 | 0.58 |
July | 56702773.32 | 0.41 | 193.16 | 01-JUL-08:62 | 0.58 |
August | 40422669.98 | 0.38 | 193.16 | 01-AUG-08:51 | 0.58 |
September | 31982412.03 | 0.40 | 193.16 | 01-SEP-15:01 | 0.58 |
October | 56029487.11 | 0.41 | 193.16 | 01-OCT-15:02 | 0.58 |
November | 82559356.09 | 0.43 | 193.16 | 01-NOV-08:62 | 0.58 |
December | 0.118814E+09 | 0.50 | 193.16 | 01-DEC-09:02 | 0.58 |
Annual Sum or Average | 0.790159E+09 | 0.43 | |||
Minimum of Months | 31982412.03 | 0.38 | 193.16 | 0.58 | |
Maximum of Months | 0.118814E+09 | 0.50 | 193.16 | 0.58 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL_FANCOILFAN
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.340256E+09 | 0.45 | 1206.39 | 01-JAN-16:01 | 0.58 |
February | 0.285821E+09 | 0.46 | 1206.39 | 01-FEB-09:02 | 0.58 |
March | 0.260640E+09 | 0.42 | 1206.39 | 01-MAR-09:02 | 0.58 |
April | 0.338737E+09 | 0.52 | 1206.39 | 01-APR-15:01 | 0.58 |
May | 0.288506E+09 | 0.50 | 1206.39 | 01-MAY-08:62 | 0.58 |
June | 0.309627E+09 | 0.51 | 1206.39 | 01-JUN-08:62 | 0.58 |
July | 0.380151E+09 | 0.52 | 1206.39 | 01-JUL-08:62 | 0.58 |
August | 0.431454E+09 | 0.53 | 1206.39 | 01-AUG-15:01 | 0.58 |
September | 0.439544E+09 | 0.53 | 1206.39 | 01-SEP-15:01 | 0.58 |
October | 0.282591E+09 | 0.47 | 1206.39 | 01-OCT-08:62 | 0.58 |
November | 0.274119E+09 | 0.45 | 1206.39 | 01-NOV-15:02 | 0.58 |
December | 0.417417E+09 | 0.44 | 1206.39 | 01-DEC-09:02 | 0.58 |
Annual Sum or Average | 0.404886E+10 | 0.48 | |||
Minimum of Months | 0.260640E+09 | 0.42 | 1206.39 | 0.58 | |
Maximum of Months | 0.439544E+09 | 0.53 | 1206.39 | 0.58 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.731597E+09 | 0.658437E+09 | 726.82 | 28-JAN-19:04 | 654.14 | 654.14 | 34.10 | 1.51 |
February | 0.496054E+09 | 0.446449E+09 | 721.64 | 26-FEB-19:04 | 649.47 | 649.47 | 34.38 | 1.47 |
March | 0.652440E+09 | 0.587196E+09 | 699.79 | 10-MAR-16:04 | 629.81 | 629.81 | 35.38 | 1.34 |
April | 0.533488E+09 | 0.480139E+09 | 681.71 | 05-APR-08:05 | 613.54 | 613.54 | 34.80 | 1.25 |
May | 0.643352E+09 | 0.579016E+09 | 674.17 | 05-MAY-08:05 | 606.75 | 606.75 | 34.37 | 1.22 |
June | 0.462778E+09 | 0.416500E+09 | 654.64 | 08-JUN-06:05 | 589.18 | 589.18 | 40.91 | 1.14 |
July | 0.315769E+09 | 0.284192E+09 | 609.28 | 09-JUL-04:00 | 548.35 | 548.35 | 35.33 | 0.98 |
August | 0.235976E+09 | 0.212379E+09 | 597.78 | 20-AUG-05:07 | 538.00 | 538.00 | 34.51 | 0.95 |
September | 0.455023E+09 | 0.409521E+09 | 677.40 | 28-SEP-06:05 | 609.66 | 609.66 | 36.06 | 1.23 |
October | 0.752732E+09 | 0.677459E+09 | 735.22 | 19-OCT-08:04 | 661.70 | 661.70 | 34.89 | 1.57 |
November | 0.817365E+09 | 0.735629E+09 | 729.69 | 21-NOV-16:02 | 656.72 | 656.72 | 34.22 | 1.53 |
December | 0.683467E+09 | 0.615120E+09 | 739.32 | 16-DEC-16:04 | 665.38 | 665.38 | 34.15 | 1.60 |
Annual Sum or Average | 0.678004E+10 | 0.610204E+10 | ||||||
Minimum of Months | 0.235976E+09 | 0.212379E+09 | 597.78 | 538.00 | 538.00 | 34.10 | 0.95 | |
Maximum of Months | 0.817365E+09 | 0.735629E+09 | 739.32 | 665.38 | 665.38 | 40.91 | 1.60 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.243527E+09 | 0.219174E+09 | 1508.78 | 19-JAN-16:01 | 1357.91 | 1357.91 | 6.72 | 3.82 |
February | 0.266693E+09 | 0.240024E+09 | 1571.76 | 27-FEB-16:01 | 1414.58 | 1414.58 | 6.72 | 4.05 |
March | 0.261911E+09 | 0.235720E+09 | 1514.55 | 20-MAR-15:01 | 1363.09 | 1363.09 | 6.72 | 3.84 |
April | 0.168164E+10 | 0.151347E+10 | 2437.49 | 29-APR-15:03 | 2193.74 | 2193.74 | 6.72 | 10.16 |
May | 0.180598E+10 | 0.162538E+10 | 2411.75 | 22-MAY-15:02 | 2170.57 | 2170.57 | 6.72 | 9.75 |
June | 0.251260E+10 | 0.226134E+10 | 2515.05 | 12-JUN-18:02 | 2263.54 | 2263.54 | 6.72 | 11.63 |
July | 0.311336E+10 | 0.280202E+10 | 2557.08 | 22-JUL-18:03 | 2301.37 | 2301.37 | 6.72 | 12.53 |
August | 0.334600E+10 | 0.301140E+10 | 2577.86 | 14-AUG-18:30 | 2320.08 | 2320.08 | 6.72 | 12.97 |
September | 0.260031E+10 | 0.234028E+10 | 2508.38 | 25-SEP-15:03 | 2257.54 | 2257.54 | 6.72 | 11.49 |
October | 0.934548E+09 | 0.841094E+09 | 2198.90 | 07-OCT-15:03 | 1979.01 | 1979.01 | 6.72 | 7.41 |
November | 0.262472E+09 | 0.236225E+09 | 1627.14 | 05-NOV-15:01 | 1464.42 | 1464.42 | 6.72 | 4.27 |
December | 50614398.65 | 45552958.79 | 840.41 | 21-DEC-19:02 | 756.37 | 756.37 | 6.72 | 1.82 |
Annual Sum or Average | 0.170797E+11 | 0.153717E+11 | ||||||
Minimum of Months | 50614398.65 | 45552958.79 | 840.41 | 756.37 | 756.37 | 6.72 | 1.82 | |
Maximum of Months | 0.334600E+10 | 0.301140E+10 | 2577.86 | 2320.08 | 2320.08 | 6.72 | 12.97 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.208575E+10 | 0.187718E+10 | 2216.74 | 01-JAN-08:40 | 1995.07 | 1995.07 | 6.78 | 19.61 |
February | 0.225079E+10 | 0.202571E+10 | 2216.74 | 01-FEB-06:03 | 1995.07 | 1995.07 | 6.73 | 19.61 |
March | 0.256635E+10 | 0.230972E+10 | 2216.74 | 01-MAR-06:03 | 1995.07 | 1995.07 | 6.73 | 19.61 |
April | 0.531053E+10 | 0.477948E+10 | 2216.74 | 01-APR-06:05 | 1995.07 | 1995.07 | 6.73 | 19.61 |
May | 0.565907E+10 | 0.509316E+10 | 2216.74 | 01-MAY-00:05 | 1995.07 | 1995.07 | 7.14 | 19.61 |
June | 0.572850E+10 | 0.515565E+10 | 2216.74 | 01-JUN-00:05 | 1995.07 | 1995.07 | 6.96 | 19.61 |
July | 0.593332E+10 | 0.533999E+10 | 2216.74 | 01-JUL-00:10 | 1995.07 | 1995.07 | 6.88 | 19.61 |
August | 0.593731E+10 | 0.534358E+10 | 2216.74 | 01-AUG-00:05 | 1995.07 | 1995.07 | 7.06 | 19.61 |
September | 0.573337E+10 | 0.516004E+10 | 2216.74 | 01-SEP-00:05 | 1995.07 | 1995.07 | 7.03 | 19.61 |
October | 0.436163E+10 | 0.392547E+10 | 2216.74 | 01-OCT-00:10 | 1995.07 | 1995.07 | 6.84 | 19.61 |
November | 0.237761E+10 | 0.213984E+10 | 2216.74 | 01-NOV-05:03 | 1995.07 | 1995.07 | 6.75 | 19.61 |
December | 0.107429E+10 | 0.966857E+09 | 2216.74 | 01-DEC-07:10 | 1995.07 | 1995.07 | 6.73 | 19.61 |
Annual Sum or Average | 0.490185E+11 | 0.441167E+11 | ||||||
Minimum of Months | 0.107429E+10 | 0.966857E+09 | 2216.74 | 1995.07 | 1995.07 | 6.73 | 19.61 | |
Maximum of Months | 0.593731E+10 | 0.534358E+10 | 2216.74 | 1995.07 | 1995.07 | 7.14 | 19.61 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:10 | 14.37 | 14.37 | 48.91 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:03 | 14.37 | 14.37 | 49.35 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:03 | 14.37 | 14.37 | 49.35 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 52.42 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:05 | 14.37 | 14.37 | 52.36 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:05 | 14.37 | 14.37 | 52.58 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 52.99 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:05 | 14.37 | 14.37 | 52.87 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:05 | 14.37 | 14.37 | 52.87 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:10 | 14.37 | 14.37 | 52.14 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:05 | 14.37 | 14.37 | 52.57 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:03 | 14.37 | 14.37 | 49.74 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 48.91 | 0.37 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 52.99 | 0.37 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 40.10 | 60.00 | 34221.23 | 163151.32 | 28-JAN-19:04 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 43.94 | 60.00 | 23762.13 | 157637.56 | 26-FEB-19:04 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 45.80 | 60.00 | 32620.67 | 141981.40 | 17-MAR-15:04 |
April | 0.00 | 0.00 | 01-APR-00:10 | 47.01 | 60.00 | 31135.07 | 132127.96 | 05-APR-08:05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.16 | 60.00 | 38544.88 | 130764.86 | 05-MAY-08:05 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.45 | 60.00 | 28950.39 | 113930.99 | 07-JUN-10:15 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 29.74 | 60.00 | 19051.67 | 103895.53 | 31-JUL-04:30 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 28.83 | 60.00 | 14195.26 | 101170.58 | 20-AUG-05:07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.88 | 60.00 | 28367.17 | 123538.24 | 28-SEP-06:05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 35.52 | 60.00 | 43572.34 | 164474.96 | 19-OCT-08:04 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 46.71 | 60.00 | 45879.68 | 164512.21 | 21-NOV-16:02 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 42.51 | 60.00 | 30223.21 | 172812.60 | 16-DEC-16:04 |
Annual Sum or Average | 0.00 | 30905.80 | ||||||
Minimum of Months | 0.00 | 0.00 | 26.88 | 60.00 | 14195.26 | 101170.58 | ||
Maximum of Months | 0.00 | 0.00 | 47.01 | 60.00 | 45879.68 | 172812.60 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 3542.15 | 72965.36 | 19-JAN-16:01 | 7.59 | 6.70 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 4267.74 | 75868.68 | 27-FEB-16:01 | 7.62 | 6.70 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 3555.88 | 72924.13 | 20-MAR-15:01 | 7.59 | 6.70 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 31308.48 | 359507.68 | 30-APR-18:03 | 11.08 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 32235.28 | 345268.94 | 22-MAY-15:03 | 10.90 | 6.70 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 57408.37 | 440543.18 | 25-JUN-18:03 | 12.06 | 6.70 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 75698.38 | 424902.94 | 22-JUL-18:03 | 11.87 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 81761.45 | 397274.00 | 14-AUG-18:03 | 11.54 | 6.70 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 59177.37 | 361557.07 | 13-SEP-15:03 | 11.10 | 6.70 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 15351.33 | 251755.50 | 07-OCT-15:03 | 9.76 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 3927.22 | 84967.26 | 05-NOV-15:01 | 7.73 | 6.70 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 814.36 | 29157.22 | 21-DEC-19:02 | 7.05 | 6.70 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 30892.78 | 0.00 | ||||||
Minimum of Months | 814.36 | 29157.22 | 7.05 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 81761.45 | 440543.18 | 12.06 | 6.70 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 48.91 | 60.05 | 26989.55 | 56695.31 | 31-JAN-07:20 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 49.35 | 60.05 | 27172.48 | 56785.25 | 14-FEB-07:50 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 49.35 | 60.05 | 27011.04 | 56692.35 | 01-MAR-07:40 |
April | 0.00 | 0.00 | 01-APR-00:10 | 52.42 | 60.05 | 26491.61 | 55848.28 | 03-APR-07:00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 52.36 | 60.05 | 25798.33 | 54620.10 | 01-MAY-06:20 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 52.58 | 60.05 | 25107.04 | 53071.03 | 01-JUN-06:40 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 52.99 | 60.05 | 24567.41 | 51700.90 | 03-JUL-06:15 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 52.87 | 60.05 | 24399.59 | 50998.77 | 31-AUG-06:20 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 52.87 | 60.05 | 24573.74 | 51705.28 | 29-SEP-06:40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 52.14 | 60.05 | 25075.58 | 53077.30 | 31-OCT-07:00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 52.57 | 60.05 | 25775.23 | 54577.56 | 30-NOV-07:50 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 49.74 | 60.05 | 26472.62 | 55853.03 | 29-DEC-07:40 |
Annual Sum or Average | 0.00 | 25778.07 | ||||||
Minimum of Months | 0.00 | 0.00 | 48.91 | 60.05 | 24399.59 | 50998.77 | ||
Maximum of Months | 0.00 | 0.00 | 52.99 | 60.05 | 27172.48 | 56785.25 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.252471E+09 | 0.00 | 0.00 | 0.271000E+10 | 0.00 | 0.00 |
February | 83318550.81 | 0.00 | 0.00 | 0.244774E+10 | 0.00 | 0.00 |
March | 1307150.44 | 0.00 | 0.00 | 0.271000E+10 | 0.00 | 0.00 |
April | 7319.02 | 0.00 | 0.871154E+09 | 0.262258E+10 | 0.00 | 0.00 |
May | 6352.33 | 0.00 | 0.908508E+09 | 0.271000E+10 | 0.00 | 0.00 |
June | 12223.26 | 0.00 | 0.290652E+10 | 0.262258E+10 | 0.00 | 0.00 |
July | 25817.97 | 0.00 | 0.528296E+10 | 0.271000E+10 | 0.00 | 0.00 |
August | 24076.45 | 0.00 | 0.612201E+10 | 0.271000E+10 | 0.00 | 0.00 |
September | 12826.79 | 0.00 | 0.309486E+10 | 0.262258E+10 | 0.00 | 0.00 |
October | 3041.39 | 0.00 | 0.156128E+09 | 0.271000E+10 | 0.00 | 0.00 |
November | 6792423.90 | 0.00 | 0.00 | 0.262258E+10 | 0.00 | 0.00 |
December | 46266835.84 | 0.00 | 0.00 | 0.271000E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.390248E+09 | 0.00 | 0.193421E+11 | 0.319080E+11 | 0.00 | 0.00 |
Minimum of Months | 3041.39 | 0.00 | 0.00 | 0.244774E+10 | 0.00 | 0.00 |
Maximum of Months | 0.252471E+09 | 0.00 | 0.612201E+10 | 0.271000E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.670222E+11 | 0.00 | 0.00 | 0.333673E+11 | 0.00 | 0.00 |
February | 0.395800E+11 | 0.00 | 0.00 | 0.302781E+11 | 0.00 | 0.00 |
March | 0.741241E+11 | 0.00 | 0.00 | 0.339936E+11 | 0.00 | 0.00 |
April | 0.786139E+11 | 0.00 | 0.152719E+11 | 0.338956E+11 | 0.00 | 0.00 |
May | 0.102240E+12 | 0.00 | 0.154628E+11 | 0.353337E+11 | 0.00 | 0.00 |
June | 0.753072E+11 | 0.00 | 0.494767E+11 | 0.350132E+11 | 0.00 | 0.00 |
July | 0.511866E+11 | 0.00 | 0.853833E+11 | 0.364633E+11 | 0.00 | 0.00 |
August | 0.381836E+11 | 0.00 | 0.994403E+11 | 0.365072E+11 | 0.00 | 0.00 |
September | 0.734850E+11 | 0.00 | 0.513385E+11 | 0.347985E+11 | 0.00 | 0.00 |
October | 0.110553E+12 | 0.00 | 0.269335E+10 | 0.345802E+11 | 0.00 | 0.00 |
November | 0.102374E+12 | 0.00 | 50951902.96 | 0.328207E+11 | 0.00 | 0.00 |
December | 0.493485E+11 | 0.00 | 0.00 | 0.331984E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.862018E+12 | 0.00 | 0.319118E+12 | 0.410250E+12 | 0.00 | 0.00 |
Minimum of Months | 0.381836E+11 | 0.00 | 0.00 | 0.302781E+11 | 0.00 | 0.00 |
Maximum of Months | 0.110553E+12 | 0.00 | 0.994403E+11 | 0.365072E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.271000E+10 | 0.00 | 0.252471E+09 | 0.443557E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244774E+10 | 0.00 | 83318550.81 | 0.405179E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.271000E+10 | 0.00 | 1307150.44 | 0.385521E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.262258E+10 | 0.871154E+09 | 7319.02 | 0.271612E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.271000E+10 | 0.908508E+09 | 6352.33 | 0.223873E+11 | 2093766.46 | 0.00 | 0.00 | 0.00 |
June | 0.262258E+10 | 0.290652E+10 | 12223.26 | 0.965509E+10 | 0.122633E+09 | 0.00 | 0.00 | 0.00 |
July | 0.271000E+10 | 0.528296E+10 | 25817.97 | 0.583887E+10 | 0.183423E+09 | 0.00 | 0.00 | 0.00 |
August | 0.271000E+10 | 0.612201E+10 | 24076.45 | 0.420371E+10 | 25552546.84 | 0.00 | 0.00 | 0.00 |
September | 0.262258E+10 | 0.309486E+10 | 12826.79 | 0.105156E+11 | 1823614.84 | 0.00 | 0.00 | 0.00 |
October | 0.271000E+10 | 0.156128E+09 | 3041.39 | 0.245740E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.262258E+10 | 0.00 | 6792423.90 | 0.336883E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.271000E+10 | 0.00 | 46266835.84 | 0.452282E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319080E+11 | 0.193421E+11 | 0.390248E+09 | 0.306678E+12 | 0.335526E+09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244774E+10 | 0.00 | 3041.39 | 0.420371E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.271000E+10 | 0.612201E+10 | 0.252471E+09 | 0.452282E+11 | 0.183423E+09 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.333673E+11 | 0.00 | 0.670222E+11 | 0.470952E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.302781E+11 | 0.00 | 0.395800E+11 | 0.446727E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.339936E+11 | 0.00 | 0.741241E+11 | 0.376435E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.338956E+11 | 0.152719E+11 | 0.786139E+11 | 0.206740E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.353337E+11 | 0.154628E+11 | 0.102240E+12 | 0.132633E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.350132E+11 | 0.494767E+11 | 0.753072E+11 | 0.194961E+11 | 0.118472E+09 | 0.00 | 0.00 | 0.00 |
July | 0.364633E+11 | 0.853833E+11 | 0.511866E+11 | 0.393611E+10 | 0.672689E+09 | 0.00 | 0.00 | 0.00 |
August | 0.365072E+11 | 0.994403E+11 | 0.381836E+11 | 0.111662E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.347985E+11 | 0.513385E+11 | 0.734850E+11 | 0.203392E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.345802E+11 | 0.269335E+10 | 0.110553E+12 | 0.151716E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.328207E+11 | 50951902.96 | 0.102374E+12 | 0.288315E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.331984E+11 | 0.00 | 0.493485E+11 | 0.504829E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.410250E+12 | 0.319118E+12 | 0.862018E+12 | 0.262323E+13 | 0.791161E+09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.302781E+11 | 0.00 | 0.381836E+11 | 0.111662E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.365072E+11 | 0.994403E+11 | 0.110553E+12 | 0.504829E+12 | 0.672689E+09 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.271000E+10 | 0.252471E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244774E+10 | 83318550.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.271000E+10 | 1307150.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.262258E+10 | 7319.02 | 0.871154E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.271000E+10 | 6352.33 | 0.908508E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.262258E+10 | 12223.26 | 0.290652E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.271000E+10 | 25817.97 | 0.528296E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.271000E+10 | 24076.45 | 0.612201E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.262258E+10 | 12826.79 | 0.309486E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.271000E+10 | 3041.39 | 0.156128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.262258E+10 | 6792423.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.271000E+10 | 46266835.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319080E+11 | 0.390248E+09 | 0.193421E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244774E+10 | 3041.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.271000E+10 | 0.252471E+09 | 0.612201E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.333673E+11 | 0.670222E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.302781E+11 | 0.395800E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.339936E+11 | 0.741241E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.338956E+11 | 0.786139E+11 | 0.152719E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.353337E+11 | 0.102240E+12 | 0.154628E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.350132E+11 | 0.753072E+11 | 0.494767E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364633E+11 | 0.511866E+11 | 0.853833E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.365072E+11 | 0.381836E+11 | 0.994403E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.347985E+11 | 0.734850E+11 | 0.513385E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.345802E+11 | 0.110553E+12 | 0.269335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.328207E+11 | 0.102374E+12 | 50951902.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.331984E+11 | 0.493485E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.410250E+12 | 0.862018E+12 | 0.319118E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.302781E+11 | 0.381836E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.365072E+11 | 0.110553E+12 | 0.994403E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.413638E+11 | 0.00 | 0.00 | 3687727.28 | 0.00 | 0.00 | 0.771776E+10 | 0.00 | 0.97 |
February | 0.386285E+11 | 0.00 | 0.00 | 1017403.74 | 0.00 | 0.00 | 0.403731E+10 | 0.00 | 0.98 |
March | 0.499238E+11 | 0.00 | 0.00 | 29184.12 | 0.00 | 0.00 | 0.315573E+09 | 0.00 | 0.97 |
April | 0.509375E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.97 |
May | 0.547404E+11 | 0.00 | 0.00 | 1040.10 | 0.00 | 0.00 | 45473541.06 | 0.00 | 0.97 |
June | 0.459811E+11 | 0.00 | 0.00 | 277844.15 | 39753367.84 | 0.00 | 0.256079E+10 | 0.00 | 0.97 |
July | 0.395060E+11 | 0.00 | 0.00 | 2285983.16 | 1106874.31 | 0.00 | 0.550615E+10 | 0.00 | 0.97 |
August | 0.339283E+11 | 0.00 | 0.00 | 5368645.17 | 0.00 | 0.00 | 0.884027E+10 | 0.00 | 0.98 |
September | 0.211767E+11 | 0.00 | 0.00 | 15157078.06 | 0.00 | 0.00 | 0.280093E+11 | 0.00 | 0.99 |
October | 0.214815E+11 | 0.00 | 0.00 | 20467570.85 | 0.00 | 0.00 | 0.352131E+11 | 0.00 | 0.99 |
November | 0.210424E+11 | 0.00 | 0.00 | 20533334.73 | 0.00 | 0.00 | 0.319244E+11 | 0.00 | 0.99 |
December | 0.283380E+11 | 0.00 | 0.00 | 11682385.82 | 0.00 | 0.00 | 0.184306E+11 | 0.00 | 0.98 |
Annual Sum or Average | 0.447048E+12 | 0.00 | 0.00 | 80508197.20 | 40860242.15 | 0.00 | 0.142601E+12 | 0.00 | 0.98 |
Minimum of Months | 0.210424E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.97 |
Maximum of Months | 0.547404E+11 | 0.00 | 0.00 | 20533334.73 | 39753367.84 | 0.00 | 0.352131E+11 | 0.00 | 0.99 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.778641E+10 | 0.00 | 0.00 | 112312.43 | 0.00 | 0.797043E+09 | 0.242328E+09 | 0.00 | 3.15 |
February | 0.707201E+10 | 0.00 | 0.00 | 247029.75 | 0.00 | 0.270514E+09 | 0.339181E+09 | 0.00 | 3.17 |
March | 0.889239E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140969E+09 | 0.00 | 0.00 | 3.15 |
April | 0.834567E+10 | 0.00 | 0.00 | 993011.85 | 0.00 | 0.00 | 0.835425E+09 | 0.00 | 3.17 |
May | 0.940513E+10 | 0.00 | 0.00 | 308373.07 | 0.00 | 0.00 | 0.445517E+09 | 0.00 | 3.15 |
June | 0.848231E+10 | 0.00 | 0.00 | 286349.11 | 7147904.02 | 0.00 | 0.245607E+09 | 0.00 | 3.16 |
July | 0.770491E+10 | 207961.97 | 0.00 | 724999.89 | 0.00 | 0.00 | 0.389993E+09 | 0.00 | 3.17 |
August | 0.707211E+10 | 0.00 | 0.00 | 1856530.26 | 0.00 | 0.00 | 0.640582E+09 | 0.00 | 3.19 |
September | 0.780952E+10 | 0.00 | 0.00 | 2910035.47 | 0.00 | 0.00 | 0.105934E+10 | 0.00 | 3.26 |
October | 0.939181E+10 | 0.00 | 0.00 | 837555.66 | 0.00 | 0.00 | 0.679969E+09 | 0.00 | 3.18 |
November | 0.891848E+10 | 0.00 | 0.00 | 82718.57 | 0.00 | 0.215802E+09 | 0.220225E+09 | 0.00 | 3.14 |
December | 0.613817E+10 | 0.00 | 0.00 | 23609.75 | 0.00 | 0.216322E+10 | 61942200.87 | 0.00 | 3.17 |
Annual Sum or Average | 0.970189E+11 | 207961.97 | 0.00 | 8382525.82 | 7147904.02 | 0.358754E+10 | 0.516011E+10 | 0.00 | 3.17 |
Minimum of Months | 0.613817E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.14 |
Maximum of Months | 0.940513E+10 | 207961.97 | 0.00 | 2910035.47 | 7147904.02 | 0.216322E+10 | 0.105934E+10 | 0.00 | 3.26 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.451777E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.40 |
February | 0.392702E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.40 |
March | 0.462400E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.40 |
April | 0.405355E+10 | 0.00 | 0.00 | 368568.52 | 0.00 | 0.00 | 0.638466E+09 | 0.00 | 1.40 |
May | 0.428418E+10 | 0.00 | 0.00 | 409029.71 | 0.00 | 0.00 | 0.764850E+09 | 0.00 | 1.40 |
June | 0.323974E+10 | 40913.65 | 0.00 | 821256.48 | 3617956.22 | 0.00 | 0.124369E+10 | 0.00 | 1.41 |
July | 0.258201E+10 | 72793.68 | 0.00 | 1468011.53 | 29082.20 | 0.00 | 0.160136E+10 | 0.00 | 1.42 |
August | 0.218940E+10 | 0.00 | 0.00 | 1494293.84 | 0.00 | 0.00 | 0.178708E+10 | 0.00 | 1.42 |
September | 0.288852E+10 | 0.00 | 0.00 | 1054809.35 | 0.00 | 0.00 | 0.163242E+10 | 0.00 | 1.42 |
October | 0.478081E+10 | 0.00 | 0.00 | 174108.76 | 0.00 | 0.00 | 0.351415E+09 | 0.00 | 1.41 |
November | 0.478836E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.39 |
December | 0.428103E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.40 |
Annual Sum or Average | 0.461564E+11 | 113707.32 | 0.00 | 5790078.19 | 3647038.42 | 0.00 | 0.801927E+10 | 0.00 | 1.41 |
Minimum of Months | 0.218940E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.39 |
Maximum of Months | 0.478836E+10 | 72793.68 | 0.00 | 1494293.84 | 3617956.22 | 0.00 | 0.178708E+10 | 0.00 | 1.42 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.330834E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.48 |
February | 0.287573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.48 |
March | 0.338613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.48 |
April | 0.343318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.48 |
May | 0.369256E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.48 |
June | 0.326935E+10 | 0.00 | 0.00 | 188.92 | 2679369.80 | 0.00 | 2381589.10 | 0.00 | 0.49 |
July | 0.298712E+10 | 0.00 | 0.00 | 36394.13 | 74603.13 | 0.00 | 46813719.87 | 0.00 | 0.49 |
August | 0.287355E+10 | 0.00 | 0.00 | 945.53 | 0.00 | 0.00 | 9403542.91 | 0.00 | 0.49 |
September | 0.328319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.49 |
October | 0.375829E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.49 |
November | 0.350649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.48 |
December | 0.313498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.48 |
Annual Sum or Average | 0.395089E+11 | 0.00 | 0.00 | 37528.59 | 2753972.93 | 0.00 | 58598851.88 | 0.00 | 0.48 |
Minimum of Months | 0.287355E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.48 |
Maximum of Months | 0.375829E+10 | 0.00 | 0.00 | 36394.13 | 2679369.80 | 0.00 | 46813719.87 | 0.00 | 0.49 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.179360E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160893E+09 | 0.00 | 0.00 | 0.49 |
February | 0.169892E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 |
March | 0.200044E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.49 |
April | 0.202824E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 |
May | 0.218148E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.49 |
June | 0.193286E+10 | 0.00 | 0.00 | 0.00 | 1582908.50 | 0.00 | 0.00 | 0.00 | 0.50 |
July | 0.179240E+10 | 0.00 | 0.00 | 0.00 | 44073.77 | 0.00 | 0.00 | 0.00 | 0.50 |
August | 0.170318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 |
September | 0.193963E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 |
October | 0.222031E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 |
November | 0.205731E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14239856.90 | 0.00 | 0.00 | 0.49 |
December | 0.172094E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131126E+09 | 0.00 | 0.00 | 0.50 |
Annual Sum or Average | 0.230693E+11 | 0.00 | 0.00 | 0.00 | 1626982.27 | 0.306259E+09 | 0.00 | 0.00 | 0.50 |
Minimum of Months | 0.169892E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.49 |
Maximum of Months | 0.222031E+10 | 0.00 | 0.00 | 0.00 | 1582908.50 | 0.160893E+09 | 0.00 | 0.00 | 0.50 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.195471E+09 | 0.00 | 0.00 | 91279555.84 | 0.00 | 0.00 | 0.749032E+11 | 0.00 | 23.14 |
February | 0.187822E+09 | 0.00 | 0.00 | 82018124.14 | 0.00 | 0.00 | 0.651088E+11 | 0.00 | 23.28 |
March | 0.161380E+09 | 0.00 | 0.00 | 88125016.65 | 0.00 | 0.00 | 0.766623E+11 | 0.00 | 23.24 |
April | 0.134423E+09 | 0.00 | 0.00 | 0.101161E+09 | 0.00 | 0.00 | 0.783980E+11 | 0.00 | 23.23 |
May | 0.187731E+09 | 0.00 | 0.00 | 0.105633E+09 | 0.00 | 0.00 | 0.843503E+11 | 0.00 | 23.19 |
June | 0.117080E+09 | 64196517.10 | 0.00 | 0.111843E+09 | 0.00 | 0.00 | 0.749060E+11 | 0.00 | 23.30 |
July | 0.111543E+09 | 1453650.27 | 0.00 | 0.125149E+09 | 0.00 | 0.00 | 0.690559E+11 | 0.00 | 23.20 |
August | 72672082.45 | 0.00 | 0.00 | 0.125391E+09 | 0.00 | 0.00 | 0.662149E+11 | 0.00 | 23.38 |
September | 0.140008E+09 | 0.00 | 0.00 | 0.110302E+09 | 0.00 | 0.00 | 0.755880E+11 | 0.00 | 23.35 |
October | 0.239322E+09 | 0.00 | 0.00 | 92984813.31 | 0.00 | 0.00 | 0.856951E+11 | 0.00 | 23.32 |
November | 0.230060E+09 | 0.00 | 0.00 | 87379441.87 | 0.00 | 0.00 | 0.790587E+11 | 0.00 | 23.13 |
December | 0.214206E+09 | 0.00 | 0.00 | 92138823.66 | 0.00 | 0.00 | 0.708201E+11 | 0.00 | 23.24 |
Annual Sum or Average | 0.199172E+10 | 65650167.38 | 0.00 | 0.121341E+10 | 0.00 | 0.00 | 0.900761E+12 | 0.00 | 23.25 |
Minimum of Months | 72672082.45 | 0.00 | 0.00 | 82018124.14 | 0.00 | 0.00 | 0.651088E+11 | 0.00 | 23.13 |
Maximum of Months | 0.239322E+09 | 64196517.10 | 0.00 | 0.125391E+09 | 0.00 | 0.00 | 0.856951E+11 | 0.00 | 23.38 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.298696E+11 | 0.00 | 0.00 | 1512880.09 | 0.00 | 0.00 | 0.528114E+10 | 0.00 | 4.46 |
February | 0.239825E+11 | 0.00 | 0.00 | 2226658.75 | 0.00 | 0.00 | 0.661607E+10 | 0.00 | 4.50 |
March | 0.318417E+11 | 0.00 | 0.00 | 407458.95 | 0.00 | 0.00 | 0.413220E+10 | 0.00 | 4.47 |
April | 0.169481E+11 | 0.00 | 0.00 | 10527548.62 | 0.00 | 0.00 | 0.195957E+11 | 0.00 | 4.50 |
May | 0.207561E+11 | 0.00 | 0.00 | 7165738.91 | 0.00 | 0.00 | 0.184665E+11 | 0.00 | 4.47 |
June | 0.145147E+11 | 7343121.90 | 0.00 | 9016599.17 | 21122563.68 | 0.00 | 0.202353E+11 | 0.00 | 4.50 |
July | 0.125248E+11 | 800563.55 | 0.00 | 13771526.70 | 0.00 | 0.00 | 0.196963E+11 | 0.00 | 4.50 |
August | 0.753818E+10 | 0.00 | 0.00 | 21495272.01 | 0.00 | 0.00 | 0.231307E+11 | 0.00 | 4.53 |
September | 0.106293E+11 | 0.00 | 0.00 | 23862020.66 | 0.00 | 0.00 | 0.245935E+11 | 0.00 | 4.61 |
October | 0.225453E+11 | 0.00 | 0.00 | 8153487.73 | 0.00 | 0.00 | 0.175347E+11 | 0.00 | 4.52 |
November | 0.292013E+11 | 0.00 | 0.00 | 1608307.23 | 0.00 | 0.00 | 0.805590E+10 | 0.00 | 4.46 |
December | 0.315246E+11 | 0.00 | 0.00 | 332814.87 | 0.00 | 0.00 | 0.178114E+10 | 0.00 | 4.49 |
Annual Sum or Average | 0.251876E+12 | 8143685.46 | 0.00 | 0.100080E+09 | 21122563.68 | 0.00 | 0.169119E+12 | 0.00 | 4.50 |
Minimum of Months | 0.753818E+10 | 0.00 | 0.00 | 332814.87 | 0.00 | 0.00 | 0.178114E+10 | 0.00 | 4.46 |
Maximum of Months | 0.318417E+11 | 7343121.90 | 0.00 | 23862020.66 | 21122563.68 | 0.00 | 0.245935E+11 | 0.00 | 4.61 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.920827E+11 | 0.00 | 0.00 | 2012634.57 | 0.00 | 0.00 | 0.901376E+10 | 0.00 | 1.86 |
February | 0.784333E+11 | 0.00 | 0.00 | 2353365.80 | 0.00 | 0.00 | 0.944298E+10 | 0.00 | 1.87 |
March | 0.927510E+11 | 0.00 | 0.00 | 2692662.43 | 0.00 | 0.00 | 0.107220E+11 | 0.00 | 1.86 |
April | 0.612037E+11 | 0.00 | 0.00 | 23455699.03 | 0.00 | 0.00 | 0.438645E+11 | 0.00 | 1.87 |
May | 0.649892E+11 | 0.00 | 0.00 | 25464253.34 | 0.00 | 0.00 | 0.480651E+11 | 0.00 | 1.87 |
June | 0.414386E+11 | 915563.71 | 0.00 | 41113092.79 | 80962458.77 | 0.00 | 0.590808E+11 | 0.00 | 1.88 |
July | 0.346641E+11 | 1628973.59 | 0.00 | 56888834.02 | 650800.04 | 0.00 | 0.591817E+11 | 0.00 | 1.89 |
August | 0.241680E+11 | 0.00 | 0.00 | 64638212.72 | 0.00 | 0.00 | 0.653834E+11 | 0.00 | 1.90 |
September | 0.316960E+11 | 0.00 | 0.00 | 54854530.74 | 0.00 | 0.00 | 0.700781E+11 | 0.00 | 1.90 |
October | 0.732409E+11 | 0.00 | 0.00 | 17532972.87 | 0.00 | 0.00 | 0.417188E+11 | 0.00 | 1.87 |
November | 0.916616E+11 | 0.00 | 0.00 | 3504683.82 | 0.00 | 0.00 | 0.154887E+11 | 0.00 | 1.86 |
December | 0.916063E+11 | 0.00 | 0.00 | 655425.41 | 0.00 | 0.00 | 0.419388E+10 | 0.00 | 1.87 |
Annual Sum or Average | 0.777935E+12 | 2544537.29 | 0.00 | 0.295166E+09 | 81613258.81 | 0.00 | 0.436234E+12 | 0.00 | 1.87 |
Minimum of Months | 0.241680E+11 | 0.00 | 0.00 | 655425.41 | 0.00 | 0.00 | 0.419388E+10 | 0.00 | 1.86 |
Maximum of Months | 0.927510E+11 | 1628973.59 | 0.00 | 64638212.72 | 80962458.77 | 0.00 | 0.700781E+11 | 0.00 | 1.90 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 69628447.67 | 0.00 | 0.00 | 464230.40 | 0.00 | 0.133960E+10 | 92858590.74 | 0.00 | 0.35 |
February | 66224778.63 | 0.00 | 0.00 | 1174491.73 | 0.00 | 0.112772E+10 | 0.156087E+09 | 0.00 | 0.36 |
March | 78801846.56 | 0.00 | 0.00 | 757049.43 | 0.00 | 0.121176E+10 | 0.210186E+09 | 0.00 | 0.35 |
April | 42955707.34 | 0.00 | 0.00 | 9818367.08 | 0.00 | 0.326692E+09 | 0.105940E+10 | 0.00 | 0.35 |
May | 36975281.79 | 19069.39 | 0.00 | 11708109.36 | 0.00 | 0.210368E+09 | 0.115288E+10 | 0.00 | 0.35 |
June | 16160981.73 | 4861815.66 | 0.00 | 15522616.79 | 0.00 | 8075584.16 | 0.109246E+10 | 0.00 | 0.35 |
July | 10578266.50 | 2691285.79 | 0.00 | 19602732.60 | 0.00 | 9172605.73 | 0.100952E+10 | 0.00 | 0.35 |
August | 2200109.99 | 974743.94 | 0.00 | 19182263.38 | 28350.95 | 2160257.92 | 0.101598E+10 | 0.00 | 0.35 |
September | 12298034.15 | 243228.87 | 0.00 | 14188529.73 | 0.00 | 33912603.25 | 0.113092E+10 | 0.00 | 0.36 |
October | 60627288.00 | 0.00 | 0.00 | 3708045.75 | 0.00 | 0.739846E+09 | 0.664509E+09 | 0.00 | 0.36 |
November | 69325824.16 | 0.00 | 0.00 | 468239.80 | 0.00 | 0.124820E+10 | 0.125515E+09 | 0.00 | 0.35 |
December | 56948632.77 | 0.00 | 0.00 | 27249.88 | 0.00 | 0.142644E+10 | 8911179.81 | 0.00 | 0.36 |
Annual Sum or Average | 0.522725E+09 | 8790143.65 | 0.00 | 96621925.91 | 28350.95 | 0.768395E+10 | 0.771922E+10 | 0.00 | 0.35 |
Minimum of Months | 2200109.99 | 0.00 | 0.00 | 27249.88 | 0.00 | 2160257.92 | 8911179.81 | 0.00 | 0.35 |
Maximum of Months | 78801846.56 | 4861815.66 | 0.00 | 19602732.60 | 28350.95 | 0.142644E+10 | 0.115288E+10 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 65364002.03 | 0.00 | 0.00 | 110246.61 | 0.00 | 0.142325E+10 | 13653624.43 | 0.00 | 0.35 |
February | 69437012.74 | 0.00 | 0.00 | 496377.10 | 0.00 | 0.122172E+10 | 59392101.90 | 0.00 | 0.36 |
March | 78792613.78 | 0.00 | 0.00 | 406793.94 | 0.00 | 0.130671E+10 | 0.115417E+09 | 0.00 | 0.35 |
April | 0.117592E+09 | 0.00 | 0.00 | 7002973.90 | 0.00 | 0.474454E+09 | 0.839651E+09 | 0.00 | 0.35 |
May | 0.131050E+09 | 12275.77 | 0.00 | 9050478.05 | 6791.38 | 0.249509E+09 | 0.102216E+10 | 0.00 | 0.35 |
June | 0.135590E+09 | 2885607.59 | 0.00 | 13469546.45 | 1975638.44 | 8004577.27 | 0.975023E+09 | 0.00 | 0.36 |
July | 0.208226E+09 | 2231908.47 | 0.00 | 15154248.37 | 459061.99 | 9437310.39 | 0.815928E+09 | 0.00 | 0.36 |
August | 0.255865E+09 | 932377.92 | 0.00 | 12604895.63 | 70599.45 | 2393160.56 | 0.768536E+09 | 0.00 | 0.36 |
September | 0.160870E+09 | 74197.39 | 0.00 | 8675094.34 | 169002.98 | 68514079.26 | 0.953116E+09 | 0.00 | 0.36 |
October | 99018783.07 | 0.00 | 0.00 | 1916929.93 | 0.00 | 0.972377E+09 | 0.395204E+09 | 0.00 | 0.36 |
November | 68937596.05 | 0.00 | 0.00 | 147819.04 | 0.00 | 0.135155E+10 | 22709573.43 | 0.00 | 0.35 |
December | 53218317.53 | 0.00 | 0.00 | 6439.06 | 0.00 | 0.143755E+10 | 1377091.39 | 0.00 | 0.36 |
Annual Sum or Average | 0.144396E+10 | 6136367.15 | 0.00 | 69041842.44 | 2681094.25 | 0.852547E+10 | 0.598217E+10 | 0.00 | 0.35 |
Minimum of Months | 53218317.53 | 0.00 | 0.00 | 6439.06 | 0.00 | 2393160.56 | 1377091.39 | 0.00 | 0.35 |
Maximum of Months | 0.255865E+09 | 2885607.59 | 0.00 | 15154248.37 | 1975638.44 | 0.143755E+10 | 0.102216E+10 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.822390E+09 | 0.00 | 0.00 | 744324.43 | 0.00 | 0.00 | 0.559990E+09 | 0.00 | 0.02 |
February | 0.701512E+09 | 0.00 | 0.00 | 1197702.79 | 0.00 | 0.00 | 0.625696E+09 | 0.00 | 0.02 |
March | 0.135893E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
April | 0.200293E+09 | 0.00 | 0.00 | 3807593.93 | 0.00 | 0.00 | 0.132674E+10 | 0.00 | 0.02 |
May | 0.350155E+09 | 0.00 | 0.00 | 2878814.54 | 0.00 | 0.00 | 0.116575E+10 | 0.00 | 0.02 |
June | 36237920.78 | 13382818.03 | 0.00 | 2704812.14 | 0.00 | 0.00 | 0.109487E+10 | 0.00 | 0.02 |
July | 0.101140E+09 | 736959.84 | 0.00 | 3969316.80 | 0.00 | 0.00 | 0.772760E+09 | 0.00 | 0.02 |
August | 24996658.81 | 2682843.80 | 0.00 | 5000190.37 | 0.00 | 0.00 | 0.674303E+09 | 0.00 | 0.02 |
September | 98016788.86 | 394539.01 | 0.00 | 5513059.80 | 0.00 | 0.00 | 0.876347E+09 | 0.00 | 0.02 |
October | 0.647300E+09 | 0.00 | 0.00 | 2487117.99 | 0.00 | 0.00 | 0.867444E+09 | 0.00 | 0.02 |
November | 0.994620E+09 | 0.00 | 0.00 | 556394.63 | 0.00 | 0.00 | 0.395435E+09 | 0.00 | 0.02 |
December | 0.952221E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
Annual Sum or Average | 0.628781E+10 | 17197160.68 | 0.00 | 28859327.43 | 0.00 | 0.00 | 0.835933E+10 | 0.00 | 0.02 |
Minimum of Months | 24996658.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
Maximum of Months | 0.135893E+10 | 13382818.03 | 0.00 | 5513059.80 | 0.00 | 0.00 | 0.132674E+10 | 0.00 | 0.02 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.100920E+10 | 0.00 | 0.00 | 15301121.01 | 0.00 | 0.617272E+10 | 0.131817E+11 | 0.00 | 0.40 |
February | 0.941871E+09 | 0.00 | 0.00 | 15008384.66 | 0.00 | 0.423064E+10 | 0.131386E+11 | 0.00 | 0.40 |
March | 0.106877E+10 | 0.00 | 0.00 | 34302521.44 | 0.00 | 0.656687E+09 | 0.186048E+11 | 0.00 | 0.40 |
April | 0.166864E+10 | 0.00 | 0.00 | 92255335.78 | 0.00 | 57134679.72 | 0.176971E+11 | 0.00 | 0.40 |
May | 0.185770E+10 | 166513.50 | 0.00 | 0.113304E+09 | 92121.05 | 43450230.09 | 0.171354E+11 | 0.00 | 0.40 |
June | 0.210742E+10 | 30814311.29 | 12284.22 | 0.152338E+09 | 35111907.29 | 18825668.02 | 0.130775E+11 | 1383.37 | 0.40 |
July | 0.315576E+10 | 27905408.80 | 0.00 | 0.171480E+09 | 8595991.25 | 7264463.98 | 0.108911E+11 | 0.00 | 0.40 |
August | 0.378799E+10 | 5899872.44 | 0.00 | 0.144883E+09 | 7704913.86 | 11402727.70 | 0.101545E+11 | 0.00 | 0.40 |
September | 0.223948E+10 | 320429.09 | 0.00 | 0.106109E+09 | 2978438.05 | 39195551.08 | 0.137728E+11 | 0.00 | 0.40 |
October | 0.134313E+10 | 0.00 | 0.00 | 49893350.99 | 0.00 | 0.198601E+09 | 0.183279E+11 | 0.00 | 0.40 |
November | 0.990793E+09 | 0.00 | 0.00 | 22765746.09 | 0.00 | 0.231509E+10 | 0.162494E+11 | 0.00 | 0.40 |
December | 0.963760E+09 | 0.00 | 0.00 | 9147829.53 | 0.00 | 0.937599E+10 | 0.989121E+10 | 0.00 | 0.40 |
Annual Sum or Average | 0.211345E+11 | 65106535.12 | 12284.22 | 0.926788E+09 | 54483371.49 | 0.231270E+11 | 0.172122E+12 | 1383.37 | 0.40 |
Minimum of Months | 0.941871E+09 | 0.00 | 0.00 | 9147829.53 | 0.00 | 7264463.98 | 0.989121E+10 | 0.00 | 0.40 |
Maximum of Months | 0.378799E+10 | 30814311.29 | 12284.22 | 0.171480E+09 | 35111907.29 | 0.937599E+10 | 0.186048E+11 | 1383.37 | 0.40 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 69682587.80 | 0.00 | 0.00 | 432575.95 | 0.00 | 0.132991E+10 | 0.102526E+09 | 0.00 | 0.35 |
February | 68511247.95 | 0.00 | 0.00 | 845856.01 | 0.00 | 0.113547E+10 | 0.146376E+09 | 0.00 | 0.36 |
March | 78370821.84 | 0.00 | 0.00 | 553096.71 | 0.00 | 0.121739E+10 | 0.205192E+09 | 0.00 | 0.35 |
April | 21950630.07 | 0.00 | 0.00 | 10542372.45 | 0.00 | 0.319172E+09 | 0.108720E+10 | 0.00 | 0.35 |
May | 20624185.60 | 19069.39 | 0.00 | 11359082.67 | 0.00 | 0.220813E+09 | 0.115914E+10 | 0.00 | 0.35 |
June | 12549025.85 | 4861815.66 | 0.00 | 14495950.87 | 0.00 | 22741139.07 | 0.108243E+10 | 0.00 | 0.35 |
July | 4186931.38 | 2691285.79 | 0.00 | 17471041.16 | 0.00 | 2818191.44 | 0.102439E+10 | 0.00 | 0.35 |
August | 1916616.98 | 974743.94 | 0.00 | 19061688.48 | 28350.95 | 2072755.57 | 0.101647E+10 | 0.00 | 0.35 |
September | 6581071.07 | 243228.87 | 0.00 | 15076112.90 | 0.00 | 21206343.50 | 0.114845E+10 | 0.00 | 0.36 |
October | 54614469.98 | 0.00 | 0.00 | 3794418.86 | 0.00 | 0.747031E+09 | 0.663250E+09 | 0.00 | 0.36 |
November | 71812181.77 | 0.00 | 0.00 | 457597.44 | 0.00 | 0.125051E+10 | 0.120731E+09 | 0.00 | 0.35 |
December | 57628841.22 | 0.00 | 0.00 | 117349.91 | 0.00 | 0.139022E+10 | 44362746.01 | 0.00 | 0.36 |
Annual Sum or Average | 0.468429E+09 | 8790143.65 | 0.00 | 94207143.42 | 28350.95 | 0.765935E+10 | 0.780053E+10 | 0.00 | 0.35 |
Minimum of Months | 1916616.98 | 0.00 | 0.00 | 117349.91 | 0.00 | 2072755.57 | 44362746.01 | 0.00 | 0.35 |
Maximum of Months | 78370821.84 | 4861815.66 | 0.00 | 19061688.48 | 28350.95 | 0.139022E+10 | 0.115914E+10 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 61721659.42 | 0.00 | 0.00 | 68492.57 | 0.00 | 0.140080E+10 | 39790061.95 | 0.00 | 0.35 |
February | 69845890.49 | 0.00 | 0.00 | 216906.99 | 0.00 | 0.121634E+10 | 64644742.52 | 0.00 | 0.36 |
March | 78792613.78 | 0.00 | 0.00 | 217289.43 | 0.00 | 0.130330E+10 | 0.119014E+09 | 0.00 | 0.35 |
April | 98922110.66 | 0.00 | 0.00 | 8034999.67 | 0.00 | 0.431234E+09 | 0.900509E+09 | 0.00 | 0.35 |
May | 0.105187E+09 | 12275.77 | 0.00 | 9208027.32 | 6791.38 | 0.267094E+09 | 0.103028E+10 | 0.00 | 0.35 |
June | 0.114607E+09 | 2885607.59 | 0.00 | 12525496.70 | 1975638.44 | 25336351.39 | 0.979618E+09 | 0.00 | 0.36 |
July | 0.189845E+09 | 2231908.47 | 0.00 | 13437090.04 | 459061.99 | 1956209.68 | 0.843507E+09 | 0.00 | 0.35 |
August | 0.244871E+09 | 932377.92 | 0.00 | 13359868.44 | 70599.45 | 1778048.24 | 0.779389E+09 | 0.00 | 0.36 |
September | 0.133890E+09 | 74197.39 | 0.00 | 9925182.97 | 169002.98 | 35305809.28 | 0.101205E+10 | 0.00 | 0.36 |
October | 98753101.52 | 0.00 | 0.00 | 1921725.37 | 0.00 | 0.964484E+09 | 0.403359E+09 | 0.00 | 0.36 |
November | 68937596.05 | 0.00 | 0.00 | 116533.04 | 0.00 | 0.132892E+10 | 45368206.43 | 0.00 | 0.35 |
December | 51038452.03 | 0.00 | 0.00 | 18868.75 | 0.00 | 0.143518E+10 | 5909636.65 | 0.00 | 0.36 |
Annual Sum or Average | 0.131641E+10 | 6136367.15 | 0.00 | 69050481.31 | 2681094.25 | 0.841173E+10 | 0.622344E+10 | 0.00 | 0.35 |
Minimum of Months | 51038452.03 | 0.00 | 0.00 | 18868.75 | 0.00 | 1778048.24 | 5909636.65 | 0.00 | 0.35 |
Maximum of Months | 0.244871E+09 | 2885607.59 | 0.00 | 13437090.04 | 1975638.44 | 0.143518E+10 | 0.103028E+10 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.311280E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.244863E+09 | 0.00 | 0.00 | 0.63 |
February | 0.272705E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.63 |
March | 0.321106E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.63 |
April | 0.325568E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.63 |
May | 0.350165E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.63 |
June | 0.310258E+11 | 0.00 | 0.00 | 0.00 | 25408402.99 | 0.00 | 0.00 | 0.00 | 0.63 |
July | 0.287710E+11 | 0.00 | 0.00 | 0.00 | 707459.77 | 0.00 | 0.00 | 0.00 | 0.63 |
August | 0.273390E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.63 |
September | 0.311344E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.63 |
October | 0.356398E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.63 |
November | 0.332067E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 45299138.03 | 0.00 | 0.00 | 0.63 |
December | 0.290994E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.629494E+09 | 0.00 | 0.00 | 0.63 |
Annual Sum or Average | 0.374298E+12 | 0.00 | 0.00 | 0.00 | 26115862.76 | 0.919656E+09 | 0.00 | 0.00 | 0.63 |
Minimum of Months | 0.272705E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.63 |
Maximum of Months | 0.356398E+11 | 0.00 | 0.00 | 0.00 | 25408402.99 | 0.629494E+09 | 0.00 | 0.00 | 0.63 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 16612647.63 | 0.00 | 0.00 | 99416.59 | 0.00 | 0.348885E+09 | 10041940.78 | 0.00 | 0.35 |
February | 16843585.99 | 0.00 | 0.00 | 280403.16 | 0.00 | 0.296539E+09 | 24138963.45 | 0.00 | 0.36 |
March | 19254188.12 | 0.00 | 0.00 | 161080.04 | 0.00 | 0.329181E+09 | 26779325.76 | 0.00 | 0.35 |
April | 10119717.23 | 0.00 | 0.00 | 2474173.75 | 0.00 | 0.134552E+09 | 0.212572E+09 | 0.00 | 0.35 |
May | 8817933.75 | 4767.35 | 0.00 | 2881226.83 | 0.00 | 0.104250E+09 | 0.237034E+09 | 0.00 | 0.35 |
June | 3650740.44 | 1215453.92 | 0.00 | 3833339.64 | 0.00 | 12239502.64 | 0.263331E+09 | 0.00 | 0.35 |
July | 2373523.75 | 672821.45 | 0.00 | 4899316.98 | 0.00 | 19627617.39 | 0.235317E+09 | 0.00 | 0.35 |
August | 532236.00 | 243685.99 | 0.00 | 4697324.60 | 7087.74 | 1247136.88 | 0.253403E+09 | 0.00 | 0.35 |
September | 2310058.24 | 60807.22 | 0.00 | 3322521.95 | 0.00 | 47687975.73 | 0.244508E+09 | 0.00 | 0.36 |
October | 15156822.00 | 0.00 | 0.00 | 805104.77 | 0.00 | 0.252140E+09 | 99070101.07 | 0.00 | 0.36 |
November | 16914638.94 | 0.00 | 0.00 | 100957.34 | 0.00 | 0.332684E+09 | 11177206.21 | 0.00 | 0.35 |
December | 9635298.20 | 0.00 | 0.00 | 1163.99 | 0.00 | 0.363271E+09 | 173348.04 | 0.00 | 0.36 |
Annual Sum or Average | 0.122221E+09 | 2197535.91 | 0.00 | 23556029.64 | 7087.74 | 0.224230E+10 | 0.161755E+10 | 0.00 | 0.35 |
Minimum of Months | 532236.00 | 0.00 | 0.00 | 1163.99 | 0.00 | 1247136.88 | 173348.04 | 0.00 | 0.35 |
Maximum of Months | 19254188.12 | 1215453.92 | 0.00 | 4899316.98 | 7087.74 | 0.363271E+09 | 0.263331E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 10696636.49 | 0.00 | 0.00 | 14090.60 | 0.00 | 0.362943E+09 | 1940650.54 | 0.00 | 0.35 |
February | 16257306.60 | 0.00 | 0.00 | 90220.19 | 0.00 | 0.309374E+09 | 12040056.02 | 0.00 | 0.36 |
March | 19148814.00 | 0.00 | 0.00 | 87219.99 | 0.00 | 0.337785E+09 | 18310720.09 | 0.00 | 0.35 |
April | 28464473.57 | 0.00 | 0.00 | 1776696.82 | 0.00 | 0.169787E+09 | 0.159647E+09 | 0.00 | 0.35 |
May | 29859238.82 | 3068.94 | 0.00 | 2240031.28 | 1697.85 | 0.118439E+09 | 0.202404E+09 | 0.00 | 0.35 |
June | 29941656.45 | 721401.90 | 0.00 | 3466304.30 | 493909.61 | 11676954.80 | 0.237937E+09 | 0.00 | 0.36 |
July | 47756715.81 | 557977.12 | 0.00 | 4014474.87 | 114765.50 | 17594422.86 | 0.192821E+09 | 0.00 | 0.36 |
August | 61337625.30 | 233094.48 | 0.00 | 3175777.56 | 17649.86 | 895879.85 | 0.194440E+09 | 0.00 | 0.36 |
September | 39779214.19 | 18549.35 | 0.00 | 1970970.57 | 42250.74 | 66820491.76 | 0.189223E+09 | 0.00 | 0.36 |
October | 24754695.77 | 0.00 | 0.00 | 398079.86 | 0.00 | 0.295077E+09 | 46899313.39 | 0.00 | 0.36 |
November | 16735650.54 | 0.00 | 0.00 | 20863.69 | 0.00 | 0.340352E+09 | 3726419.42 | 0.00 | 0.35 |
December | 6163783.43 | 0.00 | 0.00 | 192.34 | 0.00 | 0.366766E+09 | 107027.04 | 0.00 | 0.36 |
Annual Sum or Average | 0.330896E+09 | 1534091.79 | 0.00 | 17254922.07 | 670273.56 | 0.239751E+10 | 0.125950E+10 | 0.00 | 0.35 |
Minimum of Months | 6163783.43 | 0.00 | 0.00 | 192.34 | 0.00 | 895879.85 | 107027.04 | 0.00 | 0.35 |
Maximum of Months | 61337625.30 | 721401.90 | 0.00 | 4014474.87 | 493909.61 | 0.366766E+09 | 0.237937E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 74830449.12 | 0.00 | 0.00 | 3530769.56 | 0.00 | 0.162459E+10 | 0.710342E+09 | 0.00 | 0.40 |
February | 63519836.86 | 0.00 | 0.00 | 4501273.05 | 0.00 | 0.128861E+10 | 0.813573E+09 | 0.00 | 0.40 |
March | 0.109207E+09 | 0.00 | 0.00 | 2616462.68 | 0.00 | 0.146159E+10 | 0.838189E+09 | 0.00 | 0.40 |
April | 18399189.82 | 0.00 | 0.00 | 16374018.24 | 0.00 | 0.278221E+09 | 0.199800E+10 | 0.00 | 0.40 |
May | 31107841.11 | 30627.77 | 0.00 | 15283780.92 | 0.00 | 0.275361E+09 | 0.194599E+10 | 0.00 | 0.40 |
June | 21013096.64 | 7808670.73 | 0.00 | 18558037.27 | 0.00 | 22347690.84 | 0.175656E+10 | 0.00 | 0.40 |
July | 10648068.75 | 4322534.22 | 0.00 | 23588537.13 | 0.00 | 5199059.24 | 0.164518E+10 | 0.00 | 0.40 |
August | 2305610.67 | 1565558.01 | 0.00 | 26574495.58 | 45535.10 | 4611445.19 | 0.163610E+10 | 0.00 | 0.40 |
September | 9933420.70 | 390655.32 | 0.00 | 24401951.52 | 0.00 | 19430838.30 | 0.185963E+10 | 0.00 | 0.40 |
October | 63578141.50 | 0.00 | 0.00 | 9559146.13 | 0.00 | 0.666487E+09 | 0.161927E+10 | 0.00 | 0.40 |
November | 69335167.47 | 0.00 | 0.00 | 3158219.63 | 0.00 | 0.137975E+10 | 0.866205E+09 | 0.00 | 0.40 |
December | 87207152.30 | 0.00 | 0.00 | 1027689.84 | 0.00 | 0.200015E+10 | 0.308471E+09 | 0.00 | 0.40 |
Annual Sum or Average | 0.561084E+09 | 14118046.06 | 0.00 | 0.149174E+09 | 45535.10 | 0.902634E+10 | 0.159975E+11 | 0.00 | 0.40 |
Minimum of Months | 2305610.67 | 0.00 | 0.00 | 1027689.84 | 0.00 | 4611445.19 | 0.308471E+09 | 0.00 | 0.40 |
Maximum of Months | 0.109207E+09 | 7808670.73 | 0.00 | 26574495.58 | 45535.10 | 0.200015E+10 | 0.199800E+10 | 0.00 | 0.40 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.376385E+10 | 0.00 | 0.00 | 48883126.66 | 0.00 | 0.00 | 0.421485E+11 | 0.00 | 4.35 |
February | 0.204273E+10 | 0.00 | 0.00 | 45935089.82 | 0.00 | 0.00 | 0.381629E+11 | 0.00 | 4.40 |
March | 0.125859E+10 | 0.00 | 0.00 | 55662250.49 | 0.00 | 0.00 | 0.469881E+11 | 0.00 | 4.49 |
April | 0.577560E+09 | 0.00 | 0.00 | 73454021.83 | 0.00 | 0.00 | 0.506780E+11 | 0.00 | 4.70 |
May | 0.336297E+09 | 0.00 | 0.00 | 81218851.67 | 0.00 | 0.00 | 0.560200E+11 | 0.00 | 4.77 |
June | 55396829.19 | 40870065.34 | 0.00 | 92259641.93 | 0.00 | 0.00 | 0.533483E+11 | 0.00 | 5.00 |
July | 19608832.08 | 1109937.32 | 0.00 | 0.105083E+09 | 0.00 | 0.00 | 0.503250E+11 | 0.00 | 5.05 |
August | 74087299.93 | 0.00 | 0.00 | 0.100721E+09 | 0.00 | 0.00 | 0.479743E+11 | 0.00 | 5.02 |
September | 0.249496E+09 | 0.00 | 0.00 | 83038436.85 | 0.00 | 0.00 | 0.518309E+11 | 0.00 | 4.83 |
October | 0.112748E+10 | 0.00 | 0.00 | 61645618.11 | 0.00 | 0.00 | 0.537414E+11 | 0.00 | 4.58 |
November | 0.228720E+10 | 0.00 | 0.00 | 50599390.28 | 0.00 | 0.00 | 0.472996E+11 | 0.00 | 4.43 |
December | 0.354563E+10 | 0.00 | 0.00 | 47277436.67 | 0.00 | 0.00 | 0.398253E+11 | 0.00 | 4.36 |
Annual Sum or Average | 0.153379E+11 | 41980002.67 | 0.00 | 0.845777E+09 | 0.00 | 0.00 | 0.578342E+12 | 0.00 | 4.67 |
Minimum of Months | 19608832.08 | 0.00 | 0.00 | 45935089.82 | 0.00 | 0.00 | 0.381629E+11 | 0.00 | 4.35 |
Maximum of Months | 0.376385E+10 | 40870065.34 | 0.00 | 0.105083E+09 | 0.00 | 0.00 | 0.560200E+11 | 0.00 | 5.05 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.878291E+09 | 0.00 | 0.00 | 64363794.46 | 0.00 | 0.00 | 0.494579E+11 | 0.00 | 4.77 |
February | 0.362902E+09 | 0.00 | 0.00 | 60550102.36 | 0.00 | 0.00 | 0.437292E+11 | 0.00 | 4.83 |
March | 85525795.17 | 0.00 | 0.00 | 70732864.26 | 0.00 | 0.00 | 0.530466E+11 | 0.00 | 4.94 |
April | 3750457.89 | 0.00 | 0.00 | 87971791.28 | 0.00 | 0.00 | 0.561444E+11 | 0.00 | 5.15 |
May | 6413256.94 | 0.00 | 0.00 | 95327812.88 | 0.00 | 0.00 | 0.616506E+11 | 0.00 | 5.22 |
June | 0.00 | 44492806.19 | 0.00 | 0.105051E+09 | 0.00 | 0.00 | 0.579602E+11 | 0.00 | 5.44 |
July | 0.00 | 1200389.49 | 0.00 | 0.118099E+09 | 0.00 | 0.00 | 0.544580E+11 | 0.00 | 5.47 |
August | 0.00 | 0.00 | 0.00 | 0.114751E+09 | 0.00 | 0.00 | 0.518860E+11 | 0.00 | 5.43 |
September | 13455164.75 | 0.00 | 0.00 | 96800563.97 | 0.00 | 0.00 | 0.566518E+11 | 0.00 | 5.26 |
October | 89225890.49 | 0.00 | 0.00 | 76176389.02 | 0.00 | 0.00 | 0.602051E+11 | 0.00 | 5.03 |
November | 0.356514E+09 | 0.00 | 0.00 | 65465140.09 | 0.00 | 0.00 | 0.540928E+11 | 0.00 | 4.86 |
December | 0.105472E+10 | 0.00 | 0.00 | 63399762.64 | 0.00 | 0.00 | 0.464767E+11 | 0.00 | 4.77 |
Annual Sum or Average | 0.285080E+10 | 45693195.68 | 0.00 | 0.101869E+10 | 0.00 | 0.00 | 0.645759E+12 | 0.00 | 5.10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 60550102.36 | 0.00 | 0.00 | 0.437292E+11 | 0.00 | 4.77 |
Maximum of Months | 0.105472E+10 | 44492806.19 | 0.00 | 0.118099E+09 | 0.00 | 0.00 | 0.616506E+11 | 0.00 | 5.47 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.110253E+09 | 0.00 | 0.00 | 0.703273E+11 | 0.00 | 21.34 |
February | 0.00 | 0.00 | 0.00 | 0.100460E+09 | 0.00 | 0.00 | 0.612874E+11 | 0.00 | 21.60 |
March | 0.00 | 0.00 | 0.00 | 0.106476E+09 | 0.00 | 0.00 | 0.729525E+11 | 0.00 | 21.63 |
April | 0.00 | 0.00 | 0.00 | 0.130013E+09 | 0.00 | 0.00 | 0.759044E+11 | 0.00 | 22.32 |
May | 0.00 | 0.00 | 0.00 | 0.137262E+09 | 0.00 | 0.00 | 0.813096E+11 | 0.00 | 22.33 |
June | 0.00 | 70204444.15 | 0.00 | 0.146396E+09 | 0.00 | 0.00 | 0.697350E+11 | 0.00 | 22.63 |
July | 0.00 | 1954816.70 | 0.00 | 0.163586E+09 | 0.00 | 0.00 | 0.638218E+11 | 0.00 | 22.69 |
August | 0.00 | 0.00 | 0.00 | 0.163651E+09 | 0.00 | 0.00 | 0.600485E+11 | 0.00 | 22.70 |
September | 0.00 | 0.00 | 0.00 | 0.144127E+09 | 0.00 | 0.00 | 0.690898E+11 | 0.00 | 22.55 |
October | 0.00 | 0.00 | 0.00 | 0.115323E+09 | 0.00 | 0.00 | 0.810116E+11 | 0.00 | 21.96 |
November | 0.00 | 0.00 | 0.00 | 0.105144E+09 | 0.00 | 0.00 | 0.746585E+11 | 0.00 | 21.41 |
December | 0.00 | 0.00 | 0.00 | 0.111074E+09 | 0.00 | 0.00 | 0.654467E+11 | 0.00 | 21.28 |
Annual Sum or Average | 0.00 | 72159260.85 | 0.00 | 0.153377E+10 | 0.00 | 0.00 | 0.845593E+12 | 0.00 | 22.04 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.100460E+09 | 0.00 | 0.00 | 0.600485E+11 | 0.00 | 21.28 |
Maximum of Months | 0.00 | 70204444.15 | 0.00 | 0.163651E+09 | 0.00 | 0.00 | 0.813096E+11 | 0.00 | 22.70 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.159836E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110794E+09 | 0.00 | 0.00 | 1.21 |
February | 0.139723E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 17567484.55 | 0.00 | 0.00 | 1.22 |
March | 0.164729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.22 |
April | 0.166773E+11 | 0.00 | 0.00 | 28271.97 | 0.00 | 0.00 | 24470741.59 | 0.00 | 1.22 |
May | 0.179471E+11 | 0.00 | 0.00 | 2660.52 | 0.00 | 0.00 | 16511473.44 | 0.00 | 1.22 |
June | 0.158668E+11 | 0.00 | 0.00 | 101774.48 | 13034614.95 | 0.00 | 49473178.28 | 0.00 | 1.22 |
July | 0.145168E+11 | 370148.26 | 0.00 | 472680.58 | 0.00 | 0.00 | 0.242492E+09 | 0.00 | 1.22 |
August | 0.138925E+11 | 0.00 | 0.00 | 118706.83 | 0.00 | 0.00 | 0.132419E+09 | 0.00 | 1.23 |
September | 0.159523E+11 | 0.00 | 0.00 | 16620.04 | 0.00 | 0.00 | 19718784.75 | 0.00 | 1.22 |
October | 0.182834E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.22 |
November | 0.170584E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.21 |
December | 0.151945E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 56530222.30 | 0.00 | 0.00 | 1.22 |
Annual Sum or Average | 0.191818E+12 | 370148.26 | 0.00 | 740714.43 | 13034614.95 | 0.184892E+09 | 0.485085E+09 | 0.00 | 1.22 |
Minimum of Months | 0.138925E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.21 |
Maximum of Months | 0.182834E+11 | 370148.26 | 0.00 | 472680.58 | 13034614.95 | 0.110794E+09 | 0.242492E+09 | 0.00 | 1.23 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:25:19
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.791326E+11 | 0.794088E+10 | 0.239027E+12 | 0.959222E+12 | 0.744995E+11 |
February | 0.128696E+12 | 0.717122E+10 | 0.214233E+12 | 0.873284E+12 | 0.585873E+11 |
March | 0.165739E+12 | 0.720715E+10 | 0.215218E+12 | 0.884247E+12 | 0.765943E+11 |
April | 0.421031E+12 | 0.593804E+10 | 0.168285E+12 | 0.733738E+12 | 0.158273E+12 |
May | 0.547777E+12 | 0.563844E+10 | 0.163779E+12 | 0.697155E+12 | 0.167959E+12 |
June | 0.555155E+12 | 0.413204E+10 | 0.124008E+12 | 0.515835E+12 | 0.229114E+12 |
July | 0.556757E+12 | 0.382536E+10 | 0.110589E+12 | 0.462265E+12 | 0.286566E+12 |
August | 0.446498E+12 | 0.384402E+10 | 0.103080E+12 | 0.437462E+12 | 0.298472E+12 |
September | 0.325739E+12 | 0.421802E+10 | 0.121479E+12 | 0.519598E+12 | 0.236034E+12 |
October | 0.147478E+12 | 0.575947E+10 | 0.173574E+12 | 0.719504E+12 | 0.128340E+12 |
November | 0.581373E+11 | 0.661726E+10 | 0.201913E+12 | 0.811083E+12 | 0.936920E+11 |
December | 0.193386E+11 | 0.791501E+10 | 0.241620E+12 | 0.965187E+12 | 0.591181E+11 |
Annual Sum or Average | 0.345148E+13 | 0.702069E+11 | 0.207681E+13 | 0.857858E+13 | 0.186725E+13 |
Minimum of Months | 0.193386E+11 | 0.382536E+10 | 0.103080E+12 | 0.437462E+12 | 0.585873E+11 |
Maximum of Months | 0.556757E+12 | 0.794088E+10 | 0.241620E+12 | 0.965187E+12 | 0.298472E+12 |